Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:27
Tabular Output Report in Format: HTML
Building: SchoolPrimary
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2024-07-03 12:28:01
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 4408.87 | 641.66 | 641.66 |
| Net Site Energy | 4408.87 | 641.66 | 641.66 |
| Total Source Energy | 12691.68 | 1847.14 | 1847.14 |
| Net Source Energy | 12691.68 | 1847.14 | 1847.14 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 6871.00 |
| Net Conditioned Building Area | 6871.00 |
| Unconditioned Building Area | 0.00 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 109.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 783.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 1218.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 92.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1151.36 | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 489.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 140.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.47 |
| Refrigeration | 44.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 3798.59 | 610.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.47 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 68.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Boiler | 0.00 | 40.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Cooling | General | 783.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 1218.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 92.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooking | 149.71 | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInFreezer | 31.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInRefrigerator | 23.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | Transformer | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | General | 489.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | General | 0.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Heater | 0.00 | 140.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.99 | |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.48 | |
| Refrigeration | General | 7.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LowTempRefrigeration | 15.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MedTempRefrigeration | 21.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 109.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 783.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 1218.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 92.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 1151.36 | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 489.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 0.00 | 140.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.47 |
| Refrigeration | Unassigned | 44.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 190.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 185.42 | 36.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Other | 176.63 | 52.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 552.84 | 88.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 190.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 185.42 | 36.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Other | 176.63 | 52.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 552.84 | 88.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 3798.588 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 3798.588 | 100.00 |
| Total On-Site and Utility Electric Sources | 3798.588 | 100.00 |
| Total Electricity End Uses | 3798.588 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | |
| Air to Air Heat Recovery for Cooling | 0.00 | |
| Air to Air Heat Recovery for Heating | 0.00 | |
| High-Temperature Geothermal* | 0.00 | |
| Solar Water Thermal | 0.00 | |
| Solar Air Thermal | 0.00 | |
| Total On-Site Thermal Sources | 0.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 718.47 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 718.47 | 100.00 |
| Total Water End Uses | 718.47 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 148.67 |
| Time Setpoint Not Met During Occupied Cooling | 201.50 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1200.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME SCHOOLPRIMARY
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |ZoneHeatingSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |ZoneElectricSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |SpaceGainsMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |PeakSpaceGainsMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |SpaceGainComponentsAtCoolingPeakMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |ComfortReportSimple55Monthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |OccupantComfortDataSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_POD_1 COOLING COIL | PSZ-AC_1:6 COOLING COIL | PSZ-AC_2:7 COOLING COIL |WindowReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 |WindowEnergyReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 |WindowZoneSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |WindowEnergyZoneSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | VAV_POD_1 HEATING COIL | PSZ-AC_1:6 HEATING COIL | PSZ-AC_2:7 HEATING COIL | VAV_POD_1 COOLING COIL | PSZ-AC_1:6 COOLING COIL | PSZ-AC_2:7 COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| VAV_POD_1 FAN | BATH_ZN_1_FLR_1 EXHAUST FAN | GYM_ZN_1_FLR_1 EXHAUST FAN | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN | KITCHEN_ZN_1_FLR_1 EXHAUST FAN | CAFETERIA_ZN_1_FLR_1 EXHAUST FAN | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_POD_1 | PSZ-AC_1:6 | PSZ-AC_2:7 |AirLoopSystemComponentLoadsMonthly
| VAV_POD_1 | PSZ-AC_1:6 | PSZ-AC_2:7 |AirLoopSystemComponentEnergyUseMonthly
| VAV_POD_1 | PSZ-AC_1:6 | PSZ-AC_2:7 |MechanicalVentilationLoadsMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:27 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
| Latitude [deg] | 31.77 |
| Longitude [deg] | -106.5 |
| Elevation [m] | 1186.00 |
| Time Zone | -7.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Above Ground Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Window Opening Area [m2] | 552.60 | 204.13 | 72.16 | 204.16 | 72.16 |
| Gross Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Above Ground Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Above Ground Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Window Opening Area [m2] | 552.60 | 204.13 | 72.16 | 204.16 | 72.16 |
| Gross Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Above Ground Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Total | |
| Gross Roof Area [m2] | 6871.00 |
| Skylight Area [m2] | 13.38 |
| Skylight-Roof Ratio [%] | 0.19 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | Yes | Yes | 768.00 | 1.00 | 12.00 | 0.00 | 2.64 | 2.64 | 5.4810 | 18.58 | 4.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | Yes | Yes | 768.00 | 1.00 | 12.00 | 0.00 | 2.64 | 2.64 | 5.4810 | 18.58 | 4.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | Yes | Yes | 768.00 | 1.00 | 12.00 | 0.00 | 2.64 | 2.64 | 5.4810 | 18.58 | 4.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.57 | 17.57 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1260.00 | 1.00 | 140.00 | 0.00 | 30.80 | 30.80 | 15.0695 | 3.72 | 15.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | Yes | Yes | 648.00 | 1.00 | 72.00 | 0.00 | 15.84 | 15.84 | 15.0695 | 3.72 | 20.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | Yes | Yes | 2184.00 | 1.00 | 36.00 | 0.00 | 7.92 | 7.92 | 5.4810 | 18.58 | 4.0000 |
| LOBBY_ZN_1_FLR_1 | 171.00 | Yes | Yes | 684.00 | 1.00 | 76.00 | 0.00 | 16.72 | 16.72 | 13.9931 | 9.29 | 4.0000 |
| MECH_ZN_1_FLR_1 | 252.00 | Yes | Yes | 1008.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.1458 | 61.93 | 10.0000 |
| BATH_ZN_1_FLR_1 | 190.00 | Yes | Yes | 760.00 | 1.00 | 40.00 | 0.00 | 8.80 | 8.80 | 9.6875 | 18.58 | 4.0000 |
| OFFICES_ZN_1_FLR_1 | 441.00 | Yes | Yes | 1764.00 | 1.00 | 168.00 | 0.00 | 36.96 | 36.96 | 11.8403 | 18.58 | 10.8000 |
| GYM_ZN_1_FLR_1 | 357.00 | Yes | Yes | 1428.00 | 1.00 | 68.00 | 0.00 | 14.96 | 14.96 | 13.3472 | 3.10 | 5.0000 |
| KITCHEN_ZN_1_FLR_1 | 168.00 | Yes | Yes | 672.00 | 1.00 | 32.00 | 0.00 | 7.04 | 7.04 | 12.9167 | 6.22 | 1631.7643 |
| CAFETERIA_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1260.00 | 1.00 | 144.00 | 0.00 | 31.68 | 31.68 | 9.6875 | 0.93 | 25.3900 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | Yes | Yes | 1596.00 | 1.00 | 160.00 | 0.00 | 35.20 | 35.20 | 16.6840 | 9.29 | 15.0000 |
| Total | 6871.00 | 27484.00 | 2512.00 | 0.00 | 552.60 | 552.60 | 12.8652 | 4.37 | 51.7784 | |||
| Conditioned Total | 6871.00 | 27484.00 | 2512.00 | 0.00 | 552.60 | 552.60 | 12.8652 | 4.37 | 51.7784 | |||
| Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | Yes | Yes | 1.00 | CORRIDOR_POD_1_ZN_1_FLR_1 | GENERAL | CORRIDOR_POD_1_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | Yes | Yes | 1.00 | CORRIDOR_POD_2_ZN_1_FLR_1 | GENERAL | CORRIDOR_POD_2_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | Yes | Yes | 1.00 | CORRIDOR_POD_3_ZN_1_FLR_1 | GENERAL | CORRIDOR_POD_3_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | Yes | Yes | 1.00 | COMPUTER_CLASS_ZN_1_FLR_1 | GENERAL | COMPUTER_CLASS_ZN_1_FLR_1 | 15.0695 | 3.72 | 20.0000 | |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | Yes | Yes | 1.00 | MAIN_CORRIDOR_ZN_1_FLR_1 | GENERAL | MAIN_CORRIDOR_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| LOBBY_ZN_1_FLR_1 | 171.00 | Yes | Yes | 1.00 | LOBBY_ZN_1_FLR_1 | GENERAL | LOBBY_ZN_1_FLR_1 | 13.9931 | 9.29 | 4.0000 | |
| MECH_ZN_1_FLR_1 | 252.00 | Yes | Yes | 1.00 | MECH_ZN_1_FLR_1 | GENERAL | MECH_ZN_1_FLR_1 | 16.1458 | 61.93 | 10.0000 | |
| BATH_ZN_1_FLR_1 | 190.00 | Yes | Yes | 1.00 | BATH_ZN_1_FLR_1 | GENERAL | BATH_ZN_1_FLR_1 | 9.6875 | 18.58 | 4.0000 | |
| OFFICES_ZN_1_FLR_1 | 441.00 | Yes | Yes | 1.00 | OFFICES_ZN_1_FLR_1 | GENERAL | OFFICES_ZN_1_FLR_1 | 11.8403 | 18.58 | 10.8000 | |
| GYM_ZN_1_FLR_1 | 357.00 | Yes | Yes | 1.00 | GYM_ZN_1_FLR_1 | GENERAL | GYM_ZN_1_FLR_1 | 13.3472 | 3.10 | 5.0000 | |
| KITCHEN_ZN_1_FLR_1 | 168.00 | Yes | Yes | 1.00 | KITCHEN_ZN_1_FLR_1 | GENERAL | KITCHEN_ZN_1_FLR_1 | 12.9167 | 6.22 | 1631.7643 | |
| CAFETERIA_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1.00 | CAFETERIA_ZN_1_FLR_1 | GENERAL | CAFETERIA_ZN_1_FLR_1 | 9.6875 | 0.93 | 25.3900 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | Yes | Yes | 1.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | GENERAL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 16.6840 | 9.29 | 15.0000 | |
| Total | 6871.00 | 12.8652 | 2.19 | 51.7784 | |||||||
| Conditioned Total | 6871.00 | 12.8652 | 2.19 | 51.7784 | |||||||
| Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 6871.00 | 6871.00 | 0.00 | 0.00 | 12.8652 | 4.37 | 51.7784 |
| Total | 6871.00 | 6871.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 15-JUN-14:00 | 27-DEC-08:09 | - | - | - | - | - | - | - | - | - | - | 02-JAN-13:09 |
| Heating | 0.00 | 328211.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 178587.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 79557.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 70814.97 | 36063.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 1156.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 55176.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 13.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 11337.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 1379.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 386685.11 | 375612.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 204979.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Boiler | 0.00 | 123231.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Cooling | General | 178587.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 79557.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 65099.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooking | 3999.34 | 36063.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInFreezer | 986.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInRefrigerator | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | Transformer | 1156.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | General | 55176.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | General | 13.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Heater | 0.00 | 11337.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 241.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LowTempRefrigeration | 430.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MedTempRefrigeration | 707.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 118.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 2482.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 3858.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 293.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 3646.35 | 391.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 55.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 1551.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 151.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 141.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 12030.13 | 661.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 17.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 361.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 561.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 42.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 530.69 | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 8.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 225.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 22.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 20.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1750.86 | 96.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 17.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 361.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 561.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 42.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 530.69 | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 8.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 225.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 22.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 20.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1750.86 | 96.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
AirTerminal:SingleDuct:VAV:Reheat| Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 0.755250 | 0.099885 | 0.390000 | 0.294547 | 0.390000 | 0.500000 | 0.003814 | 0.000055 | 0.304853 | 12.89 | 0.008000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 3.07 | 0.118397 | 0.462000 | 1.42 | 0.462000 | 0.500000 | 0.003218 | 0.000207 | 1.42 | 12.89 | 0.008000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 0.659745 | 0.221759 | 0.300000 | 0.197923 | 0.591356 | 0.500000 | 0.001718 | 0.000054 | 0.300956 | 12.89 | 0.008000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 0.732435 | 0.102996 | 0.402000 | 0.294439 | 0.402000 | 0.500000 | 0.003699 | 0.000054 | 0.304248 | 12.89 | 0.008000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 2.91 | 0.124800 | 0.487000 | 1.42 | 0.487000 | 0.500000 | 0.003053 | 0.000206 | 1.42 | 12.89 | 0.008000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 0.749138 | 0.100700 | 0.393000 | 0.294411 | 0.393000 | 0.500000 | 0.003784 | 0.000054 | 0.302370 | 12.89 | 0.008000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 3.03 | 0.119930 | 0.468000 | 1.42 | 0.468000 | 0.500000 | 0.003177 | 0.000205 | 1.42 | 12.89 | 0.008000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 0.657818 | 0.222408 | 0.300000 | 0.197345 | 0.593088 | 0.500000 | 0.001713 | 0.000054 | 0.300105 | 12.89 | 0.008000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 0.732847 | 0.102938 | 0.402000 | 0.294604 | 0.402000 | 0.500000 | 0.003701 | 0.000055 | 0.304452 | 12.89 | 0.008000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 2.91 | 0.124727 | 0.487000 | 1.42 | 0.487000 | 0.500000 | 0.003055 | 0.000206 | 1.42 | 12.89 | 0.008000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 0.749785 | 0.100613 | 0.393000 | 0.294665 | 0.393000 | 0.500000 | 0.003787 | 0.000054 | 0.302640 | 12.89 | 0.008000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 3.04 | 0.119419 | 0.466000 | 1.42 | 0.466000 | 0.500000 | 0.003190 | 0.000206 | 1.42 | 12.89 | 0.008000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 0.663451 | 0.220520 | 0.300000 | 0.199035 | 0.588053 | 0.500000 | 0.001728 | 0.000054 | 0.300449 | 12.89 | 0.008000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 0.738294 | 0.102179 | 0.399000 | 0.294579 | 0.399000 | 0.500000 | 0.003729 | 0.000055 | 0.306415 | 12.89 | 0.008000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 1.96 | 0.122390 | 0.478000 | 0.937445 | 0.478000 | 0.500000 | 0.003113 | 0.000138 | 0.937445 | 12.89 | 0.008000 |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | 1.08 | 0.114786 | 0.448000 | 0.481790 | 0.448000 | 0.500000 | 0.003319 | 0.000068 | 0.481790 | 12.89 | 0.008000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | 1.46 | 0.284631 | 0.300000 | 0.438517 | 0.759016 | 0.500000 | 0.001339 | 0.000127 | 0.710262 | 12.89 | 0.008000 |
| LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | 0.778226 | 0.167435 | 0.300000 | 0.233468 | 0.446492 | 0.500000 | 0.002276 | 0.000074 | 0.411398 | 12.89 | 0.008000 |
| MECH_ZN_1_FLR_1 VAV BOX COMPONENT | 0.992858 | 0.193405 | 0.300000 | 0.297857 | 0.515747 | 0.500000 | 0.001970 | 0.000042 | 0.297857 | 12.89 | 0.008000 |
| BATH_ZN_1_FLR_1 VAV BOX COMPONENT | 0.680665 | 0.212704 | 0.300000 | 0.204199 | 0.567210 | 0.500000 | 0.001791 | 0.000058 | 0.322332 | 12.89 | 0.008000 |
| OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | 1.97 | 0.454767 | 0.500000 | 0.002234 | 0.000157 | 0.879302 | 12.89 | 0.008000 | |||
| GYM_ZN_1_FLR_1 VAV BOX COMPONENT | 2.22 | 0.122762 | 0.389000 | 0.862001 | 0.389000 | 0.500000 | 0.003104 | 0.000131 | 0.862001 | 12.89 | 0.008000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | 2.19 | 0.138772 | 0.300000 | 0.657275 | 0.370059 | 0.500000 | 0.002746 | 0.000137 | 0.764803 | 12.89 | 0.008000 |
| Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6239.73 | 0.000055 | 145.54 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23701.48 | 0.000207 | 526.41 |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6160.48 | 0.000054 | 143.69 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6227.36 | 0.000054 | 145.25 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23567.05 | 0.000206 | 522.79 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6188.91 | 0.000054 | 144.35 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23475.68 | 0.000205 | 520.34 |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6143.06 | 0.000054 | 143.29 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6231.53 | 0.000055 | 145.35 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23584.97 | 0.000206 | 523.21 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6194.43 | 0.000054 | 144.48 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23522.17 | 0.000206 | 521.59 |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6150.10 | 0.000054 | 143.45 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6271.71 | 0.000055 | 146.28 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 15798.61 | 0.000138 | 351.52 |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | 7801.17 | 0.000068 | 172.13 |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | 14538.81 | 0.000127 | 339.12 |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | 8420.75 | 0.000074 | 196.41 |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 4800.60 | 0.000042 | 105.83 |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6597.84 | 0.000058 | 153.89 |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | 17998.03 | 0.000157 | 419.80 |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | 15000.73 | 0.000131 | 336.11 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | 15654.30 | 0.000137 | 365.13 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| KITCHEN_ZN_1_FLR_1 DIRECT AIR | 1.83 |
| CAFETERIA_ZN_1_FLR_1 DIRECT AIR | 3.24 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| VAV_POD_1 | 17.37 | 14.16 | 34.74 | 14.16 | 34.59 | 34.59 | 0.300000 | 0.409318 | 34.59 |
| PSZ-AC_1:6 | 1.83 | 1.83 | 1.83 | 1.83 | 1.83 | 1.83 | 1.00 | 1.00 | 1.83 |
| PSZ-AC_2:7 | 3.24 | 3.24 | 3.24 | 3.24 | 3.24 | 3.24 | 1.00 | 1.00 | 3.24 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| VAV_POD_1_OA_CONTROLLER | 34.59 | |
| PSZ-AC_1:6_OA_CONTROLLER | 1.83 | 0.254814 |
| PSZ-AC_2:7_OA_CONTROLLER | 3.24 | 1.49 |
| Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
| VAV_POD_1 COOLING COIL | 34.59 | 710881.76 | 0.765123 | 11.53 | 236936.89 | 0.765123 |
| Design Size Nominal Capacity [W] | |
| VAV_POD_1 HEATING COIL | 196976.23 |
| PSZ-AC_1:6 HEATING COIL | 63053.79 |
| PSZ-AC_2:7 HEATING COIL | 78718.84 |
| Design Size Maximum Flow Rate [m3/s] | |
| VAV_POD_1 FAN | 34.59 |
| Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
| PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.83 | 3041.40 |
| PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | 3.24 | 5259.43 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| PSZ-AC_1:6_UNITARY_PACKAGE_DX | 1.83 | 1.83 | 1.83 | 1.83 | 39311.76 | 63053.79 | 32.11 | 1.00 |
| PSZ-AC_2:7_UNITARY_PACKAGE_DX | 3.24 | 3.24 | 3.24 | 3.24 | 79630.46 | 78718.84 | 32.11 | 1.00 |
| User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
| PSZ-AC_1:6 COOLING COIL | 1.83 | 0.914983 | 1.22 | 39311.76 | 19655.88 | 0.749300 | 0.749300 |
| PSZ-AC_2:7 COOLING COIL | 3.24 | 1.62 | 2.16 | 79630.46 | 39815.23 | 0.704800 | 0.704800 |
| Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
| HEATSYS1 | 0.002452 | 0.294230 |
| SWHSYS1 | 0.000105 | 0.012650 |
| Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
| HEATSYS1 PUMP | 0.002452 | 738.41 | 0.000000 |
| Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
| HEATSYS1 BOILER | 280269.52 | 280269.52 | 0.002452 |
| Design Flow Rate [m3/s] | Design Power Consumption [W] | |
| SWHSYS1 PUMP | 0.000105 | 13.47 |
| Use Side Design Flow Rate [m3/s] | |
| SWHSYS1 WATER HEATER | 0.000105 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| Possible Shadow Receivers | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | BATH_ZN_1_FLR_1_WALL_5 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | BATH_ZN_1_FLR_1_WALL_5 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | |
| BATH_ZN_1_FLR_1_WALL_5 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | |
| CAFETERIA_ZN_1_FLR_1_WALL_3 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | CAFETERIA_ZN_1_FLR_1_WALL_3 | |
| Possible Shadow Receivers | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | |
| LOBBY_ZN_1_FLR_1_WALL_1 | LOBBY_ZN_1_FLR_1_WALL_1_DOOR | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| BATH_ZN_1_FLR_1_WALL_5 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | |
| OFFICES_ZN_1_FLR_1_WALL_1 | OFFICES_ZN_1_FLR_1_WALL_1_DOOR | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| OFFICES_ZN_1_FLR_1_WALL_2 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | |
| GYM_ZN_1_FLR_1_WALL_2 | GYM_ZN_1_FLR_1_WALL_2_DOOR | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | |
| GYM_ZN_1_FLR_1_CEILING | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | |
| KITCHEN_ZN_1_FLR_1_WALL_2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | |
| CAFETERIA_ZN_1_FLR_1_WALL_2 | CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | |
| CAFETERIA_ZN_1_FLR_1_WALL_3 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | Yes | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 17.94 | 21.10 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | SchoolPrimary | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 25 | 288 | 92 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.0 | -64.00 | 0.00 | 0.00 | -58.50 | 4.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 0.00 | 9.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 0.0 | -53.00 | 0.00 | 0.00 | -26.50 | 4.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 0.00 | 9.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | 0.0 | -64.00 | 9.00 | 0.00 | -32.00 | 10.50 | 2.00 | 1 | 1 | 1 | -64.00 | 0.00 | 9.00 | 12.00 | 0.00 | 4.00 | 4.00 | 768.00 | TARP | TARP | 192.00 | 12.00 | 9.36 | 2.64 | 8 | 1 | 0 | Yes |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.0 | -64.00 | 12.00 | 0.00 | -58.50 | 16.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 12.00 | 21.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 0.0 | -53.00 | 12.00 | 0.00 | -26.50 | 16.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 12.00 | 21.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.0 | -64.00 | 30.00 | 0.00 | -58.50 | 34.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 30.00 | 39.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 0.0 | -53.00 | 30.00 | 0.00 | -26.50 | 34.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 30.00 | 39.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | 0.0 | -64.00 | 39.00 | 0.00 | -32.00 | 40.50 | 2.00 | 1 | 1 | 1 | -64.00 | 0.00 | 39.00 | 42.00 | 0.00 | 4.00 | 4.00 | 768.00 | TARP | TARP | 192.00 | 12.00 | 9.36 | 2.64 | 8 | 1 | 0 | Yes |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.0 | -64.00 | 42.00 | 0.00 | -58.50 | 46.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 42.00 | 51.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 0.0 | -53.00 | 42.00 | 0.00 | -26.50 | 46.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 42.00 | 51.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.0 | -64.00 | 61.00 | 0.00 | -58.50 | 65.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 61.00 | 70.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 0.0 | -53.00 | 61.00 | 0.00 | -26.50 | 65.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 61.00 | 70.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | 0.0 | -64.00 | 70.00 | 0.00 | -32.00 | 71.50 | 2.00 | 1 | 1 | 1 | -64.00 | 0.00 | 70.00 | 73.00 | 0.00 | 4.00 | 4.00 | 768.00 | TARP | TARP | 192.00 | 12.00 | 9.36 | 2.64 | 9 | 1 | 0 | Yes |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.0 | -64.00 | 73.00 | 0.00 | -58.50 | 77.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 73.00 | 82.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.48 | 17.57 | 6 | 4 | 0 | Yes |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.0 | -53.00 | 73.00 | 0.00 | -35.50 | 77.50 | 2.00 | 1 | 1 | 1 | -53.00 | -18.00 | 73.00 | 82.00 | 0.00 | 4.00 | 4.00 | 1260.00 | TARP | TARP | 315.00 | 140.00 | 105.30 | 30.80 | 6 | 5 | 0 | Yes |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | 0.0 | -18.00 | 73.00 | 0.00 | -9.00 | 77.50 | 2.00 | 1 | 1 | 1 | -18.00 | 0.00 | 73.00 | 82.00 | 0.00 | 4.00 | 4.00 | 648.00 | TARP | TARP | 162.00 | 72.00 | 54.21 | 15.84 | 6 | 3 | 0 | Yes |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | 0.0 | 0.00 | 9.00 | 0.00 | 6.50 | 30.00 | 2.00 | 1 | 1 | 1 | 0.00 | 13.00 | 9.00 | 51.00 | 0.00 | 4.00 | 4.00 | 2184.00 | TARP | TARP | 546.00 | 36.00 | 26.13 | 7.92 | 11 | 3 | 0 | Yes |
| 18 | LOBBY_ZN_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 9.50 | 4.50 | 2.00 | 1 | 1 | 1 | 0.00 | 19.00 | 0.00 | 9.00 | 0.00 | 4.00 | 4.00 | 684.00 | TARP | TARP | 171.00 | 76.00 | 57.33 | 16.72 | 7 | 3 | 0 | Yes |
| 19 | MECH_ZN_1_FLR_1 | 0.0 | 13.00 | 9.00 | 0.00 | 16.00 | 30.00 | 2.00 | 1 | 1 | 1 | 13.00 | 19.00 | 9.00 | 51.00 | 0.00 | 4.00 | 4.00 | 1008.00 | TARP | TARP | 252.00 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
| 20 | BATH_ZN_1_FLR_1 | 0.0 | 0.00 | 51.00 | 0.00 | 9.50 | 56.00 | 2.00 | 1 | 1 | 1 | 0.00 | 19.00 | 51.00 | 61.00 | 0.00 | 4.00 | 4.00 | 760.00 | TARP | TARP | 190.00 | 40.00 | 31.20 | 8.80 | 7 | 1 | 0 | Yes |
| 21 | OFFICES_ZN_1_FLR_1 | 0.0 | 19.00 | 0.00 | 0.00 | 29.50 | 10.50 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 0.00 | 21.00 | 0.00 | 4.00 | 4.00 | 1764.00 | TARP | TARP | 441.00 | 168.00 | 129.09 | 36.96 | 7 | 4 | 0 | Yes |
| 22 | GYM_ZN_1_FLR_1 | 0.0 | 19.00 | 21.00 | 0.00 | 29.50 | 29.50 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 21.00 | 38.00 | 0.00 | 4.00 | 4.00 | 1428.00 | TARP | TARP | 357.00 | 68.00 | 51.09 | 28.34 | 6 | 12 | 0 | Yes |
| 23 | KITCHEN_ZN_1_FLR_1 | 0.0 | 19.00 | 38.00 | 0.00 | 29.50 | 42.00 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 38.00 | 46.00 | 0.00 | 4.00 | 4.00 | 672.00 | TARP | TARP | 168.00 | 32.00 | 24.96 | 7.04 | 6 | 1 | 0 | Yes |
| 24 | CAFETERIA_ZN_1_FLR_1 | 0.0 | 19.00 | 46.00 | 0.00 | 29.50 | 53.50 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 46.00 | 61.00 | 0.00 | 4.00 | 4.00 | 1260.00 | TARP | TARP | 315.00 | 144.00 | 110.37 | 31.68 | 7 | 4 | 0 | Yes |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.0 | 0.00 | 61.00 | 0.00 | 9.50 | 71.50 | 2.00 | 1 | 1 | 1 | 0.00 | 19.00 | 61.00 | 82.00 | 0.00 | 4.00 | 4.00 | 1596.00 | TARP | TARP | 399.00 | 160.00 | 122.85 | 35.20 | 8 | 4 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 3.716 | 0.269 | 15.069 | 20.000 | 0.000 | 0.000 | 0.000 | 0.000 | 35.069 | No |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 18 | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 9.289 | 0.108 | 13.993 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.993 | No |
| 19 | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 61.932 | 1.615E-002 | 16.146 | 10.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26.146 | No |
| 20 | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 18.578 | 5.383E-002 | 9.688 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.688 | No |
| 21 | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 18.579 | 5.382E-002 | 11.840 | 10.800 | 0.000 | 0.000 | 0.000 | 0.000 | 22.640 | No |
| 22 | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 3.096 | 0.323 | 13.347 | 5.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.347 | No |
| 23 | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 6.224 | 0.161 | 12.917 | 200.664 | 1431.100 | 0.000 | 0.000 | 0.000 | 1644.681 | No |
| 24 | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 0.929 | 1.076 | 9.688 | 25.390 | 0.000 | 0.000 | 0.000 | 0.000 | 35.078 | No |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 9.289 | 0.108 | 16.684 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 31.684 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 10.3 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 10.3 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 10.3 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 84.8 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 81 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | BLDG_OCC_SCH_EXTEND | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 43.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 41 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 17 | MECH_ZN_1_FLR_1 | BLDG_OCC_SCH | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 4.1 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 4 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 18 | BATH_ZN_1_FLR_1 | BLDG_OCC_SCH | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 10.2 | 5.383E-002 | 18.578 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 19 | OFFICES_ZN_1_FLR_1 | BLDG_OCC_SCH_OFFICES_W_SB | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 23.7 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 23 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 20 | GYM_ZN_1_FLR_1 | BLDG_OCC_SCH_GYM | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 115.3 | 0.323 | 3.096 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 110 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 21 | KITCHEN_ZN_1_FLR_1 | BLDG_OCC_SCH | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 27.0 | 0.161 | 6.224 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 26 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 22 | CAFETERIA_ZN_1_FLR_1 | BLDG_OCC_SCH_CAFETERIA | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 339.1 | 1.076 | 0.929 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 322 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 23 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | BLDG_OCC_SCH | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 43.0 | 0.108 | 9.289 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 41 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 24 | MAIN_CORRIDOR_ZN_1_FLR_1 | BLDG_OCC_SCH | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 29.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 25 | LOBBY_ZN_1_FLR_1 | BLDG_OCC_SCH | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 18.4 | 0.108 | 9.289 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 1052.352 | 5.481 | 101.834 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1052.352 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 1052.352 | 5.481 | 101.834 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1052.352 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 1052.352 | 5.481 | 101.834 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1052.352 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 4746.880 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 4746.880 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1_LIGHTS | LTG_SCH_COMPUTER_ROOM | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 2441.253 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2441.253 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 2992.626 | 5.481 | 101.832 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2992.626 |
| 18 | LOBBY_ZN_1_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 2392.815 | 13.993 | 129.988 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2392.815 |
| 19 | MECH_ZN_1_FLR_1_LIGHTS | LTG_SCH_MECHANICAL | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 4068.754 | 16.146 | 999.940 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 4068.754 |
| 20 | BATH_ZN_1_FLR_1_LIGHTS | LTG_SCH_BATH | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 1840.627 | 9.688 | 179.977 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1840.627 |
| 21 | OFFICES_ZN_1_FLR_1_LIGHTS | LTG_SCH_OFFICE | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 5221.568 | 11.840 | 219.981 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 5221.568 |
| 22 | GYM_ZN_1_FLR_1_LIGHTS | LTG_SCH_GYM | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 4764.965 | 13.347 | 41.323 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 4764.965 |
| 23 | KITCHEN_ZN_1_FLR_1_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 2170.002 | 12.917 | 80.391 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2170.002 |
| 24 | CAFETERIA_ZN_1_FLR_1_LIGHTS | LTG_SCH_CAFETERIA | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 3051.566 | 9.688 | 9.000 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 3051.566 |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_LIGHTS | LTG_SCH_LIBRARY | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 6656.932 | 16.684 | 154.978 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 6656.932 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 768.000 | 4.000 | 74.318 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 149.700 | 729.600 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 768.000 | 4.000 | 74.318 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 149.700 | 729.600 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 768.000 | 4.000 | 74.318 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 149.700 | 729.600 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 4725.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 921.003 | 4488.750 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 3240.000 | 20.000 | 74.320 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 631.545 | 3078.000 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 2184.000 | 4.000 | 74.316 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 425.708 | 2074.800 |
| 18 | LOBBY_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 684.000 | 4.000 | 37.158 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 133.326 | 649.800 |
| 19 | MECH_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 2520.000 | 10.000 | 619.317 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 491.202 | 2394.000 |
| 20 | BATH_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 760.000 | 4.000 | 74.313 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 148.140 | 722.000 |
| 21 | OFFICES_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 4762.800 | 10.800 | 200.653 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 928.371 | 4524.660 |
| 22 | GYM_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 1785.000 | 5.000 | 15.480 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 347.935 | 1695.750 |
| 23 | KITCHEN_ZN_1_FLR_1_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 31995.600 | 190.450 | 1185.330 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 3199.560 | 7998.900 |
| 24 | KITCHEN_ZN_1_FLR_1_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 986.000 | 5.869 | 36.528 | 0.000 | 0.000 | 1.000 | 0.000 | ReachInFreezer | 986.000 | 986.000 |
| 25 | KITCHEN_ZN_1_FLR_1_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 730.000 | 4.345 | 27.044 | 0.000 | 0.000 | 1.000 | 0.000 | ReachInRefrigerator | 730.000 | 730.000 |
| 26 | CAFETERIA_ZN_1_FLR_1_PLUGMISC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 7997.850 | 25.390 | 23.587 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 799.785 | 1999.463 |
| 27 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 5985.000 | 15.000 | 139.335 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1166.604 | 5685.750 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | KITCHEN_ZN_1_FLR_1_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 240424.800 | 1431.100 | 8906.931 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 4808.496 | 48084.960 |
| Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
| 1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
| 2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 6 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 7 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 8 | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1980E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 9 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 10 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 11 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 12 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 13 | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1980E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 14 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 15 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 46 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 16 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 47 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 17 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 48 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 18 | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1980E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 19 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 20 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 21 | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR | 52 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 22 | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR | 53 | 2 | 7 | 0.167 | 0.2090E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 23 | LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR | 54 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 24 | MECH_ZN_1_FLR_1_FLOOR_FFACTOR | 55 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 25 | BATH_ZN_1_FLR_1_FLOOR_FFACTOR | 56 | 2 | 7 | 0.167 | 0.6720E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 26 | OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR | 57 | 2 | 7 | 0.167 | 0.1226 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 27 | GYM_ZN_1_FLR_1_FLOOR_FFACTOR | 58 | 2 | 7 | 0.167 | 0.6074E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 28 | KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR | 59 | 2 | 7 | 0.167 | 0.6074E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 29 | CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR | 60 | 2 | 7 | 0.167 | 0.1477 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 30 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR | 61 | 2 | 7 | 0.167 | 0.1292 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
| 1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
| 2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
| 3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
| 4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
| 5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
| 6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
| 7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
| 8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
| 9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
| 11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 50.42 |
| 17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 50.42 |
| 27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 32 | ~FC_Insulation_11 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 34 | ~FC_Insulation_12 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 36 | ~FC_Insulation_13 | 0.0000 | 0.000 | 0.000 | 0.000 | 50.42 |
| 37 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 38 | ~FC_Insulation_14 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 39 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 40 | ~FC_Insulation_15 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 41 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 42 | ~FC_Insulation_16 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 43 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 44 | ~FC_Insulation_17 | 0.0000 | 0.000 | 0.000 | 0.000 | 47.78 |
| 45 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 46 | ~FC_Insulation_18 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 47 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 48 | ~FC_Insulation_19 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
| 49 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 50 | ~FC_Insulation_20 | 0.0000 | 0.000 | 0.000 | 0.000 | 14.80 |
| 51 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 52 | ~FC_Insulation_21 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.077 |
| 53 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 54 | ~FC_Insulation_22 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.39 |
| 55 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 56 | ~FC_Insulation_23 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.39 |
| 57 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 58 | ~FC_Insulation_24 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.693 |
| 59 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 60 | ~FC_Insulation_25 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.662 |
| 61 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| Time | Outside | Cross | Inside | Flux (except final one) | |
| 1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
| 2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
| 3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
| 4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
| 5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
| 6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
| 7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
| 8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
| 9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
| 10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
| 11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
| 12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
| 13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
| 14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
| 15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
| 16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
| 17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
| 18 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
| 19 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
| 20 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
| 21 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
| 22 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
| 23 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
| 24 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
| 25 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
| 26 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
| 27 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
| 28 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
| 29 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
| 30 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 31 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 32 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 33 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 34 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 35 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 36 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 37 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 38 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 39 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 40 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 41 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 42 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 43 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 44 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 45 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 46 | 7 | -0.21707302E-07 | -0.21810081E-14 | -0.84952625E-14 | 0.13770899E-15 |
| 47 | 6 | 0.21407607E-05 | 0.45739277E-09 | 0.32038929E-02 | -0.26876939E-04 |
| 48 | 5 | -0.77205346E-04 | 0.24803070E-06 | -0.22452059 | 0.19631768E-02 |
| 49 | 4 | 0.12599243E-02 | 0.10780209E-04 | 4.8427850 | -0.45392265E-01 |
| 50 | 3 | -0.93942915E-02 | 0.82583168E-04 | -38.096111 | 0.39947953 |
| 51 | 2 | 0.30967349E-01 | 0.13253122E-03 | 116.62920 | -1.4198824 |
| 52 | 1 | -0.43132160E-01 | 0.38654114E-04 | -143.99276 | 2.0504445 |
| 53 | 0 | 0.20639933E-01 | 0.87079362E-06 | 60.838472 | |
| 54 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 55 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 56 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 57 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 58 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 59 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 60 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 61 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 62 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 63 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 64 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 65 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 66 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 67 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 68 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 69 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 70 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 71 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 72 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 73 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 74 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 75 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 76 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 77 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 78 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 79 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 80 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 81 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 82 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 83 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 84 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 85 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 86 | 7 | -0.21707302E-07 | -0.21810081E-14 | -0.84952625E-14 | 0.13770899E-15 |
| 87 | 6 | 0.21407607E-05 | 0.45739277E-09 | 0.32038929E-02 | -0.26876939E-04 |
| 88 | 5 | -0.77205346E-04 | 0.24803070E-06 | -0.22452059 | 0.19631768E-02 |
| 89 | 4 | 0.12599243E-02 | 0.10780209E-04 | 4.8427850 | -0.45392265E-01 |
| 90 | 3 | -0.93942915E-02 | 0.82583168E-04 | -38.096111 | 0.39947953 |
| 91 | 2 | 0.30967349E-01 | 0.13253122E-03 | 116.62920 | -1.4198824 |
| 92 | 1 | -0.43132160E-01 | 0.38654114E-04 | -143.99276 | 2.0504445 |
| 93 | 0 | 0.20639933E-01 | 0.87079362E-06 | 60.838472 | |
| 94 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 95 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 96 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 97 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 98 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 99 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 100 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 101 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 102 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 103 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 104 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 105 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 106 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 107 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 108 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 109 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 110 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 111 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 112 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 113 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 114 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 115 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 116 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 117 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 118 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 119 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 120 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 121 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 122 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 123 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 124 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 125 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 126 | 7 | -0.21707302E-07 | -0.21810081E-14 | -0.84952625E-14 | 0.13770899E-15 |
| 127 | 6 | 0.21407607E-05 | 0.45739277E-09 | 0.32038929E-02 | -0.26876939E-04 |
| 128 | 5 | -0.77205346E-04 | 0.24803070E-06 | -0.22452059 | 0.19631768E-02 |
| 129 | 4 | 0.12599243E-02 | 0.10780209E-04 | 4.8427850 | -0.45392265E-01 |
| 130 | 3 | -0.93942915E-02 | 0.82583168E-04 | -38.096111 | 0.39947953 |
| 131 | 2 | 0.30967349E-01 | 0.13253122E-03 | 116.62920 | -1.4198824 |
| 132 | 1 | -0.43132160E-01 | 0.38654114E-04 | -143.99276 | 2.0504445 |
| 133 | 0 | 0.20639933E-01 | 0.87079362E-06 | 60.838472 | |
| 134 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 135 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 136 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 137 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 138 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 139 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 140 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 141 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 142 | 7 | -0.29578731E-08 | -0.18610472E-14 | 0.16360026E-14 | -0.48190060E-16 |
| 143 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 144 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 145 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 146 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 147 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 148 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 149 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 150 | 7 | -0.29578731E-08 | -0.18610472E-14 | 0.16360026E-14 | -0.48190060E-16 |
| 151 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 152 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 153 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 154 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 155 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 156 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 157 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 158 | 7 | -0.20570949E-07 | -0.14658537E-14 | -0.76832012E-14 | 0.12671469E-15 |
| 159 | 6 | 0.20860838E-05 | 0.47270270E-09 | 0.32038024E-02 | -0.26876180E-04 |
| 160 | 5 | -0.77354338E-04 | 0.25871613E-06 | -0.22451551 | 0.19631320E-02 |
| 161 | 4 | 0.12908389E-02 | 0.11299182E-04 | 4.8427016 | -0.45391462E-01 |
| 162 | 3 | -0.97548753E-02 | 0.86890235E-04 | -38.095646 | 0.39947438 |
| 163 | 2 | 0.32375441E-01 | 0.13995703E-03 | 116.62830 | -1.4198704 |
| 164 | 1 | -0.45248243E-01 | 0.40996175E-04 | -143.99224 | 2.0504359 |
| 165 | 0 | 0.21692461E-01 | 0.93166815E-06 | 60.838472 | |
| 166 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 167 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 168 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 169 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 170 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 171 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 172 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 173 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 174 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
| 175 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
| 176 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
| 177 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
| 178 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
| 179 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
| 180 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
| 181 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
| 182 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 | |
| 183 | 7 | -0.63667935E-08 | -0.10874325E-13 | 0.11269204E-14 | -0.19557179E-16 |
| 184 | 6 | 0.22887183E-05 | 0.12967685E-08 | 0.32001644E-02 | -0.26845660E-04 |
| 185 | 5 | -0.14389595E-03 | 0.76205050E-06 | -0.22430950 | 0.19613133E-02 |
| 186 | 4 | 0.31719958E-02 | 0.34552480E-04 | 4.8392847 | -0.45358602E-01 |
| 187 | 3 | -0.27412176E-01 | 0.27382890E-03 | -38.076416 | 0.39926170 |
| 188 | 2 | 0.96706121E-01 | 0.45412367E-03 | 116.59097 | -1.4193709 |
| 189 | 1 | -0.13917125 | 0.13776341E-03 | -143.97030 | 2.0500753 |
| 190 | 0 | 0.67751290E-01 | 0.33403087E-05 | 60.838472 | |
| 191 | 7 | -0.34692083E-08 | -0.29835039E-14 | 0.22457095E-14 | -0.46878358E-16 |
| 192 | 6 | 0.35887165E-05 | 0.23456121E-08 | 0.31958645E-02 | -0.26809589E-04 |
| 193 | 5 | -0.24929292E-03 | 0.13860889E-05 | -0.22406525 | 0.19591573E-02 |
| 194 | 4 | 0.56768486E-02 | 0.63026314E-04 | 4.8352193 | -0.45319520E-01 |
| 195 | 3 | -0.49670058E-01 | 0.50068761E-03 | -38.053464 | 0.39900799 |
| 196 | 2 | 0.17611533 | 0.83223021E-03 | 116.54632 | -1.4187736 |
| 197 | 1 | -0.25403345 | 0.25321776E-03 | -143.94402 | 2.0496434 |
| 198 | 0 | 0.12381374 | 0.61501487E-05 | 60.838472 | |
| 199 | 7 | -0.70485818E-08 | -0.82048821E-14 | -0.11525862E-14 | 0.12346975E-16 |
| 200 | 6 | 0.21636134E-05 | 0.11761400E-08 | 0.32006654E-02 | -0.26849864E-04 |
| 201 | 5 | -0.13228193E-03 | 0.68999669E-06 | -0.22433795 | 0.19615643E-02 |
| 202 | 4 | 0.28871477E-02 | 0.31257738E-04 | 4.8397578 | -0.45363150E-01 |
| 203 | 3 | -0.24853202E-01 | 0.24753724E-03 | -38.079085 | 0.39929121 |
| 204 | 2 | 0.87536903E-01 | 0.41023195E-03 | 116.59616 | -1.4194403 |
| 205 | 1 | -0.12588244 | 0.12433901E-03 | -143.97335 | 2.0501255 |
| 206 | 0 | 0.61258788E-01 | 0.30111189E-05 | 60.838472 | |
| 207 | 7 | -0.70485818E-08 | -0.82048821E-14 | -0.11525862E-14 | 0.12346975E-16 |
| 208 | 6 | 0.21636134E-05 | 0.11761400E-08 | 0.32006654E-02 | -0.26849864E-04 |
| 209 | 5 | -0.13228193E-03 | 0.68999669E-06 | -0.22433795 | 0.19615643E-02 |
| 210 | 4 | 0.28871477E-02 | 0.31257738E-04 | 4.8397578 | -0.45363150E-01 |
| 211 | 3 | -0.24853202E-01 | 0.24753724E-03 | -38.079085 | 0.39929121 |
| 212 | 2 | 0.87536903E-01 | 0.41023195E-03 | 116.59616 | -1.4194403 |
| 213 | 1 | -0.12588244 | 0.12433901E-03 | -143.97335 | 2.0501255 |
| 214 | 0 | 0.61258788E-01 | 0.30111189E-05 | 60.838472 | |
| 215 | 7 | -0.28726507E-08 | -0.17143581E-14 | 0.24267693E-14 | -0.55541839E-16 |
| 216 | 6 | 0.42346750E-05 | 0.28245518E-08 | 0.31939123E-02 | -0.26793213E-04 |
| 217 | 5 | -0.29857172E-03 | 0.16707368E-05 | -0.22395432 | 0.19581782E-02 |
| 218 | 4 | 0.68293023E-02 | 0.76000496E-04 | 4.8333721 | -0.45301763E-01 |
| 219 | 3 | -0.59851213E-01 | 0.60399479E-03 | -38.043031 | 0.39889267 |
| 220 | 2 | 0.21235346 | 0.10042645E-02 | 116.52602 | -1.4185020 |
| 221 | 1 | -0.30639453 | 0.30573542E-03 | -143.93207 | 2.0494469 |
| 222 | 0 | 0.14935640 | 0.74123768E-05 | 60.838472 | |
| 223 | 7 | -0.32902409E-08 | -0.25529066E-14 | 0.11988885E-14 | -0.45014903E-16 |
| 224 | 6 | 0.37562854E-05 | 0.24712502E-08 | 0.31953527E-02 | -0.26805296E-04 |
| 225 | 5 | -0.26216584E-03 | 0.14606656E-05 | -0.22403617 | 0.19589006E-02 |
| 226 | 4 | 0.59784819E-02 | 0.66426580E-04 | 4.8347351 | -0.45314865E-01 |
| 227 | 3 | -0.52336689E-01 | 0.52775921E-03 | -38.050729 | 0.39897776 |
| 228 | 2 | 0.18560952 | 0.87732663E-03 | 116.54100 | -1.4187024 |
| 229 | 1 | -0.26775360 | 0.26697134E-03 | -143.94089 | 2.0495919 |
| 230 | 0 | 0.13050713 | 0.64865099E-05 | 60.838472 |
| Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
| 1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.251 | ||
| 2 | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | 36 | 1 | VerySmooth | 3.922 | 3.922 | 1.000 | 0.393 |
| Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
| 1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.16139 | 0.60205 | 0.60205 | 0.27500 | 0.15630 | 0.22588 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
| 2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.26553 | 0.37967 | 0.37967 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 2.30798E-002 | 1.00000 | No |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Number of Refrigeration Compressor Racks | |
| 1 | 2 |
| Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
| 1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
| 2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | SWH BOOSTER G WATER HEATER | 2.2712E-002 | 6000.0 | 1.092 | 0.9931 |
| 2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 14.749 | 0.4701 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 2 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 3 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 4 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 5 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 6 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 7 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 8 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 9 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 10 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 11 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 12 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 13 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 14 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 15 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 16 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 17 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 18 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 19 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 20 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 21 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 22 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 23 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 24 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 25 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 26 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 27 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 28 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 29 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 3 | No | No |
| 30 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 2 | No | No |
| 31 | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 32 | CORRIDOR_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 33 | CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 34 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 35 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 36 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 37 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 38 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 39 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 40 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 41 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 42 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 43 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 44 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 45 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 46 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 47 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 48 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 49 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 50 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 51 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 52 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 53 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 54 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 55 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 56 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 57 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 58 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 59 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 60 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 61 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 62 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 63 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 64 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 65 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 66 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 67 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 68 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 69 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 70 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 71 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 72 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 73 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 74 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 75 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 76 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 77 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 78 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 79 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 80 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 81 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 82 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 83 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 84 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 85 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 3 | No | No |
| 86 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 2 | No | No |
| 87 | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 88 | CORRIDOR_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 89 | CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 90 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 91 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 92 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 93 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 94 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 95 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 96 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 97 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 98 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 99 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 100 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 101 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 102 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 103 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 104 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 105 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 106 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 107 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 108 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 109 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 110 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 111 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 112 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 113 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 114 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 115 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 116 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 117 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 118 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 119 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 120 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 121 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 122 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 123 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 124 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 125 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 126 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 127 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 128 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 129 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 130 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 131 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 132 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 133 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 134 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 135 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 136 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 137 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 138 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 139 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 140 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 141 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 142 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 3 | No | No |
| 143 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 2 | No | No |
| 144 | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 145 | CORRIDOR_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 146 | CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 147 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 148 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 149 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 150 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 151 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 152 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 153 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 154 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 155 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 156 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 157 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 158 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 159 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 160 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 3 | No | No |
| 161 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 2 | No | No |
| 162 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 2 | No | No |
| 163 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 2 | No | No |
| 164 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 165 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 166 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 167 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 168 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 169 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 170 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 171 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 172 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 3 | No | No |
| 173 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 2 | No | No |
| 174 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 2 | No | No |
| 175 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 176 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 177 | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 178 | COMPUTER_CLASS_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 179 | COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 180 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 181 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 182 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 183 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 184 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 185 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 186 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 3 | No | No |
| 187 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 2 | No | No |
| 188 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 2 | No | No |
| 189 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 190 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 191 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 192 | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 193 | MAIN_CORRIDOR_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 194 | MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 195 | LOBBY_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 3 | No | No |
| 196 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 2 | No | No |
| 197 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 2 | No | No |
| 198 | LOBBY_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 199 | LOBBY_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 200 | LOBBY_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 201 | LOBBY_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 202 | LOBBY_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 203 | LOBBY_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 204 | LOBBY_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 205 | LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 206 | MECH_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 207 | MECH_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 208 | MECH_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 209 | MECH_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 210 | MECH_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 211 | MECH_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 212 | MECH_ZN_1_FLR_1_WALL_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 213 | MECH_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 214 | MECH_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 215 | MECH_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 216 | BATH_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 217 | BATH_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 218 | BATH_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 219 | BATH_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 220 | BATH_ZN_1_FLR_1_WALL_5 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 3 | No | No |
| 221 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 2 | No | No |
| 222 | BATH_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 223 | BATH_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 224 | BATH_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 225 | OFFICES_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 3 | No | No |
| 226 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 2 | No | No |
| 227 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 2 | No | No |
| 228 | OFFICES_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 229 | OFFICES_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 3 | No | No |
| 230 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 2 | No | No |
| 231 | OFFICES_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 232 | OFFICES_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 233 | OFFICES_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 234 | OFFICES_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 235 | OFFICES_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 236 | OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 237 | GYM_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 238 | GYM_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 3 | No | No |
| 239 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 240 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 241 | GYM_ZN_1_FLR_1_WALL_2_DOOR | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 242 | GYM_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 243 | GYM_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 244 | GYM_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 245 | GYM_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 246 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 247 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 248 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 249 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 250 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 251 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 252 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 253 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 254 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 255 | GYM_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 256 | KITCHEN_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 257 | KITCHEN_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 3 | No | No |
| 258 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 2 | No | No |
| 259 | KITCHEN_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 260 | KITCHEN_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 261 | KITCHEN_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 262 | KITCHEN_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 263 | KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 264 | CAFETERIA_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 265 | CAFETERIA_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 3 | No | No |
| 266 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 2 | No | No |
| 267 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 2 | No | No |
| 268 | CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 269 | CAFETERIA_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 3 | No | No |
| 270 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 2 | No | No |
| 271 | CAFETERIA_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 272 | CAFETERIA_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 273 | CAFETERIA_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 274 | CAFETERIA_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 275 | CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 276 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 277 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 3 | No | No |
| 278 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 2 | No | No |
| 279 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 2 | No | No |
| 280 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 281 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 3 | No | No |
| 282 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 2 | No | No |
| 283 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 284 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 285 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 286 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 287 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 288 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
| 1 | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.786 | 0.393 | 0.402 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 6.835E-003 | 3.560E-005 | 3.350E-005 | 3.204E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 6.835E-003 | 3.560E-005 | 3.350E-005 | 3.204E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 6.835E-003 | 3.560E-005 | 3.350E-005 | 3.204E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 7.974E-002 | 2.531E-004 | 1.738E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 4.101E-002 | 2.531E-004 | 1.738E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 2.050E-002 | 3.755E-005 | 3.511E-005 | 3.380E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | LOBBY_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 4.329E-002 | 2.531E-004 | 1.739E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | LOBBY_ZN_1_FLR_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 3.031 | 1.773E-002 | 1.218E-002 | 15.954 | 1.000 | 0.000 | 0.000 | 0.000 |
| 20 | MECH_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | BATH_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 2.278E-002 | 1.199E-004 | 9.906E-005 | 0.108 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | OFFICES_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 9.569E-002 | 2.170E-004 | 1.566E-004 | 0.195 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | GYM_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 3.873E-002 | 1.085E-004 | 9.072E-005 | 9.764E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | KITCHEN_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 1.823E-002 | 1.085E-004 | 9.113E-005 | 9.764E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | CAFETERIA_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 8.202E-002 | 2.604E-004 | 1.779E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 9.113E-002 | 2.284E-004 | 1.625E-004 | 0.206 | 0.000 | 0.000 | 0.224 | 0.000 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 18 | LOBBY_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 19 | MECH_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 20 | BATH_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 21 | OFFICES_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 22 | GYM_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 23 | KITCHEN_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 24 | CAFETERIA_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2500 |
| 2 | Zone CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1.2500 |
| 3 | Zone MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.2500 |
| 4 | Zone CORRIDOR_POD_1_ZN_1_FLR_1 | 1.2500 |
| 5 | Zone CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1.2500 |
| 6 | Zone MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.2500 |
| 7 | Zone CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1.2500 |
| 8 | Zone MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.2500 |
| 9 | Zone CORRIDOR_POD_2_ZN_1_FLR_1 | 1.2500 |
| 10 | Zone CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1.2500 |
| 11 | Zone MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.2500 |
| 12 | Zone CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1.2500 |
| 13 | Zone MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.2500 |
| 14 | Zone CORRIDOR_POD_3_ZN_1_FLR_1 | 1.2500 |
| 15 | Zone CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1.2500 |
| 16 | Zone MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1.2500 |
| 17 | Zone COMPUTER_CLASS_ZN_1_FLR_1 | 1.2500 |
| 18 | Zone MAIN_CORRIDOR_ZN_1_FLR_1 | 1.2500 |
| 19 | Zone LOBBY_ZN_1_FLR_1 | 1.2500 |
| 20 | Zone MECH_ZN_1_FLR_1 | 1.2500 |
| 21 | Zone BATH_ZN_1_FLR_1 | 1.2500 |
| 22 | Zone OFFICES_ZN_1_FLR_1 | 1.2500 |
| 23 | Zone GYM_ZN_1_FLR_1 | 1.2500 |
| 24 | Zone KITCHEN_ZN_1_FLR_1 | 1.2500 |
| 25 | Zone CAFETERIA_ZN_1_FLR_1 | 1.2500 |
| 26 | Zone LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 1.2500 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.1500 |
| 2 | Zone CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1.1500 |
| 3 | Zone MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.1500 |
| 4 | Zone CORRIDOR_POD_1_ZN_1_FLR_1 | 1.1500 |
| 5 | Zone CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1.1500 |
| 6 | Zone MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.1500 |
| 7 | Zone CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1.1500 |
| 8 | Zone MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.1500 |
| 9 | Zone CORRIDOR_POD_2_ZN_1_FLR_1 | 1.1500 |
| 10 | Zone CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1.1500 |
| 11 | Zone MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.1500 |
| 12 | Zone CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1.1500 |
| 13 | Zone MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.1500 |
| 14 | Zone CORRIDOR_POD_3_ZN_1_FLR_1 | 1.1500 |
| 15 | Zone CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1.1500 |
| 16 | Zone MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1.1500 |
| 17 | Zone COMPUTER_CLASS_ZN_1_FLR_1 | 1.1500 |
| 18 | Zone MAIN_CORRIDOR_ZN_1_FLR_1 | 1.1500 |
| 19 | Zone LOBBY_ZN_1_FLR_1 | 1.1500 |
| 20 | Zone MECH_ZN_1_FLR_1 | 1.1500 |
| 21 | Zone BATH_ZN_1_FLR_1 | 1.1500 |
| 22 | Zone OFFICES_ZN_1_FLR_1 | 1.1500 |
| 23 | Zone GYM_ZN_1_FLR_1 | 1.1500 |
| 24 | Zone KITCHEN_ZN_1_FLR_1 | 1.1500 |
| 25 | Zone CAFETERIA_ZN_1_FLR_1 | 1.1500 |
| 26 | Zone LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 1.1500 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | Cooling | 7753.63692 | 8916.68246 | 0.65674 | 0.75525 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 37.45000 | 6.87043E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 2 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | Heating | 2885.77283 | 3607.21604 | 0.24388 | 0.30485 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 3 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | Cooling | 31516.20878 | 36243.64009 | 2.66952 | 3.06995 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 38.10000 | 6.87148E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 4 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | Heating | 9162.56364 | 11453.20456 | 0.77435 | 0.96794 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 5 | CORRIDOR_POD_1_ZN_1_FLR_1 | Cooling | 6775.23554 | 7791.52087 | 0.57369 | 0.65974 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 6 | CORRIDOR_POD_1_ZN_1_FLR_1 | Heating | 2848.82770 | 3561.03462 | 0.24076 | 0.30096 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 7 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | Cooling | 7519.40409 | 8647.31471 | 0.63690 | 0.73244 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 37.14667 | 6.86994E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 8 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | Heating | 2880.05301 | 3600.06626 | 0.24340 | 0.30425 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 9 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | Cooling | 29899.21780 | 34384.10047 | 2.53257 | 2.91245 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 10 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | Heating | 9054.72319 | 11318.40399 | 0.76524 | 0.95655 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 11 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | Cooling | 7690.88763 | 8844.52077 | 0.65142 | 0.74914 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 37.45000 | 6.87043E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 12 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | Heating | 2862.27382 | 3577.84227 | 0.24190 | 0.30237 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 13 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | Cooling | 31113.29772 | 35780.29237 | 2.63540 | 3.03071 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 38.10000 | 6.87148E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 14 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | Heating | 8981.58486 | 11226.98107 | 0.75906 | 0.94882 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 15 | CORRIDOR_POD_2_ZN_1_FLR_1 | Cooling | 6755.45008 | 7768.76759 | 0.57202 | 0.65782 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 16 | CORRIDOR_POD_2_ZN_1_FLR_1 | Heating | 2840.77124 | 3550.96405 | 0.24008 | 0.30010 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 17 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | Cooling | 7523.62421 | 8652.16784 | 0.63726 | 0.73285 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 37.14667 | 6.86994E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 18 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | Heating | 2881.98030 | 3602.47538 | 0.24356 | 0.30445 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 19 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | Cooling | 29916.79744 | 34404.31705 | 2.53406 | 2.91416 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 20 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | Heating | 9063.29334 | 11329.11668 | 0.76596 | 0.95745 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 21 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | Cooling | 7697.52792 | 8852.15710 | 0.65199 | 0.74978 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 37.45000 | 6.87043E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 22 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | Heating | 2864.82693 | 3581.03366 | 0.24211 | 0.30264 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 23 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | Cooling | 31246.55535 | 35933.53865 | 2.64669 | 3.04369 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 38.10000 | 6.87148E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 24 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | Heating | 9018.85759 | 11273.57199 | 0.76221 | 0.95276 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 25 | CORRIDOR_POD_3_ZN_1_FLR_1 | Cooling | 6813.29552 | 7835.28985 | 0.57691 | 0.66345 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 26 | CORRIDOR_POD_3_ZN_1_FLR_1 | Heating | 2844.02722 | 3555.03403 | 0.24036 | 0.30045 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 27 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | Cooling | 7579.55646 | 8716.48993 | 0.64199 | 0.73829 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 37.14667 | 6.86994E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 28 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | Heating | 2900.56361 | 3625.70452 | 0.24513 | 0.30642 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 29 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | Cooling | 20133.56124 | 23153.59543 | 1.70538 | 1.96118 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 315.00000 | 84.76857 | 0.59207 | 0.00000 |
| 30 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | Heating | 6162.40362 | 7703.00453 | 0.52080 | 0.65100 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 315.00000 | 84.76857 | 0.59207 | 0.00000 |
| 31 | COMPUTER_CLASS_ZN_1_FLR_1 | Cooling | 11040.42086 | 12696.48399 | 0.93515 | 1.07542 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 162.00000 | 43.59526 | 0.30449 | 0.00000 |
| 32 | COMPUTER_CLASS_ZN_1_FLR_1 | Heating | 2912.48102 | 3640.60128 | 0.24614 | 0.30768 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 162.00000 | 43.59526 | 0.30449 | 0.00000 |
| 33 | MAIN_CORRIDOR_ZN_1_FLR_1 | Cooling | 15010.94420 | 17262.58584 | 1.27106 | 1.46172 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 37.97000 | 6.87126E-003 | 546.00000 | 29.38800 | 0.16642 | 0.00000 |
| 34 | MAIN_CORRIDOR_ZN_1_FLR_1 | Heating | 6723.29917 | 8404.12396 | 0.56821 | 0.71026 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 546.00000 | 29.38800 | 0.16642 | 0.00000 |
| 35 | LOBBY_ZN_1_FLR_1 | Cooling | 7991.28014 | 9189.97216 | 0.67672 | 0.77823 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 38.10000 | 6.87148E-003 | 171.00000 | 18.40800 | 9.55546E-002 | 0.00000 |
| 36 | LOBBY_ZN_1_FLR_1 | Heating | 3894.31253 | 4867.89066 | 0.32912 | 0.41140 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 171.00000 | 18.40800 | 9.55546E-002 | 0.00000 |
| 37 | MECH_ZN_1_FLR_1 | Cooling | 10196.67805 | 11726.17976 | 0.86335 | 0.99286 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 252.00000 | 4.06900 | 0.00000 | 0.00000 |
| 38 | MECH_ZN_1_FLR_1 | Heating | 1782.25141 | 2227.81426 | 0.15062 | 0.18828 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:40:00 | -5.20000 | 2.80840E-003 | 252.00000 | 4.06900 | 0.00000 | 0.00000 |
| 39 | BATH_ZN_1_FLR_1 | Cooling | 6990.02008 | 8038.52309 | 0.59188 | 0.68066 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 37.45000 | 6.87043E-003 | 190.00000 | 10.22700 | 0.00000 | 0.00000 |
| 40 | BATH_ZN_1_FLR_1 | Heating | 3051.19143 | 3813.98928 | 0.25787 | 0.32233 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 190.00000 | 10.22700 | 0.00000 | 0.00000 |
| 41 | OFFICES_ZN_1_FLR_1 | Cooling | 20235.73871 | 23271.09951 | 1.71347 | 1.97049 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 38.10000 | 6.87148E-003 | 441.00000 | 23.73648 | 0.19042 | 0.00000 |
| 42 | OFFICES_ZN_1_FLR_1 | Heating | 8323.49203 | 10404.36504 | 0.70344 | 0.87930 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 441.00000 | 23.73648 | 0.19042 | 0.00000 |
| 43 | GYM_ZN_1_FLR_1 | Cooling | 22746.81832 | 26158.84107 | 1.92691 | 2.21594 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 357.00000 | 115.31008 | 0.54407 | 0.00000 |
| 44 | GYM_ZN_1_FLR_1 | Heating | 6044.71206 | 7555.89008 | 0.51086 | 0.63857 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | -5.20000 | 2.80840E-003 | 357.00000 | 115.31008 | 0.54407 | 0.00000 |
| 45 | KITCHEN_ZN_1_FLR_1 | Cooling | 18766.97292 | 21582.01886 | 1.59127 | 1.82997 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 36.93000 | 6.86961E-003 | 168.00000 | 26.99300 | 0.25481 | 0.00000 |
| 46 | KITCHEN_ZN_1_FLR_1 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.25481 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -5.20000 | 2.80840E-003 | 168.00000 | 26.99300 | 0.25481 | 0.00000 |
| 47 | CAFETERIA_ZN_1_FLR_1 | Cooling | 33244.89890 | 38231.63373 | 2.81940 | 3.24231 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 37.45000 | 6.87043E-003 | 315.00000 | 339.07427 | 1.48818 | 0.00000 |
| 48 | CAFETERIA_ZN_1_FLR_1 | Heating | 6423.43542 | 8029.29428 | 0.54286 | 1.48818 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | -5.20000 | 2.80840E-003 | 315.00000 | 339.07427 | 1.48818 | 0.00000 |
| 49 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | Cooling | 22497.54813 | 25872.18035 | 1.90515 | 2.19092 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 38.10000 | 6.87148E-003 | 399.00000 | 42.95403 | 0.34458 | 0.00000 |
| 50 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | Heating | 7239.65097 | 9049.56372 | 0.61184 | 0.76480 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -5.20000 | 2.80840E-003 | 399.00000 | 42.95403 | 0.34458 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | VAV_POD_1 | Cooling | Sensible | 561294.01 | 34.58892 | 34.58892 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
| 2 | VAV_POD_1 | Heating | Sensible | 188412.29 | 12.38201 | 12.38201 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 01:00:00 |
| 3 | PSZ-AC_1:6 | Cooling | Sensible | 24709.40 | 1.82997 | 1.82997 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 4 | PSZ-AC_1:6 | Heating | Sensible | 9976.81 | 0.25481 | 0.25481 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| 5 | PSZ-AC_2:7 | Cooling | Sensible | 59383.45 | 3.24231 | 3.24231 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 6 | PSZ-AC_2:7 | Heating | Sensible | 58267.37 | 1.48818 | 1.48818 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75525 |
| 2 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.98849E-002 |
| 3 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.39000 |
| 4 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29455 |
| 5 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39000 |
| 6 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 7 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.81439E-003 |
| 8 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.45879E-005 |
| 9 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30485 |
| 10 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 11 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 12 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6239.72884 |
| 13 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.45879E-005 |
| 14 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 145.53884 |
| 15 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.06995 |
| 16 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11840 |
| 17 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46200 |
| 18 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.41832 |
| 19 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46200 |
| 20 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 21 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.21798E-003 |
| 22 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.07351E-004 |
| 23 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.41832 |
| 24 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 25 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 26 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23701.48451 |
| 27 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07351E-004 |
| 28 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 526.41058 |
| 29 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65974 |
| 30 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22176 |
| 31 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 32 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19792 |
| 33 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59136 |
| 34 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 35 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71809E-003 |
| 36 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.38946E-005 |
| 37 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30096 |
| 38 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 39 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 40 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6160.48172 |
| 41 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.38946E-005 |
| 42 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 143.69376 |
| 43 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73244 |
| 44 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10300 |
| 45 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.40200 |
| 46 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29444 |
| 47 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40200 |
| 48 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 49 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.69917E-003 |
| 50 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.44797E-005 |
| 51 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30425 |
| 52 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 53 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 54 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6227.35997 |
| 55 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.44797E-005 |
| 56 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 145.25034 |
| 57 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.91245 |
| 58 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12480 |
| 59 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48700 |
| 60 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.41836 |
| 61 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48700 |
| 62 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 63 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.05288E-003 |
| 64 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.06175E-004 |
| 65 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.41836 |
| 66 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 67 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 68 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23567.05366 |
| 69 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.06175E-004 |
| 70 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 522.79371 |
| 71 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74914 |
| 72 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10070 |
| 73 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.39300 |
| 74 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29441 |
| 75 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39300 |
| 76 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 77 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.78352E-003 |
| 78 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.41433E-005 |
| 79 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30237 |
| 80 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 81 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 82 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6188.91325 |
| 83 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.41433E-005 |
| 84 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 144.35356 |
| 85 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.03071 |
| 86 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11993 |
| 87 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46800 |
| 88 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.41837 |
| 89 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46800 |
| 90 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 91 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.17684E-003 |
| 92 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.05375E-004 |
| 93 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.41837 |
| 94 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 95 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 96 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23475.67885 |
| 97 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.05375E-004 |
| 98 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 520.34218 |
| 99 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.65782 |
| 100 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22241 |
| 101 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 102 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19735 |
| 103 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59309 |
| 104 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 105 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.71307E-003 |
| 106 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.37422E-005 |
| 107 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30010 |
| 108 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 109 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 110 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6143.05965 |
| 111 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.37422E-005 |
| 112 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 143.28738 |
| 113 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73285 |
| 114 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10294 |
| 115 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.40200 |
| 116 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29460 |
| 117 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40200 |
| 118 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 119 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.70125E-003 |
| 120 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.45161E-005 |
| 121 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30445 |
| 122 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 123 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 124 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6231.52766 |
| 125 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.45161E-005 |
| 126 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 145.34755 |
| 127 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.91416 |
| 128 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12473 |
| 129 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48700 |
| 130 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.41920 |
| 131 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48700 |
| 132 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 133 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.05468E-003 |
| 134 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.06332E-004 |
| 135 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.41920 |
| 136 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 137 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 138 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23584.97004 |
| 139 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.06332E-004 |
| 140 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 523.21009 |
| 141 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.74978 |
| 142 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10061 |
| 143 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.39300 |
| 144 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29467 |
| 145 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39300 |
| 146 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 147 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.78679E-003 |
| 148 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.41916E-005 |
| 149 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30264 |
| 150 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 151 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 152 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6194.43424 |
| 153 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.41916E-005 |
| 154 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 144.48234 |
| 155 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.04369 |
| 156 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11942 |
| 157 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46600 |
| 158 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.41836 |
| 159 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46600 |
| 160 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 161 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.19045E-003 |
| 162 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.05782E-004 |
| 163 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.41836 |
| 164 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 165 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 166 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23522.16765 |
| 167 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.05782E-004 |
| 168 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 521.58963 |
| 169 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66345 |
| 170 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22052 |
| 171 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 172 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.19904 |
| 173 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58805 |
| 174 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 175 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.72774E-003 |
| 176 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.38038E-005 |
| 177 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30045 |
| 178 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 179 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 180 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6150.10070 |
| 181 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.38038E-005 |
| 182 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 143.45162 |
| 183 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73829 |
| 184 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10218 |
| 185 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.39900 |
| 186 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29458 |
| 187 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39900 |
| 188 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 189 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.72876E-003 |
| 190 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.48677E-005 |
| 191 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30642 |
| 192 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 193 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 194 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6271.71327 |
| 195 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.48677E-005 |
| 196 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 146.28489 |
| 197 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.96118 |
| 198 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12239 |
| 199 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47800 |
| 200 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.93745 |
| 201 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47800 |
| 202 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 203 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.11299E-003 |
| 204 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.38213E-004 |
| 205 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.93745 |
| 206 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 207 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 208 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15798.60511 |
| 209 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.38213E-004 |
| 210 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 351.51919 |
| 211 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07542 |
| 212 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11479 |
| 213 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44800 |
| 214 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.48179 |
| 215 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44800 |
| 216 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 217 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.31921E-003 |
| 218 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.82481E-005 |
| 219 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.48179 |
| 220 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 221 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 222 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7801.17401 |
| 223 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.82481E-005 |
| 224 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 172.13381 |
| 225 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.46172 |
| 226 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28463 |
| 227 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 228 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.43852 |
| 229 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75902 |
| 230 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 231 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.33857E-003 |
| 232 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.27192E-004 |
| 233 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71026 |
| 234 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 235 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 236 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14538.81331 |
| 237 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.27192E-004 |
| 238 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 339.11865 |
| 239 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77823 |
| 240 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16743 |
| 241 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 242 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23347 |
| 243 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44649 |
| 244 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 245 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.27552E-003 |
| 246 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.36684E-005 |
| 247 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41140 |
| 248 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 249 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 250 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8420.74829 |
| 251 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.36684E-005 |
| 252 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 196.41168 |
| 253 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.99286 |
| 254 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19341 |
| 255 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 256 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.29786 |
| 257 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51575 |
| 258 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 259 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.96996E-003 |
| 260 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.19978E-005 |
| 261 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29786 |
| 262 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 263 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 264 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4800.60247 |
| 265 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.19978E-005 |
| 266 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 105.82621 |
| 267 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68066 |
| 268 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21270 |
| 269 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 270 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20420 |
| 271 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56721 |
| 272 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 273 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.79122E-003 |
| 274 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.77208E-005 |
| 275 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.32233 |
| 276 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 277 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 278 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6597.84180 |
| 279 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.77208E-005 |
| 280 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 153.89384 |
| 281 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.97049 |
| 282 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45477 |
| 283 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 284 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.23411E-003 |
| 285 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.57455E-004 |
| 286 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.87930 |
| 287 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 288 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 289 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17998.02717 |
| 290 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.57455E-004 |
| 291 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 419.79881 |
| 292 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.21594 |
| 293 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12276 |
| 294 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.38900 |
| 295 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.86200 |
| 296 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38900 |
| 297 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 298 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.10356E-003 |
| 299 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.31233E-004 |
| 300 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.86200 |
| 301 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 302 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 303 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15000.72781 |
| 304 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31233E-004 |
| 305 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 336.11307 |
| 306 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN_ZN_1_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.82997 |
| 307 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CAFETERIA_ZN_1_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.24231 |
| 308 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.19092 |
| 309 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13877 |
| 310 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 311 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.65728 |
| 312 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37006 |
| 313 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 314 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.74551E-003 |
| 315 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.36951E-004 |
| 316 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76480 |
| 317 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 318 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 319 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15654.30248 |
| 320 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36951E-004 |
| 321 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 365.13141 |
| 322 | AirLoopHVAC | VAV_POD_1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 17.36858 |
| 323 | AirLoopHVAC | VAV_POD_1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 14.15786 |
| 324 | AirLoopHVAC | VAV_POD_1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 34.73715 |
| 325 | AirLoopHVAC | VAV_POD_1 | Adjusted Heating Design Air Flow Rate [m3/s] | 14.15786 |
| 326 | AirLoopHVAC | VAV_POD_1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 34.58892 |
| 327 | AirLoopHVAC | VAV_POD_1 | Adjusted Main Design Air Flow Rate [m3/s] | 34.58892 |
| 328 | AirLoopHVAC | VAV_POD_1 | User Heating Air Flow Ratio [] | 0.30000 |
| 329 | AirLoopHVAC | VAV_POD_1 | Calculated Heating Air Flow Ratio [] | 0.40932 |
| 330 | AirLoopHVAC | PSZ-AC_1:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.82997 |
| 331 | AirLoopHVAC | PSZ-AC_1:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.82997 |
| 332 | AirLoopHVAC | PSZ-AC_1:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.82997 |
| 333 | AirLoopHVAC | PSZ-AC_1:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.82997 |
| 334 | AirLoopHVAC | PSZ-AC_1:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.82997 |
| 335 | AirLoopHVAC | PSZ-AC_1:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.82997 |
| 336 | AirLoopHVAC | PSZ-AC_1:6 | User Heating Air Flow Ratio [] | 1.00000 |
| 337 | AirLoopHVAC | PSZ-AC_1:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 338 | AirLoopHVAC | PSZ-AC_2:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.24231 |
| 339 | AirLoopHVAC | PSZ-AC_2:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.24231 |
| 340 | AirLoopHVAC | PSZ-AC_2:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.24231 |
| 341 | AirLoopHVAC | PSZ-AC_2:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.24231 |
| 342 | AirLoopHVAC | PSZ-AC_2:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.24231 |
| 343 | AirLoopHVAC | PSZ-AC_2:7 | Adjusted Main Design Air Flow Rate [m3/s] | 3.24231 |
| 344 | AirLoopHVAC | PSZ-AC_2:7 | User Heating Air Flow Ratio [] | 1.00000 |
| 345 | AirLoopHVAC | PSZ-AC_2:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 346 | AirLoopHVAC | VAV_POD_1 | Design Supply Air Flow Rate [m3/s] | 34.58892 |
| 347 | AirLoopHVAC | PSZ-AC_1:6 | Design Supply Air Flow Rate [m3/s] | 1.82997 |
| 348 | AirLoopHVAC | PSZ-AC_2:7 | Design Supply Air Flow Rate [m3/s] | 3.24231 |
| 349 | Controller:OutdoorAir | VAV_POD_1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 34.58892 |
| 350 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 34.58892 |
| 351 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 710881.75851 |
| 352 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.76512 |
| 353 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 11.52849 |
| 354 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 236936.89011 |
| 355 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.76512 |
| 356 | Coil:Heating:Fuel | VAV_POD_1 HEATING COIL | Design Size Nominal Capacity [W] | 196976.23204 |
| 357 | Fan:VariableVolume | VAV_POD_1 FAN | Design Size Maximum Flow Rate [m3/s] | 34.58892 |
| 358 | Controller:OutdoorAir | PSZ-AC_1:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.82997 |
| 359 | Controller:OutdoorAir | PSZ-AC_1:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.25481 |
| 360 | Fan:SystemModel | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.82997 |
| 361 | Fan:SystemModel | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3041.39837 |
| 362 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.82997 |
| 363 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.82997 |
| 364 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.82997 |
| 365 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.82997 |
| 366 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.82997 |
| 367 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.91498 |
| 368 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.21998 |
| 369 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 39311.76000 |
| 370 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 19655.88000 |
| 371 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74930 |
| 372 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74930 |
| 373 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 39311.76000 |
| 374 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 63053.78651 |
| 375 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
| 376 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 377 | Coil:Heating:Fuel | PSZ-AC_1:6 HEATING COIL | Design Size Nominal Capacity [W] | 63053.78651 |
| 378 | Controller:OutdoorAir | PSZ-AC_2:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.24231 |
| 379 | Controller:OutdoorAir | PSZ-AC_2:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.48818 |
| 380 | Fan:SystemModel | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.24231 |
| 381 | Fan:SystemModel | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 5259.43298 |
| 382 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.24231 |
| 383 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.24231 |
| 384 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.24231 |
| 385 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.24231 |
| 386 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.24231 |
| 387 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.62116 |
| 388 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.16154 |
| 389 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 79630.46000 |
| 390 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 39815.23000 |
| 391 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70480 |
| 392 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70480 |
| 393 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 79630.46000 |
| 394 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 78718.83855 |
| 395 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
| 396 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 397 | Coil:Heating:Fuel | PSZ-AC_2:7 HEATING COIL | Design Size Nominal Capacity [W] | 78718.83855 |
| 398 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.45192E-003 |
| 399 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.29423 |
| 400 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.45192E-003 |
| 401 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 738.41063 |
| 402 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
| 403 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 280269.51646 |
| 404 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 280269.52000 |
| 405 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.45192E-003 |
| 406 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.05414E-004 |
| 407 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.26497E-002 |
| 408 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.05414E-004 |
| 409 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 13.46550 |
| 410 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.05414E-004 |
| Component Type | Name | Nominal Total Capacity {W} | |
| 1 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5921.07 |
| 2 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 22496.14 |
| 3 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5845.87 |
| 4 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5909.33 |
| 5 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 22368.63 |
| 6 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5872.85 |
| 7 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 22281.96 |
| 8 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5829.34 |
| 9 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5913.29 |
| 10 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 22385.63 |
| 11 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5878.09 |
| 12 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 22326.06 |
| 13 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5836.02 |
| 14 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5951.42 |
| 15 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 14995.07 |
| 16 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | 7404.60 |
| 17 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | 13796.32 |
| 18 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | 7990.70 |
| 19 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 4556.58 |
| 20 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6260.89 |
| 21 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | 17078.87 |
| 22 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | 14237.45 |
| 23 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | 14854.84 |
| DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
| 1 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | N/A | N/A | 685338.02 | 2338470.38 | 11.34 | 3.08 | 3.32 | 3.30 | 3.44 | 10.50 | 11.32 | 11.26 | 11.73 | 34.6957 | 27.5947 | 18.5141 | 7.5925 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | 37871.9 | 10.90 | 10.90 | |||
| 2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | 77073.1 | 11.12 | 11.12 |
| Zone Name | # Surfaces | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 11 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 12 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | 10 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 11 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 12 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 11 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 12 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | 10 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 11 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 12 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 11 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 12 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | 11 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 11 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 12 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | 10 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | 15 |
| 18 | LOBBY_ZN_1_FLR_1 | 11 |
| 19 | MECH_ZN_1_FLR_1 | 10 |
| 20 | BATH_ZN_1_FLR_1 | 9 |
| 21 | OFFICES_ZN_1_FLR_1 | 12 |
| 22 | GYM_ZN_1_FLR_1 | 19 |
| 23 | KITCHEN_ZN_1_FLR_1 | 8 |
| 24 | CAFETERIA_ZN_1_FLR_1 | 12 |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 32.37 | 44.00 | 32.37 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 180.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 180.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 4 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | Door | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 5 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 8 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 9 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 10 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 11 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 12 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 161.46 | 212.00 | 161.46 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 15 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | Window | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 16 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | Door | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 17 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | Door | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 18 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 19 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 21 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 22 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 23 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 24 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 26 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 90.00 | 90.00 | 3.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 27 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 28 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 9.36 | 12.00 | 9.36 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 30 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | Window | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 2.64 | 2.64 | 2.64 | 270.00 | 90.00 | 2.90 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 31 | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.980E-002 | 1.971E-002 | 192.00 | 192.00 | 192.00 | 270.00 | 180.00 | 3.00 | 64.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 32 | CORRIDOR_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 192.00 | 192.00 | 192.00 | 90.00 | 0.00 | 3.00 | 64.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 33 | CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 384.00 | 384.00 | 384.00 | 0.00 | 90.00 | 384.00 | 1.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 34 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 35 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 36 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 32.37 | 44.00 | 32.37 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 | ||
| 37 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 0.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 38 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 0.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 |
| 39 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | Door | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | |
| 40 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 42 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 47 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 161.46 | 212.00 | 161.46 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 | ||
| 48 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 49 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 50 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | Window | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 51 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | Door | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 | |
| 52 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | Door | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 53 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 55 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 56 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 57 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 32.37 | 44.00 | 32.37 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 | ||
| 58 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 180.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 |
| 59 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 180.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.61 | 0.39 | 4 |
| 60 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | Door | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 | |
| 61 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 63 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 65 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 66 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 67 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 68 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 161.46 | 212.00 | 161.46 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 | ||
| 69 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 70 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 71 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | Window | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 72 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | Door | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 73 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | Door | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 | |
| 74 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 76 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 77 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 78 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 79 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 80 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 82 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 90.00 | 90.00 | 3.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 85 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 9.36 | 12.00 | 9.36 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 86 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | Window | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 2.64 | 2.64 | 2.64 | 270.00 | 90.00 | 2.90 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 87 | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.980E-002 | 1.971E-002 | 192.00 | 192.00 | 192.00 | 270.00 | 180.00 | 3.00 | 64.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 88 | CORRIDOR_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 192.00 | 192.00 | 192.00 | 90.00 | 0.00 | 3.00 | 64.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 89 | CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 384.00 | 384.00 | 384.00 | 0.00 | 90.00 | 384.00 | 1.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 90 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 91 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 32.37 | 44.00 | 32.37 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.56 | 0.44 | 4 | ||
| 93 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 0.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 94 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 0.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 |
| 95 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | Door | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 | |
| 96 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 99 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 100 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 101 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 103 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 161.46 | 212.00 | 161.46 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 | ||
| 104 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 |
| 105 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 106 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | Window | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 107 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | Door | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 108 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | Door | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | |
| 109 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 32.37 | 44.00 | 32.37 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.56 | 0.44 | 4 | ||
| 114 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 180.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 |
| 115 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 180.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 |
| 116 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | Door | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.58 | 0.42 | 4 | |
| 117 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 119 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 120 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 121 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 122 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 123 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 124 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 161.46 | 212.00 | 161.46 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 | ||
| 125 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 126 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 127 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | Window | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 |
| 128 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | Door | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | |
| 129 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | Door | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 130 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 131 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 134 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 135 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 136 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 137 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 90.00 | 90.00 | 3.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 139 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 72.00 | 72.00 | 72.00 | 0.00 | 90.00 | 18.00 | 4.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 140.00 | 140.00 | 140.00 | 0.00 | 90.00 | 35.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 141 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 9.36 | 12.00 | 9.36 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | Window | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 2.64 | 2.64 | 2.64 | 270.00 | 90.00 | 2.90 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 144 | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.980E-002 | 1.971E-002 | 192.00 | 192.00 | 192.00 | 270.00 | 180.00 | 3.00 | 64.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 145 | CORRIDOR_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 192.00 | 192.00 | 192.00 | 90.00 | 0.00 | 3.00 | 64.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 146 | CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 384.00 | 384.00 | 384.00 | 0.00 | 90.00 | 384.00 | 1.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 147 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 148 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 32.40 | 44.00 | 32.40 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 150 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 0.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 151 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.43 | 8.43 | 8.43 | 0.00 | 90.00 | 8.43 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 152 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | Door | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 153 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 154 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 155 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 156 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 157 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 158 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 140.00 | 140.00 | 140.00 | 180.00 | 90.00 | 35.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 159 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 105.30 | 140.00 | 105.30 | 0.00 | 90.00 | 35.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 10.27 | 10.27 | 10.27 | 0.00 | 90.00 | 10.82 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 162 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 10.27 | 10.27 | 10.27 | 0.00 | 90.00 | 10.82 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 163 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | Window | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 10.27 | 10.27 | 10.27 | 0.00 | 90.00 | 10.82 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 164 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | Door | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 165 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | Door | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 166 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 315.00 | 315.00 | 315.00 | 270.00 | 180.00 | 9.00 | 35.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 168 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 315.00 | 315.00 | 315.00 | 90.00 | 0.00 | 9.00 | 35.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 169 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 630.00 | 630.00 | 630.00 | 0.00 | 90.00 | 630.00 | 1.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 170 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 72.00 | 72.00 | 72.00 | 180.00 | 90.00 | 18.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 171 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 172 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 54.21 | 72.00 | 54.21 | 0.00 | 90.00 | 18.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 173 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 1.16 | 1.16 | 1.16 | 0.00 | 90.00 | 1.22 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 174 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 14.68 | 14.68 | 14.68 | 0.00 | 90.00 | 15.46 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | Door | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 176 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 162.00 | 162.00 | 162.00 | 270.00 | 180.00 | 9.00 | 18.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 178 | COMPUTER_CLASS_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 162.00 | 162.00 | 162.00 | 90.00 | 0.00 | 9.00 | 18.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 179 | COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 324.00 | 324.00 | 324.00 | 0.00 | 90.00 | 324.00 | 1.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 180 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 180.00 | 90.00 | 13.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 181 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 168.00 | 168.00 | 168.00 | 90.00 | 90.00 | 42.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 0.00 | 90.00 | 13.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 183 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 26.13 | 36.00 | 26.13 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | ||
| 187 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | Window | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 1.26 | 1.26 | 1.26 | 270.00 | 90.00 | 1.22 | 1.03 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.73 | 0.27 | 4 |
| 188 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | Window | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 6.66 | 6.66 | 6.66 | 270.00 | 90.00 | 6.46 | 1.03 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 189 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | Door | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.71 | 0.29 | 4 | |
| 190 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 191 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR | 2.090E-002 | 2.079E-002 | 546.00 | 546.00 | 546.00 | 270.00 | 180.00 | 42.00 | 13.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 193 | MAIN_CORRIDOR_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 546.00 | 546.00 | 546.00 | 90.00 | 0.00 | 42.00 | 13.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 194 | MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1092.00 | 1092.00 | 1092.00 | 0.00 | 90.00 | 1092.00 | 1.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 195 | LOBBY_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 57.33 | 76.00 | 57.33 | 180.00 | 90.00 | 19.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 196 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | LOBBY_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 1.15 | 1.15 | 1.15 | 180.00 | 90.00 | 1.22 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 197 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | LOBBY_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 15.57 | 15.57 | 15.57 | 180.00 | 90.00 | 16.46 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 198 | LOBBY_ZN_1_FLR_1_WALL_1_DOOR | Door | LOBBY_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 199 | LOBBY_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | OFFICES_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | LOBBY_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 6.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | LOBBY_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 0.00 | 90.00 | 13.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | LOBBY_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 203 | LOBBY_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 171.00 | 171.00 | 171.00 | 270.00 | 180.00 | 9.00 | 19.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 204 | LOBBY_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 171.00 | 171.00 | 171.00 | 90.00 | 0.00 | 9.00 | 19.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 205 | LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 342.00 | 342.00 | 342.00 | 0.00 | 90.00 | 342.00 | 1.00 | 0.00 | LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 206 | MECH_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 180.00 | 90.00 | 6.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | MECH_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 48.00 | 48.00 | 48.00 | 90.00 | 90.00 | 12.00 | 4.00 | 0.00 | OFFICES_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 208 | MECH_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.00 | 68.00 | 68.00 | 90.00 | 90.00 | 17.00 | 4.00 | 0.00 | GYM_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | MECH_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 32.00 | 32.00 | 32.00 | 90.00 | 90.00 | 8.00 | 4.00 | 0.00 | KITCHEN_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | MECH_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.00 | 20.00 | 20.00 | 90.00 | 90.00 | 5.00 | 4.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | MECH_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 6.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | MECH_ZN_1_FLR_1_WALL_7 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 168.00 | 168.00 | 168.00 | 270.00 | 90.00 | 42.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | MECH_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MECH_ZN_1_FLR_1_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 252.00 | 252.00 | 252.00 | 270.00 | 180.00 | 42.00 | 6.00 | 0.00 | MECH_ZN_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 214 | MECH_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 252.00 | 252.00 | 252.00 | 90.00 | 0.00 | 42.00 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 215 | MECH_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 504.00 | 504.00 | 504.00 | 0.00 | 90.00 | 504.00 | 1.00 | 0.00 | MECH_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 216 | BATH_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 180.00 | 90.00 | 13.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 217 | BATH_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 180.00 | 90.00 | 6.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 218 | BATH_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.00 | 40.00 | 40.00 | 90.00 | 90.00 | 10.00 | 4.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | BATH_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 76.00 | 76.00 | 76.00 | 0.00 | 90.00 | 19.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | BATH_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 31.20 | 40.00 | 31.20 | 270.00 | 90.00 | 10.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | ||
| 221 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | Window | BATH_ZN_1_FLR_1_WALL_5 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 8.80 | 8.80 | 8.80 | 270.00 | 90.00 | 9.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 222 | BATH_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | BATH_ZN_1_FLR_1_FLOOR_FFACTOR | 6.720E-002 | 6.612E-002 | 190.00 | 190.00 | 190.00 | 270.00 | 180.00 | 10.00 | 19.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 223 | BATH_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 190.00 | 190.00 | 190.00 | 90.00 | 0.00 | 10.00 | 19.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 224 | BATH_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 380.00 | 380.00 | 380.00 | 0.00 | 90.00 | 380.00 | 1.00 | 0.00 | BATH_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 225 | OFFICES_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 63.57 | 84.00 | 63.57 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | OFFICES_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 1.14 | 1.14 | 1.14 | 180.00 | 90.00 | 1.22 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 227 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | OFFICES_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 17.34 | 17.34 | 17.34 | 180.00 | 90.00 | 18.46 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 228 | OFFICES_ZN_1_FLR_1_WALL_1_DOOR | Door | OFFICES_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 229 | OFFICES_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 65.52 | 84.00 | 65.52 | 90.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 230 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | Window | OFFICES_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 18.48 | 18.48 | 18.48 | 90.00 | 90.00 | 20.90 | 0.88 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 231 | OFFICES_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | GYM_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | OFFICES_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 48.00 | 48.00 | 48.00 | 270.00 | 90.00 | 12.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | OFFICES_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 234 | OFFICES_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR | 0.123 | 0.119 | 441.00 | 441.00 | 441.00 | 270.00 | 180.00 | 21.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 235 | OFFICES_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 441.00 | 441.00 | 441.00 | 90.00 | 0.00 | 21.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 236 | OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 882.00 | 882.00 | 882.00 | 0.00 | 90.00 | 882.00 | 1.00 | 0.00 | OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 237 | GYM_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | OFFICES_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | GYM_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 51.09 | 68.00 | 51.09 | 90.00 | 90.00 | 17.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | Window | GYM_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 1.17 | 1.17 | 1.17 | 90.00 | 90.00 | 1.22 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 240 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | Window | GYM_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 13.79 | 13.79 | 13.79 | 90.00 | 90.00 | 14.46 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 241 | GYM_ZN_1_FLR_1_WALL_2_DOOR | Door | GYM_ZN_1_FLR_1_WALL_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 242 | GYM_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | KITCHEN_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 243 | GYM_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.00 | 68.00 | 68.00 | 270.00 | 90.00 | 17.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 244 | GYM_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | GYM_ZN_1_FLR_1_FLOOR_FFACTOR | 6.074E-002 | 5.986E-002 | 357.00 | 357.00 | 357.00 | 270.00 | 180.00 | 17.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 245 | GYM_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 343.62 | 357.00 | 343.62 | 90.00 | 0.00 | 17.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 246 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 247 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 248 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 249 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 250 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 251 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 252 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 253 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 254 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 255 | GYM_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 714.00 | 714.00 | 714.00 | 0.00 | 90.00 | 714.00 | 1.00 | 0.00 | GYM_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 256 | KITCHEN_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | GYM_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 257 | KITCHEN_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 24.96 | 32.00 | 24.96 | 90.00 | 90.00 | 8.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 258 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | Window | KITCHEN_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 7.04 | 7.04 | 7.04 | 90.00 | 90.00 | 7.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 259 | KITCHEN_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 260 | KITCHEN_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 32.00 | 32.00 | 32.00 | 270.00 | 90.00 | 8.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 261 | KITCHEN_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR | 6.074E-002 | 5.986E-002 | 168.00 | 168.00 | 168.00 | 270.00 | 180.00 | 8.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 262 | KITCHEN_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 168.00 | 168.00 | 168.00 | 90.00 | 0.00 | 8.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 263 | KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 336.00 | 336.00 | 336.00 | 0.00 | 90.00 | 336.00 | 1.00 | 0.00 | KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 264 | CAFETERIA_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | KITCHEN_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 265 | CAFETERIA_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 44.85 | 60.00 | 44.85 | 90.00 | 90.00 | 15.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 266 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | Window | CAFETERIA_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 1.18 | 1.18 | 1.18 | 90.00 | 90.00 | 1.22 | 0.96 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 267 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | Window | CAFETERIA_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 12.02 | 12.02 | 12.02 | 90.00 | 90.00 | 12.46 | 0.96 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 268 | CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | Door | CAFETERIA_ZN_1_FLR_1_WALL_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 269 | CAFETERIA_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 65.52 | 84.00 | 65.52 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.54 | 0.46 | 4 | ||
| 270 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | Window | CAFETERIA_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 18.48 | 18.48 | 18.48 | 0.00 | 90.00 | 20.90 | 0.88 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.54 | 0.46 | 4 |
| 271 | CAFETERIA_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.00 | 40.00 | 40.00 | 270.00 | 90.00 | 10.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 272 | CAFETERIA_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.00 | 20.00 | 20.00 | 270.00 | 90.00 | 5.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 273 | CAFETERIA_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR | 0.148 | 0.143 | 315.00 | 315.00 | 315.00 | 270.00 | 180.00 | 15.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 274 | CAFETERIA_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 315.00 | 315.00 | 315.00 | 90.00 | 0.00 | 15.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 275 | CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 630.00 | 630.00 | 630.00 | 0.00 | 90.00 | 630.00 | 1.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 276 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 76.00 | 76.00 | 76.00 | 180.00 | 90.00 | 19.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 277 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 63.57 | 84.00 | 63.57 | 90.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.54 | 0.46 | 4 | ||
| 278 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | Window | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 1.14 | 1.14 | 1.14 | 90.00 | 90.00 | 1.22 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.69 | 0.31 | 4 |
| 279 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | Window | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 17.33 | 17.33 | 17.33 | 90.00 | 90.00 | 18.46 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.53 | 0.47 | 4 |
| 280 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | Door | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 281 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 59.28 | 76.00 | 59.28 | 0.00 | 90.00 | 19.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 282 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | Window | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.25 | N/A | 3.241 | No | 16.72 | 16.72 | 16.72 | 0.00 | 90.00 | 18.90 | 0.88 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 283 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 284 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 285 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 286 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR | 0.129 | 0.125 | 399.00 | 399.00 | 399.00 | 270.00 | 180.00 | 21.00 | 19.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 287 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 399.00 | 399.00 | 399.00 | 90.00 | 0.00 | 21.00 | 19.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 288 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 798.00 | 798.00 | 798.00 | 0.00 | 90.00 | 798.00 | 1.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1096132243 | 0.1988191159 | Pass | Pass | 7.7405685057E-003 | 8.7911609247E-002 | Pass | Pass |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1019321199 | 0.2263929352 | Pass | Pass | 7.9810529835E-003 | 8.9420533063E-002 | Pass | Pass |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.0223003452E-002 | 6.0302964709E-002 | Pass | Pass | 7.3595485599E-003 | 8.5547308350E-002 | Pass | Pass |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.9544703815E-002 | 0.1198244087 | Pass | Pass | 8.0060356055E-003 | 8.9611945096E-002 | Pass | Pass |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.7483674373E-002 | 0.1361734533 | Pass | Pass | 8.3619895824E-003 | 9.1877370252E-002 | Pass | Pass |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1087432841 | 0.1971342079 | Pass | Pass | 7.7442240355E-003 | 8.7934795045E-002 | Pass | Pass |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.9740724408E-002 | 0.2213114511 | Pass | Pass | 8.0275412795E-003 | 8.9716365973E-002 | Pass | Pass |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.9848736395E-002 | 5.9479745462E-002 | Pass | Pass | 7.3619826565E-003 | 8.5562294612E-002 | Pass | Pass |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.9522119712E-002 | 0.1194030947 | Pass | Pass | 8.0195845742E-003 | 8.9700448615E-002 | Pass | Pass |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.7458503440E-002 | 0.1356690424 | Pass | Pass | 8.3645842529E-003 | 9.1894457608E-002 | Pass | Pass |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1088796616 | 0.1975591146 | Pass | Pass | 7.7421984384E-003 | 8.7922026839E-002 | Pass | Pass |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.9901478717E-002 | 0.2214865604 | Pass | Pass | 8.0269270391E-003 | 8.9712374950E-002 | Pass | Pass |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.0237878534E-002 | 6.0323249407E-002 | Pass | Pass | 7.3636221841E-003 | 8.5572330884E-002 | Pass | Pass |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.0126732842E-002 | 0.1199549243 | Pass | Pass | 8.0088072987E-003 | 8.9629897306E-002 | Pass | Pass |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.8124704534E-002 | 0.1342973143 | Pass | Pass | 8.3455562520E-003 | 9.1771191322E-002 | Pass | Pass |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.9326116765E-002 | 0.1442617103 | Pass | Pass | 8.2554268626E-003 | 9.1186636753E-002 | Pass | Pass |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.7065609988E-002 | 5.6303997748E-002 | Pass | Pass | 7.5719874452E-003 | 8.6853178065E-002 | Pass | Pass |
| 18 | LOBBY_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.0001664334E-002 | 0.1175002647 | Pass | Pass | 7.6583972065E-003 | 8.7391608030E-002 | Pass | Pass |
| 19 | MECH_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.0818056140E-002 | 9.2707409291E-002 | Pass | Pass | 7.7433110166E-003 | 8.7922405937E-002 | Pass | Pass |
| 20 | BATH_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.1979887834E-002 | 6.3683448494E-002 | Pass | Pass | 7.6201949068E-003 | 8.7157526694E-002 | Pass | Pass |
| 21 | OFFICES_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.7756052030E-002 | 0.1112925991 | Pass | Pass | 7.8483078066E-003 | 8.8577932833E-002 | Pass | Pass |
| 22 | GYM_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.7563296072E-002 | 0.1628232252 | Pass | Pass | 8.0378529262E-003 | 8.9784376085E-002 | Pass | Pass |
| 23 | KITCHEN_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.3644111266 | 0.4568022234 | Pass | Pass | 1.6771429066 | 6.7084895667 | Pass | Pass |
| 24 | CAFETERIA_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 3.5508618364E-002 | 3.3669079266E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.4019854116E-002 | 0.1014785114 | Pass | Pass | 8.1180532925E-003 | 9.0290730659E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 14305.43 | 64.12 | 732.56 | 3491.12 | 4012.73 | 22606.06 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
| EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 3.00 | 6 | |||
| Feb | 3.00 | 4 | |||
| Mar | 0.00 | 0 | |||
| Apr | 0.00 | 0 | |||
| May | 0.00 | 0 | |||
| Jun | 18.00 | 7 | |||
| Jul | 27.00 | 16 | |||
| Aug | 41.00 | 15 | |||
| Sep | 0.00 | 0 | |||
| Oct | 23.00 | 18 | |||
| Nov | 0.00 | 0 | |||
| Dec | 7.00 | 7 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 44.00 | 32.37 | 180.00 | 90.00 | S |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 212.00 | 161.46 | 180.00 | 90.00 | S |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 12.00 | 9.36 | 270.00 | 90.00 | W |
| CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.020 | 0.020 | 192.00 | 192.00 | 270.00 | 180.00 | |
| CORRIDOR_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 192.00 | 192.00 | 90.00 | 0.00 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 44.00 | 32.37 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 212.00 | 161.46 | 0.00 | 90.00 | N |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 44.00 | 32.37 | 180.00 | 90.00 | S |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 212.00 | 161.46 | 180.00 | 90.00 | S |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 12.00 | 9.36 | 270.00 | 90.00 | W |
| CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.020 | 0.020 | 192.00 | 192.00 | 270.00 | 180.00 | |
| CORRIDOR_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 192.00 | 192.00 | 90.00 | 0.00 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 44.00 | 32.37 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 212.00 | 161.46 | 0.00 | 90.00 | N |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 44.00 | 32.37 | 180.00 | 90.00 | S |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 212.00 | 161.46 | 180.00 | 90.00 | S |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 12.00 | 9.36 | 270.00 | 90.00 | W |
| CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.020 | 0.020 | 192.00 | 192.00 | 270.00 | 180.00 | |
| CORRIDOR_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 192.00 | 192.00 | 90.00 | 0.00 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 44.00 | 32.40 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 140.00 | 105.30 | 0.00 | 90.00 | N |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 315.00 | 315.00 | 270.00 | 180.00 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 315.00 | 315.00 | 90.00 | 0.00 | |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 72.00 | 54.21 | 0.00 | 90.00 | N |
| COMPUTER_CLASS_ZN_1_FLR_1_FLOOR | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 162.00 | 162.00 | 270.00 | 180.00 | |
| COMPUTER_CLASS_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 162.00 | 162.00 | 90.00 | 0.00 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.00 | 26.13 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.021 | 0.021 | 546.00 | 546.00 | 270.00 | 180.00 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 546.00 | 546.00 | 90.00 | 0.00 | |
| LOBBY_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 76.00 | 57.33 | 180.00 | 90.00 | S |
| LOBBY_ZN_1_FLR_1_FLOOR | LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 171.00 | 171.00 | 270.00 | 180.00 | |
| LOBBY_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 171.00 | 171.00 | 90.00 | 0.00 | |
| MECH_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 252.00 | 252.00 | 90.00 | 0.00 | |
| BATH_ZN_1_FLR_1_WALL_5 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 40.00 | 31.20 | 270.00 | 90.00 | W |
| BATH_ZN_1_FLR_1_FLOOR | BATH_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.066 | 0.067 | 190.00 | 190.00 | 270.00 | 180.00 | |
| BATH_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 190.00 | 190.00 | 90.00 | 0.00 | |
| OFFICES_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 84.00 | 63.57 | 180.00 | 90.00 | S |
| OFFICES_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 84.00 | 65.52 | 90.00 | 90.00 | E |
| OFFICES_ZN_1_FLR_1_FLOOR | OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.120 | 0.123 | 441.00 | 441.00 | 270.00 | 180.00 | |
| OFFICES_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 441.00 | 441.00 | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 68.00 | 51.09 | 90.00 | 90.00 | E |
| GYM_ZN_1_FLR_1_FLOOR | GYM_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.060 | 0.061 | 357.00 | 357.00 | 270.00 | 180.00 | |
| GYM_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 357.00 | 343.62 | 90.00 | 0.00 | |
| KITCHEN_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 32.00 | 24.96 | 90.00 | 90.00 | E |
| KITCHEN_ZN_1_FLR_1_FLOOR | KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.060 | 0.061 | 168.00 | 168.00 | 270.00 | 180.00 | |
| KITCHEN_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 168.00 | 168.00 | 90.00 | 0.00 | |
| CAFETERIA_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 60.00 | 44.85 | 90.00 | 90.00 | E |
| CAFETERIA_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 84.00 | 65.52 | 0.00 | 90.00 | N |
| CAFETERIA_ZN_1_FLR_1_FLOOR | CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.144 | 0.148 | 315.00 | 315.00 | 270.00 | 180.00 | |
| CAFETERIA_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 315.00 | 315.00 | 90.00 | 0.00 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 84.00 | 63.57 | 90.00 | 90.00 | E |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 76.00 | 59.28 | 0.00 | 90.00 | N |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.127 | 0.129 | 399.00 | 399.00 | 270.00 | 180.00 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 399.00 | 399.00 | 90.00 | 0.00 |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 90.00 | 90.00 | E |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 90.00 | 90.00 | E |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 90.00 | 90.00 | E |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 72.00 | 72.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 140.00 | 140.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 140.00 | 140.00 | 180.00 | 90.00 | S |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 72.00 | 72.00 | 180.00 | 90.00 | S |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 180.00 | 90.00 | S |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 168.00 | 168.00 | 90.00 | 90.00 | E |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 0.00 | 90.00 | N |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 270.00 | 90.00 | W |
| LOBBY_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| LOBBY_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 0.00 | 90.00 | N |
| LOBBY_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 0.00 | 90.00 | N |
| LOBBY_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MECH_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 180.00 | 90.00 | S |
| MECH_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 48.00 | 48.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 68.00 | 68.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 32.00 | 32.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 20.00 | 20.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 0.00 | 90.00 | N |
| MECH_ZN_1_FLR_1_WALL_7 | INT_WALL | 0.30 | 2.511 | 6.299 | 168.00 | 168.00 | 270.00 | 90.00 | W |
| MECH_ZN_1_FLR_1_FLOOR | MECH_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 252.00 | 252.00 | 270.00 | 180.00 | |
| BATH_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 180.00 | 90.00 | S |
| BATH_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 180.00 | 90.00 | S |
| BATH_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 40.00 | 40.00 | 90.00 | 90.00 | E |
| BATH_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 76.00 | 76.00 | 0.00 | 90.00 | N |
| OFFICES_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 0.00 | 90.00 | N |
| OFFICES_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 48.00 | 48.00 | 270.00 | 90.00 | W |
| OFFICES_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| GYM_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 180.00 | 90.00 | S |
| GYM_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 0.00 | 90.00 | N |
| GYM_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 68.00 | 68.00 | 270.00 | 90.00 | W |
| KITCHEN_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 180.00 | 90.00 | S |
| KITCHEN_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 0.00 | 90.00 | N |
| KITCHEN_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 32.00 | 32.00 | 270.00 | 90.00 | W |
| CAFETERIA_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 180.00 | 90.00 | S |
| CAFETERIA_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 40.00 | 40.00 | 270.00 | 90.00 | W |
| CAFETERIA_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 20.00 | 20.00 | 270.00 | 90.00 | W |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 76.00 | 76.00 | 180.00 | 90.00 | S |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 270.00 | 90.00 | W |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 384.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 384.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 384.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 630.00 | 0.00 | 90.00 | N | ||
| COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 324.00 | 0.00 | 90.00 | N | ||
| MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1092.00 | 0.00 | 90.00 | N | ||
| LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 342.00 | 0.00 | 90.00 | N | ||
| MECH_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 504.00 | 0.00 | 90.00 | N | ||
| BATH_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 380.00 | 0.00 | 90.00 | N | ||
| OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 882.00 | 0.00 | 90.00 | N | ||
| GYM_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 714.00 | 0.00 | 90.00 | N | ||
| KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 336.00 | 0.00 | 90.00 | N | ||
| CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 630.00 | 0.00 | 90.00 | N | ||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 798.00 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 2.64 | 0.00 | 0.00 | 2.64 | 2.64 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | 270.00 | 90.00 | W | |||||||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 2.64 | 0.00 | 0.00 | 2.64 | 2.64 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | 270.00 | 90.00 | W | |||||||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 2.64 | 0.00 | 0.00 | 2.64 | 2.64 | 3.241 | 0.251 | 0.276 | No | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | 270.00 | 90.00 | W | |||||||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 8.43 | 0.00 | 0.00 | 8.43 | 8.43 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.251 | 0.276 | No | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 10.27 | 0.00 | 0.00 | 10.27 | 10.27 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 10.27 | 0.00 | 0.00 | 10.27 | 10.27 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.25 | 10.27 | 0.00 | 0.00 | 10.27 | 10.27 | 3.241 | 0.251 | 0.276 | No | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 1.16 | 0.00 | 0.00 | 1.16 | 1.16 | 3.241 | 0.251 | 0.276 | No | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 14.68 | 0.00 | 0.00 | 14.68 | 14.68 | 3.241 | 0.251 | 0.276 | No | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 1.26 | 0.00 | 0.00 | 1.26 | 1.26 | 3.241 | 0.251 | 0.276 | No | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | 270.00 | 90.00 | W | |||||||
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 6.66 | 0.00 | 0.00 | 6.66 | 6.66 | 3.241 | 0.251 | 0.276 | No | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | 270.00 | 90.00 | W | |||||||
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 1.15 | 0.00 | 0.00 | 1.15 | 1.15 | 3.241 | 0.251 | 0.276 | No | LOBBY_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 15.57 | 0.00 | 0.00 | 15.57 | 15.57 | 3.241 | 0.251 | 0.276 | No | LOBBY_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 8.80 | 0.00 | 0.00 | 8.80 | 8.80 | 3.241 | 0.251 | 0.276 | No | BATH_ZN_1_FLR_1_WALL_5 | 270.00 | 90.00 | W | |||||||
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 1.14 | 0.00 | 0.00 | 1.14 | 1.14 | 3.241 | 0.251 | 0.276 | No | OFFICES_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 17.34 | 0.00 | 0.00 | 17.34 | 17.34 | 3.241 | 0.251 | 0.276 | No | OFFICES_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 18.48 | 0.00 | 0.00 | 18.48 | 18.48 | 3.241 | 0.251 | 0.276 | No | OFFICES_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 1.17 | 0.00 | 0.00 | 1.17 | 1.17 | 3.241 | 0.251 | 0.276 | No | GYM_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 13.79 | 0.00 | 0.00 | 13.79 | 13.79 | 3.241 | 0.251 | 0.276 | No | GYM_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.393 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.393 | 0.402 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.393 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.393 | 0.402 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.393 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.393 | 0.402 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.393 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.393 | 0.402 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.393 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.393 | 0.402 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.393 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.393 | 0.402 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.393 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.393 | 0.402 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.393 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.393 | 0.402 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | NONRESSKYLIGHT_U_0.69_SHGC_0.39 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.393 | 0.402 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.393 | 0.402 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 7.04 | 0.00 | 0.00 | 7.04 | 7.04 | 3.241 | 0.251 | 0.276 | No | KITCHEN_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 1.18 | 0.00 | 0.00 | 1.18 | 1.18 | 3.241 | 0.251 | 0.276 | No | CAFETERIA_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 12.02 | 0.00 | 0.00 | 12.02 | 12.02 | 3.241 | 0.251 | 0.276 | No | CAFETERIA_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 18.48 | 0.00 | 0.00 | 18.48 | 18.48 | 3.241 | 0.251 | 0.276 | No | CAFETERIA_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 1.14 | 0.00 | 0.00 | 1.14 | 1.14 | 3.241 | 0.251 | 0.276 | No | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.25 | 17.33 | 0.00 | 0.00 | 17.33 | 17.33 | 3.241 | 0.251 | 0.276 | No | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.25 | 16.72 | 0.00 | 0.00 | 16.72 | 16.72 | 3.241 | 0.251 | 0.276 | No | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| Total or Average | 565.98 | 3.257 | 0.254 | 0.279 | |||||||||||||||||
| North Total or Average | 204.13 | 3.241 | 0.251 | 0.276 | |||||||||||||||||
| Non-North Total or Average | 361.86 | 3.266 | 0.256 | 0.280 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 |
| LOBBY_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LOBBY_ZN_1_FLR_1_WALL_1 |
| OFFICES_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | OFFICES_ZN_1_FLR_1_WALL_1 |
| GYM_ZN_1_FLR_1_WALL_2_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | GYM_ZN_1_FLR_1_WALL_2 |
| CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CAFETERIA_ZN_1_FLR_1_WALL_2 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | 0.81 | 0.98 | 1.00 | 0.00 | 0.99 | 1.00 | 0.73 | 0.99 | 1.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | 0.81 | 0.98 | 1.00 | 0.00 | 0.99 | 1.00 | 0.73 | 0.99 | 1.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | 0.00 | 0.00 | 0.80 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.46 |
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | 0.00 | 0.00 | 0.87 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.66 |
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | 0.03 | 0.05 | 0.00 | 1.00 | 0.80 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.91 | 0.98 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORRIDOR_POD_1_ZN_1_FLR_1_LIGHTS | CORRIDOR_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | GENERAL | 5.4810 | 192.00 | 1052.35 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 14.50 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORRIDOR_POD_2_ZN_1_FLR_1_LIGHTS | CORRIDOR_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | GENERAL | 5.4810 | 192.00 | 1052.35 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 14.50 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORRIDOR_POD_3_ZN_1_FLR_1_LIGHTS | CORRIDOR_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | GENERAL | 5.4810 | 192.00 | 1052.35 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 14.50 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 315.00 | 4746.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 65.42 |
| COMPUTER_CLASS_ZN_1_FLR_1_LIGHTS | COMPUTER_CLASS_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | GENERAL | 15.0695 | 162.00 | 2441.25 | LightsWired | LTG_SCH_COMPUTER_ROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 33.64 |
| MAIN_CORRIDOR_ZN_1_FLR_1_LIGHTS | MAIN_CORRIDOR_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | GENERAL | 5.4810 | 546.00 | 2992.63 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 41.24 |
| LOBBY_ZN_1_FLR_1_LIGHTS | LOBBY_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | GENERAL | 13.9931 | 171.00 | 2392.81 | LightsWired | LTG_SCH_LOBBY | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 32.97 |
| MECH_ZN_1_FLR_1_LIGHTS | MECH_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | GENERAL | 16.1458 | 252.00 | 4068.75 | LightsWired | LTG_SCH_MECHANICAL | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 56.07 |
| BATH_ZN_1_FLR_1_LIGHTS | BATH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | GENERAL | 9.6875 | 190.00 | 1840.63 | LightsWired | LTG_SCH_BATH | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 25.37 |
| OFFICES_ZN_1_FLR_1_LIGHTS | OFFICES_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GENERAL | 11.8403 | 441.00 | 5221.57 | LightsWired | LTG_SCH_OFFICE | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 71.96 |
| GYM_ZN_1_FLR_1_LIGHTS | GYM_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | GENERAL | 13.3472 | 357.00 | 4764.96 | LightsWired | LTG_SCH_GYM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 65.67 |
| KITCHEN_ZN_1_FLR_1_LIGHTS | KITCHEN_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | GENERAL | 12.9167 | 168.00 | 2170.00 | LightsWired | LTG_SCH_KITCHEN | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 29.90 |
| CAFETERIA_ZN_1_FLR_1_LIGHTS | CAFETERIA_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | GENERAL | 9.6875 | 315.00 | 3051.57 | LightsWired | LTG_SCH_CAFETERIA | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 42.05 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_LIGHTS | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | GENERAL | 16.6840 | 399.00 | 6656.93 | LightsWired | LTG_SCH_LIBRARY | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 91.74 |
| Interior Lighting Total | 12.8652 | 6871.00 | 88396.96 | 1218.18 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| EXTERIOR_LIGHTS | 5897.73 | AstronomicalClock | - | 83.77 | 83.77 | 92.74 | |
| Exterior Lighting Total | 5897.73 | 92.74 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| HEATSYS1 BOILER | Boiler:HotWater | 280269.52 | 0.75 |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | 710881.76 | 543911.71 | 166970.05 | 0.77 | 3.60 | |||
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 39311.76 | 29456.30 | 9855.46 | 0.75 | 3.50 | |||
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 79630.46 | 56123.55 | 23506.91 | 0.70 | 3.50 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| VAV_POD_1 COOLING COIL | 685338.0 | 3.08 | 10.50 | N/A | N/A | 11.34 | |
| PSZ-AC_1:6 COOLING COIL | 37871.9 | 10.90 | 10.90 | ||||
| PSZ-AC_2:7 COOLING COIL | 77073.1 | 11.12 | 11.12 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6239.73 | 5921.07 | - |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23701.48 | 22496.14 | - |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6160.48 | 5845.87 | - |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6227.36 | 5909.33 | - |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23567.05 | 22368.63 | - |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6188.91 | 5872.85 | - |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23475.68 | 22281.96 | - |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6143.06 | 5829.34 | - |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6231.53 | 5913.29 | - |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23584.97 | 22385.63 | - |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6194.43 | 5878.09 | - |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23522.17 | 22326.06 | - |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6150.10 | 5836.02 | - |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6271.71 | 5951.42 | - |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15798.61 | 14995.07 | - |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 7801.17 | 7404.60 | - |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14538.81 | 13796.32 | - |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8420.75 | 7990.70 | - |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4800.60 | 4556.58 | - |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6597.84 | 6260.89 | - |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17998.03 | 17078.87 | - |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15000.73 | 14237.45 | - |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15654.30 | 14854.84 | - |
| VAV_POD_1 HEATING COIL | Coil:Heating:Fuel | 196976.23 | 0.79 | |
| PSZ-AC_1:6 HEATING COIL | Coil:Heating:Fuel | 63053.79 | 0.80 | |
| PSZ-AC_2:7 HEATING COIL | Coil:Heating:Fuel | 78718.84 | 0.79 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| BATH_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 0.28 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| GYM_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.54 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| KITCHEN_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 2.12 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| CAFETERIA_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.38 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.28 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| VAV_POD_1 FAN | Fan:VariableVolume | 0.62 | 1337.13 | 34.59 | 74584.55 | 2156.31 | 1.00 | 1.11 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
| PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.83 | 3041.40 | 1662.00 | 1.00 | 1.23 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 3.24 | 5259.43 | 1622.12 | 1.00 | 1.20 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002452 | 738.41 | 301156.09 | 0.90 | General |
| SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000105 | 13.47 | 127739.32 | 0.30 | General |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| SWH BOOSTER G WATER HEATER | WaterHeater:Mixed | 0.02 | 6000.00 | 0.80 | 1.09 | 0.99 |
| SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 14.75 | 0.47 |
| DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 685338.02 | 3.08 | 10.50 | 11.34 | 34.6957 | 3.32 | 11.32 | 27.5947 | 3.30 | 11.26 | 18.5141 | 3.44 | 11.73 | 7.5925 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 7753.64 | 8916.68 | 90.07 | 0.657 | 0.755 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00772 | 37.45 | 0.00687 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 31516.21 | 36243.64 | 75.98 | 2.670 | 3.070 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00786 | 38.10 | 0.00687 | 0.897 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 6775.24 | 7791.52 | 40.58 | 0.574 | 0.660 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00732 | 37.97 | 0.00687 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 7519.40 | 8647.31 | 87.35 | 0.637 | 0.732 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 24.00 | 24.00 | 0.00774 | 37.15 | 0.00687 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 29899.22 | 34384.10 | 72.08 | 2.533 | 2.912 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00790 | 38.10 | 0.00687 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 7690.89 | 8844.52 | 89.34 | 0.651 | 0.749 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00772 | 37.45 | 0.00687 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 31113.30 | 35780.29 | 75.01 | 2.635 | 3.031 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00787 | 38.10 | 0.00687 | 0.897 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 6755.45 | 7768.77 | 40.46 | 0.572 | 0.658 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00732 | 37.97 | 0.00687 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 7523.62 | 8652.17 | 87.40 | 0.637 | 0.733 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 24.00 | 24.00 | 0.00774 | 37.15 | 0.00687 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 29916.80 | 34404.32 | 72.13 | 2.534 | 2.914 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00790 | 38.10 | 0.00687 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 7697.53 | 8852.16 | 89.42 | 0.652 | 0.750 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00772 | 37.45 | 0.00687 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 31246.56 | 35933.54 | 75.33 | 2.647 | 3.044 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00786 | 38.10 | 0.00687 | 0.897 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 6813.30 | 7835.29 | 40.81 | 0.577 | 0.663 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00732 | 37.97 | 0.00687 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 7579.56 | 8716.49 | 88.05 | 0.642 | 0.738 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:10:00 | 24.00 | 24.00 | 0.00773 | 37.15 | 0.00687 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 20133.56 | 23153.60 | 73.50 | 1.705 | 1.961 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00789 | 38.10 | 0.00687 | 0.592 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 11040.42 | 12696.48 | 78.37 | 0.935 | 1.075 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00783 | 38.10 | 0.00687 | 0.304 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 15010.94 | 17262.59 | 31.62 | 1.271 | 1.462 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00742 | 37.97 | 0.00687 | 0.166 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 7991.28 | 9189.97 | 53.74 | 0.677 | 0.778 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00748 | 38.10 | 0.00687 | 0.096 | 0.00 |
| MECH_ZN_1_FLR_1 | 10196.68 | 11726.18 | 46.53 | 0.863 | 0.993 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00709 | 38.10 | 0.00687 | 0.000 | 0.00 |
| BATH_ZN_1_FLR_1 | 6990.02 | 8038.52 | 42.31 | 0.592 | 0.681 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00731 | 37.45 | 0.00687 | 0.000 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 20235.74 | 23271.10 | 52.77 | 1.713 | 1.970 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00725 | 38.10 | 0.00687 | 0.190 | 0.00 |
| GYM_ZN_1_FLR_1 | 22746.82 | 26158.84 | 73.27 | 1.927 | 2.216 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 23.99 | 0.00807 | 37.99 | 0.00687 | 0.544 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 18766.97 | 21582.02 | 128.46 | 1.591 | 1.830 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.99 | 0.00898 | 36.93 | 0.00687 | 0.255 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 33244.90 | 38231.63 | 121.37 | 2.819 | 3.242 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 24.00 | 23.98 | 0.00915 | 37.45 | 0.00687 | 1.488 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 22497.55 | 25872.18 | 64.84 | 1.905 | 2.191 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00740 | 38.10 | 0.00687 | 0.345 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 2885.77 | 3607.22 | 36.44 | 0.244 | 0.305 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00787 | -5.20 | 0.00281 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 9162.56 | 11453.20 | 24.01 | 0.774 | 0.968 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -5.20 | 0.00281 | 0.897 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 2848.83 | 3561.03 | 18.55 | 0.241 | 0.301 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00798 | -5.20 | 0.00281 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 2880.05 | 3600.07 | 36.36 | 0.243 | 0.304 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00787 | -5.20 | 0.00281 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 9054.72 | 11318.40 | 23.73 | 0.765 | 0.957 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -5.20 | 0.00281 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 2862.27 | 3577.84 | 36.14 | 0.242 | 0.302 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00787 | -5.20 | 0.00281 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 8981.58 | 11226.98 | 23.54 | 0.759 | 0.949 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -5.20 | 0.00281 | 0.897 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 2840.77 | 3550.96 | 18.49 | 0.240 | 0.300 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00798 | -5.20 | 0.00281 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 2881.98 | 3602.48 | 36.39 | 0.244 | 0.304 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00787 | -5.20 | 0.00281 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 9063.29 | 11329.12 | 23.75 | 0.766 | 0.957 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -5.20 | 0.00281 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 2864.83 | 3581.03 | 36.17 | 0.242 | 0.303 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00787 | -5.20 | 0.00281 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 9018.86 | 11273.57 | 23.63 | 0.762 | 0.953 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -5.20 | 0.00281 | 0.897 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 2844.03 | 3555.03 | 18.52 | 0.240 | 0.300 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00798 | -5.20 | 0.00281 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 2900.56 | 3625.70 | 36.62 | 0.245 | 0.306 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00787 | -5.20 | 0.00281 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 6162.40 | 7703.00 | 24.45 | 0.521 | 0.651 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -5.20 | 0.00281 | 0.592 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 2912.48 | 3640.60 | 22.47 | 0.246 | 0.308 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -5.20 | 0.00281 | 0.304 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 6723.30 | 8404.12 | 15.39 | 0.568 | 0.710 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00797 | -5.20 | 0.00281 | 0.166 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 3894.31 | 4867.89 | 28.47 | 0.329 | 0.411 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00791 | -5.20 | 0.00281 | 0.096 | 0.00 |
| MECH_ZN_1_FLR_1 | 1782.25 | 2227.81 | 8.84 | 0.151 | 0.188 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:40:00 | 21.00 | 21.00 | 0.00800 | -5.20 | 0.00281 | 0.000 | 0.00 |
| BATH_ZN_1_FLR_1 | 3051.19 | 3813.99 | 20.07 | 0.258 | 0.322 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00794 | -5.20 | 0.00281 | 0.000 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 8323.49 | 10404.37 | 23.59 | 0.703 | 0.879 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00790 | -5.20 | 0.00281 | 0.190 | 0.00 |
| GYM_ZN_1_FLR_1 | 6044.71 | 7555.89 | 21.16 | 0.511 | 0.639 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00794 | -5.20 | 0.00281 | 0.544 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.000 | 0.255 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 23.27 | 0.02090 | -5.20 | 0.00281 | 0.255 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 6423.44 | 8029.29 | 25.49 | 0.543 | 1.488 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00789 | -5.20 | 0.00281 | 1.488 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 7239.65 | 9049.56 | 22.68 | 0.612 | 0.765 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -5.20 | 0.00281 | 0.345 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| VAV_POD_1 | 34.59 | 34.59 | 12.38 | 12.38 | 34.5889 | 14.1579 | 34.5889 | 0.4093 | 0.3000 |
| PSZ-AC_1:6 | 1.83 | 1.83 | 0.25 | 0.25 | 1.8300 | 1.8300 | 1.8300 | 1.0000 | 1.0000 |
| PSZ-AC_2:7 | 3.24 | 3.24 | 1.49 | 1.49 | 3.2423 | 3.2423 | 3.2423 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | 6239.729 | 6239.729 | 0.304853 | 0.00005459 | 145.539 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6239.73 | 6239.73 | 0.304853 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00786627 | 44.1127 | 3607.22 | 0.00 | 6268.35 | 6268.35 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | 23701.485 | 23701.485 | 1.418318 | 0.00020735 | 526.411 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23701.48 | 23701.48 | 1.418318 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00788791 | 44.2324 | 11453.20 | 0.00 | 23813.71 | 23813.71 |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX | 6160.482 | 6160.482 | 0.300956 | 0.00005389 | 143.694 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6160.48 | 6160.48 | 0.300956 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00797923 | 44.7377 | 3561.03 | 0.00 | 6188.74 | 6188.74 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | 6227.360 | 6227.360 | 0.304248 | 0.00005448 | 145.250 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6227.36 | 6227.36 | 0.304248 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00786602 | 44.1113 | 3600.07 | 0.00 | 6255.93 | 6255.93 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | 23567.054 | 23567.054 | 1.418364 | 0.00020617 | 522.794 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23567.05 | 23567.05 | 1.418364 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00788661 | 44.2251 | 11318.40 | 0.00 | 23678.69 | 23678.69 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | 6188.913 | 6188.913 | 0.302370 | 0.00005414 | 144.354 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6188.91 | 6188.91 | 0.302370 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00786520 | 44.1068 | 3577.84 | 0.00 | 6217.30 | 6217.30 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | 23475.679 | 23475.679 | 1.418372 | 0.00020538 | 520.342 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23475.68 | 23475.68 | 1.418372 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00788570 | 44.2201 | 11226.98 | 0.00 | 23586.91 | 23586.91 |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX | 6143.060 | 6143.060 | 0.300105 | 0.00005374 | 143.287 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6143.06 | 6143.06 | 0.300105 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00797917 | 44.7374 | 3550.96 | 0.00 | 6171.24 | 6171.24 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | 6231.528 | 6231.528 | 0.304452 | 0.00005452 | 145.348 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6231.53 | 6231.53 | 0.304452 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00786610 | 44.1118 | 3602.48 | 0.00 | 6260.11 | 6260.11 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | 23584.970 | 23584.970 | 1.419198 | 0.00020633 | 523.210 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23584.97 | 23584.97 | 1.419198 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00788671 | 44.2257 | 11329.12 | 0.00 | 23696.69 | 23696.69 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | 6194.434 | 6194.434 | 0.302640 | 0.00005419 | 144.482 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6194.43 | 6194.43 | 0.302640 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00786532 | 44.1075 | 3581.03 | 0.00 | 6222.85 | 6222.85 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | 23522.168 | 23522.168 | 1.418359 | 0.00020578 | 521.590 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 23522.17 | 23522.17 | 1.418359 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00788616 | 44.2227 | 11273.57 | 0.00 | 23633.61 | 23633.61 |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX | 6150.101 | 6150.101 | 0.300449 | 0.00005380 | 143.452 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6150.10 | 6150.10 | 0.300449 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00797919 | 44.7375 | 3555.03 | 0.00 | 6178.31 | 6178.31 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | 6271.713 | 6271.713 | 0.306415 | 0.00005487 | 146.285 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6271.71 | 6271.71 | 0.306415 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00786694 | 44.1164 | 3625.70 | 0.00 | 6300.48 | 6300.48 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | 15798.605 | 15798.605 | 0.937445 | 0.00013821 | 351.519 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15798.61 | 15798.61 | 0.937445 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00788990 | 44.2434 | 7703.00 | 0.00 | 15873.36 | 15873.36 |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX | 7801.174 | 7801.174 | 0.481790 | 0.00006825 | 172.134 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 7801.17 | 7801.17 | 0.481790 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00788042 | 44.1909 | 3640.60 | 0.00 | 7838.20 | 7838.20 |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX | 14538.813 | 14538.813 | 0.710262 | 0.00012719 | 339.119 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14538.81 | 14538.81 | 0.710262 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00797362 | 44.7067 | 8404.12 | 0.00 | 14605.51 | 14605.51 |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | LOBBY_ZN_1_FLR_1 VAV BOX | 8420.748 | 8420.748 | 0.411398 | 0.00007367 | 196.412 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8420.75 | 8420.75 | 0.411398 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00790514 | 44.3278 | 4867.89 | 0.00 | 8459.38 | 8459.38 |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_ZN_1_FLR_1 VAV BOX | 4800.602 | 4800.602 | 0.297857 | 0.00004200 | 105.826 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:40:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:40:00 | 4800.60 | 4800.60 | 0.297857 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00800000 | 44.8527 | 2227.81 | 0.00 | 4823.40 | 4823.40 |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6597.842 | 6597.842 | 0.322332 | 0.00005772 | 153.894 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6597.84 | 6597.84 | 0.322332 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00793589 | 44.4979 | 3813.99 | 0.00 | 6628.11 | 6628.11 |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | OFFICES_ZN_1_FLR_1 VAV BOX | 17998.027 | 17998.027 | 0.879302 | 0.00015745 | 419.799 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 17998.03 | 17998.03 | 0.879302 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00790195 | 44.3101 | 10404.37 | 0.00 | 18080.59 | 18080.59 |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15000.728 | 15000.728 | 0.862001 | 0.00013123 | 336.113 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 15000.73 | 15000.73 | 0.862001 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00794489 | 44.5478 | 7555.89 | 0.00 | 15071.54 | 15071.54 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15654.302 | 15654.302 | 0.764803 | 0.00013695 | 365.131 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 15654.30 | 15654.30 | 0.764803 | 12.89 | 10.37 | 0.00800000 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 0.0000 | 21.00 | 0.00789283 | 44.2596 | 9049.56 | 0.00 | 15726.12 | 15726.12 |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | VAV_POD_1 | 710881.759 | 543911.706 | 34.588919 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 661061.17 | 628121.64 | 34.588919 | 28.35 | 15.54 | 0.00745372 | 10.86 | 8.51 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 30.8865 | 24.00 | 0.00771393 | 36.0658 | 355121.76 | 0.00 | 712937.78 | 509073.62 |
| VAV_POD_1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | VAV_POD_1 | 196976.232 | 196976.232 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 01:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 196976.23 | 196976.23 | 10.376676 | -5.20 | -5.20 | 0.00280840 | 12.89 | 10.37 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 102.9549 | 21.00 | 0.00790334 | 44.3180 | 117126.23 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:6 | 39311.760 | 29456.302 | 1.829970 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 19655.88 | 16103.26 | 1.219980 | 25.76 | 15.67 | 0.00868362 | 11.33 | 8.71 | 0.00700000 | 36.93 | 0.00686961 | 17.82 | 20.8867 | 23.99 | 0.00897707 | 41.9152 | 18766.97 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_1:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:6 | 63053.787 | 63053.787 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 63053.79 | 63053.79 | 1.829966 | -0.72 | -0.72 | 0.01866422 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 13.9245 | 23.52 | 0.02122923 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:7 | 79630.460 | 56123.548 | 3.242310 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 39815.23 | 35664.06 | 2.161540 | 30.53 | 16.77 | 0.00810647 | 11.37 | 8.73 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 68.8483 | 23.98 | 0.00917563 | 42.8378 | 32885.13 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_2:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:7 | 78718.839 | 78718.839 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 78718.84 | 78718.84 | 3.242313 | 8.97 | 6.09 | 0.00555815 | 32.11 | 17.18 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 45.8989 | 21.00 | 0.00789101 | 44.2498 | 6409.75 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6239.729 | 6239.729 | 0.304853 | 0.00005459 | 145.539 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 2.1824 | 2.226332 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6239.73 | 6239.73 | 1.0000 | 0.31836732 | 0.304853 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.05458230 | 60.00 | 32.22 | 27.78 | 0.000 | 6239.73 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00786627 | 21.00 | 0.00786627 | 44.1127 | 3607.22 | 0.00 | 6268.35 | 6268.35 | 0.31836732 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.9 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23701.485 | 23701.485 | 1.418318 | 0.00020735 | 526.411 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 8.2898 | 8.456676 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 23701.48 | 23701.48 | 1.0000 | 1.48119438 | 1.418318 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.20732977 | 60.00 | 32.22 | 27.78 | 0.000 | 23701.48 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00788791 | 21.00 | 0.00788791 | 44.2324 | 11453.20 | 0.00 | 23813.71 | 23813.71 | 1.48119438 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.57 | 17.55 | 0.00800000 | 49137.2 | |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX | CORRIDOR_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6160.482 | 6160.482 | 0.300956 | 0.00005389 | 143.694 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 2.1547 | 2.198056 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6160.48 | 6160.48 | 1.0000 | 0.31429759 | 0.300956 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.05388908 | 60.00 | 32.22 | 27.78 | 0.000 | 6160.48 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00797923 | 21.00 | 0.00797923 | 44.7377 | 3561.03 | 0.00 | 6188.74 | 6188.74 | 0.31429759 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.5 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6227.360 | 6227.360 | 0.304248 | 0.00005448 | 145.250 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 2.1781 | 2.221918 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6227.36 | 6227.36 | 1.0000 | 0.31773629 | 0.304248 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.05447410 | 60.00 | 32.22 | 27.78 | 0.000 | 6227.36 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00786602 | 21.00 | 0.00786602 | 44.1113 | 3600.07 | 0.00 | 6255.93 | 6255.93 | 0.31773629 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.9 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23567.054 | 23567.054 | 1.418364 | 0.00020617 | 522.794 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 8.2428 | 8.408711 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 23567.05 | 23567.05 | 1.0000 | 1.48124262 | 1.418364 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.20615383 | 60.00 | 32.22 | 27.78 | 0.000 | 23567.05 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00788661 | 21.00 | 0.00788661 | 44.2251 | 11318.40 | 0.00 | 23678.69 | 23678.69 | 1.48124262 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.48 | 17.52 | 0.00800000 | 49045.5 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6188.913 | 6188.913 | 0.302370 | 0.00005414 | 144.354 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 2.1646 | 2.208201 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6188.91 | 6188.91 | 1.0000 | 0.31577483 | 0.302370 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.05413779 | 60.00 | 32.22 | 27.78 | 0.000 | 6188.91 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00786520 | 21.00 | 0.00786520 | 44.1068 | 3577.84 | 0.00 | 6217.30 | 6217.30 | 0.31577483 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.9 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23475.679 | 23475.679 | 1.418372 | 0.00020538 | 520.342 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 8.2109 | 8.376109 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 23475.68 | 23475.68 | 1.0000 | 1.48125088 | 1.418372 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.20535453 | 60.00 | 32.22 | 27.78 | 0.000 | 23475.68 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00788570 | 21.00 | 0.00788570 | 44.2201 | 11226.98 | 0.00 | 23586.91 | 23586.91 | 1.48125088 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.42 | 17.50 | 0.00800000 | 48983.5 | |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX | CORRIDOR_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6143.060 | 6143.060 | 0.300105 | 0.00005374 | 143.287 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 2.1486 | 2.191840 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6143.06 | 6143.06 | 1.0000 | 0.31340876 | 0.300105 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.05373668 | 60.00 | 32.22 | 27.78 | 0.000 | 6143.06 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00797917 | 21.00 | 0.00797917 | 44.7374 | 3550.96 | 0.00 | 6171.24 | 6171.24 | 0.31340876 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.5 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6231.528 | 6231.528 | 0.304452 | 0.00005452 | 145.348 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 2.1795 | 2.223405 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6231.53 | 6231.53 | 1.0000 | 0.31794891 | 0.304452 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.05451056 | 60.00 | 32.22 | 27.78 | 0.000 | 6231.53 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00786610 | 21.00 | 0.00786610 | 44.1118 | 3602.48 | 0.00 | 6260.11 | 6260.11 | 0.31794891 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.9 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23584.970 | 23584.970 | 1.419198 | 0.00020633 | 523.210 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 8.2491 | 8.415104 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 23584.97 | 23584.97 | 1.0000 | 1.48211349 | 1.419198 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.20631056 | 60.00 | 32.22 | 27.78 | 0.000 | 23584.97 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00788671 | 21.00 | 0.00788671 | 44.2257 | 11329.12 | 0.00 | 23696.69 | 23696.69 | 1.48211349 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.48 | 17.52 | 0.00800000 | 49048.3 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6194.434 | 6194.434 | 0.302640 | 0.00005419 | 144.482 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 2.1666 | 2.210171 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6194.43 | 6194.43 | 1.0000 | 0.31605650 | 0.302640 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.05418608 | 60.00 | 32.22 | 27.78 | 0.000 | 6194.43 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00786532 | 21.00 | 0.00786532 | 44.1075 | 3581.03 | 0.00 | 6222.85 | 6222.85 | 0.31605650 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.9 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23522.168 | 23522.168 | 1.418359 | 0.00020578 | 521.590 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 8.2271 | 8.392696 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 23522.17 | 23522.17 | 1.0000 | 1.48123728 | 1.418359 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.20576119 | 60.00 | 32.22 | 27.78 | 0.000 | 23522.17 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00788616 | 21.00 | 0.00788616 | 44.2227 | 11273.57 | 0.00 | 23633.61 | 23633.61 | 1.48123728 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.45 | 17.51 | 0.00800000 | 49015.1 | |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX | CORRIDOR_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6150.101 | 6150.101 | 0.300449 | 0.00005380 | 143.452 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 2.1511 | 2.194352 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6150.10 | 6150.10 | 1.0000 | 0.31376797 | 0.300449 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.05379828 | 60.00 | 32.22 | 27.78 | 0.000 | 6150.10 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00797919 | 21.00 | 0.00797919 | 44.7375 | 3555.03 | 0.00 | 6178.31 | 6178.31 | 0.31376797 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.5 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6271.713 | 6271.713 | 0.306415 | 0.00005487 | 146.285 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 2.1936 | 2.237744 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6271.71 | 6271.71 | 1.0000 | 0.31999908 | 0.306415 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.05486209 | 60.00 | 32.22 | 27.78 | 0.000 | 6271.71 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00786694 | 21.00 | 0.00786694 | 44.1164 | 3625.70 | 0.00 | 6300.48 | 6300.48 | 0.31999908 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.9 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15798.605 | 15798.605 | 0.937445 | 0.00013821 | 351.519 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 5.5257 | 5.636933 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15798.61 | 15798.61 | 1.0000 | 0.97900393 | 0.937445 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.13819899 | 60.00 | 32.22 | 27.78 | 0.000 | 15798.61 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00788990 | 21.00 | 0.00788990 | 44.2434 | 7703.00 | 0.00 | 15873.36 | 15873.36 | 0.97900393 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.70 | 17.60 | 0.00800000 | 49273.6 | |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX | COMPUTER_CLASS_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7801.174 | 7801.174 | 0.481790 | 0.00006825 | 172.134 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 2.7285 | 2.783454 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 7801.17 | 7801.17 | 1.0000 | 0.50314824 | 0.481790 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.06824111 | 60.00 | 32.22 | 27.78 | 0.000 | 7801.17 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00788042 | 21.00 | 0.00788042 | 44.1909 | 3640.60 | 0.00 | 7838.20 | 7838.20 | 0.50314824 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.08 | 17.39 | 0.00800000 | 48638.1 | |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX | MAIN_CORRIDOR_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14538.813 | 14538.813 | 0.710262 | 0.00012719 | 339.119 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 5.0851 | 5.187440 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 14538.81 | 14538.81 | 1.0000 | 0.74174935 | 0.710262 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.12717891 | 60.00 | 32.22 | 27.78 | 0.000 | 14538.81 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00797362 | 21.00 | 0.00797362 | 44.7067 | 8404.12 | 0.00 | 14605.51 | 14605.51 | 0.74174935 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.5 | |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | LOBBY_ZN_1_FLR_1 VAV BOX | LOBBY_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8420.748 | 8420.748 | 0.411398 | 0.00007367 | 196.412 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 2.9452 | 3.004518 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8420.75 | 8420.75 | 1.0000 | 0.42963638 | 0.411398 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.07366086 | 60.00 | 32.22 | 27.78 | 0.000 | 8420.75 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00790514 | 21.00 | 0.00790514 | 44.3278 | 4867.89 | 0.00 | 8459.38 | 8459.38 | 0.42963638 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.4 | |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_ZN_1_FLR_1 VAV BOX | MECH_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4800.602 | 4800.602 | 0.297857 | 0.00004200 | 105.826 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 1.6791 | 1.712852 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:40:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:40:00 | Sensible | 4800.60 | 4800.60 | 1.0000 | 0.31106197 | 0.297857 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.04199348 | 60.00 | 32.22 | 27.78 | 0.000 | 4800.60 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 44.8527 | 2227.81 | 0.00 | 4823.40 | 4823.40 | 0.31106197 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.01 | 17.36 | 0.00800000 | 48566.0 | |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BATH_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6597.842 | 6597.842 | 0.322332 | 0.00005772 | 153.894 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 2.3077 | 2.354106 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6597.84 | 6597.84 | 1.0000 | 0.33662195 | 0.322332 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.05771491 | 60.00 | 32.22 | 27.78 | 0.000 | 6597.84 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00793589 | 21.00 | 0.00793589 | 44.4979 | 3813.99 | 0.00 | 6628.11 | 6628.11 | 0.33662195 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.9 | |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | OFFICES_ZN_1_FLR_1 VAV BOX | OFFICES_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17998.027 | 17998.027 | 0.879302 | 0.00015745 | 419.799 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 6.2950 | 6.421686 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 17998.03 | 17998.03 | 1.0000 | 0.91828271 | 0.879302 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.15743853 | 60.00 | 32.22 | 27.78 | 0.000 | 17998.03 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00790195 | 21.00 | 0.00790195 | 44.3101 | 10404.37 | 0.00 | 18080.59 | 18080.59 | 0.91828271 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.4 | |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | GYM_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15000.728 | 15000.728 | 0.862001 | 0.00013123 | 336.113 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 5.2467 | 5.352251 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | Sensible | 15000.73 | 15000.73 | 1.0000 | 0.90021501 | 0.862001 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.13121952 | 60.00 | 32.22 | 27.78 | 0.000 | 15000.73 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00794489 | 21.00 | 0.00794489 | 44.5478 | 7555.89 | 0.00 | 15071.54 | 15071.54 | 0.90021501 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.22 | 17.78 | 0.00800000 | 49802.0 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15654.302 | 15654.302 | 0.764803 | 0.00013695 | 365.131 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.45166987 | 54.44 | 82.22 | 27.78 | 285910.05 | 5.4753 | 5.585446 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 15654.30 | 15654.30 | 1.0000 | 0.79870837 | 0.764803 | 12.89 | 10.37 | 0.00800000 | 33150.5 | 32.11 | 17.18 | 0.00800000 | 52751.6 | 0.13693670 | 60.00 | 32.22 | 27.78 | 0.000 | 15654.30 | -5.20 | 0.00280840 | -5.20 | 0.00000000 | 0.0000 | 21.00 | 0.00789283 | 21.00 | 0.00789283 | 44.2596 | 9049.56 | 0.00 | 15726.12 | 15726.12 | 0.79870837 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.3 | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | VAV_POD_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1; MULT_CLASS_1_POD_1_ZN_1_FLR_1; CORRIDOR_POD_1_ZN_1_FLR_1; CORNER_CLASS_2_POD_1_ZN_1_FLR_1; MULT_CLASS_2_POD_1_ZN_1_FLR_1; CORNER_CLASS_1_POD_2_ZN_1_FLR_1; MULT_CLASS_1_POD_2_ZN_1_FLR_1; CORRIDOR_POD_2_ZN_1_FLR_1; CORNER_CLASS_2_POD_2_ZN_1_FLR_1; MULT_CLASS_2_POD_2_ZN_1_FLR_1; CORNER_CLASS_1_POD_3_ZN_1_FLR_1; MULT_CLASS_1_POD_3_ZN_1_FLR_1; CORRIDOR_POD_3_ZN_1_FLR_1; CORNER_CLASS_2_POD_3_ZN_1_FLR_1; MULT_CLASS_2_POD_3_ZN_1_FLR_1; COMPUTER_CLASS_ZN_1_FLR_1; MAIN_CORRIDOR_ZN_1_FLR_1; LOBBY_ZN_1_FLR_1; MECH_ZN_1_FLR_1; BATH_ZN_1_FLR_1; OFFICES_ZN_1_FLR_1; GYM_ZN_1_FLR_1; LIBRARY_MEDIA_CENTER_ZN_1_FLR_1; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 710881.759 | 543911.706 | 34.588919 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.6961 | 1004.8586 | 1.0443 | VAV_POD_1 FAN | Fan:VariableVolume | 34.588919 | 36.12230571 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 661061.17 | 628121.64 | 0.9299 | 36.12230571 | 34.588919 | 28.35 | 15.54 | 0.00745372 | 47523.9 | 10.86 | 8.51 | 0.00700000 | 28562.5 | -999.0 | -999.00 | -999.00 | -999.00 | 74584.553 | 586476.62 | 38.10 | 0.00687148 | 18.17 | 10.68330000 | 30.8865 | 24.00 | 0.00771393 | 24.00 | 0.00771393 | 36.0658 | 355121.76 | 0.00 | 712937.78 | 509073.62 | 34.69574769 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.30 | 12.27 | 0.00888090 | 34774.1 | |
| VAV_POD_1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | VAV_POD_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1; MULT_CLASS_1_POD_1_ZN_1_FLR_1; CORRIDOR_POD_1_ZN_1_FLR_1; CORNER_CLASS_2_POD_1_ZN_1_FLR_1; MULT_CLASS_2_POD_1_ZN_1_FLR_1; CORNER_CLASS_1_POD_2_ZN_1_FLR_1; MULT_CLASS_1_POD_2_ZN_1_FLR_1; CORRIDOR_POD_2_ZN_1_FLR_1; CORNER_CLASS_2_POD_2_ZN_1_FLR_1; MULT_CLASS_2_POD_2_ZN_1_FLR_1; CORNER_CLASS_1_POD_3_ZN_1_FLR_1; MULT_CLASS_1_POD_3_ZN_1_FLR_1; CORRIDOR_POD_3_ZN_1_FLR_1; CORNER_CLASS_2_POD_3_ZN_1_FLR_1; MULT_CLASS_2_POD_3_ZN_1_FLR_1; COMPUTER_CLASS_ZN_1_FLR_1; MAIN_CORRIDOR_ZN_1_FLR_1; LOBBY_ZN_1_FLR_1; MECH_ZN_1_FLR_1; BATH_ZN_1_FLR_1; OFFICES_ZN_1_FLR_1; GYM_ZN_1_FLR_1; LIBRARY_MEDIA_CENTER_ZN_1_FLR_1; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 196976.232 | 196976.232 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | VAV_POD_1 FAN | Fan:VariableVolume | 34.588919 | 36.12230571 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 01:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 196976.23 | 196976.23 | 1.0000 | 10.83669171 | 10.376676 | -5.20 | -5.20 | 0.00280840 | 1771.3 | 12.89 | 10.37 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 196976.23 | -5.20 | 0.00280840 | -5.20 | 10.68330000 | 102.9549 | 21.00 | 0.00790334 | 21.00 | 0.00790334 | 44.3180 | 117126.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:6 | KITCHEN_ZN_1_FLR_1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 39311.760 | 29456.302 | 1.829970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9824 | 1004.8586 | 1.0443 | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.829966 | 1.91109131 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 19655.88 | 16103.26 | 1.0000 | 1.27406383 | 1.219980 | 25.76 | 15.67 | 0.00868362 | 48013.5 | 11.33 | 8.71 | 0.00700000 | 29039.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19655.88 | 36.93 | 0.00686961 | 17.82 | 0.25481392 | 20.8867 | 23.95 | 0.00897707 | 23.99 | 0.00897707 | 41.9152 | 18766.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_1:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:6 | KITCHEN_ZN_1_FLR_1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 63053.787 | 63053.787 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.829966 | 1.91109131 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 63053.79 | 63053.79 | 1.0000 | 1.91109131 | 1.829966 | -0.72 | -0.72 | 0.01866422 | 45925.4 | 32.11 | 17.18 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 63053.79 | -5.20 | 0.00280840 | -5.20 | 0.25481392 | 13.9245 | 0.00 | 0.02122923 | 23.52 | 0.02122923 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:7 | CAFETERIA_ZN_1_FLR_1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 79630.460 | 56123.548 | 3.242310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.9095 | 1004.8586 | 1.0443 | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.242313 | 3.38604990 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 39815.23 | 35664.06 | 1.0000 | 2.25736481 | 2.161540 | 30.53 | 16.77 | 0.00810647 | 51414.6 | 11.37 | 8.73 | 0.00700000 | 29075.4 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39815.23 | 38.10 | 0.00687148 | 18.17 | 1.48818443 | 68.8483 | 23.98 | 0.00917563 | 23.98 | 0.00917563 | 42.8378 | 32885.13 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_2:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:7 | CAFETERIA_ZN_1_FLR_1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 78718.839 | 78718.839 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.242313 | 3.38604990 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 78718.84 | 78718.84 | 1.0000 | 3.38604990 | 3.242313 | 8.97 | 6.09 | 0.00555815 | 23011.2 | 32.11 | 17.18 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 78718.84 | -5.20 | 0.00280840 | -5.20 | 1.48818443 | 45.8989 | 21.00 | 0.00789101 | 21.00 | 0.00789101 | 44.2498 | 6409.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| VAV_POD_1_OA_CONTROLLER | FixedDryBulb | 0.00 | 34.59 | - | |||
| PSZ-AC_1:6_OA_CONTROLLER | FixedDryBulb | 0.25 | 1.83 | - | |||
| PSZ-AC_2:7_OA_CONTROLLER | FixedDryBulb | 1.49 | 3.24 | - |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| LOBBY_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000559 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MECH_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| BATH_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| OFFICES_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| GYM_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001524 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000864 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1519.83 | 1169.50 | 88.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1407.17 | 1030.50 | 54.17 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 1086.50 | 1533.33 | 47.50 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1519.00 | 1596.00 | 252.33 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1190.67 | 1662.00 | 143.33 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1511.17 | 1181.83 | 88.17 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1369.17 | 1059.67 | 53.50 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 1082.33 | 1537.00 | 49.67 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1520.67 | 1595.50 | 254.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1190.83 | 1663.50 | 144.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1515.00 | 1168.83 | 86.33 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1396.50 | 1023.17 | 53.17 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 1110.33 | 1502.17 | 38.50 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1526.50 | 1579.17 | 243.67 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1245.00 | 1627.17 | 139.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 1532.67 | 1360.67 | 205.33 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 1372.00 | 1402.17 | 84.83 |
| LOBBY_ZN_1_FLR_1 | 1597.33 | 1759.17 | 500.33 |
| MECH_ZN_1_FLR_1 | 2402.17 | 1122.83 | 610.33 |
| BATH_ZN_1_FLR_1 | 1992.67 | 1665.17 | 622.00 |
| OFFICES_ZN_1_FLR_1 | 1281.83 | 975.33 | 25.83 |
| GYM_ZN_1_FLR_1 | 1731.00 | 1014.83 | 136.67 |
| KITCHEN_ZN_1_FLR_1 | 2769.17 | 186.00 | 181.50 |
| CAFETERIA_ZN_1_FLR_1 | 1524.67 | 766.33 | 93.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 1601.33 | 1125.67 | 22.17 |
| Facility | 3051.67 | 2609.33 | 1200.17 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.00 | 2.67 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 0.00 | 0.33 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.00 | 1.33 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.00 | 1.83 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 0.00 | 0.17 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 281.33 | 210.67 | 148.67 | 201.50 |
| MECH_ZN_1_FLR_1 | 0.00 | 30.83 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 0.00 | 25.17 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 0.00 | 26.50 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 0.00 | 1.33 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 0.00 | 1011.50 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 2.83 | 109.17 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.00 | 7.83 | 0.00 | 0.00 |
| Facility | 284.17 | 1338.50 | 148.67 | 201.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.435 | 0.026 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.363 | 0.014 | 0.000 | 0.000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.911 | 0.002 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.147 | 0.026 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.069 | 0.014 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.421 | 0.026 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.345 | 0.014 | 0.000 | 0.000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.907 | 0.002 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.148 | 0.026 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.070 | 0.014 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.429 | 0.026 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.359 | 0.014 | 0.000 | 0.000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.937 | 0.002 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.159 | 0.026 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 45.65 | 84.77 | 1260.00 | 2.084 | 0.014 | 0.000 | 0.000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 38.16 | 43.60 | 648.00 | 2.422 | 0.014 | 0.000 | 0.000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 15.83 | 29.39 | 2184.00 | 0.857 | 0.002 | 0.000 | 0.000 |
| LOBBY_ZN_1_FLR_1 | 9.91 | 18.41 | 684.00 | 1.419 | 2.700 | 0.000 | 0.000 |
| MECH_ZN_1_FLR_1 | 2.19 | 4.07 | 1008.00 | 0.829 | 0.000 | 0.000 | 0.000 |
| BATH_ZN_1_FLR_1 | 5.51 | 10.23 | 760.00 | 0.707 | 0.007 | 0.000 | 0.000 |
| OFFICES_ZN_1_FLR_1 | 14.92 | 23.74 | 1764.00 | 1.520 | 0.012 | 0.000 | 0.000 |
| GYM_ZN_1_FLR_1 | 64.64 | 115.31 | 1428.00 | 2.153 | 0.006 | 0.000 | 0.000 |
| KITCHEN_ZN_1_FLR_1 | 14.54 | 26.99 | 672.00 | 4.875 | 0.006 | 0.000 | 0.000 |
| CAFETERIA_ZN_1_FLR_1 | 209.95 | 339.07 | 1260.00 | 5.740 | 0.015 | 0.000 | 0.000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 23.13 | 42.95 | 1596.00 | 1.832 | 0.013 | 0.000 | 0.000 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.295 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.136 | 0.000 | 0.000 | 0.000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.410 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.231 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.050 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.301 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.106 | 0.000 | 0.000 | 0.000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.409 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.232 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.051 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.306 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.115 | 0.000 | 0.000 | 0.000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.467 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.235 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 45.65 | 84.77 | 1260.00 | 1.067 | 0.000 | 0.000 | 0.000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 38.16 | 43.60 | 648.00 | 1.436 | 0.000 | 0.000 | 0.000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 15.83 | 29.39 | 2184.00 | 0.420 | 0.000 | 0.000 | 0.000 |
| LOBBY_ZN_1_FLR_1 | 9.91 | 18.41 | 684.00 | 0.565 | 0.000 | 0.000 | 0.000 |
| MECH_ZN_1_FLR_1 | 2.19 | 4.07 | 1008.00 | 0.411 | 0.000 | 0.000 | 0.000 |
| BATH_ZN_1_FLR_1 | 5.51 | 10.23 | 760.00 | 0.304 | 0.000 | 0.000 | 0.000 |
| OFFICES_ZN_1_FLR_1 | 14.92 | 23.74 | 1764.00 | 0.697 | 0.000 | 0.000 | 0.000 |
| GYM_ZN_1_FLR_1 | 64.64 | 115.31 | 1428.00 | 1.105 | 0.000 | 0.000 | 0.000 |
| KITCHEN_ZN_1_FLR_1 | 14.54 | 26.99 | 672.00 | 0.000 | 0.000 | 0.000 | 0.000 |
| CAFETERIA_ZN_1_FLR_1 | 209.95 | 339.07 | 1260.00 | 4.204 | 0.000 | 0.000 | 0.000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 23.13 | 42.95 | 1596.00 | 0.853 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 5.56 | 10.33 | 768.00 | 192.00 | 0.0000 | 0.059 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 5.56 | 10.33 | 768.00 | 192.00 | 0.0000 | 0.059 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 5.56 | 10.33 | 768.00 | 192.00 | 0.0000 | 0.059 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 45.65 | 84.77 | 1260.00 | 315.00 | 0.0000 | 0.592 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | 38.16 | 43.60 | 648.00 | 162.00 | 0.0000 | 0.304 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | 15.83 | 29.39 | 2184.00 | 546.00 | 0.0000 | 0.166 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | 9.91 | 18.41 | 684.00 | 171.00 | 0.0000 | 0.096 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | 2.19 | 4.07 | 1008.00 | 252.00 | 0.0000 | 0.000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | 5.51 | 10.23 | 760.00 | 190.00 | 0.0000 | 0.000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | 14.92 | 23.74 | 1764.00 | 441.00 | 0.0000 | 0.190 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | 64.64 | 115.31 | 1428.00 | 357.00 | 0.0000 | 0.544 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | 14.54 | 26.99 | 672.00 | 168.00 | 0.4528 | 0.198 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | 209.95 | 339.07 | 1260.00 | 315.00 | 1.4882 | 1.488 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | 23.13 | 42.95 | 1596.00 | 399.00 | 0.0000 | 0.345 |
| Total Facility | 892.82 | 1571.19 | 27484.00 | 6871.00 | 1.9410 | 9.699 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 3762826.21 | 0.00 | 3762826.21 | 209444.06 | 3972270.28 | 5868225.25 | 5812.77 | 89.09 | 2858.14 | 1351.62 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 17689897.84 | 0.00 | 17689897.84 | 555026.77 | 18244924.61 | 28274176.21 | 6412.81 | 66.89 | 2280.30 | 1351.62 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 2695408.72 | 0.00 | 2695408.72 | 31416.61 | 2726825.33 | 1845537.18 | 4865.91 | 2.04 | 3892.05 | 1351.62 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 3398840.46 | 0.00 | 3398840.46 | 209444.06 | 3608284.52 | 5868225.25 | 6234.14 | 88.77 | 2437.09 | 1351.62 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 15898872.34 | 0.00 | 15898872.34 | 555026.77 | 16453899.11 | 28274176.21 | 6693.81 | 25.64 | 2040.54 | 1351.62 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 3744502.22 | 0.00 | 3744502.22 | 209444.06 | 3953946.28 | 5868225.25 | 5846.09 | 94.02 | 2819.89 | 1351.62 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 17576234.47 | 0.00 | 17576234.47 | 555026.77 | 18131261.24 | 28274176.21 | 6451.47 | 69.24 | 2239.30 | 1351.62 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 2682926.85 | 0.00 | 2682926.85 | 31416.61 | 2714343.46 | 1845537.18 | 4866.20 | 1.89 | 3891.91 | 1351.62 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 3400363.70 | 0.00 | 3400363.70 | 209444.06 | 3609807.77 | 5868225.25 | 6232.59 | 88.08 | 2439.33 | 1351.62 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 15906642.91 | 0.00 | 15906642.91 | 555026.77 | 16461669.68 | 28274176.21 | 6692.56 | 26.12 | 2041.32 | 1351.62 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 3755424.20 | 0.00 | 3755424.20 | 209444.06 | 3964868.27 | 5868225.25 | 5833.55 | 90.32 | 2836.13 | 1351.62 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 17666072.26 | 0.00 | 17666072.26 | 555026.77 | 18221099.03 | 28274176.21 | 6427.96 | 69.56 | 2262.48 | 1351.62 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 2761180.11 | 0.00 | 2761180.11 | 31416.61 | 2792596.72 | 1845537.18 | 4865.42 | 2.06 | 3892.52 | 1351.62 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 3414232.41 | 0.00 | 3414232.41 | 209444.06 | 3623676.47 | 5868225.25 | 6192.59 | 92.83 | 2474.59 | 1351.62 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 10560092.20 | 0.00 | 10560092.20 | 366527.11 | 10926619.31 | 18671625.80 | 6690.50 | 27.19 | 2042.31 | 1351.62 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 6122663.29 | 0.00 | 6122663.29 | 188499.66 | 6311162.94 | 9602550.41 | 5866.37 | 114.50 | 2779.13 | 1351.62 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 7002794.32 | 0.00 | 7002794.32 | 94249.83 | 7097044.15 | 5248246.35 | 4897.60 | 2.14 | 3860.26 | 1351.62 |
| LOBBY_ZN_1_FLR_1 | 3689217.67 | 0.00 | 3689217.67 | 8932844.53 | 12622062.21 | 3013410.78 | 4852.67 | 0.60 | 3906.73 | 1351.62 |
| MECH_ZN_1_FLR_1 | 3380237.26 | 0.00 | 3380237.26 | 0.00 | 3380237.26 | 0.00 | 0.00 | 0.00 | 4627.62 | 1351.62 |
| BATH_ZN_1_FLR_1 | 2184550.07 | 0.00 | 2184550.07 | 104722.03 | 2289272.11 | 0.00 | 0.00 | 0.00 | 4627.62 | 1351.62 |
| OFFICES_ZN_1_FLR_1 | 9710612.01 | 0.00 | 9710612.01 | 439832.54 | 10150444.54 | 6005204.96 | 4911.27 | 4.13 | 3844.60 | 1836.42 |
| GYM_ZN_1_FLR_1 | 11831904.52 | 0.00 | 11831904.52 | 178027.46 | 12009931.98 | 17157717.19 | 5517.31 | 61.76 | 3180.93 | 1351.62 |
| KITCHEN_ZN_1_FLR_1 | 17425826.74 | 0.00 | 17425826.74 | 83777.63 | 17509604.36 | 6482703.52 | 3408.49 | 14.80 | 5336.71 | 3363.02 |
| CAFETERIA_ZN_1_FLR_1 | 25407141.83 | 0.00 | 25407141.83 | 376999.32 | 25784141.15 | 46931384.03 | 5382.74 | 2106.82 | 1270.44 | 1392.05 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 10874660.70 | 0.00 | 10874660.70 | 418888.13 | 11293548.83 | 10866548.77 | 4934.53 | 3.00 | 3822.47 | 1351.62 |
| Total Facility | 0.22E+09 | 0.00 | 0.22E+09 | 15310416.30 | 0.24E+09 | 0.31E+09 | 7175.11 | 2146.36 | 6019.10 | 4886.08 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.2632 | 0.0000 | 0.2632 | 0.0028 | 0.2660 | 0.1861 | 865.14 | 88.52 | 2322.34 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.2308 | 0.0000 | 1.2308 | 0.0074 | 1.2383 | 0.8966 | 1465.19 | 66.11 | 1744.70 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 0.1910 | 0.0000 | 0.1910 | 0.0004 | 0.1914 | 0.0585 | 0.00 | 0.00 | 3276.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.2323 | 0.0000 | 0.2323 | 0.0028 | 0.2351 | 0.1861 | 1286.52 | 88.17 | 1901.32 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.0790 | 0.0000 | 1.0790 | 0.0074 | 1.0865 | 0.8966 | 1746.19 | 24.87 | 1504.94 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.2616 | 0.0000 | 0.2616 | 0.0028 | 0.2645 | 0.1861 | 898.46 | 93.42 | 2284.12 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.2212 | 0.0000 | 1.2212 | 0.0074 | 1.2287 | 0.8966 | 1503.84 | 68.63 | 1703.53 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 0.1901 | 0.0000 | 0.1901 | 0.0004 | 0.1905 | 0.0585 | 0.00 | 0.00 | 3276.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.2324 | 0.0000 | 0.2324 | 0.0028 | 0.2352 | 0.1861 | 1284.99 | 87.49 | 1903.53 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.0795 | 0.0000 | 1.0795 | 0.0074 | 1.0870 | 0.8966 | 1744.94 | 25.55 | 1505.52 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.2625 | 0.0000 | 0.2625 | 0.0028 | 0.2653 | 0.1861 | 885.94 | 89.73 | 2300.33 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.2288 | 0.0000 | 1.2288 | 0.0074 | 1.2363 | 0.8966 | 1480.34 | 68.79 | 1726.88 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 0.1964 | 0.0000 | 0.1964 | 0.0004 | 0.1968 | 0.0585 | 0.00 | 0.00 | 3276.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.2336 | 0.0000 | 0.2336 | 0.0028 | 0.2364 | 0.1861 | 1244.96 | 92.25 | 1938.78 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.7176 | 0.0000 | 0.7176 | 0.0049 | 0.7225 | 0.5921 | 1742.90 | 26.60 | 1506.51 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 0.4278 | 0.0000 | 0.4278 | 0.0025 | 0.4303 | 0.3045 | 918.75 | 113.89 | 2243.36 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 0.5106 | 0.0000 | 0.5106 | 0.0013 | 0.5118 | 0.1664 | 0.00 | 0.00 | 3276.00 |
| LOBBY_ZN_1_FLR_1 | 0.2651 | 0.0000 | 0.2651 | 0.5054 | 0.7706 | 0.0956 | 0.00 | 0.00 | 3276.00 |
| MECH_ZN_1_FLR_1 | 0.2264 | 0.0000 | 0.2264 | 0.0000 | 0.2264 | 0.0000 | 0.00 | 0.00 | 3276.00 |
| BATH_ZN_1_FLR_1 | 0.1464 | 0.0000 | 0.1464 | 0.0014 | 0.1478 | 0.0000 | 0.00 | 0.00 | 3276.00 |
| OFFICES_ZN_1_FLR_1 | 0.7313 | 0.0000 | 0.7313 | 0.0059 | 0.7372 | 0.1904 | 0.00 | 0.00 | 2772.00 |
| GYM_ZN_1_FLR_1 | 0.8378 | 0.0000 | 0.8378 | 0.0024 | 0.8402 | 0.5441 | 569.82 | 61.10 | 2645.07 |
| KITCHEN_ZN_1_FLR_1 | 0.8927 | 0.0000 | 0.8927 | 0.0011 | 0.8938 | 0.2182 | 211.00 | 0.00 | 3065.00 |
| CAFETERIA_ZN_1_FLR_1 | 1.9709 | 0.0000 | 1.9709 | 0.0052 | 1.9761 | 1.4882 | 0.00 | 1673.99 | 1054.01 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.7972 | 0.0000 | 0.7972 | 0.0056 | 0.8028 | 0.3446 | 0.00 | 0.00 | 3276.00 |
| Total Facility | 15.4264 | 0.0000 | 15.4264 | 0.5911 | 16.0175 | 9.7189 | 1775.74 | 2117.20 | 3276.00 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| VAV_POD_1 | 0.20E+09 | 0.00 | 0.20E+09 | 0.25E+09 | 4931.63 | 2.83 | 3825.53 | 1351.62 |
| PSZ-AC_1:6 | 19005107.91 | 0.00 | 19005107.91 | 6482703.52 | 3349.42 | 12.14 | 5398.44 | 3363.02 |
| PSZ-AC_2:7 | 27709697.09 | 0.00 | 27709697.09 | 46931384.03 | 5334.67 | 7.40 | 3417.93 | 1391.97 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| VAV_POD_1 | 13.6788 | 0.0000 | 13.6788 | 8.0125 | 0.00 | 0.00 | 3276.00 |
| PSZ-AC_1:6 | 0.9736 | 0.0000 | 0.9736 | 0.2182 | 211.00 | 0.00 | 3065.00 |
| PSZ-AC_2:7 | 2.1495 | 0.0000 | 2.1495 | 1.4882 | 0.00 | 0.00 | 2728.00 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| VAV_POD_1 | 0.00 | 97.87 | 2523.97 | 709.08 | 0.00 | 0.00 | 1296.70 | 0.00 | 0.00 | 0.00 |
| PSZ-AC_1:6 | 0.00 | 1146.50 | 2972.08 | 2309.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| PSZ-AC_2:7 | 0.00 | 2100.53 | 1417.85 | 601.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| VAV_POD_1 | 0.0000 | 11.3087 | 16.0104 | 0.0000 | 0.0000 | 0.0000 | 10.4934 | 0.0000 | 0.0000 | 0.0000 |
| PSZ-AC_1:6 | 0.0000 | 0.2780 | 1.4967 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| PSZ-AC_2:7 | 0.0000 | 1.6237 | 2.9811 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Surfaces by Class| Total | Outdoors | |
| Wall | 121 | 33 |
| Floor | 25 | 24 |
| Roof | 25 | 25 |
| Internal Mass | 25 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 67 | 67 |
| Door | 25 | 25 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 3 |
| Conditioned Zones | 25 |
| Unconditioned Zones | 0 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1159 |
| Defaulted Fields | 890 |
| Fields with Defaults | 3720 |
| Autosized Fields | 267 |
| Autosizable Fields | 376 |
| Autocalculated Fields | 317 |
| Autocalculatable Fields | 632 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 3798.59 | 37378.94 | 15-JUL-06:50 | 386685.11 | 15-JUN-15:00 |
| Electricity:Building | 2377.40 | 35841.46 | 01-JUL-10:30 | 158543.84 | 02-JAN-11:10 |
| Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| Electricity:SpaceType:GENERAL | 2369.55 | 35741.12 | 30-JUN-23:10 | 156371.25 | 02-JAN-10:10 |
| InteriorLights:Electricity | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 24.39 | 336.28 | 30-JUN-23:10 | 1626.10 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 24.39 | 336.28 | 30-JUN-23:10 | 1626.10 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 24.39 | 336.28 | 30-JUN-23:10 | 1626.10 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 126.22 | 1762.63 | 30-JUN-23:10 | 8449.51 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 65.42 | 841.62 | 01-JAN-00:10 | 4272.19 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 65.42 | 841.62 | 01-JAN-00:10 | 4272.19 | 02-JAN-07:10 |
| Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 75.34 | 1064.38 | 30-JUN-23:10 | 5061.57 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 33.64 | 432.83 | 01-JAN-00:10 | 2197.13 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 33.64 | 432.83 | 01-JAN-00:10 | 2197.13 | 02-JAN-07:10 |
| Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 69.34 | 956.30 | 30-JUN-23:10 | 4624.21 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 41.24 | 530.59 | 01-JAN-00:10 | 2693.36 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 41.24 | 530.59 | 01-JAN-00:10 | 2693.36 | 02-JAN-07:10 |
| Electricity:Zone:LOBBY_ZN_1_FLR_1 | 41.78 | 557.57 | 30-JUN-23:10 | 2758.25 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 32.98 | 424.25 | 01-JAN-00:10 | 2153.53 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 32.98 | 424.25 | 01-JAN-00:10 | 2153.53 | 02-JAN-07:10 |
| Electricity:Zone:MECH_ZN_1_FLR_1 | 88.50 | 1212.59 | 30-JUN-23:10 | 5889.78 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MECH_ZN_1_FLR_1 | 56.07 | 721.39 | 01-JAN-00:10 | 3661.88 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MECH_ZN_1_FLR_1 | 56.07 | 721.39 | 01-JAN-00:10 | 3661.88 | 02-JAN-07:10 |
| Electricity:Zone:BATH_ZN_1_FLR_1 | 35.15 | 474.48 | 30-JUN-23:10 | 2328.47 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:BATH_ZN_1_FLR_1 | 25.37 | 326.34 | 01-JAN-00:10 | 1656.56 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:BATH_ZN_1_FLR_1 | 25.37 | 326.34 | 01-JAN-00:10 | 1656.56 | 02-JAN-07:10 |
| Electricity:Zone:OFFICES_ZN_1_FLR_1 | 133.25 | 1854.16 | 30-JUN-23:10 | 8910.14 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 71.96 | 925.78 | 01-JAN-00:10 | 4699.41 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 71.96 | 925.78 | 01-JAN-00:10 | 4699.41 | 02-JAN-07:10 |
| Electricity:Zone:GYM_ZN_1_FLR_1 | 88.64 | 1192.76 | 30-JUN-23:10 | 5866.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:GYM_ZN_1_FLR_1 | 65.67 | 844.83 | 01-JAN-00:10 | 4288.47 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:GYM_ZN_1_FLR_1 | 65.67 | 844.83 | 01-JAN-00:10 | 4288.47 | 02-JAN-07:10 |
| Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 211.64 | 5400.64 | 01-JAN-11:30 | 13840.49 | 02-JAN-11:10 |
| InteriorLights:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 29.90 | 384.74 | 01-JAN-00:10 | 1953.00 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 29.90 | 384.74 | 01-JAN-00:10 | 1953.00 | 02-JAN-07:10 |
| Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 71.99 | 1340.83 | 01-JAN-00:10 | 4745.87 | 02-JAN-10:10 |
| InteriorLights:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 42.05 | 541.04 | 01-JAN-00:10 | 2746.41 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 42.05 | 541.04 | 01-JAN-00:10 | 2746.41 | 02-JAN-07:10 |
| Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 168.75 | 2346.88 | 30-JUN-23:10 | 11282.50 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 91.74 | 1180.27 | 01-JAN-00:10 | 5991.24 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 91.74 | 1180.27 | 01-JAN-00:10 | 5991.24 | 02-JAN-07:10 |
| InteriorEquipment:Electricity | 1151.36 | 20068.34 | 30-JUN-23:10 | 76813.98 | 02-JAN-10:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 1151.36 | 20068.34 | 30-JUN-23:10 | 76813.98 | 02-JAN-10:10 |
| MiscPlug:InteriorEquipment:Electricity | 947.54 | 14352.99 | 30-JUN-23:10 | 65099.62 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 947.54 | 14352.99 | 30-JUN-23:10 | 65099.62 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 60.80 | 921.00 | 30-JUN-23:10 | 4177.31 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 60.80 | 921.00 | 30-JUN-23:10 | 4177.31 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 41.69 | 631.55 | 30-JUN-23:10 | 2864.44 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 41.69 | 631.55 | 30-JUN-23:10 | 2864.44 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 28.10 | 425.71 | 30-JUN-23:10 | 1930.85 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 28.10 | 425.71 | 30-JUN-23:10 | 1930.85 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 8.80 | 133.33 | 30-JUN-23:10 | 604.72 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 8.80 | 133.33 | 30-JUN-23:10 | 604.72 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MECH_ZN_1_FLR_1 | 32.43 | 491.20 | 30-JUN-23:10 | 2227.90 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MECH_ZN_1_FLR_1 | 32.43 | 491.20 | 30-JUN-23:10 | 2227.90 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:BATH_ZN_1_FLR_1 | 9.78 | 148.14 | 30-JUN-23:10 | 671.91 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:BATH_ZN_1_FLR_1 | 9.78 | 148.14 | 30-JUN-23:10 | 671.91 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 61.29 | 928.37 | 30-JUN-23:10 | 4210.73 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 61.29 | 928.37 | 30-JUN-23:10 | 4210.73 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GYM_ZN_1_FLR_1 | 22.97 | 347.93 | 30-JUN-23:10 | 1578.10 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GYM_ZN_1_FLR_1 | 22.97 | 347.93 | 30-JUN-23:10 | 1578.10 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 173.88 | 4915.56 | 01-JAN-00:10 | 9714.90 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity | 149.71 | 3999.34 | 01-JAN-00:10 | 9998.36 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 119.77 | 3199.56 | 01-JAN-00:10 | 7998.90 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 149.71 | 3999.34 | 01-JAN-00:10 | 9998.36 | 02-JAN-10:10 |
| ReachInFreezer:InteriorEquipment:Electricity | 31.09 | 986.00 | 01-JAN-00:10 | 986.00 | 01-JAN-00:10 |
| ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 31.09 | 986.00 | 01-JAN-00:10 | 986.00 | 01-JAN-00:10 |
| ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 31.09 | 986.00 | 01-JAN-00:10 | 986.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 29.94 | 799.79 | 01-JAN-00:10 | 1999.46 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 29.94 | 799.79 | 01-JAN-00:10 | 1999.46 | 02-JAN-10:10 |
| InteriorEquipment:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 77.02 | 1166.60 | 30-JUN-23:10 | 5291.26 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 77.02 | 1166.60 | 30-JUN-23:10 | 5291.26 | 02-JAN-08:10 |
| Refrigeration:Electricity | 44.67 | 693.61 | 21-APR-22:30 | 2870.74 | 04-OCT-10:20 |
| Refrigeration:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 7.85 | 100.34 | 01-JAN-11:30 | 2172.58 | 02-JAN-11:10 |
| General:Refrigeration:Electricity | 7.85 | 100.34 | 01-JAN-11:30 | 2172.58 | 02-JAN-11:10 |
| General:Refrigeration:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 7.85 | 100.34 | 01-JAN-11:30 | 2172.58 | 02-JAN-11:10 |
| Electricity:Plant | 37.12 | 593.27 | 21-APR-22:30 | 2237.91 | 04-JUL-10:50 |
| LowTempRefrigeration:Refrigeration:Electricity | 15.11 | 0.00 | 01-JAN-11:10 | 1503.03 | 04-JUL-10:50 |
| MedTempRefrigeration:Refrigeration:Electricity | 21.71 | 593.27 | 21-APR-22:30 | 734.88 | 01-JAN-08:50 |
| Electricity:HVAC | 1291.33 | 321.20 | 01-JUL-03:30 | 234919.90 | 15-JUN-15:00 |
| ExteriorEquipment:Electricity | 17.61 | 321.20 | 01-JUL-00:10 | 1336.02 | 02-JAN-10:10 |
| Transformer:ExteriorEquipment:Electricity | 17.61 | 321.20 | 01-JUL-00:10 | 1336.02 | 02-JAN-10:10 |
| ElectricityPurchased:Facility | 3798.59 | 37378.94 | 15-JUL-06:50 | 386685.11 | 15-JUN-15:00 |
| ElectricityPurchased:Plant | 3798.59 | 37378.94 | 15-JUL-06:50 | 386685.11 | 15-JUN-15:00 |
| Cogeneration:ElectricityPurchased | 3798.59 | 37378.94 | 15-JUL-06:50 | 386685.11 | 15-JUN-15:00 |
| General:Cogeneration:ElectricityPurchased | 3798.59 | 37378.94 | 15-JUL-06:50 | 386685.11 | 15-JUN-15:00 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 3798.59 | 37378.94 | 15-JUL-06:50 | 386685.11 | 15-JUN-15:00 |
| ElectricityNet:Plant | 3798.59 | 37378.94 | 15-JUL-06:50 | 386685.11 | 15-JUN-15:00 |
| Cogeneration:ElectricityNet | 3798.59 | 37378.94 | 15-JUL-06:50 | 386685.11 | 15-JUN-15:00 |
| General:Cogeneration:ElectricityNet | 3798.59 | 37378.94 | 15-JUL-06:50 | 386685.11 | 15-JUN-15:00 |
| Fans:Electricity | 489.86 | 0.00 | 01-JAN-00:10 | 63149.56 | 12-MAY-12:30 |
| General:Fans:Electricity | 489.86 | 0.00 | 01-JAN-00:10 | 63149.56 | 12-MAY-12:30 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 783.86 | 0.00 | 01-JAN-00:10 | 178587.35 | 15-JUN-15:00 |
| General:Cooling:Electricity | 783.86 | 0.00 | 01-JAN-00:10 | 178587.35 | 15-JUN-15:00 |
| ExteriorLights:Electricity | 92.74 | 0.00 | 01-JAN-07:20 | 5897.73 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 92.74 | 0.00 | 01-JAN-07:20 | 5897.73 | 01-JAN-00:10 |
| Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Pumps:Electricity | 0.30 | 0.00 | 01-JAN-00:10 | 490.95 | 27-DEC-07:10 |
| General:Pumps:Electricity | 0.30 | 0.00 | 01-JAN-00:10 | 490.95 | 27-DEC-07:10 |
| WIRED_LTG_ELECTRICITY | 14.50 | 0.00 | 01-JAN-00:10 | 946.73 | 02-JAN-07:20 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 610.28 | 4866.91 | 21-MAY-10:50 | 375612.72 | 27-DEC-08:10 |
| NaturalGas:Building | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| NaturalGas:SpaceType:GENERAL | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| InteriorEquipment:NaturalGas | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| InteriorEquipment:NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| InteriorEquipment:NaturalGas:SpaceType:GENERAL | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:NaturalGas | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| NaturalGas:HVAC | 68.21 | 0.00 | 01-JAN-00:10 | 204979.86 | 27-DEC-08:10 |
| Heating:NaturalGas | 109.16 | 0.00 | 01-JAN-00:10 | 328211.54 | 27-DEC-08:10 |
| General:Heating:NaturalGas | 68.21 | 0.00 | 01-JAN-00:10 | 204979.86 | 27-DEC-08:10 |
| NaturalGas:Plant | 181.04 | 58.42 | 21-MAY-10:50 | 215386.83 | 27-DEC-07:10 |
| WaterSystems:NaturalGas | 140.10 | 58.42 | 21-MAY-10:50 | 27385.87 | 30-JAN-13:40 |
| Water Heater:WaterSystems:NaturalGas | 140.10 | 58.42 | 21-MAY-10:50 | 27385.87 | 30-JAN-13:40 |
| Boiler:Heating:NaturalGas | 40.95 | 0.00 | 01-JAN-00:10 | 214659.85 | 27-DEC-07:10 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Water:Plant | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| WaterSystems:Water | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Water Heater:WaterSystems:Water | 268.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| MainsWater:Facility | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| MainsWater:Plant | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| WaterSystems:MainsWater | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Water Heater:WaterSystems:MainsWater | 268.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| WaterUse:WaterSystems:Water | 449.48 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-13:20 |
| WaterUse:WaterSystems:MainsWater | 449.48 | 0.00 | 01-JAN-00:10 | 0.00 | 03-JAN-13:20 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 6205.90 | 3578.83 | 09-APR-22:30 | 958338.37 | 03-OCT-14:00 |
| EnergyTransfer:Building | 3011.08 | 1789.42 | 09-APR-22:30 | 363993.30 | 15-JUN-14:00 |
| EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 296.15 | 1698.04 | 21-APR-22:30 | 28579.08 | 05-JUN-10:50 |
| Refrigeration:EnergyTransfer | 184.85 | 3396.07 | 21-APR-22:30 | 10745.76 | 07-JAN-11:40 |
| Refrigeration:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 92.42 | 1698.04 | 21-APR-22:30 | 5372.88 | 07-JAN-11:40 |
| General:Refrigeration:EnergyTransfer | 92.42 | 1698.04 | 21-APR-22:30 | 5372.88 | 07-JAN-11:40 |
| General:Refrigeration:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 92.42 | 1698.04 | 21-APR-22:30 | 5372.88 | 07-JAN-11:40 |
| EnergyTransfer:Plant | 192.35 | 1698.04 | 21-APR-22:30 | 163472.28 | 27-DEC-07:10 |
| LowTempRefrigeration:Refrigeration:EnergyTransfer | 17.94 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
| MedTempRefrigeration:Refrigeration:EnergyTransfer | 74.48 | 1698.04 | 21-APR-22:30 | 2686.44 | 01-JAN-08:50 |
| EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 52.11 | 0.00 | 01-JAN-00:10 | 7445.80 | 19-SEP-15:00 |
| Heating:EnergyTransfer | 14.76 | 0.00 | 01-JAN-00:10 | 103753.29 | 27-DEC-07:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 2689.67 | 27-DEC-07:10 |
| General:Heating:EnergyTransfer | 14.76 | 0.00 | 01-JAN-00:10 | 103753.29 | 27-DEC-07:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 2689.67 | 27-DEC-07:10 |
| Cooling:EnergyTransfer | 2903.90 | 0.00 | 01-JAN-00:10 | 360999.59 | 15-JUN-14:00 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 52.05 | 0.00 | 01-JAN-00:10 | 7445.80 | 19-SEP-15:00 |
| General:Cooling:EnergyTransfer | 2903.90 | 0.00 | 01-JAN-00:10 | 360999.59 | 15-JUN-14:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 52.05 | 0.00 | 01-JAN-00:10 | 7445.80 | 19-SEP-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 239.54 | 0.00 | 01-JAN-00:10 | 30782.48 | 03-OCT-13:40 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 5524.77 | 27-DEC-07:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 5524.77 | 27-DEC-07:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 239.49 | 0.00 | 01-JAN-00:10 | 30782.48 | 03-OCT-13:40 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 239.49 | 0.00 | 01-JAN-00:10 | 30782.48 | 03-OCT-13:40 |
| EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 39.30 | 0.00 | 01-JAN-00:10 | 6154.07 | 15-JUN-15:00 |
| Heating:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 2488.66 | 27-DEC-08:10 |
| General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 2488.66 | 27-DEC-08:10 |
| Cooling:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 39.25 | 0.00 | 01-JAN-00:10 | 6154.07 | 15-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 39.25 | 0.00 | 01-JAN-00:10 | 6154.07 | 15-JUN-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 45.52 | 0.00 | 01-JAN-00:10 | 6794.03 | 15-JUN-15:00 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.20 | 0.00 | 01-JAN-00:10 | 3123.98 | 03-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.20 | 0.00 | 01-JAN-00:10 | 3123.98 | 03-FEB-07:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 45.31 | 0.00 | 01-JAN-00:10 | 6794.03 | 15-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 45.31 | 0.00 | 01-JAN-00:10 | 6794.03 | 15-JUN-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 207.73 | 0.00 | 01-JAN-00:10 | 26653.29 | 15-JUN-14:40 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 0.19 | 0.00 | 01-JAN-00:10 | 9335.11 | 27-DEC-07:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 0.19 | 0.00 | 01-JAN-00:10 | 9335.11 | 27-DEC-07:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 207.53 | 0.00 | 01-JAN-00:10 | 26653.29 | 15-JUN-14:40 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 207.53 | 0.00 | 01-JAN-00:10 | 26653.29 | 15-JUN-14:40 |
| EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 51.79 | 0.00 | 01-JAN-00:10 | 7419.08 | 19-SEP-15:00 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 2683.98 | 27-DEC-07:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 2683.98 | 27-DEC-07:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 51.73 | 0.00 | 01-JAN-00:10 | 7419.08 | 19-SEP-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 51.73 | 0.00 | 01-JAN-00:10 | 7419.08 | 19-SEP-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 237.43 | 0.00 | 01-JAN-00:10 | 30290.89 | 03-OCT-13:40 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 5393.17 | 27-DEC-07:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 5393.17 | 27-DEC-07:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 237.38 | 0.00 | 01-JAN-00:10 | 30290.89 | 03-OCT-13:40 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 237.38 | 0.00 | 01-JAN-00:10 | 30290.89 | 03-OCT-13:40 |
| EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 39.09 | 0.00 | 01-JAN-00:10 | 6142.39 | 15-JUN-15:00 |
| Heating:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 2495.20 | 27-DEC-07:10 |
| General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 2495.20 | 27-DEC-07:10 |
| Cooling:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 39.04 | 0.00 | 01-JAN-00:10 | 6142.39 | 15-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 39.04 | 0.00 | 01-JAN-00:10 | 6142.39 | 15-JUN-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 45.52 | 0.00 | 01-JAN-00:10 | 6796.05 | 15-JUN-15:00 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.20 | 0.00 | 01-JAN-00:10 | 3132.60 | 03-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.20 | 0.00 | 01-JAN-00:10 | 3132.60 | 03-FEB-07:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 45.32 | 0.00 | 01-JAN-00:10 | 6796.05 | 15-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 45.32 | 0.00 | 01-JAN-00:10 | 6796.05 | 15-JUN-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 207.76 | 0.00 | 01-JAN-00:10 | 26661.07 | 15-JUN-14:40 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 0.20 | 0.00 | 01-JAN-00:10 | 9369.67 | 27-DEC-07:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 0.20 | 0.00 | 01-JAN-00:10 | 9369.67 | 27-DEC-07:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 207.57 | 0.00 | 01-JAN-00:10 | 26661.07 | 15-JUN-14:40 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 207.57 | 0.00 | 01-JAN-00:10 | 26661.07 | 15-JUN-14:40 |
| EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 51.99 | 0.00 | 01-JAN-00:10 | 7428.11 | 19-SEP-15:00 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 2669.48 | 27-DEC-07:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.06 | 0.00 | 01-JAN-00:10 | 2669.48 | 27-DEC-07:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 51.93 | 0.00 | 01-JAN-00:10 | 7428.11 | 19-SEP-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 51.93 | 0.00 | 01-JAN-00:10 | 7428.11 | 19-SEP-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 239.22 | 0.00 | 01-JAN-00:10 | 30453.82 | 03-OCT-13:40 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 5237.14 | 27-DEC-07:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 5237.14 | 27-DEC-07:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 239.17 | 0.00 | 01-JAN-00:10 | 30453.82 | 03-OCT-13:40 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 239.17 | 0.00 | 01-JAN-00:10 | 30453.82 | 03-OCT-13:40 |
| EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 40.42 | 0.00 | 01-JAN-00:10 | 6210.16 | 15-JUN-15:00 |
| Heating:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 2405.45 | 27-DEC-08:10 |
| General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 2405.45 | 27-DEC-08:10 |
| Cooling:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 40.38 | 0.00 | 01-JAN-00:10 | 6210.16 | 15-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 40.38 | 0.00 | 01-JAN-00:10 | 6210.16 | 15-JUN-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 45.88 | 0.00 | 01-JAN-00:10 | 6830.83 | 15-JUN-15:00 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.20 | 0.00 | 01-JAN-00:10 | 3123.78 | 03-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.20 | 0.00 | 01-JAN-00:10 | 3123.78 | 03-FEB-07:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 45.68 | 0.00 | 01-JAN-00:10 | 6830.83 | 15-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 45.68 | 0.00 | 01-JAN-00:10 | 6830.83 | 15-JUN-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 138.91 | 0.00 | 01-JAN-00:10 | 17878.07 | 15-JUN-15:00 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.13 | 0.00 | 01-JAN-00:10 | 6173.84 | 27-DEC-07:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.13 | 0.00 | 01-JAN-00:10 | 6173.84 | 27-DEC-07:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 138.78 | 0.00 | 01-JAN-00:10 | 17878.07 | 15-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 138.78 | 0.00 | 01-JAN-00:10 | 17878.07 | 15-JUN-15:00 |
| EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 86.16 | 0.00 | 01-JAN-00:10 | 9987.60 | 15-JUN-14:50 |
| Heating:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2145.07 | 27-DEC-07:10 |
| General:Heating:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 2145.07 | 27-DEC-07:10 |
| Cooling:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 86.13 | 0.00 | 01-JAN-00:10 | 9987.60 | 15-JUN-14:50 |
| General:Cooling:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 86.13 | 0.00 | 01-JAN-00:10 | 9987.60 | 15-JUN-14:50 |
| EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 104.28 | 0.00 | 01-JAN-00:10 | 17218.73 | 05-JUN-15:00 |
| Heating:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 0.12 | 0.00 | 01-JAN-00:10 | 6513.94 | 27-DEC-07:10 |
| General:Heating:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 0.12 | 0.00 | 01-JAN-00:10 | 6513.94 | 27-DEC-07:10 |
| Cooling:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 104.16 | 0.00 | 01-JAN-00:10 | 17218.73 | 05-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 104.16 | 0.00 | 01-JAN-00:10 | 17218.73 | 05-JUN-15:00 |
| EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 64.36 | 0.00 | 01-JAN-00:10 | 15936.84 | 15-JUN-15:00 |
| Heating:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 11.39 | 0.00 | 01-JAN-00:10 | 12026.89 | 27-DEC-08:00 |
| General:Heating:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 11.39 | 0.00 | 01-JAN-00:10 | 12026.89 | 27-DEC-08:00 |
| Cooling:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 52.97 | 0.00 | 01-JAN-00:10 | 15936.84 | 15-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 52.97 | 0.00 | 01-JAN-00:10 | 15936.84 | 15-JUN-15:00 |
| EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 61.26 | 0.00 | 01-JAN-00:10 | 6938.18 | 15-JUN-14:40 |
| Heating:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 61.26 | 0.00 | 01-JAN-00:10 | 6938.18 | 15-JUN-14:40 |
| General:Cooling:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 61.26 | 0.00 | 01-JAN-00:10 | 6938.18 | 15-JUN-14:40 |
| EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 35.53 | 0.00 | 01-JAN-00:10 | 4804.33 | 15-JUN-15:00 |
| Heating:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 35.53 | 0.00 | 01-JAN-00:10 | 4804.33 | 15-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 35.53 | 0.00 | 01-JAN-00:10 | 4804.33 | 15-JUN-15:00 |
| EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 145.40 | 0.00 | 01-JAN-00:10 | 22178.34 | 05-SEP-14:10 |
| Heating:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 6254.53 | 27-DEC-07:10 |
| General:Heating:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 6254.53 | 27-DEC-07:10 |
| Cooling:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 145.35 | 0.00 | 01-JAN-00:10 | 22178.34 | 05-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 145.35 | 0.00 | 01-JAN-00:10 | 22178.34 | 05-SEP-14:10 |
| EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 171.11 | 0.00 | 01-JAN-00:10 | 21145.83 | 05-JUN-15:20 |
| Heating:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 3914.72 | 27-DEC-06:10 |
| General:Heating:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 3914.72 | 27-DEC-06:10 |
| Cooling:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 171.09 | 0.00 | 01-JAN-00:10 | 21145.83 | 05-JUN-15:20 |
| General:Cooling:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 171.09 | 0.00 | 01-JAN-00:10 | 21145.83 | 05-JUN-15:20 |
| Heating:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 4643.79 | 11-MAY-05:40 |
| General:Heating:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 0.03 | 0.00 | 01-JAN-00:10 | 4643.79 | 11-MAY-05:40 |
| Cooling:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 203.69 | 0.00 | 01-JAN-00:10 | 23499.96 | 05-JUN-10:50 |
| General:Cooling:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 203.69 | 0.00 | 01-JAN-00:10 | 23499.96 | 05-JUN-10:50 |
| EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 204.48 | 0.00 | 01-JAN-00:10 | 32433.03 | 05-JUN-12:00 |
| Heating:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 1.46 | 0.00 | 01-JAN-00:10 | 9432.55 | 03-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 1.46 | 0.00 | 01-JAN-00:10 | 9432.55 | 03-FEB-07:10 |
| Cooling:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 203.02 | 0.00 | 01-JAN-00:10 | 32433.03 | 05-JUN-12:00 |
| General:Cooling:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 203.02 | 0.00 | 01-JAN-00:10 | 32433.03 | 05-JUN-12:00 |
| EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 160.11 | 0.00 | 01-JAN-00:10 | 21855.77 | 05-JUN-13:00 |
| Heating:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 4687.91 | 27-DEC-07:10 |
| General:Heating:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.04 | 0.00 | 01-JAN-00:10 | 4687.91 | 27-DEC-07:10 |
| Cooling:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 160.07 | 0.00 | 01-JAN-00:10 | 21855.77 | 05-JUN-13:00 |
| General:Cooling:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 160.07 | 0.00 | 01-JAN-00:10 | 21855.77 | 05-JUN-13:00 |
| PlantLoopHeatingDemand:Facility | 100.22 | 0.00 | 01-JAN-00:10 | 151900.23 | 27-DEC-07:10 |
| PlantLoopHeatingDemand:Plant | 75.22 | 0.00 | 01-JAN-00:10 | 16489.00 | 30-JAN-13:10 |
| WaterSystems:PlantLoopHeatingDemand | 75.22 | 0.00 | 01-JAN-00:10 | 16489.00 | 30-JAN-13:10 |
| General:WaterSystems:PlantLoopHeatingDemand | 75.22 | 0.00 | 01-JAN-00:10 | 16489.00 | 30-JAN-13:10 |
| EnergyTransfer:HVAC | 3002.48 | 0.00 | 01-JAN-00:10 | 594469.21 | 03-OCT-14:00 |
| HeatingCoils:EnergyTransfer | 79.05 | 0.00 | 01-JAN-00:10 | 242648.21 | 27-DEC-08:10 |
| PlantLoopHeatingDemand:HVAC | 24.99 | 0.00 | 01-JAN-00:10 | 151900.23 | 27-DEC-07:10 |
| HeatingCoils:PlantLoopHeatingDemand | 24.99 | 0.00 | 01-JAN-00:10 | 151900.23 | 27-DEC-07:10 |
| CoolingCoils:EnergyTransfer | 2923.42 | 0.00 | 01-JAN-00:10 | 594469.21 | 03-OCT-14:00 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:EnergyTransfer | 75.22 | 0.00 | 01-JAN-00:10 | 16489.00 | 30-JAN-13:10 |
| WaterUse:WaterSystems:EnergyTransfer | 75.22 | 0.00 | 01-JAN-00:10 | 16489.00 | 30-JAN-13:10 |
| Boilers:EnergyTransfer | 24.70 | 0.00 | 01-JAN-00:10 | 160461.56 | 27-DEC-07:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 0.062 | -52.051 | 0.000 | 0.000 | 11.581 | 20.559 | 19.109 | 16.665 | 0.000 | 0.261 | 0.000 | 0.000 | -8.049 | 0.000 | -1.513 | -6.624 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 0.056 | -239.482 | 0.000 | 0.000 | 55.372 | 99.059 | 92.071 | 47.471 | 0.000 | 0.774 | 0.000 | 0.000 | -22.199 | 0.000 | -4.267 | -28.855 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 0.048 | -39.250 | 0.000 | 0.000 | 4.560 | 14.502 | 9.883 | 2.393 | 0.000 | 0.038 | 9.383 | 0.000 | -1.328 | 0.000 | -0.230 | -0.000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 0.202 | -45.314 | 0.000 | 0.000 | 11.880 | 20.559 | 19.109 | 9.592 | 0.000 | 0.274 | 0.000 | 0.000 | -7.841 | 0.000 | -1.368 | -7.092 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 0.195 | -207.533 | 0.000 | 0.000 | 56.650 | 99.059 | 92.071 | 11.771 | 0.000 | 0.819 | 0.000 | 0.000 | -22.301 | 0.000 | -3.847 | -26.883 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 0.063 | -51.724 | 0.000 | 0.000 | 11.586 | 20.559 | 19.109 | 16.212 | 0.000 | 0.263 | 0.000 | 0.000 | -7.891 | 0.000 | -1.512 | -6.665 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 0.057 | -237.375 | 0.000 | 0.000 | 55.404 | 99.059 | 92.071 | 44.009 | 0.000 | 0.781 | 0.000 | 0.000 | -21.337 | 0.000 | -4.260 | -28.409 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 0.050 | -39.036 | 0.000 | 0.000 | 4.562 | 14.502 | 9.883 | 2.395 | 0.000 | 0.038 | 9.162 | 0.000 | -1.326 | 0.000 | -0.230 | -0.000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 0.204 | -45.320 | 0.000 | 0.000 | 11.881 | 20.559 | 19.109 | 9.620 | 0.000 | 0.274 | 0.000 | 0.000 | -7.846 | 0.000 | -1.368 | -7.113 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 0.197 | -207.563 | 0.000 | 0.000 | 56.657 | 99.059 | 92.071 | 11.904 | 0.000 | 0.819 | 0.000 | 0.000 | -22.314 | 0.000 | -3.845 | -26.985 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 0.060 | -51.930 | 0.000 | 0.000 | 11.580 | 20.559 | 19.109 | 16.234 | 0.000 | 0.262 | 0.000 | 0.000 | -7.923 | 0.000 | -1.517 | -6.434 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 0.052 | -239.169 | 0.000 | 0.000 | 55.360 | 99.059 | 92.071 | 44.113 | 0.000 | 0.775 | 0.000 | 0.000 | -21.480 | 0.000 | -4.283 | -26.497 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 0.038 | -40.385 | 0.000 | 0.000 | 4.547 | 14.502 | 9.883 | 2.388 | 0.000 | 0.038 | 10.563 | 0.000 | -1.341 | 0.000 | -0.233 | -0.000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 0.199 | -45.681 | 0.000 | 0.000 | 11.868 | 20.559 | 19.109 | 9.949 | 0.000 | 0.271 | 0.000 | 0.000 | -7.966 | 0.000 | -1.372 | -6.938 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 0.132 | -138.779 | 0.000 | 0.000 | 37.361 | 65.416 | 60.801 | 9.274 | 0.000 | 0.532 | 0.000 | 0.000 | -15.142 | 0.000 | -2.547 | -17.050 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 0.000 | 0.000 | 0.026 | -86.133 | 0.000 | 0.000 | 31.648 | 33.643 | 41.692 | 4.614 | 0.000 | 0.251 | 0.000 | 0.000 | -8.344 | 0.000 | -1.416 | -15.982 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 0.000 | 0.000 | 0.119 | -104.163 | 0.000 | 0.000 | 12.928 | 41.241 | 28.104 | 5.625 | 0.000 | 0.100 | 20.633 | 0.000 | -3.882 | 0.000 | -0.706 | -0.000 |
| LOBBY_ZN_1_FLR_1 | 0.000 | 0.000 | 11.390 | -52.968 | 0.000 | 0.000 | 8.526 | 32.975 | 8.802 | 17.140 | 0.000 | 12.097 | 5.875 | 0.000 | -7.533 | 0.000 | -36.304 | -0.002 |
| MECH_ZN_1_FLR_1 | 0.000 | 0.000 | 0.000 | -61.263 | 0.000 | 0.000 | 1.503 | 56.071 | 32.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -28.739 |
| BATH_ZN_1_FLR_1 | 0.000 | 0.000 | 0.000 | -35.531 | 0.000 | 0.000 | 4.200 | 25.366 | 9.780 | 6.247 | 0.000 | 0.081 | 0.000 | 0.000 | -4.485 | 0.000 | -0.811 | -4.845 |
| OFFICES_ZN_1_FLR_1 | 0.000 | 0.000 | 0.046 | -145.352 | 0.000 | 0.000 | 10.158 | 71.958 | 61.288 | 33.922 | 0.000 | 0.431 | 0.000 | 0.000 | -17.675 | 0.000 | -3.459 | -11.317 |
| GYM_ZN_1_FLR_1 | 0.000 | 0.000 | 0.025 | -171.090 | 0.000 | 0.000 | 51.665 | 65.666 | 22.969 | 44.818 | 0.000 | 0.202 | 5.608 | 0.000 | -18.436 | 0.000 | -1.426 | -0.000 |
| KITCHEN_ZN_1_FLR_1 | 0.000 | 0.000 | 0.033 | -203.678 | 0.000 | 0.000 | 11.453 | 29.905 | 138.079 | 6.027 | 0.000 | 0.069 | 23.140 | 0.000 | -4.216 | 0.000 | -0.810 | -0.000 |
| CAFETERIA_ZN_1_FLR_1 | 0.000 | 0.000 | 1.465 | -203.021 | 0.000 | 0.000 | 141.166 | 42.053 | 29.938 | 15.272 | 0.000 | 0.322 | 0.000 | 0.000 | -15.925 | 0.000 | -2.986 | -8.285 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.000 | 0.000 | 0.042 | -160.069 | 0.000 | 0.000 | 18.426 | 91.739 | 77.015 | 19.192 | 0.000 | 0.421 | 0.000 | 0.000 | -17.461 | 0.000 | -3.281 | -26.023 |
| Total Facility | 0.000 | 0.000 | 14.762 | -2903.860 | 0.000 | 0.000 | 692.522 | 1218.192 | 1115.552 | 406.847 | 0.000 | 20.191 | 84.364 | 0.000 | -274.244 | 0.000 | -83.588 | -290.741 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 21-OCT-14:42 | 0.00 | 0.00 | 0.00 | -8353.96 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 2428.50 | 0.00 | 0.00 | 5260.45 | 0.00 | -0.00 | 0.00 | -4.74 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 20-FEB-13:56 | 0.00 | 0.00 | 0.00 | -31987.42 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 8347.25 | 0.00 | 0.00 | 20590.86 | 0.00 | -0.00 | 0.00 | -177.67 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 15-JUN-15:00 | 0.00 | 0.00 | 0.00 | -6154.58 | 0.00 | 0.00 | 682.65 | 947.12 | 678.98 | 554.76 | 0.00 | 9.58 | 3281.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 15-JUN-15:00 | 0.00 | 0.00 | 0.00 | -6794.42 | 0.00 | 0.00 | 1760.09 | 1342.69 | 1312.87 | 2168.10 | 0.00 | 63.89 | 146.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 15-JUN-14:35 | 0.00 | 0.00 | 0.00 | -26655.43 | 0.00 | 0.00 | 8480.14 | 6469.32 | 6325.65 | 2539.08 | 0.00 | 158.85 | 2682.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 21-OCT-14:42 | 0.00 | 0.00 | 0.00 | -8138.21 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 2395.37 | 0.00 | 0.00 | 5077.81 | 0.00 | -0.00 | 0.00 | -4.72 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 03-OCT-13:40 | 0.00 | 0.00 | 0.00 | -30290.82 | 0.00 | 0.00 | 8480.73 | 6469.32 | 6325.65 | 7942.75 | 0.00 | 35.44 | 1036.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 15-JUN-15:00 | 0.00 | 0.00 | 0.00 | -6142.89 | 0.00 | 0.00 | 682.65 | 947.12 | 678.98 | 554.78 | 0.00 | 9.58 | 3269.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 15-JUN-15:00 | 0.00 | 0.00 | 0.00 | -6796.44 | 0.00 | 0.00 | 1760.09 | 1342.69 | 1312.87 | 2170.91 | 0.00 | 63.89 | 145.99 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 15-JUN-14:35 | 0.00 | 0.00 | 0.00 | -26663.22 | 0.00 | 0.00 | 8480.14 | 6469.32 | 6325.65 | 2550.49 | 0.00 | 158.85 | 2678.78 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 21-OCT-14:42 | 0.00 | 0.00 | 0.00 | -8215.31 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 2397.42 | 0.00 | 0.00 | 5152.87 | 0.00 | -0.00 | 0.00 | -4.73 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 03-OCT-13:40 | 0.00 | 0.00 | 0.00 | -30453.75 | 0.00 | 0.00 | 8480.72 | 6469.32 | 6325.65 | 7961.41 | 0.00 | 35.44 | 1181.21 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 15-JUN-15:00 | 0.00 | 0.00 | 0.00 | -6210.68 | 0.00 | 0.00 | 682.65 | 947.12 | 678.98 | 554.68 | 0.00 | 9.58 | 3337.67 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 15-JUN-15:00 | 0.00 | 0.00 | 0.00 | -6831.22 | 0.00 | 0.00 | 1760.09 | 1342.69 | 1312.87 | 2204.92 | 0.00 | 63.89 | 146.76 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 15-JUN-15:00 | 0.00 | 0.00 | 0.00 | -17879.35 | 0.00 | 0.00 | 5600.35 | 4272.19 | 4177.31 | 1761.27 | 0.00 | 111.81 | 1956.43 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 15-JUN-15:02 | 0.00 | 0.00 | 0.00 | -9992.84 | 0.00 | 0.00 | 2880.19 | 2197.13 | 2864.44 | 893.81 | 0.00 | 57.87 | 1099.40 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 19-JUN-07:03 | 0.00 | 0.00 | 0.00 | -18217.48 | 0.00 | 0.00 | 285.34 | 2693.36 | 1930.85 | 82.03 | 0.00 | 0.00 | 13225.92 | 0.00 | -0.00 | 0.00 | -0.02 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 15-JUN-15:00 | 0.00 | 0.00 | 0.00 | -15937.56 | 0.00 | 0.00 | 425.21 | 2153.53 | 604.72 | 790.55 | 0.00 | 18458.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6495.26 |
| MECH_ZN_1_FLR_1 | 03-AUG-03:51 | 0.00 | 0.00 | 0.00 | -14792.83 | 0.00 | 0.00 | 0.00 | 721.39 | 491.20 | 0.00 | 0.00 | 0.00 | 13580.23 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 06-AUG-16:01 | 0.00 | 0.00 | 0.00 | -10208.73 | 0.00 | 0.00 | 0.00 | 326.34 | 148.14 | 1810.36 | 0.00 | 23.67 | 7900.22 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 06-AUG-13:21 | 0.00 | 0.00 | 0.00 | -29536.82 | 0.00 | 0.00 | 0.00 | 925.78 | 928.37 | 2384.56 | 0.00 | 87.24 | 25210.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 21-AUG-05:01 | 0.00 | 0.00 | 0.00 | -29609.50 | 0.00 | 0.00 | 0.00 | 844.83 | 347.93 | 0.00 | 0.00 | 0.00 | 29152.72 | 0.00 | -731.30 | 0.00 | -4.69 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 19-DEC-06:01 | 0.00 | 0.00 | 0.00 | -84306.54 | 0.00 | 0.00 | 0.00 | 384.74 | 2721.46 | 0.00 | 0.00 | 0.00 | 81725.39 | 0.00 | -525.05 | 0.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | -96685.86 | 0.00 | 0.00 | 0.00 | 541.04 | 799.79 | 0.00 | 0.00 | 0.00 | 96535.35 | 0.00 | -1084.33 | 0.00 | -105.99 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 18-JUN-12:23 | 0.00 | 0.00 | 0.00 | -32083.75 | 0.00 | 0.00 | 0.00 | 1180.27 | 1633.25 | 1575.01 | 0.00 | 138.65 | 27556.56 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 15-JUN-14:11 | 0.00 | 0.00 | 0.00 | -361489.57 | 0.00 | 0.00 | 83924.95 | 79557.27 | 68620.86 | 45830.04 | 0.00 | 24485.29 | 59071.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 04-DEC-07:01 | 0.00 | 0.00 | 5502.11 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.69 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -244.22 | 0.00 | -42.18 | -6963.64 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 27-DEC-07:01 | 0.00 | 0.00 | 18036.08 | 0.00 | 0.00 | 0.00 | 0.00 | 6469.32 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2752.07 | 0.00 | -103.08 | -23602.78 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 04-DEC-07:01 | 0.00 | 0.00 | 4862.08 | 0.00 | 0.00 | 0.00 | 0.00 | 947.12 | 209.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -122.55 | 0.00 | -6.64 | -5889.59 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 27-DEC-06:01 | 0.00 | 0.00 | 5895.00 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -941.72 | 0.00 | -162.55 | -5460.48 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 04-DEC-07:01 | 0.00 | 0.00 | 18667.75 | 0.00 | 0.00 | 0.00 | 0.00 | 6469.32 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2054.11 | 0.00 | -111.39 | -24924.09 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 04-DEC-07:01 | 0.00 | 0.00 | 5464.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.69 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -744.67 | 0.00 | -42.14 | -6425.24 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 27-DEC-07:01 | 0.00 | 0.00 | 17724.54 | 0.00 | 0.00 | 0.00 | 0.00 | 6469.32 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2683.00 | 0.00 | -103.12 | -23360.26 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 04-DEC-07:01 | 0.00 | 0.00 | 4855.94 | 0.00 | 0.00 | 0.00 | 0.00 | 947.12 | 209.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -122.39 | 0.00 | -6.63 | -5883.62 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 27-DEC-06:01 | 0.00 | 0.00 | 5902.54 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -942.12 | 0.00 | -162.47 | -5467.69 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 04-DEC-07:01 | 0.00 | 0.00 | 18690.37 | 0.00 | 0.00 | 0.00 | 0.00 | 6469.32 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2053.10 | 0.00 | -111.36 | -24947.76 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 04-DEC-07:01 | 0.00 | 0.00 | 5467.61 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.69 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -746.42 | 0.00 | -42.15 | -6426.97 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 27-DEC-07:01 | 0.00 | 0.00 | 17697.22 | 0.00 | 0.00 | 0.00 | 0.00 | 6469.32 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2695.42 | 0.00 | -103.40 | -23320.25 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 04-DEC-07:01 | 0.00 | 0.00 | 4817.26 | 0.00 | 0.00 | 0.00 | 0.00 | 947.12 | 209.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -123.58 | 0.00 | -6.69 | -5843.70 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 27-DEC-06:01 | 0.00 | 0.00 | 5932.37 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -952.79 | 0.00 | -162.69 | -5486.64 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 04-DEC-07:01 | 0.00 | 0.00 | 12625.66 | 0.00 | 0.00 | 0.00 | 0.00 | 4272.19 | 1289.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1356.37 | 0.00 | -73.61 | -16757.27 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 04-DEC-07:01 | 0.00 | 0.00 | 5992.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2197.13 | 884.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -725.82 | 0.00 | -39.05 | -8308.48 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 29-DEC-07:01 | 0.00 | 0.00 | 11229.69 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.36 | 595.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -399.43 | 0.00 | -2.43 | -14117.18 |
| LOBBY_ZN_1_FLR_1 | 27-DEC-07:10 | 0.00 | 0.00 | 12651.18 | 0.00 | 0.00 | 0.00 | 0.00 | 2153.53 | 186.66 | 0.00 | 0.00 | 0.00 | 14862.31 | 0.00 | -943.64 | 0.00 | -28910.04 | 0.00 |
| MECH_ZN_1_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 27-DEC-07:01 | 0.00 | 0.00 | 14515.81 | 0.00 | 0.00 | 0.00 | 0.00 | 4699.41 | 1299.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2205.56 | 0.00 | -81.87 | -18227.51 |
| GYM_ZN_1_FLR_1 | 28-DEC-06:50 | 0.00 | 0.00 | 10932.76 | 0.00 | 0.00 | 0.00 | 0.00 | 844.83 | 487.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2110.88 | 0.00 | 0.00 | -10153.81 |
| KITCHEN_ZN_1_FLR_1 | 11-MAY-05:37 | 0.00 | 0.00 | 13930.19 | 0.00 | 0.00 | 0.00 | 0.00 | 384.74 | 2721.46 | 10.74 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5.55 | -17041.58 |
| CAFETERIA_ZN_1_FLR_1 | 09-JAN-06:01 | 0.00 | 0.00 | 52648.32 | 0.00 | 0.00 | 0.00 | 0.00 | 541.04 | 799.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1489.31 | 0.00 | -377.78 | -52122.05 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 27-DEC-07:01 | 0.00 | 0.00 | 13665.21 | 0.00 | 0.00 | 0.00 | 0.00 | 5991.24 | 1633.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2109.29 | 0.00 | -78.02 | -19102.38 |
| Total Facility | 27-DEC-07:01 | -5692.09 | 5692.09 | 229501.18 | -5692.09 | 0.00 | 0.00 | 0.00 | 79557.27 | 23615.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33600.68 | 0.00 | -69531.52 | -223849.59 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| VAV_POD_1 | 34.7372 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 34.5889 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| PSZ-AC_1:6 | 1.8300 | 0.0000 | 26.9930 | 1.0000 | Calculated from schedules | 0.4528 | 1.8300 | 0.2474 | 1.0000 | Not calculated | 0.4528 | 0.2474 | ||
| PSZ-AC_2:7 | 3.2423 | 0.0000 | 339.0743 | 1.0000 | Calculated from schedules | 1.4882 | 3.2423 | 0.4590 | 1.0000 | Not calculated | 1.4882 | 0.4590 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| VAV_POD_1 | 17.3686 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 14.1579 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| PSZ-AC_1:6 | 1.8300 | 0.0000 | 26.9930 | 1.0000 | Calculated from schedules | 0.4528 | 1.8300 | 1.0000 | 1.0000 | Not calculated | 0.4528 | 0.2474 | ||
| PSZ-AC_2:7 | 3.2423 | 0.0000 | 339.0743 | 1.0000 | Calculated from schedules | 1.4882 | 3.2423 | 1.0000 | 1.0000 | Not calculated | 1.4882 | 0.4590 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.3340 | 0.000305 | 192.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.3340 | 0.000305 | 192.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.3340 | 0.000305 | 192.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 84.7686 | 0.001880 | 315.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 43.5953 | 0.001880 | 162.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 29.3880 | 0.000305 | 546.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 18.4080 | 0.000559 | 171.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 4.0690 | 0.000000 | 252.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.2270 | 0.000000 | 190.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 23.7365 | 0.000432 | 441.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 115.3101 | 0.001524 | 357.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | 0.009440 | 26.9930 | 0.001179 | 168.00 | 0.4528 | 1.0000 | 0.4528 | 1.000 | 0.4528 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | 0.000000 | 339.0743 | 0.004724 | 315.00 | 1.4882 | 1.0000 | 1.4882 | 1.000 | 1.4882 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 42.9540 | 0.000864 | 399.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| VAV_POD_1 | 0.00 | 0.001254 | 6388.0000 | 0.0000 | 0.0000 | 0.0000 | |
| PSZ-AC_1:6 | 0.009440 | 26.99 | 0.001179 | 168.0000 | 0.4528 | 0.4528 | 0.4528 |
| PSZ-AC_2:7 | 0.000000 | 339.07 | 0.004724 | 315.0000 | 1.4882 | 1.4882 | 1.4882 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7552 | 0.7552 | 0.2945 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0700 | 3.0700 | 1.4183 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6597 | 0.6597 | 0.1979 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7324 | 0.7324 | 0.2944 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9125 | 2.9125 | 1.4184 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7491 | 0.7491 | 0.2944 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0307 | 3.0307 | 1.4184 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6578 | 0.6578 | 0.1973 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7328 | 0.7328 | 0.2946 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.9142 | 2.9142 | 1.4192 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7498 | 0.7498 | 0.2947 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0437 | 3.0437 | 1.4184 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6635 | 0.6635 | 0.1990 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7383 | 0.7383 | 0.2946 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9612 | 1.9612 | 0.9374 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0754 | 1.0754 | 0.4818 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4617 | 1.4617 | 0.4385 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7782 | 0.7782 | 0.2335 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9929 | 0.9929 | 0.2979 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6807 | 0.6807 | 0.2042 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9705 | 1.9705 | 0.5911 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2159 | 2.2159 | 0.8620 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8300 | 1.8300 | 1.8300 | No | 0.4528 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.2423 | 3.2423 | 3.2423 | No | 1.4882 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1909 | 2.1909 | 0.6573 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| VAV_POD_1 | 34.7372 | 34.5889 | 34.7372 | 14.1579 | 0.0000 | 1.0000 |
| PSZ-AC_1:6 | 1.8300 | 1.8300 | 1.8300 | 1.8300 | 0.4528 | 1.0000 |
| PSZ-AC_2:7 | 3.2423 | 3.2423 | 3.2423 | 3.2423 | 1.4882 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3776 | 0.3776 | 0.2945 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5350 | 1.5350 | 1.4183 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3299 | 0.3299 | 0.1979 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3662 | 0.3662 | 0.2944 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4562 | 1.4562 | 1.4184 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3746 | 0.3746 | 0.2944 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5154 | 1.5154 | 1.4184 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3289 | 0.3289 | 0.1973 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3664 | 0.3664 | 0.2946 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4571 | 1.4571 | 1.4192 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3749 | 0.3749 | 0.2947 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5218 | 1.5218 | 1.4184 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3317 | 0.3317 | 0.1990 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3691 | 0.3691 | 0.2946 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9806 | 0.9806 | 0.9374 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5377 | 0.5377 | 0.4818 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7309 | 0.7309 | 0.4385 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3891 | 0.3891 | 0.2335 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4964 | 0.4964 | 0.2979 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3403 | 0.3403 | 0.2042 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9852 | 0.9852 | 0.5911 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1080 | 1.1080 | 0.8620 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8300 | 1.8300 | 1.8300 | No | 0.4528 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.2423 | 3.2423 | 3.2423 | No | 1.4882 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0955 | 1.0955 | 0.6573 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| VAV_POD_1 | 17.3686 | 14.1579 | 14.1579 | 14.1579 | 0.0000 | 1.0000 |
| PSZ-AC_1:6 | 1.8300 | 1.8300 | 1.8300 | 1.8300 | 0.4528 | 1.0000 |
| PSZ-AC_2:7 | 3.2423 | 3.2423 | 3.2423 | 3.2423 | 1.4882 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
| Total gross floor area [m2] | 6871.00 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 192.00 | 0.00 | 62.83 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 192.00 | 0.00 | 62.83 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 192.00 | 0.00 | 62.83 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 315.00 | 0.00 | 62.83 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 162.00 | 0.00 | 62.83 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 546.00 | 0.00 | 62.83 |
| LOBBY_ZN_1_FLR_1 | 171.00 | 171.00 | 0.00 | 62.83 |
| MECH_ZN_1_FLR_1 | 252.00 | 252.00 | 0.00 | 62.83 |
| BATH_ZN_1_FLR_1 | 190.00 | 190.00 | 0.00 | 62.83 |
| OFFICES_ZN_1_FLR_1 | 441.00 | 441.00 | 0.00 | 53.16 |
| GYM_ZN_1_FLR_1 | 357.00 | 357.00 | 0.00 | 62.83 |
| KITCHEN_ZN_1_FLR_1 | 168.00 | 168.00 | 0.00 | 62.83 |
| CAFETERIA_ZN_1_FLR_1 | 315.00 | 315.00 | 0.00 | 52.32 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 399.00 | 0.00 | 62.83 |
| Totals | 6871.00 | 6871.00 | 0.00 |
| Data | |
| Number of hours heating loads not met | 148.67 |
| Number of hours cooling loads not met | 201.50 |
| Number of hours not met | 350.17 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 68.21 | 204979.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heating -- Boiler | 0.00 | 0.00 | 40.95 | 214659.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 783.86 | 178587.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 1218.19 | 79557.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 92.74 | 5897.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 947.54 | 65099.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- Cooking | 149.71 | 9998.36 | 361.03 | 48084.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ReachInFreezer | 31.09 | 986.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ReachInRefrigerator | 23.02 | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Transformer | 17.61 | 1336.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 489.86 | 63149.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- General | 0.30 | 490.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 0.00 | 0.00 | 140.10 | 27385.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- General | 7.85 | 2172.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- LowTempRefrigeration | 15.11 | 1503.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- MedTempRefrigeration | 21.71 | 734.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 1196.03 | 3798.59 |
| Natural Gas | 361.03 | 610.28 |
| Additional | 0.00 | 0.00 |
| Total | 1557.05 | 4408.87 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 177.29 |
| Space Heating | 0.00 |
| Space Cooling | 114.08 |
| Fans (All) | 71.29 |
| Service Water Heating | 0.00 |
| Receptacle Equipment | 167.57 |
| Miscellaneous (All) | 552.84 |
| Subtotal | 552.84 |
| Natural Gas [MJ/m2] | |
| Space Heating | 15.89 |
| Service Water Heating | 20.39 |
| Miscellaneous (All) | 88.82 |
| Subtotal | 88.82 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 27.63 |
| Space Heating | 2.48 |
| Space Cooling | 17.78 |
| Fans (All) | 11.11 |
| Service Water Heating | 3.18 |
| Receptacle Equipment | 34.30 |
| Miscellaneous | 3.52 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| LTG_SCH_GYM | 3903. | 8760. |
| LTG_SCH_CLASSROOM | 3903. | 8760. |
| LTG_SCH_LIBRARY | 3903. | 8760. |
| LTG_SCH_BATH | 3903. | 8760. |
| LTG_SCH_KITCHEN | 3903. | 8760. |
| LTG_SCH_OFFICE | 3903. | 8760. |
| LTG_SCH_LOBBY | 3903. | 8760. |
| LTG_SCH_MECHANICAL | 3903. | 8760. |
| LTG_SCH_COMPUTER_ROOM | 3903. | 8760. |
| LTG_SCH_CAFETERIA | 3903. | 8760. |
| LTG_SCH_CORRIDOR | 3903. | 8760. |
| BLDG_EQUIP_SCH | 3617. | 8760. |
| WALKIN_OCC_LGHT_SCH_2 | 2473. | 8760. |
| KITCHEN_ELEC_EQUIP_SCH | 1045. | 8760. |
| KITCHEN_GAS_EQUIP_SCH | 425. | 8760. |
| BLDG_OCC_SCH | 1755. | 3380. |
| BLDG_OCC_SCH_EXTEND | 2948. | 3380. |
| BLDG_OCC_SCH_OFFICES | 2197. | 3380. |
| BLDG_OCC_SCH_OFFICES_W_SB | 1743. | 2860. |
| OFFICES BINARY OCCUPANCY | 3380. | 3380. |
| BLDG_OCC_SCH_GYM | 1828. | 3380. |
| BLDG_OCC_SCH_CAFETERIA | 1687. | 2815. |
| INFIL_SCH | 6205. | 8760. |
| INFIL_SCH_PNNL | 6030. | 8760. |
| INFIL_DOOR_OPENING_SCH | 827. | 2860. |
| BLDG_SWH_SCH | 1227. | 3120. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| EXTERIOR_LGT_189_1 | 5940. | 8760. |
| WORK_EFF_SCH | 0. | 0. |
| KITCHEN_EXHAUST_SCH | 2860. | 2860. |
| MINOA_SCHED | 8760. | 8760. |
| BATH_ZN_1_FLR_1 SHW_DEFAULT LATENT FRACT SCHED | 438. | 8760. |
| BATH_ZN_1_FLR_1 SHW_DEFAULT SENSIBLE FRACT SCHED | 1752. | 8760. |
| KITCHEN_ZN_1_FLR_1 SHW_DEFAULT LATENT FRACT SCHED | 438. | 8760. |
| KITCHEN_ZN_1_FLR_1 SHW_DEFAULT SENSIBLE FRACT SCHED | 1752. | 8760. |
| KITCHEN_ZN_1_FLR_1_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
| EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 3380. | 3380. |
| EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6570. | 8760. |
| KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 2594. | 2860. |
| OFFICES_ZN_1_FLR_1_MDP_SCH | 2472. | 8240. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_SCH_YES_OPTIMUM | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
| CLGSETP_SCH_YES_OPTIMUM | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
| HTGSETP_SCH_SETBACK | MECH_ZN_1_FLR_1 DUAL SP CONTROL | January | 15.60 | 365 | 15.60 | 365 |
| CLGSETP_SCH_SETUP | MECH_ZN_1_FLR_1 DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
| HTGSETP_SCH_YES_OPTIMUM_W_SB | OFFICES_ZN_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
| CLGSETP_SCH_YES_OPTIMUM_W_SB | OFFICES_ZN_1_FLR_1 DUAL SP CONTROL | July | 24.56 | 63 | 26.70 | 365 |
| HTGSETP_SCH_NO_OPTIMUM | GYM_ZN_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
| CLGSETP_SCH_NO_OPTIMUM | GYM_ZN_1_FLR_1 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 8676.33 | 83.67 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 8110.17 | 649.83 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 8646.33 | 113.67 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 8711.00 | 49.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 6978.67 | 1780.33 | 1.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 8282.17 | 477.83 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 8727.83 | 32.17 | 0.00 | 0.00 | 0.00 |
| Min | 6978.67 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 1780.33 | 1.00 | 0.00 | 0.00 |
| Average | 8632.02 | 127.94 | 0.04 | 0.00 | 0.00 |
| Sum | 215800.50 | 3198.50 | 1.00 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 141584.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 122876.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 47696.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 28601.67 | 510.33 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 4297.00 | 215.00 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 14997.50 | 310.50 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 38444.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 202800.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 44688.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 552560.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 70792.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 4297.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 552560.00 | 510.33 | 0.00 | 0.00 | 0.00 |
| Average | 106040.65 | 41.43 | 0.00 | 0.00 | 0.00 |
| Sum | 2651016.17 | 1035.83 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 8721.17 | 38.83 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 8742.50 | 17.50 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 8730.67 | 29.33 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 8748.67 | 11.33 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 8723.33 | 36.67 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 8730.67 | 29.33 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 8721.67 | 38.33 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 8743.00 | 17.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 8729.17 | 30.83 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 8745.17 | 14.83 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 8673.83 | 86.17 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 8738.83 | 21.17 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 8606.33 | 153.67 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 7838.67 | 921.33 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 8145.33 | 614.67 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 8574.50 | 185.50 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 8613.67 | 146.33 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 6995.17 | 1762.00 | 2.83 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 8084.50 | 675.50 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 8562.50 | 197.50 | 0.00 | 0.00 | 0.00 |
| Min | 6995.17 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 1762.00 | 2.83 | 0.00 | 0.00 |
| Average | 8557.75 | 202.14 | 0.11 | 0.00 | 0.00 |
| Sum | 213943.67 | 5053.50 | 2.83 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 141584.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 122876.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 47696.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 28666.00 | 446.00 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 4239.50 | 272.50 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 14088.00 | 1220.00 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 38444.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 202800.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 44621.83 | 66.17 | 0.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 551686.33 | 873.67 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 70792.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 4239.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 551686.33 | 1220.00 | 0.00 | 0.00 | 0.00 |
| Average | 105966.95 | 115.13 | 0.00 | 0.00 | 0.00 |
| Sum | 2649173.67 | 2878.33 | 0.00 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:28:01
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME SCHOOLPRIMARY
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 8.136 |
| February | 10.272 |
| March | 12.546 |
| April | 19.230 |
| May | 23.842 |
| June | 27.856 |
| July | 27.543 |
| August | 26.276 |
| September | 23.380 |
| October | 18.301 |
| November | 11.185 |
| December | 6.787 |
| Annual Sum or Average | 17.982 |
| Minimum of Months | 6.787 |
| Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.255939E+10 | 5002.21 | 12-JAN-15:30 | 18.90 | 10.10 | 0.788877E+09 | 1277.23 | 23-JAN-15:20 | 10.60 | 6.35 |
| February | 0.241888E+10 | 6418.65 | 19-FEB-15:57 | 22.80 | 8.58 | 0.720005E+09 | 1278.80 | 02-FEB-13:30 | 22.80 | 8.58 |
| March | 0.325427E+10 | 5360.36 | 16-MAR-15:00 | 22.80 | 8.72 | 0.884674E+09 | 1277.23 | 01-MAR-15:20 | 22.80 | 8.72 |
| April | 0.428534E+10 | 6274.44 | 28-APR-15:00 | 28.90 | 14.03 | 0.794143E+09 | 1277.23 | 17-APR-14:20 | 28.90 | 14.03 |
| May | 0.581436E+10 | 6391.28 | 19-MAY-15:00 | 34.40 | 16.86 | 0.883594E+09 | 1277.23 | 30-MAY-14:20 | 34.40 | 17.58 |
| June | 0.651946E+10 | 6920.14 | 15-JUN-15:00 | 38.30 | 15.91 | 0.546176E+09 | 1277.23 | 06-JUN-14:20 | 38.30 | 15.91 |
| July | 0.491671E+10 | 4591.59 | 03-JUL-14:30 | 37.50 | 18.90 | 0.184042E+09 | 201.70 | 06-JUL-17:10 | 34.82 | 19.46 |
| August | 0.500731E+10 | 5851.73 | 06-AUG-16:01 | 36.10 | 18.33 | 0.210944E+09 | 201.69 | 08-AUG-16:49 | 27.83 | 19.62 |
| September | 0.605251E+10 | 7445.80 | 19-SEP-15:00 | 33.30 | 16.48 | 0.496757E+09 | 1277.30 | 20-SEP-07:00 | 23.90 | 16.99 |
| October | 0.529726E+10 | 8353.88 | 21-OCT-14:42 | 26.02 | 12.50 | 0.844492E+09 | 1277.24 | 02-OCT-07:30 | 26.02 | 12.50 |
| November | 0.360384E+10 | 6432.69 | 09-NOV-15:00 | 23.30 | 12.64 | 0.821318E+09 | 1278.54 | 16-NOV-10:09 | 8.07 | 4.30 |
| December | 0.232226E+10 | 4220.56 | 07-DEC-15:30 | 16.10 | 6.93 | 0.747385E+09 | 1278.37 | 04-DEC-13:09 | 16.10 | 6.93 |
| Annual Sum or Average | 0.520516E+11 | 0.792241E+10 | ||||||||
| Minimum of Months | 0.232226E+10 | 4220.56 | 16.10 | 6.93 | 0.184042E+09 | 201.69 | 8.07 | 4.30 | ||
| Maximum of Months | 0.651946E+10 | 8353.88 | 38.30 | 18.90 | 0.884674E+09 | 1278.80 | 38.30 | 19.62 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.136117E+11 | 22828.44 | 12-JAN-14:50 | 18.80 | 9.97 | 0.391727E+10 | 6153.94 | 23-JAN-15:20 | 10.60 | 6.35 |
| February | 0.128432E+11 | 31988.36 | 20-FEB-13:56 | 22.20 | 8.45 | 0.356739E+10 | 6162.68 | 02-FEB-13:30 | 22.20 | 8.45 |
| March | 0.166223E+11 | 24292.29 | 16-MAR-14:10 | 22.80 | 9.24 | 0.435512E+10 | 6153.93 | 01-MAR-15:20 | 22.80 | 9.24 |
| April | 0.201845E+11 | 26382.16 | 28-APR-14:03 | 28.90 | 14.04 | 0.384993E+10 | 6153.93 | 17-APR-14:20 | 28.90 | 14.04 |
| May | 0.258488E+11 | 26289.83 | 19-MAY-14:02 | 34.90 | 17.16 | 0.425913E+10 | 6153.93 | 30-MAY-14:20 | 34.40 | 17.58 |
| June | 0.278585E+11 | 27437.53 | 15-JUN-14:35 | 38.13 | 15.82 | 0.262873E+10 | 6153.92 | 06-JUN-14:20 | 38.13 | 15.82 |
| July | 0.210094E+11 | 18412.19 | 15-JUL-05:51 | 22.20 | 19.51 | 0.847369E+09 | 971.67 | 21-JUL-14:09 | 29.08 | 21.35 |
| August | 0.211011E+11 | 18798.45 | 06-AUG-14:41 | 35.92 | 18.43 | 0.987557E+09 | 971.71 | 30-AUG-11:50 | 28.43 | 18.17 |
| September | 0.260257E+11 | 30202.50 | 19-SEP-14:02 | 33.80 | 16.79 | 0.239248E+10 | 6154.25 | 20-SEP-07:00 | 23.90 | 16.99 |
| October | 0.242145E+11 | 30782.48 | 03-OCT-13:40 | 32.07 | 19.44 | 0.407421E+10 | 6177.51 | 23-OCT-12:20 | 23.13 | 13.57 |
| November | 0.177956E+11 | 28361.88 | 10-NOV-13:20 | 16.83 | 10.70 | 0.401074E+10 | 6162.29 | 16-NOV-10:09 | 8.07 | 4.30 |
| December | 0.123697E+11 | 19786.94 | 07-DEC-14:30 | 15.85 | 6.83 | 0.370941E+10 | 6160.80 | 04-DEC-13:09 | 15.85 | 6.83 |
| Annual Sum or Average | 0.239485E+12 | 0.385993E+11 | ||||||||
| Minimum of Months | 0.123697E+11 | 18412.19 | 15.85 | 6.83 | 0.847369E+09 | 971.67 | 8.07 | 4.30 | ||
| Maximum of Months | 0.278585E+11 | 31988.36 | 38.13 | 19.51 | 0.435512E+10 | 6177.51 | 38.13 | 21.35 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.145140E+10 | 2369.54 | 12-JAN-15:01 | 18.90 | 10.04 | 0.281366E+09 | 495.43 | 12-JAN-15:20 | 18.90 | 10.07 |
| February | 0.145395E+10 | 2663.52 | 22-FEB-14:30 | 21.95 | 7.96 | 0.266217E+09 | 495.44 | 24-FEB-15:20 | 12.80 | 3.69 |
| March | 0.212840E+10 | 3702.62 | 16-MAR-15:00 | 22.80 | 8.72 | 0.338986E+09 | 495.44 | 21-MAR-14:20 | 24.07 | 9.24 |
| April | 0.339974E+10 | 5281.78 | 28-APR-15:00 | 28.90 | 14.03 | 0.309739E+09 | 495.45 | 28-APR-08:09 | 28.90 | 14.03 |
| May | 0.496001E+10 | 5557.79 | 19-MAY-15:00 | 34.40 | 16.86 | 0.343931E+09 | 495.46 | 19-MAY-08:09 | 34.40 | 16.86 |
| June | 0.580801E+10 | 6154.07 | 15-JUN-15:00 | 38.30 | 15.91 | 0.212556E+09 | 497.75 | 15-JUN-07:10 | 38.30 | 15.91 |
| July | 0.401944E+10 | 4399.97 | 03-JUL-14:40 | 37.40 | 18.90 | 72778610.89 | 78.24 | 06-JUL-17:10 | 34.82 | 19.46 |
| August | 0.394598E+10 | 4529.30 | 07-AUG-14:50 | 35.00 | 18.73 | 83408004.78 | 78.23 | 08-AUG-16:49 | 27.83 | 19.62 |
| September | 0.476584E+10 | 5837.64 | 19-SEP-15:00 | 33.30 | 16.48 | 0.193091E+09 | 495.48 | 20-SEP-07:00 | 23.90 | 16.99 |
| October | 0.388597E+10 | 5572.78 | 03-OCT-14:00 | 32.80 | 19.64 | 0.328021E+09 | 503.82 | 02-OCT-07:10 | 32.80 | 19.64 |
| November | 0.213741E+10 | 4061.46 | 10-NOV-14:30 | 15.85 | 10.28 | 0.311560E+09 | 495.44 | 10-NOV-08:00 | 15.85 | 10.28 |
| December | 0.129451E+10 | 2296.81 | 01-DEC-15:01 | 13.12 | 5.81 | 0.263431E+09 | 482.79 | 01-DEC-14:00 | 13.12 | 5.81 |
| Annual Sum or Average | 0.392507E+11 | 0.300509E+10 | ||||||||
| Minimum of Months | 0.129451E+10 | 2296.81 | 13.12 | 5.81 | 72778610.89 | 78.23 | 12.80 | 3.69 | ||
| Maximum of Months | 0.580801E+10 | 6154.07 | 38.30 | 19.64 | 0.343931E+09 | 503.82 | 38.30 | 19.64 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.179911E+10 | 3515.18 | 12-JAN-15:01 | 18.90 | 10.04 | 0.709490E+09 | 1277.22 | 12-JAN-15:20 | 18.90 | 10.07 |
| February | 0.179528E+10 | 3516.36 | 23-FEB-15:02 | 20.73 | 7.13 | 0.663573E+09 | 1277.21 | 07-FEB-15:20 | 20.73 | 7.13 |
| March | 0.262101E+10 | 4028.37 | 16-MAR-15:00 | 22.80 | 8.72 | 0.847943E+09 | 1277.22 | 17-MAR-14:20 | 13.30 | 4.16 |
| April | 0.382326E+10 | 5516.04 | 28-APR-15:00 | 28.90 | 14.03 | 0.788920E+09 | 1277.23 | 17-APR-14:20 | 28.90 | 14.03 |
| May | 0.563489E+10 | 6112.75 | 19-MAY-15:00 | 34.40 | 16.86 | 0.883533E+09 | 1277.23 | 30-MAY-14:20 | 34.40 | 17.58 |
| June | 0.650927E+10 | 6794.03 | 15-JUN-15:00 | 38.30 | 15.91 | 0.546581E+09 | 1277.23 | 15-JUN-07:49 | 38.30 | 15.91 |
| July | 0.482840E+10 | 4346.54 | 03-JUL-14:30 | 37.50 | 18.90 | 0.183917E+09 | 201.70 | 06-JUL-17:10 | 34.82 | 19.46 |
| August | 0.463074E+10 | 4606.08 | 07-AUG-16:00 | 37.20 | 17.89 | 0.208481E+09 | 201.69 | 08-AUG-16:49 | 27.83 | 19.62 |
| September | 0.526011E+10 | 6358.67 | 20-SEP-15:00 | 33.30 | 17.34 | 0.495544E+09 | 1277.26 | 20-SEP-07:00 | 33.30 | 17.34 |
| October | 0.420421E+10 | 6091.12 | 05-OCT-15:00 | 30.60 | 17.36 | 0.838049E+09 | 1277.24 | 02-OCT-07:40 | 30.60 | 17.36 |
| November | 0.258168E+10 | 4485.69 | 09-NOV-15:40 | 23.30 | 12.89 | 0.785913E+09 | 1277.23 | 10-NOV-15:20 | 15.40 | 10.12 |
| December | 0.162648E+10 | 3439.33 | 01-DEC-15:01 | 13.12 | 5.81 | 0.671681E+09 | 1262.05 | 15-DEC-15:00 | 15.60 | 6.14 |
| Annual Sum or Average | 0.453144E+11 | 0.762362E+10 | ||||||||
| Minimum of Months | 0.162648E+10 | 3439.33 | 13.12 | 5.81 | 0.183917E+09 | 201.69 | 13.30 | 4.16 | ||
| Maximum of Months | 0.650927E+10 | 6794.03 | 38.30 | 18.90 | 0.883533E+09 | 1277.26 | 38.30 | 19.62 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.975429E+10 | 16874.00 | 12-JAN-15:01 | 18.90 | 10.04 | 0.357565E+10 | 6152.17 | 12-JAN-15:50 | 18.90 | 10.15 |
| February | 0.964525E+10 | 16933.75 | 23-FEB-15:02 | 20.73 | 7.13 | 0.334828E+10 | 6153.91 | 24-FEB-15:20 | 12.80 | 3.69 |
| March | 0.134697E+11 | 17761.13 | 16-MAR-14:30 | 22.80 | 9.03 | 0.422801E+10 | 6153.91 | 17-MAR-14:20 | 13.30 | 4.16 |
| April | 0.180188E+11 | 22548.74 | 28-APR-14:50 | 28.90 | 14.03 | 0.382999E+10 | 6153.92 | 17-APR-14:20 | 28.90 | 14.03 |
| May | 0.249814E+11 | 24670.23 | 19-MAY-14:02 | 34.90 | 17.16 | 0.425787E+10 | 6153.93 | 30-MAY-14:20 | 34.40 | 17.58 |
| June | 0.277101E+11 | 26655.33 | 15-JUN-14:35 | 38.13 | 15.82 | 0.263056E+10 | 6153.92 | 06-JUN-14:20 | 38.13 | 15.82 |
| July | 0.207333E+11 | 18358.21 | 15-JUL-05:51 | 22.20 | 19.51 | 0.836985E+09 | 949.99 | 26-JUL-17:40 | 34.80 | 19.83 |
| August | 0.199502E+11 | 18221.50 | 03-AUG-03:51 | 22.80 | 19.65 | 0.946326E+09 | 939.97 | 07-AUG-17:49 | 34.78 | 18.54 |
| September | 0.224423E+11 | 24720.28 | 20-SEP-14:02 | 33.30 | 18.03 | 0.237790E+10 | 6153.91 | 20-SEP-07:00 | 33.30 | 18.03 |
| October | 0.191151E+11 | 23769.64 | 03-OCT-14:02 | 32.62 | 19.55 | 0.404382E+10 | 6153.97 | 02-OCT-07:40 | 32.62 | 19.55 |
| November | 0.127658E+11 | 18286.29 | 10-NOV-12:40 | 18.50 | 11.34 | 0.387375E+10 | 6153.94 | 10-NOV-15:20 | 15.40 | 10.12 |
| December | 0.894841E+10 | 16622.49 | 01-DEC-15:01 | 13.12 | 5.81 | 0.337136E+10 | 6083.69 | 01-DEC-14:20 | 13.12 | 5.81 |
| Annual Sum or Average | 0.207535E+12 | 0.373205E+11 | ||||||||
| Minimum of Months | 0.894841E+10 | 16622.49 | 13.12 | 5.81 | 0.836985E+09 | 939.97 | 12.80 | 3.69 | ||
| Maximum of Months | 0.277101E+11 | 26655.33 | 38.13 | 19.65 | 0.425787E+10 | 6153.97 | 38.13 | 19.83 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.254203E+10 | 4967.00 | 12-JAN-15:15 | 18.90 | 10.07 | 0.787858E+09 | 1277.23 | 23-JAN-15:20 | 10.60 | 6.35 |
| February | 0.240515E+10 | 5401.29 | 19-FEB-15:57 | 22.80 | 8.58 | 0.719505E+09 | 1278.79 | 02-FEB-13:30 | 22.80 | 8.58 |
| March | 0.324039E+10 | 5333.86 | 16-MAR-15:00 | 22.80 | 8.72 | 0.884499E+09 | 1277.23 | 01-MAR-15:20 | 22.80 | 8.72 |
| April | 0.426296E+10 | 6237.67 | 28-APR-15:00 | 28.90 | 14.03 | 0.794076E+09 | 1277.23 | 17-APR-14:20 | 28.90 | 14.03 |
| May | 0.578190E+10 | 6353.40 | 19-MAY-15:00 | 34.40 | 16.86 | 0.883563E+09 | 1277.23 | 30-MAY-14:20 | 34.40 | 17.58 |
| June | 0.648438E+10 | 6886.24 | 15-JUN-15:00 | 38.30 | 15.91 | 0.546136E+09 | 1277.23 | 06-JUN-14:20 | 38.30 | 15.91 |
| July | 0.487146E+10 | 4502.10 | 03-JUL-14:30 | 37.50 | 18.90 | 0.183764E+09 | 201.70 | 06-JUL-17:10 | 34.82 | 19.46 |
| August | 0.496302E+10 | 5338.47 | 06-AUG-16:01 | 36.10 | 18.33 | 0.210619E+09 | 201.69 | 08-AUG-16:49 | 27.83 | 19.62 |
| September | 0.602065E+10 | 7419.08 | 19-SEP-15:00 | 33.30 | 16.48 | 0.496752E+09 | 1277.30 | 20-SEP-07:00 | 23.90 | 16.99 |
| October | 0.527172E+10 | 8138.14 | 21-OCT-14:42 | 26.02 | 12.50 | 0.844493E+09 | 1277.24 | 02-OCT-07:30 | 26.02 | 12.50 |
| November | 0.358099E+10 | 6404.71 | 09-NOV-15:00 | 23.30 | 12.64 | 0.820564E+09 | 1278.48 | 16-NOV-10:09 | 8.07 | 4.30 |
| December | 0.230047E+10 | 4173.63 | 07-DEC-15:30 | 16.10 | 6.93 | 0.745748E+09 | 1278.12 | 04-DEC-13:09 | 16.10 | 6.93 |
| Annual Sum or Average | 0.517251E+11 | 0.791758E+10 | ||||||||
| Minimum of Months | 0.230047E+10 | 4173.63 | 16.10 | 6.93 | 0.183764E+09 | 201.69 | 8.07 | 4.30 | ||
| Maximum of Months | 0.648438E+10 | 8138.14 | 38.30 | 18.90 | 0.884499E+09 | 1278.79 | 38.30 | 19.62 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.134303E+11 | 22503.83 | 12-JAN-14:50 | 18.80 | 9.97 | 0.391009E+10 | 6153.94 | 23-JAN-15:20 | 10.60 | 6.35 |
| February | 0.127339E+11 | 23586.93 | 22-FEB-13:40 | 21.33 | 7.78 | 0.356591E+10 | 6162.63 | 02-FEB-13:30 | 21.33 | 7.78 |
| March | 0.165814E+11 | 24152.86 | 16-MAR-14:10 | 22.80 | 9.24 | 0.435794E+10 | 6153.93 | 01-MAR-15:20 | 22.80 | 9.24 |
| April | 0.200997E+11 | 26216.18 | 28-APR-14:03 | 28.90 | 14.04 | 0.385114E+10 | 6153.93 | 17-APR-14:20 | 28.90 | 14.04 |
| May | 0.256917E+11 | 26058.20 | 19-MAY-14:02 | 34.90 | 17.16 | 0.425912E+10 | 6153.93 | 30-MAY-14:20 | 34.40 | 17.58 |
| June | 0.276447E+11 | 27145.34 | 15-JUN-14:25 | 38.05 | 15.77 | 0.262805E+10 | 6153.92 | 06-JUN-14:20 | 38.05 | 15.77 |
| July | 0.208374E+11 | 18369.34 | 15-JUL-05:51 | 22.20 | 19.51 | 0.841204E+09 | 965.18 | 21-JUL-14:09 | 29.08 | 21.35 |
| August | 0.209058E+11 | 18639.17 | 06-AUG-14:41 | 35.92 | 18.43 | 0.981141E+09 | 971.71 | 30-AUG-12:09 | 28.98 | 18.42 |
| September | 0.257581E+11 | 29917.19 | 19-SEP-14:02 | 33.80 | 16.79 | 0.239225E+10 | 6154.25 | 20-SEP-07:00 | 23.90 | 16.99 |
| October | 0.239565E+11 | 30290.89 | 03-OCT-13:40 | 32.07 | 19.44 | 0.407408E+10 | 6175.39 | 23-OCT-12:20 | 23.13 | 13.57 |
| November | 0.175653E+11 | 27985.65 | 10-NOV-13:20 | 16.83 | 10.70 | 0.400650E+10 | 6162.18 | 16-NOV-10:09 | 8.07 | 4.30 |
| December | 0.121729E+11 | 19349.24 | 01-DEC-13:50 | 14.50 | 6.56 | 0.369935E+10 | 6160.69 | 04-DEC-13:09 | 10.97 | 6.76 |
| Annual Sum or Average | 0.237378E+12 | 0.385668E+11 | ||||||||
| Minimum of Months | 0.121729E+11 | 18369.34 | 14.50 | 6.56 | 0.841204E+09 | 965.18 | 8.07 | 4.30 | ||
| Maximum of Months | 0.276447E+11 | 30290.89 | 38.05 | 19.51 | 0.435794E+10 | 6175.39 | 38.05 | 21.35 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.144103E+10 | 2360.22 | 12-JAN-15:01 | 18.90 | 10.04 | 0.280735E+09 | 495.42 | 12-JAN-15:00 | 18.90 | 10.18 |
| February | 0.144668E+10 | 2618.71 | 22-FEB-14:30 | 21.95 | 7.96 | 0.266078E+09 | 495.44 | 24-FEB-15:20 | 12.80 | 3.69 |
| March | 0.212672E+10 | 3702.38 | 16-MAR-15:00 | 22.80 | 8.72 | 0.339204E+09 | 495.44 | 21-MAR-14:20 | 24.07 | 9.24 |
| April | 0.339604E+10 | 5276.20 | 28-APR-15:00 | 28.90 | 14.03 | 0.309816E+09 | 495.45 | 28-APR-08:09 | 28.90 | 14.03 |
| May | 0.494733E+10 | 5546.48 | 19-MAY-15:00 | 34.40 | 16.86 | 0.343948E+09 | 495.46 | 19-MAY-08:09 | 34.40 | 16.86 |
| June | 0.578780E+10 | 6142.39 | 15-JUN-15:00 | 38.30 | 15.91 | 0.212557E+09 | 498.05 | 15-JUN-07:10 | 38.30 | 15.91 |
| July | 0.397606E+10 | 4348.00 | 03-JUL-14:40 | 37.40 | 18.90 | 72754360.56 | 78.24 | 06-JUL-17:10 | 34.82 | 19.46 |
| August | 0.390239E+10 | 4474.13 | 07-AUG-14:50 | 35.00 | 18.73 | 83369208.27 | 78.23 | 08-AUG-16:49 | 27.83 | 19.62 |
| September | 0.474288E+10 | 5820.68 | 19-SEP-15:00 | 33.30 | 16.48 | 0.193088E+09 | 495.48 | 20-SEP-07:00 | 23.90 | 16.99 |
| October | 0.386654E+10 | 5544.58 | 03-OCT-14:00 | 32.80 | 19.64 | 0.328013E+09 | 503.15 | 02-OCT-07:10 | 32.80 | 19.64 |
| November | 0.212101E+10 | 4037.32 | 10-NOV-14:30 | 15.85 | 10.28 | 0.311257E+09 | 495.44 | 10-NOV-08:00 | 15.85 | 10.28 |
| December | 0.128151E+10 | 2286.09 | 01-DEC-15:01 | 13.12 | 5.81 | 0.262718E+09 | 481.90 | 01-DEC-14:00 | 13.12 | 5.81 |
| Annual Sum or Average | 0.390360E+11 | 0.300354E+10 | ||||||||
| Minimum of Months | 0.128151E+10 | 2286.09 | 13.12 | 5.81 | 72754360.56 | 78.23 | 12.80 | 3.69 | ||
| Maximum of Months | 0.578780E+10 | 6142.39 | 38.30 | 19.64 | 0.343948E+09 | 503.15 | 38.30 | 19.64 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.179689E+10 | 3516.97 | 12-JAN-15:01 | 18.90 | 10.04 | 0.709170E+09 | 1277.22 | 12-JAN-15:20 | 18.90 | 10.07 |
| February | 0.179510E+10 | 3518.18 | 23-FEB-15:02 | 20.73 | 7.13 | 0.663468E+09 | 1277.21 | 07-FEB-15:20 | 20.73 | 7.13 |
| March | 0.262299E+10 | 4030.76 | 16-MAR-15:00 | 22.80 | 8.72 | 0.847995E+09 | 1277.22 | 17-MAR-14:20 | 13.30 | 4.16 |
| April | 0.382585E+10 | 5519.00 | 28-APR-15:00 | 28.90 | 14.03 | 0.788921E+09 | 1277.23 | 17-APR-14:20 | 28.90 | 14.03 |
| May | 0.563753E+10 | 6115.33 | 19-MAY-15:00 | 34.40 | 16.86 | 0.883524E+09 | 1277.23 | 30-MAY-14:20 | 34.40 | 17.58 |
| June | 0.651138E+10 | 6796.05 | 15-JUN-15:00 | 38.30 | 15.91 | 0.546577E+09 | 1277.23 | 15-JUN-07:49 | 38.30 | 15.91 |
| July | 0.482969E+10 | 4350.28 | 03-JUL-14:30 | 37.50 | 18.90 | 0.183902E+09 | 201.70 | 06-JUL-17:10 | 34.82 | 19.46 |
| August | 0.463149E+10 | 4605.53 | 07-AUG-16:00 | 37.20 | 17.89 | 0.208455E+09 | 201.69 | 08-AUG-16:49 | 27.83 | 19.62 |
| September | 0.526089E+10 | 6361.87 | 20-SEP-15:00 | 33.30 | 17.34 | 0.495526E+09 | 1277.26 | 20-SEP-07:00 | 33.30 | 17.34 |
| October | 0.420470E+10 | 6093.72 | 05-OCT-15:00 | 30.60 | 17.36 | 0.837994E+09 | 1277.24 | 02-OCT-07:40 | 30.60 | 17.36 |
| November | 0.258054E+10 | 4483.86 | 09-NOV-15:40 | 23.30 | 12.89 | 0.785700E+09 | 1277.23 | 10-NOV-15:20 | 15.40 | 10.12 |
| December | 0.162387E+10 | 3440.21 | 01-DEC-15:01 | 13.12 | 5.81 | 0.671358E+09 | 1261.54 | 15-DEC-15:00 | 15.60 | 6.14 |
| Annual Sum or Average | 0.453209E+11 | 0.762259E+10 | ||||||||
| Minimum of Months | 0.162387E+10 | 3440.21 | 13.12 | 5.81 | 0.183902E+09 | 201.69 | 13.30 | 4.16 | ||
| Maximum of Months | 0.651138E+10 | 6796.05 | 38.30 | 18.90 | 0.883524E+09 | 1277.26 | 38.30 | 19.62 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.974327E+10 | 16876.83 | 12-JAN-15:01 | 18.90 | 10.04 | 0.357349E+10 | 6152.11 | 12-JAN-15:50 | 18.90 | 10.15 |
| February | 0.964442E+10 | 16942.93 | 23-FEB-15:02 | 20.73 | 7.13 | 0.334754E+10 | 6153.90 | 24-FEB-15:20 | 12.80 | 3.69 |
| March | 0.134795E+11 | 17771.91 | 16-MAR-14:30 | 22.80 | 9.03 | 0.422809E+10 | 6153.91 | 17-MAR-14:20 | 13.30 | 4.16 |
| April | 0.180304E+11 | 22560.50 | 28-APR-14:50 | 28.90 | 14.03 | 0.382997E+10 | 6153.92 | 17-APR-14:20 | 28.90 | 14.03 |
| May | 0.249948E+11 | 24681.20 | 19-MAY-14:02 | 34.90 | 17.16 | 0.425785E+10 | 6153.93 | 30-MAY-14:20 | 34.40 | 17.58 |
| June | 0.277219E+11 | 26663.12 | 15-JUN-14:35 | 38.13 | 15.82 | 0.263055E+10 | 6153.92 | 06-JUN-14:20 | 38.13 | 15.82 |
| July | 0.207404E+11 | 18363.10 | 15-JUL-05:51 | 22.20 | 19.51 | 0.836867E+09 | 949.88 | 26-JUL-17:40 | 34.80 | 19.83 |
| August | 0.199533E+11 | 18223.34 | 03-AUG-03:51 | 22.80 | 19.65 | 0.946077E+09 | 939.66 | 07-AUG-17:49 | 34.78 | 18.54 |
| September | 0.224459E+11 | 24731.70 | 20-SEP-14:02 | 33.30 | 18.03 | 0.237773E+10 | 6153.91 | 20-SEP-08:09 | 33.30 | 18.03 |
| October | 0.191167E+11 | 23780.97 | 03-OCT-14:02 | 32.62 | 19.55 | 0.404357E+10 | 6153.97 | 02-OCT-07:40 | 32.62 | 19.55 |
| November | 0.127597E+11 | 18279.88 | 03-NOV-15:00 | 23.30 | 13.57 | 0.387265E+10 | 6153.94 | 10-NOV-15:20 | 15.40 | 10.12 |
| December | 0.893496E+10 | 16625.81 | 01-DEC-15:01 | 13.12 | 5.81 | 0.336922E+10 | 6081.32 | 01-DEC-14:20 | 13.12 | 5.81 |
| Annual Sum or Average | 0.207565E+12 | 0.373136E+11 | ||||||||
| Minimum of Months | 0.893496E+10 | 16625.81 | 13.12 | 5.81 | 0.836867E+09 | 939.66 | 12.80 | 3.69 | ||
| Maximum of Months | 0.277219E+11 | 26663.12 | 38.13 | 19.65 | 0.425785E+10 | 6153.97 | 38.13 | 19.83 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.256187E+10 | 5002.75 | 12-JAN-15:15 | 18.90 | 10.07 | 0.789108E+09 | 1277.23 | 23-JAN-15:20 | 10.60 | 6.35 |
| February | 0.242285E+10 | 6306.00 | 19-FEB-15:57 | 22.80 | 8.58 | 0.720392E+09 | 1278.81 | 02-FEB-13:30 | 22.80 | 8.58 |
| March | 0.325668E+10 | 5350.06 | 16-MAR-15:00 | 22.80 | 8.72 | 0.885176E+09 | 1277.23 | 01-MAR-15:20 | 22.80 | 8.72 |
| April | 0.427573E+10 | 6246.67 | 28-APR-15:00 | 28.90 | 14.03 | 0.794253E+09 | 1277.23 | 17-APR-14:20 | 28.90 | 14.03 |
| May | 0.579511E+10 | 6360.69 | 19-MAY-15:00 | 34.40 | 16.86 | 0.883629E+09 | 1277.23 | 30-MAY-14:20 | 34.40 | 17.58 |
| June | 0.649748E+10 | 6892.47 | 15-JUN-15:00 | 38.30 | 15.91 | 0.546162E+09 | 1277.23 | 06-JUN-14:20 | 38.30 | 15.91 |
| July | 0.489294E+10 | 4523.61 | 03-JUL-14:30 | 37.50 | 18.90 | 0.183905E+09 | 201.70 | 06-JUL-17:10 | 34.82 | 19.46 |
| August | 0.498606E+10 | 5537.13 | 06-AUG-16:01 | 36.10 | 18.33 | 0.210808E+09 | 201.69 | 08-AUG-16:49 | 27.83 | 19.62 |
| September | 0.603605E+10 | 7428.11 | 19-SEP-15:00 | 33.30 | 16.48 | 0.496780E+09 | 1277.30 | 20-SEP-07:00 | 23.90 | 16.99 |
| October | 0.528500E+10 | 8215.23 | 21-OCT-14:42 | 26.02 | 12.50 | 0.844558E+09 | 1277.24 | 02-OCT-07:30 | 26.02 | 12.50 |
| November | 0.359771E+10 | 6420.70 | 09-NOV-15:00 | 23.30 | 12.64 | 0.821096E+09 | 1278.52 | 16-NOV-10:09 | 8.07 | 4.30 |
| December | 0.232376E+10 | 4210.56 | 07-DEC-15:30 | 16.10 | 6.93 | 0.747240E+09 | 1278.32 | 04-DEC-13:09 | 16.10 | 6.93 |
| Annual Sum or Average | 0.519312E+11 | 0.792311E+10 | ||||||||
| Minimum of Months | 0.232376E+10 | 4210.56 | 16.10 | 6.93 | 0.183905E+09 | 201.69 | 8.07 | 4.30 | ||
| Maximum of Months | 0.649748E+10 | 8215.23 | 38.30 | 18.90 | 0.885176E+09 | 1278.81 | 38.30 | 19.62 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.135966E+11 | 22843.50 | 12-JAN-14:50 | 18.80 | 9.97 | 0.391857E+10 | 6153.94 | 23-JAN-15:20 | 10.60 | 6.35 |
| February | 0.128790E+11 | 30143.68 | 20-FEB-13:56 | 22.20 | 8.45 | 0.357164E+10 | 6162.73 | 02-FEB-13:30 | 22.20 | 8.45 |
| March | 0.167119E+11 | 24309.48 | 16-MAR-14:10 | 22.80 | 9.24 | 0.436215E+10 | 6153.93 | 01-MAR-15:20 | 22.80 | 9.24 |
| April | 0.202220E+11 | 26344.98 | 28-APR-14:03 | 28.90 | 14.04 | 0.385265E+10 | 6153.93 | 17-APR-14:20 | 28.90 | 14.04 |
| May | 0.258384E+11 | 26186.13 | 19-MAY-14:02 | 34.90 | 17.16 | 0.426020E+10 | 6153.93 | 30-MAY-14:20 | 34.40 | 17.58 |
| June | 0.278010E+11 | 27273.26 | 15-JUN-14:25 | 38.05 | 15.77 | 0.262878E+10 | 6153.92 | 06-JUN-14:20 | 38.05 | 15.77 |
| July | 0.209580E+11 | 18453.90 | 15-JUL-05:51 | 22.20 | 19.51 | 0.844820E+09 | 969.63 | 21-JUL-14:09 | 29.08 | 21.35 |
| August | 0.210399E+11 | 18732.35 | 06-AUG-14:41 | 35.92 | 18.43 | 0.985169E+09 | 971.71 | 30-AUG-11:50 | 28.43 | 18.17 |
| September | 0.259309E+11 | 30072.64 | 19-SEP-14:02 | 33.80 | 16.79 | 0.239277E+10 | 6154.26 | 20-SEP-07:00 | 23.90 | 16.99 |
| October | 0.241055E+11 | 30453.82 | 03-OCT-13:40 | 32.07 | 19.44 | 0.407477E+10 | 6177.26 | 23-OCT-12:20 | 23.13 | 13.57 |
| November | 0.177134E+11 | 28168.74 | 10-NOV-13:20 | 16.83 | 10.70 | 0.401045E+10 | 6163.40 | 10-NOV-13:20 | 16.83 | 10.70 |
| December | 0.123756E+11 | 19730.52 | 01-DEC-13:40 | 14.60 | 6.54 | 0.370941E+10 | 6160.75 | 04-DEC-13:09 | 10.97 | 6.76 |
| Annual Sum or Average | 0.239172E+12 | 0.386114E+11 | ||||||||
| Minimum of Months | 0.123756E+11 | 18453.90 | 14.60 | 6.54 | 0.844820E+09 | 969.63 | 10.60 | 6.35 | ||
| Maximum of Months | 0.278010E+11 | 30453.82 | 38.05 | 19.51 | 0.436215E+10 | 6177.26 | 38.05 | 21.35 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.149288E+10 | 2385.62 | 12-JAN-15:01 | 18.90 | 10.04 | 0.284159E+09 | 495.44 | 12-JAN-15:20 | 18.90 | 10.07 |
| February | 0.150142E+10 | 2814.05 | 22-FEB-14:30 | 21.95 | 7.96 | 0.268992E+09 | 495.44 | 24-FEB-15:20 | 12.80 | 3.69 |
| March | 0.221334E+10 | 3836.22 | 16-MAR-15:00 | 22.80 | 8.72 | 0.341307E+09 | 495.44 | 21-MAR-14:20 | 24.07 | 9.24 |
| April | 0.350313E+10 | 5361.56 | 28-APR-15:00 | 28.90 | 14.03 | 0.310265E+09 | 495.45 | 28-APR-08:09 | 28.90 | 14.03 |
| May | 0.506504E+10 | 5620.70 | 19-MAY-15:00 | 34.40 | 16.86 | 0.344102E+09 | 495.46 | 19-MAY-08:09 | 34.40 | 16.86 |
| June | 0.591970E+10 | 6210.16 | 15-JUN-15:00 | 38.30 | 15.91 | 0.212593E+09 | 499.42 | 15-JUN-07:10 | 38.30 | 15.91 |
| July | 0.417555E+10 | 4545.09 | 03-JUL-14:40 | 37.40 | 18.90 | 72893329.83 | 78.24 | 06-JUL-17:10 | 34.82 | 19.46 |
| August | 0.411646E+10 | 4686.66 | 07-AUG-14:50 | 35.00 | 18.73 | 83602206.19 | 78.23 | 08-AUG-16:49 | 27.83 | 19.62 |
| September | 0.488129E+10 | 5907.75 | 19-SEP-14:50 | 33.40 | 16.54 | 0.193152E+09 | 495.48 | 20-SEP-07:00 | 23.90 | 16.99 |
| October | 0.397706E+10 | 5641.38 | 03-OCT-14:00 | 32.80 | 19.64 | 0.328225E+09 | 505.90 | 02-OCT-07:10 | 32.80 | 19.64 |
| November | 0.219948E+10 | 4154.45 | 10-NOV-14:30 | 15.85 | 10.28 | 0.312820E+09 | 495.44 | 10-NOV-08:00 | 15.85 | 10.28 |
| December | 0.133956E+10 | 2336.97 | 01-DEC-15:01 | 13.12 | 5.81 | 0.266313E+09 | 488.71 | 01-DEC-14:00 | 13.12 | 5.81 |
| Annual Sum or Average | 0.403849E+11 | 0.301842E+10 | ||||||||
| Minimum of Months | 0.133956E+10 | 2336.97 | 13.12 | 5.81 | 72893329.83 | 78.23 | 12.80 | 3.69 | ||
| Maximum of Months | 0.591970E+10 | 6210.16 | 38.30 | 19.64 | 0.344102E+09 | 505.90 | 38.30 | 19.64 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.181290E+10 | 3518.40 | 12-JAN-15:01 | 18.90 | 10.04 | 0.711547E+09 | 1277.22 | 12-JAN-15:20 | 18.90 | 10.07 |
| February | 0.181127E+10 | 3519.89 | 23-FEB-15:02 | 20.73 | 7.13 | 0.665776E+09 | 1277.21 | 07-FEB-15:20 | 20.73 | 7.13 |
| March | 0.264332E+10 | 4067.07 | 16-MAR-15:00 | 22.80 | 8.72 | 0.850068E+09 | 1277.22 | 17-MAR-14:20 | 13.30 | 4.16 |
| April | 0.385564E+10 | 5562.28 | 28-APR-15:00 | 28.90 | 14.03 | 0.789476E+09 | 1277.23 | 17-APR-14:20 | 28.90 | 14.03 |
| May | 0.567695E+10 | 6155.39 | 19-MAY-15:00 | 34.40 | 16.86 | 0.883678E+09 | 1277.23 | 30-MAY-14:20 | 34.40 | 17.58 |
| June | 0.655003E+10 | 6830.83 | 15-JUN-15:00 | 38.30 | 15.91 | 0.546636E+09 | 1277.23 | 15-JUN-07:49 | 38.30 | 15.91 |
| July | 0.488604E+10 | 4445.62 | 03-JUL-14:30 | 37.50 | 18.90 | 0.184370E+09 | 201.70 | 06-JUL-17:10 | 34.82 | 19.46 |
| August | 0.468283E+10 | 4683.04 | 07-AUG-16:00 | 37.20 | 17.89 | 0.209163E+09 | 201.69 | 08-AUG-16:49 | 27.83 | 19.62 |
| September | 0.529830E+10 | 6416.45 | 20-SEP-15:00 | 33.30 | 17.34 | 0.495605E+09 | 1277.25 | 20-SEP-07:00 | 33.30 | 17.34 |
| October | 0.423007E+10 | 6140.25 | 05-OCT-15:00 | 30.60 | 17.36 | 0.838165E+09 | 1277.24 | 02-OCT-07:40 | 30.60 | 17.36 |
| November | 0.259353E+10 | 4507.58 | 09-NOV-15:40 | 23.30 | 12.89 | 0.786782E+09 | 1277.23 | 10-NOV-15:20 | 15.40 | 10.12 |
| December | 0.164070E+10 | 3457.59 | 01-DEC-15:01 | 13.12 | 5.81 | 0.673752E+09 | 1266.87 | 15-DEC-15:00 | 15.60 | 6.14 |
| Annual Sum or Average | 0.456816E+11 | 0.763502E+10 | ||||||||
| Minimum of Months | 0.164070E+10 | 3457.59 | 13.12 | 5.81 | 0.184370E+09 | 201.69 | 13.30 | 4.16 | ||
| Maximum of Months | 0.655003E+10 | 6830.83 | 38.30 | 18.90 | 0.883678E+09 | 1277.25 | 38.30 | 19.62 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.650172E+10 | 11182.33 | 12-JAN-15:01 | 18.90 | 10.04 | 0.236878E+10 | 4063.23 | 12-JAN-15:00 | 18.90 | 10.18 |
| February | 0.643605E+10 | 11200.71 | 23-FEB-15:02 | 20.73 | 7.13 | 0.221834E+10 | 4063.92 | 08-FEB-15:20 | 20.73 | 7.13 |
| March | 0.898973E+10 | 11922.59 | 16-MAR-14:50 | 22.80 | 8.82 | 0.279646E+10 | 4063.90 | 17-MAR-14:20 | 13.30 | 4.16 |
| April | 0.120451E+11 | 15161.90 | 21-APR-14:50 | 32.20 | 15.45 | 0.253063E+10 | 4063.91 | 17-APR-14:20 | 32.20 | 15.45 |
| May | 0.167257E+11 | 16566.62 | 19-MAY-14:02 | 34.90 | 17.16 | 0.281297E+10 | 4063.92 | 30-MAY-14:20 | 34.40 | 17.58 |
| June | 0.185726E+11 | 17878.07 | 15-JUN-15:00 | 38.30 | 15.91 | 0.173806E+10 | 4063.91 | 06-JUN-14:20 | 38.30 | 15.91 |
| July | 0.139052E+11 | 12211.53 | 15-JUL-05:51 | 22.20 | 19.51 | 0.559718E+09 | 638.22 | 21-JUL-14:09 | 29.08 | 21.35 |
| August | 0.133681E+11 | 12114.38 | 03-AUG-03:51 | 22.80 | 19.65 | 0.632091E+09 | 627.36 | 07-AUG-17:49 | 34.78 | 18.54 |
| September | 0.150125E+11 | 16678.55 | 21-SEP-14:02 | 31.78 | 18.05 | 0.157167E+10 | 4063.90 | 20-SEP-07:00 | 31.78 | 18.05 |
| October | 0.127581E+11 | 16061.72 | 03-OCT-14:02 | 32.62 | 19.55 | 0.267104E+10 | 4063.94 | 02-OCT-07:40 | 32.62 | 19.55 |
| November | 0.848798E+10 | 12261.05 | 03-NOV-15:00 | 23.30 | 13.57 | 0.256036E+10 | 4063.92 | 10-NOV-15:20 | 15.40 | 10.12 |
| December | 0.597689E+10 | 11072.15 | 01-DEC-15:01 | 13.12 | 5.81 | 0.223561E+10 | 4050.47 | 01-DEC-14:20 | 13.12 | 5.81 |
| Annual Sum or Average | 0.138780E+12 | 0.246957E+11 | ||||||||
| Minimum of Months | 0.597689E+10 | 11072.15 | 13.12 | 5.81 | 0.559718E+09 | 627.36 | 13.12 | 4.16 | ||
| Maximum of Months | 0.185726E+11 | 17878.07 | 38.30 | 19.65 | 0.281297E+10 | 4063.94 | 38.30 | 21.35 |
Report: ZoneCoolingSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.408808E+10 | 5778.72 | 12-JAN-15:01 | 18.90 | 10.04 | 0.192044E+10 | 2090.02 | 25-JAN-15:20 | 10.00 | 3.62 |
| February | 0.404069E+10 | 6313.60 | 23-FEB-14:40 | 21.47 | 7.31 | 0.177745E+10 | 2090.02 | 08-FEB-16:19 | 21.47 | 7.31 |
| March | 0.568126E+10 | 7189.38 | 16-MAR-14:30 | 22.80 | 9.03 | 0.220941E+10 | 2090.16 | 10-MAR-17:49 | 22.80 | 9.03 |
| April | 0.749435E+10 | 8688.75 | 21-APR-14:02 | 32.20 | 15.26 | 0.194906E+10 | 2090.01 | 17-APR-14:20 | 32.20 | 15.26 |
| May | 0.101995E+11 | 9337.92 | 19-MAY-14:02 | 34.90 | 17.16 | 0.214799E+10 | 2090.03 | 24-MAY-15:20 | 28.87 | 18.13 |
| June | 0.118795E+11 | 9992.95 | 15-JUN-15:02 | 38.22 | 15.87 | 0.214917E+10 | 2090.03 | 29-JUN-15:20 | 28.30 | 18.33 |
| July | 0.811794E+10 | 6777.74 | 03-JUL-14:30 | 37.50 | 18.90 | 0.102135E+10 | 1100.11 | 03-JUL-18:00 | 31.70 | 19.81 |
| August | 0.787079E+10 | 6560.32 | 04-AUG-14:02 | 35.10 | 19.57 | 0.116838E+10 | 1100.07 | 08-AUG-16:49 | 27.83 | 19.62 |
| September | 0.970845E+10 | 9421.16 | 20-SEP-14:02 | 33.30 | 18.03 | 0.190642E+10 | 2090.13 | 20-SEP-07:00 | 33.30 | 18.03 |
| October | 0.790697E+10 | 9133.37 | 03-OCT-14:02 | 32.62 | 19.55 | 0.204935E+10 | 2090.05 | 13-OCT-07:19 | 14.60 | 13.36 |
| November | 0.532275E+10 | 7327.08 | 10-NOV-12:40 | 18.50 | 11.34 | 0.200984E+10 | 2091.47 | 16-NOV-10:09 | 8.07 | 4.30 |
| December | 0.382269E+10 | 5736.28 | 01-DEC-15:01 | 13.12 | 5.81 | 0.180804E+10 | 2090.02 | 01-DEC-16:19 | 11.67 | 5.25 |
| Annual Sum or Average | 0.861329E+11 | 0.221169E+11 | ||||||||
| Minimum of Months | 0.382269E+10 | 5736.28 | 13.12 | 5.81 | 0.102135E+10 | 1100.07 | 8.07 | 3.62 | ||
| Maximum of Months | 0.118795E+11 | 9992.95 | 38.22 | 19.57 | 0.220941E+10 | 2091.47 | 33.30 | 19.81 |
Report: ZoneCoolingSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.312940E+10 | 5083.36 | 12-JAN-15:01 | 18.90 | 10.04 | 0.791153E+09 | 1362.95 | 12-JAN-15:50 | 18.90 | 10.15 |
| February | 0.326720E+10 | 6070.26 | 23-FEB-14:40 | 21.47 | 7.31 | 0.768948E+09 | 1408.93 | 24-FEB-15:20 | 12.80 | 3.69 |
| March | 0.553530E+10 | 9459.85 | 16-MAR-15:00 | 22.80 | 8.72 | 0.993969E+09 | 1408.93 | 21-MAR-14:20 | 24.07 | 9.24 |
| April | 0.944424E+10 | 13453.60 | 28-APR-14:50 | 28.90 | 14.03 | 0.890197E+09 | 1416.87 | 17-APR-07:10 | 28.90 | 14.03 |
| May | 0.138812E+11 | 17977.29 | 30-MAY-07:03 | 25.78 | 12.49 | 0.981120E+09 | 1528.50 | 30-MAY-07:10 | 25.78 | 12.49 |
| June | 0.161145E+11 | 18216.05 | 19-JUN-07:03 | 24.50 | 16.82 | 0.605483E+09 | 1542.75 | 05-JUN-07:10 | 24.50 | 16.82 |
| July | 0.122177E+11 | 17917.35 | 03-JUL-07:03 | 27.98 | 16.41 | 0.208287E+09 | 238.99 | 03-JUL-07:10 | 27.98 | 16.41 |
| August | 0.117033E+11 | 18013.36 | 07-AUG-07:03 | 26.47 | 16.94 | 0.239375E+09 | 241.78 | 07-AUG-07:10 | 26.47 | 16.94 |
| September | 0.123072E+11 | 17814.25 | 18-SEP-07:02 | 21.05 | 15.73 | 0.550003E+09 | 1482.10 | 18-SEP-07:10 | 21.05 | 15.73 |
| October | 0.923936E+10 | 17756.84 | 02-OCT-07:03 | 22.02 | 15.21 | 0.935082E+09 | 1492.40 | 02-OCT-07:10 | 22.02 | 15.21 |
| November | 0.469951E+10 | 8782.20 | 10-NOV-14:10 | 16.02 | 10.33 | 0.891692E+09 | 1409.02 | 01-NOV-08:39 | 16.02 | 10.33 |
| December | 0.262511E+10 | 4950.36 | 01-DEC-15:01 | 13.12 | 5.81 | 0.730325E+09 | 1335.32 | 01-DEC-14:50 | 13.12 | 5.81 |
| Annual Sum or Average | 0.104164E+12 | 0.858564E+10 | ||||||||
| Minimum of Months | 0.262511E+10 | 4950.36 | 13.12 | 5.81 | 0.208287E+09 | 238.99 | 12.80 | 3.69 | ||
| Maximum of Months | 0.161145E+11 | 18216.05 | 28.90 | 16.94 | 0.993969E+09 | 1542.75 | 28.90 | 16.94 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.668644E+09 | 2549.18 | 01-JAN-13:52 | 15.60 | 9.33 | 0.420166E+09 | 874.44 | 03-JAN-14:00 | 20.60 | 8.39 |
| February | 0.835737E+09 | 3877.38 | 21-FEB-15:00 | 22.80 | 8.17 | 0.398684E+09 | 882.51 | 07-FEB-13:20 | 22.80 | 8.17 |
| March | 0.158163E+10 | 5487.70 | 21-MAR-15:00 | 24.40 | 9.43 | 0.519025E+09 | 882.58 | 22-MAR-14:39 | 24.07 | 8.96 |
| April | 0.392104E+10 | 12839.79 | 21-APR-15:00 | 32.20 | 15.49 | 0.516788E+09 | 1272.94 | 21-APR-14:00 | 32.20 | 15.49 |
| May | 0.699168E+10 | 14096.54 | 30-MAY-15:00 | 34.40 | 17.77 | 0.617940E+09 | 1419.83 | 30-MAY-14:00 | 34.40 | 17.77 |
| June | 0.949615E+10 | 15936.84 | 15-JUN-15:00 | 38.30 | 15.91 | 0.410900E+09 | 1673.31 | 15-JUN-14:00 | 38.30 | 15.91 |
| July | 0.763872E+10 | 15371.04 | 03-JUL-14:50 | 37.30 | 18.89 | 0.135023E+09 | 250.45 | 03-JUL-14:00 | 37.20 | 18.88 |
| August | 0.739236E+10 | 14764.15 | 08-AUG-15:00 | 36.10 | 18.23 | 0.152502E+09 | 238.05 | 08-AUG-15:09 | 35.25 | 18.61 |
| September | 0.754133E+10 | 13736.08 | 19-SEP-14:20 | 33.70 | 16.73 | 0.352176E+09 | 1380.50 | 19-SEP-14:30 | 33.60 | 16.66 |
| October | 0.475377E+10 | 13185.55 | 03-OCT-14:20 | 32.43 | 19.47 | 0.555632E+09 | 1302.46 | 03-OCT-14:30 | 32.25 | 19.38 |
| November | 0.170526E+10 | 7252.71 | 11-NOV-13:56 | 18.30 | 7.98 | 0.487392E+09 | 882.54 | 08-NOV-15:09 | 18.30 | 7.98 |
| December | 0.442523E+09 | 2355.89 | 16-DEC-15:02 | 15.00 | 4.18 | 0.383398E+09 | 746.38 | 20-DEC-15:09 | 17.62 | 5.06 |
| Annual Sum or Average | 0.529689E+11 | 0.494963E+10 | ||||||||
| Minimum of Months | 0.442523E+09 | 2355.89 | 15.00 | 4.18 | 0.135023E+09 | 238.05 | 17.62 | 5.06 | ||
| Maximum of Months | 0.949615E+10 | 15936.84 | 38.30 | 19.47 | 0.617940E+09 | 1673.31 | 38.30 | 19.38 |
Report: ZoneCoolingSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.289428E+10 | 4091.42 | 12-JAN-15:01 | 18.90 | 10.04 | 0.135134E+09 | 226.81 | 12-JAN-15:09 | 18.90 | 10.04 |
| February | 0.284969E+10 | 4352.62 | 23-FEB-15:02 | 20.73 | 7.13 | 0.130301E+09 | 244.09 | 23-FEB-14:00 | 20.73 | 7.13 |
| March | 0.389877E+10 | 13496.51 | 19-MAR-14:59 | 23.30 | 8.99 | 0.169611E+09 | 247.12 | 21-MAR-14:39 | 24.23 | 9.34 |
| April | 0.535852E+10 | 14623.62 | 20-APR-22:41 | 23.30 | 9.60 | 0.154653E+09 | 247.13 | 21-APR-11:09 | 28.17 | 12.81 |
| May | 0.736817E+10 | 14653.58 | 20-MAY-02:31 | 23.67 | 9.96 | 0.171399E+09 | 247.14 | 19-MAY-08:30 | 23.67 | 9.96 |
| June | 0.863880E+10 | 14755.09 | 18-JUN-12:23 | 35.00 | 15.67 | 0.105932E+09 | 247.14 | 15-JUN-08:09 | 35.00 | 15.67 |
| July | 0.623042E+10 | 14792.82 | 15-JUL-05:51 | 22.20 | 19.51 | 35062393.50 | 39.02 | 24-JUL-11:00 | 31.10 | 18.94 |
| August | 0.596194E+10 | 14793.83 | 03-AUG-03:51 | 22.80 | 19.65 | 39768830.67 | 38.99 | 07-AUG-14:39 | 35.00 | 18.73 |
| September | 0.674562E+10 | 14716.82 | 19-SEP-21:51 | 22.80 | 14.59 | 95868833.74 | 247.14 | 19-SEP-08:30 | 22.80 | 14.59 |
| October | 0.515458E+10 | 14762.77 | 05-OCT-02:11 | 23.13 | 16.50 | 0.161824E+09 | 247.13 | 17-OCT-10:20 | 21.83 | 16.64 |
| November | 0.350268E+10 | 6602.85 | 11-NOV-11:41 | 17.02 | 7.80 | 0.151054E+09 | 247.12 | 09-NOV-12:00 | 17.02 | 7.80 |
| December | 0.265953E+10 | 4004.87 | 01-DEC-15:01 | 13.12 | 5.81 | 0.124900E+09 | 223.24 | 01-DEC-14:20 | 13.12 | 5.81 |
| Annual Sum or Average | 0.612630E+11 | 0.147551E+10 | ||||||||
| Minimum of Months | 0.265953E+10 | 4004.87 | 13.12 | 5.81 | 35062393.50 | 38.99 | 13.12 | 5.81 | ||
| Maximum of Months | 0.863880E+10 | 14793.83 | 35.00 | 19.65 | 0.171399E+09 | 247.14 | 35.00 | 18.94 |
Report: ZoneCoolingSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.144060E+10 | 2389.05 | 12-JAN-15:01 | 18.90 | 10.04 | 0.270061E+09 | 481.24 | 12-JAN-15:50 | 18.90 | 10.15 |
| February | 0.147200E+10 | 2588.60 | 23-FEB-15:02 | 20.73 | 7.13 | 0.263858E+09 | 522.75 | 23-FEB-14:00 | 20.73 | 7.13 |
| March | 0.211341E+10 | 2735.92 | 17-MAR-14:01 | 13.30 | 4.19 | 0.355794E+09 | 576.59 | 16-MAR-14:00 | 13.30 | 4.19 |
| April | 0.291757E+10 | 4723.81 | 30-APR-18:25 | 28.90 | 12.26 | 0.356948E+09 | 621.09 | 28-APR-14:20 | 28.90 | 12.26 |
| May | 0.421364E+10 | 8074.10 | 14-MAY-16:02 | 32.12 | 13.71 | 0.416897E+09 | 621.11 | 30-MAY-14:20 | 34.40 | 17.58 |
| June | 0.518085E+10 | 10149.85 | 03-JUN-14:41 | 34.08 | 20.20 | 0.263050E+09 | 621.10 | 06-JUN-14:20 | 36.30 | 17.21 |
| July | 0.411463E+10 | 10164.30 | 30-JUL-15:21 | 31.95 | 19.78 | 86082273.71 | 98.07 | 06-JUL-17:40 | 31.95 | 19.78 |
| August | 0.394404E+10 | 10208.80 | 06-AUG-16:01 | 36.10 | 18.33 | 96989496.74 | 98.07 | 07-AUG-18:10 | 33.95 | 18.47 |
| September | 0.397152E+10 | 8077.80 | 02-SEP-16:02 | 32.23 | 18.13 | 0.233678E+09 | 621.10 | 20-SEP-14:20 | 33.30 | 17.90 |
| October | 0.293429E+10 | 3420.35 | 05-OCT-15:00 | 30.60 | 17.36 | 0.373931E+09 | 621.10 | 03-OCT-14:20 | 30.60 | 17.36 |
| November | 0.191996E+10 | 2864.60 | 10-NOV-15:01 | 15.50 | 10.16 | 0.318985E+09 | 570.93 | 10-NOV-15:09 | 15.50 | 10.16 |
| December | 0.130906E+10 | 2336.22 | 01-DEC-15:01 | 13.12 | 5.81 | 0.250175E+09 | 471.21 | 01-DEC-14:00 | 13.12 | 5.81 |
| Annual Sum or Average | 0.355315E+11 | 0.328645E+10 | ||||||||
| Minimum of Months | 0.130906E+10 | 2336.22 | 13.12 | 4.19 | 86082273.71 | 98.07 | 13.12 | 4.19 | ||
| Maximum of Months | 0.518085E+10 | 10208.80 | 36.10 | 20.20 | 0.416897E+09 | 621.11 | 36.30 | 19.78 |
Report: ZoneCoolingSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.515444E+10 | 24043.93 | 04-JAN-15:01 | 12.20 | 3.28 | 0.615986E+09 | 1197.57 | 11-JAN-15:09 | 16.02 | 6.77 |
| February | 0.549124E+10 | 24087.52 | 24-FEB-15:01 | 12.80 | 3.76 | 0.571305E+09 | 1197.58 | 13-FEB-13:09 | 12.80 | 3.76 |
| March | 0.828294E+10 | 24335.86 | 17-MAR-14:01 | 13.30 | 4.19 | 0.705220E+09 | 1197.62 | 21-MAR-14:09 | 23.98 | 9.19 |
| April | 0.122730E+11 | 24704.91 | 17-APR-14:01 | 17.20 | 10.34 | 0.625599E+09 | 1197.64 | 20-APR-12:09 | 28.30 | 12.66 |
| May | 0.172886E+11 | 24417.46 | 30-MAY-14:01 | 34.40 | 17.53 | 0.689772E+09 | 1246.31 | 30-MAY-07:10 | 34.40 | 17.53 |
| June | 0.206792E+11 | 29387.23 | 18-JUN-12:23 | 35.00 | 15.67 | 0.690425E+09 | 1246.31 | 05-JUN-07:10 | 35.00 | 15.67 |
| July | 0.158826E+11 | 29281.03 | 30-JUL-14:01 | 31.70 | 19.83 | 0.354542E+09 | 650.55 | 03-JUL-07:10 | 31.70 | 19.83 |
| August | 0.159231E+11 | 29537.01 | 06-AUG-13:21 | 34.45 | 18.10 | 0.407413E+09 | 655.93 | 07-AUG-07:10 | 26.47 | 16.94 |
| September | 0.177670E+11 | 27806.90 | 02-SEP-14:02 | 32.20 | 18.11 | 0.613683E+09 | 1246.36 | 18-SEP-07:10 | 21.05 | 15.73 |
| October | 0.138653E+11 | 26886.74 | 09-OCT-13:19 | 23.67 | 14.65 | 0.657886E+09 | 1246.37 | 02-OCT-07:10 | 23.67 | 14.65 |
| November | 0.825748E+10 | 24803.97 | 10-NOV-15:01 | 15.50 | 10.16 | 0.644897E+09 | 1197.62 | 08-NOV-15:09 | 15.50 | 10.16 |
| December | 0.448813E+10 | 23921.77 | 01-DEC-15:01 | 13.12 | 5.81 | 0.578418E+09 | 1197.84 | 04-DEC-13:09 | 10.97 | 6.76 |
| Annual Sum or Average | 0.145353E+12 | 0.715514E+10 | ||||||||
| Minimum of Months | 0.448813E+10 | 23921.77 | 12.20 | 3.28 | 0.354542E+09 | 650.55 | 10.97 | 3.76 | ||
| Maximum of Months | 0.206792E+11 | 29537.01 | 35.00 | 19.83 | 0.705220E+09 | 1246.37 | 35.00 | 19.83 |
Report: ZoneCoolingSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.731828E+10 | 11509.09 | 13-JAN-16:10 | 18.12 | 8.89 | 0.316266E+10 | 5528.16 | 05-JAN-16:19 | 18.12 | 8.89 |
| February | 0.762325E+10 | 12803.18 | 21-FEB-16:15 | 22.60 | 8.05 | 0.294190E+10 | 5528.17 | 01-FEB-16:19 | 22.60 | 8.05 |
| March | 0.116228E+11 | 26216.34 | 16-MAR-05:01 | 14.43 | 5.41 | 0.360666E+10 | 5528.28 | 10-MAR-17:00 | 14.43 | 5.41 |
| April | 0.155565E+11 | 28790.17 | 03-APR-05:02 | 17.48 | 7.89 | 0.315929E+10 | 5528.32 | 13-APR-15:09 | 24.50 | 9.99 |
| May | 0.206484E+11 | 28724.57 | 22-MAY-05:01 | 17.98 | 13.97 | 0.347796E+10 | 5528.28 | 03-MAY-15:09 | 17.98 | 13.97 |
| June | 0.235456E+11 | 28475.42 | 26-JUN-05:01 | 21.10 | 14.86 | 0.347867E+10 | 5528.22 | 29-JUN-15:20 | 28.30 | 18.33 |
| July | 0.178202E+11 | 29574.10 | 21-JUL-05:01 | 20.60 | 20.60 | 0.190372E+10 | 2036.95 | 25-JUL-07:49 | 26.52 | 19.03 |
| August | 0.172965E+11 | 29608.03 | 21-AUG-05:01 | 20.92 | 15.81 | 0.218522E+10 | 2036.84 | 08-AUG-16:49 | 20.92 | 15.81 |
| September | 0.187706E+11 | 28908.69 | 18-SEP-05:01 | 18.30 | 13.86 | 0.309831E+10 | 5528.20 | 06-SEP-15:20 | 18.30 | 13.86 |
| October | 0.146485E+11 | 28640.73 | 02-OCT-05:01 | 23.72 | 15.10 | 0.331472E+10 | 5528.11 | 03-OCT-15:20 | 30.93 | 18.47 |
| November | 0.961527E+10 | 22685.71 | 10-NOV-06:02 | 17.87 | 11.05 | 0.326484E+10 | 5528.13 | 16-NOV-16:19 | 12.60 | 4.84 |
| December | 0.662340E+10 | 10334.53 | 15-DEC-16:10 | 15.50 | 6.10 | 0.294201E+10 | 5528.17 | 01-DEC-16:19 | 15.50 | 6.10 |
| Annual Sum or Average | 0.171089E+12 | 0.365360E+11 | ||||||||
| Minimum of Months | 0.662340E+10 | 10334.53 | 14.43 | 5.41 | 0.190372E+10 | 2036.84 | 12.60 | 4.84 | ||
| Maximum of Months | 0.235456E+11 | 29608.03 | 23.72 | 20.60 | 0.360666E+10 | 5528.32 | 30.93 | 19.03 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.129065E+11 | 81815.80 | 27-JAN-06:01 | -3.1 | -5.6 | 0.642761E+10 | 8102.44 | 02-JAN-12:00 | -3.1 | -5.6 |
| February | 0.127724E+11 | 83280.46 | 03-FEB-06:01 | -3.7 | -6.1 | 0.581026E+10 | 8102.44 | 14-FEB-11:00 | 16.10 | 8.76 |
| March | 0.165411E+11 | 83972.27 | 02-MAR-06:01 | -3.5 | -6.2 | 0.671333E+10 | 8102.35 | 28-MAR-11:30 | 15.25 | 6.87 |
| April | 0.178677E+11 | 70226.51 | 12-APR-05:11 | 4.03 | -1.2 | 0.617473E+10 | 8102.55 | 18-APR-11:50 | 17.33 | 11.50 |
| May | 0.209085E+11 | 58680.17 | 02-MAY-04:12 | 11.47 | 4.79 | 0.657103E+10 | 8102.55 | 25-MAY-09:00 | 23.90 | 17.31 |
| June | 0.209466E+11 | 50649.20 | 13-JUN-05:01 | 15.18 | 4.59 | 0.611512E+10 | 8102.52 | 09-JUN-09:00 | 15.18 | 4.59 |
| July | 0.184649E+11 | 32692.10 | 11-JUL-05:01 | 21.70 | 15.06 | 0.565777E+10 | 7015.36 | 19-JUL-10:00 | 23.90 | 21.10 |
| August | 0.188910E+11 | 39383.68 | 23-AUG-05:01 | 20.00 | 11.78 | 0.599189E+10 | 7012.61 | 14-AUG-09:09 | 20.00 | 11.78 |
| September | 0.189319E+11 | 46017.39 | 25-SEP-05:01 | 9.08 | 8.55 | 0.586100E+10 | 8102.59 | 22-SEP-09:20 | 9.08 | 8.55 |
| October | 0.185039E+11 | 55137.26 | 31-OCT-04:12 | 14.83 | 6.48 | 0.642818E+10 | 8102.65 | 16-OCT-10:20 | 14.83 | 6.48 |
| November | 0.149455E+11 | 73496.49 | 21-NOV-06:11 | 2.20 | -2.4 | 0.631722E+10 | 8102.57 | 03-NOV-10:39 | 2.20 | -2.4 |
| December | 0.120136E+11 | 84440.09 | 19-DEC-06:01 | -2.8 | -6.7 | 0.628483E+10 | 8102.35 | 11-DEC-12:00 | -2.8 | -6.7 |
| Annual Sum or Average | 0.203694E+12 | 0.743530E+11 | ||||||||
| Minimum of Months | 0.120136E+11 | 32692.10 | -3.7 | -6.7 | 0.565777E+10 | 7012.61 | -3.1 | -6.7 | ||
| Maximum of Months | 0.209466E+11 | 84440.09 | 21.70 | 15.06 | 0.671333E+10 | 8102.65 | 23.90 | 21.10 |
Report: ZoneCoolingSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.133377E+11 | 33131.81 | 27-JAN-08:61 | -3.5 | -7.2 | 0.894744E+10 | 16257.35 | 12-JAN-14:00 | -3.5 | -7.2 |
| February | 0.125552E+11 | 31941.03 | 10-FEB-08:61 | -2.0 | -4.5 | 0.828579E+10 | 16256.66 | 14-FEB-14:50 | 17.30 | 8.72 |
| March | 0.161689E+11 | 29864.63 | 02-MAR-08:61 | -0.9 | -4.7 | 0.103515E+11 | 16256.33 | 08-MAR-12:09 | 17.30 | 7.74 |
| April | 0.173996E+11 | 91945.51 | 21-APR-05:02 | 15.10 | 5.09 | 0.915386E+10 | 16259.55 | 18-APR-12:00 | 15.10 | 5.09 |
| May | 0.225890E+11 | 96703.25 | 01-MAY-05:01 | 14.40 | 5.02 | 0.100948E+11 | 16260.49 | 25-MAY-08:39 | 20.53 | 16.38 |
| June | 0.254948E+11 | 96681.05 | 13-JUN-05:01 | 15.18 | 4.59 | 0.100972E+11 | 16260.64 | 28-JUN-08:50 | 20.32 | 16.45 |
| July | 0.141662E+11 | 61002.74 | 11-JUL-05:01 | 21.70 | 15.06 | 0.234096E+10 | 5990.18 | 07-JUL-16:49 | 21.70 | 15.06 |
| August | 0.142153E+11 | 71762.68 | 23-AUG-05:01 | 20.00 | 11.78 | 0.269205E+10 | 5990.16 | 24-AUG-17:49 | 27.98 | 17.05 |
| September | 0.208645E+11 | 80220.69 | 25-SEP-05:01 | 9.08 | 8.55 | 0.883709E+10 | 16260.48 | 08-SEP-08:39 | 9.08 | 8.55 |
| October | 0.185327E+11 | 75598.59 | 23-OCT-05:01 | 12.80 | 9.91 | 0.961313E+10 | 16261.54 | 16-OCT-10:00 | 12.80 | 9.91 |
| November | 0.148139E+11 | 25883.10 | 10-NOV-12:30 | 19.15 | 11.55 | 0.937896E+10 | 16260.30 | 03-NOV-11:50 | 19.15 | 11.55 |
| December | 0.128809E+11 | 32067.61 | 27-DEC-08:61 | -3.4 | -4.3 | 0.827230E+10 | 16256.17 | 08-DEC-14:00 | -3.4 | -4.3 |
| Annual Sum or Average | 0.203019E+12 | 0.980651E+11 | ||||||||
| Minimum of Months | 0.125552E+11 | 25883.10 | -3.5 | -7.2 | 0.234096E+10 | 5990.16 | -3.5 | -7.2 | ||
| Maximum of Months | 0.254948E+11 | 96703.25 | 21.70 | 15.06 | 0.103515E+11 | 16261.54 | 27.98 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.592989E+10 | 9456.36 | 12-JAN-15:03 | 18.90 | 10.04 | 0.130353E+10 | 2059.31 | 25-JAN-15:20 | 10.00 | 3.62 |
| February | 0.632104E+10 | 11532.03 | 23-FEB-14:40 | 21.47 | 7.31 | 0.120550E+10 | 2061.44 | 24-FEB-10:39 | 8.33 | 2.60 |
| March | 0.978754E+10 | 14111.76 | 16-MAR-14:00 | 22.80 | 9.34 | 0.148423E+10 | 2059.32 | 27-MAR-08:30 | 6.95 | 3.66 |
| April | 0.143334E+11 | 18081.61 | 28-APR-14:03 | 28.90 | 14.04 | 0.130244E+10 | 2118.04 | 03-APR-07:10 | 28.90 | 14.04 |
| May | 0.201887E+11 | 26617.95 | 15-MAY-07:03 | 21.97 | 11.12 | 0.143481E+10 | 2255.35 | 30-MAY-07:10 | 25.78 | 12.49 |
| June | 0.230592E+11 | 32082.52 | 18-JUN-12:23 | 35.00 | 15.67 | 0.885549E+09 | 2255.36 | 07-JUN-07:10 | 35.00 | 15.67 |
| July | 0.165894E+11 | 27372.76 | 16-JUL-10:49 | 29.32 | 20.17 | 0.304405E+09 | 346.69 | 03-JUL-07:10 | 29.32 | 20.17 |
| August | 0.161240E+11 | 27555.68 | 06-AUG-14:41 | 35.92 | 18.43 | 0.349800E+09 | 346.81 | 07-AUG-07:10 | 26.47 | 16.94 |
| September | 0.185896E+11 | 27155.41 | 18-SEP-07:02 | 21.05 | 15.73 | 0.804416E+09 | 2255.38 | 18-SEP-07:10 | 21.05 | 15.73 |
| October | 0.148336E+11 | 25876.06 | 02-OCT-07:03 | 22.02 | 15.21 | 0.136808E+10 | 2250.79 | 02-OCT-07:10 | 22.02 | 15.21 |
| November | 0.886690E+10 | 14893.37 | 10-NOV-08:62 | 17.88 | 11.42 | 0.135162E+10 | 2087.74 | 10-NOV-08:09 | 17.88 | 11.42 |
| December | 0.544723E+10 | 9070.23 | 01-DEC-13:30 | 14.70 | 6.53 | 0.122506E+10 | 2059.31 | 12-DEC-15:20 | 10.00 | 3.92 |
| Annual Sum or Average | 0.160070E+12 | 0.130194E+11 | ||||||||
| Minimum of Months | 0.544723E+10 | 9070.23 | 14.70 | 6.53 | 0.304405E+09 | 346.69 | 6.95 | 2.60 | ||
| Maximum of Months | 0.230592E+11 | 32082.52 | 35.92 | 20.17 | 0.148423E+10 | 2255.38 | 35.00 | 20.17 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 13880545.92 | 5263.24 | 27-JAN-07:01 | -4.3 |
| February | 11461333.47 | 5361.58 | 03-FEB-07:01 | -5.1 |
| March | 7647655.57 | 5378.58 | 02-MAR-07:01 | -1.6 |
| April | 637066.54 | 4577.03 | 12-APR-07:01 | 7.35 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 2040528.47 | 5118.15 | 28-NOV-07:01 | 0.87 |
| December | 26365654.64 | 5502.11 | 04-DEC-07:01 | -0.5 |
| Annual Sum or Average | 62032784.61 | |||
| Minimum of Months | 0.00 | 0.00 | -5.1 | |
| Maximum of Months | 26365654.64 | 5502.11 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 13175901.79 | 15966.07 | 26-JAN-08:61 | 0.87 |
| February | 7962048.91 | 15651.38 | 10-FEB-08:61 | -2.0 |
| March | 4357086.32 | 15697.54 | 02-MAR-08:61 | -0.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 2773550.57 | 15751.15 | 28-NOV-08:61 | 2.48 |
| December | 27281174.19 | 18036.09 | 27-DEC-07:01 | -4.3 |
| Annual Sum or Average | 55549761.80 | |||
| Minimum of Months | 0.00 | 0.00 | -4.3 | |
| Maximum of Months | 27281174.19 | 18036.09 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 9370151.72 | 4599.48 | 18-JAN-08:61 | 5.28 |
| February | 3588552.74 | 4535.79 | 02-FEB-08:61 | -1.7 |
| March | 1160691.52 | 4511.31 | 02-MAR-08:61 | -0.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 1283826.23 | 4538.55 | 28-NOV-08:61 | 2.48 |
| December | 32709879.12 | 4862.07 | 04-DEC-07:01 | -0.5 |
| Annual Sum or Average | 48113101.33 | |||
| Minimum of Months | 0.00 | 0.00 | -1.7 | |
| Maximum of Months | 32709879.12 | 4862.07 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 58463166.73 | 5695.97 | 09-JAN-07:11 | 4.07 |
| February | 37338707.13 | 5744.37 | 03-FEB-07:01 | -5.1 |
| March | 15585424.65 | 5642.46 | 02-MAR-07:01 | -1.6 |
| April | 887798.92 | 4627.49 | 12-APR-07:01 | 7.35 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 9594015.15 | 5398.57 | 28-NOV-07:01 | 0.87 |
| December | 80069881.99 | 5894.99 | 27-DEC-06:01 | -3.5 |
| Annual Sum or Average | 0.201939E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -5.1 | |
| Maximum of Months | 80069881.99 | 5894.99 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 51164347.57 | 18487.14 | 30-JAN-07:01 | -1.0 |
| February | 29354776.72 | 17374.82 | 03-FEB-07:01 | -5.1 |
| March | 14698405.73 | 16711.77 | 02-MAR-07:01 | -1.6 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 11795587.93 | 15685.75 | 28-NOV-08:61 | 2.48 |
| December | 87688164.66 | 18667.70 | 04-DEC-07:01 | -0.5 |
| Annual Sum or Average | 0.194701E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -5.1 | |
| Maximum of Months | 87688164.66 | 18667.70 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 13807692.96 | 5214.34 | 27-JAN-07:01 | -4.3 |
| February | 11338571.51 | 5305.12 | 03-FEB-07:01 | -5.1 |
| March | 7517435.02 | 5326.59 | 02-MAR-07:01 | -1.6 |
| April | 620295.84 | 4537.59 | 12-APR-07:01 | 7.35 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 2307028.84 | 5103.60 | 28-NOV-07:01 | 0.87 |
| December | 27900810.70 | 5464.12 | 04-DEC-07:01 | -0.5 |
| Annual Sum or Average | 63491834.87 | |||
| Minimum of Months | 0.00 | 0.00 | -5.1 | |
| Maximum of Months | 27900810.70 | 5464.12 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 13571218.25 | 15704.83 | 26-JAN-08:61 | 0.87 |
| February | 7855067.78 | 15369.23 | 10-FEB-08:61 | -2.0 |
| March | 3732660.81 | 15425.81 | 02-MAR-08:61 | -0.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 3355873.54 | 15626.44 | 28-NOV-08:61 | 2.48 |
| December | 28286306.70 | 17724.54 | 27-DEC-07:01 | -4.3 |
| Annual Sum or Average | 56801127.08 | |||
| Minimum of Months | 0.00 | 0.00 | -4.3 | |
| Maximum of Months | 28286306.70 | 17724.54 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 9663872.25 | 4583.41 | 18-JAN-08:61 | 5.28 |
| February | 3542147.50 | 4523.39 | 02-FEB-08:61 | -1.7 |
| March | 1135689.49 | 4493.30 | 02-MAR-08:61 | -0.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 1320173.26 | 4540.51 | 28-NOV-08:61 | 2.48 |
| December | 34247063.21 | 4855.93 | 04-DEC-07:01 | -0.5 |
| Annual Sum or Average | 49908945.70 | |||
| Minimum of Months | 0.00 | 0.00 | -1.7 | |
| Maximum of Months | 34247063.21 | 4855.93 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 59186625.44 | 5704.29 | 09-JAN-07:11 | 4.07 |
| February | 37505239.21 | 5750.23 | 03-FEB-07:01 | -5.1 |
| March | 15584169.99 | 5646.14 | 02-MAR-07:01 | -1.6 |
| April | 888898.12 | 4630.34 | 12-APR-07:01 | 7.35 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 9723167.85 | 5405.99 | 28-NOV-07:01 | 0.87 |
| December | 80915321.93 | 5902.52 | 27-DEC-06:01 | -3.5 |
| Annual Sum or Average | 0.203803E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -5.1 | |
| Maximum of Months | 80915321.93 | 5902.52 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 52277518.42 | 18524.92 | 30-JAN-07:01 | -1.0 |
| February | 29586646.97 | 17398.80 | 03-FEB-07:01 | -5.1 |
| March | 14710237.13 | 16726.41 | 02-MAR-07:01 | -1.6 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 11950675.92 | 15698.12 | 28-NOV-08:61 | 2.48 |
| December | 88793470.40 | 18690.32 | 04-DEC-07:01 | -0.5 |
| Annual Sum or Average | 0.197319E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -5.1 | |
| Maximum of Months | 88793470.40 | 18690.32 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 12749784.28 | 5196.88 | 27-JAN-07:01 | -4.3 |
| February | 10650200.80 | 5291.76 | 03-FEB-07:01 | -5.1 |
| March | 7208530.09 | 5314.40 | 02-MAR-07:01 | -1.6 |
| April | 608338.93 | 4535.54 | 12-APR-07:01 | 7.35 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 2127973.24 | 5091.46 | 28-NOV-07:01 | 0.87 |
| December | 26292999.10 | 5467.61 | 04-DEC-07:01 | -0.5 |
| Annual Sum or Average | 59637826.45 | |||
| Minimum of Months | 0.00 | 0.00 | -5.1 | |
| Maximum of Months | 26292999.10 | 5467.61 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 12500940.81 | 15739.17 | 18-JAN-08:61 | 5.28 |
| February | 7254056.50 | 15416.36 | 02-FEB-08:61 | -1.7 |
| March | 3463598.34 | 15484.64 | 02-MAR-08:61 | -0.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 2886110.29 | 15599.99 | 28-NOV-08:61 | 2.48 |
| December | 25619454.05 | 17697.23 | 27-DEC-07:01 | -4.3 |
| Annual Sum or Average | 51724159.99 | |||
| Minimum of Months | 0.00 | 0.00 | -4.3 | |
| Maximum of Months | 25619454.05 | 17697.23 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 7968214.44 | 4552.63 | 10-JAN-08:61 | 2.48 |
| February | 2805992.93 | 4513.90 | 03-FEB-08:61 | -2.0 |
| March | 802604.89 | 4461.50 | 02-MAR-08:61 | -0.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 911659.88 | 4515.51 | 28-NOV-08:61 | 2.48 |
| December | 25783674.03 | 4817.25 | 04-DEC-07:01 | -0.5 |
| Annual Sum or Average | 38272146.17 | |||
| Minimum of Months | 0.00 | 0.00 | -2.0 | |
| Maximum of Months | 25783674.03 | 4817.25 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 58000972.47 | 5734.27 | 09-JAN-07:11 | 4.07 |
| February | 36735403.44 | 5783.26 | 03-FEB-07:01 | -5.1 |
| March | 15249826.26 | 5673.26 | 02-MAR-07:01 | -1.6 |
| April | 870259.61 | 4653.32 | 12-APR-07:01 | 7.35 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 9469062.79 | 5433.71 | 28-NOV-07:01 | 0.87 |
| December | 78792867.19 | 5932.36 | 27-DEC-06:01 | -3.5 |
| Annual Sum or Average | 0.199118E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -5.1 | |
| Maximum of Months | 78792867.19 | 5932.36 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 35308706.12 | 12532.52 | 30-JAN-07:01 | -1.0 |
| February | 19962450.53 | 11786.53 | 03-FEB-07:01 | -5.1 |
| March | 9915360.27 | 11327.90 | 02-MAR-07:01 | -1.6 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 8121503.85 | 10627.60 | 28-NOV-08:61 | 2.48 |
| December | 58917866.29 | 12625.63 | 04-DEC-07:01 | -0.5 |
| Annual Sum or Average | 0.132226E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -5.1 | |
| Maximum of Months | 58917866.29 | 12625.63 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 7612480.78 | 5865.57 | 30-JAN-07:01 | -1.0 |
| February | 3836544.54 | 5189.08 | 10-FEB-08:61 | -2.0 |
| March | 1311246.37 | 5108.62 | 02-MAR-08:61 | -0.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 996565.61 | 5192.92 | 28-NOV-08:61 | 2.48 |
| December | 12670955.70 | 5992.05 | 04-DEC-07:01 | -0.5 |
| Annual Sum or Average | 26427793.00 | |||
| Minimum of Months | 0.00 | 0.00 | -2.0 | |
| Maximum of Months | 12670955.70 | 5992.05 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 26008748.32 | 10980.03 | 30-JAN-07:01 | -1.0 |
| February | 7279538.54 | 10559.40 | 01-FEB-08:61 | -0.7 |
| March | 601852.90 | 10030.88 | 02-MAR-08:61 | -0.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 1612023.03 | 10301.57 | 28-NOV-08:61 | 2.48 |
| December | 83952329.77 | 11229.72 | 29-DEC-07:01 | -0.6 |
| Annual Sum or Average | 0.119454E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 83952329.77 | 11229.72 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.250437E+10 | 12332.13 | 27-JAN-07:10 | -4.3 |
| February | 0.186119E+10 | 12606.76 | 03-FEB-07:10 | -5.1 |
| March | 0.155106E+10 | 11593.54 | 02-MAR-07:10 | -1.6 |
| April | 0.554758E+09 | 9833.37 | 12-APR-06:10 | 3.87 |
| May | 0.147518E+09 | 8008.99 | 02-MAY-06:06 | 9.87 |
| June | 5122860.50 | 5461.20 | 29-JUN-07:02 | 17.88 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 13059096.99 | 5577.51 | 17-AUG-07:03 | 17.88 |
| September | 99028832.09 | 7120.39 | 25-SEP-06:17 | 11.10 |
| October | 0.452228E+09 | 8896.65 | 25-OCT-06:10 | 6.88 |
| November | 0.132101E+10 | 10877.50 | 28-NOV-07:10 | 0.87 |
| December | 0.288097E+10 | 12651.54 | 27-DEC-07:10 | -4.3 |
| Annual Sum or Average | 0.113903E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -5.1 | |
| Maximum of Months | 0.288097E+10 | 12651.54 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
| March | 0.00 | 0.00 | 01-MAR-00:05 | 7.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 6.42 | |
| Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
| March | 0.00 | 0.00 | 01-MAR-00:05 | 7.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 8.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 6.42 | |
| Maximum of Months | 0.00 | 0.00 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 10207395.07 | 13172.43 | 09-JAN-08:61 | 4.50 |
| February | 3826252.87 | 13174.95 | 03-FEB-08:61 | -2.0 |
| March | 1265999.94 | 13025.75 | 02-MAR-08:61 | -0.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 526083.49 | 8768.06 | 28-NOV-08:61 | 2.48 |
| December | 30259821.81 | 14515.83 | 27-DEC-07:01 | -4.3 |
| Annual Sum or Average | 46085553.19 | |||
| Minimum of Months | 0.00 | 0.00 | -4.3 | |
| Maximum of Months | 30259821.81 | 14515.83 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 84011.00 | 420.06 | 30-JAN-06:57 | -1.1 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 6.42 |
| March | 0.00 | 0.00 | 01-MAR-00:05 | 7.32 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 10.60 |
| December | 25212581.14 | 10934.06 | 28-DEC-06:50 | -3.4 |
| Annual Sum or Average | 25296592.14 | |||
| Minimum of Months | 0.00 | 0.00 | -3.4 | |
| Maximum of Months | 25212581.14 | 10934.06 | 27.63 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 2369861.16 | 7469.84 | 05-JAN-06:02 | -1.6 |
| February | 2792220.39 | 5889.76 | 21-FEB-06:53 | 4.40 |
| March | 2654551.97 | 10829.07 | 20-MAR-05:54 | 8.30 |
| April | 8097221.86 | 11960.70 | 03-APR-05:57 | 18.90 |
| May | 7348770.17 | 13931.38 | 11-MAY-05:37 | 19.60 |
| June | 1832553.65 | 4331.11 | 01-JUN-05:40 | 19.07 |
| July | 512595.13 | 1315.87 | 24-JUL-06:02 | 22.38 |
| August | 2017634.41 | 5372.72 | 23-AUG-05:37 | 20.00 |
| September | 247662.63 | 2005.96 | 15-SEP-06:01 | 17.38 |
| October | 681856.98 | 3587.70 | 30-OCT-05:34 | 12.40 |
| November | 2787397.47 | 7938.96 | 09-NOV-06:34 | 13.70 |
| December | 1607765.72 | 3890.10 | 15-DEC-07:02 | 8.27 |
| Annual Sum or Average | 32950091.54 | |||
| Minimum of Months | 247662.63 | 1315.87 | -1.6 | |
| Maximum of Months | 8097221.86 | 13931.38 | 22.38 |
Report: ZoneHeatingSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.389699E+09 | 52650.29 | 09-JAN-06:01 | 2.98 |
| February | 0.253181E+09 | 51489.93 | 03-FEB-07:01 | -5.1 |
| March | 0.180569E+09 | 35171.41 | 02-MAR-06:01 | -3.5 |
| April | 23286630.63 | 37514.15 | 21-APR-05:03 | 15.10 |
| May | 23402820.24 | 28049.67 | 16-MAY-06:03 | 21.38 |
| June | 12110501.65 | 16316.59 | 05-JUN-06:00 | 22.80 |
| July | 14466585.27 | 15802.00 | 11-JUL-05:50 | 21.70 |
| August | 6174816.45 | 9639.63 | 23-AUG-05:44 | 20.00 |
| September | 3526390.80 | 7579.21 | 13-SEP-05:50 | 22.38 |
| October | 3350649.11 | 5431.63 | 31-OCT-06:02 | 12.85 |
| November | 0.139097E+09 | 30642.54 | 28-NOV-06:01 | 1.02 |
| December | 0.415715E+09 | 50894.60 | 26-DEC-06:01 | -0.6 |
| Annual Sum or Average | 0.146458E+10 | |||
| Minimum of Months | 3350649.11 | 5431.63 | -5.1 | |
| Maximum of Months | 0.415715E+09 | 52650.29 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 12509590.60 | 13277.81 | 30-JAN-07:01 | -1.0 |
| February | 3253574.69 | 12094.50 | 03-FEB-08:61 | -2.0 |
| March | 700407.79 | 11673.46 | 02-MAR-08:61 | -0.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 11.18 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 20.40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 25.03 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 27.63 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 27.32 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 22.63 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 16.02 |
| November | 460776.72 | 7679.61 | 28-NOV-08:61 | 2.48 |
| December | 25188314.22 | 13665.24 | 27-DEC-07:01 | -4.3 |
| Annual Sum or Average | 42112664.02 | |||
| Minimum of Months | 0.00 | 0.00 | -4.3 | |
| Maximum of Months | 25188314.22 | 13665.24 | 27.63 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.130469E+10 | 947.12 | 02-JAN-07:10 | 0.892986E+09 | 678.98 | 02-JAN-08:09 |
| February | 0.117967E+10 | 947.12 | 01-FEB-07:10 | 0.807077E+09 | 678.98 | 01-FEB-08:09 |
| March | 0.138135E+10 | 947.12 | 01-MAR-07:10 | 0.924571E+09 | 678.98 | 01-MAR-08:09 |
| April | 0.125024E+10 | 947.12 | 03-APR-06:10 | 0.859085E+09 | 678.98 | 03-APR-07:10 |
| May | 0.134302E+10 | 947.12 | 01-MAY-06:10 | 0.908779E+09 | 678.98 | 01-MAY-07:10 |
| June | 0.132690E+10 | 947.12 | 01-JUN-06:10 | 0.890455E+09 | 678.98 | 01-JUN-07:10 |
| July | 0.793150E+09 | 526.18 | 03-JUL-07:10 | 0.543864E+09 | 357.36 | 03-JUL-07:10 |
| August | 0.837162E+09 | 526.18 | 01-AUG-07:10 | 0.565300E+09 | 357.36 | 01-AUG-07:10 |
| September | 0.122658E+10 | 947.12 | 05-SEP-06:10 | 0.845480E+09 | 678.98 | 05-SEP-07:10 |
| October | 0.130469E+10 | 947.12 | 02-OCT-06:10 | 0.892986E+09 | 678.98 | 02-OCT-07:10 |
| November | 0.128857E+10 | 947.12 | 01-NOV-06:10 | 0.874878E+09 | 678.98 | 01-NOV-07:10 |
| December | 0.126636E+10 | 947.12 | 01-DEC-07:10 | 0.877193E+09 | 678.98 | 01-DEC-08:09 |
| Annual Sum or Average | 0.145024E+11 | 0.988265E+10 | ||||
| Minimum of Months | 0.793150E+09 | 526.18 | 0.543864E+09 | 357.36 | ||
| Maximum of Months | 0.138135E+10 | 947.12 | 0.924571E+09 | 678.98 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.130469E+10 | 947.12 | 02-JAN-07:10 | 0.892986E+09 | 678.98 | 02-JAN-08:09 |
| February | 0.117967E+10 | 947.12 | 01-FEB-07:10 | 0.807077E+09 | 678.98 | 01-FEB-08:09 |
| March | 0.138135E+10 | 947.12 | 01-MAR-07:10 | 0.924571E+09 | 678.98 | 01-MAR-08:09 |
| April | 0.125024E+10 | 947.12 | 03-APR-06:10 | 0.859085E+09 | 678.98 | 03-APR-07:10 |
| May | 0.134302E+10 | 947.12 | 01-MAY-06:10 | 0.908779E+09 | 678.98 | 01-MAY-07:10 |
| June | 0.132690E+10 | 947.12 | 01-JUN-06:10 | 0.890455E+09 | 678.98 | 01-JUN-07:10 |
| July | 0.793150E+09 | 526.18 | 03-JUL-07:10 | 0.543864E+09 | 357.36 | 03-JUL-07:10 |
| August | 0.837162E+09 | 526.18 | 01-AUG-07:10 | 0.565300E+09 | 357.36 | 01-AUG-07:10 |
| September | 0.122658E+10 | 947.12 | 05-SEP-06:10 | 0.845480E+09 | 678.98 | 05-SEP-07:10 |
| October | 0.130469E+10 | 947.12 | 02-OCT-06:10 | 0.892986E+09 | 678.98 | 02-OCT-07:10 |
| November | 0.128857E+10 | 947.12 | 01-NOV-06:10 | 0.874878E+09 | 678.98 | 01-NOV-07:10 |
| December | 0.126636E+10 | 947.12 | 01-DEC-07:10 | 0.877193E+09 | 678.98 | 01-DEC-08:09 |
| Annual Sum or Average | 0.145024E+11 | 0.988265E+10 | ||||
| Minimum of Months | 0.793150E+09 | 526.18 | 0.543864E+09 | 357.36 | ||
| Maximum of Months | 0.138135E+10 | 947.12 | 0.924571E+09 | 678.98 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.130469E+10 | 947.12 | 02-JAN-07:10 | 0.892986E+09 | 678.98 | 02-JAN-08:09 |
| February | 0.117967E+10 | 947.12 | 01-FEB-07:10 | 0.807077E+09 | 678.98 | 01-FEB-08:09 |
| March | 0.138135E+10 | 947.12 | 01-MAR-07:10 | 0.924571E+09 | 678.98 | 01-MAR-08:09 |
| April | 0.125024E+10 | 947.12 | 03-APR-06:10 | 0.859085E+09 | 678.98 | 03-APR-07:10 |
| May | 0.134302E+10 | 947.12 | 01-MAY-06:10 | 0.908779E+09 | 678.98 | 01-MAY-07:10 |
| June | 0.132690E+10 | 947.12 | 01-JUN-06:10 | 0.890455E+09 | 678.98 | 01-JUN-07:10 |
| July | 0.793150E+09 | 526.18 | 03-JUL-07:10 | 0.543864E+09 | 357.36 | 03-JUL-07:10 |
| August | 0.837162E+09 | 526.18 | 01-AUG-07:10 | 0.565300E+09 | 357.36 | 01-AUG-07:10 |
| September | 0.122658E+10 | 947.12 | 05-SEP-06:10 | 0.845480E+09 | 678.98 | 05-SEP-07:10 |
| October | 0.130469E+10 | 947.12 | 02-OCT-06:10 | 0.892986E+09 | 678.98 | 02-OCT-07:10 |
| November | 0.128857E+10 | 947.12 | 01-NOV-06:10 | 0.874878E+09 | 678.98 | 01-NOV-07:10 |
| December | 0.126636E+10 | 947.12 | 01-DEC-07:10 | 0.877193E+09 | 678.98 | 01-DEC-08:09 |
| Annual Sum or Average | 0.145024E+11 | 0.988265E+10 | ||||
| Minimum of Months | 0.793150E+09 | 526.18 | 0.543864E+09 | 357.36 | ||
| Maximum of Months | 0.138135E+10 | 947.12 | 0.924571E+09 | 678.98 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.588512E+10 | 4272.19 | 02-JAN-07:10 | 0.549396E+10 | 4177.31 | 02-JAN-08:09 |
| February | 0.532117E+10 | 4272.19 | 01-FEB-07:10 | 0.496542E+10 | 4177.31 | 01-FEB-08:09 |
| March | 0.623092E+10 | 4272.19 | 01-MAR-07:10 | 0.568828E+10 | 4177.31 | 01-MAR-08:09 |
| April | 0.563950E+10 | 4272.19 | 03-APR-06:10 | 0.528539E+10 | 4177.31 | 03-APR-07:10 |
| May | 0.605802E+10 | 4272.19 | 01-MAY-06:10 | 0.559112E+10 | 4177.31 | 01-MAY-07:10 |
| June | 0.598530E+10 | 4272.19 | 01-JUN-06:10 | 0.547839E+10 | 4177.31 | 01-JUN-07:10 |
| July | 0.357769E+10 | 2373.44 | 03-JUL-07:10 | 0.334604E+10 | 2198.59 | 03-JUL-07:10 |
| August | 0.377621E+10 | 2373.44 | 01-AUG-07:10 | 0.347792E+10 | 2198.59 | 01-AUG-07:10 |
| September | 0.553277E+10 | 4272.19 | 05-SEP-06:10 | 0.520168E+10 | 4177.31 | 05-SEP-07:10 |
| October | 0.588512E+10 | 4272.19 | 02-OCT-06:10 | 0.549396E+10 | 4177.31 | 02-OCT-07:10 |
| November | 0.581240E+10 | 4272.19 | 01-NOV-06:10 | 0.538255E+10 | 4177.31 | 01-NOV-07:10 |
| December | 0.571221E+10 | 4272.19 | 01-DEC-07:10 | 0.539679E+10 | 4177.31 | 01-DEC-08:09 |
| Annual Sum or Average | 0.654164E+11 | 0.608015E+11 | ||||
| Minimum of Months | 0.357769E+10 | 2373.44 | 0.334604E+10 | 2198.59 | ||
| Maximum of Months | 0.623092E+10 | 4272.19 | 0.568828E+10 | 4177.31 |
Report: ZoneElectricSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.302663E+10 | 2197.13 | 02-JAN-07:10 | 0.376728E+10 | 2864.44 | 02-JAN-08:09 |
| February | 0.273660E+10 | 2197.13 | 01-FEB-07:10 | 0.340486E+10 | 2864.44 | 01-FEB-08:09 |
| March | 0.320447E+10 | 2197.13 | 01-MAR-07:10 | 0.390054E+10 | 2864.44 | 01-MAR-08:09 |
| April | 0.290031E+10 | 2197.13 | 03-APR-06:10 | 0.362427E+10 | 2864.44 | 03-APR-07:10 |
| May | 0.311555E+10 | 2197.13 | 01-MAY-06:10 | 0.383391E+10 | 2864.44 | 01-MAY-07:10 |
| June | 0.307815E+10 | 2197.13 | 01-JUN-06:10 | 0.375661E+10 | 2864.44 | 01-JUN-07:10 |
| July | 0.183996E+10 | 1220.63 | 03-JUL-07:10 | 0.229443E+10 | 1507.60 | 03-JUL-07:10 |
| August | 0.194205E+10 | 1220.63 | 01-AUG-07:10 | 0.238486E+10 | 1507.60 | 01-AUG-07:10 |
| September | 0.284543E+10 | 2197.13 | 05-SEP-06:10 | 0.356687E+10 | 2864.44 | 05-SEP-07:10 |
| October | 0.302663E+10 | 2197.13 | 02-OCT-06:10 | 0.376728E+10 | 2864.44 | 02-OCT-07:10 |
| November | 0.298923E+10 | 2197.13 | 01-NOV-06:10 | 0.369089E+10 | 2864.44 | 01-NOV-07:10 |
| December | 0.293771E+10 | 2197.13 | 01-DEC-07:10 | 0.370066E+10 | 2864.44 | 01-DEC-08:09 |
| Annual Sum or Average | 0.336427E+11 | 0.416925E+11 | ||||
| Minimum of Months | 0.183996E+10 | 1220.63 | 0.229443E+10 | 1507.60 | ||
| Maximum of Months | 0.320447E+10 | 2197.13 | 0.390054E+10 | 2864.44 |
Report: ZoneElectricSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.371022E+10 | 2693.36 | 02-JAN-07:10 | 0.253943E+10 | 1930.85 | 02-JAN-08:09 |
| February | 0.335468E+10 | 2693.36 | 01-FEB-07:10 | 0.229513E+10 | 1930.85 | 01-FEB-08:09 |
| March | 0.392822E+10 | 2693.36 | 01-MAR-07:10 | 0.262925E+10 | 1930.85 | 01-MAR-08:09 |
| April | 0.355537E+10 | 2693.36 | 03-APR-06:10 | 0.244302E+10 | 1930.85 | 03-APR-07:10 |
| May | 0.381922E+10 | 2693.36 | 01-MAY-06:10 | 0.258434E+10 | 1930.85 | 01-MAY-07:10 |
| June | 0.377338E+10 | 2693.36 | 01-JUN-06:10 | 0.253223E+10 | 1930.85 | 01-JUN-07:10 |
| July | 0.225552E+10 | 1496.31 | 03-JUL-07:10 | 0.154661E+10 | 1016.24 | 03-JUL-07:10 |
| August | 0.238068E+10 | 1496.31 | 01-AUG-07:10 | 0.160757E+10 | 1016.24 | 01-AUG-07:10 |
| September | 0.348808E+10 | 2693.36 | 05-SEP-06:10 | 0.240433E+10 | 1930.85 | 05-SEP-07:10 |
| October | 0.371022E+10 | 2693.36 | 02-OCT-06:10 | 0.253943E+10 | 1930.85 | 02-OCT-07:10 |
| November | 0.366437E+10 | 2693.36 | 01-NOV-06:10 | 0.248793E+10 | 1930.85 | 01-NOV-07:10 |
| December | 0.360121E+10 | 2693.36 | 01-DEC-07:10 | 0.249452E+10 | 1930.85 | 01-DEC-08:09 |
| Annual Sum or Average | 0.412412E+11 | 0.281038E+11 | ||||
| Minimum of Months | 0.225552E+10 | 1496.31 | 0.154661E+10 | 1016.24 | ||
| Maximum of Months | 0.392822E+10 | 2693.36 | 0.262925E+10 | 1930.85 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.296658E+10 | 2153.53 | 02-JAN-07:10 | 0.795316E+09 | 604.72 | 02-JAN-08:09 |
| February | 0.268230E+10 | 2153.53 | 01-FEB-07:10 | 0.718803E+09 | 604.72 | 01-FEB-08:09 |
| March | 0.314089E+10 | 2153.53 | 01-MAR-07:10 | 0.823446E+09 | 604.72 | 01-MAR-08:09 |
| April | 0.284277E+10 | 2153.53 | 03-APR-06:10 | 0.765123E+09 | 604.72 | 03-APR-07:10 |
| May | 0.305373E+10 | 2153.53 | 01-MAY-06:10 | 0.809381E+09 | 604.72 | 01-MAY-07:10 |
| June | 0.301708E+10 | 2153.53 | 01-JUN-06:10 | 0.793062E+09 | 604.72 | 01-JUN-07:10 |
| July | 0.180345E+10 | 1196.41 | 03-JUL-07:10 | 0.484379E+09 | 318.27 | 03-JUL-07:10 |
| August | 0.190352E+10 | 1196.41 | 01-AUG-07:10 | 0.503470E+09 | 318.27 | 01-AUG-07:10 |
| September | 0.278897E+10 | 2153.53 | 05-SEP-06:10 | 0.753006E+09 | 604.72 | 05-SEP-07:10 |
| October | 0.296658E+10 | 2153.53 | 02-OCT-06:10 | 0.795316E+09 | 604.72 | 02-OCT-07:10 |
| November | 0.292992E+10 | 2153.53 | 01-NOV-06:10 | 0.779188E+09 | 604.72 | 01-NOV-07:10 |
| December | 0.287942E+10 | 2153.53 | 01-DEC-07:10 | 0.781250E+09 | 604.72 | 01-DEC-08:09 |
| Annual Sum or Average | 0.329752E+11 | 0.880174E+10 | ||||
| Minimum of Months | 0.180345E+10 | 1196.41 | 0.484379E+09 | 318.27 | ||
| Maximum of Months | 0.314089E+10 | 2153.53 | 0.823446E+09 | 604.72 |
Report: ZoneElectricSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.504438E+10 | 3661.88 | 02-JAN-07:10 | 0.293011E+10 | 2227.90 | 02-JAN-08:09 |
| February | 0.456100E+10 | 3661.88 | 01-FEB-07:10 | 0.264822E+10 | 2227.90 | 01-FEB-08:09 |
| March | 0.534079E+10 | 3661.88 | 01-MAR-07:10 | 0.303375E+10 | 2227.90 | 01-MAR-08:09 |
| April | 0.483386E+10 | 3661.88 | 03-APR-06:10 | 0.281887E+10 | 2227.90 | 03-APR-07:10 |
| May | 0.519259E+10 | 3661.88 | 01-MAY-06:10 | 0.298193E+10 | 2227.90 | 01-MAY-07:10 |
| June | 0.513026E+10 | 3661.88 | 01-JUN-06:10 | 0.292181E+10 | 2227.90 | 01-JUN-07:10 |
| July | 0.306659E+10 | 2034.38 | 03-JUL-07:10 | 0.178455E+10 | 1172.58 | 03-JUL-07:10 |
| August | 0.323676E+10 | 2034.38 | 01-AUG-07:10 | 0.185489E+10 | 1172.58 | 01-AUG-07:10 |
| September | 0.474238E+10 | 3661.88 | 05-SEP-06:10 | 0.277423E+10 | 2227.90 | 05-SEP-07:10 |
| October | 0.504438E+10 | 3661.88 | 02-OCT-06:10 | 0.293011E+10 | 2227.90 | 02-OCT-07:10 |
| November | 0.498206E+10 | 3661.88 | 01-NOV-06:10 | 0.287069E+10 | 2227.90 | 01-NOV-07:10 |
| December | 0.489618E+10 | 3661.88 | 01-DEC-07:10 | 0.287829E+10 | 2227.90 | 01-DEC-08:09 |
| Annual Sum or Average | 0.560712E+11 | 0.324275E+11 | ||||
| Minimum of Months | 0.306659E+10 | 2034.38 | 0.178455E+10 | 1172.58 | ||
| Maximum of Months | 0.534079E+10 | 3661.88 | 0.303375E+10 | 2227.90 |
Report: ZoneElectricSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.228198E+10 | 1656.56 | 02-JAN-07:10 | 0.883684E+09 | 671.91 | 02-JAN-08:09 |
| February | 0.206331E+10 | 1656.56 | 01-FEB-07:10 | 0.798670E+09 | 671.91 | 01-FEB-08:09 |
| March | 0.241607E+10 | 1656.56 | 01-MAR-07:10 | 0.914940E+09 | 671.91 | 01-MAR-08:09 |
| April | 0.218674E+10 | 1656.56 | 03-APR-06:10 | 0.850137E+09 | 671.91 | 03-APR-07:10 |
| May | 0.234903E+10 | 1656.56 | 01-MAY-06:10 | 0.899312E+09 | 671.91 | 01-MAY-07:10 |
| June | 0.232083E+10 | 1656.56 | 01-JUN-06:10 | 0.881180E+09 | 671.91 | 01-JUN-07:10 |
| July | 0.138727E+10 | 920.31 | 03-JUL-07:10 | 0.538198E+09 | 353.64 | 03-JUL-07:10 |
| August | 0.146425E+10 | 920.31 | 01-AUG-07:10 | 0.559411E+09 | 353.64 | 01-AUG-07:10 |
| September | 0.214536E+10 | 1656.56 | 05-SEP-06:10 | 0.836673E+09 | 671.91 | 05-SEP-07:10 |
| October | 0.228198E+10 | 1656.56 | 02-OCT-06:10 | 0.883684E+09 | 671.91 | 02-OCT-07:10 |
| November | 0.225379E+10 | 1656.56 | 01-NOV-06:10 | 0.865765E+09 | 671.91 | 01-NOV-07:10 |
| December | 0.221494E+10 | 1656.56 | 01-DEC-07:10 | 0.868056E+09 | 671.91 | 01-DEC-08:09 |
| Annual Sum or Average | 0.253655E+11 | 0.977971E+10 | ||||
| Minimum of Months | 0.138727E+10 | 920.31 | 0.538198E+09 | 353.64 | ||
| Maximum of Months | 0.241607E+10 | 1656.56 | 0.914940E+09 | 671.91 |
Report: ZoneElectricSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.647363E+10 | 4699.41 | 02-JAN-07:10 | 0.553791E+10 | 4210.73 | 02-JAN-08:09 |
| February | 0.585328E+10 | 4699.41 | 01-FEB-07:10 | 0.500514E+10 | 4210.73 | 01-FEB-08:09 |
| March | 0.685401E+10 | 4699.41 | 01-MAR-07:10 | 0.573379E+10 | 4210.73 | 01-MAR-08:09 |
| April | 0.620345E+10 | 4699.41 | 03-APR-06:10 | 0.532767E+10 | 4210.73 | 03-APR-07:10 |
| May | 0.666382E+10 | 4699.41 | 01-MAY-06:10 | 0.563585E+10 | 4210.73 | 01-MAY-07:10 |
| June | 0.658383E+10 | 4699.41 | 01-JUN-06:10 | 0.552221E+10 | 4210.73 | 01-JUN-07:10 |
| July | 0.393546E+10 | 2610.78 | 03-JUL-07:10 | 0.337280E+10 | 2216.18 | 03-JUL-07:10 |
| August | 0.415384E+10 | 2610.78 | 01-AUG-07:10 | 0.350574E+10 | 2216.18 | 01-AUG-07:10 |
| September | 0.608605E+10 | 4699.41 | 05-SEP-06:10 | 0.524330E+10 | 4210.73 | 05-SEP-07:10 |
| October | 0.647363E+10 | 4699.41 | 02-OCT-06:10 | 0.553791E+10 | 4210.73 | 02-OCT-07:10 |
| November | 0.639364E+10 | 4699.41 | 01-NOV-06:10 | 0.542561E+10 | 4210.73 | 01-NOV-07:10 |
| December | 0.628344E+10 | 4699.41 | 01-DEC-07:10 | 0.543997E+10 | 4210.73 | 01-DEC-08:09 |
| Annual Sum or Average | 0.719581E+11 | 0.612879E+11 | ||||
| Minimum of Months | 0.393546E+10 | 2610.78 | 0.337280E+10 | 2216.18 | ||
| Maximum of Months | 0.685401E+10 | 4699.41 | 0.573379E+10 | 4210.73 |
Report: ZoneElectricSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.590754E+10 | 4288.47 | 02-JAN-07:10 | 0.207549E+10 | 1578.10 | 02-JAN-08:09 |
| February | 0.534144E+10 | 4288.47 | 01-FEB-07:10 | 0.187582E+10 | 1578.10 | 01-FEB-08:09 |
| March | 0.625466E+10 | 4288.47 | 01-MAR-07:10 | 0.214891E+10 | 1578.10 | 01-MAR-08:09 |
| April | 0.566098E+10 | 4288.47 | 03-APR-06:10 | 0.199670E+10 | 1578.10 | 03-APR-07:10 |
| May | 0.608110E+10 | 4288.47 | 01-MAY-06:10 | 0.211220E+10 | 1578.10 | 01-MAY-07:10 |
| June | 0.600810E+10 | 4288.47 | 01-JUN-06:10 | 0.206961E+10 | 1578.10 | 01-JUN-07:10 |
| July | 0.359132E+10 | 2382.48 | 03-JUL-07:10 | 0.126406E+10 | 830.58 | 03-JUL-07:10 |
| August | 0.379060E+10 | 2382.48 | 01-AUG-07:10 | 0.131388E+10 | 830.58 | 01-AUG-07:10 |
| September | 0.555385E+10 | 4288.47 | 05-SEP-06:10 | 0.196508E+10 | 1578.10 | 05-SEP-07:10 |
| October | 0.590754E+10 | 4288.47 | 02-OCT-06:10 | 0.207549E+10 | 1578.10 | 02-OCT-07:10 |
| November | 0.583454E+10 | 4288.47 | 01-NOV-06:10 | 0.203341E+10 | 1578.10 | 01-NOV-07:10 |
| December | 0.573398E+10 | 4288.47 | 01-DEC-07:10 | 0.203879E+10 | 1578.10 | 01-DEC-08:09 |
| Annual Sum or Average | 0.656656E+11 | 0.229695E+11 | ||||
| Minimum of Months | 0.359132E+10 | 2382.48 | 0.126406E+10 | 830.58 | ||
| Maximum of Months | 0.625466E+10 | 4288.47 | 0.214891E+10 | 1578.10 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.269034E+10 | 1953.00 | 02-JAN-07:10 | 0.147381E+11 | 9714.90 | 02-JAN-10:09 |
| February | 0.243253E+10 | 1953.00 | 01-FEB-07:10 | 0.133142E+11 | 9714.90 | 01-FEB-10:09 |
| March | 0.284842E+10 | 1953.00 | 01-MAR-07:10 | 0.148878E+11 | 9714.90 | 01-MAR-10:09 |
| April | 0.257806E+10 | 1953.00 | 03-APR-06:10 | 0.142385E+11 | 9714.90 | 03-APR-09:09 |
| May | 0.276938E+10 | 1953.00 | 01-MAY-06:10 | 0.148130E+11 | 9714.90 | 01-MAY-09:09 |
| June | 0.273614E+10 | 1953.00 | 01-JUN-06:10 | 0.143883E+11 | 9714.90 | 01-JUN-09:09 |
| July | 0.163552E+10 | 1085.00 | 03-JUL-07:10 | 0.146632E+11 | 9714.90 | 03-JUL-09:09 |
| August | 0.172627E+10 | 1085.00 | 01-AUG-07:10 | 0.148878E+11 | 9714.90 | 01-AUG-09:09 |
| September | 0.252927E+10 | 1953.00 | 05-SEP-06:10 | 0.142385E+11 | 9714.90 | 01-SEP-09:09 |
| October | 0.269034E+10 | 1953.00 | 02-OCT-06:10 | 0.147381E+11 | 9714.90 | 02-OCT-09:09 |
| November | 0.265710E+10 | 1953.00 | 01-NOV-06:10 | 0.143134E+11 | 9714.90 | 01-NOV-09:09 |
| December | 0.261130E+10 | 1953.00 | 01-DEC-07:10 | 0.146632E+11 | 9714.90 | 01-DEC-10:09 |
| Annual Sum or Average | 0.299046E+11 | 0.173884E+12 | ||||
| Minimum of Months | 0.163552E+10 | 1085.00 | 0.133142E+11 | 9714.90 | ||
| Maximum of Months | 0.284842E+10 | 1953.00 | 0.148878E+11 | 9714.90 |
Report: ZoneElectricSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.378329E+10 | 2746.41 | 02-JAN-07:10 | 0.253516E+10 | 1999.46 | 02-JAN-10:09 |
| February | 0.342075E+10 | 2746.41 | 01-FEB-07:10 | 0.229042E+10 | 1999.46 | 01-FEB-10:09 |
| March | 0.400559E+10 | 2746.41 | 01-MAR-07:10 | 0.257259E+10 | 1999.46 | 01-MAR-10:09 |
| April | 0.362539E+10 | 2746.41 | 03-APR-06:10 | 0.244734E+10 | 1999.46 | 03-APR-09:09 |
| May | 0.389444E+10 | 2746.41 | 01-MAY-06:10 | 0.255387E+10 | 1999.46 | 01-MAY-09:09 |
| June | 0.384769E+10 | 2746.41 | 01-JUN-06:10 | 0.248477E+10 | 1999.46 | 01-JUN-09:09 |
| July | 0.229994E+10 | 1525.78 | 03-JUL-07:10 | 0.251644E+10 | 1999.46 | 03-JUL-09:09 |
| August | 0.242757E+10 | 1525.78 | 01-AUG-07:10 | 0.257259E+10 | 1999.46 | 01-AUG-09:09 |
| September | 0.355678E+10 | 2746.41 | 05-SEP-06:10 | 0.244734E+10 | 1999.46 | 01-SEP-09:09 |
| October | 0.378329E+10 | 2746.41 | 02-OCT-06:10 | 0.253516E+10 | 1999.46 | 02-OCT-09:09 |
| November | 0.373654E+10 | 2746.41 | 01-NOV-06:10 | 0.246606E+10 | 1999.46 | 01-NOV-09:09 |
| December | 0.367214E+10 | 2746.41 | 01-DEC-07:10 | 0.251644E+10 | 1999.46 | 01-DEC-10:09 |
| Annual Sum or Average | 0.420534E+11 | 0.299382E+11 | ||||
| Minimum of Months | 0.229994E+10 | 1525.78 | 0.229042E+10 | 1999.46 | ||
| Maximum of Months | 0.400559E+10 | 2746.41 | 0.257259E+10 | 1999.46 |
Report: ZoneElectricSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.825317E+10 | 5991.24 | 02-JAN-07:10 | 0.695901E+10 | 5291.26 | 02-JAN-08:09 |
| February | 0.746230E+10 | 5991.24 | 01-FEB-07:10 | 0.628953E+10 | 5291.26 | 01-FEB-08:09 |
| March | 0.873812E+10 | 5991.24 | 01-MAR-07:10 | 0.720516E+10 | 5291.26 | 01-MAR-08:09 |
| April | 0.790872E+10 | 5991.24 | 03-APR-06:10 | 0.669483E+10 | 5291.26 | 03-APR-07:10 |
| May | 0.849564E+10 | 5991.24 | 01-MAY-06:10 | 0.708208E+10 | 5291.26 | 01-MAY-07:10 |
| June | 0.839367E+10 | 5991.24 | 01-JUN-06:10 | 0.693929E+10 | 5291.26 | 01-JUN-07:10 |
| July | 0.501728E+10 | 3328.47 | 03-JUL-07:10 | 0.423831E+10 | 2784.88 | 03-JUL-07:10 |
| August | 0.529569E+10 | 3328.47 | 01-AUG-07:10 | 0.440537E+10 | 2784.88 | 01-AUG-07:10 |
| September | 0.775905E+10 | 5991.24 | 05-SEP-06:10 | 0.658880E+10 | 5291.26 | 05-SEP-07:10 |
| October | 0.825317E+10 | 5991.24 | 02-OCT-06:10 | 0.695901E+10 | 5291.26 | 02-OCT-07:10 |
| November | 0.815120E+10 | 5991.24 | 01-NOV-06:10 | 0.681790E+10 | 5291.26 | 01-NOV-07:10 |
| December | 0.801070E+10 | 5991.24 | 01-DEC-07:10 | 0.683594E+10 | 5291.26 | 01-DEC-08:09 |
| Annual Sum or Average | 0.917387E+11 | 0.770152E+11 | ||||
| Minimum of Months | 0.501728E+10 | 3328.47 | 0.423831E+10 | 2784.88 | ||
| Maximum of Months | 0.873812E+10 | 5991.24 | 0.720516E+10 | 5291.26 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253646E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213179E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63149.68 | 0.232268E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15459730.21 | 0.120322E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46934418.13 | 52663155.85 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75563391.85 | 12702384.77 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60438419.90 | 10745405.24 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45229333.95 | 19930949.46 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13828797.79 | 30730155.13 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3740619.35 | 0.119930E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220270E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226548E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261258E+09 | 0.151294E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10745405.24 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75563391.85 | 0.253646E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727815E+09 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612793E+09 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171099.44 | 0.667127E+09 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45008125.89 | 0.337526E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137062E+09 | 0.144732E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215792E+09 | 32591644.36 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185233E+09 | 23708562.55 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137994E+09 | 48520335.40 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41914165.38 | 79051619.23 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11190474.20 | 0.327411E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.619910E+09 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645442E+09 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774365E+09 | 0.426663E+10 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23708562.55 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215792E+09 | 0.727815E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38275247.67 |
| February | 0.708259E+09 | 0.117967E+10 | 0.807077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32430028.30 |
| March | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9453.93 | 35932397.27 |
| April | 0.745536E+09 | 0.125024E+10 | 0.859085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2352493.40 | 19150720.61 |
| May | 0.820090E+09 | 0.134302E+10 | 0.908779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6611937.98 | 8781784.43 |
| June | 0.505804E+09 | 0.132690E+10 | 0.890455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10553208.72 | 2342115.01 |
| July | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8860264.43 | 1602641.15 |
| August | 0.200223E+09 | 0.837162E+09 | 0.565300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6967715.75 | 2807057.17 |
| September | 0.459822E+09 | 0.122658E+10 | 0.845480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2175970.69 | 4524680.35 |
| October | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 641843.52 | 17492647.54 |
| November | 0.782813E+09 | 0.128857E+10 | 0.874878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32812125.80 |
| December | 0.745536E+09 | 0.126636E+10 | 0.877193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33825011.45 |
| Annual Sum or Average | 0.756518E+10 | 0.145024E+11 | 0.988265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38172888.42 | 0.229976E+09 |
| Minimum of Months | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1602641.15 |
| Maximum of Months | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10553208.72 | 38275247.67 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225827E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 138031.93 | 0.189222E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 163591.62 | 0.210279E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18998162.27 | 0.114034E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48062282.51 | 52085743.21 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75388456.40 | 12914112.48 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60912333.89 | 10663018.86 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48005318.08 | 18543704.16 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16530753.70 | 27828979.26 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5378836.56 | 0.108596E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196397E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201749E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273578E+09 | 0.136814E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10663018.86 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75388456.40 | 0.225827E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645902E+09 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 491959.18 | 0.544163E+09 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 479648.83 | 0.606775E+09 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55160761.89 | 0.319984E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140398E+09 | 0.143086E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215551E+09 | 33116737.96 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188579E+09 | 22922514.40 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150593E+09 | 43214735.73 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50505900.29 | 70251506.84 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16775841.76 | 0.294036E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550659E+09 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572764E+09 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818536E+09 | 0.384687E+10 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22922514.40 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215551E+09 | 0.645902E+09 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253365E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213137E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63149.80 | 0.232252E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15579164.85 | 0.120450E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47140329.92 | 52759294.82 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75723605.27 | 12699746.89 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60838636.78 | 10620393.52 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45504549.48 | 19831612.50 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13955516.53 | 30667787.60 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3753416.22 | 0.119864E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220122E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226159E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262558E+09 | 0.151193E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10620393.52 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75723605.27 | 0.253365E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.725623E+09 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612625E+09 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171107.77 | 0.668565E+09 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45340913.53 | 0.338665E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137719E+09 | 0.145357E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216560E+09 | 32581971.39 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187552E+09 | 23098950.12 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139879E+09 | 47892537.81 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42600792.20 | 78602774.75 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11370453.54 | 0.326518E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.618081E+09 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642500E+09 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781192E+09 | 0.426011E+10 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23098950.12 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216560E+09 | 0.725623E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38198580.26 |
| February | 0.708259E+09 | 0.117967E+10 | 0.807077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 | 32409129.85 |
| March | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9453.92 | 35955832.23 |
| April | 0.745536E+09 | 0.125024E+10 | 0.859085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2353605.30 | 19162420.86 |
| May | 0.820090E+09 | 0.134302E+10 | 0.908779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6619731.52 | 8783794.70 |
| June | 0.505804E+09 | 0.132690E+10 | 0.890455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10563279.69 | 2339267.54 |
| July | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8893096.75 | 1584781.49 |
| August | 0.200223E+09 | 0.837162E+09 | 0.565300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6996104.86 | 2789243.41 |
| September | 0.459822E+09 | 0.122658E+10 | 0.845480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2185879.75 | 4512307.58 |
| October | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 644577.24 | 17470439.63 |
| November | 0.782813E+09 | 0.128857E+10 | 0.874878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32761645.01 |
| December | 0.745536E+09 | 0.126636E+10 | 0.877193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33736289.05 |
| Annual Sum or Average | 0.756518E+10 | 0.145024E+11 | 0.988265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38265731.91 | 0.229704E+09 |
| Minimum of Months | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1584781.49 |
| Maximum of Months | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10563279.69 | 38198580.26 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225670E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 138993.73 | 0.189159E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 163012.05 | 0.210318E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18989197.36 | 0.114024E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48065560.42 | 52064539.00 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75407686.18 | 12902493.43 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60941086.69 | 10642899.97 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48034918.78 | 18513588.35 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16535007.83 | 27806221.13 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5384603.32 | 0.108553E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196281E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201581E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273660E+09 | 0.136752E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10642899.97 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75407686.18 | 0.225670E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645427E+09 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 495651.27 | 0.543970E+09 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 478447.82 | 0.606879E+09 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55137504.21 | 0.319966E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140390E+09 | 0.143047E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215586E+09 | 33095653.83 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188655E+09 | 22880291.16 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150709E+09 | 43131254.66 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50530526.45 | 70185957.29 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16794693.41 | 0.293915E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.550328E+09 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572262E+09 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818778E+09 | 0.384509E+10 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22880291.16 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215586E+09 | 0.645427E+09 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254257E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213886E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63149.44 | 0.232973E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15497263.38 | 0.120710E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47039408.04 | 52870091.84 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75632106.00 | 12745781.04 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60595456.95 | 10752675.03 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45309599.31 | 20003370.46 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13906536.08 | 30766785.59 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3743075.29 | 0.120071E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220586E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227114E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261787E+09 | 0.151674E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10752675.03 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75632106.00 | 0.254257E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729543E+09 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615728E+09 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 170459.68 | 0.671336E+09 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44861359.56 | 0.340052E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136852E+09 | 0.146182E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215574E+09 | 32940812.39 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185675E+09 | 23783063.25 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138354E+09 | 48819704.30 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42208221.39 | 79278884.58 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11267111.31 | 0.327847E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.620316E+09 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646990E+09 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774962E+09 | 0.428282E+10 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23783063.25 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215574E+09 | 0.729543E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38667774.61 |
| February | 0.708259E+09 | 0.117967E+10 | 0.807077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32829470.72 |
| March | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9453.81 | 36383385.05 |
| April | 0.745536E+09 | 0.125024E+10 | 0.859085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2297026.23 | 19344188.40 |
| May | 0.820090E+09 | 0.134302E+10 | 0.908779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6539464.71 | 8884161.50 |
| June | 0.505804E+09 | 0.132690E+10 | 0.890455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10478248.35 | 2385736.31 |
| July | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8726797.56 | 1681302.12 |
| August | 0.200223E+09 | 0.837162E+09 | 0.565300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6855186.31 | 2902007.08 |
| September | 0.459822E+09 | 0.122658E+10 | 0.845480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2146237.73 | 4587951.25 |
| October | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 635523.83 | 17617880.92 |
| November | 0.782813E+09 | 0.128857E+10 | 0.874878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33039033.85 |
| December | 0.745536E+09 | 0.126636E+10 | 0.877193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34199558.08 |
| Annual Sum or Average | 0.756518E+10 | 0.145024E+11 | 0.988265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37687938.53 | 0.232522E+09 |
| Minimum of Months | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1681302.12 |
| Maximum of Months | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10478248.35 | 38667774.61 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226432E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 123042.02 | 0.189817E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 152064.69 | 0.211233E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18751060.38 | 0.114232E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47761375.97 | 52126271.14 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75174480.72 | 12949276.69 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60313320.07 | 10890438.61 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47532450.24 | 18775519.68 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16352201.62 | 27938090.27 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5338235.37 | 0.108725E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196541E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202312E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271498E+09 | 0.137197E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10890438.61 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75174480.72 | 0.226432E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.642132E+10 | 0.588512E+10 | 0.549396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427466E+09 |
| February | 0.580977E+10 | 0.532117E+10 | 0.496542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 286575.07 | 0.360203E+09 |
| March | 0.703288E+10 | 0.623092E+10 | 0.568828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 297340.02 | 0.401810E+09 |
| April | 0.611554E+10 | 0.563950E+10 | 0.528539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35818532.57 | 0.211356E+09 |
| May | 0.672710E+10 | 0.605802E+10 | 0.559112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91723456.71 | 94585751.90 |
| June | 0.414905E+10 | 0.598530E+10 | 0.547839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141393E+09 | 22030175.31 |
| July | 0.142818E+10 | 0.357769E+10 | 0.334604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121748E+09 | 15910295.39 |
| August | 0.164241E+10 | 0.377621E+10 | 0.347792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 97402235.03 | 29270996.53 |
| September | 0.377186E+10 | 0.553277E+10 | 0.520168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32787467.38 | 46680511.11 |
| October | 0.642132E+10 | 0.588512E+10 | 0.549396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10950370.61 | 0.194325E+09 |
| November | 0.642132E+10 | 0.581240E+10 | 0.538255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363461E+09 |
| December | 0.611554E+10 | 0.571221E+10 | 0.539679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.379511E+09 |
| Annual Sum or Average | 0.620563E+11 | 0.654164E+11 | 0.608015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532407E+09 | 0.254661E+10 |
| Minimum of Months | 0.142818E+10 | 0.357769E+10 | 0.334604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15910295.39 |
| Maximum of Months | 0.703288E+10 | 0.623092E+10 | 0.568828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141393E+09 | 0.427466E+09 |
Report: SpaceGainsMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.488438E+10 | 0.302663E+10 | 0.376728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236010E+09 |
| February | 0.441920E+10 | 0.273660E+10 | 0.340486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57107.00 | 0.200468E+09 |
| March | 0.534956E+10 | 0.320447E+10 | 0.390054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67525.42 | 0.224005E+09 |
| April | 0.465179E+10 | 0.290031E+10 | 0.362427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16122054.55 | 0.117515E+09 |
| May | 0.511697E+10 | 0.311555E+10 | 0.383391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43905286.41 | 53559570.33 |
| June | 0.511697E+10 | 0.307815E+10 | 0.375661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68931227.48 | 13343567.33 |
| July | 0.244831E+10 | 0.183996E+10 | 0.229443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56658416.06 | 10746491.49 |
| August | 0.281556E+10 | 0.194205E+10 | 0.238486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44834355.17 | 18648994.12 |
| September | 0.454162E+10 | 0.284543E+10 | 0.356687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15434537.37 | 26828721.04 |
| October | 0.488438E+10 | 0.302663E+10 | 0.376728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4971710.30 | 0.106649E+09 |
| November | 0.488438E+10 | 0.298923E+10 | 0.369089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199128E+09 |
| December | 0.465179E+10 | 0.293771E+10 | 0.370066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208610E+09 |
| Annual Sum or Average | 0.537649E+11 | 0.336427E+11 | 0.416925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250982E+09 | 0.141551E+10 |
| Minimum of Months | 0.244831E+10 | 0.183996E+10 | 0.229443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10746491.49 |
| Maximum of Months | 0.534956E+10 | 0.320447E+10 | 0.390054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68931227.48 | 0.236010E+09 |
Report: SpaceGainsMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.222618E+10 | 0.371022E+10 | 0.253943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113104E+09 |
| February | 0.201416E+10 | 0.335468E+10 | 0.229513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 97749134.44 |
| March | 0.243819E+10 | 0.392822E+10 | 0.262925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28362.22 | 0.112587E+09 |
| April | 0.212017E+10 | 0.355537E+10 | 0.244302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5838085.66 | 61595341.71 |
| May | 0.233218E+10 | 0.381922E+10 | 0.258434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16895979.22 | 29742675.05 |
| June | 0.143841E+10 | 0.377338E+10 | 0.253223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28179444.08 | 9096007.66 |
| July | 0.495129E+09 | 0.225552E+10 | 0.154661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22900433.24 | 6948618.59 |
| August | 0.569398E+09 | 0.238068E+10 | 0.160757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18537597.79 | 10311975.04 |
| September | 0.130765E+10 | 0.348808E+10 | 0.240433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5815297.65 | 14977533.37 |
| October | 0.222618E+10 | 0.371022E+10 | 0.253943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1812515.32 | 53249040.98 |
| November | 0.222618E+10 | 0.366437E+10 | 0.248793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98062534.42 |
| December | 0.212017E+10 | 0.360121E+10 | 0.249452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98355413.80 |
| Annual Sum or Average | 0.215140E+11 | 0.412412E+11 | 0.281038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100008E+09 | 0.705780E+09 |
| Minimum of Months | 0.495129E+09 | 0.225552E+10 | 0.154661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6948618.59 |
| Maximum of Months | 0.243819E+10 | 0.392822E+10 | 0.262925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28179444.08 | 0.113104E+09 |
Report: SpaceGainsMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.139443E+10 | 0.296658E+10 | 0.795316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657127E+10 |
| February | 0.126163E+10 | 0.268230E+10 | 0.718803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530422E+10 |
| March | 0.152723E+10 | 0.314089E+10 | 0.823446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8733555.29 | 0.508260E+10 |
| April | 0.132803E+10 | 0.284277E+10 | 0.765123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628628E+09 | 0.237564E+10 |
| May | 0.146083E+10 | 0.305373E+10 | 0.809381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161329E+10 | 0.938434E+09 |
| June | 0.900991E+09 | 0.301708E+10 | 0.793062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306330E+10 | 0.282795E+09 |
| July | 0.310138E+09 | 0.180345E+10 | 0.484379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.257164E+10 | 0.145501E+09 |
| August | 0.356659E+09 | 0.190352E+10 | 0.503470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224941E+10 | 0.434854E+09 |
| September | 0.819082E+09 | 0.278897E+10 | 0.753006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156494E+10 | 0.818615E+09 |
| October | 0.139443E+10 | 0.296658E+10 | 0.795316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396712E+09 | 0.255747E+10 |
| November | 0.139443E+10 | 0.292992E+10 | 0.779188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497397E+10 |
| December | 0.132803E+10 | 0.287942E+10 | 0.781250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681881E+10 |
| Annual Sum or Average | 0.134759E+11 | 0.329752E+11 | 0.880174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120967E+11 | 0.363042E+11 |
| Minimum of Months | 0.310138E+09 | 0.180345E+10 | 0.484379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145501E+09 |
| Maximum of Months | 0.152723E+10 | 0.314089E+10 | 0.823446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306330E+10 | 0.681881E+10 |
Report: SpaceGainsMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.308232E+09 | 0.504438E+10 | 0.293011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.278876E+09 | 0.456100E+10 | 0.264822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.337587E+09 | 0.534079E+10 | 0.303375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.293554E+09 | 0.483386E+10 | 0.281887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.322909E+09 | 0.519259E+10 | 0.298193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.199160E+09 | 0.513026E+10 | 0.292181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 68554512.00 | 0.306659E+10 | 0.178455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 78837688.80 | 0.323676E+10 | 0.185489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.181054E+09 | 0.474238E+10 | 0.277423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.308232E+09 | 0.504438E+10 | 0.293011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.308232E+09 | 0.498206E+10 | 0.287069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.293554E+09 | 0.489618E+10 | 0.287829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.297878E+10 | 0.560712E+11 | 0.324275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68554512.00 | 0.306659E+10 | 0.178455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.337587E+09 | 0.534079E+10 | 0.303375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.774708E+09 | 0.228198E+10 | 0.883684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123121E+09 |
| February | 0.700926E+09 | 0.206331E+10 | 0.798670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 370.58 | 0.106733E+09 |
| March | 0.848489E+09 | 0.241607E+10 | 0.914940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125039E+09 |
| April | 0.737817E+09 | 0.218674E+10 | 0.850137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4175061.78 | 74180642.60 |
| May | 0.811598E+09 | 0.234903E+10 | 0.899312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12376008.94 | 40453312.14 |
| June | 0.500567E+09 | 0.232083E+10 | 0.881180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23332283.57 | 13996228.98 |
| July | 0.172304E+09 | 0.138727E+10 | 0.538198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 19661754.24 | 10933365.69 |
| August | 0.198150E+09 | 0.146425E+10 | 0.559411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16012686.97 | 14887437.29 |
| September | 0.455061E+09 | 0.214536E+10 | 0.836673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4178308.32 | 20432009.49 |
| October | 0.774708E+09 | 0.228198E+10 | 0.883684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1321683.58 | 64444960.94 |
| November | 0.774708E+09 | 0.225379E+10 | 0.865765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109125E+09 |
| December | 0.737817E+09 | 0.221494E+10 | 0.868056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108043E+09 |
| Annual Sum or Average | 0.748685E+10 | 0.253655E+11 | 0.977971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81058157.98 | 0.811389E+09 |
| Minimum of Months | 0.172304E+09 | 0.138727E+10 | 0.538198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10933365.69 |
| Maximum of Months | 0.848489E+09 | 0.241607E+10 | 0.914940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 23332283.57 | 0.125039E+09 |
Report: SpaceGainsMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.156120E+10 | 0.647363E+10 | 0.553791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559080E+09 |
| February | 0.141251E+10 | 0.585328E+10 | 0.500514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479314E+09 |
| March | 0.170988E+10 | 0.685401E+10 | 0.573379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 104718.54 | 0.533550E+09 |
| April | 0.148685E+10 | 0.620345E+10 | 0.532767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23389719.64 | 0.292577E+09 |
| May | 0.163554E+10 | 0.666382E+10 | 0.563585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74598566.02 | 0.141122E+09 |
| June | 0.163554E+10 | 0.658383E+10 | 0.552221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126095E+09 | 43784718.97 |
| July | 0.840841E+09 | 0.393546E+10 | 0.337280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98897591.12 | 37311128.91 |
| August | 0.966967E+09 | 0.415384E+10 | 0.350574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78345360.81 | 55119040.67 |
| September | 0.145455E+10 | 0.608605E+10 | 0.524330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22754504.94 | 78011851.96 |
| October | 0.156120E+10 | 0.647363E+10 | 0.553791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6704596.69 | 0.265143E+09 |
| November | 0.156120E+10 | 0.639364E+10 | 0.542561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480852E+09 |
| December | 0.148685E+10 | 0.628344E+10 | 0.543997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492870E+09 |
| Annual Sum or Average | 0.173131E+11 | 0.719581E+11 | 0.612879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430890E+09 | 0.345873E+10 |
| Minimum of Months | 0.840841E+09 | 0.393546E+10 | 0.337280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37311128.91 |
| Maximum of Months | 0.170988E+10 | 0.685401E+10 | 0.573379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126095E+09 | 0.559080E+09 |
Report: SpaceGainsMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.789800E+10 | 0.590754E+10 | 0.207549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234944E+09 |
| February | 0.714581E+10 | 0.534144E+10 | 0.187582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203207E+09 |
| March | 0.865019E+10 | 0.625466E+10 | 0.214891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53668.09 | 0.229507E+09 |
| April | 0.752191E+10 | 0.566098E+10 | 0.199670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11030109.93 | 0.122105E+09 |
| May | 0.827410E+10 | 0.608110E+10 | 0.211220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34659278.47 | 56205763.66 |
| June | 0.827410E+10 | 0.600810E+10 | 0.206961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57840098.65 | 15036801.61 |
| July | 0.453307E+10 | 0.359132E+10 | 0.126406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45805632.11 | 12986742.06 |
| August | 0.521303E+10 | 0.379060E+10 | 0.131388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36466581.81 | 20340601.12 |
| September | 0.737247E+10 | 0.555385E+10 | 0.196508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12165047.21 | 27509316.10 |
| October | 0.789800E+10 | 0.590754E+10 | 0.207549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3800373.78 | 0.103131E+09 |
| November | 0.789800E+10 | 0.583454E+10 | 0.203341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195323E+09 |
| December | 0.752191E+10 | 0.573398E+10 | 0.203879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205299E+09 |
| Annual Sum or Average | 0.882006E+11 | 0.656656E+11 | 0.229695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201821E+09 | 0.142559E+10 |
| Minimum of Months | 0.453307E+10 | 0.359132E+10 | 0.126406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12986742.06 |
| Maximum of Months | 0.865019E+10 | 0.625466E+10 | 0.214891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57840098.65 | 0.234944E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.204475E+10 | 0.269034E+10 | 0.811357E+10 | 0.909844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135198E+09 |
| February | 0.185001E+10 | 0.243253E+10 | 0.733032E+10 | 0.822599E+10 | 0.00 | 0.00 | 0.00 | 2096.39 | 0.112529E+09 |
| March | 0.223949E+10 | 0.284842E+10 | 0.823336E+10 | 0.959699E+10 | 0.00 | 0.00 | 0.00 | 46747.82 | 0.122498E+09 |
| April | 0.194738E+10 | 0.257806E+10 | 0.783252E+10 | 0.872454E+10 | 0.00 | 0.00 | 0.00 | 3567459.82 | 66437685.15 |
| May | 0.214212E+10 | 0.276938E+10 | 0.817347E+10 | 0.934772E+10 | 0.00 | 0.00 | 0.00 | 11455052.66 | 35208675.05 |
| June | 0.132119E+10 | 0.273614E+10 | 0.795231E+10 | 0.922308E+10 | 0.00 | 0.00 | 0.00 | 19816313.12 | 12754309.42 |
| July | 0.454778E+09 | 0.163552E+10 | 0.805368E+10 | 0.884917E+10 | 0.00 | 0.00 | 0.00 | 15767331.15 | 10452546.35 |
| August | 0.522995E+09 | 0.172627E+10 | 0.823336E+10 | 0.959699E+10 | 0.00 | 0.00 | 0.00 | 12985828.54 | 13065529.44 |
| September | 0.120108E+10 | 0.252927E+10 | 0.783252E+10 | 0.872454E+10 | 0.00 | 0.00 | 0.00 | 3850460.94 | 17753645.74 |
| October | 0.204475E+10 | 0.269034E+10 | 0.811357E+10 | 0.909844E+10 | 0.00 | 0.00 | 0.00 | 1176595.93 | 57113954.99 |
| November | 0.204475E+10 | 0.265710E+10 | 0.789242E+10 | 0.897381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107393E+09 |
| December | 0.194738E+10 | 0.261130E+10 | 0.805368E+10 | 0.884917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119182E+09 |
| Annual Sum or Average | 0.197607E+11 | 0.299046E+11 | 0.958148E+11 | 0.108309E+12 | 0.00 | 0.00 | 0.00 | 68667886.38 | 0.809585E+09 |
| Minimum of Months | 0.454778E+09 | 0.163552E+10 | 0.733032E+10 | 0.822599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10452546.35 |
| Maximum of Months | 0.223949E+10 | 0.284842E+10 | 0.823336E+10 | 0.959699E+10 | 0.00 | 0.00 | 0.00 | 19816313.12 | 0.135198E+09 |
Report: SpaceGainsMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.229168E+11 | 0.378329E+10 | 0.253516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462725E+09 |
| February | 0.207343E+11 | 0.342075E+10 | 0.229042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393656E+09 |
| March | 0.250994E+11 | 0.400559E+10 | 0.257259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113399.04 | 0.445685E+09 |
| April | 0.218255E+11 | 0.362539E+10 | 0.244734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16283622.33 | 0.265166E+09 |
| May | 0.240081E+11 | 0.389444E+10 | 0.255387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53567761.49 | 0.145905E+09 |
| June | 0.240081E+11 | 0.384769E+10 | 0.248477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92587066.70 | 57265935.47 |
| July | 0.556624E+10 | 0.229994E+10 | 0.251644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74546661.01 | 44642423.41 |
| August | 0.640118E+10 | 0.242757E+10 | 0.257259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 61445921.80 | 55406671.95 |
| September | 0.210126E+11 | 0.355678E+10 | 0.244734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18116672.56 | 77674743.20 |
| October | 0.229168E+11 | 0.378329E+10 | 0.253516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5402613.89 | 0.232482E+09 |
| November | 0.229168E+11 | 0.373654E+10 | 0.246606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395759E+09 |
| December | 0.218255E+11 | 0.367214E+10 | 0.251644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410073E+09 |
| Annual Sum or Average | 0.239231E+12 | 0.420534E+11 | 0.299382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322064E+09 | 0.298644E+10 |
| Minimum of Months | 0.556624E+10 | 0.229994E+10 | 0.229042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44642423.41 |
| Maximum of Months | 0.250994E+11 | 0.400559E+10 | 0.257259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 92587066.70 | 0.462725E+09 |
Report: SpaceGainsMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.325382E+10 | 0.825317E+10 | 0.695901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523976E+09 |
| February | 0.294393E+10 | 0.746230E+10 | 0.628953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 399.23 | 0.449612E+09 |
| March | 0.356371E+10 | 0.873812E+10 | 0.720516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 126105.26 | 0.509922E+09 |
| April | 0.309888E+10 | 0.790872E+10 | 0.669483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24671067.80 | 0.283591E+09 |
| May | 0.340876E+10 | 0.849564E+10 | 0.708208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72041684.30 | 0.140919E+09 |
| June | 0.210241E+10 | 0.839367E+10 | 0.693929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120191E+09 | 43931989.90 |
| July | 0.723690E+09 | 0.501728E+10 | 0.423831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95462198.73 | 36998546.35 |
| August | 0.832243E+09 | 0.529569E+10 | 0.440537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76843832.40 | 53646425.64 |
| September | 0.191128E+10 | 0.775905E+10 | 0.658880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23780422.28 | 74273587.67 |
| October | 0.325382E+10 | 0.825317E+10 | 0.695901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7460736.00 | 0.251574E+09 |
| November | 0.325382E+10 | 0.815120E+10 | 0.681790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449753E+09 |
| December | 0.309888E+10 | 0.801070E+10 | 0.683594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462796E+09 |
| Annual Sum or Average | 0.314452E+11 | 0.917387E+11 | 0.770152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420578E+09 | 0.328099E+10 |
| Minimum of Months | 0.723690E+09 | 0.501728E+10 | 0.423831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36998546.35 |
| Maximum of Months | 0.356371E+10 | 0.873812E+10 | 0.720516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120191E+09 | 0.523976E+09 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 566.21 | 25-JAN-23:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 740.17 | 08-FEB-21:10 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 | 22-MAR-13:00 | 552.97 | 19-MAR-23:55 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.25 | 29-APR-16:00 | 576.82 | 10-APR-24:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.91 | 14-MAY-15:50 | 249.18 | 04-MAY-02:20 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.46 | 21-JUN-20:01 | 187.28 | 28-JUN-02:10 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.39 | 02-JUL-20:52 | 125.15 | 18-JUL-21:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.09 | 26-AUG-14:50 | 157.26 | 14-AUG-00:30 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.84 | 09-SEP-15:43 | 114.40 | 23-SEP-17:08 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.33 | 01-OCT-15:00 | 311.38 | 23-OCT-20:57 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 385.90 | 26-NOV-09:00 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 485.19 | 18-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.40 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 284.39 | 740.17 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1648.91 | 25-JAN-23:00 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2091.45 | 09-FEB-01:00 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | 22-MAR-13:00 | 1634.85 | 19-MAR-23:55 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 458.02 | 29-APR-16:00 | 1651.14 | 10-APR-24:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 723.98 | 14-MAY-16:10 | 726.88 | 04-MAY-02:20 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 716.01 | 21-JUN-20:01 | 506.84 | 28-JUN-02:10 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 846.53 | 02-JUL-20:52 | 309.95 | 18-JUL-21:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 646.23 | 26-AUG-14:52 | 393.03 | 14-AUG-00:30 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 292.08 | 09-SEP-16:00 | 295.24 | 24-SEP-07:00 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.46 | 01-OCT-15:00 | 852.27 | 23-OCT-21:00 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1118.32 | 26-NOV-09:00 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1411.51 | 18-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.24 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 846.53 | 2091.45 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1178.08 | 02-JAN-08:09 | 947.12 | 02-JAN-07:10 | 678.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 92.11 | 25-JAN-23:00 |
| February | 1178.08 | 01-FEB-08:09 | 947.12 | 01-FEB-07:10 | 678.98 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 119.00 | 09-FEB-01:00 |
| March | 1178.08 | 01-MAR-08:09 | 947.12 | 01-MAR-07:10 | 678.98 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 22-MAR-13:00 | 91.62 | 19-MAR-23:55 |
| April | 1178.08 | 03-APR-07:10 | 947.12 | 03-APR-06:10 | 678.98 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.61 | 29-APR-16:00 | 95.88 | 10-APR-24:00 |
| May | 1178.08 | 01-MAY-07:10 | 947.12 | 01-MAY-06:10 | 678.98 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.64 | 14-MAY-15:50 | 41.57 | 04-MAY-02:20 |
| June | 1178.08 | 01-JUN-07:10 | 947.12 | 01-JUN-06:10 | 678.98 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.39 | 21-JUN-20:01 | 29.63 | 28-JUN-02:00 |
| July | 186.01 | 03-JUL-07:10 | 526.18 | 03-JUL-07:10 | 357.36 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.99 | 02-JUL-20:52 | 16.90 | 18-JUL-21:00 |
| August | 186.01 | 01-AUG-07:10 | 526.18 | 01-AUG-07:10 | 357.36 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.17 | 26-AUG-14:52 | 23.02 | 14-AUG-00:30 |
| September | 1178.08 | 18-SEP-07:10 | 947.12 | 05-SEP-06:10 | 678.98 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.88 | 10-SEP-15:10 | 16.40 | 23-SEP-17:00 |
| October | 1178.08 | 02-OCT-07:10 | 947.12 | 02-OCT-06:10 | 678.98 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.41 | 01-OCT-15:00 | 45.89 | 23-OCT-21:00 |
| November | 1178.08 | 01-NOV-07:10 | 947.12 | 01-NOV-06:10 | 678.98 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 58.62 | 26-NOV-09:00 |
| December | 1178.08 | 01-DEC-08:09 | 947.12 | 01-DEC-07:10 | 678.98 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 76.00 | 18-DEC-05:45 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.40 | |||||
| Maximum of Months | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 40.99 | 119.00 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 543.15 | 25-JAN-23:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.05 | 20-FEB-15:20 | 714.84 | 08-FEB-21:02 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.13 | 19-MAR-14:00 | 497.46 | 19-MAR-23:55 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.73 | 01-APR-15:10 | 563.12 | 10-APR-24:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.53 | 14-MAY-15:30 | 246.20 | 04-MAY-02:20 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.32 | 21-JUN-20:01 | 188.31 | 28-JUN-02:10 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.62 | 02-JUL-20:52 | 123.67 | 18-JUL-21:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.53 | 26-AUG-14:50 | 150.08 | 14-AUG-00:30 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.20 | 09-SEP-15:43 | 106.24 | 23-SEP-17:08 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.98 | 01-OCT-15:00 | 290.01 | 23-OCT-20:57 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 336.47 | 26-NOV-09:00 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 426.22 | 18-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.24 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 284.62 | 714.84 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1567.83 | 25-JAN-23:00 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.58 | 20-FEB-16:20 | 1982.82 | 09-FEB-01:00 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.89 | 19-MAR-15:10 | 1475.00 | 19-MAR-23:55 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 516.90 | 01-APR-15:10 | 1613.15 | 10-APR-24:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 743.91 | 14-MAY-16:10 | 718.99 | 04-MAY-02:20 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 714.46 | 04-JUN-19:00 | 510.15 | 28-JUN-02:10 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 847.96 | 02-JUL-20:52 | 300.80 | 18-JUL-21:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 691.09 | 26-AUG-14:52 | 369.07 | 14-AUG-00:30 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.63 | 09-SEP-16:00 | 282.23 | 24-SEP-07:00 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 392.32 | 01-OCT-15:00 | 783.89 | 23-OCT-21:00 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 972.30 | 26-NOV-09:00 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1231.68 | 18-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.23 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 847.96 | 1982.82 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 565.53 | 25-JAN-23:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 739.96 | 08-FEB-21:10 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 | 22-MAR-13:00 | 553.22 | 19-MAR-23:55 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.76 | 29-APR-16:00 | 576.90 | 10-APR-24:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.74 | 14-MAY-15:50 | 249.62 | 04-MAY-02:20 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.48 | 21-JUN-20:01 | 187.05 | 28-JUN-02:10 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 285.27 | 02-JUL-20:52 | 124.35 | 18-JUL-21:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 218.03 | 26-AUG-14:50 | 156.43 | 14-AUG-00:30 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 09-SEP-15:43 | 113.66 | 23-SEP-17:08 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.68 | 01-OCT-15:00 | 311.35 | 23-OCT-20:57 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 384.91 | 26-NOV-09:00 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 485.04 | 18-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.66 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 285.27 | 739.96 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1647.08 | 25-JAN-23:00 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2092.33 | 09-FEB-01:00 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | 22-MAR-13:00 | 1638.82 | 19-MAR-23:55 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 463.26 | 29-APR-16:00 | 1654.23 | 10-APR-24:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 729.57 | 14-MAY-16:10 | 730.07 | 04-MAY-02:20 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 717.95 | 21-JUN-20:01 | 506.07 | 28-JUN-02:10 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 849.60 | 02-JUL-20:52 | 304.98 | 18-JUL-21:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 651.36 | 26-AUG-14:52 | 389.18 | 14-AUG-00:30 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.69 | 09-SEP-16:00 | 293.87 | 24-SEP-07:00 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 313.97 | 01-OCT-15:00 | 850.67 | 23-OCT-21:00 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1110.34 | 26-NOV-09:00 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1404.80 | 18-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.87 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 849.60 | 2092.33 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1178.08 | 02-JAN-08:09 | 947.12 | 02-JAN-07:10 | 678.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 91.99 | 25-JAN-23:00 |
| February | 1178.08 | 01-FEB-08:09 | 947.12 | 01-FEB-07:10 | 678.98 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 | 20-FEB-15:20 | 118.96 | 09-FEB-01:00 |
| March | 1178.08 | 01-MAR-08:09 | 947.12 | 01-MAR-07:10 | 678.98 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 22-MAR-13:00 | 91.65 | 19-MAR-23:55 |
| April | 1178.08 | 03-APR-07:10 | 947.12 | 03-APR-06:10 | 678.98 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.66 | 29-APR-16:00 | 95.89 | 10-APR-24:00 |
| May | 1178.08 | 01-MAY-07:10 | 947.12 | 01-MAY-06:10 | 678.98 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.72 | 14-MAY-15:50 | 41.59 | 04-MAY-02:20 |
| June | 1178.08 | 01-JUN-07:10 | 947.12 | 01-JUN-06:10 | 678.98 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.40 | 21-JUN-20:01 | 29.61 | 28-JUN-02:00 |
| July | 186.01 | 03-JUL-07:10 | 526.18 | 03-JUL-07:10 | 357.36 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 02-JUL-20:52 | 16.81 | 18-JUL-21:00 |
| August | 186.01 | 01-AUG-07:10 | 526.18 | 01-AUG-07:10 | 357.36 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.25 | 26-AUG-14:52 | 22.93 | 14-AUG-00:30 |
| September | 1178.08 | 18-SEP-07:10 | 947.12 | 05-SEP-06:10 | 678.98 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 10-SEP-15:10 | 16.34 | 23-SEP-17:00 |
| October | 1178.08 | 02-OCT-07:10 | 947.12 | 02-OCT-06:10 | 678.98 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.45 | 01-OCT-15:00 | 45.86 | 23-OCT-21:00 |
| November | 1178.08 | 01-NOV-07:10 | 947.12 | 01-NOV-06:10 | 678.98 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 58.50 | 26-NOV-09:00 |
| December | 1178.08 | 01-DEC-08:09 | 947.12 | 01-DEC-07:10 | 678.98 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 75.77 | 18-DEC-05:45 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 | |||||
| Maximum of Months | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 41.07 | 118.96 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 542.92 | 25-JAN-23:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 26.15 | 20-FEB-15:20 | 714.89 | 08-FEB-21:02 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 33.05 | 19-MAR-14:00 | 497.51 | 19-MAR-23:55 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.64 | 01-APR-15:10 | 563.11 | 10-APR-24:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 242.49 | 14-MAY-15:30 | 246.13 | 04-MAY-02:20 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.32 | 21-JUN-20:01 | 188.29 | 28-JUN-02:10 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.71 | 02-JUL-20:52 | 123.62 | 18-JUL-21:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 230.58 | 26-AUG-14:50 | 149.98 | 14-AUG-00:30 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.22 | 09-SEP-15:43 | 106.25 | 23-SEP-17:08 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.03 | 01-OCT-15:00 | 289.93 | 23-OCT-20:57 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 336.27 | 26-NOV-09:00 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 425.67 | 18-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.25 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 284.71 | 714.89 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1567.10 | 25-JAN-23:00 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 88.83 | 20-FEB-16:20 | 1982.39 | 09-FEB-01:00 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 85.58 | 19-MAR-15:10 | 1475.16 | 19-MAR-23:55 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 516.65 | 01-APR-15:10 | 1613.14 | 10-APR-24:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 743.87 | 14-MAY-16:10 | 718.76 | 04-MAY-02:20 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 714.63 | 04-JUN-19:00 | 510.13 | 28-JUN-02:10 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 848.04 | 02-JUL-20:52 | 300.63 | 18-JUL-21:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 691.28 | 26-AUG-14:52 | 368.74 | 14-AUG-00:30 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.68 | 09-SEP-16:00 | 282.11 | 24-SEP-07:00 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 392.47 | 01-OCT-15:00 | 783.67 | 23-OCT-21:00 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 971.70 | 26-NOV-09:00 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1230.12 | 18-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.11 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 848.04 | 1982.39 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 567.60 | 25-JAN-23:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 741.28 | 08-FEB-21:10 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.64 | 22-MAR-13:00 | 554.54 | 19-MAR-23:55 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 155.44 | 29-APR-16:00 | 577.69 | 10-APR-24:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 235.22 | 14-MAY-15:50 | 250.09 | 04-MAY-02:20 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.46 | 21-JUN-20:01 | 187.33 | 28-JUN-02:10 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 284.80 | 02-JUL-20:52 | 124.83 | 18-JUL-21:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.46 | 26-AUG-14:50 | 157.06 | 14-AUG-00:30 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.49 | 09-SEP-15:43 | 113.87 | 23-SEP-17:08 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 102.53 | 01-OCT-15:00 | 311.59 | 23-OCT-20:57 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 386.00 | 26-NOV-09:00 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 487.49 | 18-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.87 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 284.80 | 741.28 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1657.82 | 25-JAN-23:00 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2098.36 | 09-FEB-01:00 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.94 | 22-MAR-13:00 | 1642.43 | 19-MAR-23:55 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 461.14 | 29-APR-16:00 | 1657.59 | 10-APR-24:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 726.23 | 14-MAY-16:10 | 733.03 | 04-MAY-02:20 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 715.81 | 21-JUN-20:01 | 508.12 | 28-JUN-02:10 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 845.82 | 02-JUL-20:52 | 308.13 | 18-JUL-21:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 647.41 | 26-AUG-14:52 | 392.60 | 14-AUG-00:30 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 294.30 | 09-SEP-16:00 | 295.33 | 24-SEP-07:00 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.46 | 01-OCT-15:00 | 852.39 | 23-OCT-21:00 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1114.71 | 26-NOV-09:00 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1415.23 | 18-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 295.33 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 845.82 | 2098.36 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1178.08 | 02-JAN-08:09 | 947.12 | 02-JAN-07:10 | 678.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 93.28 | 25-JAN-23:00 |
| February | 1178.08 | 01-FEB-08:09 | 947.12 | 01-FEB-07:10 | 678.98 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 119.87 | 09-FEB-01:00 |
| March | 1178.08 | 01-MAR-08:09 | 947.12 | 01-MAR-07:10 | 678.98 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.84 | 22-MAR-13:00 | 92.32 | 19-MAR-23:55 |
| April | 1178.08 | 03-APR-07:10 | 947.12 | 03-APR-06:10 | 678.98 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.40 | 29-APR-16:00 | 96.40 | 10-APR-24:00 |
| May | 1178.08 | 01-MAY-07:10 | 947.12 | 01-MAY-06:10 | 678.98 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.34 | 14-MAY-15:50 | 41.98 | 04-MAY-02:20 |
| June | 1178.08 | 01-JUN-07:10 | 947.12 | 01-JUN-06:10 | 678.98 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.37 | 21-JUN-20:01 | 29.84 | 28-JUN-02:00 |
| July | 186.01 | 03-JUL-07:10 | 526.18 | 03-JUL-07:10 | 357.36 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.65 | 02-JUL-20:52 | 17.20 | 18-JUL-21:00 |
| August | 186.01 | 01-AUG-07:10 | 526.18 | 01-AUG-07:10 | 357.36 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.79 | 26-AUG-14:52 | 23.28 | 14-AUG-00:30 |
| September | 1178.08 | 18-SEP-07:10 | 947.12 | 05-SEP-06:10 | 678.98 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.75 | 10-SEP-15:10 | 16.50 | 23-SEP-17:00 |
| October | 1178.08 | 02-OCT-07:10 | 947.12 | 02-OCT-06:10 | 678.98 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.32 | 01-OCT-15:00 | 46.10 | 23-OCT-21:00 |
| November | 1178.08 | 01-NOV-07:10 | 947.12 | 01-NOV-06:10 | 678.98 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 58.97 | 26-NOV-09:00 |
| December | 1178.08 | 01-DEC-08:09 | 947.12 | 01-DEC-07:10 | 678.98 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 76.63 | 18-DEC-05:45 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.50 | |||||
| Maximum of Months | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 40.65 | 119.87 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 544.80 | 25-JAN-23:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 25.10 | 20-FEB-15:20 | 715.03 | 08-FEB-21:02 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.72 | 19-MAR-14:00 | 498.78 | 19-MAR-23:55 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.91 | 01-APR-15:10 | 563.98 | 10-APR-24:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 240.49 | 14-MAY-15:30 | 246.18 | 04-MAY-02:20 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 265.29 | 21-JUN-20:01 | 188.76 | 28-JUN-02:10 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 283.47 | 02-JUL-20:52 | 124.81 | 18-JUL-21:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 229.07 | 26-AUG-14:50 | 151.24 | 14-AUG-00:30 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.05 | 09-SEP-15:43 | 107.05 | 23-SEP-17:08 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.54 | 01-OCT-15:00 | 290.16 | 23-OCT-20:57 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 337.45 | 26-NOV-09:00 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 426.88 | 18-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.05 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 283.47 | 715.03 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 9663.62 | 02-JAN-08:09 | 4272.19 | 02-JAN-07:10 | 4177.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1039.97 | 25-JAN-23:00 |
| February | 9663.62 | 01-FEB-08:09 | 4272.19 | 01-FEB-07:10 | 4177.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 55.02 | 20-FEB-16:20 | 1311.52 | 09-FEB-01:00 |
| March | 9663.62 | 01-MAR-08:09 | 4272.19 | 01-MAR-07:10 | 4177.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 | 19-MAR-15:10 | 972.60 | 19-MAR-23:55 |
| April | 9663.62 | 03-APR-07:10 | 4272.19 | 03-APR-06:10 | 4177.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 336.97 | 01-APR-15:10 | 1065.16 | 10-APR-24:00 |
| May | 9663.62 | 01-MAY-07:10 | 4272.19 | 01-MAY-06:10 | 4177.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 486.61 | 14-MAY-16:10 | 474.01 | 04-MAY-02:20 |
| June | 9663.62 | 01-JUN-07:10 | 4272.19 | 01-JUN-06:10 | 4177.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 469.09 | 04-JUN-19:00 | 337.99 | 28-JUN-02:10 |
| July | 1525.83 | 03-JUL-07:10 | 2373.44 | 03-JUL-07:10 | 2198.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 555.34 | 02-JUL-20:52 | 203.10 | 18-JUL-21:00 |
| August | 1525.83 | 01-AUG-07:10 | 2373.44 | 01-AUG-07:10 | 2198.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 450.80 | 26-AUG-14:52 | 246.05 | 14-AUG-00:30 |
| September | 9663.62 | 18-SEP-07:10 | 4272.19 | 05-SEP-06:10 | 4177.31 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.84 | 09-SEP-16:00 | 186.68 | 24-SEP-07:00 |
| October | 9663.62 | 02-OCT-07:10 | 4272.19 | 02-OCT-06:10 | 4177.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 257.91 | 01-OCT-15:00 | 517.54 | 23-OCT-21:00 |
| November | 9663.62 | 01-NOV-07:10 | 4272.19 | 01-NOV-06:10 | 4177.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 642.74 | 26-NOV-09:00 |
| December | 9663.62 | 01-DEC-08:09 | 4272.19 | 01-DEC-07:10 | 4177.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 813.90 | 18-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 1525.83 | 2373.44 | 2198.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.68 | |||||
| Maximum of Months | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 555.34 | 1311.52 |
Report: PeakSpaceGainsMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 4969.86 | 02-JAN-08:09 | 2197.13 | 02-JAN-07:10 | 2864.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 574.46 | 25-JAN-23:00 |
| February | 4969.86 | 01-FEB-08:09 | 2197.13 | 01-FEB-07:10 | 2864.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.36 | 20-FEB-15:20 | 720.56 | 08-FEB-21:10 |
| March | 4969.86 | 01-MAR-08:09 | 2197.13 | 01-MAR-07:10 | 2864.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.37 | 19-MAR-14:00 | 529.39 | 19-MAR-23:55 |
| April | 4969.86 | 03-APR-07:10 | 2197.13 | 03-APR-06:10 | 2864.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.92 | 29-APR-16:00 | 572.38 | 10-APR-24:00 |
| May | 4969.86 | 01-MAY-07:10 | 2197.13 | 01-MAY-06:10 | 2864.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 243.32 | 14-MAY-15:30 | 264.80 | 04-MAY-02:20 |
| June | 4969.86 | 01-JUN-07:10 | 2197.13 | 01-JUN-06:10 | 2864.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 239.02 | 21-JUN-20:01 | 185.24 | 28-JUN-02:10 |
| July | 2615.72 | 03-JUL-07:10 | 1220.63 | 03-JUL-07:10 | 1507.60 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.80 | 02-JUL-20:52 | 119.58 | 18-JUL-21:00 |
| August | 2615.72 | 01-AUG-07:10 | 1220.63 | 01-AUG-07:10 | 1507.60 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.46 | 26-AUG-14:52 | 135.09 | 14-AUG-00:30 |
| September | 4969.86 | 05-SEP-07:10 | 2197.13 | 05-SEP-06:10 | 2864.44 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.79 | 09-SEP-15:43 | 101.38 | 24-SEP-07:00 |
| October | 4969.86 | 02-OCT-07:10 | 2197.13 | 02-OCT-06:10 | 2864.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.36 | 01-OCT-15:00 | 281.03 | 23-OCT-21:00 |
| November | 4969.86 | 01-NOV-07:10 | 2197.13 | 01-NOV-06:10 | 2864.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 347.12 | 26-NOV-09:00 |
| December | 4969.86 | 01-DEC-08:09 | 2197.13 | 01-DEC-07:10 | 2864.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 439.43 | 18-DEC-05:45 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2615.72 | 1220.63 | 1507.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.38 | |||||
| Maximum of Months | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 275.80 | 720.56 |
Report: PeakSpaceGainsMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3350.23 | 02-JAN-08:09 | 2693.36 | 02-JAN-07:10 | 1930.85 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 272.03 | 25-JAN-23:00 |
| February | 3350.23 | 01-FEB-08:09 | 2693.36 | 01-FEB-07:10 | 1930.85 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.05 | 20-FEB-15:20 | 356.97 | 09-FEB-01:00 |
| March | 3350.23 | 01-MAR-08:09 | 2693.36 | 01-MAR-07:10 | 1930.85 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.53 | 22-MAR-13:00 | 288.91 | 19-MAR-23:55 |
| April | 3350.23 | 03-APR-07:10 | 2693.36 | 03-APR-06:10 | 1930.85 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.89 | 29-APR-16:00 | 298.87 | 10-APR-24:00 |
| May | 3350.23 | 01-MAY-07:10 | 2693.36 | 01-MAY-06:10 | 1930.85 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.27 | 14-MAY-15:50 | 133.69 | 04-MAY-02:20 |
| June | 3350.23 | 01-JUN-07:10 | 2693.36 | 01-JUN-06:10 | 1930.85 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.25 | 21-JUN-20:01 | 96.78 | 28-JUN-02:10 |
| July | 528.98 | 03-JUL-07:10 | 1496.31 | 03-JUL-07:10 | 1016.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 107.76 | 02-JUL-20:52 | 56.64 | 18-JUL-21:00 |
| August | 528.98 | 01-AUG-07:10 | 1496.31 | 01-AUG-07:10 | 1016.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.87 | 26-AUG-14:52 | 79.22 | 14-AUG-00:30 |
| September | 3350.23 | 18-SEP-07:10 | 2693.36 | 05-SEP-06:10 | 1930.85 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.63 | 09-SEP-16:00 | 51.83 | 23-SEP-17:00 |
| October | 3350.23 | 02-OCT-07:10 | 2693.36 | 02-OCT-06:10 | 1930.85 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 | 01-OCT-15:00 | 139.26 | 23-OCT-21:00 |
| November | 3350.23 | 01-NOV-07:10 | 2693.36 | 01-NOV-06:10 | 1930.85 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 176.83 | 26-NOV-09:00 |
| December | 3350.23 | 01-DEC-08:09 | 2693.36 | 01-DEC-07:10 | 1930.85 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 222.13 | 18-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 528.98 | 1496.31 | 1016.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.83 | |||||
| Maximum of Months | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 121.25 | 356.97 |
Report: PeakSpaceGainsMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 2098.51 | 02-JAN-08:09 | 2153.53 | 02-JAN-07:10 | 604.72 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 70118.16 | 27-JAN-07:01 |
| February | 2098.51 | 01-FEB-08:09 | 2153.53 | 01-FEB-07:10 | 604.72 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 71710.92 | 03-FEB-07:01 |
| March | 2098.51 | 01-MAR-08:09 | 2153.53 | 01-MAR-07:10 | 604.72 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1241.89 | 21-MAR-15:00 | 62271.20 | 02-MAR-07:01 |
| April | 2098.51 | 03-APR-07:10 | 2153.53 | 03-APR-06:10 | 604.72 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22344.20 | 21-APR-14:01 | 51085.71 | 12-APR-06:01 |
| May | 2098.51 | 01-MAY-07:10 | 2153.53 | 01-MAY-06:10 | 604.72 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28216.86 | 19-MAY-14:01 | 37505.73 | 02-MAY-06:01 |
| June | 2098.51 | 01-JUN-07:10 | 2153.53 | 01-JUN-06:10 | 604.72 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34898.36 | 14-JUN-14:01 | 18720.85 | 13-JUN-06:01 |
| July | 331.34 | 03-JUL-07:10 | 1196.41 | 03-JUL-07:10 | 318.27 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35024.85 | 03-JUL-14:01 | 16099.11 | 05-JUL-06:01 |
| August | 331.34 | 01-AUG-07:10 | 1196.41 | 01-AUG-07:10 | 318.27 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29643.71 | 04-AUG-14:01 | 18733.61 | 31-AUG-06:01 |
| September | 2098.51 | 18-SEP-07:10 | 2153.53 | 05-SEP-06:10 | 604.72 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24037.17 | 19-SEP-14:01 | 38883.96 | 25-SEP-06:01 |
| October | 2098.51 | 02-OCT-07:10 | 2153.53 | 02-OCT-06:10 | 604.72 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21442.92 | 03-OCT-14:01 | 47420.77 | 11-OCT-06:01 |
| November | 2098.51 | 01-NOV-07:10 | 2153.53 | 01-NOV-06:10 | 604.72 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 61263.01 | 17-NOV-07:01 |
| December | 2098.51 | 01-DEC-08:09 | 2153.53 | 01-DEC-07:10 | 604.72 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 68342.50 | 27-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16099.11 | |||||
| Maximum of Months | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 35024.85 | 71710.92 |
Report: PeakSpaceGainsMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 463.87 | 02-JAN-08:09 | 3661.88 | 02-JAN-07:10 | 2227.90 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
| February | 463.87 | 01-FEB-08:09 | 3661.88 | 01-FEB-07:10 | 2227.90 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
| March | 463.87 | 01-MAR-08:09 | 3661.88 | 01-MAR-07:10 | 2227.90 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
| April | 463.87 | 03-APR-07:10 | 3661.88 | 03-APR-06:10 | 2227.90 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 463.87 | 01-MAY-07:10 | 3661.88 | 01-MAY-06:10 | 2227.90 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 |
| June | 463.87 | 01-JUN-07:10 | 3661.88 | 01-JUN-06:10 | 2227.90 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 01-JUN-00:03 |
| July | 73.24 | 03-JUL-07:10 | 2034.38 | 03-JUL-07:10 | 1172.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 01-JUL-00:02 |
| August | 73.24 | 01-AUG-07:10 | 2034.38 | 01-AUG-07:10 | 1172.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:03 |
| September | 463.87 | 18-SEP-07:10 | 3661.88 | 05-SEP-06:10 | 2227.90 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 |
| October | 463.87 | 02-OCT-07:10 | 3661.88 | 02-OCT-06:10 | 2227.90 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 01-OCT-00:03 |
| November | 463.87 | 01-NOV-07:10 | 3661.88 | 01-NOV-06:10 | 2227.90 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 463.87 | 01-DEC-08:09 | 3661.88 | 01-DEC-07:10 | 2227.90 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 73.24 | 2034.38 | 1172.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
| Maximum of Months | 463.87 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1165.88 | 02-JAN-08:09 | 1656.56 | 02-JAN-07:10 | 671.91 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 297.51 | 25-JAN-23:00 |
| February | 1165.88 | 01-FEB-08:09 | 1656.56 | 01-FEB-07:10 | 671.91 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 20-FEB-15:20 | 388.11 | 09-FEB-01:00 |
| March | 1165.88 | 01-MAR-08:09 | 1656.56 | 01-MAR-07:10 | 671.91 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 311.35 | 19-MAR-23:55 |
| April | 1165.88 | 03-APR-07:10 | 1656.56 | 03-APR-06:10 | 671.91 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.34 | 01-APR-15:10 | 335.38 | 10-APR-24:00 |
| May | 1165.88 | 01-MAY-07:10 | 1656.56 | 01-MAY-06:10 | 671.91 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.47 | 14-MAY-15:30 | 163.74 | 04-MAY-02:20 |
| June | 1165.88 | 01-JUN-07:10 | 1656.56 | 01-JUN-06:10 | 671.91 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.46 | 21-JUN-20:10 | 122.76 | 28-JUN-02:00 |
| July | 184.09 | 03-JUL-07:10 | 920.31 | 03-JUL-07:10 | 353.64 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.59 | 02-JUL-21:10 | 76.53 | 18-JUL-21:00 |
| August | 184.09 | 01-AUG-07:10 | 920.31 | 01-AUG-07:10 | 353.64 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.22 | 26-AUG-14:52 | 94.30 | 14-AUG-00:30 |
| September | 1165.88 | 18-SEP-07:10 | 1656.56 | 05-SEP-06:10 | 671.91 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.48 | 10-SEP-14:50 | 64.74 | 23-SEP-17:00 |
| October | 1165.88 | 02-OCT-07:10 | 1656.56 | 02-OCT-06:10 | 671.91 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.75 | 01-OCT-15:00 | 162.83 | 23-OCT-21:00 |
| November | 1165.88 | 01-NOV-07:10 | 1656.56 | 01-NOV-06:10 | 671.91 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 191.08 | 26-NOV-09:00 |
| December | 1165.88 | 01-DEC-08:09 | 1656.56 | 01-DEC-07:10 | 671.91 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 240.43 | 18-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 184.09 | 920.31 | 353.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.74 | |||||
| Maximum of Months | 1165.88 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 113.59 | 388.11 |
Report: PeakSpaceGainsMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 2705.96 | 02-JAN-08:09 | 4699.41 | 02-JAN-07:10 | 4210.73 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1294.82 | 25-JAN-23:00 |
| February | 2705.96 | 01-FEB-08:09 | 4699.41 | 01-FEB-07:10 | 4210.73 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1661.22 | 08-FEB-21:10 |
| March | 2705.96 | 01-MAR-08:09 | 4699.41 | 01-MAR-07:10 | 4210.73 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.82 | 22-MAR-13:00 | 1311.13 | 19-MAR-23:55 |
| April | 2705.96 | 03-APR-07:10 | 4699.41 | 03-APR-06:10 | 4210.73 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.11 | 29-APR-16:00 | 1351.88 | 10-APR-24:00 |
| May | 2705.96 | 01-MAY-07:10 | 4699.41 | 01-MAY-06:10 | 4210.73 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 398.96 | 14-MAY-15:50 | 611.30 | 04-MAY-02:20 |
| June | 2705.96 | 01-JUN-07:10 | 4699.41 | 01-JUN-06:10 | 4210.73 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 560.54 | 21-JUN-20:01 | 452.90 | 28-JUN-02:10 |
| July | 1424.19 | 03-JUL-07:10 | 2610.78 | 03-JUL-07:10 | 2216.18 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 488.80 | 02-JUL-21:10 | 284.57 | 18-JUL-21:00 |
| August | 1424.19 | 01-AUG-07:10 | 2610.78 | 01-AUG-07:10 | 2216.18 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 406.58 | 26-AUG-14:52 | 391.17 | 14-AUG-00:30 |
| September | 2705.96 | 05-SEP-07:10 | 4699.41 | 05-SEP-06:10 | 4210.73 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.70 | 10-SEP-15:10 | 265.56 | 23-SEP-17:00 |
| October | 2705.96 | 02-OCT-07:10 | 4699.41 | 02-OCT-06:10 | 4210.73 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.25 | 01-OCT-14:53 | 672.01 | 23-OCT-21:00 |
| November | 2705.96 | 01-NOV-07:10 | 4699.41 | 01-NOV-06:10 | 4210.73 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 865.48 | 26-NOV-09:00 |
| December | 2705.96 | 01-DEC-08:09 | 4699.41 | 01-DEC-07:10 | 4210.73 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1067.29 | 18-DEC-05:25 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 1424.19 | 2610.78 | 2216.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.56 | |||||
| Maximum of Months | 2705.96 | 4699.41 | 4210.73 | 0.00 | 0.00 | 0.00 | 0.00 | 560.54 | 1661.22 |
Report: PeakSpaceGainsMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 13145.35 | 02-JAN-16:10 | 4288.47 | 02-JAN-07:10 | 1578.10 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 561.58 | 25-JAN-23:00 |
| February | 13145.35 | 01-FEB-16:10 | 4288.47 | 01-FEB-07:10 | 1578.10 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 712.31 | 08-FEB-21:02 |
| March | 13145.35 | 01-MAR-16:10 | 4288.47 | 01-MAR-07:10 | 1578.10 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.79 | 22-MAR-13:00 | 572.67 | 19-MAR-23:55 |
| April | 13145.35 | 03-APR-15:09 | 4288.47 | 03-APR-06:10 | 1578.10 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 127.21 | 29-APR-16:00 | 574.44 | 10-APR-24:00 |
| May | 13145.35 | 01-MAY-15:09 | 4288.47 | 01-MAY-06:10 | 1578.10 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 194.13 | 14-MAY-16:10 | 262.38 | 04-MAY-02:20 |
| June | 13145.35 | 01-JUN-15:09 | 4288.47 | 01-JUN-06:10 | 1578.10 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.27 | 21-JUN-20:01 | 185.76 | 28-JUN-02:10 |
| July | 4843.02 | 03-JUL-07:10 | 2382.48 | 03-JUL-07:10 | 830.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.74 | 02-JUL-20:52 | 117.85 | 18-JUL-21:00 |
| August | 4843.02 | 01-AUG-07:10 | 2382.48 | 01-AUG-07:10 | 830.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.17 | 26-AUG-14:50 | 149.00 | 14-AUG-00:30 |
| September | 13145.35 | 05-SEP-15:09 | 4288.47 | 05-SEP-06:10 | 1578.10 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 84.92 | 09-SEP-16:00 | 100.10 | 24-SEP-07:00 |
| October | 13145.35 | 02-OCT-15:09 | 4288.47 | 02-OCT-06:10 | 1578.10 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.72 | 01-OCT-15:00 | 271.88 | 23-OCT-21:00 |
| November | 13145.35 | 01-NOV-15:09 | 4288.47 | 01-NOV-06:10 | 1578.10 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 359.08 | 26-NOV-09:00 |
| December | 13145.35 | 01-DEC-16:10 | 4288.47 | 01-DEC-07:10 | 1578.10 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 442.90 | 18-DEC-05:25 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 4843.02 | 2382.48 | 830.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.10 | |||||
| Maximum of Months | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 231.74 | 712.31 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3077.20 | 02-JAN-08:09 | 1953.00 | 02-JAN-07:10 | 6399.12 | 02-JAN-10:09 | 14425.49 | 02-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 339.68 | 25-JAN-23:34 |
| February | 3077.20 | 01-FEB-08:09 | 1953.00 | 01-FEB-07:10 | 6399.12 | 01-FEB-10:09 | 14425.49 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 5.46 | 19-FEB-15:37 | 386.75 | 09-FEB-01:00 |
| March | 3077.20 | 01-MAR-08:09 | 1953.00 | 01-MAR-07:10 | 6399.12 | 01-MAR-10:09 | 14425.49 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 28.54 | 19-MAR-14:40 | 318.92 | 19-MAR-23:50 |
| April | 3077.20 | 03-APR-07:10 | 1953.00 | 03-APR-06:10 | 6399.12 | 03-APR-09:09 | 14425.49 | 03-APR-09:09 | 0.00 | 0.00 | 0.00 | 46.27 | 21-APR-22:20 | 309.91 | 11-APR-00:10 |
| May | 3077.20 | 01-MAY-07:10 | 1953.00 | 01-MAY-06:10 | 6399.12 | 01-MAY-09:09 | 14425.49 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 70.51 | 14-MAY-16:00 | 178.77 | 04-MAY-02:10 |
| June | 3077.20 | 01-JUN-07:10 | 1953.00 | 01-JUN-06:10 | 6399.12 | 01-JUN-09:09 | 14425.49 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 102.91 | 21-JUN-20:01 | 117.46 | 28-JUN-02:10 |
| July | 485.87 | 03-JUL-07:10 | 1085.00 | 03-JUL-07:10 | 6399.12 | 03-JUL-09:09 | 14425.49 | 03-JUL-09:09 | 0.00 | 0.00 | 0.00 | 82.85 | 02-JUL-20:54 | 75.17 | 18-JUL-20:50 |
| August | 485.87 | 01-AUG-07:10 | 1085.00 | 01-AUG-07:10 | 6399.12 | 01-AUG-09:09 | 14425.49 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 78.26 | 26-AUG-14:54 | 95.86 | 14-AUG-00:50 |
| September | 3077.20 | 18-SEP-07:10 | 1953.00 | 05-SEP-06:10 | 6399.12 | 01-SEP-09:09 | 14425.49 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 27.73 | 10-SEP-14:54 | 69.62 | 24-SEP-10:50 |
| October | 3077.20 | 02-OCT-07:10 | 1953.00 | 02-OCT-06:10 | 6399.12 | 02-OCT-09:09 | 14425.49 | 02-OCT-09:09 | 0.00 | 0.00 | 0.00 | 37.80 | 01-OCT-15:00 | 147.00 | 23-OCT-20:50 |
| November | 3077.20 | 01-NOV-07:10 | 1953.00 | 01-NOV-06:10 | 6399.12 | 01-NOV-09:09 | 14425.49 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 202.56 | 26-NOV-14:00 |
| December | 3077.20 | 01-DEC-08:09 | 1953.00 | 01-DEC-07:10 | 6399.12 | 01-DEC-10:09 | 14425.49 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 271.13 | 18-DEC-05:35 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 485.87 | 1085.00 | 6399.12 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 69.62 | ||||||
| Maximum of Months | 3077.20 | 1953.00 | 6399.12 | 14425.49 | 0.00 | 0.00 | 0.00 | 102.91 | 386.75 |
Report: PeakSpaceGainsMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 38654.47 | 02-JAN-09:09 | 2746.41 | 02-JAN-07:10 | 1999.46 | 02-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1105.87 | 25-JAN-23:00 |
| February | 38654.47 | 01-FEB-09:09 | 2746.41 | 01-FEB-07:10 | 1999.46 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1379.50 | 09-FEB-01:00 |
| March | 38654.47 | 01-MAR-09:09 | 2746.41 | 01-MAR-07:10 | 1999.46 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.13 | 22-MAR-13:00 | 1066.99 | 19-MAR-23:55 |
| April | 38654.47 | 03-APR-08:09 | 2746.41 | 03-APR-06:10 | 1999.46 | 03-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 190.64 | 29-APR-15:53 | 1150.65 | 10-APR-24:00 |
| May | 38654.47 | 01-MAY-08:09 | 2746.41 | 01-MAY-06:10 | 1999.46 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 317.29 | 14-MAY-16:00 | 581.64 | 04-MAY-01:53 |
| June | 38654.47 | 01-JUN-08:09 | 2746.41 | 01-JUN-06:10 | 1999.46 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 477.57 | 21-JUN-20:01 | 442.77 | 28-JUN-01:55 |
| July | 14241.12 | 03-JUL-16:10 | 1525.78 | 03-JUL-07:10 | 1999.46 | 03-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 394.17 | 02-JUL-21:04 | 252.48 | 18-JUL-21:00 |
| August | 14241.12 | 01-AUG-16:10 | 1525.78 | 01-AUG-07:10 | 1999.46 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 349.48 | 26-AUG-14:52 | 367.93 | 14-AUG-01:00 |
| September | 38654.47 | 05-SEP-08:09 | 2746.41 | 05-SEP-06:10 | 1999.46 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 122.79 | 10-SEP-14:52 | 237.84 | 23-SEP-16:53 |
| October | 38654.47 | 02-OCT-08:09 | 2746.41 | 02-OCT-06:10 | 1999.46 | 02-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 162.97 | 01-OCT-14:53 | 556.09 | 23-OCT-21:00 |
| November | 38654.47 | 01-NOV-08:09 | 2746.41 | 01-NOV-06:10 | 1999.46 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 697.38 | 26-NOV-09:00 |
| December | 38654.47 | 01-DEC-09:09 | 2746.41 | 01-DEC-07:10 | 1999.46 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 871.73 | 18-DEC-06:10 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 14241.12 | 1525.78 | 1999.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.84 | |||||
| Maximum of Months | 38654.47 | 2746.41 | 1999.46 | 0.00 | 0.00 | 0.00 | 0.00 | 477.57 | 1379.50 |
Report: PeakSpaceGainsMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 4896.76 | 02-JAN-08:09 | 5991.24 | 02-JAN-07:10 | 5291.26 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1259.35 | 25-JAN-23:00 |
| February | 4896.76 | 01-FEB-08:09 | 5991.24 | 01-FEB-07:10 | 5291.26 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.14 | 20-FEB-15:20 | 1581.62 | 08-FEB-21:10 |
| March | 4896.76 | 01-MAR-08:09 | 5991.24 | 01-MAR-07:10 | 5291.26 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.26 | 22-MAR-13:00 | 1226.84 | 19-MAR-23:55 |
| April | 4896.76 | 03-APR-07:10 | 5991.24 | 03-APR-06:10 | 5291.26 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.64 | 29-APR-16:00 | 1303.48 | 10-APR-24:00 |
| May | 4896.76 | 01-MAY-07:10 | 5991.24 | 01-MAY-06:10 | 5291.26 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 392.13 | 14-MAY-15:50 | 615.12 | 04-MAY-02:20 |
| June | 4896.76 | 01-JUN-07:10 | 5991.24 | 01-JUN-06:10 | 5291.26 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 531.44 | 21-JUN-20:01 | 445.95 | 28-JUN-02:10 |
| July | 773.17 | 03-JUL-07:10 | 3328.47 | 03-JUL-07:10 | 2784.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 475.17 | 02-JUL-21:10 | 281.40 | 18-JUL-21:00 |
| August | 773.17 | 01-AUG-07:10 | 3328.47 | 01-AUG-07:10 | 2784.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 403.19 | 26-AUG-14:52 | 368.24 | 14-AUG-00:30 |
| September | 4896.76 | 18-SEP-07:10 | 5991.24 | 05-SEP-06:10 | 5291.26 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.27 | 09-SEP-16:00 | 249.98 | 23-SEP-17:00 |
| October | 4896.76 | 02-OCT-07:10 | 5991.24 | 02-OCT-06:10 | 5291.26 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 221.69 | 01-OCT-15:00 | 638.32 | 23-OCT-21:00 |
| November | 4896.76 | 01-NOV-07:10 | 5991.24 | 01-NOV-06:10 | 5291.26 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 795.89 | 26-NOV-09:00 |
| December | 4896.76 | 01-DEC-08:09 | 5991.24 | 01-DEC-07:10 | 5291.26 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 984.10 | 18-DEC-05:25 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 773.17 | 3328.47 | 2784.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.98 | |||||
| Maximum of Months | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 531.44 | 1581.62 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5002.21 | 12-JAN-15:30 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.59 |
| February | 6418.65 | 19-FEB-15:57 | 0.00 | 2645.10 | 4052.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.92 |
| March | 5360.36 | 16-MAR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 |
| April | 6274.44 | 28-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 | 0.00 |
| May | 6391.28 | 19-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 0.00 |
| June | 6920.14 | 15-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 | 0.00 |
| July | 4591.59 | 03-JUL-14:30 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 | 0.00 |
| August | 5851.73 | 06-AUG-16:01 | 0.00 | 1851.57 | 2026.21 | 0.00 | 0.00 | 0.00 | 0.00 | 48.89 | 0.00 |
| September | 7445.80 | 19-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 13.23 | 0.00 |
| October | 8353.88 | 21-OCT-14:42 | 0.00 | 1322.55 | 2026.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.74 |
| November | 6432.69 | 09-NOV-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
| December | 4220.56 | 07-DEC-15:30 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.73 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4220.56 | 0.00 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 8353.88 | 3037.14 | 2645.10 | 4052.41 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 | 50.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 22828.44 | 12-JAN-14:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 |
| February | 31988.36 | 20-FEB-13:56 | 0.00 | 12744.56 | 19525.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.67 |
| March | 24292.29 | 16-MAR-14:10 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.93 |
| April | 26382.16 | 28-APR-14:03 | 87800.86 | 38815.92 | 37953.88 | 0.00 | 0.00 | 0.00 | 0.00 | 21.62 | 0.00 |
| May | 26289.83 | 19-MAY-14:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 182.35 | 0.00 |
| June | 27437.53 | 15-JUN-14:35 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 158.85 | 0.00 |
| July | 18412.19 | 15-JUL-05:51 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 18798.45 | 06-AUG-14:41 | 0.00 | 8921.19 | 9762.63 | 0.00 | 0.00 | 0.00 | 0.00 | 259.27 | 0.00 |
| September | 30202.50 | 19-SEP-14:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 51.56 | 0.00 |
| October | 30782.48 | 03-OCT-13:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 35.44 | 0.00 |
| November | 28361.88 | 10-NOV-13:20 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.62 |
| December | 19786.94 | 07-DEC-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.17 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 18412.19 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 31988.36 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 259.27 | 177.67 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2369.54 | 12-JAN-15:01 | 8246.53 | 6629.82 | 4752.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
| February | 2663.52 | 22-FEB-14:30 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 3702.62 | 16-MAR-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 |
| April | 5281.78 | 28-APR-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 | 0.00 |
| May | 5557.79 | 19-MAY-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 4.85 | 0.00 |
| June | 6154.07 | 15-JUN-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 0.00 |
| July | 4399.97 | 03-JUL-14:40 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 2.02 | 0.00 |
| August | 4529.30 | 07-AUG-14:50 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 | 0.00 |
| September | 5837.64 | 19-SEP-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 | 0.00 |
| October | 5572.78 | 03-OCT-14:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 0.00 |
| November | 4061.46 | 10-NOV-14:30 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.96 |
| December | 2296.81 | 01-DEC-15:01 | 10602.68 | 8524.05 | 6110.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.10 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2296.81 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6154.07 | 10602.68 | 8524.05 | 6110.81 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 7.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 3515.18 | 12-JAN-15:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 |
| February | 3516.36 | 23-FEB-15:02 | 15185.68 | 6713.44 | 6564.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.61 |
| March | 4028.37 | 16-MAR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 |
| April | 5516.04 | 28-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 | 0.00 |
| May | 6112.75 | 19-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 0.00 |
| June | 6794.03 | 15-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 | 0.00 |
| July | 4346.54 | 03-JUL-14:30 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 | 0.00 |
| August | 4606.08 | 07-AUG-16:00 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 | 0.00 |
| September | 6358.67 | 20-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 0.00 |
| October | 6091.12 | 05-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 | 0.00 |
| November | 4485.69 | 09-NOV-15:40 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 |
| December | 3439.33 | 01-DEC-15:01 | 27334.23 | 12084.20 | 11815.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.59 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3439.33 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6794.03 | 27334.23 | 12084.20 | 11815.83 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 | 47.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 16874.00 | 12-JAN-15:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 |
| February | 16933.75 | 23-FEB-15:02 | 73167.38 | 32346.60 | 31628.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.54 |
| March | 17761.13 | 16-MAR-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 |
| April | 22548.74 | 28-APR-14:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 | 0.00 |
| May | 24670.23 | 19-MAY-14:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 182.35 | 0.00 |
| June | 26655.33 | 15-JUN-14:35 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 158.85 | 0.00 |
| July | 18358.21 | 15-JUL-05:51 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 18221.50 | 03-AUG-03:51 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.84 |
| September | 24720.28 | 20-SEP-14:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 42.07 | 0.00 |
| October | 23769.64 | 03-OCT-14:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 39.03 | 0.00 |
| November | 18286.29 | 10-NOV-12:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.53 |
| December | 16622.49 | 01-DEC-15:01 | 131701.29 | 58223.87 | 56930.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 16622.49 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 26655.33 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 182.35 | 126.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 4967.00 | 12-JAN-15:15 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 |
| February | 5401.29 | 19-FEB-15:57 | 0.00 | 2645.10 | 4052.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.83 |
| March | 5333.86 | 16-MAR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 |
| April | 6237.67 | 28-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 | 0.00 |
| May | 6353.40 | 19-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 0.00 |
| June | 6886.24 | 15-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 | 0.00 |
| July | 4502.10 | 03-JUL-14:30 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 | 0.00 |
| August | 5338.47 | 06-AUG-16:01 | 0.00 | 1851.57 | 2026.21 | 0.00 | 0.00 | 0.00 | 0.00 | 48.91 | 0.00 |
| September | 7419.08 | 19-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 13.23 | 0.00 |
| October | 8138.14 | 21-OCT-14:42 | 0.00 | 1322.55 | 2026.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.72 |
| November | 6404.71 | 09-NOV-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
| December | 4173.63 | 07-DEC-15:30 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.73 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4173.63 | 0.00 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 8138.14 | 6074.27 | 2685.38 | 4052.41 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 | 50.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 22503.83 | 12-JAN-14:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 |
| February | 23586.93 | 22-FEB-13:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.49 |
| March | 24152.86 | 16-MAR-14:10 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.93 |
| April | 26216.18 | 28-APR-14:03 | 87800.86 | 38815.92 | 37953.88 | 0.00 | 0.00 | 0.00 | 0.00 | 21.62 | 0.00 |
| May | 26058.20 | 19-MAY-14:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 182.35 | 0.00 |
| June | 27145.34 | 15-JUN-14:25 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 153.70 | 0.00 |
| July | 18369.34 | 15-JUL-05:51 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 18639.17 | 06-AUG-14:41 | 0.00 | 8921.19 | 9762.63 | 0.00 | 0.00 | 0.00 | 0.00 | 261.87 | 0.00 |
| September | 29917.19 | 19-SEP-14:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 51.56 | 0.00 |
| October | 30290.89 | 03-OCT-13:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 35.44 | 0.00 |
| November | 27985.65 | 10-NOV-13:20 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.61 |
| December | 19349.24 | 01-DEC-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.86 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 18369.34 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 30290.89 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 261.87 | 119.86 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2360.22 | 12-JAN-15:01 | 8246.53 | 6629.82 | 4752.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
| February | 2618.71 | 22-FEB-14:30 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 3702.38 | 16-MAR-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 |
| April | 5276.20 | 28-APR-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 | 0.00 |
| May | 5546.48 | 19-MAY-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 4.85 | 0.00 |
| June | 6142.39 | 15-JUN-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 0.00 |
| July | 4348.00 | 03-JUL-14:40 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 2.02 | 0.00 |
| August | 4474.13 | 07-AUG-14:50 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 | 0.00 |
| September | 5820.68 | 19-SEP-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.98 | 0.00 |
| October | 5544.58 | 03-OCT-14:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 0.00 |
| November | 4037.32 | 10-NOV-14:30 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.96 |
| December | 2286.09 | 01-DEC-15:01 | 10602.68 | 8524.05 | 6110.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2286.09 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6142.39 | 10602.68 | 8524.05 | 6110.81 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 7.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 3516.97 | 12-JAN-15:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 |
| February | 3518.18 | 23-FEB-15:02 | 15185.68 | 6713.44 | 6564.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.60 |
| March | 4030.76 | 16-MAR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 |
| April | 5519.00 | 28-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 | 0.00 |
| May | 6115.33 | 19-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 0.00 |
| June | 6796.05 | 15-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 | 0.00 |
| July | 4350.28 | 03-JUL-14:30 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 | 0.00 |
| August | 4605.53 | 07-AUG-16:00 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 | 0.00 |
| September | 6361.87 | 20-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 0.00 |
| October | 6093.72 | 05-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 | 0.00 |
| November | 4483.86 | 09-NOV-15:40 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 |
| December | 3440.21 | 01-DEC-15:01 | 27334.23 | 12084.20 | 11815.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.58 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3440.21 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6796.05 | 27334.23 | 12084.20 | 11815.83 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 | 47.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 16876.83 | 12-JAN-15:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 |
| February | 16942.93 | 23-FEB-15:02 | 73167.38 | 32346.60 | 31628.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.53 |
| March | 17771.91 | 16-MAR-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 |
| April | 22560.50 | 28-APR-14:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 15.05 | 0.00 |
| May | 24681.20 | 19-MAY-14:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 182.35 | 0.00 |
| June | 26663.12 | 15-JUN-14:35 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 158.85 | 0.00 |
| July | 18363.10 | 15-JUL-05:51 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 18223.34 | 03-AUG-03:51 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.78 |
| September | 24731.70 | 20-SEP-14:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 42.07 | 0.00 |
| October | 23780.97 | 03-OCT-14:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 39.03 | 0.00 |
| November | 18279.88 | 03-NOV-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 16625.81 | 01-DEC-15:01 | 131701.29 | 58223.87 | 56930.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.49 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 16625.81 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 26663.12 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 182.35 | 126.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5002.75 | 12-JAN-15:15 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 |
| February | 6306.00 | 19-FEB-15:57 | 0.00 | 2645.10 | 4052.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.91 |
| March | 5350.06 | 16-MAR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 |
| April | 6246.67 | 28-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 | 0.00 |
| May | 6360.69 | 19-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 0.00 |
| June | 6892.47 | 15-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 | 0.00 |
| July | 4523.61 | 03-JUL-14:30 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 | 0.00 |
| August | 5537.13 | 06-AUG-16:01 | 0.00 | 1851.57 | 2026.21 | 0.00 | 0.00 | 0.00 | 0.00 | 48.90 | 0.00 |
| September | 7428.11 | 19-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 13.23 | 0.00 |
| October | 8215.23 | 21-OCT-14:42 | 0.00 | 1322.55 | 2026.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.73 |
| November | 6420.70 | 09-NOV-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 |
| December | 4210.56 | 07-DEC-15:30 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.73 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4210.56 | 0.00 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 8215.23 | 6074.27 | 2685.38 | 4052.41 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 | 50.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 22843.50 | 12-JAN-14:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 |
| February | 30143.68 | 20-FEB-13:56 | 0.00 | 12744.56 | 19525.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.50 |
| March | 24309.48 | 16-MAR-14:10 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.93 |
| April | 26344.98 | 28-APR-14:03 | 87800.86 | 38815.92 | 37953.88 | 0.00 | 0.00 | 0.00 | 0.00 | 21.62 | 0.00 |
| May | 26186.13 | 19-MAY-14:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 182.35 | 0.00 |
| June | 27273.26 | 15-JUN-14:25 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 153.70 | 0.00 |
| July | 18453.90 | 15-JUL-05:51 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 18732.35 | 06-AUG-14:41 | 0.00 | 8921.19 | 9762.63 | 0.00 | 0.00 | 0.00 | 0.00 | 260.35 | 0.00 |
| September | 30072.64 | 19-SEP-14:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 51.56 | 0.00 |
| October | 30453.82 | 03-OCT-13:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 35.44 | 0.00 |
| November | 28168.74 | 10-NOV-13:20 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.63 |
| December | 19730.52 | 01-DEC-13:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.53 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 18453.90 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 30453.82 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 260.35 | 176.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2385.62 | 12-JAN-15:01 | 8246.53 | 6629.82 | 4752.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
| February | 2814.05 | 22-FEB-14:30 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 3836.22 | 16-MAR-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 |
| April | 5361.56 | 28-APR-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 | 0.00 |
| May | 5620.70 | 19-MAY-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 4.85 | 0.00 |
| June | 6210.16 | 15-JUN-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 0.00 |
| July | 4545.09 | 03-JUL-14:40 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 2.02 | 0.00 |
| August | 4686.66 | 07-AUG-14:50 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 2.34 | 0.00 |
| September | 5907.75 | 19-SEP-14:50 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 0.00 |
| October | 5641.38 | 03-OCT-14:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 0.00 |
| November | 4154.45 | 10-NOV-14:30 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.96 |
| December | 2336.97 | 01-DEC-15:01 | 10602.68 | 8524.05 | 6110.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.19 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2336.97 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6210.16 | 10602.68 | 8524.05 | 6110.81 | 0.00 | 0.00 | 0.00 | 0.00 | 9.58 | 7.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 3518.40 | 12-JAN-15:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 |
| February | 3519.89 | 23-FEB-15:02 | 15185.68 | 6713.44 | 6564.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.65 |
| March | 4067.07 | 16-MAR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 |
| April | 5562.28 | 28-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 | 0.00 |
| May | 6155.39 | 19-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 32.33 | 0.00 |
| June | 6830.83 | 15-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 | 0.00 |
| July | 4445.62 | 03-JUL-14:30 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 13.57 | 0.00 |
| August | 4683.04 | 07-AUG-16:00 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 | 0.00 |
| September | 6416.45 | 20-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 0.00 |
| October | 6140.25 | 05-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 14.02 | 0.00 |
| November | 4507.58 | 09-NOV-15:40 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 |
| December | 3457.59 | 01-DEC-15:01 | 27334.23 | 12084.20 | 11815.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.83 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3457.59 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6830.83 | 27334.23 | 12084.20 | 11815.83 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 | 47.83 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 11182.33 | 12-JAN-15:01 | 67645.32 | 29905.34 | 29241.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.77 |
| February | 11200.71 | 23-FEB-15:02 | 48318.08 | 21360.96 | 20886.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 |
| March | 11922.59 | 16-MAR-14:50 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.21 |
| April | 15161.90 | 21-APR-14:50 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 143.07 | 0.00 |
| May | 16566.62 | 19-MAY-14:02 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 120.42 | 0.00 |
| June | 17878.07 | 15-JUN-15:00 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 111.81 | 0.00 |
| July | 12211.53 | 15-JUL-05:51 | 0.00 | 8416.22 | 9210.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 12114.38 | 03-AUG-03:51 | 0.00 | 8416.22 | 9210.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.61 |
| September | 16678.55 | 21-SEP-14:02 | 86972.55 | 38449.73 | 37595.83 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 | 0.00 |
| October | 16061.72 | 03-OCT-14:02 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 | 0.00 |
| November | 12261.05 | 03-NOV-15:00 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 11072.15 | 01-DEC-15:01 | 86972.55 | 38449.73 | 37595.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.24 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 11072.15 | 0.00 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 17878.07 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 143.07 | 84.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5778.72 | 12-JAN-15:01 | 34789.02 | 15379.89 | 20051.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 |
| February | 6313.60 | 23-FEB-14:40 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 |
| March | 7189.38 | 16-MAR-14:30 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 |
| April | 8688.75 | 21-APR-14:02 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 70.28 | 0.00 |
| May | 9337.92 | 19-MAY-14:02 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 61.93 | 0.00 |
| June | 9992.95 | 15-JUN-15:02 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 57.87 | 0.00 |
| July | 6777.74 | 03-JUL-14:30 | 2615.72 | 1220.63 | 1507.60 | 0.00 | 0.00 | 0.00 | 0.00 | 12.21 | 0.00 |
| August | 6560.32 | 04-AUG-14:02 | 26157.16 | 12206.26 | 15076.02 | 0.00 | 0.00 | 0.00 | 0.00 | 19.78 | 0.00 |
| September | 9421.16 | 20-SEP-14:02 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 14.29 | 0.00 |
| October | 9133.37 | 03-OCT-14:02 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 13.26 | 0.00 |
| November | 7327.08 | 10-NOV-12:40 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.11 |
| December | 5736.28 | 01-DEC-15:01 | 44728.74 | 19774.15 | 25780.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.71 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 5736.28 | 2615.72 | 1220.63 | 1507.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 9992.95 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 70.28 | 43.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5083.36 | 12-JAN-15:01 | 23451.62 | 18853.54 | 13515.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.91 |
| February | 6070.26 | 23-FEB-14:40 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 |
| March | 9459.85 | 16-MAR-15:00 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.07 |
| April | 13453.60 | 28-APR-14:50 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 2.56 | 0.00 |
| May | 17977.29 | 30-MAY-07:03 | 10050.70 | 8080.09 | 5792.54 | 0.00 | 0.00 | 0.00 | 0.00 | 2.51 | 0.00 |
| June | 18216.05 | 19-JUN-07:03 | 1586.95 | 8080.09 | 5792.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| July | 17917.35 | 03-JUL-07:03 | 1586.95 | 4488.94 | 3048.71 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 | 0.00 |
| August | 18013.36 | 07-AUG-07:03 | 1586.95 | 4488.94 | 3048.71 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 | 0.00 |
| September | 17814.25 | 18-SEP-07:02 | 16751.16 | 13466.82 | 9654.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.74 |
| October | 17756.84 | 02-OCT-07:03 | 10050.70 | 8080.09 | 5792.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.87 |
| November | 8782.20 | 10-NOV-14:10 | 6700.46 | 5386.73 | 3861.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.87 |
| December | 4950.36 | 01-DEC-15:01 | 30152.09 | 24240.27 | 17377.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.69 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4950.36 | 1586.95 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 18216.05 | 30152.09 | 24240.27 | 17377.63 | 0.00 | 0.00 | 0.00 | 0.00 | 6.84 | 20.87 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2549.18 | 01-JAN-13:52 | 0.00 | 2121.23 | 933.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.51 |
| February | 3877.38 | 21-FEB-15:00 | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 506.82 |
| March | 5487.70 | 21-MAR-15:00 | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 1241.89 | 0.00 |
| April | 12839.79 | 21-APR-15:00 | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 11785.00 | 0.00 |
| May | 14096.54 | 30-MAY-15:00 | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 14035.09 | 0.00 |
| June | 15936.84 | 15-JUN-15:00 | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 18458.81 | 0.00 |
| July | 15371.04 | 03-JUL-14:50 | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 17995.22 | 0.00 |
| August | 14764.15 | 08-AUG-15:00 | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 16700.90 | 0.00 |
| September | 13736.08 | 19-SEP-14:20 | 10492.56 | 10767.67 | 3023.58 | 0.00 | 0.00 | 0.00 | 0.00 | 13123.93 | 0.00 |
| October | 13185.55 | 03-OCT-14:20 | 8394.05 | 8614.13 | 2418.86 | 0.00 | 0.00 | 0.00 | 0.00 | 11671.99 | 0.00 |
| November | 7252.71 | 11-NOV-13:56 | 0.00 | 2121.23 | 933.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.06 |
| December | 2355.89 | 16-DEC-15:02 | 0.00 | 2545.48 | 1119.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.94 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2355.89 | 0.00 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 15936.84 | 10492.56 | 10767.67 | 3023.58 | 0.00 | 0.00 | 0.00 | 0.00 | 18458.81 | 506.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 4091.42 | 12-JAN-15:01 | 3247.06 | 25633.15 | 15595.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 4352.62 | 23-FEB-15:02 | 2319.33 | 18309.39 | 11139.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 13496.51 | 19-MAR-14:59 | 0.00 | 7213.90 | 6876.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 14623.62 | 20-APR-22:41 | 0.00 | 7213.90 | 6876.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 14653.58 | 20-MAY-02:31 | 0.00 | 7213.90 | 6876.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 14755.09 | 18-JUN-12:23 | 0.00 | 2885.56 | 2750.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 14792.82 | 15-JUL-05:51 | 0.00 | 7213.90 | 4912.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 14793.83 | 03-AUG-03:51 | 0.00 | 7213.90 | 4912.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 14716.82 | 19-SEP-21:51 | 0.00 | 7213.90 | 6876.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 14762.77 | 05-OCT-02:11 | 0.00 | 7213.90 | 6876.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 6602.85 | 11-NOV-11:41 | 0.00 | 5771.12 | 5501.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 4004.87 | 01-DEC-15:01 | 4174.79 | 32956.91 | 20051.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4004.87 | 0.00 | 2885.56 | 2750.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 14793.83 | 4174.79 | 32956.91 | 20051.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2389.05 | 12-JAN-15:01 | 8161.15 | 11595.95 | 4703.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 |
| February | 2588.60 | 23-FEB-15:02 | 5829.39 | 8282.82 | 3359.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.55 |
| March | 2735.92 | 17-MAR-14:01 | 10492.90 | 14909.08 | 6047.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.18 |
| April | 4723.81 | 30-APR-18:25 | 0.00 | 1305.37 | 829.59 | 0.00 | 0.00 | 0.00 | 0.00 | 5.42 | 0.00 |
| May | 8074.10 | 14-MAY-16:02 | 0.00 | 1958.06 | 1244.38 | 0.00 | 0.00 | 0.00 | 0.00 | 83.30 | 0.00 |
| June | 10149.85 | 03-JUN-14:41 | 0.00 | 2284.40 | 1451.77 | 0.00 | 0.00 | 0.00 | 0.00 | 83.26 | 0.00 |
| July | 10164.30 | 30-JUL-15:21 | 0.00 | 2284.40 | 1036.98 | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 0.00 |
| August | 10208.80 | 06-AUG-16:01 | 0.00 | 2284.40 | 1036.98 | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 0.00 |
| September | 8077.80 | 02-SEP-16:02 | 0.00 | 1958.06 | 1244.38 | 0.00 | 0.00 | 0.00 | 0.00 | 16.40 | 0.00 |
| October | 3420.35 | 05-OCT-15:00 | 1165.88 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 4.14 | 0.00 |
| November | 2864.60 | 10-NOV-15:01 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.06 |
| December | 2336.22 | 01-DEC-15:01 | 10492.90 | 14909.08 | 6047.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.32 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2336.22 | 0.00 | 1305.37 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 10208.80 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 83.30 | 29.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 24043.93 | 04-JAN-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.01 |
| February | 24087.52 | 24-FEB-15:01 | 24353.63 | 42294.70 | 37896.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.52 |
| March | 24335.86 | 17-MAR-14:01 | 24353.63 | 42294.70 | 37896.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.43 |
| April | 24704.91 | 17-APR-14:01 | 24353.63 | 42294.70 | 37896.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.35 |
| May | 24417.46 | 30-MAY-14:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 52.28 | 0.00 |
| June | 29387.23 | 18-JUN-12:23 | 0.00 | 3703.14 | 5198.88 | 0.00 | 0.00 | 0.00 | 0.00 | 141.10 | 0.00 |
| July | 29281.03 | 30-JUL-14:01 | 0.00 | 6480.49 | 6498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 60.72 | 0.00 |
| August | 29537.01 | 06-AUG-13:21 | 0.00 | 6480.49 | 6498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 87.24 | 0.00 |
| September | 27806.90 | 02-SEP-14:02 | 0.00 | 5554.70 | 7798.32 | 0.00 | 0.00 | 0.00 | 0.00 | 10.88 | 0.00 |
| October | 26886.74 | 09-OCT-13:19 | 0.00 | 9257.84 | 12997.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.48 |
| November | 24803.97 | 10-NOV-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.07 |
| December | 23921.77 | 01-DEC-15:01 | 24353.63 | 42294.70 | 37896.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.31 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 23921.77 | 0.00 | 3703.14 | 5198.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 29537.01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 141.10 | 111.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 11509.09 | 13-JAN-16:10 | 26290.70 | 8576.94 | 3156.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.07 |
| February | 12803.18 | 21-FEB-16:15 | 26290.70 | 8576.94 | 3156.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.06 |
| March | 26216.34 | 16-MAR-05:01 | 0.00 | 6758.63 | 3896.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.93 |
| April | 28790.17 | 03-APR-05:02 | 0.00 | 5068.97 | 2922.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.34 |
| May | 28724.57 | 22-MAY-05:01 | 0.00 | 6758.63 | 3896.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.03 |
| June | 28475.42 | 26-JUN-05:01 | 0.00 | 7603.45 | 4383.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.39 |
| July | 29574.10 | 21-JUL-05:01 | 0.00 | 8448.28 | 3479.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 |
| August | 29608.03 | 21-AUG-05:01 | 0.00 | 7603.45 | 3131.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.69 |
| September | 28908.69 | 18-SEP-05:01 | 0.00 | 7603.45 | 4383.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.89 |
| October | 28640.73 | 02-OCT-05:01 | 0.00 | 8448.28 | 4871.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 |
| November | 22685.71 | 10-NOV-06:02 | 0.00 | 4224.14 | 2435.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.36 |
| December | 10334.53 | 15-DEC-16:10 | 52581.40 | 17153.87 | 6312.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.10 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 10334.53 | 0.00 | 4224.14 | 2435.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.85 | |
| Maximum of Months | 29608.03 | 52581.40 | 17153.87 | 6312.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 81815.80 | 27-JAN-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 105.07 |
| February | 83280.46 | 03-FEB-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 8.42 |
| March | 83972.27 | 02-MAR-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 73.41 |
| April | 70226.51 | 12-APR-05:11 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 41.10 |
| May | 58680.17 | 02-MAY-04:12 | 0.00 | 2308.45 | 15357.89 | 8655.29 | 0.00 | 0.00 | 0.00 | 0.00 | 63.89 |
| June | 50649.20 | 13-JUN-05:01 | 0.00 | 2693.19 | 17917.54 | 10097.84 | 0.00 | 0.00 | 0.00 | 0.00 | 21.68 |
| July | 32692.10 | 11-JUL-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 11.67 |
| August | 39383.68 | 23-AUG-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 13.36 |
| September | 46017.39 | 25-SEP-05:01 | 0.00 | 3077.93 | 20477.18 | 11540.39 | 0.00 | 0.00 | 0.00 | 0.00 | 6.25 |
| October | 55137.26 | 31-OCT-04:12 | 0.00 | 2308.45 | 15357.89 | 8655.29 | 0.00 | 0.00 | 0.00 | 0.00 | 74.27 |
| November | 73496.49 | 21-NOV-06:11 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 87.80 |
| December | 84440.09 | 19-DEC-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 32692.10 | 0.00 | 2308.45 | 15357.89 | 8655.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 84440.09 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 105.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 33131.81 | 27-JAN-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127.87 |
| February | 31941.03 | 10-FEB-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.63 |
| March | 29864.63 | 02-MAR-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.80 |
| April | 91945.51 | 21-APR-05:02 | 0.00 | 3246.26 | 4798.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.99 |
| May | 96703.25 | 01-MAY-05:01 | 0.00 | 3787.30 | 5598.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.99 |
| June | 96681.05 | 13-JUN-05:01 | 0.00 | 3787.30 | 5598.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.74 |
| July | 61002.74 | 11-JUL-05:01 | 0.00 | 5410.43 | 7997.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.02 |
| August | 71762.68 | 23-AUG-05:01 | 0.00 | 5410.43 | 7997.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.20 |
| September | 80220.69 | 25-SEP-05:01 | 0.00 | 4328.34 | 6398.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.06 |
| October | 75598.59 | 23-OCT-05:01 | 0.00 | 3787.30 | 5598.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.02 |
| November | 25883.10 | 10-NOV-12:30 | 38654.47 | 2746.41 | 1999.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.59 |
| December | 32067.61 | 27-DEC-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.85 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 25883.10 | 0.00 | 2746.41 | 1999.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.06 | |
| Maximum of Months | 96703.25 | 38654.47 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 9456.36 | 12-JAN-15:03 | 34277.32 | 41938.67 | 37038.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.39 |
| February | 11532.03 | 23-FEB-14:40 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.35 |
| March | 14111.76 | 16-MAR-14:00 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.78 |
| April | 18081.61 | 28-APR-14:03 | 29380.56 | 35947.43 | 31747.59 | 0.00 | 0.00 | 0.00 | 0.00 | 16.32 | 0.00 |
| May | 26617.95 | 15-MAY-07:03 | 19587.04 | 23964.96 | 21165.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.79 |
| June | 32082.52 | 18-JUN-12:23 | 0.00 | 4721.10 | 6532.98 | 0.00 | 0.00 | 0.00 | 0.00 | 138.65 | 0.00 |
| July | 27372.76 | 16-JUL-10:49 | 0.00 | 10622.47 | 10499.44 | 0.00 | 0.00 | 0.00 | 0.00 | 68.40 | 0.00 |
| August | 27555.68 | 06-AUG-14:41 | 0.00 | 8261.92 | 8166.23 | 0.00 | 0.00 | 0.00 | 0.00 | 170.36 | 0.00 |
| September | 27155.41 | 18-SEP-07:02 | 24483.80 | 29956.19 | 26456.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.87 |
| October | 25876.06 | 02-OCT-07:03 | 14690.28 | 17973.72 | 15873.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 |
| November | 14893.37 | 10-NOV-08:62 | 29380.56 | 35947.43 | 31747.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.68 |
| December | 9070.23 | 01-DEC-13:30 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.98 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 9070.23 | 0.00 | 4721.10 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 32082.52 | 34277.32 | 41938.67 | 37038.85 | 0.00 | 0.00 | 0.00 | 0.00 | 170.36 | 122.68 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.257127E+12 | 232916.81 | 03-JAN-14:20 | 0.719871E+11 | 338578.64 | 27-JAN-08:09 |
| February | 0.237856E+12 | 252688.46 | 22-FEB-13:00 | 0.591485E+11 | 326654.58 | 03-FEB-08:09 |
| March | 0.290352E+12 | 281457.42 | 22-MAR-12:00 | 0.584119E+11 | 290302.37 | 02-MAR-08:09 |
| April | 0.317553E+12 | 321605.84 | 21-APR-13:00 | 0.442014E+11 | 120108.57 | 11-APR-07:10 |
| May | 0.394170E+12 | 351215.79 | 19-MAY-13:00 | 0.455494E+11 | 71613.84 | 01-MAY-11:39 |
| June | 0.433081E+12 | 386685.11 | 15-JUN-14:00 | 0.395492E+11 | 70047.98 | 01-JUN-11:39 |
| July | 0.321252E+12 | 259074.03 | 03-JUL-14:09 | 0.333966E+11 | 51567.11 | 05-JUL-09:20 |
| August | 0.312284E+12 | 253376.64 | 07-AUG-15:00 | 0.363207E+11 | 51567.76 | 31-AUG-09:20 |
| September | 0.376679E+12 | 357307.98 | 20-SEP-13:00 | 0.374229E+11 | 70075.57 | 29-SEP-11:00 |
| October | 0.337430E+12 | 365789.22 | 03-OCT-13:00 | 0.447535E+11 | 86096.89 | 24-OCT-11:09 |
| November | 0.271694E+12 | 289060.36 | 09-NOV-13:00 | 0.530577E+11 | 228440.66 | 28-NOV-08:09 |
| December | 0.249111E+12 | 206899.78 | 08-DEC-14:09 | 0.864842E+11 | 375612.72 | 27-DEC-08:09 |
| Annual Sum or Average | 0.379859E+13 | 0.610283E+12 | ||||
| Minimum of Months | 0.237856E+12 | 206899.78 | 0.333966E+11 | 51567.11 | ||
| Maximum of Months | 0.433081E+12 | 386685.11 | 0.864842E+11 | 375612.72 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 0.109593E+12 | 0.910845E+10 | 0.102892E+12 | 0.158194E+10 | 0.275094E+11 | 48656199.57 | 0.00 | 0.259311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.990914E+11 | 0.779208E+10 | 0.929862E+11 | 0.142979E+10 | 0.259770E+11 | 35421212.67 | 0.00 | 0.712311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.116033E+12 | 0.800794E+10 | 0.106107E+12 | 0.164017E+10 | 0.344945E+11 | 30713392.73 | 0.00 | 0.202568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.105019E+12 | 0.712682E+10 | 0.990538E+11 | 0.152152E+10 | 0.426580E+11 | 17304922.02 | 0.00 | 0.584953E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.112813E+12 | 0.682957E+10 | 0.104499E+12 | 0.161106E+10 | 0.556842E+11 | 14394506.04 | 0.00 | 0.108916E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.111459E+12 | 0.634124E+10 | 0.102249E+12 | 0.157960E+10 | 0.580686E+11 | 12864579.54 | 0.00 | 0.149677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.666242E+11 | 0.667033E+10 | 0.693246E+11 | 0.102075E+10 | 0.439635E+11 | 11634190.35 | 0.00 | 0.129871E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.703211E+11 | 0.712682E+10 | 0.716606E+11 | 0.104481E+10 | 0.442354E+11 | 13536054.16 | 0.00 | 0.114129E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.103032E+12 | 0.747360E+10 | 0.977493E+11 | 0.149702E+10 | 0.503259E+11 | 12703821.23 | 0.00 | 0.112883E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.109593E+12 | 0.837242E+10 | 0.102892E+12 | 0.158194E+10 | 0.470749E+11 | 16828553.35 | 0.00 | 0.640865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.108239E+12 | 0.864489E+10 | 0.100662E+12 | 0.155064E+10 | 0.338113E+11 | 27357966.30 | 0.00 | 0.150907E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.106374E+12 | 0.924292E+10 | 0.101284E+12 | 0.155283E+10 | 0.260584E+11 | 59585184.63 | 0.00 | 0.736692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.121819E+13 | 0.927371E+11 | 0.115136E+13 | 0.176121E+11 | 0.489861E+12 | 0.301001E+09 | 0.00 | 0.783859E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.666242E+11 | 0.634124E+10 | 0.693246E+11 | 0.102075E+10 | 0.259770E+11 | 11634190.35 | 0.00 | 0.736692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.116033E+12 | 0.924292E+10 | 0.106107E+12 | 0.164017E+10 | 0.580686E+11 | 59585184.63 | 0.00 | 0.149677E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.303281E+11 | 0.00 | 0.262917E+11 | 0.00 | 0.153672E+11 | 0.00 | 0.00 |
| February | 0.274200E+11 | 0.00 | 0.178557E+11 | 0.00 | 0.138728E+11 | 0.00 | 0.00 |
| March | 0.319900E+11 | 0.00 | 0.102180E+11 | 0.00 | 0.162039E+11 | 0.00 | 0.00 |
| April | 0.290818E+11 | 0.00 | 0.156270E+10 | 0.00 | 0.135569E+11 | 0.00 | 0.00 |
| May | 0.311591E+11 | 0.00 | 0.358997E+09 | 0.00 | 0.140314E+11 | 0.00 | 0.00 |
| June | 0.307436E+11 | 0.00 | 26014677.61 | 0.00 | 0.877958E+10 | 0.00 | 0.00 |
| July | 0.294972E+11 | 0.00 | 10444064.17 | 0.00 | 0.388889E+10 | 0.00 | 0.00 |
| August | 0.319900E+11 | 0.00 | 43911885.46 | 0.00 | 0.428684E+10 | 0.00 | 0.00 |
| September | 0.290818E+11 | 0.00 | 0.230769E+09 | 0.00 | 0.811038E+10 | 0.00 | 0.00 |
| October | 0.303281E+11 | 0.00 | 0.976337E+09 | 0.00 | 0.134490E+11 | 0.00 | 0.00 |
| November | 0.299127E+11 | 0.00 | 0.893045E+10 | 0.00 | 0.142146E+11 | 0.00 | 0.00 |
| December | 0.294972E+11 | 0.00 | 0.426521E+11 | 0.00 | 0.143349E+11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.361030E+12 | 0.00 | 0.109157E+12 | 0.00 | 0.140096E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.274200E+11 | 0.00 | 10444064.17 | 0.00 | 0.388889E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.319900E+11 | 0.00 | 0.426521E+11 | 0.00 | 0.162039E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 79557.27 | 02-JAN-07:10 | 5897.73 | 01-JAN-00:10 | 76813.98 | 02-JAN-10:09 | 1336.02 | 02-JAN-10:09 | 35898.33 | 12-JAN-15:30 | 319.87 | 30-JAN-07:10 | 0.00 | 01-JAN-00:10 |
| February | 79557.27 | 01-FEB-07:10 | 5897.73 | 01-FEB-00:10 | 76813.98 | 01-FEB-10:09 | 1336.02 | 01-FEB-10:09 | 42177.43 | 22-FEB-13:00 | 315.77 | 03-FEB-07:10 | 0.00 | 01-FEB-00:10 |
| March | 79557.27 | 01-MAR-07:10 | 5897.73 | 01-MAR-00:10 | 76813.98 | 01-MAR-10:09 | 1336.02 | 01-MAR-10:09 | 50967.65 | 16-MAR-14:30 | 257.18 | 02-MAR-07:10 | 0.00 | 01-MAR-00:10 |
| April | 79557.27 | 03-APR-06:10 | 5897.73 | 01-APR-00:10 | 76813.98 | 03-APR-09:09 | 1336.02 | 03-APR-09:09 | 62634.05 | 27-APR-12:00 | 109.03 | 12-APR-07:10 | 0.00 | 01-APR-00:10 |
| May | 79557.27 | 01-MAY-06:10 | 5897.73 | 01-MAY-00:10 | 76813.98 | 01-MAY-09:09 | 1336.02 | 01-MAY-09:09 | 63149.56 | 12-MAY-12:30 | 69.96 | 01-MAY-06:00 | 0.00 | 01-MAY-00:10 |
| June | 79557.27 | 01-JUN-06:10 | 5897.73 | 01-JUN-00:10 | 76813.98 | 01-JUN-09:09 | 1336.02 | 01-JUN-09:09 | 55177.18 | 15-JUN-14:50 | 52.93 | 29-JUN-06:19 | 0.00 | 01-JUN-00:10 |
| July | 44198.48 | 03-JUL-07:10 | 5897.73 | 01-JUL-00:10 | 45977.32 | 03-JUL-09:09 | 606.14 | 03-JUL-09:09 | 34974.42 | 24-JUL-11:30 | 13.47 | 03-JUL-14:09 | 0.00 | 01-JUL-00:10 |
| August | 44198.48 | 01-AUG-07:10 | 5897.73 | 01-AUG-00:10 | 45977.32 | 01-AUG-09:09 | 606.14 | 01-AUG-09:09 | 36478.39 | 31-AUG-13:00 | 69.72 | 31-AUG-06:19 | 0.00 | 01-AUG-00:10 |
| September | 79557.27 | 05-SEP-06:10 | 5897.73 | 01-SEP-00:10 | 76813.98 | 05-SEP-09:09 | 1336.02 | 05-SEP-09:09 | 63057.31 | 26-SEP-12:30 | 69.96 | 28-SEP-06:00 | 0.00 | 01-SEP-00:10 |
| October | 79557.27 | 02-OCT-06:10 | 5897.73 | 01-OCT-00:10 | 76813.98 | 02-OCT-09:09 | 1336.02 | 02-OCT-09:09 | 62194.55 | 19-OCT-12:30 | 83.47 | 06-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 79557.27 | 01-NOV-06:10 | 5897.73 | 01-NOV-00:10 | 76813.98 | 01-NOV-09:09 | 1336.02 | 01-NOV-09:09 | 55333.28 | 03-NOV-14:00 | 202.98 | 28-NOV-07:10 | 0.00 | 01-NOV-00:10 |
| December | 79557.27 | 01-DEC-07:10 | 5897.73 | 01-DEC-00:10 | 76813.98 | 01-DEC-10:09 | 1336.02 | 01-DEC-10:09 | 31934.95 | 01-DEC-13:00 | 490.95 | 27-DEC-07:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | ||||||||||||||
| Minimum of Months | 44198.48 | 5897.73 | 45977.32 | 606.14 | 31934.95 | 13.47 | 0.00 | |||||||
| Maximum of Months | 79557.27 | 5897.73 | 76813.98 | 1336.02 | 63149.56 | 490.95 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 45030.19 | 03-JAN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 58759.56 | 21-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 79038.21 | 22-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 123126.18 | 21-APR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 148284.73 | 19-MAY-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 178587.35 | 15-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 139553.43 | 03-JUL-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 134081.84 | 07-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 150431.89 | 20-SEP-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 160445.98 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 79400.30 | 09-NOV-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 24007.77 | 08-DEC-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 24007.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 178587.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 232916.81 | 03-JAN-14:20 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 32925.03 | 13.47 | 0.00 | 45030.19 | 0.00 |
| February | 252688.46 | 22-FEB-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 42177.43 | 13.47 | 0.00 | 55559.58 | 0.00 |
| March | 281457.42 | 22-MAR-12:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 47447.91 | 13.47 | 0.00 | 79038.21 | 0.00 |
| April | 321605.84 | 21-APR-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 43498.05 | 13.47 | 0.00 | 123126.18 | 0.00 |
| May | 351215.79 | 19-MAY-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 47947.64 | 13.47 | 0.00 | 148284.73 | 0.00 |
| June | 386685.11 | 15-JUN-14:00 | 79557.27 | 70814.97 | 0.00 | 1156.20 | 55176.36 | 13.47 | 0.00 | 178587.35 | 0.00 |
| July | 259074.03 | 03-JUL-14:09 | 44198.48 | 39978.30 | 0.00 | 518.12 | 33496.96 | 13.47 | 0.00 | 139553.43 | 0.00 |
| August | 253376.64 | 07-AUG-15:00 | 44198.48 | 39978.30 | 0.00 | 518.12 | 33316.96 | 13.47 | 0.00 | 134081.84 | 0.00 |
| September | 357307.98 | 20-SEP-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 51892.17 | 13.47 | 0.00 | 150431.89 | 0.00 |
| October | 365789.22 | 03-OCT-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 50358.28 | 13.47 | 0.00 | 160445.98 | 0.00 |
| November | 289060.36 | 09-NOV-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 54695.38 | 13.47 | 0.00 | 79400.30 | 0.00 |
| December | 206899.78 | 08-DEC-14:09 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 27932.07 | 13.47 | 0.00 | 24007.77 | 0.00 |
| Annual Sum or Average | 0.00 | ||||||||||
| Minimum of Months | 206899.78 | 44198.48 | 39978.30 | 0.00 | 518.12 | 27932.07 | 13.47 | 0.00 | 24007.77 | 0.00 | |
| Maximum of Months | 386685.11 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 55176.36 | 13.47 | 0.00 | 178587.35 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
| January | 48084.96 | 02-JAN-10:09 | 0.00 | 291148.06 | 27-JAN-08:09 | 0.00 | 27385.87 | 30-JAN-13:39 | 0.00 |
| February | 48084.96 | 01-FEB-10:09 | 0.00 | 279225.86 | 03-FEB-08:09 | 0.00 | 27353.60 | 03-FEB-13:39 | 0.00 |
| March | 48084.96 | 01-MAR-10:09 | 0.00 | 243626.63 | 02-MAR-08:09 | 0.00 | 26842.64 | 01-MAR-13:00 | 0.00 |
| April | 48084.96 | 03-APR-09:09 | 0.00 | 73510.29 | 11-APR-07:10 | 0.00 | 25507.90 | 03-APR-12:20 | 0.00 |
| May | 48084.96 | 01-MAY-09:09 | 0.00 | 15474.67 | 04-MAY-06:19 | 0.00 | 24178.97 | 01-MAY-12:39 | 0.00 |
| June | 48084.96 | 01-JUN-09:09 | 0.00 | 12696.01 | 29-JUN-06:19 | 0.00 | 22874.02 | 01-JUN-12:00 | 0.00 |
| July | 48084.96 | 03-JUL-09:09 | 0.00 | 9102.45 | 11-JUL-05:49 | 0.00 | 7443.35 | 03-JUL-18:40 | 0.00 |
| August | 48084.96 | 01-AUG-09:09 | 0.00 | 18027.77 | 31-AUG-06:19 | 0.00 | 7452.16 | 31-AUG-18:49 | 0.00 |
| September | 48084.96 | 01-SEP-09:09 | 0.00 | 17442.12 | 12-SEP-06:19 | 0.00 | 22867.42 | 29-SEP-12:39 | 0.00 |
| October | 48084.96 | 02-OCT-09:09 | 0.00 | 31122.91 | 25-OCT-07:10 | 0.00 | 24306.09 | 31-OCT-12:39 | 0.00 |
| November | 48084.96 | 01-NOV-09:09 | 0.00 | 181820.39 | 28-NOV-08:09 | 0.00 | 25926.37 | 30-NOV-13:39 | 0.00 |
| December | 48084.96 | 01-DEC-10:09 | 0.00 | 328211.54 | 27-DEC-08:09 | 0.00 | 26830.76 | 29-DEC-13:39 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 48084.96 | 0.00 | 9102.45 | 0.00 | 7443.35 | 0.00 | |||
| Maximum of Months | 48084.96 | 0.00 | 328211.54 | 0.00 | 27385.87 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.00 | 27.30 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.35 | 0.00 | 27.35 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.53 | 0.00 | 27.53 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 2.67 | 27.41 | 0.00 | 27.41 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.53 | 0.00 | 27.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.00 | 27.30 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.33 | 27.30 | 0.00 | 27.30 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.00 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.34 | 0.00 | 27.34 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.64 | 0.00 | 27.64 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 1.33 | 27.49 | 0.00 | 27.49 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.64 | 0.00 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.00 | 27.27 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.35 | 0.00 | 27.35 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.65 | 0.00 | 27.65 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 1.83 | 27.45 | 0.00 | 27.45 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.65 | 0.00 | 27.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.00 | 27.31 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.17 | 27.31 | 0.00 | 27.31 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.00 | 27.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 58.67 | 15.80 | 37.67 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
| February | 45.50 | 15.77 | 27.00 | 16.73 | 0.00 | 16.73 | 0.00 | 16.73 |
| March | 40.67 | 15.79 | 18.33 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
| April | 14.00 | 16.78 | 1.17 | 16.93 | 10.50 | 20.59 | 10.50 | 22.13 |
| May | 3.33 | 18.54 | 0.00 | 18.54 | 23.33 | 25.62 | 23.33 | 26.09 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 66.67 | 26.51 | 66.67 | 26.51 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 | 27.17 | 30.50 | 27.17 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 30.67 | 27.00 | 28.50 | 26.99 |
| September | 2.67 | 18.47 | 0.00 | 18.47 | 37.83 | 25.79 | 33.50 | 25.96 |
| October | 15.00 | 17.66 | 1.67 | 17.86 | 10.67 | 21.15 | 8.50 | 22.30 |
| November | 31.67 | 15.87 | 12.83 | 16.64 | 0.00 | 16.64 | 0.00 | 16.64 |
| December | 69.83 | 15.97 | 50.00 | 16.89 | 0.00 | 16.89 | 0.00 | 16.89 |
| Annual Sum or Average | 281.33 | 16.05 | 148.67 | 16.86 | 210.67 | 20.07 | 201.50 | 21.62 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.64 | 0.00 | 16.64 |
| Maximum of Months | 69.83 | 18.54 | 50.00 | 18.54 | 66.67 | 27.17 | 66.67 | 27.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.00 | 27.30 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 27.31 | 0.00 | 27.31 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.38 | 0.00 | 27.38 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.34 | 0.00 | 27.34 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.32 | 0.00 | 27.32 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.28 | 0.00 | 27.28 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.28 | 0.00 | 27.28 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 30.83 | 27.34 | 0.00 | 27.34 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 27.38 | 0.00 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.35 | 0.00 | 27.35 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.42 | 0.00 | 27.42 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 27.41 | 0.00 | 27.41 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 27.40 | 0.00 | 27.40 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.30 | 0.00 | 27.30 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 25.17 | 27.40 | 0.00 | 27.40 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.42 | 0.00 | 27.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.38 | 0.00 | 27.38 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.39 | 0.00 | 27.39 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.42 | 0.00 | 27.42 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 27.44 | 0.00 | 27.44 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.42 | 0.00 | 27.42 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 26.50 | 27.41 | 0.00 | 27.41 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 27.44 | 0.00 | 27.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.00 | 27.34 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.61 | 0.00 | 24.61 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.76 | 0.00 | 24.76 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.89 | 0.00 | 24.89 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.76 | 0.00 | 24.76 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 1.33 | 25.10 | 0.00 | 25.10 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.34 | 0.00 | 27.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 50.33 | 27.30 | 0.00 | 27.30 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 55.67 | 27.43 | 0.00 | 27.43 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 73.17 | 27.50 | 0.00 | 27.50 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 27.75 | 0.00 | 27.75 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 100.67 | 27.89 | 0.00 | 27.89 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 98.33 | 27.97 | 0.00 | 27.97 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 110.83 | 28.06 | 0.00 | 28.06 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 98.00 | 27.97 | 0.00 | 27.97 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 103.50 | 27.96 | 0.00 | 27.96 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 105.67 | 27.76 | 0.00 | 27.76 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 69.33 | 27.48 | 0.00 | 27.48 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 | 27.35 | 0.00 | 27.35 |
| Annual Sum or Average | 0.00 | 0.00 | 1011.50 | 27.77 | 0.00 | 27.77 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 46.83 | 27.30 | 0.00 | 27.30 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 110.83 | 28.06 | 0.00 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.33 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
| February | 1.00 | 20.16 | 0.00 | 20.16 | 0.00 | 20.16 | 0.00 | 20.16 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.32 | 0.00 | 27.32 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 27.27 | 0.00 | 27.27 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 27.23 | 0.00 | 27.23 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 27.30 | 0.00 | 27.30 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 20.50 | 27.26 | 0.00 | 27.26 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 17.00 | 27.09 | 0.00 | 27.09 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 26.31 | 0.00 | 26.31 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1.50 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 | 0.00 | 20.21 |
| Annual Sum or Average | 2.83 | 20.20 | 0.00 | 20.20 | 109.17 | 27.05 | 0.00 | 27.05 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1.50 | 20.27 | 0.00 | 20.27 | 29.33 | 27.32 | 0.00 | 27.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.36 | 0.00 | 27.36 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.37 | 0.00 | 27.37 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.36 | 0.00 | 27.36 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 7.83 | 27.36 | 0.00 | 27.36 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.37 | 0.00 | 27.37 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 217.50 | 22.68 | 11.17 | 22.65 | 7.50 | 22.60 |
| February | 197.17 | 22.77 | 4.83 | 22.73 | 4.83 | 22.70 |
| March | 194.33 | 23.04 | 3.83 | 23.01 | 3.83 | 22.97 |
| April | 77.17 | 23.39 | 75.33 | 23.69 | 0.00 | 23.69 |
| May | 35.83 | 23.68 | 185.83 | 23.94 | 11.67 | 23.95 |
| June | 8.50 | 23.23 | 245.17 | 23.96 | 0.00 | 23.96 |
| July | 34.50 | 23.11 | 235.83 | 23.73 | 27.00 | 23.69 |
| August | 27.50 | 22.63 | 246.33 | 23.75 | 2.50 | 23.75 |
| September | 11.50 | 23.76 | 239.67 | 23.98 | 8.00 | 23.98 |
| October | 22.33 | 23.62 | 199.67 | 23.95 | 6.83 | 23.96 |
| November | 122.67 | 22.88 | 57.00 | 23.22 | 0.67 | 23.22 |
| December | 220.50 | 22.62 | 15.17 | 22.52 | 15.17 | 22.44 |
| Annual Sum or Average | 1169.50 | 22.89 | 1519.83 | 23.45 | 88.00 | 23.43 |
| Minimum of Months | 8.50 | 22.62 | 3.83 | 22.52 | 0.00 | 22.44 |
| Maximum of Months | 220.50 | 23.76 | 246.33 | 23.98 | 27.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 186.00 | 22.90 | 9.17 | 22.94 | 0.50 | 22.94 |
| February | 150.17 | 22.88 | 2.50 | 22.89 | 0.50 | 22.89 |
| March | 163.83 | 23.17 | 0.33 | 23.17 | 0.33 | 23.17 |
| April | 70.33 | 23.40 | 79.00 | 23.72 | 0.00 | 23.72 |
| May | 35.50 | 23.64 | 172.17 | 23.92 | 11.67 | 23.93 |
| June | 8.00 | 23.14 | 229.17 | 23.93 | 0.00 | 23.93 |
| July | 47.00 | 22.67 | 200.83 | 23.26 | 21.67 | 23.22 |
| August | 48.67 | 22.54 | 203.50 | 23.45 | 1.50 | 23.44 |
| September | 11.83 | 23.76 | 235.33 | 23.96 | 8.50 | 23.96 |
| October | 17.83 | 23.71 | 205.50 | 23.97 | 7.67 | 23.97 |
| November | 104.33 | 23.05 | 67.83 | 23.42 | 0.00 | 23.42 |
| December | 187.00 | 22.78 | 1.83 | 22.77 | 1.83 | 22.75 |
| Annual Sum or Average | 1030.50 | 22.99 | 1407.17 | 23.48 | 54.17 | 23.48 |
| Minimum of Months | 8.00 | 22.54 | 0.33 | 22.77 | 0.00 | 22.75 |
| Maximum of Months | 187.00 | 23.76 | 235.33 | 23.97 | 21.67 | 23.97 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 22.36 | 11.67 | 22.30 | 11.67 | 22.25 |
| February | 247.00 | 22.79 | 5.50 | 22.75 | 5.50 | 22.71 |
| March | 298.00 | 23.40 | 1.67 | 23.38 | 1.67 | 23.37 |
| April | 121.83 | 23.80 | 15.50 | 23.83 | 0.00 | 23.83 |
| May | 40.33 | 23.90 | 91.50 | 23.97 | 0.00 | 23.97 |
| June | 7.67 | 23.95 | 156.50 | 24.00 | 0.00 | 24.00 |
| July | 1.67 | 23.36 | 234.17 | 23.97 | 0.00 | 23.97 |
| August | 17.33 | 23.27 | 222.33 | 23.93 | 0.00 | 23.93 |
| September | 6.00 | 23.81 | 200.17 | 23.99 | 1.50 | 23.99 |
| October | 43.50 | 23.87 | 114.33 | 23.96 | 1.00 | 23.96 |
| November | 217.00 | 23.23 | 7.33 | 23.25 | 0.33 | 23.24 |
| December | 260.00 | 22.15 | 25.83 | 22.05 | 25.83 | 21.96 |
| Annual Sum or Average | 1533.33 | 22.94 | 1086.50 | 23.32 | 47.50 | 23.29 |
| Minimum of Months | 1.67 | 22.15 | 1.67 | 22.05 | 0.00 | 21.96 |
| Maximum of Months | 298.00 | 23.95 | 234.17 | 24.00 | 25.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.92 | 56.33 | 21.77 | 56.33 | 21.67 |
| February | 247.00 | 22.20 | 36.67 | 22.05 | 36.67 | 21.94 |
| March | 285.00 | 22.82 | 15.67 | 22.74 | 15.67 | 22.66 |
| April | 108.00 | 23.34 | 47.83 | 23.54 | 0.17 | 23.54 |
| May | 38.67 | 23.67 | 182.00 | 23.94 | 12.00 | 23.94 |
| June | 6.00 | 23.26 | 249.83 | 23.97 | 0.00 | 23.97 |
| July | 32.50 | 23.12 | 238.50 | 23.72 | 26.67 | 23.68 |
| August | 39.17 | 22.57 | 226.67 | 23.63 | 2.33 | 23.62 |
| September | 19.50 | 23.55 | 225.00 | 23.94 | 9.67 | 23.94 |
| October | 67.00 | 23.43 | 137.17 | 23.80 | 13.50 | 23.81 |
| November | 220.17 | 22.69 | 31.67 | 22.77 | 7.67 | 22.72 |
| December | 260.00 | 21.85 | 71.67 | 21.68 | 71.67 | 21.57 |
| Annual Sum or Average | 1596.00 | 22.49 | 1519.00 | 23.01 | 252.33 | 22.92 |
| Minimum of Months | 6.00 | 21.85 | 15.67 | 21.68 | 0.00 | 21.57 |
| Maximum of Months | 285.00 | 23.67 | 249.83 | 23.97 | 71.67 | 23.97 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 22.22 | 25.67 | 22.13 | 25.67 | 22.05 |
| February | 247.00 | 22.54 | 13.67 | 22.47 | 13.67 | 22.40 |
| March | 274.33 | 23.02 | 3.33 | 22.99 | 3.33 | 22.97 |
| April | 106.83 | 23.33 | 44.17 | 23.52 | 0.00 | 23.52 |
| May | 40.00 | 23.62 | 164.33 | 23.91 | 13.17 | 23.91 |
| June | 6.00 | 23.20 | 234.67 | 23.94 | 0.00 | 23.94 |
| July | 47.50 | 22.63 | 187.33 | 23.12 | 21.00 | 23.09 |
| August | 89.00 | 22.48 | 115.00 | 22.92 | 1.33 | 22.91 |
| September | 25.83 | 23.41 | 205.33 | 23.84 | 10.33 | 23.85 |
| October | 74.33 | 23.34 | 130.00 | 23.72 | 14.00 | 23.74 |
| November | 218.17 | 22.86 | 26.83 | 22.98 | 0.50 | 22.97 |
| December | 260.00 | 22.13 | 40.33 | 21.99 | 40.33 | 21.88 |
| Annual Sum or Average | 1662.00 | 22.67 | 1190.67 | 23.05 | 143.33 | 23.00 |
| Minimum of Months | 6.00 | 22.13 | 3.33 | 21.99 | 0.00 | 21.88 |
| Maximum of Months | 274.33 | 23.62 | 234.67 | 23.94 | 40.33 | 23.94 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 219.50 | 22.67 | 10.50 | 22.64 | 7.50 | 22.60 |
| February | 199.50 | 22.78 | 4.83 | 22.74 | 4.83 | 22.70 |
| March | 195.67 | 23.05 | 3.83 | 23.01 | 3.83 | 22.98 |
| April | 78.00 | 23.39 | 73.67 | 23.69 | 0.00 | 23.69 |
| May | 36.33 | 23.68 | 185.50 | 23.94 | 11.67 | 23.95 |
| June | 8.67 | 23.22 | 244.17 | 23.96 | 0.00 | 23.96 |
| July | 35.33 | 23.06 | 234.83 | 23.71 | 26.83 | 23.67 |
| August | 28.83 | 22.60 | 244.00 | 23.73 | 2.33 | 23.73 |
| September | 11.67 | 23.75 | 239.33 | 23.98 | 8.00 | 23.98 |
| October | 22.50 | 23.62 | 198.83 | 23.95 | 6.83 | 23.96 |
| November | 123.17 | 22.87 | 56.17 | 23.21 | 0.83 | 23.20 |
| December | 222.67 | 22.61 | 15.50 | 22.51 | 15.50 | 22.42 |
| Annual Sum or Average | 1181.83 | 22.88 | 1511.17 | 23.44 | 88.17 | 23.42 |
| Minimum of Months | 8.67 | 22.60 | 3.83 | 22.51 | 0.00 | 22.42 |
| Maximum of Months | 222.67 | 23.75 | 244.17 | 23.98 | 26.83 | 23.98 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 191.33 | 22.89 | 7.50 | 22.92 | 0.50 | 22.92 |
| February | 152.67 | 22.89 | 1.83 | 22.90 | 0.33 | 22.90 |
| March | 163.33 | 23.18 | 0.17 | 23.18 | 0.17 | 23.18 |
| April | 70.50 | 23.41 | 77.67 | 23.72 | 0.00 | 23.72 |
| May | 36.17 | 23.65 | 170.50 | 23.92 | 11.83 | 23.92 |
| June | 8.33 | 23.13 | 226.17 | 23.93 | 0.00 | 23.93 |
| July | 50.50 | 22.62 | 191.33 | 23.18 | 20.83 | 23.14 |
| August | 54.67 | 22.53 | 190.83 | 23.37 | 1.33 | 23.37 |
| September | 11.83 | 23.75 | 235.33 | 23.96 | 8.50 | 23.96 |
| October | 18.83 | 23.71 | 203.50 | 23.96 | 8.17 | 23.97 |
| November | 108.00 | 23.04 | 62.50 | 23.39 | 0.00 | 23.39 |
| December | 193.50 | 22.77 | 1.83 | 22.75 | 1.83 | 22.74 |
| Annual Sum or Average | 1059.67 | 22.98 | 1369.17 | 23.46 | 53.50 | 23.46 |
| Minimum of Months | 8.33 | 22.53 | 0.17 | 22.75 | 0.00 | 22.74 |
| Maximum of Months | 193.50 | 23.75 | 235.33 | 23.96 | 20.83 | 23.97 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 22.34 | 11.83 | 22.28 | 11.83 | 22.23 |
| February | 247.00 | 22.78 | 5.83 | 22.74 | 5.83 | 22.70 |
| March | 298.00 | 23.40 | 1.67 | 23.39 | 1.67 | 23.38 |
| April | 122.00 | 23.81 | 15.33 | 23.83 | 0.00 | 23.83 |
| May | 40.50 | 23.90 | 91.17 | 23.97 | 0.00 | 23.97 |
| June | 7.67 | 23.95 | 155.33 | 24.00 | 0.00 | 24.00 |
| July | 1.83 | 23.34 | 232.33 | 23.96 | 0.00 | 23.96 |
| August | 18.33 | 23.26 | 220.17 | 23.92 | 0.00 | 23.92 |
| September | 6.00 | 23.80 | 199.50 | 23.99 | 1.50 | 23.99 |
| October | 44.33 | 23.87 | 114.33 | 23.96 | 1.00 | 23.96 |
| November | 218.33 | 23.22 | 7.67 | 23.23 | 0.67 | 23.23 |
| December | 260.00 | 22.13 | 27.17 | 22.02 | 27.17 | 21.93 |
| Annual Sum or Average | 1537.00 | 22.93 | 1082.33 | 23.31 | 49.67 | 23.28 |
| Minimum of Months | 1.83 | 22.13 | 1.67 | 22.02 | 0.00 | 21.93 |
| Maximum of Months | 298.00 | 23.95 | 232.33 | 24.00 | 27.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.92 | 57.17 | 21.77 | 57.17 | 21.66 |
| February | 247.00 | 22.20 | 36.67 | 22.05 | 36.67 | 21.94 |
| March | 284.50 | 22.82 | 15.67 | 22.73 | 15.67 | 22.66 |
| April | 107.83 | 23.34 | 48.00 | 23.54 | 0.17 | 23.54 |
| May | 38.67 | 23.67 | 182.00 | 23.94 | 12.00 | 23.94 |
| June | 6.00 | 23.26 | 249.83 | 23.97 | 0.00 | 23.97 |
| July | 32.50 | 23.11 | 238.50 | 23.72 | 26.67 | 23.68 |
| August | 39.33 | 22.56 | 226.50 | 23.63 | 2.33 | 23.62 |
| September | 19.50 | 23.55 | 225.00 | 23.94 | 9.67 | 23.94 |
| October | 67.00 | 23.43 | 137.17 | 23.80 | 13.50 | 23.81 |
| November | 220.17 | 22.69 | 32.00 | 22.76 | 8.00 | 22.71 |
| December | 260.00 | 21.85 | 72.17 | 21.67 | 72.17 | 21.56 |
| Annual Sum or Average | 1595.50 | 22.48 | 1520.67 | 23.01 | 254.00 | 22.91 |
| Minimum of Months | 6.00 | 21.85 | 15.67 | 21.67 | 0.00 | 21.56 |
| Maximum of Months | 284.50 | 23.67 | 249.83 | 23.97 | 72.17 | 23.97 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 22.22 | 25.83 | 22.12 | 25.83 | 22.04 |
| February | 247.00 | 22.54 | 13.67 | 22.47 | 13.67 | 22.40 |
| March | 274.33 | 23.02 | 3.33 | 22.99 | 3.33 | 22.97 |
| April | 106.83 | 23.33 | 44.33 | 23.52 | 0.00 | 23.52 |
| May | 40.00 | 23.62 | 164.33 | 23.91 | 13.17 | 23.91 |
| June | 6.00 | 23.19 | 234.83 | 23.94 | 0.00 | 23.94 |
| July | 47.50 | 22.63 | 187.33 | 23.12 | 21.00 | 23.09 |
| August | 89.67 | 22.48 | 114.67 | 22.91 | 1.33 | 22.91 |
| September | 26.17 | 23.41 | 205.00 | 23.84 | 10.50 | 23.85 |
| October | 74.33 | 23.34 | 130.00 | 23.72 | 14.00 | 23.74 |
| November | 218.67 | 22.85 | 26.83 | 22.97 | 0.50 | 22.97 |
| December | 260.00 | 22.12 | 40.67 | 21.98 | 40.67 | 21.88 |
| Annual Sum or Average | 1663.50 | 22.67 | 1190.83 | 23.04 | 144.00 | 23.00 |
| Minimum of Months | 6.00 | 22.12 | 3.33 | 21.98 | 0.00 | 21.88 |
| Maximum of Months | 274.33 | 23.62 | 234.83 | 23.94 | 40.67 | 23.94 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 217.67 | 22.69 | 10.50 | 22.66 | 7.17 | 22.61 |
| February | 196.83 | 22.78 | 4.50 | 22.74 | 4.50 | 22.71 |
| March | 194.00 | 23.05 | 3.50 | 23.02 | 3.50 | 22.99 |
| April | 77.17 | 23.39 | 74.17 | 23.69 | 0.00 | 23.69 |
| May | 36.17 | 23.68 | 185.83 | 23.94 | 11.67 | 23.95 |
| June | 8.67 | 23.22 | 244.33 | 23.96 | 0.00 | 23.96 |
| July | 34.33 | 23.09 | 235.50 | 23.72 | 26.83 | 23.68 |
| August | 27.83 | 22.62 | 245.50 | 23.74 | 2.33 | 23.74 |
| September | 11.50 | 23.77 | 239.67 | 23.98 | 8.00 | 23.98 |
| October | 22.33 | 23.63 | 199.50 | 23.96 | 6.83 | 23.96 |
| November | 122.50 | 22.88 | 57.17 | 23.22 | 0.67 | 23.22 |
| December | 219.83 | 22.62 | 14.83 | 22.52 | 14.83 | 22.44 |
| Annual Sum or Average | 1168.83 | 22.89 | 1515.00 | 23.45 | 86.33 | 23.43 |
| Minimum of Months | 8.67 | 22.62 | 3.50 | 22.52 | 0.00 | 22.44 |
| Maximum of Months | 219.83 | 23.77 | 245.50 | 23.98 | 26.83 | 23.98 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 186.67 | 22.91 | 8.67 | 22.95 | 0.50 | 22.95 |
| February | 148.50 | 22.91 | 2.33 | 22.92 | 0.33 | 22.91 |
| March | 161.33 | 23.20 | 0.17 | 23.20 | 0.17 | 23.20 |
| April | 68.33 | 23.41 | 79.17 | 23.73 | 0.00 | 23.73 |
| May | 34.67 | 23.66 | 172.33 | 23.93 | 11.67 | 23.93 |
| June | 7.67 | 23.16 | 228.50 | 23.93 | 0.00 | 23.93 |
| July | 47.33 | 22.66 | 197.50 | 23.22 | 21.33 | 23.19 |
| August | 49.33 | 22.54 | 198.83 | 23.42 | 1.50 | 23.42 |
| September | 11.50 | 23.78 | 236.50 | 23.96 | 8.50 | 23.96 |
| October | 17.33 | 23.73 | 205.00 | 23.97 | 7.67 | 23.97 |
| November | 103.83 | 23.05 | 66.00 | 23.42 | 0.00 | 23.42 |
| December | 186.67 | 22.78 | 1.50 | 22.77 | 1.50 | 22.76 |
| Annual Sum or Average | 1023.17 | 23.00 | 1396.50 | 23.48 | 53.17 | 23.48 |
| Minimum of Months | 7.67 | 22.54 | 0.17 | 22.77 | 0.00 | 22.76 |
| Maximum of Months | 186.67 | 23.78 | 236.50 | 23.97 | 21.33 | 23.97 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 22.47 | 9.17 | 22.42 | 9.17 | 22.38 |
| February | 247.00 | 22.90 | 4.33 | 22.87 | 4.33 | 22.84 |
| March | 296.67 | 23.47 | 1.33 | 23.46 | 1.33 | 23.45 |
| April | 115.00 | 23.83 | 17.00 | 23.85 | 0.00 | 23.85 |
| May | 37.17 | 23.91 | 94.00 | 23.98 | 0.00 | 23.98 |
| June | 7.33 | 23.96 | 161.67 | 24.00 | 0.00 | 24.00 |
| July | 0.83 | 23.37 | 241.33 | 23.97 | 0.00 | 23.97 |
| August | 10.33 | 23.29 | 233.33 | 23.96 | 0.00 | 23.96 |
| September | 4.67 | 23.82 | 203.33 | 23.99 | 1.33 | 23.99 |
| October | 39.00 | 23.88 | 115.50 | 23.97 | 0.83 | 23.97 |
| November | 211.17 | 23.27 | 8.17 | 23.29 | 0.33 | 23.29 |
| December | 260.00 | 22.27 | 21.17 | 22.17 | 21.17 | 22.09 |
| Annual Sum or Average | 1502.17 | 23.01 | 1110.33 | 23.39 | 38.50 | 23.35 |
| Minimum of Months | 0.83 | 22.27 | 1.33 | 22.17 | 0.00 | 22.09 |
| Maximum of Months | 296.67 | 23.96 | 241.33 | 24.00 | 21.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 272.33 | 21.94 | 53.17 | 21.79 | 53.17 | 21.69 |
| February | 247.00 | 22.23 | 34.50 | 22.08 | 34.50 | 21.97 |
| March | 281.33 | 22.84 | 15.00 | 22.75 | 15.00 | 22.67 |
| April | 104.67 | 23.34 | 50.17 | 23.55 | 0.00 | 23.55 |
| May | 36.83 | 23.67 | 184.17 | 23.94 | 11.67 | 23.95 |
| June | 5.50 | 23.28 | 250.67 | 23.97 | 0.00 | 23.97 |
| July | 32.00 | 23.19 | 241.33 | 23.75 | 27.00 | 23.71 |
| August | 35.50 | 22.58 | 232.17 | 23.66 | 2.33 | 23.66 |
| September | 19.00 | 23.56 | 225.33 | 23.94 | 9.67 | 23.95 |
| October | 65.83 | 23.43 | 138.17 | 23.80 | 13.33 | 23.81 |
| November | 219.17 | 22.70 | 32.17 | 22.78 | 7.33 | 22.73 |
| December | 260.00 | 21.87 | 69.67 | 21.70 | 69.67 | 21.59 |
| Annual Sum or Average | 1579.17 | 22.50 | 1526.50 | 23.04 | 243.67 | 22.94 |
| Minimum of Months | 5.50 | 21.87 | 15.00 | 21.70 | 0.00 | 21.59 |
| Maximum of Months | 281.33 | 23.67 | 250.67 | 23.97 | 69.67 | 23.97 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 22.26 | 24.50 | 22.16 | 24.50 | 22.08 |
| February | 247.00 | 22.58 | 13.17 | 22.51 | 13.17 | 22.44 |
| March | 271.33 | 23.04 | 2.67 | 23.02 | 2.67 | 23.00 |
| April | 103.33 | 23.34 | 47.33 | 23.55 | 0.00 | 23.55 |
| May | 37.83 | 23.64 | 168.00 | 23.92 | 12.50 | 23.92 |
| June | 5.50 | 23.23 | 237.50 | 23.96 | 0.00 | 23.96 |
| July | 41.50 | 22.74 | 204.17 | 23.26 | 22.33 | 23.23 |
| August | 73.67 | 22.51 | 140.83 | 23.06 | 1.33 | 23.06 |
| September | 24.33 | 23.45 | 211.00 | 23.86 | 10.33 | 23.87 |
| October | 72.33 | 23.35 | 130.67 | 23.73 | 13.67 | 23.75 |
| November | 217.33 | 22.87 | 27.17 | 22.99 | 0.50 | 22.99 |
| December | 260.00 | 22.17 | 38.00 | 22.03 | 38.00 | 21.92 |
| Annual Sum or Average | 1627.17 | 22.70 | 1245.00 | 23.09 | 139.00 | 23.05 |
| Minimum of Months | 5.50 | 22.17 | 2.67 | 22.03 | 0.00 | 21.92 |
| Maximum of Months | 273.00 | 23.64 | 237.50 | 23.96 | 38.00 | 23.96 |
Report: ComfortReportSimple55Monthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 265.33 | 23.28 | 2.83 | 23.26 | 2.83 | 23.24 |
| February | 226.33 | 23.50 | 1.33 | 23.48 | 1.33 | 23.47 |
| March | 191.83 | 23.72 | 0.17 | 23.72 | 0.17 | 23.72 |
| April | 40.33 | 23.83 | 78.50 | 23.94 | 0.00 | 23.94 |
| May | 18.50 | 23.89 | 201.00 | 23.99 | 10.50 | 23.99 |
| June | 8.00 | 23.96 | 264.67 | 24.00 | 6.67 | 24.00 |
| July | 89.00 | 23.88 | 255.33 | 23.92 | 87.33 | 23.92 |
| August | 36.00 | 23.72 | 276.33 | 23.89 | 29.50 | 23.90 |
| September | 46.33 | 23.97 | 242.83 | 23.99 | 44.83 | 23.99 |
| October | 27.67 | 23.89 | 162.17 | 23.98 | 17.33 | 23.98 |
| November | 151.33 | 23.60 | 42.67 | 23.69 | 0.00 | 23.69 |
| December | 260.00 | 23.18 | 4.83 | 23.15 | 4.83 | 23.11 |
| Annual Sum or Average | 1360.67 | 23.51 | 1532.67 | 23.75 | 205.33 | 23.75 |
| Minimum of Months | 8.00 | 23.18 | 0.17 | 23.15 | 0.00 | 23.11 |
| Maximum of Months | 265.33 | 23.97 | 276.33 | 24.00 | 87.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 22.14 | 18.83 | 22.07 | 18.83 | 22.01 |
| February | 247.00 | 22.86 | 6.83 | 22.81 | 6.83 | 22.76 |
| March | 276.50 | 23.65 | 0.50 | 23.64 | 0.50 | 23.64 |
| April | 74.50 | 23.97 | 36.00 | 23.98 | 0.00 | 23.98 |
| May | 11.67 | 24.00 | 148.83 | 24.00 | 0.00 | 24.00 |
| June | 0.00 | 0.00 | 217.50 | 24.00 | 0.00 | 24.00 |
| July | 2.67 | 24.00 | 257.83 | 24.00 | 2.67 | 24.00 |
| August | 0.00 | 0.00 | 284.17 | 24.00 | 0.00 | 24.00 |
| September | 1.50 | 24.00 | 219.33 | 24.00 | 1.50 | 24.00 |
| October | 35.33 | 23.95 | 121.00 | 23.99 | 1.50 | 23.99 |
| November | 220.00 | 23.25 | 8.17 | 23.27 | 0.00 | 23.27 |
| December | 260.00 | 21.82 | 53.00 | 21.68 | 53.00 | 21.59 |
| Annual Sum or Average | 1402.17 | 22.84 | 1372.00 | 23.33 | 84.83 | 23.27 |
| Minimum of Months | 0.00 | 0.00 | 0.50 | 21.68 | 0.00 | 21.59 |
| Maximum of Months | 276.50 | 24.00 | 284.17 | 24.00 | 53.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 20.90 | 70.67 | 20.64 | 70.67 | 20.47 |
| February | 240.83 | 21.22 | 54.50 | 20.94 | 54.50 | 20.75 |
| March | 284.67 | 22.02 | 35.83 | 21.80 | 35.83 | 21.62 |
| April | 138.00 | 22.74 | 35.33 | 23.04 | 3.83 | 23.01 |
| May | 45.00 | 23.78 | 140.17 | 24.29 | 5.67 | 24.42 |
| June | 27.00 | 28.03 | 236.00 | 25.09 | 21.33 | 25.41 |
| July | 94.67 | 24.82 | 258.67 | 24.48 | 94.67 | 24.55 |
| August | 57.83 | 24.66 | 275.67 | 24.33 | 46.33 | 24.44 |
| September | 42.00 | 24.57 | 227.50 | 24.36 | 32.00 | 24.45 |
| October | 78.67 | 22.69 | 122.50 | 23.55 | 11.17 | 23.62 |
| November | 217.50 | 21.83 | 38.00 | 21.78 | 21.83 | 21.62 |
| December | 260.00 | 20.52 | 102.50 | 20.27 | 102.50 | 20.13 |
| Annual Sum or Average | 1759.17 | 22.02 | 1597.33 | 22.74 | 500.33 | 22.67 |
| Minimum of Months | 27.00 | 20.52 | 35.33 | 20.27 | 3.83 | 20.13 |
| Maximum of Months | 284.67 | 28.03 | 275.67 | 25.09 | 102.50 | 25.41 |
Report: ComfortReportSimple55Monthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 178.83 | 24.02 | 7.50 | 24.09 | 0.00 | 24.09 |
| February | 64.00 | 24.17 | 78.00 | 25.06 | 0.00 | 25.06 |
| March | 15.17 | 24.33 | 227.67 | 26.13 | 0.00 | 26.13 |
| April | 8.50 | 26.70 | 258.17 | 26.58 | 8.50 | 26.59 |
| May | 80.00 | 26.70 | 286.00 | 26.68 | 80.00 | 26.68 |
| June | 145.17 | 26.70 | 286.00 | 26.69 | 145.17 | 26.69 |
| July | 100.83 | 26.53 | 260.00 | 26.30 | 100.83 | 26.35 |
| August | 63.33 | 26.50 | 299.00 | 26.13 | 63.33 | 26.18 |
| September | 155.67 | 26.69 | 260.00 | 26.65 | 155.67 | 26.66 |
| October | 56.83 | 26.69 | 273.00 | 26.54 | 56.83 | 26.56 |
| November | 39.17 | 24.13 | 166.83 | 25.76 | 0.00 | 25.76 |
| December | 215.33 | 23.82 | 0.00 | 23.82 | 0.00 | 23.82 |
| Annual Sum or Average | 1122.83 | 25.43 | 2402.17 | 26.09 | 610.33 | 26.17 |
| Minimum of Months | 8.50 | 23.82 | 0.00 | 23.82 | 0.00 | 23.82 |
| Maximum of Months | 215.33 | 26.70 | 299.00 | 26.69 | 155.67 | 26.69 |
Report: ComfortReportSimple55Monthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 22.02 | 28.50 | 21.90 | 28.50 | 21.80 |
| February | 244.50 | 22.75 | 9.50 | 22.68 | 9.50 | 22.61 |
| March | 177.83 | 23.46 | 18.67 | 23.62 | 1.17 | 23.60 |
| April | 16.50 | 24.88 | 204.00 | 25.83 | 5.17 | 25.85 |
| May | 81.67 | 26.64 | 281.00 | 26.42 | 81.67 | 26.46 |
| June | 148.83 | 26.68 | 286.00 | 26.59 | 148.83 | 26.61 |
| July | 90.33 | 26.31 | 260.00 | 26.03 | 90.33 | 26.09 |
| August | 47.33 | 26.43 | 299.00 | 25.79 | 47.33 | 25.87 |
| September | 119.33 | 26.63 | 259.67 | 26.40 | 119.33 | 26.45 |
| October | 31.67 | 26.06 | 241.50 | 25.74 | 27.50 | 25.80 |
| November | 174.17 | 23.09 | 43.00 | 23.45 | 0.83 | 23.44 |
| December | 260.00 | 21.70 | 61.83 | 21.48 | 61.83 | 21.32 |
| Annual Sum or Average | 1665.17 | 23.78 | 1992.67 | 24.86 | 622.00 | 24.97 |
| Minimum of Months | 16.50 | 21.70 | 9.50 | 21.48 | 0.83 | 21.32 |
| Maximum of Months | 273.00 | 26.68 | 299.00 | 26.59 | 148.83 | 26.61 |
Report: ComfortReportSimple55Monthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 222.67 | 23.08 | 2.83 | 23.06 | 2.83 | 23.04 |
| February | 185.33 | 23.33 | 1.33 | 23.31 | 1.33 | 23.30 |
| March | 169.17 | 23.63 | 0.67 | 23.62 | 0.67 | 23.61 |
| April | 41.17 | 23.94 | 52.33 | 23.98 | 0.00 | 23.98 |
| May | 3.33 | 23.99 | 154.00 | 24.00 | 0.00 | 24.00 |
| June | 0.00 | 0.00 | 213.50 | 24.00 | 0.00 | 24.00 |
| July | 9.17 | 24.00 | 220.00 | 24.00 | 9.17 | 24.00 |
| August | 0.17 | 24.00 | 248.00 | 24.00 | 0.17 | 24.00 |
| September | 0.00 | 0.00 | 204.67 | 24.00 | 0.00 | 24.00 |
| October | 7.33 | 23.95 | 147.17 | 24.00 | 0.00 | 24.00 |
| November | 117.33 | 23.44 | 25.67 | 23.54 | 0.00 | 23.54 |
| December | 219.67 | 22.90 | 11.67 | 22.81 | 11.67 | 22.73 |
| Annual Sum or Average | 975.33 | 23.28 | 1281.83 | 23.67 | 25.83 | 23.65 |
| Minimum of Months | 0.00 | 0.00 | 0.67 | 22.81 | 0.00 | 22.73 |
| Maximum of Months | 222.67 | 24.00 | 248.00 | 24.00 | 11.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 259.33 | 23.25 | 0.00 | 23.25 | 0.00 | 23.25 |
| February | 157.50 | 23.50 | 1.33 | 23.51 | 0.00 | 23.51 |
| March | 77.17 | 23.49 | 2.50 | 23.50 | 0.00 | 23.50 |
| April | 8.83 | 23.64 | 134.83 | 23.98 | 0.00 | 23.98 |
| May | 3.33 | 23.91 | 247.33 | 24.00 | 2.50 | 24.00 |
| June | 4.33 | 24.00 | 276.17 | 24.00 | 4.33 | 24.00 |
| July | 71.83 | 23.98 | 260.00 | 23.99 | 71.83 | 23.99 |
| August | 21.33 | 23.98 | 296.00 | 23.98 | 21.17 | 23.98 |
| September | 22.67 | 24.00 | 256.33 | 24.00 | 22.67 | 24.00 |
| October | 19.50 | 23.78 | 206.33 | 23.98 | 12.33 | 23.98 |
| November | 109.00 | 23.39 | 48.33 | 23.58 | 0.00 | 23.58 |
| December | 260.00 | 23.03 | 1.83 | 23.02 | 1.83 | 23.01 |
| Annual Sum or Average | 1014.83 | 23.37 | 1731.00 | 23.76 | 136.67 | 23.77 |
| Minimum of Months | 3.33 | 23.03 | 0.00 | 23.02 | 0.00 | 23.01 |
| Maximum of Months | 260.00 | 24.00 | 296.00 | 24.00 | 71.83 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.00 | 24.00 | 169.50 | 23.99 | 0.00 | 23.99 |
| February | 0.50 | 24.00 | 159.00 | 23.99 | 0.00 | 23.99 |
| March | 0.00 | 0.00 | 199.67 | 24.00 | 0.00 | 24.00 |
| April | 0.00 | 0.00 | 233.33 | 24.00 | 0.00 | 24.00 |
| May | 9.17 | 24.00 | 283.00 | 24.00 | 9.17 | 24.00 |
| June | 35.17 | 24.00 | 286.00 | 24.00 | 35.17 | 24.00 |
| July | 53.00 | 24.00 | 260.00 | 24.00 | 53.00 | 24.00 |
| August | 43.33 | 24.00 | 299.00 | 24.00 | 43.33 | 24.00 |
| September | 30.17 | 24.00 | 260.00 | 24.00 | 30.17 | 24.00 |
| October | 10.67 | 24.00 | 260.83 | 24.00 | 10.67 | 24.00 |
| November | 0.00 | 0.00 | 203.83 | 24.00 | 0.00 | 24.00 |
| December | 2.00 | 24.00 | 155.00 | 23.99 | 0.00 | 23.99 |
| Annual Sum or Average | 186.00 | 24.00 | 2769.17 | 24.00 | 181.50 | 24.00 |
| Minimum of Months | 0.00 | 0.00 | 155.00 | 23.99 | 0.00 | 23.99 |
| Maximum of Months | 53.00 | 24.00 | 299.00 | 24.00 | 53.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 182.67 | 22.74 | 0.50 | 22.73 | 0.50 | 22.73 |
| February | 139.50 | 22.94 | 6.00 | 22.99 | 4.00 | 23.01 |
| March | 81.17 | 23.39 | 10.17 | 23.46 | 0.00 | 23.46 |
| April | 5.50 | 23.66 | 140.67 | 23.99 | 0.00 | 23.99 |
| May | 0.00 | 0.00 | 230.50 | 24.00 | 0.00 | 24.00 |
| June | 2.00 | 24.00 | 242.00 | 24.00 | 2.00 | 24.00 |
| July | 41.17 | 24.00 | 200.00 | 24.00 | 41.17 | 24.00 |
| August | 17.33 | 24.00 | 230.00 | 24.00 | 17.33 | 24.00 |
| September | 11.00 | 24.00 | 218.67 | 24.00 | 11.00 | 24.00 |
| October | 17.67 | 23.96 | 192.83 | 24.00 | 16.33 | 24.00 |
| November | 86.50 | 23.05 | 52.67 | 23.41 | 0.00 | 23.41 |
| December | 181.83 | 22.37 | 0.67 | 22.37 | 0.67 | 22.36 |
| Annual Sum or Average | 766.33 | 22.95 | 1524.67 | 23.65 | 93.00 | 23.66 |
| Minimum of Months | 0.00 | 0.00 | 0.50 | 22.37 | 0.00 | 22.36 |
| Maximum of Months | 182.67 | 24.00 | 242.00 | 24.00 | 41.17 | 24.00 |
Report: ComfortReportSimple55Monthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 269.83 | 23.26 | 2.83 | 23.24 | 2.83 | 23.22 |
| February | 228.00 | 23.51 | 0.83 | 23.50 | 0.83 | 23.50 |
| March | 178.00 | 23.79 | 0.17 | 23.79 | 0.17 | 23.79 |
| April | 27.17 | 23.99 | 88.83 | 24.00 | 0.00 | 24.00 |
| May | 0.83 | 24.00 | 213.00 | 24.00 | 0.00 | 24.00 |
| June | 0.00 | 0.00 | 270.00 | 24.00 | 0.00 | 24.00 |
| July | 4.83 | 23.99 | 260.00 | 24.00 | 4.83 | 24.00 |
| August | 0.00 | 0.00 | 295.50 | 24.00 | 0.00 | 24.00 |
| September | 1.67 | 24.00 | 248.00 | 24.00 | 1.67 | 24.00 |
| October | 8.00 | 23.98 | 176.83 | 24.00 | 1.50 | 24.00 |
| November | 147.33 | 23.61 | 35.00 | 23.69 | 0.00 | 23.69 |
| December | 260.00 | 23.09 | 10.33 | 23.01 | 10.33 | 22.94 |
| Annual Sum or Average | 1125.67 | 23.43 | 1601.33 | 23.75 | 22.17 | 23.74 |
| Minimum of Months | 0.00 | 0.00 | 0.17 | 23.01 | 0.00 | 22.94 |
| Maximum of Months | 269.83 | 24.00 | 295.50 | 24.00 | 10.33 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 22.94403 | 22.48943 | 0.10326 | 6.70857 |
| February | 247.00000 | 23.01800 | 21.82680 | 0.12506 | 6.66725 |
| March | 299.00000 | 23.37658 | 18.64131 | 0.21269 | 6.98951 |
| April | 260.00000 | 23.80649 | 24.54505 | 0.41825 | 9.28588 |
| May | 286.00000 | 23.94973 | 33.72722 | -0.1809 | 6.27445 |
| June | 286.00000 | 23.95046 | 36.63527 | -0.1067 | 5.58271 |
| July | 260.00000 | 23.73856 | 50.90269 | -0.1076 | 5.80927 |
| August | 299.00000 | 23.69958 | 47.96026 | -0.1369 | 6.18171 |
| September | 260.00000 | 23.96354 | 44.47592 | -0.0192 | 5.44804 |
| October | 273.00000 | 23.94646 | 37.12175 | 0.60332 | 13.06945 |
| November | 273.00000 | 23.48217 | 25.40931 | 0.32737 | 8.55337 |
| December | 260.00000 | 22.82803 | 22.05210 | 0.06139 | 6.68862 |
| Annual Sum or Average | 3276.00000 | 23.56530 | 32.22010 | 0.10541 | 7.26218 |
| Minimum of Months | 247.00000 | 22.82803 | 18.64131 | -0.1809 | 5.44804 |
| Maximum of Months | 299.00000 | 23.96354 | 50.90269 | 0.60332 | 13.06945 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 23.24560 | 22.00715 | 0.20443 | 6.94857 |
| February | 247.00000 | 23.31588 | 21.25849 | 0.22766 | 7.02851 |
| March | 299.00000 | 23.54304 | 18.33746 | 0.28155 | 7.34825 |
| April | 260.00000 | 23.81384 | 24.56329 | 0.43272 | 9.39525 |
| May | 286.00000 | 23.91682 | 34.03575 | -0.2013 | 6.36258 |
| June | 286.00000 | 23.92308 | 37.00514 | -0.1458 | 5.74991 |
| July | 260.00000 | 23.25759 | 52.38667 | -0.2694 | 6.95529 |
| August | 299.00000 | 23.39274 | 48.96243 | -0.2499 | 7.07050 |
| September | 260.00000 | 23.94584 | 44.74951 | -0.0519 | 5.45420 |
| October | 273.00000 | 23.94500 | 37.21299 | 0.60677 | 13.09226 |
| November | 273.00000 | 23.61546 | 25.18567 | 0.38038 | 8.94699 |
| December | 260.00000 | 23.12119 | 21.62402 | 0.15833 | 6.74071 |
| Annual Sum or Average | 3276.00000 | 23.59007 | 32.35595 | 0.11046 | 7.58453 |
| Minimum of Months | 247.00000 | 23.12119 | 18.33746 | -0.2694 | 5.45420 |
| Maximum of Months | 299.00000 | 23.94584 | 52.38667 | 0.60677 | 13.09226 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 22.35829 | 21.61190 | -0.0746 | 5.79168 |
| February | 247.00000 | 22.78574 | 20.46917 | 0.02345 | 5.71681 |
| March | 299.00000 | 23.39738 | 16.98147 | 0.15686 | 6.11175 |
| April | 260.00000 | 23.90758 | 22.49102 | 0.35865 | 7.95107 |
| May | 286.00000 | 23.98364 | 31.73713 | -0.2964 | 7.10047 |
| June | 286.00000 | 23.99305 | 35.29677 | -0.2372 | 6.31308 |
| July | 260.00000 | 23.94059 | 49.54916 | -0.2027 | 5.96154 |
| August | 299.00000 | 23.90221 | 46.77854 | -0.2430 | 6.42071 |
| September | 260.00000 | 23.98759 | 43.43300 | -0.2017 | 6.00530 |
| October | 273.00000 | 23.97515 | 35.60974 | 0.47962 | 10.05267 |
| November | 273.00000 | 23.38210 | 24.17124 | 0.20648 | 6.79744 |
| December | 260.00000 | 22.15316 | 21.08665 | -0.1297 | 6.03903 |
| Annual Sum or Average | 3276.00000 | 23.49251 | 30.83566 | -0.0156 | 6.69278 |
| Minimum of Months | 247.00000 | 22.15316 | 16.98147 | -0.2964 | 5.71681 |
| Maximum of Months | 299.00000 | 23.99305 | 49.54916 | 0.47962 | 10.05267 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.92049 | 23.98730 | -0.1998 | 6.79805 |
| February | 247.00000 | 22.19828 | 23.10928 | -0.1232 | 6.45530 |
| March | 299.00000 | 22.87815 | 19.63717 | 0.04995 | 6.15584 |
| April | 260.00000 | 23.71333 | 25.06587 | 0.36463 | 8.45857 |
| May | 286.00000 | 23.94580 | 33.86602 | -0.1971 | 6.38661 |
| June | 286.00000 | 23.95987 | 36.62533 | -0.1048 | 5.50845 |
| July | 260.00000 | 23.73058 | 50.96122 | -0.1176 | 5.77988 |
| August | 299.00000 | 23.57341 | 48.43536 | -0.2037 | 6.66448 |
| September | 260.00000 | 23.92378 | 44.93756 | -0.0983 | 5.65123 |
| October | 273.00000 | 23.82779 | 38.14667 | 0.50846 | 10.97558 |
| November | 273.00000 | 22.93475 | 27.01823 | 0.12487 | 6.88469 |
| December | 260.00000 | 21.85104 | 23.37795 | -0.2292 | 7.08102 |
| Annual Sum or Average | 3276.00000 | 23.21744 | 32.99445 | -0.0199 | 6.89067 |
| Minimum of Months | 247.00000 | 21.85104 | 19.63717 | -0.2292 | 5.50845 |
| Maximum of Months | 299.00000 | 23.95987 | 50.96122 | 0.50846 | 10.97558 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 22.22457 | 23.73874 | -0.1098 | 6.16159 |
| February | 247.00000 | 22.54309 | 22.79221 | -0.0206 | 6.08878 |
| March | 299.00000 | 23.09710 | 19.42335 | 0.12409 | 6.17579 |
| April | 260.00000 | 23.69826 | 25.14606 | 0.37333 | 8.43512 |
| May | 286.00000 | 23.90298 | 34.21561 | -0.2223 | 6.53370 |
| June | 286.00000 | 23.93341 | 37.00727 | -0.1460 | 5.68288 |
| July | 260.00000 | 23.13016 | 52.76597 | -0.3121 | 7.33511 |
| August | 299.00000 | 22.95385 | 50.21023 | -0.3993 | 8.77984 |
| September | 260.00000 | 23.79879 | 45.54288 | -0.1658 | 6.04472 |
| October | 273.00000 | 23.76023 | 38.42643 | 0.49285 | 10.61518 |
| November | 273.00000 | 23.07677 | 26.93558 | 0.17105 | 6.83947 |
| December | 260.00000 | 22.12892 | 23.16447 | -0.1456 | 6.39385 |
| Annual Sum or Average | 3276.00000 | 23.19566 | 33.35330 | -0.0325 | 7.09741 |
| Minimum of Months | 247.00000 | 22.12892 | 19.42335 | -0.3993 | 5.68288 |
| Maximum of Months | 299.00000 | 23.93341 | 52.76597 | 0.49285 | 10.61518 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 22.93156 | 22.52393 | 0.09893 | 6.68626 |
| February | 247.00000 | 23.01166 | 21.85461 | 0.12242 | 6.64242 |
| March | 299.00000 | 23.37380 | 18.66165 | 0.21107 | 6.96745 |
| April | 260.00000 | 23.80469 | 24.56756 | 0.41628 | 9.24753 |
| May | 286.00000 | 23.94918 | 33.75070 | -0.1839 | 6.29238 |
| June | 286.00000 | 23.94858 | 36.65451 | -0.1103 | 5.59817 |
| July | 260.00000 | 23.72233 | 50.96679 | -0.1164 | 5.86129 |
| August | 299.00000 | 23.68298 | 48.02077 | -0.1454 | 6.24720 |
| September | 260.00000 | 23.96302 | 44.48838 | -0.0220 | 5.44464 |
| October | 273.00000 | 23.94636 | 37.13837 | 0.60179 | 13.02639 |
| November | 273.00000 | 23.47443 | 25.43707 | 0.32397 | 8.52222 |
| December | 260.00000 | 22.80809 | 22.09686 | 0.05493 | 6.67043 |
| Annual Sum or Average | 3276.00000 | 23.55809 | 32.25130 | 0.10136 | 7.25851 |
| Minimum of Months | 247.00000 | 22.80809 | 18.66165 | -0.1839 | 5.44464 |
| Maximum of Months | 299.00000 | 23.96302 | 50.96679 | 0.60179 | 13.02639 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 23.21813 | 22.08325 | 0.19462 | 6.86655 |
| February | 247.00000 | 23.31154 | 21.29691 | 0.22463 | 6.97971 |
| March | 299.00000 | 23.54943 | 18.34842 | 0.28259 | 7.33540 |
| April | 260.00000 | 23.81466 | 24.58120 | 0.43166 | 9.36043 |
| May | 286.00000 | 23.91328 | 34.07089 | -0.2056 | 6.38791 |
| June | 286.00000 | 23.91551 | 37.04771 | -0.1524 | 5.78712 |
| July | 260.00000 | 23.18216 | 52.61648 | -0.2950 | 7.22659 |
| August | 299.00000 | 23.32487 | 49.15826 | -0.2735 | 7.29992 |
| September | 260.00000 | 23.94269 | 44.78339 | -0.0581 | 5.46016 |
| October | 273.00000 | 23.94324 | 37.25199 | 0.60283 | 12.98621 |
| November | 273.00000 | 23.60063 | 25.24221 | 0.37333 | 8.84933 |
| December | 260.00000 | 23.08164 | 21.71698 | 0.14520 | 6.66657 |
| Annual Sum or Average | 3276.00000 | 23.57019 | 32.42854 | 0.10183 | 7.59562 |
| Minimum of Months | 247.00000 | 23.08164 | 18.34842 | -0.2950 | 5.46016 |
| Maximum of Months | 299.00000 | 23.94324 | 52.61648 | 0.60283 | 12.98621 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 22.33559 | 21.64396 | -0.0800 | 5.80289 |
| February | 247.00000 | 22.78082 | 20.48408 | 0.02207 | 5.71261 |
| March | 299.00000 | 23.40322 | 16.98025 | 0.15812 | 6.11373 |
| April | 260.00000 | 23.90945 | 22.49007 | 0.35900 | 7.95293 |
| May | 286.00000 | 23.98395 | 31.74016 | -0.2967 | 7.10284 |
| June | 286.00000 | 23.99302 | 35.29961 | -0.2379 | 6.31939 |
| July | 260.00000 | 23.93706 | 49.56699 | -0.2058 | 5.99009 |
| August | 299.00000 | 23.89721 | 46.80058 | -0.2463 | 6.45869 |
| September | 260.00000 | 23.98728 | 43.43800 | -0.2027 | 6.01387 |
| October | 273.00000 | 23.97493 | 35.61846 | 0.47900 | 10.04041 |
| November | 273.00000 | 23.37157 | 24.19836 | 0.20355 | 6.78737 |
| December | 260.00000 | 22.12577 | 21.12283 | -0.1363 | 6.06908 |
| Annual Sum or Average | 3276.00000 | 23.48712 | 30.84947 | -0.0176 | 6.70142 |
| Minimum of Months | 247.00000 | 22.12577 | 16.98025 | -0.2967 | 5.71261 |
| Maximum of Months | 299.00000 | 23.99302 | 49.56699 | 0.47900 | 10.04041 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.91662 | 23.98844 | -0.2010 | 6.80591 |
| February | 247.00000 | 22.19668 | 23.10822 | -0.1236 | 6.45762 |
| March | 299.00000 | 22.87876 | 19.63362 | 0.05027 | 6.15719 |
| April | 260.00000 | 23.71334 | 25.06311 | 0.36481 | 8.46178 |
| May | 286.00000 | 23.94569 | 33.86453 | -0.1969 | 6.38605 |
| June | 286.00000 | 23.95981 | 36.62486 | -0.1047 | 5.50838 |
| July | 260.00000 | 23.72971 | 50.96350 | -0.1178 | 5.78258 |
| August | 299.00000 | 23.57206 | 48.43899 | -0.2040 | 6.67017 |
| September | 260.00000 | 23.92324 | 44.93874 | -0.0985 | 5.65398 |
| October | 273.00000 | 23.82695 | 38.14762 | 0.50829 | 10.97404 |
| November | 273.00000 | 22.93153 | 27.02110 | 0.12402 | 6.88435 |
| December | 260.00000 | 21.84711 | 23.37896 | -0.2304 | 7.09048 |
| Annual Sum or Average | 3276.00000 | 23.21616 | 32.99476 | -0.0202 | 6.89337 |
| Minimum of Months | 247.00000 | 21.84711 | 19.63362 | -0.2304 | 5.50838 |
| Maximum of Months | 299.00000 | 23.95981 | 50.96350 | 0.50829 | 10.97404 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 22.21913 | 23.74099 | -0.1113 | 6.16755 |
| February | 247.00000 | 22.54081 | 22.79185 | -0.0211 | 6.09042 |
| March | 299.00000 | 23.09742 | 19.41982 | 0.12437 | 6.17777 |
| April | 260.00000 | 23.69833 | 25.14330 | 0.37353 | 8.43858 |
| May | 286.00000 | 23.90308 | 34.21355 | -0.2221 | 6.53189 |
| June | 286.00000 | 23.93339 | 37.00643 | -0.1458 | 5.68212 |
| July | 260.00000 | 23.12872 | 52.76983 | -0.3124 | 7.34022 |
| August | 299.00000 | 22.95117 | 50.21742 | -0.4001 | 8.79356 |
| September | 260.00000 | 23.79734 | 45.54613 | -0.1661 | 6.05022 |
| October | 273.00000 | 23.75925 | 38.42798 | 0.49265 | 10.61290 |
| November | 273.00000 | 23.07324 | 26.93952 | 0.17010 | 6.83718 |
| December | 260.00000 | 22.12339 | 23.16669 | -0.1471 | 6.40166 |
| Annual Sum or Average | 3276.00000 | 23.19379 | 33.35452 | -0.0329 | 7.10060 |
| Minimum of Months | 247.00000 | 22.12339 | 19.41982 | -0.4001 | 5.68212 |
| Maximum of Months | 299.00000 | 23.93339 | 52.76983 | 0.49265 | 10.61290 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 22.95066 | 22.48569 | 0.10511 | 6.69375 |
| February | 247.00000 | 23.02763 | 21.81839 | 0.12785 | 6.65763 |
| March | 299.00000 | 23.38341 | 18.63869 | 0.21462 | 6.98716 |
| April | 260.00000 | 23.80734 | 24.55468 | 0.41778 | 9.26904 |
| May | 286.00000 | 23.94989 | 33.74187 | -0.1827 | 6.27980 |
| June | 286.00000 | 23.94943 | 36.64807 | -0.1091 | 5.59070 |
| July | 260.00000 | 23.73056 | 50.93559 | -0.1122 | 5.82966 |
| August | 299.00000 | 23.69255 | 47.98736 | -0.1408 | 6.20209 |
| September | 260.00000 | 23.96397 | 44.48138 | -0.0205 | 5.44008 |
| October | 273.00000 | 23.94728 | 37.12872 | 0.60277 | 13.04963 |
| November | 273.00000 | 23.48256 | 25.41477 | 0.32712 | 8.54703 |
| December | 260.00000 | 22.83177 | 22.05183 | 0.06255 | 6.67482 |
| Annual Sum or Average | 3276.00000 | 23.56635 | 32.22861 | 0.10474 | 7.25940 |
| Minimum of Months | 247.00000 | 22.83177 | 18.63869 | -0.1827 | 5.44008 |
| Maximum of Months | 299.00000 | 23.96397 | 50.93559 | 0.60277 | 13.04963 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 23.25252 | 22.01016 | 0.20603 | 6.92661 |
| February | 247.00000 | 23.33814 | 21.23209 | 0.23391 | 7.04307 |
| March | 299.00000 | 23.56493 | 18.30851 | 0.28840 | 7.38753 |
| April | 260.00000 | 23.82178 | 24.55033 | 0.43520 | 9.41741 |
| May | 286.00000 | 23.91863 | 34.03886 | -0.2012 | 6.34247 |
| June | 286.00000 | 23.92179 | 37.01677 | -0.1478 | 5.75184 |
| July | 260.00000 | 23.22644 | 52.48051 | -0.2799 | 7.04806 |
| August | 299.00000 | 23.36753 | 49.03468 | -0.2587 | 7.12899 |
| September | 260.00000 | 23.94746 | 44.75567 | -0.0533 | 5.43977 |
| October | 273.00000 | 23.94679 | 37.22445 | 0.60576 | 13.05754 |
| November | 273.00000 | 23.61780 | 25.19575 | 0.37986 | 8.92166 |
| December | 260.00000 | 23.12443 | 21.62419 | 0.15954 | 6.72434 |
| Annual Sum or Average | 3276.00000 | 23.59096 | 32.36817 | 0.10994 | 7.59280 |
| Minimum of Months | 247.00000 | 23.12443 | 18.30851 | -0.2799 | 5.43977 |
| Maximum of Months | 299.00000 | 23.94746 | 52.48051 | 0.60576 | 13.05754 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 22.46880 | 21.47910 | -0.0481 | 5.71759 |
| February | 247.00000 | 22.90315 | 20.30343 | 0.05171 | 5.73013 |
| March | 299.00000 | 23.47401 | 16.83995 | 0.17700 | 6.19591 |
| April | 260.00000 | 23.92310 | 22.42260 | 0.36577 | 8.03875 |
| May | 286.00000 | 23.98693 | 31.70228 | -0.2910 | 7.02253 |
| June | 286.00000 | 23.99482 | 35.27791 | -0.2322 | 6.26161 |
| July | 260.00000 | 23.95698 | 49.47717 | -0.1903 | 5.84420 |
| August | 299.00000 | 23.92702 | 46.67857 | -0.2280 | 6.24614 |
| September | 260.00000 | 23.99119 | 43.40429 | -0.1953 | 5.94589 |
| October | 273.00000 | 23.98037 | 35.56197 | 0.48384 | 10.13184 |
| November | 273.00000 | 23.43426 | 24.05277 | 0.22053 | 6.86471 |
| December | 260.00000 | 22.26889 | 20.95355 | -0.1015 | 5.93736 |
| Annual Sum or Average | 3276.00000 | 23.53705 | 30.74753 | -0.0014 | 6.66513 |
| Minimum of Months | 247.00000 | 22.26889 | 16.83995 | -0.2910 | 5.71759 |
| Maximum of Months | 299.00000 | 23.99482 | 49.47717 | 0.48384 | 10.13184 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.94386 | 23.96109 | -0.1929 | 6.76572 |
| February | 247.00000 | 22.22713 | 23.07541 | -0.1148 | 6.43952 |
| March | 299.00000 | 22.90554 | 19.59471 | 0.05817 | 6.17774 |
| April | 260.00000 | 23.72252 | 25.02289 | 0.36919 | 8.52294 |
| May | 286.00000 | 23.94767 | 33.83262 | -0.1929 | 6.35036 |
| June | 286.00000 | 23.96216 | 36.60303 | -0.1007 | 5.48970 |
| July | 260.00000 | 23.75697 | 50.86459 | -0.1048 | 5.70132 |
| August | 299.00000 | 23.60818 | 48.31945 | -0.1892 | 6.52162 |
| September | 260.00000 | 23.92707 | 44.91093 | -0.0940 | 5.63515 |
| October | 273.00000 | 23.82997 | 38.11522 | 0.51074 | 11.02884 |
| November | 273.00000 | 22.94456 | 26.99263 | 0.12823 | 6.90270 |
| December | 260.00000 | 21.87489 | 23.35386 | -0.2220 | 7.04313 |
| Annual Sum or Average | 3276.00000 | 23.23358 | 32.95054 | -0.0132 | 6.87147 |
| Minimum of Months | 247.00000 | 21.87489 | 19.59471 | -0.2220 | 5.48970 |
| Maximum of Months | 299.00000 | 23.96216 | 50.86459 | 0.51074 | 11.02884 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 22.25701 | 23.70078 | -0.1000 | 6.15053 |
| February | 247.00000 | 22.58081 | 22.73935 | -0.0097 | 6.10180 |
| March | 299.00000 | 23.12481 | 19.36221 | 0.13216 | 6.21680 |
| April | 260.00000 | 23.71545 | 25.07208 | 0.37895 | 8.51887 |
| May | 286.00000 | 23.91553 | 34.13306 | -0.2151 | 6.45912 |
| June | 286.00000 | 23.94611 | 36.93224 | -0.1382 | 5.62960 |
| July | 260.00000 | 23.25997 | 52.36734 | -0.2717 | 6.86513 |
| August | 299.00000 | 23.07040 | 49.87038 | -0.3632 | 8.22905 |
| September | 260.00000 | 23.82429 | 45.44147 | -0.1558 | 5.96792 |
| October | 273.00000 | 23.77053 | 38.35533 | 0.49633 | 10.69000 |
| November | 273.00000 | 23.09165 | 26.88825 | 0.17526 | 6.87045 |
| December | 260.00000 | 22.16791 | 23.12244 | -0.1336 | 6.36731 |
| Annual Sum or Average | 3276.00000 | 23.23546 | 33.23703 | -0.0195 | 7.00975 |
| Minimum of Months | 247.00000 | 22.16791 | 19.36221 | -0.3632 | 5.62960 |
| Maximum of Months | 299.00000 | 23.94611 | 52.36734 | 0.49633 | 10.69000 |
Report: OccupantComfortDataSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 23.30280 | 24.76198 | 0.13013 | 5.93847 |
| February | 247.00000 | 23.53835 | 23.71006 | 0.20621 | 6.40639 |
| March | 299.00000 | 23.82166 | 20.37500 | 0.30001 | 7.22090 |
| April | 260.00000 | 23.97145 | 25.88641 | 0.45849 | 9.63570 |
| May | 286.00000 | 23.98908 | 34.94699 | -0.1605 | 5.85980 |
| June | 286.00000 | 23.99397 | 38.91206 | -0.0754 | 5.29434 |
| July | 260.00000 | 23.92433 | 52.66616 | -0.0678 | 5.27150 |
| August | 299.00000 | 23.86578 | 49.96828 | -0.1236 | 5.61388 |
| September | 260.00000 | 23.98682 | 47.16175 | -0.0620 | 5.31308 |
| October | 273.00000 | 23.98450 | 39.07783 | 0.56489 | 11.97737 |
| November | 273.00000 | 23.77837 | 27.64600 | 0.33816 | 7.93421 |
| December | 260.00000 | 23.17908 | 24.23561 | 0.09190 | 5.92173 |
| Annual Sum or Average | 3276.00000 | 23.78286 | 34.18050 | 0.13054 | 6.85716 |
| Minimum of Months | 247.00000 | 23.17908 | 20.37500 | -0.1605 | 5.27150 |
| Maximum of Months | 299.00000 | 23.99397 | 52.66616 | 0.56489 | 11.97737 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 24.37483 | 17.46598 | 0.31670 | 7.56764 |
| February | 247.00000 | 25.06173 | 16.27267 | 0.47608 | 10.36203 |
| March | 299.00000 | 25.96554 | 13.25593 | 0.67994 | 15.25855 |
| April | 260.00000 | 26.57073 | 18.35604 | 0.90365 | 22.48969 |
| May | 286.00000 | 26.66886 | 26.41665 | 0.46196 | 9.73640 |
| June | 286.00000 | 26.68899 | 29.73872 | 0.52788 | 11.00684 |
| July | 260.00000 | 26.21192 | 43.16143 | 0.45729 | 9.66015 |
| August | 299.00000 | 26.04697 | 41.04525 | 0.38056 | 8.44381 |
| September | 260.00000 | 26.62519 | 36.88544 | 0.52788 | 11.08306 |
| October | 273.00000 | 26.50559 | 30.02520 | 0.97247 | 25.29749 |
| November | 273.00000 | 25.59104 | 19.91405 | 0.63630 | 14.51126 |
| December | 260.00000 | 24.01833 | 17.16501 | 0.22808 | 6.68934 |
| Annual Sum or Average | 3276.00000 | 25.87602 | 25.87458 | 0.54756 | 12.66560 |
| Minimum of Months | 247.00000 | 24.01833 | 13.25593 | 0.22808 | 6.68934 |
| Maximum of Months | 299.00000 | 26.68899 | 43.16143 | 0.97247 | 25.29749 |
Report: OccupantComfortDataSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 22.02158 | 21.96256 | -0.1627 | 6.21593 |
| February | 247.00000 | 22.76816 | 20.56975 | 0.01028 | 5.85244 |
| March | 299.00000 | 24.01725 | 16.83521 | 0.28797 | 7.65035 |
| April | 260.00000 | 25.64307 | 21.46631 | 0.72067 | 16.75101 |
| May | 286.00000 | 26.33092 | 29.01334 | 0.37846 | 8.87186 |
| June | 286.00000 | 26.54272 | 31.28373 | 0.50473 | 10.70655 |
| July | 260.00000 | 25.93616 | 44.46232 | 0.41118 | 9.02092 |
| August | 299.00000 | 25.69395 | 42.48494 | 0.31067 | 7.77327 |
| September | 260.00000 | 26.29209 | 39.03897 | 0.45522 | 10.01956 |
| October | 273.00000 | 25.56182 | 33.92297 | 0.79741 | 19.22961 |
| November | 273.00000 | 23.67636 | 24.22633 | 0.25653 | 7.94303 |
| December | 260.00000 | 21.70423 | 21.54000 | -0.2417 | 7.11148 |
| Annual Sum or Average | 3276.00000 | 24.71087 | 28.94534 | 0.31356 | 9.74557 |
| Minimum of Months | 247.00000 | 21.70423 | 16.83521 | -0.2417 | 5.85244 |
| Maximum of Months | 299.00000 | 26.54272 | 44.46232 | 0.79741 | 19.22961 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 231.00000 | 23.11400 | 19.68448 | 0.08763 | 5.97961 |
| February | 209.00000 | 23.40346 | 18.57258 | 0.17072 | 6.27636 |
| March | 253.00000 | 23.75526 | 15.49869 | 0.26995 | 6.97757 |
| April | 220.00000 | 23.99029 | 21.38804 | 0.44488 | 9.36274 |
| May | 242.00000 | 24.00107 | 30.77799 | -0.1658 | 5.86058 |
| June | 242.00000 | 24.00210 | 34.95372 | -0.0779 | 5.32080 |
| July | 220.00000 | 24.00102 | 49.30896 | -0.0134 | 5.10514 |
| August | 253.00000 | 23.99542 | 46.36773 | -0.0531 | 5.24079 |
| September | 220.00000 | 24.00196 | 43.02214 | -0.0420 | 5.28035 |
| October | 231.00000 | 23.99888 | 34.88969 | 0.56326 | 11.93422 |
| November | 231.00000 | 23.71694 | 22.68626 | 0.31739 | 7.81383 |
| December | 220.00000 | 22.90203 | 19.26185 | 0.02381 | 6.03813 |
| Annual Sum or Average | 2772.00000 | 23.74735 | 29.77775 | 0.12489 | 6.75505 |
| Minimum of Months | 209.00000 | 22.90203 | 15.49869 | -0.1658 | 5.10514 |
| Maximum of Months | 253.00000 | 24.00210 | 49.30896 | 0.56326 | 11.93422 |
Report: OccupantComfortDataSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 23.28538 | 24.04492 | 0.19108 | 6.24403 |
| February | 247.00000 | 23.67073 | 22.71288 | 0.30355 | 7.29175 |
| March | 299.00000 | 23.86471 | 18.92973 | 0.38438 | 8.35386 |
| April | 260.00000 | 23.98466 | 24.55389 | 0.52969 | 11.07561 |
| May | 286.00000 | 23.99582 | 33.81537 | -0.0726 | 5.37512 |
| June | 286.00000 | 23.99774 | 37.87216 | 0.00138 | 5.19029 |
| July | 260.00000 | 23.99058 | 51.80378 | 0.04589 | 5.18390 |
| August | 299.00000 | 23.97083 | 49.06083 | -0.0057 | 5.23382 |
| September | 260.00000 | 23.99293 | 46.23650 | -0.0005 | 5.21257 |
| October | 273.00000 | 23.97224 | 38.29500 | 0.59329 | 12.65789 |
| November | 273.00000 | 23.74778 | 26.88718 | 0.37357 | 8.41651 |
| December | 260.00000 | 23.03454 | 23.64723 | 0.11836 | 5.87239 |
| Annual Sum or Average | 3276.00000 | 23.79757 | 33.21845 | 0.20276 | 7.15903 |
| Minimum of Months | 247.00000 | 23.03454 | 18.92973 | -0.0726 | 5.18390 |
| Maximum of Months | 299.00000 | 23.99774 | 51.80378 | 0.59329 | 12.65789 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 23.99409 | 27.46246 | 0.57732 | 12.29006 |
| February | 247.00000 | 23.99483 | 25.99330 | 0.59193 | 12.69773 |
| March | 299.00000 | 23.99651 | 22.72786 | 0.60735 | 13.02037 |
| April | 260.00000 | 23.99929 | 33.11247 | 0.73168 | 16.64423 |
| May | 286.00000 | 24.00066 | 41.88361 | 0.16627 | 6.02986 |
| June | 286.00000 | 24.00075 | 46.80143 | 0.23177 | 6.51960 |
| July | 260.00000 | 24.00097 | 51.50290 | 0.22580 | 6.44682 |
| August | 299.00000 | 24.00087 | 50.03544 | 0.19471 | 6.19828 |
| September | 260.00000 | 24.00081 | 47.16656 | 0.19843 | 6.28163 |
| October | 273.00000 | 23.99967 | 39.55684 | 0.76796 | 17.80451 |
| November | 273.00000 | 23.99659 | 29.43298 | 0.63615 | 13.84331 |
| December | 260.00000 | 23.99363 | 28.36673 | 0.56849 | 12.06910 |
| Annual Sum or Average | 3276.00000 | 23.99827 | 37.09115 | 0.45456 | 10.75756 |
| Minimum of Months | 247.00000 | 23.99363 | 22.72786 | 0.16627 | 6.02986 |
| Maximum of Months | 299.00000 | 24.00097 | 51.50290 | 0.76796 | 17.80451 |
Report: OccupantComfortDataSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 231.00000 | 22.99981 | 27.31631 | 0.16034 | 6.78161 |
| February | 209.00000 | 23.29124 | 25.94571 | 0.24318 | 7.30601 |
| March | 253.00000 | 23.79814 | 21.88321 | 0.37284 | 8.37764 |
| April | 220.00000 | 23.98840 | 28.34404 | 0.56503 | 11.94196 |
| May | 242.00000 | 23.99996 | 36.70674 | -0.0011 | 5.27628 |
| June | 242.00000 | 24.00052 | 40.70001 | 0.09337 | 5.36557 |
| July | 200.00000 | 24.00038 | 49.73483 | 0.06216 | 5.11856 |
| August | 230.00000 | 24.00026 | 46.53970 | 0.01038 | 5.07329 |
| September | 219.00000 | 24.00074 | 45.91992 | 0.07782 | 5.34054 |
| October | 231.00000 | 23.99318 | 39.16090 | 0.64331 | 13.99409 |
| November | 231.00000 | 23.63431 | 29.71717 | 0.38186 | 8.93990 |
| December | 220.00000 | 22.65381 | 27.55076 | 0.08737 | 6.66432 |
| Annual Sum or Average | 2728.00000 | 23.70139 | 34.79357 | 0.22608 | 7.52920 |
| Minimum of Months | 200.00000 | 22.65381 | 21.88321 | -0.0011 | 5.07329 |
| Maximum of Months | 253.00000 | 24.00074 | 49.73483 | 0.64331 | 13.99409 |
Report: OccupantComfortDataSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 23.26471 | 21.01552 | 0.09846 | 5.92778 |
| February | 247.00000 | 23.54800 | 19.67298 | 0.19120 | 6.34809 |
| March | 299.00000 | 23.87456 | 16.32480 | 0.30409 | 7.22068 |
| April | 260.00000 | 23.99804 | 22.34398 | 0.47726 | 9.96488 |
| May | 286.00000 | 23.99974 | 31.73546 | -0.1130 | 5.54997 |
| June | 286.00000 | 24.00028 | 35.31118 | -0.0310 | 5.18438 |
| July | 260.00000 | 23.99964 | 49.44836 | 0.00590 | 5.08904 |
| August | 299.00000 | 23.99346 | 46.56066 | -0.0435 | 5.19692 |
| September | 260.00000 | 23.99981 | 43.46001 | -0.0232 | 5.21129 |
| October | 273.00000 | 23.99897 | 35.64831 | 0.57158 | 12.13836 |
| November | 273.00000 | 23.79039 | 23.75444 | 0.32431 | 7.76001 |
| December | 260.00000 | 23.08549 | 20.57507 | 0.04696 | 6.02810 |
| Annual Sum or Average | 3276.00000 | 23.80227 | 30.55758 | 0.14873 | 6.78805 |
| Minimum of Months | 247.00000 | 23.08549 | 16.32480 | -0.1130 | 5.08904 |
| Maximum of Months | 299.00000 | 24.00028 | 49.44836 | 0.57158 | 12.13836 |
Report: OccupantComfortDataSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 22.14285 | 22.60895 | -0.1367 | 5.95826 |
| February | 247.00000 | 22.85810 | 21.06828 | 0.02970 | 5.77172 |
| March | 299.00000 | 23.67184 | 17.00120 | 0.22674 | 6.49147 |
| April | 260.00000 | 23.99091 | 22.36835 | 0.41200 | 8.71082 |
| May | 286.00000 | 23.99983 | 31.71226 | -0.2246 | 6.28191 |
| June | 286.00000 | 24.00024 | 35.31297 | -0.1582 | 5.67508 |
| July | 260.00000 | 24.00002 | 49.33235 | -0.0948 | 5.24398 |
| August | 299.00000 | 23.99510 | 46.48016 | -0.1409 | 5.51639 |
| September | 260.00000 | 23.99967 | 43.48885 | -0.1495 | 5.61705 |
| October | 273.00000 | 23.99209 | 35.84306 | 0.49593 | 10.38952 |
| November | 273.00000 | 23.38978 | 24.81039 | 0.20095 | 6.74723 |
| December | 260.00000 | 21.81740 | 22.18611 | -0.2236 | 6.59631 |
| Annual Sum or Average | 3276.00000 | 23.50327 | 31.07519 | 0.01890 | 6.57641 |
| Minimum of Months | 247.00000 | 21.81740 | 17.00120 | -0.2246 | 5.24398 |
| Maximum of Months | 299.00000 | 24.00024 | 49.33235 | 0.49593 | 10.38952 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 20.90002 | 20.69329 | -0.3319 | 8.80411 |
| February | 247.00000 | 21.29181 | 20.10117 | -0.2427 | 8.20150 |
| March | 299.00000 | 22.11759 | 16.65130 | -0.0737 | 7.04751 |
| April | 260.00000 | 23.38627 | 22.01540 | 0.27971 | 8.11101 |
| May | 286.00000 | 24.09165 | 30.33306 | -0.2248 | 7.71817 |
| June | 286.00000 | 24.59089 | 33.46418 | -0.0167 | 7.40589 |
| July | 260.00000 | 24.35447 | 51.44307 | 0.02450 | 6.48815 |
| August | 299.00000 | 24.17220 | 47.48737 | -0.0564 | 6.62940 |
| September | 260.00000 | 24.21588 | 43.16931 | -0.0325 | 6.55963 |
| October | 273.00000 | 23.61236 | 36.22610 | 0.47948 | 11.12841 |
| November | 273.00000 | 22.26226 | 24.59321 | 0.04062 | 7.36576 |
| December | 260.00000 | 20.52445 | 20.35733 | -0.4311 | 10.49431 |
| Annual Sum or Average | 3276.00000 | 22.98458 | 30.60364 | -0.0482 | 7.97402 |
| Minimum of Months | 247.00000 | 20.52445 | 16.65130 | -0.4311 | 6.48815 |
| Maximum of Months | 299.00000 | 24.59089 | 51.44307 | 0.47948 | 11.12841 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| BOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
| January | 0.608625E+10 | 0.00 | 229.61 | 336323.42 | 09-JAN-08:61 | 0.00 | 41.79 | 52.47 | 0.02 | 0.00 | 0.01 | 1.20 | 09-JAN-08:61 |
| February | 0.388450E+10 | 0.00 | 178.22 | 336323.42 | 01-FEB-08:61 | 0.00 | 42.18 | 51.13 | 0.01 | 0.00 | 0.01 | 1.20 | 01-FEB-08:61 |
| March | 0.240508E+10 | 0.00 | 113.88 | 336323.42 | 02-MAR-08:61 | 0.00 | 50.92 | 55.65 | 0.01 | 0.00 | 0.00 | 1.20 | 02-MAR-08:61 |
| April | 0.672646E+09 | 0.00 | 33.21 | 46712.99 | 12-APR-07:01 | 0.00 | 53.27 | 54.57 | 0.00 | 0.00 | 0.00 | 0.17 | 12-APR-07:01 |
| May | 0.183245E+09 | 0.00 | 9.52 | 9771.99 | 25-MAY-07:02 | 0.00 | 54.32 | 54.67 | 0.00 | 0.00 | 0.00 | 0.03 | 25-MAY-07:02 |
| June | 9098901.76 | 0.00 | 1.07 | 9875.33 | 29-JUN-07:02 | 0.00 | 50.14 | 50.19 | 0.00 | 0.00 | 0.00 | 0.04 | 29-JUN-07:02 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 50.13 | 50.13 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 |
| August | 22547871.77 | 0.00 | 2.89 | 10469.38 | 17-AUG-07:03 | 0.00 | 49.28 | 49.41 | 0.00 | 0.00 | 0.00 | 0.04 | 17-AUG-07:03 |
| September | 0.128529E+09 | 0.00 | 6.85 | 10349.01 | 08-SEP-07:02 | 0.00 | 51.87 | 52.14 | 0.00 | 0.00 | 0.00 | 0.04 | 08-SEP-07:02 |
| October | 0.525197E+09 | 0.00 | 23.60 | 9683.21 | 25-OCT-06:04 | 0.00 | 56.05 | 56.88 | 0.00 | 0.00 | 0.00 | 0.03 | 25-OCT-06:04 |
| November | 0.207971E+10 | 0.00 | 98.62 | 327400.10 | 28-NOV-08:61 | 0.00 | 51.57 | 55.83 | 0.01 | 0.00 | 0.00 | 1.17 | 28-NOV-08:61 |
| December | 0.870408E+10 | 0.00 | 251.75 | 336323.42 | 04-DEC-07:01 | 0.00 | 39.44 | 51.35 | 0.02 | 0.00 | 0.01 | 1.20 | 04-DEC-07:01 |
| Annual Sum or Average | 0.247009E+11 | 0.00 | 949.22 | 0.00 | 49.28 | 52.88 | 0.01 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.44 | 49.41 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.870408E+10 | 0.00 | 251.75 | 336323.42 | 0.00 | 56.05 | 56.88 | 0.02 | 0.00 | 0.01 | 1.20 |
Report: DXReportMonthly
For: VAV_POD_1 COOLING COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.781355E+10 | 0.238509E+10 | 53.64 | 0.779418E+10 | 19364574.88 | 0.00 | 0.72 | 03-JAN-15:02 | 0.00 | 01-JAN-00:05 | 154026.66 | 03-JAN-15:02 | 154026.66 | 03-JAN-15:02 | 2550.64 | 01-JAN-14:20 | 42413.03 | 03-JAN-15:02 | 0.00 |
| February | 0.217928E+11 | 0.630096E+10 | 84.30 | 0.217187E+11 | 74071359.62 | 0.00 | 0.86 | 21-FEB-15:05 | 0.00 | 01-FEB-00:05 | 192123.41 | 21-FEB-15:05 | 192123.41 | 21-FEB-15:05 | 38434.41 | 13-FEB-15:01 | 50837.22 | 21-FEB-15:05 | 0.00 |
| March | 0.631613E+11 | 0.178181E+11 | 184.98 | 0.631597E+11 | 1626804.00 | 0.00 | 1.00 | 14-MAR-14:40 | 0.00 | 01-MAR-00:05 | 263354.28 | 22-MAR-14:05 | 263354.28 | 22-MAR-14:05 | 1532.21 | 10-MAR-17:40 | 66886.88 | 22-MAR-14:05 | 0.00 |
| April | 0.189026E+12 | 0.507320E+11 | 323.95 | 0.188622E+12 | 0.404216E+09 | 0.00 | 1.00 | 03-APR-11:20 | 0.00 | 01-APR-00:10 | 399774.34 | 21-APR-14:02 | 399774.34 | 21-APR-14:02 | 17774.49 | 19-APR-05:01 | 107705.42 | 21-APR-14:02 | 0.00 |
| May | 0.350786E+12 | 0.934802E+11 | 470.44 | 0.343238E+12 | 0.754807E+10 | 0.00 | 1.00 | 02-MAY-13:00 | 0.00 | 01-MAY-00:03 | 448679.85 | 19-MAY-14:02 | 448679.85 | 19-MAY-14:02 | 106879.46 | 24-MAY-12:05 | 128030.94 | 19-MAY-14:02 | 0.00 |
| June | 0.459466E+12 | 0.127559E+12 | 528.28 | 0.448071E+12 | 0.113951E+11 | 0.00 | 1.00 | 01-JUN-08:70 | 0.00 | 01-JUN-00:12 | 503187.50 | 15-JUN-15:00 | 503187.50 | 15-JUN-15:00 | 96639.90 | 28-JUN-07:02 | 155496.76 | 15-JUN-15:00 | 0.00 |
| July | 0.415620E+12 | 0.110048E+12 | 475.93 | 0.344752E+12 | 0.708684E+11 | 0.00 | 1.00 | 03-JUL-07:03 | 0.00 | 01-JUL-00:23 | 494196.86 | 17-JUL-07:03 | 402261.56 | 03-JUL-14:02 | 326627.30 | 17-JUL-07:03 | 122855.06 | 26-JUL-14:02 | 0.00 |
| August | 0.361540E+12 | 0.968277E+11 | 468.21 | 0.321137E+12 | 0.404022E+11 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:03 | 424986.32 | 02-AUG-14:02 | 386803.59 | 07-AUG-16:00 | 241750.45 | 02-AUG-05:01 | 116511.41 | 07-AUG-16:00 | 0.00 |
| September | 0.369284E+12 | 0.969729E+11 | 443.67 | 0.326996E+12 | 0.422875E+11 | 0.00 | 1.00 | 01-SEP-08:30 | 0.00 | 01-SEP-00:03 | 488779.98 | 22-SEP-14:03 | 461116.16 | 19-SEP-14:02 | 241431.94 | 22-SEP-05:01 | 129060.96 | 20-SEP-14:02 | 0.00 |
| October | 0.210466E+12 | 0.558283E+11 | 321.14 | 0.192108E+12 | 0.183573E+11 | 0.00 | 1.00 | 02-OCT-09:20 | 0.00 | 01-OCT-00:03 | 512960.96 | 03-OCT-14:02 | 438881.23 | 03-OCT-14:02 | 137311.55 | 04-OCT-10:20 | 137708.72 | 03-OCT-14:02 | 0.00 |
| November | 0.474797E+11 | 0.134834E+11 | 152.91 | 0.468916E+11 | 0.588132E+09 | 0.00 | 1.00 | 03-NOV-13:40 | 0.00 | 01-NOV-00:10 | 269051.19 | 09-NOV-14:00 | 269051.19 | 09-NOV-14:00 | 33278.84 | 02-NOV-14:01 | 68330.32 | 09-NOV-14:00 | 0.00 |
| December | 0.211448E+10 | 0.667210E+09 | 25.76 | 0.210949E+10 | 4992359.16 | 0.00 | 0.44 | 08-DEC-14:05 | 0.00 | 01-DEC-00:05 | 88643.84 | 08-DEC-14:05 | 88643.84 | 08-DEC-14:05 | 3189.95 | 14-DEC-15:01 | 26239.40 | 08-DEC-14:05 | 0.00 |
| Annual Sum or Average | 0.249855E+13 | 0.672103E+12 | 3533.21 | 0.230660E+13 | 0.191951E+12 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.211448E+10 | 0.667210E+09 | 25.76 | 0.210949E+10 | 1626804.00 | 0.00 | 0.44 | 0.00 | 88643.84 | 88643.84 | 1532.21 | 26239.40 | 0.00 | ||||||
| Maximum of Months | 0.459466E+12 | 0.127559E+12 | 528.28 | 0.448071E+12 | 0.708684E+11 | 0.00 | 1.00 | 0.00 | 512960.96 | 503187.50 | 326627.30 | 155496.76 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_1:6 COOLING COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.587401E+09 | 0.155472E+09 | 96.06 | 0.531970E+09 | 55430674.77 | 0.00 | 1.00 | 01-JAN-14:02 | 0.00 | 01-JAN-00:05 | 36994.82 | 01-JAN-14:02 | 35049.77 | 05-JAN-06:01 | 15660.80 | 24-JAN-06:01 | 8501.18 | 01-JAN-14:02 | 0.00 | 01-JAN-00:05 |
| February | 0.181763E+10 | 0.450246E+09 | 108.70 | 0.177897E+10 | 38669325.20 | 0.00 | 1.00 | 01-FEB-06:01 | 0.00 | 01-FEB-00:05 | 36994.82 | 03-FEB-06:01 | 36994.82 | 04-FEB-14:02 | 16087.13 | 27-FEB-06:01 | 8758.86 | 20-FEB-14:53 | 0.00 | 01-FEB-00:05 |
| March | 0.484796E+10 | 0.120236E+10 | 193.54 | 0.480952E+10 | 38442619.55 | 0.00 | 1.00 | 01-MAR-06:01 | 0.00 | 01-MAR-00:05 | 36994.82 | 12-MAR-18:12 | 36994.82 | 04-MAR-15:23 | 9125.89 | 14-MAR-05:01 | 8758.86 | 19-MAR-13:52 | 0.00 | 01-MAR-00:05 |
| April | 0.138764E+11 | 0.350630E+10 | 311.41 | 0.127862E+11 | 0.109016E+10 | 0.00 | 1.00 | 01-APR-08:32 | 0.00 | 01-APR-00:20 | 38003.09 | 18-APR-20:53 | 36994.82 | 03-APR-03:13 | 11916.04 | 17-APR-03:32 | 9108.88 | 29-APR-09:45 | 0.00 | 01-APR-00:10 |
| May | 0.254197E+11 | 0.655550E+10 | 439.49 | 0.220576E+11 | 0.336211E+10 | 0.00 | 1.00 | 01-MAY-03:32 | 0.00 | 01-MAY-00:03 | 40220.57 | 27-MAY-20:55 | 39161.37 | 21-MAY-14:12 | 18789.57 | 25-MAY-05:32 | 11419.60 | 21-MAY-14:12 | 0.00 | 01-MAY-00:03 |
| June | 0.317232E+11 | 0.866000E+10 | 521.32 | 0.272246E+11 | 0.449863E+10 | 0.00 | 1.00 | 01-JUN-01:23 | 0.00 | 01-JUN-00:33 | 40837.32 | 27-JUN-23:33 | 38964.22 | 03-JUN-10:52 | 22131.85 | 29-JUN-01:32 | 12052.31 | 18-JUN-16:12 | 0.00 | 01-JUN-00:03 |
| July | 0.346679E+11 | 0.901871E+10 | 544.07 | 0.257594E+11 | 0.890854E+10 | 0.00 | 1.00 | 01-JUL-00:53 | 0.00 | 01-JUL-00:02 | 43275.01 | 22-JUL-06:53 | 39846.81 | 02-JUL-12:12 | 30383.61 | 20-JUL-22:52 | 12194.44 | 02-JUL-15:32 | 0.00 | 01-JUL-00:02 |
| August | 0.308642E+11 | 0.800158E+10 | 517.68 | 0.241100E+11 | 0.675415E+10 | 0.00 | 1.00 | 01-AUG-03:32 | 0.00 | 01-AUG-00:03 | 42415.16 | 01-AUG-21:33 | 37160.41 | 26-AUG-10:52 | 25499.76 | 02-AUG-04:53 | 10844.42 | 26-AUG-14:52 | 0.00 | 01-AUG-00:03 |
| September | 0.252837E+11 | 0.639764E+10 | 393.51 | 0.195716E+11 | 0.571214E+10 | 0.00 | 1.00 | 01-SEP-00:13 | 0.00 | 01-SEP-00:03 | 42096.81 | 22-SEP-01:32 | 37984.62 | 17-SEP-10:52 | 26698.72 | 22-SEP-03:32 | 10440.14 | 17-SEP-10:52 | 0.00 | 01-SEP-00:03 |
| October | 0.145748E+11 | 0.358374E+10 | 297.57 | 0.119020E+11 | 0.267286E+10 | 0.00 | 1.00 | 01-OCT-07:33 | 0.00 | 01-OCT-00:03 | 41016.15 | 03-OCT-20:53 | 36994.82 | 29-OCT-18:12 | 22407.33 | 09-OCT-08:53 | 9543.13 | 04-OCT-22:12 | 0.00 | 01-OCT-00:03 |
| November | 0.328911E+10 | 0.821633E+09 | 164.71 | 0.312615E+10 | 0.162960E+09 | 0.00 | 1.00 | 01-NOV-05:11 | 0.00 | 01-NOV-00:10 | 36994.82 | 09-NOV-06:01 | 36994.82 | 18-NOV-12:52 | 17604.40 | 03-NOV-05:01 | 8501.18 | 01-NOV-05:11 | 0.00 | 01-NOV-00:10 |
| December | 0.242222E+09 | 64354098.22 | 71.53 | 0.212848E+09 | 29374469.13 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:05 | 36994.82 | 01-DEC-06:01 | 36994.82 | 20-DEC-06:01 | 12722.85 | 14-DEC-06:01 | 8501.18 | 01-DEC-06:01 | 0.00 | 01-DEC-00:05 |
| Annual Sum or Average | 0.187194E+12 | 0.484175E+11 | 3659.58 | 0.153871E+12 | 0.333235E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.242222E+09 | 64354098.22 | 71.53 | 0.212848E+09 | 29374469.13 | 0.00 | 1.00 | 0.00 | 36994.82 | 35049.77 | 9125.89 | 8501.18 | 0.00 | |||||||
| Maximum of Months | 0.346679E+11 | 0.901871E+10 | 544.07 | 0.272246E+11 | 0.890854E+10 | 0.00 | 1.00 | 0.00 | 43275.01 | 39846.81 | 30383.61 | 12194.44 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:7 COOLING COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.193210E+09 | 52550201.80 | 10.67 | 0.186046E+09 | 7163976.59 | 0.00 | 0.40 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 | 13526.98 | 03-JAN-15:00 | 13526.98 | 03-JAN-15:00 | 818.16 | 12-JAN-15:00 | 3532.12 | 03-JAN-15:00 | 0.00 | 01-JAN-00:05 |
| February | 0.142456E+10 | 0.371902E+09 | 35.33 | 0.142070E+10 | 3861184.89 | 0.00 | 0.63 | 21-FEB-15:00 | 0.00 | 01-FEB-00:05 | 22927.70 | 21-FEB-15:00 | 22927.70 | 21-FEB-15:00 | 336.94 | 27-FEB-14:00 | 5767.69 | 21-FEB-15:00 | 0.00 | 01-FEB-00:05 |
| March | 0.473545E+10 | 0.123631E+10 | 115.94 | 0.473370E+10 | 1746673.14 | 0.00 | 0.82 | 22-MAR-13:00 | 0.00 | 01-MAR-00:05 | 30967.48 | 22-MAR-13:00 | 30967.48 | 22-MAR-13:00 | 199.35 | 15-MAR-09:30 | 7687.22 | 22-MAR-13:00 | 0.00 | 01-MAR-00:05 |
| April | 0.163342E+11 | 0.425700E+10 | 236.38 | 0.159308E+11 | 0.403422E+09 | 0.00 | 1.00 | 02-APR-11:23 | 0.00 | 01-APR-00:10 | 74956.84 | 30-APR-10:13 | 74937.29 | 20-APR-05:42 | 23248.95 | 17-APR-05:01 | 17888.78 | 30-APR-10:13 | 0.00 | 01-APR-00:10 |
| May | 0.338034E+11 | 0.888062E+10 | 366.10 | 0.312778E+11 | 0.252564E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:03 | 81283.02 | 27-MAY-21:11 | 74937.29 | 11-MAY-05:02 | 37742.32 | 25-MAY-05:01 | 19238.08 | 27-MAY-21:11 | 0.00 | 01-MAY-00:03 |
| June | 0.482929E+11 | 0.134583E+11 | 421.11 | 0.441858E+11 | 0.410713E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:03 | 80342.95 | 04-JUN-07:11 | 74937.29 | 12-JUN-05:01 | 40148.95 | 28-JUN-05:01 | 19201.12 | 14-JUN-14:00 | 0.00 | 01-JUN-00:03 |
| July | 0.400291E+11 | 0.108040E+11 | 415.96 | 0.312103E+11 | 0.881883E+10 | 0.00 | 1.00 | 01-JUL-12:44 | 0.00 | 01-JUL-00:02 | 86900.53 | 21-JUL-05:01 | 65114.13 | 03-JUL-05:01 | 59907.88 | 21-JUL-05:01 | 20253.79 | 03-JUL-05:01 | 0.00 | 01-JUL-00:02 |
| August | 0.340905E+11 | 0.929986E+10 | 409.90 | 0.279808E+11 | 0.610973E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:03 | 85784.91 | 03-AUG-06:00 | 68014.81 | 24-AUG-05:01 | 51369.12 | 02-AUG-05:01 | 19706.29 | 03-AUG-05:01 | 0.00 | 01-AUG-00:03 |
| September | 0.371086E+11 | 0.951277E+10 | 344.51 | 0.294789E+11 | 0.762973E+10 | 0.00 | 1.00 | 01-SEP-05:02 | 0.00 | 01-SEP-00:03 | 84751.83 | 22-SEP-05:01 | 74089.71 | 24-SEP-16:41 | 53904.55 | 22-SEP-05:01 | 19868.61 | 09-SEP-09:13 | 0.00 | 01-SEP-00:03 |
| October | 0.186269E+11 | 0.467442E+10 | 238.73 | 0.150113E+11 | 0.361558E+10 | 0.00 | 1.00 | 02-OCT-05:01 | 0.00 | 01-OCT-00:03 | 80364.18 | 08-OCT-12:31 | 73283.50 | 29-OCT-11:51 | 43400.28 | 04-OCT-05:01 | 18978.45 | 08-OCT-12:31 | 0.00 | 01-OCT-00:03 |
| November | 0.302311E+10 | 0.785670E+09 | 82.93 | 0.283918E+10 | 0.183936E+09 | 0.00 | 0.78 | 08-NOV-15:00 | 0.00 | 01-NOV-00:10 | 29390.13 | 03-NOV-14:00 | 29099.50 | 08-NOV-15:00 | 5335.36 | 03-NOV-12:00 | 7163.09 | 08-NOV-15:00 | 0.00 | 01-NOV-00:10 |
| December | 18086343.79 | 5128089.30 | 2.67 | 18023047.90 | 63295.89 | 0.00 | 0.12 | 08-DEC-14:00 | 0.00 | 01-DEC-00:05 | 3843.52 | 08-DEC-14:00 | 3843.52 | 08-DEC-14:00 | 20.20 | 08-DEC-15:00 | 1080.44 | 08-DEC-14:00 | 0.00 | 01-DEC-00:05 |
| Annual Sum or Average | 0.237680E+12 | 0.633385E+11 | 2680.23 | 0.204273E+12 | 0.334068E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 18086343.79 | 5128089.30 | 2.67 | 18023047.90 | 63295.89 | 0.00 | 0.12 | 0.00 | 3843.52 | 3843.52 | 20.20 | 1080.44 | 0.00 | |||||||
| Maximum of Months | 0.482929E+11 | 0.134583E+11 | 421.11 | 0.441858E+11 | 0.881883E+10 | 0.00 | 1.00 | 0.00 | 86900.53 | 74937.29 | 59907.88 | 20253.79 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 98.97 | 55.74 | 43.23 | 98.61 | 226.03 | 0.00 | 0.00 | 0.00 |
| February | 111.68 | 59.36 | 52.32 | 121.45 | 200.91 | 0.00 | 0.00 | 0.00 |
| March | 152.19 | 81.57 | 70.62 | 189.34 | 168.16 | 0.00 | 0.00 | 0.00 |
| April | 174.93 | 94.48 | 80.45 | 264.89 | 100.47 | 0.00 | 0.00 | 0.00 |
| May | 188.42 | 100.81 | 87.60 | 327.08 | 56.92 | 0.00 | 0.00 | 0.00 |
| June | 183.41 | 98.51 | 84.90 | 366.28 | 25.77 | 0.00 | 0.00 | 0.00 |
| July | 162.76 | 80.88 | 81.88 | 326.69 | 21.07 | 0.00 | 0.00 | 0.00 |
| August | 157.63 | 80.33 | 77.29 | 298.84 | 33.81 | 0.00 | 0.00 | 0.00 |
| September | 161.20 | 89.80 | 71.39 | 282.57 | 71.82 | 0.00 | 0.00 | 0.00 |
| October | 138.76 | 80.99 | 57.78 | 202.15 | 124.83 | 0.00 | 0.00 | 0.00 |
| November | 116.47 | 70.92 | 45.55 | 133.54 | 207.05 | 0.00 | 0.00 | 0.00 |
| December | 93.86 | 50.99 | 42.87 | 87.18 | 249.08 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.14 | 78.75 | 66.39 | 225.33 | 123.44 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 93.86 | 50.99 | 42.87 | 87.18 | 21.07 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 188.42 | 100.81 | 87.60 | 366.28 | 249.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 36.99 | 28.02 | 8.97 | 49.24 | 31.05 | 0.00 | 0.00 | 0.00 |
| February | 34.31 | 24.19 | 10.12 | 46.57 | 27.93 | 0.00 | 0.00 | 0.00 |
| March | 27.89 | 16.08 | 11.81 | 38.82 | 24.87 | 0.00 | 0.00 | 0.00 |
| April | 18.91 | 7.05 | 11.85 | 30.11 | 15.71 | 0.00 | 0.00 | 0.00 |
| May | 13.36 | 1.87 | 11.49 | 24.26 | 8.85 | 0.00 | 0.00 | 0.00 |
| June | 11.53 | 0.73 | 10.80 | 26.87 | 3.92 | 0.00 | 0.00 | 0.00 |
| July | 11.75 | 1.09 | 10.66 | 27.21 | 3.26 | 0.00 | 0.00 | 0.00 |
| August | 14.98 | 3.97 | 11.01 | 31.69 | 5.22 | 0.00 | 0.00 | 0.00 |
| September | 23.38 | 12.15 | 11.23 | 44.09 | 10.92 | 0.00 | 0.00 | 0.00 |
| October | 31.77 | 21.48 | 10.29 | 50.17 | 18.33 | 0.00 | 0.00 | 0.00 |
| November | 38.23 | 29.15 | 9.08 | 53.04 | 28.43 | 0.00 | 0.00 | 0.00 |
| December | 37.89 | 28.44 | 9.45 | 49.18 | 33.66 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 25.03 | 14.46 | 10.57 | 39.22 | 17.63 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11.53 | 0.73 | 8.97 | 24.26 | 3.26 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 38.23 | 29.15 | 11.85 | 53.04 | 33.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 256.73 | 194.50 | 62.23 | 341.71 | 215.48 | 0.00 | 0.00 | 0.00 |
| February | 238.14 | 167.89 | 70.26 | 323.24 | 193.87 | 0.00 | 0.00 | 0.00 |
| March | 193.54 | 111.59 | 81.95 | 269.41 | 172.58 | 0.00 | 0.00 | 0.00 |
| April | 131.22 | 48.96 | 82.26 | 208.94 | 109.06 | 0.00 | 0.00 | 0.00 |
| May | 92.73 | 12.98 | 79.75 | 167.98 | 61.42 | 0.00 | 0.00 | 0.00 |
| June | 80.00 | 5.08 | 74.93 | 185.76 | 27.20 | 0.00 | 0.00 | 0.00 |
| July | 81.56 | 7.56 | 74.00 | 188.36 | 22.63 | 0.00 | 0.00 | 0.00 |
| August | 103.96 | 27.52 | 76.44 | 219.84 | 36.24 | 0.00 | 0.00 | 0.00 |
| September | 162.27 | 84.30 | 77.97 | 306.01 | 75.75 | 0.00 | 0.00 | 0.00 |
| October | 220.48 | 149.06 | 71.42 | 348.23 | 127.24 | 0.00 | 0.00 | 0.00 |
| November | 265.32 | 202.28 | 63.05 | 368.09 | 197.30 | 0.00 | 0.00 | 0.00 |
| December | 262.95 | 197.38 | 65.57 | 341.29 | 233.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 173.71 | 100.38 | 73.33 | 272.04 | 122.34 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 80.00 | 5.08 | 62.23 | 167.98 | 22.63 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 265.32 | 202.28 | 82.26 | 368.09 | 233.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 471.74 | 357.39 | 114.35 | 620.83 | 424.17 | 0.00 | 0.00 | 0.00 |
| February | 437.59 | 308.50 | 129.10 | 586.51 | 382.39 | 0.00 | 0.00 | 0.00 |
| March | 355.64 | 205.06 | 150.58 | 489.38 | 337.87 | 0.00 | 0.00 | 0.00 |
| April | 241.12 | 89.97 | 151.15 | 384.25 | 208.46 | 0.00 | 0.00 | 0.00 |
| May | 170.40 | 23.85 | 146.55 | 313.24 | 113.66 | 0.00 | 0.00 | 0.00 |
| June | 147.01 | 9.33 | 137.68 | 349.52 | 48.46 | 0.00 | 0.00 | 0.00 |
| July | 149.86 | 13.89 | 135.97 | 363.05 | 36.48 | 0.00 | 0.00 | 0.00 |
| August | 191.03 | 50.57 | 140.46 | 417.52 | 61.46 | 0.00 | 0.00 | 0.00 |
| September | 298.18 | 154.91 | 143.26 | 569.20 | 136.55 | 0.00 | 0.00 | 0.00 |
| October | 405.13 | 273.90 | 131.24 | 642.58 | 238.87 | 0.00 | 0.00 | 0.00 |
| November | 487.54 | 371.69 | 115.85 | 672.92 | 380.64 | 0.00 | 0.00 | 0.00 |
| December | 483.17 | 362.69 | 120.48 | 619.44 | 455.68 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 319.19 | 184.45 | 134.74 | 501.77 | 234.64 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 147.01 | 9.33 | 114.35 | 313.24 | 36.48 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 487.54 | 371.69 | 151.15 | 672.92 | 455.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 471.74 | 357.39 | 114.35 | 620.83 | 424.17 | 0.00 | 0.00 | 0.00 |
| February | 437.59 | 308.50 | 129.10 | 586.51 | 382.39 | 0.00 | 0.00 | 0.00 |
| March | 355.64 | 205.06 | 150.58 | 489.38 | 337.87 | 0.00 | 0.00 | 0.00 |
| April | 241.12 | 89.97 | 151.15 | 384.25 | 208.46 | 0.00 | 0.00 | 0.00 |
| May | 170.40 | 23.85 | 146.55 | 313.24 | 113.66 | 0.00 | 0.00 | 0.00 |
| June | 147.01 | 9.33 | 137.68 | 349.52 | 48.46 | 0.00 | 0.00 | 0.00 |
| July | 149.86 | 13.89 | 135.97 | 363.05 | 36.48 | 0.00 | 0.00 | 0.00 |
| August | 191.03 | 50.57 | 140.46 | 417.52 | 61.46 | 0.00 | 0.00 | 0.00 |
| September | 298.18 | 154.91 | 143.26 | 569.20 | 136.55 | 0.00 | 0.00 | 0.00 |
| October | 405.13 | 273.90 | 131.24 | 642.58 | 238.87 | 0.00 | 0.00 | 0.00 |
| November | 487.54 | 371.69 | 115.85 | 672.92 | 380.64 | 0.00 | 0.00 | 0.00 |
| December | 483.17 | 362.69 | 120.48 | 619.44 | 455.68 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 319.19 | 184.45 | 134.74 | 501.77 | 234.64 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 147.01 | 9.33 | 114.35 | 313.24 | 36.48 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 487.54 | 371.69 | 151.15 | 672.92 | 455.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 471.73 | 357.39 | 114.35 | 620.82 | 424.16 | 0.00 | 0.00 | 0.00 |
| February | 437.59 | 308.49 | 129.09 | 586.50 | 382.38 | 0.00 | 0.00 | 0.00 |
| March | 355.63 | 205.05 | 150.57 | 489.37 | 337.86 | 0.00 | 0.00 | 0.00 |
| April | 241.11 | 89.97 | 151.15 | 384.24 | 208.46 | 0.00 | 0.00 | 0.00 |
| May | 170.39 | 23.85 | 146.54 | 313.23 | 113.66 | 0.00 | 0.00 | 0.00 |
| June | 147.01 | 9.33 | 137.68 | 349.52 | 48.46 | 0.00 | 0.00 | 0.00 |
| July | 149.86 | 13.89 | 135.96 | 363.05 | 36.48 | 0.00 | 0.00 | 0.00 |
| August | 191.03 | 50.57 | 140.46 | 417.51 | 61.46 | 0.00 | 0.00 | 0.00 |
| September | 298.17 | 154.91 | 143.26 | 569.19 | 136.55 | 0.00 | 0.00 | 0.00 |
| October | 405.13 | 273.89 | 131.23 | 642.57 | 238.87 | 0.00 | 0.00 | 0.00 |
| November | 487.53 | 371.68 | 115.85 | 672.91 | 380.63 | 0.00 | 0.00 | 0.00 |
| December | 483.16 | 362.68 | 120.48 | 619.43 | 455.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 319.18 | 184.44 | 134.74 | 501.76 | 234.64 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 147.01 | 9.33 | 114.35 | 313.23 | 36.48 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 487.53 | 371.68 | 151.15 | 672.91 | 455.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 32.99 | 18.58 | 14.41 | 33.91 | 77.41 | 0.00 | 0.00 | 0.00 |
| February | 37.23 | 19.79 | 17.44 | 41.41 | 69.90 | 0.00 | 0.00 | 0.00 |
| March | 50.73 | 27.19 | 23.54 | 62.99 | 59.81 | 0.00 | 0.00 | 0.00 |
| April | 58.31 | 31.49 | 26.82 | 87.95 | 35.31 | 0.00 | 0.00 | 0.00 |
| May | 62.81 | 33.60 | 29.20 | 108.67 | 19.77 | 0.00 | 0.00 | 0.00 |
| June | 61.14 | 32.84 | 28.30 | 122.54 | 8.96 | 0.00 | 0.00 | 0.00 |
| July | 54.25 | 26.96 | 27.29 | 110.13 | 6.62 | 0.00 | 0.00 | 0.00 |
| August | 52.54 | 26.78 | 25.76 | 101.36 | 10.42 | 0.00 | 0.00 | 0.00 |
| September | 53.73 | 29.93 | 23.80 | 95.61 | 22.99 | 0.00 | 0.00 | 0.00 |
| October | 46.25 | 27.00 | 19.26 | 68.60 | 41.14 | 0.00 | 0.00 | 0.00 |
| November | 38.82 | 23.64 | 15.18 | 45.46 | 69.94 | 0.00 | 0.00 | 0.00 |
| December | 31.29 | 17.00 | 14.29 | 30.32 | 84.58 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.38 | 26.25 | 22.13 | 75.90 | 42.10 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.29 | 17.00 | 14.29 | 30.32 | 6.62 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 62.81 | 33.60 | 29.20 | 122.54 | 84.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 98.97 | 55.74 | 43.23 | 108.34 | 201.79 | 0.00 | 0.00 | 0.00 |
| February | 111.68 | 59.36 | 52.32 | 132.08 | 181.15 | 0.00 | 0.00 | 0.00 |
| March | 152.19 | 81.57 | 70.62 | 197.83 | 156.88 | 0.00 | 0.00 | 0.00 |
| April | 174.93 | 94.48 | 80.45 | 269.71 | 96.21 | 0.00 | 0.00 | 0.00 |
| May | 188.42 | 100.81 | 87.60 | 328.32 | 56.40 | 0.00 | 0.00 | 0.00 |
| June | 183.41 | 98.51 | 84.90 | 366.09 | 25.98 | 0.00 | 0.00 | 0.00 |
| July | 162.76 | 80.88 | 81.88 | 327.39 | 20.93 | 0.00 | 0.00 | 0.00 |
| August | 157.63 | 80.33 | 77.29 | 302.52 | 32.03 | 0.00 | 0.00 | 0.00 |
| September | 161.20 | 89.80 | 71.39 | 288.00 | 67.47 | 0.00 | 0.00 | 0.00 |
| October | 138.76 | 80.99 | 57.78 | 209.45 | 115.70 | 0.00 | 0.00 | 0.00 |
| November | 116.47 | 70.92 | 45.55 | 141.78 | 187.05 | 0.00 | 0.00 | 0.00 |
| December | 93.86 | 50.99 | 42.87 | 96.38 | 225.48 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.14 | 78.75 | 66.39 | 231.08 | 113.59 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 93.86 | 50.99 | 42.87 | 96.38 | 20.93 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 188.42 | 100.81 | 87.60 | 366.09 | 225.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.16 | 0.00 | 4.16 | 0.25 | 33.03 | 0.00 | 0.00 | 0.00 |
| February | 5.11 | 0.00 | 5.11 | 1.58 | 28.95 | 0.00 | 0.00 | 0.00 |
| March | 6.84 | 0.00 | 6.84 | 3.62 | 24.73 | 0.00 | 0.00 | 0.00 |
| April | 7.85 | 0.07 | 7.78 | 8.80 | 14.15 | 0.00 | 0.00 | 0.00 |
| May | 9.54 | 0.84 | 8.70 | 16.71 | 7.23 | 0.00 | 0.00 | 0.00 |
| June | 10.39 | 1.55 | 8.84 | 25.78 | 3.23 | 0.00 | 0.00 | 0.00 |
| July | 9.38 | 1.10 | 8.28 | 23.21 | 2.68 | 0.00 | 0.00 | 0.00 |
| August | 7.64 | 0.19 | 7.45 | 17.17 | 4.24 | 0.00 | 0.00 | 0.00 |
| September | 6.61 | 0.00 | 6.61 | 11.99 | 9.61 | 0.00 | 0.00 | 0.00 |
| October | 5.51 | 0.00 | 5.51 | 4.88 | 17.78 | 0.00 | 0.00 | 0.00 |
| November | 4.43 | 0.00 | 4.43 | 0.56 | 30.48 | 0.00 | 0.00 | 0.00 |
| December | 4.10 | 0.00 | 4.10 | 0.20 | 37.29 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 6.80 | 0.31 | 6.49 | 9.60 | 17.73 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4.10 | 0.00 | 4.10 | 0.20 | 2.68 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 10.39 | 1.55 | 8.84 | 25.78 | 37.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.90 | 0.00 | 30.90 | 2.42 | 228.22 | 0.00 | 0.00 | 0.00 |
| February | 37.87 | 0.00 | 37.87 | 12.64 | 200.93 | 0.00 | 0.00 | 0.00 |
| March | 50.37 | 0.00 | 50.37 | 27.84 | 172.10 | 0.00 | 0.00 | 0.00 |
| April | 57.88 | 0.50 | 57.39 | 64.79 | 99.30 | 0.00 | 0.00 | 0.00 |
| May | 69.90 | 5.84 | 64.06 | 120.50 | 51.71 | 0.00 | 0.00 | 0.00 |
| June | 75.67 | 10.75 | 64.92 | 182.94 | 23.35 | 0.00 | 0.00 | 0.00 |
| July | 68.65 | 7.61 | 61.04 | 165.78 | 19.35 | 0.00 | 0.00 | 0.00 |
| August | 56.47 | 1.30 | 55.17 | 123.71 | 30.35 | 0.00 | 0.00 | 0.00 |
| September | 49.04 | 0.02 | 49.02 | 87.44 | 68.00 | 0.00 | 0.00 | 0.00 |
| October | 40.84 | 0.00 | 40.84 | 36.96 | 124.08 | 0.00 | 0.00 | 0.00 |
| November | 32.88 | 0.00 | 32.88 | 4.95 | 210.98 | 0.00 | 0.00 | 0.00 |
| December | 30.50 | 0.00 | 30.50 | 1.78 | 257.87 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 50.14 | 2.18 | 47.96 | 69.61 | 123.48 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.50 | 0.00 | 30.50 | 1.78 | 19.35 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 75.67 | 10.75 | 64.92 | 182.94 | 257.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 50.52 | 0.00 | 50.52 | 1.67 | 450.09 | 0.00 | 0.00 | 0.00 |
| February | 62.06 | 0.00 | 62.06 | 15.91 | 395.62 | 0.00 | 0.00 | 0.00 |
| March | 83.32 | 0.00 | 83.32 | 39.17 | 336.49 | 0.00 | 0.00 | 0.00 |
| April | 94.65 | 0.46 | 94.19 | 108.85 | 188.64 | 0.00 | 0.00 | 0.00 |
| May | 111.74 | 7.31 | 104.43 | 205.92 | 94.48 | 0.00 | 0.00 | 0.00 |
| June | 120.92 | 14.70 | 106.22 | 319.68 | 39.07 | 0.00 | 0.00 | 0.00 |
| July | 108.49 | 9.61 | 98.89 | 297.06 | 28.65 | 0.00 | 0.00 | 0.00 |
| August | 91.12 | 1.43 | 89.70 | 230.26 | 47.74 | 0.00 | 0.00 | 0.00 |
| September | 80.50 | 0.02 | 80.48 | 156.57 | 115.55 | 0.00 | 0.00 | 0.00 |
| October | 67.07 | 0.00 | 67.07 | 61.30 | 226.68 | 0.00 | 0.00 | 0.00 |
| November | 53.94 | 0.00 | 53.94 | 5.77 | 405.44 | 0.00 | 0.00 | 0.00 |
| December | 49.66 | 0.00 | 49.66 | 1.26 | 502.76 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.25 | 2.81 | 78.45 | 120.84 | 235.16 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 49.66 | 0.00 | 49.66 | 1.26 | 28.65 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.92 | 14.70 | 106.22 | 319.68 | 502.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 53.10 | 0.00 | 53.10 | 2.12 | 450.90 | 0.00 | 0.00 | 0.00 |
| February | 65.15 | 0.00 | 65.15 | 17.24 | 397.23 | 0.00 | 0.00 | 0.00 |
| March | 87.22 | 0.00 | 87.22 | 42.01 | 338.33 | 0.00 | 0.00 | 0.00 |
| April | 99.87 | 0.82 | 99.05 | 112.56 | 189.01 | 0.00 | 0.00 | 0.00 |
| May | 120.10 | 9.64 | 110.45 | 214.98 | 93.18 | 0.00 | 0.00 | 0.00 |
| June | 130.58 | 18.37 | 112.21 | 334.12 | 39.69 | 0.00 | 0.00 | 0.00 |
| July | 117.73 | 12.71 | 105.02 | 312.02 | 29.23 | 0.00 | 0.00 | 0.00 |
| August | 97.06 | 2.20 | 94.86 | 237.54 | 48.21 | 0.00 | 0.00 | 0.00 |
| September | 84.33 | 0.03 | 84.30 | 160.37 | 117.93 | 0.00 | 0.00 | 0.00 |
| October | 70.34 | 0.00 | 70.34 | 64.12 | 228.74 | 0.00 | 0.00 | 0.00 |
| November | 56.58 | 0.00 | 56.58 | 6.43 | 406.95 | 0.00 | 0.00 | 0.00 |
| December | 52.31 | 0.00 | 52.31 | 1.64 | 504.16 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 86.30 | 3.66 | 82.63 | 126.01 | 236.18 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 52.31 | 0.00 | 52.31 | 1.64 | 29.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 130.58 | 18.37 | 112.21 | 334.12 | 504.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 53.12 | 0.00 | 53.12 | 2.13 | 450.88 | 0.00 | 0.00 | 0.00 |
| February | 65.18 | 0.00 | 65.18 | 17.26 | 397.22 | 0.00 | 0.00 | 0.00 |
| March | 87.25 | 0.00 | 87.25 | 42.04 | 338.33 | 0.00 | 0.00 | 0.00 |
| April | 100.15 | 0.91 | 99.24 | 112.60 | 188.44 | 0.00 | 0.00 | 0.00 |
| May | 121.38 | 10.48 | 110.90 | 217.28 | 92.85 | 0.00 | 0.00 | 0.00 |
| June | 131.57 | 19.03 | 112.54 | 336.04 | 39.69 | 0.00 | 0.00 | 0.00 |
| July | 118.89 | 13.47 | 105.43 | 314.26 | 29.16 | 0.00 | 0.00 | 0.00 |
| August | 97.47 | 2.39 | 95.09 | 238.15 | 47.96 | 0.00 | 0.00 | 0.00 |
| September | 84.40 | 0.03 | 84.37 | 160.41 | 117.86 | 0.00 | 0.00 | 0.00 |
| October | 70.37 | 0.00 | 70.37 | 64.14 | 228.74 | 0.00 | 0.00 | 0.00 |
| November | 56.60 | 0.00 | 56.60 | 6.43 | 406.95 | 0.00 | 0.00 | 0.00 |
| December | 52.33 | 0.00 | 52.33 | 1.65 | 504.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 86.66 | 3.88 | 82.78 | 126.62 | 236.07 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 52.33 | 0.00 | 52.33 | 1.65 | 29.16 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 131.57 | 19.03 | 112.54 | 336.04 | 504.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 98.97 | 55.74 | 43.23 | 98.76 | 225.79 | 0.00 | 0.00 | 0.00 |
| February | 111.68 | 59.36 | 52.32 | 121.61 | 200.94 | 0.00 | 0.00 | 0.00 |
| March | 152.19 | 81.57 | 70.62 | 189.50 | 168.31 | 0.00 | 0.00 | 0.00 |
| April | 174.93 | 94.48 | 80.45 | 265.07 | 100.61 | 0.00 | 0.00 | 0.00 |
| May | 188.42 | 100.81 | 87.60 | 327.32 | 56.98 | 0.00 | 0.00 | 0.00 |
| June | 183.41 | 98.51 | 84.90 | 366.52 | 25.78 | 0.00 | 0.00 | 0.00 |
| July | 162.76 | 80.88 | 81.88 | 327.21 | 20.93 | 0.00 | 0.00 | 0.00 |
| August | 157.63 | 80.33 | 77.29 | 299.28 | 33.68 | 0.00 | 0.00 | 0.00 |
| September | 161.20 | 89.80 | 71.39 | 282.81 | 71.80 | 0.00 | 0.00 | 0.00 |
| October | 138.76 | 80.99 | 57.78 | 202.32 | 124.87 | 0.00 | 0.00 | 0.00 |
| November | 116.47 | 70.92 | 45.55 | 133.68 | 206.96 | 0.00 | 0.00 | 0.00 |
| December | 93.86 | 50.99 | 42.87 | 87.36 | 248.71 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.14 | 78.75 | 66.39 | 225.57 | 123.39 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 93.86 | 50.99 | 42.87 | 87.36 | 20.93 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 188.42 | 100.81 | 87.60 | 366.52 | 248.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 36.21 | 27.99 | 8.22 | 48.35 | 30.52 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 24.14 | 9.22 | 45.51 | 27.45 | 0.00 | 0.00 | 0.00 |
| March | 26.82 | 16.08 | 10.74 | 37.51 | 24.28 | 0.00 | 0.00 | 0.00 |
| April | 17.66 | 7.05 | 10.61 | 28.65 | 15.19 | 0.00 | 0.00 | 0.00 |
| May | 12.02 | 1.87 | 10.15 | 22.65 | 8.33 | 0.00 | 0.00 | 0.00 |
| June | 10.24 | 0.73 | 9.50 | 25.44 | 3.58 | 0.00 | 0.00 | 0.00 |
| July | 10.45 | 1.09 | 9.36 | 25.56 | 2.97 | 0.00 | 0.00 | 0.00 |
| August | 13.72 | 3.97 | 9.75 | 30.09 | 4.86 | 0.00 | 0.00 | 0.00 |
| September | 22.24 | 12.15 | 10.09 | 42.61 | 10.40 | 0.00 | 0.00 | 0.00 |
| October | 30.79 | 21.45 | 9.34 | 48.95 | 17.85 | 0.00 | 0.00 | 0.00 |
| November | 37.24 | 28.99 | 8.25 | 52.10 | 28.16 | 0.00 | 0.00 | 0.00 |
| December | 36.86 | 28.21 | 8.65 | 48.16 | 33.29 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 23.91 | 14.42 | 9.49 | 37.91 | 17.19 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 10.24 | 0.73 | 8.22 | 22.65 | 2.97 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 37.24 | 28.99 | 10.74 | 52.10 | 33.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 248.79 | 194.24 | 54.55 | 332.45 | 209.84 | 0.00 | 0.00 | 0.00 |
| February | 228.53 | 167.51 | 61.02 | 312.16 | 188.37 | 0.00 | 0.00 | 0.00 |
| March | 182.52 | 111.58 | 70.94 | 255.87 | 166.51 | 0.00 | 0.00 | 0.00 |
| April | 118.36 | 48.96 | 69.40 | 193.83 | 103.65 | 0.00 | 0.00 | 0.00 |
| May | 78.87 | 12.98 | 65.89 | 151.37 | 56.11 | 0.00 | 0.00 | 0.00 |
| June | 66.67 | 5.08 | 61.59 | 170.93 | 23.76 | 0.00 | 0.00 | 0.00 |
| July | 68.13 | 7.56 | 60.57 | 171.16 | 19.72 | 0.00 | 0.00 | 0.00 |
| August | 90.93 | 27.52 | 63.41 | 203.14 | 32.65 | 0.00 | 0.00 | 0.00 |
| September | 150.45 | 84.30 | 66.15 | 290.66 | 70.46 | 0.00 | 0.00 | 0.00 |
| October | 210.52 | 148.85 | 61.67 | 335.56 | 122.04 | 0.00 | 0.00 | 0.00 |
| November | 255.86 | 201.21 | 54.65 | 358.51 | 193.28 | 0.00 | 0.00 | 0.00 |
| December | 253.29 | 195.79 | 57.50 | 331.24 | 228.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 162.37 | 100.08 | 62.28 | 258.53 | 117.56 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 66.67 | 5.08 | 54.55 | 151.37 | 19.72 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 255.86 | 201.21 | 70.94 | 358.51 | 228.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 452.64 | 354.77 | 97.87 | 599.44 | 413.91 | 0.00 | 0.00 | 0.00 |
| February | 417.66 | 307.81 | 109.85 | 563.63 | 370.66 | 0.00 | 0.00 | 0.00 |
| March | 332.61 | 205.02 | 127.60 | 461.00 | 326.05 | 0.00 | 0.00 | 0.00 |
| April | 214.26 | 89.97 | 124.30 | 352.82 | 197.66 | 0.00 | 0.00 | 0.00 |
| May | 141.45 | 23.85 | 117.60 | 279.01 | 102.93 | 0.00 | 0.00 | 0.00 |
| June | 119.16 | 9.33 | 109.83 | 319.21 | 41.43 | 0.00 | 0.00 | 0.00 |
| July | 121.83 | 13.89 | 107.94 | 328.68 | 30.62 | 0.00 | 0.00 | 0.00 |
| August | 163.81 | 50.57 | 113.25 | 384.22 | 54.08 | 0.00 | 0.00 | 0.00 |
| September | 273.50 | 154.90 | 118.60 | 537.72 | 125.25 | 0.00 | 0.00 | 0.00 |
| October | 384.23 | 273.38 | 110.85 | 616.30 | 227.54 | 0.00 | 0.00 | 0.00 |
| November | 466.94 | 368.75 | 98.19 | 652.33 | 372.22 | 0.00 | 0.00 | 0.00 |
| December | 458.49 | 355.46 | 103.04 | 594.17 | 447.89 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 294.84 | 183.27 | 111.58 | 473.40 | 225.12 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 119.16 | 9.33 | 97.87 | 279.01 | 30.62 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 466.94 | 368.75 | 127.60 | 652.33 | 447.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 451.01 | 353.46 | 97.56 | 599.12 | 416.73 | 0.00 | 0.00 | 0.00 |
| February | 416.77 | 307.15 | 109.62 | 563.36 | 372.37 | 0.00 | 0.00 | 0.00 |
| March | 332.48 | 204.96 | 127.52 | 460.96 | 326.29 | 0.00 | 0.00 | 0.00 |
| April | 214.23 | 89.97 | 124.26 | 352.78 | 197.64 | 0.00 | 0.00 | 0.00 |
| May | 141.41 | 23.85 | 117.56 | 278.97 | 102.91 | 0.00 | 0.00 | 0.00 |
| June | 119.13 | 9.33 | 109.80 | 319.17 | 41.42 | 0.00 | 0.00 | 0.00 |
| July | 121.79 | 13.89 | 107.90 | 328.64 | 30.62 | 0.00 | 0.00 | 0.00 |
| August | 163.78 | 50.57 | 113.21 | 384.17 | 54.07 | 0.00 | 0.00 | 0.00 |
| September | 273.44 | 154.88 | 118.56 | 537.67 | 125.31 | 0.00 | 0.00 | 0.00 |
| October | 383.86 | 273.11 | 110.75 | 615.97 | 227.98 | 0.00 | 0.00 | 0.00 |
| November | 465.14 | 367.28 | 97.85 | 651.54 | 375.11 | 0.00 | 0.00 | 0.00 |
| December | 456.68 | 353.91 | 102.77 | 593.80 | 450.95 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 294.27 | 182.82 | 111.45 | 473.20 | 226.05 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 119.13 | 9.33 | 97.56 | 278.97 | 30.62 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 465.14 | 367.28 | 127.52 | 651.54 | 450.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 422.35 | 330.72 | 91.64 | 555.27 | 419.04 | 0.00 | 0.00 | 0.00 |
| February | 391.13 | 288.02 | 103.11 | 525.24 | 376.87 | 0.00 | 0.00 | 0.00 |
| March | 317.71 | 196.19 | 121.52 | 438.80 | 327.65 | 0.00 | 0.00 | 0.00 |
| April | 206.80 | 87.69 | 119.11 | 341.83 | 195.19 | 0.00 | 0.00 | 0.00 |
| May | 136.24 | 23.46 | 112.79 | 273.10 | 100.29 | 0.00 | 0.00 | 0.00 |
| June | 114.72 | 9.21 | 105.51 | 315.54 | 39.85 | 0.00 | 0.00 | 0.00 |
| July | 117.06 | 13.69 | 103.37 | 323.16 | 29.45 | 0.00 | 0.00 | 0.00 |
| August | 157.80 | 49.40 | 108.40 | 375.67 | 52.58 | 0.00 | 0.00 | 0.00 |
| September | 262.88 | 149.49 | 113.38 | 519.69 | 123.64 | 0.00 | 0.00 | 0.00 |
| October | 363.92 | 259.33 | 104.59 | 583.69 | 228.88 | 0.00 | 0.00 | 0.00 |
| November | 435.01 | 343.64 | 91.38 | 605.48 | 378.60 | 0.00 | 0.00 | 0.00 |
| December | 425.96 | 329.94 | 96.02 | 546.64 | 452.61 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 278.65 | 172.74 | 105.91 | 449.78 | 226.29 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 114.72 | 9.21 | 91.38 | 273.10 | 29.45 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 435.01 | 343.64 | 121.52 | 605.48 | 452.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 32.99 | 18.58 | 14.41 | 33.96 | 77.25 | 0.00 | 0.00 | 0.00 |
| February | 37.23 | 19.79 | 17.44 | 41.44 | 69.87 | 0.00 | 0.00 | 0.00 |
| March | 50.73 | 27.19 | 23.54 | 62.99 | 59.85 | 0.00 | 0.00 | 0.00 |
| April | 58.31 | 31.49 | 26.82 | 87.95 | 35.33 | 0.00 | 0.00 | 0.00 |
| May | 62.81 | 33.60 | 29.20 | 108.68 | 19.77 | 0.00 | 0.00 | 0.00 |
| June | 61.14 | 32.84 | 28.30 | 122.57 | 8.95 | 0.00 | 0.00 | 0.00 |
| July | 54.25 | 26.96 | 27.29 | 110.21 | 6.57 | 0.00 | 0.00 | 0.00 |
| August | 52.54 | 26.78 | 25.76 | 101.44 | 10.37 | 0.00 | 0.00 | 0.00 |
| September | 53.73 | 29.93 | 23.80 | 95.64 | 22.96 | 0.00 | 0.00 | 0.00 |
| October | 46.25 | 27.00 | 19.26 | 68.62 | 41.11 | 0.00 | 0.00 | 0.00 |
| November | 38.82 | 23.64 | 15.18 | 45.49 | 69.84 | 0.00 | 0.00 | 0.00 |
| December | 31.29 | 17.00 | 14.29 | 30.37 | 84.39 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.38 | 26.25 | 22.13 | 75.93 | 42.05 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.29 | 17.00 | 14.29 | 30.37 | 6.57 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 62.81 | 33.60 | 29.20 | 122.57 | 84.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 98.97 | 55.74 | 43.23 | 108.38 | 201.65 | 0.00 | 0.00 | 0.00 |
| February | 111.68 | 59.36 | 52.32 | 132.09 | 181.09 | 0.00 | 0.00 | 0.00 |
| March | 152.19 | 81.57 | 70.62 | 197.80 | 156.89 | 0.00 | 0.00 | 0.00 |
| April | 174.93 | 94.48 | 80.45 | 269.70 | 96.20 | 0.00 | 0.00 | 0.00 |
| May | 188.42 | 100.81 | 87.60 | 328.31 | 56.38 | 0.00 | 0.00 | 0.00 |
| June | 183.41 | 98.51 | 84.90 | 366.09 | 25.96 | 0.00 | 0.00 | 0.00 |
| July | 162.76 | 80.88 | 81.88 | 327.40 | 20.90 | 0.00 | 0.00 | 0.00 |
| August | 157.63 | 80.33 | 77.29 | 302.54 | 31.99 | 0.00 | 0.00 | 0.00 |
| September | 161.20 | 89.80 | 71.39 | 288.00 | 67.43 | 0.00 | 0.00 | 0.00 |
| October | 138.76 | 80.99 | 57.78 | 209.46 | 115.65 | 0.00 | 0.00 | 0.00 |
| November | 116.47 | 70.92 | 45.55 | 141.80 | 186.94 | 0.00 | 0.00 | 0.00 |
| December | 93.86 | 50.99 | 42.87 | 96.42 | 225.31 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.14 | 78.75 | 66.39 | 231.08 | 113.53 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 93.86 | 50.99 | 42.87 | 96.42 | 20.90 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 188.42 | 100.81 | 87.60 | 366.09 | 225.31 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.26 | 0.00 | 4.26 | 0.28 | 32.99 | 0.00 | 0.00 | 0.00 |
| February | 5.23 | 0.00 | 5.23 | 1.65 | 28.96 | 0.00 | 0.00 | 0.00 |
| March | 6.98 | 0.00 | 6.98 | 3.74 | 24.76 | 0.00 | 0.00 | 0.00 |
| April | 8.02 | 0.07 | 7.95 | 8.98 | 14.20 | 0.00 | 0.00 | 0.00 |
| May | 9.73 | 0.84 | 8.88 | 16.93 | 7.30 | 0.00 | 0.00 | 0.00 |
| June | 10.57 | 1.55 | 9.02 | 25.98 | 3.27 | 0.00 | 0.00 | 0.00 |
| July | 9.57 | 1.10 | 8.46 | 23.46 | 2.71 | 0.00 | 0.00 | 0.00 |
| August | 7.82 | 0.19 | 7.63 | 17.40 | 4.28 | 0.00 | 0.00 | 0.00 |
| September | 6.77 | 0.00 | 6.77 | 12.19 | 9.67 | 0.00 | 0.00 | 0.00 |
| October | 5.64 | 0.00 | 5.64 | 5.01 | 17.81 | 0.00 | 0.00 | 0.00 |
| November | 4.54 | 0.00 | 4.54 | 0.61 | 30.47 | 0.00 | 0.00 | 0.00 |
| December | 4.20 | 0.00 | 4.20 | 0.22 | 37.26 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 6.95 | 0.31 | 6.64 | 9.75 | 17.75 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4.20 | 0.00 | 4.20 | 0.22 | 2.71 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 10.57 | 1.55 | 9.02 | 25.98 | 37.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 31.37 | 0.00 | 31.37 | 2.61 | 228.03 | 0.00 | 0.00 | 0.00 |
| February | 38.43 | 0.00 | 38.43 | 13.00 | 200.96 | 0.00 | 0.00 | 0.00 |
| March | 51.05 | 0.00 | 51.05 | 28.43 | 172.29 | 0.00 | 0.00 | 0.00 |
| April | 58.69 | 0.50 | 58.19 | 65.63 | 99.55 | 0.00 | 0.00 | 0.00 |
| May | 70.77 | 5.85 | 64.92 | 121.55 | 52.04 | 0.00 | 0.00 | 0.00 |
| June | 76.50 | 10.75 | 65.75 | 183.86 | 23.55 | 0.00 | 0.00 | 0.00 |
| July | 69.55 | 7.66 | 61.89 | 167.01 | 19.46 | 0.00 | 0.00 | 0.00 |
| August | 57.32 | 1.32 | 56.00 | 124.84 | 30.48 | 0.00 | 0.00 | 0.00 |
| September | 49.77 | 0.02 | 49.75 | 88.37 | 68.27 | 0.00 | 0.00 | 0.00 |
| October | 41.44 | 0.00 | 41.44 | 37.61 | 124.26 | 0.00 | 0.00 | 0.00 |
| November | 33.37 | 0.00 | 33.37 | 5.18 | 210.91 | 0.00 | 0.00 | 0.00 |
| December | 30.98 | 0.00 | 30.98 | 1.88 | 257.65 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 50.83 | 2.19 | 48.64 | 70.29 | 123.58 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.98 | 0.00 | 30.98 | 1.88 | 19.46 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 76.50 | 10.75 | 65.75 | 183.86 | 257.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.25 | 0.00 | 51.25 | 1.80 | 449.52 | 0.00 | 0.00 | 0.00 |
| February | 62.93 | 0.00 | 62.93 | 16.38 | 395.54 | 0.00 | 0.00 | 0.00 |
| March | 84.38 | 0.00 | 84.38 | 39.97 | 336.67 | 0.00 | 0.00 | 0.00 |
| April | 95.96 | 0.49 | 95.46 | 110.18 | 188.94 | 0.00 | 0.00 | 0.00 |
| May | 113.27 | 7.43 | 105.84 | 207.88 | 94.96 | 0.00 | 0.00 | 0.00 |
| June | 122.45 | 14.86 | 107.59 | 321.58 | 39.39 | 0.00 | 0.00 | 0.00 |
| July | 110.00 | 9.74 | 100.26 | 299.19 | 28.84 | 0.00 | 0.00 | 0.00 |
| August | 92.43 | 1.45 | 90.98 | 232.03 | 47.95 | 0.00 | 0.00 | 0.00 |
| September | 81.64 | 0.02 | 81.62 | 158.02 | 115.93 | 0.00 | 0.00 | 0.00 |
| October | 68.01 | 0.00 | 68.01 | 62.27 | 226.90 | 0.00 | 0.00 | 0.00 |
| November | 54.71 | 0.00 | 54.71 | 6.04 | 405.19 | 0.00 | 0.00 | 0.00 |
| December | 50.41 | 0.00 | 50.41 | 1.37 | 502.24 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.37 | 2.85 | 79.53 | 121.96 | 235.23 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 50.41 | 0.00 | 50.41 | 1.37 | 28.84 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 122.45 | 14.86 | 107.59 | 321.58 | 502.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 54.14 | 0.00 | 54.14 | 2.36 | 450.30 | 0.00 | 0.00 | 0.00 |
| February | 66.40 | 0.00 | 66.40 | 17.93 | 397.19 | 0.00 | 0.00 | 0.00 |
| March | 88.73 | 0.00 | 88.73 | 43.22 | 338.62 | 0.00 | 0.00 | 0.00 |
| April | 101.63 | 0.82 | 100.81 | 114.36 | 189.55 | 0.00 | 0.00 | 0.00 |
| May | 122.20 | 9.77 | 112.42 | 217.65 | 93.90 | 0.00 | 0.00 | 0.00 |
| June | 132.65 | 18.54 | 114.12 | 336.63 | 40.14 | 0.00 | 0.00 | 0.00 |
| July | 119.88 | 12.91 | 106.97 | 315.02 | 29.47 | 0.00 | 0.00 | 0.00 |
| August | 98.91 | 2.23 | 96.68 | 240.04 | 48.55 | 0.00 | 0.00 | 0.00 |
| September | 85.95 | 0.03 | 85.92 | 162.44 | 118.52 | 0.00 | 0.00 | 0.00 |
| October | 71.67 | 0.00 | 71.67 | 65.52 | 229.12 | 0.00 | 0.00 | 0.00 |
| November | 57.66 | 0.00 | 57.66 | 6.83 | 406.74 | 0.00 | 0.00 | 0.00 |
| December | 53.36 | 0.00 | 53.36 | 1.81 | 503.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 87.87 | 3.71 | 84.16 | 127.57 | 236.36 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 53.36 | 0.00 | 53.36 | 1.81 | 29.47 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 132.65 | 18.54 | 114.12 | 336.63 | 503.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 54.14 | 0.00 | 54.14 | 2.36 | 450.29 | 0.00 | 0.00 | 0.00 |
| February | 66.40 | 0.00 | 66.40 | 17.93 | 397.18 | 0.00 | 0.00 | 0.00 |
| March | 88.72 | 0.00 | 88.72 | 43.22 | 338.62 | 0.00 | 0.00 | 0.00 |
| April | 101.88 | 0.91 | 100.96 | 114.36 | 188.97 | 0.00 | 0.00 | 0.00 |
| May | 123.48 | 10.64 | 112.84 | 219.97 | 93.54 | 0.00 | 0.00 | 0.00 |
| June | 133.69 | 19.26 | 114.43 | 338.67 | 40.13 | 0.00 | 0.00 | 0.00 |
| July | 121.13 | 13.75 | 107.38 | 317.45 | 29.38 | 0.00 | 0.00 | 0.00 |
| August | 99.31 | 2.43 | 96.88 | 240.58 | 48.23 | 0.00 | 0.00 | 0.00 |
| September | 85.98 | 0.03 | 85.95 | 162.44 | 118.44 | 0.00 | 0.00 | 0.00 |
| October | 71.67 | 0.00 | 71.67 | 65.52 | 229.11 | 0.00 | 0.00 | 0.00 |
| November | 57.66 | 0.00 | 57.66 | 6.83 | 406.73 | 0.00 | 0.00 | 0.00 |
| December | 53.36 | 0.00 | 53.36 | 1.81 | 503.62 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 88.22 | 3.94 | 84.29 | 128.19 | 236.23 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 53.36 | 0.00 | 53.36 | 1.81 | 29.38 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 133.69 | 19.26 | 114.43 | 338.67 | 503.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 98.97 | 55.74 | 43.23 | 98.60 | 226.62 | 0.00 | 0.00 | 0.00 |
| February | 111.68 | 59.36 | 52.32 | 121.41 | 201.65 | 0.00 | 0.00 | 0.00 |
| March | 152.19 | 81.57 | 70.62 | 189.31 | 168.75 | 0.00 | 0.00 | 0.00 |
| April | 174.93 | 94.48 | 80.45 | 264.95 | 100.80 | 0.00 | 0.00 | 0.00 |
| May | 188.42 | 100.81 | 87.60 | 327.22 | 57.09 | 0.00 | 0.00 | 0.00 |
| June | 183.41 | 98.51 | 84.90 | 366.42 | 25.84 | 0.00 | 0.00 | 0.00 |
| July | 162.76 | 80.88 | 81.88 | 326.94 | 21.10 | 0.00 | 0.00 | 0.00 |
| August | 157.63 | 80.33 | 77.29 | 299.02 | 33.90 | 0.00 | 0.00 | 0.00 |
| September | 161.20 | 89.80 | 71.39 | 282.70 | 71.95 | 0.00 | 0.00 | 0.00 |
| October | 138.76 | 80.99 | 57.78 | 202.23 | 125.06 | 0.00 | 0.00 | 0.00 |
| November | 116.47 | 70.92 | 45.55 | 133.58 | 207.42 | 0.00 | 0.00 | 0.00 |
| December | 93.86 | 50.99 | 42.87 | 87.18 | 249.73 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.14 | 78.75 | 66.39 | 225.41 | 123.77 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 93.86 | 50.99 | 42.87 | 87.18 | 21.10 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 188.42 | 100.81 | 87.60 | 366.42 | 249.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 36.28 | 28.01 | 8.27 | 48.36 | 30.62 | 0.00 | 0.00 | 0.00 |
| February | 33.43 | 24.15 | 9.28 | 45.53 | 27.56 | 0.00 | 0.00 | 0.00 |
| March | 26.89 | 16.08 | 10.81 | 37.56 | 24.38 | 0.00 | 0.00 | 0.00 |
| April | 17.74 | 7.05 | 10.68 | 28.72 | 15.25 | 0.00 | 0.00 | 0.00 |
| May | 12.10 | 1.87 | 10.23 | 22.74 | 8.37 | 0.00 | 0.00 | 0.00 |
| June | 10.32 | 0.73 | 9.59 | 25.51 | 3.61 | 0.00 | 0.00 | 0.00 |
| July | 10.53 | 1.09 | 9.44 | 25.63 | 3.01 | 0.00 | 0.00 | 0.00 |
| August | 13.80 | 3.97 | 9.83 | 30.15 | 4.92 | 0.00 | 0.00 | 0.00 |
| September | 22.31 | 12.15 | 10.16 | 42.69 | 10.45 | 0.00 | 0.00 | 0.00 |
| October | 30.85 | 21.45 | 9.40 | 49.01 | 17.90 | 0.00 | 0.00 | 0.00 |
| November | 37.32 | 29.01 | 8.31 | 52.14 | 28.20 | 0.00 | 0.00 | 0.00 |
| December | 36.97 | 28.26 | 8.71 | 48.20 | 33.38 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 23.99 | 14.43 | 9.56 | 37.97 | 17.25 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 10.32 | 0.73 | 8.27 | 22.74 | 3.01 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 37.32 | 29.01 | 10.81 | 52.14 | 33.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 249.56 | 194.38 | 55.18 | 332.88 | 210.71 | 0.00 | 0.00 | 0.00 |
| February | 229.33 | 167.57 | 61.75 | 312.71 | 189.35 | 0.00 | 0.00 | 0.00 |
| March | 183.38 | 111.58 | 71.80 | 256.70 | 167.42 | 0.00 | 0.00 | 0.00 |
| April | 119.36 | 48.96 | 70.40 | 194.88 | 104.29 | 0.00 | 0.00 | 0.00 |
| May | 79.94 | 12.98 | 66.96 | 152.56 | 56.62 | 0.00 | 0.00 | 0.00 |
| June | 67.70 | 5.08 | 62.63 | 171.98 | 24.08 | 0.00 | 0.00 | 0.00 |
| July | 69.17 | 7.56 | 61.61 | 172.23 | 20.10 | 0.00 | 0.00 | 0.00 |
| August | 91.94 | 27.52 | 64.42 | 204.19 | 33.15 | 0.00 | 0.00 | 0.00 |
| September | 151.37 | 84.30 | 67.07 | 291.75 | 71.02 | 0.00 | 0.00 | 0.00 |
| October | 211.30 | 148.87 | 62.43 | 336.44 | 122.60 | 0.00 | 0.00 | 0.00 |
| November | 256.70 | 201.37 | 55.33 | 359.12 | 193.81 | 0.00 | 0.00 | 0.00 |
| December | 254.30 | 196.12 | 58.18 | 331.80 | 229.60 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 163.29 | 100.14 | 63.15 | 259.39 | 118.20 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67.70 | 5.08 | 55.18 | 152.56 | 20.10 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 256.70 | 201.37 | 71.80 | 359.12 | 229.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 454.83 | 355.71 | 99.12 | 600.79 | 415.85 | 0.00 | 0.00 | 0.00 |
| February | 419.09 | 307.96 | 111.12 | 564.26 | 373.14 | 0.00 | 0.00 | 0.00 |
| March | 334.12 | 205.04 | 129.08 | 462.23 | 328.08 | 0.00 | 0.00 | 0.00 |
| April | 216.01 | 89.97 | 126.03 | 354.37 | 199.17 | 0.00 | 0.00 | 0.00 |
| May | 143.32 | 23.85 | 119.46 | 280.67 | 104.16 | 0.00 | 0.00 | 0.00 |
| June | 120.96 | 9.33 | 111.63 | 320.49 | 42.23 | 0.00 | 0.00 | 0.00 |
| July | 123.64 | 13.89 | 109.75 | 329.50 | 31.61 | 0.00 | 0.00 | 0.00 |
| August | 165.57 | 50.57 | 115.00 | 385.06 | 55.38 | 0.00 | 0.00 | 0.00 |
| September | 275.10 | 154.91 | 120.19 | 539.22 | 126.73 | 0.00 | 0.00 | 0.00 |
| October | 385.72 | 273.52 | 112.19 | 617.77 | 229.03 | 0.00 | 0.00 | 0.00 |
| November | 469.10 | 369.59 | 99.51 | 653.84 | 373.21 | 0.00 | 0.00 | 0.00 |
| December | 461.97 | 357.50 | 104.47 | 596.32 | 449.51 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 296.75 | 183.62 | 113.13 | 474.74 | 226.60 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 120.96 | 9.33 | 99.12 | 280.67 | 31.61 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 469.10 | 369.59 | 129.08 | 653.84 | 449.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 452.97 | 354.19 | 98.77 | 600.17 | 418.82 | 0.00 | 0.00 | 0.00 |
| February | 418.29 | 307.35 | 110.93 | 564.02 | 374.64 | 0.00 | 0.00 | 0.00 |
| March | 334.00 | 204.97 | 129.03 | 462.20 | 328.29 | 0.00 | 0.00 | 0.00 |
| April | 215.99 | 89.97 | 126.02 | 354.34 | 199.16 | 0.00 | 0.00 | 0.00 |
| May | 143.31 | 23.85 | 119.46 | 280.65 | 104.16 | 0.00 | 0.00 | 0.00 |
| June | 120.95 | 9.33 | 111.62 | 320.46 | 42.23 | 0.00 | 0.00 | 0.00 |
| July | 123.63 | 13.89 | 109.74 | 329.48 | 31.61 | 0.00 | 0.00 | 0.00 |
| August | 165.56 | 50.57 | 115.00 | 385.04 | 55.37 | 0.00 | 0.00 | 0.00 |
| September | 275.06 | 154.88 | 120.18 | 539.18 | 126.79 | 0.00 | 0.00 | 0.00 |
| October | 385.30 | 273.21 | 112.10 | 617.39 | 229.48 | 0.00 | 0.00 | 0.00 |
| November | 467.11 | 367.96 | 99.15 | 653.04 | 376.48 | 0.00 | 0.00 | 0.00 |
| December | 459.83 | 355.66 | 104.17 | 595.76 | 453.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 296.13 | 183.11 | 113.02 | 474.51 | 227.60 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 120.95 | 9.33 | 98.77 | 280.65 | 31.61 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 467.11 | 367.96 | 129.03 | 653.04 | 453.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 423.73 | 331.25 | 92.48 | 555.92 | 421.34 | 0.00 | 0.00 | 0.00 |
| February | 392.11 | 288.10 | 104.01 | 525.42 | 379.21 | 0.00 | 0.00 | 0.00 |
| March | 318.76 | 196.18 | 122.57 | 439.46 | 329.40 | 0.00 | 0.00 | 0.00 |
| April | 208.03 | 87.69 | 120.34 | 342.76 | 196.46 | 0.00 | 0.00 | 0.00 |
| May | 137.57 | 23.46 | 114.12 | 274.09 | 101.31 | 0.00 | 0.00 | 0.00 |
| June | 116.00 | 9.21 | 106.79 | 316.20 | 40.51 | 0.00 | 0.00 | 0.00 |
| July | 118.34 | 13.69 | 104.65 | 323.27 | 30.33 | 0.00 | 0.00 | 0.00 |
| August | 159.05 | 49.40 | 109.65 | 375.82 | 53.74 | 0.00 | 0.00 | 0.00 |
| September | 264.01 | 149.49 | 114.52 | 520.56 | 124.90 | 0.00 | 0.00 | 0.00 |
| October | 364.92 | 259.39 | 105.53 | 584.57 | 230.21 | 0.00 | 0.00 | 0.00 |
| November | 436.26 | 344.02 | 92.24 | 606.46 | 380.32 | 0.00 | 0.00 | 0.00 |
| December | 428.07 | 331.10 | 96.97 | 547.74 | 455.21 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 279.92 | 172.93 | 107.00 | 450.46 | 227.81 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 116.00 | 9.21 | 92.24 | 274.09 | 30.33 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 436.26 | 344.02 | 122.57 | 606.46 | 455.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 32.99 | 18.58 | 14.41 | 33.75 | 78.21 | 0.00 | 0.00 | 0.00 |
| February | 37.23 | 19.79 | 17.44 | 41.18 | 70.74 | 0.00 | 0.00 | 0.00 |
| March | 50.73 | 27.19 | 23.54 | 62.75 | 60.47 | 0.00 | 0.00 | 0.00 |
| April | 58.31 | 31.49 | 26.82 | 87.78 | 35.63 | 0.00 | 0.00 | 0.00 |
| May | 62.81 | 33.60 | 29.20 | 108.52 | 19.95 | 0.00 | 0.00 | 0.00 |
| June | 61.14 | 32.84 | 28.30 | 122.39 | 9.07 | 0.00 | 0.00 | 0.00 |
| July | 54.25 | 26.96 | 27.29 | 109.82 | 6.81 | 0.00 | 0.00 | 0.00 |
| August | 52.54 | 26.78 | 25.76 | 101.06 | 10.68 | 0.00 | 0.00 | 0.00 |
| September | 53.73 | 29.93 | 23.80 | 95.47 | 23.21 | 0.00 | 0.00 | 0.00 |
| October | 46.25 | 27.00 | 19.26 | 68.50 | 41.40 | 0.00 | 0.00 | 0.00 |
| November | 38.82 | 23.64 | 15.18 | 45.36 | 70.46 | 0.00 | 0.00 | 0.00 |
| December | 31.29 | 17.00 | 14.29 | 30.14 | 85.47 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.38 | 26.25 | 22.13 | 75.71 | 42.53 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 31.29 | 17.00 | 14.29 | 30.14 | 6.81 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 62.81 | 33.60 | 29.20 | 122.39 | 85.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.41 | 0.00 | 5.41 | 0.76 | 33.12 | 0.00 | 0.00 | 0.00 |
| February | 6.60 | 0.00 | 6.60 | 2.55 | 29.37 | 0.00 | 0.00 | 0.00 |
| March | 8.64 | 0.00 | 8.64 | 5.24 | 25.30 | 0.00 | 0.00 | 0.00 |
| April | 9.98 | 0.08 | 9.90 | 11.07 | 14.90 | 0.00 | 0.00 | 0.00 |
| May | 11.83 | 0.86 | 10.98 | 19.50 | 8.18 | 0.00 | 0.00 | 0.00 |
| June | 12.58 | 1.55 | 11.03 | 28.22 | 3.83 | 0.00 | 0.00 | 0.00 |
| July | 11.63 | 1.13 | 10.50 | 26.07 | 3.15 | 0.00 | 0.00 | 0.00 |
| August | 9.81 | 0.20 | 9.61 | 19.89 | 4.81 | 0.00 | 0.00 | 0.00 |
| September | 8.56 | 0.00 | 8.55 | 14.43 | 10.45 | 0.00 | 0.00 | 0.00 |
| October | 7.10 | 0.00 | 7.10 | 6.59 | 18.41 | 0.00 | 0.00 | 0.00 |
| November | 5.74 | 0.00 | 5.74 | 1.18 | 30.71 | 0.00 | 0.00 | 0.00 |
| December | 5.37 | 0.00 | 5.37 | 0.48 | 37.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 8.61 | 0.32 | 8.29 | 11.38 | 18.25 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5.37 | 0.00 | 5.37 | 0.48 | 3.15 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 12.58 | 1.55 | 11.03 | 28.22 | 37.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 98.97 | 55.74 | 43.23 | 108.08 | 202.22 | 0.00 | 0.00 | 0.00 |
| February | 111.68 | 59.36 | 52.32 | 131.72 | 181.61 | 0.00 | 0.00 | 0.00 |
| March | 152.19 | 81.57 | 70.62 | 197.38 | 157.30 | 0.00 | 0.00 | 0.00 |
| April | 174.93 | 94.48 | 80.45 | 269.36 | 96.34 | 0.00 | 0.00 | 0.00 |
| May | 188.42 | 100.81 | 87.60 | 327.99 | 56.44 | 0.00 | 0.00 | 0.00 |
| June | 183.41 | 98.51 | 84.90 | 365.80 | 26.01 | 0.00 | 0.00 | 0.00 |
| July | 162.76 | 80.88 | 81.88 | 326.64 | 21.18 | 0.00 | 0.00 | 0.00 |
| August | 157.63 | 80.33 | 77.29 | 301.81 | 32.32 | 0.00 | 0.00 | 0.00 |
| September | 161.20 | 89.80 | 71.39 | 287.67 | 67.59 | 0.00 | 0.00 | 0.00 |
| October | 138.76 | 80.99 | 57.78 | 209.25 | 115.76 | 0.00 | 0.00 | 0.00 |
| November | 116.47 | 70.92 | 45.55 | 141.61 | 187.15 | 0.00 | 0.00 | 0.00 |
| December | 93.86 | 50.99 | 42.87 | 96.12 | 225.97 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 145.14 | 78.75 | 66.39 | 230.70 | 113.82 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 93.86 | 50.99 | 42.87 | 96.12 | 21.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 188.42 | 100.81 | 87.60 | 365.80 | 225.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 37.38 | 0.00 | 37.38 | 5.39 | 228.24 | 0.00 | 0.00 | 0.00 |
| February | 45.64 | 0.00 | 45.64 | 17.87 | 202.65 | 0.00 | 0.00 | 0.00 |
| March | 59.73 | 0.00 | 59.73 | 36.40 | 174.76 | 0.00 | 0.00 | 0.00 |
| April | 68.97 | 0.54 | 68.42 | 76.63 | 102.99 | 0.00 | 0.00 | 0.00 |
| May | 81.80 | 5.92 | 75.88 | 134.78 | 56.54 | 0.00 | 0.00 | 0.00 |
| June | 86.98 | 10.71 | 76.27 | 195.09 | 26.51 | 0.00 | 0.00 | 0.00 |
| July | 80.39 | 7.82 | 72.56 | 180.25 | 21.79 | 0.00 | 0.00 | 0.00 |
| August | 67.78 | 1.39 | 66.40 | 137.52 | 33.27 | 0.00 | 0.00 | 0.00 |
| September | 59.15 | 0.02 | 59.12 | 99.97 | 72.25 | 0.00 | 0.00 | 0.00 |
| October | 49.11 | 0.00 | 49.11 | 45.95 | 127.06 | 0.00 | 0.00 | 0.00 |
| November | 39.64 | 0.00 | 39.64 | 8.37 | 211.65 | 0.00 | 0.00 | 0.00 |
| December | 37.09 | 0.00 | 37.09 | 3.36 | 257.68 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 59.54 | 2.21 | 57.33 | 78.78 | 125.91 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 37.09 | 0.00 | 37.09 | 3.36 | 21.79 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 86.98 | 10.71 | 76.27 | 195.09 | 257.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 45.54 | 0.00 | 45.54 | 4.77 | 297.87 | 0.00 | 0.00 | 0.00 |
| February | 55.61 | 0.00 | 55.61 | 18.79 | 265.20 | 0.00 | 0.00 | 0.00 |
| March | 72.77 | 0.00 | 72.77 | 40.77 | 227.58 | 0.00 | 0.00 | 0.00 |
| April | 84.02 | 0.66 | 83.36 | 93.05 | 130.44 | 0.00 | 0.00 | 0.00 |
| May | 99.65 | 7.21 | 92.45 | 166.80 | 69.10 | 0.00 | 0.00 | 0.00 |
| June | 105.97 | 13.05 | 92.92 | 243.06 | 31.22 | 0.00 | 0.00 | 0.00 |
| July | 97.93 | 9.53 | 88.40 | 230.85 | 23.25 | 0.00 | 0.00 | 0.00 |
| August | 82.58 | 1.69 | 80.89 | 178.63 | 36.48 | 0.00 | 0.00 | 0.00 |
| September | 72.06 | 0.03 | 72.03 | 125.94 | 84.93 | 0.00 | 0.00 | 0.00 |
| October | 59.83 | 0.00 | 59.83 | 56.58 | 156.43 | 0.00 | 0.00 | 0.00 |
| November | 48.30 | 0.00 | 48.30 | 8.96 | 270.33 | 0.00 | 0.00 | 0.00 |
| December | 45.19 | 0.00 | 45.19 | 3.04 | 333.98 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 72.54 | 2.69 | 69.84 | 98.03 | 160.05 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 45.19 | 0.00 | 45.19 | 3.04 | 23.25 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 105.97 | 13.05 | 92.92 | 243.06 | 333.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 45.54 | 0.00 | 45.54 | 4.77 | 297.87 | 0.00 | 0.00 | 0.00 |
| February | 55.61 | 0.00 | 55.61 | 18.79 | 265.20 | 0.00 | 0.00 | 0.00 |
| March | 72.77 | 0.00 | 72.77 | 40.77 | 227.58 | 0.00 | 0.00 | 0.00 |
| April | 84.02 | 0.66 | 83.36 | 93.05 | 130.44 | 0.00 | 0.00 | 0.00 |
| May | 99.65 | 7.21 | 92.45 | 166.80 | 69.10 | 0.00 | 0.00 | 0.00 |
| June | 105.97 | 13.05 | 92.92 | 243.06 | 31.22 | 0.00 | 0.00 | 0.00 |
| July | 97.93 | 9.53 | 88.40 | 230.85 | 23.25 | 0.00 | 0.00 | 0.00 |
| August | 82.58 | 1.69 | 80.89 | 178.63 | 36.48 | 0.00 | 0.00 | 0.00 |
| September | 72.06 | 0.03 | 72.03 | 125.94 | 84.93 | 0.00 | 0.00 | 0.00 |
| October | 59.83 | 0.00 | 59.83 | 56.58 | 156.43 | 0.00 | 0.00 | 0.00 |
| November | 48.30 | 0.00 | 48.30 | 8.96 | 270.33 | 0.00 | 0.00 | 0.00 |
| December | 45.19 | 0.00 | 45.19 | 3.04 | 333.98 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 72.54 | 2.69 | 69.84 | 98.03 | 160.05 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 45.19 | 0.00 | 45.19 | 3.04 | 23.25 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 105.97 | 13.05 | 92.92 | 243.06 | 333.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 45.54 | 0.00 | 45.54 | 4.77 | 297.86 | 0.00 | 0.00 | 0.00 |
| February | 55.61 | 0.00 | 55.61 | 18.79 | 265.19 | 0.00 | 0.00 | 0.00 |
| March | 72.77 | 0.00 | 72.77 | 40.77 | 227.57 | 0.00 | 0.00 | 0.00 |
| April | 84.02 | 0.66 | 83.36 | 93.04 | 130.44 | 0.00 | 0.00 | 0.00 |
| May | 99.65 | 7.21 | 92.45 | 166.79 | 69.10 | 0.00 | 0.00 | 0.00 |
| June | 105.96 | 13.05 | 92.92 | 243.05 | 31.22 | 0.00 | 0.00 | 0.00 |
| July | 97.93 | 9.53 | 88.40 | 230.84 | 23.25 | 0.00 | 0.00 | 0.00 |
| August | 82.58 | 1.69 | 80.89 | 178.63 | 36.48 | 0.00 | 0.00 | 0.00 |
| September | 72.06 | 0.03 | 72.03 | 125.93 | 84.93 | 0.00 | 0.00 | 0.00 |
| October | 59.83 | 0.00 | 59.83 | 56.58 | 156.42 | 0.00 | 0.00 | 0.00 |
| November | 48.30 | 0.00 | 48.30 | 8.96 | 270.32 | 0.00 | 0.00 | 0.00 |
| December | 45.18 | 0.00 | 45.18 | 3.04 | 333.97 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 72.53 | 2.69 | 69.84 | 98.03 | 160.05 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 45.18 | 0.00 | 45.18 | 3.04 | 23.25 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 105.96 | 13.05 | 92.92 | 243.05 | 333.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.14 | 0.00 | 5.14 | 0.37 | 36.09 | 0.00 | 0.00 | 0.00 |
| February | 6.27 | 0.00 | 6.27 | 1.81 | 32.22 | 0.00 | 0.00 | 0.00 |
| March | 8.21 | 0.00 | 8.21 | 4.21 | 27.54 | 0.00 | 0.00 | 0.00 |
| April | 9.47 | 0.07 | 9.40 | 10.16 | 15.67 | 0.00 | 0.00 | 0.00 |
| May | 11.24 | 0.81 | 10.42 | 18.53 | 8.26 | 0.00 | 0.00 | 0.00 |
| June | 11.95 | 1.47 | 10.48 | 27.14 | 3.83 | 0.00 | 0.00 | 0.00 |
| July | 11.04 | 1.07 | 9.97 | 25.15 | 3.06 | 0.00 | 0.00 | 0.00 |
| August | 9.31 | 0.19 | 9.12 | 19.18 | 4.75 | 0.00 | 0.00 | 0.00 |
| September | 8.13 | 0.00 | 8.12 | 13.93 | 10.19 | 0.00 | 0.00 | 0.00 |
| October | 6.75 | 0.00 | 6.75 | 6.17 | 18.56 | 0.00 | 0.00 | 0.00 |
| November | 5.45 | 0.00 | 5.45 | 0.86 | 32.46 | 0.00 | 0.00 | 0.00 |
| December | 5.10 | 0.00 | 5.10 | 0.24 | 40.20 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 8.18 | 0.30 | 7.88 | 10.69 | 19.34 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5.10 | 0.00 | 5.10 | 0.24 | 3.06 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 11.95 | 1.47 | 10.48 | 27.14 | 40.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 65.12 | 0.00 | 65.12 | 4.74 | 457.65 | 0.00 | 0.00 | 0.00 |
| February | 79.52 | 0.00 | 79.52 | 22.99 | 408.64 | 0.00 | 0.00 | 0.00 |
| March | 104.07 | 0.00 | 104.07 | 53.45 | 349.23 | 0.00 | 0.00 | 0.00 |
| April | 120.16 | 0.95 | 119.21 | 128.89 | 198.69 | 0.00 | 0.00 | 0.00 |
| May | 142.51 | 10.31 | 132.21 | 235.05 | 104.78 | 0.00 | 0.00 | 0.00 |
| June | 151.54 | 18.66 | 132.88 | 344.13 | 48.52 | 0.00 | 0.00 | 0.00 |
| July | 140.05 | 13.63 | 126.42 | 318.98 | 38.78 | 0.00 | 0.00 | 0.00 |
| August | 118.09 | 2.41 | 115.68 | 243.19 | 60.22 | 0.00 | 0.00 | 0.00 |
| September | 103.05 | 0.04 | 103.01 | 176.70 | 129.27 | 0.00 | 0.00 | 0.00 |
| October | 85.56 | 0.00 | 85.56 | 78.24 | 235.34 | 0.00 | 0.00 | 0.00 |
| November | 69.07 | 0.00 | 69.07 | 10.84 | 411.61 | 0.00 | 0.00 | 0.00 |
| December | 64.62 | 0.00 | 64.62 | 3.02 | 509.78 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 103.73 | 3.85 | 99.88 | 135.61 | 245.24 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 64.62 | 0.00 | 64.62 | 3.02 | 38.78 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 151.54 | 18.66 | 132.88 | 344.13 | 509.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.02 | 7.94 | 5.08 | 14.42 | 35.06 | 0.00 | 0.00 | 0.00 |
| February | 15.38 | 9.09 | 6.29 | 18.30 | 31.80 | 0.00 | 0.00 | 0.00 |
| March | 21.66 | 12.93 | 8.73 | 27.93 | 27.93 | 0.00 | 0.00 | 0.00 |
| April | 23.01 | 13.30 | 9.71 | 35.78 | 16.34 | 0.00 | 0.00 | 0.00 |
| May | 21.08 | 11.03 | 10.05 | 38.03 | 8.83 | 0.00 | 0.00 | 0.00 |
| June | 19.72 | 9.99 | 9.73 | 43.29 | 3.98 | 0.00 | 0.00 | 0.00 |
| July | 17.77 | 8.50 | 9.28 | 38.75 | 3.19 | 0.00 | 0.00 | 0.00 |
| August | 20.09 | 10.93 | 9.17 | 40.51 | 4.77 | 0.00 | 0.00 | 0.00 |
| September | 22.63 | 13.82 | 8.81 | 41.67 | 10.01 | 0.00 | 0.00 | 0.00 |
| October | 19.69 | 12.62 | 7.07 | 30.39 | 18.28 | 0.00 | 0.00 | 0.00 |
| November | 15.86 | 10.42 | 5.44 | 19.86 | 31.82 | 0.00 | 0.00 | 0.00 |
| December | 11.86 | 6.88 | 4.98 | 12.42 | 37.77 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 18.49 | 10.62 | 7.87 | 30.16 | 19.08 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11.86 | 6.88 | 4.98 | 12.42 | 3.19 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 23.01 | 13.82 | 10.05 | 43.29 | 37.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 41.76 | 16.82 | 24.94 | 27.71 | 190.86 | 0.00 | 0.00 | 0.00 |
| February | 59.23 | 27.37 | 31.86 | 55.95 | 172.79 | 0.00 | 0.00 | 0.00 |
| March | 98.56 | 52.68 | 45.88 | 116.60 | 150.86 | 0.00 | 0.00 | 0.00 |
| April | 127.48 | 73.09 | 54.39 | 194.29 | 88.90 | 0.00 | 0.00 | 0.00 |
| May | 139.18 | 79.70 | 59.49 | 244.99 | 49.50 | 0.00 | 0.00 | 0.00 |
| June | 136.72 | 78.66 | 58.06 | 281.37 | 22.92 | 0.00 | 0.00 | 0.00 |
| July | 118.35 | 63.33 | 55.02 | 244.17 | 18.05 | 0.00 | 0.00 | 0.00 |
| August | 115.83 | 63.82 | 52.01 | 227.17 | 26.82 | 0.00 | 0.00 | 0.00 |
| September | 111.78 | 64.47 | 47.31 | 202.86 | 55.69 | 0.00 | 0.00 | 0.00 |
| October | 79.32 | 43.44 | 35.88 | 113.87 | 99.60 | 0.00 | 0.00 | 0.00 |
| November | 52.88 | 26.03 | 26.85 | 48.60 | 173.43 | 0.00 | 0.00 | 0.00 |
| December | 37.31 | 13.04 | 24.28 | 20.04 | 206.35 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 93.32 | 50.28 | 43.05 | 148.52 | 104.30 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 37.31 | 13.04 | 24.28 | 20.04 | 18.05 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 139.18 | 79.70 | 59.49 | 281.37 | 206.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 34.98 | 26.50 | 8.48 | 48.22 | 28.24 | 0.00 | 0.00 | 0.00 |
| February | 32.45 | 22.88 | 9.57 | 45.56 | 25.61 | 0.00 | 0.00 | 0.00 |
| March | 26.37 | 15.21 | 11.17 | 37.83 | 22.93 | 0.00 | 0.00 | 0.00 |
| April | 17.88 | 6.67 | 11.21 | 28.68 | 14.88 | 0.00 | 0.00 | 0.00 |
| May | 12.64 | 1.77 | 10.87 | 22.55 | 8.86 | 0.00 | 0.00 | 0.00 |
| June | 10.90 | 0.69 | 10.21 | 24.29 | 4.41 | 0.00 | 0.00 | 0.00 |
| July | 11.11 | 1.03 | 10.08 | 24.77 | 3.64 | 0.00 | 0.00 | 0.00 |
| August | 14.17 | 3.75 | 10.42 | 29.47 | 5.37 | 0.00 | 0.00 | 0.00 |
| September | 22.11 | 11.49 | 10.62 | 41.45 | 10.68 | 0.00 | 0.00 | 0.00 |
| October | 30.04 | 20.31 | 9.73 | 47.84 | 17.02 | 0.00 | 0.00 | 0.00 |
| November | 36.16 | 27.56 | 8.59 | 51.34 | 26.25 | 0.00 | 0.00 | 0.00 |
| December | 35.83 | 26.90 | 8.93 | 48.39 | 30.35 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 23.67 | 13.68 | 9.99 | 37.48 | 16.47 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 10.90 | 0.69 | 8.48 | 22.55 | 3.64 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 36.16 | 27.56 | 11.21 | 51.34 | 30.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 472.36 | 357.86 | 114.50 | 651.04 | 381.31 | 0.00 | 0.00 | 0.00 |
| February | 438.17 | 308.90 | 129.27 | 615.09 | 345.72 | 0.00 | 0.00 | 0.00 |
| March | 356.10 | 205.33 | 150.77 | 510.71 | 309.61 | 0.00 | 0.00 | 0.00 |
| April | 241.44 | 90.09 | 151.35 | 387.22 | 200.92 | 0.00 | 0.00 | 0.00 |
| May | 170.62 | 23.88 | 146.74 | 304.42 | 119.61 | 0.00 | 0.00 | 0.00 |
| June | 147.20 | 9.34 | 137.86 | 327.90 | 59.51 | 0.00 | 0.00 | 0.00 |
| July | 150.06 | 13.91 | 136.15 | 334.51 | 49.16 | 0.00 | 0.00 | 0.00 |
| August | 191.28 | 50.63 | 140.65 | 397.85 | 72.46 | 0.00 | 0.00 | 0.00 |
| September | 298.57 | 155.12 | 143.45 | 559.65 | 144.16 | 0.00 | 0.00 | 0.00 |
| October | 405.66 | 274.26 | 131.41 | 646.00 | 229.83 | 0.00 | 0.00 | 0.00 |
| November | 488.18 | 372.18 | 116.00 | 693.16 | 354.41 | 0.00 | 0.00 | 0.00 |
| December | 483.80 | 363.17 | 120.64 | 653.40 | 409.81 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 319.61 | 184.69 | 134.92 | 506.02 | 222.40 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 147.20 | 9.34 | 114.50 | 304.42 | 49.16 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 488.18 | 372.18 | 151.35 | 693.16 | 409.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BATH_ZN_1_FLR_1_WALL_5_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 69.53 | 34.47 | 35.06 | 60.07 | 246.17 | 0.00 | 0.00 | 0.00 |
| February | 90.46 | 46.27 | 44.19 | 94.32 | 224.16 | 0.00 | 0.00 | 0.00 |
| March | 139.93 | 77.31 | 62.61 | 169.09 | 199.00 | 0.00 | 0.00 | 0.00 |
| April | 170.24 | 97.50 | 72.73 | 250.92 | 126.05 | 0.00 | 0.00 | 0.00 |
| May | 180.18 | 101.49 | 78.70 | 301.24 | 76.77 | 0.00 | 0.00 | 0.00 |
| June | 175.70 | 99.07 | 76.63 | 340.88 | 39.09 | 0.00 | 0.00 | 0.00 |
| July | 153.12 | 80.29 | 72.83 | 300.50 | 31.44 | 0.00 | 0.00 | 0.00 |
| August | 153.38 | 83.98 | 69.40 | 286.13 | 44.15 | 0.00 | 0.00 | 0.00 |
| September | 153.90 | 89.97 | 63.93 | 265.15 | 87.24 | 0.00 | 0.00 | 0.00 |
| October | 118.39 | 68.79 | 49.60 | 166.45 | 141.80 | 0.00 | 0.00 | 0.00 |
| November | 86.12 | 48.55 | 37.58 | 89.77 | 228.22 | 0.00 | 0.00 | 0.00 |
| December | 62.86 | 28.59 | 34.27 | 47.49 | 267.79 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 129.62 | 71.43 | 58.19 | 198.09 | 142.23 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 62.86 | 28.59 | 34.27 | 47.49 | 31.44 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 180.18 | 101.49 | 78.70 | 340.88 | 267.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 219.23 | 118.93 | 100.31 | 192.56 | 532.43 | 0.00 | 0.00 | 0.00 |
| February | 293.31 | 167.19 | 126.13 | 309.19 | 473.04 | 0.00 | 0.00 | 0.00 |
| March | 362.14 | 199.53 | 162.61 | 422.92 | 399.62 | 0.00 | 0.00 | 0.00 |
| April | 436.37 | 242.09 | 194.28 | 628.02 | 239.27 | 0.00 | 0.00 | 0.00 |
| May | 450.31 | 244.72 | 205.58 | 749.28 | 142.59 | 0.00 | 0.00 | 0.00 |
| June | 450.56 | 250.66 | 199.90 | 863.41 | 72.61 | 0.00 | 0.00 | 0.00 |
| July | 404.05 | 211.23 | 192.82 | 774.94 | 61.59 | 0.00 | 0.00 | 0.00 |
| August | 384.48 | 196.77 | 187.71 | 703.09 | 87.89 | 0.00 | 0.00 | 0.00 |
| September | 380.91 | 217.34 | 163.58 | 639.17 | 168.18 | 0.00 | 0.00 | 0.00 |
| October | 292.95 | 158.10 | 134.85 | 394.46 | 288.55 | 0.00 | 0.00 | 0.00 |
| November | 262.60 | 152.88 | 109.72 | 264.37 | 477.73 | 0.00 | 0.00 | 0.00 |
| December | 219.04 | 116.05 | 102.99 | 180.99 | 582.98 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 346.37 | 189.52 | 156.85 | 510.88 | 293.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 219.04 | 116.05 | 100.31 | 180.99 | 61.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 450.56 | 250.66 | 205.58 | 863.41 | 582.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 34.74 | 26.32 | 8.42 | 46.09 | 30.42 | 0.00 | 0.00 | 0.00 |
| February | 32.22 | 22.72 | 9.51 | 43.21 | 27.91 | 0.00 | 0.00 | 0.00 |
| March | 26.19 | 15.10 | 11.09 | 35.70 | 25.19 | 0.00 | 0.00 | 0.00 |
| April | 17.75 | 6.62 | 11.13 | 27.34 | 16.36 | 0.00 | 0.00 | 0.00 |
| May | 12.55 | 1.76 | 10.79 | 21.59 | 9.68 | 0.00 | 0.00 | 0.00 |
| June | 10.83 | 0.69 | 10.14 | 23.77 | 4.78 | 0.00 | 0.00 | 0.00 |
| July | 11.03 | 1.02 | 10.01 | 24.02 | 4.03 | 0.00 | 0.00 | 0.00 |
| August | 14.07 | 3.72 | 10.34 | 28.81 | 5.80 | 0.00 | 0.00 | 0.00 |
| September | 21.96 | 11.41 | 10.55 | 40.90 | 11.14 | 0.00 | 0.00 | 0.00 |
| October | 29.83 | 20.17 | 9.66 | 46.97 | 17.67 | 0.00 | 0.00 | 0.00 |
| November | 35.90 | 27.37 | 8.53 | 49.62 | 27.56 | 0.00 | 0.00 | 0.00 |
| December | 35.58 | 26.71 | 8.87 | 46.09 | 32.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 23.50 | 13.58 | 9.92 | 36.13 | 17.71 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 10.83 | 0.69 | 8.42 | 21.59 | 4.03 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 35.90 | 27.37 | 11.13 | 49.62 | 32.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 526.00 | 398.50 | 127.50 | 697.89 | 460.67 | 0.00 | 0.00 | 0.00 |
| February | 487.92 | 343.98 | 143.95 | 654.31 | 422.65 | 0.00 | 0.00 | 0.00 |
| March | 396.54 | 228.64 | 167.90 | 540.53 | 381.44 | 0.00 | 0.00 | 0.00 |
| April | 268.85 | 100.32 | 168.54 | 413.94 | 247.71 | 0.00 | 0.00 | 0.00 |
| May | 189.99 | 26.59 | 163.40 | 326.96 | 146.43 | 0.00 | 0.00 | 0.00 |
| June | 163.92 | 10.40 | 153.52 | 360.03 | 72.30 | 0.00 | 0.00 | 0.00 |
| July | 167.10 | 15.49 | 151.61 | 363.82 | 60.91 | 0.00 | 0.00 | 0.00 |
| August | 213.00 | 56.38 | 156.62 | 436.21 | 87.76 | 0.00 | 0.00 | 0.00 |
| September | 332.47 | 172.73 | 159.74 | 619.33 | 168.63 | 0.00 | 0.00 | 0.00 |
| October | 451.73 | 305.40 | 146.33 | 711.19 | 267.61 | 0.00 | 0.00 | 0.00 |
| November | 543.62 | 414.44 | 129.18 | 751.38 | 417.30 | 0.00 | 0.00 | 0.00 |
| December | 538.74 | 404.41 | 134.34 | 697.86 | 494.02 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 355.90 | 205.66 | 150.24 | 547.04 | 268.16 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 163.92 | 10.40 | 127.50 | 326.96 | 60.91 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 543.62 | 414.44 | 168.54 | 751.38 | 494.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 44.66 | 30.97 | 13.70 | 49.26 | 63.11 | 0.00 | 0.00 | 0.00 |
| February | 59.73 | 42.54 | 17.19 | 70.75 | 59.83 | 0.00 | 0.00 | 0.00 |
| March | 81.53 | 57.42 | 24.12 | 103.78 | 53.45 | 0.00 | 0.00 | 0.00 |
| April | 103.42 | 77.04 | 26.38 | 143.92 | 37.45 | 0.00 | 0.00 | 0.00 |
| May | 113.70 | 84.77 | 28.93 | 167.58 | 26.79 | 0.00 | 0.00 | 0.00 |
| June | 120.33 | 93.62 | 26.71 | 186.63 | 16.35 | 0.00 | 0.00 | 0.00 |
| July | 104.12 | 75.39 | 28.73 | 163.60 | 12.85 | 0.00 | 0.00 | 0.00 |
| August | 96.79 | 69.96 | 26.83 | 149.52 | 16.61 | 0.00 | 0.00 | 0.00 |
| September | 88.96 | 66.74 | 22.22 | 134.41 | 26.42 | 0.00 | 0.00 | 0.00 |
| October | 66.50 | 48.31 | 18.18 | 91.94 | 38.39 | 0.00 | 0.00 | 0.00 |
| November | 52.12 | 38.72 | 13.40 | 61.63 | 58.50 | 0.00 | 0.00 | 0.00 |
| December | 41.70 | 27.50 | 14.21 | 43.15 | 69.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.20 | 59.45 | 21.75 | 114.01 | 39.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41.70 | 27.50 | 13.40 | 43.15 | 12.85 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.33 | 93.62 | 28.93 | 186.63 | 69.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 44.66 | 30.97 | 13.70 | 49.26 | 63.11 | 0.00 | 0.00 | 0.00 |
| February | 59.73 | 42.54 | 17.19 | 70.75 | 59.83 | 0.00 | 0.00 | 0.00 |
| March | 81.53 | 57.42 | 24.12 | 103.78 | 53.45 | 0.00 | 0.00 | 0.00 |
| April | 103.42 | 77.04 | 26.38 | 143.92 | 37.45 | 0.00 | 0.00 | 0.00 |
| May | 113.70 | 84.77 | 28.93 | 167.58 | 26.79 | 0.00 | 0.00 | 0.00 |
| June | 120.33 | 93.62 | 26.71 | 186.63 | 16.35 | 0.00 | 0.00 | 0.00 |
| July | 104.12 | 75.39 | 28.73 | 163.60 | 12.85 | 0.00 | 0.00 | 0.00 |
| August | 96.79 | 69.96 | 26.83 | 149.52 | 16.61 | 0.00 | 0.00 | 0.00 |
| September | 88.96 | 66.74 | 22.22 | 134.41 | 26.42 | 0.00 | 0.00 | 0.00 |
| October | 66.50 | 48.31 | 18.18 | 91.94 | 38.39 | 0.00 | 0.00 | 0.00 |
| November | 52.12 | 38.72 | 13.40 | 61.63 | 58.50 | 0.00 | 0.00 | 0.00 |
| December | 41.70 | 27.50 | 14.21 | 43.15 | 69.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.20 | 59.45 | 21.75 | 114.01 | 39.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41.70 | 27.50 | 13.40 | 43.15 | 12.85 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.33 | 93.62 | 28.93 | 186.63 | 69.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 44.66 | 30.97 | 13.70 | 49.26 | 63.11 | 0.00 | 0.00 | 0.00 |
| February | 59.73 | 42.54 | 17.19 | 70.75 | 59.83 | 0.00 | 0.00 | 0.00 |
| March | 81.53 | 57.42 | 24.12 | 103.78 | 53.45 | 0.00 | 0.00 | 0.00 |
| April | 103.42 | 77.04 | 26.38 | 143.92 | 37.45 | 0.00 | 0.00 | 0.00 |
| May | 113.70 | 84.77 | 28.93 | 167.58 | 26.79 | 0.00 | 0.00 | 0.00 |
| June | 120.33 | 93.62 | 26.71 | 186.63 | 16.35 | 0.00 | 0.00 | 0.00 |
| July | 104.12 | 75.39 | 28.73 | 163.60 | 12.85 | 0.00 | 0.00 | 0.00 |
| August | 96.79 | 69.96 | 26.83 | 149.52 | 16.61 | 0.00 | 0.00 | 0.00 |
| September | 88.96 | 66.74 | 22.22 | 134.41 | 26.42 | 0.00 | 0.00 | 0.00 |
| October | 66.50 | 48.31 | 18.18 | 91.94 | 38.39 | 0.00 | 0.00 | 0.00 |
| November | 52.12 | 38.72 | 13.40 | 61.63 | 58.50 | 0.00 | 0.00 | 0.00 |
| December | 41.70 | 27.50 | 14.21 | 43.15 | 69.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.20 | 59.45 | 21.75 | 114.01 | 39.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41.70 | 27.50 | 13.40 | 43.15 | 12.85 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.33 | 93.62 | 28.93 | 186.63 | 69.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 44.66 | 30.97 | 13.70 | 49.26 | 63.11 | 0.00 | 0.00 | 0.00 |
| February | 59.73 | 42.54 | 17.19 | 70.75 | 59.83 | 0.00 | 0.00 | 0.00 |
| March | 81.53 | 57.42 | 24.12 | 103.78 | 53.45 | 0.00 | 0.00 | 0.00 |
| April | 103.42 | 77.04 | 26.38 | 143.92 | 37.45 | 0.00 | 0.00 | 0.00 |
| May | 113.70 | 84.77 | 28.93 | 167.58 | 26.79 | 0.00 | 0.00 | 0.00 |
| June | 120.33 | 93.62 | 26.71 | 186.63 | 16.35 | 0.00 | 0.00 | 0.00 |
| July | 104.12 | 75.39 | 28.73 | 163.60 | 12.85 | 0.00 | 0.00 | 0.00 |
| August | 96.79 | 69.96 | 26.83 | 149.52 | 16.61 | 0.00 | 0.00 | 0.00 |
| September | 88.96 | 66.74 | 22.22 | 134.41 | 26.42 | 0.00 | 0.00 | 0.00 |
| October | 66.50 | 48.31 | 18.18 | 91.94 | 38.39 | 0.00 | 0.00 | 0.00 |
| November | 52.12 | 38.72 | 13.40 | 61.63 | 58.50 | 0.00 | 0.00 | 0.00 |
| December | 41.70 | 27.50 | 14.21 | 43.15 | 69.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.20 | 59.45 | 21.75 | 114.01 | 39.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41.70 | 27.50 | 13.40 | 43.15 | 12.85 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.33 | 93.62 | 28.93 | 186.63 | 69.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 44.66 | 30.97 | 13.70 | 49.26 | 63.11 | 0.00 | 0.00 | 0.00 |
| February | 59.73 | 42.54 | 17.19 | 70.75 | 59.83 | 0.00 | 0.00 | 0.00 |
| March | 81.53 | 57.42 | 24.12 | 103.78 | 53.45 | 0.00 | 0.00 | 0.00 |
| April | 103.42 | 77.04 | 26.38 | 143.92 | 37.45 | 0.00 | 0.00 | 0.00 |
| May | 113.70 | 84.77 | 28.93 | 167.58 | 26.79 | 0.00 | 0.00 | 0.00 |
| June | 120.33 | 93.62 | 26.71 | 186.63 | 16.35 | 0.00 | 0.00 | 0.00 |
| July | 104.12 | 75.39 | 28.73 | 163.60 | 12.85 | 0.00 | 0.00 | 0.00 |
| August | 96.79 | 69.96 | 26.83 | 149.52 | 16.61 | 0.00 | 0.00 | 0.00 |
| September | 88.96 | 66.74 | 22.22 | 134.41 | 26.42 | 0.00 | 0.00 | 0.00 |
| October | 66.50 | 48.31 | 18.18 | 91.94 | 38.39 | 0.00 | 0.00 | 0.00 |
| November | 52.12 | 38.72 | 13.40 | 61.63 | 58.50 | 0.00 | 0.00 | 0.00 |
| December | 41.70 | 27.50 | 14.21 | 43.15 | 69.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.20 | 59.45 | 21.75 | 114.01 | 39.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41.70 | 27.50 | 13.40 | 43.15 | 12.85 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.33 | 93.62 | 28.93 | 186.63 | 69.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 44.66 | 30.97 | 13.70 | 49.26 | 63.11 | 0.00 | 0.00 | 0.00 |
| February | 59.73 | 42.54 | 17.19 | 70.75 | 59.83 | 0.00 | 0.00 | 0.00 |
| March | 81.53 | 57.42 | 24.12 | 103.78 | 53.45 | 0.00 | 0.00 | 0.00 |
| April | 103.42 | 77.04 | 26.38 | 143.92 | 37.45 | 0.00 | 0.00 | 0.00 |
| May | 113.70 | 84.77 | 28.93 | 167.58 | 26.79 | 0.00 | 0.00 | 0.00 |
| June | 120.33 | 93.62 | 26.71 | 186.63 | 16.35 | 0.00 | 0.00 | 0.00 |
| July | 104.12 | 75.39 | 28.73 | 163.60 | 12.85 | 0.00 | 0.00 | 0.00 |
| August | 96.79 | 69.96 | 26.83 | 149.52 | 16.61 | 0.00 | 0.00 | 0.00 |
| September | 88.96 | 66.74 | 22.22 | 134.41 | 26.42 | 0.00 | 0.00 | 0.00 |
| October | 66.50 | 48.31 | 18.18 | 91.94 | 38.39 | 0.00 | 0.00 | 0.00 |
| November | 52.12 | 38.72 | 13.40 | 61.63 | 58.50 | 0.00 | 0.00 | 0.00 |
| December | 41.70 | 27.50 | 14.21 | 43.15 | 69.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.20 | 59.45 | 21.75 | 114.01 | 39.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41.70 | 27.50 | 13.40 | 43.15 | 12.85 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.33 | 93.62 | 28.93 | 186.63 | 69.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 44.66 | 30.97 | 13.70 | 49.26 | 63.11 | 0.00 | 0.00 | 0.00 |
| February | 59.73 | 42.54 | 17.19 | 70.75 | 59.83 | 0.00 | 0.00 | 0.00 |
| March | 81.53 | 57.42 | 24.12 | 103.78 | 53.45 | 0.00 | 0.00 | 0.00 |
| April | 103.42 | 77.04 | 26.38 | 143.92 | 37.45 | 0.00 | 0.00 | 0.00 |
| May | 113.70 | 84.77 | 28.93 | 167.58 | 26.79 | 0.00 | 0.00 | 0.00 |
| June | 120.33 | 93.62 | 26.71 | 186.63 | 16.35 | 0.00 | 0.00 | 0.00 |
| July | 104.12 | 75.39 | 28.73 | 163.60 | 12.85 | 0.00 | 0.00 | 0.00 |
| August | 96.79 | 69.96 | 26.83 | 149.52 | 16.61 | 0.00 | 0.00 | 0.00 |
| September | 88.96 | 66.74 | 22.22 | 134.41 | 26.42 | 0.00 | 0.00 | 0.00 |
| October | 66.50 | 48.31 | 18.18 | 91.94 | 38.39 | 0.00 | 0.00 | 0.00 |
| November | 52.12 | 38.72 | 13.40 | 61.63 | 58.50 | 0.00 | 0.00 | 0.00 |
| December | 41.70 | 27.50 | 14.21 | 43.15 | 69.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.20 | 59.45 | 21.75 | 114.01 | 39.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41.70 | 27.50 | 13.40 | 43.15 | 12.85 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.33 | 93.62 | 28.93 | 186.63 | 69.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 44.66 | 30.97 | 13.70 | 49.26 | 63.11 | 0.00 | 0.00 | 0.00 |
| February | 59.73 | 42.54 | 17.19 | 70.75 | 59.83 | 0.00 | 0.00 | 0.00 |
| March | 81.53 | 57.42 | 24.12 | 103.78 | 53.45 | 0.00 | 0.00 | 0.00 |
| April | 103.42 | 77.04 | 26.38 | 143.92 | 37.45 | 0.00 | 0.00 | 0.00 |
| May | 113.70 | 84.77 | 28.93 | 167.58 | 26.79 | 0.00 | 0.00 | 0.00 |
| June | 120.33 | 93.62 | 26.71 | 186.63 | 16.35 | 0.00 | 0.00 | 0.00 |
| July | 104.12 | 75.39 | 28.73 | 163.60 | 12.85 | 0.00 | 0.00 | 0.00 |
| August | 96.79 | 69.96 | 26.83 | 149.52 | 16.61 | 0.00 | 0.00 | 0.00 |
| September | 88.96 | 66.74 | 22.22 | 134.41 | 26.42 | 0.00 | 0.00 | 0.00 |
| October | 66.50 | 48.31 | 18.18 | 91.94 | 38.39 | 0.00 | 0.00 | 0.00 |
| November | 52.12 | 38.72 | 13.40 | 61.63 | 58.50 | 0.00 | 0.00 | 0.00 |
| December | 41.70 | 27.50 | 14.21 | 43.15 | 69.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.20 | 59.45 | 21.75 | 114.01 | 39.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41.70 | 27.50 | 13.40 | 43.15 | 12.85 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.33 | 93.62 | 28.93 | 186.63 | 69.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 44.66 | 30.97 | 13.70 | 49.26 | 63.11 | 0.00 | 0.00 | 0.00 |
| February | 59.73 | 42.54 | 17.19 | 70.75 | 59.83 | 0.00 | 0.00 | 0.00 |
| March | 81.53 | 57.42 | 24.12 | 103.78 | 53.45 | 0.00 | 0.00 | 0.00 |
| April | 103.42 | 77.04 | 26.38 | 143.92 | 37.45 | 0.00 | 0.00 | 0.00 |
| May | 113.70 | 84.77 | 28.93 | 167.58 | 26.79 | 0.00 | 0.00 | 0.00 |
| June | 120.33 | 93.62 | 26.71 | 186.63 | 16.35 | 0.00 | 0.00 | 0.00 |
| July | 104.12 | 75.39 | 28.73 | 163.60 | 12.85 | 0.00 | 0.00 | 0.00 |
| August | 96.79 | 69.96 | 26.83 | 149.52 | 16.61 | 0.00 | 0.00 | 0.00 |
| September | 88.96 | 66.74 | 22.22 | 134.41 | 26.42 | 0.00 | 0.00 | 0.00 |
| October | 66.50 | 48.31 | 18.18 | 91.94 | 38.39 | 0.00 | 0.00 | 0.00 |
| November | 52.12 | 38.72 | 13.40 | 61.63 | 58.50 | 0.00 | 0.00 | 0.00 |
| December | 41.70 | 27.50 | 14.21 | 43.15 | 69.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.20 | 59.45 | 21.75 | 114.01 | 39.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41.70 | 27.50 | 13.40 | 43.15 | 12.85 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 120.33 | 93.62 | 28.93 | 186.63 | 69.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.82 | 7.50 | 6.33 | 11.94 | 34.98 | 0.00 | 0.00 | 0.00 |
| February | 18.50 | 10.54 | 7.95 | 19.04 | 31.38 | 0.00 | 0.00 | 0.00 |
| March | 22.84 | 12.58 | 10.25 | 25.94 | 26.69 | 0.00 | 0.00 | 0.00 |
| April | 27.52 | 15.27 | 12.25 | 39.05 | 15.75 | 0.00 | 0.00 | 0.00 |
| May | 28.40 | 15.43 | 12.96 | 46.95 | 9.16 | 0.00 | 0.00 | 0.00 |
| June | 28.41 | 15.81 | 12.61 | 54.40 | 4.44 | 0.00 | 0.00 | 0.00 |
| July | 25.48 | 13.32 | 12.16 | 48.95 | 3.78 | 0.00 | 0.00 | 0.00 |
| August | 24.24 | 12.41 | 11.84 | 44.48 | 5.42 | 0.00 | 0.00 | 0.00 |
| September | 24.02 | 13.70 | 10.31 | 40.64 | 10.15 | 0.00 | 0.00 | 0.00 |
| October | 18.47 | 9.97 | 8.50 | 25.04 | 17.98 | 0.00 | 0.00 | 0.00 |
| November | 16.56 | 9.64 | 6.92 | 16.61 | 30.46 | 0.00 | 0.00 | 0.00 |
| December | 13.81 | 7.32 | 6.49 | 11.19 | 37.97 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 21.84 | 11.95 | 9.89 | 32.06 | 18.95 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 13.81 | 7.32 | 6.33 | 11.19 | 3.78 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 28.41 | 15.81 | 12.96 | 54.40 | 37.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 163.63 | 88.76 | 74.87 | 141.30 | 413.71 | 0.00 | 0.00 | 0.00 |
| February | 218.92 | 124.78 | 94.14 | 225.51 | 371.02 | 0.00 | 0.00 | 0.00 |
| March | 270.29 | 148.92 | 121.37 | 307.40 | 315.40 | 0.00 | 0.00 | 0.00 |
| April | 325.69 | 180.68 | 145.01 | 463.11 | 186.31 | 0.00 | 0.00 | 0.00 |
| May | 336.09 | 182.65 | 153.44 | 556.64 | 108.45 | 0.00 | 0.00 | 0.00 |
| June | 336.28 | 187.07 | 149.21 | 644.69 | 52.60 | 0.00 | 0.00 | 0.00 |
| July | 301.57 | 157.65 | 143.92 | 580.12 | 44.79 | 0.00 | 0.00 | 0.00 |
| August | 286.96 | 146.86 | 140.10 | 527.31 | 64.17 | 0.00 | 0.00 | 0.00 |
| September | 284.30 | 162.21 | 122.09 | 482.11 | 120.19 | 0.00 | 0.00 | 0.00 |
| October | 218.64 | 118.00 | 100.65 | 297.24 | 212.79 | 0.00 | 0.00 | 0.00 |
| November | 195.99 | 114.10 | 81.90 | 196.72 | 360.10 | 0.00 | 0.00 | 0.00 |
| December | 163.49 | 86.62 | 76.87 | 132.49 | 449.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 258.51 | 141.45 | 117.07 | 380.08 | 224.18 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 163.49 | 86.62 | 74.87 | 132.49 | 44.79 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 336.28 | 187.07 | 153.44 | 644.69 | 449.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 83.52 | 45.30 | 38.21 | 67.26 | 251.24 | 21.33 | 0.00 | 0.00 |
| February | 111.74 | 63.69 | 48.05 | 110.56 | 217.48 | 9.67 | 0.00 | 0.00 |
| March | 137.96 | 76.01 | 61.95 | 154.30 | 179.85 | 4.33 | 0.00 | 0.00 |
| April | 166.23 | 92.22 | 74.01 | 234.51 | 106.18 | 0.00 | 0.00 | 0.00 |
| May | 171.54 | 93.23 | 78.32 | 282.64 | 65.82 | 0.00 | 0.00 | 0.00 |
| June | 171.64 | 95.48 | 76.15 | 327.02 | 36.51 | 0.00 | 0.00 | 0.00 |
| July | 153.92 | 80.47 | 73.45 | 293.20 | 31.05 | 0.00 | 0.00 | 0.00 |
| August | 146.46 | 74.96 | 71.51 | 268.23 | 40.83 | 0.00 | 0.00 | 0.00 |
| September | 145.11 | 82.79 | 62.31 | 243.83 | 73.15 | 0.00 | 0.00 | 0.00 |
| October | 111.60 | 60.23 | 51.37 | 149.48 | 123.57 | 0.00 | 0.00 | 0.00 |
| November | 100.04 | 58.24 | 41.80 | 97.38 | 210.13 | 3.17 | 0.00 | 0.00 |
| December | 83.44 | 44.21 | 39.23 | 61.60 | 273.18 | 59.83 | 0.00 | 0.00 |
| Annual Sum or Average | 131.95 | 72.20 | 59.75 | 191.11 | 133.70 | 98.33 | 0.00 | 0.00 |
| Minimum of Months | 83.44 | 44.21 | 38.21 | 61.60 | 31.05 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 171.64 | 95.48 | 78.32 | 327.02 | 273.18 | 59.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 76.98 | 0.00 | 76.98 | 3.67 | 572.15 | 0.00 | 0.00 | 0.00 |
| February | 94.10 | 0.00 | 94.10 | 23.45 | 511.38 | 0.00 | 0.00 | 0.00 |
| March | 123.61 | 0.00 | 123.61 | 57.56 | 439.21 | 0.00 | 0.00 | 0.00 |
| April | 141.83 | 0.73 | 141.11 | 135.83 | 269.48 | 0.00 | 0.00 | 0.00 |
| May | 164.35 | 9.05 | 155.30 | 245.92 | 158.42 | 0.00 | 0.00 | 0.00 |
| June | 174.58 | 18.18 | 156.40 | 373.51 | 88.51 | 0.00 | 0.00 | 0.00 |
| July | 160.82 | 12.66 | 148.15 | 338.03 | 71.76 | 0.00 | 0.00 | 0.00 |
| August | 138.73 | 2.26 | 136.47 | 262.37 | 95.91 | 0.00 | 0.00 | 0.00 |
| September | 121.98 | 0.03 | 121.95 | 192.68 | 194.55 | 0.00 | 0.00 | 0.00 |
| October | 101.34 | 0.00 | 101.34 | 81.69 | 309.69 | 0.00 | 0.00 | 0.00 |
| November | 81.78 | 0.00 | 81.78 | 10.86 | 516.95 | 0.00 | 0.00 | 0.00 |
| December | 76.24 | 0.00 | 76.24 | 2.50 | 636.14 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 121.49 | 3.59 | 117.90 | 144.62 | 321.05 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 76.24 | 0.00 | 76.24 | 2.50 | 71.76 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 174.58 | 18.18 | 156.40 | 373.51 | 636.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.96 | 7.57 | 6.39 | 12.61 | 32.65 | 0.00 | 0.00 | 0.00 |
| February | 18.67 | 10.64 | 8.03 | 20.21 | 29.03 | 0.00 | 0.00 | 0.00 |
| March | 23.05 | 12.70 | 10.35 | 27.35 | 25.05 | 0.00 | 0.00 | 0.00 |
| April | 27.78 | 15.41 | 12.37 | 39.91 | 15.71 | 0.00 | 0.00 | 0.00 |
| May | 28.66 | 15.58 | 13.09 | 47.30 | 10.15 | 0.00 | 0.00 | 0.00 |
| June | 28.68 | 15.96 | 12.73 | 54.37 | 5.76 | 0.00 | 0.00 | 0.00 |
| July | 25.72 | 13.45 | 12.27 | 48.70 | 4.68 | 0.00 | 0.00 | 0.00 |
| August | 24.47 | 12.53 | 11.95 | 44.50 | 6.14 | 0.00 | 0.00 | 0.00 |
| September | 24.25 | 13.83 | 10.41 | 40.63 | 11.58 | 0.00 | 0.00 | 0.00 |
| October | 18.65 | 10.06 | 8.58 | 25.39 | 18.53 | 0.00 | 0.00 | 0.00 |
| November | 16.72 | 9.73 | 6.98 | 17.31 | 29.26 | 0.00 | 0.00 | 0.00 |
| December | 13.94 | 7.39 | 6.56 | 11.77 | 36.05 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 22.05 | 12.06 | 9.98 | 32.54 | 18.67 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 13.94 | 7.39 | 6.39 | 11.77 | 4.68 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 28.68 | 15.96 | 13.09 | 54.37 | 36.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 142.64 | 77.38 | 65.26 | 128.87 | 333.70 | 0.00 | 0.00 | 0.00 |
| February | 190.84 | 108.78 | 82.06 | 206.57 | 296.76 | 0.00 | 0.00 | 0.00 |
| March | 235.62 | 129.82 | 105.80 | 279.58 | 256.01 | 0.00 | 0.00 | 0.00 |
| April | 283.91 | 157.51 | 126.41 | 407.88 | 160.59 | 0.00 | 0.00 | 0.00 |
| May | 292.98 | 159.23 | 133.76 | 483.48 | 103.72 | 0.00 | 0.00 | 0.00 |
| June | 293.15 | 163.08 | 130.06 | 555.83 | 58.91 | 0.00 | 0.00 | 0.00 |
| July | 262.89 | 137.43 | 125.46 | 497.82 | 47.81 | 0.00 | 0.00 | 0.00 |
| August | 250.15 | 128.03 | 122.13 | 454.85 | 62.79 | 0.00 | 0.00 | 0.00 |
| September | 247.84 | 141.41 | 106.43 | 415.31 | 118.34 | 0.00 | 0.00 | 0.00 |
| October | 190.60 | 102.87 | 87.74 | 259.52 | 189.45 | 0.00 | 0.00 | 0.00 |
| November | 170.86 | 99.47 | 71.39 | 176.89 | 299.11 | 0.00 | 0.00 | 0.00 |
| December | 142.52 | 75.51 | 67.01 | 120.28 | 368.50 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 225.36 | 123.31 | 102.05 | 332.65 | 190.79 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 142.52 | 75.51 | 65.26 | 120.28 | 47.81 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 293.15 | 163.08 | 133.76 | 555.83 | 368.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 74.16 | 0.00 | 74.16 | 4.65 | 522.75 | 0.00 | 0.00 | 0.00 |
| February | 90.56 | 0.00 | 90.56 | 23.52 | 471.35 | 0.00 | 0.00 | 0.00 |
| March | 118.51 | 0.00 | 118.51 | 56.24 | 406.82 | 0.00 | 0.00 | 0.00 |
| April | 136.83 | 1.08 | 135.75 | 133.89 | 241.16 | 0.00 | 0.00 | 0.00 |
| May | 162.29 | 11.74 | 150.55 | 247.67 | 134.41 | 0.00 | 0.00 | 0.00 |
| June | 172.57 | 21.24 | 151.32 | 367.31 | 68.76 | 0.00 | 0.00 | 0.00 |
| July | 159.48 | 15.52 | 143.96 | 337.27 | 56.74 | 0.00 | 0.00 | 0.00 |
| August | 134.48 | 2.75 | 131.73 | 255.38 | 81.52 | 0.00 | 0.00 | 0.00 |
| September | 117.35 | 0.05 | 117.30 | 185.80 | 165.64 | 0.00 | 0.00 | 0.00 |
| October | 97.43 | 0.00 | 97.43 | 81.20 | 279.52 | 0.00 | 0.00 | 0.00 |
| November | 78.65 | 0.00 | 78.65 | 10.83 | 476.55 | 0.00 | 0.00 | 0.00 |
| December | 73.59 | 0.00 | 73.59 | 3.08 | 580.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 118.12 | 4.39 | 113.74 | 142.86 | 289.52 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 73.59 | 0.00 | 73.59 | 3.08 | 56.74 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 172.57 | 21.24 | 151.32 | 367.31 | 580.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 3.93 | 0.00 | 3.93 | 0.09 | 35.04 | 0.00 | 0.00 | 0.00 |
| February | 4.82 | 0.00 | 4.82 | 1.05 | 31.30 | 0.00 | 0.00 | 0.00 |
| March | 6.81 | 0.39 | 6.42 | 2.91 | 26.16 | 0.00 | 0.00 | 0.00 |
| April | 19.59 | 10.28 | 9.31 | 26.99 | 13.40 | 0.00 | 0.00 | 0.00 |
| May | 24.59 | 14.06 | 10.52 | 41.94 | 7.57 | 0.00 | 0.00 | 0.00 |
| June | 25.63 | 15.15 | 10.48 | 51.17 | 3.72 | 0.00 | 0.00 | 0.00 |
| July | 22.39 | 12.52 | 9.87 | 44.59 | 3.16 | 0.00 | 0.00 | 0.00 |
| August | 18.81 | 9.64 | 9.17 | 35.89 | 4.61 | 0.00 | 0.00 | 0.00 |
| September | 12.12 | 4.91 | 7.20 | 20.40 | 9.25 | 0.00 | 0.00 | 0.00 |
| October | 5.22 | 0.00 | 5.22 | 4.37 | 18.13 | 0.00 | 0.00 | 0.00 |
| November | 4.22 | 0.00 | 4.22 | 0.47 | 31.69 | 0.00 | 0.00 | 0.00 |
| December | 3.86 | 0.00 | 3.86 | 0.04 | 38.90 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 12.70 | 5.60 | 7.10 | 19.25 | 18.52 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3.86 | 0.00 | 3.86 | 0.04 | 3.16 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 25.63 | 15.15 | 10.52 | 51.17 | 38.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 192.99 | 103.57 | 89.42 | 167.64 | 484.68 | 0.00 | 0.00 | 0.00 |
| February | 264.14 | 150.78 | 113.36 | 280.42 | 431.63 | 0.00 | 0.00 | 0.00 |
| March | 334.50 | 186.90 | 147.60 | 393.52 | 371.67 | 0.00 | 0.00 | 0.00 |
| April | 403.64 | 227.06 | 176.58 | 584.00 | 223.27 | 0.00 | 0.00 | 0.00 |
| May | 416.29 | 229.53 | 186.76 | 694.78 | 133.84 | 0.00 | 0.00 | 0.00 |
| June | 416.78 | 235.09 | 181.69 | 802.02 | 68.08 | 0.00 | 0.00 | 0.00 |
| July | 373.10 | 198.12 | 174.98 | 719.81 | 57.06 | 0.00 | 0.00 | 0.00 |
| August | 354.91 | 184.56 | 170.35 | 654.54 | 80.79 | 0.00 | 0.00 | 0.00 |
| September | 351.90 | 203.67 | 148.24 | 596.51 | 154.52 | 0.00 | 0.00 | 0.00 |
| October | 267.70 | 145.91 | 121.79 | 365.24 | 266.40 | 0.00 | 0.00 | 0.00 |
| November | 230.41 | 133.11 | 97.31 | 230.40 | 437.17 | 0.00 | 0.00 | 0.00 |
| December | 187.58 | 96.63 | 90.95 | 147.60 | 534.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 316.21 | 174.50 | 141.71 | 470.35 | 269.53 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 187.58 | 96.63 | 89.42 | 147.60 | 57.06 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 416.78 | 235.09 | 186.76 | 802.02 | 534.67 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.265090E+09 | 0.149291E+09 | 0.115799E+09 | 0.264110E+09 | 0.605409E+09 |
| February | 0.270179E+09 | 0.143606E+09 | 0.126573E+09 | 0.293818E+09 | 0.486053E+09 |
| March | 0.407623E+09 | 0.218472E+09 | 0.189151E+09 | 0.507132E+09 | 0.450392E+09 |
| April | 0.453415E+09 | 0.244898E+09 | 0.208518E+09 | 0.686606E+09 | 0.260422E+09 |
| May | 0.504651E+09 | 0.270011E+09 | 0.234640E+09 | 0.876063E+09 | 0.152448E+09 |
| June | 0.475392E+09 | 0.255338E+09 | 0.220054E+09 | 0.949405E+09 | 66802895.99 |
| July | 0.435939E+09 | 0.216627E+09 | 0.219312E+09 | 0.875006E+09 | 56429534.30 |
| August | 0.422185E+09 | 0.215162E+09 | 0.207023E+09 | 0.800425E+09 | 90548423.00 |
| September | 0.417822E+09 | 0.232769E+09 | 0.185053E+09 | 0.732417E+09 | 0.186170E+09 |
| October | 0.371666E+09 | 0.216916E+09 | 0.154749E+09 | 0.541443E+09 | 0.334358E+09 |
| November | 0.301896E+09 | 0.183822E+09 | 0.118073E+09 | 0.346143E+09 | 0.536678E+09 |
| December | 0.251393E+09 | 0.136565E+09 | 0.114828E+09 | 0.233496E+09 | 0.667126E+09 |
| Annual Sum or Average | 0.457725E+10 | 0.248348E+10 | 0.209377E+10 | 0.710606E+10 | 0.389284E+10 |
| Minimum of Months | 0.251393E+09 | 0.136565E+09 | 0.114828E+09 | 0.233496E+09 | 56429534.30 |
| Maximum of Months | 0.504651E+09 | 0.270011E+09 | 0.234640E+09 | 0.949405E+09 | 0.667126E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 99076069.04 | 75060382.61 | 24015686.43 | 0.131874E+09 | 83156879.56 |
| February | 83010192.81 | 58520809.86 | 24489382.95 | 0.112672E+09 | 67579104.30 |
| March | 74691255.56 | 43066655.98 | 31624599.58 | 0.103971E+09 | 66603456.36 |
| April | 49006922.22 | 18285633.56 | 30721288.66 | 78034983.72 | 40726538.15 |
| May | 35787160.05 | 5008994.72 | 30778165.33 | 64976194.40 | 23692081.39 |
| June | 29879375.29 | 1895839.00 | 27983536.29 | 69637620.45 | 10160238.40 |
| July | 31473985.53 | 2917671.20 | 28556314.33 | 72877041.44 | 8732931.56 |
| August | 40120575.71 | 10620101.47 | 29500474.24 | 84874686.24 | 13986164.07 |
| September | 60603421.86 | 31485481.86 | 29117940.00 | 0.114284E+09 | 28292279.10 |
| October | 85086851.65 | 57524286.80 | 27562564.85 | 0.134388E+09 | 49103895.11 |
| November | 99091134.98 | 75544730.59 | 23546404.39 | 0.137473E+09 | 73685510.76 |
| December | 0.101477E+09 | 76172834.52 | 25303713.27 | 0.131711E+09 | 90163762.70 |
| Annual Sum or Average | 0.789303E+09 | 0.456103E+09 | 0.333200E+09 | 0.123677E+10 | 0.555883E+09 |
| Minimum of Months | 29879375.29 | 1895839.00 | 23546404.39 | 64976194.40 | 8732931.56 |
| Maximum of Months | 0.101477E+09 | 76172834.52 | 31624599.58 | 0.137473E+09 | 90163762.70 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.687617E+09 | 0.520941E+09 | 0.166676E+09 | 0.915240E+09 | 0.577133E+09 |
| February | 0.576115E+09 | 0.406151E+09 | 0.169963E+09 | 0.781976E+09 | 0.469018E+09 |
| March | 0.518379E+09 | 0.298895E+09 | 0.219484E+09 | 0.721592E+09 | 0.462247E+09 |
| April | 0.340122E+09 | 0.126908E+09 | 0.213215E+09 | 0.541563E+09 | 0.282681E+09 |
| May | 0.248373E+09 | 34763869.54 | 0.213609E+09 | 0.449908E+09 | 0.164511E+09 |
| June | 0.207371E+09 | 13157670.04 | 0.194214E+09 | 0.481494E+09 | 70515027.26 |
| July | 0.218439E+09 | 20249480.49 | 0.198189E+09 | 0.504502E+09 | 60622360.70 |
| August | 0.278448E+09 | 73706570.36 | 0.204742E+09 | 0.588829E+09 | 97072123.29 |
| September | 0.420605E+09 | 0.218518E+09 | 0.202087E+09 | 0.793168E+09 | 0.196354E+09 |
| October | 0.590527E+09 | 0.399235E+09 | 0.191292E+09 | 0.932689E+09 | 0.340795E+09 |
| November | 0.687721E+09 | 0.524302E+09 | 0.163419E+09 | 0.954101E+09 | 0.511399E+09 |
| December | 0.704277E+09 | 0.528661E+09 | 0.175615E+09 | 0.914112E+09 | 0.625763E+09 |
| Annual Sum or Average | 0.547799E+10 | 0.316549E+10 | 0.231250E+10 | 0.857917E+10 | 0.385811E+10 |
| Minimum of Months | 0.207371E+09 | 13157670.04 | 0.163419E+09 | 0.449908E+09 | 60622360.70 |
| Maximum of Months | 0.704277E+09 | 0.528661E+09 | 0.219484E+09 | 0.954101E+09 | 0.625763E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.126351E+10 | 0.957244E+09 | 0.306270E+09 | 0.166284E+10 | 0.113609E+10 |
| February | 0.105863E+10 | 0.746315E+09 | 0.312311E+09 | 0.141888E+10 | 0.925070E+09 |
| March | 0.952534E+09 | 0.549229E+09 | 0.403306E+09 | 0.131077E+10 | 0.904950E+09 |
| April | 0.624982E+09 | 0.233196E+09 | 0.391785E+09 | 0.995977E+09 | 0.540329E+09 |
| May | 0.456390E+09 | 63879651.68 | 0.392510E+09 | 0.838975E+09 | 0.304437E+09 |
| June | 0.381048E+09 | 24177612.86 | 0.356870E+09 | 0.905965E+09 | 0.125619E+09 |
| July | 0.401384E+09 | 37209026.99 | 0.364175E+09 | 0.972403E+09 | 97721325.10 |
| August | 0.511655E+09 | 0.135438E+09 | 0.376216E+09 | 0.111828E+10 | 0.164627E+09 |
| September | 0.772872E+09 | 0.401534E+09 | 0.371338E+09 | 0.147537E+10 | 0.353943E+09 |
| October | 0.108511E+10 | 0.733607E+09 | 0.351503E+09 | 0.172110E+10 | 0.639789E+09 |
| November | 0.126371E+10 | 0.963421E+09 | 0.300285E+09 | 0.174421E+10 | 0.986620E+09 |
| December | 0.129413E+10 | 0.971431E+09 | 0.322697E+09 | 0.165912E+10 | 0.122048E+10 |
| Annual Sum or Average | 0.100660E+11 | 0.581668E+10 | 0.424927E+10 | 0.158239E+11 | 0.739967E+10 |
| Minimum of Months | 0.381048E+09 | 24177612.86 | 0.300285E+09 | 0.838975E+09 | 97721325.10 |
| Maximum of Months | 0.129413E+10 | 0.971431E+09 | 0.403306E+09 | 0.174421E+10 | 0.122048E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.126351E+10 | 0.957244E+09 | 0.306270E+09 | 0.166284E+10 | 0.113609E+10 |
| February | 0.105863E+10 | 0.746315E+09 | 0.312311E+09 | 0.141888E+10 | 0.925070E+09 |
| March | 0.952534E+09 | 0.549229E+09 | 0.403306E+09 | 0.131077E+10 | 0.904950E+09 |
| April | 0.624982E+09 | 0.233196E+09 | 0.391785E+09 | 0.995977E+09 | 0.540329E+09 |
| May | 0.456390E+09 | 63879651.68 | 0.392510E+09 | 0.838975E+09 | 0.304437E+09 |
| June | 0.381048E+09 | 24177612.86 | 0.356870E+09 | 0.905965E+09 | 0.125619E+09 |
| July | 0.401384E+09 | 37209026.99 | 0.364175E+09 | 0.972403E+09 | 97721325.10 |
| August | 0.511655E+09 | 0.135438E+09 | 0.376216E+09 | 0.111828E+10 | 0.164627E+09 |
| September | 0.772872E+09 | 0.401534E+09 | 0.371338E+09 | 0.147537E+10 | 0.353943E+09 |
| October | 0.108511E+10 | 0.733607E+09 | 0.351503E+09 | 0.172110E+10 | 0.639789E+09 |
| November | 0.126371E+10 | 0.963421E+09 | 0.300285E+09 | 0.174421E+10 | 0.986620E+09 |
| December | 0.129413E+10 | 0.971431E+09 | 0.322697E+09 | 0.165912E+10 | 0.122048E+10 |
| Annual Sum or Average | 0.100660E+11 | 0.581668E+10 | 0.424927E+10 | 0.158239E+11 | 0.739967E+10 |
| Minimum of Months | 0.381048E+09 | 24177612.86 | 0.300285E+09 | 0.838975E+09 | 97721325.10 |
| Maximum of Months | 0.129413E+10 | 0.971431E+09 | 0.403306E+09 | 0.174421E+10 | 0.122048E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.126349E+10 | 0.957226E+09 | 0.306264E+09 | 0.166281E+10 | 0.113606E+10 |
| February | 0.105861E+10 | 0.746301E+09 | 0.312305E+09 | 0.141885E+10 | 0.925052E+09 |
| March | 0.952516E+09 | 0.549218E+09 | 0.403298E+09 | 0.131074E+10 | 0.904932E+09 |
| April | 0.624970E+09 | 0.233192E+09 | 0.391778E+09 | 0.995957E+09 | 0.540319E+09 |
| May | 0.456381E+09 | 63878413.63 | 0.392503E+09 | 0.838959E+09 | 0.304431E+09 |
| June | 0.381041E+09 | 24177144.27 | 0.356864E+09 | 0.905948E+09 | 0.125617E+09 |
| July | 0.401377E+09 | 37208305.84 | 0.364168E+09 | 0.972384E+09 | 97719431.17 |
| August | 0.511645E+09 | 0.135435E+09 | 0.376209E+09 | 0.111826E+10 | 0.164624E+09 |
| September | 0.772857E+09 | 0.401526E+09 | 0.371331E+09 | 0.147534E+10 | 0.353936E+09 |
| October | 0.108509E+10 | 0.733592E+09 | 0.351496E+09 | 0.172107E+10 | 0.639777E+09 |
| November | 0.126368E+10 | 0.963402E+09 | 0.300280E+09 | 0.174418E+10 | 0.986601E+09 |
| December | 0.129410E+10 | 0.971412E+09 | 0.322690E+09 | 0.165909E+10 | 0.122046E+10 |
| Annual Sum or Average | 0.100658E+11 | 0.581657E+10 | 0.424919E+10 | 0.158236E+11 | 0.739953E+10 |
| Minimum of Months | 0.381041E+09 | 24177144.27 | 0.300280E+09 | 0.838959E+09 | 97719431.17 |
| Maximum of Months | 0.129410E+10 | 0.971412E+09 | 0.403298E+09 | 0.174418E+10 | 0.122046E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 88363542.88 | 49763851.35 | 38599691.53 | 90832108.50 | 0.207323E+09 |
| February | 90059831.58 | 47868739.55 | 42191092.04 | 0.100190E+09 | 0.169098E+09 |
| March | 0.135875E+09 | 72824222.81 | 63050606.59 | 0.168719E+09 | 0.160182E+09 |
| April | 0.151139E+09 | 81632895.25 | 69506104.79 | 0.227959E+09 | 91517886.97 |
| May | 0.168217E+09 | 90003984.72 | 78213505.00 | 0.291049E+09 | 52938949.33 |
| June | 0.158465E+09 | 85112889.14 | 73351624.10 | 0.317632E+09 | 23230981.10 |
| July | 0.145314E+09 | 72209221.10 | 73104399.47 | 0.294977E+09 | 17723481.02 |
| August | 0.140729E+09 | 71720812.08 | 69008002.58 | 0.271489E+09 | 27899170.24 |
| September | 0.139275E+09 | 77590030.53 | 61684563.74 | 0.247815E+09 | 59600214.87 |
| October | 0.123889E+09 | 72305718.98 | 51583335.65 | 0.183734E+09 | 0.110188E+09 |
| November | 0.100632E+09 | 61274315.14 | 39357906.06 | 0.117835E+09 | 0.181278E+09 |
| December | 83797994.24 | 45521768.27 | 38276225.97 | 81221677.31 | 0.226552E+09 |
| Annual Sum or Average | 0.152576E+10 | 0.827828E+09 | 0.697927E+09 | 0.239345E+10 | 0.132753E+10 |
| Minimum of Months | 83797994.24 | 45521768.27 | 38276225.97 | 81221677.31 | 17723481.02 |
| Maximum of Months | 0.168217E+09 | 90003984.72 | 78213505.00 | 0.317632E+09 | 0.226552E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.265090E+09 | 0.149291E+09 | 0.115799E+09 | 0.290190E+09 | 0.540485E+09 |
| February | 0.270179E+09 | 0.143606E+09 | 0.126573E+09 | 0.319538E+09 | 0.438235E+09 |
| March | 0.407623E+09 | 0.218472E+09 | 0.189151E+09 | 0.529858E+09 | 0.420199E+09 |
| April | 0.453415E+09 | 0.244898E+09 | 0.208518E+09 | 0.699097E+09 | 0.249380E+09 |
| May | 0.504651E+09 | 0.270011E+09 | 0.234640E+09 | 0.879372E+09 | 0.151065E+09 |
| June | 0.475392E+09 | 0.255338E+09 | 0.220054E+09 | 0.948917E+09 | 67339480.74 |
| July | 0.435939E+09 | 0.216627E+09 | 0.219312E+09 | 0.876875E+09 | 56050119.59 |
| August | 0.422185E+09 | 0.215162E+09 | 0.207023E+09 | 0.810261E+09 | 85780886.38 |
| September | 0.417822E+09 | 0.232769E+09 | 0.185053E+09 | 0.746486E+09 | 0.174873E+09 |
| October | 0.371666E+09 | 0.216916E+09 | 0.154749E+09 | 0.561003E+09 | 0.309883E+09 |
| November | 0.301896E+09 | 0.183822E+09 | 0.118073E+09 | 0.367491E+09 | 0.484832E+09 |
| December | 0.251393E+09 | 0.136565E+09 | 0.114828E+09 | 0.258157E+09 | 0.603925E+09 |
| Annual Sum or Average | 0.457725E+10 | 0.248348E+10 | 0.209377E+10 | 0.728725E+10 | 0.358205E+10 |
| Minimum of Months | 0.251393E+09 | 0.136565E+09 | 0.114828E+09 | 0.258157E+09 | 56050119.59 |
| Maximum of Months | 0.504651E+09 | 0.270011E+09 | 0.234640E+09 | 0.948917E+09 | 0.603925E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 11147379.91 | 0.00 | 11147379.91 | 668751.83 | 88463554.54 |
| February | 12353932.66 | 0.00 | 12353932.66 | 3824080.96 | 70044528.95 |
| March | 18310941.49 | 0.00 | 18310941.49 | 9689387.64 | 66232318.55 |
| April | 20340328.54 | 185349.71 | 20154978.84 | 22807046.83 | 36670002.28 |
| May | 25554213.52 | 2254585.19 | 23299628.33 | 44755478.73 | 19374830.14 |
| June | 26935926.99 | 4013936.63 | 22921990.36 | 66830761.26 | 8365261.30 |
| July | 25114223.02 | 2936947.49 | 22177275.53 | 62157313.08 | 7179293.12 |
| August | 20453907.92 | 500113.05 | 19953794.86 | 45980932.42 | 11369081.05 |
| September | 17141213.44 | 6557.20 | 17134656.24 | 31079183.79 | 24911547.32 |
| October | 14767025.26 | 0.00 | 14767025.26 | 13057701.79 | 47613006.86 |
| November | 11493912.12 | 0.00 | 11493912.12 | 1457947.08 | 78994691.07 |
| December | 10980455.56 | 0.00 | 10980455.56 | 526253.42 | 99885466.70 |
| Annual Sum or Average | 0.214593E+09 | 9897489.27 | 0.204696E+09 | 0.302835E+09 | 0.559104E+09 |
| Minimum of Months | 10980455.56 | 0.00 | 10980455.56 | 526253.42 | 7179293.12 |
| Maximum of Months | 26935926.99 | 4013936.63 | 23299628.33 | 66830761.26 | 99885466.70 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 82769061.30 | 0.00 | 82769061.30 | 6488513.58 | 0.611275E+09 |
| February | 91603303.23 | 0.00 | 91603303.23 | 30573678.90 | 0.486081E+09 |
| March | 0.134912E+09 | 0.00 | 0.134912E+09 | 74556567.99 | 0.460946E+09 |
| April | 0.150034E+09 | 1286380.48 | 0.148748E+09 | 0.167933E+09 | 0.257389E+09 |
| May | 0.187231E+09 | 15647472.16 | 0.171583E+09 | 0.322756E+09 | 0.138496E+09 |
| June | 0.196137E+09 | 27857879.09 | 0.168279E+09 | 0.474168E+09 | 60516704.22 |
| July | 0.183863E+09 | 20383263.53 | 0.163480E+09 | 0.444036E+09 | 51829926.84 |
| August | 0.151246E+09 | 3471261.21 | 0.147775E+09 | 0.331347E+09 | 81285239.39 |
| September | 0.127122E+09 | 48859.77 | 0.127073E+09 | 0.226634E+09 | 0.176249E+09 |
| October | 0.109389E+09 | 0.00 | 0.109389E+09 | 98985894.63 | 0.332327E+09 |
| November | 85232029.91 | 0.00 | 85232029.91 | 12828936.49 | 0.546855E+09 |
| December | 81699262.97 | 0.00 | 81699262.97 | 4760847.20 | 0.690684E+09 |
| Annual Sum or Average | 0.158124E+10 | 68695116.24 | 0.151254E+10 | 0.219507E+10 | 0.389394E+10 |
| Minimum of Months | 81699262.97 | 0.00 | 81699262.97 | 4760847.20 | 51829926.84 |
| Maximum of Months | 0.196137E+09 | 27857879.09 | 0.171583E+09 | 0.474168E+09 | 0.690684E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.135302E+09 | 0.00 | 0.135302E+09 | 4463065.68 | 0.120551E+10 |
| February | 0.150126E+09 | 0.00 | 0.150126E+09 | 38494581.92 | 0.957086E+09 |
| March | 0.223169E+09 | 0.00 | 0.223169E+09 | 0.104906E+09 | 0.901246E+09 |
| April | 0.245328E+09 | 1192568.79 | 0.244136E+09 | 0.282129E+09 | 0.488964E+09 |
| May | 0.299276E+09 | 19569620.00 | 0.279706E+09 | 0.551531E+09 | 0.253044E+09 |
| June | 0.313430E+09 | 38104343.58 | 0.275325E+09 | 0.828609E+09 | 0.101276E+09 |
| July | 0.290592E+09 | 25732385.74 | 0.264859E+09 | 0.795656E+09 | 76728433.31 |
| August | 0.244068E+09 | 3827188.49 | 0.240241E+09 | 0.616720E+09 | 0.127859E+09 |
| September | 0.208665E+09 | 54149.56 | 0.208611E+09 | 0.405818E+09 | 0.299498E+09 |
| October | 0.179649E+09 | 0.00 | 0.179649E+09 | 0.164178E+09 | 0.607150E+09 |
| November | 0.139816E+09 | 0.00 | 0.139816E+09 | 14963374.22 | 0.105090E+10 |
| December | 0.133019E+09 | 0.00 | 0.133019E+09 | 3387606.92 | 0.134660E+10 |
| Annual Sum or Average | 0.256244E+10 | 88480256.15 | 0.247396E+10 | 0.381085E+10 | 0.741587E+10 |
| Minimum of Months | 0.133019E+09 | 0.00 | 0.133019E+09 | 3387606.92 | 76728433.31 |
| Maximum of Months | 0.313430E+09 | 38104343.58 | 0.279706E+09 | 0.828609E+09 | 0.134660E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.142226E+09 | 0.00 | 0.142226E+09 | 5687447.85 | 0.120768E+10 |
| February | 0.157618E+09 | 0.00 | 0.157618E+09 | 41712875.87 | 0.960976E+09 |
| March | 0.233611E+09 | 0.00 | 0.233611E+09 | 0.112529E+09 | 0.906178E+09 |
| April | 0.258851E+09 | 2121413.24 | 0.256730E+09 | 0.291747E+09 | 0.489925E+09 |
| May | 0.321669E+09 | 25832849.95 | 0.295836E+09 | 0.575796E+09 | 0.249573E+09 |
| June | 0.338467E+09 | 47621269.34 | 0.290845E+09 | 0.866037E+09 | 0.102867E+09 |
| July | 0.315333E+09 | 34052433.36 | 0.281281E+09 | 0.835712E+09 | 78278411.89 |
| August | 0.259952E+09 | 5879554.93 | 0.254073E+09 | 0.636216E+09 | 0.129121E+09 |
| September | 0.218579E+09 | 65938.23 | 0.218513E+09 | 0.415687E+09 | 0.305679E+09 |
| October | 0.188405E+09 | 0.00 | 0.188405E+09 | 0.171733E+09 | 0.612656E+09 |
| November | 0.146646E+09 | 0.00 | 0.146646E+09 | 16658457.33 | 0.105483E+10 |
| December | 0.140098E+09 | 0.00 | 0.140098E+09 | 4399309.58 | 0.135035E+10 |
| Annual Sum or Average | 0.272146E+10 | 0.115573E+09 | 0.260588E+10 | 0.397392E+10 | 0.744811E+10 |
| Minimum of Months | 0.140098E+09 | 0.00 | 0.140098E+09 | 4399309.58 | 78278411.89 |
| Maximum of Months | 0.338467E+09 | 47621269.34 | 0.295836E+09 | 0.866037E+09 | 0.135035E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.142278E+09 | 0.00 | 0.142278E+09 | 5698424.04 | 0.120764E+10 |
| February | 0.157675E+09 | 0.00 | 0.157675E+09 | 41744006.44 | 0.960962E+09 |
| March | 0.233686E+09 | 0.00 | 0.233686E+09 | 0.112593E+09 | 0.906174E+09 |
| April | 0.259587E+09 | 2363051.84 | 0.257224E+09 | 0.291847E+09 | 0.488432E+09 |
| May | 0.325106E+09 | 28068940.53 | 0.297037E+09 | 0.581962E+09 | 0.248688E+09 |
| June | 0.341028E+09 | 49328012.60 | 0.291700E+09 | 0.871013E+09 | 0.102880E+09 |
| July | 0.318448E+09 | 36065346.42 | 0.282383E+09 | 0.841703E+09 | 78091149.54 |
| August | 0.261073E+09 | 6392360.67 | 0.254680E+09 | 0.637865E+09 | 0.128456E+09 |
| September | 0.218757E+09 | 79543.60 | 0.218677E+09 | 0.415783E+09 | 0.305490E+09 |
| October | 0.188471E+09 | 0.00 | 0.188471E+09 | 0.171803E+09 | 0.612669E+09 |
| November | 0.146698E+09 | 0.00 | 0.146698E+09 | 16677725.67 | 0.105481E+10 |
| December | 0.140151E+09 | 0.00 | 0.140151E+09 | 4407262.66 | 0.135032E+10 |
| Annual Sum or Average | 0.273296E+10 | 0.122297E+09 | 0.261066E+10 | 0.399310E+10 | 0.744461E+10 |
| Minimum of Months | 0.140151E+09 | 0.00 | 0.140151E+09 | 4407262.66 | 78091149.54 |
| Maximum of Months | 0.341028E+09 | 49328012.60 | 0.297037E+09 | 0.871013E+09 | 0.135032E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.265090E+09 | 0.149291E+09 | 0.115799E+09 | 0.264516E+09 | 0.604764E+09 |
| February | 0.270179E+09 | 0.143606E+09 | 0.126573E+09 | 0.294211E+09 | 0.486110E+09 |
| March | 0.407623E+09 | 0.218472E+09 | 0.189151E+09 | 0.507549E+09 | 0.450797E+09 |
| April | 0.453415E+09 | 0.244898E+09 | 0.208518E+09 | 0.687072E+09 | 0.260774E+09 |
| May | 0.504651E+09 | 0.270011E+09 | 0.234640E+09 | 0.876684E+09 | 0.152628E+09 |
| June | 0.475392E+09 | 0.255338E+09 | 0.220054E+09 | 0.950020E+09 | 66820133.85 |
| July | 0.435939E+09 | 0.216627E+09 | 0.219312E+09 | 0.876399E+09 | 56053967.78 |
| August | 0.422185E+09 | 0.215162E+09 | 0.207023E+09 | 0.801593E+09 | 90198654.04 |
| September | 0.417822E+09 | 0.232769E+09 | 0.185053E+09 | 0.733038E+09 | 0.186097E+09 |
| October | 0.371666E+09 | 0.216916E+09 | 0.154749E+09 | 0.541892E+09 | 0.334457E+09 |
| November | 0.301896E+09 | 0.183822E+09 | 0.118073E+09 | 0.346503E+09 | 0.536440E+09 |
| December | 0.251393E+09 | 0.136565E+09 | 0.114828E+09 | 0.233989E+09 | 0.666158E+09 |
| Annual Sum or Average | 0.457725E+10 | 0.248348E+10 | 0.209377E+10 | 0.711347E+10 | 0.389130E+10 |
| Minimum of Months | 0.251393E+09 | 0.136565E+09 | 0.114828E+09 | 0.233989E+09 | 56053967.78 |
| Maximum of Months | 0.504651E+09 | 0.270011E+09 | 0.234640E+09 | 0.950020E+09 | 0.666158E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 96972807.98 | 74962740.89 | 22010067.09 | 0.129501E+09 | 81751990.31 |
| February | 80700241.26 | 58388786.31 | 22311454.96 | 0.110099E+09 | 66417330.49 |
| March | 71827563.78 | 43059553.14 | 28768010.63 | 0.100472E+09 | 65038637.87 |
| April | 45776540.44 | 18285633.56 | 27490906.88 | 74253429.58 | 39370378.90 |
| May | 32188530.02 | 5008994.72 | 27179535.30 | 60675126.80 | 22297979.10 |
| June | 26529566.42 | 1895839.00 | 24633727.41 | 65931472.66 | 9284175.78 |
| July | 27989891.71 | 2917671.20 | 25072220.51 | 68470442.40 | 7946667.04 |
| August | 36737615.49 | 10620101.47 | 26117514.02 | 80587800.32 | 13026476.94 |
| September | 57633955.97 | 31482976.31 | 26150979.65 | 0.110456E+09 | 26954150.54 |
| October | 82466784.60 | 57443776.25 | 25023008.35 | 0.131109E+09 | 47810321.52 |
| November | 96524415.46 | 75145290.48 | 21379124.98 | 0.135037E+09 | 72979767.31 |
| December | 98724644.35 | 75560480.59 | 23164163.76 | 0.129003E+09 | 89150999.43 |
| Annual Sum or Average | 0.754073E+09 | 0.454772E+09 | 0.299301E+09 | 0.119559E+10 | 0.542029E+09 |
| Minimum of Months | 26529566.42 | 1895839.00 | 21379124.98 | 60675126.80 | 7946667.04 |
| Maximum of Months | 98724644.35 | 75560480.59 | 28768010.63 | 0.135037E+09 | 89150999.43 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.666366E+09 | 0.520263E+09 | 0.146103E+09 | 0.890423E+09 | 0.562042E+09 |
| February | 0.552863E+09 | 0.405235E+09 | 0.147628E+09 | 0.755176E+09 | 0.455708E+09 |
| March | 0.488856E+09 | 0.298843E+09 | 0.190013E+09 | 0.685323E+09 | 0.445970E+09 |
| April | 0.306785E+09 | 0.126908E+09 | 0.179877E+09 | 0.502414E+09 | 0.268672E+09 |
| May | 0.211236E+09 | 34763869.54 | 0.176472E+09 | 0.405439E+09 | 0.150296E+09 |
| June | 0.172802E+09 | 13157670.04 | 0.159644E+09 | 0.443056E+09 | 61578991.75 |
| July | 0.182483E+09 | 20249480.49 | 0.162233E+09 | 0.458428E+09 | 52820953.77 |
| August | 0.243536E+09 | 73706570.36 | 0.169830E+09 | 0.544100E+09 | 87456821.58 |
| September | 0.389972E+09 | 0.218501E+09 | 0.171471E+09 | 0.753391E+09 | 0.182637E+09 |
| October | 0.563846E+09 | 0.398676E+09 | 0.165169E+09 | 0.898759E+09 | 0.326872E+09 |
| November | 0.663183E+09 | 0.521530E+09 | 0.141653E+09 | 0.929257E+09 | 0.500986E+09 |
| December | 0.678415E+09 | 0.524412E+09 | 0.154004E+09 | 0.887193E+09 | 0.612467E+09 |
| Annual Sum or Average | 0.512034E+10 | 0.315624E+10 | 0.196410E+10 | 0.815296E+10 | 0.370751E+10 |
| Minimum of Months | 0.172802E+09 | 13157670.04 | 0.141653E+09 | 0.405439E+09 | 52820953.77 |
| Maximum of Months | 0.678415E+09 | 0.524412E+09 | 0.190013E+09 | 0.929257E+09 | 0.612467E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.121235E+10 | 0.950220E+09 | 0.262129E+09 | 0.160554E+10 | 0.110861E+10 |
| February | 0.101041E+10 | 0.744659E+09 | 0.265756E+09 | 0.136354E+10 | 0.896712E+09 |
| March | 0.890875E+09 | 0.549119E+09 | 0.341756E+09 | 0.123474E+10 | 0.873282E+09 |
| April | 0.555374E+09 | 0.233196E+09 | 0.322177E+09 | 0.914507E+09 | 0.512331E+09 |
| May | 0.378847E+09 | 63879651.68 | 0.314967E+09 | 0.747309E+09 | 0.275683E+09 |
| June | 0.308866E+09 | 24177612.86 | 0.284689E+09 | 0.827390E+09 | 0.107389E+09 |
| July | 0.326309E+09 | 37209026.99 | 0.289100E+09 | 0.880341E+09 | 82023927.96 |
| August | 0.438758E+09 | 0.135438E+09 | 0.303320E+09 | 0.102909E+10 | 0.144836E+09 |
| September | 0.708904E+09 | 0.401493E+09 | 0.307411E+09 | 0.139376E+10 | 0.324656E+09 |
| October | 0.102913E+10 | 0.732225E+09 | 0.296909E+09 | 0.165069E+10 | 0.609449E+09 |
| November | 0.121031E+10 | 0.955794E+09 | 0.254515E+09 | 0.169085E+10 | 0.964790E+09 |
| December | 0.122803E+10 | 0.952053E+09 | 0.275972E+09 | 0.159144E+10 | 0.119963E+10 |
| Annual Sum or Average | 0.929816E+10 | 0.577946E+10 | 0.351870E+10 | 0.149292E+11 | 0.709940E+10 |
| Minimum of Months | 0.308866E+09 | 24177612.86 | 0.254515E+09 | 0.747309E+09 | 82023927.96 |
| Maximum of Months | 0.122803E+10 | 0.955794E+09 | 0.341756E+09 | 0.169085E+10 | 0.119963E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.120799E+10 | 0.946698E+09 | 0.261293E+09 | 0.160469E+10 | 0.111618E+10 |
| February | 0.100824E+10 | 0.743054E+09 | 0.265188E+09 | 0.136287E+10 | 0.900828E+09 |
| March | 0.890504E+09 | 0.548963E+09 | 0.341541E+09 | 0.123465E+10 | 0.873924E+09 |
| April | 0.555284E+09 | 0.233196E+09 | 0.322087E+09 | 0.914402E+09 | 0.512294E+09 |
| May | 0.378746E+09 | 63879651.68 | 0.314867E+09 | 0.747191E+09 | 0.275647E+09 |
| June | 0.308773E+09 | 24177612.86 | 0.284595E+09 | 0.827288E+09 | 0.107367E+09 |
| July | 0.326212E+09 | 37209026.99 | 0.289003E+09 | 0.880216E+09 | 82006583.09 |
| August | 0.438664E+09 | 0.135438E+09 | 0.303226E+09 | 0.102896E+10 | 0.144814E+09 |
| September | 0.708755E+09 | 0.401444E+09 | 0.307311E+09 | 0.139365E+10 | 0.324793E+09 |
| October | 0.102813E+10 | 0.731499E+09 | 0.296627E+09 | 0.164983E+10 | 0.610614E+09 |
| November | 0.120564E+10 | 0.952002E+09 | 0.253636E+09 | 0.168879E+10 | 0.972278E+09 |
| December | 0.122317E+10 | 0.947924E+09 | 0.275250E+09 | 0.159043E+10 | 0.120782E+10 |
| Annual Sum or Average | 0.928011E+10 | 0.576549E+10 | 0.351462E+10 | 0.149230E+11 | 0.712856E+10 |
| Minimum of Months | 0.308773E+09 | 24177612.86 | 0.253636E+09 | 0.747191E+09 | 82006583.09 |
| Maximum of Months | 0.122317E+10 | 0.952002E+09 | 0.341541E+09 | 0.168879E+10 | 0.120782E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.113123E+10 | 0.885790E+09 | 0.245443E+09 | 0.148724E+10 | 0.112235E+10 |
| February | 0.946232E+09 | 0.696785E+09 | 0.249446E+09 | 0.127065E+10 | 0.911721E+09 |
| March | 0.850947E+09 | 0.525470E+09 | 0.325478E+09 | 0.117528E+10 | 0.877568E+09 |
| April | 0.536030E+09 | 0.227292E+09 | 0.308738E+09 | 0.886015E+09 | 0.505927E+09 |
| May | 0.364917E+09 | 62831192.96 | 0.302086E+09 | 0.731465E+09 | 0.268618E+09 |
| June | 0.297350E+09 | 23875719.06 | 0.273474E+09 | 0.817874E+09 | 0.103287E+09 |
| July | 0.313526E+09 | 36672184.44 | 0.276854E+09 | 0.865563E+09 | 78876382.16 |
| August | 0.422662E+09 | 0.132315E+09 | 0.290347E+09 | 0.100620E+10 | 0.140834E+09 |
| September | 0.681375E+09 | 0.387486E+09 | 0.293889E+09 | 0.134702E+10 | 0.320467E+09 |
| October | 0.974717E+09 | 0.694593E+09 | 0.280124E+09 | 0.156335E+10 | 0.613030E+09 |
| November | 0.112756E+10 | 0.890705E+09 | 0.236851E+09 | 0.156939E+10 | 0.981334E+09 |
| December | 0.114089E+10 | 0.883700E+09 | 0.257191E+09 | 0.146411E+10 | 0.121228E+10 |
| Annual Sum or Average | 0.878744E+10 | 0.544752E+10 | 0.333992E+10 | 0.141842E+11 | 0.713629E+10 |
| Minimum of Months | 0.297350E+09 | 23875719.06 | 0.236851E+09 | 0.731465E+09 | 78876382.16 |
| Maximum of Months | 0.114089E+10 | 0.890705E+09 | 0.325478E+09 | 0.156939E+10 | 0.121228E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 88363542.88 | 49763851.35 | 38599691.53 | 90950474.73 | 0.206916E+09 |
| February | 90059831.58 | 47868739.55 | 42191092.04 | 0.100249E+09 | 0.169025E+09 |
| March | 0.135875E+09 | 72824222.81 | 63050606.59 | 0.168701E+09 | 0.160314E+09 |
| April | 0.151139E+09 | 81632895.25 | 69506104.79 | 0.227957E+09 | 91581524.64 |
| May | 0.168217E+09 | 90003984.72 | 78213505.00 | 0.291084E+09 | 52942671.26 |
| June | 0.158465E+09 | 85112889.14 | 73351624.10 | 0.317695E+09 | 23207362.35 |
| July | 0.145314E+09 | 72209221.10 | 73104399.47 | 0.295196E+09 | 17604622.69 |
| August | 0.140729E+09 | 71720812.08 | 69008002.58 | 0.271696E+09 | 27762348.34 |
| September | 0.139275E+09 | 77590030.53 | 61684563.74 | 0.247906E+09 | 59508157.85 |
| October | 0.123889E+09 | 72305718.98 | 51583335.65 | 0.183804E+09 | 0.110104E+09 |
| November | 0.100632E+09 | 61274315.14 | 39357906.06 | 0.117913E+09 | 0.181021E+09 |
| December | 83797994.24 | 45521768.27 | 38276225.97 | 81356390.59 | 0.226023E+09 |
| Annual Sum or Average | 0.152576E+10 | 0.827828E+09 | 0.697927E+09 | 0.239451E+10 | 0.132601E+10 |
| Minimum of Months | 83797994.24 | 45521768.27 | 38276225.97 | 81356390.59 | 17604622.69 |
| Maximum of Months | 0.168217E+09 | 90003984.72 | 78213505.00 | 0.317695E+09 | 0.226023E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.265090E+09 | 0.149291E+09 | 0.115799E+09 | 0.290274E+09 | 0.540101E+09 |
| February | 0.270179E+09 | 0.143606E+09 | 0.126573E+09 | 0.319554E+09 | 0.438092E+09 |
| March | 0.407623E+09 | 0.218472E+09 | 0.189151E+09 | 0.529790E+09 | 0.420227E+09 |
| April | 0.453415E+09 | 0.244898E+09 | 0.208518E+09 | 0.699051E+09 | 0.249361E+09 |
| May | 0.504651E+09 | 0.270011E+09 | 0.234640E+09 | 0.879344E+09 | 0.151017E+09 |
| June | 0.475392E+09 | 0.255338E+09 | 0.220054E+09 | 0.948918E+09 | 67297800.41 |
| July | 0.435939E+09 | 0.216627E+09 | 0.219312E+09 | 0.876912E+09 | 55972954.77 |
| August | 0.422185E+09 | 0.215162E+09 | 0.207023E+09 | 0.810319E+09 | 85677268.73 |
| September | 0.417822E+09 | 0.232769E+09 | 0.185053E+09 | 0.746499E+09 | 0.174777E+09 |
| October | 0.371666E+09 | 0.216916E+09 | 0.154749E+09 | 0.561013E+09 | 0.309768E+09 |
| November | 0.301896E+09 | 0.183822E+09 | 0.118073E+09 | 0.367537E+09 | 0.484551E+09 |
| December | 0.251393E+09 | 0.136565E+09 | 0.114828E+09 | 0.258243E+09 | 0.603479E+09 |
| Annual Sum or Average | 0.457725E+10 | 0.248348E+10 | 0.209377E+10 | 0.728745E+10 | 0.358032E+10 |
| Minimum of Months | 0.251393E+09 | 0.136565E+09 | 0.114828E+09 | 0.258243E+09 | 55972954.77 |
| Maximum of Months | 0.504651E+09 | 0.270011E+09 | 0.234640E+09 | 0.948918E+09 | 0.603479E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 11418300.10 | 0.00 | 11418300.10 | 751237.86 | 88358101.31 |
| February | 12647939.24 | 0.00 | 12647939.24 | 4001569.19 | 70060826.62 |
| March | 18703509.15 | 0.00 | 18703509.15 | 10021585.68 | 66320586.97 |
| April | 20786003.27 | 185780.67 | 20600222.60 | 23271515.73 | 36808694.37 |
| May | 26052017.51 | 2256835.94 | 23795181.57 | 45356542.24 | 19563439.06 |
| June | 27397887.43 | 4014504.72 | 23383382.71 | 67349172.89 | 8480986.41 |
| July | 25623362.65 | 2955639.09 | 22667723.56 | 62841673.99 | 7253545.83 |
| August | 20936155.99 | 507829.80 | 20428326.18 | 46617116.79 | 11457601.40 |
| September | 17549423.76 | 6557.20 | 17542866.56 | 31599451.12 | 25067085.10 |
| October | 15113062.76 | 0.00 | 15113062.76 | 13423952.88 | 47714647.31 |
| November | 11767737.30 | 0.00 | 11767737.30 | 1571615.69 | 78966826.33 |
| December | 11255823.61 | 0.00 | 11255823.61 | 579498.00 | 99789121.59 |
| Annual Sum or Average | 0.219251E+09 | 9927147.42 | 0.209324E+09 | 0.307385E+09 | 0.559841E+09 |
| Minimum of Months | 11255823.61 | 0.00 | 11255823.61 | 579498.00 | 7253545.83 |
| Maximum of Months | 27397887.43 | 4014504.72 | 23795181.57 | 67349172.89 | 99789121.59 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 84022512.96 | 0.00 | 84022512.96 | 6986348.33 | 0.610742E+09 |
| February | 92963567.46 | 0.00 | 92963567.46 | 31457027.18 | 0.486167E+09 |
| March | 0.136729E+09 | 0.00 | 0.136729E+09 | 76148949.55 | 0.461451E+09 |
| April | 0.152112E+09 | 1294750.94 | 0.150818E+09 | 0.170110E+09 | 0.258035E+09 |
| May | 0.189540E+09 | 15663093.00 | 0.173877E+09 | 0.325562E+09 | 0.139376E+09 |
| June | 0.198277E+09 | 27861821.78 | 0.170415E+09 | 0.476578E+09 | 61042638.11 |
| July | 0.186287E+09 | 20512988.64 | 0.165774E+09 | 0.447331E+09 | 52117804.66 |
| August | 0.153516E+09 | 3524817.68 | 0.149991E+09 | 0.334364E+09 | 81627818.38 |
| September | 0.129010E+09 | 48859.77 | 0.128961E+09 | 0.229057E+09 | 0.176946E+09 |
| October | 0.110990E+09 | 0.00 | 0.110990E+09 | 0.100731E+09 | 0.332807E+09 |
| November | 86498921.97 | 0.00 | 86498921.97 | 13428925.97 | 0.546689E+09 |
| December | 82973293.34 | 0.00 | 82973293.34 | 5048116.68 | 0.690096E+09 |
| Annual Sum or Average | 0.160292E+10 | 68906331.81 | 0.153401E+10 | 0.221680E+10 | 0.389710E+10 |
| Minimum of Months | 82973293.34 | 0.00 | 82973293.34 | 5048116.68 | 52117804.66 |
| Maximum of Months | 0.198277E+09 | 27861821.78 | 0.173877E+09 | 0.476578E+09 | 0.690096E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.137262E+09 | 0.00 | 0.137262E+09 | 4831471.65 | 0.120399E+10 |
| February | 0.152252E+09 | 0.00 | 0.152252E+09 | 39632830.76 | 0.956880E+09 |
| March | 0.226008E+09 | 0.00 | 0.226008E+09 | 0.107069E+09 | 0.901742E+09 |
| April | 0.248718E+09 | 1282289.66 | 0.247436E+09 | 0.285591E+09 | 0.489733E+09 |
| May | 0.303383E+09 | 19903946.34 | 0.283479E+09 | 0.556790E+09 | 0.254332E+09 |
| June | 0.317390E+09 | 38523825.97 | 0.278866E+09 | 0.833533E+09 | 0.102088E+09 |
| July | 0.294611E+09 | 26088360.36 | 0.268523E+09 | 0.801347E+09 | 77247024.33 |
| August | 0.247566E+09 | 3897042.40 | 0.243669E+09 | 0.621482E+09 | 0.128417E+09 |
| September | 0.211617E+09 | 54149.56 | 0.211563E+09 | 0.409590E+09 | 0.300495E+09 |
| October | 0.182151E+09 | 0.00 | 0.182151E+09 | 0.166783E+09 | 0.607730E+09 |
| November | 0.141796E+09 | 0.00 | 0.141796E+09 | 15655972.65 | 0.105025E+10 |
| December | 0.135010E+09 | 0.00 | 0.135010E+09 | 3675424.53 | 0.134521E+10 |
| Annual Sum or Average | 0.259777E+10 | 89749614.30 | 0.250802E+10 | 0.384598E+10 | 0.741811E+10 |
| Minimum of Months | 0.135010E+09 | 0.00 | 0.135010E+09 | 3675424.53 | 77247024.33 |
| Maximum of Months | 0.317390E+09 | 38523825.97 | 0.283479E+09 | 0.833533E+09 | 0.134521E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.145008E+09 | 0.00 | 0.145008E+09 | 6319063.15 | 0.120607E+10 |
| February | 0.160637E+09 | 0.00 | 0.160637E+09 | 43371577.93 | 0.960886E+09 |
| March | 0.237641E+09 | 0.00 | 0.237641E+09 | 0.115764E+09 | 0.906971E+09 |
| April | 0.263424E+09 | 2126583.27 | 0.261298E+09 | 0.296426E+09 | 0.491325E+09 |
| May | 0.327294E+09 | 26180382.90 | 0.301114E+09 | 0.582946E+09 | 0.251495E+09 |
| June | 0.343835E+09 | 48046224.31 | 0.295789E+09 | 0.872535E+09 | 0.104032E+09 |
| July | 0.321087E+09 | 34586478.78 | 0.286501E+09 | 0.843751E+09 | 78944859.86 |
| August | 0.264921E+09 | 5984074.57 | 0.258936E+09 | 0.642936E+09 | 0.130030E+09 |
| September | 0.222770E+09 | 65938.23 | 0.222704E+09 | 0.421043E+09 | 0.307207E+09 |
| October | 0.191957E+09 | 0.00 | 0.191957E+09 | 0.175495E+09 | 0.613667E+09 |
| November | 0.149457E+09 | 0.00 | 0.149457E+09 | 17700378.11 | 0.105426E+10 |
| December | 0.142926E+09 | 0.00 | 0.142926E+09 | 4855997.26 | 0.134893E+10 |
| Annual Sum or Average | 0.277096E+10 | 0.116990E+09 | 0.265397E+10 | 0.402314E+10 | 0.745383E+10 |
| Minimum of Months | 0.142926E+09 | 0.00 | 0.142926E+09 | 4855997.26 | 78944859.86 |
| Maximum of Months | 0.343835E+09 | 48046224.31 | 0.301114E+09 | 0.872535E+09 | 0.134893E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.145005E+09 | 0.00 | 0.145005E+09 | 6318936.45 | 0.120605E+10 |
| February | 0.160634E+09 | 0.00 | 0.160634E+09 | 43370726.06 | 0.960868E+09 |
| March | 0.237637E+09 | 0.00 | 0.237637E+09 | 0.115762E+09 | 0.906954E+09 |
| April | 0.264061E+09 | 2363051.84 | 0.261698E+09 | 0.296420E+09 | 0.489812E+09 |
| May | 0.330734E+09 | 28511557.89 | 0.302222E+09 | 0.589171E+09 | 0.250543E+09 |
| June | 0.346526E+09 | 49916456.45 | 0.296610E+09 | 0.877825E+09 | 0.104014E+09 |
| July | 0.324445E+09 | 36836898.98 | 0.287608E+09 | 0.850249E+09 | 78699326.42 |
| August | 0.265987E+09 | 6497983.76 | 0.259489E+09 | 0.644377E+09 | 0.129167E+09 |
| September | 0.222865E+09 | 79543.60 | 0.222785E+09 | 0.421035E+09 | 0.306985E+09 |
| October | 0.191954E+09 | 0.00 | 0.191954E+09 | 0.175491E+09 | 0.613655E+09 |
| November | 0.149454E+09 | 0.00 | 0.149454E+09 | 17700028.01 | 0.105424E+10 |
| December | 0.142923E+09 | 0.00 | 0.142923E+09 | 4855900.17 | 0.134891E+10 |
| Annual Sum or Average | 0.278222E+10 | 0.124205E+09 | 0.265802E+10 | 0.404258E+10 | 0.744990E+10 |
| Minimum of Months | 0.142923E+09 | 0.00 | 0.142923E+09 | 4855900.17 | 78699326.42 |
| Maximum of Months | 0.346526E+09 | 49916456.45 | 0.302222E+09 | 0.877825E+09 | 0.134891E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.265090E+09 | 0.149291E+09 | 0.115799E+09 | 0.264098E+09 | 0.606980E+09 |
| February | 0.270179E+09 | 0.143606E+09 | 0.126573E+09 | 0.293720E+09 | 0.487829E+09 |
| March | 0.407623E+09 | 0.218472E+09 | 0.189151E+09 | 0.507054E+09 | 0.451992E+09 |
| April | 0.453415E+09 | 0.244898E+09 | 0.208518E+09 | 0.686750E+09 | 0.261276E+09 |
| May | 0.504651E+09 | 0.270011E+09 | 0.234640E+09 | 0.876417E+09 | 0.152900E+09 |
| June | 0.475392E+09 | 0.255338E+09 | 0.220054E+09 | 0.949756E+09 | 66987922.49 |
| July | 0.435939E+09 | 0.216627E+09 | 0.219312E+09 | 0.875672E+09 | 56513633.91 |
| August | 0.422185E+09 | 0.215162E+09 | 0.207023E+09 | 0.800901E+09 | 90791812.29 |
| September | 0.417822E+09 | 0.232769E+09 | 0.185053E+09 | 0.732755E+09 | 0.186486E+09 |
| October | 0.371666E+09 | 0.216916E+09 | 0.154749E+09 | 0.541666E+09 | 0.334956E+09 |
| November | 0.301896E+09 | 0.183822E+09 | 0.118073E+09 | 0.346250E+09 | 0.537625E+09 |
| December | 0.251393E+09 | 0.136565E+09 | 0.114828E+09 | 0.233490E+09 | 0.668879E+09 |
| Annual Sum or Average | 0.457725E+10 | 0.248348E+10 | 0.209377E+10 | 0.710853E+10 | 0.390322E+10 |
| Minimum of Months | 0.251393E+09 | 0.136565E+09 | 0.114828E+09 | 0.233490E+09 | 56513633.91 |
| Maximum of Months | 0.504651E+09 | 0.270011E+09 | 0.234640E+09 | 0.949756E+09 | 0.668879E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 97166928.60 | 75014472.18 | 22152456.42 | 0.129539E+09 | 82006561.58 |
| February | 80865371.60 | 58411802.06 | 22453569.54 | 0.110153E+09 | 66678320.02 |
| March | 72009349.65 | 43060574.16 | 28948775.49 | 0.100607E+09 | 65308267.67 |
| April | 45980676.16 | 18285633.56 | 27695042.61 | 74446753.89 | 39536813.29 |
| May | 32415936.25 | 5008994.72 | 27406941.53 | 60909555.75 | 22427878.83 |
| June | 26741249.03 | 1895839.00 | 24845410.03 | 66128240.05 | 9364211.94 |
| July | 28210060.12 | 2917671.20 | 25292388.92 | 68645987.73 | 8060808.71 |
| August | 36951393.02 | 10620101.47 | 26331291.55 | 80761251.48 | 13173895.83 |
| September | 57822308.32 | 31483657.22 | 26338651.10 | 0.110658E+09 | 27095483.36 |
| October | 82638856.86 | 57454025.52 | 25184831.34 | 0.131279E+09 | 47949812.75 |
| November | 96736763.89 | 75206752.08 | 21530011.82 | 0.135143E+09 | 73094070.40 |
| December | 99009248.09 | 75686123.95 | 23323124.14 | 0.129095E+09 | 89414915.94 |
| Annual Sum or Average | 0.756548E+09 | 0.455046E+09 | 0.301502E+09 | 0.119737E+10 | 0.544111E+09 |
| Minimum of Months | 26741249.03 | 1895839.00 | 21530011.82 | 60909555.75 | 8060808.71 |
| Maximum of Months | 99009248.09 | 75686123.95 | 28948775.49 | 0.135143E+09 | 89414915.94 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.668427E+09 | 0.520622E+09 | 0.147805E+09 | 0.891586E+09 | 0.564378E+09 |
| February | 0.554784E+09 | 0.405395E+09 | 0.149389E+09 | 0.756509E+09 | 0.458079E+09 |
| March | 0.491152E+09 | 0.298850E+09 | 0.192302E+09 | 0.687547E+09 | 0.448421E+09 |
| April | 0.309373E+09 | 0.126908E+09 | 0.182465E+09 | 0.505133E+09 | 0.270310E+09 |
| May | 0.214119E+09 | 34763869.54 | 0.179355E+09 | 0.408609E+09 | 0.151661E+09 |
| June | 0.175485E+09 | 13157670.04 | 0.162328E+09 | 0.445765E+09 | 62424293.06 |
| July | 0.185274E+09 | 20249480.49 | 0.165025E+09 | 0.461292E+09 | 53848233.38 |
| August | 0.246247E+09 | 73706570.36 | 0.172540E+09 | 0.546895E+09 | 88782714.16 |
| September | 0.392353E+09 | 0.218504E+09 | 0.173848E+09 | 0.756204E+09 | 0.184089E+09 |
| October | 0.565950E+09 | 0.398747E+09 | 0.167204E+09 | 0.901131E+09 | 0.328366E+09 |
| November | 0.665378E+09 | 0.521957E+09 | 0.143422E+09 | 0.930843E+09 | 0.502364E+09 |
| December | 0.681116E+09 | 0.525284E+09 | 0.155832E+09 | 0.888701E+09 | 0.614971E+09 |
| Annual Sum or Average | 0.514966E+10 | 0.315814E+10 | 0.199151E+10 | 0.818021E+10 | 0.372769E+10 |
| Minimum of Months | 0.175485E+09 | 13157670.04 | 0.143422E+09 | 0.408609E+09 | 53848233.38 |
| Maximum of Months | 0.681116E+09 | 0.525284E+09 | 0.192302E+09 | 0.930843E+09 | 0.614971E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.121822E+10 | 0.952746E+09 | 0.265474E+09 | 0.160916E+10 | 0.111382E+10 |
| February | 0.101386E+10 | 0.745025E+09 | 0.268831E+09 | 0.136506E+10 | 0.902697E+09 |
| March | 0.894906E+09 | 0.549169E+09 | 0.345738E+09 | 0.123804E+10 | 0.878730E+09 |
| April | 0.559885E+09 | 0.233212E+09 | 0.326674E+09 | 0.918522E+09 | 0.516247E+09 |
| May | 0.383857E+09 | 63883839.16 | 0.319973E+09 | 0.751751E+09 | 0.278992E+09 |
| June | 0.313527E+09 | 24179197.76 | 0.289348E+09 | 0.830698E+09 | 0.109461E+09 |
| July | 0.331157E+09 | 37211466.14 | 0.293946E+09 | 0.882541E+09 | 84673453.86 |
| August | 0.443474E+09 | 0.135447E+09 | 0.308027E+09 | 0.103136E+10 | 0.148319E+09 |
| September | 0.713059E+09 | 0.401519E+09 | 0.311540E+09 | 0.139765E+10 | 0.328480E+09 |
| October | 0.103310E+10 | 0.732601E+09 | 0.300499E+09 | 0.165464E+10 | 0.613425E+09 |
| November | 0.121590E+10 | 0.957968E+09 | 0.257932E+09 | 0.169475E+10 | 0.967364E+09 |
| December | 0.123734E+10 | 0.957535E+09 | 0.279809E+09 | 0.159718E+10 | 0.120398E+10 |
| Annual Sum or Average | 0.935829E+10 | 0.579050E+10 | 0.356779E+10 | 0.149713E+11 | 0.714619E+10 |
| Minimum of Months | 0.313527E+09 | 24179197.76 | 0.257932E+09 | 0.751751E+09 | 84673453.86 |
| Maximum of Months | 0.123734E+10 | 0.957968E+09 | 0.345738E+09 | 0.169475E+10 | 0.120398E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.121323E+10 | 0.948674E+09 | 0.264559E+09 | 0.160748E+10 | 0.112176E+10 |
| February | 0.101192E+10 | 0.743552E+09 | 0.268365E+09 | 0.136447E+10 | 0.906340E+09 |
| March | 0.894581E+09 | 0.548995E+09 | 0.345585E+09 | 0.123796E+10 | 0.879305E+09 |
| April | 0.559848E+09 | 0.233196E+09 | 0.326652E+09 | 0.918461E+09 | 0.516213E+09 |
| May | 0.383831E+09 | 63879651.68 | 0.319952E+09 | 0.751701E+09 | 0.278974E+09 |
| June | 0.313506E+09 | 24177612.86 | 0.289329E+09 | 0.830643E+09 | 0.109453E+09 |
| July | 0.331135E+09 | 37209026.99 | 0.293926E+09 | 0.882483E+09 | 84667823.71 |
| August | 0.443444E+09 | 0.135438E+09 | 0.308006E+09 | 0.103129E+10 | 0.148310E+09 |
| September | 0.712947E+09 | 0.401444E+09 | 0.311502E+09 | 0.139756E+10 | 0.328631E+09 |
| October | 0.103200E+10 | 0.731756E+09 | 0.300242E+09 | 0.165361E+10 | 0.614647E+09 |
| November | 0.121074E+10 | 0.953748E+09 | 0.256991E+09 | 0.169267E+10 | 0.975840E+09 |
| December | 0.123160E+10 | 0.952595E+09 | 0.279008E+09 | 0.159568E+10 | 0.121335E+10 |
| Annual Sum or Average | 0.933878E+10 | 0.577467E+10 | 0.356412E+10 | 0.149640E+11 | 0.717749E+10 |
| Minimum of Months | 0.313506E+09 | 24177612.86 | 0.256991E+09 | 0.751701E+09 | 84667823.71 |
| Maximum of Months | 0.123160E+10 | 0.953748E+09 | 0.345585E+09 | 0.169267E+10 | 0.121335E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.113492E+10 | 0.887233E+09 | 0.247691E+09 | 0.148898E+10 | 0.112853E+10 |
| February | 0.948601E+09 | 0.696971E+09 | 0.251630E+09 | 0.127110E+10 | 0.917380E+09 |
| March | 0.853757E+09 | 0.525455E+09 | 0.328302E+09 | 0.117705E+10 | 0.882270E+09 |
| April | 0.539213E+09 | 0.227280E+09 | 0.311934E+09 | 0.888421E+09 | 0.509232E+09 |
| May | 0.368476E+09 | 62827621.53 | 0.305648E+09 | 0.734110E+09 | 0.271339E+09 |
| June | 0.300665E+09 | 23874345.28 | 0.276791E+09 | 0.819599E+09 | 0.104997E+09 |
| July | 0.316974E+09 | 36670094.56 | 0.280304E+09 | 0.865850E+09 | 81227863.81 |
| August | 0.426004E+09 | 0.132308E+09 | 0.293696E+09 | 0.100660E+10 | 0.143937E+09 |
| September | 0.684309E+09 | 0.387478E+09 | 0.296831E+09 | 0.134928E+10 | 0.323735E+09 |
| October | 0.977401E+09 | 0.694745E+09 | 0.282656E+09 | 0.156572E+10 | 0.616590E+09 |
| November | 0.113078E+10 | 0.891708E+09 | 0.239075E+09 | 0.157194E+10 | 0.985801E+09 |
| December | 0.114654E+10 | 0.886824E+09 | 0.259712E+09 | 0.146706E+10 | 0.121923E+10 |
| Annual Sum or Average | 0.882764E+10 | 0.545337E+10 | 0.337427E+10 | 0.142057E+11 | 0.718426E+10 |
| Minimum of Months | 0.300665E+09 | 23874345.28 | 0.239075E+09 | 0.734110E+09 | 81227863.81 |
| Maximum of Months | 0.114654E+10 | 0.891708E+09 | 0.328302E+09 | 0.157194E+10 | 0.121923E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 88363542.88 | 49763851.35 | 38599691.53 | 90382704.18 | 0.209479E+09 |
| February | 90059831.58 | 47868739.55 | 42191092.04 | 99617462.33 | 0.171143E+09 |
| March | 0.135875E+09 | 72824222.81 | 63050606.59 | 0.168058E+09 | 0.161961E+09 |
| April | 0.151139E+09 | 81632895.25 | 69506104.79 | 0.227515E+09 | 92364301.76 |
| May | 0.168217E+09 | 90003984.72 | 78213505.00 | 0.290669E+09 | 53426587.92 |
| June | 0.158465E+09 | 85112889.14 | 73351624.10 | 0.317224E+09 | 23520948.68 |
| July | 0.145314E+09 | 72209221.10 | 73104399.47 | 0.294138E+09 | 18248440.65 |
| August | 0.140729E+09 | 71720812.08 | 69008002.58 | 0.270672E+09 | 28592404.97 |
| September | 0.139275E+09 | 77590030.53 | 61684563.74 | 0.247458E+09 | 60158771.06 |
| October | 0.123889E+09 | 72305718.98 | 51583335.65 | 0.183482E+09 | 0.110886E+09 |
| November | 0.100632E+09 | 61274315.14 | 39357906.06 | 0.117564E+09 | 0.182621E+09 |
| December | 83797994.24 | 45521768.27 | 38276225.97 | 80724783.53 | 0.228910E+09 |
| Annual Sum or Average | 0.152576E+10 | 0.827828E+09 | 0.697927E+09 | 0.238750E+10 | 0.134131E+10 |
| Minimum of Months | 83797994.24 | 45521768.27 | 38276225.97 | 80724783.53 | 18248440.65 |
| Maximum of Months | 0.168217E+09 | 90003984.72 | 78213505.00 | 0.317224E+09 | 0.228910E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 14482884.09 | 0.00 | 14482884.09 | 2047952.77 | 88718411.27 |
| February | 15973670.98 | 0.00 | 15973670.98 | 6179596.72 | 71041913.70 |
| March | 23144140.07 | 0.00 | 23144140.07 | 14033939.06 | 67767574.18 |
| April | 25860488.05 | 203741.47 | 25656746.57 | 28702539.17 | 38617741.61 |
| May | 31693841.59 | 2291889.01 | 29401952.58 | 52217880.03 | 21908807.57 |
| June | 32613846.95 | 4015114.69 | 28598732.26 | 73150012.02 | 9939498.88 |
| July | 31146233.07 | 3031824.79 | 28114408.28 | 69838681.37 | 8442716.07 |
| August | 26263071.78 | 537007.40 | 25726064.37 | 53269586.12 | 12892659.01 |
| September | 22177650.00 | 8849.60 | 22168800.40 | 37398786.41 | 27092039.41 |
| October | 19027355.68 | 0.00 | 19027355.68 | 17644693.27 | 49302058.97 |
| November | 14865181.93 | 0.00 | 14865181.93 | 3057373.64 | 79611391.59 |
| December | 14370720.82 | 0.00 | 14370720.82 | 1285042.43 | 0.100161E+09 |
| Annual Sum or Average | 0.271619E+09 | 10088426.97 | 0.261531E+09 | 0.358826E+09 | 0.575496E+09 |
| Minimum of Months | 14370720.82 | 0.00 | 14370720.82 | 1285042.43 | 8442716.07 |
| Maximum of Months | 32613846.95 | 4015114.69 | 29401952.58 | 73150012.02 | 0.100161E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.265090E+09 | 0.149291E+09 | 0.115799E+09 | 0.289479E+09 | 0.541637E+09 |
| February | 0.270179E+09 | 0.143606E+09 | 0.126573E+09 | 0.318645E+09 | 0.439350E+09 |
| March | 0.407623E+09 | 0.218472E+09 | 0.189151E+09 | 0.528662E+09 | 0.421304E+09 |
| April | 0.453415E+09 | 0.244898E+09 | 0.208518E+09 | 0.698188E+09 | 0.249703E+09 |
| May | 0.504651E+09 | 0.270011E+09 | 0.234640E+09 | 0.878491E+09 | 0.151168E+09 |
| June | 0.475392E+09 | 0.255338E+09 | 0.220054E+09 | 0.948155E+09 | 67422102.80 |
| July | 0.435939E+09 | 0.216627E+09 | 0.219312E+09 | 0.874865E+09 | 56729731.44 |
| August | 0.422185E+09 | 0.215162E+09 | 0.207023E+09 | 0.808375E+09 | 86577037.00 |
| September | 0.417822E+09 | 0.232769E+09 | 0.185053E+09 | 0.745647E+09 | 0.175188E+09 |
| October | 0.371666E+09 | 0.216916E+09 | 0.154749E+09 | 0.560450E+09 | 0.310046E+09 |
| November | 0.301896E+09 | 0.183822E+09 | 0.118073E+09 | 0.367062E+09 | 0.485082E+09 |
| December | 0.251393E+09 | 0.136565E+09 | 0.114828E+09 | 0.257445E+09 | 0.605236E+09 |
| Annual Sum or Average | 0.457725E+10 | 0.248348E+10 | 0.209377E+10 | 0.727546E+10 | 0.358944E+10 |
| Minimum of Months | 0.251393E+09 | 0.136565E+09 | 0.114828E+09 | 0.257445E+09 | 56729731.44 |
| Maximum of Months | 0.504651E+09 | 0.270011E+09 | 0.234640E+09 | 0.948155E+09 | 0.605236E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.100115E+09 | 0.00 | 0.100115E+09 | 14426163.69 | 0.611331E+09 |
| February | 0.110421E+09 | 0.00 | 0.110421E+09 | 43221431.55 | 0.490250E+09 |
| March | 0.159988E+09 | 0.00 | 0.159988E+09 | 97504281.99 | 0.468071E+09 |
| April | 0.178765E+09 | 1408393.01 | 0.177356E+09 | 0.198625E+09 | 0.266949E+09 |
| May | 0.219089E+09 | 15843021.18 | 0.203246E+09 | 0.360997E+09 | 0.151448E+09 |
| June | 0.225448E+09 | 27755073.08 | 0.197693E+09 | 0.505667E+09 | 68708369.15 |
| July | 0.215303E+09 | 20957936.47 | 0.194345E+09 | 0.482787E+09 | 58361627.01 |
| August | 0.181548E+09 | 3712142.95 | 0.177836E+09 | 0.368346E+09 | 89122626.60 |
| September | 0.153307E+09 | 61174.19 | 0.153245E+09 | 0.259111E+09 | 0.187276E+09 |
| October | 0.131530E+09 | 0.00 | 0.131530E+09 | 0.123071E+09 | 0.340327E+09 |
| November | 0.102758E+09 | 0.00 | 0.102758E+09 | 21686920.24 | 0.548588E+09 |
| December | 99339912.89 | 0.00 | 99339912.89 | 9012791.50 | 0.690182E+09 |
| Annual Sum or Average | 0.187761E+10 | 69737740.88 | 0.180787E+10 | 0.248446E+10 | 0.397061E+10 |
| Minimum of Months | 99339912.89 | 0.00 | 99339912.89 | 9012791.50 | 58361627.01 |
| Maximum of Months | 0.225448E+09 | 27755073.08 | 0.203246E+09 | 0.505667E+09 | 0.690182E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.121970E+09 | 0.00 | 0.121970E+09 | 12766117.13 | 0.797817E+09 |
| February | 0.134525E+09 | 0.00 | 0.134525E+09 | 45455309.79 | 0.641579E+09 |
| March | 0.194913E+09 | 0.00 | 0.194913E+09 | 0.109206E+09 | 0.609556E+09 |
| April | 0.217789E+09 | 1715844.59 | 0.216073E+09 | 0.241179E+09 | 0.338110E+09 |
| May | 0.266916E+09 | 19301545.86 | 0.247614E+09 | 0.446752E+09 | 0.185077E+09 |
| June | 0.274664E+09 | 33813993.55 | 0.240850E+09 | 0.630015E+09 | 80918581.72 |
| July | 0.262304E+09 | 25533044.95 | 0.236771E+09 | 0.618307E+09 | 62278802.83 |
| August | 0.221180E+09 | 4522502.16 | 0.216657E+09 | 0.478451E+09 | 97699134.46 |
| September | 0.186773E+09 | 74528.49 | 0.186699E+09 | 0.326432E+09 | 0.220135E+09 |
| October | 0.160243E+09 | 0.00 | 0.160243E+09 | 0.151547E+09 | 0.418972E+09 |
| November | 0.125190E+09 | 0.00 | 0.125190E+09 | 23234655.20 | 0.700683E+09 |
| December | 0.121026E+09 | 0.00 | 0.121026E+09 | 8152082.19 | 0.894531E+09 |
| Annual Sum or Average | 0.228749E+10 | 84961459.60 | 0.220253E+10 | 0.309150E+10 | 0.504736E+10 |
| Minimum of Months | 0.121026E+09 | 0.00 | 0.121026E+09 | 8152082.19 | 62278802.83 |
| Maximum of Months | 0.274664E+09 | 33813993.55 | 0.247614E+09 | 0.630015E+09 | 0.894531E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.121970E+09 | 0.00 | 0.121970E+09 | 12765837.13 | 0.797817E+09 |
| February | 0.134525E+09 | 0.00 | 0.134525E+09 | 45454947.68 | 0.641578E+09 |
| March | 0.194912E+09 | 0.00 | 0.194912E+09 | 0.109205E+09 | 0.609555E+09 |
| April | 0.217788E+09 | 1715828.73 | 0.216072E+09 | 0.241178E+09 | 0.338109E+09 |
| May | 0.266914E+09 | 19301367.49 | 0.247613E+09 | 0.446751E+09 | 0.185076E+09 |
| June | 0.274662E+09 | 33813681.06 | 0.240849E+09 | 0.630013E+09 | 80918109.14 |
| July | 0.262303E+09 | 25532808.98 | 0.236770E+09 | 0.618305E+09 | 62278435.86 |
| August | 0.221178E+09 | 4522460.36 | 0.216656E+09 | 0.478450E+09 | 97698704.81 |
| September | 0.186773E+09 | 74527.81 | 0.186698E+09 | 0.326431E+09 | 0.220134E+09 |
| October | 0.160242E+09 | 0.00 | 0.160242E+09 | 0.151546E+09 | 0.418972E+09 |
| November | 0.125189E+09 | 0.00 | 0.125189E+09 | 23234457.68 | 0.700683E+09 |
| December | 0.121025E+09 | 0.00 | 0.121025E+09 | 8151913.00 | 0.894531E+09 |
| Annual Sum or Average | 0.228748E+10 | 84960674.43 | 0.220252E+10 | 0.309149E+10 | 0.504735E+10 |
| Minimum of Months | 0.121025E+09 | 0.00 | 0.121025E+09 | 8151913.00 | 62278435.86 |
| Maximum of Months | 0.274662E+09 | 33813681.06 | 0.247613E+09 | 0.630013E+09 | 0.894531E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.121966E+09 | 0.00 | 0.121966E+09 | 12765583.65 | 0.797791E+09 |
| February | 0.134521E+09 | 0.00 | 0.134521E+09 | 45453651.51 | 0.641557E+09 |
| March | 0.194906E+09 | 0.00 | 0.194906E+09 | 0.109202E+09 | 0.609535E+09 |
| April | 0.217781E+09 | 1715781.16 | 0.216066E+09 | 0.241171E+09 | 0.338098E+09 |
| May | 0.266906E+09 | 19300832.36 | 0.247606E+09 | 0.446737E+09 | 0.185070E+09 |
| June | 0.274654E+09 | 33812743.58 | 0.240841E+09 | 0.629993E+09 | 80915695.05 |
| July | 0.262295E+09 | 25532101.09 | 0.236763E+09 | 0.618286E+09 | 62276579.87 |
| August | 0.221172E+09 | 4522334.98 | 0.216649E+09 | 0.478435E+09 | 97695702.72 |
| September | 0.186767E+09 | 74525.74 | 0.186692E+09 | 0.326421E+09 | 0.220127E+09 |
| October | 0.160237E+09 | 0.00 | 0.160237E+09 | 0.151542E+09 | 0.418958E+09 |
| November | 0.125186E+09 | 0.00 | 0.125186E+09 | 23233802.84 | 0.700660E+09 |
| December | 0.121021E+09 | 0.00 | 0.121021E+09 | 8151745.18 | 0.894501E+09 |
| Annual Sum or Average | 0.228741E+10 | 84958318.90 | 0.220245E+10 | 0.309139E+10 | 0.504719E+10 |
| Minimum of Months | 0.121021E+09 | 0.00 | 0.121021E+09 | 8151745.18 | 62276579.87 |
| Maximum of Months | 0.274654E+09 | 33812743.58 | 0.247606E+09 | 0.629993E+09 | 0.894501E+09 |
Report: WindowEnergyReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13753981.53 | 0.00 | 13753981.53 | 1000964.64 | 96656993.58 |
| February | 15169736.12 | 0.00 | 15169736.12 | 4386334.48 | 77953366.45 |
| March | 21979320.23 | 0.00 | 21979320.23 | 11288045.44 | 73758047.42 |
| April | 24558945.12 | 193488.95 | 24365456.17 | 26343559.66 | 40610040.63 |
| May | 30098730.94 | 2176558.33 | 27922172.60 | 49642337.65 | 22128850.10 |
| June | 30972436.76 | 3813069.17 | 27159367.59 | 70336527.71 | 9916411.07 |
| July | 29578698.88 | 2879259.63 | 26699439.25 | 67368517.20 | 8190519.74 |
| August | 24941278.31 | 509984.53 | 24431293.78 | 51362602.33 | 12718547.64 |
| September | 21061459.37 | 8404.28 | 21053055.09 | 36115358.49 | 26420705.93 |
| October | 18069728.62 | 0.00 | 18069728.62 | 16524779.55 | 49703909.06 |
| November | 14117031.58 | 0.00 | 14117031.58 | 2216464.75 | 84127165.16 |
| December | 13647467.97 | 0.00 | 13647467.97 | 637969.97 | 0.107666E+09 |
| Annual Sum or Average | 0.257949E+09 | 9580764.90 | 0.248368E+09 | 0.337223E+09 | 0.609851E+09 |
| Minimum of Months | 13647467.97 | 0.00 | 13647467.97 | 637969.97 | 8190519.74 |
| Maximum of Months | 30972436.76 | 3813069.17 | 27922172.60 | 70336527.71 | 0.107666E+09 |
Report: WindowEnergyReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.174425E+09 | 0.00 | 0.174425E+09 | 12693991.91 | 0.122578E+10 |
| February | 0.192379E+09 | 0.00 | 0.192379E+09 | 55626434.73 | 0.988586E+09 |
| March | 0.278736E+09 | 0.00 | 0.278736E+09 | 0.143152E+09 | 0.935382E+09 |
| April | 0.311451E+09 | 2453780.14 | 0.308997E+09 | 0.334083E+09 | 0.515007E+09 |
| May | 0.381705E+09 | 27602587.23 | 0.354102E+09 | 0.629552E+09 | 0.280633E+09 |
| June | 0.392785E+09 | 48356422.50 | 0.344429E+09 | 0.891991E+09 | 0.125758E+09 |
| July | 0.375110E+09 | 36514075.38 | 0.338596E+09 | 0.854351E+09 | 0.103870E+09 |
| August | 0.316299E+09 | 6467500.64 | 0.309832E+09 | 0.651368E+09 | 0.161294E+09 |
| September | 0.267096E+09 | 106581.06 | 0.266990E+09 | 0.458006E+09 | 0.335061E+09 |
| October | 0.229156E+09 | 0.00 | 0.229156E+09 | 0.209563E+09 | 0.630333E+09 |
| November | 0.179029E+09 | 0.00 | 0.179029E+09 | 28108670.69 | 0.106688E+10 |
| December | 0.173074E+09 | 0.00 | 0.173074E+09 | 8090581.06 | 0.136540E+10 |
| Annual Sum or Average | 0.327124E+10 | 0.121501E+09 | 0.314974E+10 | 0.427659E+10 | 0.773398E+10 |
| Minimum of Months | 0.173074E+09 | 0.00 | 0.173074E+09 | 8090581.06 | 0.103870E+09 |
| Maximum of Months | 0.392785E+09 | 48356422.50 | 0.354102E+09 | 0.891991E+09 | 0.136540E+10 |
Report: WindowEnergyReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 34885498.41 | 21278847.05 | 13606651.36 | 38620109.00 | 93914734.97 |
| February | 37208988.58 | 21983219.56 | 15225769.01 | 44263245.44 | 76920720.52 |
| March | 58014483.93 | 34619240.20 | 23395243.73 | 74820661.97 | 74813328.69 |
| April | 59653916.09 | 34478744.73 | 25175171.36 | 92748951.30 | 42360084.62 |
| May | 56461828.68 | 29554948.65 | 26906880.03 | 0.101857E+09 | 23640028.71 |
| June | 51106833.85 | 25895349.97 | 25211483.88 | 0.112218E+09 | 10322281.21 |
| July | 47605307.60 | 22757343.68 | 24847963.92 | 0.103783E+09 | 8535101.10 |
| August | 53812509.63 | 29261566.92 | 24550942.71 | 0.108510E+09 | 12785098.13 |
| September | 58657684.82 | 35823728.85 | 22833955.97 | 0.108005E+09 | 25951532.85 |
| October | 52730750.88 | 33805154.22 | 18925596.65 | 81404972.76 | 48953797.11 |
| November | 41106117.56 | 27000379.29 | 14105738.28 | 51469850.27 | 82474175.68 |
| December | 31755753.13 | 18429471.67 | 13326281.45 | 33274932.36 | 0.101170E+09 |
| Annual Sum or Average | 0.583000E+09 | 0.334888E+09 | 0.248112E+09 | 0.950976E+09 | 0.601841E+09 |
| Minimum of Months | 31755753.13 | 18429471.67 | 13326281.45 | 33274932.36 | 8535101.10 |
| Maximum of Months | 59653916.09 | 35823728.85 | 26906880.03 | 0.112218E+09 | 0.101170E+09 |
Report: WindowEnergyReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.111847E+09 | 45049848.54 | 66796673.70 | 74208462.68 | 0.511205E+09 |
| February | 0.143284E+09 | 66216613.39 | 77067870.37 | 0.135345E+09 | 0.418015E+09 |
| March | 0.263976E+09 | 0.141102E+09 | 0.122874E+09 | 0.312293E+09 | 0.404067E+09 |
| April | 0.330422E+09 | 0.189438E+09 | 0.140984E+09 | 0.503607E+09 | 0.230430E+09 |
| May | 0.372788E+09 | 0.213459E+09 | 0.159328E+09 | 0.656188E+09 | 0.132578E+09 |
| June | 0.354380E+09 | 0.203893E+09 | 0.150488E+09 | 0.729322E+09 | 59402249.98 |
| July | 0.316989E+09 | 0.169618E+09 | 0.147372E+09 | 0.653976E+09 | 48354941.41 |
| August | 0.310229E+09 | 0.170923E+09 | 0.139306E+09 | 0.608464E+09 | 71844410.92 |
| September | 0.289733E+09 | 0.167111E+09 | 0.122621E+09 | 0.525802E+09 | 0.144356E+09 |
| October | 0.212438E+09 | 0.116339E+09 | 96099066.72 | 0.304994E+09 | 0.266760E+09 |
| November | 0.137065E+09 | 67478508.77 | 69586187.02 | 0.125967E+09 | 0.449543E+09 |
| December | 99943232.27 | 34922727.09 | 65020505.18 | 53669038.43 | 0.552691E+09 |
| Annual Sum or Average | 0.294309E+10 | 0.158555E+10 | 0.135754E+10 | 0.468384E+10 | 0.328925E+10 |
| Minimum of Months | 99943232.27 | 34922727.09 | 65020505.18 | 53669038.43 | 48354941.41 |
| Maximum of Months | 0.372788E+09 | 0.213459E+09 | 0.159328E+09 | 0.729322E+09 | 0.552691E+09 |
Report: WindowEnergyReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 93702574.52 | 70989484.00 | 22713090.52 | 0.129148E+09 | 75641134.39 |
| February | 78508016.82 | 55346934.70 | 23161082.12 | 0.110208E+09 | 61944666.65 |
| March | 70640199.08 | 40730936.60 | 29909262.48 | 0.101311E+09 | 61417194.37 |
| April | 46348822.17 | 17293912.52 | 29054909.65 | 74334932.48 | 38571083.87 |
| May | 33846007.50 | 4737331.98 | 29108675.52 | 60388160.71 | 23726749.08 |
| June | 28258627.63 | 1793018.21 | 26465609.42 | 62947700.06 | 11423773.24 |
| July | 29766777.97 | 2759431.35 | 27007346.62 | 66356994.35 | 9751396.96 |
| August | 37944434.45 | 10044120.44 | 27900314.00 | 78921435.59 | 14373938.60 |
| September | 57316413.08 | 29777867.27 | 27538545.81 | 0.107438E+09 | 27674192.39 |
| October | 80472021.19 | 54404458.06 | 26067563.14 | 0.128148E+09 | 45591654.30 |
| November | 93716813.31 | 71447563.38 | 22269249.93 | 0.133067E+09 | 68036877.07 |
| December | 95972868.84 | 72041602.09 | 23931266.75 | 0.129616E+09 | 81294330.91 |
| Annual Sum or Average | 0.746494E+09 | 0.431367E+09 | 0.315127E+09 | 0.118188E+10 | 0.519447E+09 |
| Minimum of Months | 28258627.63 | 1793018.21 | 22269249.93 | 60388160.71 | 9751396.96 |
| Maximum of Months | 95972868.84 | 72041602.09 | 29909262.48 | 0.133067E+09 | 81294330.91 |
Report: WindowEnergyReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.126517E+10 | 0.958498E+09 | 0.306671E+09 | 0.174376E+10 | 0.102130E+10 |
| February | 0.106001E+10 | 0.747293E+09 | 0.312720E+09 | 0.148803E+10 | 0.836375E+09 |
| March | 0.953782E+09 | 0.549948E+09 | 0.403834E+09 | 0.136789E+10 | 0.829253E+09 |
| April | 0.625800E+09 | 0.233502E+09 | 0.392298E+09 | 0.100367E+10 | 0.520786E+09 |
| May | 0.456988E+09 | 63963307.14 | 0.393024E+09 | 0.815359E+09 | 0.320358E+09 |
| June | 0.381547E+09 | 24209275.36 | 0.357338E+09 | 0.849918E+09 | 0.154243E+09 |
| July | 0.401910E+09 | 37257755.16 | 0.364652E+09 | 0.895950E+09 | 0.131663E+09 |
| August | 0.512325E+09 | 0.135615E+09 | 0.376709E+09 | 0.106559E+10 | 0.194076E+09 |
| September | 0.773884E+09 | 0.402060E+09 | 0.371825E+09 | 0.145062E+10 | 0.373656E+09 |
| October | 0.108653E+10 | 0.734567E+09 | 0.351963E+09 | 0.173025E+10 | 0.615577E+09 |
| November | 0.126536E+10 | 0.964683E+09 | 0.300679E+09 | 0.179666E+10 | 0.918632E+09 |
| December | 0.129582E+10 | 0.972703E+09 | 0.323119E+09 | 0.175006E+10 | 0.109763E+10 |
| Annual Sum or Average | 0.100791E+11 | 0.582430E+10 | 0.425483E+10 | 0.159578E+11 | 0.701356E+10 |
| Minimum of Months | 0.381547E+09 | 24209275.36 | 0.300679E+09 | 0.815359E+09 | 0.131663E+09 |
| Maximum of Months | 0.129582E+10 | 0.972703E+09 | 0.403834E+09 | 0.179666E+10 | 0.109763E+10 |
Report: WindowEnergyReportMonthly
For: BATH_ZN_1_FLR_1_WALL_5_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.186235E+09 | 92332946.93 | 93901883.99 | 0.160900E+09 | 0.659342E+09 |
| February | 0.218837E+09 | 0.111938E+09 | 0.106899E+09 | 0.228190E+09 | 0.542294E+09 |
| March | 0.374776E+09 | 0.207076E+09 | 0.167700E+09 | 0.452890E+09 | 0.532995E+09 |
| April | 0.441258E+09 | 0.252731E+09 | 0.188527E+09 | 0.650375E+09 | 0.326730E+09 |
| May | 0.482605E+09 | 0.271823E+09 | 0.210783E+09 | 0.806835E+09 | 0.205627E+09 |
| June | 0.455411E+09 | 0.256778E+09 | 0.198633E+09 | 0.883559E+09 | 0.101325E+09 |
| July | 0.410112E+09 | 0.215052E+09 | 0.195061E+09 | 0.804852E+09 | 84199770.45 |
| August | 0.410809E+09 | 0.224939E+09 | 0.185870E+09 | 0.766370E+09 | 0.118238E+09 |
| September | 0.398918E+09 | 0.233200E+09 | 0.165718E+09 | 0.687269E+09 | 0.226123E+09 |
| October | 0.317109E+09 | 0.184255E+09 | 0.132854E+09 | 0.445827E+09 | 0.379797E+09 |
| November | 0.223229E+09 | 0.125829E+09 | 97399585.48 | 0.232686E+09 | 0.591549E+09 |
| December | 0.168365E+09 | 76578182.95 | 91786478.60 | 0.127191E+09 | 0.717238E+09 |
| Annual Sum or Average | 0.408766E+10 | 0.225253E+10 | 0.183513E+10 | 0.624694E+10 | 0.448546E+10 |
| Minimum of Months | 0.168365E+09 | 76578182.95 | 91786478.60 | 0.127191E+09 | 84199770.45 |
| Maximum of Months | 0.482605E+09 | 0.271823E+09 | 0.210783E+09 | 0.883559E+09 | 0.717238E+09 |
Report: WindowEnergyReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.587193E+09 | 0.318531E+09 | 0.268662E+09 | 0.515760E+09 | 0.142607E+10 |
| February | 0.709582E+09 | 0.404457E+09 | 0.305125E+09 | 0.747982E+09 | 0.114439E+10 |
| March | 0.969969E+09 | 0.534422E+09 | 0.435547E+09 | 0.113276E+10 | 0.107035E+10 |
| April | 0.113106E+10 | 0.627487E+09 | 0.503576E+09 | 0.162784E+10 | 0.620180E+09 |
| May | 0.120610E+10 | 0.655471E+09 | 0.550630E+09 | 0.200686E+10 | 0.381906E+09 |
| June | 0.116785E+10 | 0.649698E+09 | 0.518153E+09 | 0.223796E+10 | 0.188204E+09 |
| July | 0.108222E+10 | 0.565765E+09 | 0.516454E+09 | 0.207560E+10 | 0.164975E+09 |
| August | 0.102979E+10 | 0.527037E+09 | 0.502753E+09 | 0.188316E+10 | 0.235408E+09 |
| September | 0.987331E+09 | 0.563344E+09 | 0.423987E+09 | 0.165672E+10 | 0.435917E+09 |
| October | 0.784631E+09 | 0.423457E+09 | 0.361173E+09 | 0.105651E+10 | 0.772850E+09 |
| November | 0.680663E+09 | 0.396260E+09 | 0.284403E+09 | 0.685246E+09 | 0.123827E+10 |
| December | 0.586689E+09 | 0.310841E+09 | 0.275848E+09 | 0.484759E+09 | 0.156145E+10 |
| Annual Sum or Average | 0.109231E+11 | 0.597677E+10 | 0.494631E+10 | 0.161112E+11 | 0.923996E+10 |
| Minimum of Months | 0.586689E+09 | 0.310841E+09 | 0.268662E+09 | 0.484759E+09 | 0.164975E+09 |
| Maximum of Months | 0.120610E+10 | 0.655471E+09 | 0.550630E+09 | 0.223796E+10 | 0.156145E+10 |
Report: WindowEnergyReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 93039474.07 | 70487116.17 | 22552357.89 | 0.123444E+09 | 81484121.29 |
| February | 77952442.96 | 54955263.74 | 22997179.21 | 0.104535E+09 | 67523686.33 |
| March | 70140303.02 | 40442697.97 | 29697605.06 | 95608889.61 | 67469632.81 |
| April | 46020827.72 | 17171529.53 | 28849298.18 | 70856964.96 | 42410811.48 |
| May | 33606491.11 | 4703807.53 | 28902683.58 | 57829075.57 | 25925578.82 |
| June | 28058651.18 | 1780329.64 | 26278321.53 | 61612508.00 | 12390586.28 |
| July | 29556128.86 | 2739903.81 | 26816225.05 | 64338137.06 | 10793757.18 |
| August | 37675914.91 | 9973041.70 | 27702873.21 | 77155698.73 | 15534849.07 |
| September | 56910804.81 | 29567139.68 | 27343665.12 | 0.106014E+09 | 28866436.70 |
| October | 79902548.75 | 54019456.67 | 25883092.08 | 0.125796E+09 | 47335442.00 |
| November | 93053612.09 | 70941953.88 | 22111658.21 | 0.128618E+09 | 71432183.77 |
| December | 95293702.31 | 71531788.79 | 23761913.52 | 0.123438E+09 | 87382991.75 |
| Annual Sum or Average | 0.741211E+09 | 0.428314E+09 | 0.312897E+09 | 0.113925E+10 | 0.558550E+09 |
| Minimum of Months | 28058651.18 | 1780329.64 | 22111658.21 | 57829075.57 | 10793757.18 |
| Maximum of Months | 95293702.31 | 71531788.79 | 29697605.06 | 0.128618E+09 | 87382991.75 |
Report: WindowEnergyReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.140884E+10 | 0.106734E+10 | 0.341497E+09 | 0.186924E+10 | 0.123386E+10 |
| February | 0.118039E+10 | 0.832154E+09 | 0.348232E+09 | 0.158291E+10 | 0.102247E+10 |
| March | 0.106209E+10 | 0.612399E+09 | 0.449693E+09 | 0.144775E+10 | 0.102165E+10 |
| April | 0.696865E+09 | 0.260018E+09 | 0.436847E+09 | 0.107294E+10 | 0.642074E+09 |
| May | 0.508883E+09 | 71226880.82 | 0.437656E+09 | 0.875718E+09 | 0.392207E+09 |
| June | 0.424875E+09 | 26958443.01 | 0.397917E+09 | 0.933204E+09 | 0.187396E+09 |
| July | 0.447550E+09 | 41488687.89 | 0.406062E+09 | 0.974460E+09 | 0.163153E+09 |
| August | 0.570503E+09 | 0.151016E+09 | 0.419488E+09 | 0.116836E+10 | 0.235063E+09 |
| September | 0.861766E+09 | 0.447717E+09 | 0.414048E+09 | 0.160530E+10 | 0.437097E+09 |
| October | 0.120992E+10 | 0.817984E+09 | 0.391932E+09 | 0.190486E+10 | 0.716772E+09 |
| November | 0.140905E+10 | 0.107423E+10 | 0.334823E+09 | 0.194758E+10 | 0.108165E+10 |
| December | 0.144297E+10 | 0.108316E+10 | 0.359812E+09 | 0.186915E+10 | 0.132319E+10 |
| Annual Sum or Average | 0.112237E+11 | 0.648570E+10 | 0.473801E+10 | 0.172515E+11 | 0.845659E+10 |
| Minimum of Months | 0.424875E+09 | 26958443.01 | 0.334823E+09 | 0.875718E+09 | 0.163153E+09 |
| Maximum of Months | 0.144297E+10 | 0.108316E+10 | 0.449693E+09 | 0.194758E+10 | 0.132319E+10 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.119624E+09 | 82938475.51 | 36685290.73 | 0.131933E+09 | 0.169023E+09 |
| February | 0.144511E+09 | 0.102922E+09 | 41588295.67 | 0.171152E+09 | 0.144730E+09 |
| March | 0.218381E+09 | 0.153788E+09 | 64593839.41 | 0.277958E+09 | 0.143165E+09 |
| April | 0.268067E+09 | 0.199679E+09 | 68387515.30 | 0.373037E+09 | 97076844.50 |
| May | 0.304529E+09 | 0.227052E+09 | 77477708.50 | 0.448840E+09 | 71746456.39 |
| June | 0.311899E+09 | 0.242660E+09 | 69238584.15 | 0.483736E+09 | 42366388.57 |
| July | 0.278862E+09 | 0.201917E+09 | 76945149.28 | 0.438190E+09 | 34427351.83 |
| August | 0.259247E+09 | 0.187383E+09 | 71863795.22 | 0.400485E+09 | 44480960.72 |
| September | 0.230580E+09 | 0.172998E+09 | 57581410.45 | 0.348388E+09 | 68483971.71 |
| October | 0.178107E+09 | 0.129401E+09 | 48706503.53 | 0.246262E+09 | 0.102824E+09 |
| November | 0.135099E+09 | 0.100363E+09 | 34735760.23 | 0.159753E+09 | 0.151630E+09 |
| December | 0.111702E+09 | 73647220.16 | 38054443.77 | 0.115564E+09 | 0.186314E+09 |
| Annual Sum or Average | 0.256061E+10 | 0.187475E+10 | 0.685858E+09 | 0.359530E+10 | 0.125627E+10 |
| Minimum of Months | 0.111702E+09 | 73647220.16 | 34735760.23 | 0.115564E+09 | 34427351.83 |
| Maximum of Months | 0.311899E+09 | 0.242660E+09 | 77477708.50 | 0.483736E+09 | 0.186314E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.119624E+09 | 82938475.51 | 36685290.73 | 0.131933E+09 | 0.169023E+09 |
| February | 0.144511E+09 | 0.102922E+09 | 41588295.67 | 0.171152E+09 | 0.144730E+09 |
| March | 0.218381E+09 | 0.153788E+09 | 64593839.41 | 0.277958E+09 | 0.143165E+09 |
| April | 0.268067E+09 | 0.199679E+09 | 68387515.30 | 0.373037E+09 | 97076844.50 |
| May | 0.304529E+09 | 0.227052E+09 | 77477708.50 | 0.448840E+09 | 71746456.39 |
| June | 0.311899E+09 | 0.242660E+09 | 69238584.15 | 0.483736E+09 | 42366388.57 |
| July | 0.278862E+09 | 0.201917E+09 | 76945149.28 | 0.438190E+09 | 34427351.83 |
| August | 0.259247E+09 | 0.187383E+09 | 71863795.22 | 0.400485E+09 | 44480960.72 |
| September | 0.230580E+09 | 0.172998E+09 | 57581410.45 | 0.348388E+09 | 68483971.71 |
| October | 0.178107E+09 | 0.129401E+09 | 48706503.53 | 0.246262E+09 | 0.102824E+09 |
| November | 0.135099E+09 | 0.100363E+09 | 34735760.23 | 0.159753E+09 | 0.151630E+09 |
| December | 0.111702E+09 | 73647220.16 | 38054443.77 | 0.115564E+09 | 0.186314E+09 |
| Annual Sum or Average | 0.256061E+10 | 0.187475E+10 | 0.685858E+09 | 0.359530E+10 | 0.125627E+10 |
| Minimum of Months | 0.111702E+09 | 73647220.16 | 34735760.23 | 0.115564E+09 | 34427351.83 |
| Maximum of Months | 0.311899E+09 | 0.242660E+09 | 77477708.50 | 0.483736E+09 | 0.186314E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.119624E+09 | 82938475.51 | 36685290.73 | 0.131933E+09 | 0.169023E+09 |
| February | 0.144511E+09 | 0.102922E+09 | 41588295.67 | 0.171152E+09 | 0.144730E+09 |
| March | 0.218381E+09 | 0.153788E+09 | 64593839.41 | 0.277958E+09 | 0.143165E+09 |
| April | 0.268067E+09 | 0.199679E+09 | 68387515.30 | 0.373037E+09 | 97076844.50 |
| May | 0.304529E+09 | 0.227052E+09 | 77477708.50 | 0.448840E+09 | 71746456.39 |
| June | 0.311899E+09 | 0.242660E+09 | 69238584.15 | 0.483736E+09 | 42366388.57 |
| July | 0.278862E+09 | 0.201917E+09 | 76945149.28 | 0.438190E+09 | 34427351.83 |
| August | 0.259247E+09 | 0.187383E+09 | 71863795.22 | 0.400485E+09 | 44480960.72 |
| September | 0.230580E+09 | 0.172998E+09 | 57581410.45 | 0.348388E+09 | 68483971.71 |
| October | 0.178107E+09 | 0.129401E+09 | 48706503.53 | 0.246262E+09 | 0.102824E+09 |
| November | 0.135099E+09 | 0.100363E+09 | 34735760.23 | 0.159753E+09 | 0.151630E+09 |
| December | 0.111702E+09 | 73647220.16 | 38054443.77 | 0.115564E+09 | 0.186314E+09 |
| Annual Sum or Average | 0.256061E+10 | 0.187475E+10 | 0.685858E+09 | 0.359530E+10 | 0.125627E+10 |
| Minimum of Months | 0.111702E+09 | 73647220.16 | 34735760.23 | 0.115564E+09 | 34427351.83 |
| Maximum of Months | 0.311899E+09 | 0.242660E+09 | 77477708.50 | 0.483736E+09 | 0.186314E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.119624E+09 | 82938475.51 | 36685290.73 | 0.131933E+09 | 0.169023E+09 |
| February | 0.144511E+09 | 0.102922E+09 | 41588295.67 | 0.171152E+09 | 0.144730E+09 |
| March | 0.218381E+09 | 0.153788E+09 | 64593839.41 | 0.277958E+09 | 0.143165E+09 |
| April | 0.268067E+09 | 0.199679E+09 | 68387515.30 | 0.373037E+09 | 97076844.50 |
| May | 0.304529E+09 | 0.227052E+09 | 77477708.50 | 0.448840E+09 | 71746456.39 |
| June | 0.311899E+09 | 0.242660E+09 | 69238584.15 | 0.483736E+09 | 42366388.57 |
| July | 0.278862E+09 | 0.201917E+09 | 76945149.28 | 0.438190E+09 | 34427351.83 |
| August | 0.259247E+09 | 0.187383E+09 | 71863795.22 | 0.400485E+09 | 44480960.72 |
| September | 0.230580E+09 | 0.172998E+09 | 57581410.45 | 0.348388E+09 | 68483971.71 |
| October | 0.178107E+09 | 0.129401E+09 | 48706503.53 | 0.246262E+09 | 0.102824E+09 |
| November | 0.135099E+09 | 0.100363E+09 | 34735760.23 | 0.159753E+09 | 0.151630E+09 |
| December | 0.111702E+09 | 73647220.16 | 38054443.77 | 0.115564E+09 | 0.186314E+09 |
| Annual Sum or Average | 0.256061E+10 | 0.187475E+10 | 0.685858E+09 | 0.359530E+10 | 0.125627E+10 |
| Minimum of Months | 0.111702E+09 | 73647220.16 | 34735760.23 | 0.115564E+09 | 34427351.83 |
| Maximum of Months | 0.311899E+09 | 0.242660E+09 | 77477708.50 | 0.483736E+09 | 0.186314E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.119624E+09 | 82938475.51 | 36685290.73 | 0.131933E+09 | 0.169023E+09 |
| February | 0.144511E+09 | 0.102922E+09 | 41588295.67 | 0.171152E+09 | 0.144730E+09 |
| March | 0.218381E+09 | 0.153788E+09 | 64593839.41 | 0.277958E+09 | 0.143165E+09 |
| April | 0.268067E+09 | 0.199679E+09 | 68387515.30 | 0.373037E+09 | 97076844.50 |
| May | 0.304529E+09 | 0.227052E+09 | 77477708.50 | 0.448840E+09 | 71746456.39 |
| June | 0.311899E+09 | 0.242660E+09 | 69238584.15 | 0.483736E+09 | 42366388.57 |
| July | 0.278862E+09 | 0.201917E+09 | 76945149.28 | 0.438190E+09 | 34427351.83 |
| August | 0.259247E+09 | 0.187383E+09 | 71863795.22 | 0.400485E+09 | 44480960.72 |
| September | 0.230580E+09 | 0.172998E+09 | 57581410.45 | 0.348388E+09 | 68483971.71 |
| October | 0.178107E+09 | 0.129401E+09 | 48706503.53 | 0.246262E+09 | 0.102824E+09 |
| November | 0.135099E+09 | 0.100363E+09 | 34735760.23 | 0.159753E+09 | 0.151630E+09 |
| December | 0.111702E+09 | 73647220.16 | 38054443.77 | 0.115564E+09 | 0.186314E+09 |
| Annual Sum or Average | 0.256061E+10 | 0.187475E+10 | 0.685858E+09 | 0.359530E+10 | 0.125627E+10 |
| Minimum of Months | 0.111702E+09 | 73647220.16 | 34735760.23 | 0.115564E+09 | 34427351.83 |
| Maximum of Months | 0.311899E+09 | 0.242660E+09 | 77477708.50 | 0.483736E+09 | 0.186314E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.119624E+09 | 82938475.51 | 36685290.73 | 0.131933E+09 | 0.169023E+09 |
| February | 0.144511E+09 | 0.102922E+09 | 41588295.67 | 0.171152E+09 | 0.144730E+09 |
| March | 0.218381E+09 | 0.153788E+09 | 64593839.41 | 0.277958E+09 | 0.143165E+09 |
| April | 0.268067E+09 | 0.199679E+09 | 68387515.30 | 0.373037E+09 | 97076844.50 |
| May | 0.304529E+09 | 0.227052E+09 | 77477708.50 | 0.448840E+09 | 71746456.39 |
| June | 0.311899E+09 | 0.242660E+09 | 69238584.15 | 0.483736E+09 | 42366388.57 |
| July | 0.278862E+09 | 0.201917E+09 | 76945149.28 | 0.438190E+09 | 34427351.83 |
| August | 0.259247E+09 | 0.187383E+09 | 71863795.22 | 0.400485E+09 | 44480960.72 |
| September | 0.230580E+09 | 0.172998E+09 | 57581410.45 | 0.348388E+09 | 68483971.71 |
| October | 0.178107E+09 | 0.129401E+09 | 48706503.53 | 0.246262E+09 | 0.102824E+09 |
| November | 0.135099E+09 | 0.100363E+09 | 34735760.23 | 0.159753E+09 | 0.151630E+09 |
| December | 0.111702E+09 | 73647220.16 | 38054443.77 | 0.115564E+09 | 0.186314E+09 |
| Annual Sum or Average | 0.256061E+10 | 0.187475E+10 | 0.685858E+09 | 0.359530E+10 | 0.125627E+10 |
| Minimum of Months | 0.111702E+09 | 73647220.16 | 34735760.23 | 0.115564E+09 | 34427351.83 |
| Maximum of Months | 0.311899E+09 | 0.242660E+09 | 77477708.50 | 0.483736E+09 | 0.186314E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.119624E+09 | 82938475.51 | 36685290.73 | 0.131933E+09 | 0.169023E+09 |
| February | 0.144511E+09 | 0.102922E+09 | 41588295.67 | 0.171152E+09 | 0.144730E+09 |
| March | 0.218381E+09 | 0.153788E+09 | 64593839.41 | 0.277958E+09 | 0.143165E+09 |
| April | 0.268067E+09 | 0.199679E+09 | 68387515.30 | 0.373037E+09 | 97076844.50 |
| May | 0.304529E+09 | 0.227052E+09 | 77477708.50 | 0.448840E+09 | 71746456.39 |
| June | 0.311899E+09 | 0.242660E+09 | 69238584.15 | 0.483736E+09 | 42366388.57 |
| July | 0.278862E+09 | 0.201917E+09 | 76945149.28 | 0.438190E+09 | 34427351.83 |
| August | 0.259247E+09 | 0.187383E+09 | 71863795.22 | 0.400485E+09 | 44480960.72 |
| September | 0.230580E+09 | 0.172998E+09 | 57581410.45 | 0.348388E+09 | 68483971.71 |
| October | 0.178107E+09 | 0.129401E+09 | 48706503.53 | 0.246262E+09 | 0.102824E+09 |
| November | 0.135099E+09 | 0.100363E+09 | 34735760.23 | 0.159753E+09 | 0.151630E+09 |
| December | 0.111702E+09 | 73647220.16 | 38054443.77 | 0.115564E+09 | 0.186314E+09 |
| Annual Sum or Average | 0.256061E+10 | 0.187475E+10 | 0.685858E+09 | 0.359530E+10 | 0.125627E+10 |
| Minimum of Months | 0.111702E+09 | 73647220.16 | 34735760.23 | 0.115564E+09 | 34427351.83 |
| Maximum of Months | 0.311899E+09 | 0.242660E+09 | 77477708.50 | 0.483736E+09 | 0.186314E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.119624E+09 | 82938475.51 | 36685290.73 | 0.131933E+09 | 0.169023E+09 |
| February | 0.144511E+09 | 0.102922E+09 | 41588295.67 | 0.171152E+09 | 0.144730E+09 |
| March | 0.218381E+09 | 0.153788E+09 | 64593839.41 | 0.277958E+09 | 0.143165E+09 |
| April | 0.268067E+09 | 0.199679E+09 | 68387515.30 | 0.373037E+09 | 97076844.50 |
| May | 0.304529E+09 | 0.227052E+09 | 77477708.50 | 0.448840E+09 | 71746456.39 |
| June | 0.311899E+09 | 0.242660E+09 | 69238584.15 | 0.483736E+09 | 42366388.57 |
| July | 0.278862E+09 | 0.201917E+09 | 76945149.28 | 0.438190E+09 | 34427351.83 |
| August | 0.259247E+09 | 0.187383E+09 | 71863795.22 | 0.400485E+09 | 44480960.72 |
| September | 0.230580E+09 | 0.172998E+09 | 57581410.45 | 0.348388E+09 | 68483971.71 |
| October | 0.178107E+09 | 0.129401E+09 | 48706503.53 | 0.246262E+09 | 0.102824E+09 |
| November | 0.135099E+09 | 0.100363E+09 | 34735760.23 | 0.159753E+09 | 0.151630E+09 |
| December | 0.111702E+09 | 73647220.16 | 38054443.77 | 0.115564E+09 | 0.186314E+09 |
| Annual Sum or Average | 0.256061E+10 | 0.187475E+10 | 0.685858E+09 | 0.359530E+10 | 0.125627E+10 |
| Minimum of Months | 0.111702E+09 | 73647220.16 | 34735760.23 | 0.115564E+09 | 34427351.83 |
| Maximum of Months | 0.311899E+09 | 0.242660E+09 | 77477708.50 | 0.483736E+09 | 0.186314E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.119624E+09 | 82938475.51 | 36685290.73 | 0.131933E+09 | 0.169023E+09 |
| February | 0.144511E+09 | 0.102922E+09 | 41588295.67 | 0.171152E+09 | 0.144730E+09 |
| March | 0.218381E+09 | 0.153788E+09 | 64593839.41 | 0.277958E+09 | 0.143165E+09 |
| April | 0.268067E+09 | 0.199679E+09 | 68387515.30 | 0.373037E+09 | 97076844.50 |
| May | 0.304529E+09 | 0.227052E+09 | 77477708.50 | 0.448840E+09 | 71746456.39 |
| June | 0.311899E+09 | 0.242660E+09 | 69238584.15 | 0.483736E+09 | 42366388.57 |
| July | 0.278862E+09 | 0.201917E+09 | 76945149.28 | 0.438190E+09 | 34427351.83 |
| August | 0.259247E+09 | 0.187383E+09 | 71863795.22 | 0.400485E+09 | 44480960.72 |
| September | 0.230580E+09 | 0.172998E+09 | 57581410.45 | 0.348388E+09 | 68483971.71 |
| October | 0.178107E+09 | 0.129401E+09 | 48706503.53 | 0.246262E+09 | 0.102824E+09 |
| November | 0.135099E+09 | 0.100363E+09 | 34735760.23 | 0.159753E+09 | 0.151630E+09 |
| December | 0.111702E+09 | 73647220.16 | 38054443.77 | 0.115564E+09 | 0.186314E+09 |
| Annual Sum or Average | 0.256061E+10 | 0.187475E+10 | 0.685858E+09 | 0.359530E+10 | 0.125627E+10 |
| Minimum of Months | 0.111702E+09 | 73647220.16 | 34735760.23 | 0.115564E+09 | 34427351.83 |
| Maximum of Months | 0.311899E+09 | 0.242660E+09 | 77477708.50 | 0.483736E+09 | 0.186314E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 37026992.60 | 20085812.80 | 16941179.80 | 31972403.74 | 93693224.78 |
| February | 44744511.18 | 25504093.56 | 19240417.62 | 46060334.08 | 75906943.76 |
| March | 61163892.87 | 33699350.14 | 27464542.72 | 69467737.10 | 71481000.62 |
| April | 71322052.51 | 39567802.31 | 31754250.20 | 0.101216E+09 | 40828880.53 |
| May | 76053803.51 | 41332421.79 | 34721381.72 | 0.125758E+09 | 24538732.86 |
| June | 73641898.70 | 40968410.28 | 32673488.42 | 0.140995E+09 | 11518526.27 |
| July | 68242098.71 | 35675797.21 | 32566301.50 | 0.131118E+09 | 10134555.32 |
| August | 64936051.94 | 33233676.38 | 31702375.56 | 0.119130E+09 | 14519338.30 |
| September | 62258705.45 | 35523143.66 | 26735561.78 | 0.105334E+09 | 26319790.34 |
| October | 49476914.48 | 26702211.06 | 22774703.42 | 67072082.22 | 48170237.30 |
| November | 42920983.37 | 24987222.60 | 17933760.77 | 43053201.97 | 78949238.72 |
| December | 36995198.25 | 19600884.44 | 17394313.82 | 29983647.03 | 0.101700E+09 |
| Annual Sum or Average | 0.688783E+09 | 0.376881E+09 | 0.311902E+09 | 0.101116E+10 | 0.597761E+09 |
| Minimum of Months | 36995198.25 | 19600884.44 | 16941179.80 | 29983647.03 | 10134555.32 |
| Maximum of Months | 76053803.51 | 41332421.79 | 34721381.72 | 0.140995E+09 | 0.101700E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.438256E+09 | 0.237730E+09 | 0.200525E+09 | 0.378468E+09 | 0.110808E+10 |
| February | 0.529600E+09 | 0.301860E+09 | 0.227740E+09 | 0.545550E+09 | 0.897560E+09 |
| March | 0.723943E+09 | 0.398857E+09 | 0.325086E+09 | 0.823328E+09 | 0.844780E+09 |
| April | 0.844177E+09 | 0.468314E+09 | 0.375863E+09 | 0.120038E+10 | 0.482923E+09 |
| May | 0.900184E+09 | 0.489200E+09 | 0.410984E+09 | 0.149091E+10 | 0.290466E+09 |
| June | 0.871638E+09 | 0.484891E+09 | 0.386746E+09 | 0.167103E+10 | 0.136342E+09 |
| July | 0.807724E+09 | 0.422249E+09 | 0.385475E+09 | 0.155380E+10 | 0.119961E+09 |
| August | 0.768593E+09 | 0.393345E+09 | 0.375248E+09 | 0.141234E+10 | 0.171868E+09 |
| September | 0.736902E+09 | 0.420443E+09 | 0.316459E+09 | 0.124963E+10 | 0.311541E+09 |
| October | 0.585615E+09 | 0.316040E+09 | 0.269575E+09 | 0.796118E+09 | 0.569937E+09 |
| November | 0.508017E+09 | 0.295742E+09 | 0.212274E+09 | 0.509898E+09 | 0.933367E+09 |
| December | 0.437879E+09 | 0.231991E+09 | 0.205888E+09 | 0.354873E+09 | 0.120300E+10 |
| Annual Sum or Average | 0.815253E+10 | 0.446066E+10 | 0.369186E+10 | 0.119863E+11 | 0.706983E+10 |
| Minimum of Months | 0.437879E+09 | 0.231991E+09 | 0.200525E+09 | 0.354873E+09 | 0.119961E+09 |
| Maximum of Months | 0.900184E+09 | 0.489200E+09 | 0.410984E+09 | 0.167103E+10 | 0.120300E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.223687E+09 | 0.121341E+09 | 0.102345E+09 | 0.180162E+09 | 0.672922E+09 |
| February | 0.270310E+09 | 0.154074E+09 | 0.116236E+09 | 0.267469E+09 | 0.526130E+09 |
| March | 0.369502E+09 | 0.203583E+09 | 0.165919E+09 | 0.413282E+09 | 0.481711E+09 |
| April | 0.430869E+09 | 0.239035E+09 | 0.191835E+09 | 0.607839E+09 | 0.275225E+09 |
| May | 0.459455E+09 | 0.249695E+09 | 0.209760E+09 | 0.757025E+09 | 0.176299E+09 |
| June | 0.444884E+09 | 0.247496E+09 | 0.197388E+09 | 0.847645E+09 | 94631686.70 |
| July | 0.412263E+09 | 0.215523E+09 | 0.196740E+09 | 0.785307E+09 | 83158625.93 |
| August | 0.392291E+09 | 0.200769E+09 | 0.191521E+09 | 0.718439E+09 | 0.109364E+09 |
| September | 0.376116E+09 | 0.214600E+09 | 0.161516E+09 | 0.632005E+09 | 0.189617E+09 |
| October | 0.298899E+09 | 0.161312E+09 | 0.137587E+09 | 0.400360E+09 | 0.330978E+09 |
| November | 0.259293E+09 | 0.150951E+09 | 0.108342E+09 | 0.252417E+09 | 0.544658E+09 |
| December | 0.223495E+09 | 0.118412E+09 | 0.105083E+09 | 0.164986E+09 | 0.731694E+09 |
| Annual Sum or Average | 0.416106E+10 | 0.227679E+10 | 0.188427E+10 | 0.602694E+10 | 0.421639E+10 |
| Minimum of Months | 0.223495E+09 | 0.118412E+09 | 0.102345E+09 | 0.164986E+09 | 83158625.93 |
| Maximum of Months | 0.459455E+09 | 0.249695E+09 | 0.209760E+09 | 0.847645E+09 | 0.731694E+09 |
Report: WindowEnergyReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.206170E+09 | 0.00 | 0.206170E+09 | 9829206.24 | 0.153245E+10 |
| February | 0.227649E+09 | 0.00 | 0.227649E+09 | 56726365.25 | 0.123714E+10 |
| March | 0.331073E+09 | 0.00 | 0.331073E+09 | 0.154170E+09 | 0.117637E+10 |
| April | 0.367630E+09 | 1880828.01 | 0.365749E+09 | 0.352071E+09 | 0.698487E+09 |
| May | 0.440199E+09 | 24240845.31 | 0.415958E+09 | 0.658683E+09 | 0.424314E+09 |
| June | 0.452518E+09 | 47133855.25 | 0.405384E+09 | 0.968125E+09 | 0.229412E+09 |
| July | 0.430734E+09 | 33921585.48 | 0.396812E+09 | 0.905367E+09 | 0.192199E+09 |
| August | 0.371576E+09 | 6042510.01 | 0.365533E+09 | 0.702732E+09 | 0.256896E+09 |
| September | 0.316178E+09 | 70676.64 | 0.316107E+09 | 0.499419E+09 | 0.504267E+09 |
| October | 0.271433E+09 | 0.00 | 0.271433E+09 | 0.218786E+09 | 0.829485E+09 |
| November | 0.211980E+09 | 0.00 | 0.211980E+09 | 28150548.08 | 0.133992E+10 |
| December | 0.204211E+09 | 0.00 | 0.204211E+09 | 6706240.09 | 0.170384E+10 |
| Annual Sum or Average | 0.383135E+10 | 0.113290E+09 | 0.371806E+10 | 0.456077E+10 | 0.101248E+11 |
| Minimum of Months | 0.204211E+09 | 0.00 | 0.204211E+09 | 6706240.09 | 0.192199E+09 |
| Maximum of Months | 0.452518E+09 | 47133855.25 | 0.415958E+09 | 0.968125E+09 | 0.170384E+10 |
Report: WindowEnergyReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 37378128.12 | 20276291.20 | 17101836.92 | 33770791.63 | 87443463.08 |
| February | 45168833.71 | 25745954.77 | 19422878.94 | 48892046.71 | 70239242.86 |
| March | 61743924.18 | 34018928.86 | 27724995.32 | 73261563.96 | 67086101.46 |
| April | 71998415.99 | 39943032.91 | 32055383.09 | 0.103436E+09 | 40724349.48 |
| May | 76775039.28 | 41724386.68 | 35050652.60 | 0.126678E+09 | 27181103.04 |
| June | 74340261.83 | 41356923.17 | 32983338.65 | 0.140929E+09 | 14938754.84 |
| July | 68889254.28 | 36014119.03 | 32875135.25 | 0.130431E+09 | 12529044.09 |
| August | 65551855.51 | 33548839.00 | 32003016.51 | 0.119188E+09 | 16452970.04 |
| September | 62849119.12 | 35860017.83 | 26989101.29 | 0.105320E+09 | 30011210.96 |
| October | 49946115.48 | 26955434.29 | 22990681.19 | 68006797.63 | 49643819.70 |
| November | 43328012.96 | 25224182.20 | 18103830.76 | 44858519.85 | 75852308.33 |
| December | 37346032.26 | 19786764.15 | 17559268.11 | 31519418.66 | 96564968.02 |
| Annual Sum or Average | 0.695315E+09 | 0.380455E+09 | 0.314860E+09 | 0.102629E+10 | 0.588667E+09 |
| Minimum of Months | 37346032.26 | 19786764.15 | 17101836.92 | 31519418.66 | 12529044.09 |
| Maximum of Months | 76775039.28 | 41724386.68 | 35050652.60 | 0.140929E+09 | 96564968.02 |
Report: WindowEnergyReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.382047E+09 | 0.207247E+09 | 0.174800E+09 | 0.345176E+09 | 0.893771E+09 |
| February | 0.461676E+09 | 0.263153E+09 | 0.198524E+09 | 0.499732E+09 | 0.717924E+09 |
| March | 0.631093E+09 | 0.347712E+09 | 0.283381E+09 | 0.748816E+09 | 0.685696E+09 |
| April | 0.735905E+09 | 0.408263E+09 | 0.327642E+09 | 0.105723E+10 | 0.416243E+09 |
| May | 0.784728E+09 | 0.426470E+09 | 0.358257E+09 | 0.129494E+10 | 0.277802E+09 |
| June | 0.759841E+09 | 0.422714E+09 | 0.337127E+09 | 0.144071E+10 | 0.152691E+09 |
| July | 0.704126E+09 | 0.368105E+09 | 0.336021E+09 | 0.133335E+10 | 0.128054E+09 |
| August | 0.670014E+09 | 0.342907E+09 | 0.327107E+09 | 0.121826E+10 | 0.168167E+09 |
| September | 0.642389E+09 | 0.366530E+09 | 0.275859E+09 | 0.107649E+10 | 0.306748E+09 |
| October | 0.510506E+09 | 0.275515E+09 | 0.234991E+09 | 0.695106E+09 | 0.507416E+09 |
| November | 0.442861E+09 | 0.257820E+09 | 0.185042E+09 | 0.458505E+09 | 0.775296E+09 |
| December | 0.381719E+09 | 0.202243E+09 | 0.179476E+09 | 0.322164E+09 | 0.987003E+09 |
| Annual Sum or Average | 0.710690E+10 | 0.388868E+10 | 0.321823E+10 | 0.104905E+11 | 0.601681E+10 |
| Minimum of Months | 0.381719E+09 | 0.202243E+09 | 0.174800E+09 | 0.322164E+09 | 0.128054E+09 |
| Maximum of Months | 0.784728E+09 | 0.426470E+09 | 0.358257E+09 | 0.144071E+10 | 0.987003E+09 |
Report: WindowEnergyReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.198629E+09 | 0.00 | 0.198629E+09 | 12467721.25 | 0.140014E+10 |
| February | 0.219075E+09 | 0.00 | 0.219075E+09 | 56905234.72 | 0.114029E+10 |
| March | 0.317416E+09 | 0.00 | 0.317416E+09 | 0.150632E+09 | 0.108962E+10 |
| April | 0.354671E+09 | 2794194.65 | 0.351876E+09 | 0.347031E+09 | 0.625074E+09 |
| May | 0.434673E+09 | 31431911.98 | 0.403241E+09 | 0.663354E+09 | 0.359996E+09 |
| June | 0.447290E+09 | 55064940.23 | 0.392225E+09 | 0.952057E+09 | 0.178225E+09 |
| July | 0.427162E+09 | 41579696.64 | 0.385582E+09 | 0.903344E+09 | 0.151985E+09 |
| August | 0.360191E+09 | 7364741.18 | 0.352827E+09 | 0.683999E+09 | 0.218353E+09 |
| September | 0.304161E+09 | 121367.12 | 0.304040E+09 | 0.481587E+09 | 0.429341E+09 |
| October | 0.260955E+09 | 0.00 | 0.260955E+09 | 0.217489E+09 | 0.748666E+09 |
| November | 0.203872E+09 | 0.00 | 0.203872E+09 | 28065333.70 | 0.123522E+10 |
| December | 0.197090E+09 | 0.00 | 0.197090E+09 | 8245977.79 | 0.155350E+10 |
| Annual Sum or Average | 0.372519E+10 | 0.138357E+09 | 0.358683E+10 | 0.450518E+10 | 0.913041E+10 |
| Minimum of Months | 0.197090E+09 | 0.00 | 0.197090E+09 | 8245977.79 | 0.151985E+09 |
| Maximum of Months | 0.447290E+09 | 55064940.23 | 0.403241E+09 | 0.952057E+09 | 0.155350E+10 |
Report: WindowEnergyReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 10514136.84 | 0.00 | 10514136.84 | 228156.28 | 93843849.30 |
| February | 11663348.71 | 0.00 | 11663348.71 | 2541148.76 | 75710754.90 |
| March | 18226845.57 | 1036229.07 | 17190616.50 | 7798097.54 | 70071650.52 |
| April | 50771191.41 | 26641916.58 | 24129274.83 | 69966840.78 | 34723712.99 |
| May | 65854589.90 | 37665935.60 | 28188654.30 | 0.112323E+09 | 20264528.93 |
| June | 66439522.52 | 39271301.66 | 27168220.86 | 0.132642E+09 | 9630449.46 |
| July | 59968583.40 | 33539159.04 | 26429424.36 | 0.119442E+09 | 8463570.66 |
| August | 50390383.48 | 25825345.41 | 24565038.08 | 96124088.66 | 12346777.33 |
| September | 31406354.75 | 12736502.87 | 18669851.88 | 52876197.61 | 23972256.91 |
| October | 13979646.56 | 1904.46 | 13977742.10 | 11717490.49 | 48552378.53 |
| November | 10938436.28 | 0.00 | 10938436.28 | 1226430.37 | 82151647.18 |
| December | 10333493.35 | 0.00 | 10333493.35 | 111953.20 | 0.104196E+09 |
| Annual Sum or Average | 0.400487E+09 | 0.176718E+09 | 0.223768E+09 | 0.606997E+09 | 0.583927E+09 |
| Minimum of Months | 10333493.35 | 0.00 | 10333493.35 | 111953.20 | 8463570.66 |
| Maximum of Months | 66439522.52 | 39271301.66 | 28188654.30 | 0.132642E+09 | 0.104196E+09 |
Report: WindowEnergyReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.516915E+09 | 0.277406E+09 | 0.239508E+09 | 0.449001E+09 | 0.129816E+10 |
| February | 0.639012E+09 | 0.364769E+09 | 0.274244E+09 | 0.678391E+09 | 0.104419E+10 |
| March | 0.895925E+09 | 0.500591E+09 | 0.395334E+09 | 0.105400E+10 | 0.995483E+09 |
| April | 0.104623E+10 | 0.588528E+09 | 0.457705E+09 | 0.151374E+10 | 0.578705E+09 |
| May | 0.111499E+10 | 0.614775E+09 | 0.500211E+09 | 0.186089E+10 | 0.358476E+09 |
| June | 0.108029E+10 | 0.609360E+09 | 0.470929E+09 | 0.207884E+10 | 0.176467E+09 |
| July | 0.999306E+09 | 0.530639E+09 | 0.468668E+09 | 0.192793E+10 | 0.152820E+09 |
| August | 0.950590E+09 | 0.494315E+09 | 0.456276E+09 | 0.175311E+10 | 0.216382E+09 |
| September | 0.912135E+09 | 0.527906E+09 | 0.384229E+09 | 0.154615E+10 | 0.400513E+09 |
| October | 0.717000E+09 | 0.390808E+09 | 0.326191E+09 | 0.978253E+09 | 0.713526E+09 |
| November | 0.597232E+09 | 0.345013E+09 | 0.252219E+09 | 0.597208E+09 | 0.113313E+10 |
| December | 0.502425E+09 | 0.258817E+09 | 0.243608E+09 | 0.395329E+09 | 0.143205E+10 |
| Annual Sum or Average | 0.997205E+10 | 0.550293E+10 | 0.446912E+10 | 0.148328E+11 | 0.849991E+10 |
| Minimum of Months | 0.502425E+09 | 0.258817E+09 | 0.239508E+09 | 0.395329E+09 | 0.152820E+09 |
| Maximum of Months | 0.111499E+10 | 0.614775E+09 | 0.500211E+09 | 0.207884E+10 | 0.143205E+10 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 469.13 | 452.13 | 392.69 | 278.26 | 114.43 | 0.00 | 0.00 |
| February | 474.55 | 406.01 | 384.14 | 251.44 | 132.70 | 0.00 | 0.00 |
| March | 488.15 | 356.19 | 373.62 | 209.24 | 164.37 | 0.00 | 0.00 |
| April | 500.71 | 222.02 | 325.06 | 150.50 | 174.56 | 0.00 | 0.00 |
| May | 518.85 | 126.72 | 294.51 | 115.66 | 178.85 | 0.00 | 0.00 |
| June | 578.90 | 56.89 | 274.94 | 104.32 | 170.62 | 0.00 | 0.00 |
| July | 541.99 | 46.69 | 256.07 | 89.53 | 166.54 | 0.00 | 0.00 |
| August | 550.29 | 75.18 | 276.57 | 111.82 | 164.75 | 0.00 | 0.00 |
| September | 631.95 | 157.78 | 346.85 | 186.26 | 160.59 | 0.00 | 0.00 |
| October | 595.86 | 265.72 | 391.01 | 251.52 | 139.49 | 0.00 | 0.00 |
| November | 537.24 | 415.34 | 420.03 | 302.34 | 117.68 | 0.00 | 0.00 |
| December | 452.67 | 491.40 | 394.69 | 276.81 | 117.89 | 0.00 | 0.00 |
| Annual Sum or Average | 528.43 | 255.24 | 343.88 | 193.59 | 150.29 | 0.00 | 0.00 |
| Minimum of Months | 452.67 | 46.69 | 256.07 | 89.53 | 114.43 | 0.00 | 0.00 |
| Maximum of Months | 631.95 | 491.40 | 420.03 | 302.34 | 178.85 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1862.49 | 1272.49 | 1415.22 | 1072.18 | 343.04 | 0.00 | 0.00 |
| February | 1759.51 | 1147.15 | 1312.77 | 925.48 | 387.29 | 0.00 | 0.00 |
| March | 1468.14 | 1013.60 | 1066.90 | 615.17 | 451.73 | 0.00 | 0.00 |
| April | 1152.74 | 625.38 | 723.35 | 269.90 | 453.45 | 0.00 | 0.00 |
| May | 939.71 | 340.99 | 511.19 | 71.55 | 439.64 | 0.00 | 0.00 |
| June | 1048.56 | 145.39 | 441.03 | 27.98 | 413.04 | 0.00 | 0.00 |
| July | 1089.15 | 109.45 | 449.58 | 41.68 | 407.90 | 0.00 | 0.00 |
| August | 1252.54 | 184.39 | 573.09 | 151.70 | 421.39 | 0.00 | 0.00 |
| September | 1707.60 | 409.65 | 894.52 | 464.74 | 429.79 | 0.00 | 0.00 |
| October | 1927.74 | 716.61 | 1215.39 | 821.69 | 393.71 | 0.00 | 0.00 |
| November | 2018.75 | 1141.91 | 1462.61 | 1115.06 | 347.55 | 0.00 | 0.00 |
| December | 1858.32 | 1367.02 | 1449.51 | 1088.07 | 361.44 | 0.00 | 0.00 |
| Annual Sum or Average | 1505.31 | 703.92 | 957.56 | 553.33 | 404.23 | 0.00 | 0.00 |
| Minimum of Months | 939.71 | 109.45 | 441.03 | 27.98 | 343.04 | 0.00 | 0.00 |
| Maximum of Months | 2018.75 | 1367.02 | 1462.61 | 1115.06 | 453.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 33.91 | 77.41 | 32.99 | 18.58 | 14.41 | 0.00 | 0.00 |
| February | 41.41 | 69.90 | 37.23 | 19.79 | 17.44 | 0.00 | 0.00 |
| March | 62.99 | 59.81 | 50.73 | 27.19 | 23.54 | 0.00 | 0.00 |
| April | 87.95 | 35.31 | 58.31 | 31.49 | 26.82 | 0.00 | 0.00 |
| May | 108.67 | 19.77 | 62.81 | 33.60 | 29.20 | 0.00 | 0.00 |
| June | 122.54 | 8.96 | 61.14 | 32.84 | 28.30 | 0.00 | 0.00 |
| July | 110.13 | 6.62 | 54.25 | 26.96 | 27.29 | 0.00 | 0.00 |
| August | 101.36 | 10.42 | 52.54 | 26.78 | 25.76 | 0.00 | 0.00 |
| September | 95.61 | 22.99 | 53.73 | 29.93 | 23.80 | 0.00 | 0.00 |
| October | 68.60 | 41.14 | 46.25 | 27.00 | 19.26 | 0.00 | 0.00 |
| November | 45.46 | 69.94 | 38.82 | 23.64 | 15.18 | 0.00 | 0.00 |
| December | 30.32 | 84.58 | 31.29 | 17.00 | 14.29 | 0.00 | 0.00 |
| Annual Sum or Average | 75.90 | 42.10 | 48.38 | 26.25 | 22.13 | 0.00 | 0.00 |
| Minimum of Months | 30.32 | 6.62 | 31.29 | 17.00 | 14.29 | 0.00 | 0.00 |
| Maximum of Months | 122.54 | 84.58 | 62.81 | 33.60 | 29.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 96.50 | 448.53 | 134.04 | 55.74 | 78.30 | 0.00 | 0.00 |
| February | 135.15 | 399.87 | 154.65 | 59.36 | 95.29 | 0.00 | 0.00 |
| March | 221.00 | 345.43 | 209.40 | 81.57 | 127.83 | 0.00 | 0.00 |
| April | 340.87 | 207.23 | 240.66 | 95.05 | 145.61 | 0.00 | 0.00 |
| May | 464.32 | 114.13 | 267.86 | 107.49 | 160.37 | 0.00 | 0.00 |
| June | 574.02 | 51.76 | 269.47 | 110.81 | 158.66 | 0.00 | 0.00 |
| July | 515.83 | 42.41 | 240.78 | 89.59 | 151.20 | 0.00 | 0.00 |
| August | 442.98 | 66.20 | 221.73 | 81.81 | 139.92 | 0.00 | 0.00 |
| September | 387.16 | 144.81 | 216.85 | 89.82 | 127.03 | 0.00 | 0.00 |
| October | 247.73 | 253.99 | 185.12 | 80.99 | 104.13 | 0.00 | 0.00 |
| November | 134.75 | 415.97 | 153.79 | 70.92 | 82.87 | 0.00 | 0.00 |
| December | 80.20 | 502.48 | 128.46 | 50.99 | 77.47 | 0.00 | 0.00 |
| Annual Sum or Average | 304.15 | 248.65 | 202.09 | 81.24 | 120.85 | 0.00 | 0.00 |
| Minimum of Months | 80.20 | 42.41 | 128.46 | 50.99 | 77.47 | 0.00 | 0.00 |
| Maximum of Months | 574.02 | 502.48 | 269.47 | 110.81 | 160.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 5.88 | 1351.83 | 156.74 | 0.00 | 156.74 | 0.00 | 0.00 |
| February | 50.39 | 1190.06 | 192.39 | 0.00 | 192.39 | 0.00 | 0.00 |
| March | 123.17 | 1013.10 | 257.79 | 0.00 | 257.79 | 0.00 | 0.00 |
| April | 333.97 | 566.07 | 294.66 | 2.19 | 292.47 | 0.00 | 0.00 |
| May | 637.15 | 279.48 | 353.21 | 27.43 | 325.78 | 0.00 | 0.00 |
| June | 989.33 | 117.94 | 383.07 | 52.10 | 330.97 | 0.00 | 0.00 |
| July | 922.88 | 86.57 | 345.12 | 35.79 | 309.34 | 0.00 | 0.00 |
| August | 705.45 | 143.41 | 285.65 | 6.01 | 279.64 | 0.00 | 0.00 |
| September | 477.34 | 351.33 | 249.23 | 0.08 | 249.15 | 0.00 | 0.00 |
| October | 189.54 | 684.14 | 207.78 | 0.00 | 207.78 | 0.00 | 0.00 |
| November | 18.62 | 1219.33 | 167.11 | 0.00 | 167.11 | 0.00 | 0.00 |
| December | 4.53 | 1511.05 | 154.30 | 0.00 | 154.30 | 0.00 | 0.00 |
| Annual Sum or Average | 373.25 | 707.18 | 254.21 | 10.35 | 243.86 | 0.00 | 0.00 |
| Minimum of Months | 4.53 | 86.57 | 154.30 | 0.00 | 154.30 | 0.00 | 0.00 |
| Maximum of Months | 989.33 | 1511.05 | 383.07 | 52.10 | 330.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 459.38 | 445.98 | 383.97 | 277.97 | 106.00 | 0.00 | 0.00 |
| February | 462.82 | 400.30 | 373.57 | 251.00 | 122.57 | 0.00 | 0.00 |
| March | 473.76 | 349.98 | 361.52 | 209.22 | 152.30 | 0.00 | 0.00 |
| April | 484.31 | 216.21 | 310.95 | 150.50 | 160.45 | 0.00 | 0.00 |
| May | 500.78 | 120.86 | 279.30 | 115.66 | 163.64 | 0.00 | 0.00 |
| June | 562.80 | 53.03 | 260.31 | 104.32 | 155.99 | 0.00 | 0.00 |
| July | 523.57 | 43.25 | 241.34 | 89.53 | 151.81 | 0.00 | 0.00 |
| August | 532.39 | 71.07 | 262.27 | 111.82 | 150.45 | 0.00 | 0.00 |
| September | 615.42 | 152.00 | 333.88 | 186.25 | 147.64 | 0.00 | 0.00 |
| October | 582.41 | 260.35 | 380.07 | 251.28 | 128.79 | 0.00 | 0.00 |
| November | 527.56 | 411.67 | 409.57 | 301.12 | 108.45 | 0.00 | 0.00 |
| December | 443.11 | 487.01 | 384.01 | 274.99 | 109.02 | 0.00 | 0.00 |
| Annual Sum or Average | 514.08 | 250.22 | 331.42 | 193.26 | 138.17 | 0.00 | 0.00 |
| Minimum of Months | 443.11 | 43.25 | 241.34 | 89.53 | 106.00 | 0.00 | 0.00 |
| Maximum of Months | 615.42 | 487.01 | 409.57 | 301.12 | 163.64 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1752.28 | 1248.12 | 1326.01 | 1038.94 | 287.06 | 0.00 | 0.00 |
| February | 1649.39 | 1117.07 | 1225.57 | 902.98 | 322.58 | 0.00 | 0.00 |
| March | 1360.27 | 979.48 | 982.80 | 606.16 | 376.63 | 0.00 | 0.00 |
| April | 1047.40 | 590.46 | 635.30 | 267.63 | 367.67 | 0.00 | 0.00 |
| May | 831.07 | 306.12 | 419.10 | 71.16 | 347.94 | 0.00 | 0.00 |
| June | 953.90 | 122.69 | 353.01 | 27.87 | 325.14 | 0.00 | 0.00 |
| July | 980.47 | 90.68 | 360.68 | 41.48 | 319.20 | 0.00 | 0.00 |
| August | 1144.05 | 160.71 | 485.40 | 150.53 | 334.86 | 0.00 | 0.00 |
| September | 1594.95 | 374.07 | 809.81 | 459.27 | 350.54 | 0.00 | 0.00 |
| October | 1815.06 | 683.50 | 1132.01 | 805.82 | 326.19 | 0.00 | 0.00 |
| November | 1906.61 | 1123.19 | 1367.09 | 1079.67 | 287.42 | 0.00 | 0.00 |
| December | 1732.95 | 1349.79 | 1341.13 | 1039.31 | 301.83 | 0.00 | 0.00 |
| Annual Sum or Average | 1395.53 | 676.60 | 867.76 | 538.83 | 328.93 | 0.00 | 0.00 |
| Minimum of Months | 831.07 | 90.68 | 353.01 | 27.87 | 287.06 | 0.00 | 0.00 |
| Maximum of Months | 1906.61 | 1349.79 | 1367.09 | 1079.67 | 376.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 33.96 | 77.25 | 32.99 | 18.58 | 14.41 | 0.00 | 0.00 |
| February | 41.44 | 69.87 | 37.23 | 19.79 | 17.44 | 0.00 | 0.00 |
| March | 62.99 | 59.85 | 50.73 | 27.19 | 23.54 | 0.00 | 0.00 |
| April | 87.95 | 35.33 | 58.31 | 31.49 | 26.82 | 0.00 | 0.00 |
| May | 108.68 | 19.77 | 62.81 | 33.60 | 29.20 | 0.00 | 0.00 |
| June | 122.57 | 8.95 | 61.14 | 32.84 | 28.30 | 0.00 | 0.00 |
| July | 110.21 | 6.57 | 54.25 | 26.96 | 27.29 | 0.00 | 0.00 |
| August | 101.44 | 10.37 | 52.54 | 26.78 | 25.76 | 0.00 | 0.00 |
| September | 95.64 | 22.96 | 53.73 | 29.93 | 23.80 | 0.00 | 0.00 |
| October | 68.62 | 41.11 | 46.25 | 27.00 | 19.26 | 0.00 | 0.00 |
| November | 45.49 | 69.84 | 38.82 | 23.64 | 15.18 | 0.00 | 0.00 |
| December | 30.37 | 84.39 | 31.29 | 17.00 | 14.29 | 0.00 | 0.00 |
| Annual Sum or Average | 75.93 | 42.05 | 48.38 | 26.25 | 22.13 | 0.00 | 0.00 |
| Minimum of Months | 30.37 | 6.57 | 31.29 | 17.00 | 14.29 | 0.00 | 0.00 |
| Maximum of Months | 122.57 | 84.39 | 62.81 | 33.60 | 29.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 96.97 | 448.37 | 134.61 | 55.74 | 78.87 | 0.00 | 0.00 |
| February | 135.73 | 399.99 | 155.34 | 59.36 | 95.98 | 0.00 | 0.00 |
| March | 221.78 | 345.74 | 210.22 | 81.57 | 128.65 | 0.00 | 0.00 |
| April | 341.92 | 207.58 | 241.63 | 95.05 | 146.58 | 0.00 | 0.00 |
| May | 465.58 | 114.51 | 268.91 | 107.50 | 161.41 | 0.00 | 0.00 |
| June | 575.16 | 52.00 | 270.47 | 110.81 | 159.67 | 0.00 | 0.00 |
| July | 517.31 | 42.50 | 241.88 | 89.64 | 152.24 | 0.00 | 0.00 |
| August | 444.34 | 66.30 | 222.76 | 81.84 | 140.92 | 0.00 | 0.00 |
| September | 388.30 | 145.11 | 217.74 | 89.82 | 127.92 | 0.00 | 0.00 |
| October | 248.56 | 254.21 | 185.85 | 80.99 | 104.86 | 0.00 | 0.00 |
| November | 135.21 | 415.94 | 154.38 | 70.92 | 83.46 | 0.00 | 0.00 |
| December | 80.58 | 502.29 | 129.04 | 50.99 | 78.05 | 0.00 | 0.00 |
| Annual Sum or Average | 305.06 | 248.80 | 202.92 | 81.25 | 121.67 | 0.00 | 0.00 |
| Minimum of Months | 80.58 | 42.50 | 129.04 | 50.99 | 78.05 | 0.00 | 0.00 |
| Maximum of Months | 575.16 | 502.29 | 270.47 | 110.81 | 161.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 6.47 | 1350.05 | 159.53 | 0.00 | 159.53 | 0.00 | 0.00 |
| February | 52.22 | 1189.89 | 195.74 | 0.00 | 195.74 | 0.00 | 0.00 |
| March | 126.37 | 1013.87 | 261.83 | 0.00 | 261.83 | 0.00 | 0.00 |
| April | 338.87 | 567.43 | 299.46 | 2.23 | 297.23 | 0.00 | 0.00 |
| May | 644.46 | 281.35 | 358.95 | 27.85 | 331.10 | 0.00 | 0.00 |
| June | 996.36 | 119.14 | 388.79 | 52.66 | 336.14 | 0.00 | 0.00 |
| July | 931.16 | 87.20 | 351.01 | 36.41 | 314.60 | 0.00 | 0.00 |
| August | 712.12 | 144.18 | 290.65 | 6.12 | 284.53 | 0.00 | 0.00 |
| September | 482.89 | 352.88 | 253.57 | 0.08 | 253.49 | 0.00 | 0.00 |
| October | 193.28 | 685.10 | 211.34 | 0.00 | 211.34 | 0.00 | 0.00 |
| November | 19.68 | 1218.64 | 170.03 | 0.00 | 170.03 | 0.00 | 0.00 |
| December | 4.97 | 1509.48 | 157.13 | 0.00 | 157.13 | 0.00 | 0.00 |
| Annual Sum or Average | 377.48 | 707.58 | 258.46 | 10.49 | 247.97 | 0.00 | 0.00 |
| Minimum of Months | 4.97 | 87.20 | 157.13 | 0.00 | 157.13 | 0.00 | 0.00 |
| Maximum of Months | 996.36 | 1509.48 | 388.79 | 52.66 | 336.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 459.51 | 447.62 | 384.81 | 278.12 | 106.69 | 0.00 | 0.00 |
| February | 463.09 | 402.00 | 374.43 | 251.08 | 123.35 | 0.00 | 0.00 |
| March | 474.38 | 351.37 | 362.45 | 209.22 | 153.23 | 0.00 | 0.00 |
| April | 485.31 | 217.09 | 312.03 | 150.50 | 161.53 | 0.00 | 0.00 |
| May | 501.97 | 121.54 | 280.46 | 115.66 | 164.80 | 0.00 | 0.00 |
| June | 563.83 | 53.46 | 261.43 | 104.32 | 157.11 | 0.00 | 0.00 |
| July | 524.44 | 43.86 | 242.47 | 89.53 | 152.94 | 0.00 | 0.00 |
| August | 533.24 | 71.84 | 263.36 | 111.82 | 151.54 | 0.00 | 0.00 |
| September | 616.47 | 152.76 | 334.88 | 186.25 | 148.63 | 0.00 | 0.00 |
| October | 583.25 | 261.11 | 380.92 | 251.31 | 129.61 | 0.00 | 0.00 |
| November | 527.95 | 412.54 | 410.50 | 301.31 | 109.19 | 0.00 | 0.00 |
| December | 443.22 | 488.76 | 385.12 | 275.36 | 109.76 | 0.00 | 0.00 |
| Annual Sum or Average | 514.78 | 251.23 | 332.43 | 193.32 | 139.10 | 0.00 | 0.00 |
| Minimum of Months | 443.22 | 43.86 | 242.47 | 89.53 | 106.69 | 0.00 | 0.00 |
| Maximum of Months | 616.47 | 488.76 | 410.50 | 301.31 | 164.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1755.39 | 1254.52 | 1331.53 | 1041.16 | 290.37 | 0.00 | 0.00 |
| February | 1650.97 | 1124.26 | 1229.49 | 903.42 | 326.07 | 0.00 | 0.00 |
| March | 1363.39 | 985.27 | 986.87 | 606.19 | 380.68 | 0.00 | 0.00 |
| April | 1051.44 | 594.76 | 640.03 | 267.63 | 372.40 | 0.00 | 0.00 |
| May | 835.39 | 309.61 | 424.20 | 71.16 | 353.04 | 0.00 | 0.00 |
| June | 957.14 | 124.95 | 357.91 | 27.87 | 330.04 | 0.00 | 0.00 |
| July | 982.24 | 93.54 | 365.62 | 41.48 | 324.14 | 0.00 | 0.00 |
| August | 1145.91 | 164.47 | 490.19 | 150.54 | 339.65 | 0.00 | 0.00 |
| September | 1598.82 | 378.28 | 814.16 | 459.28 | 354.89 | 0.00 | 0.00 |
| October | 1818.72 | 687.70 | 1135.94 | 806.12 | 329.82 | 0.00 | 0.00 |
| November | 1910.37 | 1127.06 | 1372.46 | 1081.57 | 290.89 | 0.00 | 0.00 |
| December | 1738.02 | 1355.94 | 1349.87 | 1044.26 | 305.60 | 0.00 | 0.00 |
| Annual Sum or Average | 1398.82 | 681.13 | 872.80 | 539.65 | 333.15 | 0.00 | 0.00 |
| Minimum of Months | 835.39 | 93.54 | 357.91 | 27.87 | 290.37 | 0.00 | 0.00 |
| Maximum of Months | 1910.37 | 1355.94 | 1372.46 | 1081.57 | 380.68 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 33.75 | 78.21 | 32.99 | 18.58 | 14.41 | 0.00 | 0.00 |
| February | 41.18 | 70.74 | 37.23 | 19.79 | 17.44 | 0.00 | 0.00 |
| March | 62.75 | 60.47 | 50.73 | 27.19 | 23.54 | 0.00 | 0.00 |
| April | 87.78 | 35.63 | 58.31 | 31.49 | 26.82 | 0.00 | 0.00 |
| May | 108.52 | 19.95 | 62.81 | 33.60 | 29.20 | 0.00 | 0.00 |
| June | 122.39 | 9.07 | 61.14 | 32.84 | 28.30 | 0.00 | 0.00 |
| July | 109.82 | 6.81 | 54.25 | 26.96 | 27.29 | 0.00 | 0.00 |
| August | 101.06 | 10.68 | 52.54 | 26.78 | 25.76 | 0.00 | 0.00 |
| September | 95.47 | 23.21 | 53.73 | 29.93 | 23.80 | 0.00 | 0.00 |
| October | 68.50 | 41.40 | 46.25 | 27.00 | 19.26 | 0.00 | 0.00 |
| November | 45.36 | 70.46 | 38.82 | 23.64 | 15.18 | 0.00 | 0.00 |
| December | 30.14 | 85.47 | 31.29 | 17.00 | 14.29 | 0.00 | 0.00 |
| Annual Sum or Average | 75.71 | 42.53 | 48.38 | 26.25 | 22.13 | 0.00 | 0.00 |
| Minimum of Months | 30.14 | 6.81 | 31.29 | 17.00 | 14.29 | 0.00 | 0.00 |
| Maximum of Months | 122.39 | 85.47 | 62.81 | 33.60 | 29.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 101.89 | 451.25 | 141.76 | 55.74 | 86.02 | 0.00 | 0.00 |
| February | 142.44 | 403.93 | 163.93 | 59.36 | 104.57 | 0.00 | 0.00 |
| March | 231.60 | 349.94 | 220.56 | 81.57 | 138.99 | 0.00 | 0.00 |
| April | 355.01 | 212.17 | 253.87 | 95.10 | 158.77 | 0.00 | 0.00 |
| May | 480.90 | 119.80 | 282.05 | 107.58 | 174.47 | 0.00 | 0.00 |
| June | 588.37 | 55.61 | 282.97 | 110.77 | 172.20 | 0.00 | 0.00 |
| July | 532.27 | 45.43 | 254.77 | 89.84 | 164.94 | 0.00 | 0.00 |
| August | 458.73 | 69.92 | 235.21 | 81.92 | 153.29 | 0.00 | 0.00 |
| September | 401.84 | 150.06 | 228.90 | 89.83 | 139.07 | 0.00 | 0.00 |
| October | 258.67 | 258.11 | 194.98 | 80.99 | 113.99 | 0.00 | 0.00 |
| November | 140.36 | 418.70 | 161.85 | 70.92 | 90.93 | 0.00 | 0.00 |
| December | 84.28 | 505.37 | 136.31 | 50.99 | 85.33 | 0.00 | 0.00 |
| Annual Sum or Average | 315.49 | 252.60 | 213.30 | 81.28 | 132.01 | 0.00 | 0.00 |
| Minimum of Months | 84.28 | 45.43 | 136.31 | 50.99 | 85.33 | 0.00 | 0.00 |
| Maximum of Months | 588.37 | 505.37 | 282.97 | 110.77 | 174.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 14.30 | 893.60 | 136.61 | 0.00 | 136.61 | 0.00 | 0.00 |
| February | 56.37 | 795.60 | 166.82 | 0.00 | 166.82 | 0.00 | 0.00 |
| March | 122.32 | 682.74 | 218.31 | 0.00 | 218.31 | 0.00 | 0.00 |
| April | 279.14 | 391.33 | 252.07 | 1.99 | 250.08 | 0.00 | 0.00 |
| May | 500.39 | 207.30 | 298.96 | 21.62 | 277.34 | 0.00 | 0.00 |
| June | 729.17 | 93.65 | 317.89 | 39.14 | 278.76 | 0.00 | 0.00 |
| July | 692.54 | 69.76 | 293.80 | 28.60 | 265.20 | 0.00 | 0.00 |
| August | 535.89 | 109.43 | 247.73 | 5.07 | 242.67 | 0.00 | 0.00 |
| September | 377.81 | 254.78 | 216.17 | 0.09 | 216.08 | 0.00 | 0.00 |
| October | 169.74 | 469.27 | 179.48 | 0.00 | 179.48 | 0.00 | 0.00 |
| November | 26.89 | 810.97 | 144.89 | 0.00 | 144.89 | 0.00 | 0.00 |
| December | 9.13 | 1001.93 | 135.56 | 0.00 | 135.56 | 0.00 | 0.00 |
| Annual Sum or Average | 294.09 | 480.15 | 217.60 | 8.08 | 209.52 | 0.00 | 0.00 |
| Minimum of Months | 9.13 | 69.76 | 135.56 | 0.00 | 135.56 | 0.00 | 0.00 |
| Maximum of Months | 729.17 | 1001.93 | 317.89 | 39.14 | 278.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 5.11 | 493.74 | 70.26 | 0.00 | 70.26 | 0.00 | 0.00 |
| February | 24.81 | 440.86 | 85.79 | 0.00 | 85.79 | 0.00 | 0.00 |
| March | 57.66 | 376.77 | 112.27 | 0.00 | 112.27 | 0.00 | 0.00 |
| April | 139.05 | 214.36 | 129.63 | 1.02 | 128.61 | 0.00 | 0.00 |
| May | 253.58 | 113.04 | 153.75 | 11.12 | 142.63 | 0.00 | 0.00 |
| June | 371.27 | 52.34 | 163.49 | 20.13 | 143.36 | 0.00 | 0.00 |
| July | 344.13 | 41.84 | 151.09 | 14.71 | 136.39 | 0.00 | 0.00 |
| August | 262.37 | 64.97 | 127.40 | 2.61 | 124.80 | 0.00 | 0.00 |
| September | 190.63 | 139.46 | 111.17 | 0.04 | 111.13 | 0.00 | 0.00 |
| October | 84.41 | 253.90 | 92.30 | 0.00 | 92.30 | 0.00 | 0.00 |
| November | 11.70 | 444.06 | 74.52 | 0.00 | 74.52 | 0.00 | 0.00 |
| December | 3.26 | 549.98 | 69.71 | 0.00 | 69.71 | 0.00 | 0.00 |
| Annual Sum or Average | 146.30 | 264.58 | 111.91 | 4.16 | 107.75 | 0.00 | 0.00 |
| Minimum of Months | 3.26 | 41.84 | 69.71 | 0.00 | 69.71 | 0.00 | 0.00 |
| Maximum of Months | 371.27 | 549.98 | 163.49 | 20.13 | 143.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 41.29 | 225.09 | 54.78 | 24.76 | 30.02 | 0.00 | 0.00 |
| February | 73.83 | 204.17 | 74.61 | 36.46 | 38.15 | 0.00 | 0.00 |
| March | 144.47 | 178.74 | 120.22 | 65.61 | 54.61 | 0.00 | 0.00 |
| April | 229.94 | 105.11 | 150.49 | 86.39 | 64.10 | 0.00 | 0.00 |
| May | 282.99 | 58.30 | 160.26 | 90.73 | 69.53 | 0.00 | 0.00 |
| June | 324.66 | 26.90 | 156.44 | 88.65 | 67.79 | 0.00 | 0.00 |
| July | 282.88 | 21.20 | 136.12 | 71.82 | 64.30 | 0.00 | 0.00 |
| August | 267.68 | 31.59 | 135.92 | 74.74 | 61.18 | 0.00 | 0.00 |
| September | 244.52 | 65.70 | 134.41 | 78.29 | 56.12 | 0.00 | 0.00 |
| October | 144.08 | 117.69 | 99.00 | 56.06 | 42.95 | 0.00 | 0.00 |
| November | 67.71 | 204.51 | 68.74 | 36.45 | 32.29 | 0.00 | 0.00 |
| December | 31.37 | 243.03 | 49.17 | 19.92 | 29.25 | 0.00 | 0.00 |
| Annual Sum or Average | 178.38 | 123.09 | 111.81 | 60.90 | 50.91 | 0.00 | 0.00 |
| Minimum of Months | 31.37 | 21.20 | 49.17 | 19.92 | 29.25 | 0.00 | 0.00 |
| Maximum of Months | 324.66 | 243.03 | 160.26 | 90.73 | 69.53 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 699.26 | 409.55 | 507.34 | 384.37 | 122.98 | 0.00 | 0.00 |
| February | 660.65 | 371.33 | 470.62 | 331.78 | 138.84 | 0.00 | 0.00 |
| March | 548.54 | 332.54 | 382.48 | 220.53 | 161.94 | 0.00 | 0.00 |
| April | 415.90 | 215.80 | 259.32 | 96.76 | 162.56 | 0.00 | 0.00 |
| May | 326.97 | 128.47 | 183.26 | 25.65 | 157.61 | 0.00 | 0.00 |
| June | 352.19 | 63.91 | 158.10 | 10.03 | 148.07 | 0.00 | 0.00 |
| July | 359.28 | 52.80 | 161.17 | 14.94 | 146.23 | 0.00 | 0.00 |
| August | 427.31 | 77.83 | 205.45 | 54.38 | 151.06 | 0.00 | 0.00 |
| September | 601.10 | 154.83 | 320.68 | 166.60 | 154.08 | 0.00 | 0.00 |
| October | 693.85 | 246.85 | 435.71 | 294.57 | 141.14 | 0.00 | 0.00 |
| November | 744.49 | 380.66 | 524.34 | 399.74 | 124.59 | 0.00 | 0.00 |
| December | 701.79 | 440.16 | 519.64 | 390.06 | 129.57 | 0.00 | 0.00 |
| Annual Sum or Average | 543.49 | 238.87 | 343.28 | 198.37 | 144.91 | 0.00 | 0.00 |
| Minimum of Months | 326.97 | 52.80 | 158.10 | 10.03 | 122.98 | 0.00 | 0.00 |
| Maximum of Months | 744.49 | 440.16 | 524.34 | 399.74 | 162.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 60.07 | 246.17 | 69.53 | 34.47 | 35.06 | 0.00 | 0.00 |
| February | 94.32 | 224.16 | 90.46 | 46.27 | 44.19 | 0.00 | 0.00 |
| March | 169.09 | 199.00 | 139.93 | 77.31 | 62.61 | 0.00 | 0.00 |
| April | 250.92 | 126.05 | 170.24 | 97.50 | 72.73 | 0.00 | 0.00 |
| May | 301.24 | 76.77 | 180.18 | 101.49 | 78.70 | 0.00 | 0.00 |
| June | 340.88 | 39.09 | 175.70 | 99.07 | 76.63 | 0.00 | 0.00 |
| July | 300.50 | 31.44 | 153.12 | 80.29 | 72.83 | 0.00 | 0.00 |
| August | 286.13 | 44.15 | 153.38 | 83.98 | 69.40 | 0.00 | 0.00 |
| September | 265.15 | 87.24 | 153.90 | 89.97 | 63.93 | 0.00 | 0.00 |
| October | 166.45 | 141.80 | 118.39 | 68.79 | 49.60 | 0.00 | 0.00 |
| November | 89.77 | 228.22 | 86.12 | 48.55 | 37.58 | 0.00 | 0.00 |
| December | 47.49 | 267.79 | 62.86 | 28.59 | 34.27 | 0.00 | 0.00 |
| Annual Sum or Average | 198.09 | 142.23 | 129.62 | 71.43 | 58.19 | 0.00 | 0.00 |
| Minimum of Months | 47.49 | 31.44 | 62.86 | 28.59 | 34.27 | 0.00 | 0.00 |
| Maximum of Months | 340.88 | 267.79 | 180.18 | 101.49 | 78.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 901.54 | 988.52 | 779.97 | 543.74 | 236.23 | 0.00 | 0.00 |
| February | 983.41 | 900.30 | 813.46 | 533.88 | 279.58 | 0.00 | 0.00 |
| March | 976.58 | 783.69 | 784.87 | 443.27 | 341.60 | 0.00 | 0.00 |
| April | 1045.64 | 479.68 | 722.97 | 349.03 | 373.95 | 0.00 | 0.00 |
| May | 1085.01 | 285.89 | 652.85 | 273.07 | 379.77 | 0.00 | 0.00 |
| June | 1243.01 | 145.49 | 625.30 | 261.74 | 363.56 | 0.00 | 0.00 |
| July | 1159.57 | 123.33 | 582.19 | 227.75 | 354.44 | 0.00 | 0.00 |
| August | 1163.17 | 176.51 | 611.55 | 256.88 | 354.67 | 0.00 | 0.00 |
| September | 1287.86 | 336.42 | 735.34 | 401.48 | 333.87 | 0.00 | 0.00 |
| October | 1145.36 | 566.58 | 774.51 | 483.67 | 290.84 | 0.00 | 0.00 |
| November | 1038.91 | 896.12 | 842.12 | 594.69 | 247.43 | 0.00 | 0.00 |
| December | 878.92 | 1063.61 | 793.37 | 547.17 | 246.20 | 0.00 | 0.00 |
| Annual Sum or Average | 1075.65 | 560.47 | 725.77 | 408.76 | 317.01 | 0.00 | 0.00 |
| Minimum of Months | 878.92 | 123.33 | 582.19 | 227.75 | 236.23 | 0.00 | 0.00 |
| Maximum of Months | 1287.86 | 1063.61 | 842.12 | 594.69 | 379.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 569.17 | 989.25 | 579.41 | 374.95 | 204.46 | 0.00 | 0.00 |
| February | 852.36 | 911.91 | 775.02 | 518.21 | 256.81 | 0.00 | 0.00 |
| March | 1246.11 | 801.94 | 1026.93 | 678.26 | 348.68 | 0.00 | 0.00 |
| April | 1785.32 | 527.03 | 1283.99 | 889.27 | 394.72 | 0.00 | 0.00 |
| May | 2103.74 | 350.64 | 1387.77 | 961.02 | 426.75 | 0.00 | 0.00 |
| June | 2369.54 | 194.97 | 1447.67 | 1045.45 | 402.22 | 0.00 | 0.00 |
| July | 2094.21 | 156.98 | 1264.08 | 849.45 | 414.63 | 0.00 | 0.00 |
| August | 1910.10 | 211.65 | 1182.33 | 788.91 | 393.42 | 0.00 | 0.00 |
| September | 1723.21 | 358.92 | 1108.94 | 776.60 | 332.34 | 0.00 | 0.00 |
| October | 1139.76 | 566.27 | 835.60 | 562.78 | 272.82 | 0.00 | 0.00 |
| November | 741.00 | 890.02 | 681.65 | 472.22 | 209.43 | 0.00 | 0.00 |
| December | 494.50 | 1075.66 | 552.64 | 341.40 | 211.24 | 0.00 | 0.00 |
| Annual Sum or Average | 1421.16 | 584.62 | 1011.12 | 688.43 | 322.69 | 0.00 | 0.00 |
| Minimum of Months | 494.50 | 156.98 | 552.64 | 341.40 | 204.46 | 0.00 | 0.00 |
| Maximum of Months | 2369.54 | 1075.66 | 1447.67 | 1045.45 | 426.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 67.26 | 251.24 | 83.52 | 45.30 | 38.21 | 0.00 | 0.00 |
| February | 110.56 | 217.48 | 111.74 | 63.69 | 48.05 | 0.00 | 0.00 |
| March | 154.30 | 179.85 | 137.96 | 76.01 | 61.95 | 0.00 | 0.00 |
| April | 234.51 | 106.18 | 166.23 | 92.22 | 74.01 | 0.00 | 0.00 |
| May | 282.64 | 65.82 | 171.54 | 93.23 | 78.32 | 0.00 | 0.00 |
| June | 327.02 | 36.51 | 171.64 | 95.48 | 76.15 | 0.00 | 0.00 |
| July | 293.20 | 31.05 | 153.92 | 80.47 | 73.45 | 0.00 | 0.00 |
| August | 268.23 | 40.83 | 146.46 | 74.96 | 71.51 | 0.00 | 0.00 |
| September | 243.83 | 73.15 | 145.11 | 82.79 | 62.31 | 0.00 | 0.00 |
| October | 149.48 | 123.57 | 111.60 | 60.23 | 51.37 | 0.00 | 0.00 |
| November | 97.38 | 210.13 | 100.04 | 58.24 | 41.80 | 0.00 | 0.00 |
| December | 61.60 | 273.18 | 83.44 | 44.21 | 39.23 | 0.00 | 0.00 |
| Annual Sum or Average | 191.11 | 133.70 | 131.95 | 72.20 | 59.75 | 0.00 | 0.00 |
| Minimum of Months | 61.60 | 31.05 | 83.44 | 44.21 | 38.21 | 0.00 | 0.00 |
| Maximum of Months | 327.02 | 273.18 | 171.64 | 95.48 | 78.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 97.60 | 890.95 | 233.57 | 84.95 | 148.62 | 0.00 | 0.00 |
| February | 198.34 | 785.29 | 303.61 | 119.42 | 184.19 | 0.00 | 0.00 |
| March | 324.16 | 679.93 | 382.28 | 142.52 | 239.76 | 0.00 | 0.00 |
| April | 559.17 | 421.33 | 453.52 | 173.64 | 279.88 | 0.00 | 0.00 |
| May | 773.58 | 269.17 | 486.00 | 183.85 | 302.15 | 0.00 | 0.00 |
| June | 983.28 | 152.75 | 496.41 | 197.22 | 299.19 | 0.00 | 0.00 |
| July | 884.35 | 124.06 | 449.43 | 163.55 | 285.88 | 0.00 | 0.00 |
| August | 759.95 | 163.08 | 413.36 | 142.81 | 270.55 | 0.00 | 0.00 |
| September | 633.41 | 309.26 | 394.06 | 155.27 | 238.79 | 0.00 | 0.00 |
| October | 347.67 | 498.75 | 310.59 | 112.93 | 197.66 | 0.00 | 0.00 |
| November | 156.85 | 797.11 | 269.36 | 109.20 | 160.16 | 0.00 | 0.00 |
| December | 77.96 | 984.10 | 232.70 | 82.90 | 149.81 | 0.00 | 0.00 |
| Annual Sum or Average | 484.27 | 504.97 | 368.90 | 138.97 | 229.93 | 0.00 | 0.00 |
| Minimum of Months | 77.96 | 124.06 | 232.70 | 82.90 | 148.62 | 0.00 | 0.00 |
| Maximum of Months | 983.28 | 984.10 | 496.41 | 197.22 | 302.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 127.42 | 997.51 | 271.08 | 103.57 | 167.51 | 0.00 | 0.00 |
| February | 255.61 | 884.89 | 359.52 | 150.78 | 208.74 | 0.00 | 0.00 |
| March | 412.42 | 764.40 | 459.81 | 187.29 | 272.53 | 0.00 | 0.00 |
| April | 722.94 | 455.88 | 560.06 | 238.41 | 321.65 | 0.00 | 0.00 |
| May | 981.11 | 272.54 | 603.16 | 255.33 | 347.83 | 0.00 | 0.00 |
| June | 1220.04 | 140.10 | 614.98 | 271.49 | 343.49 | 0.00 | 0.00 |
| July | 1101.38 | 116.66 | 554.97 | 226.16 | 328.81 | 0.00 | 0.00 |
| August | 944.19 | 165.31 | 508.20 | 196.95 | 311.26 | 0.00 | 0.00 |
| September | 789.35 | 316.06 | 481.37 | 208.63 | 272.74 | 0.00 | 0.00 |
| October | 432.43 | 545.66 | 370.35 | 145.91 | 224.43 | 0.00 | 0.00 |
| November | 198.04 | 901.75 | 313.29 | 133.11 | 180.18 | 0.00 | 0.00 |
| December | 99.80 | 1102.66 | 265.03 | 96.63 | 168.40 | 0.00 | 0.00 |
| Annual Sum or Average | 608.57 | 553.69 | 447.04 | 184.49 | 262.55 | 0.00 | 0.00 |
| Minimum of Months | 99.80 | 116.66 | 265.03 | 96.63 | 167.51 | 0.00 | 0.00 |
| Maximum of Months | 1220.04 | 1102.66 | 614.98 | 271.49 | 347.83 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.125651E+10 | 0.121099E+10 | 0.105178E+10 | 0.745292E+09 | 0.306490E+09 | 0.00 | 0.00 |
| February | 0.114803E+10 | 0.982212E+09 | 0.929303E+09 | 0.608278E+09 | 0.321026E+09 | 0.00 | 0.00 |
| March | 0.130746E+10 | 0.954010E+09 | 0.100069E+10 | 0.560434E+09 | 0.440260E+09 | 0.00 | 0.00 |
| April | 0.129785E+10 | 0.575472E+09 | 0.842545E+09 | 0.390091E+09 | 0.452454E+09 | 0.00 | 0.00 |
| May | 0.138970E+10 | 0.339401E+09 | 0.788811E+09 | 0.309784E+09 | 0.479027E+09 | 0.00 | 0.00 |
| June | 0.150051E+10 | 0.147451E+09 | 0.712643E+09 | 0.270391E+09 | 0.442251E+09 | 0.00 | 0.00 |
| July | 0.145166E+10 | 0.125059E+09 | 0.685852E+09 | 0.239794E+09 | 0.446058E+09 | 0.00 | 0.00 |
| August | 0.147389E+10 | 0.201371E+09 | 0.740754E+09 | 0.299488E+09 | 0.441266E+09 | 0.00 | 0.00 |
| September | 0.163802E+10 | 0.408968E+09 | 0.899031E+09 | 0.482773E+09 | 0.416258E+09 | 0.00 | 0.00 |
| October | 0.159596E+10 | 0.711703E+09 | 0.104728E+10 | 0.673676E+09 | 0.373604E+09 | 0.00 | 0.00 |
| November | 0.139253E+10 | 0.107657E+10 | 0.108871E+10 | 0.783669E+09 | 0.305039E+09 | 0.00 | 0.00 |
| December | 0.121242E+10 | 0.131616E+10 | 0.105715E+10 | 0.741399E+09 | 0.315747E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.166645E+11 | 0.804936E+10 | 0.108445E+11 | 0.610507E+10 | 0.473948E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.114803E+10 | 0.125059E+09 | 0.685852E+09 | 0.239794E+09 | 0.305039E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.163802E+10 | 0.131616E+10 | 0.108871E+10 | 0.783669E+09 | 0.479027E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.498849E+10 | 0.340824E+10 | 0.379052E+10 | 0.287171E+10 | 0.918805E+09 | 0.00 | 0.00 |
| February | 0.425661E+10 | 0.277519E+10 | 0.317586E+10 | 0.223893E+10 | 0.936928E+09 | 0.00 | 0.00 |
| March | 0.393227E+10 | 0.271483E+10 | 0.285758E+10 | 0.164768E+10 | 0.120991E+10 | 0.00 | 0.00 |
| April | 0.298791E+10 | 0.162098E+10 | 0.187493E+10 | 0.699585E+09 | 0.117535E+10 | 0.00 | 0.00 |
| May | 0.251691E+10 | 0.913306E+09 | 0.136916E+10 | 0.191638E+09 | 0.117752E+10 | 0.00 | 0.00 |
| June | 0.271788E+10 | 0.376855E+09 | 0.114314E+10 | 72532369.99 | 0.107060E+10 | 0.00 | 0.00 |
| July | 0.291719E+10 | 0.293162E+09 | 0.120415E+10 | 0.111626E+09 | 0.109252E+10 | 0.00 | 0.00 |
| August | 0.335481E+10 | 0.493879E+09 | 0.153495E+10 | 0.406311E+09 | 0.112864E+10 | 0.00 | 0.00 |
| September | 0.442609E+10 | 0.106182E+10 | 0.231860E+10 | 0.120459E+10 | 0.111401E+10 | 0.00 | 0.00 |
| October | 0.516327E+10 | 0.191936E+10 | 0.325531E+10 | 0.220081E+10 | 0.105450E+10 | 0.00 | 0.00 |
| November | 0.523260E+10 | 0.295984E+10 | 0.379110E+10 | 0.289024E+10 | 0.900851E+09 | 0.00 | 0.00 |
| December | 0.497733E+10 | 0.366142E+10 | 0.388236E+10 | 0.291428E+10 | 0.968084E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.474714E+11 | 0.221989E+11 | 0.301977E+11 | 0.174499E+11 | 0.127477E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.251691E+10 | 0.293162E+09 | 0.114314E+10 | 72532369.99 | 0.900851E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.523260E+10 | 0.366142E+10 | 0.388236E+10 | 0.291428E+10 | 0.120991E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 90832108.50 | 0.207323E+09 | 88363542.88 | 49763851.35 | 38599691.53 | 0.00 | 0.00 |
| February | 0.100190E+09 | 0.169098E+09 | 90059831.58 | 47868739.55 | 42191092.04 | 0.00 | 0.00 |
| March | 0.168719E+09 | 0.160182E+09 | 0.135875E+09 | 72824222.81 | 63050606.59 | 0.00 | 0.00 |
| April | 0.227959E+09 | 91517886.97 | 0.151139E+09 | 81632895.25 | 69506104.79 | 0.00 | 0.00 |
| May | 0.291049E+09 | 52938949.33 | 0.168217E+09 | 90003984.72 | 78213505.00 | 0.00 | 0.00 |
| June | 0.317632E+09 | 23230981.10 | 0.158465E+09 | 85112889.14 | 73351624.10 | 0.00 | 0.00 |
| July | 0.294977E+09 | 17723481.02 | 0.145314E+09 | 72209221.10 | 73104399.47 | 0.00 | 0.00 |
| August | 0.271489E+09 | 27899170.24 | 0.140729E+09 | 71720812.08 | 69008002.58 | 0.00 | 0.00 |
| September | 0.247815E+09 | 59600214.87 | 0.139275E+09 | 77590030.53 | 61684563.74 | 0.00 | 0.00 |
| October | 0.183734E+09 | 0.110188E+09 | 0.123889E+09 | 72305718.98 | 51583335.65 | 0.00 | 0.00 |
| November | 0.117835E+09 | 0.181278E+09 | 0.100632E+09 | 61274315.14 | 39357906.06 | 0.00 | 0.00 |
| December | 81221677.31 | 0.226552E+09 | 83797994.24 | 45521768.27 | 38276225.97 | 0.00 | 0.00 |
| Annual Sum or Average | 0.239345E+10 | 0.132753E+10 | 0.152576E+10 | 0.827828E+09 | 0.697927E+09 | 0.00 | 0.00 |
| Minimum of Months | 81221677.31 | 17723481.02 | 83797994.24 | 45521768.27 | 38276225.97 | 0.00 | 0.00 |
| Maximum of Months | 0.317632E+09 | 0.226552E+09 | 0.168217E+09 | 90003984.72 | 78213505.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.258471E+09 | 0.120135E+10 | 0.359006E+09 | 0.149291E+09 | 0.209715E+09 | 0.00 | 0.00 |
| February | 0.326946E+09 | 0.967371E+09 | 0.374136E+09 | 0.143606E+09 | 0.230530E+09 | 0.00 | 0.00 |
| March | 0.591924E+09 | 0.925198E+09 | 0.560846E+09 | 0.218472E+09 | 0.342374E+09 | 0.00 | 0.00 |
| April | 0.883547E+09 | 0.537150E+09 | 0.623790E+09 | 0.246370E+09 | 0.377420E+09 | 0.00 | 0.00 |
| May | 0.124364E+10 | 0.305689E+09 | 0.717436E+09 | 0.287913E+09 | 0.429523E+09 | 0.00 | 0.00 |
| June | 0.148786E+10 | 0.134163E+09 | 0.698465E+09 | 0.287210E+09 | 0.411256E+09 | 0.00 | 0.00 |
| July | 0.138160E+10 | 0.113595E+09 | 0.644916E+09 | 0.239947E+09 | 0.404969E+09 | 0.00 | 0.00 |
| August | 0.118647E+10 | 0.177318E+09 | 0.593885E+09 | 0.219133E+09 | 0.374752E+09 | 0.00 | 0.00 |
| September | 0.100351E+10 | 0.375342E+09 | 0.562085E+09 | 0.232825E+09 | 0.329260E+09 | 0.00 | 0.00 |
| October | 0.663510E+09 | 0.680286E+09 | 0.495821E+09 | 0.216916E+09 | 0.278905E+09 | 0.00 | 0.00 |
| November | 0.349285E+09 | 0.107819E+10 | 0.398622E+09 | 0.183822E+09 | 0.214799E+09 | 0.00 | 0.00 |
| December | 0.214799E+09 | 0.134585E+10 | 0.344073E+09 | 0.136565E+09 | 0.207508E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.959156E+10 | 0.784150E+10 | 0.637308E+10 | 0.256207E+10 | 0.381101E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.214799E+09 | 0.113595E+09 | 0.344073E+09 | 0.136565E+09 | 0.207508E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.148786E+10 | 0.134585E+10 | 0.717436E+09 | 0.287913E+09 | 0.429523E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 15762152.55 | 0.362075E+10 | 0.419806E+09 | 0.00 | 0.419806E+09 | 0.00 | 0.00 |
| February | 0.121911E+09 | 0.287898E+10 | 0.465419E+09 | 0.00 | 0.465419E+09 | 0.00 | 0.00 |
| March | 0.329904E+09 | 0.271347E+10 | 0.690466E+09 | 0.00 | 0.690466E+09 | 0.00 | 0.00 |
| April | 0.865659E+09 | 0.146726E+10 | 0.763767E+09 | 5677033.86 | 0.758090E+09 | 0.00 | 0.00 |
| May | 0.170655E+10 | 0.748564E+09 | 0.946050E+09 | 73471410.48 | 0.872579E+09 | 0.00 | 0.00 |
| June | 0.256434E+10 | 0.305699E+09 | 0.992924E+09 | 0.135054E+09 | 0.857871E+09 | 0.00 | 0.00 |
| July | 0.247185E+10 | 0.231881E+09 | 0.924373E+09 | 95850165.51 | 0.828523E+09 | 0.00 | 0.00 |
| August | 0.188949E+10 | 0.384120E+09 | 0.765093E+09 | 16099104.09 | 0.748994E+09 | 0.00 | 0.00 |
| September | 0.123726E+10 | 0.910643E+09 | 0.646001E+09 | 199631.40 | 0.645801E+09 | 0.00 | 0.00 |
| October | 0.507652E+09 | 0.183241E+10 | 0.556524E+09 | 0.00 | 0.556524E+09 | 0.00 | 0.00 |
| November | 48255086.85 | 0.316049E+10 | 0.433160E+09 | 0.00 | 0.433160E+09 | 0.00 | 0.00 |
| December | 12135487.48 | 0.404721E+10 | 0.413268E+09 | 0.00 | 0.413268E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117708E+11 | 0.223015E+11 | 0.801685E+10 | 0.326351E+09 | 0.769050E+10 | 0.00 | 0.00 |
| Minimum of Months | 12135487.48 | 0.231881E+09 | 0.413268E+09 | 0.00 | 0.413268E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.256434E+10 | 0.404721E+10 | 0.992924E+09 | 0.135054E+09 | 0.872579E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.123039E+10 | 0.119451E+10 | 0.102843E+10 | 0.744517E+09 | 0.283912E+09 | 0.00 | 0.00 |
| February | 0.111966E+10 | 0.968414E+09 | 0.903742E+09 | 0.607230E+09 | 0.296512E+09 | 0.00 | 0.00 |
| March | 0.126892E+10 | 0.937386E+09 | 0.968307E+09 | 0.560374E+09 | 0.407933E+09 | 0.00 | 0.00 |
| April | 0.125534E+10 | 0.560416E+09 | 0.805977E+09 | 0.390091E+09 | 0.415886E+09 | 0.00 | 0.00 |
| May | 0.134129E+10 | 0.323718E+09 | 0.748075E+09 | 0.309784E+09 | 0.438291E+09 | 0.00 | 0.00 |
| June | 0.145878E+10 | 0.137454E+09 | 0.674723E+09 | 0.270391E+09 | 0.404332E+09 | 0.00 | 0.00 |
| July | 0.140233E+10 | 0.115850E+09 | 0.646412E+09 | 0.239794E+09 | 0.406618E+09 | 0.00 | 0.00 |
| August | 0.142594E+10 | 0.190341E+09 | 0.702459E+09 | 0.299488E+09 | 0.402971E+09 | 0.00 | 0.00 |
| September | 0.159518E+10 | 0.393983E+09 | 0.865428E+09 | 0.482753E+09 | 0.382675E+09 | 0.00 | 0.00 |
| October | 0.155994E+10 | 0.697315E+09 | 0.101798E+10 | 0.673037E+09 | 0.344942E+09 | 0.00 | 0.00 |
| November | 0.136743E+10 | 0.106704E+10 | 0.106160E+10 | 0.780498E+09 | 0.281105E+09 | 0.00 | 0.00 |
| December | 0.118682E+10 | 0.130441E+10 | 0.102853E+10 | 0.736537E+09 | 0.291996E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.162120E+11 | 0.789084E+10 | 0.104517E+11 | 0.609449E+10 | 0.435717E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.111966E+10 | 0.115850E+09 | 0.646412E+09 | 0.239794E+09 | 0.281105E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.159518E+10 | 0.130441E+10 | 0.106160E+10 | 0.780498E+09 | 0.438291E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.469329E+10 | 0.334297E+10 | 0.355157E+10 | 0.278271E+10 | 0.768864E+09 | 0.00 | 0.00 |
| February | 0.399022E+10 | 0.270241E+10 | 0.296489E+10 | 0.218450E+10 | 0.780390E+09 | 0.00 | 0.00 |
| March | 0.364334E+10 | 0.262344E+10 | 0.263233E+10 | 0.162355E+10 | 0.100878E+10 | 0.00 | 0.00 |
| April | 0.271485E+10 | 0.153048E+10 | 0.164669E+10 | 0.693685E+09 | 0.953002E+09 | 0.00 | 0.00 |
| May | 0.222593E+10 | 0.819911E+09 | 0.112251E+10 | 0.190590E+09 | 0.931920E+09 | 0.00 | 0.00 |
| June | 0.247252E+10 | 0.318009E+09 | 0.914990E+09 | 72230944.78 | 0.842759E+09 | 0.00 | 0.00 |
| July | 0.262610E+10 | 0.242883E+09 | 0.966048E+09 | 0.111090E+09 | 0.854957E+09 | 0.00 | 0.00 |
| August | 0.306422E+10 | 0.430449E+09 | 0.130009E+10 | 0.403192E+09 | 0.896894E+09 | 0.00 | 0.00 |
| September | 0.413410E+10 | 0.969583E+09 | 0.209903E+10 | 0.119042E+10 | 0.908611E+09 | 0.00 | 0.00 |
| October | 0.486145E+10 | 0.183067E+10 | 0.303198E+10 | 0.215832E+10 | 0.873661E+09 | 0.00 | 0.00 |
| November | 0.494194E+10 | 0.291131E+10 | 0.354350E+10 | 0.279850E+10 | 0.745001E+09 | 0.00 | 0.00 |
| December | 0.464152E+10 | 0.361526E+10 | 0.359209E+10 | 0.278368E+10 | 0.808414E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.440095E+11 | 0.213374E+11 | 0.273657E+11 | 0.169925E+11 | 0.103732E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.222593E+10 | 0.242883E+09 | 0.914990E+09 | 72230944.78 | 0.745001E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.494194E+10 | 0.361526E+10 | 0.359209E+10 | 0.279850E+10 | 0.100878E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 90950474.73 | 0.206916E+09 | 88363542.88 | 49763851.35 | 38599691.53 | 0.00 | 0.00 |
| February | 0.100249E+09 | 0.169025E+09 | 90059831.58 | 47868739.55 | 42191092.04 | 0.00 | 0.00 |
| March | 0.168701E+09 | 0.160314E+09 | 0.135875E+09 | 72824222.81 | 63050606.59 | 0.00 | 0.00 |
| April | 0.227957E+09 | 91581524.64 | 0.151139E+09 | 81632895.25 | 69506104.79 | 0.00 | 0.00 |
| May | 0.291084E+09 | 52942671.26 | 0.168217E+09 | 90003984.72 | 78213505.00 | 0.00 | 0.00 |
| June | 0.317695E+09 | 23207362.35 | 0.158465E+09 | 85112889.14 | 73351624.10 | 0.00 | 0.00 |
| July | 0.295196E+09 | 17604622.69 | 0.145314E+09 | 72209221.10 | 73104399.47 | 0.00 | 0.00 |
| August | 0.271696E+09 | 27762348.34 | 0.140729E+09 | 71720812.08 | 69008002.58 | 0.00 | 0.00 |
| September | 0.247906E+09 | 59508157.85 | 0.139275E+09 | 77590030.53 | 61684563.74 | 0.00 | 0.00 |
| October | 0.183804E+09 | 0.110104E+09 | 0.123889E+09 | 72305718.98 | 51583335.65 | 0.00 | 0.00 |
| November | 0.117913E+09 | 0.181021E+09 | 0.100632E+09 | 61274315.14 | 39357906.06 | 0.00 | 0.00 |
| December | 81356390.59 | 0.226023E+09 | 83797994.24 | 45521768.27 | 38276225.97 | 0.00 | 0.00 |
| Annual Sum or Average | 0.239451E+10 | 0.132601E+10 | 0.152576E+10 | 0.827828E+09 | 0.697927E+09 | 0.00 | 0.00 |
| Minimum of Months | 81356390.59 | 17604622.69 | 83797994.24 | 45521768.27 | 38276225.97 | 0.00 | 0.00 |
| Maximum of Months | 0.317695E+09 | 0.226023E+09 | 0.168217E+09 | 90003984.72 | 78213505.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.259736E+09 | 0.120093E+10 | 0.360531E+09 | 0.149291E+09 | 0.211240E+09 | 0.00 | 0.00 |
| February | 0.328359E+09 | 0.967667E+09 | 0.375790E+09 | 0.143606E+09 | 0.232184E+09 | 0.00 | 0.00 |
| March | 0.594002E+09 | 0.926041E+09 | 0.563055E+09 | 0.218472E+09 | 0.344583E+09 | 0.00 | 0.00 |
| April | 0.886267E+09 | 0.538038E+09 | 0.626314E+09 | 0.246378E+09 | 0.379935E+09 | 0.00 | 0.00 |
| May | 0.124701E+10 | 0.306703E+09 | 0.720243E+09 | 0.287931E+09 | 0.432312E+09 | 0.00 | 0.00 |
| June | 0.149081E+10 | 0.134784E+09 | 0.701067E+09 | 0.287214E+09 | 0.413853E+09 | 0.00 | 0.00 |
| July | 0.138557E+10 | 0.113833E+09 | 0.647850E+09 | 0.240096E+09 | 0.407754E+09 | 0.00 | 0.00 |
| August | 0.119011E+10 | 0.177573E+09 | 0.596637E+09 | 0.219194E+09 | 0.377443E+09 | 0.00 | 0.00 |
| September | 0.100648E+10 | 0.376116E+09 | 0.564382E+09 | 0.232825E+09 | 0.331557E+09 | 0.00 | 0.00 |
| October | 0.665749E+09 | 0.680871E+09 | 0.497769E+09 | 0.216916E+09 | 0.280852E+09 | 0.00 | 0.00 |
| November | 0.350456E+09 | 0.107812E+10 | 0.400162E+09 | 0.183822E+09 | 0.216340E+09 | 0.00 | 0.00 |
| December | 0.215832E+09 | 0.134532E+10 | 0.345622E+09 | 0.136565E+09 | 0.209057E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.962039E+10 | 0.784600E+10 | 0.639942E+10 | 0.256231E+10 | 0.383711E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.215832E+09 | 0.113833E+09 | 0.345622E+09 | 0.136565E+09 | 0.209057E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.149081E+10 | 0.134532E+10 | 0.720243E+09 | 0.287931E+09 | 0.432312E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 17341551.61 | 0.361599E+10 | 0.427274E+09 | 0.00 | 0.427274E+09 | 0.00 | 0.00 |
| February | 0.126325E+09 | 0.287858E+10 | 0.473523E+09 | 0.00 | 0.473523E+09 | 0.00 | 0.00 |
| March | 0.338472E+09 | 0.271555E+10 | 0.701287E+09 | 0.00 | 0.701287E+09 | 0.00 | 0.00 |
| April | 0.878353E+09 | 0.147079E+10 | 0.776204E+09 | 5771924.77 | 0.770432E+09 | 0.00 | 0.00 |
| May | 0.172611E+10 | 0.753573E+09 | 0.961411E+09 | 74595887.13 | 0.886816E+09 | 0.00 | 0.00 |
| June | 0.258256E+10 | 0.308804E+09 | 0.100775E+10 | 0.136487E+09 | 0.871265E+09 | 0.00 | 0.00 |
| July | 0.249402E+10 | 0.233569E+09 | 0.940144E+09 | 97511738.12 | 0.842632E+09 | 0.00 | 0.00 |
| August | 0.190734E+10 | 0.386160E+09 | 0.778473E+09 | 16379100.73 | 0.762094E+09 | 0.00 | 0.00 |
| September | 0.125164E+10 | 0.914661E+09 | 0.657253E+09 | 199631.40 | 0.657053E+09 | 0.00 | 0.00 |
| October | 0.517686E+09 | 0.183497E+10 | 0.566063E+09 | 0.00 | 0.566063E+09 | 0.00 | 0.00 |
| November | 51004709.43 | 0.315870E+10 | 0.440708E+09 | 0.00 | 0.440708E+09 | 0.00 | 0.00 |
| December | 13313384.06 | 0.404298E+10 | 0.420859E+09 | 0.00 | 0.420859E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.119042E+11 | 0.223143E+11 | 0.815095E+10 | 0.330945E+09 | 0.782000E+10 | 0.00 | 0.00 |
| Minimum of Months | 13313384.06 | 0.233569E+09 | 0.420859E+09 | 0.00 | 0.420859E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.258256E+10 | 0.404298E+10 | 0.100775E+10 | 0.136487E+09 | 0.886816E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.123076E+10 | 0.119890E+10 | 0.103068E+10 | 0.744928E+09 | 0.285756E+09 | 0.00 | 0.00 |
| February | 0.112030E+10 | 0.972507E+09 | 0.905828E+09 | 0.607412E+09 | 0.298415E+09 | 0.00 | 0.00 |
| March | 0.127059E+10 | 0.941103E+09 | 0.970784E+09 | 0.560382E+09 | 0.410402E+09 | 0.00 | 0.00 |
| April | 0.125791E+10 | 0.562708E+09 | 0.808769E+09 | 0.390091E+09 | 0.418678E+09 | 0.00 | 0.00 |
| May | 0.134447E+10 | 0.325525E+09 | 0.751185E+09 | 0.309784E+09 | 0.441401E+09 | 0.00 | 0.00 |
| June | 0.146145E+10 | 0.138578E+09 | 0.677619E+09 | 0.270391E+09 | 0.407227E+09 | 0.00 | 0.00 |
| July | 0.140467E+10 | 0.117478E+09 | 0.649424E+09 | 0.239794E+09 | 0.409630E+09 | 0.00 | 0.00 |
| August | 0.142824E+10 | 0.192428E+09 | 0.705383E+09 | 0.299488E+09 | 0.405895E+09 | 0.00 | 0.00 |
| September | 0.159790E+10 | 0.395955E+09 | 0.867997E+09 | 0.482757E+09 | 0.385240E+09 | 0.00 | 0.00 |
| October | 0.156217E+10 | 0.699367E+09 | 0.102025E+10 | 0.673117E+09 | 0.347138E+09 | 0.00 | 0.00 |
| November | 0.136845E+10 | 0.106930E+10 | 0.106401E+10 | 0.780986E+09 | 0.283025E+09 | 0.00 | 0.00 |
| December | 0.118712E+10 | 0.130910E+10 | 0.103152E+10 | 0.737535E+09 | 0.293984E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.162340E+11 | 0.792295E+10 | 0.104835E+11 | 0.609667E+10 | 0.438679E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.112030E+10 | 0.117478E+09 | 0.649424E+09 | 0.239794E+09 | 0.283025E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.159790E+10 | 0.130910E+10 | 0.106401E+10 | 0.780986E+09 | 0.441401E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.470162E+10 | 0.336011E+10 | 0.356638E+10 | 0.278865E+10 | 0.777724E+09 | 0.00 | 0.00 |
| February | 0.399403E+10 | 0.271981E+10 | 0.297437E+10 | 0.218555E+10 | 0.788826E+09 | 0.00 | 0.00 |
| March | 0.365171E+10 | 0.263896E+10 | 0.264324E+10 | 0.162362E+10 | 0.101962E+10 | 0.00 | 0.00 |
| April | 0.272533E+10 | 0.154162E+10 | 0.165895E+10 | 0.693688E+09 | 0.965259E+09 | 0.00 | 0.00 |
| May | 0.223751E+10 | 0.829254E+09 | 0.113616E+10 | 0.190591E+09 | 0.945573E+09 | 0.00 | 0.00 |
| June | 0.248091E+10 | 0.323877E+09 | 0.927699E+09 | 72231155.90 | 0.855468E+09 | 0.00 | 0.00 |
| July | 0.263084E+10 | 0.250540E+09 | 0.979267E+09 | 0.111091E+09 | 0.868176E+09 | 0.00 | 0.00 |
| August | 0.306919E+10 | 0.440514E+09 | 0.131292E+10 | 0.403193E+09 | 0.909729E+09 | 0.00 | 0.00 |
| September | 0.414415E+10 | 0.980505E+09 | 0.211032E+10 | 0.119044E+10 | 0.919874E+09 | 0.00 | 0.00 |
| October | 0.487125E+10 | 0.184195E+10 | 0.304250E+10 | 0.215910E+10 | 0.883397E+09 | 0.00 | 0.00 |
| November | 0.495169E+10 | 0.292133E+10 | 0.355742E+10 | 0.280342E+10 | 0.753998E+09 | 0.00 | 0.00 |
| December | 0.465510E+10 | 0.363175E+10 | 0.361548E+10 | 0.279695E+10 | 0.818528E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.441133E+11 | 0.214802E+11 | 0.275247E+11 | 0.170185E+11 | 0.105062E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.223751E+10 | 0.250540E+09 | 0.927699E+09 | 72231155.90 | 0.753998E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.495169E+10 | 0.363175E+10 | 0.361548E+10 | 0.280342E+10 | 0.101962E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 90382704.18 | 0.209479E+09 | 88363542.88 | 49763851.35 | 38599691.53 | 0.00 | 0.00 |
| February | 99617462.33 | 0.171143E+09 | 90059831.58 | 47868739.55 | 42191092.04 | 0.00 | 0.00 |
| March | 0.168058E+09 | 0.161961E+09 | 0.135875E+09 | 72824222.81 | 63050606.59 | 0.00 | 0.00 |
| April | 0.227515E+09 | 92364301.76 | 0.151139E+09 | 81632895.25 | 69506104.79 | 0.00 | 0.00 |
| May | 0.290669E+09 | 53426587.92 | 0.168217E+09 | 90003984.72 | 78213505.00 | 0.00 | 0.00 |
| June | 0.317224E+09 | 23520948.68 | 0.158465E+09 | 85112889.14 | 73351624.10 | 0.00 | 0.00 |
| July | 0.294138E+09 | 18248440.65 | 0.145314E+09 | 72209221.10 | 73104399.47 | 0.00 | 0.00 |
| August | 0.270672E+09 | 28592404.97 | 0.140729E+09 | 71720812.08 | 69008002.58 | 0.00 | 0.00 |
| September | 0.247458E+09 | 60158771.06 | 0.139275E+09 | 77590030.53 | 61684563.74 | 0.00 | 0.00 |
| October | 0.183482E+09 | 0.110886E+09 | 0.123889E+09 | 72305718.98 | 51583335.65 | 0.00 | 0.00 |
| November | 0.117564E+09 | 0.182621E+09 | 0.100632E+09 | 61274315.14 | 39357906.06 | 0.00 | 0.00 |
| December | 80724783.53 | 0.228910E+09 | 83797994.24 | 45521768.27 | 38276225.97 | 0.00 | 0.00 |
| Annual Sum or Average | 0.238750E+10 | 0.134131E+10 | 0.152576E+10 | 0.827828E+09 | 0.697927E+09 | 0.00 | 0.00 |
| Minimum of Months | 80724783.53 | 18248440.65 | 83797994.24 | 45521768.27 | 38276225.97 | 0.00 | 0.00 |
| Maximum of Months | 0.317224E+09 | 0.228910E+09 | 0.168217E+09 | 90003984.72 | 78213505.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.272907E+09 | 0.120864E+10 | 0.379688E+09 | 0.149291E+09 | 0.230397E+09 | 0.00 | 0.00 |
| February | 0.344589E+09 | 0.977184E+09 | 0.396573E+09 | 0.143606E+09 | 0.252967E+09 | 0.00 | 0.00 |
| March | 0.620329E+09 | 0.937271E+09 | 0.590755E+09 | 0.218472E+09 | 0.372283E+09 | 0.00 | 0.00 |
| April | 0.920197E+09 | 0.549950E+09 | 0.658041E+09 | 0.246510E+09 | 0.411531E+09 | 0.00 | 0.00 |
| May | 0.128805E+10 | 0.320872E+09 | 0.755433E+09 | 0.288146E+09 | 0.467287E+09 | 0.00 | 0.00 |
| June | 0.152504E+10 | 0.144140E+09 | 0.733454E+09 | 0.287108E+09 | 0.446346E+09 | 0.00 | 0.00 |
| July | 0.142564E+10 | 0.121681E+09 | 0.682389E+09 | 0.240617E+09 | 0.441772E+09 | 0.00 | 0.00 |
| August | 0.122867E+10 | 0.187272E+09 | 0.629996E+09 | 0.219411E+09 | 0.410585E+09 | 0.00 | 0.00 |
| September | 0.104156E+10 | 0.388956E+09 | 0.593307E+09 | 0.232839E+09 | 0.360467E+09 | 0.00 | 0.00 |
| October | 0.692815E+09 | 0.691325E+09 | 0.522223E+09 | 0.216916E+09 | 0.305307E+09 | 0.00 | 0.00 |
| November | 0.363800E+09 | 0.108528E+10 | 0.419519E+09 | 0.183822E+09 | 0.235696E+09 | 0.00 | 0.00 |
| December | 0.225734E+09 | 0.135357E+10 | 0.365104E+09 | 0.136565E+09 | 0.228539E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.994933E+10 | 0.796614E+10 | 0.672648E+10 | 0.256330E+10 | 0.416318E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.225734E+09 | 0.121681E+09 | 0.365104E+09 | 0.136565E+09 | 0.228539E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.152504E+10 | 0.135357E+10 | 0.755433E+09 | 0.288146E+09 | 0.467287E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 38297537.91 | 0.239342E+10 | 0.365906E+09 | 0.00 | 0.365906E+09 | 0.00 | 0.00 |
| February | 0.136364E+09 | 0.192471E+10 | 0.403571E+09 | 0.00 | 0.403571E+09 | 0.00 | 0.00 |
| March | 0.327614E+09 | 0.182865E+10 | 0.584731E+09 | 0.00 | 0.584731E+09 | 0.00 | 0.00 |
| April | 0.723528E+09 | 0.101432E+10 | 0.653359E+09 | 5147454.49 | 0.648211E+09 | 0.00 | 0.00 |
| May | 0.134024E+10 | 0.555222E+09 | 0.800737E+09 | 57903745.70 | 0.742833E+09 | 0.00 | 0.00 |
| June | 0.189002E+10 | 0.242752E+09 | 0.823980E+09 | 0.101440E+09 | 0.722540E+09 | 0.00 | 0.00 |
| July | 0.185490E+10 | 0.186834E+09 | 0.786901E+09 | 76597955.02 | 0.710303E+09 | 0.00 | 0.00 |
| August | 0.143534E+10 | 0.293094E+09 | 0.663530E+09 | 13567297.49 | 0.649962E+09 | 0.00 | 0.00 |
| September | 0.979284E+09 | 0.660396E+09 | 0.560313E+09 | 223582.04 | 0.560089E+09 | 0.00 | 0.00 |
| October | 0.454635E+09 | 0.125690E+10 | 0.480721E+09 | 0.00 | 0.480721E+09 | 0.00 | 0.00 |
| November | 69702915.72 | 0.210203E+10 | 0.375565E+09 | 0.00 | 0.375565E+09 | 0.00 | 0.00 |
| December | 24455740.37 | 0.268356E+10 | 0.363072E+09 | 0.00 | 0.363072E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.927438E+10 | 0.151419E+11 | 0.686239E+10 | 0.254880E+09 | 0.660750E+10 | 0.00 | 0.00 |
| Minimum of Months | 24455740.37 | 0.186834E+09 | 0.363072E+09 | 0.00 | 0.363072E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.189002E+10 | 0.268356E+10 | 0.823980E+09 | 0.101440E+09 | 0.742833E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 13694956.55 | 0.132244E+10 | 0.188179E+09 | 0.00 | 0.188179E+09 | 0.00 | 0.00 |
| February | 60012769.22 | 0.106654E+10 | 0.207549E+09 | 0.00 | 0.207549E+09 | 0.00 | 0.00 |
| March | 0.154440E+09 | 0.100914E+10 | 0.300716E+09 | 0.00 | 0.300716E+09 | 0.00 | 0.00 |
| April | 0.360426E+09 | 0.555617E+09 | 0.336010E+09 | 2647269.09 | 0.333362E+09 | 0.00 | 0.00 |
| May | 0.679194E+09 | 0.302762E+09 | 0.411804E+09 | 29779145.57 | 0.382024E+09 | 0.00 | 0.00 |
| June | 0.962327E+09 | 0.135674E+09 | 0.423757E+09 | 52169491.67 | 0.371588E+09 | 0.00 | 0.00 |
| July | 0.921720E+09 | 0.112061E+09 | 0.404689E+09 | 39393335.01 | 0.365295E+09 | 0.00 | 0.00 |
| August | 0.702731E+09 | 0.174012E+09 | 0.341241E+09 | 6977485.17 | 0.334263E+09 | 0.00 | 0.00 |
| September | 0.494122E+09 | 0.361482E+09 | 0.288158E+09 | 114985.34 | 0.288043E+09 | 0.00 | 0.00 |
| October | 0.226088E+09 | 0.680037E+09 | 0.247226E+09 | 0.00 | 0.247226E+09 | 0.00 | 0.00 |
| November | 30325135.43 | 0.115101E+10 | 0.193146E+09 | 0.00 | 0.193146E+09 | 0.00 | 0.00 |
| December | 8728551.03 | 0.147306E+10 | 0.186721E+09 | 0.00 | 0.186721E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.461381E+10 | 0.834383E+10 | 0.352919E+10 | 0.131082E+09 | 0.339811E+10 | 0.00 | 0.00 |
| Minimum of Months | 8728551.03 | 0.112061E+09 | 0.186721E+09 | 0.00 | 0.186721E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.962327E+09 | 0.147306E+10 | 0.423757E+09 | 52169491.67 | 0.382024E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.110592E+09 | 0.602883E+09 | 0.146732E+09 | 66328695.59 | 80403325.06 | 0.00 | 0.00 |
| February | 0.178599E+09 | 0.493926E+09 | 0.180493E+09 | 88199832.95 | 92293639.38 | 0.00 | 0.00 |
| March | 0.386958E+09 | 0.478725E+09 | 0.321990E+09 | 0.175721E+09 | 0.146269E+09 | 0.00 | 0.00 |
| April | 0.596016E+09 | 0.272450E+09 | 0.390076E+09 | 0.223916E+09 | 0.166159E+09 | 0.00 | 0.00 |
| May | 0.757970E+09 | 0.156142E+09 | 0.429250E+09 | 0.243014E+09 | 0.186235E+09 | 0.00 | 0.00 |
| June | 0.841527E+09 | 69711878.45 | 0.405487E+09 | 0.229788E+09 | 0.175699E+09 | 0.00 | 0.00 |
| July | 0.757662E+09 | 56792979.49 | 0.364595E+09 | 0.192375E+09 | 0.172220E+09 | 0.00 | 0.00 |
| August | 0.716944E+09 | 84598678.82 | 0.364042E+09 | 0.200185E+09 | 0.163857E+09 | 0.00 | 0.00 |
| September | 0.633791E+09 | 0.170291E+09 | 0.348390E+09 | 0.202935E+09 | 0.145455E+09 | 0.00 | 0.00 |
| October | 0.385904E+09 | 0.315219E+09 | 0.265169E+09 | 0.150144E+09 | 0.115025E+09 | 0.00 | 0.00 |
| November | 0.175509E+09 | 0.530090E+09 | 0.178171E+09 | 94478888.06 | 83691925.30 | 0.00 | 0.00 |
| December | 84021917.66 | 0.650938E+09 | 0.131699E+09 | 53352198.76 | 78346786.64 | 0.00 | 0.00 |
| Annual Sum or Average | 0.562549E+10 | 0.388177E+10 | 0.352609E+10 | 0.192044E+10 | 0.160565E+10 | 0.00 | 0.00 |
| Minimum of Months | 84021917.66 | 56792979.49 | 0.131699E+09 | 53352198.76 | 78346786.64 | 0.00 | 0.00 |
| Maximum of Months | 0.841527E+09 | 0.650938E+09 | 0.429250E+09 | 0.243014E+09 | 0.186235E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.187291E+10 | 0.109695E+10 | 0.135887E+10 | 0.102949E+10 | 0.329385E+09 | 0.00 | 0.00 |
| February | 0.159824E+10 | 0.898320E+09 | 0.113852E+10 | 0.802640E+09 | 0.335881E+09 | 0.00 | 0.00 |
| March | 0.146920E+10 | 0.890670E+09 | 0.102442E+10 | 0.590679E+09 | 0.433743E+09 | 0.00 | 0.00 |
| April | 0.107800E+10 | 0.559357E+09 | 0.672149E+09 | 0.250796E+09 | 0.421353E+09 | 0.00 | 0.00 |
| May | 0.875747E+09 | 0.344085E+09 | 0.490834E+09 | 68700639.12 | 0.422133E+09 | 0.00 | 0.00 |
| June | 0.912866E+09 | 0.165667E+09 | 0.409806E+09 | 26002293.56 | 0.383803E+09 | 0.00 | 0.00 |
| July | 0.962307E+09 | 0.141414E+09 | 0.431677E+09 | 40017186.51 | 0.391660E+09 | 0.00 | 0.00 |
| August | 0.114452E+10 | 0.208450E+09 | 0.550269E+09 | 0.145660E+09 | 0.404609E+09 | 0.00 | 0.00 |
| September | 0.155806E+10 | 0.401330E+09 | 0.831201E+09 | 0.431838E+09 | 0.399363E+09 | 0.00 | 0.00 |
| October | 0.185840E+10 | 0.661169E+09 | 0.116700E+10 | 0.788972E+09 | 0.378031E+09 | 0.00 | 0.00 |
| November | 0.192973E+10 | 0.986669E+09 | 0.135908E+10 | 0.103613E+10 | 0.322948E+09 | 0.00 | 0.00 |
| December | 0.187968E+10 | 0.117893E+10 | 0.139180E+10 | 0.104475E+10 | 0.347050E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.171396E+11 | 0.753300E+10 | 0.108256E+11 | 0.625567E+10 | 0.456996E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.875747E+09 | 0.141414E+09 | 0.409806E+09 | 26002293.56 | 0.322948E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.192973E+10 | 0.117893E+10 | 0.139180E+10 | 0.104475E+10 | 0.433743E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.160900E+09 | 0.659342E+09 | 0.186235E+09 | 92332946.93 | 93901883.99 | 0.00 | 0.00 |
| February | 0.228190E+09 | 0.542294E+09 | 0.218837E+09 | 0.111938E+09 | 0.106899E+09 | 0.00 | 0.00 |
| March | 0.452890E+09 | 0.532995E+09 | 0.374776E+09 | 0.207076E+09 | 0.167700E+09 | 0.00 | 0.00 |
| April | 0.650375E+09 | 0.326730E+09 | 0.441258E+09 | 0.252731E+09 | 0.188527E+09 | 0.00 | 0.00 |
| May | 0.806835E+09 | 0.205627E+09 | 0.482605E+09 | 0.271823E+09 | 0.210783E+09 | 0.00 | 0.00 |
| June | 0.883559E+09 | 0.101325E+09 | 0.455411E+09 | 0.256778E+09 | 0.198633E+09 | 0.00 | 0.00 |
| July | 0.804852E+09 | 84199770.45 | 0.410112E+09 | 0.215052E+09 | 0.195061E+09 | 0.00 | 0.00 |
| August | 0.766370E+09 | 0.118238E+09 | 0.410809E+09 | 0.224939E+09 | 0.185870E+09 | 0.00 | 0.00 |
| September | 0.687269E+09 | 0.226123E+09 | 0.398918E+09 | 0.233200E+09 | 0.165718E+09 | 0.00 | 0.00 |
| October | 0.445827E+09 | 0.379797E+09 | 0.317109E+09 | 0.184255E+09 | 0.132854E+09 | 0.00 | 0.00 |
| November | 0.232686E+09 | 0.591549E+09 | 0.223229E+09 | 0.125829E+09 | 97399585.48 | 0.00 | 0.00 |
| December | 0.127191E+09 | 0.717238E+09 | 0.168365E+09 | 76578182.95 | 91786478.60 | 0.00 | 0.00 |
| Annual Sum or Average | 0.624694E+10 | 0.448546E+10 | 0.408766E+10 | 0.225253E+10 | 0.183513E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.127191E+09 | 84199770.45 | 0.168365E+09 | 76578182.95 | 91786478.60 | 0.00 | 0.00 |
| Maximum of Months | 0.883559E+09 | 0.717238E+09 | 0.482605E+09 | 0.271823E+09 | 0.210783E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.241469E+10 | 0.264766E+10 | 0.208907E+10 | 0.145636E+10 | 0.632711E+09 | 0.00 | 0.00 |
| February | 0.237906E+10 | 0.217801E+10 | 0.196792E+10 | 0.129157E+10 | 0.676354E+09 | 0.00 | 0.00 |
| March | 0.261568E+10 | 0.209904E+10 | 0.210220E+10 | 0.118726E+10 | 0.914937E+09 | 0.00 | 0.00 |
| April | 0.271031E+10 | 0.124333E+10 | 0.187395E+10 | 0.904676E+09 | 0.969272E+09 | 0.00 | 0.00 |
| May | 0.290609E+10 | 0.765722E+09 | 0.174859E+10 | 0.731402E+09 | 0.101719E+10 | 0.00 | 0.00 |
| June | 0.322189E+10 | 0.377107E+09 | 0.162079E+10 | 0.678437E+09 | 0.942348E+09 | 0.00 | 0.00 |
| July | 0.310579E+10 | 0.330315E+09 | 0.155933E+10 | 0.609994E+09 | 0.949332E+09 | 0.00 | 0.00 |
| August | 0.311543E+10 | 0.472759E+09 | 0.163797E+10 | 0.688025E+09 | 0.949944E+09 | 0.00 | 0.00 |
| September | 0.333815E+10 | 0.871990E+09 | 0.190601E+10 | 0.104063E+10 | 0.865379E+09 | 0.00 | 0.00 |
| October | 0.306774E+10 | 0.151753E+10 | 0.207445E+10 | 0.129546E+10 | 0.778988E+09 | 0.00 | 0.00 |
| November | 0.269285E+10 | 0.232275E+10 | 0.218277E+10 | 0.154143E+10 | 0.641338E+09 | 0.00 | 0.00 |
| December | 0.235409E+10 | 0.284876E+10 | 0.212496E+10 | 0.146553E+10 | 0.659422E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.339218E+11 | 0.176750E+11 | 0.228880E+11 | 0.128908E+11 | 0.999721E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.235409E+10 | 0.330315E+09 | 0.155933E+10 | 0.609994E+09 | 0.632711E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.333815E+10 | 0.284876E+10 | 0.218277E+10 | 0.154143E+10 | 0.101719E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.152446E+10 | 0.264960E+10 | 0.155190E+10 | 0.100426E+10 | 0.547634E+09 | 0.00 | 0.00 |
| February | 0.206202E+10 | 0.220609E+10 | 0.187494E+10 | 0.125366E+10 | 0.621275E+09 | 0.00 | 0.00 |
| March | 0.333758E+10 | 0.214791E+10 | 0.275054E+10 | 0.181664E+10 | 0.933896E+09 | 0.00 | 0.00 |
| April | 0.462754E+10 | 0.136605E+10 | 0.332810E+10 | 0.230499E+10 | 0.102310E+10 | 0.00 | 0.00 |
| May | 0.563465E+10 | 0.939144E+09 | 0.371700E+10 | 0.257400E+10 | 0.114301E+10 | 0.00 | 0.00 |
| June | 0.614184E+10 | 0.505350E+09 | 0.375237E+10 | 0.270980E+10 | 0.104257E+10 | 0.00 | 0.00 |
| July | 0.560914E+10 | 0.420451E+09 | 0.338572E+10 | 0.227518E+10 | 0.111055E+10 | 0.00 | 0.00 |
| August | 0.511601E+10 | 0.566887E+09 | 0.316675E+10 | 0.211303E+10 | 0.105372E+10 | 0.00 | 0.00 |
| September | 0.446655E+10 | 0.930313E+09 | 0.287438E+10 | 0.201295E+10 | 0.861427E+09 | 0.00 | 0.00 |
| October | 0.305273E+10 | 0.151671E+10 | 0.223806E+10 | 0.150735E+10 | 0.730708E+09 | 0.00 | 0.00 |
| November | 0.192066E+10 | 0.230692E+10 | 0.176682E+10 | 0.122399E+10 | 0.542830E+09 | 0.00 | 0.00 |
| December | 0.132446E+10 | 0.288105E+10 | 0.148019E+10 | 0.914417E+09 | 0.565772E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.448176E+11 | 0.184365E+11 | 0.318868E+11 | 0.217103E+11 | 0.101765E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.132446E+10 | 0.420451E+09 | 0.148019E+10 | 0.914417E+09 | 0.542830E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.614184E+10 | 0.288105E+10 | 0.375237E+10 | 0.270980E+10 | 0.114301E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.180162E+09 | 0.672922E+09 | 0.223687E+09 | 0.121341E+09 | 0.102345E+09 | 0.00 | 0.00 |
| February | 0.267469E+09 | 0.526130E+09 | 0.270310E+09 | 0.154074E+09 | 0.116236E+09 | 0.00 | 0.00 |
| March | 0.413282E+09 | 0.481711E+09 | 0.369502E+09 | 0.203583E+09 | 0.165919E+09 | 0.00 | 0.00 |
| April | 0.607839E+09 | 0.275225E+09 | 0.430869E+09 | 0.239035E+09 | 0.191835E+09 | 0.00 | 0.00 |
| May | 0.757025E+09 | 0.176299E+09 | 0.459455E+09 | 0.249695E+09 | 0.209760E+09 | 0.00 | 0.00 |
| June | 0.847645E+09 | 94631686.70 | 0.444884E+09 | 0.247496E+09 | 0.197388E+09 | 0.00 | 0.00 |
| July | 0.785307E+09 | 83158625.93 | 0.412263E+09 | 0.215523E+09 | 0.196740E+09 | 0.00 | 0.00 |
| August | 0.718439E+09 | 0.109364E+09 | 0.392291E+09 | 0.200769E+09 | 0.191521E+09 | 0.00 | 0.00 |
| September | 0.632005E+09 | 0.189617E+09 | 0.376116E+09 | 0.214600E+09 | 0.161516E+09 | 0.00 | 0.00 |
| October | 0.400360E+09 | 0.330978E+09 | 0.298899E+09 | 0.161312E+09 | 0.137587E+09 | 0.00 | 0.00 |
| November | 0.252417E+09 | 0.544658E+09 | 0.259293E+09 | 0.150951E+09 | 0.108342E+09 | 0.00 | 0.00 |
| December | 0.164986E+09 | 0.731694E+09 | 0.223495E+09 | 0.118412E+09 | 0.105083E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.602694E+10 | 0.421639E+10 | 0.416106E+10 | 0.227679E+10 | 0.188427E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.164986E+09 | 83158625.93 | 0.223495E+09 | 0.118412E+09 | 0.102345E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.847645E+09 | 0.731694E+09 | 0.459455E+09 | 0.249695E+09 | 0.209760E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.261424E+09 | 0.238631E+10 | 0.625595E+09 | 0.227523E+09 | 0.398072E+09 | 0.00 | 0.00 |
| February | 0.479834E+09 | 0.189978E+10 | 0.734494E+09 | 0.288899E+09 | 0.445595E+09 | 0.00 | 0.00 |
| March | 0.868229E+09 | 0.182113E+10 | 0.102391E+10 | 0.381731E+09 | 0.642178E+09 | 0.00 | 0.00 |
| April | 0.144937E+10 | 0.109209E+10 | 0.117553E+10 | 0.450087E+09 | 0.725446E+09 | 0.00 | 0.00 |
| May | 0.207194E+10 | 0.720939E+09 | 0.130170E+10 | 0.492436E+09 | 0.809266E+09 | 0.00 | 0.00 |
| June | 0.254865E+10 | 0.395929E+09 | 0.128670E+10 | 0.511205E+09 | 0.775494E+09 | 0.00 | 0.00 |
| July | 0.236864E+10 | 0.332276E+09 | 0.120375E+10 | 0.438041E+09 | 0.765708E+09 | 0.00 | 0.00 |
| August | 0.203546E+10 | 0.436794E+09 | 0.110714E+10 | 0.382498E+09 | 0.724643E+09 | 0.00 | 0.00 |
| September | 0.164181E+10 | 0.801608E+09 | 0.102142E+10 | 0.402461E+09 | 0.618955E+09 | 0.00 | 0.00 |
| October | 0.931194E+09 | 0.133584E+10 | 0.831885E+09 | 0.302470E+09 | 0.529415E+09 | 0.00 | 0.00 |
| November | 0.406560E+09 | 0.206612E+10 | 0.698170E+09 | 0.283044E+09 | 0.415126E+09 | 0.00 | 0.00 |
| December | 0.208807E+09 | 0.263582E+10 | 0.623275E+09 | 0.222030E+09 | 0.401245E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.152719E+11 | 0.159246E+11 | 0.116336E+11 | 0.438242E+10 | 0.725115E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.208807E+09 | 0.332276E+09 | 0.623275E+09 | 0.222030E+09 | 0.398072E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.254865E+10 | 0.263582E+10 | 0.130170E+10 | 0.511205E+09 | 0.809266E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.341293E+09 | 0.267174E+10 | 0.726058E+09 | 0.277406E+09 | 0.448651E+09 | 0.00 | 0.00 |
| February | 0.618367E+09 | 0.214071E+10 | 0.869751E+09 | 0.364769E+09 | 0.504982E+09 | 0.00 | 0.00 |
| March | 0.110463E+10 | 0.204738E+10 | 0.123157E+10 | 0.501628E+09 | 0.729940E+09 | 0.00 | 0.00 |
| April | 0.187386E+10 | 0.118163E+10 | 0.145167E+10 | 0.617964E+09 | 0.833711E+09 | 0.00 | 0.00 |
| May | 0.262779E+10 | 0.729961E+09 | 0.161551E+10 | 0.683873E+09 | 0.931640E+09 | 0.00 | 0.00 |
| June | 0.316234E+10 | 0.363130E+09 | 0.159402E+10 | 0.703697E+09 | 0.890322E+09 | 0.00 | 0.00 |
| July | 0.294993E+10 | 0.312474E+09 | 0.148644E+10 | 0.605757E+09 | 0.880679E+09 | 0.00 | 0.00 |
| August | 0.252891E+10 | 0.442763E+09 | 0.136117E+10 | 0.527505E+09 | 0.833667E+09 | 0.00 | 0.00 |
| September | 0.204601E+10 | 0.819222E+09 | 0.124770E+10 | 0.540764E+09 | 0.706939E+09 | 0.00 | 0.00 |
| October | 0.115822E+10 | 0.146150E+10 | 0.991935E+09 | 0.390810E+09 | 0.601125E+09 | 0.00 | 0.00 |
| November | 0.513323E+09 | 0.233733E+10 | 0.812042E+09 | 0.345013E+09 | 0.467029E+09 | 0.00 | 0.00 |
| December | 0.267311E+09 | 0.295337E+10 | 0.709849E+09 | 0.258817E+09 | 0.451032E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.191920E+11 | 0.174612E+11 | 0.140977E+11 | 0.581800E+10 | 0.827972E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.267311E+09 | 0.312474E+09 | 0.709849E+09 | 0.258817E+09 | 0.448651E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.316234E+10 | 0.295337E+10 | 0.161551E+10 | 0.703697E+09 | 0.931640E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
| February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
| March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
| April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
| May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
| June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
| July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
| August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
| September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
| October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
| November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
| December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
| Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
| Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
| Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
| February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
| March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
| April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
| May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
| June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
| July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
| August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
| September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
| October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
| November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
| December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
| Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
| February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
| March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
| April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
| May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
| June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
| July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
| August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
| September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
| October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
| November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
| December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
| Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
| February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
| March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
| April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
| May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
| June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
| July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
| August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
| September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
| October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
| November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
| December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
| Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
| February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
| March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
| April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
| May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
| June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
| July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
| August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
| September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
| October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
| November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
| December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
| Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER G WATER HEATER
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.274039E+10 | -0.258087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159517448.6 | 82.17 | 0.00 | 0.00 |
| February | 0.247924E+10 | -0.233507E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -144162814.6 | 82.17 | 0.00 | 0.00 |
| March | 0.298660E+10 | -0.282667E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159933200.3 | 82.17 | 0.00 | 0.00 |
| April | 0.261250E+10 | -0.245797E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154529113.7 | 82.17 | 0.00 | 0.00 |
| May | 0.286358E+10 | -0.270377E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159814744.1 | 82.17 | 0.00 | 0.00 |
| June | 0.184156E+10 | -0.168695E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154617687.4 | 82.17 | 0.00 | 0.00 |
| July | 0.768370E+09 | -609202405.1 | 0.00 | 0.00 | 744.00 | 0.00 | -159167767.8 | 82.17 | 0.00 | 0.00 |
| August | 0.860393E+09 | -700582820.4 | 0.00 | 0.00 | 744.00 | 0.00 | -159809733.8 | 82.17 | 0.00 | 0.00 |
| September | 0.168792E+10 | -0.153359E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154334343.6 | 82.17 | 0.00 | 0.00 |
| October | 0.274049E+10 | -0.258087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159618554.8 | 82.17 | 0.00 | 0.00 |
| November | 0.273540E+10 | -0.258087E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154530300.4 | 82.17 | 0.00 | 0.00 |
| December | 0.261734E+10 | -0.245797E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159369264.0 | 82.17 | 0.00 | 0.00 |
| Annual Sum or Average | 0.269338E+11 | -0.250544E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.187940E+10 | 82.17 | 0.00 | 0.00 |
| Minimum of Months | 0.768370E+09 | -0.282667E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -159933200.3 | 82.17 | 0.00 | 0.00 |
| Maximum of Months | 0.298660E+10 | -609202405.1 | 0.00 | 0.00 | 744.00 | 0.00 | -144162814.6 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.961481E+10 | -0.868359E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -931215765.4 | 60.05 | 0.00 | 0.00 |
| February | 0.867414E+10 | -0.785188E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -822263808.6 | 60.05 | 0.00 | 0.00 |
| March | 0.100404E+11 | -0.915694E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -883471853.6 | 60.05 | 0.00 | 0.00 |
| April | 0.828564E+10 | -0.744929E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -836353357.1 | 60.05 | 0.00 | 0.00 |
| May | 0.841516E+10 | -0.755172E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -863445644.6 | 60.05 | 0.00 | 0.00 |
| June | 0.521549E+10 | -0.437862E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -836872050.3 | 60.05 | 0.00 | 0.00 |
| July | 0.235761E+10 | -0.148851E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -869107077.3 | 60.05 | 0.00 | 0.00 |
| August | 0.258564E+10 | -0.171464E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -870993915.8 | 60.05 | 0.00 | 0.00 |
| September | 0.483121E+10 | -0.399469E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -836518158.0 | 60.05 | 0.00 | 0.00 |
| October | 0.806981E+10 | -0.720445E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -865359479.9 | 60.05 | 0.00 | 0.00 |
| November | 0.869181E+10 | -0.782712E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -864697257.1 | 60.05 | 0.00 | 0.00 |
| December | 0.890723E+10 | -0.796623E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -941004434.8 | 60.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.856890E+11 | -0.752677E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.104213E+11 | 60.05 | 0.00 | 0.00 |
| Minimum of Months | 0.235761E+10 | -0.915694E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -941004434.8 | 60.05 | 0.00 | 0.00 |
| Maximum of Months | 0.100404E+11 | -0.148851E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -822263808.6 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 4125.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 73511417.91 | 6681.48 | 17-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 50068377.94 | 6682.42 | 14-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 27479460.74 | 6678.27 | 27-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 1062484.84 | 6676.17 | 11-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 16190821.46 | 6678.81 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.115378E+09 | 6679.67 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.283691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.115378E+09 | 6682.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 41735243.05 | 23751.17 | 25-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 28859589.86 | 23769.15 | 27-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 14567937.17 | 23744.93 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 4716653.17 | 23752.04 | 30-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.143308E+09 | 23741.07 | 06-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.233187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.143308E+09 | 23769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 32194578.41 | 6230.22 | 19-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 11822284.87 | 6216.55 | 17-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 2501792.94 | 6216.12 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 2069121.07 | 6228.02 | 28-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.107670E+09 | 6226.51 | 06-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.156258E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.107670E+09 | 6230.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.300806E+09 | 6584.12 | 17-JAN-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.192625E+09 | 6580.96 | 14-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 77568404.55 | 6579.54 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 1483702.50 | 6574.66 | 11-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 61567705.87 | 6580.42 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.384976E+09 | 6581.80 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.101903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.384976E+09 | 6584.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.589649E+09 | 23049.44 | 30-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.271120E+09 | 23049.72 | 14-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 77614050.68 | 23036.63 | 27-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 172964.69 | 2882.74 | 12-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 89625474.83 | 23039.03 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.844099E+09 | 23053.50 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.187228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.844099E+09 | 23053.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 74788742.57 | 6627.22 | 17-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 50178679.60 | 6628.16 | 14-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 27010136.90 | 6624.04 | 27-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 1039699.39 | 6621.96 | 11-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 18275926.69 | 6624.57 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.120695E+09 | 6625.42 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.291988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.120695E+09 | 6628.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 41488953.50 | 23380.38 | 25-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 26744387.02 | 23398.06 | 27-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 12240556.32 | 23374.25 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 5914012.17 | 23381.24 | 30-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.153881E+09 | 23370.45 | 06-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.240268E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.153881E+09 | 23398.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 33466005.00 | 6212.32 | 19-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 11743164.14 | 6198.69 | 17-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 2415593.91 | 6198.25 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 2294893.59 | 6210.12 | 28-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.112487E+09 | 6208.62 | 06-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.162406E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.112487E+09 | 6212.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.303642E+09 | 6588.20 | 17-JAN-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.193457E+09 | 6585.03 | 14-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 77589350.66 | 6583.61 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 1483905.89 | 6578.72 | 11-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 62245113.16 | 6584.49 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.388346E+09 | 6585.87 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.102676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.388346E+09 | 6588.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.599411E+09 | 23066.96 | 30-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.273427E+09 | 23067.25 | 14-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 77620471.91 | 23054.15 | 27-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 173097.50 | 2884.96 | 12-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 91290673.34 | 23056.55 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.856149E+09 | 23071.03 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.189807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.856149E+09 | 23071.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 70333202.87 | 6633.05 | 17-JAN-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 47373366.79 | 6633.98 | 14-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 25856467.46 | 6629.86 | 27-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 1020470.96 | 6627.78 | 11-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 16835701.85 | 6630.40 | 28-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.113857E+09 | 6631.25 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.275276E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.113857E+09 | 6633.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 33739336.13 | 23465.67 | 19-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 23670590.90 | 23492.31 | 27-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 11113217.56 | 23468.42 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 4832782.79 | 23475.43 | 30-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.137694E+09 | 23464.61 | 06-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.211050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.137694E+09 | 23492.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 22821016.43 | 6239.87 | 18-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 7878988.86 | 6228.25 | 17-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1515476.05 | 6125.76 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 1416381.13 | 6239.74 | 28-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 87705154.37 | 6226.97 | 06-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.121337E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 87705154.37 | 6239.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.295057E+09 | 6633.72 | 17-JAN-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.187286E+09 | 6630.53 | 14-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 75571454.29 | 6629.11 | 01-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 1418027.85 | 6624.18 | 11-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 60517211.79 | 6629.99 | 28-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.377492E+09 | 6631.38 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.997341E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.377492E+09 | 6633.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.369380E+09 | 15591.77 | 30-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.168032E+09 | 15591.97 | 14-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 48083125.29 | 15583.10 | 27-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 95033.80 | 1583.90 | 12-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 57715065.26 | 15584.72 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.533434E+09 | 15594.53 | 05-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.117674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.533434E+09 | 15594.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 39961814.33 | 7937.72 | 30-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 17205454.13 | 7935.43 | 27-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 4354593.82 | 7927.72 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 2933746.60 | 7929.80 | 20-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 62192145.54 | 7932.73 | 11-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.126648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 62192145.54 | 7937.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 62735245.82 | 14248.43 | 19-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 23588161.26 | 14215.40 | 06-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 838995.11 | 13983.25 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 2389312.99 | 14222.06 | 30-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.343182E+09 | 14242.10 | 14-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.432733E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.343182E+09 | 14248.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.307905E+10 | 8185.16 | 19-JAN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.230526E+10 | 8184.82 | 13-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.185698E+10 | 8190.18 | 27-MAR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.668973E+09 | 7905.73 | 18-APR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.189223E+09 | 8166.55 | 01-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 9488680.10 | 7989.85 | 29-JUN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 22867135.62 | 8190.98 | 14-AUG-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.126768E+09 | 8185.10 | 06-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.531005E+09 | 8183.12 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.160178E+10 | 8178.91 | 29-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.354990E+10 | 8185.02 | 13-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.139413E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.354990E+10 | 8190.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 14910522.82 | 18356.13 | 19-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 7801083.50 | 18245.53 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1772972.80 | 18055.75 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 725244.45 | 12087.41 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 95338207.64 | 18322.50 | 27-DEC-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.120548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 95338207.64 | 18356.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 70084289.68 | 5326.24 | 30-JAN-06:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 19139527.99 | 4792.38 | 02-FEB-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 2193985.20 | 2562.92 | 02-MAR-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 3022179.21 | 1987.75 | 28-NOV-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.201970E+09 | 16280.78 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.296410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.201970E+09 | 16280.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 26339789.54 | 17893.25 | 02-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 7029166.06 | 17750.12 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1053870.06 | 17564.50 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 682200.96 | 11370.02 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 76115324.28 | 17844.32 | 18-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.111220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 76115324.28 | 17893.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_POD_1 HEATING COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.103328E+11 | 142752.31 | 27-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.710093E+10 | 127142.19 | 03-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.386113E+10 | 116876.17 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.193408E+09 | 41042.30 | 11-APR-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 16421065.98 | 24399.86 | 24-OCT-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.336411E+10 | 81165.49 | 28-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.184413E+11 | 142051.66 | 27-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.433101E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.184413E+11 | 142752.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:6 HEATING COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 1558120.61 | 20547.82 | 05-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3124198.53 | 14313.72 | 02-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 3683193.56 | 16397.14 | 20-MAR-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 8040727.26 | 12123.12 | 03-APR-05:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 6885416.38 | 13821.73 | 11-MAY-05:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 927713.71 | 4373.88 | 01-JUN-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 1056040.87 | 5280.20 | 23-AUG-05:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 547802.05 | 4565.02 | 30-OCT-05:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 2901859.72 | 11032.47 | 17-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1201311.16 | 7035.48 | 07-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 29926383.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 8040727.26 | 20547.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:7 HEATING COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.253937E+10 | 78718.84 | 27-JAN-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.190768E+10 | 78718.84 | 02-FEB-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.962608E+09 | 78718.84 | 02-MAR-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 92493145.47 | 43020.31 | 21-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 19836167.38 | 24060.26 | 08-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 6894350.05 | 14248.14 | 05-JUN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 8276920.86 | 14427.38 | 11-JUL-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 2026420.53 | 9446.63 | 23-AUG-05:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 2028938.57 | 6763.13 | 13-SEP-05:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 17767074.30 | 11999.73 | 25-OCT-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.857732E+09 | 56481.85 | 28-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.430112E+10 | 78718.84 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.107178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 2026420.53 | 6763.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.430112E+10 | 78718.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_POD_1 COOLING COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.781355E+10 | 0.779418E+10 | 154026.66 | 03-JAN-15:02 | 154026.66 | 0.00 |
| February | 0.00 | 0.00 | 0.217928E+11 | 0.217187E+11 | 192123.41 | 21-FEB-15:05 | 192123.41 | 0.00 |
| March | 0.00 | 0.00 | 0.631613E+11 | 0.631597E+11 | 263354.28 | 22-MAR-14:05 | 263354.28 | 0.00 |
| April | 0.00 | 0.00 | 0.189026E+12 | 0.188622E+12 | 399774.34 | 21-APR-14:02 | 399774.34 | 0.00 |
| May | 0.00 | 0.00 | 0.350786E+12 | 0.343238E+12 | 448679.85 | 19-MAY-14:02 | 448679.85 | 0.00 |
| June | 0.00 | 0.00 | 0.459466E+12 | 0.448071E+12 | 503187.50 | 15-JUN-15:00 | 503187.50 | 0.00 |
| July | 0.00 | 0.00 | 0.415620E+12 | 0.344752E+12 | 494196.86 | 17-JUL-07:03 | 167569.56 | 0.00 |
| August | 0.00 | 0.00 | 0.361540E+12 | 0.321137E+12 | 424986.32 | 02-AUG-14:02 | 330956.40 | 0.00 |
| September | 0.00 | 0.00 | 0.369284E+12 | 0.326996E+12 | 488779.98 | 22-SEP-14:03 | 415212.59 | 0.00 |
| October | 0.00 | 0.00 | 0.210466E+12 | 0.192108E+12 | 512960.96 | 03-OCT-14:02 | 438881.23 | 0.00 |
| November | 0.00 | 0.00 | 0.474797E+11 | 0.468916E+11 | 269051.19 | 09-NOV-14:00 | 269051.19 | 0.00 |
| December | 0.00 | 0.00 | 0.211448E+10 | 0.210949E+10 | 88643.84 | 08-DEC-14:05 | 88643.84 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.249855E+13 | 0.230660E+13 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.211448E+10 | 0.210949E+10 | 88643.84 | 88643.84 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.459466E+12 | 0.448071E+12 | 512960.96 | 503187.50 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:6 COOLING COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.587401E+09 | 0.531970E+09 | 36994.82 | 01-JAN-14:02 | 30155.10 | 0.00 |
| February | 0.00 | 0.00 | 0.181763E+10 | 0.177897E+10 | 36994.82 | 03-FEB-06:01 | 32155.99 | 0.00 |
| March | 0.00 | 0.00 | 0.484796E+10 | 0.480952E+10 | 36994.82 | 12-MAR-18:12 | 36994.82 | 0.00 |
| April | 0.00 | 0.00 | 0.138764E+11 | 0.127862E+11 | 38003.09 | 18-APR-20:53 | 30576.45 | 0.00 |
| May | 0.00 | 0.00 | 0.254197E+11 | 0.220576E+11 | 40220.57 | 27-MAY-20:55 | 25945.34 | 0.00 |
| June | 0.00 | 0.00 | 0.317232E+11 | 0.272246E+11 | 40837.32 | 27-JUN-23:33 | 23647.78 | 0.00 |
| July | 0.00 | 0.00 | 0.346679E+11 | 0.257594E+11 | 43275.01 | 22-JUL-06:53 | 16162.74 | 0.00 |
| August | 0.00 | 0.00 | 0.308642E+11 | 0.241100E+11 | 42415.16 | 01-AUG-21:33 | 18361.24 | 0.00 |
| September | 0.00 | 0.00 | 0.252837E+11 | 0.195716E+11 | 42096.81 | 22-SEP-01:32 | 15536.66 | 0.00 |
| October | 0.00 | 0.00 | 0.145748E+11 | 0.119020E+11 | 41016.15 | 03-OCT-20:53 | 19853.32 | 0.00 |
| November | 0.00 | 0.00 | 0.328911E+10 | 0.312615E+10 | 36994.82 | 09-NOV-06:01 | 34236.65 | 0.00 |
| December | 0.00 | 0.00 | 0.242222E+09 | 0.212848E+09 | 36994.82 | 01-DEC-06:01 | 27300.86 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.187194E+12 | 0.153871E+12 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.242222E+09 | 0.212848E+09 | 36994.82 | 15536.66 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.346679E+11 | 0.272246E+11 | 43275.01 | 36994.82 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:7 COOLING COIL
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.193210E+09 | 0.186046E+09 | 13526.98 | 03-JAN-15:00 | 13526.98 | 0.00 |
| February | 0.00 | 0.00 | 0.142456E+10 | 0.142070E+10 | 22927.70 | 21-FEB-15:00 | 22927.70 | 0.00 |
| March | 0.00 | 0.00 | 0.473545E+10 | 0.473370E+10 | 30967.48 | 22-MAR-13:00 | 30967.48 | 0.00 |
| April | 0.00 | 0.00 | 0.163342E+11 | 0.159308E+11 | 74956.84 | 30-APR-10:13 | 65969.32 | 0.00 |
| May | 0.00 | 0.00 | 0.338034E+11 | 0.312778E+11 | 81283.02 | 27-MAY-21:11 | 50127.76 | 0.00 |
| June | 0.00 | 0.00 | 0.482929E+11 | 0.441858E+11 | 80342.95 | 04-JUN-07:11 | 50681.09 | 0.00 |
| July | 0.00 | 0.00 | 0.400291E+11 | 0.312103E+11 | 86900.53 | 21-JUL-05:01 | 26992.65 | 0.00 |
| August | 0.00 | 0.00 | 0.340905E+11 | 0.279808E+11 | 85784.91 | 03-AUG-06:00 | 35470.31 | 0.00 |
| September | 0.00 | 0.00 | 0.371086E+11 | 0.294789E+11 | 84751.83 | 22-SEP-05:01 | 30847.29 | 0.00 |
| October | 0.00 | 0.00 | 0.186269E+11 | 0.150113E+11 | 80364.18 | 08-OCT-12:31 | 51410.76 | 0.00 |
| November | 0.00 | 0.00 | 0.302311E+10 | 0.283918E+10 | 29390.13 | 03-NOV-14:00 | 25491.07 | 0.00 |
| December | 0.00 | 0.00 | 18086343.79 | 18023047.90 | 3843.52 | 08-DEC-14:00 | 3843.52 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.237680E+12 | 0.204273E+12 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 18086343.79 | 18023047.90 | 3843.52 | 3843.52 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.482929E+11 | 0.441858E+11 | 86900.53 | 65969.32 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 2275.36 | 367135.78 | 17-JAN-08:61 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 1607.49 | 371579.58 | 03-FEB-08:61 |
| March | 0.00 | 0.00 | 01-MAR-00:05 | 898.52 | 361535.39 | 02-MAR-08:61 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 259.51 | 46712.99 | 12-APR-07:01 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 68.42 | 9771.99 | 25-MAY-07:02 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 3.51 | 9875.33 | 29-JUN-07:02 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 01-JUL-00:02 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 8.42 | 10469.38 | 17-AUG-07:03 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 49.59 | 10349.01 | 08-SEP-07:02 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 196.09 | 9683.21 | 25-OCT-06:04 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 802.36 | 327400.10 | 28-NOV-08:61 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 3261.39 | 404494.94 | 26-DEC-07:01 |
| Annual Sum or Average | 0.00 | 784.69 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 3261.39 | 404494.94 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 3230.74 | 16462.82 | 30-JAN-13:30 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 3234.29 | 16460.98 | 01-FEB-14:00 |
| March | 0.00 | 0.00 | 01-MAR-00:05 | 3406.52 | 16152.72 | 01-MAR-13:30 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 2863.23 | 15210.74 | 03-APR-13:00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 2808.46 | 14134.48 | 01-MAY-13:00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 1679.54 | 12953.06 | 01-JUN-12:20 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 548.42 | 3622.11 | 03-JUL-18:30 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 631.75 | 3636.70 | 31-AUG-18:40 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 1532.30 | 12935.15 | 29-SEP-12:50 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 2679.31 | 14153.67 | 31-OCT-12:20 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 3008.46 | 15297.62 | 30-NOV-13:20 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 2963.56 | 16470.45 | 12-DEC-15:01 |
| Annual Sum or Average | 0.00 | 2376.43 | ||||
| Minimum of Months | 0.00 | 0.00 | 548.42 | 3622.11 | ||
| Maximum of Months | 0.00 | 0.00 | 3406.52 | 16470.45 |
Report: FanReportMonthly
For: VAV_POD_1 FAN
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.185142E+11 | 0.44 | 27687.91 | 12-JAN-15:15 | 1.33 |
| February | 0.177052E+11 | 0.45 | 34300.65 | 22-FEB-14:10 | 1.47 |
| March | 0.244777E+11 | 0.52 | 42666.82 | 16-MAR-14:30 | 1.61 |
| April | 0.333201E+11 | 0.65 | 55000.51 | 28-APR-12:10 | 1.78 |
| May | 0.448475E+11 | 0.82 | 55792.63 | 12-MAY-12:10 | 1.79 |
| June | 0.466384E+11 | 0.91 | 48141.98 | 23-JUN-15:10 | 1.68 |
| July | 0.327471E+11 | 0.72 | 28166.44 | 13-JUL-15:10 | 1.33 |
| August | 0.324167E+11 | 0.71 | 29583.78 | 28-AUG-15:09 | 1.36 |
| September | 0.401506E+11 | 0.78 | 56255.38 | 26-SEP-12:10 | 1.79 |
| October | 0.373445E+11 | 0.65 | 53972.99 | 18-OCT-11:10 | 1.75 |
| November | 0.246909E+11 | 0.52 | 47032.45 | 03-NOV-15:00 | 1.66 |
| December | 0.174365E+11 | 0.42 | 24509.01 | 01-DEC-13:05 | 1.27 |
| Annual Sum or Average | 0.370289E+12 | 0.63 | |||
| Minimum of Months | 0.174365E+11 | 0.42 | 24509.01 | 1.27 | |
| Maximum of Months | 0.466384E+11 | 0.91 | 56255.38 | 1.79 |
Report: FanReportMonthly
For: BATH_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
| June | 0.00 | -0.0 | 0.00 | 01-JUN-00:03 | -0.0 |
| July | 0.00 | -0.0 | 0.00 | 01-JUL-00:02 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: GYM_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | -0.0 | 0.00 | 01-MAY-00:03 | 0.00 |
| June | 0.00 | -0.0 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:03 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:03 | 0.00 |
| November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 |
| April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 |
| June | 0.00 | -0.0 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | -0.0 | 0.00 | 01-JUL-00:02 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:03 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 01-OCT-00:03 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
| April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | -0.0 | 0.00 | 01-MAY-00:03 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 |
| August | 0.00 | -0.0 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:03 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:03 | 0.00 |
| November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | -0.0 |
| December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: CAFETERIA_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
| April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | -0.0 | 0.00 | 01-MAY-00:03 | 0.00 |
| June | 0.00 | -0.0 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | -0.0 | 0.00 | 01-JUL-00:02 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:03 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:03 | 0.00 |
| November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.340599E+10 | 1.15 | 3041.40 | 03-JAN-07:01 | 1.57 |
| February | 0.320759E+10 | 1.19 | 3041.40 | 22-FEB-18:20 | 1.58 |
| March | 0.391461E+10 | 1.27 | 3041.40 | 06-MAR-09:40 | 1.57 |
| April | 0.392418E+10 | 1.25 | 3041.40 | 03-APR-11:20 | 1.57 |
| May | 0.461290E+10 | 1.27 | 3041.40 | 08-MAY-15:07 | 1.56 |
| June | 0.487852E+10 | 1.31 | 3041.40 | 02-JUN-15:04 | 1.56 |
| July | 0.495087E+10 | 1.30 | 3041.40 | 01-JUL-09:43 | 1.55 |
| August | 0.506903E+10 | 1.30 | 3041.40 | 04-AUG-08:50 | 1.55 |
| September | 0.442071E+10 | 1.25 | 3041.40 | 01-SEP-12:10 | 1.55 |
| October | 0.405913E+10 | 1.24 | 3041.40 | 16-OCT-14:30 | 1.55 |
| November | 0.355144E+10 | 1.25 | 3041.40 | 02-NOV-15:05 | 1.56 |
| December | 0.325150E+10 | 1.07 | 3041.40 | 15-DEC-11:40 | 1.57 |
| Annual Sum or Average | 0.492465E+11 | 1.24 | |||
| Minimum of Months | 0.320759E+10 | 1.07 | 3041.40 | 1.55 | |
| Maximum of Months | 0.506903E+10 | 1.31 | 3041.40 | 1.58 |
Report: FanReportMonthly
For: PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.558921E+10 | 0.61 | 5259.43 | 02-JAN-08:03 | 1.53 |
| February | 0.506426E+10 | 0.61 | 5259.43 | 01-FEB-07:01 | 1.54 |
| March | 0.610218E+10 | 0.67 | 5259.43 | 01-MAR-08:23 | 1.54 |
| April | 0.541371E+10 | 0.71 | 5259.43 | 03-APR-11:30 | 1.53 |
| May | 0.622377E+10 | 0.86 | 5259.43 | 01-MAY-06:01 | 1.54 |
| June | 0.655164E+10 | 0.98 | 5259.43 | 13-JUN-15:16 | 1.53 |
| July | 0.626550E+10 | 0.94 | 5259.43 | 01-JUL-14:04 | 1.52 |
| August | 0.674969E+10 | 0.93 | 5259.43 | 01-AUG-07:05 | 1.52 |
| September | 0.575461E+10 | 0.85 | 5259.43 | 01-SEP-06:05 | 1.51 |
| October | 0.567123E+10 | 0.68 | 5259.43 | 02-OCT-07:00 | 1.52 |
| November | 0.556902E+10 | 0.63 | 5259.43 | 01-NOV-06:02 | 1.53 |
| December | 0.537043E+10 | 0.59 | 5259.43 | 26-DEC-08:17 | 1.54 |
| Annual Sum or Average | 0.703252E+11 | 0.76 | |||
| Minimum of Months | 0.506426E+10 | 0.59 | 5259.43 | 1.51 | |
| Maximum of Months | 0.674969E+10 | 0.98 | 5259.43 | 1.54 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 36440299.71 | 32796269.74 | 692.08 | 10-JAN-08:61 | 622.87 | 622.87 | 43.43 | 2.22 |
| February | 24368731.84 | 21931858.66 | 692.43 | 01-FEB-08:61 | 623.19 | 623.19 | 44.84 | 2.22 |
| March | 17334073.83 | 15600666.45 | 691.99 | 02-MAR-08:61 | 622.79 | 622.79 | 43.05 | 2.22 |
| April | 5670731.67 | 5103658.50 | 326.29 | 12-APR-07:01 | 293.66 | 293.66 | 56.01 | 0.43 |
| May | 1596896.66 | 1437206.99 | 69.96 | 01-MAY-07:00 | 62.97 | 62.97 | 56.70 | 0.07 |
| June | 66970.15 | 60273.14 | 69.75 | 29-JUN-07:02 | 62.77 | 62.77 | 49.93 | 0.07 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:02 | 0.00 | 0.00 | 50.13 | 0.00 |
| August | 156735.26 | 141061.73 | 69.75 | 14-AUG-07:02 | 62.78 | 62.78 | 50.02 | 0.07 |
| September | 1069630.88 | 962667.79 | 69.96 | 28-SEP-07:02 | 62.97 | 62.97 | 56.61 | 0.07 |
| October | 4612653.49 | 4151388.14 | 70.01 | 06-OCT-15:00 | 63.01 | 63.01 | 57.92 | 0.07 |
| November | 15142066.43 | 13627859.79 | 665.31 | 28-NOV-08:61 | 598.78 | 598.78 | 44.92 | 2.11 |
| December | 47950994.28 | 43155894.85 | 701.34 | 27-DEC-07:03 | 631.21 | 631.21 | 50.90 | 2.25 |
| Annual Sum or Average | 0.154410E+09 | 0.138969E+09 | ||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.05 | 0.00 | |
| Maximum of Months | 47950994.28 | 43155894.85 | 701.34 | 631.21 | 631.21 | 57.92 | 2.25 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 12215899.87 | 3664769.96 | 13.47 | 02-JAN-08:61 | 4.04 | 4.04 | 54.46 | 0.11 |
| February | 11052480.83 | 3315744.25 | 13.47 | 01-FEB-08:61 | 4.04 | 4.04 | 47.29 | 0.11 |
| March | 13379318.90 | 4013795.67 | 13.47 | 01-MAR-08:61 | 4.04 | 4.04 | 47.52 | 0.11 |
| April | 11634190.35 | 3490257.10 | 13.47 | 03-APR-07:03 | 4.04 | 4.04 | 47.24 | 0.11 |
| May | 12797609.38 | 3839282.82 | 13.47 | 01-MAY-07:02 | 4.04 | 4.04 | 48.55 | 0.11 |
| June | 12797609.38 | 3839282.82 | 13.47 | 01-JUN-07:03 | 4.04 | 4.04 | 49.16 | 0.11 |
| July | 11634190.35 | 3490257.10 | 13.47 | 03-JUL-07:03 | 4.04 | 4.04 | 55.30 | 0.11 |
| August | 13379318.90 | 4013795.67 | 13.47 | 01-AUG-07:05 | 4.04 | 4.04 | 55.86 | 0.11 |
| September | 11634190.35 | 3490257.10 | 13.47 | 01-SEP-07:05 | 4.04 | 4.04 | 55.74 | 0.11 |
| October | 12215899.87 | 3664769.96 | 13.47 | 02-OCT-07:03 | 4.04 | 4.04 | 48.86 | 0.11 |
| November | 12215899.87 | 3664769.96 | 13.47 | 01-NOV-07:01 | 4.04 | 4.04 | 49.07 | 0.11 |
| December | 11634190.35 | 3490257.10 | 13.47 | 01-DEC-08:61 | 4.04 | 4.04 | 48.18 | 0.11 |
| Annual Sum or Average | 0.146591E+09 | 43977239.52 | ||||||
| Minimum of Months | 11052480.83 | 3315744.25 | 13.47 | 4.04 | 4.04 | 47.24 | 0.11 | |
| Maximum of Months | 13379318.90 | 4013795.67 | 13.47 | 4.04 | 4.04 | 55.86 | 0.11 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 82.00 | 82.00 | 2275.36 | 367135.78 | 17-JAN-08:61 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 39.37 | 39.37 | 1607.49 | 371579.58 | 03-FEB-08:61 |
| March | 0.00 | 0.00 | 01-MAR-00:05 | 40.95 | 40.95 | 898.52 | 361535.39 | 02-MAR-08:61 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 50.54 | 50.54 | 259.51 | 46712.99 | 12-APR-07:01 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 56.66 | 56.66 | 68.42 | 9771.99 | 25-MAY-07:02 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 50.59 | 50.59 | 3.51 | 9875.33 | 29-JUN-07:02 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 50.13 | 50.13 | 0.00 | 0.00 | 01-JUL-00:02 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 50.13 | 50.13 | 8.42 | 10469.38 | 17-AUG-07:03 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 50.02 | 50.02 | 49.59 | 10349.01 | 08-SEP-07:02 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 55.35 | 55.35 | 196.09 | 9683.21 | 25-OCT-06:04 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 56.30 | 56.30 | 802.36 | 327400.10 | 28-NOV-08:61 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 49.71 | 49.71 | 3261.39 | 404494.94 | 26-DEC-07:01 |
| Annual Sum or Average | 0.00 | 784.69 | ||||||
| Minimum of Months | 0.00 | 0.00 | 39.37 | 39.37 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 82.00 | 82.00 | 3261.39 | 404494.94 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 60.00 | 60.00 | 3230.74 | 16462.82 | 30-JAN-13:30 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 48.79 | 48.79 | 3234.29 | 16460.98 | 01-FEB-14:00 |
| March | 0.00 | 0.00 | 01-MAR-00:05 | 48.98 | 48.98 | 3406.52 | 16152.72 | 01-MAR-13:30 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 49.57 | 49.57 | 2863.23 | 15210.74 | 03-APR-13:00 |
| May | 0.00 | 0.00 | 01-MAY-00:03 | 50.29 | 50.29 | 2808.46 | 14134.48 | 01-MAY-13:00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 51.16 | 51.16 | 1679.54 | 12953.06 | 01-JUN-12:20 |
| July | 0.00 | 0.00 | 01-JUL-00:02 | 51.74 | 51.74 | 548.42 | 3622.11 | 03-JUL-18:30 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 51.97 | 51.97 | 631.75 | 3636.70 | 31-AUG-18:40 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 51.75 | 51.75 | 1532.30 | 12935.15 | 29-SEP-12:50 |
| October | 0.00 | 0.00 | 01-OCT-00:03 | 51.20 | 51.20 | 2679.31 | 14153.67 | 31-OCT-12:20 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 50.36 | 50.36 | 3008.46 | 15297.62 | 30-NOV-13:20 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 49.58 | 49.58 | 2963.56 | 16470.45 | 12-DEC-15:01 |
| Annual Sum or Average | 0.00 | 2376.43 | ||||||
| Minimum of Months | 0.00 | 0.00 | 48.79 | 48.79 | 548.42 | 3622.11 | ||
| Maximum of Months | 0.00 | 0.00 | 60.00 | 60.00 | 3406.52 | 16470.45 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_POD_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.617510E+10 | 0.00 | 0.00 | 0.208993E+11 | 0.00 | 0.00 |
| February | 0.392431E+10 | 0.00 | 0.00 | 0.240061E+11 | 0.00 | 0.00 |
| March | 0.242594E+10 | 0.00 | 0.00 | 0.422958E+11 | 0.00 | 0.00 |
| April | 0.676922E+09 | 0.00 | 0.00 | 0.840521E+11 | 0.00 | 0.00 |
| May | 0.189223E+09 | 0.00 | 0.00 | 0.138328E+12 | 0.00 | 0.00 |
| June | 9488680.10 | 0.00 | 0.00 | 0.174197E+12 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.142795E+12 | 0.00 | 0.00 |
| August | 22867135.62 | 0.00 | 0.00 | 0.129244E+12 | 0.00 | 0.00 |
| September | 0.126768E+09 | 0.00 | 0.00 | 0.137124E+12 | 0.00 | 0.00 |
| October | 0.531005E+09 | 0.00 | 0.00 | 0.931728E+11 | 0.00 | 0.00 |
| November | 0.210704E+10 | 0.00 | 0.00 | 0.381742E+11 | 0.00 | 0.00 |
| December | 0.880586E+10 | 0.00 | 0.00 | 0.181037E+11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.249945E+11 | 0.00 | 0.00 | 0.104239E+13 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.181037E+11 | 0.00 | 0.00 |
| Maximum of Months | 0.880586E+10 | 0.00 | 0.00 | 0.174197E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:6
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.356146E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.365784E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.511697E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.743048E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.111684E+11 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.135385E+11 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.139696E+11 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.130706E+11 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.108184E+11 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.764287E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.437307E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.331586E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.976640E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.331586E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.139696E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:7
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.564176E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.543616E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.733848E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.967070E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.151044E+11 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.200100E+11 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.170695E+11 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.160496E+11 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.152674E+11 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.103456E+11 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.635469E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.537556E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.133664E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.537556E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.200100E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_POD_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.185142E+11 | 0.781355E+10 | 0.165079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.177052E+11 | 0.217928E+11 | 0.110252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.244777E+11 | 0.631613E+11 | 0.628707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.333201E+11 | 0.189026E+12 | 0.870330E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.448475E+11 | 0.350786E+12 | 0.189223E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.466384E+11 | 0.459466E+12 | 9488680.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.327471E+11 | 0.415620E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.324167E+11 | 0.361540E+12 | 22867135.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.401506E+11 | 0.369284E+12 | 0.126768E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.373445E+11 | 0.210466E+12 | 0.547427E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.246909E+11 | 0.474797E+11 | 0.547115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.174365E+11 | 0.211448E+10 | 0.272472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.370289E+12 | 0.249855E+13 | 0.683046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.174365E+11 | 0.211448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.466384E+11 | 0.459466E+12 | 0.272472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:6
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.340599E+10 | 0.587401E+09 | 1558120.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.320759E+10 | 0.181763E+10 | 3124198.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.391461E+10 | 0.484796E+10 | 3683193.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.392418E+10 | 0.138764E+11 | 8040727.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.461290E+10 | 0.254197E+11 | 6885416.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.487852E+10 | 0.317232E+11 | 927713.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.495087E+10 | 0.346679E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.506903E+10 | 0.308642E+11 | 1056040.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.442071E+10 | 0.252837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.405913E+10 | 0.145748E+11 | 547802.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.355144E+10 | 0.328911E+10 | 2901859.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.325150E+10 | 0.242222E+09 | 1201311.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.492465E+11 | 0.187194E+12 | 29926383.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.320759E+10 | 0.242222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.506903E+10 | 0.346679E+11 | 8040727.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:7
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.558921E+10 | 0.193210E+09 | 0.253937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.506426E+10 | 0.142456E+10 | 0.190768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.610218E+10 | 0.473545E+10 | 0.962608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.541371E+10 | 0.163342E+11 | 92493145.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.622377E+10 | 0.338034E+11 | 19836167.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.655164E+10 | 0.482929E+11 | 6894350.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.626550E+10 | 0.400291E+11 | 8276920.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.674969E+10 | 0.340905E+11 | 2026420.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.575461E+10 | 0.371086E+11 | 2028938.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.567123E+10 | 0.186269E+11 | 17767074.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.556902E+10 | 0.302311E+10 | 0.857732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.537043E+10 | 18086343.79 | 0.430112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.703252E+11 | 0.237680E+12 | 0.107178E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.506426E+10 | 18086343.79 | 2026420.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.674969E+10 | 0.482929E+11 | 0.430112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_POD_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.185142E+11 | 0.617510E+10 | 0.00 | 0.00 | 0.238509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.177052E+11 | 0.392431E+10 | 0.00 | 0.00 | 0.630096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.244777E+11 | 0.242594E+10 | 0.00 | 0.00 | 0.178181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.333201E+11 | 0.676922E+09 | 0.00 | 0.00 | 0.507320E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.448475E+11 | 0.189223E+09 | 0.00 | 0.00 | 0.934802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.466384E+11 | 9488680.10 | 0.00 | 0.00 | 0.127559E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.327471E+11 | 0.00 | 0.00 | 0.00 | 0.110048E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.324167E+11 | 22867135.62 | 0.00 | 0.00 | 0.968277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.401506E+11 | 0.126768E+09 | 0.00 | 0.00 | 0.969729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.373445E+11 | 0.531005E+09 | 0.00 | 0.00 | 0.558283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.246909E+11 | 0.210704E+10 | 0.00 | 0.00 | 0.134834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.174365E+11 | 0.880586E+10 | 0.00 | 0.00 | 0.667210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.370289E+12 | 0.249945E+11 | 0.00 | 0.00 | 0.672103E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.174365E+11 | 0.00 | 0.00 | 0.00 | 0.667210E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.466384E+11 | 0.880586E+10 | 0.00 | 0.00 | 0.127559E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:6
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.340599E+10 | 0.00 | 0.00 | 0.00 | 0.155472E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.320759E+10 | 0.00 | 0.00 | 0.00 | 0.450246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.391461E+10 | 0.00 | 0.00 | 0.00 | 0.120236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.392418E+10 | 0.00 | 0.00 | 0.00 | 0.350630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.461290E+10 | 0.00 | 0.00 | 0.00 | 0.655550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.487852E+10 | 0.00 | 0.00 | 0.00 | 0.866000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.495087E+10 | 0.00 | 0.00 | 0.00 | 0.901871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.506903E+10 | 0.00 | 0.00 | 0.00 | 0.800158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.442071E+10 | 0.00 | 0.00 | 0.00 | 0.639764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.405913E+10 | 0.00 | 0.00 | 0.00 | 0.358374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.355144E+10 | 0.00 | 0.00 | 0.00 | 0.821633E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.325150E+10 | 0.00 | 0.00 | 0.00 | 64354098.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.492465E+11 | 0.00 | 0.00 | 0.00 | 0.484175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.320759E+10 | 0.00 | 0.00 | 0.00 | 64354098.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.506903E+10 | 0.00 | 0.00 | 0.00 | 0.901871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:7
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.558921E+10 | 0.00 | 0.00 | 0.00 | 52550201.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.506426E+10 | 0.00 | 0.00 | 0.00 | 0.371902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.610218E+10 | 0.00 | 0.00 | 0.00 | 0.123631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.541371E+10 | 0.00 | 0.00 | 0.00 | 0.425700E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.622377E+10 | 0.00 | 0.00 | 0.00 | 0.888062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.655164E+10 | 0.00 | 0.00 | 0.00 | 0.134583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.626550E+10 | 0.00 | 0.00 | 0.00 | 0.108040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.674969E+10 | 0.00 | 0.00 | 0.00 | 0.929986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.575461E+10 | 0.00 | 0.00 | 0.00 | 0.951277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.567123E+10 | 0.00 | 0.00 | 0.00 | 0.467442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.556902E+10 | 0.00 | 0.00 | 0.00 | 0.785670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.537043E+10 | 0.00 | 0.00 | 0.00 | 5128089.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.703252E+11 | 0.00 | 0.00 | 0.00 | 0.633385E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.506426E+10 | 0.00 | 0.00 | 0.00 | 5128089.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.674969E+10 | 0.00 | 0.00 | 0.00 | 0.134583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.150251E+10 | 0.00 | 0.00 | 3370914.05 | 0.00 | 26449294.52 | 0.222873E+10 | 0.00 | 0.87 |
| February | 0.123731E+10 | 0.00 | 0.00 | 3185138.18 | 0.00 | 19900054.94 | 0.191957E+10 | 0.00 | 0.95 |
| March | 0.102346E+10 | 0.00 | 0.00 | 4544243.92 | 0.00 | 11017488.31 | 0.234831E+10 | 0.00 | 1.19 |
| April | 0.540936E+09 | 55212647.04 | 0.00 | 4811189.12 | 9720496.77 | 552666.23 | 0.138992E+10 | 0.00 | 1.19 |
| May | 0.328792E+09 | 0.274737E+09 | 0.00 | 4135446.69 | 74137908.29 | 0.00 | 0.547722E+09 | 0.00 | 1.18 |
| June | 0.100972E+09 | 0.102268E+10 | 0.00 | 623853.79 | 0.152128E+09 | 0.00 | 27932860.69 | 0.00 | 1.07 |
| July | 1020514.28 | 0.165670E+10 | 0.00 | 0.00 | 0.691721E+09 | 0.00 | 0.00 | 0.00 | 0.86 |
| August | 39482911.04 | 0.122232E+10 | 0.00 | 29687.38 | 0.288651E+09 | 0.00 | 1575032.80 | 0.00 | 1.01 |
| September | 0.238884E+09 | 0.690602E+09 | 0.00 | 2535153.24 | 0.258960E+09 | 0.00 | 0.240551E+09 | 0.00 | 1.26 |
| October | 0.403714E+09 | 0.160083E+09 | 0.00 | 6705001.58 | 28540366.31 | 0.00 | 0.199690E+10 | 0.00 | 1.54 |
| November | 0.960751E+09 | 0.00 | 0.00 | 5788789.01 | 0.00 | 2189390.10 | 0.292788E+10 | 0.00 | 1.35 |
| December | 0.166031E+10 | 0.00 | 0.00 | 2967063.98 | 0.00 | 43518866.00 | 0.204201E+10 | 0.00 | 0.77 |
| Annual Sum or Average | 0.803815E+10 | 0.508234E+10 | 0.00 | 38696480.94 | 0.150386E+10 | 0.103628E+09 | 0.156711E+11 | 0.00 | 1.10 |
| Minimum of Months | 1020514.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 |
| Maximum of Months | 0.166031E+10 | 0.165670E+10 | 0.00 | 6705001.58 | 0.691721E+09 | 43518866.00 | 0.292788E+10 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.613880E+10 | 0.00 | 0.00 | 19725270.81 | 0.00 | 16962195.70 | 0.126784E+11 | 0.00 | 0.90 |
| February | 0.477674E+10 | 0.00 | 0.00 | 18764273.69 | 0.00 | 12320384.40 | 0.112872E+11 | 0.00 | 0.99 |
| March | 0.392546E+10 | 0.00 | 0.00 | 24500045.78 | 0.00 | 6153422.17 | 0.130526E+11 | 0.00 | 1.23 |
| April | 0.240983E+10 | 0.224378E+09 | 0.00 | 23080811.73 | 47564227.94 | 0.00 | 0.709782E+10 | 0.00 | 1.18 |
| May | 0.154294E+10 | 0.106916E+10 | 0.00 | 19082266.02 | 0.357535E+09 | 0.00 | 0.271119E+10 | 0.00 | 1.12 |
| June | 0.486520E+09 | 0.398423E+10 | 0.00 | 2810836.42 | 0.736517E+09 | 0.00 | 0.130899E+09 | 0.00 | 0.96 |
| July | 4914027.50 | 0.594760E+10 | 0.00 | 0.00 | 0.458652E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
| August | 0.191058E+09 | 0.459108E+10 | 0.00 | 82825.50 | 0.186365E+10 | 0.00 | 6664849.74 | 0.00 | 0.94 |
| September | 0.114821E+10 | 0.275851E+10 | 0.00 | 11027543.59 | 0.127217E+10 | 0.00 | 0.112812E+10 | 0.00 | 1.16 |
| October | 0.186742E+10 | 0.662015E+09 | 0.00 | 31401691.09 | 0.143112E+09 | 0.00 | 0.963855E+10 | 0.00 | 1.48 |
| November | 0.344191E+10 | 0.00 | 0.00 | 30798707.05 | 0.00 | 3535590.89 | 0.156381E+11 | 0.00 | 1.36 |
| December | 0.691572E+10 | 0.00 | 0.00 | 17014885.93 | 0.00 | 42303523.82 | 0.116609E+11 | 0.00 | 0.79 |
| Annual Sum or Average | 0.328495E+11 | 0.192370E+11 | 0.00 | 0.198289E+09 | 0.900707E+10 | 81275116.97 | 0.850305E+11 | 0.00 | 1.08 |
| Minimum of Months | 4914027.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
| Maximum of Months | 0.691572E+10 | 0.594760E+10 | 0.00 | 31401691.09 | 0.458652E+10 | 42303523.82 | 0.156381E+11 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.219922E+10 | 0.00 | 0.00 | 81328.10 | 0.00 | 12974287.89 | 95590375.06 | 0.00 | 0.27 |
| February | 0.166592E+10 | 0.00 | 0.00 | 529382.09 | 0.00 | 6455101.32 | 0.302087E+09 | 0.00 | 0.30 |
| March | 0.121366E+10 | 0.00 | 0.00 | 2176253.32 | 0.00 | 1112595.40 | 0.961862E+09 | 0.00 | 0.39 |
| April | 0.416526E+09 | 49283804.07 | 0.00 | 3897459.61 | 6637492.36 | 0.00 | 0.100248E+10 | 0.00 | 0.47 |
| May | 0.229250E+09 | 0.259344E+09 | 0.00 | 3623284.17 | 49942722.84 | 0.00 | 0.447944E+09 | 0.00 | 0.50 |
| June | 67662673.30 | 0.100625E+10 | 0.00 | 608627.36 | 0.100653E+09 | 0.00 | 23992416.60 | 0.00 | 0.48 |
| July | 685742.66 | 0.145817E+10 | 0.00 | 0.00 | 0.444420E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
| August | 26648706.61 | 0.100983E+10 | 0.00 | 22778.61 | 0.199212E+09 | 0.00 | 965233.04 | 0.00 | 0.40 |
| September | 0.165008E+09 | 0.582076E+09 | 0.00 | 1935936.80 | 0.175347E+09 | 0.00 | 0.174823E+09 | 0.00 | 0.50 |
| October | 0.302857E+09 | 0.127472E+09 | 0.00 | 4698105.21 | 20082339.21 | 0.00 | 0.138593E+10 | 0.00 | 0.57 |
| November | 0.114031E+10 | 0.00 | 0.00 | 2551901.95 | 0.00 | 952754.45 | 0.118676E+10 | 0.00 | 0.41 |
| December | 0.224318E+10 | 0.00 | 0.00 | 8497.14 | 0.00 | 67696553.15 | 30943148.46 | 0.00 | 0.24 |
| Annual Sum or Average | 0.967092E+10 | 0.449242E+10 | 0.00 | 20133554.36 | 0.996294E+09 | 89191292.21 | 0.561338E+10 | 0.00 | 0.41 |
| Minimum of Months | 685742.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
| Maximum of Months | 0.224318E+10 | 0.145817E+10 | 0.00 | 4698105.21 | 0.444420E+09 | 67696553.15 | 0.138593E+10 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.275537E+10 | 0.00 | 0.00 | 311736.19 | 0.00 | 99916652.51 | 0.575899E+09 | 0.00 | 0.78 |
| February | 0.209389E+10 | 0.00 | 0.00 | 689548.71 | 0.00 | 56479185.04 | 0.757888E+09 | 0.00 | 0.84 |
| March | 0.159455E+10 | 0.00 | 0.00 | 2163205.24 | 0.00 | 23291524.30 | 0.143641E+10 | 0.00 | 1.05 |
| April | 0.601538E+09 | 49223896.85 | 0.00 | 3907383.66 | 9874208.70 | 729226.05 | 0.118272E+10 | 0.00 | 1.09 |
| May | 0.330076E+09 | 0.267296E+09 | 0.00 | 3943151.96 | 74223423.54 | 0.00 | 0.524112E+09 | 0.00 | 1.15 |
| June | 0.100637E+09 | 0.102129E+10 | 0.00 | 651793.34 | 0.151206E+09 | 0.00 | 28567803.41 | 0.00 | 1.07 |
| July | 1020139.19 | 0.162371E+10 | 0.00 | 0.00 | 0.681614E+09 | 0.00 | 0.00 | 0.00 | 0.85 |
| August | 40418700.46 | 0.107711E+10 | 0.00 | 9374.19 | 0.324688E+09 | 0.00 | 637138.12 | 0.00 | 0.96 |
| September | 0.247690E+09 | 0.573422E+09 | 0.00 | 1995706.44 | 0.267885E+09 | 0.00 | 0.197305E+09 | 0.00 | 1.14 |
| October | 0.500977E+09 | 0.128530E+09 | 0.00 | 4448384.57 | 30017384.12 | 0.00 | 0.149072E+10 | 0.00 | 1.26 |
| November | 0.161079E+10 | 0.00 | 0.00 | 2613552.77 | 0.00 | 15852670.14 | 0.154625E+10 | 0.00 | 1.06 |
| December | 0.273945E+10 | 0.00 | 0.00 | 245650.38 | 0.00 | 0.157524E+09 | 0.582625E+09 | 0.00 | 0.70 |
| Annual Sum or Average | 0.126164E+11 | 0.474058E+10 | 0.00 | 20979487.45 | 0.153951E+10 | 0.353793E+09 | 0.832314E+10 | 0.00 | 1.00 |
| Minimum of Months | 1020139.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
| Maximum of Months | 0.275537E+10 | 0.162371E+10 | 0.00 | 4448384.57 | 0.681614E+09 | 0.157524E+09 | 0.154625E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.107661E+11 | 0.00 | 0.00 | 2962241.10 | 0.00 | 0.103195E+09 | 0.564432E+10 | 0.00 | 0.78 |
| February | 0.779455E+10 | 0.00 | 0.00 | 5855939.77 | 0.00 | 60498819.64 | 0.615805E+10 | 0.00 | 0.85 |
| March | 0.622814E+10 | 0.00 | 0.00 | 13334015.55 | 0.00 | 17135294.05 | 0.864969E+10 | 0.00 | 1.06 |
| April | 0.286142E+10 | 0.202691E+09 | 0.00 | 18488860.96 | 47565777.21 | 0.00 | 0.589599E+10 | 0.00 | 1.09 |
| May | 0.157035E+10 | 0.103508E+10 | 0.00 | 18102507.95 | 0.357547E+09 | 0.00 | 0.257559E+10 | 0.00 | 1.09 |
| June | 0.485408E+09 | 0.394896E+10 | 0.00 | 2914755.24 | 0.733719E+09 | 0.00 | 0.133181E+09 | 0.00 | 0.96 |
| July | 4914187.56 | 0.563562E+10 | 0.00 | 0.00 | 0.489837E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
| August | 0.197213E+09 | 0.356641E+10 | 0.00 | 6825.59 | 0.286174E+10 | 0.00 | 591819.83 | 0.00 | 0.93 |
| September | 0.118635E+10 | 0.224220E+10 | 0.00 | 8356792.92 | 0.136735E+10 | 0.00 | 0.934440E+09 | 0.00 | 1.06 |
| October | 0.253380E+10 | 0.528588E+09 | 0.00 | 19798337.09 | 0.144841E+09 | 0.00 | 0.700643E+10 | 0.00 | 1.22 |
| November | 0.697027E+10 | 0.00 | 0.00 | 13075153.01 | 0.00 | 13725155.66 | 0.826280E+10 | 0.00 | 1.05 |
| December | 0.115660E+11 | 0.00 | 0.00 | 2390322.44 | 0.00 | 0.176446E+09 | 0.500724E+10 | 0.00 | 0.70 |
| Annual Sum or Average | 0.521645E+11 | 0.171596E+11 | 0.00 | 0.105286E+09 | 0.104111E+11 | 0.371001E+09 | 0.502683E+11 | 0.00 | 0.97 |
| Minimum of Months | 4914187.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
| Maximum of Months | 0.115660E+11 | 0.563562E+10 | 0.00 | 19798337.09 | 0.489837E+10 | 0.176446E+09 | 0.864969E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.151371E+10 | 0.00 | 0.00 | 3306725.48 | 0.00 | 26576028.92 | 0.220122E+10 | 0.00 | 0.86 |
| February | 0.123764E+10 | 0.00 | 0.00 | 3131601.69 | 0.00 | 19971115.57 | 0.190596E+10 | 0.00 | 0.95 |
| March | 0.102857E+10 | 0.00 | 0.00 | 4499500.13 | 0.00 | 10985409.44 | 0.233104E+10 | 0.00 | 1.19 |
| April | 0.543677E+09 | 54826486.34 | 0.00 | 4771437.22 | 9727975.56 | 549286.33 | 0.137796E+10 | 0.00 | 1.19 |
| May | 0.328640E+09 | 0.272675E+09 | 0.00 | 4104285.01 | 74103634.92 | 0.00 | 0.544217E+09 | 0.00 | 1.17 |
| June | 0.100925E+09 | 0.101589E+10 | 0.00 | 615405.86 | 0.152111E+09 | 0.00 | 27761550.73 | 0.00 | 1.06 |
| July | 1020042.51 | 0.161903E+10 | 0.00 | 0.00 | 0.709959E+09 | 0.00 | 0.00 | 0.00 | 0.85 |
| August | 39584364.25 | 0.120326E+10 | 0.00 | 27459.36 | 0.294958E+09 | 0.00 | 1455414.04 | 0.00 | 1.01 |
| September | 0.239280E+09 | 0.685510E+09 | 0.00 | 2521492.48 | 0.258991E+09 | 0.00 | 0.239157E+09 | 0.00 | 1.25 |
| October | 0.404217E+09 | 0.158961E+09 | 0.00 | 6650590.62 | 28678876.26 | 0.00 | 0.198542E+10 | 0.00 | 1.53 |
| November | 0.968672E+09 | 0.00 | 0.00 | 5706805.54 | 0.00 | 3792085.58 | 0.290014E+10 | 0.00 | 1.35 |
| December | 0.167440E+10 | 0.00 | 0.00 | 2886443.03 | 0.00 | 46043691.26 | 0.200828E+10 | 0.00 | 0.77 |
| Annual Sum or Average | 0.808033E+10 | 0.501016E+10 | 0.00 | 38221746.43 | 0.152853E+10 | 0.107918E+09 | 0.155226E+11 | 0.00 | 1.10 |
| Minimum of Months | 1020042.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 |
| Maximum of Months | 0.167440E+10 | 0.161903E+10 | 0.00 | 6650590.62 | 0.709959E+09 | 46043691.26 | 0.290014E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.626102E+10 | 0.00 | 0.00 | 19006820.27 | 0.00 | 17745473.17 | 0.123691E+11 | 0.00 | 0.89 |
| February | 0.482313E+10 | 0.00 | 0.00 | 18350408.67 | 0.00 | 12228401.83 | 0.111245E+11 | 0.00 | 0.99 |
| March | 0.390339E+10 | 0.00 | 0.00 | 24436501.46 | 0.00 | 6114433.24 | 0.130245E+11 | 0.00 | 1.22 |
| April | 0.238886E+10 | 0.222265E+09 | 0.00 | 22972725.77 | 47566042.47 | 0.00 | 0.709150E+10 | 0.00 | 1.18 |
| May | 0.154300E+10 | 0.105923E+10 | 0.00 | 18943803.33 | 0.357549E+09 | 0.00 | 0.269780E+10 | 0.00 | 1.11 |
| June | 0.486224E+09 | 0.394158E+10 | 0.00 | 2761132.67 | 0.736545E+09 | 0.00 | 0.130461E+09 | 0.00 | 0.96 |
| July | 4914214.97 | 0.564097E+10 | 0.00 | 0.00 | 0.489308E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
| August | 0.191609E+09 | 0.443877E+10 | 0.00 | 68223.71 | 0.200599E+10 | 0.00 | 6135766.44 | 0.00 | 0.94 |
| September | 0.115069E+10 | 0.271877E+10 | 0.00 | 10914945.15 | 0.127222E+10 | 0.00 | 0.111764E+10 | 0.00 | 1.15 |
| October | 0.187459E+10 | 0.652865E+09 | 0.00 | 30836358.95 | 0.143300E+09 | 0.00 | 0.952642E+10 | 0.00 | 1.47 |
| November | 0.352089E+10 | 0.00 | 0.00 | 29890628.22 | 0.00 | 3511037.96 | 0.153582E+11 | 0.00 | 1.34 |
| December | 0.715890E+10 | 0.00 | 0.00 | 16242333.19 | 0.00 | 45049943.39 | 0.112321E+11 | 0.00 | 0.78 |
| Annual Sum or Average | 0.333072E+11 | 0.186744E+11 | 0.00 | 0.194424E+09 | 0.945625E+10 | 84649289.59 | 0.836783E+11 | 0.00 | 1.07 |
| Minimum of Months | 4914214.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 |
| Maximum of Months | 0.715890E+10 | 0.564097E+10 | 0.00 | 30836358.95 | 0.489308E+10 | 45049943.39 | 0.153582E+11 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.219934E+10 | 0.00 | 0.00 | 70119.55 | 0.00 | 14289735.51 | 87343230.14 | 0.00 | 0.27 |
| February | 0.166982E+10 | 0.00 | 0.00 | 514531.16 | 0.00 | 6392975.82 | 0.291013E+09 | 0.00 | 0.30 |
| March | 0.120374E+10 | 0.00 | 0.00 | 2184627.16 | 0.00 | 1109346.36 | 0.967728E+09 | 0.00 | 0.39 |
| April | 0.411054E+09 | 49190074.15 | 0.00 | 3900883.09 | 6618109.35 | 0.00 | 0.100632E+10 | 0.00 | 0.47 |
| May | 0.228331E+09 | 0.258507E+09 | 0.00 | 3619349.92 | 49796878.52 | 0.00 | 0.447514E+09 | 0.00 | 0.50 |
| June | 67415622.68 | 0.100280E+10 | 0.00 | 606575.09 | 0.100359E+09 | 0.00 | 23954167.63 | 0.00 | 0.48 |
| July | 683740.13 | 0.143073E+10 | 0.00 | 0.00 | 0.449349E+09 | 0.00 | 0.00 | 0.00 | 0.35 |
| August | 26638383.01 | 0.993423E+09 | 0.00 | 21660.40 | 0.201381E+09 | 0.00 | 893099.15 | 0.00 | 0.40 |
| September | 0.165195E+09 | 0.578193E+09 | 0.00 | 1926924.63 | 0.175525E+09 | 0.00 | 0.173378E+09 | 0.00 | 0.50 |
| October | 0.303198E+09 | 0.126903E+09 | 0.00 | 4667792.72 | 20023694.12 | 0.00 | 0.137673E+10 | 0.00 | 0.57 |
| November | 0.114392E+10 | 0.00 | 0.00 | 2513549.89 | 0.00 | 1020156.19 | 0.116971E+10 | 0.00 | 0.41 |
| December | 0.223853E+10 | 0.00 | 0.00 | 7112.20 | 0.00 | 68559913.26 | 27926739.43 | 0.00 | 0.24 |
| Annual Sum or Average | 0.965786E+10 | 0.443975E+10 | 0.00 | 20033125.80 | 0.100305E+10 | 91372127.15 | 0.557251E+10 | 0.00 | 0.41 |
| Minimum of Months | 683740.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
| Maximum of Months | 0.223853E+10 | 0.143073E+10 | 0.00 | 4667792.72 | 0.449349E+09 | 68559913.26 | 0.137673E+10 | 0.00 | 0.57 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.275896E+10 | 0.00 | 0.00 | 308384.75 | 0.00 | 0.100252E+09 | 0.573886E+09 | 0.00 | 0.78 |
| February | 0.209867E+10 | 0.00 | 0.00 | 687899.40 | 0.00 | 56702165.66 | 0.754457E+09 | 0.00 | 0.84 |
| March | 0.159337E+10 | 0.00 | 0.00 | 2167724.25 | 0.00 | 23304048.24 | 0.143947E+10 | 0.00 | 1.05 |
| April | 0.601876E+09 | 49256742.21 | 0.00 | 3910751.76 | 9879749.99 | 728544.31 | 0.118361E+10 | 0.00 | 1.09 |
| May | 0.330261E+09 | 0.267419E+09 | 0.00 | 3944636.07 | 74265076.84 | 0.00 | 0.524380E+09 | 0.00 | 1.15 |
| June | 0.100694E+09 | 0.102155E+10 | 0.00 | 651940.67 | 0.151291E+09 | 0.00 | 28578703.44 | 0.00 | 1.07 |
| July | 1020711.68 | 0.162362E+10 | 0.00 | 0.00 | 0.682726E+09 | 0.00 | 0.00 | 0.00 | 0.85 |
| August | 40441382.95 | 0.107703E+10 | 0.00 | 9360.72 | 0.325262E+09 | 0.00 | 637459.30 | 0.00 | 0.96 |
| September | 0.248038E+09 | 0.573540E+09 | 0.00 | 1994767.96 | 0.268035E+09 | 0.00 | 0.197075E+09 | 0.00 | 1.14 |
| October | 0.503465E+09 | 0.128576E+09 | 0.00 | 4445500.71 | 30034229.52 | 0.00 | 0.148876E+10 | 0.00 | 1.26 |
| November | 0.161459E+10 | 0.00 | 0.00 | 2607798.76 | 0.00 | 15881090.94 | 0.154342E+10 | 0.00 | 1.06 |
| December | 0.273625E+10 | 0.00 | 0.00 | 242505.59 | 0.00 | 0.163611E+09 | 0.581718E+09 | 0.00 | 0.70 |
| Annual Sum or Average | 0.126276E+11 | 0.474099E+10 | 0.00 | 20971270.63 | 0.154149E+10 | 0.360479E+09 | 0.831600E+10 | 0.00 | 1.00 |
| Minimum of Months | 1020711.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
| Maximum of Months | 0.275896E+10 | 0.162362E+10 | 0.00 | 4445500.71 | 0.682726E+09 | 0.163611E+09 | 0.154342E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.107929E+11 | 0.00 | 0.00 | 2926368.42 | 0.00 | 0.105347E+09 | 0.562501E+10 | 0.00 | 0.78 |
| February | 0.779926E+10 | 0.00 | 0.00 | 5842979.73 | 0.00 | 61989699.17 | 0.615919E+10 | 0.00 | 0.85 |
| March | 0.623180E+10 | 0.00 | 0.00 | 13353311.31 | 0.00 | 17145368.39 | 0.865584E+10 | 0.00 | 1.06 |
| April | 0.285680E+10 | 0.202817E+09 | 0.00 | 18503462.91 | 47593742.54 | 0.00 | 0.590634E+10 | 0.00 | 1.09 |
| May | 0.157127E+10 | 0.103577E+10 | 0.00 | 18109749.20 | 0.357757E+09 | 0.00 | 0.257671E+10 | 0.00 | 1.09 |
| June | 0.485693E+09 | 0.395088E+10 | 0.00 | 2915459.44 | 0.734150E+09 | 0.00 | 0.133232E+09 | 0.00 | 0.96 |
| July | 4917076.76 | 0.563608E+10 | 0.00 | 0.00 | 0.490410E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
| August | 0.197329E+09 | 0.356718E+10 | 0.00 | 6774.31 | 0.286475E+10 | 0.00 | 592223.07 | 0.00 | 0.93 |
| September | 0.118704E+10 | 0.224323E+10 | 0.00 | 8349819.42 | 0.136815E+10 | 0.00 | 0.934287E+09 | 0.00 | 1.06 |
| October | 0.254029E+10 | 0.528811E+09 | 0.00 | 19778934.81 | 0.144926E+09 | 0.00 | 0.700181E+10 | 0.00 | 1.22 |
| November | 0.699392E+10 | 0.00 | 0.00 | 13040140.66 | 0.00 | 13733225.08 | 0.824262E+10 | 0.00 | 1.05 |
| December | 0.115859E+11 | 0.00 | 0.00 | 2356550.46 | 0.00 | 0.178033E+09 | 0.499568E+10 | 0.00 | 0.70 |
| Annual Sum or Average | 0.522471E+11 | 0.171648E+11 | 0.00 | 0.105184E+09 | 0.104214E+11 | 0.376249E+09 | 0.502313E+11 | 0.00 | 0.97 |
| Minimum of Months | 4917076.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
| Maximum of Months | 0.115859E+11 | 0.563608E+10 | 0.00 | 19778934.81 | 0.490410E+10 | 0.178033E+09 | 0.865584E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.150229E+10 | 0.00 | 0.00 | 3368706.59 | 0.00 | 22681669.39 | 0.223069E+10 | 0.00 | 0.87 |
| February | 0.123194E+10 | 0.00 | 0.00 | 3188428.71 | 0.00 | 19455255.27 | 0.192450E+10 | 0.00 | 0.95 |
| March | 0.101624E+10 | 0.00 | 0.00 | 4546398.81 | 0.00 | 10994893.55 | 0.235428E+10 | 0.00 | 1.19 |
| April | 0.542583E+09 | 54968233.10 | 0.00 | 4794860.73 | 9724391.24 | 549760.55 | 0.138390E+10 | 0.00 | 1.19 |
| May | 0.328923E+09 | 0.273303E+09 | 0.00 | 4117796.20 | 74167611.29 | 0.00 | 0.545663E+09 | 0.00 | 1.17 |
| June | 0.101012E+09 | 0.101784E+10 | 0.00 | 618683.51 | 0.152242E+09 | 0.00 | 27827809.61 | 0.00 | 1.06 |
| July | 1020923.15 | 0.164136E+10 | 0.00 | 0.00 | 0.695458E+09 | 0.00 | 0.00 | 0.00 | 0.86 |
| August | 39498729.68 | 0.121409E+10 | 0.00 | 28839.23 | 0.289731E+09 | 0.00 | 1575700.28 | 0.00 | 1.01 |
| September | 0.238631E+09 | 0.687506E+09 | 0.00 | 2531004.38 | 0.259128E+09 | 0.00 | 0.240644E+09 | 0.00 | 1.26 |
| October | 0.403304E+09 | 0.159322E+09 | 0.00 | 6683736.57 | 28603159.90 | 0.00 | 0.199250E+10 | 0.00 | 1.54 |
| November | 0.962137E+09 | 0.00 | 0.00 | 5765955.03 | 0.00 | 2949740.67 | 0.292020E+10 | 0.00 | 1.35 |
| December | 0.166107E+10 | 0.00 | 0.00 | 2963221.58 | 0.00 | 44986335.64 | 0.203835E+10 | 0.00 | 0.77 |
| Annual Sum or Average | 0.802864E+10 | 0.504839E+10 | 0.00 | 38607631.35 | 0.150906E+10 | 0.101618E+09 | 0.156601E+11 | 0.00 | 1.10 |
| Minimum of Months | 1020923.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.77 |
| Maximum of Months | 0.166107E+10 | 0.164136E+10 | 0.00 | 6683736.57 | 0.695458E+09 | 44986335.64 | 0.292020E+10 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.611268E+10 | 0.00 | 0.00 | 19683676.22 | 0.00 | 15424968.47 | 0.126619E+11 | 0.00 | 0.90 |
| February | 0.465980E+10 | 0.00 | 0.00 | 18918983.57 | 0.00 | 12258842.27 | 0.114088E+11 | 0.00 | 0.99 |
| March | 0.380004E+10 | 0.00 | 0.00 | 24919659.28 | 0.00 | 6127339.31 | 0.132264E+11 | 0.00 | 1.23 |
| April | 0.236647E+10 | 0.223564E+09 | 0.00 | 23264166.70 | 47565605.72 | 0.00 | 0.716089E+10 | 0.00 | 1.18 |
| May | 0.153917E+10 | 0.106486E+10 | 0.00 | 19143081.92 | 0.357546E+09 | 0.00 | 0.272058E+10 | 0.00 | 1.12 |
| June | 0.486219E+09 | 0.396630E+10 | 0.00 | 2810915.24 | 0.736539E+09 | 0.00 | 0.131169E+09 | 0.00 | 0.96 |
| July | 4914169.84 | 0.582958E+10 | 0.00 | 0.00 | 0.470437E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
| August | 0.191063E+09 | 0.454119E+10 | 0.00 | 78499.25 | 0.190813E+10 | 0.00 | 6669371.45 | 0.00 | 0.94 |
| September | 0.114825E+10 | 0.274545E+10 | 0.00 | 11041846.33 | 0.126731E+10 | 0.00 | 0.112822E+10 | 0.00 | 1.16 |
| October | 0.186537E+10 | 0.656648E+09 | 0.00 | 31237931.41 | 0.143228E+09 | 0.00 | 0.960089E+10 | 0.00 | 1.48 |
| November | 0.343868E+10 | 0.00 | 0.00 | 30514874.26 | 0.00 | 3519164.28 | 0.155604E+11 | 0.00 | 1.35 |
| December | 0.695205E+10 | 0.00 | 0.00 | 16979440.82 | 0.00 | 37987448.93 | 0.116193E+11 | 0.00 | 0.79 |
| Annual Sum or Average | 0.325647E+11 | 0.190276E+11 | 0.00 | 0.198593E+09 | 0.916468E+10 | 75317763.27 | 0.852252E+11 | 0.00 | 1.07 |
| Minimum of Months | 4914169.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.79 |
| Maximum of Months | 0.695205E+10 | 0.582958E+10 | 0.00 | 31237931.41 | 0.470437E+10 | 37987448.93 | 0.155604E+11 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.218152E+10 | 0.00 | 0.00 | 128089.35 | 0.00 | 7591159.30 | 0.131848E+09 | 0.00 | 0.27 |
| February | 0.162501E+10 | 0.00 | 0.00 | 650078.61 | 0.00 | 3206138.81 | 0.368148E+09 | 0.00 | 0.30 |
| March | 0.112149E+10 | 0.00 | 0.00 | 2460530.23 | 0.00 | 783813.83 | 0.110782E+10 | 0.00 | 0.41 |
| April | 0.394508E+09 | 50642791.03 | 0.00 | 4107103.05 | 6674778.02 | 0.00 | 0.106602E+10 | 0.00 | 0.48 |
| May | 0.227101E+09 | 0.265111E+09 | 0.00 | 3749277.16 | 50161679.14 | 0.00 | 0.465912E+09 | 0.00 | 0.51 |
| June | 67829262.22 | 0.102692E+10 | 0.00 | 641405.49 | 0.100729E+09 | 0.00 | 25009181.92 | 0.00 | 0.49 |
| July | 689594.77 | 0.155816E+10 | 0.00 | 0.00 | 0.422903E+09 | 0.00 | 0.00 | 0.00 | 0.37 |
| August | 26290719.74 | 0.107703E+10 | 0.00 | 32224.39 | 0.186823E+09 | 0.00 | 1492273.69 | 0.00 | 0.42 |
| September | 0.163824E+09 | 0.601877E+09 | 0.00 | 2006019.79 | 0.175195E+09 | 0.00 | 0.182103E+09 | 0.00 | 0.51 |
| October | 0.292023E+09 | 0.129782E+09 | 0.00 | 4892855.02 | 20135776.64 | 0.00 | 0.144029E+10 | 0.00 | 0.59 |
| November | 0.109171E+10 | 0.00 | 0.00 | 2735025.09 | 0.00 | 800864.38 | 0.128218E+10 | 0.00 | 0.42 |
| December | 0.222837E+10 | 0.00 | 0.00 | 26100.51 | 0.00 | 58016605.54 | 67709433.34 | 0.00 | 0.25 |
| Annual Sum or Average | 0.942037E+10 | 0.470953E+10 | 0.00 | 21428708.68 | 0.962623E+09 | 70398581.86 | 0.613853E+10 | 0.00 | 0.42 |
| Minimum of Months | 689594.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
| Maximum of Months | 0.222837E+10 | 0.155816E+10 | 0.00 | 4892855.02 | 0.422903E+09 | 58016605.54 | 0.144029E+10 | 0.00 | 0.59 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.272546E+10 | 0.00 | 0.00 | 339570.05 | 0.00 | 99057764.25 | 0.608564E+09 | 0.00 | 0.78 |
| February | 0.205945E+10 | 0.00 | 0.00 | 746637.75 | 0.00 | 56471950.63 | 0.794986E+09 | 0.00 | 0.85 |
| March | 0.155808E+10 | 0.00 | 0.00 | 2262158.84 | 0.00 | 21114570.95 | 0.148289E+10 | 0.00 | 1.05 |
| April | 0.596111E+09 | 49719662.93 | 0.00 | 3977422.66 | 9878915.03 | 707197.06 | 0.119841E+10 | 0.00 | 1.10 |
| May | 0.328874E+09 | 0.269882E+09 | 0.00 | 3988387.84 | 74145982.08 | 0.00 | 0.530132E+09 | 0.00 | 1.16 |
| June | 0.100570E+09 | 0.102879E+10 | 0.00 | 662857.39 | 0.151231E+09 | 0.00 | 28901735.19 | 0.00 | 1.07 |
| July | 1020625.42 | 0.167225E+10 | 0.00 | 0.00 | 0.655644E+09 | 0.00 | 0.00 | 0.00 | 0.85 |
| August | 40242478.12 | 0.110210E+10 | 0.00 | 10590.15 | 0.312425E+09 | 0.00 | 833154.85 | 0.00 | 0.97 |
| September | 0.247564E+09 | 0.579235E+09 | 0.00 | 2009743.32 | 0.267908E+09 | 0.00 | 0.198477E+09 | 0.00 | 1.14 |
| October | 0.502418E+09 | 0.129594E+09 | 0.00 | 4492648.63 | 30031691.25 | 0.00 | 0.149889E+10 | 0.00 | 1.27 |
| November | 0.159324E+10 | 0.00 | 0.00 | 2654842.99 | 0.00 | 15881631.20 | 0.157049E+10 | 0.00 | 1.06 |
| December | 0.271761E+10 | 0.00 | 0.00 | 276300.68 | 0.00 | 0.155424E+09 | 0.608264E+09 | 0.00 | 0.70 |
| Annual Sum or Average | 0.124706E+11 | 0.483158E+10 | 0.00 | 21421160.30 | 0.150126E+10 | 0.348657E+09 | 0.852084E+10 | 0.00 | 1.00 |
| Minimum of Months | 1020625.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
| Maximum of Months | 0.272546E+10 | 0.167225E+10 | 0.00 | 4492648.63 | 0.655644E+09 | 0.155424E+09 | 0.157049E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.694381E+10 | 0.00 | 0.00 | 2157544.24 | 0.00 | 70405188.04 | 0.390129E+10 | 0.00 | 0.78 |
| February | 0.508879E+10 | 0.00 | 0.00 | 4153067.73 | 0.00 | 40439333.34 | 0.414577E+10 | 0.00 | 0.85 |
| March | 0.404751E+10 | 0.00 | 0.00 | 9141958.94 | 0.00 | 11025512.07 | 0.582960E+10 | 0.00 | 1.07 |
| April | 0.185232E+10 | 0.135384E+09 | 0.00 | 12530227.18 | 31437849.50 | 0.00 | 0.397990E+10 | 0.00 | 1.10 |
| May | 0.103096E+10 | 0.695506E+09 | 0.00 | 12228954.81 | 0.236205E+09 | 0.00 | 0.173193E+10 | 0.00 | 1.10 |
| June | 0.320823E+09 | 0.266075E+10 | 0.00 | 1999673.18 | 0.484286E+09 | 0.00 | 89117341.97 | 0.00 | 0.97 |
| July | 3247954.69 | 0.410417E+10 | 0.00 | 0.00 | 0.285811E+10 | 0.00 | 0.00 | 0.00 | 0.81 |
| August | 0.129956E+09 | 0.257598E+10 | 0.00 | 8071.68 | 0.167261E+10 | 0.00 | 776879.20 | 0.00 | 0.93 |
| September | 0.784927E+09 | 0.151039E+10 | 0.00 | 5612788.90 | 0.896031E+09 | 0.00 | 0.620814E+09 | 0.00 | 1.07 |
| October | 0.162995E+10 | 0.354181E+09 | 0.00 | 13326260.86 | 95730521.94 | 0.00 | 0.471833E+10 | 0.00 | 1.23 |
| November | 0.457188E+10 | 0.00 | 0.00 | 8828670.61 | 0.00 | 9179020.94 | 0.552568E+10 | 0.00 | 1.05 |
| December | 0.749815E+10 | 0.00 | 0.00 | 1812905.65 | 0.00 | 0.124028E+09 | 0.344851E+10 | 0.00 | 0.70 |
| Annual Sum or Average | 0.339023E+11 | 0.120364E+11 | 0.00 | 71800123.77 | 0.627440E+10 | 0.255078E+09 | 0.339917E+11 | 0.00 | 0.97 |
| Minimum of Months | 3247954.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.70 |
| Maximum of Months | 0.749815E+10 | 0.410417E+10 | 0.00 | 13326260.86 | 0.285811E+10 | 0.124028E+09 | 0.582960E+10 | 0.00 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.155790E+10 | 0.00 | 0.00 | 4901271.44 | 0.00 | 10706044.31 | 0.411814E+10 | 0.00 | 0.79 |
| February | 0.838239E+09 | 0.00 | 0.00 | 6071619.78 | 0.00 | 4894414.38 | 0.415320E+10 | 0.00 | 0.90 |
| March | 0.726086E+09 | 0.00 | 0.00 | 9972645.82 | 0.00 | 2843138.24 | 0.487512E+10 | 0.00 | 1.21 |
| April | 0.664163E+09 | 97245615.22 | 0.00 | 9763529.69 | 16157135.06 | 0.00 | 0.274405E+10 | 0.00 | 1.28 |
| May | 0.502250E+09 | 0.497873E+09 | 0.00 | 7960391.29 | 0.120949E+09 | 0.00 | 0.107235E+10 | 0.00 | 1.28 |
| June | 0.161658E+09 | 0.191967E+10 | 0.00 | 1602424.79 | 0.242560E+09 | 0.00 | 63748938.76 | 0.00 | 1.22 |
| July | 1669250.39 | 0.292536E+10 | 0.00 | 0.00 | 0.936528E+09 | 0.00 | 0.00 | 0.00 | 0.87 |
| August | 59774096.76 | 0.193705E+10 | 0.00 | 125744.62 | 0.406904E+09 | 0.00 | 7309339.78 | 0.00 | 0.99 |
| September | 0.380167E+09 | 0.114361E+10 | 0.00 | 4142577.90 | 0.421166E+09 | 0.00 | 0.407524E+09 | 0.00 | 1.29 |
| October | 0.632710E+09 | 0.231319E+09 | 0.00 | 10259767.45 | 49005643.72 | 0.00 | 0.312894E+10 | 0.00 | 1.44 |
| November | 0.877597E+09 | 0.00 | 0.00 | 9238786.60 | 0.00 | 1298242.08 | 0.483174E+10 | 0.00 | 1.18 |
| December | 0.206294E+10 | 0.00 | 0.00 | 3954798.58 | 0.00 | 24637064.97 | 0.367733E+10 | 0.00 | 0.72 |
| Annual Sum or Average | 0.846516E+10 | 0.875212E+10 | 0.00 | 67993557.96 | 0.219327E+10 | 44378903.98 | 0.290794E+11 | 0.00 | 1.10 |
| Minimum of Months | 1669250.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.72 |
| Maximum of Months | 0.206294E+10 | 0.292536E+10 | 0.00 | 10259767.45 | 0.936528E+09 | 24637064.97 | 0.487512E+10 | 0.00 | 1.44 |
Report: MechanicalVentilationLoadsMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.505530E+10 | 0.00 | 0.00 | 2895.83 | 0.00 | 27775181.90 | 30417993.55 | 0.00 | 0.21 |
| February | 0.353504E+10 | 0.00 | 0.00 | 1234461.50 | 0.00 | 7782265.66 | 0.841015E+09 | 0.00 | 0.23 |
| March | 0.184872E+10 | 0.00 | 0.00 | 7534791.08 | 0.00 | 578103.89 | 0.354967E+10 | 0.00 | 0.35 |
| April | 0.599699E+09 | 0.128845E+09 | 0.00 | 13075232.35 | 14705961.52 | 0.00 | 0.351866E+10 | 0.00 | 0.46 |
| May | 0.443650E+09 | 0.728529E+09 | 0.00 | 12014403.34 | 0.107692E+09 | 0.00 | 0.153908E+10 | 0.00 | 0.49 |
| June | 0.146555E+09 | 0.282704E+10 | 0.00 | 2411650.11 | 0.210104E+09 | 0.00 | 90113905.24 | 0.00 | 0.47 |
| July | 1519324.55 | 0.513604E+10 | 0.00 | 0.00 | 0.785168E+09 | 0.00 | 0.00 | 0.00 | 0.39 |
| August | 53083270.31 | 0.329712E+10 | 0.00 | 361296.36 | 0.343138E+09 | 0.00 | 9928712.97 | 0.00 | 0.42 |
| September | 0.337436E+09 | 0.156208E+10 | 0.00 | 5900135.67 | 0.380191E+09 | 0.00 | 0.544072E+09 | 0.00 | 0.45 |
| October | 0.588870E+09 | 0.304778E+09 | 0.00 | 12042462.66 | 42561058.36 | 0.00 | 0.349995E+10 | 0.00 | 0.48 |
| November | 0.252795E+10 | 0.00 | 0.00 | 5408710.18 | 0.00 | 1427473.01 | 0.262145E+10 | 0.00 | 0.32 |
| December | 0.496334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228587E+09 | 0.00 | 0.00 | 0.19 |
| Annual Sum or Average | 0.201012E+11 | 0.139844E+11 | 0.00 | 59986039.08 | 0.188356E+10 | 0.266150E+09 | 0.162444E+11 | 0.00 | 0.37 |
| Minimum of Months | 1519324.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
| Maximum of Months | 0.505530E+10 | 0.513604E+10 | 0.00 | 13075232.35 | 0.785168E+09 | 0.228587E+09 | 0.354967E+10 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.123126E+10 | 0.00 | 0.00 | 12936.97 | 0.00 | 0.188476E+10 | 13528287.59 | 0.00 | 0.40 |
| February | 0.109518E+10 | 0.00 | 0.00 | 318145.49 | 0.00 | 0.140727E+10 | 0.124212E+09 | 0.00 | 0.43 |
| March | 0.135650E+10 | 0.00 | 0.00 | 917297.31 | 0.00 | 0.105172E+10 | 0.265787E+09 | 0.00 | 0.52 |
| April | 0.835987E+09 | 77762868.61 | 0.00 | 4534895.16 | 7776792.45 | 0.302276E+09 | 0.367079E+09 | 0.00 | 0.60 |
| May | 0.342296E+09 | 0.412534E+09 | 0.00 | 5648644.00 | 58262949.71 | 70373908.88 | 0.338340E+09 | 0.00 | 0.72 |
| June | 82562222.43 | 0.167024E+10 | 0.00 | 879336.38 | 0.117010E+09 | 2167125.89 | 27871400.30 | 0.00 | 0.81 |
| July | 808893.22 | 0.308938E+10 | 0.00 | 0.00 | 0.485595E+09 | 0.00 | 0.00 | 0.00 | 0.74 |
| August | 27630018.78 | 0.217541E+10 | 0.00 | 38949.54 | 0.201205E+09 | 3821717.21 | 1298571.74 | 0.00 | 0.79 |
| September | 0.199813E+09 | 0.103538E+10 | 42678.21 | 3849822.91 | 0.201210E+09 | 42712759.03 | 0.185574E+09 | 3155.11 | 0.82 |
| October | 0.683651E+09 | 0.221289E+09 | 0.00 | 4728985.28 | 21592027.53 | 0.233209E+09 | 0.914106E+09 | 0.00 | 0.76 |
| November | 0.134540E+10 | 0.00 | 0.00 | 1298200.37 | 0.00 | 0.889031E+09 | 0.525766E+09 | 0.00 | 0.53 |
| December | 0.102869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228007E+10 | 0.00 | 0.00 | 0.37 |
| Annual Sum or Average | 0.822977E+10 | 0.868200E+10 | 42678.21 | 22227213.41 | 0.109265E+10 | 0.816741E+10 | 0.276356E+10 | 3155.11 | 0.63 |
| Minimum of Months | 808893.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
| Maximum of Months | 0.135650E+10 | 0.308938E+10 | 42678.21 | 5648644.00 | 0.485595E+09 | 0.228007E+10 | 0.914106E+09 | 3155.11 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.346833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
| February | 0.269207E+10 | 0.00 | 0.00 | 205371.43 | 0.00 | 0.00 | 0.242967E+09 | 0.00 | 0.34 |
| March | 0.172174E+10 | 0.00 | 0.00 | 3112218.61 | 0.00 | 0.00 | 0.135929E+10 | 0.00 | 0.42 |
| April | 0.513451E+09 | 49363408.22 | 0.00 | 6670153.90 | 7615331.40 | 0.00 | 0.134165E+10 | 0.00 | 0.45 |
| May | 0.308958E+09 | 0.275448E+09 | 0.00 | 6698349.39 | 49141380.70 | 0.00 | 0.568047E+09 | 0.00 | 0.45 |
| June | 87997818.46 | 0.102400E+10 | 0.00 | 1971840.37 | 0.111043E+09 | 0.00 | 54596445.91 | 0.00 | 0.43 |
| July | 922910.89 | 0.118728E+10 | 0.00 | 46070.96 | 0.105703E+10 | 0.00 | 248849.56 | 0.00 | 0.33 |
| August | 38878049.11 | 0.738273E+09 | 0.00 | 309251.16 | 0.620462E+09 | 0.00 | 4649330.18 | 0.00 | 0.38 |
| September | 0.238078E+09 | 0.585689E+09 | 0.00 | 3355230.37 | 0.256033E+09 | 0.00 | 0.210253E+09 | 0.00 | 0.45 |
| October | 0.591184E+09 | 0.111855E+09 | 0.00 | 5354656.67 | 29248187.61 | 0.00 | 0.129904E+10 | 0.00 | 0.47 |
| November | 0.211764E+10 | 0.00 | 0.00 | 1594649.58 | 0.00 | 0.00 | 0.989769E+09 | 0.00 | 0.40 |
| December | 0.351774E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
| Annual Sum or Average | 0.152970E+11 | 0.397191E+10 | 0.00 | 29317792.44 | 0.213057E+10 | 0.00 | 0.607051E+10 | 0.00 | 0.39 |
| Minimum of Months | 922910.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
| Maximum of Months | 0.351774E+10 | 0.118728E+10 | 0.00 | 6698349.39 | 0.105703E+10 | 0.00 | 0.135929E+10 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.237775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
| February | 0.201229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 |
| March | 0.208620E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
| April | 0.107493E+10 | 21839777.88 | 0.00 | 495576.81 | 12025278.14 | 0.00 | 73498666.50 | 0.00 | 0.36 |
| May | 0.411978E+09 | 0.158822E+09 | 0.00 | 1395303.28 | 41850641.05 | 0.00 | 0.108972E+09 | 0.00 | 0.36 |
| June | 77326548.73 | 0.607191E+09 | 0.00 | 236129.70 | 94217485.55 | 0.00 | 9108034.52 | 0.00 | 0.35 |
| July | 704913.42 | 0.549927E+09 | 0.00 | 2281.59 | 0.973785E+09 | 0.00 | 292.03 | 0.00 | 0.30 |
| August | 28333780.59 | 0.340556E+09 | 0.00 | 10044.24 | 0.589241E+09 | 0.00 | 137445.08 | 0.00 | 0.34 |
| September | 0.244817E+09 | 0.273845E+09 | 0.00 | 691353.66 | 0.239416E+09 | 0.00 | 36537239.18 | 0.00 | 0.37 |
| October | 0.113049E+10 | 50995059.64 | 0.00 | 223210.18 | 35130683.73 | 0.00 | 86739726.41 | 0.00 | 0.39 |
| November | 0.211998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 |
| December | 0.241163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
| Annual Sum or Average | 0.139764E+11 | 0.200317E+10 | 0.00 | 3053899.45 | 0.198567E+10 | 0.00 | 0.314994E+09 | 0.00 | 0.33 |
| Minimum of Months | 704913.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
| Maximum of Months | 0.241163E+10 | 0.607191E+09 | 0.00 | 1395303.28 | 0.973785E+09 | 0.00 | 0.108972E+09 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.324268E+10 | 0.00 | 0.00 | 6692028.49 | 0.00 | 9736392.29 | 0.377295E+10 | 0.00 | 0.37 |
| February | 0.219949E+10 | 0.00 | 0.00 | 8449576.15 | 0.00 | 3960719.47 | 0.434877E+10 | 0.00 | 0.45 |
| March | 0.142815E+10 | 0.00 | 0.00 | 14307762.91 | 0.00 | 1282144.11 | 0.647370E+10 | 0.00 | 0.64 |
| April | 0.772566E+09 | 0.161058E+09 | 0.00 | 17498963.17 | 18825445.64 | 0.00 | 0.458300E+10 | 0.00 | 0.74 |
| May | 0.590426E+09 | 0.882217E+09 | 0.00 | 15025995.86 | 0.124244E+09 | 0.00 | 0.197571E+10 | 0.00 | 0.76 |
| June | 0.193245E+09 | 0.348609E+10 | 0.00 | 3282703.82 | 0.250896E+09 | 0.00 | 0.124853E+09 | 0.00 | 0.75 |
| July | 2048137.21 | 0.647607E+10 | 0.00 | 0.00 | 0.967313E+09 | 0.00 | 0.00 | 0.00 | 0.61 |
| August | 69757639.96 | 0.439300E+10 | 0.00 | 641770.06 | 0.411354E+09 | 0.00 | 17192533.32 | 0.00 | 0.70 |
| September | 0.411272E+09 | 0.230694E+10 | 0.00 | 9329259.71 | 0.449638E+09 | 0.00 | 0.868749E+09 | 0.00 | 0.81 |
| October | 0.706687E+09 | 0.435006E+09 | 0.00 | 20034251.72 | 50064569.35 | 0.00 | 0.551420E+10 | 0.00 | 0.89 |
| November | 0.157361E+10 | 0.00 | 0.00 | 15341162.20 | 0.00 | 396737.13 | 0.686123E+10 | 0.00 | 0.67 |
| December | 0.363615E+10 | 0.00 | 0.00 | 5021985.97 | 0.00 | 35365756.28 | 0.310987E+10 | 0.00 | 0.31 |
| Annual Sum or Average | 0.148261E+11 | 0.181404E+11 | 0.00 | 0.115625E+09 | 0.227234E+10 | 50741749.27 | 0.376502E+11 | 0.00 | 0.64 |
| Minimum of Months | 2048137.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
| Maximum of Months | 0.363615E+10 | 0.647607E+10 | 0.00 | 20034251.72 | 0.967313E+09 | 35365756.28 | 0.686123E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.364594E+10 | 0.00 | 0.00 | 6837627.36 | 0.00 | 940888.51 | 0.647749E+10 | 0.00 | 0.64 |
| February | 0.186301E+10 | 0.00 | 0.00 | 11732375.25 | 0.00 | 0.00 | 0.719785E+10 | 0.00 | 0.76 |
| March | 0.139803E+10 | 0.00 | 0.00 | 20877990.85 | 0.00 | 0.00 | 0.963218E+10 | 0.00 | 1.11 |
| April | 0.971551E+09 | 0.214100E+09 | 0.00 | 21361522.48 | 28011412.07 | 0.00 | 0.585974E+10 | 0.00 | 1.18 |
| May | 0.697888E+09 | 0.110808E+10 | 0.00 | 17074654.54 | 0.200665E+09 | 0.00 | 0.233124E+10 | 0.00 | 1.15 |
| June | 0.243140E+09 | 0.401597E+10 | 0.00 | 4012615.98 | 0.392980E+09 | 0.00 | 0.171140E+09 | 0.00 | 1.07 |
| July | 2221079.95 | 0.697319E+10 | 0.00 | 260482.33 | 0.132440E+10 | 0.00 | 1216214.68 | 0.00 | 0.85 |
| August | 91119073.24 | 0.459621E+10 | 0.00 | 1254551.89 | 0.535957E+09 | 0.00 | 37444040.01 | 0.00 | 0.96 |
| September | 0.566334E+09 | 0.228124E+10 | 0.00 | 8977961.05 | 0.705039E+09 | 0.00 | 0.876682E+09 | 0.00 | 1.10 |
| October | 0.111815E+10 | 0.443540E+09 | 0.00 | 18504284.07 | 79716947.09 | 0.00 | 0.562667E+10 | 0.00 | 1.20 |
| November | 0.225897E+10 | 0.00 | 0.00 | 15850488.88 | 0.00 | 0.00 | 0.788770E+10 | 0.00 | 0.96 |
| December | 0.518465E+10 | 0.00 | 0.00 | 3913436.95 | 0.00 | 53512408.52 | 0.495954E+10 | 0.00 | 0.58 |
| Annual Sum or Average | 0.180410E+11 | 0.196323E+11 | 0.00 | 0.130658E+09 | 0.326677E+10 | 54453297.03 | 0.510589E+11 | 0.00 | 0.96 |
| Minimum of Months | 2221079.95 | 0.00 | 0.00 | 260482.33 | 0.00 | 0.00 | 1216214.68 | 0.00 | 0.58 |
| Maximum of Months | 0.518465E+10 | 0.697319E+10 | 0.00 | 21361522.48 | 0.132440E+10 | 53512408.52 | 0.963218E+10 | 0.00 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 233081.71 | 0.00 | 0.00 | 39003467.82 | 0.00 | 2295745.27 | 0.239565E+11 | 0.00 | 2.40 |
| February | 601823.86 | 0.00 | 0.00 | 38060326.23 | 0.00 | 3118380.02 | 0.217569E+11 | 0.00 | 2.87 |
| March | 0.00 | 0.00 | 0.00 | 47088436.51 | 0.00 | 2142320.49 | 0.246237E+11 | 0.00 | 3.67 |
| April | 0.00 | 45430592.63 | 0.00 | 49195188.93 | 0.00 | 1801962.38 | 0.159352E+11 | 0.00 | 3.26 |
| May | 0.00 | 0.743467E+09 | 0.00 | 47115336.49 | 0.00 | 933440.51 | 0.909167E+10 | 0.00 | 2.89 |
| June | 44266.65 | 0.185147E+10 | 0.00 | 39544835.19 | 0.00 | 97036.03 | 0.348460E+10 | 0.00 | 2.68 |
| July | 0.00 | 0.584271E+10 | 0.00 | 13502724.24 | 448715.22 | 0.00 | 0.102090E+10 | 0.00 | 3.07 |
| August | 0.00 | 0.324056E+10 | 0.00 | 22827621.95 | 2097697.70 | 42924.16 | 0.337032E+10 | 0.00 | 3.27 |
| September | 31557.37 | 0.139039E+10 | 0.00 | 38203390.40 | 227984.44 | 0.00 | 0.640800E+10 | 0.00 | 3.04 |
| October | 0.00 | 0.371041E+09 | 0.00 | 46858307.95 | 626916.63 | 230332.77 | 0.162824E+11 | 0.00 | 3.76 |
| November | 441545.92 | 0.00 | 0.00 | 44342706.43 | 0.00 | 1775926.53 | 0.233364E+11 | 0.00 | 3.35 |
| December | 0.00 | 0.00 | 0.00 | 36927554.35 | 0.00 | 1342488.74 | 0.230608E+11 | 0.00 | 2.05 |
| Annual Sum or Average | 1352275.51 | 0.134851E+11 | 0.00 | 0.462670E+09 | 3401314.00 | 13780556.91 | 0.172327E+12 | 0.00 | 3.03 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 13502724.24 | 0.00 | 0.00 | 0.102090E+10 | 0.00 | 2.05 |
| Maximum of Months | 601823.86 | 0.584271E+10 | 0.00 | 49195188.93 | 2097697.70 | 3118380.02 | 0.246237E+11 | 0.00 | 3.76 |
Report: MechanicalVentilationLoadsMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.887051E+10 | 0.00 | 0.00 | 16019409.69 | 0.00 | 0.353012E+09 | 0.205638E+11 | 0.00 | 1.85 |
| February | 0.660930E+10 | 0.00 | 0.00 | 17237089.12 | 0.00 | 0.452586E+09 | 0.190537E+11 | 0.00 | 2.08 |
| March | 0.385105E+10 | 0.00 | 0.00 | 27767746.44 | 0.00 | 95953306.36 | 0.246319E+11 | 0.00 | 2.74 |
| April | 0.969163E+09 | 0.194670E+09 | 0.00 | 32745699.44 | 0.00 | 2747834.08 | 0.148239E+11 | 0.00 | 2.45 |
| May | 78536974.50 | 0.251397E+10 | 122185.62 | 30818439.87 | 0.00 | 3631456.94 | 0.737067E+10 | 33395.51 | 2.47 |
| June | 198493.67 | 0.767232E+10 | 1136249.81 | 16389412.83 | 3034216.05 | 389981.61 | 0.151376E+10 | 16837.57 | 2.43 |
| July | 0.00 | 0.173041E+11 | 3225869.48 | 2273117.76 | 18414791.09 | 0.00 | 0.293388E+09 | 31299.91 | 2.29 |
| August | 2861832.41 | 0.119498E+11 | 253373.82 | 5766116.81 | 4162271.12 | 0.00 | 0.167861E+10 | 14057.56 | 2.61 |
| September | 54354996.04 | 0.492327E+10 | 934999.17 | 18570739.26 | 0.00 | 0.00 | 0.324992E+10 | 7612.23 | 2.34 |
| October | 0.110520E+10 | 0.127579E+10 | 0.00 | 28183279.23 | 0.00 | 0.00 | 0.153409E+11 | 0.00 | 2.75 |
| November | 0.438559E+10 | 0.00 | 0.00 | 24666151.00 | 0.00 | 24636642.59 | 0.229331E+11 | 0.00 | 2.48 |
| December | 0.106350E+11 | 0.00 | 0.00 | 13082478.06 | 0.00 | 0.130212E+10 | 0.183828E+11 | 0.00 | 1.66 |
| Annual Sum or Average | 0.365617E+11 | 0.458340E+11 | 5672677.89 | 0.233520E+09 | 25611278.26 | 0.223508E+10 | 0.149837E+12 | 103202.77 | 2.35 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 2273117.76 | 0.00 | 0.00 | 0.293388E+09 | 0.00 | 1.66 |
| Maximum of Months | 0.106350E+11 | 0.173041E+11 | 3225869.48 | 32745699.44 | 18414791.09 | 0.130212E+10 | 0.246319E+11 | 33395.51 | 2.75 |
Report: MechanicalVentilationLoadsMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.331212E+10 | 0.00 | 0.00 | 7330266.35 | 0.00 | 12577030.05 | 0.488290E+10 | 0.00 | 0.47 |
| February | 0.207294E+10 | 0.00 | 0.00 | 9936143.97 | 0.00 | 4036536.77 | 0.564091E+10 | 0.00 | 0.57 |
| March | 0.109599E+10 | 0.00 | 0.00 | 18360023.12 | 0.00 | 866496.41 | 0.847839E+10 | 0.00 | 0.84 |
| April | 0.809798E+09 | 0.177279E+09 | 0.00 | 21508652.92 | 21704327.34 | 0.00 | 0.578205E+10 | 0.00 | 0.97 |
| May | 0.614985E+09 | 0.982879E+09 | 0.00 | 18662405.04 | 0.142033E+09 | 0.00 | 0.252226E+10 | 0.00 | 1.00 |
| June | 0.198689E+09 | 0.384482E+10 | 0.00 | 3979680.23 | 0.279165E+09 | 0.00 | 0.161579E+09 | 0.00 | 0.92 |
| July | 2277253.79 | 0.667595E+10 | 0.00 | 0.00 | 0.110971E+10 | 0.00 | 0.00 | 0.00 | 0.71 |
| August | 76454442.43 | 0.437489E+10 | 0.00 | 673405.68 | 0.480270E+09 | 0.00 | 18664398.69 | 0.00 | 0.79 |
| September | 0.438673E+09 | 0.231674E+10 | 0.00 | 9890635.00 | 0.523941E+09 | 0.00 | 0.100248E+10 | 0.00 | 0.95 |
| October | 0.766509E+09 | 0.450020E+09 | 0.00 | 21575407.28 | 60653695.40 | 0.00 | 0.621962E+10 | 0.00 | 1.07 |
| November | 0.153169E+10 | 0.00 | 0.00 | 16314926.86 | 0.00 | 441118.46 | 0.780770E+10 | 0.00 | 0.80 |
| December | 0.402671E+10 | 0.00 | 0.00 | 5809905.62 | 0.00 | 29336933.86 | 0.418609E+10 | 0.00 | 0.42 |
| Annual Sum or Average | 0.149468E+11 | 0.188226E+11 | 0.00 | 0.134041E+09 | 0.261748E+10 | 47258115.55 | 0.467027E+11 | 0.00 | 0.79 |
| Minimum of Months | 2277253.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
| Maximum of Months | 0.402671E+10 | 0.667595E+10 | 0.00 | 21575407.28 | 0.110971E+10 | 29336933.86 | 0.847839E+10 | 0.00 | 1.07 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:28:01
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.742630E+12 | 0.151994E+11 | 0.139013E+12 | 0.541481E+12 | 0.360359E+11 |
| February | 0.826974E+12 | 0.124239E+11 | 0.111389E+12 | 0.476781E+12 | 0.539702E+11 |
| March | 0.131141E+13 | 0.135627E+11 | 0.109449E+12 | 0.555916E+12 | 0.115156E+12 |
| April | 0.148958E+13 | 0.613136E+10 | 0.625740E+11 | 0.354219E+12 | 0.301568E+12 |
| May | 0.164062E+13 | 0.102008E+10 | 0.301931E+11 | 0.170213E+12 | 0.545395E+12 |
| June | 0.162847E+13 | -0.443850E+10 | -0.260039E+10 | -0.301165E+11 | 0.717047E+12 |
| July | 0.154751E+13 | -0.768972E+10 | -0.541363E+11 | -0.182791E+12 | 0.649758E+12 |
| August | 0.141259E+13 | -0.406940E+10 | -0.246564E+11 | -0.480876E+11 | 0.567659E+12 |
| September | 0.125786E+13 | -0.107228E+10 | 0.728630E+10 | 0.544354E+11 | 0.572136E+12 |
| October | 0.105423E+13 | 0.574335E+10 | 0.617817E+11 | 0.447999E+12 | 0.332236E+12 |
| November | 0.781931E+12 | 0.126141E+11 | 0.129649E+12 | 0.613537E+12 | 0.900746E+11 |
| December | 0.611628E+12 | 0.146919E+11 | 0.162621E+12 | 0.537450E+12 | 0.316903E+11 |
| Annual Sum or Average | 0.143054E+14 | 0.641169E+11 | 0.732563E+12 | 0.349104E+13 | 0.401273E+13 |
| Minimum of Months | 0.611628E+12 | -0.768972E+10 | -0.541363E+11 | -0.182791E+12 | 0.316903E+11 |
| Maximum of Months | 0.164062E+13 | 0.151994E+11 | 0.162621E+12 | 0.613537E+12 | 0.717047E+12 |