Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:30
Tabular Output Report in Format: HTML
Building: SchoolPrimary
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2024-07-03 12:31:19
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 6811.11 | 991.28 | 991.28 |
| Net Site Energy | 6811.11 | 991.28 | 991.28 |
| Total Source Energy | 13995.78 | 2036.93 | 2036.93 |
| Net Source Energy | 13995.78 | 2036.93 | 2036.93 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 6871.00 |
| Net Conditioned Building Area | 6871.00 |
| Unconditioned Building Area | 0.00 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 3100.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 240.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 1218.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 92.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1151.36 | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 406.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 4.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 175.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.47 |
| Refrigeration | 44.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 3174.52 | 3636.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.47 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 1872.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Boiler | 0.00 | 1228.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Cooling | General | 240.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 1218.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 92.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooking | 149.71 | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInFreezer | 31.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInRefrigerator | 23.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | Transformer | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | General | 406.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | General | 4.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Heater | 0.00 | 175.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.99 | |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.48 | |
| Refrigeration | General | 7.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LowTempRefrigeration | 14.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MedTempRefrigeration | 21.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 3100.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 240.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 1218.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 92.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 1151.36 | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 406.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 4.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 0.00 | 175.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.47 |
| Refrigeration | Unassigned | 44.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 190.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 94.67 | 476.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Other | 176.59 | 52.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 462.02 | 529.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 190.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 94.67 | 476.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Other | 176.59 | 52.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 462.02 | 529.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 3174.524 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 3174.524 | 100.00 |
| Total On-Site and Utility Electric Sources | 3174.524 | 100.00 |
| Total Electricity End Uses | 3174.524 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | |
| Air to Air Heat Recovery for Cooling | 0.00 | |
| Air to Air Heat Recovery for Heating | 0.00 | |
| High-Temperature Geothermal* | 0.00 | |
| Solar Water Thermal | 0.00 | |
| Solar Air Thermal | 0.00 | |
| Total On-Site Thermal Sources | 0.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 718.47 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 718.47 | 100.00 |
| Total Water End Uses | 718.47 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 1279.67 |
| Time Setpoint Not Met During Occupied Cooling | 28.00 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 2086.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME SCHOOLPRIMARY
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |ZoneHeatingSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |ZoneElectricSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |SpaceGainsMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |PeakSpaceGainsMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |SpaceGainComponentsAtCoolingPeakMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |ComfortReportSimple55Monthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |OccupantComfortDataSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_POD_1 COOLING COIL | PSZ-AC_1:6 COOLING COIL | PSZ-AC_2:7 COOLING COIL |WindowReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 |WindowEnergyReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 |WindowZoneSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |WindowEnergyZoneSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | VAV_POD_1 HEATING COIL | PSZ-AC_1:6 HEATING COIL | PSZ-AC_2:7 HEATING COIL | VAV_POD_1 COOLING COIL | PSZ-AC_1:6 COOLING COIL | PSZ-AC_2:7 COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| VAV_POD_1 FAN | BATH_ZN_1_FLR_1 EXHAUST FAN | GYM_ZN_1_FLR_1 EXHAUST FAN | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN | KITCHEN_ZN_1_FLR_1 EXHAUST FAN | CAFETERIA_ZN_1_FLR_1 EXHAUST FAN | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_POD_1 | PSZ-AC_1:6 | PSZ-AC_2:7 |AirLoopSystemComponentLoadsMonthly
| VAV_POD_1 | PSZ-AC_1:6 | PSZ-AC_2:7 |AirLoopSystemComponentEnergyUseMonthly
| VAV_POD_1 | PSZ-AC_1:6 | PSZ-AC_2:7 |MechanicalVentilationLoadsMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:30 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
| Latitude [deg] | 48.57 |
| Longitude [deg] | -93.4 |
| Elevation [m] | 359.00 |
| Time Zone | -6.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Above Ground Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Window Opening Area [m2] | 552.60 | 204.13 | 72.16 | 204.16 | 72.16 |
| Gross Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Above Ground Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Above Ground Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Window Opening Area [m2] | 552.60 | 204.13 | 72.16 | 204.16 | 72.16 |
| Gross Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Above Ground Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Total | |
| Gross Roof Area [m2] | 6871.00 |
| Skylight Area [m2] | 13.38 |
| Skylight-Roof Ratio [%] | 0.19 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | Yes | Yes | 768.00 | 1.00 | 12.00 | 0.00 | 2.64 | 2.64 | 5.4810 | 18.58 | 4.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | Yes | Yes | 768.00 | 1.00 | 12.00 | 0.00 | 2.64 | 2.64 | 5.4810 | 18.58 | 4.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | Yes | Yes | 768.00 | 1.00 | 12.00 | 0.00 | 2.64 | 2.64 | 5.4810 | 18.58 | 4.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.57 | 17.57 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1260.00 | 1.00 | 140.00 | 0.00 | 30.80 | 30.80 | 15.0695 | 3.72 | 15.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | Yes | Yes | 648.00 | 1.00 | 72.00 | 0.00 | 15.84 | 15.84 | 15.0695 | 3.72 | 20.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | Yes | Yes | 2184.00 | 1.00 | 36.00 | 0.00 | 7.92 | 7.92 | 5.4810 | 18.58 | 4.0000 |
| LOBBY_ZN_1_FLR_1 | 171.00 | Yes | Yes | 684.00 | 1.00 | 76.00 | 0.00 | 16.72 | 16.72 | 13.9931 | 9.29 | 4.0000 |
| MECH_ZN_1_FLR_1 | 252.00 | Yes | Yes | 1008.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.1458 | 61.93 | 10.0000 |
| BATH_ZN_1_FLR_1 | 190.00 | Yes | Yes | 760.00 | 1.00 | 40.00 | 0.00 | 8.80 | 8.80 | 9.6875 | 18.58 | 4.0000 |
| OFFICES_ZN_1_FLR_1 | 441.00 | Yes | Yes | 1764.00 | 1.00 | 168.00 | 0.00 | 36.96 | 36.96 | 11.8403 | 18.58 | 10.8000 |
| GYM_ZN_1_FLR_1 | 357.00 | Yes | Yes | 1428.00 | 1.00 | 68.00 | 0.00 | 14.96 | 14.96 | 13.3472 | 3.10 | 5.0000 |
| KITCHEN_ZN_1_FLR_1 | 168.00 | Yes | Yes | 672.00 | 1.00 | 32.00 | 0.00 | 7.04 | 7.04 | 12.9167 | 6.22 | 1631.7643 |
| CAFETERIA_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1260.00 | 1.00 | 144.00 | 0.00 | 31.68 | 31.68 | 9.6875 | 0.93 | 25.3900 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | Yes | Yes | 1596.00 | 1.00 | 160.00 | 0.00 | 35.20 | 35.20 | 16.6840 | 9.29 | 15.0000 |
| Total | 6871.00 | 27484.00 | 2512.00 | 0.00 | 552.60 | 552.60 | 12.8652 | 4.37 | 51.7784 | |||
| Conditioned Total | 6871.00 | 27484.00 | 2512.00 | 0.00 | 552.60 | 552.60 | 12.8652 | 4.37 | 51.7784 | |||
| Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | Yes | Yes | 1.00 | CORRIDOR_POD_1_ZN_1_FLR_1 | GENERAL | CORRIDOR_POD_1_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | Yes | Yes | 1.00 | CORRIDOR_POD_2_ZN_1_FLR_1 | GENERAL | CORRIDOR_POD_2_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | Yes | Yes | 1.00 | CORRIDOR_POD_3_ZN_1_FLR_1 | GENERAL | CORRIDOR_POD_3_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | Yes | Yes | 1.00 | COMPUTER_CLASS_ZN_1_FLR_1 | GENERAL | COMPUTER_CLASS_ZN_1_FLR_1 | 15.0695 | 3.72 | 20.0000 | |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | Yes | Yes | 1.00 | MAIN_CORRIDOR_ZN_1_FLR_1 | GENERAL | MAIN_CORRIDOR_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| LOBBY_ZN_1_FLR_1 | 171.00 | Yes | Yes | 1.00 | LOBBY_ZN_1_FLR_1 | GENERAL | LOBBY_ZN_1_FLR_1 | 13.9931 | 9.29 | 4.0000 | |
| MECH_ZN_1_FLR_1 | 252.00 | Yes | Yes | 1.00 | MECH_ZN_1_FLR_1 | GENERAL | MECH_ZN_1_FLR_1 | 16.1458 | 61.93 | 10.0000 | |
| BATH_ZN_1_FLR_1 | 190.00 | Yes | Yes | 1.00 | BATH_ZN_1_FLR_1 | GENERAL | BATH_ZN_1_FLR_1 | 9.6875 | 18.58 | 4.0000 | |
| OFFICES_ZN_1_FLR_1 | 441.00 | Yes | Yes | 1.00 | OFFICES_ZN_1_FLR_1 | GENERAL | OFFICES_ZN_1_FLR_1 | 11.8403 | 18.58 | 10.8000 | |
| GYM_ZN_1_FLR_1 | 357.00 | Yes | Yes | 1.00 | GYM_ZN_1_FLR_1 | GENERAL | GYM_ZN_1_FLR_1 | 13.3472 | 3.10 | 5.0000 | |
| KITCHEN_ZN_1_FLR_1 | 168.00 | Yes | Yes | 1.00 | KITCHEN_ZN_1_FLR_1 | GENERAL | KITCHEN_ZN_1_FLR_1 | 12.9167 | 6.22 | 1631.7643 | |
| CAFETERIA_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1.00 | CAFETERIA_ZN_1_FLR_1 | GENERAL | CAFETERIA_ZN_1_FLR_1 | 9.6875 | 0.93 | 25.3900 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | Yes | Yes | 1.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | GENERAL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 16.6840 | 9.29 | 15.0000 | |
| Total | 6871.00 | 12.8652 | 2.19 | 51.7784 | |||||||
| Conditioned Total | 6871.00 | 12.8652 | 2.19 | 51.7784 | |||||||
| Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 6871.00 | 6871.00 | 0.00 | 0.00 | 12.8652 | 4.37 | 51.7784 |
| Total | 6871.00 | 6871.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 29-JUN-15:00 | 09-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | 02-JAN-13:09 |
| Heating | 0.00 | 1223736.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 191317.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 79557.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 70814.97 | 36063.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 1156.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 33276.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 13.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 13229.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 1343.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 377479.23 | 1273029.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 731232.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Boiler | 0.00 | 492503.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Cooling | General | 191317.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 79557.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 65099.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooking | 3999.34 | 36063.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInFreezer | 986.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInRefrigerator | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | Transformer | 1156.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | General | 33276.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | General | 13.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Heater | 0.00 | 13229.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 241.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LowTempRefrigeration | 431.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MedTempRefrigeration | 670.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 3360.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 761.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 3858.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 292.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 3646.35 | 391.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 55.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 1286.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 12.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 190.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 140.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 10053.72 | 3942.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 489.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 110.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 561.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 42.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 530.69 | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 8.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 187.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 1.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 27.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1463.21 | 573.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 489.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 110.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 561.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 42.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 530.69 | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 8.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 187.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 1.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 27.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 20.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1463.21 | 573.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
AirTerminal:SingleDuct:VAV:Reheat| Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 0.668973 | 0.112767 | 0.414000 | 0.276955 | 0.414000 | 0.500000 | 0.003379 | 0.000111 | 0.559864 | 12.89 | 0.008000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 2.80 | 0.129608 | 0.476000 | 1.33 | 0.476000 | 0.500000 | 0.002940 | 0.000358 | 1.81 | 12.89 | 0.008000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 0.556724 | 0.262794 | 0.300000 | 0.167017 | 0.700785 | 0.500000 | 0.001450 | 0.000101 | 0.512884 | 12.89 | 0.008000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 0.593260 | 0.127158 | 0.467000 | 0.277053 | 0.467000 | 0.500000 | 0.002996 | 0.000110 | 0.553724 | 12.89 | 0.008000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 2.33 | 0.155691 | 0.572000 | 1.34 | 0.572000 | 0.500000 | 0.002447 | 0.000352 | 1.78 | 12.89 | 0.008000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 0.662676 | 0.113838 | 0.418000 | 0.276999 | 0.418000 | 0.500000 | 0.003347 | 0.000110 | 0.558245 | 12.89 | 0.008000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 2.76 | 0.131506 | 0.483000 | 1.33 | 0.483000 | 0.500000 | 0.002897 | 0.000355 | 1.79 | 12.89 | 0.008000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 0.554318 | 0.263935 | 0.300000 | 0.166296 | 0.703826 | 0.500000 | 0.001444 | 0.000101 | 0.512326 | 12.89 | 0.008000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 0.593707 | 0.127063 | 0.467000 | 0.277261 | 0.467000 | 0.500000 | 0.002999 | 0.000110 | 0.553873 | 12.89 | 0.008000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 2.34 | 0.155564 | 0.571000 | 1.33 | 0.571000 | 0.500000 | 0.002449 | 0.000352 | 1.78 | 12.89 | 0.008000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 0.663372 | 0.113719 | 0.418000 | 0.277289 | 0.418000 | 0.500000 | 0.003350 | 0.000110 | 0.558430 | 12.89 | 0.008000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 2.78 | 0.130912 | 0.481000 | 1.34 | 0.481000 | 0.500000 | 0.002910 | 0.000356 | 1.80 | 12.89 | 0.008000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 0.560526 | 0.261012 | 0.300000 | 0.168158 | 0.696031 | 0.500000 | 0.001460 | 0.000102 | 0.513001 | 12.89 | 0.008000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 0.599699 | 0.125793 | 0.462000 | 0.277061 | 0.462000 | 0.500000 | 0.003029 | 0.000110 | 0.555248 | 12.89 | 0.008000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 1.58 | 0.152215 | 0.559000 | 0.881495 | 0.559000 | 0.500000 | 0.002503 | 0.000238 | 1.20 | 12.89 | 0.008000 |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | 0.871907 | 0.141579 | 0.520000 | 0.453392 | 0.520000 | 0.500000 | 0.002691 | 0.000117 | 0.592236 | 12.89 | 0.008000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | 1.23 | 0.337101 | 0.300000 | 0.370262 | 0.898936 | 0.500000 | 0.001130 | 0.000244 | 1.23 | 12.89 | 0.008000 |
| LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | 0.713225 | 0.182694 | 0.300000 | 0.213967 | 0.487184 | 0.500000 | 0.002085 | 0.000141 | 0.713225 | 12.89 | 0.008000 |
| MECH_ZN_1_FLR_1 VAV BOX COMPONENT | 0.840866 | 0.228365 | 0.300000 | 0.252260 | 0.608972 | 0.500000 | 0.001668 | 0.000083 | 0.421111 | 12.89 | 0.008000 |
| BATH_ZN_1_FLR_1 VAV BOX COMPONENT | 0.559630 | 0.258706 | 0.300000 | 0.167889 | 0.689884 | 0.500000 | 0.001473 | 0.000111 | 0.559292 | 12.89 | 0.008000 |
| OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | 1.72 | 0.521813 | 0.500000 | 0.001947 | 0.000313 | 1.58 | 12.89 | 0.008000 | |||
| GYM_ZN_1_FLR_1 VAV BOX COMPONENT | 1.99 | 0.136785 | 0.407000 | 0.809430 | 0.407000 | 0.500000 | 0.002785 | 0.000235 | 1.19 | 12.89 | 0.008000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | 1.80 | 0.168567 | 0.300000 | 0.541099 | 0.449512 | 0.500000 | 0.002260 | 0.000280 | 1.41 | 12.89 | 0.008000 |
| Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 12661.84 | 0.000111 | 295.33 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 40933.30 | 0.000358 | 954.75 |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11600.31 | 0.000101 | 270.58 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 12522.96 | 0.000110 | 292.09 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 40206.38 | 0.000352 | 937.80 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 12625.23 | 0.000110 | 294.48 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 40595.86 | 0.000355 | 946.88 |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11587.69 | 0.000101 | 270.28 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 12526.34 | 0.000110 | 292.17 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 40220.00 | 0.000352 | 938.12 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 12629.41 | 0.000110 | 294.58 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 40711.49 | 0.000356 | 949.58 |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11602.96 | 0.000102 | 270.64 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 12557.45 | 0.000110 | 292.90 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 27153.12 | 0.000238 | 633.34 |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | 13394.13 | 0.000117 | 312.41 |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | 27914.90 | 0.000244 | 651.12 |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | 16130.62 | 0.000141 | 376.24 |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 9524.78 | 0.000083 | 222.17 |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 12649.52 | 0.000111 | 295.05 |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | 35817.28 | 0.000313 | 835.43 |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | 26849.53 | 0.000235 | 626.26 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | 31994.20 | 0.000280 | 746.25 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| KITCHEN_ZN_1_FLR_1 DIRECT AIR | 1.61 |
| CAFETERIA_ZN_1_FLR_1 DIRECT AIR | 2.75 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| VAV_POD_1 | 15.33 | 13.04 | 29.78 | 22.74 | 29.51 | 29.51 | 0.300000 | 0.770669 | 29.51 |
| PSZ-AC_1:6 | 1.61 | 1.61 | 1.61 | 1.61 | 1.61 | 1.61 | 1.00 | 1.00 | 1.61 |
| PSZ-AC_2:7 | 2.75 | 2.75 | 2.75 | 2.75 | 2.75 | 2.75 | 1.00 | 1.00 | 2.75 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| VAV_POD_1_OA_CONTROLLER | 29.51 | |
| PSZ-AC_1:6_OA_CONTROLLER | 1.61 | 0.254814 |
| PSZ-AC_2:7_OA_CONTROLLER | 2.75 | 1.49 |
| Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
| VAV_POD_1 COOLING COIL | 29.51 | 676031.31 | 0.726692 | 9.84 | 225321.24 | 0.726692 |
| Design Size Nominal Capacity [W] | |
| VAV_POD_1 HEATING COIL | 468033.13 |
| PSZ-AC_1:6 HEATING COIL | 37306.96 |
| PSZ-AC_2:7 HEATING COIL | 128129.16 |
| Design Size Maximum Flow Rate [m3/s] | |
| VAV_POD_1 FAN | 29.51 |
| Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
| PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.61 | 2673.20 |
| PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | 2.75 | 4465.58 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| PSZ-AC_1:6_UNITARY_PACKAGE_DX | 1.61 | 1.61 | 1.61 | 1.61 | 34567.45 | 37306.96 | 32.11 | 1.00 |
| PSZ-AC_2:7_UNITARY_PACKAGE_DX | 2.75 | 2.75 | 2.75 | 2.75 | 68361.53 | 128129.16 | 32.11 | 1.00 |
| User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
| PSZ-AC_1:6 COOLING COIL | 1.61 | 0.804213 | 1.07 | 34567.45 | 17283.72 | 0.749180 | 0.749180 |
| PSZ-AC_2:7 COOLING COIL | 2.75 | 1.38 | 1.84 | 68361.53 | 34180.76 | 0.701080 | 0.701080 |
| Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
| HEATSYS1 | 0.004500 | 0.540033 |
| SWHSYS1 | 0.000105 | 0.012650 |
| Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
| HEATSYS1 PUMP | 0.004500 | 1355.29 | 0.000000 |
| Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
| HEATSYS1 BOILER | 514409.29 | 514409.29 | 0.004500 |
| Design Flow Rate [m3/s] | Design Power Consumption [W] | |
| SWHSYS1 PUMP | 0.000105 | 13.47 |
| Use Side Design Flow Rate [m3/s] | |
| SWHSYS1 WATER HEATER | 0.000105 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| Possible Shadow Receivers | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | BATH_ZN_1_FLR_1_WALL_5 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | BATH_ZN_1_FLR_1_WALL_5 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | |
| BATH_ZN_1_FLR_1_WALL_5 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | |
| CAFETERIA_ZN_1_FLR_1_WALL_3 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | CAFETERIA_ZN_1_FLR_1_WALL_3 | |
| Possible Shadow Receivers | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | |
| LOBBY_ZN_1_FLR_1_WALL_1 | LOBBY_ZN_1_FLR_1_WALL_1_DOOR | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| BATH_ZN_1_FLR_1_WALL_5 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | |
| OFFICES_ZN_1_FLR_1_WALL_1 | OFFICES_ZN_1_FLR_1_WALL_1_DOOR | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| OFFICES_ZN_1_FLR_1_WALL_2 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | |
| GYM_ZN_1_FLR_1_WALL_2 | GYM_ZN_1_FLR_1_WALL_2_DOOR | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | |
| GYM_ZN_1_FLR_1_CEILING | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | |
| KITCHEN_ZN_1_FLR_1_WALL_2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | |
| CAFETERIA_ZN_1_FLR_1_WALL_2 | CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | |
| CAFETERIA_ZN_1_FLR_1_WALL_3 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | Yes | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 3.29 | 36.60 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | SchoolPrimary | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 25 | 288 | 92 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.0 | -64.00 | 0.00 | 0.00 | -58.50 | 4.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 0.00 | 9.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 0.0 | -53.00 | 0.00 | 0.00 | -26.50 | 4.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 0.00 | 9.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | 0.0 | -64.00 | 9.00 | 0.00 | -32.00 | 10.50 | 2.00 | 1 | 1 | 1 | -64.00 | 0.00 | 9.00 | 12.00 | 0.00 | 4.00 | 4.00 | 768.00 | TARP | TARP | 192.00 | 12.00 | 9.36 | 2.64 | 8 | 1 | 0 | Yes |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.0 | -64.00 | 12.00 | 0.00 | -58.50 | 16.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 12.00 | 21.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 0.0 | -53.00 | 12.00 | 0.00 | -26.50 | 16.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 12.00 | 21.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.0 | -64.00 | 30.00 | 0.00 | -58.50 | 34.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 30.00 | 39.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 0.0 | -53.00 | 30.00 | 0.00 | -26.50 | 34.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 30.00 | 39.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | 0.0 | -64.00 | 39.00 | 0.00 | -32.00 | 40.50 | 2.00 | 1 | 1 | 1 | -64.00 | 0.00 | 39.00 | 42.00 | 0.00 | 4.00 | 4.00 | 768.00 | TARP | TARP | 192.00 | 12.00 | 9.36 | 2.64 | 8 | 1 | 0 | Yes |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.0 | -64.00 | 42.00 | 0.00 | -58.50 | 46.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 42.00 | 51.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 0.0 | -53.00 | 42.00 | 0.00 | -26.50 | 46.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 42.00 | 51.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.0 | -64.00 | 61.00 | 0.00 | -58.50 | 65.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 61.00 | 70.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 0.0 | -53.00 | 61.00 | 0.00 | -26.50 | 65.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 61.00 | 70.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | 0.0 | -64.00 | 70.00 | 0.00 | -32.00 | 71.50 | 2.00 | 1 | 1 | 1 | -64.00 | 0.00 | 70.00 | 73.00 | 0.00 | 4.00 | 4.00 | 768.00 | TARP | TARP | 192.00 | 12.00 | 9.36 | 2.64 | 9 | 1 | 0 | Yes |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.0 | -64.00 | 73.00 | 0.00 | -58.50 | 77.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 73.00 | 82.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.48 | 17.57 | 6 | 4 | 0 | Yes |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.0 | -53.00 | 73.00 | 0.00 | -35.50 | 77.50 | 2.00 | 1 | 1 | 1 | -53.00 | -18.00 | 73.00 | 82.00 | 0.00 | 4.00 | 4.00 | 1260.00 | TARP | TARP | 315.00 | 140.00 | 105.30 | 30.80 | 6 | 5 | 0 | Yes |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | 0.0 | -18.00 | 73.00 | 0.00 | -9.00 | 77.50 | 2.00 | 1 | 1 | 1 | -18.00 | 0.00 | 73.00 | 82.00 | 0.00 | 4.00 | 4.00 | 648.00 | TARP | TARP | 162.00 | 72.00 | 54.21 | 15.84 | 6 | 3 | 0 | Yes |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | 0.0 | 0.00 | 9.00 | 0.00 | 6.50 | 30.00 | 2.00 | 1 | 1 | 1 | 0.00 | 13.00 | 9.00 | 51.00 | 0.00 | 4.00 | 4.00 | 2184.00 | TARP | TARP | 546.00 | 36.00 | 26.13 | 7.92 | 11 | 3 | 0 | Yes |
| 18 | LOBBY_ZN_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 9.50 | 4.50 | 2.00 | 1 | 1 | 1 | 0.00 | 19.00 | 0.00 | 9.00 | 0.00 | 4.00 | 4.00 | 684.00 | TARP | TARP | 171.00 | 76.00 | 57.33 | 16.72 | 7 | 3 | 0 | Yes |
| 19 | MECH_ZN_1_FLR_1 | 0.0 | 13.00 | 9.00 | 0.00 | 16.00 | 30.00 | 2.00 | 1 | 1 | 1 | 13.00 | 19.00 | 9.00 | 51.00 | 0.00 | 4.00 | 4.00 | 1008.00 | TARP | TARP | 252.00 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
| 20 | BATH_ZN_1_FLR_1 | 0.0 | 0.00 | 51.00 | 0.00 | 9.50 | 56.00 | 2.00 | 1 | 1 | 1 | 0.00 | 19.00 | 51.00 | 61.00 | 0.00 | 4.00 | 4.00 | 760.00 | TARP | TARP | 190.00 | 40.00 | 31.20 | 8.80 | 7 | 1 | 0 | Yes |
| 21 | OFFICES_ZN_1_FLR_1 | 0.0 | 19.00 | 0.00 | 0.00 | 29.50 | 10.50 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 0.00 | 21.00 | 0.00 | 4.00 | 4.00 | 1764.00 | TARP | TARP | 441.00 | 168.00 | 129.09 | 36.96 | 7 | 4 | 0 | Yes |
| 22 | GYM_ZN_1_FLR_1 | 0.0 | 19.00 | 21.00 | 0.00 | 29.50 | 29.50 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 21.00 | 38.00 | 0.00 | 4.00 | 4.00 | 1428.00 | TARP | TARP | 357.00 | 68.00 | 51.09 | 28.34 | 6 | 12 | 0 | Yes |
| 23 | KITCHEN_ZN_1_FLR_1 | 0.0 | 19.00 | 38.00 | 0.00 | 29.50 | 42.00 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 38.00 | 46.00 | 0.00 | 4.00 | 4.00 | 672.00 | TARP | TARP | 168.00 | 32.00 | 24.96 | 7.04 | 6 | 1 | 0 | Yes |
| 24 | CAFETERIA_ZN_1_FLR_1 | 0.0 | 19.00 | 46.00 | 0.00 | 29.50 | 53.50 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 46.00 | 61.00 | 0.00 | 4.00 | 4.00 | 1260.00 | TARP | TARP | 315.00 | 144.00 | 110.37 | 31.68 | 7 | 4 | 0 | Yes |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.0 | 0.00 | 61.00 | 0.00 | 9.50 | 71.50 | 2.00 | 1 | 1 | 1 | 0.00 | 19.00 | 61.00 | 82.00 | 0.00 | 4.00 | 4.00 | 1596.00 | TARP | TARP | 399.00 | 160.00 | 122.85 | 35.20 | 8 | 4 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 3.716 | 0.269 | 15.069 | 20.000 | 0.000 | 0.000 | 0.000 | 0.000 | 35.069 | No |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 18 | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 9.289 | 0.108 | 13.993 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.993 | No |
| 19 | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 61.932 | 1.615E-002 | 16.146 | 10.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26.146 | No |
| 20 | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 18.578 | 5.383E-002 | 9.688 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.688 | No |
| 21 | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 18.579 | 5.382E-002 | 11.840 | 10.800 | 0.000 | 0.000 | 0.000 | 0.000 | 22.640 | No |
| 22 | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 3.096 | 0.323 | 13.347 | 5.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.347 | No |
| 23 | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 6.224 | 0.161 | 12.917 | 200.664 | 1431.100 | 0.000 | 0.000 | 0.000 | 1644.681 | No |
| 24 | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 0.929 | 1.076 | 9.688 | 25.390 | 0.000 | 0.000 | 0.000 | 0.000 | 35.078 | No |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 9.289 | 0.108 | 16.684 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 31.684 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 10.3 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 10.3 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 10.3 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 84.8 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 81 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | BLDG_OCC_SCH_EXTEND | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 43.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 41 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 17 | MECH_ZN_1_FLR_1 | BLDG_OCC_SCH | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 4.1 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 4 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 18 | BATH_ZN_1_FLR_1 | BLDG_OCC_SCH | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 10.2 | 5.383E-002 | 18.578 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 19 | OFFICES_ZN_1_FLR_1 | BLDG_OCC_SCH_OFFICES_W_SB | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 23.7 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 23 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 20 | GYM_ZN_1_FLR_1 | BLDG_OCC_SCH_GYM | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 115.3 | 0.323 | 3.096 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 110 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 21 | KITCHEN_ZN_1_FLR_1 | BLDG_OCC_SCH | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 27.0 | 0.161 | 6.224 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 26 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 22 | CAFETERIA_ZN_1_FLR_1 | BLDG_OCC_SCH_CAFETERIA | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 339.1 | 1.076 | 0.929 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 322 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 23 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | BLDG_OCC_SCH | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 43.0 | 0.108 | 9.289 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 41 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 24 | MAIN_CORRIDOR_ZN_1_FLR_1 | BLDG_OCC_SCH | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 29.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 25 | LOBBY_ZN_1_FLR_1 | BLDG_OCC_SCH | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 18.4 | 0.108 | 9.289 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 1052.352 | 5.481 | 101.834 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1052.352 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 1052.352 | 5.481 | 101.834 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1052.352 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 1052.352 | 5.481 | 101.834 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1052.352 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 4746.880 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 4746.880 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1_LIGHTS | LTG_SCH_COMPUTER_ROOM | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 2441.253 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2441.253 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 2992.626 | 5.481 | 101.832 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2992.626 |
| 18 | LOBBY_ZN_1_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 2392.815 | 13.993 | 129.988 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2392.815 |
| 19 | MECH_ZN_1_FLR_1_LIGHTS | LTG_SCH_MECHANICAL | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 4068.754 | 16.146 | 999.940 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 4068.754 |
| 20 | BATH_ZN_1_FLR_1_LIGHTS | LTG_SCH_BATH | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 1840.627 | 9.688 | 179.977 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1840.627 |
| 21 | OFFICES_ZN_1_FLR_1_LIGHTS | LTG_SCH_OFFICE | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 5221.568 | 11.840 | 219.981 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 5221.568 |
| 22 | GYM_ZN_1_FLR_1_LIGHTS | LTG_SCH_GYM | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 4764.965 | 13.347 | 41.323 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 4764.965 |
| 23 | KITCHEN_ZN_1_FLR_1_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 2170.002 | 12.917 | 80.391 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2170.002 |
| 24 | CAFETERIA_ZN_1_FLR_1_LIGHTS | LTG_SCH_CAFETERIA | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 3051.566 | 9.688 | 9.000 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 3051.566 |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_LIGHTS | LTG_SCH_LIBRARY | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 6656.932 | 16.684 | 154.978 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 6656.932 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 768.000 | 4.000 | 74.318 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 149.700 | 729.600 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 768.000 | 4.000 | 74.318 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 149.700 | 729.600 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 768.000 | 4.000 | 74.318 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 149.700 | 729.600 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 4725.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 921.003 | 4488.750 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 3240.000 | 20.000 | 74.320 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 631.545 | 3078.000 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 2184.000 | 4.000 | 74.316 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 425.708 | 2074.800 |
| 18 | LOBBY_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 684.000 | 4.000 | 37.158 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 133.326 | 649.800 |
| 19 | MECH_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 2520.000 | 10.000 | 619.317 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 491.202 | 2394.000 |
| 20 | BATH_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 760.000 | 4.000 | 74.313 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 148.140 | 722.000 |
| 21 | OFFICES_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 4762.800 | 10.800 | 200.653 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 928.371 | 4524.660 |
| 22 | GYM_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 1785.000 | 5.000 | 15.480 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 347.935 | 1695.750 |
| 23 | KITCHEN_ZN_1_FLR_1_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 31995.600 | 190.450 | 1185.330 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 3199.560 | 7998.900 |
| 24 | KITCHEN_ZN_1_FLR_1_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 986.000 | 5.869 | 36.528 | 0.000 | 0.000 | 1.000 | 0.000 | ReachInFreezer | 986.000 | 986.000 |
| 25 | KITCHEN_ZN_1_FLR_1_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 730.000 | 4.345 | 27.044 | 0.000 | 0.000 | 1.000 | 0.000 | ReachInRefrigerator | 730.000 | 730.000 |
| 26 | CAFETERIA_ZN_1_FLR_1_PLUGMISC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 7997.850 | 25.390 | 23.587 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 799.785 | 1999.463 |
| 27 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 5985.000 | 15.000 | 139.335 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1166.604 | 5685.750 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | KITCHEN_ZN_1_FLR_1_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 240424.800 | 1431.100 | 8906.931 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 4808.496 | 48084.960 |
| Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
| 1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
| 2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 6 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 7 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 8 | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1980E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 9 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 10 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 11 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 12 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 13 | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1980E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 14 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 15 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 46 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 16 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 47 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 17 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 48 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 18 | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1980E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 19 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 20 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 21 | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR | 52 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 22 | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR | 53 | 2 | 7 | 0.167 | 0.2090E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 23 | LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR | 54 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 24 | MECH_ZN_1_FLR_1_FLOOR_FFACTOR | 55 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 25 | BATH_ZN_1_FLR_1_FLOOR_FFACTOR | 56 | 2 | 7 | 0.167 | 0.6720E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 26 | OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR | 57 | 2 | 7 | 0.167 | 0.1226 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 27 | GYM_ZN_1_FLR_1_FLOOR_FFACTOR | 58 | 2 | 7 | 0.167 | 0.6074E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 28 | KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR | 59 | 2 | 7 | 0.167 | 0.6074E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 29 | CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR | 60 | 2 | 7 | 0.167 | 0.1477 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 30 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR | 61 | 2 | 7 | 0.167 | 0.1292 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
| 1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
| 2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
| 3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
| 4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
| 5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
| 6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
| 7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
| 8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
| 9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
| 11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 50.42 |
| 17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 50.42 |
| 27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 32 | ~FC_Insulation_11 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 34 | ~FC_Insulation_12 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 36 | ~FC_Insulation_13 | 0.0000 | 0.000 | 0.000 | 0.000 | 50.42 |
| 37 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 38 | ~FC_Insulation_14 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 39 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 40 | ~FC_Insulation_15 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 41 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 42 | ~FC_Insulation_16 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 43 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 44 | ~FC_Insulation_17 | 0.0000 | 0.000 | 0.000 | 0.000 | 47.78 |
| 45 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 46 | ~FC_Insulation_18 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 47 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 48 | ~FC_Insulation_19 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
| 49 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 50 | ~FC_Insulation_20 | 0.0000 | 0.000 | 0.000 | 0.000 | 14.80 |
| 51 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 52 | ~FC_Insulation_21 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.077 |
| 53 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 54 | ~FC_Insulation_22 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.39 |
| 55 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 56 | ~FC_Insulation_23 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.39 |
| 57 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 58 | ~FC_Insulation_24 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.693 |
| 59 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 60 | ~FC_Insulation_25 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.662 |
| 61 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| Time | Outside | Cross | Inside | Flux (except final one) | |
| 1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
| 2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
| 3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
| 4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
| 5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
| 6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
| 7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
| 8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
| 9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
| 10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
| 11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
| 12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
| 13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
| 14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
| 15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
| 16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
| 17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
| 18 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
| 19 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
| 20 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
| 21 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
| 22 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
| 23 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
| 24 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
| 25 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
| 26 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
| 27 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
| 28 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
| 29 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
| 30 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 31 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 32 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 33 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 34 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 35 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 36 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 37 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 38 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 39 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 40 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 41 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 42 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 43 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 44 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 45 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 46 | 7 | -0.21707302E-07 | -0.21810081E-14 | -0.84952625E-14 | 0.13770899E-15 |
| 47 | 6 | 0.21407607E-05 | 0.45739277E-09 | 0.32038929E-02 | -0.26876939E-04 |
| 48 | 5 | -0.77205346E-04 | 0.24803070E-06 | -0.22452059 | 0.19631768E-02 |
| 49 | 4 | 0.12599243E-02 | 0.10780209E-04 | 4.8427850 | -0.45392265E-01 |
| 50 | 3 | -0.93942915E-02 | 0.82583168E-04 | -38.096111 | 0.39947953 |
| 51 | 2 | 0.30967349E-01 | 0.13253122E-03 | 116.62920 | -1.4198824 |
| 52 | 1 | -0.43132160E-01 | 0.38654114E-04 | -143.99276 | 2.0504445 |
| 53 | 0 | 0.20639933E-01 | 0.87079362E-06 | 60.838472 | |
| 54 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 55 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 56 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 57 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 58 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 59 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 60 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 61 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 62 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 63 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 64 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 65 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 66 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 67 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 68 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 69 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 70 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 71 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 72 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 73 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 74 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 75 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 76 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 77 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 78 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 79 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 80 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 81 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 82 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 83 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 84 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 85 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 86 | 7 | -0.21707302E-07 | -0.21810081E-14 | -0.84952625E-14 | 0.13770899E-15 |
| 87 | 6 | 0.21407607E-05 | 0.45739277E-09 | 0.32038929E-02 | -0.26876939E-04 |
| 88 | 5 | -0.77205346E-04 | 0.24803070E-06 | -0.22452059 | 0.19631768E-02 |
| 89 | 4 | 0.12599243E-02 | 0.10780209E-04 | 4.8427850 | -0.45392265E-01 |
| 90 | 3 | -0.93942915E-02 | 0.82583168E-04 | -38.096111 | 0.39947953 |
| 91 | 2 | 0.30967349E-01 | 0.13253122E-03 | 116.62920 | -1.4198824 |
| 92 | 1 | -0.43132160E-01 | 0.38654114E-04 | -143.99276 | 2.0504445 |
| 93 | 0 | 0.20639933E-01 | 0.87079362E-06 | 60.838472 | |
| 94 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 95 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 96 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 97 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 98 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 99 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 100 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 101 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 102 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 103 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 104 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 105 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 106 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 107 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 108 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 109 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 110 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 111 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 112 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 113 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 114 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 115 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 116 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 117 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 118 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 119 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 120 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 121 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 122 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 123 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 124 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 125 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 126 | 7 | -0.21707302E-07 | -0.21810081E-14 | -0.84952625E-14 | 0.13770899E-15 |
| 127 | 6 | 0.21407607E-05 | 0.45739277E-09 | 0.32038929E-02 | -0.26876939E-04 |
| 128 | 5 | -0.77205346E-04 | 0.24803070E-06 | -0.22452059 | 0.19631768E-02 |
| 129 | 4 | 0.12599243E-02 | 0.10780209E-04 | 4.8427850 | -0.45392265E-01 |
| 130 | 3 | -0.93942915E-02 | 0.82583168E-04 | -38.096111 | 0.39947953 |
| 131 | 2 | 0.30967349E-01 | 0.13253122E-03 | 116.62920 | -1.4198824 |
| 132 | 1 | -0.43132160E-01 | 0.38654114E-04 | -143.99276 | 2.0504445 |
| 133 | 0 | 0.20639933E-01 | 0.87079362E-06 | 60.838472 | |
| 134 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 135 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 136 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 137 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 138 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 139 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 140 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 141 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 142 | 7 | -0.29578731E-08 | -0.18610472E-14 | 0.16360026E-14 | -0.48190060E-16 |
| 143 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 144 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 145 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 146 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 147 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 148 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 149 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 150 | 7 | -0.29578731E-08 | -0.18610472E-14 | 0.16360026E-14 | -0.48190060E-16 |
| 151 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 152 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 153 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 154 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 155 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 156 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 157 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 158 | 7 | -0.20570949E-07 | -0.14658537E-14 | -0.76832012E-14 | 0.12671469E-15 |
| 159 | 6 | 0.20860838E-05 | 0.47270270E-09 | 0.32038024E-02 | -0.26876180E-04 |
| 160 | 5 | -0.77354338E-04 | 0.25871613E-06 | -0.22451551 | 0.19631320E-02 |
| 161 | 4 | 0.12908389E-02 | 0.11299182E-04 | 4.8427016 | -0.45391462E-01 |
| 162 | 3 | -0.97548753E-02 | 0.86890235E-04 | -38.095646 | 0.39947438 |
| 163 | 2 | 0.32375441E-01 | 0.13995703E-03 | 116.62830 | -1.4198704 |
| 164 | 1 | -0.45248243E-01 | 0.40996175E-04 | -143.99224 | 2.0504359 |
| 165 | 0 | 0.21692461E-01 | 0.93166815E-06 | 60.838472 | |
| 166 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 167 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 168 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 169 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 170 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 171 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 172 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 173 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 174 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
| 175 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
| 176 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
| 177 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
| 178 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
| 179 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
| 180 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
| 181 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
| 182 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 | |
| 183 | 7 | -0.63667935E-08 | -0.10874325E-13 | 0.11269204E-14 | -0.19557179E-16 |
| 184 | 6 | 0.22887183E-05 | 0.12967685E-08 | 0.32001644E-02 | -0.26845660E-04 |
| 185 | 5 | -0.14389595E-03 | 0.76205050E-06 | -0.22430950 | 0.19613133E-02 |
| 186 | 4 | 0.31719958E-02 | 0.34552480E-04 | 4.8392847 | -0.45358602E-01 |
| 187 | 3 | -0.27412176E-01 | 0.27382890E-03 | -38.076416 | 0.39926170 |
| 188 | 2 | 0.96706121E-01 | 0.45412367E-03 | 116.59097 | -1.4193709 |
| 189 | 1 | -0.13917125 | 0.13776341E-03 | -143.97030 | 2.0500753 |
| 190 | 0 | 0.67751290E-01 | 0.33403087E-05 | 60.838472 | |
| 191 | 7 | -0.34692083E-08 | -0.29835039E-14 | 0.22457095E-14 | -0.46878358E-16 |
| 192 | 6 | 0.35887165E-05 | 0.23456121E-08 | 0.31958645E-02 | -0.26809589E-04 |
| 193 | 5 | -0.24929292E-03 | 0.13860889E-05 | -0.22406525 | 0.19591573E-02 |
| 194 | 4 | 0.56768486E-02 | 0.63026314E-04 | 4.8352193 | -0.45319520E-01 |
| 195 | 3 | -0.49670058E-01 | 0.50068761E-03 | -38.053464 | 0.39900799 |
| 196 | 2 | 0.17611533 | 0.83223021E-03 | 116.54632 | -1.4187736 |
| 197 | 1 | -0.25403345 | 0.25321776E-03 | -143.94402 | 2.0496434 |
| 198 | 0 | 0.12381374 | 0.61501487E-05 | 60.838472 | |
| 199 | 7 | -0.70485818E-08 | -0.82048821E-14 | -0.11525862E-14 | 0.12346975E-16 |
| 200 | 6 | 0.21636134E-05 | 0.11761400E-08 | 0.32006654E-02 | -0.26849864E-04 |
| 201 | 5 | -0.13228193E-03 | 0.68999669E-06 | -0.22433795 | 0.19615643E-02 |
| 202 | 4 | 0.28871477E-02 | 0.31257738E-04 | 4.8397578 | -0.45363150E-01 |
| 203 | 3 | -0.24853202E-01 | 0.24753724E-03 | -38.079085 | 0.39929121 |
| 204 | 2 | 0.87536903E-01 | 0.41023195E-03 | 116.59616 | -1.4194403 |
| 205 | 1 | -0.12588244 | 0.12433901E-03 | -143.97335 | 2.0501255 |
| 206 | 0 | 0.61258788E-01 | 0.30111189E-05 | 60.838472 | |
| 207 | 7 | -0.70485818E-08 | -0.82048821E-14 | -0.11525862E-14 | 0.12346975E-16 |
| 208 | 6 | 0.21636134E-05 | 0.11761400E-08 | 0.32006654E-02 | -0.26849864E-04 |
| 209 | 5 | -0.13228193E-03 | 0.68999669E-06 | -0.22433795 | 0.19615643E-02 |
| 210 | 4 | 0.28871477E-02 | 0.31257738E-04 | 4.8397578 | -0.45363150E-01 |
| 211 | 3 | -0.24853202E-01 | 0.24753724E-03 | -38.079085 | 0.39929121 |
| 212 | 2 | 0.87536903E-01 | 0.41023195E-03 | 116.59616 | -1.4194403 |
| 213 | 1 | -0.12588244 | 0.12433901E-03 | -143.97335 | 2.0501255 |
| 214 | 0 | 0.61258788E-01 | 0.30111189E-05 | 60.838472 | |
| 215 | 7 | -0.28726507E-08 | -0.17143581E-14 | 0.24267693E-14 | -0.55541839E-16 |
| 216 | 6 | 0.42346750E-05 | 0.28245518E-08 | 0.31939123E-02 | -0.26793213E-04 |
| 217 | 5 | -0.29857172E-03 | 0.16707368E-05 | -0.22395432 | 0.19581782E-02 |
| 218 | 4 | 0.68293023E-02 | 0.76000496E-04 | 4.8333721 | -0.45301763E-01 |
| 219 | 3 | -0.59851213E-01 | 0.60399479E-03 | -38.043031 | 0.39889267 |
| 220 | 2 | 0.21235346 | 0.10042645E-02 | 116.52602 | -1.4185020 |
| 221 | 1 | -0.30639453 | 0.30573542E-03 | -143.93207 | 2.0494469 |
| 222 | 0 | 0.14935640 | 0.74123768E-05 | 60.838472 | |
| 223 | 7 | -0.32902409E-08 | -0.25529066E-14 | 0.11988885E-14 | -0.45014903E-16 |
| 224 | 6 | 0.37562854E-05 | 0.24712502E-08 | 0.31953527E-02 | -0.26805296E-04 |
| 225 | 5 | -0.26216584E-03 | 0.14606656E-05 | -0.22403617 | 0.19589006E-02 |
| 226 | 4 | 0.59784819E-02 | 0.66426580E-04 | 4.8347351 | -0.45314865E-01 |
| 227 | 3 | -0.52336689E-01 | 0.52775921E-03 | -38.050729 | 0.39897776 |
| 228 | 2 | 0.18560952 | 0.87732663E-03 | 116.54100 | -1.4187024 |
| 229 | 1 | -0.26775360 | 0.26697134E-03 | -143.94089 | 2.0495919 |
| 230 | 0 | 0.13050713 | 0.64865099E-05 | 60.838472 |
| Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
| 1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.491 | ||
| 2 | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | 36 | 1 | VerySmooth | 3.922 | 3.922 | 1.000 | 0.683 |
| Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
| 1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.40797 | 0.37250 | 0.37250 | 0.53900 | 0.12971 | 0.15583 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
| 2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.59264 | 0.15506 | 0.15506 | 0.68000 | 0.13462 | 0.14960 | 0.00000 | 0.84000 | 0.84000 | 2.30798E-002 | 1.00000 | No |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Number of Refrigeration Compressor Racks | |
| 1 | 2 |
| Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
| 1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
| 2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | SWH BOOSTER G WATER HEATER | 2.2712E-002 | 6000.0 | 1.092 | 0.9931 |
| 2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 14.749 | 0.4701 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 2 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 3 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 4 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 5 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 6 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 7 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 8 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 9 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 10 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 11 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 12 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 13 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 14 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 15 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 16 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 17 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 18 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 19 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 20 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 21 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 22 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 23 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 24 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 25 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 26 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 27 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 28 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 29 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 3 | No | No |
| 30 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 2 | No | No |
| 31 | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 32 | CORRIDOR_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 33 | CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 34 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 35 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 36 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 37 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 38 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 39 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 40 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 41 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 42 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 43 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 44 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 45 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 46 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 47 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 48 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 49 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 50 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 51 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 52 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 53 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 54 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 55 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 56 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 57 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 58 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 59 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 60 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 61 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 62 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 63 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 64 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 65 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 66 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 67 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 68 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 69 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 70 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 71 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 72 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 73 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 74 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 75 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 76 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 77 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 78 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 79 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 80 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 81 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 82 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 83 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 84 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 85 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 3 | No | No |
| 86 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 2 | No | No |
| 87 | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 88 | CORRIDOR_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 89 | CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 90 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 91 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 92 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 93 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 94 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 95 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 96 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 97 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 98 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 99 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 100 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 101 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 102 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 103 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 104 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 105 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 106 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 107 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 108 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 109 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 110 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 111 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 112 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 113 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 114 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 115 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 116 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 117 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 118 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 119 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 120 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 121 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 122 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 123 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 124 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 125 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 126 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 127 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 128 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 129 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 130 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 131 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 132 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 133 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 134 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 135 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 136 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 137 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 138 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 139 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 140 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 141 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 142 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 3 | No | No |
| 143 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 2 | No | No |
| 144 | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 145 | CORRIDOR_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 146 | CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 147 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 148 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 149 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 150 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 151 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 152 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 153 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 154 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 155 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 156 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 157 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 158 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 159 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 160 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 3 | No | No |
| 161 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 2 | No | No |
| 162 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 2 | No | No |
| 163 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 2 | No | No |
| 164 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 165 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 166 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 167 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 168 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 169 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 170 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 171 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 172 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 3 | No | No |
| 173 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 2 | No | No |
| 174 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 2 | No | No |
| 175 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 176 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 177 | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 178 | COMPUTER_CLASS_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 179 | COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 180 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 181 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 182 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 183 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 184 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 185 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 186 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 3 | No | No |
| 187 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 2 | No | No |
| 188 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 2 | No | No |
| 189 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 190 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 191 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 192 | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 193 | MAIN_CORRIDOR_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 194 | MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 195 | LOBBY_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 3 | No | No |
| 196 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 2 | No | No |
| 197 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 2 | No | No |
| 198 | LOBBY_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 199 | LOBBY_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 200 | LOBBY_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 201 | LOBBY_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 202 | LOBBY_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 203 | LOBBY_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 204 | LOBBY_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 205 | LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 206 | MECH_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 207 | MECH_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 208 | MECH_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 209 | MECH_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 210 | MECH_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 211 | MECH_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 212 | MECH_ZN_1_FLR_1_WALL_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 213 | MECH_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 214 | MECH_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 215 | MECH_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 216 | BATH_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 217 | BATH_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 218 | BATH_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 219 | BATH_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 220 | BATH_ZN_1_FLR_1_WALL_5 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 3 | No | No |
| 221 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 2 | No | No |
| 222 | BATH_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 223 | BATH_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 224 | BATH_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 225 | OFFICES_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 3 | No | No |
| 226 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 2 | No | No |
| 227 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 2 | No | No |
| 228 | OFFICES_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 229 | OFFICES_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 3 | No | No |
| 230 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 2 | No | No |
| 231 | OFFICES_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 232 | OFFICES_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 233 | OFFICES_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 234 | OFFICES_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 235 | OFFICES_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 236 | OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 237 | GYM_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 238 | GYM_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 3 | No | No |
| 239 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 240 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 241 | GYM_ZN_1_FLR_1_WALL_2_DOOR | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 242 | GYM_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 243 | GYM_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 244 | GYM_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 245 | GYM_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 246 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 247 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 248 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 249 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 250 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 251 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 252 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 253 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 254 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 255 | GYM_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 256 | KITCHEN_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 257 | KITCHEN_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 3 | No | No |
| 258 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 2 | No | No |
| 259 | KITCHEN_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 260 | KITCHEN_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 261 | KITCHEN_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 262 | KITCHEN_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 263 | KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 264 | CAFETERIA_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 265 | CAFETERIA_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 3 | No | No |
| 266 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 2 | No | No |
| 267 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 2 | No | No |
| 268 | CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 269 | CAFETERIA_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 3 | No | No |
| 270 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 2 | No | No |
| 271 | CAFETERIA_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 272 | CAFETERIA_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 273 | CAFETERIA_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 274 | CAFETERIA_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 275 | CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 276 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 277 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 3 | No | No |
| 278 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 2 | No | No |
| 279 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 2 | No | No |
| 280 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 281 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 3 | No | No |
| 282 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 2 | No | No |
| 283 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 284 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 285 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 286 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 287 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 288 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
| 1 | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.786 | 0.682 | 0.682 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 6.835E-003 | 3.560E-005 | 3.350E-005 | 3.204E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 6.835E-003 | 3.560E-005 | 3.350E-005 | 3.204E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 6.835E-003 | 3.560E-005 | 3.350E-005 | 3.204E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 7.974E-002 | 2.531E-004 | 1.738E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 4.101E-002 | 2.531E-004 | 1.738E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 2.050E-002 | 3.755E-005 | 3.511E-005 | 3.380E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | LOBBY_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 4.329E-002 | 2.531E-004 | 1.739E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | LOBBY_ZN_1_FLR_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 3.031 | 1.773E-002 | 1.218E-002 | 15.954 | 1.000 | 0.000 | 0.000 | 0.000 |
| 20 | MECH_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | BATH_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 2.278E-002 | 1.199E-004 | 9.906E-005 | 0.108 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | OFFICES_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 9.569E-002 | 2.170E-004 | 1.566E-004 | 0.195 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | GYM_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 3.873E-002 | 1.085E-004 | 9.072E-005 | 9.764E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | KITCHEN_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 1.823E-002 | 1.085E-004 | 9.113E-005 | 9.764E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | CAFETERIA_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 8.202E-002 | 2.604E-004 | 1.779E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 9.113E-002 | 2.284E-004 | 1.625E-004 | 0.206 | 0.000 | 0.000 | 0.224 | 0.000 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 18 | LOBBY_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 19 | MECH_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 20 | BATH_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 21 | OFFICES_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 22 | GYM_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 23 | KITCHEN_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 24 | CAFETERIA_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2500 |
| 2 | Zone CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1.2500 |
| 3 | Zone MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.2500 |
| 4 | Zone CORRIDOR_POD_1_ZN_1_FLR_1 | 1.2500 |
| 5 | Zone CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1.2500 |
| 6 | Zone MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.2500 |
| 7 | Zone CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1.2500 |
| 8 | Zone MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.2500 |
| 9 | Zone CORRIDOR_POD_2_ZN_1_FLR_1 | 1.2500 |
| 10 | Zone CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1.2500 |
| 11 | Zone MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.2500 |
| 12 | Zone CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1.2500 |
| 13 | Zone MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.2500 |
| 14 | Zone CORRIDOR_POD_3_ZN_1_FLR_1 | 1.2500 |
| 15 | Zone CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1.2500 |
| 16 | Zone MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1.2500 |
| 17 | Zone COMPUTER_CLASS_ZN_1_FLR_1 | 1.2500 |
| 18 | Zone MAIN_CORRIDOR_ZN_1_FLR_1 | 1.2500 |
| 19 | Zone LOBBY_ZN_1_FLR_1 | 1.2500 |
| 20 | Zone MECH_ZN_1_FLR_1 | 1.2500 |
| 21 | Zone BATH_ZN_1_FLR_1 | 1.2500 |
| 22 | Zone OFFICES_ZN_1_FLR_1 | 1.2500 |
| 23 | Zone GYM_ZN_1_FLR_1 | 1.2500 |
| 24 | Zone KITCHEN_ZN_1_FLR_1 | 1.2500 |
| 25 | Zone CAFETERIA_ZN_1_FLR_1 | 1.2500 |
| 26 | Zone LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 1.2500 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.1500 |
| 2 | Zone CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1.1500 |
| 3 | Zone MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.1500 |
| 4 | Zone CORRIDOR_POD_1_ZN_1_FLR_1 | 1.1500 |
| 5 | Zone CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1.1500 |
| 6 | Zone MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.1500 |
| 7 | Zone CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1.1500 |
| 8 | Zone MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.1500 |
| 9 | Zone CORRIDOR_POD_2_ZN_1_FLR_1 | 1.1500 |
| 10 | Zone CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1.1500 |
| 11 | Zone MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.1500 |
| 12 | Zone CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1.1500 |
| 13 | Zone MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.1500 |
| 14 | Zone CORRIDOR_POD_3_ZN_1_FLR_1 | 1.1500 |
| 15 | Zone CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1.1500 |
| 16 | Zone MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1.1500 |
| 17 | Zone COMPUTER_CLASS_ZN_1_FLR_1 | 1.1500 |
| 18 | Zone MAIN_CORRIDOR_ZN_1_FLR_1 | 1.1500 |
| 19 | Zone LOBBY_ZN_1_FLR_1 | 1.1500 |
| 20 | Zone MECH_ZN_1_FLR_1 | 1.1500 |
| 21 | Zone BATH_ZN_1_FLR_1 | 1.1500 |
| 22 | Zone OFFICES_ZN_1_FLR_1 | 1.1500 |
| 23 | Zone GYM_ZN_1_FLR_1 | 1.1500 |
| 24 | Zone KITCHEN_ZN_1_FLR_1 | 1.1500 |
| 25 | Zone CAFETERIA_ZN_1_FLR_1 | 1.1500 |
| 26 | Zone LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 1.1500 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | Cooling | 7609.24502 | 8750.63177 | 0.58172 | 0.66897 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 29.60400 | 1.27250E-002 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 2 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | Heating | 5856.06568 | 7320.08210 | 0.44789 | 0.55986 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -32.70000 | 1.83376E-004 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 3 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | Cooling | 31898.51244 | 36683.28930 | 2.43861 | 2.80441 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.10000 | 1.27259E-002 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 4 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | Heating | 18930.79283 | 23663.49104 | 1.44792 | 1.80990 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 5 | CORRIDOR_POD_1_ZN_1_FLR_1 | Cooling | 6334.55264 | 7284.73554 | 0.48411 | 0.55672 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 29.72800 | 1.27252E-002 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 6 | CORRIDOR_POD_1_ZN_1_FLR_1 | Heating | 5364.41653 | 6705.52066 | 0.41031 | 0.51288 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 7 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | Cooling | 6747.99985 | 7760.19982 | 0.51588 | 0.59326 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 28.69467 | 1.27234E-002 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 8 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | Heating | 5791.84063 | 7239.80079 | 0.44298 | 0.55372 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -32.70000 | 1.83376E-004 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 9 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | Cooling | 26554.32139 | 30537.46960 | 2.03008 | 2.33459 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.10000 | 1.27259E-002 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 10 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | Heating | 18594.63610 | 23243.29513 | 1.42221 | 1.77776 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 11 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | Cooling | 7537.62081 | 8668.26393 | 0.57624 | 0.66268 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 29.60400 | 1.27250E-002 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 12 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | Heating | 5839.13282 | 7298.91603 | 0.44660 | 0.55824 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -32.70000 | 1.83376E-004 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 13 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | Cooling | 31438.20925 | 36153.94063 | 2.40343 | 2.76394 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.10000 | 1.27259E-002 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 14 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | Heating | 18774.74738 | 23468.43422 | 1.43599 | 1.79498 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 15 | CORRIDOR_POD_2_ZN_1_FLR_1 | Cooling | 6307.17640 | 7253.25286 | 0.48202 | 0.55432 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 29.72800 | 1.27252E-002 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 16 | CORRIDOR_POD_2_ZN_1_FLR_1 | Heating | 5358.57999 | 6698.22499 | 0.40986 | 0.51233 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 17 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | Cooling | 6753.07564 | 7766.03698 | 0.51627 | 0.59371 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 28.69467 | 1.27234E-002 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 18 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | Heating | 5793.40268 | 7241.75335 | 0.44310 | 0.55387 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -32.70000 | 1.83376E-004 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 19 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | Cooling | 26575.89147 | 30562.27519 | 2.03173 | 2.33648 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.10000 | 1.27259E-002 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 20 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | Heating | 18600.93404 | 23251.16755 | 1.42269 | 1.77837 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 21 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | Cooling | 7545.52949 | 8677.35891 | 0.57684 | 0.66337 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 29.60400 | 1.27250E-002 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 22 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | Heating | 5841.06964 | 7301.33705 | 0.44674 | 0.55843 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -32.70000 | 1.83376E-004 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 23 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | Cooling | 31580.71003 | 36317.81654 | 2.41432 | 2.77647 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.10000 | 1.27259E-002 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 24 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | Heating | 18828.21996 | 23535.27496 | 1.44008 | 1.80010 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 25 | CORRIDOR_POD_3_ZN_1_FLR_1 | Cooling | 6377.81297 | 7334.48492 | 0.48741 | 0.56053 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 29.72800 | 1.27252E-002 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 26 | CORRIDOR_POD_3_ZN_1_FLR_1 | Heating | 5365.64332 | 6707.05416 | 0.41040 | 0.51300 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 27 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | Cooling | 6821.24587 | 7844.43276 | 0.52148 | 0.59970 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 28.69467 | 1.27234E-002 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 28 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | Heating | 5807.79020 | 7259.73775 | 0.44420 | 0.55525 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -32.70000 | 1.83376E-004 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 29 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | Cooling | 17936.36703 | 20626.82208 | 1.37123 | 1.57691 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.10000 | 1.27259E-002 | 315.00000 | 84.76857 | 0.59207 | 0.00000 |
| 30 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | Heating | 12557.74267 | 15697.17834 | 0.96048 | 1.20060 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 315.00000 | 84.76857 | 0.59207 | 0.00000 |
| 31 | COMPUTER_CLASS_ZN_1_FLR_1 | Cooling | 9917.45309 | 11405.07106 | 0.75818 | 0.87191 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.10000 | 1.27259E-002 | 162.00000 | 43.59526 | 0.30449 | 0.00000 |
| 32 | COMPUTER_CLASS_ZN_1_FLR_1 | Heating | 6194.52281 | 7743.15351 | 0.47379 | 0.59224 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 162.00000 | 43.59526 | 0.30449 | 0.00000 |
| 33 | MAIN_CORRIDOR_ZN_1_FLR_1 | Cooling | 13604.35851 | 15645.01229 | 1.03970 | 1.19566 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 29.60400 | 1.27250E-002 | 546.00000 | 29.38800 | 0.16642 | 0.00000 |
| 34 | MAIN_CORRIDOR_ZN_1_FLR_1 | Heating | 12908.95552 | 16136.19440 | 0.98736 | 1.23421 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 546.00000 | 29.38800 | 0.16642 | 0.00000 |
| 35 | LOBBY_ZN_1_FLR_1 | Cooling | 8081.16306 | 9293.33752 | 0.61765 | 0.71030 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.10000 | 1.27259E-002 | 171.00000 | 18.40800 | 9.55546E-002 | 0.00000 |
| 36 | LOBBY_ZN_1_FLR_1 | Heating | 7460.01593 | 9325.01991 | 0.57058 | 0.71322 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 171.00000 | 18.40800 | 9.55546E-002 | 0.00000 |
| 37 | MECH_ZN_1_FLR_1 | Cooling | 9568.10366 | 11003.31921 | 0.73119 | 0.84087 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.10000 | 1.27259E-002 | 252.00000 | 4.06900 | 0.00000 | 0.00000 |
| 38 | MECH_ZN_1_FLR_1 | Heating | 4404.52313 | 5505.65392 | 0.33689 | 0.42111 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -32.70000 | 1.83376E-004 | 252.00000 | 4.06900 | 0.00000 | 0.00000 |
| 39 | BATH_ZN_1_FLR_1 | Cooling | 6367.51938 | 7322.64728 | 0.48664 | 0.55963 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 28.52933 | 1.27231E-002 | 190.00000 | 10.22700 | 0.00000 | 0.00000 |
| 40 | BATH_ZN_1_FLR_1 | Heating | 5849.86854 | 7312.33567 | 0.44743 | 0.55929 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 190.00000 | 10.22700 | 0.00000 | 0.00000 |
| 41 | OFFICES_ZN_1_FLR_1 | Cooling | 19539.45981 | 22470.37878 | 1.49331 | 1.71731 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.10000 | 1.27259E-002 | 441.00000 | 23.73648 | 0.19042 | 0.00000 |
| 42 | OFFICES_ZN_1_FLR_1 | Heating | 16564.55533 | 20705.69416 | 1.26694 | 1.58368 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 441.00000 | 23.73648 | 0.19042 | 0.00000 |
| 43 | GYM_ZN_1_FLR_1 | Cooling | 22619.50130 | 26012.42649 | 1.72937 | 1.98877 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.10000 | 1.27259E-002 | 357.00000 | 115.31008 | 0.54407 | 0.00000 |
| 44 | GYM_ZN_1_FLR_1 | Heating | 12416.63939 | 15520.79923 | 0.94970 | 1.18712 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -32.70000 | 1.83376E-004 | 357.00000 | 115.31008 | 0.54407 | 0.00000 |
| 45 | KITCHEN_ZN_1_FLR_1 | Cooling | 18277.24534 | 21018.83214 | 1.39863 | 1.60843 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 28.98400 | 1.27239E-002 | 168.00000 | 26.99300 | 0.25481 | 0.00000 |
| 46 | KITCHEN_ZN_1_FLR_1 | Heating | 1887.97051 | 2359.96313 | 0.14444 | 0.25481 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -32.70000 | 1.83376E-004 | 168.00000 | 26.99300 | 0.25481 | 0.00000 |
| 47 | CAFETERIA_ZN_1_FLR_1 | Cooling | 31276.21529 | 35967.64759 | 2.39384 | 2.75292 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 29.48000 | 1.27248E-002 | 315.00000 | 339.07427 | 1.48818 | 0.00000 |
| 48 | CAFETERIA_ZN_1_FLR_1 | Heating | 13188.42276 | 16485.52845 | 1.00871 | 1.48818 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -32.70000 | 1.83376E-004 | 315.00000 | 339.07427 | 1.48818 | 0.00000 |
| 49 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | Cooling | 20520.38266 | 23598.44006 | 1.56840 | 1.80366 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.10000 | 1.27259E-002 | 399.00000 | 42.95403 | 0.34458 | 0.00000 |
| 50 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | Heating | 14796.57436 | 18495.71795 | 1.13172 | 1.41465 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -32.70000 | 1.83376E-004 | 399.00000 | 42.95403 | 0.34458 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | VAV_POD_1 | Cooling | Sensible | 455719.24 | 29.51303 | 29.51303 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
| 2 | VAV_POD_1 | Heating | Sensible | 451380.79 | 22.74477 | 22.74477 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 |
| 3 | PSZ-AC_1:6 | Cooling | Sensible | 22113.45 | 1.60843 | 1.60843 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 4 | PSZ-AC_1:6 | Heating | Sensible | 19149.07 | 0.25481 | 0.25481 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 5 | PSZ-AC_2:7 | Cooling | Sensible | 45497.88 | 2.75292 | 2.75292 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 6 | PSZ-AC_2:7 | Heating | Sensible | 111835.90 | 1.48818 | 1.48818 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66897 |
| 2 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11277 |
| 3 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.41400 |
| 4 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27695 |
| 5 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41400 |
| 6 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 7 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.37865E-003 |
| 8 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.10771E-004 |
| 9 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55986 |
| 10 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 11 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 12 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12661.84209 |
| 13 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.10771E-004 |
| 14 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 295.33168 |
| 15 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.80441 |
| 16 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12961 |
| 17 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47600 |
| 18 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.33490 |
| 19 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47600 |
| 20 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 21 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.93963E-003 |
| 22 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.58102E-004 |
| 23 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.80990 |
| 24 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 25 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 26 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40933.29797 |
| 27 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.58102E-004 |
| 28 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 954.75465 |
| 29 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55672 |
| 30 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26279 |
| 31 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 32 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16702 |
| 33 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70078 |
| 34 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 35 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44980E-003 |
| 36 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.01485E-004 |
| 37 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.51288 |
| 38 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 39 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 40 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11600.30923 |
| 41 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01485E-004 |
| 42 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 270.57809 |
| 43 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59326 |
| 44 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12716 |
| 45 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
| 46 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27705 |
| 47 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46700 |
| 48 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 49 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.99626E-003 |
| 50 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.09556E-004 |
| 51 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55372 |
| 52 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 53 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 54 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12522.96180 |
| 55 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.09556E-004 |
| 56 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 292.09227 |
| 57 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.33459 |
| 58 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15569 |
| 59 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57200 |
| 60 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.33538 |
| 61 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57200 |
| 62 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 63 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44716E-003 |
| 64 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.51743E-004 |
| 65 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.77776 |
| 66 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 67 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 68 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40206.37733 |
| 69 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.51743E-004 |
| 70 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 937.79909 |
| 71 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66268 |
| 72 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11384 |
| 73 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.41800 |
| 74 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27700 |
| 75 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41800 |
| 76 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 77 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.34685E-003 |
| 78 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.10451E-004 |
| 79 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55824 |
| 80 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 81 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 82 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12625.22645 |
| 83 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.10451E-004 |
| 84 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 294.47761 |
| 85 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.76394 |
| 86 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13151 |
| 87 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48300 |
| 88 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.33498 |
| 89 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48300 |
| 90 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 91 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.89721E-003 |
| 92 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.55150E-004 |
| 93 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.79498 |
| 94 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 95 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 96 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40595.85802 |
| 97 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.55150E-004 |
| 98 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 946.88380 |
| 99 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55432 |
| 100 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26393 |
| 101 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 102 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16630 |
| 103 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70383 |
| 104 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 105 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44354E-003 |
| 106 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.01374E-004 |
| 107 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.51233 |
| 108 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 109 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 110 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11587.68777 |
| 111 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01374E-004 |
| 112 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 270.28369 |
| 113 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59371 |
| 114 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12706 |
| 115 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
| 116 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27726 |
| 117 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46700 |
| 118 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 119 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.99852E-003 |
| 120 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.09586E-004 |
| 121 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55387 |
| 122 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 123 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 124 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12526.33957 |
| 125 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.09586E-004 |
| 126 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 292.17106 |
| 127 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.33648 |
| 128 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15556 |
| 129 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.57100 |
| 130 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.33413 |
| 131 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57100 |
| 132 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 133 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44915E-003 |
| 134 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.51862E-004 |
| 135 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.77837 |
| 136 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 137 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 138 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40219.99627 |
| 139 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.51862E-004 |
| 140 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 938.11675 |
| 141 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66337 |
| 142 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11372 |
| 143 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.41800 |
| 144 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27729 |
| 145 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41800 |
| 146 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 147 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.35036E-003 |
| 148 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.10488E-004 |
| 149 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55843 |
| 150 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 151 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 152 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12629.41464 |
| 153 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.10488E-004 |
| 154 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 294.57530 |
| 155 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.77647 |
| 156 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13091 |
| 157 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48100 |
| 158 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.33548 |
| 159 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48100 |
| 160 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 161 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.91034E-003 |
| 162 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.56162E-004 |
| 163 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.80010 |
| 164 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 165 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 166 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 40711.48971 |
| 167 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.56162E-004 |
| 168 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 949.58093 |
| 169 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.56053 |
| 170 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26101 |
| 171 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 172 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16816 |
| 173 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.69603 |
| 174 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 175 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.45970E-003 |
| 176 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.01508E-004 |
| 177 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.51300 |
| 178 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 179 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 180 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11602.96217 |
| 181 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.01508E-004 |
| 182 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 270.63997 |
| 183 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.59970 |
| 184 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12579 |
| 185 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46200 |
| 186 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27706 |
| 187 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46200 |
| 188 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 189 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.02879E-003 |
| 190 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.09858E-004 |
| 191 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55525 |
| 192 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 193 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 194 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12557.45117 |
| 195 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.09858E-004 |
| 196 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 292.89674 |
| 197 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.57691 |
| 198 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15222 |
| 199 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55900 |
| 200 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.88149 |
| 201 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55900 |
| 202 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 203 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.50304E-003 |
| 204 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.37547E-004 |
| 205 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20060 |
| 206 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 207 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 208 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27153.11922 |
| 209 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.37547E-004 |
| 210 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 633.33693 |
| 211 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.87191 |
| 212 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14158 |
| 213 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52000 |
| 214 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.45339 |
| 215 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52000 |
| 216 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 217 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.69107E-003 |
| 218 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.17178E-004 |
| 219 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.59224 |
| 220 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 221 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 222 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 13394.13147 |
| 223 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.17178E-004 |
| 224 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 312.41308 |
| 225 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.23421 |
| 226 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33710 |
| 227 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 228 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.37026 |
| 229 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89894 |
| 230 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 231 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.13022E-003 |
| 232 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.44212E-004 |
| 233 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.23421 |
| 234 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 235 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 236 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 27914.89967 |
| 237 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.44212E-004 |
| 238 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 651.11640 |
| 239 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.71322 |
| 240 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18269 |
| 241 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 242 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21397 |
| 243 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48718 |
| 244 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 245 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.08545E-003 |
| 246 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.41118E-004 |
| 247 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71322 |
| 248 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 249 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 250 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16130.62495 |
| 251 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.41118E-004 |
| 252 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 376.24189 |
| 253 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.84087 |
| 254 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22836 |
| 255 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 256 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25226 |
| 257 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60897 |
| 258 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 259 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.66838E-003 |
| 260 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.33269E-005 |
| 261 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42111 |
| 262 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 263 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 264 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9524.77979 |
| 265 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.33269E-005 |
| 266 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 222.16726 |
| 267 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.55963 |
| 268 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.25871 |
| 269 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 270 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.16789 |
| 271 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.68988 |
| 272 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 273 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.47271E-003 |
| 274 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.10664E-004 |
| 275 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.55929 |
| 276 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 277 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 278 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12649.52041 |
| 279 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.10664E-004 |
| 280 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 295.04820 |
| 281 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.71731 |
| 282 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52181 |
| 283 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 284 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.94706E-003 |
| 285 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.13345E-004 |
| 286 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.58368 |
| 287 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 288 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 289 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35817.27503 |
| 290 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.13345E-004 |
| 291 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 835.42702 |
| 292 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.98877 |
| 293 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13678 |
| 294 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.40700 |
| 295 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80943 |
| 296 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40700 |
| 297 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 298 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.78539E-003 |
| 299 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.34891E-004 |
| 300 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.18712 |
| 301 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 302 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 303 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 26849.52710 |
| 304 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.34891E-004 |
| 305 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 626.26314 |
| 306 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN_ZN_1_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.60843 |
| 307 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CAFETERIA_ZN_1_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.75292 |
| 308 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.80366 |
| 309 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16857 |
| 310 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 311 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.54110 |
| 312 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44951 |
| 313 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 314 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.26023E-003 |
| 315 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.79899E-004 |
| 316 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.41465 |
| 317 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 318 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 319 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31994.20103 |
| 320 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.79899E-004 |
| 321 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 746.25396 |
| 322 | AirLoopHVAC | VAV_POD_1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 15.33227 |
| 323 | AirLoopHVAC | VAV_POD_1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 13.04395 |
| 324 | AirLoopHVAC | VAV_POD_1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 29.77563 |
| 325 | AirLoopHVAC | VAV_POD_1 | Adjusted Heating Design Air Flow Rate [m3/s] | 22.74477 |
| 326 | AirLoopHVAC | VAV_POD_1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 29.51303 |
| 327 | AirLoopHVAC | VAV_POD_1 | Adjusted Main Design Air Flow Rate [m3/s] | 29.51303 |
| 328 | AirLoopHVAC | VAV_POD_1 | User Heating Air Flow Ratio [] | 0.30000 |
| 329 | AirLoopHVAC | VAV_POD_1 | Calculated Heating Air Flow Ratio [] | 0.77067 |
| 330 | AirLoopHVAC | PSZ-AC_1:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.60843 |
| 331 | AirLoopHVAC | PSZ-AC_1:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.60843 |
| 332 | AirLoopHVAC | PSZ-AC_1:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.60843 |
| 333 | AirLoopHVAC | PSZ-AC_1:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.60843 |
| 334 | AirLoopHVAC | PSZ-AC_1:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.60843 |
| 335 | AirLoopHVAC | PSZ-AC_1:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.60843 |
| 336 | AirLoopHVAC | PSZ-AC_1:6 | User Heating Air Flow Ratio [] | 1.00000 |
| 337 | AirLoopHVAC | PSZ-AC_1:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 338 | AirLoopHVAC | PSZ-AC_2:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.75292 |
| 339 | AirLoopHVAC | PSZ-AC_2:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.75292 |
| 340 | AirLoopHVAC | PSZ-AC_2:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.75292 |
| 341 | AirLoopHVAC | PSZ-AC_2:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.75292 |
| 342 | AirLoopHVAC | PSZ-AC_2:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.75292 |
| 343 | AirLoopHVAC | PSZ-AC_2:7 | Adjusted Main Design Air Flow Rate [m3/s] | 2.75292 |
| 344 | AirLoopHVAC | PSZ-AC_2:7 | User Heating Air Flow Ratio [] | 1.00000 |
| 345 | AirLoopHVAC | PSZ-AC_2:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 346 | AirLoopHVAC | VAV_POD_1 | Design Supply Air Flow Rate [m3/s] | 29.51303 |
| 347 | AirLoopHVAC | PSZ-AC_1:6 | Design Supply Air Flow Rate [m3/s] | 1.60843 |
| 348 | AirLoopHVAC | PSZ-AC_2:7 | Design Supply Air Flow Rate [m3/s] | 2.75292 |
| 349 | Controller:OutdoorAir | VAV_POD_1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 29.51303 |
| 350 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 29.51303 |
| 351 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 676031.31012 |
| 352 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.72669 |
| 353 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 9.83669 |
| 354 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 225321.23566 |
| 355 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.72669 |
| 356 | Coil:Heating:Fuel | VAV_POD_1 HEATING COIL | Design Size Nominal Capacity [W] | 468033.13500 |
| 357 | Fan:VariableVolume | VAV_POD_1 FAN | Design Size Maximum Flow Rate [m3/s] | 29.51303 |
| 358 | Controller:OutdoorAir | PSZ-AC_1:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.60843 |
| 359 | Controller:OutdoorAir | PSZ-AC_1:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.25481 |
| 360 | Fan:SystemModel | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.60843 |
| 361 | Fan:SystemModel | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2673.19879 |
| 362 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.60843 |
| 363 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.60843 |
| 364 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.60843 |
| 365 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.60843 |
| 366 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.60843 |
| 367 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.80421 |
| 368 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.07229 |
| 369 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34567.45000 |
| 370 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17283.72500 |
| 371 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.74918 |
| 372 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.74918 |
| 373 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34567.45000 |
| 374 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37306.95870 |
| 375 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
| 376 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 377 | Coil:Heating:Fuel | PSZ-AC_1:6 HEATING COIL | Design Size Nominal Capacity [W] | 37306.95870 |
| 378 | Controller:OutdoorAir | PSZ-AC_2:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.75292 |
| 379 | Controller:OutdoorAir | PSZ-AC_2:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.48818 |
| 380 | Fan:SystemModel | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.75292 |
| 381 | Fan:SystemModel | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 4465.57538 |
| 382 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.75292 |
| 383 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.75292 |
| 384 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.75292 |
| 385 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.75292 |
| 386 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.75292 |
| 387 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.37646 |
| 388 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.83528 |
| 389 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 68361.53000 |
| 390 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 34180.76500 |
| 391 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
| 392 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
| 393 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 68361.53000 |
| 394 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 128129.15725 |
| 395 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
| 396 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 397 | Coil:Heating:Fuel | PSZ-AC_2:7 HEATING COIL | Design Size Nominal Capacity [W] | 128129.15725 |
| 398 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.50028E-003 |
| 399 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.54003 |
| 400 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.50028E-003 |
| 401 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1355.28577 |
| 402 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
| 403 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 514409.29286 |
| 404 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 514409.29000 |
| 405 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.50028E-003 |
| 406 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.05414E-004 |
| 407 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.26497E-002 |
| 408 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.05414E-004 |
| 409 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 13.46550 |
| 410 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.05414E-004 |
| Component Type | Name | Nominal Total Capacity {W} | |
| 1 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 12012.70 |
| 2 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 38834.76 |
| 3 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11005.59 |
| 4 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11880.94 |
| 5 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 38145.11 |
| 6 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11977.97 |
| 7 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 38514.62 |
| 8 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 10993.62 |
| 9 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11884.15 |
| 10 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 38158.03 |
| 11 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11981.94 |
| 12 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 38624.32 |
| 13 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11008.11 |
| 14 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11913.67 |
| 15 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 25761.05 |
| 16 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | 12707.45 |
| 17 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | 26483.78 |
| 18 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | 15303.65 |
| 19 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 9036.47 |
| 20 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 12001.01 |
| 21 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | 33981.02 |
| 22 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | 25473.02 |
| 23 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | 30353.95 |
| DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
| 1 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | N/A | N/A | 654353.74 | 2232747.63 | 11.37 | 3.13 | 3.33 | 3.31 | 3.44 | 10.68 | 11.35 | 11.29 | 11.72 | 32.7109 | 25.9526 | 17.4071 | 7.3061 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | 33301.9 | 10.90 | 10.90 | |||
| 2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | 66189.7 | 10.86 | 10.86 |
| Zone Name | # Surfaces | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 11 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 12 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | 10 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 11 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 12 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 11 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 12 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | 10 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 11 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 12 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 11 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 12 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | 11 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 11 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 12 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | 10 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | 15 |
| 18 | LOBBY_ZN_1_FLR_1 | 11 |
| 19 | MECH_ZN_1_FLR_1 | 10 |
| 20 | BATH_ZN_1_FLR_1 | 9 |
| 21 | OFFICES_ZN_1_FLR_1 | 12 |
| 22 | GYM_ZN_1_FLR_1 | 19 |
| 23 | KITCHEN_ZN_1_FLR_1 | 8 |
| 24 | CAFETERIA_ZN_1_FLR_1 | 12 |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 32.37 | 44.00 | 32.37 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 180.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 180.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 4 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | Door | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 5 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 8 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 9 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 10 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 11 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 12 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 161.46 | 212.00 | 161.46 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 15 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | Window | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 16 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | Door | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 17 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | Door | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 18 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 19 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 21 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 22 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 23 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 24 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 26 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 90.00 | 90.00 | 3.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 27 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 28 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 9.36 | 12.00 | 9.36 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 30 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | Window | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 2.64 | 2.64 | 2.64 | 270.00 | 90.00 | 2.90 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 31 | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.980E-002 | 1.971E-002 | 192.00 | 192.00 | 192.00 | 270.00 | 180.00 | 3.00 | 64.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 32 | CORRIDOR_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 192.00 | 192.00 | 192.00 | 90.00 | 0.00 | 3.00 | 64.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 33 | CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 384.00 | 384.00 | 384.00 | 0.00 | 90.00 | 384.00 | 1.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 34 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 35 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 36 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 32.37 | 44.00 | 32.37 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 | ||
| 37 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 0.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 38 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 0.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 |
| 39 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | Door | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | |
| 40 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 42 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 47 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 161.46 | 212.00 | 161.46 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 | ||
| 48 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 49 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 50 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | Window | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 51 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | Door | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 | |
| 52 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | Door | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 53 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 55 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 56 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 57 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 32.37 | 44.00 | 32.37 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 | ||
| 58 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 180.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 |
| 59 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 180.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.61 | 0.39 | 4 |
| 60 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | Door | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 | |
| 61 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 63 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 65 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 66 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 67 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 68 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 161.46 | 212.00 | 161.46 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 | ||
| 69 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 70 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 71 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | Window | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 72 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | Door | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 73 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | Door | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 | |
| 74 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 76 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 77 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 78 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 79 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 80 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 82 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 90.00 | 90.00 | 3.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 85 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 9.36 | 12.00 | 9.36 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 86 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | Window | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 2.64 | 2.64 | 2.64 | 270.00 | 90.00 | 2.90 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 87 | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.980E-002 | 1.971E-002 | 192.00 | 192.00 | 192.00 | 270.00 | 180.00 | 3.00 | 64.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 88 | CORRIDOR_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 192.00 | 192.00 | 192.00 | 90.00 | 0.00 | 3.00 | 64.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 89 | CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 384.00 | 384.00 | 384.00 | 0.00 | 90.00 | 384.00 | 1.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 90 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 91 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 32.37 | 44.00 | 32.37 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.56 | 0.44 | 4 | ||
| 93 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 0.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 94 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 0.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 |
| 95 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | Door | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 | |
| 96 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 99 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 100 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 101 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 103 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 161.46 | 212.00 | 161.46 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 | ||
| 104 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 |
| 105 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 106 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | Window | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 107 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | Door | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 108 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | Door | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | |
| 109 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 32.37 | 44.00 | 32.37 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.56 | 0.44 | 4 | ||
| 114 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 180.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 |
| 115 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 180.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 |
| 116 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | Door | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.58 | 0.42 | 4 | |
| 117 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 119 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 120 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 121 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 122 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 123 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 124 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 161.46 | 212.00 | 161.46 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 | ||
| 125 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 126 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 127 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | Window | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 |
| 128 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | Door | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | |
| 129 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | Door | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 130 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 131 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 134 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 135 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 136 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 137 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 90.00 | 90.00 | 3.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 139 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 72.00 | 72.00 | 72.00 | 0.00 | 90.00 | 18.00 | 4.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 140.00 | 140.00 | 140.00 | 0.00 | 90.00 | 35.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 141 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 9.36 | 12.00 | 9.36 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | Window | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 2.64 | 2.64 | 2.64 | 270.00 | 90.00 | 2.90 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 144 | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.980E-002 | 1.971E-002 | 192.00 | 192.00 | 192.00 | 270.00 | 180.00 | 3.00 | 64.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 145 | CORRIDOR_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 192.00 | 192.00 | 192.00 | 90.00 | 0.00 | 3.00 | 64.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 146 | CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 384.00 | 384.00 | 384.00 | 0.00 | 90.00 | 384.00 | 1.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 147 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 148 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 32.40 | 44.00 | 32.40 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 150 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 0.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 151 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 8.43 | 8.43 | 8.43 | 0.00 | 90.00 | 8.43 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 152 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | Door | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 153 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 154 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 155 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 156 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 157 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 158 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 140.00 | 140.00 | 140.00 | 180.00 | 90.00 | 35.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 159 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 105.30 | 140.00 | 105.30 | 0.00 | 90.00 | 35.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 10.27 | 10.27 | 10.27 | 0.00 | 90.00 | 10.82 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 162 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 10.27 | 10.27 | 10.27 | 0.00 | 90.00 | 10.82 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 163 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | Window | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 10.27 | 10.27 | 10.27 | 0.00 | 90.00 | 10.82 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 164 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | Door | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 165 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | Door | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 166 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 315.00 | 315.00 | 315.00 | 270.00 | 180.00 | 9.00 | 35.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 168 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 315.00 | 315.00 | 315.00 | 90.00 | 0.00 | 9.00 | 35.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 169 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 630.00 | 630.00 | 630.00 | 0.00 | 90.00 | 630.00 | 1.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 170 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 72.00 | 72.00 | 72.00 | 180.00 | 90.00 | 18.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 171 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 172 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 54.21 | 72.00 | 54.21 | 0.00 | 90.00 | 18.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 173 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 1.16 | 1.16 | 1.16 | 0.00 | 90.00 | 1.22 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 174 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 14.68 | 14.68 | 14.68 | 0.00 | 90.00 | 15.46 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | Door | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 176 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 162.00 | 162.00 | 162.00 | 270.00 | 180.00 | 9.00 | 18.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 178 | COMPUTER_CLASS_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 162.00 | 162.00 | 162.00 | 90.00 | 0.00 | 9.00 | 18.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 179 | COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 324.00 | 324.00 | 324.00 | 0.00 | 90.00 | 324.00 | 1.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 180 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 180.00 | 90.00 | 13.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 181 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 168.00 | 168.00 | 168.00 | 90.00 | 90.00 | 42.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 0.00 | 90.00 | 13.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 183 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 26.13 | 36.00 | 26.13 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | ||
| 187 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | Window | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 1.26 | 1.26 | 1.26 | 270.00 | 90.00 | 1.22 | 1.03 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.73 | 0.27 | 4 |
| 188 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | Window | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 6.66 | 6.66 | 6.66 | 270.00 | 90.00 | 6.46 | 1.03 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 189 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | Door | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.71 | 0.29 | 4 | |
| 190 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 191 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR | 2.090E-002 | 2.079E-002 | 546.00 | 546.00 | 546.00 | 270.00 | 180.00 | 42.00 | 13.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 193 | MAIN_CORRIDOR_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 546.00 | 546.00 | 546.00 | 90.00 | 0.00 | 42.00 | 13.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 194 | MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1092.00 | 1092.00 | 1092.00 | 0.00 | 90.00 | 1092.00 | 1.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 195 | LOBBY_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 57.33 | 76.00 | 57.33 | 180.00 | 90.00 | 19.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 196 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | LOBBY_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 1.15 | 1.15 | 1.15 | 180.00 | 90.00 | 1.22 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 197 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | LOBBY_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 15.57 | 15.57 | 15.57 | 180.00 | 90.00 | 16.46 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 198 | LOBBY_ZN_1_FLR_1_WALL_1_DOOR | Door | LOBBY_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 199 | LOBBY_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | OFFICES_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | LOBBY_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 6.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | LOBBY_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 0.00 | 90.00 | 13.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | LOBBY_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 203 | LOBBY_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 171.00 | 171.00 | 171.00 | 270.00 | 180.00 | 9.00 | 19.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 204 | LOBBY_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 171.00 | 171.00 | 171.00 | 90.00 | 0.00 | 9.00 | 19.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 205 | LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 342.00 | 342.00 | 342.00 | 0.00 | 90.00 | 342.00 | 1.00 | 0.00 | LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 206 | MECH_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 180.00 | 90.00 | 6.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | MECH_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 48.00 | 48.00 | 48.00 | 90.00 | 90.00 | 12.00 | 4.00 | 0.00 | OFFICES_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 208 | MECH_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.00 | 68.00 | 68.00 | 90.00 | 90.00 | 17.00 | 4.00 | 0.00 | GYM_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | MECH_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 32.00 | 32.00 | 32.00 | 90.00 | 90.00 | 8.00 | 4.00 | 0.00 | KITCHEN_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | MECH_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.00 | 20.00 | 20.00 | 90.00 | 90.00 | 5.00 | 4.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | MECH_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 6.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | MECH_ZN_1_FLR_1_WALL_7 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 168.00 | 168.00 | 168.00 | 270.00 | 90.00 | 42.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | MECH_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MECH_ZN_1_FLR_1_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 252.00 | 252.00 | 252.00 | 270.00 | 180.00 | 42.00 | 6.00 | 0.00 | MECH_ZN_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 214 | MECH_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 252.00 | 252.00 | 252.00 | 90.00 | 0.00 | 42.00 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 215 | MECH_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 504.00 | 504.00 | 504.00 | 0.00 | 90.00 | 504.00 | 1.00 | 0.00 | MECH_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 216 | BATH_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 180.00 | 90.00 | 13.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 217 | BATH_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 180.00 | 90.00 | 6.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 218 | BATH_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.00 | 40.00 | 40.00 | 90.00 | 90.00 | 10.00 | 4.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | BATH_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 76.00 | 76.00 | 76.00 | 0.00 | 90.00 | 19.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | BATH_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 31.20 | 40.00 | 31.20 | 270.00 | 90.00 | 10.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | ||
| 221 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | Window | BATH_ZN_1_FLR_1_WALL_5 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 8.80 | 8.80 | 8.80 | 270.00 | 90.00 | 9.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 222 | BATH_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | BATH_ZN_1_FLR_1_FLOOR_FFACTOR | 6.720E-002 | 6.612E-002 | 190.00 | 190.00 | 190.00 | 270.00 | 180.00 | 10.00 | 19.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 223 | BATH_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 190.00 | 190.00 | 190.00 | 90.00 | 0.00 | 10.00 | 19.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 224 | BATH_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 380.00 | 380.00 | 380.00 | 0.00 | 90.00 | 380.00 | 1.00 | 0.00 | BATH_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 225 | OFFICES_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 63.57 | 84.00 | 63.57 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | OFFICES_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 1.14 | 1.14 | 1.14 | 180.00 | 90.00 | 1.22 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 227 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | OFFICES_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 17.34 | 17.34 | 17.34 | 180.00 | 90.00 | 18.46 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 228 | OFFICES_ZN_1_FLR_1_WALL_1_DOOR | Door | OFFICES_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 229 | OFFICES_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 65.52 | 84.00 | 65.52 | 90.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 230 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | Window | OFFICES_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 18.48 | 18.48 | 18.48 | 90.00 | 90.00 | 20.90 | 0.88 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 231 | OFFICES_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | GYM_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | OFFICES_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 48.00 | 48.00 | 48.00 | 270.00 | 90.00 | 12.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | OFFICES_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 234 | OFFICES_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR | 0.123 | 0.119 | 441.00 | 441.00 | 441.00 | 270.00 | 180.00 | 21.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 235 | OFFICES_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 441.00 | 441.00 | 441.00 | 90.00 | 0.00 | 21.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 236 | OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 882.00 | 882.00 | 882.00 | 0.00 | 90.00 | 882.00 | 1.00 | 0.00 | OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 237 | GYM_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | OFFICES_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | GYM_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 51.09 | 68.00 | 51.09 | 90.00 | 90.00 | 17.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | Window | GYM_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 1.17 | 1.17 | 1.17 | 90.00 | 90.00 | 1.22 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 240 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | Window | GYM_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 13.79 | 13.79 | 13.79 | 90.00 | 90.00 | 14.46 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 241 | GYM_ZN_1_FLR_1_WALL_2_DOOR | Door | GYM_ZN_1_FLR_1_WALL_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 242 | GYM_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | KITCHEN_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 243 | GYM_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.00 | 68.00 | 68.00 | 270.00 | 90.00 | 17.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 244 | GYM_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | GYM_ZN_1_FLR_1_FLOOR_FFACTOR | 6.074E-002 | 5.986E-002 | 357.00 | 357.00 | 357.00 | 270.00 | 180.00 | 17.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 245 | GYM_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 343.62 | 357.00 | 343.62 | 90.00 | 0.00 | 17.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 246 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 247 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 248 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 249 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 250 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 251 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 252 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 253 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 254 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 255 | GYM_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 714.00 | 714.00 | 714.00 | 0.00 | 90.00 | 714.00 | 1.00 | 0.00 | GYM_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 256 | KITCHEN_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | GYM_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 257 | KITCHEN_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 24.96 | 32.00 | 24.96 | 90.00 | 90.00 | 8.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 258 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | Window | KITCHEN_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 7.04 | 7.04 | 7.04 | 90.00 | 90.00 | 7.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 259 | KITCHEN_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 260 | KITCHEN_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 32.00 | 32.00 | 32.00 | 270.00 | 90.00 | 8.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 261 | KITCHEN_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR | 6.074E-002 | 5.986E-002 | 168.00 | 168.00 | 168.00 | 270.00 | 180.00 | 8.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 262 | KITCHEN_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 168.00 | 168.00 | 168.00 | 90.00 | 0.00 | 8.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 263 | KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 336.00 | 336.00 | 336.00 | 0.00 | 90.00 | 336.00 | 1.00 | 0.00 | KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 264 | CAFETERIA_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | KITCHEN_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 265 | CAFETERIA_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 44.85 | 60.00 | 44.85 | 90.00 | 90.00 | 15.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 266 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | Window | CAFETERIA_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 1.18 | 1.18 | 1.18 | 90.00 | 90.00 | 1.22 | 0.96 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 267 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | Window | CAFETERIA_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 12.02 | 12.02 | 12.02 | 90.00 | 90.00 | 12.46 | 0.96 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 268 | CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | Door | CAFETERIA_ZN_1_FLR_1_WALL_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 269 | CAFETERIA_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 65.52 | 84.00 | 65.52 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.54 | 0.46 | 4 | ||
| 270 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | Window | CAFETERIA_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 18.48 | 18.48 | 18.48 | 0.00 | 90.00 | 20.90 | 0.88 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.54 | 0.46 | 4 |
| 271 | CAFETERIA_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.00 | 40.00 | 40.00 | 270.00 | 90.00 | 10.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 272 | CAFETERIA_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.00 | 20.00 | 20.00 | 270.00 | 90.00 | 5.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 273 | CAFETERIA_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR | 0.148 | 0.143 | 315.00 | 315.00 | 315.00 | 270.00 | 180.00 | 15.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 274 | CAFETERIA_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 315.00 | 315.00 | 315.00 | 90.00 | 0.00 | 15.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 275 | CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 630.00 | 630.00 | 630.00 | 0.00 | 90.00 | 630.00 | 1.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 276 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 76.00 | 76.00 | 76.00 | 180.00 | 90.00 | 19.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 277 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 63.57 | 84.00 | 63.57 | 90.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.54 | 0.46 | 4 | ||
| 278 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | Window | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 1.14 | 1.14 | 1.14 | 90.00 | 90.00 | 1.22 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.69 | 0.31 | 4 |
| 279 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | Window | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 17.33 | 17.33 | 17.33 | 90.00 | 90.00 | 18.46 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.53 | 0.47 | 4 |
| 280 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | Door | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 281 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.384 | 0.363 | 59.28 | 76.00 | 59.28 | 0.00 | 90.00 | 19.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 282 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | Window | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.49 | N/A | 3.241 | No | 16.72 | 16.72 | 16.72 | 0.00 | 90.00 | 18.90 | 0.88 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 283 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 284 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 285 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 286 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR | 0.129 | 0.125 | 399.00 | 399.00 | 399.00 | 270.00 | 180.00 | 21.00 | 19.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 287 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 399.00 | 399.00 | 399.00 | 90.00 | 0.00 | 21.00 | 19.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 288 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 798.00 | 798.00 | 798.00 | 0.00 | 90.00 | 798.00 | 1.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.6641703088 | 0.6960295193 | Pass | Pass | 0.7729214049 | 1.1993472673 | Pass | Pass |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.3872117199 | 0.4473334277 | Pass | Pass | 0.8474845758 | 1.5241964754 | Pass | Pass |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.3801427045 | 0.3733102868 | Pass | Pass | 0.6877440182 | 0.6742585528 | Pass | Pass |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.8768894907 | 0.8275054187 | Pass | Pass | 0.6431451564 | 0.6231737638 | Pass | Pass |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.6086948346 | 0.5850523599 | Pass | Pass | 0.6663489849 | 0.6290730005 | Pass | Pass |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.6900819635 | 0.7120872513 | Pass | Pass | 0.7511164111 | 1.0464630577 | Pass | Pass |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.4243720676 | 0.4663562694 | Pass | Pass | 0.8345201485 | 1.5461601686 | Pass | Pass |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.3912691693 | 0.3809584439 | Pass | Pass | 0.6812860262 | 0.6699738509 | Pass | Pass |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.8778095001 | 0.8280875595 | Pass | Pass | 0.6431395821 | 0.6236244464 | Pass | Pass |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.6097003062 | 0.5856197526 | Pass | Pass | 0.6657939830 | 0.6288442487 | Pass | Pass |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.6824710208 | 0.7077383634 | Pass | Pass | 0.7631254881 | 1.1434088161 | Pass | Pass |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.4177039169 | 0.4635955401 | Pass | Pass | 0.8394339522 | 1.5927227864 | Pass | Pass |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.3890821182 | 0.3804388646 | Pass | Pass | 0.6839781868 | 0.6736336673 | Pass | Pass |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.8778859181 | 0.8301665787 | Pass | Pass | 0.6467363420 | 0.6262965633 | Pass | Pass |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.6193299585 | 0.5952548362 | Pass | Pass | 0.6654311191 | 0.6304058569 | Pass | Pass |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.5858457612 | 0.5659113276 | Pass | Pass | 0.6670575814 | 0.6349204342 | Pass | Pass |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.3714630825 | 0.3450097082 | Pass | Pass | 0.6672924721 | 0.5972782594 | Pass | Pass |
| 18 | LOBBY_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.4538867163 | 0.4920713088 | Pass | Pass | 0.8661540761 | 1.9550706594 | Pass | Pass |
| 19 | MECH_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1958104937 | 0.2039773762 | Pass | Pass | 0.7886492266 | 0.9306571969 | Pass | Pass |
| 20 | BATH_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.4842610076 | 0.4476667505 | Pass | Pass | 0.6424952285 | 0.6017110314 | Pass | Pass |
| 21 | OFFICES_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.4684344643 | 0.4720724257 | Pass | Pass | 0.7029181880 | 0.6645788135 | Pass | Pass |
| 22 | GYM_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.4708214546 | 0.4708259308 | Pass | Pass | 0.7028140382 | 0.6619150655 | Pass | Pass |
| 23 | KITCHEN_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.7621443428E-002 | 0.1287213799 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 24 | CAFETERIA_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.8384760375 | 0.6879714008 | Pass | Pass | 1.1887783300 | 2.8078704625 | Pass | Pass |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.5523643212 | 0.5331585603 | Pass | Pass | 0.6766820313 | 0.6364670326 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 9656.15 | 259.68 | 1955.34 | 4292.52 | 2170.15 | 18333.89 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
| INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 0.00 | 0 | |||
| Feb | 0.00 | 0 | |||
| Mar | 12.00 | 13 | |||
| Apr | 16.00 | 23 | |||
| May | 0.00 | 0 | |||
| Jun | 190.00 | 53 | |||
| Jul | 136.00 | 41 | |||
| Aug | 87.00 | 42 | |||
| Sep | 0.00 | 0 | |||
| Oct | 0.00 | 0 | |||
| Nov | 0.00 | 0 | |||
| Dec | 0.00 | 0 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 44.00 | 32.37 | 180.00 | 90.00 | S |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 212.00 | 161.46 | 180.00 | 90.00 | S |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 12.00 | 9.36 | 270.00 | 90.00 | W |
| CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.020 | 0.020 | 192.00 | 192.00 | 270.00 | 180.00 | |
| CORRIDOR_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 192.00 | 192.00 | 90.00 | 0.00 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 44.00 | 32.37 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 212.00 | 161.46 | 0.00 | 90.00 | N |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 44.00 | 32.37 | 180.00 | 90.00 | S |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 212.00 | 161.46 | 180.00 | 90.00 | S |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 12.00 | 9.36 | 270.00 | 90.00 | W |
| CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.020 | 0.020 | 192.00 | 192.00 | 270.00 | 180.00 | |
| CORRIDOR_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 192.00 | 192.00 | 90.00 | 0.00 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 44.00 | 32.37 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 212.00 | 161.46 | 0.00 | 90.00 | N |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 44.00 | 32.37 | 180.00 | 90.00 | S |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 212.00 | 161.46 | 180.00 | 90.00 | S |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 12.00 | 9.36 | 270.00 | 90.00 | W |
| CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.020 | 0.020 | 192.00 | 192.00 | 270.00 | 180.00 | |
| CORRIDOR_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 192.00 | 192.00 | 90.00 | 0.00 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 44.00 | 32.40 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 140.00 | 105.30 | 0.00 | 90.00 | N |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 315.00 | 315.00 | 270.00 | 180.00 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 315.00 | 315.00 | 90.00 | 0.00 | |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 72.00 | 54.21 | 0.00 | 90.00 | N |
| COMPUTER_CLASS_ZN_1_FLR_1_FLOOR | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 162.00 | 162.00 | 270.00 | 180.00 | |
| COMPUTER_CLASS_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 162.00 | 162.00 | 90.00 | 0.00 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 36.00 | 26.13 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.021 | 0.021 | 546.00 | 546.00 | 270.00 | 180.00 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 546.00 | 546.00 | 90.00 | 0.00 | |
| LOBBY_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 76.00 | 57.33 | 180.00 | 90.00 | S |
| LOBBY_ZN_1_FLR_1_FLOOR | LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 171.00 | 171.00 | 270.00 | 180.00 | |
| LOBBY_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 171.00 | 171.00 | 90.00 | 0.00 | |
| MECH_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 252.00 | 252.00 | 90.00 | 0.00 | |
| BATH_ZN_1_FLR_1_WALL_5 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 40.00 | 31.20 | 270.00 | 90.00 | W |
| BATH_ZN_1_FLR_1_FLOOR | BATH_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.066 | 0.067 | 190.00 | 190.00 | 270.00 | 180.00 | |
| BATH_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 190.00 | 190.00 | 90.00 | 0.00 | |
| OFFICES_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 84.00 | 63.57 | 180.00 | 90.00 | S |
| OFFICES_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 84.00 | 65.52 | 90.00 | 90.00 | E |
| OFFICES_ZN_1_FLR_1_FLOOR | OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.120 | 0.123 | 441.00 | 441.00 | 270.00 | 180.00 | |
| OFFICES_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 441.00 | 441.00 | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 68.00 | 51.09 | 90.00 | 90.00 | E |
| GYM_ZN_1_FLR_1_FLOOR | GYM_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.060 | 0.061 | 357.00 | 357.00 | 270.00 | 180.00 | |
| GYM_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 357.00 | 343.62 | 90.00 | 0.00 | |
| KITCHEN_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 32.00 | 24.96 | 90.00 | 90.00 | E |
| KITCHEN_ZN_1_FLR_1_FLOOR | KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.060 | 0.061 | 168.00 | 168.00 | 270.00 | 180.00 | |
| KITCHEN_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 168.00 | 168.00 | 90.00 | 0.00 | |
| CAFETERIA_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 60.00 | 44.85 | 90.00 | 90.00 | E |
| CAFETERIA_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 84.00 | 65.52 | 0.00 | 90.00 | N |
| CAFETERIA_ZN_1_FLR_1_FLOOR | CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.144 | 0.148 | 315.00 | 315.00 | 270.00 | 180.00 | |
| CAFETERIA_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 315.00 | 315.00 | 90.00 | 0.00 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 84.00 | 63.57 | 90.00 | 90.00 | E |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 76.00 | 59.28 | 0.00 | 90.00 | N |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.127 | 0.129 | 399.00 | 399.00 | 270.00 | 180.00 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 399.00 | 399.00 | 90.00 | 0.00 |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 90.00 | 90.00 | E |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 90.00 | 90.00 | E |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 90.00 | 90.00 | E |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 72.00 | 72.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 140.00 | 140.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 140.00 | 140.00 | 180.00 | 90.00 | S |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 72.00 | 72.00 | 180.00 | 90.00 | S |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 180.00 | 90.00 | S |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 168.00 | 168.00 | 90.00 | 90.00 | E |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 0.00 | 90.00 | N |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 270.00 | 90.00 | W |
| LOBBY_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| LOBBY_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 0.00 | 90.00 | N |
| LOBBY_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 0.00 | 90.00 | N |
| LOBBY_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MECH_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 180.00 | 90.00 | S |
| MECH_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 48.00 | 48.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 68.00 | 68.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 32.00 | 32.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 20.00 | 20.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 0.00 | 90.00 | N |
| MECH_ZN_1_FLR_1_WALL_7 | INT_WALL | 0.30 | 2.511 | 6.299 | 168.00 | 168.00 | 270.00 | 90.00 | W |
| MECH_ZN_1_FLR_1_FLOOR | MECH_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 252.00 | 252.00 | 270.00 | 180.00 | |
| BATH_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 180.00 | 90.00 | S |
| BATH_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 180.00 | 90.00 | S |
| BATH_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 40.00 | 40.00 | 90.00 | 90.00 | E |
| BATH_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 76.00 | 76.00 | 0.00 | 90.00 | N |
| OFFICES_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 0.00 | 90.00 | N |
| OFFICES_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 48.00 | 48.00 | 270.00 | 90.00 | W |
| OFFICES_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| GYM_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 180.00 | 90.00 | S |
| GYM_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 0.00 | 90.00 | N |
| GYM_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 68.00 | 68.00 | 270.00 | 90.00 | W |
| KITCHEN_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 180.00 | 90.00 | S |
| KITCHEN_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 0.00 | 90.00 | N |
| KITCHEN_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 32.00 | 32.00 | 270.00 | 90.00 | W |
| CAFETERIA_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 180.00 | 90.00 | S |
| CAFETERIA_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 40.00 | 40.00 | 270.00 | 90.00 | W |
| CAFETERIA_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 20.00 | 20.00 | 270.00 | 90.00 | W |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 76.00 | 76.00 | 180.00 | 90.00 | S |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 270.00 | 90.00 | W |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 384.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 384.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 384.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 630.00 | 0.00 | 90.00 | N | ||
| COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 324.00 | 0.00 | 90.00 | N | ||
| MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1092.00 | 0.00 | 90.00 | N | ||
| LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 342.00 | 0.00 | 90.00 | N | ||
| MECH_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 504.00 | 0.00 | 90.00 | N | ||
| BATH_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 380.00 | 0.00 | 90.00 | N | ||
| OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 882.00 | 0.00 | 90.00 | N | ||
| GYM_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 714.00 | 0.00 | 90.00 | N | ||
| KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 336.00 | 0.00 | 90.00 | N | ||
| CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 630.00 | 0.00 | 90.00 | N | ||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 798.00 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 2.64 | 0.00 | 0.00 | 2.64 | 2.64 | 3.241 | 0.491 | 0.541 | No | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | 270.00 | 90.00 | W | |||||||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 2.64 | 0.00 | 0.00 | 2.64 | 2.64 | 3.241 | 0.491 | 0.541 | No | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | 270.00 | 90.00 | W | |||||||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 2.64 | 0.00 | 0.00 | 2.64 | 2.64 | 3.241 | 0.491 | 0.541 | No | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | 270.00 | 90.00 | W | |||||||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 8.43 | 0.00 | 0.00 | 8.43 | 8.43 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.491 | 0.541 | No | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 10.27 | 0.00 | 0.00 | 10.27 | 10.27 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 10.27 | 0.00 | 0.00 | 10.27 | 10.27 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.49 | 10.27 | 0.00 | 0.00 | 10.27 | 10.27 | 3.241 | 0.491 | 0.541 | No | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 1.16 | 0.00 | 0.00 | 1.16 | 1.16 | 3.241 | 0.491 | 0.541 | No | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 14.68 | 0.00 | 0.00 | 14.68 | 14.68 | 3.241 | 0.491 | 0.541 | No | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 1.26 | 0.00 | 0.00 | 1.26 | 1.26 | 3.241 | 0.491 | 0.541 | No | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | 270.00 | 90.00 | W | |||||||
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 6.66 | 0.00 | 0.00 | 6.66 | 6.66 | 3.241 | 0.491 | 0.541 | No | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | 270.00 | 90.00 | W | |||||||
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 1.15 | 0.00 | 0.00 | 1.15 | 1.15 | 3.241 | 0.491 | 0.541 | No | LOBBY_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 15.57 | 0.00 | 0.00 | 15.57 | 15.57 | 3.241 | 0.491 | 0.541 | No | LOBBY_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 8.80 | 0.00 | 0.00 | 8.80 | 8.80 | 3.241 | 0.491 | 0.541 | No | BATH_ZN_1_FLR_1_WALL_5 | 270.00 | 90.00 | W | |||||||
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 1.14 | 0.00 | 0.00 | 1.14 | 1.14 | 3.241 | 0.491 | 0.541 | No | OFFICES_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 17.34 | 0.00 | 0.00 | 17.34 | 17.34 | 3.241 | 0.491 | 0.541 | No | OFFICES_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 18.48 | 0.00 | 0.00 | 18.48 | 18.48 | 3.241 | 0.491 | 0.541 | No | OFFICES_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 1.17 | 0.00 | 0.00 | 1.17 | 1.17 | 3.241 | 0.491 | 0.541 | No | GYM_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 13.79 | 0.00 | 0.00 | 13.79 | 13.79 | 3.241 | 0.491 | 0.541 | No | GYM_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.683 | 0.682 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.682 | 0.682 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.683 | 0.682 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.682 | 0.682 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.683 | 0.682 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.682 | 0.682 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.683 | 0.682 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.682 | 0.682 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.683 | 0.682 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.682 | 0.682 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.683 | 0.682 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.682 | 0.682 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.683 | 0.682 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.682 | 0.682 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.683 | 0.682 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.682 | 0.682 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | NONRESSKYLIGHT_U_0.69_SHGC_0.68 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.683 | 0.682 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.682 | 0.682 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 7.04 | 0.00 | 0.00 | 7.04 | 7.04 | 3.241 | 0.491 | 0.541 | No | KITCHEN_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 1.18 | 0.00 | 0.00 | 1.18 | 1.18 | 3.241 | 0.491 | 0.541 | No | CAFETERIA_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 12.02 | 0.00 | 0.00 | 12.02 | 12.02 | 3.241 | 0.491 | 0.541 | No | CAFETERIA_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 18.48 | 0.00 | 0.00 | 18.48 | 18.48 | 3.241 | 0.491 | 0.541 | No | CAFETERIA_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 1.14 | 0.00 | 0.00 | 1.14 | 1.14 | 3.241 | 0.491 | 0.541 | No | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.49 | 17.33 | 0.00 | 0.00 | 17.33 | 17.33 | 3.241 | 0.491 | 0.541 | No | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.49 | 16.72 | 0.00 | 0.00 | 16.72 | 16.72 | 3.241 | 0.491 | 0.541 | No | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| Total or Average | 565.98 | 3.257 | 0.496 | 0.544 | |||||||||||||||||
| North Total or Average | 204.13 | 3.241 | 0.491 | 0.541 | |||||||||||||||||
| Non-North Total or Average | 361.86 | 3.266 | 0.499 | 0.546 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 |
| LOBBY_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LOBBY_ZN_1_FLR_1_WALL_1 |
| OFFICES_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | OFFICES_ZN_1_FLR_1_WALL_1 |
| GYM_ZN_1_FLR_1_WALL_2_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | GYM_ZN_1_FLR_1_WALL_2 |
| CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CAFETERIA_ZN_1_FLR_1_WALL_2 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.81 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.69 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.69 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | 0.73 | 0.97 | 1.00 | 0.87 | 0.99 | 1.00 | 0.00 | 0.96 | 0.69 |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.95 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.95 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.95 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | 0.73 | 0.97 | 1.00 | 0.87 | 0.99 | 1.00 | 0.00 | 0.96 | 0.95 |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.48 |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | 0.00 | 0.00 | 0.63 | 0.00 | 0.00 | 0.89 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | 0.00 | 0.00 | 0.77 | 0.00 | 0.00 | 0.93 | 0.00 | 0.00 | 0.18 |
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.67 | 0.28 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | 0.99 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.31 | 0.82 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORRIDOR_POD_1_ZN_1_FLR_1_LIGHTS | CORRIDOR_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | GENERAL | 5.4810 | 192.00 | 1052.35 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 14.50 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORRIDOR_POD_2_ZN_1_FLR_1_LIGHTS | CORRIDOR_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | GENERAL | 5.4810 | 192.00 | 1052.35 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 14.50 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORRIDOR_POD_3_ZN_1_FLR_1_LIGHTS | CORRIDOR_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | GENERAL | 5.4810 | 192.00 | 1052.35 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 14.50 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 315.00 | 4746.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 65.42 |
| COMPUTER_CLASS_ZN_1_FLR_1_LIGHTS | COMPUTER_CLASS_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | GENERAL | 15.0695 | 162.00 | 2441.25 | LightsWired | LTG_SCH_COMPUTER_ROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 33.64 |
| MAIN_CORRIDOR_ZN_1_FLR_1_LIGHTS | MAIN_CORRIDOR_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | GENERAL | 5.4810 | 546.00 | 2992.63 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 41.24 |
| LOBBY_ZN_1_FLR_1_LIGHTS | LOBBY_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | GENERAL | 13.9931 | 171.00 | 2392.81 | LightsWired | LTG_SCH_LOBBY | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 32.97 |
| MECH_ZN_1_FLR_1_LIGHTS | MECH_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | GENERAL | 16.1458 | 252.00 | 4068.75 | LightsWired | LTG_SCH_MECHANICAL | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 56.07 |
| BATH_ZN_1_FLR_1_LIGHTS | BATH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | GENERAL | 9.6875 | 190.00 | 1840.63 | LightsWired | LTG_SCH_BATH | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 25.37 |
| OFFICES_ZN_1_FLR_1_LIGHTS | OFFICES_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GENERAL | 11.8403 | 441.00 | 5221.57 | LightsWired | LTG_SCH_OFFICE | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 71.96 |
| GYM_ZN_1_FLR_1_LIGHTS | GYM_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | GENERAL | 13.3472 | 357.00 | 4764.96 | LightsWired | LTG_SCH_GYM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 65.67 |
| KITCHEN_ZN_1_FLR_1_LIGHTS | KITCHEN_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | GENERAL | 12.9167 | 168.00 | 2170.00 | LightsWired | LTG_SCH_KITCHEN | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 29.90 |
| CAFETERIA_ZN_1_FLR_1_LIGHTS | CAFETERIA_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | GENERAL | 9.6875 | 315.00 | 3051.57 | LightsWired | LTG_SCH_CAFETERIA | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 42.05 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_LIGHTS | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | GENERAL | 16.6840 | 399.00 | 6656.93 | LightsWired | LTG_SCH_LIBRARY | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 91.74 |
| Interior Lighting Total | 12.8652 | 6871.00 | 88396.96 | 1218.18 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| EXTERIOR_LIGHTS | 5897.73 | AstronomicalClock | - | 83.52 | 83.52 | 92.46 | |
| Exterior Lighting Total | 5897.73 | 92.46 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| HEATSYS1 BOILER | Boiler:HotWater | 514409.29 | 0.75 |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | 676031.31 | 491266.72 | 184764.59 | 0.73 | 3.60 | |||
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34567.45 | 25897.24 | 8670.21 | 0.75 | 3.50 | |||
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 68361.53 | 47926.90 | 20434.63 | 0.70 | 3.40 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| VAV_POD_1 COOLING COIL | 654353.7 | 3.13 | 10.68 | N/A | N/A | 11.37 | |
| PSZ-AC_1:6 COOLING COIL | 33301.9 | 10.90 | 10.90 | ||||
| PSZ-AC_2:7 COOLING COIL | 66189.7 | 10.86 | 10.86 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12661.84 | 12012.70 | - |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 40933.30 | 38834.76 | - |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11600.31 | 11005.59 | - |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12522.96 | 11880.94 | - |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 40206.38 | 38145.11 | - |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12625.23 | 11977.97 | - |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 40595.86 | 38514.62 | - |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11587.69 | 10993.62 | - |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12526.34 | 11884.15 | - |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 40220.00 | 38158.03 | - |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12629.41 | 11981.94 | - |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 40711.49 | 38624.32 | - |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11602.96 | 11008.11 | - |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12557.45 | 11913.67 | - |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 27153.12 | 25761.05 | - |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 13394.13 | 12707.45 | - |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 27914.90 | 26483.78 | - |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16130.62 | 15303.65 | - |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9524.78 | 9036.47 | - |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12649.52 | 12001.01 | - |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 35817.28 | 33981.02 | - |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 26849.53 | 25473.02 | - |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 31994.20 | 30353.95 | - |
| VAV_POD_1 HEATING COIL | Coil:Heating:Fuel | 468033.13 | 0.79 | |
| PSZ-AC_1:6 HEATING COIL | Coil:Heating:Fuel | 37306.96 | 0.80 | |
| PSZ-AC_2:7 HEATING COIL | Coil:Heating:Fuel | 128129.16 | 0.79 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| BATH_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 0.28 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| GYM_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.54 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| KITCHEN_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 2.12 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| CAFETERIA_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.38 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.28 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| VAV_POD_1 FAN | Fan:VariableVolume | 0.62 | 1337.13 | 29.51 | 63639.34 | 2156.31 | 1.00 | 1.11 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
| PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.61 | 2673.20 | 1662.00 | 1.00 | 1.25 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 2.75 | 4465.58 | 1622.12 | 1.00 | 1.22 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004500 | 1355.29 | 301156.09 | 0.90 | General |
| SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000105 | 13.47 | 127739.32 | 0.30 | General |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| SWH BOOSTER G WATER HEATER | WaterHeater:Mixed | 0.02 | 6000.00 | 0.80 | 1.09 | 0.99 |
| SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 14.75 | 0.47 |
| DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 654353.74 | 3.13 | 10.68 | 11.37 | 32.7109 | 3.33 | 11.35 | 25.9526 | 3.31 | 11.29 | 17.4071 | 3.44 | 11.72 | 7.3061 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 7609.25 | 8750.63 | 88.39 | 0.582 | 0.669 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00932 | 29.60 | 0.01272 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 31898.51 | 36683.29 | 76.90 | 2.439 | 2.804 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00940 | 30.10 | 0.01273 | 0.897 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 6334.55 | 7284.74 | 37.94 | 0.484 | 0.557 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00886 | 29.73 | 0.01273 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 6748.00 | 7760.20 | 78.39 | 0.516 | 0.593 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00942 | 28.69 | 0.01272 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 26554.32 | 30537.47 | 64.02 | 2.030 | 2.335 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00958 | 30.10 | 0.01273 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 7537.62 | 8668.26 | 87.56 | 0.576 | 0.663 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00932 | 29.60 | 0.01272 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 31438.21 | 36153.94 | 75.79 | 2.403 | 2.764 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00941 | 30.10 | 0.01273 | 0.897 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 6307.18 | 7253.25 | 37.78 | 0.482 | 0.554 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00886 | 29.73 | 0.01273 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 6753.08 | 7766.04 | 78.44 | 0.516 | 0.594 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00942 | 28.69 | 0.01272 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 26575.89 | 30562.28 | 64.07 | 2.032 | 2.336 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00958 | 30.10 | 0.01273 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 7545.53 | 8677.36 | 87.65 | 0.577 | 0.663 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00932 | 29.60 | 0.01272 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 31580.71 | 36317.82 | 76.14 | 2.414 | 2.776 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00941 | 30.10 | 0.01273 | 0.897 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 6377.81 | 7334.48 | 38.20 | 0.487 | 0.561 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 24.00 | 24.00 | 0.00886 | 29.73 | 0.01273 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 6821.25 | 7844.43 | 79.24 | 0.521 | 0.600 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 24.00 | 24.00 | 0.00941 | 28.69 | 0.01272 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 17936.37 | 20626.82 | 65.48 | 1.371 | 1.577 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00956 | 30.10 | 0.01273 | 0.592 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 9917.45 | 11405.07 | 70.40 | 0.758 | 0.872 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00948 | 30.10 | 0.01273 | 0.304 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 13604.36 | 15645.01 | 28.65 | 1.040 | 1.196 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00898 | 29.60 | 0.01272 | 0.166 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 8081.16 | 9293.34 | 54.35 | 0.618 | 0.710 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00905 | 30.10 | 0.01273 | 0.096 | 0.00 |
| MECH_ZN_1_FLR_1 | 9568.10 | 11003.32 | 43.66 | 0.731 | 0.841 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00859 | 30.10 | 0.01273 | 0.000 | 0.00 |
| BATH_ZN_1_FLR_1 | 6367.52 | 7322.65 | 38.54 | 0.487 | 0.560 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00889 | 28.53 | 0.01272 | 0.000 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 19539.46 | 22470.38 | 50.95 | 1.493 | 1.717 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00883 | 30.10 | 0.01273 | 0.190 | 0.00 |
| GYM_ZN_1_FLR_1 | 22619.50 | 26012.43 | 72.86 | 1.729 | 1.989 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 24.00 | 23.99 | 0.00961 | 30.10 | 0.01273 | 0.544 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 18277.25 | 21018.83 | 125.11 | 1.399 | 1.608 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.99 | 0.01053 | 28.98 | 0.01272 | 0.255 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 31276.22 | 35967.65 | 114.18 | 2.394 | 2.753 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 24.00 | 23.98 | 0.01082 | 29.48 | 0.01272 | 1.488 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 20520.38 | 23598.44 | 59.14 | 1.568 | 1.804 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 24.00 | 0.00900 | 30.10 | 0.01273 | 0.345 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 5856.07 | 7320.08 | 73.94 | 0.448 | 0.560 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00786 | -32.70 | 0.00018 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 18930.79 | 23663.49 | 49.61 | 1.448 | 1.810 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -32.70 | 0.00018 | 0.897 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 5364.42 | 6705.52 | 34.92 | 0.410 | 0.513 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00798 | -32.70 | 0.00018 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 5791.84 | 7239.80 | 73.13 | 0.443 | 0.554 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00786 | -32.70 | 0.00018 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 18594.64 | 23243.30 | 48.73 | 1.422 | 1.778 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -32.70 | 0.00018 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 5839.13 | 7298.92 | 73.73 | 0.447 | 0.558 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00786 | -32.70 | 0.00018 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 18774.75 | 23468.43 | 49.20 | 1.436 | 1.795 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -32.70 | 0.00018 | 0.897 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 5358.58 | 6698.22 | 34.89 | 0.410 | 0.512 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00798 | -32.70 | 0.00018 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 5793.40 | 7241.75 | 73.15 | 0.443 | 0.554 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00786 | -32.70 | 0.00018 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 18600.93 | 23251.17 | 48.74 | 1.423 | 1.778 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -32.70 | 0.00018 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 5841.07 | 7301.34 | 73.75 | 0.447 | 0.558 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00786 | -32.70 | 0.00018 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 18828.22 | 23535.27 | 49.34 | 1.440 | 1.800 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -32.70 | 0.00018 | 0.897 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 5365.64 | 6707.05 | 34.93 | 0.410 | 0.513 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00798 | -32.70 | 0.00018 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 5807.79 | 7259.74 | 73.33 | 0.444 | 0.555 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00786 | -32.70 | 0.00018 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 12557.74 | 15697.18 | 49.83 | 0.960 | 1.201 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -32.70 | 0.00018 | 0.592 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 6194.52 | 7743.15 | 47.80 | 0.474 | 0.592 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -32.70 | 0.00018 | 0.304 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 12908.96 | 16136.19 | 29.55 | 0.987 | 1.234 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00797 | -32.70 | 0.00018 | 0.166 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 7460.02 | 9325.02 | 54.53 | 0.571 | 0.713 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00790 | -32.70 | 0.00018 | 0.096 | 0.00 |
| MECH_ZN_1_FLR_1 | 4404.52 | 5505.65 | 21.85 | 0.337 | 0.421 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00800 | -32.70 | 0.00018 | 0.000 | 0.00 |
| BATH_ZN_1_FLR_1 | 5849.87 | 7312.34 | 38.49 | 0.447 | 0.559 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00793 | -32.70 | 0.00018 | 0.000 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 16564.56 | 20705.69 | 46.95 | 1.267 | 1.584 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00790 | -32.70 | 0.00018 | 0.190 | 0.00 |
| GYM_ZN_1_FLR_1 | 12416.64 | 15520.80 | 43.48 | 0.950 | 1.187 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00795 | -32.70 | 0.00018 | 0.544 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 1887.97 | 2359.96 | 14.05 | 0.144 | 0.255 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.01081 | -32.70 | 0.00018 | 0.255 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 13188.42 | 16485.53 | 52.34 | 1.009 | 1.488 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00789 | -32.70 | 0.00018 | 1.488 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 14796.57 | 18495.72 | 46.36 | 1.132 | 1.415 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -32.70 | 0.00018 | 0.345 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| VAV_POD_1 | 29.51 | 29.51 | 22.74 | 22.74 | 29.5130 | 22.7448 | 29.5130 | 0.7707 | 0.3000 |
| PSZ-AC_1:6 | 1.61 | 1.61 | 0.25 | 0.25 | 1.6084 | 1.6084 | 1.6084 | 1.0000 | 1.0000 |
| PSZ-AC_2:7 | 2.75 | 2.75 | 1.49 | 1.49 | 2.7529 | 2.7529 | 2.7529 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | 12661.842 | 12661.842 | 0.559864 | 0.00011077 | 295.332 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 12661.84 | 12661.84 | 0.559864 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00786499 | 48.7351 | 7320.08 | 0.00 | 12719.93 | 12719.93 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | 40933.298 | 40933.298 | 1.809903 | 0.00035810 | 954.755 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 40933.30 | 40933.30 | 1.809903 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00788899 | 48.8812 | 23663.49 | 0.00 | 41121.08 | 41121.08 |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX | 11600.309 | 11600.309 | 0.512884 | 0.00010148 | 270.578 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11600.31 | 11600.31 | 0.512884 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00797757 | 49.4225 | 6705.52 | 0.00 | 11653.52 | 11653.52 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | 12522.962 | 12522.962 | 0.553724 | 0.00010956 | 292.092 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 12522.96 | 12522.96 | 0.553724 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00786352 | 48.7261 | 7239.80 | 0.00 | 12580.41 | 12580.41 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | 40206.377 | 40206.377 | 1.777764 | 0.00035174 | 937.799 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 40206.38 | 40206.38 | 1.777764 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00788701 | 48.8691 | 23243.30 | 0.00 | 40390.82 | 40390.82 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | 12625.226 | 12625.226 | 0.558245 | 0.00011045 | 294.478 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 12625.23 | 12625.23 | 0.558245 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00786461 | 48.7327 | 7298.92 | 0.00 | 12683.14 | 12683.14 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | 40595.858 | 40595.858 | 1.794984 | 0.00035515 | 946.884 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 40595.86 | 40595.86 | 1.794984 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00788808 | 48.8757 | 23468.43 | 0.00 | 40782.09 | 40782.09 |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX | 11587.688 | 11587.688 | 0.512326 | 0.00010137 | 270.284 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11587.69 | 11587.69 | 0.512326 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00797755 | 49.4223 | 6698.22 | 0.00 | 11640.85 | 11640.85 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | 12526.340 | 12526.340 | 0.553873 | 0.00010959 | 292.171 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 12526.34 | 12526.34 | 0.553873 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00786356 | 48.7263 | 7241.75 | 0.00 | 12583.80 | 12583.80 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | 40219.996 | 40219.996 | 1.778366 | 0.00035186 | 938.117 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 40220.00 | 40220.00 | 1.778366 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00788705 | 48.8694 | 23251.17 | 0.00 | 40404.50 | 40404.50 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | 12629.415 | 12629.415 | 0.558430 | 0.00011049 | 294.575 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 12629.41 | 12629.41 | 0.558430 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00786465 | 48.7330 | 7301.34 | 0.00 | 12687.35 | 12687.35 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | 40711.490 | 40711.490 | 1.800096 | 0.00035616 | 949.581 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 40711.49 | 40711.49 | 1.800096 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00788839 | 48.8776 | 23535.27 | 0.00 | 40898.25 | 40898.25 |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX | 11602.962 | 11602.962 | 0.513001 | 0.00010151 | 270.640 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11602.96 | 11602.96 | 0.513001 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00797758 | 49.4225 | 6707.05 | 0.00 | 11656.19 | 11656.19 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | 12557.451 | 12557.451 | 0.555248 | 0.00010986 | 292.897 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 12557.45 | 12557.45 | 0.555248 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00786389 | 48.7283 | 7259.74 | 0.00 | 12615.06 | 12615.06 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | 27153.119 | 27153.119 | 1.200599 | 0.00023755 | 633.337 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 27153.12 | 27153.12 | 1.200599 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00788948 | 48.8842 | 15697.18 | 0.00 | 27277.68 | 27277.68 |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX | 13394.131 | 13394.131 | 0.592236 | 0.00011718 | 312.413 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 13394.13 | 13394.13 | 0.592236 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00788484 | 48.8559 | 7743.15 | 0.00 | 13455.58 | 13455.58 |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX | 27914.900 | 27914.900 | 1.234205 | 0.00024421 | 651.116 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 27914.90 | 27914.90 | 1.234205 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00797206 | 49.3888 | 16136.19 | 0.00 | 28042.96 | 28042.96 |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | LOBBY_ZN_1_FLR_1 VAV BOX | 16130.625 | 16130.625 | 0.713225 | 0.00014112 | 376.242 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 16130.62 | 16130.62 | 0.713225 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00789888 | 48.9418 | 9325.02 | 0.00 | 16204.62 | 16204.62 |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_ZN_1_FLR_1 VAV BOX | 9524.780 | 9524.780 | 0.421111 | 0.00008333 | 222.167 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 9524.78 | 9524.78 | 0.421111 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00800000 | 49.5595 | 5505.65 | 0.00 | 9568.47 | 9568.47 |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 12649.520 | 12649.520 | 0.559292 | 0.00011066 | 295.048 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12649.52 | 12649.52 | 0.559292 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00793184 | 49.1430 | 7312.34 | 0.00 | 12707.55 | 12707.55 |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | OFFICES_ZN_1_FLR_1 VAV BOX | 35817.275 | 35817.275 | 1.583681 | 0.00031335 | 835.427 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 35817.28 | 35817.28 | 1.583681 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00789933 | 48.9444 | 20705.69 | 0.00 | 35981.58 | 35981.58 |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 26849.527 | 26849.527 | 1.187125 | 0.00023489 | 626.263 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 26849.53 | 26849.53 | 1.187125 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00794531 | 49.2254 | 15520.80 | 0.00 | 26972.70 | 26972.70 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 31994.201 | 31994.201 | 1.414649 | 0.00027990 | 746.254 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 31994.20 | 31994.20 | 1.414649 | 12.89 | 11.26 | 0.00800000 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 0.0000 | 21.00 | 0.00789275 | 48.9042 | 18495.72 | 0.00 | 32140.97 | 32140.97 |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | VAV_POD_1 | 676031.310 | 491266.716 | 29.513027 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 680604.80 | 509635.67 | 29.513027 | 26.21 | 18.35 | 0.01054793 | 11.06 | 11.00 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 36.1986 | 24.00 | 0.00931226 | 47.9860 | 335720.59 | 0.00 | 677986.54 | 482410.24 |
| VAV_POD_1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | VAV_POD_1 | 468033.135 | 468033.135 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 468033.13 | 468033.13 | 8.853908 | -32.70 | -32.70 | 0.00018338 | 12.89 | 11.26 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 120.6620 | 21.00 | 0.00790262 | 48.9648 | 237814.53 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:6 | 34567.450 | 25897.242 | 1.608430 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 17283.72 | 12088.65 | 1.072287 | 24.75 | 18.14 | 0.01087483 | 11.48 | 11.18 | 0.00850000 | 28.98 | 0.01272390 | 20.81 | 23.7636 | 23.99 | 0.01052675 | 54.1732 | 18277.25 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_1:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:6 | 37306.959 | 37306.959 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 37306.96 | 37306.96 | 1.608425 | 12.11 | 11.87 | 0.00894437 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 15.8424 | 21.00 | 0.01059361 | 65.3495 | 1169.05 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:7 | 68361.530 | 47926.901 | 2.752920 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 34180.76 | 22544.48 | 1.835280 | 27.33 | 19.71 | 0.01188122 | 11.52 | 11.19 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 81.0876 | 23.98 | 0.01085777 | 55.8599 | 30861.15 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_2:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:7 | 128129.157 | 128129.157 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 128129.16 | 128129.16 | 2.752919 | -8.03 | -8.03 | 0.00372470 | 32.11 | 18.27 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 54.0584 | 21.00 | 0.00789169 | 48.8980 | 13186.78 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12661.842 | 12661.842 | 0.559864 | 0.00011077 | 295.332 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 2.4129 | 2.461433 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 12661.84 | 12661.84 | 1.0000 | 0.64604067 | 0.559864 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.11076002 | 60.00 | 32.22 | 27.78 | 0.000 | 12661.84 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00786499 | 21.00 | 0.00786499 | 48.7351 | 7320.08 | 0.00 | 12719.93 | 12719.93 | 0.64604067 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.9 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 40933.298 | 40933.298 | 1.809903 | 0.00035810 | 954.755 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 7.8004 | 7.957340 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 40933.30 | 40933.30 | 1.0000 | 2.08849196 | 1.809903 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.35806582 | 60.00 | 32.22 | 27.78 | 0.000 | 40933.30 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00788899 | 21.00 | 0.00788899 | 48.8812 | 23663.49 | 0.00 | 41121.08 | 41121.08 | 2.08849196 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.2 | |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX | CORRIDOR_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11600.309 | 11600.309 | 0.512884 | 0.00010148 | 270.578 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 2.2106 | 2.255074 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11600.31 | 11600.31 | 1.0000 | 0.59182941 | 0.512884 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.10147421 | 60.00 | 32.22 | 27.78 | 0.000 | 11600.31 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00797757 | 21.00 | 0.00797757 | 49.4225 | 6705.52 | 0.00 | 11653.52 | 11653.52 | 0.59182941 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.5 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12522.962 | 12522.962 | 0.553724 | 0.00010956 | 292.092 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 2.3864 | 2.434435 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 12522.96 | 12522.96 | 1.0000 | 0.63895535 | 0.553724 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.10954516 | 60.00 | 32.22 | 27.78 | 0.000 | 12522.96 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00786352 | 21.00 | 0.00786352 | 48.7261 | 7239.80 | 0.00 | 12580.41 | 12580.41 | 0.63895535 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.9 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 40206.377 | 40206.377 | 1.777764 | 0.00035174 | 937.799 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 7.6618 | 7.816029 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 40206.38 | 40206.38 | 1.0000 | 2.05140626 | 1.777764 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.35170705 | 60.00 | 32.22 | 27.78 | 0.000 | 40206.38 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00788701 | 21.00 | 0.00788701 | 48.8691 | 23243.30 | 0.00 | 40390.82 | 40390.82 | 2.05140626 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.2 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12625.226 | 12625.226 | 0.558245 | 0.00011045 | 294.478 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 2.4059 | 2.454315 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 12625.23 | 12625.23 | 1.0000 | 0.64417263 | 0.558245 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.11043972 | 60.00 | 32.22 | 27.78 | 0.000 | 12625.23 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00786461 | 21.00 | 0.00786461 | 48.7327 | 7298.92 | 0.00 | 12683.14 | 12683.14 | 0.64417263 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.9 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 40595.858 | 40595.858 | 1.794984 | 0.00035515 | 946.884 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 7.7361 | 7.891743 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 40595.86 | 40595.86 | 1.0000 | 2.07127661 | 1.794984 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.35511405 | 60.00 | 32.22 | 27.78 | 0.000 | 40595.86 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00788808 | 21.00 | 0.00788808 | 48.8757 | 23468.43 | 0.00 | 40782.09 | 40782.09 | 2.07127661 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.2 | |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX | CORRIDOR_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11587.688 | 11587.688 | 0.512326 | 0.00010137 | 270.284 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 2.2082 | 2.252620 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11587.69 | 11587.69 | 1.0000 | 0.59118549 | 0.512326 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.10136381 | 60.00 | 32.22 | 27.78 | 0.000 | 11587.69 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00797755 | 21.00 | 0.00797755 | 49.4223 | 6698.22 | 0.00 | 11640.85 | 11640.85 | 0.59118549 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.5 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12526.340 | 12526.340 | 0.553873 | 0.00010959 | 292.171 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 2.3871 | 2.435092 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 12526.34 | 12526.34 | 1.0000 | 0.63912767 | 0.553873 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.10957470 | 60.00 | 32.22 | 27.78 | 0.000 | 12526.34 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00786356 | 21.00 | 0.00786356 | 48.7263 | 7241.75 | 0.00 | 12583.80 | 12583.80 | 0.63912767 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.9 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 40219.996 | 40219.996 | 1.778366 | 0.00035186 | 938.117 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 7.6644 | 7.818676 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 40220.00 | 40220.00 | 1.0000 | 2.05210107 | 1.778366 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.35182618 | 60.00 | 32.22 | 27.78 | 0.000 | 40220.00 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00788705 | 21.00 | 0.00788705 | 48.8694 | 23251.17 | 0.00 | 40404.50 | 40404.50 | 2.05210107 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.2 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12629.415 | 12629.415 | 0.558430 | 0.00011049 | 294.575 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 2.4067 | 2.455130 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 12629.41 | 12629.41 | 1.0000 | 0.64438630 | 0.558430 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.11047636 | 60.00 | 32.22 | 27.78 | 0.000 | 12629.41 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00786465 | 21.00 | 0.00786465 | 48.7330 | 7301.34 | 0.00 | 12687.35 | 12687.35 | 0.64438630 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.9 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 40711.490 | 40711.490 | 1.800096 | 0.00035616 | 949.581 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 7.7581 | 7.914221 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 40711.49 | 40711.49 | 1.0000 | 2.07717585 | 1.800096 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.35612554 | 60.00 | 32.22 | 27.78 | 0.000 | 40711.49 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00788839 | 21.00 | 0.00788839 | 48.8776 | 23535.27 | 0.00 | 40898.25 | 40898.25 | 2.07717585 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.2 | |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX | CORRIDOR_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11602.962 | 11602.962 | 0.513001 | 0.00010151 | 270.640 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 2.2111 | 2.255590 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11602.96 | 11602.96 | 1.0000 | 0.59196475 | 0.513001 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.10149742 | 60.00 | 32.22 | 27.78 | 0.000 | 11602.96 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00797758 | 21.00 | 0.00797758 | 49.4225 | 6707.05 | 0.00 | 11656.19 | 11656.19 | 0.59196475 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.5 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12557.451 | 12557.451 | 0.555248 | 0.00010986 | 292.897 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 2.3930 | 2.441140 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 12557.45 | 12557.45 | 1.0000 | 0.64071491 | 0.555248 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.10984685 | 60.00 | 32.22 | 27.78 | 0.000 | 12557.45 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00786389 | 21.00 | 0.00786389 | 48.7283 | 7259.74 | 0.00 | 12615.06 | 12615.06 | 0.64071491 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.9 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27153.119 | 27153.119 | 1.200599 | 0.00023755 | 633.337 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 5.1744 | 5.278505 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 27153.12 | 27153.12 | 1.0000 | 1.38540145 | 1.200599 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.23752310 | 60.00 | 32.22 | 27.78 | 0.000 | 27153.12 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00788948 | 21.00 | 0.00788948 | 48.8842 | 15697.18 | 0.00 | 27277.68 | 27277.68 | 1.38540145 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.2 | |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX | COMPUTER_CLASS_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 13394.131 | 13394.131 | 0.592236 | 0.00011718 | 312.413 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 2.5524 | 2.603789 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 13394.13 | 13394.13 | 1.0000 | 0.68339537 | 0.592236 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.11716575 | 60.00 | 32.22 | 27.78 | 0.000 | 13394.13 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00788484 | 21.00 | 0.00788484 | 48.8559 | 7743.15 | 0.00 | 13455.58 | 13455.58 | 0.68339537 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.1 | |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX | MAIN_CORRIDOR_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 27914.900 | 27914.900 | 1.234205 | 0.00024421 | 651.116 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 5.3195 | 5.426593 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 27914.90 | 27914.90 | 1.0000 | 1.42417995 | 1.234205 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.24418681 | 60.00 | 32.22 | 27.78 | 0.000 | 27914.90 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00797206 | 21.00 | 0.00797206 | 49.3888 | 16136.19 | 0.00 | 28042.96 | 28042.96 | 1.42417995 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.4 | |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | LOBBY_ZN_1_FLR_1 VAV BOX | LOBBY_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16130.625 | 16130.625 | 0.713225 | 0.00014112 | 376.242 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 3.0739 | 3.135757 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 16130.62 | 16130.62 | 1.0000 | 0.82300784 | 0.713225 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.14110335 | 60.00 | 32.22 | 27.78 | 0.000 | 16130.62 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00789888 | 21.00 | 0.00789888 | 48.9418 | 9325.02 | 0.00 | 16204.62 | 16204.62 | 0.82300784 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.3 | |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_ZN_1_FLR_1 VAV BOX | MECH_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9524.780 | 9524.780 | 0.421111 | 0.00008333 | 222.167 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 1.8151 | 1.851596 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 9524.78 | 9524.78 | 1.0000 | 0.48593087 | 0.421111 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.08331843 | 60.00 | 32.22 | 27.78 | 0.000 | 9524.78 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 49.5595 | 5505.65 | 0.00 | 9568.47 | 9568.47 | 0.48593087 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.8 | |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BATH_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12649.520 | 12649.520 | 0.559292 | 0.00011066 | 295.048 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 2.4105 | 2.459038 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 12649.52 | 12649.52 | 1.0000 | 0.64538091 | 0.559292 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.11065223 | 60.00 | 32.22 | 27.78 | 0.000 | 12649.52 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00793184 | 21.00 | 0.00793184 | 49.1430 | 7312.34 | 0.00 | 12707.55 | 12707.55 | 0.64538091 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.8 | |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | OFFICES_ZN_1_FLR_1 VAV BOX | OFFICES_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35817.275 | 35817.275 | 1.583681 | 0.00031335 | 835.427 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 6.8254 | 6.962797 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 35817.28 | 35817.28 | 1.0000 | 1.82744882 | 1.583681 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.31331318 | 60.00 | 32.22 | 27.78 | 0.000 | 35817.28 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00789933 | 21.00 | 0.00789933 | 48.9444 | 20705.69 | 0.00 | 35981.58 | 35981.58 | 1.82744882 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.3 | |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | GYM_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 26849.527 | 26849.527 | 1.187125 | 0.00023489 | 626.263 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 5.1165 | 5.219487 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 26849.53 | 26849.53 | 1.0000 | 1.36985299 | 1.187125 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.23486741 | 60.00 | 32.22 | 27.78 | 0.000 | 26849.53 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00794531 | 21.00 | 0.00794531 | 49.2254 | 15520.80 | 0.00 | 26972.70 | 26972.70 | 1.36985299 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.0 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31994.201 | 31994.201 | 1.414649 | 0.00027990 | 746.254 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.49981782 | 54.44 | 82.22 | 27.78 | 524761.98 | 6.0969 | 6.219600 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 31994.20 | 31994.20 | 1.0000 | 1.63239826 | 1.414649 | 12.89 | 11.26 | 0.00800000 | 33150.5 | 32.11 | 18.27 | 0.00800000 | 52751.6 | 0.27987068 | 60.00 | 32.22 | 27.78 | 0.000 | 31994.20 | -32.70 | 0.00018338 | -32.70 | 0.00000000 | 0.0000 | 21.00 | 0.00789275 | 21.00 | 0.00789275 | 48.9042 | 18495.72 | 0.00 | 32140.97 | 32140.97 | 1.63239826 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.2 | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | VAV_POD_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1; MULT_CLASS_1_POD_1_ZN_1_FLR_1; CORRIDOR_POD_1_ZN_1_FLR_1; CORNER_CLASS_2_POD_1_ZN_1_FLR_1; MULT_CLASS_2_POD_1_ZN_1_FLR_1; CORNER_CLASS_1_POD_2_ZN_1_FLR_1; MULT_CLASS_1_POD_2_ZN_1_FLR_1; CORRIDOR_POD_2_ZN_1_FLR_1; CORNER_CLASS_2_POD_2_ZN_1_FLR_1; MULT_CLASS_2_POD_2_ZN_1_FLR_1; CORNER_CLASS_1_POD_3_ZN_1_FLR_1; MULT_CLASS_1_POD_3_ZN_1_FLR_1; CORRIDOR_POD_3_ZN_1_FLR_1; CORNER_CLASS_2_POD_3_ZN_1_FLR_1; MULT_CLASS_2_POD_3_ZN_1_FLR_1; COMPUTER_CLASS_ZN_1_FLR_1; MAIN_CORRIDOR_ZN_1_FLR_1; LOBBY_ZN_1_FLR_1; MECH_ZN_1_FLR_1; BATH_ZN_1_FLR_1; OFFICES_ZN_1_FLR_1; GYM_ZN_1_FLR_1; LIBRARY_MEDIA_CENTER_ZN_1_FLR_1; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 676031.310 | 491266.716 | 29.513027 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4481 | 1004.8586 | 1.1539 | VAV_POD_1 FAN | Fan:VariableVolume | 29.513027 | 34.05581542 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 680604.80 | 509635.67 | 1.0068 | 34.05581542 | 29.513027 | 26.21 | 18.35 | 0.01054793 | 53226.2 | 11.06 | 11.00 | 0.00850000 | 32551.2 | -999.0 | -999.00 | -999.00 | -999.00 | 63639.338 | 616965.46 | 30.10 | 0.01272586 | 21.13 | 10.68330000 | 36.1986 | 24.00 | 0.00931226 | 24.00 | 0.00931226 | 47.9860 | 335720.59 | 0.00 | 677986.54 | 482410.24 | 32.71086815 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.23 | 12.20 | 0.00884045 | 34595.7 | |
| VAV_POD_1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | VAV_POD_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1; MULT_CLASS_1_POD_1_ZN_1_FLR_1; CORRIDOR_POD_1_ZN_1_FLR_1; CORNER_CLASS_2_POD_1_ZN_1_FLR_1; MULT_CLASS_2_POD_1_ZN_1_FLR_1; CORNER_CLASS_1_POD_2_ZN_1_FLR_1; MULT_CLASS_1_POD_2_ZN_1_FLR_1; CORRIDOR_POD_2_ZN_1_FLR_1; CORNER_CLASS_2_POD_2_ZN_1_FLR_1; MULT_CLASS_2_POD_2_ZN_1_FLR_1; CORNER_CLASS_1_POD_3_ZN_1_FLR_1; MULT_CLASS_1_POD_3_ZN_1_FLR_1; CORRIDOR_POD_3_ZN_1_FLR_1; CORNER_CLASS_2_POD_3_ZN_1_FLR_1; MULT_CLASS_2_POD_3_ZN_1_FLR_1; COMPUTER_CLASS_ZN_1_FLR_1; MAIN_CORRIDOR_ZN_1_FLR_1; LOBBY_ZN_1_FLR_1; MECH_ZN_1_FLR_1; BATH_ZN_1_FLR_1; OFFICES_ZN_1_FLR_1; GYM_ZN_1_FLR_1; LIBRARY_MEDIA_CENTER_ZN_1_FLR_1; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 468033.135 | 468033.135 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | VAV_POD_1 FAN | Fan:VariableVolume | 29.513027 | 34.05581542 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 468033.13 | 468033.13 | 1.0000 | 10.21674463 | 8.853908 | -32.70 | -32.70 | 0.00018338 | -32410.8 | 12.89 | 11.26 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 468033.13 | -32.70 | 0.00018338 | -32.70 | 10.68330000 | 120.6620 | 21.00 | 0.00790262 | 21.00 | 0.00790262 | 48.9648 | 237814.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:6 | KITCHEN_ZN_1_FLR_1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34567.450 | 25897.242 | 1.608430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1025.0558 | 1004.8586 | 1.1539 | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.608425 | 1.85600199 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 17283.72 | 12088.65 | 1.0000 | 1.23733824 | 1.072287 | 24.75 | 18.14 | 0.01087483 | 52563.2 | 11.48 | 11.18 | 0.00850000 | 32978.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17283.72 | 28.98 | 0.01272390 | 20.81 | 0.25481392 | 23.7636 | 23.95 | 0.01052675 | 23.99 | 0.01052675 | 54.1732 | 18277.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_1:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:6 | KITCHEN_ZN_1_FLR_1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37306.959 | 37306.959 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.608425 | 1.85600199 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 37306.96 | 37306.96 | 1.0000 | 1.85600199 | 1.608425 | 12.11 | 11.87 | 0.00894437 | 34735.7 | 32.11 | 18.27 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37306.96 | -32.70 | 0.00018338 | -32.70 | 0.25481392 | 15.8424 | 20.54 | 0.01059361 | 21.00 | 0.01059361 | 65.3495 | 1169.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:7 | CAFETERIA_ZN_1_FLR_1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 68361.530 | 47926.901 | 2.752920 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.9266 | 1004.8586 | 1.1539 | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.752919 | 3.17666127 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 34180.76 | 22544.48 | 1.0000 | 2.11777521 | 1.835280 | 27.33 | 19.71 | 0.01188122 | 57784.3 | 11.52 | 11.19 | 0.00850000 | 33015.8 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34180.76 | 30.10 | 0.01272586 | 21.13 | 1.48818443 | 81.0876 | 23.98 | 0.01085777 | 23.98 | 0.01085777 | 55.8599 | 30861.15 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_2:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:7 | CAFETERIA_ZN_1_FLR_1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 128129.157 | 128129.157 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.752919 | 3.17666127 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 128129.16 | 128129.16 | 1.0000 | 3.17666127 | 2.752919 | -8.03 | -8.03 | 0.00372470 | 1191.3 | 32.11 | 18.27 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 128129.16 | -32.70 | 0.00018338 | -32.70 | 1.48818443 | 54.0584 | 21.00 | 0.00789169 | 21.00 | 0.00789169 | 48.8980 | 13186.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| VAV_POD_1_OA_CONTROLLER | FixedDryBulb | 0.00 | 29.51 | - | |||
| PSZ-AC_1:6_OA_CONTROLLER | FixedDryBulb | 0.25 | 1.61 | - | |||
| PSZ-AC_2:7_OA_CONTROLLER | FixedDryBulb | 1.49 | 2.75 | - |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| LOBBY_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000559 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MECH_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| BATH_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| OFFICES_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| GYM_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001524 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000864 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1864.67 | 2504.00 | 1342.67 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1610.83 | 2509.17 | 1171.17 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 1692.00 | 2680.67 | 1451.50 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1776.50 | 2888.00 | 1555.67 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1592.50 | 2988.17 | 1441.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1844.17 | 2538.83 | 1356.33 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1572.17 | 2562.67 | 1187.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 1681.00 | 2708.67 | 1456.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1776.33 | 2889.17 | 1555.33 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1594.17 | 2987.17 | 1440.83 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1858.00 | 2518.33 | 1350.83 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1592.17 | 2521.00 | 1174.33 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 1733.33 | 2571.67 | 1430.33 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1799.33 | 2819.33 | 1539.83 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1608.17 | 2920.83 | 1423.33 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 1833.17 | 2262.83 | 1236.83 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 2087.50 | 2280.33 | 1500.33 |
| LOBBY_ZN_1_FLR_1 | 2160.67 | 2819.50 | 1858.67 |
| MECH_ZN_1_FLR_1 | 2464.33 | 1878.50 | 1242.17 |
| BATH_ZN_1_FLR_1 | 2455.50 | 2194.17 | 1580.00 |
| OFFICES_ZN_1_FLR_1 | 1899.50 | 1779.33 | 1177.33 |
| GYM_ZN_1_FLR_1 | 2194.33 | 1893.67 | 1127.83 |
| KITCHEN_ZN_1_FLR_1 | 2329.67 | 953.67 | 357.67 |
| CAFETERIA_ZN_1_FLR_1 | 1807.50 | 1893.00 | 1119.67 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 2176.67 | 2035.50 | 1290.67 |
| Facility | 3219.33 | 3202.00 | 2086.17 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 232.67 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 84.50 | 0.17 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 147.83 | 0.00 | 41.17 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 304.17 | 0.00 | 0.17 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 128.50 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 236.33 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 88.67 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 153.33 | 0.00 | 44.33 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 304.17 | 0.00 | 0.17 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 128.67 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 235.33 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 87.67 | 0.17 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 145.83 | 0.00 | 41.17 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 301.67 | 0.00 | 0.17 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 134.33 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 109.17 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 196.17 | 0.00 | 94.17 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 1787.50 | 23.00 | 1279.67 | 23.00 |
| MECH_ZN_1_FLR_1 | 0.00 | 1.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 127.33 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 188.33 | 1.00 | 4.17 | 0.00 |
| GYM_ZN_1_FLR_1 | 105.33 | 1.17 | 0.17 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 4.67 | 551.83 | 0.00 | 0.33 |
| CAFETERIA_ZN_1_FLR_1 | 210.33 | 8.00 | 0.00 | 4.67 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 112.67 | 0.00 | 0.17 | 0.00 |
| Facility | 2000.50 | 584.67 | 1279.67 | 28.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.992 | 0.028 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.977 | 0.015 | 0.000 | 0.000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.646 | 0.002 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.922 | 0.028 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.919 | 0.015 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.983 | 0.028 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.968 | 0.015 | 0.000 | 0.000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.642 | 0.002 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.924 | 0.028 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.918 | 0.015 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.989 | 0.028 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.975 | 0.015 | 0.000 | 0.000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.662 | 0.002 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.927 | 0.028 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 45.65 | 84.77 | 1260.00 | 1.925 | 0.015 | 0.000 | 0.000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 38.16 | 43.60 | 648.00 | 2.049 | 0.015 | 0.000 | 0.000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 15.83 | 29.39 | 2184.00 | 0.586 | 0.002 | 0.000 | 0.000 |
| LOBBY_ZN_1_FLR_1 | 9.91 | 18.41 | 684.00 | 1.145 | 2.787 | 0.000 | 0.000 |
| MECH_ZN_1_FLR_1 | 2.19 | 4.07 | 1008.00 | 0.702 | 0.000 | 0.000 | 0.000 |
| BATH_ZN_1_FLR_1 | 5.51 | 10.23 | 760.00 | 0.601 | 0.007 | 0.000 | 0.000 |
| OFFICES_ZN_1_FLR_1 | 14.92 | 23.74 | 1764.00 | 1.052 | 0.013 | 0.000 | 0.000 |
| GYM_ZN_1_FLR_1 | 64.64 | 115.31 | 1428.00 | 1.851 | 0.007 | 0.000 | 0.000 |
| KITCHEN_ZN_1_FLR_1 | 14.54 | 26.99 | 672.00 | 3.943 | 0.007 | 0.000 | 0.000 |
| CAFETERIA_ZN_1_FLR_1 | 209.95 | 339.07 | 1260.00 | 5.062 | 0.016 | 0.000 | 0.000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 23.13 | 42.95 | 1596.00 | 1.236 | 0.014 | 0.000 | 0.000 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.488 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.330 | 0.000 | 0.000 | 0.000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.481 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.330 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.185 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.439 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.330 | 0.000 | 0.000 | 0.000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.478 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.331 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.188 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.456 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.330 | 0.000 | 0.000 | 0.000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.484 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.330 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 45.65 | 84.77 | 1260.00 | 1.233 | 0.000 | 0.000 | 0.000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 38.16 | 43.60 | 648.00 | 1.442 | 0.000 | 0.000 | 0.000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 15.83 | 29.39 | 2184.00 | 0.384 | 0.000 | 0.000 | 0.000 |
| LOBBY_ZN_1_FLR_1 | 9.91 | 18.41 | 684.00 | 0.544 | 0.000 | 0.000 | 0.000 |
| MECH_ZN_1_FLR_1 | 2.19 | 4.07 | 1008.00 | 0.524 | 0.000 | 0.000 | 0.000 |
| BATH_ZN_1_FLR_1 | 5.51 | 10.23 | 760.00 | 0.306 | 0.000 | 0.000 | 0.000 |
| OFFICES_ZN_1_FLR_1 | 14.92 | 23.74 | 1764.00 | 0.663 | 0.000 | 0.000 | 0.000 |
| GYM_ZN_1_FLR_1 | 64.64 | 115.31 | 1428.00 | 1.226 | 0.000 | 0.000 | 0.000 |
| KITCHEN_ZN_1_FLR_1 | 14.54 | 26.99 | 672.00 | 0.000 | 0.000 | 0.000 | 0.000 |
| CAFETERIA_ZN_1_FLR_1 | 209.95 | 339.07 | 1260.00 | 4.148 | 0.000 | 0.000 | 0.000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 23.13 | 42.95 | 1596.00 | 0.752 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 5.56 | 10.33 | 768.00 | 192.00 | 0.0000 | 0.059 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 5.56 | 10.33 | 768.00 | 192.00 | 0.0000 | 0.059 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 5.56 | 10.33 | 768.00 | 192.00 | 0.0000 | 0.059 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 45.65 | 84.77 | 1260.00 | 315.00 | 0.0000 | 0.592 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | 38.16 | 43.60 | 648.00 | 162.00 | 0.0000 | 0.304 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | 15.83 | 29.39 | 2184.00 | 546.00 | 0.0000 | 0.166 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | 9.91 | 18.41 | 684.00 | 171.00 | 0.0000 | 0.096 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | 2.19 | 4.07 | 1008.00 | 252.00 | 0.0000 | 0.000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | 5.51 | 10.23 | 760.00 | 190.00 | 0.0000 | 0.000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | 14.92 | 23.74 | 1764.00 | 441.00 | 0.0000 | 0.190 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | 64.64 | 115.31 | 1428.00 | 357.00 | 0.0000 | 0.544 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | 14.54 | 26.99 | 672.00 | 168.00 | 0.4528 | 0.198 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | 209.95 | 339.07 | 1260.00 | 315.00 | 1.4882 | 1.488 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | 23.13 | 42.95 | 1596.00 | 399.00 | 0.0000 | 0.345 |
| Total Facility | 892.82 | 1571.19 | 27484.00 | 6871.00 | 1.9410 | 9.699 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 2970218.62 | 0.00 | 2970218.62 | 227978.09 | 3198196.71 | 5868225.25 | 7127.89 | 142.50 | 1489.60 | 1802.84 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 14212885.54 | 0.00 | 14212885.54 | 604141.93 | 14817027.47 | 28274176.21 | 7206.18 | 135.93 | 1417.89 | 1802.84 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 1863002.66 | 0.00 | 1863002.66 | 34196.71 | 1897199.37 | 1845537.18 | 5163.04 | 0.77 | 3596.18 | 1802.84 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 2884364.72 | 0.00 | 2884364.72 | 227978.09 | 3112342.81 | 5868225.25 | 7269.20 | 142.24 | 1348.56 | 1802.84 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 13881196.92 | 0.00 | 13881196.92 | 604141.93 | 14485338.85 | 28274176.21 | 7287.08 | 141.85 | 1331.07 | 1802.84 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 2958331.69 | 0.00 | 2958331.69 | 227978.09 | 3186309.77 | 5868225.25 | 7145.16 | 145.49 | 1469.35 | 1802.84 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 14161107.78 | 0.00 | 14161107.78 | 604141.93 | 14765249.71 | 28274176.21 | 7218.39 | 143.59 | 1398.03 | 1802.84 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 1852269.15 | 0.00 | 1852269.15 | 34196.71 | 1886465.86 | 1845537.18 | 5162.89 | 0.92 | 3596.18 | 1802.84 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 2886583.89 | 0.00 | 2886583.89 | 227978.09 | 3114561.97 | 5868225.25 | 7257.42 | 152.30 | 1350.28 | 1802.84 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 13869594.33 | 0.00 | 13869594.33 | 604141.93 | 14473736.25 | 28274176.21 | 7299.68 | 130.23 | 1330.09 | 1802.84 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 2966517.86 | 0.00 | 2966517.86 | 227978.09 | 3194495.95 | 5868225.25 | 7119.56 | 158.57 | 1481.87 | 1802.84 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 14202653.70 | 0.00 | 14202653.70 | 604141.93 | 14806795.63 | 28274176.21 | 7203.64 | 145.28 | 1411.08 | 1802.84 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 1902890.06 | 0.00 | 1902890.06 | 34196.71 | 1937086.77 | 1845537.18 | 5163.21 | 0.77 | 3596.02 | 1802.84 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 2890542.11 | 0.00 | 2890542.11 | 227978.09 | 3118520.20 | 5868225.25 | 7253.88 | 147.79 | 1358.33 | 1802.84 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 9186230.18 | 0.00 | 9186230.18 | 398961.65 | 9585191.83 | 18671625.80 | 7290.64 | 134.45 | 1334.91 | 1802.84 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 4968644.75 | 0.00 | 4968644.75 | 205180.28 | 5173825.02 | 9602550.41 | 7125.13 | 140.00 | 1494.87 | 1802.84 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 4701791.78 | 0.00 | 4701791.78 | 102590.14 | 4804381.92 | 5248246.35 | 5184.14 | 2.08 | 3573.78 | 1802.84 |
| LOBBY_ZN_1_FLR_1 | 2936758.60 | 0.00 | 2936758.60 | 9418735.69 | 12355494.29 | 3013410.78 | 5151.44 | 1.52 | 3607.04 | 1802.84 |
| MECH_ZN_1_FLR_1 | 2675692.84 | 0.00 | 2675692.84 | 0.00 | 2675692.84 | 0.00 | 0.00 | 0.00 | 5078.84 | 1802.84 |
| BATH_ZN_1_FLR_1 | 1737247.94 | 0.00 | 1737247.94 | 113989.04 | 1851236.98 | 0.00 | 0.00 | 0.00 | 5078.84 | 1802.84 |
| OFFICES_ZN_1_FLR_1 | 6349505.96 | 0.00 | 6349505.96 | 478753.98 | 6828259.94 | 6005204.96 | 5451.67 | 2.70 | 3305.63 | 2041.34 |
| GYM_ZN_1_FLR_1 | 9759328.75 | 0.00 | 9759328.75 | 193781.37 | 9953110.13 | 17157717.19 | 6900.27 | 127.40 | 1732.33 | 1802.84 |
| KITCHEN_ZN_1_FLR_1 | 11034309.01 | 0.00 | 11034309.01 | 91191.23 | 11125500.25 | 6482703.52 | 4654.65 | 16.91 | 4088.45 | 1997.86 |
| CAFETERIA_ZN_1_FLR_1 | 21789105.05 | 0.00 | 21789105.05 | 410360.56 | 22199465.61 | 46931384.03 | 5473.42 | 2515.62 | 770.96 | 1325.97 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 7178052.48 | 0.00 | 7178052.48 | 455956.17 | 7634008.66 | 10866548.77 | 5237.22 | 144.63 | 3378.15 | 1802.84 |
| Total Facility | 0.18E+09 | 0.00 | 0.18E+09 | 16360668.43 | 0.19E+09 | 0.31E+09 | 7691.06 | 2543.02 | 5808.87 | 4304.54 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.2158 | 0.0000 | 0.2158 | 0.0030 | 0.2188 | 0.1861 | 1904.84 | 140.27 | 1230.89 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.0316 | 0.0000 | 1.0316 | 0.0080 | 1.0396 | 0.8966 | 1983.13 | 133.74 | 1159.14 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 0.1358 | 0.0000 | 0.1358 | 0.0005 | 0.1363 | 0.0585 | 0.00 | 0.00 | 3276.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.2085 | 0.0000 | 0.2085 | 0.0030 | 0.2116 | 0.1861 | 2046.15 | 140.05 | 1089.81 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.0034 | 0.0000 | 1.0034 | 0.0080 | 1.0115 | 0.8966 | 2064.02 | 139.70 | 1072.28 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.2148 | 0.0000 | 0.2148 | 0.0030 | 0.2178 | 0.1861 | 1922.14 | 143.24 | 1210.62 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.0272 | 0.0000 | 1.0272 | 0.0080 | 1.0352 | 0.8966 | 1995.33 | 141.39 | 1139.28 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 0.1350 | 0.0000 | 0.1350 | 0.0005 | 0.1354 | 0.0585 | 0.00 | 0.00 | 3276.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.2087 | 0.0000 | 0.2087 | 0.0030 | 0.2117 | 0.1861 | 2034.58 | 149.92 | 1091.49 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.0026 | 0.0000 | 1.0026 | 0.0080 | 1.0106 | 0.8966 | 2076.59 | 127.81 | 1071.60 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.2154 | 0.0000 | 0.2154 | 0.0030 | 0.2185 | 0.1861 | 1896.76 | 156.28 | 1222.97 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.0306 | 0.0000 | 1.0306 | 0.0080 | 1.0387 | 0.8966 | 1980.58 | 143.12 | 1152.29 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 0.1390 | 0.0000 | 0.1390 | 0.0005 | 0.1395 | 0.0585 | 0.00 | 0.00 | 3276.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.2090 | 0.0000 | 0.2090 | 0.0030 | 0.2121 | 0.1861 | 2030.82 | 145.60 | 1099.58 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.6643 | 0.0000 | 0.6643 | 0.0053 | 0.6696 | 0.5921 | 2067.59 | 132.25 | 1076.16 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 0.3624 | 0.0000 | 0.3624 | 0.0027 | 0.3651 | 0.3045 | 1902.07 | 137.81 | 1236.12 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 0.3495 | 0.0000 | 0.3495 | 0.0014 | 0.3509 | 0.1664 | 0.00 | 0.00 | 3276.00 |
| LOBBY_ZN_1_FLR_1 | 0.2171 | 0.0000 | 0.2171 | 0.5339 | 0.7509 | 0.0956 | 0.00 | 0.00 | 3276.00 |
| MECH_ZN_1_FLR_1 | 0.1928 | 0.0000 | 0.1928 | 0.0000 | 0.1928 | 0.0000 | 0.00 | 0.00 | 3276.00 |
| BATH_ZN_1_FLR_1 | 0.1253 | 0.0000 | 0.1253 | 0.0015 | 0.1268 | 0.0000 | 0.00 | 0.00 | 3276.00 |
| OFFICES_ZN_1_FLR_1 | 0.5064 | 0.0000 | 0.5064 | 0.0063 | 0.5127 | 0.1904 | 0.00 | 0.00 | 2772.00 |
| GYM_ZN_1_FLR_1 | 0.7207 | 0.0000 | 0.7207 | 0.0026 | 0.7232 | 0.5441 | 1677.41 | 124.98 | 1473.61 |
| KITCHEN_ZN_1_FLR_1 | 0.7173 | 0.0000 | 0.7173 | 0.0012 | 0.7185 | 0.2182 | 212.59 | 4.56 | 3058.85 |
| CAFETERIA_ZN_1_FLR_1 | 1.7412 | 0.0000 | 1.7412 | 0.0056 | 1.7469 | 1.4882 | 0.00 | 2038.26 | 689.74 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.5377 | 0.0000 | 0.5377 | 0.0061 | 0.5438 | 0.3446 | 18.87 | 142.83 | 3114.29 |
| Total Facility | 12.9123 | 0.0000 | 12.9123 | 0.6262 | 13.5385 | 9.7189 | 2215.69 | 2518.98 | 3276.00 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| VAV_POD_1 | 0.19E+09 | 0.00 | 0.19E+09 | 0.25E+09 | 5187.80 | 1.44 | 3570.76 | 1802.84 |
| PSZ-AC_1:6 | 14692652.23 | 0.00 | 14692652.23 | 6482703.52 | 4470.21 | 14.86 | 4274.93 | 1997.79 |
| PSZ-AC_2:7 | 29013119.41 | 0.00 | 29013119.41 | 46931384.03 | 5369.13 | 5.44 | 3385.43 | 1325.97 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| VAV_POD_1 | 13.8714 | 0.0000 | 13.8714 | 8.0125 | 0.00 | 0.00 | 3276.00 |
| PSZ-AC_1:6 | 0.9552 | 0.0000 | 0.9552 | 0.2182 | 181.63 | 3.18 | 3091.19 |
| PSZ-AC_2:7 | 2.3185 | 0.0000 | 2.3185 | 1.4882 | 0.00 | 0.00 | 2728.00 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| VAV_POD_1 | 0.00 | 49.06 | 2539.08 | 1158.49 | 0.00 | 0.00 | 1332.20 | 0.00 | 0.00 | 0.00 |
| PSZ-AC_1:6 | 0.00 | 819.51 | 3239.64 | 1161.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| PSZ-AC_2:7 | 0.00 | 2511.87 | 889.55 | 652.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| VAV_POD_1 | 0.0000 | 14.1052 | 15.3571 | 0.0000 | 0.0000 | 0.0000 | 11.7607 | 0.0000 | 0.0000 | 0.0000 |
| PSZ-AC_1:6 | 0.0000 | 0.3395 | 1.1865 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| PSZ-AC_2:7 | 0.0000 | 1.9824 | 3.3104 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Surfaces by Class| Total | Outdoors | |
| Wall | 121 | 33 |
| Floor | 25 | 24 |
| Roof | 25 | 25 |
| Internal Mass | 25 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 67 | 67 |
| Door | 25 | 25 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 3 |
| Conditioned Zones | 25 |
| Unconditioned Zones | 0 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1159 |
| Defaulted Fields | 890 |
| Fields with Defaults | 3720 |
| Autosized Fields | 267 |
| Autosizable Fields | 376 |
| Autocalculated Fields | 317 |
| Autocalculatable Fields | 632 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 3174.52 | 37055.58 | 09-JUL-10:30 | 377479.23 | 29-JUN-16:00 |
| Electricity:Building | 2377.40 | 35841.46 | 01-JUL-10:30 | 158543.84 | 02-JAN-11:10 |
| Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| Electricity:SpaceType:GENERAL | 2369.55 | 35741.12 | 30-JUN-23:10 | 156371.25 | 02-JAN-10:10 |
| InteriorLights:Electricity | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 24.39 | 336.28 | 30-JUN-23:10 | 1626.10 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 24.39 | 336.28 | 30-JUN-23:10 | 1626.10 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 24.39 | 336.28 | 30-JUN-23:10 | 1626.10 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 126.22 | 1762.63 | 30-JUN-23:10 | 8449.51 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 65.42 | 841.62 | 01-JAN-00:10 | 4272.19 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 65.42 | 841.62 | 01-JAN-00:10 | 4272.19 | 02-JAN-07:10 |
| Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 75.34 | 1064.38 | 30-JUN-23:10 | 5061.57 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 33.64 | 432.83 | 01-JAN-00:10 | 2197.13 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 33.64 | 432.83 | 01-JAN-00:10 | 2197.13 | 02-JAN-07:10 |
| Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 69.34 | 956.30 | 30-JUN-23:10 | 4624.21 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 41.24 | 530.59 | 01-JAN-00:10 | 2693.36 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 41.24 | 530.59 | 01-JAN-00:10 | 2693.36 | 02-JAN-07:10 |
| Electricity:Zone:LOBBY_ZN_1_FLR_1 | 41.78 | 557.57 | 30-JUN-23:10 | 2758.25 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 32.98 | 424.25 | 01-JAN-00:10 | 2153.53 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 32.98 | 424.25 | 01-JAN-00:10 | 2153.53 | 02-JAN-07:10 |
| Electricity:Zone:MECH_ZN_1_FLR_1 | 88.50 | 1212.59 | 30-JUN-23:10 | 5889.78 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MECH_ZN_1_FLR_1 | 56.07 | 721.39 | 01-JAN-00:10 | 3661.88 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MECH_ZN_1_FLR_1 | 56.07 | 721.39 | 01-JAN-00:10 | 3661.88 | 02-JAN-07:10 |
| Electricity:Zone:BATH_ZN_1_FLR_1 | 35.15 | 474.48 | 30-JUN-23:10 | 2328.47 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:BATH_ZN_1_FLR_1 | 25.37 | 326.34 | 01-JAN-00:10 | 1656.56 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:BATH_ZN_1_FLR_1 | 25.37 | 326.34 | 01-JAN-00:10 | 1656.56 | 02-JAN-07:10 |
| Electricity:Zone:OFFICES_ZN_1_FLR_1 | 133.25 | 1854.16 | 30-JUN-23:10 | 8910.14 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 71.96 | 925.78 | 01-JAN-00:10 | 4699.41 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 71.96 | 925.78 | 01-JAN-00:10 | 4699.41 | 02-JAN-07:10 |
| Electricity:Zone:GYM_ZN_1_FLR_1 | 88.64 | 1192.76 | 30-JUN-23:10 | 5866.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:GYM_ZN_1_FLR_1 | 65.67 | 844.83 | 01-JAN-00:10 | 4288.47 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:GYM_ZN_1_FLR_1 | 65.67 | 844.83 | 01-JAN-00:10 | 4288.47 | 02-JAN-07:10 |
| Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 211.64 | 5400.64 | 01-JAN-11:30 | 13840.49 | 02-JAN-11:10 |
| InteriorLights:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 29.90 | 384.74 | 01-JAN-00:10 | 1953.00 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 29.90 | 384.74 | 01-JAN-00:10 | 1953.00 | 02-JAN-07:10 |
| Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 71.99 | 1340.83 | 01-JAN-00:10 | 4745.87 | 02-JAN-10:10 |
| InteriorLights:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 42.05 | 541.04 | 01-JAN-00:10 | 2746.41 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 42.05 | 541.04 | 01-JAN-00:10 | 2746.41 | 02-JAN-07:10 |
| Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 168.75 | 2346.88 | 30-JUN-23:10 | 11282.50 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 91.74 | 1180.27 | 01-JAN-00:10 | 5991.24 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 91.74 | 1180.27 | 01-JAN-00:10 | 5991.24 | 02-JAN-07:10 |
| InteriorEquipment:Electricity | 1151.36 | 20068.34 | 30-JUN-23:10 | 76813.98 | 02-JAN-10:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 1151.36 | 20068.34 | 30-JUN-23:10 | 76813.98 | 02-JAN-10:10 |
| MiscPlug:InteriorEquipment:Electricity | 947.54 | 14352.99 | 30-JUN-23:10 | 65099.62 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 947.54 | 14352.99 | 30-JUN-23:10 | 65099.62 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 60.80 | 921.00 | 30-JUN-23:10 | 4177.31 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 60.80 | 921.00 | 30-JUN-23:10 | 4177.31 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 41.69 | 631.55 | 30-JUN-23:10 | 2864.44 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 41.69 | 631.55 | 30-JUN-23:10 | 2864.44 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 28.10 | 425.71 | 30-JUN-23:10 | 1930.85 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 28.10 | 425.71 | 30-JUN-23:10 | 1930.85 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 8.80 | 133.33 | 30-JUN-23:10 | 604.72 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 8.80 | 133.33 | 30-JUN-23:10 | 604.72 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MECH_ZN_1_FLR_1 | 32.43 | 491.20 | 30-JUN-23:10 | 2227.90 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MECH_ZN_1_FLR_1 | 32.43 | 491.20 | 30-JUN-23:10 | 2227.90 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:BATH_ZN_1_FLR_1 | 9.78 | 148.14 | 30-JUN-23:10 | 671.91 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:BATH_ZN_1_FLR_1 | 9.78 | 148.14 | 30-JUN-23:10 | 671.91 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 61.29 | 928.37 | 30-JUN-23:10 | 4210.73 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 61.29 | 928.37 | 30-JUN-23:10 | 4210.73 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GYM_ZN_1_FLR_1 | 22.97 | 347.93 | 30-JUN-23:10 | 1578.10 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GYM_ZN_1_FLR_1 | 22.97 | 347.93 | 30-JUN-23:10 | 1578.10 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 173.88 | 4915.56 | 01-JAN-00:10 | 9714.90 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity | 149.71 | 3999.34 | 01-JAN-00:10 | 9998.36 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 119.77 | 3199.56 | 01-JAN-00:10 | 7998.90 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 149.71 | 3999.34 | 01-JAN-00:10 | 9998.36 | 02-JAN-10:10 |
| ReachInFreezer:InteriorEquipment:Electricity | 31.09 | 986.00 | 01-JAN-00:10 | 986.00 | 01-JAN-00:10 |
| ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 31.09 | 986.00 | 01-JAN-00:10 | 986.00 | 01-JAN-00:10 |
| ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 31.09 | 986.00 | 01-JAN-00:10 | 986.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 29.94 | 799.79 | 01-JAN-00:10 | 1999.46 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 29.94 | 799.79 | 01-JAN-00:10 | 1999.46 | 02-JAN-10:10 |
| InteriorEquipment:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 77.02 | 1166.60 | 30-JUN-23:10 | 5291.26 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 77.02 | 1166.60 | 30-JUN-23:10 | 5291.26 | 02-JAN-08:10 |
| Refrigeration:Electricity | 44.41 | 704.13 | 01-JAN-23:30 | 2907.46 | 10-APR-10:10 |
| Refrigeration:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 7.85 | 100.34 | 01-JAN-11:30 | 2172.58 | 02-JAN-11:10 |
| General:Refrigeration:Electricity | 7.85 | 100.34 | 01-JAN-11:30 | 2172.58 | 02-JAN-11:10 |
| General:Refrigeration:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 7.85 | 100.34 | 01-JAN-11:30 | 2172.58 | 02-JAN-11:10 |
| Electricity:Plant | 40.64 | 560.96 | 09-JAN-07:00 | 2789.40 | 23-JAN-11:50 |
| LowTempRefrigeration:Refrigeration:Electricity | 14.74 | 0.00 | 01-JAN-11:10 | 1475.93 | 20-AUG-10:50 |
| MedTempRefrigeration:Refrigeration:Electricity | 21.82 | 385.61 | 09-JAN-07:00 | 734.88 | 03-JAN-07:30 |
| Electricity:HVAC | 664.03 | 321.20 | 01-JUL-18:10 | 225749.79 | 29-JUN-16:00 |
| ExteriorEquipment:Electricity | 17.61 | 321.20 | 30-JUN-24:00 | 1336.02 | 02-JAN-10:10 |
| Transformer:ExteriorEquipment:Electricity | 17.61 | 321.20 | 30-JUN-24:00 | 1336.02 | 02-JAN-10:10 |
| ElectricityPurchased:Facility | 3174.52 | 37055.58 | 09-JUL-10:30 | 377479.23 | 29-JUN-16:00 |
| ElectricityPurchased:Plant | 3174.52 | 37055.58 | 09-JUL-10:30 | 377479.23 | 29-JUN-16:00 |
| Cogeneration:ElectricityPurchased | 3174.52 | 37055.58 | 09-JUL-10:30 | 377479.23 | 29-JUN-16:00 |
| General:Cogeneration:ElectricityPurchased | 3174.52 | 37055.58 | 09-JUL-10:30 | 377479.23 | 29-JUN-16:00 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 3174.52 | 37055.58 | 09-JUL-10:30 | 377479.23 | 29-JUN-16:00 |
| ElectricityNet:Plant | 3174.52 | 37055.58 | 09-JUL-10:30 | 377479.23 | 29-JUN-16:00 |
| Cogeneration:ElectricityNet | 3174.52 | 37055.58 | 09-JUL-10:30 | 377479.23 | 29-JUN-16:00 |
| General:Cogeneration:ElectricityNet | 3174.52 | 37055.58 | 09-JUL-10:30 | 377479.23 | 29-JUN-16:00 |
| Fans:Electricity | 406.11 | 0.00 | 01-JAN-00:40 | 52570.73 | 25-MAY-13:20 |
| General:Fans:Electricity | 406.11 | 0.00 | 01-JAN-00:40 | 52570.73 | 25-MAY-13:20 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 240.31 | 0.00 | 01-JAN-00:10 | 191317.43 | 29-JUN-16:00 |
| General:Cooling:Electricity | 240.31 | 0.00 | 01-JAN-00:10 | 191317.43 | 29-JUN-16:00 |
| ExteriorLights:Electricity | 92.46 | 0.00 | 01-JAN-08:20 | 5897.73 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 92.46 | 0.00 | 01-JAN-08:20 | 5897.73 | 01-JAN-00:10 |
| Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Pumps:Electricity | 4.07 | 0.00 | 01-JAN-00:40 | 1342.09 | 09-JAN-07:10 |
| General:Pumps:Electricity | 4.07 | 0.00 | 01-JAN-00:40 | 1342.09 | 09-JAN-07:10 |
| WIRED_LTG_ELECTRICITY | 14.50 | 0.00 | 01-JAN-00:10 | 946.73 | 02-JAN-07:20 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 3636.59 | 4866.92 | 15-JUL-10:50 | 1273029.11 | 09-JAN-08:10 |
| NaturalGas:Building | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| NaturalGas:SpaceType:GENERAL | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| InteriorEquipment:NaturalGas | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| InteriorEquipment:NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| InteriorEquipment:NaturalGas:SpaceType:GENERAL | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:NaturalGas | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| NaturalGas:HVAC | 1872.24 | 0.00 | 01-JAN-00:40 | 733972.31 | 06-JAN-08:20 |
| Heating:NaturalGas | 3100.28 | 0.00 | 01-JAN-00:40 | 1223736.16 | 09-JAN-08:10 |
| General:Heating:NaturalGas | 1872.24 | 0.00 | 01-JAN-00:40 | 733972.31 | 06-JAN-08:20 |
| NaturalGas:Plant | 1403.32 | 58.42 | 15-JUL-10:50 | 532337.93 | 13-FEB-07:10 |
| WaterSystems:NaturalGas | 175.28 | 58.42 | 15-JUL-10:50 | 34196.88 | 22-FEB-13:50 |
| Water Heater:WaterSystems:NaturalGas | 175.28 | 58.42 | 15-JUL-10:50 | 34196.88 | 22-FEB-13:50 |
| Boiler:Heating:NaturalGas | 1228.05 | 0.00 | 01-JAN-00:40 | 532259.94 | 13-FEB-07:10 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Water:Plant | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| WaterSystems:Water | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Water Heater:WaterSystems:Water | 268.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:20 |
| MainsWater:Facility | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| MainsWater:Plant | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| WaterSystems:MainsWater | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Water Heater:WaterSystems:MainsWater | 268.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:20 |
| WaterUse:WaterSystems:Water | 449.48 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| WaterUse:WaterSystems:MainsWater | 449.48 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 6486.37 | 3012.46 | 02-JAN-06:40 | 1657299.75 | 09-JAN-08:10 |
| EnergyTransfer:Building | 2150.52 | 1506.23 | 02-JAN-06:40 | 436013.28 | 09-JAN-06:10 |
| EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 236.94 | 940.10 | 09-JAN-06:40 | 37227.68 | 09-JAN-06:10 |
| Refrigeration:EnergyTransfer | 186.45 | 1532.99 | 09-JAN-07:00 | 10745.76 | 21-JAN-11:40 |
| Refrigeration:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 93.22 | 766.49 | 09-JAN-07:00 | 5372.88 | 21-JAN-11:40 |
| General:Refrigeration:EnergyTransfer | 93.22 | 766.49 | 09-JAN-07:00 | 5372.88 | 21-JAN-11:40 |
| General:Refrigeration:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 93.22 | 766.49 | 09-JAN-07:00 | 5372.88 | 21-JAN-11:40 |
| EnergyTransfer:Plant | 1059.21 | 766.49 | 09-JAN-07:00 | 399274.47 | 13-FEB-07:10 |
| LowTempRefrigeration:Refrigeration:EnergyTransfer | 17.98 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
| MedTempRefrigeration:Refrigeration:EnergyTransfer | 75.25 | 248.54 | 09-JAN-07:00 | 2686.44 | 03-JAN-07:30 |
| EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 36.32 | 0.00 | 01-JAN-00:40 | 8500.31 | 09-JAN-07:10 |
| Heating:EnergyTransfer | 591.30 | 0.00 | 01-JAN-00:40 | 423796.44 | 09-JAN-07:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 12.71 | 0.00 | 01-JAN-00:40 | 8500.31 | 09-JAN-07:10 |
| General:Heating:EnergyTransfer | 591.30 | 0.00 | 01-JAN-00:40 | 423796.44 | 09-JAN-07:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 12.71 | 0.00 | 01-JAN-00:40 | 8500.31 | 09-JAN-07:10 |
| Cooling:EnergyTransfer | 1466.00 | 0.00 | 01-JAN-00:20 | 302757.47 | 18-MAY-14:00 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 23.62 | 0.00 | 01-JAN-00:10 | 6190.37 | 18-MAY-15:00 |
| General:Cooling:EnergyTransfer | 1466.00 | 0.00 | 01-JAN-00:20 | 302757.47 | 18-MAY-14:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 23.62 | 0.00 | 01-JAN-00:10 | 6190.37 | 18-MAY-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 149.76 | 0.00 | 01-JAN-00:40 | 31324.97 | 09-JAN-07:10 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 26.01 | 0.00 | 01-JAN-00:40 | 31324.97 | 09-JAN-07:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 26.01 | 0.00 | 01-JAN-00:40 | 31324.97 | 09-JAN-07:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 123.75 | 0.00 | 01-JAN-00:20 | 26358.58 | 18-MAY-13:50 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 123.75 | 0.00 | 01-JAN-00:20 | 26358.58 | 18-MAY-13:50 |
| EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 32.07 | 0.00 | 01-JAN-00:40 | 7670.09 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 18.17 | 0.00 | 01-JAN-00:40 | 7670.09 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 18.17 | 0.00 | 01-JAN-00:40 | 7670.09 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 13.90 | 0.00 | 01-JAN-00:10 | 4664.61 | 18-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 13.90 | 0.00 | 01-JAN-00:10 | 4664.61 | 18-MAY-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 35.71 | 0.00 | 01-JAN-00:40 | 7977.42 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 16.68 | 0.00 | 01-JAN-00:40 | 7977.42 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 16.68 | 0.00 | 01-JAN-00:40 | 7977.42 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 19.02 | 0.00 | 01-JAN-00:10 | 4937.48 | 18-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 19.02 | 0.00 | 01-JAN-00:10 | 4937.48 | 18-MAY-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 137.43 | 0.00 | 01-JAN-00:40 | 30583.55 | 09-JAN-07:10 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 37.97 | 0.00 | 01-JAN-00:40 | 30583.55 | 09-JAN-07:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 37.97 | 0.00 | 01-JAN-00:40 | 30583.55 | 09-JAN-07:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 99.46 | 0.00 | 01-JAN-00:10 | 19924.32 | 25-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 99.46 | 0.00 | 01-JAN-00:10 | 19924.32 | 25-MAY-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 36.18 | 0.00 | 01-JAN-00:40 | 8489.58 | 09-JAN-07:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 13.01 | 0.00 | 01-JAN-00:40 | 8489.58 | 09-JAN-07:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 13.01 | 0.00 | 01-JAN-00:40 | 8489.58 | 09-JAN-07:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 23.17 | 0.00 | 01-JAN-00:10 | 6095.69 | 18-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 23.17 | 0.00 | 01-JAN-00:10 | 6095.69 | 18-MAY-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 148.11 | 0.00 | 01-JAN-00:40 | 31027.94 | 09-JAN-07:10 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 26.33 | 0.00 | 01-JAN-00:40 | 31027.94 | 09-JAN-07:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 26.33 | 0.00 | 01-JAN-00:40 | 31027.94 | 09-JAN-07:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 121.78 | 0.00 | 01-JAN-00:10 | 25814.03 | 18-MAY-13:50 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 121.78 | 0.00 | 01-JAN-00:10 | 25814.03 | 18-MAY-13:50 |
| EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 32.10 | 0.00 | 01-JAN-00:40 | 7632.04 | 26-DEC-06:10 |
| Heating:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 18.38 | 0.00 | 01-JAN-00:40 | 7632.04 | 26-DEC-06:10 |
| General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 18.38 | 0.00 | 01-JAN-00:40 | 7632.04 | 26-DEC-06:10 |
| Cooling:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 13.72 | 0.00 | 01-JAN-00:10 | 4625.67 | 18-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 13.72 | 0.00 | 01-JAN-00:10 | 4625.67 | 18-MAY-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 35.72 | 0.00 | 01-JAN-00:40 | 7981.44 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 16.70 | 0.00 | 01-JAN-00:40 | 7981.44 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 16.70 | 0.00 | 01-JAN-00:40 | 7981.44 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 19.03 | 0.00 | 01-JAN-00:10 | 4942.41 | 18-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 19.03 | 0.00 | 01-JAN-00:10 | 4942.41 | 18-MAY-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 137.43 | 0.00 | 01-JAN-00:40 | 30577.91 | 09-JAN-07:10 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 38.01 | 0.00 | 01-JAN-00:40 | 30577.91 | 09-JAN-07:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 38.01 | 0.00 | 01-JAN-00:40 | 30577.91 | 09-JAN-07:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 99.41 | 0.00 | 01-JAN-00:10 | 19947.00 | 25-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 99.41 | 0.00 | 01-JAN-00:10 | 19947.00 | 25-MAY-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 36.31 | 0.00 | 01-JAN-00:40 | 8492.41 | 09-JAN-07:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 12.91 | 0.00 | 01-JAN-00:40 | 8492.41 | 09-JAN-07:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 12.91 | 0.00 | 01-JAN-00:40 | 8492.41 | 09-JAN-07:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 23.40 | 0.00 | 01-JAN-00:10 | 6121.63 | 18-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 23.40 | 0.00 | 01-JAN-00:10 | 6121.63 | 18-MAY-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 149.43 | 0.00 | 01-JAN-00:40 | 31122.82 | 09-JAN-07:10 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 26.01 | 0.00 | 01-JAN-00:40 | 31122.82 | 09-JAN-07:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 26.01 | 0.00 | 01-JAN-00:40 | 31122.82 | 09-JAN-07:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 123.42 | 0.00 | 01-JAN-00:20 | 26043.82 | 18-MAY-13:50 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 123.42 | 0.00 | 01-JAN-00:20 | 26043.82 | 18-MAY-13:50 |
| EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 32.68 | 0.00 | 01-JAN-00:40 | 7718.30 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 18.03 | 0.00 | 01-JAN-00:40 | 7718.30 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 18.03 | 0.00 | 01-JAN-00:40 | 7718.30 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 14.66 | 0.00 | 01-JAN-00:10 | 4816.28 | 18-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 14.66 | 0.00 | 01-JAN-00:10 | 4816.28 | 18-MAY-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 36.06 | 0.00 | 01-JAN-00:40 | 8047.80 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 16.62 | 0.00 | 01-JAN-00:40 | 8047.80 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 16.62 | 0.00 | 01-JAN-00:40 | 8047.80 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 19.44 | 0.00 | 01-JAN-00:10 | 5053.36 | 18-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 19.44 | 0.00 | 01-JAN-00:10 | 5053.36 | 18-MAY-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 93.08 | 0.00 | 01-JAN-00:40 | 20403.18 | 09-JAN-07:10 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 25.79 | 0.00 | 01-JAN-00:40 | 20403.18 | 09-JAN-07:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 25.79 | 0.00 | 01-JAN-00:40 | 20403.18 | 09-JAN-07:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 67.29 | 0.00 | 01-JAN-00:10 | 13663.47 | 25-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 67.29 | 0.00 | 01-JAN-00:10 | 13663.47 | 25-MAY-15:00 |
| EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 55.13 | 0.00 | 01-JAN-00:40 | 10263.52 | 09-JAN-07:10 |
| Heating:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 8.95 | 0.00 | 01-JAN-00:40 | 10263.52 | 09-JAN-07:10 |
| General:Heating:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 8.95 | 0.00 | 01-JAN-00:40 | 10263.52 | 09-JAN-07:10 |
| Cooling:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 46.18 | 0.00 | 01-JAN-00:10 | 8827.36 | 30-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 46.18 | 0.00 | 01-JAN-00:10 | 8827.36 | 30-JUN-15:00 |
| EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 87.72 | 0.00 | 01-JAN-00:40 | 17225.19 | 09-JAN-07:10 |
| Heating:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 50.25 | 0.00 | 01-JAN-00:40 | 17225.19 | 09-JAN-07:10 |
| General:Heating:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 50.25 | 0.00 | 01-JAN-00:40 | 17225.19 | 09-JAN-07:10 |
| Cooling:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 37.47 | 0.00 | 01-JAN-00:10 | 12555.39 | 30-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 37.47 | 0.00 | 01-JAN-00:10 | 12555.39 | 30-JUN-15:00 |
| EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 99.89 | 0.00 | 01-JAN-00:40 | 23772.11 | 06-JAN-08:00 |
| Heating:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 85.84 | 0.00 | 01-JAN-00:40 | 23772.11 | 06-JAN-08:00 |
| General:Heating:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 85.84 | 0.00 | 01-JAN-00:40 | 23772.11 | 06-JAN-08:00 |
| Cooling:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 14.05 | 0.00 | 01-JAN-00:10 | 14438.95 | 29-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 14.05 | 0.00 | 01-JAN-00:10 | 14438.95 | 29-JUN-15:00 |
| EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 35.19 | 0.00 | 01-JAN-00:40 | 6190.25 | 30-JUN-14:20 |
| Heating:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 0.59 | 0.00 | 01-JAN-00:40 | 3257.03 | 09-JAN-00:30 |
| General:Heating:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 0.59 | 0.00 | 01-JAN-00:40 | 3257.03 | 09-JAN-00:30 |
| Cooling:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 34.60 | 0.00 | 01-JAN-00:20 | 6190.25 | 30-JUN-14:20 |
| General:Cooling:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 34.60 | 0.00 | 01-JAN-00:20 | 6190.25 | 30-JUN-14:20 |
| EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 24.10 | 0.00 | 01-JAN-00:40 | 5835.74 | 25-DEC-04:40 |
| Heating:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 8.52 | 0.00 | 01-JAN-00:40 | 5834.90 | 25-DEC-04:40 |
| General:Heating:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 8.52 | 0.00 | 01-JAN-00:40 | 5834.90 | 25-DEC-04:40 |
| Cooling:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 15.58 | 0.00 | 01-JAN-00:10 | 3521.45 | 30-JUN-16:00 |
| General:Cooling:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 15.58 | 0.00 | 01-JAN-00:10 | 3521.45 | 30-JUN-16:00 |
| EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 100.06 | 0.00 | 01-JAN-00:40 | 23298.01 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 40.85 | 0.00 | 01-JAN-00:40 | 23298.01 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 40.85 | 0.00 | 01-JAN-00:40 | 23298.01 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 59.20 | 0.00 | 01-JAN-00:10 | 19575.99 | 30-JUN-14:10 |
| General:Cooling:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 59.20 | 0.00 | 01-JAN-00:10 | 19575.99 | 30-JUN-14:10 |
| EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 114.60 | 0.00 | 01-JAN-00:40 | 21622.17 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 17.73 | 0.00 | 01-JAN-00:40 | 21622.17 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 17.73 | 0.00 | 01-JAN-00:40 | 21622.17 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 96.87 | 0.00 | 01-JAN-00:10 | 20539.50 | 28-JUN-15:20 |
| General:Cooling:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 96.87 | 0.00 | 01-JAN-00:10 | 20539.50 | 28-JUN-15:20 |
| Heating:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 0.44 | 0.00 | 01-JAN-00:10 | 29254.29 | 09-JAN-07:10 |
| General:Heating:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 0.44 | 0.00 | 01-JAN-00:10 | 29254.29 | 09-JAN-07:10 |
| Cooling:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 143.28 | 0.00 | 01-JAN-00:10 | 34560.18 | 09-JAN-06:10 |
| General:Cooling:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 143.28 | 0.00 | 01-JAN-00:10 | 34560.18 | 09-JAN-06:10 |
| EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 168.81 | 0.00 | 01-JAN-00:40 | 45811.21 | 26-DEC-06:20 |
| Heating:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 23.40 | 0.00 | 01-JAN-00:40 | 40674.63 | 26-DEC-06:20 |
| General:Heating:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 23.40 | 0.00 | 01-JAN-00:40 | 40674.63 | 26-DEC-06:20 |
| Cooling:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 145.40 | 0.00 | 01-JAN-00:10 | 29273.04 | 28-JUN-11:50 |
| General:Cooling:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 145.40 | 0.00 | 01-JAN-00:10 | 29273.04 | 28-JUN-11:50 |
| EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 99.69 | 0.00 | 01-JAN-00:40 | 22818.06 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 31.39 | 0.00 | 01-JAN-00:40 | 22818.06 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 31.39 | 0.00 | 01-JAN-00:40 | 22818.06 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 68.30 | 0.00 | 01-JAN-00:10 | 16762.69 | 18-MAY-14:10 |
| General:Cooling:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 68.30 | 0.00 | 01-JAN-00:10 | 16762.69 | 18-MAY-14:10 |
| PlantLoopHeatingDemand:Facility | 973.77 | 0.00 | 01-JAN-00:40 | 385126.50 | 09-JAN-07:10 |
| PlantLoopHeatingDemand:Plant | 102.51 | 0.00 | 01-JAN-00:10 | 21790.59 | 24-FEB-13:10 |
| WaterSystems:PlantLoopHeatingDemand | 102.51 | 0.00 | 01-JAN-00:10 | 21790.59 | 24-FEB-13:10 |
| General:WaterSystems:PlantLoopHeatingDemand | 102.51 | 0.00 | 01-JAN-00:10 | 21790.59 | 24-FEB-13:10 |
| EnergyTransfer:HVAC | 3276.63 | 0.00 | 01-JAN-00:40 | 951477.66 | 09-JAN-08:10 |
| HeatingCoils:EnergyTransfer | 2355.03 | 0.00 | 01-JAN-00:40 | 951477.66 | 09-JAN-08:10 |
| PlantLoopHeatingDemand:HVAC | 871.26 | 0.00 | 01-JAN-00:40 | 385126.50 | 09-JAN-07:10 |
| HeatingCoils:PlantLoopHeatingDemand | 871.26 | 0.00 | 01-JAN-00:40 | 385126.50 | 09-JAN-07:10 |
| CoolingCoils:EnergyTransfer | 921.60 | 0.00 | 01-JAN-00:10 | 734589.58 | 30-JUN-15:10 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:EnergyTransfer | 102.51 | 0.00 | 01-JAN-00:10 | 21790.59 | 24-FEB-13:10 |
| WaterUse:WaterSystems:EnergyTransfer | 102.51 | 0.00 | 01-JAN-00:10 | 21790.59 | 24-FEB-13:10 |
| Boilers:EnergyTransfer | 863.48 | 0.00 | 01-JAN-00:40 | 396355.96 | 13-FEB-07:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 12.707 | -23.615 | 0.000 | 0.000 | 12.730 | 20.559 | 19.109 | 18.882 | 0.000 | 0.023 | 0.000 | 0.000 | -16.944 | 0.000 | -4.748 | -38.703 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 26.013 | -123.747 | 0.000 | 0.000 | 60.688 | 99.059 | 92.071 | 59.099 | 0.000 | 0.072 | 0.000 | 0.000 | -45.957 | 0.000 | -12.975 | -154.324 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 18.167 | -13.902 | 0.000 | 0.000 | 4.992 | 14.502 | 9.883 | 2.396 | 0.000 | 0.004 | 0.000 | 0.000 | -2.920 | 0.000 | -0.729 | -32.393 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 16.685 | -19.022 | 0.000 | 0.000 | 12.943 | 20.559 | 19.109 | 9.278 | 0.000 | 0.032 | 0.000 | 0.000 | -18.137 | 0.000 | -4.609 | -36.837 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 37.969 | -99.461 | 0.000 | 0.000 | 61.959 | 99.059 | 92.071 | 9.948 | 0.000 | 0.101 | 0.000 | 0.000 | -52.073 | 0.000 | -12.540 | -137.034 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 13.015 | -23.170 | 0.000 | 0.000 | 12.746 | 20.559 | 19.109 | 18.108 | 0.000 | 0.024 | 0.000 | 0.000 | -17.031 | 0.000 | -4.738 | -38.623 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 26.330 | -121.782 | 0.000 | 0.000 | 60.779 | 99.059 | 92.071 | 52.992 | 0.000 | 0.075 | 0.000 | 0.000 | -46.783 | 0.000 | -12.949 | -149.793 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 18.385 | -13.719 | 0.000 | 0.000 | 4.995 | 14.502 | 9.883 | 2.398 | 0.000 | 0.004 | 0.000 | 0.000 | -2.917 | 0.000 | -0.728 | -32.803 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 16.696 | -19.028 | 0.000 | 0.000 | 12.943 | 20.559 | 19.109 | 9.323 | 0.000 | 0.032 | 0.000 | 0.000 | -18.130 | 0.000 | -4.609 | -36.895 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 38.012 | -99.414 | 0.000 | 0.000 | 61.955 | 99.059 | 92.071 | 10.158 | 0.000 | 0.101 | 0.000 | 0.000 | -52.020 | 0.000 | -12.540 | -137.382 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 12.906 | -23.402 | 0.000 | 0.000 | 12.737 | 20.559 | 19.109 | 18.185 | 0.000 | 0.024 | 0.000 | 0.000 | -17.029 | 0.000 | -4.747 | -38.343 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 26.007 | -123.420 | 0.000 | 0.000 | 60.698 | 99.059 | 92.071 | 53.417 | 0.000 | 0.073 | 0.000 | 0.000 | -46.737 | 0.000 | -12.983 | -148.185 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 18.027 | -14.658 | 0.000 | 0.000 | 4.979 | 14.502 | 9.883 | 2.388 | 0.000 | 0.004 | 0.000 | 0.000 | -2.934 | 0.000 | -0.732 | -31.457 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 16.624 | -19.436 | 0.000 | 0.000 | 12.921 | 20.559 | 19.109 | 9.831 | 0.000 | 0.030 | 0.000 | 0.000 | -18.102 | 0.000 | -4.624 | -36.913 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 25.789 | -67.292 | 0.000 | 0.000 | 40.819 | 65.416 | 60.801 | 9.004 | 0.000 | 0.062 | 0.000 | 0.000 | -34.055 | 0.000 | -8.311 | -92.234 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 0.000 | 0.000 | 8.949 | -46.178 | 0.000 | 0.000 | 34.373 | 33.643 | 41.692 | 4.397 | 0.000 | 0.025 | 0.000 | 0.000 | -18.035 | 0.000 | -4.401 | -54.466 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 0.000 | 0.000 | 50.253 | -37.471 | 0.000 | 0.000 | 14.139 | 41.241 | 28.104 | 5.149 | 0.000 | 0.009 | 0.000 | 0.000 | -9.030 | 0.000 | -2.211 | -90.182 |
| LOBBY_ZN_1_FLR_1 | 0.000 | 0.000 | 85.841 | -14.054 | 0.000 | 0.000 | 10.400 | 32.975 | 8.802 | 22.007 | 0.000 | 1.843 | 0.000 | 0.000 | -14.920 | 0.000 | -111.663 | -21.231 |
| MECH_ZN_1_FLR_1 | 0.000 | 0.000 | 0.591 | -34.596 | 0.000 | 0.000 | 1.869 | 56.071 | 32.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -56.363 |
| BATH_ZN_1_FLR_1 | 0.000 | 0.000 | 8.521 | -15.577 | 0.000 | 0.000 | 5.269 | 25.366 | 9.780 | 5.958 | 0.000 | 0.006 | 0.000 | 0.000 | -9.547 | 0.000 | -2.393 | -27.380 |
| OFFICES_ZN_1_FLR_1 | 0.000 | 0.000 | 40.855 | -59.201 | 0.000 | 0.000 | 11.055 | 71.958 | 61.288 | 37.954 | 0.000 | 0.034 | 0.000 | 0.000 | -36.509 | 0.000 | -10.379 | -117.055 |
| GYM_ZN_1_FLR_1 | 0.000 | 0.000 | 17.730 | -96.870 | 0.000 | 0.000 | 55.658 | 65.666 | 22.969 | 39.851 | 0.000 | 0.015 | 0.000 | 0.000 | -35.028 | 0.000 | -4.349 | -65.642 |
| KITCHEN_ZN_1_FLR_1 | 0.000 | 0.000 | 0.437 | -143.269 | 0.000 | 0.000 | 11.743 | 29.905 | 138.079 | 5.894 | 0.000 | 0.005 | 0.000 | 0.000 | -9.160 | 0.000 | -2.454 | -31.180 |
| CAFETERIA_ZN_1_FLR_1 | 0.000 | 0.000 | 23.403 | -145.408 | 0.000 | 0.000 | 154.945 | 42.053 | 29.938 | 14.962 | 0.000 | 0.027 | 0.000 | 0.000 | -34.504 | 0.000 | -8.932 | -76.483 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.000 | 0.000 | 31.387 | -68.300 | 0.000 | 0.000 | 20.144 | 91.739 | 77.015 | 18.647 | 0.000 | 0.035 | 0.000 | 0.000 | -38.193 | 0.000 | -9.913 | -122.560 |
| Total Facility | 0.000 | 0.000 | 591.298 | -1465.994 | 0.000 | 0.000 | 758.479 | 1218.192 | 1115.552 | 440.225 | 0.000 | 2.660 | 0.006 | 0.000 | -596.693 | 0.000 | -259.257 | -1804.463 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 13-AUG-15:18 | 0.00 | 0.00 | 0.00 | -6784.28 | 0.00 | 0.00 | 0.00 | 264.51 | 289.46 | 3686.79 | 0.00 | 0.00 | 2593.53 | 0.00 | -0.00 | 0.00 | -50.02 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 18-MAY-13:50 | 0.00 | 0.00 | 0.00 | -26357.10 | 0.00 | 0.00 | 8480.60 | 6469.32 | 6325.65 | 10655.54 | 0.00 | 31.18 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5605.19 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 18-MAY-15:00 | 0.00 | 0.00 | 0.00 | -4664.07 | 0.00 | 0.00 | 682.67 | 947.12 | 678.98 | 804.66 | 0.00 | 1.73 | 1548.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 18-MAY-15:00 | 0.00 | 0.00 | 0.00 | -4936.86 | 0.00 | 0.00 | 1760.19 | 1342.69 | 1312.87 | 2913.71 | 0.00 | 11.57 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2404.16 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 25-MAY-15:00 | 0.00 | 0.00 | 0.00 | -19921.30 | 0.00 | 0.00 | 8481.13 | 6469.32 | 6325.65 | 2047.29 | 0.00 | 30.50 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3432.58 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 18-MAY-15:00 | 0.00 | 0.00 | 0.00 | -6095.02 | 0.00 | 0.00 | 1760.17 | 1342.69 | 1312.87 | 3758.84 | 0.00 | 11.57 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2091.12 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 18-MAY-13:50 | 0.00 | 0.00 | 0.00 | -25812.59 | 0.00 | 0.00 | 8480.60 | 6469.32 | 6325.65 | 9985.67 | 0.00 | 31.18 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5479.83 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 18-MAY-15:00 | 0.00 | 0.00 | 0.00 | -4625.13 | 0.00 | 0.00 | 682.67 | 947.12 | 678.98 | 804.73 | 0.00 | 1.73 | 1509.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 18-MAY-15:00 | 0.00 | 0.00 | 0.00 | -4941.80 | 0.00 | 0.00 | 1760.19 | 1342.69 | 1312.87 | 2921.21 | 0.00 | 11.57 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2406.73 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 25-MAY-15:00 | 0.00 | 0.00 | 0.00 | -19943.97 | 0.00 | 0.00 | 8481.13 | 6469.32 | 6325.65 | 2074.79 | 0.00 | 30.50 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3437.41 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 18-MAY-15:00 | 0.00 | 0.00 | 0.00 | -6120.95 | 0.00 | 0.00 | 1760.17 | 1342.69 | 1312.87 | 3766.82 | 0.00 | 11.57 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2073.16 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 18-MAY-13:50 | 0.00 | 0.00 | 0.00 | -26042.38 | 0.00 | 0.00 | 8480.60 | 6469.32 | 6325.65 | 10020.64 | 0.00 | 31.18 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5285.01 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 18-MAY-15:00 | 0.00 | 0.00 | 0.00 | -4815.72 | 0.00 | 0.00 | 682.67 | 947.12 | 678.98 | 804.42 | 0.00 | 1.73 | 1700.80 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 18-MAY-15:00 | 0.00 | 0.00 | 0.00 | -5052.73 | 0.00 | 0.00 | 1760.18 | 1342.69 | 1312.87 | 3014.18 | 0.00 | 11.57 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2388.75 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 25-MAY-15:00 | 0.00 | 0.00 | 0.00 | -13661.44 | 0.00 | 0.00 | 5600.73 | 4272.19 | 4177.31 | 1660.36 | 0.00 | 20.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2069.29 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 30-JUN-15:03 | 0.00 | 0.00 | 0.00 | -8835.80 | 0.00 | 0.00 | 2880.25 | 2197.13 | 2864.44 | 1237.31 | 0.00 | 42.58 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -385.91 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 30-JUN-07:03 | 0.00 | 0.00 | 0.00 | -15840.44 | 0.00 | 0.00 | 297.08 | 2693.36 | 1930.85 | 80.53 | 0.00 | 2.23 | 10836.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | -14431.85 | 0.00 | 0.00 | 109.04 | 2153.53 | 604.72 | 2419.47 | 0.00 | 15400.59 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6255.51 |
| MECH_ZN_1_FLR_1 | 12-AUG-13:11 | 0.00 | 0.00 | 0.00 | -13852.96 | 0.00 | 0.00 | 0.00 | 721.39 | 491.20 | 0.00 | 0.00 | 0.00 | 12640.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 29-JUL-17:30 | 0.00 | 0.00 | 0.00 | -8122.60 | 0.00 | 0.00 | 0.00 | 326.34 | 148.14 | 2631.82 | 0.00 | 8.37 | 5007.93 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 23-JUL-14:02 | 0.00 | 0.00 | 0.00 | -26648.93 | 0.00 | 0.00 | 0.00 | 925.78 | 928.37 | 4598.66 | 0.00 | 126.44 | 20069.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 19-JUN-05:01 | 0.00 | 0.00 | 0.00 | -30096.43 | 0.00 | 0.00 | 0.00 | 844.83 | 487.11 | 525.62 | 0.00 | 0.00 | 28331.67 | 0.00 | -0.00 | 0.00 | -92.80 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 10-NOV-06:01 | 0.00 | 0.00 | 0.00 | -85273.13 | 0.00 | 0.00 | 0.00 | 384.74 | 2721.46 | 0.00 | 0.00 | 0.00 | 82979.01 | 0.00 | -611.21 | 0.00 | -200.87 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 20-DEC-19:11 | 0.00 | 0.00 | 0.00 | -67930.30 | 0.00 | 0.00 | 9809.52 | 2746.41 | 799.79 | 0.00 | 0.00 | 0.00 | 58174.39 | 0.00 | -3422.77 | 0.00 | -177.03 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 28-JUN-07:03 | 0.00 | 0.00 | 0.00 | -24309.18 | 0.00 | 0.00 | 417.06 | 5991.24 | 5291.26 | 7120.20 | 0.00 | 0.00 | 5490.12 | 0.00 | -0.00 | 0.00 | -0.71 | 0.00 |
| Total Facility | 18-MAY-14:03 | 0.00 | 0.00 | 0.00 | -303560.96 | 0.00 | 0.00 | 84598.47 | 79557.27 | 68620.86 | 80503.32 | 0.00 | 11423.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -21142.34 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 25-DEC-06:31 | 0.00 | 0.00 | 10145.92 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1849.96 | 0.00 | -573.61 | -8392.10 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 25-DEC-06:31 | 0.00 | 0.00 | 36775.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5062.92 | 0.00 | -1551.85 | -33387.37 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 25-DEC-06:31 | 0.00 | 0.00 | 8247.24 | 0.00 | 0.00 | 0.00 | 0.00 | 186.58 | 209.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -286.66 | 0.00 | -88.49 | -8268.25 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 25-DEC-05:51 | 0.00 | 0.00 | 9293.92 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1813.68 | 0.00 | -578.31 | -7571.68 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 25-DEC-05:51 | 0.00 | 0.00 | 35824.15 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4856.25 | 0.00 | -1565.12 | -32629.76 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 25-DEC-06:31 | 0.00 | 0.00 | 10085.99 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1838.88 | 0.00 | -573.31 | -8343.56 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 25-DEC-06:31 | 0.00 | 0.00 | 36395.89 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4995.11 | 0.00 | -1550.47 | -33077.30 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 25-DEC-06:31 | 0.00 | 0.00 | 8206.94 | 0.00 | 0.00 | 0.00 | 0.00 | 186.58 | 209.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -286.54 | 0.00 | -88.46 | -8228.10 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 24-DEC-09:11 | 0.00 | 0.00 | 9308.44 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1775.19 | 0.00 | -893.92 | -7309.08 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 25-DEC-05:51 | 0.00 | 0.00 | 35812.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4859.47 | 0.00 | -1565.02 | -32614.75 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 25-DEC-06:31 | 0.00 | 0.00 | 10090.72 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1840.07 | 0.00 | -573.41 | -8346.99 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 25-DEC-06:31 | 0.00 | 0.00 | 36524.28 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4999.42 | 0.00 | -1550.74 | -33201.10 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 25-DEC-06:31 | 0.00 | 0.00 | 8304.74 | 0.00 | 0.00 | 0.00 | 0.00 | 186.58 | 209.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -286.55 | 0.00 | -88.47 | -8325.88 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 24-DEC-09:11 | 0.00 | 0.00 | 9393.67 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1751.84 | 0.00 | -894.12 | -7417.47 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 25-DEC-05:51 | 0.00 | 0.00 | 23897.30 | 0.00 | 0.00 | 0.00 | 0.00 | 841.62 | 1289.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3246.08 | 0.00 | -1032.61 | -21749.64 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 25-DEC-05:51 | 0.00 | 0.00 | 12028.50 | 0.00 | 0.00 | 0.00 | 0.00 | 432.83 | 884.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1676.97 | 0.00 | -532.60 | -11135.93 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 25-DEC-06:31 | 0.00 | 0.00 | 18290.95 | 0.00 | 0.00 | 0.00 | 0.00 | 530.59 | 595.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -832.46 | 0.00 | -265.33 | -18319.75 |
| LOBBY_ZN_1_FLR_1 | 06-JAN-07:10 | 0.00 | 0.00 | 24857.34 | 0.00 | 0.00 | 0.00 | 0.00 | 2153.53 | 186.66 | 0.00 | 0.00 | 0.00 | 40556.71 | 0.00 | -1875.04 | 0.00 | -65879.20 | 0.00 |
| MECH_ZN_1_FLR_1 | 09-JAN-07:01 | 0.00 | 0.00 | 9559.08 | 0.00 | 0.00 | 0.00 | 0.00 | 3661.88 | 687.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13908.64 |
| BATH_ZN_1_FLR_1 | 09-JAN-07:01 | 0.00 | 0.00 | 8457.49 | 0.00 | 0.00 | 0.00 | 0.00 | 1656.56 | 207.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1013.05 | 0.00 | -50.21 | -9258.19 |
| OFFICES_ZN_1_FLR_1 | 25-DEC-06:31 | 0.00 | 0.00 | 26007.00 | 0.00 | 0.00 | 0.00 | 0.00 | 925.78 | 1299.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4009.60 | 0.00 | -1222.92 | -22999.99 |
| GYM_ZN_1_FLR_1 | 25-DEC-06:31 | 0.00 | 0.00 | 25093.79 | 0.00 | 0.00 | 0.00 | 0.00 | 844.83 | 487.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3572.70 | 0.00 | -499.50 | -22353.52 |
| KITCHEN_ZN_1_FLR_1 | 09-JAN-07:07 | 0.00 | 0.00 | 36834.86 | 0.00 | 0.00 | 0.00 | 0.00 | 1953.00 | 2721.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -690.24 | 0.00 | -46.01 | -40773.07 |
| CAFETERIA_ZN_1_FLR_1 | 11-DEC-07:01 | 0.00 | 0.00 | 129402.52 | 0.00 | 0.00 | 0.00 | 0.00 | 2746.41 | 799.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3033.00 | 0.00 | -147.90 | -129767.81 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 25-DEC-05:51 | 0.00 | 0.00 | 25924.68 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.27 | 1633.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3782.21 | 0.00 | -1181.95 | -23774.03 |
| Total Facility | 11-DEC-07:01 | 0.00 | 0.00 | 566807.55 | 0.00 | 0.00 | 0.00 | 0.00 | 79557.27 | 23615.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -53706.85 | 0.00 | -143312.15 | -472961.24 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| VAV_POD_1 | 29.7756 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 29.5130 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| PSZ-AC_1:6 | 1.6084 | 0.0000 | 26.9930 | 1.0000 | Calculated from schedules | 0.4528 | 1.6084 | 0.2815 | 1.0000 | Not calculated | 0.4528 | 0.2815 | ||
| PSZ-AC_2:7 | 2.7529 | 0.0000 | 339.0743 | 1.0000 | Calculated from schedules | 1.4882 | 2.7529 | 0.5406 | 1.0000 | Not calculated | 1.4882 | 0.5406 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| VAV_POD_1 | 15.3323 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 13.0440 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| PSZ-AC_1:6 | 1.6084 | 0.0000 | 26.9930 | 1.0000 | Calculated from schedules | 0.4528 | 1.6084 | 1.0000 | 1.0000 | Not calculated | 0.4528 | 0.2815 | ||
| PSZ-AC_2:7 | 2.7529 | 0.0000 | 339.0743 | 1.0000 | Calculated from schedules | 1.4882 | 2.7529 | 1.0000 | 1.0000 | Not calculated | 1.4882 | 0.5406 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.3340 | 0.000305 | 192.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.3340 | 0.000305 | 192.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.3340 | 0.000305 | 192.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 84.7686 | 0.001880 | 315.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 43.5953 | 0.001880 | 162.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 29.3880 | 0.000305 | 546.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 18.4080 | 0.000559 | 171.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 4.0690 | 0.000000 | 252.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.2270 | 0.000000 | 190.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 23.7365 | 0.000432 | 441.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 115.3101 | 0.001524 | 357.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | 0.009440 | 26.9930 | 0.001179 | 168.00 | 0.4528 | 1.0000 | 0.4528 | 1.000 | 0.4528 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | 0.000000 | 339.0743 | 0.004724 | 315.00 | 1.4882 | 1.0000 | 1.4882 | 1.000 | 1.4882 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 42.9540 | 0.000864 | 399.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| VAV_POD_1 | 0.00 | 0.001254 | 6388.0000 | 0.0000 | 0.0000 | 0.0000 | |
| PSZ-AC_1:6 | 0.009440 | 26.99 | 0.001179 | 168.0000 | 0.4528 | 0.4528 | 0.4528 |
| PSZ-AC_2:7 | 0.000000 | 339.07 | 0.004724 | 315.0000 | 1.4882 | 1.4882 | 1.4882 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6690 | 0.6690 | 0.2770 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8044 | 2.8044 | 1.3349 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5567 | 0.5567 | 0.1670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5933 | 0.5933 | 0.2771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3346 | 2.3346 | 1.3354 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6627 | 0.6627 | 0.2770 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7639 | 2.7639 | 1.3350 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5543 | 0.5543 | 0.1663 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5937 | 0.5937 | 0.2773 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.3365 | 2.3365 | 1.3341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6634 | 0.6634 | 0.2773 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7765 | 2.7765 | 1.3355 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5605 | 0.5605 | 0.1682 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5997 | 0.5997 | 0.2771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5769 | 1.5769 | 0.8815 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8719 | 0.8719 | 0.4534 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2342 | 1.2342 | 0.3703 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7132 | 0.7132 | 0.2140 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8409 | 0.8409 | 0.2523 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5596 | 0.5596 | 0.1679 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7173 | 1.7173 | 0.5152 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9888 | 1.9888 | 0.8094 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6084 | 1.6084 | 1.6084 | No | 0.4528 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.7529 | 2.7529 | 2.7529 | No | 1.4882 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.8037 | 1.8037 | 0.5411 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| VAV_POD_1 | 29.7756 | 29.5130 | 29.7756 | 13.0440 | 0.0000 | 1.0000 |
| PSZ-AC_1:6 | 1.6084 | 1.6084 | 1.6084 | 1.6084 | 0.4528 | 1.0000 |
| PSZ-AC_2:7 | 2.7529 | 2.7529 | 2.7529 | 2.7529 | 1.4882 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3345 | 0.3345 | 0.2770 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4022 | 1.4022 | 1.3349 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2784 | 0.2784 | 0.1670 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2966 | 0.2966 | 0.2771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3354 | 1.3354 | 1.3354 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3313 | 0.3313 | 0.2770 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3820 | 1.3820 | 1.3350 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2772 | 0.2772 | 0.1663 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2969 | 0.2969 | 0.2773 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3341 | 1.3341 | 1.3341 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3317 | 0.3317 | 0.2773 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3882 | 1.3882 | 1.3355 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2803 | 0.2803 | 0.1682 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2998 | 0.2998 | 0.2771 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8815 | 0.8815 | 0.8815 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4534 | 0.4534 | 0.4534 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6171 | 0.6171 | 0.3703 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3566 | 0.3566 | 0.2140 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4204 | 0.4204 | 0.2523 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2798 | 0.2798 | 0.1679 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8587 | 0.8587 | 0.5152 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9944 | 0.9944 | 0.8094 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.6084 | 1.6084 | 1.6084 | No | 0.4528 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.7529 | 2.7529 | 2.7529 | No | 1.4882 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9018 | 0.9018 | 0.5411 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| VAV_POD_1 | 15.3323 | 13.0440 | 13.0440 | 13.0440 | 0.0000 | 1.0000 |
| PSZ-AC_1:6 | 1.6084 | 1.6084 | 1.6084 | 1.6084 | 0.4528 | 1.0000 |
| PSZ-AC_2:7 | 2.7529 | 2.7529 | 2.7529 | 2.7529 | 1.4882 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
| Total gross floor area [m2] | 6871.00 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 192.00 | 0.00 | 62.83 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 192.00 | 0.00 | 62.83 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 192.00 | 0.00 | 62.83 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 315.00 | 0.00 | 62.83 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 162.00 | 0.00 | 62.83 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 546.00 | 0.00 | 62.83 |
| LOBBY_ZN_1_FLR_1 | 171.00 | 171.00 | 0.00 | 62.83 |
| MECH_ZN_1_FLR_1 | 252.00 | 252.00 | 0.00 | 62.83 |
| BATH_ZN_1_FLR_1 | 190.00 | 190.00 | 0.00 | 62.83 |
| OFFICES_ZN_1_FLR_1 | 441.00 | 441.00 | 0.00 | 53.16 |
| GYM_ZN_1_FLR_1 | 357.00 | 357.00 | 0.00 | 62.83 |
| KITCHEN_ZN_1_FLR_1 | 168.00 | 168.00 | 0.00 | 62.83 |
| CAFETERIA_ZN_1_FLR_1 | 315.00 | 315.00 | 0.00 | 52.32 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 399.00 | 0.00 | 62.83 |
| Totals | 6871.00 | 6871.00 | 0.00 |
| Data | |
| Number of hours heating loads not met | 1279.67 |
| Number of hours cooling loads not met | 28.00 |
| Number of hours not met | 1307.67 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 1872.24 | 733972.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heating -- Boiler | 0.00 | 0.00 | 1228.05 | 532259.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 240.31 | 191317.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 1218.19 | 79557.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 92.46 | 5897.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 947.54 | 65099.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- Cooking | 149.71 | 9998.36 | 361.03 | 48084.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ReachInFreezer | 31.09 | 986.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ReachInRefrigerator | 23.02 | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Transformer | 17.61 | 1336.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 406.11 | 52570.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- General | 4.07 | 1342.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 0.00 | 0.00 | 175.28 | 34196.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- General | 7.85 | 2172.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- LowTempRefrigeration | 14.74 | 1475.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- MedTempRefrigeration | 21.82 | 734.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 1195.77 | 3174.52 |
| Natural Gas | 361.03 | 3636.59 |
| Additional | 0.00 | 0.00 |
| Total | 1556.80 | 6811.11 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 177.29 |
| Space Heating | 0.00 |
| Space Cooling | 34.97 |
| Fans (All) | 59.10 |
| Service Water Heating | 0.00 |
| Receptacle Equipment | 167.57 |
| Miscellaneous (All) | 462.02 |
| Subtotal | 462.02 |
| Natural Gas [MJ/m2] | |
| Space Heating | 451.21 |
| Service Water Heating | 25.51 |
| Miscellaneous (All) | 529.27 |
| Subtotal | 529.27 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 17.89 |
| Space Heating | 45.52 |
| Space Cooling | 3.53 |
| Fans (All) | 5.96 |
| Service Water Heating | 2.57 |
| Receptacle Equipment | 22.20 |
| Miscellaneous | 2.33 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| LTG_SCH_GYM | 3903. | 8760. |
| LTG_SCH_CLASSROOM | 3903. | 8760. |
| LTG_SCH_LIBRARY | 3903. | 8760. |
| LTG_SCH_BATH | 3903. | 8760. |
| LTG_SCH_KITCHEN | 3903. | 8760. |
| LTG_SCH_OFFICE | 3903. | 8760. |
| LTG_SCH_LOBBY | 3903. | 8760. |
| LTG_SCH_MECHANICAL | 3903. | 8760. |
| LTG_SCH_COMPUTER_ROOM | 3903. | 8760. |
| LTG_SCH_CAFETERIA | 3903. | 8760. |
| LTG_SCH_CORRIDOR | 3903. | 8760. |
| BLDG_EQUIP_SCH | 3617. | 8760. |
| WALKIN_OCC_LGHT_SCH_2 | 2473. | 8760. |
| KITCHEN_ELEC_EQUIP_SCH | 1045. | 8760. |
| KITCHEN_GAS_EQUIP_SCH | 425. | 8760. |
| BLDG_OCC_SCH | 1755. | 3380. |
| BLDG_OCC_SCH_EXTEND | 2948. | 3380. |
| BLDG_OCC_SCH_OFFICES | 2197. | 3380. |
| BLDG_OCC_SCH_OFFICES_W_SB | 1743. | 2860. |
| OFFICES BINARY OCCUPANCY | 3380. | 3380. |
| BLDG_OCC_SCH_GYM | 1828. | 3380. |
| BLDG_OCC_SCH_CAFETERIA | 1687. | 2815. |
| INFIL_SCH | 6205. | 8760. |
| INFIL_SCH_PNNL | 6030. | 8760. |
| INFIL_DOOR_OPENING_SCH | 827. | 2860. |
| BLDG_SWH_SCH | 1227. | 3120. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| EXTERIOR_LGT_189_1 | 5940. | 8760. |
| WORK_EFF_SCH | 0. | 0. |
| KITCHEN_EXHAUST_SCH | 2860. | 2860. |
| MINOA_SCHED | 8760. | 8760. |
| BATH_ZN_1_FLR_1 SHW_DEFAULT LATENT FRACT SCHED | 438. | 8760. |
| BATH_ZN_1_FLR_1 SHW_DEFAULT SENSIBLE FRACT SCHED | 1752. | 8760. |
| KITCHEN_ZN_1_FLR_1 SHW_DEFAULT LATENT FRACT SCHED | 438. | 8760. |
| KITCHEN_ZN_1_FLR_1 SHW_DEFAULT SENSIBLE FRACT SCHED | 1752. | 8760. |
| KITCHEN_ZN_1_FLR_1_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
| EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 3380. | 3380. |
| EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6570. | 8760. |
| KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 2594. | 2860. |
| OFFICES_ZN_1_FLR_1_MDP_SCH | 2472. | 8240. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_SCH_YES_OPTIMUM | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
| CLGSETP_SCH_YES_OPTIMUM | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
| HTGSETP_SCH_SETBACK | MECH_ZN_1_FLR_1 DUAL SP CONTROL | January | 15.60 | 365 | 15.60 | 365 |
| CLGSETP_SCH_SETUP | MECH_ZN_1_FLR_1 DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
| HTGSETP_SCH_YES_OPTIMUM_W_SB | OFFICES_ZN_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
| CLGSETP_SCH_YES_OPTIMUM_W_SB | OFFICES_ZN_1_FLR_1 DUAL SP CONTROL | July | 24.56 | 63 | 26.70 | 365 |
| HTGSETP_SCH_NO_OPTIMUM | GYM_ZN_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
| CLGSETP_SCH_NO_OPTIMUM | GYM_ZN_1_FLR_1 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 8752.00 | 8.00 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 8298.33 | 461.67 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 8738.50 | 21.50 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 8737.17 | 22.83 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 8705.17 | 54.83 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 6611.17 | 2127.50 | 21.33 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 8556.83 | 203.17 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
| Min | 6611.17 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 2127.50 | 21.33 | 0.00 | 0.00 |
| Average | 8642.60 | 116.55 | 0.85 | 0.00 | 0.00 |
| Sum | 216065.00 | 2913.67 | 21.33 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 141584.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 122876.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 47696.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 29103.00 | 9.00 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 4443.00 | 69.00 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 15287.00 | 21.00 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 38444.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 202800.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 44688.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 552560.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 70792.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 4443.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 552560.00 | 69.00 | 0.00 | 0.00 | 0.00 |
| Average | 106078.12 | 3.96 | 0.00 | 0.00 | 0.00 |
| Sum | 2651953.00 | 99.00 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 8683.00 | 77.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 8727.00 | 33.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 8752.00 | 8.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 8696.83 | 63.17 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 8744.67 | 15.33 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 8752.50 | 7.50 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 8686.00 | 74.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 8729.33 | 30.67 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 8744.50 | 15.50 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 8622.83 | 137.17 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 8737.50 | 22.50 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 8587.00 | 173.00 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 7813.17 | 946.83 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 8340.33 | 419.67 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 8492.17 | 267.83 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 8311.83 | 448.17 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 4898.83 | 3768.83 | 92.33 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 7950.50 | 809.50 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 8476.17 | 283.83 | 0.00 | 0.00 | 0.00 |
| Min | 4898.83 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 3768.83 | 92.33 | 0.00 | 0.00 |
| Average | 8452.11 | 304.20 | 3.69 | 0.00 | 0.00 |
| Sum | 211302.67 | 7605.00 | 92.33 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 141584.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 122876.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 47696.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 28927.33 | 184.67 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 4371.50 | 140.50 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 14901.50 | 406.50 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 38444.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 202800.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 42801.00 | 1887.00 | 0.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 531314.67 | 21245.33 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 70792.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 4371.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 531314.67 | 21245.33 | 0.00 | 0.00 | 0.00 |
| Average | 105127.52 | 954.56 | 0.00 | 0.00 | 0.00 |
| Sum | 2628188.00 | 23864.00 | 0.00 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:31:19
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -16.89 |
| February | -11.56 |
| March | -6.15 |
| April | 3.968 |
| May | 13.433 |
| June | 18.029 |
| July | 19.667 |
| August | 17.942 |
| September | 12.293 |
| October | 5.424 |
| November | -2.00 |
| December | -14.64 |
| Annual Sum or Average | 3.363 |
| Minimum of Months | -16.89 |
| Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -16.89 |
| February | -11.56 |
| March | -6.15 |
| April | 3.968 |
| May | 13.433 |
| June | 18.029 |
| July | 19.667 |
| August | 17.942 |
| September | 12.293 |
| October | 5.424 |
| November | -2.00 |
| December | -14.64 |
| Annual Sum or Average | 3.363 |
| Minimum of Months | -16.89 |
| Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -16.89 |
| February | -11.56 |
| March | -6.15 |
| April | 3.968 |
| May | 13.433 |
| June | 18.029 |
| July | 19.667 |
| August | 17.942 |
| September | 12.293 |
| October | 5.424 |
| November | -2.00 |
| December | -14.64 |
| Annual Sum or Average | 3.363 |
| Minimum of Months | -16.89 |
| Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -16.89 |
| February | -11.56 |
| March | -6.15 |
| April | 3.968 |
| May | 13.433 |
| June | 18.029 |
| July | 19.667 |
| August | 17.942 |
| September | 12.293 |
| October | 5.424 |
| November | -2.00 |
| December | -14.64 |
| Annual Sum or Average | 3.363 |
| Minimum of Months | -16.89 |
| Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME SCHOOLPRIMARY
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -16.89 |
| February | -11.56 |
| March | -6.15 |
| April | 3.968 |
| May | 13.433 |
| June | 18.029 |
| July | 19.667 |
| August | 17.942 |
| September | 12.293 |
| October | 5.424 |
| November | -2.00 |
| December | -14.64 |
| Annual Sum or Average | 3.363 |
| Minimum of Months | -16.89 |
| Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -16.89 |
| February | -11.56 |
| March | -6.15 |
| April | 3.968 |
| May | 13.433 |
| June | 18.029 |
| July | 19.667 |
| August | 17.942 |
| September | 12.293 |
| October | 5.424 |
| November | -2.00 |
| December | -14.64 |
| Annual Sum or Average | 3.363 |
| Minimum of Months | -16.89 |
| Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -16.89 |
| February | -11.56 |
| March | -6.15 |
| April | 3.968 |
| May | 13.433 |
| June | 18.029 |
| July | 19.667 |
| August | 17.942 |
| September | 12.293 |
| October | 5.424 |
| November | -2.00 |
| December | -14.64 |
| Annual Sum or Average | 3.363 |
| Minimum of Months | -16.89 |
| Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -16.89 |
| February | -11.56 |
| March | -6.15 |
| April | 3.968 |
| May | 13.433 |
| June | 18.029 |
| July | 19.667 |
| August | 17.942 |
| September | 12.293 |
| October | 5.424 |
| November | -2.00 |
| December | -14.64 |
| Annual Sum or Average | 3.363 |
| Minimum of Months | -16.89 |
| Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -16.89 |
| February | -11.56 |
| March | -6.15 |
| April | 3.968 |
| May | 13.433 |
| June | 18.029 |
| July | 19.667 |
| August | 17.942 |
| September | 12.293 |
| October | 5.424 |
| November | -2.00 |
| December | -14.64 |
| Annual Sum or Average | 3.363 |
| Minimum of Months | -16.89 |
| Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.306730E+09 | 2148.43 | 27-JAN-15:30 | -14.4 | -15.6 | 0.629185E+09 | 1078.70 | 27-JAN-15:39 | -14.4 | -15.6 |
| February | 0.555953E+09 | 2469.14 | 28-FEB-15:50 | 6.10 | 1.55 | 0.577362E+09 | 1186.93 | 28-FEB-15:00 | 6.10 | 1.55 |
| March | 0.918805E+09 | 2629.50 | 31-MAR-15:00 | 8.30 | 2.63 | 0.704813E+09 | 1238.01 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.161373E+10 | 3874.88 | 13-APR-15:00 | 20.00 | 8.11 | 0.668472E+09 | 1277.24 | 19-APR-14:20 | 6.70 | 0.87 |
| May | 0.334759E+10 | 6190.37 | 18-MAY-15:00 | 28.90 | 16.60 | 0.829173E+09 | 1277.23 | 19-MAY-14:20 | 17.67 | 14.71 |
| June | 0.391032E+10 | 5431.43 | 08-JUN-15:00 | 23.90 | 13.85 | 0.528409E+09 | 1277.22 | 13-JUN-14:20 | 17.93 | 13.65 |
| July | 0.321148E+10 | 4285.25 | 24-JUL-15:03 | 29.32 | 19.17 | 0.172695E+09 | 201.70 | 21-JUL-15:50 | 29.32 | 19.17 |
| August | 0.313580E+10 | 6784.06 | 13-AUG-15:18 | 22.60 | 14.75 | 0.191543E+09 | 201.70 | 25-AUG-15:39 | 28.30 | 19.34 |
| September | 0.298427E+10 | 5433.05 | 03-SEP-14:30 | 21.40 | 16.15 | 0.473226E+09 | 1277.24 | 21-SEP-14:20 | 9.80 | 7.98 |
| October | 0.223379E+10 | 5416.03 | 20-OCT-14:30 | 18.90 | 10.07 | 0.736299E+09 | 1277.24 | 02-OCT-14:20 | 18.90 | 10.07 |
| November | 0.109732E+10 | 2701.90 | 17-NOV-15:40 | 10.20 | 3.28 | 0.664654E+09 | 1266.56 | 17-NOV-15:39 | 10.20 | 3.28 |
| December | 0.299651E+09 | 1948.04 | 28-DEC-14:40 | -1.7 | -3.7 | 0.597904E+09 | 1009.90 | 28-DEC-14:50 | -1.7 | -3.7 |
| Annual Sum or Average | 0.236154E+11 | 0.677374E+10 | ||||||||
| Minimum of Months | 0.299651E+09 | 1948.04 | -14.4 | -15.6 | 0.172695E+09 | 201.70 | -14.4 | -15.6 | ||
| Maximum of Months | 0.391032E+10 | 6784.06 | 29.32 | 19.17 | 0.829173E+09 | 1277.24 | 29.32 | 19.34 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.306827E+10 | 10533.96 | 27-JAN-15:02 | -14.4 | -15.6 | 0.304802E+10 | 5255.98 | 27-JAN-14:00 | -14.4 | -15.6 |
| February | 0.440163E+10 | 11793.88 | 08-FEB-15:10 | 4.90 | -0.6 | 0.282555E+10 | 5684.89 | 08-FEB-15:20 | 4.80 | -0.7 |
| March | 0.679469E+10 | 12949.94 | 31-MAR-14:40 | 8.30 | 2.79 | 0.349096E+10 | 6092.24 | 31-MAR-14:50 | 8.30 | 2.71 |
| April | 0.936363E+10 | 17567.15 | 18-APR-14:02 | 17.33 | 10.22 | 0.335263E+10 | 6159.01 | 20-APR-13:20 | 9.60 | 2.32 |
| May | 0.163252E+11 | 26358.58 | 18-MAY-13:50 | 28.45 | 16.75 | 0.408328E+10 | 6153.93 | 30-MAY-14:20 | 11.57 | 8.79 |
| June | 0.183443E+11 | 23433.39 | 08-JUN-14:00 | 23.90 | 13.30 | 0.256936E+10 | 6153.88 | 09-JUN-14:20 | 14.07 | 12.92 |
| July | 0.144318E+11 | 18074.73 | 23-JUL-14:02 | 30.00 | 22.46 | 0.801755E+09 | 971.67 | 24-JUL-13:20 | 29.07 | 19.87 |
| August | 0.143108E+11 | 20839.07 | 12-AUG-13:11 | 21.30 | 16.51 | 0.898624E+09 | 971.69 | 25-AUG-13:20 | 27.57 | 18.63 |
| September | 0.144196E+11 | 23519.21 | 25-SEP-14:03 | 13.40 | 8.03 | 0.232129E+10 | 6153.96 | 20-SEP-14:20 | 13.40 | 8.03 |
| October | 0.118850E+11 | 24164.56 | 20-OCT-13:50 | 18.80 | 10.02 | 0.368723E+10 | 6153.96 | 03-OCT-14:20 | 18.80 | 10.02 |
| November | 0.722649E+10 | 13438.93 | 17-NOV-13:30 | 10.30 | 3.32 | 0.330739E+10 | 6153.42 | 17-NOV-14:30 | 10.60 | 3.43 |
| December | 0.317595E+10 | 9970.86 | 28-DEC-14:40 | -1.7 | -3.7 | 0.289710E+10 | 5057.70 | 28-DEC-14:50 | -1.7 | -3.7 |
| Annual Sum or Average | 0.123747E+12 | 0.332832E+11 | ||||||||
| Minimum of Months | 0.306827E+10 | 9970.86 | -14.4 | -15.6 | 0.801755E+09 | 971.67 | -14.4 | -15.6 | ||
| Maximum of Months | 0.183443E+11 | 26358.58 | 30.00 | 22.46 | 0.408328E+10 | 6159.01 | 29.07 | 19.87 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 94546357.11 | 863.67 | 26-JAN-21:11 | -19.3 | -19.9 | 0.239927E+09 | 366.73 | 30-JAN-10:39 | -7.2 | -7.5 |
| February | 0.115321E+09 | 1076.28 | 08-FEB-16:00 | 4.40 | -1.0 | 0.218413E+09 | 371.38 | 08-FEB-15:00 | 4.40 | -1.0 |
| March | 0.280283E+09 | 1244.42 | 31-MAR-15:00 | 8.30 | 2.63 | 0.266123E+09 | 404.39 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.828470E+09 | 2010.66 | 21-APR-14:01 | 11.28 | 2.93 | 0.244643E+09 | 461.67 | 21-APR-14:00 | 12.20 | 3.44 |
| May | 0.221529E+10 | 4664.61 | 18-MAY-15:00 | 28.90 | 16.60 | 0.318061E+09 | 495.45 | 23-MAY-12:09 | 24.05 | 16.59 |
| June | 0.289362E+10 | 4531.96 | 30-JUN-15:00 | 32.20 | 24.51 | 0.208300E+09 | 495.45 | 06-JUN-10:09 | 32.20 | 24.51 |
| July | 0.205866E+10 | 3167.98 | 24-JUL-14:50 | 29.40 | 19.36 | 69203652.03 | 78.23 | 21-JUL-15:50 | 29.40 | 19.36 |
| August | 0.195611E+10 | 2367.53 | 12-AUG-13:11 | 21.30 | 16.51 | 76245280.78 | 78.23 | 08-AUG-16:30 | 21.30 | 16.51 |
| September | 0.180473E+10 | 2879.05 | 05-SEP-15:50 | 16.78 | 9.85 | 0.184787E+09 | 495.44 | 26-SEP-14:20 | 13.17 | 11.16 |
| October | 0.115822E+10 | 2217.04 | 20-OCT-14:01 | 18.90 | 10.07 | 0.272940E+09 | 495.43 | 20-OCT-14:20 | 18.90 | 10.07 |
| November | 0.363734E+09 | 1275.78 | 01-NOV-15:00 | 18.30 | 13.44 | 0.244980E+09 | 410.41 | 01-NOV-14:00 | 18.30 | 13.44 |
| December | 0.133303E+09 | 868.02 | 21-DEC-21:11 | -15.5 | -16.2 | 0.229317E+09 | 366.71 | 12-DEC-15:09 | -15.5 | -16.2 |
| Annual Sum or Average | 0.139023E+11 | 0.257294E+10 | ||||||||
| Minimum of Months | 94546357.11 | 863.67 | -19.3 | -19.9 | 69203652.03 | 78.23 | -15.5 | -16.2 | ||
| Maximum of Months | 0.289362E+10 | 4664.61 | 32.20 | 24.51 | 0.318061E+09 | 495.45 | 32.20 | 24.51 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 69356434.73 | 1765.98 | 19-JAN-08:03 | -3.4 | -3.6 | 0.626840E+09 | 945.92 | 05-JAN-09:00 | -3.4 | -3.6 |
| February | 0.175000E+09 | 1936.06 | 08-FEB-16:00 | 4.40 | -1.0 | 0.567573E+09 | 1004.57 | 08-FEB-15:00 | 4.40 | -1.0 |
| March | 0.430507E+09 | 2093.41 | 31-MAR-15:00 | 8.30 | 2.63 | 0.688122E+09 | 1050.10 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.115286E+10 | 3297.43 | 13-APR-14:02 | 19.08 | 7.54 | 0.622149E+09 | 1201.56 | 13-APR-14:00 | 20.00 | 8.11 |
| May | 0.291124E+10 | 4937.48 | 18-MAY-15:00 | 28.90 | 16.60 | 0.804553E+09 | 1277.23 | 19-MAY-14:20 | 17.67 | 14.71 |
| June | 0.355435E+10 | 4625.01 | 08-JUN-15:00 | 23.90 | 13.85 | 0.523106E+09 | 1277.22 | 13-JUN-14:20 | 17.93 | 13.65 |
| July | 0.288858E+10 | 3662.42 | 16-JUL-16:39 | 21.67 | 15.89 | 0.162484E+09 | 201.68 | 24-JUL-17:19 | 28.70 | 19.19 |
| August | 0.269847E+10 | 3866.71 | 12-AUG-13:11 | 21.30 | 16.51 | 0.178164E+09 | 197.11 | 09-AUG-16:00 | 21.30 | 16.51 |
| September | 0.247839E+10 | 3726.44 | 18-SEP-14:02 | 19.40 | 16.89 | 0.455591E+09 | 1277.22 | 25-SEP-14:20 | 13.50 | 7.97 |
| October | 0.178378E+10 | 3659.42 | 20-OCT-14:01 | 18.90 | 10.07 | 0.696124E+09 | 1277.22 | 20-OCT-14:20 | 18.90 | 10.07 |
| November | 0.766047E+09 | 2355.97 | 01-NOV-15:00 | 18.30 | 13.44 | 0.638765E+09 | 1138.60 | 01-NOV-14:00 | 18.30 | 13.44 |
| December | 0.113391E+09 | 1778.46 | 06-DEC-08:03 | -3.3 | -3.3 | 0.597051E+09 | 945.95 | 11-DEC-11:30 | -21.0 | -21.5 |
| Annual Sum or Average | 0.190220E+11 | 0.656052E+10 | ||||||||
| Minimum of Months | 69356434.73 | 1765.98 | -3.4 | -3.6 | 0.162484E+09 | 197.11 | -21.0 | -21.5 | ||
| Maximum of Months | 0.355435E+10 | 4937.48 | 28.90 | 16.89 | 0.804553E+09 | 1277.23 | 28.70 | 19.19 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.109899E+10 | 8659.21 | 19-JAN-08:03 | -3.4 | -3.6 | 0.302042E+10 | 4559.00 | 19-JAN-14:50 | -2.8 | -3.6 |
| February | 0.196617E+10 | 9278.76 | 08-FEB-15:10 | 4.90 | -0.6 | 0.273581E+10 | 4830.36 | 08-FEB-15:20 | 4.80 | -0.7 |
| March | 0.400842E+10 | 10373.75 | 31-MAR-15:00 | 8.30 | 2.63 | 0.333859E+10 | 5180.42 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.698003E+10 | 16026.75 | 13-APR-14:02 | 19.08 | 7.54 | 0.309630E+10 | 5722.91 | 13-APR-14:00 | 20.00 | 8.11 |
| May | 0.142612E+11 | 19924.32 | 25-MAY-15:00 | 28.90 | 19.67 | 0.396931E+10 | 6153.91 | 19-MAY-14:20 | 28.90 | 19.67 |
| June | 0.167785E+11 | 19377.10 | 08-JUN-14:30 | 23.90 | 13.58 | 0.254130E+10 | 6153.87 | 13-JUN-14:20 | 17.93 | 13.65 |
| July | 0.129547E+11 | 17035.87 | 05-JUL-05:01 | 19.60 | 18.81 | 0.743572E+09 | 868.90 | 21-JUL-14:09 | 28.98 | 22.57 |
| August | 0.122999E+11 | 17838.62 | 12-AUG-13:11 | 21.30 | 16.51 | 0.824301E+09 | 855.02 | 09-AUG-15:00 | 21.30 | 16.51 |
| September | 0.120660E+11 | 17949.48 | 18-SEP-14:02 | 19.40 | 16.89 | 0.224025E+10 | 6153.96 | 21-SEP-14:20 | 9.80 | 7.98 |
| October | 0.974423E+10 | 17538.13 | 20-OCT-14:01 | 18.90 | 10.07 | 0.348327E+10 | 6151.53 | 20-OCT-14:50 | 18.90 | 10.07 |
| November | 0.540832E+10 | 11677.22 | 01-NOV-15:00 | 18.30 | 13.44 | 0.314179E+10 | 5599.31 | 01-NOV-14:00 | 18.30 | 13.44 |
| December | 0.189429E+10 | 8718.84 | 06-DEC-08:03 | -3.3 | -3.3 | 0.287669E+10 | 4574.63 | 06-DEC-14:50 | -6.7 | -6.8 |
| Annual Sum or Average | 0.994608E+11 | 0.320116E+11 | ||||||||
| Minimum of Months | 0.109899E+10 | 8659.21 | -3.4 | -3.6 | 0.743572E+09 | 855.02 | -6.7 | -6.8 | ||
| Maximum of Months | 0.167785E+11 | 19924.32 | 28.90 | 19.67 | 0.396931E+10 | 6153.96 | 28.98 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.272203E+09 | 2082.53 | 27-JAN-15:30 | -14.4 | -15.6 | 0.628569E+09 | 1056.38 | 27-JAN-15:39 | -14.4 | -15.6 |
| February | 0.541522E+09 | 2454.58 | 28-FEB-15:50 | 6.10 | 1.55 | 0.576765E+09 | 1181.65 | 28-FEB-15:00 | 6.10 | 1.55 |
| March | 0.899532E+09 | 2611.18 | 31-MAR-15:00 | 8.30 | 2.63 | 0.703700E+09 | 1231.18 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.159048E+10 | 3790.83 | 13-APR-15:00 | 20.00 | 8.11 | 0.666377E+09 | 1277.24 | 19-APR-14:20 | 6.70 | 0.87 |
| May | 0.329579E+10 | 6095.69 | 18-MAY-15:00 | 28.90 | 16.60 | 0.826386E+09 | 1277.23 | 19-MAY-14:20 | 17.67 | 14.71 |
| June | 0.384241E+10 | 5312.61 | 08-JUN-15:00 | 23.90 | 13.85 | 0.526954E+09 | 1277.22 | 13-JUN-14:20 | 17.93 | 13.65 |
| July | 0.315051E+10 | 4146.69 | 24-JUL-15:03 | 29.32 | 19.17 | 0.171241E+09 | 201.70 | 21-JUL-15:50 | 29.32 | 19.17 |
| August | 0.308083E+10 | 4380.28 | 12-AUG-13:11 | 21.30 | 16.51 | 0.190232E+09 | 201.70 | 25-AUG-15:39 | 28.30 | 19.34 |
| September | 0.294786E+10 | 5112.57 | 25-SEP-15:00 | 13.90 | 7.75 | 0.472211E+09 | 1277.24 | 27-SEP-14:20 | 8.90 | 6.19 |
| October | 0.221561E+10 | 5360.58 | 20-OCT-14:30 | 18.90 | 10.07 | 0.734788E+09 | 1277.24 | 02-OCT-14:20 | 18.90 | 10.07 |
| November | 0.107193E+10 | 2682.52 | 17-NOV-15:40 | 10.20 | 3.28 | 0.662456E+09 | 1259.16 | 17-NOV-15:39 | 10.20 | 3.28 |
| December | 0.261344E+09 | 1892.51 | 28-DEC-14:40 | -1.7 | -3.7 | 0.597483E+09 | 991.72 | 28-DEC-14:50 | -1.7 | -3.7 |
| Annual Sum or Average | 0.231700E+11 | 0.675716E+10 | ||||||||
| Minimum of Months | 0.261344E+09 | 1892.51 | -14.4 | -15.6 | 0.171241E+09 | 201.70 | -14.4 | -15.6 | ||
| Maximum of Months | 0.384241E+10 | 6095.69 | 29.32 | 19.17 | 0.826386E+09 | 1277.24 | 29.32 | 19.34 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.287424E+10 | 10275.91 | 27-JAN-14:40 | -14.4 | -15.6 | 0.304209E+10 | 5170.42 | 27-JAN-14:50 | -14.4 | -15.6 |
| February | 0.438877E+10 | 11723.08 | 08-FEB-15:10 | 4.90 | -0.6 | 0.282138E+10 | 5659.69 | 08-FEB-15:20 | 4.80 | -0.7 |
| March | 0.680950E+10 | 12839.74 | 31-MAR-14:40 | 8.30 | 2.79 | 0.348377E+10 | 6051.88 | 31-MAR-14:50 | 8.30 | 2.71 |
| April | 0.929695E+10 | 17547.14 | 18-APR-14:02 | 17.33 | 10.22 | 0.334464E+10 | 6158.93 | 20-APR-13:20 | 9.60 | 2.32 |
| May | 0.160896E+11 | 25814.03 | 18-MAY-13:50 | 28.45 | 16.75 | 0.407440E+10 | 6153.93 | 30-MAY-14:20 | 11.57 | 8.79 |
| June | 0.180141E+11 | 22716.70 | 08-JUN-14:00 | 23.90 | 13.30 | 0.256407E+10 | 6153.88 | 09-JUN-14:20 | 14.07 | 12.92 |
| July | 0.141546E+11 | 17806.22 | 01-JUL-10:31 | 21.50 | 16.30 | 0.790910E+09 | 964.65 | 24-JUL-13:20 | 29.07 | 19.87 |
| August | 0.140560E+11 | 20484.32 | 12-AUG-13:11 | 21.30 | 16.51 | 0.888719E+09 | 971.68 | 25-AUG-14:09 | 28.30 | 18.89 |
| September | 0.142221E+11 | 22931.86 | 25-SEP-14:03 | 13.40 | 8.03 | 0.231944E+10 | 6153.96 | 20-SEP-14:20 | 13.40 | 8.03 |
| October | 0.117811E+11 | 23583.42 | 20-OCT-13:50 | 18.80 | 10.02 | 0.368158E+10 | 6153.96 | 03-OCT-14:20 | 18.80 | 10.02 |
| November | 0.709653E+10 | 13040.58 | 17-NOV-13:20 | 10.20 | 3.29 | 0.329116E+10 | 6126.61 | 17-NOV-13:00 | 10.60 | 3.43 |
| December | 0.299837E+10 | 9740.16 | 28-DEC-14:10 | -1.7 | -3.6 | 0.289028E+10 | 4969.09 | 28-DEC-14:30 | -1.7 | -3.6 |
| Annual Sum or Average | 0.121782E+12 | 0.331924E+11 | ||||||||
| Minimum of Months | 0.287424E+10 | 9740.16 | -14.4 | -15.6 | 0.790910E+09 | 964.65 | -14.4 | -15.6 | ||
| Maximum of Months | 0.180141E+11 | 25814.03 | 28.45 | 16.75 | 0.407440E+10 | 6158.93 | 29.07 | 19.87 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 92635788.70 | 857.55 | 26-JAN-21:11 | -19.3 | -19.9 | 0.239692E+09 | 366.72 | 03-JAN-09:50 | -19.3 | -19.9 |
| February | 0.114239E+09 | 1069.81 | 08-FEB-16:00 | 4.40 | -1.0 | 0.218360E+09 | 370.99 | 08-FEB-15:00 | 4.40 | -1.0 |
| March | 0.276493E+09 | 1234.50 | 31-MAR-15:00 | 8.30 | 2.63 | 0.266068E+09 | 403.41 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.820209E+09 | 1999.45 | 21-APR-14:01 | 11.28 | 2.93 | 0.244407E+09 | 461.11 | 21-APR-14:00 | 12.20 | 3.44 |
| May | 0.219236E+10 | 4625.67 | 18-MAY-15:00 | 28.90 | 16.60 | 0.317649E+09 | 495.45 | 23-MAY-12:09 | 24.05 | 16.59 |
| June | 0.285422E+10 | 4485.49 | 30-JUN-15:00 | 32.20 | 24.51 | 0.208160E+09 | 495.45 | 06-JUN-10:09 | 32.20 | 24.51 |
| July | 0.202335E+10 | 3046.92 | 24-JUL-14:50 | 29.40 | 19.36 | 68886186.14 | 78.23 | 21-JUL-15:50 | 29.40 | 19.36 |
| August | 0.192988E+10 | 2342.41 | 12-AUG-13:11 | 21.30 | 16.51 | 75887918.32 | 78.23 | 08-AUG-16:30 | 21.30 | 16.51 |
| September | 0.178325E+10 | 2807.08 | 08-SEP-16:00 | 18.90 | 9.70 | 0.184685E+09 | 495.44 | 26-SEP-14:20 | 13.17 | 11.16 |
| October | 0.114894E+10 | 2207.27 | 20-OCT-14:01 | 18.90 | 10.07 | 0.272619E+09 | 495.43 | 20-OCT-14:20 | 18.90 | 10.07 |
| November | 0.353215E+09 | 1269.75 | 01-NOV-15:00 | 18.30 | 13.44 | 0.244886E+09 | 410.30 | 01-NOV-14:00 | 18.30 | 13.44 |
| December | 0.130545E+09 | 863.82 | 21-DEC-21:11 | -15.5 | -16.2 | 0.229138E+09 | 366.73 | 18-DEC-13:39 | -15.5 | -16.2 |
| Annual Sum or Average | 0.137194E+11 | 0.257044E+10 | ||||||||
| Minimum of Months | 92635788.70 | 857.55 | -19.3 | -19.9 | 68886186.14 | 78.23 | -19.3 | -19.9 | ||
| Maximum of Months | 0.285422E+10 | 4625.67 | 32.20 | 24.51 | 0.317649E+09 | 495.45 | 32.20 | 24.51 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 69406930.03 | 1767.24 | 19-JAN-08:03 | -3.4 | -3.6 | 0.626844E+09 | 946.02 | 09-JAN-10:00 | -3.4 | -3.6 |
| February | 0.175395E+09 | 1937.53 | 08-FEB-16:00 | 4.40 | -1.0 | 0.567575E+09 | 1004.59 | 08-FEB-15:00 | 4.40 | -1.0 |
| March | 0.431645E+09 | 2095.06 | 31-MAR-15:00 | 8.30 | 2.63 | 0.688130E+09 | 1050.14 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.115392E+10 | 3300.04 | 13-APR-14:02 | 19.08 | 7.54 | 0.622141E+09 | 1201.61 | 13-APR-14:00 | 20.00 | 8.11 |
| May | 0.291347E+10 | 4942.41 | 18-MAY-15:00 | 28.90 | 16.60 | 0.804535E+09 | 1277.23 | 19-MAY-14:20 | 17.67 | 14.71 |
| June | 0.355789E+10 | 4630.83 | 08-JUN-15:00 | 23.90 | 13.85 | 0.523124E+09 | 1277.22 | 13-JUN-14:20 | 17.93 | 13.65 |
| July | 0.288821E+10 | 3661.68 | 16-JUL-16:39 | 21.67 | 15.89 | 0.162395E+09 | 201.68 | 24-JUL-17:19 | 28.70 | 19.19 |
| August | 0.269656E+10 | 3867.72 | 12-AUG-13:11 | 21.30 | 16.51 | 0.178051E+09 | 197.01 | 09-AUG-16:00 | 21.30 | 16.51 |
| September | 0.247856E+10 | 3729.15 | 18-SEP-14:02 | 19.40 | 16.89 | 0.455502E+09 | 1277.22 | 25-SEP-14:20 | 13.50 | 7.97 |
| October | 0.178359E+10 | 3662.07 | 20-OCT-14:01 | 18.90 | 10.07 | 0.695965E+09 | 1277.22 | 20-OCT-14:20 | 18.90 | 10.07 |
| November | 0.765668E+09 | 2357.47 | 01-NOV-15:00 | 18.30 | 13.44 | 0.638729E+09 | 1138.51 | 01-NOV-14:00 | 18.30 | 13.44 |
| December | 0.113330E+09 | 1779.23 | 06-DEC-08:03 | -3.3 | -3.3 | 0.597052E+09 | 945.89 | 18-DEC-11:20 | -22.4 | -23.2 |
| Annual Sum or Average | 0.190277E+11 | 0.656004E+10 | ||||||||
| Minimum of Months | 69406930.03 | 1767.24 | -3.4 | -3.6 | 0.162395E+09 | 197.01 | -22.4 | -23.2 | ||
| Maximum of Months | 0.355789E+10 | 4942.41 | 28.90 | 16.89 | 0.804535E+09 | 1277.23 | 28.70 | 19.19 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.109891E+10 | 8651.15 | 19-JAN-08:03 | -3.4 | -3.6 | 0.302041E+10 | 4560.22 | 19-JAN-14:50 | -2.8 | -3.6 |
| February | 0.196920E+10 | 9276.60 | 08-FEB-15:10 | 4.90 | -0.6 | 0.273584E+10 | 4832.48 | 08-FEB-15:20 | 4.80 | -0.7 |
| March | 0.401344E+10 | 10371.48 | 31-MAR-15:00 | 8.30 | 2.63 | 0.333895E+10 | 5182.92 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.698084E+10 | 16020.12 | 13-APR-14:02 | 19.08 | 7.54 | 0.309715E+10 | 5725.78 | 13-APR-14:00 | 20.00 | 8.11 |
| May | 0.142627E+11 | 19947.00 | 25-MAY-15:00 | 28.90 | 19.67 | 0.397058E+10 | 6153.91 | 19-MAY-14:20 | 28.90 | 19.67 |
| June | 0.167839E+11 | 19410.05 | 08-JUN-14:30 | 23.90 | 13.58 | 0.254209E+10 | 6153.87 | 13-JUN-14:20 | 17.93 | 13.65 |
| July | 0.129405E+11 | 17004.17 | 05-JUL-05:01 | 19.60 | 18.81 | 0.743529E+09 | 869.14 | 21-JUL-14:09 | 28.98 | 22.57 |
| August | 0.122794E+11 | 17815.47 | 12-AUG-13:11 | 21.30 | 16.51 | 0.824081E+09 | 854.99 | 09-AUG-15:00 | 21.30 | 16.51 |
| September | 0.120560E+11 | 17933.30 | 18-SEP-14:02 | 19.40 | 16.89 | 0.224066E+10 | 6153.96 | 21-SEP-14:20 | 9.80 | 7.98 |
| October | 0.973650E+10 | 17526.97 | 20-OCT-14:01 | 18.90 | 10.07 | 0.348379E+10 | 6151.80 | 20-OCT-14:50 | 18.90 | 10.07 |
| November | 0.540171E+10 | 11673.04 | 01-NOV-15:00 | 18.30 | 13.44 | 0.314204E+10 | 5601.66 | 01-NOV-14:00 | 18.30 | 13.44 |
| December | 0.189140E+10 | 8711.02 | 06-DEC-08:03 | -3.3 | -3.3 | 0.287671E+10 | 4575.73 | 06-DEC-14:50 | -6.7 | -6.8 |
| Annual Sum or Average | 0.994145E+11 | 0.320158E+11 | ||||||||
| Minimum of Months | 0.109891E+10 | 8651.15 | -3.4 | -3.6 | 0.743529E+09 | 854.99 | -6.7 | -6.8 | ||
| Maximum of Months | 0.167839E+11 | 19947.00 | 28.90 | 19.67 | 0.397058E+10 | 6153.96 | 28.98 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.283582E+09 | 2115.66 | 27-JAN-15:30 | -14.4 | -15.6 | 0.628801E+09 | 1066.77 | 27-JAN-15:39 | -14.4 | -15.6 |
| February | 0.544329E+09 | 2458.61 | 28-FEB-15:50 | 6.10 | 1.55 | 0.576828E+09 | 1182.17 | 28-FEB-15:00 | 6.10 | 1.55 |
| March | 0.903353E+09 | 2617.50 | 31-MAR-15:00 | 8.30 | 2.63 | 0.703835E+09 | 1232.51 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.160339E+10 | 3818.33 | 13-APR-15:00 | 20.00 | 8.11 | 0.667254E+09 | 1277.24 | 19-APR-14:20 | 6.70 | 0.87 |
| May | 0.332119E+10 | 6121.63 | 18-MAY-15:00 | 28.90 | 16.60 | 0.827854E+09 | 1277.23 | 19-MAY-14:20 | 17.67 | 14.71 |
| June | 0.387189E+10 | 5341.94 | 08-JUN-15:00 | 23.90 | 13.85 | 0.527670E+09 | 1277.22 | 13-JUN-14:20 | 17.93 | 13.65 |
| July | 0.318295E+10 | 4202.87 | 24-JUL-15:03 | 29.32 | 19.17 | 0.171984E+09 | 201.70 | 21-JUL-15:50 | 29.32 | 19.17 |
| August | 0.311511E+10 | 5410.24 | 13-AUG-15:18 | 22.60 | 14.75 | 0.191011E+09 | 201.70 | 25-AUG-15:39 | 28.30 | 19.34 |
| September | 0.297661E+10 | 5163.18 | 25-SEP-15:00 | 13.90 | 7.75 | 0.473295E+09 | 1277.24 | 27-SEP-14:20 | 8.90 | 6.19 |
| October | 0.224098E+10 | 5402.13 | 20-OCT-14:30 | 18.90 | 10.07 | 0.736721E+09 | 1277.24 | 02-OCT-14:20 | 18.90 | 10.07 |
| November | 0.108575E+10 | 2694.43 | 17-NOV-15:40 | 10.20 | 3.28 | 0.663400E+09 | 1262.45 | 17-NOV-15:39 | 10.20 | 3.28 |
| December | 0.273259E+09 | 1914.91 | 28-DEC-14:40 | -1.7 | -3.7 | 0.597586E+09 | 998.35 | 28-DEC-14:50 | -1.7 | -3.7 |
| Annual Sum or Average | 0.234024E+11 | 0.676624E+10 | ||||||||
| Minimum of Months | 0.273259E+09 | 1914.91 | -14.4 | -15.6 | 0.171984E+09 | 201.70 | -14.4 | -15.6 | ||
| Maximum of Months | 0.387189E+10 | 6121.63 | 29.32 | 19.17 | 0.827854E+09 | 1277.24 | 29.32 | 19.34 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.296904E+10 | 10384.26 | 27-JAN-14:40 | -14.4 | -15.6 | 0.304498E+10 | 5205.76 | 27-JAN-14:50 | -14.4 | -15.6 |
| February | 0.441713E+10 | 11750.81 | 08-FEB-15:10 | 4.90 | -0.6 | 0.282269E+10 | 5667.92 | 08-FEB-15:20 | 4.80 | -0.7 |
| March | 0.683316E+10 | 12891.27 | 31-MAR-15:00 | 8.30 | 2.63 | 0.348586E+10 | 6068.68 | 31-MAR-14:50 | 8.30 | 2.63 |
| April | 0.939481E+10 | 17564.41 | 18-APR-14:02 | 17.33 | 10.22 | 0.335251E+10 | 6159.00 | 20-APR-13:20 | 9.60 | 2.32 |
| May | 0.162619E+11 | 26043.82 | 18-MAY-13:50 | 28.45 | 16.75 | 0.408455E+10 | 6153.93 | 30-MAY-14:20 | 11.57 | 8.79 |
| June | 0.182210E+11 | 22973.50 | 08-JUN-14:00 | 23.90 | 13.30 | 0.256906E+10 | 6153.88 | 09-JUN-14:20 | 14.07 | 12.92 |
| July | 0.143267E+11 | 17915.99 | 01-JUL-10:31 | 21.50 | 16.30 | 0.797205E+09 | 971.65 | 24-JUL-13:20 | 29.07 | 19.87 |
| August | 0.142486E+11 | 20668.83 | 12-AUG-13:11 | 21.30 | 16.51 | 0.895508E+09 | 971.69 | 25-AUG-14:09 | 28.30 | 18.89 |
| September | 0.144384E+11 | 23346.42 | 25-SEP-14:03 | 13.40 | 8.03 | 0.232626E+10 | 6153.96 | 20-SEP-14:20 | 13.40 | 8.03 |
| October | 0.120005E+11 | 24036.25 | 20-OCT-13:50 | 18.80 | 10.02 | 0.369966E+10 | 6153.96 | 03-OCT-14:20 | 18.80 | 10.02 |
| November | 0.722285E+10 | 13187.69 | 17-NOV-13:40 | 10.40 | 3.36 | 0.330163E+10 | 6152.62 | 17-NOV-13:00 | 10.60 | 3.43 |
| December | 0.308662E+10 | 9809.03 | 28-DEC-14:10 | -1.7 | -3.6 | 0.289259E+10 | 5001.22 | 28-DEC-14:39 | -1.7 | -3.7 |
| Annual Sum or Average | 0.123421E+12 | 0.332725E+11 | ||||||||
| Minimum of Months | 0.296904E+10 | 9809.03 | -14.4 | -15.6 | 0.797205E+09 | 971.65 | -14.4 | -15.6 | ||
| Maximum of Months | 0.182210E+11 | 26043.82 | 28.45 | 16.75 | 0.408455E+10 | 6159.00 | 29.07 | 19.87 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 95700288.22 | 869.88 | 26-JAN-21:11 | -19.3 | -19.9 | 0.239932E+09 | 366.73 | 23-JAN-13:09 | -19.3 | -19.9 |
| February | 0.119053E+09 | 1089.12 | 08-FEB-16:00 | 4.40 | -1.0 | 0.218471E+09 | 372.46 | 08-FEB-15:00 | 4.40 | -1.0 |
| March | 0.296987E+09 | 1265.17 | 31-MAR-15:00 | 8.30 | 2.63 | 0.266258E+09 | 406.97 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.879581E+09 | 2051.77 | 21-APR-14:01 | 11.28 | 2.93 | 0.246279E+09 | 467.86 | 21-APR-14:00 | 12.20 | 3.44 |
| May | 0.231410E+10 | 4816.28 | 18-MAY-15:00 | 28.90 | 16.60 | 0.320825E+09 | 495.45 | 23-MAY-12:09 | 24.05 | 16.59 |
| June | 0.307437E+10 | 4758.33 | 30-JUN-15:00 | 32.20 | 24.51 | 0.209297E+09 | 495.45 | 06-JUN-10:09 | 32.20 | 24.51 |
| July | 0.216403E+10 | 3452.67 | 24-JUL-14:40 | 29.40 | 19.47 | 70092019.82 | 78.23 | 21-JUL-15:50 | 29.40 | 19.47 |
| August | 0.203084E+10 | 2559.67 | 09-AUG-15:00 | 27.80 | 21.83 | 77347912.32 | 78.23 | 25-AUG-15:50 | 28.30 | 19.37 |
| September | 0.191886E+10 | 3164.25 | 08-SEP-15:50 | 18.98 | 9.79 | 0.186756E+09 | 495.44 | 20-SEP-14:20 | 9.27 | 7.66 |
| October | 0.123433E+10 | 2345.28 | 20-OCT-15:00 | 18.90 | 10.07 | 0.276400E+09 | 495.44 | 02-OCT-14:20 | 18.90 | 10.07 |
| November | 0.395168E+09 | 1309.52 | 01-NOV-15:00 | 18.30 | 13.44 | 0.245483E+09 | 415.72 | 01-NOV-14:00 | 18.30 | 13.44 |
| December | 0.134984E+09 | 875.82 | 21-DEC-21:11 | -15.5 | -16.2 | 0.229308E+09 | 366.73 | 18-DEC-12:50 | -15.5 | -16.2 |
| Annual Sum or Average | 0.146580E+11 | 0.258645E+10 | ||||||||
| Minimum of Months | 95700288.22 | 869.88 | -19.3 | -19.9 | 70092019.82 | 78.23 | -19.3 | -19.9 | ||
| Maximum of Months | 0.307437E+10 | 4816.28 | 32.20 | 24.51 | 0.320825E+09 | 495.45 | 32.20 | 24.51 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 71612952.05 | 1765.03 | 19-JAN-08:03 | -3.4 | -3.6 | 0.626852E+09 | 945.95 | 05-JAN-10:39 | -3.4 | -3.6 |
| February | 0.182288E+09 | 1945.24 | 08-FEB-16:00 | 4.40 | -1.0 | 0.567613E+09 | 1007.68 | 08-FEB-15:00 | 4.40 | -1.0 |
| March | 0.450208E+09 | 2112.91 | 31-MAR-15:00 | 8.30 | 2.63 | 0.688440E+09 | 1056.56 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.118489E+10 | 3323.23 | 13-APR-14:02 | 19.08 | 7.54 | 0.624302E+09 | 1210.79 | 13-APR-14:00 | 20.00 | 8.11 |
| May | 0.297481E+10 | 5053.36 | 18-MAY-15:00 | 28.90 | 16.60 | 0.809750E+09 | 1277.23 | 19-MAY-14:20 | 17.67 | 14.71 |
| June | 0.364148E+10 | 4761.59 | 08-JUN-15:00 | 23.90 | 13.85 | 0.526121E+09 | 1277.22 | 13-JUN-14:20 | 17.93 | 13.65 |
| July | 0.295601E+10 | 3737.28 | 16-JUL-16:39 | 21.67 | 15.89 | 0.164924E+09 | 201.68 | 24-JUL-16:40 | 28.90 | 18.95 |
| August | 0.275549E+10 | 3935.27 | 12-AUG-13:11 | 21.30 | 16.51 | 0.180096E+09 | 199.80 | 09-AUG-16:10 | 21.30 | 16.51 |
| September | 0.251449E+10 | 3730.20 | 18-SEP-14:02 | 19.40 | 16.89 | 0.458594E+09 | 1277.22 | 25-SEP-14:20 | 13.50 | 7.97 |
| October | 0.181356E+10 | 3661.75 | 20-OCT-14:01 | 18.90 | 10.07 | 0.699378E+09 | 1277.22 | 20-OCT-14:20 | 18.90 | 10.07 |
| November | 0.775675E+09 | 2367.58 | 01-NOV-15:00 | 18.30 | 13.44 | 0.639302E+09 | 1142.62 | 01-NOV-14:00 | 18.30 | 13.44 |
| December | 0.115920E+09 | 1777.27 | 06-DEC-08:03 | -3.3 | -3.3 | 0.597051E+09 | 945.93 | 26-DEC-11:39 | -21.2 | -21.7 |
| Annual Sum or Average | 0.194364E+11 | 0.658242E+10 | ||||||||
| Minimum of Months | 71612952.05 | 1765.03 | -3.4 | -3.6 | 0.164924E+09 | 199.80 | -21.2 | -21.7 | ||
| Maximum of Months | 0.364148E+10 | 5053.36 | 28.90 | 16.89 | 0.809750E+09 | 1277.23 | 28.90 | 18.95 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.722092E+09 | 5711.95 | 19-JAN-08:03 | -3.4 | -3.6 | 0.199463E+10 | 3015.60 | 19-JAN-14:50 | -2.8 | -3.6 |
| February | 0.131383E+10 | 6172.91 | 08-FEB-15:00 | 5.00 | -0.5 | 0.180696E+10 | 3205.49 | 08-FEB-15:09 | 4.90 | -0.6 |
| March | 0.268972E+10 | 6927.57 | 31-MAR-15:00 | 8.30 | 2.63 | 0.220760E+10 | 3447.95 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.471255E+10 | 10689.27 | 13-APR-14:02 | 19.08 | 7.54 | 0.205516E+10 | 3820.31 | 14-APR-13:09 | 16.10 | 7.12 |
| May | 0.967537E+10 | 13663.47 | 25-MAY-15:00 | 28.90 | 19.67 | 0.264188E+10 | 4063.90 | 19-MAY-14:20 | 28.90 | 19.67 |
| June | 0.114396E+11 | 13458.21 | 08-JUN-14:30 | 23.90 | 13.58 | 0.169087E+10 | 4063.88 | 09-JUN-14:20 | 14.07 | 12.92 |
| July | 0.885561E+10 | 11405.58 | 05-JUL-05:01 | 19.60 | 18.81 | 0.502176E+09 | 591.22 | 21-JUL-14:09 | 28.98 | 22.57 |
| August | 0.836850E+10 | 12071.72 | 12-AUG-13:11 | 21.30 | 16.51 | 0.552732E+09 | 577.09 | 09-AUG-15:00 | 21.30 | 16.51 |
| September | 0.813873E+10 | 11866.41 | 18-SEP-14:02 | 19.40 | 16.89 | 0.149040E+10 | 4063.94 | 20-SEP-14:20 | 9.27 | 7.66 |
| October | 0.655589E+10 | 11630.41 | 20-OCT-14:01 | 18.90 | 10.07 | 0.231659E+10 | 4063.74 | 20-OCT-14:20 | 18.90 | 10.07 |
| November | 0.358856E+10 | 7775.69 | 01-NOV-15:00 | 18.30 | 13.44 | 0.207812E+10 | 3721.39 | 01-NOV-14:00 | 18.30 | 13.44 |
| December | 0.123162E+10 | 5751.06 | 06-DEC-08:03 | -3.3 | -3.3 | 0.189972E+10 | 3023.64 | 06-DEC-14:39 | -6.6 | -6.8 |
| Annual Sum or Average | 0.672921E+11 | 0.212369E+11 | ||||||||
| Minimum of Months | 0.722092E+09 | 5711.95 | -3.4 | -3.6 | 0.502176E+09 | 577.09 | -6.6 | -6.8 | ||
| Maximum of Months | 0.114396E+11 | 13663.47 | 28.90 | 19.67 | 0.264188E+10 | 4063.94 | 28.98 | 22.57 |
Report: ZoneCoolingSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.775447E+09 | 3095.89 | 19-JAN-15:02 | -2.8 | -3.6 | 0.152002E+10 | 1618.35 | 19-JAN-15:09 | -2.8 | -3.6 |
| February | 0.133858E+10 | 3408.05 | 08-FEB-15:00 | 5.00 | -0.5 | 0.138158E+10 | 1725.52 | 08-FEB-15:09 | 4.90 | -0.6 |
| March | 0.248052E+10 | 3874.49 | 31-MAR-15:20 | 8.50 | 3.01 | 0.170913E+10 | 1881.42 | 31-MAR-15:30 | 8.60 | 3.20 |
| April | 0.335876E+10 | 5841.77 | 13-APR-14:02 | 19.08 | 7.54 | 0.165936E+10 | 2089.99 | 14-APR-15:20 | 15.00 | 6.95 |
| May | 0.606907E+10 | 8007.34 | 25-MAY-15:03 | 28.93 | 19.66 | 0.209366E+10 | 2092.60 | 31-MAY-10:30 | 9.70 | 7.35 |
| June | 0.781149E+10 | 8835.81 | 30-JUN-15:03 | 32.12 | 24.53 | 0.214449E+10 | 2090.12 | 29-JUN-17:19 | 32.12 | 24.53 |
| July | 0.525999E+10 | 6258.82 | 22-JUL-09:54 | 22.80 | 19.75 | 0.965738E+09 | 1099.99 | 21-JUL-16:19 | 22.80 | 19.75 |
| August | 0.514444E+10 | 6637.48 | 12-AUG-13:11 | 21.30 | 16.51 | 0.106694E+10 | 1099.98 | 09-AUG-16:10 | 21.30 | 16.51 |
| September | 0.552322E+10 | 7223.71 | 08-SEP-14:03 | 18.98 | 10.67 | 0.189086E+10 | 2091.86 | 21-SEP-15:39 | 9.40 | 8.36 |
| October | 0.420474E+10 | 6012.02 | 20-OCT-14:01 | 18.90 | 10.07 | 0.187820E+10 | 2090.03 | 04-OCT-14:20 | 18.90 | 10.07 |
| November | 0.292293E+10 | 4333.88 | 01-NOV-15:40 | 17.97 | 13.32 | 0.163198E+10 | 2033.22 | 01-NOV-15:50 | 17.88 | 13.29 |
| December | 0.128891E+10 | 3122.71 | 06-DEC-14:10 | -6.5 | -6.7 | 0.144975E+10 | 1628.11 | 06-DEC-14:50 | -6.7 | -6.8 |
| Annual Sum or Average | 0.461781E+11 | 0.193917E+11 | ||||||||
| Minimum of Months | 0.775447E+09 | 3095.89 | -6.5 | -6.7 | 0.965738E+09 | 1099.98 | -6.7 | -6.8 | ||
| Maximum of Months | 0.781149E+10 | 8835.81 | 32.12 | 24.53 | 0.214449E+10 | 2092.60 | 32.12 | 24.53 |
Report: ZoneCoolingSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.134603E+09 | 1826.99 | 26-JAN-21:11 | -19.3 | -19.9 | 0.670110E+09 | 1042.93 | 23-JAN-14:50 | -19.3 | -19.9 |
| February | 0.181499E+09 | 1813.98 | 01-FEB-21:11 | -25.4 | -25.8 | 0.618001E+09 | 1042.93 | 13-FEB-12:50 | -20.8 | -21.5 |
| March | 0.545174E+09 | 2654.98 | 31-MAR-15:00 | 8.30 | 2.63 | 0.755560E+09 | 1124.61 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.214715E+10 | 4620.86 | 21-APR-14:01 | 11.28 | 2.93 | 0.714510E+09 | 1354.30 | 21-APR-14:00 | 12.20 | 3.44 |
| May | 0.612777E+10 | 11970.16 | 25-MAY-15:00 | 28.90 | 19.67 | 0.941976E+09 | 1431.09 | 26-MAY-07:10 | 20.08 | 16.35 |
| June | 0.872138E+10 | 15841.19 | 30-JUN-07:03 | 26.02 | 21.73 | 0.603767E+09 | 1408.96 | 06-JUN-10:09 | 26.02 | 21.73 |
| July | 0.666922E+10 | 12107.38 | 24-JUL-07:03 | 20.97 | 18.41 | 0.207170E+09 | 228.46 | 24-JUL-07:10 | 20.97 | 18.41 |
| August | 0.542284E+10 | 8022.89 | 08-AUG-15:03 | 30.60 | 23.30 | 0.231809E+09 | 222.47 | 08-AUG-16:19 | 30.20 | 23.02 |
| September | 0.440991E+10 | 7460.59 | 05-SEP-15:40 | 16.87 | 9.89 | 0.534986E+09 | 1408.94 | 18-SEP-09:09 | 15.18 | 15.02 |
| October | 0.237052E+10 | 4834.32 | 02-OCT-14:01 | 10.00 | 9.40 | 0.761773E+09 | 1388.33 | 02-OCT-14:09 | 10.00 | 9.40 |
| November | 0.517608E+09 | 2707.72 | 01-NOV-15:00 | 18.30 | 13.44 | 0.692497E+09 | 1134.95 | 01-NOV-14:00 | 18.30 | 13.44 |
| December | 0.223743E+09 | 1845.94 | 21-DEC-21:11 | -15.5 | -16.2 | 0.643107E+09 | 1042.91 | 19-DEC-14:50 | -15.5 | -16.2 |
| Annual Sum or Average | 0.374714E+11 | 0.737527E+10 | ||||||||
| Minimum of Months | 0.134603E+09 | 1813.98 | -25.4 | -25.8 | 0.207170E+09 | 222.47 | -20.8 | -21.5 | ||
| Maximum of Months | 0.872138E+10 | 15841.19 | 30.60 | 23.30 | 0.941976E+09 | 1431.09 | 30.20 | 23.02 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 2632430.22 | 582.26 | 19-JAN-06:47 | -3.3 | -3.7 | 0.115408E+09 | 711.99 | 06-JAN-08:09 | -3.3 | -3.7 |
| February | 6445364.22 | 590.42 | 22-FEB-06:25 | -9.8 | -10.1 | 0.161993E+09 | 653.25 | 08-FEB-13:30 | -9.8 | -10.1 |
| March | 13531431.14 | 1350.84 | 23-MAR-17:06 | 0.40 | -3.6 | 0.263356E+09 | 653.23 | 29-MAR-12:00 | 2.80 | 0.04 |
| April | 0.275677E+09 | 2299.51 | 23-APR-15:12 | 25.97 | 16.64 | 0.348193E+09 | 757.57 | 18-APR-13:00 | 25.97 | 16.64 |
| May | 0.219409E+10 | 11431.61 | 18-MAY-15:00 | 28.90 | 16.60 | 0.500541E+09 | 1089.15 | 18-MAY-14:00 | 28.90 | 16.60 |
| June | 0.361572E+10 | 14438.95 | 29-JUN-15:00 | 34.40 | 24.01 | 0.335502E+09 | 882.58 | 08-JUN-14:39 | 34.40 | 24.01 |
| July | 0.342968E+10 | 11643.70 | 24-JUL-15:00 | 29.40 | 19.26 | 0.122565E+09 | 175.29 | 24-JUL-15:09 | 29.32 | 19.17 |
| August | 0.279215E+10 | 12299.59 | 08-AUG-15:00 | 30.60 | 23.36 | 0.132124E+09 | 185.20 | 08-AUG-15:09 | 30.60 | 23.30 |
| September | 0.134519E+10 | 9794.65 | 01-SEP-15:00 | 26.10 | 17.82 | 0.259776E+09 | 832.28 | 18-SEP-13:00 | 19.40 | 16.83 |
| October | 0.353215E+09 | 2709.87 | 22-OCT-14:02 | 19.40 | 12.77 | 0.393775E+09 | 882.35 | 19-OCT-14:09 | 19.40 | 12.77 |
| November | 21851905.13 | 1380.84 | 02-NOV-17:07 | 3.30 | 1.51 | 0.313399E+09 | 653.30 | 09-NOV-12:00 | 2.20 | -3.0 |
| December | 3658494.27 | 579.21 | 07-DEC-06:57 | -7.8 | -8.0 | 0.129053E+09 | 490.20 | 28-DEC-14:50 | -1.7 | -3.7 |
| Annual Sum or Average | 0.140538E+11 | 0.307568E+10 | ||||||||
| Minimum of Months | 2632430.22 | 579.21 | -9.8 | -10.1 | 0.115408E+09 | 175.29 | -9.8 | -10.1 | ||
| Maximum of Months | 0.361572E+10 | 14438.95 | 34.40 | 24.01 | 0.500541E+09 | 1089.15 | 34.40 | 24.01 |
Report: ZoneCoolingSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.123654E+10 | 1658.13 | 20-JAN-15:20 | -5.2 | -7.0 | 74150221.79 | 148.21 | 20-JAN-15:30 | -5.3 | -7.0 |
| February | 0.158397E+10 | 1874.95 | 08-FEB-15:20 | 4.80 | -0.7 | 76045953.22 | 160.07 | 08-FEB-15:30 | 4.70 | -0.8 |
| March | 0.236106E+10 | 2441.11 | 31-MAR-15:00 | 8.30 | 2.63 | 0.106032E+09 | 192.90 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.263230E+10 | 3822.79 | 21-APR-14:01 | 11.28 | 2.93 | 0.120050E+09 | 229.63 | 21-APR-14:00 | 12.20 | 3.44 |
| May | 0.415516E+10 | 12911.52 | 25-MAY-20:10 | 24.63 | 17.29 | 0.162188E+09 | 247.14 | 23-MAY-12:09 | 24.63 | 17.29 |
| June | 0.524579E+10 | 13809.74 | 26-JUN-20:11 | 18.90 | 17.09 | 0.104940E+09 | 247.13 | 06-JUN-10:09 | 18.90 | 17.09 |
| July | 0.399115E+10 | 13751.29 | 01-JUL-10:31 | 21.50 | 16.30 | 33803057.62 | 39.02 | 24-JUL-12:09 | 28.40 | 19.78 |
| August | 0.382146E+10 | 13853.83 | 12-AUG-13:11 | 21.30 | 16.51 | 36907462.64 | 37.49 | 08-AUG-13:00 | 21.30 | 16.51 |
| September | 0.338626E+10 | 11996.12 | 17-SEP-14:11 | 21.10 | 17.11 | 90213056.97 | 247.12 | 18-SEP-14:00 | 19.40 | 17.20 |
| October | 0.263393E+10 | 3881.93 | 02-OCT-14:01 | 10.00 | 9.40 | 0.129507E+09 | 230.05 | 02-OCT-14:09 | 10.00 | 9.40 |
| November | 0.209499E+10 | 2478.31 | 01-NOV-15:00 | 18.30 | 13.44 | 0.101998E+09 | 194.10 | 01-NOV-14:00 | 18.30 | 13.44 |
| December | 0.145322E+10 | 1676.10 | 07-DEC-14:10 | -8.1 | -8.1 | 74308612.04 | 148.81 | 07-DEC-14:50 | -8.3 | -8.3 |
| Annual Sum or Average | 0.345958E+11 | 0.111014E+10 | ||||||||
| Minimum of Months | 0.123654E+10 | 1658.13 | -8.1 | -8.1 | 33803057.62 | 37.49 | -8.3 | -8.3 | ||
| Maximum of Months | 0.524579E+10 | 13853.83 | 24.63 | 17.29 | 0.162188E+09 | 247.14 | 28.40 | 19.78 |
Report: ZoneCoolingSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.133315E+09 | 548.75 | 20-JAN-15:20 | -5.2 | -7.0 | 0.135045E+09 | 267.64 | 20-JAN-15:30 | -5.3 | -7.0 |
| February | 0.255179E+09 | 760.31 | 08-FEB-15:50 | 4.50 | -0.9 | 0.135656E+09 | 305.48 | 08-FEB-15:00 | 4.40 | -1.0 |
| March | 0.560144E+09 | 1118.35 | 31-MAR-15:00 | 8.30 | 2.63 | 0.187745E+09 | 372.73 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.109307E+10 | 2102.13 | 21-APR-14:01 | 11.28 | 2.93 | 0.229290E+09 | 477.23 | 21-APR-14:00 | 12.20 | 3.44 |
| May | 0.214584E+10 | 2781.88 | 18-MAY-15:13 | 28.77 | 16.51 | 0.349726E+09 | 620.97 | 18-MAY-14:09 | 28.77 | 16.51 |
| June | 0.271602E+10 | 5608.21 | 30-JUN-20:08 | 23.77 | 17.76 | 0.236173E+09 | 621.07 | 08-JUN-14:00 | 23.77 | 17.76 |
| July | 0.240963E+10 | 8122.51 | 29-JUL-17:30 | 29.15 | 21.27 | 79158884.77 | 97.41 | 24-JUL-17:10 | 29.15 | 21.27 |
| August | 0.227401E+10 | 2620.41 | 12-AUG-13:11 | 21.30 | 16.51 | 84901619.55 | 90.44 | 08-AUG-16:40 | 21.30 | 16.51 |
| September | 0.184397E+10 | 2511.33 | 08-SEP-14:01 | 18.98 | 10.67 | 0.192394E+09 | 545.11 | 18-SEP-14:50 | 19.40 | 17.14 |
| October | 0.128667E+10 | 2209.92 | 02-OCT-14:01 | 10.00 | 9.40 | 0.262604E+09 | 487.62 | 20-OCT-14:00 | 18.90 | 10.07 |
| November | 0.672032E+09 | 1246.43 | 01-NOV-15:00 | 18.30 | 13.44 | 0.191109E+09 | 398.90 | 01-NOV-14:00 | 18.30 | 13.44 |
| December | 0.187462E+09 | 562.43 | 06-DEC-14:10 | -6.5 | -6.7 | 0.134455E+09 | 269.41 | 06-DEC-14:50 | -6.7 | -6.8 |
| Annual Sum or Average | 0.155773E+11 | 0.221826E+10 | ||||||||
| Minimum of Months | 0.133315E+09 | 548.75 | -6.5 | -7.0 | 79158884.77 | 90.44 | -6.7 | -7.0 | ||
| Maximum of Months | 0.271602E+10 | 8122.51 | 29.15 | 21.27 | 0.349726E+09 | 621.07 | 29.15 | 21.27 |
Report: ZoneCoolingSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.117871E+09 | 3359.17 | 13-JAN-13:06 | -21.4 | -21.9 | 0.480427E+09 | 847.67 | 27-JAN-13:20 | -15.2 | -16.2 |
| February | 0.299369E+09 | 4156.53 | 08-FEB-15:01 | 4.90 | -0.6 | 0.438174E+09 | 990.83 | 08-FEB-15:09 | 4.90 | -0.6 |
| March | 0.101696E+10 | 12453.46 | 31-MAR-14:01 | 8.30 | 3.02 | 0.540399E+09 | 1156.95 | 31-MAR-14:09 | 8.30 | 3.02 |
| April | 0.338106E+10 | 23090.44 | 21-APR-14:01 | 11.28 | 2.93 | 0.535733E+09 | 1197.57 | 19-APR-14:09 | 11.28 | 2.93 |
| May | 0.863188E+10 | 23540.29 | 19-MAY-14:01 | 17.63 | 14.64 | 0.673146E+09 | 1197.66 | 23-MAY-12:09 | 24.05 | 16.59 |
| June | 0.125174E+11 | 25193.88 | 25-JUN-10:47 | 27.62 | 22.19 | 0.688891E+09 | 1216.05 | 28-JUN-07:10 | 23.17 | 20.20 |
| July | 0.101581E+11 | 26650.57 | 23-JUL-14:02 | 30.00 | 22.46 | 0.353556E+09 | 635.92 | 24-JUL-07:10 | 20.97 | 18.41 |
| August | 0.912945E+10 | 26061.72 | 13-AUG-15:18 | 22.60 | 14.75 | 0.401216E+09 | 630.31 | 10-AUG-14:09 | 22.60 | 14.75 |
| September | 0.821115E+10 | 23525.42 | 05-SEP-14:01 | 16.28 | 9.79 | 0.607487E+09 | 1197.60 | 11-SEP-14:09 | 18.98 | 14.79 |
| October | 0.421701E+10 | 23307.91 | 02-OCT-14:01 | 10.00 | 9.40 | 0.581042E+09 | 1197.57 | 18-OCT-12:09 | 13.68 | 9.55 |
| November | 0.134978E+10 | 5022.65 | 17-NOV-15:01 | 10.50 | 3.39 | 0.499914E+09 | 1139.29 | 17-NOV-15:09 | 10.50 | 3.39 |
| December | 0.170627E+09 | 3400.90 | 08-DEC-13:07 | -13.0 | -13.9 | 0.457945E+09 | 847.20 | 08-DEC-13:20 | -12.8 | -13.7 |
| Annual Sum or Average | 0.592007E+11 | 0.625793E+10 | ||||||||
| Minimum of Months | 0.117871E+09 | 3359.17 | -21.4 | -21.9 | 0.353556E+09 | 630.31 | -15.2 | -16.2 | ||
| Maximum of Months | 0.125174E+11 | 26650.57 | 30.00 | 22.46 | 0.688891E+09 | 1216.05 | 24.05 | 20.20 |
Report: ZoneCoolingSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.102291E+10 | 5481.49 | 19-JAN-17:00 | -2.8 | -3.6 | 0.246032E+10 | 4266.60 | 19-JAN-17:10 | -2.9 | -3.6 |
| February | 0.245412E+10 | 6142.78 | 08-FEB-17:00 | 3.30 | -1.3 | 0.224286E+10 | 4593.49 | 08-FEB-16:30 | 3.30 | -1.3 |
| March | 0.525895E+10 | 7773.11 | 31-MAR-16:00 | 8.90 | 3.77 | 0.286907E+10 | 5429.26 | 31-MAR-16:10 | 8.90 | 3.69 |
| April | 0.761943E+10 | 13249.63 | 21-APR-15:13 | 12.03 | 3.33 | 0.292399E+10 | 5528.16 | 24-APR-15:20 | 8.90 | 5.01 |
| May | 0.136609E+11 | 28132.29 | 25-MAY-05:01 | 16.68 | 13.73 | 0.345924E+10 | 5539.98 | 18-MAY-15:30 | 16.68 | 13.73 |
| June | 0.171641E+11 | 30102.27 | 19-JUN-05:01 | 17.80 | 16.77 | 0.347708E+10 | 5532.03 | 26-JUN-15:20 | 26.70 | 18.12 |
| July | 0.135246E+11 | 29817.57 | 03-JUL-05:01 | 17.98 | 16.78 | 0.190169E+10 | 2036.87 | 21-JUL-15:50 | 29.90 | 21.99 |
| August | 0.119854E+11 | 29711.08 | 07-AUG-05:01 | 13.80 | 12.30 | 0.214120E+10 | 2036.83 | 09-AUG-15:39 | 27.07 | 20.97 |
| September | 0.106549E+11 | 27498.90 | 19-SEP-05:01 | 15.60 | 15.30 | 0.307330E+10 | 5532.39 | 21-SEP-15:39 | 9.40 | 8.36 |
| October | 0.719298E+10 | 11828.34 | 19-OCT-15:10 | 22.12 | 13.61 | 0.303158E+10 | 5528.17 | 24-OCT-15:20 | 10.20 | 5.96 |
| November | 0.462641E+10 | 7706.38 | 01-NOV-15:40 | 17.97 | 13.32 | 0.261757E+10 | 5361.26 | 01-NOV-15:50 | 17.88 | 13.29 |
| December | 0.170422E+10 | 5430.66 | 06-DEC-17:00 | -7.0 | -7.2 | 0.234444E+10 | 4244.84 | 06-DEC-17:10 | -7.0 | -7.2 |
| Annual Sum or Average | 0.968689E+11 | 0.325423E+11 | ||||||||
| Minimum of Months | 0.102291E+10 | 5430.66 | -7.0 | -7.2 | 0.190169E+10 | 2036.83 | -7.0 | -7.2 | ||
| Maximum of Months | 0.171641E+11 | 30102.27 | 22.12 | 16.78 | 0.347708E+10 | 5539.98 | 29.90 | 21.99 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.636478E+10 | 82323.02 | 20-JAN-06:01 | -6.8 | -7.3 | 0.631282E+10 | 8101.85 | 17-JAN-12:20 | -6.8 | -7.3 |
| February | 0.635310E+10 | 38468.76 | 09-FEB-06:01 | -3.2 | -4.5 | 0.576086E+10 | 8101.87 | 15-FEB-12:20 | -12.8 | -14.1 |
| March | 0.901920E+10 | 83456.43 | 24-MAR-05:01 | -6.0 | -7.7 | 0.669462E+10 | 8101.99 | 13-MAR-11:20 | -6.0 | -7.7 |
| April | 0.113438E+11 | 81431.94 | 20-APR-05:01 | -4.1 | -6.7 | 0.617397E+10 | 8102.45 | 18-APR-11:09 | -4.1 | -6.7 |
| May | 0.170628E+11 | 79150.87 | 01-MAY-05:01 | -3.4 | -5.9 | 0.657073E+10 | 8143.06 | 26-MAY-10:00 | 24.10 | 19.21 |
| June | 0.178873E+11 | 52722.89 | 02-JUN-05:01 | 7.07 | 4.87 | 0.611503E+10 | 8102.56 | 12-JUN-10:20 | 17.40 | 14.55 |
| July | 0.161089E+11 | 46212.75 | 18-JUL-05:01 | 8.27 | 7.95 | 0.565780E+10 | 7040.47 | 05-JUL-10:50 | 8.27 | 7.95 |
| August | 0.159602E+11 | 46864.76 | 25-AUG-05:01 | 7.88 | 7.62 | 0.599186E+10 | 7012.60 | 31-AUG-09:00 | 18.90 | 17.78 |
| September | 0.148325E+11 | 62570.26 | 06-SEP-05:11 | 1.47 | 1.39 | 0.586067E+10 | 8102.58 | 18-SEP-10:30 | 17.20 | 15.80 |
| October | 0.123882E+11 | 79453.28 | 06-OCT-05:01 | -5.3 | -5.8 | 0.642753E+10 | 8102.48 | 19-OCT-11:09 | 16.47 | 11.42 |
| November | 0.900678E+10 | 85436.35 | 10-NOV-06:01 | -7.0 | -8.5 | 0.630946E+10 | 8102.51 | 01-NOV-11:00 | -7.0 | -8.5 |
| December | 0.695421E+10 | 45215.13 | 26-DEC-06:01 | -26.7 | -26.9 | 0.618777E+10 | 8101.91 | 27-DEC-12:20 | -6.5 | -7.0 |
| Annual Sum or Average | 0.143282E+12 | 0.740631E+11 | ||||||||
| Minimum of Months | 0.635310E+10 | 38468.76 | -26.7 | -26.9 | 0.565780E+10 | 7012.60 | -12.8 | -14.1 | ||
| Maximum of Months | 0.178873E+11 | 85436.35 | 8.27 | 7.95 | 0.669462E+10 | 8143.06 | 24.10 | 19.21 |
Report: ZoneCoolingSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.806457E+10 | 55297.96 | 09-JAN-15:01 | -15.7 | -16.9 | 0.713132E+10 | 12028.64 | 31-JAN-12:30 | -16.9 | -17.5 |
| February | 0.854162E+10 | 37310.47 | 14-FEB-06:49 | -33.0 | -33.2 | 0.645215E+10 | 12028.64 | 09-FEB-09:09 | -33.0 | -33.2 |
| March | 0.121189E+11 | 33495.76 | 30-MAR-07:01 | -2.7 | -3.2 | 0.781923E+10 | 13758.17 | 31-MAR-13:00 | 8.30 | 3.10 |
| April | 0.128683E+11 | 36039.42 | 13-APR-07:01 | -1.8 | -3.5 | 0.756012E+10 | 16257.48 | 18-APR-10:20 | 17.93 | 11.23 |
| May | 0.164846E+11 | 55079.51 | 25-MAY-05:01 | 16.68 | 13.73 | 0.973826E+10 | 16260.15 | 25-MAY-09:09 | 19.75 | 15.79 |
| June | 0.189032E+11 | 65517.00 | 17-JUN-18:41 | 22.48 | 12.85 | 0.100911E+11 | 17612.12 | 30-JUN-13:09 | 31.60 | 24.35 |
| July | 0.918278E+10 | 65737.27 | 17-JUL-05:01 | 11.88 | 11.25 | 0.233733E+10 | 5990.09 | 06-JUL-16:00 | 11.88 | 11.25 |
| August | 0.897966E+10 | 62455.53 | 07-AUG-05:01 | 13.80 | 12.30 | 0.261165E+10 | 5990.04 | 11-AUG-16:40 | 26.30 | 19.42 |
| September | 0.151499E+11 | 49322.15 | 01-SEP-05:01 | 15.68 | 15.63 | 0.847556E+10 | 16260.49 | 18-SEP-11:09 | 18.48 | 16.57 |
| October | 0.149004E+11 | 38326.96 | 25-OCT-07:01 | -3.2 | -3.4 | 0.786296E+10 | 16258.81 | 19-OCT-13:09 | -3.2 | -3.4 |
| November | 0.119525E+11 | 36105.28 | 17-NOV-08:61 | -2.9 | -4.2 | 0.741471E+10 | 16257.57 | 01-NOV-13:00 | -2.9 | -4.2 |
| December | 0.825706E+10 | 67930.31 | 20-DEC-19:11 | -23.5 | -23.9 | 0.679172E+10 | 12028.64 | 05-DEC-09:09 | -23.5 | -23.9 |
| Annual Sum or Average | 0.145404E+12 | 0.842861E+11 | ||||||||
| Minimum of Months | 0.806457E+10 | 33495.76 | -33.0 | -33.2 | 0.233733E+10 | 5990.04 | -33.0 | -33.2 | ||
| Maximum of Months | 0.189032E+11 | 67930.31 | 22.48 | 15.63 | 0.100911E+11 | 17612.12 | 31.60 | 24.35 |
Report: ZoneCoolingSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.246251E+09 | 3453.01 | 19-JAN-14:10 | -2.8 | -3.6 | 0.101052E+10 | 1531.11 | 19-JAN-14:50 | -2.8 | -3.6 |
| February | 0.621706E+09 | 3985.23 | 08-FEB-15:10 | 4.90 | -0.6 | 0.916801E+09 | 1678.06 | 08-FEB-15:20 | 4.80 | -0.7 |
| March | 0.190515E+10 | 4838.07 | 31-MAR-15:00 | 8.30 | 2.63 | 0.113553E+10 | 1913.64 | 31-MAR-14:00 | 8.30 | 2.63 |
| April | 0.435650E+10 | 8417.62 | 14-APR-12:40 | 15.93 | 7.12 | 0.115380E+10 | 2060.39 | 20-APR-13:20 | 9.60 | 2.32 |
| May | 0.105061E+11 | 16778.53 | 18-MAY-14:03 | 28.57 | 16.73 | 0.141852E+10 | 2104.26 | 26-MAY-07:10 | 20.08 | 16.35 |
| June | 0.141786E+11 | 24317.98 | 28-JUN-07:03 | 23.17 | 20.20 | 0.884184E+09 | 2194.77 | 07-JUN-07:10 | 23.17 | 20.20 |
| July | 0.993194E+10 | 15469.51 | 24-JUL-07:03 | 20.97 | 18.41 | 0.303762E+09 | 337.59 | 24-JUL-07:10 | 20.97 | 18.41 |
| August | 0.872895E+10 | 11295.83 | 08-AUG-14:30 | 30.30 | 23.11 | 0.343478E+09 | 325.19 | 09-AUG-15:39 | 27.07 | 20.97 |
| September | 0.901447E+10 | 13148.25 | 18-SEP-13:40 | 19.40 | 16.83 | 0.802069E+09 | 2059.35 | 26-SEP-07:49 | 9.22 | 8.08 |
| October | 0.567979E+10 | 10314.44 | 20-OCT-14:03 | 18.90 | 10.07 | 0.128295E+10 | 2059.33 | 02-OCT-08:09 | 18.90 | 10.07 |
| November | 0.261853E+10 | 5892.14 | 01-NOV-15:00 | 18.30 | 13.44 | 0.108721E+10 | 2059.25 | 01-NOV-14:20 | 18.30 | 13.44 |
| December | 0.512401E+09 | 3496.57 | 06-DEC-08:03 | -3.3 | -3.3 | 0.962567E+09 | 1537.84 | 06-DEC-14:39 | -6.6 | -6.8 |
| Annual Sum or Average | 0.683004E+11 | 0.113014E+11 | ||||||||
| Minimum of Months | 0.246251E+09 | 3453.01 | -3.3 | -3.6 | 0.303762E+09 | 325.19 | -6.6 | -6.8 | ||
| Maximum of Months | 0.141786E+11 | 24317.98 | 30.30 | 23.11 | 0.141852E+10 | 2194.77 | 27.07 | 20.97 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.400274E+10 | 10114.05 | 09-JAN-00:21 | -30.0 |
| February | 0.239370E+10 | 10036.36 | 13-FEB-04:12 | -23.0 |
| March | 0.161534E+10 | 9811.65 | 05-MAR-05:52 | -27.2 |
| April | 0.385439E+09 | 9217.17 | 03-APR-05:11 | -4.2 |
| May | 34375616.26 | 8826.91 | 01-MAY-05:01 | -3.4 |
| June | 1023165.75 | 5446.09 | 12-JUN-07:01 | 13.22 |
| July | 1494862.16 | 6426.23 | 10-JUL-07:01 | 15.37 |
| August | 1991275.85 | 7286.55 | 18-AUG-07:01 | 11.28 |
| September | 1598437.60 | 6852.44 | 29-SEP-07:01 | 7.88 |
| October | 53310747.28 | 9014.76 | 30-OCT-05:01 | -9.9 |
| November | 0.802301E+09 | 9238.51 | 29-NOV-06:11 | -20.0 |
| December | 0.341387E+10 | 10145.92 | 25-DEC-06:31 | -28.9 |
| Annual Sum or Average | 0.127072E+11 | |||
| Minimum of Months | 1023165.75 | 5446.09 | -30.0 | |
| Maximum of Months | 0.400274E+10 | 10145.92 | 15.37 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.906855E+10 | 36718.02 | 09-JAN-00:21 | -30.0 |
| February | 0.457348E+10 | 36163.03 | 13-FEB-04:12 | -23.0 |
| March | 0.280500E+10 | 35555.80 | 05-MAR-05:52 | -27.2 |
| April | 0.515883E+09 | 33108.40 | 03-APR-05:11 | -4.2 |
| May | 52207171.55 | 30301.52 | 01-MAY-05:01 | -3.4 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 4664338.40 | 22501.11 | 10-JUL-07:01 | 15.37 |
| August | 7699289.31 | 26398.70 | 18-AUG-07:01 | 11.28 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
| October | 71535650.48 | 31723.34 | 30-OCT-05:01 | -9.9 |
| November | 0.147969E+10 | 33751.43 | 29-NOV-06:11 | -20.0 |
| December | 0.743466E+10 | 36775.15 | 25-DEC-06:31 | -28.9 |
| Annual Sum or Average | 0.260134E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -30.0 | |
| Maximum of Months | 0.906855E+10 | 36775.15 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.545950E+10 | 8241.35 | 09-JAN-00:21 | -30.0 |
| February | 0.338134E+10 | 8106.37 | 13-FEB-04:12 | -23.0 |
| March | 0.249245E+10 | 8050.77 | 05-MAR-07:52 | -26.7 |
| April | 0.551947E+09 | 7722.93 | 03-APR-05:11 | -4.2 |
| May | 43063971.12 | 7182.12 | 01-MAY-05:01 | -3.4 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
| August | 287238.55 | 4787.31 | 18-AUG-07:01 | 11.28 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
| October | 99706974.42 | 7300.49 | 30-OCT-05:01 | -9.9 |
| November | 0.154822E+10 | 7795.77 | 27-NOV-06:01 | -7.1 |
| December | 0.459034E+10 | 8247.23 | 25-DEC-06:31 | -28.9 |
| Annual Sum or Average | 0.181669E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -30.0 | |
| Maximum of Months | 0.545950E+10 | 8247.23 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.507837E+10 | 9248.55 | 09-JAN-00:21 | -30.0 |
| February | 0.331058E+10 | 9198.33 | 13-FEB-04:12 | -23.0 |
| March | 0.230075E+10 | 8957.37 | 06-MAR-03:12 | -16.5 |
| April | 0.569190E+09 | 8700.61 | 03-APR-05:11 | -4.2 |
| May | 50931019.10 | 8329.63 | 01-MAY-05:01 | -3.4 |
| June | 1225593.92 | 5412.85 | 12-JUN-07:01 | 13.22 |
| July | 2382198.38 | 6700.95 | 18-JUL-07:01 | 14.97 |
| August | 5957755.17 | 6804.96 | 16-AUG-07:01 | 13.07 |
| September | 4561583.87 | 6748.03 | 13-SEP-07:01 | 7.15 |
| October | 82240959.10 | 8269.99 | 30-OCT-05:01 | -9.9 |
| November | 0.107638E+10 | 8465.01 | 29-NOV-06:11 | -20.0 |
| December | 0.420217E+10 | 9293.91 | 25-DEC-05:51 | -29.4 |
| Annual Sum or Average | 0.166847E+11 | |||
| Minimum of Months | 1225593.92 | 5412.85 | -30.0 | |
| Maximum of Months | 0.507837E+10 | 9293.91 | 14.97 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.125038E+11 | 35675.60 | 09-JAN-00:21 | -30.0 |
| February | 0.754311E+10 | 35260.00 | 13-FEB-04:12 | -23.0 |
| March | 0.479704E+10 | 34471.06 | 06-MAR-03:12 | -16.5 |
| April | 0.850669E+09 | 32660.12 | 03-APR-05:11 | -4.2 |
| May | 84482213.13 | 30544.36 | 01-MAY-05:01 | -3.4 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 10899785.18 | 25070.82 | 10-JUL-07:01 | 15.37 |
| August | 27646170.33 | 25602.51 | 18-AUG-07:01 | 11.28 |
| September | 5170407.54 | 19535.62 | 13-SEP-07:01 | 7.15 |
| October | 0.115782E+09 | 31196.48 | 30-OCT-05:01 | -9.9 |
| November | 0.202913E+10 | 32750.62 | 29-NOV-06:11 | -20.0 |
| December | 0.100016E+11 | 35824.12 | 25-DEC-05:51 | -29.4 |
| Annual Sum or Average | 0.379694E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -30.0 | |
| Maximum of Months | 0.125038E+11 | 35824.12 | 15.37 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.412211E+10 | 10051.89 | 09-JAN-00:21 | -30.0 |
| February | 0.241648E+10 | 9969.87 | 13-FEB-04:12 | -23.0 |
| March | 0.162413E+10 | 9745.51 | 05-MAR-05:52 | -27.2 |
| April | 0.391158E+09 | 9162.39 | 03-APR-05:11 | -4.2 |
| May | 35703288.49 | 8780.80 | 01-MAY-05:01 | -3.4 |
| June | 1301022.71 | 6398.47 | 12-JUN-07:01 | 13.22 |
| July | 1823475.50 | 7096.79 | 10-JUL-07:01 | 15.37 |
| August | 2261187.86 | 7246.94 | 18-AUG-07:01 | 11.28 |
| September | 1685943.92 | 7025.15 | 29-SEP-07:01 | 7.88 |
| October | 54743571.56 | 8958.16 | 30-OCT-05:01 | -9.9 |
| November | 0.818788E+09 | 9181.09 | 29-NOV-06:11 | -20.0 |
| December | 0.354461E+10 | 10085.99 | 25-DEC-06:31 | -28.9 |
| Annual Sum or Average | 0.130148E+11 | |||
| Minimum of Months | 1301022.71 | 6398.47 | -30.0 | |
| Maximum of Months | 0.412211E+10 | 10085.99 | 15.37 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.928395E+10 | 36319.03 | 09-JAN-00:21 | -30.0 |
| February | 0.449042E+10 | 35720.22 | 13-FEB-04:12 | -23.0 |
| March | 0.271547E+10 | 35089.82 | 05-MAR-05:52 | -27.2 |
| April | 0.498816E+09 | 32727.45 | 03-APR-05:11 | -4.2 |
| May | 52722876.16 | 29981.12 | 01-MAY-05:01 | -3.4 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 6269942.81 | 25325.63 | 10-JUL-07:01 | 15.37 |
| August | 8919685.27 | 26117.48 | 18-AUG-07:01 | 11.28 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
| October | 68517123.98 | 31281.94 | 30-OCT-05:01 | -9.9 |
| November | 0.146773E+10 | 33359.91 | 29-NOV-06:11 | -20.0 |
| December | 0.773730E+10 | 36395.89 | 25-DEC-06:31 | -28.9 |
| Annual Sum or Average | 0.263301E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -30.0 | |
| Maximum of Months | 0.928395E+10 | 36395.89 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.553843E+10 | 8199.64 | 09-JAN-00:21 | -30.0 |
| February | 0.339412E+10 | 8083.22 | 13-FEB-04:12 | -23.0 |
| March | 0.249576E+10 | 8005.36 | 05-MAR-07:52 | -26.7 |
| April | 0.553613E+09 | 7718.76 | 03-APR-05:11 | -4.2 |
| May | 43911474.35 | 7170.41 | 01-MAY-05:01 | -3.4 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
| August | 310511.89 | 5175.20 | 18-AUG-07:01 | 11.28 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
| October | 0.101279E+09 | 7257.53 | 30-OCT-05:01 | -9.9 |
| November | 0.157367E+10 | 7773.11 | 27-NOV-06:01 | -7.1 |
| December | 0.468381E+10 | 8206.93 | 25-DEC-06:31 | -28.9 |
| Annual Sum or Average | 0.183849E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -30.0 | |
| Maximum of Months | 0.553843E+10 | 8206.93 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.508250E+10 | 9254.10 | 09-JAN-00:21 | -30.0 |
| February | 0.331038E+10 | 9203.42 | 13-FEB-04:12 | -23.0 |
| March | 0.229993E+10 | 8962.19 | 06-MAR-03:12 | -16.5 |
| April | 0.569207E+09 | 8705.76 | 03-APR-05:11 | -4.2 |
| May | 50954974.88 | 8334.40 | 01-MAY-05:01 | -3.4 |
| June | 1223559.64 | 5387.59 | 12-JUN-07:01 | 13.22 |
| July | 2431304.62 | 6707.73 | 18-JUL-07:01 | 14.97 |
| August | 6050948.63 | 6807.94 | 16-AUG-07:01 | 13.07 |
| September | 4627281.72 | 6751.47 | 13-SEP-07:01 | 7.15 |
| October | 82438392.82 | 8274.67 | 30-OCT-05:01 | -9.9 |
| November | 0.107830E+10 | 8469.96 | 29-NOV-06:11 | -20.0 |
| December | 0.420751E+10 | 9308.39 | 24-DEC-09:11 | -30.7 |
| Annual Sum or Average | 0.166956E+11 | |||
| Minimum of Months | 1223559.64 | 5387.59 | -30.7 | |
| Maximum of Months | 0.508250E+10 | 9308.39 | 14.97 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.125217E+11 | 35662.72 | 09-JAN-00:21 | -30.0 |
| February | 0.754297E+10 | 35246.10 | 13-FEB-04:12 | -23.0 |
| March | 0.479473E+10 | 34456.71 | 06-MAR-03:12 | -16.5 |
| April | 0.850549E+09 | 32649.72 | 03-APR-05:11 | -4.2 |
| May | 84397565.33 | 30535.00 | 01-MAY-05:01 | -3.4 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 11054639.48 | 25077.45 | 18-JUL-07:01 | 14.97 |
| August | 28079348.51 | 25596.47 | 18-AUG-07:01 | 11.28 |
| September | 5326208.12 | 19834.12 | 13-SEP-07:01 | 7.15 |
| October | 0.115950E+09 | 31187.79 | 30-OCT-05:01 | -9.9 |
| November | 0.203403E+10 | 32740.35 | 29-NOV-06:11 | -20.0 |
| December | 0.100233E+11 | 35812.24 | 25-DEC-05:51 | -29.4 |
| Annual Sum or Average | 0.380120E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -30.0 | |
| Maximum of Months | 0.125217E+11 | 35812.24 | 14.97 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.408462E+10 | 10057.39 | 09-JAN-00:21 | -30.0 |
| February | 0.240998E+10 | 9977.01 | 13-FEB-04:12 | -23.0 |
| March | 0.162085E+10 | 9752.75 | 05-MAR-05:52 | -27.2 |
| April | 0.385925E+09 | 9166.12 | 03-APR-05:11 | -4.2 |
| May | 34486387.74 | 8778.47 | 01-MAY-05:01 | -3.4 |
| June | 1102484.96 | 5769.64 | 12-JUN-07:01 | 13.22 |
| July | 1582100.48 | 6682.32 | 10-JUL-07:01 | 15.37 |
| August | 1994566.65 | 7250.92 | 18-AUG-07:01 | 11.28 |
| September | 1446779.98 | 6391.30 | 29-SEP-07:01 | 7.88 |
| October | 51051687.17 | 8962.89 | 30-OCT-05:01 | -9.9 |
| November | 0.807543E+09 | 9186.50 | 29-NOV-06:11 | -20.0 |
| December | 0.350584E+10 | 10090.72 | 25-DEC-06:31 | -28.9 |
| Annual Sum or Average | 0.129064E+11 | |||
| Minimum of Months | 1102484.96 | 5769.64 | -30.0 | |
| Maximum of Months | 0.408462E+10 | 10090.72 | 15.37 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.913991E+10 | 36450.08 | 09-JAN-00:21 | -30.0 |
| February | 0.447892E+10 | 35863.72 | 13-FEB-04:12 | -23.0 |
| March | 0.272461E+10 | 35236.28 | 05-MAR-05:52 | -27.2 |
| April | 0.495396E+09 | 32856.09 | 03-APR-05:11 | -4.2 |
| May | 49694413.35 | 30008.88 | 01-MAY-05:01 | -3.4 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 4589152.62 | 22423.28 | 10-JUL-07:01 | 15.37 |
| August | 7122429.86 | 26199.36 | 18-AUG-07:01 | 11.28 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
| October | 63635820.32 | 31246.10 | 30-OCT-05:01 | -9.9 |
| November | 0.144529E+10 | 33477.24 | 29-NOV-06:11 | -20.0 |
| December | 0.759744E+10 | 36524.28 | 25-DEC-06:31 | -28.9 |
| Annual Sum or Average | 0.260066E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -30.0 | |
| Maximum of Months | 0.913991E+10 | 36524.28 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.547612E+10 | 8297.39 | 09-JAN-00:21 | -30.0 |
| February | 0.334754E+10 | 8158.85 | 13-FEB-04:12 | -23.0 |
| March | 0.244205E+10 | 8100.83 | 05-MAR-07:52 | -26.7 |
| April | 0.524848E+09 | 7755.00 | 03-APR-05:11 | -4.2 |
| May | 37539811.94 | 7166.11 | 01-MAY-05:01 | -3.4 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
| August | 48552.89 | 809.21 | 18-AUG-07:01 | 11.28 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
| October | 75830520.72 | 7039.01 | 30-OCT-06:01 | -9.4 |
| November | 0.150382E+10 | 7826.08 | 27-NOV-06:01 | -7.1 |
| December | 0.461870E+10 | 8304.73 | 25-DEC-06:31 | -28.9 |
| Annual Sum or Average | 0.180265E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -30.0 | |
| Maximum of Months | 0.547612E+10 | 8304.73 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.507594E+10 | 9341.41 | 09-JAN-00:21 | -30.0 |
| February | 0.329559E+10 | 9289.11 | 13-FEB-04:12 | -23.0 |
| March | 0.228091E+10 | 9045.09 | 05-MAR-05:52 | -27.2 |
| April | 0.554465E+09 | 8759.87 | 03-APR-05:11 | -4.2 |
| May | 47635337.24 | 8366.42 | 01-MAY-05:01 | -3.4 |
| June | 769056.97 | 3745.73 | 12-JUN-07:01 | 13.22 |
| July | 1676479.47 | 6728.74 | 18-JUL-07:01 | 14.97 |
| August | 4937788.97 | 6866.66 | 16-AUG-07:01 | 13.07 |
| September | 4019582.22 | 6785.14 | 13-SEP-07:01 | 7.15 |
| October | 78609198.45 | 8349.82 | 30-OCT-05:01 | -9.9 |
| November | 0.107314E+10 | 8549.47 | 29-NOV-06:11 | -20.0 |
| December | 0.420625E+10 | 9393.62 | 24-DEC-09:11 | -30.7 |
| Annual Sum or Average | 0.166239E+11 | |||
| Minimum of Months | 769056.97 | 3745.73 | -30.7 | |
| Maximum of Months | 0.507594E+10 | 9393.62 | 14.97 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.849821E+10 | 23796.26 | 09-JAN-00:21 | -30.0 |
| February | 0.511430E+10 | 23517.58 | 13-FEB-04:12 | -23.0 |
| March | 0.324527E+10 | 22988.64 | 06-MAR-03:12 | -16.5 |
| April | 0.567954E+09 | 21779.74 | 03-APR-05:11 | -4.2 |
| May | 51677541.21 | 20308.16 | 01-MAY-05:01 | -3.4 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 4086503.28 | 15254.86 | 18-JUL-07:01 | 14.97 |
| August | 14407341.17 | 17103.58 | 18-AUG-07:01 | 11.28 |
| September | 1532010.30 | 8175.94 | 06-SEP-07:01 | 4.05 |
| October | 75146107.64 | 20782.52 | 30-OCT-05:01 | -9.9 |
| November | 0.139280E+10 | 21847.30 | 29-NOV-06:11 | -20.0 |
| December | 0.682354E+10 | 23897.28 | 25-DEC-05:51 | -29.4 |
| Annual Sum or Average | 0.257889E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -30.0 | |
| Maximum of Months | 0.849821E+10 | 23897.28 | 14.97 |
Report: ZoneHeatingSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.300554E+10 | 11977.62 | 09-JAN-00:21 | -30.0 |
| February | 0.173951E+10 | 11830.33 | 13-FEB-04:12 | -23.0 |
| March | 0.108271E+10 | 11558.47 | 06-MAR-03:12 | -16.5 |
| April | 0.182129E+09 | 10889.83 | 03-APR-05:11 | -4.2 |
| May | 14766421.16 | 9878.52 | 01-MAY-05:01 | -3.4 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
| August | 727038.05 | 8443.80 | 18-AUG-07:01 | 11.28 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
| October | 19523367.83 | 10153.72 | 30-OCT-05:01 | -9.9 |
| November | 0.436464E+09 | 10969.66 | 29-NOV-06:11 | -20.0 |
| December | 0.246804E+10 | 12028.50 | 25-DEC-05:51 | -29.4 |
| Annual Sum or Average | 0.894942E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -30.0 | |
| Maximum of Months | 0.300554E+10 | 12028.50 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.157034E+11 | 18279.89 | 09-JAN-00:21 | -30.0 |
| February | 0.959259E+10 | 17928.68 | 13-FEB-04:12 | -23.0 |
| March | 0.627790E+10 | 17737.08 | 06-MAR-03:12 | -16.5 |
| April | 0.872938E+09 | 16646.21 | 03-APR-05:11 | -4.2 |
| May | 31476114.56 | 15545.31 | 01-MAY-06:01 | -3.5 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
| October | 0.220792E+09 | 15887.69 | 30-OCT-06:01 | -9.4 |
| November | 0.443451E+10 | 17572.26 | 27-NOV-06:01 | -7.1 |
| December | 0.131193E+11 | 18290.92 | 25-DEC-06:31 | -28.9 |
| Annual Sum or Average | 0.502529E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -30.0 | |
| Maximum of Months | 0.157034E+11 | 18290.92 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.181818E+11 | 24857.52 | 06-JAN-07:10 | -35.0 |
| February | 0.133671E+11 | 24212.05 | 14-FEB-07:10 | -33.0 |
| March | 0.125302E+11 | 20362.25 | 07-MAR-07:10 | -20.8 |
| April | 0.582242E+10 | 17275.35 | 05-APR-06:10 | -13.5 |
| May | 0.191963E+10 | 14679.98 | 01-MAY-06:10 | -3.5 |
| June | 0.595523E+09 | 10672.55 | 02-JUN-06:10 | 9.08 |
| July | 0.363449E+09 | 10288.23 | 10-JUL-06:06 | 11.75 |
| August | 0.829153E+09 | 10609.57 | 25-AUG-06:10 | 9.05 |
| September | 0.186530E+10 | 12451.68 | 06-SEP-06:10 | 2.38 |
| October | 0.530451E+10 | 16679.30 | 30-OCT-06:10 | -9.4 |
| November | 0.894997E+10 | 18594.08 | 29-NOV-07:10 | -18.4 |
| December | 0.161114E+11 | 23095.64 | 20-DEC-07:10 | -29.1 |
| Annual Sum or Average | 0.858404E+11 | |||
| Minimum of Months | 0.363449E+09 | 10288.23 | -35.0 | |
| Maximum of Months | 0.181818E+11 | 24857.52 | 11.75 |
Report: ZoneHeatingSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.343713E+09 | 9559.05 | 09-JAN-07:01 | -32.3 |
| February | 131965.05 | 139.22 | 20-FEB-07:12 | -10.2 |
| March | 0.00 | 0.00 | 01-MAR-00:05 | -1.3 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 3.52 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 3.60 |
| December | 0.247402E+09 | 9383.27 | 25-DEC-06:31 | -28.9 |
| Annual Sum or Average | 0.591248E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -32.3 | |
| Maximum of Months | 0.343713E+09 | 9559.05 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.322051E+10 | 8457.46 | 09-JAN-07:01 | -32.3 |
| February | 0.170656E+10 | 8277.36 | 13-FEB-04:12 | -23.0 |
| March | 0.680962E+09 | 8201.80 | 05-MAR-05:52 | -27.2 |
| April | 2073101.16 | 2102.71 | 03-APR-05:11 | -4.2 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | -0.0 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 7.52 |
| November | 0.314574E+09 | 8010.69 | 27-NOV-06:01 | -7.1 |
| December | 0.259591E+10 | 8418.13 | 25-DEC-05:51 | -29.4 |
| Annual Sum or Average | 0.852059E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -32.3 | |
| Maximum of Months | 0.322051E+10 | 8457.46 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.137061E+11 | 25935.98 | 09-JAN-00:21 | -30.0 |
| February | 0.761511E+10 | 25590.34 | 13-FEB-04:12 | -23.0 |
| March | 0.471367E+10 | 25208.11 | 05-MAR-05:52 | -27.2 |
| April | 0.631298E+09 | 23971.23 | 03-APR-05:11 | -4.2 |
| May | 18073789.73 | 21547.80 | 01-MAY-06:01 | -3.5 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
| October | 81432025.95 | 22559.91 | 30-OCT-05:01 | -9.9 |
| November | 0.265027E+10 | 24234.41 | 29-NOV-06:11 | -20.0 |
| December | 0.114390E+11 | 26006.99 | 25-DEC-06:31 | -28.9 |
| Annual Sum or Average | 0.408550E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -30.0 | |
| Maximum of Months | 0.137061E+11 | 26006.99 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.638361E+10 | 25002.48 | 09-JAN-00:21 | -30.0 |
| February | 0.290536E+10 | 24256.47 | 13-FEB-04:12 | -23.0 |
| March | 0.168348E+10 | 23696.98 | 05-MAR-05:52 | -27.2 |
| April | 0.237542E+09 | 20826.22 | 05-APR-05:11 | -13.5 |
| May | 6678857.33 | 17671.77 | 01-MAY-05:01 | -3.4 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
| October | 43565118.82 | 20472.59 | 30-OCT-05:01 | -9.9 |
| November | 0.108438E+10 | 22795.97 | 29-NOV-06:11 | -20.0 |
| December | 0.538542E+10 | 25093.78 | 25-DEC-06:31 | -28.9 |
| Annual Sum or Average | 0.177300E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -30.0 | |
| Maximum of Months | 0.638361E+10 | 25093.78 | 19.75 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.224024E+09 | 36832.60 | 09-JAN-07:07 | -32.3 |
| February | 60832510.28 | 2812.89 | 03-FEB-07:02 | -13.5 |
| March | 15207077.14 | 2802.04 | 14-MAR-06:02 | -14.2 |
| April | 191214.51 | 1598.59 | 18-APR-06:02 | 12.38 |
| May | 365100.99 | 1549.46 | 31-MAY-06:01 | 7.83 |
| June | 283279.40 | 1591.57 | 01-JUN-06:01 | 15.28 |
| July | 376444.90 | 1861.68 | 03-JUL-06:01 | 18.90 |
| August | 404682.10 | 1832.01 | 30-AUG-06:01 | 18.30 |
| September | 371626.52 | 1637.91 | 18-SEP-06:01 | 12.98 |
| October | 1430589.91 | 3396.34 | 23-OCT-06:02 | 5.60 |
| November | 3666571.89 | 2522.76 | 13-NOV-07:02 | -8.7 |
| December | 0.130219E+09 | 36174.12 | 26-DEC-07:01 | -26.5 |
| Annual Sum or Average | 0.437371E+09 | |||
| Minimum of Months | 191214.51 | 1549.46 | -32.3 | |
| Maximum of Months | 0.224024E+09 | 36832.60 | 18.90 |
Report: ZoneHeatingSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.751797E+10 | 121266.05 | 26-JAN-07:01 | -33.1 |
| February | 0.426150E+10 | 124349.55 | 14-FEB-07:01 | -33.0 |
| March | 0.284253E+10 | 114978.96 | 08-MAR-07:01 | -17.5 |
| April | 0.811330E+09 | 96107.38 | 10-APR-05:01 | -2.7 |
| May | 0.140541E+09 | 91558.44 | 01-MAY-05:01 | -3.4 |
| June | 2150486.52 | 4713.92 | 06-JUN-06:02 | 11.75 |
| July | 2240671.83 | 4918.49 | 19-JUL-06:02 | 15.05 |
| August | 15264064.45 | 4917.29 | 23-AUG-06:02 | 16.20 |
| September | 52762886.44 | 6090.70 | 21-SEP-07:05 | 5.78 |
| October | 0.392260E+09 | 84577.64 | 10-OCT-05:01 | 3.40 |
| November | 0.151486E+10 | 104494.03 | 20-NOV-06:01 | 4.90 |
| December | 0.584968E+10 | 129402.55 | 11-DEC-07:01 | -23.8 |
| Annual Sum or Average | 0.234031E+11 | |||
| Minimum of Months | 2150486.52 | 4713.92 | -33.1 | |
| Maximum of Months | 0.751797E+10 | 129402.55 | 16.20 |
Report: ZoneHeatingSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.109687E+11 | 25813.11 | 09-JAN-00:21 | -30.0 |
| February | 0.610170E+10 | 25495.98 | 13-FEB-04:12 | -23.0 |
| March | 0.355388E+10 | 24974.99 | 06-MAR-03:12 | -16.5 |
| April | 0.423702E+09 | 23533.04 | 03-APR-05:11 | -4.2 |
| May | 14038287.53 | 20811.45 | 01-MAY-06:01 | -3.5 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 11.35 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.83 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 17.07 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 19.75 |
| October | 35181279.19 | 20795.00 | 30-OCT-06:01 | -9.4 |
| November | 0.159981E+10 | 23906.64 | 29-NOV-06:11 | -20.0 |
| December | 0.868964E+10 | 25924.65 | 25-DEC-05:51 | -29.4 |
| Annual Sum or Average | 0.313867E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -30.0 | |
| Maximum of Months | 0.109687E+11 | 25924.65 | 19.75 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.130469E+10 | 947.12 | 02-JAN-07:10 | 0.892986E+09 | 678.98 | 02-JAN-08:09 |
| February | 0.117967E+10 | 947.12 | 01-FEB-07:10 | 0.807077E+09 | 678.98 | 01-FEB-08:09 |
| March | 0.138135E+10 | 947.12 | 01-MAR-07:10 | 0.924571E+09 | 678.98 | 01-MAR-08:09 |
| April | 0.125024E+10 | 947.12 | 03-APR-06:10 | 0.859085E+09 | 678.98 | 03-APR-07:10 |
| May | 0.134302E+10 | 947.12 | 01-MAY-06:10 | 0.908779E+09 | 678.98 | 01-MAY-07:10 |
| June | 0.132690E+10 | 947.12 | 01-JUN-06:10 | 0.890455E+09 | 678.98 | 01-JUN-07:10 |
| July | 0.793150E+09 | 526.18 | 03-JUL-07:10 | 0.543864E+09 | 357.36 | 03-JUL-07:10 |
| August | 0.837162E+09 | 526.18 | 01-AUG-07:10 | 0.565300E+09 | 357.36 | 01-AUG-07:10 |
| September | 0.122658E+10 | 947.12 | 05-SEP-06:10 | 0.845480E+09 | 678.98 | 05-SEP-07:10 |
| October | 0.130469E+10 | 947.12 | 02-OCT-06:10 | 0.892986E+09 | 678.98 | 02-OCT-07:10 |
| November | 0.128857E+10 | 947.12 | 01-NOV-06:10 | 0.874878E+09 | 678.98 | 01-NOV-07:10 |
| December | 0.126636E+10 | 947.12 | 01-DEC-07:10 | 0.877193E+09 | 678.98 | 01-DEC-08:09 |
| Annual Sum or Average | 0.145024E+11 | 0.988265E+10 | ||||
| Minimum of Months | 0.793150E+09 | 526.18 | 0.543864E+09 | 357.36 | ||
| Maximum of Months | 0.138135E+10 | 947.12 | 0.924571E+09 | 678.98 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.130469E+10 | 947.12 | 02-JAN-07:10 | 0.892986E+09 | 678.98 | 02-JAN-08:09 |
| February | 0.117967E+10 | 947.12 | 01-FEB-07:10 | 0.807077E+09 | 678.98 | 01-FEB-08:09 |
| March | 0.138135E+10 | 947.12 | 01-MAR-07:10 | 0.924571E+09 | 678.98 | 01-MAR-08:09 |
| April | 0.125024E+10 | 947.12 | 03-APR-06:10 | 0.859085E+09 | 678.98 | 03-APR-07:10 |
| May | 0.134302E+10 | 947.12 | 01-MAY-06:10 | 0.908779E+09 | 678.98 | 01-MAY-07:10 |
| June | 0.132690E+10 | 947.12 | 01-JUN-06:10 | 0.890455E+09 | 678.98 | 01-JUN-07:10 |
| July | 0.793150E+09 | 526.18 | 03-JUL-07:10 | 0.543864E+09 | 357.36 | 03-JUL-07:10 |
| August | 0.837162E+09 | 526.18 | 01-AUG-07:10 | 0.565300E+09 | 357.36 | 01-AUG-07:10 |
| September | 0.122658E+10 | 947.12 | 05-SEP-06:10 | 0.845480E+09 | 678.98 | 05-SEP-07:10 |
| October | 0.130469E+10 | 947.12 | 02-OCT-06:10 | 0.892986E+09 | 678.98 | 02-OCT-07:10 |
| November | 0.128857E+10 | 947.12 | 01-NOV-06:10 | 0.874878E+09 | 678.98 | 01-NOV-07:10 |
| December | 0.126636E+10 | 947.12 | 01-DEC-07:10 | 0.877193E+09 | 678.98 | 01-DEC-08:09 |
| Annual Sum or Average | 0.145024E+11 | 0.988265E+10 | ||||
| Minimum of Months | 0.793150E+09 | 526.18 | 0.543864E+09 | 357.36 | ||
| Maximum of Months | 0.138135E+10 | 947.12 | 0.924571E+09 | 678.98 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.130469E+10 | 947.12 | 02-JAN-07:10 | 0.892986E+09 | 678.98 | 02-JAN-08:09 |
| February | 0.117967E+10 | 947.12 | 01-FEB-07:10 | 0.807077E+09 | 678.98 | 01-FEB-08:09 |
| March | 0.138135E+10 | 947.12 | 01-MAR-07:10 | 0.924571E+09 | 678.98 | 01-MAR-08:09 |
| April | 0.125024E+10 | 947.12 | 03-APR-06:10 | 0.859085E+09 | 678.98 | 03-APR-07:10 |
| May | 0.134302E+10 | 947.12 | 01-MAY-06:10 | 0.908779E+09 | 678.98 | 01-MAY-07:10 |
| June | 0.132690E+10 | 947.12 | 01-JUN-06:10 | 0.890455E+09 | 678.98 | 01-JUN-07:10 |
| July | 0.793150E+09 | 526.18 | 03-JUL-07:10 | 0.543864E+09 | 357.36 | 03-JUL-07:10 |
| August | 0.837162E+09 | 526.18 | 01-AUG-07:10 | 0.565300E+09 | 357.36 | 01-AUG-07:10 |
| September | 0.122658E+10 | 947.12 | 05-SEP-06:10 | 0.845480E+09 | 678.98 | 05-SEP-07:10 |
| October | 0.130469E+10 | 947.12 | 02-OCT-06:10 | 0.892986E+09 | 678.98 | 02-OCT-07:10 |
| November | 0.128857E+10 | 947.12 | 01-NOV-06:10 | 0.874878E+09 | 678.98 | 01-NOV-07:10 |
| December | 0.126636E+10 | 947.12 | 01-DEC-07:10 | 0.877193E+09 | 678.98 | 01-DEC-08:09 |
| Annual Sum or Average | 0.145024E+11 | 0.988265E+10 | ||||
| Minimum of Months | 0.793150E+09 | 526.18 | 0.543864E+09 | 357.36 | ||
| Maximum of Months | 0.138135E+10 | 947.12 | 0.924571E+09 | 678.98 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.588512E+10 | 4272.19 | 02-JAN-07:10 | 0.549396E+10 | 4177.31 | 02-JAN-08:09 |
| February | 0.532117E+10 | 4272.19 | 01-FEB-07:10 | 0.496542E+10 | 4177.31 | 01-FEB-08:09 |
| March | 0.623092E+10 | 4272.19 | 01-MAR-07:10 | 0.568828E+10 | 4177.31 | 01-MAR-08:09 |
| April | 0.563950E+10 | 4272.19 | 03-APR-06:10 | 0.528539E+10 | 4177.31 | 03-APR-07:10 |
| May | 0.605802E+10 | 4272.19 | 01-MAY-06:10 | 0.559112E+10 | 4177.31 | 01-MAY-07:10 |
| June | 0.598530E+10 | 4272.19 | 01-JUN-06:10 | 0.547839E+10 | 4177.31 | 01-JUN-07:10 |
| July | 0.357769E+10 | 2373.44 | 03-JUL-07:10 | 0.334604E+10 | 2198.59 | 03-JUL-07:10 |
| August | 0.377621E+10 | 2373.44 | 01-AUG-07:10 | 0.347792E+10 | 2198.59 | 01-AUG-07:10 |
| September | 0.553277E+10 | 4272.19 | 05-SEP-06:10 | 0.520168E+10 | 4177.31 | 05-SEP-07:10 |
| October | 0.588512E+10 | 4272.19 | 02-OCT-06:10 | 0.549396E+10 | 4177.31 | 02-OCT-07:10 |
| November | 0.581240E+10 | 4272.19 | 01-NOV-06:10 | 0.538255E+10 | 4177.31 | 01-NOV-07:10 |
| December | 0.571221E+10 | 4272.19 | 01-DEC-07:10 | 0.539679E+10 | 4177.31 | 01-DEC-08:09 |
| Annual Sum or Average | 0.654164E+11 | 0.608015E+11 | ||||
| Minimum of Months | 0.357769E+10 | 2373.44 | 0.334604E+10 | 2198.59 | ||
| Maximum of Months | 0.623092E+10 | 4272.19 | 0.568828E+10 | 4177.31 |
Report: ZoneElectricSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.302663E+10 | 2197.13 | 02-JAN-07:10 | 0.376728E+10 | 2864.44 | 02-JAN-08:09 |
| February | 0.273660E+10 | 2197.13 | 01-FEB-07:10 | 0.340486E+10 | 2864.44 | 01-FEB-08:09 |
| March | 0.320447E+10 | 2197.13 | 01-MAR-07:10 | 0.390054E+10 | 2864.44 | 01-MAR-08:09 |
| April | 0.290031E+10 | 2197.13 | 03-APR-06:10 | 0.362427E+10 | 2864.44 | 03-APR-07:10 |
| May | 0.311555E+10 | 2197.13 | 01-MAY-06:10 | 0.383391E+10 | 2864.44 | 01-MAY-07:10 |
| June | 0.307815E+10 | 2197.13 | 01-JUN-06:10 | 0.375661E+10 | 2864.44 | 01-JUN-07:10 |
| July | 0.183996E+10 | 1220.63 | 03-JUL-07:10 | 0.229443E+10 | 1507.60 | 03-JUL-07:10 |
| August | 0.194205E+10 | 1220.63 | 01-AUG-07:10 | 0.238486E+10 | 1507.60 | 01-AUG-07:10 |
| September | 0.284543E+10 | 2197.13 | 05-SEP-06:10 | 0.356687E+10 | 2864.44 | 05-SEP-07:10 |
| October | 0.302663E+10 | 2197.13 | 02-OCT-06:10 | 0.376728E+10 | 2864.44 | 02-OCT-07:10 |
| November | 0.298923E+10 | 2197.13 | 01-NOV-06:10 | 0.369089E+10 | 2864.44 | 01-NOV-07:10 |
| December | 0.293771E+10 | 2197.13 | 01-DEC-07:10 | 0.370066E+10 | 2864.44 | 01-DEC-08:09 |
| Annual Sum or Average | 0.336427E+11 | 0.416925E+11 | ||||
| Minimum of Months | 0.183996E+10 | 1220.63 | 0.229443E+10 | 1507.60 | ||
| Maximum of Months | 0.320447E+10 | 2197.13 | 0.390054E+10 | 2864.44 |
Report: ZoneElectricSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.371022E+10 | 2693.36 | 02-JAN-07:10 | 0.253943E+10 | 1930.85 | 02-JAN-08:09 |
| February | 0.335468E+10 | 2693.36 | 01-FEB-07:10 | 0.229513E+10 | 1930.85 | 01-FEB-08:09 |
| March | 0.392822E+10 | 2693.36 | 01-MAR-07:10 | 0.262925E+10 | 1930.85 | 01-MAR-08:09 |
| April | 0.355537E+10 | 2693.36 | 03-APR-06:10 | 0.244302E+10 | 1930.85 | 03-APR-07:10 |
| May | 0.381922E+10 | 2693.36 | 01-MAY-06:10 | 0.258434E+10 | 1930.85 | 01-MAY-07:10 |
| June | 0.377338E+10 | 2693.36 | 01-JUN-06:10 | 0.253223E+10 | 1930.85 | 01-JUN-07:10 |
| July | 0.225552E+10 | 1496.31 | 03-JUL-07:10 | 0.154661E+10 | 1016.24 | 03-JUL-07:10 |
| August | 0.238068E+10 | 1496.31 | 01-AUG-07:10 | 0.160757E+10 | 1016.24 | 01-AUG-07:10 |
| September | 0.348808E+10 | 2693.36 | 05-SEP-06:10 | 0.240433E+10 | 1930.85 | 05-SEP-07:10 |
| October | 0.371022E+10 | 2693.36 | 02-OCT-06:10 | 0.253943E+10 | 1930.85 | 02-OCT-07:10 |
| November | 0.366437E+10 | 2693.36 | 01-NOV-06:10 | 0.248793E+10 | 1930.85 | 01-NOV-07:10 |
| December | 0.360121E+10 | 2693.36 | 01-DEC-07:10 | 0.249452E+10 | 1930.85 | 01-DEC-08:09 |
| Annual Sum or Average | 0.412412E+11 | 0.281038E+11 | ||||
| Minimum of Months | 0.225552E+10 | 1496.31 | 0.154661E+10 | 1016.24 | ||
| Maximum of Months | 0.392822E+10 | 2693.36 | 0.262925E+10 | 1930.85 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.296658E+10 | 2153.53 | 02-JAN-07:10 | 0.795316E+09 | 604.72 | 02-JAN-08:09 |
| February | 0.268230E+10 | 2153.53 | 01-FEB-07:10 | 0.718803E+09 | 604.72 | 01-FEB-08:09 |
| March | 0.314089E+10 | 2153.53 | 01-MAR-07:10 | 0.823446E+09 | 604.72 | 01-MAR-08:09 |
| April | 0.284277E+10 | 2153.53 | 03-APR-06:10 | 0.765123E+09 | 604.72 | 03-APR-07:10 |
| May | 0.305373E+10 | 2153.53 | 01-MAY-06:10 | 0.809381E+09 | 604.72 | 01-MAY-07:10 |
| June | 0.301708E+10 | 2153.53 | 01-JUN-06:10 | 0.793062E+09 | 604.72 | 01-JUN-07:10 |
| July | 0.180345E+10 | 1196.41 | 03-JUL-07:10 | 0.484379E+09 | 318.27 | 03-JUL-07:10 |
| August | 0.190352E+10 | 1196.41 | 01-AUG-07:10 | 0.503470E+09 | 318.27 | 01-AUG-07:10 |
| September | 0.278897E+10 | 2153.53 | 05-SEP-06:10 | 0.753006E+09 | 604.72 | 05-SEP-07:10 |
| October | 0.296658E+10 | 2153.53 | 02-OCT-06:10 | 0.795316E+09 | 604.72 | 02-OCT-07:10 |
| November | 0.292992E+10 | 2153.53 | 01-NOV-06:10 | 0.779188E+09 | 604.72 | 01-NOV-07:10 |
| December | 0.287942E+10 | 2153.53 | 01-DEC-07:10 | 0.781250E+09 | 604.72 | 01-DEC-08:09 |
| Annual Sum or Average | 0.329752E+11 | 0.880174E+10 | ||||
| Minimum of Months | 0.180345E+10 | 1196.41 | 0.484379E+09 | 318.27 | ||
| Maximum of Months | 0.314089E+10 | 2153.53 | 0.823446E+09 | 604.72 |
Report: ZoneElectricSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.504438E+10 | 3661.88 | 02-JAN-07:10 | 0.293011E+10 | 2227.90 | 02-JAN-08:09 |
| February | 0.456100E+10 | 3661.88 | 01-FEB-07:10 | 0.264822E+10 | 2227.90 | 01-FEB-08:09 |
| March | 0.534079E+10 | 3661.88 | 01-MAR-07:10 | 0.303375E+10 | 2227.90 | 01-MAR-08:09 |
| April | 0.483386E+10 | 3661.88 | 03-APR-06:10 | 0.281887E+10 | 2227.90 | 03-APR-07:10 |
| May | 0.519259E+10 | 3661.88 | 01-MAY-06:10 | 0.298193E+10 | 2227.90 | 01-MAY-07:10 |
| June | 0.513026E+10 | 3661.88 | 01-JUN-06:10 | 0.292181E+10 | 2227.90 | 01-JUN-07:10 |
| July | 0.306659E+10 | 2034.38 | 03-JUL-07:10 | 0.178455E+10 | 1172.58 | 03-JUL-07:10 |
| August | 0.323676E+10 | 2034.38 | 01-AUG-07:10 | 0.185489E+10 | 1172.58 | 01-AUG-07:10 |
| September | 0.474238E+10 | 3661.88 | 05-SEP-06:10 | 0.277423E+10 | 2227.90 | 05-SEP-07:10 |
| October | 0.504438E+10 | 3661.88 | 02-OCT-06:10 | 0.293011E+10 | 2227.90 | 02-OCT-07:10 |
| November | 0.498206E+10 | 3661.88 | 01-NOV-06:10 | 0.287069E+10 | 2227.90 | 01-NOV-07:10 |
| December | 0.489618E+10 | 3661.88 | 01-DEC-07:10 | 0.287829E+10 | 2227.90 | 01-DEC-08:09 |
| Annual Sum or Average | 0.560712E+11 | 0.324275E+11 | ||||
| Minimum of Months | 0.306659E+10 | 2034.38 | 0.178455E+10 | 1172.58 | ||
| Maximum of Months | 0.534079E+10 | 3661.88 | 0.303375E+10 | 2227.90 |
Report: ZoneElectricSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.228198E+10 | 1656.56 | 02-JAN-07:10 | 0.883684E+09 | 671.91 | 02-JAN-08:09 |
| February | 0.206331E+10 | 1656.56 | 01-FEB-07:10 | 0.798670E+09 | 671.91 | 01-FEB-08:09 |
| March | 0.241607E+10 | 1656.56 | 01-MAR-07:10 | 0.914940E+09 | 671.91 | 01-MAR-08:09 |
| April | 0.218674E+10 | 1656.56 | 03-APR-06:10 | 0.850137E+09 | 671.91 | 03-APR-07:10 |
| May | 0.234903E+10 | 1656.56 | 01-MAY-06:10 | 0.899312E+09 | 671.91 | 01-MAY-07:10 |
| June | 0.232083E+10 | 1656.56 | 01-JUN-06:10 | 0.881180E+09 | 671.91 | 01-JUN-07:10 |
| July | 0.138727E+10 | 920.31 | 03-JUL-07:10 | 0.538198E+09 | 353.64 | 03-JUL-07:10 |
| August | 0.146425E+10 | 920.31 | 01-AUG-07:10 | 0.559411E+09 | 353.64 | 01-AUG-07:10 |
| September | 0.214536E+10 | 1656.56 | 05-SEP-06:10 | 0.836673E+09 | 671.91 | 05-SEP-07:10 |
| October | 0.228198E+10 | 1656.56 | 02-OCT-06:10 | 0.883684E+09 | 671.91 | 02-OCT-07:10 |
| November | 0.225379E+10 | 1656.56 | 01-NOV-06:10 | 0.865765E+09 | 671.91 | 01-NOV-07:10 |
| December | 0.221494E+10 | 1656.56 | 01-DEC-07:10 | 0.868056E+09 | 671.91 | 01-DEC-08:09 |
| Annual Sum or Average | 0.253655E+11 | 0.977971E+10 | ||||
| Minimum of Months | 0.138727E+10 | 920.31 | 0.538198E+09 | 353.64 | ||
| Maximum of Months | 0.241607E+10 | 1656.56 | 0.914940E+09 | 671.91 |
Report: ZoneElectricSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.647363E+10 | 4699.41 | 02-JAN-07:10 | 0.553791E+10 | 4210.73 | 02-JAN-08:09 |
| February | 0.585328E+10 | 4699.41 | 01-FEB-07:10 | 0.500514E+10 | 4210.73 | 01-FEB-08:09 |
| March | 0.685401E+10 | 4699.41 | 01-MAR-07:10 | 0.573379E+10 | 4210.73 | 01-MAR-08:09 |
| April | 0.620345E+10 | 4699.41 | 03-APR-06:10 | 0.532767E+10 | 4210.73 | 03-APR-07:10 |
| May | 0.666382E+10 | 4699.41 | 01-MAY-06:10 | 0.563585E+10 | 4210.73 | 01-MAY-07:10 |
| June | 0.658383E+10 | 4699.41 | 01-JUN-06:10 | 0.552221E+10 | 4210.73 | 01-JUN-07:10 |
| July | 0.393546E+10 | 2610.78 | 03-JUL-07:10 | 0.337280E+10 | 2216.18 | 03-JUL-07:10 |
| August | 0.415384E+10 | 2610.78 | 01-AUG-07:10 | 0.350574E+10 | 2216.18 | 01-AUG-07:10 |
| September | 0.608605E+10 | 4699.41 | 05-SEP-06:10 | 0.524330E+10 | 4210.73 | 05-SEP-07:10 |
| October | 0.647363E+10 | 4699.41 | 02-OCT-06:10 | 0.553791E+10 | 4210.73 | 02-OCT-07:10 |
| November | 0.639364E+10 | 4699.41 | 01-NOV-06:10 | 0.542561E+10 | 4210.73 | 01-NOV-07:10 |
| December | 0.628344E+10 | 4699.41 | 01-DEC-07:10 | 0.543997E+10 | 4210.73 | 01-DEC-08:09 |
| Annual Sum or Average | 0.719581E+11 | 0.612879E+11 | ||||
| Minimum of Months | 0.393546E+10 | 2610.78 | 0.337280E+10 | 2216.18 | ||
| Maximum of Months | 0.685401E+10 | 4699.41 | 0.573379E+10 | 4210.73 |
Report: ZoneElectricSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.590754E+10 | 4288.47 | 02-JAN-07:10 | 0.207549E+10 | 1578.10 | 02-JAN-08:09 |
| February | 0.534144E+10 | 4288.47 | 01-FEB-07:10 | 0.187582E+10 | 1578.10 | 01-FEB-08:09 |
| March | 0.625466E+10 | 4288.47 | 01-MAR-07:10 | 0.214891E+10 | 1578.10 | 01-MAR-08:09 |
| April | 0.566098E+10 | 4288.47 | 03-APR-06:10 | 0.199670E+10 | 1578.10 | 03-APR-07:10 |
| May | 0.608110E+10 | 4288.47 | 01-MAY-06:10 | 0.211220E+10 | 1578.10 | 01-MAY-07:10 |
| June | 0.600810E+10 | 4288.47 | 01-JUN-06:10 | 0.206961E+10 | 1578.10 | 01-JUN-07:10 |
| July | 0.359132E+10 | 2382.48 | 03-JUL-07:10 | 0.126406E+10 | 830.58 | 03-JUL-07:10 |
| August | 0.379060E+10 | 2382.48 | 01-AUG-07:10 | 0.131388E+10 | 830.58 | 01-AUG-07:10 |
| September | 0.555385E+10 | 4288.47 | 05-SEP-06:10 | 0.196508E+10 | 1578.10 | 05-SEP-07:10 |
| October | 0.590754E+10 | 4288.47 | 02-OCT-06:10 | 0.207549E+10 | 1578.10 | 02-OCT-07:10 |
| November | 0.583454E+10 | 4288.47 | 01-NOV-06:10 | 0.203341E+10 | 1578.10 | 01-NOV-07:10 |
| December | 0.573398E+10 | 4288.47 | 01-DEC-07:10 | 0.203879E+10 | 1578.10 | 01-DEC-08:09 |
| Annual Sum or Average | 0.656656E+11 | 0.229695E+11 | ||||
| Minimum of Months | 0.359132E+10 | 2382.48 | 0.126406E+10 | 830.58 | ||
| Maximum of Months | 0.625466E+10 | 4288.47 | 0.214891E+10 | 1578.10 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.269034E+10 | 1953.00 | 02-JAN-07:10 | 0.147381E+11 | 9714.90 | 02-JAN-10:09 |
| February | 0.243253E+10 | 1953.00 | 01-FEB-07:10 | 0.133142E+11 | 9714.90 | 01-FEB-10:09 |
| March | 0.284842E+10 | 1953.00 | 01-MAR-07:10 | 0.148878E+11 | 9714.90 | 01-MAR-10:09 |
| April | 0.257806E+10 | 1953.00 | 03-APR-06:10 | 0.142385E+11 | 9714.90 | 03-APR-09:09 |
| May | 0.276938E+10 | 1953.00 | 01-MAY-06:10 | 0.148130E+11 | 9714.90 | 01-MAY-09:09 |
| June | 0.273614E+10 | 1953.00 | 01-JUN-06:10 | 0.143883E+11 | 9714.90 | 01-JUN-09:09 |
| July | 0.163552E+10 | 1085.00 | 03-JUL-07:10 | 0.146632E+11 | 9714.90 | 03-JUL-09:09 |
| August | 0.172627E+10 | 1085.00 | 01-AUG-07:10 | 0.148878E+11 | 9714.90 | 01-AUG-09:09 |
| September | 0.252927E+10 | 1953.00 | 05-SEP-06:10 | 0.142385E+11 | 9714.90 | 01-SEP-09:09 |
| October | 0.269034E+10 | 1953.00 | 02-OCT-06:10 | 0.147381E+11 | 9714.90 | 02-OCT-09:09 |
| November | 0.265710E+10 | 1953.00 | 01-NOV-06:10 | 0.143134E+11 | 9714.90 | 01-NOV-09:09 |
| December | 0.261130E+10 | 1953.00 | 01-DEC-07:10 | 0.146632E+11 | 9714.90 | 01-DEC-10:09 |
| Annual Sum or Average | 0.299046E+11 | 0.173884E+12 | ||||
| Minimum of Months | 0.163552E+10 | 1085.00 | 0.133142E+11 | 9714.90 | ||
| Maximum of Months | 0.284842E+10 | 1953.00 | 0.148878E+11 | 9714.90 |
Report: ZoneElectricSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.378329E+10 | 2746.41 | 02-JAN-07:10 | 0.253516E+10 | 1999.46 | 02-JAN-10:09 |
| February | 0.342075E+10 | 2746.41 | 01-FEB-07:10 | 0.229042E+10 | 1999.46 | 01-FEB-10:09 |
| March | 0.400559E+10 | 2746.41 | 01-MAR-07:10 | 0.257259E+10 | 1999.46 | 01-MAR-10:09 |
| April | 0.362539E+10 | 2746.41 | 03-APR-06:10 | 0.244734E+10 | 1999.46 | 03-APR-09:09 |
| May | 0.389444E+10 | 2746.41 | 01-MAY-06:10 | 0.255387E+10 | 1999.46 | 01-MAY-09:09 |
| June | 0.384769E+10 | 2746.41 | 01-JUN-06:10 | 0.248477E+10 | 1999.46 | 01-JUN-09:09 |
| July | 0.229994E+10 | 1525.78 | 03-JUL-07:10 | 0.251644E+10 | 1999.46 | 03-JUL-09:09 |
| August | 0.242757E+10 | 1525.78 | 01-AUG-07:10 | 0.257259E+10 | 1999.46 | 01-AUG-09:09 |
| September | 0.355678E+10 | 2746.41 | 05-SEP-06:10 | 0.244734E+10 | 1999.46 | 01-SEP-09:09 |
| October | 0.378329E+10 | 2746.41 | 02-OCT-06:10 | 0.253516E+10 | 1999.46 | 02-OCT-09:09 |
| November | 0.373654E+10 | 2746.41 | 01-NOV-06:10 | 0.246606E+10 | 1999.46 | 01-NOV-09:09 |
| December | 0.367214E+10 | 2746.41 | 01-DEC-07:10 | 0.251644E+10 | 1999.46 | 01-DEC-10:09 |
| Annual Sum or Average | 0.420534E+11 | 0.299382E+11 | ||||
| Minimum of Months | 0.229994E+10 | 1525.78 | 0.229042E+10 | 1999.46 | ||
| Maximum of Months | 0.400559E+10 | 2746.41 | 0.257259E+10 | 1999.46 |
Report: ZoneElectricSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.825317E+10 | 5991.24 | 02-JAN-07:10 | 0.695901E+10 | 5291.26 | 02-JAN-08:09 |
| February | 0.746230E+10 | 5991.24 | 01-FEB-07:10 | 0.628953E+10 | 5291.26 | 01-FEB-08:09 |
| March | 0.873812E+10 | 5991.24 | 01-MAR-07:10 | 0.720516E+10 | 5291.26 | 01-MAR-08:09 |
| April | 0.790872E+10 | 5991.24 | 03-APR-06:10 | 0.669483E+10 | 5291.26 | 03-APR-07:10 |
| May | 0.849564E+10 | 5991.24 | 01-MAY-06:10 | 0.708208E+10 | 5291.26 | 01-MAY-07:10 |
| June | 0.839367E+10 | 5991.24 | 01-JUN-06:10 | 0.693929E+10 | 5291.26 | 01-JUN-07:10 |
| July | 0.501728E+10 | 3328.47 | 03-JUL-07:10 | 0.423831E+10 | 2784.88 | 03-JUL-07:10 |
| August | 0.529569E+10 | 3328.47 | 01-AUG-07:10 | 0.440537E+10 | 2784.88 | 01-AUG-07:10 |
| September | 0.775905E+10 | 5991.24 | 05-SEP-06:10 | 0.658880E+10 | 5291.26 | 05-SEP-07:10 |
| October | 0.825317E+10 | 5991.24 | 02-OCT-06:10 | 0.695901E+10 | 5291.26 | 02-OCT-07:10 |
| November | 0.815120E+10 | 5991.24 | 01-NOV-06:10 | 0.681790E+10 | 5291.26 | 01-NOV-07:10 |
| December | 0.801070E+10 | 5991.24 | 01-DEC-07:10 | 0.683594E+10 | 5291.26 | 01-DEC-08:09 |
| Annual Sum or Average | 0.917387E+11 | 0.770152E+11 | ||||
| Minimum of Months | 0.501728E+10 | 3328.47 | 0.423831E+10 | 2784.88 | ||
| Maximum of Months | 0.873812E+10 | 5991.24 | 0.720516E+10 | 5291.26 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802869E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674689E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462224E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 260807.86 | 0.405860E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1332795.56 | 0.202395E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8783115.49 | 0.103958E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10618589.37 | 76037574.32 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2359458.52 | 0.112488E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63285.70 | 0.233647E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313572E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523065E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837058E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23418052.51 | 0.474786E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76037574.32 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10618589.37 | 0.837058E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214351E+10 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181223E+10 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126391E+10 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1014874.24 | 0.116282E+10 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3698644.81 | 0.574978E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24976456.27 | 0.297591E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34045754.83 | 0.200157E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7971436.02 | 0.295976E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 199030.47 | 0.647869E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.885549E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144926E+10 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224074E+10 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 71906196.64 | 0.129746E+11 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200157E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34045754.83 | 0.224074E+10 |
Report: SpaceGainsMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122065E+09 |
| February | 0.708259E+09 | 0.117967E+10 | 0.807077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102658E+09 |
| March | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71396754.94 |
| April | 0.745536E+09 | 0.125024E+10 | 0.859085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 210126.34 | 64480010.51 |
| May | 0.820090E+09 | 0.134302E+10 | 0.908779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 197579.13 | 32248882.69 |
| June | 0.505804E+09 | 0.132690E+10 | 0.890455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1186921.65 | 17161589.98 |
| July | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1684519.11 | 11444065.54 |
| August | 0.200223E+09 | 0.837162E+09 | 0.565300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 454935.35 | 15939960.11 |
| September | 0.459822E+09 | 0.122658E+10 | 0.845480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11182.30 | 34534166.61 |
| October | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47785930.48 |
| November | 0.782813E+09 | 0.128857E+10 | 0.874878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81245825.01 |
| December | 0.745536E+09 | 0.126636E+10 | 0.877193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127816E+09 |
| Annual Sum or Average | 0.756518E+10 | 0.145024E+11 | 0.988265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3745263.88 | 0.728776E+09 |
| Minimum of Months | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11444065.54 |
| Maximum of Months | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1684519.11 | 0.127816E+09 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801410E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669062E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452670E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1813546.73 | 0.381163E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1412680.84 | 0.190291E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10101478.11 | 0.100019E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13764781.77 | 68907180.39 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4517956.78 | 96660185.25 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 180163.82 | 0.210042E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292995E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510905E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835335E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31790608.05 | 0.460946E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68907180.39 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13764781.77 | 0.835335E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213694E+10 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178757E+10 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122757E+10 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5669894.86 | 0.108608E+10 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4237614.04 | 0.541143E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29914962.11 | 0.285914E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44549612.53 | 0.178332E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16035077.35 | 0.250402E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 685138.62 | 0.579401E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825614E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140834E+10 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223309E+10 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101092E+09 | 0.125404E+11 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178332E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44549612.53 | 0.223309E+10 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802699E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674487E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461918E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 281274.69 | 0.404633E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1341219.11 | 0.201003E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8998261.42 | 0.102998E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11042428.88 | 74780208.88 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2458213.85 | 0.110992E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63288.90 | 0.232496E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312958E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522420E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.836806E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24184686.85 | 0.473819E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74780208.88 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11042428.88 | 0.836806E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214294E+10 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181154E+10 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126380E+10 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1130656.13 | 0.116103E+10 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3744777.31 | 0.572304E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25750955.29 | 0.295644E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35854098.12 | 0.195879E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8633000.48 | 0.290555E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 212517.69 | 0.644108E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.883887E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144736E+10 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223981E+10 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75326005.01 | 0.129489E+11 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195879E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35854098.12 | 0.223981E+10 |
Report: SpaceGainsMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122039E+09 |
| February | 0.708259E+09 | 0.117967E+10 | 0.807077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102650E+09 |
| March | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71389399.81 |
| April | 0.745536E+09 | 0.125024E+10 | 0.859085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 214063.23 | 64420668.28 |
| May | 0.820090E+09 | 0.134302E+10 | 0.908779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 197998.23 | 32171024.32 |
| June | 0.505804E+09 | 0.132690E+10 | 0.890455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1197191.04 | 17109799.82 |
| July | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1719894.41 | 11332076.50 |
| August | 0.200223E+09 | 0.837162E+09 | 0.565300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 469163.93 | 15795431.33 |
| September | 0.459822E+09 | 0.122658E+10 | 0.845480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11597.35 | 34435525.92 |
| October | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47737856.43 |
| November | 0.782813E+09 | 0.128857E+10 | 0.874878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81192018.24 |
| December | 0.745536E+09 | 0.126636E+10 | 0.877193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127781E+09 |
| Annual Sum or Average | 0.756518E+10 | 0.145024E+11 | 0.988265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3809908.19 | 0.728054E+09 |
| Minimum of Months | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11332076.50 |
| Maximum of Months | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1719894.41 | 0.127781E+09 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801406E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669060E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452675E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1813308.02 | 0.381152E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1412433.85 | 0.190276E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10098639.85 | 0.100020E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13792452.63 | 68796722.68 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4530257.34 | 96501355.87 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 181250.99 | 0.209924E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292948E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510835E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835324E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 31828342.68 | 0.460892E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68796722.68 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13792452.63 | 0.835324E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213692E+10 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178757E+10 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122761E+10 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5668342.38 | 0.108612E+10 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4229047.59 | 0.541252E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29846969.35 | 0.286080E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44580414.79 | 0.178159E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16054256.34 | 0.250066E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 686041.02 | 0.579190E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.825553E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140815E+10 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223305E+10 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101065E+09 | 0.125397E+11 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178159E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44580414.79 | 0.223305E+10 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802760E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674523E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462008E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 266520.06 | 0.405630E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1337075.97 | 0.202071E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8892571.89 | 0.103716E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10822401.55 | 75668779.23 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2405607.10 | 0.112117E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63286.31 | 0.233812E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314348E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.523025E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.836900E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 23787462.88 | 0.474658E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75668779.23 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10822401.55 | 0.836900E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214327E+10 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181166E+10 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126389E+10 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1033217.91 | 0.116459E+10 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3714157.69 | 0.576199E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25255734.08 | 0.298484E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34802966.83 | 0.199299E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8252535.39 | 0.295232E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 204154.54 | 0.649698E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.890370E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145035E+10 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224036E+10 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73262766.44 | 0.129834E+11 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199299E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34802966.83 | 0.224036E+10 |
Report: SpaceGainsMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122073E+09 |
| February | 0.708259E+09 | 0.117967E+10 | 0.807077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102687E+09 |
| March | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71471066.54 |
| April | 0.745536E+09 | 0.125024E+10 | 0.859085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 192247.09 | 64960146.46 |
| May | 0.820090E+09 | 0.134302E+10 | 0.908779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 194601.00 | 32726509.54 |
| June | 0.505804E+09 | 0.132690E+10 | 0.890455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1144776.36 | 17510571.52 |
| July | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1598423.17 | 11784947.18 |
| August | 0.200223E+09 | 0.837162E+09 | 0.565300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 421522.90 | 16372275.75 |
| September | 0.459822E+09 | 0.122658E+10 | 0.845480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10090.79 | 35117320.18 |
| October | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48393131.60 |
| November | 0.782813E+09 | 0.128857E+10 | 0.874878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81467046.99 |
| December | 0.745536E+09 | 0.126636E+10 | 0.877193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127829E+09 |
| Annual Sum or Average | 0.756518E+10 | 0.145024E+11 | 0.988265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3561661.31 | 0.732392E+09 |
| Minimum of Months | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11784947.18 |
| Maximum of Months | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1598423.17 | 0.127829E+09 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801417E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669121E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452903E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1703492.15 | 0.382874E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1384573.43 | 0.192733E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9708503.79 | 0.101829E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13058423.12 | 70918995.64 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4222872.84 | 98664095.23 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161656.19 | 0.212415E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294642E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511138E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835325E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30239521.52 | 0.462398E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70918995.64 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13058423.12 | 0.835325E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.642132E+10 | 0.588512E+10 | 0.549396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141098E+10 |
| February | 0.580977E+10 | 0.532117E+10 | 0.496542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118030E+10 |
| March | 0.703288E+10 | 0.623092E+10 | 0.568828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810764E+09 |
| April | 0.611554E+10 | 0.563950E+10 | 0.528539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3534795.88 | 0.720041E+09 |
| May | 0.672710E+10 | 0.605802E+10 | 0.559112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2660793.26 | 0.362390E+09 |
| June | 0.414905E+10 | 0.598530E+10 | 0.547839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18398227.45 | 0.193192E+09 |
| July | 0.142818E+10 | 0.357769E+10 | 0.334604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27443279.24 | 0.122447E+09 |
| August | 0.164241E+10 | 0.377621E+10 | 0.347792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9702566.74 | 0.169590E+09 |
| September | 0.377186E+10 | 0.553277E+10 | 0.520168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 400137.78 | 0.387806E+09 |
| October | 0.642132E+10 | 0.588512E+10 | 0.549396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.548960E+09 |
| November | 0.642132E+10 | 0.581240E+10 | 0.538255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930127E+09 |
| December | 0.611554E+10 | 0.571221E+10 | 0.539679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147427E+10 |
| Annual Sum or Average | 0.620563E+11 | 0.654164E+11 | 0.608015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62139800.35 | 0.831087E+10 |
| Minimum of Months | 0.142818E+10 | 0.357769E+10 | 0.334604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122447E+09 |
| Maximum of Months | 0.703288E+10 | 0.623092E+10 | 0.568828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27443279.24 | 0.147427E+10 |
Report: SpaceGainsMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.488438E+10 | 0.302663E+10 | 0.376728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727140E+09 |
| February | 0.441920E+10 | 0.273660E+10 | 0.340486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609400E+09 |
| March | 0.534956E+10 | 0.320447E+10 | 0.390054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.422505E+09 |
| April | 0.465179E+10 | 0.290031E+10 | 0.362427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1319922.12 | 0.389503E+09 |
| May | 0.511697E+10 | 0.311555E+10 | 0.383391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1141682.93 | 0.201203E+09 |
| June | 0.511697E+10 | 0.307815E+10 | 0.375661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7938165.39 | 0.109965E+09 |
| July | 0.244831E+10 | 0.183996E+10 | 0.229443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11060522.00 | 72343356.95 |
| August | 0.281556E+10 | 0.194205E+10 | 0.238486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3226376.74 | 0.100101E+09 |
| September | 0.454162E+10 | 0.284543E+10 | 0.356687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 83852.89 | 0.217674E+09 |
| October | 0.488438E+10 | 0.302663E+10 | 0.376728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299854E+09 |
| November | 0.488438E+10 | 0.298923E+10 | 0.369089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490473E+09 |
| December | 0.465179E+10 | 0.293771E+10 | 0.370066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760892E+09 |
| Annual Sum or Average | 0.537649E+11 | 0.336427E+11 | 0.416925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 24770522.07 | 0.440106E+10 |
| Minimum of Months | 0.244831E+10 | 0.183996E+10 | 0.229443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72343356.95 |
| Maximum of Months | 0.534956E+10 | 0.320447E+10 | 0.390054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11060522.00 | 0.760892E+09 |
Report: SpaceGainsMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.222618E+10 | 0.371022E+10 | 0.253943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364558E+09 |
| February | 0.201416E+10 | 0.335468E+10 | 0.229513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306920E+09 |
| March | 0.243819E+10 | 0.392822E+10 | 0.262925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214505E+09 |
| April | 0.212017E+10 | 0.355537E+10 | 0.244302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 455779.80 | 0.199761E+09 |
| May | 0.233218E+10 | 0.381922E+10 | 0.258434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 568782.53 | 0.104171E+09 |
| June | 0.143841E+10 | 0.377338E+10 | 0.253223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2824922.35 | 56927329.07 |
| July | 0.495129E+09 | 0.225552E+10 | 0.154661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3930535.87 | 40059821.94 |
| August | 0.569398E+09 | 0.238068E+10 | 0.160757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1021147.39 | 54002811.68 |
| September | 0.130765E+10 | 0.348808E+10 | 0.240433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28472.93 | 0.105960E+09 |
| October | 0.222618E+10 | 0.371022E+10 | 0.253943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140932E+09 |
| November | 0.222618E+10 | 0.366437E+10 | 0.248793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241649E+09 |
| December | 0.212017E+10 | 0.360121E+10 | 0.249452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381667E+09 |
| Annual Sum or Average | 0.215140E+11 | 0.412412E+11 | 0.281038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 8829640.86 | 0.221111E+10 |
| Minimum of Months | 0.495129E+09 | 0.225552E+10 | 0.154661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40059821.94 |
| Maximum of Months | 0.243819E+10 | 0.392822E+10 | 0.262925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3930535.87 | 0.381667E+09 |
Report: SpaceGainsMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.139443E+10 | 0.296658E+10 | 0.795316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194510E+11 |
| February | 0.126163E+10 | 0.268230E+10 | 0.718803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150765E+11 |
| March | 0.152723E+10 | 0.314089E+10 | 0.823446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148849E+11 |
| April | 0.132803E+10 | 0.284277E+10 | 0.765123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 645446.59 | 0.880244E+10 |
| May | 0.146083E+10 | 0.305373E+10 | 0.809381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281118E+09 | 0.457301E+10 |
| June | 0.900991E+09 | 0.301708E+10 | 0.793062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536098E+09 | 0.232444E+10 |
| July | 0.310138E+09 | 0.180345E+10 | 0.484379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601811E+09 | 0.139353E+10 |
| August | 0.356659E+09 | 0.190352E+10 | 0.503470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396329E+09 | 0.257601E+10 |
| September | 0.819082E+09 | 0.278897E+10 | 0.753006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26957654.16 | 0.538675E+10 |
| October | 0.139443E+10 | 0.296658E+10 | 0.795316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897588E+10 |
| November | 0.139443E+10 | 0.292992E+10 | 0.779188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112164E+11 |
| December | 0.132803E+10 | 0.287942E+10 | 0.781250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170024E+11 |
| Annual Sum or Average | 0.134759E+11 | 0.329752E+11 | 0.880174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184296E+10 | 0.111663E+12 |
| Minimum of Months | 0.310138E+09 | 0.180345E+10 | 0.484379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139353E+10 |
| Maximum of Months | 0.152723E+10 | 0.314089E+10 | 0.823446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.601811E+09 | 0.194510E+11 |
Report: SpaceGainsMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.308232E+09 | 0.504438E+10 | 0.293011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.278876E+09 | 0.456100E+10 | 0.264822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.337587E+09 | 0.534079E+10 | 0.303375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.293554E+09 | 0.483386E+10 | 0.281887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.322909E+09 | 0.519259E+10 | 0.298193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.199160E+09 | 0.513026E+10 | 0.292181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 68554512.00 | 0.306659E+10 | 0.178455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 78837688.80 | 0.323676E+10 | 0.185489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.181054E+09 | 0.474238E+10 | 0.277423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.308232E+09 | 0.504438E+10 | 0.293011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.308232E+09 | 0.498206E+10 | 0.287069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.293554E+09 | 0.489618E+10 | 0.287829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.297878E+10 | 0.560712E+11 | 0.324275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68554512.00 | 0.306659E+10 | 0.178455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.337587E+09 | 0.534079E+10 | 0.303375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.774708E+09 | 0.228198E+10 | 0.883684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392360E+09 |
| February | 0.700926E+09 | 0.206331E+10 | 0.798670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.326808E+09 |
| March | 0.848489E+09 | 0.241607E+10 | 0.914940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222400E+09 |
| April | 0.737817E+09 | 0.218674E+10 | 0.850137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 438977.45 | 0.212629E+09 |
| May | 0.811598E+09 | 0.234903E+10 | 0.899312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 168140.17 | 0.117418E+09 |
| June | 0.500567E+09 | 0.232083E+10 | 0.881180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1744295.23 | 67988084.31 |
| July | 0.172304E+09 | 0.138727E+10 | 0.538198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3161615.20 | 49135375.64 |
| August | 0.198150E+09 | 0.146425E+10 | 0.559411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 658181.63 | 63964033.28 |
| September | 0.455061E+09 | 0.214536E+10 | 0.836673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11708.08 | 0.120739E+09 |
| October | 0.774708E+09 | 0.228198E+10 | 0.883684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155597E+09 |
| November | 0.774708E+09 | 0.225379E+10 | 0.865765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254631E+09 |
| December | 0.737817E+09 | 0.221494E+10 | 0.868056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409369E+09 |
| Annual Sum or Average | 0.748685E+10 | 0.253655E+11 | 0.977971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6182917.75 | 0.239304E+10 |
| Minimum of Months | 0.172304E+09 | 0.138727E+10 | 0.538198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49135375.64 |
| Maximum of Months | 0.848489E+09 | 0.241607E+10 | 0.914940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3161615.20 | 0.409369E+09 |
Report: SpaceGainsMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.156120E+10 | 0.647363E+10 | 0.553791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169261E+10 |
| February | 0.141251E+10 | 0.585328E+10 | 0.500514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142154E+10 |
| March | 0.170988E+10 | 0.685401E+10 | 0.573379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988125E+09 |
| April | 0.148685E+10 | 0.620345E+10 | 0.532767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 492897.10 | 0.930904E+09 |
| May | 0.163554E+10 | 0.666382E+10 | 0.563585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2495323.75 | 0.488331E+09 |
| June | 0.163554E+10 | 0.658383E+10 | 0.552221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11901106.50 | 0.270285E+09 |
| July | 0.840841E+09 | 0.393546E+10 | 0.337280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14898132.79 | 0.197138E+09 |
| August | 0.966967E+09 | 0.415384E+10 | 0.350574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3637970.29 | 0.282099E+09 |
| September | 0.145455E+10 | 0.608605E+10 | 0.524330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 120922.93 | 0.527544E+09 |
| October | 0.156120E+10 | 0.647363E+10 | 0.553791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.689741E+09 |
| November | 0.156120E+10 | 0.639364E+10 | 0.542561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112332E+10 |
| December | 0.148685E+10 | 0.628344E+10 | 0.543997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176731E+10 |
| Annual Sum or Average | 0.173131E+11 | 0.719581E+11 | 0.612879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 33546353.36 | 0.103789E+11 |
| Minimum of Months | 0.840841E+09 | 0.393546E+10 | 0.337280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197138E+09 |
| Maximum of Months | 0.170988E+10 | 0.685401E+10 | 0.573379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14898132.79 | 0.176731E+10 |
Report: SpaceGainsMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.789800E+10 | 0.590754E+10 | 0.207549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691183E+09 |
| February | 0.714581E+10 | 0.534144E+10 | 0.187582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585036E+09 |
| March | 0.865019E+10 | 0.625466E+10 | 0.214891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418131E+09 |
| April | 0.752191E+10 | 0.566098E+10 | 0.199670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 100775.40 | 0.415958E+09 |
| May | 0.827410E+10 | 0.608110E+10 | 0.211220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1070828.58 | 0.214733E+09 |
| June | 0.827410E+10 | 0.600810E+10 | 0.206961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5319355.56 | 0.116732E+09 |
| July | 0.453307E+10 | 0.359132E+10 | 0.126406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6667221.61 | 84485412.47 |
| August | 0.521303E+10 | 0.379060E+10 | 0.131388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1631451.72 | 0.117160E+09 |
| September | 0.737247E+10 | 0.555385E+10 | 0.196508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53814.53 | 0.217052E+09 |
| October | 0.789800E+10 | 0.590754E+10 | 0.207549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291445E+09 |
| November | 0.789800E+10 | 0.583454E+10 | 0.203341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.473668E+09 |
| December | 0.752191E+10 | 0.573398E+10 | 0.203879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.723876E+09 |
| Annual Sum or Average | 0.882006E+11 | 0.656656E+11 | 0.229695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 14843447.39 | 0.434946E+10 |
| Minimum of Months | 0.453307E+10 | 0.359132E+10 | 0.126406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84485412.47 |
| Maximum of Months | 0.865019E+10 | 0.625466E+10 | 0.214891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6667221.61 | 0.723876E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.204475E+10 | 0.269034E+10 | 0.811357E+10 | 0.909844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381306E+09 |
| February | 0.185001E+10 | 0.243253E+10 | 0.733032E+10 | 0.822599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339028E+09 |
| March | 0.223949E+10 | 0.284842E+10 | 0.823336E+10 | 0.959699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244833E+09 |
| April | 0.194738E+10 | 0.257806E+10 | 0.783252E+10 | 0.872454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240043E+09 |
| May | 0.214212E+10 | 0.276938E+10 | 0.817347E+10 | 0.934772E+10 | 0.00 | 0.00 | 0.00 | 502686.52 | 0.112295E+09 |
| June | 0.132119E+10 | 0.273614E+10 | 0.795231E+10 | 0.922308E+10 | 0.00 | 0.00 | 0.00 | 1789117.99 | 62778846.86 |
| July | 0.454778E+09 | 0.163552E+10 | 0.805368E+10 | 0.884917E+10 | 0.00 | 0.00 | 0.00 | 2433558.70 | 44892556.56 |
| August | 0.522995E+09 | 0.172627E+10 | 0.823336E+10 | 0.959699E+10 | 0.00 | 0.00 | 0.00 | 714822.42 | 62257668.03 |
| September | 0.120108E+10 | 0.252927E+10 | 0.783252E+10 | 0.872454E+10 | 0.00 | 0.00 | 0.00 | 25292.93 | 0.113801E+09 |
| October | 0.204475E+10 | 0.269034E+10 | 0.811357E+10 | 0.909844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168983E+09 |
| November | 0.204475E+10 | 0.265710E+10 | 0.789242E+10 | 0.897381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282520E+09 |
| December | 0.194738E+10 | 0.261130E+10 | 0.805368E+10 | 0.884917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.401038E+09 |
| Annual Sum or Average | 0.197607E+11 | 0.299046E+11 | 0.958148E+11 | 0.108309E+12 | 0.00 | 0.00 | 0.00 | 5465478.57 | 0.245378E+10 |
| Minimum of Months | 0.454778E+09 | 0.163552E+10 | 0.733032E+10 | 0.822599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44892556.56 |
| Maximum of Months | 0.223949E+10 | 0.284842E+10 | 0.823336E+10 | 0.959699E+10 | 0.00 | 0.00 | 0.00 | 2433558.70 | 0.401038E+09 |
Report: SpaceGainsMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.229168E+11 | 0.378329E+10 | 0.253516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145602E+10 |
| February | 0.207343E+11 | 0.342075E+10 | 0.229042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122260E+10 |
| March | 0.250994E+11 | 0.400559E+10 | 0.257259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857334E+09 |
| April | 0.218255E+11 | 0.362539E+10 | 0.244734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1368671.45 | 0.791113E+09 |
| May | 0.240081E+11 | 0.389444E+10 | 0.255387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2263432.23 | 0.418081E+09 |
| June | 0.240081E+11 | 0.384769E+10 | 0.248477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8174044.14 | 0.241183E+09 |
| July | 0.556624E+10 | 0.229994E+10 | 0.251644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11600414.75 | 0.177108E+09 |
| August | 0.640118E+10 | 0.242757E+10 | 0.257259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3226997.53 | 0.240584E+09 |
| September | 0.210126E+11 | 0.355678E+10 | 0.244734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113877.67 | 0.436733E+09 |
| October | 0.229168E+11 | 0.378329E+10 | 0.253516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.581661E+09 |
| November | 0.229168E+11 | 0.373654E+10 | 0.246606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986240E+09 |
| December | 0.218255E+11 | 0.367214E+10 | 0.251644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152297E+10 |
| Annual Sum or Average | 0.239231E+12 | 0.420534E+11 | 0.299382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26747437.77 | 0.893163E+10 |
| Minimum of Months | 0.556624E+10 | 0.229994E+10 | 0.229042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177108E+09 |
| Maximum of Months | 0.250994E+11 | 0.400559E+10 | 0.257259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11600414.75 | 0.152297E+10 |
Report: SpaceGainsMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.325382E+10 | 0.825317E+10 | 0.695901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161432E+10 |
| February | 0.294393E+10 | 0.746230E+10 | 0.628953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135186E+10 |
| March | 0.356371E+10 | 0.873812E+10 | 0.720516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.936898E+09 |
| April | 0.309888E+10 | 0.790872E+10 | 0.669483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1540758.65 | 0.881328E+09 |
| May | 0.340876E+10 | 0.849564E+10 | 0.708208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2516471.53 | 0.471577E+09 |
| June | 0.210241E+10 | 0.839367E+10 | 0.693929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11688140.14 | 0.265312E+09 |
| July | 0.723690E+09 | 0.501728E+10 | 0.423831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15454666.77 | 0.188521E+09 |
| August | 0.832243E+09 | 0.529569E+10 | 0.440537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3820232.98 | 0.261900E+09 |
| September | 0.191128E+10 | 0.775905E+10 | 0.658880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 126552.89 | 0.503441E+09 |
| October | 0.325382E+10 | 0.825317E+10 | 0.695901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669873E+09 |
| November | 0.325382E+10 | 0.815120E+10 | 0.681790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108007E+10 |
| December | 0.309888E+10 | 0.801070E+10 | 0.683594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168764E+10 |
| Annual Sum or Average | 0.314452E+11 | 0.917387E+11 | 0.770152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35146822.95 | 0.991274E+10 |
| Minimum of Months | 0.723690E+09 | 0.501728E+10 | 0.423831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188521E+09 |
| Maximum of Months | 0.356371E+10 | 0.873812E+10 | 0.720516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15454666.77 | 0.168764E+10 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1205.18 | 04-JAN-06:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1504.91 | 12-FEB-22:58 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 750.08 | 15-MAR-05:06 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.77 | 23-APR-15:40 | 599.03 | 26-APR-20:03 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.46 | 24-MAY-15:00 | 326.19 | 20-MAY-05:53 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.25 | 24-JUN-17:00 | 207.83 | 03-JUN-07:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 175.85 | 15-JUL-16:00 | 212.37 | 08-JUL-14:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.11 | 08-AUG-16:00 | 300.65 | 27-AUG-06:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.77 | 01-SEP-15:00 | 390.02 | 20-SEP-01:00 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 516.23 | 31-OCT-20:03 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 809.44 | 21-NOV-21:03 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1195.85 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.83 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 175.85 | 1504.91 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3193.72 | 04-JAN-05:52 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4005.55 | 12-FEB-22:54 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1987.72 | 15-MAR-05:07 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 300.80 | 23-APR-15:40 | 1609.48 | 15-APR-15:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.62 | 24-MAY-15:00 | 943.83 | 20-MAY-06:00 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 270.51 | 24-JUN-17:00 | 609.50 | 03-JUN-09:00 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 523.30 | 15-JUL-15:10 | 589.37 | 08-JUL-14:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.15 | 26-AUG-16:10 | 824.48 | 27-AUG-06:00 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.83 | 01-SEP-15:00 | 1105.94 | 20-SEP-01:00 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1376.82 | 31-OCT-20:03 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2328.58 | 22-NOV-02:00 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3178.20 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 589.37 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 523.30 | 4005.55 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1178.08 | 02-JAN-08:09 | 947.12 | 02-JAN-07:10 | 678.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 180.77 | 04-JAN-05:54 |
| February | 1178.08 | 01-FEB-08:09 | 947.12 | 01-FEB-07:10 | 678.98 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 226.50 | 12-FEB-22:54 |
| March | 1178.08 | 01-MAR-08:09 | 947.12 | 01-MAR-07:10 | 678.98 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 112.51 | 15-MAR-05:09 |
| April | 1178.08 | 03-APR-07:10 | 947.12 | 03-APR-06:10 | 678.98 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.08 | 23-APR-15:43 | 91.23 | 15-APR-15:00 |
| May | 1178.08 | 01-MAY-07:10 | 947.12 | 01-MAY-06:10 | 678.98 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 | 24-MAY-15:00 | 54.41 | 20-MAY-05:53 |
| June | 1178.08 | 01-JUN-07:10 | 947.12 | 01-JUN-06:10 | 678.98 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.25 | 24-JUN-17:00 | 34.44 | 03-JUN-07:00 |
| July | 186.01 | 03-JUL-07:10 | 526.18 | 03-JUL-07:10 | 357.36 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.76 | 15-JUL-15:00 | 32.37 | 08-JUL-14:00 |
| August | 186.01 | 01-AUG-07:10 | 526.18 | 01-AUG-07:10 | 357.36 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.56 | 20-AUG-14:00 | 44.88 | 27-AUG-06:00 |
| September | 1178.08 | 18-SEP-07:10 | 947.12 | 05-SEP-06:10 | 678.98 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 01-SEP-15:00 | 62.84 | 20-SEP-01:00 |
| October | 1178.08 | 02-OCT-07:10 | 947.12 | 02-OCT-06:10 | 678.98 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 77.94 | 31-OCT-20:03 |
| November | 1178.08 | 01-NOV-07:10 | 947.12 | 01-NOV-06:10 | 678.98 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 134.42 | 22-NOV-02:00 |
| December | 1178.08 | 01-DEC-08:09 | 947.12 | 01-DEC-07:10 | 678.98 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 180.12 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.37 | |||||
| Maximum of Months | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 26.76 | 226.50 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1205.16 | 04-JAN-05:54 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1504.93 | 12-FEB-22:58 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 750.09 | 15-MAR-05:10 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.36 | 23-APR-15:40 | 598.12 | 26-APR-20:03 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.89 | 24-MAY-15:04 | 320.08 | 20-MAY-05:53 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.02 | 18-JUN-13:00 | 211.38 | 03-JUN-07:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.58 | 15-JUL-15:10 | 200.10 | 08-JUL-14:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.18 | 20-AUG-14:00 | 269.45 | 27-AUG-06:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.43 | 01-SEP-14:30 | 383.62 | 20-SEP-01:00 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 515.73 | 31-OCT-20:03 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 808.26 | 21-NOV-21:03 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1195.43 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.10 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 197.58 | 1504.93 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3193.76 | 04-JAN-05:52 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3988.04 | 12-FEB-23:00 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1987.71 | 15-MAR-05:09 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 517.48 | 23-APR-15:40 | 1600.67 | 26-APR-20:03 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.08 | 24-MAY-16:30 | 925.59 | 20-MAY-06:00 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 290.01 | 24-JUN-17:00 | 613.15 | 03-JUN-07:00 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 587.82 | 15-JUL-15:10 | 548.39 | 08-JUL-14:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.23 | 20-AUG-14:00 | 726.58 | 27-AUG-06:00 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.34 | 01-SEP-14:30 | 1089.16 | 20-SEP-01:00 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1375.53 | 31-OCT-20:03 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2295.88 | 22-NOV-02:00 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3177.58 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.39 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 587.82 | 3988.04 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1205.17 | 04-JAN-05:58 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1504.96 | 12-FEB-22:58 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 750.09 | 15-MAR-05:08 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 98.53 | 23-APR-15:40 | 598.95 | 26-APR-20:03 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.46 | 24-MAY-15:00 | 325.56 | 20-MAY-05:53 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 91.23 | 24-JUN-17:00 | 206.29 | 03-JUN-07:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 179.96 | 15-JUL-16:00 | 210.14 | 08-JUL-14:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.11 | 08-AUG-16:00 | 298.37 | 27-AUG-06:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.77 | 01-SEP-15:00 | 389.52 | 20-SEP-01:00 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 516.20 | 31-OCT-20:03 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 809.52 | 21-NOV-21:03 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1195.79 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.29 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 179.96 | 1504.96 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3193.68 | 04-JAN-05:54 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4004.94 | 12-FEB-22:54 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1987.71 | 15-MAR-05:06 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 309.67 | 23-APR-15:40 | 1604.25 | 15-APR-15:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.68 | 24-MAY-15:04 | 943.43 | 20-MAY-06:00 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 276.42 | 24-JUN-17:00 | 604.88 | 03-JUN-07:00 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 538.11 | 15-JUL-15:10 | 581.53 | 08-JUL-14:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 126.14 | 26-AUG-16:10 | 813.89 | 27-AUG-06:00 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.75 | 01-SEP-15:00 | 1106.57 | 20-SEP-01:00 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1376.98 | 31-OCT-20:03 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2329.89 | 22-NOV-02:00 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3178.48 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 581.53 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 538.11 | 4004.94 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1178.08 | 02-JAN-08:09 | 947.12 | 02-JAN-07:10 | 678.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 180.77 | 04-JAN-05:56 |
| February | 1178.08 | 01-FEB-08:09 | 947.12 | 01-FEB-07:10 | 678.98 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 226.51 | 12-FEB-22:54 |
| March | 1178.08 | 01-MAR-08:09 | 947.12 | 01-MAR-07:10 | 678.98 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 112.51 | 15-MAR-05:08 |
| April | 1178.08 | 03-APR-07:10 | 947.12 | 03-APR-06:10 | 678.98 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.27 | 23-APR-15:43 | 91.10 | 15-APR-15:00 |
| May | 1178.08 | 01-MAY-07:10 | 947.12 | 01-MAY-06:10 | 678.98 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 | 24-MAY-15:00 | 54.39 | 20-MAY-05:53 |
| June | 1178.08 | 01-JUN-07:10 | 947.12 | 01-JUN-06:10 | 678.98 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.37 | 24-JUN-17:00 | 34.39 | 03-JUN-07:00 |
| July | 186.01 | 03-JUL-07:10 | 526.18 | 03-JUL-07:10 | 357.36 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.09 | 15-JUL-15:00 | 32.21 | 08-JUL-14:00 |
| August | 186.01 | 01-AUG-07:10 | 526.18 | 01-AUG-07:10 | 357.36 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 | 20-AUG-14:00 | 44.59 | 27-AUG-06:00 |
| September | 1178.08 | 18-SEP-07:10 | 947.12 | 05-SEP-06:10 | 678.98 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 | 01-SEP-15:00 | 62.81 | 20-SEP-01:00 |
| October | 1178.08 | 02-OCT-07:10 | 947.12 | 02-OCT-06:10 | 678.98 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 77.94 | 31-OCT-20:03 |
| November | 1178.08 | 01-NOV-07:10 | 947.12 | 01-NOV-06:10 | 678.98 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 134.36 | 22-NOV-02:00 |
| December | 1178.08 | 01-DEC-08:09 | 947.12 | 01-DEC-07:10 | 678.98 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 180.11 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.21 | |||||
| Maximum of Months | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 27.09 | 226.51 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1205.16 | 04-JAN-05:58 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1504.95 | 12-FEB-22:58 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 750.08 | 15-MAR-05:08 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 173.36 | 23-APR-15:40 | 598.14 | 26-APR-20:03 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 | 24-MAY-15:04 | 320.09 | 20-MAY-05:53 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.94 | 18-JUN-13:00 | 211.52 | 03-JUN-07:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 197.74 | 15-JUL-15:10 | 199.95 | 08-JUL-14:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 74.21 | 20-AUG-14:00 | 269.03 | 27-AUG-06:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.45 | 01-SEP-14:30 | 383.55 | 20-SEP-01:00 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 515.78 | 31-OCT-20:03 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 808.20 | 21-NOV-21:03 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1195.42 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.95 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 197.74 | 1504.95 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3193.75 | 04-JAN-05:52 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3988.13 | 12-FEB-23:00 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1987.72 | 15-MAR-05:09 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 517.31 | 23-APR-15:40 | 1600.49 | 26-APR-20:03 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.00 | 24-MAY-16:30 | 925.73 | 20-MAY-06:00 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.74 | 24-JUN-17:00 | 613.50 | 03-JUN-07:00 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 588.06 | 15-JUL-15:10 | 548.12 | 08-JUL-14:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 237.21 | 20-AUG-14:00 | 725.47 | 27-AUG-06:00 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.36 | 01-SEP-14:30 | 1089.07 | 20-SEP-01:00 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1375.49 | 31-OCT-20:03 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2295.24 | 22-NOV-02:00 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3177.57 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 548.12 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 588.06 | 3988.13 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1205.16 | 04-JAN-06:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1504.96 | 12-FEB-23:00 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 750.08 | 15-MAR-05:06 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.64 | 23-APR-15:40 | 598.97 | 26-APR-20:03 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.46 | 24-MAY-15:00 | 326.16 | 20-MAY-05:53 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.37 | 24-JUN-17:00 | 207.34 | 03-JUN-07:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.99 | 15-JUL-15:10 | 211.70 | 08-JUL-14:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.11 | 08-AUG-16:00 | 300.45 | 27-AUG-06:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.77 | 01-SEP-15:00 | 390.93 | 20-SEP-01:00 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 516.34 | 31-OCT-20:03 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 810.37 | 22-NOV-02:00 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1195.86 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.34 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 177.99 | 1504.96 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 3193.70 | 04-JAN-05:52 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 4005.44 | 12-FEB-22:54 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1987.71 | 15-MAR-05:07 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 302.56 | 23-APR-15:40 | 1612.94 | 15-APR-15:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.62 | 24-MAY-15:00 | 945.50 | 20-MAY-06:00 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 273.14 | 24-JUN-17:00 | 609.19 | 03-JUN-09:00 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 530.56 | 15-JUL-15:10 | 587.36 | 08-JUL-14:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.63 | 26-AUG-16:10 | 822.97 | 27-AUG-06:00 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.25 | 01-SEP-15:00 | 1112.32 | 20-SEP-01:00 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1377.18 | 31-OCT-20:03 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2336.23 | 22-NOV-02:00 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 3178.34 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 587.36 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 530.56 | 4005.44 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1178.08 | 02-JAN-08:09 | 947.12 | 02-JAN-07:10 | 678.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 180.77 | 04-JAN-05:56 |
| February | 1178.08 | 01-FEB-08:09 | 947.12 | 01-FEB-07:10 | 678.98 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 226.50 | 12-FEB-22:54 |
| March | 1178.08 | 01-MAR-08:09 | 947.12 | 01-MAR-07:10 | 678.98 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 112.51 | 15-MAR-05:10 |
| April | 1178.08 | 03-APR-07:10 | 947.12 | 03-APR-06:10 | 678.98 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.27 | 23-APR-15:43 | 92.20 | 15-APR-15:00 |
| May | 1178.08 | 01-MAY-07:10 | 947.12 | 01-MAY-06:10 | 678.98 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 | 24-MAY-15:00 | 54.73 | 20-MAY-05:53 |
| June | 1178.08 | 01-JUN-07:10 | 947.12 | 01-JUN-06:10 | 678.98 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.86 | 24-JUN-17:00 | 34.96 | 03-JUN-07:00 |
| July | 186.01 | 03-JUL-07:10 | 526.18 | 03-JUL-07:10 | 357.36 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 | 15-JUL-15:00 | 33.00 | 08-JUL-14:00 |
| August | 186.01 | 01-AUG-07:10 | 526.18 | 01-AUG-07:10 | 357.36 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.03 | 20-AUG-14:00 | 45.58 | 27-AUG-06:00 |
| September | 1178.08 | 18-SEP-07:10 | 947.12 | 05-SEP-06:10 | 678.98 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.90 | 01-SEP-15:00 | 63.48 | 20-SEP-01:00 |
| October | 1178.08 | 02-OCT-07:10 | 947.12 | 02-OCT-06:10 | 678.98 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 77.99 | 31-OCT-20:03 |
| November | 1178.08 | 01-NOV-07:10 | 947.12 | 01-NOV-06:10 | 678.98 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 135.05 | 22-NOV-02:00 |
| December | 1178.08 | 01-DEC-08:09 | 947.12 | 01-DEC-07:10 | 678.98 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 180.13 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.00 | |||||
| Maximum of Months | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 26.04 | 226.50 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1205.16 | 04-JAN-05:58 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1504.93 | 12-FEB-22:58 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 750.09 | 15-MAR-05:09 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 169.37 | 23-APR-15:40 | 598.31 | 26-APR-20:03 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.72 | 24-MAY-15:04 | 321.49 | 20-MAY-06:00 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.63 | 18-JUN-12:20 | 215.17 | 03-JUN-07:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.35 | 15-JUL-15:10 | 204.00 | 08-JUL-14:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.94 | 20-AUG-14:00 | 273.02 | 27-AUG-06:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.10 | 01-SEP-14:30 | 385.55 | 20-SEP-01:00 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 515.84 | 31-OCT-20:03 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 808.38 | 21-NOV-21:03 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1195.48 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.00 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 192.35 | 1504.93 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 9663.62 | 02-JAN-08:09 | 4272.19 | 02-JAN-07:10 | 4177.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2109.05 | 04-JAN-05:56 |
| February | 9663.62 | 01-FEB-08:09 | 4272.19 | 01-FEB-07:10 | 4177.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2633.65 | 12-FEB-22:58 |
| March | 9663.62 | 01-MAR-08:09 | 4272.19 | 01-MAR-07:10 | 4177.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1312.65 | 15-MAR-05:08 |
| April | 9663.62 | 03-APR-07:10 | 4272.19 | 03-APR-06:10 | 4177.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 333.63 | 23-APR-15:40 | 1057.23 | 26-APR-20:03 |
| May | 9663.62 | 01-MAY-07:10 | 4272.19 | 01-MAY-06:10 | 4177.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.24 | 24-MAY-15:04 | 613.86 | 20-MAY-06:00 |
| June | 9663.62 | 01-JUN-07:10 | 4272.19 | 01-JUN-06:10 | 4177.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.63 | 24-JUN-17:00 | 413.92 | 03-JUN-07:00 |
| July | 1525.83 | 03-JUL-07:10 | 2373.44 | 03-JUL-07:10 | 2198.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 374.76 | 15-JUL-15:10 | 370.84 | 08-JUL-14:00 |
| August | 1525.83 | 01-AUG-07:10 | 2373.44 | 01-AUG-07:10 | 2198.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.87 | 20-AUG-14:00 | 486.95 | 27-AUG-06:00 |
| September | 9663.62 | 18-SEP-07:10 | 4272.19 | 05-SEP-06:10 | 4177.31 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.13 | 01-SEP-14:30 | 723.07 | 20-SEP-01:00 |
| October | 9663.62 | 02-OCT-07:10 | 4272.19 | 02-OCT-06:10 | 4177.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 908.52 | 31-OCT-20:03 |
| November | 9663.62 | 01-NOV-07:10 | 4272.19 | 01-NOV-06:10 | 4177.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1516.61 | 22-NOV-02:00 |
| December | 9663.62 | 01-DEC-08:09 | 4272.19 | 01-DEC-07:10 | 4177.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2098.02 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 1525.83 | 2373.44 | 2198.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370.84 | |||||
| Maximum of Months | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 374.76 | 2633.65 |
Report: PeakSpaceGainsMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 4969.86 | 02-JAN-08:09 | 2197.13 | 02-JAN-07:10 | 2864.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1084.66 | 04-JAN-05:52 |
| February | 4969.86 | 01-FEB-08:09 | 2197.13 | 01-FEB-07:10 | 2864.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1355.08 | 12-FEB-22:54 |
| March | 4969.86 | 01-MAR-08:09 | 2197.13 | 01-MAR-07:10 | 2864.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 675.08 | 15-MAR-05:09 |
| April | 4969.86 | 03-APR-07:10 | 2197.13 | 03-APR-06:10 | 2864.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.54 | 23-APR-15:40 | 554.89 | 26-APR-20:03 |
| May | 4969.86 | 01-MAY-07:10 | 2197.13 | 01-MAY-06:10 | 2864.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.81 | 24-MAY-15:00 | 329.15 | 20-MAY-06:00 |
| June | 4969.86 | 01-JUN-07:10 | 2197.13 | 01-JUN-06:10 | 2864.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.84 | 24-JUN-17:00 | 226.37 | 03-JUN-07:00 |
| July | 2615.72 | 03-JUL-07:10 | 1220.63 | 03-JUL-07:10 | 1507.60 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 177.61 | 15-JUL-15:10 | 207.90 | 08-JUL-14:00 |
| August | 2615.72 | 01-AUG-07:10 | 1220.63 | 01-AUG-07:10 | 1507.60 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.59 | 20-AUG-14:00 | 269.08 | 27-AUG-06:00 |
| September | 4969.86 | 05-SEP-07:10 | 2197.13 | 05-SEP-06:10 | 2864.44 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 | 01-SEP-15:00 | 390.43 | 20-SEP-01:00 |
| October | 4969.86 | 02-OCT-07:10 | 2197.13 | 02-OCT-06:10 | 2864.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 478.41 | 31-OCT-20:03 |
| November | 4969.86 | 01-NOV-07:10 | 2197.13 | 01-NOV-06:10 | 2864.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 809.69 | 22-NOV-02:00 |
| December | 4969.86 | 01-DEC-08:09 | 2197.13 | 01-DEC-07:10 | 2864.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1079.74 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2615.72 | 1220.63 | 1507.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.90 | |||||
| Maximum of Months | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 177.61 | 1355.08 |
Report: PeakSpaceGainsMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3350.23 | 02-JAN-08:09 | 2693.36 | 02-JAN-07:10 | 1930.85 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 542.32 | 04-JAN-05:52 |
| February | 3350.23 | 01-FEB-08:09 | 2693.36 | 01-FEB-07:10 | 1930.85 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 679.10 | 12-FEB-22:54 |
| March | 3350.23 | 01-MAR-08:09 | 2693.36 | 01-MAR-07:10 | 1930.85 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 337.54 | 15-MAR-05:10 |
| April | 3350.23 | 03-APR-07:10 | 2693.36 | 03-APR-06:10 | 1930.85 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.65 | 23-APR-15:43 | 281.90 | 15-APR-15:00 |
| May | 3350.23 | 01-MAY-07:10 | 2693.36 | 01-MAY-06:10 | 1930.85 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.40 | 24-MAY-15:00 | 169.54 | 20-MAY-06:00 |
| June | 3350.23 | 01-JUN-07:10 | 2693.36 | 01-JUN-06:10 | 1930.85 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.06 | 29-JUN-20:01 | 109.86 | 03-JUN-07:00 |
| July | 528.98 | 03-JUL-07:10 | 1496.31 | 03-JUL-07:10 | 1016.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.75 | 15-JUL-15:00 | 107.59 | 08-JUL-14:00 |
| August | 528.98 | 01-AUG-07:10 | 1496.31 | 01-AUG-07:10 | 1016.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 | 08-AUG-16:00 | 141.80 | 27-AUG-06:00 |
| September | 3350.23 | 18-SEP-07:10 | 2693.36 | 05-SEP-06:10 | 1930.85 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 | 01-SEP-15:00 | 191.13 | 20-SEP-01:00 |
| October | 3350.23 | 02-OCT-07:10 | 2693.36 | 02-OCT-06:10 | 1930.85 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 233.67 | 31-OCT-20:03 |
| November | 3350.23 | 01-NOV-07:10 | 2693.36 | 01-NOV-06:10 | 1930.85 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 397.74 | 22-NOV-02:00 |
| December | 3350.23 | 01-DEC-08:09 | 2693.36 | 01-DEC-07:10 | 1930.85 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 535.75 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 528.98 | 1496.31 | 1016.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.59 | |||||
| Maximum of Months | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 69.75 | 679.10 |
Report: PeakSpaceGainsMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 2098.51 | 02-JAN-08:09 | 2153.53 | 02-JAN-07:10 | 604.72 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 188908.83 | 26-JAN-07:01 |
| February | 2098.51 | 01-FEB-08:09 | 2153.53 | 01-FEB-07:10 | 604.72 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 181978.83 | 14-FEB-07:01 |
| March | 2098.51 | 01-MAR-08:09 | 2153.53 | 01-MAR-07:10 | 604.72 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 146652.59 | 16-MAR-06:01 |
| April | 2098.51 | 03-APR-07:10 | 2153.53 | 03-APR-06:10 | 604.72 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.38 | 23-APR-15:40 | 109095.42 | 05-APR-06:01 |
| May | 2098.51 | 01-MAY-07:10 | 2153.53 | 01-MAY-06:10 | 604.72 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13560.67 | 18-MAY-14:02 | 72886.02 | 01-MAY-06:01 |
| June | 2098.51 | 01-JUN-07:10 | 2153.53 | 01-JUN-06:10 | 604.72 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27532.76 | 29-JUN-14:01 | 40081.28 | 02-JUN-06:01 |
| July | 331.34 | 03-JUL-07:10 | 1196.41 | 03-JUL-07:10 | 318.27 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15973.69 | 24-JUL-14:02 | 35309.99 | 18-JUL-06:01 |
| August | 331.34 | 01-AUG-07:10 | 1196.41 | 01-AUG-07:10 | 318.27 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18510.07 | 08-AUG-14:01 | 44131.10 | 25-AUG-06:01 |
| September | 2098.51 | 18-SEP-07:10 | 2153.53 | 05-SEP-06:10 | 604.72 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5737.53 | 01-SEP-15:00 | 66001.95 | 06-SEP-06:01 |
| October | 2098.51 | 02-OCT-07:10 | 2153.53 | 02-OCT-06:10 | 604.72 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 92817.53 | 30-OCT-06:01 |
| November | 2098.51 | 01-NOV-07:10 | 2153.53 | 01-NOV-06:10 | 604.72 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 127909.43 | 29-NOV-07:01 |
| December | 2098.51 | 01-DEC-08:09 | 2153.53 | 01-DEC-07:10 | 604.72 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 164306.22 | 20-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35309.99 | |||||
| Maximum of Months | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 27532.76 | 188908.83 |
Report: PeakSpaceGainsMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 463.87 | 02-JAN-08:09 | 3661.88 | 02-JAN-07:10 | 2227.90 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
| February | 463.87 | 01-FEB-08:09 | 3661.88 | 01-FEB-07:10 | 2227.90 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
| March | 463.87 | 01-MAR-08:09 | 3661.88 | 01-MAR-07:10 | 2227.90 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
| April | 463.87 | 03-APR-07:10 | 3661.88 | 03-APR-06:10 | 2227.90 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 463.87 | 01-MAY-07:10 | 3661.88 | 01-MAY-06:10 | 2227.90 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 463.87 | 01-JUN-07:10 | 3661.88 | 01-JUN-06:10 | 2227.90 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 |
| July | 73.24 | 03-JUL-07:10 | 2034.38 | 03-JUL-07:10 | 1172.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 01-JUL-00:03 |
| August | 73.24 | 01-AUG-07:10 | 2034.38 | 01-AUG-07:10 | 1172.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:03 |
| September | 463.87 | 18-SEP-07:10 | 3661.88 | 05-SEP-06:10 | 2227.90 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 |
| October | 463.87 | 02-OCT-07:10 | 3661.88 | 02-OCT-06:10 | 2227.90 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 463.87 | 01-NOV-07:10 | 3661.88 | 01-NOV-06:10 | 2227.90 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 463.87 | 01-DEC-08:09 | 3661.88 | 01-DEC-07:10 | 2227.90 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 73.24 | 2034.38 | 1172.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
| Maximum of Months | 463.87 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1165.88 | 02-JAN-08:09 | 1656.56 | 02-JAN-07:10 | 671.91 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 602.58 | 04-JAN-06:00 |
| February | 1165.88 | 01-FEB-08:09 | 1656.56 | 01-FEB-07:10 | 671.91 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 752.47 | 12-FEB-22:58 |
| March | 1165.88 | 01-MAR-08:09 | 1656.56 | 01-MAR-07:10 | 671.91 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 362.03 | 15-MAR-04:55 |
| April | 1165.88 | 03-APR-07:10 | 1656.56 | 03-APR-06:10 | 671.91 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.37 | 23-APR-15:43 | 303.64 | 15-APR-15:00 |
| May | 1165.88 | 01-MAY-07:10 | 1656.56 | 01-MAY-06:10 | 671.91 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 | 24-MAY-15:04 | 190.85 | 20-MAY-05:53 |
| June | 1165.88 | 01-JUN-07:10 | 1656.56 | 01-JUN-06:10 | 671.91 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.68 | 24-JUN-17:00 | 122.99 | 03-JUN-07:00 |
| July | 184.09 | 03-JUL-07:10 | 920.31 | 03-JUL-07:10 | 353.64 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.52 | 15-JUL-15:00 | 125.29 | 08-JUL-14:00 |
| August | 184.09 | 01-AUG-07:10 | 920.31 | 01-AUG-07:10 | 353.64 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.76 | 08-AUG-15:25 | 162.96 | 27-AUG-06:00 |
| September | 1165.88 | 18-SEP-07:10 | 1656.56 | 05-SEP-06:10 | 671.91 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.78 | 01-SEP-15:00 | 213.44 | 20-SEP-01:00 |
| October | 1165.88 | 02-OCT-07:10 | 1656.56 | 02-OCT-06:10 | 671.91 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 244.80 | 31-OCT-21:00 |
| November | 1165.88 | 01-NOV-07:10 | 1656.56 | 01-NOV-06:10 | 671.91 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 422.56 | 22-NOV-02:00 |
| December | 1165.88 | 01-DEC-08:09 | 1656.56 | 01-DEC-07:10 | 671.91 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 573.28 | 16-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 184.09 | 920.31 | 353.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.99 | |||||
| Maximum of Months | 1165.88 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 70.52 | 752.47 |
Report: PeakSpaceGainsMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 2705.96 | 02-JAN-08:09 | 4699.41 | 02-JAN-07:10 | 4210.73 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2530.84 | 04-JAN-05:56 |
| February | 2705.96 | 01-FEB-08:09 | 4699.41 | 01-FEB-07:10 | 4210.73 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3160.38 | 12-FEB-23:00 |
| March | 2705.96 | 01-MAR-08:09 | 4699.41 | 01-MAR-07:10 | 4210.73 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1575.16 | 15-MAR-05:09 |
| April | 2705.96 | 03-APR-07:10 | 4699.41 | 03-APR-06:10 | 4210.73 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 145.15 | 23-APR-15:40 | 1301.93 | 15-APR-15:00 |
| May | 2705.96 | 01-MAY-07:10 | 4699.41 | 01-MAY-06:10 | 4210.73 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.55 | 24-MAY-15:00 | 763.06 | 20-MAY-06:00 |
| June | 2705.96 | 01-JUN-07:10 | 4699.41 | 01-JUN-06:10 | 4210.73 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 138.89 | 29-JUN-20:01 | 546.61 | 03-JUN-09:00 |
| July | 1424.19 | 03-JUL-07:10 | 2610.78 | 03-JUL-07:10 | 2216.18 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.87 | 15-JUL-15:00 | 505.56 | 08-JUL-14:00 |
| August | 1424.19 | 01-AUG-07:10 | 2610.78 | 01-AUG-07:10 | 2216.18 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 75.83 | 08-AUG-16:00 | 698.63 | 27-AUG-06:00 |
| September | 2705.96 | 05-SEP-07:10 | 4699.41 | 05-SEP-06:10 | 4210.73 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.12 | 01-SEP-15:00 | 887.91 | 20-SEP-01:00 |
| October | 2705.96 | 02-OCT-07:10 | 4699.41 | 02-OCT-06:10 | 4210.73 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1089.62 | 31-OCT-20:03 |
| November | 2705.96 | 01-NOV-07:10 | 4699.41 | 01-NOV-06:10 | 4210.73 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1804.70 | 22-NOV-02:00 |
| December | 2705.96 | 01-DEC-08:09 | 4699.41 | 01-DEC-07:10 | 4210.73 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2517.65 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 1424.19 | 2610.78 | 2216.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.56 | |||||
| Maximum of Months | 2705.96 | 4699.41 | 4210.73 | 0.00 | 0.00 | 0.00 | 0.00 | 288.87 | 3160.38 |
Report: PeakSpaceGainsMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 13145.35 | 02-JAN-16:10 | 4288.47 | 02-JAN-07:10 | 1578.10 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 1049.55 | 04-JAN-06:10 |
| February | 13145.35 | 01-FEB-16:10 | 4288.47 | 01-FEB-07:10 | 1578.10 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1282.35 | 12-FEB-22:54 |
| March | 13145.35 | 01-MAR-16:10 | 4288.47 | 01-MAR-07:10 | 1578.10 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 674.04 | 15-MAR-05:10 |
| April | 13145.35 | 03-APR-15:09 | 4288.47 | 03-APR-06:10 | 1578.10 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.62 | 23-APR-15:40 | 585.32 | 15-APR-15:00 |
| May | 13145.35 | 01-MAY-15:09 | 4288.47 | 01-MAY-06:10 | 1578.10 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.99 | 24-MAY-15:00 | 328.05 | 20-MAY-06:00 |
| June | 13145.35 | 01-JUN-15:09 | 4288.47 | 01-JUN-06:10 | 1578.10 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.42 | 24-JUN-17:00 | 250.57 | 03-JUN-09:00 |
| July | 4843.02 | 03-JUL-07:10 | 2382.48 | 03-JUL-07:10 | 830.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.97 | 15-JUL-14:50 | 228.18 | 08-JUL-14:00 |
| August | 4843.02 | 01-AUG-07:10 | 2382.48 | 01-AUG-07:10 | 830.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.70 | 08-AUG-16:00 | 294.89 | 27-AUG-06:00 |
| September | 13145.35 | 05-SEP-15:09 | 4288.47 | 05-SEP-06:10 | 1578.10 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.91 | 01-SEP-15:00 | 372.72 | 20-SEP-01:00 |
| October | 13145.35 | 02-OCT-15:09 | 4288.47 | 02-OCT-06:10 | 1578.10 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 466.67 | 31-OCT-20:03 |
| November | 13145.35 | 01-NOV-15:09 | 4288.47 | 01-NOV-06:10 | 1578.10 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 786.13 | 22-NOV-02:00 |
| December | 13145.35 | 01-DEC-16:10 | 4288.47 | 01-DEC-07:10 | 1578.10 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1020.67 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 4843.02 | 2382.48 | 830.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.18 | |||||
| Maximum of Months | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.97 | 1282.35 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3077.20 | 02-JAN-08:09 | 1953.00 | 02-JAN-07:10 | 6399.12 | 02-JAN-10:09 | 14425.49 | 02-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 538.86 | 04-JAN-05:52 |
| February | 3077.20 | 01-FEB-08:09 | 1953.00 | 01-FEB-07:10 | 6399.12 | 01-FEB-10:09 | 14425.49 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 722.77 | 12-FEB-22:52 |
| March | 3077.20 | 01-MAR-08:09 | 1953.00 | 01-MAR-07:10 | 6399.12 | 01-MAR-10:09 | 14425.49 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 382.98 | 17-MAR-04:00 |
| April | 3077.20 | 03-APR-07:10 | 1953.00 | 03-APR-06:10 | 6399.12 | 03-APR-09:09 | 14425.49 | 03-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 342.82 | 01-APR-19:00 |
| May | 3077.20 | 01-MAY-07:10 | 1953.00 | 01-MAY-06:10 | 6399.12 | 01-MAY-09:09 | 14425.49 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 6.58 | 24-MAY-15:00 | 182.29 | 09-MAY-03:10 |
| June | 3077.20 | 01-JUN-07:10 | 1953.00 | 01-JUN-06:10 | 6399.12 | 01-JUN-09:09 | 14425.49 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 24.88 | 29-JUN-20:01 | 137.19 | 20-JUN-03:30 |
| July | 485.87 | 03-JUL-07:10 | 1085.00 | 03-JUL-07:10 | 6399.12 | 03-JUL-09:09 | 14425.49 | 03-JUL-09:09 | 0.00 | 0.00 | 0.00 | 46.23 | 15-JUL-15:00 | 127.52 | 08-JUL-14:10 |
| August | 485.87 | 01-AUG-07:10 | 1085.00 | 01-AUG-07:10 | 6399.12 | 01-AUG-09:09 | 14425.49 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 14.44 | 08-AUG-16:00 | 147.69 | 27-AUG-06:00 |
| September | 3077.20 | 18-SEP-07:10 | 1953.00 | 05-SEP-06:10 | 6399.12 | 01-SEP-09:09 | 14425.49 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 2.31 | 01-SEP-15:00 | 204.74 | 20-SEP-01:10 |
| October | 3077.20 | 02-OCT-07:10 | 1953.00 | 02-OCT-06:10 | 6399.12 | 02-OCT-09:09 | 14425.49 | 02-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 260.14 | 31-OCT-21:00 |
| November | 3077.20 | 01-NOV-07:10 | 1953.00 | 01-NOV-06:10 | 6399.12 | 01-NOV-09:09 | 14425.49 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 477.60 | 22-NOV-02:00 |
| December | 3077.20 | 01-DEC-08:09 | 1953.00 | 01-DEC-07:10 | 6399.12 | 01-DEC-10:09 | 14425.49 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 565.62 | 16-DEC-06:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 485.87 | 1085.00 | 6399.12 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 127.52 | ||||||
| Maximum of Months | 3077.20 | 1953.00 | 6399.12 | 14425.49 | 0.00 | 0.00 | 0.00 | 46.23 | 722.77 |
Report: PeakSpaceGainsMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 38654.47 | 02-JAN-09:09 | 2746.41 | 02-JAN-07:10 | 1999.46 | 02-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2161.79 | 03-JAN-21:01 |
| February | 38654.47 | 01-FEB-09:09 | 2746.41 | 01-FEB-07:10 | 1999.46 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2688.27 | 12-FEB-22:52 |
| March | 38654.47 | 01-MAR-09:09 | 2746.41 | 01-MAR-07:10 | 1999.46 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1452.53 | 15-MAR-05:08 |
| April | 38654.47 | 03-APR-08:09 | 2746.41 | 03-APR-06:10 | 1999.46 | 03-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 143.13 | 23-APR-15:53 | 1109.85 | 15-APR-15:00 |
| May | 38654.47 | 01-MAY-08:09 | 2746.41 | 01-MAY-06:10 | 1999.46 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.60 | 24-MAY-15:00 | 653.03 | 20-MAY-06:00 |
| June | 38654.47 | 01-JUN-08:09 | 2746.41 | 01-JUN-06:10 | 1999.46 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 118.26 | 29-JUN-20:01 | 467.50 | 03-JUN-09:00 |
| July | 14241.12 | 03-JUL-16:10 | 1525.78 | 03-JUL-07:10 | 1999.46 | 03-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 203.94 | 15-JUL-14:50 | 434.54 | 08-JUL-14:00 |
| August | 14241.12 | 01-AUG-16:10 | 1525.78 | 01-AUG-07:10 | 1999.46 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 65.00 | 08-AUG-16:00 | 590.86 | 27-AUG-06:00 |
| September | 38654.47 | 05-SEP-08:09 | 2746.41 | 05-SEP-06:10 | 1999.46 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10.39 | 01-SEP-15:00 | 752.51 | 20-SEP-01:00 |
| October | 38654.47 | 02-OCT-08:09 | 2746.41 | 02-OCT-06:10 | 1999.46 | 02-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 935.79 | 31-OCT-20:03 |
| November | 38654.47 | 01-NOV-08:09 | 2746.41 | 01-NOV-06:10 | 1999.46 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1629.58 | 22-NOV-02:00 |
| December | 38654.47 | 01-DEC-09:09 | 2746.41 | 01-DEC-07:10 | 1999.46 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2158.23 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 14241.12 | 1525.78 | 1999.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.54 | |||||
| Maximum of Months | 38654.47 | 2746.41 | 1999.46 | 0.00 | 0.00 | 0.00 | 0.00 | 203.94 | 2688.27 |
Report: PeakSpaceGainsMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 4896.76 | 02-JAN-08:09 | 5991.24 | 02-JAN-07:10 | 5291.26 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 2410.32 | 04-JAN-05:58 |
| February | 4896.76 | 01-FEB-08:09 | 5991.24 | 01-FEB-07:10 | 5291.26 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 3009.88 | 12-FEB-23:00 |
| March | 4896.76 | 01-MAR-08:09 | 5991.24 | 01-MAR-07:10 | 5291.26 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 1500.17 | 15-MAR-05:08 |
| April | 4896.76 | 03-APR-07:10 | 5991.24 | 03-APR-06:10 | 5291.26 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 220.66 | 23-APR-15:40 | 1242.52 | 15-APR-15:00 |
| May | 4896.76 | 01-MAY-07:10 | 5991.24 | 01-MAY-06:10 | 5291.26 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.91 | 24-MAY-15:00 | 741.20 | 20-MAY-06:00 |
| June | 4896.76 | 01-JUN-07:10 | 5991.24 | 01-JUN-06:10 | 5291.26 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.68 | 24-JUN-17:00 | 546.17 | 03-JUN-09:00 |
| July | 773.17 | 03-JUL-07:10 | 3328.47 | 03-JUL-07:10 | 2784.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 289.90 | 15-JUL-15:10 | 489.61 | 08-JUL-14:00 |
| August | 773.17 | 01-AUG-07:10 | 3328.47 | 01-AUG-07:10 | 2784.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.22 | 08-AUG-16:00 | 654.31 | 27-AUG-06:00 |
| September | 4896.76 | 18-SEP-07:10 | 5991.24 | 05-SEP-06:10 | 5291.26 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 01-SEP-15:00 | 868.47 | 20-SEP-01:00 |
| October | 4896.76 | 02-OCT-07:10 | 5991.24 | 02-OCT-06:10 | 5291.26 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1040.27 | 31-OCT-20:03 |
| November | 4896.76 | 01-NOV-07:10 | 5991.24 | 01-NOV-06:10 | 5291.26 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1763.20 | 22-NOV-02:00 |
| December | 4896.76 | 01-DEC-08:09 | 5991.24 | 01-DEC-07:10 | 5291.26 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2398.64 | 18-DEC-21:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 773.17 | 3328.47 | 2784.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 489.61 | |||||
| Maximum of Months | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 289.90 | 3009.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2148.43 | 27-JAN-15:30 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 2469.14 | 28-FEB-15:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.19 |
| March | 2629.50 | 31-MAR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.79 |
| April | 3874.88 | 13-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 |
| May | 6190.37 | 18-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 0.00 |
| June | 5431.43 | 08-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
| July | 4285.25 | 24-JUL-15:03 | 2877.29 | 4475.63 | 4145.91 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 0.00 |
| August | 6784.06 | 13-AUG-15:18 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.02 |
| September | 5433.05 | 03-SEP-14:30 | 0.00 | 1322.55 | 2026.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.52 |
| October | 5416.03 | 20-OCT-14:30 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 |
| November | 2701.90 | 17-NOV-15:40 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.22 |
| December | 1948.04 | 28-DEC-14:40 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.79 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1948.04 | 0.00 | 1322.55 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6784.06 | 6074.27 | 4475.63 | 4145.91 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 120.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 10533.96 | 27-JAN-15:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 11793.88 | 08-FEB-15:10 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.45 |
| March | 12949.94 | 31-MAR-14:40 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.89 |
| April | 17567.15 | 18-APR-14:02 | 73167.38 | 32346.60 | 31628.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.19 |
| May | 26358.58 | 18-MAY-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 31.18 | 0.00 |
| June | 23433.39 | 08-JUN-14:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
| July | 18074.73 | 23-JUL-14:02 | 0.00 | 7646.74 | 8367.97 | 0.00 | 0.00 | 0.00 | 0.00 | 241.27 | 0.00 |
| August | 20839.07 | 12-AUG-13:11 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.17 |
| September | 23519.21 | 25-SEP-14:03 | 117067.81 | 51754.55 | 50605.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.02 |
| October | 24164.56 | 20-OCT-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.66 |
| November | 13438.93 | 17-NOV-13:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.93 |
| December | 9970.86 | 28-DEC-14:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.52 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 9970.86 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 26358.58 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 241.27 | 236.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 863.67 | 26-JAN-21:11 | 0.00 | 1306.07 | 1467.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.65 |
| February | 1076.28 | 08-FEB-16:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 |
| March | 1244.42 | 31-MAR-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.69 |
| April | 2010.66 | 21-APR-14:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 |
| May | 4664.61 | 18-MAY-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 | 0.00 |
| June | 4531.96 | 30-JUN-15:00 | 186.01 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 | 0.00 |
| July | 3167.98 | 24-JUL-14:50 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 0.00 |
| August | 2367.53 | 12-AUG-13:11 | 0.00 | 1865.82 | 1497.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.97 |
| September | 2879.05 | 05-SEP-15:50 | 186.01 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.37 |
| October | 2217.04 | 20-OCT-14:01 | 8246.53 | 6629.82 | 4752.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 |
| November | 1275.78 | 01-NOV-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.37 |
| December | 868.02 | 21-DEC-21:11 | 0.00 | 1306.07 | 1467.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.04 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 863.67 | 0.00 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4664.61 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 | 80.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1765.98 | 19-JAN-08:03 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.71 |
| February | 1936.06 | 08-FEB-16:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.31 |
| March | 2093.41 | 31-MAR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.59 |
| April | 3297.43 | 13-APR-14:02 | 15185.68 | 6713.44 | 6564.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 |
| May | 4937.48 | 18-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 0.00 |
| June | 4625.01 | 08-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
| July | 3662.42 | 16-JUL-16:39 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.88 |
| August | 3866.71 | 12-AUG-13:11 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.88 |
| September | 3726.44 | 18-SEP-14:02 | 18222.82 | 8056.13 | 7877.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.95 |
| October | 3659.42 | 20-OCT-14:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 |
| November | 2355.97 | 01-NOV-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.85 |
| December | 1778.46 | 06-DEC-08:03 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.43 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1765.98 | 0.00 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4937.48 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 90.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 8659.21 | 19-JAN-08:03 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.14 |
| February | 9278.76 | 08-FEB-15:10 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.75 |
| March | 10373.75 | 31-MAR-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.52 |
| April | 16026.75 | 13-APR-14:02 | 73167.38 | 32346.60 | 31628.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.90 |
| May | 19924.32 | 25-MAY-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 0.00 |
| June | 19377.10 | 08-JUN-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
| July | 17035.87 | 05-JUL-05:01 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.85 |
| August | 17838.62 | 12-AUG-13:11 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.75 |
| September | 17949.48 | 18-SEP-14:02 | 87800.86 | 38815.92 | 37953.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.60 |
| October | 17538.13 | 20-OCT-14:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.10 |
| November | 11677.22 | 01-NOV-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.04 |
| December | 8718.84 | 06-DEC-08:03 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.57 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 8659.21 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 19924.32 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 240.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2082.53 | 27-JAN-15:30 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 2454.58 | 28-FEB-15:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.99 |
| March | 2611.18 | 31-MAR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.58 |
| April | 3790.83 | 13-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 |
| May | 6095.69 | 18-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 0.00 |
| June | 5312.61 | 08-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
| July | 4146.69 | 24-JUL-15:03 | 2877.29 | 4475.63 | 4145.91 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 0.00 |
| August | 4380.28 | 12-AUG-13:11 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.24 |
| September | 5112.57 | 25-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.16 |
| October | 5360.58 | 20-OCT-14:30 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 |
| November | 2682.52 | 17-NOV-15:40 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.89 |
| December | 1892.51 | 28-DEC-14:40 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.39 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1892.51 | 0.00 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6095.69 | 6074.27 | 4475.63 | 4145.91 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 92.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 10275.91 | 27-JAN-14:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 11723.08 | 08-FEB-15:10 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.95 |
| March | 12839.74 | 31-MAR-14:40 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.19 |
| April | 17547.14 | 18-APR-14:02 | 73167.38 | 32346.60 | 31628.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.87 |
| May | 25814.03 | 18-MAY-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 31.18 | 0.00 |
| June | 22716.70 | 08-JUN-14:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
| July | 17806.22 | 01-JUL-10:31 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.10 |
| August | 20484.32 | 12-AUG-13:11 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.99 |
| September | 22931.86 | 25-SEP-14:03 | 117067.81 | 51754.55 | 50605.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.02 |
| October | 23583.42 | 20-OCT-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.66 |
| November | 13040.58 | 17-NOV-13:20 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.49 |
| December | 9740.16 | 28-DEC-14:10 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.65 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 9740.16 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 25814.03 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 31.18 | 224.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 857.55 | 26-JAN-21:11 | 0.00 | 1306.07 | 1467.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.63 |
| February | 1069.81 | 08-FEB-16:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 |
| March | 1234.50 | 31-MAR-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.68 |
| April | 1999.45 | 21-APR-14:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.66 |
| May | 4625.67 | 18-MAY-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 | 0.00 |
| June | 4485.49 | 30-JUN-15:00 | 186.01 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 | 0.00 |
| July | 3046.92 | 24-JUL-14:50 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 0.00 |
| August | 2342.41 | 12-AUG-13:11 | 0.00 | 1865.82 | 1497.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.75 |
| September | 2807.08 | 08-SEP-16:00 | 186.01 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.57 |
| October | 2207.27 | 20-OCT-14:01 | 8246.53 | 6629.82 | 4752.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 |
| November | 1269.75 | 01-NOV-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.36 |
| December | 863.82 | 21-DEC-21:11 | 0.00 | 1306.07 | 1467.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.04 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 857.55 | 0.00 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4625.67 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 | 80.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1767.24 | 19-JAN-08:03 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.71 |
| February | 1937.53 | 08-FEB-16:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.31 |
| March | 2095.06 | 31-MAR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.59 |
| April | 3300.04 | 13-APR-14:02 | 15185.68 | 6713.44 | 6564.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 |
| May | 4942.41 | 18-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 0.00 |
| June | 4630.83 | 08-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
| July | 3661.68 | 16-JUL-16:39 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.62 |
| August | 3867.72 | 12-AUG-13:11 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.77 |
| September | 3729.15 | 18-SEP-14:02 | 18222.82 | 8056.13 | 7877.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.94 |
| October | 3662.07 | 20-OCT-14:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 |
| November | 2357.47 | 01-NOV-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.85 |
| December | 1779.23 | 06-DEC-08:03 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.43 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1767.24 | 0.00 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4942.41 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 90.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 8651.15 | 19-JAN-08:03 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.14 |
| February | 9276.60 | 08-FEB-15:10 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.80 |
| March | 10371.48 | 31-MAR-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.56 |
| April | 16020.12 | 13-APR-14:02 | 73167.38 | 32346.60 | 31628.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.95 |
| May | 19947.00 | 25-MAY-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 0.00 |
| June | 19410.05 | 08-JUN-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
| July | 17004.17 | 05-JUL-05:01 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.70 |
| August | 17815.47 | 12-AUG-13:11 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.55 |
| September | 17933.30 | 18-SEP-14:02 | 87800.86 | 38815.92 | 37953.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.60 |
| October | 17526.97 | 20-OCT-14:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.13 |
| November | 11673.04 | 01-NOV-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.07 |
| December | 8711.02 | 06-DEC-08:03 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.57 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 8651.15 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 19947.00 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 | 240.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2115.66 | 27-JAN-15:30 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 2458.61 | 28-FEB-15:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.01 |
| March | 2617.50 | 31-MAR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.62 |
| April | 3818.33 | 13-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.09 |
| May | 6121.63 | 18-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 0.00 |
| June | 5341.94 | 08-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
| July | 4202.87 | 24-JUL-15:03 | 2877.29 | 4475.63 | 4145.91 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 0.00 |
| August | 5410.24 | 13-AUG-15:18 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.95 |
| September | 5163.18 | 25-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.16 |
| October | 5402.13 | 20-OCT-14:30 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.71 |
| November | 2694.43 | 17-NOV-15:40 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.04 |
| December | 1914.91 | 28-DEC-14:40 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.54 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1914.91 | 0.00 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6121.63 | 6074.27 | 4475.63 | 4145.91 | 0.00 | 0.00 | 0.00 | 0.00 | 18.51 | 76.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 10384.26 | 27-JAN-14:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 11750.81 | 08-FEB-15:10 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.11 |
| March | 12891.27 | 31-MAR-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.49 |
| April | 17564.41 | 18-APR-14:02 | 73167.38 | 32346.60 | 31628.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.03 |
| May | 26043.82 | 18-MAY-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 31.18 | 0.00 |
| June | 22973.50 | 08-JUN-14:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
| July | 17915.99 | 01-JUL-10:31 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.85 |
| August | 20668.83 | 12-AUG-13:11 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.54 |
| September | 23346.42 | 25-SEP-14:03 | 117067.81 | 51754.55 | 50605.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.02 |
| October | 24036.25 | 20-OCT-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.66 |
| November | 13187.69 | 17-NOV-13:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.60 |
| December | 9809.03 | 28-DEC-14:10 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.93 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 9809.03 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 26043.82 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 31.18 | 230.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 869.88 | 26-JAN-21:11 | 0.00 | 1306.07 | 1467.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.65 |
| February | 1089.12 | 08-FEB-16:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.40 |
| March | 1265.17 | 31-MAR-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.73 |
| April | 2051.77 | 21-APR-14:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.73 |
| May | 4816.28 | 18-MAY-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 | 0.00 |
| June | 4758.33 | 30-JUN-15:00 | 186.01 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 | 0.00 |
| July | 3452.67 | 24-JUL-14:40 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 | 0.00 |
| August | 2559.67 | 09-AUG-15:00 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 | 0.00 |
| September | 3164.25 | 08-SEP-15:50 | 186.01 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.55 |
| October | 2345.28 | 20-OCT-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.48 |
| November | 1309.52 | 01-NOV-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 |
| December | 875.82 | 21-DEC-21:11 | 0.00 | 1306.07 | 1467.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.05 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 869.88 | 0.00 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4816.28 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 7.55 | 80.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1765.03 | 19-JAN-08:03 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.70 |
| February | 1945.24 | 08-FEB-16:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.42 |
| March | 2112.91 | 31-MAR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.82 |
| April | 3323.23 | 13-APR-14:02 | 15185.68 | 6713.44 | 6564.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.91 |
| May | 5053.36 | 18-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 0.00 |
| June | 4761.59 | 08-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
| July | 3737.28 | 16-JUL-16:39 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.49 |
| August | 3935.27 | 12-AUG-13:11 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.79 |
| September | 3730.20 | 18-SEP-14:02 | 18222.82 | 8056.13 | 7877.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.98 |
| October | 3661.75 | 20-OCT-14:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.95 |
| November | 2367.58 | 01-NOV-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 |
| December | 1777.27 | 06-DEC-08:03 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.42 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1765.03 | 0.00 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5053.36 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 11.57 | 90.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5711.95 | 19-JAN-08:03 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.66 |
| February | 6172.91 | 08-FEB-15:00 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.61 |
| March | 6927.57 | 31-MAR-15:00 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.98 |
| April | 10689.27 | 13-APR-14:02 | 48318.08 | 21360.96 | 20886.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.03 |
| May | 13663.47 | 25-MAY-15:00 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 | 0.00 |
| June | 13458.21 | 08-JUN-14:30 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
| July | 11405.58 | 05-JUL-05:01 | 0.00 | 8416.22 | 9210.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.39 |
| August | 12071.72 | 12-AUG-13:11 | 0.00 | 8416.22 | 9210.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.91 |
| September | 11866.41 | 18-SEP-14:02 | 57981.70 | 25633.15 | 25063.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.95 |
| October | 11630.41 | 20-OCT-14:01 | 67645.32 | 29905.34 | 29241.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.76 |
| November | 7775.69 | 01-NOV-15:00 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.11 |
| December | 5751.06 | 06-DEC-08:03 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.84 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 5711.95 | 0.00 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 13663.47 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 20.14 | 158.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 3095.89 | 19-JAN-15:02 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.08 |
| February | 3408.05 | 08-FEB-15:00 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.73 |
| March | 3874.49 | 31-MAR-15:20 | 44728.74 | 19774.15 | 25780.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.92 |
| April | 5841.77 | 13-APR-14:02 | 24849.30 | 10985.64 | 14322.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 |
| May | 8007.34 | 25-MAY-15:03 | 29819.16 | 13182.76 | 17186.66 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 | 0.00 |
| June | 8835.81 | 30-JUN-15:03 | 39758.88 | 17577.02 | 22915.55 | 0.00 | 0.00 | 0.00 | 0.00 | 42.58 | 0.00 |
| July | 6258.82 | 22-JUL-09:54 | 0.00 | 4328.34 | 6315.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 |
| August | 6637.48 | 12-AUG-13:11 | 0.00 | 4328.34 | 6315.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.32 |
| September | 7223.71 | 08-SEP-14:03 | 34789.02 | 15379.89 | 20051.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.90 |
| October | 6012.02 | 20-OCT-14:01 | 34789.02 | 15379.89 | 20051.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.10 |
| November | 4333.88 | 01-NOV-15:40 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.09 |
| December | 3122.71 | 06-DEC-14:10 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.18 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3095.89 | 0.00 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 8835.81 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 42.58 | 76.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1826.99 | 26-JAN-21:11 | 0.00 | 3714.15 | 4171.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.70 |
| February | 1813.98 | 01-FEB-21:11 | 0.00 | 3714.15 | 4171.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.39 |
| March | 2654.98 | 31-MAR-15:00 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 |
| April | 4620.86 | 21-APR-14:01 | 33502.32 | 26933.63 | 19308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.54 |
| May | 11970.16 | 25-MAY-15:00 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 5.18 | 0.00 |
| June | 15841.19 | 30-JUN-07:03 | 1586.95 | 8080.09 | 5792.54 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 | 0.00 |
| July | 12107.38 | 24-JUL-07:03 | 1586.95 | 4488.94 | 3048.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.58 |
| August | 8022.89 | 08-AUG-15:03 | 4231.87 | 11970.50 | 8129.88 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 | 0.00 |
| September | 7460.59 | 05-SEP-15:40 | 528.98 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.71 |
| October | 4834.32 | 02-OCT-14:01 | 33502.32 | 26933.63 | 19308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.60 |
| November | 2707.72 | 01-NOV-15:00 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.80 |
| December | 1845.94 | 21-DEC-21:11 | 0.00 | 3714.15 | 4171.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.33 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1813.98 | 0.00 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 15841.19 | 33502.32 | 26933.63 | 19308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 15.31 | 240.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 582.26 | 19-JAN-06:47 | 0.00 | 1696.98 | 746.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.73 |
| February | 590.42 | 22-FEB-06:25 | 0.00 | 2545.48 | 1119.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1350.84 | 23-MAR-17:06 | 2319.41 | 15074.73 | 1559.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.67 |
| April | 2299.51 | 23-APR-15:12 | 0.00 | 2121.23 | 933.28 | 0.00 | 0.00 | 0.00 | 0.00 | 35.90 | 0.00 |
| May | 11431.61 | 18-MAY-15:00 | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 8469.55 | 0.00 |
| June | 14438.95 | 29-JUN-15:00 | 331.34 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 15400.59 | 0.00 |
| July | 11643.70 | 24-JUL-15:00 | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 9496.99 | 0.00 |
| August | 12299.59 | 08-AUG-15:00 | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 11349.93 | 0.00 |
| September | 9794.65 | 01-SEP-15:00 | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 5737.53 | 0.00 |
| October | 2709.87 | 22-OCT-14:02 | 0.00 | 1696.98 | 746.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.44 |
| November | 1380.84 | 02-NOV-17:07 | 994.03 | 6460.60 | 668.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.45 |
| December | 579.21 | 07-DEC-06:57 | 0.00 | 1696.98 | 746.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 280.64 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 579.21 | 0.00 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 14438.95 | 2319.41 | 15074.73 | 1559.53 | 0.00 | 0.00 | 0.00 | 0.00 | 15400.59 | 280.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1658.13 | 20-JAN-15:20 | 4638.66 | 36618.79 | 22279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1874.95 | 08-FEB-15:20 | 3710.93 | 29295.03 | 17823.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 2441.11 | 31-MAR-15:00 | 463.87 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 3822.79 | 21-APR-14:01 | 4638.66 | 36618.79 | 22279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 12911.52 | 25-MAY-20:10 | 0.00 | 5049.73 | 4813.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 13809.74 | 26-JUN-20:11 | 0.00 | 5049.73 | 4813.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 13751.29 | 01-JUL-10:31 | 0.00 | 7213.90 | 4912.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 13853.83 | 12-AUG-13:11 | 0.00 | 7213.90 | 4912.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 11996.12 | 17-SEP-14:11 | 0.00 | 7213.90 | 6876.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 3881.93 | 02-OCT-14:01 | 4638.66 | 36618.79 | 22279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 2478.31 | 01-NOV-15:00 | 463.87 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1676.10 | 07-DEC-14:10 | 463.87 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1658.13 | 0.00 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 13853.83 | 4638.66 | 36618.79 | 22279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 548.75 | 20-JAN-15:20 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.81 |
| February | 760.31 | 08-FEB-15:50 | 1165.88 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.63 |
| March | 1118.35 | 31-MAR-15:00 | 1165.88 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.37 |
| April | 2102.13 | 21-APR-14:01 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.55 |
| May | 2781.88 | 18-MAY-15:13 | 552.26 | 4969.69 | 2015.72 | 0.00 | 0.00 | 0.00 | 0.00 | 2.55 | 0.00 |
| June | 5608.21 | 30-JUN-20:08 | 0.00 | 1958.06 | 1244.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.96 |
| July | 8122.51 | 29-JUL-17:30 | 0.00 | 1631.72 | 740.70 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 0.00 |
| August | 2620.41 | 12-AUG-13:11 | 0.00 | 3263.43 | 1481.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 |
| September | 2511.33 | 08-SEP-14:01 | 1288.60 | 11595.95 | 4703.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.26 |
| October | 2209.92 | 02-OCT-14:01 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.05 |
| November | 1246.43 | 01-NOV-15:00 | 1165.88 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 |
| December | 562.43 | 06-DEC-14:10 | 1165.88 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.27 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 548.75 | 0.00 | 1631.72 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 8122.51 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 8.37 | 60.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 3359.17 | 13-JAN-13:06 | 13529.79 | 23497.06 | 21053.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.97 |
| February | 4156.53 | 08-FEB-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.24 |
| March | 12453.46 | 31-MAR-14:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.64 |
| April | 23090.44 | 21-APR-14:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.55 |
| May | 23540.29 | 19-MAY-14:01 | 18941.71 | 32895.88 | 29475.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.62 |
| June | 25193.88 | 25-JUN-10:47 | 0.00 | 8332.06 | 11697.48 | 0.00 | 0.00 | 0.00 | 0.00 | 30.02 | 0.00 |
| July | 26650.57 | 23-JUL-14:02 | 0.00 | 5554.70 | 5570.23 | 0.00 | 0.00 | 0.00 | 0.00 | 126.44 | 0.00 |
| August | 26061.72 | 13-AUG-15:18 | 0.00 | 9257.84 | 9283.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.46 |
| September | 23525.42 | 05-SEP-14:01 | 21647.67 | 37595.29 | 33685.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.33 |
| October | 23307.91 | 02-OCT-14:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.34 |
| November | 5022.65 | 17-NOV-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.02 |
| December | 3400.90 | 08-DEC-13:07 | 8117.88 | 14098.23 | 12632.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.17 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3359.17 | 0.00 | 5554.70 | 5570.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 26650.57 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 126.44 | 170.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5481.49 | 19-JAN-17:00 | 26290.70 | 8576.94 | 3156.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.00 |
| February | 6142.78 | 08-FEB-17:00 | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.46 |
| March | 7773.11 | 31-MAR-16:00 | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.98 |
| April | 13249.63 | 21-APR-15:13 | 39436.05 | 12865.40 | 4734.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.20 |
| May | 28132.29 | 25-MAY-05:01 | 0.00 | 5913.80 | 3409.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.27 |
| June | 30102.27 | 19-JUN-05:01 | 0.00 | 5913.80 | 3409.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.80 |
| July | 29817.57 | 03-JUL-05:01 | 0.00 | 5913.80 | 2435.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.56 |
| August | 29711.08 | 07-AUG-05:01 | 0.00 | 5913.80 | 2435.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.96 |
| September | 27498.90 | 19-SEP-05:01 | 0.00 | 5913.80 | 3409.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.66 |
| October | 11828.34 | 19-OCT-15:10 | 26290.70 | 8576.94 | 3156.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 |
| November | 7706.38 | 01-NOV-15:40 | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.42 |
| December | 5430.66 | 06-DEC-17:00 | 26290.70 | 8576.94 | 3156.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.75 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 5430.66 | 0.00 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | |
| Maximum of Months | 30102.27 | 39436.05 | 12865.40 | 4734.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 82323.02 | 20-JAN-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 297.08 |
| February | 38468.76 | 09-FEB-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 95.24 |
| March | 83456.43 | 24-MAR-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 167.34 |
| April | 81431.94 | 20-APR-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 123.24 |
| May | 79150.87 | 01-MAY-05:01 | 0.00 | 3462.67 | 23036.83 | 12982.94 | 0.00 | 0.00 | 0.00 | 0.00 | 27.59 |
| June | 52722.89 | 02-JUN-05:01 | 0.00 | 3077.93 | 20477.18 | 11540.39 | 0.00 | 0.00 | 0.00 | 0.00 | 58.79 |
| July | 46212.75 | 18-JUL-05:01 | 0.00 | 3077.93 | 20477.18 | 11540.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 46864.76 | 25-AUG-05:01 | 0.00 | 3077.93 | 20477.18 | 11540.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 62570.26 | 06-SEP-05:11 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 21.88 |
| October | 79453.28 | 06-OCT-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 84.85 |
| November | 85436.35 | 10-NOV-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 200.87 |
| December | 45215.13 | 26-DEC-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 170.91 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 38468.76 | 0.00 | 3077.93 | 20477.18 | 11540.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 85436.35 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 297.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 55297.96 | 09-JAN-15:01 | 142411.19 | 27464.09 | 7997.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.51 |
| February | 37310.47 | 14-FEB-06:49 | 0.00 | 5410.43 | 7997.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.33 |
| March | 33495.76 | 30-MAR-07:01 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.34 |
| April | 36039.42 | 13-APR-07:01 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.97 |
| May | 55079.51 | 25-MAY-05:01 | 0.00 | 3787.30 | 5598.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.09 |
| June | 65517.00 | 17-JUN-18:41 | 0.00 | 5410.43 | 7997.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.27 |
| July | 65737.27 | 17-JUL-05:01 | 0.00 | 4328.34 | 6398.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.23 |
| August | 62455.53 | 07-AUG-05:01 | 0.00 | 3787.30 | 5598.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.14 |
| September | 49322.15 | 01-SEP-05:01 | 0.00 | 3787.30 | 5598.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 |
| October | 38326.96 | 25-OCT-07:01 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 36105.28 | 17-NOV-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.47 |
| December | 67930.31 | 20-DEC-19:11 | 142411.19 | 27464.09 | 7997.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 33495.76 | 0.00 | 3787.30 | 5598.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 67930.31 | 142411.19 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 3453.01 | 19-JAN-14:10 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.41 |
| February | 3985.23 | 08-FEB-15:10 | 48967.60 | 59912.39 | 52912.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.90 |
| March | 4838.07 | 31-MAR-15:00 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.07 |
| April | 8417.62 | 14-APR-12:40 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.83 |
| May | 16778.53 | 18-MAY-14:03 | 29380.56 | 35947.43 | 31747.59 | 0.00 | 0.00 | 0.00 | 0.00 | 23.32 | 0.00 |
| June | 24317.98 | 28-JUN-07:03 | 2319.52 | 17973.72 | 15873.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 |
| July | 15469.51 | 24-JUL-07:03 | 2319.52 | 9985.40 | 8354.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.47 |
| August | 11295.83 | 08-AUG-14:30 | 773.17 | 3328.47 | 2784.88 | 0.00 | 0.00 | 0.00 | 0.00 | 64.27 | 0.00 |
| September | 13148.25 | 18-SEP-13:40 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.66 |
| October | 10314.44 | 20-OCT-14:03 | 34277.32 | 41938.67 | 37038.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.39 |
| November | 5892.14 | 01-NOV-15:00 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.40 |
| December | 3496.57 | 06-DEC-08:03 | 48967.60 | 59912.39 | 52912.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.13 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3453.01 | 773.17 | 3328.47 | 2784.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 24317.98 | 48967.60 | 59912.39 | 52912.65 | 0.00 | 0.00 | 0.00 | 0.00 | 64.27 | 181.13 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.273724E+12 | 188695.57 | 09-JAN-08:09 | 0.900224E+12 | 1273029.11 | 09-JAN-08:09 |
| February | 0.243408E+12 | 185427.21 | 13-FEB-11:09 | 0.598823E+12 | 1130173.22 | 14-FEB-08:09 |
| March | 0.274304E+12 | 185268.22 | 13-MAR-10:09 | 0.495474E+12 | 943721.32 | 15-MAR-07:10 |
| April | 0.244809E+12 | 210998.23 | 13-APR-14:00 | 0.176506E+12 | 672358.56 | 05-APR-07:10 |
| May | 0.293637E+12 | 324209.07 | 25-MAY-13:00 | 0.645849E+11 | 438318.44 | 01-MAY-07:10 |
| June | 0.331229E+12 | 377479.23 | 29-JUN-15:00 | 0.435920E+11 | 77954.97 | 02-JUN-11:30 |
| July | 0.244123E+12 | 242291.49 | 21-JUL-14:09 | 0.353022E+11 | 84034.09 | 10-JUL-07:10 |
| August | 0.238169E+12 | 249864.98 | 08-AUG-14:00 | 0.422568E+11 | 146183.80 | 18-AUG-07:10 |
| September | 0.254544E+12 | 257772.12 | 07-SEP-12:00 | 0.493494E+11 | 171158.43 | 06-SEP-07:10 |
| October | 0.254090E+12 | 235108.36 | 19-OCT-13:00 | 0.136859E+12 | 609683.00 | 30-OCT-07:10 |
| November | 0.255050E+12 | 199680.55 | 01-NOV-14:00 | 0.319154E+12 | 783196.02 | 29-NOV-08:09 |
| December | 0.267436E+12 | 188260.19 | 26-DEC-08:09 | 0.774463E+12 | 1136298.85 | 26-DEC-08:09 |
| Annual Sum or Average | 0.317452E+13 | 0.363659E+13 | ||||
| Minimum of Months | 0.238169E+12 | 185268.22 | 0.353022E+11 | 77954.97 | ||
| Maximum of Months | 0.331229E+12 | 377479.23 | 0.900224E+12 | 1273029.11 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 0.109593E+12 | 0.101453E+11 | 0.102892E+12 | 0.158194E+10 | 0.447867E+11 | 0.107307E+10 | 0.00 | 624727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.990914E+11 | 0.833349E+10 | 0.929862E+11 | 0.142979E+10 | 0.374944E+11 | 0.702660E+09 | 0.00 | 404856.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.116033E+12 | 0.809994E+10 | 0.106107E+12 | 0.164017E+10 | 0.380516E+11 | 0.566032E+09 | 0.00 | 8517293.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.105019E+12 | 0.670572E+10 | 0.990538E+11 | 0.152152E+10 | 0.266091E+11 | 0.186080E+09 | 0.00 | 0.202058E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.112813E+12 | 0.590953E+10 | 0.104499E+12 | 0.161106E+10 | 0.329926E+11 | 43986994.64 | 0.00 | 0.319585E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.111459E+12 | 0.516641E+10 | 0.102249E+12 | 0.157960E+10 | 0.376935E+11 | 20651631.77 | 0.00 | 0.693490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.666242E+11 | 0.559813E+10 | 0.693246E+11 | 0.102075E+10 | 0.307645E+11 | 17031880.95 | 0.00 | 0.670013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.703211E+11 | 0.647217E+10 | 0.716606E+11 | 0.104481E+10 | 0.309304E+11 | 29847239.00 | 0.00 | 0.539440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.103032E+12 | 0.734267E+10 | 0.977493E+11 | 0.149702E+10 | 0.276562E+11 | 33598084.97 | 0.00 | 0.135347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.109593E+12 | 0.876167E+10 | 0.102892E+12 | 0.158194E+10 | 0.253277E+11 | 0.109145E+09 | 0.00 | 0.199824E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.108239E+12 | 0.950832E+10 | 0.100662E+12 | 0.155064E+10 | 0.305443E+11 | 0.373074E+09 | 0.00 | 0.490692E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.106374E+12 | 0.104178E+11 | 0.101284E+12 | 0.155283E+10 | 0.432559E+11 | 0.918987E+09 | 0.00 | 311550.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.121819E+13 | 0.924611E+11 | 0.115136E+13 | 0.176121E+11 | 0.406107E+12 | 0.407416E+10 | 0.00 | 0.240307E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.666242E+11 | 0.516641E+10 | 0.693246E+11 | 0.102075E+10 | 0.253277E+11 | 17031880.95 | 0.00 | 311550.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.116033E+12 | 0.104178E+11 | 0.106107E+12 | 0.164017E+10 | 0.447867E+11 | 0.107307E+10 | 0.00 | 0.693490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.303281E+11 | 0.00 | 0.851111E+12 | 0.00 | 0.187855E+11 | 0.00 | 0.00 |
| February | 0.274200E+11 | 0.00 | 0.554157E+12 | 0.00 | 0.172463E+11 | 0.00 | 0.00 |
| March | 0.319900E+11 | 0.00 | 0.442868E+12 | 0.00 | 0.206163E+11 | 0.00 | 0.00 |
| April | 0.290818E+11 | 0.00 | 0.129848E+12 | 0.00 | 0.175763E+11 | 0.00 | 0.00 |
| May | 0.311591E+11 | 0.00 | 0.149732E+11 | 0.00 | 0.184527E+11 | 0.00 | 0.00 |
| June | 0.307436E+11 | 0.00 | 0.136225E+10 | 0.00 | 0.114862E+11 | 0.00 | 0.00 |
| July | 0.294972E+11 | 0.00 | 0.996636E+09 | 0.00 | 0.480831E+10 | 0.00 | 0.00 |
| August | 0.319900E+11 | 0.00 | 0.499924E+10 | 0.00 | 0.526755E+10 | 0.00 | 0.00 |
| September | 0.290818E+11 | 0.00 | 0.102732E+11 | 0.00 | 0.999441E+10 | 0.00 | 0.00 |
| October | 0.303281E+11 | 0.00 | 0.900437E+11 | 0.00 | 0.164872E+11 | 0.00 | 0.00 |
| November | 0.299127E+11 | 0.00 | 0.272017E+12 | 0.00 | 0.172239E+11 | 0.00 | 0.00 |
| December | 0.294972E+11 | 0.00 | 0.727636E+12 | 0.00 | 0.173304E+11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.361030E+12 | 0.00 | 0.310028E+13 | 0.00 | 0.175275E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.274200E+11 | 0.00 | 0.996636E+09 | 0.00 | 0.480831E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.319900E+11 | 0.00 | 0.851111E+12 | 0.00 | 0.206163E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 79557.27 | 02-JAN-07:10 | 5897.73 | 01-JAN-00:10 | 76813.98 | 02-JAN-10:09 | 1336.02 | 02-JAN-10:09 | 27082.94 | 09-JAN-07:10 | 1342.09 | 09-JAN-07:10 | 0.00 | 01-JAN-00:10 |
| February | 79557.27 | 01-FEB-07:10 | 5897.73 | 01-FEB-00:10 | 76813.98 | 01-FEB-10:09 | 1336.02 | 01-FEB-10:09 | 26899.81 | 13-FEB-07:10 | 1324.42 | 13-FEB-07:10 | 0.00 | 01-FEB-00:10 |
| March | 79557.27 | 01-MAR-07:10 | 5897.73 | 01-MAR-00:10 | 76813.98 | 01-MAR-10:09 | 1336.02 | 01-MAR-10:09 | 26886.14 | 06-MAR-07:10 | 1321.31 | 06-MAR-07:10 | 0.00 | 01-MAR-00:10 |
| April | 79557.27 | 03-APR-06:10 | 5897.73 | 01-APR-00:10 | 76813.98 | 03-APR-09:09 | 1336.02 | 03-APR-09:09 | 27663.07 | 21-APR-14:00 | 1141.42 | 10-APR-06:10 | 0.00 | 01-APR-00:10 |
| May | 79557.27 | 01-MAY-06:10 | 5897.73 | 01-MAY-00:10 | 76813.98 | 01-MAY-09:09 | 1336.02 | 01-MAY-09:09 | 52570.73 | 25-MAY-13:20 | 880.87 | 01-MAY-06:10 | 0.00 | 01-MAY-00:10 |
| June | 79557.27 | 01-JUN-06:10 | 5897.73 | 01-JUN-00:10 | 76813.98 | 01-JUN-09:09 | 1336.02 | 01-JUN-09:09 | 52386.41 | 08-JUN-14:30 | 134.84 | 09-JUN-14:09 | 0.00 | 01-JUN-00:10 |
| July | 44198.48 | 03-JUL-07:10 | 5897.73 | 01-JUL-00:10 | 45977.32 | 03-JUL-09:09 | 606.14 | 03-JUL-09:09 | 32224.85 | 24-JUL-11:50 | 181.21 | 10-JUL-07:10 | 0.00 | 01-JUL-00:10 |
| August | 44198.48 | 01-AUG-07:10 | 5897.73 | 01-AUG-00:10 | 45977.32 | 01-AUG-09:09 | 606.14 | 01-AUG-09:09 | 29874.22 | 08-AUG-12:00 | 325.37 | 18-AUG-07:10 | 0.00 | 01-AUG-00:10 |
| September | 79557.27 | 05-SEP-06:10 | 5897.73 | 01-SEP-00:10 | 76813.98 | 05-SEP-09:09 | 1336.02 | 05-SEP-09:09 | 39342.77 | 25-SEP-14:30 | 197.33 | 13-SEP-07:10 | 0.00 | 01-SEP-00:10 |
| October | 79557.27 | 02-OCT-06:10 | 5897.73 | 01-OCT-00:10 | 76813.98 | 02-OCT-09:09 | 1336.02 | 02-OCT-09:09 | 35886.86 | 20-OCT-14:30 | 948.20 | 30-OCT-06:10 | 0.00 | 01-OCT-00:10 |
| November | 79557.27 | 01-NOV-06:10 | 5897.73 | 01-NOV-00:10 | 76813.98 | 01-NOV-09:09 | 1336.02 | 01-NOV-09:09 | 26010.11 | 27-NOV-07:10 | 1207.39 | 27-NOV-07:10 | 0.00 | 01-NOV-00:10 |
| December | 79557.27 | 01-DEC-07:10 | 5897.73 | 01-DEC-00:10 | 76813.98 | 01-DEC-10:09 | 1336.02 | 01-DEC-10:09 | 26905.97 | 11-DEC-07:10 | 1325.92 | 26-DEC-07:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | ||||||||||||||
| Minimum of Months | 44198.48 | 5897.73 | 45977.32 | 606.14 | 26010.11 | 134.84 | 0.00 | |||||||
| Maximum of Months | 79557.27 | 5897.73 | 76813.98 | 1336.02 | 52570.73 | 1342.09 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 778.88 | 20-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 115.05 | 09-FEB-06:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 872.06 | 29-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 43507.22 | 23-APR-13:39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 128015.96 | 25-MAY-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 191317.43 | 29-JUN-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 129514.40 | 21-JUL-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 137097.17 | 08-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 81629.03 | 01-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 48851.49 | 19-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 23726.25 | 01-NOV-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 90.65 | 06-DEC-06:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 90.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 191317.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 188695.57 | 09-JAN-08:09 | 79557.27 | 72814.64 | 5897.73 | 1213.82 | 26667.35 | 1283.55 | 0.00 | 0.00 | 0.00 |
| February | 185427.21 | 13-FEB-11:09 | 79557.27 | 76813.98 | 0.00 | 1336.02 | 24065.01 | 809.78 | 0.00 | 0.00 | 0.00 |
| March | 185268.22 | 13-MAR-10:09 | 79557.27 | 76813.98 | 0.00 | 1336.02 | 23886.91 | 803.49 | 0.00 | 0.00 | 0.00 |
| April | 210998.23 | 13-APR-14:00 | 79557.27 | 70814.97 | 0.00 | 1156.20 | 27357.19 | 13.47 | 0.00 | 30746.84 | 0.00 |
| May | 324209.07 | 25-MAY-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 49232.82 | 13.47 | 0.00 | 119988.38 | 0.00 |
| June | 377479.23 | 29-JUN-15:00 | 79557.27 | 70814.97 | 0.00 | 1156.20 | 33276.16 | 13.47 | 0.00 | 191317.43 | 0.00 |
| July | 242291.49 | 21-JUL-14:09 | 44198.48 | 39978.30 | 0.00 | 518.12 | 26745.37 | 13.47 | 0.00 | 129514.40 | 0.00 |
| August | 249864.98 | 08-AUG-14:00 | 44198.48 | 39978.30 | 0.00 | 518.12 | 26738.00 | 13.47 | 0.00 | 137097.17 | 0.00 |
| September | 257772.12 | 07-SEP-12:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 36426.44 | 13.47 | 0.00 | 66376.20 | 0.00 |
| October | 235108.36 | 19-OCT-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 31492.18 | 13.47 | 0.00 | 48638.99 | 0.00 |
| November | 199680.55 | 01-NOV-14:00 | 79557.27 | 70814.97 | 0.00 | 1156.20 | 22936.02 | 113.98 | 0.00 | 23726.25 | 0.00 |
| December | 188260.19 | 26-DEC-08:09 | 79557.27 | 72814.64 | 5897.73 | 1213.82 | 26309.11 | 1206.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | ||||||||||
| Minimum of Months | 185268.22 | 44198.48 | 39978.30 | 0.00 | 518.12 | 22936.02 | 13.47 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 377479.23 | 79557.27 | 76813.98 | 5897.73 | 1336.02 | 49232.82 | 1283.55 | 0.00 | 191317.43 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
| January | 48084.96 | 02-JAN-10:09 | 0.00 | 1223736.16 | 09-JAN-08:09 | 0.00 | 34053.60 | 31-JAN-13:00 | 0.00 |
| February | 48084.96 | 01-FEB-10:09 | 0.00 | 1080068.13 | 14-FEB-08:09 | 0.00 | 34196.88 | 22-FEB-13:50 | 0.00 |
| March | 48084.96 | 01-MAR-10:09 | 0.00 | 894334.59 | 15-MAR-07:10 | 0.00 | 34189.09 | 07-MAR-13:20 | 0.00 |
| April | 48084.96 | 03-APR-09:09 | 0.00 | 623068.89 | 05-APR-07:10 | 0.00 | 33589.72 | 04-APR-12:20 | 0.00 |
| May | 48084.96 | 01-MAY-09:09 | 0.00 | 389100.90 | 01-MAY-07:10 | 0.00 | 32231.28 | 01-MAY-12:39 | 0.00 |
| June | 48084.96 | 01-JUN-09:09 | 0.00 | 28333.25 | 01-JUN-06:19 | 0.00 | 30820.76 | 01-JUN-12:00 | 0.00 |
| July | 48084.96 | 03-JUL-09:09 | 0.00 | 43096.18 | 10-JUL-07:10 | 0.00 | 9074.14 | 03-JUL-18:00 | 0.00 |
| August | 48084.96 | 01-AUG-09:09 | 0.00 | 105927.95 | 18-AUG-07:10 | 0.00 | 9045.55 | 01-AUG-18:00 | 0.00 |
| September | 48084.96 | 01-SEP-09:09 | 0.00 | 130875.03 | 06-SEP-07:10 | 0.00 | 28490.01 | 28-SEP-12:20 | 0.00 |
| October | 48084.96 | 02-OCT-09:09 | 0.00 | 561368.52 | 30-OCT-07:10 | 0.00 | 29971.91 | 30-OCT-12:20 | 0.00 |
| November | 48084.96 | 01-NOV-09:09 | 0.00 | 734320.34 | 29-NOV-08:09 | 0.00 | 31641.06 | 29-NOV-13:20 | 0.00 |
| December | 48084.96 | 01-DEC-10:09 | 0.00 | 1087071.11 | 26-DEC-08:09 | 0.00 | 32417.63 | 29-DEC-13:39 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 48084.96 | 0.00 | 28333.25 | 0.00 | 9045.55 | 0.00 | |||
| Maximum of Months | 48084.96 | 0.00 | 1223736.16 | 0.00 | 34196.88 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 83.50 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
| February | 43.50 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
| March | 23.33 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
| April | 4.83 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
| May | 0.17 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.33 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
| November | 14.50 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
| December | 62.50 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
| Annual Sum or Average | 232.67 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 83.50 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 29.50 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
| February | 14.50 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
| March | 8.83 | 15.78 | 0.00 | 15.78 | 0.00 | 15.78 | 0.00 | 15.78 |
| April | 1.17 | 16.44 | 0.00 | 16.44 | 0.00 | 16.44 | 0.00 | 16.44 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.38 | 0.00 | 27.38 |
| November | 1.17 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
| December | 29.33 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 |
| Annual Sum or Average | 84.50 | 15.44 | 0.00 | 15.44 | 0.17 | 15.46 | 0.00 | 15.46 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 29.50 | 16.77 | 0.00 | 16.77 | 0.17 | 27.38 | 0.00 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 54.67 | 17.62 | 16.50 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
| February | 24.33 | 18.35 | 8.00 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
| March | 16.17 | 18.34 | 4.17 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
| April | 3.50 | 18.45 | 0.33 | 18.62 | 0.00 | 18.62 | 0.00 | 18.62 |
| May | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
| November | 6.33 | 18.79 | 1.50 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
| December | 42.50 | 17.31 | 10.67 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
| Annual Sum or Average | 147.83 | 17.80 | 41.17 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 54.67 | 19.35 | 16.50 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 97.00 | 14.75 | 0.17 | 14.76 | 0.00 | 14.76 | 0.00 | 14.76 |
| February | 63.50 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
| March | 38.00 | 15.03 | 0.00 | 15.03 | 0.00 | 15.03 | 0.00 | 15.03 |
| April | 8.50 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 | 0.00 | 15.76 |
| May | 0.17 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.50 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 |
| November | 21.00 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
| December | 75.50 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 |
| Annual Sum or Average | 304.17 | 14.86 | 0.17 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 97.00 | 17.50 | 0.17 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 41.50 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
| February | 25.17 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 |
| March | 15.33 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
| April | 2.00 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 1.50 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 |
| December | 43.00 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
| Annual Sum or Average | 128.50 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 43.00 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 | 0.00 | 17.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 84.67 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
| February | 44.33 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
| March | 23.33 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
| April | 4.83 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 | 0.00 | 15.99 |
| May | 0.17 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.33 | 16.70 | 0.00 | 16.70 | 0.00 | 16.70 | 0.00 | 16.70 |
| November | 14.67 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
| December | 64.00 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 |
| Annual Sum or Average | 236.33 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 84.67 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 30.50 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 |
| February | 14.83 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 | 0.00 | 15.59 |
| March | 8.50 | 15.74 | 0.00 | 15.74 | 0.00 | 15.74 | 0.00 | 15.74 |
| April | 1.17 | 16.46 | 0.00 | 16.46 | 0.00 | 16.46 | 0.00 | 16.46 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 1.17 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
| December | 32.50 | 15.26 | 0.00 | 15.26 | 0.00 | 15.26 | 0.00 | 15.26 |
| Annual Sum or Average | 88.67 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 32.50 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 | 0.00 | 16.78 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 56.83 | 17.66 | 17.33 | 18.17 | 0.00 | 18.17 | 0.00 | 18.17 |
| February | 25.17 | 18.39 | 8.67 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
| March | 16.33 | 18.36 | 4.33 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
| April | 3.50 | 18.45 | 0.33 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
| May | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
| November | 6.33 | 18.78 | 1.50 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
| December | 44.83 | 17.35 | 12.17 | 17.88 | 0.00 | 17.88 | 0.00 | 17.88 |
| Annual Sum or Average | 153.33 | 17.83 | 44.33 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 56.83 | 19.34 | 17.33 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 97.00 | 14.75 | 0.17 | 14.76 | 0.00 | 14.76 | 0.00 | 14.76 |
| February | 63.50 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
| March | 38.00 | 15.03 | 0.00 | 15.03 | 0.00 | 15.03 | 0.00 | 15.03 |
| April | 8.33 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 | 0.00 | 15.77 |
| May | 0.17 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 | 0.00 | 16.74 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.50 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 |
| November | 21.17 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
| December | 75.50 | 14.72 | 0.00 | 14.72 | 0.00 | 14.72 | 0.00 | 14.72 |
| Annual Sum or Average | 304.17 | 14.86 | 0.17 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 97.00 | 17.50 | 0.17 | 17.50 | 0.00 | 17.50 | 0.00 | 17.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 41.67 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 | 0.00 | 15.18 |
| February | 25.17 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 | 0.00 | 15.33 |
| March | 15.33 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 | 0.00 | 15.54 |
| April | 2.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 1.50 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 |
| December | 43.00 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
| Annual Sum or Average | 128.67 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 43.00 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 84.33 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 | 0.00 | 14.80 |
| February | 44.17 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
| March | 23.33 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 | 0.00 | 15.04 |
| April | 4.83 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 | 0.00 | 16.00 |
| May | 0.17 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.33 | 16.72 | 0.00 | 16.72 | 0.00 | 16.72 | 0.00 | 16.72 |
| November | 14.50 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 | 0.00 | 15.05 |
| December | 63.67 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 | 0.00 | 14.77 |
| Annual Sum or Average | 235.33 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 | 0.00 | 14.88 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 84.33 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 30.17 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
| February | 14.83 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 | 0.00 | 15.58 |
| March | 8.67 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 | 0.00 | 15.72 |
| April | 1.17 | 16.46 | 0.00 | 16.46 | 0.00 | 16.46 | 0.00 | 16.46 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.32 | 0.00 | 27.32 |
| November | 1.00 | 16.70 | 0.00 | 16.70 | 0.00 | 16.70 | 0.00 | 16.70 |
| December | 31.83 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
| Annual Sum or Average | 87.67 | 15.42 | 0.00 | 15.42 | 0.17 | 15.44 | 0.00 | 15.44 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 31.83 | 16.70 | 0.00 | 16.70 | 0.17 | 27.32 | 0.00 | 27.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 54.33 | 17.64 | 16.83 | 18.16 | 0.00 | 18.16 | 0.00 | 18.16 |
| February | 23.67 | 18.35 | 7.67 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
| March | 15.67 | 18.32 | 4.17 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
| April | 3.00 | 18.44 | 0.33 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
| May | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.17 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
| November | 6.00 | 18.81 | 1.33 | 19.04 | 0.00 | 19.04 | 0.00 | 19.04 |
| December | 42.83 | 17.28 | 10.83 | 17.79 | 0.00 | 17.79 | 0.00 | 17.79 |
| Annual Sum or Average | 145.83 | 17.79 | 41.17 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 54.33 | 19.38 | 16.83 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 96.67 | 14.75 | 0.17 | 14.76 | 0.00 | 14.76 | 0.00 | 14.76 |
| February | 62.83 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
| March | 37.17 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
| April | 8.33 | 15.78 | 0.00 | 15.78 | 0.00 | 15.78 | 0.00 | 15.78 |
| May | 0.17 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.50 | 17.51 | 0.00 | 17.51 | 0.00 | 17.51 | 0.00 | 17.51 |
| November | 20.50 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 | 0.00 | 15.07 |
| December | 75.50 | 14.72 | 0.00 | 14.72 | 0.00 | 14.72 | 0.00 | 14.72 |
| Annual Sum or Average | 301.67 | 14.86 | 0.17 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 96.67 | 17.51 | 0.17 | 17.51 | 0.00 | 17.51 | 0.00 | 17.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 43.83 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 | 0.00 | 15.16 |
| February | 26.83 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
| March | 15.83 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
| April | 1.83 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 1.83 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
| December | 44.17 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
| Annual Sum or Average | 134.33 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 | 0.00 | 15.27 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 44.17 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 34.17 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
| February | 21.33 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
| March | 12.67 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 | 0.00 | 15.62 |
| April | 1.67 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 | 0.00 | 16.88 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 1.17 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
| December | 38.17 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
| Annual Sum or Average | 109.17 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 38.17 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 | 0.00 | 17.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 80.33 | 18.35 | 41.00 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
| February | 29.00 | 18.93 | 14.50 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
| March | 15.00 | 18.64 | 4.83 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
| April | 1.67 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
| November | 6.50 | 19.02 | 2.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
| December | 63.50 | 18.24 | 31.83 | 18.78 | 0.00 | 18.78 | 0.00 | 18.78 |
| Annual Sum or Average | 196.17 | 18.45 | 94.17 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 80.33 | 19.28 | 41.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 384.00 | 11.12 | 260.83 | 11.10 | 0.00 | 11.10 | 0.00 | 11.10 |
| February | 293.67 | 12.50 | 211.00 | 12.78 | 0.00 | 12.78 | 0.00 | 12.78 |
| March | 272.33 | 13.93 | 218.67 | 14.44 | 0.00 | 14.44 | 0.00 | 14.44 |
| April | 114.33 | 15.58 | 91.83 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
| May | 31.67 | 15.88 | 14.17 | 16.52 | 4.50 | 17.32 | 4.50 | 17.98 |
| June | 13.00 | 18.14 | 2.83 | 18.34 | 7.00 | 20.87 | 7.00 | 22.22 |
| July | 5.50 | 18.42 | 0.00 | 18.42 | 7.50 | 22.43 | 7.50 | 23.50 |
| August | 14.83 | 18.30 | 3.00 | 18.36 | 4.00 | 19.69 | 4.00 | 20.60 |
| September | 30.67 | 16.09 | 13.83 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 |
| October | 83.83 | 15.78 | 62.67 | 16.50 | 0.00 | 16.50 | 0.00 | 16.50 |
| November | 192.33 | 15.34 | 157.50 | 15.86 | 0.00 | 15.86 | 0.00 | 15.86 |
| December | 351.33 | 11.93 | 243.33 | 12.01 | 0.00 | 12.01 | 0.00 | 12.01 |
| Annual Sum or Average | 1787.50 | 13.19 | 1279.67 | 13.50 | 23.00 | 13.59 | 23.00 | 13.68 |
| Minimum of Months | 5.50 | 11.12 | 0.00 | 11.10 | 0.00 | 11.10 | 0.00 | 11.10 |
| Maximum of Months | 384.00 | 18.42 | 260.83 | 18.42 | 7.50 | 22.43 | 7.50 | 23.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.00 | 27.31 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.26 | 0.00 | 27.26 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.00 | 27.28 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 1.00 | 27.28 | 0.00 | 27.28 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.31 | 0.00 | 27.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 54.00 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
| February | 21.67 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
| March | 7.67 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 44.00 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 | 0.00 | 14.82 |
| Annual Sum or Average | 127.33 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 54.00 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 70.33 | 17.08 | 2.33 | 17.17 | 0.00 | 17.17 | 0.00 | 17.17 |
| February | 30.83 | 17.13 | 0.17 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
| March | 15.83 | 17.04 | 0.17 | 17.08 | 0.00 | 17.08 | 0.00 | 17.08 |
| April | 1.83 | 17.33 | 0.00 | 17.33 | 0.00 | 17.33 | 0.00 | 17.33 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.35 | 0.00 | 27.35 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 27.27 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 6.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
| December | 63.50 | 16.91 | 1.50 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 |
| Annual Sum or Average | 188.33 | 17.09 | 4.17 | 17.15 | 1.00 | 17.21 | 0.00 | 17.21 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 70.33 | 18.88 | 2.33 | 18.88 | 0.83 | 27.35 | 0.00 | 27.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 37.33 | 16.94 | 0.17 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
| February | 15.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 | 0.00 | 18.53 |
| March | 9.83 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
| April | 2.67 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.33 | 0.00 | 27.33 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.63 | 0.00 | 24.63 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.72 | 0.00 | 24.72 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.39 | 0.00 | 27.39 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.50 | 20.01 | 0.00 | 20.01 | 0.00 | 20.01 | 0.00 | 20.01 |
| November | 5.33 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 |
| December | 34.67 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
| Annual Sum or Average | 105.33 | 17.54 | 0.17 | 17.54 | 1.17 | 17.64 | 0.00 | 17.64 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 37.33 | 20.01 | 0.17 | 20.01 | 0.50 | 27.39 | 0.00 | 27.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.33 | 9.61 | 0.00 | 9.61 | 0.17 | 10.63 | 0.00 | 10.63 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.65 | 0.00 | 24.65 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 25.83 | 0.00 | 25.83 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 27.26 | 0.00 | 27.26 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 81.83 | 27.53 | 0.00 | 27.53 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 95.00 | 27.65 | 0.00 | 27.65 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 110.83 | 27.75 | 0.33 | 27.75 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 95.17 | 27.66 | 0.00 | 27.66 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 90.17 | 27.59 | 0.00 | 27.59 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 41.17 | 27.33 | 0.00 | 27.33 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 26.36 | 0.00 | 26.36 |
| December | 2.33 | 10.34 | 0.00 | 10.34 | 0.33 | 12.12 | 0.00 | 12.12 |
| Annual Sum or Average | 4.67 | 9.98 | 0.00 | 9.98 | 551.83 | 27.43 | 0.33 | 27.43 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 10.63 | 0.00 | 10.63 |
| Maximum of Months | 2.33 | 10.34 | 0.00 | 10.34 | 110.83 | 27.75 | 0.33 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 70.33 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
| February | 39.00 | 15.64 | 0.00 | 15.64 | 0.00 | 15.64 | 0.00 | 15.64 |
| March | 19.17 | 16.28 | 0.00 | 16.28 | 0.00 | 16.28 | 0.00 | 16.28 |
| April | 1.67 | 19.86 | 0.00 | 19.86 | 0.00 | 19.86 | 0.00 | 19.86 |
| May | 0.17 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 | 0.00 | 20.23 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 24.88 | 4.67 | 24.82 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 26.77 | 0.00 | 26.77 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.33 | 20.11 | 0.00 | 20.11 | 0.00 | 20.11 | 0.00 | 20.11 |
| November | 3.50 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
| December | 76.17 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
| Annual Sum or Average | 210.33 | 15.46 | 0.00 | 15.46 | 8.00 | 15.83 | 4.67 | 16.01 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 76.17 | 20.23 | 0.00 | 20.23 | 5.67 | 26.77 | 4.67 | 26.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 37.50 | 15.40 | 0.17 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
| February | 20.50 | 15.66 | 0.00 | 15.66 | 0.00 | 15.66 | 0.00 | 15.66 |
| March | 12.50 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 | 0.00 | 15.82 |
| April | 1.50 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 1.50 | 17.33 | 0.00 | 17.33 | 0.00 | 17.33 | 0.00 | 17.33 |
| December | 39.17 | 15.28 | 0.00 | 15.28 | 0.00 | 15.28 | 0.00 | 15.28 |
| Annual Sum or Average | 112.67 | 15.50 | 0.17 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 39.17 | 17.33 | 0.17 | 17.33 | 0.00 | 17.33 | 0.00 | 17.33 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.02 | 270.00 | 21.02 | 270.00 | 21.02 |
| February | 247.00 | 21.12 | 225.33 | 21.08 | 225.33 | 21.06 |
| March | 299.00 | 21.20 | 247.17 | 21.12 | 247.17 | 21.09 |
| April | 256.67 | 21.91 | 104.33 | 21.66 | 104.33 | 21.52 |
| May | 163.67 | 22.59 | 90.00 | 22.99 | 7.83 | 22.94 |
| June | 95.50 | 22.76 | 136.50 | 23.46 | 0.00 | 23.46 |
| July | 106.50 | 22.22 | 119.67 | 23.05 | 0.00 | 23.05 |
| August | 168.33 | 21.96 | 97.50 | 22.63 | 0.00 | 22.63 |
| September | 132.67 | 22.78 | 75.50 | 23.21 | 7.00 | 23.23 |
| October | 228.67 | 22.02 | 62.83 | 21.99 | 45.17 | 21.86 |
| November | 273.00 | 21.39 | 177.33 | 21.25 | 177.33 | 21.19 |
| December | 260.00 | 21.01 | 258.50 | 21.01 | 258.50 | 21.01 |
| Annual Sum or Average | 2504.00 | 21.65 | 1864.67 | 21.73 | 1342.67 | 21.57 |
| Minimum of Months | 95.50 | 21.01 | 62.83 | 21.01 | 0.00 | 21.01 |
| Maximum of Months | 299.00 | 22.78 | 270.00 | 23.46 | 270.00 | 23.46 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.06 | 264.50 | 21.04 | 264.50 | 21.04 |
| February | 247.00 | 21.22 | 209.67 | 21.14 | 209.67 | 21.11 |
| March | 299.00 | 21.37 | 207.83 | 21.24 | 207.83 | 21.19 |
| April | 250.83 | 22.13 | 71.00 | 21.89 | 71.00 | 21.74 |
| May | 150.67 | 22.74 | 86.17 | 23.12 | 5.00 | 23.08 |
| June | 84.00 | 22.79 | 139.33 | 23.49 | 0.00 | 23.49 |
| July | 143.33 | 22.20 | 64.17 | 22.59 | 0.00 | 22.59 |
| August | 200.50 | 21.97 | 59.83 | 22.33 | 0.00 | 22.33 |
| September | 111.00 | 22.90 | 80.67 | 23.34 | 6.67 | 23.36 |
| October | 216.83 | 22.30 | 38.00 | 22.36 | 16.83 | 22.27 |
| November | 273.00 | 21.61 | 134.33 | 21.42 | 134.33 | 21.32 |
| December | 260.00 | 21.05 | 255.33 | 21.04 | 255.33 | 21.04 |
| Annual Sum or Average | 2509.17 | 21.76 | 1610.83 | 21.78 | 1171.17 | 21.62 |
| Minimum of Months | 84.00 | 21.05 | 38.00 | 21.04 | 0.00 | 21.04 |
| Maximum of Months | 299.00 | 22.90 | 264.50 | 23.49 | 264.50 | 23.49 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 20.92 | 273.00 | 20.92 | 273.00 | 20.92 |
| February | 247.00 | 20.95 | 247.00 | 20.95 | 247.00 | 20.95 |
| March | 299.00 | 21.00 | 279.83 | 20.99 | 279.83 | 20.99 |
| April | 260.00 | 21.53 | 121.33 | 21.36 | 121.33 | 21.28 |
| May | 189.00 | 22.80 | 66.67 | 22.98 | 11.83 | 22.89 |
| June | 74.50 | 23.42 | 86.00 | 23.73 | 0.00 | 23.73 |
| July | 131.33 | 23.00 | 50.67 | 23.26 | 0.00 | 23.26 |
| August | 225.17 | 22.69 | 30.17 | 22.84 | 0.00 | 22.84 |
| September | 178.67 | 23.34 | 18.83 | 23.40 | 0.00 | 23.40 |
| October | 270.00 | 22.05 | 47.67 | 21.89 | 47.67 | 21.78 |
| November | 273.00 | 21.06 | 210.83 | 21.03 | 210.83 | 21.02 |
| December | 260.00 | 20.94 | 260.00 | 20.94 | 260.00 | 20.94 |
| Annual Sum or Average | 2680.67 | 21.73 | 1692.00 | 21.60 | 1451.50 | 21.44 |
| Minimum of Months | 74.50 | 20.92 | 18.83 | 20.92 | 0.00 | 20.92 |
| Maximum of Months | 299.00 | 23.42 | 279.83 | 23.73 | 279.83 | 23.73 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.00 | 273.00 | 21.00 | 273.00 | 21.00 |
| February | 247.00 | 21.01 | 246.50 | 21.00 | 246.50 | 21.00 |
| March | 299.00 | 21.02 | 292.00 | 21.01 | 292.00 | 21.01 |
| April | 260.00 | 21.31 | 168.00 | 21.20 | 168.00 | 21.16 |
| May | 202.33 | 22.40 | 81.17 | 22.67 | 17.33 | 22.58 |
| June | 125.17 | 22.74 | 93.17 | 23.25 | 0.00 | 23.25 |
| July | 186.50 | 22.12 | 37.67 | 22.35 | 0.00 | 22.35 |
| August | 262.17 | 21.81 | 17.83 | 21.91 | 0.00 | 21.91 |
| September | 228.67 | 22.56 | 16.33 | 22.64 | 8.00 | 22.68 |
| October | 271.17 | 21.78 | 67.33 | 21.63 | 67.33 | 21.53 |
| November | 273.00 | 21.12 | 223.50 | 21.07 | 223.50 | 21.06 |
| December | 260.00 | 21.00 | 260.00 | 21.00 | 260.00 | 21.00 |
| Annual Sum or Average | 2888.00 | 21.56 | 1776.50 | 21.49 | 1555.67 | 21.37 |
| Minimum of Months | 125.17 | 21.00 | 16.33 | 21.00 | 0.00 | 21.00 |
| Maximum of Months | 299.00 | 22.74 | 292.00 | 23.25 | 292.00 | 23.25 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.00 | 273.00 | 21.00 | 273.00 | 21.00 |
| February | 247.00 | 21.01 | 247.00 | 21.01 | 247.00 | 21.01 |
| March | 299.00 | 21.06 | 280.00 | 21.04 | 280.00 | 21.03 |
| April | 260.00 | 21.50 | 133.17 | 21.36 | 133.17 | 21.28 |
| May | 201.33 | 22.56 | 65.50 | 22.79 | 10.50 | 22.72 |
| June | 125.50 | 22.76 | 86.50 | 23.16 | 0.00 | 23.16 |
| July | 255.67 | 21.93 | 0.00 | 21.93 | 0.00 | 21.93 |
| August | 299.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
| September | 224.50 | 22.55 | 17.33 | 22.65 | 7.33 | 22.69 |
| October | 270.17 | 22.02 | 34.83 | 21.91 | 34.83 | 21.82 |
| November | 273.00 | 21.26 | 195.17 | 21.17 | 195.17 | 21.13 |
| December | 260.00 | 21.00 | 260.00 | 21.00 | 260.00 | 21.00 |
| Annual Sum or Average | 2988.17 | 21.60 | 1592.50 | 21.50 | 1441.00 | 21.39 |
| Minimum of Months | 125.50 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
| Maximum of Months | 299.00 | 22.76 | 280.00 | 23.16 | 280.00 | 23.16 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.02 | 270.67 | 21.01 | 270.67 | 21.01 |
| February | 247.00 | 21.12 | 226.83 | 21.07 | 226.83 | 21.06 |
| March | 299.00 | 21.19 | 248.67 | 21.11 | 248.67 | 21.08 |
| April | 257.33 | 21.89 | 106.83 | 21.64 | 106.83 | 21.50 |
| May | 167.33 | 22.55 | 88.50 | 22.95 | 8.50 | 22.89 |
| June | 101.83 | 22.74 | 130.17 | 23.42 | 0.00 | 23.42 |
| July | 114.67 | 22.18 | 108.33 | 22.94 | 0.00 | 22.94 |
| August | 177.17 | 21.94 | 88.67 | 22.55 | 0.00 | 22.55 |
| September | 138.00 | 22.77 | 71.17 | 23.18 | 7.00 | 23.20 |
| October | 230.50 | 22.01 | 62.33 | 21.97 | 45.83 | 21.84 |
| November | 273.00 | 21.37 | 182.00 | 21.23 | 182.00 | 21.18 |
| December | 260.00 | 21.01 | 260.00 | 21.01 | 260.00 | 21.01 |
| Annual Sum or Average | 2538.83 | 21.64 | 1844.17 | 21.71 | 1356.33 | 21.55 |
| Minimum of Months | 101.83 | 21.01 | 62.33 | 21.01 | 0.00 | 21.01 |
| Maximum of Months | 299.00 | 22.77 | 270.67 | 23.42 | 270.67 | 23.42 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.05 | 269.33 | 21.04 | 269.33 | 21.04 |
| February | 247.00 | 21.21 | 211.00 | 21.14 | 211.00 | 21.11 |
| March | 299.00 | 21.36 | 210.83 | 21.23 | 210.83 | 21.18 |
| April | 254.67 | 22.13 | 71.33 | 21.90 | 71.33 | 21.75 |
| May | 155.67 | 22.72 | 83.33 | 23.09 | 5.33 | 23.05 |
| June | 92.17 | 22.77 | 130.50 | 23.43 | 0.00 | 23.43 |
| July | 160.00 | 22.15 | 44.33 | 22.41 | 0.00 | 22.41 |
| August | 212.33 | 21.93 | 44.67 | 22.19 | 0.00 | 22.19 |
| September | 117.17 | 22.90 | 74.67 | 23.30 | 6.67 | 23.33 |
| October | 218.67 | 22.29 | 37.83 | 22.34 | 18.17 | 22.25 |
| November | 273.00 | 21.57 | 138.17 | 21.39 | 138.17 | 21.30 |
| December | 260.00 | 21.03 | 256.17 | 21.03 | 256.17 | 21.02 |
| Annual Sum or Average | 2562.67 | 21.76 | 1572.17 | 21.75 | 1187.00 | 21.59 |
| Minimum of Months | 92.17 | 21.03 | 37.83 | 21.03 | 0.00 | 21.02 |
| Maximum of Months | 299.00 | 22.90 | 269.33 | 23.43 | 269.33 | 23.43 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 20.91 | 273.00 | 20.91 | 273.00 | 20.91 |
| February | 247.00 | 20.95 | 247.00 | 20.95 | 247.00 | 20.95 |
| March | 299.00 | 21.00 | 280.83 | 20.99 | 280.83 | 20.99 |
| April | 260.00 | 21.52 | 122.33 | 21.36 | 122.33 | 21.27 |
| May | 189.83 | 22.79 | 66.33 | 22.96 | 12.00 | 22.87 |
| June | 77.67 | 23.41 | 83.50 | 23.71 | 0.00 | 23.71 |
| July | 142.17 | 22.99 | 43.67 | 23.21 | 0.00 | 23.21 |
| August | 234.33 | 22.67 | 25.67 | 22.80 | 0.00 | 22.80 |
| September | 182.50 | 23.33 | 17.83 | 23.39 | 0.00 | 23.39 |
| October | 270.17 | 22.04 | 47.67 | 21.88 | 47.67 | 21.77 |
| November | 273.00 | 21.05 | 213.17 | 21.03 | 213.17 | 21.02 |
| December | 260.00 | 20.93 | 260.00 | 20.93 | 260.00 | 20.93 |
| Annual Sum or Average | 2708.67 | 21.74 | 1681.00 | 21.60 | 1456.00 | 21.44 |
| Minimum of Months | 77.67 | 20.91 | 17.83 | 20.91 | 0.00 | 20.91 |
| Maximum of Months | 299.00 | 23.41 | 280.83 | 23.71 | 280.83 | 23.71 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.00 | 273.00 | 21.00 | 273.00 | 21.00 |
| February | 247.00 | 21.01 | 246.50 | 21.00 | 246.50 | 21.00 |
| March | 299.00 | 21.02 | 291.83 | 21.01 | 291.83 | 21.01 |
| April | 260.00 | 21.31 | 168.00 | 21.20 | 168.00 | 21.16 |
| May | 202.33 | 22.40 | 81.17 | 22.67 | 17.33 | 22.58 |
| June | 125.17 | 22.74 | 93.50 | 23.25 | 0.00 | 23.25 |
| July | 187.33 | 22.11 | 37.67 | 22.34 | 0.00 | 22.34 |
| August | 262.17 | 21.80 | 17.67 | 21.90 | 0.00 | 21.90 |
| September | 229.00 | 22.55 | 16.33 | 22.64 | 8.00 | 22.68 |
| October | 271.17 | 21.78 | 67.17 | 21.63 | 67.17 | 21.53 |
| November | 273.00 | 21.12 | 223.50 | 21.07 | 223.50 | 21.06 |
| December | 260.00 | 21.00 | 260.00 | 21.00 | 260.00 | 21.00 |
| Annual Sum or Average | 2889.17 | 21.56 | 1776.33 | 21.49 | 1555.33 | 21.37 |
| Minimum of Months | 125.17 | 21.00 | 16.33 | 21.00 | 0.00 | 21.00 |
| Maximum of Months | 299.00 | 22.74 | 291.83 | 23.25 | 291.83 | 23.25 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.00 | 273.00 | 21.00 | 273.00 | 21.00 |
| February | 247.00 | 21.01 | 247.00 | 21.01 | 247.00 | 21.01 |
| March | 299.00 | 21.06 | 279.83 | 21.04 | 279.83 | 21.03 |
| April | 260.00 | 21.51 | 133.00 | 21.36 | 133.00 | 21.28 |
| May | 201.33 | 22.57 | 65.83 | 22.79 | 10.50 | 22.73 |
| June | 124.83 | 22.76 | 87.83 | 23.17 | 0.00 | 23.17 |
| July | 255.50 | 21.93 | 0.00 | 21.93 | 0.00 | 21.93 |
| August | 299.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
| September | 224.33 | 22.55 | 17.50 | 22.65 | 7.33 | 22.69 |
| October | 270.17 | 22.02 | 34.83 | 21.91 | 34.83 | 21.83 |
| November | 273.00 | 21.26 | 195.33 | 21.17 | 195.33 | 21.13 |
| December | 260.00 | 21.00 | 260.00 | 21.00 | 260.00 | 21.00 |
| Annual Sum or Average | 2987.17 | 21.60 | 1594.17 | 21.50 | 1440.83 | 21.39 |
| Minimum of Months | 124.83 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
| Maximum of Months | 299.00 | 22.76 | 279.83 | 23.17 | 279.83 | 23.17 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.02 | 270.33 | 21.02 | 270.33 | 21.01 |
| February | 247.00 | 21.12 | 226.67 | 21.07 | 226.67 | 21.06 |
| March | 299.00 | 21.19 | 248.17 | 21.11 | 248.17 | 21.08 |
| April | 257.17 | 21.90 | 106.00 | 21.65 | 106.00 | 21.51 |
| May | 165.50 | 22.57 | 89.00 | 22.97 | 8.00 | 22.92 |
| June | 99.00 | 22.75 | 133.33 | 23.45 | 0.00 | 23.45 |
| July | 110.17 | 22.20 | 113.83 | 23.00 | 0.00 | 23.00 |
| August | 171.67 | 21.96 | 93.83 | 22.60 | 0.00 | 22.60 |
| September | 134.00 | 22.79 | 74.50 | 23.21 | 7.00 | 23.23 |
| October | 228.83 | 22.03 | 62.17 | 21.99 | 44.50 | 21.87 |
| November | 273.00 | 21.38 | 180.67 | 21.24 | 180.67 | 21.18 |
| December | 260.00 | 21.01 | 259.50 | 21.01 | 259.50 | 21.01 |
| Annual Sum or Average | 2518.33 | 21.65 | 1858.00 | 21.72 | 1350.83 | 21.56 |
| Minimum of Months | 99.00 | 21.01 | 62.17 | 21.01 | 0.00 | 21.01 |
| Maximum of Months | 299.00 | 22.79 | 270.33 | 23.45 | 270.33 | 23.45 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.05 | 267.50 | 21.04 | 267.50 | 21.04 |
| February | 247.00 | 21.21 | 210.33 | 21.14 | 210.33 | 21.11 |
| March | 299.00 | 21.36 | 209.00 | 21.24 | 209.00 | 21.18 |
| April | 251.17 | 22.13 | 69.83 | 21.90 | 69.83 | 21.75 |
| May | 151.67 | 22.75 | 84.67 | 23.12 | 5.00 | 23.08 |
| June | 85.67 | 22.79 | 136.17 | 23.48 | 0.00 | 23.48 |
| July | 150.17 | 22.18 | 53.67 | 22.51 | 0.00 | 22.51 |
| August | 205.17 | 21.97 | 53.33 | 22.28 | 0.00 | 22.28 |
| September | 108.83 | 22.92 | 80.00 | 23.35 | 6.50 | 23.38 |
| October | 216.33 | 22.34 | 35.33 | 22.41 | 13.83 | 22.34 |
| November | 273.00 | 21.59 | 136.50 | 21.41 | 136.50 | 21.32 |
| December | 260.00 | 21.04 | 255.83 | 21.03 | 255.83 | 21.03 |
| Annual Sum or Average | 2521.00 | 21.76 | 1592.17 | 21.77 | 1174.33 | 21.61 |
| Minimum of Months | 85.67 | 21.04 | 35.33 | 21.03 | 0.00 | 21.03 |
| Maximum of Months | 299.00 | 22.92 | 267.50 | 23.48 | 267.50 | 23.48 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 20.92 | 273.00 | 20.92 | 273.00 | 20.92 |
| February | 247.00 | 20.96 | 247.00 | 20.96 | 247.00 | 20.96 |
| March | 299.00 | 21.01 | 277.50 | 20.99 | 277.50 | 20.99 |
| April | 260.00 | 21.60 | 115.67 | 21.42 | 115.67 | 21.32 |
| May | 182.83 | 22.90 | 69.00 | 23.08 | 10.50 | 23.00 |
| June | 58.50 | 23.50 | 100.17 | 23.81 | 0.00 | 23.81 |
| July | 107.17 | 23.08 | 75.00 | 23.44 | 0.00 | 23.44 |
| August | 190.83 | 22.72 | 45.50 | 22.96 | 0.00 | 22.96 |
| September | 151.67 | 23.42 | 23.83 | 23.50 | 0.00 | 23.50 |
| October | 268.67 | 22.17 | 41.50 | 22.01 | 41.50 | 21.89 |
| November | 273.00 | 21.07 | 205.17 | 21.04 | 205.17 | 21.03 |
| December | 260.00 | 20.94 | 260.00 | 20.94 | 260.00 | 20.94 |
| Annual Sum or Average | 2571.67 | 21.72 | 1733.33 | 21.63 | 1430.33 | 21.46 |
| Minimum of Months | 58.50 | 20.92 | 23.83 | 20.92 | 0.00 | 20.92 |
| Maximum of Months | 299.00 | 23.50 | 277.50 | 23.81 | 277.50 | 23.81 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.00 | 273.00 | 21.00 | 273.00 | 21.00 |
| February | 247.00 | 21.01 | 246.33 | 21.00 | 246.33 | 21.00 |
| March | 299.00 | 21.02 | 290.00 | 21.01 | 290.00 | 21.01 |
| April | 260.00 | 21.34 | 161.00 | 21.22 | 161.00 | 21.17 |
| May | 197.50 | 22.46 | 83.33 | 22.74 | 16.17 | 22.65 |
| June | 112.17 | 22.78 | 110.50 | 23.35 | 0.00 | 23.35 |
| July | 167.17 | 22.18 | 47.83 | 22.49 | 0.00 | 22.49 |
| August | 246.83 | 21.84 | 23.67 | 21.98 | 0.00 | 21.98 |
| September | 215.00 | 22.58 | 17.67 | 22.68 | 7.33 | 22.71 |
| October | 268.67 | 21.80 | 63.33 | 21.65 | 63.33 | 21.55 |
| November | 273.00 | 21.13 | 222.67 | 21.08 | 222.67 | 21.06 |
| December | 260.00 | 21.00 | 260.00 | 21.00 | 260.00 | 21.00 |
| Annual Sum or Average | 2819.33 | 21.56 | 1799.33 | 21.51 | 1539.83 | 21.39 |
| Minimum of Months | 112.17 | 21.00 | 17.67 | 21.00 | 0.00 | 21.00 |
| Maximum of Months | 299.00 | 22.78 | 290.00 | 23.35 | 290.00 | 23.35 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.00 | 273.00 | 21.00 | 273.00 | 21.00 |
| February | 247.00 | 21.01 | 246.33 | 21.01 | 246.33 | 21.01 |
| March | 299.00 | 21.07 | 277.00 | 21.05 | 277.00 | 21.04 |
| April | 260.00 | 21.54 | 126.33 | 21.39 | 126.33 | 21.31 |
| May | 187.17 | 22.61 | 70.83 | 22.86 | 10.00 | 22.80 |
| June | 100.17 | 22.81 | 109.83 | 23.33 | 0.00 | 23.33 |
| July | 240.33 | 22.11 | 0.83 | 22.11 | 0.00 | 22.11 |
| August | 296.33 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
| September | 215.67 | 22.64 | 20.67 | 22.75 | 7.33 | 22.79 |
| October | 269.17 | 22.08 | 31.67 | 21.98 | 31.67 | 21.89 |
| November | 273.00 | 21.27 | 191.67 | 21.17 | 191.67 | 21.13 |
| December | 260.00 | 21.00 | 260.00 | 21.00 | 260.00 | 21.00 |
| Annual Sum or Average | 2920.83 | 21.63 | 1608.17 | 21.53 | 1423.33 | 21.41 |
| Minimum of Months | 100.17 | 21.00 | 0.00 | 21.00 | 0.00 | 21.00 |
| Maximum of Months | 299.00 | 22.81 | 277.00 | 23.33 | 277.00 | 23.33 |
Report: ComfortReportSimple55Monthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.01 | 273.00 | 21.01 | 273.00 | 21.01 |
| February | 247.00 | 21.05 | 242.33 | 21.05 | 242.33 | 21.04 |
| March | 299.00 | 21.25 | 239.00 | 21.17 | 239.00 | 21.14 |
| April | 260.00 | 22.30 | 63.67 | 22.08 | 63.67 | 21.93 |
| May | 114.00 | 23.31 | 100.33 | 23.59 | 3.33 | 23.55 |
| June | 19.50 | 23.72 | 233.50 | 23.97 | 11.83 | 23.98 |
| July | 72.67 | 22.77 | 118.00 | 23.33 | 0.00 | 23.33 |
| August | 161.50 | 22.49 | 70.67 | 22.82 | 0.00 | 22.82 |
| September | 43.17 | 23.54 | 91.00 | 23.83 | 6.17 | 23.84 |
| October | 240.00 | 22.94 | 9.83 | 22.92 | 5.67 | 22.88 |
| November | 273.00 | 21.67 | 131.83 | 21.48 | 131.83 | 21.38 |
| December | 260.00 | 21.03 | 260.00 | 21.03 | 260.00 | 21.03 |
| Annual Sum or Average | 2262.83 | 21.83 | 1833.17 | 21.91 | 1236.83 | 21.72 |
| Minimum of Months | 19.50 | 21.01 | 9.83 | 21.01 | 0.00 | 21.01 |
| Maximum of Months | 299.00 | 23.72 | 273.00 | 23.97 | 273.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 20.78 | 273.00 | 20.78 | 273.00 | 20.78 |
| February | 247.00 | 20.92 | 247.00 | 20.92 | 247.00 | 20.92 |
| March | 299.00 | 20.99 | 291.33 | 20.98 | 291.33 | 20.98 |
| April | 260.00 | 21.73 | 108.83 | 21.52 | 108.83 | 21.41 |
| May | 146.33 | 23.19 | 80.17 | 23.38 | 7.17 | 23.31 |
| June | 16.17 | 23.89 | 167.83 | 23.99 | 0.00 | 23.99 |
| July | 9.00 | 23.34 | 183.17 | 23.97 | 0.00 | 23.97 |
| August | 85.00 | 23.01 | 134.50 | 23.61 | 0.00 | 23.61 |
| September | 138.83 | 23.51 | 28.67 | 23.59 | 0.00 | 23.59 |
| October | 273.00 | 21.84 | 71.00 | 21.67 | 71.00 | 21.55 |
| November | 273.00 | 21.01 | 242.00 | 21.00 | 242.00 | 21.00 |
| December | 260.00 | 20.82 | 260.00 | 20.82 | 260.00 | 20.82 |
| Annual Sum or Average | 2280.33 | 21.53 | 2087.50 | 21.65 | 1500.33 | 21.46 |
| Minimum of Months | 9.00 | 20.78 | 28.67 | 20.78 | 0.00 | 20.78 |
| Maximum of Months | 299.00 | 23.89 | 291.33 | 23.99 | 291.33 | 23.99 |
Report: ComfortReportSimple55Monthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 11.52 | 273.00 | 11.52 | 273.00 | 11.52 |
| February | 247.00 | 14.31 | 247.00 | 14.31 | 247.00 | 14.31 |
| March | 299.00 | 16.64 | 298.67 | 16.64 | 298.67 | 16.64 |
| April | 260.00 | 19.73 | 183.33 | 19.48 | 183.33 | 19.37 |
| May | 210.33 | 21.43 | 88.50 | 21.72 | 34.50 | 21.52 |
| June | 158.67 | 22.54 | 118.83 | 23.09 | 46.33 | 23.15 |
| July | 131.17 | 22.81 | 153.67 | 23.38 | 55.33 | 23.42 |
| August | 212.00 | 22.22 | 121.00 | 22.76 | 60.00 | 22.86 |
| September | 223.00 | 21.45 | 29.00 | 21.46 | 12.83 | 21.31 |
| October | 272.33 | 20.31 | 133.67 | 19.98 | 133.67 | 19.81 |
| November | 273.00 | 18.39 | 254.00 | 18.30 | 254.00 | 18.27 |
| December | 260.00 | 12.69 | 260.00 | 12.69 | 260.00 | 12.69 |
| Annual Sum or Average | 2819.50 | 18.16 | 2160.67 | 17.84 | 1858.67 | 17.43 |
| Minimum of Months | 131.17 | 11.52 | 29.00 | 11.52 | 12.83 | 11.52 |
| Maximum of Months | 299.00 | 22.81 | 298.67 | 23.38 | 298.67 | 23.42 |
Report: ComfortReportSimple55Monthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 18.77 | 273.00 | 18.77 | 273.00 | 18.77 |
| February | 247.00 | 19.83 | 243.00 | 19.81 | 243.00 | 19.81 |
| March | 299.00 | 21.11 | 191.67 | 20.83 | 191.67 | 20.71 |
| April | 192.17 | 23.17 | 30.17 | 23.05 | 22.17 | 22.87 |
| May | 60.67 | 25.58 | 236.83 | 26.16 | 36.33 | 26.22 |
| June | 80.50 | 26.70 | 286.00 | 26.62 | 80.50 | 26.63 |
| July | 6.83 | 26.62 | 260.00 | 25.80 | 6.83 | 25.82 |
| August | 6.83 | 23.64 | 275.33 | 25.24 | 0.00 | 25.24 |
| September | 0.00 | 0.00 | 250.83 | 26.02 | 0.00 | 26.02 |
| October | 179.50 | 23.38 | 30.33 | 23.64 | 1.50 | 23.62 |
| November | 273.00 | 21.52 | 127.17 | 21.18 | 127.17 | 21.01 |
| December | 260.00 | 19.18 | 260.00 | 19.18 | 260.00 | 19.18 |
| Annual Sum or Average | 1878.50 | 21.23 | 2464.33 | 22.29 | 1242.17 | 21.85 |
| Minimum of Months | 0.00 | 0.00 | 30.17 | 18.77 | 0.00 | 18.77 |
| Maximum of Months | 299.00 | 26.70 | 286.00 | 26.62 | 273.00 | 26.63 |
Report: ComfortReportSimple55Monthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 16.28 | 273.00 | 16.28 | 273.00 | 16.28 |
| February | 247.00 | 17.05 | 247.00 | 17.05 | 247.00 | 17.05 |
| March | 299.00 | 18.14 | 298.17 | 18.13 | 298.17 | 18.13 |
| April | 260.00 | 21.04 | 121.67 | 20.58 | 121.67 | 20.34 |
| May | 130.67 | 23.29 | 126.67 | 24.27 | 16.50 | 24.21 |
| June | 38.50 | 26.30 | 261.17 | 25.71 | 34.00 | 25.80 |
| July | 4.83 | 25.11 | 245.67 | 25.04 | 2.67 | 25.06 |
| August | 48.33 | 22.88 | 202.67 | 24.28 | 0.00 | 24.28 |
| September | 88.50 | 23.52 | 92.50 | 24.20 | 0.00 | 24.20 |
| October | 271.33 | 21.74 | 77.00 | 21.41 | 77.00 | 21.20 |
| November | 273.00 | 18.87 | 250.00 | 18.77 | 250.00 | 18.73 |
| December | 260.00 | 16.60 | 260.00 | 16.60 | 260.00 | 16.60 |
| Annual Sum or Average | 2194.17 | 19.27 | 2455.50 | 19.91 | 1580.00 | 19.41 |
| Minimum of Months | 4.83 | 16.28 | 77.00 | 16.28 | 0.00 | 16.28 |
| Maximum of Months | 299.00 | 26.30 | 298.17 | 25.71 | 298.17 | 25.80 |
Report: ComfortReportSimple55Monthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 231.00 | 20.98 | 231.00 | 20.98 | 231.00 | 20.98 |
| February | 209.00 | 21.01 | 206.83 | 21.01 | 206.83 | 21.01 |
| March | 253.00 | 21.12 | 225.67 | 21.07 | 225.67 | 21.05 |
| April | 217.50 | 22.24 | 75.67 | 21.93 | 75.67 | 21.75 |
| May | 107.67 | 23.39 | 78.83 | 23.60 | 3.00 | 23.56 |
| June | 6.00 | 23.77 | 176.83 | 23.99 | 0.00 | 23.99 |
| July | 1.00 | 23.22 | 204.33 | 23.99 | 0.00 | 23.99 |
| August | 33.50 | 22.98 | 194.17 | 23.83 | 0.00 | 23.83 |
| September | 58.67 | 23.56 | 71.00 | 23.80 | 0.00 | 23.80 |
| October | 211.00 | 22.43 | 37.50 | 22.22 | 37.50 | 22.07 |
| November | 231.00 | 21.20 | 177.67 | 21.12 | 177.67 | 21.09 |
| December | 220.00 | 20.98 | 220.00 | 20.98 | 220.00 | 20.98 |
| Annual Sum or Average | 1779.33 | 21.64 | 1899.50 | 21.90 | 1177.33 | 21.68 |
| Minimum of Months | 1.00 | 20.98 | 37.50 | 20.98 | 0.00 | 20.98 |
| Maximum of Months | 253.00 | 23.77 | 231.00 | 23.99 | 231.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.01 | 273.00 | 21.01 | 273.00 | 21.01 |
| February | 247.00 | 21.05 | 238.67 | 21.04 | 238.67 | 21.04 |
| March | 299.00 | 21.43 | 187.50 | 21.29 | 187.50 | 21.22 |
| April | 194.83 | 22.62 | 21.33 | 22.48 | 19.50 | 22.36 |
| May | 34.67 | 23.31 | 154.67 | 23.87 | 0.00 | 23.87 |
| June | 9.33 | 23.99 | 269.00 | 24.00 | 9.17 | 24.00 |
| July | 0.00 | 0.00 | 258.00 | 23.98 | 0.00 | 23.98 |
| August | 32.17 | 22.80 | 241.50 | 23.79 | 0.00 | 23.79 |
| September | 34.33 | 23.26 | 150.67 | 23.85 | 3.67 | 23.85 |
| October | 236.33 | 22.60 | 8.67 | 22.59 | 5.00 | 22.56 |
| November | 273.00 | 21.42 | 131.33 | 21.29 | 131.33 | 21.23 |
| December | 260.00 | 21.01 | 260.00 | 21.01 | 260.00 | 21.01 |
| Annual Sum or Average | 1893.67 | 21.63 | 2194.33 | 22.08 | 1127.83 | 21.86 |
| Minimum of Months | 0.00 | 0.00 | 8.67 | 21.01 | 0.00 | 21.01 |
| Maximum of Months | 299.00 | 23.99 | 273.00 | 24.00 | 273.00 | 24.00 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 236.67 | 22.60 | 78.83 | 22.68 | 52.83 | 22.64 |
| February | 163.67 | 23.12 | 99.17 | 23.25 | 40.00 | 23.18 |
| March | 102.50 | 23.48 | 162.67 | 23.68 | 28.50 | 23.61 |
| April | 10.33 | 23.95 | 158.83 | 23.99 | 2.50 | 23.98 |
| May | 0.00 | 0.00 | 266.83 | 24.00 | 0.00 | 24.00 |
| June | 37.50 | 24.00 | 285.17 | 24.00 | 37.50 | 24.00 |
| July | 38.50 | 24.01 | 260.00 | 24.00 | 38.50 | 24.00 |
| August | 71.33 | 24.00 | 299.00 | 24.00 | 71.33 | 24.00 |
| September | 16.17 | 24.00 | 257.67 | 24.00 | 16.17 | 24.00 |
| October | 1.83 | 23.82 | 212.17 | 23.99 | 1.17 | 23.99 |
| November | 69.00 | 23.04 | 156.00 | 23.66 | 16.17 | 23.65 |
| December | 206.17 | 21.78 | 93.33 | 22.19 | 53.00 | 22.23 |
| Annual Sum or Average | 953.67 | 22.90 | 2329.67 | 23.60 | 357.67 | 23.57 |
| Minimum of Months | 0.00 | 0.00 | 78.83 | 22.19 | 0.00 | 22.23 |
| Maximum of Months | 236.67 | 24.01 | 299.00 | 24.00 | 71.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 231.00 | 21.00 | 227.50 | 21.00 | 227.50 | 21.00 |
| February | 209.00 | 21.00 | 191.83 | 21.00 | 191.83 | 21.00 |
| March | 253.00 | 21.01 | 167.67 | 21.00 | 167.67 | 21.00 |
| April | 208.50 | 21.80 | 32.33 | 21.69 | 32.33 | 21.61 |
| May | 70.00 | 22.48 | 122.33 | 23.44 | 0.33 | 23.43 |
| June | 55.50 | 24.06 | 226.67 | 24.02 | 53.83 | 24.03 |
| July | 43.00 | 23.99 | 198.17 | 23.99 | 42.67 | 23.99 |
| August | 103.17 | 23.30 | 190.17 | 23.73 | 71.67 | 23.78 |
| September | 75.00 | 22.52 | 127.67 | 23.43 | 18.17 | 23.48 |
| October | 199.33 | 21.44 | 11.83 | 21.55 | 2.33 | 21.54 |
| November | 225.50 | 21.22 | 103.83 | 21.19 | 103.83 | 21.18 |
| December | 220.00 | 21.00 | 207.50 | 21.00 | 207.50 | 21.00 |
| Annual Sum or Average | 1893.00 | 21.56 | 1807.50 | 22.00 | 1119.67 | 21.88 |
| Minimum of Months | 43.00 | 21.00 | 11.83 | 21.00 | 0.33 | 21.00 |
| Maximum of Months | 253.00 | 24.06 | 227.50 | 24.02 | 227.50 | 24.03 |
Report: ComfortReportSimple55Monthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.00 | 273.00 | 21.00 | 273.00 | 21.00 |
| February | 247.00 | 21.02 | 244.83 | 21.01 | 244.83 | 21.01 |
| March | 299.00 | 21.19 | 260.17 | 21.12 | 260.17 | 21.09 |
| April | 260.00 | 22.57 | 67.33 | 22.28 | 67.33 | 22.08 |
| May | 99.83 | 23.64 | 100.83 | 23.80 | 1.50 | 23.78 |
| June | 1.83 | 23.99 | 246.67 | 24.00 | 0.00 | 24.00 |
| July | 0.83 | 23.25 | 245.17 | 23.99 | 0.00 | 23.99 |
| August | 41.00 | 22.95 | 221.00 | 23.82 | 0.00 | 23.82 |
| September | 34.83 | 23.86 | 73.83 | 23.95 | 0.00 | 23.95 |
| October | 245.17 | 23.06 | 13.00 | 22.97 | 13.00 | 22.88 |
| November | 273.00 | 21.54 | 170.83 | 21.36 | 170.83 | 21.27 |
| December | 260.00 | 21.00 | 260.00 | 21.00 | 260.00 | 21.00 |
| Annual Sum or Average | 2035.50 | 21.77 | 2176.67 | 22.01 | 1290.67 | 21.78 |
| Minimum of Months | 0.83 | 21.00 | 13.00 | 21.00 | 0.00 | 21.00 |
| Maximum of Months | 299.00 | 23.99 | 273.00 | 24.00 | 273.00 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.02494 | 12.68118 | -0.6906 | 15.31796 |
| February | 247.00000 | 21.12447 | 14.86120 | -0.5988 | 13.19871 |
| March | 299.00000 | 21.19724 | 19.63248 | -0.5174 | 11.43944 |
| April | 260.00000 | 21.93927 | 21.54971 | -0.2277 | 8.13294 |
| May | 286.00000 | 23.16876 | 38.35681 | -0.5571 | 15.32742 |
| June | 286.00000 | 23.50481 | 47.47198 | -0.3120 | 8.46361 |
| July | 260.00000 | 23.06405 | 52.74119 | -0.3720 | 9.68888 |
| August | 299.00000 | 22.68377 | 54.85428 | -0.5035 | 13.15059 |
| September | 260.00000 | 23.31745 | 40.75647 | -0.4423 | 10.87723 |
| October | 273.00000 | 22.33623 | 33.03046 | -0.0052 | 7.32685 |
| November | 273.00000 | 21.38918 | 24.77588 | -0.4000 | 9.50130 |
| December | 260.00000 | 21.00987 | 14.73401 | -0.6736 | 14.78263 |
| Annual Sum or Average | 3276.00000 | 22.15800 | 31.58594 | -0.4417 | 11.44623 |
| Minimum of Months | 247.00000 | 21.00987 | 12.68118 | -0.6906 | 7.32685 |
| Maximum of Months | 299.00000 | 23.50481 | 54.85428 | -0.0052 | 15.32742 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.05878 | 12.70731 | -0.6421 | 13.96228 |
| February | 247.00000 | 21.21998 | 14.86608 | -0.5390 | 11.80441 |
| March | 299.00000 | 21.36987 | 19.54528 | -0.4386 | 10.02683 |
| April | 260.00000 | 22.19365 | 21.32836 | -0.1375 | 7.32148 |
| May | 286.00000 | 23.29324 | 38.20935 | -0.4935 | 13.03419 |
| June | 286.00000 | 23.51503 | 47.39569 | -0.2935 | 7.77466 |
| July | 260.00000 | 22.68450 | 53.89189 | -0.4840 | 11.05515 |
| August | 299.00000 | 22.41974 | 55.66512 | -0.5771 | 13.92613 |
| September | 260.00000 | 23.43959 | 40.46774 | -0.3853 | 9.28730 |
| October | 273.00000 | 22.63942 | 32.59860 | 0.08755 | 7.11766 |
| November | 273.00000 | 21.60637 | 24.57892 | -0.3206 | 8.50554 |
| December | 260.00000 | 21.04526 | 14.75300 | -0.6249 | 13.47852 |
| Annual Sum or Average | 3276.00000 | 22.21738 | 31.63495 | -0.4045 | 10.62358 |
| Minimum of Months | 247.00000 | 21.04526 | 12.70731 | -0.6421 | 7.11766 |
| Maximum of Months | 299.00000 | 23.51503 | 55.66512 | 0.08755 | 13.96228 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 20.91629 | 10.76655 | -0.6710 | 14.72552 |
| February | 247.00000 | 20.95366 | 13.12990 | -0.6145 | 13.16343 |
| March | 299.00000 | 21.00101 | 17.93477 | -0.5347 | 11.27214 |
| April | 260.00000 | 21.53228 | 20.19334 | -0.3183 | 7.98136 |
| May | 286.00000 | 23.20416 | 36.17146 | -0.6233 | 16.06473 |
| June | 286.00000 | 23.81165 | 45.31092 | -0.3289 | 7.68354 |
| July | 260.00000 | 23.40459 | 51.17510 | -0.4297 | 9.47650 |
| August | 299.00000 | 22.95232 | 53.43384 | -0.5711 | 13.06945 |
| September | 260.00000 | 23.52471 | 39.20531 | -0.5025 | 10.92108 |
| October | 273.00000 | 22.07173 | 31.95440 | -0.0939 | 6.56816 |
| November | 273.00000 | 21.05787 | 23.46629 | -0.4621 | 9.88391 |
| December | 260.00000 | 20.93788 | 12.79255 | -0.6394 | 13.86283 |
| Annual Sum or Average | 3276.00000 | 22.12836 | 29.92387 | -0.4826 | 11.23805 |
| Minimum of Months | 247.00000 | 20.91629 | 10.76655 | -0.6710 | 6.56816 |
| Maximum of Months | 299.00000 | 23.81165 | 53.43384 | -0.0939 | 16.06473 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 20.99995 | 12.68220 | -0.7572 | 17.26379 |
| February | 247.00000 | 21.00518 | 14.93304 | -0.6954 | 15.41956 |
| March | 299.00000 | 21.01651 | 19.78472 | -0.6197 | 13.36862 |
| April | 260.00000 | 21.31115 | 22.11892 | -0.4226 | 9.50147 |
| May | 286.00000 | 22.84526 | 39.18494 | -0.7070 | 19.51336 |
| June | 286.00000 | 23.35004 | 48.12176 | -0.3940 | 9.56868 |
| July | 260.00000 | 22.45015 | 54.65087 | -0.5861 | 13.53625 |
| August | 299.00000 | 21.97797 | 57.17227 | -0.7524 | 18.54928 |
| September | 260.00000 | 22.69856 | 42.33044 | -0.6860 | 16.39541 |
| October | 273.00000 | 21.79317 | 34.18251 | -0.1710 | 6.91601 |
| November | 273.00000 | 21.12399 | 24.99906 | -0.5018 | 10.90650 |
| December | 260.00000 | 21.00059 | 14.73829 | -0.7155 | 15.99348 |
| Annual Sum or Average | 3276.00000 | 21.80848 | 32.38252 | -0.5842 | 13.93743 |
| Minimum of Months | 247.00000 | 20.99995 | 12.68220 | -0.7572 | 6.91601 |
| Maximum of Months | 299.00000 | 23.35004 | 57.17227 | -0.1710 | 19.51336 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.00032 | 12.71479 | -0.7139 | 15.88035 |
| February | 247.00000 | 21.00766 | 14.97342 | -0.6567 | 14.25872 |
| March | 299.00000 | 21.06101 | 19.78039 | -0.5717 | 12.18742 |
| April | 260.00000 | 21.50399 | 21.99457 | -0.3523 | 8.42721 |
| May | 286.00000 | 22.93968 | 39.16669 | -0.6565 | 17.25805 |
| June | 286.00000 | 23.26344 | 48.32930 | -0.4035 | 9.15698 |
| July | 260.00000 | 21.94500 | 56.23953 | -0.7354 | 16.91061 |
| August | 299.00000 | 21.59333 | 58.42963 | -0.8626 | 21.37790 |
| September | 260.00000 | 22.73464 | 42.26681 | -0.6567 | 15.27597 |
| October | 273.00000 | 22.04195 | 33.88411 | -0.0941 | 6.35494 |
| November | 273.00000 | 21.25705 | 24.87469 | -0.4418 | 9.86748 |
| December | 260.00000 | 21.00067 | 14.76952 | -0.6715 | 14.68408 |
| Annual Sum or Average | 3276.00000 | 21.78824 | 32.59759 | -0.5688 | 13.50859 |
| Minimum of Months | 247.00000 | 21.00032 | 12.71479 | -0.8626 | 6.35494 |
| Maximum of Months | 299.00000 | 23.26344 | 58.42963 | -0.0941 | 21.37790 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.01836 | 12.68102 | -0.6999 | 15.58025 |
| February | 247.00000 | 21.11741 | 14.86460 | -0.6027 | 13.27660 |
| March | 299.00000 | 21.18510 | 19.64230 | -0.5223 | 11.50989 |
| April | 260.00000 | 21.90959 | 21.58360 | -0.2371 | 8.17571 |
| May | 286.00000 | 23.13000 | 38.46014 | -0.5750 | 15.80739 |
| June | 286.00000 | 23.46893 | 47.61100 | -0.3298 | 8.74479 |
| July | 260.00000 | 22.97693 | 53.01849 | -0.4041 | 10.23546 |
| August | 299.00000 | 22.61506 | 55.08333 | -0.5291 | 13.65467 |
| September | 260.00000 | 23.28931 | 40.83964 | -0.4548 | 11.11419 |
| October | 273.00000 | 22.31707 | 33.07100 | -0.0114 | 7.31730 |
| November | 273.00000 | 21.36683 | 24.79461 | -0.4082 | 9.60498 |
| December | 260.00000 | 21.00541 | 14.73565 | -0.6822 | 15.02489 |
| Annual Sum or Average | 3276.00000 | 22.12771 | 31.66551 | -0.4548 | 11.68550 |
| Minimum of Months | 247.00000 | 21.00541 | 12.68102 | -0.6999 | 7.31730 |
| Maximum of Months | 299.00000 | 23.46893 | 55.08333 | -0.0114 | 15.80739 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.04530 | 12.70934 | -0.6505 | 14.15495 |
| February | 247.00000 | 21.21022 | 14.87217 | -0.5407 | 11.80135 |
| March | 299.00000 | 21.35559 | 19.55731 | -0.4416 | 10.02114 |
| April | 260.00000 | 22.16914 | 21.36645 | -0.1449 | 7.30614 |
| May | 286.00000 | 23.26144 | 38.31487 | -0.5092 | 13.36301 |
| June | 286.00000 | 23.47255 | 47.56013 | -0.3137 | 8.03122 |
| July | 260.00000 | 22.54838 | 54.32132 | -0.5306 | 11.97709 |
| August | 299.00000 | 22.31138 | 56.02046 | -0.6146 | 14.70757 |
| September | 260.00000 | 23.41465 | 40.55026 | -0.3974 | 9.44443 |
| October | 273.00000 | 22.62323 | 32.64998 | 0.08191 | 7.05982 |
| November | 273.00000 | 21.56991 | 24.60887 | -0.3317 | 8.59069 |
| December | 260.00000 | 21.03032 | 14.75692 | -0.6325 | 13.65313 |
| Annual Sum or Average | 3276.00000 | 22.17754 | 31.74342 | -0.4194 | 10.86186 |
| Minimum of Months | 247.00000 | 21.03032 | 12.70934 | -0.6505 | 7.05982 |
| Maximum of Months | 299.00000 | 23.47255 | 56.02046 | 0.08191 | 14.70757 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 20.91034 | 10.76162 | -0.6743 | 14.83060 |
| February | 247.00000 | 20.95219 | 13.14035 | -0.6151 | 13.18263 |
| March | 299.00000 | 20.99924 | 17.94779 | -0.5354 | 11.28437 |
| April | 260.00000 | 21.52252 | 20.21637 | -0.3209 | 7.99938 |
| May | 286.00000 | 23.19004 | 36.21092 | -0.6288 | 16.22434 |
| June | 286.00000 | 23.80331 | 45.35462 | -0.3334 | 7.75239 |
| July | 260.00000 | 23.35644 | 51.32800 | -0.4460 | 9.78542 |
| August | 299.00000 | 22.90453 | 53.58787 | -0.5866 | 13.42253 |
| September | 260.00000 | 23.51153 | 39.25071 | -0.5077 | 11.02879 |
| October | 273.00000 | 22.06089 | 31.98844 | -0.0967 | 6.56090 |
| November | 273.00000 | 21.05474 | 23.48186 | -0.4641 | 9.92298 |
| December | 260.00000 | 20.93303 | 12.79041 | -0.6425 | 13.95701 |
| Annual Sum or Average | 3276.00000 | 22.11408 | 29.96829 | -0.4879 | 11.34616 |
| Minimum of Months | 247.00000 | 20.91034 | 10.76162 | -0.6743 | 6.56090 |
| Maximum of Months | 299.00000 | 23.80331 | 53.58787 | -0.0967 | 16.22434 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.00001 | 12.67862 | -0.7573 | 17.26753 |
| February | 247.00000 | 21.00525 | 14.92949 | -0.6954 | 15.41793 |
| March | 299.00000 | 21.01657 | 19.78121 | -0.6196 | 13.36568 |
| April | 260.00000 | 21.31104 | 22.11557 | -0.4225 | 9.49972 |
| May | 286.00000 | 22.84507 | 39.18168 | -0.7068 | 19.51035 |
| June | 286.00000 | 23.35037 | 48.11820 | -0.3935 | 9.56258 |
| July | 260.00000 | 22.44469 | 54.66755 | -0.5878 | 13.58111 |
| August | 299.00000 | 21.97186 | 57.19253 | -0.7544 | 18.61018 |
| September | 260.00000 | 22.69470 | 42.33743 | -0.6871 | 16.43086 |
| October | 273.00000 | 21.79122 | 34.18227 | -0.1714 | 6.91647 |
| November | 273.00000 | 21.12358 | 24.99618 | -0.5020 | 10.91022 |
| December | 260.00000 | 21.00060 | 14.73476 | -0.7157 | 15.99800 |
| Annual Sum or Average | 3276.00000 | 21.80700 | 32.38396 | -0.5846 | 13.94906 |
| Minimum of Months | 247.00000 | 21.00001 | 12.67862 | -0.7573 | 6.91647 |
| Maximum of Months | 299.00000 | 23.35037 | 57.19253 | -0.1714 | 19.51035 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.00031 | 12.71928 | -0.7139 | 15.88322 |
| February | 247.00000 | 21.00776 | 14.97779 | -0.6566 | 14.25588 |
| March | 299.00000 | 21.06175 | 19.78416 | -0.5714 | 12.18140 |
| April | 260.00000 | 21.50599 | 21.99751 | -0.3518 | 8.42150 |
| May | 286.00000 | 22.94353 | 39.16132 | -0.6552 | 17.22507 |
| June | 286.00000 | 23.26919 | 48.31236 | -0.4016 | 9.12411 |
| July | 260.00000 | 21.94450 | 56.24226 | -0.7358 | 16.92557 |
| August | 299.00000 | 21.59087 | 58.43970 | -0.8637 | 21.41929 |
| September | 260.00000 | 22.73492 | 42.26836 | -0.6568 | 15.28471 |
| October | 273.00000 | 22.04306 | 33.88714 | -0.0940 | 6.35476 |
| November | 273.00000 | 21.25763 | 24.87857 | -0.4418 | 9.86868 |
| December | 260.00000 | 21.00068 | 14.77396 | -0.6716 | 14.68780 |
| Annual Sum or Average | 3276.00000 | 21.78921 | 32.59911 | -0.5687 | 13.50790 |
| Minimum of Months | 247.00000 | 21.00031 | 12.71928 | -0.8637 | 6.35476 |
| Maximum of Months | 299.00000 | 23.26919 | 58.43970 | -0.0940 | 21.41929 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.02089 | 12.67572 | -0.6970 | 15.50191 |
| February | 247.00000 | 21.11815 | 14.85928 | -0.6020 | 13.26111 |
| March | 299.00000 | 21.18670 | 19.63596 | -0.5215 | 11.49800 |
| April | 260.00000 | 21.92275 | 21.56289 | -0.2326 | 8.15692 |
| May | 286.00000 | 23.14983 | 38.40960 | -0.5659 | 15.53616 |
| June | 286.00000 | 23.48661 | 47.54456 | -0.3215 | 8.59644 |
| July | 260.00000 | 23.02153 | 52.87538 | -0.3876 | 9.92967 |
| August | 299.00000 | 22.65600 | 54.94495 | -0.5137 | 13.31943 |
| September | 260.00000 | 23.31617 | 40.76169 | -0.4433 | 10.86537 |
| October | 273.00000 | 22.34244 | 33.01651 | -0.0030 | 7.31856 |
| November | 273.00000 | 21.37669 | 24.77925 | -0.4043 | 9.55594 |
| December | 260.00000 | 21.00654 | 14.73011 | -0.6798 | 14.95858 |
| Annual Sum or Average | 3276.00000 | 22.14488 | 31.61580 | -0.4477 | 11.55474 |
| Minimum of Months | 247.00000 | 21.00654 | 12.67572 | -0.6970 | 7.31856 |
| Maximum of Months | 299.00000 | 23.48661 | 54.94495 | -0.0030 | 15.53616 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.05142 | 12.70672 | -0.6460 | 14.04594 |
| February | 247.00000 | 21.21354 | 14.86861 | -0.5390 | 11.76807 |
| March | 299.00000 | 21.36028 | 19.55158 | -0.4398 | 10.00277 |
| April | 260.00000 | 22.19423 | 21.32885 | -0.1368 | 7.29383 |
| May | 286.00000 | 23.29353 | 38.23100 | -0.4946 | 12.98158 |
| June | 286.00000 | 23.50521 | 47.43976 | -0.2993 | 7.80832 |
| July | 260.00000 | 22.62762 | 54.06931 | -0.5033 | 11.38747 |
| August | 299.00000 | 22.38595 | 55.77310 | -0.5884 | 14.08621 |
| September | 260.00000 | 23.45738 | 40.41850 | -0.3788 | 9.09728 |
| October | 273.00000 | 22.67552 | 32.54026 | 0.09856 | 7.11713 |
| November | 273.00000 | 21.59353 | 24.58120 | -0.3233 | 8.52146 |
| December | 260.00000 | 21.03541 | 14.75354 | -0.6286 | 13.55744 |
| Annual Sum or Average | 3276.00000 | 22.20959 | 31.65684 | -0.4071 | 10.65521 |
| Minimum of Months | 247.00000 | 21.03541 | 12.70672 | -0.6460 | 7.11713 |
| Maximum of Months | 299.00000 | 23.50521 | 55.77310 | 0.09856 | 14.08621 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 20.91636 | 10.75189 | -0.6711 | 14.73239 |
| February | 247.00000 | 20.95536 | 13.11495 | -0.6127 | 13.11630 |
| March | 299.00000 | 21.00563 | 17.91433 | -0.5315 | 11.20607 |
| April | 260.00000 | 21.60193 | 20.10210 | -0.2994 | 7.83382 |
| May | 286.00000 | 23.29657 | 35.96686 | -0.5896 | 15.04103 |
| June | 286.00000 | 23.86623 | 45.06915 | -0.3033 | 7.27962 |
| July | 260.00000 | 23.53934 | 50.74597 | -0.3833 | 8.62044 |
| August | 299.00000 | 23.10009 | 52.96164 | -0.5229 | 11.93925 |
| September | 260.00000 | 23.64452 | 38.85612 | -0.4592 | 9.95862 |
| October | 273.00000 | 22.19860 | 31.70629 | -0.0613 | 6.54235 |
| November | 273.00000 | 21.07476 | 23.41743 | -0.4553 | 9.79176 |
| December | 260.00000 | 20.93760 | 12.77438 | -0.6396 | 13.87072 |
| Annual Sum or Average | 3276.00000 | 22.19293 | 29.74239 | -0.4607 | 10.83601 |
| Minimum of Months | 247.00000 | 20.91636 | 10.75189 | -0.6711 | 6.54235 |
| Maximum of Months | 299.00000 | 23.86623 | 52.96164 | -0.0613 | 15.04103 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.00012 | 12.68199 | -0.7564 | 17.24031 |
| February | 247.00000 | 21.00565 | 14.93250 | -0.6937 | 15.37296 |
| March | 299.00000 | 21.01973 | 19.78129 | -0.6164 | 13.29525 |
| April | 260.00000 | 21.33990 | 22.09262 | -0.4121 | 9.37005 |
| May | 286.00000 | 22.91405 | 39.02762 | -0.6780 | 18.62609 |
| June | 286.00000 | 23.42459 | 47.86723 | -0.3623 | 9.00769 |
| July | 260.00000 | 22.59841 | 54.17942 | -0.5352 | 12.35626 |
| August | 299.00000 | 22.08135 | 56.82567 | -0.7159 | 17.54615 |
| September | 260.00000 | 22.78082 | 42.13378 | -0.6563 | 15.56780 |
| October | 273.00000 | 21.83328 | 34.11454 | -0.1586 | 6.87857 |
| November | 273.00000 | 21.12952 | 24.99118 | -0.4994 | 10.87066 |
| December | 260.00000 | 21.00062 | 14.73810 | -0.7151 | 15.98002 |
| Annual Sum or Average | 3276.00000 | 21.85515 | 32.25311 | -0.5666 | 13.53034 |
| Minimum of Months | 247.00000 | 21.00012 | 12.68199 | -0.7564 | 6.87857 |
| Maximum of Months | 299.00000 | 23.42459 | 56.82567 | -0.1586 | 18.62609 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.00037 | 12.71666 | -0.7120 | 15.82774 |
| February | 247.00000 | 21.00871 | 14.97463 | -0.6537 | 14.17951 |
| March | 299.00000 | 21.06958 | 19.77466 | -0.5660 | 12.07361 |
| April | 260.00000 | 21.54421 | 21.96152 | -0.3378 | 8.28301 |
| May | 286.00000 | 23.04068 | 38.92236 | -0.6160 | 16.14227 |
| June | 286.00000 | 23.41042 | 47.83336 | -0.3494 | 8.28109 |
| July | 260.00000 | 22.16304 | 55.52319 | -0.6634 | 14.82350 |
| August | 299.00000 | 21.73741 | 57.93265 | -0.8141 | 19.78579 |
| September | 260.00000 | 22.84771 | 41.97677 | -0.6169 | 14.16976 |
| October | 273.00000 | 22.10958 | 33.77404 | -0.0738 | 6.34899 |
| November | 273.00000 | 21.26824 | 24.86167 | -0.4367 | 9.80742 |
| December | 260.00000 | 21.00073 | 14.77142 | -0.6701 | 14.64774 |
| Annual Sum or Average | 3276.00000 | 21.85995 | 32.39472 | -0.5430 | 12.89539 |
| Minimum of Months | 247.00000 | 21.00037 | 12.71666 | -0.8141 | 6.34899 |
| Maximum of Months | 299.00000 | 23.41042 | 57.93265 | -0.0738 | 19.78579 |
Report: OccupantComfortDataSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.01179 | 14.79019 | -0.6733 | 14.70860 |
| February | 247.00000 | 21.05389 | 17.02127 | -0.6081 | 13.01918 |
| March | 299.00000 | 21.25244 | 21.70588 | -0.4941 | 10.71171 |
| April | 260.00000 | 22.30203 | 23.49674 | -0.1571 | 6.90294 |
| May | 286.00000 | 23.71723 | 39.43591 | -0.3947 | 10.29226 |
| June | 286.00000 | 23.97229 | 49.00375 | -0.1415 | 5.71884 |
| July | 260.00000 | 23.32784 | 54.60743 | -0.3234 | 7.79121 |
| August | 299.00000 | 22.90971 | 56.77434 | -0.4686 | 10.62827 |
| September | 260.00000 | 23.88741 | 42.84316 | -0.2854 | 7.03972 |
| October | 273.00000 | 23.06418 | 34.41655 | 0.14454 | 6.58501 |
| November | 273.00000 | 21.66935 | 26.46678 | -0.3227 | 8.46053 |
| December | 260.00000 | 21.02523 | 16.85739 | -0.6278 | 13.52128 |
| Annual Sum or Average | 3276.00000 | 22.44613 | 33.41016 | -0.3621 | 9.60464 |
| Minimum of Months | 247.00000 | 21.01179 | 14.79019 | -0.6733 | 5.71884 |
| Maximum of Months | 299.00000 | 23.97229 | 56.77434 | 0.14454 | 14.70860 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 18.77350 | 9.62744 | -1.0428 | 28.84855 |
| February | 247.00000 | 19.83018 | 11.53594 | -0.7951 | 19.40764 |
| March | 299.00000 | 21.10643 | 15.40051 | -0.4797 | 11.70987 |
| April | 260.00000 | 23.69763 | 15.78016 | 0.13471 | 7.55099 |
| May | 286.00000 | 25.99964 | 29.17378 | 0.17620 | 8.41633 |
| June | 286.00000 | 26.59713 | 37.52758 | 0.48052 | 10.14615 |
| July | 260.00000 | 25.78000 | 43.95655 | 0.28909 | 7.17098 |
| August | 299.00000 | 25.17801 | 46.31370 | 0.09786 | 6.00819 |
| September | 260.00000 | 25.98182 | 32.82455 | 0.18435 | 6.34106 |
| October | 273.00000 | 23.93901 | 26.61714 | 0.26580 | 7.81827 |
| November | 273.00000 | 21.51513 | 20.35616 | -0.3541 | 9.67508 |
| December | 260.00000 | 19.17666 | 11.61083 | -0.9410 | 24.95706 |
| Annual Sum or Average | 3276.00000 | 23.17439 | 25.30991 | -0.1581 | 12.21515 |
| Minimum of Months | 247.00000 | 18.77350 | 9.62744 | -1.0428 | 6.00819 |
| Maximum of Months | 299.00000 | 26.59713 | 46.31370 | 0.48052 | 28.84855 |
Report: OccupantComfortDataSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 16.27764 | 12.90701 | -1.5511 | 53.76984 |
| February | 247.00000 | 17.04728 | 15.31643 | -1.3635 | 43.99461 |
| March | 299.00000 | 18.13795 | 20.24009 | -1.0932 | 31.63369 |
| April | 260.00000 | 21.03739 | 20.60380 | -0.4123 | 11.71664 |
| May | 286.00000 | 24.34110 | 34.23384 | -0.2913 | 12.36887 |
| June | 286.00000 | 25.51105 | 41.71948 | 0.17144 | 7.09158 |
| July | 260.00000 | 24.97059 | 46.79222 | 0.07595 | 5.98838 |
| August | 299.00000 | 24.19172 | 49.75546 | -0.1685 | 7.08965 |
| September | 260.00000 | 24.22579 | 37.90533 | -0.2941 | 7.89441 |
| October | 273.00000 | 21.75531 | 32.49822 | -0.1696 | 7.41952 |
| November | 273.00000 | 18.86523 | 25.76120 | -0.8941 | 24.05984 |
| December | 260.00000 | 16.59673 | 15.29283 | -1.4651 | 49.22502 |
| Annual Sum or Average | 3276.00000 | 21.13373 | 29.67564 | -0.6126 | 21.59280 |
| Minimum of Months | 247.00000 | 16.27764 | 12.90701 | -1.5511 | 5.98838 |
| Maximum of Months | 299.00000 | 25.51105 | 49.75546 | 0.17144 | 53.76984 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 231.00000 | 20.97982 | 9.90933 | -0.7487 | 16.96479 |
| February | 209.00000 | 21.01057 | 12.13352 | -0.6715 | 14.71739 |
| March | 253.00000 | 21.12202 | 16.84261 | -0.5609 | 12.15930 |
| April | 220.00000 | 22.25943 | 18.33627 | -0.1686 | 7.64311 |
| May | 242.00000 | 23.72582 | 34.03470 | -0.4085 | 10.39225 |
| June | 242.00000 | 23.98922 | 44.46738 | -0.1494 | 5.79421 |
| July | 220.00000 | 23.97900 | 49.49985 | -0.1028 | 5.41421 |
| August | 253.00000 | 23.81937 | 51.00363 | -0.1923 | 6.49067 |
| September | 220.00000 | 23.87632 | 37.91416 | -0.3131 | 7.63072 |
| October | 231.00000 | 22.56877 | 29.74866 | 0.00457 | 6.90399 |
| November | 231.00000 | 21.20124 | 22.19465 | -0.4748 | 10.45323 |
| December | 220.00000 | 20.98347 | 11.90867 | -0.7183 | 16.05743 |
| Annual Sum or Average | 2772.00000 | 22.47736 | 28.45290 | -0.3730 | 10.00140 |
| Minimum of Months | 209.00000 | 20.97982 | 9.90933 | -0.7487 | 5.41421 |
| Maximum of Months | 253.00000 | 23.98922 | 51.00363 | 0.00457 | 16.96479 |
Report: OccupantComfortDataSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.00624 | 13.88668 | -0.6557 | 14.19823 |
| February | 247.00000 | 21.04863 | 16.13247 | -0.5649 | 11.92128 |
| March | 299.00000 | 21.42794 | 20.72534 | -0.3800 | 8.94817 |
| April | 260.00000 | 22.96059 | 21.75853 | 0.10546 | 6.94863 |
| May | 286.00000 | 23.90573 | 37.31591 | -0.1896 | 6.68873 |
| June | 286.00000 | 23.99090 | 47.30305 | -0.0146 | 5.25717 |
| July | 260.00000 | 23.97760 | 51.79096 | 0.00883 | 5.18622 |
| August | 299.00000 | 23.74814 | 53.87549 | -0.1259 | 6.12130 |
| September | 260.00000 | 23.85921 | 41.73447 | -0.2282 | 6.56713 |
| October | 273.00000 | 22.77685 | 34.01284 | 0.12854 | 6.63805 |
| November | 273.00000 | 21.42294 | 26.00233 | -0.3393 | 8.31312 |
| December | 260.00000 | 21.00944 | 15.99126 | -0.6209 | 13.31848 |
| Annual Sum or Average | 3276.00000 | 22.61176 | 31.98967 | -0.2371 | 8.28753 |
| Minimum of Months | 247.00000 | 21.00624 | 13.88668 | -0.6557 | 5.18622 |
| Maximum of Months | 299.00000 | 23.99090 | 53.87549 | 0.12854 | 14.19823 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 22.77143 | 57.45478 | 0.23661 | 7.51351 |
| February | 247.00000 | 23.39553 | 51.56414 | 0.39791 | 9.15246 |
| March | 299.00000 | 23.81049 | 45.80091 | 0.51624 | 11.09397 |
| April | 260.00000 | 23.99165 | 32.17483 | 0.58841 | 12.56953 |
| May | 286.00000 | 23.99777 | 40.52844 | 0.05996 | 5.62820 |
| June | 286.00000 | 24.00018 | 49.13300 | 0.17090 | 6.03921 |
| July | 260.00000 | 24.00221 | 53.73041 | 0.19367 | 6.14064 |
| August | 299.00000 | 23.99981 | 56.53935 | 0.15864 | 5.88105 |
| September | 260.00000 | 23.99646 | 44.45163 | 0.05741 | 5.48694 |
| October | 273.00000 | 23.99282 | 40.84027 | 0.64206 | 13.92578 |
| November | 273.00000 | 23.75066 | 42.81753 | 0.51145 | 11.37460 |
| December | 260.00000 | 22.22393 | 52.85401 | 0.13819 | 8.00093 |
| Annual Sum or Average | 3276.00000 | 23.67145 | 47.35587 | 0.30519 | 8.54785 |
| Minimum of Months | 247.00000 | 22.22393 | 32.17483 | 0.05741 | 5.48694 |
| Maximum of Months | 299.00000 | 24.00221 | 57.45478 | 0.64206 | 13.92578 |
Report: OccupantComfortDataSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 231.00000 | 20.99976 | 17.51574 | -0.6205 | 13.28160 |
| February | 209.00000 | 20.99998 | 19.89595 | -0.5439 | 11.42810 |
| March | 253.00000 | 21.00808 | 24.79734 | -0.4393 | 9.37357 |
| April | 220.00000 | 21.91018 | 26.30132 | -0.1036 | 6.94837 |
| May | 242.00000 | 23.54743 | 41.19524 | -0.3127 | 9.50916 |
| June | 242.00000 | 23.99034 | 51.16030 | -0.0073 | 5.49862 |
| July | 200.00000 | 23.98344 | 53.60717 | -0.0344 | 5.18282 |
| August | 230.00000 | 23.64571 | 57.19204 | -0.1728 | 7.26458 |
| September | 219.00000 | 23.42890 | 46.55849 | -0.3019 | 8.79628 |
| October | 231.00000 | 21.78460 | 38.98856 | -0.0020 | 6.55642 |
| November | 231.00000 | 21.28151 | 29.49435 | -0.3014 | 8.20251 |
| December | 220.00000 | 20.99956 | 19.73315 | -0.5768 | 12.24532 |
| Annual Sum or Average | 2728.00000 | 22.29240 | 35.50118 | -0.2852 | 8.69708 |
| Minimum of Months | 200.00000 | 20.99956 | 17.51574 | -0.6205 | 5.18282 |
| Maximum of Months | 253.00000 | 23.99034 | 57.19204 | -0.0020 | 13.28160 |
Report: OccupantComfortDataSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 20.99831 | 11.83926 | -0.7256 | 16.23651 |
| February | 247.00000 | 21.01736 | 14.05725 | -0.6600 | 14.36245 |
| March | 299.00000 | 21.18773 | 18.70904 | -0.5427 | 11.74982 |
| April | 260.00000 | 22.57081 | 19.85626 | -0.1154 | 7.17080 |
| May | 286.00000 | 23.87408 | 35.13909 | -0.3428 | 8.92446 |
| June | 286.00000 | 23.99951 | 44.45824 | -0.1153 | 5.50806 |
| July | 260.00000 | 23.98066 | 49.40829 | -0.1083 | 5.39607 |
| August | 299.00000 | 23.79690 | 50.94926 | -0.2154 | 6.64206 |
| September | 260.00000 | 23.97753 | 37.89296 | -0.2746 | 6.80921 |
| October | 273.00000 | 23.15879 | 30.60524 | 0.12991 | 6.70053 |
| November | 273.00000 | 21.54001 | 23.59913 | -0.3922 | 9.54600 |
| December | 260.00000 | 20.99961 | 13.84151 | -0.6858 | 15.09359 |
| Annual Sum or Average | 3276.00000 | 22.60876 | 29.47328 | -0.3352 | 9.46410 |
| Minimum of Months | 247.00000 | 20.99831 | 11.83926 | -0.7256 | 5.39607 |
| Maximum of Months | 299.00000 | 23.99951 | 50.94926 | 0.12991 | 16.23651 |
Report: OccupantComfortDataSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 20.77894 | 11.00663 | -0.7698 | 17.91741 |
| February | 247.00000 | 20.92058 | 13.73091 | -0.6796 | 15.00124 |
| March | 299.00000 | 20.98528 | 18.67058 | -0.5744 | 12.21092 |
| April | 260.00000 | 21.73480 | 20.82686 | -0.2782 | 7.70260 |
| May | 286.00000 | 23.58319 | 35.86820 | -0.4852 | 12.32366 |
| June | 286.00000 | 23.99070 | 44.69267 | -0.2187 | 6.20506 |
| July | 260.00000 | 23.94938 | 49.46178 | -0.2035 | 6.03305 |
| August | 299.00000 | 23.65215 | 51.33498 | -0.3319 | 8.02511 |
| September | 260.00000 | 23.72829 | 39.15717 | -0.4374 | 9.50831 |
| October | 273.00000 | 21.84012 | 33.27954 | -0.1640 | 6.64202 |
| November | 273.00000 | 21.01006 | 24.30978 | -0.5164 | 10.95511 |
| December | 260.00000 | 20.82126 | 13.22814 | -0.7274 | 16.60628 |
| Annual Sum or Average | 3276.00000 | 22.26851 | 29.91011 | -0.4469 | 10.71784 |
| Minimum of Months | 247.00000 | 20.77894 | 11.00663 | -0.7698 | 6.03305 |
| Maximum of Months | 299.00000 | 23.99070 | 51.33498 | -0.1640 | 17.91741 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 11.52175 | 11.83831 | -2.4635 | 78.56014 |
| February | 247.00000 | 14.31066 | 13.25961 | -1.9034 | 61.76619 |
| March | 299.00000 | 16.64130 | 18.51532 | -1.4186 | 45.51690 |
| April | 260.00000 | 19.73216 | 18.97124 | -0.6999 | 19.05141 |
| May | 286.00000 | 22.11826 | 36.89938 | -0.8897 | 26.95673 |
| June | 286.00000 | 23.17535 | 49.26677 | -0.4245 | 12.24972 |
| July | 260.00000 | 23.35257 | 55.26047 | -0.3110 | 8.98154 |
| August | 299.00000 | 22.67771 | 58.26704 | -0.5169 | 14.04391 |
| September | 260.00000 | 21.78519 | 42.30519 | -0.9024 | 25.39754 |
| October | 273.00000 | 20.31758 | 31.91307 | -0.4593 | 12.67416 |
| November | 273.00000 | 18.39341 | 23.15174 | -1.0201 | 30.37520 |
| December | 260.00000 | 12.69165 | 14.55986 | -2.2368 | 73.23949 |
| Annual Sum or Average | 3276.00000 | 18.96356 | 31.50985 | -1.0928 | 33.70316 |
| Minimum of Months | 247.00000 | 11.52175 | 11.83831 | -2.4635 | 8.98154 |
| Maximum of Months | 299.00000 | 23.35257 | 58.26704 | -0.3110 | 78.56014 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| BOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
| January | 0.243515E+12 | 0.00 | 613.10 | 617291.15 | 02-JAN-06:01 | 0.00 | 42.68 | 74.10 | 0.64 | 0.00 | 0.18 | 1.20 | 02-JAN-06:01 |
| February | 0.155590E+12 | 0.00 | 515.53 | 617291.15 | 06-FEB-06:01 | 0.00 | 39.80 | 70.89 | 0.43 | 0.00 | 0.13 | 1.20 | 06-FEB-06:01 |
| March | 0.121232E+12 | 0.00 | 507.47 | 617291.15 | 01-MAR-07:01 | 0.00 | 37.71 | 65.57 | 0.30 | 0.00 | 0.09 | 1.20 | 01-MAR-07:01 |
| April | 0.344284E+11 | 0.00 | 313.81 | 617291.15 | 03-APR-05:11 | 0.00 | 36.29 | 52.47 | 0.09 | 0.00 | 0.03 | 1.20 | 03-APR-05:11 |
| May | 0.461028E+10 | 0.00 | 132.99 | 617291.15 | 01-MAY-05:01 | 0.00 | 54.85 | 60.10 | 0.01 | 0.00 | 0.00 | 1.20 | 01-MAY-05:01 |
| June | 0.752672E+09 | 0.00 | 40.86 | 48634.49 | 12-JUN-07:01 | 0.00 | 58.51 | 59.84 | 0.00 | 0.00 | 0.00 | 0.09 | 12-JUN-07:01 |
| July | 0.575590E+09 | 0.00 | 19.57 | 219572.10 | 10-JUL-07:01 | 0.00 | 54.81 | 55.44 | 0.00 | 0.00 | 0.00 | 0.43 | 10-JUL-07:01 |
| August | 0.267346E+10 | 0.00 | 79.40 | 407182.76 | 18-AUG-07:01 | 0.00 | 49.34 | 53.29 | 0.01 | 0.00 | 0.00 | 0.79 | 18-AUG-07:01 |
| September | 0.232303E+10 | 0.00 | 125.56 | 101393.03 | 13-SEP-07:01 | 0.00 | 55.80 | 60.46 | 0.01 | 0.00 | 0.00 | 0.20 | 13-SEP-07:01 |
| October | 0.146743E+11 | 0.00 | 263.33 | 617291.15 | 16-OCT-06:11 | 0.00 | 44.35 | 54.70 | 0.04 | 0.00 | 0.01 | 1.20 | 16-OCT-06:11 |
| November | 0.755020E+11 | 0.00 | 396.89 | 617291.15 | 06-NOV-06:01 | 0.00 | 35.39 | 57.37 | 0.19 | 0.00 | 0.06 | 1.20 | 06-NOV-06:01 |
| December | 0.207604E+12 | 0.00 | 592.20 | 617291.15 | 01-DEC-06:01 | 0.00 | 41.16 | 72.63 | 0.53 | 0.00 | 0.15 | 1.20 | 01-DEC-06:01 |
| Annual Sum or Average | 0.863481E+12 | 0.00 | 3600.69 | 0.00 | 45.93 | 61.37 | 0.19 | 0.00 | 0.05 | ||||
| Minimum of Months | 0.575590E+09 | 0.00 | 19.57 | 48634.49 | 0.00 | 35.39 | 52.47 | 0.00 | 0.00 | 0.00 | 0.09 | ||
| Maximum of Months | 0.243515E+12 | 0.00 | 613.10 | 617291.15 | 0.00 | 58.51 | 74.10 | 0.64 | 0.00 | 0.18 | 1.20 |
Report: DXReportMonthly
For: VAV_POD_1 COOLING COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 |
| April | 0.595604E+10 | 0.182078E+10 | 42.45 | 0.590179E+10 | 54255981.51 | 0.00 | 0.76 | 23-APR-15:12 | 0.00 | 01-APR-00:10 | 156079.22 | 23-APR-15:12 | 156079.22 | 23-APR-15:12 | 10853.84 | 23-APR-13:24 | 42520.13 | 23-APR-15:12 | 0.00 |
| May | 0.101966E+12 | 0.273514E+11 | 202.85 | 0.936638E+11 | 0.830253E+10 | 0.00 | 1.00 | 16-MAY-12:05 | 0.00 | 01-MAY-00:10 | 465862.60 | 25-MAY-14:02 | 358570.61 | 18-MAY-14:03 | 130172.94 | 25-MAY-14:02 | 114967.20 | 25-MAY-14:02 | 0.00 |
| June | 0.229442E+12 | 0.596231E+11 | 333.46 | 0.168573E+12 | 0.608693E+11 | 0.00 | 1.00 | 06-JUN-11:20 | 0.00 | 01-JUN-00:10 | 649515.34 | 30-JUN-15:03 | 394972.40 | 29-JUN-16:00 | 280464.48 | 30-JUN-16:00 | 167899.84 | 29-JUN-16:00 | 0.00 |
| July | 0.227327E+12 | 0.586910E+11 | 344.25 | 0.158708E+12 | 0.686190E+11 | 0.00 | 1.00 | 03-JUL-05:01 | 0.00 | 01-JUL-00:23 | 499697.49 | 21-JUL-14:02 | 300139.35 | 24-JUL-14:02 | 285642.59 | 05-JUL-10:37 | 119252.72 | 21-JUL-14:02 | 0.00 |
| August | 0.184406E+12 | 0.482303E+11 | 322.38 | 0.119332E+12 | 0.650736E+11 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:03 | 511276.81 | 08-AUG-14:01 | 294479.88 | 08-AUG-14:01 | 216796.94 | 08-AUG-14:01 | 123986.81 | 08-AUG-14:01 | 0.00 |
| September | 0.429064E+11 | 0.121179E+11 | 128.06 | 0.341839E+11 | 0.872253E+10 | 0.00 | 1.00 | 01-SEP-14:05 | 0.00 | 01-SEP-00:03 | 292381.65 | 01-SEP-14:05 | 230523.92 | 01-SEP-14:05 | 123408.62 | 18-SEP-14:02 | 73287.06 | 01-SEP-14:05 | 0.00 |
| October | 0.610042E+10 | 0.179524E+10 | 25.51 | 0.580330E+10 | 0.297121E+09 | 0.00 | 0.86 | 19-OCT-14:02 | 0.00 | 01-OCT-00:10 | 182336.62 | 19-OCT-14:02 | 182336.62 | 19-OCT-14:02 | 15342.83 | 22-OCT-12:50 | 48266.72 | 19-OCT-14:02 | 0.00 |
| November | 0.146872E+10 | 0.448519E+09 | 8.50 | 0.106364E+10 | 0.405085E+09 | 0.00 | 0.41 | 01-NOV-15:00 | 0.00 | 01-NOV-00:10 | 76410.79 | 01-NOV-15:00 | 57714.32 | 01-NOV-15:00 | 18696.46 | 01-NOV-15:00 | 22835.51 | 01-NOV-15:00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.799573E+12 | 0.210078E+12 | 1407.46 | 0.587230E+12 | 0.212343E+12 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.229442E+12 | 0.596231E+11 | 344.25 | 0.168573E+12 | 0.686190E+11 | 0.00 | 1.00 | 0.00 | 649515.34 | 394972.40 | 285642.59 | 167899.84 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_1:6 COOLING COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 2563785.63 | 624727.86 | 6.80 | 1993452.48 | 570333.15 | 0.00 | 1.00 | 20-JAN-06:01 | 0.00 | 01-JAN-00:02 | 32530.13 | 20-JAN-06:01 | 26397.19 | 20-JAN-06:01 | 6132.94 | 20-JAN-06:01 | 7475.23 | 20-JAN-06:01 | 0.00 | 01-JAN-00:02 |
| February | 1410917.78 | 404856.09 | 5.77 | 1084493.05 | 326424.73 | 0.00 | 0.13 | 24-FEB-06:57 | 0.00 | 01-FEB-00:05 | 1814.93 | 24-FEB-06:57 | 1750.11 | 24-FEB-06:57 | 180.31 | 09-FEB-06:07 | 508.83 | 24-FEB-06:57 | 0.00 | 01-FEB-00:05 |
| March | 32836398.59 | 8517293.00 | 11.24 | 25055872.46 | 7780526.13 | 0.00 | 1.00 | 21-MAR-05:01 | 0.00 | 01-MAR-00:05 | 32530.13 | 21-MAR-05:01 | 28559.74 | 24-MAR-05:01 | 10818.11 | 21-MAR-05:01 | 7475.23 | 21-MAR-05:01 | 0.00 | 01-MAR-00:05 |
| April | 0.600257E+09 | 0.157283E+09 | 74.22 | 0.550126E+09 | 50131300.57 | 0.00 | 1.00 | 07-APR-05:01 | 0.00 | 01-APR-00:10 | 34271.16 | 23-APR-13:32 | 32530.13 | 22-APR-10:52 | 11477.33 | 24-APR-05:01 | 8255.54 | 23-APR-13:32 | 0.00 | 01-APR-00:10 |
| May | 0.828481E+10 | 0.201290E+10 | 207.91 | 0.662332E+10 | 0.166150E+10 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 36559.98 | 26-MAY-10:50 | 32530.13 | 14-MAY-13:52 | 14858.17 | 26-MAY-10:40 | 8607.67 | 26-MAY-10:50 | 0.00 | 01-MAY-00:10 |
| June | 0.157319E+11 | 0.378715E+10 | 310.31 | 0.110988E+11 | 0.463309E+10 | 0.00 | 1.00 | 01-JUN-05:11 | 0.00 | 01-JUN-00:20 | 39748.15 | 30-JUN-00:53 | 32827.09 | 17-JUN-13:50 | 23736.94 | 29-JUN-22:53 | 9395.11 | 30-JUN-10:50 | 0.00 | 01-JUN-00:10 |
| July | 0.181193E+11 | 0.432975E+10 | 341.14 | 0.117600E+11 | 0.635929E+10 | 0.00 | 1.00 | 01-JUL-06:53 | 0.00 | 01-JUL-00:03 | 39697.48 | 15-JUL-12:53 | 28539.96 | 02-JUL-15:50 | 26263.98 | 04-JUL-00:55 | 9411.48 | 15-JUL-14:13 | 0.00 | 01-JUL-00:03 |
| August | 0.130477E+11 | 0.310611E+10 | 278.79 | 0.823488E+10 | 0.481284E+10 | 0.00 | 1.00 | 01-AUG-03:32 | 0.00 | 01-AUG-00:03 | 37554.58 | 31-AUG-20:53 | 30725.01 | 13-AUG-14:00 | 22314.99 | 30-AUG-05:53 | 8608.40 | 31-AUG-20:53 | 0.00 | 01-AUG-00:03 |
| September | 0.283428E+10 | 0.693119E+09 | 128.29 | 0.203274E+10 | 0.801541E+09 | 0.00 | 1.00 | 01-SEP-00:13 | 0.00 | 01-SEP-00:03 | 36191.29 | 01-SEP-00:13 | 29959.74 | 09-SEP-09:53 | 21335.23 | 01-SEP-03:32 | 8297.25 | 01-SEP-00:13 | 0.00 | 01-SEP-00:03 |
| October | 0.518393E+09 | 0.132252E+09 | 77.76 | 0.428149E+09 | 90243837.25 | 0.00 | 1.00 | 01-OCT-13:53 | 0.00 | 01-OCT-00:10 | 32639.92 | 22-OCT-13:22 | 31664.05 | 21-OCT-15:22 | 15144.73 | 20-OCT-05:11 | 7505.95 | 22-OCT-13:22 | 0.00 | 01-OCT-00:10 |
| November | 0.139095E+09 | 36573090.48 | 20.16 | 99169076.14 | 39925505.80 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 32530.13 | 01-NOV-05:01 | 28585.95 | 10-NOV-06:01 | 16035.31 | 21-NOV-06:01 | 7475.23 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 |
| December | 1081642.51 | 311550.81 | 3.67 | 754593.18 | 327049.33 | 0.00 | 0.07 | 06-DEC-06:13 | 0.00 | 01-DEC-00:05 | 954.90 | 06-DEC-06:13 | 598.20 | 06-DEC-06:13 | 356.70 | 06-DEC-06:13 | 271.96 | 06-DEC-06:13 | 0.00 | 01-DEC-00:05 |
| Annual Sum or Average | 0.593137E+11 | 0.142650E+11 | 1466.06 | 0.408561E+11 | 0.184576E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 1081642.51 | 311550.81 | 3.67 | 754593.18 | 326424.73 | 0.00 | 0.07 | 0.00 | 954.90 | 598.20 | 180.31 | 271.96 | 0.00 | |||||||
| Maximum of Months | 0.181193E+11 | 0.432975E+10 | 341.14 | 0.117600E+11 | 0.635929E+10 | 0.00 | 1.00 | 0.00 | 39748.15 | 32827.09 | 26263.98 | 9411.48 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:7 COOLING COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 | 0.00 | 01-JAN-00:02 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
| April | 0.150071E+09 | 42516500.88 | 9.83 | 0.135742E+09 | 14328769.42 | 0.00 | 0.30 | 13-APR-14:00 | 0.00 | 01-APR-00:10 | 8501.78 | 13-APR-14:00 | 8501.78 | 13-APR-14:00 | 1013.79 | 18-APR-10:00 | 2347.73 | 13-APR-14:00 | 0.00 | 01-APR-00:10 |
| May | 0.102199E+11 | 0.259420E+10 | 135.88 | 0.803235E+10 | 0.218756E+10 | 0.00 | 1.00 | 16-MAY-13:50 | 0.00 | 01-MAY-00:10 | 68196.84 | 26-MAY-05:02 | 39526.40 | 26-MAY-05:02 | 28670.43 | 26-MAY-05:02 | 16224.28 | 26-MAY-05:02 | 0.00 | 01-MAY-00:10 |
| June | 0.237206E+11 | 0.593875E+10 | 243.70 | 0.158091E+11 | 0.791149E+10 | 0.00 | 1.00 | 06-JUN-10:00 | 0.00 | 01-JUN-00:10 | 75809.23 | 30-JUN-05:01 | 60066.31 | 17-JUN-13:02 | 41664.69 | 23-JUN-05:01 | 19820.13 | 29-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.154490E+11 | 0.398053E+10 | 241.26 | 0.993913E+10 | 0.550991E+10 | 0.00 | 1.00 | 01-JUL-10:41 | 0.00 | 01-JUL-00:03 | 75041.56 | 23-JUL-07:52 | 52733.23 | 02-JUL-16:12 | 44042.15 | 05-JUL-05:01 | 17667.39 | 23-JUL-07:52 | 0.00 | 01-JUL-00:03 |
| August | 0.101299E+11 | 0.260764E+10 | 172.55 | 0.618803E+10 | 0.394182E+10 | 0.00 | 1.00 | 01-AUG-05:02 | 0.00 | 01-AUG-00:03 | 72394.44 | 27-AUG-16:23 | 56750.39 | 13-AUG-13:53 | 42502.85 | 30-AUG-05:01 | 17432.90 | 27-AUG-16:23 | 0.00 | 01-AUG-00:03 |
| September | 0.275884E+10 | 0.723722E+09 | 75.90 | 0.208954E+10 | 0.669302E+09 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:03 | 68121.58 | 01-SEP-05:01 | 29335.32 | 07-SEP-13:40 | 40537.27 | 01-SEP-05:01 | 16207.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:03 |
| October | 0.261581E+09 | 70743940.45 | 8.18 | 0.225026E+09 | 36554879.24 | 0.00 | 0.65 | 19-OCT-14:00 | 0.00 | 01-OCT-00:10 | 20821.98 | 19-OCT-14:00 | 17888.30 | 19-OCT-14:00 | 3341.49 | 19-OCT-13:00 | 5272.28 | 19-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 19287560.31 | 5599917.22 | 2.17 | 13313508.15 | 5974052.16 | 0.00 | 0.14 | 01-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3780.62 | 01-NOV-14:00 | 2559.57 | 01-NOV-14:00 | 1221.05 | 01-NOV-14:00 | 1091.79 | 01-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
| Annual Sum or Average | 0.627092E+11 | 0.159637E+11 | 889.46 | 0.424323E+11 | 0.202769E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.237206E+11 | 0.593875E+10 | 243.70 | 0.158091E+11 | 0.791149E+10 | 0.00 | 1.00 | 0.00 | 75809.23 | 60066.31 | 44042.15 | 19820.13 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 115.79 | 48.49 | 67.31 | 34.26 | 557.90 | 0.00 | 0.00 | 0.00 |
| February | 188.66 | 86.17 | 102.49 | 103.59 | 443.81 | 0.00 | 0.00 | 0.00 |
| March | 248.27 | 127.04 | 121.23 | 174.56 | 340.87 | 0.00 | 0.00 | 0.00 |
| April | 317.15 | 160.63 | 156.51 | 280.32 | 204.31 | 0.00 | 0.00 | 0.00 |
| May | 389.67 | 185.87 | 203.80 | 419.51 | 116.07 | 0.00 | 0.00 | 0.00 |
| June | 376.02 | 162.59 | 213.43 | 435.79 | 80.74 | 0.00 | 0.00 | 0.00 |
| July | 401.44 | 186.63 | 214.81 | 484.32 | 75.63 | 0.00 | 0.00 | 0.00 |
| August | 330.36 | 150.11 | 180.25 | 380.33 | 90.49 | 0.00 | 0.00 | 0.00 |
| September | 258.19 | 116.00 | 142.19 | 244.05 | 157.81 | 0.00 | 0.00 | 0.00 |
| October | 163.10 | 65.48 | 97.62 | 110.76 | 231.95 | 0.00 | 0.00 | 0.00 |
| November | 99.06 | 33.40 | 65.66 | 38.34 | 333.66 | 0.00 | 0.00 | 0.00 |
| December | 88.31 | 30.91 | 57.40 | 18.06 | 538.71 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 248.33 | 112.94 | 135.39 | 227.76 | 263.62 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 88.31 | 30.91 | 57.40 | 18.06 | 75.63 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 401.44 | 186.63 | 214.81 | 484.32 | 557.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.39 | 38.53 | 16.86 | 40.34 | 72.09 | 0.00 | 0.00 | 0.00 |
| February | 70.14 | 47.37 | 22.76 | 60.64 | 59.39 | 0.00 | 0.00 | 0.00 |
| March | 61.80 | 39.11 | 22.69 | 55.56 | 48.52 | 0.00 | 0.00 | 0.00 |
| April | 55.99 | 30.39 | 25.60 | 56.08 | 31.50 | 0.00 | 0.00 | 0.00 |
| May | 47.07 | 16.09 | 30.98 | 51.51 | 18.48 | 0.00 | 0.00 | 0.00 |
| June | 42.24 | 11.26 | 30.98 | 50.21 | 12.82 | 0.00 | 0.00 | 0.00 |
| July | 46.18 | 14.63 | 31.55 | 57.91 | 11.83 | 0.00 | 0.00 | 0.00 |
| August | 49.31 | 20.63 | 28.69 | 59.26 | 14.14 | 0.00 | 0.00 | 0.00 |
| September | 52.82 | 28.13 | 24.69 | 56.37 | 24.29 | 0.00 | 0.00 | 0.00 |
| October | 45.11 | 26.53 | 18.58 | 41.67 | 33.84 | 0.00 | 0.00 | 0.00 |
| November | 40.18 | 25.22 | 14.96 | 32.59 | 45.81 | 0.00 | 0.00 | 0.00 |
| December | 42.77 | 28.04 | 14.72 | 28.60 | 70.48 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 50.62 | 27.03 | 23.59 | 49.14 | 36.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40.18 | 11.26 | 14.72 | 28.60 | 11.83 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 70.14 | 47.37 | 31.55 | 60.64 | 72.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 384.42 | 267.43 | 116.99 | 279.95 | 500.35 | 0.00 | 0.00 | 0.00 |
| February | 486.76 | 328.78 | 157.99 | 420.88 | 412.17 | 0.00 | 0.00 | 0.00 |
| March | 428.90 | 271.43 | 157.47 | 385.58 | 336.73 | 0.00 | 0.00 | 0.00 |
| April | 388.57 | 210.90 | 177.66 | 389.19 | 218.69 | 0.00 | 0.00 | 0.00 |
| May | 326.68 | 111.68 | 215.00 | 357.06 | 128.90 | 0.00 | 0.00 | 0.00 |
| June | 293.13 | 78.13 | 215.00 | 347.36 | 89.34 | 0.00 | 0.00 | 0.00 |
| July | 320.48 | 101.53 | 218.96 | 400.91 | 82.37 | 0.00 | 0.00 | 0.00 |
| August | 342.26 | 143.16 | 199.09 | 411.15 | 98.27 | 0.00 | 0.00 | 0.00 |
| September | 366.61 | 195.25 | 171.36 | 391.22 | 168.57 | 0.00 | 0.00 | 0.00 |
| October | 313.06 | 184.12 | 128.93 | 289.22 | 234.83 | 0.00 | 0.00 | 0.00 |
| November | 278.86 | 175.02 | 103.85 | 226.19 | 317.96 | 0.00 | 0.00 | 0.00 |
| December | 296.82 | 194.63 | 102.19 | 198.51 | 489.17 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 351.33 | 187.61 | 163.72 | 340.81 | 255.80 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 278.86 | 78.13 | 102.19 | 198.51 | 82.37 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 486.76 | 328.78 | 218.96 | 420.88 | 500.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 706.37 | 491.41 | 214.97 | 513.06 | 934.75 | 0.00 | 0.00 | 0.00 |
| February | 894.44 | 604.14 | 290.30 | 771.06 | 775.43 | 0.00 | 0.00 | 0.00 |
| March | 788.11 | 498.76 | 289.35 | 703.76 | 642.53 | 0.00 | 0.00 | 0.00 |
| April | 714.00 | 387.54 | 326.46 | 706.83 | 430.76 | 0.00 | 0.00 | 0.00 |
| May | 600.29 | 205.22 | 395.06 | 651.31 | 251.55 | 0.00 | 0.00 | 0.00 |
| June | 538.63 | 143.57 | 395.06 | 636.26 | 174.61 | 0.00 | 0.00 | 0.00 |
| July | 588.89 | 186.56 | 402.34 | 745.36 | 150.59 | 0.00 | 0.00 | 0.00 |
| August | 628.91 | 263.07 | 365.84 | 762.90 | 180.02 | 0.00 | 0.00 | 0.00 |
| September | 673.65 | 358.77 | 314.88 | 717.99 | 321.76 | 0.00 | 0.00 | 0.00 |
| October | 575.25 | 338.33 | 236.92 | 526.43 | 456.50 | 0.00 | 0.00 | 0.00 |
| November | 512.42 | 321.60 | 190.83 | 411.40 | 610.40 | 0.00 | 0.00 | 0.00 |
| December | 545.41 | 357.63 | 187.78 | 363.05 | 915.17 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 645.58 | 344.74 | 300.84 | 624.68 | 485.76 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 512.42 | 143.57 | 187.78 | 363.05 | 150.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 894.44 | 604.14 | 402.34 | 771.06 | 934.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 706.37 | 491.41 | 214.97 | 513.06 | 934.75 | 0.00 | 0.00 | 0.00 |
| February | 894.44 | 604.14 | 290.30 | 771.06 | 775.43 | 0.00 | 0.00 | 0.00 |
| March | 788.11 | 498.76 | 289.35 | 703.76 | 642.53 | 0.00 | 0.00 | 0.00 |
| April | 714.00 | 387.54 | 326.46 | 706.83 | 430.76 | 0.00 | 0.00 | 0.00 |
| May | 600.29 | 205.22 | 395.06 | 651.31 | 251.55 | 0.00 | 0.00 | 0.00 |
| June | 538.63 | 143.57 | 395.06 | 636.26 | 174.61 | 0.00 | 0.00 | 0.00 |
| July | 588.89 | 186.56 | 402.34 | 745.36 | 150.59 | 0.00 | 0.00 | 0.00 |
| August | 628.91 | 263.07 | 365.84 | 762.90 | 180.02 | 0.00 | 0.00 | 0.00 |
| September | 673.65 | 358.77 | 314.88 | 717.99 | 321.76 | 0.00 | 0.00 | 0.00 |
| October | 575.25 | 338.33 | 236.92 | 526.43 | 456.50 | 0.00 | 0.00 | 0.00 |
| November | 512.42 | 321.60 | 190.83 | 411.40 | 610.40 | 0.00 | 0.00 | 0.00 |
| December | 545.41 | 357.63 | 187.78 | 363.05 | 915.17 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 645.58 | 344.74 | 300.84 | 624.68 | 485.76 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 512.42 | 143.57 | 187.78 | 363.05 | 150.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 894.44 | 604.14 | 402.34 | 771.06 | 934.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 706.36 | 491.40 | 214.96 | 513.05 | 934.74 | 0.00 | 0.00 | 0.00 |
| February | 894.42 | 604.12 | 290.30 | 771.05 | 775.42 | 0.00 | 0.00 | 0.00 |
| March | 788.10 | 498.75 | 289.34 | 703.75 | 642.51 | 0.00 | 0.00 | 0.00 |
| April | 713.99 | 387.53 | 326.46 | 706.82 | 430.75 | 0.00 | 0.00 | 0.00 |
| May | 600.28 | 205.22 | 395.06 | 651.30 | 251.55 | 0.00 | 0.00 | 0.00 |
| June | 538.62 | 143.56 | 395.05 | 636.25 | 174.61 | 0.00 | 0.00 | 0.00 |
| July | 588.88 | 186.56 | 402.33 | 745.35 | 150.59 | 0.00 | 0.00 | 0.00 |
| August | 628.89 | 263.06 | 365.83 | 762.89 | 180.01 | 0.00 | 0.00 | 0.00 |
| September | 673.64 | 358.76 | 314.88 | 717.97 | 321.75 | 0.00 | 0.00 | 0.00 |
| October | 575.24 | 338.33 | 236.91 | 526.42 | 456.49 | 0.00 | 0.00 | 0.00 |
| November | 512.41 | 321.59 | 190.82 | 411.40 | 610.39 | 0.00 | 0.00 | 0.00 |
| December | 545.40 | 357.62 | 187.77 | 363.04 | 915.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 645.56 | 344.73 | 300.83 | 624.66 | 485.75 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 512.41 | 143.56 | 187.77 | 363.04 | 150.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 894.42 | 604.12 | 402.33 | 771.05 | 934.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 38.60 | 16.16 | 22.44 | 11.13 | 194.98 | 0.00 | 0.00 | 0.00 |
| February | 62.89 | 28.72 | 34.16 | 34.36 | 155.81 | 0.00 | 0.00 | 0.00 |
| March | 82.76 | 42.35 | 40.41 | 58.02 | 121.29 | 0.00 | 0.00 | 0.00 |
| April | 105.72 | 53.54 | 52.17 | 93.08 | 74.26 | 0.00 | 0.00 | 0.00 |
| May | 129.89 | 61.96 | 67.93 | 138.86 | 41.90 | 0.00 | 0.00 | 0.00 |
| June | 125.34 | 54.20 | 71.14 | 143.95 | 29.30 | 0.00 | 0.00 | 0.00 |
| July | 133.81 | 62.21 | 71.60 | 162.22 | 25.20 | 0.00 | 0.00 | 0.00 |
| August | 110.12 | 50.04 | 60.08 | 128.38 | 29.50 | 0.00 | 0.00 | 0.00 |
| September | 86.06 | 38.67 | 47.40 | 82.41 | 53.78 | 0.00 | 0.00 | 0.00 |
| October | 54.37 | 21.83 | 32.54 | 37.51 | 80.73 | 0.00 | 0.00 | 0.00 |
| November | 33.02 | 11.13 | 21.89 | 12.90 | 118.12 | 0.00 | 0.00 | 0.00 |
| December | 29.44 | 10.30 | 19.13 | 5.85 | 189.21 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.78 | 37.65 | 45.13 | 75.98 | 92.58 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.44 | 10.30 | 19.13 | 5.85 | 25.20 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 133.81 | 62.21 | 71.60 | 162.22 | 194.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 115.79 | 48.49 | 67.31 | 35.80 | 553.53 | 0.00 | 0.00 | 0.00 |
| February | 188.66 | 86.17 | 102.49 | 107.75 | 437.05 | 0.00 | 0.00 | 0.00 |
| March | 248.27 | 127.04 | 121.23 | 180.47 | 332.97 | 0.00 | 0.00 | 0.00 |
| April | 317.15 | 160.63 | 156.51 | 291.30 | 193.39 | 0.00 | 0.00 | 0.00 |
| May | 389.67 | 185.87 | 203.80 | 426.96 | 110.48 | 0.00 | 0.00 | 0.00 |
| June | 376.02 | 162.59 | 213.43 | 440.15 | 78.27 | 0.00 | 0.00 | 0.00 |
| July | 401.44 | 186.63 | 214.81 | 492.98 | 70.48 | 0.00 | 0.00 | 0.00 |
| August | 330.36 | 150.11 | 180.25 | 391.39 | 81.70 | 0.00 | 0.00 | 0.00 |
| September | 258.19 | 116.00 | 142.19 | 254.91 | 145.75 | 0.00 | 0.00 | 0.00 |
| October | 163.10 | 65.48 | 97.62 | 118.00 | 217.75 | 0.00 | 0.00 | 0.00 |
| November | 99.06 | 33.40 | 65.66 | 41.45 | 324.97 | 0.00 | 0.00 | 0.00 |
| December | 88.31 | 30.91 | 57.40 | 19.10 | 534.87 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 248.33 | 112.94 | 135.39 | 234.13 | 256.07 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 88.31 | 30.91 | 57.40 | 19.10 | 70.48 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 401.44 | 186.63 | 214.81 | 492.98 | 553.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 6.47 | 0.00 | 6.47 | 0.00 | 92.85 | 0.00 | 0.00 | 0.00 |
| February | 9.84 | 0.00 | 9.84 | 0.21 | 74.42 | 0.00 | 0.00 | 0.00 |
| March | 12.06 | 0.00 | 12.06 | 0.56 | 57.21 | 0.00 | 0.00 | 0.00 |
| April | 15.88 | 0.13 | 15.75 | 5.05 | 31.55 | 0.00 | 0.00 | 0.00 |
| May | 22.72 | 1.36 | 21.36 | 17.35 | 15.98 | 0.00 | 0.00 | 0.00 |
| June | 25.25 | 3.09 | 22.16 | 25.90 | 11.23 | 0.00 | 0.00 | 0.00 |
| July | 23.78 | 2.25 | 21.53 | 26.84 | 9.98 | 0.00 | 0.00 | 0.00 |
| August | 18.01 | 0.37 | 17.64 | 17.45 | 11.78 | 0.00 | 0.00 | 0.00 |
| September | 14.16 | 0.00 | 14.16 | 7.37 | 22.89 | 0.00 | 0.00 | 0.00 |
| October | 10.03 | 0.00 | 10.03 | 1.35 | 35.26 | 0.00 | 0.00 | 0.00 |
| November | 6.60 | 0.00 | 6.60 | 0.27 | 53.61 | 0.00 | 0.00 | 0.00 |
| December | 5.56 | 0.00 | 5.56 | 0.00 | 88.09 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 14.22 | 0.60 | 13.62 | 8.59 | 41.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5.56 | 0.00 | 5.56 | 0.00 | 9.98 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 25.25 | 3.09 | 22.16 | 26.84 | 92.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 47.46 | 0.00 | 47.46 | 0.05 | 641.81 | 0.00 | 0.00 | 0.00 |
| February | 72.35 | 0.00 | 72.35 | 2.06 | 512.45 | 0.00 | 0.00 | 0.00 |
| March | 88.78 | 0.00 | 88.78 | 5.19 | 392.62 | 0.00 | 0.00 | 0.00 |
| April | 116.68 | 0.91 | 115.77 | 40.02 | 217.29 | 0.00 | 0.00 | 0.00 |
| May | 165.88 | 9.43 | 156.45 | 129.63 | 111.40 | 0.00 | 0.00 | 0.00 |
| June | 184.20 | 21.45 | 162.75 | 190.28 | 78.69 | 0.00 | 0.00 | 0.00 |
| July | 174.12 | 15.59 | 158.53 | 197.04 | 70.22 | 0.00 | 0.00 | 0.00 |
| August | 132.53 | 2.56 | 129.97 | 130.15 | 82.48 | 0.00 | 0.00 | 0.00 |
| September | 103.97 | 0.02 | 103.95 | 57.27 | 158.68 | 0.00 | 0.00 | 0.00 |
| October | 73.26 | 0.00 | 73.26 | 11.52 | 243.17 | 0.00 | 0.00 | 0.00 |
| November | 48.27 | 0.00 | 48.27 | 2.10 | 370.28 | 0.00 | 0.00 | 0.00 |
| December | 40.62 | 0.00 | 40.62 | 0.00 | 609.74 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 104.17 | 4.18 | 99.99 | 64.19 | 289.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 40.62 | 0.00 | 40.62 | 0.00 | 70.22 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 184.20 | 21.45 | 162.75 | 197.04 | 641.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 78.29 | 0.00 | 78.29 | 0.00 | 1201.39 | 0.00 | 0.00 | 0.00 |
| February | 119.12 | 0.00 | 119.12 | 1.84 | 968.13 | 0.00 | 0.00 | 0.00 |
| March | 146.22 | 0.00 | 146.22 | 5.08 | 755.00 | 0.00 | 0.00 | 0.00 |
| April | 191.09 | 0.77 | 190.31 | 53.47 | 435.23 | 0.00 | 0.00 | 0.00 |
| May | 266.75 | 10.87 | 255.88 | 197.49 | 226.03 | 0.00 | 0.00 | 0.00 |
| June | 285.17 | 23.14 | 262.04 | 285.30 | 156.14 | 0.00 | 0.00 | 0.00 |
| July | 272.63 | 16.93 | 255.70 | 316.26 | 126.57 | 0.00 | 0.00 | 0.00 |
| August | 214.76 | 2.63 | 212.13 | 216.87 | 150.30 | 0.00 | 0.00 | 0.00 |
| September | 171.55 | 0.03 | 171.52 | 85.49 | 301.29 | 0.00 | 0.00 | 0.00 |
| October | 121.53 | 0.00 | 121.53 | 12.72 | 476.88 | 0.00 | 0.00 | 0.00 |
| November | 79.80 | 0.00 | 79.80 | 2.93 | 711.71 | 0.00 | 0.00 | 0.00 |
| December | 67.29 | 0.00 | 67.29 | 0.00 | 1141.49 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 168.10 | 4.55 | 163.54 | 98.82 | 552.46 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 67.29 | 0.00 | 67.29 | 0.00 | 126.57 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 285.17 | 23.14 | 262.04 | 316.26 | 1201.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 82.55 | 0.00 | 82.55 | 0.02 | 1199.70 | 0.00 | 0.00 | 0.00 |
| February | 125.50 | 0.00 | 125.50 | 2.55 | 964.63 | 0.00 | 0.00 | 0.00 |
| March | 153.85 | 0.00 | 153.85 | 6.28 | 750.03 | 0.00 | 0.00 | 0.00 |
| April | 201.86 | 1.34 | 200.53 | 59.09 | 430.40 | 0.00 | 0.00 | 0.00 |
| May | 286.19 | 15.00 | 271.19 | 214.35 | 219.50 | 0.00 | 0.00 | 0.00 |
| June | 313.15 | 33.23 | 279.91 | 320.04 | 154.82 | 0.00 | 0.00 | 0.00 |
| July | 296.98 | 24.17 | 272.81 | 346.33 | 126.28 | 0.00 | 0.00 | 0.00 |
| August | 228.49 | 3.98 | 224.51 | 230.64 | 148.59 | 0.00 | 0.00 | 0.00 |
| September | 180.55 | 0.03 | 180.52 | 93.92 | 301.20 | 0.00 | 0.00 | 0.00 |
| October | 127.98 | 0.00 | 127.98 | 15.36 | 474.59 | 0.00 | 0.00 | 0.00 |
| November | 84.17 | 0.00 | 84.17 | 3.28 | 710.06 | 0.00 | 0.00 | 0.00 |
| December | 70.94 | 0.00 | 70.94 | 0.00 | 1140.32 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 179.62 | 6.51 | 173.11 | 108.39 | 549.95 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 70.94 | 0.00 | 70.94 | 0.00 | 126.28 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 313.15 | 33.23 | 279.91 | 346.33 | 1199.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 82.58 | 0.00 | 82.58 | 0.02 | 1199.66 | 0.00 | 0.00 | 0.00 |
| February | 125.54 | 0.00 | 125.54 | 2.55 | 964.59 | 0.00 | 0.00 | 0.00 |
| March | 153.90 | 0.00 | 153.90 | 6.29 | 749.98 | 0.00 | 0.00 | 0.00 |
| April | 202.58 | 1.66 | 200.92 | 59.16 | 429.29 | 0.00 | 0.00 | 0.00 |
| May | 288.13 | 16.20 | 271.93 | 215.68 | 218.02 | 0.00 | 0.00 | 0.00 |
| June | 315.24 | 34.61 | 280.63 | 321.59 | 153.49 | 0.00 | 0.00 | 0.00 |
| July | 299.02 | 25.51 | 273.50 | 348.13 | 125.23 | 0.00 | 0.00 | 0.00 |
| August | 229.67 | 4.60 | 225.07 | 231.59 | 147.77 | 0.00 | 0.00 | 0.00 |
| September | 180.67 | 0.04 | 180.64 | 93.98 | 301.09 | 0.00 | 0.00 | 0.00 |
| October | 128.01 | 0.00 | 128.01 | 15.37 | 474.57 | 0.00 | 0.00 | 0.00 |
| November | 84.19 | 0.00 | 84.19 | 3.28 | 710.04 | 0.00 | 0.00 | 0.00 |
| December | 70.96 | 0.00 | 70.96 | 0.00 | 1140.30 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 180.32 | 6.92 | 173.40 | 108.88 | 549.44 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 70.96 | 0.00 | 70.96 | 0.00 | 125.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 315.24 | 34.61 | 280.63 | 348.13 | 1199.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 115.79 | 48.49 | 67.31 | 34.42 | 557.70 | 0.00 | 0.00 | 0.00 |
| February | 188.66 | 86.17 | 102.49 | 103.75 | 443.70 | 0.00 | 0.00 | 0.00 |
| March | 248.27 | 127.04 | 121.23 | 174.81 | 340.65 | 0.00 | 0.00 | 0.00 |
| April | 317.15 | 160.63 | 156.51 | 280.88 | 203.87 | 0.00 | 0.00 | 0.00 |
| May | 389.67 | 185.87 | 203.80 | 420.42 | 115.51 | 0.00 | 0.00 | 0.00 |
| June | 376.02 | 162.59 | 213.43 | 436.78 | 80.21 | 0.00 | 0.00 | 0.00 |
| July | 401.44 | 186.63 | 214.81 | 485.74 | 74.81 | 0.00 | 0.00 | 0.00 |
| August | 330.36 | 150.11 | 180.25 | 381.40 | 89.68 | 0.00 | 0.00 | 0.00 |
| September | 258.19 | 116.00 | 142.19 | 244.65 | 157.25 | 0.00 | 0.00 | 0.00 |
| October | 163.10 | 65.48 | 97.62 | 111.04 | 231.57 | 0.00 | 0.00 | 0.00 |
| November | 99.06 | 33.40 | 65.66 | 38.52 | 333.21 | 0.00 | 0.00 | 0.00 |
| December | 88.31 | 30.91 | 57.40 | 18.22 | 538.34 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 248.33 | 112.94 | 135.39 | 228.32 | 263.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 88.31 | 30.91 | 57.40 | 18.22 | 74.81 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 401.44 | 186.63 | 214.81 | 485.74 | 557.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.53 | 36.26 | 15.27 | 38.08 | 74.05 | 0.00 | 0.00 | 0.00 |
| February | 68.10 | 47.02 | 21.09 | 59.14 | 59.74 | 0.00 | 0.00 | 0.00 |
| March | 59.94 | 39.11 | 20.83 | 53.83 | 48.38 | 0.00 | 0.00 | 0.00 |
| April | 53.62 | 30.39 | 23.23 | 53.85 | 31.37 | 0.00 | 0.00 | 0.00 |
| May | 44.08 | 16.09 | 27.98 | 48.38 | 18.25 | 0.00 | 0.00 | 0.00 |
| June | 38.98 | 11.26 | 27.72 | 46.68 | 12.57 | 0.00 | 0.00 | 0.00 |
| July | 42.87 | 14.63 | 28.24 | 54.34 | 11.44 | 0.00 | 0.00 | 0.00 |
| August | 46.57 | 20.63 | 25.94 | 56.28 | 13.79 | 0.00 | 0.00 | 0.00 |
| September | 50.75 | 28.13 | 22.61 | 54.17 | 23.99 | 0.00 | 0.00 | 0.00 |
| October | 43.64 | 26.44 | 17.20 | 40.36 | 33.65 | 0.00 | 0.00 | 0.00 |
| November | 38.28 | 24.57 | 13.72 | 31.33 | 46.21 | 0.00 | 0.00 | 0.00 |
| December | 38.49 | 25.28 | 13.21 | 25.89 | 72.51 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.93 | 26.52 | 21.42 | 46.76 | 37.07 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 38.28 | 11.26 | 13.21 | 25.89 | 11.44 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 68.10 | 47.02 | 28.24 | 59.14 | 74.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 351.29 | 249.12 | 102.16 | 257.97 | 513.34 | 0.00 | 0.00 | 0.00 |
| February | 467.64 | 326.32 | 141.32 | 405.49 | 413.45 | 0.00 | 0.00 | 0.00 |
| March | 409.72 | 271.42 | 138.30 | 367.67 | 335.45 | 0.00 | 0.00 | 0.00 |
| April | 364.15 | 210.90 | 153.24 | 366.04 | 217.64 | 0.00 | 0.00 | 0.00 |
| May | 295.77 | 111.68 | 184.08 | 324.46 | 126.92 | 0.00 | 0.00 | 0.00 |
| June | 259.48 | 78.13 | 181.35 | 310.54 | 87.27 | 0.00 | 0.00 | 0.00 |
| July | 286.32 | 101.53 | 184.79 | 363.49 | 78.94 | 0.00 | 0.00 | 0.00 |
| August | 313.94 | 143.16 | 170.77 | 379.98 | 95.26 | 0.00 | 0.00 | 0.00 |
| September | 345.17 | 195.25 | 149.92 | 368.25 | 165.80 | 0.00 | 0.00 | 0.00 |
| October | 298.39 | 183.51 | 114.88 | 275.70 | 232.71 | 0.00 | 0.00 | 0.00 |
| November | 261.45 | 169.54 | 91.91 | 213.29 | 319.67 | 0.00 | 0.00 | 0.00 |
| December | 257.54 | 170.26 | 87.28 | 170.55 | 504.14 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 324.94 | 183.29 | 141.65 | 316.25 | 256.92 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 257.54 | 78.13 | 87.28 | 170.55 | 78.94 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 467.64 | 326.32 | 184.79 | 405.49 | 513.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 614.69 | 436.10 | 178.59 | 456.70 | 981.63 | 0.00 | 0.00 | 0.00 |
| February | 852.21 | 597.41 | 254.80 | 737.58 | 780.50 | 0.00 | 0.00 | 0.00 |
| March | 748.06 | 498.73 | 249.33 | 666.65 | 640.97 | 0.00 | 0.00 | 0.00 |
| April | 663.01 | 387.54 | 275.47 | 659.03 | 430.17 | 0.00 | 0.00 | 0.00 |
| May | 535.74 | 205.22 | 330.52 | 583.27 | 248.35 | 0.00 | 0.00 | 0.00 |
| June | 468.38 | 143.57 | 324.81 | 559.73 | 171.17 | 0.00 | 0.00 | 0.00 |
| July | 517.56 | 186.56 | 331.00 | 667.89 | 143.11 | 0.00 | 0.00 | 0.00 |
| August | 569.77 | 263.07 | 306.71 | 698.42 | 173.23 | 0.00 | 0.00 | 0.00 |
| September | 628.89 | 358.77 | 270.12 | 670.32 | 316.14 | 0.00 | 0.00 | 0.00 |
| October | 544.62 | 337.11 | 207.51 | 498.99 | 452.92 | 0.00 | 0.00 | 0.00 |
| November | 466.03 | 303.04 | 162.99 | 379.52 | 622.39 | 0.00 | 0.00 | 0.00 |
| December | 443.39 | 293.26 | 150.13 | 301.10 | 969.72 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 585.86 | 332.43 | 253.43 | 571.98 | 493.04 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 443.39 | 143.57 | 150.13 | 301.10 | 143.11 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 852.21 | 597.41 | 331.00 | 737.58 | 981.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 614.06 | 435.64 | 178.42 | 456.68 | 982.45 | 0.00 | 0.00 | 0.00 |
| February | 848.53 | 595.01 | 253.53 | 736.99 | 785.23 | 0.00 | 0.00 | 0.00 |
| March | 747.73 | 498.62 | 249.11 | 666.61 | 641.47 | 0.00 | 0.00 | 0.00 |
| April | 662.95 | 387.54 | 275.41 | 658.97 | 430.18 | 0.00 | 0.00 | 0.00 |
| May | 535.66 | 205.22 | 330.43 | 583.18 | 248.34 | 0.00 | 0.00 | 0.00 |
| June | 468.29 | 143.57 | 324.72 | 559.63 | 171.17 | 0.00 | 0.00 | 0.00 |
| July | 517.47 | 186.56 | 330.91 | 667.78 | 143.10 | 0.00 | 0.00 | 0.00 |
| August | 569.70 | 263.07 | 306.63 | 698.34 | 173.22 | 0.00 | 0.00 | 0.00 |
| September | 628.77 | 358.75 | 270.02 | 670.22 | 316.19 | 0.00 | 0.00 | 0.00 |
| October | 543.87 | 336.76 | 207.11 | 498.90 | 453.98 | 0.00 | 0.00 | 0.00 |
| November | 464.61 | 302.15 | 162.45 | 379.42 | 624.23 | 0.00 | 0.00 | 0.00 |
| December | 443.19 | 293.14 | 150.05 | 301.08 | 969.96 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 585.26 | 332.08 | 253.18 | 571.87 | 493.78 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 443.19 | 143.57 | 150.05 | 301.08 | 143.10 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 848.53 | 595.01 | 330.91 | 736.99 | 982.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 570.54 | 403.44 | 167.10 | 410.67 | 988.90 | 0.00 | 0.00 | 0.00 |
| February | 789.48 | 553.34 | 236.14 | 675.96 | 798.03 | 0.00 | 0.00 | 0.00 |
| March | 706.06 | 470.93 | 235.14 | 621.79 | 650.86 | 0.00 | 0.00 | 0.00 |
| April | 636.03 | 373.15 | 262.88 | 627.05 | 432.05 | 0.00 | 0.00 | 0.00 |
| May | 515.87 | 200.23 | 315.64 | 559.17 | 247.84 | 0.00 | 0.00 | 0.00 |
| June | 450.42 | 140.27 | 310.15 | 538.08 | 170.64 | 0.00 | 0.00 | 0.00 |
| July | 498.73 | 182.46 | 316.27 | 644.60 | 141.95 | 0.00 | 0.00 | 0.00 |
| August | 548.66 | 255.88 | 292.78 | 671.48 | 172.41 | 0.00 | 0.00 | 0.00 |
| September | 598.99 | 342.48 | 256.52 | 633.33 | 317.43 | 0.00 | 0.00 | 0.00 |
| October | 509.48 | 314.87 | 194.61 | 461.65 | 459.78 | 0.00 | 0.00 | 0.00 |
| November | 431.82 | 279.80 | 152.02 | 345.17 | 628.87 | 0.00 | 0.00 | 0.00 |
| December | 413.57 | 272.69 | 140.88 | 272.01 | 975.51 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 554.17 | 314.19 | 239.98 | 537.31 | 497.45 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 413.57 | 140.27 | 140.88 | 272.01 | 141.95 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 789.48 | 553.34 | 316.27 | 675.96 | 988.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 38.60 | 16.16 | 22.44 | 11.14 | 194.88 | 0.00 | 0.00 | 0.00 |
| February | 62.89 | 28.72 | 34.16 | 34.37 | 155.79 | 0.00 | 0.00 | 0.00 |
| March | 82.76 | 42.35 | 40.41 | 58.03 | 121.28 | 0.00 | 0.00 | 0.00 |
| April | 105.72 | 53.54 | 52.17 | 93.13 | 74.21 | 0.00 | 0.00 | 0.00 |
| May | 129.89 | 61.96 | 67.93 | 138.95 | 41.82 | 0.00 | 0.00 | 0.00 |
| June | 125.34 | 54.20 | 71.14 | 144.04 | 29.23 | 0.00 | 0.00 | 0.00 |
| July | 133.81 | 62.21 | 71.60 | 162.45 | 25.02 | 0.00 | 0.00 | 0.00 |
| August | 110.12 | 50.04 | 60.08 | 128.58 | 29.30 | 0.00 | 0.00 | 0.00 |
| September | 86.06 | 38.67 | 47.40 | 82.49 | 53.66 | 0.00 | 0.00 | 0.00 |
| October | 54.37 | 21.83 | 32.54 | 37.55 | 80.65 | 0.00 | 0.00 | 0.00 |
| November | 33.02 | 11.13 | 21.89 | 12.92 | 118.03 | 0.00 | 0.00 | 0.00 |
| December | 29.44 | 10.30 | 19.13 | 5.87 | 189.08 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.78 | 37.65 | 45.13 | 76.05 | 92.49 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.44 | 10.30 | 19.13 | 5.87 | 25.02 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 133.81 | 62.21 | 71.60 | 162.45 | 194.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 115.79 | 48.49 | 67.31 | 35.80 | 553.51 | 0.00 | 0.00 | 0.00 |
| February | 188.66 | 86.17 | 102.49 | 107.75 | 437.05 | 0.00 | 0.00 | 0.00 |
| March | 248.27 | 127.04 | 121.23 | 180.46 | 332.98 | 0.00 | 0.00 | 0.00 |
| April | 317.15 | 160.63 | 156.51 | 291.29 | 193.38 | 0.00 | 0.00 | 0.00 |
| May | 389.67 | 185.87 | 203.80 | 426.94 | 110.45 | 0.00 | 0.00 | 0.00 |
| June | 376.02 | 162.59 | 213.43 | 440.11 | 78.25 | 0.00 | 0.00 | 0.00 |
| July | 401.44 | 186.63 | 214.81 | 493.05 | 70.38 | 0.00 | 0.00 | 0.00 |
| August | 330.36 | 150.11 | 180.25 | 391.46 | 81.58 | 0.00 | 0.00 | 0.00 |
| September | 258.19 | 116.00 | 142.19 | 254.95 | 145.67 | 0.00 | 0.00 | 0.00 |
| October | 163.10 | 65.48 | 97.62 | 118.01 | 217.70 | 0.00 | 0.00 | 0.00 |
| November | 99.06 | 33.40 | 65.66 | 41.46 | 324.92 | 0.00 | 0.00 | 0.00 |
| December | 88.31 | 30.91 | 57.40 | 19.10 | 534.84 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 248.33 | 112.94 | 135.39 | 234.14 | 256.02 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 88.31 | 30.91 | 57.40 | 19.10 | 70.38 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 401.44 | 186.63 | 214.81 | 493.05 | 553.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 6.60 | 0.00 | 6.60 | 0.00 | 92.78 | 0.00 | 0.00 | 0.00 |
| February | 10.04 | 0.00 | 10.04 | 0.24 | 74.29 | 0.00 | 0.00 | 0.00 |
| March | 12.31 | 0.00 | 12.31 | 0.61 | 57.04 | 0.00 | 0.00 | 0.00 |
| April | 16.20 | 0.13 | 16.07 | 5.27 | 31.47 | 0.00 | 0.00 | 0.00 |
| May | 23.15 | 1.37 | 21.78 | 17.80 | 15.97 | 0.00 | 0.00 | 0.00 |
| June | 25.75 | 3.12 | 22.63 | 26.47 | 11.25 | 0.00 | 0.00 | 0.00 |
| July | 24.27 | 2.27 | 22.00 | 27.42 | 10.00 | 0.00 | 0.00 | 0.00 |
| August | 18.39 | 0.37 | 18.02 | 17.89 | 11.79 | 0.00 | 0.00 | 0.00 |
| September | 14.44 | 0.00 | 14.44 | 7.65 | 22.87 | 0.00 | 0.00 | 0.00 |
| October | 10.21 | 0.00 | 10.21 | 1.44 | 35.20 | 0.00 | 0.00 | 0.00 |
| November | 6.72 | 0.00 | 6.72 | 0.28 | 53.55 | 0.00 | 0.00 | 0.00 |
| December | 5.66 | 0.00 | 5.66 | 0.00 | 88.06 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 14.50 | 0.61 | 13.89 | 8.81 | 41.89 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5.66 | 0.00 | 5.66 | 0.00 | 10.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 25.75 | 3.12 | 22.63 | 27.42 | 92.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 48.05 | 0.00 | 48.05 | 0.05 | 641.52 | 0.00 | 0.00 | 0.00 |
| February | 73.30 | 0.00 | 73.30 | 2.19 | 511.87 | 0.00 | 0.00 | 0.00 |
| March | 89.97 | 0.00 | 89.97 | 5.50 | 391.89 | 0.00 | 0.00 | 0.00 |
| April | 118.19 | 0.91 | 117.28 | 41.14 | 216.96 | 0.00 | 0.00 | 0.00 |
| May | 167.94 | 9.53 | 158.41 | 131.72 | 111.28 | 0.00 | 0.00 | 0.00 |
| June | 186.62 | 21.67 | 164.94 | 192.99 | 78.69 | 0.00 | 0.00 | 0.00 |
| July | 176.49 | 15.75 | 160.74 | 199.83 | 70.23 | 0.00 | 0.00 | 0.00 |
| August | 134.30 | 2.57 | 131.72 | 132.25 | 82.49 | 0.00 | 0.00 | 0.00 |
| September | 105.29 | 0.02 | 105.27 | 58.63 | 158.60 | 0.00 | 0.00 | 0.00 |
| October | 74.11 | 0.00 | 74.11 | 12.00 | 242.94 | 0.00 | 0.00 | 0.00 |
| November | 48.85 | 0.00 | 48.85 | 2.15 | 370.00 | 0.00 | 0.00 | 0.00 |
| December | 41.10 | 0.00 | 41.10 | 0.00 | 609.55 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 105.51 | 4.22 | 101.29 | 65.29 | 289.61 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41.10 | 0.00 | 41.10 | 0.00 | 70.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 186.62 | 21.67 | 164.94 | 199.83 | 641.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 79.21 | 0.00 | 79.21 | 0.01 | 1200.92 | 0.00 | 0.00 | 0.00 |
| February | 120.60 | 0.00 | 120.60 | 1.99 | 967.19 | 0.00 | 0.00 | 0.00 |
| March | 148.06 | 0.00 | 148.06 | 5.38 | 753.69 | 0.00 | 0.00 | 0.00 |
| April | 193.48 | 0.79 | 192.69 | 54.95 | 434.46 | 0.00 | 0.00 | 0.00 |
| May | 270.11 | 11.12 | 259.00 | 200.86 | 225.85 | 0.00 | 0.00 | 0.00 |
| June | 289.24 | 23.69 | 265.55 | 289.88 | 156.30 | 0.00 | 0.00 | 0.00 |
| July | 276.47 | 17.30 | 259.17 | 320.84 | 126.71 | 0.00 | 0.00 | 0.00 |
| August | 217.68 | 2.74 | 214.94 | 220.36 | 150.31 | 0.00 | 0.00 | 0.00 |
| September | 173.61 | 0.03 | 173.58 | 87.50 | 301.11 | 0.00 | 0.00 | 0.00 |
| October | 122.85 | 0.00 | 122.85 | 13.28 | 476.37 | 0.00 | 0.00 | 0.00 |
| November | 80.70 | 0.00 | 80.70 | 2.99 | 711.25 | 0.00 | 0.00 | 0.00 |
| December | 68.03 | 0.00 | 68.03 | 0.00 | 1141.19 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 170.25 | 4.66 | 165.59 | 100.54 | 552.06 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68.03 | 0.00 | 68.03 | 0.00 | 126.71 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 289.24 | 23.69 | 265.55 | 320.84 | 1200.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 83.86 | 0.00 | 83.86 | 0.03 | 1199.05 | 0.00 | 0.00 | 0.00 |
| February | 127.60 | 0.00 | 127.60 | 2.79 | 963.32 | 0.00 | 0.00 | 0.00 |
| March | 156.47 | 0.00 | 156.47 | 6.80 | 748.26 | 0.00 | 0.00 | 0.00 |
| April | 205.32 | 1.40 | 203.92 | 61.32 | 429.32 | 0.00 | 0.00 | 0.00 |
| May | 291.04 | 15.39 | 275.65 | 219.13 | 219.08 | 0.00 | 0.00 | 0.00 |
| June | 319.23 | 34.22 | 285.01 | 326.85 | 154.80 | 0.00 | 0.00 | 0.00 |
| July | 302.70 | 24.85 | 277.85 | 353.05 | 126.39 | 0.00 | 0.00 | 0.00 |
| August | 232.57 | 4.10 | 228.47 | 235.49 | 148.73 | 0.00 | 0.00 | 0.00 |
| September | 183.49 | 0.03 | 183.46 | 96.82 | 301.05 | 0.00 | 0.00 | 0.00 |
| October | 129.85 | 0.00 | 129.85 | 16.22 | 473.95 | 0.00 | 0.00 | 0.00 |
| November | 85.45 | 0.00 | 85.45 | 3.37 | 709.45 | 0.00 | 0.00 | 0.00 |
| December | 71.98 | 0.00 | 71.98 | 0.00 | 1139.92 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 182.74 | 6.70 | 176.04 | 110.91 | 549.39 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 71.98 | 0.00 | 71.98 | 0.00 | 126.39 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 319.23 | 34.22 | 285.01 | 353.05 | 1199.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 83.86 | 0.00 | 83.86 | 0.03 | 1199.03 | 0.00 | 0.00 | 0.00 |
| February | 127.60 | 0.00 | 127.60 | 2.79 | 963.30 | 0.00 | 0.00 | 0.00 |
| March | 156.47 | 0.00 | 156.47 | 6.80 | 748.25 | 0.00 | 0.00 | 0.00 |
| April | 205.86 | 1.66 | 204.20 | 61.33 | 428.39 | 0.00 | 0.00 | 0.00 |
| May | 293.14 | 16.76 | 276.38 | 220.64 | 217.52 | 0.00 | 0.00 | 0.00 |
| June | 321.76 | 35.96 | 285.80 | 328.66 | 153.13 | 0.00 | 0.00 | 0.00 |
| July | 305.06 | 26.49 | 278.57 | 355.18 | 125.17 | 0.00 | 0.00 | 0.00 |
| August | 233.64 | 4.71 | 228.93 | 236.22 | 147.83 | 0.00 | 0.00 | 0.00 |
| September | 183.55 | 0.04 | 183.51 | 96.82 | 300.94 | 0.00 | 0.00 | 0.00 |
| October | 129.85 | 0.00 | 129.85 | 16.22 | 473.95 | 0.00 | 0.00 | 0.00 |
| November | 85.44 | 0.00 | 85.44 | 3.37 | 709.44 | 0.00 | 0.00 | 0.00 |
| December | 71.98 | 0.00 | 71.98 | 0.00 | 1139.90 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 183.47 | 7.17 | 176.30 | 111.43 | 548.85 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 71.98 | 0.00 | 71.98 | 0.00 | 125.17 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 321.76 | 35.96 | 285.80 | 355.18 | 1199.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 115.79 | 48.49 | 67.31 | 34.36 | 557.86 | 0.00 | 0.00 | 0.00 |
| February | 188.66 | 86.17 | 102.49 | 103.73 | 443.75 | 0.00 | 0.00 | 0.00 |
| March | 248.27 | 127.04 | 121.23 | 174.78 | 340.72 | 0.00 | 0.00 | 0.00 |
| April | 317.15 | 160.63 | 156.51 | 280.61 | 204.34 | 0.00 | 0.00 | 0.00 |
| May | 389.67 | 185.87 | 203.80 | 419.95 | 116.05 | 0.00 | 0.00 | 0.00 |
| June | 376.02 | 162.59 | 213.43 | 436.28 | 80.67 | 0.00 | 0.00 | 0.00 |
| July | 401.44 | 186.63 | 214.81 | 484.98 | 75.47 | 0.00 | 0.00 | 0.00 |
| August | 330.36 | 150.11 | 180.25 | 380.78 | 90.42 | 0.00 | 0.00 | 0.00 |
| September | 258.19 | 116.00 | 142.19 | 244.19 | 158.10 | 0.00 | 0.00 | 0.00 |
| October | 163.10 | 65.48 | 97.62 | 110.73 | 232.66 | 0.00 | 0.00 | 0.00 |
| November | 99.06 | 33.40 | 65.66 | 38.44 | 333.69 | 0.00 | 0.00 | 0.00 |
| December | 88.31 | 30.91 | 57.40 | 18.16 | 538.55 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 248.33 | 112.94 | 135.39 | 228.02 | 263.65 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 88.31 | 30.91 | 57.40 | 18.16 | 75.47 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 401.44 | 186.63 | 214.81 | 484.98 | 557.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 52.31 | 36.85 | 15.47 | 38.69 | 73.72 | 0.00 | 0.00 | 0.00 |
| February | 68.30 | 47.09 | 21.21 | 59.26 | 59.65 | 0.00 | 0.00 | 0.00 |
| March | 60.06 | 39.11 | 20.95 | 53.94 | 48.40 | 0.00 | 0.00 | 0.00 |
| April | 53.77 | 30.39 | 23.38 | 53.96 | 31.44 | 0.00 | 0.00 | 0.00 |
| May | 44.26 | 16.09 | 28.17 | 48.52 | 18.34 | 0.00 | 0.00 | 0.00 |
| June | 39.18 | 11.26 | 27.92 | 46.84 | 12.66 | 0.00 | 0.00 | 0.00 |
| July | 43.08 | 14.63 | 28.45 | 54.47 | 11.56 | 0.00 | 0.00 | 0.00 |
| August | 46.74 | 20.63 | 26.12 | 56.38 | 13.92 | 0.00 | 0.00 | 0.00 |
| September | 50.88 | 28.13 | 22.74 | 54.24 | 24.13 | 0.00 | 0.00 | 0.00 |
| October | 43.75 | 26.46 | 17.29 | 40.40 | 33.80 | 0.00 | 0.00 | 0.00 |
| November | 38.61 | 24.76 | 13.85 | 31.57 | 46.16 | 0.00 | 0.00 | 0.00 |
| December | 39.43 | 25.98 | 13.45 | 26.65 | 72.13 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 48.23 | 26.65 | 21.58 | 46.98 | 37.07 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 38.61 | 11.26 | 13.45 | 26.65 | 11.56 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 68.30 | 47.09 | 28.45 | 59.26 | 73.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 359.65 | 255.22 | 104.43 | 265.42 | 510.71 | 0.00 | 0.00 | 0.00 |
| February | 469.55 | 326.81 | 142.75 | 406.87 | 412.98 | 0.00 | 0.00 | 0.00 |
| March | 411.21 | 271.42 | 139.79 | 369.03 | 335.60 | 0.00 | 0.00 | 0.00 |
| April | 366.04 | 210.90 | 155.14 | 367.60 | 218.18 | 0.00 | 0.00 | 0.00 |
| May | 298.17 | 111.68 | 186.48 | 326.60 | 127.64 | 0.00 | 0.00 | 0.00 |
| June | 262.09 | 78.13 | 183.96 | 312.97 | 87.89 | 0.00 | 0.00 | 0.00 |
| July | 288.97 | 101.53 | 187.45 | 365.74 | 79.88 | 0.00 | 0.00 | 0.00 |
| August | 316.13 | 143.16 | 172.97 | 381.84 | 96.25 | 0.00 | 0.00 | 0.00 |
| September | 346.83 | 195.25 | 151.59 | 369.59 | 166.86 | 0.00 | 0.00 | 0.00 |
| October | 299.67 | 183.66 | 116.01 | 276.47 | 233.83 | 0.00 | 0.00 | 0.00 |
| November | 264.80 | 171.51 | 93.29 | 216.20 | 319.38 | 0.00 | 0.00 | 0.00 |
| December | 268.85 | 178.44 | 90.41 | 180.62 | 500.38 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 328.39 | 184.72 | 143.67 | 319.23 | 256.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 262.09 | 78.13 | 90.41 | 180.62 | 79.88 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 469.55 | 326.81 | 187.45 | 406.87 | 510.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 634.84 | 451.11 | 183.72 | 471.76 | 972.06 | 0.00 | 0.00 | 0.00 |
| February | 857.52 | 599.63 | 257.89 | 740.97 | 777.95 | 0.00 | 0.00 | 0.00 |
| March | 750.68 | 498.77 | 251.91 | 668.99 | 641.16 | 0.00 | 0.00 | 0.00 |
| April | 666.34 | 387.57 | 278.77 | 661.45 | 431.57 | 0.00 | 0.00 | 0.00 |
| May | 539.92 | 205.24 | 334.69 | 586.57 | 250.15 | 0.00 | 0.00 | 0.00 |
| June | 472.93 | 143.58 | 329.35 | 563.36 | 172.78 | 0.00 | 0.00 | 0.00 |
| July | 522.18 | 186.57 | 335.61 | 670.97 | 145.45 | 0.00 | 0.00 | 0.00 |
| August | 573.61 | 263.08 | 310.53 | 700.87 | 175.89 | 0.00 | 0.00 | 0.00 |
| September | 631.81 | 358.79 | 273.01 | 672.11 | 319.10 | 0.00 | 0.00 | 0.00 |
| October | 546.94 | 337.42 | 209.52 | 499.74 | 456.50 | 0.00 | 0.00 | 0.00 |
| November | 474.87 | 308.55 | 166.31 | 385.75 | 620.08 | 0.00 | 0.00 | 0.00 |
| December | 465.81 | 309.60 | 156.21 | 318.44 | 959.72 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 592.99 | 335.75 | 257.24 | 577.17 | 492.38 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 465.81 | 143.58 | 156.21 | 318.44 | 145.45 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 857.52 | 599.63 | 335.61 | 740.97 | 972.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 633.21 | 449.90 | 183.31 | 471.72 | 974.15 | 0.00 | 0.00 | 0.00 |
| February | 853.76 | 597.18 | 256.58 | 740.39 | 782.78 | 0.00 | 0.00 | 0.00 |
| March | 750.35 | 498.62 | 251.73 | 668.95 | 641.62 | 0.00 | 0.00 | 0.00 |
| April | 666.29 | 387.54 | 278.75 | 661.41 | 431.54 | 0.00 | 0.00 | 0.00 |
| May | 539.89 | 205.22 | 334.66 | 586.54 | 250.13 | 0.00 | 0.00 | 0.00 |
| June | 472.89 | 143.57 | 329.33 | 563.33 | 172.77 | 0.00 | 0.00 | 0.00 |
| July | 522.15 | 186.56 | 335.59 | 670.92 | 145.44 | 0.00 | 0.00 | 0.00 |
| August | 573.57 | 263.07 | 310.51 | 700.83 | 175.88 | 0.00 | 0.00 | 0.00 |
| September | 631.74 | 358.76 | 272.97 | 672.05 | 319.10 | 0.00 | 0.00 | 0.00 |
| October | 546.23 | 337.05 | 209.17 | 499.66 | 457.48 | 0.00 | 0.00 | 0.00 |
| November | 472.86 | 307.27 | 165.59 | 385.51 | 622.54 | 0.00 | 0.00 | 0.00 |
| December | 465.08 | 309.11 | 155.97 | 318.42 | 960.59 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 592.23 | 335.26 | 256.97 | 577.06 | 493.32 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 465.08 | 143.57 | 155.97 | 318.42 | 145.44 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 853.76 | 597.18 | 335.59 | 740.39 | 974.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 584.63 | 413.97 | 170.66 | 420.58 | 981.72 | 0.00 | 0.00 | 0.00 |
| February | 792.65 | 554.54 | 238.10 | 678.12 | 796.77 | 0.00 | 0.00 | 0.00 |
| March | 707.87 | 470.90 | 236.97 | 623.33 | 650.89 | 0.00 | 0.00 | 0.00 |
| April | 638.35 | 373.13 | 265.22 | 628.50 | 433.37 | 0.00 | 0.00 | 0.00 |
| May | 518.82 | 200.21 | 318.60 | 561.15 | 249.58 | 0.00 | 0.00 | 0.00 |
| June | 453.64 | 140.26 | 313.38 | 540.23 | 172.20 | 0.00 | 0.00 | 0.00 |
| July | 501.99 | 182.45 | 319.54 | 646.14 | 144.19 | 0.00 | 0.00 | 0.00 |
| August | 551.35 | 255.86 | 295.49 | 672.63 | 174.98 | 0.00 | 0.00 | 0.00 |
| September | 601.04 | 342.47 | 258.58 | 634.16 | 320.26 | 0.00 | 0.00 | 0.00 |
| October | 510.99 | 314.97 | 196.02 | 461.65 | 463.31 | 0.00 | 0.00 | 0.00 |
| November | 437.67 | 283.47 | 154.20 | 349.15 | 627.89 | 0.00 | 0.00 | 0.00 |
| December | 430.54 | 285.07 | 145.48 | 284.32 | 967.13 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 559.20 | 316.53 | 242.67 | 540.58 | 497.28 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 430.54 | 140.26 | 145.48 | 284.32 | 144.19 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 792.65 | 554.54 | 319.54 | 678.12 | 981.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 38.60 | 16.16 | 22.44 | 11.13 | 194.98 | 0.00 | 0.00 | 0.00 |
| February | 62.89 | 28.72 | 34.16 | 34.35 | 155.88 | 0.00 | 0.00 | 0.00 |
| March | 82.76 | 42.35 | 40.41 | 57.98 | 121.43 | 0.00 | 0.00 | 0.00 |
| April | 105.72 | 53.54 | 52.17 | 92.80 | 74.83 | 0.00 | 0.00 | 0.00 |
| May | 129.89 | 61.96 | 67.93 | 138.41 | 42.47 | 0.00 | 0.00 | 0.00 |
| June | 125.34 | 54.20 | 71.14 | 143.46 | 29.80 | 0.00 | 0.00 | 0.00 |
| July | 133.81 | 62.21 | 71.60 | 161.57 | 25.76 | 0.00 | 0.00 | 0.00 |
| August | 110.12 | 50.04 | 60.08 | 127.83 | 30.13 | 0.00 | 0.00 | 0.00 |
| September | 86.06 | 38.67 | 47.40 | 81.95 | 54.64 | 0.00 | 0.00 | 0.00 |
| October | 54.37 | 21.83 | 32.54 | 37.22 | 81.83 | 0.00 | 0.00 | 0.00 |
| November | 33.02 | 11.13 | 21.89 | 12.87 | 118.51 | 0.00 | 0.00 | 0.00 |
| December | 29.44 | 10.30 | 19.13 | 5.86 | 189.20 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 82.78 | 37.65 | 45.13 | 75.71 | 93.04 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.44 | 10.30 | 19.13 | 5.86 | 25.76 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 133.81 | 62.21 | 71.60 | 161.57 | 194.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 8.04 | 0.00 | 8.04 | 0.03 | 92.14 | 0.00 | 0.00 | 0.00 |
| February | 12.36 | 0.00 | 12.36 | 0.58 | 72.93 | 0.00 | 0.00 | 0.00 |
| March | 15.20 | 0.00 | 15.20 | 1.48 | 55.37 | 0.00 | 0.00 | 0.00 |
| April | 19.93 | 0.16 | 19.77 | 8.07 | 30.91 | 0.00 | 0.00 | 0.00 |
| May | 28.03 | 1.51 | 26.52 | 22.82 | 16.23 | 0.00 | 0.00 | 0.00 |
| June | 31.28 | 3.44 | 27.84 | 32.37 | 11.46 | 0.00 | 0.00 | 0.00 |
| July | 29.88 | 2.56 | 27.31 | 33.38 | 10.43 | 0.00 | 0.00 | 0.00 |
| August | 22.69 | 0.39 | 22.30 | 22.63 | 12.39 | 0.00 | 0.00 | 0.00 |
| September | 17.68 | 0.00 | 17.68 | 10.78 | 23.18 | 0.00 | 0.00 | 0.00 |
| October | 12.28 | 0.00 | 12.28 | 2.64 | 35.07 | 0.00 | 0.00 | 0.00 |
| November | 8.13 | 0.00 | 8.13 | 0.41 | 53.07 | 0.00 | 0.00 | 0.00 |
| December | 6.82 | 0.00 | 6.82 | 0.00 | 87.69 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 17.72 | 0.67 | 17.04 | 11.34 | 41.61 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6.82 | 0.00 | 6.82 | 0.00 | 10.43 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 31.28 | 3.44 | 27.84 | 33.38 | 92.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 115.79 | 48.49 | 67.31 | 35.78 | 553.55 | 0.00 | 0.00 | 0.00 |
| February | 188.66 | 86.17 | 102.49 | 107.66 | 437.13 | 0.00 | 0.00 | 0.00 |
| March | 248.27 | 127.04 | 121.23 | 180.27 | 333.16 | 0.00 | 0.00 | 0.00 |
| April | 317.15 | 160.63 | 156.51 | 290.59 | 194.07 | 0.00 | 0.00 | 0.00 |
| May | 389.67 | 185.87 | 203.80 | 425.56 | 111.50 | 0.00 | 0.00 | 0.00 |
| June | 376.02 | 162.59 | 213.43 | 438.47 | 79.20 | 0.00 | 0.00 | 0.00 |
| July | 401.44 | 186.63 | 214.81 | 490.80 | 71.73 | 0.00 | 0.00 | 0.00 |
| August | 330.36 | 150.11 | 180.25 | 389.88 | 82.89 | 0.00 | 0.00 | 0.00 |
| September | 258.19 | 116.00 | 142.19 | 253.80 | 147.08 | 0.00 | 0.00 | 0.00 |
| October | 163.10 | 65.48 | 97.62 | 117.46 | 218.89 | 0.00 | 0.00 | 0.00 |
| November | 99.06 | 33.40 | 65.66 | 41.38 | 325.19 | 0.00 | 0.00 | 0.00 |
| December | 88.31 | 30.91 | 57.40 | 19.09 | 534.86 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 248.33 | 112.94 | 135.39 | 233.33 | 256.74 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 88.31 | 30.91 | 57.40 | 19.09 | 71.73 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 401.44 | 186.63 | 214.81 | 490.80 | 553.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.60 | 0.00 | 55.60 | 0.23 | 635.56 | 0.00 | 0.00 | 0.00 |
| February | 85.41 | 0.00 | 85.41 | 4.13 | 502.66 | 0.00 | 0.00 | 0.00 |
| March | 105.08 | 0.00 | 105.08 | 10.45 | 381.81 | 0.00 | 0.00 | 0.00 |
| April | 137.76 | 1.08 | 136.68 | 56.18 | 213.55 | 0.00 | 0.00 | 0.00 |
| May | 193.75 | 10.43 | 183.32 | 157.93 | 112.16 | 0.00 | 0.00 | 0.00 |
| June | 216.23 | 23.77 | 192.46 | 223.90 | 79.25 | 0.00 | 0.00 | 0.00 |
| July | 206.53 | 17.72 | 188.81 | 230.93 | 72.09 | 0.00 | 0.00 | 0.00 |
| August | 156.87 | 2.69 | 154.17 | 156.76 | 85.66 | 0.00 | 0.00 | 0.00 |
| September | 122.24 | 0.03 | 122.21 | 75.09 | 160.10 | 0.00 | 0.00 | 0.00 |
| October | 84.88 | 0.00 | 84.88 | 18.57 | 241.90 | 0.00 | 0.00 | 0.00 |
| November | 56.20 | 0.00 | 56.20 | 2.87 | 366.03 | 0.00 | 0.00 | 0.00 |
| December | 47.11 | 0.00 | 47.11 | 0.00 | 605.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 122.49 | 4.66 | 117.83 | 78.57 | 287.14 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 47.11 | 0.00 | 47.11 | 0.00 | 72.09 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 216.23 | 23.77 | 192.46 | 230.93 | 635.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 67.74 | 0.00 | 67.74 | 0.25 | 786.23 | 0.00 | 0.00 | 0.00 |
| February | 104.06 | 0.00 | 104.06 | 4.68 | 624.37 | 0.00 | 0.00 | 0.00 |
| March | 128.02 | 0.00 | 128.02 | 11.37 | 479.36 | 0.00 | 0.00 | 0.00 |
| April | 167.83 | 1.31 | 166.52 | 63.30 | 277.26 | 0.00 | 0.00 | 0.00 |
| May | 236.05 | 12.71 | 223.34 | 188.41 | 145.49 | 0.00 | 0.00 | 0.00 |
| June | 263.43 | 28.96 | 234.47 | 270.20 | 102.41 | 0.00 | 0.00 | 0.00 |
| July | 251.62 | 21.59 | 230.03 | 287.27 | 86.66 | 0.00 | 0.00 | 0.00 |
| August | 191.11 | 3.28 | 187.83 | 195.85 | 103.05 | 0.00 | 0.00 | 0.00 |
| September | 148.93 | 0.04 | 148.89 | 90.21 | 201.78 | 0.00 | 0.00 | 0.00 |
| October | 103.41 | 0.00 | 103.41 | 20.06 | 312.00 | 0.00 | 0.00 | 0.00 |
| November | 68.47 | 0.00 | 68.47 | 3.18 | 464.37 | 0.00 | 0.00 | 0.00 |
| December | 57.40 | 0.00 | 57.40 | 0.00 | 749.51 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 149.23 | 5.68 | 143.55 | 95.17 | 359.97 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 57.40 | 0.00 | 57.40 | 0.00 | 86.66 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 263.43 | 28.96 | 234.47 | 287.27 | 786.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 67.74 | 0.00 | 67.74 | 0.25 | 786.23 | 0.00 | 0.00 | 0.00 |
| February | 104.06 | 0.00 | 104.06 | 4.68 | 624.37 | 0.00 | 0.00 | 0.00 |
| March | 128.02 | 0.00 | 128.02 | 11.37 | 479.36 | 0.00 | 0.00 | 0.00 |
| April | 167.83 | 1.31 | 166.52 | 63.30 | 277.26 | 0.00 | 0.00 | 0.00 |
| May | 236.05 | 12.71 | 223.33 | 188.41 | 145.49 | 0.00 | 0.00 | 0.00 |
| June | 263.43 | 28.96 | 234.47 | 270.20 | 102.41 | 0.00 | 0.00 | 0.00 |
| July | 251.62 | 21.59 | 230.02 | 287.26 | 86.66 | 0.00 | 0.00 | 0.00 |
| August | 191.11 | 3.28 | 187.83 | 195.85 | 103.05 | 0.00 | 0.00 | 0.00 |
| September | 148.93 | 0.04 | 148.89 | 90.20 | 201.78 | 0.00 | 0.00 | 0.00 |
| October | 103.41 | 0.00 | 103.41 | 20.06 | 312.00 | 0.00 | 0.00 | 0.00 |
| November | 68.47 | 0.00 | 68.47 | 3.18 | 464.37 | 0.00 | 0.00 | 0.00 |
| December | 57.40 | 0.00 | 57.40 | 0.00 | 749.51 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 149.23 | 5.68 | 143.55 | 95.17 | 359.97 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 57.40 | 0.00 | 57.40 | 0.00 | 86.66 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 263.43 | 28.96 | 234.47 | 287.26 | 786.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 67.74 | 0.00 | 67.74 | 0.25 | 786.20 | 0.00 | 0.00 | 0.00 |
| February | 104.05 | 0.00 | 104.05 | 4.68 | 624.35 | 0.00 | 0.00 | 0.00 |
| March | 128.02 | 0.00 | 128.02 | 11.37 | 479.34 | 0.00 | 0.00 | 0.00 |
| April | 167.82 | 1.31 | 166.51 | 63.29 | 277.25 | 0.00 | 0.00 | 0.00 |
| May | 236.04 | 12.71 | 223.33 | 188.40 | 145.49 | 0.00 | 0.00 | 0.00 |
| June | 263.42 | 28.96 | 234.47 | 270.19 | 102.41 | 0.00 | 0.00 | 0.00 |
| July | 251.61 | 21.59 | 230.02 | 287.26 | 86.66 | 0.00 | 0.00 | 0.00 |
| August | 191.11 | 3.28 | 187.82 | 195.84 | 103.05 | 0.00 | 0.00 | 0.00 |
| September | 148.92 | 0.04 | 148.89 | 90.20 | 201.77 | 0.00 | 0.00 | 0.00 |
| October | 103.40 | 0.00 | 103.40 | 20.06 | 311.99 | 0.00 | 0.00 | 0.00 |
| November | 68.47 | 0.00 | 68.47 | 3.18 | 464.35 | 0.00 | 0.00 | 0.00 |
| December | 57.39 | 0.00 | 57.39 | 0.00 | 749.48 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 149.23 | 5.68 | 143.54 | 95.17 | 359.96 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 57.39 | 0.00 | 57.39 | 0.00 | 86.66 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 263.42 | 28.96 | 234.47 | 287.26 | 786.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 7.64 | 0.00 | 7.64 | 0.03 | 89.15 | 0.00 | 0.00 | 0.00 |
| February | 11.73 | 0.00 | 11.73 | 0.51 | 70.99 | 0.00 | 0.00 | 0.00 |
| March | 14.44 | 0.00 | 14.44 | 1.18 | 54.92 | 0.00 | 0.00 | 0.00 |
| April | 18.93 | 0.15 | 18.78 | 6.53 | 32.98 | 0.00 | 0.00 | 0.00 |
| May | 26.62 | 1.43 | 25.18 | 20.33 | 17.62 | 0.00 | 0.00 | 0.00 |
| June | 29.71 | 3.27 | 26.44 | 29.49 | 12.48 | 0.00 | 0.00 | 0.00 |
| July | 28.37 | 2.44 | 25.94 | 31.02 | 10.72 | 0.00 | 0.00 | 0.00 |
| August | 21.55 | 0.37 | 21.18 | 20.83 | 12.89 | 0.00 | 0.00 | 0.00 |
| September | 16.79 | 0.00 | 16.79 | 9.36 | 24.70 | 0.00 | 0.00 | 0.00 |
| October | 11.66 | 0.00 | 11.66 | 1.92 | 37.56 | 0.00 | 0.00 | 0.00 |
| November | 7.72 | 0.00 | 7.72 | 0.32 | 53.88 | 0.00 | 0.00 | 0.00 |
| December | 6.47 | 0.00 | 6.47 | 0.00 | 85.14 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 16.83 | 0.64 | 16.19 | 10.19 | 41.80 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6.47 | 0.00 | 6.47 | 0.00 | 10.72 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 29.71 | 3.27 | 26.44 | 31.02 | 89.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 96.87 | 0.00 | 96.87 | 0.34 | 1130.60 | 0.00 | 0.00 | 0.00 |
| February | 148.81 | 0.00 | 148.81 | 6.45 | 900.33 | 0.00 | 0.00 | 0.00 |
| March | 183.08 | 0.00 | 183.08 | 14.97 | 696.53 | 0.00 | 0.00 | 0.00 |
| April | 240.01 | 1.87 | 238.13 | 82.87 | 418.22 | 0.00 | 0.00 | 0.00 |
| May | 337.56 | 18.18 | 319.38 | 257.81 | 223.39 | 0.00 | 0.00 | 0.00 |
| June | 376.72 | 41.41 | 335.31 | 374.03 | 158.23 | 0.00 | 0.00 | 0.00 |
| July | 359.83 | 30.88 | 328.95 | 393.35 | 135.96 | 0.00 | 0.00 | 0.00 |
| August | 273.30 | 4.69 | 268.61 | 264.19 | 163.47 | 0.00 | 0.00 | 0.00 |
| September | 212.98 | 0.05 | 212.92 | 118.66 | 313.22 | 0.00 | 0.00 | 0.00 |
| October | 147.88 | 0.00 | 147.88 | 24.40 | 476.31 | 0.00 | 0.00 | 0.00 |
| November | 97.92 | 0.00 | 97.92 | 4.06 | 683.29 | 0.00 | 0.00 | 0.00 |
| December | 82.08 | 0.00 | 82.08 | 0.00 | 1079.69 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 213.41 | 8.13 | 205.28 | 129.25 | 530.09 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 82.08 | 0.00 | 82.08 | 0.00 | 135.96 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 376.72 | 41.41 | 335.31 | 393.35 | 1130.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 11.43 | 4.40 | 7.04 | 2.37 | 93.32 | 0.00 | 0.00 | 0.00 |
| February | 23.79 | 12.10 | 11.70 | 13.86 | 74.41 | 0.00 | 0.00 | 0.00 |
| March | 34.56 | 20.16 | 14.40 | 25.85 | 58.22 | 0.00 | 0.00 | 0.00 |
| April | 40.98 | 22.78 | 18.19 | 36.60 | 37.31 | 0.00 | 0.00 | 0.00 |
| May | 44.25 | 21.59 | 22.66 | 45.75 | 21.45 | 0.00 | 0.00 | 0.00 |
| June | 41.14 | 17.71 | 23.43 | 46.40 | 15.36 | 0.00 | 0.00 | 0.00 |
| July | 45.84 | 21.74 | 24.09 | 54.95 | 13.05 | 0.00 | 0.00 | 0.00 |
| August | 41.06 | 20.34 | 20.72 | 47.37 | 15.15 | 0.00 | 0.00 | 0.00 |
| September | 34.48 | 17.81 | 16.67 | 32.89 | 25.77 | 0.00 | 0.00 | 0.00 |
| October | 21.35 | 10.12 | 11.23 | 15.69 | 37.95 | 0.00 | 0.00 | 0.00 |
| November | 10.74 | 3.71 | 7.03 | 4.11 | 56.20 | 0.00 | 0.00 | 0.00 |
| December | 7.67 | 2.03 | 5.64 | 0.59 | 90.90 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 29.80 | 14.55 | 15.25 | 27.28 | 44.80 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 7.67 | 2.03 | 5.64 | 0.59 | 13.05 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 45.84 | 22.78 | 24.09 | 54.95 | 93.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 36.41 | 2.09 | 34.32 | 0.00 | 520.50 | 0.00 | 0.00 | 0.00 |
| February | 73.29 | 17.31 | 55.98 | 11.17 | 406.82 | 0.00 | 0.00 | 0.00 |
| March | 138.35 | 63.66 | 74.69 | 74.67 | 308.66 | 0.00 | 0.00 | 0.00 |
| April | 215.39 | 112.80 | 102.59 | 181.90 | 193.47 | 0.00 | 0.00 | 0.00 |
| May | 274.63 | 139.90 | 134.74 | 286.65 | 111.52 | 0.00 | 0.00 | 0.00 |
| June | 261.48 | 121.15 | 140.33 | 296.12 | 80.18 | 0.00 | 0.00 | 0.00 |
| July | 281.98 | 140.25 | 141.73 | 336.45 | 69.35 | 0.00 | 0.00 | 0.00 |
| August | 228.03 | 109.92 | 118.11 | 259.13 | 79.82 | 0.00 | 0.00 | 0.00 |
| September | 163.68 | 72.76 | 90.91 | 145.02 | 135.95 | 0.00 | 0.00 | 0.00 |
| October | 81.37 | 23.61 | 57.76 | 38.80 | 202.35 | 0.00 | 0.00 | 0.00 |
| November | 38.18 | 2.91 | 35.27 | 2.00 | 307.86 | 0.00 | 0.00 | 0.00 |
| December | 29.30 | 0.44 | 28.86 | 0.00 | 499.23 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 152.29 | 67.53 | 84.76 | 136.80 | 242.33 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.30 | 0.44 | 28.86 | 0.00 | 69.35 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 281.98 | 140.25 | 141.73 | 336.45 | 520.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 52.38 | 36.44 | 15.94 | 42.56 | 61.83 | 0.00 | 0.00 | 0.00 |
| February | 66.33 | 44.80 | 21.53 | 61.30 | 51.85 | 0.00 | 0.00 | 0.00 |
| March | 58.45 | 36.99 | 21.46 | 55.29 | 42.41 | 0.00 | 0.00 | 0.00 |
| April | 52.95 | 28.74 | 24.21 | 54.55 | 28.66 | 0.00 | 0.00 | 0.00 |
| May | 44.52 | 15.22 | 29.30 | 49.47 | 17.52 | 0.00 | 0.00 | 0.00 |
| June | 39.94 | 10.65 | 29.30 | 47.51 | 12.56 | 0.00 | 0.00 | 0.00 |
| July | 43.67 | 13.84 | 29.84 | 54.33 | 11.81 | 0.00 | 0.00 | 0.00 |
| August | 46.64 | 19.51 | 27.13 | 56.26 | 13.57 | 0.00 | 0.00 | 0.00 |
| September | 49.96 | 26.61 | 23.35 | 54.63 | 21.90 | 0.00 | 0.00 | 0.00 |
| October | 42.66 | 25.09 | 17.57 | 40.84 | 29.98 | 0.00 | 0.00 | 0.00 |
| November | 38.00 | 23.85 | 14.15 | 32.35 | 40.60 | 0.00 | 0.00 | 0.00 |
| December | 40.45 | 26.52 | 13.93 | 29.52 | 59.81 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.88 | 25.57 | 22.31 | 48.12 | 32.62 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 38.00 | 10.65 | 13.93 | 29.52 | 11.81 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 66.33 | 44.80 | 29.84 | 61.30 | 61.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 707.30 | 492.05 | 215.25 | 574.70 | 834.84 | 0.00 | 0.00 | 0.00 |
| February | 895.61 | 604.93 | 290.68 | 827.68 | 700.05 | 0.00 | 0.00 | 0.00 |
| March | 789.14 | 499.42 | 289.72 | 746.53 | 572.57 | 0.00 | 0.00 | 0.00 |
| April | 714.94 | 388.05 | 326.89 | 736.54 | 386.91 | 0.00 | 0.00 | 0.00 |
| May | 601.07 | 205.49 | 395.58 | 667.89 | 236.59 | 0.00 | 0.00 | 0.00 |
| June | 539.33 | 143.76 | 395.58 | 641.44 | 169.55 | 0.00 | 0.00 | 0.00 |
| July | 589.67 | 186.80 | 402.86 | 733.57 | 159.46 | 0.00 | 0.00 | 0.00 |
| August | 629.73 | 263.41 | 366.32 | 759.58 | 183.24 | 0.00 | 0.00 | 0.00 |
| September | 674.53 | 359.24 | 315.29 | 737.64 | 295.65 | 0.00 | 0.00 | 0.00 |
| October | 576.00 | 338.78 | 237.23 | 551.42 | 404.85 | 0.00 | 0.00 | 0.00 |
| November | 513.09 | 322.02 | 191.08 | 436.82 | 548.14 | 0.00 | 0.00 | 0.00 |
| December | 546.12 | 358.10 | 188.02 | 398.60 | 807.52 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 646.42 | 345.19 | 301.23 | 649.73 | 440.49 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 513.09 | 143.76 | 188.02 | 398.60 | 159.46 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 895.61 | 604.93 | 402.86 | 827.68 | 834.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BATH_ZN_1_FLR_1_WALL_5_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 61.85 | 12.83 | 49.02 | 1.17 | 628.70 | 0.00 | 0.00 | 0.00 |
| February | 125.68 | 45.49 | 80.19 | 45.53 | 489.33 | 0.00 | 0.00 | 0.00 |
| March | 208.54 | 105.20 | 103.34 | 135.34 | 372.42 | 0.00 | 0.00 | 0.00 |
| April | 294.14 | 156.17 | 137.98 | 255.11 | 244.53 | 0.00 | 0.00 | 0.00 |
| May | 361.47 | 182.24 | 179.24 | 372.16 | 150.12 | 0.00 | 0.00 | 0.00 |
| June | 342.45 | 156.12 | 186.33 | 376.88 | 112.57 | 0.00 | 0.00 | 0.00 |
| July | 371.34 | 182.62 | 188.72 | 434.15 | 99.07 | 0.00 | 0.00 | 0.00 |
| August | 307.17 | 148.62 | 158.55 | 344.89 | 111.84 | 0.00 | 0.00 | 0.00 |
| September | 231.17 | 107.38 | 123.79 | 207.11 | 184.53 | 0.00 | 0.00 | 0.00 |
| October | 126.62 | 45.82 | 80.80 | 73.02 | 265.36 | 0.00 | 0.00 | 0.00 |
| November | 61.84 | 11.87 | 49.98 | 10.76 | 374.24 | 0.00 | 0.00 | 0.00 |
| December | 46.11 | 5.48 | 40.63 | 0.00 | 608.78 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 212.01 | 96.95 | 115.06 | 188.91 | 302.75 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 46.11 | 5.48 | 40.63 | 0.00 | 99.07 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 371.34 | 182.62 | 188.72 | 434.15 | 628.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 267.33 | 111.59 | 155.74 | 66.87 | 1275.43 | 0.00 | 0.00 | 0.00 |
| February | 420.08 | 179.19 | 240.89 | 200.61 | 1003.15 | 0.00 | 0.00 | 0.00 |
| March | 572.38 | 287.12 | 285.27 | 380.94 | 788.71 | 0.00 | 0.00 | 0.00 |
| April | 793.49 | 427.99 | 365.50 | 694.69 | 493.63 | 0.00 | 0.00 | 0.00 |
| May | 858.79 | 377.53 | 481.25 | 866.91 | 290.12 | 0.00 | 0.00 | 0.00 |
| June | 972.21 | 465.06 | 507.15 | 1101.20 | 212.26 | 0.00 | 0.00 | 0.00 |
| July | 952.40 | 447.19 | 505.22 | 1114.08 | 193.32 | 0.00 | 0.00 | 0.00 |
| August | 734.31 | 320.94 | 413.36 | 809.08 | 233.10 | 0.00 | 0.00 | 0.00 |
| September | 588.06 | 263.21 | 324.85 | 536.31 | 380.33 | 0.00 | 0.00 | 0.00 |
| October | 356.08 | 135.02 | 221.05 | 218.76 | 553.37 | 0.00 | 0.00 | 0.00 |
| November | 226.68 | 75.79 | 150.90 | 85.15 | 776.61 | 0.00 | 0.00 | 0.00 |
| December | 206.85 | 76.45 | 130.39 | 41.50 | 1237.28 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 579.64 | 264.14 | 315.50 | 511.18 | 618.31 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 206.85 | 75.79 | 130.39 | 41.50 | 193.32 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 972.21 | 465.06 | 507.15 | 1114.08 | 1275.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 52.01 | 36.19 | 15.83 | 38.09 | 68.30 | 0.00 | 0.00 | 0.00 |
| February | 65.86 | 44.49 | 21.38 | 57.24 | 56.36 | 0.00 | 0.00 | 0.00 |
| March | 58.03 | 36.73 | 21.31 | 52.15 | 46.65 | 0.00 | 0.00 | 0.00 |
| April | 52.58 | 28.54 | 24.04 | 51.78 | 32.14 | 0.00 | 0.00 | 0.00 |
| May | 44.20 | 15.11 | 29.09 | 46.92 | 19.69 | 0.00 | 0.00 | 0.00 |
| June | 39.66 | 10.57 | 29.09 | 45.29 | 14.19 | 0.00 | 0.00 | 0.00 |
| July | 43.36 | 13.74 | 29.63 | 52.54 | 12.86 | 0.00 | 0.00 | 0.00 |
| August | 46.31 | 19.37 | 26.94 | 54.30 | 15.16 | 0.00 | 0.00 | 0.00 |
| September | 49.60 | 26.42 | 23.19 | 52.41 | 24.34 | 0.00 | 0.00 | 0.00 |
| October | 42.36 | 24.91 | 17.45 | 38.94 | 33.23 | 0.00 | 0.00 | 0.00 |
| November | 37.73 | 23.68 | 14.05 | 30.71 | 43.99 | 0.00 | 0.00 | 0.00 |
| December | 40.16 | 26.33 | 13.83 | 26.96 | 66.80 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 47.54 | 25.39 | 22.15 | 45.52 | 36.06 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 37.73 | 10.57 | 13.83 | 26.96 | 12.86 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 65.86 | 44.49 | 29.63 | 57.24 | 68.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 787.62 | 547.93 | 239.69 | 576.80 | 1034.26 | 0.00 | 0.00 | 0.00 |
| February | 997.32 | 673.62 | 323.69 | 866.77 | 853.36 | 0.00 | 0.00 | 0.00 |
| March | 878.76 | 556.13 | 322.63 | 789.69 | 706.37 | 0.00 | 0.00 | 0.00 |
| April | 796.12 | 432.11 | 364.01 | 784.03 | 486.52 | 0.00 | 0.00 | 0.00 |
| May | 669.33 | 228.83 | 440.50 | 710.42 | 297.65 | 0.00 | 0.00 | 0.00 |
| June | 600.58 | 160.08 | 440.50 | 685.86 | 214.21 | 0.00 | 0.00 | 0.00 |
| July | 656.63 | 208.02 | 448.61 | 795.73 | 194.18 | 0.00 | 0.00 | 0.00 |
| August | 701.24 | 293.32 | 407.92 | 822.28 | 229.42 | 0.00 | 0.00 | 0.00 |
| September | 751.13 | 400.03 | 351.10 | 793.66 | 368.55 | 0.00 | 0.00 | 0.00 |
| October | 641.41 | 377.25 | 264.17 | 589.72 | 503.19 | 0.00 | 0.00 | 0.00 |
| November | 571.36 | 358.59 | 212.77 | 464.98 | 666.06 | 0.00 | 0.00 | 0.00 |
| December | 608.14 | 398.76 | 209.37 | 408.22 | 1011.47 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 719.83 | 384.39 | 335.44 | 689.33 | 545.83 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 571.36 | 160.08 | 209.37 | 408.22 | 194.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 997.32 | 673.62 | 448.61 | 866.77 | 1034.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.41 | 13.61 | 25.80 | 7.72 | 132.77 | 0.00 | 0.00 | 0.00 |
| February | 70.33 | 32.38 | 37.95 | 39.21 | 107.34 | 0.00 | 0.00 | 0.00 |
| March | 100.55 | 56.56 | 43.99 | 72.75 | 84.84 | 0.00 | 0.00 | 0.00 |
| April | 148.47 | 93.81 | 54.66 | 132.49 | 59.94 | 0.00 | 0.00 | 0.00 |
| May | 181.95 | 102.56 | 79.39 | 182.69 | 38.43 | 0.00 | 0.00 | 0.00 |
| June | 191.27 | 110.26 | 81.02 | 200.95 | 28.58 | 0.00 | 0.00 | 0.00 |
| July | 196.41 | 117.47 | 78.93 | 210.64 | 27.27 | 0.00 | 0.00 | 0.00 |
| August | 154.92 | 87.08 | 67.84 | 162.21 | 29.54 | 0.00 | 0.00 | 0.00 |
| September | 112.39 | 57.85 | 54.54 | 105.68 | 44.12 | 0.00 | 0.00 | 0.00 |
| October | 66.66 | 26.51 | 40.15 | 48.78 | 62.53 | 0.00 | 0.00 | 0.00 |
| November | 38.40 | 11.49 | 26.91 | 15.88 | 84.93 | 0.00 | 0.00 | 0.00 |
| December | 30.77 | 7.81 | 22.96 | 3.05 | 128.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 111.17 | 59.91 | 51.25 | 98.82 | 68.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.77 | 7.81 | 22.96 | 3.05 | 27.27 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.41 | 117.47 | 81.02 | 210.64 | 132.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.41 | 13.61 | 25.80 | 7.72 | 132.77 | 0.00 | 0.00 | 0.00 |
| February | 70.33 | 32.38 | 37.95 | 39.21 | 107.34 | 0.00 | 0.00 | 0.00 |
| March | 100.55 | 56.56 | 43.99 | 72.75 | 84.84 | 0.00 | 0.00 | 0.00 |
| April | 148.47 | 93.81 | 54.66 | 132.49 | 59.94 | 0.00 | 0.00 | 0.00 |
| May | 181.95 | 102.56 | 79.39 | 182.69 | 38.43 | 0.00 | 0.00 | 0.00 |
| June | 191.27 | 110.26 | 81.02 | 200.95 | 28.58 | 0.00 | 0.00 | 0.00 |
| July | 196.41 | 117.47 | 78.93 | 210.64 | 27.27 | 0.00 | 0.00 | 0.00 |
| August | 154.92 | 87.08 | 67.84 | 162.21 | 29.54 | 0.00 | 0.00 | 0.00 |
| September | 112.39 | 57.85 | 54.54 | 105.68 | 44.12 | 0.00 | 0.00 | 0.00 |
| October | 66.66 | 26.51 | 40.15 | 48.78 | 62.53 | 0.00 | 0.00 | 0.00 |
| November | 38.40 | 11.49 | 26.91 | 15.88 | 84.93 | 0.00 | 0.00 | 0.00 |
| December | 30.77 | 7.81 | 22.96 | 3.05 | 128.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 111.17 | 59.91 | 51.25 | 98.82 | 68.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.77 | 7.81 | 22.96 | 3.05 | 27.27 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.41 | 117.47 | 81.02 | 210.64 | 132.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.41 | 13.61 | 25.80 | 7.72 | 132.77 | 0.00 | 0.00 | 0.00 |
| February | 70.33 | 32.38 | 37.95 | 39.21 | 107.34 | 0.00 | 0.00 | 0.00 |
| March | 100.55 | 56.56 | 43.99 | 72.75 | 84.84 | 0.00 | 0.00 | 0.00 |
| April | 148.47 | 93.81 | 54.66 | 132.49 | 59.94 | 0.00 | 0.00 | 0.00 |
| May | 181.95 | 102.56 | 79.39 | 182.69 | 38.43 | 0.00 | 0.00 | 0.00 |
| June | 191.27 | 110.26 | 81.02 | 200.95 | 28.58 | 0.00 | 0.00 | 0.00 |
| July | 196.41 | 117.47 | 78.93 | 210.64 | 27.27 | 0.00 | 0.00 | 0.00 |
| August | 154.92 | 87.08 | 67.84 | 162.21 | 29.54 | 0.00 | 0.00 | 0.00 |
| September | 112.39 | 57.85 | 54.54 | 105.68 | 44.12 | 0.00 | 0.00 | 0.00 |
| October | 66.66 | 26.51 | 40.15 | 48.78 | 62.53 | 0.00 | 0.00 | 0.00 |
| November | 38.40 | 11.49 | 26.91 | 15.88 | 84.93 | 0.00 | 0.00 | 0.00 |
| December | 30.77 | 7.81 | 22.96 | 3.05 | 128.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 111.17 | 59.91 | 51.25 | 98.82 | 68.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.77 | 7.81 | 22.96 | 3.05 | 27.27 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.41 | 117.47 | 81.02 | 210.64 | 132.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.41 | 13.61 | 25.80 | 7.72 | 132.77 | 0.00 | 0.00 | 0.00 |
| February | 70.33 | 32.38 | 37.95 | 39.21 | 107.34 | 0.00 | 0.00 | 0.00 |
| March | 100.55 | 56.56 | 43.99 | 72.75 | 84.84 | 0.00 | 0.00 | 0.00 |
| April | 148.47 | 93.81 | 54.66 | 132.49 | 59.94 | 0.00 | 0.00 | 0.00 |
| May | 181.95 | 102.56 | 79.39 | 182.69 | 38.43 | 0.00 | 0.00 | 0.00 |
| June | 191.27 | 110.26 | 81.02 | 200.95 | 28.58 | 0.00 | 0.00 | 0.00 |
| July | 196.41 | 117.47 | 78.93 | 210.64 | 27.27 | 0.00 | 0.00 | 0.00 |
| August | 154.92 | 87.08 | 67.84 | 162.21 | 29.54 | 0.00 | 0.00 | 0.00 |
| September | 112.39 | 57.85 | 54.54 | 105.68 | 44.12 | 0.00 | 0.00 | 0.00 |
| October | 66.66 | 26.51 | 40.15 | 48.78 | 62.53 | 0.00 | 0.00 | 0.00 |
| November | 38.40 | 11.49 | 26.91 | 15.88 | 84.93 | 0.00 | 0.00 | 0.00 |
| December | 30.77 | 7.81 | 22.96 | 3.05 | 128.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 111.17 | 59.91 | 51.25 | 98.82 | 68.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.77 | 7.81 | 22.96 | 3.05 | 27.27 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.41 | 117.47 | 81.02 | 210.64 | 132.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.41 | 13.61 | 25.80 | 7.72 | 132.77 | 0.00 | 0.00 | 0.00 |
| February | 70.33 | 32.38 | 37.95 | 39.21 | 107.34 | 0.00 | 0.00 | 0.00 |
| March | 100.55 | 56.56 | 43.99 | 72.75 | 84.84 | 0.00 | 0.00 | 0.00 |
| April | 148.47 | 93.81 | 54.66 | 132.49 | 59.94 | 0.00 | 0.00 | 0.00 |
| May | 181.95 | 102.56 | 79.39 | 182.69 | 38.43 | 0.00 | 0.00 | 0.00 |
| June | 191.27 | 110.26 | 81.02 | 200.95 | 28.58 | 0.00 | 0.00 | 0.00 |
| July | 196.41 | 117.47 | 78.93 | 210.64 | 27.27 | 0.00 | 0.00 | 0.00 |
| August | 154.92 | 87.08 | 67.84 | 162.21 | 29.54 | 0.00 | 0.00 | 0.00 |
| September | 112.39 | 57.85 | 54.54 | 105.68 | 44.12 | 0.00 | 0.00 | 0.00 |
| October | 66.66 | 26.51 | 40.15 | 48.78 | 62.53 | 0.00 | 0.00 | 0.00 |
| November | 38.40 | 11.49 | 26.91 | 15.88 | 84.93 | 0.00 | 0.00 | 0.00 |
| December | 30.77 | 7.81 | 22.96 | 3.05 | 128.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 111.17 | 59.91 | 51.25 | 98.82 | 68.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.77 | 7.81 | 22.96 | 3.05 | 27.27 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.41 | 117.47 | 81.02 | 210.64 | 132.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.41 | 13.61 | 25.80 | 7.72 | 132.77 | 0.00 | 0.00 | 0.00 |
| February | 70.33 | 32.38 | 37.95 | 39.21 | 107.34 | 0.00 | 0.00 | 0.00 |
| March | 100.55 | 56.56 | 43.99 | 72.75 | 84.84 | 0.00 | 0.00 | 0.00 |
| April | 148.47 | 93.81 | 54.66 | 132.49 | 59.94 | 0.00 | 0.00 | 0.00 |
| May | 181.95 | 102.56 | 79.39 | 182.69 | 38.43 | 0.00 | 0.00 | 0.00 |
| June | 191.27 | 110.26 | 81.02 | 200.95 | 28.58 | 0.00 | 0.00 | 0.00 |
| July | 196.41 | 117.47 | 78.93 | 210.64 | 27.27 | 0.00 | 0.00 | 0.00 |
| August | 154.92 | 87.08 | 67.84 | 162.21 | 29.54 | 0.00 | 0.00 | 0.00 |
| September | 112.39 | 57.85 | 54.54 | 105.68 | 44.12 | 0.00 | 0.00 | 0.00 |
| October | 66.66 | 26.51 | 40.15 | 48.78 | 62.53 | 0.00 | 0.00 | 0.00 |
| November | 38.40 | 11.49 | 26.91 | 15.88 | 84.93 | 0.00 | 0.00 | 0.00 |
| December | 30.77 | 7.81 | 22.96 | 3.05 | 128.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 111.17 | 59.91 | 51.25 | 98.82 | 68.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.77 | 7.81 | 22.96 | 3.05 | 27.27 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.41 | 117.47 | 81.02 | 210.64 | 132.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.41 | 13.61 | 25.80 | 7.72 | 132.77 | 0.00 | 0.00 | 0.00 |
| February | 70.33 | 32.38 | 37.95 | 39.21 | 107.34 | 0.00 | 0.00 | 0.00 |
| March | 100.55 | 56.56 | 43.99 | 72.75 | 84.84 | 0.00 | 0.00 | 0.00 |
| April | 148.47 | 93.81 | 54.66 | 132.49 | 59.94 | 0.00 | 0.00 | 0.00 |
| May | 181.95 | 102.56 | 79.39 | 182.69 | 38.43 | 0.00 | 0.00 | 0.00 |
| June | 191.27 | 110.26 | 81.02 | 200.95 | 28.58 | 0.00 | 0.00 | 0.00 |
| July | 196.41 | 117.47 | 78.93 | 210.64 | 27.27 | 0.00 | 0.00 | 0.00 |
| August | 154.92 | 87.08 | 67.84 | 162.21 | 29.54 | 0.00 | 0.00 | 0.00 |
| September | 112.39 | 57.85 | 54.54 | 105.68 | 44.12 | 0.00 | 0.00 | 0.00 |
| October | 66.66 | 26.51 | 40.15 | 48.78 | 62.53 | 0.00 | 0.00 | 0.00 |
| November | 38.40 | 11.49 | 26.91 | 15.88 | 84.93 | 0.00 | 0.00 | 0.00 |
| December | 30.77 | 7.81 | 22.96 | 3.05 | 128.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 111.17 | 59.91 | 51.25 | 98.82 | 68.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.77 | 7.81 | 22.96 | 3.05 | 27.27 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.41 | 117.47 | 81.02 | 210.64 | 132.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.41 | 13.61 | 25.80 | 7.72 | 132.77 | 0.00 | 0.00 | 0.00 |
| February | 70.33 | 32.38 | 37.95 | 39.21 | 107.34 | 0.00 | 0.00 | 0.00 |
| March | 100.55 | 56.56 | 43.99 | 72.75 | 84.84 | 0.00 | 0.00 | 0.00 |
| April | 148.47 | 93.81 | 54.66 | 132.49 | 59.94 | 0.00 | 0.00 | 0.00 |
| May | 181.95 | 102.56 | 79.39 | 182.69 | 38.43 | 0.00 | 0.00 | 0.00 |
| June | 191.27 | 110.26 | 81.02 | 200.95 | 28.58 | 0.00 | 0.00 | 0.00 |
| July | 196.41 | 117.47 | 78.93 | 210.64 | 27.27 | 0.00 | 0.00 | 0.00 |
| August | 154.92 | 87.08 | 67.84 | 162.21 | 29.54 | 0.00 | 0.00 | 0.00 |
| September | 112.39 | 57.85 | 54.54 | 105.68 | 44.12 | 0.00 | 0.00 | 0.00 |
| October | 66.66 | 26.51 | 40.15 | 48.78 | 62.53 | 0.00 | 0.00 | 0.00 |
| November | 38.40 | 11.49 | 26.91 | 15.88 | 84.93 | 0.00 | 0.00 | 0.00 |
| December | 30.77 | 7.81 | 22.96 | 3.05 | 128.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 111.17 | 59.91 | 51.25 | 98.82 | 68.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.77 | 7.81 | 22.96 | 3.05 | 27.27 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.41 | 117.47 | 81.02 | 210.64 | 132.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 39.41 | 13.61 | 25.80 | 7.72 | 132.77 | 0.00 | 0.00 | 0.00 |
| February | 70.33 | 32.38 | 37.95 | 39.21 | 107.34 | 0.00 | 0.00 | 0.00 |
| March | 100.55 | 56.56 | 43.99 | 72.75 | 84.84 | 0.00 | 0.00 | 0.00 |
| April | 148.47 | 93.81 | 54.66 | 132.49 | 59.94 | 0.00 | 0.00 | 0.00 |
| May | 181.95 | 102.56 | 79.39 | 182.69 | 38.43 | 0.00 | 0.00 | 0.00 |
| June | 191.27 | 110.26 | 81.02 | 200.95 | 28.58 | 0.00 | 0.00 | 0.00 |
| July | 196.41 | 117.47 | 78.93 | 210.64 | 27.27 | 0.00 | 0.00 | 0.00 |
| August | 154.92 | 87.08 | 67.84 | 162.21 | 29.54 | 0.00 | 0.00 | 0.00 |
| September | 112.39 | 57.85 | 54.54 | 105.68 | 44.12 | 0.00 | 0.00 | 0.00 |
| October | 66.66 | 26.51 | 40.15 | 48.78 | 62.53 | 0.00 | 0.00 | 0.00 |
| November | 38.40 | 11.49 | 26.91 | 15.88 | 84.93 | 0.00 | 0.00 | 0.00 |
| December | 30.77 | 7.81 | 22.96 | 3.05 | 128.83 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 111.17 | 59.91 | 51.25 | 98.82 | 68.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.77 | 7.81 | 22.96 | 3.05 | 27.27 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 196.41 | 117.47 | 81.02 | 210.64 | 132.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 16.86 | 7.04 | 9.82 | 4.14 | 81.90 | 0.00 | 0.00 | 0.00 |
| February | 26.49 | 11.30 | 15.19 | 12.37 | 65.07 | 0.00 | 0.00 | 0.00 |
| March | 36.09 | 18.10 | 17.99 | 23.43 | 52.67 | 0.00 | 0.00 | 0.00 |
| April | 50.04 | 26.99 | 23.05 | 42.17 | 34.80 | 0.00 | 0.00 | 0.00 |
| May | 54.15 | 23.81 | 30.35 | 53.07 | 20.13 | 0.00 | 0.00 | 0.00 |
| June | 61.31 | 29.33 | 31.98 | 68.28 | 14.48 | 0.00 | 0.00 | 0.00 |
| July | 60.06 | 28.20 | 31.86 | 69.39 | 13.04 | 0.00 | 0.00 | 0.00 |
| August | 46.30 | 20.24 | 26.07 | 50.57 | 15.33 | 0.00 | 0.00 | 0.00 |
| September | 37.08 | 16.60 | 20.48 | 33.53 | 24.68 | 0.00 | 0.00 | 0.00 |
| October | 22.45 | 8.51 | 13.94 | 13.54 | 36.67 | 0.00 | 0.00 | 0.00 |
| November | 14.29 | 4.78 | 9.52 | 5.19 | 51.50 | 0.00 | 0.00 | 0.00 |
| December | 13.04 | 4.82 | 8.22 | 2.57 | 79.71 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 36.55 | 16.66 | 19.89 | 31.62 | 40.74 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 13.04 | 4.78 | 8.22 | 2.57 | 13.04 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 61.31 | 29.33 | 31.98 | 69.39 | 81.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 199.52 | 83.28 | 116.24 | 49.00 | 969.25 | 0.00 | 0.00 | 0.00 |
| February | 313.53 | 133.73 | 179.79 | 146.44 | 769.75 | 0.00 | 0.00 | 0.00 |
| March | 427.20 | 214.28 | 212.92 | 277.51 | 622.43 | 0.00 | 0.00 | 0.00 |
| April | 592.22 | 319.42 | 272.80 | 500.26 | 411.34 | 0.00 | 0.00 | 0.00 |
| May | 640.96 | 281.77 | 359.20 | 630.04 | 238.22 | 0.00 | 0.00 | 0.00 |
| June | 725.61 | 347.09 | 378.52 | 810.08 | 171.39 | 0.00 | 0.00 | 0.00 |
| July | 710.83 | 333.75 | 377.08 | 823.42 | 154.34 | 0.00 | 0.00 | 0.00 |
| August | 548.05 | 239.53 | 308.52 | 600.18 | 181.49 | 0.00 | 0.00 | 0.00 |
| September | 438.90 | 196.44 | 242.46 | 397.96 | 291.97 | 0.00 | 0.00 | 0.00 |
| October | 265.76 | 100.77 | 164.99 | 160.47 | 433.84 | 0.00 | 0.00 | 0.00 |
| November | 169.19 | 56.56 | 112.62 | 61.48 | 609.40 | 0.00 | 0.00 | 0.00 |
| December | 154.38 | 57.06 | 97.32 | 30.38 | 943.50 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 432.61 | 197.13 | 235.48 | 375.05 | 481.95 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 154.38 | 56.56 | 97.32 | 30.38 | 154.34 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 725.61 | 347.09 | 378.52 | 823.42 | 969.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 101.84 | 42.51 | 59.33 | 23.12 | 572.17 | 666.50 | 0.00 | 0.00 |
| February | 160.03 | 68.26 | 91.77 | 66.26 | 474.59 | 507.67 | 0.00 | 0.00 |
| March | 218.04 | 109.37 | 108.67 | 131.25 | 392.67 | 402.17 | 0.00 | 0.00 |
| April | 302.27 | 163.04 | 139.23 | 244.92 | 252.82 | 183.83 | 0.00 | 0.00 |
| May | 327.15 | 143.82 | 183.33 | 317.64 | 134.83 | 7.50 | 0.00 | 0.00 |
| June | 370.35 | 177.16 | 193.19 | 411.94 | 97.79 | 0.00 | 0.00 | 0.00 |
| July | 362.81 | 170.35 | 192.46 | 419.44 | 86.65 | 0.00 | 0.00 | 0.00 |
| August | 279.73 | 122.26 | 157.47 | 304.82 | 103.65 | 0.00 | 0.00 | 0.00 |
| September | 224.02 | 100.27 | 123.75 | 199.74 | 164.86 | 0.00 | 0.00 | 0.00 |
| October | 135.65 | 51.44 | 84.21 | 75.34 | 265.88 | 103.33 | 0.00 | 0.00 |
| November | 86.35 | 28.87 | 57.48 | 27.18 | 391.69 | 359.00 | 0.00 | 0.00 |
| December | 78.80 | 29.12 | 49.67 | 13.75 | 557.58 | 568.00 | 0.00 | 0.00 |
| Annual Sum or Average | 220.81 | 100.62 | 120.19 | 186.89 | 290.47 | 2798.00 | 0.00 | 0.00 |
| Minimum of Months | 78.80 | 28.87 | 49.67 | 13.75 | 86.65 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 370.35 | 177.16 | 193.19 | 419.44 | 572.17 | 666.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 114.69 | 0.00 | 114.69 | 0.23 | 1431.37 | 0.00 | 0.00 | 0.00 |
| February | 176.11 | 0.00 | 176.11 | 6.02 | 1149.62 | 0.00 | 0.00 | 0.00 |
| March | 216.79 | 0.00 | 216.79 | 13.71 | 902.47 | 0.00 | 0.00 | 0.00 |
| April | 282.63 | 1.30 | 281.32 | 85.18 | 547.69 | 0.00 | 0.00 | 0.00 |
| May | 389.92 | 14.71 | 375.21 | 273.34 | 295.20 | 0.00 | 0.00 | 0.00 |
| June | 429.13 | 37.75 | 391.38 | 399.83 | 214.93 | 0.00 | 0.00 | 0.00 |
| July | 412.53 | 27.46 | 385.07 | 410.13 | 195.01 | 0.00 | 0.00 | 0.00 |
| August | 319.57 | 3.49 | 316.08 | 277.41 | 231.31 | 0.00 | 0.00 | 0.00 |
| September | 252.14 | 0.03 | 252.11 | 129.58 | 390.24 | 0.00 | 0.00 | 0.00 |
| October | 175.44 | 0.00 | 175.44 | 26.53 | 582.76 | 0.00 | 0.00 | 0.00 |
| November | 115.97 | 0.00 | 115.97 | 4.03 | 872.60 | 0.00 | 0.00 | 0.00 |
| December | 97.30 | 0.00 | 97.30 | 0.00 | 1366.65 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 248.88 | 7.09 | 241.79 | 136.35 | 679.73 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 97.30 | 0.00 | 97.30 | 0.00 | 195.01 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 429.13 | 37.75 | 391.38 | 410.13 | 1431.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.02 | 7.10 | 9.91 | 4.34 | 81.55 | 0.00 | 0.00 | 0.00 |
| February | 26.74 | 11.41 | 15.33 | 12.88 | 64.21 | 0.00 | 0.00 | 0.00 |
| March | 36.44 | 18.28 | 18.16 | 24.34 | 50.76 | 0.00 | 0.00 | 0.00 |
| April | 50.51 | 27.24 | 23.27 | 44.59 | 31.27 | 0.00 | 0.00 | 0.00 |
| May | 54.67 | 24.03 | 30.63 | 55.40 | 18.44 | 0.00 | 0.00 | 0.00 |
| June | 61.89 | 29.60 | 32.28 | 70.03 | 13.88 | 0.00 | 0.00 | 0.00 |
| July | 60.63 | 28.47 | 32.16 | 70.72 | 12.56 | 0.00 | 0.00 | 0.00 |
| August | 46.74 | 20.43 | 26.31 | 51.81 | 14.61 | 0.00 | 0.00 | 0.00 |
| September | 37.43 | 16.75 | 20.68 | 34.80 | 23.31 | 0.00 | 0.00 | 0.00 |
| October | 22.67 | 8.60 | 14.07 | 14.37 | 34.50 | 0.00 | 0.00 | 0.00 |
| November | 14.43 | 4.82 | 9.61 | 5.34 | 50.77 | 0.00 | 0.00 | 0.00 |
| December | 13.17 | 4.87 | 8.30 | 2.69 | 79.38 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 36.90 | 16.81 | 20.08 | 32.70 | 39.51 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 13.17 | 4.82 | 8.30 | 2.69 | 12.56 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 61.89 | 29.60 | 32.28 | 70.72 | 81.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 173.93 | 72.60 | 101.33 | 44.36 | 833.57 | 0.00 | 0.00 | 0.00 |
| February | 273.32 | 116.58 | 156.73 | 131.63 | 656.30 | 0.00 | 0.00 | 0.00 |
| March | 372.41 | 186.81 | 185.60 | 248.80 | 518.86 | 0.00 | 0.00 | 0.00 |
| April | 516.27 | 278.47 | 237.80 | 455.77 | 319.56 | 0.00 | 0.00 | 0.00 |
| May | 558.75 | 245.63 | 313.12 | 566.25 | 188.38 | 0.00 | 0.00 | 0.00 |
| June | 632.55 | 302.58 | 329.97 | 715.92 | 141.78 | 0.00 | 0.00 | 0.00 |
| July | 619.66 | 290.96 | 328.71 | 722.94 | 128.31 | 0.00 | 0.00 | 0.00 |
| August | 477.76 | 208.82 | 268.95 | 529.57 | 149.35 | 0.00 | 0.00 | 0.00 |
| September | 382.61 | 171.25 | 211.35 | 355.65 | 238.28 | 0.00 | 0.00 | 0.00 |
| October | 231.68 | 87.85 | 143.82 | 146.89 | 352.64 | 0.00 | 0.00 | 0.00 |
| November | 147.49 | 49.31 | 98.18 | 54.53 | 518.95 | 0.00 | 0.00 | 0.00 |
| December | 134.58 | 49.74 | 84.84 | 27.49 | 811.37 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 377.13 | 171.86 | 205.27 | 334.29 | 403.81 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 134.58 | 49.31 | 84.84 | 27.49 | 128.31 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 632.55 | 302.58 | 329.97 | 722.94 | 833.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 110.32 | 0.00 | 110.32 | 0.39 | 1284.86 | 0.00 | 0.00 | 0.00 |
| February | 169.45 | 0.00 | 169.45 | 7.31 | 1022.45 | 0.00 | 0.00 | 0.00 |
| March | 208.48 | 0.00 | 208.48 | 16.31 | 791.75 | 0.00 | 0.00 | 0.00 |
| April | 273.31 | 2.13 | 271.18 | 86.89 | 486.13 | 0.00 | 0.00 | 0.00 |
| May | 384.40 | 20.70 | 363.70 | 278.78 | 265.60 | 0.00 | 0.00 | 0.00 |
| June | 429.00 | 47.16 | 381.84 | 408.28 | 189.69 | 0.00 | 0.00 | 0.00 |
| July | 409.76 | 35.16 | 374.60 | 420.32 | 170.95 | 0.00 | 0.00 | 0.00 |
| August | 311.23 | 5.34 | 305.88 | 277.31 | 207.50 | 0.00 | 0.00 | 0.00 |
| September | 242.53 | 0.06 | 242.47 | 127.36 | 368.10 | 0.00 | 0.00 | 0.00 |
| October | 168.40 | 0.00 | 168.40 | 25.88 | 546.48 | 0.00 | 0.00 | 0.00 |
| November | 111.50 | 0.00 | 111.50 | 4.69 | 771.13 | 0.00 | 0.00 | 0.00 |
| December | 93.47 | 0.00 | 93.47 | 0.00 | 1225.52 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 243.02 | 9.25 | 233.77 | 138.66 | 609.18 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 93.47 | 0.00 | 93.47 | 0.00 | 170.95 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 429.00 | 47.16 | 381.84 | 420.32 | 1284.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.51 | 0.00 | 5.51 | 0.00 | 87.94 | 0.00 | 0.00 | 0.00 |
| February | 8.60 | 0.00 | 8.60 | 0.12 | 70.79 | 0.00 | 0.00 | 0.00 |
| March | 10.72 | 0.00 | 10.72 | 0.34 | 55.66 | 0.00 | 0.00 | 0.00 |
| April | 23.80 | 8.34 | 15.46 | 12.75 | 31.25 | 0.00 | 0.00 | 0.00 |
| May | 37.51 | 15.74 | 21.77 | 33.99 | 17.53 | 0.00 | 0.00 | 0.00 |
| June | 47.14 | 23.32 | 23.83 | 51.81 | 12.99 | 0.00 | 0.00 | 0.00 |
| July | 44.64 | 21.08 | 23.56 | 51.07 | 11.21 | 0.00 | 0.00 | 0.00 |
| August | 27.69 | 9.91 | 17.78 | 27.91 | 13.71 | 0.00 | 0.00 | 0.00 |
| September | 13.93 | 1.22 | 12.71 | 6.06 | 24.35 | 0.00 | 0.00 | 0.00 |
| October | 8.40 | 0.00 | 8.40 | 0.61 | 38.40 | 0.00 | 0.00 | 0.00 |
| November | 5.52 | 0.00 | 5.52 | 0.13 | 53.01 | 0.00 | 0.00 | 0.00 |
| December | 4.63 | 0.00 | 4.63 | 0.00 | 83.48 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 19.90 | 6.67 | 13.23 | 15.50 | 41.58 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4.63 | 0.00 | 4.63 | 0.00 | 11.21 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 47.14 | 23.32 | 23.83 | 51.81 | 87.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 200.86 | 69.45 | 131.41 | 25.28 | 1218.56 | 0.00 | 0.00 | 0.00 |
| February | 354.52 | 143.20 | 211.32 | 150.49 | 941.79 | 0.00 | 0.00 | 0.00 |
| March | 525.13 | 266.68 | 258.45 | 351.88 | 733.48 | 0.00 | 0.00 | 0.00 |
| April | 733.31 | 401.42 | 331.89 | 646.34 | 457.92 | 0.00 | 0.00 | 0.00 |
| May | 791.54 | 354.09 | 437.45 | 798.23 | 272.78 | 0.00 | 0.00 | 0.00 |
| June | 896.82 | 436.19 | 460.64 | 1014.54 | 201.55 | 0.00 | 0.00 | 0.00 |
| July | 878.08 | 419.42 | 458.65 | 1030.88 | 178.54 | 0.00 | 0.00 | 0.00 |
| August | 676.04 | 301.02 | 375.03 | 750.95 | 212.71 | 0.00 | 0.00 | 0.00 |
| September | 541.33 | 246.57 | 294.76 | 495.91 | 356.42 | 0.00 | 0.00 | 0.00 |
| October | 315.56 | 117.27 | 198.28 | 186.09 | 528.54 | 0.00 | 0.00 | 0.00 |
| November | 184.79 | 54.27 | 130.51 | 55.87 | 741.72 | 0.00 | 0.00 | 0.00 |
| December | 150.92 | 41.64 | 109.28 | 10.25 | 1185.17 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 521.36 | 237.86 | 283.50 | 461.24 | 584.44 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 150.92 | 41.64 | 109.28 | 10.25 | 178.54 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 896.82 | 436.19 | 460.64 | 1030.88 | 1218.56 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.310144E+09 | 0.129870E+09 | 0.180274E+09 | 91765272.39 | 0.149429E+10 |
| February | 0.456414E+09 | 0.208459E+09 | 0.247954E+09 | 0.250613E+09 | 0.107365E+10 |
| March | 0.664956E+09 | 0.340253E+09 | 0.324702E+09 | 0.467555E+09 | 0.912978E+09 |
| April | 0.822043E+09 | 0.416357E+09 | 0.405686E+09 | 0.726579E+09 | 0.529567E+09 |
| May | 0.104369E+10 | 0.497847E+09 | 0.545847E+09 | 0.112361E+10 | 0.310894E+09 |
| June | 0.974652E+09 | 0.421432E+09 | 0.553220E+09 | 0.112957E+10 | 0.209283E+09 |
| July | 0.107522E+10 | 0.499866E+09 | 0.575354E+09 | 0.129719E+10 | 0.202556E+09 |
| August | 0.884835E+09 | 0.402064E+09 | 0.482771E+09 | 0.101866E+10 | 0.242377E+09 |
| September | 0.669225E+09 | 0.300673E+09 | 0.368552E+09 | 0.632586E+09 | 0.409056E+09 |
| October | 0.436846E+09 | 0.175369E+09 | 0.261477E+09 | 0.296670E+09 | 0.621243E+09 |
| November | 0.256760E+09 | 86569689.51 | 0.170190E+09 | 99374442.48 | 0.864855E+09 |
| December | 0.236517E+09 | 82782512.07 | 0.153734E+09 | 48375122.82 | 0.144289E+10 |
| Annual Sum or Average | 0.783130E+10 | 0.356154E+10 | 0.426976E+10 | 0.718255E+10 | 0.831365E+10 |
| Minimum of Months | 0.236517E+09 | 82782512.07 | 0.153734E+09 | 48375122.82 | 0.202556E+09 |
| Maximum of Months | 0.107522E+10 | 0.499866E+09 | 0.575354E+09 | 0.129719E+10 | 0.149429E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.148354E+09 | 0.103206E+09 | 45147506.20 | 0.108038E+09 | 0.193096E+09 |
| February | 0.169672E+09 | 0.114603E+09 | 55069898.86 | 0.146709E+09 | 0.143671E+09 |
| March | 0.165520E+09 | 0.104751E+09 | 60769093.06 | 0.148803E+09 | 0.129951E+09 |
| April | 0.145119E+09 | 78766283.30 | 66352611.61 | 0.145353E+09 | 81658486.40 |
| May | 0.126074E+09 | 43101517.15 | 82972384.29 | 0.137963E+09 | 49509175.78 |
| June | 0.109474E+09 | 29179634.64 | 80294862.75 | 0.130152E+09 | 33231248.04 |
| July | 0.123681E+09 | 39181341.40 | 84499451.36 | 0.155117E+09 | 31686751.40 |
| August | 0.132084E+09 | 55249543.34 | 76834358.00 | 0.158718E+09 | 37869002.23 |
| September | 0.136918E+09 | 72918738.40 | 63998847.86 | 0.146109E+09 | 62958223.65 |
| October | 0.120815E+09 | 71057292.48 | 49757814.94 | 0.111616E+09 | 90625427.50 |
| November | 0.104148E+09 | 65363352.13 | 38784649.56 | 84475196.99 | 0.118748E+09 |
| December | 0.114547E+09 | 75109807.89 | 39437219.01 | 76609892.84 | 0.188779E+09 |
| Annual Sum or Average | 0.159641E+10 | 0.852488E+09 | 0.743919E+09 | 0.154966E+10 | 0.116178E+10 |
| Minimum of Months | 0.104148E+09 | 29179634.64 | 38784649.56 | 76609892.84 | 31686751.40 |
| Maximum of Months | 0.169672E+09 | 0.114603E+09 | 84499451.36 | 0.158718E+09 | 0.193096E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.102962E+10 | 0.716282E+09 | 0.313337E+09 | 0.749814E+09 | 0.134014E+10 |
| February | 0.117758E+10 | 0.795375E+09 | 0.382201E+09 | 0.101820E+10 | 0.997119E+09 |
| March | 0.114876E+10 | 0.727003E+09 | 0.421755E+09 | 0.103274E+10 | 0.901899E+09 |
| April | 0.100717E+10 | 0.546661E+09 | 0.460506E+09 | 0.100878E+10 | 0.566845E+09 |
| May | 0.874989E+09 | 0.299137E+09 | 0.575852E+09 | 0.956336E+09 | 0.345239E+09 |
| June | 0.759785E+09 | 0.202515E+09 | 0.557270E+09 | 0.900356E+09 | 0.231573E+09 |
| July | 0.858380E+09 | 0.271930E+09 | 0.586451E+09 | 0.107380E+10 | 0.220628E+09 |
| August | 0.916700E+09 | 0.383448E+09 | 0.533253E+09 | 0.110123E+10 | 0.263200E+09 |
| September | 0.950248E+09 | 0.506077E+09 | 0.444170E+09 | 0.101404E+10 | 0.436936E+09 |
| October | 0.838492E+09 | 0.493158E+09 | 0.345334E+09 | 0.774649E+09 | 0.628967E+09 |
| November | 0.722817E+09 | 0.453641E+09 | 0.269177E+09 | 0.586282E+09 | 0.824147E+09 |
| December | 0.794989E+09 | 0.521284E+09 | 0.273706E+09 | 0.531695E+09 | 0.131018E+10 |
| Annual Sum or Average | 0.110795E+11 | 0.591651E+10 | 0.516301E+10 | 0.107479E+11 | 0.806688E+10 |
| Minimum of Months | 0.722817E+09 | 0.202515E+09 | 0.269177E+09 | 0.531695E+09 | 0.220628E+09 |
| Maximum of Months | 0.117758E+10 | 0.795375E+09 | 0.586451E+09 | 0.110123E+10 | 0.134014E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.189195E+10 | 0.131619E+10 | 0.575764E+09 | 0.137418E+10 | 0.250365E+10 |
| February | 0.216383E+10 | 0.146153E+10 | 0.702304E+09 | 0.186535E+10 | 0.187593E+10 |
| March | 0.211087E+10 | 0.133589E+10 | 0.774984E+09 | 0.188495E+10 | 0.172094E+10 |
| April | 0.185070E+10 | 0.100451E+10 | 0.846190E+09 | 0.183211E+10 | 0.111654E+10 |
| May | 0.160781E+10 | 0.549673E+09 | 0.105814E+10 | 0.174448E+10 | 0.673759E+09 |
| June | 0.139612E+10 | 0.372128E+09 | 0.102399E+10 | 0.164919E+10 | 0.452595E+09 |
| July | 0.157729E+10 | 0.499679E+09 | 0.107761E+10 | 0.199638E+10 | 0.403337E+09 |
| August | 0.168446E+10 | 0.704597E+09 | 0.979863E+09 | 0.204336E+10 | 0.482154E+09 |
| September | 0.174610E+10 | 0.929932E+09 | 0.816173E+09 | 0.186103E+10 | 0.833998E+09 |
| October | 0.154075E+10 | 0.906193E+09 | 0.634559E+09 | 0.141000E+10 | 0.122269E+10 |
| November | 0.132820E+10 | 0.833578E+09 | 0.494619E+09 | 0.106636E+10 | 0.158217E+10 |
| December | 0.146082E+10 | 0.957875E+09 | 0.502941E+09 | 0.972390E+09 | 0.245119E+10 |
| Annual Sum or Average | 0.203589E+11 | 0.108718E+11 | 0.948714E+10 | 0.196998E+11 | 0.153189E+11 |
| Minimum of Months | 0.132820E+10 | 0.372128E+09 | 0.494619E+09 | 0.972390E+09 | 0.403337E+09 |
| Maximum of Months | 0.216383E+10 | 0.146153E+10 | 0.107761E+10 | 0.204336E+10 | 0.250365E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.189195E+10 | 0.131619E+10 | 0.575764E+09 | 0.137418E+10 | 0.250365E+10 |
| February | 0.216383E+10 | 0.146153E+10 | 0.702304E+09 | 0.186535E+10 | 0.187593E+10 |
| March | 0.211087E+10 | 0.133589E+10 | 0.774984E+09 | 0.188495E+10 | 0.172094E+10 |
| April | 0.185070E+10 | 0.100451E+10 | 0.846190E+09 | 0.183211E+10 | 0.111654E+10 |
| May | 0.160781E+10 | 0.549673E+09 | 0.105814E+10 | 0.174448E+10 | 0.673759E+09 |
| June | 0.139612E+10 | 0.372128E+09 | 0.102399E+10 | 0.164919E+10 | 0.452595E+09 |
| July | 0.157729E+10 | 0.499679E+09 | 0.107761E+10 | 0.199638E+10 | 0.403337E+09 |
| August | 0.168446E+10 | 0.704597E+09 | 0.979863E+09 | 0.204336E+10 | 0.482154E+09 |
| September | 0.174610E+10 | 0.929932E+09 | 0.816173E+09 | 0.186103E+10 | 0.833998E+09 |
| October | 0.154075E+10 | 0.906193E+09 | 0.634559E+09 | 0.141000E+10 | 0.122269E+10 |
| November | 0.132820E+10 | 0.833578E+09 | 0.494619E+09 | 0.106636E+10 | 0.158217E+10 |
| December | 0.146082E+10 | 0.957875E+09 | 0.502941E+09 | 0.972390E+09 | 0.245119E+10 |
| Annual Sum or Average | 0.203589E+11 | 0.108718E+11 | 0.948714E+10 | 0.196998E+11 | 0.153189E+11 |
| Minimum of Months | 0.132820E+10 | 0.372128E+09 | 0.494619E+09 | 0.972390E+09 | 0.403337E+09 |
| Maximum of Months | 0.216383E+10 | 0.146153E+10 | 0.107761E+10 | 0.204336E+10 | 0.250365E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.189192E+10 | 0.131617E+10 | 0.575753E+09 | 0.137415E+10 | 0.250360E+10 |
| February | 0.216379E+10 | 0.146150E+10 | 0.702290E+09 | 0.186532E+10 | 0.187589E+10 |
| March | 0.211083E+10 | 0.133586E+10 | 0.774969E+09 | 0.188491E+10 | 0.172091E+10 |
| April | 0.185066E+10 | 0.100449E+10 | 0.846173E+09 | 0.183208E+10 | 0.111652E+10 |
| May | 0.160778E+10 | 0.549662E+09 | 0.105812E+10 | 0.174445E+10 | 0.673746E+09 |
| June | 0.139609E+10 | 0.372120E+09 | 0.102397E+10 | 0.164916E+10 | 0.452586E+09 |
| July | 0.157726E+10 | 0.499670E+09 | 0.107759E+10 | 0.199634E+10 | 0.403329E+09 |
| August | 0.168443E+10 | 0.704583E+09 | 0.979844E+09 | 0.204332E+10 | 0.482145E+09 |
| September | 0.174607E+10 | 0.929914E+09 | 0.816157E+09 | 0.186099E+10 | 0.833982E+09 |
| October | 0.154072E+10 | 0.906175E+09 | 0.634546E+09 | 0.140997E+10 | 0.122266E+10 |
| November | 0.132817E+10 | 0.833562E+09 | 0.494609E+09 | 0.106634E+10 | 0.158214E+10 |
| December | 0.146079E+10 | 0.957856E+09 | 0.502932E+09 | 0.972372E+09 | 0.245114E+10 |
| Annual Sum or Average | 0.203585E+11 | 0.108716E+11 | 0.948696E+10 | 0.196994E+11 | 0.153186E+11 |
| Minimum of Months | 0.132817E+10 | 0.372120E+09 | 0.494609E+09 | 0.972372E+09 | 0.403329E+09 |
| Maximum of Months | 0.216379E+10 | 0.146150E+10 | 0.107759E+10 | 0.204332E+10 | 0.250360E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.103382E+09 | 43290087.88 | 60091432.06 | 29803224.21 | 0.522233E+09 |
| February | 0.152138E+09 | 69486688.70 | 82651674.54 | 83119354.48 | 0.376931E+09 |
| March | 0.221653E+09 | 0.113418E+09 | 0.108234E+09 | 0.155392E+09 | 0.324856E+09 |
| April | 0.274015E+09 | 0.138786E+09 | 0.135229E+09 | 0.241274E+09 | 0.192479E+09 |
| May | 0.347899E+09 | 0.165949E+09 | 0.181950E+09 | 0.371930E+09 | 0.112223E+09 |
| June | 0.324885E+09 | 0.140478E+09 | 0.184407E+09 | 0.373126E+09 | 75952822.78 |
| July | 0.358408E+09 | 0.166623E+09 | 0.191785E+09 | 0.434479E+09 | 67485649.92 |
| August | 0.294946E+09 | 0.134022E+09 | 0.160924E+09 | 0.343866E+09 | 79008127.71 |
| September | 0.223076E+09 | 0.100225E+09 | 0.122851E+09 | 0.213596E+09 | 0.139391E+09 |
| October | 0.145616E+09 | 58456537.20 | 87159171.73 | 0.100475E+09 | 0.216226E+09 |
| November | 85586924.79 | 28856659.36 | 56730265.43 | 33428838.37 | 0.306162E+09 |
| December | 78839157.79 | 27594262.67 | 51244895.12 | 15672946.57 | 0.506779E+09 |
| Annual Sum or Average | 0.261044E+10 | 0.118718E+10 | 0.142326E+10 | 0.239616E+10 | 0.291973E+10 |
| Minimum of Months | 78839157.79 | 27594262.67 | 51244895.12 | 15672946.57 | 67485649.92 |
| Maximum of Months | 0.358408E+09 | 0.166623E+09 | 0.191785E+09 | 0.434479E+09 | 0.522233E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.310144E+09 | 0.129870E+09 | 0.180274E+09 | 95879466.60 | 0.148258E+10 |
| February | 0.456414E+09 | 0.208459E+09 | 0.247954E+09 | 0.260671E+09 | 0.105731E+10 |
| March | 0.664956E+09 | 0.340253E+09 | 0.324702E+09 | 0.483374E+09 | 0.891835E+09 |
| April | 0.822043E+09 | 0.416357E+09 | 0.405686E+09 | 0.755053E+09 | 0.501268E+09 |
| May | 0.104369E+10 | 0.497847E+09 | 0.545847E+09 | 0.114356E+10 | 0.295909E+09 |
| June | 0.974652E+09 | 0.421432E+09 | 0.553220E+09 | 0.114086E+10 | 0.202865E+09 |
| July | 0.107522E+10 | 0.499866E+09 | 0.575354E+09 | 0.132039E+10 | 0.188778E+09 |
| August | 0.884835E+09 | 0.402064E+09 | 0.482771E+09 | 0.104829E+10 | 0.218829E+09 |
| September | 0.669225E+09 | 0.300673E+09 | 0.368552E+09 | 0.660739E+09 | 0.377796E+09 |
| October | 0.436846E+09 | 0.175369E+09 | 0.261477E+09 | 0.316055E+09 | 0.583216E+09 |
| November | 0.256760E+09 | 86569689.51 | 0.170190E+09 | 0.107451E+09 | 0.842326E+09 |
| December | 0.236517E+09 | 82782512.07 | 0.153734E+09 | 51162958.83 | 0.143260E+10 |
| Annual Sum or Average | 0.783130E+10 | 0.356154E+10 | 0.426976E+10 | 0.738349E+10 | 0.807532E+10 |
| Minimum of Months | 0.236517E+09 | 82782512.07 | 0.153734E+09 | 51162958.83 | 0.188778E+09 |
| Maximum of Months | 0.107522E+10 | 0.499866E+09 | 0.575354E+09 | 0.132039E+10 | 0.148258E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 17331208.92 | 0.00 | 17331208.92 | 6643.50 | 0.248680E+09 |
| February | 23798516.09 | 0.00 | 23798516.09 | 514748.22 | 0.180040E+09 |
| March | 32299168.77 | 0.00 | 32299168.77 | 1492190.20 | 0.153222E+09 |
| April | 41151341.75 | 340028.76 | 40811312.99 | 13076763.51 | 81771627.93 |
| May | 60843839.44 | 3638766.15 | 57205073.28 | 46468458.69 | 42812739.52 |
| June | 65450169.33 | 8009319.10 | 57440850.23 | 67141520.60 | 29116264.05 |
| July | 63689484.95 | 6016388.80 | 57673096.15 | 71888618.30 | 26741748.55 |
| August | 48237324.05 | 987049.12 | 47250274.93 | 46730281.58 | 31550791.09 |
| September | 36698249.74 | 8064.32 | 36690185.43 | 19100632.00 | 59330790.63 |
| October | 26869264.83 | 0.00 | 26869264.83 | 3604616.70 | 94430994.24 |
| November | 17100985.74 | 0.00 | 17100985.74 | 712164.64 | 0.138961E+09 |
| December | 14893344.37 | 0.00 | 14893344.37 | 0.00 | 0.235950E+09 |
| Annual Sum or Average | 0.448363E+09 | 18999616.25 | 0.429363E+09 | 0.270737E+09 | 0.132261E+10 |
| Minimum of Months | 14893344.37 | 0.00 | 14893344.37 | 0.00 | 26741748.55 |
| Maximum of Months | 65450169.33 | 8009319.10 | 57673096.15 | 71888618.30 | 0.248680E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.127108E+09 | 0.00 | 0.127108E+09 | 125075.10 | 0.171903E+10 |
| February | 0.175037E+09 | 0.00 | 0.175037E+09 | 4986578.29 | 0.123972E+10 |
| March | 0.237799E+09 | 0.00 | 0.237799E+09 | 13912350.23 | 0.105160E+10 |
| April | 0.302436E+09 | 2359897.74 | 0.300076E+09 | 0.103739E+09 | 0.563204E+09 |
| May | 0.444296E+09 | 25254087.67 | 0.419042E+09 | 0.347202E+09 | 0.298367E+09 |
| June | 0.477436E+09 | 55586986.97 | 0.421849E+09 | 0.493213E+09 | 0.203953E+09 |
| July | 0.466359E+09 | 41755475.29 | 0.424604E+09 | 0.527756E+09 | 0.188069E+09 |
| August | 0.354958E+09 | 6850623.32 | 0.348108E+09 | 0.348589E+09 | 0.220906E+09 |
| September | 0.269484E+09 | 58255.97 | 0.269426E+09 | 0.148454E+09 | 0.411293E+09 |
| October | 0.196229E+09 | 0.00 | 0.196229E+09 | 30847328.47 | 0.651313E+09 |
| November | 0.125120E+09 | 0.00 | 0.125120E+09 | 5454262.09 | 0.959763E+09 |
| December | 0.108808E+09 | 0.00 | 0.108808E+09 | 0.00 | 0.163312E+10 |
| Annual Sum or Average | 0.328507E+10 | 0.131865E+09 | 0.315321E+10 | 0.202428E+10 | 0.914034E+10 |
| Minimum of Months | 0.108808E+09 | 0.00 | 0.108808E+09 | 0.00 | 0.188069E+09 |
| Maximum of Months | 0.477436E+09 | 55586986.97 | 0.424604E+09 | 0.527756E+09 | 0.171903E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.209694E+09 | 0.00 | 0.209694E+09 | 8474.53 | 0.321781E+10 |
| February | 0.288185E+09 | 0.00 | 0.288185E+09 | 4458851.72 | 0.234211E+10 |
| March | 0.391627E+09 | 0.00 | 0.391627E+09 | 13616675.29 | 0.202219E+10 |
| April | 0.495294E+09 | 1999031.43 | 0.493294E+09 | 0.138596E+09 | 0.112813E+10 |
| May | 0.714451E+09 | 29113036.44 | 0.685338E+09 | 0.528947E+09 | 0.605389E+09 |
| June | 0.739166E+09 | 59969065.07 | 0.679197E+09 | 0.739493E+09 | 0.404724E+09 |
| July | 0.730218E+09 | 45351241.49 | 0.684866E+09 | 0.847071E+09 | 0.339013E+09 |
| August | 0.575220E+09 | 7053153.41 | 0.568167E+09 | 0.580871E+09 | 0.402556E+09 |
| September | 0.444649E+09 | 79374.11 | 0.444570E+09 | 0.221603E+09 | 0.780947E+09 |
| October | 0.325501E+09 | 0.00 | 0.325501E+09 | 34064343.13 | 0.127727E+10 |
| November | 0.206833E+09 | 0.00 | 0.206833E+09 | 7601086.63 | 0.184476E+10 |
| December | 0.180230E+09 | 0.00 | 0.180230E+09 | 0.00 | 0.305737E+10 |
| Annual Sum or Average | 0.530107E+10 | 0.143565E+09 | 0.515750E+10 | 0.311633E+10 | 0.174223E+11 |
| Minimum of Months | 0.180230E+09 | 0.00 | 0.180230E+09 | 0.00 | 0.339013E+09 |
| Maximum of Months | 0.739166E+09 | 59969065.07 | 0.685338E+09 | 0.847071E+09 | 0.321781E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.221105E+09 | 0.00 | 0.221105E+09 | 57596.76 | 0.321327E+10 |
| February | 0.303619E+09 | 0.00 | 0.303619E+09 | 6166343.62 | 0.233364E+10 |
| March | 0.412071E+09 | 0.00 | 0.412071E+09 | 16810236.74 | 0.200888E+10 |
| April | 0.523232E+09 | 3469090.18 | 0.519763E+09 | 0.153155E+09 | 0.111561E+10 |
| May | 0.766532E+09 | 40169985.59 | 0.726362E+09 | 0.574119E+09 | 0.587900E+09 |
| June | 0.811679E+09 | 86144151.53 | 0.725535E+09 | 0.829540E+09 | 0.401281E+09 |
| July | 0.795431E+09 | 64737366.35 | 0.730694E+09 | 0.927615E+09 | 0.338224E+09 |
| August | 0.611994E+09 | 10668022.58 | 0.601326E+09 | 0.617746E+09 | 0.397985E+09 |
| September | 0.467995E+09 | 83511.90 | 0.467912E+09 | 0.243445E+09 | 0.780715E+09 |
| October | 0.342778E+09 | 0.00 | 0.342778E+09 | 41127651.91 | 0.127113E+10 |
| November | 0.218165E+09 | 0.00 | 0.218165E+09 | 8498894.72 | 0.184047E+10 |
| December | 0.189999E+09 | 0.00 | 0.189999E+09 | 0.00 | 0.305424E+10 |
| Annual Sum or Average | 0.566460E+10 | 0.205272E+09 | 0.545933E+10 | 0.341828E+10 | 0.173434E+11 |
| Minimum of Months | 0.189999E+09 | 0.00 | 0.189999E+09 | 0.00 | 0.338224E+09 |
| Maximum of Months | 0.811679E+09 | 86144151.53 | 0.730694E+09 | 0.927615E+09 | 0.321327E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.221170E+09 | 0.00 | 0.221170E+09 | 58066.84 | 0.321318E+10 |
| February | 0.303713E+09 | 0.00 | 0.303713E+09 | 6177771.05 | 0.233353E+10 |
| March | 0.412202E+09 | 0.00 | 0.412202E+09 | 16837793.25 | 0.200874E+10 |
| April | 0.525088E+09 | 4301356.14 | 0.520787E+09 | 0.153345E+09 | 0.111272E+10 |
| May | 0.771728E+09 | 43397358.55 | 0.728330E+09 | 0.577684E+09 | 0.583952E+09 |
| June | 0.817104E+09 | 89702593.19 | 0.727402E+09 | 0.833555E+09 | 0.397850E+09 |
| July | 0.800884E+09 | 68332823.46 | 0.732551E+09 | 0.932434E+09 | 0.335416E+09 |
| August | 0.615150E+09 | 12330859.74 | 0.602820E+09 | 0.620289E+09 | 0.395774E+09 |
| September | 0.468309E+09 | 100735.96 | 0.468208E+09 | 0.243587E+09 | 0.780437E+09 |
| October | 0.342871E+09 | 0.00 | 0.342871E+09 | 41172125.40 | 0.127108E+10 |
| November | 0.218226E+09 | 0.00 | 0.218226E+09 | 8503185.55 | 0.184041E+10 |
| December | 0.190050E+09 | 0.00 | 0.190050E+09 | 0.00 | 0.305417E+10 |
| Annual Sum or Average | 0.568650E+10 | 0.218166E+09 | 0.546833E+10 | 0.343364E+10 | 0.173273E+11 |
| Minimum of Months | 0.190050E+09 | 0.00 | 0.190050E+09 | 0.00 | 0.335416E+09 |
| Maximum of Months | 0.817104E+09 | 89702593.19 | 0.732551E+09 | 0.932434E+09 | 0.321318E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.310144E+09 | 0.129870E+09 | 0.180274E+09 | 92184599.95 | 0.149375E+10 |
| February | 0.456414E+09 | 0.208459E+09 | 0.247954E+09 | 0.250989E+09 | 0.107341E+10 |
| March | 0.664956E+09 | 0.340253E+09 | 0.324702E+09 | 0.468220E+09 | 0.912390E+09 |
| April | 0.822043E+09 | 0.416357E+09 | 0.405686E+09 | 0.728045E+09 | 0.528424E+09 |
| May | 0.104369E+10 | 0.497847E+09 | 0.545847E+09 | 0.112605E+10 | 0.309379E+09 |
| June | 0.974652E+09 | 0.421432E+09 | 0.553220E+09 | 0.113213E+10 | 0.207917E+09 |
| July | 0.107522E+10 | 0.499866E+09 | 0.575354E+09 | 0.130099E+10 | 0.200372E+09 |
| August | 0.884835E+09 | 0.402064E+09 | 0.482771E+09 | 0.102155E+10 | 0.240188E+09 |
| September | 0.669225E+09 | 0.300673E+09 | 0.368552E+09 | 0.634142E+09 | 0.407595E+09 |
| October | 0.436846E+09 | 0.175369E+09 | 0.261477E+09 | 0.297398E+09 | 0.620230E+09 |
| November | 0.256760E+09 | 86569689.51 | 0.170190E+09 | 99836041.03 | 0.863693E+09 |
| December | 0.236517E+09 | 82782512.07 | 0.153734E+09 | 48788774.77 | 0.144189E+10 |
| Annual Sum or Average | 0.783130E+10 | 0.356154E+10 | 0.426976E+10 | 0.720033E+10 | 0.829924E+10 |
| Minimum of Months | 0.236517E+09 | 82782512.07 | 0.153734E+09 | 48788774.77 | 0.200372E+09 |
| Maximum of Months | 0.107522E+10 | 0.499866E+09 | 0.575354E+09 | 0.130099E+10 | 0.149375E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.138023E+09 | 97127139.43 | 40896306.12 | 0.101998E+09 | 0.198344E+09 |
| February | 0.164756E+09 | 0.113745E+09 | 51011157.99 | 0.143063E+09 | 0.144515E+09 |
| March | 0.160542E+09 | 0.104747E+09 | 55794615.79 | 0.144181E+09 | 0.129579E+09 |
| April | 0.138986E+09 | 78766283.30 | 60219292.94 | 0.139581E+09 | 81301671.90 |
| May | 0.118050E+09 | 43101517.15 | 74948974.62 | 0.129583E+09 | 48869061.68 |
| June | 0.101024E+09 | 29179634.64 | 71844673.67 | 0.120991E+09 | 32593930.79 |
| July | 0.114814E+09 | 39181341.40 | 75633049.08 | 0.145554E+09 | 30638780.28 |
| August | 0.124734E+09 | 55249543.34 | 69484193.16 | 0.150734E+09 | 36931181.01 |
| September | 0.131531E+09 | 72918650.15 | 58612750.13 | 0.140410E+09 | 62176136.49 |
| October | 0.116884E+09 | 70819184.12 | 46064858.49 | 0.108090E+09 | 90141492.41 |
| November | 99234654.06 | 63681366.93 | 35553287.13 | 81196057.42 | 0.119778E+09 |
| December | 0.103092E+09 | 67723308.54 | 35369086.68 | 69354756.78 | 0.194204E+09 |
| Annual Sum or Average | 0.151167E+10 | 0.836241E+09 | 0.675432E+09 | 0.147474E+10 | 0.116907E+10 |
| Minimum of Months | 99234654.06 | 29179634.64 | 35369086.68 | 69354756.78 | 30638780.28 |
| Maximum of Months | 0.164756E+09 | 0.113745E+09 | 75633049.08 | 0.150734E+09 | 0.198344E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.940883E+09 | 0.667245E+09 | 0.273638E+09 | 0.690948E+09 | 0.137493E+10 |
| February | 0.113130E+10 | 0.789424E+09 | 0.341880E+09 | 0.980972E+09 | 0.100023E+10 |
| March | 0.109740E+10 | 0.726972E+09 | 0.370432E+09 | 0.984781E+09 | 0.898471E+09 |
| April | 0.943872E+09 | 0.546661E+09 | 0.397211E+09 | 0.948776E+09 | 0.564126E+09 |
| May | 0.792188E+09 | 0.299137E+09 | 0.493051E+09 | 0.869037E+09 | 0.339946E+09 |
| June | 0.672579E+09 | 0.202515E+09 | 0.470064E+09 | 0.804931E+09 | 0.226206E+09 |
| July | 0.766880E+09 | 0.271930E+09 | 0.494950E+09 | 0.973577E+09 | 0.211440E+09 |
| August | 0.840847E+09 | 0.383448E+09 | 0.457399E+09 | 0.101773E+10 | 0.255132E+09 |
| September | 0.894673E+09 | 0.506076E+09 | 0.388596E+09 | 0.954508E+09 | 0.429744E+09 |
| October | 0.799205E+09 | 0.491506E+09 | 0.307700E+09 | 0.738422E+09 | 0.623291E+09 |
| November | 0.677671E+09 | 0.439435E+09 | 0.238236E+09 | 0.552848E+09 | 0.828573E+09 |
| December | 0.689783E+09 | 0.456017E+09 | 0.233766E+09 | 0.456812E+09 | 0.135029E+10 |
| Annual Sum or Average | 0.102473E+11 | 0.578037E+10 | 0.446692E+10 | 0.997335E+10 | 0.810237E+10 |
| Minimum of Months | 0.672579E+09 | 0.202515E+09 | 0.233766E+09 | 0.456812E+09 | 0.211440E+09 |
| Maximum of Months | 0.113130E+10 | 0.789424E+09 | 0.494950E+09 | 0.101773E+10 | 0.137493E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.164639E+10 | 0.116805E+10 | 0.478334E+09 | 0.122322E+10 | 0.262918E+10 |
| February | 0.206166E+10 | 0.144525E+10 | 0.616411E+09 | 0.178436E+10 | 0.188818E+10 |
| March | 0.200361E+10 | 0.133581E+10 | 0.667798E+09 | 0.178556E+10 | 0.171677E+10 |
| April | 0.171853E+10 | 0.100451E+10 | 0.714029E+09 | 0.170821E+10 | 0.111501E+10 |
| May | 0.143492E+10 | 0.549673E+09 | 0.885251E+09 | 0.156223E+10 | 0.665169E+09 |
| June | 0.121404E+10 | 0.372128E+09 | 0.841909E+09 | 0.145083E+10 | 0.443678E+09 |
| July | 0.138624E+10 | 0.499679E+09 | 0.886561E+09 | 0.178887E+10 | 0.383303E+09 |
| August | 0.152608E+10 | 0.704597E+09 | 0.821481E+09 | 0.187066E+10 | 0.463977E+09 |
| September | 0.163007E+10 | 0.929931E+09 | 0.700141E+09 | 0.173748E+10 | 0.819445E+09 |
| October | 0.145872E+10 | 0.902926E+09 | 0.555797E+09 | 0.133649E+10 | 0.121309E+10 |
| November | 0.120795E+10 | 0.785487E+09 | 0.422464E+09 | 0.983707E+09 | 0.161324E+10 |
| December | 0.118758E+10 | 0.785473E+09 | 0.402108E+09 | 0.806453E+09 | 0.259731E+10 |
| Annual Sum or Average | 0.184758E+11 | 0.104835E+11 | 0.799228E+10 | 0.180381E+11 | 0.155484E+11 |
| Minimum of Months | 0.118758E+10 | 0.372128E+09 | 0.402108E+09 | 0.806453E+09 | 0.383303E+09 |
| Maximum of Months | 0.206166E+10 | 0.144525E+10 | 0.886561E+09 | 0.187066E+10 | 0.262918E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.164469E+10 | 0.116681E+10 | 0.477879E+09 | 0.122317E+10 | 0.263140E+10 |
| February | 0.205277E+10 | 0.143944E+10 | 0.613336E+09 | 0.178292E+10 | 0.189963E+10 |
| March | 0.200271E+10 | 0.133550E+10 | 0.667215E+09 | 0.178544E+10 | 0.171812E+10 |
| April | 0.171836E+10 | 0.100451E+10 | 0.713858E+09 | 0.170805E+10 | 0.111501E+10 |
| May | 0.143470E+10 | 0.549673E+09 | 0.885028E+09 | 0.156199E+10 | 0.665163E+09 |
| June | 0.121380E+10 | 0.372128E+09 | 0.841673E+09 | 0.145057E+10 | 0.443673E+09 |
| July | 0.138599E+10 | 0.499679E+09 | 0.886314E+09 | 0.178859E+10 | 0.383287E+09 |
| August | 0.152587E+10 | 0.704597E+09 | 0.821277E+09 | 0.187043E+10 | 0.463964E+09 |
| September | 0.162978E+10 | 0.929875E+09 | 0.699901E+09 | 0.173722E+10 | 0.819555E+09 |
| October | 0.145670E+10 | 0.901974E+09 | 0.554730E+09 | 0.133626E+10 | 0.121595E+10 |
| November | 0.120426E+10 | 0.783178E+09 | 0.421083E+09 | 0.983447E+09 | 0.161801E+10 |
| December | 0.118705E+10 | 0.785150E+09 | 0.401896E+09 | 0.806418E+09 | 0.259794E+10 |
| Annual Sum or Average | 0.184567E+11 | 0.104725E+11 | 0.798419E+10 | 0.180345E+11 | 0.155717E+11 |
| Minimum of Months | 0.118705E+10 | 0.372128E+09 | 0.401896E+09 | 0.806418E+09 | 0.383287E+09 |
| Maximum of Months | 0.205277E+10 | 0.143944E+10 | 0.886314E+09 | 0.187043E+10 | 0.263140E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.152814E+10 | 0.108058E+10 | 0.447560E+09 | 0.109993E+10 | 0.264868E+10 |
| February | 0.190990E+10 | 0.133864E+10 | 0.571266E+09 | 0.163528E+10 | 0.193060E+10 |
| March | 0.189112E+10 | 0.126133E+10 | 0.629786E+09 | 0.166539E+10 | 0.174326E+10 |
| April | 0.164860E+10 | 0.967212E+09 | 0.681386E+09 | 0.162531E+10 | 0.111987E+10 |
| May | 0.138170E+10 | 0.536285E+09 | 0.845414E+09 | 0.149769E+10 | 0.663804E+09 |
| June | 0.116750E+10 | 0.363580E+09 | 0.803915E+09 | 0.139470E+10 | 0.442295E+09 |
| July | 0.133579E+10 | 0.488699E+09 | 0.847094E+09 | 0.172649E+10 | 0.380204E+09 |
| August | 0.146952E+10 | 0.685340E+09 | 0.784181E+09 | 0.179850E+10 | 0.461776E+09 |
| September | 0.155259E+10 | 0.887699E+09 | 0.664891E+09 | 0.164159E+10 | 0.822771E+09 |
| October | 0.136460E+10 | 0.843351E+09 | 0.521252E+09 | 0.123647E+10 | 0.123147E+10 |
| November | 0.111928E+10 | 0.725240E+09 | 0.394039E+09 | 0.894685E+09 | 0.163003E+10 |
| December | 0.110771E+10 | 0.730367E+09 | 0.377345E+09 | 0.728555E+09 | 0.261282E+10 |
| Annual Sum or Average | 0.174765E+11 | 0.990832E+10 | 0.756813E+10 | 0.169446E+11 | 0.156876E+11 |
| Minimum of Months | 0.110771E+10 | 0.363580E+09 | 0.377345E+09 | 0.728555E+09 | 0.380204E+09 |
| Maximum of Months | 0.190990E+10 | 0.133864E+10 | 0.847094E+09 | 0.179850E+10 | 0.264868E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.103382E+09 | 43290087.88 | 60091432.06 | 29834634.85 | 0.521960E+09 |
| February | 0.152138E+09 | 69486688.70 | 82651674.54 | 83145564.23 | 0.376897E+09 |
| March | 0.221653E+09 | 0.113418E+09 | 0.108234E+09 | 0.155435E+09 | 0.324838E+09 |
| April | 0.274015E+09 | 0.138786E+09 | 0.135229E+09 | 0.241396E+09 | 0.192344E+09 |
| May | 0.347899E+09 | 0.165949E+09 | 0.181950E+09 | 0.372165E+09 | 0.112010E+09 |
| June | 0.324885E+09 | 0.140478E+09 | 0.184407E+09 | 0.373360E+09 | 75771076.40 |
| July | 0.358408E+09 | 0.166623E+09 | 0.191785E+09 | 0.435098E+09 | 67008852.72 |
| August | 0.294946E+09 | 0.134022E+09 | 0.160924E+09 | 0.344384E+09 | 78477185.78 |
| September | 0.223076E+09 | 0.100225E+09 | 0.122851E+09 | 0.213821E+09 | 0.139091E+09 |
| October | 0.145616E+09 | 58456537.20 | 87159171.73 | 0.100572E+09 | 0.216024E+09 |
| November | 85586924.79 | 28856659.36 | 56730265.43 | 33480087.70 | 0.305930E+09 |
| December | 78839157.79 | 27594262.67 | 51244895.12 | 15714326.78 | 0.506431E+09 |
| Annual Sum or Average | 0.261044E+10 | 0.118718E+10 | 0.142326E+10 | 0.239840E+10 | 0.291678E+10 |
| Minimum of Months | 78839157.79 | 27594262.67 | 51244895.12 | 15714326.78 | 67008852.72 |
| Maximum of Months | 0.358408E+09 | 0.166623E+09 | 0.191785E+09 | 0.435098E+09 | 0.521960E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.310144E+09 | 0.129870E+09 | 0.180274E+09 | 95880087.59 | 0.148253E+10 |
| February | 0.456414E+09 | 0.208459E+09 | 0.247954E+09 | 0.260661E+09 | 0.105731E+10 |
| March | 0.664956E+09 | 0.340253E+09 | 0.324702E+09 | 0.483346E+09 | 0.891843E+09 |
| April | 0.822043E+09 | 0.416357E+09 | 0.405686E+09 | 0.755019E+09 | 0.501230E+09 |
| May | 0.104369E+10 | 0.497847E+09 | 0.545847E+09 | 0.114351E+10 | 0.295841E+09 |
| June | 0.974652E+09 | 0.421432E+09 | 0.553220E+09 | 0.114078E+10 | 0.202829E+09 |
| July | 0.107522E+10 | 0.499866E+09 | 0.575354E+09 | 0.132057E+10 | 0.188503E+09 |
| August | 0.884835E+09 | 0.402064E+09 | 0.482771E+09 | 0.104848E+10 | 0.218504E+09 |
| September | 0.669225E+09 | 0.300673E+09 | 0.368552E+09 | 0.660824E+09 | 0.377582E+09 |
| October | 0.436846E+09 | 0.175369E+09 | 0.261477E+09 | 0.316068E+09 | 0.583085E+09 |
| November | 0.256760E+09 | 86569689.51 | 0.170190E+09 | 0.107466E+09 | 0.842206E+09 |
| December | 0.236517E+09 | 82782512.07 | 0.153734E+09 | 51166066.81 | 0.143252E+10 |
| Annual Sum or Average | 0.783130E+10 | 0.356154E+10 | 0.426976E+10 | 0.738377E+10 | 0.807398E+10 |
| Minimum of Months | 0.236517E+09 | 82782512.07 | 0.153734E+09 | 51166066.81 | 0.188503E+09 |
| Maximum of Months | 0.107522E+10 | 0.499866E+09 | 0.575354E+09 | 0.132057E+10 | 0.148253E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 17673401.92 | 0.00 | 17673401.92 | 10198.20 | 0.248514E+09 |
| February | 24293364.76 | 0.00 | 24293364.76 | 574898.22 | 0.179730E+09 |
| March | 32982802.86 | 0.00 | 32982802.86 | 1643805.20 | 0.152765E+09 |
| April | 41995444.83 | 340028.76 | 41655416.08 | 13666339.69 | 81558125.68 |
| May | 62006849.60 | 3676693.63 | 58330155.97 | 47668714.68 | 42779941.71 |
| June | 66742308.11 | 8094363.35 | 58647944.76 | 68598610.69 | 29147428.74 |
| July | 65011991.39 | 6079958.97 | 58932032.42 | 73437630.99 | 26785409.90 |
| August | 49257336.60 | 993198.20 | 48264138.39 | 47926878.31 | 31584703.95 |
| September | 37439116.28 | 8064.32 | 37431051.96 | 19837395.88 | 59286355.62 |
| October | 27358086.69 | 0.00 | 27358086.69 | 3854210.85 | 94280579.30 |
| November | 17423627.03 | 0.00 | 17423627.03 | 736010.71 | 0.138810E+09 |
| December | 15166304.81 | 0.00 | 15166304.81 | 0.00 | 0.235848E+09 |
| Annual Sum or Average | 0.457351E+09 | 19192307.23 | 0.438158E+09 | 0.277955E+09 | 0.132109E+10 |
| Minimum of Months | 15166304.81 | 0.00 | 15166304.81 | 0.00 | 26785409.90 |
| Maximum of Months | 66742308.11 | 8094363.35 | 58932032.42 | 73437630.99 | 0.248514E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.128691E+09 | 0.00 | 0.128691E+09 | 145787.51 | 0.171825E+10 |
| February | 0.177327E+09 | 0.00 | 0.177327E+09 | 5292426.59 | 0.123831E+10 |
| March | 0.240962E+09 | 0.00 | 0.240962E+09 | 14735892.86 | 0.104963E+10 |
| April | 0.306342E+09 | 2359897.74 | 0.303982E+09 | 0.106622E+09 | 0.562373E+09 |
| May | 0.449813E+09 | 25517315.30 | 0.424295E+09 | 0.352793E+09 | 0.298056E+09 |
| June | 0.483713E+09 | 56177218.60 | 0.427536E+09 | 0.500220E+09 | 0.203968E+09 |
| July | 0.472714E+09 | 42196670.61 | 0.430518E+09 | 0.535237E+09 | 0.188102E+09 |
| August | 0.359697E+09 | 6893299.73 | 0.352804E+09 | 0.354206E+09 | 0.220938E+09 |
| September | 0.272912E+09 | 58255.97 | 0.272853E+09 | 0.151971E+09 | 0.411093E+09 |
| October | 0.198491E+09 | 0.00 | 0.198491E+09 | 32128376.01 | 0.650695E+09 |
| November | 0.126613E+09 | 0.00 | 0.126613E+09 | 5577283.30 | 0.959034E+09 |
| December | 0.110071E+09 | 0.00 | 0.110071E+09 | 0.00 | 0.163262E+10 |
| Annual Sum or Average | 0.332735E+10 | 0.133203E+09 | 0.319414E+10 | 0.205893E+10 | 0.913307E+10 |
| Minimum of Months | 0.110071E+09 | 0.00 | 0.110071E+09 | 0.00 | 0.188102E+09 |
| Maximum of Months | 0.483713E+09 | 56177218.60 | 0.430518E+09 | 0.535237E+09 | 0.171825E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.212169E+09 | 0.00 | 0.212169E+09 | 15269.82 | 0.321654E+10 |
| February | 0.291764E+09 | 0.00 | 0.291764E+09 | 4814315.04 | 0.233982E+10 |
| March | 0.396571E+09 | 0.00 | 0.396571E+09 | 14407331.41 | 0.201869E+10 |
| April | 0.501494E+09 | 2045389.47 | 0.499449E+09 | 0.142437E+09 | 0.112612E+10 |
| May | 0.723465E+09 | 29773007.22 | 0.693692E+09 | 0.537979E+09 | 0.604924E+09 |
| June | 0.749701E+09 | 61401361.83 | 0.688300E+09 | 0.751359E+09 | 0.405132E+09 |
| July | 0.740503E+09 | 46343119.10 | 0.694160E+09 | 0.859337E+09 | 0.339376E+09 |
| August | 0.583029E+09 | 7329142.81 | 0.575699E+09 | 0.590203E+09 | 0.402602E+09 |
| September | 0.450008E+09 | 79374.11 | 0.449928E+09 | 0.226812E+09 | 0.780467E+09 |
| October | 0.329037E+09 | 0.00 | 0.329037E+09 | 35560141.08 | 0.127590E+10 |
| November | 0.209166E+09 | 0.00 | 0.209166E+09 | 7740891.41 | 0.184356E+10 |
| December | 0.182204E+09 | 0.00 | 0.182204E+09 | 0.00 | 0.305656E+10 |
| Annual Sum or Average | 0.536911E+10 | 0.146971E+09 | 0.522214E+10 | 0.317067E+10 | 0.174097E+11 |
| Minimum of Months | 0.182204E+09 | 0.00 | 0.182204E+09 | 0.00 | 0.339376E+09 |
| Maximum of Months | 0.749701E+09 | 61401361.83 | 0.694160E+09 | 0.859337E+09 | 0.321654E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.224619E+09 | 0.00 | 0.224619E+09 | 85570.69 | 0.321155E+10 |
| February | 0.308699E+09 | 0.00 | 0.308699E+09 | 6753593.95 | 0.233047E+10 |
| March | 0.419090E+09 | 0.00 | 0.419090E+09 | 18225405.16 | 0.200414E+10 |
| April | 0.532179E+09 | 3622892.51 | 0.528556E+09 | 0.158931E+09 | 0.111280E+10 |
| May | 0.779520E+09 | 41231984.38 | 0.738288E+09 | 0.586914E+09 | 0.586797E+09 |
| June | 0.827453E+09 | 88702405.63 | 0.738750E+09 | 0.847185E+09 | 0.401246E+09 |
| July | 0.810741E+09 | 66553934.19 | 0.744187E+09 | 0.945618E+09 | 0.338515E+09 |
| August | 0.622918E+09 | 10977423.57 | 0.611941E+09 | 0.630725E+09 | 0.398357E+09 |
| September | 0.475602E+09 | 83511.90 | 0.475518E+09 | 0.250965E+09 | 0.780317E+09 |
| October | 0.347797E+09 | 0.00 | 0.347797E+09 | 43440638.28 | 0.126944E+10 |
| November | 0.221477E+09 | 0.00 | 0.221477E+09 | 8728046.32 | 0.183890E+10 |
| December | 0.192801E+09 | 0.00 | 0.192801E+09 | 0.00 | 0.305317E+10 |
| Annual Sum or Average | 0.576290E+10 | 0.211172E+09 | 0.555172E+10 | 0.349757E+10 | 0.173257E+11 |
| Minimum of Months | 0.192801E+09 | 0.00 | 0.192801E+09 | 0.00 | 0.338515E+09 |
| Maximum of Months | 0.827453E+09 | 88702405.63 | 0.744187E+09 | 0.945618E+09 | 0.321155E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.224614E+09 | 0.00 | 0.224614E+09 | 85568.82 | 0.321149E+10 |
| February | 0.308693E+09 | 0.00 | 0.308693E+09 | 6753458.94 | 0.233043E+10 |
| March | 0.419082E+09 | 0.00 | 0.419082E+09 | 18225041.85 | 0.200410E+10 |
| April | 0.533583E+09 | 4301356.44 | 0.529282E+09 | 0.158959E+09 | 0.111037E+10 |
| May | 0.785151E+09 | 44886019.59 | 0.740265E+09 | 0.590952E+09 | 0.582606E+09 |
| June | 0.834008E+09 | 93208311.40 | 0.740799E+09 | 0.851897E+09 | 0.396906E+09 |
| July | 0.817082E+09 | 70950069.56 | 0.746132E+09 | 0.951318E+09 | 0.335268E+09 |
| August | 0.625778E+09 | 12604920.37 | 0.613173E+09 | 0.632684E+09 | 0.395942E+09 |
| September | 0.475765E+09 | 100735.96 | 0.475665E+09 | 0.250960E+09 | 0.780041E+09 |
| October | 0.347790E+09 | 0.00 | 0.347790E+09 | 43439780.14 | 0.126941E+10 |
| November | 0.221473E+09 | 0.00 | 0.221473E+09 | 8727875.57 | 0.183886E+10 |
| December | 0.192798E+09 | 0.00 | 0.192798E+09 | 0.00 | 0.305311E+10 |
| Annual Sum or Average | 0.578582E+10 | 0.226051E+09 | 0.555977E+10 | 0.351400E+10 | 0.173085E+11 |
| Minimum of Months | 0.192798E+09 | 0.00 | 0.192798E+09 | 0.00 | 0.335268E+09 |
| Maximum of Months | 0.834008E+09 | 93208311.40 | 0.746132E+09 | 0.951318E+09 | 0.321149E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.310144E+09 | 0.129870E+09 | 0.180274E+09 | 92026513.84 | 0.149418E+10 |
| February | 0.456414E+09 | 0.208459E+09 | 0.247954E+09 | 0.250939E+09 | 0.107352E+10 |
| March | 0.664956E+09 | 0.340253E+09 | 0.324702E+09 | 0.468119E+09 | 0.912591E+09 |
| April | 0.822043E+09 | 0.416357E+09 | 0.405686E+09 | 0.727341E+09 | 0.529651E+09 |
| May | 0.104369E+10 | 0.497847E+09 | 0.545847E+09 | 0.112481E+10 | 0.310822E+09 |
| June | 0.974652E+09 | 0.421432E+09 | 0.553220E+09 | 0.113083E+10 | 0.209088E+09 |
| July | 0.107522E+10 | 0.499866E+09 | 0.575354E+09 | 0.129896E+10 | 0.202148E+09 |
| August | 0.884835E+09 | 0.402064E+09 | 0.482771E+09 | 0.101987E+10 | 0.242179E+09 |
| September | 0.669225E+09 | 0.300673E+09 | 0.368552E+09 | 0.632937E+09 | 0.409794E+09 |
| October | 0.436846E+09 | 0.175369E+09 | 0.261477E+09 | 0.296589E+09 | 0.623154E+09 |
| November | 0.256760E+09 | 86569689.51 | 0.170190E+09 | 99625124.77 | 0.864932E+09 |
| December | 0.236517E+09 | 82782512.07 | 0.153734E+09 | 48642314.62 | 0.144245E+10 |
| Annual Sum or Average | 0.783130E+10 | 0.356154E+10 | 0.426976E+10 | 0.719069E+10 | 0.831450E+10 |
| Minimum of Months | 0.236517E+09 | 82782512.07 | 0.153734E+09 | 48642314.62 | 0.202148E+09 |
| Maximum of Months | 0.107522E+10 | 0.499866E+09 | 0.575354E+09 | 0.129896E+10 | 0.149418E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.140117E+09 | 98686033.49 | 41431258.09 | 0.103619E+09 | 0.197455E+09 |
| February | 0.165237E+09 | 0.113916E+09 | 51321239.29 | 0.143363E+09 | 0.144312E+09 |
| March | 0.160856E+09 | 0.104747E+09 | 56108514.00 | 0.144462E+09 | 0.129627E+09 |
| April | 0.139373E+09 | 78766283.30 | 60606872.35 | 0.139857E+09 | 81503985.58 |
| May | 0.118558E+09 | 43101517.15 | 75455993.50 | 0.129960E+09 | 49133557.72 |
| June | 0.101558E+09 | 29179634.64 | 72378661.79 | 0.121405E+09 | 32812868.84 |
| July | 0.115375E+09 | 39181341.40 | 76193338.73 | 0.145896E+09 | 30969823.66 |
| August | 0.125198E+09 | 55249543.34 | 69948668.05 | 0.151017E+09 | 37289103.91 |
| September | 0.131872E+09 | 72918668.32 | 58953505.46 | 0.140600E+09 | 62547666.45 |
| October | 0.117192E+09 | 70876607.51 | 46315151.30 | 0.108207E+09 | 90537992.95 |
| November | 0.100077E+09 | 64185011.54 | 35892470.94 | 81824205.58 | 0.119642E+09 |
| December | 0.105611E+09 | 69589725.68 | 36021186.07 | 71368675.97 | 0.193189E+09 |
| Annual Sum or Average | 0.152102E+10 | 0.840398E+09 | 0.680627E+09 | 0.148158E+10 | 0.116902E+10 |
| Minimum of Months | 0.100077E+09 | 29179634.64 | 35892470.94 | 71368675.97 | 30969823.66 |
| Maximum of Months | 0.165237E+09 | 0.113916E+09 | 76193338.73 | 0.151017E+09 | 0.197455E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.963293E+09 | 0.683586E+09 | 0.279707E+09 | 0.710889E+09 | 0.136789E+10 |
| February | 0.113595E+10 | 0.790609E+09 | 0.345336E+09 | 0.984310E+09 | 0.999090E+09 |
| March | 0.110138E+10 | 0.726972E+09 | 0.374411E+09 | 0.988414E+09 | 0.898877E+09 |
| April | 0.948785E+09 | 0.546661E+09 | 0.402124E+09 | 0.952808E+09 | 0.565532E+09 |
| May | 0.798616E+09 | 0.299137E+09 | 0.499479E+09 | 0.874771E+09 | 0.341863E+09 |
| June | 0.679349E+09 | 0.202515E+09 | 0.476834E+09 | 0.811208E+09 | 0.227812E+09 |
| July | 0.773983E+09 | 0.271930E+09 | 0.502053E+09 | 0.979590E+09 | 0.213953E+09 |
| August | 0.846736E+09 | 0.383448E+09 | 0.463288E+09 | 0.102271E+10 | 0.257785E+09 |
| September | 0.898989E+09 | 0.506077E+09 | 0.392913E+09 | 0.957970E+09 | 0.432509E+09 |
| October | 0.802628E+09 | 0.491904E+09 | 0.310724E+09 | 0.740487E+09 | 0.626284E+09 |
| November | 0.686362E+09 | 0.444545E+09 | 0.241817E+09 | 0.560397E+09 | 0.827826E+09 |
| December | 0.720091E+09 | 0.477932E+09 | 0.242159E+09 | 0.483784E+09 | 0.134022E+10 |
| Annual Sum or Average | 0.103562E+11 | 0.582531E+10 | 0.453085E+10 | 0.100673E+11 | 0.809965E+10 |
| Minimum of Months | 0.679349E+09 | 0.202515E+09 | 0.241817E+09 | 0.483784E+09 | 0.213953E+09 |
| Maximum of Months | 0.113595E+10 | 0.790609E+09 | 0.502053E+09 | 0.102271E+10 | 0.136789E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.170035E+10 | 0.120827E+10 | 0.492084E+09 | 0.126355E+10 | 0.260358E+10 |
| February | 0.207451E+10 | 0.145062E+10 | 0.623888E+09 | 0.179256E+10 | 0.188201E+10 |
| March | 0.201062E+10 | 0.133590E+10 | 0.674725E+09 | 0.179183E+10 | 0.171728E+10 |
| April | 0.172714E+10 | 0.100457E+10 | 0.722572E+09 | 0.171448E+10 | 0.111863E+10 |
| May | 0.144613E+10 | 0.549709E+09 | 0.896425E+09 | 0.157108E+10 | 0.670005E+09 |
| June | 0.122582E+10 | 0.372152E+09 | 0.853671E+09 | 0.146024E+10 | 0.447846E+09 |
| July | 0.139861E+10 | 0.499712E+09 | 0.898903E+09 | 0.179712E+10 | 0.389564E+09 |
| August | 0.153636E+10 | 0.704643E+09 | 0.831718E+09 | 0.187721E+10 | 0.471109E+09 |
| September | 0.163764E+10 | 0.929992E+09 | 0.707650E+09 | 0.174211E+10 | 0.827107E+09 |
| October | 0.146492E+10 | 0.903741E+09 | 0.561179E+09 | 0.133851E+10 | 0.122268E+10 |
| November | 0.123086E+10 | 0.799773E+09 | 0.431083E+09 | 0.999876E+09 | 0.160725E+10 |
| December | 0.124762E+10 | 0.829230E+09 | 0.418391E+09 | 0.852921E+09 | 0.257051E+10 |
| Annual Sum or Average | 0.187006E+11 | 0.105883E+11 | 0.811229E+10 | 0.182015E+11 | 0.155276E+11 |
| Minimum of Months | 0.122582E+10 | 0.372152E+09 | 0.418391E+09 | 0.852921E+09 | 0.389564E+09 |
| Maximum of Months | 0.207451E+10 | 0.145062E+10 | 0.898903E+09 | 0.187721E+10 | 0.260358E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.169600E+10 | 0.120501E+10 | 0.490987E+09 | 0.126346E+10 | 0.260917E+10 |
| February | 0.206541E+10 | 0.144469E+10 | 0.620720E+09 | 0.179114E+10 | 0.189370E+10 |
| March | 0.200973E+10 | 0.133550E+10 | 0.674236E+09 | 0.179171E+10 | 0.171852E+10 |
| April | 0.172703E+10 | 0.100451E+10 | 0.722524E+09 | 0.171437E+10 | 0.111855E+10 |
| May | 0.144604E+10 | 0.549673E+09 | 0.896365E+09 | 0.157098E+10 | 0.669961E+09 |
| June | 0.122574E+10 | 0.372128E+09 | 0.853614E+09 | 0.146014E+10 | 0.447816E+09 |
| July | 0.139852E+10 | 0.499679E+09 | 0.898842E+09 | 0.179700E+10 | 0.389538E+09 |
| August | 0.153626E+10 | 0.704597E+09 | 0.831662E+09 | 0.187709E+10 | 0.471078E+09 |
| September | 0.163746E+10 | 0.929912E+09 | 0.707551E+09 | 0.174195E+10 | 0.827114E+09 |
| October | 0.146301E+10 | 0.902759E+09 | 0.560250E+09 | 0.133829E+10 | 0.122530E+10 |
| November | 0.122566E+10 | 0.796449E+09 | 0.429216E+09 | 0.999254E+09 | 0.161363E+10 |
| December | 0.124567E+10 | 0.827924E+09 | 0.417748E+09 | 0.852858E+09 | 0.257285E+10 |
| Annual Sum or Average | 0.186765E+11 | 0.105728E+11 | 0.810372E+10 | 0.181982E+11 | 0.155572E+11 |
| Minimum of Months | 0.122566E+10 | 0.372128E+09 | 0.417748E+09 | 0.852858E+09 | 0.389538E+09 |
| Maximum of Months | 0.206541E+10 | 0.144469E+10 | 0.898842E+09 | 0.187709E+10 | 0.260917E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.156587E+10 | 0.110877E+10 | 0.457101E+09 | 0.112649E+10 | 0.262945E+10 |
| February | 0.191757E+10 | 0.134155E+10 | 0.576018E+09 | 0.164052E+10 | 0.192755E+10 |
| March | 0.189595E+10 | 0.126126E+10 | 0.634692E+09 | 0.166954E+10 | 0.174335E+10 |
| April | 0.165461E+10 | 0.967160E+09 | 0.687448E+09 | 0.162906E+10 | 0.112328E+10 |
| May | 0.138960E+10 | 0.536255E+09 | 0.853347E+09 | 0.150300E+10 | 0.668466E+09 |
| June | 0.117584E+10 | 0.363561E+09 | 0.812275E+09 | 0.140029E+10 | 0.446333E+09 |
| July | 0.134454E+10 | 0.488671E+09 | 0.855866E+09 | 0.173061E+10 | 0.386196E+09 |
| August | 0.147675E+10 | 0.685300E+09 | 0.791447E+09 | 0.180158E+10 | 0.468669E+09 |
| September | 0.155790E+10 | 0.887670E+09 | 0.670228E+09 | 0.164375E+10 | 0.830101E+09 |
| October | 0.136864E+10 | 0.843616E+09 | 0.525024E+09 | 0.123648E+10 | 0.124093E+10 |
| November | 0.113444E+10 | 0.734760E+09 | 0.399679E+09 | 0.904989E+09 | 0.162749E+10 |
| December | 0.115317E+10 | 0.763530E+09 | 0.389641E+09 | 0.761533E+09 | 0.259037E+10 |
| Annual Sum or Average | 0.176349E+11 | 0.998210E+10 | 0.765277E+10 | 0.170478E+11 | 0.156822E+11 |
| Minimum of Months | 0.113444E+10 | 0.363561E+09 | 0.389641E+09 | 0.761533E+09 | 0.386196E+09 |
| Maximum of Months | 0.191757E+10 | 0.134155E+10 | 0.855866E+09 | 0.180158E+10 | 0.262945E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.103382E+09 | 43290087.88 | 60091432.06 | 29813216.53 | 0.522223E+09 |
| February | 0.152138E+09 | 69486688.70 | 82651674.54 | 83104980.25 | 0.377112E+09 |
| March | 0.221653E+09 | 0.113418E+09 | 0.108234E+09 | 0.155301E+09 | 0.325247E+09 |
| April | 0.274015E+09 | 0.138786E+09 | 0.135229E+09 | 0.240551E+09 | 0.193953E+09 |
| May | 0.347899E+09 | 0.165949E+09 | 0.181950E+09 | 0.370710E+09 | 0.113742E+09 |
| June | 0.324885E+09 | 0.140478E+09 | 0.184407E+09 | 0.371840E+09 | 77233058.08 |
| July | 0.358408E+09 | 0.166623E+09 | 0.191785E+09 | 0.432745E+09 | 68989666.54 |
| August | 0.294946E+09 | 0.134022E+09 | 0.160924E+09 | 0.342371E+09 | 80706289.13 |
| September | 0.223076E+09 | 0.100225E+09 | 0.122851E+09 | 0.212409E+09 | 0.141639E+09 |
| October | 0.145616E+09 | 58456537.20 | 87159171.73 | 99677388.91 | 0.219178E+09 |
| November | 85586924.79 | 28856659.36 | 56730265.43 | 33348502.07 | 0.307177E+09 |
| December | 78839157.79 | 27594262.67 | 51244895.12 | 15696002.91 | 0.506751E+09 |
| Annual Sum or Average | 0.261044E+10 | 0.118718E+10 | 0.142326E+10 | 0.238757E+10 | 0.293395E+10 |
| Minimum of Months | 78839157.79 | 27594262.67 | 51244895.12 | 15696002.91 | 68989666.54 |
| Maximum of Months | 0.358408E+09 | 0.166623E+09 | 0.191785E+09 | 0.432745E+09 | 0.522223E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 21544206.81 | 0.00 | 21544206.81 | 86410.41 | 0.246792E+09 |
| February | 29890973.90 | 0.00 | 29890973.90 | 1405773.30 | 0.176427E+09 |
| March | 40715907.16 | 0.00 | 40715907.16 | 3969190.86 | 0.148301E+09 |
| April | 51654236.22 | 403152.34 | 51251083.88 | 20918150.35 | 80110194.85 |
| May | 75071323.35 | 4042455.41 | 71028867.94 | 61108674.10 | 43459048.88 |
| June | 81078156.84 | 8912605.52 | 72165551.32 | 83910975.12 | 29714991.26 |
| July | 80023841.43 | 6867522.74 | 73156318.70 | 89401537.24 | 27930519.58 |
| August | 60780641.16 | 1043783.07 | 59736858.09 | 60603026.22 | 33190920.76 |
| September | 45836677.24 | 11235.98 | 45825441.26 | 27952250.46 | 60069938.04 |
| October | 32887521.96 | 0.00 | 32887521.96 | 7063127.80 | 93936922.17 |
| November | 21073267.63 | 0.00 | 21073267.63 | 1072624.49 | 0.137548E+09 |
| December | 18253967.66 | 0.00 | 18253967.66 | 0.00 | 0.234856E+09 |
| Annual Sum or Average | 0.558811E+09 | 21280755.05 | 0.537530E+09 | 0.357492E+09 | 0.131234E+10 |
| Minimum of Months | 18253967.66 | 0.00 | 18253967.66 | 0.00 | 27930519.58 |
| Maximum of Months | 81078156.84 | 8912605.52 | 73156318.70 | 89401537.24 | 0.246792E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.310144E+09 | 0.129870E+09 | 0.180274E+09 | 95824203.11 | 0.148262E+10 |
| February | 0.456414E+09 | 0.208459E+09 | 0.247954E+09 | 0.260461E+09 | 0.105752E+10 |
| March | 0.664956E+09 | 0.340253E+09 | 0.324702E+09 | 0.482843E+09 | 0.892330E+09 |
| April | 0.822043E+09 | 0.416357E+09 | 0.405686E+09 | 0.753214E+09 | 0.503023E+09 |
| May | 0.104369E+10 | 0.497847E+09 | 0.545847E+09 | 0.113981E+10 | 0.298646E+09 |
| June | 0.974652E+09 | 0.421432E+09 | 0.553220E+09 | 0.113651E+10 | 0.205296E+09 |
| July | 0.107522E+10 | 0.499866E+09 | 0.575354E+09 | 0.131455E+10 | 0.192119E+09 |
| August | 0.884835E+09 | 0.402064E+09 | 0.482771E+09 | 0.104426E+10 | 0.222015E+09 |
| September | 0.669225E+09 | 0.300673E+09 | 0.368552E+09 | 0.657847E+09 | 0.381222E+09 |
| October | 0.436846E+09 | 0.175369E+09 | 0.261477E+09 | 0.314596E+09 | 0.586267E+09 |
| November | 0.256760E+09 | 86569689.51 | 0.170190E+09 | 0.107269E+09 | 0.842890E+09 |
| December | 0.236517E+09 | 82782512.07 | 0.153734E+09 | 51136416.39 | 0.143258E+10 |
| Annual Sum or Average | 0.783130E+10 | 0.356154E+10 | 0.426976E+10 | 0.735831E+10 | 0.809652E+10 |
| Minimum of Months | 0.236517E+09 | 82782512.07 | 0.153734E+09 | 51136416.39 | 0.192119E+09 |
| Maximum of Months | 0.107522E+10 | 0.499866E+09 | 0.575354E+09 | 0.131455E+10 | 0.148262E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.148928E+09 | 0.00 | 0.148928E+09 | 613347.06 | 0.170228E+10 |
| February | 0.206626E+09 | 0.00 | 0.206626E+09 | 9990953.14 | 0.121604E+10 |
| March | 0.281455E+09 | 0.00 | 0.281455E+09 | 28002095.52 | 0.102263E+10 |
| April | 0.357068E+09 | 2786850.06 | 0.354281E+09 | 0.145609E+09 | 0.553512E+09 |
| May | 0.518942E+09 | 27944069.83 | 0.490998E+09 | 0.423010E+09 | 0.300418E+09 |
| June | 0.560466E+09 | 61609701.47 | 0.498856E+09 | 0.580358E+09 | 0.205410E+09 |
| July | 0.553177E+09 | 47472764.83 | 0.505705E+09 | 0.618522E+09 | 0.193075E+09 |
| August | 0.420156E+09 | 7215304.59 | 0.412941E+09 | 0.419870E+09 | 0.229438E+09 |
| September | 0.316853E+09 | 77670.37 | 0.316776E+09 | 0.194644E+09 | 0.414987E+09 |
| October | 0.227340E+09 | 0.00 | 0.227340E+09 | 49735213.72 | 0.647910E+09 |
| November | 0.145672E+09 | 0.00 | 0.145672E+09 | 7446401.82 | 0.948760E+09 |
| December | 0.126183E+09 | 0.00 | 0.126183E+09 | 0.00 | 0.162084E+10 |
| Annual Sum or Average | 0.386287E+10 | 0.147106E+09 | 0.371576E+10 | 0.247780E+10 | 0.905531E+10 |
| Minimum of Months | 0.126183E+09 | 0.00 | 0.126183E+09 | 0.00 | 0.193075E+09 |
| Maximum of Months | 0.560466E+09 | 61609701.47 | 0.505705E+09 | 0.618522E+09 | 0.170228E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.181439E+09 | 0.00 | 0.181439E+09 | 658995.80 | 0.210583E+10 |
| February | 0.251732E+09 | 0.00 | 0.251732E+09 | 11318354.08 | 0.151047E+10 |
| March | 0.342897E+09 | 0.00 | 0.342897E+09 | 30453719.46 | 0.128391E+10 |
| April | 0.435016E+09 | 3395218.23 | 0.431621E+09 | 0.164066E+09 | 0.718667E+09 |
| May | 0.632227E+09 | 34044248.21 | 0.598183E+09 | 0.504629E+09 | 0.389689E+09 |
| June | 0.682815E+09 | 75059072.69 | 0.607756E+09 | 0.700360E+09 | 0.265445E+09 |
| July | 0.673936E+09 | 57836048.90 | 0.616100E+09 | 0.769412E+09 | 0.232105E+09 |
| August | 0.511876E+09 | 8790402.47 | 0.503085E+09 | 0.524557E+09 | 0.276013E+09 |
| September | 0.386022E+09 | 94625.77 | 0.385928E+09 | 0.233812E+09 | 0.523017E+09 |
| October | 0.276968E+09 | 0.00 | 0.276968E+09 | 53735929.46 | 0.835670E+09 |
| November | 0.177472E+09 | 0.00 | 0.177472E+09 | 8240948.17 | 0.120364E+10 |
| December | 0.153729E+09 | 0.00 | 0.153729E+09 | 0.00 | 0.200748E+10 |
| Annual Sum or Average | 0.470613E+10 | 0.179220E+09 | 0.452691E+10 | 0.300124E+10 | 0.113519E+11 |
| Minimum of Months | 0.153729E+09 | 0.00 | 0.153729E+09 | 0.00 | 0.232105E+09 |
| Maximum of Months | 0.682815E+09 | 75059072.69 | 0.616100E+09 | 0.769412E+09 | 0.210583E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.181437E+09 | 0.00 | 0.181437E+09 | 658964.06 | 0.210583E+10 |
| February | 0.251731E+09 | 0.00 | 0.251731E+09 | 11318072.22 | 0.151047E+10 |
| March | 0.342895E+09 | 0.00 | 0.342895E+09 | 30453081.48 | 0.128391E+10 |
| April | 0.435014E+09 | 3395186.85 | 0.431618E+09 | 0.164064E+09 | 0.718667E+09 |
| May | 0.632223E+09 | 34043933.58 | 0.598179E+09 | 0.504625E+09 | 0.389689E+09 |
| June | 0.682811E+09 | 75058379.03 | 0.607752E+09 | 0.700355E+09 | 0.265445E+09 |
| July | 0.673932E+09 | 57835514.40 | 0.616096E+09 | 0.769407E+09 | 0.232105E+09 |
| August | 0.511873E+09 | 8790321.23 | 0.503082E+09 | 0.524553E+09 | 0.276013E+09 |
| September | 0.386020E+09 | 94624.90 | 0.385925E+09 | 0.233810E+09 | 0.523016E+09 |
| October | 0.276967E+09 | 0.00 | 0.276967E+09 | 53734867.78 | 0.835670E+09 |
| November | 0.177471E+09 | 0.00 | 0.177471E+09 | 8240800.83 | 0.120364E+10 |
| December | 0.153728E+09 | 0.00 | 0.153728E+09 | 0.00 | 0.200748E+10 |
| Annual Sum or Average | 0.470610E+10 | 0.179218E+09 | 0.452688E+10 | 0.300122E+10 | 0.113519E+11 |
| Minimum of Months | 0.153728E+09 | 0.00 | 0.153728E+09 | 0.00 | 0.232105E+09 |
| Maximum of Months | 0.682811E+09 | 75058379.03 | 0.616096E+09 | 0.769407E+09 | 0.210583E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.181432E+09 | 0.00 | 0.181432E+09 | 658961.69 | 0.210576E+10 |
| February | 0.251723E+09 | 0.00 | 0.251723E+09 | 11317868.33 | 0.151042E+10 |
| March | 0.342884E+09 | 0.00 | 0.342884E+09 | 30452458.22 | 0.128387E+10 |
| April | 0.435001E+09 | 3395092.72 | 0.431605E+09 | 0.164060E+09 | 0.718643E+09 |
| May | 0.632205E+09 | 34042989.72 | 0.598162E+09 | 0.504611E+09 | 0.389676E+09 |
| June | 0.682790E+09 | 75056298.05 | 0.607734E+09 | 0.700335E+09 | 0.265436E+09 |
| July | 0.673912E+09 | 57833910.92 | 0.616078E+09 | 0.769385E+09 | 0.232098E+09 |
| August | 0.511857E+09 | 8790077.52 | 0.503067E+09 | 0.524538E+09 | 0.276004E+09 |
| September | 0.386008E+09 | 94622.28 | 0.385914E+09 | 0.233803E+09 | 0.522999E+09 |
| October | 0.276958E+09 | 0.00 | 0.276958E+09 | 53733728.33 | 0.835642E+09 |
| November | 0.177466E+09 | 0.00 | 0.177466E+09 | 8240616.48 | 0.120360E+10 |
| December | 0.153724E+09 | 0.00 | 0.153724E+09 | 0.00 | 0.200741E+10 |
| Annual Sum or Average | 0.470596E+10 | 0.179213E+09 | 0.452675E+10 | 0.300114E+10 | 0.113516E+11 |
| Minimum of Months | 0.153724E+09 | 0.00 | 0.153724E+09 | 0.00 | 0.232098E+09 |
| Maximum of Months | 0.682790E+09 | 75056298.05 | 0.616078E+09 | 0.769385E+09 | 0.210576E+10 |
Report: WindowEnergyReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 20459966.68 | 0.00 | 20459966.68 | 70828.81 | 0.238784E+09 |
| February | 28386654.92 | 0.00 | 28386654.92 | 1230694.24 | 0.171749E+09 |
| March | 38666783.41 | 0.00 | 38666783.41 | 3162264.29 | 0.147108E+09 |
| April | 49054591.69 | 382865.22 | 48671726.47 | 16938465.62 | 85480187.30 |
| May | 71293218.46 | 3839034.07 | 67454184.39 | 54449268.35 | 47180293.49 |
| June | 76997771.65 | 8464112.23 | 68533659.43 | 76447458.37 | 32340632.25 |
| July | 75996486.00 | 6521940.53 | 69474545.47 | 83075537.89 | 28714128.96 |
| August | 57721720.11 | 991258.62 | 56730461.48 | 55798060.94 | 34524893.42 |
| September | 43529854.54 | 10670.57 | 43519183.97 | 24252308.52 | 64018593.81 |
| October | 31232418.79 | 0.00 | 31232418.79 | 5152757.05 | 0.100596E+09 |
| November | 20012736.24 | 0.00 | 20012736.24 | 830630.44 | 0.139657E+09 |
| December | 17335320.31 | 0.00 | 17335320.31 | 0.00 | 0.228032E+09 |
| Annual Sum or Average | 0.530688E+09 | 20209881.24 | 0.510478E+09 | 0.321408E+09 | 0.131818E+10 |
| Minimum of Months | 17335320.31 | 0.00 | 17335320.31 | 0.00 | 28714128.96 |
| Maximum of Months | 76997771.65 | 8464112.23 | 69474545.47 | 83075537.89 | 0.238784E+09 |
Report: WindowEnergyReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.259468E+09 | 0.00 | 0.259468E+09 | 898233.84 | 0.302820E+10 |
| February | 0.359993E+09 | 0.00 | 0.359993E+09 | 15607367.23 | 0.217808E+10 |
| March | 0.490363E+09 | 0.00 | 0.490363E+09 | 40103072.07 | 0.186559E+10 |
| April | 0.622098E+09 | 4855404.22 | 0.617243E+09 | 0.214810E+09 | 0.108404E+10 |
| May | 0.904123E+09 | 48685703.08 | 0.855438E+09 | 0.690512E+09 | 0.598329E+09 |
| June | 0.976467E+09 | 0.107340E+09 | 0.869127E+09 | 0.969488E+09 | 0.410136E+09 |
| July | 0.963769E+09 | 82709674.98 | 0.881059E+09 | 0.105354E+10 | 0.364146E+09 |
| August | 0.732013E+09 | 12570902.49 | 0.719442E+09 | 0.707618E+09 | 0.437836E+09 |
| September | 0.552035E+09 | 135321.61 | 0.551900E+09 | 0.307562E+09 | 0.811868E+09 |
| October | 0.396082E+09 | 0.00 | 0.396082E+09 | 65346020.70 | 0.127574E+10 |
| November | 0.253797E+09 | 0.00 | 0.253797E+09 | 10533854.69 | 0.177109E+10 |
| December | 0.219842E+09 | 0.00 | 0.219842E+09 | 0.00 | 0.289184E+10 |
| Annual Sum or Average | 0.673005E+10 | 0.256297E+09 | 0.647375E+10 | 0.407602E+10 | 0.167169E+11 |
| Minimum of Months | 0.219842E+09 | 0.00 | 0.219842E+09 | 0.00 | 0.364146E+09 |
| Maximum of Months | 0.976467E+09 | 0.107340E+09 | 0.881059E+09 | 0.105354E+10 | 0.302820E+10 |
Report: WindowEnergyReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 30618453.60 | 11773947.07 | 18844506.53 | 6335623.51 | 0.249953E+09 |
| February | 57556474.82 | 29261369.01 | 28295105.81 | 33529867.31 | 0.180006E+09 |
| March | 92569127.17 | 54007962.36 | 38561164.82 | 69246437.41 | 0.155924E+09 |
| April | 0.106216E+09 | 59055997.60 | 47160255.84 | 94869910.66 | 96705536.99 |
| May | 0.118529E+09 | 57824720.06 | 60703936.27 | 0.122532E+09 | 57452527.04 |
| June | 0.106633E+09 | 45904247.51 | 60728589.73 | 0.120279E+09 | 39821724.35 |
| July | 0.122773E+09 | 58237236.06 | 64535759.33 | 0.147179E+09 | 34959959.69 |
| August | 0.109965E+09 | 54480957.00 | 55484388.17 | 0.126864E+09 | 40568251.58 |
| September | 89362906.44 | 46160974.68 | 43201931.77 | 85257140.81 | 66787375.98 |
| October | 57186855.89 | 27105620.68 | 30081235.21 | 42034091.27 | 0.101649E+09 |
| November | 27838275.69 | 9626923.26 | 18211352.43 | 10641310.58 | 0.145668E+09 |
| December | 20532776.77 | 5426502.38 | 15106274.38 | 1581631.82 | 0.243472E+09 |
| Annual Sum or Average | 0.939781E+09 | 0.458866E+09 | 0.480915E+09 | 0.860349E+09 | 0.141297E+10 |
| Minimum of Months | 20532776.77 | 5426502.38 | 15106274.38 | 1581631.82 | 34959959.69 |
| Maximum of Months | 0.122773E+09 | 59055997.60 | 64535759.33 | 0.147179E+09 | 0.249953E+09 |
Report: WindowEnergyReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 97514975.03 | 5592555.76 | 91922419.27 | 0.00 | 0.139412E+10 |
| February | 0.177295E+09 | 41867173.57 | 0.135428E+09 | 27034336.01 | 0.984188E+09 |
| March | 0.370567E+09 | 0.170519E+09 | 0.200048E+09 | 0.199992E+09 | 0.826708E+09 |
| April | 0.558300E+09 | 0.292387E+09 | 0.265913E+09 | 0.471492E+09 | 0.501474E+09 |
| May | 0.735570E+09 | 0.374695E+09 | 0.360875E+09 | 0.767762E+09 | 0.298705E+09 |
| June | 0.677760E+09 | 0.314028E+09 | 0.363731E+09 | 0.767541E+09 | 0.207835E+09 |
| July | 0.755252E+09 | 0.375652E+09 | 0.379600E+09 | 0.901148E+09 | 0.185755E+09 |
| August | 0.610761E+09 | 0.294423E+09 | 0.316338E+09 | 0.694043E+09 | 0.213781E+09 |
| September | 0.424257E+09 | 0.188606E+09 | 0.235650E+09 | 0.375891E+09 | 0.352390E+09 |
| October | 0.217934E+09 | 63238687.57 | 0.154695E+09 | 0.103921E+09 | 0.541987E+09 |
| November | 98969116.75 | 7538879.67 | 91430237.08 | 5175499.05 | 0.797962E+09 |
| December | 78488607.53 | 1184154.60 | 77304452.93 | 0.00 | 0.133714E+10 |
| Annual Sum or Average | 0.480267E+10 | 0.212973E+10 | 0.267294E+10 | 0.431400E+10 | 0.764204E+10 |
| Minimum of Months | 78488607.53 | 1184154.60 | 77304452.93 | 0.00 | 0.185755E+09 |
| Maximum of Months | 0.755252E+09 | 0.375652E+09 | 0.379600E+09 | 0.901148E+09 | 0.139412E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.140308E+09 | 97609040.06 | 42698823.29 | 0.114004E+09 | 0.165609E+09 |
| February | 0.160470E+09 | 0.108387E+09 | 52083016.16 | 0.148299E+09 | 0.125431E+09 |
| March | 0.156543E+09 | 99069998.81 | 57473034.18 | 0.148091E+09 | 0.113581E+09 |
| April | 0.137248E+09 | 74494395.23 | 62753640.49 | 0.141395E+09 | 74276411.01 |
| May | 0.119236E+09 | 40763907.08 | 78471956.75 | 0.132491E+09 | 46933254.66 |
| June | 0.103537E+09 | 27597077.64 | 75939641.54 | 0.123139E+09 | 32548371.51 |
| July | 0.116973E+09 | 37056341.99 | 79916169.76 | 0.145520E+09 | 31631574.00 |
| August | 0.124920E+09 | 52253085.27 | 72666885.06 | 0.150678E+09 | 36349174.09 |
| September | 0.129492E+09 | 68963991.83 | 60527607.86 | 0.141607E+09 | 56755606.19 |
| October | 0.114263E+09 | 67203501.39 | 47059038.79 | 0.109386E+09 | 80311252.06 |
| November | 98499438.34 | 61818371.80 | 36681066.54 | 83858026.09 | 0.105227E+09 |
| December | 0.108334E+09 | 71036228.70 | 37298257.24 | 79070154.20 | 0.160189E+09 |
| Annual Sum or Average | 0.150982E+10 | 0.806253E+09 | 0.703569E+09 | 0.151754E+10 | 0.102884E+10 |
| Minimum of Months | 98499438.34 | 27597077.64 | 36681066.54 | 79070154.20 | 31631574.00 |
| Maximum of Months | 0.160470E+09 | 0.108387E+09 | 79916169.76 | 0.150678E+09 | 0.165609E+09 |
Report: WindowEnergyReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.189443E+10 | 0.131791E+10 | 0.576518E+09 | 0.153928E+10 | 0.223604E+10 |
| February | 0.216666E+10 | 0.146344E+10 | 0.703223E+09 | 0.200233E+10 | 0.169356E+10 |
| March | 0.211364E+10 | 0.133764E+10 | 0.775999E+09 | 0.199952E+10 | 0.153357E+10 |
| April | 0.185312E+10 | 0.100582E+10 | 0.847298E+09 | 0.190912E+10 | 0.100288E+10 |
| May | 0.160992E+10 | 0.550393E+09 | 0.105953E+10 | 0.178888E+10 | 0.633691E+09 |
| June | 0.139795E+10 | 0.372615E+09 | 0.102533E+10 | 0.166262E+10 | 0.439467E+09 |
| July | 0.157936E+10 | 0.500334E+09 | 0.107903E+10 | 0.196481E+10 | 0.427089E+09 |
| August | 0.168667E+10 | 0.705520E+09 | 0.981146E+09 | 0.203445E+10 | 0.490785E+09 |
| September | 0.174839E+10 | 0.931150E+09 | 0.817242E+09 | 0.191197E+10 | 0.766312E+09 |
| October | 0.154277E+10 | 0.907380E+09 | 0.635390E+09 | 0.147693E+10 | 0.108436E+10 |
| November | 0.132994E+10 | 0.834670E+09 | 0.495267E+09 | 0.113225E+10 | 0.142077E+10 |
| December | 0.146273E+10 | 0.959129E+09 | 0.503600E+09 | 0.106760E+10 | 0.216287E+10 |
| Annual Sum or Average | 0.203856E+11 | 0.108860E+11 | 0.949957E+10 | 0.204898E+11 | 0.138914E+11 |
| Minimum of Months | 0.132994E+10 | 0.372615E+09 | 0.495267E+09 | 0.106760E+10 | 0.427089E+09 |
| Maximum of Months | 0.216666E+10 | 0.146344E+10 | 0.107903E+10 | 0.203445E+10 | 0.223604E+10 |
Report: WindowEnergyReportMonthly
For: BATH_ZN_1_FLR_1_WALL_5_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.165661E+09 | 34353862.88 | 0.131308E+09 | 3142631.86 | 0.168390E+10 |
| February | 0.304054E+09 | 0.110059E+09 | 0.193996E+09 | 0.110136E+09 | 0.118379E+10 |
| March | 0.558555E+09 | 0.281759E+09 | 0.276796E+09 | 0.362495E+09 | 0.997491E+09 |
| April | 0.762423E+09 | 0.404785E+09 | 0.357638E+09 | 0.661241E+09 | 0.633820E+09 |
| May | 0.968172E+09 | 0.488107E+09 | 0.480065E+09 | 0.996804E+09 | 0.402073E+09 |
| June | 0.887627E+09 | 0.404670E+09 | 0.482957E+09 | 0.976866E+09 | 0.291775E+09 |
| July | 0.994607E+09 | 0.489129E+09 | 0.505478E+09 | 0.116283E+10 | 0.265352E+09 |
| August | 0.822718E+09 | 0.398062E+09 | 0.424656E+09 | 0.923757E+09 | 0.299562E+09 |
| September | 0.599200E+09 | 0.278333E+09 | 0.320866E+09 | 0.536821E+09 | 0.478297E+09 |
| October | 0.339143E+09 | 0.122726E+09 | 0.216417E+09 | 0.195575E+09 | 0.710745E+09 |
| November | 0.160302E+09 | 30762262.12 | 0.129539E+09 | 27898782.90 | 0.970023E+09 |
| December | 0.123513E+09 | 14687435.58 | 0.108825E+09 | 0.00 | 0.163054E+10 |
| Annual Sum or Average | 0.668597E+10 | 0.305743E+10 | 0.362854E+10 | 0.595757E+10 | 0.954737E+10 |
| Minimum of Months | 0.123513E+09 | 14687435.58 | 0.108825E+09 | 0.00 | 0.265352E+09 |
| Maximum of Months | 0.994607E+09 | 0.489129E+09 | 0.505478E+09 | 0.116283E+10 | 0.168390E+10 |
Report: WindowEnergyReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.716004E+09 | 0.298882E+09 | 0.417122E+09 | 0.179094E+09 | 0.341611E+10 |
| February | 0.101625E+10 | 0.433487E+09 | 0.582764E+09 | 0.485304E+09 | 0.242682E+10 |
| March | 0.153307E+10 | 0.769011E+09 | 0.764059E+09 | 0.102031E+10 | 0.211248E+10 |
| April | 0.205672E+10 | 0.110935E+10 | 0.947367E+09 | 0.180063E+10 | 0.127949E+10 |
| May | 0.230018E+10 | 0.101118E+10 | 0.128899E+10 | 0.232193E+10 | 0.777053E+09 |
| June | 0.251996E+10 | 0.120544E+10 | 0.131452E+10 | 0.285431E+10 | 0.550172E+09 |
| July | 0.255092E+10 | 0.119775E+10 | 0.135317E+10 | 0.298396E+10 | 0.517786E+09 |
| August | 0.196676E+10 | 0.859614E+09 | 0.110715E+10 | 0.216703E+10 | 0.624331E+09 |
| September | 0.152424E+10 | 0.682242E+09 | 0.841999E+09 | 0.139012E+10 | 0.985820E+09 |
| October | 0.953720E+09 | 0.361649E+09 | 0.592071E+09 | 0.585918E+09 | 0.148216E+10 |
| November | 0.587560E+09 | 0.196435E+09 | 0.391125E+09 | 0.220720E+09 | 0.201297E+10 |
| December | 0.554015E+09 | 0.204773E+09 | 0.349242E+09 | 0.111149E+09 | 0.331393E+10 |
| Annual Sum or Average | 0.182794E+11 | 0.832982E+10 | 0.994959E+10 | 0.161205E+11 | 0.194991E+11 |
| Minimum of Months | 0.554015E+09 | 0.196435E+09 | 0.349242E+09 | 0.111149E+09 | 0.517786E+09 |
| Maximum of Months | 0.255092E+10 | 0.120544E+10 | 0.135317E+10 | 0.298396E+10 | 0.341611E+10 |
Report: WindowEnergyReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.139315E+09 | 96918294.91 | 42396658.61 | 0.102025E+09 | 0.182940E+09 |
| February | 0.159335E+09 | 0.107620E+09 | 51714442.81 | 0.138479E+09 | 0.136335E+09 |
| March | 0.155435E+09 | 98368914.97 | 57066317.56 | 0.139682E+09 | 0.124943E+09 |
| April | 0.136277E+09 | 73967224.37 | 62309554.86 | 0.134206E+09 | 83303748.61 |
| May | 0.118392E+09 | 40475435.12 | 77916638.07 | 0.125659E+09 | 52728588.09 |
| June | 0.102804E+09 | 27401782.74 | 75402243.17 | 0.117381E+09 | 36785653.74 |
| July | 0.116145E+09 | 36794107.18 | 79350630.89 | 0.140730E+09 | 34451164.12 |
| August | 0.124036E+09 | 51883308.41 | 72152646.85 | 0.145445E+09 | 40608566.86 |
| September | 0.128575E+09 | 68475957.70 | 60099275.08 | 0.135855E+09 | 63087287.36 |
| October | 0.113454E+09 | 66727925.64 | 46726018.38 | 0.104310E+09 | 89004845.39 |
| November | 97802392.16 | 61380904.74 | 36421487.42 | 79593775.36 | 0.114013E+09 |
| December | 0.107568E+09 | 70533530.08 | 37034310.47 | 72206373.50 | 0.178909E+09 |
| Annual Sum or Average | 0.149914E+10 | 0.800547E+09 | 0.698590E+09 | 0.143557E+10 | 0.113711E+10 |
| Minimum of Months | 97802392.16 | 27401782.74 | 36421487.42 | 72206373.50 | 34451164.12 |
| Maximum of Months | 0.159335E+09 | 0.107620E+09 | 79350630.89 | 0.145445E+09 | 0.182940E+09 |
Report: WindowEnergyReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.210956E+10 | 0.146757E+10 | 0.641987E+09 | 0.154491E+10 | 0.277015E+10 |
| February | 0.241271E+10 | 0.162963E+10 | 0.783080E+09 | 0.209690E+10 | 0.206444E+10 |
| March | 0.235366E+10 | 0.148954E+10 | 0.864120E+09 | 0.211512E+10 | 0.189194E+10 |
| April | 0.206356E+10 | 0.112004E+10 | 0.943515E+09 | 0.203220E+10 | 0.126106E+10 |
| May | 0.179274E+10 | 0.612895E+09 | 0.117984E+10 | 0.190279E+10 | 0.797220E+09 |
| June | 0.155670E+10 | 0.414928E+09 | 0.114177E+10 | 0.177776E+10 | 0.555245E+09 |
| July | 0.175871E+10 | 0.557151E+09 | 0.120156E+10 | 0.213128E+10 | 0.520080E+09 |
| August | 0.187820E+10 | 0.785637E+09 | 0.109256E+10 | 0.220240E+10 | 0.614468E+09 |
| September | 0.194694E+10 | 0.103689E+10 | 0.910047E+09 | 0.205716E+10 | 0.955276E+09 |
| October | 0.171796E+10 | 0.101042E+10 | 0.707544E+09 | 0.157950E+10 | 0.134775E+10 |
| November | 0.148096E+10 | 0.929454E+09 | 0.551508E+09 | 0.120524E+10 | 0.172643E+10 |
| December | 0.162883E+10 | 0.106805E+10 | 0.560788E+09 | 0.109338E+10 | 0.270911E+10 |
| Annual Sum or Average | 0.227005E+11 | 0.121222E+11 | 0.105783E+11 | 0.217386E+11 | 0.172132E+11 |
| Minimum of Months | 0.148096E+10 | 0.414928E+09 | 0.551508E+09 | 0.109338E+10 | 0.520080E+09 |
| Maximum of Months | 0.241271E+10 | 0.162963E+10 | 0.120156E+10 | 0.220240E+10 | 0.277015E+10 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105562E+09 | 36456888.83 | 69105030.35 | 20668182.39 | 0.355600E+09 |
| February | 0.170142E+09 | 78332591.78 | 91809756.70 | 94851430.15 | 0.259665E+09 |
| March | 0.269320E+09 | 0.151490E+09 | 0.117830E+09 | 0.194843E+09 | 0.227232E+09 |
| April | 0.384833E+09 | 0.243153E+09 | 0.141680E+09 | 0.343417E+09 | 0.155373E+09 |
| May | 0.487337E+09 | 0.274689E+09 | 0.212648E+09 | 0.489306E+09 | 0.102918E+09 |
| June | 0.495776E+09 | 0.285782E+09 | 0.209994E+09 | 0.520859E+09 | 74067007.22 |
| July | 0.526055E+09 | 0.314641E+09 | 0.211414E+09 | 0.564184E+09 | 73037928.25 |
| August | 0.414932E+09 | 0.233225E+09 | 0.181707E+09 | 0.434459E+09 | 79129447.23 |
| September | 0.291322E+09 | 0.149959E+09 | 0.141363E+09 | 0.273916E+09 | 0.114371E+09 |
| October | 0.178549E+09 | 71000609.82 | 0.107548E+09 | 0.130643E+09 | 0.167476E+09 |
| November | 99539064.44 | 29787446.10 | 69751618.34 | 41162544.36 | 0.220148E+09 |
| December | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 0.345061E+09 |
| Annual Sum or Average | 0.350577E+10 | 0.188943E+10 | 0.161635E+10 | 0.311649E+10 | 0.217408E+10 |
| Minimum of Months | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 73037928.25 |
| Maximum of Months | 0.526055E+09 | 0.314641E+09 | 0.212648E+09 | 0.564184E+09 | 0.355600E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105562E+09 | 36456888.83 | 69105030.35 | 20668182.39 | 0.355600E+09 |
| February | 0.170142E+09 | 78332591.78 | 91809756.70 | 94851430.15 | 0.259665E+09 |
| March | 0.269320E+09 | 0.151490E+09 | 0.117830E+09 | 0.194843E+09 | 0.227232E+09 |
| April | 0.384833E+09 | 0.243153E+09 | 0.141680E+09 | 0.343417E+09 | 0.155373E+09 |
| May | 0.487337E+09 | 0.274689E+09 | 0.212648E+09 | 0.489306E+09 | 0.102918E+09 |
| June | 0.495776E+09 | 0.285782E+09 | 0.209994E+09 | 0.520859E+09 | 74067007.22 |
| July | 0.526055E+09 | 0.314641E+09 | 0.211414E+09 | 0.564184E+09 | 73037928.25 |
| August | 0.414932E+09 | 0.233225E+09 | 0.181707E+09 | 0.434459E+09 | 79129447.23 |
| September | 0.291322E+09 | 0.149959E+09 | 0.141363E+09 | 0.273916E+09 | 0.114371E+09 |
| October | 0.178549E+09 | 71000609.82 | 0.107548E+09 | 0.130643E+09 | 0.167476E+09 |
| November | 99539064.44 | 29787446.10 | 69751618.34 | 41162544.36 | 0.220148E+09 |
| December | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 0.345061E+09 |
| Annual Sum or Average | 0.350577E+10 | 0.188943E+10 | 0.161635E+10 | 0.311649E+10 | 0.217408E+10 |
| Minimum of Months | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 73037928.25 |
| Maximum of Months | 0.526055E+09 | 0.314641E+09 | 0.212648E+09 | 0.564184E+09 | 0.355600E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105562E+09 | 36456888.83 | 69105030.35 | 20668182.39 | 0.355600E+09 |
| February | 0.170142E+09 | 78332591.78 | 91809756.70 | 94851430.15 | 0.259665E+09 |
| March | 0.269320E+09 | 0.151490E+09 | 0.117830E+09 | 0.194843E+09 | 0.227232E+09 |
| April | 0.384833E+09 | 0.243153E+09 | 0.141680E+09 | 0.343417E+09 | 0.155373E+09 |
| May | 0.487337E+09 | 0.274689E+09 | 0.212648E+09 | 0.489306E+09 | 0.102918E+09 |
| June | 0.495776E+09 | 0.285782E+09 | 0.209994E+09 | 0.520859E+09 | 74067007.22 |
| July | 0.526055E+09 | 0.314641E+09 | 0.211414E+09 | 0.564184E+09 | 73037928.25 |
| August | 0.414932E+09 | 0.233225E+09 | 0.181707E+09 | 0.434459E+09 | 79129447.23 |
| September | 0.291322E+09 | 0.149959E+09 | 0.141363E+09 | 0.273916E+09 | 0.114371E+09 |
| October | 0.178549E+09 | 71000609.82 | 0.107548E+09 | 0.130643E+09 | 0.167476E+09 |
| November | 99539064.44 | 29787446.10 | 69751618.34 | 41162544.36 | 0.220148E+09 |
| December | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 0.345061E+09 |
| Annual Sum or Average | 0.350577E+10 | 0.188943E+10 | 0.161635E+10 | 0.311649E+10 | 0.217408E+10 |
| Minimum of Months | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 73037928.25 |
| Maximum of Months | 0.526055E+09 | 0.314641E+09 | 0.212648E+09 | 0.564184E+09 | 0.355600E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105562E+09 | 36456888.83 | 69105030.35 | 20668182.39 | 0.355600E+09 |
| February | 0.170142E+09 | 78332591.78 | 91809756.70 | 94851430.15 | 0.259665E+09 |
| March | 0.269320E+09 | 0.151490E+09 | 0.117830E+09 | 0.194843E+09 | 0.227232E+09 |
| April | 0.384833E+09 | 0.243153E+09 | 0.141680E+09 | 0.343417E+09 | 0.155373E+09 |
| May | 0.487337E+09 | 0.274689E+09 | 0.212648E+09 | 0.489306E+09 | 0.102918E+09 |
| June | 0.495776E+09 | 0.285782E+09 | 0.209994E+09 | 0.520859E+09 | 74067007.22 |
| July | 0.526055E+09 | 0.314641E+09 | 0.211414E+09 | 0.564184E+09 | 73037928.25 |
| August | 0.414932E+09 | 0.233225E+09 | 0.181707E+09 | 0.434459E+09 | 79129447.23 |
| September | 0.291322E+09 | 0.149959E+09 | 0.141363E+09 | 0.273916E+09 | 0.114371E+09 |
| October | 0.178549E+09 | 71000609.82 | 0.107548E+09 | 0.130643E+09 | 0.167476E+09 |
| November | 99539064.44 | 29787446.10 | 69751618.34 | 41162544.36 | 0.220148E+09 |
| December | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 0.345061E+09 |
| Annual Sum or Average | 0.350577E+10 | 0.188943E+10 | 0.161635E+10 | 0.311649E+10 | 0.217408E+10 |
| Minimum of Months | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 73037928.25 |
| Maximum of Months | 0.526055E+09 | 0.314641E+09 | 0.212648E+09 | 0.564184E+09 | 0.355600E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105562E+09 | 36456888.83 | 69105030.35 | 20668182.39 | 0.355600E+09 |
| February | 0.170142E+09 | 78332591.78 | 91809756.70 | 94851430.15 | 0.259665E+09 |
| March | 0.269320E+09 | 0.151490E+09 | 0.117830E+09 | 0.194843E+09 | 0.227232E+09 |
| April | 0.384833E+09 | 0.243153E+09 | 0.141680E+09 | 0.343417E+09 | 0.155373E+09 |
| May | 0.487337E+09 | 0.274689E+09 | 0.212648E+09 | 0.489306E+09 | 0.102918E+09 |
| June | 0.495776E+09 | 0.285782E+09 | 0.209994E+09 | 0.520859E+09 | 74067007.22 |
| July | 0.526055E+09 | 0.314641E+09 | 0.211414E+09 | 0.564184E+09 | 73037928.25 |
| August | 0.414932E+09 | 0.233225E+09 | 0.181707E+09 | 0.434459E+09 | 79129447.23 |
| September | 0.291322E+09 | 0.149959E+09 | 0.141363E+09 | 0.273916E+09 | 0.114371E+09 |
| October | 0.178549E+09 | 71000609.82 | 0.107548E+09 | 0.130643E+09 | 0.167476E+09 |
| November | 99539064.44 | 29787446.10 | 69751618.34 | 41162544.36 | 0.220148E+09 |
| December | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 0.345061E+09 |
| Annual Sum or Average | 0.350577E+10 | 0.188943E+10 | 0.161635E+10 | 0.311649E+10 | 0.217408E+10 |
| Minimum of Months | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 73037928.25 |
| Maximum of Months | 0.526055E+09 | 0.314641E+09 | 0.212648E+09 | 0.564184E+09 | 0.355600E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105562E+09 | 36456888.83 | 69105030.35 | 20668182.39 | 0.355600E+09 |
| February | 0.170142E+09 | 78332591.78 | 91809756.70 | 94851430.15 | 0.259665E+09 |
| March | 0.269320E+09 | 0.151490E+09 | 0.117830E+09 | 0.194843E+09 | 0.227232E+09 |
| April | 0.384833E+09 | 0.243153E+09 | 0.141680E+09 | 0.343417E+09 | 0.155373E+09 |
| May | 0.487337E+09 | 0.274689E+09 | 0.212648E+09 | 0.489306E+09 | 0.102918E+09 |
| June | 0.495776E+09 | 0.285782E+09 | 0.209994E+09 | 0.520859E+09 | 74067007.22 |
| July | 0.526055E+09 | 0.314641E+09 | 0.211414E+09 | 0.564184E+09 | 73037928.25 |
| August | 0.414932E+09 | 0.233225E+09 | 0.181707E+09 | 0.434459E+09 | 79129447.23 |
| September | 0.291322E+09 | 0.149959E+09 | 0.141363E+09 | 0.273916E+09 | 0.114371E+09 |
| October | 0.178549E+09 | 71000609.82 | 0.107548E+09 | 0.130643E+09 | 0.167476E+09 |
| November | 99539064.44 | 29787446.10 | 69751618.34 | 41162544.36 | 0.220148E+09 |
| December | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 0.345061E+09 |
| Annual Sum or Average | 0.350577E+10 | 0.188943E+10 | 0.161635E+10 | 0.311649E+10 | 0.217408E+10 |
| Minimum of Months | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 73037928.25 |
| Maximum of Months | 0.526055E+09 | 0.314641E+09 | 0.212648E+09 | 0.564184E+09 | 0.355600E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105562E+09 | 36456888.83 | 69105030.35 | 20668182.39 | 0.355600E+09 |
| February | 0.170142E+09 | 78332591.78 | 91809756.70 | 94851430.15 | 0.259665E+09 |
| March | 0.269320E+09 | 0.151490E+09 | 0.117830E+09 | 0.194843E+09 | 0.227232E+09 |
| April | 0.384833E+09 | 0.243153E+09 | 0.141680E+09 | 0.343417E+09 | 0.155373E+09 |
| May | 0.487337E+09 | 0.274689E+09 | 0.212648E+09 | 0.489306E+09 | 0.102918E+09 |
| June | 0.495776E+09 | 0.285782E+09 | 0.209994E+09 | 0.520859E+09 | 74067007.22 |
| July | 0.526055E+09 | 0.314641E+09 | 0.211414E+09 | 0.564184E+09 | 73037928.25 |
| August | 0.414932E+09 | 0.233225E+09 | 0.181707E+09 | 0.434459E+09 | 79129447.23 |
| September | 0.291322E+09 | 0.149959E+09 | 0.141363E+09 | 0.273916E+09 | 0.114371E+09 |
| October | 0.178549E+09 | 71000609.82 | 0.107548E+09 | 0.130643E+09 | 0.167476E+09 |
| November | 99539064.44 | 29787446.10 | 69751618.34 | 41162544.36 | 0.220148E+09 |
| December | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 0.345061E+09 |
| Annual Sum or Average | 0.350577E+10 | 0.188943E+10 | 0.161635E+10 | 0.311649E+10 | 0.217408E+10 |
| Minimum of Months | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 73037928.25 |
| Maximum of Months | 0.526055E+09 | 0.314641E+09 | 0.212648E+09 | 0.564184E+09 | 0.355600E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105562E+09 | 36456888.83 | 69105030.35 | 20668182.39 | 0.355600E+09 |
| February | 0.170142E+09 | 78332591.78 | 91809756.70 | 94851430.15 | 0.259665E+09 |
| March | 0.269320E+09 | 0.151490E+09 | 0.117830E+09 | 0.194843E+09 | 0.227232E+09 |
| April | 0.384833E+09 | 0.243153E+09 | 0.141680E+09 | 0.343417E+09 | 0.155373E+09 |
| May | 0.487337E+09 | 0.274689E+09 | 0.212648E+09 | 0.489306E+09 | 0.102918E+09 |
| June | 0.495776E+09 | 0.285782E+09 | 0.209994E+09 | 0.520859E+09 | 74067007.22 |
| July | 0.526055E+09 | 0.314641E+09 | 0.211414E+09 | 0.564184E+09 | 73037928.25 |
| August | 0.414932E+09 | 0.233225E+09 | 0.181707E+09 | 0.434459E+09 | 79129447.23 |
| September | 0.291322E+09 | 0.149959E+09 | 0.141363E+09 | 0.273916E+09 | 0.114371E+09 |
| October | 0.178549E+09 | 71000609.82 | 0.107548E+09 | 0.130643E+09 | 0.167476E+09 |
| November | 99539064.44 | 29787446.10 | 69751618.34 | 41162544.36 | 0.220148E+09 |
| December | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 0.345061E+09 |
| Annual Sum or Average | 0.350577E+10 | 0.188943E+10 | 0.161635E+10 | 0.311649E+10 | 0.217408E+10 |
| Minimum of Months | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 73037928.25 |
| Maximum of Months | 0.526055E+09 | 0.314641E+09 | 0.212648E+09 | 0.564184E+09 | 0.355600E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.105562E+09 | 36456888.83 | 69105030.35 | 20668182.39 | 0.355600E+09 |
| February | 0.170142E+09 | 78332591.78 | 91809756.70 | 94851430.15 | 0.259665E+09 |
| March | 0.269320E+09 | 0.151490E+09 | 0.117830E+09 | 0.194843E+09 | 0.227232E+09 |
| April | 0.384833E+09 | 0.243153E+09 | 0.141680E+09 | 0.343417E+09 | 0.155373E+09 |
| May | 0.487337E+09 | 0.274689E+09 | 0.212648E+09 | 0.489306E+09 | 0.102918E+09 |
| June | 0.495776E+09 | 0.285782E+09 | 0.209994E+09 | 0.520859E+09 | 74067007.22 |
| July | 0.526055E+09 | 0.314641E+09 | 0.211414E+09 | 0.564184E+09 | 73037928.25 |
| August | 0.414932E+09 | 0.233225E+09 | 0.181707E+09 | 0.434459E+09 | 79129447.23 |
| September | 0.291322E+09 | 0.149959E+09 | 0.141363E+09 | 0.273916E+09 | 0.114371E+09 |
| October | 0.178549E+09 | 71000609.82 | 0.107548E+09 | 0.130643E+09 | 0.167476E+09 |
| November | 99539064.44 | 29787446.10 | 69751618.34 | 41162544.36 | 0.220148E+09 |
| December | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 0.345061E+09 |
| Annual Sum or Average | 0.350577E+10 | 0.188943E+10 | 0.161635E+10 | 0.311649E+10 | 0.217408E+10 |
| Minimum of Months | 82407535.48 | 20910741.28 | 61496794.20 | 8181354.58 | 73037928.25 |
| Maximum of Months | 0.526055E+09 | 0.314641E+09 | 0.212648E+09 | 0.564184E+09 | 0.355600E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 45149464.85 | 18846793.47 | 26302671.39 | 11092035.42 | 0.219362E+09 |
| February | 64082385.97 | 27334682.38 | 36747703.59 | 29925300.62 | 0.157420E+09 |
| March | 96671670.39 | 48491962.02 | 48179708.38 | 62760696.42 | 0.141070E+09 |
| April | 0.129692E+09 | 69953217.04 | 59738671.06 | 0.109305E+09 | 90209824.24 |
| May | 0.145044E+09 | 63762787.72 | 81280748.14 | 0.142149E+09 | 53927724.63 |
| June | 0.158903E+09 | 76011946.37 | 82890644.17 | 0.176995E+09 | 37532072.68 |
| July | 0.160855E+09 | 75527333.32 | 85327568.29 | 0.185861E+09 | 34922830.78 |
| August | 0.124019E+09 | 54205177.53 | 69814226.99 | 0.135439E+09 | 41054229.47 |
| September | 96114929.34 | 43020550.03 | 53094379.31 | 86906135.64 | 63960369.00 |
| October | 60139276.60 | 22804699.32 | 37334577.28 | 36253465.99 | 98221016.80 |
| November | 37050125.43 | 12386706.84 | 24663418.59 | 13463841.39 | 0.133476E+09 |
| December | 34934834.61 | 12912470.97 | 22022363.64 | 6877556.09 | 0.213507E+09 |
| Annual Sum or Average | 0.115266E+10 | 0.525258E+09 | 0.627397E+09 | 0.997028E+09 | 0.128466E+10 |
| Minimum of Months | 34934834.61 | 12386706.84 | 22022363.64 | 6877556.09 | 34922830.78 |
| Maximum of Months | 0.160855E+09 | 76011946.37 | 85327568.29 | 0.185861E+09 | 0.219362E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.534391E+09 | 0.223066E+09 | 0.311326E+09 | 0.131241E+09 | 0.259605E+10 |
| February | 0.758484E+09 | 0.323526E+09 | 0.434958E+09 | 0.354257E+09 | 0.186219E+10 |
| March | 0.114421E+10 | 0.573938E+09 | 0.570275E+09 | 0.743271E+09 | 0.166710E+10 |
| April | 0.153504E+10 | 0.827948E+09 | 0.707096E+09 | 0.129668E+10 | 0.106620E+10 |
| May | 0.171675E+10 | 0.754680E+09 | 0.962073E+09 | 0.168750E+10 | 0.638051E+09 |
| June | 0.188079E+10 | 0.899657E+09 | 0.981128E+09 | 0.209972E+10 | 0.444244E+09 |
| July | 0.190390E+10 | 0.893922E+09 | 0.100997E+10 | 0.220546E+10 | 0.413387E+09 |
| August | 0.146791E+10 | 0.641558E+09 | 0.826351E+09 | 0.160752E+10 | 0.486102E+09 |
| September | 0.113763E+10 | 0.509180E+09 | 0.628446E+09 | 0.103153E+10 | 0.756781E+09 |
| October | 0.711814E+09 | 0.269910E+09 | 0.441904E+09 | 0.429796E+09 | 0.116201E+10 |
| November | 0.438528E+09 | 0.146606E+09 | 0.291923E+09 | 0.159348E+09 | 0.157956E+10 |
| December | 0.413491E+09 | 0.152829E+09 | 0.260662E+09 | 81374733.99 | 0.252707E+10 |
| Annual Sum or Average | 0.136429E+11 | 0.621682E+10 | 0.742612E+10 | 0.118277E+11 | 0.151987E+11 |
| Minimum of Months | 0.413491E+09 | 0.146606E+09 | 0.260662E+09 | 81374733.99 | 0.413387E+09 |
| Maximum of Months | 0.190390E+10 | 0.899657E+09 | 0.100997E+10 | 0.220546E+10 | 0.259605E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.272756E+09 | 0.113856E+09 | 0.158900E+09 | 61937667.58 | 0.153250E+10 |
| February | 0.387133E+09 | 0.165133E+09 | 0.222000E+09 | 0.160298E+09 | 0.114814E+10 |
| March | 0.584011E+09 | 0.292947E+09 | 0.291064E+09 | 0.351544E+09 | 0.105173E+10 |
| April | 0.783492E+09 | 0.422598E+09 | 0.360894E+09 | 0.634829E+09 | 0.655313E+09 |
| May | 0.876234E+09 | 0.385200E+09 | 0.491034E+09 | 0.850755E+09 | 0.361135E+09 |
| June | 0.959959E+09 | 0.459199E+09 | 0.500760E+09 | 0.106776E+10 | 0.253460E+09 |
| July | 0.971753E+09 | 0.456272E+09 | 0.515482E+09 | 0.112342E+10 | 0.232093E+09 |
| August | 0.749224E+09 | 0.327461E+09 | 0.421762E+09 | 0.816422E+09 | 0.277619E+09 |
| September | 0.580647E+09 | 0.259893E+09 | 0.320754E+09 | 0.517736E+09 | 0.427329E+09 |
| October | 0.363312E+09 | 0.137766E+09 | 0.225546E+09 | 0.201799E+09 | 0.712137E+09 |
| November | 0.223826E+09 | 74829891.62 | 0.148996E+09 | 70438789.30 | 0.101525E+10 |
| December | 0.211047E+09 | 78006108.93 | 0.133041E+09 | 36836758.73 | 0.149342E+10 |
| Annual Sum or Average | 0.696339E+10 | 0.317316E+10 | 0.379023E+10 | 0.589377E+10 | 0.916013E+10 |
| Minimum of Months | 0.211047E+09 | 74829891.62 | 0.133041E+09 | 36836758.73 | 0.232093E+09 |
| Maximum of Months | 0.971753E+09 | 0.459199E+09 | 0.515482E+09 | 0.112342E+10 | 0.153250E+10 |
Report: WindowEnergyReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.307175E+09 | 0.00 | 0.307175E+09 | 617648.86 | 0.383378E+10 |
| February | 0.426052E+09 | 0.00 | 0.426052E+09 | 14569018.06 | 0.278117E+10 |
| March | 0.580650E+09 | 0.00 | 0.580650E+09 | 36729128.03 | 0.241717E+10 |
| April | 0.732565E+09 | 3371389.56 | 0.729194E+09 | 0.220789E+09 | 0.141962E+10 |
| May | 0.104437E+10 | 39405094.81 | 0.100496E+10 | 0.732105E+09 | 0.790652E+09 |
| June | 0.111231E+10 | 97847388.35 | 0.101446E+10 | 0.103637E+10 | 0.557106E+09 |
| July | 0.110492E+10 | 73556772.49 | 0.103136E+10 | 0.109849E+10 | 0.522327E+09 |
| August | 0.855938E+09 | 9342609.42 | 0.846595E+09 | 0.743010E+09 | 0.619534E+09 |
| September | 0.653551E+09 | 76082.23 | 0.653474E+09 | 0.335875E+09 | 0.101151E+10 |
| October | 0.469886E+09 | 0.00 | 0.469886E+09 | 71054898.16 | 0.156087E+10 |
| November | 0.300604E+09 | 0.00 | 0.300604E+09 | 10447842.34 | 0.226178E+10 |
| December | 0.260596E+09 | 0.00 | 0.260596E+09 | 0.00 | 0.366045E+10 |
| Annual Sum or Average | 0.784862E+10 | 0.223599E+09 | 0.762502E+10 | 0.430006E+10 | 0.214360E+11 |
| Minimum of Months | 0.260596E+09 | 0.00 | 0.260596E+09 | 0.00 | 0.522327E+09 |
| Maximum of Months | 0.111231E+10 | 97847388.35 | 0.103136E+10 | 0.109849E+10 | 0.383378E+10 |
Report: WindowEnergyReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 45577627.65 | 19025521.96 | 26552105.69 | 11623237.50 | 0.218432E+09 |
| February | 64690094.02 | 27593903.48 | 37096190.55 | 31155815.83 | 0.155337E+09 |
| March | 97588430.16 | 48951822.48 | 48636607.67 | 65198139.01 | 0.135964E+09 |
| April | 0.130922E+09 | 70616599.54 | 60305186.67 | 0.115579E+09 | 81039106.97 |
| May | 0.146419E+09 | 64367464.95 | 82051552.24 | 0.148372E+09 | 49386387.72 |
| June | 0.160410E+09 | 76732785.20 | 83676715.28 | 0.181523E+09 | 35983102.65 |
| July | 0.162380E+09 | 76243576.46 | 86136749.31 | 0.189419E+09 | 33645891.17 |
| August | 0.125196E+09 | 54719217.74 | 70476291.42 | 0.138768E+09 | 39142745.28 |
| September | 97026409.40 | 43428523.84 | 53597885.56 | 90190618.53 | 60424844.17 |
| October | 60709591.24 | 23020961.55 | 37688629.69 | 38490965.65 | 92407806.12 |
| November | 37401480.32 | 12504172.84 | 24897307.48 | 13828859.87 | 0.131603E+09 |
| December | 35266129.71 | 13034922.91 | 22231206.80 | 7203541.75 | 0.212616E+09 |
| Annual Sum or Average | 0.116359E+10 | 0.530239E+09 | 0.633346E+09 | 0.103135E+10 | 0.124598E+10 |
| Minimum of Months | 35266129.71 | 12504172.84 | 22231206.80 | 7203541.75 | 33645891.17 |
| Maximum of Months | 0.162380E+09 | 76732785.20 | 86136749.31 | 0.189419E+09 | 0.218432E+09 |
Report: WindowEnergyReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.465855E+09 | 0.194462E+09 | 0.271392E+09 | 0.118803E+09 | 0.223262E+10 |
| February | 0.661206E+09 | 0.282041E+09 | 0.379165E+09 | 0.318448E+09 | 0.158772E+10 |
| March | 0.997464E+09 | 0.500343E+09 | 0.497121E+09 | 0.666399E+09 | 0.138971E+10 |
| April | 0.133817E+10 | 0.721781E+09 | 0.616387E+09 | 0.118135E+10 | 0.828298E+09 |
| May | 0.149657E+10 | 0.657908E+09 | 0.838659E+09 | 0.151665E+10 | 0.504548E+09 |
| June | 0.163957E+10 | 0.784296E+09 | 0.855270E+09 | 0.185567E+10 | 0.367497E+09 |
| July | 0.165971E+10 | 0.779295E+09 | 0.880415E+09 | 0.193633E+10 | 0.343665E+09 |
| August | 0.127964E+10 | 0.559292E+09 | 0.720347E+09 | 0.141839E+10 | 0.400025E+09 |
| September | 0.991719E+09 | 0.443889E+09 | 0.547831E+09 | 0.921850E+09 | 0.617610E+09 |
| October | 0.620521E+09 | 0.235300E+09 | 0.385220E+09 | 0.393421E+09 | 0.944512E+09 |
| November | 0.382285E+09 | 0.127807E+09 | 0.254479E+09 | 0.141347E+09 | 0.134513E+10 |
| December | 0.360460E+09 | 0.133232E+09 | 0.227228E+09 | 73628326.62 | 0.217317E+10 |
| Annual Sum or Average | 0.118932E+11 | 0.541965E+10 | 0.647352E+10 | 0.105423E+11 | 0.127345E+11 |
| Minimum of Months | 0.360460E+09 | 0.127807E+09 | 0.227228E+09 | 73628326.62 | 0.343665E+09 |
| Maximum of Months | 0.165971E+10 | 0.784296E+09 | 0.880415E+09 | 0.193633E+10 | 0.223262E+10 |
Report: WindowEnergyReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.295471E+09 | 0.00 | 0.295471E+09 | 1037236.48 | 0.344136E+10 |
| February | 0.409944E+09 | 0.00 | 0.409944E+09 | 17678596.37 | 0.247350E+10 |
| March | 0.558406E+09 | 0.00 | 0.558406E+09 | 43674026.85 | 0.212061E+10 |
| April | 0.708422E+09 | 5528997.59 | 0.702893E+09 | 0.225219E+09 | 0.126006E+10 |
| May | 0.102958E+10 | 55439902.11 | 0.974138E+09 | 0.746675E+09 | 0.711372E+09 |
| June | 0.111196E+10 | 0.122231E+09 | 0.989727E+09 | 0.105827E+10 | 0.491684E+09 |
| July | 0.109750E+10 | 94184041.61 | 0.100332E+10 | 0.112577E+10 | 0.457885E+09 |
| August | 0.833587E+09 | 14314871.92 | 0.819272E+09 | 0.742749E+09 | 0.555755E+09 |
| September | 0.628635E+09 | 154094.86 | 0.628481E+09 | 0.330109E+09 | 0.954113E+09 |
| October | 0.451040E+09 | 0.00 | 0.451040E+09 | 69318633.40 | 0.146369E+10 |
| November | 0.289012E+09 | 0.00 | 0.289012E+09 | 12152725.40 | 0.199877E+10 |
| December | 0.250346E+09 | 0.00 | 0.250346E+09 | 0.00 | 0.328244E+10 |
| Annual Sum or Average | 0.766390E+10 | 0.291853E+09 | 0.737204E+10 | 0.437265E+10 | 0.192112E+11 |
| Minimum of Months | 0.250346E+09 | 0.00 | 0.250346E+09 | 0.00 | 0.457885E+09 |
| Maximum of Months | 0.111196E+10 | 0.122231E+09 | 0.100332E+10 | 0.112577E+10 | 0.344136E+10 |
Report: WindowEnergyReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 14769663.39 | 0.00 | 14769663.39 | 88.98 | 0.235546E+09 |
| February | 20797513.61 | 0.00 | 20797513.61 | 288172.86 | 0.171255E+09 |
| March | 28703165.29 | 0.00 | 28703165.29 | 915843.21 | 0.149072E+09 |
| April | 61690879.98 | 21611199.37 | 40079680.61 | 33046684.03 | 80994765.28 |
| May | 0.100459E+09 | 42144902.88 | 58314424.96 | 91039322.30 | 46962572.85 |
| June | 0.122188E+09 | 60433522.27 | 61754785.98 | 0.134286E+09 | 33671947.22 |
| July | 0.119554E+09 | 56460994.43 | 63092733.77 | 0.136799E+09 | 30033629.30 |
| August | 74158272.04 | 26541288.55 | 47616983.48 | 74752725.77 | 36709788.59 |
| September | 36108112.13 | 3162217.19 | 32945894.94 | 15703765.33 | 63104903.80 |
| October | 22508432.85 | 0.00 | 22508432.85 | 1645378.85 | 0.102843E+09 |
| November | 14303548.90 | 0.00 | 14303548.90 | 342553.68 | 0.137394E+09 |
| December | 12393792.98 | 0.00 | 12393792.98 | 0.00 | 0.223582E+09 |
| Annual Sum or Average | 0.627635E+09 | 0.210354E+09 | 0.417281E+09 | 0.488819E+09 | 0.131117E+10 |
| Minimum of Months | 12393792.98 | 0.00 | 12393792.98 | 0.00 | 30033629.30 |
| Maximum of Months | 0.122188E+09 | 60433522.27 | 63092733.77 | 0.136799E+09 | 0.235546E+09 |
Report: WindowEnergyReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.537981E+09 | 0.186015E+09 | 0.351966E+09 | 67697644.24 | 0.326378E+10 |
| February | 0.857655E+09 | 0.346423E+09 | 0.511232E+09 | 0.364068E+09 | 0.227837E+10 |
| March | 0.140651E+10 | 0.714275E+09 | 0.692239E+09 | 0.942480E+09 | 0.196456E+10 |
| April | 0.190074E+10 | 0.104048E+10 | 0.860261E+09 | 0.167531E+10 | 0.118694E+10 |
| May | 0.212006E+10 | 0.948402E+09 | 0.117166E+10 | 0.213797E+10 | 0.730608E+09 |
| June | 0.232457E+10 | 0.113059E+10 | 0.119397E+10 | 0.262968E+10 | 0.522430E+09 |
| July | 0.235184E+10 | 0.112339E+10 | 0.122846E+10 | 0.276112E+10 | 0.478199E+09 |
| August | 0.181072E+10 | 0.806243E+09 | 0.100447E+10 | 0.201135E+10 | 0.569718E+09 |
| September | 0.140314E+10 | 0.639121E+09 | 0.764016E+09 | 0.128540E+10 | 0.923846E+09 |
| October | 0.845184E+09 | 0.314108E+09 | 0.531076E+09 | 0.498425E+09 | 0.141565E+10 |
| November | 0.478965E+09 | 0.140680E+09 | 0.338285E+09 | 0.144813E+09 | 0.192254E+10 |
| December | 0.404229E+09 | 0.111525E+09 | 0.292703E+09 | 27451836.24 | 0.317435E+10 |
| Annual Sum or Average | 0.164416E+11 | 0.750125E+10 | 0.894034E+10 | 0.145458E+11 | 0.184310E+11 |
| Minimum of Months | 0.404229E+09 | 0.111525E+09 | 0.292703E+09 | 27451836.24 | 0.478199E+09 |
| Maximum of Months | 0.235184E+10 | 0.113059E+10 | 0.122846E+10 | 0.276112E+10 | 0.326378E+10 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 294.73 | 1070.54 | 555.60 | 354.45 | 201.15 | 0.00 | 0.00 |
| February | 544.36 | 874.60 | 745.56 | 462.32 | 283.24 | 0.00 | 0.00 |
| March | 591.39 | 701.80 | 738.96 | 437.58 | 301.38 | 0.00 | 0.00 |
| April | 713.55 | 442.47 | 761.70 | 401.92 | 359.78 | 0.00 | 0.00 |
| May | 823.76 | 259.15 | 763.42 | 313.65 | 449.77 | 0.00 | 0.00 |
| June | 830.32 | 179.86 | 711.39 | 251.98 | 459.41 | 0.00 | 0.00 |
| July | 941.31 | 168.00 | 768.10 | 302.78 | 465.32 | 0.00 | 0.00 |
| August | 849.34 | 201.50 | 721.93 | 313.90 | 408.03 | 0.00 | 0.00 |
| September | 686.91 | 345.94 | 677.62 | 339.38 | 338.24 | 0.00 | 0.00 |
| October | 433.26 | 492.21 | 521.26 | 276.13 | 245.13 | 0.00 | 0.00 |
| November | 276.18 | 676.50 | 418.10 | 233.63 | 184.47 | 0.00 | 0.00 |
| December | 198.15 | 1051.34 | 427.89 | 253.58 | 174.31 | 0.00 | 0.00 |
| Annual Sum or Average | 598.74 | 537.29 | 650.28 | 327.58 | 322.70 | 0.00 | 0.00 |
| Minimum of Months | 198.15 | 168.00 | 418.10 | 233.63 | 174.31 | 0.00 | 0.00 |
| Maximum of Months | 941.31 | 1070.54 | 768.10 | 462.32 | 465.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1539.17 | 2804.25 | 2119.11 | 1474.22 | 644.89 | 0.00 | 0.00 |
| February | 2313.17 | 2326.29 | 2683.30 | 1812.40 | 870.91 | 0.00 | 0.00 |
| March | 2111.26 | 1927.56 | 2364.32 | 1496.28 | 868.03 | 0.00 | 0.00 |
| April | 2120.49 | 1292.28 | 2141.99 | 1162.61 | 979.38 | 0.00 | 0.00 |
| May | 1953.93 | 754.65 | 1800.85 | 615.67 | 1185.19 | 0.00 | 0.00 |
| June | 1908.77 | 523.83 | 1615.87 | 430.70 | 1185.17 | 0.00 | 0.00 |
| July | 2236.07 | 451.76 | 1766.67 | 559.67 | 1207.00 | 0.00 | 0.00 |
| August | 2288.70 | 540.04 | 1886.70 | 789.19 | 1097.51 | 0.00 | 0.00 |
| September | 2153.95 | 965.27 | 2020.94 | 1076.30 | 944.64 | 0.00 | 0.00 |
| October | 1579.29 | 1369.49 | 1725.74 | 1014.99 | 710.75 | 0.00 | 0.00 |
| November | 1234.20 | 1831.20 | 1537.26 | 964.78 | 572.47 | 0.00 | 0.00 |
| December | 1089.14 | 2745.49 | 1636.21 | 1072.88 | 563.33 | 0.00 | 0.00 |
| Annual Sum or Average | 1874.02 | 1457.27 | 1936.72 | 1034.22 | 902.50 | 0.00 | 0.00 |
| Minimum of Months | 1089.14 | 451.76 | 1537.26 | 430.70 | 563.33 | 0.00 | 0.00 |
| Maximum of Months | 2313.17 | 2804.25 | 2683.30 | 1812.40 | 1207.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 11.13 | 194.98 | 38.60 | 16.16 | 22.44 | 0.00 | 0.00 |
| February | 34.36 | 155.81 | 62.89 | 28.72 | 34.16 | 0.00 | 0.00 |
| March | 58.02 | 121.29 | 82.76 | 42.35 | 40.41 | 0.00 | 0.00 |
| April | 93.08 | 74.26 | 105.72 | 53.54 | 52.17 | 0.00 | 0.00 |
| May | 138.86 | 41.90 | 129.89 | 61.96 | 67.93 | 0.00 | 0.00 |
| June | 143.95 | 29.30 | 125.34 | 54.20 | 71.14 | 0.00 | 0.00 |
| July | 162.22 | 25.20 | 133.81 | 62.21 | 71.60 | 0.00 | 0.00 |
| August | 128.38 | 29.50 | 110.12 | 50.04 | 60.08 | 0.00 | 0.00 |
| September | 82.41 | 53.78 | 86.06 | 38.67 | 47.40 | 0.00 | 0.00 |
| October | 37.51 | 80.73 | 54.37 | 21.83 | 32.54 | 0.00 | 0.00 |
| November | 12.90 | 118.12 | 33.02 | 11.13 | 21.89 | 0.00 | 0.00 |
| December | 5.85 | 189.21 | 29.44 | 10.30 | 19.13 | 0.00 | 0.00 |
| Annual Sum or Average | 75.98 | 92.58 | 82.78 | 37.65 | 45.13 | 0.00 | 0.00 |
| Minimum of Months | 5.85 | 25.20 | 29.44 | 10.30 | 19.13 | 0.00 | 0.00 |
| Maximum of Months | 162.22 | 194.98 | 133.81 | 62.21 | 71.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 9.66 | 1262.00 | 169.72 | 48.49 | 121.23 | 0.00 | 0.00 |
| February | 77.45 | 991.34 | 270.85 | 86.17 | 184.69 | 0.00 | 0.00 |
| March | 155.50 | 752.08 | 349.11 | 127.04 | 222.07 | 0.00 | 0.00 |
| April | 325.05 | 430.90 | 449.70 | 161.67 | 288.03 | 0.00 | 0.00 |
| May | 571.95 | 235.87 | 578.27 | 196.66 | 381.61 | 0.00 | 0.00 |
| June | 654.02 | 165.88 | 585.47 | 187.13 | 398.35 | 0.00 | 0.00 |
| July | 715.45 | 149.27 | 599.34 | 204.46 | 394.87 | 0.00 | 0.00 |
| August | 538.35 | 175.33 | 480.90 | 153.04 | 327.86 | 0.00 | 0.00 |
| September | 314.70 | 322.46 | 376.31 | 116.03 | 260.29 | 0.00 | 0.00 |
| October | 121.84 | 487.16 | 246.39 | 65.48 | 180.92 | 0.00 | 0.00 |
| November | 28.17 | 733.20 | 153.93 | 33.40 | 120.53 | 0.00 | 0.00 |
| December | 1.90 | 1215.50 | 134.49 | 30.91 | 103.58 | 0.00 | 0.00 |
| Annual Sum or Average | 294.19 | 575.13 | 366.72 | 117.72 | 249.00 | 0.00 | 0.00 |
| Minimum of Months | 1.90 | 149.27 | 134.49 | 30.91 | 103.58 | 0.00 | 0.00 |
| Maximum of Months | 715.45 | 1262.00 | 599.34 | 204.46 | 398.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.04 | 3600.75 | 243.42 | 0.00 | 243.42 | 0.00 | 0.00 |
| February | 6.91 | 2897.32 | 370.17 | 0.00 | 370.17 | 0.00 | 0.00 |
| March | 17.55 | 2254.91 | 453.97 | 0.00 | 453.97 | 0.00 | 0.00 |
| April | 171.61 | 1294.82 | 595.53 | 3.77 | 591.76 | 0.00 | 0.00 |
| May | 624.70 | 660.73 | 841.07 | 42.07 | 799.00 | 0.00 | 0.00 |
| June | 925.23 | 462.75 | 913.56 | 90.98 | 822.58 | 0.00 | 0.00 |
| July | 1009.26 | 376.62 | 868.63 | 66.61 | 802.01 | 0.00 | 0.00 |
| August | 677.79 | 445.35 | 672.93 | 11.22 | 661.71 | 0.00 | 0.00 |
| September | 273.33 | 903.52 | 532.78 | 0.10 | 532.67 | 0.00 | 0.00 |
| October | 43.37 | 1425.96 | 377.52 | 0.00 | 377.52 | 0.00 | 0.00 |
| November | 9.48 | 2131.80 | 248.16 | 0.00 | 248.16 | 0.00 | 0.00 |
| December | 0.00 | 3422.11 | 209.18 | 0.00 | 209.18 | 0.00 | 0.00 |
| Annual Sum or Average | 315.44 | 1651.21 | 528.04 | 17.98 | 510.06 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 376.62 | 209.18 | 0.00 | 209.18 | 0.00 | 0.00 |
| Maximum of Months | 1009.26 | 3600.75 | 913.56 | 90.98 | 822.58 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 279.34 | 1093.96 | 518.61 | 333.87 | 184.74 | 0.00 | 0.00 |
| February | 529.19 | 877.71 | 724.40 | 459.50 | 264.90 | 0.00 | 0.00 |
| March | 572.37 | 700.53 | 717.93 | 437.56 | 280.36 | 0.00 | 0.00 |
| April | 688.19 | 440.29 | 734.92 | 401.92 | 332.99 | 0.00 | 0.00 |
| May | 788.26 | 255.68 | 729.51 | 313.65 | 415.86 | 0.00 | 0.00 |
| June | 790.54 | 176.60 | 674.48 | 251.98 | 422.50 | 0.00 | 0.00 |
| July | 901.46 | 163.08 | 730.63 | 302.78 | 427.84 | 0.00 | 0.00 |
| August | 815.95 | 197.01 | 690.87 | 313.90 | 376.96 | 0.00 | 0.00 |
| September | 662.19 | 342.15 | 654.10 | 339.38 | 314.72 | 0.00 | 0.00 |
| October | 419.37 | 490.22 | 505.13 | 275.42 | 229.70 | 0.00 | 0.00 |
| November | 264.74 | 680.70 | 398.79 | 227.50 | 171.29 | 0.00 | 0.00 |
| December | 178.09 | 1078.41 | 384.33 | 226.45 | 157.88 | 0.00 | 0.00 |
| Annual Sum or Average | 574.21 | 540.04 | 621.20 | 322.75 | 298.46 | 0.00 | 0.00 |
| Minimum of Months | 178.09 | 163.08 | 384.33 | 226.45 | 157.88 | 0.00 | 0.00 |
| Maximum of Months | 901.46 | 1093.96 | 734.92 | 459.50 | 427.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1322.78 | 2951.72 | 1799.29 | 1275.18 | 524.11 | 0.00 | 0.00 |
| February | 2146.98 | 2360.21 | 2490.22 | 1745.75 | 744.47 | 0.00 | 0.00 |
| March | 1953.89 | 1932.15 | 2201.85 | 1468.28 | 733.57 | 0.00 | 0.00 |
| April | 1944.85 | 1292.19 | 1962.00 | 1148.23 | 813.76 | 0.00 | 0.00 |
| May | 1725.59 | 744.49 | 1587.26 | 610.67 | 976.59 | 0.00 | 0.00 |
| June | 1657.43 | 512.97 | 1387.09 | 427.41 | 959.68 | 0.00 | 0.00 |
| July | 1980.26 | 428.15 | 1533.76 | 555.58 | 978.18 | 0.00 | 0.00 |
| August | 2068.23 | 518.84 | 1688.12 | 782.01 | 906.12 | 0.00 | 0.00 |
| September | 1973.61 | 949.49 | 1856.65 | 1059.99 | 796.66 | 0.00 | 0.00 |
| October | 1458.10 | 1365.25 | 1597.98 | 988.74 | 609.24 | 0.00 | 0.00 |
| November | 1103.37 | 1874.76 | 1362.46 | 884.99 | 477.46 | 0.00 | 0.00 |
| December | 873.15 | 2914.15 | 1300.16 | 859.09 | 441.07 | 0.00 | 0.00 |
| Annual Sum or Average | 1680.37 | 1483.47 | 1725.30 | 978.70 | 746.59 | 0.00 | 0.00 |
| Minimum of Months | 873.15 | 428.15 | 1300.16 | 427.41 | 441.07 | 0.00 | 0.00 |
| Maximum of Months | 2146.98 | 2951.72 | 2490.22 | 1745.75 | 978.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 11.14 | 194.88 | 38.60 | 16.16 | 22.44 | 0.00 | 0.00 |
| February | 34.37 | 155.79 | 62.89 | 28.72 | 34.16 | 0.00 | 0.00 |
| March | 58.03 | 121.28 | 82.76 | 42.35 | 40.41 | 0.00 | 0.00 |
| April | 93.13 | 74.21 | 105.72 | 53.54 | 52.17 | 0.00 | 0.00 |
| May | 138.95 | 41.82 | 129.89 | 61.96 | 67.93 | 0.00 | 0.00 |
| June | 144.04 | 29.23 | 125.34 | 54.20 | 71.14 | 0.00 | 0.00 |
| July | 162.45 | 25.02 | 133.81 | 62.21 | 71.60 | 0.00 | 0.00 |
| August | 128.58 | 29.30 | 110.12 | 50.04 | 60.08 | 0.00 | 0.00 |
| September | 82.49 | 53.66 | 86.06 | 38.67 | 47.40 | 0.00 | 0.00 |
| October | 37.55 | 80.65 | 54.37 | 21.83 | 32.54 | 0.00 | 0.00 |
| November | 12.92 | 118.03 | 33.02 | 11.13 | 21.89 | 0.00 | 0.00 |
| December | 5.87 | 189.08 | 29.44 | 10.30 | 19.13 | 0.00 | 0.00 |
| Annual Sum or Average | 76.05 | 92.49 | 82.78 | 37.65 | 45.13 | 0.00 | 0.00 |
| Minimum of Months | 5.87 | 25.02 | 29.44 | 10.30 | 19.13 | 0.00 | 0.00 |
| Maximum of Months | 162.45 | 194.88 | 133.81 | 62.21 | 71.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 9.73 | 1261.69 | 170.44 | 48.49 | 121.95 | 0.00 | 0.00 |
| February | 77.88 | 990.92 | 272.00 | 86.17 | 185.84 | 0.00 | 0.00 |
| March | 156.31 | 751.63 | 350.55 | 127.04 | 223.51 | 0.00 | 0.00 |
| April | 326.64 | 430.75 | 451.54 | 161.67 | 289.86 | 0.00 | 0.00 |
| May | 574.47 | 235.73 | 580.76 | 196.77 | 383.99 | 0.00 | 0.00 |
| June | 657.05 | 165.67 | 588.39 | 187.39 | 401.00 | 0.00 | 0.00 |
| July | 718.70 | 149.01 | 602.21 | 204.65 | 397.55 | 0.00 | 0.00 |
| August | 540.97 | 175.24 | 483.05 | 153.06 | 329.99 | 0.00 | 0.00 |
| September | 316.47 | 322.39 | 377.92 | 116.03 | 261.90 | 0.00 | 0.00 |
| October | 122.62 | 487.02 | 247.42 | 65.48 | 181.95 | 0.00 | 0.00 |
| November | 28.37 | 732.95 | 154.63 | 33.40 | 121.23 | 0.00 | 0.00 |
| December | 1.92 | 1215.27 | 135.06 | 30.91 | 104.16 | 0.00 | 0.00 |
| Annual Sum or Average | 295.62 | 574.91 | 368.34 | 117.77 | 250.57 | 0.00 | 0.00 |
| Minimum of Months | 1.92 | 149.01 | 135.06 | 30.91 | 104.16 | 0.00 | 0.00 |
| Maximum of Months | 718.70 | 1261.69 | 602.21 | 204.65 | 401.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.06 | 3599.00 | 246.94 | 0.00 | 246.94 | 0.00 | 0.00 |
| February | 7.54 | 2893.78 | 375.81 | 0.00 | 375.81 | 0.00 | 0.00 |
| March | 18.89 | 2250.10 | 461.00 | 0.00 | 461.00 | 0.00 | 0.00 |
| April | 177.47 | 1292.04 | 604.65 | 3.85 | 600.80 | 0.00 | 0.00 |
| May | 637.84 | 659.67 | 854.29 | 43.27 | 811.02 | 0.00 | 0.00 |
| June | 943.03 | 461.87 | 930.23 | 93.87 | 836.36 | 0.00 | 0.00 |
| July | 1026.95 | 376.14 | 884.23 | 68.64 | 815.59 | 0.00 | 0.00 |
| August | 690.66 | 445.47 | 683.89 | 11.54 | 672.35 | 0.00 | 0.00 |
| September | 281.08 | 903.02 | 540.65 | 0.10 | 540.55 | 0.00 | 0.00 |
| October | 45.63 | 1424.18 | 382.55 | 0.00 | 382.55 | 0.00 | 0.00 |
| November | 9.71 | 2130.13 | 251.59 | 0.00 | 251.59 | 0.00 | 0.00 |
| December | 0.00 | 3421.01 | 211.99 | 0.00 | 211.99 | 0.00 | 0.00 |
| Annual Sum or Average | 322.11 | 1649.54 | 536.46 | 18.52 | 517.94 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 376.14 | 211.99 | 0.00 | 211.99 | 0.00 | 0.00 |
| Maximum of Months | 1026.95 | 3599.00 | 930.23 | 93.87 | 836.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 285.21 | 1089.05 | 527.76 | 340.55 | 187.21 | 0.00 | 0.00 |
| February | 530.30 | 876.82 | 726.52 | 460.06 | 266.46 | 0.00 | 0.00 |
| March | 573.76 | 700.74 | 719.53 | 437.56 | 281.97 | 0.00 | 0.00 |
| April | 689.59 | 441.40 | 736.96 | 401.92 | 335.04 | 0.00 | 0.00 |
| May | 790.10 | 257.05 | 732.10 | 313.65 | 418.45 | 0.00 | 0.00 |
| June | 792.65 | 177.78 | 677.30 | 251.98 | 425.32 | 0.00 | 0.00 |
| July | 903.07 | 164.80 | 733.49 | 302.78 | 430.71 | 0.00 | 0.00 |
| August | 817.30 | 198.89 | 693.24 | 313.90 | 379.33 | 0.00 | 0.00 |
| September | 663.11 | 344.18 | 655.90 | 339.38 | 316.52 | 0.00 | 0.00 |
| October | 419.75 | 492.44 | 506.52 | 275.59 | 230.93 | 0.00 | 0.00 |
| November | 267.22 | 680.24 | 402.47 | 229.67 | 172.80 | 0.00 | 0.00 |
| December | 186.65 | 1072.28 | 396.59 | 235.33 | 161.26 | 0.00 | 0.00 |
| Annual Sum or Average | 576.65 | 539.98 | 624.95 | 324.30 | 300.65 | 0.00 | 0.00 |
| Minimum of Months | 186.65 | 164.80 | 396.59 | 229.67 | 161.26 | 0.00 | 0.00 |
| Maximum of Months | 903.07 | 1089.05 | 736.96 | 460.06 | 430.71 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1362.21 | 2926.09 | 1852.68 | 1314.98 | 537.70 | 0.00 | 0.00 |
| February | 2155.02 | 2353.04 | 2503.92 | 1751.35 | 752.57 | 0.00 | 0.00 |
| March | 1960.12 | 1932.51 | 2208.90 | 1468.28 | 740.61 | 0.00 | 0.00 |
| April | 1951.15 | 1296.27 | 1970.98 | 1148.24 | 822.74 | 0.00 | 0.00 |
| May | 1734.22 | 749.82 | 1598.63 | 610.68 | 987.95 | 0.00 | 0.00 |
| June | 1666.90 | 517.72 | 1399.46 | 427.41 | 972.05 | 0.00 | 0.00 |
| July | 1988.02 | 435.06 | 1546.32 | 555.58 | 990.74 | 0.00 | 0.00 |
| August | 2074.31 | 526.73 | 1698.54 | 782.01 | 916.53 | 0.00 | 0.00 |
| September | 1978.06 | 958.20 | 1864.58 | 1060.02 | 804.56 | 0.00 | 0.00 |
| October | 1459.53 | 1375.77 | 1604.16 | 989.44 | 614.72 | 0.00 | 0.00 |
| November | 1119.36 | 1869.46 | 1385.40 | 899.30 | 486.10 | 0.00 | 0.00 |
| December | 920.00 | 2886.25 | 1361.43 | 903.78 | 457.65 | 0.00 | 0.00 |
| Annual Sum or Average | 1693.85 | 1482.01 | 1744.42 | 987.55 | 756.87 | 0.00 | 0.00 |
| Minimum of Months | 920.00 | 435.06 | 1361.43 | 427.41 | 457.65 | 0.00 | 0.00 |
| Maximum of Months | 2155.02 | 2926.09 | 2503.92 | 1751.35 | 990.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 11.13 | 194.98 | 38.60 | 16.16 | 22.44 | 0.00 | 0.00 |
| February | 34.35 | 155.88 | 62.89 | 28.72 | 34.16 | 0.00 | 0.00 |
| March | 57.98 | 121.43 | 82.76 | 42.35 | 40.41 | 0.00 | 0.00 |
| April | 92.80 | 74.83 | 105.72 | 53.54 | 52.17 | 0.00 | 0.00 |
| May | 138.41 | 42.47 | 129.89 | 61.96 | 67.93 | 0.00 | 0.00 |
| June | 143.46 | 29.80 | 125.34 | 54.20 | 71.14 | 0.00 | 0.00 |
| July | 161.57 | 25.76 | 133.81 | 62.21 | 71.60 | 0.00 | 0.00 |
| August | 127.83 | 30.13 | 110.12 | 50.04 | 60.08 | 0.00 | 0.00 |
| September | 81.95 | 54.64 | 86.06 | 38.67 | 47.40 | 0.00 | 0.00 |
| October | 37.22 | 81.83 | 54.37 | 21.83 | 32.54 | 0.00 | 0.00 |
| November | 12.87 | 118.51 | 33.02 | 11.13 | 21.89 | 0.00 | 0.00 |
| December | 5.86 | 189.20 | 29.44 | 10.30 | 19.13 | 0.00 | 0.00 |
| Annual Sum or Average | 75.71 | 93.04 | 82.78 | 37.65 | 45.13 | 0.00 | 0.00 |
| Minimum of Months | 5.86 | 25.76 | 29.44 | 10.30 | 19.13 | 0.00 | 0.00 |
| Maximum of Months | 161.57 | 194.98 | 133.81 | 62.21 | 71.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 10.75 | 1255.96 | 179.44 | 48.49 | 130.95 | 0.00 | 0.00 |
| February | 83.58 | 983.93 | 286.43 | 86.17 | 200.26 | 0.00 | 0.00 |
| March | 167.26 | 745.39 | 368.55 | 127.04 | 241.51 | 0.00 | 0.00 |
| April | 346.18 | 429.86 | 474.83 | 161.86 | 312.97 | 0.00 | 0.00 |
| May | 603.91 | 237.49 | 611.45 | 197.82 | 413.63 | 0.00 | 0.00 |
| June | 691.06 | 166.23 | 623.53 | 189.80 | 433.74 | 0.00 | 0.00 |
| July | 752.13 | 151.27 | 637.85 | 206.92 | 430.93 | 0.00 | 0.00 |
| August | 568.54 | 180.22 | 509.92 | 153.20 | 356.72 | 0.00 | 0.00 |
| September | 335.74 | 326.41 | 398.12 | 116.03 | 282.08 | 0.00 | 0.00 |
| October | 131.64 | 488.84 | 260.26 | 65.48 | 194.78 | 0.00 | 0.00 |
| November | 30.88 | 730.50 | 163.39 | 33.40 | 129.99 | 0.00 | 0.00 |
| December | 2.28 | 1210.88 | 142.23 | 30.91 | 111.32 | 0.00 | 0.00 |
| Annual Sum or Average | 311.75 | 574.01 | 388.54 | 118.28 | 270.26 | 0.00 | 0.00 |
| Minimum of Months | 2.28 | 151.27 | 142.23 | 30.91 | 111.32 | 0.00 | 0.00 |
| Maximum of Months | 752.13 | 1255.96 | 637.85 | 206.92 | 433.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.74 | 2358.66 | 203.22 | 0.00 | 203.22 | 0.00 | 0.00 |
| February | 14.04 | 1873.08 | 312.16 | 0.00 | 312.16 | 0.00 | 0.00 |
| March | 34.11 | 1438.05 | 384.06 | 0.00 | 384.06 | 0.00 | 0.00 |
| April | 189.89 | 831.78 | 503.48 | 3.93 | 499.55 | 0.00 | 0.00 |
| May | 565.21 | 436.47 | 708.13 | 38.13 | 670.00 | 0.00 | 0.00 |
| June | 810.59 | 307.22 | 790.28 | 86.87 | 703.41 | 0.00 | 0.00 |
| July | 861.78 | 259.97 | 754.85 | 64.78 | 690.07 | 0.00 | 0.00 |
| August | 587.53 | 309.15 | 573.33 | 9.85 | 563.48 | 0.00 | 0.00 |
| September | 270.61 | 605.34 | 446.78 | 0.11 | 446.67 | 0.00 | 0.00 |
| October | 60.19 | 936.00 | 310.22 | 0.00 | 310.22 | 0.00 | 0.00 |
| November | 9.54 | 1393.08 | 205.41 | 0.00 | 205.41 | 0.00 | 0.00 |
| December | 0.00 | 2248.50 | 172.19 | 0.00 | 172.19 | 0.00 | 0.00 |
| Annual Sum or Average | 285.50 | 1079.89 | 447.68 | 17.05 | 430.64 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 259.97 | 172.19 | 0.00 | 172.19 | 0.00 | 0.00 |
| Maximum of Months | 861.78 | 2358.66 | 790.28 | 86.87 | 703.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.36 | 1219.75 | 104.51 | 0.00 | 104.51 | 0.00 | 0.00 |
| February | 6.96 | 971.32 | 160.54 | 0.00 | 160.54 | 0.00 | 0.00 |
| March | 16.15 | 751.46 | 197.52 | 0.00 | 197.52 | 0.00 | 0.00 |
| April | 89.41 | 451.20 | 258.93 | 2.02 | 256.91 | 0.00 | 0.00 |
| May | 278.14 | 241.01 | 364.18 | 19.61 | 344.57 | 0.00 | 0.00 |
| June | 403.52 | 170.71 | 406.43 | 44.68 | 361.75 | 0.00 | 0.00 |
| July | 424.37 | 146.68 | 388.20 | 33.32 | 354.89 | 0.00 | 0.00 |
| August | 285.03 | 176.36 | 294.85 | 5.06 | 289.79 | 0.00 | 0.00 |
| September | 128.01 | 337.92 | 229.77 | 0.06 | 229.71 | 0.00 | 0.00 |
| October | 26.32 | 513.86 | 159.54 | 0.00 | 159.54 | 0.00 | 0.00 |
| November | 4.38 | 737.17 | 105.64 | 0.00 | 105.64 | 0.00 | 0.00 |
| December | 0.00 | 1164.83 | 88.55 | 0.00 | 88.55 | 0.00 | 0.00 |
| Annual Sum or Average | 139.44 | 571.89 | 230.24 | 8.77 | 221.47 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 146.68 | 88.55 | 0.00 | 88.55 | 0.00 | 0.00 |
| Maximum of Months | 424.37 | 1219.75 | 406.43 | 44.68 | 361.75 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.08 | 611.54 | 47.84 | 6.48 | 41.36 | 0.00 | 0.00 |
| February | 22.11 | 478.31 | 97.08 | 29.40 | 67.68 | 0.00 | 0.00 |
| March | 100.29 | 366.64 | 172.92 | 83.83 | 89.09 | 0.00 | 0.00 |
| April | 218.04 | 230.32 | 256.37 | 135.59 | 120.78 | 0.00 | 0.00 |
| May | 332.00 | 132.58 | 318.88 | 161.48 | 157.40 | 0.00 | 0.00 |
| June | 342.31 | 95.33 | 302.62 | 138.86 | 163.76 | 0.00 | 0.00 |
| July | 391.26 | 82.27 | 327.82 | 162.00 | 165.82 | 0.00 | 0.00 |
| August | 306.36 | 94.83 | 269.09 | 130.27 | 138.82 | 0.00 | 0.00 |
| September | 177.74 | 161.55 | 198.16 | 90.57 | 107.58 | 0.00 | 0.00 |
| October | 53.98 | 239.79 | 102.72 | 33.73 | 68.99 | 0.00 | 0.00 |
| November | 4.27 | 362.23 | 48.92 | 6.62 | 42.30 | 0.00 | 0.00 |
| December | 0.00 | 589.54 | 36.97 | 2.47 | 34.50 | 0.00 | 0.00 |
| Annual Sum or Average | 163.27 | 286.32 | 182.09 | 82.08 | 100.01 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 82.27 | 36.97 | 2.47 | 34.50 | 0.00 | 0.00 |
| Maximum of Months | 391.26 | 611.54 | 327.82 | 162.00 | 165.82 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 617.27 | 896.67 | 759.68 | 528.50 | 231.19 | 0.00 | 0.00 |
| February | 888.98 | 751.90 | 961.94 | 649.73 | 312.21 | 0.00 | 0.00 |
| March | 801.83 | 614.97 | 847.59 | 536.41 | 311.18 | 0.00 | 0.00 |
| April | 791.09 | 415.57 | 767.89 | 416.79 | 351.10 | 0.00 | 0.00 |
| May | 717.36 | 254.12 | 645.59 | 220.71 | 424.88 | 0.00 | 0.00 |
| June | 688.95 | 182.10 | 579.28 | 154.40 | 424.87 | 0.00 | 0.00 |
| July | 787.91 | 171.27 | 633.34 | 200.64 | 432.70 | 0.00 | 0.00 |
| August | 815.83 | 196.81 | 676.37 | 282.92 | 393.45 | 0.00 | 0.00 |
| September | 792.28 | 317.54 | 724.49 | 385.85 | 338.65 | 0.00 | 0.00 |
| October | 592.26 | 434.84 | 618.66 | 363.87 | 254.80 | 0.00 | 0.00 |
| November | 469.18 | 588.73 | 551.09 | 345.87 | 205.23 | 0.00 | 0.00 |
| December | 428.12 | 867.33 | 586.57 | 384.62 | 201.95 | 0.00 | 0.00 |
| Annual Sum or Average | 697.85 | 473.12 | 694.30 | 370.76 | 323.54 | 0.00 | 0.00 |
| Minimum of Months | 428.12 | 171.27 | 551.09 | 154.40 | 201.95 | 0.00 | 0.00 |
| Maximum of Months | 888.98 | 896.67 | 961.94 | 649.73 | 432.70 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.17 | 628.70 | 61.85 | 12.83 | 49.02 | 0.00 | 0.00 |
| February | 45.53 | 489.33 | 125.68 | 45.49 | 80.19 | 0.00 | 0.00 |
| March | 135.34 | 372.42 | 208.54 | 105.20 | 103.34 | 0.00 | 0.00 |
| April | 255.11 | 244.53 | 294.14 | 156.17 | 137.98 | 0.00 | 0.00 |
| May | 372.16 | 150.12 | 361.47 | 182.24 | 179.24 | 0.00 | 0.00 |
| June | 376.88 | 112.57 | 342.45 | 156.12 | 186.33 | 0.00 | 0.00 |
| July | 434.15 | 99.07 | 371.34 | 182.62 | 188.72 | 0.00 | 0.00 |
| August | 344.89 | 111.84 | 307.17 | 148.62 | 158.55 | 0.00 | 0.00 |
| September | 207.11 | 184.53 | 231.17 | 107.38 | 123.79 | 0.00 | 0.00 |
| October | 73.02 | 265.36 | 126.62 | 45.82 | 80.80 | 0.00 | 0.00 |
| November | 10.76 | 374.24 | 61.84 | 11.87 | 49.98 | 0.00 | 0.00 |
| December | 0.00 | 608.78 | 46.11 | 5.48 | 40.63 | 0.00 | 0.00 |
| Annual Sum or Average | 188.91 | 302.75 | 212.01 | 96.95 | 115.06 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 99.07 | 46.11 | 5.48 | 40.63 | 0.00 | 0.00 |
| Maximum of Months | 434.15 | 628.70 | 371.34 | 182.62 | 188.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 558.01 | 2254.24 | 1106.96 | 695.70 | 411.25 | 0.00 | 0.00 |
| February | 1049.24 | 1837.48 | 1483.26 | 897.29 | 585.96 | 0.00 | 0.00 |
| March | 1169.71 | 1488.65 | 1509.17 | 879.97 | 629.20 | 0.00 | 0.00 |
| April | 1497.03 | 978.83 | 1642.19 | 888.64 | 753.55 | 0.00 | 0.00 |
| May | 1599.90 | 583.11 | 1572.32 | 621.47 | 950.85 | 0.00 | 0.00 |
| June | 1818.28 | 426.59 | 1612.45 | 635.71 | 976.73 | 0.00 | 0.00 |
| July | 1950.55 | 388.55 | 1652.39 | 668.94 | 983.45 | 0.00 | 0.00 |
| August | 1676.97 | 468.98 | 1481.86 | 633.64 | 848.22 | 0.00 | 0.00 |
| September | 1369.93 | 760.76 | 1388.79 | 689.66 | 699.13 | 0.00 | 0.00 |
| October | 834.33 | 1076.71 | 1039.85 | 537.19 | 502.67 | 0.00 | 0.00 |
| November | 535.73 | 1441.54 | 835.77 | 458.05 | 377.72 | 0.00 | 0.00 |
| December | 380.70 | 2219.57 | 855.14 | 501.55 | 353.59 | 0.00 | 0.00 |
| Annual Sum or Average | 1203.52 | 1157.69 | 1347.00 | 673.91 | 673.09 | 0.00 | 0.00 |
| Minimum of Months | 380.70 | 388.55 | 835.77 | 458.05 | 353.59 | 0.00 | 0.00 |
| Maximum of Months | 1950.55 | 2254.24 | 1652.39 | 897.29 | 983.45 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 56.20 | 2179.65 | 571.09 | 212.82 | 358.26 | 0.00 | 0.00 |
| February | 437.06 | 1726.22 | 972.99 | 436.45 | 536.54 | 0.00 | 0.00 |
| March | 894.63 | 1377.62 | 1368.27 | 741.43 | 626.84 | 0.00 | 0.00 |
| April | 1701.89 | 952.67 | 1978.49 | 1190.69 | 787.79 | 0.00 | 0.00 |
| May | 2312.12 | 589.01 | 2332.67 | 1228.58 | 1104.09 | 0.00 | 0.00 |
| June | 2677.05 | 433.20 | 2508.36 | 1368.71 | 1139.65 | 0.00 | 0.00 |
| July | 2779.82 | 404.02 | 2538.55 | 1419.21 | 1119.33 | 0.00 | 0.00 |
| August | 2103.17 | 455.26 | 1988.62 | 1043.46 | 945.16 | 0.00 | 0.00 |
| September | 1370.49 | 701.66 | 1487.51 | 733.73 | 753.78 | 0.00 | 0.00 |
| October | 589.48 | 1009.76 | 888.18 | 347.86 | 540.31 | 0.00 | 0.00 |
| November | 171.94 | 1387.64 | 529.10 | 164.77 | 364.33 | 0.00 | 0.00 |
| December | 18.01 | 2140.26 | 444.33 | 132.15 | 312.18 | 0.00 | 0.00 |
| Annual Sum or Average | 1263.66 | 1110.72 | 1469.67 | 753.01 | 716.66 | 0.00 | 0.00 |
| Minimum of Months | 18.01 | 404.02 | 444.33 | 132.15 | 312.18 | 0.00 | 0.00 |
| Maximum of Months | 2779.82 | 2179.65 | 2538.55 | 1419.21 | 1139.65 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 23.12 | 572.17 | 101.84 | 42.51 | 59.33 | 0.00 | 0.00 |
| February | 66.26 | 474.59 | 160.03 | 68.26 | 91.77 | 0.00 | 0.00 |
| March | 131.25 | 392.67 | 218.04 | 109.37 | 108.67 | 0.00 | 0.00 |
| April | 244.92 | 252.82 | 302.27 | 163.04 | 139.23 | 0.00 | 0.00 |
| May | 317.64 | 134.83 | 327.15 | 143.82 | 183.33 | 0.00 | 0.00 |
| June | 411.94 | 97.79 | 370.35 | 177.16 | 193.19 | 0.00 | 0.00 |
| July | 419.44 | 86.65 | 362.81 | 170.35 | 192.46 | 0.00 | 0.00 |
| August | 304.82 | 103.65 | 279.73 | 122.26 | 157.47 | 0.00 | 0.00 |
| September | 199.74 | 164.86 | 224.02 | 100.27 | 123.75 | 0.00 | 0.00 |
| October | 75.34 | 265.88 | 135.65 | 51.44 | 84.21 | 0.00 | 0.00 |
| November | 27.18 | 391.69 | 86.35 | 28.87 | 57.48 | 0.00 | 0.00 |
| December | 13.75 | 557.58 | 78.80 | 29.12 | 49.67 | 0.00 | 0.00 |
| Annual Sum or Average | 186.89 | 290.47 | 220.81 | 100.62 | 120.19 | 0.00 | 0.00 |
| Minimum of Months | 13.75 | 86.65 | 78.80 | 28.87 | 49.67 | 0.00 | 0.00 |
| Maximum of Months | 419.44 | 572.17 | 370.35 | 177.16 | 193.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.81 | 2299.38 | 305.63 | 79.71 | 225.93 | 0.00 | 0.00 |
| February | 75.20 | 1794.80 | 476.17 | 127.99 | 348.18 | 0.00 | 0.00 |
| March | 215.93 | 1401.15 | 625.64 | 205.08 | 420.55 | 0.00 | 0.00 |
| April | 542.01 | 854.99 | 849.40 | 307.01 | 542.39 | 0.00 | 0.00 |
| May | 884.69 | 491.72 | 1003.34 | 284.38 | 718.96 | 0.00 | 0.00 |
| June | 1184.80 | 369.61 | 1123.57 | 369.94 | 753.63 | 0.00 | 0.00 |
| July | 1202.88 | 334.97 | 1092.82 | 346.88 | 745.94 | 0.00 | 0.00 |
| August | 855.69 | 392.18 | 844.08 | 232.73 | 611.34 | 0.00 | 0.00 |
| September | 503.10 | 634.90 | 672.18 | 188.04 | 484.14 | 0.00 | 0.00 |
| October | 165.61 | 947.72 | 429.78 | 96.45 | 333.33 | 0.00 | 0.00 |
| November | 33.48 | 1411.91 | 277.89 | 54.13 | 223.76 | 0.00 | 0.00 |
| December | 1.11 | 2228.34 | 245.04 | 54.61 | 190.43 | 0.00 | 0.00 |
| Annual Sum or Average | 474.43 | 1094.13 | 662.90 | 195.76 | 467.14 | 0.00 | 0.00 |
| Minimum of Months | 1.11 | 334.97 | 245.04 | 54.13 | 190.43 | 0.00 | 0.00 |
| Maximum of Months | 1202.88 | 2299.38 | 1123.57 | 369.94 | 753.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.42 | 2567.11 | 316.69 | 69.45 | 247.24 | 0.00 | 0.00 |
| February | 91.78 | 1968.88 | 532.57 | 143.20 | 389.37 | 0.00 | 0.00 |
| March | 301.52 | 1513.88 | 744.33 | 266.68 | 477.65 | 0.00 | 0.00 |
| April | 707.96 | 937.28 | 1030.42 | 411.89 | 618.53 | 0.00 | 0.00 |
| May | 1098.41 | 543.32 | 1213.45 | 390.53 | 822.92 | 0.00 | 0.00 |
| June | 1469.59 | 399.20 | 1372.96 | 506.66 | 866.30 | 0.00 | 0.00 |
| July | 1498.59 | 357.02 | 1332.47 | 475.67 | 856.80 | 0.00 | 0.00 |
| August | 1052.04 | 429.78 | 1014.96 | 316.27 | 698.69 | 0.00 | 0.00 |
| September | 612.67 | 732.21 | 797.79 | 247.85 | 549.94 | 0.00 | 0.00 |
| October | 191.42 | 1092.26 | 492.36 | 117.27 | 375.08 | 0.00 | 0.00 |
| November | 36.36 | 1541.53 | 301.81 | 54.27 | 247.53 | 0.00 | 0.00 |
| December | 0.24 | 2484.15 | 249.02 | 41.64 | 207.38 | 0.00 | 0.00 |
| Annual Sum or Average | 591.29 | 1211.09 | 784.28 | 253.79 | 530.49 | 0.00 | 0.00 |
| Minimum of Months | 0.24 | 357.02 | 249.02 | 41.64 | 207.38 | 0.00 | 0.00 |
| Maximum of Months | 1498.59 | 2567.11 | 1372.96 | 506.66 | 866.30 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.789415E+09 | 0.286733E+10 | 0.148812E+10 | 0.949359E+09 | 0.538758E+09 | 0.00 | 0.00 |
| February | 0.131692E+10 | 0.211584E+10 | 0.180366E+10 | 0.111844E+10 | 0.685225E+09 | 0.00 | 0.00 |
| March | 0.158397E+10 | 0.187970E+10 | 0.197923E+10 | 0.117201E+10 | 0.807226E+09 | 0.00 | 0.00 |
| April | 0.184952E+10 | 0.114687E+10 | 0.197433E+10 | 0.104178E+10 | 0.932545E+09 | 0.00 | 0.00 |
| May | 0.220636E+10 | 0.694098E+09 | 0.204476E+10 | 0.840085E+09 | 0.120467E+10 | 0.00 | 0.00 |
| June | 0.215219E+10 | 0.466198E+09 | 0.184391E+10 | 0.653127E+09 | 0.119078E+10 | 0.00 | 0.00 |
| July | 0.252120E+10 | 0.449962E+09 | 0.205728E+10 | 0.810977E+09 | 0.124630E+10 | 0.00 | 0.00 |
| August | 0.227487E+10 | 0.539698E+09 | 0.193362E+10 | 0.840761E+09 | 0.109286E+10 | 0.00 | 0.00 |
| September | 0.178047E+10 | 0.896680E+09 | 0.175639E+10 | 0.879669E+09 | 0.876721E+09 | 0.00 | 0.00 |
| October | 0.116044E+10 | 0.131834E+10 | 0.139615E+10 | 0.739584E+09 | 0.656568E+09 | 0.00 | 0.00 |
| November | 0.715868E+09 | 0.175349E+10 | 0.108373E+10 | 0.605574E+09 | 0.478152E+09 | 0.00 | 0.00 |
| December | 0.530731E+09 | 0.281591E+10 | 0.114605E+10 | 0.679176E+09 | 0.466877E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.188819E+11 | 0.169441E+11 | 0.205072E+11 | 0.103305E+11 | 0.101767E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.530731E+09 | 0.449962E+09 | 0.108373E+10 | 0.605574E+09 | 0.466877E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.252120E+10 | 0.286733E+10 | 0.205728E+10 | 0.117201E+10 | 0.124630E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.412250E+10 | 0.751089E+10 | 0.567583E+10 | 0.394855E+10 | 0.172728E+10 | 0.00 | 0.00 |
| February | 0.559602E+10 | 0.562775E+10 | 0.649145E+10 | 0.438455E+10 | 0.210690E+10 | 0.00 | 0.00 |
| March | 0.565481E+10 | 0.516279E+10 | 0.633258E+10 | 0.400765E+10 | 0.232494E+10 | 0.00 | 0.00 |
| April | 0.549630E+10 | 0.334959E+10 | 0.555205E+10 | 0.301350E+10 | 0.253855E+10 | 0.00 | 0.00 |
| May | 0.523341E+10 | 0.202126E+10 | 0.482341E+10 | 0.164901E+10 | 0.317440E+10 | 0.00 | 0.00 |
| June | 0.494754E+10 | 0.135778E+10 | 0.418834E+10 | 0.111638E+10 | 0.307196E+10 | 0.00 | 0.00 |
| July | 0.598909E+10 | 0.121000E+10 | 0.473185E+10 | 0.149903E+10 | 0.323282E+10 | 0.00 | 0.00 |
| August | 0.613004E+10 | 0.144645E+10 | 0.505335E+10 | 0.211378E+10 | 0.293957E+10 | 0.00 | 0.00 |
| September | 0.558304E+10 | 0.250198E+10 | 0.523828E+10 | 0.278978E+10 | 0.244850E+10 | 0.00 | 0.00 |
| October | 0.422997E+10 | 0.366804E+10 | 0.462222E+10 | 0.271856E+10 | 0.190366E+10 | 0.00 | 0.00 |
| November | 0.319906E+10 | 0.474647E+10 | 0.398457E+10 | 0.250072E+10 | 0.148385E+10 | 0.00 | 0.00 |
| December | 0.291715E+10 | 0.735353E+10 | 0.438242E+10 | 0.287360E+10 | 0.150881E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.590989E+11 | 0.459565E+11 | 0.610763E+11 | 0.326151E+11 | 0.284612E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.291715E+10 | 0.121000E+10 | 0.398457E+10 | 0.111638E+10 | 0.148385E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.613004E+10 | 0.751089E+10 | 0.649145E+10 | 0.438455E+10 | 0.323282E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 29803224.21 | 0.522233E+09 | 0.103382E+09 | 43290087.88 | 60091432.06 | 0.00 | 0.00 |
| February | 83119354.48 | 0.376931E+09 | 0.152138E+09 | 69486688.70 | 82651674.54 | 0.00 | 0.00 |
| March | 0.155392E+09 | 0.324856E+09 | 0.221653E+09 | 0.113418E+09 | 0.108234E+09 | 0.00 | 0.00 |
| April | 0.241274E+09 | 0.192479E+09 | 0.274015E+09 | 0.138786E+09 | 0.135229E+09 | 0.00 | 0.00 |
| May | 0.371930E+09 | 0.112223E+09 | 0.347899E+09 | 0.165949E+09 | 0.181950E+09 | 0.00 | 0.00 |
| June | 0.373126E+09 | 75952822.78 | 0.324885E+09 | 0.140478E+09 | 0.184407E+09 | 0.00 | 0.00 |
| July | 0.434479E+09 | 67485649.92 | 0.358408E+09 | 0.166623E+09 | 0.191785E+09 | 0.00 | 0.00 |
| August | 0.343866E+09 | 79008127.71 | 0.294946E+09 | 0.134022E+09 | 0.160924E+09 | 0.00 | 0.00 |
| September | 0.213596E+09 | 0.139391E+09 | 0.223076E+09 | 0.100225E+09 | 0.122851E+09 | 0.00 | 0.00 |
| October | 0.100475E+09 | 0.216226E+09 | 0.145616E+09 | 58456537.20 | 87159171.73 | 0.00 | 0.00 |
| November | 33428838.37 | 0.306162E+09 | 85586924.79 | 28856659.36 | 56730265.43 | 0.00 | 0.00 |
| December | 15672946.57 | 0.506779E+09 | 78839157.79 | 27594262.67 | 51244895.12 | 0.00 | 0.00 |
| Annual Sum or Average | 0.239616E+10 | 0.291973E+10 | 0.261044E+10 | 0.118718E+10 | 0.142326E+10 | 0.00 | 0.00 |
| Minimum of Months | 15672946.57 | 67485649.92 | 78839157.79 | 27594262.67 | 51244895.12 | 0.00 | 0.00 |
| Maximum of Months | 0.434479E+09 | 0.522233E+09 | 0.358408E+09 | 0.166623E+09 | 0.191785E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 25861503.20 | 0.338014E+10 | 0.454583E+09 | 0.129870E+09 | 0.324713E+09 | 0.00 | 0.00 |
| February | 0.187356E+09 | 0.239825E+10 | 0.655250E+09 | 0.208459E+09 | 0.446790E+09 | 0.00 | 0.00 |
| March | 0.416497E+09 | 0.201438E+10 | 0.935054E+09 | 0.340253E+09 | 0.594801E+09 | 0.00 | 0.00 |
| April | 0.842523E+09 | 0.111690E+10 | 0.116563E+10 | 0.419057E+09 | 0.746574E+09 | 0.00 | 0.00 |
| May | 0.153190E+10 | 0.631758E+09 | 0.154883E+10 | 0.526740E+09 | 0.102209E+10 | 0.00 | 0.00 |
| June | 0.169523E+10 | 0.429954E+09 | 0.151754E+10 | 0.485028E+09 | 0.103251E+10 | 0.00 | 0.00 |
| July | 0.191625E+10 | 0.399800E+09 | 0.160527E+10 | 0.547638E+09 | 0.105763E+10 | 0.00 | 0.00 |
| August | 0.144192E+10 | 0.469597E+09 | 0.128803E+10 | 0.409901E+09 | 0.878129E+09 | 0.00 | 0.00 |
| September | 0.815696E+09 | 0.835822E+09 | 0.975407E+09 | 0.300739E+09 | 0.674668E+09 | 0.00 | 0.00 |
| October | 0.326346E+09 | 0.130480E+10 | 0.659944E+09 | 0.175369E+09 | 0.484575E+09 | 0.00 | 0.00 |
| November | 73016669.40 | 0.190045E+10 | 0.398981E+09 | 86569689.51 | 0.312412E+09 | 0.00 | 0.00 |
| December | 5076336.59 | 0.325558E+10 | 0.360218E+09 | 82782512.07 | 0.277435E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.927768E+10 | 0.181374E+11 | 0.115647E+11 | 0.371241E+10 | 0.785233E+10 | 0.00 | 0.00 |
| Minimum of Months | 5076336.59 | 0.399800E+09 | 0.360218E+09 | 82782512.07 | 0.277435E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.191625E+10 | 0.338014E+10 | 0.160527E+10 | 0.547638E+09 | 0.105763E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 111202.92 | 0.964425E+10 | 0.651970E+09 | 0.00 | 0.651970E+09 | 0.00 | 0.00 |
| February | 16712697.84 | 0.700919E+10 | 0.895516E+09 | 0.00 | 0.895516E+09 | 0.00 | 0.00 |
| March | 47018749.42 | 0.603956E+10 | 0.121590E+10 | 0.00 | 0.121590E+10 | 0.00 | 0.00 |
| April | 0.444817E+09 | 0.335617E+10 | 0.154361E+10 | 9769477.75 | 0.153384E+10 | 0.00 | 0.00 |
| May | 0.167320E+10 | 0.176969E+10 | 0.225271E+10 | 0.112680E+09 | 0.214003E+10 | 0.00 | 0.00 |
| June | 0.239819E+10 | 0.119946E+10 | 0.236795E+10 | 0.235816E+09 | 0.213213E+10 | 0.00 | 0.00 |
| July | 0.270321E+10 | 0.100874E+10 | 0.232653E+10 | 0.178421E+09 | 0.214811E+10 | 0.00 | 0.00 |
| August | 0.181541E+10 | 0.119281E+10 | 0.180236E+10 | 30052035.73 | 0.177231E+10 | 0.00 | 0.00 |
| September | 0.708469E+09 | 0.234193E+10 | 0.138095E+10 | 263621.97 | 0.138069E+10 | 0.00 | 0.00 |
| October | 0.116159E+09 | 0.381928E+10 | 0.101115E+10 | 0.00 | 0.101115E+10 | 0.00 | 0.00 |
| November | 24576469.25 | 0.552562E+10 | 0.643223E+09 | 0.00 | 0.643223E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.916579E+10 | 0.560279E+09 | 0.00 | 0.560279E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.994787E+10 | 0.520725E+11 | 0.166522E+11 | 0.567003E+09 | 0.160852E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.100874E+10 | 0.560279E+09 | 0.00 | 0.560279E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.270321E+10 | 0.964425E+10 | 0.236795E+10 | 0.235816E+09 | 0.214811E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.748176E+09 | 0.293007E+10 | 0.138905E+10 | 0.894242E+09 | 0.494808E+09 | 0.00 | 0.00 |
| February | 0.128022E+10 | 0.212335E+10 | 0.175247E+10 | 0.111163E+10 | 0.640846E+09 | 0.00 | 0.00 |
| March | 0.153303E+10 | 0.187629E+10 | 0.192290E+10 | 0.117197E+10 | 0.750929E+09 | 0.00 | 0.00 |
| April | 0.178378E+10 | 0.114123E+10 | 0.190490E+10 | 0.104178E+10 | 0.863116E+09 | 0.00 | 0.00 |
| May | 0.211128E+10 | 0.684803E+09 | 0.195393E+10 | 0.840085E+09 | 0.111385E+10 | 0.00 | 0.00 |
| June | 0.204909E+10 | 0.457751E+09 | 0.174826E+10 | 0.653127E+09 | 0.109513E+10 | 0.00 | 0.00 |
| July | 0.241447E+10 | 0.436791E+09 | 0.195691E+10 | 0.810977E+09 | 0.114594E+10 | 0.00 | 0.00 |
| August | 0.218544E+10 | 0.527677E+09 | 0.185042E+10 | 0.840761E+09 | 0.100965E+10 | 0.00 | 0.00 |
| September | 0.171640E+10 | 0.886856E+09 | 0.169543E+10 | 0.879668E+09 | 0.815761E+09 | 0.00 | 0.00 |
| October | 0.112325E+10 | 0.131300E+10 | 0.135293E+10 | 0.737694E+09 | 0.615241E+09 | 0.00 | 0.00 |
| November | 0.686203E+09 | 0.176437E+10 | 0.103367E+10 | 0.589686E+09 | 0.443979E+09 | 0.00 | 0.00 |
| December | 0.476990E+09 | 0.288842E+10 | 0.102939E+10 | 0.606523E+09 | 0.422869E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.181083E+11 | 0.170306E+11 | 0.195903E+11 | 0.101781E+11 | 0.941212E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.476990E+09 | 0.436791E+09 | 0.102939E+10 | 0.589686E+09 | 0.422869E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.241447E+10 | 0.293007E+10 | 0.195691E+10 | 0.117197E+10 | 0.114594E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.354294E+10 | 0.790589E+10 | 0.481922E+10 | 0.341544E+10 | 0.140377E+10 | 0.00 | 0.00 |
| February | 0.519398E+10 | 0.570983E+10 | 0.602433E+10 | 0.422332E+10 | 0.180101E+10 | 0.00 | 0.00 |
| March | 0.523331E+10 | 0.517507E+10 | 0.589744E+10 | 0.393264E+10 | 0.196480E+10 | 0.00 | 0.00 |
| April | 0.504104E+10 | 0.334936E+10 | 0.508550E+10 | 0.297622E+10 | 0.210927E+10 | 0.00 | 0.00 |
| May | 0.462182E+10 | 0.199404E+10 | 0.425132E+10 | 0.163563E+10 | 0.261569E+10 | 0.00 | 0.00 |
| June | 0.429606E+10 | 0.132961E+10 | 0.359533E+10 | 0.110784E+10 | 0.248750E+10 | 0.00 | 0.00 |
| July | 0.530392E+10 | 0.114676E+10 | 0.410803E+10 | 0.148806E+10 | 0.261997E+10 | 0.00 | 0.00 |
| August | 0.553954E+10 | 0.138967E+10 | 0.452147E+10 | 0.209453E+10 | 0.242694E+10 | 0.00 | 0.00 |
| September | 0.511559E+10 | 0.246107E+10 | 0.481244E+10 | 0.274750E+10 | 0.206493E+10 | 0.00 | 0.00 |
| October | 0.390539E+10 | 0.365668E+10 | 0.428003E+10 | 0.264825E+10 | 0.163178E+10 | 0.00 | 0.00 |
| November | 0.285993E+10 | 0.485937E+10 | 0.353149E+10 | 0.229390E+10 | 0.123759E+10 | 0.00 | 0.00 |
| December | 0.233864E+10 | 0.780527E+10 | 0.348234E+10 | 0.230099E+10 | 0.118135E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.529921E+11 | 0.467826E+11 | 0.544089E+11 | 0.308643E+11 | 0.235446E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.233864E+10 | 0.114676E+10 | 0.348234E+10 | 0.110784E+10 | 0.118135E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.553954E+10 | 0.790589E+10 | 0.602433E+10 | 0.422332E+10 | 0.261997E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 29834634.85 | 0.521960E+09 | 0.103382E+09 | 43290087.88 | 60091432.06 | 0.00 | 0.00 |
| February | 83145564.23 | 0.376897E+09 | 0.152138E+09 | 69486688.70 | 82651674.54 | 0.00 | 0.00 |
| March | 0.155435E+09 | 0.324838E+09 | 0.221653E+09 | 0.113418E+09 | 0.108234E+09 | 0.00 | 0.00 |
| April | 0.241396E+09 | 0.192344E+09 | 0.274015E+09 | 0.138786E+09 | 0.135229E+09 | 0.00 | 0.00 |
| May | 0.372165E+09 | 0.112010E+09 | 0.347899E+09 | 0.165949E+09 | 0.181950E+09 | 0.00 | 0.00 |
| June | 0.373360E+09 | 75771076.40 | 0.324885E+09 | 0.140478E+09 | 0.184407E+09 | 0.00 | 0.00 |
| July | 0.435098E+09 | 67008852.72 | 0.358408E+09 | 0.166623E+09 | 0.191785E+09 | 0.00 | 0.00 |
| August | 0.344384E+09 | 78477185.78 | 0.294946E+09 | 0.134022E+09 | 0.160924E+09 | 0.00 | 0.00 |
| September | 0.213821E+09 | 0.139091E+09 | 0.223076E+09 | 0.100225E+09 | 0.122851E+09 | 0.00 | 0.00 |
| October | 0.100572E+09 | 0.216024E+09 | 0.145616E+09 | 58456537.20 | 87159171.73 | 0.00 | 0.00 |
| November | 33480087.70 | 0.305930E+09 | 85586924.79 | 28856659.36 | 56730265.43 | 0.00 | 0.00 |
| December | 15714326.78 | 0.506431E+09 | 78839157.79 | 27594262.67 | 51244895.12 | 0.00 | 0.00 |
| Annual Sum or Average | 0.239840E+10 | 0.291678E+10 | 0.261044E+10 | 0.118718E+10 | 0.142326E+10 | 0.00 | 0.00 |
| Minimum of Months | 15714326.78 | 67008852.72 | 78839157.79 | 27594262.67 | 51244895.12 | 0.00 | 0.00 |
| Maximum of Months | 0.435098E+09 | 0.521960E+09 | 0.358408E+09 | 0.166623E+09 | 0.191785E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 26054184.36 | 0.337931E+10 | 0.456508E+09 | 0.129870E+09 | 0.326638E+09 | 0.00 | 0.00 |
| February | 0.188398E+09 | 0.239723E+10 | 0.658034E+09 | 0.208459E+09 | 0.449575E+09 | 0.00 | 0.00 |
| March | 0.418652E+09 | 0.201316E+10 | 0.938901E+09 | 0.340253E+09 | 0.598647E+09 | 0.00 | 0.00 |
| April | 0.846642E+09 | 0.111650E+10 | 0.117038E+10 | 0.419057E+09 | 0.751323E+09 | 0.00 | 0.00 |
| May | 0.153866E+10 | 0.631369E+09 | 0.155551E+10 | 0.527041E+09 | 0.102847E+10 | 0.00 | 0.00 |
| June | 0.170307E+10 | 0.429421E+09 | 0.152511E+10 | 0.485704E+09 | 0.103940E+10 | 0.00 | 0.00 |
| July | 0.192497E+10 | 0.399109E+09 | 0.161295E+10 | 0.548143E+09 | 0.106480E+10 | 0.00 | 0.00 |
| August | 0.144894E+10 | 0.469350E+09 | 0.129379E+10 | 0.409950E+09 | 0.883839E+09 | 0.00 | 0.00 |
| September | 0.820297E+09 | 0.835627E+09 | 0.979575E+09 | 0.300739E+09 | 0.678836E+09 | 0.00 | 0.00 |
| October | 0.328434E+09 | 0.130444E+10 | 0.662695E+09 | 0.175369E+09 | 0.487325E+09 | 0.00 | 0.00 |
| November | 73543797.52 | 0.189981E+10 | 0.400797E+09 | 86569689.51 | 0.314227E+09 | 0.00 | 0.00 |
| December | 5140877.78 | 0.325497E+10 | 0.361754E+09 | 82782512.07 | 0.278971E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.932280E+10 | 0.181303E+11 | 0.116160E+11 | 0.371394E+10 | 0.790206E+10 | 0.00 | 0.00 |
| Minimum of Months | 5140877.78 | 0.399109E+09 | 0.361754E+09 | 82782512.07 | 0.278971E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.192497E+10 | 0.337931E+10 | 0.161295E+10 | 0.548143E+09 | 0.106480E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 165531.65 | 0.963956E+10 | 0.661402E+09 | 0.00 | 0.661402E+09 | 0.00 | 0.00 |
| February | 18230907.96 | 0.700063E+10 | 0.909156E+09 | 0.00 | 0.909156E+09 | 0.00 | 0.00 |
| March | 50582385.23 | 0.602666E+10 | 0.123474E+10 | 0.00 | 0.123474E+10 | 0.00 | 0.00 |
| April | 0.460009E+09 | 0.334898E+10 | 0.156726E+10 | 9969638.42 | 0.155729E+10 | 0.00 | 0.00 |
| May | 0.170839E+10 | 0.176687E+10 | 0.228814E+10 | 0.115891E+09 | 0.217224E+10 | 0.00 | 0.00 |
| June | 0.244433E+10 | 0.119717E+10 | 0.241116E+10 | 0.243312E+09 | 0.216785E+10 | 0.00 | 0.00 |
| July | 0.275057E+10 | 0.100746E+10 | 0.236833E+10 | 0.183847E+09 | 0.218448E+10 | 0.00 | 0.00 |
| August | 0.184986E+10 | 0.119315E+10 | 0.183172E+10 | 30911486.76 | 0.180081E+10 | 0.00 | 0.00 |
| September | 0.728549E+09 | 0.234064E+10 | 0.140137E+10 | 263621.97 | 0.140111E+10 | 0.00 | 0.00 |
| October | 0.122207E+09 | 0.381452E+10 | 0.102462E+10 | 0.00 | 0.102462E+10 | 0.00 | 0.00 |
| November | 25159096.13 | 0.552129E+10 | 0.652117E+09 | 0.00 | 0.652117E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.916284E+10 | 0.567803E+09 | 0.00 | 0.567803E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.101581E+11 | 0.520198E+11 | 0.169178E+11 | 0.584195E+09 | 0.163336E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.100746E+10 | 0.567803E+09 | 0.00 | 0.567803E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.275057E+10 | 0.963956E+10 | 0.241116E+10 | 0.243312E+09 | 0.218448E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.763909E+09 | 0.291690E+10 | 0.141355E+10 | 0.912142E+09 | 0.501412E+09 | 0.00 | 0.00 |
| February | 0.128290E+10 | 0.212121E+10 | 0.175760E+10 | 0.111298E+10 | 0.644611E+09 | 0.00 | 0.00 |
| March | 0.153677E+10 | 0.187687E+10 | 0.192719E+10 | 0.117197E+10 | 0.755222E+09 | 0.00 | 0.00 |
| April | 0.178742E+10 | 0.114410E+10 | 0.191020E+10 | 0.104178E+10 | 0.868417E+09 | 0.00 | 0.00 |
| May | 0.211621E+10 | 0.688496E+09 | 0.196087E+10 | 0.840085E+09 | 0.112078E+10 | 0.00 | 0.00 |
| June | 0.205454E+10 | 0.460805E+09 | 0.175556E+10 | 0.653127E+09 | 0.110243E+10 | 0.00 | 0.00 |
| July | 0.241878E+10 | 0.441401E+09 | 0.196458E+10 | 0.810977E+09 | 0.115360E+10 | 0.00 | 0.00 |
| August | 0.218905E+10 | 0.532696E+09 | 0.185677E+10 | 0.840761E+09 | 0.101601E+10 | 0.00 | 0.00 |
| September | 0.171877E+10 | 0.892113E+09 | 0.170009E+10 | 0.879668E+09 | 0.820418E+09 | 0.00 | 0.00 |
| October | 0.112426E+10 | 0.131895E+10 | 0.135667E+10 | 0.738150E+09 | 0.618516E+09 | 0.00 | 0.00 |
| November | 0.692635E+09 | 0.176319E+10 | 0.104320E+10 | 0.595300E+09 | 0.447900E+09 | 0.00 | 0.00 |
| December | 0.499922E+09 | 0.287198E+10 | 0.106222E+10 | 0.630304E+09 | 0.431914E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.181852E+11 | 0.170287E+11 | 0.197085E+11 | 0.102273E+11 | 0.948123E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.499922E+09 | 0.441401E+09 | 0.104320E+10 | 0.595300E+09 | 0.431914E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.241878E+10 | 0.291690E+10 | 0.196458E+10 | 0.117197E+10 | 0.115360E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.364855E+10 | 0.783723E+10 | 0.496221E+10 | 0.352204E+10 | 0.144017E+10 | 0.00 | 0.00 |
| February | 0.521342E+10 | 0.569248E+10 | 0.605749E+10 | 0.423686E+10 | 0.182063E+10 | 0.00 | 0.00 |
| March | 0.524999E+10 | 0.517605E+10 | 0.591631E+10 | 0.393265E+10 | 0.198365E+10 | 0.00 | 0.00 |
| April | 0.505738E+10 | 0.335993E+10 | 0.510878E+10 | 0.297624E+10 | 0.213254E+10 | 0.00 | 0.00 |
| May | 0.464494E+10 | 0.200832E+10 | 0.428177E+10 | 0.163564E+10 | 0.264614E+10 | 0.00 | 0.00 |
| June | 0.432061E+10 | 0.134194E+10 | 0.362740E+10 | 0.110784E+10 | 0.251956E+10 | 0.00 | 0.00 |
| July | 0.532471E+10 | 0.116526E+10 | 0.414167E+10 | 0.148806E+10 | 0.265361E+10 | 0.00 | 0.00 |
| August | 0.555583E+10 | 0.141080E+10 | 0.454937E+10 | 0.209454E+10 | 0.245483E+10 | 0.00 | 0.00 |
| September | 0.512713E+10 | 0.248365E+10 | 0.483300E+10 | 0.274757E+10 | 0.208543E+10 | 0.00 | 0.00 |
| October | 0.390922E+10 | 0.368486E+10 | 0.429657E+10 | 0.265012E+10 | 0.164645E+10 | 0.00 | 0.00 |
| November | 0.290139E+10 | 0.484564E+10 | 0.359096E+10 | 0.233098E+10 | 0.125998E+10 | 0.00 | 0.00 |
| December | 0.246412E+10 | 0.773054E+10 | 0.364646E+10 | 0.242068E+10 | 0.122578E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.534173E+11 | 0.467367E+11 | 0.550120E+11 | 0.311432E+11 | 0.238688E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.246412E+10 | 0.116526E+10 | 0.359096E+10 | 0.110784E+10 | 0.122578E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.555583E+10 | 0.783723E+10 | 0.605749E+10 | 0.423686E+10 | 0.265361E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 29813216.53 | 0.522223E+09 | 0.103382E+09 | 43290087.88 | 60091432.06 | 0.00 | 0.00 |
| February | 83104980.25 | 0.377112E+09 | 0.152138E+09 | 69486688.70 | 82651674.54 | 0.00 | 0.00 |
| March | 0.155301E+09 | 0.325247E+09 | 0.221653E+09 | 0.113418E+09 | 0.108234E+09 | 0.00 | 0.00 |
| April | 0.240551E+09 | 0.193953E+09 | 0.274015E+09 | 0.138786E+09 | 0.135229E+09 | 0.00 | 0.00 |
| May | 0.370710E+09 | 0.113742E+09 | 0.347899E+09 | 0.165949E+09 | 0.181950E+09 | 0.00 | 0.00 |
| June | 0.371840E+09 | 77233058.08 | 0.324885E+09 | 0.140478E+09 | 0.184407E+09 | 0.00 | 0.00 |
| July | 0.432745E+09 | 68989666.54 | 0.358408E+09 | 0.166623E+09 | 0.191785E+09 | 0.00 | 0.00 |
| August | 0.342371E+09 | 80706289.13 | 0.294946E+09 | 0.134022E+09 | 0.160924E+09 | 0.00 | 0.00 |
| September | 0.212409E+09 | 0.141639E+09 | 0.223076E+09 | 0.100225E+09 | 0.122851E+09 | 0.00 | 0.00 |
| October | 99677388.91 | 0.219178E+09 | 0.145616E+09 | 58456537.20 | 87159171.73 | 0.00 | 0.00 |
| November | 33348502.07 | 0.307177E+09 | 85586924.79 | 28856659.36 | 56730265.43 | 0.00 | 0.00 |
| December | 15696002.91 | 0.506751E+09 | 78839157.79 | 27594262.67 | 51244895.12 | 0.00 | 0.00 |
| Annual Sum or Average | 0.238757E+10 | 0.293395E+10 | 0.261044E+10 | 0.118718E+10 | 0.142326E+10 | 0.00 | 0.00 |
| Minimum of Months | 15696002.91 | 68989666.54 | 78839157.79 | 27594262.67 | 51244895.12 | 0.00 | 0.00 |
| Maximum of Months | 0.432745E+09 | 0.522223E+09 | 0.358408E+09 | 0.166623E+09 | 0.191785E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 28802885.96 | 0.336397E+10 | 0.480615E+09 | 0.129870E+09 | 0.350746E+09 | 0.00 | 0.00 |
| February | 0.202191E+09 | 0.238032E+10 | 0.692931E+09 | 0.208459E+09 | 0.484471E+09 | 0.00 | 0.00 |
| March | 0.447992E+09 | 0.199644E+10 | 0.987127E+09 | 0.340253E+09 | 0.646873E+09 | 0.00 | 0.00 |
| April | 0.897303E+09 | 0.111421E+10 | 0.123077E+10 | 0.419547E+09 | 0.811218E+09 | 0.00 | 0.00 |
| May | 0.161751E+10 | 0.636096E+09 | 0.163771E+10 | 0.529833E+09 | 0.110787E+10 | 0.00 | 0.00 |
| June | 0.179121E+10 | 0.430861E+09 | 0.161620E+10 | 0.491954E+09 | 0.112424E+10 | 0.00 | 0.00 |
| July | 0.201451E+10 | 0.405163E+09 | 0.170842E+10 | 0.554206E+09 | 0.115422E+10 | 0.00 | 0.00 |
| August | 0.152279E+10 | 0.482704E+09 | 0.136577E+10 | 0.410323E+09 | 0.955448E+09 | 0.00 | 0.00 |
| September | 0.870227E+09 | 0.846062E+09 | 0.103191E+10 | 0.300762E+09 | 0.731153E+09 | 0.00 | 0.00 |
| October | 0.352589E+09 | 0.130931E+10 | 0.697073E+09 | 0.175369E+09 | 0.521704E+09 | 0.00 | 0.00 |
| November | 80047217.60 | 0.189346E+10 | 0.423505E+09 | 86569689.51 | 0.336936E+09 | 0.00 | 0.00 |
| December | 6096191.21 | 0.324323E+10 | 0.380954E+09 | 82782512.07 | 0.298172E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.983127E+10 | 0.181018E+11 | 0.122530E+11 | 0.372993E+10 | 0.852305E+10 | 0.00 | 0.00 |
| Minimum of Months | 6096191.21 | 0.405163E+09 | 0.380954E+09 | 82782512.07 | 0.298172E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.201451E+10 | 0.336397E+10 | 0.170842E+10 | 0.554206E+09 | 0.115422E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 1976921.54 | 0.631742E+10 | 0.544308E+09 | 0.00 | 0.544308E+09 | 0.00 | 0.00 |
| February | 33954294.63 | 0.453135E+10 | 0.755187E+09 | 0.00 | 0.755187E+09 | 0.00 | 0.00 |
| March | 91359259.16 | 0.385169E+10 | 0.102868E+10 | 0.00 | 0.102868E+10 | 0.00 | 0.00 |
| April | 0.492191E+09 | 0.215598E+10 | 0.130503E+10 | 10185497.80 | 0.129484E+10 | 0.00 | 0.00 |
| May | 0.151387E+10 | 0.116905E+10 | 0.189666E+10 | 0.102131E+09 | 0.179452E+10 | 0.00 | 0.00 |
| June | 0.210105E+10 | 0.796327E+09 | 0.204842E+10 | 0.225174E+09 | 0.182324E+10 | 0.00 | 0.00 |
| July | 0.230820E+10 | 0.696308E+09 | 0.202178E+10 | 0.173505E+09 | 0.184827E+10 | 0.00 | 0.00 |
| August | 0.157365E+10 | 0.828030E+09 | 0.153561E+10 | 26370801.23 | 0.150923E+10 | 0.00 | 0.00 |
| September | 0.701425E+09 | 0.156903E+10 | 0.115805E+10 | 283872.95 | 0.115777E+10 | 0.00 | 0.00 |
| October | 0.161205E+09 | 0.250698E+10 | 0.830893E+09 | 0.00 | 0.830893E+09 | 0.00 | 0.00 |
| November | 24722365.48 | 0.361087E+10 | 0.532410E+09 | 0.00 | 0.532410E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.602238E+10 | 0.461181E+09 | 0.00 | 0.461181E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.900360E+10 | 0.340554E+11 | 0.141182E+11 | 0.537651E+09 | 0.135805E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.696308E+09 | 0.461181E+09 | 0.00 | 0.461181E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.230820E+10 | 0.631742E+10 | 0.204842E+10 | 0.225174E+09 | 0.184827E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 969062.64 | 0.326699E+10 | 0.279928E+09 | 0.00 | 0.279928E+09 | 0.00 | 0.00 |
| February | 16838061.48 | 0.234983E+10 | 0.388379E+09 | 0.00 | 0.388379E+09 | 0.00 | 0.00 |
| March | 43265336.36 | 0.201270E+10 | 0.529030E+09 | 0.00 | 0.529030E+09 | 0.00 | 0.00 |
| April | 0.231748E+09 | 0.116952E+10 | 0.671153E+09 | 5238269.44 | 0.665915E+09 | 0.00 | 0.00 |
| May | 0.744962E+09 | 0.645509E+09 | 0.975417E+09 | 52524737.15 | 0.922892E+09 | 0.00 | 0.00 |
| June | 0.104594E+10 | 0.442477E+09 | 0.105346E+10 | 0.115804E+09 | 0.937661E+09 | 0.00 | 0.00 |
| July | 0.113662E+10 | 0.392860E+09 | 0.103977E+10 | 89231615.51 | 0.950534E+09 | 0.00 | 0.00 |
| August | 0.763416E+09 | 0.472361E+09 | 0.789735E+09 | 13562161.12 | 0.776172E+09 | 0.00 | 0.00 |
| September | 0.331814E+09 | 0.875887E+09 | 0.595565E+09 | 145992.18 | 0.595419E+09 | 0.00 | 0.00 |
| October | 70498777.75 | 0.137633E+10 | 0.427314E+09 | 0.00 | 0.427314E+09 | 0.00 | 0.00 |
| November | 11364485.13 | 0.191075E+10 | 0.273809E+09 | 0.00 | 0.273809E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.311988E+10 | 0.237178E+09 | 0.00 | 0.237178E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.439743E+10 | 0.180351E+11 | 0.726074E+10 | 0.276507E+09 | 0.698423E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.392860E+09 | 0.237178E+09 | 0.00 | 0.237178E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.113662E+10 | 0.326699E+10 | 0.105346E+10 | 0.115804E+09 | 0.950534E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 215210.64 | 0.163795E+10 | 0.128133E+09 | 17366502.83 | 0.110767E+09 | 0.00 | 0.00 |
| February | 53490286.03 | 0.115712E+10 | 0.234852E+09 | 71128542.58 | 0.163723E+09 | 0.00 | 0.00 |
| March | 0.268610E+09 | 0.982004E+09 | 0.463136E+09 | 0.224527E+09 | 0.238609E+09 | 0.00 | 0.00 |
| April | 0.565166E+09 | 0.596983E+09 | 0.664516E+09 | 0.351443E+09 | 0.313073E+09 | 0.00 | 0.00 |
| May | 0.889236E+09 | 0.355100E+09 | 0.854099E+09 | 0.432520E+09 | 0.421579E+09 | 0.00 | 0.00 |
| June | 0.887262E+09 | 0.247099E+09 | 0.784392E+09 | 0.359932E+09 | 0.424460E+09 | 0.00 | 0.00 |
| July | 0.104796E+10 | 0.220345E+09 | 0.878025E+09 | 0.433889E+09 | 0.444136E+09 | 0.00 | 0.00 |
| August | 0.820556E+09 | 0.253998E+09 | 0.720726E+09 | 0.348904E+09 | 0.371823E+09 | 0.00 | 0.00 |
| September | 0.460706E+09 | 0.418736E+09 | 0.513620E+09 | 0.234767E+09 | 0.278852E+09 | 0.00 | 0.00 |
| October | 0.144584E+09 | 0.642265E+09 | 0.275120E+09 | 90344308.25 | 0.184776E+09 | 0.00 | 0.00 |
| November | 11075651.25 | 0.938889E+09 | 0.126807E+09 | 17165802.93 | 0.109642E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.157903E+10 | 99021384.30 | 6610656.98 | 92410727.32 | 0.00 | 0.00 |
| Annual Sum or Average | 0.514886E+10 | 0.902951E+10 | 0.574245E+10 | 0.258860E+10 | 0.315385E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.220345E+09 | 99021384.30 | 6610656.98 | 92410727.32 | 0.00 | 0.00 |
| Maximum of Months | 0.104796E+10 | 0.163795E+10 | 0.878025E+09 | 0.433889E+09 | 0.444136E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.165328E+10 | 0.240165E+10 | 0.203474E+10 | 0.141552E+10 | 0.619217E+09 | 0.00 | 0.00 |
| February | 0.215063E+10 | 0.181899E+10 | 0.232713E+10 | 0.157183E+10 | 0.755306E+09 | 0.00 | 0.00 |
| March | 0.214761E+10 | 0.164715E+10 | 0.227018E+10 | 0.143671E+10 | 0.833472E+09 | 0.00 | 0.00 |
| April | 0.205051E+10 | 0.107715E+10 | 0.199037E+10 | 0.108032E+10 | 0.910051E+09 | 0.00 | 0.00 |
| May | 0.192138E+10 | 0.680625E+09 | 0.172915E+10 | 0.591157E+09 | 0.113800E+10 | 0.00 | 0.00 |
| June | 0.178576E+10 | 0.472015E+09 | 0.150149E+10 | 0.400212E+09 | 0.110127E+10 | 0.00 | 0.00 |
| July | 0.211033E+10 | 0.458720E+09 | 0.169633E+10 | 0.537390E+09 | 0.115894E+10 | 0.00 | 0.00 |
| August | 0.218513E+10 | 0.527135E+09 | 0.181159E+10 | 0.757773E+09 | 0.105381E+10 | 0.00 | 0.00 |
| September | 0.205358E+10 | 0.823068E+09 | 0.187788E+10 | 0.100011E+10 | 0.877769E+09 | 0.00 | 0.00 |
| October | 0.158632E+10 | 0.116467E+10 | 0.165703E+10 | 0.974583E+09 | 0.682449E+09 | 0.00 | 0.00 |
| November | 0.121611E+10 | 0.152600E+10 | 0.142844E+10 | 0.896488E+09 | 0.531948E+09 | 0.00 | 0.00 |
| December | 0.114667E+10 | 0.232306E+10 | 0.157106E+10 | 0.103017E+10 | 0.540898E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.220073E+11 | 0.149202E+11 | 0.218954E+11 | 0.116923E+11 | 0.102031E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.114667E+10 | 0.458720E+09 | 0.142844E+10 | 0.400212E+09 | 0.531948E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.218513E+10 | 0.240165E+10 | 0.232713E+10 | 0.157183E+10 | 0.115894E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 3142631.86 | 0.168390E+10 | 0.165661E+09 | 34353862.88 | 0.131308E+09 | 0.00 | 0.00 |
| February | 0.110136E+09 | 0.118379E+10 | 0.304054E+09 | 0.110059E+09 | 0.193996E+09 | 0.00 | 0.00 |
| March | 0.362495E+09 | 0.997491E+09 | 0.558555E+09 | 0.281759E+09 | 0.276796E+09 | 0.00 | 0.00 |
| April | 0.661241E+09 | 0.633820E+09 | 0.762423E+09 | 0.404785E+09 | 0.357638E+09 | 0.00 | 0.00 |
| May | 0.996804E+09 | 0.402073E+09 | 0.968172E+09 | 0.488107E+09 | 0.480065E+09 | 0.00 | 0.00 |
| June | 0.976866E+09 | 0.291775E+09 | 0.887627E+09 | 0.404670E+09 | 0.482957E+09 | 0.00 | 0.00 |
| July | 0.116283E+10 | 0.265352E+09 | 0.994607E+09 | 0.489129E+09 | 0.505478E+09 | 0.00 | 0.00 |
| August | 0.923757E+09 | 0.299562E+09 | 0.822718E+09 | 0.398062E+09 | 0.424656E+09 | 0.00 | 0.00 |
| September | 0.536821E+09 | 0.478297E+09 | 0.599200E+09 | 0.278333E+09 | 0.320866E+09 | 0.00 | 0.00 |
| October | 0.195575E+09 | 0.710745E+09 | 0.339143E+09 | 0.122726E+09 | 0.216417E+09 | 0.00 | 0.00 |
| November | 27898782.90 | 0.970023E+09 | 0.160302E+09 | 30762262.12 | 0.129539E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.163054E+10 | 0.123513E+09 | 14687435.58 | 0.108825E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.595757E+10 | 0.954737E+10 | 0.668597E+10 | 0.305743E+10 | 0.362854E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.265352E+09 | 0.123513E+09 | 14687435.58 | 0.108825E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.116283E+10 | 0.168390E+10 | 0.994607E+09 | 0.489129E+09 | 0.505478E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.149458E+10 | 0.603776E+10 | 0.296488E+10 | 0.186337E+10 | 0.110150E+10 | 0.00 | 0.00 |
| February | 0.253831E+10 | 0.444523E+10 | 0.358829E+10 | 0.217073E+10 | 0.141756E+10 | 0.00 | 0.00 |
| March | 0.313295E+10 | 0.398720E+10 | 0.404217E+10 | 0.235692E+10 | 0.168525E+10 | 0.00 | 0.00 |
| April | 0.388031E+10 | 0.253713E+10 | 0.425655E+10 | 0.230336E+10 | 0.195319E+10 | 0.00 | 0.00 |
| May | 0.428517E+10 | 0.156180E+10 | 0.421131E+10 | 0.166455E+10 | 0.254675E+10 | 0.00 | 0.00 |
| June | 0.471298E+10 | 0.110573E+10 | 0.417946E+10 | 0.164777E+10 | 0.253170E+10 | 0.00 | 0.00 |
| July | 0.522435E+10 | 0.104069E+10 | 0.442577E+10 | 0.179170E+10 | 0.263408E+10 | 0.00 | 0.00 |
| August | 0.449159E+10 | 0.125612E+10 | 0.396900E+10 | 0.169713E+10 | 0.227187E+10 | 0.00 | 0.00 |
| September | 0.355085E+10 | 0.197189E+10 | 0.359975E+10 | 0.178761E+10 | 0.181214E+10 | 0.00 | 0.00 |
| October | 0.223467E+10 | 0.288385E+10 | 0.278514E+10 | 0.143880E+10 | 0.134634E+10 | 0.00 | 0.00 |
| November | 0.138861E+10 | 0.373647E+10 | 0.216632E+10 | 0.118727E+10 | 0.979055E+09 | 0.00 | 0.00 |
| December | 0.101968E+10 | 0.594489E+10 | 0.229042E+10 | 0.134335E+10 | 0.947064E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.379541E+11 | 0.365088E+11 | 0.424791E+11 | 0.212526E+11 | 0.212265E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.101968E+10 | 0.104069E+10 | 0.216632E+10 | 0.118727E+10 | 0.947064E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.522435E+10 | 0.603776E+10 | 0.442577E+10 | 0.235692E+10 | 0.263408E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.150513E+09 | 0.583797E+10 | 0.152960E+10 | 0.570024E+09 | 0.959574E+09 | 0.00 | 0.00 |
| February | 0.105733E+10 | 0.417608E+10 | 0.235385E+10 | 0.105585E+10 | 0.129799E+10 | 0.00 | 0.00 |
| March | 0.239617E+10 | 0.368981E+10 | 0.366476E+10 | 0.198584E+10 | 0.167893E+10 | 0.00 | 0.00 |
| April | 0.441130E+10 | 0.246933E+10 | 0.512824E+10 | 0.308628E+10 | 0.204196E+10 | 0.00 | 0.00 |
| May | 0.619277E+10 | 0.157761E+10 | 0.624783E+10 | 0.329064E+10 | 0.295719E+10 | 0.00 | 0.00 |
| June | 0.693891E+10 | 0.112284E+10 | 0.650167E+10 | 0.354771E+10 | 0.295396E+10 | 0.00 | 0.00 |
| July | 0.744546E+10 | 0.108214E+10 | 0.679925E+10 | 0.380122E+10 | 0.299802E+10 | 0.00 | 0.00 |
| August | 0.563313E+10 | 0.121936E+10 | 0.532631E+10 | 0.279479E+10 | 0.253152E+10 | 0.00 | 0.00 |
| September | 0.355231E+10 | 0.181871E+10 | 0.385564E+10 | 0.190183E+10 | 0.195381E+10 | 0.00 | 0.00 |
| October | 0.157885E+10 | 0.270453E+10 | 0.237889E+10 | 0.931721E+09 | 0.144717E+10 | 0.00 | 0.00 |
| November | 0.445675E+09 | 0.359677E+10 | 0.137143E+10 | 0.427080E+09 | 0.944351E+09 | 0.00 | 0.00 |
| December | 48231708.98 | 0.573248E+10 | 0.119009E+10 | 0.353938E+09 | 0.836156E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.398506E+11 | 0.350276E+11 | 0.463476E+11 | 0.237469E+11 | 0.226006E+11 | 0.00 | 0.00 |
| Minimum of Months | 48231708.98 | 0.108214E+10 | 0.119009E+10 | 0.353938E+09 | 0.836156E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.744546E+10 | 0.583797E+10 | 0.679925E+10 | 0.380122E+10 | 0.299802E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 61937667.58 | 0.153250E+10 | 0.272756E+09 | 0.113856E+09 | 0.158900E+09 | 0.00 | 0.00 |
| February | 0.160298E+09 | 0.114814E+10 | 0.387133E+09 | 0.165133E+09 | 0.222000E+09 | 0.00 | 0.00 |
| March | 0.351544E+09 | 0.105173E+10 | 0.584011E+09 | 0.292947E+09 | 0.291064E+09 | 0.00 | 0.00 |
| April | 0.634829E+09 | 0.655313E+09 | 0.783492E+09 | 0.422598E+09 | 0.360894E+09 | 0.00 | 0.00 |
| May | 0.850755E+09 | 0.361135E+09 | 0.876234E+09 | 0.385200E+09 | 0.491034E+09 | 0.00 | 0.00 |
| June | 0.106776E+10 | 0.253460E+09 | 0.959959E+09 | 0.459199E+09 | 0.500760E+09 | 0.00 | 0.00 |
| July | 0.112342E+10 | 0.232093E+09 | 0.971753E+09 | 0.456272E+09 | 0.515482E+09 | 0.00 | 0.00 |
| August | 0.816422E+09 | 0.277619E+09 | 0.749224E+09 | 0.327461E+09 | 0.421762E+09 | 0.00 | 0.00 |
| September | 0.517736E+09 | 0.427329E+09 | 0.580647E+09 | 0.259893E+09 | 0.320754E+09 | 0.00 | 0.00 |
| October | 0.201799E+09 | 0.712137E+09 | 0.363312E+09 | 0.137766E+09 | 0.225546E+09 | 0.00 | 0.00 |
| November | 70438789.30 | 0.101525E+10 | 0.223826E+09 | 74829891.62 | 0.148996E+09 | 0.00 | 0.00 |
| December | 36836758.73 | 0.149342E+10 | 0.211047E+09 | 78006108.93 | 0.133041E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.589377E+10 | 0.916013E+10 | 0.696339E+10 | 0.317316E+10 | 0.379023E+10 | 0.00 | 0.00 |
| Minimum of Months | 36836758.73 | 0.232093E+09 | 0.211047E+09 | 74829891.62 | 0.133041E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.112342E+10 | 0.153250E+10 | 0.971753E+09 | 0.459199E+09 | 0.515482E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 4857952.61 | 0.615865E+10 | 0.818607E+09 | 0.213488E+09 | 0.605120E+09 | 0.00 | 0.00 |
| February | 0.181921E+09 | 0.434197E+10 | 0.115195E+10 | 0.309635E+09 | 0.842313E+09 | 0.00 | 0.00 |
| March | 0.578336E+09 | 0.375285E+10 | 0.167570E+10 | 0.549295E+09 | 0.112641E+10 | 0.00 | 0.00 |
| April | 0.140490E+10 | 0.221614E+10 | 0.220166E+10 | 0.795769E+09 | 0.140589E+10 | 0.00 | 0.00 |
| May | 0.236955E+10 | 0.131701E+10 | 0.268736E+10 | 0.761681E+09 | 0.192568E+10 | 0.00 | 0.00 |
| June | 0.307100E+10 | 0.958026E+09 | 0.291229E+10 | 0.958876E+09 | 0.195341E+10 | 0.00 | 0.00 |
| July | 0.322180E+10 | 0.897193E+09 | 0.292701E+10 | 0.929096E+09 | 0.199791E+10 | 0.00 | 0.00 |
| August | 0.229189E+10 | 0.105042E+10 | 0.226077E+10 | 0.623354E+09 | 0.163742E+10 | 0.00 | 0.00 |
| September | 0.130402E+10 | 0.164565E+10 | 0.174230E+10 | 0.487393E+09 | 0.125490E+10 | 0.00 | 0.00 |
| October | 0.443563E+09 | 0.253839E+10 | 0.115112E+10 | 0.258321E+09 | 0.892795E+09 | 0.00 | 0.00 |
| November | 86780099.24 | 0.365967E+10 | 0.720291E+09 | 0.140311E+09 | 0.579980E+09 | 0.00 | 0.00 |
| December | 2981467.01 | 0.596838E+10 | 0.656322E+09 | 0.146267E+09 | 0.510055E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.149616E+11 | 0.345044E+11 | 0.209054E+11 | 0.617348E+10 | 0.147319E+11 | 0.00 | 0.00 |
| Minimum of Months | 2981467.01 | 0.897193E+09 | 0.656322E+09 | 0.140311E+09 | 0.510055E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.322180E+10 | 0.615865E+10 | 0.292701E+10 | 0.958876E+09 | 0.199791E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 3807929.72 | 0.687576E+10 | 0.848222E+09 | 0.186015E+09 | 0.662207E+09 | 0.00 | 0.00 |
| February | 0.222037E+09 | 0.476313E+10 | 0.128840E+10 | 0.346423E+09 | 0.941974E+09 | 0.00 | 0.00 |
| March | 0.807593E+09 | 0.405477E+10 | 0.199362E+10 | 0.714275E+09 | 0.127935E+10 | 0.00 | 0.00 |
| April | 0.183502E+10 | 0.242944E+10 | 0.267085E+10 | 0.106762E+10 | 0.160323E+10 | 0.00 | 0.00 |
| May | 0.294197E+10 | 0.145523E+10 | 0.325010E+10 | 0.104599E+10 | 0.220411E+10 | 0.00 | 0.00 |
| June | 0.380917E+10 | 0.103472E+10 | 0.355871E+10 | 0.131326E+10 | 0.224545E+10 | 0.00 | 0.00 |
| July | 0.401382E+10 | 0.956246E+09 | 0.356890E+10 | 0.127403E+10 | 0.229487E+10 | 0.00 | 0.00 |
| August | 0.281778E+10 | 0.115111E+10 | 0.271846E+10 | 0.847099E+09 | 0.187136E+10 | 0.00 | 0.00 |
| September | 0.158804E+10 | 0.189789E+10 | 0.206788E+10 | 0.642438E+09 | 0.142544E+10 | 0.00 | 0.00 |
| October | 0.512701E+09 | 0.292550E+10 | 0.131873E+10 | 0.314108E+09 | 0.100462E+10 | 0.00 | 0.00 |
| November | 94235222.38 | 0.399564E+10 | 0.782280E+09 | 0.140680E+09 | 0.641600E+09 | 0.00 | 0.00 |
| December | 630816.90 | 0.665355E+10 | 0.666969E+09 | 0.111525E+09 | 0.555443E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.186468E+11 | 0.381930E+11 | 0.247331E+11 | 0.800346E+10 | 0.167297E+11 | 0.00 | 0.00 |
| Minimum of Months | 630816.90 | 0.956246E+09 | 0.666969E+09 | 0.111525E+09 | 0.555443E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.401382E+10 | 0.687576E+10 | 0.356890E+10 | 0.131326E+10 | 0.229487E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
| February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
| March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
| April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
| May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
| June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
| July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
| August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
| September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
| October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
| November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
| December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
| Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
| Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
| Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
| February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
| March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
| April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
| May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
| June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
| July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
| August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
| September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
| October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
| November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
| December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
| Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
| February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
| March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
| April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
| May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
| June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
| July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
| August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
| September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
| October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
| November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
| December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
| Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
| February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
| March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
| April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
| May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
| June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
| July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
| August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
| September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
| October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
| November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
| December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
| Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
| February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
| March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
| April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
| May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
| June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
| July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
| August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
| September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
| October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
| November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
| December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
| Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER G WATER HEATER
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.274953E+10 | -0.258087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -168656833.5 | 82.17 | 0.00 | 0.00 |
| February | 0.248442E+10 | -0.233507E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -149343371.0 | 82.17 | 0.00 | 0.00 |
| March | 0.298921E+10 | -0.282667E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162542160.7 | 82.17 | 0.00 | 0.00 |
| April | 0.261258E+10 | -0.245797E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154610069.1 | 82.17 | 0.00 | 0.00 |
| May | 0.286356E+10 | -0.270377E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159792725.7 | 82.17 | 0.00 | 0.00 |
| June | 0.184159E+10 | -0.168695E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154640835.1 | 82.17 | 0.00 | 0.00 |
| July | 0.768508E+09 | -609202512.0 | 0.00 | 0.00 | 744.00 | 0.00 | -159304991.9 | 82.17 | 0.00 | 0.00 |
| August | 0.860476E+09 | -700582930.7 | 0.00 | 0.00 | 744.00 | 0.00 | -159893215.2 | 82.17 | 0.00 | 0.00 |
| September | 0.168791E+10 | -0.153359E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154318013.1 | 82.17 | 0.00 | 0.00 |
| October | 0.274040E+10 | -0.258087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159532942.2 | 82.17 | 0.00 | 0.00 |
| November | 0.273745E+10 | -0.258087E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -156579634.6 | 82.17 | 0.00 | 0.00 |
| December | 0.262658E+10 | -0.245797E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -168607104.8 | 82.17 | 0.00 | 0.00 |
| Annual Sum or Average | 0.269622E+11 | -0.250544E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.190782E+10 | 82.17 | 0.00 | 0.00 |
| Minimum of Months | 0.768508E+09 | -0.282667E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -168656833.5 | 82.17 | 0.00 | 0.00 |
| Maximum of Months | 0.298921E+10 | -609202512.0 | 0.00 | 0.00 | 744.00 | 0.00 | -149343371.0 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.123577E+11 | -0.112548E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.110290E+10 | 60.05 | 0.00 | 0.00 |
| February | 0.113850E+11 | -0.104123E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -972756789.7 | 60.05 | 0.00 | 0.00 |
| March | 0.135905E+11 | -0.125536E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103689E+10 | 60.05 | 0.00 | 0.00 |
| April | 0.115218E+11 | -0.105953E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -926479124.6 | 60.05 | 0.00 | 0.00 |
| May | 0.119747E+11 | -0.110932E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -881522530.3 | 60.05 | 0.00 | 0.00 |
| June | 0.739445E+10 | -0.655688E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -837564375.4 | 60.05 | 0.00 | 0.00 |
| July | 0.309781E+10 | -0.222315E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -874658395.6 | 60.05 | 0.00 | 0.00 |
| August | 0.337530E+10 | -0.248652E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -888782365.2 | 60.05 | 0.00 | 0.00 |
| September | 0.634782E+10 | -0.549734E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -850473399.8 | 60.05 | 0.00 | 0.00 |
| October | 0.105166E+11 | -0.957400E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -942582753.9 | 60.05 | 0.00 | 0.00 |
| November | 0.111123E+11 | -0.101238E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988502574.5 | 60.05 | 0.00 | 0.00 |
| December | 0.113098E+11 | -0.102180E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.109181E+10 | 60.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.113984E+12 | -0.102589E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.113949E+11 | 60.05 | 0.00 | 0.00 |
| Minimum of Months | 0.309781E+10 | -0.125536E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.110290E+10 | 60.05 | 0.00 | 0.00 |
| Maximum of Months | 0.135905E+11 | -0.222315E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -837564375.4 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 243.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 265.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 254.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 296.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 401.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 409.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 352.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 344.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 255.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3785.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.557619E+10 | 9394.93 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.357353E+10 | 9229.94 | 21-FEB-07:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.282407E+10 | 9234.47 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.857925E+09 | 9232.95 | 24-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 83017903.35 | 9236.80 | 30-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1783817.68 | 7205.36 | 12-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 3189645.96 | 8244.73 | 10-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 46798057.87 | 9244.76 | 16-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 2239439.26 | 8793.77 | 29-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.271277E+09 | 9236.17 | 10-OCT-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.169295E+10 | 9234.45 | 03-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.490688E+10 | 9236.85 | 18-DEC-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.198398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 1783817.68 | 7205.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.557619E+10 | 9394.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.153735E+11 | 34984.34 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.906485E+10 | 34379.65 | 21-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.708139E+10 | 34376.37 | 28-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.191776E+10 | 34373.13 | 10-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.150485E+09 | 34379.08 | 15-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 10362881.02 | 30969.11 | 10-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.134309E+09 | 34448.34 | 16-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.590530E+09 | 34372.84 | 05-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.443453E+10 | 34399.10 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.133791E+11 | 34391.30 | 18-DEC-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.521368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.153735E+11 | 34984.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.672280E+10 | 8191.39 | 06-JAN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.445279E+10 | 7939.47 | 21-FEB-07:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.361674E+10 | 7949.05 | 21-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.953076E+09 | 7963.11 | 26-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 73933034.72 | 7940.91 | 03-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 405863.78 | 6140.96 | 18-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.296914E+09 | 7966.41 | 31-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.239815E+10 | 7992.96 | 21-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.576895E+10 | 7950.56 | 06-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.242838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.672280E+10 | 8191.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.686539E+10 | 8777.36 | 06-JAN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.481579E+10 | 8442.12 | 13-FEB-06:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.391004E+10 | 8470.90 | 21-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.127873E+10 | 8488.69 | 24-APR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.133345E+09 | 8490.62 | 16-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 2001061.75 | 7172.69 | 12-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 6820769.75 | 8519.21 | 10-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 82542698.99 | 8541.30 | 16-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 7252768.89 | 8490.50 | 15-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.419530E+09 | 8491.48 | 02-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.220470E+10 | 8489.56 | 02-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.586002E+10 | 8466.74 | 01-DEC-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.255862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 2001061.75 | 7172.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.686539E+10 | 8777.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.205275E+11 | 33754.32 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.138196E+11 | 33173.86 | 21-FEB-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.109334E+11 | 33207.94 | 21-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.324334E+10 | 33182.27 | 24-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.304590E+09 | 33188.38 | 22-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 407439.22 | 4753.46 | 05-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 35137690.56 | 33238.10 | 10-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.323020E+09 | 33261.25 | 15-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 10656662.96 | 27963.10 | 13-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.100096E+10 | 33193.78 | 20-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.607461E+10 | 33192.66 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.169624E+11 | 33184.53 | 18-DEC-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.732357E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 407439.22 | 4753.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.205275E+11 | 33754.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.572655E+10 | 9334.12 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.360778E+10 | 9170.30 | 21-FEB-07:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.284720E+10 | 9174.80 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.873610E+09 | 9173.31 | 24-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 87878331.90 | 9177.16 | 30-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 2300317.17 | 8208.73 | 12-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 4323006.86 | 9184.77 | 10-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 51407039.81 | 9185.11 | 16-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 2333451.82 | 9074.12 | 29-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.277655E+09 | 9176.49 | 10-OCT-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.172700E+10 | 9174.77 | 03-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.507152E+10 | 9177.12 | 18-DEC-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.202796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 2300317.17 | 8208.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.572655E+10 | 9334.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.157481E+11 | 34571.25 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.898104E+10 | 33974.06 | 21-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.696500E+10 | 33970.81 | 28-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.189844E+10 | 33967.59 | 10-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.152991E+09 | 33973.54 | 15-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 13596012.24 | 34039.86 | 10-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.147949E+09 | 34042.27 | 16-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.591812E+09 | 33967.35 | 05-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.448774E+10 | 33993.54 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.138099E+11 | 33985.44 | 18-DEC-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.527966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.157481E+11 | 34571.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.680348E+10 | 8167.39 | 06-JAN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.446249E+10 | 7897.51 | 13-FEB-06:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.361803E+10 | 7918.37 | 21-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.955805E+09 | 7921.03 | 27-APR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 75297701.52 | 7917.87 | 03-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 466956.39 | 6636.66 | 18-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.299036E+09 | 7940.81 | 11-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.242820E+10 | 7969.71 | 21-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.586309E+10 | 7916.84 | 06-DEC-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.245059E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.680348E+10 | 8167.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.687089E+10 | 8782.14 | 06-JAN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.481647E+10 | 8467.38 | 21-FEB-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.390966E+10 | 8475.47 | 21-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.127905E+10 | 8493.27 | 24-APR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.133543E+09 | 8495.20 | 16-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1994024.39 | 7148.96 | 12-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 6979115.54 | 8523.81 | 10-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 83758779.04 | 8545.93 | 16-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 7367747.56 | 8495.09 | 15-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.420792E+09 | 8496.06 | 02-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.220828E+10 | 8494.15 | 02-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.586671E+10 | 8471.31 | 01-DEC-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.256055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 1994024.39 | 7148.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.687089E+10 | 8782.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.205363E+11 | 33740.68 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.138089E+11 | 33160.51 | 21-FEB-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.109184E+11 | 33194.59 | 21-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.323661E+10 | 33168.94 | 24-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.303474E+09 | 33175.05 | 22-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 393940.28 | 4595.97 | 05-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 35425103.08 | 33224.80 | 10-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.325707E+09 | 33247.95 | 15-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 10857708.20 | 28252.20 | 13-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.100029E+10 | 33180.46 | 20-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.607757E+10 | 33179.37 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.169778E+11 | 33171.16 | 18-DEC-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.732317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 393940.28 | 4595.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.205363E+11 | 33740.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.568099E+10 | 9340.89 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.360067E+10 | 9176.94 | 21-FEB-07:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.284309E+10 | 9181.44 | 22-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.863622E+09 | 9179.96 | 24-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 83930126.01 | 9183.80 | 30-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1914035.84 | 7530.90 | 12-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 3513549.61 | 8571.45 | 10-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 47618552.27 | 9191.76 | 16-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 2080572.94 | 8200.34 | 29-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.266201E+09 | 9183.13 | 10-OCT-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.170770E+10 | 9181.42 | 03-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.502411E+10 | 9183.77 | 18-DEC-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.201254E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 1914035.84 | 7530.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.568099E+10 | 9340.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.155314E+11 | 34703.24 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.895015E+10 | 34103.67 | 21-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.695953E+10 | 34100.42 | 28-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.186816E+10 | 34097.19 | 10-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.143299E+09 | 34102.34 | 08-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 10221638.46 | 30896.07 | 10-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.125887E+09 | 34172.06 | 16-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.537786E+09 | 34088.77 | 31-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.439132E+10 | 34123.16 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.136072E+11 | 34115.13 | 18-DEC-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.521250E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.155314E+11 | 34703.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.674532E+10 | 8223.92 | 06-JAN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.442293E+10 | 7991.06 | 21-FEB-07:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.356046E+10 | 8013.29 | 21-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.898528E+09 | 8014.66 | 26-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 64951336.33 | 7992.51 | 03-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 112333.76 | 1872.23 | 18-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.237484E+09 | 8017.98 | 31-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.233475E+10 | 8044.52 | 21-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.580401E+10 | 8001.84 | 06-DEC-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.240685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.674532E+10 | 8223.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.686149E+10 | 8842.02 | 06-JAN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.479420E+10 | 8546.70 | 21-FEB-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.387219E+10 | 8577.02 | 21-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.124120E+10 | 8572.64 | 24-APR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.122215E+09 | 8574.58 | 16-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1391760.74 | 5506.31 | 12-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 4400261.77 | 8624.09 | 18-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 70893218.86 | 8625.75 | 25-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 6200277.44 | 8574.41 | 29-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.400677E+09 | 8575.35 | 11-OCT-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.219380E+10 | 8573.52 | 02-NOV-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.586207E+10 | 8550.67 | 01-DEC-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.254307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 1391760.74 | 5506.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.686149E+10 | 8842.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.137944E+11 | 22493.68 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.923842E+10 | 22107.68 | 21-FEB-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.725744E+10 | 22130.48 | 21-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.208289E+10 | 22113.50 | 24-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.175254E+09 | 22117.61 | 22-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 10134611.91 | 20844.91 | 18-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.163377E+09 | 22152.95 | 16-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 4291516.98 | 13732.49 | 06-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.612575E+09 | 22121.31 | 20-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.405386E+10 | 22120.88 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.114281E+11 | 22114.50 | 18-DEC-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.488207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.137944E+11 | 22493.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.536483E+10 | 11369.19 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.325875E+10 | 11173.33 | 21-FEB-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.221645E+10 | 11173.26 | 27-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.447067E+09 | 11176.08 | 24-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 36391652.85 | 11172.49 | 08-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 1302070.12 | 11187.32 | 18-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 65875121.89 | 11178.61 | 10-OCT-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.983705E+09 | 11179.39 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.425751E+10 | 11177.05 | 18-DEC-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.166319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.536483E+10 | 11369.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.189221E+11 | 18756.94 | 06-JAN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.121466E+11 | 17615.96 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.889305E+10 | 17619.55 | 21-MAR-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.158074E+10 | 17610.05 | 10-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 63434531.18 | 17602.93 | 01-MAY-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.741305E+09 | 17676.99 | 31-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.661162E+10 | 17744.72 | 21-NOV-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.159674E+11 | 17619.93 | 06-DEC-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.649262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.189221E+11 | 18756.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.158532E+11 | 10838.70 | 06-JAN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.123244E+11 | 10179.39 | 07-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.123907E+11 | 10193.72 | 30-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.648264E+10 | 11008.23 | 21-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.234147E+10 | 11021.11 | 30-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.744999E+09 | 11031.51 | 09-JUN-14:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.438742E+09 | 10314.02 | 28-JUL-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.109553E+10 | 11015.38 | 17-AUG-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.230148E+10 | 11032.87 | 26-SEP-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.620699E+10 | 11029.84 | 02-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.954944E+10 | 10253.78 | 21-NOV-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.144223E+11 | 10180.15 | 06-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.841519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.438742E+09 | 10179.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.158532E+11 | 11032.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.343124E+09 | 9169.85 | 09-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 122363.16 | 122.41 | 20-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.247024E+09 | 9169.19 | 26-DEC-06:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.590270E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.343124E+09 | 9169.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.321347E+10 | 7958.32 | 10-JAN-05:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.170336E+10 | 7958.60 | 19-FEB-03:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.678684E+09 | 7958.89 | 06-MAR-03:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 1935735.51 | 2093.14 | 03-APR-05:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.314208E+09 | 7946.34 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.258943E+10 | 7958.61 | 23-DEC-21:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.850108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.321347E+10 | 7958.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.168037E+11 | 25277.23 | 06-JAN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.101731E+11 | 24497.97 | 21-FEB-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.724616E+10 | 24529.56 | 21-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.123882E+10 | 24498.93 | 17-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 36634855.34 | 24473.32 | 01-MAY-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.302554E+09 | 24583.16 | 31-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.446298E+10 | 24665.07 | 21-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.143508E+11 | 24507.10 | 28-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.546146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.168037E+11 | 25277.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.112951E+11 | 23573.61 | 19-JAN-06:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.608183E+10 | 23575.70 | 24-FEB-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.385816E+10 | 23590.12 | 21-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.677784E+09 | 23578.01 | 10-APR-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 38108347.91 | 22975.75 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.229785E+09 | 23564.37 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.280921E+10 | 23592.09 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.955295E+10 | 23580.72 | 06-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.345430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.112951E+11 | 23592.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.144989E+11 | 24687.01 | 06-JAN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.888696E+10 | 24158.19 | 21-FEB-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.594440E+10 | 24162.64 | 21-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.880409E+09 | 24153.11 | 10-APR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 26744307.38 | 24120.13 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 90780954.48 | 24149.95 | 30-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.305448E+10 | 24166.53 | 29-NOV-06:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.118435E+11 | 24171.12 | 18-DEC-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.452262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.144989E+11 | 24687.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_POD_1 HEATING COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.308745E+12 | 468033.13 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.209183E+12 | 452621.69 | 14-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.172043E+12 | 375427.89 | 15-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.520483E+11 | 246164.93 | 05-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.486207E+10 | 136517.25 | 01-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1816828.03 | 8348.31 | 02-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.104977E+09 | 36100.80 | 17-AUG-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.395177E+10 | 70685.20 | 06-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.452674E+11 | 221666.05 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.106977E+12 | 289802.84 | 29-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.259530E+12 | 434762.14 | 20-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116271E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.308745E+12 | 468033.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:6 HEATING COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.100102E+10 | 37306.96 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.145331E+09 | 9043.53 | 14-FEB-08:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 6279928.77 | 4503.02 | 15-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 14061617.04 | 1997.31 | 28-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.156301E+10 | 37306.96 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.272970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.156301E+10 | 37306.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:7 HEATING COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.959307E+11 | 128129.16 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.555314E+11 | 128129.16 | 01-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.411702E+11 | 128129.16 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.971384E+10 | 128129.16 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.103674E+10 | 128129.16 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 19570800.00 | 11662.51 | 02-JUN-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.182721E+09 | 10110.40 | 18-AUG-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.930373E+09 | 28093.90 | 21-SEP-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.715579E+10 | 128129.16 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.210865E+11 | 128129.16 | 06-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.855721E+11 | 128129.16 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.318330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.959307E+11 | 128129.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_POD_1 COOLING COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.595604E+10 | 0.590179E+10 | 156079.22 | 23-APR-15:12 | 156079.22 | 0.00 |
| May | 0.00 | 0.00 | 0.101966E+12 | 0.936638E+11 | 465862.60 | 25-MAY-14:02 | 335689.65 | 0.00 |
| June | 0.00 | 0.00 | 0.229442E+12 | 0.168573E+12 | 649515.34 | 30-JUN-15:03 | 374708.68 | 0.00 |
| July | 0.00 | 0.00 | 0.227327E+12 | 0.158708E+12 | 499697.49 | 21-JUL-14:02 | 281958.14 | 0.00 |
| August | 0.00 | 0.00 | 0.184406E+12 | 0.119332E+12 | 511276.81 | 08-AUG-14:01 | 294479.88 | 0.00 |
| September | 0.00 | 0.00 | 0.429064E+11 | 0.341839E+11 | 292381.65 | 01-SEP-14:05 | 230523.92 | 0.00 |
| October | 0.00 | 0.00 | 0.610042E+10 | 0.580330E+10 | 182336.62 | 19-OCT-14:02 | 182336.62 | 0.00 |
| November | 0.00 | 0.00 | 0.146872E+10 | 0.106364E+10 | 76410.79 | 01-NOV-15:00 | 57714.32 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.799573E+12 | 0.587230E+12 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.229442E+12 | 0.168573E+12 | 649515.34 | 374708.68 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:6 COOLING COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 2563785.63 | 1993452.48 | 32530.13 | 20-JAN-06:01 | 26397.19 | 0.00 |
| February | 0.00 | 0.00 | 1410917.78 | 1084493.05 | 1814.93 | 24-FEB-06:57 | 1750.11 | 0.00 |
| March | 0.00 | 0.00 | 32836398.59 | 25055872.46 | 32530.13 | 21-MAR-05:01 | 21712.02 | 0.00 |
| April | 0.00 | 0.00 | 0.600257E+09 | 0.550126E+09 | 34271.16 | 23-APR-13:32 | 28654.37 | 0.00 |
| May | 0.00 | 0.00 | 0.828481E+10 | 0.662332E+10 | 36559.98 | 26-MAY-10:50 | 21767.68 | 0.00 |
| June | 0.00 | 0.00 | 0.157319E+11 | 0.110988E+11 | 39748.15 | 30-JUN-00:53 | 16793.74 | 0.00 |
| July | 0.00 | 0.00 | 0.181193E+11 | 0.117600E+11 | 39697.48 | 15-JUL-12:53 | 18095.51 | 0.00 |
| August | 0.00 | 0.00 | 0.130477E+11 | 0.823488E+10 | 37554.58 | 31-AUG-20:53 | 16881.22 | 0.00 |
| September | 0.00 | 0.00 | 0.283428E+10 | 0.203274E+10 | 36191.29 | 01-SEP-00:13 | 15447.00 | 0.00 |
| October | 0.00 | 0.00 | 0.518393E+09 | 0.428149E+09 | 32639.92 | 22-OCT-13:22 | 25538.74 | 0.00 |
| November | 0.00 | 0.00 | 0.139095E+09 | 99169076.14 | 32530.13 | 01-NOV-05:01 | 18515.12 | 0.00 |
| December | 0.00 | 0.00 | 1081642.51 | 754593.18 | 954.90 | 06-DEC-06:13 | 598.20 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.593137E+11 | 0.408561E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 1081642.51 | 754593.18 | 954.90 | 598.20 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.181193E+11 | 0.117600E+11 | 39748.15 | 28654.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:7 COOLING COIL
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:02 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.150071E+09 | 0.135742E+09 | 8501.78 | 13-APR-14:00 | 8501.78 | 0.00 |
| May | 0.00 | 0.00 | 0.102199E+11 | 0.803235E+10 | 68196.84 | 26-MAY-05:02 | 39526.40 | 0.00 |
| June | 0.00 | 0.00 | 0.237206E+11 | 0.158091E+11 | 75809.23 | 30-JUN-05:01 | 38971.81 | 0.00 |
| July | 0.00 | 0.00 | 0.154490E+11 | 0.993913E+10 | 75041.56 | 23-JUL-07:52 | 31884.59 | 0.00 |
| August | 0.00 | 0.00 | 0.101299E+11 | 0.618803E+10 | 72394.44 | 27-AUG-16:23 | 39708.41 | 0.00 |
| September | 0.00 | 0.00 | 0.275884E+10 | 0.208954E+10 | 68121.58 | 01-SEP-05:01 | 27584.31 | 0.00 |
| October | 0.00 | 0.00 | 0.261581E+09 | 0.225026E+09 | 20821.98 | 19-OCT-14:00 | 17888.30 | 0.00 |
| November | 0.00 | 0.00 | 19287560.31 | 13313508.15 | 3780.62 | 01-NOV-14:00 | 2559.57 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.627092E+11 | 0.424323E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.237206E+11 | 0.158091E+11 | 75809.23 | 39708.41 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:02 | 90931.73 | 730983.83 | 17-JAN-06:01 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 64335.30 | 741192.37 | 24-FEB-06:01 |
| March | 0.00 | 0.00 | 01-MAR-00:05 | 45295.33 | 836690.31 | 27-MAR-05:11 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 13314.49 | 843323.31 | 10-APR-05:11 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 1728.27 | 771354.28 | 02-MAY-06:01 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 290.38 | 48634.49 | 12-JUN-07:01 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 214.90 | 219572.10 | 10-JUL-07:01 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 998.16 | 407182.76 | 18-AUG-07:01 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 896.23 | 101393.03 | 13-SEP-07:01 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 5481.66 | 716670.53 | 30-OCT-06:01 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 29164.24 | 847094.50 | 24-NOV-06:01 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 77534.64 | 762600.69 | 04-DEC-06:01 |
| Annual Sum or Average | 0.00 | 27394.72 | ||||
| Minimum of Months | 0.00 | 0.00 | 214.90 | 48634.49 | ||
| Maximum of Months | 0.00 | 0.00 | 90931.73 | 847094.50 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:02 | 4191.82 | 21606.93 | 31-JAN-13:30 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 4294.27 | 21818.18 | 24-FEB-13:30 |
| March | 0.00 | 0.00 | 01-MAR-00:05 | 4676.23 | 21813.31 | 01-MAR-13:40 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4077.40 | 21368.15 | 03-APR-12:30 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 4130.09 | 20522.60 | 01-MAY-12:50 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 2519.16 | 19331.92 | 01-JUN-13:00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 822.42 | 5451.13 | 03-JUL-19:00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 919.64 | 5236.21 | 01-AUG-18:50 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 2111.33 | 17592.15 | 29-SEP-12:30 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 3563.05 | 18527.02 | 31-OCT-12:40 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 3894.06 | 19676.32 | 30-NOV-13:30 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 3804.51 | 20755.47 | 29-DEC-14:00 |
| Annual Sum or Average | 0.00 | 3242.84 | ||||
| Minimum of Months | 0.00 | 0.00 | 822.42 | 5236.21 | ||
| Maximum of Months | 0.00 | 0.00 | 4676.23 | 21818.18 |
Report: FanReportMonthly
For: VAV_POD_1 FAN
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.357911E+11 | 0.87 | 20379.33 | 01-JAN-02:62 | 1.15 |
| February | 0.300190E+11 | 0.81 | 19998.80 | 01-FEB-06:32 | 1.14 |
| March | 0.293929E+11 | 0.72 | 19998.80 | 05-MAR-05:52 | 1.14 |
| April | 0.192591E+11 | 0.48 | 20856.59 | 21-APR-14:13 | 1.15 |
| May | 0.246228E+11 | 0.52 | 46198.15 | 25-MAY-13:10 | 1.59 |
| June | 0.289815E+11 | 0.60 | 45732.19 | 08-JUN-14:10 | 1.59 |
| July | 0.223486E+11 | 0.50 | 26129.04 | 24-JUL-15:10 | 1.25 |
| August | 0.219074E+11 | 0.51 | 23287.31 | 08-AUG-13:10 | 1.19 |
| September | 0.199922E+11 | 0.45 | 32352.09 | 25-SEP-14:13 | 1.38 |
| October | 0.175976E+11 | 0.42 | 28812.63 | 20-OCT-14:15 | 1.31 |
| November | 0.228911E+11 | 0.58 | 19998.80 | 27-NOV-06:01 | 1.13 |
| December | 0.346485E+11 | 0.84 | 20379.33 | 11-DEC-07:01 | 1.15 |
| Annual Sum or Average | 0.307452E+12 | 0.61 | |||
| Minimum of Months | 0.175976E+11 | 0.42 | 19998.80 | 1.13 | |
| Maximum of Months | 0.357911E+11 | 0.87 | 46198.15 | 1.59 |
Report: FanReportMonthly
For: BATH_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:02 | 0.00 |
| February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | -0.0 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
| July | 0.00 | -0.0 | 0.00 | 01-JUL-00:03 | 0.00 |
| August | 0.00 | -0.0 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: GYM_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:02 | 0.00 |
| February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
| July | 0.00 | -0.0 | 0.00 | 01-JUL-00:03 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:02 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
| April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 |
| August | 0.00 | -0.0 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:03 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:02 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
| July | 0.00 | -0.0 | 0.00 | 01-JUL-00:03 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | -0.0 |
| November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: CAFETERIA_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:02 | 0.00 |
| February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:05 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | -0.0 | 0.00 | 01-JUN-00:10 | 0.00 |
| July | 0.00 | -0.0 | 0.00 | 01-JUL-00:03 | 0.00 |
| August | 0.00 | -0.0 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:03 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.284626E+10 | 0.56 | 2673.20 | 02-JAN-07:16 | 1.43 |
| February | 0.256178E+10 | 0.57 | 2673.20 | 01-FEB-16:07 | 1.42 |
| March | 0.311393E+10 | 0.66 | 2673.20 | 06-MAR-08:50 | 1.40 |
| April | 0.281815E+10 | 0.85 | 2673.20 | 03-APR-06:01 | 1.39 |
| May | 0.340970E+10 | 1.12 | 2673.20 | 02-MAY-16:00 | 1.42 |
| June | 0.367672E+10 | 1.15 | 2673.20 | 07-JUN-07:08 | 1.42 |
| July | 0.371293E+10 | 1.12 | 2673.20 | 03-JUL-06:17 | 1.40 |
| August | 0.378694E+10 | 1.13 | 2673.20 | 02-AUG-15:03 | 1.41 |
| September | 0.316073E+10 | 1.14 | 2673.20 | 01-SEP-06:03 | 1.40 |
| October | 0.299714E+10 | 0.97 | 2673.20 | 20-OCT-16:00 | 1.42 |
| November | 0.285548E+10 | 0.65 | 2673.20 | 01-NOV-15:00 | 1.41 |
| December | 0.271246E+10 | 0.54 | 2673.20 | 01-DEC-17:30 | 1.42 |
| Annual Sum or Average | 0.376522E+11 | 0.87 | |||
| Minimum of Months | 0.256178E+10 | 0.54 | 2673.20 | 1.39 | |
| Maximum of Months | 0.378694E+10 | 1.15 | 2673.20 | 1.43 |
Report: FanReportMonthly
For: PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.614938E+10 | 0.93 | 4465.58 | 12-JAN-07:55 | 1.40 |
| February | 0.491364E+10 | 0.78 | 4465.58 | 01-FEB-07:08 | 1.40 |
| March | 0.554468E+10 | 0.71 | 4465.58 | 06-MAR-16:17 | 1.40 |
| April | 0.453179E+10 | 0.56 | 4465.58 | 03-APR-09:10 | 1.39 |
| May | 0.496007E+10 | 0.58 | 4465.58 | 05-MAY-13:05 | 1.39 |
| June | 0.503525E+10 | 0.64 | 4465.58 | 01-JUN-18:40 | 1.38 |
| July | 0.470304E+10 | 0.62 | 4465.58 | 06-JUL-06:04 | 1.38 |
| August | 0.523601E+10 | 0.63 | 4465.58 | 02-AUG-14:30 | 1.38 |
| September | 0.450325E+10 | 0.54 | 4465.58 | 12-SEP-07:00 | 1.38 |
| October | 0.473302E+10 | 0.55 | 4465.58 | 03-OCT-15:19 | 1.39 |
| November | 0.479768E+10 | 0.64 | 4465.58 | 02-NOV-14:30 | 1.39 |
| December | 0.589495E+10 | 0.82 | 4465.58 | 01-DEC-07:10 | 1.40 |
| Annual Sum or Average | 0.610028E+11 | 0.67 | |||
| Minimum of Months | 0.450325E+10 | 0.54 | 4465.58 | 1.38 | |
| Maximum of Months | 0.614938E+10 | 0.93 | 4465.58 | 1.40 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 0.106085E+10 | 0.954768E+09 | 1389.47 | 02-JAN-06:01 | 1250.53 | 1250.53 | 46.38 | 4.43 |
| February | 0.691608E+09 | 0.622447E+09 | 1378.31 | 06-FEB-06:02 | 1240.48 | 1240.48 | 53.93 | 4.38 |
| March | 0.552653E+09 | 0.497388E+09 | 1375.57 | 13-MAR-05:11 | 1238.01 | 1238.01 | 42.32 | 4.40 |
| April | 0.174446E+09 | 0.157001E+09 | 1348.52 | 04-APR-05:02 | 1213.67 | 1213.67 | 51.90 | 4.31 |
| May | 31189385.25 | 28070446.73 | 1273.12 | 02-MAY-06:02 | 1145.81 | 1145.81 | 49.95 | 4.07 |
| June | 7854022.39 | 7068620.15 | 459.86 | 12-JUN-07:01 | 413.87 | 413.87 | 61.17 | 0.56 |
| July | 5397690.60 | 4857921.54 | 1057.64 | 10-JUL-07:01 | 951.88 | 951.88 | 61.39 | 2.55 |
| August | 16467920.10 | 14821128.09 | 1102.36 | 18-AUG-07:01 | 992.13 | 992.13 | 50.21 | 3.06 |
| September | 21963894.62 | 19767505.16 | 764.62 | 13-SEP-07:01 | 688.16 | 688.16 | 60.67 | 1.14 |
| October | 96929215.84 | 87236294.26 | 1336.92 | 30-OCT-06:02 | 1203.23 | 1203.23 | 52.82 | 4.27 |
| November | 0.360858E+09 | 0.324772E+09 | 1373.06 | 27-NOV-06:01 | 1235.76 | 1235.76 | 42.52 | 4.39 |
| December | 0.907353E+09 | 0.816618E+09 | 1381.04 | 18-DEC-06:12 | 1242.94 | 1242.94 | 53.56 | 4.39 |
| Annual Sum or Average | 0.392757E+10 | 0.353482E+10 | ||||||
| Minimum of Months | 5397690.60 | 4857921.54 | 459.86 | 413.87 | 413.87 | 42.32 | 0.56 | |
| Maximum of Months | 0.106085E+10 | 0.954768E+09 | 1389.47 | 1250.53 | 1250.53 | 61.39 | 4.43 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 12215899.87 | 3664769.96 | 13.47 | 02-JAN-08:61 | 4.04 | 4.04 | 52.87 | 0.11 |
| February | 11052480.83 | 3315744.25 | 13.47 | 01-FEB-08:61 | 4.04 | 4.04 | 43.34 | 0.11 |
| March | 13379318.90 | 4013795.67 | 13.47 | 01-MAR-08:61 | 4.04 | 4.04 | 43.19 | 0.11 |
| April | 11634190.35 | 3490257.10 | 13.47 | 03-APR-07:01 | 4.04 | 4.04 | 43.50 | 0.11 |
| May | 12797609.38 | 3839282.82 | 13.47 | 01-MAY-07:01 | 4.04 | 4.04 | 44.13 | 0.11 |
| June | 12797609.38 | 3839282.82 | 13.47 | 01-JUN-07:03 | 4.04 | 4.04 | 43.82 | 0.11 |
| July | 11634190.35 | 3490257.10 | 13.47 | 03-JUL-07:03 | 4.04 | 4.04 | 52.33 | 0.11 |
| August | 13379318.90 | 4013795.67 | 13.47 | 01-AUG-07:03 | 4.04 | 4.04 | 52.65 | 0.11 |
| September | 11634190.35 | 3490257.10 | 13.47 | 01-SEP-07:03 | 4.04 | 4.04 | 52.74 | 0.11 |
| October | 12215899.87 | 3664769.96 | 13.47 | 02-OCT-07:01 | 4.04 | 4.04 | 46.40 | 0.11 |
| November | 12215899.87 | 3664769.96 | 13.47 | 01-NOV-07:01 | 4.04 | 4.04 | 45.69 | 0.11 |
| December | 11634190.35 | 3490257.10 | 13.47 | 01-DEC-08:61 | 4.04 | 4.04 | 44.81 | 0.11 |
| Annual Sum or Average | 0.146591E+09 | 43977239.52 | ||||||
| Minimum of Months | 11052480.83 | 3315744.25 | 13.47 | 4.04 | 4.04 | 43.19 | 0.11 | |
| Maximum of Months | 13379318.90 | 4013795.67 | 13.47 | 4.04 | 4.04 | 52.87 | 0.11 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:02 | 40.30 | 40.30 | 90931.73 | 730983.83 | 17-JAN-06:01 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 39.00 | 82.00 | 64335.30 | 741192.37 | 24-FEB-06:01 |
| March | 0.00 | 0.00 | 01-MAR-00:05 | 33.58 | 33.58 | 45295.33 | 836690.31 | 27-MAR-05:11 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.23 | 23.23 | 13314.49 | 843323.31 | 10-APR-05:11 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 24.26 | 24.26 | 1728.27 | 771354.28 | 02-MAY-06:01 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 49.67 | 49.67 | 290.38 | 48634.49 | 12-JUN-07:01 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 54.49 | 54.49 | 214.90 | 219572.10 | 10-JUL-07:01 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 54.43 | 54.43 | 998.16 | 407182.76 | 18-AUG-07:01 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 54.41 | 54.41 | 896.23 | 101393.03 | 13-SEP-07:01 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 52.37 | 52.37 | 5481.66 | 716670.53 | 30-OCT-06:01 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 25.53 | 25.53 | 29164.24 | 847094.50 | 24-NOV-06:01 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 29.86 | 29.86 | 77534.64 | 762600.69 | 04-DEC-06:01 |
| Annual Sum or Average | 0.00 | 27394.72 | ||||||
| Minimum of Months | 0.00 | 0.00 | 23.23 | 23.23 | 214.90 | 48634.49 | ||
| Maximum of Months | 0.00 | 0.00 | 54.49 | 82.00 | 90931.73 | 847094.50 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:02 | 60.00 | 60.00 | 4191.82 | 21606.93 | 31-JAN-13:30 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 45.30 | 45.30 | 4294.27 | 21818.18 | 24-FEB-13:30 |
| March | 0.00 | 0.00 | 01-MAR-00:05 | 45.16 | 45.16 | 4676.23 | 21813.31 | 01-MAR-13:40 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 45.42 | 45.42 | 4077.40 | 21368.15 | 03-APR-12:30 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 45.96 | 45.96 | 4130.09 | 20522.60 | 01-MAY-12:50 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 46.81 | 46.81 | 2519.16 | 19331.92 | 01-JUN-13:00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 47.56 | 47.56 | 822.42 | 5451.13 | 03-JUL-19:00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 48.11 | 48.11 | 919.64 | 5236.21 | 01-AUG-18:50 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 48.26 | 48.26 | 2111.33 | 17592.15 | 29-SEP-12:30 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 48.02 | 48.02 | 3563.05 | 18527.02 | 31-OCT-12:40 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 47.38 | 47.38 | 3894.06 | 19676.32 | 30-NOV-13:30 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 46.61 | 46.61 | 3804.51 | 20755.47 | 29-DEC-14:00 |
| Annual Sum or Average | 0.00 | 3242.84 | ||||||
| Minimum of Months | 0.00 | 0.00 | 45.16 | 45.16 | 822.42 | 5236.21 | ||
| Maximum of Months | 0.00 | 0.00 | 60.00 | 60.00 | 4676.23 | 21818.18 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_POD_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.245659E+12 | 0.00 | 0.00 | 0.357911E+11 | 0.00 | 0.00 |
| February | 0.156985E+12 | 0.00 | 0.00 | 0.300190E+11 | 0.00 | 0.00 |
| March | 0.122344E+12 | 0.00 | 0.00 | 0.293929E+11 | 0.00 | 0.00 |
| April | 0.347582E+11 | 0.00 | 0.00 | 0.210799E+11 | 0.00 | 0.00 |
| May | 0.463099E+10 | 0.00 | 0.00 | 0.519742E+11 | 0.00 | 0.00 |
| June | 0.757186E+09 | 0.00 | 0.00 | 0.886047E+11 | 0.00 | 0.00 |
| July | 0.582846E+09 | 0.00 | 0.00 | 0.810396E+11 | 0.00 | 0.00 |
| August | 0.270109E+10 | 0.00 | 0.00 | 0.701377E+11 | 0.00 | 0.00 |
| September | 0.235476E+10 | 0.00 | 0.00 | 0.321101E+11 | 0.00 | 0.00 |
| October | 0.148608E+11 | 0.00 | 0.00 | 0.193928E+11 | 0.00 | 0.00 |
| November | 0.762008E+11 | 0.00 | 0.00 | 0.233396E+11 | 0.00 | 0.00 |
| December | 0.209423E+12 | 0.00 | 0.00 | 0.346485E+11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.871257E+12 | 0.00 | 0.00 | 0.517530E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.582846E+09 | 0.00 | 0.00 | 0.193928E+11 | 0.00 | 0.00 |
| Maximum of Months | 0.245659E+12 | 0.00 | 0.00 | 0.886047E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:6
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.284688E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.256218E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.312244E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.297543E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.542260E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.746386E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.804268E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.689306E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.385385E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.312939E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.289205E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.271277E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.519172E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.256218E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.804268E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:7
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.614938E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.491364E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.554468E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.457430E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.755428E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.109740E+11 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.868358E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.784365E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.522697E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.480377E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.480328E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.589495E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.769665E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.457430E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.109740E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_POD_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.357911E+11 | 0.00 | 0.554403E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.300190E+11 | 0.00 | 0.366168E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.293929E+11 | 0.00 | 0.294387E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.192591E+11 | 0.595604E+10 | 0.868064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.246228E+11 | 0.101966E+12 | 0.949306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.289815E+11 | 0.229442E+12 | 0.759003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.223486E+11 | 0.227327E+12 | 0.582846E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.219074E+11 | 0.184406E+12 | 0.280607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.199922E+11 | 0.429064E+11 | 0.630653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.175976E+11 | 0.610042E+10 | 0.601282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.228911E+11 | 0.146872E+10 | 0.183177E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.346485E+11 | 0.00 | 0.468953E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.307452E+12 | 0.799573E+12 | 0.203397E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.175976E+11 | 0.00 | 0.582846E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.357911E+11 | 0.229442E+12 | 0.554403E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:6
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.284626E+10 | 2563785.63 | 0.100102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.256178E+10 | 1410917.78 | 0.145331E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.311393E+10 | 32836398.59 | 6279928.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.281815E+10 | 0.600257E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.340970E+10 | 0.828481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.367672E+10 | 0.157319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.371293E+10 | 0.181193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.378694E+10 | 0.130477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.316073E+10 | 0.283428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.299714E+10 | 0.518393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.285548E+10 | 0.139095E+09 | 14061617.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.271246E+10 | 1081642.51 | 0.156301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.376522E+11 | 0.593137E+11 | 0.272970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.256178E+10 | 1081642.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.378694E+10 | 0.181193E+11 | 0.156301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:7
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.614938E+10 | 0.00 | 0.959307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.491364E+10 | 0.00 | 0.555314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.554468E+10 | 0.00 | 0.411702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.453179E+10 | 0.150071E+09 | 0.971384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.496007E+10 | 0.102199E+11 | 0.103674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.503525E+10 | 0.237206E+11 | 19570800.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.470304E+10 | 0.154490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.523601E+10 | 0.101299E+11 | 0.182721E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.450325E+10 | 0.275884E+10 | 0.930373E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.473302E+10 | 0.261581E+09 | 0.715579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.479768E+10 | 19287560.31 | 0.210865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.589495E+10 | 0.00 | 0.855721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.610028E+11 | 0.627092E+11 | 0.318330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.450325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.614938E+10 | 0.237206E+11 | 0.959307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_POD_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.357911E+11 | 0.245659E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.300190E+11 | 0.156985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.293929E+11 | 0.122344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.192591E+11 | 0.347582E+11 | 0.00 | 0.00 | 0.182078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.246228E+11 | 0.463099E+10 | 0.00 | 0.00 | 0.273514E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.289815E+11 | 0.757186E+09 | 0.00 | 0.00 | 0.596231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.223486E+11 | 0.582846E+09 | 0.00 | 0.00 | 0.586910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.219074E+11 | 0.270109E+10 | 0.00 | 0.00 | 0.482303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.199922E+11 | 0.235476E+10 | 0.00 | 0.00 | 0.121179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.175976E+11 | 0.148608E+11 | 0.00 | 0.00 | 0.179524E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.228911E+11 | 0.762008E+11 | 0.00 | 0.00 | 0.448519E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.346485E+11 | 0.209423E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.307452E+12 | 0.871257E+12 | 0.00 | 0.00 | 0.210078E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.175976E+11 | 0.582846E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.357911E+11 | 0.245659E+12 | 0.00 | 0.00 | 0.596231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:6
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.284626E+10 | 0.00 | 0.00 | 0.00 | 624727.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.256178E+10 | 0.00 | 0.00 | 0.00 | 404856.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.311393E+10 | 0.00 | 0.00 | 0.00 | 8517293.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.281815E+10 | 0.00 | 0.00 | 0.00 | 0.157283E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.340970E+10 | 0.00 | 0.00 | 0.00 | 0.201290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.367672E+10 | 0.00 | 0.00 | 0.00 | 0.378715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.371293E+10 | 0.00 | 0.00 | 0.00 | 0.432975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.378694E+10 | 0.00 | 0.00 | 0.00 | 0.310611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.316073E+10 | 0.00 | 0.00 | 0.00 | 0.693119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.299714E+10 | 0.00 | 0.00 | 0.00 | 0.132252E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.285548E+10 | 0.00 | 0.00 | 0.00 | 36573090.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.271246E+10 | 0.00 | 0.00 | 0.00 | 311550.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.376522E+11 | 0.00 | 0.00 | 0.00 | 0.142650E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.256178E+10 | 0.00 | 0.00 | 0.00 | 311550.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.378694E+10 | 0.00 | 0.00 | 0.00 | 0.432975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:7
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.614938E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.491364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.554468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.453179E+10 | 0.00 | 0.00 | 0.00 | 42516500.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.496007E+10 | 0.00 | 0.00 | 0.00 | 0.259420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.503525E+10 | 0.00 | 0.00 | 0.00 | 0.593875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.470304E+10 | 0.00 | 0.00 | 0.00 | 0.398053E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.523601E+10 | 0.00 | 0.00 | 0.00 | 0.260764E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.450325E+10 | 0.00 | 0.00 | 0.00 | 0.723722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.473302E+10 | 0.00 | 0.00 | 0.00 | 70743940.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.479768E+10 | 0.00 | 0.00 | 0.00 | 5599917.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.589495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.610028E+11 | 0.00 | 0.00 | 0.00 | 0.159637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.450325E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.614938E+10 | 0.00 | 0.00 | 0.00 | 0.593875E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.292023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658605E+10 | 0.00 | 0.00 | 0.70 |
| February | 0.306650E+10 | 0.00 | 0.00 | 6756.86 | 0.00 | 0.411754E+10 | 39377703.44 | 0.00 | 0.70 |
| March | 0.381564E+10 | 0.00 | 0.00 | 17983.75 | 0.00 | 0.314916E+10 | 69229848.93 | 0.00 | 0.74 |
| April | 0.274723E+10 | 0.00 | 0.00 | 886222.26 | 4334696.55 | 0.674795E+09 | 0.706903E+09 | 0.00 | 0.72 |
| May | 0.141174E+10 | 54090583.33 | 0.00 | 3005006.98 | 576252.10 | 37885422.48 | 0.132600E+10 | 0.00 | 1.05 |
| June | 0.603687E+09 | 0.787416E+09 | 0.00 | 2883398.83 | 0.233581E+09 | 726888.62 | 0.101572E+10 | 0.00 | 1.25 |
| July | 0.365176E+09 | 0.680138E+09 | 51467.36 | 623910.24 | 0.497929E+09 | 198307.76 | 0.114915E+09 | 2314.33 | 0.99 |
| August | 0.815451E+09 | 0.600513E+09 | 0.00 | 416647.16 | 0.320502E+09 | 1096526.38 | 74035771.63 | 0.00 | 1.14 |
| September | 0.113597E+10 | 24268900.07 | 0.00 | 3468325.17 | 3233051.95 | 1113226.56 | 0.193039E+10 | 0.00 | 0.98 |
| October | 0.281551E+10 | 0.00 | 0.00 | 1783612.56 | 0.00 | 0.177628E+09 | 0.134316E+10 | 0.00 | 0.74 |
| November | 0.336036E+10 | 0.00 | 4768.11 | 113612.26 | 52466.21 | 0.169853E+10 | 0.235778E+09 | 9586.21 | 0.71 |
| December | 0.260206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580443E+10 | 0.00 | 0.00 | 0.68 |
| Annual Sum or Average | 0.256596E+11 | 0.214643E+10 | 56235.47 | 13205476.07 | 0.106021E+10 | 0.222492E+11 | 0.685550E+10 | 11900.55 | 0.87 |
| Minimum of Months | 0.365176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 198307.76 | 0.00 | 0.00 | 0.68 |
| Maximum of Months | 0.381564E+10 | 0.787416E+09 | 51467.36 | 3468325.17 | 0.497929E+09 | 0.658605E+10 | 0.193039E+10 | 9586.21 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.212048E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245549E+11 | 0.00 | 0.00 | 0.70 |
| February | 0.204269E+11 | 0.00 | 0.00 | 75800.37 | 0.00 | 0.138767E+11 | 0.477905E+09 | 0.00 | 0.70 |
| March | 0.243560E+11 | 0.00 | 0.00 | 463243.26 | 0.00 | 0.836668E+10 | 0.115574E+10 | 0.00 | 0.74 |
| April | 0.140136E+11 | 0.00 | 0.00 | 5651841.51 | 20892850.90 | 0.108569E+10 | 0.493001E+10 | 0.00 | 0.73 |
| May | 0.572476E+10 | 0.219950E+09 | 0.00 | 15979905.70 | 3147520.80 | 61844667.06 | 0.766585E+10 | 0.00 | 1.04 |
| June | 0.277889E+10 | 0.337144E+10 | 0.00 | 13692759.49 | 0.111395E+10 | 0.00 | 0.511602E+10 | 0.00 | 1.23 |
| July | 0.195559E+10 | 0.217276E+10 | 253640.43 | 1098609.71 | 0.334602E+10 | 1483415.41 | 0.345357E+09 | 5582.52 | 0.97 |
| August | 0.409800E+10 | 0.197856E+10 | 0.00 | 495042.02 | 0.225609E+10 | 4644963.87 | 0.184716E+09 | 0.00 | 1.12 |
| September | 0.474948E+10 | 0.102598E+09 | 0.00 | 17829433.09 | 17225922.02 | 0.00 | 0.100529E+11 | 0.00 | 0.96 |
| October | 0.121494E+11 | 0.00 | 0.00 | 10388564.94 | 0.00 | 78041843.34 | 0.881378E+10 | 0.00 | 0.74 |
| November | 0.196305E+11 | 0.00 | 48551.63 | 1129727.92 | 252882.47 | 0.394046E+10 | 0.193958E+10 | 8734.86 | 0.71 |
| December | 0.195046E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209698E+11 | 0.00 | 0.00 | 0.68 |
| Annual Sum or Average | 0.150593E+12 | 0.784530E+10 | 302192.06 | 66804928.00 | 0.675759E+10 | 0.729403E+11 | 0.406819E+11 | 14317.38 | 0.86 |
| Minimum of Months | 0.195559E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
| Maximum of Months | 0.243560E+11 | 0.337144E+10 | 253640.43 | 17829433.09 | 0.334602E+10 | 0.245549E+11 | 0.100529E+11 | 8734.86 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.310215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626420E+10 | 0.00 | 0.00 | 0.25 |
| February | 0.376877E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436803E+10 | 0.00 | 0.00 | 0.23 |
| March | 0.910005E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356100E+10 | 0.00 | 0.00 | 0.24 |
| April | 0.178209E+10 | 0.00 | 0.00 | 0.00 | 2614034.60 | 0.724099E+09 | 0.00 | 0.00 | 0.22 |
| May | 0.121965E+10 | 45396463.59 | 0.00 | 1518636.34 | 393805.92 | 45100769.82 | 0.413266E+09 | 0.00 | 0.34 |
| June | 0.392757E+09 | 0.648734E+09 | 0.00 | 2254106.52 | 0.133257E+09 | 0.00 | 0.670938E+09 | 0.00 | 0.44 |
| July | 0.237200E+09 | 0.331891E+09 | 0.00 | 302467.75 | 0.386533E+09 | 0.00 | 52356425.86 | 0.00 | 0.31 |
| August | 0.521201E+09 | 0.183062E+09 | 0.00 | 30634.39 | 0.355779E+09 | 88362.43 | 15173041.31 | 0.00 | 0.35 |
| September | 0.104046E+10 | 8118778.83 | 0.00 | 1549762.18 | 6749920.73 | 0.00 | 0.776894E+09 | 0.00 | 0.30 |
| October | 0.216107E+10 | 0.00 | 0.00 | 137226.05 | 0.00 | 0.249971E+09 | 0.121199E+09 | 0.00 | 0.22 |
| November | 0.119478E+10 | 0.00 | 5200.79 | 0.00 | 31639.70 | 0.209574E+10 | 0.00 | 6744.99 | 0.23 |
| December | 0.332278E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538250E+10 | 0.00 | 0.00 | 0.23 |
| Annual Sum or Average | 0.104786E+11 | 0.121720E+10 | 5200.79 | 5792833.23 | 0.885358E+09 | 0.226907E+11 | 0.204983E+10 | 6744.99 | 0.28 |
| Minimum of Months | 0.237200E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
| Maximum of Months | 0.216107E+10 | 0.648734E+09 | 5200.79 | 2254106.52 | 0.386533E+09 | 0.626420E+10 | 0.776894E+09 | 6744.99 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.798245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.870475E+10 | 0.00 | 0.00 | 0.70 |
| February | 0.134656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587532E+10 | 0.00 | 0.00 | 0.70 |
| March | 0.259885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443481E+10 | 0.00 | 0.00 | 0.74 |
| April | 0.300440E+10 | 0.00 | 0.00 | 14412.36 | 4336227.25 | 0.103012E+10 | 67720431.01 | 0.00 | 0.71 |
| May | 0.174532E+10 | 45225050.34 | 0.00 | 1785389.79 | 954211.94 | 55229801.29 | 0.887545E+09 | 0.00 | 0.99 |
| June | 0.663611E+09 | 0.651729E+09 | 0.00 | 2164395.42 | 0.277778E+09 | 587921.26 | 0.883885E+09 | 0.00 | 1.18 |
| July | 0.439792E+09 | 0.344678E+09 | 113682.38 | 117865.21 | 0.800634E+09 | 601235.85 | 37592150.94 | 3358.67 | 0.97 |
| August | 0.872785E+09 | 0.195281E+09 | 5267.97 | 9411.81 | 0.682066E+09 | 2322993.50 | 14849314.43 | 1023.24 | 1.12 |
| September | 0.176781E+10 | 5681332.62 | 0.00 | 1114294.98 | 18714496.30 | 3139899.97 | 0.111157E+10 | 0.00 | 0.89 |
| October | 0.345113E+10 | 0.00 | 0.00 | 286796.04 | 0.00 | 0.238734E+09 | 0.501317E+09 | 0.00 | 0.69 |
| November | 0.292333E+10 | 0.00 | 2073.87 | 604.12 | 52484.74 | 0.236659E+10 | 5274103.92 | 10655.87 | 0.71 |
| December | 0.124969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715442E+10 | 0.00 | 0.00 | 0.68 |
| Annual Sum or Average | 0.208615E+11 | 0.124260E+10 | 121024.22 | 5493169.74 | 0.178453E+10 | 0.298666E+11 | 0.350975E+10 | 15037.79 | 0.84 |
| Minimum of Months | 0.439792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 587921.26 | 0.00 | 0.00 | 0.68 |
| Maximum of Months | 0.345113E+10 | 0.651729E+09 | 113682.38 | 2164395.42 | 0.800634E+09 | 0.870475E+10 | 0.111157E+10 | 10655.87 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.121579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336058E+11 | 0.00 | 0.00 | 0.70 |
| February | 0.141642E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206226E+11 | 0.00 | 0.00 | 0.70 |
| March | 0.196331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142525E+11 | 0.00 | 0.00 | 0.74 |
| April | 0.167339E+11 | 0.00 | 0.00 | 215538.89 | 20900475.11 | 0.212431E+10 | 0.908966E+09 | 0.00 | 0.71 |
| May | 0.713228E+10 | 0.189991E+09 | 0.00 | 9803337.69 | 5935289.35 | 88955222.77 | 0.572559E+10 | 0.00 | 0.98 |
| June | 0.315094E+10 | 0.267713E+10 | 0.00 | 10051405.78 | 0.159993E+10 | 0.00 | 0.437528E+10 | 0.00 | 1.17 |
| July | 0.230154E+10 | 0.00 | 550146.73 | 0.00 | 0.551858E+10 | 2831391.97 | 0.00 | 13987.35 | 0.97 |
| August | 0.427799E+10 | 0.00 | 892123.28 | 0.00 | 0.422792E+10 | 11369006.79 | 0.00 | 6021.20 | 1.12 |
| September | 0.838578E+10 | 512245.45 | 0.00 | 6475445.15 | 0.117075E+09 | 6943969.47 | 0.553582E+10 | 0.00 | 0.89 |
| October | 0.158647E+11 | 0.00 | 0.00 | 2088316.04 | 0.00 | 0.130963E+09 | 0.419511E+10 | 0.00 | 0.69 |
| November | 0.194573E+11 | 0.00 | 42498.17 | 28047.69 | 252974.75 | 0.597962E+10 | 79944739.29 | 14809.22 | 0.71 |
| December | 0.143790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261004E+11 | 0.00 | 0.00 | 0.68 |
| Annual Sum or Average | 0.137639E+12 | 0.286763E+10 | 1484768.18 | 28662091.23 | 0.114906E+11 | 0.102926E+12 | 0.208207E+11 | 34817.76 | 0.84 |
| Minimum of Months | 0.230154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
| Maximum of Months | 0.196331E+11 | 0.267713E+10 | 892123.28 | 10051405.78 | 0.551858E+10 | 0.336058E+11 | 0.572559E+10 | 14809.22 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.266854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683913E+10 | 0.00 | 0.00 | 0.71 |
| February | 0.302491E+10 | 0.00 | 0.00 | 5449.79 | 0.00 | 0.416343E+10 | 35976387.48 | 0.00 | 0.70 |
| March | 0.378763E+10 | 0.00 | 0.00 | 14820.78 | 0.00 | 0.319525E+10 | 51993425.67 | 0.00 | 0.74 |
| April | 0.275184E+10 | 0.00 | 0.00 | 825670.49 | 4335384.20 | 0.695008E+09 | 0.677866E+09 | 0.00 | 0.72 |
| May | 0.144608E+10 | 53001430.08 | 0.00 | 2865438.56 | 625063.28 | 40059738.14 | 0.127734E+10 | 0.00 | 1.04 |
| June | 0.613577E+09 | 0.757404E+09 | 0.00 | 2745862.61 | 0.249583E+09 | 730834.11 | 0.991072E+09 | 0.00 | 1.24 |
| July | 0.374188E+09 | 0.638958E+09 | 50829.61 | 547365.33 | 0.527979E+09 | 341069.60 | 0.104866E+09 | 2960.61 | 0.98 |
| August | 0.820954E+09 | 0.556635E+09 | 0.00 | 338125.93 | 0.354907E+09 | 1582209.13 | 67504318.10 | 0.00 | 1.14 |
| September | 0.117009E+10 | 23507734.96 | 0.00 | 3280977.69 | 3574475.81 | 1122847.45 | 0.187772E+10 | 0.00 | 0.97 |
| October | 0.283422E+10 | 0.00 | 0.00 | 1720829.42 | 0.00 | 0.183596E+09 | 0.131048E+10 | 0.00 | 0.74 |
| November | 0.333213E+10 | 0.00 | 4700.67 | 88118.90 | 52474.54 | 0.175906E+10 | 0.204269E+09 | 9518.56 | 0.71 |
| December | 0.244445E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.596316E+10 | 0.00 | 0.00 | 0.68 |
| Annual Sum or Average | 0.252686E+11 | 0.202951E+10 | 55530.28 | 12432659.50 | 0.114106E+10 | 0.228425E+11 | 0.659909E+10 | 12479.16 | 0.86 |
| Minimum of Months | 0.374188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 341069.60 | 0.00 | 0.00 | 0.68 |
| Maximum of Months | 0.378763E+10 | 0.757404E+09 | 50829.61 | 3280977.69 | 0.527979E+09 | 0.683913E+10 | 0.187772E+10 | 9518.56 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.206050E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251539E+11 | 0.00 | 0.00 | 0.70 |
| February | 0.205724E+11 | 0.00 | 0.00 | 53965.47 | 0.00 | 0.138035E+11 | 0.405636E+09 | 0.00 | 0.70 |
| March | 0.248286E+11 | 0.00 | 0.00 | 363159.42 | 0.00 | 0.797937E+10 | 0.107105E+10 | 0.00 | 0.74 |
| April | 0.141870E+11 | 0.00 | 0.00 | 5336397.97 | 20894193.44 | 0.105930E+10 | 0.473887E+10 | 0.00 | 0.73 |
| May | 0.583742E+10 | 0.215310E+09 | 0.00 | 15264110.66 | 3147723.06 | 63124053.20 | 0.747449E+10 | 0.00 | 1.04 |
| June | 0.287925E+10 | 0.322900E+10 | 0.00 | 13013474.48 | 0.118477E+10 | 0.00 | 0.493650E+10 | 0.00 | 1.22 |
| July | 0.201717E+10 | 0.172104E+10 | 250860.69 | 738837.97 | 0.379618E+10 | 1497949.08 | 0.284287E+09 | 8378.92 | 0.97 |
| August | 0.412929E+10 | 0.160179E+10 | 0.00 | 325861.00 | 0.262643E+10 | 6344080.45 | 0.152151E+09 | 0.00 | 1.12 |
| September | 0.487195E+10 | 97629750.44 | 0.00 | 16951051.77 | 21039308.11 | 0.00 | 0.981848E+10 | 0.00 | 0.95 |
| October | 0.122736E+11 | 0.00 | 0.00 | 9877386.56 | 0.00 | 76292499.32 | 0.860144E+10 | 0.00 | 0.74 |
| November | 0.197473E+11 | 0.00 | 50367.52 | 852464.21 | 252898.71 | 0.398227E+10 | 0.178104E+10 | 6922.65 | 0.71 |
| December | 0.187545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217197E+11 | 0.00 | 0.00 | 0.68 |
| Annual Sum or Average | 0.150703E+12 | 0.686478E+10 | 301228.21 | 62776709.50 | 0.765272E+10 | 0.738453E+11 | 0.392639E+11 | 15301.57 | 0.86 |
| Minimum of Months | 0.201717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
| Maximum of Months | 0.248286E+11 | 0.322900E+10 | 250860.69 | 16951051.77 | 0.379618E+10 | 0.251539E+11 | 0.981848E+10 | 8378.92 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.300502E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629556E+10 | 0.00 | 0.00 | 0.25 |
| February | 0.370181E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436023E+10 | 0.00 | 0.00 | 0.23 |
| March | 0.896929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355705E+10 | 0.00 | 0.00 | 0.24 |
| April | 0.177209E+10 | 0.00 | 0.00 | 0.00 | 2602737.55 | 0.723667E+09 | 0.00 | 0.00 | 0.22 |
| May | 0.122674E+10 | 44866263.91 | 0.00 | 1473076.83 | 392104.01 | 44926471.48 | 0.396864E+09 | 0.00 | 0.34 |
| June | 0.395385E+09 | 0.635781E+09 | 0.00 | 2196346.37 | 0.135894E+09 | 0.00 | 0.657012E+09 | 0.00 | 0.44 |
| July | 0.241786E+09 | 0.295324E+09 | 0.00 | 245155.13 | 0.413026E+09 | 0.00 | 45964668.52 | 0.00 | 0.31 |
| August | 0.521530E+09 | 0.156026E+09 | 0.00 | 17379.51 | 0.376765E+09 | 95401.16 | 12538499.66 | 0.00 | 0.35 |
| September | 0.105784E+10 | 7415260.73 | 0.00 | 1478332.54 | 7312945.07 | 0.00 | 0.744648E+09 | 0.00 | 0.29 |
| October | 0.215693E+10 | 0.00 | 0.00 | 120349.69 | 0.00 | 0.252468E+09 | 0.111455E+09 | 0.00 | 0.22 |
| November | 0.116250E+10 | 0.00 | 5244.75 | 0.00 | 31502.96 | 0.211658E+10 | 0.00 | 6626.90 | 0.22 |
| December | 0.324897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540525E+10 | 0.00 | 0.00 | 0.23 |
| Annual Sum or Average | 0.104273E+11 | 0.113941E+10 | 5244.75 | 5530640.07 | 0.936025E+09 | 0.227558E+11 | 0.196848E+10 | 6626.90 | 0.28 |
| Minimum of Months | 0.241786E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
| Maximum of Months | 0.215693E+10 | 0.635781E+09 | 5244.75 | 2196346.37 | 0.413026E+09 | 0.629556E+10 | 0.744648E+09 | 6626.90 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.798846E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.871129E+10 | 0.00 | 0.00 | 0.71 |
| February | 0.134291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588439E+10 | 0.00 | 0.00 | 0.70 |
| March | 0.260112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.443783E+10 | 0.00 | 0.00 | 0.74 |
| April | 0.300660E+10 | 0.00 | 0.00 | 14485.67 | 4339488.68 | 0.103095E+10 | 67771303.53 | 0.00 | 0.71 |
| May | 0.174341E+10 | 45270063.36 | 0.00 | 1787589.75 | 954929.63 | 56150085.12 | 0.890582E+09 | 0.00 | 0.99 |
| June | 0.664111E+09 | 0.652423E+09 | 0.00 | 2168889.31 | 0.277987E+09 | 588363.45 | 0.884761E+09 | 0.00 | 1.18 |
| July | 0.440123E+09 | 0.342720E+09 | 113671.21 | 116706.47 | 0.803428E+09 | 601688.06 | 37621672.75 | 3457.87 | 0.97 |
| August | 0.873944E+09 | 0.190107E+09 | 5207.22 | 8964.92 | 0.687900E+09 | 2324740.71 | 14358136.13 | 1088.73 | 1.12 |
| September | 0.177277E+10 | 5685605.75 | 0.00 | 1111103.64 | 18728572.15 | 3142261.61 | 0.110871E+10 | 0.00 | 0.89 |
| October | 0.345359E+10 | 0.00 | 0.00 | 284987.36 | 0.00 | 0.239057E+09 | 0.501677E+09 | 0.00 | 0.69 |
| November | 0.292252E+10 | 0.00 | 2072.29 | 605.49 | 52524.22 | 0.237138E+10 | 5278069.84 | 10667.03 | 0.71 |
| December | 0.125063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715980E+10 | 0.00 | 0.00 | 0.68 |
| Annual Sum or Average | 0.208706E+11 | 0.123621E+10 | 120950.71 | 5493332.60 | 0.179339E+10 | 0.298975E+11 | 0.351076E+10 | 15213.63 | 0.84 |
| Minimum of Months | 0.440123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 588363.45 | 0.00 | 0.00 | 0.68 |
| Maximum of Months | 0.345359E+10 | 0.652423E+09 | 113671.21 | 2168889.31 | 0.803428E+09 | 0.871129E+10 | 0.110871E+10 | 10667.03 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.121730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335478E+11 | 0.00 | 0.00 | 0.70 |
| February | 0.141427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206115E+11 | 0.00 | 0.00 | 0.70 |
| March | 0.196252E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142286E+11 | 0.00 | 0.00 | 0.74 |
| April | 0.167111E+11 | 0.00 | 0.00 | 218976.20 | 20880882.68 | 0.212046E+10 | 0.917077E+09 | 0.00 | 0.71 |
| May | 0.712560E+10 | 0.190017E+09 | 0.00 | 9852180.16 | 5929725.52 | 88871834.77 | 0.572217E+10 | 0.00 | 0.98 |
| June | 0.313274E+10 | 0.268634E+10 | 0.00 | 10103698.91 | 0.158672E+10 | 0.00 | 0.439209E+10 | 0.00 | 1.17 |
| July | 0.229939E+10 | 0.00 | 549324.24 | 0.00 | 0.551341E+10 | 2828737.78 | 0.00 | 14281.00 | 0.97 |
| August | 0.427398E+10 | 0.00 | 890512.85 | 0.00 | 0.422395E+10 | 11358349.31 | 0.00 | 6789.69 | 1.12 |
| September | 0.837560E+10 | 511765.26 | 0.00 | 6507373.94 | 0.116965E+09 | 6937460.08 | 0.553562E+10 | 0.00 | 0.89 |
| October | 0.158499E+11 | 0.00 | 0.00 | 2093759.80 | 0.00 | 0.132828E+09 | 0.418911E+10 | 0.00 | 0.69 |
| November | 0.194346E+11 | 0.00 | 42433.79 | 28396.30 | 252737.60 | 0.597851E+10 | 79869422.95 | 14819.89 | 0.71 |
| December | 0.143251E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261163E+11 | 0.00 | 0.00 | 0.68 |
| Annual Sum or Average | 0.137469E+12 | 0.287686E+10 | 1482270.88 | 28804385.30 | 0.114681E+11 | 0.102846E+12 | 0.208359E+11 | 35890.58 | 0.84 |
| Minimum of Months | 0.229939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
| Maximum of Months | 0.196252E+11 | 0.268634E+10 | 890512.85 | 10103698.91 | 0.551341E+10 | 0.335478E+11 | 0.572217E+10 | 14819.89 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.277477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.674274E+10 | 0.00 | 0.00 | 0.71 |
| February | 0.303736E+10 | 0.00 | 0.00 | 5607.70 | 0.00 | 0.415846E+10 | 36013980.29 | 0.00 | 0.70 |
| March | 0.380044E+10 | 0.00 | 0.00 | 15288.99 | 0.00 | 0.318975E+10 | 52047522.47 | 0.00 | 0.74 |
| April | 0.276006E+10 | 0.00 | 0.00 | 852715.36 | 4339932.71 | 0.683070E+09 | 0.687730E+09 | 0.00 | 0.72 |
| May | 0.143337E+10 | 53298333.89 | 0.00 | 2926878.67 | 602365.07 | 37896095.07 | 0.130007E+10 | 0.00 | 1.05 |
| June | 0.611871E+09 | 0.772368E+09 | 0.00 | 2799096.52 | 0.239328E+09 | 727766.67 | 0.999183E+09 | 0.00 | 1.25 |
| July | 0.371604E+09 | 0.659772E+09 | 51351.87 | 581083.35 | 0.512591E+09 | 201879.39 | 0.108455E+09 | 2494.79 | 0.99 |
| August | 0.819080E+09 | 0.582673E+09 | 0.00 | 374125.55 | 0.333802E+09 | 1095208.05 | 71076916.87 | 0.00 | 1.14 |
| September | 0.114043E+10 | 24109306.07 | 0.00 | 3416439.33 | 3236957.37 | 1102691.81 | 0.192191E+10 | 0.00 | 0.98 |
| October | 0.281890E+10 | 0.00 | 0.00 | 1782278.84 | 0.00 | 0.170745E+09 | 0.135058E+10 | 0.00 | 0.74 |
| November | 0.334778E+10 | 0.00 | 5010.37 | 97933.52 | 52529.59 | 0.173307E+10 | 0.220110E+09 | 9223.77 | 0.71 |
| December | 0.248685E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592945E+10 | 0.00 | 0.00 | 0.68 |
| Annual Sum or Average | 0.254025E+11 | 0.209222E+10 | 56362.24 | 12851447.83 | 0.109395E+10 | 0.226483E+11 | 0.674718E+10 | 11718.56 | 0.87 |
| Minimum of Months | 0.371604E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 201879.39 | 0.00 | 0.00 | 0.68 |
| Maximum of Months | 0.380044E+10 | 0.772368E+09 | 51351.87 | 3416439.33 | 0.512591E+09 | 0.674274E+10 | 0.192191E+10 | 9223.77 | 1.25 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.208355E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249413E+11 | 0.00 | 0.00 | 0.70 |
| February | 0.206564E+11 | 0.00 | 0.00 | 58451.39 | 0.00 | 0.137195E+11 | 0.419121E+09 | 0.00 | 0.70 |
| March | 0.248134E+11 | 0.00 | 0.00 | 388640.70 | 0.00 | 0.798653E+10 | 0.109214E+10 | 0.00 | 0.74 |
| April | 0.140481E+11 | 0.00 | 0.00 | 5586030.69 | 20901983.20 | 0.104266E+10 | 0.493522E+10 | 0.00 | 0.73 |
| May | 0.570446E+10 | 0.216874E+09 | 0.00 | 15818795.62 | 3148896.59 | 61744350.43 | 0.766872E+10 | 0.00 | 1.04 |
| June | 0.280355E+10 | 0.332079E+10 | 0.00 | 13451181.13 | 0.112045E+10 | 0.00 | 0.506379E+10 | 0.00 | 1.23 |
| July | 0.198556E+10 | 0.195598E+10 | 253968.32 | 910776.49 | 0.356332E+10 | 1484063.81 | 0.316585E+09 | 5367.94 | 0.97 |
| August | 0.411316E+10 | 0.181090E+10 | 0.00 | 415498.25 | 0.242202E+10 | 4634968.24 | 0.171503E+09 | 0.00 | 1.12 |
| September | 0.465170E+10 | 0.101375E+09 | 0.00 | 17967612.20 | 17992167.90 | 0.00 | 0.101653E+11 | 0.00 | 0.96 |
| October | 0.118992E+11 | 0.00 | 0.00 | 10639551.65 | 0.00 | 72240773.58 | 0.908720E+10 | 0.00 | 0.74 |
| November | 0.196961E+11 | 0.00 | 53104.88 | 1010126.84 | 252993.00 | 0.394684E+10 | 0.187725E+10 | 4206.65 | 0.71 |
| December | 0.191724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213176E+11 | 0.00 | 0.00 | 0.68 |
| Annual Sum or Average | 0.150380E+12 | 0.740592E+10 | 307073.20 | 66246664.96 | 0.714808E+10 | 0.730946E+11 | 0.407968E+11 | 9574.58 | 0.86 |
| Minimum of Months | 0.198556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
| Maximum of Months | 0.248134E+11 | 0.332079E+10 | 253968.32 | 17967612.20 | 0.356332E+10 | 0.249413E+11 | 0.101653E+11 | 5367.94 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.313970E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629191E+10 | 0.00 | 0.00 | 0.25 |
| February | 0.403323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436010E+10 | 0.00 | 0.00 | 0.24 |
| March | 0.969921E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352139E+10 | 0.00 | 0.00 | 0.24 |
| April | 0.185212E+10 | 0.00 | 0.00 | 0.00 | 2631886.26 | 0.668883E+09 | 0.00 | 0.00 | 0.22 |
| May | 0.115789E+10 | 47226584.52 | 0.00 | 1774915.95 | 396495.28 | 40401872.88 | 0.510346E+09 | 0.00 | 0.35 |
| June | 0.353735E+09 | 0.721705E+09 | 0.00 | 2542571.85 | 0.109553E+09 | 0.00 | 0.758851E+09 | 0.00 | 0.47 |
| July | 0.227528E+09 | 0.420161E+09 | 0.00 | 444383.21 | 0.330429E+09 | 0.00 | 67749745.97 | 0.00 | 0.32 |
| August | 0.514527E+09 | 0.248888E+09 | 0.00 | 103403.69 | 0.308850E+09 | 69355.92 | 25477398.21 | 0.00 | 0.36 |
| September | 0.865328E+09 | 10077211.23 | 0.00 | 2128790.69 | 5393777.72 | 0.00 | 0.102119E+10 | 0.00 | 0.31 |
| October | 0.217434E+10 | 0.00 | 0.00 | 234678.49 | 0.00 | 0.184615E+09 | 0.194756E+09 | 0.00 | 0.22 |
| November | 0.124811E+10 | 0.00 | 3724.96 | 0.00 | 31855.77 | 0.205954E+10 | 0.00 | 4637.60 | 0.23 |
| December | 0.331523E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541913E+10 | 0.00 | 0.00 | 0.24 |
| Annual Sum or Average | 0.104123E+11 | 0.144806E+10 | 3724.96 | 7228743.87 | 0.757286E+09 | 0.225460E+11 | 0.257837E+10 | 4637.60 | 0.29 |
| Minimum of Months | 0.227528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
| Maximum of Months | 0.217434E+10 | 0.721705E+09 | 3724.96 | 2542571.85 | 0.330429E+09 | 0.629191E+10 | 0.102119E+10 | 4637.60 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.854902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.864945E+10 | 0.00 | 0.00 | 0.70 |
| February | 0.143177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579090E+10 | 0.00 | 0.00 | 0.70 |
| March | 0.266013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437423E+10 | 0.00 | 0.00 | 0.74 |
| April | 0.301206E+10 | 0.00 | 0.00 | 21344.41 | 4336361.01 | 0.101319E+10 | 77263714.98 | 0.00 | 0.71 |
| May | 0.164015E+10 | 46561899.40 | 0.00 | 1975708.23 | 819790.62 | 50205960.03 | 0.100381E+10 | 0.00 | 0.99 |
| June | 0.619338E+09 | 0.689234E+09 | 0.00 | 2382431.08 | 0.254765E+09 | 587939.39 | 0.942333E+09 | 0.00 | 1.19 |
| July | 0.428563E+09 | 0.429428E+09 | 51663.93 | 170017.67 | 0.717347E+09 | 316954.42 | 49063177.73 | 2138.41 | 0.97 |
| August | 0.861656E+09 | 0.240026E+09 | 5906.62 | 28237.61 | 0.637348E+09 | 2308017.09 | 25987194.42 | 384.79 | 1.12 |
| September | 0.169945E+10 | 7394682.88 | 0.00 | 1311036.69 | 17001898.58 | 2796557.86 | 0.118507E+10 | 0.00 | 0.89 |
| October | 0.340637E+10 | 0.00 | 0.00 | 332671.36 | 0.00 | 0.227111E+09 | 0.558378E+09 | 0.00 | 0.69 |
| November | 0.294976E+10 | 0.00 | 2340.15 | 1033.80 | 52486.36 | 0.233782E+10 | 7948156.86 | 10527.76 | 0.71 |
| December | 0.125781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714744E+10 | 0.00 | 0.00 | 0.68 |
| Annual Sum or Average | 0.208220E+11 | 0.141264E+10 | 59910.70 | 6222480.85 | 0.163167E+10 | 0.295964E+11 | 0.384985E+10 | 13050.96 | 0.84 |
| Minimum of Months | 0.428563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 316954.42 | 0.00 | 0.00 | 0.68 |
| Maximum of Months | 0.340637E+10 | 0.689234E+09 | 51663.93 | 2382431.08 | 0.717347E+09 | 0.864945E+10 | 0.118507E+10 | 10527.76 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.796192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222469E+11 | 0.00 | 0.00 | 0.70 |
| February | 0.933651E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136265E+11 | 0.00 | 0.00 | 0.70 |
| March | 0.129774E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.939062E+10 | 0.00 | 0.00 | 0.74 |
| April | 0.109155E+11 | 0.00 | 0.00 | 211417.67 | 13796520.13 | 0.138728E+10 | 0.745603E+09 | 0.00 | 0.71 |
| May | 0.448442E+10 | 0.129845E+09 | 0.00 | 7472315.88 | 2124031.47 | 56306405.12 | 0.404335E+10 | 0.00 | 0.99 |
| June | 0.188706E+10 | 0.198871E+10 | 0.00 | 7641883.80 | 0.837472E+09 | 0.00 | 0.316616E+10 | 0.00 | 1.19 |
| July | 0.152015E+10 | 0.192442E+09 | 167921.03 | 0.00 | 0.345060E+10 | 979568.11 | 0.00 | 3255.93 | 0.97 |
| August | 0.282500E+10 | 0.00 | 19654.42 | 0.00 | 0.279144E+10 | 6428667.64 | 0.00 | 362.27 | 1.12 |
| September | 0.519695E+10 | 338136.08 | 0.00 | 4965082.95 | 77281768.35 | 2524045.06 | 0.404393E+10 | 0.00 | 0.90 |
| October | 0.102010E+11 | 0.00 | 0.00 | 1751360.40 | 0.00 | 88285316.97 | 0.304015E+10 | 0.00 | 0.69 |
| November | 0.127593E+11 | 0.00 | 28527.69 | 24460.96 | 166990.04 | 0.398838E+10 | 96181680.31 | 9301.24 | 0.71 |
| December | 0.935372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173669E+11 | 0.00 | 0.00 | 0.68 |
| Annual Sum or Average | 0.894189E+11 | 0.231134E+10 | 216103.13 | 22066521.67 | 0.717289E+10 | 0.681612E+11 | 0.151354E+11 | 12919.44 | 0.84 |
| Minimum of Months | 0.152015E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
| Maximum of Months | 0.129774E+11 | 0.198871E+10 | 167921.03 | 7641883.80 | 0.345060E+10 | 0.222469E+11 | 0.404393E+10 | 9301.24 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.775699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778075E+10 | 0.00 | 0.00 | 0.70 |
| February | 0.841141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339948E+10 | 0.00 | 0.00 | 0.70 |
| March | 0.951988E+10 | 0.00 | 0.00 | 2805.25 | 0.00 | 0.195901E+10 | 25984451.18 | 0.00 | 0.74 |
| April | 0.499545E+10 | 0.00 | 0.00 | 1006109.57 | 7096159.57 | 0.228958E+09 | 0.148679E+10 | 0.00 | 0.71 |
| May | 0.115609E+10 | 89274652.14 | 0.00 | 8161456.96 | 943359.43 | 19953096.92 | 0.352724E+10 | 0.00 | 1.09 |
| June | 0.552020E+09 | 0.174467E+10 | 0.00 | 7995725.58 | 0.236061E+09 | 0.00 | 0.245346E+10 | 0.00 | 1.46 |
| July | 0.468840E+09 | 0.143957E+10 | 0.00 | 926661.60 | 0.441594E+09 | 0.00 | 0.312642E+09 | 0.00 | 0.98 |
| August | 0.127964E+10 | 0.110374E+10 | 0.00 | 361758.27 | 0.332584E+09 | 373909.97 | 0.175952E+09 | 0.00 | 1.13 |
| September | 0.673269E+09 | 37400005.23 | 0.00 | 10508262.17 | 2626315.53 | 0.00 | 0.475040E+10 | 0.00 | 1.05 |
| October | 0.287640E+10 | 0.00 | 0.00 | 4283739.60 | 0.00 | 27282330.93 | 0.404503E+10 | 0.00 | 0.71 |
| November | 0.761590E+10 | 0.00 | 0.00 | 181374.84 | 105347.44 | 0.590784E+09 | 0.456684E+09 | 0.00 | 0.71 |
| December | 0.871380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502982E+10 | 0.00 | 0.00 | 0.68 |
| Annual Sum or Average | 0.540197E+11 | 0.441465E+10 | 0.00 | 33427893.83 | 0.102101E+10 | 0.190364E+11 | 0.172342E+11 | 0.00 | 0.89 |
| Minimum of Months | 0.468840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.68 |
| Maximum of Months | 0.951988E+10 | 0.174467E+10 | 0.00 | 10508262.17 | 0.441594E+09 | 0.778075E+10 | 0.475040E+10 | 0.00 | 1.46 |
Report: MechanicalVentilationLoadsMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.536347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167801E+11 | 0.00 | 0.00 | 0.23 |
| February | 0.655033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106767E+11 | 0.00 | 0.00 | 0.20 |
| March | 0.165083E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.843422E+10 | 0.00 | 0.00 | 0.19 |
| April | 0.420754E+10 | 0.00 | 0.00 | 0.00 | 5795065.96 | 0.130625E+10 | 0.00 | 0.00 | 0.17 |
| May | 0.184638E+10 | 0.121814E+09 | 0.00 | 6970496.20 | 683321.89 | 36970052.29 | 0.230158E+10 | 0.00 | 0.31 |
| June | 0.456578E+09 | 0.218191E+10 | 0.00 | 8829083.71 | 0.187635E+09 | 0.00 | 0.258077E+10 | 0.00 | 0.46 |
| July | 0.300717E+09 | 0.209100E+10 | 0.00 | 2983907.41 | 0.265535E+09 | 0.00 | 0.491961E+09 | 0.00 | 0.33 |
| August | 0.944645E+09 | 0.129604E+10 | 0.00 | 1497803.55 | 0.207189E+09 | 0.00 | 0.289420E+09 | 0.00 | 0.31 |
| September | 0.178483E+10 | 41661314.88 | 0.00 | 5187515.98 | 1849883.88 | 0.00 | 0.243245E+10 | 0.00 | 0.25 |
| October | 0.486087E+10 | 0.00 | 0.00 | 23931.42 | 0.00 | 0.682282E+09 | 66333408.57 | 0.00 | 0.17 |
| November | 0.176557E+10 | 0.00 | 7451.89 | 0.00 | 70142.20 | 0.563651E+10 | 0.00 | 19030.77 | 0.18 |
| December | 0.654285E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135964E+11 | 0.00 | 0.00 | 0.20 |
| Annual Sum or Average | 0.196636E+11 | 0.573244E+10 | 7451.89 | 25492738.26 | 0.668757E+09 | 0.571494E+11 | 0.816250E+10 | 19030.77 | 0.25 |
| Minimum of Months | 0.300717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
| Maximum of Months | 0.486087E+10 | 0.218191E+10 | 7451.89 | 8829083.71 | 0.265535E+09 | 0.167801E+11 | 0.258077E+10 | 19030.77 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 41323290.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116923E+11 | 0.00 | 0.00 | 0.48 |
| February | 59695162.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.867243E+10 | 0.00 | 0.00 | 0.47 |
| March | 90789229.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823765E+10 | 0.00 | 0.00 | 0.49 |
| April | 0.528663E+09 | 0.00 | 0.00 | 0.00 | 3348863.84 | 0.373645E+10 | 0.00 | 0.00 | 0.40 |
| May | 0.103112E+10 | 69695513.98 | 0.00 | 1858306.47 | 504508.39 | 0.114874E+10 | 0.126344E+09 | 0.00 | 0.51 |
| June | 0.739597E+09 | 0.128124E+10 | 847555.04 | 1357390.76 | 0.174330E+09 | 0.254367E+09 | 0.289755E+09 | 17975.12 | 0.65 |
| July | 0.269721E+09 | 0.113004E+10 | 792452.36 | 354715.92 | 0.295397E+09 | 76765328.64 | 52728359.41 | 39426.42 | 0.55 |
| August | 0.410167E+09 | 0.849034E+09 | 2682100.92 | 108610.89 | 0.226815E+09 | 0.327655E+09 | 17914397.40 | 42136.98 | 0.59 |
| September | 0.111089E+10 | 32107684.91 | 0.00 | 401678.20 | 3012839.99 | 0.118368E+10 | 0.137038E+09 | 0.00 | 0.44 |
| October | 0.679390E+09 | 0.00 | 0.00 | 10551.40 | 0.00 | 0.351475E+10 | 9922267.79 | 0.00 | 0.38 |
| November | 97593948.29 | 0.00 | 8366.18 | 0.00 | 11115.18 | 0.592418E+10 | 0.00 | 49343.66 | 0.45 |
| December | 60269750.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102010E+11 | 0.00 | 0.00 | 0.46 |
| Annual Sum or Average | 0.511922E+10 | 0.336211E+10 | 4330474.51 | 4091253.65 | 0.703419E+09 | 0.549700E+11 | 0.633701E+09 | 148882.18 | 0.49 |
| Minimum of Months | 41323290.82 | 0.00 | 0.00 | 0.00 | 0.00 | 76765328.64 | 0.00 | 0.00 | 0.38 |
| Maximum of Months | 0.111089E+10 | 0.128124E+10 | 2682100.92 | 1858306.47 | 0.295397E+09 | 0.116923E+11 | 0.289755E+09 | 49343.66 | 0.65 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.842814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219077E+09 | 0.00 | 0.00 | 0.25 |
| February | 0.656896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2423356.51 | 0.00 | 0.00 | 0.25 |
| March | 0.640113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
| April | 0.373414E+10 | 0.00 | 0.00 | 0.00 | 3948186.60 | 0.00 | 0.00 | 0.00 | 0.26 |
| May | 0.153654E+10 | 44567041.78 | 0.00 | 3489443.78 | 594796.73 | 0.00 | 0.949776E+09 | 0.00 | 0.37 |
| June | 0.406311E+09 | 0.903617E+09 | 0.00 | 4720635.11 | 0.119359E+09 | 0.00 | 0.108578E+10 | 0.00 | 0.47 |
| July | 0.380644E+09 | 0.302297E+09 | 0.00 | 586430.19 | 0.754753E+09 | 0.00 | 62080386.51 | 0.00 | 0.36 |
| August | 0.800656E+09 | 37803270.06 | 0.00 | 267231.37 | 0.762352E+09 | 0.00 | 14382938.26 | 0.00 | 0.41 |
| September | 0.167605E+10 | 112350.93 | 0.00 | 2139911.90 | 22115927.77 | 0.00 | 0.967770E+09 | 0.00 | 0.33 |
| October | 0.381451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
| November | 0.482025E+10 | 0.00 | 0.00 | 0.00 | 58613.59 | 0.00 | 0.00 | 0.00 | 0.25 |
| December | 0.748446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163435E+09 | 0.00 | 0.00 | 0.24 |
| Annual Sum or Average | 0.460518E+11 | 0.128840E+10 | 0.00 | 11203652.35 | 0.166318E+10 | 0.384935E+09 | 0.307979E+10 | 0.00 | 0.31 |
| Minimum of Months | 0.380644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
| Maximum of Months | 0.842814E+10 | 0.903617E+09 | 0.00 | 4720635.11 | 0.762352E+09 | 0.219077E+09 | 0.108578E+10 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.359571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219175E+10 | 0.00 | 0.00 | 0.22 |
| February | 0.358791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.798553E+09 | 0.00 | 0.00 | 0.22 |
| March | 0.397277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292087E+09 | 0.00 | 0.00 | 0.23 |
| April | 0.247893E+10 | 0.00 | 0.00 | 0.00 | 2627679.59 | 6296259.36 | 0.00 | 0.00 | 0.22 |
| May | 0.160716E+10 | 18433477.76 | 0.00 | 78808.01 | 4361604.97 | 0.00 | 8056241.38 | 0.00 | 0.30 |
| June | 0.866818E+09 | 0.286707E+09 | 0.00 | 180566.30 | 0.273128E+09 | 0.00 | 42036860.92 | 0.00 | 0.36 |
| July | 0.288747E+09 | 17340081.03 | 0.00 | 31062.67 | 0.676994E+09 | 0.00 | 1169193.63 | 0.00 | 0.31 |
| August | 0.539130E+09 | 250029.78 | 0.00 | 178.13 | 0.531411E+09 | 0.00 | 143108.81 | 0.00 | 0.36 |
| September | 0.173990E+10 | 0.00 | 0.00 | 0.00 | 14783455.32 | 0.00 | 0.00 | 0.00 | 0.28 |
| October | 0.253871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
| November | 0.308954E+10 | 0.00 | 0.00 | 0.00 | 39009.74 | 0.120513E+09 | 0.00 | 0.00 | 0.22 |
| December | 0.369303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142114E+10 | 0.00 | 0.00 | 0.21 |
| Annual Sum or Average | 0.279984E+11 | 0.322730E+09 | 0.00 | 290615.11 | 0.150334E+10 | 0.483034E+10 | 51405404.74 | 0.00 | 0.26 |
| Minimum of Months | 0.288747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
| Maximum of Months | 0.397277E+10 | 0.286707E+09 | 0.00 | 180566.30 | 0.676994E+09 | 0.219175E+10 | 42036860.92 | 0.00 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.768734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152802E+11 | 0.00 | 0.00 | 0.27 |
| February | 0.163543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102924E+11 | 0.00 | 0.00 | 0.26 |
| March | 0.393075E+10 | 0.00 | 0.00 | 12707.39 | 0.00 | 0.743273E+10 | 1084480.98 | 0.00 | 0.27 |
| April | 0.433938E+10 | 0.00 | 0.00 | 3052208.76 | 8063410.86 | 0.105724E+10 | 0.160573E+10 | 0.00 | 0.28 |
| May | 0.170803E+10 | 0.147536E+09 | 0.00 | 12141924.35 | 950792.47 | 13944463.78 | 0.411681E+10 | 0.00 | 0.54 |
| June | 0.602656E+09 | 0.309421E+10 | 0.00 | 13287769.12 | 0.255003E+09 | 0.00 | 0.371572E+10 | 0.00 | 0.82 |
| July | 0.383823E+09 | 0.315493E+10 | 0.00 | 5060589.00 | 0.296486E+09 | 0.00 | 0.804558E+09 | 0.00 | 0.61 |
| August | 0.951462E+09 | 0.254565E+10 | 0.00 | 4561881.73 | 65393966.16 | 0.00 | 0.787445E+09 | 0.00 | 0.61 |
| September | 0.115251E+10 | 84548698.58 | 0.00 | 16322996.83 | 705860.83 | 0.00 | 0.617884E+10 | 0.00 | 0.57 |
| October | 0.490640E+10 | 0.00 | 0.00 | 4206591.60 | 0.00 | 0.107236E+09 | 0.226702E+10 | 0.00 | 0.28 |
| November | 0.419243E+10 | 0.00 | 10685.58 | 2803.12 | 97597.75 | 0.429439E+10 | 1647081.88 | 11423.63 | 0.25 |
| December | 0.885755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132339E+11 | 0.00 | 0.00 | 0.26 |
| Annual Sum or Average | 0.254574E+11 | 0.902688E+10 | 10685.58 | 58649471.91 | 0.626701E+09 | 0.517120E+11 | 0.194789E+11 | 11423.63 | 0.42 |
| Minimum of Months | 0.383823E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
| Maximum of Months | 0.490640E+10 | 0.315493E+10 | 10685.58 | 16322996.83 | 0.296486E+09 | 0.152802E+11 | 0.617884E+10 | 11423.63 | 0.82 |
Report: MechanicalVentilationLoadsMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.958952E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182165E+11 | 0.00 | 0.00 | 0.57 |
| February | 0.139742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714251E+10 | 0.00 | 0.00 | 0.57 |
| March | 0.169760E+11 | 0.00 | 0.00 | 136026.20 | 0.00 | 0.322431E+10 | 0.357195E+09 | 0.00 | 0.60 |
| April | 0.695674E+10 | 1512910.39 | 0.00 | 8054661.86 | 11407054.86 | 0.219817E+09 | 0.538080E+10 | 0.00 | 0.62 |
| May | 0.149892E+10 | 0.207058E+09 | 0.00 | 21812718.08 | 657694.60 | 8870114.15 | 0.810121E+10 | 0.00 | 1.07 |
| June | 0.674666E+09 | 0.384227E+10 | 0.00 | 20311309.65 | 0.360310E+09 | 0.00 | 0.561955E+10 | 0.00 | 1.42 |
| July | 0.498102E+09 | 0.407193E+10 | 0.00 | 8143418.81 | 0.411916E+09 | 0.00 | 0.119904E+10 | 0.00 | 1.02 |
| August | 0.142758E+10 | 0.304961E+10 | 0.00 | 6993400.37 | 0.104706E+09 | 0.00 | 0.129425E+10 | 0.00 | 1.04 |
| September | 0.147805E+10 | 88516262.80 | 0.00 | 18665228.73 | 1108994.48 | 0.00 | 0.851558E+10 | 0.00 | 0.92 |
| October | 0.792728E+10 | 0.00 | 0.00 | 4460342.20 | 0.00 | 35497052.06 | 0.438107E+10 | 0.00 | 0.57 |
| November | 0.133094E+11 | 0.00 | 39938.05 | 76134.41 | 146026.16 | 0.203398E+10 | 0.133718E+09 | 2110.20 | 0.57 |
| December | 0.109626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136213E+11 | 0.00 | 0.00 | 0.55 |
| Annual Sum or Average | 0.852731E+11 | 0.112609E+11 | 39938.05 | 88653240.31 | 0.890252E+09 | 0.445029E+11 | 0.349824E+11 | 2110.20 | 0.79 |
| Minimum of Months | 0.498102E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.55 |
| Maximum of Months | 0.169760E+11 | 0.407193E+10 | 39938.05 | 21812718.08 | 0.411916E+09 | 0.182165E+11 | 0.851558E+10 | 2110.20 | 1.42 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.716581E+10 | 0.00 | 0.00 | 7081386.28 | 0.00 | 0.460596E+09 | 0.840089E+10 | 0.00 | 0.45 |
| February | 0.312769E+10 | 0.00 | 0.00 | 12728781.35 | 0.00 | 0.00 | 0.117678E+11 | 0.00 | 0.56 |
| March | 0.141928E+10 | 0.00 | 0.00 | 25619522.06 | 0.00 | 0.00 | 0.182948E+11 | 0.00 | 0.81 |
| April | 48963652.48 | 0.00 | 0.00 | 35450112.10 | 0.00 | 0.00 | 0.211707E+11 | 0.00 | 1.66 |
| May | 178369.94 | 58701395.34 | 0.00 | 47152409.67 | 18146.56 | 0.00 | 0.203485E+11 | 0.00 | 2.85 |
| June | 0.00 | 0.140835E+10 | 0.00 | 40736466.31 | 0.00 | 0.00 | 0.142556E+11 | 0.00 | 3.61 |
| July | 0.00 | 0.226917E+10 | 0.00 | 31830242.35 | 380488.85 | 0.00 | 0.993532E+10 | 0.00 | 3.37 |
| August | 89231.36 | 0.956339E+09 | 0.00 | 37620923.14 | 0.00 | 0.00 | 0.141098E+11 | 0.00 | 3.59 |
| September | 0.00 | 19679653.32 | 0.00 | 45852010.43 | 0.00 | 0.00 | 0.218293E+11 | 0.00 | 2.89 |
| October | 17959922.35 | 0.00 | 0.00 | 39273304.94 | 0.00 | 0.00 | 0.225101E+11 | 0.00 | 1.64 |
| November | 0.115214E+10 | 0.00 | 0.00 | 26214340.63 | 0.00 | 0.00 | 0.177812E+11 | 0.00 | 1.06 |
| December | 0.914286E+10 | 0.00 | 0.00 | 7488790.57 | 0.00 | 0.465618E+09 | 0.770998E+10 | 0.00 | 0.54 |
| Annual Sum or Average | 0.220750E+11 | 0.471224E+10 | 0.00 | 0.357048E+09 | 398635.42 | 0.926214E+09 | 0.188114E+12 | 0.00 | 1.93 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 7081386.28 | 0.00 | 0.00 | 0.770998E+10 | 0.00 | 0.45 |
| Maximum of Months | 0.914286E+10 | 0.226917E+10 | 0.00 | 47152409.67 | 380488.85 | 0.465618E+09 | 0.225101E+11 | 0.00 | 3.61 |
Report: MechanicalVentilationLoadsMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.529040E+11 | 0.00 | 0.00 | 116021.89 | 0.00 | 0.549575E+11 | 0.171873E+10 | 0.00 | 1.99 |
| February | 0.388258E+11 | 0.00 | 0.00 | 417022.29 | 0.00 | 0.259489E+11 | 0.628544E+10 | 0.00 | 1.80 |
| March | 0.318976E+11 | 0.00 | 0.00 | 1259911.67 | 0.00 | 0.171547E+11 | 0.146233E+11 | 0.00 | 1.83 |
| April | 0.144593E+11 | 0.00 | 0.00 | 7731952.08 | 0.00 | 0.217036E+10 | 0.170161E+11 | 0.00 | 1.68 |
| May | 0.454951E+10 | 0.446716E+09 | 0.00 | 22675433.89 | 0.00 | 82857371.81 | 0.174937E+11 | 0.00 | 2.20 |
| June | 0.894503E+09 | 0.431660E+10 | 0.00 | 26103114.86 | 0.00 | 0.00 | 0.136831E+11 | 0.00 | 2.67 |
| July | 0.282094E+09 | 0.520716E+10 | 0.00 | 10038198.74 | 0.00 | 0.00 | 0.569569E+10 | 0.00 | 2.24 |
| August | 0.322583E+10 | 0.294560E+10 | 0.00 | 9374415.97 | 0.00 | 0.00 | 0.649566E+10 | 0.00 | 2.38 |
| September | 0.588714E+10 | 0.106555E+09 | 0.00 | 21813900.19 | 0.00 | 8115977.19 | 0.204408E+11 | 0.00 | 2.06 |
| October | 0.157254E+11 | 0.00 | 0.00 | 8017353.24 | 0.00 | 0.453131E+09 | 0.177005E+11 | 0.00 | 1.66 |
| November | 0.234680E+11 | 0.00 | 34800.25 | 3437332.83 | 0.00 | 0.542421E+10 | 0.147105E+11 | 25540.80 | 1.70 |
| December | 0.432206E+11 | 0.00 | 0.00 | 245677.40 | 0.00 | 0.522236E+11 | 0.501252E+10 | 0.00 | 1.83 |
| Annual Sum or Average | 0.235340E+12 | 0.130226E+11 | 34800.25 | 0.111230E+09 | 0.00 | 0.158423E+12 | 0.140876E+12 | 25540.80 | 2.00 |
| Minimum of Months | 0.282094E+09 | 0.00 | 0.00 | 116021.89 | 0.00 | 0.00 | 0.171873E+10 | 0.00 | 1.66 |
| Maximum of Months | 0.529040E+11 | 0.520716E+10 | 34800.25 | 26103114.86 | 0.00 | 0.549575E+11 | 0.204408E+11 | 25540.80 | 2.67 |
Report: MechanicalVentilationLoadsMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.146715E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172905E+11 | 0.00 | 0.00 | 0.34 |
| February | 0.358063E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106142E+11 | 0.00 | 0.00 | 0.34 |
| March | 0.720283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659078E+10 | 0.00 | 0.00 | 0.36 |
| April | 0.534031E+10 | 0.00 | 0.00 | 3634268.91 | 8468896.11 | 0.680964E+09 | 0.237175E+10 | 0.00 | 0.37 |
| May | 0.129993E+10 | 0.162257E+09 | 0.00 | 17052115.35 | 998605.04 | 11244224.82 | 0.619112E+10 | 0.00 | 0.73 |
| June | 0.568601E+09 | 0.326334E+10 | 0.00 | 16946705.56 | 0.251848E+09 | 0.00 | 0.485230E+10 | 0.00 | 1.04 |
| July | 0.402476E+09 | 0.307858E+10 | 0.00 | 4807187.49 | 0.331510E+09 | 0.00 | 0.789384E+09 | 0.00 | 0.67 |
| August | 0.114930E+10 | 0.235592E+10 | 0.00 | 3517933.46 | 75662251.64 | 0.00 | 0.688626E+09 | 0.00 | 0.67 |
| September | 0.708600E+09 | 72267694.23 | 0.00 | 18806631.69 | 741356.50 | 0.00 | 0.791318E+10 | 0.00 | 0.68 |
| October | 0.437893E+10 | 0.00 | 0.00 | 7226493.75 | 0.00 | 40097144.30 | 0.468008E+10 | 0.00 | 0.38 |
| November | 0.718713E+10 | 0.00 | 0.00 | 180951.19 | 125726.67 | 0.297767E+10 | 0.201742E+09 | 0.00 | 0.34 |
| December | 0.324882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133035E+11 | 0.00 | 0.00 | 0.33 |
| Annual Sum or Average | 0.365347E+11 | 0.893237E+10 | 0.00 | 72172287.40 | 0.669355E+09 | 0.515090E+11 | 0.276882E+11 | 0.00 | 0.52 |
| Minimum of Months | 0.402476E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
| Maximum of Months | 0.720283E+10 | 0.326334E+10 | 0.00 | 18806631.69 | 0.331510E+09 | 0.172905E+11 | 0.791318E+10 | 0.00 | 1.04 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:31:19
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.305271E+12 | 0.450187E+11 | 0.295035E+12 | 0.411242E+12 | 0.229565E+12 |
| February | 0.534572E+12 | 0.368400E+11 | 0.217267E+12 | 0.326441E+12 | 0.155721E+12 |
| March | 0.829526E+12 | 0.304433E+11 | 0.211505E+12 | 0.358743E+12 | 0.129259E+12 |
| April | 0.111152E+13 | 0.227449E+11 | 0.154094E+12 | 0.345231E+12 | 0.596430E+11 |
| May | 0.133808E+13 | 0.120107E+11 | 0.107791E+12 | 0.457826E+12 | 0.177310E+12 |
| June | 0.137270E+13 | 0.310342E+10 | 0.486580E+11 | 0.256443E+12 | 0.360307E+12 |
| July | 0.139994E+13 | -372933181.8 | 0.248979E+11 | 0.139281E+12 | 0.351524E+12 |
| August | 0.115241E+13 | 0.389509E+10 | 0.518743E+11 | 0.280442E+12 | 0.285468E+12 |
| September | 0.825741E+12 | 0.130102E+11 | 0.129263E+12 | 0.559690E+12 | 0.853677E+11 |
| October | 0.436266E+12 | 0.203686E+11 | 0.196771E+12 | 0.506323E+12 | 0.497744E+11 |
| November | 0.168160E+12 | 0.288392E+11 | 0.197909E+12 | 0.312069E+12 | 0.878079E+11 |
| December | 0.181962E+12 | 0.437804E+11 | 0.320273E+12 | 0.338792E+12 | 0.198407E+12 |
| Annual Sum or Average | 0.965615E+13 | 0.259682E+12 | 0.195534E+13 | 0.429252E+13 | 0.217015E+13 |
| Minimum of Months | 0.168160E+12 | -372933181.8 | 0.248979E+11 | 0.139281E+12 | 0.497744E+11 |
| Maximum of Months | 0.139994E+13 | 0.450187E+11 | 0.320273E+12 | 0.559690E+12 | 0.360307E+12 |