Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:27
Tabular Output Report in Format: HTML
Building: SchoolPrimary
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2024-07-03 12:27:52
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 4159.75 | 605.41 | 605.41 |
| Net Site Energy | 4159.75 | 605.41 | 605.41 |
| Total Source Energy | 10606.09 | 1543.60 | 1543.60 |
| Net Source Energy | 10606.09 | 1543.60 | 1543.60 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 6871.00 |
| Net Conditioned Building Area | 6871.00 |
| Unconditioned Building Area | 0.00 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 712.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 84.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 1218.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 92.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1151.36 | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 316.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 1.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 159.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.47 |
| Refrigeration | 44.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 2926.99 | 1232.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.47 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 445.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Boiler | 0.00 | 267.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Cooling | General | 84.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 1218.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 92.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooking | 149.71 | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInFreezer | 31.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInRefrigerator | 23.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | Transformer | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | General | 316.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | General | 1.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Heater | 0.00 | 159.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.99 | |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.48 | |
| Refrigeration | General | 7.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LowTempRefrigeration | 15.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MedTempRefrigeration | 22.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 712.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 84.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 1218.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 92.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 1151.36 | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 316.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 1.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 0.00 | 159.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.47 |
| Refrigeration | Unassigned | 44.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 190.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 58.56 | 126.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Other | 176.68 | 52.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 425.99 | 179.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 190.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 58.56 | 126.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Other | 176.68 | 52.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 425.99 | 179.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 2926.989 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 2926.989 | 100.00 |
| Total On-Site and Utility Electric Sources | 2926.989 | 100.00 |
| Total Electricity End Uses | 2926.989 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | |
| Air to Air Heat Recovery for Cooling | 0.00 | |
| Air to Air Heat Recovery for Heating | 0.00 | |
| High-Temperature Geothermal* | 0.00 | |
| Solar Water Thermal | 0.00 | |
| Solar Air Thermal | 0.00 | |
| Total On-Site Thermal Sources | 0.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 718.47 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 718.47 | 100.00 |
| Total Water End Uses | 718.47 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 825.17 |
| Time Setpoint Not Met During Occupied Cooling | 1.17 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1346.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME SCHOOLPRIMARY
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |ZoneHeatingSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |ZoneElectricSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |SpaceGainsMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |PeakSpaceGainsMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |SpaceGainComponentsAtCoolingPeakMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |ComfortReportSimple55Monthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |OccupantComfortDataSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_POD_1 COOLING COIL | PSZ-AC_1:6 COOLING COIL | PSZ-AC_2:7 COOLING COIL |WindowReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 |WindowEnergyReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 |WindowZoneSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |WindowEnergyZoneSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | VAV_POD_1 HEATING COIL | PSZ-AC_1:6 HEATING COIL | PSZ-AC_2:7 HEATING COIL | VAV_POD_1 COOLING COIL | PSZ-AC_1:6 COOLING COIL | PSZ-AC_2:7 COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| VAV_POD_1 FAN | BATH_ZN_1_FLR_1 EXHAUST FAN | GYM_ZN_1_FLR_1 EXHAUST FAN | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN | KITCHEN_ZN_1_FLR_1 EXHAUST FAN | CAFETERIA_ZN_1_FLR_1 EXHAUST FAN | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_POD_1 | PSZ-AC_1:6 | PSZ-AC_2:7 |AirLoopSystemComponentLoadsMonthly
| VAV_POD_1 | PSZ-AC_1:6 | PSZ-AC_2:7 |AirLoopSystemComponentEnergyUseMonthly
| VAV_POD_1 | PSZ-AC_1:6 | PSZ-AC_2:7 |MechanicalVentilationLoadsMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:27 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
| Latitude [deg] | 48.12 |
| Longitude [deg] | -123.5 |
| Elevation [m] | 91.00 |
| Time Zone | -8.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Above Ground Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Window Opening Area [m2] | 552.60 | 204.13 | 72.16 | 204.16 | 72.16 |
| Gross Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Above Ground Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Above Ground Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Window Opening Area [m2] | 552.60 | 204.13 | 72.16 | 204.16 | 72.16 |
| Gross Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Above Ground Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Total | |
| Gross Roof Area [m2] | 6871.00 |
| Skylight Area [m2] | 13.38 |
| Skylight-Roof Ratio [%] | 0.19 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | Yes | Yes | 768.00 | 1.00 | 12.00 | 0.00 | 2.64 | 2.64 | 5.4810 | 18.58 | 4.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | Yes | Yes | 768.00 | 1.00 | 12.00 | 0.00 | 2.64 | 2.64 | 5.4810 | 18.58 | 4.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | Yes | Yes | 768.00 | 1.00 | 12.00 | 0.00 | 2.64 | 2.64 | 5.4810 | 18.58 | 4.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.57 | 17.57 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1260.00 | 1.00 | 140.00 | 0.00 | 30.80 | 30.80 | 15.0695 | 3.72 | 15.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | Yes | Yes | 648.00 | 1.00 | 72.00 | 0.00 | 15.84 | 15.84 | 15.0695 | 3.72 | 20.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | Yes | Yes | 2184.00 | 1.00 | 36.00 | 0.00 | 7.92 | 7.92 | 5.4810 | 18.58 | 4.0000 |
| LOBBY_ZN_1_FLR_1 | 171.00 | Yes | Yes | 684.00 | 1.00 | 76.00 | 0.00 | 16.72 | 16.72 | 13.9931 | 9.29 | 4.0000 |
| MECH_ZN_1_FLR_1 | 252.00 | Yes | Yes | 1008.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.1458 | 61.93 | 10.0000 |
| BATH_ZN_1_FLR_1 | 190.00 | Yes | Yes | 760.00 | 1.00 | 40.00 | 0.00 | 8.80 | 8.80 | 9.6875 | 18.58 | 4.0000 |
| OFFICES_ZN_1_FLR_1 | 441.00 | Yes | Yes | 1764.00 | 1.00 | 168.00 | 0.00 | 36.96 | 36.96 | 11.8403 | 18.58 | 10.8000 |
| GYM_ZN_1_FLR_1 | 357.00 | Yes | Yes | 1428.00 | 1.00 | 68.00 | 0.00 | 14.96 | 14.96 | 13.3472 | 3.10 | 5.0000 |
| KITCHEN_ZN_1_FLR_1 | 168.00 | Yes | Yes | 672.00 | 1.00 | 32.00 | 0.00 | 7.04 | 7.04 | 12.9167 | 6.22 | 1631.7643 |
| CAFETERIA_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1260.00 | 1.00 | 144.00 | 0.00 | 31.68 | 31.68 | 9.6875 | 0.93 | 25.3900 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | Yes | Yes | 1596.00 | 1.00 | 160.00 | 0.00 | 35.20 | 35.20 | 16.6840 | 9.29 | 15.0000 |
| Total | 6871.00 | 27484.00 | 2512.00 | 0.00 | 552.60 | 552.60 | 12.8652 | 4.37 | 51.7784 | |||
| Conditioned Total | 6871.00 | 27484.00 | 2512.00 | 0.00 | 552.60 | 552.60 | 12.8652 | 4.37 | 51.7784 | |||
| Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | Yes | Yes | 1.00 | CORRIDOR_POD_1_ZN_1_FLR_1 | GENERAL | CORRIDOR_POD_1_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | Yes | Yes | 1.00 | CORRIDOR_POD_2_ZN_1_FLR_1 | GENERAL | CORRIDOR_POD_2_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | Yes | Yes | 1.00 | CORRIDOR_POD_3_ZN_1_FLR_1 | GENERAL | CORRIDOR_POD_3_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | Yes | Yes | 1.00 | COMPUTER_CLASS_ZN_1_FLR_1 | GENERAL | COMPUTER_CLASS_ZN_1_FLR_1 | 15.0695 | 3.72 | 20.0000 | |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | Yes | Yes | 1.00 | MAIN_CORRIDOR_ZN_1_FLR_1 | GENERAL | MAIN_CORRIDOR_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| LOBBY_ZN_1_FLR_1 | 171.00 | Yes | Yes | 1.00 | LOBBY_ZN_1_FLR_1 | GENERAL | LOBBY_ZN_1_FLR_1 | 13.9931 | 9.29 | 4.0000 | |
| MECH_ZN_1_FLR_1 | 252.00 | Yes | Yes | 1.00 | MECH_ZN_1_FLR_1 | GENERAL | MECH_ZN_1_FLR_1 | 16.1458 | 61.93 | 10.0000 | |
| BATH_ZN_1_FLR_1 | 190.00 | Yes | Yes | 1.00 | BATH_ZN_1_FLR_1 | GENERAL | BATH_ZN_1_FLR_1 | 9.6875 | 18.58 | 4.0000 | |
| OFFICES_ZN_1_FLR_1 | 441.00 | Yes | Yes | 1.00 | OFFICES_ZN_1_FLR_1 | GENERAL | OFFICES_ZN_1_FLR_1 | 11.8403 | 18.58 | 10.8000 | |
| GYM_ZN_1_FLR_1 | 357.00 | Yes | Yes | 1.00 | GYM_ZN_1_FLR_1 | GENERAL | GYM_ZN_1_FLR_1 | 13.3472 | 3.10 | 5.0000 | |
| KITCHEN_ZN_1_FLR_1 | 168.00 | Yes | Yes | 1.00 | KITCHEN_ZN_1_FLR_1 | GENERAL | KITCHEN_ZN_1_FLR_1 | 12.9167 | 6.22 | 1631.7643 | |
| CAFETERIA_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1.00 | CAFETERIA_ZN_1_FLR_1 | GENERAL | CAFETERIA_ZN_1_FLR_1 | 9.6875 | 0.93 | 25.3900 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | Yes | Yes | 1.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | GENERAL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 16.6840 | 9.29 | 15.0000 | |
| Total | 6871.00 | 12.8652 | 2.19 | 51.7784 | |||||||
| Conditioned Total | 6871.00 | 12.8652 | 2.19 | 51.7784 | |||||||
| Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 6871.00 | 6871.00 | 0.00 | 0.00 | 12.8652 | 4.37 | 51.7784 |
| Total | 6871.00 | 6871.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 13-JUN-13:00 | 10-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | 02-JAN-13:09 |
| Heating | 0.00 | 484969.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 105755.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 79557.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 72814.64 | 36063.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 1213.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 47154.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 13.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 11699.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 1389.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 307898.07 | 532733.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 271403.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Boiler | 0.00 | 213566.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Cooling | General | 105755.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 79557.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 65099.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooking | 5999.02 | 36063.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInFreezer | 986.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInRefrigerator | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | Transformer | 1213.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | General | 47154.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | General | 13.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Heater | 0.00 | 11699.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 241.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LowTempRefrigeration | 431.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MedTempRefrigeration | 715.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 772.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 268.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 3858.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 292.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 3646.35 | 391.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 55.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 1003.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 3.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 172.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 142.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 9269.78 | 1336.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 112.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 39.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 561.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 42.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 530.69 | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 8.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 145.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 25.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 20.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1349.12 | 194.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 112.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 39.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 561.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 42.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 530.69 | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 8.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 145.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 25.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 20.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1349.12 | 194.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
AirTerminal:SingleDuct:VAV:Reheat| Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 0.627075 | 0.120301 | 0.427000 | 0.267761 | 0.427000 | 0.500000 | 0.003167 | 0.000053 | 0.267761 | 12.89 | 0.008000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 2.68 | 0.135417 | 0.480000 | 1.29 | 0.480000 | 0.500000 | 0.002814 | 0.000208 | 1.29 | 12.89 | 0.008000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 0.504400 | 0.290055 | 0.300000 | 0.151320 | 0.773481 | 0.500000 | 0.001314 | 0.000053 | 0.260581 | 12.89 | 0.008000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 0.528141 | 0.142837 | 0.506000 | 0.267239 | 0.506000 | 0.500000 | 0.002667 | 0.000053 | 0.267239 | 12.89 | 0.008000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 2.12 | 0.171651 | 0.609000 | 1.29 | 0.609000 | 0.500000 | 0.002220 | 0.000206 | 1.29 | 12.89 | 0.008000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 0.623345 | 0.121021 | 0.429000 | 0.267415 | 0.429000 | 0.500000 | 0.003148 | 0.000053 | 0.267415 | 12.89 | 0.008000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 2.65 | 0.136921 | 0.485000 | 1.29 | 0.485000 | 0.500000 | 0.002783 | 0.000206 | 1.29 | 12.89 | 0.008000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 0.502803 | 0.290977 | 0.300000 | 0.150841 | 0.775939 | 0.500000 | 0.001309 | 0.000053 | 0.259954 | 12.89 | 0.008000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 0.528362 | 0.142777 | 0.506000 | 0.267351 | 0.506000 | 0.500000 | 0.002668 | 0.000053 | 0.267351 | 12.89 | 0.008000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 2.12 | 0.171580 | 0.608000 | 1.29 | 0.608000 | 0.500000 | 0.002221 | 0.000206 | 1.29 | 12.89 | 0.008000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 0.623802 | 0.120933 | 0.429000 | 0.267611 | 0.429000 | 0.500000 | 0.003151 | 0.000053 | 0.267611 | 12.89 | 0.008000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 2.67 | 0.136376 | 0.484000 | 1.29 | 0.484000 | 0.500000 | 0.002794 | 0.000207 | 1.29 | 12.89 | 0.008000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 0.507544 | 0.288259 | 0.300000 | 0.152263 | 0.768690 | 0.500000 | 0.001322 | 0.000053 | 0.260211 | 12.89 | 0.008000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 0.531723 | 0.141875 | 0.503000 | 0.267457 | 0.503000 | 0.500000 | 0.002685 | 0.000053 | 0.267457 | 12.89 | 0.008000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 1.42 | 0.169014 | 0.599000 | 0.850686 | 0.599000 | 0.500000 | 0.002254 | 0.000138 | 0.850686 | 12.89 | 0.008000 |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | 0.790041 | 0.156250 | 0.554000 | 0.437683 | 0.554000 | 0.500000 | 0.002438 | 0.000068 | 0.437683 | 12.89 | 0.008000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | 1.06 | 0.393602 | 0.300000 | 0.317111 | 1.00 | 0.500000 | 0.000968 | 0.000125 | 0.610545 | 12.89 | 0.008000 |
| LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | 0.676599 | 0.192584 | 0.300000 | 0.202980 | 0.513557 | 0.500000 | 0.001978 | 0.000072 | 0.350187 | 12.89 | 0.008000 |
| MECH_ZN_1_FLR_1 VAV BOX COMPONENT | 0.774835 | 0.247826 | 0.300000 | 0.232450 | 0.660869 | 0.500000 | 0.001537 | 0.000039 | 0.232450 | 12.89 | 0.008000 |
| BATH_ZN_1_FLR_1 VAV BOX COMPONENT | 0.491944 | 0.294301 | 0.300000 | 0.147583 | 0.784804 | 0.500000 | 0.001295 | 0.000056 | 0.275031 | 12.89 | 0.008000 |
| OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | 1.56 | 0.573422 | 0.500000 | 0.001772 | 0.000152 | 0.743055 | 12.89 | 0.008000 | |||
| GYM_ZN_1_FLR_1 VAV BOX COMPONENT | 1.72 | 0.158005 | 0.454000 | 0.781644 | 0.454000 | 0.500000 | 0.002411 | 0.000131 | 0.781644 | 12.89 | 0.008000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | 1.61 | 0.188923 | 0.308000 | 0.495671 | 0.503795 | 0.500000 | 0.002017 | 0.000131 | 0.641259 | 12.89 | 0.008000 |
| Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6107.66 | 0.000053 | 141.56 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23740.52 | 0.000208 | 523.58 |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6085.08 | 0.000053 | 141.94 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6061.71 | 0.000053 | 140.28 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23500.19 | 0.000206 | 517.12 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6079.61 | 0.000053 | 140.78 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23539.30 | 0.000206 | 518.32 |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6070.45 | 0.000053 | 141.59 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6065.04 | 0.000053 | 140.37 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23493.76 | 0.000206 | 517.08 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6084.06 | 0.000053 | 140.89 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23606.95 | 0.000207 | 519.91 |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6076.43 | 0.000053 | 141.73 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6088.54 | 0.000053 | 141.04 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 15730.58 | 0.000138 | 347.17 |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | 7769.21 | 0.000068 | 170.08 |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | 14257.39 | 0.000125 | 332.56 |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | 8177.24 | 0.000072 | 190.73 |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 4465.51 | 0.000039 | 99.34 |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6422.37 | 0.000056 | 149.80 |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | 17351.12 | 0.000152 | 404.71 |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | 15003.37 | 0.000131 | 333.71 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | 14974.00 | 0.000131 | 349.27 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| KITCHEN_ZN_1_FLR_1 DIRECT AIR | 1.52 |
| CAFETERIA_ZN_1_FLR_1 DIRECT AIR | 2.56 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| VAV_POD_1 | 14.31 | 12.44 | 27.32 | 12.44 | 27.10 | 27.10 | 0.300000 | 0.458999 | 27.10 |
| PSZ-AC_1:6 | 1.52 | 1.52 | 1.52 | 1.52 | 1.52 | 1.52 | 1.00 | 1.00 | 1.52 |
| PSZ-AC_2:7 | 2.56 | 2.56 | 2.56 | 2.56 | 2.56 | 2.56 | 1.00 | 1.00 | 2.56 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| VAV_POD_1_OA_CONTROLLER | 27.10 | |
| PSZ-AC_1:6_OA_CONTROLLER | 1.52 | 0.254814 |
| PSZ-AC_2:7_OA_CONTROLLER | 2.56 | 1.49 |
| Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
| VAV_POD_1 COOLING COIL | 27.10 | 488636.69 | 0.800489 | 9.03 | 162862.61 | 0.800489 |
| Design Size Nominal Capacity [W] | |
| VAV_POD_1 HEATING COIL | 167276.58 |
| PSZ-AC_1:6 HEATING COIL | 59717.73 |
| PSZ-AC_2:7 HEATING COIL | 79107.52 |
| Design Size Maximum Flow Rate [m3/s] | |
| VAV_POD_1 FAN | 27.10 |
| Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
| PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.52 | 2525.20 |
| PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | 2.56 | 4150.67 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| PSZ-AC_1:6_UNITARY_PACKAGE_DX | 1.52 | 1.52 | 1.52 | 1.52 | 29570.63 | 59717.73 | 32.11 | 1.00 |
| PSZ-AC_2:7_UNITARY_PACKAGE_DX | 2.56 | 2.56 | 2.56 | 2.56 | 47977.82 | 79107.52 | 32.11 | 1.00 |
| User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
| PSZ-AC_1:6 COOLING COIL | 1.52 | 0.759687 | 1.01 | 29570.63 | 14785.32 | 0.786710 | 0.786710 |
| PSZ-AC_2:7 COOLING COIL | 2.56 | 1.28 | 1.71 | 47977.82 | 23988.91 | 0.800580 | 0.800580 |
| Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
| HEATSYS1 | 0.002421 | 0.290536 |
| SWHSYS1 | 0.000105 | 0.012650 |
| Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
| HEATSYS1 PUMP | 0.002421 | 729.14 | 0.000000 |
| Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
| HEATSYS1 BOILER | 276750.10 | 276750.10 | 0.002421 |
| Design Flow Rate [m3/s] | Design Power Consumption [W] | |
| SWHSYS1 PUMP | 0.000105 | 13.47 |
| Use Side Design Flow Rate [m3/s] | |
| SWHSYS1 WATER HEATER | 0.000105 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| Possible Shadow Receivers | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | BATH_ZN_1_FLR_1_WALL_5 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | BATH_ZN_1_FLR_1_WALL_5 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | |
| BATH_ZN_1_FLR_1_WALL_5 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | |
| CAFETERIA_ZN_1_FLR_1_WALL_3 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | CAFETERIA_ZN_1_FLR_1_WALL_3 | |
| Possible Shadow Receivers | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | |
| LOBBY_ZN_1_FLR_1_WALL_1 | LOBBY_ZN_1_FLR_1_WALL_1_DOOR | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| BATH_ZN_1_FLR_1_WALL_5 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | |
| OFFICES_ZN_1_FLR_1_WALL_1 | OFFICES_ZN_1_FLR_1_WALL_1_DOOR | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| OFFICES_ZN_1_FLR_1_WALL_2 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | |
| GYM_ZN_1_FLR_1_WALL_2 | GYM_ZN_1_FLR_1_WALL_2_DOOR | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | |
| GYM_ZN_1_FLR_1_CEILING | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | |
| KITCHEN_ZN_1_FLR_1_WALL_2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | |
| CAFETERIA_ZN_1_FLR_1_WALL_2 | CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | |
| CAFETERIA_ZN_1_FLR_1_WALL_3 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | Yes | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 9.23 | 11.60 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | SchoolPrimary | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 25 | 288 | 92 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.0 | -64.00 | 0.00 | 0.00 | -58.50 | 4.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 0.00 | 9.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 0.0 | -53.00 | 0.00 | 0.00 | -26.50 | 4.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 0.00 | 9.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | 0.0 | -64.00 | 9.00 | 0.00 | -32.00 | 10.50 | 2.00 | 1 | 1 | 1 | -64.00 | 0.00 | 9.00 | 12.00 | 0.00 | 4.00 | 4.00 | 768.00 | TARP | TARP | 192.00 | 12.00 | 9.36 | 2.64 | 8 | 1 | 0 | Yes |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.0 | -64.00 | 12.00 | 0.00 | -58.50 | 16.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 12.00 | 21.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 0.0 | -53.00 | 12.00 | 0.00 | -26.50 | 16.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 12.00 | 21.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.0 | -64.00 | 30.00 | 0.00 | -58.50 | 34.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 30.00 | 39.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 0.0 | -53.00 | 30.00 | 0.00 | -26.50 | 34.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 30.00 | 39.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | 0.0 | -64.00 | 39.00 | 0.00 | -32.00 | 40.50 | 2.00 | 1 | 1 | 1 | -64.00 | 0.00 | 39.00 | 42.00 | 0.00 | 4.00 | 4.00 | 768.00 | TARP | TARP | 192.00 | 12.00 | 9.36 | 2.64 | 8 | 1 | 0 | Yes |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.0 | -64.00 | 42.00 | 0.00 | -58.50 | 46.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 42.00 | 51.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 0.0 | -53.00 | 42.00 | 0.00 | -26.50 | 46.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 42.00 | 51.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.0 | -64.00 | 61.00 | 0.00 | -58.50 | 65.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 61.00 | 70.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 0.0 | -53.00 | 61.00 | 0.00 | -26.50 | 65.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 61.00 | 70.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | 0.0 | -64.00 | 70.00 | 0.00 | -32.00 | 71.50 | 2.00 | 1 | 1 | 1 | -64.00 | 0.00 | 70.00 | 73.00 | 0.00 | 4.00 | 4.00 | 768.00 | TARP | TARP | 192.00 | 12.00 | 9.36 | 2.64 | 9 | 1 | 0 | Yes |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.0 | -64.00 | 73.00 | 0.00 | -58.50 | 77.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 73.00 | 82.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.48 | 17.57 | 6 | 4 | 0 | Yes |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.0 | -53.00 | 73.00 | 0.00 | -35.50 | 77.50 | 2.00 | 1 | 1 | 1 | -53.00 | -18.00 | 73.00 | 82.00 | 0.00 | 4.00 | 4.00 | 1260.00 | TARP | TARP | 315.00 | 140.00 | 105.30 | 30.80 | 6 | 5 | 0 | Yes |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | 0.0 | -18.00 | 73.00 | 0.00 | -9.00 | 77.50 | 2.00 | 1 | 1 | 1 | -18.00 | 0.00 | 73.00 | 82.00 | 0.00 | 4.00 | 4.00 | 648.00 | TARP | TARP | 162.00 | 72.00 | 54.21 | 15.84 | 6 | 3 | 0 | Yes |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | 0.0 | 0.00 | 9.00 | 0.00 | 6.50 | 30.00 | 2.00 | 1 | 1 | 1 | 0.00 | 13.00 | 9.00 | 51.00 | 0.00 | 4.00 | 4.00 | 2184.00 | TARP | TARP | 546.00 | 36.00 | 26.13 | 7.92 | 11 | 3 | 0 | Yes |
| 18 | LOBBY_ZN_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 9.50 | 4.50 | 2.00 | 1 | 1 | 1 | 0.00 | 19.00 | 0.00 | 9.00 | 0.00 | 4.00 | 4.00 | 684.00 | TARP | TARP | 171.00 | 76.00 | 57.33 | 16.72 | 7 | 3 | 0 | Yes |
| 19 | MECH_ZN_1_FLR_1 | 0.0 | 13.00 | 9.00 | 0.00 | 16.00 | 30.00 | 2.00 | 1 | 1 | 1 | 13.00 | 19.00 | 9.00 | 51.00 | 0.00 | 4.00 | 4.00 | 1008.00 | TARP | TARP | 252.00 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
| 20 | BATH_ZN_1_FLR_1 | 0.0 | 0.00 | 51.00 | 0.00 | 9.50 | 56.00 | 2.00 | 1 | 1 | 1 | 0.00 | 19.00 | 51.00 | 61.00 | 0.00 | 4.00 | 4.00 | 760.00 | TARP | TARP | 190.00 | 40.00 | 31.20 | 8.80 | 7 | 1 | 0 | Yes |
| 21 | OFFICES_ZN_1_FLR_1 | 0.0 | 19.00 | 0.00 | 0.00 | 29.50 | 10.50 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 0.00 | 21.00 | 0.00 | 4.00 | 4.00 | 1764.00 | TARP | TARP | 441.00 | 168.00 | 129.09 | 36.96 | 7 | 4 | 0 | Yes |
| 22 | GYM_ZN_1_FLR_1 | 0.0 | 19.00 | 21.00 | 0.00 | 29.50 | 29.50 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 21.00 | 38.00 | 0.00 | 4.00 | 4.00 | 1428.00 | TARP | TARP | 357.00 | 68.00 | 51.09 | 28.34 | 6 | 12 | 0 | Yes |
| 23 | KITCHEN_ZN_1_FLR_1 | 0.0 | 19.00 | 38.00 | 0.00 | 29.50 | 42.00 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 38.00 | 46.00 | 0.00 | 4.00 | 4.00 | 672.00 | TARP | TARP | 168.00 | 32.00 | 24.96 | 7.04 | 6 | 1 | 0 | Yes |
| 24 | CAFETERIA_ZN_1_FLR_1 | 0.0 | 19.00 | 46.00 | 0.00 | 29.50 | 53.50 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 46.00 | 61.00 | 0.00 | 4.00 | 4.00 | 1260.00 | TARP | TARP | 315.00 | 144.00 | 110.37 | 31.68 | 7 | 4 | 0 | Yes |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.0 | 0.00 | 61.00 | 0.00 | 9.50 | 71.50 | 2.00 | 1 | 1 | 1 | 0.00 | 19.00 | 61.00 | 82.00 | 0.00 | 4.00 | 4.00 | 1596.00 | TARP | TARP | 399.00 | 160.00 | 122.85 | 35.20 | 8 | 4 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 3.716 | 0.269 | 15.069 | 20.000 | 0.000 | 0.000 | 0.000 | 0.000 | 35.069 | No |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 18 | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 9.289 | 0.108 | 13.993 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.993 | No |
| 19 | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 61.932 | 1.615E-002 | 16.146 | 10.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26.146 | No |
| 20 | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 18.578 | 5.383E-002 | 9.688 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.688 | No |
| 21 | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 18.579 | 5.382E-002 | 11.840 | 10.800 | 0.000 | 0.000 | 0.000 | 0.000 | 22.640 | No |
| 22 | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 3.096 | 0.323 | 13.347 | 5.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.347 | No |
| 23 | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 6.224 | 0.161 | 12.917 | 200.664 | 1431.100 | 0.000 | 0.000 | 0.000 | 1644.681 | No |
| 24 | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 0.929 | 1.076 | 9.688 | 25.390 | 0.000 | 0.000 | 0.000 | 0.000 | 35.078 | No |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 9.289 | 0.108 | 16.684 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 31.684 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 10.3 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 10.3 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 10.3 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 84.8 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 81 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | BLDG_OCC_SCH_EXTEND | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 43.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 41 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 17 | MECH_ZN_1_FLR_1 | BLDG_OCC_SCH | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 4.1 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 4 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 18 | BATH_ZN_1_FLR_1 | BLDG_OCC_SCH | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 10.2 | 5.383E-002 | 18.578 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 19 | OFFICES_ZN_1_FLR_1 | BLDG_OCC_SCH_OFFICES_W_SB | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 23.7 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 23 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 20 | GYM_ZN_1_FLR_1 | BLDG_OCC_SCH_GYM | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 115.3 | 0.323 | 3.096 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 110 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 21 | KITCHEN_ZN_1_FLR_1 | BLDG_OCC_SCH | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 27.0 | 0.161 | 6.224 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 26 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 22 | CAFETERIA_ZN_1_FLR_1 | BLDG_OCC_SCH_CAFETERIA | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 339.1 | 1.076 | 0.929 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 322 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 23 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | BLDG_OCC_SCH | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 43.0 | 0.108 | 9.289 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 41 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 24 | MAIN_CORRIDOR_ZN_1_FLR_1 | BLDG_OCC_SCH | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 29.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 25 | LOBBY_ZN_1_FLR_1 | BLDG_OCC_SCH | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 18.4 | 0.108 | 9.289 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 1052.352 | 5.481 | 101.834 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1052.352 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 1052.352 | 5.481 | 101.834 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1052.352 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 1052.352 | 5.481 | 101.834 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1052.352 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 4746.880 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 4746.880 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1_LIGHTS | LTG_SCH_COMPUTER_ROOM | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 2441.253 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2441.253 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 2992.626 | 5.481 | 101.832 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2992.626 |
| 18 | LOBBY_ZN_1_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 2392.815 | 13.993 | 129.988 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2392.815 |
| 19 | MECH_ZN_1_FLR_1_LIGHTS | LTG_SCH_MECHANICAL | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 4068.754 | 16.146 | 999.940 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 4068.754 |
| 20 | BATH_ZN_1_FLR_1_LIGHTS | LTG_SCH_BATH | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 1840.627 | 9.688 | 179.977 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1840.627 |
| 21 | OFFICES_ZN_1_FLR_1_LIGHTS | LTG_SCH_OFFICE | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 5221.568 | 11.840 | 219.981 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 5221.568 |
| 22 | GYM_ZN_1_FLR_1_LIGHTS | LTG_SCH_GYM | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 4764.965 | 13.347 | 41.323 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 4764.965 |
| 23 | KITCHEN_ZN_1_FLR_1_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 2170.002 | 12.917 | 80.391 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2170.002 |
| 24 | CAFETERIA_ZN_1_FLR_1_LIGHTS | LTG_SCH_CAFETERIA | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 3051.566 | 9.688 | 9.000 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 3051.566 |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_LIGHTS | LTG_SCH_LIBRARY | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 6656.932 | 16.684 | 154.978 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 6656.932 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 768.000 | 4.000 | 74.318 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 149.700 | 729.600 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 768.000 | 4.000 | 74.318 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 149.700 | 729.600 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 768.000 | 4.000 | 74.318 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 149.700 | 729.600 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 4725.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 921.003 | 4488.750 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 3240.000 | 20.000 | 74.320 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 631.545 | 3078.000 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 2184.000 | 4.000 | 74.316 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 425.708 | 2074.800 |
| 18 | LOBBY_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 684.000 | 4.000 | 37.158 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 133.326 | 649.800 |
| 19 | MECH_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 2520.000 | 10.000 | 619.317 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 491.202 | 2394.000 |
| 20 | BATH_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 760.000 | 4.000 | 74.313 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 148.140 | 722.000 |
| 21 | OFFICES_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 4762.800 | 10.800 | 200.653 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 928.371 | 4524.660 |
| 22 | GYM_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 1785.000 | 5.000 | 15.480 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 347.935 | 1695.750 |
| 23 | KITCHEN_ZN_1_FLR_1_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 31995.600 | 190.450 | 1185.330 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 3199.560 | 7998.900 |
| 24 | KITCHEN_ZN_1_FLR_1_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 986.000 | 5.869 | 36.528 | 0.000 | 0.000 | 1.000 | 0.000 | ReachInFreezer | 986.000 | 986.000 |
| 25 | KITCHEN_ZN_1_FLR_1_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 730.000 | 4.345 | 27.044 | 0.000 | 0.000 | 1.000 | 0.000 | ReachInRefrigerator | 730.000 | 730.000 |
| 26 | CAFETERIA_ZN_1_FLR_1_PLUGMISC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 7997.850 | 25.390 | 23.587 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 799.785 | 1999.463 |
| 27 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 5985.000 | 15.000 | 139.335 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1166.604 | 5685.750 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | KITCHEN_ZN_1_FLR_1_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 240424.800 | 1431.100 | 8906.931 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 4808.496 | 48084.960 |
| Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
| 1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
| 2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 6 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 7 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 8 | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1980E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 9 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 10 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 11 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 12 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 13 | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1980E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 14 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 15 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 46 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 16 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 47 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 17 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 48 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 18 | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1980E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 19 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 20 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 21 | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR | 52 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 22 | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR | 53 | 2 | 7 | 0.167 | 0.2090E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 23 | LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR | 54 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 24 | MECH_ZN_1_FLR_1_FLOOR_FFACTOR | 55 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 25 | BATH_ZN_1_FLR_1_FLOOR_FFACTOR | 56 | 2 | 7 | 0.167 | 0.6720E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 26 | OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR | 57 | 2 | 7 | 0.167 | 0.1226 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 27 | GYM_ZN_1_FLR_1_FLOOR_FFACTOR | 58 | 2 | 7 | 0.167 | 0.6074E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 28 | KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR | 59 | 2 | 7 | 0.167 | 0.6074E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 29 | CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR | 60 | 2 | 7 | 0.167 | 0.1477 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 30 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR | 61 | 2 | 7 | 0.167 | 0.1292 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
| 1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
| 2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
| 3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
| 4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
| 5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
| 6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
| 7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
| 8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
| 9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
| 11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 50.42 |
| 17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 50.42 |
| 27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 32 | ~FC_Insulation_11 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 34 | ~FC_Insulation_12 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 36 | ~FC_Insulation_13 | 0.0000 | 0.000 | 0.000 | 0.000 | 50.42 |
| 37 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 38 | ~FC_Insulation_14 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 39 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 40 | ~FC_Insulation_15 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 41 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 42 | ~FC_Insulation_16 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 43 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 44 | ~FC_Insulation_17 | 0.0000 | 0.000 | 0.000 | 0.000 | 47.78 |
| 45 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 46 | ~FC_Insulation_18 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 47 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 48 | ~FC_Insulation_19 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
| 49 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 50 | ~FC_Insulation_20 | 0.0000 | 0.000 | 0.000 | 0.000 | 14.80 |
| 51 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 52 | ~FC_Insulation_21 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.077 |
| 53 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 54 | ~FC_Insulation_22 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.39 |
| 55 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 56 | ~FC_Insulation_23 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.39 |
| 57 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 58 | ~FC_Insulation_24 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.693 |
| 59 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 60 | ~FC_Insulation_25 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.662 |
| 61 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| Time | Outside | Cross | Inside | Flux (except final one) | |
| 1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
| 2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
| 3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
| 4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
| 5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
| 6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
| 7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
| 8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
| 9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
| 10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
| 11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
| 12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
| 13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
| 14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
| 15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
| 16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
| 17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
| 18 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
| 19 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
| 20 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
| 21 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
| 22 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
| 23 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
| 24 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
| 25 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
| 26 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
| 27 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
| 28 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
| 29 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
| 30 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 31 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 32 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 33 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 34 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 35 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 36 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 37 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 38 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 39 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 40 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 41 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 42 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 43 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 44 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 45 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 46 | 7 | -0.21707302E-07 | -0.21810081E-14 | -0.84952625E-14 | 0.13770899E-15 |
| 47 | 6 | 0.21407607E-05 | 0.45739277E-09 | 0.32038929E-02 | -0.26876939E-04 |
| 48 | 5 | -0.77205346E-04 | 0.24803070E-06 | -0.22452059 | 0.19631768E-02 |
| 49 | 4 | 0.12599243E-02 | 0.10780209E-04 | 4.8427850 | -0.45392265E-01 |
| 50 | 3 | -0.93942915E-02 | 0.82583168E-04 | -38.096111 | 0.39947953 |
| 51 | 2 | 0.30967349E-01 | 0.13253122E-03 | 116.62920 | -1.4198824 |
| 52 | 1 | -0.43132160E-01 | 0.38654114E-04 | -143.99276 | 2.0504445 |
| 53 | 0 | 0.20639933E-01 | 0.87079362E-06 | 60.838472 | |
| 54 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 55 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 56 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 57 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 58 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 59 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 60 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 61 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 62 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 63 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 64 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 65 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 66 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 67 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 68 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 69 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 70 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 71 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 72 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 73 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 74 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 75 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 76 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 77 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 78 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 79 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 80 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 81 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 82 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 83 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 84 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 85 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 86 | 7 | -0.21707302E-07 | -0.21810081E-14 | -0.84952625E-14 | 0.13770899E-15 |
| 87 | 6 | 0.21407607E-05 | 0.45739277E-09 | 0.32038929E-02 | -0.26876939E-04 |
| 88 | 5 | -0.77205346E-04 | 0.24803070E-06 | -0.22452059 | 0.19631768E-02 |
| 89 | 4 | 0.12599243E-02 | 0.10780209E-04 | 4.8427850 | -0.45392265E-01 |
| 90 | 3 | -0.93942915E-02 | 0.82583168E-04 | -38.096111 | 0.39947953 |
| 91 | 2 | 0.30967349E-01 | 0.13253122E-03 | 116.62920 | -1.4198824 |
| 92 | 1 | -0.43132160E-01 | 0.38654114E-04 | -143.99276 | 2.0504445 |
| 93 | 0 | 0.20639933E-01 | 0.87079362E-06 | 60.838472 | |
| 94 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 95 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 96 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 97 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 98 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 99 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 100 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 101 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 102 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 103 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 104 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 105 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 106 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 107 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 108 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 109 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 110 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 111 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 112 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 113 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 114 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 115 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 116 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 117 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 118 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 119 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 120 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 121 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 122 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 123 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 124 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 125 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 126 | 7 | -0.21707302E-07 | -0.21810081E-14 | -0.84952625E-14 | 0.13770899E-15 |
| 127 | 6 | 0.21407607E-05 | 0.45739277E-09 | 0.32038929E-02 | -0.26876939E-04 |
| 128 | 5 | -0.77205346E-04 | 0.24803070E-06 | -0.22452059 | 0.19631768E-02 |
| 129 | 4 | 0.12599243E-02 | 0.10780209E-04 | 4.8427850 | -0.45392265E-01 |
| 130 | 3 | -0.93942915E-02 | 0.82583168E-04 | -38.096111 | 0.39947953 |
| 131 | 2 | 0.30967349E-01 | 0.13253122E-03 | 116.62920 | -1.4198824 |
| 132 | 1 | -0.43132160E-01 | 0.38654114E-04 | -143.99276 | 2.0504445 |
| 133 | 0 | 0.20639933E-01 | 0.87079362E-06 | 60.838472 | |
| 134 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 135 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 136 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 137 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 138 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 139 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 140 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 141 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 142 | 7 | -0.29578731E-08 | -0.18610472E-14 | 0.16360026E-14 | -0.48190060E-16 |
| 143 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 144 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 145 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 146 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 147 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 148 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 149 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 150 | 7 | -0.29578731E-08 | -0.18610472E-14 | 0.16360026E-14 | -0.48190060E-16 |
| 151 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 152 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 153 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 154 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 155 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 156 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 157 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 158 | 7 | -0.20570949E-07 | -0.14658537E-14 | -0.76832012E-14 | 0.12671469E-15 |
| 159 | 6 | 0.20860838E-05 | 0.47270270E-09 | 0.32038024E-02 | -0.26876180E-04 |
| 160 | 5 | -0.77354338E-04 | 0.25871613E-06 | -0.22451551 | 0.19631320E-02 |
| 161 | 4 | 0.12908389E-02 | 0.11299182E-04 | 4.8427016 | -0.45391462E-01 |
| 162 | 3 | -0.97548753E-02 | 0.86890235E-04 | -38.095646 | 0.39947438 |
| 163 | 2 | 0.32375441E-01 | 0.13995703E-03 | 116.62830 | -1.4198704 |
| 164 | 1 | -0.45248243E-01 | 0.40996175E-04 | -143.99224 | 2.0504359 |
| 165 | 0 | 0.21692461E-01 | 0.93166815E-06 | 60.838472 | |
| 166 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 167 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 168 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 169 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 170 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 171 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 172 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 173 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 174 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
| 175 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
| 176 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
| 177 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
| 178 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
| 179 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
| 180 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
| 181 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
| 182 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 | |
| 183 | 7 | -0.63667935E-08 | -0.10874325E-13 | 0.11269204E-14 | -0.19557179E-16 |
| 184 | 6 | 0.22887183E-05 | 0.12967685E-08 | 0.32001644E-02 | -0.26845660E-04 |
| 185 | 5 | -0.14389595E-03 | 0.76205050E-06 | -0.22430950 | 0.19613133E-02 |
| 186 | 4 | 0.31719958E-02 | 0.34552480E-04 | 4.8392847 | -0.45358602E-01 |
| 187 | 3 | -0.27412176E-01 | 0.27382890E-03 | -38.076416 | 0.39926170 |
| 188 | 2 | 0.96706121E-01 | 0.45412367E-03 | 116.59097 | -1.4193709 |
| 189 | 1 | -0.13917125 | 0.13776341E-03 | -143.97030 | 2.0500753 |
| 190 | 0 | 0.67751290E-01 | 0.33403087E-05 | 60.838472 | |
| 191 | 7 | -0.34692083E-08 | -0.29835039E-14 | 0.22457095E-14 | -0.46878358E-16 |
| 192 | 6 | 0.35887165E-05 | 0.23456121E-08 | 0.31958645E-02 | -0.26809589E-04 |
| 193 | 5 | -0.24929292E-03 | 0.13860889E-05 | -0.22406525 | 0.19591573E-02 |
| 194 | 4 | 0.56768486E-02 | 0.63026314E-04 | 4.8352193 | -0.45319520E-01 |
| 195 | 3 | -0.49670058E-01 | 0.50068761E-03 | -38.053464 | 0.39900799 |
| 196 | 2 | 0.17611533 | 0.83223021E-03 | 116.54632 | -1.4187736 |
| 197 | 1 | -0.25403345 | 0.25321776E-03 | -143.94402 | 2.0496434 |
| 198 | 0 | 0.12381374 | 0.61501487E-05 | 60.838472 | |
| 199 | 7 | -0.70485818E-08 | -0.82048821E-14 | -0.11525862E-14 | 0.12346975E-16 |
| 200 | 6 | 0.21636134E-05 | 0.11761400E-08 | 0.32006654E-02 | -0.26849864E-04 |
| 201 | 5 | -0.13228193E-03 | 0.68999669E-06 | -0.22433795 | 0.19615643E-02 |
| 202 | 4 | 0.28871477E-02 | 0.31257738E-04 | 4.8397578 | -0.45363150E-01 |
| 203 | 3 | -0.24853202E-01 | 0.24753724E-03 | -38.079085 | 0.39929121 |
| 204 | 2 | 0.87536903E-01 | 0.41023195E-03 | 116.59616 | -1.4194403 |
| 205 | 1 | -0.12588244 | 0.12433901E-03 | -143.97335 | 2.0501255 |
| 206 | 0 | 0.61258788E-01 | 0.30111189E-05 | 60.838472 | |
| 207 | 7 | -0.70485818E-08 | -0.82048821E-14 | -0.11525862E-14 | 0.12346975E-16 |
| 208 | 6 | 0.21636134E-05 | 0.11761400E-08 | 0.32006654E-02 | -0.26849864E-04 |
| 209 | 5 | -0.13228193E-03 | 0.68999669E-06 | -0.22433795 | 0.19615643E-02 |
| 210 | 4 | 0.28871477E-02 | 0.31257738E-04 | 4.8397578 | -0.45363150E-01 |
| 211 | 3 | -0.24853202E-01 | 0.24753724E-03 | -38.079085 | 0.39929121 |
| 212 | 2 | 0.87536903E-01 | 0.41023195E-03 | 116.59616 | -1.4194403 |
| 213 | 1 | -0.12588244 | 0.12433901E-03 | -143.97335 | 2.0501255 |
| 214 | 0 | 0.61258788E-01 | 0.30111189E-05 | 60.838472 | |
| 215 | 7 | -0.28726507E-08 | -0.17143581E-14 | 0.24267693E-14 | -0.55541839E-16 |
| 216 | 6 | 0.42346750E-05 | 0.28245518E-08 | 0.31939123E-02 | -0.26793213E-04 |
| 217 | 5 | -0.29857172E-03 | 0.16707368E-05 | -0.22395432 | 0.19581782E-02 |
| 218 | 4 | 0.68293023E-02 | 0.76000496E-04 | 4.8333721 | -0.45301763E-01 |
| 219 | 3 | -0.59851213E-01 | 0.60399479E-03 | -38.043031 | 0.39889267 |
| 220 | 2 | 0.21235346 | 0.10042645E-02 | 116.52602 | -1.4185020 |
| 221 | 1 | -0.30639453 | 0.30573542E-03 | -143.93207 | 2.0494469 |
| 222 | 0 | 0.14935640 | 0.74123768E-05 | 60.838472 | |
| 223 | 7 | -0.32902409E-08 | -0.25529066E-14 | 0.11988885E-14 | -0.45014903E-16 |
| 224 | 6 | 0.37562854E-05 | 0.24712502E-08 | 0.31953527E-02 | -0.26805296E-04 |
| 225 | 5 | -0.26216584E-03 | 0.14606656E-05 | -0.22403617 | 0.19589006E-02 |
| 226 | 4 | 0.59784819E-02 | 0.66426580E-04 | 4.8347351 | -0.45314865E-01 |
| 227 | 3 | -0.52336689E-01 | 0.52775921E-03 | -38.050729 | 0.39897776 |
| 228 | 2 | 0.18560952 | 0.87732663E-03 | 116.54100 | -1.4187024 |
| 229 | 1 | -0.26775360 | 0.26697134E-03 | -143.94089 | 2.0495919 |
| 230 | 0 | 0.13050713 | 0.64865099E-05 | 60.838472 |
| Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
| 1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
| 2 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | 36 | 1 | VerySmooth | 3.922 | 3.922 | 1.000 | 0.493 |
| Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
| 1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
| 2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.36905 | 0.28585 | 0.28585 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 2.30798E-002 | 1.00000 | No |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Number of Refrigeration Compressor Racks | |
| 1 | 2 |
| Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
| 1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
| 2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | SWH BOOSTER G WATER HEATER | 2.2712E-002 | 6000.0 | 1.092 | 0.9931 |
| 2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 14.749 | 0.4701 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 2 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 3 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 4 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 5 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 6 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 7 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 8 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 9 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 10 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 11 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 12 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 13 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 14 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 15 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 16 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 17 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 18 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 19 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 20 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 21 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 22 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 23 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 24 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 25 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 26 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 27 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 28 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 29 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 3 | No | No |
| 30 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 2 | No | No |
| 31 | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 32 | CORRIDOR_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 33 | CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 34 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 35 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 36 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 37 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 38 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 39 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 40 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 41 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 42 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 43 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 44 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 45 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 46 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 47 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 48 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 49 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 50 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 51 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 52 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 53 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 54 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 55 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 56 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 57 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 58 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 59 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 60 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 61 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 62 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 63 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 64 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 65 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 66 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 67 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 68 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 69 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 70 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 71 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 72 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 73 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 74 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 75 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 76 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 77 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 78 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 79 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 80 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 81 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 82 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 83 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 84 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 85 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 3 | No | No |
| 86 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 2 | No | No |
| 87 | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 88 | CORRIDOR_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 89 | CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 90 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 91 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 92 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 93 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 94 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 95 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 96 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 97 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 98 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 99 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 100 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 101 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 102 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 103 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 104 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 105 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 106 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 107 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 108 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 109 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 110 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 111 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 112 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 113 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 114 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 115 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 116 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 117 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 118 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 119 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 120 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 121 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 122 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 123 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 124 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 125 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 126 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 127 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 128 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 129 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 130 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 131 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 132 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 133 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 134 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 135 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 136 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 137 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 138 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 139 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 140 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 141 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 142 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 3 | No | No |
| 143 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 2 | No | No |
| 144 | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 145 | CORRIDOR_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 146 | CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 147 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 148 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 149 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 150 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 151 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 152 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 153 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 154 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 155 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 156 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 157 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 158 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 159 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 160 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 3 | No | No |
| 161 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 2 | No | No |
| 162 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 2 | No | No |
| 163 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 2 | No | No |
| 164 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 165 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 166 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 167 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 168 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 169 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 170 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 171 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 172 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 3 | No | No |
| 173 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 2 | No | No |
| 174 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 2 | No | No |
| 175 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 176 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 177 | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 178 | COMPUTER_CLASS_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 179 | COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 180 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 181 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 182 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 183 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 184 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 185 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 186 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 3 | No | No |
| 187 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 2 | No | No |
| 188 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 2 | No | No |
| 189 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 190 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 191 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 192 | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 193 | MAIN_CORRIDOR_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 194 | MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 195 | LOBBY_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 3 | No | No |
| 196 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 2 | No | No |
| 197 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 2 | No | No |
| 198 | LOBBY_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 199 | LOBBY_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 200 | LOBBY_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 201 | LOBBY_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 202 | LOBBY_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 203 | LOBBY_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 204 | LOBBY_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 205 | LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 206 | MECH_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 207 | MECH_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 208 | MECH_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 209 | MECH_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 210 | MECH_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 211 | MECH_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 212 | MECH_ZN_1_FLR_1_WALL_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 213 | MECH_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 214 | MECH_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 215 | MECH_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 216 | BATH_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 217 | BATH_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 218 | BATH_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 219 | BATH_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 220 | BATH_ZN_1_FLR_1_WALL_5 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 3 | No | No |
| 221 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 2 | No | No |
| 222 | BATH_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 223 | BATH_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 224 | BATH_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 225 | OFFICES_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 3 | No | No |
| 226 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 2 | No | No |
| 227 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 2 | No | No |
| 228 | OFFICES_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 229 | OFFICES_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 3 | No | No |
| 230 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 2 | No | No |
| 231 | OFFICES_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 232 | OFFICES_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 233 | OFFICES_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 234 | OFFICES_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 235 | OFFICES_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 236 | OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 237 | GYM_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 238 | GYM_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 3 | No | No |
| 239 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 240 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 241 | GYM_ZN_1_FLR_1_WALL_2_DOOR | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 242 | GYM_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 243 | GYM_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 244 | GYM_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 245 | GYM_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 246 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 247 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 248 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 249 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 250 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 251 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 252 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 253 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 254 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 255 | GYM_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 256 | KITCHEN_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 257 | KITCHEN_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 3 | No | No |
| 258 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 2 | No | No |
| 259 | KITCHEN_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 260 | KITCHEN_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 261 | KITCHEN_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 262 | KITCHEN_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 263 | KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 264 | CAFETERIA_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 265 | CAFETERIA_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 3 | No | No |
| 266 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 2 | No | No |
| 267 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 2 | No | No |
| 268 | CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 269 | CAFETERIA_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 3 | No | No |
| 270 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 2 | No | No |
| 271 | CAFETERIA_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 272 | CAFETERIA_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 273 | CAFETERIA_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 274 | CAFETERIA_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 275 | CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 276 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 277 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 3 | No | No |
| 278 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 2 | No | No |
| 279 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 2 | No | No |
| 280 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 281 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 3 | No | No |
| 282 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 2 | No | No |
| 283 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 284 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 285 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 286 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 287 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 288 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
| 1 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.786 | 0.497 | 0.492 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 6.835E-003 | 3.560E-005 | 3.350E-005 | 3.204E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 6.835E-003 | 3.560E-005 | 3.350E-005 | 3.204E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 6.835E-003 | 3.560E-005 | 3.350E-005 | 3.204E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 7.974E-002 | 2.531E-004 | 1.738E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 4.101E-002 | 2.531E-004 | 1.738E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 2.050E-002 | 3.755E-005 | 3.511E-005 | 3.380E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | LOBBY_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 4.329E-002 | 2.531E-004 | 1.739E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | LOBBY_ZN_1_FLR_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 3.031 | 1.773E-002 | 1.218E-002 | 15.954 | 1.000 | 0.000 | 0.000 | 0.000 |
| 20 | MECH_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | BATH_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 2.278E-002 | 1.199E-004 | 9.906E-005 | 0.108 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | OFFICES_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 9.569E-002 | 2.170E-004 | 1.566E-004 | 0.195 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | GYM_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 3.873E-002 | 1.085E-004 | 9.072E-005 | 9.764E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | KITCHEN_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 1.823E-002 | 1.085E-004 | 9.113E-005 | 9.764E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | CAFETERIA_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 8.202E-002 | 2.604E-004 | 1.779E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 9.113E-002 | 2.284E-004 | 1.625E-004 | 0.206 | 0.000 | 0.000 | 0.224 | 0.000 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 18 | LOBBY_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 19 | MECH_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 20 | BATH_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 21 | OFFICES_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 22 | GYM_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 23 | KITCHEN_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 24 | CAFETERIA_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2500 |
| 2 | Zone CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1.2500 |
| 3 | Zone MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.2500 |
| 4 | Zone CORRIDOR_POD_1_ZN_1_FLR_1 | 1.2500 |
| 5 | Zone CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1.2500 |
| 6 | Zone MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.2500 |
| 7 | Zone CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1.2500 |
| 8 | Zone MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.2500 |
| 9 | Zone CORRIDOR_POD_2_ZN_1_FLR_1 | 1.2500 |
| 10 | Zone CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1.2500 |
| 11 | Zone MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.2500 |
| 12 | Zone CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1.2500 |
| 13 | Zone MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.2500 |
| 14 | Zone CORRIDOR_POD_3_ZN_1_FLR_1 | 1.2500 |
| 15 | Zone CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1.2500 |
| 16 | Zone MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1.2500 |
| 17 | Zone COMPUTER_CLASS_ZN_1_FLR_1 | 1.2500 |
| 18 | Zone MAIN_CORRIDOR_ZN_1_FLR_1 | 1.2500 |
| 19 | Zone LOBBY_ZN_1_FLR_1 | 1.2500 |
| 20 | Zone MECH_ZN_1_FLR_1 | 1.2500 |
| 21 | Zone BATH_ZN_1_FLR_1 | 1.2500 |
| 22 | Zone OFFICES_ZN_1_FLR_1 | 1.2500 |
| 23 | Zone GYM_ZN_1_FLR_1 | 1.2500 |
| 24 | Zone KITCHEN_ZN_1_FLR_1 | 1.2500 |
| 25 | Zone CAFETERIA_ZN_1_FLR_1 | 1.2500 |
| 26 | Zone LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 1.2500 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.1500 |
| 2 | Zone CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1.1500 |
| 3 | Zone MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.1500 |
| 4 | Zone CORRIDOR_POD_1_ZN_1_FLR_1 | 1.1500 |
| 5 | Zone CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1.1500 |
| 6 | Zone MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.1500 |
| 7 | Zone CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1.1500 |
| 8 | Zone MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.1500 |
| 9 | Zone CORRIDOR_POD_2_ZN_1_FLR_1 | 1.1500 |
| 10 | Zone CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1.1500 |
| 11 | Zone MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.1500 |
| 12 | Zone CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1.1500 |
| 13 | Zone MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.1500 |
| 14 | Zone CORRIDOR_POD_3_ZN_1_FLR_1 | 1.1500 |
| 15 | Zone CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1.1500 |
| 16 | Zone MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1.1500 |
| 17 | Zone COMPUTER_CLASS_ZN_1_FLR_1 | 1.1500 |
| 18 | Zone MAIN_CORRIDOR_ZN_1_FLR_1 | 1.1500 |
| 19 | Zone LOBBY_ZN_1_FLR_1 | 1.1500 |
| 20 | Zone MECH_ZN_1_FLR_1 | 1.1500 |
| 21 | Zone BATH_ZN_1_FLR_1 | 1.1500 |
| 22 | Zone OFFICES_ZN_1_FLR_1 | 1.1500 |
| 23 | Zone GYM_ZN_1_FLR_1 | 1.1500 |
| 24 | Zone KITCHEN_ZN_1_FLR_1 | 1.1500 |
| 25 | Zone CAFETERIA_ZN_1_FLR_1 | 1.1500 |
| 26 | Zone LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 1.1500 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | Cooling | 7364.45499 | 8469.12323 | 0.54528 | 0.62707 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 26.03600 | 8.40651E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 2 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | Heating | 2775.72782 | 3469.65977 | 0.20563 | 0.25704 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 3 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | Cooling | 31521.86143 | 36250.14064 | 2.33401 | 2.68411 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 26.40000 | 8.40708E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 4 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | Heating | 8837.57006 | 11046.96258 | 0.65471 | 0.89657 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 5 | CORRIDOR_POD_1_ZN_1_FLR_1 | Cooling | 5925.46662 | 6814.28661 | 0.43861 | 0.50440 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 26.12700 | 8.40665E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 6 | CORRIDOR_POD_1_ZN_1_FLR_1 | Heating | 2813.94313 | 3517.42891 | 0.20846 | 0.26058 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 7 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | Cooling | 6202.50723 | 7132.88331 | 0.45925 | 0.52814 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 25.24733 | 8.40527E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 8 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | Heating | 2743.08122 | 3428.85152 | 0.20321 | 0.25402 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 9 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | Cooling | 24867.48794 | 28597.61113 | 1.84132 | 2.11751 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.40000 | 8.40708E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 10 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | Heating | 8635.92638 | 10794.90797 | 0.63977 | 0.89657 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 11 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | Cooling | 7320.65794 | 8418.75664 | 0.54204 | 0.62335 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 26.03600 | 8.40651E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 12 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | Heating | 2756.01042 | 3445.01303 | 0.20417 | 0.25521 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 13 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | Cooling | 31175.55260 | 35851.88549 | 2.30837 | 2.65462 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 26.40000 | 8.40708E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 14 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | Heating | 8683.55902 | 10854.44878 | 0.64330 | 0.89657 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 15 | CORRIDOR_POD_2_ZN_1_FLR_1 | Cooling | 5906.69756 | 6792.70219 | 0.43722 | 0.50280 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 26.12700 | 8.40665E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 16 | CORRIDOR_POD_2_ZN_1_FLR_1 | Heating | 2807.17460 | 3508.96825 | 0.20796 | 0.25995 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 17 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | Cooling | 6205.10459 | 7135.87028 | 0.45945 | 0.52836 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 25.24733 | 8.40527E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 18 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | Heating | 2744.86266 | 3431.07833 | 0.20334 | 0.25418 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 19 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | Cooling | 24877.79350 | 28609.46252 | 1.84208 | 2.11839 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.40000 | 8.40708E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 20 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | Heating | 8643.26629 | 10804.08287 | 0.64031 | 0.89657 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 21 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | Cooling | 7326.02365 | 8424.92720 | 0.54244 | 0.62380 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 26.03600 | 8.40651E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 22 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | Heating | 2758.02971 | 3447.53714 | 0.20432 | 0.25540 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 23 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | Cooling | 31300.26882 | 35995.30915 | 2.31760 | 2.66524 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 26.40000 | 8.40708E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 24 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | Heating | 8718.08344 | 10897.60429 | 0.64586 | 0.89657 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 25 | CORRIDOR_POD_3_ZN_1_FLR_1 | Cooling | 5962.39657 | 6856.75605 | 0.44134 | 0.50754 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 26.12700 | 8.40665E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 26 | CORRIDOR_POD_3_ZN_1_FLR_1 | Heating | 2809.94152 | 3512.42690 | 0.20817 | 0.26021 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 27 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | Cooling | 6244.56754 | 7181.25267 | 0.46237 | 0.53172 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 25.36867 | 8.40546E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 28 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | Heating | 2762.83221 | 3453.54026 | 0.20468 | 0.25585 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 29 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | Cooling | 16678.21801 | 19179.95071 | 1.23494 | 1.42018 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.40000 | 8.40708E-003 | 315.00000 | 84.76857 | 0.59207 | 0.00000 |
| 30 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | Heating | 5879.41282 | 7349.26603 | 0.43556 | 0.59207 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 315.00000 | 84.76857 | 0.59207 | 0.00000 |
| 31 | COMPUTER_CLASS_ZN_1_FLR_1 | Cooling | 9278.12659 | 10669.84558 | 0.68699 | 0.79004 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.40000 | 8.40708E-003 | 162.00000 | 43.59526 | 0.30449 | 0.00000 |
| 32 | COMPUTER_CLASS_ZN_1_FLR_1 | Heating | 2765.62845 | 3457.03557 | 0.20488 | 0.30449 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 162.00000 | 43.59526 | 0.30449 | 0.00000 |
| 33 | MAIN_CORRIDOR_ZN_1_FLR_1 | Cooling | 12417.43231 | 14280.04716 | 0.91916 | 1.05704 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 26.12700 | 8.40665E-003 | 546.00000 | 29.38800 | 0.16642 | 0.00000 |
| 34 | MAIN_CORRIDOR_ZN_1_FLR_1 | Heating | 6593.10719 | 8241.38399 | 0.48844 | 0.61055 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 546.00000 | 29.38800 | 0.16642 | 0.00000 |
| 35 | LOBBY_ZN_1_FLR_1 | Cooling | 7947.73497 | 9139.89521 | 0.58835 | 0.67660 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 26.40000 | 8.40708E-003 | 171.00000 | 18.40800 | 9.55546E-002 | 0.00000 |
| 36 | LOBBY_ZN_1_FLR_1 | Heating | 3781.58944 | 4726.98680 | 0.28015 | 0.35019 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 171.00000 | 18.40800 | 9.55546E-002 | 0.00000 |
| 37 | MECH_ZN_1_FLR_1 | Cooling | 9102.86806 | 10468.29827 | 0.67377 | 0.77483 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 26.40000 | 8.40708E-003 | 252.00000 | 4.06900 | 0.00000 | 0.00000 |
| 38 | MECH_ZN_1_FLR_1 | Heating | 1739.98916 | 2174.98645 | 0.12890 | 0.16113 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:40:00 | -4.30000 | 2.65759E-003 | 252.00000 | 4.06900 | 0.00000 | 0.00000 |
| 39 | BATH_ZN_1_FLR_1 | Cooling | 5779.09902 | 6645.96388 | 0.42778 | 0.49194 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 25.49000 | 8.40565E-003 | 190.00000 | 10.22700 | 0.00000 | 0.00000 |
| 40 | BATH_ZN_1_FLR_1 | Heating | 2969.99004 | 3712.48756 | 0.22002 | 0.27503 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 190.00000 | 10.22700 | 0.00000 | 0.00000 |
| 41 | OFFICES_ZN_1_FLR_1 | Cooling | 18358.29347 | 21112.03750 | 1.35891 | 1.56274 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40000 | 8.40708E-003 | 441.00000 | 23.73648 | 0.19042 | 0.00000 |
| 42 | OFFICES_ZN_1_FLR_1 | Heating | 8024.08448 | 10030.10560 | 0.59444 | 0.74305 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 441.00000 | 23.73648 | 0.19042 | 0.00000 |
| 43 | GYM_ZN_1_FLR_1 | Cooling | 20217.41073 | 23250.02234 | 1.49712 | 1.72168 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 357.00000 | 115.31008 | 0.54407 | 0.00000 |
| 44 | GYM_ZN_1_FLR_1 | Heating | 5841.40121 | 7301.75152 | 0.43275 | 0.54407 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | -4.30000 | 2.65759E-003 | 357.00000 | 115.31008 | 0.54407 | 0.00000 |
| 45 | KITCHEN_ZN_1_FLR_1 | Cooling | 17826.02032 | 20499.92336 | 1.32120 | 1.51937 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 25.58100 | 8.40579E-003 | 168.00000 | 26.99300 | 0.25481 | 0.00000 |
| 46 | KITCHEN_ZN_1_FLR_1 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.25481 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -4.30000 | 2.65759E-003 | 168.00000 | 26.99300 | 0.25481 | 0.00000 |
| 47 | CAFETERIA_ZN_1_FLR_1 | Cooling | 30015.00714 | 34517.25821 | 2.22503 | 2.55879 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 25.94500 | 8.40636E-003 | 315.00000 | 339.07427 | 1.48818 | 0.00000 |
| 48 | CAFETERIA_ZN_1_FLR_1 | Heating | 6115.00810 | 7643.76012 | 0.45301 | 1.48818 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | -4.30000 | 2.65759E-003 | 315.00000 | 339.07427 | 1.48818 | 0.00000 |
| 49 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | Cooling | 18903.95802 | 21739.55172 | 1.39941 | 1.60932 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 26.40000 | 8.40708E-003 | 399.00000 | 42.95403 | 0.34458 | 0.00000 |
| 50 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | Heating | 6924.81789 | 8656.02236 | 0.51301 | 0.64126 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -4.30000 | 2.65759E-003 | 399.00000 | 42.95403 | 0.34458 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | VAV_POD_1 | Cooling | Sensible | 391058.57 | 27.09652 | 27.09652 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
| 2 | VAV_POD_1 | Heating | Sensible | 216644.18 | 11.01695 | 11.01695 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 |
| 3 | PSZ-AC_1:6 | Cooling | Sensible | 20612.96 | 1.51937 | 1.51937 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 4 | PSZ-AC_1:6 | Heating | Sensible | 11106.98 | 0.25481 | 0.25481 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 5 | PSZ-AC_2:7 | Cooling | Sensible | 37772.97 | 2.55879 | 2.55879 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 6 | PSZ-AC_2:7 | Heating | Sensible | 64867.89 | 1.48818 | 1.48818 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 01:30:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62707 |
| 2 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12030 |
| 3 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42700 |
| 4 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26776 |
| 5 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42700 |
| 6 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 7 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.16704E-003 |
| 8 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.34325E-005 |
| 9 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26776 |
| 10 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 11 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 12 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6107.66252 |
| 13 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.34325E-005 |
| 14 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 141.55756 |
| 15 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.68411 |
| 16 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13542 |
| 17 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48000 |
| 18 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28837 |
| 19 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48000 |
| 20 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 21 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.81353E-003 |
| 22 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.07692E-004 |
| 23 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28837 |
| 24 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 25 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 26 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23740.51884 |
| 27 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.07692E-004 |
| 28 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 523.57715 |
| 29 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.50440 |
| 30 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29006 |
| 31 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 32 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15132 |
| 33 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77348 |
| 34 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 35 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.31354E-003 |
| 36 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.32350E-005 |
| 37 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26058 |
| 38 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 39 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 40 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6085.08307 |
| 41 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.32350E-005 |
| 42 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 141.93529 |
| 43 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.52814 |
| 44 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14284 |
| 45 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
| 46 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26724 |
| 47 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50600 |
| 48 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 49 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.66738E-003 |
| 50 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.30305E-005 |
| 51 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26724 |
| 52 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 53 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 54 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6061.71258 |
| 55 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.30305E-005 |
| 56 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 140.28333 |
| 57 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.11751 |
| 58 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17165 |
| 59 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.60900 |
| 60 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28957 |
| 61 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60900 |
| 62 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 63 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.21961E-003 |
| 64 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.05590E-004 |
| 65 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28957 |
| 66 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 67 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 68 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23500.18522 |
| 69 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.05590E-004 |
| 70 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 517.11946 |
| 71 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62335 |
| 72 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12102 |
| 73 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42900 |
| 74 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26742 |
| 75 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42900 |
| 76 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 77 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.14821E-003 |
| 78 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.31871E-005 |
| 79 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26742 |
| 80 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 81 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 82 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6079.60766 |
| 83 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.31871E-005 |
| 84 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 140.78303 |
| 85 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.65462 |
| 86 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13692 |
| 87 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48500 |
| 88 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28749 |
| 89 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48500 |
| 90 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 91 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.78262E-003 |
| 92 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.05932E-004 |
| 93 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28749 |
| 94 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 95 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 96 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23539.30067 |
| 97 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.05932E-004 |
| 98 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 518.32002 |
| 99 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.50280 |
| 100 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29098 |
| 101 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 102 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15084 |
| 103 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.77594 |
| 104 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 105 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.30938E-003 |
| 106 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.31069E-005 |
| 107 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.25995 |
| 108 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 109 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 110 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6070.44616 |
| 111 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.31069E-005 |
| 112 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 141.59389 |
| 113 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.52836 |
| 114 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14278 |
| 115 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50600 |
| 116 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26735 |
| 117 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50600 |
| 118 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 119 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.66850E-003 |
| 120 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.30596E-005 |
| 121 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26735 |
| 122 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 123 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 124 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6065.04212 |
| 125 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.30596E-005 |
| 126 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 140.36524 |
| 127 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.11839 |
| 128 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17158 |
| 129 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.60800 |
| 130 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28798 |
| 131 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60800 |
| 132 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 133 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.22053E-003 |
| 134 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.05534E-004 |
| 135 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28798 |
| 136 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 137 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 138 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23493.75541 |
| 139 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.05534E-004 |
| 140 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 517.07682 |
| 141 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62380 |
| 142 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12093 |
| 143 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.42900 |
| 144 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26761 |
| 145 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42900 |
| 146 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 147 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.15052E-003 |
| 148 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.32260E-005 |
| 149 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26761 |
| 150 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 151 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 152 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6084.06300 |
| 153 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.32260E-005 |
| 154 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 140.88620 |
| 155 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.66524 |
| 156 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13638 |
| 157 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48400 |
| 158 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.28998 |
| 159 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48400 |
| 160 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 161 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.79375E-003 |
| 162 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.06524E-004 |
| 163 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.28998 |
| 164 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 165 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 166 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23606.94539 |
| 167 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.06524E-004 |
| 168 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 519.90784 |
| 169 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.50754 |
| 170 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28826 |
| 171 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 172 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15226 |
| 173 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.76869 |
| 174 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 175 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.32173E-003 |
| 176 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.31593E-005 |
| 177 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26021 |
| 178 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 179 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 180 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6076.42960 |
| 181 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.31593E-005 |
| 182 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 141.73345 |
| 183 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.53172 |
| 184 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14187 |
| 185 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.50300 |
| 186 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26746 |
| 187 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50300 |
| 188 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 189 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.68547E-003 |
| 190 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.32652E-005 |
| 191 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26746 |
| 192 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 193 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 194 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6088.54393 |
| 195 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.32652E-005 |
| 196 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 141.03927 |
| 197 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.42018 |
| 198 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16901 |
| 199 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59900 |
| 200 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.85069 |
| 201 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59900 |
| 202 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 203 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.25425E-003 |
| 204 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.37618E-004 |
| 205 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.85069 |
| 206 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 207 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 208 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15730.57700 |
| 209 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.37618E-004 |
| 210 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 347.17250 |
| 211 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79004 |
| 212 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15625 |
| 213 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.55400 |
| 214 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.43768 |
| 215 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.55400 |
| 216 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 217 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.43840E-003 |
| 218 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.79685E-005 |
| 219 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.43768 |
| 220 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 221 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 222 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7769.21332 |
| 223 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.79685E-005 |
| 224 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 170.07945 |
| 225 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.05704 |
| 226 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.39360 |
| 227 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 228 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.31711 |
| 229 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
| 230 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 231 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.67982E-004 |
| 232 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.24730E-004 |
| 233 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.61055 |
| 234 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 235 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 236 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14257.38985 |
| 237 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.24730E-004 |
| 238 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 332.55507 |
| 239 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67660 |
| 240 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19258 |
| 241 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 242 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.20298 |
| 243 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51356 |
| 244 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 245 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.97836E-003 |
| 246 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.15381E-005 |
| 247 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.35019 |
| 248 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 249 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 250 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8177.24180 |
| 251 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.15381E-005 |
| 252 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 190.73321 |
| 253 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.77483 |
| 254 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24783 |
| 255 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 256 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23245 |
| 257 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.66087 |
| 258 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 259 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.53737E-003 |
| 260 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.90662E-005 |
| 261 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23245 |
| 262 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 263 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 264 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4465.51015 |
| 265 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.90662E-005 |
| 266 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 99.34099 |
| 267 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.49194 |
| 268 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29430 |
| 269 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 270 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.14758 |
| 271 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78480 |
| 272 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 273 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.29459E-003 |
| 274 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.61857E-005 |
| 275 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.27503 |
| 276 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 277 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 278 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6422.37499 |
| 279 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.61857E-005 |
| 280 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 149.80177 |
| 281 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.56274 |
| 282 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.57342 |
| 283 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 284 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.77182E-003 |
| 285 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.51795E-004 |
| 286 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.74305 |
| 287 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 288 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 289 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17351.11535 |
| 290 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.51795E-004 |
| 291 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 404.71250 |
| 292 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.72168 |
| 293 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15800 |
| 294 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45400 |
| 295 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.78164 |
| 296 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45400 |
| 297 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 298 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.41132E-003 |
| 299 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.31256E-004 |
| 300 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78164 |
| 301 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 302 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 303 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15003.37351 |
| 304 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31256E-004 |
| 305 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 333.70995 |
| 306 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN_ZN_1_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.51937 |
| 307 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CAFETERIA_ZN_1_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.55879 |
| 308 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.60932 |
| 309 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18892 |
| 310 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30800 |
| 311 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.49567 |
| 312 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.50379 |
| 313 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 314 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.01669E-003 |
| 315 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.30999E-004 |
| 316 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.64126 |
| 317 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 318 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 319 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14974.00293 |
| 320 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30999E-004 |
| 321 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 349.26618 |
| 322 | AirLoopHVAC | VAV_POD_1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 14.31151 |
| 323 | AirLoopHVAC | VAV_POD_1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 12.43727 |
| 324 | AirLoopHVAC | VAV_POD_1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 27.32145 |
| 325 | AirLoopHVAC | VAV_POD_1 | Adjusted Heating Design Air Flow Rate [m3/s] | 12.43727 |
| 326 | AirLoopHVAC | VAV_POD_1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 27.09652 |
| 327 | AirLoopHVAC | VAV_POD_1 | Adjusted Main Design Air Flow Rate [m3/s] | 27.09652 |
| 328 | AirLoopHVAC | VAV_POD_1 | User Heating Air Flow Ratio [] | 0.30000 |
| 329 | AirLoopHVAC | VAV_POD_1 | Calculated Heating Air Flow Ratio [] | 0.45900 |
| 330 | AirLoopHVAC | PSZ-AC_1:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.51937 |
| 331 | AirLoopHVAC | PSZ-AC_1:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.51937 |
| 332 | AirLoopHVAC | PSZ-AC_1:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.51937 |
| 333 | AirLoopHVAC | PSZ-AC_1:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.51937 |
| 334 | AirLoopHVAC | PSZ-AC_1:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.51937 |
| 335 | AirLoopHVAC | PSZ-AC_1:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.51937 |
| 336 | AirLoopHVAC | PSZ-AC_1:6 | User Heating Air Flow Ratio [] | 1.00000 |
| 337 | AirLoopHVAC | PSZ-AC_1:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 338 | AirLoopHVAC | PSZ-AC_2:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.55879 |
| 339 | AirLoopHVAC | PSZ-AC_2:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.55879 |
| 340 | AirLoopHVAC | PSZ-AC_2:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.55879 |
| 341 | AirLoopHVAC | PSZ-AC_2:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.55879 |
| 342 | AirLoopHVAC | PSZ-AC_2:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.55879 |
| 343 | AirLoopHVAC | PSZ-AC_2:7 | Adjusted Main Design Air Flow Rate [m3/s] | 2.55879 |
| 344 | AirLoopHVAC | PSZ-AC_2:7 | User Heating Air Flow Ratio [] | 1.00000 |
| 345 | AirLoopHVAC | PSZ-AC_2:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 346 | AirLoopHVAC | VAV_POD_1 | Design Supply Air Flow Rate [m3/s] | 27.09652 |
| 347 | AirLoopHVAC | PSZ-AC_1:6 | Design Supply Air Flow Rate [m3/s] | 1.51937 |
| 348 | AirLoopHVAC | PSZ-AC_2:7 | Design Supply Air Flow Rate [m3/s] | 2.55879 |
| 349 | Controller:OutdoorAir | VAV_POD_1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 27.09652 |
| 350 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 27.09652 |
| 351 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 488636.69219 |
| 352 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80049 |
| 353 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 9.03127 |
| 354 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 162862.60951 |
| 355 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80049 |
| 356 | Coil:Heating:Fuel | VAV_POD_1 HEATING COIL | Design Size Nominal Capacity [W] | 167276.58376 |
| 357 | Fan:VariableVolume | VAV_POD_1 FAN | Design Size Maximum Flow Rate [m3/s] | 27.09652 |
| 358 | Controller:OutdoorAir | PSZ-AC_1:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.51937 |
| 359 | Controller:OutdoorAir | PSZ-AC_1:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.25481 |
| 360 | Fan:SystemModel | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.51937 |
| 361 | Fan:SystemModel | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2525.19634 |
| 362 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.51937 |
| 363 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.51937 |
| 364 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.51937 |
| 365 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.51937 |
| 366 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.51937 |
| 367 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.75969 |
| 368 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.01291 |
| 369 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 29570.63000 |
| 370 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 14785.31500 |
| 371 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78671 |
| 372 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78671 |
| 373 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 29570.63000 |
| 374 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 59717.72709 |
| 375 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
| 376 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 377 | Coil:Heating:Fuel | PSZ-AC_1:6 HEATING COIL | Design Size Nominal Capacity [W] | 59717.72709 |
| 378 | Controller:OutdoorAir | PSZ-AC_2:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.55879 |
| 379 | Controller:OutdoorAir | PSZ-AC_2:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.48818 |
| 380 | Fan:SystemModel | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.55879 |
| 381 | Fan:SystemModel | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 4150.66801 |
| 382 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.55879 |
| 383 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.55879 |
| 384 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.55879 |
| 385 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.55879 |
| 386 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.55879 |
| 387 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.27939 |
| 388 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.70586 |
| 389 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 47977.82000 |
| 390 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 23988.91000 |
| 391 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80058 |
| 392 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80058 |
| 393 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 47977.82000 |
| 394 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 79107.52245 |
| 395 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
| 396 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 397 | Coil:Heating:Fuel | PSZ-AC_2:7 HEATING COIL | Design Size Nominal Capacity [W] | 79107.52245 |
| 398 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.42113E-003 |
| 399 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.29054 |
| 400 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.42113E-003 |
| 401 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 729.13820 |
| 402 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
| 403 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 276750.09509 |
| 404 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 276750.10000 |
| 405 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.42113E-003 |
| 406 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.05414E-004 |
| 407 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.26497E-002 |
| 408 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.05414E-004 |
| 409 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 13.46550 |
| 410 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.05414E-004 |
| Component Type | Name | Nominal Total Capacity {W} | |
| 1 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5794.35 |
| 2 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 22529.01 |
| 3 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5772.76 |
| 4 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5750.79 |
| 5 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 22301.17 |
| 6 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5767.75 |
| 7 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 22338.22 |
| 8 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5758.87 |
| 9 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5753.95 |
| 10 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 22295.05 |
| 11 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5771.98 |
| 12 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 22402.40 |
| 13 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5764.55 |
| 14 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5776.22 |
| 15 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 14927.78 |
| 16 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | 7372.99 |
| 17 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | 13525.61 |
| 18 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | 7757.53 |
| 19 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 4237.47 |
| 20 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6092.74 |
| 21 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | 16460.54 |
| 22 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | 14237.19 |
| 23 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | 14205.44 |
| DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
| 1 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | N/A | N/A | 468510.46 | 1598624.04 | 10.80 | 3.01 | 3.15 | 3.14 | 3.31 | 10.27 | 10.76 | 10.70 | 11.30 | 31.0071 | 24.6071 | 16.5067 | 6.6200 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | 28377.1 | 10.72 | 10.72 | |||
| 2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | 45968.9 | 10.40 | 10.40 |
| Zone Name | # Surfaces | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 11 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 12 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | 10 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 11 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 12 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 11 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 12 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | 10 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 11 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 12 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 11 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 12 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | 11 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 11 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 12 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | 10 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | 15 |
| 18 | LOBBY_ZN_1_FLR_1 | 11 |
| 19 | MECH_ZN_1_FLR_1 | 10 |
| 20 | BATH_ZN_1_FLR_1 | 9 |
| 21 | OFFICES_ZN_1_FLR_1 | 12 |
| 22 | GYM_ZN_1_FLR_1 | 19 |
| 23 | KITCHEN_ZN_1_FLR_1 | 8 |
| 24 | CAFETERIA_ZN_1_FLR_1 | 12 |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 32.37 | 44.00 | 32.37 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 180.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 180.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 4 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | Door | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 5 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 8 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 9 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 10 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 11 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 12 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 161.46 | 212.00 | 161.46 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 15 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | Window | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 16 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | Door | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 17 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | Door | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 18 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 19 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 21 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 22 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 23 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 24 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 26 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 90.00 | 90.00 | 3.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 27 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 28 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 9.36 | 12.00 | 9.36 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 30 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | Window | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.64 | 2.64 | 2.64 | 270.00 | 90.00 | 2.90 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 31 | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.980E-002 | 1.971E-002 | 192.00 | 192.00 | 192.00 | 270.00 | 180.00 | 3.00 | 64.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 32 | CORRIDOR_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 192.00 | 192.00 | 192.00 | 90.00 | 0.00 | 3.00 | 64.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 33 | CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 384.00 | 384.00 | 384.00 | 0.00 | 90.00 | 384.00 | 1.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 34 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 35 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 36 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 32.37 | 44.00 | 32.37 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 | ||
| 37 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 0.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 38 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 0.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 |
| 39 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | Door | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | |
| 40 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 42 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 47 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 161.46 | 212.00 | 161.46 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 | ||
| 48 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 49 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 50 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | Window | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 51 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | Door | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 | |
| 52 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | Door | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 53 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 55 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 56 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 57 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 32.37 | 44.00 | 32.37 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 | ||
| 58 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 180.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 |
| 59 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 180.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.61 | 0.39 | 4 |
| 60 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | Door | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 | |
| 61 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 63 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 65 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 66 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 67 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 68 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 161.46 | 212.00 | 161.46 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 | ||
| 69 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 70 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 71 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | Window | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 72 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | Door | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 73 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | Door | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 | |
| 74 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 76 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 77 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 78 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 79 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 80 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 82 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 90.00 | 90.00 | 3.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 85 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 9.36 | 12.00 | 9.36 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 86 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | Window | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.64 | 2.64 | 2.64 | 270.00 | 90.00 | 2.90 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 87 | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.980E-002 | 1.971E-002 | 192.00 | 192.00 | 192.00 | 270.00 | 180.00 | 3.00 | 64.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 88 | CORRIDOR_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 192.00 | 192.00 | 192.00 | 90.00 | 0.00 | 3.00 | 64.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 89 | CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 384.00 | 384.00 | 384.00 | 0.00 | 90.00 | 384.00 | 1.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 90 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 91 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 32.37 | 44.00 | 32.37 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.56 | 0.44 | 4 | ||
| 93 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 0.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 94 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 0.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 |
| 95 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | Door | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 | |
| 96 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 99 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 100 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 101 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 103 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 161.46 | 212.00 | 161.46 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 | ||
| 104 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 |
| 105 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 106 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | Window | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 107 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | Door | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 108 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | Door | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | |
| 109 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 32.37 | 44.00 | 32.37 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.56 | 0.44 | 4 | ||
| 114 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 180.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 |
| 115 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 180.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 |
| 116 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | Door | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.58 | 0.42 | 4 | |
| 117 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 119 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 120 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 121 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 122 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 123 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 124 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 161.46 | 212.00 | 161.46 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 | ||
| 125 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 126 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 127 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | Window | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 |
| 128 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | Door | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | |
| 129 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | Door | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 130 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 131 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 134 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 135 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 136 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 137 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 90.00 | 90.00 | 3.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 139 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 72.00 | 72.00 | 72.00 | 0.00 | 90.00 | 18.00 | 4.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 140.00 | 140.00 | 140.00 | 0.00 | 90.00 | 35.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 141 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 9.36 | 12.00 | 9.36 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | Window | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.64 | 2.64 | 2.64 | 270.00 | 90.00 | 2.90 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 144 | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.980E-002 | 1.971E-002 | 192.00 | 192.00 | 192.00 | 270.00 | 180.00 | 3.00 | 64.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 145 | CORRIDOR_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 192.00 | 192.00 | 192.00 | 90.00 | 0.00 | 3.00 | 64.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 146 | CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 384.00 | 384.00 | 384.00 | 0.00 | 90.00 | 384.00 | 1.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 147 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 148 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 32.40 | 44.00 | 32.40 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 150 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 0.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 151 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.43 | 8.43 | 8.43 | 0.00 | 90.00 | 8.43 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 152 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | Door | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 153 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 154 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 155 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 156 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 157 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 158 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 140.00 | 140.00 | 140.00 | 180.00 | 90.00 | 35.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 159 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 105.30 | 140.00 | 105.30 | 0.00 | 90.00 | 35.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 10.27 | 10.27 | 10.27 | 0.00 | 90.00 | 10.82 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 162 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 10.27 | 10.27 | 10.27 | 0.00 | 90.00 | 10.82 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 163 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | Window | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 10.27 | 10.27 | 10.27 | 0.00 | 90.00 | 10.82 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 164 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | Door | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 165 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | Door | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 166 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 315.00 | 315.00 | 315.00 | 270.00 | 180.00 | 9.00 | 35.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 168 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 315.00 | 315.00 | 315.00 | 90.00 | 0.00 | 9.00 | 35.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 169 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 630.00 | 630.00 | 630.00 | 0.00 | 90.00 | 630.00 | 1.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 170 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 72.00 | 72.00 | 72.00 | 180.00 | 90.00 | 18.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 171 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 172 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 54.21 | 72.00 | 54.21 | 0.00 | 90.00 | 18.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 173 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.16 | 1.16 | 1.16 | 0.00 | 90.00 | 1.22 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 174 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 14.68 | 14.68 | 14.68 | 0.00 | 90.00 | 15.46 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | Door | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 176 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 162.00 | 162.00 | 162.00 | 270.00 | 180.00 | 9.00 | 18.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 178 | COMPUTER_CLASS_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 162.00 | 162.00 | 162.00 | 90.00 | 0.00 | 9.00 | 18.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 179 | COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 324.00 | 324.00 | 324.00 | 0.00 | 90.00 | 324.00 | 1.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 180 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 180.00 | 90.00 | 13.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 181 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 168.00 | 168.00 | 168.00 | 90.00 | 90.00 | 42.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 0.00 | 90.00 | 13.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 183 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 26.13 | 36.00 | 26.13 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | ||
| 187 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | Window | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.26 | 1.26 | 1.26 | 270.00 | 90.00 | 1.22 | 1.03 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.73 | 0.27 | 4 |
| 188 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | Window | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 6.66 | 6.66 | 6.66 | 270.00 | 90.00 | 6.46 | 1.03 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 189 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | Door | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.71 | 0.29 | 4 | |
| 190 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 191 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR | 2.090E-002 | 2.079E-002 | 546.00 | 546.00 | 546.00 | 270.00 | 180.00 | 42.00 | 13.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 193 | MAIN_CORRIDOR_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 546.00 | 546.00 | 546.00 | 90.00 | 0.00 | 42.00 | 13.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 194 | MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1092.00 | 1092.00 | 1092.00 | 0.00 | 90.00 | 1092.00 | 1.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 195 | LOBBY_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 57.33 | 76.00 | 57.33 | 180.00 | 90.00 | 19.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 196 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | LOBBY_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.15 | 1.15 | 1.15 | 180.00 | 90.00 | 1.22 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 197 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | LOBBY_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.57 | 15.57 | 15.57 | 180.00 | 90.00 | 16.46 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 198 | LOBBY_ZN_1_FLR_1_WALL_1_DOOR | Door | LOBBY_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 199 | LOBBY_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | OFFICES_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | LOBBY_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 6.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | LOBBY_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 0.00 | 90.00 | 13.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | LOBBY_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 203 | LOBBY_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 171.00 | 171.00 | 171.00 | 270.00 | 180.00 | 9.00 | 19.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 204 | LOBBY_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 171.00 | 171.00 | 171.00 | 90.00 | 0.00 | 9.00 | 19.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 205 | LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 342.00 | 342.00 | 342.00 | 0.00 | 90.00 | 342.00 | 1.00 | 0.00 | LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 206 | MECH_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 180.00 | 90.00 | 6.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | MECH_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 48.00 | 48.00 | 48.00 | 90.00 | 90.00 | 12.00 | 4.00 | 0.00 | OFFICES_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 208 | MECH_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.00 | 68.00 | 68.00 | 90.00 | 90.00 | 17.00 | 4.00 | 0.00 | GYM_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | MECH_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 32.00 | 32.00 | 32.00 | 90.00 | 90.00 | 8.00 | 4.00 | 0.00 | KITCHEN_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | MECH_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.00 | 20.00 | 20.00 | 90.00 | 90.00 | 5.00 | 4.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | MECH_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 6.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | MECH_ZN_1_FLR_1_WALL_7 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 168.00 | 168.00 | 168.00 | 270.00 | 90.00 | 42.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | MECH_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MECH_ZN_1_FLR_1_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 252.00 | 252.00 | 252.00 | 270.00 | 180.00 | 42.00 | 6.00 | 0.00 | MECH_ZN_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 214 | MECH_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 252.00 | 252.00 | 252.00 | 90.00 | 0.00 | 42.00 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 215 | MECH_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 504.00 | 504.00 | 504.00 | 0.00 | 90.00 | 504.00 | 1.00 | 0.00 | MECH_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 216 | BATH_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 180.00 | 90.00 | 13.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 217 | BATH_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 180.00 | 90.00 | 6.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 218 | BATH_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.00 | 40.00 | 40.00 | 90.00 | 90.00 | 10.00 | 4.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | BATH_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 76.00 | 76.00 | 76.00 | 0.00 | 90.00 | 19.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | BATH_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 31.20 | 40.00 | 31.20 | 270.00 | 90.00 | 10.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | ||
| 221 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | Window | BATH_ZN_1_FLR_1_WALL_5 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.80 | 8.80 | 8.80 | 270.00 | 90.00 | 9.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 222 | BATH_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | BATH_ZN_1_FLR_1_FLOOR_FFACTOR | 6.720E-002 | 6.612E-002 | 190.00 | 190.00 | 190.00 | 270.00 | 180.00 | 10.00 | 19.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 223 | BATH_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 190.00 | 190.00 | 190.00 | 90.00 | 0.00 | 10.00 | 19.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 224 | BATH_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 380.00 | 380.00 | 380.00 | 0.00 | 90.00 | 380.00 | 1.00 | 0.00 | BATH_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 225 | OFFICES_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 63.57 | 84.00 | 63.57 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | OFFICES_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.14 | 1.14 | 1.14 | 180.00 | 90.00 | 1.22 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 227 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | OFFICES_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 17.34 | 17.34 | 17.34 | 180.00 | 90.00 | 18.46 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 228 | OFFICES_ZN_1_FLR_1_WALL_1_DOOR | Door | OFFICES_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 229 | OFFICES_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 65.52 | 84.00 | 65.52 | 90.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 230 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | Window | OFFICES_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 18.48 | 18.48 | 18.48 | 90.00 | 90.00 | 20.90 | 0.88 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 231 | OFFICES_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | GYM_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | OFFICES_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 48.00 | 48.00 | 48.00 | 270.00 | 90.00 | 12.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | OFFICES_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 234 | OFFICES_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR | 0.123 | 0.119 | 441.00 | 441.00 | 441.00 | 270.00 | 180.00 | 21.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 235 | OFFICES_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 441.00 | 441.00 | 441.00 | 90.00 | 0.00 | 21.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 236 | OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 882.00 | 882.00 | 882.00 | 0.00 | 90.00 | 882.00 | 1.00 | 0.00 | OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 237 | GYM_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | OFFICES_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | GYM_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 51.09 | 68.00 | 51.09 | 90.00 | 90.00 | 17.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | Window | GYM_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.17 | 1.17 | 1.17 | 90.00 | 90.00 | 1.22 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 240 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | Window | GYM_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 13.79 | 13.79 | 13.79 | 90.00 | 90.00 | 14.46 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 241 | GYM_ZN_1_FLR_1_WALL_2_DOOR | Door | GYM_ZN_1_FLR_1_WALL_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 242 | GYM_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | KITCHEN_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 243 | GYM_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.00 | 68.00 | 68.00 | 270.00 | 90.00 | 17.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 244 | GYM_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | GYM_ZN_1_FLR_1_FLOOR_FFACTOR | 6.074E-002 | 5.986E-002 | 357.00 | 357.00 | 357.00 | 270.00 | 180.00 | 17.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 245 | GYM_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 343.62 | 357.00 | 343.62 | 90.00 | 0.00 | 17.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 246 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 247 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 248 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 249 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 250 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 251 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 252 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 253 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 254 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 255 | GYM_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 714.00 | 714.00 | 714.00 | 0.00 | 90.00 | 714.00 | 1.00 | 0.00 | GYM_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 256 | KITCHEN_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | GYM_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 257 | KITCHEN_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 24.96 | 32.00 | 24.96 | 90.00 | 90.00 | 8.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 258 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | Window | KITCHEN_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.04 | 7.04 | 7.04 | 90.00 | 90.00 | 7.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 259 | KITCHEN_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 260 | KITCHEN_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 32.00 | 32.00 | 32.00 | 270.00 | 90.00 | 8.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 261 | KITCHEN_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR | 6.074E-002 | 5.986E-002 | 168.00 | 168.00 | 168.00 | 270.00 | 180.00 | 8.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 262 | KITCHEN_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 168.00 | 168.00 | 168.00 | 90.00 | 0.00 | 8.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 263 | KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 336.00 | 336.00 | 336.00 | 0.00 | 90.00 | 336.00 | 1.00 | 0.00 | KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 264 | CAFETERIA_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | KITCHEN_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 265 | CAFETERIA_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 44.85 | 60.00 | 44.85 | 90.00 | 90.00 | 15.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 266 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | Window | CAFETERIA_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.18 | 1.18 | 1.18 | 90.00 | 90.00 | 1.22 | 0.96 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 267 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | Window | CAFETERIA_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 12.02 | 12.02 | 12.02 | 90.00 | 90.00 | 12.46 | 0.96 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 268 | CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | Door | CAFETERIA_ZN_1_FLR_1_WALL_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 269 | CAFETERIA_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 65.52 | 84.00 | 65.52 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.54 | 0.46 | 4 | ||
| 270 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | Window | CAFETERIA_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 18.48 | 18.48 | 18.48 | 0.00 | 90.00 | 20.90 | 0.88 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.54 | 0.46 | 4 |
| 271 | CAFETERIA_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.00 | 40.00 | 40.00 | 270.00 | 90.00 | 10.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 272 | CAFETERIA_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.00 | 20.00 | 20.00 | 270.00 | 90.00 | 5.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 273 | CAFETERIA_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR | 0.148 | 0.143 | 315.00 | 315.00 | 315.00 | 270.00 | 180.00 | 15.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 274 | CAFETERIA_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 315.00 | 315.00 | 315.00 | 90.00 | 0.00 | 15.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 275 | CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 630.00 | 630.00 | 630.00 | 0.00 | 90.00 | 630.00 | 1.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 276 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 76.00 | 76.00 | 76.00 | 180.00 | 90.00 | 19.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 277 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 63.57 | 84.00 | 63.57 | 90.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.54 | 0.46 | 4 | ||
| 278 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | Window | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.14 | 1.14 | 1.14 | 90.00 | 90.00 | 1.22 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.69 | 0.31 | 4 |
| 279 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | Window | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 17.33 | 17.33 | 17.33 | 90.00 | 90.00 | 18.46 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.53 | 0.47 | 4 |
| 280 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | Door | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 281 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 59.28 | 76.00 | 59.28 | 0.00 | 90.00 | 19.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 282 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | Window | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 16.72 | 16.72 | 16.72 | 0.00 | 90.00 | 18.90 | 0.88 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 283 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 284 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 285 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 286 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR | 0.129 | 0.125 | 399.00 | 399.00 | 399.00 | 270.00 | 180.00 | 21.00 | 19.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 287 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 399.00 | 399.00 | 399.00 | 90.00 | 0.00 | 21.00 | 19.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 288 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 798.00 | 798.00 | 798.00 | 0.00 | 90.00 | 798.00 | 1.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.7271107936E-002 | 7.9663967630E-002 | Pass | Pass | 3.4718636955 | 8.1004037941 | Pass | Pass |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.7773828366E-002 | 8.3003543357E-002 | Pass | Pass | 0.6216856015 | 1.5717337099 | Pass | Pass |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.6117091732E-002 | 4.9477458449E-002 | Pass | Pass | 29.5755647109 | 170.2588147395 | Pass | Pass |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1786746335 | 0.1827273873 | Pass | Pass | 3.8329341588 | 9.7774504352 | Fail | Pass |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.9389497749E-002 | 8.6019944117E-002 | Pass | Pass | 5.9883149072 | 24.5236458476 | Fail | Fail |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.5394212164E-002 | 8.9280546754E-002 | Pass | Pass | 4.3838994462 | 11.5523038387 | Pass | Pass |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.4510191673E-002 | 6.2111830341E-002 | Pass | Pass | 1.0493621766 | 1.8066585201 | Pass | Pass |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.9814979528E-002 | 6.4735094541E-002 | Pass | Pass | 13.7060445260 | 60.6712089826 | Pass | Pass |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1811563112 | 0.1853659038 | Pass | Pass | 3.8220175064 | 9.7432463403 | Fail | Pass |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.2196869379E-002 | 8.8416159447E-002 | Pass | Pass | 6.3456734392 | 29.7280472738 | Fail | Fail |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.2753954366E-002 | 8.5998905421E-002 | Pass | Pass | 4.9156151355 | 15.7146368792 | Pass | Pass |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.8605515015E-002 | 6.6637319989E-002 | Pass | Pass | 0.7879639415 | 1.2152069850 | Pass | Pass |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.5536439541E-002 | 5.9547437813E-002 | Pass | Pass | 11.8708953696 | 43.7654455959 | Pass | Pass |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1786674952 | 0.1828706293 | Pass | Pass | 3.8298996856 | 9.7371464063 | Fail | Pass |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.2406839064E-002 | 9.0489381267E-002 | Pass | Pass | 6.9651728217 | 24.6651763195 | Fail | Fail |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.9730652588E-002 | 5.2587099894E-002 | Pass | Pass | 42.8027899227 | 454.4424070341 | Fail | Pass |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.7373740540E-002 | 6.0003089178E-002 | Pass | Pass | 749.0690562731 | 5966.2122053715 | Pass | Pass |
| 18 | LOBBY_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.9463345983E-002 | 5.0939742891E-002 | Pass | Pass | 6.1388175560 | 15.3754669206 | Pass | Pass |
| 19 | MECH_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.5400833123E-002 | 2.9439930210E-002 | Pass | Pass | 0.5131224813 | 0.7460526175 | Pass | Pass |
| 20 | BATH_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.6428821691E-002 | 9.5671281994E-002 | Pass | Pass | 19.2720968002 | 92.9148885294 | Pass | Pass |
| 21 | OFFICES_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.0463011933E-002 | 3.3885743389E-002 | Pass | Pass | 54.5279631919 | 379.8746506276 | Fail | Pass |
| 22 | GYM_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.6786472394E-002 | 4.9748311149E-002 | Pass | Pass | 0.5862376531 | 2.2059861708 | Pass | Pass |
| 23 | KITCHEN_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.4850681533E-002 | 0.1589234564 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 24 | CAFETERIA_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.7958737247E-002 | 1.8599519720E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.1439825968E-002 | 5.1436437040E-002 | Pass | Pass | 8.3333063922 | 20.2112816947 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 9305.97 | 146.05 | 1714.78 | 5344.53 | 794.33 | 17305.75 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
| WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 0.00 | 0 | |||
| Feb | 42.00 | 35 | |||
| Mar | 0.00 | 0 | |||
| Apr | 0.00 | 0 | |||
| May | 40.00 | 22 | |||
| Jun | 4.00 | 8 | |||
| Jul | 5.00 | 4 | |||
| Aug | 7.00 | 8 | |||
| Sep | 17.00 | 10 | |||
| Oct | 50.00 | 49 | |||
| Nov | 69.00 | 59 | |||
| Dec | 95.00 | 53 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 44.00 | 32.37 | 180.00 | 90.00 | S |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 212.00 | 161.46 | 180.00 | 90.00 | S |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 12.00 | 9.36 | 270.00 | 90.00 | W |
| CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.020 | 0.020 | 192.00 | 192.00 | 270.00 | 180.00 | |
| CORRIDOR_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 192.00 | 192.00 | 90.00 | 0.00 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 44.00 | 32.37 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 212.00 | 161.46 | 0.00 | 90.00 | N |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 44.00 | 32.37 | 180.00 | 90.00 | S |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 212.00 | 161.46 | 180.00 | 90.00 | S |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 12.00 | 9.36 | 270.00 | 90.00 | W |
| CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.020 | 0.020 | 192.00 | 192.00 | 270.00 | 180.00 | |
| CORRIDOR_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 192.00 | 192.00 | 90.00 | 0.00 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 44.00 | 32.37 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 212.00 | 161.46 | 0.00 | 90.00 | N |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 44.00 | 32.37 | 180.00 | 90.00 | S |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 212.00 | 161.46 | 180.00 | 90.00 | S |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 12.00 | 9.36 | 270.00 | 90.00 | W |
| CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.020 | 0.020 | 192.00 | 192.00 | 270.00 | 180.00 | |
| CORRIDOR_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 192.00 | 192.00 | 90.00 | 0.00 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 44.00 | 32.40 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 140.00 | 105.30 | 0.00 | 90.00 | N |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 315.00 | 315.00 | 270.00 | 180.00 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 315.00 | 315.00 | 90.00 | 0.00 | |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 72.00 | 54.21 | 0.00 | 90.00 | N |
| COMPUTER_CLASS_ZN_1_FLR_1_FLOOR | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 162.00 | 162.00 | 270.00 | 180.00 | |
| COMPUTER_CLASS_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 162.00 | 162.00 | 90.00 | 0.00 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 36.00 | 26.13 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.021 | 0.021 | 546.00 | 546.00 | 270.00 | 180.00 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 546.00 | 546.00 | 90.00 | 0.00 | |
| LOBBY_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 76.00 | 57.33 | 180.00 | 90.00 | S |
| LOBBY_ZN_1_FLR_1_FLOOR | LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 171.00 | 171.00 | 270.00 | 180.00 | |
| LOBBY_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 171.00 | 171.00 | 90.00 | 0.00 | |
| MECH_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 252.00 | 252.00 | 90.00 | 0.00 | |
| BATH_ZN_1_FLR_1_WALL_5 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 40.00 | 31.20 | 270.00 | 90.00 | W |
| BATH_ZN_1_FLR_1_FLOOR | BATH_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.066 | 0.067 | 190.00 | 190.00 | 270.00 | 180.00 | |
| BATH_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 190.00 | 190.00 | 90.00 | 0.00 | |
| OFFICES_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 84.00 | 63.57 | 180.00 | 90.00 | S |
| OFFICES_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 84.00 | 65.52 | 90.00 | 90.00 | E |
| OFFICES_ZN_1_FLR_1_FLOOR | OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.120 | 0.123 | 441.00 | 441.00 | 270.00 | 180.00 | |
| OFFICES_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 441.00 | 441.00 | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 68.00 | 51.09 | 90.00 | 90.00 | E |
| GYM_ZN_1_FLR_1_FLOOR | GYM_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.060 | 0.061 | 357.00 | 357.00 | 270.00 | 180.00 | |
| GYM_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 357.00 | 343.62 | 90.00 | 0.00 | |
| KITCHEN_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 32.00 | 24.96 | 90.00 | 90.00 | E |
| KITCHEN_ZN_1_FLR_1_FLOOR | KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.060 | 0.061 | 168.00 | 168.00 | 270.00 | 180.00 | |
| KITCHEN_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 168.00 | 168.00 | 90.00 | 0.00 | |
| CAFETERIA_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 60.00 | 44.85 | 90.00 | 90.00 | E |
| CAFETERIA_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 84.00 | 65.52 | 0.00 | 90.00 | N |
| CAFETERIA_ZN_1_FLR_1_FLOOR | CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.144 | 0.148 | 315.00 | 315.00 | 270.00 | 180.00 | |
| CAFETERIA_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 315.00 | 315.00 | 90.00 | 0.00 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 84.00 | 63.57 | 90.00 | 90.00 | E |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 76.00 | 59.28 | 0.00 | 90.00 | N |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.127 | 0.129 | 399.00 | 399.00 | 270.00 | 180.00 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 399.00 | 399.00 | 90.00 | 0.00 |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 90.00 | 90.00 | E |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 90.00 | 90.00 | E |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 90.00 | 90.00 | E |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 72.00 | 72.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 140.00 | 140.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 140.00 | 140.00 | 180.00 | 90.00 | S |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 72.00 | 72.00 | 180.00 | 90.00 | S |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 180.00 | 90.00 | S |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 168.00 | 168.00 | 90.00 | 90.00 | E |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 0.00 | 90.00 | N |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 270.00 | 90.00 | W |
| LOBBY_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| LOBBY_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 0.00 | 90.00 | N |
| LOBBY_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 0.00 | 90.00 | N |
| LOBBY_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MECH_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 180.00 | 90.00 | S |
| MECH_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 48.00 | 48.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 68.00 | 68.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 32.00 | 32.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 20.00 | 20.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 0.00 | 90.00 | N |
| MECH_ZN_1_FLR_1_WALL_7 | INT_WALL | 0.30 | 2.511 | 6.299 | 168.00 | 168.00 | 270.00 | 90.00 | W |
| MECH_ZN_1_FLR_1_FLOOR | MECH_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 252.00 | 252.00 | 270.00 | 180.00 | |
| BATH_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 180.00 | 90.00 | S |
| BATH_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 180.00 | 90.00 | S |
| BATH_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 40.00 | 40.00 | 90.00 | 90.00 | E |
| BATH_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 76.00 | 76.00 | 0.00 | 90.00 | N |
| OFFICES_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 0.00 | 90.00 | N |
| OFFICES_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 48.00 | 48.00 | 270.00 | 90.00 | W |
| OFFICES_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| GYM_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 180.00 | 90.00 | S |
| GYM_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 0.00 | 90.00 | N |
| GYM_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 68.00 | 68.00 | 270.00 | 90.00 | W |
| KITCHEN_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 180.00 | 90.00 | S |
| KITCHEN_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 0.00 | 90.00 | N |
| KITCHEN_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 32.00 | 32.00 | 270.00 | 90.00 | W |
| CAFETERIA_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 180.00 | 90.00 | S |
| CAFETERIA_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 40.00 | 40.00 | 270.00 | 90.00 | W |
| CAFETERIA_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 20.00 | 20.00 | 270.00 | 90.00 | W |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 76.00 | 76.00 | 180.00 | 90.00 | S |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 270.00 | 90.00 | W |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 384.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 384.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 384.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 630.00 | 0.00 | 90.00 | N | ||
| COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 324.00 | 0.00 | 90.00 | N | ||
| MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1092.00 | 0.00 | 90.00 | N | ||
| LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 342.00 | 0.00 | 90.00 | N | ||
| MECH_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 504.00 | 0.00 | 90.00 | N | ||
| BATH_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 380.00 | 0.00 | 90.00 | N | ||
| OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 882.00 | 0.00 | 90.00 | N | ||
| GYM_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 714.00 | 0.00 | 90.00 | N | ||
| KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 336.00 | 0.00 | 90.00 | N | ||
| CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 630.00 | 0.00 | 90.00 | N | ||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 798.00 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.64 | 0.00 | 0.00 | 2.64 | 2.64 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | 270.00 | 90.00 | W | |||||||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.64 | 0.00 | 0.00 | 2.64 | 2.64 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | 270.00 | 90.00 | W | |||||||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.64 | 0.00 | 0.00 | 2.64 | 2.64 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | 270.00 | 90.00 | W | |||||||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.43 | 0.00 | 0.00 | 8.43 | 8.43 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 10.27 | 0.00 | 0.00 | 10.27 | 10.27 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 10.27 | 0.00 | 0.00 | 10.27 | 10.27 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 10.27 | 0.00 | 0.00 | 10.27 | 10.27 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.16 | 0.00 | 0.00 | 1.16 | 1.16 | 3.241 | 0.391 | 0.431 | No | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 14.68 | 0.00 | 0.00 | 14.68 | 14.68 | 3.241 | 0.391 | 0.431 | No | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.26 | 0.00 | 0.00 | 1.26 | 1.26 | 3.241 | 0.391 | 0.431 | No | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | 270.00 | 90.00 | W | |||||||
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 6.66 | 0.00 | 0.00 | 6.66 | 6.66 | 3.241 | 0.391 | 0.431 | No | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | 270.00 | 90.00 | W | |||||||
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.15 | 0.00 | 0.00 | 1.15 | 1.15 | 3.241 | 0.391 | 0.431 | No | LOBBY_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.57 | 0.00 | 0.00 | 15.57 | 15.57 | 3.241 | 0.391 | 0.431 | No | LOBBY_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.80 | 0.00 | 0.00 | 8.80 | 8.80 | 3.241 | 0.391 | 0.431 | No | BATH_ZN_1_FLR_1_WALL_5 | 270.00 | 90.00 | W | |||||||
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.14 | 0.00 | 0.00 | 1.14 | 1.14 | 3.241 | 0.391 | 0.431 | No | OFFICES_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 17.34 | 0.00 | 0.00 | 17.34 | 17.34 | 3.241 | 0.391 | 0.431 | No | OFFICES_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 18.48 | 0.00 | 0.00 | 18.48 | 18.48 | 3.241 | 0.391 | 0.431 | No | OFFICES_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.17 | 0.00 | 0.00 | 1.17 | 1.17 | 3.241 | 0.391 | 0.431 | No | GYM_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 13.79 | 0.00 | 0.00 | 13.79 | 13.79 | 3.241 | 0.391 | 0.431 | No | GYM_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.04 | 0.00 | 0.00 | 7.04 | 7.04 | 3.241 | 0.391 | 0.431 | No | KITCHEN_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.18 | 0.00 | 0.00 | 1.18 | 1.18 | 3.241 | 0.391 | 0.431 | No | CAFETERIA_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 12.02 | 0.00 | 0.00 | 12.02 | 12.02 | 3.241 | 0.391 | 0.431 | No | CAFETERIA_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 18.48 | 0.00 | 0.00 | 18.48 | 18.48 | 3.241 | 0.391 | 0.431 | No | CAFETERIA_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.14 | 0.00 | 0.00 | 1.14 | 1.14 | 3.241 | 0.391 | 0.431 | No | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 17.33 | 0.00 | 0.00 | 17.33 | 17.33 | 3.241 | 0.391 | 0.431 | No | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 16.72 | 0.00 | 0.00 | 16.72 | 16.72 | 3.241 | 0.391 | 0.431 | No | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| Total or Average | 565.98 | 3.257 | 0.394 | 0.432 | |||||||||||||||||
| North Total or Average | 204.13 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
| Non-North Total or Average | 361.86 | 3.266 | 0.395 | 0.433 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 |
| LOBBY_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LOBBY_ZN_1_FLR_1_WALL_1 |
| OFFICES_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | OFFICES_ZN_1_FLR_1_WALL_1 |
| GYM_ZN_1_FLR_1_WALL_2_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | GYM_ZN_1_FLR_1_WALL_2 |
| CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CAFETERIA_ZN_1_FLR_1_WALL_2 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.86 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.78 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.78 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | 0.73 | 0.97 | 1.00 | 0.87 | 0.99 | 1.00 | 0.00 | 0.96 | 0.78 |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.99 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | 0.73 | 0.97 | 1.00 | 0.87 | 0.99 | 1.00 | 0.00 | 0.96 | 1.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.55 |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | 0.00 | 0.00 | 0.63 | 0.00 | 0.00 | 0.89 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | 0.00 | 0.00 | 0.77 | 0.00 | 0.00 | 0.93 | 0.00 | 0.00 | 0.21 |
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.68 | 0.29 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | 0.99 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.36 | 0.83 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORRIDOR_POD_1_ZN_1_FLR_1_LIGHTS | CORRIDOR_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | GENERAL | 5.4810 | 192.00 | 1052.35 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 14.50 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORRIDOR_POD_2_ZN_1_FLR_1_LIGHTS | CORRIDOR_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | GENERAL | 5.4810 | 192.00 | 1052.35 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 14.50 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORRIDOR_POD_3_ZN_1_FLR_1_LIGHTS | CORRIDOR_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | GENERAL | 5.4810 | 192.00 | 1052.35 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 14.50 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 315.00 | 4746.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 65.42 |
| COMPUTER_CLASS_ZN_1_FLR_1_LIGHTS | COMPUTER_CLASS_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | GENERAL | 15.0695 | 162.00 | 2441.25 | LightsWired | LTG_SCH_COMPUTER_ROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 33.64 |
| MAIN_CORRIDOR_ZN_1_FLR_1_LIGHTS | MAIN_CORRIDOR_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | GENERAL | 5.4810 | 546.00 | 2992.63 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 41.24 |
| LOBBY_ZN_1_FLR_1_LIGHTS | LOBBY_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | GENERAL | 13.9931 | 171.00 | 2392.81 | LightsWired | LTG_SCH_LOBBY | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 32.97 |
| MECH_ZN_1_FLR_1_LIGHTS | MECH_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | GENERAL | 16.1458 | 252.00 | 4068.75 | LightsWired | LTG_SCH_MECHANICAL | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 56.07 |
| BATH_ZN_1_FLR_1_LIGHTS | BATH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | GENERAL | 9.6875 | 190.00 | 1840.63 | LightsWired | LTG_SCH_BATH | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 25.37 |
| OFFICES_ZN_1_FLR_1_LIGHTS | OFFICES_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GENERAL | 11.8403 | 441.00 | 5221.57 | LightsWired | LTG_SCH_OFFICE | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 71.96 |
| GYM_ZN_1_FLR_1_LIGHTS | GYM_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | GENERAL | 13.3472 | 357.00 | 4764.96 | LightsWired | LTG_SCH_GYM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 65.67 |
| KITCHEN_ZN_1_FLR_1_LIGHTS | KITCHEN_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | GENERAL | 12.9167 | 168.00 | 2170.00 | LightsWired | LTG_SCH_KITCHEN | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 29.90 |
| CAFETERIA_ZN_1_FLR_1_LIGHTS | CAFETERIA_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | GENERAL | 9.6875 | 315.00 | 3051.57 | LightsWired | LTG_SCH_CAFETERIA | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 42.05 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_LIGHTS | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | GENERAL | 16.6840 | 399.00 | 6656.93 | LightsWired | LTG_SCH_LIBRARY | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 91.74 |
| Interior Lighting Total | 12.8652 | 6871.00 | 88396.96 | 1218.18 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| EXTERIOR_LIGHTS | 5897.73 | AstronomicalClock | - | 83.54 | 83.54 | 92.49 | |
| Exterior Lighting Total | 5897.73 | 92.49 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| HEATSYS1 BOILER | Boiler:HotWater | 276750.10 | 0.75 |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | 488636.69 | 391148.19 | 97488.50 | 0.80 | 3.60 | |||
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 29570.63 | 23263.51 | 6307.12 | 0.79 | 3.50 | |||
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 47977.82 | 38410.08 | 9567.74 | 0.80 | 3.40 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| VAV_POD_1 COOLING COIL | 468510.5 | 3.01 | 10.27 | N/A | N/A | 10.80 | |
| PSZ-AC_1:6 COOLING COIL | 28377.1 | 10.72 | 10.72 | ||||
| PSZ-AC_2:7 COOLING COIL | 45968.9 | 10.40 | 10.40 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6107.66 | 5794.35 | - |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23740.52 | 22529.01 | - |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6085.08 | 5772.76 | - |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6061.71 | 5750.79 | - |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23500.19 | 22301.17 | - |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6079.61 | 5767.75 | - |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23539.30 | 22338.22 | - |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6070.45 | 5758.87 | - |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6065.04 | 5753.95 | - |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23493.76 | 22295.05 | - |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6084.06 | 5771.98 | - |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 23606.95 | 22402.40 | - |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6076.43 | 5764.55 | - |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6088.54 | 5776.22 | - |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15730.58 | 14927.78 | - |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 7769.21 | 7372.99 | - |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14257.39 | 13525.61 | - |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8177.24 | 7757.53 | - |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4465.51 | 4237.47 | - |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6422.37 | 6092.74 | - |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17351.12 | 16460.54 | - |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15003.37 | 14237.19 | - |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14974.00 | 14205.44 | - |
| VAV_POD_1 HEATING COIL | Coil:Heating:Fuel | 167276.58 | 0.79 | |
| PSZ-AC_1:6 HEATING COIL | Coil:Heating:Fuel | 59717.73 | 0.80 | |
| PSZ-AC_2:7 HEATING COIL | Coil:Heating:Fuel | 79107.52 | 0.79 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| BATH_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 0.28 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| GYM_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.54 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| KITCHEN_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 2.12 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| CAFETERIA_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.38 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.28 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| VAV_POD_1 FAN | Fan:VariableVolume | 0.62 | 1337.13 | 27.10 | 58428.59 | 2156.31 | 1.00 | 1.11 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 |
| PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.52 | 2525.20 | 1662.00 | 1.00 | 1.26 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 2.56 | 4150.67 | 1622.12 | 1.00 | 1.22 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 01:30:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002421 | 729.14 | 301156.09 | 0.90 | General |
| SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000105 | 13.47 | 127739.32 | 0.30 | General |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| SWH BOOSTER G WATER HEATER | WaterHeater:Mixed | 0.02 | 6000.00 | 0.80 | 1.09 | 0.99 |
| SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 14.75 | 0.47 |
| DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 468510.46 | 3.01 | 10.27 | 10.80 | 31.0071 | 3.15 | 10.76 | 24.6071 | 3.14 | 10.70 | 16.5067 | 3.31 | 11.30 | 6.6200 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 7364.45 | 8469.12 | 85.55 | 0.545 | 0.627 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 24.00 | 24.00 | 0.00926 | 26.04 | 0.00841 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 31521.86 | 36250.14 | 76.00 | 2.334 | 2.684 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00936 | 26.40 | 0.00841 | 0.897 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 5925.47 | 6814.29 | 35.49 | 0.439 | 0.504 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00887 | 26.13 | 0.00841 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 6202.51 | 7132.88 | 72.05 | 0.459 | 0.528 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 24.00 | 24.00 | 0.00940 | 25.25 | 0.00841 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 24867.49 | 28597.61 | 59.95 | 1.841 | 2.118 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00959 | 26.40 | 0.00841 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 7320.66 | 8418.76 | 85.04 | 0.542 | 0.623 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 24.00 | 24.00 | 0.00927 | 26.04 | 0.00841 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 31175.55 | 35851.89 | 75.16 | 2.308 | 2.655 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00937 | 26.40 | 0.00841 | 0.897 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 5906.70 | 6792.70 | 35.38 | 0.437 | 0.503 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00887 | 26.13 | 0.00841 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 6205.10 | 7135.87 | 72.08 | 0.459 | 0.528 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 24.00 | 24.00 | 0.00940 | 25.25 | 0.00841 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 24877.79 | 28609.46 | 59.98 | 1.842 | 2.118 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00959 | 26.40 | 0.00841 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 7326.02 | 8424.93 | 85.10 | 0.542 | 0.624 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 24.00 | 24.00 | 0.00927 | 26.04 | 0.00841 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 31300.27 | 35995.31 | 75.46 | 2.318 | 2.665 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00937 | 26.40 | 0.00841 | 0.897 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 5962.40 | 6856.76 | 35.71 | 0.441 | 0.508 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00887 | 26.13 | 0.00841 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 6244.57 | 7181.25 | 72.54 | 0.462 | 0.532 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 24.00 | 24.00 | 0.00940 | 25.37 | 0.00841 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 16678.22 | 19179.95 | 60.89 | 1.235 | 1.420 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00958 | 26.40 | 0.00841 | 0.592 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 9278.13 | 10669.85 | 65.86 | 0.687 | 0.790 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00949 | 26.40 | 0.00841 | 0.304 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 12417.43 | 14280.05 | 26.15 | 0.919 | 1.057 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00901 | 26.13 | 0.00841 | 0.166 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 7947.73 | 9139.90 | 53.45 | 0.588 | 0.677 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00899 | 26.40 | 0.00841 | 0.096 | 0.00 |
| MECH_ZN_1_FLR_1 | 9102.87 | 10468.30 | 41.54 | 0.674 | 0.775 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00860 | 26.40 | 0.00841 | 0.000 | 0.00 |
| BATH_ZN_1_FLR_1 | 5779.10 | 6645.96 | 34.98 | 0.428 | 0.492 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 16:30:00 | 24.00 | 24.00 | 0.00888 | 25.49 | 0.00841 | 0.000 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 18358.29 | 21112.04 | 47.87 | 1.359 | 1.563 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00877 | 26.40 | 0.00841 | 0.190 | 0.00 |
| GYM_ZN_1_FLR_1 | 20217.41 | 23250.02 | 65.13 | 1.497 | 1.722 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 23.99 | 0.00971 | 26.25 | 0.00841 | 0.544 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 17826.02 | 20499.92 | 122.02 | 1.321 | 1.519 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.99 | 0.01056 | 25.58 | 0.00841 | 0.255 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 30015.01 | 34517.26 | 109.58 | 2.225 | 2.559 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24.00 | 23.98 | 0.01089 | 25.95 | 0.00841 | 1.488 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 18903.96 | 21739.55 | 54.49 | 1.399 | 1.609 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00898 | 26.40 | 0.00841 | 0.345 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 2775.73 | 3469.66 | 35.05 | 0.206 | 0.257 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00791 | -4.30 | 0.00266 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 8837.57 | 11046.96 | 23.16 | 0.655 | 0.897 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00793 | -4.30 | 0.00266 | 0.897 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 2813.94 | 3517.43 | 18.32 | 0.208 | 0.261 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00799 | -4.30 | 0.00266 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 2743.08 | 3428.85 | 34.63 | 0.203 | 0.254 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00791 | -4.30 | 0.00266 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 8635.93 | 10794.91 | 22.63 | 0.640 | 0.897 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00792 | -4.30 | 0.00266 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 2756.01 | 3445.01 | 34.80 | 0.204 | 0.255 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00791 | -4.30 | 0.00266 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 8683.56 | 10854.45 | 22.76 | 0.643 | 0.897 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00792 | -4.30 | 0.00266 | 0.897 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 2807.17 | 3508.97 | 18.28 | 0.208 | 0.260 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00799 | -4.30 | 0.00266 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 2744.86 | 3431.08 | 34.66 | 0.203 | 0.254 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00791 | -4.30 | 0.00266 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 8643.27 | 10804.08 | 22.65 | 0.640 | 0.897 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00792 | -4.30 | 0.00266 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 2758.03 | 3447.54 | 34.82 | 0.204 | 0.255 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00791 | -4.30 | 0.00266 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 8718.08 | 10897.60 | 22.85 | 0.646 | 0.897 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00792 | -4.30 | 0.00266 | 0.897 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 2809.94 | 3512.43 | 18.29 | 0.208 | 0.260 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00799 | -4.30 | 0.00266 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 2762.83 | 3453.54 | 34.88 | 0.205 | 0.256 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00791 | -4.30 | 0.00266 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 5879.41 | 7349.27 | 23.33 | 0.436 | 0.592 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00793 | -4.30 | 0.00266 | 0.592 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 2765.63 | 3457.04 | 21.34 | 0.205 | 0.304 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00792 | -4.30 | 0.00266 | 0.304 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 6593.11 | 8241.38 | 15.09 | 0.488 | 0.611 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00798 | -4.30 | 0.00266 | 0.166 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 3781.59 | 4726.99 | 27.64 | 0.280 | 0.350 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00794 | -4.30 | 0.00266 | 0.096 | 0.00 |
| MECH_ZN_1_FLR_1 | 1739.99 | 2174.99 | 8.63 | 0.129 | 0.161 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:40:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 0.000 | 0.00 |
| BATH_ZN_1_FLR_1 | 2969.99 | 3712.49 | 19.54 | 0.220 | 0.275 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00796 | -4.30 | 0.00266 | 0.000 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 8024.08 | 10030.11 | 22.74 | 0.594 | 0.743 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00793 | -4.30 | 0.00266 | 0.190 | 0.00 |
| GYM_ZN_1_FLR_1 | 5841.40 | 7301.75 | 20.45 | 0.433 | 0.544 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 21.00 | 21.00 | 0.00796 | -4.30 | 0.00266 | 0.544 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.000 | 0.255 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 23.51 | 0.01852 | -4.30 | 0.00266 | 0.255 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 6115.01 | 7643.76 | 24.27 | 0.453 | 1.488 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 21.00 | 21.00 | 0.00793 | -4.30 | 0.00266 | 1.488 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 6924.82 | 8656.02 | 21.69 | 0.513 | 0.641 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00793 | -4.30 | 0.00266 | 0.345 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| VAV_POD_1 | 27.10 | 27.10 | 11.02 | 11.02 | 27.0965 | 12.4373 | 27.0965 | 0.4590 | 0.3000 |
| PSZ-AC_1:6 | 1.52 | 1.52 | 0.25 | 0.25 | 1.5194 | 1.5194 | 1.5194 | 1.0000 | 1.0000 |
| PSZ-AC_2:7 | 2.56 | 2.56 | 1.49 | 1.49 | 2.5588 | 2.5588 | 2.5588 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | 6107.663 | 6107.663 | 0.267761 | 0.00005343 | 141.558 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6107.66 | 6107.66 | 0.267761 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00791043 | 50.6025 | 3469.66 | 0.00 | 6135.76 | 6135.76 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | 23740.519 | 23740.519 | 1.288371 | 0.00020769 | 523.577 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 23740.52 | 23740.52 | 1.288371 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00792524 | 50.6959 | 11046.96 | 0.00 | 23853.22 | 23853.22 |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX | 6085.083 | 6085.083 | 0.260581 | 0.00005323 | 141.935 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6085.08 | 6085.08 | 0.260581 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00798656 | 51.0830 | 3517.43 | 0.00 | 6113.00 | 6113.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | 6061.713 | 6061.713 | 0.267239 | 0.00005303 | 140.283 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6061.71 | 6061.71 | 0.267239 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00790939 | 50.5959 | 3428.85 | 0.00 | 6089.61 | 6089.61 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | 23500.185 | 23500.185 | 1.289565 | 0.00020559 | 517.119 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 23500.19 | 23500.19 | 1.289565 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00792352 | 50.6850 | 10794.91 | 0.00 | 23611.84 | 23611.84 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | 6079.608 | 6079.608 | 0.267415 | 0.00005319 | 140.783 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6079.61 | 6079.61 | 0.267415 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00790980 | 50.5985 | 3445.01 | 0.00 | 6107.58 | 6107.58 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | 23539.301 | 23539.301 | 1.287491 | 0.00020593 | 518.320 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 23539.30 | 23539.30 | 1.287491 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00792393 | 50.6876 | 10854.45 | 0.00 | 23651.11 | 23651.11 |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX | 6070.446 | 6070.446 | 0.259954 | 0.00005311 | 141.594 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6070.45 | 6070.45 | 0.259954 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00798652 | 51.0828 | 3508.97 | 0.00 | 6098.29 | 6098.29 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | 6065.042 | 6065.042 | 0.267351 | 0.00005306 | 140.365 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6065.04 | 6065.04 | 0.267351 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00790944 | 50.5962 | 3431.08 | 0.00 | 6092.96 | 6092.96 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | 23493.755 | 23493.755 | 1.287981 | 0.00020553 | 517.077 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 23493.76 | 23493.76 | 1.287981 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00792359 | 50.6854 | 10804.08 | 0.00 | 23605.37 | 23605.37 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | 6084.063 | 6084.063 | 0.267611 | 0.00005323 | 140.886 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6084.06 | 6084.06 | 0.267611 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00790987 | 50.5989 | 3447.54 | 0.00 | 6112.06 | 6112.06 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | 23606.945 | 23606.945 | 1.289976 | 0.00020652 | 519.908 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 23606.95 | 23606.95 | 1.289976 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00792423 | 50.6895 | 10897.60 | 0.00 | 23719.07 | 23719.07 |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX | 6076.430 | 6076.430 | 0.260211 | 0.00005316 | 141.733 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6076.43 | 6076.43 | 0.260211 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00798654 | 51.0829 | 3512.43 | 0.00 | 6104.30 | 6104.30 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | 6088.544 | 6088.544 | 0.267457 | 0.00005327 | 141.039 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6088.54 | 6088.54 | 0.267457 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00791002 | 50.5999 | 3453.54 | 0.00 | 6116.55 | 6116.55 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | 15730.577 | 15730.577 | 0.850686 | 0.00013762 | 347.173 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 15730.58 | 15730.58 | 0.850686 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00792578 | 50.6993 | 7349.27 | 0.00 | 15805.23 | 15805.23 |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX | 7769.213 | 7769.213 | 0.437683 | 0.00006797 | 170.079 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7769.21 | 7769.21 | 0.437683 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00791896 | 50.6562 | 3457.04 | 0.00 | 7806.20 | 7806.20 |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX | 14257.390 | 14257.390 | 0.610545 | 0.00012473 | 332.555 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14257.39 | 14257.39 | 0.610545 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00798280 | 51.0592 | 8241.38 | 0.00 | 14322.79 | 14322.79 |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | LOBBY_ZN_1_FLR_1 VAV BOX | 8177.242 | 8177.242 | 0.350187 | 0.00007154 | 190.733 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8177.24 | 8177.24 | 0.350187 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00793723 | 50.7716 | 4726.99 | 0.00 | 8214.75 | 8214.75 |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_ZN_1_FLR_1 VAV BOX | 4465.510 | 4465.510 | 0.232450 | 0.00003907 | 99.341 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:40:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:40:00 | 4465.51 | 4465.51 | 0.232450 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 2174.99 | 0.00 | 4486.64 | 4486.64 |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6422.375 | 6422.375 | 0.275031 | 0.00005619 | 149.802 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 6422.37 | 6422.37 | 0.275031 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00795777 | 50.9012 | 3712.49 | 0.00 | 6451.84 | 6451.84 |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | OFFICES_ZN_1_FLR_1 VAV BOX | 17351.115 | 17351.115 | 0.743055 | 0.00015180 | 404.713 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 17351.12 | 17351.12 | 0.743055 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00793464 | 50.7552 | 10030.11 | 0.00 | 17430.71 | 17430.71 |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15003.374 | 15003.374 | 0.781644 | 0.00013126 | 333.710 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | 15003.37 | 15003.37 | 0.781644 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00796345 | 50.9372 | 7301.75 | 0.00 | 15074.38 | 15074.38 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 14974.003 | 14974.003 | 0.641259 | 0.00013100 | 349.266 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 14974.00 | 14974.00 | 0.641259 | 12.89 | 11.54 | 0.00800000 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00792796 | 50.7130 | 8656.02 | 0.00 | 15042.69 | 15042.69 |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | VAV_POD_1 | 488636.692 | 391148.190 | 27.096517 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 479328.16 | 442582.87 | 27.096517 | 24.94 | 16.99 | 0.00894932 | 11.12 | 11.12 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 39.4268 | 24.00 | 0.00930227 | 49.4901 | 318242.06 | 0.00 | 490049.93 | 389143.57 |
| VAV_POD_1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | VAV_POD_1 | 167276.584 | 167276.584 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 167276.58 | 167276.58 | 8.128955 | -4.30 | -4.30 | 0.00265759 | 12.89 | 11.54 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 131.4228 | 21.00 | 0.00793551 | 50.7609 | 112910.00 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:6 | 29570.630 | 23263.510 | 1.519370 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 14785.32 | 11104.09 | 1.012913 | 24.22 | 17.77 | 0.01019905 | 11.53 | 11.47 | 0.00850000 | 25.58 | 0.00840579 | 16.75 | 25.1565 | 23.99 | 0.01056040 | 56.1060 | 17826.02 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_1:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:6 | 59717.727 | 59717.727 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 59717.73 | 59717.73 | 1.519374 | -0.72 | -0.72 | 0.01606876 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 16.7710 | 23.73 | 0.01877116 | 99.9996 | 0.00 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:7 | 47977.820 | 38410.083 | 2.558790 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 23988.91 | 20535.42 | 1.705860 | 25.41 | 17.56 | 0.00944123 | 11.56 | 11.49 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 87.2395 | 23.98 | 0.01093303 | 58.0642 | 29749.33 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_2:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:7 | 79107.522 | 79107.522 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 01:30:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 01:30:00 | 79107.52 | 79107.52 | 2.558786 | 6.29 | 4.90 | 0.00486211 | 32.11 | 18.62 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 58.1598 | 21.00 | 0.00792650 | 50.7040 | 6109.98 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6107.663 | 6107.663 | 0.267761 | 0.00005343 | 141.558 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 2.1634 | 2.206923 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 6107.66 | 6107.66 | 1.0000 | 0.31900274 | 0.267761 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.05342705 | 60.00 | 32.22 | 27.78 | 0.000 | 6107.66 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00791043 | 21.00 | 0.00791043 | 50.6025 | 3469.66 | 0.00 | 6135.76 | 6135.76 | 0.31900274 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.66 | 18.59 | 0.00800000 | 52294.0 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23740.519 | 23740.519 | 1.288371 | 0.00020769 | 523.577 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 8.4091 | 8.578324 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 23740.52 | 23740.52 | 1.0000 | 1.53492963 | 1.288371 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.20767123 | 60.00 | 32.22 | 27.78 | 0.000 | 23740.52 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00792524 | 21.00 | 0.00792524 | 50.6959 | 11046.96 | 0.00 | 23853.22 | 23853.22 | 1.53492963 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.04 | 17.37 | 0.00800000 | 48600.1 | |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX | CORRIDOR_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6085.083 | 6085.083 | 0.260581 | 0.00005323 | 141.935 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 2.1554 | 2.198765 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 6085.08 | 6085.08 | 1.0000 | 0.31044915 | 0.260581 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.05322953 | 60.00 | 32.22 | 27.78 | 0.000 | 6085.08 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00798656 | 21.00 | 0.00798656 | 51.0830 | 3517.43 | 0.00 | 6113.00 | 6113.00 | 0.31044915 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.6 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6061.713 | 6061.713 | 0.267239 | 0.00005303 | 140.283 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 2.1471 | 2.190320 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 6061.71 | 6061.71 | 1.0000 | 0.31838159 | 0.267239 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.05302510 | 60.00 | 32.22 | 27.78 | 0.000 | 6061.71 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00790939 | 21.00 | 0.00790939 | 50.5959 | 3428.85 | 0.00 | 6089.61 | 6089.61 | 0.31838159 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.56 | 18.55 | 0.00800000 | 52186.6 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23500.185 | 23500.185 | 1.289565 | 0.00020559 | 517.119 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 8.3240 | 8.491482 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 23500.19 | 23500.19 | 1.0000 | 1.53635178 | 1.289565 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.20556890 | 60.00 | 32.22 | 27.78 | 0.000 | 23500.19 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00792352 | 21.00 | 0.00792352 | 50.6850 | 10794.91 | 0.00 | 23611.84 | 23611.84 | 1.53635178 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 27.87 | 17.32 | 0.00800000 | 48428.6 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6079.608 | 6079.608 | 0.267415 | 0.00005319 | 140.783 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 2.1534 | 2.196786 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 6079.61 | 6079.61 | 1.0000 | 0.31859098 | 0.267415 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.05318163 | 60.00 | 32.22 | 27.78 | 0.000 | 6079.61 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00790980 | 21.00 | 0.00790980 | 50.5985 | 3445.01 | 0.00 | 6107.58 | 6107.58 | 0.31859098 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.60 | 18.57 | 0.00800000 | 52230.4 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23539.301 | 23539.301 | 1.287491 | 0.00020593 | 518.320 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 8.3378 | 8.505616 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 23539.30 | 23539.30 | 1.0000 | 1.53388074 | 1.287491 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.20591106 | 60.00 | 32.22 | 27.78 | 0.000 | 23539.30 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00792393 | 21.00 | 0.00792393 | 50.6876 | 10854.45 | 0.00 | 23651.11 | 23651.11 | 1.53388074 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 27.92 | 17.33 | 0.00800000 | 48479.0 | |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX | CORRIDOR_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6070.446 | 6070.446 | 0.259954 | 0.00005311 | 141.594 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 2.1502 | 2.193476 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 6070.45 | 6070.45 | 1.0000 | 0.30970242 | 0.259954 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.05310149 | 60.00 | 32.22 | 27.78 | 0.000 | 6070.45 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00798652 | 21.00 | 0.00798652 | 51.0828 | 3508.97 | 0.00 | 6098.29 | 6098.29 | 0.30970242 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.6 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6065.042 | 6065.042 | 0.267351 | 0.00005306 | 140.365 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 2.1483 | 2.191523 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 6065.04 | 6065.04 | 1.0000 | 0.31851490 | 0.267351 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.05305422 | 60.00 | 32.22 | 27.78 | 0.000 | 6065.04 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00790944 | 21.00 | 0.00790944 | 50.5962 | 3431.08 | 0.00 | 6092.96 | 6092.96 | 0.31851490 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.56 | 18.55 | 0.00800000 | 52189.1 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23493.755 | 23493.755 | 1.287981 | 0.00020553 | 517.077 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 8.3217 | 8.489159 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 23493.76 | 23493.76 | 1.0000 | 1.53446464 | 1.287981 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.20551265 | 60.00 | 32.22 | 27.78 | 0.000 | 23493.76 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00792359 | 21.00 | 0.00792359 | 50.6854 | 10804.08 | 0.00 | 23605.37 | 23605.37 | 1.53446464 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 27.89 | 17.32 | 0.00800000 | 48443.3 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6084.063 | 6084.063 | 0.267611 | 0.00005323 | 140.886 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 2.1550 | 2.198396 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 6084.06 | 6084.06 | 1.0000 | 0.31882448 | 0.267611 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.05322061 | 60.00 | 32.22 | 27.78 | 0.000 | 6084.06 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00790987 | 21.00 | 0.00790987 | 50.5989 | 3447.54 | 0.00 | 6112.06 | 6112.06 | 0.31882448 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.60 | 18.57 | 0.00800000 | 52230.4 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23606.945 | 23606.945 | 1.289976 | 0.00020652 | 519.908 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 8.3618 | 8.530059 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 23606.95 | 23606.95 | 1.0000 | 1.53684120 | 1.289976 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.20650279 | 60.00 | 32.22 | 27.78 | 0.000 | 23606.95 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00792423 | 21.00 | 0.00792423 | 50.6895 | 10897.60 | 0.00 | 23719.07 | 23719.07 | 1.53684120 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 27.94 | 17.34 | 0.00800000 | 48493.5 | |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX | CORRIDOR_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6076.430 | 6076.430 | 0.260211 | 0.00005316 | 141.733 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 2.1523 | 2.195638 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 6076.43 | 6076.43 | 1.0000 | 0.31000768 | 0.260211 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.05315383 | 60.00 | 32.22 | 27.78 | 0.000 | 6076.43 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00798654 | 21.00 | 0.00798654 | 51.0829 | 3512.43 | 0.00 | 6104.30 | 6104.30 | 0.31000768 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.6 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6088.544 | 6088.544 | 0.267457 | 0.00005327 | 141.039 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 2.1566 | 2.200015 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 6088.54 | 6088.54 | 1.0000 | 0.31864031 | 0.267457 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.05325980 | 60.00 | 32.22 | 27.78 | 0.000 | 6088.54 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00791002 | 21.00 | 0.00791002 | 50.5999 | 3453.54 | 0.00 | 6116.55 | 6116.55 | 0.31864031 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 31.62 | 18.57 | 0.00800000 | 52255.6 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15730.577 | 15730.577 | 0.850686 | 0.00013762 | 347.173 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 5.5719 | 5.684037 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 15730.58 | 15730.58 | 1.0000 | 1.01348348 | 0.850686 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.13760391 | 60.00 | 32.22 | 27.78 | 0.000 | 15730.58 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00792578 | 21.00 | 0.00792578 | 50.6993 | 7349.27 | 0.00 | 15805.23 | 15805.23 | 1.01348348 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.09 | 17.39 | 0.00800000 | 48654.8 | |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX | COMPUTER_CLASS_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7769.213 | 7769.213 | 0.437683 | 0.00006797 | 170.079 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 2.7519 | 2.807303 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7769.21 | 7769.21 | 1.0000 | 0.52144290 | 0.437683 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.06796153 | 60.00 | 32.22 | 27.78 | 0.000 | 7769.21 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00791896 | 21.00 | 0.00791896 | 50.6562 | 3457.04 | 0.00 | 7806.20 | 7806.20 | 0.52144290 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 27.48 | 17.18 | 0.00800000 | 48030.2 | |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX | MAIN_CORRIDOR_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14257.390 | 14257.390 | 0.610545 | 0.00012473 | 332.555 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 5.0501 | 5.151720 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 14257.39 | 14257.39 | 1.0000 | 0.72738649 | 0.610545 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.12471714 | 60.00 | 32.22 | 27.78 | 0.000 | 14257.39 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00798280 | 21.00 | 0.00798280 | 51.0592 | 8241.38 | 0.00 | 14322.79 | 14322.79 | 0.72738649 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.6 | |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | LOBBY_ZN_1_FLR_1 VAV BOX | LOBBY_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8177.242 | 8177.242 | 0.350187 | 0.00007154 | 190.733 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 2.8964 | 2.954739 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8177.24 | 8177.24 | 1.0000 | 0.41720243 | 0.350187 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.07153078 | 60.00 | 32.22 | 27.78 | 0.000 | 8177.24 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00793723 | 21.00 | 0.00793723 | 50.7716 | 4726.99 | 0.00 | 8214.75 | 8214.75 | 0.41720243 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.9 | |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_ZN_1_FLR_1 VAV BOX | MECH_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4465.510 | 4465.510 | 0.232450 | 0.00003907 | 99.341 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 1.5817 | 1.613553 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:40:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:40:00 | Sensible | 4465.51 | 4465.51 | 1.0000 | 0.27693489 | 0.232450 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.03906225 | 60.00 | 32.22 | 27.78 | 0.000 | 4465.51 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 2174.99 | 0.00 | 4486.64 | 4486.64 | 0.27693489 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.69 | 17.60 | 0.00800000 | 49260.9 | |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BATH_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6422.375 | 6422.375 | 0.275031 | 0.00005619 | 149.802 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 2.2749 | 2.320641 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 6422.37 | 6422.37 | 1.0000 | 0.32766424 | 0.275031 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.05618001 | 60.00 | 32.22 | 27.78 | 0.000 | 6422.37 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00795777 | 21.00 | 0.00795777 | 50.9012 | 3712.49 | 0.00 | 6451.84 | 6451.84 | 0.32766424 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.2 | |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | OFFICES_ZN_1_FLR_1 VAV BOX | OFFICES_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17351.115 | 17351.115 | 0.743055 | 0.00015180 | 404.713 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 6.1459 | 6.269597 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 17351.12 | 17351.12 | 1.0000 | 0.88525481 | 0.743055 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.15177964 | 60.00 | 32.22 | 27.78 | 0.000 | 17351.12 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00793464 | 21.00 | 0.00793464 | 50.7552 | 10030.11 | 0.00 | 17430.71 | 17430.71 | 0.88525481 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.9 | |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | GYM_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15003.374 | 15003.374 | 0.781644 | 0.00013126 | 333.710 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 5.3143 | 5.421271 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 04:30:00 | Sensible | 15003.37 | 15003.37 | 1.0000 | 0.93122938 | 0.781644 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.13124267 | 60.00 | 32.22 | 27.78 | 0.000 | 15003.37 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00796345 | 21.00 | 0.00796345 | 50.9372 | 7301.75 | 0.00 | 15074.38 | 15074.38 | 0.93122938 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.67 | 17.59 | 0.00800000 | 49247.4 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14974.003 | 14974.003 | 0.641259 | 0.00013100 | 349.266 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.42088358 | 54.44 | 82.22 | 27.78 | 282319.80 | 5.3039 | 5.410659 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 14974.00 | 14974.00 | 1.0000 | 0.76397830 | 0.641259 | 12.89 | 11.54 | 0.00800000 | 33150.5 | 32.11 | 18.62 | 0.00800000 | 52751.6 | 0.13098575 | 60.00 | 32.22 | 27.78 | 0.000 | 14974.00 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00792796 | 21.00 | 0.00792796 | 50.7130 | 8656.02 | 0.00 | 15042.69 | 15042.69 | 0.76397830 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.8 | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | VAV_POD_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1; MULT_CLASS_1_POD_1_ZN_1_FLR_1; CORRIDOR_POD_1_ZN_1_FLR_1; CORNER_CLASS_2_POD_1_ZN_1_FLR_1; MULT_CLASS_2_POD_1_ZN_1_FLR_1; CORNER_CLASS_1_POD_2_ZN_1_FLR_1; MULT_CLASS_1_POD_2_ZN_1_FLR_1; CORRIDOR_POD_2_ZN_1_FLR_1; CORNER_CLASS_2_POD_2_ZN_1_FLR_1; MULT_CLASS_2_POD_2_ZN_1_FLR_1; CORNER_CLASS_1_POD_3_ZN_1_FLR_1; MULT_CLASS_1_POD_3_ZN_1_FLR_1; CORRIDOR_POD_3_ZN_1_FLR_1; CORNER_CLASS_2_POD_3_ZN_1_FLR_1; MULT_CLASS_2_POD_3_ZN_1_FLR_1; COMPUTER_CLASS_ZN_1_FLR_1; MAIN_CORRIDOR_ZN_1_FLR_1; LOBBY_ZN_1_FLR_1; MECH_ZN_1_FLR_1; BATH_ZN_1_FLR_1; OFFICES_ZN_1_FLR_1; GYM_ZN_1_FLR_1; LIBRARY_MEDIA_CENTER_ZN_1_FLR_1; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 488636.692 | 391148.190 | 27.096517 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4763 | 1004.8586 | 1.1914 | VAV_POD_1 FAN | Fan:VariableVolume | 27.096517 | 32.28203184 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 479328.16 | 442582.87 | 0.9810 | 32.28203184 | 27.096517 | 24.94 | 16.99 | 0.00894932 | 47861.6 | 11.12 | 11.12 | 0.00850000 | 32604.5 | -999.0 | -999.00 | -999.00 | -999.00 | 58428.585 | 420899.58 | 26.40 | 0.00840708 | 17.04 | 10.68330000 | 39.4268 | 24.00 | 0.00930227 | 24.00 | 0.00930227 | 49.4901 | 318242.06 | 0.00 | 490049.93 | 389143.57 | 31.00713562 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.40 | 14.10 | 0.00990873 | 39518.0 | |
| VAV_POD_1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | VAV_POD_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1; MULT_CLASS_1_POD_1_ZN_1_FLR_1; CORRIDOR_POD_1_ZN_1_FLR_1; CORNER_CLASS_2_POD_1_ZN_1_FLR_1; MULT_CLASS_2_POD_1_ZN_1_FLR_1; CORNER_CLASS_1_POD_2_ZN_1_FLR_1; MULT_CLASS_1_POD_2_ZN_1_FLR_1; CORRIDOR_POD_2_ZN_1_FLR_1; CORNER_CLASS_2_POD_2_ZN_1_FLR_1; MULT_CLASS_2_POD_2_ZN_1_FLR_1; CORNER_CLASS_1_POD_3_ZN_1_FLR_1; MULT_CLASS_1_POD_3_ZN_1_FLR_1; CORRIDOR_POD_3_ZN_1_FLR_1; CORNER_CLASS_2_POD_3_ZN_1_FLR_1; MULT_CLASS_2_POD_3_ZN_1_FLR_1; COMPUTER_CLASS_ZN_1_FLR_1; MAIN_CORRIDOR_ZN_1_FLR_1; LOBBY_ZN_1_FLR_1; MECH_ZN_1_FLR_1; BATH_ZN_1_FLR_1; OFFICES_ZN_1_FLR_1; GYM_ZN_1_FLR_1; LIBRARY_MEDIA_CENTER_ZN_1_FLR_1; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 167276.584 | 167276.584 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_POD_1 FAN | Fan:VariableVolume | 27.096517 | 32.28203184 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 167276.58 | 167276.58 | 1.0000 | 9.68460955 | 8.128955 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 12.89 | 11.54 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 167276.58 | -4.30 | 0.00265759 | -4.30 | 10.68330000 | 131.4228 | 21.00 | 0.00793493 | 21.00 | 0.00793551 | 50.7609 | 112910.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:6 | KITCHEN_ZN_1_FLR_1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 29570.630 | 23263.510 | 1.519370 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7995 | 1004.8586 | 1.1914 | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.519374 | 1.81014014 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 14785.32 | 11104.09 | 1.0000 | 1.20675660 | 1.012913 | 24.22 | 17.77 | 0.01019905 | 50305.0 | 11.53 | 11.47 | 0.00850000 | 33022.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 14785.32 | 25.58 | 0.00840579 | 16.75 | 0.25481392 | 25.1565 | 23.95 | 0.01056040 | 23.99 | 0.01056040 | 56.1060 | 17826.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_1:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:6 | KITCHEN_ZN_1_FLR_1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 59717.727 | 59717.727 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.519374 | 1.81014014 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 59717.73 | 59717.73 | 1.0000 | 1.81014014 | 1.519374 | -0.72 | -0.72 | 0.01606876 | 39440.8 | 32.11 | 18.62 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59717.73 | -4.30 | 0.00265759 | -4.30 | 0.25481392 | 16.7710 | 0.00 | 0.01877116 | 23.73 | 0.01877116 | 99.9996 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:7 | CAFETERIA_ZN_1_FLR_1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 47977.820 | 38410.083 | 2.558790 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.3908 | 1004.8586 | 1.1914 | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.558786 | 3.04846593 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | Sensible | 23988.91 | 20535.42 | 1.0000 | 2.03231386 | 1.705860 | 25.41 | 17.56 | 0.00944123 | 49591.3 | 11.56 | 11.49 | 0.00850000 | 33053.7 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23988.91 | 26.40 | 0.00840708 | 17.04 | 1.48818443 | 87.2395 | 23.98 | 0.01093303 | 23.98 | 0.01093303 | 58.0642 | 29749.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_2:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:7 | CAFETERIA_ZN_1_FLR_1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 79107.522 | 79107.522 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.558786 | 3.04846593 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 01:30:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 01:30:00 | Sensible | 79107.52 | 79107.52 | 1.0000 | 3.04846593 | 2.558786 | 6.29 | 4.90 | 0.00486211 | 18532.6 | 32.11 | 18.62 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 79107.52 | -4.30 | 0.00265759 | -4.30 | 1.48818443 | 58.1598 | 21.00 | 0.00792650 | 21.00 | 0.00792650 | 50.7040 | 6109.98 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| VAV_POD_1_OA_CONTROLLER | FixedDryBulb | 0.00 | 27.10 | - | |||
| PSZ-AC_1:6_OA_CONTROLLER | FixedDryBulb | 0.25 | 1.52 | - | |||
| PSZ-AC_2:7_OA_CONTROLLER | FixedDryBulb | 1.49 | 2.56 | - |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| LOBBY_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000559 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MECH_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| BATH_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| OFFICES_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| GYM_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001524 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000864 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 877.00 | 2583.83 | 525.83 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 584.17 | 2558.33 | 229.33 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 518.67 | 2830.17 | 452.50 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 880.17 | 3003.17 | 772.17 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 520.83 | 3011.83 | 426.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 872.83 | 2624.50 | 544.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 564.50 | 2601.50 | 236.17 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 523.17 | 2844.00 | 461.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 881.00 | 3002.83 | 773.17 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 523.50 | 3008.50 | 427.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 868.83 | 2600.67 | 530.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 570.67 | 2556.17 | 222.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 498.17 | 2746.50 | 410.83 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 883.67 | 2970.83 | 754.17 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 528.83 | 2934.83 | 409.67 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 579.33 | 2297.17 | 150.17 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 835.33 | 2343.83 | 603.17 |
| LOBBY_ZN_1_FLR_1 | 1381.67 | 3088.00 | 1288.00 |
| MECH_ZN_1_FLR_1 | 1690.50 | 1480.67 | 105.00 |
| BATH_ZN_1_FLR_1 | 1652.83 | 2122.00 | 877.67 |
| OFFICES_ZN_1_FLR_1 | 971.00 | 1690.00 | 458.00 |
| GYM_ZN_1_FLR_1 | 1201.17 | 1719.67 | 127.50 |
| KITCHEN_ZN_1_FLR_1 | 2847.83 | 29.17 | 3.50 |
| CAFETERIA_ZN_1_FLR_1 | 825.33 | 1676.00 | 71.17 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 883.67 | 1875.17 | 264.33 |
| Facility | 3245.83 | 3228.67 | 1346.17 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 4.83 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.67 | 0.33 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 11.33 | 0.00 | 3.67 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 9.50 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 4.17 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 4.83 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 2.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 12.00 | 0.00 | 4.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 10.17 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 4.33 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 4.67 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.83 | 0.17 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 10.17 | 0.00 | 3.50 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 9.33 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 4.17 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 2.33 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 9.50 | 0.00 | 3.50 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 1058.17 | 1.17 | 825.17 | 1.17 |
| MECH_ZN_1_FLR_1 | 0.00 | 0.33 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 4.33 | 0.00 | 0.17 | 0.00 |
| GYM_ZN_1_FLR_1 | 6.67 | 1.33 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 0.00 | 663.17 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 5.00 | 0.17 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 2.67 | 0.00 | 0.00 | 0.00 |
| Facility | 1066.67 | 666.33 | 825.17 | 1.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.076 | 0.016 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.071 | 0.009 | 0.000 | 0.000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.623 | 0.001 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.973 | 0.016 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.975 | 0.009 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.065 | 0.016 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.061 | 0.009 | 0.000 | 0.000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.619 | 0.001 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.974 | 0.016 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.973 | 0.009 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.070 | 0.016 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.071 | 0.009 | 0.000 | 0.000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.639 | 0.001 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.979 | 0.016 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 45.65 | 84.77 | 1260.00 | 1.980 | 0.009 | 0.000 | 0.000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 38.16 | 43.60 | 648.00 | 2.121 | 0.009 | 0.000 | 0.000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 15.83 | 29.39 | 2184.00 | 0.526 | 0.001 | 0.000 | 0.000 |
| LOBBY_ZN_1_FLR_1 | 9.91 | 18.41 | 684.00 | 1.032 | 2.750 | 0.000 | 0.000 |
| MECH_ZN_1_FLR_1 | 2.19 | 4.07 | 1008.00 | 0.694 | 0.000 | 0.000 | 0.000 |
| BATH_ZN_1_FLR_1 | 5.51 | 10.23 | 760.00 | 0.564 | 0.004 | 0.000 | 0.000 |
| OFFICES_ZN_1_FLR_1 | 14.92 | 23.74 | 1764.00 | 1.037 | 0.007 | 0.000 | 0.000 |
| GYM_ZN_1_FLR_1 | 64.64 | 115.31 | 1428.00 | 1.859 | 0.004 | 0.000 | 0.000 |
| KITCHEN_ZN_1_FLR_1 | 14.54 | 26.99 | 672.00 | 4.888 | 0.004 | 0.000 | 0.000 |
| CAFETERIA_ZN_1_FLR_1 | 209.95 | 339.07 | 1260.00 | 4.838 | 0.009 | 0.000 | 0.000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 23.13 | 42.95 | 1596.00 | 1.249 | 0.008 | 0.000 | 0.000 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.584 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.505 | 0.000 | 0.000 | 0.000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.460 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.305 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.199 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.582 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.466 | 0.000 | 0.000 | 0.000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.459 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.307 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.197 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.584 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.497 | 0.000 | 0.000 | 0.000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.463 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.358 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 45.65 | 84.77 | 1260.00 | 1.198 | 0.000 | 0.000 | 0.000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 38.16 | 43.60 | 648.00 | 1.546 | 0.000 | 0.000 | 0.000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 15.83 | 29.39 | 2184.00 | 0.345 | 0.000 | 0.000 | 0.000 |
| LOBBY_ZN_1_FLR_1 | 9.91 | 18.41 | 684.00 | 0.638 | 0.000 | 0.000 | 0.000 |
| MECH_ZN_1_FLR_1 | 2.19 | 4.07 | 1008.00 | 0.524 | 0.000 | 0.000 | 0.000 |
| BATH_ZN_1_FLR_1 | 5.51 | 10.23 | 760.00 | 0.316 | 0.000 | 0.000 | 0.000 |
| OFFICES_ZN_1_FLR_1 | 14.92 | 23.74 | 1764.00 | 0.630 | 0.000 | 0.000 | 0.000 |
| GYM_ZN_1_FLR_1 | 64.64 | 115.31 | 1428.00 | 1.257 | 0.000 | 0.000 | 0.000 |
| KITCHEN_ZN_1_FLR_1 | 14.54 | 26.99 | 672.00 | 0.000 | 0.000 | 0.000 | 0.000 |
| CAFETERIA_ZN_1_FLR_1 | 209.95 | 339.07 | 1260.00 | 4.177 | 0.000 | 0.000 | 0.000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 23.13 | 42.95 | 1596.00 | 0.732 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 5.56 | 10.33 | 768.00 | 192.00 | 0.0000 | 0.059 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 5.56 | 10.33 | 768.00 | 192.00 | 0.0000 | 0.059 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 5.56 | 10.33 | 768.00 | 192.00 | 0.0000 | 0.059 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 45.65 | 84.77 | 1260.00 | 315.00 | 0.0000 | 0.592 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | 38.16 | 43.60 | 648.00 | 162.00 | 0.0000 | 0.304 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | 15.83 | 29.39 | 2184.00 | 546.00 | 0.0000 | 0.166 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | 9.91 | 18.41 | 684.00 | 171.00 | 0.0000 | 0.096 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | 2.19 | 4.07 | 1008.00 | 252.00 | 0.0000 | 0.000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | 5.51 | 10.23 | 760.00 | 190.00 | 0.0000 | 0.000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | 14.92 | 23.74 | 1764.00 | 441.00 | 0.0000 | 0.190 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | 64.64 | 115.31 | 1428.00 | 357.00 | 0.0000 | 0.544 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | 14.54 | 26.99 | 672.00 | 168.00 | 0.4528 | 0.198 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | 209.95 | 339.07 | 1260.00 | 315.00 | 1.4882 | 1.488 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | 23.13 | 42.95 | 1596.00 | 399.00 | 0.0000 | 0.345 |
| Total Facility | 892.82 | 1571.19 | 27484.00 | 6871.00 | 1.9410 | 9.699 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 2922597.42 | 0.00 | 2922597.42 | 133953.82 | 3056551.23 | 5868225.25 | 6659.36 | 377.94 | 1722.70 | 486.10 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 14044094.11 | 0.00 | 14044094.11 | 354977.61 | 14399071.73 | 28274176.21 | 6713.46 | 327.32 | 1719.22 | 486.10 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 1697338.59 | 0.00 | 1697338.59 | 20093.07 | 1717431.67 | 1845537.18 | 5169.10 | 4.62 | 3586.28 | 486.10 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 2794141.75 | 0.00 | 2794141.75 | 133953.82 | 2928095.57 | 5868225.25 | 6774.79 | 303.92 | 1681.30 | 486.10 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 13477235.49 | 0.00 | 13477235.49 | 354977.61 | 13832213.11 | 28274176.21 | 6708.30 | 366.57 | 1685.13 | 486.10 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 2908818.96 | 0.00 | 2908818.96 | 133953.82 | 3042772.78 | 5868225.25 | 6714.33 | 332.34 | 1713.32 | 486.10 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 13983690.80 | 0.00 | 13983690.80 | 354977.61 | 14338668.41 | 28274176.21 | 6748.62 | 295.92 | 1715.45 | 486.10 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 1688711.59 | 0.00 | 1688711.59 | 20093.07 | 1708804.66 | 1845537.18 | 5169.42 | 5.04 | 3585.55 | 486.10 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 2795455.52 | 0.00 | 2795455.52 | 133953.82 | 2929409.34 | 5868225.25 | 6754.10 | 323.41 | 1682.49 | 486.10 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 13463033.37 | 0.00 | 13463033.37 | 354977.61 | 13818010.98 | 28274176.21 | 6762.71 | 316.46 | 1680.83 | 486.10 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 2915635.19 | 0.00 | 2915635.19 | 133953.82 | 3049589.01 | 5868225.25 | 6679.89 | 361.72 | 1718.39 | 486.10 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 14046360.22 | 0.00 | 14046360.22 | 354977.61 | 14401337.84 | 28274176.21 | 6664.49 | 372.13 | 1723.38 | 486.10 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 1738169.72 | 0.00 | 1738169.72 | 20093.07 | 1758262.79 | 1845537.18 | 5167.52 | 5.61 | 3586.87 | 486.10 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 2802470.01 | 0.00 | 2802470.01 | 133953.82 | 2936423.82 | 5868225.25 | 6729.96 | 342.16 | 1687.88 | 486.10 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 8917611.40 | 0.00 | 8917611.40 | 234419.18 | 9152030.58 | 18671625.80 | 6755.48 | 319.94 | 1684.57 | 486.10 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 4862940.20 | 0.00 | 4862940.20 | 120558.43 | 4983498.64 | 9602550.41 | 6649.36 | 337.79 | 1772.86 | 486.10 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 4023538.73 | 0.00 | 4023538.73 | 60279.22 | 4083817.95 | 5248246.35 | 5234.18 | 4.57 | 3521.25 | 486.10 |
| LOBBY_ZN_1_FLR_1 | 2558196.72 | 0.00 | 2558196.72 | 9125807.31 | 11684004.02 | 3013410.78 | 5118.06 | 3.22 | 3638.72 | 486.10 |
| MECH_ZN_1_FLR_1 | 2487852.71 | 0.00 | 2487852.71 | 0.00 | 2487852.71 | 0.00 | 0.00 | 0.00 | 3762.10 | 486.10 |
| BATH_ZN_1_FLR_1 | 1529200.07 | 0.00 | 1529200.07 | 66976.91 | 1596176.97 | 0.00 | 0.00 | 0.00 | 3762.10 | 486.10 |
| OFFICES_ZN_1_FLR_1 | 6023092.82 | 0.00 | 6023092.82 | 281303.01 | 6304395.84 | 6005204.96 | 5447.84 | 6.21 | 3305.95 | 754.94 |
| GYM_ZN_1_FLR_1 | 9337604.92 | 0.00 | 9337604.92 | 113860.74 | 9451465.67 | 17157717.19 | 6574.39 | 302.34 | 1883.27 | 486.10 |
| KITCHEN_ZN_1_FLR_1 | 12777474.95 | 0.00 | 12777474.95 | 53581.53 | 12831056.48 | 6482703.52 | 4404.21 | 19.29 | 4336.50 | 2724.88 |
| CAFETERIA_ZN_1_FLR_1 | 19576678.40 | 0.00 | 19576678.40 | 241116.87 | 19817795.27 | 46931384.03 | 5482.04 | 2508.63 | 769.33 | 725.78 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 6914522.77 | 0.00 | 6914522.77 | 267907.63 | 7182430.41 | 10866548.77 | 6448.02 | 312.60 | 1999.38 | 486.10 |
| Total Facility | 0.17E+09 | 0.00 | 0.17E+09 | 13204701.01 | 0.18E+09 | 0.31E+09 | 7171.61 | 2562.42 | 4485.53 | 3651.33 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.2251 | 0.0000 | 0.2251 | 0.0017 | 0.2268 | 0.1861 | 1368.35 | 372.34 | 1535.32 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.0816 | 0.0000 | 1.0816 | 0.0046 | 1.0862 | 0.8966 | 1422.18 | 321.57 | 1532.25 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 0.1310 | 0.0000 | 0.1310 | 0.0003 | 0.1312 | 0.0585 | 0.00 | 0.00 | 3276.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.2143 | 0.0000 | 0.2143 | 0.0017 | 0.2160 | 0.1861 | 1483.45 | 298.10 | 1494.45 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.0335 | 0.0000 | 1.0335 | 0.0046 | 1.0380 | 0.8966 | 1417.15 | 360.92 | 1497.93 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.2239 | 0.0000 | 0.2239 | 0.0017 | 0.2257 | 0.1861 | 1423.06 | 326.59 | 1526.35 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.0766 | 0.0000 | 1.0766 | 0.0046 | 1.0811 | 0.8966 | 1457.29 | 290.10 | 1528.61 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 0.1303 | 0.0000 | 0.1303 | 0.0003 | 0.1305 | 0.0585 | 0.00 | 0.00 | 3276.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.2144 | 0.0000 | 0.2144 | 0.0017 | 0.2161 | 0.1861 | 1462.80 | 317.67 | 1495.54 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.0324 | 0.0000 | 1.0324 | 0.0046 | 1.0370 | 0.8966 | 1471.41 | 310.64 | 1493.95 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.2245 | 0.0000 | 0.2245 | 0.0017 | 0.2262 | 0.1861 | 1388.72 | 356.08 | 1531.20 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.0817 | 0.0000 | 1.0817 | 0.0046 | 1.0862 | 0.8966 | 1373.44 | 366.56 | 1536.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 0.1344 | 0.0000 | 0.1344 | 0.0003 | 0.1346 | 0.0585 | 0.00 | 0.00 | 3276.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.2150 | 0.0000 | 0.2150 | 0.0017 | 0.2167 | 0.1861 | 1438.68 | 336.41 | 1500.91 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.6841 | 0.0000 | 0.6841 | 0.0030 | 0.6871 | 0.5921 | 1464.19 | 314.20 | 1497.62 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 0.3752 | 0.0000 | 0.3752 | 0.0015 | 0.3768 | 0.3045 | 1358.13 | 331.99 | 1585.88 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 0.3140 | 0.0000 | 0.3140 | 0.0008 | 0.3148 | 0.1664 | 0.00 | 0.00 | 3276.00 |
| LOBBY_ZN_1_FLR_1 | 0.1949 | 0.0000 | 0.1949 | 0.5221 | 0.7170 | 0.0956 | 0.00 | 0.00 | 3276.00 |
| MECH_ZN_1_FLR_1 | 0.1903 | 0.0000 | 0.1903 | 0.0000 | 0.1903 | 0.0000 | 0.00 | 0.00 | 3276.00 |
| BATH_ZN_1_FLR_1 | 0.1171 | 0.0000 | 0.1171 | 0.0009 | 0.1180 | 0.0000 | 0.00 | 0.00 | 3276.00 |
| OFFICES_ZN_1_FLR_1 | 0.5000 | 0.0000 | 0.5000 | 0.0035 | 0.5035 | 0.1904 | 0.00 | 0.00 | 2772.00 |
| GYM_ZN_1_FLR_1 | 0.7247 | 0.0000 | 0.7247 | 0.0015 | 0.7261 | 0.5441 | 1283.70 | 296.63 | 1695.67 |
| KITCHEN_ZN_1_FLR_1 | 0.8928 | 0.0000 | 0.8928 | 0.0007 | 0.8935 | 0.2182 | 7.02 | 2.15 | 3266.83 |
| CAFETERIA_ZN_1_FLR_1 | 1.6658 | 0.0000 | 1.6658 | 0.0032 | 1.6689 | 1.4882 | 0.00 | 1970.05 | 757.95 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.5442 | 0.0000 | 0.5442 | 0.0034 | 0.5476 | 0.3446 | 1156.87 | 306.94 | 1812.18 |
| Total Facility | 13.2215 | 0.0000 | 13.2215 | 0.5745 | 13.7960 | 9.7189 | 1689.05 | 2517.38 | 3276.00 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| VAV_POD_1 | 0.20E+09 | 0.00 | 0.20E+09 | 0.25E+09 | 5212.23 | 7.02 | 3540.74 | 486.10 |
| PSZ-AC_1:6 | 18135929.72 | 0.00 | 18135929.72 | 6482703.52 | 4087.46 | 18.67 | 4653.86 | 2724.88 |
| PSZ-AC_2:7 | 27786498.14 | 0.00 | 27786498.14 | 46931384.03 | 5473.10 | 0.32 | 3286.58 | 725.69 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| VAV_POD_1 | 15.0926 | 0.0000 | 15.0926 | 8.0125 | 0.00 | 0.00 | 3276.00 |
| PSZ-AC_1:6 | 1.2672 | 0.0000 | 1.2672 | 0.2182 | 5.17 | 0.00 | 3270.83 |
| PSZ-AC_2:7 | 2.3644 | 0.0000 | 2.3644 | 1.4882 | 0.00 | 0.00 | 2728.00 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| VAV_POD_1 | 0.00 | 34.77 | 3606.40 | 20.50 | 0.00 | 0.00 | 100.44 | 0.00 | 0.00 | 0.00 |
| PSZ-AC_1:6 | 0.00 | 37.83 | 4016.62 | 1941.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| PSZ-AC_2:7 | 0.00 | 2498.05 | 895.81 | 59.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| VAV_POD_1 | 0.0000 | 15.8492 | 15.1763 | 0.0000 | 0.0000 | 0.0000 | 12.5107 | 0.0000 | 0.0000 | 0.0000 |
| PSZ-AC_1:6 | 0.0000 | 0.3698 | 1.2798 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| PSZ-AC_2:7 | 0.0000 | 2.1131 | 3.0084 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Surfaces by Class| Total | Outdoors | |
| Wall | 121 | 33 |
| Floor | 25 | 24 |
| Roof | 25 | 25 |
| Internal Mass | 25 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 67 | 67 |
| Door | 25 | 25 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 3 |
| Conditioned Zones | 25 |
| Unconditioned Zones | 0 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1159 |
| Defaulted Fields | 890 |
| Fields with Defaults | 3720 |
| Autosized Fields | 267 |
| Autosizable Fields | 376 |
| Autocalculated Fields | 317 |
| Autocalculatable Fields | 632 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 2926.99 | 36874.62 | 01-JUL-10:30 | 307898.07 | 13-JUN-14:00 |
| Electricity:Building | 2377.40 | 35841.46 | 01-JUL-10:30 | 158543.84 | 02-JAN-11:10 |
| Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| Electricity:SpaceType:GENERAL | 2369.55 | 35741.12 | 30-JUN-23:10 | 156371.25 | 02-JAN-10:10 |
| InteriorLights:Electricity | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 24.39 | 336.28 | 30-JUN-23:10 | 1626.10 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 24.39 | 336.28 | 30-JUN-23:10 | 1626.10 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 24.39 | 336.28 | 30-JUN-23:10 | 1626.10 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 126.22 | 1762.63 | 30-JUN-23:10 | 8449.51 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 65.42 | 841.62 | 01-JAN-00:10 | 4272.19 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 65.42 | 841.62 | 01-JAN-00:10 | 4272.19 | 02-JAN-07:10 |
| Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 75.34 | 1064.38 | 30-JUN-23:10 | 5061.57 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 33.64 | 432.83 | 01-JAN-00:10 | 2197.13 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 33.64 | 432.83 | 01-JAN-00:10 | 2197.13 | 02-JAN-07:10 |
| Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 69.34 | 956.30 | 30-JUN-23:10 | 4624.21 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 41.24 | 530.59 | 01-JAN-00:10 | 2693.36 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 41.24 | 530.59 | 01-JAN-00:10 | 2693.36 | 02-JAN-07:10 |
| Electricity:Zone:LOBBY_ZN_1_FLR_1 | 41.78 | 557.57 | 30-JUN-23:10 | 2758.25 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 32.98 | 424.25 | 01-JAN-00:10 | 2153.53 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 32.98 | 424.25 | 01-JAN-00:10 | 2153.53 | 02-JAN-07:10 |
| Electricity:Zone:MECH_ZN_1_FLR_1 | 88.50 | 1212.59 | 30-JUN-23:10 | 5889.78 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MECH_ZN_1_FLR_1 | 56.07 | 721.39 | 01-JAN-00:10 | 3661.88 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MECH_ZN_1_FLR_1 | 56.07 | 721.39 | 01-JAN-00:10 | 3661.88 | 02-JAN-07:10 |
| Electricity:Zone:BATH_ZN_1_FLR_1 | 35.15 | 474.48 | 30-JUN-23:10 | 2328.47 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:BATH_ZN_1_FLR_1 | 25.37 | 326.34 | 01-JAN-00:10 | 1656.56 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:BATH_ZN_1_FLR_1 | 25.37 | 326.34 | 01-JAN-00:10 | 1656.56 | 02-JAN-07:10 |
| Electricity:Zone:OFFICES_ZN_1_FLR_1 | 133.25 | 1854.16 | 30-JUN-23:10 | 8910.14 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 71.96 | 925.78 | 01-JAN-00:10 | 4699.41 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 71.96 | 925.78 | 01-JAN-00:10 | 4699.41 | 02-JAN-07:10 |
| Electricity:Zone:GYM_ZN_1_FLR_1 | 88.64 | 1192.76 | 30-JUN-23:10 | 5866.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:GYM_ZN_1_FLR_1 | 65.67 | 844.83 | 01-JAN-00:10 | 4288.47 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:GYM_ZN_1_FLR_1 | 65.67 | 844.83 | 01-JAN-00:10 | 4288.47 | 02-JAN-07:10 |
| Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 211.64 | 5400.64 | 01-JAN-11:30 | 13840.49 | 02-JAN-11:10 |
| InteriorLights:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 29.90 | 384.74 | 01-JAN-00:10 | 1953.00 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 29.90 | 384.74 | 01-JAN-00:10 | 1953.00 | 02-JAN-07:10 |
| Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 71.99 | 1340.83 | 01-JAN-00:10 | 4745.87 | 02-JAN-10:10 |
| InteriorLights:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 42.05 | 541.04 | 01-JAN-00:10 | 2746.41 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 42.05 | 541.04 | 01-JAN-00:10 | 2746.41 | 02-JAN-07:10 |
| Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 168.75 | 2346.88 | 30-JUN-23:10 | 11282.50 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 91.74 | 1180.27 | 01-JAN-00:10 | 5991.24 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 91.74 | 1180.27 | 01-JAN-00:10 | 5991.24 | 02-JAN-07:10 |
| InteriorEquipment:Electricity | 1151.36 | 20068.34 | 30-JUN-23:10 | 76813.98 | 02-JAN-10:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 1151.36 | 20068.34 | 30-JUN-23:10 | 76813.98 | 02-JAN-10:10 |
| MiscPlug:InteriorEquipment:Electricity | 947.54 | 14352.99 | 30-JUN-23:10 | 65099.62 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 947.54 | 14352.99 | 30-JUN-23:10 | 65099.62 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 60.80 | 921.00 | 30-JUN-23:10 | 4177.31 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 60.80 | 921.00 | 30-JUN-23:10 | 4177.31 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 41.69 | 631.55 | 30-JUN-23:10 | 2864.44 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 41.69 | 631.55 | 30-JUN-23:10 | 2864.44 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 28.10 | 425.71 | 30-JUN-23:10 | 1930.85 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 28.10 | 425.71 | 30-JUN-23:10 | 1930.85 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 8.80 | 133.33 | 30-JUN-23:10 | 604.72 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 8.80 | 133.33 | 30-JUN-23:10 | 604.72 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MECH_ZN_1_FLR_1 | 32.43 | 491.20 | 30-JUN-23:10 | 2227.90 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MECH_ZN_1_FLR_1 | 32.43 | 491.20 | 30-JUN-23:10 | 2227.90 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:BATH_ZN_1_FLR_1 | 9.78 | 148.14 | 30-JUN-23:10 | 671.91 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:BATH_ZN_1_FLR_1 | 9.78 | 148.14 | 30-JUN-23:10 | 671.91 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 61.29 | 928.37 | 30-JUN-23:10 | 4210.73 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 61.29 | 928.37 | 30-JUN-23:10 | 4210.73 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GYM_ZN_1_FLR_1 | 22.97 | 347.93 | 30-JUN-23:10 | 1578.10 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GYM_ZN_1_FLR_1 | 22.97 | 347.93 | 30-JUN-23:10 | 1578.10 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 173.88 | 4915.56 | 01-JAN-00:10 | 9714.90 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity | 149.71 | 3999.34 | 01-JAN-00:10 | 9998.36 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 119.77 | 3199.56 | 01-JAN-00:10 | 7998.90 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 149.71 | 3999.34 | 01-JAN-00:10 | 9998.36 | 02-JAN-10:10 |
| ReachInFreezer:InteriorEquipment:Electricity | 31.09 | 986.00 | 01-JAN-00:10 | 986.00 | 01-JAN-00:10 |
| ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 31.09 | 986.00 | 01-JAN-00:10 | 986.00 | 01-JAN-00:10 |
| ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 31.09 | 986.00 | 01-JAN-00:10 | 986.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 29.94 | 799.79 | 01-JAN-00:10 | 1999.46 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 29.94 | 799.79 | 01-JAN-00:10 | 1999.46 | 02-JAN-10:10 |
| InteriorEquipment:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 77.02 | 1166.60 | 30-JUN-23:10 | 5291.26 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 77.02 | 1166.60 | 30-JUN-23:10 | 5291.26 | 02-JAN-08:10 |
| Refrigeration:Electricity | 44.99 | 754.51 | 22-JUL-22:30 | 2907.46 | 09-JAN-11:10 |
| Refrigeration:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 7.85 | 100.34 | 01-JAN-11:30 | 2172.58 | 02-JAN-11:10 |
| General:Refrigeration:Electricity | 7.85 | 100.34 | 01-JAN-11:30 | 2172.58 | 02-JAN-11:10 |
| General:Refrigeration:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 7.85 | 100.34 | 01-JAN-11:30 | 2172.58 | 02-JAN-11:10 |
| Electricity:Plant | 38.16 | 654.17 | 22-JUL-22:30 | 2398.47 | 02-JAN-11:40 |
| LowTempRefrigeration:Refrigeration:Electricity | 15.13 | 0.00 | 01-JAN-11:10 | 1474.01 | 07-MAY-10:50 |
| MedTempRefrigeration:Refrigeration:Electricity | 22.01 | 631.67 | 29-DEC-21:10 | 734.88 | 01-JAN-07:10 |
| Electricity:HVAC | 418.94 | 321.20 | 02-JUL-13:50 | 154123.62 | 13-JUN-14:00 |
| ExteriorEquipment:Electricity | 17.61 | 321.20 | 01-JUL-10:00 | 1336.02 | 02-JAN-10:10 |
| Transformer:ExteriorEquipment:Electricity | 17.61 | 321.20 | 01-JUL-10:00 | 1336.02 | 02-JAN-10:10 |
| ElectricityPurchased:Facility | 2926.99 | 36874.62 | 01-JUL-10:30 | 307898.07 | 13-JUN-14:00 |
| ElectricityPurchased:Plant | 2926.99 | 36874.62 | 01-JUL-10:30 | 307898.07 | 13-JUN-14:00 |
| Cogeneration:ElectricityPurchased | 2926.99 | 36874.62 | 01-JUL-10:30 | 307898.07 | 13-JUN-14:00 |
| General:Cogeneration:ElectricityPurchased | 2926.99 | 36874.62 | 01-JUL-10:30 | 307898.07 | 13-JUN-14:00 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 2926.99 | 36874.62 | 01-JUL-10:30 | 307898.07 | 13-JUN-14:00 |
| ElectricityNet:Plant | 2926.99 | 36874.62 | 01-JUL-10:30 | 307898.07 | 13-JUN-14:00 |
| Cogeneration:ElectricityNet | 2926.99 | 36874.62 | 01-JUL-10:30 | 307898.07 | 13-JUN-14:00 |
| General:Cogeneration:ElectricityNet | 2926.99 | 36874.62 | 01-JUL-10:30 | 307898.07 | 13-JUN-14:00 |
| Fans:Electricity | 316.71 | 0.00 | 01-JAN-00:10 | 49898.17 | 13-JUN-12:30 |
| General:Fans:Electricity | 316.71 | 0.00 | 01-JAN-00:10 | 49898.17 | 13-JUN-12:30 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 84.62 | 0.00 | 01-JAN-00:10 | 110242.31 | 13-JUN-14:10 |
| General:Cooling:Electricity | 84.62 | 0.00 | 01-JAN-00:10 | 110242.31 | 13-JUN-14:10 |
| ExteriorLights:Electricity | 92.49 | 0.00 | 01-JAN-08:20 | 5897.73 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 92.49 | 0.00 | 01-JAN-08:20 | 5897.73 | 01-JAN-00:10 |
| Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Pumps:Electricity | 1.02 | 0.00 | 01-JAN-00:10 | 730.25 | 02-JAN-07:30 |
| General:Pumps:Electricity | 1.02 | 0.00 | 01-JAN-00:10 | 730.25 | 02-JAN-07:30 |
| WIRED_LTG_ELECTRICITY | 14.50 | 0.00 | 01-JAN-00:10 | 946.73 | 02-JAN-07:20 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 1232.76 | 4866.92 | 22-JUL-10:50 | 532733.68 | 10-JAN-08:10 |
| NaturalGas:Building | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| NaturalGas:SpaceType:GENERAL | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| InteriorEquipment:NaturalGas | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| InteriorEquipment:NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| InteriorEquipment:NaturalGas:SpaceType:GENERAL | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:NaturalGas | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| NaturalGas:HVAC | 445.33 | 0.00 | 01-JAN-00:10 | 271403.51 | 10-JAN-08:10 |
| Heating:NaturalGas | 712.55 | 0.00 | 01-JAN-00:10 | 484969.97 | 10-JAN-08:10 |
| General:Heating:NaturalGas | 445.33 | 0.00 | 01-JAN-00:10 | 271403.51 | 10-JAN-08:10 |
| NaturalGas:Plant | 426.40 | 58.43 | 22-JUL-10:50 | 348768.96 | 02-JAN-07:20 |
| WaterSystems:NaturalGas | 159.18 | 58.43 | 22-JUL-10:50 | 29843.74 | 14-FEB-13:20 |
| Water Heater:WaterSystems:NaturalGas | 159.18 | 58.43 | 22-JUL-10:50 | 29843.74 | 14-FEB-13:20 |
| Boiler:Heating:NaturalGas | 267.21 | 0.00 | 01-JAN-00:10 | 348041.55 | 02-JAN-07:20 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Water:Plant | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| WaterSystems:Water | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Water Heater:WaterSystems:Water | 268.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| MainsWater:Facility | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| MainsWater:Plant | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| WaterSystems:MainsWater | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Water Heater:WaterSystems:MainsWater | 268.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| WaterUse:WaterSystems:Water | 449.48 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-14:00 |
| WaterUse:WaterSystems:MainsWater | 449.48 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-14:00 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 3028.36 | 4246.16 | 22-JUL-22:30 | 768274.90 | 02-JAN-07:20 |
| EnergyTransfer:Building | 1827.02 | 2123.08 | 22-JUL-22:30 | 302865.71 | 13-JUN-14:00 |
| EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 253.28 | 2123.08 | 22-JUL-22:30 | 27309.84 | 13-JUN-10:50 |
| Refrigeration:EnergyTransfer | 189.35 | 4246.16 | 22-JUL-22:30 | 10745.76 | 01-JAN-11:40 |
| Refrigeration:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 94.67 | 2123.08 | 22-JUL-22:30 | 5372.88 | 01-JAN-11:40 |
| General:Refrigeration:EnergyTransfer | 94.67 | 2123.08 | 22-JUL-22:30 | 5372.88 | 01-JAN-11:40 |
| General:Refrigeration:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 94.67 | 2123.08 | 22-JUL-22:30 | 5372.88 | 01-JAN-11:40 |
| EnergyTransfer:Plant | 362.07 | 2123.08 | 22-JUL-22:30 | 263445.26 | 02-JAN-07:20 |
| LowTempRefrigeration:Refrigeration:EnergyTransfer | 18.05 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
| MedTempRefrigeration:Refrigeration:EnergyTransfer | 76.62 | 1966.04 | 29-DEC-21:10 | 2686.44 | 01-JAN-07:10 |
| EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 27.77 | 0.00 | 01-JAN-00:10 | 6019.76 | 13-JUN-15:00 |
| Heating:EnergyTransfer | 72.60 | 0.00 | 01-JAN-00:10 | 231885.03 | 02-JAN-07:20 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.76 | 0.00 | 01-JAN-00:10 | 5022.20 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer | 72.60 | 0.00 | 01-JAN-00:10 | 231885.03 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.76 | 0.00 | 01-JAN-00:10 | 5022.20 | 02-JAN-07:20 |
| Cooling:EnergyTransfer | 1659.75 | 0.00 | 01-JAN-00:10 | 299831.05 | 13-JUN-14:00 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 27.01 | 0.00 | 01-JAN-00:10 | 6019.76 | 13-JUN-15:00 |
| General:Cooling:EnergyTransfer | 1659.75 | 0.00 | 01-JAN-00:10 | 299831.05 | 13-JUN-14:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 27.01 | 0.00 | 01-JAN-00:10 | 6019.76 | 13-JUN-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 142.32 | 0.00 | 01-JAN-00:10 | 26299.41 | 25-SEP-13:50 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.03 | 0.00 | 01-JAN-00:10 | 18576.49 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.03 | 0.00 | 01-JAN-00:10 | 18576.49 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 141.30 | 0.00 | 01-JAN-00:10 | 26299.41 | 25-SEP-13:50 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 141.30 | 0.00 | 01-JAN-00:10 | 26299.41 | 25-SEP-13:50 |
| EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 17.29 | 0.00 | 01-JAN-00:10 | 5348.59 | 02-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 1.99 | 0.00 | 01-JAN-00:10 | 5348.59 | 02-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 1.99 | 0.00 | 01-JAN-00:10 | 5348.59 | 02-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 15.30 | 0.00 | 01-JAN-00:10 | 4677.48 | 13-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 15.30 | 0.00 | 01-JAN-00:10 | 4677.48 | 13-JUN-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 23.70 | 0.00 | 01-JAN-00:10 | 5079.50 | 13-JUN-15:00 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1.23 | 0.00 | 01-JAN-00:10 | 5048.91 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1.23 | 0.00 | 01-JAN-00:10 | 5048.91 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 22.47 | 0.00 | 01-JAN-00:10 | 5079.50 | 13-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 22.47 | 0.00 | 01-JAN-00:10 | 5079.50 | 13-JUN-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 121.84 | 0.00 | 01-JAN-00:10 | 20484.52 | 13-JUN-15:00 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.83 | 0.00 | 01-JAN-00:10 | 18900.15 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.83 | 0.00 | 01-JAN-00:10 | 18900.15 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 120.01 | 0.00 | 01-JAN-00:10 | 20484.52 | 13-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 120.01 | 0.00 | 01-JAN-00:10 | 20484.52 | 13-JUN-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 27.40 | 0.00 | 01-JAN-00:10 | 5923.20 | 13-JUN-15:00 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.81 | 0.00 | 01-JAN-00:10 | 5163.00 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.81 | 0.00 | 01-JAN-00:10 | 5163.00 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 26.59 | 0.00 | 01-JAN-00:10 | 5923.20 | 13-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 26.59 | 0.00 | 01-JAN-00:10 | 5923.20 | 13-JUN-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 140.66 | 0.00 | 01-JAN-00:10 | 25740.21 | 25-SEP-13:50 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.05 | 0.00 | 01-JAN-00:10 | 18574.73 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.05 | 0.00 | 01-JAN-00:10 | 18574.73 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 139.61 | 0.00 | 01-JAN-00:10 | 25740.21 | 25-SEP-13:50 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 139.61 | 0.00 | 01-JAN-00:10 | 25740.21 | 25-SEP-13:50 |
| EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 17.21 | 0.00 | 01-JAN-00:10 | 5346.80 | 02-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 2.07 | 0.00 | 01-JAN-00:10 | 5346.80 | 02-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 2.07 | 0.00 | 01-JAN-00:10 | 5346.80 | 02-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 15.13 | 0.00 | 01-JAN-00:10 | 4635.94 | 13-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 15.13 | 0.00 | 01-JAN-00:10 | 4635.94 | 13-JUN-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 23.70 | 0.00 | 01-JAN-00:10 | 5084.88 | 13-JUN-15:00 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1.23 | 0.00 | 01-JAN-00:10 | 5054.22 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1.23 | 0.00 | 01-JAN-00:10 | 5054.22 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 22.47 | 0.00 | 01-JAN-00:10 | 5084.88 | 13-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 22.47 | 0.00 | 01-JAN-00:10 | 5084.88 | 13-JUN-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 121.77 | 0.00 | 01-JAN-00:10 | 20512.31 | 13-JUN-15:00 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.84 | 0.00 | 01-JAN-00:10 | 18912.29 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.84 | 0.00 | 01-JAN-00:10 | 18912.29 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 119.92 | 0.00 | 01-JAN-00:10 | 20512.31 | 13-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 119.92 | 0.00 | 01-JAN-00:10 | 20512.31 | 13-JUN-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 27.65 | 0.00 | 01-JAN-00:10 | 5948.60 | 13-JUN-15:00 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.77 | 0.00 | 01-JAN-00:10 | 5122.90 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.77 | 0.00 | 01-JAN-00:10 | 5122.90 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 26.88 | 0.00 | 01-JAN-00:10 | 5948.60 | 13-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 26.88 | 0.00 | 01-JAN-00:10 | 5948.60 | 13-JUN-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 142.73 | 0.00 | 01-JAN-00:10 | 26025.89 | 25-SEP-13:50 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 0.99 | 0.00 | 01-JAN-00:10 | 18589.39 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 0.99 | 0.00 | 01-JAN-00:10 | 18589.39 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 141.74 | 0.00 | 01-JAN-00:10 | 26025.89 | 25-SEP-13:50 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 141.74 | 0.00 | 01-JAN-00:10 | 26025.89 | 25-SEP-13:50 |
| EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 18.03 | 0.00 | 01-JAN-00:10 | 5368.53 | 02-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 1.81 | 0.00 | 01-JAN-00:10 | 5368.53 | 02-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 1.81 | 0.00 | 01-JAN-00:10 | 5368.53 | 02-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 16.21 | 0.00 | 01-JAN-00:10 | 4811.42 | 13-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 16.21 | 0.00 | 01-JAN-00:10 | 4811.42 | 13-JUN-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 24.12 | 0.00 | 01-JAN-00:10 | 5198.51 | 13-JUN-15:00 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1.21 | 0.00 | 01-JAN-00:10 | 5073.60 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1.21 | 0.00 | 01-JAN-00:10 | 5073.60 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 22.91 | 0.00 | 01-JAN-00:10 | 5198.51 | 13-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 22.91 | 0.00 | 01-JAN-00:10 | 5198.51 | 13-JUN-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 82.16 | 0.00 | 01-JAN-00:10 | 14085.38 | 13-JUN-15:00 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1.23 | 0.00 | 01-JAN-00:10 | 12688.89 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1.23 | 0.00 | 01-JAN-00:10 | 12688.89 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 80.93 | 0.00 | 01-JAN-00:10 | 14085.38 | 13-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 80.93 | 0.00 | 01-JAN-00:10 | 14085.38 | 13-JUN-15:00 |
| EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 54.29 | 0.00 | 01-JAN-00:10 | 8176.78 | 13-JUN-15:00 |
| Heating:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 0.34 | 0.00 | 01-JAN-00:10 | 6200.98 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 0.34 | 0.00 | 01-JAN-00:10 | 6200.98 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 53.96 | 0.00 | 01-JAN-00:10 | 8176.78 | 13-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 53.96 | 0.00 | 01-JAN-00:10 | 8176.78 | 13-JUN-15:00 |
| EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 43.53 | 0.00 | 01-JAN-00:10 | 12398.79 | 13-JUN-15:00 |
| Heating:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 5.19 | 0.00 | 01-JAN-00:10 | 11972.96 | 02-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 5.19 | 0.00 | 01-JAN-00:10 | 11972.96 | 02-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 38.34 | 0.00 | 01-JAN-00:10 | 12398.79 | 13-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 38.34 | 0.00 | 01-JAN-00:10 | 12398.79 | 13-JUN-15:00 |
| EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 48.45 | 0.00 | 01-JAN-00:10 | 12877.03 | 10-JAN-08:00 |
| Heating:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 39.75 | 0.00 | 01-JAN-00:10 | 12877.03 | 10-JAN-08:00 |
| General:Heating:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 39.75 | 0.00 | 01-JAN-00:10 | 12877.03 | 10-JAN-08:00 |
| Cooling:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 8.70 | 0.00 | 01-JAN-00:10 | 9909.35 | 21-JUL-14:20 |
| General:Cooling:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 8.70 | 0.00 | 01-JAN-00:10 | 9909.35 | 21-JUL-14:20 |
| EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 34.73 | 0.00 | 01-JAN-00:10 | 5658.28 | 13-JUN-14:10 |
| Heating:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 34.73 | 0.00 | 01-JAN-00:10 | 5658.28 | 13-JUN-14:10 |
| General:Cooling:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 34.73 | 0.00 | 01-JAN-00:10 | 5658.28 | 13-JUN-14:10 |
| EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 16.78 | 0.00 | 01-JAN-00:10 | 2982.29 | 13-JUN-15:00 |
| Heating:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 1653.31 | 01-JAN-01:40 |
| General:Heating:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 0.05 | 0.00 | 01-JAN-00:10 | 1653.31 | 01-JAN-01:40 |
| Cooling:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 16.73 | 0.00 | 01-JAN-00:10 | 2982.29 | 13-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 16.73 | 0.00 | 01-JAN-00:10 | 2982.29 | 13-JUN-15:00 |
| EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 66.17 | 0.00 | 01-JAN-00:10 | 17670.44 | 13-JUN-14:10 |
| Heating:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 2.01 | 0.00 | 01-JAN-00:10 | 14868.89 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 2.01 | 0.00 | 01-JAN-00:10 | 14868.89 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 64.16 | 0.00 | 01-JAN-00:10 | 17670.44 | 13-JUN-14:10 |
| General:Cooling:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 64.16 | 0.00 | 01-JAN-00:10 | 17670.44 | 13-JUN-14:10 |
| EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 105.48 | 0.00 | 01-JAN-00:10 | 19041.78 | 13-JUN-15:40 |
| Heating:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 0.94 | 0.00 | 01-JAN-00:10 | 12794.75 | 02-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 0.94 | 0.00 | 01-JAN-00:10 | 12794.75 | 02-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 104.54 | 0.00 | 01-JAN-00:10 | 19041.78 | 13-JUN-15:40 |
| General:Cooling:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 104.54 | 0.00 | 01-JAN-00:10 | 19041.78 | 13-JUN-15:40 |
| Heating:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 542.01 | 10-NOV-07:10 |
| General:Heating:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 542.01 | 10-NOV-07:10 |
| Cooling:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 158.60 | 0.00 | 01-JAN-00:10 | 22226.97 | 13-JUN-10:50 |
| General:Cooling:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 158.60 | 0.00 | 01-JAN-00:10 | 22226.97 | 13-JUN-10:50 |
| EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 165.82 | 0.00 | 01-JAN-00:10 | 27926.96 | 13-JUN-12:00 |
| Heating:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 3.53 | 0.00 | 01-JAN-00:10 | 23120.51 | 02-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 3.53 | 0.00 | 01-JAN-00:10 | 23120.51 | 02-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 162.28 | 0.00 | 01-JAN-00:10 | 27926.96 | 13-JUN-12:00 |
| General:Cooling:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 162.28 | 0.00 | 01-JAN-00:10 | 27926.96 | 13-JUN-12:00 |
| EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 80.14 | 0.00 | 01-JAN-00:10 | 17336.47 | 13-JUN-14:20 |
| Heating:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.91 | 0.00 | 01-JAN-00:10 | 13767.50 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.91 | 0.00 | 01-JAN-00:10 | 13767.50 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 79.22 | 0.00 | 01-JAN-00:10 | 17336.47 | 13-JUN-14:20 |
| General:Cooling:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 79.22 | 0.00 | 01-JAN-00:10 | 17336.47 | 13-JUN-14:20 |
| PlantLoopHeatingDemand:Facility | 269.07 | 0.00 | 01-JAN-00:10 | 260604.07 | 02-JAN-07:30 |
| PlantLoopHeatingDemand:Plant | 90.10 | 0.00 | 01-JAN-00:10 | 18293.92 | 14-FEB-13:20 |
| WaterSystems:PlantLoopHeatingDemand | 90.10 | 0.00 | 01-JAN-00:10 | 18293.92 | 14-FEB-13:20 |
| General:WaterSystems:PlantLoopHeatingDemand | 90.10 | 0.00 | 01-JAN-00:10 | 18293.92 | 14-FEB-13:20 |
| EnergyTransfer:HVAC | 839.27 | 0.00 | 01-JAN-00:10 | 441079.66 | 13-JUN-14:10 |
| HeatingCoils:EnergyTransfer | 531.90 | 0.00 | 01-JAN-00:10 | 374132.83 | 10-JAN-08:10 |
| PlantLoopHeatingDemand:HVAC | 178.97 | 0.00 | 01-JAN-00:10 | 260604.07 | 02-JAN-07:30 |
| HeatingCoils:PlantLoopHeatingDemand | 178.97 | 0.00 | 01-JAN-00:10 | 260604.07 | 02-JAN-07:30 |
| CoolingCoils:EnergyTransfer | 307.37 | 0.00 | 01-JAN-00:10 | 441079.66 | 13-JUN-14:10 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:EnergyTransfer | 90.10 | 0.00 | 01-JAN-00:10 | 18293.92 | 14-FEB-13:20 |
| WaterUse:WaterSystems:EnergyTransfer | 90.10 | 0.00 | 01-JAN-00:10 | 18293.92 | 14-FEB-13:20 |
| Boilers:EnergyTransfer | 177.30 | 0.00 | 01-JAN-00:10 | 260261.15 | 02-JAN-07:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 0.765 | -27.006 | 0.000 | 0.000 | 12.477 | 20.559 | 19.109 | 14.132 | 0.000 | 0.001 | 0.000 | 0.000 | -11.935 | 0.000 | -1.912 | -26.190 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 1.028 | -141.297 | 0.000 | 0.000 | 58.942 | 99.059 | 92.071 | 43.377 | 0.000 | 0.005 | 0.000 | 0.000 | -33.934 | 0.000 | -5.391 | -113.859 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 1.991 | -15.297 | 0.000 | 0.000 | 4.901 | 14.502 | 9.883 | 1.754 | 0.000 | 0.000 | 0.000 | 0.000 | -1.967 | 0.000 | -0.297 | -15.471 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 1.228 | -22.470 | 0.000 | 0.000 | 12.750 | 20.559 | 19.109 | 6.627 | 0.000 | 0.002 | 0.000 | 0.000 | -11.584 | 0.000 | -1.792 | -24.430 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 1.829 | -120.013 | 0.000 | 0.000 | 60.350 | 99.059 | 92.071 | 5.427 | 0.000 | 0.008 | 0.000 | 0.000 | -33.668 | 0.000 | -5.053 | -100.009 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 0.806 | -26.591 | 0.000 | 0.000 | 12.499 | 20.559 | 19.109 | 13.483 | 0.000 | 0.002 | 0.000 | 0.000 | -11.887 | 0.000 | -1.903 | -26.076 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 1.053 | -139.610 | 0.000 | 0.000 | 59.039 | 99.059 | 92.071 | 38.578 | 0.000 | 0.005 | 0.000 | 0.000 | -33.890 | 0.000 | -5.373 | -110.932 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 2.075 | -15.133 | 0.000 | 0.000 | 4.903 | 14.502 | 9.883 | 1.756 | 0.000 | 0.000 | 0.000 | 0.000 | -1.964 | 0.000 | -0.296 | -15.727 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 1.235 | -22.469 | 0.000 | 0.000 | 12.750 | 20.559 | 19.109 | 6.667 | 0.000 | 0.002 | 0.000 | 0.000 | -11.582 | 0.000 | -1.792 | -24.480 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 1.843 | -119.922 | 0.000 | 0.000 | 60.341 | 99.059 | 92.071 | 5.599 | 0.000 | 0.008 | 0.000 | 0.000 | -33.636 | 0.000 | -5.053 | -100.311 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 0.772 | -26.875 | 0.000 | 0.000 | 12.482 | 20.559 | 19.109 | 13.529 | 0.000 | 0.002 | 0.000 | 0.000 | -11.933 | 0.000 | -1.912 | -25.732 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 0.990 | -141.740 | 0.000 | 0.000 | 58.904 | 99.059 | 92.071 | 38.840 | 0.000 | 0.005 | 0.000 | 0.000 | -34.076 | 0.000 | -5.409 | -108.644 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 1.815 | -16.213 | 0.000 | 0.000 | 4.878 | 14.502 | 9.883 | 1.744 | 0.000 | 0.000 | 0.000 | 0.000 | -1.990 | 0.000 | -0.301 | -14.319 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 1.211 | -22.906 | 0.000 | 0.000 | 12.722 | 20.559 | 19.109 | 7.133 | 0.000 | 0.002 | 0.000 | 0.000 | -11.655 | 0.000 | -1.806 | -24.370 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 1.230 | -80.935 | 0.000 | 0.000 | 39.729 | 65.416 | 60.801 | 5.687 | 0.000 | 0.005 | 0.000 | 0.000 | -22.237 | 0.000 | -3.365 | -66.331 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 0.000 | 0.000 | 0.336 | -53.959 | 0.000 | 0.000 | 33.238 | 33.643 | 41.692 | 2.670 | 0.000 | 0.002 | 0.000 | 0.000 | -12.225 | 0.000 | -1.859 | -43.538 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 0.000 | 0.000 | 5.189 | -38.342 | 0.000 | 0.000 | 13.800 | 41.241 | 28.104 | 3.692 | 0.000 | 0.001 | 0.000 | 0.000 | -6.024 | 0.000 | -0.924 | -46.737 |
| LOBBY_ZN_1_FLR_1 | 0.000 | 0.000 | 39.746 | -8.700 | 0.000 | 0.000 | 9.648 | 32.975 | 8.802 | 16.133 | 0.000 | 0.095 | 0.000 | 0.000 | -10.936 | 0.000 | -76.308 | -11.455 |
| MECH_ZN_1_FLR_1 | 0.000 | 0.000 | 0.000 | -34.734 | 0.000 | 0.000 | 1.682 | 56.071 | 32.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -55.447 |
| BATH_ZN_1_FLR_1 | 0.000 | 0.000 | 0.054 | -16.727 | 0.000 | 0.000 | 4.809 | 25.366 | 9.780 | 4.254 | 0.000 | 0.000 | 0.000 | 0.000 | -6.615 | 0.000 | -1.030 | -19.891 |
| OFFICES_ZN_1_FLR_1 | 0.000 | 0.000 | 2.010 | -64.161 | 0.000 | 0.000 | 10.781 | 71.958 | 61.288 | 28.610 | 0.000 | 0.002 | 0.000 | 0.000 | -26.593 | 0.000 | -4.411 | -79.483 |
| GYM_ZN_1_FLR_1 | 0.000 | 0.000 | 0.942 | -104.544 | 0.000 | 0.000 | 54.169 | 65.666 | 22.969 | 29.175 | 0.000 | 0.001 | 0.000 | 0.000 | -25.791 | 0.000 | -1.880 | -40.706 |
| KITCHEN_ZN_1_FLR_1 | 0.000 | 0.000 | 0.007 | -158.587 | 0.000 | 0.000 | 11.456 | 29.905 | 138.079 | 4.452 | 0.000 | 0.000 | 0.000 | 0.000 | -6.694 | 0.000 | -1.067 | -17.550 |
| CAFETERIA_ZN_1_FLR_1 | 0.000 | 0.000 | 3.534 | -162.291 | 0.000 | 0.000 | 151.481 | 42.053 | 29.938 | 10.882 | 0.000 | 0.001 | 0.000 | 0.000 | -23.500 | 0.000 | -3.747 | -48.352 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.000 | 0.000 | 0.913 | -79.223 | 0.000 | 0.000 | 19.222 | 91.739 | 77.015 | 13.410 | 0.000 | 0.002 | 0.000 | 0.000 | -26.452 | 0.000 | -4.267 | -92.359 |
| Total Facility | 0.000 | 0.000 | 72.601 | -1659.744 | 0.000 | 0.000 | 737.953 | 1218.192 | 1115.552 | 317.611 | 0.000 | 0.151 | 0.000 | 0.000 | -412.768 | 0.000 | -137.149 | -1252.399 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 24-SEP-15:31 | 0.00 | 0.00 | 0.00 | -6030.03 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 2657.40 | 0.00 | 0.00 | 2747.44 | 0.00 | -0.00 | 0.00 | -44.57 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 25-SEP-13:50 | 0.00 | 0.00 | 0.00 | -26306.02 | 0.00 | 0.00 | 8479.99 | 6469.32 | 6325.65 | 10577.64 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -23.88 | -5522.69 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | -4677.14 | 0.00 | 0.00 | 682.67 | 947.12 | 678.98 | 649.99 | 0.00 | 1.21 | 1717.18 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | -5079.42 | 0.00 | 0.00 | 1760.15 | 1342.69 | 1312.87 | 2333.99 | 0.00 | 8.07 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1678.35 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | -20484.32 | 0.00 | 0.00 | 8480.78 | 6469.32 | 6325.65 | 1731.36 | 0.00 | 21.39 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2544.18 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | -5923.28 | 0.00 | 0.00 | 1760.13 | 1342.69 | 1312.87 | 2869.39 | 0.00 | 8.07 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1369.87 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 25-SEP-13:50 | 0.00 | 0.00 | 0.00 | -25746.64 | 0.00 | 0.00 | 8480.00 | 6469.32 | 6325.65 | 10187.97 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -23.88 | -5692.42 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | -4635.60 | 0.00 | 0.00 | 682.67 | 947.12 | 678.98 | 650.06 | 0.00 | 1.21 | 1675.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | -5084.80 | 0.00 | 0.00 | 1760.15 | 1342.69 | 1312.87 | 2340.22 | 0.00 | 8.07 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1679.20 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | -20512.11 | 0.00 | 0.00 | 8480.78 | 6469.32 | 6325.65 | 1762.07 | 0.00 | 21.39 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2547.09 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | -5948.69 | 0.00 | 0.00 | 1760.13 | 1342.69 | 1312.87 | 2875.96 | 0.00 | 8.07 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1351.03 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 25-SEP-13:50 | 0.00 | 0.00 | 0.00 | -26032.41 | 0.00 | 0.00 | 8479.99 | 6469.32 | 6325.65 | 10206.42 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -23.88 | -5425.09 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | -4811.08 | 0.00 | 0.00 | 682.67 | 947.12 | 678.98 | 649.77 | 0.00 | 1.21 | 1851.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | -5198.44 | 0.00 | 0.00 | 1760.15 | 1342.69 | 1312.87 | 2417.50 | 0.00 | 8.07 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1642.84 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 13-JUN-15:00 | 0.00 | 0.00 | 0.00 | -14085.29 | 0.00 | 0.00 | 5600.50 | 4272.19 | 4177.31 | 1501.02 | 0.00 | 14.12 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1479.86 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 13-JUN-15:20 | 0.00 | 0.00 | 0.00 | -8178.44 | 0.00 | 0.00 | 2879.87 | 2197.13 | 2864.44 | 738.62 | 0.00 | 7.34 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -508.96 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 14-JUN-07:01 | 0.00 | 0.00 | 0.00 | -13993.80 | 0.00 | 0.00 | 1927.30 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 7586.98 | 0.00 | -124.75 | 0.00 | -19.94 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 21-JUL-14:20 | 0.00 | 0.00 | 0.00 | -9907.62 | 0.00 | 0.00 | 181.61 | 1196.41 | 318.27 | 2462.53 | 0.00 | 7549.49 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -1800.69 |
| MECH_ZN_1_FLR_1 | 12-JUN-20:13 | 0.00 | 0.00 | 0.00 | -12259.16 | 0.00 | 0.00 | 0.00 | 721.39 | 687.68 | 0.00 | 0.00 | 0.00 | 10850.09 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 22-JUL-16:10 | 0.00 | 0.00 | 0.00 | -5098.19 | 0.00 | 0.00 | 0.00 | 326.34 | 148.14 | 2024.78 | 0.00 | 9.30 | 2589.62 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 10-SEP-14:38 | 0.00 | 0.00 | 0.00 | -24667.92 | 0.00 | 0.00 | 0.00 | 925.78 | 1299.72 | 3727.04 | 0.00 | 0.00 | 18866.28 | 0.00 | -0.00 | 0.00 | -150.91 | 0.00 |
| GYM_ZN_1_FLR_1 | 17-JUL-05:01 | 0.00 | 0.00 | 0.00 | -26593.60 | 0.00 | 0.00 | 0.00 | 844.83 | 347.93 | 0.00 | 0.00 | 0.00 | 26271.75 | 0.00 | -806.06 | 0.00 | -64.86 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 10-JAN-06:01 | 0.00 | 0.00 | 0.00 | -72627.72 | 0.00 | 0.00 | 0.00 | 384.74 | 2721.46 | 0.00 | 0.00 | 0.00 | 70194.86 | 0.00 | -557.80 | 0.00 | -115.53 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 13-JUN-05:01 | 0.00 | 0.00 | 0.00 | -51726.76 | 0.00 | 0.00 | 0.00 | 541.04 | 799.79 | 1167.29 | 0.00 | 0.00 | 49336.35 | 0.00 | -0.00 | 0.00 | -117.71 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 13-JUN-07:02 | 0.00 | 0.00 | 0.00 | -22599.74 | 0.00 | 0.00 | 2682.69 | 5991.24 | 5291.26 | 5200.50 | 0.00 | 0.00 | 3439.65 | 0.00 | -0.00 | 0.00 | -5.60 | 0.00 |
| Total Facility | 13-JUN-14:00 | 0.00 | 0.00 | 0.00 | -299824.21 | 0.00 | 0.00 | 97235.02 | 79557.27 | 73747.43 | 57565.30 | 0.00 | 616.37 | 0.00 | 0.00 | 0.00 | 0.00 | -2.48 | -8894.69 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 09-JAN-06:11 | 0.00 | 0.00 | 6247.55 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -746.82 | 0.00 | 0.00 | -6170.48 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 02-JAN-06:01 | 0.00 | 0.00 | 21721.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1636.47 | 0.00 | 0.00 | -23312.33 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 02-JAN-07:11 | 0.00 | 0.00 | 5557.46 | 0.00 | 0.00 | 0.00 | 0.00 | 947.12 | 209.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -89.63 | 0.00 | 0.00 | -6624.52 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 09-JAN-06:11 | 0.00 | 0.00 | 5829.04 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -717.29 | 0.00 | 0.00 | -5781.50 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 09-JAN-06:11 | 0.00 | 0.00 | 21582.31 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2003.76 | 0.00 | 0.00 | -22805.53 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 09-JAN-06:11 | 0.00 | 0.00 | 6215.39 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -735.80 | 0.00 | 0.00 | -6149.34 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 02-JAN-06:01 | 0.00 | 0.00 | 21464.51 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1574.45 | 0.00 | 0.00 | -23117.04 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 02-JAN-07:11 | 0.00 | 0.00 | 5556.08 | 0.00 | 0.00 | 0.00 | 0.00 | 947.12 | 209.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -89.20 | 0.00 | 0.00 | -6623.57 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 09-JAN-06:11 | 0.00 | 0.00 | 5833.66 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -717.30 | 0.00 | 0.00 | -5786.11 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 09-JAN-06:11 | 0.00 | 0.00 | 21605.48 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2003.83 | 0.00 | 0.00 | -22828.63 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 09-JAN-06:11 | 0.00 | 0.00 | 6212.76 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -738.34 | 0.00 | 0.00 | -6144.17 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 02-JAN-06:01 | 0.00 | 0.00 | 21542.23 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1580.03 | 0.00 | 0.00 | -23189.19 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 02-JAN-07:11 | 0.00 | 0.00 | 5580.53 | 0.00 | 0.00 | 0.00 | 0.00 | 947.12 | 209.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -89.33 | 0.00 | 0.00 | -6647.90 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 09-JAN-06:11 | 0.00 | 0.00 | 5855.71 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -723.45 | 0.00 | 0.00 | -5802.01 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 09-JAN-06:11 | 0.00 | 0.00 | 14504.58 | 0.00 | 0.00 | 0.00 | 0.00 | 841.62 | 1289.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1351.65 | 0.00 | 0.00 | -15283.95 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 02-JAN-07:11 | 0.00 | 0.00 | 7033.96 | 0.00 | 0.00 | 0.00 | 0.00 | 2197.13 | 884.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -522.86 | 0.00 | 0.00 | -9592.39 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 02-JAN-07:11 | 0.00 | 0.00 | 12262.86 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.36 | 595.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -257.68 | 0.00 | 0.00 | -15294.54 |
| LOBBY_ZN_1_FLR_1 | 10-JAN-08:00 | 0.00 | 0.00 | 12901.34 | 0.00 | 0.00 | 0.00 | 0.00 | 2153.53 | 186.66 | 0.00 | 0.00 | 0.00 | 20694.82 | 0.00 | -630.89 | 0.00 | -35305.46 | 0.00 |
| MECH_ZN_1_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 01-JAN-01:40 | 0.00 | 0.00 | 3306.64 | 0.00 | 0.00 | 0.00 | 0.00 | 326.34 | 207.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -213.02 | 0.00 | 0.00 | -3627.36 |
| OFFICES_ZN_1_FLR_1 | 02-JAN-07:11 | 0.00 | 0.00 | 16173.92 | 0.00 | 0.00 | 0.00 | 0.00 | 4699.41 | 1299.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1249.79 | 0.00 | 0.00 | -20923.27 |
| GYM_ZN_1_FLR_1 | 02-JAN-06:01 | 0.00 | 0.00 | 14005.65 | 0.00 | 0.00 | 0.00 | 0.00 | 844.83 | 487.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1213.77 | 0.00 | 0.00 | -14123.81 |
| KITCHEN_ZN_1_FLR_1 | 10-NOV-07:02 | 0.00 | 0.00 | 3374.69 | 0.00 | 0.00 | 0.00 | 0.00 | 1953.00 | 2721.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -349.48 | 0.00 | -8.57 | -7691.09 |
| CAFETERIA_ZN_1_FLR_1 | 02-JAN-07:01 | 0.00 | 0.00 | 78363.97 | 0.00 | 0.00 | 0.00 | 0.00 | 2746.41 | 799.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1177.38 | 0.00 | 0.00 | -80732.78 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 02-JAN-07:11 | 0.00 | 0.00 | 15148.19 | 0.00 | 0.00 | 0.00 | 0.00 | 5991.24 | 1633.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1162.98 | 0.00 | 0.00 | -21609.69 |
| Total Facility | 02-JAN-06:01 | -354.79 | 354.79 | 299443.54 | -354.79 | 0.00 | 0.00 | 0.00 | 15672.78 | 23615.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -19549.29 | 0.00 | 0.00 | -318827.67 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| VAV_POD_1 | 27.3214 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 27.0965 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| PSZ-AC_1:6 | 1.5194 | 0.0000 | 26.9930 | 1.0000 | Calculated from schedules | 0.4528 | 1.5194 | 0.2980 | 1.0000 | Not calculated | 0.4528 | 0.2980 | ||
| PSZ-AC_2:7 | 2.5588 | 0.0000 | 339.0743 | 1.0000 | Calculated from schedules | 1.4882 | 2.5588 | 0.5816 | 1.0000 | Not calculated | 1.4882 | 0.5816 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| VAV_POD_1 | 14.3115 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.4373 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| PSZ-AC_1:6 | 1.5194 | 0.0000 | 26.9930 | 1.0000 | Calculated from schedules | 0.4528 | 1.5194 | 1.0000 | 1.0000 | Not calculated | 0.4528 | 0.2980 | ||
| PSZ-AC_2:7 | 2.5588 | 0.0000 | 339.0743 | 1.0000 | Calculated from schedules | 1.4882 | 2.5588 | 1.0000 | 1.0000 | Not calculated | 1.4882 | 0.5816 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.3340 | 0.000305 | 192.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.3340 | 0.000305 | 192.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.3340 | 0.000305 | 192.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 84.7686 | 0.001880 | 315.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 43.5953 | 0.001880 | 162.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 29.3880 | 0.000305 | 546.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 18.4080 | 0.000559 | 171.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 4.0690 | 0.000000 | 252.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.2270 | 0.000000 | 190.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 23.7365 | 0.000432 | 441.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 115.3101 | 0.001524 | 357.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | 0.009440 | 26.9930 | 0.001179 | 168.00 | 0.4528 | 1.0000 | 0.4528 | 1.000 | 0.4528 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | 0.000000 | 339.0743 | 0.004724 | 315.00 | 1.4882 | 1.0000 | 1.4882 | 1.000 | 1.4882 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 42.9540 | 0.000864 | 399.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| VAV_POD_1 | 0.00 | 0.001254 | 6388.0000 | 0.0000 | 0.0000 | 0.0000 | |
| PSZ-AC_1:6 | 0.009440 | 26.99 | 0.001179 | 168.0000 | 0.4528 | 0.4528 | 0.4528 |
| PSZ-AC_2:7 | 0.000000 | 339.07 | 0.004724 | 315.0000 | 1.4882 | 1.4882 | 1.4882 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6271 | 0.6271 | 0.2678 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6841 | 2.6841 | 1.2884 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5044 | 0.5044 | 0.1513 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5281 | 0.5281 | 0.2672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1175 | 2.1175 | 1.2896 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6233 | 0.6233 | 0.2674 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6546 | 2.6546 | 1.2875 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5028 | 0.5028 | 0.1508 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5284 | 0.5284 | 0.2674 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1184 | 2.1184 | 1.2880 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6238 | 0.6238 | 0.2676 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6652 | 2.6652 | 1.2900 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5075 | 0.5075 | 0.1523 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5317 | 0.5317 | 0.2675 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4202 | 1.4202 | 0.8507 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7900 | 0.7900 | 0.4377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0570 | 1.0570 | 0.3171 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6766 | 0.6766 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7748 | 0.7748 | 0.2325 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4919 | 0.4919 | 0.1476 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5627 | 1.5627 | 0.4688 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7217 | 1.7217 | 0.7816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5194 | 1.5194 | 1.5194 | No | 0.4528 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5588 | 2.5588 | 2.5588 | No | 1.4882 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6093 | 1.6093 | 0.4957 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| VAV_POD_1 | 27.3214 | 27.0965 | 27.3214 | 12.4373 | 0.0000 | 1.0000 |
| PSZ-AC_1:6 | 1.5194 | 1.5194 | 1.5194 | 1.5194 | 0.4528 | 1.0000 |
| PSZ-AC_2:7 | 2.5588 | 2.5588 | 2.5588 | 2.5588 | 1.4882 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3135 | 0.3135 | 0.2678 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3421 | 1.3421 | 1.2884 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2522 | 0.2522 | 0.1513 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2672 | 0.2672 | 0.2672 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2896 | 1.2896 | 1.2896 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3117 | 0.3117 | 0.2674 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3273 | 1.3273 | 1.2875 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2514 | 0.2514 | 0.1508 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2674 | 0.2674 | 0.2674 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2880 | 1.2880 | 1.2880 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3119 | 0.3119 | 0.2676 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3326 | 1.3326 | 1.2900 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2538 | 0.2538 | 0.1523 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2675 | 0.2675 | 0.2675 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8507 | 0.8507 | 0.8507 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4377 | 0.4377 | 0.4377 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5285 | 0.5285 | 0.3171 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3383 | 0.3383 | 0.2030 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3874 | 0.3874 | 0.2325 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2460 | 0.2460 | 0.1476 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7814 | 0.7814 | 0.4688 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8608 | 0.8608 | 0.7816 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5194 | 1.5194 | 1.5194 | No | 0.4528 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.5588 | 2.5588 | 2.5588 | No | 1.4882 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8047 | 0.8047 | 0.4957 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| VAV_POD_1 | 14.3115 | 12.4373 | 12.4373 | 12.4373 | 0.0000 | 1.0000 |
| PSZ-AC_1:6 | 1.5194 | 1.5194 | 1.5194 | 1.5194 | 0.4528 | 1.0000 |
| PSZ-AC_2:7 | 2.5588 | 2.5588 | 2.5588 | 2.5588 | 1.4882 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
| Total gross floor area [m2] | 6871.00 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 192.00 | 0.00 | 62.83 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 192.00 | 0.00 | 62.83 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 192.00 | 0.00 | 62.83 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 315.00 | 0.00 | 62.83 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 162.00 | 0.00 | 62.83 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 546.00 | 0.00 | 62.83 |
| LOBBY_ZN_1_FLR_1 | 171.00 | 171.00 | 0.00 | 62.83 |
| MECH_ZN_1_FLR_1 | 252.00 | 252.00 | 0.00 | 62.83 |
| BATH_ZN_1_FLR_1 | 190.00 | 190.00 | 0.00 | 62.83 |
| OFFICES_ZN_1_FLR_1 | 441.00 | 441.00 | 0.00 | 53.16 |
| GYM_ZN_1_FLR_1 | 357.00 | 357.00 | 0.00 | 62.83 |
| KITCHEN_ZN_1_FLR_1 | 168.00 | 168.00 | 0.00 | 62.83 |
| CAFETERIA_ZN_1_FLR_1 | 315.00 | 315.00 | 0.00 | 52.32 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 399.00 | 0.00 | 62.83 |
| Totals | 6871.00 | 6871.00 | 0.00 |
| Data | |
| Number of hours heating loads not met | 825.17 |
| Number of hours cooling loads not met | 1.17 |
| Number of hours not met | 826.33 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 445.33 | 271403.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heating -- Boiler | 0.00 | 0.00 | 267.21 | 348041.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 84.62 | 110242.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 1218.19 | 79557.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 92.49 | 5897.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 947.54 | 65099.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- Cooking | 149.71 | 9998.36 | 361.03 | 48084.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ReachInFreezer | 31.09 | 986.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ReachInRefrigerator | 23.02 | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Transformer | 17.61 | 1336.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 316.71 | 49898.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- General | 1.02 | 730.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 0.00 | 0.00 | 159.18 | 29843.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- General | 7.85 | 2172.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- LowTempRefrigeration | 15.13 | 1474.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- MedTempRefrigeration | 22.01 | 734.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 1196.35 | 2926.99 |
| Natural Gas | 361.03 | 1232.76 |
| Additional | 0.00 | 0.00 |
| Total | 1557.38 | 4159.75 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 177.29 |
| Space Heating | 0.00 |
| Space Cooling | 12.32 |
| Fans (All) | 46.09 |
| Service Water Heating | 0.00 |
| Receptacle Equipment | 167.57 |
| Miscellaneous (All) | 425.99 |
| Subtotal | 425.99 |
| Natural Gas [MJ/m2] | |
| Space Heating | 103.70 |
| Service Water Heating | 23.17 |
| Miscellaneous (All) | 179.41 |
| Subtotal | 179.41 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 29.29 |
| Space Heating | 17.13 |
| Space Cooling | 2.03 |
| Fans (All) | 7.61 |
| Service Water Heating | 3.83 |
| Receptacle Equipment | 36.36 |
| Miscellaneous | 3.75 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| LTG_SCH_GYM | 3903. | 8760. |
| LTG_SCH_CLASSROOM | 3903. | 8760. |
| LTG_SCH_LIBRARY | 3903. | 8760. |
| LTG_SCH_BATH | 3903. | 8760. |
| LTG_SCH_KITCHEN | 3903. | 8760. |
| LTG_SCH_OFFICE | 3903. | 8760. |
| LTG_SCH_LOBBY | 3903. | 8760. |
| LTG_SCH_MECHANICAL | 3903. | 8760. |
| LTG_SCH_COMPUTER_ROOM | 3903. | 8760. |
| LTG_SCH_CAFETERIA | 3903. | 8760. |
| LTG_SCH_CORRIDOR | 3903. | 8760. |
| BLDG_EQUIP_SCH | 3617. | 8760. |
| WALKIN_OCC_LGHT_SCH_2 | 2473. | 8760. |
| KITCHEN_ELEC_EQUIP_SCH | 1045. | 8760. |
| KITCHEN_GAS_EQUIP_SCH | 425. | 8760. |
| BLDG_OCC_SCH | 1755. | 3380. |
| BLDG_OCC_SCH_EXTEND | 2948. | 3380. |
| BLDG_OCC_SCH_OFFICES | 2197. | 3380. |
| BLDG_OCC_SCH_OFFICES_W_SB | 1743. | 2860. |
| OFFICES BINARY OCCUPANCY | 3380. | 3380. |
| BLDG_OCC_SCH_GYM | 1828. | 3380. |
| BLDG_OCC_SCH_CAFETERIA | 1687. | 2815. |
| INFIL_SCH | 6205. | 8760. |
| INFIL_SCH_PNNL | 6030. | 8760. |
| INFIL_DOOR_OPENING_SCH | 827. | 2860. |
| BLDG_SWH_SCH | 1227. | 3120. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| EXTERIOR_LGT_189_1 | 5940. | 8760. |
| WORK_EFF_SCH | 0. | 0. |
| KITCHEN_EXHAUST_SCH | 2860. | 2860. |
| MINOA_SCHED | 8760. | 8760. |
| BATH_ZN_1_FLR_1 SHW_DEFAULT LATENT FRACT SCHED | 438. | 8760. |
| BATH_ZN_1_FLR_1 SHW_DEFAULT SENSIBLE FRACT SCHED | 1752. | 8760. |
| KITCHEN_ZN_1_FLR_1 SHW_DEFAULT LATENT FRACT SCHED | 438. | 8760. |
| KITCHEN_ZN_1_FLR_1 SHW_DEFAULT SENSIBLE FRACT SCHED | 1752. | 8760. |
| KITCHEN_ZN_1_FLR_1_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
| EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 3380. | 3380. |
| EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6570. | 8760. |
| KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 2594. | 2860. |
| OFFICES_ZN_1_FLR_1_MDP_SCH | 2472. | 8240. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_SCH_YES_OPTIMUM | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
| CLGSETP_SCH_YES_OPTIMUM | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
| HTGSETP_SCH_SETBACK | MECH_ZN_1_FLR_1 DUAL SP CONTROL | January | 15.60 | 365 | 15.60 | 365 |
| CLGSETP_SCH_SETUP | MECH_ZN_1_FLR_1 DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
| HTGSETP_SCH_YES_OPTIMUM_W_SB | OFFICES_ZN_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
| CLGSETP_SCH_YES_OPTIMUM_W_SB | OFFICES_ZN_1_FLR_1 DUAL SP CONTROL | July | 24.56 | 63 | 26.70 | 365 |
| HTGSETP_SCH_NO_OPTIMUM | GYM_ZN_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
| CLGSETP_SCH_NO_OPTIMUM | GYM_ZN_1_FLR_1 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 8638.50 | 121.50 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 8723.50 | 36.50 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 5064.83 | 3601.67 | 93.50 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 8748.33 | 11.67 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
| Min | 5064.83 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 3601.67 | 93.50 | 0.00 | 0.00 |
| Average | 8604.45 | 151.81 | 3.74 | 0.00 | 0.00 |
| Sum | 215111.17 | 3795.33 | 93.50 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 141584.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 122876.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 47696.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 29112.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 4465.50 | 46.50 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 15257.33 | 50.67 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 38444.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 202800.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 44688.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 552560.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 70792.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 4465.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 552560.00 | 50.67 | 0.00 | 0.00 | 0.00 |
| Average | 106078.19 | 3.89 | 0.00 | 0.00 | 0.00 |
| Sum | 2651954.83 | 97.17 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 8758.67 | 1.33 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 8606.83 | 153.17 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 8718.67 | 41.33 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 8756.00 | 4.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 8700.83 | 59.17 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 4542.50 | 4006.33 | 211.17 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 8739.17 | 20.83 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
| Min | 4542.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 4006.33 | 211.17 | 0.00 | 0.00 |
| Average | 8579.97 | 171.58 | 8.45 | 0.00 | 0.00 |
| Sum | 214499.33 | 4289.50 | 211.17 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 141584.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 122876.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 47696.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 29112.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 4448.50 | 63.50 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 15112.33 | 195.67 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 38444.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 202800.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 44620.33 | 67.67 | 0.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 551325.67 | 1234.33 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 70792.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 4448.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 551325.67 | 1234.33 | 0.00 | 0.00 | 0.00 |
| Average | 106019.63 | 62.45 | 0.00 | 0.00 | 0.00 |
| Sum | 2650490.83 | 1561.17 | 0.00 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:27:52
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.180 |
| February | 4.245 |
| March | 5.898 |
| April | 8.962 |
| May | 9.987 |
| June | 13.308 |
| July | 15.016 |
| August | 15.650 |
| September | 13.434 |
| October | 9.327 |
| November | 6.665 |
| December | 4.103 |
| Annual Sum or Average | 9.257 |
| Minimum of Months | 4.103 |
| Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.180 |
| February | 4.245 |
| March | 5.898 |
| April | 8.962 |
| May | 9.987 |
| June | 13.308 |
| July | 15.016 |
| August | 15.650 |
| September | 13.434 |
| October | 9.327 |
| November | 6.665 |
| December | 4.103 |
| Annual Sum or Average | 9.257 |
| Minimum of Months | 4.103 |
| Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.180 |
| February | 4.245 |
| March | 5.898 |
| April | 8.962 |
| May | 9.987 |
| June | 13.308 |
| July | 15.016 |
| August | 15.650 |
| September | 13.434 |
| October | 9.327 |
| November | 6.665 |
| December | 4.103 |
| Annual Sum or Average | 9.257 |
| Minimum of Months | 4.103 |
| Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.180 |
| February | 4.245 |
| March | 5.898 |
| April | 8.962 |
| May | 9.987 |
| June | 13.308 |
| July | 15.016 |
| August | 15.650 |
| September | 13.434 |
| October | 9.327 |
| November | 6.665 |
| December | 4.103 |
| Annual Sum or Average | 9.257 |
| Minimum of Months | 4.103 |
| Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME SCHOOLPRIMARY
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.180 |
| February | 4.245 |
| March | 5.898 |
| April | 8.962 |
| May | 9.987 |
| June | 13.308 |
| July | 15.016 |
| August | 15.650 |
| September | 13.434 |
| October | 9.327 |
| November | 6.665 |
| December | 4.103 |
| Annual Sum or Average | 9.257 |
| Minimum of Months | 4.103 |
| Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.180 |
| February | 4.245 |
| March | 5.898 |
| April | 8.962 |
| May | 9.987 |
| June | 13.308 |
| July | 15.016 |
| August | 15.650 |
| September | 13.434 |
| October | 9.327 |
| November | 6.665 |
| December | 4.103 |
| Annual Sum or Average | 9.257 |
| Minimum of Months | 4.103 |
| Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.180 |
| February | 4.245 |
| March | 5.898 |
| April | 8.962 |
| May | 9.987 |
| June | 13.308 |
| July | 15.016 |
| August | 15.650 |
| September | 13.434 |
| October | 9.327 |
| November | 6.665 |
| December | 4.103 |
| Annual Sum or Average | 9.257 |
| Minimum of Months | 4.103 |
| Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.180 |
| February | 4.245 |
| March | 5.898 |
| April | 8.962 |
| May | 9.987 |
| June | 13.308 |
| July | 15.016 |
| August | 15.650 |
| September | 13.434 |
| October | 9.327 |
| November | 6.665 |
| December | 4.103 |
| Annual Sum or Average | 9.257 |
| Minimum of Months | 4.103 |
| Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.180 |
| February | 4.245 |
| March | 5.898 |
| April | 8.962 |
| May | 9.987 |
| June | 13.308 |
| July | 15.016 |
| August | 15.650 |
| September | 13.434 |
| October | 9.327 |
| November | 6.665 |
| December | 4.103 |
| Annual Sum or Average | 9.257 |
| Minimum of Months | 4.103 |
| Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.124267E+10 | 2617.88 | 19-JAN-15:40 | 8.33 | 7.46 | 0.663993E+09 | 1236.13 | 19-JAN-15:50 | 8.17 | 7.46 |
| February | 0.133331E+10 | 3495.11 | 09-FEB-15:01 | 8.00 | 6.01 | 0.613922E+09 | 1249.96 | 09-FEB-15:50 | 8.00 | 5.73 |
| March | 0.170411E+10 | 3393.64 | 10-MAR-15:01 | 8.83 | 4.79 | 0.741599E+09 | 1204.99 | 10-MAR-15:39 | 8.33 | 4.33 |
| April | 0.268234E+10 | 5688.04 | 28-APR-15:00 | 20.10 | 13.70 | 0.747413E+09 | 1277.24 | 14-APR-14:20 | 20.10 | 13.70 |
| May | 0.314030E+10 | 5550.21 | 22-MAY-15:00 | 24.00 | 16.08 | 0.836378E+09 | 1277.24 | 05-MAY-14:20 | 24.00 | 16.08 |
| June | 0.352616E+10 | 6019.76 | 13-JUN-15:00 | 26.00 | 17.83 | 0.526225E+09 | 1277.24 | 07-JUN-14:20 | 26.00 | 17.83 |
| July | 0.247523E+10 | 3644.13 | 24-JUL-14:01 | 19.00 | 15.90 | 0.161216E+09 | 201.67 | 21-JUL-17:19 | 19.00 | 15.90 |
| August | 0.263232E+10 | 4119.50 | 20-AUG-15:40 | 23.67 | 14.78 | 0.183611E+09 | 201.67 | 21-AUG-15:20 | 21.00 | 15.01 |
| September | 0.314419E+10 | 6030.05 | 24-SEP-15:31 | 22.00 | 15.41 | 0.480320E+09 | 1277.24 | 19-SEP-14:20 | 22.00 | 15.41 |
| October | 0.239164E+10 | 5064.72 | 03-OCT-15:00 | 14.00 | 8.96 | 0.754662E+09 | 1277.23 | 04-OCT-14:20 | 14.00 | 10.28 |
| November | 0.166337E+10 | 3617.01 | 10-NOV-15:01 | 11.83 | 8.42 | 0.695757E+09 | 1277.24 | 10-NOV-15:20 | 11.67 | 8.42 |
| December | 0.107068E+10 | 2452.14 | 21-DEC-14:40 | 8.00 | 6.98 | 0.621550E+09 | 1177.33 | 21-DEC-14:50 | 8.00 | 6.98 |
| Annual Sum or Average | 0.270063E+11 | 0.702665E+10 | ||||||||
| Minimum of Months | 0.107068E+10 | 2452.14 | 8.00 | 4.79 | 0.161216E+09 | 201.67 | 8.00 | 4.33 | ||
| Maximum of Months | 0.352616E+10 | 6030.05 | 26.00 | 17.83 | 0.836378E+09 | 1277.24 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.797851E+10 | 12856.33 | 20-JAN-15:02 | 7.83 | 6.41 | 0.334114E+10 | 6050.67 | 20-JAN-13:20 | 7.83 | 6.41 |
| February | 0.813121E+10 | 17136.27 | 09-FEB-15:01 | 8.00 | 6.01 | 0.311096E+10 | 6092.73 | 03-FEB-14:50 | 8.00 | 6.01 |
| March | 0.100911E+11 | 16805.44 | 10-MAR-15:01 | 8.83 | 4.79 | 0.377609E+10 | 5974.81 | 10-MAR-15:09 | 8.83 | 4.79 |
| April | 0.136557E+11 | 24733.60 | 28-APR-14:30 | 20.05 | 13.23 | 0.370496E+10 | 6153.99 | 14-APR-14:20 | 20.05 | 13.23 |
| May | 0.156124E+11 | 24140.09 | 23-MAY-13:50 | 18.83 | 14.71 | 0.412838E+10 | 6160.65 | 03-MAY-13:39 | 18.83 | 14.71 |
| June | 0.167928E+11 | 25222.79 | 13-JUN-14:00 | 25.10 | 17.45 | 0.255937E+10 | 6153.98 | 07-JUN-14:20 | 25.10 | 17.45 |
| July | 0.115471E+11 | 16986.44 | 24-JUL-05:01 | 13.00 | 13.00 | 0.754830E+09 | 941.18 | 24-JUL-14:50 | 19.00 | 15.90 |
| August | 0.124816E+11 | 18579.80 | 20-AUG-15:40 | 23.67 | 14.78 | 0.870141E+09 | 949.92 | 21-AUG-14:50 | 21.00 | 15.01 |
| September | 0.152805E+11 | 26299.41 | 25-SEP-13:50 | 21.17 | 13.49 | 0.233896E+10 | 6153.97 | 19-SEP-14:20 | 21.17 | 13.49 |
| October | 0.126875E+11 | 23438.34 | 03-OCT-14:02 | 14.00 | 9.33 | 0.377969E+10 | 6153.96 | 31-OCT-14:20 | 12.67 | 7.82 |
| November | 0.977266E+10 | 17406.97 | 10-NOV-15:01 | 11.83 | 8.42 | 0.352815E+10 | 6153.98 | 03-NOV-14:20 | 11.83 | 8.42 |
| December | 0.726615E+10 | 12237.66 | 21-DEC-14:30 | 8.00 | 6.98 | 0.313669E+10 | 5827.62 | 21-DEC-14:39 | 8.00 | 6.98 |
| Annual Sum or Average | 0.141297E+12 | 0.350294E+11 | ||||||||
| Minimum of Months | 0.726615E+10 | 12237.66 | 7.83 | 4.79 | 0.754830E+09 | 941.18 | 7.83 | 4.79 | ||
| Maximum of Months | 0.167928E+11 | 26299.41 | 25.10 | 17.45 | 0.412838E+10 | 6160.65 | 25.10 | 17.45 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.407669E+09 | 1222.05 | 19-JAN-16:00 | 8.00 | 7.45 | 0.245637E+09 | 416.88 | 19-JAN-15:00 | 8.00 | 7.45 |
| February | 0.530068E+09 | 1714.04 | 09-FEB-15:01 | 8.00 | 6.01 | 0.224347E+09 | 421.73 | 09-FEB-15:00 | 8.00 | 5.66 |
| March | 0.891566E+09 | 1749.84 | 31-MAR-14:01 | 7.00 | 4.61 | 0.276757E+09 | 432.19 | 31-MAR-14:00 | 7.00 | 4.34 |
| April | 0.152796E+10 | 3580.35 | 28-APR-15:00 | 20.10 | 13.70 | 0.284676E+09 | 495.44 | 28-APR-14:00 | 20.10 | 13.70 |
| May | 0.201110E+10 | 3970.84 | 23-MAY-15:00 | 18.00 | 14.38 | 0.327573E+09 | 495.44 | 26-MAY-14:00 | 16.00 | 13.03 |
| June | 0.246144E+10 | 4677.48 | 13-JUN-15:00 | 26.00 | 17.83 | 0.208514E+09 | 495.45 | 09-JUN-14:09 | 26.00 | 17.83 |
| July | 0.151587E+10 | 2069.29 | 24-JUL-14:01 | 19.00 | 15.90 | 65089298.85 | 78.23 | 24-JUL-14:20 | 19.00 | 15.90 |
| August | 0.157390E+10 | 2002.07 | 21-AUG-14:02 | 21.00 | 15.01 | 72978677.71 | 77.32 | 14-AUG-16:10 | 21.00 | 15.01 |
| September | 0.186534E+10 | 3679.49 | 27-SEP-15:00 | 22.00 | 13.07 | 0.187246E+09 | 495.45 | 19-SEP-14:09 | 22.00 | 13.07 |
| October | 0.133181E+10 | 2435.64 | 03-OCT-15:00 | 14.00 | 8.96 | 0.283540E+09 | 495.44 | 02-OCT-14:20 | 14.00 | 8.96 |
| November | 0.863493E+09 | 1881.87 | 10-NOV-15:01 | 11.83 | 8.42 | 0.255420E+09 | 455.82 | 10-NOV-15:00 | 11.00 | 8.40 |
| December | 0.316835E+09 | 1134.82 | 21-DEC-15:10 | 7.83 | 6.90 | 0.232651E+09 | 398.47 | 21-DEC-15:20 | 7.67 | 6.81 |
| Annual Sum or Average | 0.152971E+11 | 0.266443E+10 | ||||||||
| Minimum of Months | 0.316835E+09 | 1134.82 | 7.00 | 4.61 | 65089298.85 | 77.32 | 7.00 | 4.34 | ||
| Maximum of Months | 0.246144E+10 | 4677.48 | 26.00 | 17.83 | 0.327573E+09 | 495.45 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.907970E+09 | 2244.62 | 19-JAN-16:00 | 8.00 | 7.45 | 0.639752E+09 | 1106.20 | 19-JAN-15:00 | 8.00 | 7.45 |
| February | 0.100024E+10 | 3063.48 | 09-FEB-15:01 | 8.00 | 6.01 | 0.583314E+09 | 1103.12 | 09-FEB-15:00 | 8.00 | 5.66 |
| March | 0.150507E+10 | 3139.11 | 30-MAR-14:01 | 12.83 | 7.23 | 0.721966E+09 | 1122.43 | 31-MAR-14:00 | 7.00 | 4.34 |
| April | 0.221078E+10 | 4033.22 | 28-APR-15:00 | 20.10 | 13.70 | 0.709002E+09 | 1277.22 | 21-APR-14:20 | 20.10 | 13.70 |
| May | 0.272855E+10 | 4302.87 | 23-MAY-15:00 | 18.00 | 14.38 | 0.814142E+09 | 1277.24 | 12-MAY-14:20 | 18.00 | 14.38 |
| June | 0.318725E+10 | 5079.50 | 13-JUN-15:00 | 26.00 | 17.83 | 0.519842E+09 | 1277.24 | 07-JUN-14:20 | 26.00 | 17.83 |
| July | 0.218699E+10 | 3238.22 | 24-JUL-14:01 | 19.00 | 15.90 | 0.151068E+09 | 188.45 | 21-JUL-17:10 | 19.00 | 15.90 |
| August | 0.214136E+10 | 3353.74 | 20-AUG-15:40 | 23.67 | 14.78 | 0.168261E+09 | 184.47 | 14-AUG-16:10 | 23.67 | 14.78 |
| September | 0.240272E+10 | 3982.06 | 27-SEP-15:00 | 22.00 | 13.07 | 0.460295E+09 | 1277.23 | 28-SEP-14:20 | 16.00 | 13.03 |
| October | 0.196196E+10 | 3615.11 | 03-OCT-14:01 | 14.00 | 9.33 | 0.715970E+09 | 1277.03 | 05-OCT-14:00 | 15.00 | 8.96 |
| November | 0.139362E+10 | 3322.09 | 10-NOV-15:01 | 11.83 | 8.42 | 0.665163E+09 | 1182.66 | 10-NOV-15:00 | 11.00 | 8.40 |
| December | 0.842916E+09 | 2084.75 | 21-DEC-14:50 | 8.00 | 6.98 | 0.604344E+09 | 1053.25 | 21-DEC-14:00 | 8.00 | 6.98 |
| Annual Sum or Average | 0.224694E+11 | 0.675312E+10 | ||||||||
| Minimum of Months | 0.842916E+09 | 2084.75 | 8.00 | 6.01 | 0.151068E+09 | 184.47 | 7.00 | 4.34 | ||
| Maximum of Months | 0.318725E+10 | 5079.50 | 26.00 | 17.83 | 0.814142E+09 | 1277.24 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.635648E+10 | 10973.29 | 19-JAN-15:40 | 8.33 | 7.46 | 0.317492E+10 | 5382.72 | 19-JAN-15:50 | 8.17 | 7.46 |
| February | 0.656680E+10 | 15171.38 | 09-FEB-15:01 | 8.00 | 6.01 | 0.292480E+10 | 5411.44 | 03-FEB-15:09 | 8.00 | 6.01 |
| March | 0.925862E+10 | 15848.54 | 30-MAR-14:01 | 12.83 | 7.23 | 0.366564E+10 | 5630.98 | 30-MAR-14:00 | 12.00 | 6.56 |
| April | 0.113821E+11 | 17873.54 | 28-APR-14:02 | 20.02 | 12.92 | 0.355441E+10 | 6153.92 | 20-APR-14:20 | 20.02 | 12.92 |
| May | 0.136748E+11 | 18249.74 | 25-MAY-14:05 | 14.50 | 11.61 | 0.404285E+10 | 6153.96 | 02-MAY-14:20 | 14.50 | 11.61 |
| June | 0.153284E+11 | 20484.52 | 13-JUN-15:00 | 26.00 | 17.83 | 0.252797E+10 | 6153.98 | 07-JUN-14:20 | 26.00 | 17.83 |
| July | 0.101639E+11 | 15695.82 | 24-JUL-05:01 | 13.00 | 13.00 | 0.704926E+09 | 829.69 | 24-JUL-14:50 | 19.00 | 15.90 |
| August | 0.101011E+11 | 14695.60 | 20-AUG-15:40 | 23.67 | 14.78 | 0.793374E+09 | 807.97 | 14-AUG-15:50 | 23.67 | 14.78 |
| September | 0.117819E+11 | 17909.46 | 26-SEP-14:01 | 17.83 | 12.89 | 0.224906E+10 | 6153.92 | 28-SEP-14:20 | 16.00 | 13.03 |
| October | 0.106325E+11 | 17572.74 | 03-OCT-14:01 | 14.00 | 9.33 | 0.360704E+10 | 6150.72 | 03-OCT-14:50 | 14.00 | 9.04 |
| November | 0.850483E+10 | 16253.17 | 10-NOV-15:01 | 11.83 | 8.42 | 0.336151E+10 | 5738.38 | 10-NOV-15:09 | 11.83 | 8.42 |
| December | 0.626126E+10 | 10653.78 | 22-DEC-14:10 | 7.00 | 5.54 | 0.301485E+10 | 5264.86 | 22-DEC-14:20 | 7.00 | 5.54 |
| Annual Sum or Average | 0.120013E+12 | 0.336214E+11 | ||||||||
| Minimum of Months | 0.626126E+10 | 10653.78 | 7.00 | 5.54 | 0.704926E+09 | 807.97 | 7.00 | 5.54 | ||
| Maximum of Months | 0.153284E+11 | 20484.52 | 26.00 | 17.83 | 0.404285E+10 | 6153.98 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.118952E+10 | 2566.61 | 19-JAN-15:40 | 8.33 | 7.46 | 0.659854E+09 | 1218.97 | 19-JAN-15:50 | 8.17 | 7.46 |
| February | 0.132061E+10 | 3480.58 | 09-FEB-15:01 | 8.00 | 6.01 | 0.612576E+09 | 1246.60 | 09-FEB-15:50 | 8.00 | 5.73 |
| March | 0.169322E+10 | 3377.29 | 10-MAR-15:01 | 8.83 | 4.79 | 0.740390E+09 | 1200.85 | 10-MAR-15:39 | 8.33 | 4.33 |
| April | 0.264507E+10 | 5603.72 | 28-APR-15:00 | 20.10 | 13.70 | 0.745355E+09 | 1277.24 | 14-APR-14:20 | 20.10 | 13.70 |
| May | 0.309562E+10 | 5456.40 | 22-MAY-15:00 | 24.00 | 16.08 | 0.834221E+09 | 1277.24 | 01-MAY-14:20 | 24.00 | 16.08 |
| June | 0.347063E+10 | 5923.20 | 13-JUN-15:00 | 26.00 | 17.83 | 0.524949E+09 | 1277.24 | 07-JUN-14:20 | 26.00 | 17.83 |
| July | 0.243294E+10 | 3616.88 | 24-JUL-14:01 | 19.00 | 15.90 | 0.159874E+09 | 201.67 | 24-JUL-15:20 | 19.33 | 16.00 |
| August | 0.259326E+10 | 4068.02 | 20-AUG-15:40 | 23.67 | 14.78 | 0.182325E+09 | 201.67 | 21-AUG-15:20 | 21.00 | 15.01 |
| September | 0.310976E+10 | 5770.32 | 25-SEP-15:00 | 22.00 | 13.57 | 0.479815E+09 | 1277.24 | 19-SEP-14:20 | 22.00 | 13.57 |
| October | 0.237584E+10 | 4996.55 | 03-OCT-15:00 | 14.00 | 8.96 | 0.753864E+09 | 1277.23 | 04-OCT-14:20 | 14.00 | 10.28 |
| November | 0.164093E+10 | 3611.64 | 10-NOV-15:01 | 11.83 | 8.42 | 0.693387E+09 | 1277.24 | 10-NOV-15:20 | 11.67 | 8.42 |
| December | 0.102375E+10 | 2402.60 | 21-DEC-14:40 | 8.00 | 6.98 | 0.618090E+09 | 1161.10 | 21-DEC-14:50 | 8.00 | 6.98 |
| Annual Sum or Average | 0.265912E+11 | 0.700470E+10 | ||||||||
| Minimum of Months | 0.102375E+10 | 2402.60 | 8.00 | 4.79 | 0.159874E+09 | 201.67 | 8.00 | 4.33 | ||
| Maximum of Months | 0.347063E+10 | 5923.20 | 26.00 | 17.83 | 0.834221E+09 | 1277.24 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.768116E+10 | 12499.91 | 20-JAN-15:02 | 7.83 | 6.41 | 0.331117E+10 | 5912.21 | 20-JAN-13:20 | 7.83 | 6.41 |
| February | 0.808881E+10 | 17062.16 | 09-FEB-15:01 | 8.00 | 6.01 | 0.310422E+10 | 6078.88 | 03-FEB-14:50 | 8.00 | 6.01 |
| March | 0.101182E+11 | 16730.30 | 10-MAR-15:01 | 8.83 | 4.79 | 0.377712E+10 | 5951.76 | 10-MAR-15:09 | 8.83 | 4.79 |
| April | 0.135090E+11 | 24297.10 | 28-APR-14:30 | 20.05 | 13.23 | 0.370050E+10 | 6153.99 | 14-APR-14:20 | 20.05 | 13.23 |
| May | 0.154572E+11 | 23635.69 | 23-MAY-13:50 | 18.83 | 14.71 | 0.412564E+10 | 6160.60 | 03-MAY-13:39 | 18.83 | 14.71 |
| June | 0.165844E+11 | 24672.58 | 13-JUN-14:00 | 25.10 | 17.45 | 0.255580E+10 | 6153.98 | 07-JUN-14:20 | 25.10 | 17.45 |
| July | 0.113715E+11 | 16816.65 | 24-JUL-05:01 | 13.00 | 13.00 | 0.748194E+09 | 928.41 | 24-JUL-14:50 | 19.00 | 15.90 |
| August | 0.123012E+11 | 18250.88 | 20-AUG-15:40 | 23.67 | 14.78 | 0.862710E+09 | 937.22 | 21-AUG-14:50 | 21.00 | 15.01 |
| September | 0.150662E+11 | 25740.21 | 25-SEP-13:50 | 21.17 | 13.49 | 0.233655E+10 | 6153.97 | 19-SEP-14:20 | 21.17 | 13.49 |
| October | 0.126050E+11 | 22962.98 | 03-OCT-14:02 | 14.00 | 9.33 | 0.377845E+10 | 6153.96 | 31-OCT-14:20 | 12.67 | 7.82 |
| November | 0.968831E+10 | 17390.83 | 10-NOV-15:01 | 11.83 | 8.42 | 0.351581E+10 | 6153.98 | 03-NOV-14:20 | 11.83 | 8.42 |
| December | 0.713881E+10 | 11976.40 | 21-DEC-14:30 | 8.00 | 6.98 | 0.311597E+10 | 5737.91 | 21-DEC-14:39 | 8.00 | 6.98 |
| Annual Sum or Average | 0.139610E+12 | 0.349321E+11 | ||||||||
| Minimum of Months | 0.713881E+10 | 11976.40 | 7.83 | 4.79 | 0.748194E+09 | 928.41 | 7.83 | 4.79 | ||
| Maximum of Months | 0.165844E+11 | 25740.21 | 25.10 | 17.45 | 0.412564E+10 | 6160.60 | 25.10 | 17.45 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.379078E+09 | 1199.35 | 19-JAN-16:00 | 8.00 | 7.45 | 0.245199E+09 | 413.16 | 19-JAN-15:00 | 8.00 | 7.45 |
| February | 0.524590E+09 | 1706.97 | 09-FEB-15:01 | 8.00 | 6.01 | 0.224255E+09 | 421.35 | 09-FEB-15:00 | 8.00 | 5.66 |
| March | 0.892046E+09 | 1743.47 | 31-MAR-14:01 | 7.00 | 4.61 | 0.276820E+09 | 431.94 | 31-MAR-14:00 | 7.00 | 4.34 |
| April | 0.151743E+10 | 3556.24 | 28-APR-15:00 | 20.10 | 13.70 | 0.284402E+09 | 495.44 | 28-APR-14:00 | 20.10 | 13.70 |
| May | 0.199572E+10 | 3936.33 | 23-MAY-15:00 | 18.00 | 14.38 | 0.327417E+09 | 495.44 | 26-MAY-14:00 | 16.00 | 13.03 |
| June | 0.243539E+10 | 4635.94 | 13-JUN-15:00 | 26.00 | 17.83 | 0.208421E+09 | 495.45 | 09-JUN-14:09 | 26.00 | 17.83 |
| July | 0.150156E+10 | 2061.87 | 24-JUL-14:01 | 19.00 | 15.90 | 64843137.62 | 78.23 | 24-JUL-14:20 | 19.00 | 15.90 |
| August | 0.155993E+10 | 1984.97 | 21-AUG-14:02 | 21.00 | 15.01 | 72693265.92 | 76.94 | 14-AUG-16:10 | 21.00 | 15.01 |
| September | 0.184777E+10 | 3654.04 | 27-SEP-15:00 | 22.00 | 13.07 | 0.187127E+09 | 495.45 | 19-SEP-14:09 | 22.00 | 13.07 |
| October | 0.132406E+10 | 2392.14 | 03-OCT-15:00 | 14.00 | 8.96 | 0.283450E+09 | 495.44 | 02-OCT-14:20 | 14.00 | 8.96 |
| November | 0.851559E+09 | 1873.34 | 10-NOV-15:01 | 11.83 | 8.42 | 0.255121E+09 | 455.19 | 10-NOV-15:00 | 11.00 | 8.40 |
| December | 0.303423E+09 | 1121.12 | 21-DEC-15:10 | 7.83 | 6.90 | 0.232469E+09 | 396.18 | 21-DEC-15:20 | 7.67 | 6.81 |
| Annual Sum or Average | 0.151326E+11 | 0.266222E+10 | ||||||||
| Minimum of Months | 0.303423E+09 | 1121.12 | 7.00 | 4.61 | 64843137.62 | 76.94 | 7.00 | 4.34 | ||
| Maximum of Months | 0.243539E+10 | 4635.94 | 26.00 | 17.83 | 0.327417E+09 | 495.45 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.903671E+09 | 2242.65 | 19-JAN-16:00 | 8.00 | 7.45 | 0.639558E+09 | 1105.23 | 19-JAN-15:00 | 8.00 | 7.45 |
| February | 0.100022E+10 | 3065.13 | 09-FEB-15:01 | 8.00 | 6.01 | 0.583318E+09 | 1103.22 | 09-FEB-15:00 | 8.00 | 5.66 |
| March | 0.150702E+10 | 3141.29 | 30-MAR-14:01 | 12.83 | 7.23 | 0.722085E+09 | 1122.78 | 31-MAR-14:00 | 7.00 | 4.34 |
| April | 0.221221E+10 | 4038.31 | 28-APR-15:00 | 20.10 | 13.70 | 0.709075E+09 | 1277.22 | 21-APR-14:20 | 20.10 | 13.70 |
| May | 0.273120E+10 | 4308.60 | 23-MAY-15:00 | 18.00 | 14.38 | 0.814275E+09 | 1277.24 | 12-MAY-14:20 | 18.00 | 14.38 |
| June | 0.319009E+10 | 5084.88 | 13-JUN-15:00 | 26.00 | 17.83 | 0.519897E+09 | 1277.24 | 07-JUN-14:20 | 26.00 | 17.83 |
| July | 0.218703E+10 | 3238.44 | 24-JUL-14:01 | 19.00 | 15.90 | 0.151048E+09 | 188.42 | 21-JUL-17:10 | 19.00 | 15.90 |
| August | 0.213950E+10 | 3353.14 | 20-AUG-15:40 | 23.67 | 14.78 | 0.168229E+09 | 184.43 | 14-AUG-16:10 | 23.67 | 14.78 |
| September | 0.240250E+10 | 3983.75 | 27-SEP-15:00 | 22.00 | 13.07 | 0.460243E+09 | 1277.23 | 28-SEP-14:20 | 16.00 | 13.03 |
| October | 0.196219E+10 | 3615.71 | 03-OCT-14:01 | 14.00 | 9.33 | 0.715903E+09 | 1277.03 | 05-OCT-14:00 | 15.00 | 8.96 |
| November | 0.139197E+10 | 3322.96 | 10-NOV-15:01 | 11.83 | 8.42 | 0.665008E+09 | 1182.46 | 10-NOV-15:00 | 11.00 | 8.40 |
| December | 0.841552E+09 | 2084.65 | 21-DEC-14:50 | 8.00 | 6.98 | 0.604283E+09 | 1052.93 | 21-DEC-14:00 | 8.00 | 6.98 |
| Annual Sum or Average | 0.224692E+11 | 0.675292E+10 | ||||||||
| Minimum of Months | 0.841552E+09 | 2084.65 | 8.00 | 6.01 | 0.151048E+09 | 184.43 | 7.00 | 4.34 | ||
| Maximum of Months | 0.319009E+10 | 5084.88 | 26.00 | 17.83 | 0.814275E+09 | 1277.24 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.632811E+10 | 10952.50 | 19-JAN-15:40 | 8.33 | 7.46 | 0.317380E+10 | 5380.20 | 19-JAN-15:50 | 8.17 | 7.46 |
| February | 0.656129E+10 | 15162.23 | 09-FEB-15:01 | 8.00 | 6.01 | 0.292556E+10 | 5415.15 | 03-FEB-15:09 | 8.00 | 6.01 |
| March | 0.926150E+10 | 15841.18 | 30-MAR-14:01 | 12.83 | 7.23 | 0.366768E+10 | 5634.91 | 30-MAR-14:00 | 12.00 | 6.56 |
| April | 0.113799E+11 | 17853.10 | 28-APR-14:02 | 20.02 | 12.92 | 0.355609E+10 | 6153.92 | 20-APR-14:20 | 20.02 | 12.92 |
| May | 0.136780E+11 | 18196.73 | 25-MAY-14:05 | 14.50 | 11.61 | 0.404487E+10 | 6153.96 | 02-MAY-14:20 | 14.50 | 11.61 |
| June | 0.153310E+11 | 20512.31 | 13-JUN-15:00 | 26.00 | 17.83 | 0.252887E+10 | 6153.98 | 07-JUN-14:20 | 26.00 | 17.83 |
| July | 0.101562E+11 | 15662.03 | 24-JUL-05:01 | 13.00 | 13.00 | 0.705075E+09 | 829.81 | 24-JUL-14:50 | 19.00 | 15.90 |
| August | 0.100854E+11 | 14669.18 | 20-AUG-15:40 | 23.67 | 14.78 | 0.793402E+09 | 808.05 | 14-AUG-15:50 | 23.67 | 14.78 |
| September | 0.117731E+11 | 17888.18 | 26-SEP-14:01 | 17.83 | 12.89 | 0.224937E+10 | 6153.95 | 19-SEP-14:20 | 17.83 | 12.89 |
| October | 0.106261E+11 | 17555.09 | 03-OCT-14:01 | 14.00 | 9.33 | 0.360830E+10 | 6150.92 | 03-OCT-14:50 | 14.00 | 9.04 |
| November | 0.849163E+10 | 16238.95 | 10-NOV-15:01 | 11.83 | 8.42 | 0.336164E+10 | 5740.35 | 10-NOV-15:09 | 11.83 | 8.42 |
| December | 0.624962E+10 | 10641.59 | 22-DEC-14:10 | 7.00 | 5.54 | 0.301492E+10 | 5265.16 | 22-DEC-14:20 | 7.00 | 5.54 |
| Annual Sum or Average | 0.119922E+12 | 0.336296E+11 | ||||||||
| Minimum of Months | 0.624962E+10 | 10641.59 | 7.00 | 5.54 | 0.705075E+09 | 808.05 | 7.00 | 5.54 | ||
| Maximum of Months | 0.153310E+11 | 20512.31 | 26.00 | 17.83 | 0.404487E+10 | 6153.98 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.121324E+10 | 2591.54 | 19-JAN-15:40 | 8.33 | 7.46 | 0.661582E+09 | 1227.21 | 19-JAN-15:50 | 8.17 | 7.46 |
| February | 0.133420E+10 | 3490.42 | 09-FEB-15:01 | 8.00 | 6.01 | 0.613523E+09 | 1249.23 | 09-FEB-15:50 | 8.00 | 5.73 |
| March | 0.171321E+10 | 3387.54 | 10-MAR-15:01 | 8.83 | 4.79 | 0.741919E+09 | 1203.76 | 10-MAR-15:39 | 8.33 | 4.33 |
| April | 0.267168E+10 | 5634.27 | 28-APR-15:00 | 20.10 | 13.70 | 0.747295E+09 | 1277.24 | 14-APR-14:20 | 20.10 | 13.70 |
| May | 0.312046E+10 | 5508.32 | 22-MAY-15:00 | 24.00 | 16.08 | 0.835847E+09 | 1277.24 | 05-MAY-14:20 | 24.00 | 16.08 |
| June | 0.349532E+10 | 5948.60 | 13-JUN-15:00 | 26.00 | 17.83 | 0.525707E+09 | 1277.24 | 07-JUN-14:20 | 26.00 | 17.83 |
| July | 0.246088E+10 | 3637.52 | 24-JUL-14:01 | 19.00 | 15.90 | 0.160669E+09 | 201.67 | 24-JUL-15:20 | 19.33 | 16.00 |
| August | 0.261987E+10 | 4095.80 | 20-AUG-15:40 | 23.67 | 14.78 | 0.183105E+09 | 201.67 | 21-AUG-15:20 | 21.00 | 15.01 |
| September | 0.313569E+10 | 5802.92 | 25-SEP-15:00 | 22.00 | 13.57 | 0.480436E+09 | 1277.24 | 19-SEP-14:20 | 22.00 | 13.57 |
| October | 0.239992E+10 | 5025.31 | 03-OCT-15:00 | 14.00 | 8.96 | 0.755956E+09 | 1277.23 | 04-OCT-14:20 | 14.00 | 10.28 |
| November | 0.166671E+10 | 3615.09 | 10-NOV-15:01 | 11.83 | 8.42 | 0.695819E+09 | 1277.24 | 10-NOV-15:20 | 11.67 | 8.42 |
| December | 0.104414E+10 | 2425.40 | 21-DEC-14:40 | 8.00 | 6.98 | 0.619418E+09 | 1168.44 | 21-DEC-14:50 | 8.00 | 6.98 |
| Annual Sum or Average | 0.268753E+11 | 0.702128E+10 | ||||||||
| Minimum of Months | 0.104414E+10 | 2425.40 | 8.00 | 4.79 | 0.160669E+09 | 201.67 | 8.00 | 4.33 | ||
| Maximum of Months | 0.349532E+10 | 5948.60 | 26.00 | 17.83 | 0.835847E+09 | 1277.24 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.785658E+10 | 12673.09 | 20-JAN-15:02 | 7.83 | 6.41 | 0.332610E+10 | 5963.74 | 20-JAN-13:20 | 7.83 | 6.41 |
| February | 0.820769E+10 | 17166.52 | 09-FEB-15:01 | 8.00 | 6.01 | 0.311470E+10 | 6104.33 | 03-FEB-14:50 | 8.00 | 6.01 |
| March | 0.102944E+11 | 16847.64 | 10-MAR-15:01 | 8.83 | 4.79 | 0.379447E+10 | 5982.48 | 10-MAR-15:09 | 8.83 | 4.79 |
| April | 0.137124E+11 | 24544.55 | 28-APR-14:30 | 20.05 | 13.23 | 0.371248E+10 | 6153.99 | 14-APR-14:20 | 20.05 | 13.23 |
| May | 0.156406E+11 | 23935.26 | 23-MAY-13:50 | 18.83 | 14.71 | 0.413500E+10 | 6160.70 | 03-MAY-13:39 | 18.83 | 14.71 |
| June | 0.167638E+11 | 24894.48 | 13-JUN-14:00 | 25.10 | 17.45 | 0.256069E+10 | 6153.98 | 07-JUN-14:20 | 25.10 | 17.45 |
| July | 0.115483E+11 | 17029.46 | 24-JUL-05:01 | 13.00 | 13.00 | 0.753451E+09 | 934.99 | 24-JUL-14:50 | 19.00 | 15.90 |
| August | 0.124741E+11 | 18455.76 | 20-AUG-15:40 | 23.67 | 14.78 | 0.868156E+09 | 943.82 | 21-AUG-14:50 | 21.00 | 15.01 |
| September | 0.152696E+11 | 26025.89 | 25-SEP-13:50 | 21.17 | 13.49 | 0.234064E+10 | 6153.97 | 19-SEP-14:20 | 21.17 | 13.49 |
| October | 0.127872E+11 | 23191.26 | 03-OCT-14:02 | 14.00 | 9.33 | 0.379536E+10 | 6153.96 | 31-OCT-14:20 | 12.67 | 7.82 |
| November | 0.990076E+10 | 17431.19 | 10-NOV-15:01 | 11.83 | 8.42 | 0.353676E+10 | 6153.98 | 03-NOV-14:20 | 11.83 | 8.42 |
| December | 0.728477E+10 | 12114.99 | 21-DEC-14:30 | 8.00 | 6.98 | 0.312902E+10 | 5778.73 | 21-DEC-14:39 | 8.00 | 6.98 |
| Annual Sum or Average | 0.141740E+12 | 0.350668E+11 | ||||||||
| Minimum of Months | 0.728477E+10 | 12114.99 | 7.83 | 4.79 | 0.753451E+09 | 934.99 | 7.83 | 4.79 | ||
| Maximum of Months | 0.167638E+11 | 26025.89 | 25.10 | 17.45 | 0.413500E+10 | 6160.70 | 25.10 | 17.45 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.438041E+09 | 1235.54 | 19-JAN-16:00 | 8.00 | 7.45 | 0.245982E+09 | 418.62 | 19-JAN-15:00 | 8.00 | 7.45 |
| February | 0.591090E+09 | 1746.67 | 09-FEB-15:01 | 8.00 | 6.01 | 0.225353E+09 | 426.84 | 09-FEB-15:00 | 8.00 | 5.66 |
| March | 0.986872E+09 | 1794.71 | 31-MAR-14:01 | 7.00 | 4.61 | 0.279571E+09 | 440.14 | 31-MAR-14:00 | 7.00 | 4.34 |
| April | 0.161094E+10 | 3765.00 | 28-APR-15:00 | 20.10 | 13.70 | 0.288549E+09 | 495.44 | 28-APR-14:00 | 20.10 | 13.70 |
| May | 0.212003E+10 | 4167.36 | 23-MAY-15:00 | 18.00 | 14.38 | 0.330628E+09 | 495.44 | 26-MAY-14:00 | 16.00 | 13.03 |
| June | 0.261232E+10 | 4811.42 | 13-JUN-15:00 | 26.00 | 17.83 | 0.209600E+09 | 495.45 | 09-JUN-14:09 | 26.00 | 17.83 |
| July | 0.156868E+10 | 2237.59 | 24-JUL-16:00 | 20.00 | 16.18 | 66239388.21 | 78.23 | 24-JUL-14:20 | 20.00 | 16.18 |
| August | 0.161945E+10 | 2040.72 | 21-AUG-14:02 | 21.00 | 15.01 | 74114603.89 | 78.22 | 14-AUG-16:10 | 21.00 | 15.01 |
| September | 0.198596E+10 | 3812.05 | 27-SEP-15:00 | 22.00 | 13.07 | 0.188409E+09 | 495.45 | 19-SEP-14:09 | 22.00 | 13.07 |
| October | 0.139100E+10 | 2574.37 | 03-OCT-15:00 | 14.00 | 8.96 | 0.287695E+09 | 495.44 | 02-OCT-14:20 | 14.00 | 8.96 |
| November | 0.933352E+09 | 1927.02 | 10-NOV-15:01 | 11.83 | 8.42 | 0.258190E+09 | 463.82 | 10-NOV-15:00 | 11.00 | 8.40 |
| December | 0.354872E+09 | 1152.67 | 21-DEC-15:10 | 7.83 | 6.90 | 0.232970E+09 | 400.89 | 21-DEC-15:20 | 7.67 | 6.81 |
| Annual Sum or Average | 0.162126E+11 | 0.268730E+10 | ||||||||
| Minimum of Months | 0.354872E+09 | 1152.67 | 7.00 | 4.61 | 66239388.21 | 78.22 | 7.00 | 4.34 | ||
| Maximum of Months | 0.261232E+10 | 4811.42 | 26.00 | 17.83 | 0.330628E+09 | 495.45 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.914660E+09 | 2254.27 | 19-JAN-16:00 | 8.00 | 7.45 | 0.640215E+09 | 1109.04 | 19-JAN-15:00 | 8.00 | 7.45 |
| February | 0.101572E+10 | 3081.23 | 09-FEB-15:01 | 8.00 | 6.01 | 0.584388E+09 | 1108.11 | 09-FEB-15:00 | 8.00 | 5.66 |
| March | 0.153620E+10 | 3162.75 | 30-MAR-14:01 | 12.83 | 7.23 | 0.724565E+09 | 1131.07 | 31-MAR-14:00 | 7.00 | 4.34 |
| April | 0.225628E+10 | 4138.92 | 28-APR-15:00 | 20.10 | 13.70 | 0.714796E+09 | 1277.22 | 21-APR-14:20 | 20.10 | 13.70 |
| May | 0.278729E+10 | 4429.92 | 23-MAY-15:00 | 18.00 | 14.38 | 0.819579E+09 | 1277.24 | 12-MAY-14:20 | 18.00 | 14.38 |
| June | 0.325625E+10 | 5198.51 | 13-JUN-15:00 | 26.00 | 17.83 | 0.522544E+09 | 1277.24 | 07-JUN-14:20 | 26.00 | 17.83 |
| July | 0.225122E+10 | 3289.28 | 24-JUL-14:01 | 19.00 | 15.90 | 0.152765E+09 | 190.81 | 21-JUL-17:10 | 19.00 | 15.90 |
| August | 0.220082E+10 | 3412.10 | 20-AUG-15:40 | 23.67 | 14.78 | 0.169520E+09 | 186.75 | 14-AUG-16:10 | 23.67 | 14.78 |
| September | 0.244077E+10 | 4048.30 | 27-SEP-15:00 | 22.00 | 13.07 | 0.462187E+09 | 1277.23 | 28-SEP-14:20 | 16.00 | 13.03 |
| October | 0.198768E+10 | 3639.70 | 03-OCT-14:01 | 14.00 | 9.33 | 0.719121E+09 | 1277.07 | 05-OCT-14:00 | 15.00 | 8.96 |
| November | 0.141097E+10 | 3340.95 | 10-NOV-15:01 | 11.83 | 8.42 | 0.666824E+09 | 1188.06 | 10-NOV-15:00 | 11.00 | 8.40 |
| December | 0.847566E+09 | 2094.73 | 21-DEC-14:50 | 8.00 | 6.98 | 0.604616E+09 | 1056.01 | 21-DEC-14:00 | 8.00 | 6.98 |
| Annual Sum or Average | 0.229054E+11 | 0.678112E+10 | ||||||||
| Minimum of Months | 0.847566E+09 | 2094.73 | 8.00 | 6.01 | 0.152765E+09 | 186.75 | 7.00 | 4.34 | ||
| Maximum of Months | 0.325625E+10 | 5198.51 | 26.00 | 17.83 | 0.819579E+09 | 1277.24 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.420905E+10 | 7291.66 | 19-JAN-15:40 | 8.33 | 7.46 | 0.209985E+10 | 3572.82 | 19-JAN-15:39 | 8.33 | 7.46 |
| February | 0.438545E+10 | 10081.06 | 09-FEB-15:01 | 8.00 | 6.01 | 0.193799E+10 | 3597.53 | 03-FEB-15:09 | 8.00 | 6.01 |
| March | 0.623901E+10 | 10552.56 | 30-MAR-14:01 | 12.83 | 7.23 | 0.243541E+10 | 3752.21 | 30-MAR-14:00 | 12.00 | 6.56 |
| April | 0.769625E+10 | 11805.09 | 28-APR-14:02 | 20.02 | 12.92 | 0.236973E+10 | 4063.93 | 19-APR-14:20 | 20.02 | 12.92 |
| May | 0.925313E+10 | 12340.03 | 23-MAY-14:03 | 18.83 | 14.71 | 0.269037E+10 | 4063.94 | 02-MAY-14:20 | 18.83 | 14.71 |
| June | 0.103996E+11 | 14085.38 | 13-JUN-15:00 | 26.00 | 17.83 | 0.168098E+10 | 4063.95 | 07-JUN-14:20 | 26.00 | 17.83 |
| July | 0.696880E+10 | 10498.84 | 24-JUL-05:01 | 13.00 | 13.00 | 0.472851E+09 | 558.79 | 24-JUL-14:50 | 19.00 | 15.90 |
| August | 0.689811E+10 | 9897.21 | 20-AUG-15:40 | 23.67 | 14.78 | 0.528975E+09 | 543.26 | 14-AUG-15:50 | 23.67 | 14.78 |
| September | 0.793706E+10 | 11821.53 | 26-SEP-14:01 | 17.83 | 12.89 | 0.149249E+10 | 4063.94 | 19-SEP-14:20 | 17.83 | 12.89 |
| October | 0.712238E+10 | 11652.26 | 03-OCT-14:01 | 14.00 | 9.33 | 0.239705E+10 | 4063.41 | 05-OCT-14:00 | 15.00 | 8.96 |
| November | 0.569345E+10 | 10818.67 | 10-NOV-15:01 | 11.83 | 8.42 | 0.222906E+10 | 3823.73 | 10-NOV-15:09 | 11.83 | 8.42 |
| December | 0.413223E+10 | 7073.74 | 22-DEC-14:10 | 7.00 | 5.54 | 0.199281E+10 | 3492.74 | 22-DEC-14:09 | 7.00 | 5.54 |
| Annual Sum or Average | 0.809346E+11 | 0.223275E+11 | ||||||||
| Minimum of Months | 0.413223E+10 | 7073.74 | 7.00 | 5.54 | 0.472851E+09 | 543.26 | 7.00 | 5.54 | ||
| Maximum of Months | 0.103996E+11 | 14085.38 | 26.00 | 17.83 | 0.269037E+10 | 4063.95 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.321973E+10 | 4087.12 | 27-JAN-15:20 | 8.47 | 7.37 | 0.166821E+10 | 1953.45 | 27-JAN-15:30 | 8.35 | 7.27 |
| February | 0.319109E+10 | 5531.53 | 09-FEB-15:01 | 8.00 | 6.01 | 0.155639E+10 | 1970.75 | 03-FEB-15:09 | 8.00 | 6.01 |
| March | 0.418205E+10 | 5796.59 | 30-MAR-14:01 | 12.83 | 7.23 | 0.198149E+10 | 2072.60 | 31-MAR-16:10 | 9.00 | 4.96 |
| April | 0.482121E+10 | 7076.19 | 28-APR-15:07 | 20.08 | 13.47 | 0.189700E+10 | 2090.03 | 14-APR-14:20 | 20.08 | 13.47 |
| May | 0.579001E+10 | 7391.71 | 23-MAY-14:03 | 18.83 | 14.71 | 0.212307E+10 | 2092.46 | 03-MAY-13:39 | 18.83 | 14.71 |
| June | 0.709445E+10 | 8176.78 | 13-JUN-15:00 | 26.00 | 17.83 | 0.214389E+10 | 2090.03 | 07-JUN-14:20 | 26.00 | 17.83 |
| July | 0.430924E+10 | 5784.04 | 24-JUL-14:01 | 19.00 | 15.90 | 0.916093E+09 | 1070.58 | 24-JUL-14:50 | 19.00 | 15.90 |
| August | 0.446104E+10 | 5555.36 | 18-AUG-14:02 | 19.83 | 16.14 | 0.102157E+10 | 1046.92 | 14-AUG-15:50 | 19.83 | 16.14 |
| September | 0.542699E+10 | 7322.23 | 13-SEP-14:50 | 23.00 | 16.22 | 0.188530E+10 | 2090.03 | 19-SEP-14:20 | 13.67 | 13.67 |
| October | 0.443365E+10 | 6195.86 | 04-OCT-14:04 | 14.00 | 10.28 | 0.194109E+10 | 2090.03 | 13-OCT-14:20 | 11.00 | 11.00 |
| November | 0.384110E+10 | 5910.78 | 10-NOV-15:01 | 11.83 | 8.42 | 0.180416E+10 | 2090.02 | 10-NOV-16:19 | 9.67 | 7.83 |
| December | 0.318816E+10 | 3976.07 | 22-DEC-14:10 | 7.00 | 5.54 | 0.158826E+10 | 1912.36 | 22-DEC-14:09 | 7.00 | 5.54 |
| Annual Sum or Average | 0.539587E+11 | 0.205265E+11 | ||||||||
| Minimum of Months | 0.318816E+10 | 3976.07 | 7.00 | 5.54 | 0.916093E+09 | 1046.92 | 7.00 | 4.96 | ||
| Maximum of Months | 0.709445E+10 | 8176.78 | 26.00 | 17.83 | 0.214389E+10 | 2092.46 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.608452E+09 | 2341.35 | 25-JAN-15:10 | 10.67 | 9.25 | 0.694036E+09 | 1120.39 | 19-JAN-15:30 | 10.67 | 9.25 |
| February | 0.970257E+09 | 3511.75 | 09-FEB-15:01 | 8.00 | 6.01 | 0.635044E+09 | 1162.58 | 09-FEB-15:39 | 8.00 | 5.80 |
| March | 0.197398E+10 | 3713.72 | 31-MAR-14:01 | 7.00 | 4.61 | 0.793135E+09 | 1236.12 | 31-MAR-14:00 | 7.00 | 4.34 |
| April | 0.370469E+10 | 8797.77 | 28-APR-15:00 | 20.10 | 13.70 | 0.840572E+09 | 1408.95 | 28-APR-14:00 | 20.10 | 13.70 |
| May | 0.549981E+10 | 10410.16 | 23-MAY-14:50 | 18.17 | 14.45 | 0.969557E+09 | 1409.47 | 03-MAY-13:39 | 18.17 | 14.45 |
| June | 0.735781E+10 | 13993.60 | 14-JUN-07:01 | 12.00 | 12.00 | 0.603973E+09 | 1427.68 | 13-JUN-07:10 | 12.00 | 12.00 |
| July | 0.451102E+10 | 8605.55 | 24-JUL-15:50 | 19.83 | 16.14 | 0.203839E+09 | 222.47 | 21-JUL-17:00 | 19.83 | 16.14 |
| August | 0.411193E+10 | 6275.00 | 21-AUG-15:30 | 21.00 | 15.01 | 0.229748E+09 | 222.47 | 21-AUG-14:09 | 21.00 | 15.01 |
| September | 0.458284E+10 | 8479.95 | 27-SEP-14:40 | 22.00 | 13.23 | 0.543288E+09 | 1408.96 | 19-SEP-14:09 | 22.00 | 13.23 |
| October | 0.286527E+10 | 5075.57 | 03-OCT-14:30 | 14.00 | 9.18 | 0.819513E+09 | 1408.93 | 02-OCT-14:20 | 14.00 | 9.18 |
| November | 0.166270E+10 | 3823.83 | 10-NOV-15:01 | 11.83 | 8.42 | 0.721336E+09 | 1251.98 | 10-NOV-14:50 | 11.83 | 8.42 |
| December | 0.492818E+09 | 2231.29 | 22-DEC-14:10 | 7.00 | 5.54 | 0.659668E+09 | 1086.31 | 22-DEC-14:30 | 7.00 | 5.54 |
| Annual Sum or Average | 0.383416E+11 | 0.771371E+10 | ||||||||
| Minimum of Months | 0.492818E+09 | 2231.29 | 7.00 | 4.61 | 0.203839E+09 | 222.47 | 7.00 | 4.34 | ||
| Maximum of Months | 0.735781E+10 | 13993.60 | 22.00 | 16.14 | 0.969557E+09 | 1427.68 | 22.00 | 16.14 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 16012914.98 | 1366.39 | 24-JAN-18:07 | 7.83 | 6.89 | 0.326158E+09 | 653.28 | 17-JAN-12:00 | 7.83 | 6.89 |
| February | 21711661.29 | 1366.77 | 08-FEB-18:07 | 6.67 | 5.76 | 0.323790E+09 | 653.18 | 22-FEB-11:30 | 10.00 | 8.67 |
| March | 39069909.52 | 1372.08 | 09-MAR-18:07 | 6.88 | 4.64 | 0.401359E+09 | 653.20 | 31-MAR-13:00 | 7.00 | 4.66 |
| April | 0.654437E+09 | 3094.54 | 30-APR-12:29 | 22.00 | 13.54 | 0.396783E+09 | 882.51 | 28-APR-14:09 | 22.00 | 13.54 |
| May | 0.917452E+09 | 4957.43 | 22-MAY-15:00 | 24.00 | 16.08 | 0.451633E+09 | 882.53 | 22-MAY-14:50 | 24.00 | 16.08 |
| June | 0.175876E+10 | 9742.10 | 13-JUN-15:00 | 26.00 | 17.83 | 0.301699E+09 | 926.89 | 13-JUN-14:00 | 26.00 | 17.83 |
| July | 0.150140E+10 | 9909.35 | 21-JUL-14:20 | 27.00 | 16.08 | 0.105719E+09 | 151.03 | 21-JUL-14:30 | 27.00 | 16.02 |
| August | 0.167024E+10 | 7196.21 | 14-AUG-15:00 | 25.00 | 16.02 | 0.123017E+09 | 139.35 | 14-AUG-15:20 | 25.33 | 15.98 |
| September | 0.157808E+10 | 4946.35 | 25-SEP-15:10 | 22.00 | 13.57 | 0.286907E+09 | 882.53 | 25-SEP-14:09 | 22.00 | 13.57 |
| October | 0.471492E+09 | 2510.45 | 01-OCT-12:52 | 12.00 | 9.78 | 0.413539E+09 | 754.03 | 02-OCT-12:50 | 14.00 | 10.70 |
| November | 55686663.19 | 1386.33 | 01-NOV-17:07 | 7.00 | 6.56 | 0.377730E+09 | 653.20 | 02-NOV-10:00 | 11.20 | 7.91 |
| December | 15621026.24 | 1347.46 | 08-DEC-18:07 | 3.67 | 2.95 | 0.319826E+09 | 653.12 | 21-DEC-14:00 | 8.00 | 6.98 |
| Annual Sum or Average | 0.869997E+10 | 0.382816E+10 | ||||||||
| Minimum of Months | 15621026.24 | 1347.46 | 3.67 | 2.95 | 0.105719E+09 | 139.35 | 7.00 | 4.66 | ||
| Maximum of Months | 0.175876E+10 | 9909.35 | 27.00 | 17.83 | 0.451633E+09 | 926.89 | 27.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.201533E+10 | 2336.65 | 27-JAN-15:20 | 8.47 | 7.37 | 0.109128E+09 | 193.14 | 27-JAN-15:30 | 8.35 | 7.27 |
| February | 0.199743E+10 | 3187.80 | 09-FEB-15:01 | 8.00 | 6.01 | 0.106124E+09 | 199.20 | 09-FEB-15:39 | 8.00 | 5.80 |
| March | 0.256831E+10 | 3360.84 | 31-MAR-14:01 | 7.00 | 4.61 | 0.136079E+09 | 211.58 | 31-MAR-14:00 | 7.00 | 4.34 |
| April | 0.302968E+10 | 12025.39 | 30-APR-12:29 | 22.00 | 13.54 | 0.143668E+09 | 247.13 | 28-APR-14:00 | 22.00 | 13.54 |
| May | 0.373643E+10 | 9526.35 | 21-MAY-17:42 | 20.00 | 13.14 | 0.166102E+09 | 247.12 | 22-MAY-14:09 | 23.17 | 15.81 |
| June | 0.456429E+10 | 12259.91 | 12-JUN-20:13 | 20.00 | 15.40 | 0.104870E+09 | 247.13 | 09-JUN-14:09 | 20.00 | 15.40 |
| July | 0.319042E+10 | 10526.04 | 22-JUL-14:48 | 28.83 | 16.92 | 32618237.25 | 38.52 | 24-JUL-14:50 | 19.00 | 15.90 |
| August | 0.330393E+10 | 12114.26 | 20-AUG-15:40 | 23.67 | 14.78 | 36375027.34 | 37.09 | 21-AUG-14:50 | 21.00 | 15.01 |
| September | 0.332287E+10 | 10018.77 | 10-SEP-14:38 | 21.67 | 16.29 | 93425986.56 | 247.13 | 19-SEP-14:09 | 13.83 | 13.83 |
| October | 0.271739E+10 | 3901.92 | 03-OCT-14:01 | 14.00 | 9.33 | 0.139528E+09 | 243.98 | 03-OCT-14:50 | 14.00 | 9.04 |
| November | 0.231262E+10 | 3417.81 | 10-NOV-15:01 | 11.83 | 8.42 | 0.123005E+09 | 213.21 | 10-NOV-14:50 | 11.83 | 8.42 |
| December | 0.197544E+10 | 2251.96 | 22-DEC-14:10 | 7.00 | 5.54 | 0.105534E+09 | 187.62 | 22-DEC-14:30 | 7.00 | 5.54 |
| Annual Sum or Average | 0.347341E+11 | 0.129646E+10 | ||||||||
| Minimum of Months | 0.197544E+10 | 2251.96 | 7.00 | 4.61 | 32618237.25 | 37.09 | 7.00 | 4.34 | ||
| Maximum of Months | 0.456429E+10 | 12259.91 | 28.83 | 16.92 | 0.166102E+09 | 247.13 | 23.17 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.736180E+09 | 1078.60 | 27-JAN-15:20 | 8.47 | 7.37 | 0.206720E+09 | 387.74 | 27-JAN-15:30 | 8.35 | 7.27 |
| February | 0.808087E+09 | 1628.73 | 09-FEB-15:01 | 8.00 | 6.01 | 0.204788E+09 | 405.45 | 09-FEB-15:50 | 8.00 | 5.73 |
| March | 0.113279E+10 | 1751.72 | 31-MAR-14:01 | 7.00 | 4.61 | 0.269646E+09 | 438.22 | 31-MAR-14:00 | 7.00 | 4.34 |
| April | 0.151671E+10 | 2389.77 | 28-APR-14:02 | 20.02 | 12.92 | 0.300880E+09 | 592.60 | 28-APR-14:00 | 20.10 | 13.70 |
| May | 0.186518E+10 | 2512.16 | 23-MAY-14:01 | 18.83 | 14.71 | 0.361132E+09 | 621.06 | 23-MAY-14:00 | 18.00 | 14.38 |
| June | 0.225979E+10 | 2982.29 | 13-JUN-15:00 | 26.00 | 17.83 | 0.238916E+09 | 621.09 | 13-JUN-13:20 | 26.00 | 17.83 |
| July | 0.179848E+10 | 5098.24 | 22-JUL-16:10 | 29.00 | 16.57 | 74834403.36 | 93.19 | 24-JUL-16:10 | 19.83 | 16.13 |
| August | 0.183046E+10 | 2200.64 | 20-AUG-15:40 | 23.67 | 14.78 | 82266822.37 | 87.28 | 21-AUG-16:10 | 21.00 | 15.01 |
| September | 0.168926E+10 | 2357.73 | 26-SEP-14:01 | 17.83 | 12.89 | 0.203736E+09 | 588.50 | 27-SEP-14:00 | 22.00 | 13.07 |
| October | 0.132699E+10 | 2141.71 | 03-OCT-14:01 | 14.00 | 9.33 | 0.288161E+09 | 525.18 | 03-OCT-14:00 | 14.00 | 8.96 |
| November | 0.102367E+10 | 1839.84 | 10-NOV-15:01 | 11.83 | 8.42 | 0.245853E+09 | 450.47 | 10-NOV-15:09 | 11.83 | 8.42 |
| December | 0.738890E+09 | 1002.95 | 22-DEC-14:10 | 7.00 | 5.54 | 0.200454E+09 | 370.15 | 22-DEC-14:20 | 7.00 | 5.54 |
| Annual Sum or Average | 0.167265E+11 | 0.267739E+10 | ||||||||
| Minimum of Months | 0.736180E+09 | 1002.95 | 7.00 | 4.61 | 74834403.36 | 87.28 | 7.00 | 4.34 | ||
| Maximum of Months | 0.225979E+10 | 5098.24 | 29.00 | 17.83 | 0.361132E+09 | 621.09 | 26.00 | 17.83 |
Report: ZoneCoolingSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.161299E+10 | 12230.51 | 20-JAN-15:01 | 7.83 | 6.41 | 0.506347E+09 | 1155.76 | 20-JAN-15:09 | 7.83 | 6.41 |
| February | 0.202513E+10 | 21188.28 | 09-FEB-15:01 | 8.00 | 6.01 | 0.472153E+09 | 1175.87 | 09-FEB-15:09 | 8.00 | 6.01 |
| March | 0.303873E+10 | 21587.25 | 30-MAR-14:01 | 12.83 | 7.23 | 0.587818E+09 | 1197.57 | 31-MAR-14:09 | 7.00 | 4.61 |
| April | 0.637642E+10 | 24405.69 | 30-APR-12:29 | 22.00 | 13.54 | 0.609062E+09 | 1197.65 | 14-APR-14:09 | 22.00 | 13.54 |
| May | 0.813501E+10 | 22437.75 | 25-MAY-14:01 | 14.50 | 11.61 | 0.681954E+09 | 1197.61 | 22-MAY-14:09 | 14.50 | 11.61 |
| June | 0.105643E+11 | 22410.61 | 09-JUN-14:01 | 18.33 | 13.88 | 0.688566E+09 | 1202.80 | 26-JUN-07:10 | 19.67 | 14.49 |
| July | 0.714976E+10 | 22001.25 | 24-JUL-14:01 | 19.00 | 15.90 | 0.349513E+09 | 630.31 | 12-JUL-14:09 | 19.00 | 15.90 |
| August | 0.743736E+10 | 24562.79 | 20-AUG-15:40 | 23.67 | 14.78 | 0.399011E+09 | 630.32 | 21-AUG-14:09 | 21.00 | 15.01 |
| September | 0.882602E+10 | 24667.26 | 10-SEP-14:38 | 21.67 | 16.29 | 0.610710E+09 | 1197.64 | 19-SEP-14:09 | 13.83 | 13.83 |
| October | 0.477634E+10 | 22129.28 | 03-OCT-14:01 | 14.00 | 9.33 | 0.609798E+09 | 1197.58 | 03-OCT-12:09 | 14.00 | 9.33 |
| November | 0.285952E+10 | 21718.79 | 10-NOV-15:01 | 11.83 | 8.42 | 0.543922E+09 | 1197.56 | 03-NOV-12:09 | 11.83 | 8.42 |
| December | 0.135936E+10 | 4423.36 | 21-DEC-15:01 | 7.83 | 6.90 | 0.473751E+09 | 1079.21 | 21-DEC-15:09 | 7.83 | 6.90 |
| Annual Sum or Average | 0.641609E+11 | 0.653260E+10 | ||||||||
| Minimum of Months | 0.135936E+10 | 4423.36 | 7.83 | 6.01 | 0.349513E+09 | 630.31 | 7.00 | 4.61 | ||
| Maximum of Months | 0.105643E+11 | 24667.26 | 23.67 | 16.29 | 0.688566E+09 | 1202.80 | 22.00 | 15.90 |
Report: ZoneCoolingSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.510531E+10 | 7149.71 | 19-JAN-17:00 | 6.00 | 6.00 | 0.268337E+10 | 5089.63 | 19-JAN-17:10 | 5.83 | 5.75 |
| February | 0.532883E+10 | 8902.25 | 09-FEB-15:01 | 8.00 | 6.01 | 0.251901E+10 | 5174.89 | 10-FEB-17:10 | 5.67 | 4.36 |
| March | 0.706508E+10 | 9432.83 | 31-MAR-14:01 | 7.00 | 4.61 | 0.320478E+10 | 5528.05 | 31-MAR-15:30 | 8.00 | 4.68 |
| April | 0.975735E+10 | 23357.83 | 18-APR-06:01 | 8.17 | 7.05 | 0.311769E+10 | 5528.23 | 28-APR-15:09 | 20.08 | 13.47 |
| May | 0.122302E+11 | 24295.70 | 23-MAY-05:01 | 9.67 | 9.01 | 0.345700E+10 | 5531.19 | 15-MAY-15:39 | 9.67 | 9.01 |
| June | 0.147254E+11 | 25611.01 | 27-JUN-05:01 | 14.17 | 14.17 | 0.347443E+10 | 5535.36 | 13-JUN-15:20 | 14.17 | 14.17 |
| July | 0.103157E+11 | 26594.81 | 17-JUL-05:01 | 14.00 | 12.94 | 0.187788E+10 | 2036.74 | 21-JUL-17:00 | 22.00 | 15.41 |
| August | 0.103611E+11 | 25260.17 | 07-AUG-05:01 | 10.17 | 9.06 | 0.212446E+10 | 2036.71 | 15-AUG-14:20 | 18.67 | 15.19 |
| September | 0.108259E+11 | 24204.90 | 11-SEP-05:01 | 9.17 | 9.17 | 0.308097E+10 | 5528.17 | 06-SEP-15:20 | 9.17 | 9.17 |
| October | 0.763622E+10 | 12418.12 | 11-OCT-15:07 | 16.33 | 10.99 | 0.311093E+10 | 5528.16 | 10-OCT-15:20 | 16.33 | 10.99 |
| November | 0.621214E+10 | 9416.44 | 10-NOV-15:01 | 11.83 | 8.42 | 0.284492E+10 | 5335.75 | 10-NOV-17:10 | 6.83 | 6.31 |
| December | 0.497946E+10 | 6734.29 | 22-DEC-17:00 | 5.00 | 4.08 | 0.253598E+10 | 4882.73 | 22-DEC-17:10 | 5.00 | 4.08 |
| Annual Sum or Average | 0.104543E+12 | 0.340314E+11 | ||||||||
| Minimum of Months | 0.497946E+10 | 6734.29 | 5.00 | 4.08 | 0.187788E+10 | 2036.71 | 5.00 | 4.08 | ||
| Maximum of Months | 0.147254E+11 | 26594.81 | 16.33 | 14.17 | 0.347443E+10 | 5535.36 | 22.00 | 15.41 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.989765E+10 | 72774.09 | 10-JAN-06:01 | -4.0 | -4.9 | 0.642747E+10 | 8101.51 | 02-JAN-12:20 | -4.0 | -4.9 |
| February | 0.954692E+10 | 69139.89 | 17-FEB-06:11 | -3.3 | -3.3 | 0.581019E+10 | 8101.55 | 03-FEB-10:09 | -3.3 | -3.3 |
| March | 0.123978E+11 | 64211.57 | 08-MAR-06:01 | -0.2 | -1.3 | 0.671304E+10 | 8101.40 | 01-MAR-12:20 | -0.2 | -1.3 |
| April | 0.145665E+11 | 61465.85 | 20-APR-05:11 | 1.33 | 0.08 | 0.617420E+10 | 8102.43 | 27-APR-11:09 | 16.00 | 10.99 |
| May | 0.166344E+11 | 55694.21 | 10-MAY-05:01 | 3.50 | 2.84 | 0.657040E+10 | 8102.48 | 31-MAY-11:39 | 16.00 | 12.93 |
| June | 0.169536E+11 | 52689.03 | 08-JUN-05:11 | 6.33 | 4.33 | 0.611487E+10 | 8102.47 | 01-JUN-11:50 | 6.33 | 4.33 |
| July | 0.144537E+11 | 50262.48 | 31-JUL-05:01 | 7.50 | 5.48 | 0.565773E+10 | 7012.58 | 18-JUL-10:09 | 7.50 | 5.48 |
| August | 0.150472E+11 | 46362.09 | 24-AUG-05:11 | 8.67 | 7.29 | 0.599185E+10 | 7012.58 | 17-AUG-09:20 | 8.67 | 7.29 |
| September | 0.149526E+11 | 51495.74 | 21-SEP-05:11 | 5.67 | 4.88 | 0.586088E+10 | 8102.49 | 19-SEP-09:30 | 5.67 | 4.88 |
| October | 0.134566E+11 | 55600.68 | 06-OCT-05:11 | 3.00 | 3.00 | 0.642764E+10 | 8102.40 | 11-OCT-10:30 | 16.50 | 10.88 |
| November | 0.112694E+11 | 65732.19 | 29-NOV-06:01 | -1.0 | -1.8 | 0.631695E+10 | 8102.39 | 24-NOV-12:09 | -1.0 | -1.8 |
| December | 0.942272E+10 | 64050.72 | 15-DEC-06:01 | -0.3 | -1.0 | 0.628465E+10 | 8101.65 | 18-DEC-10:09 | 5.33 | 4.28 |
| Annual Sum or Average | 0.158599E+12 | 0.743499E+11 | ||||||||
| Minimum of Months | 0.942272E+10 | 46362.09 | -4.0 | -4.9 | 0.565773E+10 | 7012.58 | -4.0 | -4.9 | ||
| Maximum of Months | 0.169536E+11 | 72774.09 | 8.67 | 7.29 | 0.671304E+10 | 8102.49 | 16.50 | 12.93 |
Report: ZoneCoolingSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.126298E+11 | 31095.99 | 31-JAN-08:61 | 1.17 | 0.75 | 0.749908E+10 | 16219.05 | 18-JAN-13:09 | 1.17 | 0.75 |
| February | 0.123131E+11 | 35091.22 | 17-FEB-08:61 | -2.3 | -2.4 | 0.670984E+10 | 14828.50 | 07-FEB-14:00 | -2.3 | -2.4 |
| March | 0.155411E+11 | 32063.41 | 21-MAR-07:01 | 1.33 | 0.86 | 0.845016E+10 | 16246.75 | 28-MAR-11:39 | 12.00 | 6.73 |
| April | 0.149548E+11 | 46526.71 | 30-APR-14:02 | 23.17 | 12.84 | 0.845343E+10 | 16256.90 | 28-APR-11:50 | 23.17 | 12.84 |
| May | 0.173777E+11 | 29150.60 | 23-MAY-08:07 | 17.33 | 14.10 | 0.948159E+10 | 16257.82 | 23-MAY-08:00 | 19.00 | 14.78 |
| June | 0.182465E+11 | 51748.80 | 13-JUN-05:01 | 14.50 | 12.20 | 0.992667E+10 | 16258.06 | 23-JUN-12:09 | 16.50 | 14.26 |
| July | 0.799375E+10 | 50419.75 | 24-JUL-05:01 | 13.00 | 13.00 | 0.221751E+10 | 5989.55 | 24-JUL-16:30 | 19.50 | 16.04 |
| August | 0.790296E+10 | 44190.38 | 20-AUG-16:03 | 23.67 | 14.78 | 0.261554E+10 | 5989.62 | 17-AUG-16:49 | 23.67 | 14.78 |
| September | 0.148828E+11 | 28396.53 | 12-SEP-08:06 | 16.33 | 13.27 | 0.869877E+10 | 16258.10 | 11-SEP-08:00 | 16.33 | 13.27 |
| October | 0.142636E+11 | 30260.08 | 12-OCT-07:01 | 3.67 | 3.67 | 0.881460E+10 | 16256.26 | 11-OCT-11:30 | 3.67 | 3.67 |
| November | 0.137421E+11 | 33948.29 | 29-NOV-08:61 | -0.7 | -1.6 | 0.791872E+10 | 16247.59 | 24-NOV-12:30 | -0.7 | -1.6 |
| December | 0.124356E+11 | 32111.07 | 08-DEC-08:61 | 1.00 | 0.66 | 0.696469E+10 | 14454.49 | 04-DEC-14:09 | 1.00 | 0.66 |
| Annual Sum or Average | 0.162284E+12 | 0.877506E+11 | ||||||||
| Minimum of Months | 0.790296E+10 | 28396.53 | -2.3 | -2.4 | 0.221751E+10 | 5989.55 | -2.3 | -2.4 | ||
| Maximum of Months | 0.182465E+11 | 51748.80 | 23.67 | 14.78 | 0.992667E+10 | 16258.10 | 23.67 | 16.04 |
Report: ZoneCoolingSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.310398E+10 | 4883.51 | 27-JAN-15:35 | 8.23 | 7.17 | 0.111424E+10 | 2004.45 | 27-JAN-15:50 | 8.12 | 7.07 |
| February | 0.350375E+10 | 6627.16 | 09-FEB-15:01 | 8.00 | 6.01 | 0.105592E+10 | 2047.33 | 03-FEB-15:09 | 8.00 | 6.01 |
| March | 0.497652E+10 | 6896.41 | 30-MAR-14:02 | 12.83 | 7.23 | 0.136352E+10 | 2059.31 | 31-MAR-14:20 | 7.00 | 4.56 |
| April | 0.792265E+10 | 14188.73 | 28-APR-15:00 | 20.10 | 13.70 | 0.129244E+10 | 2060.46 | 26-APR-07:49 | 20.10 | 13.70 |
| May | 0.102161E+11 | 21983.89 | 23-MAY-07:01 | 14.50 | 12.54 | 0.143056E+10 | 2110.36 | 23-MAY-07:10 | 14.50 | 12.54 |
| June | 0.124119E+11 | 22599.32 | 13-JUN-07:02 | 19.33 | 14.98 | 0.884094E+09 | 2214.07 | 13-JUN-07:10 | 19.33 | 14.98 |
| July | 0.704453E+10 | 10616.23 | 23-JUL-11:45 | 21.00 | 15.99 | 0.300567E+09 | 325.17 | 21-JUL-17:00 | 21.00 | 15.99 |
| August | 0.693491E+10 | 8818.15 | 21-AUG-13:30 | 21.00 | 14.72 | 0.341145E+09 | 325.17 | 24-AUG-16:40 | 18.33 | 12.14 |
| September | 0.918551E+10 | 13866.80 | 25-SEP-14:20 | 21.33 | 13.57 | 0.801916E+09 | 2059.45 | 21-SEP-08:09 | 21.33 | 13.57 |
| October | 0.623758E+10 | 10390.10 | 03-OCT-14:02 | 14.00 | 9.33 | 0.133738E+10 | 2059.33 | 06-OCT-08:09 | 8.83 | 7.37 |
| November | 0.453368E+10 | 7494.92 | 10-NOV-14:10 | 12.00 | 8.83 | 0.124353E+10 | 2059.32 | 08-NOV-15:20 | 12.00 | 8.83 |
| December | 0.315151E+10 | 4651.02 | 22-DEC-14:10 | 7.00 | 5.54 | 0.105776E+10 | 1930.13 | 22-DEC-14:20 | 7.00 | 5.54 |
| Annual Sum or Average | 0.792226E+11 | 0.122231E+11 | ||||||||
| Minimum of Months | 0.310398E+10 | 4651.02 | 7.00 | 5.54 | 0.300567E+09 | 325.17 | 7.00 | 4.56 | ||
| Maximum of Months | 0.124119E+11 | 22599.32 | 21.33 | 15.99 | 0.143056E+10 | 2214.07 | 21.33 | 15.99 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.248392E+09 | 6247.58 | 09-JAN-06:11 | -2.0 |
| February | 0.107180E+09 | 5881.82 | 27-FEB-07:11 | 6.00 |
| March | 98201528.82 | 5975.81 | 06-MAR-07:11 | 4.67 |
| April | 9189355.27 | 5002.77 | 03-APR-06:11 | 3.33 |
| May | 4035433.14 | 4523.23 | 05-MAY-07:01 | 7.17 |
| June | 779407.59 | 4341.02 | 30-JUN-07:01 | 12.00 |
| July | 4929538.16 | 4561.43 | 05-JUL-07:01 | 12.17 |
| August | 7017545.43 | 4536.59 | 30-AUG-07:01 | 12.33 |
| September | 1397375.62 | 4466.11 | 01-SEP-07:01 | 14.33 |
| October | 10651080.07 | 4985.84 | 23-OCT-06:11 | 4.00 |
| November | 57624472.61 | 5712.62 | 27-NOV-07:11 | 4.00 |
| December | 0.215537E+09 | 6155.53 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.764934E+09 | |||
| Minimum of Months | 779407.59 | 4341.02 | -2.0 | |
| Maximum of Months | 0.248392E+09 | 6247.58 | 14.33 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.347314E+09 | 21721.82 | 02-JAN-06:01 | 1.17 |
| February | 0.140560E+09 | 19666.25 | 27-FEB-07:11 | 6.00 |
| March | 0.117041E+09 | 20046.55 | 06-MAR-07:11 | 4.67 |
| April | 11526324.27 | 15617.46 | 04-APR-07:01 | 6.33 |
| May | 4892474.39 | 14978.60 | 05-MAY-07:01 | 7.17 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 16467086.20 | 15719.72 | 05-JUL-07:01 | 12.17 |
| August | 21816080.97 | 15644.87 | 24-AUG-07:01 | 13.50 |
| September | 1128059.10 | 15040.79 | 01-SEP-07:01 | 14.33 |
| October | 15913397.29 | 15629.11 | 31-OCT-07:01 | 6.22 |
| November | 74149260.32 | 18858.14 | 27-NOV-07:11 | 4.00 |
| December | 0.277000E+09 | 21207.34 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.102781E+10 | |||
| Minimum of Months | 0.00 | 0.00 | 1.17 | |
| Maximum of Months | 0.347314E+09 | 21721.82 | 14.33 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.793279E+09 | 5557.46 | 02-JAN-07:11 | 1.67 |
| February | 0.287868E+09 | 5210.51 | 21-FEB-07:11 | 4.00 |
| March | 0.156067E+09 | 5137.40 | 06-MAR-07:11 | 4.67 |
| April | 3245899.17 | 4363.83 | 03-APR-07:01 | 4.67 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 144417.98 | 2406.97 | 05-JUL-07:01 | 12.17 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
| October | 6127408.98 | 4347.04 | 24-OCT-07:01 | 6.17 |
| November | 0.130124E+09 | 4948.17 | 27-NOV-07:11 | 4.00 |
| December | 0.614529E+09 | 5420.49 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.199139E+10 | |||
| Minimum of Months | 0.00 | 0.00 | 1.67 | |
| Maximum of Months | 0.793279E+09 | 5557.46 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.423365E+09 | 5829.05 | 09-JAN-06:11 | -2.0 |
| February | 0.191149E+09 | 5634.14 | 21-FEB-07:11 | 4.00 |
| March | 0.125017E+09 | 5553.93 | 06-MAR-07:11 | 4.67 |
| April | 18328862.26 | 4908.30 | 03-APR-06:11 | 3.33 |
| May | 5127215.19 | 4284.87 | 05-MAY-07:01 | 7.17 |
| June | 1200569.16 | 4156.70 | 30-JUN-07:01 | 12.00 |
| July | 7858478.92 | 4317.32 | 05-JUL-07:01 | 12.17 |
| August | 11053630.64 | 4310.50 | 30-AUG-07:01 | 12.33 |
| September | 4568016.45 | 4301.33 | 07-SEP-07:01 | 10.33 |
| October | 20079610.20 | 4953.06 | 23-OCT-06:11 | 4.00 |
| November | 0.105759E+09 | 5583.17 | 20-NOV-06:01 | -0.7 |
| December | 0.314257E+09 | 5709.55 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.122776E+10 | |||
| Minimum of Months | 1200569.16 | 4156.70 | -2.0 | |
| Maximum of Months | 0.423365E+09 | 5829.05 | 12.33 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.751381E+09 | 21582.37 | 09-JAN-06:11 | -2.0 |
| February | 0.260597E+09 | 20599.81 | 21-FEB-07:11 | 4.00 |
| March | 0.154546E+09 | 19628.93 | 06-MAR-07:11 | 4.67 |
| April | 23189400.68 | 16299.25 | 03-APR-06:11 | 3.33 |
| May | 11874959.19 | 14751.50 | 17-MAY-07:01 | 7.17 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 31043769.52 | 15348.90 | 05-JUL-07:01 | 12.17 |
| August | 44092571.70 | 15346.49 | 28-AUG-07:01 | 14.67 |
| September | 6969697.01 | 15211.28 | 01-SEP-07:01 | 14.33 |
| October | 30599802.80 | 16575.15 | 23-OCT-06:11 | 4.00 |
| November | 0.125191E+09 | 19012.80 | 27-NOV-07:11 | 4.00 |
| December | 0.389493E+09 | 21227.78 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.182898E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -2.0 | |
| Maximum of Months | 0.751381E+09 | 21582.37 | 14.67 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.269655E+09 | 6215.41 | 09-JAN-06:11 | -2.0 |
| February | 0.109487E+09 | 5851.13 | 27-FEB-07:11 | 6.00 |
| March | 97685988.68 | 5929.05 | 06-MAR-07:11 | 4.67 |
| April | 9512695.55 | 4982.74 | 03-APR-06:11 | 3.33 |
| May | 4157104.41 | 4492.73 | 05-MAY-07:01 | 7.17 |
| June | 958616.85 | 4324.74 | 30-JUN-07:01 | 12.00 |
| July | 5320343.90 | 4531.75 | 05-JUL-07:01 | 12.17 |
| August | 7534800.66 | 4507.51 | 28-AUG-07:01 | 14.67 |
| September | 1460182.54 | 4449.19 | 01-SEP-07:01 | 14.33 |
| October | 10735772.25 | 4948.81 | 23-OCT-06:11 | 4.00 |
| November | 60830550.81 | 5675.32 | 27-NOV-07:11 | 4.00 |
| December | 0.228544E+09 | 6117.54 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.805882E+09 | |||
| Minimum of Months | 958616.85 | 4324.74 | -2.0 | |
| Maximum of Months | 0.269655E+09 | 6215.41 | 14.67 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.382755E+09 | 21464.51 | 02-JAN-06:01 | 1.17 |
| February | 0.139774E+09 | 19407.22 | 27-FEB-07:11 | 6.00 |
| March | 0.109635E+09 | 19664.12 | 06-MAR-07:11 | 4.67 |
| April | 11063896.10 | 15393.02 | 04-APR-07:01 | 6.33 |
| May | 4846565.68 | 14682.18 | 05-MAY-07:01 | 7.17 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 17600949.66 | 15497.12 | 05-JUL-07:01 | 12.17 |
| August | 23457662.76 | 15421.18 | 24-AUG-07:01 | 13.50 |
| September | 1115211.92 | 14869.49 | 01-SEP-07:01 | 14.33 |
| October | 15707173.38 | 15406.22 | 31-OCT-07:01 | 6.22 |
| November | 74832546.10 | 18575.43 | 27-NOV-07:11 | 4.00 |
| December | 0.271799E+09 | 20939.08 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.105259E+10 | |||
| Minimum of Months | 0.00 | 0.00 | 1.17 | |
| Maximum of Months | 0.382755E+09 | 21464.51 | 14.33 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.845764E+09 | 5556.08 | 02-JAN-07:11 | 1.67 |
| February | 0.293261E+09 | 5211.24 | 21-FEB-07:11 | 4.00 |
| March | 0.153227E+09 | 5114.73 | 06-MAR-07:11 | 4.67 |
| April | 3302233.74 | 4352.37 | 03-APR-07:01 | 4.67 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 191729.46 | 3182.33 | 05-JUL-07:01 | 12.17 |
| August | 26803.96 | 402.06 | 24-AUG-07:01 | 13.50 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
| October | 6089080.78 | 4334.75 | 24-OCT-07:01 | 6.17 |
| November | 0.137579E+09 | 4935.82 | 27-NOV-07:11 | 4.00 |
| December | 0.635390E+09 | 5411.64 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.207483E+10 | |||
| Minimum of Months | 0.00 | 0.00 | 1.67 | |
| Maximum of Months | 0.845764E+09 | 5556.08 | 13.50 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.427613E+09 | 5833.67 | 09-JAN-06:11 | -2.0 |
| February | 0.191831E+09 | 5639.49 | 21-FEB-07:11 | 4.00 |
| March | 0.124818E+09 | 5555.99 | 06-MAR-07:11 | 4.67 |
| April | 18383529.64 | 4911.39 | 03-APR-06:11 | 3.33 |
| May | 5102398.38 | 4286.53 | 05-MAY-07:01 | 7.17 |
| June | 1190567.51 | 4158.70 | 30-JUN-07:01 | 12.00 |
| July | 7879242.65 | 4319.50 | 05-JUL-07:01 | 12.17 |
| August | 11086869.73 | 4313.29 | 30-AUG-07:01 | 12.33 |
| September | 4604456.56 | 4303.86 | 07-SEP-07:01 | 10.33 |
| October | 20139696.95 | 4955.65 | 23-OCT-06:11 | 4.00 |
| November | 0.106441E+09 | 5590.30 | 20-NOV-06:01 | -0.7 |
| December | 0.315625E+09 | 5713.05 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.123471E+10 | |||
| Minimum of Months | 1190567.51 | 4158.70 | -2.0 | |
| Maximum of Months | 0.427613E+09 | 5833.67 | 12.33 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.762034E+09 | 21605.54 | 09-JAN-06:11 | -2.0 |
| February | 0.261413E+09 | 20610.83 | 21-FEB-07:11 | 4.00 |
| March | 0.154137E+09 | 19618.24 | 06-MAR-07:11 | 4.67 |
| April | 23165851.34 | 16300.38 | 03-APR-06:11 | 3.33 |
| May | 11869331.24 | 14747.06 | 17-MAY-07:01 | 7.17 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 31082862.14 | 15351.96 | 05-JUL-07:01 | 12.17 |
| August | 44200766.83 | 15353.26 | 30-AUG-07:01 | 12.33 |
| September | 7023655.97 | 15214.18 | 01-SEP-07:01 | 14.33 |
| October | 30594960.44 | 16573.67 | 23-OCT-06:11 | 4.00 |
| November | 0.126347E+09 | 19014.16 | 27-NOV-07:11 | 4.00 |
| December | 0.391473E+09 | 21232.90 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.184334E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -2.0 | |
| Maximum of Months | 0.762034E+09 | 21605.54 | 14.33 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.259845E+09 | 6212.78 | 09-JAN-06:11 | -2.0 |
| February | 0.106240E+09 | 5840.90 | 27-FEB-07:11 | 6.00 |
| March | 93474373.95 | 5918.73 | 06-MAR-07:11 | 4.67 |
| April | 8793329.44 | 4952.33 | 03-APR-06:11 | 3.33 |
| May | 3968584.33 | 4495.44 | 05-MAY-07:01 | 7.17 |
| June | 799222.05 | 4305.15 | 30-JUN-07:01 | 12.00 |
| July | 4900191.16 | 4533.27 | 05-JUL-07:01 | 12.17 |
| August | 6968595.65 | 4506.81 | 24-AUG-07:01 | 13.50 |
| September | 1312994.79 | 4435.52 | 01-SEP-07:01 | 14.33 |
| October | 9736425.38 | 4921.08 | 23-OCT-06:11 | 4.00 |
| November | 56660095.38 | 5658.65 | 27-NOV-07:11 | 4.00 |
| December | 0.219452E+09 | 6117.01 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.772151E+09 | |||
| Minimum of Months | 799222.05 | 4305.15 | -2.0 | |
| Maximum of Months | 0.259845E+09 | 6212.78 | 14.33 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.362057E+09 | 21542.23 | 02-JAN-06:01 | 1.17 |
| February | 0.134017E+09 | 19404.09 | 27-FEB-07:11 | 6.00 |
| March | 0.100890E+09 | 19655.98 | 06-MAR-07:11 | 4.67 |
| April | 9428355.69 | 15440.80 | 04-APR-07:01 | 6.33 |
| May | 4108607.32 | 14654.76 | 05-MAY-07:01 | 7.17 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 15541350.20 | 15549.26 | 05-JUL-07:01 | 12.17 |
| August | 20607862.50 | 15466.71 | 24-AUG-07:01 | 13.50 |
| September | 1112456.09 | 14832.75 | 01-SEP-07:01 | 14.33 |
| October | 13691469.32 | 15452.47 | 31-OCT-07:01 | 6.22 |
| November | 67980276.92 | 18524.99 | 27-NOV-07:11 | 4.00 |
| December | 0.260923E+09 | 20929.67 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.990357E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 1.17 | |
| Maximum of Months | 0.362057E+09 | 21542.23 | 14.33 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.776666E+09 | 5580.54 | 02-JAN-07:11 | 1.67 |
| February | 0.245269E+09 | 5205.75 | 21-FEB-07:11 | 4.00 |
| March | 0.119050E+09 | 5098.09 | 06-MAR-07:11 | 4.67 |
| April | 2102444.55 | 4354.18 | 03-APR-07:01 | 4.67 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
| October | 3673161.03 | 4292.01 | 24-OCT-07:01 | 6.17 |
| November | 0.106906E+09 | 4913.56 | 27-NOV-07:11 | 4.00 |
| December | 0.561308E+09 | 5407.85 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.181498E+10 | |||
| Minimum of Months | 0.00 | 0.00 | 1.67 | |
| Maximum of Months | 0.776666E+09 | 5580.54 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.424481E+09 | 5855.73 | 09-JAN-06:11 | -2.0 |
| February | 0.186956E+09 | 5655.26 | 21-FEB-07:11 | 4.00 |
| March | 0.119777E+09 | 5569.69 | 06-MAR-07:11 | 4.67 |
| April | 15908892.12 | 4895.67 | 03-APR-06:11 | 3.33 |
| May | 4661333.05 | 4306.71 | 05-MAY-07:01 | 7.17 |
| June | 704173.99 | 4143.33 | 30-JUN-07:01 | 12.00 |
| July | 6805311.68 | 4338.59 | 05-JUL-07:01 | 12.17 |
| August | 10674217.81 | 4334.26 | 30-AUG-07:01 | 12.33 |
| September | 4231103.88 | 4324.11 | 07-SEP-07:01 | 10.33 |
| October | 18732597.87 | 4954.90 | 23-OCT-06:11 | 4.00 |
| November | 0.103619E+09 | 5595.95 | 20-NOV-06:01 | -0.7 |
| December | 0.314260E+09 | 5734.76 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.121081E+10 | |||
| Minimum of Months | 704173.99 | 4143.33 | -2.0 | |
| Maximum of Months | 0.424481E+09 | 5855.73 | 12.33 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.517149E+09 | 14504.62 | 09-JAN-06:11 | -2.0 |
| February | 0.174333E+09 | 13818.29 | 21-FEB-07:11 | 4.00 |
| March | 98855094.65 | 13144.76 | 06-MAR-07:11 | 4.67 |
| April | 14390698.45 | 10845.36 | 03-APR-06:11 | 3.33 |
| May | 6347994.22 | 9840.55 | 17-MAY-07:01 | 7.17 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 17575670.52 | 10329.72 | 05-JUL-07:01 | 12.17 |
| August | 28430783.58 | 10337.91 | 30-AUG-07:01 | 12.33 |
| September | 4034602.85 | 10249.35 | 01-SEP-07:01 | 14.33 |
| October | 18921453.11 | 11088.49 | 23-OCT-06:11 | 4.00 |
| November | 82341201.05 | 12751.44 | 27-NOV-07:11 | 4.00 |
| December | 0.267583E+09 | 14254.04 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.122996E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -2.0 | |
| Maximum of Months | 0.517149E+09 | 14504.62 | 14.33 |
Report: ZoneHeatingSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.149592E+09 | 7033.96 | 02-JAN-07:11 | 1.67 |
| February | 49588355.15 | 6560.58 | 21-FEB-07:11 | 4.00 |
| March | 23545517.55 | 6165.65 | 06-MAR-07:11 | 4.67 |
| April | 2242865.49 | 4953.46 | 03-APR-07:01 | 4.67 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 1181795.62 | 4751.86 | 05-JUL-07:01 | 12.17 |
| August | 5256546.29 | 4889.64 | 30-AUG-07:01 | 12.33 |
| September | 360615.21 | 4808.20 | 01-SEP-07:01 | 14.33 |
| October | 3272606.31 | 4968.73 | 24-OCT-07:01 | 6.17 |
| November | 22525555.69 | 5957.73 | 27-NOV-07:11 | 4.00 |
| December | 78435317.17 | 6767.98 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.336001E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 1.67 | |
| Maximum of Months | 0.149592E+09 | 7033.96 | 14.33 |
Report: ZoneHeatingSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.236934E+10 | 12262.87 | 02-JAN-07:11 | 1.67 |
| February | 0.651958E+09 | 11407.67 | 21-FEB-07:11 | 4.00 |
| March | 0.214308E+09 | 10996.40 | 06-MAR-07:11 | 4.67 |
| April | 2206526.65 | 9623.04 | 03-APR-07:01 | 4.67 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
| October | 11147500.92 | 9704.70 | 24-OCT-07:01 | 6.17 |
| November | 0.345037E+09 | 10777.48 | 27-NOV-07:11 | 4.00 |
| December | 0.159517E+10 | 11699.32 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.518917E+10 | |||
| Minimum of Months | 0.00 | 0.00 | 1.67 | |
| Maximum of Months | 0.236934E+10 | 12262.87 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.622671E+10 | 12901.64 | 10-JAN-08:00 | -6.0 |
| February | 0.513958E+10 | 12588.86 | 17-FEB-07:10 | -3.8 |
| March | 0.579836E+10 | 11580.32 | 08-MAR-07:10 | -0.5 |
| April | 0.249724E+10 | 10430.65 | 03-APR-06:10 | 3.17 |
| May | 0.230941E+10 | 9595.87 | 02-MAY-06:10 | 5.17 |
| June | 0.116732E+10 | 9007.18 | 08-JUN-06:10 | 7.50 |
| July | 0.842184E+09 | 8473.53 | 05-JUL-06:10 | 9.50 |
| August | 0.878172E+09 | 8656.71 | 24-AUG-06:10 | 8.83 |
| September | 0.106864E+10 | 9570.54 | 21-SEP-06:10 | 5.33 |
| October | 0.290986E+10 | 10250.00 | 06-OCT-06:10 | 3.00 |
| November | 0.490625E+10 | 11824.81 | 29-NOV-07:10 | -1.0 |
| December | 0.600137E+10 | 11971.01 | 27-DEC-07:10 | -1.8 |
| Annual Sum or Average | 0.397451E+11 | |||
| Minimum of Months | 0.842184E+09 | 8473.53 | -6.0 | |
| Maximum of Months | 0.622671E+10 | 12901.64 | 9.50 |
Report: ZoneHeatingSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 1.92 | |
| Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 53536833.98 | 3306.62 | 01-JAN-01:40 | 5.33 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
| December | 13947.78 | 92.99 | 31-DEC-23:40 | 0.00 |
| Annual Sum or Average | 53550781.76 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 53536833.98 | 3306.62 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.957129E+09 | 16173.93 | 02-JAN-07:11 | 1.67 |
| February | 0.196594E+09 | 14930.91 | 21-FEB-07:11 | 4.00 |
| March | 0.120390E+09 | 14962.21 | 06-MAR-07:11 | 4.67 |
| April | 735261.42 | 12254.36 | 03-APR-07:01 | 4.67 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
| October | 5849820.93 | 12400.40 | 30-OCT-07:01 | 6.17 |
| November | 96660186.86 | 14373.43 | 27-NOV-07:11 | 4.00 |
| December | 0.632807E+09 | 15991.01 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.201017E+10 | |||
| Minimum of Months | 0.00 | 0.00 | 1.67 | |
| Maximum of Months | 0.957129E+09 | 16173.93 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.415954E+09 | 14005.65 | 02-JAN-06:01 | 1.17 |
| February | 0.123018E+09 | 11315.02 | 21-FEB-06:01 | 4.75 |
| March | 38569703.35 | 10834.50 | 06-MAR-06:01 | 4.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
| November | 68028220.08 | 10858.44 | 20-NOV-06:01 | -0.7 |
| December | 0.296249E+09 | 12830.03 | 26-DEC-06:11 | 1.93 |
| Annual Sum or Average | 0.941820E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -0.7 | |
| Maximum of Months | 0.415954E+09 | 14005.65 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 1072403.88 | 3311.69 | 24-JAN-07:02 | 6.00 |
| February | 502417.62 | 3066.98 | 08-FEB-07:02 | 6.00 |
| March | 1105932.71 | 3344.52 | 24-MAR-06:02 | 4.00 |
| April | 620416.35 | 3168.91 | 10-APR-06:02 | 7.17 |
| May | 332146.34 | 3352.96 | 08-MAY-06:02 | 7.75 |
| June | 543163.99 | 1560.74 | 28-JUN-06:01 | 11.83 |
| July | 94426.96 | 1573.78 | 19-JUL-06:01 | 14.17 |
| August | 404967.25 | 1650.23 | 25-AUG-06:01 | 12.50 |
| September | 273386.63 | 1610.61 | 27-SEP-06:01 | 8.33 |
| October | 1001527.55 | 3185.45 | 18-OCT-06:02 | 9.17 |
| November | 325208.96 | 3375.44 | 10-NOV-07:02 | 6.83 |
| December | 229000.52 | 2971.80 | 13-DEC-07:02 | 4.00 |
| Annual Sum or Average | 6504998.76 | |||
| Minimum of Months | 94426.96 | 1560.74 | 4.00 | |
| Maximum of Months | 1105932.71 | 3375.44 | 14.17 |
Report: ZoneHeatingSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.827477E+09 | 78363.96 | 02-JAN-07:01 | 1.83 |
| February | 0.516368E+09 | 58306.68 | 27-FEB-06:01 | 6.00 |
| March | 0.449590E+09 | 55189.34 | 06-MAR-06:01 | 4.00 |
| April | 0.193018E+09 | 21533.85 | 03-APR-06:01 | 3.17 |
| May | 0.103248E+09 | 4238.32 | 23-MAY-06:02 | 13.17 |
| June | 7388208.62 | 4428.06 | 22-JUN-06:02 | 10.33 |
| July | 23363557.21 | 4535.87 | 10-JUL-06:02 | 17.83 |
| August | 53397681.31 | 4619.22 | 21-AUG-06:02 | 11.50 |
| September | 39748050.18 | 3991.08 | 21-SEP-06:11 | 5.67 |
| October | 0.250769E+09 | 30384.89 | 23-OCT-05:01 | 3.17 |
| November | 0.405269E+09 | 53971.70 | 13-NOV-06:01 | 4.17 |
| December | 0.664769E+09 | 54331.17 | 04-DEC-06:01 | 3.00 |
| Annual Sum or Average | 0.353441E+10 | |||
| Minimum of Months | 7388208.62 | 3991.08 | 1.83 | |
| Maximum of Months | 0.827477E+09 | 78363.96 | 17.83 |
Report: ZoneHeatingSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.524681E+09 | 15148.19 | 02-JAN-07:11 | 1.67 |
| February | 0.100346E+09 | 14028.22 | 21-FEB-07:11 | 4.00 |
| March | 39072540.75 | 13247.91 | 06-MAR-07:11 | 4.67 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.47 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 9.27 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 12.43 |
| October | 1265510.45 | 10799.72 | 23-OCT-07:01 | 4.50 |
| November | 36566637.29 | 12901.87 | 20-NOV-07:01 | 1.00 |
| December | 0.211419E+09 | 14635.64 | 26-DEC-07:11 | 1.67 |
| Annual Sum or Average | 0.913351E+09 | |||
| Minimum of Months | 0.00 | 0.00 | 1.00 | |
| Maximum of Months | 0.524681E+09 | 15148.19 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.130469E+10 | 947.12 | 02-JAN-07:10 | 0.892986E+09 | 678.98 | 02-JAN-08:09 |
| February | 0.117967E+10 | 947.12 | 01-FEB-07:10 | 0.807077E+09 | 678.98 | 01-FEB-08:09 |
| March | 0.138135E+10 | 947.12 | 01-MAR-07:10 | 0.924571E+09 | 678.98 | 01-MAR-08:09 |
| April | 0.125024E+10 | 947.12 | 03-APR-06:10 | 0.859085E+09 | 678.98 | 03-APR-07:10 |
| May | 0.134302E+10 | 947.12 | 01-MAY-06:10 | 0.908779E+09 | 678.98 | 01-MAY-07:10 |
| June | 0.132690E+10 | 947.12 | 01-JUN-06:10 | 0.890455E+09 | 678.98 | 01-JUN-07:10 |
| July | 0.793150E+09 | 526.18 | 03-JUL-07:10 | 0.543864E+09 | 357.36 | 03-JUL-07:10 |
| August | 0.837162E+09 | 526.18 | 01-AUG-07:10 | 0.565300E+09 | 357.36 | 01-AUG-07:10 |
| September | 0.122658E+10 | 947.12 | 05-SEP-06:10 | 0.845480E+09 | 678.98 | 05-SEP-07:10 |
| October | 0.130469E+10 | 947.12 | 02-OCT-06:10 | 0.892986E+09 | 678.98 | 02-OCT-07:10 |
| November | 0.128857E+10 | 947.12 | 01-NOV-06:10 | 0.874878E+09 | 678.98 | 01-NOV-07:10 |
| December | 0.126636E+10 | 947.12 | 01-DEC-07:10 | 0.877193E+09 | 678.98 | 01-DEC-08:09 |
| Annual Sum or Average | 0.145024E+11 | 0.988265E+10 | ||||
| Minimum of Months | 0.793150E+09 | 526.18 | 0.543864E+09 | 357.36 | ||
| Maximum of Months | 0.138135E+10 | 947.12 | 0.924571E+09 | 678.98 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.130469E+10 | 947.12 | 02-JAN-07:10 | 0.892986E+09 | 678.98 | 02-JAN-08:09 |
| February | 0.117967E+10 | 947.12 | 01-FEB-07:10 | 0.807077E+09 | 678.98 | 01-FEB-08:09 |
| March | 0.138135E+10 | 947.12 | 01-MAR-07:10 | 0.924571E+09 | 678.98 | 01-MAR-08:09 |
| April | 0.125024E+10 | 947.12 | 03-APR-06:10 | 0.859085E+09 | 678.98 | 03-APR-07:10 |
| May | 0.134302E+10 | 947.12 | 01-MAY-06:10 | 0.908779E+09 | 678.98 | 01-MAY-07:10 |
| June | 0.132690E+10 | 947.12 | 01-JUN-06:10 | 0.890455E+09 | 678.98 | 01-JUN-07:10 |
| July | 0.793150E+09 | 526.18 | 03-JUL-07:10 | 0.543864E+09 | 357.36 | 03-JUL-07:10 |
| August | 0.837162E+09 | 526.18 | 01-AUG-07:10 | 0.565300E+09 | 357.36 | 01-AUG-07:10 |
| September | 0.122658E+10 | 947.12 | 05-SEP-06:10 | 0.845480E+09 | 678.98 | 05-SEP-07:10 |
| October | 0.130469E+10 | 947.12 | 02-OCT-06:10 | 0.892986E+09 | 678.98 | 02-OCT-07:10 |
| November | 0.128857E+10 | 947.12 | 01-NOV-06:10 | 0.874878E+09 | 678.98 | 01-NOV-07:10 |
| December | 0.126636E+10 | 947.12 | 01-DEC-07:10 | 0.877193E+09 | 678.98 | 01-DEC-08:09 |
| Annual Sum or Average | 0.145024E+11 | 0.988265E+10 | ||||
| Minimum of Months | 0.793150E+09 | 526.18 | 0.543864E+09 | 357.36 | ||
| Maximum of Months | 0.138135E+10 | 947.12 | 0.924571E+09 | 678.98 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.130469E+10 | 947.12 | 02-JAN-07:10 | 0.892986E+09 | 678.98 | 02-JAN-08:09 |
| February | 0.117967E+10 | 947.12 | 01-FEB-07:10 | 0.807077E+09 | 678.98 | 01-FEB-08:09 |
| March | 0.138135E+10 | 947.12 | 01-MAR-07:10 | 0.924571E+09 | 678.98 | 01-MAR-08:09 |
| April | 0.125024E+10 | 947.12 | 03-APR-06:10 | 0.859085E+09 | 678.98 | 03-APR-07:10 |
| May | 0.134302E+10 | 947.12 | 01-MAY-06:10 | 0.908779E+09 | 678.98 | 01-MAY-07:10 |
| June | 0.132690E+10 | 947.12 | 01-JUN-06:10 | 0.890455E+09 | 678.98 | 01-JUN-07:10 |
| July | 0.793150E+09 | 526.18 | 03-JUL-07:10 | 0.543864E+09 | 357.36 | 03-JUL-07:10 |
| August | 0.837162E+09 | 526.18 | 01-AUG-07:10 | 0.565300E+09 | 357.36 | 01-AUG-07:10 |
| September | 0.122658E+10 | 947.12 | 05-SEP-06:10 | 0.845480E+09 | 678.98 | 05-SEP-07:10 |
| October | 0.130469E+10 | 947.12 | 02-OCT-06:10 | 0.892986E+09 | 678.98 | 02-OCT-07:10 |
| November | 0.128857E+10 | 947.12 | 01-NOV-06:10 | 0.874878E+09 | 678.98 | 01-NOV-07:10 |
| December | 0.126636E+10 | 947.12 | 01-DEC-07:10 | 0.877193E+09 | 678.98 | 01-DEC-08:09 |
| Annual Sum or Average | 0.145024E+11 | 0.988265E+10 | ||||
| Minimum of Months | 0.793150E+09 | 526.18 | 0.543864E+09 | 357.36 | ||
| Maximum of Months | 0.138135E+10 | 947.12 | 0.924571E+09 | 678.98 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.588512E+10 | 4272.19 | 02-JAN-07:10 | 0.549396E+10 | 4177.31 | 02-JAN-08:09 |
| February | 0.532117E+10 | 4272.19 | 01-FEB-07:10 | 0.496542E+10 | 4177.31 | 01-FEB-08:09 |
| March | 0.623092E+10 | 4272.19 | 01-MAR-07:10 | 0.568828E+10 | 4177.31 | 01-MAR-08:09 |
| April | 0.563950E+10 | 4272.19 | 03-APR-06:10 | 0.528539E+10 | 4177.31 | 03-APR-07:10 |
| May | 0.605802E+10 | 4272.19 | 01-MAY-06:10 | 0.559112E+10 | 4177.31 | 01-MAY-07:10 |
| June | 0.598530E+10 | 4272.19 | 01-JUN-06:10 | 0.547839E+10 | 4177.31 | 01-JUN-07:10 |
| July | 0.357769E+10 | 2373.44 | 03-JUL-07:10 | 0.334604E+10 | 2198.59 | 03-JUL-07:10 |
| August | 0.377621E+10 | 2373.44 | 01-AUG-07:10 | 0.347792E+10 | 2198.59 | 01-AUG-07:10 |
| September | 0.553277E+10 | 4272.19 | 05-SEP-06:10 | 0.520168E+10 | 4177.31 | 05-SEP-07:10 |
| October | 0.588512E+10 | 4272.19 | 02-OCT-06:10 | 0.549396E+10 | 4177.31 | 02-OCT-07:10 |
| November | 0.581240E+10 | 4272.19 | 01-NOV-06:10 | 0.538255E+10 | 4177.31 | 01-NOV-07:10 |
| December | 0.571221E+10 | 4272.19 | 01-DEC-07:10 | 0.539679E+10 | 4177.31 | 01-DEC-08:09 |
| Annual Sum or Average | 0.654164E+11 | 0.608015E+11 | ||||
| Minimum of Months | 0.357769E+10 | 2373.44 | 0.334604E+10 | 2198.59 | ||
| Maximum of Months | 0.623092E+10 | 4272.19 | 0.568828E+10 | 4177.31 |
Report: ZoneElectricSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.302663E+10 | 2197.13 | 02-JAN-07:10 | 0.376728E+10 | 2864.44 | 02-JAN-08:09 |
| February | 0.273660E+10 | 2197.13 | 01-FEB-07:10 | 0.340486E+10 | 2864.44 | 01-FEB-08:09 |
| March | 0.320447E+10 | 2197.13 | 01-MAR-07:10 | 0.390054E+10 | 2864.44 | 01-MAR-08:09 |
| April | 0.290031E+10 | 2197.13 | 03-APR-06:10 | 0.362427E+10 | 2864.44 | 03-APR-07:10 |
| May | 0.311555E+10 | 2197.13 | 01-MAY-06:10 | 0.383391E+10 | 2864.44 | 01-MAY-07:10 |
| June | 0.307815E+10 | 2197.13 | 01-JUN-06:10 | 0.375661E+10 | 2864.44 | 01-JUN-07:10 |
| July | 0.183996E+10 | 1220.63 | 03-JUL-07:10 | 0.229443E+10 | 1507.60 | 03-JUL-07:10 |
| August | 0.194205E+10 | 1220.63 | 01-AUG-07:10 | 0.238486E+10 | 1507.60 | 01-AUG-07:10 |
| September | 0.284543E+10 | 2197.13 | 05-SEP-06:10 | 0.356687E+10 | 2864.44 | 05-SEP-07:10 |
| October | 0.302663E+10 | 2197.13 | 02-OCT-06:10 | 0.376728E+10 | 2864.44 | 02-OCT-07:10 |
| November | 0.298923E+10 | 2197.13 | 01-NOV-06:10 | 0.369089E+10 | 2864.44 | 01-NOV-07:10 |
| December | 0.293771E+10 | 2197.13 | 01-DEC-07:10 | 0.370066E+10 | 2864.44 | 01-DEC-08:09 |
| Annual Sum or Average | 0.336427E+11 | 0.416925E+11 | ||||
| Minimum of Months | 0.183996E+10 | 1220.63 | 0.229443E+10 | 1507.60 | ||
| Maximum of Months | 0.320447E+10 | 2197.13 | 0.390054E+10 | 2864.44 |
Report: ZoneElectricSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.371022E+10 | 2693.36 | 02-JAN-07:10 | 0.253943E+10 | 1930.85 | 02-JAN-08:09 |
| February | 0.335468E+10 | 2693.36 | 01-FEB-07:10 | 0.229513E+10 | 1930.85 | 01-FEB-08:09 |
| March | 0.392822E+10 | 2693.36 | 01-MAR-07:10 | 0.262925E+10 | 1930.85 | 01-MAR-08:09 |
| April | 0.355537E+10 | 2693.36 | 03-APR-06:10 | 0.244302E+10 | 1930.85 | 03-APR-07:10 |
| May | 0.381922E+10 | 2693.36 | 01-MAY-06:10 | 0.258434E+10 | 1930.85 | 01-MAY-07:10 |
| June | 0.377338E+10 | 2693.36 | 01-JUN-06:10 | 0.253223E+10 | 1930.85 | 01-JUN-07:10 |
| July | 0.225552E+10 | 1496.31 | 03-JUL-07:10 | 0.154661E+10 | 1016.24 | 03-JUL-07:10 |
| August | 0.238068E+10 | 1496.31 | 01-AUG-07:10 | 0.160757E+10 | 1016.24 | 01-AUG-07:10 |
| September | 0.348808E+10 | 2693.36 | 05-SEP-06:10 | 0.240433E+10 | 1930.85 | 05-SEP-07:10 |
| October | 0.371022E+10 | 2693.36 | 02-OCT-06:10 | 0.253943E+10 | 1930.85 | 02-OCT-07:10 |
| November | 0.366437E+10 | 2693.36 | 01-NOV-06:10 | 0.248793E+10 | 1930.85 | 01-NOV-07:10 |
| December | 0.360121E+10 | 2693.36 | 01-DEC-07:10 | 0.249452E+10 | 1930.85 | 01-DEC-08:09 |
| Annual Sum or Average | 0.412412E+11 | 0.281038E+11 | ||||
| Minimum of Months | 0.225552E+10 | 1496.31 | 0.154661E+10 | 1016.24 | ||
| Maximum of Months | 0.392822E+10 | 2693.36 | 0.262925E+10 | 1930.85 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.296658E+10 | 2153.53 | 02-JAN-07:10 | 0.795316E+09 | 604.72 | 02-JAN-08:09 |
| February | 0.268230E+10 | 2153.53 | 01-FEB-07:10 | 0.718803E+09 | 604.72 | 01-FEB-08:09 |
| March | 0.314089E+10 | 2153.53 | 01-MAR-07:10 | 0.823446E+09 | 604.72 | 01-MAR-08:09 |
| April | 0.284277E+10 | 2153.53 | 03-APR-06:10 | 0.765123E+09 | 604.72 | 03-APR-07:10 |
| May | 0.305373E+10 | 2153.53 | 01-MAY-06:10 | 0.809381E+09 | 604.72 | 01-MAY-07:10 |
| June | 0.301708E+10 | 2153.53 | 01-JUN-06:10 | 0.793062E+09 | 604.72 | 01-JUN-07:10 |
| July | 0.180345E+10 | 1196.41 | 03-JUL-07:10 | 0.484379E+09 | 318.27 | 03-JUL-07:10 |
| August | 0.190352E+10 | 1196.41 | 01-AUG-07:10 | 0.503470E+09 | 318.27 | 01-AUG-07:10 |
| September | 0.278897E+10 | 2153.53 | 05-SEP-06:10 | 0.753006E+09 | 604.72 | 05-SEP-07:10 |
| October | 0.296658E+10 | 2153.53 | 02-OCT-06:10 | 0.795316E+09 | 604.72 | 02-OCT-07:10 |
| November | 0.292992E+10 | 2153.53 | 01-NOV-06:10 | 0.779188E+09 | 604.72 | 01-NOV-07:10 |
| December | 0.287942E+10 | 2153.53 | 01-DEC-07:10 | 0.781250E+09 | 604.72 | 01-DEC-08:09 |
| Annual Sum or Average | 0.329752E+11 | 0.880174E+10 | ||||
| Minimum of Months | 0.180345E+10 | 1196.41 | 0.484379E+09 | 318.27 | ||
| Maximum of Months | 0.314089E+10 | 2153.53 | 0.823446E+09 | 604.72 |
Report: ZoneElectricSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.504438E+10 | 3661.88 | 02-JAN-07:10 | 0.293011E+10 | 2227.90 | 02-JAN-08:09 |
| February | 0.456100E+10 | 3661.88 | 01-FEB-07:10 | 0.264822E+10 | 2227.90 | 01-FEB-08:09 |
| March | 0.534079E+10 | 3661.88 | 01-MAR-07:10 | 0.303375E+10 | 2227.90 | 01-MAR-08:09 |
| April | 0.483386E+10 | 3661.88 | 03-APR-06:10 | 0.281887E+10 | 2227.90 | 03-APR-07:10 |
| May | 0.519259E+10 | 3661.88 | 01-MAY-06:10 | 0.298193E+10 | 2227.90 | 01-MAY-07:10 |
| June | 0.513026E+10 | 3661.88 | 01-JUN-06:10 | 0.292181E+10 | 2227.90 | 01-JUN-07:10 |
| July | 0.306659E+10 | 2034.38 | 03-JUL-07:10 | 0.178455E+10 | 1172.58 | 03-JUL-07:10 |
| August | 0.323676E+10 | 2034.38 | 01-AUG-07:10 | 0.185489E+10 | 1172.58 | 01-AUG-07:10 |
| September | 0.474238E+10 | 3661.88 | 05-SEP-06:10 | 0.277423E+10 | 2227.90 | 05-SEP-07:10 |
| October | 0.504438E+10 | 3661.88 | 02-OCT-06:10 | 0.293011E+10 | 2227.90 | 02-OCT-07:10 |
| November | 0.498206E+10 | 3661.88 | 01-NOV-06:10 | 0.287069E+10 | 2227.90 | 01-NOV-07:10 |
| December | 0.489618E+10 | 3661.88 | 01-DEC-07:10 | 0.287829E+10 | 2227.90 | 01-DEC-08:09 |
| Annual Sum or Average | 0.560712E+11 | 0.324275E+11 | ||||
| Minimum of Months | 0.306659E+10 | 2034.38 | 0.178455E+10 | 1172.58 | ||
| Maximum of Months | 0.534079E+10 | 3661.88 | 0.303375E+10 | 2227.90 |
Report: ZoneElectricSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.228198E+10 | 1656.56 | 02-JAN-07:10 | 0.883684E+09 | 671.91 | 02-JAN-08:09 |
| February | 0.206331E+10 | 1656.56 | 01-FEB-07:10 | 0.798670E+09 | 671.91 | 01-FEB-08:09 |
| March | 0.241607E+10 | 1656.56 | 01-MAR-07:10 | 0.914940E+09 | 671.91 | 01-MAR-08:09 |
| April | 0.218674E+10 | 1656.56 | 03-APR-06:10 | 0.850137E+09 | 671.91 | 03-APR-07:10 |
| May | 0.234903E+10 | 1656.56 | 01-MAY-06:10 | 0.899312E+09 | 671.91 | 01-MAY-07:10 |
| June | 0.232083E+10 | 1656.56 | 01-JUN-06:10 | 0.881180E+09 | 671.91 | 01-JUN-07:10 |
| July | 0.138727E+10 | 920.31 | 03-JUL-07:10 | 0.538198E+09 | 353.64 | 03-JUL-07:10 |
| August | 0.146425E+10 | 920.31 | 01-AUG-07:10 | 0.559411E+09 | 353.64 | 01-AUG-07:10 |
| September | 0.214536E+10 | 1656.56 | 05-SEP-06:10 | 0.836673E+09 | 671.91 | 05-SEP-07:10 |
| October | 0.228198E+10 | 1656.56 | 02-OCT-06:10 | 0.883684E+09 | 671.91 | 02-OCT-07:10 |
| November | 0.225379E+10 | 1656.56 | 01-NOV-06:10 | 0.865765E+09 | 671.91 | 01-NOV-07:10 |
| December | 0.221494E+10 | 1656.56 | 01-DEC-07:10 | 0.868056E+09 | 671.91 | 01-DEC-08:09 |
| Annual Sum or Average | 0.253655E+11 | 0.977971E+10 | ||||
| Minimum of Months | 0.138727E+10 | 920.31 | 0.538198E+09 | 353.64 | ||
| Maximum of Months | 0.241607E+10 | 1656.56 | 0.914940E+09 | 671.91 |
Report: ZoneElectricSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.647363E+10 | 4699.41 | 02-JAN-07:10 | 0.553791E+10 | 4210.73 | 02-JAN-08:09 |
| February | 0.585328E+10 | 4699.41 | 01-FEB-07:10 | 0.500514E+10 | 4210.73 | 01-FEB-08:09 |
| March | 0.685401E+10 | 4699.41 | 01-MAR-07:10 | 0.573379E+10 | 4210.73 | 01-MAR-08:09 |
| April | 0.620345E+10 | 4699.41 | 03-APR-06:10 | 0.532767E+10 | 4210.73 | 03-APR-07:10 |
| May | 0.666382E+10 | 4699.41 | 01-MAY-06:10 | 0.563585E+10 | 4210.73 | 01-MAY-07:10 |
| June | 0.658383E+10 | 4699.41 | 01-JUN-06:10 | 0.552221E+10 | 4210.73 | 01-JUN-07:10 |
| July | 0.393546E+10 | 2610.78 | 03-JUL-07:10 | 0.337280E+10 | 2216.18 | 03-JUL-07:10 |
| August | 0.415384E+10 | 2610.78 | 01-AUG-07:10 | 0.350574E+10 | 2216.18 | 01-AUG-07:10 |
| September | 0.608605E+10 | 4699.41 | 05-SEP-06:10 | 0.524330E+10 | 4210.73 | 05-SEP-07:10 |
| October | 0.647363E+10 | 4699.41 | 02-OCT-06:10 | 0.553791E+10 | 4210.73 | 02-OCT-07:10 |
| November | 0.639364E+10 | 4699.41 | 01-NOV-06:10 | 0.542561E+10 | 4210.73 | 01-NOV-07:10 |
| December | 0.628344E+10 | 4699.41 | 01-DEC-07:10 | 0.543997E+10 | 4210.73 | 01-DEC-08:09 |
| Annual Sum or Average | 0.719581E+11 | 0.612879E+11 | ||||
| Minimum of Months | 0.393546E+10 | 2610.78 | 0.337280E+10 | 2216.18 | ||
| Maximum of Months | 0.685401E+10 | 4699.41 | 0.573379E+10 | 4210.73 |
Report: ZoneElectricSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.590754E+10 | 4288.47 | 02-JAN-07:10 | 0.207549E+10 | 1578.10 | 02-JAN-08:09 |
| February | 0.534144E+10 | 4288.47 | 01-FEB-07:10 | 0.187582E+10 | 1578.10 | 01-FEB-08:09 |
| March | 0.625466E+10 | 4288.47 | 01-MAR-07:10 | 0.214891E+10 | 1578.10 | 01-MAR-08:09 |
| April | 0.566098E+10 | 4288.47 | 03-APR-06:10 | 0.199670E+10 | 1578.10 | 03-APR-07:10 |
| May | 0.608110E+10 | 4288.47 | 01-MAY-06:10 | 0.211220E+10 | 1578.10 | 01-MAY-07:10 |
| June | 0.600810E+10 | 4288.47 | 01-JUN-06:10 | 0.206961E+10 | 1578.10 | 01-JUN-07:10 |
| July | 0.359132E+10 | 2382.48 | 03-JUL-07:10 | 0.126406E+10 | 830.58 | 03-JUL-07:10 |
| August | 0.379060E+10 | 2382.48 | 01-AUG-07:10 | 0.131388E+10 | 830.58 | 01-AUG-07:10 |
| September | 0.555385E+10 | 4288.47 | 05-SEP-06:10 | 0.196508E+10 | 1578.10 | 05-SEP-07:10 |
| October | 0.590754E+10 | 4288.47 | 02-OCT-06:10 | 0.207549E+10 | 1578.10 | 02-OCT-07:10 |
| November | 0.583454E+10 | 4288.47 | 01-NOV-06:10 | 0.203341E+10 | 1578.10 | 01-NOV-07:10 |
| December | 0.573398E+10 | 4288.47 | 01-DEC-07:10 | 0.203879E+10 | 1578.10 | 01-DEC-08:09 |
| Annual Sum or Average | 0.656656E+11 | 0.229695E+11 | ||||
| Minimum of Months | 0.359132E+10 | 2382.48 | 0.126406E+10 | 830.58 | ||
| Maximum of Months | 0.625466E+10 | 4288.47 | 0.214891E+10 | 1578.10 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.269034E+10 | 1953.00 | 02-JAN-07:10 | 0.147381E+11 | 9714.90 | 02-JAN-10:09 |
| February | 0.243253E+10 | 1953.00 | 01-FEB-07:10 | 0.133142E+11 | 9714.90 | 01-FEB-10:09 |
| March | 0.284842E+10 | 1953.00 | 01-MAR-07:10 | 0.148878E+11 | 9714.90 | 01-MAR-10:09 |
| April | 0.257806E+10 | 1953.00 | 03-APR-06:10 | 0.142385E+11 | 9714.90 | 03-APR-09:09 |
| May | 0.276938E+10 | 1953.00 | 01-MAY-06:10 | 0.148130E+11 | 9714.90 | 01-MAY-09:09 |
| June | 0.273614E+10 | 1953.00 | 01-JUN-06:10 | 0.143883E+11 | 9714.90 | 01-JUN-09:09 |
| July | 0.163552E+10 | 1085.00 | 03-JUL-07:10 | 0.146632E+11 | 9714.90 | 03-JUL-09:09 |
| August | 0.172627E+10 | 1085.00 | 01-AUG-07:10 | 0.148878E+11 | 9714.90 | 01-AUG-09:09 |
| September | 0.252927E+10 | 1953.00 | 05-SEP-06:10 | 0.142385E+11 | 9714.90 | 01-SEP-09:09 |
| October | 0.269034E+10 | 1953.00 | 02-OCT-06:10 | 0.147381E+11 | 9714.90 | 02-OCT-09:09 |
| November | 0.265710E+10 | 1953.00 | 01-NOV-06:10 | 0.143134E+11 | 9714.90 | 01-NOV-09:09 |
| December | 0.261130E+10 | 1953.00 | 01-DEC-07:10 | 0.146632E+11 | 9714.90 | 01-DEC-10:09 |
| Annual Sum or Average | 0.299046E+11 | 0.173884E+12 | ||||
| Minimum of Months | 0.163552E+10 | 1085.00 | 0.133142E+11 | 9714.90 | ||
| Maximum of Months | 0.284842E+10 | 1953.00 | 0.148878E+11 | 9714.90 |
Report: ZoneElectricSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.378329E+10 | 2746.41 | 02-JAN-07:10 | 0.253516E+10 | 1999.46 | 02-JAN-10:09 |
| February | 0.342075E+10 | 2746.41 | 01-FEB-07:10 | 0.229042E+10 | 1999.46 | 01-FEB-10:09 |
| March | 0.400559E+10 | 2746.41 | 01-MAR-07:10 | 0.257259E+10 | 1999.46 | 01-MAR-10:09 |
| April | 0.362539E+10 | 2746.41 | 03-APR-06:10 | 0.244734E+10 | 1999.46 | 03-APR-09:09 |
| May | 0.389444E+10 | 2746.41 | 01-MAY-06:10 | 0.255387E+10 | 1999.46 | 01-MAY-09:09 |
| June | 0.384769E+10 | 2746.41 | 01-JUN-06:10 | 0.248477E+10 | 1999.46 | 01-JUN-09:09 |
| July | 0.229994E+10 | 1525.78 | 03-JUL-07:10 | 0.251644E+10 | 1999.46 | 03-JUL-09:09 |
| August | 0.242757E+10 | 1525.78 | 01-AUG-07:10 | 0.257259E+10 | 1999.46 | 01-AUG-09:09 |
| September | 0.355678E+10 | 2746.41 | 05-SEP-06:10 | 0.244734E+10 | 1999.46 | 01-SEP-09:09 |
| October | 0.378329E+10 | 2746.41 | 02-OCT-06:10 | 0.253516E+10 | 1999.46 | 02-OCT-09:09 |
| November | 0.373654E+10 | 2746.41 | 01-NOV-06:10 | 0.246606E+10 | 1999.46 | 01-NOV-09:09 |
| December | 0.367214E+10 | 2746.41 | 01-DEC-07:10 | 0.251644E+10 | 1999.46 | 01-DEC-10:09 |
| Annual Sum or Average | 0.420534E+11 | 0.299382E+11 | ||||
| Minimum of Months | 0.229994E+10 | 1525.78 | 0.229042E+10 | 1999.46 | ||
| Maximum of Months | 0.400559E+10 | 2746.41 | 0.257259E+10 | 1999.46 |
Report: ZoneElectricSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.825317E+10 | 5991.24 | 02-JAN-07:10 | 0.695901E+10 | 5291.26 | 02-JAN-08:09 |
| February | 0.746230E+10 | 5991.24 | 01-FEB-07:10 | 0.628953E+10 | 5291.26 | 01-FEB-08:09 |
| March | 0.873812E+10 | 5991.24 | 01-MAR-07:10 | 0.720516E+10 | 5291.26 | 01-MAR-08:09 |
| April | 0.790872E+10 | 5991.24 | 03-APR-06:10 | 0.669483E+10 | 5291.26 | 03-APR-07:10 |
| May | 0.849564E+10 | 5991.24 | 01-MAY-06:10 | 0.708208E+10 | 5291.26 | 01-MAY-07:10 |
| June | 0.839367E+10 | 5991.24 | 01-JUN-06:10 | 0.693929E+10 | 5291.26 | 01-JUN-07:10 |
| July | 0.501728E+10 | 3328.47 | 03-JUL-07:10 | 0.423831E+10 | 2784.88 | 03-JUL-07:10 |
| August | 0.529569E+10 | 3328.47 | 01-AUG-07:10 | 0.440537E+10 | 2784.88 | 01-AUG-07:10 |
| September | 0.775905E+10 | 5991.24 | 05-SEP-06:10 | 0.658880E+10 | 5291.26 | 05-SEP-07:10 |
| October | 0.825317E+10 | 5991.24 | 02-OCT-06:10 | 0.695901E+10 | 5291.26 | 02-OCT-07:10 |
| November | 0.815120E+10 | 5991.24 | 01-NOV-06:10 | 0.681790E+10 | 5291.26 | 01-NOV-07:10 |
| December | 0.801070E+10 | 5991.24 | 01-DEC-07:10 | 0.683594E+10 | 5291.26 | 01-DEC-08:09 |
| Annual Sum or Average | 0.917387E+11 | 0.770152E+11 | ||||
| Minimum of Months | 0.501728E+10 | 3328.47 | 0.423831E+10 | 2784.88 | ||
| Maximum of Months | 0.873812E+10 | 5991.24 | 0.720516E+10 | 5291.26 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94996566.36 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134406E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77670661.58 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111923E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262157E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 129536.81 | 0.197327E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1288682.47 | 0.178807E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79259.05 | 0.129233E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155876E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158633E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184630E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226401E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1497478.33 | 0.191206E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77670661.58 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1288682.47 | 0.262157E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271217E+09 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385790E+09 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222230E+09 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4328.31 | 0.315630E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735969E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 393288.32 | 0.544727E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4302803.38 | 0.485132E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 296544.82 | 0.351046E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438265E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454379E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533484E+09 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653481E+09 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4996964.84 | 0.539135E+10 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222230E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4302803.38 | 0.735969E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14721838.89 |
| February | 0.708259E+09 | 0.117967E+10 | 0.807077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20914980.63 |
| March | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12204196.51 |
| April | 0.745536E+09 | 0.125024E+10 | 0.859085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17010005.05 |
| May | 0.820090E+09 | 0.134302E+10 | 0.908779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41254942.68 |
| June | 0.505804E+09 | 0.132690E+10 | 0.890455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17460.01 | 31252337.42 |
| July | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 228286.93 | 27377865.49 |
| August | 0.200223E+09 | 0.837162E+09 | 0.565300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14116.13 | 19033389.97 |
| September | 0.459822E+09 | 0.122658E+10 | 0.845480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23232338.35 |
| October | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24283573.49 |
| November | 0.782813E+09 | 0.128857E+10 | 0.874878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28970276.07 |
| December | 0.745536E+09 | 0.126636E+10 | 0.877193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36524406.92 |
| Annual Sum or Average | 0.756518E+10 | 0.145024E+11 | 0.988265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 259863.07 | 0.296780E+09 |
| Minimum of Months | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12204196.51 |
| Maximum of Months | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 228286.93 | 41254942.68 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90325699.80 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126252E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75469566.75 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38201.99 | 0.102031E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249549E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 187206.65 | 0.190579E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1872214.05 | 0.165759E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 227692.43 | 0.112472E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138270E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145826E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174371E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221120E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2325315.13 | 0.179202E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75469566.75 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1872214.05 | 0.249549E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256948E+09 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361763E+09 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216219E+09 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 213498.85 | 0.288696E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.71 | 0.701584E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 609806.07 | 0.525492E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5983016.67 | 0.449394E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 856978.81 | 0.304476E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8571.88 | 0.387696E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418451E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504620E+09 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637681E+09 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7672034.00 | 0.505302E+10 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216219E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5983016.67 | 0.701584E+09 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94300585.96 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134137E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77590922.23 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111373E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261034E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 135819.81 | 0.196218E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1349815.03 | 0.177018E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 82002.05 | 0.128000E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155229E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158371E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184174E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225717E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1567636.89 | 0.190316E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77590922.23 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1349815.03 | 0.261034E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268854E+09 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385245E+09 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222486E+09 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7296.85 | 0.314546E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.734817E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 418632.26 | 0.542867E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4506479.76 | 0.481125E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 321986.07 | 0.347494E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436154E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453822E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532276E+09 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653034E+09 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5254394.94 | 0.537272E+10 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222486E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4506479.76 | 0.734817E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14673107.07 |
| February | 0.708259E+09 | 0.117967E+10 | 0.807077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20897757.94 |
| March | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12207684.36 |
| April | 0.745536E+09 | 0.125024E+10 | 0.859085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16984699.95 |
| May | 0.820090E+09 | 0.134302E+10 | 0.908779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41216739.43 |
| June | 0.505804E+09 | 0.132690E+10 | 0.890455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17598.29 | 31203226.19 |
| July | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 232617.17 | 27260846.95 |
| August | 0.200223E+09 | 0.837162E+09 | 0.565300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14640.68 | 18927175.75 |
| September | 0.459822E+09 | 0.122658E+10 | 0.845480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23171274.55 |
| October | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24266353.02 |
| November | 0.782813E+09 | 0.128857E+10 | 0.874878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28932659.16 |
| December | 0.745536E+09 | 0.126636E+10 | 0.877193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36496194.13 |
| Annual Sum or Average | 0.756518E+10 | 0.145024E+11 | 0.988265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 264856.14 | 0.296238E+09 |
| Minimum of Months | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12207684.36 |
| Maximum of Months | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 232617.17 | 41216739.43 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90258878.35 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126231E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75484461.89 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38172.89 | 0.102043E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249609E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 186937.70 | 0.190607E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1873798.30 | 0.165702E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 228412.26 | 0.112379E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138198E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145809E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174306E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221064E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2327321.15 | 0.179169E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75484461.89 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1873798.30 | 0.249609E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256764E+09 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.361722E+09 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216284E+09 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 212622.53 | 0.288771E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.69 | 0.701895E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 607192.73 | 0.525736E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5981937.76 | 0.449354E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 857725.78 | 0.304271E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8511.33 | 0.387552E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.418455E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504469E+09 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637526E+09 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7668112.81 | 0.505280E+10 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216284E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5981937.76 | 0.701895E+09 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94665912.74 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134496E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77863098.66 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111939E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262077E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 133016.42 | 0.197001E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1313478.84 | 0.178593E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80325.70 | 0.129045E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156104E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159147E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185101E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226397E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1526820.97 | 0.191243E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77863098.66 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1313478.84 | 0.262077E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270235E+09 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386759E+09 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223751E+09 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5725.83 | 0.316768E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738673E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 405093.49 | 0.545831E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4361291.50 | 0.486730E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 307067.79 | 0.351424E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439678E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.457325E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536511E+09 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.655807E+09 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5079178.61 | 0.540949E+10 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223751E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4361291.50 | 0.738673E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14766033.39 |
| February | 0.708259E+09 | 0.117967E+10 | 0.807077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21061376.08 |
| March | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12353871.64 |
| April | 0.745536E+09 | 0.125024E+10 | 0.859085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17266240.06 |
| May | 0.820090E+09 | 0.134302E+10 | 0.908779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41762530.43 |
| June | 0.505804E+09 | 0.132690E+10 | 0.890455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 17216.35 | 31629990.50 |
| July | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 211060.63 | 28017145.78 |
| August | 0.200223E+09 | 0.837162E+09 | 0.565300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 12691.90 | 19450517.26 |
| September | 0.459822E+09 | 0.122658E+10 | 0.845480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23614767.49 |
| October | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24662428.83 |
| November | 0.782813E+09 | 0.128857E+10 | 0.874878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29326962.66 |
| December | 0.745536E+09 | 0.126636E+10 | 0.877193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36740810.40 |
| Annual Sum or Average | 0.756518E+10 | 0.145024E+11 | 0.988265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 240968.88 | 0.300653E+09 |
| Minimum of Months | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12353871.64 |
| Maximum of Months | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 211060.63 | 41762530.43 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90390005.85 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126555E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75820228.68 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30340.56 | 0.103178E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251994E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 171824.92 | 0.192620E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1775987.08 | 0.168758E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 204983.80 | 0.114064E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139589E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146683E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174958E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221256E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2183136.36 | 0.180586E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75820228.68 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1775987.08 | 0.251994E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.642132E+10 | 0.588512E+10 | 0.549396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169707E+09 |
| February | 0.580977E+10 | 0.532117E+10 | 0.496542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239337E+09 |
| March | 0.703288E+10 | 0.623092E+10 | 0.568828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143570E+09 |
| April | 0.611554E+10 | 0.563950E+10 | 0.528539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114005.59 | 0.192978E+09 |
| May | 0.672710E+10 | 0.605802E+10 | 0.559112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.468334E+09 |
| June | 0.414905E+10 | 0.598530E+10 | 0.547839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 351040.90 | 0.351797E+09 |
| July | 0.142818E+10 | 0.357769E+10 | 0.334604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3701295.74 | 0.302986E+09 |
| August | 0.164241E+10 | 0.377621E+10 | 0.347792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 499745.96 | 0.203912E+09 |
| September | 0.377186E+10 | 0.553277E+10 | 0.520168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1356.40 | 0.258761E+09 |
| October | 0.642132E+10 | 0.588512E+10 | 0.549396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278133E+09 |
| November | 0.642132E+10 | 0.581240E+10 | 0.538255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334450E+09 |
| December | 0.611554E+10 | 0.571221E+10 | 0.539679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420986E+09 |
| Annual Sum or Average | 0.620563E+11 | 0.654164E+11 | 0.608015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4667444.59 | 0.336495E+10 |
| Minimum of Months | 0.142818E+10 | 0.357769E+10 | 0.334604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143570E+09 |
| Maximum of Months | 0.703288E+10 | 0.623092E+10 | 0.568828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3701295.74 | 0.468334E+09 |
Report: SpaceGainsMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.488438E+10 | 0.302663E+10 | 0.376728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91024296.06 |
| February | 0.441920E+10 | 0.273660E+10 | 0.340486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129695E+09 |
| March | 0.534956E+10 | 0.320447E+10 | 0.390054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78724769.09 |
| April | 0.465179E+10 | 0.290031E+10 | 0.362427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27565.85 | 0.106433E+09 |
| May | 0.511697E+10 | 0.311555E+10 | 0.383391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256395E+09 |
| June | 0.511697E+10 | 0.307815E+10 | 0.375661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 134029.54 | 0.193966E+09 |
| July | 0.244831E+10 | 0.183996E+10 | 0.229443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1462919.51 | 0.172871E+09 |
| August | 0.281556E+10 | 0.194205E+10 | 0.238486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 126181.36 | 0.118740E+09 |
| September | 0.454162E+10 | 0.284543E+10 | 0.356687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146659E+09 |
| October | 0.488438E+10 | 0.302663E+10 | 0.376728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154397E+09 |
| November | 0.488438E+10 | 0.298923E+10 | 0.369089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183448E+09 |
| December | 0.465179E+10 | 0.293771E+10 | 0.370066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227099E+09 |
| Annual Sum or Average | 0.537649E+11 | 0.336427E+11 | 0.416925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1750696.27 | 0.185945E+10 |
| Minimum of Months | 0.244831E+10 | 0.183996E+10 | 0.229443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78724769.09 |
| Maximum of Months | 0.534956E+10 | 0.320447E+10 | 0.390054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1462919.51 | 0.256395E+09 |
Report: SpaceGainsMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.222618E+10 | 0.371022E+10 | 0.253943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43762885.31 |
| February | 0.201416E+10 | 0.335468E+10 | 0.229513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62671279.10 |
| March | 0.243819E+10 | 0.392822E+10 | 0.262925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36914586.69 |
| April | 0.212017E+10 | 0.355537E+10 | 0.244302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52734901.39 |
| May | 0.233218E+10 | 0.381922E+10 | 0.258434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129733E+09 |
| June | 0.143841E+10 | 0.377338E+10 | 0.253223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50611.08 | 98877712.18 |
| July | 0.495129E+09 | 0.225552E+10 | 0.154661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 427797.48 | 93026041.70 |
| August | 0.569398E+09 | 0.238068E+10 | 0.160757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32826.12 | 64872230.67 |
| September | 0.130765E+10 | 0.348808E+10 | 0.240433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72493833.62 |
| October | 0.222618E+10 | 0.371022E+10 | 0.253943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73186205.54 |
| November | 0.222618E+10 | 0.366437E+10 | 0.248793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86119756.35 |
| December | 0.212017E+10 | 0.360121E+10 | 0.249452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109755E+09 |
| Annual Sum or Average | 0.215140E+11 | 0.412412E+11 | 0.281038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 511234.69 | 0.924147E+09 |
| Minimum of Months | 0.495129E+09 | 0.225552E+10 | 0.154661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36914586.69 |
| Maximum of Months | 0.243819E+10 | 0.392822E+10 | 0.262925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 427797.48 | 0.129733E+09 |
Report: SpaceGainsMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.139443E+10 | 0.296658E+10 | 0.795316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872288E+10 |
| February | 0.126163E+10 | 0.268230E+10 | 0.718803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765001E+10 |
| March | 0.152723E+10 | 0.314089E+10 | 0.823446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.872980E+10 |
| April | 0.132803E+10 | 0.284277E+10 | 0.765123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.638513E+10 |
| May | 0.146083E+10 | 0.305373E+10 | 0.809381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.675487E+10 |
| June | 0.900991E+09 | 0.301708E+10 | 0.793062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26379883.89 | 0.479472E+10 |
| July | 0.310138E+09 | 0.180345E+10 | 0.484379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53932532.85 | 0.322742E+10 |
| August | 0.356659E+09 | 0.190352E+10 | 0.503470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14597312.97 | 0.321698E+10 |
| September | 0.819082E+09 | 0.278897E+10 | 0.753006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432368E+10 |
| October | 0.139443E+10 | 0.296658E+10 | 0.795316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646768E+10 |
| November | 0.139443E+10 | 0.292992E+10 | 0.779188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.781014E+10 |
| December | 0.132803E+10 | 0.287942E+10 | 0.781250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.822469E+10 |
| Annual Sum or Average | 0.134759E+11 | 0.329752E+11 | 0.880174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 94909729.72 | 0.763080E+11 |
| Minimum of Months | 0.310138E+09 | 0.180345E+10 | 0.484379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321698E+10 |
| Maximum of Months | 0.152723E+10 | 0.314089E+10 | 0.823446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 53932532.85 | 0.872980E+10 |
Report: SpaceGainsMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.308232E+09 | 0.504438E+10 | 0.293011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.278876E+09 | 0.456100E+10 | 0.264822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.337587E+09 | 0.534079E+10 | 0.303375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.293554E+09 | 0.483386E+10 | 0.281887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.322909E+09 | 0.519259E+10 | 0.298193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.199160E+09 | 0.513026E+10 | 0.292181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 68554512.00 | 0.306659E+10 | 0.178455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 78837688.80 | 0.323676E+10 | 0.185489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.181054E+09 | 0.474238E+10 | 0.277423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.308232E+09 | 0.504438E+10 | 0.293011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.308232E+09 | 0.498206E+10 | 0.287069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.293554E+09 | 0.489618E+10 | 0.287829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.297878E+10 | 0.560712E+11 | 0.324275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68554512.00 | 0.306659E+10 | 0.178455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.337587E+09 | 0.534079E+10 | 0.303375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.774708E+09 | 0.228198E+10 | 0.883684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45830559.69 |
| February | 0.700926E+09 | 0.206331E+10 | 0.798670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67119144.98 |
| March | 0.848489E+09 | 0.241607E+10 | 0.914940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40439107.46 |
| April | 0.737817E+09 | 0.218674E+10 | 0.850137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58946630.59 |
| May | 0.811598E+09 | 0.234903E+10 | 0.899312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146443E+09 |
| June | 0.500567E+09 | 0.232083E+10 | 0.881180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 528.96 | 0.115871E+09 |
| July | 0.172304E+09 | 0.138727E+10 | 0.538198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 335152.84 | 0.106870E+09 |
| August | 0.198150E+09 | 0.146425E+10 | 0.559411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16370.93 | 74419303.89 |
| September | 0.455061E+09 | 0.214536E+10 | 0.836673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82713095.34 |
| October | 0.774708E+09 | 0.228198E+10 | 0.883684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81250680.46 |
| November | 0.774708E+09 | 0.225379E+10 | 0.865765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94454204.47 |
| December | 0.737817E+09 | 0.221494E+10 | 0.868056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115990E+09 |
| Annual Sum or Average | 0.748685E+10 | 0.253655E+11 | 0.977971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 352052.74 | 0.103035E+10 |
| Minimum of Months | 0.172304E+09 | 0.138727E+10 | 0.538198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40439107.46 |
| Maximum of Months | 0.848489E+09 | 0.241607E+10 | 0.914940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 335152.84 | 0.146443E+09 |
Report: SpaceGainsMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.156120E+10 | 0.647363E+10 | 0.553791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206557E+09 |
| February | 0.141251E+10 | 0.585328E+10 | 0.500514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295842E+09 |
| March | 0.170988E+10 | 0.685401E+10 | 0.573379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175078E+09 |
| April | 0.148685E+10 | 0.620345E+10 | 0.532767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256221E+09 |
| May | 0.163554E+10 | 0.666382E+10 | 0.563585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607936E+09 |
| June | 0.163554E+10 | 0.658383E+10 | 0.552221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 226381.65 | 0.462340E+09 |
| July | 0.840841E+09 | 0.393546E+10 | 0.337280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1226635.02 | 0.450128E+09 |
| August | 0.966967E+09 | 0.415384E+10 | 0.350574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 153103.19 | 0.324689E+09 |
| September | 0.145455E+10 | 0.608605E+10 | 0.524330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359963E+09 |
| October | 0.156120E+10 | 0.647363E+10 | 0.553791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.357057E+09 |
| November | 0.156120E+10 | 0.639364E+10 | 0.542561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411175E+09 |
| December | 0.148685E+10 | 0.628344E+10 | 0.543997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.503956E+09 |
| Annual Sum or Average | 0.173131E+11 | 0.719581E+11 | 0.612879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1606119.86 | 0.441094E+10 |
| Minimum of Months | 0.840841E+09 | 0.393546E+10 | 0.337280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175078E+09 |
| Maximum of Months | 0.170988E+10 | 0.685401E+10 | 0.573379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1226635.02 | 0.607936E+09 |
Report: SpaceGainsMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.789800E+10 | 0.590754E+10 | 0.207549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88989791.44 |
| February | 0.714581E+10 | 0.534144E+10 | 0.187582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128282E+09 |
| March | 0.865019E+10 | 0.625466E+10 | 0.214891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76451207.69 |
| April | 0.752191E+10 | 0.566098E+10 | 0.199670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108836E+09 |
| May | 0.827410E+10 | 0.608110E+10 | 0.211220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.259250E+09 |
| June | 0.827410E+10 | 0.600810E+10 | 0.206961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 95819.66 | 0.194121E+09 |
| July | 0.453307E+10 | 0.359132E+10 | 0.126406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 651802.01 | 0.192216E+09 |
| August | 0.521303E+10 | 0.379060E+10 | 0.131388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62033.27 | 0.135609E+09 |
| September | 0.737247E+10 | 0.555385E+10 | 0.196508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148322E+09 |
| October | 0.789800E+10 | 0.590754E+10 | 0.207549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149702E+09 |
| November | 0.789800E+10 | 0.583454E+10 | 0.203341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176988E+09 |
| December | 0.752191E+10 | 0.573398E+10 | 0.203879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221387E+09 |
| Annual Sum or Average | 0.882006E+11 | 0.656656E+11 | 0.229695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 809654.93 | 0.188015E+10 |
| Minimum of Months | 0.453307E+10 | 0.359132E+10 | 0.126406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76451207.69 |
| Maximum of Months | 0.865019E+10 | 0.625466E+10 | 0.214891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 651802.01 | 0.259250E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.204475E+10 | 0.269034E+10 | 0.811357E+10 | 0.909844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57407263.45 |
| February | 0.185001E+10 | 0.243253E+10 | 0.733032E+10 | 0.822599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79589731.66 |
| March | 0.223949E+10 | 0.284842E+10 | 0.823336E+10 | 0.959699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44834304.27 |
| April | 0.194738E+10 | 0.257806E+10 | 0.783252E+10 | 0.872454E+10 | 0.00 | 0.00 | 0.00 | 26.25 | 57011418.35 |
| May | 0.214212E+10 | 0.276938E+10 | 0.817347E+10 | 0.934772E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134464E+09 |
| June | 0.132119E+10 | 0.273614E+10 | 0.795231E+10 | 0.922308E+10 | 0.00 | 0.00 | 0.00 | 44972.78 | 0.101334E+09 |
| July | 0.454778E+09 | 0.163552E+10 | 0.805368E+10 | 0.884917E+10 | 0.00 | 0.00 | 0.00 | 172465.49 | 0.101324E+09 |
| August | 0.522995E+09 | 0.172627E+10 | 0.823336E+10 | 0.959699E+10 | 0.00 | 0.00 | 0.00 | 29168.47 | 73410180.75 |
| September | 0.120108E+10 | 0.252927E+10 | 0.783252E+10 | 0.872454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79085193.57 |
| October | 0.204475E+10 | 0.269034E+10 | 0.811357E+10 | 0.909844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86038557.87 |
| November | 0.204475E+10 | 0.265710E+10 | 0.789242E+10 | 0.897381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109774E+09 |
| December | 0.194738E+10 | 0.261130E+10 | 0.805368E+10 | 0.884917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142908E+09 |
| Annual Sum or Average | 0.197607E+11 | 0.299046E+11 | 0.958148E+11 | 0.108309E+12 | 0.00 | 0.00 | 0.00 | 246632.99 | 0.106718E+10 |
| Minimum of Months | 0.454778E+09 | 0.163552E+10 | 0.733032E+10 | 0.822599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44834304.27 |
| Maximum of Months | 0.223949E+10 | 0.284842E+10 | 0.823336E+10 | 0.959699E+10 | 0.00 | 0.00 | 0.00 | 172465.49 | 0.142908E+09 |
Report: SpaceGainsMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.229168E+11 | 0.378329E+10 | 0.253516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182448E+09 |
| February | 0.207343E+11 | 0.342075E+10 | 0.229042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258069E+09 |
| March | 0.250994E+11 | 0.400559E+10 | 0.257259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152466E+09 |
| April | 0.218255E+11 | 0.362539E+10 | 0.244734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208399E+09 |
| May | 0.240081E+11 | 0.389444E+10 | 0.255387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.498647E+09 |
| June | 0.240081E+11 | 0.384769E+10 | 0.248477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 202397.98 | 0.394571E+09 |
| July | 0.556624E+10 | 0.229994E+10 | 0.251644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 862154.37 | 0.376925E+09 |
| August | 0.640118E+10 | 0.242757E+10 | 0.257259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 135603.17 | 0.270223E+09 |
| September | 0.210126E+11 | 0.355678E+10 | 0.244734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293129E+09 |
| October | 0.229168E+11 | 0.378329E+10 | 0.253516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296857E+09 |
| November | 0.229168E+11 | 0.373654E+10 | 0.246606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358741E+09 |
| December | 0.218255E+11 | 0.367214E+10 | 0.251644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456307E+09 |
| Annual Sum or Average | 0.239231E+12 | 0.420534E+11 | 0.299382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1200155.52 | 0.374678E+10 |
| Minimum of Months | 0.556624E+10 | 0.229994E+10 | 0.229042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152466E+09 |
| Maximum of Months | 0.250994E+11 | 0.400559E+10 | 0.257259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 862154.37 | 0.498647E+09 |
Report: SpaceGainsMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.325382E+10 | 0.825317E+10 | 0.695901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199365E+09 |
| February | 0.294393E+10 | 0.746230E+10 | 0.628953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286290E+09 |
| March | 0.356371E+10 | 0.873812E+10 | 0.720516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175306E+09 |
| April | 0.309888E+10 | 0.790872E+10 | 0.669483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245303E+09 |
| May | 0.340876E+10 | 0.849564E+10 | 0.708208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588406E+09 |
| June | 0.210241E+10 | 0.839367E+10 | 0.693929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 224964.88 | 0.449024E+09 |
| July | 0.723690E+09 | 0.501728E+10 | 0.423831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1407838.61 | 0.428899E+09 |
| August | 0.832243E+09 | 0.529569E+10 | 0.440537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 145906.00 | 0.302668E+09 |
| September | 0.191128E+10 | 0.775905E+10 | 0.658880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340682E+09 |
| October | 0.325382E+10 | 0.825317E+10 | 0.695901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347499E+09 |
| November | 0.325382E+10 | 0.815120E+10 | 0.681790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407125E+09 |
| December | 0.309888E+10 | 0.801070E+10 | 0.683594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496237E+09 |
| Annual Sum or Average | 0.314452E+11 | 0.917387E+11 | 0.770152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1778709.50 | 0.426680E+10 |
| Minimum of Months | 0.723690E+09 | 0.501728E+10 | 0.423831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175306E+09 |
| Maximum of Months | 0.356371E+10 | 0.873812E+10 | 0.720516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1407838.61 | 0.588406E+09 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 259.81 | 07-JAN-10:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 273.94 | 01-FEB-21:03 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 264.56 | 11-MAR-17:00 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 277.71 | 23-APR-21:55 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 428.02 | 04-MAY-23:00 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 13-JUN-15:30 | 315.27 | 05-JUN-21:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.97 | 22-JUL-12:10 | 322.87 | 30-JUL-18:53 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.74 | 14-AUG-18:00 | 206.59 | 22-AUG-21:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 280.30 | 29-SEP-05:53 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 338.92 | 01-OCT-24:00 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 400.77 | 15-NOV-07:00 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 484.26 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.59 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 49.97 | 484.26 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 761.62 | 08-JAN-08:00 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 759.55 | 08-FEB-22:00 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 761.79 | 11-MAR-17:00 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.60 | 30-APR-16:55 | 824.26 | 23-APR-21:55 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1253.76 | 04-MAY-23:00 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.58 | 25-JUN-16:00 | 868.14 | 05-JUN-21:15 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.24 | 22-JUL-12:10 | 826.36 | 30-JUL-18:53 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.34 | 14-AUG-18:00 | 557.96 | 22-AUG-21:00 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 812.10 | 29-SEP-05:53 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 981.80 | 01-OCT-24:00 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1184.97 | 15-NOV-07:00 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1430.69 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 557.96 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 149.24 | 1430.69 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1178.08 | 02-JAN-08:09 | 947.12 | 02-JAN-07:10 | 678.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 42.12 | 08-JAN-08:00 |
| February | 1178.08 | 01-FEB-08:09 | 947.12 | 01-FEB-07:10 | 678.98 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 42.54 | 08-FEB-22:00 |
| March | 1178.08 | 01-MAR-08:09 | 947.12 | 01-MAR-07:10 | 678.98 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 41.39 | 11-MAR-17:00 |
| April | 1178.08 | 03-APR-07:10 | 947.12 | 03-APR-06:10 | 678.98 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 46.27 | 23-APR-21:55 |
| May | 1178.08 | 01-MAY-07:10 | 947.12 | 01-MAY-06:10 | 678.98 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 72.77 | 04-MAY-23:00 |
| June | 1178.08 | 01-JUN-07:10 | 947.12 | 01-JUN-06:10 | 678.98 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 13-JUN-15:30 | 50.08 | 05-JUN-21:00 |
| July | 186.01 | 03-JUL-07:10 | 526.18 | 03-JUL-07:10 | 357.36 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 | 22-JUL-12:10 | 44.70 | 30-JUL-18:53 |
| August | 186.01 | 01-AUG-07:10 | 526.18 | 01-AUG-07:10 | 357.36 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 14-AUG-18:00 | 30.92 | 22-AUG-21:00 |
| September | 1178.08 | 18-SEP-07:10 | 947.12 | 05-SEP-06:10 | 678.98 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 44.70 | 29-SEP-05:53 |
| October | 1178.08 | 02-OCT-07:10 | 947.12 | 02-OCT-06:10 | 678.98 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 52.30 | 20-OCT-22:00 |
| November | 1178.08 | 01-NOV-07:10 | 947.12 | 01-NOV-06:10 | 678.98 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 65.46 | 15-NOV-07:00 |
| December | 1178.08 | 01-DEC-08:09 | 947.12 | 01-DEC-07:10 | 678.98 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 81.06 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.92 | |||||
| Maximum of Months | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 | 81.06 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 237.41 | 08-JAN-08:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 273.81 | 01-FEB-21:03 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 258.88 | 27-MAR-20:03 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 | 30-APR-14:30 | 261.46 | 23-APR-21:55 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 419.55 | 04-MAY-23:00 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.44 | 25-JUN-12:50 | 310.02 | 05-JUN-21:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.40 | 22-JUL-11:55 | 295.10 | 30-JUL-18:53 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.59 | 20-AUG-13:20 | 183.88 | 22-AUG-21:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 260.73 | 29-SEP-05:53 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 317.13 | 20-OCT-22:00 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 387.60 | 15-NOV-07:00 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 471.72 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.88 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 67.40 | 471.72 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 710.58 | 08-JAN-08:00 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 736.06 | 08-FEB-22:00 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 718.04 | 11-MAR-17:00 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.28 | 30-APR-14:30 | 777.57 | 23-APR-21:55 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 | 22-MAY-15:10 | 1232.50 | 04-MAY-23:00 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.87 | 25-JUN-16:00 | 855.71 | 05-JUN-21:15 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.72 | 22-JUL-12:00 | 748.32 | 30-JUL-18:53 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.06 | 20-AUG-13:20 | 493.85 | 22-AUG-21:00 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.86 | 10-SEP-15:00 | 753.04 | 29-SEP-05:53 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 918.56 | 20-OCT-22:00 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1146.44 | 15-NOV-07:00 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1397.27 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.85 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 193.72 | 1397.27 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 253.39 | 08-JAN-08:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 273.95 | 01-FEB-21:03 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 263.72 | 11-MAR-17:00 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 276.58 | 23-APR-21:55 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 427.25 | 04-MAY-23:00 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 13-JUN-15:30 | 313.77 | 05-JUN-21:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 51.47 | 22-JUL-12:10 | 319.15 | 30-JUL-18:53 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 | 14-AUG-18:00 | 205.16 | 22-AUG-21:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 280.44 | 29-SEP-05:53 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 337.44 | 01-OCT-24:00 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 400.40 | 15-NOV-07:00 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 482.63 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.16 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 51.47 | 482.63 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 756.13 | 08-JAN-08:00 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 759.73 | 08-FEB-22:00 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 760.28 | 11-MAR-17:00 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 | 30-APR-16:55 | 823.01 | 23-APR-21:55 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1257.40 | 04-MAY-23:00 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.54 | 25-JUN-16:00 | 866.57 | 05-JUN-21:30 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.19 | 22-JUL-12:10 | 816.08 | 30-JUL-18:53 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.96 | 14-AUG-18:00 | 554.09 | 22-AUG-21:00 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 813.41 | 29-SEP-05:53 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 973.96 | 01-OCT-24:00 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1186.01 | 15-NOV-07:00 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1431.24 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 554.09 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 154.19 | 1431.24 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1178.08 | 02-JAN-08:09 | 947.12 | 02-JAN-07:10 | 678.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 41.93 | 08-JAN-08:00 |
| February | 1178.08 | 01-FEB-08:09 | 947.12 | 01-FEB-07:10 | 678.98 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 42.53 | 08-FEB-22:00 |
| March | 1178.08 | 01-MAR-08:09 | 947.12 | 01-MAR-07:10 | 678.98 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 41.36 | 11-MAR-17:00 |
| April | 1178.08 | 03-APR-07:10 | 947.12 | 03-APR-06:10 | 678.98 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 46.20 | 23-APR-21:55 |
| May | 1178.08 | 01-MAY-07:10 | 947.12 | 01-MAY-06:10 | 678.98 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 72.79 | 04-MAY-23:00 |
| June | 1178.08 | 01-JUN-07:10 | 947.12 | 01-JUN-06:10 | 678.98 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 13-JUN-15:30 | 50.00 | 05-JUN-21:00 |
| July | 186.01 | 03-JUL-07:10 | 526.18 | 03-JUL-07:10 | 357.36 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 | 22-JUL-12:10 | 44.46 | 30-JUL-18:53 |
| August | 186.01 | 01-AUG-07:10 | 526.18 | 01-AUG-07:10 | 357.36 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 14-AUG-18:00 | 30.76 | 22-AUG-21:00 |
| September | 1178.08 | 18-SEP-07:10 | 947.12 | 05-SEP-06:10 | 678.98 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 44.69 | 29-SEP-05:53 |
| October | 1178.08 | 02-OCT-07:10 | 947.12 | 02-OCT-06:10 | 678.98 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 52.38 | 20-OCT-22:00 |
| November | 1178.08 | 01-NOV-07:10 | 947.12 | 01-NOV-06:10 | 678.98 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 65.40 | 15-NOV-07:00 |
| December | 1178.08 | 01-DEC-08:09 | 947.12 | 01-DEC-07:10 | 678.98 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 81.05 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.76 | |||||
| Maximum of Months | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 7.24 | 81.05 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 237.06 | 08-JAN-08:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 273.82 | 01-FEB-21:03 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 258.90 | 27-MAR-20:03 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 | 30-APR-14:30 | 261.41 | 23-APR-21:55 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 419.61 | 04-MAY-23:00 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.41 | 25-JUN-12:50 | 310.03 | 05-JUN-21:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.54 | 22-JUL-11:55 | 294.99 | 30-JUL-18:53 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.65 | 20-AUG-13:20 | 183.70 | 22-AUG-21:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 260.68 | 29-SEP-05:53 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 317.20 | 20-OCT-22:00 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 387.37 | 15-NOV-07:00 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 471.72 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.70 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 67.54 | 471.72 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 709.66 | 08-JAN-08:00 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 736.11 | 08-FEB-22:00 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 718.31 | 11-MAR-17:00 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.20 | 30-APR-14:30 | 777.49 | 23-APR-21:55 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 | 22-MAY-15:10 | 1232.92 | 04-MAY-23:00 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 25-JUN-16:00 | 855.88 | 05-JUN-21:15 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.67 | 22-JUL-12:00 | 748.21 | 30-JUL-18:53 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.14 | 20-AUG-13:20 | 493.42 | 22-AUG-21:00 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 | 10-SEP-15:00 | 752.98 | 29-SEP-05:53 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 918.87 | 20-OCT-22:00 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1145.83 | 15-NOV-07:00 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1397.30 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 493.42 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 193.67 | 1397.30 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 255.29 | 07-JAN-10:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 274.01 | 01-FEB-21:03 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 264.84 | 11-MAR-17:00 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 278.13 | 23-APR-21:55 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 428.70 | 04-MAY-23:00 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 13-JUN-15:30 | 314.92 | 05-JUN-21:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.63 | 22-JUL-12:10 | 321.56 | 30-JUL-18:53 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 14-AUG-18:00 | 206.56 | 22-AUG-21:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 281.04 | 29-SEP-05:53 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 338.68 | 01-OCT-24:00 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 402.77 | 15-NOV-07:00 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 484.64 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.56 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 50.63 | 484.64 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 760.44 | 08-JAN-08:00 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 762.75 | 08-FEB-22:00 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 765.49 | 11-MAR-17:00 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 | 30-APR-16:55 | 828.26 | 23-APR-21:55 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1262.63 | 04-MAY-23:00 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.53 | 25-JUN-16:00 | 870.86 | 05-JUN-21:30 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 150.99 | 22-JUL-12:10 | 824.69 | 30-JUL-18:53 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.56 | 14-AUG-18:00 | 558.97 | 22-AUG-21:00 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 816.04 | 29-SEP-05:53 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 978.54 | 01-OCT-24:00 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1196.85 | 15-NOV-07:00 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1439.92 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 558.97 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 150.99 | 1439.92 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1178.08 | 02-JAN-08:09 | 947.12 | 02-JAN-07:10 | 678.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 42.26 | 08-JAN-08:00 |
| February | 1178.08 | 01-FEB-08:09 | 947.12 | 01-FEB-07:10 | 678.98 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 42.92 | 08-FEB-22:00 |
| March | 1178.08 | 01-MAR-08:09 | 947.12 | 01-MAR-07:10 | 678.98 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 41.92 | 11-MAR-17:00 |
| April | 1178.08 | 03-APR-07:10 | 947.12 | 03-APR-06:10 | 678.98 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 46.84 | 23-APR-21:55 |
| May | 1178.08 | 01-MAY-07:10 | 947.12 | 01-MAY-06:10 | 678.98 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 73.66 | 04-MAY-23:00 |
| June | 1178.08 | 01-JUN-07:10 | 947.12 | 01-JUN-06:10 | 678.98 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.23 | 13-JUN-15:30 | 50.62 | 05-JUN-21:00 |
| July | 186.01 | 03-JUL-07:10 | 526.18 | 03-JUL-07:10 | 357.36 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 22-JUL-12:10 | 45.48 | 30-JUL-18:53 |
| August | 186.01 | 01-AUG-07:10 | 526.18 | 01-AUG-07:10 | 357.36 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.01 | 14-AUG-18:00 | 31.46 | 22-AUG-21:00 |
| September | 1178.08 | 18-SEP-07:10 | 947.12 | 05-SEP-06:10 | 678.98 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 45.10 | 29-SEP-05:53 |
| October | 1178.08 | 02-OCT-07:10 | 947.12 | 02-OCT-06:10 | 678.98 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 53.46 | 20-OCT-22:00 |
| November | 1178.08 | 01-NOV-07:10 | 947.12 | 01-NOV-06:10 | 678.98 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 66.47 | 15-NOV-07:00 |
| December | 1178.08 | 01-DEC-08:09 | 947.12 | 01-DEC-07:10 | 678.98 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 81.88 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.46 | |||||
| Maximum of Months | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 6.75 | 81.88 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 237.37 | 08-JAN-08:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 273.84 | 01-FEB-21:03 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 258.99 | 27-MAR-20:03 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.46 | 30-APR-14:30 | 263.99 | 23-APR-21:55 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 421.96 | 04-MAY-23:00 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 25-JUN-12:50 | 312.56 | 05-JUN-21:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.34 | 22-JUL-11:55 | 300.30 | 30-JUL-18:53 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 | 20-AUG-13:20 | 185.52 | 22-AUG-21:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 261.43 | 29-SEP-05:53 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 318.43 | 20-OCT-22:00 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 389.00 | 15-NOV-07:00 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 472.98 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.52 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 65.34 | 472.98 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 9663.62 | 02-JAN-08:09 | 4272.19 | 02-JAN-07:10 | 4177.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 468.23 | 08-JAN-08:00 |
| February | 9663.62 | 01-FEB-08:09 | 4272.19 | 01-FEB-07:10 | 4177.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 487.50 | 08-FEB-22:00 |
| March | 9663.62 | 01-MAR-08:09 | 4272.19 | 01-MAR-07:10 | 4177.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 478.37 | 11-MAR-17:00 |
| April | 9663.62 | 03-APR-07:10 | 4272.19 | 03-APR-06:10 | 4177.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.90 | 30-APR-17:00 | 517.38 | 23-APR-21:55 |
| May | 9663.62 | 01-MAY-07:10 | 4272.19 | 01-MAY-06:10 | 4177.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 818.35 | 04-MAY-23:00 |
| June | 9663.62 | 01-JUN-07:10 | 4272.19 | 01-JUN-06:10 | 4177.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.70 | 25-JUN-16:00 | 570.36 | 05-JUN-21:00 |
| July | 1525.83 | 03-JUL-07:10 | 2373.44 | 03-JUL-07:10 | 2198.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 122.53 | 22-JUL-11:58 | 504.91 | 30-JUL-18:53 |
| August | 1525.83 | 01-AUG-07:10 | 2373.44 | 01-AUG-07:10 | 2198.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.01 | 20-AUG-16:00 | 328.45 | 22-AUG-21:00 |
| September | 9663.62 | 18-SEP-07:10 | 4272.19 | 05-SEP-06:10 | 4177.31 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 11-SEP-17:00 | 498.15 | 29-SEP-05:53 |
| October | 9663.62 | 02-OCT-07:10 | 4272.19 | 02-OCT-06:10 | 4177.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 610.50 | 20-OCT-22:00 |
| November | 9663.62 | 01-NOV-07:10 | 4272.19 | 01-NOV-06:10 | 4177.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 760.37 | 15-NOV-07:00 |
| December | 9663.62 | 01-DEC-08:09 | 4272.19 | 01-DEC-07:10 | 4177.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 925.13 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 1525.83 | 2373.44 | 2198.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.45 | |||||
| Maximum of Months | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 122.53 | 925.13 |
Report: PeakSpaceGainsMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 4969.86 | 02-JAN-08:09 | 2197.13 | 02-JAN-07:10 | 2864.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 252.81 | 08-JAN-08:00 |
| February | 4969.86 | 01-FEB-08:09 | 2197.13 | 01-FEB-07:10 | 2864.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 268.04 | 08-FEB-22:00 |
| March | 4969.86 | 01-MAR-08:09 | 2197.13 | 01-MAR-07:10 | 2864.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 260.50 | 11-MAR-17:00 |
| April | 4969.86 | 03-APR-07:10 | 2197.13 | 03-APR-06:10 | 2864.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 | 30-APR-16:55 | 281.82 | 23-APR-21:55 |
| May | 4969.86 | 01-MAY-07:10 | 2197.13 | 01-MAY-06:10 | 2864.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 449.94 | 04-MAY-23:00 |
| June | 4969.86 | 01-JUN-07:10 | 2197.13 | 01-JUN-06:10 | 2864.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.87 | 25-JUN-16:00 | 313.04 | 05-JUN-21:00 |
| July | 2615.72 | 03-JUL-07:10 | 1220.63 | 03-JUL-07:10 | 1507.60 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.38 | 22-JUL-12:10 | 277.90 | 30-JUL-18:53 |
| August | 2615.72 | 01-AUG-07:10 | 1220.63 | 01-AUG-07:10 | 1507.60 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 | 20-AUG-16:00 | 189.57 | 22-AUG-21:00 |
| September | 4969.86 | 05-SEP-07:10 | 2197.13 | 05-SEP-06:10 | 2864.44 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 274.09 | 29-SEP-05:53 |
| October | 4969.86 | 02-OCT-07:10 | 2197.13 | 02-OCT-06:10 | 2864.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 345.16 | 20-OCT-22:00 |
| November | 4969.86 | 01-NOV-07:10 | 2197.13 | 01-NOV-06:10 | 2864.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 420.83 | 15-NOV-07:00 |
| December | 4969.86 | 01-DEC-08:09 | 2197.13 | 01-DEC-07:10 | 2864.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 502.91 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2615.72 | 1220.63 | 1507.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.57 | |||||
| Maximum of Months | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 54.38 | 502.91 |
Report: PeakSpaceGainsMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3350.23 | 02-JAN-08:09 | 2693.36 | 02-JAN-07:10 | 1930.85 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 125.78 | 08-JAN-08:00 |
| February | 3350.23 | 01-FEB-08:09 | 2693.36 | 01-FEB-07:10 | 1930.85 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 125.14 | 08-FEB-22:00 |
| March | 3350.23 | 01-MAR-08:09 | 2693.36 | 01-MAR-07:10 | 1930.85 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 123.78 | 11-MAR-17:00 |
| April | 3350.23 | 03-APR-07:10 | 2693.36 | 03-APR-06:10 | 1930.85 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 145.67 | 23-APR-21:55 |
| May | 3350.23 | 01-MAY-07:10 | 2693.36 | 01-MAY-06:10 | 1930.85 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 228.24 | 04-MAY-23:00 |
| June | 3350.23 | 01-JUN-07:10 | 2693.36 | 01-JUN-06:10 | 1930.85 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.68 | 13-JUN-15:30 | 155.89 | 05-JUN-21:00 |
| July | 528.98 | 03-JUL-07:10 | 1496.31 | 03-JUL-07:10 | 1016.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.44 | 22-JUL-15:10 | 147.72 | 30-JUL-18:53 |
| August | 528.98 | 01-AUG-07:10 | 1496.31 | 01-AUG-07:10 | 1016.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.79 | 14-AUG-16:50 | 105.03 | 22-AUG-21:00 |
| September | 3350.23 | 18-SEP-07:10 | 2693.36 | 05-SEP-06:10 | 1930.85 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 135.95 | 29-SEP-05:53 |
| October | 3350.23 | 02-OCT-07:10 | 2693.36 | 02-OCT-06:10 | 1930.85 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 157.40 | 20-OCT-22:00 |
| November | 3350.23 | 01-NOV-07:10 | 2693.36 | 01-NOV-06:10 | 1930.85 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 193.95 | 15-NOV-07:00 |
| December | 3350.23 | 01-DEC-08:09 | 2693.36 | 01-DEC-07:10 | 1930.85 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 241.21 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 528.98 | 1496.31 | 1016.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.03 | |||||
| Maximum of Months | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 15.44 | 241.21 |
Report: PeakSpaceGainsMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 2098.51 | 02-JAN-08:09 | 2153.53 | 02-JAN-07:10 | 604.72 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 76790.41 | 10-JAN-07:01 |
| February | 2098.51 | 01-FEB-08:09 | 2153.53 | 01-FEB-07:10 | 604.72 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 75949.37 | 17-FEB-07:01 |
| March | 2098.51 | 01-MAR-08:09 | 2153.53 | 01-MAR-07:10 | 604.72 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 61919.67 | 08-MAR-07:01 |
| April | 2098.51 | 03-APR-07:10 | 2153.53 | 03-APR-06:10 | 604.72 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 58595.45 | 17-APR-06:01 |
| May | 2098.51 | 01-MAY-07:10 | 2153.53 | 01-MAY-06:10 | 604.72 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 56126.14 | 01-MAY-06:01 |
| June | 2098.51 | 01-JUN-07:10 | 2153.53 | 01-JUN-06:10 | 604.72 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4906.77 | 13-JUN-15:00 | 44323.82 | 08-JUN-06:01 |
| July | 331.34 | 03-JUL-07:10 | 1196.41 | 03-JUL-07:10 | 318.27 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9112.43 | 21-JUL-14:05 | 38683.01 | 05-JUL-06:01 |
| August | 331.34 | 01-AUG-07:10 | 1196.41 | 01-AUG-07:10 | 318.27 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3585.28 | 14-AUG-15:00 | 41492.58 | 24-AUG-06:01 |
| September | 2098.51 | 18-SEP-07:10 | 2153.53 | 05-SEP-06:10 | 604.72 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 54757.63 | 21-SEP-06:01 |
| October | 2098.51 | 02-OCT-07:10 | 2153.53 | 02-OCT-06:10 | 604.72 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 60889.79 | 04-OCT-06:01 |
| November | 2098.51 | 01-NOV-07:10 | 2153.53 | 01-NOV-06:10 | 604.72 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 66028.97 | 29-NOV-07:01 |
| December | 2098.51 | 01-DEC-08:09 | 2153.53 | 01-DEC-07:10 | 604.72 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 68359.27 | 27-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38683.01 | |||||
| Maximum of Months | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 9112.43 | 76790.41 |
Report: PeakSpaceGainsMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 463.87 | 02-JAN-08:09 | 3661.88 | 02-JAN-07:10 | 2227.90 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
| February | 463.87 | 01-FEB-08:09 | 3661.88 | 01-FEB-07:10 | 2227.90 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 463.87 | 01-MAR-08:09 | 3661.88 | 01-MAR-07:10 | 2227.90 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 463.87 | 03-APR-07:10 | 3661.88 | 03-APR-06:10 | 2227.90 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 463.87 | 01-MAY-07:10 | 3661.88 | 01-MAY-06:10 | 2227.90 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 463.87 | 01-JUN-07:10 | 3661.88 | 01-JUN-06:10 | 2227.90 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 01-JUN-00:03 |
| July | 73.24 | 03-JUL-07:10 | 2034.38 | 03-JUL-07:10 | 1172.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 |
| August | 73.24 | 01-AUG-07:10 | 2034.38 | 01-AUG-07:10 | 1172.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 |
| September | 463.87 | 18-SEP-07:10 | 3661.88 | 05-SEP-06:10 | 2227.90 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 01-SEP-00:05 |
| October | 463.87 | 02-OCT-07:10 | 3661.88 | 02-OCT-06:10 | 2227.90 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 463.87 | 01-NOV-07:10 | 3661.88 | 01-NOV-06:10 | 2227.90 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 463.87 | 01-DEC-08:09 | 3661.88 | 01-DEC-07:10 | 2227.90 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 73.24 | 2034.38 | 1172.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
| Maximum of Months | 463.87 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1165.88 | 02-JAN-08:09 | 1656.56 | 02-JAN-07:10 | 671.91 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 132.52 | 08-JAN-08:00 |
| February | 1165.88 | 01-FEB-08:09 | 1656.56 | 01-FEB-07:10 | 671.91 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 134.71 | 08-FEB-22:00 |
| March | 1165.88 | 01-MAR-08:09 | 1656.56 | 01-MAR-07:10 | 671.91 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 136.17 | 11-MAR-17:00 |
| April | 1165.88 | 03-APR-07:10 | 1656.56 | 03-APR-06:10 | 671.91 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 158.70 | 23-APR-21:55 |
| May | 1165.88 | 01-MAY-07:10 | 1656.56 | 01-MAY-06:10 | 671.91 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 250.08 | 04-MAY-23:00 |
| June | 1165.88 | 01-JUN-07:10 | 1656.56 | 01-JUN-06:10 | 671.91 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.36 | 13-JUN-17:00 | 177.26 | 05-JUN-21:00 |
| July | 184.09 | 03-JUL-07:10 | 920.31 | 03-JUL-07:10 | 353.64 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.46 | 22-JUL-15:10 | 170.58 | 30-JUL-18:53 |
| August | 184.09 | 01-AUG-07:10 | 920.31 | 01-AUG-07:10 | 353.64 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.04 | 14-AUG-18:00 | 120.56 | 22-AUG-21:00 |
| September | 1165.88 | 18-SEP-07:10 | 1656.56 | 05-SEP-06:10 | 671.91 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 152.99 | 29-SEP-05:53 |
| October | 1165.88 | 02-OCT-07:10 | 1656.56 | 02-OCT-06:10 | 671.91 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 176.47 | 20-OCT-22:00 |
| November | 1165.88 | 01-NOV-07:10 | 1656.56 | 01-NOV-06:10 | 671.91 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 213.51 | 15-NOV-07:00 |
| December | 1165.88 | 01-DEC-08:09 | 1656.56 | 01-DEC-07:10 | 671.91 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 258.99 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 184.09 | 920.31 | 353.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.56 | |||||
| Maximum of Months | 1165.88 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 14.46 | 258.99 |
Report: PeakSpaceGainsMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 2705.96 | 02-JAN-08:09 | 4699.41 | 02-JAN-07:10 | 4210.73 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 579.03 | 08-JAN-08:00 |
| February | 2705.96 | 01-FEB-08:09 | 4699.41 | 01-FEB-07:10 | 4210.73 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 582.76 | 08-FEB-22:00 |
| March | 2705.96 | 01-MAR-08:09 | 4699.41 | 01-MAR-07:10 | 4210.73 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 590.98 | 11-MAR-17:00 |
| April | 2705.96 | 03-APR-07:10 | 4699.41 | 03-APR-06:10 | 4210.73 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 669.87 | 23-APR-21:55 |
| May | 2705.96 | 01-MAY-07:10 | 4699.41 | 01-MAY-06:10 | 4210.73 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1020.86 | 04-MAY-23:00 |
| June | 2705.96 | 01-JUN-07:10 | 4699.41 | 01-JUN-06:10 | 4210.73 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.16 | 13-JUN-15:30 | 714.51 | 05-JUN-21:00 |
| July | 1424.19 | 03-JUL-07:10 | 2610.78 | 03-JUL-07:10 | 2216.18 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.38 | 22-JUL-15:10 | 712.50 | 30-JUL-18:53 |
| August | 1424.19 | 01-AUG-07:10 | 2610.78 | 01-AUG-07:10 | 2216.18 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.01 | 14-AUG-16:50 | 501.25 | 22-AUG-21:00 |
| September | 2705.96 | 05-SEP-07:10 | 4699.41 | 05-SEP-06:10 | 4210.73 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 639.73 | 06-SEP-04:00 |
| October | 2705.96 | 02-OCT-07:10 | 4699.41 | 02-OCT-06:10 | 4210.73 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 751.26 | 01-OCT-24:00 |
| November | 2705.96 | 01-NOV-07:10 | 4699.41 | 01-NOV-06:10 | 4210.73 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 916.82 | 15-NOV-07:00 |
| December | 2705.96 | 01-DEC-08:09 | 4699.41 | 01-DEC-07:10 | 4210.73 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1097.13 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 1424.19 | 2610.78 | 2216.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 501.25 | |||||
| Maximum of Months | 2705.96 | 4699.41 | 4210.73 | 0.00 | 0.00 | 0.00 | 0.00 | 58.38 | 1097.13 |
Report: PeakSpaceGainsMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 13145.35 | 02-JAN-16:10 | 4288.47 | 02-JAN-07:10 | 1578.10 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 253.56 | 08-JAN-08:00 |
| February | 13145.35 | 01-FEB-16:10 | 4288.47 | 01-FEB-07:10 | 1578.10 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 258.84 | 01-FEB-21:03 |
| March | 13145.35 | 01-MAR-16:10 | 4288.47 | 01-MAR-07:10 | 1578.10 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 258.96 | 11-MAR-17:00 |
| April | 13145.35 | 03-APR-15:09 | 4288.47 | 03-APR-06:10 | 1578.10 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 289.73 | 23-APR-21:55 |
| May | 13145.35 | 01-MAY-15:09 | 4288.47 | 01-MAY-06:10 | 1578.10 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 440.29 | 04-MAY-23:00 |
| June | 13145.35 | 01-JUN-15:09 | 4288.47 | 01-JUN-06:10 | 1578.10 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.95 | 13-JUN-15:30 | 307.05 | 18-JUN-10:33 |
| July | 4843.02 | 03-JUL-07:10 | 2382.48 | 03-JUL-07:10 | 830.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.80 | 22-JUL-15:10 | 312.03 | 30-JUL-18:53 |
| August | 4843.02 | 01-AUG-07:10 | 2382.48 | 01-AUG-07:10 | 830.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.27 | 14-AUG-16:50 | 209.65 | 22-AUG-21:00 |
| September | 13145.35 | 05-SEP-15:09 | 4288.47 | 05-SEP-06:10 | 1578.10 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 270.99 | 06-SEP-04:00 |
| October | 13145.35 | 02-OCT-15:09 | 4288.47 | 02-OCT-06:10 | 1578.10 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 324.36 | 20-OCT-22:00 |
| November | 13145.35 | 01-NOV-15:09 | 4288.47 | 01-NOV-06:10 | 1578.10 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 404.18 | 15-NOV-07:00 |
| December | 13145.35 | 01-DEC-16:10 | 4288.47 | 01-DEC-07:10 | 1578.10 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 487.50 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 4843.02 | 2382.48 | 830.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.65 | |||||
| Maximum of Months | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.80 | 487.50 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3077.20 | 02-JAN-08:09 | 1953.00 | 02-JAN-07:10 | 6399.12 | 02-JAN-10:09 | 14425.49 | 02-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 169.83 | 08-JAN-08:00 |
| February | 3077.20 | 01-FEB-08:09 | 1953.00 | 01-FEB-07:10 | 6399.12 | 01-FEB-10:09 | 14425.49 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 163.07 | 08-FEB-22:00 |
| March | 3077.20 | 01-MAR-08:09 | 1953.00 | 01-MAR-07:10 | 6399.12 | 01-MAR-10:09 | 14425.49 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 154.67 | 27-MAR-21:00 |
| April | 3077.20 | 03-APR-07:10 | 1953.00 | 03-APR-06:10 | 6399.12 | 03-APR-09:09 | 14425.49 | 03-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.13 | 30-APR-14:37 | 158.03 | 23-APR-21:55 |
| May | 3077.20 | 01-MAY-07:10 | 1953.00 | 01-MAY-06:10 | 6399.12 | 01-MAY-09:09 | 14425.49 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 244.93 | 04-MAY-23:00 |
| June | 3077.20 | 01-JUN-07:10 | 1953.00 | 01-JUN-06:10 | 6399.12 | 01-JUN-09:09 | 14425.49 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 3.27 | 13-JUN-15:30 | 167.70 | 05-JUN-21:50 |
| July | 485.87 | 03-JUL-07:10 | 1085.00 | 03-JUL-07:10 | 6399.12 | 03-JUL-09:09 | 14425.49 | 03-JUL-09:09 | 0.00 | 0.00 | 0.00 | 8.91 | 22-JUL-15:00 | 169.56 | 30-JUL-19:00 |
| August | 485.87 | 01-AUG-07:10 | 1085.00 | 01-AUG-07:10 | 6399.12 | 01-AUG-09:09 | 14425.49 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 2.48 | 14-AUG-16:50 | 121.41 | 22-AUG-21:10 |
| September | 3077.20 | 18-SEP-07:10 | 1953.00 | 05-SEP-06:10 | 6399.12 | 01-SEP-09:09 | 14425.49 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 154.62 | 06-SEP-03:30 |
| October | 3077.20 | 02-OCT-07:10 | 1953.00 | 02-OCT-06:10 | 6399.12 | 02-OCT-09:09 | 14425.49 | 02-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 194.51 | 20-OCT-22:00 |
| November | 3077.20 | 01-NOV-07:10 | 1953.00 | 01-NOV-06:10 | 6399.12 | 01-NOV-09:09 | 14425.49 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 221.06 | 15-NOV-07:00 |
| December | 3077.20 | 01-DEC-08:09 | 1953.00 | 01-DEC-07:10 | 6399.12 | 01-DEC-10:09 | 14425.49 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 320.42 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 485.87 | 1085.00 | 6399.12 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 121.41 | ||||||
| Maximum of Months | 3077.20 | 1953.00 | 6399.12 | 14425.49 | 0.00 | 0.00 | 0.00 | 8.91 | 320.42 |
Report: PeakSpaceGainsMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 38654.47 | 02-JAN-09:09 | 2746.41 | 02-JAN-07:10 | 1999.46 | 02-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 509.50 | 08-JAN-08:00 |
| February | 38654.47 | 01-FEB-09:09 | 2746.41 | 01-FEB-07:10 | 1999.46 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 519.60 | 08-FEB-22:00 |
| March | 38654.47 | 01-MAR-09:09 | 2746.41 | 01-MAR-07:10 | 1999.46 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 512.23 | 11-MAR-17:00 |
| April | 38654.47 | 03-APR-08:09 | 2746.41 | 03-APR-06:10 | 1999.46 | 03-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 552.79 | 23-APR-21:55 |
| May | 38654.47 | 01-MAY-08:09 | 2746.41 | 01-MAY-06:10 | 1999.46 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 839.94 | 04-MAY-23:00 |
| June | 38654.47 | 01-JUN-08:09 | 2746.41 | 01-JUN-06:10 | 1999.46 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 14.71 | 13-JUN-15:30 | 626.42 | 18-JUN-15:53 |
| July | 14241.12 | 03-JUL-16:10 | 1525.78 | 03-JUL-07:10 | 1999.46 | 03-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 40.13 | 22-JUL-14:53 | 587.22 | 30-JUL-18:53 |
| August | 14241.12 | 01-AUG-16:10 | 1525.78 | 01-AUG-07:10 | 1999.46 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 11.15 | 14-AUG-16:50 | 397.92 | 22-AUG-21:00 |
| September | 38654.47 | 05-SEP-08:09 | 2746.41 | 05-SEP-06:10 | 1999.46 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 524.54 | 06-SEP-04:00 |
| October | 38654.47 | 02-OCT-08:09 | 2746.41 | 02-OCT-06:10 | 1999.46 | 02-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 647.13 | 20-OCT-22:00 |
| November | 38654.47 | 01-NOV-08:09 | 2746.41 | 01-NOV-06:10 | 1999.46 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 819.92 | 15-NOV-07:00 |
| December | 38654.47 | 01-DEC-09:09 | 2746.41 | 01-DEC-07:10 | 1999.46 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 994.66 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 14241.12 | 1525.78 | 1999.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 397.92 | |||||
| Maximum of Months | 38654.47 | 2746.41 | 1999.46 | 0.00 | 0.00 | 0.00 | 0.00 | 40.13 | 994.66 |
Report: PeakSpaceGainsMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 4896.76 | 02-JAN-08:09 | 5991.24 | 02-JAN-07:10 | 5291.26 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 554.07 | 08-JAN-08:00 |
| February | 4896.76 | 01-FEB-08:09 | 5991.24 | 01-FEB-07:10 | 5291.26 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 580.18 | 08-FEB-22:00 |
| March | 4896.76 | 01-MAR-08:09 | 5991.24 | 01-MAR-07:10 | 5291.26 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 581.01 | 11-MAR-17:00 |
| April | 4896.76 | 03-APR-07:10 | 5991.24 | 03-APR-06:10 | 5291.26 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 644.31 | 23-APR-21:55 |
| May | 4896.76 | 01-MAY-07:10 | 5991.24 | 01-MAY-06:10 | 5291.26 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 1006.56 | 04-MAY-23:00 |
| June | 4896.76 | 01-JUN-07:10 | 5991.24 | 01-JUN-06:10 | 5291.26 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.34 | 13-JUN-15:30 | 700.51 | 05-JUN-21:00 |
| July | 773.17 | 03-JUL-07:10 | 3328.47 | 03-JUL-07:10 | 2784.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.78 | 22-JUL-15:10 | 671.90 | 30-JUL-18:53 |
| August | 773.17 | 01-AUG-07:10 | 3328.47 | 01-AUG-07:10 | 2784.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.39 | 14-AUG-16:50 | 468.94 | 22-AUG-21:00 |
| September | 4896.76 | 18-SEP-07:10 | 5991.24 | 05-SEP-06:10 | 5291.26 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 614.36 | 29-SEP-05:53 |
| October | 4896.76 | 02-OCT-07:10 | 5991.24 | 02-OCT-06:10 | 5291.26 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 762.02 | 20-OCT-22:00 |
| November | 4896.76 | 01-NOV-07:10 | 5991.24 | 01-NOV-06:10 | 5291.26 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 929.57 | 15-NOV-07:00 |
| December | 4896.76 | 01-DEC-08:09 | 5991.24 | 01-DEC-07:10 | 5291.26 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1097.96 | 02-DEC-18:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 773.17 | 3328.47 | 2784.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.94 | |||||
| Maximum of Months | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 66.78 | 1097.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2617.88 | 19-JAN-15:40 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3495.11 | 09-FEB-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.12 |
| March | 3393.64 | 10-MAR-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 |
| April | 5688.04 | 28-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.61 |
| May | 5550.21 | 22-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 6019.76 | 13-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 0.00 |
| July | 3644.13 | 24-JUL-14:01 | 3356.84 | 5221.57 | 4836.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.48 |
| August | 4119.50 | 20-AUG-15:40 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.90 |
| September | 6030.05 | 24-SEP-15:31 | 0.00 | 2645.10 | 4052.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.57 |
| October | 5064.72 | 03-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.98 |
| November | 3617.01 | 10-NOV-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.14 |
| December | 2452.14 | 21-DEC-14:40 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.32 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2452.14 | 0.00 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6030.05 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 44.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 12856.33 | 20-JAN-15:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 17136.27 | 09-FEB-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.69 |
| March | 16805.44 | 10-MAR-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.08 |
| April | 24733.60 | 28-APR-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 |
| May | 24140.09 | 23-MAY-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.90 |
| June | 25222.79 | 13-JUN-14:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 0.00 |
| July | 16986.44 | 24-JUL-05:01 | 0.00 | 8921.19 | 9762.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.15 |
| August | 18579.80 | 20-AUG-15:40 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.56 |
| September | 26299.41 | 25-SEP-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.88 |
| October | 23438.34 | 03-OCT-14:02 | 131701.29 | 58223.87 | 56930.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.28 |
| November | 17406.97 | 10-NOV-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.67 |
| December | 12237.66 | 21-DEC-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.64 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 12237.66 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 26299.41 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 291.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1222.05 | 19-JAN-16:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1714.04 | 09-FEB-15:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 |
| March | 1749.84 | 31-MAR-14:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.28 |
| April | 3580.35 | 28-APR-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
| May | 3970.84 | 23-MAY-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 |
| June | 4677.48 | 13-JUN-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 0.00 |
| July | 2069.29 | 24-JUL-14:01 | 1302.08 | 3683.23 | 2501.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 |
| August | 2002.07 | 21-AUG-14:02 | 930.06 | 2630.88 | 1786.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 |
| September | 3679.49 | 27-SEP-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
| October | 2435.64 | 03-OCT-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 |
| November | 1881.87 | 10-NOV-15:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 |
| December | 1134.82 | 21-DEC-15:10 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.86 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1134.82 | 930.06 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4677.48 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 4.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2244.62 | 19-JAN-16:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3063.48 | 09-FEB-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.35 |
| March | 3139.11 | 30-MAR-14:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.63 |
| April | 4033.22 | 28-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.61 |
| May | 4302.87 | 23-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 |
| June | 5079.50 | 13-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 0.00 |
| July | 3238.22 | 24-JUL-14:01 | 3356.84 | 5221.57 | 4836.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.39 |
| August | 3353.74 | 20-AUG-15:40 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 |
| September | 3982.06 | 27-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 |
| October | 3615.11 | 03-OCT-14:01 | 27334.23 | 12084.20 | 11815.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.97 |
| November | 3322.09 | 10-NOV-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.52 |
| December | 2084.75 | 21-DEC-14:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2084.75 | 0.00 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5079.50 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 30.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 10973.29 | 19-JAN-15:40 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 15171.38 | 09-FEB-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.17 |
| March | 15848.54 | 30-MAR-14:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.41 |
| April | 17873.54 | 28-APR-14:02 | 87800.86 | 38815.92 | 37953.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.28 |
| May | 18249.74 | 25-MAY-14:05 | 117067.81 | 51754.55 | 50605.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.04 |
| June | 20484.52 | 13-JUN-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 | 0.00 |
| July | 15695.82 | 24-JUL-05:01 | 0.00 | 8921.19 | 9762.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.44 |
| August | 14695.60 | 20-AUG-15:40 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 5.93 | 0.00 |
| September | 17909.46 | 26-SEP-14:01 | 117067.81 | 51754.55 | 50605.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.86 |
| October | 17572.74 | 03-OCT-14:01 | 131701.29 | 58223.87 | 56930.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.39 |
| November | 16253.17 | 10-NOV-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.05 |
| December | 10653.78 | 22-DEC-14:10 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.96 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 10653.78 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 20484.52 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 | 268.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2566.61 | 19-JAN-15:40 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3480.58 | 09-FEB-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.08 |
| March | 3377.29 | 10-MAR-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.30 |
| April | 5603.72 | 28-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.61 |
| May | 5456.40 | 22-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 5923.20 | 13-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 0.00 |
| July | 3616.88 | 24-JUL-14:01 | 3356.84 | 5221.57 | 4836.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 |
| August | 4068.02 | 20-AUG-15:40 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 |
| September | 5770.32 | 25-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 |
| October | 4996.55 | 03-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.98 |
| November | 3611.64 | 10-NOV-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.13 |
| December | 2402.60 | 21-DEC-14:40 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2402.60 | 0.00 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5923.20 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 31.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 12499.91 | 20-JAN-15:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 17062.16 | 09-FEB-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.55 |
| March | 16730.30 | 10-MAR-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.92 |
| April | 24297.10 | 28-APR-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 |
| May | 23635.69 | 23-MAY-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.90 |
| June | 24672.58 | 13-JUN-14:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 0.00 |
| July | 16816.65 | 24-JUL-05:01 | 0.00 | 8921.19 | 9762.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.40 |
| August | 18250.88 | 20-AUG-15:40 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.95 |
| September | 25740.21 | 25-SEP-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.88 |
| October | 22962.98 | 03-OCT-14:02 | 131701.29 | 58223.87 | 56930.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.28 |
| November | 17390.83 | 10-NOV-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.66 |
| December | 11976.40 | 21-DEC-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.78 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 11976.40 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 25740.21 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 288.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1199.35 | 19-JAN-16:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1706.97 | 09-FEB-15:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.88 |
| March | 1743.47 | 31-MAR-14:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.28 |
| April | 3556.24 | 28-APR-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
| May | 3936.33 | 23-MAY-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 |
| June | 4635.94 | 13-JUN-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 0.00 |
| July | 2061.87 | 24-JUL-14:01 | 1302.08 | 3683.23 | 2501.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 |
| August | 1984.97 | 21-AUG-14:02 | 930.06 | 2630.88 | 1786.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 |
| September | 3654.04 | 27-SEP-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
| October | 2392.14 | 03-OCT-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 |
| November | 1873.34 | 10-NOV-15:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.08 |
| December | 1121.12 | 21-DEC-15:10 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.84 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1121.12 | 930.06 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4635.94 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 4.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2242.65 | 19-JAN-16:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3065.13 | 09-FEB-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.35 |
| March | 3141.29 | 30-MAR-14:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.63 |
| April | 4038.31 | 28-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.61 |
| May | 4308.60 | 23-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 |
| June | 5084.88 | 13-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 0.00 |
| July | 3238.44 | 24-JUL-14:01 | 3356.84 | 5221.57 | 4836.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 |
| August | 3353.14 | 20-AUG-15:40 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.13 |
| September | 3983.75 | 27-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 |
| October | 3615.71 | 03-OCT-14:01 | 27334.23 | 12084.20 | 11815.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.96 |
| November | 3322.96 | 10-NOV-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.51 |
| December | 2084.65 | 21-DEC-14:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2084.65 | 0.00 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5084.88 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 30.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 10952.50 | 19-JAN-15:40 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 15162.23 | 09-FEB-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.19 |
| March | 15841.18 | 30-MAR-14:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.45 |
| April | 17853.10 | 28-APR-14:02 | 87800.86 | 38815.92 | 37953.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 |
| May | 18196.73 | 25-MAY-14:05 | 117067.81 | 51754.55 | 50605.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.04 |
| June | 20512.31 | 13-JUN-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 | 0.00 |
| July | 15662.03 | 24-JUL-05:01 | 0.00 | 8921.19 | 9762.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.19 |
| August | 14669.18 | 20-AUG-15:40 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 6.02 | 0.00 |
| September | 17888.18 | 26-SEP-14:01 | 117067.81 | 51754.55 | 50605.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.87 |
| October | 17555.09 | 03-OCT-14:01 | 131701.29 | 58223.87 | 56930.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.41 |
| November | 16238.95 | 10-NOV-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.07 |
| December | 10641.59 | 22-DEC-14:10 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 10641.59 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 20512.31 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 | 268.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2591.54 | 19-JAN-15:40 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3490.42 | 09-FEB-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.11 |
| March | 3387.54 | 10-MAR-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.34 |
| April | 5634.27 | 28-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.61 |
| May | 5508.32 | 22-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 5948.60 | 13-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 0.00 |
| July | 3637.52 | 24-JUL-14:01 | 3356.84 | 5221.57 | 4836.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.43 |
| August | 4095.80 | 20-AUG-15:40 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.46 |
| September | 5802.92 | 25-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 |
| October | 5025.31 | 03-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.98 |
| November | 3615.09 | 10-NOV-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.14 |
| December | 2425.40 | 21-DEC-14:40 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.16 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2425.40 | 0.00 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5948.60 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 31.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 12673.09 | 20-JAN-15:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 17166.52 | 09-FEB-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.71 |
| March | 16847.64 | 10-MAR-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.13 |
| April | 24544.55 | 28-APR-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.84 |
| May | 23935.26 | 23-MAY-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.90 |
| June | 24894.48 | 13-JUN-14:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 0.00 |
| July | 17029.46 | 24-JUL-05:01 | 0.00 | 8921.19 | 9762.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.53 |
| August | 18455.76 | 20-AUG-15:40 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.89 |
| September | 26025.89 | 25-SEP-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.88 |
| October | 23191.26 | 03-OCT-14:02 | 131701.29 | 58223.87 | 56930.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.28 |
| November | 17431.19 | 10-NOV-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.68 |
| December | 12114.99 | 21-DEC-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.17 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 12114.99 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 26025.89 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 | 291.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1235.54 | 19-JAN-16:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1746.67 | 09-FEB-15:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.91 |
| March | 1794.71 | 31-MAR-14:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.32 |
| April | 3765.00 | 28-APR-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.99 |
| May | 4167.36 | 23-MAY-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.91 |
| June | 4811.42 | 13-JUN-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 0.00 |
| July | 2237.59 | 24-JUL-16:00 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 |
| August | 2040.72 | 21-AUG-14:02 | 930.06 | 2630.88 | 1786.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.13 |
| September | 3812.05 | 27-SEP-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
| October | 2574.37 | 03-OCT-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 |
| November | 1927.02 | 10-NOV-15:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.13 |
| December | 1152.67 | 21-DEC-15:10 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.87 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1152.67 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4811.42 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 4.50 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2254.27 | 19-JAN-16:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3081.23 | 09-FEB-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 |
| March | 3162.75 | 30-MAR-14:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.76 |
| April | 4138.92 | 28-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.61 |
| May | 4429.92 | 23-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 |
| June | 5198.51 | 13-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 0.00 |
| July | 3289.28 | 24-JUL-14:01 | 3356.84 | 5221.57 | 4836.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.88 |
| August | 3412.10 | 20-AUG-15:40 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 |
| September | 4048.30 | 27-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 |
| October | 3639.70 | 03-OCT-14:01 | 27334.23 | 12084.20 | 11815.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.15 |
| November | 3340.95 | 10-NOV-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.61 |
| December | 2094.73 | 21-DEC-14:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.06 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2094.73 | 0.00 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5198.51 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 8.07 | 30.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 7291.66 | 19-JAN-15:40 | 19327.23 | 8544.38 | 8354.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 10081.06 | 09-FEB-15:01 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.62 |
| March | 10552.56 | 30-MAR-14:01 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.26 |
| April | 11805.09 | 28-APR-14:02 | 57981.70 | 25633.15 | 25063.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.11 |
| May | 12340.03 | 23-MAY-14:03 | 67645.32 | 29905.34 | 29241.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.09 |
| June | 14085.38 | 13-JUN-15:00 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 | 0.00 |
| July | 10498.84 | 24-JUL-05:01 | 0.00 | 5891.35 | 6447.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.79 |
| August | 9897.21 | 20-AUG-15:40 | 0.00 | 8416.22 | 9210.03 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 0.00 |
| September | 11821.53 | 26-SEP-14:01 | 77308.93 | 34177.54 | 33418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.02 |
| October | 11652.26 | 03-OCT-14:01 | 86972.55 | 38449.73 | 37595.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.10 |
| November | 10818.67 | 10-NOV-15:01 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.65 |
| December | 7073.74 | 22-DEC-14:10 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.91 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 7073.74 | 0.00 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 14085.38 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 14.12 | 179.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 4087.12 | 27-JAN-15:20 | 34789.02 | 15379.89 | 20051.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.01 |
| February | 5531.53 | 09-FEB-15:01 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.59 |
| March | 5796.59 | 30-MAR-14:01 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.91 |
| April | 7076.19 | 28-APR-15:07 | 14909.58 | 6591.38 | 8593.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.97 |
| May | 7391.71 | 23-MAY-14:03 | 34789.02 | 15379.89 | 20051.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 |
| June | 8176.78 | 13-JUN-15:00 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 | 0.00 |
| July | 5784.04 | 24-JUL-14:01 | 18310.01 | 8544.38 | 10553.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.82 |
| August | 5555.36 | 18-AUG-14:02 | 15694.29 | 7323.76 | 9045.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.48 |
| September | 7322.23 | 13-SEP-14:50 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 |
| October | 6195.86 | 04-OCT-14:04 | 44728.74 | 19774.15 | 25780.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 |
| November | 5910.78 | 10-NOV-15:01 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 |
| December | 3976.07 | 22-DEC-14:10 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.31 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3976.07 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 8176.78 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 7.26 | 26.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2341.35 | 25-JAN-15:10 | 33502.32 | 26933.63 | 19308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.45 |
| February | 3511.75 | 09-FEB-15:01 | 33502.32 | 26933.63 | 19308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 |
| March | 3713.72 | 31-MAR-14:01 | 33502.32 | 26933.63 | 19308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.92 |
| April | 8797.77 | 28-APR-15:00 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 |
| May | 10410.16 | 23-MAY-14:50 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.55 |
| June | 13993.60 | 14-JUN-07:01 | 33502.32 | 26933.63 | 19308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 |
| July | 8605.55 | 24-JUL-15:50 | 528.98 | 1496.31 | 1016.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.61 |
| August | 6275.00 | 21-AUG-15:30 | 528.98 | 1496.31 | 1016.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.27 |
| September | 8479.95 | 27-SEP-14:40 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 |
| October | 5075.57 | 03-OCT-14:30 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.56 |
| November | 3823.83 | 10-NOV-15:01 | 33502.32 | 26933.63 | 19308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.98 |
| December | 2231.29 | 22-DEC-14:10 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.38 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2231.29 | 528.98 | 1496.31 | 1016.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | |
| Maximum of Months | 13993.60 | 33502.32 | 26933.63 | 19308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1366.39 | 24-JAN-18:07 | 994.03 | 6460.60 | 668.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 |
| February | 1366.77 | 08-FEB-18:07 | 994.03 | 6460.60 | 668.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.07 |
| March | 1372.08 | 09-MAR-18:07 | 994.03 | 6460.60 | 668.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.29 |
| April | 3094.54 | 30-APR-12:29 | 0.00 | 2969.72 | 1306.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.49 |
| May | 4957.43 | 22-MAY-15:00 | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.38 |
| June | 9742.10 | 13-JUN-15:00 | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 4906.77 | 0.00 |
| July | 9909.35 | 21-JUL-14:20 | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 7549.49 | 0.00 |
| August | 7196.21 | 14-AUG-15:00 | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 3585.28 | 0.00 |
| September | 4946.35 | 25-SEP-15:10 | 994.03 | 6460.60 | 1814.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 957.02 |
| October | 2510.45 | 01-OCT-12:52 | 0.00 | 2121.23 | 933.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.85 |
| November | 1386.33 | 01-NOV-17:07 | 994.03 | 6460.60 | 668.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1347.46 | 08-DEC-18:07 | 2319.41 | 15074.73 | 1559.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.20 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1347.46 | 0.00 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 9909.35 | 2319.41 | 15074.73 | 1814.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7549.49 | 957.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2336.65 | 27-JAN-15:20 | 3247.06 | 25633.15 | 15595.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3187.80 | 09-FEB-15:01 | 4638.66 | 36618.79 | 22279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 3360.84 | 31-MAR-14:01 | 4638.66 | 36618.79 | 22279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 12025.39 | 30-APR-12:29 | 0.00 | 5049.73 | 4813.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 9526.35 | 21-MAY-17:42 | 0.00 | 3606.95 | 3438.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 12259.91 | 12-JUN-20:13 | 0.00 | 5049.73 | 4813.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 10526.04 | 22-JUL-14:48 | 0.00 | 4328.34 | 2947.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 12114.26 | 20-AUG-15:40 | 0.00 | 7213.90 | 4912.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 10018.77 | 10-SEP-14:38 | 0.00 | 7213.90 | 6876.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 3901.92 | 03-OCT-14:01 | 4174.79 | 32956.91 | 20051.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 3417.81 | 10-NOV-15:01 | 4638.66 | 36618.79 | 22279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 2251.96 | 22-DEC-14:10 | 463.87 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2251.96 | 0.00 | 3606.95 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 12259.91 | 4638.66 | 36618.79 | 22279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1078.60 | 27-JAN-15:20 | 8161.15 | 11595.95 | 4703.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 |
| February | 1628.73 | 09-FEB-15:01 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.44 |
| March | 1751.72 | 31-MAR-14:01 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.11 |
| April | 2389.77 | 28-APR-14:02 | 6995.27 | 9939.39 | 4031.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.96 |
| May | 2512.16 | 23-MAY-14:01 | 8161.15 | 11595.95 | 4703.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 |
| June | 2982.29 | 13-JUN-15:00 | 1165.88 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 |
| July | 5098.24 | 22-JUL-16:10 | 0.00 | 1631.72 | 740.70 | 0.00 | 0.00 | 0.00 | 0.00 | 9.30 | 0.00 |
| August | 2200.64 | 20-AUG-15:40 | 0.00 | 3263.43 | 1481.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.61 |
| September | 2357.73 | 26-SEP-14:01 | 9327.02 | 13252.51 | 5375.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.87 |
| October | 2141.71 | 03-OCT-14:01 | 10492.90 | 14909.08 | 6047.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.07 |
| November | 1839.84 | 10-NOV-15:01 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.29 |
| December | 1002.95 | 22-DEC-14:10 | 1165.88 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.60 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1002.95 | 0.00 | 1631.72 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5098.24 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 9.30 | 14.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 12230.51 | 20-JAN-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 21188.28 | 09-FEB-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.57 |
| March | 21587.25 | 30-MAR-14:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.46 |
| April | 24405.69 | 30-APR-12:29 | 0.00 | 6480.49 | 9098.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.80 |
| May | 22437.75 | 25-MAY-14:01 | 21647.67 | 37595.29 | 33685.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.76 |
| June | 22410.61 | 09-JUN-14:01 | 18941.71 | 32895.88 | 29475.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.59 |
| July | 22001.25 | 24-JUL-14:01 | 9969.32 | 18275.49 | 15513.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.34 |
| August | 24562.79 | 20-AUG-15:40 | 0.00 | 9257.84 | 9283.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.59 |
| September | 24667.26 | 10-SEP-14:38 | 0.00 | 9257.84 | 12997.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.91 |
| October | 22129.28 | 03-OCT-14:01 | 24353.63 | 42294.70 | 37896.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.60 |
| November | 21718.79 | 10-NOV-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.77 |
| December | 4423.36 | 21-DEC-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.20 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4423.36 | 0.00 | 6480.49 | 9098.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 24667.26 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 7149.71 | 19-JAN-17:00 | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 8902.25 | 09-FEB-15:01 | 48430.23 | 42884.68 | 15780.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.39 |
| March | 9432.83 | 31-MAR-14:01 | 48430.23 | 42884.68 | 15780.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.10 |
| April | 23357.83 | 18-APR-06:01 | 0.00 | 42884.68 | 4871.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 24295.70 | 23-MAY-05:01 | 0.00 | 6758.63 | 3896.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.22 |
| June | 25611.01 | 27-JUN-05:01 | 0.00 | 6758.63 | 3896.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.17 |
| July | 26594.81 | 17-JUL-05:01 | 0.00 | 8448.28 | 3479.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.86 |
| August | 25260.17 | 07-AUG-05:01 | 0.00 | 8448.28 | 3479.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.64 |
| September | 24204.90 | 11-SEP-05:01 | 0.00 | 6758.63 | 3896.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 12418.12 | 11-OCT-15:07 | 39436.05 | 12865.40 | 4734.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.99 |
| November | 9416.44 | 10-NOV-15:01 | 48430.23 | 42884.68 | 15780.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.96 |
| December | 6734.29 | 22-DEC-17:00 | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.31 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 6734.29 | 0.00 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 26594.81 | 48430.23 | 42884.68 | 15780.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 72774.09 | 10-JAN-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 115.53 |
| February | 69139.89 | 17-FEB-06:11 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 28.57 |
| March | 64211.57 | 08-MAR-06:01 | 0.00 | 3462.67 | 23036.83 | 12982.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 61465.85 | 20-APR-05:11 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 55694.21 | 10-MAY-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 80.09 |
| June | 52689.03 | 08-JUN-05:11 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 93.51 |
| July | 50262.48 | 31-JUL-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 73.95 |
| August | 46362.09 | 24-AUG-05:11 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 43.43 |
| September | 51495.74 | 21-SEP-05:11 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 |
| October | 55600.68 | 06-OCT-05:11 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 |
| November | 65732.19 | 29-NOV-06:01 | 0.00 | 3462.67 | 23036.83 | 12982.94 | 0.00 | 0.00 | 0.00 | 0.00 | 15.35 |
| December | 64050.72 | 15-DEC-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 12.27 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 46362.09 | 0.00 | 3462.67 | 23036.83 | 12982.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 72774.09 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 115.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 31095.99 | 31-JAN-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.12 |
| February | 35091.22 | 17-FEB-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 32063.41 | 21-MAR-07:01 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 46526.71 | 30-APR-14:02 | 0.00 | 2164.17 | 3199.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.76 |
| May | 29150.60 | 23-MAY-08:07 | 115963.40 | 8239.23 | 3599.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.07 |
| June | 51748.80 | 13-JUN-05:01 | 0.00 | 4328.34 | 6398.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.71 |
| July | 50419.75 | 24-JUL-05:01 | 0.00 | 3787.30 | 5598.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.93 |
| August | 44190.38 | 20-AUG-16:03 | 0.00 | 1623.13 | 2399.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 |
| September | 28396.53 | 12-SEP-08:06 | 193272.34 | 13732.05 | 5998.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.05 |
| October | 30260.08 | 12-OCT-07:01 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.54 |
| November | 33948.29 | 29-NOV-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.27 |
| December | 32111.07 | 08-DEC-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 28396.53 | 0.00 | 1623.13 | 2399.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 51748.80 | 193272.34 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.93 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 4883.51 | 27-JAN-15:35 | 9793.52 | 11982.48 | 10582.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.79 |
| February | 6627.16 | 09-FEB-15:01 | 48967.60 | 59912.39 | 52912.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.95 |
| March | 6896.41 | 30-MAR-14:02 | 48967.60 | 59912.39 | 52912.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.12 |
| April | 14188.73 | 28-APR-15:00 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.22 |
| May | 21983.89 | 23-MAY-07:01 | 48967.60 | 59912.39 | 52912.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.76 |
| June | 22599.32 | 13-JUN-07:02 | 24483.80 | 29956.19 | 26456.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 |
| July | 10616.23 | 23-JUL-11:45 | 0.00 | 4721.10 | 4666.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.86 |
| August | 8818.15 | 21-AUG-13:30 | 773.17 | 3328.47 | 2784.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.57 |
| September | 13866.80 | 25-SEP-14:20 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.24 |
| October | 10390.10 | 03-OCT-14:02 | 44070.84 | 53921.15 | 47621.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.04 |
| November | 7494.92 | 10-NOV-14:10 | 9793.52 | 11982.48 | 10582.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.16 |
| December | 4651.02 | 22-DEC-14:10 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.97 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4651.02 | 0.00 | 3328.47 | 2784.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.60 | |
| Maximum of Months | 22599.32 | 48967.60 | 59912.39 | 52912.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.86 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.253540E+12 | 186189.26 | 02-JAN-08:09 | 0.216976E+12 | 532733.68 | 10-JAN-08:09 |
| February | 0.227242E+12 | 182823.03 | 27-FEB-11:09 | 0.158108E+12 | 424475.40 | 17-FEB-08:09 |
| March | 0.261601E+12 | 182788.60 | 06-MAR-11:09 | 0.153687E+12 | 362380.99 | 13-MAR-07:10 |
| April | 0.244648E+12 | 244691.14 | 28-APR-13:00 | 0.666021E+11 | 253766.51 | 03-APR-07:10 |
| May | 0.264472E+12 | 278691.06 | 22-MAY-14:00 | 0.641978E+11 | 156986.65 | 17-MAY-07:10 |
| June | 0.274423E+12 | 307898.07 | 13-JUN-13:00 | 0.449273E+11 | 120470.64 | 07-JUN-09:00 |
| July | 0.191399E+12 | 179601.88 | 21-JUL-14:09 | 0.386477E+11 | 131043.71 | 05-JUL-07:10 |
| August | 0.205457E+12 | 166545.60 | 14-AUG-15:00 | 0.444810E+11 | 131009.07 | 24-AUG-07:10 |
| September | 0.257514E+12 | 262535.55 | 27-SEP-13:00 | 0.424765E+11 | 124690.02 | 20-SEP-07:10 |
| October | 0.252123E+12 | 206201.69 | 05-OCT-13:20 | 0.732193E+11 | 267964.64 | 23-OCT-07:10 |
| November | 0.247384E+12 | 190538.73 | 24-NOV-11:00 | 0.133127E+12 | 392964.36 | 29-NOV-08:09 |
| December | 0.247188E+12 | 185155.68 | 27-DEC-08:09 | 0.196311E+12 | 456112.90 | 26-DEC-08:09 |
| Annual Sum or Average | 0.292699E+13 | 0.123276E+13 | ||||
| Minimum of Months | 0.191399E+12 | 166545.60 | 0.386477E+11 | 120470.64 | ||
| Maximum of Months | 0.274423E+12 | 307898.07 | 0.216976E+12 | 532733.68 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 0.109593E+12 | 0.101099E+11 | 0.102892E+12 | 0.158194E+10 | 0.252724E+11 | 0.211708E+09 | 0.00 | 31395749.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.990914E+11 | 0.831934E+10 | 0.929862E+11 | 0.142979E+10 | 0.217649E+11 | 0.138043E+09 | 0.00 | 31440720.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.116033E+12 | 0.809640E+10 | 0.106107E+12 | 0.164017E+10 | 0.257197E+11 | 0.128073E+09 | 0.00 | 41905990.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.105019E+12 | 0.670926E+10 | 0.990538E+11 | 0.152152E+10 | 0.257861E+11 | 40848964.94 | 0.00 | 0.282947E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.112813E+12 | 0.594491E+10 | 0.104499E+12 | 0.161106E+10 | 0.304110E+11 | 36905370.17 | 0.00 | 0.533478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.111459E+12 | 0.522657E+10 | 0.102249E+12 | 0.157960E+10 | 0.339012E+11 | 25277340.61 | 0.00 | 0.162740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.666242E+11 | 0.563351E+10 | 0.693246E+11 | 0.102075E+10 | 0.257819E+11 | 25780778.44 | 0.00 | 0.192314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.703211E+11 | 0.649340E+10 | 0.716606E+11 | 0.104481E+10 | 0.278339E+11 | 34403649.46 | 0.00 | 0.243143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.103032E+12 | 0.734621E+10 | 0.977493E+11 | 0.149702E+10 | 0.285261E+11 | 23656839.41 | 0.00 | 0.156366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.109593E+12 | 0.874751E+10 | 0.102892E+12 | 0.158194E+10 | 0.246267E+11 | 50588010.07 | 0.00 | 0.802810E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.108239E+12 | 0.947647E+10 | 0.100662E+12 | 0.155064E+10 | 0.235673E+11 | 0.112278E+09 | 0.00 | 63504981.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.106374E+12 | 0.103824E+11 | 0.101284E+12 | 0.155283E+10 | 0.235163E+11 | 0.190037E+09 | 0.00 | 29612912.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.121819E+13 | 0.924858E+11 | 0.115136E+13 | 0.176121E+11 | 0.316707E+12 | 0.101760E+10 | 0.00 | 0.846213E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.666242E+11 | 0.522657E+10 | 0.693246E+11 | 0.102075E+10 | 0.217649E+11 | 23656839.41 | 0.00 | 29612912.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.116033E+12 | 0.103824E+11 | 0.106107E+12 | 0.164017E+10 | 0.339012E+11 | 0.211708E+09 | 0.00 | 0.243143E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.303281E+11 | 0.00 | 0.170035E+12 | 0.00 | 0.166129E+11 | 0.00 | 0.00 |
| February | 0.274200E+11 | 0.00 | 0.115609E+12 | 0.00 | 0.150790E+11 | 0.00 | 0.00 |
| March | 0.319900E+11 | 0.00 | 0.103691E+12 | 0.00 | 0.180060E+11 | 0.00 | 0.00 |
| April | 0.290818E+11 | 0.00 | 0.220094E+11 | 0.00 | 0.155109E+11 | 0.00 | 0.00 |
| May | 0.311591E+11 | 0.00 | 0.163983E+11 | 0.00 | 0.166404E+11 | 0.00 | 0.00 |
| June | 0.307436E+11 | 0.00 | 0.355703E+10 | 0.00 | 0.106266E+11 | 0.00 | 0.00 |
| July | 0.294972E+11 | 0.00 | 0.452514E+10 | 0.00 | 0.462530E+10 | 0.00 | 0.00 |
| August | 0.319900E+11 | 0.00 | 0.737620E+10 | 0.00 | 0.511481E+10 | 0.00 | 0.00 |
| September | 0.290818E+11 | 0.00 | 0.375155E+10 | 0.00 | 0.964320E+10 | 0.00 | 0.00 |
| October | 0.303281E+11 | 0.00 | 0.272157E+11 | 0.00 | 0.156755E+11 | 0.00 | 0.00 |
| November | 0.299127E+11 | 0.00 | 0.872292E+11 | 0.00 | 0.159848E+11 | 0.00 | 0.00 |
| December | 0.294972E+11 | 0.00 | 0.151150E+12 | 0.00 | 0.156640E+11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.361030E+12 | 0.00 | 0.712547E+12 | 0.00 | 0.159184E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.274200E+11 | 0.00 | 0.355703E+10 | 0.00 | 0.462530E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.319900E+11 | 0.00 | 0.170035E+12 | 0.00 | 0.180060E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 79557.27 | 02-JAN-07:10 | 5897.73 | 01-JAN-00:10 | 76813.98 | 02-JAN-10:09 | 1336.02 | 02-JAN-10:09 | 25344.02 | 02-JAN-07:30 | 730.25 | 02-JAN-07:30 | 0.00 | 01-JAN-00:10 |
| February | 79557.27 | 01-FEB-07:10 | 5897.73 | 01-FEB-00:10 | 76813.98 | 01-FEB-10:09 | 1336.02 | 01-FEB-10:09 | 24317.80 | 21-FEB-07:19 | 618.89 | 21-FEB-07:19 | 0.00 | 01-FEB-00:10 |
| March | 79557.27 | 01-MAR-07:10 | 5897.73 | 01-MAR-00:10 | 76813.98 | 01-MAR-10:09 | 1336.02 | 01-MAR-10:09 | 24207.53 | 06-MAR-07:19 | 602.53 | 06-MAR-07:19 | 0.00 | 01-MAR-00:10 |
| April | 79557.27 | 03-APR-06:10 | 5897.73 | 01-APR-00:10 | 76813.98 | 03-APR-09:09 | 1336.02 | 03-APR-09:09 | 46572.55 | 28-APR-14:30 | 253.57 | 03-APR-06:19 | 0.00 | 01-APR-00:10 |
| May | 79557.27 | 01-MAY-06:10 | 5897.73 | 01-MAY-00:10 | 76813.98 | 01-MAY-09:09 | 1336.02 | 01-MAY-09:09 | 49008.29 | 23-MAY-14:30 | 139.11 | 05-MAY-07:10 | 0.00 | 01-MAY-00:10 |
| June | 79557.27 | 01-JUN-06:10 | 5897.73 | 01-JUN-00:10 | 76813.98 | 01-JUN-09:09 | 1336.02 | 01-JUN-09:09 | 49898.17 | 13-JUN-12:30 | 104.93 | 30-JUN-07:10 | 0.00 | 01-JUN-00:10 |
| July | 44198.48 | 03-JUL-07:10 | 5897.73 | 01-JUL-00:10 | 45977.32 | 03-JUL-09:09 | 606.14 | 03-JUL-09:09 | 27428.52 | 24-JUL-14:30 | 235.93 | 05-JUL-07:10 | 0.00 | 01-JUL-00:10 |
| August | 44198.48 | 01-AUG-07:10 | 5897.73 | 01-AUG-00:10 | 45977.32 | 01-AUG-09:09 | 606.14 | 01-AUG-09:09 | 26724.02 | 14-AUG-14:50 | 241.06 | 24-AUG-07:10 | 0.00 | 01-AUG-00:10 |
| September | 79557.27 | 05-SEP-06:10 | 5897.73 | 01-SEP-00:10 | 76813.98 | 05-SEP-09:09 | 1336.02 | 05-SEP-09:09 | 47244.06 | 27-SEP-14:30 | 207.36 | 01-SEP-07:10 | 0.00 | 01-SEP-00:10 |
| October | 79557.27 | 02-OCT-06:10 | 5897.73 | 01-OCT-00:10 | 76813.98 | 02-OCT-09:09 | 1336.02 | 02-OCT-09:09 | 35436.48 | 03-OCT-14:30 | 276.00 | 23-OCT-06:19 | 0.00 | 01-OCT-00:10 |
| November | 79557.27 | 01-NOV-06:10 | 5897.73 | 01-NOV-00:10 | 76813.98 | 01-NOV-09:09 | 1336.02 | 01-NOV-09:09 | 23830.10 | 20-NOV-07:10 | 562.79 | 20-NOV-07:10 | 0.00 | 01-NOV-00:10 |
| December | 79557.27 | 01-DEC-07:10 | 5897.73 | 01-DEC-00:10 | 76813.98 | 01-DEC-10:09 | 1336.02 | 01-DEC-10:09 | 25007.36 | 26-DEC-07:19 | 682.71 | 26-DEC-07:19 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | ||||||||||||||
| Minimum of Months | 44198.48 | 5897.73 | 45977.32 | 606.14 | 23830.10 | 104.93 | 0.00 | |||||||
| Maximum of Months | 79557.27 | 5897.73 | 76813.98 | 1336.02 | 49898.17 | 730.25 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 1278.93 | 27-JAN-06:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1280.33 | 10-FEB-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1337.59 | 17-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 45243.09 | 28-APR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 77693.26 | 22-MAY-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 110242.31 | 13-JUN-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 68714.14 | 21-JUL-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 55785.47 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 62821.05 | 13-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 19461.25 | 05-OCT-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 9429.60 | 24-NOV-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 796.60 | 06-DEC-06:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 796.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 110242.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 186189.26 | 02-JAN-08:09 | 79557.27 | 72814.64 | 5897.73 | 1213.82 | 24671.81 | 631.13 | 0.00 | 0.00 | 0.00 |
| February | 182823.03 | 27-FEB-11:09 | 79557.27 | 76813.98 | 0.00 | 1336.02 | 22112.22 | 135.80 | 0.00 | 0.00 | 0.00 |
| March | 182788.60 | 06-MAR-11:09 | 79557.27 | 76813.98 | 0.00 | 1336.02 | 22112.22 | 104.11 | 0.00 | 0.00 | 0.00 |
| April | 244691.14 | 28-APR-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 44472.61 | 13.47 | 0.00 | 45243.09 | 0.00 |
| May | 278691.06 | 22-MAY-14:00 | 79557.27 | 70814.97 | 0.00 | 1156.20 | 48078.70 | 13.47 | 0.00 | 77693.26 | 0.00 |
| June | 307898.07 | 13-JUN-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 47154.33 | 13.47 | 0.00 | 105755.48 | 0.00 |
| July | 179601.88 | 21-JUL-14:09 | 44198.48 | 39978.30 | 0.00 | 518.12 | 24860.28 | 13.47 | 0.00 | 68714.14 | 0.00 |
| August | 166545.60 | 14-AUG-15:00 | 44198.48 | 39978.30 | 0.00 | 518.12 | 26010.37 | 13.47 | 0.00 | 54554.12 | 0.00 |
| September | 262535.55 | 27-SEP-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 46392.68 | 13.47 | 0.00 | 61166.44 | 0.00 |
| October | 206201.69 | 05-OCT-13:20 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 31773.82 | 13.47 | 0.00 | 19461.25 | 0.00 |
| November | 190538.73 | 24-NOV-11:00 | 79557.27 | 76813.98 | 0.00 | 1336.02 | 21831.92 | 25.54 | 0.00 | 9429.60 | 0.00 |
| December | 185155.68 | 27-DEC-08:09 | 79557.27 | 72814.64 | 5897.73 | 1213.82 | 23795.89 | 495.90 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | ||||||||||
| Minimum of Months | 166545.60 | 44198.48 | 39978.30 | 0.00 | 518.12 | 21831.92 | 13.47 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 307898.07 | 79557.27 | 76813.98 | 5897.73 | 1336.02 | 48078.70 | 631.13 | 0.00 | 105755.48 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
| January | 48084.96 | 02-JAN-10:09 | 0.00 | 484969.97 | 10-JAN-08:09 | 0.00 | 29784.92 | 26-JAN-13:00 | 0.00 |
| February | 48084.96 | 01-FEB-10:09 | 0.00 | 376200.54 | 17-FEB-08:09 | 0.00 | 29843.74 | 14-FEB-13:20 | 0.00 |
| March | 48084.96 | 01-MAR-10:09 | 0.00 | 314105.54 | 13-MAR-07:10 | 0.00 | 29793.76 | 03-MAR-13:50 | 0.00 |
| April | 48084.96 | 03-APR-09:09 | 0.00 | 205494.26 | 03-APR-07:10 | 0.00 | 29434.83 | 06-APR-12:00 | 0.00 |
| May | 48084.96 | 01-MAY-09:09 | 0.00 | 109500.51 | 17-MAY-07:10 | 0.00 | 28477.15 | 02-MAY-12:39 | 0.00 |
| June | 48084.96 | 01-JUN-09:09 | 0.00 | 51023.15 | 07-JUN-09:00 | 0.00 | 28205.92 | 02-JUN-12:39 | 0.00 |
| July | 48084.96 | 03-JUL-09:09 | 0.00 | 90793.46 | 05-JUL-07:10 | 0.00 | 9013.83 | 03-JUL-18:40 | 0.00 |
| August | 48084.96 | 01-AUG-09:09 | 0.00 | 90735.84 | 24-AUG-07:10 | 0.00 | 9005.00 | 31-AUG-18:40 | 0.00 |
| September | 48084.96 | 01-SEP-09:09 | 0.00 | 77257.69 | 20-SEP-07:10 | 0.00 | 27802.76 | 29-SEP-12:39 | 0.00 |
| October | 48084.96 | 02-OCT-09:09 | 0.00 | 220317.91 | 23-OCT-07:10 | 0.00 | 28207.45 | 31-OCT-12:30 | 0.00 |
| November | 48084.96 | 01-NOV-09:09 | 0.00 | 345458.25 | 29-NOV-08:09 | 0.00 | 28492.99 | 29-NOV-13:39 | 0.00 |
| December | 48084.96 | 01-DEC-10:09 | 0.00 | 408306.01 | 26-DEC-08:09 | 0.00 | 29513.75 | 29-DEC-13:00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 48084.96 | 0.00 | 51023.15 | 0.00 | 9005.00 | 0.00 | |||
| Maximum of Months | 48084.96 | 0.00 | 484969.97 | 0.00 | 29843.74 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.00 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
| February | 0.67 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
| March | 0.50 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
| December | 1.50 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
| Annual Sum or Average | 4.83 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 | 0.00 | 18.67 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.83 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.38 | 0.00 | 27.38 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.67 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
| Annual Sum or Average | 1.67 | 18.72 | 0.00 | 18.72 | 0.33 | 20.15 | 0.00 | 20.15 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.83 | 19.32 | 0.00 | 19.32 | 0.17 | 27.38 | 0.00 | 27.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 5.83 | 18.99 | 2.50 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
| February | 1.17 | 19.28 | 0.17 | 19.42 | 0.00 | 19.42 | 0.00 | 19.42 |
| March | 0.33 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.33 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
| December | 3.67 | 19.30 | 1.00 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
| Annual Sum or Average | 11.33 | 19.13 | 3.67 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 5.83 | 19.38 | 2.50 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 3.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
| February | 1.83 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
| March | 0.83 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.50 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
| December | 3.33 | 17.84 | 0.00 | 17.84 | 0.00 | 17.84 | 0.00 | 17.84 |
| Annual Sum or Average | 9.50 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 | 0.00 | 18.33 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3.33 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.00 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
| February | 0.67 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
| March | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
| December | 1.17 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
| Annual Sum or Average | 4.17 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.00 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 |
| February | 0.67 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
| March | 0.50 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
| December | 1.50 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
| Annual Sum or Average | 4.83 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 1.00 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 |
| February | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
| March | 0.17 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 | 0.00 | 19.35 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.67 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
| Annual Sum or Average | 2.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 6.50 | 19.02 | 2.83 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
| February | 1.17 | 19.26 | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
| March | 0.33 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.33 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
| December | 3.67 | 19.28 | 1.00 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
| Annual Sum or Average | 12.00 | 19.14 | 4.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 6.50 | 19.36 | 2.83 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 3.33 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 |
| February | 2.00 | 18.62 | 0.00 | 18.62 | 0.00 | 18.62 | 0.00 | 18.62 |
| March | 0.83 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.50 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 | 0.00 | 18.51 |
| December | 3.50 | 17.92 | 0.00 | 17.92 | 0.00 | 17.92 | 0.00 | 17.92 |
| Annual Sum or Average | 10.17 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3.50 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.17 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 | 0.00 | 18.55 |
| February | 0.67 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
| March | 0.17 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
| December | 1.17 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
| Annual Sum or Average | 4.33 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2.17 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.00 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
| February | 0.67 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
| March | 0.33 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 | 0.00 | 19.13 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.17 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
| December | 1.50 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 | 0.00 | 18.87 |
| Annual Sum or Average | 4.67 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 1.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 27.27 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.67 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
| Annual Sum or Average | 1.83 | 18.76 | 0.00 | 18.76 | 0.17 | 19.47 | 0.00 | 19.47 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1.00 | 19.38 | 0.00 | 19.38 | 0.17 | 27.27 | 0.00 | 27.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 5.67 | 18.96 | 2.50 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
| February | 0.83 | 19.28 | 0.17 | 19.47 | 0.00 | 19.47 | 0.00 | 19.47 |
| March | 0.17 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 3.50 | 19.31 | 0.83 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
| Annual Sum or Average | 10.17 | 19.11 | 3.50 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 5.67 | 19.31 | 2.50 | 19.49 | 0.00 | 19.49 | 0.00 | 19.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 3.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 | 0.00 | 18.24 |
| February | 1.83 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
| March | 0.83 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 | 0.00 | 19.17 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.33 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
| December | 3.33 | 17.85 | 0.00 | 17.85 | 0.00 | 17.85 | 0.00 | 17.85 |
| Annual Sum or Average | 9.33 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3.33 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.00 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
| February | 0.67 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 | 0.00 | 19.19 |
| March | 0.17 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
| December | 1.17 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
| Annual Sum or Average | 4.17 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 | 0.00 | 18.85 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 1.67 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
| February | 0.17 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.50 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
| Annual Sum or Average | 2.33 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1.67 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 6.50 | 18.94 | 3.33 | 19.22 | 0.00 | 19.22 | 0.00 | 19.22 |
| February | 0.67 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
| December | 2.17 | 19.10 | 0.17 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
| Annual Sum or Average | 9.50 | 18.99 | 3.50 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 6.50 | 19.40 | 3.33 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 185.17 | 16.37 | 162.33 | 16.81 | 0.00 | 16.81 | 0.00 | 16.81 |
| February | 147.00 | 17.08 | 128.00 | 17.59 | 0.00 | 17.59 | 0.00 | 17.59 |
| March | 151.50 | 16.92 | 128.50 | 17.46 | 0.00 | 17.46 | 0.00 | 17.46 |
| April | 54.17 | 16.03 | 34.17 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
| May | 50.33 | 16.45 | 29.67 | 16.98 | 0.00 | 16.98 | 0.00 | 16.98 |
| June | 34.50 | 17.80 | 18.00 | 18.16 | 0.17 | 18.18 | 0.17 | 18.20 |
| July | 22.00 | 18.07 | 7.83 | 18.48 | 1.00 | 18.68 | 1.00 | 18.87 |
| August | 23.83 | 18.11 | 5.83 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
| September | 30.50 | 17.24 | 13.00 | 17.86 | 0.00 | 17.86 | 0.00 | 17.86 |
| October | 60.67 | 16.45 | 40.33 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
| November | 115.83 | 16.69 | 95.00 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
| December | 182.67 | 16.87 | 162.50 | 17.30 | 0.00 | 17.30 | 0.00 | 17.30 |
| Annual Sum or Average | 1058.17 | 16.81 | 825.17 | 17.29 | 1.17 | 17.30 | 1.17 | 17.30 |
| Minimum of Months | 22.00 | 16.03 | 5.83 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
| Maximum of Months | 185.17 | 18.11 | 162.50 | 18.48 | 1.00 | 18.68 | 1.00 | 18.87 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.00 | 27.28 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.33 | 27.27 | 0.00 | 27.27 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.00 | 27.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.33 | 18.72 | 0.17 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
| February | 0.50 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
| March | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1.33 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
| Annual Sum or Average | 4.33 | 18.97 | 0.17 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2.33 | 19.39 | 0.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 3.67 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 | 0.00 | 19.56 |
| February | 0.67 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
| March | 0.17 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 | 0.00 | 20.44 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.30 | 0.00 | 27.30 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.27 | 0.00 | 27.27 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.41 | 0.00 | 27.41 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 2.17 | 19.89 | 0.00 | 19.89 | 0.00 | 19.89 | 0.00 | 19.89 |
| Annual Sum or Average | 6.67 | 19.77 | 0.00 | 19.77 | 1.33 | 21.02 | 0.00 | 21.02 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3.67 | 20.44 | 0.00 | 20.44 | 0.50 | 27.41 | 0.00 | 27.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 26.82 | 0.00 | 26.82 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 26.97 | 0.00 | 26.97 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 27.12 | 0.00 | 27.12 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 64.33 | 27.46 | 0.00 | 27.46 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 75.83 | 27.50 | 0.00 | 27.50 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 91.50 | 27.58 | 0.00 | 27.58 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 102.00 | 27.59 | 0.00 | 27.59 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 90.00 | 27.54 | 0.00 | 27.54 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 91.17 | 27.52 | 0.00 | 27.52 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 49.67 | 27.34 | 0.00 | 27.34 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 24.50 | 27.10 | 0.00 | 27.10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.81 | 0.00 | 26.81 |
| Annual Sum or Average | 0.00 | 0.00 | 663.17 | 27.44 | 0.00 | 27.44 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 | 26.81 | 0.00 | 26.81 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 102.00 | 27.59 | 0.00 | 27.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.00 | 19.89 | 0.00 | 19.89 | 0.00 | 19.89 | 0.00 | 19.89 |
| February | 0.83 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 | 0.00 | 20.24 |
| March | 0.67 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 27.27 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.33 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 | 0.00 | 20.35 |
| December | 1.17 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 | 0.00 | 20.15 |
| Annual Sum or Average | 5.00 | 20.10 | 0.00 | 20.10 | 0.17 | 20.33 | 0.00 | 20.33 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2.00 | 20.35 | 0.00 | 20.35 | 0.17 | 27.27 | 0.00 | 27.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 1.83 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 | 0.00 | 18.47 |
| February | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.67 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
| Annual Sum or Average | 2.67 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 | 0.00 | 18.72 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1.83 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.39 | 139.83 | 21.26 | 139.83 | 21.20 |
| February | 247.00 | 21.56 | 87.17 | 21.42 | 87.17 | 21.33 |
| March | 299.00 | 21.55 | 89.67 | 21.42 | 89.67 | 21.35 |
| April | 178.83 | 22.60 | 20.50 | 22.71 | 2.17 | 22.70 |
| May | 169.17 | 22.68 | 59.83 | 23.02 | 0.00 | 23.02 |
| June | 129.17 | 22.66 | 102.17 | 23.24 | 0.00 | 23.24 |
| July | 193.33 | 21.98 | 24.00 | 22.18 | 0.00 | 22.18 |
| August | 231.83 | 21.91 | 24.00 | 22.09 | 0.00 | 22.09 |
| September | 110.17 | 22.55 | 103.50 | 23.25 | 0.00 | 23.25 |
| October | 222.83 | 22.18 | 21.33 | 22.32 | 2.00 | 22.31 |
| November | 269.50 | 21.69 | 44.00 | 21.59 | 44.00 | 21.52 |
| December | 260.00 | 21.26 | 161.00 | 21.16 | 161.00 | 21.12 |
| Annual Sum or Average | 2583.83 | 21.88 | 877.00 | 21.96 | 525.83 | 21.84 |
| Minimum of Months | 110.17 | 21.26 | 20.50 | 21.16 | 0.00 | 21.12 |
| Maximum of Months | 299.00 | 22.68 | 161.00 | 23.25 | 161.00 | 23.25 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.69 | 84.00 | 21.53 | 84.00 | 21.44 |
| February | 247.00 | 21.91 | 22.50 | 21.84 | 22.50 | 21.78 |
| March | 299.00 | 21.94 | 24.00 | 21.87 | 24.00 | 21.82 |
| April | 155.50 | 22.75 | 26.17 | 22.93 | 0.00 | 22.93 |
| May | 144.67 | 22.84 | 71.67 | 23.22 | 0.00 | 23.22 |
| June | 122.33 | 22.75 | 99.83 | 23.30 | 0.00 | 23.30 |
| July | 235.00 | 21.97 | 4.17 | 22.00 | 0.00 | 22.00 |
| August | 259.50 | 21.93 | 10.33 | 21.99 | 0.00 | 21.99 |
| September | 91.83 | 22.64 | 115.67 | 23.38 | 0.00 | 23.38 |
| October | 205.50 | 22.49 | 27.00 | 22.66 | 0.00 | 22.66 |
| November | 265.00 | 22.04 | 15.67 | 21.98 | 15.67 | 21.93 |
| December | 260.00 | 21.57 | 83.17 | 21.44 | 83.17 | 21.36 |
| Annual Sum or Average | 2558.33 | 22.09 | 584.17 | 22.23 | 229.33 | 22.15 |
| Minimum of Months | 91.83 | 21.57 | 4.17 | 21.44 | 0.00 | 21.36 |
| Maximum of Months | 299.00 | 22.84 | 115.67 | 23.38 | 84.00 | 23.38 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.08 | 134.17 | 21.04 | 134.17 | 21.03 |
| February | 247.00 | 21.16 | 66.50 | 21.12 | 66.50 | 21.10 |
| March | 299.00 | 21.33 | 60.17 | 21.28 | 60.17 | 21.23 |
| April | 235.50 | 22.94 | 0.83 | 22.93 | 0.83 | 22.93 |
| May | 193.17 | 23.23 | 14.83 | 23.28 | 0.00 | 23.28 |
| June | 113.00 | 23.39 | 38.50 | 23.55 | 0.00 | 23.55 |
| July | 243.33 | 22.70 | 2.50 | 22.71 | 0.00 | 22.71 |
| August | 293.67 | 22.49 | 0.00 | 22.49 | 0.00 | 22.49 |
| September | 138.33 | 23.09 | 10.33 | 23.16 | 0.00 | 23.16 |
| October | 261.17 | 22.35 | 1.17 | 22.35 | 1.17 | 22.34 |
| November | 273.00 | 21.40 | 44.17 | 21.34 | 44.17 | 21.30 |
| December | 260.00 | 21.03 | 145.50 | 21.02 | 145.50 | 21.01 |
| Annual Sum or Average | 2830.17 | 22.04 | 518.67 | 21.93 | 452.50 | 21.82 |
| Minimum of Months | 113.00 | 21.03 | 0.00 | 21.02 | 0.00 | 21.01 |
| Maximum of Months | 299.00 | 23.39 | 145.50 | 23.55 | 145.50 | 23.55 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.14 | 189.00 | 21.08 | 189.00 | 21.06 |
| February | 247.00 | 21.19 | 146.83 | 21.12 | 146.83 | 21.09 |
| March | 299.00 | 21.34 | 127.50 | 21.24 | 127.50 | 21.19 |
| April | 244.33 | 22.37 | 8.83 | 22.34 | 7.50 | 22.30 |
| May | 217.50 | 22.57 | 33.00 | 22.75 | 0.00 | 22.75 |
| June | 173.17 | 22.61 | 58.83 | 22.96 | 0.00 | 22.96 |
| July | 255.67 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
| August | 299.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
| September | 190.17 | 22.23 | 14.83 | 22.35 | 0.00 | 22.35 |
| October | 271.33 | 21.99 | 7.50 | 21.96 | 7.50 | 21.94 |
| November | 273.00 | 21.40 | 88.33 | 21.30 | 88.33 | 21.25 |
| December | 260.00 | 21.08 | 205.50 | 21.05 | 205.50 | 21.03 |
| Annual Sum or Average | 3003.17 | 21.69 | 880.17 | 21.62 | 772.17 | 21.52 |
| Minimum of Months | 173.17 | 21.08 | 0.00 | 21.05 | 0.00 | 21.03 |
| Maximum of Months | 299.00 | 22.61 | 205.50 | 22.96 | 205.50 | 22.96 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.33 | 134.33 | 21.23 | 134.33 | 21.18 |
| February | 247.00 | 21.45 | 77.17 | 21.35 | 77.17 | 21.28 |
| March | 299.00 | 21.70 | 46.33 | 21.61 | 46.33 | 21.55 |
| April | 240.17 | 22.61 | 0.83 | 22.61 | 0.33 | 22.61 |
| May | 212.17 | 22.78 | 29.67 | 22.93 | 0.00 | 22.93 |
| June | 178.83 | 22.68 | 49.50 | 22.95 | 0.00 | 22.95 |
| July | 260.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
| August | 299.00 | 21.24 | 0.00 | 21.24 | 0.00 | 21.24 |
| September | 199.50 | 22.32 | 15.17 | 22.43 | 0.00 | 22.43 |
| October | 270.17 | 22.31 | 0.67 | 22.31 | 0.67 | 22.31 |
| November | 273.00 | 21.72 | 37.17 | 21.64 | 37.17 | 21.58 |
| December | 260.00 | 21.31 | 130.00 | 21.21 | 130.00 | 21.17 |
| Annual Sum or Average | 3011.83 | 21.85 | 520.83 | 21.81 | 426.00 | 21.72 |
| Minimum of Months | 178.83 | 21.24 | 0.00 | 21.21 | 0.00 | 21.17 |
| Maximum of Months | 299.00 | 22.78 | 134.33 | 22.95 | 134.33 | 22.95 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.35 | 145.83 | 21.23 | 145.83 | 21.17 |
| February | 247.00 | 21.55 | 88.33 | 21.40 | 88.33 | 21.32 |
| March | 299.00 | 21.53 | 92.17 | 21.41 | 92.17 | 21.34 |
| April | 183.17 | 22.59 | 18.83 | 22.69 | 2.17 | 22.67 |
| May | 172.33 | 22.65 | 55.50 | 22.98 | 0.00 | 22.98 |
| June | 136.50 | 22.64 | 97.67 | 23.20 | 0.00 | 23.20 |
| July | 203.83 | 21.96 | 18.67 | 22.11 | 0.00 | 22.11 |
| August | 241.83 | 21.90 | 20.00 | 22.04 | 0.00 | 22.04 |
| September | 113.83 | 22.54 | 102.17 | 23.22 | 0.00 | 23.22 |
| October | 223.67 | 22.18 | 20.33 | 22.30 | 2.17 | 22.29 |
| November | 270.33 | 21.67 | 46.33 | 21.57 | 46.33 | 21.50 |
| December | 260.00 | 21.22 | 167.00 | 21.14 | 167.00 | 21.10 |
| Annual Sum or Average | 2624.50 | 21.87 | 872.83 | 21.93 | 544.00 | 21.81 |
| Minimum of Months | 113.83 | 21.22 | 18.67 | 21.14 | 0.00 | 21.10 |
| Maximum of Months | 299.00 | 22.65 | 167.00 | 23.22 | 167.00 | 23.22 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.62 | 88.50 | 21.47 | 88.50 | 21.39 |
| February | 247.00 | 21.89 | 22.83 | 21.82 | 22.83 | 21.76 |
| March | 299.00 | 21.94 | 21.83 | 21.88 | 21.83 | 21.83 |
| April | 159.67 | 22.75 | 23.83 | 22.91 | 0.00 | 22.91 |
| May | 148.33 | 22.84 | 66.50 | 23.20 | 0.00 | 23.20 |
| June | 128.67 | 22.75 | 94.00 | 23.26 | 0.00 | 23.26 |
| July | 245.00 | 21.93 | 3.67 | 21.95 | 0.00 | 21.95 |
| August | 268.33 | 21.89 | 4.50 | 21.91 | 0.00 | 21.91 |
| September | 96.50 | 22.63 | 111.83 | 23.35 | 0.00 | 23.35 |
| October | 208.67 | 22.50 | 24.00 | 22.66 | 0.00 | 22.66 |
| November | 267.33 | 22.03 | 17.00 | 21.97 | 17.00 | 21.92 |
| December | 260.00 | 21.53 | 86.00 | 21.41 | 86.00 | 21.33 |
| Annual Sum or Average | 2601.50 | 22.07 | 564.50 | 22.19 | 236.17 | 22.11 |
| Minimum of Months | 96.50 | 21.53 | 3.67 | 21.41 | 0.00 | 21.33 |
| Maximum of Months | 299.00 | 22.84 | 111.83 | 23.35 | 88.50 | 23.35 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.07 | 136.33 | 21.03 | 136.33 | 21.02 |
| February | 247.00 | 21.15 | 68.83 | 21.12 | 68.83 | 21.09 |
| March | 299.00 | 21.33 | 59.00 | 21.28 | 59.00 | 21.24 |
| April | 235.83 | 22.93 | 0.83 | 22.92 | 0.83 | 22.91 |
| May | 194.50 | 23.23 | 14.33 | 23.28 | 0.00 | 23.28 |
| June | 115.50 | 23.39 | 37.67 | 23.54 | 0.00 | 23.54 |
| July | 248.50 | 22.68 | 1.67 | 22.69 | 0.00 | 22.69 |
| August | 295.33 | 22.46 | 0.00 | 22.46 | 0.00 | 22.46 |
| September | 140.50 | 23.08 | 8.50 | 23.13 | 0.00 | 23.13 |
| October | 261.83 | 22.35 | 1.17 | 22.35 | 1.17 | 22.34 |
| November | 273.00 | 21.39 | 45.67 | 21.33 | 45.67 | 21.29 |
| December | 260.00 | 21.03 | 149.17 | 21.01 | 149.17 | 21.00 |
| Annual Sum or Average | 2844.00 | 22.03 | 523.17 | 21.92 | 461.00 | 21.81 |
| Minimum of Months | 115.50 | 21.03 | 0.00 | 21.01 | 0.00 | 21.00 |
| Maximum of Months | 299.00 | 23.39 | 149.17 | 23.54 | 149.17 | 23.54 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.13 | 190.00 | 21.08 | 190.00 | 21.06 |
| February | 247.00 | 21.19 | 146.67 | 21.12 | 146.67 | 21.09 |
| March | 299.00 | 21.34 | 127.50 | 21.25 | 127.50 | 21.19 |
| April | 244.33 | 22.37 | 8.83 | 22.34 | 7.50 | 22.30 |
| May | 217.50 | 22.57 | 33.17 | 22.75 | 0.00 | 22.75 |
| June | 172.83 | 22.61 | 58.83 | 22.96 | 0.00 | 22.96 |
| July | 255.67 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
| August | 299.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
| September | 190.17 | 22.22 | 14.50 | 22.34 | 0.00 | 22.34 |
| October | 271.33 | 21.99 | 7.50 | 21.96 | 7.50 | 21.94 |
| November | 273.00 | 21.40 | 88.33 | 21.30 | 88.33 | 21.24 |
| December | 260.00 | 21.08 | 205.67 | 21.05 | 205.67 | 21.03 |
| Annual Sum or Average | 3002.83 | 21.69 | 881.00 | 21.62 | 773.17 | 21.52 |
| Minimum of Months | 172.83 | 21.08 | 0.00 | 21.05 | 0.00 | 21.03 |
| Maximum of Months | 299.00 | 22.61 | 205.67 | 22.96 | 205.67 | 22.96 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.33 | 134.83 | 21.23 | 134.83 | 21.18 |
| February | 247.00 | 21.45 | 77.33 | 21.35 | 77.33 | 21.29 |
| March | 299.00 | 21.71 | 46.17 | 21.62 | 46.17 | 21.55 |
| April | 239.17 | 22.61 | 0.83 | 22.61 | 0.33 | 22.61 |
| May | 211.17 | 22.79 | 30.00 | 22.94 | 0.00 | 22.94 |
| June | 178.17 | 22.69 | 50.50 | 22.96 | 0.00 | 22.96 |
| July | 260.00 | 21.44 | 0.00 | 21.44 | 0.00 | 21.44 |
| August | 299.00 | 21.24 | 0.00 | 21.24 | 0.00 | 21.24 |
| September | 199.00 | 22.31 | 15.50 | 22.44 | 0.00 | 22.44 |
| October | 270.00 | 22.31 | 0.67 | 22.31 | 0.67 | 22.31 |
| November | 273.00 | 21.72 | 37.33 | 21.64 | 37.33 | 21.58 |
| December | 260.00 | 21.31 | 130.33 | 21.21 | 130.33 | 21.17 |
| Annual Sum or Average | 3008.50 | 21.85 | 523.50 | 21.81 | 427.00 | 21.72 |
| Minimum of Months | 178.17 | 21.24 | 0.00 | 21.21 | 0.00 | 21.17 |
| Maximum of Months | 299.00 | 22.79 | 134.83 | 22.96 | 134.83 | 22.96 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.36 | 143.00 | 21.24 | 143.00 | 21.18 |
| February | 247.00 | 21.56 | 86.17 | 21.42 | 86.17 | 21.33 |
| March | 299.00 | 21.55 | 88.83 | 21.43 | 88.83 | 21.35 |
| April | 181.33 | 22.62 | 19.33 | 22.72 | 1.83 | 22.71 |
| May | 170.67 | 22.67 | 57.33 | 23.01 | 0.00 | 23.01 |
| June | 132.33 | 22.65 | 99.33 | 23.22 | 0.00 | 23.22 |
| July | 197.00 | 21.97 | 21.00 | 22.14 | 0.00 | 22.14 |
| August | 236.83 | 21.91 | 21.50 | 22.07 | 0.00 | 22.07 |
| September | 110.83 | 22.56 | 103.17 | 23.25 | 0.00 | 23.25 |
| October | 223.00 | 22.20 | 20.83 | 22.34 | 1.83 | 22.33 |
| November | 269.67 | 21.69 | 43.50 | 21.60 | 43.50 | 21.53 |
| December | 260.00 | 21.24 | 164.83 | 21.15 | 164.83 | 21.11 |
| Annual Sum or Average | 2600.67 | 21.88 | 868.83 | 21.95 | 530.00 | 21.83 |
| Minimum of Months | 110.83 | 21.24 | 19.33 | 21.15 | 0.00 | 21.11 |
| Maximum of Months | 299.00 | 22.67 | 164.83 | 23.25 | 164.83 | 23.25 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.65 | 85.83 | 21.50 | 85.83 | 21.41 |
| February | 247.00 | 21.92 | 19.83 | 21.86 | 19.83 | 21.80 |
| March | 299.00 | 21.98 | 19.33 | 21.92 | 19.33 | 21.88 |
| April | 153.67 | 22.78 | 26.33 | 22.96 | 0.00 | 22.96 |
| May | 143.17 | 22.86 | 71.67 | 23.24 | 0.00 | 23.24 |
| June | 122.33 | 22.76 | 98.00 | 23.30 | 0.00 | 23.30 |
| July | 239.33 | 21.97 | 4.17 | 22.00 | 0.00 | 22.00 |
| August | 263.00 | 21.92 | 7.33 | 21.97 | 0.00 | 21.97 |
| September | 90.17 | 22.65 | 115.67 | 23.39 | 0.00 | 23.39 |
| October | 201.33 | 22.52 | 25.50 | 22.69 | 0.00 | 22.69 |
| November | 264.17 | 22.06 | 15.00 | 22.00 | 15.00 | 21.95 |
| December | 260.00 | 21.56 | 82.00 | 21.43 | 82.00 | 21.36 |
| Annual Sum or Average | 2556.17 | 22.10 | 570.67 | 22.23 | 222.00 | 22.15 |
| Minimum of Months | 90.17 | 21.56 | 4.17 | 21.43 | 0.00 | 21.36 |
| Maximum of Months | 299.00 | 22.86 | 115.67 | 23.39 | 85.83 | 23.39 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.09 | 130.67 | 21.05 | 130.67 | 21.03 |
| February | 247.00 | 21.20 | 56.83 | 21.16 | 56.83 | 21.13 |
| March | 299.00 | 21.43 | 48.00 | 21.37 | 48.00 | 21.32 |
| April | 227.33 | 23.06 | 0.67 | 23.06 | 0.67 | 23.05 |
| May | 181.67 | 23.34 | 20.17 | 23.40 | 0.00 | 23.40 |
| June | 88.00 | 23.47 | 42.33 | 23.64 | 0.00 | 23.64 |
| July | 229.83 | 22.83 | 4.50 | 22.85 | 0.00 | 22.85 |
| August | 284.83 | 22.61 | 0.00 | 22.61 | 0.00 | 22.61 |
| September | 125.17 | 23.21 | 20.33 | 23.32 | 0.00 | 23.32 |
| October | 257.67 | 22.50 | 0.67 | 22.49 | 0.67 | 22.49 |
| November | 273.00 | 21.50 | 37.50 | 21.44 | 37.50 | 21.39 |
| December | 260.00 | 21.04 | 136.50 | 21.02 | 136.50 | 21.01 |
| Annual Sum or Average | 2746.50 | 22.09 | 498.17 | 22.00 | 410.83 | 21.89 |
| Minimum of Months | 88.00 | 21.04 | 0.00 | 21.02 | 0.00 | 21.01 |
| Maximum of Months | 299.00 | 23.47 | 136.50 | 23.64 | 136.50 | 23.64 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.14 | 186.67 | 21.08 | 186.67 | 21.06 |
| February | 247.00 | 21.20 | 143.50 | 21.13 | 143.50 | 21.10 |
| March | 299.00 | 21.37 | 121.33 | 21.27 | 121.33 | 21.21 |
| April | 240.17 | 22.43 | 7.50 | 22.41 | 5.67 | 22.38 |
| May | 209.67 | 22.61 | 37.33 | 22.82 | 0.00 | 22.82 |
| June | 161.83 | 22.66 | 69.17 | 23.05 | 0.00 | 23.05 |
| July | 253.17 | 21.81 | 0.00 | 21.81 | 0.00 | 21.81 |
| August | 298.83 | 21.51 | 0.00 | 21.51 | 0.00 | 21.51 |
| September | 184.33 | 22.26 | 21.17 | 22.43 | 0.00 | 22.43 |
| October | 270.83 | 22.02 | 6.83 | 22.00 | 6.83 | 21.98 |
| November | 273.00 | 21.41 | 86.33 | 21.32 | 86.33 | 21.26 |
| December | 260.00 | 21.08 | 203.83 | 21.05 | 203.83 | 21.04 |
| Annual Sum or Average | 2970.83 | 21.72 | 883.67 | 21.66 | 754.17 | 21.55 |
| Minimum of Months | 161.83 | 21.08 | 0.00 | 21.05 | 0.00 | 21.04 |
| Maximum of Months | 299.00 | 22.66 | 203.83 | 23.05 | 203.83 | 23.05 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.34 | 132.67 | 21.24 | 132.67 | 21.19 |
| February | 247.00 | 21.48 | 73.33 | 21.37 | 73.33 | 21.31 |
| March | 299.00 | 21.75 | 40.17 | 21.67 | 40.17 | 21.60 |
| April | 226.67 | 22.65 | 1.33 | 22.66 | 0.17 | 22.66 |
| May | 193.50 | 22.83 | 34.67 | 23.00 | 0.00 | 23.00 |
| June | 154.33 | 22.76 | 64.33 | 23.10 | 0.00 | 23.10 |
| July | 260.00 | 21.59 | 0.00 | 21.59 | 0.00 | 21.59 |
| August | 299.00 | 21.33 | 0.00 | 21.33 | 0.00 | 21.33 |
| September | 185.00 | 22.36 | 19.00 | 22.51 | 0.00 | 22.51 |
| October | 264.33 | 22.34 | 0.50 | 22.34 | 0.50 | 22.34 |
| November | 273.00 | 21.76 | 35.33 | 21.67 | 35.33 | 21.61 |
| December | 260.00 | 21.31 | 127.50 | 21.22 | 127.50 | 21.17 |
| Annual Sum or Average | 2934.83 | 21.88 | 528.83 | 21.85 | 409.67 | 21.76 |
| Minimum of Months | 154.33 | 21.31 | 0.00 | 21.22 | 0.00 | 21.17 |
| Maximum of Months | 299.00 | 22.83 | 132.67 | 23.10 | 132.67 | 23.10 |
Report: ComfortReportSimple55Monthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.88 | 80.50 | 21.71 | 80.50 | 21.60 |
| February | 247.00 | 22.19 | 13.67 | 22.13 | 13.67 | 22.08 |
| March | 299.00 | 22.69 | 5.33 | 22.66 | 5.33 | 22.64 |
| April | 147.00 | 23.45 | 8.33 | 23.48 | 0.00 | 23.48 |
| May | 66.67 | 23.49 | 68.00 | 23.75 | 0.00 | 23.75 |
| June | 10.50 | 23.34 | 223.17 | 23.97 | 0.00 | 23.97 |
| July | 202.17 | 22.62 | 7.00 | 22.65 | 0.00 | 22.65 |
| August | 282.00 | 22.43 | 0.00 | 22.43 | 0.00 | 22.43 |
| September | 41.33 | 23.04 | 121.50 | 23.76 | 0.00 | 23.76 |
| October | 197.50 | 23.20 | 1.17 | 23.20 | 0.00 | 23.20 |
| November | 271.00 | 22.65 | 6.50 | 22.61 | 6.50 | 22.58 |
| December | 260.00 | 21.88 | 44.17 | 21.77 | 44.17 | 21.69 |
| Annual Sum or Average | 2297.17 | 22.53 | 579.33 | 22.67 | 150.17 | 22.60 |
| Minimum of Months | 10.50 | 21.88 | 0.00 | 21.71 | 0.00 | 21.60 |
| Maximum of Months | 299.00 | 23.49 | 223.17 | 23.97 | 80.50 | 23.97 |
Report: ComfortReportSimple55Monthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.03 | 168.33 | 21.00 | 168.33 | 20.99 |
| February | 247.00 | 21.11 | 105.00 | 21.07 | 105.00 | 21.05 |
| March | 299.00 | 21.37 | 69.67 | 21.30 | 69.67 | 21.25 |
| April | 216.83 | 23.25 | 0.17 | 23.25 | 0.17 | 23.24 |
| May | 132.83 | 23.71 | 37.50 | 23.78 | 0.00 | 23.78 |
| June | 19.17 | 23.87 | 91.33 | 23.98 | 0.00 | 23.98 |
| July | 81.00 | 23.36 | 57.50 | 23.62 | 0.00 | 23.62 |
| August | 170.17 | 23.27 | 17.33 | 23.34 | 0.00 | 23.34 |
| September | 108.00 | 23.55 | 28.50 | 23.64 | 0.00 | 23.64 |
| October | 263.83 | 22.47 | 0.67 | 22.46 | 0.67 | 22.46 |
| November | 273.00 | 21.31 | 63.50 | 21.25 | 63.50 | 21.21 |
| December | 260.00 | 21.01 | 195.83 | 21.00 | 195.83 | 21.00 |
| Annual Sum or Average | 2343.83 | 22.01 | 835.33 | 21.96 | 603.17 | 21.81 |
| Minimum of Months | 19.17 | 21.01 | 0.17 | 21.00 | 0.00 | 20.99 |
| Maximum of Months | 299.00 | 23.87 | 195.83 | 23.98 | 195.83 | 23.98 |
Report: ComfortReportSimple55Monthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 18.78 | 246.50 | 18.67 | 246.50 | 18.63 |
| February | 247.00 | 19.50 | 218.00 | 19.41 | 218.00 | 19.37 |
| March | 299.00 | 19.72 | 267.50 | 19.65 | 267.50 | 19.62 |
| April | 257.50 | 20.86 | 44.83 | 20.55 | 44.83 | 20.32 |
| May | 268.17 | 21.02 | 36.17 | 20.81 | 27.67 | 20.57 |
| June | 240.50 | 21.49 | 38.83 | 21.72 | 5.83 | 21.64 |
| July | 236.50 | 21.68 | 11.83 | 21.74 | 2.33 | 21.71 |
| August | 264.83 | 21.77 | 13.50 | 21.85 | 1.67 | 21.84 |
| September | 195.50 | 21.75 | 35.67 | 21.99 | 4.83 | 21.93 |
| October | 273.00 | 20.74 | 42.50 | 20.45 | 42.50 | 20.23 |
| November | 273.00 | 19.88 | 170.00 | 19.62 | 170.00 | 19.51 |
| December | 260.00 | 18.96 | 256.33 | 18.95 | 256.33 | 18.94 |
| Annual Sum or Average | 3088.00 | 20.46 | 1381.67 | 20.13 | 1288.00 | 19.88 |
| Minimum of Months | 195.50 | 18.78 | 11.83 | 18.67 | 1.67 | 18.63 |
| Maximum of Months | 299.00 | 21.77 | 267.50 | 21.99 | 267.50 | 21.93 |
Report: ComfortReportSimple55Monthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 22.19 | 58.00 | 21.92 | 58.00 | 21.73 |
| February | 247.00 | 22.91 | 1.83 | 22.89 | 1.83 | 22.88 |
| March | 290.50 | 23.49 | 0.17 | 23.49 | 0.17 | 23.49 |
| April | 24.67 | 24.20 | 175.33 | 25.89 | 0.00 | 25.89 |
| May | 3.67 | 26.70 | 282.50 | 26.27 | 3.67 | 26.28 |
| June | 25.00 | 26.70 | 286.00 | 26.58 | 25.00 | 26.59 |
| July | 0.67 | 23.94 | 248.00 | 25.41 | 0.00 | 25.41 |
| August | 2.33 | 23.82 | 261.67 | 25.12 | 0.00 | 25.12 |
| September | 0.33 | 23.73 | 255.33 | 26.24 | 0.00 | 26.24 |
| October | 95.67 | 23.90 | 105.33 | 24.78 | 0.00 | 24.78 |
| November | 257.83 | 23.29 | 0.33 | 23.29 | 0.33 | 23.29 |
| December | 260.00 | 22.33 | 16.00 | 22.25 | 16.00 | 22.18 |
| Annual Sum or Average | 1480.67 | 23.02 | 1690.50 | 24.45 | 105.00 | 24.38 |
| Minimum of Months | 0.33 | 22.19 | 0.17 | 21.92 | 0.00 | 21.73 |
| Maximum of Months | 290.50 | 26.70 | 286.00 | 26.58 | 58.00 | 26.59 |
Report: ComfortReportSimple55Monthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 19.55 | 229.17 | 19.42 | 229.17 | 19.37 |
| February | 247.00 | 20.36 | 183.17 | 20.23 | 183.17 | 20.18 |
| March | 299.00 | 21.17 | 106.33 | 20.96 | 106.33 | 20.84 |
| April | 170.17 | 23.16 | 33.50 | 23.49 | 0.67 | 23.48 |
| May | 90.00 | 23.62 | 123.83 | 24.73 | 0.00 | 24.73 |
| June | 17.00 | 26.01 | 257.83 | 25.58 | 12.83 | 25.63 |
| July | 57.00 | 23.34 | 150.33 | 24.43 | 0.00 | 24.43 |
| August | 123.67 | 23.27 | 85.33 | 23.81 | 0.00 | 23.81 |
| September | 59.33 | 23.49 | 137.83 | 24.66 | 0.00 | 24.66 |
| October | 252.83 | 22.52 | 2.17 | 22.50 | 2.17 | 22.49 |
| November | 273.00 | 21.07 | 92.50 | 20.82 | 92.50 | 20.68 |
| December | 260.00 | 19.70 | 250.83 | 19.68 | 250.83 | 19.67 |
| Annual Sum or Average | 2122.00 | 21.38 | 1652.83 | 21.82 | 877.67 | 21.45 |
| Minimum of Months | 17.00 | 19.55 | 2.17 | 19.42 | 0.00 | 19.37 |
| Maximum of Months | 299.00 | 26.01 | 257.83 | 25.58 | 250.83 | 25.63 |
Report: ComfortReportSimple55Monthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 231.00 | 21.28 | 128.50 | 21.18 | 128.50 | 21.14 |
| February | 209.00 | 21.48 | 72.50 | 21.36 | 72.50 | 21.29 |
| March | 253.00 | 21.76 | 58.83 | 21.62 | 58.83 | 21.52 |
| April | 132.00 | 23.42 | 8.33 | 23.46 | 0.00 | 23.46 |
| May | 91.50 | 23.61 | 46.17 | 23.74 | 0.00 | 23.74 |
| June | 9.67 | 23.83 | 134.83 | 23.99 | 0.00 | 23.99 |
| July | 35.50 | 23.30 | 116.33 | 23.84 | 0.00 | 23.84 |
| August | 61.33 | 23.23 | 107.33 | 23.72 | 0.00 | 23.72 |
| September | 24.50 | 23.65 | 99.33 | 23.93 | 0.00 | 23.93 |
| October | 191.50 | 22.85 | 1.00 | 22.85 | 0.33 | 22.85 |
| November | 231.00 | 21.84 | 41.33 | 21.71 | 41.33 | 21.62 |
| December | 220.00 | 21.15 | 156.50 | 21.09 | 156.50 | 21.07 |
| Annual Sum or Average | 1690.00 | 22.07 | 971.00 | 22.26 | 458.00 | 22.08 |
| Minimum of Months | 9.67 | 21.15 | 1.00 | 21.09 | 0.00 | 21.07 |
| Maximum of Months | 253.00 | 23.83 | 156.50 | 23.99 | 156.50 | 23.99 |
Report: ComfortReportSimple55Monthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.60 | 73.83 | 21.48 | 73.83 | 21.40 |
| February | 247.00 | 21.91 | 5.83 | 21.89 | 5.83 | 21.87 |
| March | 299.00 | 22.37 | 0.83 | 22.36 | 0.83 | 22.36 |
| April | 67.50 | 23.15 | 55.33 | 23.53 | 0.00 | 23.53 |
| May | 26.50 | 23.23 | 166.17 | 23.89 | 0.00 | 23.89 |
| June | 2.33 | 23.32 | 263.00 | 23.99 | 0.00 | 23.99 |
| July | 13.00 | 23.00 | 206.67 | 23.90 | 0.00 | 23.90 |
| August | 50.83 | 22.90 | 175.67 | 23.72 | 0.00 | 23.72 |
| September | 19.67 | 23.08 | 201.50 | 23.91 | 0.00 | 23.91 |
| October | 187.83 | 22.71 | 5.33 | 22.74 | 0.00 | 22.74 |
| November | 273.00 | 22.12 | 6.50 | 22.10 | 6.50 | 22.07 |
| December | 260.00 | 21.51 | 40.50 | 21.44 | 40.50 | 21.39 |
| Annual Sum or Average | 1719.67 | 22.12 | 1201.17 | 22.76 | 127.50 | 22.69 |
| Minimum of Months | 2.33 | 21.51 | 0.83 | 21.44 | 0.00 | 21.39 |
| Maximum of Months | 299.00 | 23.32 | 263.00 | 23.99 | 73.83 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 18.50 | 23.97 | 184.83 | 23.99 | 1.50 | 23.99 |
| February | 0.00 | 0.00 | 175.00 | 23.99 | 0.00 | 23.99 |
| March | 0.00 | 0.00 | 211.17 | 23.99 | 0.00 | 23.99 |
| April | 0.33 | 24.00 | 248.17 | 23.99 | 0.33 | 23.99 |
| May | 0.00 | 0.00 | 284.50 | 23.99 | 0.00 | 23.99 |
| June | 1.00 | 24.00 | 286.00 | 24.00 | 1.00 | 24.00 |
| July | 0.00 | 0.00 | 259.67 | 24.00 | 0.00 | 24.00 |
| August | 0.50 | 24.00 | 298.33 | 24.00 | 0.50 | 24.00 |
| September | 0.17 | 23.99 | 259.17 | 24.00 | 0.17 | 24.00 |
| October | 0.00 | 0.00 | 257.83 | 23.99 | 0.00 | 23.99 |
| November | 0.67 | 23.57 | 219.50 | 23.99 | 0.00 | 23.99 |
| December | 8.00 | 23.53 | 163.67 | 23.97 | 0.00 | 23.97 |
| Annual Sum or Average | 29.17 | 23.84 | 2847.83 | 23.99 | 3.50 | 23.99 |
| Minimum of Months | 0.00 | 0.00 | 163.67 | 23.97 | 0.00 | 23.97 |
| Maximum of Months | 18.50 | 24.00 | 298.33 | 24.00 | 1.50 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 231.00 | 21.34 | 45.17 | 21.28 | 45.17 | 21.24 |
| February | 209.00 | 21.26 | 1.50 | 21.26 | 1.50 | 21.26 |
| March | 252.00 | 21.53 | 0.67 | 21.53 | 0.67 | 21.53 |
| April | 126.17 | 22.00 | 44.50 | 22.52 | 0.00 | 22.52 |
| May | 101.00 | 21.85 | 108.17 | 22.94 | 0.00 | 22.94 |
| June | 23.00 | 22.49 | 191.83 | 23.79 | 2.17 | 23.79 |
| July | 66.67 | 22.34 | 95.67 | 23.28 | 0.00 | 23.28 |
| August | 44.50 | 22.65 | 125.00 | 23.63 | 0.00 | 23.63 |
| September | 28.67 | 22.65 | 154.67 | 23.77 | 0.33 | 23.77 |
| October | 155.33 | 22.07 | 35.17 | 22.42 | 0.00 | 22.42 |
| November | 218.67 | 21.59 | 3.17 | 21.61 | 1.50 | 21.62 |
| December | 220.00 | 21.17 | 19.83 | 21.15 | 19.83 | 21.14 |
| Annual Sum or Average | 1676.00 | 21.63 | 825.33 | 22.32 | 71.17 | 22.29 |
| Minimum of Months | 23.00 | 21.17 | 0.67 | 21.15 | 0.00 | 21.14 |
| Maximum of Months | 252.00 | 22.65 | 191.83 | 23.79 | 45.17 | 23.79 |
Report: ComfortReportSimple55Monthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.74 | 110.67 | 21.55 | 110.67 | 21.44 |
| February | 247.00 | 22.12 | 36.33 | 21.99 | 36.33 | 21.88 |
| March | 299.00 | 22.80 | 6.50 | 22.77 | 6.50 | 22.74 |
| April | 130.17 | 23.76 | 9.83 | 23.78 | 0.00 | 23.78 |
| May | 49.00 | 23.85 | 69.33 | 23.94 | 0.00 | 23.94 |
| June | 1.17 | 23.95 | 204.83 | 24.00 | 0.00 | 24.00 |
| July | 37.83 | 23.30 | 126.50 | 23.84 | 0.00 | 23.84 |
| August | 89.00 | 23.21 | 94.33 | 23.62 | 0.00 | 23.62 |
| September | 22.00 | 23.61 | 114.50 | 23.94 | 0.00 | 23.94 |
| October | 194.00 | 23.47 | 0.00 | 23.47 | 0.00 | 23.47 |
| November | 273.00 | 22.75 | 19.17 | 22.64 | 19.17 | 22.54 |
| December | 260.00 | 21.69 | 91.67 | 21.53 | 91.67 | 21.44 |
| Annual Sum or Average | 1875.17 | 22.60 | 883.67 | 22.77 | 264.33 | 22.62 |
| Minimum of Months | 1.17 | 21.69 | 0.00 | 21.53 | 0.00 | 21.44 |
| Maximum of Months | 299.00 | 23.95 | 204.83 | 24.00 | 110.67 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.38884 | 36.63483 | -0.3182 | 8.04953 |
| February | 247.00000 | 21.56177 | 39.00086 | -0.2355 | 7.02296 |
| March | 299.00000 | 21.54523 | 36.50806 | -0.2446 | 6.89673 |
| April | 260.00000 | 23.02726 | 34.80059 | 0.21384 | 7.42166 |
| May | 286.00000 | 23.19926 | 41.52343 | -0.5244 | 13.16950 |
| June | 286.00000 | 23.32894 | 46.01328 | -0.3923 | 9.89980 |
| July | 260.00000 | 22.36532 | 48.59682 | -0.6655 | 16.40406 |
| August | 299.00000 | 22.26846 | 48.33925 | -0.7046 | 17.52983 |
| September | 260.00000 | 23.32647 | 44.12944 | -0.3856 | 10.22691 |
| October | 273.00000 | 22.51237 | 44.80818 | 0.12274 | 6.83737 |
| November | 273.00000 | 21.71741 | 42.70611 | -0.1544 | 6.49266 |
| December | 260.00000 | 21.26015 | 36.20636 | -0.3631 | 8.24087 |
| Annual Sum or Average | 3276.00000 | 22.29597 | 41.66710 | -0.3088 | 9.91116 |
| Minimum of Months | 247.00000 | 21.26015 | 34.80059 | -0.7046 | 6.49266 |
| Maximum of Months | 299.00000 | 23.32894 | 48.59682 | 0.21384 | 17.52983 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.68680 | 36.14973 | -0.2138 | 7.10311 |
| February | 247.00000 | 21.90768 | 38.41408 | -0.1218 | 6.26268 |
| March | 299.00000 | 21.93736 | 35.91271 | -0.1210 | 6.07269 |
| April | 260.00000 | 23.23725 | 34.35802 | 0.28849 | 7.79565 |
| May | 286.00000 | 23.37910 | 41.12588 | -0.4384 | 10.63627 |
| June | 286.00000 | 23.36792 | 45.91836 | -0.3645 | 8.94392 |
| July | 260.00000 | 22.08642 | 49.37435 | -0.7376 | 17.69802 |
| August | 299.00000 | 22.10810 | 48.76753 | -0.7377 | 17.91825 |
| September | 260.00000 | 23.43846 | 43.82387 | -0.3270 | 8.78963 |
| October | 273.00000 | 22.84552 | 44.00133 | 0.22736 | 7.33138 |
| November | 273.00000 | 22.09473 | 41.98340 | -0.0345 | 6.07881 |
| December | 260.00000 | 21.57198 | 35.72960 | -0.2532 | 7.01680 |
| Annual Sum or Average | 3276.00000 | 22.47451 | 41.36122 | -0.2411 | 9.35845 |
| Minimum of Months | 247.00000 | 21.57198 | 34.35802 | -0.7377 | 6.07269 |
| Maximum of Months | 299.00000 | 23.43846 | 49.37435 | 0.28849 | 17.91825 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.08105 | 35.53703 | -0.3645 | 8.16067 |
| February | 247.00000 | 21.15688 | 38.15975 | -0.3068 | 7.17766 |
| March | 299.00000 | 21.33291 | 35.29983 | -0.2640 | 6.74922 |
| April | 260.00000 | 23.03891 | 33.16505 | 0.16089 | 6.43414 |
| May | 286.00000 | 23.47807 | 39.09419 | -0.5224 | 11.70476 |
| June | 286.00000 | 23.75019 | 43.71312 | -0.3755 | 8.40385 |
| July | 260.00000 | 22.77053 | 47.03527 | -0.6792 | 15.59699 |
| August | 299.00000 | 22.51535 | 47.14805 | -0.7644 | 18.06711 |
| September | 260.00000 | 23.50984 | 42.76813 | -0.4741 | 10.64250 |
| October | 273.00000 | 22.42484 | 43.48426 | 0.07089 | 5.94644 |
| November | 273.00000 | 21.39837 | 41.62820 | -0.2091 | 6.39914 |
| December | 260.00000 | 21.03091 | 35.02005 | -0.3803 | 8.17151 |
| Annual Sum or Average | 3276.00000 | 22.29962 | 40.22423 | -0.3462 | 9.51220 |
| Minimum of Months | 247.00000 | 21.03091 | 33.16505 | -0.7644 | 5.94644 |
| Maximum of Months | 299.00000 | 23.75019 | 47.14805 | 0.16089 | 18.06711 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.13515 | 37.09858 | -0.4155 | 9.09308 |
| February | 247.00000 | 21.18976 | 39.67703 | -0.3609 | 8.03299 |
| March | 299.00000 | 21.34277 | 36.84786 | -0.3110 | 7.42379 |
| April | 260.00000 | 22.45994 | 36.17682 | 0.04266 | 6.21796 |
| May | 286.00000 | 22.88902 | 42.57446 | -0.6680 | 16.52313 |
| June | 286.00000 | 23.11151 | 46.83154 | -0.4919 | 11.64050 |
| July | 260.00000 | 21.74013 | 50.38028 | -0.8822 | 22.50108 |
| August | 299.00000 | 21.43857 | 50.69321 | -0.9996 | 26.78140 |
| September | 260.00000 | 22.65333 | 46.45008 | -0.6766 | 16.73863 |
| October | 273.00000 | 22.00250 | 46.20933 | -0.0336 | 5.91015 |
| November | 273.00000 | 21.39768 | 43.32597 | -0.2574 | 7.02598 |
| December | 260.00000 | 21.07931 | 36.51489 | -0.4318 | 9.11707 |
| Annual Sum or Average | 3276.00000 | 21.87494 | 42.79362 | -0.4616 | 12.35339 |
| Minimum of Months | 247.00000 | 21.07931 | 36.17682 | -0.9996 | 5.91015 |
| Maximum of Months | 299.00000 | 23.11151 | 50.69321 | 0.04266 | 26.78140 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.32912 | 36.73582 | -0.3353 | 8.01340 |
| February | 247.00000 | 21.45100 | 39.20978 | -0.2691 | 6.94026 |
| March | 299.00000 | 21.70192 | 36.27881 | -0.1948 | 6.32865 |
| April | 260.00000 | 22.70960 | 35.80899 | 0.12149 | 6.26046 |
| May | 286.00000 | 23.07928 | 42.24290 | -0.5820 | 13.58629 |
| June | 286.00000 | 23.09726 | 46.87717 | -0.4788 | 10.81791 |
| July | 260.00000 | 21.43884 | 51.25971 | -0.9631 | 25.01840 |
| August | 299.00000 | 21.23930 | 51.26495 | -1.0489 | 28.51075 |
| September | 260.00000 | 22.68475 | 46.40202 | -0.6455 | 15.39432 |
| October | 273.00000 | 22.32794 | 45.48792 | 0.06595 | 5.93136 |
| November | 273.00000 | 21.72440 | 42.67464 | -0.1506 | 6.22888 |
| December | 260.00000 | 21.30684 | 36.14077 | -0.3390 | 7.76939 |
| Annual Sum or Average | 3276.00000 | 22.01156 | 42.59615 | -0.4063 | 11.83556 |
| Minimum of Months | 247.00000 | 21.23930 | 35.80899 | -1.0489 | 5.93136 |
| Maximum of Months | 299.00000 | 23.09726 | 51.26495 | 0.12149 | 28.51075 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.34572 | 36.71771 | -0.3340 | 8.18298 |
| February | 247.00000 | 21.54585 | 39.03577 | -0.2406 | 7.04822 |
| March | 299.00000 | 21.53242 | 36.53561 | -0.2486 | 6.91785 |
| April | 260.00000 | 22.99535 | 34.89533 | 0.20331 | 7.33155 |
| May | 286.00000 | 23.16831 | 41.63017 | -0.5391 | 13.52031 |
| June | 286.00000 | 23.28974 | 46.14828 | -0.4098 | 10.23406 |
| July | 260.00000 | 22.28333 | 48.83040 | -0.6946 | 17.16195 |
| August | 299.00000 | 22.20009 | 48.53205 | -0.7289 | 18.17380 |
| September | 260.00000 | 23.30294 | 44.21195 | -0.3964 | 10.44329 |
| October | 273.00000 | 22.50205 | 44.84992 | 0.11897 | 6.79724 |
| November | 273.00000 | 21.69346 | 42.75651 | -0.1623 | 6.53128 |
| December | 260.00000 | 21.22392 | 36.27130 | -0.3766 | 8.39486 |
| Annual Sum or Average | 3276.00000 | 22.26100 | 41.76329 | -0.3220 | 10.12696 |
| Minimum of Months | 247.00000 | 21.22392 | 34.89533 | -0.7289 | 6.53128 |
| Maximum of Months | 299.00000 | 23.30294 | 48.83040 | 0.20331 | 18.17380 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.61727 | 36.27309 | -0.2365 | 7.19144 |
| February | 247.00000 | 21.89076 | 38.44714 | -0.1269 | 6.24866 |
| March | 299.00000 | 21.93897 | 35.91337 | -0.1203 | 6.04227 |
| April | 260.00000 | 23.21895 | 34.43426 | 0.28168 | 7.70439 |
| May | 286.00000 | 23.36601 | 41.19514 | -0.4461 | 10.74377 |
| June | 286.00000 | 23.33498 | 46.03426 | -0.3790 | 9.16186 |
| July | 260.00000 | 22.00123 | 49.61944 | -0.7673 | 18.54765 |
| August | 299.00000 | 22.02556 | 48.99967 | -0.7663 | 18.70343 |
| September | 260.00000 | 23.40958 | 43.92770 | -0.3408 | 8.99976 |
| October | 273.00000 | 22.84068 | 44.03640 | 0.22491 | 7.27057 |
| November | 273.00000 | 22.06631 | 42.04014 | -0.0431 | 6.06983 |
| December | 260.00000 | 21.52742 | 35.80132 | -0.2666 | 7.08942 |
| Annual Sum or Average | 3276.00000 | 22.43922 | 41.45849 | -0.2538 | 9.53886 |
| Minimum of Months | 247.00000 | 21.52742 | 34.43426 | -0.7673 | 6.04227 |
| Maximum of Months | 299.00000 | 23.40958 | 49.61944 | 0.28168 | 18.70343 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.06608 | 35.57779 | -0.3708 | 8.24218 |
| February | 247.00000 | 21.15345 | 38.17806 | -0.3080 | 7.19180 |
| March | 299.00000 | 21.33469 | 35.30740 | -0.2634 | 6.74268 |
| April | 260.00000 | 23.02822 | 33.20034 | 0.15813 | 6.41882 |
| May | 286.00000 | 23.47257 | 39.12346 | -0.5250 | 11.75918 |
| June | 286.00000 | 23.74282 | 43.74677 | -0.3791 | 8.46595 |
| July | 260.00000 | 22.73233 | 47.14439 | -0.6914 | 15.93440 |
| August | 299.00000 | 22.47645 | 47.25784 | -0.7767 | 18.44530 |
| September | 260.00000 | 23.49557 | 42.81703 | -0.4794 | 10.77480 |
| October | 273.00000 | 22.42168 | 43.50624 | 0.06991 | 5.93417 |
| November | 273.00000 | 21.38816 | 41.66055 | -0.2122 | 6.42423 |
| December | 260.00000 | 21.02531 | 35.03952 | -0.3832 | 8.21272 |
| Annual Sum or Average | 3276.00000 | 22.28704 | 40.26663 | -0.3506 | 9.60455 |
| Minimum of Months | 247.00000 | 21.02531 | 33.20034 | -0.7767 | 5.93417 |
| Maximum of Months | 299.00000 | 23.74282 | 47.25784 | 0.15813 | 18.44530 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.13307 | 37.10097 | -0.4166 | 9.10785 |
| February | 247.00000 | 21.18977 | 39.67494 | -0.3609 | 8.03400 |
| March | 299.00000 | 21.34395 | 36.84372 | -0.3106 | 7.41939 |
| April | 260.00000 | 22.46107 | 36.17248 | 0.04305 | 6.22106 |
| May | 286.00000 | 22.89086 | 42.56747 | -0.6671 | 16.49869 |
| June | 286.00000 | 23.11296 | 46.82557 | -0.4911 | 11.62578 |
| July | 260.00000 | 21.73886 | 50.38384 | -0.8825 | 22.51308 |
| August | 299.00000 | 21.43679 | 50.69796 | -1.0004 | 26.81010 |
| September | 260.00000 | 22.65135 | 46.45419 | -0.6772 | 16.76316 |
| October | 273.00000 | 22.00162 | 46.20902 | -0.0338 | 5.91002 |
| November | 273.00000 | 21.39610 | 43.32729 | -0.2580 | 7.03148 |
| December | 260.00000 | 21.07862 | 36.51406 | -0.4321 | 9.12308 |
| Annual Sum or Average | 3276.00000 | 21.87457 | 42.79287 | -0.4617 | 12.35757 |
| Minimum of Months | 247.00000 | 21.07862 | 36.17248 | -1.0004 | 5.91002 |
| Maximum of Months | 299.00000 | 23.11296 | 50.69796 | 0.04305 | 26.81010 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.32673 | 36.74713 | -0.3365 | 8.02665 |
| February | 247.00000 | 21.45283 | 39.21282 | -0.2688 | 6.93908 |
| March | 299.00000 | 21.70609 | 36.27855 | -0.1937 | 6.32341 |
| April | 260.00000 | 22.71457 | 35.80537 | 0.12257 | 6.26788 |
| May | 286.00000 | 23.08533 | 42.23235 | -0.5800 | 13.53471 |
| June | 286.00000 | 23.10314 | 46.86158 | -0.4769 | 10.77714 |
| July | 260.00000 | 21.44084 | 51.25527 | -0.9626 | 25.00055 |
| August | 299.00000 | 21.23962 | 51.26531 | -1.0492 | 28.52123 |
| September | 260.00000 | 22.68583 | 46.40073 | -0.6454 | 15.39820 |
| October | 273.00000 | 22.33090 | 45.48771 | 0.06649 | 5.93444 |
| November | 273.00000 | 21.72470 | 42.68045 | -0.1508 | 6.23205 |
| December | 260.00000 | 21.30700 | 36.14672 | -0.3392 | 7.77272 |
| Annual Sum or Average | 3276.00000 | 22.01387 | 42.59524 | -0.4059 | 11.82926 |
| Minimum of Months | 247.00000 | 21.23962 | 35.80537 | -1.0492 | 5.93444 |
| Maximum of Months | 299.00000 | 23.10314 | 51.26531 | 0.12257 | 28.52123 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.36402 | 36.68078 | -0.3271 | 8.12348 |
| February | 247.00000 | 21.55732 | 39.01108 | -0.2363 | 7.01721 |
| March | 299.00000 | 21.54835 | 36.50539 | -0.2429 | 6.87258 |
| April | 260.00000 | 23.02389 | 34.82489 | 0.21237 | 7.38173 |
| May | 286.00000 | 23.19017 | 41.56535 | -0.5294 | 13.25446 |
| June | 286.00000 | 23.31207 | 46.07635 | -0.4005 | 10.02780 |
| July | 260.00000 | 22.33212 | 48.69073 | -0.6769 | 16.66740 |
| August | 299.00000 | 22.24172 | 48.41369 | -0.7137 | 17.73963 |
| September | 260.00000 | 23.32782 | 44.13422 | -0.3860 | 10.20124 |
| October | 273.00000 | 22.52787 | 44.77922 | 0.12729 | 6.82736 |
| November | 273.00000 | 21.71909 | 42.69956 | -0.1536 | 6.49454 |
| December | 260.00000 | 21.23798 | 36.24446 | -0.3709 | 8.32670 |
| Annual Sum or Average | 3276.00000 | 22.28602 | 41.69724 | -0.3127 | 9.97425 |
| Minimum of Months | 247.00000 | 21.23798 | 34.82489 | -0.7137 | 6.49454 |
| Maximum of Months | 299.00000 | 23.32782 | 48.69073 | 0.21237 | 17.73963 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.65064 | 36.20465 | -0.2247 | 7.13256 |
| February | 247.00000 | 21.91802 | 38.38856 | -0.1174 | 6.22106 |
| March | 299.00000 | 21.97754 | 35.84096 | -0.1073 | 6.00483 |
| April | 260.00000 | 23.26059 | 34.31476 | 0.29563 | 7.82608 |
| May | 286.00000 | 23.39607 | 41.09316 | -0.4319 | 10.42661 |
| June | 286.00000 | 23.36939 | 45.92069 | -0.3646 | 8.88896 |
| July | 260.00000 | 22.06888 | 49.42246 | -0.7428 | 17.78448 |
| August | 299.00000 | 22.08622 | 48.82528 | -0.7443 | 18.03521 |
| September | 260.00000 | 23.44764 | 43.80575 | -0.3243 | 8.68414 |
| October | 273.00000 | 22.89160 | 43.89176 | 0.24074 | 7.38697 |
| November | 273.00000 | 22.11830 | 41.91818 | -0.0259 | 6.07698 |
| December | 260.00000 | 21.55647 | 35.74512 | -0.2563 | 7.00821 |
| Annual Sum or Average | 3276.00000 | 22.48132 | 41.34555 | -0.2385 | 9.34384 |
| Minimum of Months | 247.00000 | 21.55647 | 34.31476 | -0.7443 | 6.00483 |
| Maximum of Months | 299.00000 | 23.44764 | 49.42246 | 0.29563 | 18.03521 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.09231 | 35.49204 | -0.3595 | 8.11061 |
| February | 247.00000 | 21.19566 | 38.06056 | -0.2928 | 7.03285 |
| March | 299.00000 | 21.43220 | 35.09708 | -0.2365 | 6.51760 |
| April | 260.00000 | 23.18211 | 32.82575 | 0.19641 | 6.61157 |
| May | 286.00000 | 23.57790 | 38.78580 | -0.4859 | 10.77496 |
| June | 286.00000 | 23.82427 | 43.44130 | -0.3451 | 7.84039 |
| July | 260.00000 | 22.94905 | 46.53848 | -0.6226 | 14.00875 |
| August | 299.00000 | 22.67031 | 46.71336 | -0.7155 | 16.54760 |
| September | 260.00000 | 23.61107 | 42.43565 | -0.4361 | 9.75574 |
| October | 273.00000 | 22.58129 | 43.05494 | 0.10819 | 6.03048 |
| November | 273.00000 | 21.49955 | 41.37587 | -0.1823 | 6.25788 |
| December | 260.00000 | 21.04085 | 34.98255 | -0.3738 | 8.07753 |
| Annual Sum or Average | 3276.00000 | 22.39770 | 39.95165 | -0.3157 | 9.01235 |
| Minimum of Months | 247.00000 | 21.04085 | 32.82575 | -0.7155 | 6.03048 |
| Maximum of Months | 299.00000 | 23.82427 | 46.71336 | 0.19641 | 16.54760 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.13994 | 37.08471 | -0.4137 | 9.07399 |
| February | 247.00000 | 21.20245 | 39.64934 | -0.3560 | 7.97565 |
| March | 299.00000 | 21.36893 | 36.79995 | -0.3018 | 7.33276 |
| April | 260.00000 | 22.54175 | 36.02346 | 0.06593 | 6.29395 |
| May | 286.00000 | 22.96191 | 42.38150 | -0.6381 | 15.67081 |
| June | 286.00000 | 23.18919 | 46.58489 | -0.4609 | 10.94663 |
| July | 260.00000 | 21.84653 | 50.06713 | -0.8429 | 21.16356 |
| August | 299.00000 | 21.50830 | 50.48876 | -0.9726 | 25.74701 |
| September | 260.00000 | 22.71459 | 46.26252 | -0.6528 | 16.06793 |
| October | 273.00000 | 22.04033 | 46.11956 | -0.0221 | 5.92794 |
| November | 273.00000 | 21.41498 | 43.28515 | -0.2514 | 6.98608 |
| December | 260.00000 | 21.08214 | 36.50589 | -0.4306 | 9.10074 |
| Annual Sum or Average | 3276.00000 | 21.92281 | 42.66546 | -0.4440 | 11.95328 |
| Minimum of Months | 247.00000 | 21.08214 | 36.02346 | -0.9726 | 5.92794 |
| Maximum of Months | 299.00000 | 23.18919 | 50.48876 | 0.06593 | 25.74701 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.33988 | 36.71993 | -0.3306 | 7.97736 |
| February | 247.00000 | 21.47504 | 39.17138 | -0.2599 | 6.86731 |
| March | 299.00000 | 21.74965 | 36.20648 | -0.1784 | 6.24653 |
| April | 260.00000 | 22.81984 | 35.59335 | 0.15211 | 6.43695 |
| May | 286.00000 | 23.18048 | 41.96385 | -0.5425 | 12.58925 |
| June | 286.00000 | 23.22677 | 46.47187 | -0.4320 | 9.83656 |
| July | 260.00000 | 21.58533 | 50.82422 | -0.9119 | 23.06738 |
| August | 299.00000 | 21.32814 | 51.00095 | -1.0163 | 27.17805 |
| September | 260.00000 | 22.78037 | 46.10546 | -0.6115 | 14.44013 |
| October | 273.00000 | 22.39133 | 45.34930 | 0.08417 | 6.02188 |
| November | 273.00000 | 21.75583 | 42.61426 | -0.1394 | 6.20626 |
| December | 260.00000 | 21.31316 | 36.13522 | -0.3357 | 7.73701 |
| Annual Sum or Average | 3276.00000 | 22.08324 | 42.40925 | -0.3814 | 11.31173 |
| Minimum of Months | 247.00000 | 21.31316 | 35.59335 | -1.0163 | 6.02188 |
| Maximum of Months | 299.00000 | 23.22677 | 51.00095 | 0.15211 | 27.17805 |
Report: OccupantComfortDataSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.88364 | 37.88042 | -0.1899 | 6.82817 |
| February | 247.00000 | 22.18628 | 40.06096 | -0.0862 | 5.69942 |
| March | 299.00000 | 22.68993 | 36.90457 | 0.03716 | 5.60143 |
| April | 260.00000 | 23.68423 | 35.99617 | 0.35561 | 8.09479 |
| May | 286.00000 | 23.86731 | 42.19954 | -0.3164 | 7.55991 |
| June | 286.00000 | 23.96989 | 47.59798 | -0.1780 | 5.87175 |
| July | 260.00000 | 22.78524 | 50.18897 | -0.5595 | 12.22499 |
| August | 299.00000 | 22.47747 | 50.46220 | -0.6737 | 15.19083 |
| September | 260.00000 | 23.83034 | 46.73697 | -0.2759 | 7.21910 |
| October | 273.00000 | 23.41043 | 45.18702 | 0.31523 | 7.56123 |
| November | 273.00000 | 22.65882 | 42.95363 | 0.07057 | 5.97087 |
| December | 260.00000 | 21.88379 | 37.33004 | -0.1875 | 6.29749 |
| Annual Sum or Average | 3276.00000 | 22.95036 | 42.84772 | -0.1444 | 7.88214 |
| Minimum of Months | 247.00000 | 21.88364 | 35.99617 | -0.6737 | 5.60143 |
| Maximum of Months | 299.00000 | 23.96989 | 50.46220 | 0.35561 | 15.19083 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 22.18645 | 30.72476 | -0.1370 | 6.88101 |
| February | 247.00000 | 22.90806 | 32.13922 | 0.04388 | 5.45537 |
| March | 299.00000 | 23.52889 | 28.80956 | 0.17196 | 6.05459 |
| April | 260.00000 | 25.67413 | 26.45828 | 0.68725 | 15.72754 |
| May | 286.00000 | 26.24898 | 31.50811 | 0.26122 | 7.10782 |
| June | 286.00000 | 26.56877 | 36.11468 | 0.43547 | 9.22042 |
| July | 260.00000 | 25.36603 | 39.78653 | 0.10390 | 5.83469 |
| August | 299.00000 | 25.01682 | 40.10090 | -0.0133 | 5.53559 |
| September | 260.00000 | 26.20306 | 35.54023 | 0.28070 | 7.35772 |
| October | 273.00000 | 24.74149 | 35.79536 | 0.51966 | 11.39251 |
| November | 273.00000 | 23.36635 | 34.77528 | 0.17403 | 6.33341 |
| December | 260.00000 | 22.32727 | 30.09260 | -0.1082 | 5.73679 |
| Annual Sum or Average | 3276.00000 | 24.52930 | 33.52398 | 0.20148 | 7.69575 |
| Minimum of Months | 247.00000 | 22.18645 | 26.45828 | -0.1370 | 5.45537 |
| Maximum of Months | 299.00000 | 26.56877 | 40.10090 | 0.68725 | 15.72754 |
Report: OccupantComfortDataSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 19.55327 | 38.38930 | -0.6759 | 16.40870 |
| February | 247.00000 | 20.36213 | 39.98016 | -0.4763 | 10.34816 |
| March | 299.00000 | 21.16810 | 35.82521 | -0.3061 | 7.60122 |
| April | 260.00000 | 23.72684 | 32.46558 | 0.30038 | 8.16838 |
| May | 286.00000 | 24.64742 | 37.46143 | -0.1855 | 7.86041 |
| June | 286.00000 | 25.42862 | 40.43950 | 0.11554 | 6.51040 |
| July | 260.00000 | 24.34432 | 42.92662 | -0.1781 | 6.89491 |
| August | 299.00000 | 23.85984 | 43.62907 | -0.3364 | 8.19928 |
| September | 260.00000 | 24.55832 | 40.89650 | -0.1768 | 6.98692 |
| October | 273.00000 | 22.65919 | 43.23427 | 0.10578 | 6.14191 |
| November | 273.00000 | 21.06774 | 42.43735 | -0.2894 | 7.81059 |
| December | 260.00000 | 19.69899 | 37.67115 | -0.6456 | 14.40545 |
| Annual Sum or Average | 3276.00000 | 22.61766 | 39.62448 | -0.2279 | 8.90033 |
| Minimum of Months | 247.00000 | 19.55327 | 32.46558 | -0.6759 | 6.14191 |
| Maximum of Months | 299.00000 | 25.42862 | 43.62907 | 0.30038 | 16.40870 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 231.00000 | 21.27869 | 33.84874 | -0.3650 | 8.45326 |
| February | 209.00000 | 21.48483 | 36.25653 | -0.2718 | 7.08529 |
| March | 253.00000 | 21.76068 | 33.28882 | -0.2071 | 6.55664 |
| April | 220.00000 | 23.65414 | 30.57271 | 0.32194 | 7.74405 |
| May | 242.00000 | 23.85258 | 36.76839 | -0.3499 | 8.16722 |
| June | 242.00000 | 23.99146 | 42.68411 | -0.2015 | 6.08079 |
| July | 220.00000 | 23.85572 | 44.19147 | -0.2473 | 6.68288 |
| August | 253.00000 | 23.77606 | 43.90131 | -0.2884 | 7.26284 |
| September | 220.00000 | 23.95772 | 41.23421 | -0.2360 | 6.48398 |
| October | 231.00000 | 23.04477 | 40.52299 | 0.19700 | 6.73162 |
| November | 231.00000 | 21.84070 | 39.32441 | -0.1487 | 6.32374 |
| December | 220.00000 | 21.15401 | 33.55239 | -0.3961 | 8.54225 |
| Annual Sum or Average | 2772.00000 | 22.81748 | 38.05888 | -0.1845 | 7.16932 |
| Minimum of Months | 209.00000 | 21.15401 | 30.57271 | -0.3961 | 6.08079 |
| Maximum of Months | 253.00000 | 23.99146 | 44.19147 | 0.32194 | 8.54225 |
Report: OccupantComfortDataSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.59588 | 37.52895 | -0.2057 | 6.68581 |
| February | 247.00000 | 21.90915 | 39.69461 | -0.0860 | 5.58124 |
| March | 299.00000 | 22.36690 | 36.54949 | 0.02542 | 5.62715 |
| April | 260.00000 | 23.76513 | 34.33846 | 0.44845 | 9.59681 |
| May | 286.00000 | 23.89559 | 40.40508 | -0.1986 | 6.28455 |
| June | 286.00000 | 23.97953 | 46.06388 | -0.0803 | 5.35300 |
| July | 260.00000 | 23.84162 | 47.06504 | -0.1387 | 5.77927 |
| August | 299.00000 | 23.66556 | 47.21735 | -0.2234 | 6.68149 |
| September | 260.00000 | 23.90001 | 45.19302 | -0.1716 | 5.97958 |
| October | 273.00000 | 23.08663 | 45.02244 | 0.28770 | 7.40514 |
| November | 273.00000 | 22.12322 | 43.11781 | -0.0016 | 5.70775 |
| December | 260.00000 | 21.50970 | 37.07506 | -0.2239 | 6.45040 |
| Annual Sum or Average | 3276.00000 | 22.98223 | 41.64935 | -0.0490 | 6.41691 |
| Minimum of Months | 247.00000 | 21.50970 | 34.33846 | -0.2239 | 5.35300 |
| Maximum of Months | 299.00000 | 23.97953 | 47.21735 | 0.44845 | 9.59681 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 23.99023 | 46.81952 | 0.61150 | 13.12907 |
| February | 247.00000 | 23.99432 | 46.10881 | 0.63710 | 13.77196 |
| March | 299.00000 | 23.99406 | 42.36634 | 0.63503 | 13.68802 |
| April | 260.00000 | 23.99391 | 38.54738 | 0.70127 | 15.57514 |
| May | 286.00000 | 23.99471 | 44.36269 | 0.07106 | 5.53677 |
| June | 286.00000 | 23.99693 | 48.53220 | 0.13703 | 5.76888 |
| July | 260.00000 | 23.99846 | 50.14721 | 0.11979 | 5.65654 |
| August | 299.00000 | 23.99925 | 49.49439 | 0.09670 | 5.56171 |
| September | 260.00000 | 23.99845 | 47.07614 | 0.09548 | 5.58663 |
| October | 273.00000 | 23.99442 | 46.85991 | 0.70562 | 15.72074 |
| November | 273.00000 | 23.99323 | 47.45440 | 0.65774 | 14.33320 |
| December | 260.00000 | 23.97924 | 45.20520 | 0.60163 | 12.84380 |
| Annual Sum or Average | 3276.00000 | 23.99401 | 46.09477 | 0.41805 | 10.52865 |
| Minimum of Months | 247.00000 | 23.97924 | 38.54738 | 0.07106 | 5.53677 |
| Maximum of Months | 299.00000 | 23.99925 | 50.14721 | 0.70562 | 15.72074 |
Report: OccupantComfortDataSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 231.00000 | 21.33802 | 41.91672 | -0.1893 | 6.69704 |
| February | 209.00000 | 21.26396 | 44.56877 | -0.1452 | 5.85728 |
| March | 253.00000 | 21.53952 | 41.46052 | -0.0715 | 5.81902 |
| April | 220.00000 | 22.81802 | 40.49949 | 0.28889 | 8.13104 |
| May | 242.00000 | 23.02971 | 47.35824 | -0.4109 | 11.15075 |
| June | 242.00000 | 23.73324 | 51.43813 | -0.1219 | 6.11096 |
| July | 200.00000 | 23.34720 | 49.21847 | -0.3287 | 8.47579 |
| August | 230.00000 | 23.64899 | 48.46542 | -0.2832 | 7.35557 |
| September | 219.00000 | 23.74499 | 49.43396 | -0.1884 | 6.47662 |
| October | 231.00000 | 22.67906 | 50.21974 | 0.26296 | 7.78845 |
| November | 231.00000 | 21.71712 | 47.93533 | -0.0095 | 6.21314 |
| December | 220.00000 | 21.16794 | 41.37009 | -0.2144 | 6.28295 |
| Annual Sum or Average | 2728.00000 | 22.50025 | 46.15021 | -0.1167 | 7.19630 |
| Minimum of Months | 200.00000 | 21.16794 | 40.49949 | -0.4109 | 5.81902 |
| Maximum of Months | 253.00000 | 23.74499 | 51.43813 | 0.28889 | 11.15075 |
Report: OccupantComfortDataSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.74288 | 35.23993 | -0.2593 | 7.62185 |
| February | 247.00000 | 22.12198 | 37.29458 | -0.1350 | 6.19225 |
| March | 299.00000 | 22.80107 | 33.65640 | 0.02053 | 5.86563 |
| April | 260.00000 | 23.88105 | 31.26427 | 0.38374 | 8.34944 |
| May | 286.00000 | 23.97431 | 37.57049 | -0.2805 | 6.93326 |
| June | 286.00000 | 23.99938 | 42.75887 | -0.1642 | 5.72760 |
| July | 260.00000 | 23.86757 | 44.08775 | -0.2540 | 6.67063 |
| August | 299.00000 | 23.72616 | 44.01181 | -0.3263 | 7.71209 |
| September | 260.00000 | 23.96369 | 41.41363 | -0.2399 | 6.44877 |
| October | 273.00000 | 23.62375 | 40.76967 | 0.32369 | 7.64270 |
| November | 273.00000 | 22.74647 | 39.59790 | 0.04835 | 6.24671 |
| December | 260.00000 | 21.68664 | 34.78759 | -0.2665 | 7.13187 |
| Annual Sum or Average | 3276.00000 | 23.19135 | 38.57553 | -0.0974 | 6.87393 |
| Minimum of Months | 247.00000 | 21.68664 | 31.26427 | -0.3263 | 5.72760 |
| Maximum of Months | 299.00000 | 23.99938 | 44.08775 | 0.38374 | 8.34944 |
Report: OccupantComfortDataSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.02545 | 36.75246 | -0.4106 | 8.85594 |
| February | 247.00000 | 21.10557 | 39.42418 | -0.3406 | 7.56300 |
| March | 299.00000 | 21.37225 | 36.47313 | -0.2692 | 6.79032 |
| April | 260.00000 | 23.37238 | 33.35548 | 0.23279 | 6.85188 |
| May | 286.00000 | 23.86624 | 38.60343 | -0.3846 | 8.48275 |
| June | 286.00000 | 23.98877 | 43.05099 | -0.2564 | 6.51042 |
| July | 260.00000 | 23.77526 | 44.37272 | -0.3419 | 7.86646 |
| August | 299.00000 | 23.56099 | 44.49680 | -0.4334 | 9.39874 |
| September | 260.00000 | 23.80834 | 42.33193 | -0.3763 | 8.35617 |
| October | 273.00000 | 22.51910 | 44.44570 | 0.07766 | 5.96651 |
| November | 273.00000 | 21.30986 | 43.00616 | -0.2509 | 6.69735 |
| December | 260.00000 | 21.00850 | 36.23745 | -0.4107 | 8.62061 |
| Annual Sum or Average | 3276.00000 | 22.57346 | 40.24606 | -0.2656 | 7.66553 |
| Minimum of Months | 247.00000 | 21.00850 | 33.35548 | -0.4334 | 5.96651 |
| Maximum of Months | 299.00000 | 23.98877 | 44.49680 | 0.23279 | 9.39874 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 18.78247 | 36.54399 | -0.8538 | 23.87807 |
| February | 247.00000 | 19.50057 | 38.49160 | -0.6762 | 17.01376 |
| March | 299.00000 | 19.71945 | 34.91046 | -0.6434 | 15.91845 |
| April | 260.00000 | 20.88756 | 34.28680 | -0.2437 | 7.81223 |
| May | 286.00000 | 21.19404 | 42.09750 | -1.0987 | 32.60112 |
| June | 286.00000 | 21.86924 | 48.29364 | -0.8169 | 21.87354 |
| July | 260.00000 | 21.86449 | 50.32119 | -0.8149 | 20.69705 |
| August | 299.00000 | 21.98212 | 49.80683 | -0.7917 | 19.85183 |
| September | 260.00000 | 22.25097 | 45.66429 | -0.7155 | 18.61118 |
| October | 273.00000 | 20.74267 | 44.74034 | -0.2601 | 7.68705 |
| November | 273.00000 | 19.88061 | 41.89774 | -0.5522 | 13.78972 |
| December | 260.00000 | 18.95950 | 35.88674 | -0.8369 | 22.47743 |
| Annual Sum or Average | 3276.00000 | 20.65004 | 41.97796 | -0.6953 | 18.60647 |
| Minimum of Months | 247.00000 | 18.78247 | 34.28680 | -1.0987 | 7.68705 |
| Maximum of Months | 299.00000 | 22.25097 | 50.32119 | -0.2437 | 32.60112 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| BOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
| January | 0.456713E+11 | 0.00 | 324.63 | 332100.12 | 02-JAN-06:01 | 0.00 | 34.73 | 51.88 | 0.10 | 0.00 | 0.06 | 1.20 | 02-JAN-06:01 |
| February | 0.267058E+11 | 0.00 | 277.80 | 332100.12 | 01-FEB-08:61 | 0.00 | 34.34 | 49.71 | 0.07 | 0.00 | 0.04 | 1.20 | 01-FEB-08:61 |
| March | 0.220499E+11 | 0.00 | 325.58 | 332100.12 | 01-MAR-07:11 | 0.00 | 34.48 | 49.78 | 0.05 | 0.00 | 0.03 | 1.20 | 01-MAR-07:11 |
| April | 0.413779E+10 | 0.00 | 205.55 | 332100.12 | 03-APR-07:01 | 0.00 | 47.67 | 56.76 | 0.01 | 0.00 | 0.01 | 1.20 | 03-APR-07:01 |
| May | 0.315742E+10 | 0.00 | 188.75 | 195979.92 | 05-MAY-07:01 | 0.00 | 50.81 | 58.76 | 0.01 | 0.00 | 0.00 | 0.71 | 05-MAY-07:01 |
| June | 0.160852E+10 | 0.00 | 122.11 | 44258.50 | 30-JUN-07:01 | 0.00 | 51.73 | 57.10 | 0.01 | 0.00 | 0.00 | 0.16 | 30-JUN-07:01 |
| July | 0.255121E+10 | 0.00 | 114.88 | 265926.30 | 05-JUL-07:01 | 0.00 | 38.68 | 45.12 | 0.01 | 0.00 | 0.00 | 0.96 | 05-JUL-07:01 |
| August | 0.429522E+10 | 0.00 | 154.78 | 254515.60 | 24-AUG-07:01 | 0.00 | 31.74 | 41.60 | 0.01 | 0.00 | 0.01 | 0.92 | 24-AUG-07:01 |
| September | 0.161567E+10 | 0.00 | 82.83 | 235014.14 | 01-SEP-07:01 | 0.00 | 49.60 | 53.21 | 0.00 | 0.00 | 0.00 | 0.85 | 01-SEP-07:01 |
| October | 0.592985E+10 | 0.00 | 241.62 | 332100.12 | 23-OCT-07:01 | 0.00 | 43.26 | 54.21 | 0.02 | 0.00 | 0.01 | 1.20 | 23-OCT-07:01 |
| November | 0.193075E+11 | 0.00 | 298.38 | 332100.12 | 03-NOV-07:01 | 0.00 | 33.35 | 48.15 | 0.05 | 0.00 | 0.03 | 1.20 | 03-NOV-07:01 |
| December | 0.402699E+11 | 0.00 | 301.49 | 332100.12 | 01-DEC-08:61 | 0.00 | 34.38 | 50.35 | 0.09 | 0.00 | 0.05 | 1.20 | 01-DEC-08:61 |
| Annual Sum or Average | 0.177300E+12 | 0.00 | 2638.38 | 0.00 | 40.39 | 51.37 | 0.03 | 0.00 | 0.02 | ||||
| Minimum of Months | 0.160852E+10 | 0.00 | 82.83 | 44258.50 | 0.00 | 31.74 | 41.60 | 0.00 | 0.00 | 0.00 | 0.16 | ||
| Maximum of Months | 0.456713E+11 | 0.00 | 325.58 | 332100.12 | 0.00 | 51.73 | 58.76 | 0.10 | 0.00 | 0.06 | 1.20 |
Report: DXReportMonthly
For: VAV_POD_1 COOLING COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 |
| March | 1522398.05 | 488428.64 | 0.03 | 1486021.11 | 36376.94 | 0.00 | 0.14 | 30-MAR-14:01 | 0.00 | 01-MAR-00:10 | 17616.61 | 30-MAR-14:01 | 17616.61 | 30-MAR-14:01 | 606.28 | 28-MAR-14:01 | 5620.89 | 30-MAR-14:01 | 0.00 |
| April | 0.907175E+10 | 0.257330E+10 | 39.22 | 0.894384E+10 | 0.127909E+09 | 0.00 | 1.00 | 28-APR-14:02 | 0.00 | 01-APR-00:10 | 175489.74 | 28-APR-14:02 | 175489.74 | 28-APR-14:02 | 29108.25 | 28-APR-08:00 | 44574.18 | 28-APR-14:02 | 0.00 |
| May | 0.170166E+11 | 0.470535E+10 | 61.26 | 0.153342E+11 | 0.168248E+10 | 0.00 | 1.00 | 22-MAY-12:05 | 0.00 | 01-MAY-00:10 | 269792.11 | 22-MAY-15:00 | 269792.11 | 22-MAY-15:00 | 49711.28 | 23-MAY-14:01 | 68443.21 | 22-MAY-15:00 | 0.00 |
| June | 0.523992E+11 | 0.141840E+11 | 162.17 | 0.455728E+11 | 0.682637E+10 | 0.00 | 1.00 | 09-JUN-14:01 | 0.00 | 01-JUN-00:03 | 395953.14 | 13-JUN-14:05 | 318588.16 | 13-JUN-15:00 | 135465.46 | 25-JUN-17:57 | 99542.67 | 13-JUN-14:05 | 0.00 |
| July | 0.639193E+11 | 0.179344E+11 | 239.94 | 0.517030E+11 | 0.122163E+11 | 0.00 | 1.00 | 10-JUL-10:50 | 0.00 | 01-JUL-00:10 | 242238.84 | 21-JUL-14:05 | 242238.84 | 21-JUL-14:05 | 76234.95 | 24-JUL-14:01 | 61475.20 | 21-JUL-14:05 | 0.00 |
| August | 0.807656E+11 | 0.228558E+11 | 299.51 | 0.641142E+11 | 0.166514E+11 | 0.00 | 1.00 | 14-AUG-13:00 | 0.00 | 01-AUG-00:10 | 208802.44 | 17-AUG-14:03 | 195489.74 | 20-AUG-15:40 | 69610.89 | 18-AUG-14:02 | 53012.70 | 17-AUG-14:03 | 0.00 |
| September | 0.501076E+11 | 0.137873E+11 | 179.04 | 0.436505E+11 | 0.645705E+10 | 0.00 | 1.00 | 10-SEP-14:38 | 0.00 | 01-SEP-00:05 | 246319.63 | 12-SEP-14:02 | 214687.69 | 27-SEP-14:05 | 69933.84 | 12-SEP-14:02 | 62507.52 | 12-SEP-14:02 | 0.00 |
| October | 0.233935E+10 | 0.720596E+09 | 20.92 | 0.220097E+10 | 0.138380E+09 | 0.00 | 0.77 | 17-OCT-14:02 | 0.00 | 01-OCT-00:10 | 114593.25 | 17-OCT-14:02 | 82077.55 | 17-OCT-14:02 | 33378.01 | 18-OCT-14:01 | 31133.20 | 17-OCT-14:02 | 0.00 |
| November | 56509431.06 | 17927337.92 | 0.87 | 42629020.08 | 13880410.98 | 0.00 | 0.30 | 10-NOV-15:01 | 0.00 | 01-NOV-00:10 | 39113.03 | 10-NOV-15:01 | 33357.42 | 10-NOV-15:01 | 6374.98 | 15-NOV-15:01 | 12015.20 | 10-NOV-15:01 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
| Annual Sum or Average | 0.275677E+12 | 0.767791E+11 | 1002.95 | 0.231564E+12 | 0.441139E+11 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.807656E+11 | 0.228558E+11 | 299.51 | 0.641142E+11 | 0.166514E+11 | 0.00 | 1.00 | 0.00 | 395953.14 | 318588.16 | 135465.46 | 99542.67 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_1:6 COOLING COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.119464E+09 | 31395749.61 | 37.28 | 75301976.24 | 44162393.63 | 0.00 | 1.00 | 03-JAN-06:01 | 0.00 | 01-JAN-00:05 | 27827.84 | 03-JAN-06:01 | 21948.74 | 10-JAN-06:01 | 12327.18 | 23-JAN-06:01 | 6394.66 | 03-JAN-06:01 | 0.00 | 01-JAN-00:05 |
| February | 0.119598E+09 | 31440720.47 | 36.30 | 73573295.54 | 46024642.25 | 0.00 | 1.00 | 01-FEB-06:11 | 0.00 | 01-FEB-00:10 | 27827.84 | 03-FEB-06:01 | 21654.08 | 15-FEB-06:11 | 12911.85 | 22-FEB-06:01 | 6394.66 | 01-FEB-06:11 | 0.00 | 01-FEB-00:10 |
| March | 0.156809E+09 | 41417561.53 | 57.14 | 0.101382E+09 | 55427263.37 | 0.00 | 1.00 | 01-MAR-06:01 | 0.00 | 01-MAR-00:10 | 27827.84 | 01-MAR-06:01 | 20580.41 | 08-MAR-06:01 | 11351.70 | 17-MAR-05:52 | 6394.66 | 01-MAR-06:01 | 0.00 | 01-MAR-00:10 |
| April | 0.745541E+09 | 0.187547E+09 | 97.19 | 0.648247E+09 | 97294577.86 | 0.00 | 1.00 | 03-APR-05:01 | 0.00 | 01-APR-00:20 | 28447.22 | 30-APR-11:53 | 28146.69 | 30-APR-14:50 | 10966.02 | 21-APR-05:01 | 6806.01 | 30-APR-14:50 | 0.00 | 01-APR-00:10 |
| May | 0.145670E+10 | 0.351116E+09 | 106.39 | 0.109790E+10 | 0.358800E+09 | 0.00 | 1.00 | 01-MAY-05:11 | 0.00 | 01-MAY-00:20 | 28088.14 | 21-MAY-18:33 | 27827.84 | 21-MAY-15:13 | 13280.43 | 24-MAY-05:01 | 6466.83 | 21-MAY-18:33 | 0.00 | 01-MAY-00:10 |
| June | 0.401351E+10 | 0.957161E+09 | 140.62 | 0.300496E+10 | 0.100856E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:03 | 31877.39 | 25-JUN-17:53 | 28746.64 | 25-JUN-15:12 | 17421.56 | 25-JUN-17:53 | 7283.96 | 25-JUN-17:53 | 0.00 | 01-JUN-00:03 |
| July | 0.386823E+10 | 0.961638E+09 | 181.58 | 0.292871E+10 | 0.939519E+09 | 0.00 | 1.00 | 01-JUL-09:13 | 0.00 | 01-JUL-00:20 | 30105.11 | 23-JUL-15:52 | 29592.27 | 22-JUL-19:32 | 15762.84 | 24-JUL-05:01 | 7468.39 | 22-JUL-19:32 | 0.00 | 01-JUL-00:10 |
| August | 0.472498E+10 | 0.116204E+10 | 220.97 | 0.354052E+10 | 0.118446E+10 | 0.00 | 1.00 | 01-AUG-04:22 | 0.00 | 01-AUG-00:10 | 29482.05 | 19-AUG-15:53 | 28265.45 | 20-AUG-15:35 | 15587.74 | 17-AUG-05:01 | 6913.09 | 20-AUG-15:35 | 0.00 | 01-AUG-00:10 |
| September | 0.362215E+10 | 0.870146E+09 | 170.06 | 0.283219E+10 | 0.789956E+09 | 0.00 | 1.00 | 01-SEP-05:01 | 0.00 | 01-SEP-00:05 | 29955.06 | 10-SEP-15:33 | 23925.02 | 24-SEP-15:13 | 14963.51 | 01-SEP-05:01 | 6976.89 | 10-SEP-14:53 | 0.00 | 01-SEP-00:05 |
| October | 0.299229E+09 | 79418639.35 | 92.48 | 0.207253E+09 | 91975909.59 | 0.00 | 1.00 | 01-OCT-11:02 | 0.00 | 01-OCT-00:10 | 27827.84 | 19-OCT-05:11 | 27783.04 | 07-OCT-13:12 | 14803.75 | 20-OCT-05:11 | 6394.66 | 01-OCT-11:02 | 0.00 | 01-OCT-00:10 |
| November | 0.172431E+09 | 45577643.37 | 63.12 | 0.106739E+09 | 65692112.81 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 27827.84 | 01-NOV-05:01 | 20505.77 | 28-NOV-06:01 | 13774.22 | 09-NOV-06:11 | 6394.66 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 |
| December | 0.112530E+09 | 29612912.43 | 27.26 | 72595765.56 | 39933842.22 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 | 27827.84 | 20-DEC-06:01 | 22613.61 | 29-DEC-06:01 | 11589.07 | 20-DEC-06:01 | 6394.66 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.194112E+11 | 0.474851E+10 | 1230.39 | 0.146894E+11 | 0.472181E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.112530E+09 | 29612912.43 | 27.26 | 72595765.56 | 39933842.22 | 0.00 | 1.00 | 0.00 | 27827.84 | 20505.77 | 10966.02 | 6394.66 | 0.00 | |||||||
| Maximum of Months | 0.472498E+10 | 0.116204E+10 | 220.97 | 0.354052E+10 | 0.118446E+10 | 0.00 | 1.00 | 0.00 | 31877.39 | 29592.27 | 17421.56 | 7468.39 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:7 COOLING COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.254836E+09 | 68618796.64 | 12.09 | 0.233905E+09 | 20931073.96 | 0.00 | 1.00 | 30-APR-14:02 | 0.00 | 01-APR-00:10 | 45532.83 | 30-APR-14:02 | 45532.83 | 30-APR-14:02 | 6915.07 | 28-APR-08:07 | 11185.87 | 30-APR-14:02 | 0.00 | 01-APR-00:10 |
| May | 0.113255E+10 | 0.278311E+09 | 28.96 | 0.912321E+09 | 0.220234E+09 | 0.00 | 1.00 | 22-MAY-13:05 | 0.00 | 01-MAY-00:10 | 29642.35 | 22-MAY-14:00 | 26309.54 | 22-MAY-14:00 | 6917.52 | 23-MAY-08:07 | 6966.66 | 22-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.463889E+10 | 0.113290E+10 | 97.02 | 0.362903E+10 | 0.100986E+10 | 0.00 | 1.00 | 12-JUN-11:40 | 0.00 | 01-JUN-00:03 | 49971.99 | 25-JUN-17:31 | 46411.43 | 25-JUN-12:22 | 27016.08 | 27-JUN-05:01 | 11884.43 | 25-JUN-17:31 | 0.00 | 01-JUN-00:03 |
| July | 0.123609E+10 | 0.335431E+09 | 49.34 | 0.114316E+10 | 92925680.65 | 0.00 | 1.00 | 17-JUL-05:01 | 0.00 | 01-JUL-00:10 | 48844.95 | 23-JUL-15:51 | 35248.22 | 23-JUL-13:11 | 25667.23 | 24-JUL-05:01 | 11731.05 | 23-JUL-15:51 | 0.00 | 01-JUL-00:10 |
| August | 0.108316E+10 | 0.296422E+09 | 51.68 | 0.954608E+09 | 0.128557E+09 | 0.00 | 1.00 | 20-AUG-16:03 | 0.00 | 01-AUG-00:10 | 46570.98 | 20-AUG-16:03 | 46570.98 | 20-AUG-16:03 | 2373.94 | 14-AUG-12:40 | 11546.01 | 20-AUG-16:03 | 0.00 | 01-AUG-00:10 |
| September | 0.392922E+10 | 0.979187E+09 | 100.96 | 0.315101E+10 | 0.778203E+09 | 0.00 | 1.00 | 11-SEP-14:00 | 0.00 | 01-SEP-00:05 | 31152.15 | 13-SEP-14:00 | 26229.68 | 13-SEP-14:00 | 9300.76 | 12-SEP-14:00 | 7341.03 | 13-SEP-14:00 | 0.00 | 01-SEP-00:05 |
| October | 9591026.35 | 2794500.42 | 3.02 | 8966070.28 | 624956.07 | 0.00 | 0.15 | 11-OCT-11:00 | 0.00 | 01-OCT-00:10 | 2826.67 | 11-OCT-11:00 | 2662.19 | 11-OCT-11:00 | 172.56 | 11-OCT-10:50 | 812.52 | 11-OCT-11:00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.122843E+11 | 0.309367E+10 | 343.08 | 0.100330E+11 | 0.225133E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.463889E+10 | 0.113290E+10 | 100.96 | 0.362903E+10 | 0.100986E+10 | 0.00 | 1.00 | 0.00 | 49971.99 | 46570.98 | 27016.08 | 11884.43 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 64.64 | 21.36 | 43.28 | 32.96 | 236.84 | 0.00 | 0.00 | 0.00 |
| February | 114.45 | 48.32 | 66.13 | 81.37 | 228.59 | 0.00 | 0.00 | 0.00 |
| March | 103.49 | 19.80 | 83.69 | 52.35 | 182.62 | 0.00 | 0.00 | 0.00 |
| April | 244.18 | 96.99 | 147.19 | 231.39 | 165.06 | 0.00 | 0.00 | 0.00 |
| May | 286.48 | 116.49 | 169.99 | 269.17 | 145.49 | 0.00 | 0.00 | 0.00 |
| June | 309.37 | 127.36 | 182.01 | 325.20 | 113.27 | 0.00 | 0.00 | 0.00 |
| July | 315.08 | 138.92 | 176.16 | 359.58 | 97.00 | 0.00 | 0.00 | 0.00 |
| August | 264.65 | 114.58 | 150.06 | 304.29 | 106.39 | 0.00 | 0.00 | 0.00 |
| September | 212.32 | 95.21 | 117.11 | 220.99 | 152.27 | 0.00 | 0.00 | 0.00 |
| October | 113.26 | 40.73 | 72.53 | 85.17 | 194.64 | 0.00 | 0.00 | 0.00 |
| November | 61.29 | 17.89 | 43.40 | 30.34 | 227.50 | 0.00 | 0.00 | 0.00 |
| December | 34.69 | 7.32 | 27.37 | 9.97 | 263.70 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 177.18 | 70.44 | 106.74 | 167.22 | 175.81 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34.69 | 7.32 | 27.37 | 9.97 | 97.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 315.08 | 138.92 | 182.01 | 359.58 | 263.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 28.42 | 18.40 | 10.02 | 27.44 | 33.32 | 0.00 | 0.00 | 0.00 |
| February | 34.71 | 21.18 | 13.53 | 34.34 | 33.17 | 0.00 | 0.00 | 0.00 |
| March | 21.46 | 6.25 | 15.21 | 16.17 | 27.77 | 0.00 | 0.00 | 0.00 |
| April | 44.56 | 20.14 | 24.42 | 48.79 | 26.05 | 0.00 | 0.00 | 0.00 |
| May | 36.86 | 12.00 | 24.86 | 36.02 | 23.73 | 0.00 | 0.00 | 0.00 |
| June | 33.95 | 8.22 | 25.74 | 34.94 | 18.20 | 0.00 | 0.00 | 0.00 |
| July | 36.79 | 11.52 | 25.27 | 43.00 | 15.52 | 0.00 | 0.00 | 0.00 |
| August | 43.11 | 19.39 | 23.72 | 53.99 | 16.66 | 0.00 | 0.00 | 0.00 |
| September | 50.94 | 29.84 | 21.10 | 61.73 | 23.26 | 0.00 | 0.00 | 0.00 |
| October | 35.00 | 20.46 | 14.54 | 37.25 | 28.97 | 0.00 | 0.00 | 0.00 |
| November | 24.81 | 15.10 | 9.72 | 23.80 | 32.83 | 0.00 | 0.00 | 0.00 |
| December | 19.67 | 12.60 | 7.07 | 18.43 | 37.76 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 34.14 | 16.19 | 17.94 | 36.27 | 26.40 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19.67 | 6.25 | 7.07 | 16.17 | 15.52 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 50.94 | 29.84 | 25.74 | 61.73 | 37.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 197.24 | 127.68 | 69.56 | 190.43 | 231.23 | 0.00 | 0.00 | 0.00 |
| February | 240.90 | 147.00 | 93.90 | 238.35 | 230.20 | 0.00 | 0.00 | 0.00 |
| March | 148.94 | 43.36 | 105.57 | 112.22 | 192.73 | 0.00 | 0.00 | 0.00 |
| April | 309.28 | 139.79 | 169.49 | 338.59 | 180.83 | 0.00 | 0.00 | 0.00 |
| May | 255.81 | 83.28 | 172.52 | 249.92 | 165.09 | 0.00 | 0.00 | 0.00 |
| June | 235.65 | 57.04 | 178.61 | 242.12 | 126.84 | 0.00 | 0.00 | 0.00 |
| July | 255.33 | 79.96 | 175.37 | 298.05 | 108.03 | 0.00 | 0.00 | 0.00 |
| August | 299.18 | 134.58 | 164.60 | 374.66 | 115.70 | 0.00 | 0.00 | 0.00 |
| September | 353.56 | 207.12 | 146.44 | 428.44 | 161.40 | 0.00 | 0.00 | 0.00 |
| October | 242.91 | 141.97 | 100.94 | 258.50 | 201.09 | 0.00 | 0.00 | 0.00 |
| November | 172.22 | 104.77 | 67.46 | 165.20 | 227.82 | 0.00 | 0.00 | 0.00 |
| December | 136.50 | 87.46 | 49.04 | 127.88 | 262.10 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 236.93 | 112.40 | 124.53 | 251.69 | 183.31 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 136.50 | 43.36 | 49.04 | 112.22 | 108.03 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 353.56 | 207.12 | 178.61 | 428.44 | 262.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 362.44 | 234.62 | 127.82 | 344.00 | 455.38 | 0.00 | 0.00 | 0.00 |
| February | 442.66 | 270.11 | 172.54 | 430.33 | 455.73 | 0.00 | 0.00 | 0.00 |
| March | 273.68 | 79.68 | 194.00 | 197.89 | 384.36 | 0.00 | 0.00 | 0.00 |
| April | 568.32 | 256.87 | 311.44 | 616.03 | 353.95 | 0.00 | 0.00 | 0.00 |
| May | 470.05 | 153.03 | 317.02 | 453.90 | 321.87 | 0.00 | 0.00 | 0.00 |
| June | 433.02 | 104.82 | 328.20 | 443.14 | 242.39 | 0.00 | 0.00 | 0.00 |
| July | 469.17 | 146.92 | 322.24 | 550.87 | 201.73 | 0.00 | 0.00 | 0.00 |
| August | 549.76 | 247.30 | 302.46 | 690.64 | 217.52 | 0.00 | 0.00 | 0.00 |
| September | 649.67 | 380.59 | 269.08 | 784.48 | 311.41 | 0.00 | 0.00 | 0.00 |
| October | 446.35 | 260.87 | 185.48 | 469.13 | 397.36 | 0.00 | 0.00 | 0.00 |
| November | 316.46 | 192.51 | 123.95 | 298.17 | 451.24 | 0.00 | 0.00 | 0.00 |
| December | 250.83 | 160.71 | 90.12 | 230.56 | 518.16 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 435.37 | 206.53 | 228.83 | 458.49 | 358.68 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 250.83 | 79.68 | 90.12 | 197.89 | 201.73 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 649.67 | 380.59 | 328.20 | 784.48 | 518.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 362.44 | 234.62 | 127.82 | 344.00 | 455.38 | 0.00 | 0.00 | 0.00 |
| February | 442.66 | 270.11 | 172.54 | 430.33 | 455.73 | 0.00 | 0.00 | 0.00 |
| March | 273.68 | 79.68 | 194.00 | 197.89 | 384.36 | 0.00 | 0.00 | 0.00 |
| April | 568.32 | 256.87 | 311.44 | 616.03 | 353.95 | 0.00 | 0.00 | 0.00 |
| May | 470.05 | 153.03 | 317.02 | 453.90 | 321.87 | 0.00 | 0.00 | 0.00 |
| June | 433.02 | 104.82 | 328.20 | 443.14 | 242.39 | 0.00 | 0.00 | 0.00 |
| July | 469.17 | 146.92 | 322.24 | 550.87 | 201.73 | 0.00 | 0.00 | 0.00 |
| August | 549.76 | 247.30 | 302.46 | 690.64 | 217.52 | 0.00 | 0.00 | 0.00 |
| September | 649.67 | 380.59 | 269.08 | 784.48 | 311.41 | 0.00 | 0.00 | 0.00 |
| October | 446.35 | 260.87 | 185.48 | 469.13 | 397.36 | 0.00 | 0.00 | 0.00 |
| November | 316.46 | 192.51 | 123.95 | 298.17 | 451.24 | 0.00 | 0.00 | 0.00 |
| December | 250.83 | 160.71 | 90.12 | 230.56 | 518.16 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 435.37 | 206.53 | 228.83 | 458.49 | 358.68 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 250.83 | 79.68 | 90.12 | 197.89 | 201.73 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 649.67 | 380.59 | 328.20 | 784.48 | 518.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 362.43 | 234.62 | 127.82 | 344.00 | 455.37 | 0.00 | 0.00 | 0.00 |
| February | 442.65 | 270.11 | 172.54 | 430.32 | 455.72 | 0.00 | 0.00 | 0.00 |
| March | 273.67 | 79.68 | 193.99 | 197.88 | 384.35 | 0.00 | 0.00 | 0.00 |
| April | 568.31 | 256.87 | 311.44 | 616.01 | 353.95 | 0.00 | 0.00 | 0.00 |
| May | 470.04 | 153.03 | 317.01 | 453.89 | 321.87 | 0.00 | 0.00 | 0.00 |
| June | 433.01 | 104.81 | 328.20 | 443.13 | 242.38 | 0.00 | 0.00 | 0.00 |
| July | 469.16 | 146.92 | 322.23 | 550.86 | 201.73 | 0.00 | 0.00 | 0.00 |
| August | 549.75 | 247.30 | 302.45 | 690.63 | 217.51 | 0.00 | 0.00 | 0.00 |
| September | 649.66 | 380.58 | 269.08 | 784.47 | 311.40 | 0.00 | 0.00 | 0.00 |
| October | 446.34 | 260.87 | 185.48 | 469.12 | 397.35 | 0.00 | 0.00 | 0.00 |
| November | 316.46 | 192.51 | 123.95 | 298.16 | 451.23 | 0.00 | 0.00 | 0.00 |
| December | 250.82 | 160.70 | 90.12 | 230.55 | 518.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 435.36 | 206.53 | 228.83 | 458.49 | 358.67 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 250.82 | 79.68 | 90.12 | 197.88 | 201.73 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 649.66 | 380.58 | 328.20 | 784.47 | 518.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.55 | 7.12 | 14.43 | 11.15 | 83.95 | 0.00 | 0.00 | 0.00 |
| February | 38.15 | 16.11 | 22.04 | 27.35 | 81.46 | 0.00 | 0.00 | 0.00 |
| March | 34.50 | 6.60 | 27.90 | 16.60 | 66.41 | 0.00 | 0.00 | 0.00 |
| April | 81.39 | 32.33 | 49.06 | 77.02 | 58.18 | 0.00 | 0.00 | 0.00 |
| May | 95.49 | 38.83 | 56.66 | 88.32 | 52.66 | 0.00 | 0.00 | 0.00 |
| June | 103.12 | 42.45 | 60.67 | 106.80 | 40.63 | 0.00 | 0.00 | 0.00 |
| July | 105.03 | 46.31 | 58.72 | 119.72 | 33.61 | 0.00 | 0.00 | 0.00 |
| August | 88.22 | 38.20 | 50.02 | 102.33 | 35.91 | 0.00 | 0.00 | 0.00 |
| September | 70.77 | 31.74 | 39.04 | 74.64 | 52.02 | 0.00 | 0.00 | 0.00 |
| October | 37.75 | 13.58 | 24.18 | 28.80 | 68.51 | 0.00 | 0.00 | 0.00 |
| November | 20.43 | 5.96 | 14.47 | 10.30 | 80.71 | 0.00 | 0.00 | 0.00 |
| December | 11.56 | 2.44 | 9.12 | 3.33 | 95.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 59.06 | 23.48 | 35.58 | 55.63 | 62.37 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11.56 | 2.44 | 9.12 | 3.33 | 33.61 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 105.03 | 46.31 | 60.67 | 119.72 | 95.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 64.64 | 21.36 | 43.28 | 36.38 | 226.95 | 0.00 | 0.00 | 0.00 |
| February | 114.45 | 48.32 | 66.13 | 86.79 | 216.34 | 0.00 | 0.00 | 0.00 |
| March | 103.49 | 19.80 | 83.69 | 55.23 | 178.08 | 0.00 | 0.00 | 0.00 |
| April | 244.18 | 96.99 | 147.19 | 241.88 | 154.51 | 0.00 | 0.00 | 0.00 |
| May | 286.48 | 116.49 | 169.99 | 276.49 | 139.03 | 0.00 | 0.00 | 0.00 |
| June | 309.37 | 127.36 | 182.01 | 330.34 | 109.75 | 0.00 | 0.00 | 0.00 |
| July | 315.08 | 138.92 | 176.16 | 368.35 | 91.50 | 0.00 | 0.00 | 0.00 |
| August | 264.65 | 114.58 | 150.06 | 316.37 | 96.61 | 0.00 | 0.00 | 0.00 |
| September | 212.32 | 95.21 | 117.11 | 232.46 | 138.60 | 0.00 | 0.00 | 0.00 |
| October | 113.26 | 40.73 | 72.53 | 92.36 | 181.79 | 0.00 | 0.00 | 0.00 |
| November | 61.29 | 17.89 | 43.40 | 33.42 | 216.60 | 0.00 | 0.00 | 0.00 |
| December | 34.69 | 7.32 | 27.37 | 11.06 | 257.41 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 177.18 | 70.44 | 106.74 | 173.74 | 166.99 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34.69 | 7.32 | 27.37 | 11.06 | 91.50 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 315.08 | 138.92 | 182.01 | 368.35 | 257.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.01 | 0.00 | 4.01 | 0.05 | 37.06 | 0.00 | 0.00 | 0.00 |
| February | 6.26 | 0.00 | 6.26 | 0.17 | 35.37 | 0.00 | 0.00 | 0.00 |
| March | 8.97 | 0.00 | 8.97 | 1.21 | 28.86 | 0.00 | 0.00 | 0.00 |
| April | 13.87 | 0.07 | 13.80 | 5.26 | 24.39 | 0.00 | 0.00 | 0.00 |
| May | 17.66 | 0.91 | 16.74 | 6.21 | 20.68 | 0.00 | 0.00 | 0.00 |
| June | 19.65 | 1.37 | 18.28 | 11.96 | 15.82 | 0.00 | 0.00 | 0.00 |
| July | 18.44 | 1.17 | 17.28 | 14.61 | 13.01 | 0.00 | 0.00 | 0.00 |
| August | 14.11 | 0.24 | 13.87 | 11.27 | 13.82 | 0.00 | 0.00 | 0.00 |
| September | 10.62 | 0.00 | 10.62 | 5.53 | 21.16 | 0.00 | 0.00 | 0.00 |
| October | 7.02 | 0.00 | 7.02 | 0.99 | 28.29 | 0.00 | 0.00 | 0.00 |
| November | 4.27 | 0.00 | 4.27 | 0.03 | 34.41 | 0.00 | 0.00 | 0.00 |
| December | 2.91 | 0.00 | 2.91 | 0.00 | 39.94 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 10.67 | 0.32 | 10.35 | 4.80 | 26.01 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 2.91 | 0.00 | 2.91 | 0.00 | 13.01 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 19.65 | 1.37 | 18.28 | 14.61 | 39.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 29.45 | 0.00 | 29.45 | 0.56 | 256.16 | 0.00 | 0.00 | 0.00 |
| February | 45.98 | 0.00 | 45.98 | 1.75 | 243.39 | 0.00 | 0.00 | 0.00 |
| March | 65.27 | 0.00 | 65.27 | 10.43 | 199.51 | 0.00 | 0.00 | 0.00 |
| April | 102.29 | 0.47 | 101.82 | 42.93 | 168.77 | 0.00 | 0.00 | 0.00 |
| May | 129.24 | 6.34 | 122.90 | 50.34 | 143.16 | 0.00 | 0.00 | 0.00 |
| June | 143.58 | 9.52 | 134.06 | 91.88 | 110.35 | 0.00 | 0.00 | 0.00 |
| July | 135.14 | 8.09 | 127.05 | 110.31 | 91.05 | 0.00 | 0.00 | 0.00 |
| August | 104.36 | 1.66 | 102.71 | 86.15 | 96.94 | 0.00 | 0.00 | 0.00 |
| September | 78.90 | 0.01 | 78.88 | 44.24 | 147.33 | 0.00 | 0.00 | 0.00 |
| October | 51.68 | 0.00 | 51.68 | 9.19 | 196.01 | 0.00 | 0.00 | 0.00 |
| November | 31.32 | 0.00 | 31.32 | 0.39 | 237.94 | 0.00 | 0.00 | 0.00 |
| December | 21.34 | 0.00 | 21.34 | 0.00 | 277.18 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 78.36 | 2.19 | 76.17 | 37.56 | 180.29 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21.34 | 0.00 | 21.34 | 0.00 | 91.05 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 143.58 | 9.52 | 134.06 | 110.31 | 277.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 48.45 | 0.00 | 48.45 | 0.19 | 505.84 | 0.00 | 0.00 | 0.00 |
| February | 75.70 | 0.00 | 75.70 | 0.97 | 489.34 | 0.00 | 0.00 | 0.00 |
| March | 108.59 | 0.00 | 108.59 | 8.37 | 404.64 | 0.00 | 0.00 | 0.00 |
| April | 166.54 | 0.28 | 166.26 | 53.57 | 336.45 | 0.00 | 0.00 | 0.00 |
| May | 206.79 | 6.57 | 200.22 | 62.02 | 294.20 | 0.00 | 0.00 | 0.00 |
| June | 229.95 | 12.99 | 216.96 | 130.76 | 217.22 | 0.00 | 0.00 | 0.00 |
| July | 215.69 | 10.28 | 205.40 | 170.15 | 174.34 | 0.00 | 0.00 | 0.00 |
| August | 167.85 | 1.28 | 166.58 | 136.23 | 183.43 | 0.00 | 0.00 | 0.00 |
| September | 128.47 | 0.01 | 128.46 | 62.24 | 281.45 | 0.00 | 0.00 | 0.00 |
| October | 84.83 | 0.00 | 84.83 | 7.26 | 389.94 | 0.00 | 0.00 | 0.00 |
| November | 51.52 | 0.00 | 51.52 | 0.07 | 475.30 | 0.00 | 0.00 | 0.00 |
| December | 35.11 | 0.00 | 35.11 | 0.00 | 548.53 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 126.85 | 2.63 | 124.22 | 52.98 | 357.65 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.11 | 0.00 | 35.11 | 0.00 | 174.34 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 229.95 | 12.99 | 216.96 | 170.15 | 548.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.18 | 0.00 | 51.18 | 0.36 | 505.13 | 0.00 | 0.00 | 0.00 |
| February | 79.89 | 0.00 | 79.89 | 1.42 | 487.07 | 0.00 | 0.00 | 0.00 |
| March | 114.48 | 0.00 | 114.48 | 11.26 | 401.97 | 0.00 | 0.00 | 0.00 |
| April | 176.43 | 0.64 | 175.79 | 61.75 | 333.54 | 0.00 | 0.00 | 0.00 |
| May | 222.59 | 10.21 | 212.39 | 73.70 | 285.25 | 0.00 | 0.00 | 0.00 |
| June | 247.69 | 17.50 | 230.19 | 150.92 | 214.00 | 0.00 | 0.00 | 0.00 |
| July | 232.13 | 14.11 | 218.02 | 188.99 | 171.98 | 0.00 | 0.00 | 0.00 |
| August | 179.10 | 2.60 | 176.49 | 146.48 | 181.15 | 0.00 | 0.00 | 0.00 |
| September | 135.48 | 0.01 | 135.47 | 68.73 | 282.61 | 0.00 | 0.00 | 0.00 |
| October | 89.54 | 0.00 | 89.54 | 9.60 | 389.41 | 0.00 | 0.00 | 0.00 |
| November | 54.43 | 0.00 | 54.43 | 0.16 | 474.49 | 0.00 | 0.00 | 0.00 |
| December | 37.11 | 0.00 | 37.11 | 0.00 | 548.95 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 135.26 | 3.78 | 131.48 | 59.81 | 355.55 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 37.11 | 0.00 | 37.11 | 0.00 | 171.98 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 247.69 | 17.50 | 230.19 | 188.99 | 548.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.20 | 0.00 | 51.20 | 0.36 | 505.12 | 0.00 | 0.00 | 0.00 |
| February | 79.91 | 0.00 | 79.91 | 1.42 | 487.04 | 0.00 | 0.00 | 0.00 |
| March | 114.51 | 0.00 | 114.51 | 11.28 | 401.95 | 0.00 | 0.00 | 0.00 |
| April | 176.99 | 0.84 | 176.15 | 61.86 | 332.64 | 0.00 | 0.00 | 0.00 |
| May | 224.09 | 10.99 | 213.11 | 73.99 | 283.24 | 0.00 | 0.00 | 0.00 |
| June | 248.42 | 17.52 | 230.90 | 151.07 | 213.10 | 0.00 | 0.00 | 0.00 |
| July | 233.31 | 14.45 | 218.85 | 189.32 | 170.54 | 0.00 | 0.00 | 0.00 |
| August | 180.01 | 3.00 | 177.02 | 146.84 | 180.04 | 0.00 | 0.00 | 0.00 |
| September | 135.60 | 0.02 | 135.58 | 68.79 | 282.49 | 0.00 | 0.00 | 0.00 |
| October | 89.57 | 0.00 | 89.57 | 9.62 | 389.40 | 0.00 | 0.00 | 0.00 |
| November | 54.45 | 0.00 | 54.45 | 0.16 | 474.47 | 0.00 | 0.00 | 0.00 |
| December | 37.12 | 0.00 | 37.12 | 0.00 | 548.94 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 135.69 | 3.93 | 131.76 | 59.92 | 355.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 37.12 | 0.00 | 37.12 | 0.00 | 170.54 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 248.42 | 17.52 | 230.90 | 189.32 | 548.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 64.64 | 21.36 | 43.28 | 33.39 | 235.44 | 0.00 | 0.00 | 0.00 |
| February | 114.45 | 48.32 | 66.13 | 81.59 | 228.27 | 0.00 | 0.00 | 0.00 |
| March | 103.49 | 19.80 | 83.69 | 52.53 | 182.53 | 0.00 | 0.00 | 0.00 |
| April | 244.18 | 96.99 | 147.19 | 232.05 | 164.52 | 0.00 | 0.00 | 0.00 |
| May | 286.48 | 116.49 | 169.99 | 269.94 | 144.93 | 0.00 | 0.00 | 0.00 |
| June | 309.37 | 127.36 | 182.01 | 326.09 | 112.70 | 0.00 | 0.00 | 0.00 |
| July | 315.08 | 138.92 | 176.16 | 360.81 | 96.25 | 0.00 | 0.00 | 0.00 |
| August | 264.65 | 114.58 | 150.06 | 305.28 | 105.71 | 0.00 | 0.00 | 0.00 |
| September | 212.32 | 95.21 | 117.11 | 221.50 | 151.85 | 0.00 | 0.00 | 0.00 |
| October | 113.26 | 40.73 | 72.53 | 85.40 | 194.45 | 0.00 | 0.00 | 0.00 |
| November | 61.29 | 17.89 | 43.40 | 30.52 | 226.96 | 0.00 | 0.00 | 0.00 |
| December | 34.69 | 7.32 | 27.37 | 10.11 | 262.87 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 177.18 | 70.44 | 106.74 | 167.75 | 175.23 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34.69 | 7.32 | 27.37 | 10.11 | 96.25 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 315.08 | 138.92 | 182.01 | 360.81 | 262.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 26.35 | 17.22 | 9.12 | 25.74 | 33.67 | 0.00 | 0.00 | 0.00 |
| February | 33.51 | 20.99 | 12.53 | 33.35 | 33.19 | 0.00 | 0.00 | 0.00 |
| March | 20.37 | 6.25 | 14.12 | 15.07 | 27.59 | 0.00 | 0.00 | 0.00 |
| April | 42.37 | 20.14 | 22.23 | 46.32 | 25.84 | 0.00 | 0.00 | 0.00 |
| May | 34.41 | 12.00 | 22.41 | 33.46 | 23.70 | 0.00 | 0.00 | 0.00 |
| June | 31.32 | 8.22 | 23.10 | 31.97 | 18.05 | 0.00 | 0.00 | 0.00 |
| July | 34.18 | 11.52 | 22.66 | 40.06 | 15.21 | 0.00 | 0.00 | 0.00 |
| August | 40.77 | 19.39 | 21.38 | 51.34 | 16.21 | 0.00 | 0.00 | 0.00 |
| September | 49.06 | 29.84 | 19.22 | 59.62 | 22.79 | 0.00 | 0.00 | 0.00 |
| October | 33.82 | 20.39 | 13.43 | 36.09 | 28.70 | 0.00 | 0.00 | 0.00 |
| November | 23.57 | 14.64 | 8.94 | 22.87 | 32.91 | 0.00 | 0.00 | 0.00 |
| December | 17.57 | 11.32 | 6.25 | 16.66 | 38.16 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 32.22 | 15.93 | 16.29 | 34.33 | 26.30 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 17.57 | 6.25 | 6.25 | 15.07 | 15.21 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 49.06 | 29.84 | 23.10 | 59.62 | 38.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 179.44 | 118.59 | 60.86 | 174.78 | 232.59 | 0.00 | 0.00 | 0.00 |
| February | 229.49 | 145.66 | 83.83 | 228.27 | 229.37 | 0.00 | 0.00 | 0.00 |
| March | 137.71 | 43.36 | 94.34 | 100.85 | 191.02 | 0.00 | 0.00 | 0.00 |
| April | 286.65 | 139.79 | 146.86 | 312.96 | 179.02 | 0.00 | 0.00 | 0.00 |
| May | 230.57 | 83.28 | 147.29 | 223.43 | 165.42 | 0.00 | 0.00 | 0.00 |
| June | 208.49 | 57.04 | 151.45 | 211.42 | 125.96 | 0.00 | 0.00 | 0.00 |
| July | 228.43 | 79.96 | 148.47 | 267.34 | 105.57 | 0.00 | 0.00 | 0.00 |
| August | 275.05 | 134.58 | 140.46 | 346.99 | 111.49 | 0.00 | 0.00 | 0.00 |
| September | 334.12 | 207.10 | 127.03 | 406.39 | 156.87 | 0.00 | 0.00 | 0.00 |
| October | 231.04 | 141.51 | 89.52 | 246.58 | 197.93 | 0.00 | 0.00 | 0.00 |
| November | 161.34 | 101.44 | 59.90 | 156.59 | 227.40 | 0.00 | 0.00 | 0.00 |
| December | 119.20 | 77.62 | 41.59 | 112.90 | 263.86 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 218.05 | 110.37 | 107.68 | 231.98 | 181.93 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 119.20 | 43.36 | 41.59 | 100.85 | 105.57 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 334.12 | 207.10 | 151.45 | 406.39 | 263.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 312.92 | 208.52 | 104.40 | 302.61 | 466.74 | 0.00 | 0.00 | 0.00 |
| February | 417.68 | 266.67 | 151.01 | 408.44 | 455.30 | 0.00 | 0.00 | 0.00 |
| March | 250.20 | 79.67 | 170.53 | 174.65 | 382.88 | 0.00 | 0.00 | 0.00 |
| April | 521.06 | 256.87 | 264.19 | 562.68 | 351.62 | 0.00 | 0.00 | 0.00 |
| May | 417.37 | 153.03 | 264.33 | 398.63 | 324.35 | 0.00 | 0.00 | 0.00 |
| June | 376.31 | 104.82 | 271.49 | 378.92 | 241.60 | 0.00 | 0.00 | 0.00 |
| July | 413.01 | 146.92 | 266.08 | 486.47 | 197.15 | 0.00 | 0.00 | 0.00 |
| August | 499.36 | 247.30 | 252.06 | 632.93 | 208.78 | 0.00 | 0.00 | 0.00 |
| September | 609.10 | 380.55 | 228.56 | 738.80 | 302.01 | 0.00 | 0.00 | 0.00 |
| October | 420.91 | 259.43 | 161.48 | 443.74 | 391.56 | 0.00 | 0.00 | 0.00 |
| November | 291.27 | 184.34 | 106.93 | 279.06 | 453.04 | 0.00 | 0.00 | 0.00 |
| December | 216.30 | 141.78 | 74.51 | 202.33 | 524.11 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 394.68 | 201.64 | 193.04 | 416.72 | 357.69 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 216.30 | 79.67 | 74.51 | 174.65 | 197.15 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 609.10 | 380.55 | 271.49 | 738.80 | 524.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 312.44 | 208.26 | 104.18 | 302.57 | 467.39 | 0.00 | 0.00 | 0.00 |
| February | 415.64 | 265.41 | 150.22 | 407.94 | 458.07 | 0.00 | 0.00 | 0.00 |
| March | 250.07 | 79.64 | 170.43 | 174.62 | 383.05 | 0.00 | 0.00 | 0.00 |
| April | 521.00 | 256.87 | 264.13 | 562.61 | 351.61 | 0.00 | 0.00 | 0.00 |
| May | 417.30 | 153.03 | 264.26 | 398.56 | 324.36 | 0.00 | 0.00 | 0.00 |
| June | 376.23 | 104.82 | 271.42 | 378.83 | 241.60 | 0.00 | 0.00 | 0.00 |
| July | 412.94 | 146.92 | 266.01 | 486.39 | 197.15 | 0.00 | 0.00 | 0.00 |
| August | 499.29 | 247.30 | 251.99 | 632.85 | 208.77 | 0.00 | 0.00 | 0.00 |
| September | 608.91 | 380.46 | 228.45 | 738.73 | 302.24 | 0.00 | 0.00 | 0.00 |
| October | 420.24 | 259.04 | 161.20 | 443.67 | 392.61 | 0.00 | 0.00 | 0.00 |
| November | 290.56 | 183.93 | 106.63 | 278.97 | 454.00 | 0.00 | 0.00 | 0.00 |
| December | 216.28 | 141.78 | 74.50 | 202.32 | 524.10 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 394.31 | 201.45 | 192.86 | 416.62 | 358.16 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 216.28 | 79.64 | 74.50 | 174.62 | 197.15 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 608.91 | 380.46 | 271.42 | 738.73 | 524.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 287.95 | 190.19 | 97.76 | 271.98 | 468.12 | 0.00 | 0.00 | 0.00 |
| February | 387.19 | 246.74 | 140.44 | 374.18 | 462.11 | 0.00 | 0.00 | 0.00 |
| March | 235.76 | 74.75 | 161.01 | 159.83 | 386.47 | 0.00 | 0.00 | 0.00 |
| April | 498.74 | 247.23 | 251.51 | 532.78 | 352.36 | 0.00 | 0.00 | 0.00 |
| May | 401.66 | 149.28 | 252.38 | 379.70 | 325.37 | 0.00 | 0.00 | 0.00 |
| June | 362.09 | 102.74 | 259.35 | 361.60 | 241.95 | 0.00 | 0.00 | 0.00 |
| July | 398.02 | 143.74 | 254.28 | 467.06 | 196.51 | 0.00 | 0.00 | 0.00 |
| August | 479.97 | 239.41 | 240.56 | 605.99 | 207.20 | 0.00 | 0.00 | 0.00 |
| September | 577.31 | 361.25 | 216.07 | 695.55 | 303.11 | 0.00 | 0.00 | 0.00 |
| October | 390.92 | 239.79 | 151.13 | 407.41 | 395.82 | 0.00 | 0.00 | 0.00 |
| November | 269.83 | 169.95 | 99.88 | 254.15 | 455.26 | 0.00 | 0.00 | 0.00 |
| December | 199.83 | 130.15 | 69.69 | 182.48 | 524.04 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 373.42 | 190.49 | 182.92 | 390.43 | 359.26 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 199.83 | 74.75 | 69.69 | 159.83 | 196.51 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 577.31 | 361.25 | 259.35 | 695.55 | 524.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.55 | 7.12 | 14.43 | 11.21 | 83.63 | 0.00 | 0.00 | 0.00 |
| February | 38.15 | 16.11 | 22.04 | 27.38 | 81.40 | 0.00 | 0.00 | 0.00 |
| March | 34.50 | 6.60 | 27.90 | 16.60 | 66.45 | 0.00 | 0.00 | 0.00 |
| April | 81.39 | 32.33 | 49.06 | 77.07 | 58.12 | 0.00 | 0.00 | 0.00 |
| May | 95.49 | 38.83 | 56.66 | 88.37 | 52.62 | 0.00 | 0.00 | 0.00 |
| June | 103.12 | 42.45 | 60.67 | 106.87 | 40.57 | 0.00 | 0.00 | 0.00 |
| July | 105.03 | 46.31 | 58.72 | 119.87 | 33.49 | 0.00 | 0.00 | 0.00 |
| August | 88.22 | 38.20 | 50.02 | 102.48 | 35.76 | 0.00 | 0.00 | 0.00 |
| September | 70.77 | 31.74 | 39.04 | 74.71 | 51.92 | 0.00 | 0.00 | 0.00 |
| October | 37.75 | 13.58 | 24.18 | 28.83 | 68.48 | 0.00 | 0.00 | 0.00 |
| November | 20.43 | 5.96 | 14.47 | 10.32 | 80.59 | 0.00 | 0.00 | 0.00 |
| December | 11.56 | 2.44 | 9.12 | 3.34 | 95.53 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 59.06 | 23.48 | 35.58 | 55.69 | 62.27 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11.56 | 2.44 | 9.12 | 3.34 | 33.49 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 105.03 | 46.31 | 60.67 | 119.87 | 95.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 64.64 | 21.36 | 43.28 | 36.41 | 226.74 | 0.00 | 0.00 | 0.00 |
| February | 114.45 | 48.32 | 66.13 | 86.79 | 216.30 | 0.00 | 0.00 | 0.00 |
| March | 103.49 | 19.80 | 83.69 | 55.20 | 178.12 | 0.00 | 0.00 | 0.00 |
| April | 244.18 | 96.99 | 147.19 | 241.85 | 154.50 | 0.00 | 0.00 | 0.00 |
| May | 286.48 | 116.49 | 169.99 | 276.44 | 139.04 | 0.00 | 0.00 | 0.00 |
| June | 309.37 | 127.36 | 182.01 | 330.30 | 109.75 | 0.00 | 0.00 | 0.00 |
| July | 315.08 | 138.92 | 176.16 | 368.36 | 91.45 | 0.00 | 0.00 | 0.00 |
| August | 264.65 | 114.58 | 150.06 | 316.40 | 96.52 | 0.00 | 0.00 | 0.00 |
| September | 212.32 | 95.21 | 117.11 | 232.48 | 138.53 | 0.00 | 0.00 | 0.00 |
| October | 113.26 | 40.73 | 72.53 | 92.36 | 181.76 | 0.00 | 0.00 | 0.00 |
| November | 61.29 | 17.89 | 43.40 | 33.42 | 216.50 | 0.00 | 0.00 | 0.00 |
| December | 34.69 | 7.32 | 27.37 | 11.06 | 257.33 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 177.18 | 70.44 | 106.74 | 173.74 | 166.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34.69 | 7.32 | 27.37 | 11.06 | 91.45 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 315.08 | 138.92 | 182.01 | 368.36 | 257.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.09 | 0.00 | 4.09 | 0.06 | 37.00 | 0.00 | 0.00 | 0.00 |
| February | 6.39 | 0.00 | 6.39 | 0.20 | 35.30 | 0.00 | 0.00 | 0.00 |
| March | 9.12 | 0.00 | 9.12 | 1.31 | 28.83 | 0.00 | 0.00 | 0.00 |
| April | 14.17 | 0.07 | 14.11 | 5.56 | 24.36 | 0.00 | 0.00 | 0.00 |
| May | 18.02 | 0.93 | 17.09 | 6.56 | 20.63 | 0.00 | 0.00 | 0.00 |
| June | 20.04 | 1.39 | 18.65 | 12.40 | 15.82 | 0.00 | 0.00 | 0.00 |
| July | 18.82 | 1.18 | 17.64 | 15.06 | 13.01 | 0.00 | 0.00 | 0.00 |
| August | 14.44 | 0.24 | 14.20 | 11.66 | 13.85 | 0.00 | 0.00 | 0.00 |
| September | 10.88 | 0.00 | 10.88 | 5.80 | 21.18 | 0.00 | 0.00 | 0.00 |
| October | 7.17 | 0.00 | 7.17 | 1.09 | 28.28 | 0.00 | 0.00 | 0.00 |
| November | 4.35 | 0.00 | 4.35 | 0.04 | 34.37 | 0.00 | 0.00 | 0.00 |
| December | 2.97 | 0.00 | 2.97 | 0.00 | 39.94 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 10.89 | 0.32 | 10.57 | 5.01 | 25.99 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 2.97 | 0.00 | 2.97 | 0.00 | 13.01 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 20.04 | 1.39 | 18.65 | 15.06 | 39.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 29.83 | 0.00 | 29.83 | 0.63 | 255.82 | 0.00 | 0.00 | 0.00 |
| February | 46.56 | 0.00 | 46.56 | 1.91 | 243.09 | 0.00 | 0.00 | 0.00 |
| March | 65.96 | 0.00 | 65.96 | 10.90 | 199.43 | 0.00 | 0.00 | 0.00 |
| April | 103.69 | 0.47 | 103.22 | 44.38 | 168.70 | 0.00 | 0.00 | 0.00 |
| May | 130.97 | 6.45 | 124.52 | 52.02 | 142.91 | 0.00 | 0.00 | 0.00 |
| June | 145.43 | 9.63 | 135.80 | 93.96 | 110.27 | 0.00 | 0.00 | 0.00 |
| July | 136.96 | 8.19 | 128.77 | 112.42 | 91.00 | 0.00 | 0.00 | 0.00 |
| August | 105.89 | 1.68 | 104.21 | 87.97 | 97.04 | 0.00 | 0.00 | 0.00 |
| September | 80.09 | 0.01 | 80.08 | 45.52 | 147.42 | 0.00 | 0.00 | 0.00 |
| October | 52.37 | 0.00 | 52.37 | 9.72 | 196.03 | 0.00 | 0.00 | 0.00 |
| November | 31.71 | 0.00 | 31.71 | 0.45 | 237.75 | 0.00 | 0.00 | 0.00 |
| December | 21.61 | 0.00 | 21.61 | 0.00 | 277.14 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 79.41 | 2.22 | 77.19 | 38.54 | 180.19 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21.61 | 0.00 | 21.61 | 0.00 | 91.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 145.43 | 9.63 | 135.80 | 112.42 | 277.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 49.03 | 0.00 | 49.03 | 0.23 | 505.13 | 0.00 | 0.00 | 0.00 |
| February | 76.61 | 0.00 | 76.61 | 1.06 | 488.74 | 0.00 | 0.00 | 0.00 |
| March | 109.68 | 0.00 | 109.68 | 8.85 | 404.34 | 0.00 | 0.00 | 0.00 |
| April | 168.74 | 0.28 | 168.46 | 55.64 | 336.20 | 0.00 | 0.00 | 0.00 |
| May | 209.52 | 6.70 | 202.82 | 64.29 | 293.58 | 0.00 | 0.00 | 0.00 |
| June | 232.89 | 13.04 | 219.85 | 133.89 | 217.10 | 0.00 | 0.00 | 0.00 |
| July | 218.60 | 10.39 | 208.20 | 173.48 | 174.25 | 0.00 | 0.00 | 0.00 |
| August | 170.29 | 1.31 | 168.98 | 139.12 | 183.57 | 0.00 | 0.00 | 0.00 |
| September | 130.34 | 0.01 | 130.33 | 64.11 | 281.47 | 0.00 | 0.00 | 0.00 |
| October | 85.91 | 0.00 | 85.91 | 7.84 | 389.77 | 0.00 | 0.00 | 0.00 |
| November | 52.14 | 0.00 | 52.14 | 0.08 | 474.91 | 0.00 | 0.00 | 0.00 |
| December | 35.53 | 0.00 | 35.53 | 0.00 | 548.45 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 128.50 | 2.66 | 125.84 | 54.38 | 357.39 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.53 | 0.00 | 35.53 | 0.00 | 174.25 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 232.89 | 13.04 | 219.85 | 173.48 | 548.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 52.01 | 0.00 | 52.01 | 0.43 | 504.36 | 0.00 | 0.00 | 0.00 |
| February | 81.19 | 0.00 | 81.19 | 1.59 | 486.28 | 0.00 | 0.00 | 0.00 |
| March | 116.02 | 0.00 | 116.02 | 12.06 | 401.58 | 0.00 | 0.00 | 0.00 |
| April | 179.57 | 0.65 | 178.92 | 64.81 | 333.23 | 0.00 | 0.00 | 0.00 |
| May | 226.54 | 10.47 | 216.07 | 77.13 | 284.34 | 0.00 | 0.00 | 0.00 |
| June | 252.00 | 17.73 | 234.27 | 155.44 | 213.59 | 0.00 | 0.00 | 0.00 |
| July | 236.35 | 14.36 | 221.99 | 193.71 | 171.73 | 0.00 | 0.00 | 0.00 |
| August | 182.54 | 2.66 | 179.88 | 150.57 | 181.45 | 0.00 | 0.00 | 0.00 |
| September | 138.14 | 0.01 | 138.13 | 71.45 | 282.76 | 0.00 | 0.00 | 0.00 |
| October | 91.07 | 0.00 | 91.07 | 10.53 | 389.28 | 0.00 | 0.00 | 0.00 |
| November | 55.31 | 0.00 | 55.31 | 0.20 | 474.03 | 0.00 | 0.00 | 0.00 |
| December | 37.70 | 0.00 | 37.70 | 0.00 | 548.90 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 137.63 | 3.85 | 133.78 | 61.86 | 355.22 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 37.70 | 0.00 | 37.70 | 0.00 | 171.73 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 252.00 | 17.73 | 234.27 | 193.71 | 548.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 52.01 | 0.00 | 52.01 | 0.43 | 504.35 | 0.00 | 0.00 | 0.00 |
| February | 81.18 | 0.00 | 81.18 | 1.59 | 486.27 | 0.00 | 0.00 | 0.00 |
| March | 116.02 | 0.00 | 116.02 | 12.06 | 401.57 | 0.00 | 0.00 | 0.00 |
| April | 180.03 | 0.84 | 179.19 | 64.83 | 332.38 | 0.00 | 0.00 | 0.00 |
| May | 228.15 | 11.37 | 216.78 | 77.45 | 282.15 | 0.00 | 0.00 | 0.00 |
| June | 252.81 | 17.73 | 235.08 | 155.50 | 212.46 | 0.00 | 0.00 | 0.00 |
| July | 237.62 | 14.73 | 222.89 | 193.98 | 170.08 | 0.00 | 0.00 | 0.00 |
| August | 183.40 | 3.07 | 180.32 | 150.76 | 180.22 | 0.00 | 0.00 | 0.00 |
| September | 138.20 | 0.02 | 138.18 | 71.45 | 282.64 | 0.00 | 0.00 | 0.00 |
| October | 91.07 | 0.00 | 91.07 | 10.53 | 389.27 | 0.00 | 0.00 | 0.00 |
| November | 55.31 | 0.00 | 55.31 | 0.20 | 474.02 | 0.00 | 0.00 | 0.00 |
| December | 37.70 | 0.00 | 37.70 | 0.00 | 548.89 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 138.05 | 4.01 | 134.05 | 61.93 | 354.61 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 37.70 | 0.00 | 37.70 | 0.00 | 170.08 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 252.81 | 17.73 | 235.08 | 193.98 | 548.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 64.64 | 21.36 | 43.28 | 33.20 | 236.32 | 0.00 | 0.00 | 0.00 |
| February | 114.45 | 48.32 | 66.13 | 81.45 | 228.90 | 0.00 | 0.00 | 0.00 |
| March | 103.49 | 19.80 | 83.69 | 52.29 | 183.23 | 0.00 | 0.00 | 0.00 |
| April | 244.18 | 96.99 | 147.19 | 231.55 | 165.38 | 0.00 | 0.00 | 0.00 |
| May | 286.48 | 116.49 | 169.99 | 269.46 | 145.58 | 0.00 | 0.00 | 0.00 |
| June | 309.37 | 127.36 | 182.01 | 325.64 | 113.20 | 0.00 | 0.00 | 0.00 |
| July | 315.08 | 138.92 | 176.16 | 359.99 | 97.04 | 0.00 | 0.00 | 0.00 |
| August | 264.65 | 114.58 | 150.06 | 304.66 | 106.43 | 0.00 | 0.00 | 0.00 |
| September | 212.32 | 95.21 | 117.11 | 221.08 | 152.64 | 0.00 | 0.00 | 0.00 |
| October | 113.26 | 40.73 | 72.53 | 85.13 | 195.47 | 0.00 | 0.00 | 0.00 |
| November | 61.29 | 17.89 | 43.40 | 30.36 | 228.16 | 0.00 | 0.00 | 0.00 |
| December | 34.69 | 7.32 | 27.37 | 10.05 | 263.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 177.18 | 70.44 | 106.74 | 167.39 | 176.03 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34.69 | 7.32 | 27.37 | 10.05 | 97.04 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 315.08 | 138.92 | 182.01 | 359.99 | 263.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 26.76 | 17.53 | 9.23 | 26.14 | 33.69 | 0.00 | 0.00 | 0.00 |
| February | 33.63 | 21.03 | 12.60 | 33.42 | 33.24 | 0.00 | 0.00 | 0.00 |
| March | 20.44 | 6.25 | 14.19 | 15.10 | 27.71 | 0.00 | 0.00 | 0.00 |
| April | 42.51 | 20.14 | 22.37 | 46.42 | 25.98 | 0.00 | 0.00 | 0.00 |
| May | 34.57 | 12.00 | 22.57 | 33.57 | 23.81 | 0.00 | 0.00 | 0.00 |
| June | 31.49 | 8.22 | 23.27 | 32.10 | 18.14 | 0.00 | 0.00 | 0.00 |
| July | 34.35 | 11.52 | 22.83 | 40.15 | 15.36 | 0.00 | 0.00 | 0.00 |
| August | 40.92 | 19.39 | 21.53 | 51.43 | 16.34 | 0.00 | 0.00 | 0.00 |
| September | 49.18 | 29.84 | 19.34 | 59.69 | 22.94 | 0.00 | 0.00 | 0.00 |
| October | 33.91 | 20.40 | 13.50 | 36.13 | 28.85 | 0.00 | 0.00 | 0.00 |
| November | 23.76 | 14.74 | 9.01 | 23.00 | 33.03 | 0.00 | 0.00 | 0.00 |
| December | 18.04 | 11.66 | 6.38 | 17.15 | 38.17 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 32.41 | 16.00 | 16.41 | 34.47 | 26.40 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.04 | 6.25 | 6.38 | 15.10 | 15.36 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 49.18 | 29.84 | 23.27 | 59.69 | 38.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 183.74 | 121.51 | 62.22 | 179.38 | 232.75 | 0.00 | 0.00 | 0.00 |
| February | 230.64 | 145.95 | 84.68 | 229.10 | 229.85 | 0.00 | 0.00 | 0.00 |
| March | 138.58 | 43.36 | 95.21 | 101.47 | 191.87 | 0.00 | 0.00 | 0.00 |
| April | 288.41 | 139.79 | 148.62 | 314.50 | 180.06 | 0.00 | 0.00 | 0.00 |
| May | 232.53 | 83.28 | 149.25 | 225.10 | 166.09 | 0.00 | 0.00 | 0.00 |
| June | 210.60 | 57.04 | 153.56 | 213.42 | 126.53 | 0.00 | 0.00 | 0.00 |
| July | 230.52 | 79.96 | 150.56 | 269.03 | 106.60 | 0.00 | 0.00 | 0.00 |
| August | 276.92 | 134.58 | 142.34 | 348.61 | 112.56 | 0.00 | 0.00 | 0.00 |
| September | 335.64 | 207.10 | 128.54 | 407.68 | 158.00 | 0.00 | 0.00 | 0.00 |
| October | 232.05 | 141.61 | 90.44 | 247.27 | 199.15 | 0.00 | 0.00 | 0.00 |
| November | 162.96 | 102.30 | 60.67 | 157.87 | 228.32 | 0.00 | 0.00 | 0.00 |
| December | 123.52 | 80.67 | 42.85 | 117.50 | 263.84 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 220.11 | 110.98 | 109.13 | 233.86 | 182.69 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 123.52 | 43.36 | 42.85 | 101.47 | 106.60 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 335.64 | 207.10 | 153.56 | 407.68 | 263.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 323.43 | 215.56 | 107.87 | 312.50 | 465.75 | 0.00 | 0.00 | 0.00 |
| February | 420.59 | 267.74 | 152.85 | 410.26 | 456.34 | 0.00 | 0.00 | 0.00 |
| March | 251.73 | 79.68 | 172.05 | 175.24 | 385.58 | 0.00 | 0.00 | 0.00 |
| April | 524.13 | 256.89 | 267.24 | 564.88 | 354.49 | 0.00 | 0.00 | 0.00 |
| May | 420.78 | 153.04 | 267.74 | 401.17 | 326.20 | 0.00 | 0.00 | 0.00 |
| June | 379.98 | 104.82 | 275.16 | 381.98 | 243.12 | 0.00 | 0.00 | 0.00 |
| July | 416.65 | 146.93 | 269.71 | 488.83 | 199.61 | 0.00 | 0.00 | 0.00 |
| August | 502.63 | 247.32 | 255.31 | 635.22 | 211.33 | 0.00 | 0.00 | 0.00 |
| September | 611.76 | 380.58 | 231.18 | 740.60 | 304.89 | 0.00 | 0.00 | 0.00 |
| October | 422.98 | 259.83 | 163.15 | 444.81 | 395.09 | 0.00 | 0.00 | 0.00 |
| November | 295.61 | 186.72 | 108.89 | 282.08 | 455.50 | 0.00 | 0.00 | 0.00 |
| December | 224.62 | 147.68 | 76.94 | 210.62 | 524.32 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 398.82 | 203.06 | 195.75 | 419.98 | 359.62 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 224.62 | 79.68 | 76.94 | 175.24 | 199.61 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 611.76 | 380.58 | 275.16 | 740.60 | 524.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 322.30 | 214.91 | 107.39 | 312.35 | 467.24 | 0.00 | 0.00 | 0.00 |
| February | 418.46 | 266.41 | 152.05 | 409.74 | 459.19 | 0.00 | 0.00 | 0.00 |
| March | 251.61 | 79.64 | 171.97 | 175.23 | 385.73 | 0.00 | 0.00 | 0.00 |
| April | 524.10 | 256.87 | 267.23 | 564.85 | 354.46 | 0.00 | 0.00 | 0.00 |
| May | 420.75 | 153.03 | 267.72 | 401.14 | 326.18 | 0.00 | 0.00 | 0.00 |
| June | 379.95 | 104.82 | 275.14 | 381.95 | 243.11 | 0.00 | 0.00 | 0.00 |
| July | 416.62 | 146.92 | 269.69 | 488.80 | 199.60 | 0.00 | 0.00 | 0.00 |
| August | 502.60 | 247.30 | 255.30 | 635.17 | 211.31 | 0.00 | 0.00 | 0.00 |
| September | 611.62 | 380.49 | 231.12 | 740.54 | 305.05 | 0.00 | 0.00 | 0.00 |
| October | 422.29 | 259.39 | 162.90 | 444.71 | 396.10 | 0.00 | 0.00 | 0.00 |
| November | 294.70 | 186.17 | 108.53 | 281.92 | 456.69 | 0.00 | 0.00 | 0.00 |
| December | 224.59 | 147.66 | 76.92 | 210.60 | 524.30 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 398.39 | 202.81 | 195.58 | 419.89 | 360.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 224.59 | 79.64 | 76.92 | 175.23 | 199.60 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 611.62 | 380.49 | 275.14 | 740.54 | 524.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 295.13 | 194.88 | 100.25 | 278.63 | 468.33 | 0.00 | 0.00 | 0.00 |
| February | 388.91 | 247.23 | 141.68 | 375.11 | 463.73 | 0.00 | 0.00 | 0.00 |
| March | 236.84 | 74.75 | 162.09 | 160.00 | 389.10 | 0.00 | 0.00 | 0.00 |
| April | 500.90 | 247.22 | 253.68 | 533.95 | 355.17 | 0.00 | 0.00 | 0.00 |
| May | 404.07 | 149.27 | 254.80 | 381.18 | 327.24 | 0.00 | 0.00 | 0.00 |
| June | 364.69 | 102.74 | 261.95 | 363.45 | 243.46 | 0.00 | 0.00 | 0.00 |
| July | 400.59 | 143.73 | 256.85 | 468.17 | 198.90 | 0.00 | 0.00 | 0.00 |
| August | 482.27 | 239.40 | 242.87 | 607.13 | 209.60 | 0.00 | 0.00 | 0.00 |
| September | 579.18 | 361.24 | 217.94 | 696.42 | 305.79 | 0.00 | 0.00 | 0.00 |
| October | 392.32 | 240.01 | 152.31 | 407.84 | 399.30 | 0.00 | 0.00 | 0.00 |
| November | 272.58 | 171.35 | 101.23 | 255.65 | 458.18 | 0.00 | 0.00 | 0.00 |
| December | 205.60 | 134.18 | 71.41 | 187.65 | 524.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 376.25 | 191.40 | 184.85 | 392.32 | 361.33 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 205.60 | 74.75 | 71.41 | 160.00 | 198.90 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 579.18 | 361.24 | 261.95 | 696.42 | 524.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.55 | 7.12 | 14.43 | 11.13 | 84.22 | 0.00 | 0.00 | 0.00 |
| February | 38.15 | 16.11 | 22.04 | 27.24 | 82.08 | 0.00 | 0.00 | 0.00 |
| March | 34.50 | 6.60 | 27.90 | 16.32 | 67.32 | 0.00 | 0.00 | 0.00 |
| April | 81.39 | 32.33 | 49.06 | 76.51 | 59.08 | 0.00 | 0.00 | 0.00 |
| May | 95.49 | 38.83 | 56.66 | 87.85 | 53.40 | 0.00 | 0.00 | 0.00 |
| June | 103.12 | 42.45 | 60.67 | 106.35 | 41.21 | 0.00 | 0.00 | 0.00 |
| July | 105.03 | 46.31 | 58.72 | 118.98 | 34.31 | 0.00 | 0.00 | 0.00 |
| August | 88.22 | 38.20 | 50.02 | 101.77 | 36.54 | 0.00 | 0.00 | 0.00 |
| September | 70.77 | 31.74 | 39.04 | 74.23 | 52.83 | 0.00 | 0.00 | 0.00 |
| October | 37.75 | 13.58 | 24.18 | 28.54 | 69.66 | 0.00 | 0.00 | 0.00 |
| November | 20.43 | 5.96 | 14.47 | 10.18 | 81.76 | 0.00 | 0.00 | 0.00 |
| December | 11.56 | 2.44 | 9.12 | 3.31 | 96.18 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 59.06 | 23.48 | 35.58 | 55.30 | 63.11 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11.56 | 2.44 | 9.12 | 3.31 | 34.31 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 105.03 | 46.31 | 60.67 | 118.98 | 96.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.01 | 0.00 | 5.01 | 0.22 | 36.89 | 0.00 | 0.00 | 0.00 |
| February | 7.82 | 0.00 | 7.82 | 0.65 | 34.86 | 0.00 | 0.00 | 0.00 |
| March | 10.82 | 0.00 | 10.82 | 2.54 | 28.74 | 0.00 | 0.00 | 0.00 |
| April | 17.61 | 0.08 | 17.53 | 9.08 | 24.47 | 0.00 | 0.00 | 0.00 |
| May | 22.02 | 1.06 | 20.96 | 10.63 | 20.56 | 0.00 | 0.00 | 0.00 |
| June | 24.34 | 1.53 | 22.82 | 17.26 | 16.06 | 0.00 | 0.00 | 0.00 |
| July | 23.09 | 1.32 | 21.77 | 19.84 | 13.42 | 0.00 | 0.00 | 0.00 |
| August | 18.15 | 0.28 | 17.86 | 15.85 | 14.51 | 0.00 | 0.00 | 0.00 |
| September | 13.81 | 0.00 | 13.81 | 8.81 | 21.78 | 0.00 | 0.00 | 0.00 |
| October | 8.85 | 0.00 | 8.85 | 2.40 | 28.63 | 0.00 | 0.00 | 0.00 |
| November | 5.32 | 0.00 | 5.32 | 0.20 | 34.33 | 0.00 | 0.00 | 0.00 |
| December | 3.62 | 0.00 | 3.62 | 0.00 | 40.08 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 13.40 | 0.36 | 13.04 | 7.33 | 26.14 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3.62 | 0.00 | 3.62 | 0.00 | 13.42 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 24.34 | 1.53 | 22.82 | 19.84 | 40.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 64.64 | 21.36 | 43.28 | 36.31 | 227.06 | 0.00 | 0.00 | 0.00 |
| February | 114.45 | 48.32 | 66.13 | 86.57 | 216.81 | 0.00 | 0.00 | 0.00 |
| March | 103.49 | 19.80 | 83.69 | 54.81 | 178.88 | 0.00 | 0.00 | 0.00 |
| April | 244.18 | 96.99 | 147.19 | 240.62 | 155.86 | 0.00 | 0.00 | 0.00 |
| May | 286.48 | 116.49 | 169.99 | 275.08 | 140.29 | 0.00 | 0.00 | 0.00 |
| June | 309.37 | 127.36 | 182.01 | 328.89 | 110.85 | 0.00 | 0.00 | 0.00 |
| July | 315.08 | 138.92 | 176.16 | 366.54 | 92.78 | 0.00 | 0.00 | 0.00 |
| August | 264.65 | 114.58 | 150.06 | 315.17 | 97.52 | 0.00 | 0.00 | 0.00 |
| September | 212.32 | 95.21 | 117.11 | 231.55 | 139.62 | 0.00 | 0.00 | 0.00 |
| October | 113.26 | 40.73 | 72.53 | 91.90 | 182.76 | 0.00 | 0.00 | 0.00 |
| November | 61.29 | 17.89 | 43.40 | 33.25 | 217.32 | 0.00 | 0.00 | 0.00 |
| December | 34.69 | 7.32 | 27.37 | 11.03 | 257.55 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 177.18 | 70.44 | 106.74 | 172.96 | 167.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34.69 | 7.32 | 27.37 | 11.03 | 92.78 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 315.08 | 138.92 | 182.01 | 366.54 | 257.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 34.60 | 0.00 | 34.60 | 1.59 | 254.41 | 0.00 | 0.00 | 0.00 |
| February | 54.04 | 0.00 | 54.04 | 4.59 | 240.21 | 0.00 | 0.00 | 0.00 |
| March | 74.78 | 0.00 | 74.78 | 17.62 | 198.57 | 0.00 | 0.00 | 0.00 |
| April | 121.75 | 0.54 | 121.20 | 63.01 | 169.12 | 0.00 | 0.00 | 0.00 |
| May | 152.22 | 7.34 | 144.87 | 73.61 | 142.11 | 0.00 | 0.00 | 0.00 |
| June | 168.26 | 10.55 | 157.71 | 119.40 | 110.99 | 0.00 | 0.00 | 0.00 |
| July | 159.61 | 9.10 | 150.51 | 137.28 | 92.76 | 0.00 | 0.00 | 0.00 |
| August | 125.46 | 1.97 | 123.49 | 109.85 | 100.31 | 0.00 | 0.00 | 0.00 |
| September | 95.49 | 0.02 | 95.47 | 61.39 | 150.44 | 0.00 | 0.00 | 0.00 |
| October | 61.19 | 0.00 | 61.19 | 16.84 | 197.62 | 0.00 | 0.00 | 0.00 |
| November | 36.77 | 0.00 | 36.77 | 1.43 | 236.96 | 0.00 | 0.00 | 0.00 |
| December | 25.04 | 0.00 | 25.04 | 0.01 | 276.87 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 92.60 | 2.48 | 90.13 | 50.81 | 180.53 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.04 | 0.00 | 25.04 | 0.01 | 92.76 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 168.26 | 10.55 | 157.71 | 137.28 | 276.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.16 | 0.00 | 42.16 | 1.25 | 331.77 | 0.00 | 0.00 | 0.00 |
| February | 65.83 | 0.00 | 65.83 | 3.89 | 316.51 | 0.00 | 0.00 | 0.00 |
| March | 91.10 | 0.00 | 91.10 | 17.25 | 263.79 | 0.00 | 0.00 | 0.00 |
| April | 148.32 | 0.66 | 147.66 | 72.04 | 220.26 | 0.00 | 0.00 | 0.00 |
| May | 185.44 | 8.95 | 176.50 | 84.91 | 184.72 | 0.00 | 0.00 | 0.00 |
| June | 205.00 | 12.85 | 192.14 | 143.64 | 141.25 | 0.00 | 0.00 | 0.00 |
| July | 194.45 | 11.09 | 183.36 | 168.90 | 115.10 | 0.00 | 0.00 | 0.00 |
| August | 152.85 | 2.39 | 150.45 | 135.07 | 124.63 | 0.00 | 0.00 | 0.00 |
| September | 116.34 | 0.03 | 116.31 | 72.32 | 191.91 | 0.00 | 0.00 | 0.00 |
| October | 74.55 | 0.00 | 74.55 | 17.19 | 259.71 | 0.00 | 0.00 | 0.00 |
| November | 44.79 | 0.00 | 44.79 | 0.98 | 312.75 | 0.00 | 0.00 | 0.00 |
| December | 30.50 | 0.00 | 30.50 | 0.00 | 363.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 112.82 | 3.02 | 109.80 | 60.11 | 235.04 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.50 | 0.00 | 30.50 | 0.00 | 115.10 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 205.00 | 12.85 | 192.14 | 168.90 | 363.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.16 | 0.00 | 42.16 | 1.25 | 331.77 | 0.00 | 0.00 | 0.00 |
| February | 65.83 | 0.00 | 65.83 | 3.89 | 316.51 | 0.00 | 0.00 | 0.00 |
| March | 91.10 | 0.00 | 91.10 | 17.25 | 263.79 | 0.00 | 0.00 | 0.00 |
| April | 148.32 | 0.66 | 147.66 | 72.04 | 220.26 | 0.00 | 0.00 | 0.00 |
| May | 185.44 | 8.95 | 176.50 | 84.91 | 184.72 | 0.00 | 0.00 | 0.00 |
| June | 205.00 | 12.85 | 192.14 | 143.64 | 141.25 | 0.00 | 0.00 | 0.00 |
| July | 194.45 | 11.09 | 183.36 | 168.90 | 115.10 | 0.00 | 0.00 | 0.00 |
| August | 152.85 | 2.39 | 150.45 | 135.06 | 124.63 | 0.00 | 0.00 | 0.00 |
| September | 116.34 | 0.03 | 116.31 | 72.31 | 191.91 | 0.00 | 0.00 | 0.00 |
| October | 74.55 | 0.00 | 74.55 | 17.19 | 259.71 | 0.00 | 0.00 | 0.00 |
| November | 44.79 | 0.00 | 44.79 | 0.98 | 312.75 | 0.00 | 0.00 | 0.00 |
| December | 30.50 | 0.00 | 30.50 | 0.00 | 363.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 112.82 | 3.02 | 109.80 | 60.11 | 235.04 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.50 | 0.00 | 30.50 | 0.00 | 115.10 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 205.00 | 12.85 | 192.14 | 168.90 | 363.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.16 | 0.00 | 42.16 | 1.25 | 331.76 | 0.00 | 0.00 | 0.00 |
| February | 65.83 | 0.00 | 65.83 | 3.89 | 316.50 | 0.00 | 0.00 | 0.00 |
| March | 91.10 | 0.00 | 91.10 | 17.25 | 263.78 | 0.00 | 0.00 | 0.00 |
| April | 148.32 | 0.66 | 147.66 | 72.04 | 220.25 | 0.00 | 0.00 | 0.00 |
| May | 185.44 | 8.95 | 176.49 | 84.90 | 184.71 | 0.00 | 0.00 | 0.00 |
| June | 204.99 | 12.85 | 192.14 | 143.64 | 141.24 | 0.00 | 0.00 | 0.00 |
| July | 194.44 | 11.09 | 183.36 | 168.89 | 115.09 | 0.00 | 0.00 | 0.00 |
| August | 152.84 | 2.39 | 150.45 | 135.06 | 124.63 | 0.00 | 0.00 | 0.00 |
| September | 116.33 | 0.03 | 116.31 | 72.31 | 191.90 | 0.00 | 0.00 | 0.00 |
| October | 74.55 | 0.00 | 74.55 | 17.19 | 259.70 | 0.00 | 0.00 | 0.00 |
| November | 44.79 | 0.00 | 44.79 | 0.98 | 312.74 | 0.00 | 0.00 | 0.00 |
| December | 30.50 | 0.00 | 30.50 | 0.00 | 363.62 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 112.82 | 3.02 | 109.80 | 60.11 | 235.04 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.50 | 0.00 | 30.50 | 0.00 | 115.09 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 204.99 | 12.85 | 192.14 | 168.89 | 363.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.75 | 0.00 | 4.75 | 0.10 | 39.10 | 0.00 | 0.00 | 0.00 |
| February | 7.42 | 0.00 | 7.42 | 0.33 | 37.78 | 0.00 | 0.00 | 0.00 |
| March | 10.27 | 0.00 | 10.27 | 1.56 | 31.89 | 0.00 | 0.00 | 0.00 |
| April | 16.73 | 0.07 | 16.65 | 7.42 | 26.75 | 0.00 | 0.00 | 0.00 |
| May | 20.91 | 1.01 | 19.90 | 8.75 | 22.38 | 0.00 | 0.00 | 0.00 |
| June | 23.12 | 1.45 | 21.67 | 15.19 | 17.10 | 0.00 | 0.00 | 0.00 |
| July | 21.93 | 1.25 | 20.68 | 17.56 | 14.16 | 0.00 | 0.00 | 0.00 |
| August | 17.24 | 0.27 | 16.97 | 13.97 | 15.40 | 0.00 | 0.00 | 0.00 |
| September | 13.12 | 0.00 | 13.12 | 7.34 | 23.61 | 0.00 | 0.00 | 0.00 |
| October | 8.41 | 0.00 | 8.41 | 1.57 | 31.72 | 0.00 | 0.00 | 0.00 |
| November | 5.05 | 0.00 | 5.05 | 0.06 | 37.80 | 0.00 | 0.00 | 0.00 |
| December | 3.44 | 0.00 | 3.44 | 0.00 | 42.99 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 12.72 | 0.34 | 12.38 | 6.19 | 28.33 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3.44 | 0.00 | 3.44 | 0.00 | 14.16 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 23.12 | 1.45 | 21.67 | 17.56 | 42.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 60.29 | 0.00 | 60.29 | 1.25 | 495.84 | 0.00 | 0.00 | 0.00 |
| February | 94.14 | 0.00 | 94.14 | 4.21 | 479.07 | 0.00 | 0.00 | 0.00 |
| March | 130.28 | 0.00 | 130.28 | 19.77 | 404.36 | 0.00 | 0.00 | 0.00 |
| April | 212.11 | 0.95 | 211.16 | 94.15 | 339.28 | 0.00 | 0.00 | 0.00 |
| May | 265.20 | 12.79 | 252.40 | 110.95 | 283.83 | 0.00 | 0.00 | 0.00 |
| June | 293.16 | 18.38 | 274.77 | 192.65 | 216.82 | 0.00 | 0.00 | 0.00 |
| July | 278.08 | 15.85 | 262.22 | 222.70 | 179.52 | 0.00 | 0.00 | 0.00 |
| August | 218.58 | 3.42 | 215.16 | 177.21 | 195.26 | 0.00 | 0.00 | 0.00 |
| September | 166.37 | 0.04 | 166.33 | 93.06 | 299.36 | 0.00 | 0.00 | 0.00 |
| October | 106.61 | 0.00 | 106.61 | 19.91 | 402.26 | 0.00 | 0.00 | 0.00 |
| November | 64.06 | 0.00 | 64.06 | 0.72 | 479.33 | 0.00 | 0.00 | 0.00 |
| December | 43.62 | 0.00 | 43.62 | 0.00 | 545.13 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 161.34 | 4.32 | 157.02 | 78.47 | 359.31 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 43.62 | 0.00 | 43.62 | 0.00 | 179.52 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 293.16 | 18.38 | 274.77 | 222.70 | 545.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 6.23 | 1.91 | 4.31 | 2.58 | 39.77 | 0.00 | 0.00 | 0.00 |
| February | 14.34 | 6.85 | 7.49 | 10.76 | 38.82 | 0.00 | 0.00 | 0.00 |
| March | 12.65 | 3.13 | 9.52 | 5.56 | 32.36 | 0.00 | 0.00 | 0.00 |
| April | 31.59 | 14.35 | 17.24 | 29.23 | 28.76 | 0.00 | 0.00 | 0.00 |
| May | 32.77 | 14.30 | 18.47 | 28.58 | 28.28 | 0.00 | 0.00 | 0.00 |
| June | 34.32 | 14.64 | 19.68 | 33.40 | 21.72 | 0.00 | 0.00 | 0.00 |
| July | 35.96 | 16.62 | 19.33 | 38.77 | 18.42 | 0.00 | 0.00 | 0.00 |
| August | 33.95 | 16.49 | 17.45 | 38.27 | 18.25 | 0.00 | 0.00 | 0.00 |
| September | 28.89 | 14.86 | 14.02 | 30.66 | 24.58 | 0.00 | 0.00 | 0.00 |
| October | 14.55 | 6.16 | 8.39 | 11.33 | 32.14 | 0.00 | 0.00 | 0.00 |
| November | 7.03 | 2.30 | 4.73 | 3.64 | 37.66 | 0.00 | 0.00 | 0.00 |
| December | 3.68 | 0.80 | 2.88 | 0.89 | 44.48 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 21.34 | 9.37 | 11.98 | 19.49 | 30.39 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3.68 | 0.80 | 2.88 | 0.89 | 18.25 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 35.96 | 16.62 | 19.68 | 38.77 | 44.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.88 | 0.75 | 21.12 | 0.30 | 217.80 | 0.00 | 0.00 | 0.00 |
| February | 45.85 | 10.31 | 35.54 | 12.70 | 208.52 | 0.00 | 0.00 | 0.00 |
| March | 62.39 | 9.94 | 52.45 | 19.10 | 170.58 | 0.00 | 0.00 | 0.00 |
| April | 165.41 | 69.06 | 96.35 | 145.14 | 149.89 | 0.00 | 0.00 | 0.00 |
| May | 199.89 | 87.62 | 112.27 | 175.53 | 142.12 | 0.00 | 0.00 | 0.00 |
| June | 221.23 | 101.04 | 120.19 | 222.14 | 109.87 | 0.00 | 0.00 | 0.00 |
| July | 223.91 | 107.60 | 116.31 | 244.02 | 94.67 | 0.00 | 0.00 | 0.00 |
| August | 182.19 | 83.96 | 98.23 | 200.38 | 96.66 | 0.00 | 0.00 | 0.00 |
| September | 129.73 | 56.50 | 73.22 | 125.05 | 131.41 | 0.00 | 0.00 | 0.00 |
| October | 56.29 | 14.57 | 41.72 | 27.98 | 172.17 | 0.00 | 0.00 | 0.00 |
| November | 25.01 | 2.01 | 22.99 | 1.60 | 203.70 | 0.00 | 0.00 | 0.00 |
| December | 15.33 | 0.22 | 15.12 | 0.00 | 241.30 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 112.72 | 45.46 | 67.26 | 98.25 | 161.31 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 15.33 | 0.22 | 15.12 | 0.00 | 94.67 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 223.91 | 107.60 | 120.19 | 244.02 | 241.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 26.88 | 17.40 | 9.48 | 27.05 | 29.30 | 0.00 | 0.00 | 0.00 |
| February | 32.83 | 20.03 | 12.80 | 33.63 | 29.80 | 0.00 | 0.00 | 0.00 |
| March | 20.30 | 5.91 | 14.39 | 16.34 | 24.86 | 0.00 | 0.00 | 0.00 |
| April | 42.15 | 19.05 | 23.10 | 47.82 | 23.50 | 0.00 | 0.00 | 0.00 |
| May | 34.86 | 11.35 | 23.51 | 35.64 | 21.57 | 0.00 | 0.00 | 0.00 |
| June | 32.11 | 7.77 | 24.34 | 34.34 | 16.76 | 0.00 | 0.00 | 0.00 |
| July | 34.79 | 10.90 | 23.90 | 40.98 | 14.96 | 0.00 | 0.00 | 0.00 |
| August | 40.77 | 18.34 | 22.43 | 51.32 | 16.11 | 0.00 | 0.00 | 0.00 |
| September | 48.18 | 28.22 | 19.96 | 59.32 | 21.55 | 0.00 | 0.00 | 0.00 |
| October | 33.10 | 19.35 | 13.76 | 36.30 | 26.17 | 0.00 | 0.00 | 0.00 |
| November | 23.47 | 14.28 | 9.19 | 23.24 | 29.28 | 0.00 | 0.00 | 0.00 |
| December | 18.60 | 11.92 | 6.68 | 17.96 | 33.50 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 32.29 | 15.32 | 16.97 | 35.28 | 23.91 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.60 | 5.91 | 6.68 | 16.34 | 14.96 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 48.18 | 28.22 | 24.34 | 59.32 | 33.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 362.92 | 234.93 | 127.99 | 365.29 | 395.57 | 0.00 | 0.00 | 0.00 |
| February | 443.24 | 270.47 | 172.77 | 454.05 | 402.41 | 0.00 | 0.00 | 0.00 |
| March | 274.04 | 79.79 | 194.25 | 220.66 | 335.72 | 0.00 | 0.00 | 0.00 |
| April | 569.06 | 257.21 | 311.85 | 645.61 | 317.33 | 0.00 | 0.00 | 0.00 |
| May | 470.67 | 153.23 | 317.43 | 481.27 | 291.22 | 0.00 | 0.00 | 0.00 |
| June | 433.58 | 104.95 | 328.63 | 463.67 | 226.33 | 0.00 | 0.00 | 0.00 |
| July | 469.78 | 147.12 | 322.66 | 553.26 | 202.00 | 0.00 | 0.00 | 0.00 |
| August | 550.48 | 247.63 | 302.85 | 692.88 | 217.47 | 0.00 | 0.00 | 0.00 |
| September | 650.52 | 381.09 | 269.44 | 800.92 | 290.90 | 0.00 | 0.00 | 0.00 |
| October | 446.94 | 261.21 | 185.72 | 490.05 | 353.39 | 0.00 | 0.00 | 0.00 |
| November | 316.88 | 192.76 | 124.11 | 313.72 | 395.35 | 0.00 | 0.00 | 0.00 |
| December | 251.15 | 160.92 | 90.24 | 242.44 | 452.37 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 435.94 | 206.80 | 229.13 | 476.31 | 322.86 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 251.15 | 79.79 | 90.24 | 220.66 | 202.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 650.52 | 381.09 | 328.63 | 800.92 | 452.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BATH_ZN_1_FLR_1_WALL_5_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 35.66 | 5.44 | 30.22 | 4.90 | 264.48 | 0.00 | 0.00 | 0.00 |
| February | 77.45 | 26.22 | 51.23 | 38.60 | 262.02 | 0.00 | 0.00 | 0.00 |
| March | 88.22 | 16.38 | 71.84 | 31.95 | 221.19 | 0.00 | 0.00 | 0.00 |
| April | 226.05 | 96.09 | 129.96 | 200.27 | 199.61 | 0.00 | 0.00 | 0.00 |
| May | 263.92 | 115.17 | 148.75 | 227.16 | 190.83 | 0.00 | 0.00 | 0.00 |
| June | 288.97 | 129.91 | 159.06 | 279.48 | 153.15 | 0.00 | 0.00 | 0.00 |
| July | 294.17 | 139.92 | 154.25 | 315.37 | 129.61 | 0.00 | 0.00 | 0.00 |
| August | 246.98 | 114.88 | 132.10 | 270.55 | 131.55 | 0.00 | 0.00 | 0.00 |
| September | 186.38 | 85.69 | 100.69 | 182.35 | 178.29 | 0.00 | 0.00 | 0.00 |
| October | 86.99 | 28.05 | 58.94 | 52.94 | 227.43 | 0.00 | 0.00 | 0.00 |
| November | 40.49 | 7.53 | 32.96 | 9.30 | 263.49 | 0.00 | 0.00 | 0.00 |
| December | 23.29 | 2.17 | 21.12 | 0.95 | 299.02 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 155.18 | 64.09 | 91.09 | 134.91 | 209.75 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 23.29 | 2.17 | 21.12 | 0.95 | 129.61 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 294.17 | 139.92 | 159.06 | 315.37 | 299.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 155.10 | 62.30 | 92.80 | 78.57 | 566.81 | 0.00 | 0.00 | 0.00 |
| February | 231.28 | 85.44 | 145.85 | 132.55 | 554.18 | 0.00 | 0.00 | 0.00 |
| March | 241.70 | 47.63 | 194.07 | 117.01 | 454.58 | 0.00 | 0.00 | 0.00 |
| April | 648.98 | 304.96 | 344.02 | 624.20 | 402.44 | 0.00 | 0.00 | 0.00 |
| May | 682.38 | 297.57 | 384.81 | 626.31 | 364.37 | 0.00 | 0.00 | 0.00 |
| June | 675.43 | 269.76 | 405.67 | 675.23 | 283.23 | 0.00 | 0.00 | 0.00 |
| July | 689.48 | 293.03 | 396.45 | 735.87 | 252.99 | 0.00 | 0.00 | 0.00 |
| August | 653.13 | 312.06 | 341.07 | 724.86 | 271.07 | 0.00 | 0.00 | 0.00 |
| September | 588.17 | 312.76 | 275.41 | 616.54 | 363.78 | 0.00 | 0.00 | 0.00 |
| October | 283.92 | 117.66 | 166.25 | 215.69 | 477.77 | 0.00 | 0.00 | 0.00 |
| November | 148.01 | 50.45 | 97.57 | 69.72 | 548.18 | 0.00 | 0.00 | 0.00 |
| December | 109.70 | 40.78 | 68.91 | 46.85 | 621.44 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 426.22 | 183.10 | 243.12 | 389.54 | 429.39 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 109.70 | 40.78 | 68.91 | 46.85 | 252.99 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 689.48 | 312.76 | 405.67 | 735.87 | 621.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 26.69 | 17.28 | 9.41 | 25.73 | 32.47 | 0.00 | 0.00 | 0.00 |
| February | 32.60 | 19.89 | 12.71 | 32.08 | 32.60 | 0.00 | 0.00 | 0.00 |
| March | 20.15 | 5.87 | 14.28 | 14.62 | 28.08 | 0.00 | 0.00 | 0.00 |
| April | 41.85 | 18.91 | 22.93 | 44.87 | 26.78 | 0.00 | 0.00 | 0.00 |
| May | 34.61 | 11.27 | 23.34 | 32.66 | 24.92 | 0.00 | 0.00 | 0.00 |
| June | 31.89 | 7.72 | 24.17 | 31.45 | 19.15 | 0.00 | 0.00 | 0.00 |
| July | 34.55 | 10.82 | 23.73 | 38.12 | 17.17 | 0.00 | 0.00 | 0.00 |
| August | 40.48 | 18.21 | 22.27 | 48.81 | 18.15 | 0.00 | 0.00 | 0.00 |
| September | 47.84 | 28.02 | 19.81 | 57.18 | 23.71 | 0.00 | 0.00 | 0.00 |
| October | 32.87 | 19.21 | 13.66 | 34.57 | 29.30 | 0.00 | 0.00 | 0.00 |
| November | 23.30 | 14.18 | 9.13 | 22.16 | 32.53 | 0.00 | 0.00 | 0.00 |
| December | 18.47 | 11.83 | 6.64 | 17.17 | 37.25 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 32.06 | 15.21 | 16.85 | 33.23 | 26.81 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.47 | 5.87 | 6.64 | 14.62 | 17.17 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 47.84 | 28.02 | 24.17 | 57.18 | 37.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 404.13 | 261.61 | 142.52 | 389.58 | 491.66 | 0.00 | 0.00 | 0.00 |
| February | 493.57 | 301.18 | 192.39 | 485.70 | 493.68 | 0.00 | 0.00 | 0.00 |
| March | 305.16 | 88.85 | 216.31 | 221.36 | 425.26 | 0.00 | 0.00 | 0.00 |
| April | 633.68 | 286.42 | 347.27 | 679.48 | 405.44 | 0.00 | 0.00 | 0.00 |
| May | 524.11 | 170.63 | 353.48 | 494.53 | 376.91 | 0.00 | 0.00 | 0.00 |
| June | 482.82 | 116.87 | 365.95 | 476.32 | 289.61 | 0.00 | 0.00 | 0.00 |
| July | 523.13 | 163.82 | 359.30 | 577.21 | 259.60 | 0.00 | 0.00 | 0.00 |
| August | 612.99 | 275.75 | 337.24 | 739.07 | 274.62 | 0.00 | 0.00 | 0.00 |
| September | 724.40 | 424.36 | 300.03 | 865.79 | 359.09 | 0.00 | 0.00 | 0.00 |
| October | 497.69 | 290.88 | 206.81 | 523.54 | 443.68 | 0.00 | 0.00 | 0.00 |
| November | 352.86 | 214.65 | 138.21 | 335.53 | 492.58 | 0.00 | 0.00 | 0.00 |
| December | 279.68 | 179.19 | 100.49 | 260.03 | 563.99 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 485.44 | 230.29 | 255.15 | 503.23 | 405.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 279.68 | 88.85 | 100.49 | 221.36 | 259.60 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 724.40 | 424.36 | 365.95 | 865.79 | 563.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.75 | 4.71 | 13.04 | 8.65 | 65.26 | 0.00 | 0.00 | 0.00 |
| February | 31.10 | 10.89 | 20.22 | 22.00 | 63.96 | 0.00 | 0.00 | 0.00 |
| March | 38.91 | 7.08 | 31.83 | 28.85 | 53.08 | 0.00 | 0.00 | 0.00 |
| April | 94.74 | 50.37 | 44.37 | 104.34 | 48.96 | 0.00 | 0.00 | 0.00 |
| May | 114.04 | 62.83 | 51.21 | 124.24 | 44.10 | 0.00 | 0.00 | 0.00 |
| June | 122.47 | 66.29 | 56.18 | 141.70 | 34.60 | 0.00 | 0.00 | 0.00 |
| July | 124.03 | 72.37 | 51.66 | 148.00 | 32.89 | 0.00 | 0.00 | 0.00 |
| August | 106.15 | 63.92 | 42.22 | 127.75 | 36.84 | 0.00 | 0.00 | 0.00 |
| September | 79.09 | 47.37 | 31.72 | 90.03 | 46.77 | 0.00 | 0.00 | 0.00 |
| October | 37.80 | 15.22 | 22.58 | 32.97 | 56.54 | 0.67 | 0.00 | 0.00 |
| November | 19.37 | 5.40 | 13.97 | 10.40 | 63.29 | 5.67 | 0.00 | 0.00 |
| December | 12.29 | 2.82 | 9.48 | 3.91 | 73.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.63 | 34.21 | 32.43 | 70.45 | 51.59 | 6.33 | 0.00 | 0.00 |
| Minimum of Months | 12.29 | 2.82 | 9.48 | 3.91 | 32.89 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.03 | 72.37 | 56.18 | 148.00 | 73.63 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.75 | 4.71 | 13.04 | 8.65 | 65.26 | 0.00 | 0.00 | 0.00 |
| February | 31.10 | 10.89 | 20.22 | 22.00 | 63.96 | 0.00 | 0.00 | 0.00 |
| March | 38.91 | 7.08 | 31.83 | 28.85 | 53.08 | 0.00 | 0.00 | 0.00 |
| April | 94.74 | 50.37 | 44.37 | 104.34 | 48.96 | 0.00 | 0.00 | 0.00 |
| May | 114.04 | 62.83 | 51.21 | 124.24 | 44.10 | 0.00 | 0.00 | 0.00 |
| June | 122.47 | 66.29 | 56.18 | 141.70 | 34.60 | 0.00 | 0.00 | 0.00 |
| July | 124.03 | 72.37 | 51.66 | 148.00 | 32.89 | 0.00 | 0.00 | 0.00 |
| August | 106.15 | 63.92 | 42.22 | 127.75 | 36.84 | 0.00 | 0.00 | 0.00 |
| September | 79.09 | 47.37 | 31.72 | 90.03 | 46.77 | 0.00 | 0.00 | 0.00 |
| October | 37.80 | 15.22 | 22.58 | 32.97 | 56.54 | 0.67 | 0.00 | 0.00 |
| November | 19.37 | 5.40 | 13.97 | 10.40 | 63.29 | 5.67 | 0.00 | 0.00 |
| December | 12.29 | 2.82 | 9.48 | 3.91 | 73.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.63 | 34.21 | 32.43 | 70.45 | 51.59 | 6.33 | 0.00 | 0.00 |
| Minimum of Months | 12.29 | 2.82 | 9.48 | 3.91 | 32.89 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.03 | 72.37 | 56.18 | 148.00 | 73.63 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.75 | 4.71 | 13.04 | 8.65 | 65.26 | 0.00 | 0.00 | 0.00 |
| February | 31.10 | 10.89 | 20.22 | 22.00 | 63.96 | 0.00 | 0.00 | 0.00 |
| March | 38.91 | 7.08 | 31.83 | 28.85 | 53.08 | 0.00 | 0.00 | 0.00 |
| April | 94.74 | 50.37 | 44.37 | 104.34 | 48.96 | 0.00 | 0.00 | 0.00 |
| May | 114.04 | 62.83 | 51.21 | 124.24 | 44.10 | 0.00 | 0.00 | 0.00 |
| June | 122.47 | 66.29 | 56.18 | 141.70 | 34.60 | 0.00 | 0.00 | 0.00 |
| July | 124.03 | 72.37 | 51.66 | 148.00 | 32.89 | 0.00 | 0.00 | 0.00 |
| August | 106.15 | 63.92 | 42.22 | 127.75 | 36.84 | 0.00 | 0.00 | 0.00 |
| September | 79.09 | 47.37 | 31.72 | 90.03 | 46.77 | 0.00 | 0.00 | 0.00 |
| October | 37.80 | 15.22 | 22.58 | 32.97 | 56.54 | 0.67 | 0.00 | 0.00 |
| November | 19.37 | 5.40 | 13.97 | 10.40 | 63.29 | 5.67 | 0.00 | 0.00 |
| December | 12.29 | 2.82 | 9.48 | 3.91 | 73.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.63 | 34.21 | 32.43 | 70.45 | 51.59 | 6.33 | 0.00 | 0.00 |
| Minimum of Months | 12.29 | 2.82 | 9.48 | 3.91 | 32.89 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.03 | 72.37 | 56.18 | 148.00 | 73.63 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.75 | 4.71 | 13.04 | 8.65 | 65.26 | 0.00 | 0.00 | 0.00 |
| February | 31.10 | 10.89 | 20.22 | 22.00 | 63.96 | 0.00 | 0.00 | 0.00 |
| March | 38.91 | 7.08 | 31.83 | 28.85 | 53.08 | 0.00 | 0.00 | 0.00 |
| April | 94.74 | 50.37 | 44.37 | 104.34 | 48.96 | 0.00 | 0.00 | 0.00 |
| May | 114.04 | 62.83 | 51.21 | 124.24 | 44.10 | 0.00 | 0.00 | 0.00 |
| June | 122.47 | 66.29 | 56.18 | 141.70 | 34.60 | 0.00 | 0.00 | 0.00 |
| July | 124.03 | 72.37 | 51.66 | 148.00 | 32.89 | 0.00 | 0.00 | 0.00 |
| August | 106.15 | 63.92 | 42.22 | 127.75 | 36.84 | 0.00 | 0.00 | 0.00 |
| September | 79.09 | 47.37 | 31.72 | 90.03 | 46.77 | 0.00 | 0.00 | 0.00 |
| October | 37.80 | 15.22 | 22.58 | 32.97 | 56.54 | 0.67 | 0.00 | 0.00 |
| November | 19.37 | 5.40 | 13.97 | 10.40 | 63.29 | 5.67 | 0.00 | 0.00 |
| December | 12.29 | 2.82 | 9.48 | 3.91 | 73.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.63 | 34.21 | 32.43 | 70.45 | 51.59 | 6.33 | 0.00 | 0.00 |
| Minimum of Months | 12.29 | 2.82 | 9.48 | 3.91 | 32.89 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.03 | 72.37 | 56.18 | 148.00 | 73.63 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.75 | 4.71 | 13.04 | 8.65 | 65.26 | 0.00 | 0.00 | 0.00 |
| February | 31.10 | 10.89 | 20.22 | 22.00 | 63.96 | 0.00 | 0.00 | 0.00 |
| March | 38.91 | 7.08 | 31.83 | 28.85 | 53.08 | 0.00 | 0.00 | 0.00 |
| April | 94.74 | 50.37 | 44.37 | 104.34 | 48.96 | 0.00 | 0.00 | 0.00 |
| May | 114.04 | 62.83 | 51.21 | 124.24 | 44.10 | 0.00 | 0.00 | 0.00 |
| June | 122.47 | 66.29 | 56.18 | 141.70 | 34.60 | 0.00 | 0.00 | 0.00 |
| July | 124.03 | 72.37 | 51.66 | 148.00 | 32.89 | 0.00 | 0.00 | 0.00 |
| August | 106.15 | 63.92 | 42.22 | 127.75 | 36.84 | 0.00 | 0.00 | 0.00 |
| September | 79.09 | 47.37 | 31.72 | 90.03 | 46.77 | 0.00 | 0.00 | 0.00 |
| October | 37.80 | 15.22 | 22.58 | 32.97 | 56.54 | 0.67 | 0.00 | 0.00 |
| November | 19.37 | 5.40 | 13.97 | 10.40 | 63.29 | 5.67 | 0.00 | 0.00 |
| December | 12.29 | 2.82 | 9.48 | 3.91 | 73.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.63 | 34.21 | 32.43 | 70.45 | 51.59 | 6.33 | 0.00 | 0.00 |
| Minimum of Months | 12.29 | 2.82 | 9.48 | 3.91 | 32.89 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.03 | 72.37 | 56.18 | 148.00 | 73.63 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.75 | 4.71 | 13.04 | 8.65 | 65.26 | 0.00 | 0.00 | 0.00 |
| February | 31.10 | 10.89 | 20.22 | 22.00 | 63.96 | 0.00 | 0.00 | 0.00 |
| March | 38.91 | 7.08 | 31.83 | 28.85 | 53.08 | 0.00 | 0.00 | 0.00 |
| April | 94.74 | 50.37 | 44.37 | 104.34 | 48.96 | 0.00 | 0.00 | 0.00 |
| May | 114.04 | 62.83 | 51.21 | 124.24 | 44.10 | 0.00 | 0.00 | 0.00 |
| June | 122.47 | 66.29 | 56.18 | 141.70 | 34.60 | 0.00 | 0.00 | 0.00 |
| July | 124.03 | 72.37 | 51.66 | 148.00 | 32.89 | 0.00 | 0.00 | 0.00 |
| August | 106.15 | 63.92 | 42.22 | 127.75 | 36.84 | 0.00 | 0.00 | 0.00 |
| September | 79.09 | 47.37 | 31.72 | 90.03 | 46.77 | 0.00 | 0.00 | 0.00 |
| October | 37.80 | 15.22 | 22.58 | 32.97 | 56.54 | 0.67 | 0.00 | 0.00 |
| November | 19.37 | 5.40 | 13.97 | 10.40 | 63.29 | 5.67 | 0.00 | 0.00 |
| December | 12.29 | 2.82 | 9.48 | 3.91 | 73.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.63 | 34.21 | 32.43 | 70.45 | 51.59 | 6.33 | 0.00 | 0.00 |
| Minimum of Months | 12.29 | 2.82 | 9.48 | 3.91 | 32.89 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.03 | 72.37 | 56.18 | 148.00 | 73.63 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.75 | 4.71 | 13.04 | 8.65 | 65.26 | 0.00 | 0.00 | 0.00 |
| February | 31.10 | 10.89 | 20.22 | 22.00 | 63.96 | 0.00 | 0.00 | 0.00 |
| March | 38.91 | 7.08 | 31.83 | 28.85 | 53.08 | 0.00 | 0.00 | 0.00 |
| April | 94.74 | 50.37 | 44.37 | 104.34 | 48.96 | 0.00 | 0.00 | 0.00 |
| May | 114.04 | 62.83 | 51.21 | 124.24 | 44.10 | 0.00 | 0.00 | 0.00 |
| June | 122.47 | 66.29 | 56.18 | 141.70 | 34.60 | 0.00 | 0.00 | 0.00 |
| July | 124.03 | 72.37 | 51.66 | 148.00 | 32.89 | 0.00 | 0.00 | 0.00 |
| August | 106.15 | 63.92 | 42.22 | 127.75 | 36.84 | 0.00 | 0.00 | 0.00 |
| September | 79.09 | 47.37 | 31.72 | 90.03 | 46.77 | 0.00 | 0.00 | 0.00 |
| October | 37.80 | 15.22 | 22.58 | 32.97 | 56.54 | 0.67 | 0.00 | 0.00 |
| November | 19.37 | 5.40 | 13.97 | 10.40 | 63.29 | 5.67 | 0.00 | 0.00 |
| December | 12.29 | 2.82 | 9.48 | 3.91 | 73.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.63 | 34.21 | 32.43 | 70.45 | 51.59 | 6.33 | 0.00 | 0.00 |
| Minimum of Months | 12.29 | 2.82 | 9.48 | 3.91 | 32.89 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.03 | 72.37 | 56.18 | 148.00 | 73.63 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.75 | 4.71 | 13.04 | 8.65 | 65.26 | 0.00 | 0.00 | 0.00 |
| February | 31.10 | 10.89 | 20.22 | 22.00 | 63.96 | 0.00 | 0.00 | 0.00 |
| March | 38.91 | 7.08 | 31.83 | 28.85 | 53.08 | 0.00 | 0.00 | 0.00 |
| April | 94.74 | 50.37 | 44.37 | 104.34 | 48.96 | 0.00 | 0.00 | 0.00 |
| May | 114.04 | 62.83 | 51.21 | 124.24 | 44.10 | 0.00 | 0.00 | 0.00 |
| June | 122.47 | 66.29 | 56.18 | 141.70 | 34.60 | 0.00 | 0.00 | 0.00 |
| July | 124.03 | 72.37 | 51.66 | 148.00 | 32.89 | 0.00 | 0.00 | 0.00 |
| August | 106.15 | 63.92 | 42.22 | 127.75 | 36.84 | 0.00 | 0.00 | 0.00 |
| September | 79.09 | 47.37 | 31.72 | 90.03 | 46.77 | 0.00 | 0.00 | 0.00 |
| October | 37.80 | 15.22 | 22.58 | 32.97 | 56.54 | 0.67 | 0.00 | 0.00 |
| November | 19.37 | 5.40 | 13.97 | 10.40 | 63.29 | 5.67 | 0.00 | 0.00 |
| December | 12.29 | 2.82 | 9.48 | 3.91 | 73.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.63 | 34.21 | 32.43 | 70.45 | 51.59 | 6.33 | 0.00 | 0.00 |
| Minimum of Months | 12.29 | 2.82 | 9.48 | 3.91 | 32.89 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.03 | 72.37 | 56.18 | 148.00 | 73.63 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.75 | 4.71 | 13.04 | 8.65 | 65.26 | 0.00 | 0.00 | 0.00 |
| February | 31.10 | 10.89 | 20.22 | 22.00 | 63.96 | 0.00 | 0.00 | 0.00 |
| March | 38.91 | 7.08 | 31.83 | 28.85 | 53.08 | 0.00 | 0.00 | 0.00 |
| April | 94.74 | 50.37 | 44.37 | 104.34 | 48.96 | 0.00 | 0.00 | 0.00 |
| May | 114.04 | 62.83 | 51.21 | 124.24 | 44.10 | 0.00 | 0.00 | 0.00 |
| June | 122.47 | 66.29 | 56.18 | 141.70 | 34.60 | 0.00 | 0.00 | 0.00 |
| July | 124.03 | 72.37 | 51.66 | 148.00 | 32.89 | 0.00 | 0.00 | 0.00 |
| August | 106.15 | 63.92 | 42.22 | 127.75 | 36.84 | 0.00 | 0.00 | 0.00 |
| September | 79.09 | 47.37 | 31.72 | 90.03 | 46.77 | 0.00 | 0.00 | 0.00 |
| October | 37.80 | 15.22 | 22.58 | 32.97 | 56.54 | 0.67 | 0.00 | 0.00 |
| November | 19.37 | 5.40 | 13.97 | 10.40 | 63.29 | 5.67 | 0.00 | 0.00 |
| December | 12.29 | 2.82 | 9.48 | 3.91 | 73.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 66.63 | 34.21 | 32.43 | 70.45 | 51.59 | 6.33 | 0.00 | 0.00 |
| Minimum of Months | 12.29 | 2.82 | 9.48 | 3.91 | 32.89 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.03 | 72.37 | 56.18 | 148.00 | 73.63 | 5.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 9.78 | 3.93 | 5.85 | 4.76 | 38.45 | 0.00 | 0.00 | 0.00 |
| February | 14.58 | 5.39 | 9.20 | 7.98 | 37.94 | 0.00 | 0.00 | 0.00 |
| March | 15.24 | 3.00 | 12.24 | 6.73 | 31.93 | 0.00 | 0.00 | 0.00 |
| April | 40.92 | 19.23 | 21.69 | 38.53 | 26.98 | 0.00 | 0.00 | 0.00 |
| May | 43.03 | 18.76 | 24.26 | 38.44 | 24.54 | 0.00 | 0.00 | 0.00 |
| June | 42.59 | 17.01 | 25.58 | 41.74 | 18.88 | 0.00 | 0.00 | 0.00 |
| July | 43.48 | 18.48 | 25.00 | 45.48 | 16.97 | 0.00 | 0.00 | 0.00 |
| August | 41.18 | 19.68 | 21.51 | 45.22 | 17.79 | 0.00 | 0.00 | 0.00 |
| September | 37.09 | 19.72 | 17.37 | 38.61 | 23.49 | 0.00 | 0.00 | 0.00 |
| October | 17.90 | 7.42 | 10.48 | 13.46 | 31.54 | 0.00 | 0.00 | 0.00 |
| November | 9.33 | 3.18 | 6.15 | 4.21 | 36.94 | 0.00 | 0.00 | 0.00 |
| December | 6.92 | 2.57 | 4.35 | 2.76 | 42.58 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 26.88 | 11.55 | 15.33 | 24.05 | 28.96 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6.92 | 2.57 | 4.35 | 2.76 | 16.97 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 43.48 | 19.72 | 25.58 | 45.48 | 42.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 115.76 | 46.50 | 69.26 | 56.31 | 455.10 | 0.00 | 0.00 | 0.00 |
| February | 172.62 | 63.77 | 108.85 | 94.44 | 448.85 | 0.00 | 0.00 | 0.00 |
| March | 180.39 | 35.55 | 144.84 | 79.68 | 377.86 | 0.00 | 0.00 | 0.00 |
| April | 484.37 | 227.60 | 256.77 | 456.73 | 319.31 | 0.00 | 0.00 | 0.00 |
| May | 509.30 | 222.09 | 287.21 | 455.73 | 290.38 | 0.00 | 0.00 | 0.00 |
| June | 504.11 | 201.33 | 302.78 | 495.16 | 223.47 | 0.00 | 0.00 | 0.00 |
| July | 514.60 | 218.70 | 295.90 | 539.46 | 200.90 | 0.00 | 0.00 | 0.00 |
| August | 487.47 | 232.90 | 254.57 | 536.32 | 210.61 | 0.00 | 0.00 | 0.00 |
| September | 438.98 | 233.42 | 205.56 | 457.82 | 278.03 | 0.00 | 0.00 | 0.00 |
| October | 211.90 | 87.82 | 124.09 | 159.51 | 373.30 | 0.00 | 0.00 | 0.00 |
| November | 110.47 | 37.65 | 72.82 | 49.88 | 437.24 | 0.00 | 0.00 | 0.00 |
| December | 81.87 | 30.44 | 51.43 | 32.62 | 504.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 318.11 | 136.66 | 181.46 | 285.15 | 342.70 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 81.87 | 30.44 | 51.43 | 32.62 | 200.90 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 514.60 | 233.42 | 302.78 | 539.46 | 504.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 59.08 | 23.73 | 35.35 | 23.74 | 303.75 | 281.17 | 0.00 | 0.00 |
| February | 88.11 | 32.55 | 55.56 | 41.64 | 295.06 | 259.83 | 0.00 | 0.00 |
| March | 92.07 | 18.14 | 73.93 | 33.50 | 242.22 | 115.67 | 0.00 | 0.00 |
| April | 247.22 | 116.17 | 131.05 | 227.91 | 182.75 | 0.00 | 0.00 | 0.00 |
| May | 259.95 | 113.36 | 146.59 | 229.19 | 163.13 | 0.00 | 0.00 | 0.00 |
| June | 257.30 | 102.76 | 154.54 | 250.14 | 125.69 | 0.00 | 0.00 | 0.00 |
| July | 262.65 | 111.63 | 151.03 | 272.00 | 114.10 | 0.00 | 0.00 | 0.00 |
| August | 248.81 | 118.88 | 129.93 | 270.65 | 121.03 | 0.00 | 0.00 | 0.00 |
| September | 224.06 | 119.14 | 104.91 | 230.30 | 157.84 | 0.00 | 0.00 | 0.00 |
| October | 108.16 | 44.82 | 63.33 | 76.31 | 227.35 | 4.00 | 0.00 | 0.00 |
| November | 56.38 | 19.22 | 37.17 | 21.48 | 282.47 | 114.17 | 0.00 | 0.00 |
| December | 41.79 | 15.54 | 26.25 | 12.92 | 336.68 | 347.00 | 0.00 | 0.00 |
| Annual Sum or Average | 162.37 | 69.75 | 92.62 | 141.17 | 212.27 | 1121.83 | 0.00 | 0.00 |
| Minimum of Months | 41.79 | 15.54 | 26.25 | 12.92 | 114.10 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 262.65 | 119.14 | 154.54 | 272.00 | 336.68 | 347.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 71.26 | 0.00 | 71.26 | 0.54 | 632.19 | 0.00 | 0.00 | 0.00 |
| February | 111.35 | 0.00 | 111.35 | 3.24 | 607.82 | 0.00 | 0.00 | 0.00 |
| March | 154.64 | 0.00 | 154.64 | 21.05 | 503.30 | 0.00 | 0.00 | 0.00 |
| April | 249.85 | 0.92 | 248.94 | 101.28 | 418.01 | 0.00 | 0.00 | 0.00 |
| May | 305.68 | 11.57 | 294.11 | 115.47 | 355.57 | 0.00 | 0.00 | 0.00 |
| June | 338.41 | 19.29 | 319.12 | 198.84 | 280.30 | 0.00 | 0.00 | 0.00 |
| July | 320.35 | 15.39 | 304.95 | 221.13 | 245.63 | 0.00 | 0.00 | 0.00 |
| August | 255.87 | 3.31 | 252.55 | 173.58 | 272.28 | 0.00 | 0.00 | 0.00 |
| September | 196.15 | 0.04 | 196.11 | 98.39 | 376.09 | 0.00 | 0.00 | 0.00 |
| October | 125.98 | 0.00 | 125.98 | 19.28 | 489.68 | 0.00 | 0.00 | 0.00 |
| November | 75.72 | 0.00 | 75.72 | 0.50 | 593.74 | 0.00 | 0.00 | 0.00 |
| December | 51.56 | 0.00 | 51.56 | 0.00 | 692.54 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 188.40 | 4.24 | 184.17 | 79.85 | 454.77 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.56 | 0.00 | 51.56 | 0.00 | 245.63 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 338.41 | 19.29 | 319.12 | 221.13 | 692.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 9.87 | 3.97 | 5.91 | 4.97 | 37.38 | 0.00 | 0.00 | 0.00 |
| February | 14.72 | 5.44 | 9.28 | 8.41 | 36.06 | 0.00 | 0.00 | 0.00 |
| March | 15.39 | 3.03 | 12.35 | 7.36 | 29.99 | 0.00 | 0.00 | 0.00 |
| April | 41.31 | 19.41 | 21.90 | 40.56 | 24.40 | 0.00 | 0.00 | 0.00 |
| May | 43.44 | 18.94 | 24.50 | 40.75 | 22.04 | 0.00 | 0.00 | 0.00 |
| June | 42.99 | 17.17 | 25.82 | 43.24 | 17.84 | 0.00 | 0.00 | 0.00 |
| July | 43.89 | 18.65 | 25.24 | 47.44 | 15.58 | 0.00 | 0.00 | 0.00 |
| August | 41.58 | 19.86 | 21.71 | 46.66 | 16.71 | 0.00 | 0.00 | 0.00 |
| September | 37.44 | 19.91 | 17.53 | 40.02 | 22.16 | 0.00 | 0.00 | 0.00 |
| October | 18.07 | 7.49 | 10.58 | 14.08 | 29.63 | 0.00 | 0.00 | 0.00 |
| November | 9.42 | 3.21 | 6.21 | 4.43 | 35.56 | 0.00 | 0.00 | 0.00 |
| December | 6.98 | 2.60 | 4.39 | 2.90 | 41.70 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 27.13 | 11.66 | 15.48 | 25.13 | 27.38 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6.98 | 2.60 | 4.39 | 2.90 | 15.58 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 43.89 | 19.91 | 25.82 | 47.44 | 41.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 100.91 | 40.54 | 60.38 | 50.82 | 382.03 | 0.00 | 0.00 | 0.00 |
| February | 150.48 | 55.59 | 94.89 | 85.99 | 368.61 | 0.00 | 0.00 | 0.00 |
| March | 157.26 | 30.99 | 126.27 | 75.23 | 306.55 | 0.00 | 0.00 | 0.00 |
| April | 422.25 | 198.42 | 223.83 | 414.57 | 249.40 | 0.00 | 0.00 | 0.00 |
| May | 443.98 | 193.61 | 250.37 | 416.52 | 225.19 | 0.00 | 0.00 | 0.00 |
| June | 439.46 | 175.51 | 263.94 | 442.01 | 182.28 | 0.00 | 0.00 | 0.00 |
| July | 448.60 | 190.65 | 257.94 | 484.88 | 159.18 | 0.00 | 0.00 | 0.00 |
| August | 424.95 | 203.04 | 221.91 | 476.97 | 170.74 | 0.00 | 0.00 | 0.00 |
| September | 382.68 | 203.49 | 179.19 | 409.04 | 226.47 | 0.00 | 0.00 | 0.00 |
| October | 184.73 | 76.55 | 108.17 | 143.88 | 302.83 | 0.00 | 0.00 | 0.00 |
| November | 96.30 | 32.82 | 63.48 | 45.28 | 363.49 | 0.00 | 0.00 | 0.00 |
| December | 71.37 | 26.54 | 44.84 | 29.69 | 426.27 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 277.31 | 119.13 | 158.18 | 256.86 | 279.80 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 71.37 | 26.54 | 44.84 | 29.69 | 159.18 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 448.60 | 203.49 | 263.94 | 484.88 | 426.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 68.65 | 0.00 | 68.65 | 1.39 | 556.89 | 0.00 | 0.00 | 0.00 |
| February | 107.21 | 0.00 | 107.21 | 4.45 | 542.11 | 0.00 | 0.00 | 0.00 |
| March | 148.35 | 0.00 | 148.35 | 20.72 | 460.48 | 0.00 | 0.00 | 0.00 |
| April | 241.55 | 1.08 | 240.47 | 98.58 | 398.97 | 0.00 | 0.00 | 0.00 |
| May | 301.99 | 14.57 | 287.42 | 115.16 | 334.67 | 0.00 | 0.00 | 0.00 |
| June | 333.84 | 20.93 | 312.90 | 205.63 | 255.27 | 0.00 | 0.00 | 0.00 |
| July | 316.66 | 18.05 | 298.61 | 224.42 | 223.42 | 0.00 | 0.00 | 0.00 |
| August | 248.91 | 3.90 | 245.01 | 175.02 | 247.27 | 0.00 | 0.00 | 0.00 |
| September | 189.46 | 0.04 | 189.41 | 97.16 | 354.26 | 0.00 | 0.00 | 0.00 |
| October | 121.40 | 0.00 | 121.40 | 20.15 | 465.43 | 0.00 | 0.00 | 0.00 |
| November | 72.94 | 0.00 | 72.94 | 0.66 | 546.73 | 0.00 | 0.00 | 0.00 |
| December | 49.67 | 0.00 | 49.67 | 0.00 | 611.04 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 183.73 | 4.91 | 178.81 | 80.68 | 415.65 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 49.67 | 0.00 | 49.67 | 0.00 | 223.42 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 333.84 | 20.93 | 312.90 | 224.42 | 611.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 3.39 | 0.00 | 3.39 | 0.01 | 38.38 | 0.00 | 0.00 | 0.00 |
| February | 5.34 | 0.00 | 5.34 | 0.04 | 38.11 | 0.00 | 0.00 | 0.00 |
| March | 7.24 | 0.00 | 7.24 | 0.22 | 32.84 | 0.00 | 0.00 | 0.00 |
| April | 20.27 | 6.51 | 13.77 | 11.69 | 25.15 | 0.00 | 0.00 | 0.00 |
| May | 29.94 | 12.64 | 17.30 | 22.87 | 23.11 | 0.00 | 0.00 | 0.00 |
| June | 32.05 | 13.24 | 18.80 | 29.06 | 17.71 | 0.00 | 0.00 | 0.00 |
| July | 31.50 | 13.21 | 18.29 | 30.81 | 15.12 | 0.00 | 0.00 | 0.00 |
| August | 23.55 | 9.02 | 14.53 | 21.99 | 15.48 | 0.00 | 0.00 | 0.00 |
| September | 11.94 | 1.72 | 10.22 | 5.57 | 22.22 | 0.00 | 0.00 | 0.00 |
| October | 6.08 | 0.00 | 6.08 | 0.40 | 32.03 | 0.00 | 0.00 | 0.00 |
| November | 3.59 | 0.00 | 3.59 | 0.00 | 37.70 | 0.00 | 0.00 | 0.00 |
| December | 2.44 | 0.00 | 2.44 | 0.00 | 41.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 14.83 | 4.73 | 10.10 | 10.29 | 28.24 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 2.44 | 0.00 | 2.44 | 0.00 | 15.12 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 32.05 | 13.24 | 18.80 | 30.81 | 41.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 118.46 | 39.17 | 79.29 | 44.30 | 543.39 | 0.00 | 0.00 | 0.00 |
| February | 196.46 | 67.73 | 128.73 | 100.71 | 528.95 | 0.00 | 0.00 | 0.00 |
| March | 220.85 | 44.32 | 176.53 | 98.14 | 448.75 | 0.00 | 0.00 | 0.00 |
| April | 598.56 | 286.02 | 312.54 | 575.06 | 379.89 | 0.00 | 0.00 | 0.00 |
| May | 628.70 | 279.10 | 349.60 | 574.45 | 345.97 | 0.00 | 0.00 | 0.00 |
| June | 621.32 | 253.01 | 368.31 | 617.99 | 269.20 | 0.00 | 0.00 | 0.00 |
| July | 634.69 | 274.84 | 359.86 | 679.44 | 234.61 | 0.00 | 0.00 | 0.00 |
| August | 601.89 | 292.69 | 309.20 | 674.91 | 246.20 | 0.00 | 0.00 | 0.00 |
| September | 541.24 | 291.91 | 249.33 | 571.76 | 335.83 | 0.00 | 0.00 | 0.00 |
| October | 250.66 | 102.16 | 148.50 | 184.03 | 457.09 | 0.00 | 0.00 | 0.00 |
| November | 120.56 | 35.69 | 84.87 | 43.87 | 537.12 | 0.00 | 0.00 | 0.00 |
| December | 81.05 | 23.27 | 57.78 | 21.05 | 605.07 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 385.14 | 166.08 | 219.07 | 349.72 | 410.37 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 81.05 | 23.27 | 57.78 | 21.05 | 234.61 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 634.69 | 292.69 | 368.31 | 679.44 | 605.07 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.173135E+09 | 57204555.42 | 0.115931E+09 | 88272139.35 | 0.634350E+09 |
| February | 0.276879E+09 | 0.116907E+09 | 0.159972E+09 | 0.196851E+09 | 0.553011E+09 |
| March | 0.277182E+09 | 53024880.35 | 0.224157E+09 | 0.140211E+09 | 0.489125E+09 |
| April | 0.632923E+09 | 0.251402E+09 | 0.381520E+09 | 0.599772E+09 | 0.427828E+09 |
| May | 0.767317E+09 | 0.312017E+09 | 0.455299E+09 | 0.720947E+09 | 0.389674E+09 |
| June | 0.801890E+09 | 0.330108E+09 | 0.471782E+09 | 0.842919E+09 | 0.293603E+09 |
| July | 0.843913E+09 | 0.372083E+09 | 0.471829E+09 | 0.963086E+09 | 0.259815E+09 |
| August | 0.708830E+09 | 0.306904E+09 | 0.401927E+09 | 0.815005E+09 | 0.284957E+09 |
| September | 0.550326E+09 | 0.246779E+09 | 0.303547E+09 | 0.572817E+09 | 0.394697E+09 |
| October | 0.303364E+09 | 0.109088E+09 | 0.194275E+09 | 0.228114E+09 | 0.521323E+09 |
| November | 0.158874E+09 | 46377322.20 | 0.112497E+09 | 78645033.01 | 0.589681E+09 |
| December | 92925003.65 | 19609204.17 | 73315799.48 | 26696707.62 | 0.706287E+09 |
| Annual Sum or Average | 0.558756E+10 | 0.222150E+10 | 0.336605E+10 | 0.527334E+10 | 0.554435E+10 |
| Minimum of Months | 92925003.65 | 19609204.17 | 73315799.48 | 26696707.62 | 0.259815E+09 |
| Maximum of Months | 0.843913E+09 | 0.372083E+09 | 0.471829E+09 | 0.963086E+09 | 0.706287E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 76120501.54 | 49275884.71 | 26844616.83 | 73491480.36 | 89236748.68 |
| February | 83970408.73 | 51239832.47 | 32730576.26 | 83082904.59 | 80241588.20 |
| March | 57478522.40 | 16735127.14 | 40743395.27 | 43307764.83 | 74377695.04 |
| April | 0.115509E+09 | 52208406.27 | 63300204.10 | 0.126453E+09 | 67528192.74 |
| May | 98720991.84 | 32140223.95 | 66580767.88 | 96472330.42 | 63548964.63 |
| June | 88009517.14 | 21303339.68 | 66706177.46 | 90553209.26 | 47178296.01 |
| July | 98535179.22 | 30857274.27 | 67677904.94 | 0.115180E+09 | 41555829.30 |
| August | 0.115461E+09 | 51938720.64 | 63522775.09 | 0.144599E+09 | 44621943.36 |
| September | 0.132044E+09 | 77353308.90 | 54690457.40 | 0.160009E+09 | 60279926.76 |
| October | 93743453.29 | 54788749.14 | 38954704.15 | 99761492.37 | 77605509.04 |
| November | 64320046.15 | 39127483.76 | 25192562.39 | 61696658.58 | 85083219.46 |
| December | 52678853.08 | 33751562.95 | 18927290.12 | 49351338.85 | 0.101148E+09 |
| Annual Sum or Average | 0.107659E+10 | 0.510720E+09 | 0.565871E+09 | 0.114396E+10 | 0.832406E+09 |
| Minimum of Months | 52678853.08 | 16735127.14 | 18927290.12 | 43307764.83 | 41555829.30 |
| Maximum of Months | 0.132044E+09 | 77353308.90 | 67677904.94 | 0.160009E+09 | 0.101148E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.528298E+09 | 0.341989E+09 | 0.186309E+09 | 0.510052E+09 | 0.619329E+09 |
| February | 0.582779E+09 | 0.355619E+09 | 0.227160E+09 | 0.576619E+09 | 0.556900E+09 |
| March | 0.398918E+09 | 0.116147E+09 | 0.282771E+09 | 0.300568E+09 | 0.516203E+09 |
| April | 0.801663E+09 | 0.362341E+09 | 0.439322E+09 | 0.877618E+09 | 0.468702E+09 |
| May | 0.685152E+09 | 0.223062E+09 | 0.462090E+09 | 0.669380E+09 | 0.442181E+09 |
| June | 0.610811E+09 | 0.147851E+09 | 0.462960E+09 | 0.627567E+09 | 0.328782E+09 |
| July | 0.683863E+09 | 0.214158E+09 | 0.469704E+09 | 0.798284E+09 | 0.289340E+09 |
| August | 0.801336E+09 | 0.360470E+09 | 0.440866E+09 | 0.100350E+10 | 0.309887E+09 |
| September | 0.916422E+09 | 0.536854E+09 | 0.379568E+09 | 0.111051E+10 | 0.418357E+09 |
| October | 0.650607E+09 | 0.380250E+09 | 0.270357E+09 | 0.692374E+09 | 0.538605E+09 |
| November | 0.446400E+09 | 0.271556E+09 | 0.174844E+09 | 0.428193E+09 | 0.590502E+09 |
| December | 0.365606E+09 | 0.234246E+09 | 0.131361E+09 | 0.342513E+09 | 0.701999E+09 |
| Annual Sum or Average | 0.747185E+10 | 0.354454E+10 | 0.392731E+10 | 0.793718E+10 | 0.578079E+10 |
| Minimum of Months | 0.365606E+09 | 0.116147E+09 | 0.131361E+09 | 0.300568E+09 | 0.289340E+09 |
| Maximum of Months | 0.916422E+09 | 0.536854E+09 | 0.469704E+09 | 0.111051E+10 | 0.701999E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.970763E+09 | 0.628415E+09 | 0.342348E+09 | 0.921381E+09 | 0.121968E+10 |
| February | 0.107087E+10 | 0.653461E+09 | 0.417411E+09 | 0.104105E+10 | 0.110249E+10 |
| March | 0.733021E+09 | 0.213423E+09 | 0.519598E+09 | 0.530025E+09 | 0.102946E+10 |
| April | 0.147308E+10 | 0.665813E+09 | 0.807263E+09 | 0.159674E+10 | 0.917446E+09 |
| May | 0.125898E+10 | 0.409884E+09 | 0.849099E+09 | 0.121573E+10 | 0.862102E+09 |
| June | 0.112238E+10 | 0.271681E+09 | 0.850698E+09 | 0.114863E+10 | 0.628266E+09 |
| July | 0.125661E+10 | 0.393522E+09 | 0.863091E+09 | 0.147546E+10 | 0.540320E+09 |
| August | 0.147247E+10 | 0.662374E+09 | 0.810101E+09 | 0.184982E+10 | 0.582597E+09 |
| September | 0.168395E+10 | 0.986486E+09 | 0.697464E+09 | 0.203337E+10 | 0.807177E+09 |
| October | 0.119551E+10 | 0.698720E+09 | 0.496787E+09 | 0.125651E+10 | 0.106429E+10 |
| November | 0.820272E+09 | 0.498992E+09 | 0.321280E+09 | 0.772849E+09 | 0.116961E+10 |
| December | 0.671812E+09 | 0.430433E+09 | 0.241379E+09 | 0.617526E+09 | 0.138783E+10 |
| Annual Sum or Average | 0.137297E+11 | 0.651321E+10 | 0.721652E+10 | 0.144591E+11 | 0.113113E+11 |
| Minimum of Months | 0.671812E+09 | 0.213423E+09 | 0.241379E+09 | 0.530025E+09 | 0.540320E+09 |
| Maximum of Months | 0.168395E+10 | 0.986486E+09 | 0.863091E+09 | 0.203337E+10 | 0.138783E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.970763E+09 | 0.628415E+09 | 0.342348E+09 | 0.921381E+09 | 0.121968E+10 |
| February | 0.107087E+10 | 0.653461E+09 | 0.417411E+09 | 0.104105E+10 | 0.110249E+10 |
| March | 0.733021E+09 | 0.213423E+09 | 0.519598E+09 | 0.530025E+09 | 0.102946E+10 |
| April | 0.147308E+10 | 0.665813E+09 | 0.807263E+09 | 0.159674E+10 | 0.917446E+09 |
| May | 0.125898E+10 | 0.409884E+09 | 0.849099E+09 | 0.121573E+10 | 0.862102E+09 |
| June | 0.112238E+10 | 0.271681E+09 | 0.850698E+09 | 0.114863E+10 | 0.628266E+09 |
| July | 0.125661E+10 | 0.393522E+09 | 0.863091E+09 | 0.147546E+10 | 0.540320E+09 |
| August | 0.147247E+10 | 0.662374E+09 | 0.810101E+09 | 0.184982E+10 | 0.582597E+09 |
| September | 0.168395E+10 | 0.986486E+09 | 0.697464E+09 | 0.203337E+10 | 0.807177E+09 |
| October | 0.119551E+10 | 0.698720E+09 | 0.496787E+09 | 0.125651E+10 | 0.106429E+10 |
| November | 0.820272E+09 | 0.498992E+09 | 0.321280E+09 | 0.772849E+09 | 0.116961E+10 |
| December | 0.671812E+09 | 0.430433E+09 | 0.241379E+09 | 0.617526E+09 | 0.138783E+10 |
| Annual Sum or Average | 0.137297E+11 | 0.651321E+10 | 0.721652E+10 | 0.144591E+11 | 0.113113E+11 |
| Minimum of Months | 0.671812E+09 | 0.213423E+09 | 0.241379E+09 | 0.530025E+09 | 0.540320E+09 |
| Maximum of Months | 0.168395E+10 | 0.986486E+09 | 0.863091E+09 | 0.203337E+10 | 0.138783E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.970744E+09 | 0.628403E+09 | 0.342342E+09 | 0.921363E+09 | 0.121965E+10 |
| February | 0.107085E+10 | 0.653448E+09 | 0.417403E+09 | 0.104103E+10 | 0.110247E+10 |
| March | 0.733007E+09 | 0.213419E+09 | 0.519588E+09 | 0.530014E+09 | 0.102944E+10 |
| April | 0.147305E+10 | 0.665800E+09 | 0.807247E+09 | 0.159671E+10 | 0.917428E+09 |
| May | 0.125896E+10 | 0.409876E+09 | 0.849083E+09 | 0.121570E+10 | 0.862086E+09 |
| June | 0.112236E+10 | 0.271676E+09 | 0.850682E+09 | 0.114860E+10 | 0.628253E+09 |
| July | 0.125659E+10 | 0.393515E+09 | 0.863074E+09 | 0.147543E+10 | 0.540310E+09 |
| August | 0.147245E+10 | 0.662361E+09 | 0.810085E+09 | 0.184978E+10 | 0.582586E+09 |
| September | 0.168392E+10 | 0.986467E+09 | 0.697450E+09 | 0.203333E+10 | 0.807161E+09 |
| October | 0.119548E+10 | 0.698707E+09 | 0.496778E+09 | 0.125648E+10 | 0.106427E+10 |
| November | 0.820256E+09 | 0.498983E+09 | 0.321273E+09 | 0.772834E+09 | 0.116958E+10 |
| December | 0.671799E+09 | 0.430425E+09 | 0.241374E+09 | 0.617514E+09 | 0.138780E+10 |
| Annual Sum or Average | 0.137295E+11 | 0.651308E+10 | 0.721638E+10 | 0.144588E+11 | 0.113111E+11 |
| Minimum of Months | 0.671799E+09 | 0.213419E+09 | 0.241374E+09 | 0.530014E+09 | 0.540310E+09 |
| Maximum of Months | 0.168392E+10 | 0.986467E+09 | 0.863074E+09 | 0.203333E+10 | 0.138780E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 57711920.74 | 19068248.70 | 38643672.04 | 29865100.35 | 0.224844E+09 |
| February | 92293229.18 | 38969160.85 | 53324068.33 | 66175039.91 | 0.197065E+09 |
| March | 92394264.78 | 17675019.03 | 74719245.74 | 44458454.43 | 0.177874E+09 |
| April | 0.210975E+09 | 83801043.43 | 0.127174E+09 | 0.199634E+09 | 0.150811E+09 |
| May | 0.255773E+09 | 0.104006E+09 | 0.151767E+09 | 0.236569E+09 | 0.141043E+09 |
| June | 0.267298E+09 | 0.110036E+09 | 0.157261E+09 | 0.276827E+09 | 0.105320E+09 |
| July | 0.281305E+09 | 0.124028E+09 | 0.157277E+09 | 0.320656E+09 | 90024357.72 |
| August | 0.236278E+09 | 0.102302E+09 | 0.133976E+09 | 0.274080E+09 | 96184878.15 |
| September | 0.183443E+09 | 82259818.46 | 0.101183E+09 | 0.193468E+09 | 0.134843E+09 |
| October | 0.101122E+09 | 36362868.60 | 64758671.88 | 77135307.78 | 0.183494E+09 |
| November | 52958201.52 | 15459158.93 | 37499042.59 | 26696024.01 | 0.209202E+09 |
| December | 30975104.47 | 6536423.18 | 24438681.29 | 8918005.83 | 0.256132E+09 |
| Annual Sum or Average | 0.186253E+10 | 0.740504E+09 | 0.112202E+10 | 0.175448E+10 | 0.196684E+10 |
| Minimum of Months | 30975104.47 | 6536423.18 | 24438681.29 | 8918005.83 | 90024357.72 |
| Maximum of Months | 0.281305E+09 | 0.124028E+09 | 0.157277E+09 | 0.320656E+09 | 0.256132E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.173135E+09 | 57204555.42 | 0.115931E+09 | 97441593.69 | 0.607860E+09 |
| February | 0.276879E+09 | 0.116907E+09 | 0.159972E+09 | 0.209951E+09 | 0.523375E+09 |
| March | 0.277182E+09 | 53024880.35 | 0.224157E+09 | 0.147915E+09 | 0.476974E+09 |
| April | 0.632923E+09 | 0.251402E+09 | 0.381520E+09 | 0.626956E+09 | 0.400485E+09 |
| May | 0.767317E+09 | 0.312017E+09 | 0.455299E+09 | 0.740543E+09 | 0.372370E+09 |
| June | 0.801890E+09 | 0.330108E+09 | 0.471782E+09 | 0.856243E+09 | 0.284468E+09 |
| July | 0.843913E+09 | 0.372083E+09 | 0.471829E+09 | 0.986597E+09 | 0.245072E+09 |
| August | 0.708830E+09 | 0.306904E+09 | 0.401927E+09 | 0.847372E+09 | 0.258749E+09 |
| September | 0.550326E+09 | 0.246779E+09 | 0.303547E+09 | 0.602535E+09 | 0.359246E+09 |
| October | 0.303364E+09 | 0.109088E+09 | 0.194275E+09 | 0.247381E+09 | 0.486894E+09 |
| November | 0.158874E+09 | 46377322.20 | 0.112497E+09 | 86611831.75 | 0.561420E+09 |
| December | 92925003.65 | 19609204.17 | 73315799.48 | 29618789.17 | 0.689440E+09 |
| Annual Sum or Average | 0.558756E+10 | 0.222150E+10 | 0.336605E+10 | 0.547916E+10 | 0.526635E+10 |
| Minimum of Months | 92925003.65 | 19609204.17 | 73315799.48 | 29618789.17 | 0.245072E+09 |
| Maximum of Months | 0.843913E+09 | 0.372083E+09 | 0.471829E+09 | 0.986597E+09 | 0.689440E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 10745897.20 | 0.00 | 10745897.20 | 138463.92 | 99253213.26 |
| February | 15149027.80 | 0.00 | 15149027.80 | 412260.97 | 85559369.99 |
| March | 24036273.63 | 0.00 | 24036273.63 | 3238598.47 | 77303361.69 |
| April | 35955205.58 | 174669.40 | 35780536.19 | 13623514.84 | 63207203.49 |
| May | 47287582.27 | 2447596.87 | 44839985.40 | 16638753.65 | 55395278.06 |
| June | 50923912.27 | 3553958.83 | 47369953.44 | 30991990.52 | 41018247.55 |
| July | 49392444.92 | 3121073.81 | 46271371.11 | 39126137.88 | 34833481.05 |
| August | 37798603.89 | 639230.31 | 37159373.59 | 30193246.88 | 37020462.40 |
| September | 27539087.22 | 4325.07 | 27534762.15 | 14344000.33 | 54857779.07 |
| October | 18798626.13 | 0.00 | 18798626.13 | 2648317.84 | 75761855.08 |
| November | 11059524.36 | 0.00 | 11059524.36 | 85862.56 | 89187514.67 |
| December | 7790233.19 | 0.00 | 7790233.19 | 0.00 | 0.106980E+09 |
| Annual Sum or Average | 0.336476E+09 | 9940854.27 | 0.326536E+09 | 0.151441E+09 | 0.820378E+09 |
| Minimum of Months | 7790233.19 | 0.00 | 7790233.19 | 0.00 | 34833481.05 |
| Maximum of Months | 50923912.27 | 3553958.83 | 47369953.44 | 39126137.88 | 0.106980E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 78891640.00 | 0.00 | 78891640.00 | 1508323.57 | 0.686101E+09 |
| February | 0.111232E+09 | 0.00 | 0.111232E+09 | 4235663.26 | 0.588797E+09 |
| March | 0.174816E+09 | 0.00 | 0.174816E+09 | 27933342.33 | 0.534380E+09 |
| April | 0.265142E+09 | 1212256.03 | 0.263930E+09 | 0.111285E+09 | 0.437448E+09 |
| May | 0.346164E+09 | 16987028.92 | 0.329177E+09 | 0.134839E+09 | 0.383437E+09 |
| June | 0.372150E+09 | 24665500.37 | 0.347484E+09 | 0.238161E+09 | 0.286025E+09 |
| July | 0.361956E+09 | 21661153.31 | 0.340295E+09 | 0.295443E+09 | 0.243861E+09 |
| August | 0.279529E+09 | 4436487.86 | 0.275093E+09 | 0.230754E+09 | 0.259656E+09 |
| September | 0.204500E+09 | 30624.89 | 0.204469E+09 | 0.114674E+09 | 0.381884E+09 |
| October | 0.138422E+09 | 0.00 | 0.138422E+09 | 24608701.85 | 0.524995E+09 |
| November | 81173015.21 | 0.00 | 81173015.21 | 1018927.11 | 0.616749E+09 |
| December | 57162070.35 | 0.00 | 57162070.35 | 0.00 | 0.742401E+09 |
| Annual Sum or Average | 0.247114E+10 | 68993051.39 | 0.240214E+10 | 0.118446E+10 | 0.568573E+10 |
| Minimum of Months | 57162070.35 | 0.00 | 57162070.35 | 0.00 | 0.243861E+09 |
| Maximum of Months | 0.372150E+09 | 24665500.37 | 0.347484E+09 | 0.295443E+09 | 0.742401E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.129761E+09 | 0.00 | 0.129761E+09 | 522183.15 | 0.135485E+10 |
| February | 0.183123E+09 | 0.00 | 0.183123E+09 | 2352365.16 | 0.118381E+10 |
| March | 0.290854E+09 | 0.00 | 0.290854E+09 | 22409381.32 | 0.108379E+10 |
| April | 0.431662E+09 | 713139.23 | 0.430949E+09 | 0.138859E+09 | 0.872082E+09 |
| May | 0.553879E+09 | 17596769.95 | 0.536282E+09 | 0.166118E+09 | 0.787975E+09 |
| June | 0.596041E+09 | 33669199.64 | 0.562371E+09 | 0.338941E+09 | 0.563046E+09 |
| July | 0.577695E+09 | 27542453.23 | 0.550153E+09 | 0.455739E+09 | 0.466944E+09 |
| August | 0.449582E+09 | 3418763.18 | 0.446164E+09 | 0.364870E+09 | 0.491296E+09 |
| September | 0.332988E+09 | 20560.84 | 0.332967E+09 | 0.161331E+09 | 0.729513E+09 |
| October | 0.227206E+09 | 0.00 | 0.227206E+09 | 19447086.61 | 0.104443E+10 |
| November | 0.133548E+09 | 0.00 | 0.133548E+09 | 170277.10 | 0.123197E+10 |
| December | 94028763.38 | 0.00 | 94028763.38 | 0.00 | 0.146918E+10 |
| Annual Sum or Average | 0.400037E+10 | 82960886.08 | 0.391741E+10 | 0.167076E+10 | 0.112789E+11 |
| Minimum of Months | 94028763.38 | 0.00 | 94028763.38 | 0.00 | 0.466944E+09 |
| Maximum of Months | 0.596041E+09 | 33669199.64 | 0.562371E+09 | 0.455739E+09 | 0.146918E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.137093E+09 | 0.00 | 0.137093E+09 | 964055.92 | 0.135295E+10 |
| February | 0.193267E+09 | 0.00 | 0.193267E+09 | 3437389.26 | 0.117832E+10 |
| March | 0.306629E+09 | 0.00 | 0.306629E+09 | 30157661.55 | 0.107663E+10 |
| April | 0.457312E+09 | 1657797.29 | 0.455654E+09 | 0.160060E+09 | 0.864525E+09 |
| May | 0.596198E+09 | 27343715.25 | 0.568854E+09 | 0.197391E+09 | 0.764012E+09 |
| June | 0.642017E+09 | 45367578.71 | 0.596650E+09 | 0.391186E+09 | 0.554680E+09 |
| July | 0.621747E+09 | 37802934.83 | 0.583944E+09 | 0.506200E+09 | 0.460644E+09 |
| August | 0.479698E+09 | 6974855.40 | 0.472723E+09 | 0.392339E+09 | 0.485203E+09 |
| September | 0.351177E+09 | 26336.37 | 0.351151E+09 | 0.178158E+09 | 0.732518E+09 |
| October | 0.239833E+09 | 0.00 | 0.239833E+09 | 25707118.29 | 0.104300E+10 |
| November | 0.141094E+09 | 0.00 | 0.141094E+09 | 418184.67 | 0.122987E+10 |
| December | 99385396.84 | 0.00 | 99385396.84 | 0.00 | 0.147030E+10 |
| Annual Sum or Average | 0.426545E+10 | 0.119173E+09 | 0.414628E+10 | 0.188602E+10 | 0.112127E+11 |
| Minimum of Months | 99385396.84 | 0.00 | 99385396.84 | 0.00 | 0.460644E+09 |
| Maximum of Months | 0.642017E+09 | 45367578.71 | 0.596650E+09 | 0.506200E+09 | 0.147030E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.137134E+09 | 0.00 | 0.137134E+09 | 967182.74 | 0.135291E+10 |
| February | 0.193325E+09 | 0.00 | 0.193325E+09 | 3444808.49 | 0.117826E+10 |
| March | 0.306704E+09 | 0.00 | 0.306704E+09 | 30200715.45 | 0.107658E+10 |
| April | 0.458760E+09 | 2179287.50 | 0.456581E+09 | 0.160337E+09 | 0.862204E+09 |
| May | 0.600211E+09 | 29426186.27 | 0.570785E+09 | 0.198184E+09 | 0.758637E+09 |
| June | 0.643902E+09 | 45414181.35 | 0.598488E+09 | 0.391580E+09 | 0.552356E+09 |
| July | 0.624893E+09 | 38714887.08 | 0.586179E+09 | 0.507067E+09 | 0.456788E+09 |
| August | 0.482147E+09 | 8029160.92 | 0.474118E+09 | 0.393285E+09 | 0.482214E+09 |
| September | 0.351469E+09 | 51156.96 | 0.351418E+09 | 0.178293E+09 | 0.732227E+09 |
| October | 0.239909E+09 | 0.00 | 0.239909E+09 | 25755524.49 | 0.104297E+10 |
| November | 0.141136E+09 | 0.00 | 0.141136E+09 | 419988.12 | 0.122983E+10 |
| December | 99414874.67 | 0.00 | 99414874.67 | 0.00 | 0.147028E+10 |
| Annual Sum or Average | 0.427901E+10 | 0.123815E+09 | 0.415519E+10 | 0.188953E+10 | 0.111953E+11 |
| Minimum of Months | 99414874.67 | 0.00 | 99414874.67 | 0.00 | 0.456788E+09 |
| Maximum of Months | 0.643902E+09 | 45414181.35 | 0.598488E+09 | 0.507067E+09 | 0.147028E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.173135E+09 | 57204555.42 | 0.115931E+09 | 89435958.47 | 0.630605E+09 |
| February | 0.276879E+09 | 0.116907E+09 | 0.159972E+09 | 0.197381E+09 | 0.552241E+09 |
| March | 0.277182E+09 | 53024880.35 | 0.224157E+09 | 0.140699E+09 | 0.488883E+09 |
| April | 0.632923E+09 | 0.251402E+09 | 0.381520E+09 | 0.601471E+09 | 0.426440E+09 |
| May | 0.767317E+09 | 0.312017E+09 | 0.455299E+09 | 0.722998E+09 | 0.388186E+09 |
| June | 0.801890E+09 | 0.330108E+09 | 0.471782E+09 | 0.845220E+09 | 0.292117E+09 |
| July | 0.843913E+09 | 0.372083E+09 | 0.471829E+09 | 0.966386E+09 | 0.257789E+09 |
| August | 0.708830E+09 | 0.306904E+09 | 0.401927E+09 | 0.817654E+09 | 0.283131E+09 |
| September | 0.550326E+09 | 0.246779E+09 | 0.303547E+09 | 0.574136E+09 | 0.393606E+09 |
| October | 0.303364E+09 | 0.109088E+09 | 0.194275E+09 | 0.228726E+09 | 0.520810E+09 |
| November | 0.158874E+09 | 46377322.20 | 0.112497E+09 | 79095239.41 | 0.588282E+09 |
| December | 92925003.65 | 19609204.17 | 73315799.48 | 27077514.75 | 0.704062E+09 |
| Annual Sum or Average | 0.558756E+10 | 0.222150E+10 | 0.336605E+10 | 0.529028E+10 | 0.552615E+10 |
| Minimum of Months | 92925003.65 | 19609204.17 | 73315799.48 | 27077514.75 | 0.257789E+09 |
| Maximum of Months | 0.843913E+09 | 0.372083E+09 | 0.471829E+09 | 0.966386E+09 | 0.704062E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 70563542.72 | 46130445.44 | 24433097.29 | 68941972.76 | 90182025.62 |
| February | 81074168.31 | 50773409.35 | 30300758.96 | 80684022.36 | 80288056.17 |
| March | 54562940.34 | 16734857.16 | 37828083.18 | 40367555.10 | 73904913.13 |
| April | 0.109824E+09 | 52208406.27 | 57615706.79 | 0.120074E+09 | 66975796.10 |
| May | 92172241.89 | 32140223.95 | 60032017.93 | 89626781.55 | 63483023.59 |
| June | 81187987.02 | 21303339.68 | 59884647.34 | 82870729.79 | 46792287.39 |
| July | 91554999.06 | 30857274.27 | 60697724.78 | 0.107304E+09 | 40745157.83 |
| August | 0.109197E+09 | 51938720.64 | 57257861.81 | 0.137521E+09 | 43404607.47 |
| September | 0.127157E+09 | 77344241.71 | 49812669.69 | 0.154530E+09 | 59081714.11 |
| October | 90574167.14 | 54613427.57 | 35960739.57 | 96664262.71 | 76860352.52 |
| November | 61105130.53 | 37935197.50 | 23169933.03 | 59266116.82 | 85304279.05 |
| December | 47064163.21 | 30312311.37 | 16751851.84 | 44632197.15 | 0.102217E+09 |
| Annual Sum or Average | 0.101604E+10 | 0.502292E+09 | 0.513745E+09 | 0.108248E+10 | 0.829240E+09 |
| Minimum of Months | 47064163.21 | 16734857.16 | 16751851.84 | 40367555.10 | 40745157.83 |
| Maximum of Months | 0.127157E+09 | 77344241.71 | 60697724.78 | 0.154530E+09 | 0.102217E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.480617E+09 | 0.317622E+09 | 0.162995E+09 | 0.468124E+09 | 0.622960E+09 |
| February | 0.555175E+09 | 0.352382E+09 | 0.202793E+09 | 0.552240E+09 | 0.554881E+09 |
| March | 0.368833E+09 | 0.116144E+09 | 0.252689E+09 | 0.270120E+09 | 0.511621E+09 |
| April | 0.742999E+09 | 0.362341E+09 | 0.380658E+09 | 0.811189E+09 | 0.464032E+09 |
| May | 0.617569E+09 | 0.223062E+09 | 0.394507E+09 | 0.598441E+09 | 0.443051E+09 |
| June | 0.540414E+09 | 0.147851E+09 | 0.392562E+09 | 0.548009E+09 | 0.326491E+09 |
| July | 0.611828E+09 | 0.214158E+09 | 0.397669E+09 | 0.716038E+09 | 0.282766E+09 |
| August | 0.736683E+09 | 0.360470E+09 | 0.376213E+09 | 0.929387E+09 | 0.298612E+09 |
| September | 0.866045E+09 | 0.536791E+09 | 0.329254E+09 | 0.105337E+10 | 0.406598E+09 |
| October | 0.618816E+09 | 0.379033E+09 | 0.239783E+09 | 0.660445E+09 | 0.530141E+09 |
| November | 0.418196E+09 | 0.262929E+09 | 0.155267E+09 | 0.405894E+09 | 0.589421E+09 |
| December | 0.319270E+09 | 0.207884E+09 | 0.111386E+09 | 0.302399E+09 | 0.706718E+09 |
| Annual Sum or Average | 0.687645E+10 | 0.348067E+10 | 0.339578E+10 | 0.731565E+10 | 0.573729E+10 |
| Minimum of Months | 0.319270E+09 | 0.116144E+09 | 0.111386E+09 | 0.270120E+09 | 0.282766E+09 |
| Maximum of Months | 0.866045E+09 | 0.536791E+09 | 0.397669E+09 | 0.105337E+10 | 0.706718E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.838127E+09 | 0.558498E+09 | 0.279628E+09 | 0.810505E+09 | 0.125010E+10 |
| February | 0.101045E+10 | 0.645119E+09 | 0.365329E+09 | 0.988090E+09 | 0.110147E+10 |
| March | 0.670129E+09 | 0.213379E+09 | 0.456750E+09 | 0.467773E+09 | 0.102550E+10 |
| April | 0.135059E+10 | 0.665813E+09 | 0.684773E+09 | 0.145847E+10 | 0.911389E+09 |
| May | 0.111787E+10 | 0.409884E+09 | 0.707987E+09 | 0.106769E+10 | 0.868745E+09 |
| June | 0.975389E+09 | 0.271681E+09 | 0.703708E+09 | 0.982150E+09 | 0.626222E+09 |
| July | 0.110620E+10 | 0.393522E+09 | 0.712682E+09 | 0.130297E+10 | 0.528056E+09 |
| August | 0.133748E+10 | 0.662374E+09 | 0.675104E+09 | 0.169524E+10 | 0.559186E+09 |
| September | 0.157880E+10 | 0.986373E+09 | 0.592423E+09 | 0.191497E+10 | 0.782800E+09 |
| October | 0.112736E+10 | 0.694851E+09 | 0.432505E+09 | 0.118850E+10 | 0.104874E+10 |
| November | 0.754978E+09 | 0.477820E+09 | 0.277158E+09 | 0.723315E+09 | 0.117427E+10 |
| December | 0.579325E+09 | 0.379750E+09 | 0.199575E+09 | 0.541930E+09 | 0.140377E+10 |
| Annual Sum or Average | 0.124467E+11 | 0.635907E+10 | 0.608762E+10 | 0.131416E+11 | 0.112803E+11 |
| Minimum of Months | 0.579325E+09 | 0.213379E+09 | 0.199575E+09 | 0.467773E+09 | 0.528056E+09 |
| Maximum of Months | 0.157880E+10 | 0.986373E+09 | 0.712682E+09 | 0.191497E+10 | 0.140377E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.836844E+09 | 0.557815E+09 | 0.279029E+09 | 0.810404E+09 | 0.125187E+10 |
| February | 0.100551E+10 | 0.642088E+09 | 0.363417E+09 | 0.986900E+09 | 0.110815E+10 |
| March | 0.669776E+09 | 0.213298E+09 | 0.456478E+09 | 0.467694E+09 | 0.102595E+10 |
| April | 0.135043E+10 | 0.665813E+09 | 0.684615E+09 | 0.145829E+10 | 0.911385E+09 |
| May | 0.111769E+10 | 0.409884E+09 | 0.707804E+09 | 0.106750E+10 | 0.868759E+09 |
| June | 0.975199E+09 | 0.271681E+09 | 0.703518E+09 | 0.981937E+09 | 0.626227E+09 |
| July | 0.110601E+10 | 0.393522E+09 | 0.712487E+09 | 0.130274E+10 | 0.528048E+09 |
| August | 0.133730E+10 | 0.662374E+09 | 0.674930E+09 | 0.169504E+10 | 0.559164E+09 |
| September | 0.157830E+10 | 0.986158E+09 | 0.592139E+09 | 0.191480E+10 | 0.783417E+09 |
| October | 0.112556E+10 | 0.693804E+09 | 0.431756E+09 | 0.118833E+10 | 0.105155E+10 |
| November | 0.753143E+09 | 0.476751E+09 | 0.276392E+09 | 0.723097E+09 | 0.117677E+10 |
| December | 0.579287E+09 | 0.379748E+09 | 0.199539E+09 | 0.541905E+09 | 0.140375E+10 |
| Annual Sum or Average | 0.124350E+11 | 0.635294E+10 | 0.608211E+10 | 0.131386E+11 | 0.112950E+11 |
| Minimum of Months | 0.579287E+09 | 0.213298E+09 | 0.199539E+09 | 0.467694E+09 | 0.528048E+09 |
| Maximum of Months | 0.157830E+10 | 0.986158E+09 | 0.712487E+09 | 0.191480E+10 | 0.140375E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.771237E+09 | 0.509392E+09 | 0.261844E+09 | 0.728474E+09 | 0.125382E+10 |
| February | 0.936679E+09 | 0.596918E+09 | 0.339761E+09 | 0.905208E+09 | 0.111793E+10 |
| March | 0.631463E+09 | 0.200215E+09 | 0.431248E+09 | 0.428079E+09 | 0.103511E+10 |
| April | 0.129274E+10 | 0.640823E+09 | 0.651919E+09 | 0.138098E+10 | 0.913315E+09 |
| May | 0.107580E+10 | 0.399831E+09 | 0.675972E+09 | 0.101698E+10 | 0.871483E+09 |
| June | 0.938543E+09 | 0.266306E+09 | 0.672238E+09 | 0.937277E+09 | 0.627131E+09 |
| July | 0.106605E+10 | 0.384997E+09 | 0.681051E+09 | 0.125097E+10 | 0.526332E+09 |
| August | 0.128555E+10 | 0.641239E+09 | 0.644309E+09 | 0.162309E+10 | 0.554957E+09 |
| September | 0.149640E+10 | 0.936350E+09 | 0.560050E+09 | 0.180287E+10 | 0.785664E+09 |
| October | 0.104705E+10 | 0.642259E+09 | 0.404790E+09 | 0.109122E+10 | 0.106016E+10 |
| November | 0.699387E+09 | 0.440508E+09 | 0.258880E+09 | 0.658768E+09 | 0.118003E+10 |
| December | 0.535237E+09 | 0.348584E+09 | 0.186653E+09 | 0.488741E+09 | 0.140358E+10 |
| Annual Sum or Average | 0.117761E+11 | 0.600742E+10 | 0.576872E+10 | 0.123126E+11 | 0.113295E+11 |
| Minimum of Months | 0.535237E+09 | 0.200215E+09 | 0.186653E+09 | 0.428079E+09 | 0.526332E+09 |
| Maximum of Months | 0.149640E+10 | 0.936350E+09 | 0.681051E+09 | 0.180287E+10 | 0.140358E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 57711920.74 | 19068248.70 | 38643672.04 | 30023351.27 | 0.223984E+09 |
| February | 92293229.18 | 38969160.85 | 53324068.33 | 66226314.87 | 0.196920E+09 |
| March | 92394264.78 | 17675019.03 | 74719245.74 | 44450382.20 | 0.177975E+09 |
| April | 0.210975E+09 | 83801043.43 | 0.127174E+09 | 0.199772E+09 | 0.150652E+09 |
| May | 0.255773E+09 | 0.104006E+09 | 0.151767E+09 | 0.236693E+09 | 0.140928E+09 |
| June | 0.267298E+09 | 0.110036E+09 | 0.157261E+09 | 0.277001E+09 | 0.105155E+09 |
| July | 0.281305E+09 | 0.124028E+09 | 0.157277E+09 | 0.321069E+09 | 89688359.31 |
| August | 0.236278E+09 | 0.102302E+09 | 0.133976E+09 | 0.274475E+09 | 95789538.73 |
| September | 0.183443E+09 | 82259818.46 | 0.101183E+09 | 0.193654E+09 | 0.134581E+09 |
| October | 0.101122E+09 | 36362868.60 | 64758671.88 | 77205580.48 | 0.183414E+09 |
| November | 52958201.52 | 15459158.93 | 37499042.59 | 26750755.32 | 0.208889E+09 |
| December | 30975104.47 | 6536423.18 | 24438681.29 | 8941014.38 | 0.255880E+09 |
| Annual Sum or Average | 0.186253E+10 | 0.740504E+09 | 0.112202E+10 | 0.175626E+10 | 0.196386E+10 |
| Minimum of Months | 30975104.47 | 6536423.18 | 24438681.29 | 8941014.38 | 89688359.31 |
| Maximum of Months | 0.281305E+09 | 0.124028E+09 | 0.157277E+09 | 0.321069E+09 | 0.255880E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.173135E+09 | 57204555.42 | 0.115931E+09 | 97523728.21 | 0.607291E+09 |
| February | 0.276879E+09 | 0.116907E+09 | 0.159972E+09 | 0.209954E+09 | 0.523282E+09 |
| March | 0.277182E+09 | 53024880.35 | 0.224157E+09 | 0.147852E+09 | 0.477065E+09 |
| April | 0.632923E+09 | 0.251402E+09 | 0.381520E+09 | 0.626882E+09 | 0.400471E+09 |
| May | 0.767317E+09 | 0.312017E+09 | 0.455299E+09 | 0.740404E+09 | 0.372411E+09 |
| June | 0.801890E+09 | 0.330108E+09 | 0.471782E+09 | 0.856136E+09 | 0.284475E+09 |
| July | 0.843913E+09 | 0.372083E+09 | 0.471829E+09 | 0.986617E+09 | 0.244935E+09 |
| August | 0.708830E+09 | 0.306904E+09 | 0.401927E+09 | 0.847445E+09 | 0.258531E+09 |
| September | 0.550326E+09 | 0.246779E+09 | 0.303547E+09 | 0.602577E+09 | 0.359068E+09 |
| October | 0.303364E+09 | 0.109088E+09 | 0.194275E+09 | 0.247381E+09 | 0.486819E+09 |
| November | 0.158874E+09 | 46377322.20 | 0.112497E+09 | 86634840.46 | 0.561174E+09 |
| December | 92925003.65 | 19609204.17 | 73315799.48 | 29623911.34 | 0.689244E+09 |
| Annual Sum or Average | 0.558756E+10 | 0.222150E+10 | 0.336605E+10 | 0.547903E+10 | 0.526477E+10 |
| Minimum of Months | 92925003.65 | 19609204.17 | 73315799.48 | 29623911.34 | 0.244935E+09 |
| Maximum of Months | 0.843913E+09 | 0.372083E+09 | 0.471829E+09 | 0.986617E+09 | 0.689244E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 10962111.36 | 0.00 | 10962111.36 | 164877.77 | 99098007.89 |
| February | 15454571.05 | 0.00 | 15454571.05 | 472603.37 | 85389830.07 |
| March | 24437253.39 | 0.00 | 24437253.39 | 3495968.73 | 77227779.41 |
| April | 36737539.26 | 174669.40 | 36562869.86 | 14414285.12 | 63143966.19 |
| May | 48254806.78 | 2490732.74 | 45764074.03 | 17575707.94 | 55253124.11 |
| June | 51930946.19 | 3597940.95 | 48333005.24 | 32141750.98 | 41004371.31 |
| July | 50414199.87 | 3160263.49 | 47253936.38 | 40333150.80 | 34847852.36 |
| August | 38676061.84 | 648596.75 | 38027465.09 | 31231216.80 | 37097951.96 |
| September | 28209388.89 | 4325.07 | 28205063.82 | 15042716.04 | 54902084.87 |
| October | 19197475.72 | 0.00 | 19197475.72 | 2929895.51 | 75750494.80 |
| November | 11280989.03 | 0.00 | 11280989.03 | 103473.19 | 89083107.49 |
| December | 7945453.85 | 0.00 | 7945453.85 | 0.00 | 0.106973E+09 |
| Annual Sum or Average | 0.343501E+09 | 10076528.40 | 0.333424E+09 | 0.157906E+09 | 0.819771E+09 |
| Minimum of Months | 7945453.85 | 0.00 | 7945453.85 | 0.00 | 34847852.36 |
| Maximum of Months | 51930946.19 | 3597940.95 | 48333005.24 | 40333150.80 | 0.106973E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 79891986.29 | 0.00 | 79891986.29 | 1675913.20 | 0.685198E+09 |
| February | 0.112646E+09 | 0.00 | 0.112646E+09 | 4614147.83 | 0.588080E+09 |
| March | 0.176671E+09 | 0.00 | 0.176671E+09 | 29203657.24 | 0.534165E+09 |
| April | 0.268761E+09 | 1212256.03 | 0.267549E+09 | 0.115025E+09 | 0.437261E+09 |
| May | 0.350791E+09 | 17286404.36 | 0.333505E+09 | 0.139337E+09 | 0.382771E+09 |
| June | 0.376967E+09 | 24970748.95 | 0.351996E+09 | 0.243537E+09 | 0.285823E+09 |
| July | 0.366825E+09 | 21933141.06 | 0.344892E+09 | 0.301102E+09 | 0.243732E+09 |
| August | 0.283624E+09 | 4501493.71 | 0.279123E+09 | 0.235607E+09 | 0.259910E+09 |
| September | 0.207601E+09 | 30624.89 | 0.207570E+09 | 0.117995E+09 | 0.382104E+09 |
| October | 0.140268E+09 | 0.00 | 0.140268E+09 | 26025808.79 | 0.525034E+09 |
| November | 82197653.75 | 0.00 | 82197653.75 | 1162500.67 | 0.616237E+09 |
| December | 57880221.31 | 0.00 | 57880221.31 | 0.00 | 0.742301E+09 |
| Annual Sum or Average | 0.250412E+10 | 69934669.00 | 0.243419E+10 | 0.121529E+10 | 0.568262E+10 |
| Minimum of Months | 57880221.31 | 0.00 | 57880221.31 | 0.00 | 0.243732E+09 |
| Maximum of Months | 0.376967E+09 | 24970748.95 | 0.351996E+09 | 0.301102E+09 | 0.742301E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.131325E+09 | 0.00 | 0.131325E+09 | 627739.15 | 0.135295E+10 |
| February | 0.185332E+09 | 0.00 | 0.185332E+09 | 2571372.44 | 0.118235E+10 |
| March | 0.293754E+09 | 0.00 | 0.293754E+09 | 23701011.74 | 0.108297E+10 |
| April | 0.437362E+09 | 725193.92 | 0.436637E+09 | 0.144216E+09 | 0.871425E+09 |
| May | 0.561168E+09 | 17946703.06 | 0.543221E+09 | 0.172202E+09 | 0.786314E+09 |
| June | 0.603642E+09 | 33794531.05 | 0.569847E+09 | 0.347030E+09 | 0.562725E+09 |
| July | 0.585494E+09 | 27838377.22 | 0.557656E+09 | 0.464636E+09 | 0.466714E+09 |
| August | 0.456111E+09 | 3519135.08 | 0.452592E+09 | 0.372609E+09 | 0.491686E+09 |
| September | 0.337836E+09 | 20560.84 | 0.337815E+09 | 0.166166E+09 | 0.729576E+09 |
| October | 0.230091E+09 | 0.00 | 0.230091E+09 | 20998523.66 | 0.104397E+10 |
| November | 0.135150E+09 | 0.00 | 0.135150E+09 | 216743.06 | 0.123097E+10 |
| December | 95151417.42 | 0.00 | 95151417.42 | 0.00 | 0.146897E+10 |
| Annual Sum or Average | 0.405242E+10 | 83844501.17 | 0.396857E+10 | 0.171497E+10 | 0.112706E+11 |
| Minimum of Months | 95151417.42 | 0.00 | 95151417.42 | 0.00 | 0.466714E+09 |
| Maximum of Months | 0.603642E+09 | 33794531.05 | 0.569847E+09 | 0.464636E+09 | 0.146897E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.139313E+09 | 0.00 | 0.139313E+09 | 1155445.67 | 0.135089E+10 |
| February | 0.196404E+09 | 0.00 | 0.196404E+09 | 3854417.06 | 0.117640E+10 |
| March | 0.310746E+09 | 0.00 | 0.310746E+09 | 32303833.05 | 0.107558E+10 |
| April | 0.465451E+09 | 1679865.86 | 0.463771E+09 | 0.167996E+09 | 0.863727E+09 |
| May | 0.606752E+09 | 28041431.02 | 0.578710E+09 | 0.206588E+09 | 0.761567E+09 |
| June | 0.653181E+09 | 45949312.55 | 0.607232E+09 | 0.402910E+09 | 0.553624E+09 |
| July | 0.633048E+09 | 38473458.41 | 0.594574E+09 | 0.518834E+09 | 0.459970E+09 |
| August | 0.488914E+09 | 7117441.77 | 0.481797E+09 | 0.403299E+09 | 0.485995E+09 |
| September | 0.358059E+09 | 26336.51 | 0.358033E+09 | 0.185211E+09 | 0.732918E+09 |
| October | 0.243928E+09 | 0.00 | 0.243928E+09 | 28211086.71 | 0.104265E+10 |
| November | 0.143368E+09 | 0.00 | 0.143368E+09 | 525489.26 | 0.122868E+10 |
| December | 0.100979E+09 | 0.00 | 0.100979E+09 | 0.00 | 0.147016E+10 |
| Annual Sum or Average | 0.434014E+10 | 0.121288E+09 | 0.421885E+10 | 0.195089E+10 | 0.112022E+11 |
| Minimum of Months | 0.100979E+09 | 0.00 | 0.100979E+09 | 0.00 | 0.459970E+09 |
| Maximum of Months | 0.653181E+09 | 45949312.55 | 0.607232E+09 | 0.518834E+09 | 0.147016E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.139310E+09 | 0.00 | 0.139310E+09 | 1155422.08 | 0.135086E+10 |
| February | 0.196401E+09 | 0.00 | 0.196401E+09 | 3854339.49 | 0.117638E+10 |
| March | 0.310740E+09 | 0.00 | 0.310740E+09 | 32303191.30 | 0.107556E+10 |
| April | 0.466634E+09 | 2179287.69 | 0.464455E+09 | 0.168047E+09 | 0.861528E+09 |
| May | 0.611069E+09 | 30450287.78 | 0.580619E+09 | 0.207446E+09 | 0.755703E+09 |
| June | 0.655275E+09 | 45949609.20 | 0.609325E+09 | 0.403053E+09 | 0.550691E+09 |
| July | 0.636452E+09 | 39462092.74 | 0.596990E+09 | 0.519567E+09 | 0.455531E+09 |
| August | 0.491208E+09 | 8232936.99 | 0.482975E+09 | 0.403806E+09 | 0.482702E+09 |
| September | 0.358215E+09 | 51157.11 | 0.358164E+09 | 0.185207E+09 | 0.732615E+09 |
| October | 0.243923E+09 | 0.00 | 0.243923E+09 | 28210522.20 | 0.104263E+10 |
| November | 0.143365E+09 | 0.00 | 0.143365E+09 | 525478.35 | 0.122866E+10 |
| December | 0.100977E+09 | 0.00 | 0.100977E+09 | 0.00 | 0.147013E+10 |
| Annual Sum or Average | 0.435357E+10 | 0.126325E+09 | 0.422724E+10 | 0.195318E+10 | 0.111830E+11 |
| Minimum of Months | 0.100977E+09 | 0.00 | 0.100977E+09 | 0.00 | 0.455531E+09 |
| Maximum of Months | 0.655275E+09 | 45949609.20 | 0.609325E+09 | 0.519567E+09 | 0.147013E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.173135E+09 | 57204555.42 | 0.115931E+09 | 88922423.29 | 0.632962E+09 |
| February | 0.276879E+09 | 0.116907E+09 | 0.159972E+09 | 0.197034E+09 | 0.553751E+09 |
| March | 0.277182E+09 | 53024880.35 | 0.224157E+09 | 0.140049E+09 | 0.490769E+09 |
| April | 0.632923E+09 | 0.251402E+09 | 0.381520E+09 | 0.600171E+09 | 0.428659E+09 |
| May | 0.767317E+09 | 0.312017E+09 | 0.455299E+09 | 0.721725E+09 | 0.389933E+09 |
| June | 0.801890E+09 | 0.330108E+09 | 0.471782E+09 | 0.844058E+09 | 0.293424E+09 |
| July | 0.843913E+09 | 0.372083E+09 | 0.471829E+09 | 0.964206E+09 | 0.259910E+09 |
| August | 0.708830E+09 | 0.306904E+09 | 0.401927E+09 | 0.816007E+09 | 0.285061E+09 |
| September | 0.550326E+09 | 0.246779E+09 | 0.303547E+09 | 0.573031E+09 | 0.395636E+09 |
| October | 0.303364E+09 | 0.109088E+09 | 0.194275E+09 | 0.228012E+09 | 0.523547E+09 |
| November | 0.158874E+09 | 46377322.20 | 0.112497E+09 | 78683091.41 | 0.591384E+09 |
| December | 92925003.65 | 19609204.17 | 73315799.48 | 26909083.13 | 0.706208E+09 |
| Annual Sum or Average | 0.558756E+10 | 0.222150E+10 | 0.336605E+10 | 0.527881E+10 | 0.555124E+10 |
| Minimum of Months | 92925003.65 | 19609204.17 | 73315799.48 | 26909083.13 | 0.259910E+09 |
| Maximum of Months | 0.843913E+09 | 0.372083E+09 | 0.471829E+09 | 0.964206E+09 | 0.706208E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 71677279.89 | 46951638.70 | 24725641.18 | 70010704.04 | 90222159.50 |
| February | 81359309.31 | 50875572.08 | 30483737.23 | 80853657.87 | 80420593.40 |
| March | 54747081.97 | 16734857.16 | 38012224.81 | 40450274.63 | 74213369.02 |
| April | 0.110183E+09 | 52208406.27 | 57974924.08 | 0.120310E+09 | 67351459.51 |
| May | 92586073.41 | 32140223.95 | 60445849.46 | 89913062.79 | 63766623.65 |
| June | 81619056.19 | 21303339.68 | 60315716.51 | 83215681.63 | 47015017.91 |
| July | 91996093.71 | 30857274.27 | 61138819.44 | 0.107531E+09 | 41127059.41 |
| August | 0.109592E+09 | 51938720.64 | 57653757.00 | 0.137760E+09 | 43773605.22 |
| September | 0.127468E+09 | 77345792.51 | 50121751.34 | 0.154718E+09 | 59452749.60 |
| October | 90811498.82 | 54650214.00 | 36161284.81 | 96768126.95 | 77278151.57 |
| November | 61580847.43 | 38218856.01 | 23361991.42 | 59610563.17 | 85614695.17 |
| December | 48316013.03 | 31237983.02 | 17078030.01 | 45931509.88 | 0.102230E+09 |
| Annual Sum or Average | 0.102194E+10 | 0.504463E+09 | 0.517474E+09 | 0.108707E+10 | 0.832465E+09 |
| Minimum of Months | 48316013.03 | 16734857.16 | 17078030.01 | 40450274.63 | 41127059.41 |
| Maximum of Months | 0.127468E+09 | 77345792.51 | 61138819.44 | 0.154718E+09 | 0.102230E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.492116E+09 | 0.325457E+09 | 0.166660E+09 | 0.480463E+09 | 0.623400E+09 |
| February | 0.557959E+09 | 0.353091E+09 | 0.204868E+09 | 0.554235E+09 | 0.556042E+09 |
| March | 0.371167E+09 | 0.116144E+09 | 0.255023E+09 | 0.271765E+09 | 0.513895E+09 |
| April | 0.747553E+09 | 0.362341E+09 | 0.385212E+09 | 0.815192E+09 | 0.466721E+09 |
| May | 0.622816E+09 | 0.223062E+09 | 0.399753E+09 | 0.602915E+09 | 0.444851E+09 |
| June | 0.545879E+09 | 0.147851E+09 | 0.398027E+09 | 0.553186E+09 | 0.327963E+09 |
| July | 0.617420E+09 | 0.214158E+09 | 0.403261E+09 | 0.720574E+09 | 0.285524E+09 |
| August | 0.741702E+09 | 0.360470E+09 | 0.381232E+09 | 0.933721E+09 | 0.301472E+09 |
| September | 0.869967E+09 | 0.536802E+09 | 0.333165E+09 | 0.105672E+10 | 0.409542E+09 |
| October | 0.621514E+09 | 0.379288E+09 | 0.242226E+09 | 0.662281E+09 | 0.533390E+09 |
| November | 0.422404E+09 | 0.265150E+09 | 0.157255E+09 | 0.409204E+09 | 0.591807E+09 |
| December | 0.330836E+09 | 0.216056E+09 | 0.114780E+09 | 0.314723E+09 | 0.706675E+09 |
| Annual Sum or Average | 0.694133E+10 | 0.349987E+10 | 0.344146E+10 | 0.737498E+10 | 0.576128E+10 |
| Minimum of Months | 0.330836E+09 | 0.116144E+09 | 0.114780E+09 | 0.271765E+09 | 0.285524E+09 |
| Maximum of Months | 0.869967E+09 | 0.536802E+09 | 0.403261E+09 | 0.105672E+10 | 0.706675E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.866264E+09 | 0.577354E+09 | 0.288910E+09 | 0.836990E+09 | 0.124746E+10 |
| February | 0.101748E+10 | 0.647711E+09 | 0.369774E+09 | 0.992506E+09 | 0.110398E+10 |
| March | 0.674244E+09 | 0.213412E+09 | 0.460832E+09 | 0.469355E+09 | 0.103275E+10 |
| April | 0.135855E+10 | 0.665857E+09 | 0.692694E+09 | 0.146418E+10 | 0.918831E+09 |
| May | 0.112702E+10 | 0.409911E+09 | 0.717106E+09 | 0.107448E+10 | 0.873694E+09 |
| June | 0.984904E+09 | 0.271699E+09 | 0.713205E+09 | 0.990088E+09 | 0.630179E+09 |
| July | 0.111595E+10 | 0.393548E+09 | 0.722399E+09 | 0.130928E+10 | 0.534632E+09 |
| August | 0.134625E+10 | 0.662417E+09 | 0.683828E+09 | 0.170136E+10 | 0.566016E+09 |
| September | 0.158568E+10 | 0.986455E+09 | 0.599224E+09 | 0.191963E+10 | 0.790273E+09 |
| October | 0.113290E+10 | 0.695923E+09 | 0.436981E+09 | 0.119139E+10 | 0.105820E+10 |
| November | 0.766231E+09 | 0.483979E+09 | 0.282253E+09 | 0.731139E+09 | 0.118067E+10 |
| December | 0.601613E+09 | 0.395539E+09 | 0.206074E+09 | 0.564124E+09 | 0.140433E+10 |
| Annual Sum or Average | 0.125771E+11 | 0.640380E+10 | 0.617328E+10 | 0.132445E+11 | 0.113410E+11 |
| Minimum of Months | 0.601613E+09 | 0.213412E+09 | 0.206074E+09 | 0.469355E+09 | 0.534632E+09 |
| Maximum of Months | 0.158568E+10 | 0.986455E+09 | 0.722399E+09 | 0.191963E+10 | 0.140433E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.863242E+09 | 0.575604E+09 | 0.287638E+09 | 0.836608E+09 | 0.125145E+10 |
| February | 0.101235E+10 | 0.644495E+09 | 0.367851E+09 | 0.991235E+09 | 0.111087E+10 |
| March | 0.673921E+09 | 0.213314E+09 | 0.460606E+09 | 0.469324E+09 | 0.103315E+10 |
| April | 0.135846E+10 | 0.665813E+09 | 0.692647E+09 | 0.146408E+10 | 0.918771E+09 |
| May | 0.112694E+10 | 0.409884E+09 | 0.717058E+09 | 0.107441E+10 | 0.873637E+09 |
| June | 0.984838E+09 | 0.271681E+09 | 0.713157E+09 | 0.990022E+09 | 0.630138E+09 |
| July | 0.111587E+10 | 0.393522E+09 | 0.722350E+09 | 0.130920E+10 | 0.534597E+09 |
| August | 0.134616E+10 | 0.662374E+09 | 0.683783E+09 | 0.170125E+10 | 0.565979E+09 |
| September | 0.158531E+10 | 0.986234E+09 | 0.599074E+09 | 0.191948E+10 | 0.790682E+09 |
| October | 0.113106E+10 | 0.694738E+09 | 0.436320E+09 | 0.119112E+10 | 0.106093E+10 |
| November | 0.763859E+09 | 0.482557E+09 | 0.281302E+09 | 0.730744E+09 | 0.118374E+10 |
| December | 0.601533E+09 | 0.395498E+09 | 0.206035E+09 | 0.564083E+09 | 0.140430E+10 |
| Annual Sum or Average | 0.125635E+11 | 0.639572E+10 | 0.616782E+10 | 0.132416E+11 | 0.113582E+11 |
| Minimum of Months | 0.601533E+09 | 0.213314E+09 | 0.206035E+09 | 0.469324E+09 | 0.534597E+09 |
| Maximum of Months | 0.158531E+10 | 0.986234E+09 | 0.722350E+09 | 0.191948E+10 | 0.140430E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.790467E+09 | 0.521953E+09 | 0.268513E+09 | 0.746280E+09 | 0.125438E+10 |
| February | 0.940850E+09 | 0.598099E+09 | 0.342751E+09 | 0.907475E+09 | 0.112185E+10 |
| March | 0.634355E+09 | 0.200222E+09 | 0.434133E+09 | 0.428545E+09 | 0.104218E+10 |
| April | 0.129833E+10 | 0.640789E+09 | 0.657537E+09 | 0.138400E+10 | 0.920593E+09 |
| May | 0.108226E+10 | 0.399808E+09 | 0.682448E+09 | 0.102096E+10 | 0.876492E+09 |
| June | 0.945274E+09 | 0.266290E+09 | 0.678984E+09 | 0.942052E+09 | 0.631038E+09 |
| July | 0.107293E+10 | 0.384975E+09 | 0.687956E+09 | 0.125395E+10 | 0.532742E+09 |
| August | 0.129171E+10 | 0.641206E+09 | 0.650504E+09 | 0.162614E+10 | 0.561393E+09 |
| September | 0.150124E+10 | 0.936345E+09 | 0.564891E+09 | 0.180513E+10 | 0.792602E+09 |
| October | 0.105080E+10 | 0.642848E+09 | 0.407955E+09 | 0.109236E+10 | 0.106949E+10 |
| November | 0.706530E+09 | 0.444149E+09 | 0.262381E+09 | 0.662646E+09 | 0.118759E+10 |
| December | 0.550666E+09 | 0.359388E+09 | 0.191278E+09 | 0.502597E+09 | 0.140455E+10 |
| Annual Sum or Average | 0.118654E+11 | 0.603607E+10 | 0.582933E+10 | 0.123721E+11 | 0.113949E+11 |
| Minimum of Months | 0.550666E+09 | 0.200222E+09 | 0.191278E+09 | 0.428545E+09 | 0.532742E+09 |
| Maximum of Months | 0.150124E+10 | 0.936345E+09 | 0.687956E+09 | 0.180513E+10 | 0.140455E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 57711920.74 | 19068248.70 | 38643672.04 | 29810952.79 | 0.225581E+09 |
| February | 92293229.18 | 38969160.85 | 53324068.33 | 65905512.10 | 0.198573E+09 |
| March | 92394264.78 | 17675019.03 | 74719245.74 | 43713246.55 | 0.180300E+09 |
| April | 0.210975E+09 | 83801043.43 | 0.127174E+09 | 0.198322E+09 | 0.153139E+09 |
| May | 0.255773E+09 | 0.104006E+09 | 0.151767E+09 | 0.235286E+09 | 0.143015E+09 |
| June | 0.267298E+09 | 0.110036E+09 | 0.157261E+09 | 0.275670E+09 | 0.106809E+09 |
| July | 0.281305E+09 | 0.124028E+09 | 0.157277E+09 | 0.318667E+09 | 91904912.24 |
| August | 0.236278E+09 | 0.102302E+09 | 0.133976E+09 | 0.272579E+09 | 97856087.12 |
| September | 0.183443E+09 | 82259818.46 | 0.101183E+09 | 0.192406E+09 | 0.136944E+09 |
| October | 0.101122E+09 | 36362868.60 | 64758671.88 | 76436913.12 | 0.186580E+09 |
| November | 52958201.52 | 15459158.93 | 37499042.59 | 26397023.38 | 0.211914E+09 |
| December | 30975104.47 | 6536423.18 | 24438681.29 | 8873489.50 | 0.257596E+09 |
| Annual Sum or Average | 0.186253E+10 | 0.740504E+09 | 0.112202E+10 | 0.174407E+10 | 0.199021E+10 |
| Minimum of Months | 30975104.47 | 6536423.18 | 24438681.29 | 8873489.50 | 91904912.24 |
| Maximum of Months | 0.281305E+09 | 0.124028E+09 | 0.157277E+09 | 0.318667E+09 | 0.257596E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13407873.98 | 0.00 | 13407873.98 | 601871.64 | 98798906.44 |
| February | 18910802.87 | 0.00 | 18910802.87 | 1581744.60 | 84339153.68 |
| March | 28973040.02 | 0.00 | 28973040.02 | 6807060.22 | 76986365.62 |
| April | 45650941.78 | 204313.25 | 45446628.54 | 23524256.64 | 63418056.61 |
| May | 58977812.93 | 2845378.41 | 56132434.52 | 28468980.36 | 55060758.56 |
| June | 63093153.24 | 3956326.38 | 59136826.86 | 44738361.93 | 41615372.38 |
| July | 61842204.24 | 3525930.27 | 58316273.97 | 53138882.28 | 35939447.72 |
| August | 48611177.20 | 761611.57 | 47849565.63 | 42460521.59 | 38868208.01 |
| September | 35806245.09 | 7923.15 | 35798321.94 | 22832504.55 | 56449057.62 |
| October | 23709166.39 | 0.00 | 23709166.39 | 6422817.35 | 76671919.92 |
| November | 13786144.15 | 0.00 | 13786144.15 | 523632.45 | 88989752.66 |
| December | 9701272.61 | 0.00 | 9701272.61 | 4168.38 | 0.107352E+09 |
| Annual Sum or Average | 0.422470E+09 | 11301483.02 | 0.411168E+09 | 0.231105E+09 | 0.824489E+09 |
| Minimum of Months | 9701272.61 | 0.00 | 9701272.61 | 4168.38 | 35939447.72 |
| Maximum of Months | 63093153.24 | 3956326.38 | 59136826.86 | 53138882.28 | 0.107352E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.173135E+09 | 57204555.42 | 0.115931E+09 | 97248339.34 | 0.608162E+09 |
| February | 0.276879E+09 | 0.116907E+09 | 0.159972E+09 | 0.209422E+09 | 0.524512E+09 |
| March | 0.277182E+09 | 53024880.35 | 0.224157E+09 | 0.146794E+09 | 0.479102E+09 |
| April | 0.632923E+09 | 0.251402E+09 | 0.381520E+09 | 0.623695E+09 | 0.403977E+09 |
| May | 0.767317E+09 | 0.312017E+09 | 0.455299E+09 | 0.736783E+09 | 0.375744E+09 |
| June | 0.801890E+09 | 0.330108E+09 | 0.471782E+09 | 0.852484E+09 | 0.287333E+09 |
| July | 0.843913E+09 | 0.372083E+09 | 0.471829E+09 | 0.981738E+09 | 0.248493E+09 |
| August | 0.708830E+09 | 0.306904E+09 | 0.401927E+09 | 0.844149E+09 | 0.261208E+09 |
| September | 0.550326E+09 | 0.246779E+09 | 0.303547E+09 | 0.600176E+09 | 0.361905E+09 |
| October | 0.303364E+09 | 0.109088E+09 | 0.194275E+09 | 0.246141E+09 | 0.489515E+09 |
| November | 0.158874E+09 | 46377322.20 | 0.112497E+09 | 86193675.99 | 0.563302E+09 |
| December | 92925003.65 | 19609204.17 | 73315799.48 | 29540093.78 | 0.689830E+09 |
| Annual Sum or Average | 0.558756E+10 | 0.222150E+10 | 0.336605E+10 | 0.545436E+10 | 0.529309E+10 |
| Minimum of Months | 92925003.65 | 19609204.17 | 73315799.48 | 29540093.78 | 0.248493E+09 |
| Maximum of Months | 0.843913E+09 | 0.372083E+09 | 0.471829E+09 | 0.981738E+09 | 0.689830E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 92684021.21 | 0.00 | 92684021.21 | 4265509.04 | 0.681410E+09 |
| February | 0.130724E+09 | 0.00 | 0.130724E+09 | 11108269.75 | 0.581105E+09 |
| March | 0.200281E+09 | 0.00 | 0.200281E+09 | 47195292.10 | 0.531856E+09 |
| April | 0.315569E+09 | 1412345.47 | 0.314157E+09 | 0.163322E+09 | 0.438348E+09 |
| May | 0.407693E+09 | 19669098.32 | 0.388024E+09 | 0.197152E+09 | 0.380615E+09 |
| June | 0.436141E+09 | 27348690.21 | 0.408793E+09 | 0.309479E+09 | 0.287674E+09 |
| July | 0.427494E+09 | 24373513.56 | 0.403121E+09 | 0.367682E+09 | 0.248438E+09 |
| August | 0.336033E+09 | 5264752.41 | 0.330768E+09 | 0.294220E+09 | 0.268682E+09 |
| September | 0.247516E+09 | 54769.93 | 0.247462E+09 | 0.159128E+09 | 0.389946E+09 |
| October | 0.163893E+09 | 0.00 | 0.163893E+09 | 45112689.29 | 0.529305E+09 |
| November | 95298871.99 | 0.00 | 95298871.99 | 3695658.72 | 0.614198E+09 |
| December | 67061557.43 | 0.00 | 67061557.43 | 31073.95 | 0.741567E+09 |
| Annual Sum or Average | 0.292039E+10 | 78123169.91 | 0.284227E+10 | 0.160239E+10 | 0.569314E+10 |
| Minimum of Months | 67061557.43 | 0.00 | 67061557.43 | 31073.95 | 0.248438E+09 |
| Maximum of Months | 0.436141E+09 | 27348690.21 | 0.408793E+09 | 0.367682E+09 | 0.741567E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.112917E+09 | 0.00 | 0.112917E+09 | 3343816.43 | 0.888609E+09 |
| February | 0.159261E+09 | 0.00 | 0.159261E+09 | 9410374.89 | 0.765707E+09 |
| March | 0.244002E+09 | 0.00 | 0.244002E+09 | 46202159.37 | 0.706528E+09 |
| April | 0.384458E+09 | 1720659.88 | 0.382737E+09 | 0.186729E+09 | 0.570904E+09 |
| May | 0.496693E+09 | 23962853.99 | 0.472730E+09 | 0.227415E+09 | 0.494745E+09 |
| June | 0.531351E+09 | 33318897.47 | 0.498032E+09 | 0.372327E+09 | 0.366113E+09 |
| July | 0.520816E+09 | 29694241.04 | 0.491122E+09 | 0.452378E+09 | 0.308276E+09 |
| August | 0.409388E+09 | 6414045.59 | 0.402974E+09 | 0.361760E+09 | 0.333810E+09 |
| September | 0.301549E+09 | 66726.19 | 0.301482E+09 | 0.187441E+09 | 0.497421E+09 |
| October | 0.199671E+09 | 0.00 | 0.199671E+09 | 46041777.85 | 0.695614E+09 |
| November | 0.116103E+09 | 0.00 | 0.116103E+09 | 2540531.17 | 0.810640E+09 |
| December | 81701071.10 | 0.00 | 81701071.10 | 0.00 | 0.973951E+09 |
| Annual Sum or Average | 0.355791E+10 | 95177424.16 | 0.346273E+10 | 0.189559E+10 | 0.741232E+10 |
| Minimum of Months | 81701071.10 | 0.00 | 81701071.10 | 0.00 | 0.308276E+09 |
| Maximum of Months | 0.531351E+09 | 33318897.47 | 0.498032E+09 | 0.452378E+09 | 0.973951E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.112916E+09 | 0.00 | 0.112916E+09 | 3343681.65 | 0.888609E+09 |
| February | 0.159260E+09 | 0.00 | 0.159260E+09 | 9410048.62 | 0.765708E+09 |
| March | 0.244000E+09 | 0.00 | 0.244000E+09 | 46200877.26 | 0.706528E+09 |
| April | 0.384456E+09 | 1720643.98 | 0.382735E+09 | 0.186726E+09 | 0.570904E+09 |
| May | 0.496690E+09 | 23962632.53 | 0.472727E+09 | 0.227411E+09 | 0.494745E+09 |
| June | 0.531348E+09 | 33318589.56 | 0.498029E+09 | 0.372323E+09 | 0.366113E+09 |
| July | 0.520813E+09 | 29693966.62 | 0.491119E+09 | 0.452374E+09 | 0.308276E+09 |
| August | 0.409386E+09 | 6413986.31 | 0.402972E+09 | 0.361758E+09 | 0.333810E+09 |
| September | 0.301547E+09 | 66725.57 | 0.301481E+09 | 0.187439E+09 | 0.497421E+09 |
| October | 0.199670E+09 | 0.00 | 0.199670E+09 | 46040870.90 | 0.695614E+09 |
| November | 0.116102E+09 | 0.00 | 0.116102E+09 | 2540400.00 | 0.810640E+09 |
| December | 81700510.56 | 0.00 | 81700510.56 | 0.00 | 0.973951E+09 |
| Annual Sum or Average | 0.355789E+10 | 95176544.58 | 0.346271E+10 | 0.189557E+10 | 0.741232E+10 |
| Minimum of Months | 81700510.56 | 0.00 | 81700510.56 | 0.00 | 0.308276E+09 |
| Maximum of Months | 0.531348E+09 | 33318589.56 | 0.498029E+09 | 0.452374E+09 | 0.973951E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.112913E+09 | 0.00 | 0.112913E+09 | 3343653.35 | 0.888579E+09 |
| February | 0.159255E+09 | 0.00 | 0.159255E+09 | 9409936.09 | 0.765682E+09 |
| March | 0.243993E+09 | 0.00 | 0.243993E+09 | 46200126.52 | 0.706504E+09 |
| April | 0.384444E+09 | 1720596.27 | 0.382724E+09 | 0.186722E+09 | 0.570885E+09 |
| May | 0.496675E+09 | 23961968.17 | 0.472713E+09 | 0.227406E+09 | 0.494728E+09 |
| June | 0.531332E+09 | 33317665.80 | 0.498014E+09 | 0.372313E+09 | 0.366100E+09 |
| July | 0.520797E+09 | 29693143.36 | 0.491104E+09 | 0.452361E+09 | 0.308265E+09 |
| August | 0.409374E+09 | 6413808.49 | 0.402960E+09 | 0.361747E+09 | 0.333799E+09 |
| September | 0.301538E+09 | 66723.72 | 0.301472E+09 | 0.187434E+09 | 0.497405E+09 |
| October | 0.199664E+09 | 0.00 | 0.199664E+09 | 46039892.91 | 0.695591E+09 |
| November | 0.116098E+09 | 0.00 | 0.116098E+09 | 2540396.33 | 0.810613E+09 |
| December | 81698124.83 | 0.00 | 81698124.83 | 0.00 | 0.973918E+09 |
| Annual Sum or Average | 0.355778E+10 | 95173905.82 | 0.346261E+10 | 0.189552E+10 | 0.741207E+10 |
| Minimum of Months | 81698124.83 | 0.00 | 81698124.83 | 0.00 | 0.308265E+09 |
| Maximum of Months | 0.531332E+09 | 33317665.80 | 0.498014E+09 | 0.452361E+09 | 0.973918E+09 |
Report: WindowEnergyReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 12733111.50 | 0.00 | 12733111.50 | 264044.51 | 0.104721E+09 |
| February | 17959094.81 | 0.00 | 17959094.81 | 802609.49 | 91388770.51 |
| March | 27514961.80 | 0.00 | 27514961.80 | 4176072.92 | 85401388.56 |
| April | 43353454.43 | 194031.95 | 43159422.48 | 19242340.06 | 69343878.90 |
| May | 56009643.93 | 2702195.46 | 53307448.47 | 23433066.80 | 59944503.20 |
| June | 59917884.02 | 3757239.16 | 56160644.86 | 39376353.30 | 44314985.45 |
| July | 58729868.02 | 3348501.12 | 55381366.90 | 47034279.21 | 37913858.19 |
| August | 46164691.42 | 723286.34 | 45441405.09 | 37426863.23 | 41239569.86 |
| September | 34004199.64 | 7524.45 | 33996675.19 | 19020342.42 | 61186511.21 |
| October | 22515968.43 | 0.00 | 22515968.43 | 4204079.62 | 84957005.35 |
| November | 13092345.34 | 0.00 | 13092345.34 | 146142.19 | 97968619.64 |
| December | 9213049.80 | 0.00 | 9213049.80 | 0.00 | 0.115131E+09 |
| Annual Sum or Average | 0.401208E+09 | 10732778.47 | 0.390475E+09 | 0.195126E+09 | 0.893511E+09 |
| Minimum of Months | 9213049.80 | 0.00 | 9213049.80 | 0.00 | 37913858.19 |
| Maximum of Months | 59917884.02 | 3757239.16 | 56160644.86 | 47034279.21 | 0.115131E+09 |
Report: WindowEnergyReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.161478E+09 | 0.00 | 0.161478E+09 | 3348548.72 | 0.132805E+10 |
| February | 0.227753E+09 | 0.00 | 0.227753E+09 | 10178499.75 | 0.115897E+10 |
| March | 0.348938E+09 | 0.00 | 0.348938E+09 | 52959948.39 | 0.108304E+10 |
| April | 0.549798E+09 | 2460666.35 | 0.547337E+09 | 0.244027E+09 | 0.879402E+09 |
| May | 0.710301E+09 | 34268590.31 | 0.676032E+09 | 0.297172E+09 | 0.760202E+09 |
| June | 0.759864E+09 | 47648399.80 | 0.712216E+09 | 0.499361E+09 | 0.561992E+09 |
| July | 0.744798E+09 | 42464882.58 | 0.702333E+09 | 0.596477E+09 | 0.480814E+09 |
| August | 0.585449E+09 | 9172542.66 | 0.576277E+09 | 0.474638E+09 | 0.522990E+09 |
| September | 0.431233E+09 | 95423.21 | 0.431138E+09 | 0.241211E+09 | 0.775953E+09 |
| October | 0.285542E+09 | 0.00 | 0.285542E+09 | 53315122.61 | 0.107740E+10 |
| November | 0.166034E+09 | 0.00 | 0.166034E+09 | 1853339.99 | 0.124241E+10 |
| December | 0.116838E+09 | 0.00 | 0.116838E+09 | 0.00 | 0.146007E+10 |
| Annual Sum or Average | 0.508803E+10 | 0.136111E+09 | 0.495192E+10 | 0.247454E+10 | 0.113313E+11 |
| Minimum of Months | 0.116838E+09 | 0.00 | 0.116838E+09 | 0.00 | 0.480814E+09 |
| Maximum of Months | 0.759864E+09 | 47648399.80 | 0.712216E+09 | 0.596477E+09 | 0.146007E+10 |
Report: WindowEnergyReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 16679671.37 | 5124614.18 | 11555057.19 | 6918911.61 | 0.106509E+09 |
| February | 34684913.96 | 16575535.35 | 18109378.61 | 26023719.51 | 93913244.22 |
| March | 33889122.30 | 8387321.97 | 25501800.33 | 14899866.28 | 86684812.68 |
| April | 81871502.86 | 37185123.46 | 44686379.41 | 75751577.63 | 74548607.54 |
| May | 87769709.19 | 38311376.54 | 49458332.65 | 76556882.16 | 75746126.87 |
| June | 88963784.46 | 37943214.92 | 51020569.54 | 86566581.32 | 56293574.41 |
| July | 96307387.72 | 44525124.96 | 51782262.76 | 0.103835E+09 | 49338695.49 |
| August | 90922968.03 | 44171590.40 | 46751377.63 | 0.102506E+09 | 48875382.22 |
| September | 74874896.41 | 38527940.60 | 36346955.81 | 79460922.44 | 63717337.87 |
| October | 38977964.86 | 16507842.67 | 22470122.19 | 30353263.83 | 86081125.30 |
| November | 18215573.39 | 5961973.37 | 12253600.03 | 9425377.79 | 97622655.44 |
| December | 9866032.68 | 2142931.83 | 7723100.85 | 2373374.28 | 0.119134E+09 |
| Annual Sum or Average | 0.673024E+09 | 0.295365E+09 | 0.377659E+09 | 0.614672E+09 | 0.958464E+09 |
| Minimum of Months | 9866032.68 | 2142931.83 | 7723100.85 | 2373374.28 | 48875382.22 |
| Maximum of Months | 96307387.72 | 44525124.96 | 51782262.76 | 0.103835E+09 | 0.119134E+09 |
Report: WindowEnergyReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58598446.16 | 2021662.11 | 56576784.05 | 800853.99 | 0.583352E+09 |
| February | 0.110925E+09 | 24949322.47 | 85975457.81 | 30730956.41 | 0.504443E+09 |
| March | 0.167118E+09 | 26630217.56 | 0.140488E+09 | 51159210.59 | 0.456872E+09 |
| April | 0.428742E+09 | 0.179014E+09 | 0.249728E+09 | 0.376204E+09 | 0.388523E+09 |
| May | 0.535398E+09 | 0.234684E+09 | 0.300714E+09 | 0.470127E+09 | 0.380648E+09 |
| June | 0.573440E+09 | 0.261907E+09 | 0.311533E+09 | 0.575784E+09 | 0.284790E+09 |
| July | 0.599718E+09 | 0.288207E+09 | 0.311511E+09 | 0.653593E+09 | 0.253566E+09 |
| August | 0.487974E+09 | 0.224870E+09 | 0.263104E+09 | 0.536710E+09 | 0.258897E+09 |
| September | 0.336252E+09 | 0.146459E+09 | 0.189793E+09 | 0.324123E+09 | 0.340603E+09 |
| October | 0.150776E+09 | 39027583.37 | 0.111748E+09 | 74951326.78 | 0.461145E+09 |
| November | 64817992.10 | 5219692.29 | 59598299.81 | 4153627.49 | 0.527981E+09 |
| December | 41064882.90 | 576448.96 | 40488433.93 | 0.00 | 0.646290E+09 |
| Annual Sum or Average | 0.355482E+10 | 0.143357E+10 | 0.212126E+10 | 0.309834E+10 | 0.508711E+10 |
| Minimum of Months | 41064882.90 | 576448.96 | 40488433.93 | 0.00 | 0.253566E+09 |
| Maximum of Months | 0.599718E+09 | 0.288207E+09 | 0.311533E+09 | 0.653593E+09 | 0.646290E+09 |
Report: WindowEnergyReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 71992045.91 | 46603407.92 | 25388638.00 | 72463694.84 | 78468844.25 |
| February | 79416182.22 | 48460841.01 | 30955341.22 | 81353263.10 | 72101505.59 |
| March | 54361057.03 | 15827497.79 | 38533559.23 | 43773046.50 | 66597940.37 |
| April | 0.109244E+09 | 49376884.22 | 59866844.00 | 0.123940E+09 | 60918875.31 |
| May | 93366529.06 | 30397099.44 | 62969429.62 | 95470812.18 | 57769584.42 |
| June | 83235979.83 | 20147953.41 | 63088026.43 | 89011723.89 | 43449374.45 |
| July | 93190766.58 | 29183730.51 | 64007036.06 | 0.109751E+09 | 40070773.40 |
| August | 0.109199E+09 | 49121824.98 | 60077308.27 | 0.137447E+09 | 43138959.70 |
| September | 0.124882E+09 | 73158053.47 | 51724091.21 | 0.153754E+09 | 55844771.71 |
| October | 88659155.67 | 51817282.23 | 36841873.43 | 97212564.86 | 70102172.87 |
| November | 60831586.72 | 37005405.32 | 23826181.40 | 60226381.90 | 75897087.46 |
| December | 49821773.71 | 31921047.49 | 17900726.22 | 48092452.06 | 89737579.43 |
| Annual Sum or Average | 0.101820E+10 | 0.483021E+09 | 0.535179E+09 | 0.111250E+10 | 0.754097E+09 |
| Minimum of Months | 49821773.71 | 15827497.79 | 17900726.22 | 43773046.50 | 40070773.40 |
| Maximum of Months | 0.124882E+09 | 73158053.47 | 64007036.06 | 0.153754E+09 | 89737579.43 |
Report: WindowEnergyReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.972034E+09 | 0.629238E+09 | 0.342797E+09 | 0.978403E+09 | 0.105948E+10 |
| February | 0.107227E+10 | 0.654317E+09 | 0.417958E+09 | 0.109843E+10 | 0.973512E+09 |
| March | 0.733981E+09 | 0.213702E+09 | 0.520279E+09 | 0.591022E+09 | 0.899203E+09 |
| April | 0.147501E+10 | 0.666685E+09 | 0.808320E+09 | 0.167343E+10 | 0.822525E+09 |
| May | 0.126063E+10 | 0.410421E+09 | 0.850211E+09 | 0.128904E+10 | 0.780003E+09 |
| June | 0.112385E+10 | 0.272037E+09 | 0.851813E+09 | 0.120183E+10 | 0.586652E+09 |
| July | 0.125826E+10 | 0.394038E+09 | 0.864221E+09 | 0.148186E+10 | 0.541034E+09 |
| August | 0.147440E+10 | 0.663241E+09 | 0.811162E+09 | 0.185580E+10 | 0.582461E+09 |
| September | 0.168615E+10 | 0.987778E+09 | 0.698377E+09 | 0.207599E+10 | 0.754014E+09 |
| October | 0.119707E+10 | 0.699635E+09 | 0.497438E+09 | 0.131256E+10 | 0.946517E+09 |
| November | 0.821346E+09 | 0.499646E+09 | 0.321700E+09 | 0.813175E+09 | 0.102476E+10 |
| December | 0.672692E+09 | 0.430997E+09 | 0.241695E+09 | 0.649343E+09 | 0.121163E+10 |
| Annual Sum or Average | 0.137477E+11 | 0.652173E+10 | 0.722597E+10 | 0.150209E+11 | 0.101818E+11 |
| Minimum of Months | 0.672692E+09 | 0.213702E+09 | 0.241695E+09 | 0.591022E+09 | 0.541034E+09 |
| Maximum of Months | 0.168615E+10 | 0.987778E+09 | 0.864221E+09 | 0.207599E+10 | 0.121163E+10 |
Report: WindowEnergyReportMonthly
For: BATH_ZN_1_FLR_1_WALL_5_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 95518376.77 | 14572254.78 | 80946122.00 | 13113504.19 | 0.708377E+09 |
| February | 0.187364E+09 | 63440412.69 | 0.123924E+09 | 93373490.75 | 0.633882E+09 |
| March | 0.236301E+09 | 43878366.39 | 0.192423E+09 | 85574669.47 | 0.592428E+09 |
| April | 0.585912E+09 | 0.249062E+09 | 0.336850E+09 | 0.519092E+09 | 0.517390E+09 |
| May | 0.706881E+09 | 0.308459E+09 | 0.398422E+09 | 0.608428E+09 | 0.511112E+09 |
| June | 0.749002E+09 | 0.336731E+09 | 0.412272E+09 | 0.724415E+09 | 0.396962E+09 |
| July | 0.787912E+09 | 0.374768E+09 | 0.413144E+09 | 0.844674E+09 | 0.347145E+09 |
| August | 0.661508E+09 | 0.307696E+09 | 0.353811E+09 | 0.724641E+09 | 0.352348E+09 |
| September | 0.483100E+09 | 0.222113E+09 | 0.260987E+09 | 0.472650E+09 | 0.462120E+09 |
| October | 0.232990E+09 | 75134430.46 | 0.157855E+09 | 0.141799E+09 | 0.609153E+09 |
| November | 0.104941E+09 | 19519976.37 | 85420965.83 | 24112856.12 | 0.682964E+09 |
| December | 62391871.59 | 5812821.47 | 56579050.12 | 2534006.18 | 0.800908E+09 |
| Annual Sum or Average | 0.489382E+10 | 0.202119E+10 | 0.287263E+10 | 0.425441E+10 | 0.661479E+10 |
| Minimum of Months | 62391871.59 | 5812821.47 | 56579050.12 | 2534006.18 | 0.347145E+09 |
| Maximum of Months | 0.787912E+09 | 0.374768E+09 | 0.413144E+09 | 0.844674E+09 | 0.800908E+09 |
Report: WindowEnergyReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.415426E+09 | 0.166877E+09 | 0.248549E+09 | 0.210433E+09 | 0.151815E+10 |
| February | 0.559524E+09 | 0.206692E+09 | 0.352832E+09 | 0.320667E+09 | 0.134067E+10 |
| March | 0.647363E+09 | 0.127571E+09 | 0.519791E+09 | 0.313410E+09 | 0.121756E+10 |
| April | 0.168215E+10 | 0.790453E+09 | 0.891697E+09 | 0.161793E+10 | 0.104313E+10 |
| May | 0.182769E+10 | 0.797022E+09 | 0.103066E+10 | 0.167750E+10 | 0.975921E+09 |
| June | 0.175072E+10 | 0.699219E+09 | 0.105150E+10 | 0.175020E+10 | 0.734129E+09 |
| July | 0.184671E+10 | 0.784850E+09 | 0.106186E+10 | 0.197094E+10 | 0.677600E+09 |
| August | 0.174935E+10 | 0.835823E+09 | 0.913528E+09 | 0.194146E+10 | 0.726041E+09 |
| September | 0.152453E+10 | 0.810677E+09 | 0.713856E+09 | 0.159807E+10 | 0.942930E+09 |
| October | 0.760442E+09 | 0.315147E+09 | 0.445295E+09 | 0.577700E+09 | 0.127967E+10 |
| November | 0.383653E+09 | 0.130754E+09 | 0.252898E+09 | 0.180727E+09 | 0.142089E+10 |
| December | 0.293811E+09 | 0.109235E+09 | 0.184576E+09 | 0.125470E+09 | 0.166445E+10 |
| Annual Sum or Average | 0.134414E+11 | 0.577432E+10 | 0.766704E+10 | 0.122845E+11 | 0.135412E+11 |
| Minimum of Months | 0.293811E+09 | 0.109235E+09 | 0.184576E+09 | 0.125470E+09 | 0.677600E+09 |
| Maximum of Months | 0.184671E+10 | 0.835823E+09 | 0.106186E+10 | 0.197094E+10 | 0.166445E+10 |
Report: WindowEnergyReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 71482583.30 | 46273611.85 | 25208971.46 | 68908927.37 | 86965116.98 |
| February | 78854181.59 | 48117900.53 | 30736281.06 | 77597614.57 | 78871817.52 |
| March | 53976362.78 | 15715492.11 | 38260870.67 | 39153934.66 | 75219558.62 |
| April | 0.108471E+09 | 49027461.22 | 59443187.22 | 0.116310E+09 | 69419800.03 |
| May | 92705806.68 | 30181989.76 | 62523816.92 | 87473159.13 | 66735050.38 |
| June | 82646947.82 | 20005373.36 | 62641574.46 | 81530792.67 | 49631673.22 |
| July | 92531288.01 | 28977207.43 | 63554080.59 | 0.102095E+09 | 45976314.65 |
| August | 0.108426E+09 | 48774206.95 | 59652162.10 | 0.130728E+09 | 48609807.76 |
| September | 0.123998E+09 | 72640339.43 | 51358057.85 | 0.148202E+09 | 61467689.38 |
| October | 88031745.73 | 51450589.39 | 36581156.34 | 92603457.59 | 78477877.33 |
| November | 60401102.79 | 36743530.97 | 23657571.82 | 57433688.22 | 84317391.27 |
| December | 49469202.39 | 31695153.37 | 17774049.02 | 45994092.88 | 99758783.12 |
| Annual Sum or Average | 0.101099E+10 | 0.479603E+09 | 0.531392E+09 | 0.104803E+10 | 0.845451E+09 |
| Minimum of Months | 49469202.39 | 15715492.11 | 17774049.02 | 39153934.66 | 45976314.65 |
| Maximum of Months | 0.123998E+09 | 72640339.43 | 63554080.59 | 0.148202E+09 | 99758783.12 |
Report: WindowEnergyReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.108242E+10 | 0.700693E+09 | 0.381724E+09 | 0.104345E+10 | 0.131686E+10 |
| February | 0.119404E+10 | 0.728620E+09 | 0.465421E+09 | 0.117501E+10 | 0.119431E+10 |
| March | 0.817331E+09 | 0.237970E+09 | 0.579361E+09 | 0.592884E+09 | 0.113900E+10 |
| April | 0.164250E+10 | 0.742393E+09 | 0.900112E+09 | 0.176122E+10 | 0.105091E+10 |
| May | 0.140379E+10 | 0.457027E+09 | 0.946760E+09 | 0.132455E+10 | 0.100952E+10 |
| June | 0.125147E+10 | 0.302929E+09 | 0.948543E+09 | 0.123461E+10 | 0.750675E+09 |
| July | 0.140114E+10 | 0.438784E+09 | 0.962361E+09 | 0.154600E+10 | 0.695308E+09 |
| August | 0.164183E+10 | 0.738558E+09 | 0.903276E+09 | 0.197953E+10 | 0.735549E+09 |
| September | 0.187763E+10 | 0.109995E+10 | 0.777684E+09 | 0.224414E+10 | 0.930749E+09 |
| October | 0.133301E+10 | 0.779085E+09 | 0.553926E+09 | 0.140224E+10 | 0.118834E+10 |
| November | 0.914617E+09 | 0.556385E+09 | 0.358232E+09 | 0.869683E+09 | 0.127677E+10 |
| December | 0.749082E+09 | 0.479940E+09 | 0.269142E+09 | 0.696460E+09 | 0.151059E+10 |
| Annual Sum or Average | 0.153089E+11 | 0.726233E+10 | 0.804654E+10 | 0.158698E+11 | 0.127986E+11 |
| Minimum of Months | 0.749082E+09 | 0.237970E+09 | 0.269142E+09 | 0.592884E+09 | 0.695308E+09 |
| Maximum of Months | 0.187763E+10 | 0.109995E+10 | 0.962361E+09 | 0.224414E+10 | 0.151059E+10 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 47554324.11 | 12622068.14 | 34932255.96 | 23164083.98 | 0.174804E+09 |
| February | 75243745.02 | 26336428.89 | 48907316.13 | 53213192.21 | 0.154724E+09 |
| March | 0.104227E+09 | 18974163.79 | 85252519.16 | 77281495.25 | 0.142171E+09 |
| April | 0.245570E+09 | 0.130555E+09 | 0.115015E+09 | 0.270450E+09 | 0.126896E+09 |
| May | 0.305437E+09 | 0.168280E+09 | 0.137157E+09 | 0.332776E+09 | 0.118114E+09 |
| June | 0.317441E+09 | 0.171817E+09 | 0.145624E+09 | 0.367284E+09 | 89676854.09 |
| July | 0.332214E+09 | 0.193843E+09 | 0.138372E+09 | 0.396414E+09 | 88090669.94 |
| August | 0.284303E+09 | 0.171209E+09 | 0.113094E+09 | 0.342170E+09 | 98682556.37 |
| September | 0.205006E+09 | 0.122788E+09 | 82217718.42 | 0.233350E+09 | 0.121216E+09 |
| October | 0.101246E+09 | 40770828.61 | 60475274.37 | 88319380.33 | 0.151446E+09 |
| November | 50202149.03 | 13983875.60 | 36218273.43 | 26946482.75 | 0.164060E+09 |
| December | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 0.197213E+09 |
| Annual Sum or Average | 0.210137E+10 | 0.107873E+10 | 0.102264E+10 | 0.222184E+10 | 0.162709E+10 |
| Minimum of Months | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 88090669.94 |
| Maximum of Months | 0.332214E+09 | 0.193843E+09 | 0.145624E+09 | 0.396414E+09 | 0.197213E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 47554324.11 | 12622068.14 | 34932255.96 | 23164083.98 | 0.174804E+09 |
| February | 75243745.02 | 26336428.89 | 48907316.13 | 53213192.21 | 0.154724E+09 |
| March | 0.104227E+09 | 18974163.79 | 85252519.16 | 77281495.25 | 0.142171E+09 |
| April | 0.245570E+09 | 0.130555E+09 | 0.115015E+09 | 0.270450E+09 | 0.126896E+09 |
| May | 0.305437E+09 | 0.168280E+09 | 0.137157E+09 | 0.332776E+09 | 0.118114E+09 |
| June | 0.317441E+09 | 0.171817E+09 | 0.145624E+09 | 0.367284E+09 | 89676854.09 |
| July | 0.332214E+09 | 0.193843E+09 | 0.138372E+09 | 0.396414E+09 | 88090669.94 |
| August | 0.284303E+09 | 0.171209E+09 | 0.113094E+09 | 0.342170E+09 | 98682556.37 |
| September | 0.205006E+09 | 0.122788E+09 | 82217718.42 | 0.233350E+09 | 0.121216E+09 |
| October | 0.101246E+09 | 40770828.61 | 60475274.37 | 88319380.33 | 0.151446E+09 |
| November | 50202149.03 | 13983875.60 | 36218273.43 | 26946482.75 | 0.164060E+09 |
| December | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 0.197213E+09 |
| Annual Sum or Average | 0.210137E+10 | 0.107873E+10 | 0.102264E+10 | 0.222184E+10 | 0.162709E+10 |
| Minimum of Months | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 88090669.94 |
| Maximum of Months | 0.332214E+09 | 0.193843E+09 | 0.145624E+09 | 0.396414E+09 | 0.197213E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 47554324.11 | 12622068.14 | 34932255.96 | 23164083.98 | 0.174804E+09 |
| February | 75243745.02 | 26336428.89 | 48907316.13 | 53213192.21 | 0.154724E+09 |
| March | 0.104227E+09 | 18974163.79 | 85252519.16 | 77281495.25 | 0.142171E+09 |
| April | 0.245570E+09 | 0.130555E+09 | 0.115015E+09 | 0.270450E+09 | 0.126896E+09 |
| May | 0.305437E+09 | 0.168280E+09 | 0.137157E+09 | 0.332776E+09 | 0.118114E+09 |
| June | 0.317441E+09 | 0.171817E+09 | 0.145624E+09 | 0.367284E+09 | 89676854.09 |
| July | 0.332214E+09 | 0.193843E+09 | 0.138372E+09 | 0.396414E+09 | 88090669.94 |
| August | 0.284303E+09 | 0.171209E+09 | 0.113094E+09 | 0.342170E+09 | 98682556.37 |
| September | 0.205006E+09 | 0.122788E+09 | 82217718.42 | 0.233350E+09 | 0.121216E+09 |
| October | 0.101246E+09 | 40770828.61 | 60475274.37 | 88319380.33 | 0.151446E+09 |
| November | 50202149.03 | 13983875.60 | 36218273.43 | 26946482.75 | 0.164060E+09 |
| December | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 0.197213E+09 |
| Annual Sum or Average | 0.210137E+10 | 0.107873E+10 | 0.102264E+10 | 0.222184E+10 | 0.162709E+10 |
| Minimum of Months | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 88090669.94 |
| Maximum of Months | 0.332214E+09 | 0.193843E+09 | 0.145624E+09 | 0.396414E+09 | 0.197213E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 47554324.11 | 12622068.14 | 34932255.96 | 23164083.98 | 0.174804E+09 |
| February | 75243745.02 | 26336428.89 | 48907316.13 | 53213192.21 | 0.154724E+09 |
| March | 0.104227E+09 | 18974163.79 | 85252519.16 | 77281495.25 | 0.142171E+09 |
| April | 0.245570E+09 | 0.130555E+09 | 0.115015E+09 | 0.270450E+09 | 0.126896E+09 |
| May | 0.305437E+09 | 0.168280E+09 | 0.137157E+09 | 0.332776E+09 | 0.118114E+09 |
| June | 0.317441E+09 | 0.171817E+09 | 0.145624E+09 | 0.367284E+09 | 89676854.09 |
| July | 0.332214E+09 | 0.193843E+09 | 0.138372E+09 | 0.396414E+09 | 88090669.94 |
| August | 0.284303E+09 | 0.171209E+09 | 0.113094E+09 | 0.342170E+09 | 98682556.37 |
| September | 0.205006E+09 | 0.122788E+09 | 82217718.42 | 0.233350E+09 | 0.121216E+09 |
| October | 0.101246E+09 | 40770828.61 | 60475274.37 | 88319380.33 | 0.151446E+09 |
| November | 50202149.03 | 13983875.60 | 36218273.43 | 26946482.75 | 0.164060E+09 |
| December | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 0.197213E+09 |
| Annual Sum or Average | 0.210137E+10 | 0.107873E+10 | 0.102264E+10 | 0.222184E+10 | 0.162709E+10 |
| Minimum of Months | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 88090669.94 |
| Maximum of Months | 0.332214E+09 | 0.193843E+09 | 0.145624E+09 | 0.396414E+09 | 0.197213E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 47554324.11 | 12622068.14 | 34932255.96 | 23164083.98 | 0.174804E+09 |
| February | 75243745.02 | 26336428.89 | 48907316.13 | 53213192.21 | 0.154724E+09 |
| March | 0.104227E+09 | 18974163.79 | 85252519.16 | 77281495.25 | 0.142171E+09 |
| April | 0.245570E+09 | 0.130555E+09 | 0.115015E+09 | 0.270450E+09 | 0.126896E+09 |
| May | 0.305437E+09 | 0.168280E+09 | 0.137157E+09 | 0.332776E+09 | 0.118114E+09 |
| June | 0.317441E+09 | 0.171817E+09 | 0.145624E+09 | 0.367284E+09 | 89676854.09 |
| July | 0.332214E+09 | 0.193843E+09 | 0.138372E+09 | 0.396414E+09 | 88090669.94 |
| August | 0.284303E+09 | 0.171209E+09 | 0.113094E+09 | 0.342170E+09 | 98682556.37 |
| September | 0.205006E+09 | 0.122788E+09 | 82217718.42 | 0.233350E+09 | 0.121216E+09 |
| October | 0.101246E+09 | 40770828.61 | 60475274.37 | 88319380.33 | 0.151446E+09 |
| November | 50202149.03 | 13983875.60 | 36218273.43 | 26946482.75 | 0.164060E+09 |
| December | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 0.197213E+09 |
| Annual Sum or Average | 0.210137E+10 | 0.107873E+10 | 0.102264E+10 | 0.222184E+10 | 0.162709E+10 |
| Minimum of Months | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 88090669.94 |
| Maximum of Months | 0.332214E+09 | 0.193843E+09 | 0.145624E+09 | 0.396414E+09 | 0.197213E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 47554324.11 | 12622068.14 | 34932255.96 | 23164083.98 | 0.174804E+09 |
| February | 75243745.02 | 26336428.89 | 48907316.13 | 53213192.21 | 0.154724E+09 |
| March | 0.104227E+09 | 18974163.79 | 85252519.16 | 77281495.25 | 0.142171E+09 |
| April | 0.245570E+09 | 0.130555E+09 | 0.115015E+09 | 0.270450E+09 | 0.126896E+09 |
| May | 0.305437E+09 | 0.168280E+09 | 0.137157E+09 | 0.332776E+09 | 0.118114E+09 |
| June | 0.317441E+09 | 0.171817E+09 | 0.145624E+09 | 0.367284E+09 | 89676854.09 |
| July | 0.332214E+09 | 0.193843E+09 | 0.138372E+09 | 0.396414E+09 | 88090669.94 |
| August | 0.284303E+09 | 0.171209E+09 | 0.113094E+09 | 0.342170E+09 | 98682556.37 |
| September | 0.205006E+09 | 0.122788E+09 | 82217718.42 | 0.233350E+09 | 0.121216E+09 |
| October | 0.101246E+09 | 40770828.61 | 60475274.37 | 88319380.33 | 0.151446E+09 |
| November | 50202149.03 | 13983875.60 | 36218273.43 | 26946482.75 | 0.164060E+09 |
| December | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 0.197213E+09 |
| Annual Sum or Average | 0.210137E+10 | 0.107873E+10 | 0.102264E+10 | 0.222184E+10 | 0.162709E+10 |
| Minimum of Months | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 88090669.94 |
| Maximum of Months | 0.332214E+09 | 0.193843E+09 | 0.145624E+09 | 0.396414E+09 | 0.197213E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 47554324.11 | 12622068.14 | 34932255.96 | 23164083.98 | 0.174804E+09 |
| February | 75243745.02 | 26336428.89 | 48907316.13 | 53213192.21 | 0.154724E+09 |
| March | 0.104227E+09 | 18974163.79 | 85252519.16 | 77281495.25 | 0.142171E+09 |
| April | 0.245570E+09 | 0.130555E+09 | 0.115015E+09 | 0.270450E+09 | 0.126896E+09 |
| May | 0.305437E+09 | 0.168280E+09 | 0.137157E+09 | 0.332776E+09 | 0.118114E+09 |
| June | 0.317441E+09 | 0.171817E+09 | 0.145624E+09 | 0.367284E+09 | 89676854.09 |
| July | 0.332214E+09 | 0.193843E+09 | 0.138372E+09 | 0.396414E+09 | 88090669.94 |
| August | 0.284303E+09 | 0.171209E+09 | 0.113094E+09 | 0.342170E+09 | 98682556.37 |
| September | 0.205006E+09 | 0.122788E+09 | 82217718.42 | 0.233350E+09 | 0.121216E+09 |
| October | 0.101246E+09 | 40770828.61 | 60475274.37 | 88319380.33 | 0.151446E+09 |
| November | 50202149.03 | 13983875.60 | 36218273.43 | 26946482.75 | 0.164060E+09 |
| December | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 0.197213E+09 |
| Annual Sum or Average | 0.210137E+10 | 0.107873E+10 | 0.102264E+10 | 0.222184E+10 | 0.162709E+10 |
| Minimum of Months | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 88090669.94 |
| Maximum of Months | 0.332214E+09 | 0.193843E+09 | 0.145624E+09 | 0.396414E+09 | 0.197213E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 47554324.11 | 12622068.14 | 34932255.96 | 23164083.98 | 0.174804E+09 |
| February | 75243745.02 | 26336428.89 | 48907316.13 | 53213192.21 | 0.154724E+09 |
| March | 0.104227E+09 | 18974163.79 | 85252519.16 | 77281495.25 | 0.142171E+09 |
| April | 0.245570E+09 | 0.130555E+09 | 0.115015E+09 | 0.270450E+09 | 0.126896E+09 |
| May | 0.305437E+09 | 0.168280E+09 | 0.137157E+09 | 0.332776E+09 | 0.118114E+09 |
| June | 0.317441E+09 | 0.171817E+09 | 0.145624E+09 | 0.367284E+09 | 89676854.09 |
| July | 0.332214E+09 | 0.193843E+09 | 0.138372E+09 | 0.396414E+09 | 88090669.94 |
| August | 0.284303E+09 | 0.171209E+09 | 0.113094E+09 | 0.342170E+09 | 98682556.37 |
| September | 0.205006E+09 | 0.122788E+09 | 82217718.42 | 0.233350E+09 | 0.121216E+09 |
| October | 0.101246E+09 | 40770828.61 | 60475274.37 | 88319380.33 | 0.151446E+09 |
| November | 50202149.03 | 13983875.60 | 36218273.43 | 26946482.75 | 0.164060E+09 |
| December | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 0.197213E+09 |
| Annual Sum or Average | 0.210137E+10 | 0.107873E+10 | 0.102264E+10 | 0.222184E+10 | 0.162709E+10 |
| Minimum of Months | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 88090669.94 |
| Maximum of Months | 0.332214E+09 | 0.193843E+09 | 0.145624E+09 | 0.396414E+09 | 0.197213E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 47554324.11 | 12622068.14 | 34932255.96 | 23164083.98 | 0.174804E+09 |
| February | 75243745.02 | 26336428.89 | 48907316.13 | 53213192.21 | 0.154724E+09 |
| March | 0.104227E+09 | 18974163.79 | 85252519.16 | 77281495.25 | 0.142171E+09 |
| April | 0.245570E+09 | 0.130555E+09 | 0.115015E+09 | 0.270450E+09 | 0.126896E+09 |
| May | 0.305437E+09 | 0.168280E+09 | 0.137157E+09 | 0.332776E+09 | 0.118114E+09 |
| June | 0.317441E+09 | 0.171817E+09 | 0.145624E+09 | 0.367284E+09 | 89676854.09 |
| July | 0.332214E+09 | 0.193843E+09 | 0.138372E+09 | 0.396414E+09 | 88090669.94 |
| August | 0.284303E+09 | 0.171209E+09 | 0.113094E+09 | 0.342170E+09 | 98682556.37 |
| September | 0.205006E+09 | 0.122788E+09 | 82217718.42 | 0.233350E+09 | 0.121216E+09 |
| October | 0.101246E+09 | 40770828.61 | 60475274.37 | 88319380.33 | 0.151446E+09 |
| November | 50202149.03 | 13983875.60 | 36218273.43 | 26946482.75 | 0.164060E+09 |
| December | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 0.197213E+09 |
| Annual Sum or Average | 0.210137E+10 | 0.107873E+10 | 0.102264E+10 | 0.222184E+10 | 0.162709E+10 |
| Minimum of Months | 32928483.83 | 7548616.02 | 25379867.81 | 10466648.51 | 88090669.94 |
| Maximum of Months | 0.332214E+09 | 0.193843E+09 | 0.145624E+09 | 0.396414E+09 | 0.197213E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 26195770.73 | 10522882.43 | 15672888.30 | 12743549.21 | 0.102987E+09 |
| February | 35282212.80 | 13033513.01 | 22248699.79 | 19302954.52 | 91777706.28 |
| March | 40821118.66 | 8044349.58 | 32776769.09 | 18022487.43 | 85516958.14 |
| April | 0.106072E+09 | 49844069.69 | 56228220.12 | 99864699.80 | 69940961.37 |
| May | 0.115249E+09 | 50258288.11 | 64991121.06 | 0.102948E+09 | 65741045.62 |
| June | 0.110396E+09 | 44091058.46 | 66304914.18 | 0.108197E+09 | 48942503.45 |
| July | 0.116449E+09 | 49490745.85 | 66958129.97 | 0.121804E+09 | 45458517.77 |
| August | 0.110310E+09 | 52705019.50 | 57604853.95 | 0.121115E+09 | 47644569.86 |
| September | 96133364.26 | 51119336.04 | 45014028.22 | 0.100067E+09 | 60886471.83 |
| October | 47951648.79 | 19872396.21 | 28079252.58 | 36057800.09 | 84483326.96 |
| November | 24192217.07 | 8245057.48 | 15947159.59 | 10924227.58 | 95757359.86 |
| December | 18527025.53 | 6888088.22 | 11638937.31 | 7382284.39 | 0.114042E+09 |
| Annual Sum or Average | 0.847580E+09 | 0.364115E+09 | 0.483465E+09 | 0.758429E+09 | 0.913178E+09 |
| Minimum of Months | 18527025.53 | 6888088.22 | 11638937.31 | 7382284.39 | 45458517.77 |
| Maximum of Months | 0.116449E+09 | 52705019.50 | 66958129.97 | 0.121804E+09 | 0.114042E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.310054E+09 | 0.124546E+09 | 0.185508E+09 | 0.150827E+09 | 0.121894E+10 |
| February | 0.417603E+09 | 0.154261E+09 | 0.263342E+09 | 0.228480E+09 | 0.108586E+10 |
| March | 0.483164E+09 | 95210800.58 | 0.387953E+09 | 0.213411E+09 | 0.101206E+10 |
| April | 0.125548E+10 | 0.589941E+09 | 0.665539E+09 | 0.118385E+10 | 0.827644E+09 |
| May | 0.136411E+10 | 0.594844E+09 | 0.769261E+09 | 0.122062E+10 | 0.777752E+09 |
| June | 0.130666E+10 | 0.521850E+09 | 0.784813E+09 | 0.128345E+10 | 0.579222E+09 |
| July | 0.137831E+10 | 0.585759E+09 | 0.792546E+09 | 0.144490E+10 | 0.538090E+09 |
| August | 0.130564E+10 | 0.623803E+09 | 0.681837E+09 | 0.143648E+10 | 0.564086E+09 |
| September | 0.113784E+10 | 0.605035E+09 | 0.532804E+09 | 0.118666E+10 | 0.720651E+09 |
| October | 0.567559E+09 | 0.235204E+09 | 0.332355E+09 | 0.427237E+09 | 0.999844E+09 |
| November | 0.286341E+09 | 97586326.38 | 0.188755E+09 | 0.129285E+09 | 0.113333E+10 |
| December | 0.219287E+09 | 81525596.04 | 0.137761E+09 | 87358728.08 | 0.134990E+10 |
| Annual Sum or Average | 0.100320E+11 | 0.430957E+10 | 0.572247E+10 | 0.899255E+10 | 0.108074E+11 |
| Minimum of Months | 0.219287E+09 | 81525596.04 | 0.137761E+09 | 87358728.08 | 0.538090E+09 |
| Maximum of Months | 0.137831E+10 | 0.623803E+09 | 0.792546E+09 | 0.144490E+10 | 0.134990E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.158253E+09 | 63570258.18 | 94682937.46 | 63580955.20 | 0.813571E+09 |
| February | 0.213146E+09 | 78737341.48 | 0.134409E+09 | 0.100739E+09 | 0.713816E+09 |
| March | 0.246608E+09 | 48597081.91 | 0.198011E+09 | 89716519.37 | 0.648771E+09 |
| April | 0.640801E+09 | 0.301115E+09 | 0.339686E+09 | 0.590747E+09 | 0.473684E+09 |
| May | 0.696242E+09 | 0.303618E+09 | 0.392625E+09 | 0.613856E+09 | 0.436916E+09 |
| June | 0.666922E+09 | 0.266360E+09 | 0.400562E+09 | 0.648371E+09 | 0.325779E+09 |
| July | 0.703489E+09 | 0.298981E+09 | 0.404508E+09 | 0.728533E+09 | 0.305615E+09 |
| August | 0.666402E+09 | 0.318399E+09 | 0.348003E+09 | 0.724914E+09 | 0.324154E+09 |
| September | 0.580758E+09 | 0.308819E+09 | 0.271939E+09 | 0.596938E+09 | 0.409122E+09 |
| October | 0.289684E+09 | 0.120052E+09 | 0.169632E+09 | 0.204388E+09 | 0.608923E+09 |
| November | 0.146149E+09 | 49809587.44 | 96339865.90 | 55673771.59 | 0.732169E+09 |
| December | 0.111925E+09 | 41611939.45 | 70313025.74 | 34612100.38 | 0.901765E+09 |
| Annual Sum or Average | 0.512038E+10 | 0.219967E+10 | 0.292071E+10 | 0.445207E+10 | 0.669428E+10 |
| Minimum of Months | 0.111925E+09 | 41611939.45 | 70313025.74 | 34612100.38 | 0.305615E+09 |
| Maximum of Months | 0.703489E+09 | 0.318399E+09 | 0.404508E+09 | 0.728533E+09 | 0.901765E+09 |
Report: WindowEnergyReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.190868E+09 | 0.00 | 0.190868E+09 | 1455096.43 | 0.169326E+10 |
| February | 0.269376E+09 | 0.00 | 0.269376E+09 | 7833262.07 | 0.147044E+10 |
| March | 0.414182E+09 | 0.00 | 0.414182E+09 | 56384017.21 | 0.134805E+10 |
| April | 0.647616E+09 | 2373401.81 | 0.645242E+09 | 0.262511E+09 | 0.108348E+10 |
| May | 0.818737E+09 | 30988055.14 | 0.787749E+09 | 0.309280E+09 | 0.952348E+09 |
| June | 0.877164E+09 | 50010141.56 | 0.827154E+09 | 0.515396E+09 | 0.726527E+09 |
| July | 0.858013E+09 | 41224086.35 | 0.816789E+09 | 0.592285E+09 | 0.657904E+09 |
| August | 0.685311E+09 | 8871890.46 | 0.676439E+09 | 0.464918E+09 | 0.729281E+09 |
| September | 0.508425E+09 | 95691.60 | 0.508329E+09 | 0.255014E+09 | 0.974828E+09 |
| October | 0.337417E+09 | 0.00 | 0.337417E+09 | 51632866.57 | 0.131157E+10 |
| November | 0.196268E+09 | 0.00 | 0.196268E+09 | 1290959.88 | 0.153898E+10 |
| December | 0.138085E+09 | 0.00 | 0.138085E+09 | 0.00 | 0.185490E+10 |
| Annual Sum or Average | 0.594146E+10 | 0.133563E+09 | 0.580790E+10 | 0.251800E+10 | 0.143416E+11 |
| Minimum of Months | 0.138085E+09 | 0.00 | 0.138085E+09 | 0.00 | 0.657904E+09 |
| Maximum of Months | 0.877164E+09 | 50010141.56 | 0.827154E+09 | 0.592285E+09 | 0.185490E+10 |
Report: WindowEnergyReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 26444191.27 | 10622673.35 | 15821517.92 | 13316317.32 | 0.100110E+09 |
| February | 35616802.17 | 13157112.82 | 22459689.34 | 20353378.43 | 87246050.17 |
| March | 41208234.75 | 8120636.00 | 33087598.75 | 19713292.04 | 80330317.80 |
| April | 0.107078E+09 | 50316752.51 | 56761445.31 | 0.105133E+09 | 63245379.85 |
| May | 0.116342E+09 | 50734899.06 | 65607446.87 | 0.109147E+09 | 59026407.14 |
| June | 0.111443E+09 | 44509184.14 | 66933698.98 | 0.112083E+09 | 46244945.03 |
| July | 0.117553E+09 | 49960078.01 | 67593109.37 | 0.127052E+09 | 41731652.40 |
| August | 0.111356E+09 | 53204833.37 | 58151134.07 | 0.124986E+09 | 44744675.88 |
| September | 97045019.15 | 51604112.50 | 45440906.64 | 0.103729E+09 | 57431575.12 |
| October | 48406385.34 | 20060850.73 | 28345534.61 | 37703633.03 | 79355193.80 |
| November | 24421637.45 | 8323247.26 | 16098390.19 | 11482941.77 | 92179359.33 |
| December | 18702721.59 | 6953409.55 | 11749312.04 | 7779490.35 | 0.111701E+09 |
| Annual Sum or Average | 0.855618E+09 | 0.367568E+09 | 0.488050E+09 | 0.792479E+09 | 0.863347E+09 |
| Minimum of Months | 18702721.59 | 6953409.55 | 11749312.04 | 7779490.35 | 41731652.40 |
| Maximum of Months | 0.117553E+09 | 53204833.37 | 67593109.37 | 0.127052E+09 | 0.111701E+09 |
Report: WindowEnergyReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.270289E+09 | 0.108576E+09 | 0.161714E+09 | 0.136108E+09 | 0.102324E+10 |
| February | 0.364044E+09 | 0.134481E+09 | 0.229563E+09 | 0.208034E+09 | 0.891753E+09 |
| March | 0.421195E+09 | 83002064.93 | 0.338193E+09 | 0.201492E+09 | 0.821067E+09 |
| April | 0.109446E+10 | 0.514294E+09 | 0.580166E+09 | 0.107458E+10 | 0.646433E+09 |
| May | 0.118915E+10 | 0.518568E+09 | 0.670582E+09 | 0.111562E+10 | 0.603142E+09 |
| June | 0.113907E+10 | 0.454934E+09 | 0.684138E+09 | 0.114568E+10 | 0.472461E+09 |
| July | 0.120153E+10 | 0.510648E+09 | 0.690878E+09 | 0.129869E+10 | 0.426339E+09 |
| August | 0.113818E+10 | 0.543813E+09 | 0.594370E+09 | 0.127750E+10 | 0.457312E+09 |
| September | 0.991910E+09 | 0.527452E+09 | 0.464457E+09 | 0.106022E+10 | 0.587016E+09 |
| October | 0.494768E+09 | 0.205045E+09 | 0.289723E+09 | 0.385374E+09 | 0.811100E+09 |
| November | 0.249617E+09 | 85072980.68 | 0.164544E+09 | 0.117369E+09 | 0.942177E+09 |
| December | 0.191163E+09 | 71071693.28 | 0.120091E+09 | 79515171.34 | 0.114171E+10 |
| Annual Sum or Average | 0.874538E+10 | 0.375696E+10 | 0.498842E+10 | 0.810019E+10 | 0.882375E+10 |
| Minimum of Months | 0.191163E+09 | 71071693.28 | 0.120091E+09 | 79515171.34 | 0.426339E+09 |
| Maximum of Months | 0.120153E+10 | 0.543813E+09 | 0.690878E+09 | 0.129869E+10 | 0.114171E+10 |
Report: WindowEnergyReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.183884E+09 | 0.00 | 0.183884E+09 | 3724148.99 | 0.149158E+10 |
| February | 0.259355E+09 | 0.00 | 0.259355E+09 | 10775708.14 | 0.131148E+10 |
| March | 0.397353E+09 | 0.00 | 0.397353E+09 | 55490475.99 | 0.123335E+10 |
| April | 0.626088E+09 | 2802036.18 | 0.623286E+09 | 0.255523E+09 | 0.103414E+10 |
| May | 0.808861E+09 | 39022693.98 | 0.769838E+09 | 0.308436E+09 | 0.896371E+09 |
| June | 0.865301E+09 | 54258693.08 | 0.811042E+09 | 0.532993E+09 | 0.661667E+09 |
| July | 0.848145E+09 | 48356063.17 | 0.799789E+09 | 0.601079E+09 | 0.598415E+09 |
| August | 0.666687E+09 | 10445055.43 | 0.656242E+09 | 0.468777E+09 | 0.662283E+09 |
| September | 0.491072E+09 | 108661.33 | 0.490963E+09 | 0.251835E+09 | 0.918246E+09 |
| October | 0.325163E+09 | 0.00 | 0.325163E+09 | 53981997.73 | 0.124662E+10 |
| November | 0.189072E+09 | 0.00 | 0.189072E+09 | 1717185.52 | 0.141712E+10 |
| December | 0.133049E+09 | 0.00 | 0.133049E+09 | 0.00 | 0.163660E+10 |
| Annual Sum or Average | 0.579403E+10 | 0.154993E+09 | 0.563904E+10 | 0.254433E+10 | 0.131079E+11 |
| Minimum of Months | 0.133049E+09 | 0.00 | 0.133049E+09 | 0.00 | 0.598415E+09 |
| Maximum of Months | 0.865301E+09 | 54258693.08 | 0.811042E+09 | 0.601079E+09 | 0.163660E+10 |
Report: WindowEnergyReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 9068302.29 | 0.00 | 9068302.29 | 19799.43 | 0.102800E+09 |
| February | 12907613.97 | 0.00 | 12907613.97 | 92652.25 | 92190878.52 |
| March | 19397715.41 | 0.00 | 19397715.41 | 582184.30 | 87960225.48 |
| April | 52551842.86 | 16863074.33 | 35688768.53 | 30302258.64 | 65186639.12 |
| May | 80204158.09 | 33867375.10 | 46336782.99 | 61259037.81 | 61910264.72 |
| June | 83068370.32 | 34330592.19 | 48737778.13 | 75324656.69 | 45912194.01 |
| July | 84377289.70 | 35391538.73 | 48985750.97 | 82511061.35 | 40500063.55 |
| August | 63079963.17 | 24154677.52 | 38925285.65 | 58897968.42 | 41467769.32 |
| September | 30950170.60 | 4468799.34 | 26481371.26 | 14448786.01 | 57602996.06 |
| October | 16293863.65 | 0.00 | 16293863.65 | 1059684.81 | 85798363.98 |
| November | 9316708.22 | 0.00 | 9316708.22 | 3530.40 | 97726955.73 |
| December | 6526809.27 | 0.00 | 6526809.27 | 0.00 | 0.111492E+09 |
| Annual Sum or Average | 0.467743E+09 | 0.149076E+09 | 0.318667E+09 | 0.324502E+09 | 0.890549E+09 |
| Minimum of Months | 6526809.27 | 0.00 | 6526809.27 | 0.00 | 40500063.55 |
| Maximum of Months | 84377289.70 | 35391538.73 | 48985750.97 | 82511061.35 | 0.111492E+09 |
Report: WindowEnergyReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.317281E+09 | 0.104921E+09 | 0.212360E+09 | 0.118666E+09 | 0.145542E+10 |
| February | 0.475267E+09 | 0.163847E+09 | 0.311419E+09 | 0.243643E+09 | 0.127962E+10 |
| March | 0.591524E+09 | 0.118718E+09 | 0.472806E+09 | 0.262867E+09 | 0.120193E+10 |
| April | 0.155147E+10 | 0.741376E+09 | 0.810094E+09 | 0.149056E+10 | 0.984673E+09 |
| May | 0.168392E+10 | 0.747537E+09 | 0.936381E+09 | 0.153862E+10 | 0.926657E+09 |
| June | 0.161047E+10 | 0.655806E+09 | 0.954665E+09 | 0.160182E+10 | 0.697755E+09 |
| July | 0.169996E+10 | 0.736121E+09 | 0.963842E+09 | 0.181981E+10 | 0.628386E+09 |
| August | 0.161210E+10 | 0.783930E+09 | 0.828170E+09 | 0.180769E+10 | 0.659414E+09 |
| September | 0.140290E+10 | 0.756634E+09 | 0.646269E+09 | 0.148200E+10 | 0.870478E+09 |
| October | 0.671374E+09 | 0.273636E+09 | 0.397738E+09 | 0.492894E+09 | 0.122428E+10 |
| November | 0.312497E+09 | 92510263.85 | 0.219987E+09 | 0.113703E+09 | 0.139222E+10 |
| December | 0.217086E+09 | 62330521.93 | 0.154755E+09 | 56373746.71 | 0.162061E+10 |
| Annual Sum or Average | 0.121459E+11 | 0.523737E+10 | 0.690849E+10 | 0.110286E+11 | 0.129414E+11 |
| Minimum of Months | 0.217086E+09 | 62330521.93 | 0.154755E+09 | 56373746.71 | 0.628386E+09 |
| Maximum of Months | 0.169996E+10 | 0.783930E+09 | 0.963842E+09 | 0.181981E+10 | 0.162061E+10 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 236.95 | 487.51 | 290.31 | 167.44 | 122.87 | 0.00 | 0.00 |
| February | 345.59 | 483.48 | 390.06 | 216.50 | 173.55 | 0.00 | 0.00 |
| March | 176.85 | 399.23 | 273.89 | 69.41 | 204.48 | 0.00 | 0.00 |
| April | 612.28 | 365.45 | 598.03 | 256.93 | 341.10 | 0.00 | 0.00 |
| May | 545.96 | 325.16 | 579.15 | 211.78 | 367.37 | 0.00 | 0.00 |
| June | 597.31 | 253.38 | 578.98 | 192.62 | 386.36 | 0.00 | 0.00 |
| July | 696.48 | 216.41 | 607.19 | 230.40 | 376.80 | 0.00 | 0.00 |
| August | 730.31 | 236.12 | 606.94 | 268.56 | 338.38 | 0.00 | 0.00 |
| September | 707.13 | 332.90 | 616.82 | 332.17 | 284.65 | 0.00 | 0.00 |
| October | 376.05 | 419.84 | 391.17 | 203.15 | 188.02 | 0.00 | 0.00 |
| November | 209.89 | 478.69 | 258.33 | 137.75 | 120.58 | 0.00 | 0.00 |
| December | 143.34 | 550.63 | 190.86 | 107.38 | 83.48 | 0.00 | 0.00 |
| Annual Sum or Average | 448.11 | 378.44 | 448.25 | 199.04 | 249.21 | 0.00 | 0.00 |
| Minimum of Months | 143.34 | 216.41 | 190.86 | 69.41 | 83.48 | 0.00 | 0.00 |
| Maximum of Months | 730.31 | 550.63 | 616.82 | 332.17 | 386.36 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1032.01 | 1366.12 | 1087.32 | 703.87 | 383.45 | 0.00 | 0.00 |
| February | 1290.98 | 1367.17 | 1327.96 | 810.34 | 517.62 | 0.00 | 0.00 |
| March | 593.66 | 1153.07 | 821.03 | 239.05 | 581.98 | 0.00 | 0.00 |
| April | 1848.06 | 1061.85 | 1704.94 | 770.61 | 934.33 | 0.00 | 0.00 |
| May | 1361.69 | 965.61 | 1410.14 | 459.10 | 951.05 | 0.00 | 0.00 |
| June | 1329.42 | 727.15 | 1299.04 | 314.44 | 984.60 | 0.00 | 0.00 |
| July | 1652.61 | 605.19 | 1407.49 | 440.77 | 966.72 | 0.00 | 0.00 |
| August | 2071.91 | 652.55 | 1649.27 | 741.90 | 907.37 | 0.00 | 0.00 |
| September | 2353.43 | 934.23 | 1949.00 | 1141.76 | 807.24 | 0.00 | 0.00 |
| October | 1407.37 | 1192.07 | 1339.05 | 782.61 | 556.43 | 0.00 | 0.00 |
| November | 894.50 | 1353.70 | 949.38 | 577.53 | 371.85 | 0.00 | 0.00 |
| December | 691.67 | 1554.46 | 752.47 | 482.11 | 270.36 | 0.00 | 0.00 |
| Annual Sum or Average | 1375.47 | 1076.03 | 1306.09 | 619.59 | 686.50 | 0.00 | 0.00 |
| Minimum of Months | 593.66 | 605.19 | 752.47 | 239.05 | 270.36 | 0.00 | 0.00 |
| Maximum of Months | 2353.43 | 1554.46 | 1949.00 | 1141.76 | 984.60 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 11.15 | 83.95 | 21.55 | 7.12 | 14.43 | 0.00 | 0.00 |
| February | 27.35 | 81.46 | 38.15 | 16.11 | 22.04 | 0.00 | 0.00 |
| March | 16.60 | 66.41 | 34.50 | 6.60 | 27.90 | 0.00 | 0.00 |
| April | 77.02 | 58.18 | 81.39 | 32.33 | 49.06 | 0.00 | 0.00 |
| May | 88.32 | 52.66 | 95.49 | 38.83 | 56.66 | 0.00 | 0.00 |
| June | 106.80 | 40.63 | 103.12 | 42.45 | 60.67 | 0.00 | 0.00 |
| July | 119.72 | 33.61 | 105.03 | 46.31 | 58.72 | 0.00 | 0.00 |
| August | 102.33 | 35.91 | 88.22 | 38.20 | 50.02 | 0.00 | 0.00 |
| September | 74.64 | 52.02 | 70.77 | 31.74 | 39.04 | 0.00 | 0.00 |
| October | 28.80 | 68.51 | 37.75 | 13.58 | 24.18 | 0.00 | 0.00 |
| November | 10.30 | 80.71 | 20.43 | 5.96 | 14.47 | 0.00 | 0.00 |
| December | 3.33 | 95.63 | 11.56 | 2.44 | 9.12 | 0.00 | 0.00 |
| Annual Sum or Average | 55.63 | 62.37 | 59.06 | 23.48 | 35.58 | 0.00 | 0.00 |
| Minimum of Months | 3.33 | 33.61 | 11.56 | 2.44 | 9.12 | 0.00 | 0.00 |
| Maximum of Months | 119.72 | 95.63 | 105.03 | 46.31 | 60.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 25.09 | 508.26 | 98.11 | 21.36 | 76.75 | 0.00 | 0.00 |
| February | 75.47 | 481.86 | 166.69 | 48.32 | 118.37 | 0.00 | 0.00 |
| March | 59.90 | 399.49 | 177.73 | 19.80 | 157.93 | 0.00 | 0.00 |
| April | 282.85 | 340.44 | 360.35 | 97.53 | 262.82 | 0.00 | 0.00 |
| May | 328.58 | 298.41 | 433.38 | 123.75 | 309.63 | 0.00 | 0.00 |
| June | 431.23 | 232.97 | 472.59 | 138.24 | 334.35 | 0.00 | 0.00 |
| July | 491.03 | 193.32 | 468.66 | 148.17 | 320.49 | 0.00 | 0.00 |
| August | 412.48 | 206.05 | 383.12 | 116.48 | 266.64 | 0.00 | 0.00 |
| September | 278.14 | 303.00 | 301.84 | 95.22 | 206.62 | 0.00 | 0.00 |
| October | 97.46 | 401.00 | 171.96 | 40.73 | 131.23 | 0.00 | 0.00 |
| November | 25.78 | 480.89 | 96.88 | 17.89 | 78.99 | 0.00 | 0.00 |
| December | 6.27 | 569.74 | 58.94 | 7.32 | 51.62 | 0.00 | 0.00 |
| Annual Sum or Average | 210.13 | 367.33 | 266.21 | 72.95 | 193.26 | 0.00 | 0.00 |
| Minimum of Months | 6.27 | 193.32 | 58.94 | 7.32 | 51.62 | 0.00 | 0.00 |
| Maximum of Months | 491.03 | 569.74 | 472.59 | 148.17 | 334.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.90 | 1516.08 | 150.83 | 0.00 | 150.83 | 0.00 | 0.00 |
| February | 3.77 | 1463.40 | 235.50 | 0.00 | 235.50 | 0.00 | 0.00 |
| March | 30.74 | 1208.40 | 337.58 | 0.00 | 337.58 | 0.00 | 0.00 |
| April | 177.09 | 1002.54 | 519.96 | 1.76 | 518.20 | 0.00 | 0.00 |
| May | 207.64 | 860.61 | 653.48 | 27.77 | 625.72 | 0.00 | 0.00 |
| June | 430.74 | 642.30 | 726.06 | 48.01 | 678.05 | 0.00 | 0.00 |
| July | 546.70 | 515.10 | 681.13 | 38.85 | 642.28 | 0.00 | 0.00 |
| August | 428.77 | 543.85 | 526.97 | 6.88 | 520.09 | 0.00 | 0.00 |
| September | 199.70 | 846.49 | 399.55 | 0.04 | 399.51 | 0.00 | 0.00 |
| October | 26.37 | 1168.66 | 263.94 | 0.00 | 263.94 | 0.00 | 0.00 |
| November | 0.38 | 1424.24 | 160.41 | 0.00 | 160.41 | 0.00 | 0.00 |
| December | 0.00 | 1646.42 | 109.33 | 0.00 | 109.33 | 0.00 | 0.00 |
| Annual Sum or Average | 172.10 | 1067.60 | 397.79 | 10.34 | 387.46 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 515.10 | 109.33 | 0.00 | 109.33 | 0.00 | 0.00 |
| Maximum of Months | 546.70 | 1646.42 | 726.06 | 48.01 | 678.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 223.81 | 491.60 | 270.43 | 157.17 | 113.26 | 0.00 | 0.00 |
| February | 335.58 | 483.19 | 377.45 | 214.97 | 162.48 | 0.00 | 0.00 |
| March | 164.75 | 397.44 | 261.57 | 69.41 | 192.16 | 0.00 | 0.00 |
| April | 584.06 | 362.11 | 573.20 | 256.93 | 316.28 | 0.00 | 0.00 |
| May | 515.89 | 323.11 | 551.47 | 211.78 | 339.69 | 0.00 | 0.00 |
| June | 563.22 | 250.45 | 549.19 | 192.62 | 356.57 | 0.00 | 0.00 |
| July | 663.35 | 212.18 | 577.69 | 230.40 | 347.30 | 0.00 | 0.00 |
| August | 700.58 | 230.37 | 580.46 | 268.56 | 311.90 | 0.00 | 0.00 |
| September | 683.47 | 327.48 | 595.50 | 332.14 | 263.35 | 0.00 | 0.00 |
| October | 363.54 | 416.54 | 378.12 | 202.63 | 175.49 | 0.00 | 0.00 |
| November | 202.53 | 479.83 | 246.21 | 133.97 | 112.24 | 0.00 | 0.00 |
| December | 131.11 | 556.32 | 171.47 | 96.25 | 75.21 | 0.00 | 0.00 |
| Annual Sum or Average | 427.53 | 376.93 | 427.45 | 196.74 | 230.71 | 0.00 | 0.00 |
| Minimum of Months | 131.11 | 212.18 | 171.47 | 69.41 | 75.21 | 0.00 | 0.00 |
| Maximum of Months | 700.58 | 556.32 | 595.50 | 332.14 | 356.57 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 876.72 | 1401.82 | 913.31 | 606.97 | 306.34 | 0.00 | 0.00 |
| February | 1188.76 | 1373.68 | 1220.50 | 778.82 | 441.68 | 0.00 | 0.00 |
| March | 508.76 | 1152.06 | 736.02 | 234.05 | 501.97 | 0.00 | 0.00 |
| April | 1657.94 | 1055.45 | 1540.80 | 760.98 | 779.83 | 0.00 | 0.00 |
| May | 1176.81 | 974.01 | 1236.32 | 455.35 | 780.97 | 0.00 | 0.00 |
| June | 1119.28 | 725.08 | 1114.63 | 312.37 | 802.26 | 0.00 | 0.00 |
| July | 1439.89 | 590.78 | 1223.96 | 437.59 | 786.37 | 0.00 | 0.00 |
| August | 1871.73 | 624.69 | 1478.62 | 734.02 | 744.60 | 0.00 | 0.00 |
| September | 2172.51 | 906.78 | 1795.33 | 1122.25 | 673.08 | 0.00 | 0.00 |
| October | 1293.50 | 1178.66 | 1232.07 | 758.26 | 473.81 | 0.00 | 0.00 |
| November | 811.64 | 1361.75 | 851.66 | 538.22 | 313.44 | 0.00 | 0.00 |
| December | 586.74 | 1571.85 | 632.41 | 413.71 | 218.70 | 0.00 | 0.00 |
| Annual Sum or Average | 1223.30 | 1074.64 | 1162.41 | 593.59 | 568.82 | 0.00 | 0.00 |
| Minimum of Months | 508.76 | 590.78 | 632.41 | 234.05 | 218.70 | 0.00 | 0.00 |
| Maximum of Months | 2172.51 | 1571.85 | 1795.33 | 1122.25 | 802.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 11.21 | 83.63 | 21.55 | 7.12 | 14.43 | 0.00 | 0.00 |
| February | 27.38 | 81.40 | 38.15 | 16.11 | 22.04 | 0.00 | 0.00 |
| March | 16.60 | 66.45 | 34.50 | 6.60 | 27.90 | 0.00 | 0.00 |
| April | 77.07 | 58.12 | 81.39 | 32.33 | 49.06 | 0.00 | 0.00 |
| May | 88.37 | 52.62 | 95.49 | 38.83 | 56.66 | 0.00 | 0.00 |
| June | 106.87 | 40.57 | 103.12 | 42.45 | 60.67 | 0.00 | 0.00 |
| July | 119.87 | 33.49 | 105.03 | 46.31 | 58.72 | 0.00 | 0.00 |
| August | 102.48 | 35.76 | 88.22 | 38.20 | 50.02 | 0.00 | 0.00 |
| September | 74.71 | 51.92 | 70.77 | 31.74 | 39.04 | 0.00 | 0.00 |
| October | 28.83 | 68.48 | 37.75 | 13.58 | 24.18 | 0.00 | 0.00 |
| November | 10.32 | 80.59 | 20.43 | 5.96 | 14.47 | 0.00 | 0.00 |
| December | 3.34 | 95.53 | 11.56 | 2.44 | 9.12 | 0.00 | 0.00 |
| Annual Sum or Average | 55.69 | 62.27 | 59.06 | 23.48 | 35.58 | 0.00 | 0.00 |
| Minimum of Months | 3.34 | 33.49 | 11.56 | 2.44 | 9.12 | 0.00 | 0.00 |
| Maximum of Months | 119.87 | 95.53 | 105.03 | 46.31 | 60.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 25.35 | 507.81 | 98.56 | 21.36 | 77.20 | 0.00 | 0.00 |
| February | 75.96 | 481.76 | 167.40 | 48.32 | 119.08 | 0.00 | 0.00 |
| March | 60.59 | 399.57 | 178.57 | 19.80 | 158.78 | 0.00 | 0.00 |
| April | 284.76 | 340.52 | 362.05 | 97.53 | 264.52 | 0.00 | 0.00 |
| May | 330.65 | 298.21 | 435.47 | 123.88 | 311.59 | 0.00 | 0.00 |
| June | 433.66 | 232.84 | 474.84 | 138.38 | 336.46 | 0.00 | 0.00 |
| July | 493.57 | 193.19 | 470.86 | 148.29 | 322.57 | 0.00 | 0.00 |
| August | 414.71 | 206.10 | 384.98 | 116.51 | 268.47 | 0.00 | 0.00 |
| September | 279.79 | 303.11 | 303.29 | 95.22 | 208.07 | 0.00 | 0.00 |
| October | 98.23 | 401.12 | 172.80 | 40.73 | 132.07 | 0.00 | 0.00 |
| November | 26.02 | 480.72 | 97.36 | 17.89 | 79.47 | 0.00 | 0.00 |
| December | 6.34 | 569.69 | 59.27 | 7.32 | 51.95 | 0.00 | 0.00 |
| Annual Sum or Average | 211.41 | 367.27 | 267.48 | 72.98 | 194.50 | 0.00 | 0.00 |
| Minimum of Months | 6.34 | 193.19 | 59.27 | 7.32 | 51.95 | 0.00 | 0.00 |
| Maximum of Months | 493.57 | 569.69 | 474.84 | 148.29 | 336.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.08 | 1513.83 | 153.06 | 0.00 | 153.06 | 0.00 | 0.00 |
| February | 4.20 | 1461.23 | 238.98 | 0.00 | 238.98 | 0.00 | 0.00 |
| March | 32.81 | 1207.32 | 341.71 | 0.00 | 341.71 | 0.00 | 0.00 |
| April | 185.17 | 1001.69 | 528.34 | 1.77 | 526.57 | 0.00 | 0.00 |
| May | 216.74 | 857.93 | 664.20 | 28.54 | 635.66 | 0.00 | 0.00 |
| June | 442.76 | 641.09 | 737.69 | 48.49 | 689.20 | 0.00 | 0.00 |
| July | 559.28 | 514.17 | 692.58 | 39.49 | 653.08 | 0.00 | 0.00 |
| August | 439.64 | 544.43 | 536.23 | 7.05 | 529.18 | 0.00 | 0.00 |
| September | 206.95 | 846.82 | 406.68 | 0.04 | 406.64 | 0.00 | 0.00 |
| October | 28.78 | 1168.20 | 268.05 | 0.00 | 268.05 | 0.00 | 0.00 |
| November | 0.47 | 1422.94 | 162.76 | 0.00 | 162.76 | 0.00 | 0.00 |
| December | 0.00 | 1646.23 | 110.93 | 0.00 | 110.93 | 0.00 | 0.00 |
| Annual Sum or Average | 177.55 | 1066.59 | 404.18 | 10.51 | 393.67 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 514.17 | 110.93 | 0.00 | 110.93 | 0.00 | 0.00 |
| Maximum of Months | 559.28 | 1646.23 | 737.69 | 48.49 | 689.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 227.86 | 491.89 | 275.14 | 160.40 | 114.74 | 0.00 | 0.00 |
| February | 336.02 | 484.04 | 378.72 | 215.31 | 163.41 | 0.00 | 0.00 |
| March | 165.13 | 399.08 | 262.51 | 69.41 | 193.10 | 0.00 | 0.00 |
| April | 585.20 | 364.16 | 575.10 | 256.93 | 318.17 | 0.00 | 0.00 |
| May | 517.30 | 324.64 | 553.58 | 211.78 | 341.81 | 0.00 | 0.00 |
| June | 565.01 | 251.72 | 551.46 | 192.62 | 358.84 | 0.00 | 0.00 |
| July | 664.34 | 214.16 | 579.95 | 230.40 | 349.55 | 0.00 | 0.00 |
| August | 701.68 | 232.30 | 582.48 | 268.56 | 313.92 | 0.00 | 0.00 |
| September | 684.38 | 329.51 | 597.13 | 332.15 | 264.98 | 0.00 | 0.00 |
| October | 363.89 | 418.83 | 379.21 | 202.74 | 176.47 | 0.00 | 0.00 |
| November | 203.28 | 481.56 | 248.02 | 134.93 | 113.08 | 0.00 | 0.00 |
| December | 135.34 | 556.32 | 176.25 | 99.65 | 76.60 | 0.00 | 0.00 |
| Annual Sum or Average | 429.00 | 378.40 | 429.69 | 197.42 | 232.27 | 0.00 | 0.00 |
| Minimum of Months | 135.34 | 214.16 | 176.25 | 69.41 | 76.60 | 0.00 | 0.00 |
| Maximum of Months | 701.68 | 556.32 | 597.13 | 332.15 | 358.84 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 902.86 | 1400.69 | 940.85 | 625.34 | 315.51 | 0.00 | 0.00 |
| February | 1192.72 | 1376.86 | 1227.96 | 781.38 | 446.58 | 0.00 | 0.00 |
| March | 510.12 | 1160.08 | 740.19 | 234.08 | 506.11 | 0.00 | 0.00 |
| April | 1663.54 | 1063.98 | 1549.13 | 760.98 | 788.15 | 0.00 | 0.00 |
| May | 1183.40 | 979.54 | 1245.60 | 455.35 | 790.25 | 0.00 | 0.00 |
| June | 1127.30 | 729.61 | 1124.62 | 312.37 | 812.25 | 0.00 | 0.00 |
| July | 1445.76 | 598.07 | 1233.85 | 437.59 | 796.26 | 0.00 | 0.00 |
| August | 1877.47 | 632.19 | 1487.50 | 734.02 | 753.48 | 0.00 | 0.00 |
| September | 2176.98 | 915.14 | 1802.56 | 1122.31 | 680.24 | 0.00 | 0.00 |
| October | 1295.99 | 1189.12 | 1237.59 | 759.22 | 478.37 | 0.00 | 0.00 |
| November | 818.72 | 1369.44 | 862.89 | 544.25 | 318.65 | 0.00 | 0.00 |
| December | 608.49 | 1572.64 | 654.80 | 429.52 | 225.28 | 0.00 | 0.00 |
| Annual Sum or Average | 1231.61 | 1080.55 | 1173.45 | 597.27 | 576.18 | 0.00 | 0.00 |
| Minimum of Months | 510.12 | 598.07 | 654.80 | 234.08 | 225.28 | 0.00 | 0.00 |
| Maximum of Months | 2176.98 | 1572.64 | 1802.56 | 1122.31 | 812.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 11.13 | 84.22 | 21.55 | 7.12 | 14.43 | 0.00 | 0.00 |
| February | 27.24 | 82.08 | 38.15 | 16.11 | 22.04 | 0.00 | 0.00 |
| March | 16.32 | 67.32 | 34.50 | 6.60 | 27.90 | 0.00 | 0.00 |
| April | 76.51 | 59.08 | 81.39 | 32.33 | 49.06 | 0.00 | 0.00 |
| May | 87.85 | 53.40 | 95.49 | 38.83 | 56.66 | 0.00 | 0.00 |
| June | 106.35 | 41.21 | 103.12 | 42.45 | 60.67 | 0.00 | 0.00 |
| July | 118.98 | 34.31 | 105.03 | 46.31 | 58.72 | 0.00 | 0.00 |
| August | 101.77 | 36.54 | 88.22 | 38.20 | 50.02 | 0.00 | 0.00 |
| September | 74.23 | 52.83 | 70.77 | 31.74 | 39.04 | 0.00 | 0.00 |
| October | 28.54 | 69.66 | 37.75 | 13.58 | 24.18 | 0.00 | 0.00 |
| November | 10.18 | 81.76 | 20.43 | 5.96 | 14.47 | 0.00 | 0.00 |
| December | 3.31 | 96.18 | 11.56 | 2.44 | 9.12 | 0.00 | 0.00 |
| Annual Sum or Average | 55.30 | 63.11 | 59.06 | 23.48 | 35.58 | 0.00 | 0.00 |
| Minimum of Months | 3.31 | 34.31 | 11.56 | 2.44 | 9.12 | 0.00 | 0.00 |
| Maximum of Months | 118.98 | 96.18 | 105.03 | 46.31 | 60.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 27.94 | 508.17 | 104.25 | 21.36 | 82.89 | 0.00 | 0.00 |
| February | 82.14 | 482.21 | 176.30 | 48.32 | 127.98 | 0.00 | 0.00 |
| March | 69.50 | 400.72 | 189.08 | 19.80 | 169.28 | 0.00 | 0.00 |
| April | 307.26 | 343.99 | 383.54 | 97.62 | 285.93 | 0.00 | 0.00 |
| May | 355.44 | 299.07 | 460.72 | 124.90 | 335.82 | 0.00 | 0.00 |
| June | 462.15 | 234.50 | 501.98 | 139.43 | 362.54 | 0.00 | 0.00 |
| July | 520.79 | 196.09 | 497.78 | 149.34 | 348.44 | 0.00 | 0.00 |
| August | 439.54 | 211.02 | 408.26 | 116.83 | 291.42 | 0.00 | 0.00 |
| September | 298.37 | 308.46 | 321.62 | 95.23 | 226.39 | 0.00 | 0.00 |
| October | 107.30 | 405.17 | 183.31 | 40.73 | 142.58 | 0.00 | 0.00 |
| November | 28.73 | 482.47 | 103.38 | 17.89 | 85.49 | 0.00 | 0.00 |
| December | 7.15 | 570.61 | 63.35 | 7.32 | 56.03 | 0.00 | 0.00 |
| Annual Sum or Average | 226.17 | 369.59 | 283.18 | 73.28 | 209.90 | 0.00 | 0.00 |
| Minimum of Months | 7.15 | 196.09 | 63.35 | 7.32 | 56.03 | 0.00 | 0.00 |
| Maximum of Months | 520.79 | 570.61 | 501.98 | 149.34 | 362.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 3.75 | 995.29 | 126.47 | 0.00 | 126.47 | 0.00 | 0.00 |
| February | 11.67 | 949.53 | 197.49 | 0.00 | 197.49 | 0.00 | 0.00 |
| March | 51.75 | 791.35 | 273.30 | 0.00 | 273.30 | 0.00 | 0.00 |
| April | 216.12 | 660.76 | 444.97 | 1.99 | 442.98 | 0.00 | 0.00 |
| May | 254.72 | 554.14 | 556.32 | 26.84 | 529.48 | 0.00 | 0.00 |
| June | 430.93 | 423.74 | 614.98 | 38.56 | 576.42 | 0.00 | 0.00 |
| July | 506.69 | 345.29 | 583.34 | 33.26 | 550.08 | 0.00 | 0.00 |
| August | 405.19 | 373.89 | 458.54 | 7.18 | 451.35 | 0.00 | 0.00 |
| September | 216.94 | 575.71 | 349.01 | 0.08 | 348.93 | 0.00 | 0.00 |
| October | 51.57 | 779.13 | 223.64 | 0.00 | 223.64 | 0.00 | 0.00 |
| November | 2.94 | 938.23 | 134.38 | 0.00 | 134.38 | 0.00 | 0.00 |
| December | 0.00 | 1090.88 | 91.51 | 0.00 | 91.51 | 0.00 | 0.00 |
| Annual Sum or Average | 180.32 | 705.12 | 338.46 | 9.05 | 329.40 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 345.29 | 91.51 | 0.00 | 91.51 | 0.00 | 0.00 |
| Maximum of Months | 506.69 | 1090.88 | 614.98 | 38.56 | 576.42 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.35 | 534.93 | 65.04 | 0.00 | 65.04 | 0.00 | 0.00 |
| February | 4.54 | 516.85 | 101.57 | 0.00 | 101.57 | 0.00 | 0.00 |
| March | 21.33 | 436.25 | 140.55 | 0.00 | 140.55 | 0.00 | 0.00 |
| April | 101.57 | 366.03 | 228.84 | 1.02 | 227.82 | 0.00 | 0.00 |
| May | 119.70 | 306.21 | 286.11 | 13.80 | 272.30 | 0.00 | 0.00 |
| June | 207.85 | 233.91 | 316.27 | 19.83 | 296.44 | 0.00 | 0.00 |
| July | 240.26 | 193.67 | 300.00 | 17.10 | 282.90 | 0.00 | 0.00 |
| August | 191.18 | 210.66 | 235.82 | 3.69 | 232.12 | 0.00 | 0.00 |
| September | 100.40 | 322.97 | 179.49 | 0.04 | 179.45 | 0.00 | 0.00 |
| October | 21.48 | 433.98 | 115.02 | 0.00 | 115.02 | 0.00 | 0.00 |
| November | 0.77 | 517.12 | 69.11 | 0.00 | 69.11 | 0.00 | 0.00 |
| December | 0.00 | 588.11 | 47.06 | 0.00 | 47.06 | 0.00 | 0.00 |
| Annual Sum or Average | 84.65 | 387.65 | 174.06 | 4.66 | 169.41 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 193.67 | 47.06 | 0.00 | 47.06 | 0.00 | 0.00 |
| Maximum of Months | 240.26 | 588.11 | 316.27 | 19.83 | 296.44 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.31 | 255.99 | 28.11 | 2.67 | 25.44 | 0.00 | 0.00 |
| February | 22.46 | 246.34 | 60.19 | 17.16 | 43.02 | 0.00 | 0.00 |
| March | 24.49 | 202.76 | 75.05 | 13.07 | 61.97 | 0.00 | 0.00 |
| April | 173.98 | 178.27 | 197.00 | 83.41 | 113.59 | 0.00 | 0.00 |
| May | 203.09 | 169.38 | 232.66 | 101.92 | 130.74 | 0.00 | 0.00 |
| June | 254.81 | 130.86 | 255.56 | 115.68 | 139.87 | 0.00 | 0.00 |
| July | 282.26 | 112.56 | 259.87 | 124.23 | 135.64 | 0.00 | 0.00 |
| August | 238.39 | 114.64 | 216.14 | 100.45 | 115.69 | 0.00 | 0.00 |
| September | 155.51 | 155.80 | 158.61 | 71.37 | 87.25 | 0.00 | 0.00 |
| October | 38.92 | 203.91 | 70.85 | 20.73 | 50.11 | 0.00 | 0.00 |
| November | 4.17 | 240.29 | 32.03 | 4.31 | 27.72 | 0.00 | 0.00 |
| December | 0.02 | 284.91 | 19.02 | 1.02 | 18.00 | 0.00 | 0.00 |
| Annual Sum or Average | 117.06 | 191.02 | 134.06 | 54.82 | 79.24 | 0.00 | 0.00 |
| Minimum of Months | 0.02 | 112.56 | 19.02 | 1.02 | 18.00 | 0.00 | 0.00 |
| Maximum of Months | 282.26 | 284.91 | 259.87 | 124.23 | 139.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 392.35 | 424.86 | 389.79 | 252.33 | 137.46 | 0.00 | 0.00 |
| February | 487.67 | 432.21 | 476.06 | 290.50 | 185.56 | 0.00 | 0.00 |
| March | 237.01 | 360.59 | 294.33 | 85.70 | 208.64 | 0.00 | 0.00 |
| April | 693.43 | 340.83 | 611.21 | 276.26 | 334.95 | 0.00 | 0.00 |
| May | 516.92 | 312.79 | 505.53 | 164.58 | 340.94 | 0.00 | 0.00 |
| June | 498.01 | 243.09 | 465.70 | 112.73 | 352.97 | 0.00 | 0.00 |
| July | 594.24 | 216.96 | 504.57 | 158.01 | 346.56 | 0.00 | 0.00 |
| August | 744.19 | 233.57 | 591.25 | 265.97 | 325.28 | 0.00 | 0.00 |
| September | 860.24 | 312.45 | 698.70 | 409.31 | 289.39 | 0.00 | 0.00 |
| October | 526.35 | 379.56 | 480.04 | 280.56 | 199.48 | 0.00 | 0.00 |
| November | 336.96 | 424.64 | 340.35 | 207.04 | 133.30 | 0.00 | 0.00 |
| December | 260.39 | 485.88 | 269.76 | 172.83 | 96.92 | 0.00 | 0.00 |
| Annual Sum or Average | 511.59 | 346.78 | 468.22 | 222.12 | 246.10 | 0.00 | 0.00 |
| Minimum of Months | 237.01 | 216.96 | 269.76 | 85.70 | 96.92 | 0.00 | 0.00 |
| Maximum of Months | 860.24 | 485.88 | 698.70 | 409.31 | 352.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 4.90 | 264.48 | 35.66 | 5.44 | 30.22 | 0.00 | 0.00 |
| February | 38.60 | 262.02 | 77.45 | 26.22 | 51.23 | 0.00 | 0.00 |
| March | 31.95 | 221.19 | 88.22 | 16.38 | 71.84 | 0.00 | 0.00 |
| April | 200.27 | 199.61 | 226.05 | 96.09 | 129.96 | 0.00 | 0.00 |
| May | 227.16 | 190.83 | 263.92 | 115.17 | 148.75 | 0.00 | 0.00 |
| June | 279.48 | 153.15 | 288.97 | 129.91 | 159.06 | 0.00 | 0.00 |
| July | 315.37 | 129.61 | 294.17 | 139.92 | 154.25 | 0.00 | 0.00 |
| August | 270.55 | 131.55 | 246.98 | 114.88 | 132.10 | 0.00 | 0.00 |
| September | 182.35 | 178.29 | 186.38 | 85.69 | 100.69 | 0.00 | 0.00 |
| October | 52.94 | 227.43 | 86.99 | 28.05 | 58.94 | 0.00 | 0.00 |
| November | 9.30 | 263.49 | 40.49 | 7.53 | 32.96 | 0.00 | 0.00 |
| December | 0.95 | 299.02 | 23.29 | 2.17 | 21.12 | 0.00 | 0.00 |
| Annual Sum or Average | 134.91 | 209.75 | 155.18 | 64.09 | 91.09 | 0.00 | 0.00 |
| Minimum of Months | 0.95 | 129.61 | 23.29 | 2.17 | 21.12 | 0.00 | 0.00 |
| Maximum of Months | 315.37 | 299.02 | 294.17 | 139.92 | 159.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 464.68 | 1061.75 | 585.92 | 341.19 | 244.73 | 0.00 | 0.00 |
| February | 625.39 | 1055.53 | 757.45 | 406.51 | 350.94 | 0.00 | 0.00 |
| March | 344.83 | 899.77 | 567.01 | 142.35 | 424.66 | 0.00 | 0.00 |
| April | 1322.78 | 808.89 | 1324.51 | 610.29 | 714.22 | 0.00 | 0.00 |
| May | 1127.22 | 739.92 | 1241.11 | 479.48 | 761.63 | 0.00 | 0.00 |
| June | 1167.62 | 576.61 | 1190.14 | 394.35 | 795.79 | 0.00 | 0.00 |
| July | 1335.69 | 514.25 | 1247.16 | 467.67 | 779.48 | 0.00 | 0.00 |
| August | 1497.20 | 548.31 | 1306.61 | 606.02 | 700.59 | 0.00 | 0.00 |
| September | 1519.67 | 726.75 | 1360.40 | 765.15 | 595.25 | 0.00 | 0.00 |
| October | 764.11 | 941.06 | 814.47 | 427.75 | 386.72 | 0.00 | 0.00 |
| November | 409.36 | 1055.24 | 524.18 | 279.28 | 244.90 | 0.00 | 0.00 |
| December | 306.37 | 1204.99 | 407.84 | 231.81 | 176.03 | 0.00 | 0.00 |
| Annual Sum or Average | 907.23 | 843.26 | 943.72 | 428.60 | 515.12 | 0.00 | 0.00 |
| Minimum of Months | 306.37 | 514.25 | 407.84 | 142.35 | 176.03 | 0.00 | 0.00 |
| Maximum of Months | 1519.67 | 1204.99 | 1360.40 | 765.15 | 795.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 113.06 | 1055.08 | 285.33 | 92.84 | 192.49 | 0.00 | 0.00 |
| February | 272.26 | 1034.27 | 467.13 | 167.13 | 300.00 | 0.00 | 0.00 |
| March | 332.05 | 873.47 | 545.86 | 102.31 | 443.55 | 0.00 | 0.00 |
| April | 1412.38 | 764.96 | 1377.96 | 700.15 | 677.82 | 0.00 | 0.00 |
| May | 1592.22 | 691.67 | 1578.66 | 806.31 | 772.35 | 0.00 | 0.00 |
| June | 1800.86 | 542.39 | 1648.93 | 814.93 | 834.00 | 0.00 | 0.00 |
| July | 1906.07 | 502.97 | 1674.39 | 888.53 | 785.86 | 0.00 | 0.00 |
| August | 1720.27 | 548.96 | 1483.98 | 827.88 | 656.10 | 0.00 | 0.00 |
| September | 1287.12 | 702.86 | 1187.90 | 679.49 | 508.40 | 0.00 | 0.00 |
| October | 453.98 | 897.96 | 570.01 | 232.23 | 337.78 | 0.00 | 0.00 |
| November | 127.15 | 1023.33 | 294.12 | 89.39 | 204.73 | 0.00 | 0.00 |
| December | 50.73 | 1189.44 | 199.44 | 58.37 | 141.06 | 0.00 | 0.00 |
| Annual Sum or Average | 925.12 | 817.84 | 944.70 | 456.06 | 488.64 | 0.00 | 0.00 |
| Minimum of Months | 50.73 | 502.97 | 199.44 | 58.37 | 141.06 | 0.00 | 0.00 |
| Maximum of Months | 1906.07 | 1189.44 | 1674.39 | 888.53 | 834.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 23.74 | 303.75 | 59.08 | 23.73 | 35.35 | 0.00 | 0.00 |
| February | 41.64 | 295.06 | 88.11 | 32.55 | 55.56 | 0.00 | 0.00 |
| March | 33.50 | 242.22 | 92.07 | 18.14 | 73.93 | 0.00 | 0.00 |
| April | 227.91 | 182.75 | 247.22 | 116.17 | 131.05 | 0.00 | 0.00 |
| May | 229.19 | 163.13 | 259.95 | 113.36 | 146.59 | 0.00 | 0.00 |
| June | 250.14 | 125.69 | 257.30 | 102.76 | 154.54 | 0.00 | 0.00 |
| July | 272.00 | 114.10 | 262.65 | 111.63 | 151.03 | 0.00 | 0.00 |
| August | 270.65 | 121.03 | 248.81 | 118.88 | 129.93 | 0.00 | 0.00 |
| September | 230.30 | 157.84 | 224.06 | 119.14 | 104.91 | 0.00 | 0.00 |
| October | 76.31 | 227.35 | 108.16 | 44.82 | 63.33 | 0.00 | 0.00 |
| November | 21.48 | 282.47 | 56.38 | 19.22 | 37.17 | 0.00 | 0.00 |
| December | 12.92 | 336.68 | 41.79 | 15.54 | 26.25 | 0.00 | 0.00 |
| Annual Sum or Average | 141.17 | 212.27 | 162.37 | 69.75 | 92.62 | 0.00 | 0.00 |
| Minimum of Months | 12.92 | 114.10 | 41.79 | 15.54 | 26.25 | 0.00 | 0.00 |
| Maximum of Months | 272.00 | 336.68 | 262.65 | 119.14 | 154.54 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 30.49 | 1025.76 | 182.05 | 44.50 | 137.55 | 0.00 | 0.00 |
| February | 71.66 | 986.52 | 276.55 | 61.03 | 215.53 | 0.00 | 0.00 |
| March | 91.37 | 827.58 | 327.28 | 34.02 | 293.26 | 0.00 | 0.00 |
| April | 529.91 | 665.30 | 713.41 | 218.74 | 494.66 | 0.00 | 0.00 |
| May | 563.06 | 593.10 | 793.10 | 224.12 | 568.97 | 0.00 | 0.00 |
| June | 680.58 | 476.90 | 820.86 | 211.98 | 608.88 | 0.00 | 0.00 |
| July | 750.41 | 417.35 | 812.83 | 224.70 | 588.13 | 0.00 | 0.00 |
| August | 689.03 | 451.54 | 722.39 | 226.21 | 496.18 | 0.00 | 0.00 |
| September | 521.42 | 598.70 | 616.27 | 223.44 | 392.83 | 0.00 | 0.00 |
| October | 159.05 | 803.95 | 328.77 | 84.04 | 244.73 | 0.00 | 0.00 |
| November | 28.50 | 971.09 | 181.45 | 36.03 | 145.41 | 0.00 | 0.00 |
| December | 11.11 | 1139.03 | 129.91 | 29.13 | 100.78 | 0.00 | 0.00 |
| Annual Sum or Average | 345.06 | 745.18 | 492.85 | 135.02 | 357.83 | 0.00 | 0.00 |
| Minimum of Months | 11.11 | 417.35 | 129.91 | 29.13 | 100.78 | 0.00 | 0.00 |
| Maximum of Months | 750.41 | 1139.03 | 820.86 | 226.21 | 608.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 28.25 | 1121.21 | 190.50 | 39.17 | 151.33 | 0.00 | 0.00 |
| February | 83.39 | 1087.35 | 309.00 | 67.73 | 241.27 | 0.00 | 0.00 |
| March | 106.02 | 929.01 | 376.45 | 44.32 | 332.12 | 0.00 | 0.00 |
| April | 659.88 | 778.56 | 860.38 | 293.61 | 566.77 | 0.00 | 0.00 |
| May | 699.44 | 690.71 | 960.64 | 306.31 | 654.33 | 0.00 | 0.00 |
| June | 844.84 | 534.34 | 987.21 | 287.19 | 700.02 | 0.00 | 0.00 |
| July | 928.27 | 466.76 | 982.86 | 306.10 | 676.75 | 0.00 | 0.00 |
| August | 864.17 | 501.20 | 874.35 | 305.60 | 568.75 | 0.00 | 0.00 |
| September | 649.01 | 686.84 | 742.64 | 293.68 | 448.96 | 0.00 | 0.00 |
| October | 186.74 | 936.72 | 378.15 | 102.16 | 275.98 | 0.00 | 0.00 |
| November | 27.46 | 1104.49 | 197.10 | 35.69 | 161.41 | 0.00 | 0.00 |
| December | 7.62 | 1244.30 | 133.16 | 23.27 | 109.89 | 0.00 | 0.00 |
| Annual Sum or Average | 425.22 | 838.79 | 583.70 | 175.72 | 407.98 | 0.00 | 0.00 |
| Minimum of Months | 7.62 | 466.76 | 133.16 | 23.27 | 109.89 | 0.00 | 0.00 |
| Maximum of Months | 928.27 | 1244.30 | 987.21 | 306.31 | 700.02 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.634637E+09 | 0.130574E+10 | 0.777554E+09 | 0.448469E+09 | 0.329085E+09 | 0.00 | 0.00 |
| February | 0.836044E+09 | 0.116964E+10 | 0.943628E+09 | 0.523766E+09 | 0.419862E+09 | 0.00 | 0.00 |
| March | 0.473679E+09 | 0.106930E+10 | 0.733578E+09 | 0.185907E+09 | 0.547671E+09 | 0.00 | 0.00 |
| April | 0.158702E+10 | 0.947237E+09 | 0.155009E+10 | 0.665952E+09 | 0.884142E+09 | 0.00 | 0.00 |
| May | 0.146230E+10 | 0.870910E+09 | 0.155119E+10 | 0.567220E+09 | 0.983970E+09 | 0.00 | 0.00 |
| June | 0.154824E+10 | 0.656759E+09 | 0.150071E+10 | 0.499262E+09 | 0.100145E+10 | 0.00 | 0.00 |
| July | 0.186546E+10 | 0.579624E+09 | 0.162631E+10 | 0.617099E+09 | 0.100921E+10 | 0.00 | 0.00 |
| August | 0.195607E+10 | 0.632425E+09 | 0.162563E+10 | 0.719312E+09 | 0.906316E+09 | 0.00 | 0.00 |
| September | 0.183287E+10 | 0.862871E+09 | 0.159879E+10 | 0.860986E+09 | 0.737805E+09 | 0.00 | 0.00 |
| October | 0.100722E+10 | 0.112451E+10 | 0.104771E+10 | 0.544127E+09 | 0.503587E+09 | 0.00 | 0.00 |
| November | 0.544044E+09 | 0.124078E+10 | 0.669594E+09 | 0.357061E+09 | 0.312533E+09 | 0.00 | 0.00 |
| December | 0.383924E+09 | 0.147480E+10 | 0.511210E+09 | 0.287606E+09 | 0.223604E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.141315E+11 | 0.119346E+11 | 0.141360E+11 | 0.627677E+10 | 0.785923E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.383924E+09 | 0.579624E+09 | 0.511210E+09 | 0.185907E+09 | 0.223604E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.195607E+10 | 0.147480E+10 | 0.162631E+10 | 0.860986E+09 | 0.100921E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.276413E+10 | 0.365901E+10 | 0.291227E+10 | 0.188523E+10 | 0.102704E+10 | 0.00 | 0.00 |
| February | 0.312313E+10 | 0.330746E+10 | 0.321260E+10 | 0.196037E+10 | 0.125223E+10 | 0.00 | 0.00 |
| March | 0.159006E+10 | 0.308837E+10 | 0.219905E+10 | 0.640265E+09 | 0.155879E+10 | 0.00 | 0.00 |
| April | 0.479018E+10 | 0.275232E+10 | 0.441920E+10 | 0.199743E+10 | 0.242177E+10 | 0.00 | 0.00 |
| May | 0.364715E+10 | 0.258629E+10 | 0.377693E+10 | 0.122964E+10 | 0.254728E+10 | 0.00 | 0.00 |
| June | 0.344585E+10 | 0.188478E+10 | 0.336712E+10 | 0.815038E+09 | 0.255208E+10 | 0.00 | 0.00 |
| July | 0.442636E+10 | 0.162095E+10 | 0.376982E+10 | 0.118056E+10 | 0.258926E+10 | 0.00 | 0.00 |
| August | 0.554941E+10 | 0.174778E+10 | 0.441740E+10 | 0.198711E+10 | 0.243029E+10 | 0.00 | 0.00 |
| September | 0.610008E+10 | 0.242152E+10 | 0.505182E+10 | 0.295944E+10 | 0.209238E+10 | 0.00 | 0.00 |
| October | 0.376950E+10 | 0.319285E+10 | 0.358650E+10 | 0.209615E+10 | 0.149035E+10 | 0.00 | 0.00 |
| November | 0.231853E+10 | 0.350880E+10 | 0.246080E+10 | 0.149697E+10 | 0.963833E+09 | 0.00 | 0.00 |
| December | 0.185257E+10 | 0.416346E+10 | 0.201542E+10 | 0.129129E+10 | 0.724132E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.433770E+11 | 0.339336E+11 | 0.411889E+11 | 0.195395E+11 | 0.216494E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.159006E+10 | 0.162095E+10 | 0.201542E+10 | 0.640265E+09 | 0.724132E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.610008E+10 | 0.416346E+10 | 0.505182E+10 | 0.295944E+10 | 0.258926E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 29865100.35 | 0.224844E+09 | 57711920.74 | 19068248.70 | 38643672.04 | 0.00 | 0.00 |
| February | 66175039.91 | 0.197065E+09 | 92293229.18 | 38969160.85 | 53324068.33 | 0.00 | 0.00 |
| March | 44458454.43 | 0.177874E+09 | 92394264.78 | 17675019.03 | 74719245.74 | 0.00 | 0.00 |
| April | 0.199634E+09 | 0.150811E+09 | 0.210975E+09 | 83801043.43 | 0.127174E+09 | 0.00 | 0.00 |
| May | 0.236569E+09 | 0.141043E+09 | 0.255773E+09 | 0.104006E+09 | 0.151767E+09 | 0.00 | 0.00 |
| June | 0.276827E+09 | 0.105320E+09 | 0.267298E+09 | 0.110036E+09 | 0.157261E+09 | 0.00 | 0.00 |
| July | 0.320656E+09 | 90024357.72 | 0.281305E+09 | 0.124028E+09 | 0.157277E+09 | 0.00 | 0.00 |
| August | 0.274080E+09 | 96184878.15 | 0.236278E+09 | 0.102302E+09 | 0.133976E+09 | 0.00 | 0.00 |
| September | 0.193468E+09 | 0.134843E+09 | 0.183443E+09 | 82259818.46 | 0.101183E+09 | 0.00 | 0.00 |
| October | 77135307.78 | 0.183494E+09 | 0.101122E+09 | 36362868.60 | 64758671.88 | 0.00 | 0.00 |
| November | 26696024.01 | 0.209202E+09 | 52958201.52 | 15459158.93 | 37499042.59 | 0.00 | 0.00 |
| December | 8918005.83 | 0.256132E+09 | 30975104.47 | 6536423.18 | 24438681.29 | 0.00 | 0.00 |
| Annual Sum or Average | 0.175448E+10 | 0.196684E+10 | 0.186253E+10 | 0.740504E+09 | 0.112202E+10 | 0.00 | 0.00 |
| Minimum of Months | 8918005.83 | 90024357.72 | 30975104.47 | 6536423.18 | 24438681.29 | 0.00 | 0.00 |
| Maximum of Months | 0.320656E+09 | 0.256132E+09 | 0.281305E+09 | 0.124028E+09 | 0.157277E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 67207491.03 | 0.136133E+10 | 0.262773E+09 | 57204555.42 | 0.205568E+09 | 0.00 | 0.00 |
| February | 0.182578E+09 | 0.116571E+10 | 0.403260E+09 | 0.116907E+09 | 0.286353E+09 | 0.00 | 0.00 |
| March | 0.160430E+09 | 0.107000E+10 | 0.476034E+09 | 53024880.35 | 0.423009E+09 | 0.00 | 0.00 |
| April | 0.733150E+09 | 0.882426E+09 | 0.934020E+09 | 0.252789E+09 | 0.681230E+09 | 0.00 | 0.00 |
| May | 0.880069E+09 | 0.799251E+09 | 0.116077E+10 | 0.331452E+09 | 0.829316E+09 | 0.00 | 0.00 |
| June | 0.111775E+10 | 0.603869E+09 | 0.122496E+10 | 0.358327E+09 | 0.866636E+09 | 0.00 | 0.00 |
| July | 0.131518E+10 | 0.517782E+09 | 0.125526E+10 | 0.396866E+09 | 0.858396E+09 | 0.00 | 0.00 |
| August | 0.110479E+10 | 0.551894E+09 | 0.102616E+10 | 0.311979E+09 | 0.714179E+09 | 0.00 | 0.00 |
| September | 0.720933E+09 | 0.785367E+09 | 0.782365E+09 | 0.246814E+09 | 0.535551E+09 | 0.00 | 0.00 |
| October | 0.261029E+09 | 0.107404E+10 | 0.460584E+09 | 0.109088E+09 | 0.351496E+09 | 0.00 | 0.00 |
| November | 66814176.00 | 0.124645E+10 | 0.251107E+09 | 46377322.20 | 0.204729E+09 | 0.00 | 0.00 |
| December | 16796351.14 | 0.152600E+10 | 0.157877E+09 | 19609204.17 | 0.138268E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.662673E+10 | 0.115841E+11 | 0.839517E+10 | 0.230044E+10 | 0.609473E+10 | 0.00 | 0.00 |
| Minimum of Months | 16796351.14 | 0.517782E+09 | 0.157877E+09 | 19609204.17 | 0.138268E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.131518E+10 | 0.152600E+10 | 0.125526E+10 | 0.396866E+09 | 0.866636E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 2416379.43 | 0.406068E+10 | 0.403989E+09 | 0.00 | 0.403989E+09 | 0.00 | 0.00 |
| February | 9119909.99 | 0.354027E+10 | 0.569715E+09 | 0.00 | 0.569715E+09 | 0.00 | 0.00 |
| March | 82346544.37 | 0.323658E+10 | 0.904187E+09 | 0.00 | 0.904187E+09 | 0.00 | 0.00 |
| April | 0.459027E+09 | 0.259858E+10 | 0.134773E+10 | 4550224.02 | 0.134318E+10 | 0.00 | 0.00 |
| May | 0.556136E+09 | 0.230507E+10 | 0.175029E+10 | 74366671.48 | 0.167592E+10 | 0.00 | 0.00 |
| June | 0.111648E+10 | 0.166485E+10 | 0.188196E+10 | 0.124451E+09 | 0.175751E+10 | 0.00 | 0.00 |
| July | 0.146429E+10 | 0.137966E+10 | 0.182434E+10 | 0.104060E+09 | 0.172028E+10 | 0.00 | 0.00 |
| August | 0.114842E+10 | 0.145664E+10 | 0.141143E+10 | 18422779.50 | 0.139300E+10 | 0.00 | 0.00 |
| September | 0.517627E+09 | 0.219410E+10 | 0.103563E+10 | 98054.16 | 0.103554E+10 | 0.00 | 0.00 |
| October | 70632543.58 | 0.313013E+10 | 0.706948E+09 | 0.00 | 0.706948E+09 | 0.00 | 0.00 |
| November | 974017.42 | 0.369164E+10 | 0.415778E+09 | 0.00 | 0.415778E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.440977E+10 | 0.292829E+09 | 0.00 | 0.292829E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.542747E+10 | 0.336680E+11 | 0.125448E+11 | 0.325949E+09 | 0.122189E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.137966E+10 | 0.292829E+09 | 0.00 | 0.292829E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.146429E+10 | 0.440977E+10 | 0.188196E+10 | 0.124451E+09 | 0.175751E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.599450E+09 | 0.131669E+10 | 0.724315E+09 | 0.420957E+09 | 0.303358E+09 | 0.00 | 0.00 |
| February | 0.811837E+09 | 0.116894E+10 | 0.913128E+09 | 0.520063E+09 | 0.393065E+09 | 0.00 | 0.00 |
| March | 0.441269E+09 | 0.106449E+10 | 0.700578E+09 | 0.185904E+09 | 0.514674E+09 | 0.00 | 0.00 |
| April | 0.151387E+10 | 0.938586E+09 | 0.148575E+10 | 0.665952E+09 | 0.819794E+09 | 0.00 | 0.00 |
| May | 0.138176E+10 | 0.865412E+09 | 0.147706E+10 | 0.567220E+09 | 0.909838E+09 | 0.00 | 0.00 |
| June | 0.145987E+10 | 0.649174E+09 | 0.142349E+10 | 0.499262E+09 | 0.924229E+09 | 0.00 | 0.00 |
| July | 0.177673E+10 | 0.568301E+09 | 0.154730E+10 | 0.617099E+09 | 0.930196E+09 | 0.00 | 0.00 |
| August | 0.187644E+10 | 0.617029E+09 | 0.155471E+10 | 0.719312E+09 | 0.835397E+09 | 0.00 | 0.00 |
| September | 0.177157E+10 | 0.848818E+09 | 0.154353E+10 | 0.860914E+09 | 0.682614E+09 | 0.00 | 0.00 |
| October | 0.973697E+09 | 0.111567E+10 | 0.101275E+10 | 0.542735E+09 | 0.470020E+09 | 0.00 | 0.00 |
| November | 0.524959E+09 | 0.124371E+10 | 0.638175E+09 | 0.347242E+09 | 0.290933E+09 | 0.00 | 0.00 |
| December | 0.351164E+09 | 0.149005E+10 | 0.459260E+09 | 0.257806E+09 | 0.201454E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134826E+11 | 0.118869E+11 | 0.134800E+11 | 0.620447E+10 | 0.727557E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.351164E+09 | 0.568301E+09 | 0.459260E+09 | 0.185904E+09 | 0.201454E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.187644E+10 | 0.149005E+10 | 0.155471E+10 | 0.860914E+09 | 0.930196E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.234822E+10 | 0.375463E+10 | 0.244621E+10 | 0.162571E+10 | 0.820502E+09 | 0.00 | 0.00 |
| February | 0.287586E+10 | 0.332321E+10 | 0.295263E+10 | 0.188413E+10 | 0.106851E+10 | 0.00 | 0.00 |
| March | 0.136266E+10 | 0.308568E+10 | 0.197137E+10 | 0.626892E+09 | 0.134448E+10 | 0.00 | 0.00 |
| April | 0.429739E+10 | 0.273573E+10 | 0.399376E+10 | 0.197245E+10 | 0.202131E+10 | 0.00 | 0.00 |
| May | 0.315197E+10 | 0.260878E+10 | 0.331136E+10 | 0.121960E+10 | 0.209176E+10 | 0.00 | 0.00 |
| June | 0.290119E+10 | 0.187940E+10 | 0.288913E+10 | 0.809668E+09 | 0.207946E+10 | 0.00 | 0.00 |
| July | 0.385659E+10 | 0.158234E+10 | 0.327826E+10 | 0.117204E+10 | 0.210622E+10 | 0.00 | 0.00 |
| August | 0.501324E+10 | 0.167318E+10 | 0.396033E+10 | 0.196599E+10 | 0.199434E+10 | 0.00 | 0.00 |
| September | 0.563113E+10 | 0.235038E+10 | 0.465349E+10 | 0.290888E+10 | 0.174461E+10 | 0.00 | 0.00 |
| October | 0.346452E+10 | 0.315692E+10 | 0.329997E+10 | 0.203091E+10 | 0.126905E+10 | 0.00 | 0.00 |
| November | 0.210377E+10 | 0.352965E+10 | 0.220751E+10 | 0.139508E+10 | 0.812430E+09 | 0.00 | 0.00 |
| December | 0.157154E+10 | 0.421005E+10 | 0.169385E+10 | 0.110808E+10 | 0.585766E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.385781E+11 | 0.338900E+11 | 0.366579E+11 | 0.187194E+11 | 0.179384E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.136266E+10 | 0.158234E+10 | 0.169385E+10 | 0.626892E+09 | 0.585766E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.563113E+10 | 0.421005E+10 | 0.465349E+10 | 0.290888E+10 | 0.210622E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 30023351.27 | 0.223984E+09 | 57711920.74 | 19068248.70 | 38643672.04 | 0.00 | 0.00 |
| February | 66226314.87 | 0.196920E+09 | 92293229.18 | 38969160.85 | 53324068.33 | 0.00 | 0.00 |
| March | 44450382.20 | 0.177975E+09 | 92394264.78 | 17675019.03 | 74719245.74 | 0.00 | 0.00 |
| April | 0.199772E+09 | 0.150652E+09 | 0.210975E+09 | 83801043.43 | 0.127174E+09 | 0.00 | 0.00 |
| May | 0.236693E+09 | 0.140928E+09 | 0.255773E+09 | 0.104006E+09 | 0.151767E+09 | 0.00 | 0.00 |
| June | 0.277001E+09 | 0.105155E+09 | 0.267298E+09 | 0.110036E+09 | 0.157261E+09 | 0.00 | 0.00 |
| July | 0.321069E+09 | 89688359.31 | 0.281305E+09 | 0.124028E+09 | 0.157277E+09 | 0.00 | 0.00 |
| August | 0.274475E+09 | 95789538.73 | 0.236278E+09 | 0.102302E+09 | 0.133976E+09 | 0.00 | 0.00 |
| September | 0.193654E+09 | 0.134581E+09 | 0.183443E+09 | 82259818.46 | 0.101183E+09 | 0.00 | 0.00 |
| October | 77205580.48 | 0.183414E+09 | 0.101122E+09 | 36362868.60 | 64758671.88 | 0.00 | 0.00 |
| November | 26750755.32 | 0.208889E+09 | 52958201.52 | 15459158.93 | 37499042.59 | 0.00 | 0.00 |
| December | 8941014.38 | 0.255880E+09 | 30975104.47 | 6536423.18 | 24438681.29 | 0.00 | 0.00 |
| Annual Sum or Average | 0.175626E+10 | 0.196386E+10 | 0.186253E+10 | 0.740504E+09 | 0.112202E+10 | 0.00 | 0.00 |
| Minimum of Months | 8941014.38 | 89688359.31 | 30975104.47 | 6536423.18 | 24438681.29 | 0.00 | 0.00 |
| Maximum of Months | 0.321069E+09 | 0.255880E+09 | 0.281305E+09 | 0.124028E+09 | 0.157277E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 67903615.70 | 0.136013E+10 | 0.263989E+09 | 57204555.42 | 0.206785E+09 | 0.00 | 0.00 |
| February | 0.183767E+09 | 0.116548E+10 | 0.404979E+09 | 0.116907E+09 | 0.288072E+09 | 0.00 | 0.00 |
| March | 0.162293E+09 | 0.107020E+10 | 0.478290E+09 | 53024880.35 | 0.425265E+09 | 0.00 | 0.00 |
| April | 0.738086E+09 | 0.882640E+09 | 0.938421E+09 | 0.252789E+09 | 0.685632E+09 | 0.00 | 0.00 |
| May | 0.885600E+09 | 0.798718E+09 | 0.116636E+10 | 0.331795E+09 | 0.834568E+09 | 0.00 | 0.00 |
| June | 0.112404E+10 | 0.603532E+09 | 0.123079E+10 | 0.358676E+09 | 0.872111E+09 | 0.00 | 0.00 |
| July | 0.132197E+10 | 0.517432E+09 | 0.126115E+10 | 0.397177E+09 | 0.863975E+09 | 0.00 | 0.00 |
| August | 0.111077E+10 | 0.552027E+09 | 0.103113E+10 | 0.312054E+09 | 0.719077E+09 | 0.00 | 0.00 |
| September | 0.725205E+09 | 0.785665E+09 | 0.786136E+09 | 0.246814E+09 | 0.539323E+09 | 0.00 | 0.00 |
| October | 0.263103E+09 | 0.107437E+10 | 0.462829E+09 | 0.109088E+09 | 0.353740E+09 | 0.00 | 0.00 |
| November | 67431010.95 | 0.124602E+10 | 0.252353E+09 | 46377322.20 | 0.205975E+09 | 0.00 | 0.00 |
| December | 16971821.97 | 0.152587E+10 | 0.158751E+09 | 19609204.17 | 0.139141E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.666715E+10 | 0.115821E+11 | 0.843518E+10 | 0.230152E+10 | 0.613367E+10 | 0.00 | 0.00 |
| Minimum of Months | 16971821.97 | 0.517432E+09 | 0.158751E+09 | 19609204.17 | 0.139141E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.132197E+10 | 0.152587E+10 | 0.126115E+10 | 0.397177E+09 | 0.872111E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 2896080.73 | 0.405465E+10 | 0.409949E+09 | 0.00 | 0.409949E+09 | 0.00 | 0.00 |
| February | 10157419.75 | 0.353501E+10 | 0.578138E+09 | 0.00 | 0.578138E+09 | 0.00 | 0.00 |
| March | 87874992.60 | 0.323368E+10 | 0.915240E+09 | 0.00 | 0.915240E+09 | 0.00 | 0.00 |
| April | 0.479962E+09 | 0.259638E+10 | 0.136945E+10 | 4584347.46 | 0.136486E+10 | 0.00 | 0.00 |
| May | 0.580526E+09 | 0.229787E+10 | 0.177899E+10 | 76438421.85 | 0.170255E+10 | 0.00 | 0.00 |
| June | 0.114765E+10 | 0.166169E+10 | 0.191210E+10 | 0.125693E+09 | 0.178640E+10 | 0.00 | 0.00 |
| July | 0.149798E+10 | 0.137716E+10 | 0.185499E+10 | 0.105774E+09 | 0.174922E+10 | 0.00 | 0.00 |
| August | 0.117753E+10 | 0.145820E+10 | 0.143623E+10 | 18869513.84 | 0.141736E+10 | 0.00 | 0.00 |
| September | 0.536421E+09 | 0.219495E+10 | 0.105411E+10 | 98054.46 | 0.105401E+10 | 0.00 | 0.00 |
| October | 77095767.57 | 0.312892E+10 | 0.717942E+09 | 0.00 | 0.717942E+09 | 0.00 | 0.00 |
| November | 1221909.18 | 0.368827E+10 | 0.421883E+09 | 0.00 | 0.421883E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.440926E+10 | 0.297108E+09 | 0.00 | 0.297108E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.559931E+10 | 0.336360E+11 | 0.127461E+11 | 0.331458E+09 | 0.124147E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.137716E+10 | 0.297108E+09 | 0.00 | 0.297108E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.149798E+10 | 0.440926E+10 | 0.191210E+10 | 0.125693E+09 | 0.178640E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.610298E+09 | 0.131749E+10 | 0.736929E+09 | 0.429613E+09 | 0.307316E+09 | 0.00 | 0.00 |
| February | 0.812892E+09 | 0.117098E+10 | 0.916197E+09 | 0.520874E+09 | 0.395323E+09 | 0.00 | 0.00 |
| March | 0.442284E+09 | 0.106890E+10 | 0.703096E+09 | 0.185904E+09 | 0.517192E+09 | 0.00 | 0.00 |
| April | 0.151684E+10 | 0.943902E+09 | 0.149066E+10 | 0.665952E+09 | 0.824707E+09 | 0.00 | 0.00 |
| May | 0.138553E+10 | 0.869523E+09 | 0.148272E+10 | 0.567220E+09 | 0.915499E+09 | 0.00 | 0.00 |
| June | 0.146450E+10 | 0.652446E+09 | 0.142939E+10 | 0.499262E+09 | 0.930125E+09 | 0.00 | 0.00 |
| July | 0.177936E+10 | 0.573612E+09 | 0.155333E+10 | 0.617099E+09 | 0.936229E+09 | 0.00 | 0.00 |
| August | 0.187937E+10 | 0.622190E+09 | 0.156012E+10 | 0.719312E+09 | 0.840812E+09 | 0.00 | 0.00 |
| September | 0.177392E+10 | 0.854080E+09 | 0.154776E+10 | 0.860927E+09 | 0.686834E+09 | 0.00 | 0.00 |
| October | 0.974643E+09 | 0.112180E+10 | 0.101569E+10 | 0.543027E+09 | 0.472663E+09 | 0.00 | 0.00 |
| November | 0.526889E+09 | 0.124820E+10 | 0.642859E+09 | 0.349746E+09 | 0.293113E+09 | 0.00 | 0.00 |
| December | 0.362498E+09 | 0.149005E+10 | 0.472077E+09 | 0.266903E+09 | 0.205174E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.135290E+11 | 0.119332E+11 | 0.135508E+11 | 0.622584E+10 | 0.732499E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.362498E+09 | 0.573612E+09 | 0.472077E+09 | 0.185904E+09 | 0.205174E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.187937E+10 | 0.149005E+10 | 0.156012E+10 | 0.860927E+09 | 0.936229E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.241821E+10 | 0.375162E+10 | 0.251997E+10 | 0.167491E+10 | 0.845061E+09 | 0.00 | 0.00 |
| February | 0.288543E+10 | 0.333091E+10 | 0.297068E+10 | 0.189031E+10 | 0.108038E+10 | 0.00 | 0.00 |
| March | 0.136631E+10 | 0.310716E+10 | 0.198252E+10 | 0.626948E+09 | 0.135557E+10 | 0.00 | 0.00 |
| April | 0.431189E+10 | 0.275782E+10 | 0.401534E+10 | 0.197246E+10 | 0.204288E+10 | 0.00 | 0.00 |
| May | 0.316963E+10 | 0.262360E+10 | 0.333621E+10 | 0.121960E+10 | 0.211661E+10 | 0.00 | 0.00 |
| June | 0.292197E+10 | 0.189116E+10 | 0.291502E+10 | 0.809670E+09 | 0.210535E+10 | 0.00 | 0.00 |
| July | 0.387233E+10 | 0.160187E+10 | 0.330475E+10 | 0.117205E+10 | 0.213270E+10 | 0.00 | 0.00 |
| August | 0.502862E+10 | 0.169326E+10 | 0.398411E+10 | 0.196600E+10 | 0.201811E+10 | 0.00 | 0.00 |
| September | 0.564273E+10 | 0.237205E+10 | 0.467222E+10 | 0.290903E+10 | 0.176319E+10 | 0.00 | 0.00 |
| October | 0.347119E+10 | 0.318493E+10 | 0.331476E+10 | 0.203351E+10 | 0.128126E+10 | 0.00 | 0.00 |
| November | 0.212211E+10 | 0.354958E+10 | 0.223662E+10 | 0.141069E+10 | 0.825935E+09 | 0.00 | 0.00 |
| December | 0.162978E+10 | 0.421215E+10 | 0.175381E+10 | 0.115043E+10 | 0.603387E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.388402E+11 | 0.340761E+11 | 0.370060E+11 | 0.188356E+11 | 0.181704E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.136631E+10 | 0.160187E+10 | 0.175381E+10 | 0.626948E+09 | 0.603387E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.564273E+10 | 0.421215E+10 | 0.467222E+10 | 0.290903E+10 | 0.213270E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 29810952.79 | 0.225581E+09 | 57711920.74 | 19068248.70 | 38643672.04 | 0.00 | 0.00 |
| February | 65905512.10 | 0.198573E+09 | 92293229.18 | 38969160.85 | 53324068.33 | 0.00 | 0.00 |
| March | 43713246.55 | 0.180300E+09 | 92394264.78 | 17675019.03 | 74719245.74 | 0.00 | 0.00 |
| April | 0.198322E+09 | 0.153139E+09 | 0.210975E+09 | 83801043.43 | 0.127174E+09 | 0.00 | 0.00 |
| May | 0.235286E+09 | 0.143015E+09 | 0.255773E+09 | 0.104006E+09 | 0.151767E+09 | 0.00 | 0.00 |
| June | 0.275670E+09 | 0.106809E+09 | 0.267298E+09 | 0.110036E+09 | 0.157261E+09 | 0.00 | 0.00 |
| July | 0.318667E+09 | 91904912.24 | 0.281305E+09 | 0.124028E+09 | 0.157277E+09 | 0.00 | 0.00 |
| August | 0.272579E+09 | 97856087.12 | 0.236278E+09 | 0.102302E+09 | 0.133976E+09 | 0.00 | 0.00 |
| September | 0.192406E+09 | 0.136944E+09 | 0.183443E+09 | 82259818.46 | 0.101183E+09 | 0.00 | 0.00 |
| October | 76436913.12 | 0.186580E+09 | 0.101122E+09 | 36362868.60 | 64758671.88 | 0.00 | 0.00 |
| November | 26397023.38 | 0.211914E+09 | 52958201.52 | 15459158.93 | 37499042.59 | 0.00 | 0.00 |
| December | 8873489.50 | 0.257596E+09 | 30975104.47 | 6536423.18 | 24438681.29 | 0.00 | 0.00 |
| Annual Sum or Average | 0.174407E+10 | 0.199021E+10 | 0.186253E+10 | 0.740504E+09 | 0.112202E+10 | 0.00 | 0.00 |
| Minimum of Months | 8873489.50 | 91904912.24 | 30975104.47 | 6536423.18 | 24438681.29 | 0.00 | 0.00 |
| Maximum of Months | 0.318667E+09 | 0.257596E+09 | 0.281305E+09 | 0.124028E+09 | 0.157277E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 74823260.78 | 0.136108E+10 | 0.279227E+09 | 57204555.42 | 0.222023E+09 | 0.00 | 0.00 |
| February | 0.198713E+09 | 0.116656E+10 | 0.426513E+09 | 0.116907E+09 | 0.309606E+09 | 0.00 | 0.00 |
| March | 0.186153E+09 | 0.107330E+10 | 0.506436E+09 | 53024880.35 | 0.453411E+09 | 0.00 | 0.00 |
| April | 0.796413E+09 | 0.891615E+09 | 0.994143E+09 | 0.253019E+09 | 0.741124E+09 | 0.00 | 0.00 |
| May | 0.952011E+09 | 0.801028E+09 | 0.123399E+10 | 0.334532E+09 | 0.899456E+09 | 0.00 | 0.00 |
| June | 0.119789E+10 | 0.607815E+09 | 0.130112E+10 | 0.361413E+09 | 0.939712E+09 | 0.00 | 0.00 |
| July | 0.139489E+10 | 0.525199E+09 | 0.133325E+10 | 0.399983E+09 | 0.933266E+09 | 0.00 | 0.00 |
| August | 0.117726E+10 | 0.565186E+09 | 0.109347E+10 | 0.312930E+09 | 0.780544E+09 | 0.00 | 0.00 |
| September | 0.773364E+09 | 0.799528E+09 | 0.833649E+09 | 0.246841E+09 | 0.586807E+09 | 0.00 | 0.00 |
| October | 0.287384E+09 | 0.108520E+10 | 0.490966E+09 | 0.109088E+09 | 0.381878E+09 | 0.00 | 0.00 |
| November | 74477618.12 | 0.125055E+10 | 0.267959E+09 | 46377322.20 | 0.221582E+09 | 0.00 | 0.00 |
| December | 19149141.04 | 0.152832E+10 | 0.169688E+09 | 19609204.17 | 0.150079E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.713253E+10 | 0.116554E+11 | 0.893042E+10 | 0.231093E+10 | 0.661949E+10 | 0.00 | 0.00 |
| Minimum of Months | 19149141.04 | 0.525199E+09 | 0.169688E+09 | 19609204.17 | 0.150079E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.139489E+10 | 0.152832E+10 | 0.133325E+10 | 0.399983E+09 | 0.939712E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 10031151.42 | 0.266580E+10 | 0.338746E+09 | 0.00 | 0.338746E+09 | 0.00 | 0.00 |
| February | 28230359.61 | 0.229710E+10 | 0.477776E+09 | 0.00 | 0.477776E+09 | 0.00 | 0.00 |
| March | 0.138603E+09 | 0.211956E+10 | 0.731995E+09 | 0.00 | 0.731995E+09 | 0.00 | 0.00 |
| April | 0.560177E+09 | 0.171269E+10 | 0.115336E+10 | 5161900.13 | 0.114820E+10 | 0.00 | 0.00 |
| May | 0.682232E+09 | 0.148422E+10 | 0.149006E+10 | 71887454.69 | 0.141817E+10 | 0.00 | 0.00 |
| June | 0.111696E+10 | 0.109833E+10 | 0.159403E+10 | 99955152.83 | 0.149408E+10 | 0.00 | 0.00 |
| July | 0.135711E+10 | 0.924817E+09 | 0.156243E+10 | 89081351.03 | 0.147334E+10 | 0.00 | 0.00 |
| August | 0.108526E+10 | 0.100142E+10 | 0.122815E+10 | 19241840.39 | 0.120891E+10 | 0.00 | 0.00 |
| September | 0.562313E+09 | 0.149225E+10 | 0.904635E+09 | 200175.48 | 0.904435E+09 | 0.00 | 0.00 |
| October | 0.138123E+09 | 0.208682E+10 | 0.599005E+09 | 0.00 | 0.599005E+09 | 0.00 | 0.00 |
| November | 7621327.49 | 0.243189E+10 | 0.348303E+09 | 0.00 | 0.348303E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.292182E+10 | 0.245100E+09 | 0.00 | 0.245100E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.568667E+10 | 0.222367E+11 | 0.106736E+11 | 0.285528E+09 | 0.103881E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.924817E+09 | 0.245100E+09 | 0.00 | 0.245100E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.135711E+10 | 0.292182E+10 | 0.159403E+10 | 99955152.83 | 0.149408E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 3612593.23 | 0.143277E+10 | 0.174211E+09 | 0.00 | 0.174211E+09 | 0.00 | 0.00 |
| February | 10981109.24 | 0.125036E+10 | 0.245712E+09 | 0.00 | 0.245712E+09 | 0.00 | 0.00 |
| March | 57136021.31 | 0.116844E+10 | 0.376453E+09 | 0.00 | 0.376453E+09 | 0.00 | 0.00 |
| April | 0.263269E+09 | 0.948746E+09 | 0.593151E+09 | 2654698.30 | 0.590497E+09 | 0.00 | 0.00 |
| May | 0.320606E+09 | 0.820146E+09 | 0.766310E+09 | 36970785.77 | 0.729340E+09 | 0.00 | 0.00 |
| June | 0.538738E+09 | 0.606307E+09 | 0.819782E+09 | 51405638.96 | 0.768376E+09 | 0.00 | 0.00 |
| July | 0.643512E+09 | 0.518728E+09 | 0.803528E+09 | 45813383.70 | 0.757714E+09 | 0.00 | 0.00 |
| August | 0.512065E+09 | 0.564230E+09 | 0.631614E+09 | 9895829.00 | 0.621718E+09 | 0.00 | 0.00 |
| September | 0.260232E+09 | 0.837139E+09 | 0.465237E+09 | 102947.65 | 0.465134E+09 | 0.00 | 0.00 |
| October | 57519202.23 | 0.116236E+10 | 0.308058E+09 | 0.00 | 0.308058E+09 | 0.00 | 0.00 |
| November | 1999482.18 | 0.134038E+10 | 0.179126E+09 | 0.00 | 0.179126E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.157520E+10 | 0.126051E+09 | 0.00 | 0.126051E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.266967E+10 | 0.122248E+11 | 0.548923E+10 | 0.146843E+09 | 0.534239E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.518728E+09 | 0.126051E+09 | 0.00 | 0.126051E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.643512E+09 | 0.157520E+10 | 0.819782E+09 | 51405638.96 | 0.768376E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 3515402.82 | 0.685657E+09 | 75278117.53 | 7146276.29 | 68131841.24 | 0.00 | 0.00 |
| February | 54342139.16 | 0.595944E+09 | 0.145610E+09 | 41524857.82 | 0.104085E+09 | 0.00 | 0.00 |
| March | 65583035.87 | 0.543080E+09 | 0.201007E+09 | 35017539.53 | 0.165989E+09 | 0.00 | 0.00 |
| April | 0.450969E+09 | 0.462085E+09 | 0.510614E+09 | 0.216200E+09 | 0.294414E+09 | 0.00 | 0.00 |
| May | 0.543963E+09 | 0.453673E+09 | 0.623167E+09 | 0.272995E+09 | 0.350172E+09 | 0.00 | 0.00 |
| June | 0.660468E+09 | 0.339200E+09 | 0.662404E+09 | 0.299851E+09 | 0.362553E+09 | 0.00 | 0.00 |
| July | 0.756007E+09 | 0.301482E+09 | 0.696026E+09 | 0.332732E+09 | 0.363294E+09 | 0.00 | 0.00 |
| August | 0.638498E+09 | 0.307054E+09 | 0.578897E+09 | 0.269042E+09 | 0.309855E+09 | 0.00 | 0.00 |
| September | 0.403092E+09 | 0.403828E+09 | 0.411127E+09 | 0.184987E+09 | 0.226140E+09 | 0.00 | 0.00 |
| October | 0.104231E+09 | 0.546153E+09 | 0.189754E+09 | 55535426.04 | 0.134218E+09 | 0.00 | 0.00 |
| November | 10818890.50 | 0.622843E+09 | 83033565.49 | 11181665.66 | 71851899.84 | 0.00 | 0.00 |
| December | 42163.53 | 0.763093E+09 | 50930915.58 | 2719380.79 | 48211534.78 | 0.00 | 0.00 |
| Annual Sum or Average | 0.369153E+10 | 0.602409E+10 | 0.422785E+10 | 0.172893E+10 | 0.249892E+10 | 0.00 | 0.00 |
| Minimum of Months | 42163.53 | 0.301482E+09 | 50930915.58 | 2719380.79 | 48211534.78 | 0.00 | 0.00 |
| Maximum of Months | 0.756007E+09 | 0.763093E+09 | 0.696026E+09 | 0.332732E+09 | 0.363294E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.105087E+10 | 0.113795E+10 | 0.104403E+10 | 0.675841E+09 | 0.368185E+09 | 0.00 | 0.00 |
| February | 0.117978E+10 | 0.104561E+10 | 0.115169E+10 | 0.702778E+09 | 0.448913E+09 | 0.00 | 0.00 |
| March | 0.634795E+09 | 0.965801E+09 | 0.788342E+09 | 0.229530E+09 | 0.558812E+09 | 0.00 | 0.00 |
| April | 0.179737E+10 | 0.883444E+09 | 0.158425E+10 | 0.716062E+09 | 0.868187E+09 | 0.00 | 0.00 |
| May | 0.138451E+10 | 0.837773E+09 | 0.135400E+10 | 0.440818E+09 | 0.913181E+09 | 0.00 | 0.00 |
| June | 0.129085E+10 | 0.630101E+09 | 0.120709E+10 | 0.292185E+09 | 0.914901E+09 | 0.00 | 0.00 |
| July | 0.159161E+10 | 0.581105E+09 | 0.135145E+10 | 0.423222E+09 | 0.928228E+09 | 0.00 | 0.00 |
| August | 0.199325E+10 | 0.625600E+09 | 0.158360E+10 | 0.712363E+09 | 0.871239E+09 | 0.00 | 0.00 |
| September | 0.222974E+10 | 0.809859E+09 | 0.181104E+10 | 0.106094E+10 | 0.750101E+09 | 0.00 | 0.00 |
| October | 0.140977E+10 | 0.101662E+10 | 0.128573E+10 | 0.751453E+09 | 0.534280E+09 | 0.00 | 0.00 |
| November | 0.873401E+09 | 0.110066E+10 | 0.882178E+09 | 0.536651E+09 | 0.345527E+09 | 0.00 | 0.00 |
| December | 0.697435E+09 | 0.130137E+10 | 0.722514E+09 | 0.462918E+09 | 0.259596E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.161334E+11 | 0.109359E+11 | 0.147659E+11 | 0.700476E+10 | 0.776115E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.634795E+09 | 0.581105E+09 | 0.722514E+09 | 0.229530E+09 | 0.259596E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.222974E+10 | 0.130137E+10 | 0.181104E+10 | 0.106094E+10 | 0.928228E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 13113504.19 | 0.708377E+09 | 95518376.77 | 14572254.78 | 80946122.00 | 0.00 | 0.00 |
| February | 93373490.75 | 0.633882E+09 | 0.187364E+09 | 63440412.69 | 0.123924E+09 | 0.00 | 0.00 |
| March | 85574669.47 | 0.592428E+09 | 0.236301E+09 | 43878366.39 | 0.192423E+09 | 0.00 | 0.00 |
| April | 0.519092E+09 | 0.517390E+09 | 0.585912E+09 | 0.249062E+09 | 0.336850E+09 | 0.00 | 0.00 |
| May | 0.608428E+09 | 0.511112E+09 | 0.706881E+09 | 0.308459E+09 | 0.398422E+09 | 0.00 | 0.00 |
| June | 0.724415E+09 | 0.396962E+09 | 0.749002E+09 | 0.336731E+09 | 0.412272E+09 | 0.00 | 0.00 |
| July | 0.844674E+09 | 0.347145E+09 | 0.787912E+09 | 0.374768E+09 | 0.413144E+09 | 0.00 | 0.00 |
| August | 0.724641E+09 | 0.352348E+09 | 0.661508E+09 | 0.307696E+09 | 0.353811E+09 | 0.00 | 0.00 |
| September | 0.472650E+09 | 0.462120E+09 | 0.483100E+09 | 0.222113E+09 | 0.260987E+09 | 0.00 | 0.00 |
| October | 0.141799E+09 | 0.609153E+09 | 0.232990E+09 | 75134430.46 | 0.157855E+09 | 0.00 | 0.00 |
| November | 24112856.12 | 0.682964E+09 | 0.104941E+09 | 19519976.37 | 85420965.83 | 0.00 | 0.00 |
| December | 2534006.18 | 0.800908E+09 | 62391871.59 | 5812821.47 | 56579050.12 | 0.00 | 0.00 |
| Annual Sum or Average | 0.425441E+10 | 0.661479E+10 | 0.489382E+10 | 0.202119E+10 | 0.287263E+10 | 0.00 | 0.00 |
| Minimum of Months | 2534006.18 | 0.347145E+09 | 62391871.59 | 5812821.47 | 56579050.12 | 0.00 | 0.00 |
| Maximum of Months | 0.844674E+09 | 0.800908E+09 | 0.787912E+09 | 0.374768E+09 | 0.413144E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.124460E+10 | 0.284378E+10 | 0.156933E+10 | 0.913844E+09 | 0.655482E+09 | 0.00 | 0.00 |
| February | 0.151295E+10 | 0.255353E+10 | 0.183242E+10 | 0.983430E+09 | 0.848989E+09 | 0.00 | 0.00 |
| March | 0.923601E+09 | 0.240994E+10 | 0.151867E+10 | 0.381257E+09 | 0.113741E+10 | 0.00 | 0.00 |
| April | 0.342865E+10 | 0.209666E+10 | 0.343312E+10 | 0.158187E+10 | 0.185125E+10 | 0.00 | 0.00 |
| May | 0.301915E+10 | 0.198180E+10 | 0.332418E+10 | 0.128423E+10 | 0.203995E+10 | 0.00 | 0.00 |
| June | 0.302648E+10 | 0.149457E+10 | 0.308484E+10 | 0.102215E+10 | 0.206268E+10 | 0.00 | 0.00 |
| July | 0.357752E+10 | 0.137736E+10 | 0.334038E+10 | 0.125261E+10 | 0.208777E+10 | 0.00 | 0.00 |
| August | 0.401010E+10 | 0.146858E+10 | 0.349961E+10 | 0.162316E+10 | 0.187646E+10 | 0.00 | 0.00 |
| September | 0.393900E+10 | 0.188373E+10 | 0.352616E+10 | 0.198327E+10 | 0.154290E+10 | 0.00 | 0.00 |
| October | 0.204659E+10 | 0.252054E+10 | 0.218148E+10 | 0.114568E+10 | 0.103580E+10 | 0.00 | 0.00 |
| November | 0.106105E+10 | 0.273518E+10 | 0.135867E+10 | 0.723883E+09 | 0.634788E+09 | 0.00 | 0.00 |
| December | 0.820580E+09 | 0.322746E+10 | 0.109236E+10 | 0.620870E+09 | 0.471492E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.286103E+11 | 0.265931E+11 | 0.297612E+11 | 0.135163E+11 | 0.162450E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.820580E+09 | 0.137736E+10 | 0.109236E+10 | 0.381257E+09 | 0.471492E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.401010E+10 | 0.322746E+10 | 0.352616E+10 | 0.198327E+10 | 0.208777E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.302815E+09 | 0.282593E+10 | 0.764239E+09 | 0.248668E+09 | 0.515571E+09 | 0.00 | 0.00 |
| February | 0.658652E+09 | 0.250210E+10 | 0.113008E+10 | 0.404323E+09 | 0.725757E+09 | 0.00 | 0.00 |
| March | 0.889354E+09 | 0.233951E+10 | 0.146202E+10 | 0.274023E+09 | 0.118800E+10 | 0.00 | 0.00 |
| April | 0.366089E+10 | 0.198278E+10 | 0.357168E+10 | 0.181478E+10 | 0.175690E+10 | 0.00 | 0.00 |
| May | 0.426460E+10 | 0.185256E+10 | 0.422828E+10 | 0.215962E+10 | 0.206866E+10 | 0.00 | 0.00 |
| June | 0.466783E+10 | 0.140589E+10 | 0.427403E+10 | 0.211230E+10 | 0.216173E+10 | 0.00 | 0.00 |
| July | 0.510521E+10 | 0.134714E+10 | 0.448468E+10 | 0.237983E+10 | 0.210485E+10 | 0.00 | 0.00 |
| August | 0.460758E+10 | 0.147033E+10 | 0.397468E+10 | 0.221739E+10 | 0.175729E+10 | 0.00 | 0.00 |
| September | 0.333621E+10 | 0.182181E+10 | 0.307903E+10 | 0.176125E+10 | 0.131778E+10 | 0.00 | 0.00 |
| October | 0.121593E+10 | 0.240511E+10 | 0.152673E+10 | 0.622014E+09 | 0.904712E+09 | 0.00 | 0.00 |
| November | 0.329568E+09 | 0.265247E+10 | 0.762353E+09 | 0.231686E+09 | 0.530666E+09 | 0.00 | 0.00 |
| December | 0.135864E+09 | 0.318578E+10 | 0.534170E+09 | 0.156351E+09 | 0.377819E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.291745E+11 | 0.257914E+11 | 0.297920E+11 | 0.143822E+11 | 0.154097E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.135864E+09 | 0.134714E+10 | 0.534170E+09 | 0.156351E+09 | 0.377819E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.510521E+10 | 0.318578E+10 | 0.448468E+10 | 0.237983E+10 | 0.216173E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 63580955.20 | 0.813571E+09 | 0.158253E+09 | 63570258.18 | 94682937.46 | 0.00 | 0.00 |
| February | 0.100739E+09 | 0.713816E+09 | 0.213146E+09 | 78737341.48 | 0.134409E+09 | 0.00 | 0.00 |
| March | 89716519.37 | 0.648771E+09 | 0.246608E+09 | 48597081.91 | 0.198011E+09 | 0.00 | 0.00 |
| April | 0.590747E+09 | 0.473684E+09 | 0.640801E+09 | 0.301115E+09 | 0.339686E+09 | 0.00 | 0.00 |
| May | 0.613856E+09 | 0.436916E+09 | 0.696242E+09 | 0.303618E+09 | 0.392625E+09 | 0.00 | 0.00 |
| June | 0.648371E+09 | 0.325779E+09 | 0.666922E+09 | 0.266360E+09 | 0.400562E+09 | 0.00 | 0.00 |
| July | 0.728533E+09 | 0.305615E+09 | 0.703489E+09 | 0.298981E+09 | 0.404508E+09 | 0.00 | 0.00 |
| August | 0.724914E+09 | 0.324154E+09 | 0.666402E+09 | 0.318399E+09 | 0.348003E+09 | 0.00 | 0.00 |
| September | 0.596938E+09 | 0.409122E+09 | 0.580758E+09 | 0.308819E+09 | 0.271939E+09 | 0.00 | 0.00 |
| October | 0.204388E+09 | 0.608923E+09 | 0.289684E+09 | 0.120052E+09 | 0.169632E+09 | 0.00 | 0.00 |
| November | 55673771.59 | 0.732169E+09 | 0.146149E+09 | 49809587.44 | 96339865.90 | 0.00 | 0.00 |
| December | 34612100.38 | 0.901765E+09 | 0.111925E+09 | 41611939.45 | 70313025.74 | 0.00 | 0.00 |
| Annual Sum or Average | 0.445207E+10 | 0.669428E+10 | 0.512038E+10 | 0.219967E+10 | 0.292071E+10 | 0.00 | 0.00 |
| Minimum of Months | 34612100.38 | 0.305615E+09 | 0.111925E+09 | 41611939.45 | 70313025.74 | 0.00 | 0.00 |
| Maximum of Months | 0.728533E+09 | 0.901765E+09 | 0.703489E+09 | 0.318399E+09 | 0.404508E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 81668746.01 | 0.274740E+10 | 0.487602E+09 | 0.119198E+09 | 0.368404E+09 | 0.00 | 0.00 |
| February | 0.173369E+09 | 0.238659E+10 | 0.669037E+09 | 0.147638E+09 | 0.521399E+09 | 0.00 | 0.00 |
| March | 0.244721E+09 | 0.221658E+10 | 0.876585E+09 | 91122700.93 | 0.785463E+09 | 0.00 | 0.00 |
| April | 0.137353E+10 | 0.172446E+10 | 0.184915E+10 | 0.566984E+09 | 0.128217E+10 | 0.00 | 0.00 |
| May | 0.150810E+10 | 0.158857E+10 | 0.212423E+10 | 0.600291E+09 | 0.152394E+10 | 0.00 | 0.00 |
| June | 0.176405E+10 | 0.123613E+10 | 0.212768E+10 | 0.549453E+09 | 0.157823E+10 | 0.00 | 0.00 |
| July | 0.200989E+10 | 0.111784E+10 | 0.217709E+10 | 0.601833E+09 | 0.157526E+10 | 0.00 | 0.00 |
| August | 0.184549E+10 | 0.120941E+10 | 0.193485E+10 | 0.605890E+09 | 0.132896E+10 | 0.00 | 0.00 |
| September | 0.135151E+10 | 0.155182E+10 | 0.159738E+10 | 0.579152E+09 | 0.101823E+10 | 0.00 | 0.00 |
| October | 0.425987E+09 | 0.215330E+10 | 0.880591E+09 | 0.225105E+09 | 0.655485E+09 | 0.00 | 0.00 |
| November | 73881322.28 | 0.251707E+10 | 0.470306E+09 | 93396227.94 | 0.376910E+09 | 0.00 | 0.00 |
| December | 29767753.49 | 0.305079E+10 | 0.347951E+09 | 78025102.83 | 0.269926E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.108820E+11 | 0.234999E+11 | 0.155425E+11 | 0.425809E+10 | 0.112844E+11 | 0.00 | 0.00 |
| Minimum of Months | 29767753.49 | 0.111784E+10 | 0.347951E+09 | 78025102.83 | 0.269926E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.200989E+10 | 0.305079E+10 | 0.217709E+10 | 0.605890E+09 | 0.157823E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 75668577.79 | 0.300306E+10 | 0.510234E+09 | 0.104921E+09 | 0.405312E+09 | 0.00 | 0.00 |
| February | 0.201728E+09 | 0.263051E+10 | 0.747529E+09 | 0.163847E+09 | 0.583682E+09 | 0.00 | 0.00 |
| March | 0.283967E+09 | 0.248827E+10 | 0.100827E+10 | 0.118718E+09 | 0.889557E+09 | 0.00 | 0.00 |
| April | 0.171040E+10 | 0.201801E+10 | 0.223011E+10 | 0.761041E+09 | 0.146907E+10 | 0.00 | 0.00 |
| May | 0.187337E+10 | 0.185000E+10 | 0.257298E+10 | 0.820427E+09 | 0.175256E+10 | 0.00 | 0.00 |
| June | 0.218982E+10 | 0.138502E+10 | 0.255884E+10 | 0.744396E+09 | 0.181444E+10 | 0.00 | 0.00 |
| July | 0.248627E+10 | 0.125017E+10 | 0.263249E+10 | 0.819869E+09 | 0.181262E+10 | 0.00 | 0.00 |
| August | 0.231460E+10 | 0.134241E+10 | 0.234187E+10 | 0.818529E+09 | 0.152334E+10 | 0.00 | 0.00 |
| September | 0.168223E+10 | 0.178028E+10 | 0.192493E+10 | 0.761212E+09 | 0.116371E+10 | 0.00 | 0.00 |
| October | 0.500151E+09 | 0.250891E+10 | 0.101283E+10 | 0.273636E+09 | 0.739195E+09 | 0.00 | 0.00 |
| November | 71185904.21 | 0.286283E+10 | 0.510886E+09 | 92510263.85 | 0.418376E+09 | 0.00 | 0.00 |
| December | 20400522.38 | 0.333273E+10 | 0.356662E+09 | 62330521.93 | 0.294331E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.134098E+11 | 0.264522E+11 | 0.184076E+11 | 0.554144E+10 | 0.128662E+11 | 0.00 | 0.00 |
| Minimum of Months | 20400522.38 | 0.125017E+10 | 0.356662E+09 | 62330521.93 | 0.294331E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.248627E+10 | 0.333273E+10 | 0.263249E+10 | 0.820427E+09 | 0.181444E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
| February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
| March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
| April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
| May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
| June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
| July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
| August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
| September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
| October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
| November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
| December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
| Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
| Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
| Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
| February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
| March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
| April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
| May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
| June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
| July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
| August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
| September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
| October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
| November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
| December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
| Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
| February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
| March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
| April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
| May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
| June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
| July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
| August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
| September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
| October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
| November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
| December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
| Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
| February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
| March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
| April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
| May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
| June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
| July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
| August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
| September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
| October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
| November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
| December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
| Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
| February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
| March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
| April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
| May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
| June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
| July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
| August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
| September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
| October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
| November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
| December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
| Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER G WATER HEATER
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.274088E+10 | -0.258087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160013428.1 | 82.17 | 0.00 | 0.00 |
| February | 0.247923E+10 | -0.233507E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -144160483.4 | 82.17 | 0.00 | 0.00 |
| March | 0.298649E+10 | -0.282667E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159828054.4 | 82.17 | 0.00 | 0.00 |
| April | 0.261234E+10 | -0.245797E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154366625.7 | 82.17 | 0.00 | 0.00 |
| May | 0.286345E+10 | -0.270377E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159686458.9 | 82.17 | 0.00 | 0.00 |
| June | 0.184158E+10 | -0.168695E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154632419.5 | 82.17 | 0.00 | 0.00 |
| July | 0.768552E+09 | -609202530.3 | 0.00 | 0.00 | 744.00 | 0.00 | -159349748.3 | 82.17 | 0.00 | 0.00 |
| August | 0.860421E+09 | -700582778.4 | 0.00 | 0.00 | 744.00 | 0.00 | -159838008.2 | 82.17 | 0.00 | 0.00 |
| September | 0.168790E+10 | -0.153359E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154317196.6 | 82.17 | 0.00 | 0.00 |
| October | 0.274042E+10 | -0.258087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159551849.0 | 82.17 | 0.00 | 0.00 |
| November | 0.273539E+10 | -0.258087E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154517562.0 | 82.17 | 0.00 | 0.00 |
| December | 0.261753E+10 | -0.245797E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159562022.0 | 82.17 | 0.00 | 0.00 |
| Annual Sum or Average | 0.269342E+11 | -0.250544E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.187982E+10 | 82.17 | 0.00 | 0.00 |
| Minimum of Months | 0.768552E+09 | -0.282667E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -160013428.1 | 82.17 | 0.00 | 0.00 |
| Maximum of Months | 0.298649E+10 | -609202530.3 | 0.00 | 0.00 | 744.00 | 0.00 | -144160483.4 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.106173E+11 | -0.962053E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -996778984.7 | 60.05 | 0.00 | 0.00 |
| February | 0.964539E+10 | -0.876177E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -883617676.9 | 60.05 | 0.00 | 0.00 |
| March | 0.114913E+11 | -0.105344E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -956899002.5 | 60.05 | 0.00 | 0.00 |
| April | 0.985910E+10 | -0.899186E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -867234086.2 | 60.05 | 0.00 | 0.00 |
| May | 0.105161E+11 | -0.963960E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -876494188.1 | 60.05 | 0.00 | 0.00 |
| June | 0.670227E+10 | -0.586463E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -837634025.9 | 60.05 | 0.00 | 0.00 |
| July | 0.295059E+10 | -0.206425E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -886338789.5 | 60.05 | 0.00 | 0.00 |
| August | 0.325195E+10 | -0.235661E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -895343779.1 | 60.05 | 0.00 | 0.00 |
| September | 0.606547E+10 | -0.521644E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -849030435.8 | 60.05 | 0.00 | 0.00 |
| October | 0.986276E+10 | -0.894357E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -919187662.1 | 60.05 | 0.00 | 0.00 |
| November | 0.101169E+11 | -0.918864E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -928235824.1 | 60.05 | 0.00 | 0.00 |
| December | 0.997699E+10 | -0.898405E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -992930560.3 | 60.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.101056E+12 | -0.901664E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.108897E+11 | 60.05 | 0.00 | 0.00 |
| Minimum of Months | 0.295059E+10 | -0.105344E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -996778984.7 | 60.05 | 0.00 | 0.00 |
| Maximum of Months | 0.114913E+11 | -0.206425E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -837634025.9 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 195.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 217.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 215.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 417.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 234.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3515.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.976741E+09 | 6475.25 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.603845E+09 | 6374.88 | 01-FEB-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.585465E+09 | 6373.30 | 02-MAR-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 51578747.53 | 6370.27 | 27-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 18195346.98 | 6372.65 | 31-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1408543.08 | 6374.17 | 30-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 39761072.25 | 6374.17 | 19-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 47304167.38 | 6377.00 | 17-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 3698973.84 | 6375.55 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.120578E+09 | 6373.35 | 13-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.463589E+09 | 6372.88 | 24-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.976330E+09 | 6372.87 | 05-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.388849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 1408543.08 | 6370.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.976741E+09 | 6475.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.242448E+10 | 23769.45 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.138438E+10 | 23389.88 | 27-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.127051E+10 | 23384.02 | 06-MAR-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 40499794.45 | 23376.71 | 13-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 8555395.16 | 23385.44 | 19-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 90868276.33 | 23400.72 | 13-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.129761E+09 | 23399.14 | 31-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 2829278.90 | 23402.18 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 97810379.18 | 23393.76 | 20-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.899339E+09 | 23384.14 | 09-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.241896E+10 | 23388.00 | 12-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.876799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.242448E+10 | 23769.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.147421E+10 | 5868.59 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.745234E+09 | 5779.42 | 22-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.472281E+09 | 5775.64 | 27-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 6817745.81 | 5776.76 | 10-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 234347.34 | 3390.89 | 05-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 55653.06 | 834.80 | 24-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 19792018.27 | 5780.32 | 17-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.387471E+09 | 5779.67 | 15-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.132922E+10 | 5778.24 | 05-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.443531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.147421E+10 | 5868.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.139118E+10 | 5946.33 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.898555E+09 | 5855.68 | 01-FEB-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.732695E+09 | 5854.10 | 02-MAR-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.108440E+09 | 5854.88 | 28-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 31183825.82 | 5853.95 | 31-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 2268291.07 | 5855.54 | 30-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 84890688.29 | 5858.18 | 25-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.190403E+09 | 5858.46 | 17-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 29425533.20 | 5858.61 | 11-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.217601E+09 | 5854.70 | 13-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.669965E+09 | 5854.22 | 24-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.123785E+10 | 5854.32 | 05-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.559446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 2268291.07 | 5853.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.139118E+10 | 5946.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.381139E+10 | 23068.02 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.237008E+10 | 22712.15 | 22-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.174293E+10 | 22697.64 | 06-MAR-07:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.158299E+09 | 22698.00 | 18-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 19356590.83 | 22700.69 | 15-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.308308E+09 | 22717.77 | 25-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.809678E+09 | 22720.61 | 16-AUG-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 72496664.20 | 22722.22 | 01-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.360926E+09 | 22706.67 | 13-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.160882E+10 | 22700.15 | 30-NOV-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.310588E+10 | 22706.19 | 05-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.143682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.381139E+10 | 23068.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.103300E+10 | 6430.97 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.611517E+09 | 6331.31 | 01-FEB-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.588539E+09 | 6329.74 | 02-MAR-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 54560543.10 | 6326.74 | 27-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 19770604.79 | 6329.11 | 31-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1782908.05 | 6331.92 | 29-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 46596263.81 | 6330.61 | 19-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 53514250.99 | 6333.42 | 17-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 4111717.19 | 6331.99 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.120855E+09 | 6329.79 | 13-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.478232E+09 | 6329.33 | 24-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.102231E+10 | 6329.32 | 05-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.403479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 1782908.05 | 6326.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.103300E+10 | 6430.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.261179E+10 | 23450.58 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.139484E+10 | 23076.40 | 27-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.123303E+10 | 23070.62 | 06-MAR-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 40316711.44 | 23063.42 | 13-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 8453746.29 | 23072.02 | 19-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.106739E+09 | 23087.08 | 13-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.143407E+09 | 23093.25 | 17-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 3330837.69 | 23088.52 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 89984492.61 | 23080.22 | 20-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.924730E+09 | 23070.74 | 09-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.246758E+10 | 23074.55 | 12-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.902421E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.261179E+10 | 23450.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.154990E+10 | 5852.14 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.752646E+09 | 5763.23 | 22-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.465547E+09 | 5759.46 | 27-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 6968559.49 | 5760.58 | 10-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 324349.97 | 4162.26 | 05-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 92376.39 | 1385.65 | 24-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 20003035.82 | 5764.13 | 17-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.401357E+09 | 5763.48 | 15-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.135986E+10 | 5762.05 | 05-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.455669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.154990E+10 | 5852.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.139966E+10 | 5949.59 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.899954E+09 | 5858.89 | 01-FEB-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.731862E+09 | 5857.32 | 02-MAR-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.108559E+09 | 5858.09 | 28-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 31019381.57 | 5857.16 | 31-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 2258751.28 | 5858.75 | 30-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 85261945.77 | 5861.40 | 25-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.192446E+09 | 5861.68 | 17-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 29999103.20 | 5861.83 | 11-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.218025E+09 | 5857.91 | 13-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.672559E+09 | 5857.43 | 24-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.124105E+10 | 5857.53 | 05-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.561265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 2258751.28 | 5857.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.139966E+10 | 5949.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.383386E+10 | 23061.65 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.236799E+10 | 22705.90 | 22-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.173349E+10 | 22691.38 | 06-MAR-07:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.157334E+09 | 22691.75 | 18-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 19305045.98 | 22694.44 | 15-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.306261E+09 | 22711.54 | 25-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.811937E+09 | 22714.38 | 16-AUG-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 72768780.38 | 22715.98 | 01-SEP-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.358363E+09 | 22700.42 | 13-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.161117E+10 | 22693.90 | 30-NOV-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.310810E+10 | 22699.94 | 05-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.143806E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.383386E+10 | 23061.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.100761E+10 | 6435.68 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.599901E+09 | 6335.95 | 01-FEB-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.571819E+09 | 6334.38 | 02-MAR-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 49234595.30 | 6331.37 | 27-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 17589806.43 | 6333.75 | 31-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1441752.70 | 6335.25 | 30-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 40038473.49 | 6335.25 | 19-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 46948963.81 | 6338.07 | 17-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 3559483.63 | 6336.63 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.111197E+09 | 6334.43 | 13-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.458951E+09 | 6333.97 | 24-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.999037E+09 | 6333.96 | 05-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.390733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 1441752.70 | 6331.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.100761E+10 | 6435.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.249622E+10 | 23541.39 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.133033E+10 | 23165.69 | 27-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.113774E+10 | 23159.90 | 06-MAR-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 29232030.98 | 23151.52 | 10-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 7147844.17 | 23157.95 | 17-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 78006526.66 | 23176.40 | 13-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.114341E+09 | 23174.84 | 31-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 2468660.29 | 23177.85 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 62511472.47 | 23169.52 | 20-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.823595E+09 | 23160.00 | 09-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.237873E+10 | 23163.83 | 12-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.846032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.249622E+10 | 23541.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.143634E+10 | 5883.58 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.653976E+09 | 5794.10 | 22-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.367582E+09 | 5789.67 | 06-MAR-07:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 3609468.68 | 5787.42 | 10-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 9803669.64 | 5793.27 | 24-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.321199E+09 | 5794.35 | 15-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.124616E+10 | 5792.50 | 05-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.403867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.143634E+10 | 5883.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.138868E+10 | 5972.58 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.884211E+09 | 5881.55 | 01-FEB-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.707559E+09 | 5879.96 | 02-MAR-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 95617325.39 | 5880.76 | 28-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 24141309.89 | 5879.82 | 31-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1483538.24 | 5881.42 | 30-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 62730283.30 | 5884.09 | 25-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.161003E+09 | 5884.37 | 17-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 24454215.98 | 5884.52 | 11-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.205567E+09 | 5880.57 | 13-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.657840E+09 | 5880.09 | 24-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.123552E+10 | 5880.18 | 05-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.544881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 1483538.24 | 5879.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.138868E+10 | 5972.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.252964E+10 | 15440.75 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.153465E+10 | 15202.68 | 22-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.106943E+10 | 15191.24 | 06-MAR-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 78149082.42 | 15192.55 | 27-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 10961044.91 | 15192.58 | 30-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.115509E+09 | 15206.64 | 25-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.414337E+09 | 15208.54 | 16-AUG-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 40154020.50 | 15204.18 | 05-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.198629E+09 | 15198.65 | 10-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.101096E+10 | 15194.58 | 30-NOV-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.206192E+10 | 15198.69 | 05-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.906434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.252964E+10 | 15440.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.432564E+09 | 7626.81 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.170071E+09 | 7505.38 | 27-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.102676E+09 | 7503.52 | 06-MAR-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 5621634.79 | 7501.34 | 17-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 2880557.49 | 7504.48 | 06-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 10300117.64 | 7508.30 | 31-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 563194.81 | 7509.26 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 10056374.71 | 7502.20 | 17-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 80058380.10 | 7499.88 | 15-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.252150E+09 | 7504.79 | 12-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.106694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.432564E+09 | 7626.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.405104E+10 | 12953.92 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.173212E+10 | 12759.63 | 22-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.791486E+09 | 12749.30 | 06-MAR-07:26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 2951413.81 | 12738.74 | 04-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 24652501.74 | 12758.94 | 25-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.999217E+09 | 12760.36 | 15-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.325494E+10 | 12757.01 | 20-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.108564E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.405104E+10 | 12953.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.703419E+10 | 7878.74 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.612786E+10 | 8028.51 | 09-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.700931E+10 | 8028.63 | 31-MAR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.316640E+10 | 8049.38 | 17-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.298160E+10 | 8055.29 | 12-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.161762E+10 | 8057.10 | 06-JUN-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.121887E+10 | 8040.12 | 27-JUL-14:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.121071E+10 | 7954.90 | 11-AUG-14:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.132737E+10 | 8052.10 | 19-SEP-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.372262E+10 | 8047.48 | 10-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.601714E+10 | 8033.31 | 10-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.690930E+10 | 7759.09 | 05-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.483430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.121071E+10 | 7759.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.703419E+10 | 8057.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 52808016.75 | 3210.29 | 02-JAN-05:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 52808016.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 52808016.75 | 3210.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.229093E+10 | 17459.16 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.919610E+09 | 17182.07 | 27-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.503466E+09 | 17178.43 | 06-MAR-07:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 1027175.03 | 17099.05 | 03-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 8117369.62 | 17167.76 | 24-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.456471E+09 | 17180.84 | 30-NOV-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.203425E+10 | 17186.62 | 05-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.621387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.229093E+10 | 17459.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.153686E+10 | 15182.38 | 09-JAN-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.645228E+09 | 15179.73 | 22-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.361757E+09 | 15176.50 | 01-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 358123.20 | 514.56 | 03-APR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 33071987.48 | 4413.45 | 30-OCT-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.412585E+09 | 15176.67 | 13-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.122216E+10 | 15179.43 | 05-DEC-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.421203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.153686E+10 | 15182.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.132277E+10 | 16402.54 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.326846E+09 | 16136.85 | 22-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 84724904.87 | 16129.15 | 06-MAR-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 1835194.73 | 15810.43 | 23-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.135484E+09 | 16114.89 | 30-NOV-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.770856E+09 | 16136.28 | 05-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.264251E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.132277E+10 | 16402.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_POD_1 HEATING COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.688030E+11 | 167276.58 | 10-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.507762E+11 | 158466.57 | 17-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.470781E+11 | 118947.55 | 21-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.969936E+10 | 79456.27 | 03-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.703651E+10 | 77252.75 | 02-MAY-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.335550E+09 | 32461.04 | 07-JUN-10:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 10920629.81 | 18863.95 | 05-JUL-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 549052.28 | 1830.17 | 31-AUG-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.392276E+09 | 41154.93 | 20-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.107105E+11 | 86041.38 | 12-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.382760E+11 | 140424.54 | 29-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.619493E+11 | 150591.40 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.295068E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 549052.28 | 1830.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.688030E+11 | 167276.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:6 HEATING COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:7 HEATING COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.140041E+11 | 79107.52 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.939579E+10 | 79107.52 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.817423E+10 | 79107.52 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.211166E+10 | 31757.68 | 03-APR-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.155631E+10 | 24624.15 | 17-MAY-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.222227E+09 | 14805.57 | 08-JUN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.156429E+09 | 12291.25 | 20-JUL-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.104844E+09 | 9593.39 | 30-AUG-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.337761E+09 | 19831.86 | 28-SEP-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.283754E+10 | 57260.87 | 23-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.724900E+10 | 79107.52 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.117078E+11 | 79107.52 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.578576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.104844E+09 | 9593.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.140041E+11 | 79107.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_POD_1 COOLING COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 1522398.05 | 1486021.11 | 17616.61 | 30-MAR-14:01 | 17616.61 | 0.00 |
| April | 0.00 | 0.00 | 0.907175E+10 | 0.894384E+10 | 175489.74 | 28-APR-14:02 | 175489.74 | 0.00 |
| May | 0.00 | 0.00 | 0.170166E+11 | 0.153342E+11 | 269792.11 | 22-MAY-15:00 | 269792.11 | 0.00 |
| June | 0.00 | 0.00 | 0.523992E+11 | 0.455728E+11 | 395953.14 | 13-JUN-14:05 | 313690.96 | 0.00 |
| July | 0.00 | 0.00 | 0.639193E+11 | 0.517030E+11 | 242238.84 | 21-JUL-14:05 | 242238.84 | 0.00 |
| August | 0.00 | 0.00 | 0.807656E+11 | 0.641142E+11 | 208802.44 | 17-AUG-14:03 | 157954.84 | 0.00 |
| September | 0.00 | 0.00 | 0.501076E+11 | 0.436505E+11 | 246319.63 | 12-SEP-14:02 | 176385.79 | 0.00 |
| October | 0.00 | 0.00 | 0.233935E+10 | 0.220097E+10 | 114593.25 | 17-OCT-14:02 | 82077.55 | 0.00 |
| November | 0.00 | 0.00 | 56509431.06 | 42629020.08 | 39113.03 | 10-NOV-15:01 | 33357.42 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.275677E+12 | 0.231564E+12 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.807656E+11 | 0.641142E+11 | 395953.14 | 313690.96 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:6 COOLING COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.119464E+09 | 75301976.24 | 27827.84 | 03-JAN-06:01 | 19454.94 | 0.00 |
| February | 0.00 | 0.00 | 0.119598E+09 | 73573295.54 | 27827.84 | 03-FEB-06:01 | 16804.47 | 0.00 |
| March | 0.00 | 0.00 | 0.156809E+09 | 0.101382E+09 | 27827.84 | 01-MAR-06:01 | 17418.78 | 0.00 |
| April | 0.00 | 0.00 | 0.745541E+09 | 0.648247E+09 | 28447.22 | 30-APR-11:53 | 26825.51 | 0.00 |
| May | 0.00 | 0.00 | 0.145670E+10 | 0.109790E+10 | 28088.14 | 21-MAY-18:33 | 23545.50 | 0.00 |
| June | 0.00 | 0.00 | 0.401351E+10 | 0.300496E+10 | 31877.39 | 25-JUN-17:53 | 14455.83 | 0.00 |
| July | 0.00 | 0.00 | 0.386823E+10 | 0.292871E+10 | 30105.11 | 23-JUL-15:52 | 20863.43 | 0.00 |
| August | 0.00 | 0.00 | 0.472498E+10 | 0.354052E+10 | 29482.05 | 19-AUG-15:53 | 19723.00 | 0.00 |
| September | 0.00 | 0.00 | 0.362215E+10 | 0.283219E+10 | 29955.06 | 10-SEP-15:33 | 20421.86 | 0.00 |
| October | 0.00 | 0.00 | 0.299229E+09 | 0.207253E+09 | 27827.84 | 19-OCT-05:11 | 17771.61 | 0.00 |
| November | 0.00 | 0.00 | 0.172431E+09 | 0.106739E+09 | 27827.84 | 01-NOV-05:01 | 16965.86 | 0.00 |
| December | 0.00 | 0.00 | 0.112530E+09 | 72595765.56 | 27827.84 | 20-DEC-06:01 | 16238.77 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.194112E+11 | 0.146894E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.112530E+09 | 72595765.56 | 27827.84 | 14455.83 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.472498E+10 | 0.354052E+10 | 31877.39 | 26825.51 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:7 COOLING COIL
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.254836E+09 | 0.233905E+09 | 45532.83 | 30-APR-14:02 | 45532.83 | 0.00 |
| May | 0.00 | 0.00 | 0.113255E+10 | 0.912321E+09 | 29642.35 | 22-MAY-14:00 | 26309.54 | 0.00 |
| June | 0.00 | 0.00 | 0.463889E+10 | 0.362903E+10 | 49971.99 | 25-JUN-17:31 | 29263.88 | 0.00 |
| July | 0.00 | 0.00 | 0.123609E+10 | 0.114316E+10 | 48844.95 | 23-JUL-15:51 | 34293.89 | 0.00 |
| August | 0.00 | 0.00 | 0.108316E+10 | 0.954608E+09 | 46570.98 | 20-AUG-16:03 | 46570.98 | 0.00 |
| September | 0.00 | 0.00 | 0.392922E+10 | 0.315101E+10 | 31152.15 | 13-SEP-14:00 | 26229.68 | 0.00 |
| October | 0.00 | 0.00 | 9591026.35 | 8966070.28 | 2826.67 | 11-OCT-11:00 | 2662.19 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.122843E+11 | 0.100330E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.463889E+10 | 0.362903E+10 | 49971.99 | 46570.98 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 17073.92 | 414960.88 | 02-JAN-06:01 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 11064.61 | 405358.11 | 23-FEB-07:01 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 8256.88 | 415439.14 | 08-MAR-07:01 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 1596.51 | 338073.38 | 03-APR-07:01 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 1178.85 | 195979.92 | 05-MAY-07:01 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 620.57 | 44258.50 | 30-JUN-07:01 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 952.51 | 265926.30 | 05-JUL-07:01 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 1603.65 | 254515.60 | 24-AUG-07:01 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 623.33 | 235014.14 | 01-SEP-07:01 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 2215.37 | 364279.51 | 30-OCT-07:01 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 7462.57 | 384734.23 | 20-NOV-07:01 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 15057.14 | 432843.20 | 18-DEC-06:01 |
| Annual Sum or Average | 0.00 | 5631.20 | ||||
| Minimum of Months | 0.00 | 0.00 | 620.57 | 44258.50 | ||
| Maximum of Months | 0.00 | 0.00 | 17073.92 | 432843.20 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 3580.42 | 18248.41 | 31-JAN-13:30 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 3610.28 | 18277.42 | 14-FEB-13:20 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 3920.54 | 18247.46 | 01-MAR-13:50 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 3457.78 | 17974.61 | 03-APR-12:20 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 3587.02 | 17577.36 | 01-MAY-12:30 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 2252.12 | 17076.61 | 01-JUN-12:40 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 763.16 | 4992.93 | 03-JUL-19:00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 871.19 | 4924.96 | 31-AUG-18:30 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 2003.03 | 16634.80 | 29-SEP-12:30 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 3327.75 | 17078.70 | 31-OCT-12:15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 3533.17 | 17563.60 | 30-NOV-13:30 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 3343.32 | 17976.13 | 29-DEC-13:20 |
| Annual Sum or Average | 0.00 | 2848.40 | ||||
| Minimum of Months | 0.00 | 0.00 | 763.16 | 4924.96 | ||
| Maximum of Months | 0.00 | 0.00 | 3920.54 | 18277.42 |
Report: FanReportMonthly
For: VAV_POD_1 FAN
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.180792E+11 | 0.45 | 18668.16 | 02-JAN-06:01 | 1.10 |
| February | 0.152768E+11 | 0.42 | 18488.77 | 01-FEB-08:61 | 1.09 |
| March | 0.178586E+11 | 0.44 | 18668.16 | 08-MAR-07:01 | 1.10 |
| April | 0.187777E+11 | 0.44 | 39896.69 | 28-APR-14:30 | 1.51 |
| May | 0.226942E+11 | 0.48 | 43881.27 | 23-MAY-14:04 | 1.57 |
| June | 0.260492E+11 | 0.56 | 43454.06 | 13-JUN-12:10 | 1.56 |
| July | 0.184423E+11 | 0.44 | 21442.41 | 22-JUL-10:50 | 1.16 |
| August | 0.195943E+11 | 0.47 | 20478.52 | 20-AUG-15:40 | 1.14 |
| September | 0.213782E+11 | 0.46 | 41075.57 | 27-SEP-14:10 | 1.53 |
| October | 0.173396E+11 | 0.41 | 29073.60 | 03-OCT-14:13 | 1.32 |
| November | 0.163758E+11 | 0.42 | 18488.77 | 06-NOV-08:61 | 1.09 |
| December | 0.166927E+11 | 0.41 | 18668.16 | 08-DEC-07:01 | 1.10 |
| Annual Sum or Average | 0.228558E+12 | 0.45 | |||
| Minimum of Months | 0.152768E+11 | 0.41 | 18488.77 | 1.09 | |
| Maximum of Months | 0.260492E+11 | 0.56 | 43881.27 | 1.57 |
Report: FanReportMonthly
For: BATH_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | -0.0 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
| August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: GYM_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | -0.0 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | -0.0 | 0.00 | 01-FEB-00:10 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
| August | 0.00 | -0.0 | 0.00 | 01-AUG-00:10 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | -0.0 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: CAFETERIA_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | -0.0 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | -0.0 | 0.00 | 01-JUL-00:10 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:05 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.273710E+10 | 0.73 | 2525.20 | 02-JAN-07:04 | 1.35 |
| February | 0.248013E+10 | 0.74 | 2525.20 | 03-FEB-07:01 | 1.37 |
| March | 0.303426E+10 | 0.90 | 2525.20 | 10-MAR-07:01 | 1.37 |
| April | 0.282203E+10 | 1.09 | 2525.20 | 27-APR-09:30 | 1.37 |
| May | 0.311453E+10 | 1.11 | 2525.20 | 22-MAY-11:00 | 1.37 |
| June | 0.323154E+10 | 1.12 | 2525.20 | 08-JUN-14:20 | 1.37 |
| July | 0.311694E+10 | 1.10 | 2525.20 | 18-JUL-08:00 | 1.36 |
| August | 0.342479E+10 | 1.12 | 2525.20 | 04-AUG-06:17 | 1.37 |
| September | 0.296405E+10 | 1.10 | 2525.20 | 05-SEP-13:05 | 1.37 |
| October | 0.289355E+10 | 1.06 | 2525.20 | 02-OCT-10:00 | 1.37 |
| November | 0.278314E+10 | 0.90 | 2525.20 | 01-NOV-06:01 | 1.37 |
| December | 0.259784E+10 | 0.65 | 2525.20 | 05-DEC-07:01 | 1.37 |
| Annual Sum or Average | 0.351999E+11 | 0.97 | |||
| Minimum of Months | 0.248013E+10 | 0.65 | 2525.20 | 1.35 | |
| Maximum of Months | 0.342479E+10 | 1.12 | 2525.20 | 1.37 |
Report: FanReportMonthly
For: PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.445610E+10 | 0.55 | 4150.67 | 05-JAN-16:18 | 1.34 |
| February | 0.400802E+10 | 0.55 | 4150.67 | 09-FEB-16:12 | 1.34 |
| March | 0.482690E+10 | 0.59 | 4150.67 | 17-MAR-15:04 | 1.34 |
| April | 0.418634E+10 | 0.52 | 4150.67 | 05-APR-07:27 | 1.34 |
| May | 0.460226E+10 | 0.55 | 4150.67 | 08-MAY-17:05 | 1.34 |
| June | 0.462049E+10 | 0.59 | 4150.67 | 16-JUN-06:40 | 1.34 |
| July | 0.422259E+10 | 0.53 | 4150.67 | 03-JUL-07:00 | 1.34 |
| August | 0.481484E+10 | 0.58 | 4150.67 | 18-AUG-06:27 | 1.33 |
| September | 0.418387E+10 | 0.52 | 4150.67 | 07-SEP-07:13 | 1.34 |
| October | 0.439359E+10 | 0.53 | 4150.67 | 23-OCT-16:30 | 1.34 |
| November | 0.440833E+10 | 0.56 | 4150.67 | 01-NOV-06:01 | 1.34 |
| December | 0.422573E+10 | 0.53 | 4150.67 | 11-DEC-11:20 | 1.34 |
| Annual Sum or Average | 0.529491E+11 | 0.55 | |||
| Minimum of Months | 0.400802E+10 | 0.52 | 4150.67 | 1.33 | |
| Maximum of Months | 0.482690E+10 | 0.59 | 4150.67 | 1.34 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 0.199492E+09 | 0.179543E+09 | 737.04 | 02-JAN-06:33 | 663.34 | 663.34 | 52.60 | 2.35 |
| February | 0.126990E+09 | 0.114291E+09 | 697.94 | 21-FEB-07:15 | 628.15 | 628.15 | 54.94 | 2.23 |
| March | 0.114694E+09 | 0.103225E+09 | 724.19 | 08-MAR-07:01 | 651.77 | 651.77 | 39.26 | 2.33 |
| April | 29214774.59 | 26293297.13 | 651.61 | 03-APR-07:01 | 586.45 | 586.45 | 42.80 | 2.06 |
| May | 24107760.78 | 21696984.71 | 585.13 | 17-MAY-07:01 | 526.61 | 526.61 | 52.42 | 1.56 |
| June | 12479731.23 | 11231758.11 | 303.14 | 30-JUN-07:01 | 272.83 | 272.83 | 54.92 | 0.39 |
| July | 14146588.09 | 12731929.28 | 597.78 | 05-JUL-07:01 | 538.00 | 538.00 | 44.58 | 1.70 |
| August | 21024330.55 | 18921897.50 | 591.65 | 24-AUG-07:01 | 532.48 | 532.48 | 44.81 | 1.64 |
| September | 12022649.06 | 10820384.15 | 590.92 | 01-SEP-07:01 | 531.83 | 531.83 | 47.46 | 1.63 |
| October | 38372110.20 | 34534899.18 | 683.57 | 23-OCT-07:01 | 615.21 | 615.21 | 42.42 | 2.19 |
| November | 0.100062E+09 | 90056241.92 | 695.51 | 20-NOV-07:04 | 625.96 | 625.96 | 53.73 | 2.22 |
| December | 0.178402E+09 | 0.160562E+09 | 728.82 | 26-DEC-07:11 | 655.94 | 655.94 | 52.17 | 2.33 |
| Annual Sum or Average | 0.871009E+09 | 0.783908E+09 | ||||||
| Minimum of Months | 12022649.06 | 10820384.15 | 303.14 | 272.83 | 272.83 | 39.26 | 0.39 | |
| Maximum of Months | 0.199492E+09 | 0.179543E+09 | 737.04 | 663.34 | 663.34 | 54.94 | 2.35 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 12215899.87 | 3664769.96 | 13.47 | 02-JAN-08:61 | 4.04 | 4.04 | 53.84 | 0.11 |
| February | 11052480.83 | 3315744.25 | 13.47 | 01-FEB-08:61 | 4.04 | 4.04 | 45.92 | 0.11 |
| March | 13379318.90 | 4013795.67 | 13.47 | 01-MAR-08:61 | 4.04 | 4.04 | 45.92 | 0.11 |
| April | 11634190.35 | 3490257.10 | 13.47 | 03-APR-07:01 | 4.04 | 4.04 | 46.11 | 0.11 |
| May | 12797609.38 | 3839282.82 | 13.47 | 01-MAY-07:01 | 4.04 | 4.04 | 46.41 | 0.11 |
| June | 12797609.38 | 3839282.82 | 13.47 | 01-JUN-07:01 | 4.04 | 4.04 | 46.81 | 0.11 |
| July | 11634190.35 | 3490257.10 | 13.47 | 03-JUL-07:01 | 4.04 | 4.04 | 51.36 | 0.11 |
| August | 13379318.90 | 4013795.67 | 13.47 | 01-AUG-07:01 | 4.04 | 4.04 | 51.98 | 0.11 |
| September | 11634190.35 | 3490257.10 | 13.47 | 01-SEP-07:01 | 4.04 | 4.04 | 51.72 | 0.11 |
| October | 12215899.87 | 3664769.96 | 13.47 | 02-OCT-07:01 | 4.04 | 4.04 | 47.15 | 0.11 |
| November | 12215899.87 | 3664769.96 | 13.47 | 01-NOV-07:01 | 4.04 | 4.04 | 46.81 | 0.11 |
| December | 11634190.35 | 3490257.10 | 13.47 | 01-DEC-08:61 | 4.04 | 4.04 | 46.44 | 0.11 |
| Annual Sum or Average | 0.146591E+09 | 43977239.52 | ||||||
| Minimum of Months | 11052480.83 | 3315744.25 | 13.47 | 4.04 | 4.04 | 45.92 | 0.11 | |
| Maximum of Months | 13379318.90 | 4013795.67 | 13.47 | 4.04 | 4.04 | 53.84 | 0.11 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 28.49 | 28.49 | 17073.92 | 414960.88 | 02-JAN-06:01 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 27.73 | 27.73 | 11064.61 | 405358.11 | 23-FEB-07:01 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 27.36 | 27.36 | 8256.88 | 415439.14 | 08-MAR-07:01 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 24.35 | 24.35 | 1596.51 | 338073.38 | 03-APR-07:01 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 53.75 | 53.75 | 1178.85 | 195979.92 | 05-MAY-07:01 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 47.83 | 47.83 | 620.57 | 44258.50 | 30-JUN-07:01 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 46.02 | 46.02 | 952.51 | 265926.30 | 05-JUL-07:01 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 28.50 | 28.50 | 1603.65 | 254515.60 | 24-AUG-07:01 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 27.92 | 27.92 | 623.33 | 235014.14 | 01-SEP-07:01 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 55.29 | 55.29 | 2215.37 | 364279.51 | 30-OCT-07:01 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 23.83 | 23.83 | 7462.57 | 384734.23 | 20-NOV-07:01 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 27.45 | 27.45 | 15057.14 | 432843.20 | 18-DEC-06:01 |
| Annual Sum or Average | 0.00 | 5631.20 | ||||||
| Minimum of Months | 0.00 | 0.00 | 23.83 | 23.83 | 620.57 | 44258.50 | ||
| Maximum of Months | 0.00 | 0.00 | 55.29 | 55.29 | 17073.92 | 432843.20 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 60.00 | 60.00 | 3580.42 | 18248.41 | 31-JAN-13:30 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 47.57 | 47.57 | 3610.28 | 18277.42 | 14-FEB-13:20 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 47.57 | 47.57 | 3920.54 | 18247.46 | 01-MAR-13:50 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 47.73 | 47.73 | 3457.78 | 17974.61 | 03-APR-12:20 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 48.00 | 48.00 | 3587.02 | 17577.36 | 01-MAY-12:30 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 48.36 | 48.36 | 2252.12 | 17076.61 | 01-JUN-12:40 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 48.65 | 48.65 | 763.16 | 4992.93 | 03-JUL-19:00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 48.82 | 48.82 | 871.19 | 4924.96 | 31-AUG-18:30 |
| September | 0.00 | 0.00 | 01-SEP-00:05 | 48.82 | 48.82 | 2003.03 | 16634.80 | 29-SEP-12:30 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 48.67 | 48.67 | 3327.75 | 17078.70 | 31-OCT-12:15 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 48.37 | 48.37 | 3533.17 | 17563.60 | 30-NOV-13:30 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 48.04 | 48.04 | 3343.32 | 17976.13 | 29-DEC-13:20 |
| Annual Sum or Average | 0.00 | 2848.40 | ||||||
| Minimum of Months | 0.00 | 0.00 | 47.57 | 47.57 | 763.16 | 4924.96 | ||
| Maximum of Months | 0.00 | 0.00 | 60.00 | 60.00 | 3920.54 | 18277.42 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_POD_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.460859E+11 | 0.00 | 0.00 | 0.180792E+11 | 0.00 | 0.00 |
| February | 0.269539E+11 | 0.00 | 0.00 | 0.152768E+11 | 0.00 | 0.00 |
| March | 0.222639E+11 | 0.00 | 0.00 | 0.178591E+11 | 0.00 | 0.00 |
| April | 0.416557E+10 | 0.00 | 0.00 | 0.213510E+11 | 0.00 | 0.00 |
| May | 0.319728E+10 | 0.00 | 0.00 | 0.273996E+11 | 0.00 | 0.00 |
| June | 0.162826E+10 | 0.00 | 0.00 | 0.402332E+11 | 0.00 | 0.00 |
| July | 0.258728E+10 | 0.00 | 0.00 | 0.363767E+11 | 0.00 | 0.00 |
| August | 0.433624E+10 | 0.00 | 0.00 | 0.424501E+11 | 0.00 | 0.00 |
| September | 0.161723E+10 | 0.00 | 0.00 | 0.351654E+11 | 0.00 | 0.00 |
| October | 0.601200E+10 | 0.00 | 0.00 | 0.180602E+11 | 0.00 | 0.00 |
| November | 0.194907E+11 | 0.00 | 0.00 | 0.163937E+11 | 0.00 | 0.00 |
| December | 0.406322E+11 | 0.00 | 0.00 | 0.166927E+11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.178970E+12 | 0.00 | 0.00 | 0.305338E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.161723E+10 | 0.00 | 0.00 | 0.152768E+11 | 0.00 | 0.00 |
| Maximum of Months | 0.460859E+11 | 0.00 | 0.00 | 0.424501E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:6
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.276849E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.251157E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.307567E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.300957E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.346564E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.418870E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.407858E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.458683E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.383420E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.297296E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.282871E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.262745E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.399484E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.251157E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.458683E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:7
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.445610E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.400802E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.482690E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.425495E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.488057E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.575339E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.455802E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.511127E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.516306E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.439639E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.440833E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.422573E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.560427E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.400802E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.575339E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_POD_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.180792E+11 | 0.00 | 0.114889E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.152768E+11 | 0.00 | 0.777300E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.178586E+11 | 1522398.05 | 0.693420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.187777E+11 | 0.907175E+10 | 0.138649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.226942E+11 | 0.170166E+11 | 0.102338E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.260492E+11 | 0.523992E+11 | 0.196381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.184423E+11 | 0.639193E+11 | 0.259820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.195943E+11 | 0.807656E+11 | 0.433679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.213782E+11 | 0.501076E+11 | 0.200950E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.173396E+11 | 0.233935E+10 | 0.167224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.163758E+11 | 56509431.06 | 0.577667E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.166927E+11 | 0.00 | 0.102581E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.228558E+12 | 0.275677E+12 | 0.474038E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.152768E+11 | 0.00 | 0.196381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.260492E+11 | 0.807656E+11 | 0.114889E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:6
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.273710E+10 | 0.119464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.248013E+10 | 0.119598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.303426E+10 | 0.156809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.282203E+10 | 0.745541E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.311453E+10 | 0.145670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.323154E+10 | 0.401351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.311694E+10 | 0.386823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.342479E+10 | 0.472498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.296405E+10 | 0.362215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.289355E+10 | 0.299229E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.278314E+10 | 0.172431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.259784E+10 | 0.112530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.351999E+11 | 0.194112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.248013E+10 | 0.112530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.342479E+10 | 0.472498E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:7
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.445610E+10 | 0.00 | 0.140041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.400802E+10 | 0.00 | 0.939579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.482690E+10 | 0.00 | 0.817423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.418634E+10 | 0.254836E+09 | 0.211166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.460226E+10 | 0.113255E+10 | 0.155631E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.462049E+10 | 0.463889E+10 | 0.222227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.422259E+10 | 0.123609E+10 | 0.156429E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.481484E+10 | 0.108316E+10 | 0.104844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.418387E+10 | 0.392922E+10 | 0.337761E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.439359E+10 | 9591026.35 | 0.283754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.440833E+10 | 0.00 | 0.724900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.422573E+10 | 0.00 | 0.117078E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.529491E+11 | 0.122843E+11 | 0.578576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.400802E+10 | 0.00 | 0.104844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.482690E+10 | 0.463889E+10 | 0.140041E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_POD_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.180792E+11 | 0.460859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.152768E+11 | 0.269539E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.178586E+11 | 0.222639E+11 | 0.00 | 0.00 | 488428.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.187777E+11 | 0.416557E+10 | 0.00 | 0.00 | 0.257330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.226942E+11 | 0.319728E+10 | 0.00 | 0.00 | 0.470535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.260492E+11 | 0.162826E+10 | 0.00 | 0.00 | 0.141840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.184423E+11 | 0.258728E+10 | 0.00 | 0.00 | 0.179344E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.195943E+11 | 0.433624E+10 | 0.00 | 0.00 | 0.228558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.213782E+11 | 0.161723E+10 | 0.00 | 0.00 | 0.137873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.173396E+11 | 0.601200E+10 | 0.00 | 0.00 | 0.720596E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.163758E+11 | 0.194907E+11 | 0.00 | 0.00 | 17927337.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.166927E+11 | 0.406322E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.228558E+12 | 0.178970E+12 | 0.00 | 0.00 | 0.767791E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.152768E+11 | 0.161723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.260492E+11 | 0.460859E+11 | 0.00 | 0.00 | 0.228558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:6
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.273710E+10 | 0.00 | 0.00 | 0.00 | 31395749.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.248013E+10 | 0.00 | 0.00 | 0.00 | 31440720.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.303426E+10 | 0.00 | 0.00 | 0.00 | 41417561.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.282203E+10 | 0.00 | 0.00 | 0.00 | 0.187547E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.311453E+10 | 0.00 | 0.00 | 0.00 | 0.351116E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.323154E+10 | 0.00 | 0.00 | 0.00 | 0.957161E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.311694E+10 | 0.00 | 0.00 | 0.00 | 0.961638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.342479E+10 | 0.00 | 0.00 | 0.00 | 0.116204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.296405E+10 | 0.00 | 0.00 | 0.00 | 0.870146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.289355E+10 | 0.00 | 0.00 | 0.00 | 79418639.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.278314E+10 | 0.00 | 0.00 | 0.00 | 45577643.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.259784E+10 | 0.00 | 0.00 | 0.00 | 29612912.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.351999E+11 | 0.00 | 0.00 | 0.00 | 0.474851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.248013E+10 | 0.00 | 0.00 | 0.00 | 29612912.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.342479E+10 | 0.00 | 0.00 | 0.00 | 0.116204E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:7
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.445610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.400802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.482690E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.418634E+10 | 0.00 | 0.00 | 0.00 | 68618796.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.460226E+10 | 0.00 | 0.00 | 0.00 | 0.278311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.462049E+10 | 0.00 | 0.00 | 0.00 | 0.113290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.422259E+10 | 0.00 | 0.00 | 0.00 | 0.335431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.481484E+10 | 0.00 | 0.00 | 0.00 | 0.296422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.418387E+10 | 0.00 | 0.00 | 0.00 | 0.979187E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.439359E+10 | 0.00 | 0.00 | 0.00 | 2794500.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.440833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.422573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.529491E+11 | 0.00 | 0.00 | 0.00 | 0.309367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.400802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.482690E+10 | 0.00 | 0.00 | 0.00 | 0.113290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.355798E+10 | 0.00 | 0.00 | 48067.77 | 0.00 | 0.820433E+09 | 0.107880E+09 | 0.00 | 0.65 |
| February | 0.339841E+10 | 0.00 | 0.00 | 92178.45 | 0.00 | 0.221083E+09 | 0.255504E+09 | 0.00 | 0.65 |
| March | 0.412494E+10 | 0.00 | 0.00 | 23505.63 | 0.00 | 0.201842E+09 | 0.113133E+09 | 0.00 | 0.71 |
| April | 0.156874E+10 | 0.00 | 0.00 | 3452412.74 | 83218.13 | 11170672.49 | 0.230578E+10 | 0.00 | 0.82 |
| May | 0.151854E+10 | 0.00 | 0.00 | 4047329.91 | 5166.91 | 4186601.77 | 0.275972E+10 | 0.00 | 0.93 |
| June | 0.150840E+10 | 8626685.13 | 0.00 | 3720831.51 | 8360829.32 | 735969.37 | 0.209888E+10 | 0.00 | 1.20 |
| July | 0.148564E+10 | 13497080.00 | 18783.12 | 528428.00 | 6820184.46 | 3929641.30 | 0.274078E+09 | 744.57 | 0.99 |
| August | 0.132276E+10 | 1828120.97 | 0.00 | 600119.94 | 1234380.19 | 4177937.11 | 0.230066E+09 | 0.00 | 1.11 |
| September | 0.104875E+10 | 0.00 | 0.00 | 4074457.11 | 327610.49 | 1185250.58 | 0.194327E+10 | 0.00 | 1.11 |
| October | 0.228769E+10 | 0.00 | 0.00 | 1912198.48 | 0.00 | 16057069.55 | 0.154730E+10 | 0.00 | 0.78 |
| November | 0.344435E+10 | 0.00 | 0.00 | 280914.46 | 0.00 | 0.183701E+09 | 0.325984E+09 | 0.00 | 0.68 |
| December | 0.327024E+10 | 0.00 | 0.00 | 3925.85 | 0.00 | 0.861887E+09 | 20322606.11 | 0.00 | 0.62 |
| Annual Sum or Average | 0.285364E+11 | 23951886.09 | 18783.12 | 18784369.84 | 16831389.50 | 0.233039E+10 | 0.119819E+11 | 744.57 | 0.85 |
| Minimum of Months | 0.104875E+10 | 0.00 | 0.00 | 3925.85 | 0.00 | 735969.37 | 20322606.11 | 0.00 | 0.62 |
| Maximum of Months | 0.412494E+10 | 13497080.00 | 18783.12 | 4074457.11 | 8360829.32 | 0.861887E+09 | 0.275972E+10 | 744.57 | 1.20 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.182957E+11 | 0.00 | 0.00 | 829148.50 | 0.00 | 0.937107E+09 | 0.234041E+10 | 0.00 | 0.65 |
| February | 0.153257E+11 | 0.00 | 0.00 | 1404441.17 | 0.00 | 0.226623E+09 | 0.308279E+10 | 0.00 | 0.65 |
| March | 0.179428E+11 | 0.00 | 0.00 | 974469.25 | 0.00 | 0.201913E+09 | 0.320666E+10 | 0.00 | 0.71 |
| April | 0.641394E+10 | 0.00 | 0.00 | 18415668.80 | 400416.52 | 18862975.63 | 0.126192E+11 | 0.00 | 0.83 |
| May | 0.643805E+10 | 0.00 | 0.00 | 22018681.46 | 24861.38 | 5024725.19 | 0.143528E+11 | 0.00 | 0.93 |
| June | 0.703910E+10 | 33114787.77 | 0.00 | 17129161.78 | 40229386.83 | 0.00 | 0.103106E+11 | 0.00 | 1.18 |
| July | 0.802343E+10 | 45022010.84 | 90571.07 | 426933.98 | 51261678.05 | 12949075.55 | 0.447048E+09 | 3389.37 | 0.98 |
| August | 0.693848E+10 | 4424686.49 | 0.00 | 977739.43 | 10290117.05 | 14382661.25 | 0.535937E+09 | 0.00 | 1.11 |
| September | 0.433561E+10 | 0.00 | 0.00 | 20809496.18 | 1576347.13 | 595958.32 | 0.101433E+11 | 0.00 | 1.10 |
| October | 0.829118E+10 | 0.00 | 0.00 | 12247041.00 | 0.00 | 20277445.82 | 0.104394E+11 | 0.00 | 0.79 |
| November | 0.145308E+11 | 0.00 | 0.00 | 2822581.40 | 0.00 | 0.140148E+09 | 0.437388E+10 | 0.00 | 0.68 |
| December | 0.185737E+11 | 0.00 | 0.00 | 238037.36 | 0.00 | 0.396587E+09 | 0.996003E+09 | 0.00 | 0.62 |
| Annual Sum or Average | 0.132148E+12 | 82561485.11 | 90571.07 | 98293400.31 | 0.103783E+09 | 0.197447E+10 | 0.728481E+11 | 3389.37 | 0.85 |
| Minimum of Months | 0.433561E+10 | 0.00 | 0.00 | 238037.36 | 0.00 | 0.00 | 0.447048E+09 | 0.00 | 0.62 |
| Maximum of Months | 0.185737E+11 | 45022010.84 | 90571.07 | 22018681.46 | 51261678.05 | 0.937107E+09 | 0.143528E+11 | 3389.37 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.128146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131170E+10 | 0.00 | 0.00 | 0.19 |
| February | 0.159379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.612885E+09 | 0.00 | 0.00 | 0.19 |
| March | 0.219913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320226E+09 | 0.00 | 0.00 | 0.21 |
| April | 0.142978E+10 | 0.00 | 0.00 | 1248012.00 | 47029.19 | 2741272.02 | 0.722225E+09 | 0.00 | 0.24 |
| May | 0.125710E+10 | 0.00 | 0.00 | 2515794.06 | 2919.99 | 0.00 | 0.132071E+10 | 0.00 | 0.30 |
| June | 0.800479E+09 | 7232178.88 | 0.00 | 3246333.19 | 4724968.49 | 0.00 | 0.149957E+10 | 0.00 | 0.41 |
| July | 0.970722E+09 | 4196521.21 | 0.00 | 103367.57 | 7123098.41 | 69095.79 | 26634958.27 | 0.00 | 0.29 |
| August | 0.874366E+09 | 22690.19 | 0.00 | 20372.95 | 1705573.36 | 0.00 | 5255953.75 | 0.00 | 0.32 |
| September | 0.782155E+09 | 0.00 | 0.00 | 2230674.56 | 185143.03 | 0.00 | 0.936578E+09 | 0.00 | 0.33 |
| October | 0.176909E+10 | 0.00 | 0.00 | 500174.97 | 0.00 | 7880901.18 | 0.312656E+09 | 0.00 | 0.22 |
| November | 0.190925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330926E+09 | 0.00 | 0.00 | 0.20 |
| December | 0.115698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122709E+10 | 0.00 | 0.00 | 0.18 |
| Annual Sum or Average | 0.160243E+11 | 11451390.28 | 0.00 | 9864729.30 | 13788732.47 | 0.381351E+10 | 0.482363E+10 | 0.00 | 0.26 |
| Minimum of Months | 0.782155E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
| Maximum of Months | 0.219913E+10 | 7232178.88 | 0.00 | 3246333.19 | 7123098.41 | 0.131170E+10 | 0.149957E+10 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.315429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131994E+10 | 0.00 | 0.00 | 0.65 |
| February | 0.318389E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681237E+09 | 0.00 | 0.00 | 0.65 |
| March | 0.411057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317934E+09 | 0.00 | 0.00 | 0.70 |
| April | 0.236857E+10 | 0.00 | 0.00 | 954623.41 | 83056.09 | 28255786.39 | 0.120774E+10 | 0.00 | 0.75 |
| May | 0.203830E+10 | 0.00 | 0.00 | 2191502.22 | 5156.85 | 6210654.94 | 0.192700E+10 | 0.00 | 0.85 |
| June | 0.182250E+10 | 7239575.57 | 0.00 | 2438541.46 | 8344549.37 | 1454556.30 | 0.160904E+10 | 0.00 | 1.12 |
| July | 0.174702E+10 | 7097694.69 | 16878.55 | 6154.00 | 12873874.82 | 6108685.66 | 6545361.69 | 2611.12 | 0.98 |
| August | 0.154499E+10 | 21215.39 | 0.00 | 1053.27 | 3030991.33 | 8053874.78 | 453891.77 | 0.00 | 1.10 |
| September | 0.163249E+10 | 0.00 | 0.00 | 1612843.47 | 326972.58 | 3866247.02 | 0.988958E+09 | 0.00 | 0.95 |
| October | 0.291290E+10 | 0.00 | 0.00 | 330549.67 | 0.00 | 32042514.03 | 0.673776E+09 | 0.00 | 0.72 |
| November | 0.353025E+10 | 0.00 | 0.00 | 8073.87 | 0.00 | 0.368291E+09 | 44685372.07 | 0.00 | 0.68 |
| December | 0.294141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119941E+10 | 0.00 | 0.00 | 0.62 |
| Annual Sum or Average | 0.309872E+11 | 14358485.65 | 16878.55 | 7543341.37 | 24664601.03 | 0.397281E+10 | 0.645820E+10 | 2611.12 | 0.82 |
| Minimum of Months | 0.154499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1454556.30 | 0.00 | 0.00 | 0.62 |
| Maximum of Months | 0.411057E+10 | 7239575.57 | 16878.55 | 2438541.46 | 12873874.82 | 0.131994E+10 | 0.192700E+10 | 2611.12 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.187230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286743E+10 | 0.00 | 0.00 | 0.65 |
| February | 0.182125E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438737E+09 | 0.00 | 0.00 | 0.65 |
| March | 0.201703E+11 | 0.00 | 0.00 | 103963.05 | 0.00 | 0.253809E+09 | 0.945530E+09 | 0.00 | 0.71 |
| April | 0.946384E+10 | 0.00 | 0.00 | 6961404.84 | 400787.52 | 31314789.93 | 0.792562E+10 | 0.00 | 0.75 |
| May | 0.819363E+10 | 0.00 | 0.00 | 12691677.56 | 24884.41 | 11860356.52 | 0.109827E+11 | 0.00 | 0.85 |
| June | 0.917352E+10 | 28847341.48 | 0.00 | 10591096.79 | 40266660.39 | 0.00 | 0.745829E+10 | 0.00 | 1.12 |
| July | 0.847208E+10 | 0.00 | 911846.67 | 0.00 | 95541598.31 | 19279540.13 | 0.00 | 13500.71 | 0.98 |
| August | 0.746593E+10 | 0.00 | 0.00 | 0.00 | 14728437.18 | 30474000.37 | 0.00 | 0.00 | 1.10 |
| September | 0.808282E+10 | 0.00 | 0.00 | 7410422.77 | 1577807.65 | 8553810.61 | 0.461419E+10 | 0.00 | 0.95 |
| October | 0.116224E+11 | 0.00 | 0.00 | 3197682.73 | 0.00 | 38370915.66 | 0.579532E+10 | 0.00 | 0.73 |
| November | 0.175912E+11 | 0.00 | 0.00 | 243724.44 | 0.00 | 0.221507E+09 | 0.121514E+10 | 0.00 | 0.68 |
| December | 0.185931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138841E+10 | 0.00 | 0.00 | 0.62 |
| Annual Sum or Average | 0.155764E+12 | 28847341.48 | 911846.67 | 41199972.17 | 0.152540E+09 | 0.530975E+10 | 0.389368E+11 | 13500.71 | 0.82 |
| Minimum of Months | 0.746593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
| Maximum of Months | 0.201703E+11 | 28847341.48 | 911846.67 | 12691677.56 | 95541598.31 | 0.286743E+10 | 0.109827E+11 | 13500.71 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.351391E+10 | 0.00 | 0.00 | 29200.83 | 0.00 | 0.881290E+09 | 85320719.80 | 0.00 | 0.65 |
| February | 0.340828E+10 | 0.00 | 0.00 | 82008.60 | 0.00 | 0.226876E+09 | 0.234827E+09 | 0.00 | 0.65 |
| March | 0.413272E+10 | 0.00 | 0.00 | 19560.16 | 0.00 | 0.201441E+09 | 99943876.32 | 0.00 | 0.71 |
| April | 0.159797E+10 | 0.00 | 0.00 | 3281519.39 | 83110.71 | 11986693.76 | 0.224446E+10 | 0.00 | 0.81 |
| May | 0.156931E+10 | 0.00 | 0.00 | 3868609.68 | 5160.24 | 4340745.80 | 0.267175E+10 | 0.00 | 0.92 |
| June | 0.158994E+10 | 8438563.67 | 0.00 | 3523108.75 | 8350037.36 | 758792.79 | 0.198835E+10 | 0.00 | 1.19 |
| July | 0.152660E+10 | 12866780.11 | 18425.70 | 397140.13 | 7219618.83 | 4196923.10 | 0.230321E+09 | 1076.79 | 0.98 |
| August | 0.135170E+10 | 1727979.10 | 0.00 | 472595.98 | 1329696.10 | 4425041.39 | 0.198676E+09 | 0.00 | 1.11 |
| September | 0.107058E+10 | 0.00 | 0.00 | 3955304.29 | 327187.62 | 1192030.42 | 0.190106E+10 | 0.00 | 1.10 |
| October | 0.229055E+10 | 0.00 | 0.00 | 1856769.90 | 0.00 | 16015787.54 | 0.152724E+10 | 0.00 | 0.77 |
| November | 0.344032E+10 | 0.00 | 0.00 | 247540.47 | 0.00 | 0.203359E+09 | 0.304376E+09 | 0.00 | 0.68 |
| December | 0.322548E+10 | 0.00 | 0.00 | 1789.90 | 0.00 | 0.906431E+09 | 15295193.21 | 0.00 | 0.62 |
| Annual Sum or Average | 0.287174E+11 | 23033322.88 | 18425.70 | 17735148.09 | 17314810.87 | 0.246231E+10 | 0.115016E+11 | 1076.79 | 0.85 |
| Minimum of Months | 0.107058E+10 | 0.00 | 0.00 | 1789.90 | 0.00 | 758792.79 | 15295193.21 | 0.00 | 0.62 |
| Maximum of Months | 0.413272E+10 | 12866780.11 | 18425.70 | 3955304.29 | 8350037.36 | 0.906431E+09 | 0.267175E+10 | 1076.79 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.189283E+11 | 0.00 | 0.00 | 431240.83 | 0.00 | 0.111378E+10 | 0.151610E+10 | 0.00 | 0.65 |
| February | 0.155806E+11 | 0.00 | 0.00 | 1199102.51 | 0.00 | 0.216255E+09 | 0.282507E+10 | 0.00 | 0.65 |
| March | 0.180498E+11 | 0.00 | 0.00 | 905209.89 | 0.00 | 0.182628E+09 | 0.310386E+10 | 0.00 | 0.71 |
| April | 0.651719E+10 | 0.00 | 0.00 | 17773622.70 | 400142.90 | 17762443.36 | 0.123618E+11 | 0.00 | 0.82 |
| May | 0.652241E+10 | 0.00 | 0.00 | 21350115.51 | 24844.39 | 4977179.23 | 0.141102E+11 | 0.00 | 0.92 |
| June | 0.726407E+10 | 32402730.77 | 0.00 | 16239198.42 | 40201896.22 | 0.00 | 0.998192E+10 | 0.00 | 1.17 |
| July | 0.819262E+10 | 26666429.68 | 89524.76 | 222500.51 | 69551464.09 | 15254676.99 | 0.269871E+09 | 4371.47 | 0.98 |
| August | 0.714519E+10 | 3243817.79 | 0.00 | 608518.83 | 11460930.44 | 15612277.20 | 0.323202E+09 | 0.00 | 1.11 |
| September | 0.450093E+10 | 0.00 | 0.00 | 19933555.51 | 1575269.94 | 589411.37 | 0.985138E+10 | 0.00 | 1.09 |
| October | 0.835621E+10 | 0.00 | 0.00 | 11772958.88 | 0.00 | 20157680.84 | 0.102570E+11 | 0.00 | 0.78 |
| November | 0.147232E+11 | 0.00 | 0.00 | 2528705.73 | 0.00 | 0.142216E+09 | 0.415371E+10 | 0.00 | 0.68 |
| December | 0.188814E+11 | 0.00 | 0.00 | 125490.05 | 0.00 | 0.389222E+09 | 0.681203E+09 | 0.00 | 0.62 |
| Annual Sum or Average | 0.134662E+12 | 62312978.24 | 89524.76 | 93090219.39 | 0.123215E+09 | 0.211846E+10 | 0.694352E+11 | 4371.47 | 0.85 |
| Minimum of Months | 0.450093E+10 | 0.00 | 0.00 | 125490.05 | 0.00 | 0.00 | 0.269871E+09 | 0.00 | 0.62 |
| Maximum of Months | 0.189283E+11 | 32402730.77 | 89524.76 | 21350115.51 | 69551464.09 | 0.111378E+10 | 0.141102E+11 | 4371.47 | 1.17 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.122850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136137E+10 | 0.00 | 0.00 | 0.19 |
| February | 0.157519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625250E+09 | 0.00 | 0.00 | 0.19 |
| March | 0.219633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314955E+09 | 0.00 | 0.00 | 0.21 |
| April | 0.144121E+10 | 0.00 | 0.00 | 1209901.08 | 46880.22 | 2732589.07 | 0.699617E+09 | 0.00 | 0.23 |
| May | 0.126271E+10 | 0.00 | 0.00 | 2468201.78 | 2910.74 | 0.00 | 0.129817E+10 | 0.00 | 0.29 |
| June | 0.815771E+09 | 7141521.63 | 0.00 | 3173236.41 | 4710002.21 | 0.00 | 0.146484E+10 | 0.00 | 0.40 |
| July | 0.973077E+09 | 4055200.41 | 0.00 | 86861.95 | 7228564.44 | 137232.87 | 20664027.98 | 0.00 | 0.29 |
| August | 0.872497E+09 | 11974.82 | 0.00 | 12124.47 | 1710814.47 | 66018.51 | 4280870.81 | 0.00 | 0.32 |
| September | 0.786465E+09 | 0.00 | 0.00 | 2186628.79 | 184556.59 | 0.00 | 0.920901E+09 | 0.00 | 0.33 |
| October | 0.177100E+10 | 0.00 | 0.00 | 481710.88 | 0.00 | 7867909.44 | 0.300521E+09 | 0.00 | 0.22 |
| November | 0.189126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341900E+09 | 0.00 | 0.00 | 0.20 |
| December | 0.111883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126007E+10 | 0.00 | 0.00 | 0.18 |
| Annual Sum or Average | 0.159328E+11 | 11208696.87 | 0.00 | 9618665.36 | 13883728.67 | 0.391434E+10 | 0.470900E+10 | 0.00 | 0.25 |
| Minimum of Months | 0.786465E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
| Maximum of Months | 0.219633E+10 | 7141521.63 | 0.00 | 3173236.41 | 7228564.44 | 0.136137E+10 | 0.146484E+10 | 0.00 | 0.40 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.314602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133007E+10 | 0.00 | 0.00 | 0.65 |
| February | 0.318815E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678601E+09 | 0.00 | 0.00 | 0.65 |
| March | 0.411229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318068E+09 | 0.00 | 0.00 | 0.70 |
| April | 0.236566E+10 | 0.00 | 0.00 | 959416.13 | 83090.86 | 28267617.94 | 0.121233E+10 | 0.00 | 0.75 |
| May | 0.203495E+10 | 0.00 | 0.00 | 2199970.94 | 5159.01 | 6213255.53 | 0.193266E+10 | 0.00 | 0.85 |
| June | 0.182000E+10 | 7248561.86 | 0.00 | 2446403.59 | 8348043.48 | 1455165.36 | 0.161364E+10 | 0.00 | 1.13 |
| July | 0.174776E+10 | 7100666.71 | 16871.07 | 6058.94 | 12879265.49 | 6111243.55 | 6548200.07 | 2626.76 | 0.98 |
| August | 0.154554E+10 | 21224.27 | 0.00 | 1004.88 | 3032260.49 | 8152329.45 | 454130.66 | 0.00 | 1.10 |
| September | 0.163317E+10 | 0.00 | 0.00 | 1613180.41 | 327109.49 | 3867865.93 | 0.989422E+09 | 0.00 | 0.95 |
| October | 0.291433E+10 | 0.00 | 0.00 | 329471.87 | 0.00 | 31850722.52 | 0.674043E+09 | 0.00 | 0.72 |
| November | 0.353105E+10 | 0.00 | 0.00 | 8023.46 | 0.00 | 0.369131E+09 | 44704136.97 | 0.00 | 0.68 |
| December | 0.294246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120010E+10 | 0.00 | 0.00 | 0.62 |
| Annual Sum or Average | 0.309814E+11 | 14370452.84 | 16871.07 | 7563530.21 | 24674928.84 | 0.398189E+10 | 0.647380E+10 | 2626.76 | 0.82 |
| Minimum of Months | 0.154554E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1455165.36 | 0.00 | 0.00 | 0.62 |
| Maximum of Months | 0.411229E+10 | 7248561.86 | 16871.07 | 2446403.59 | 12879265.49 | 0.133007E+10 | 0.193266E+10 | 2626.76 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.186615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290236E+10 | 0.00 | 0.00 | 0.65 |
| February | 0.181929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435388E+09 | 0.00 | 0.00 | 0.65 |
| March | 0.201020E+11 | 0.00 | 0.00 | 109237.05 | 0.00 | 0.253497E+09 | 0.987892E+09 | 0.00 | 0.71 |
| April | 0.940479E+10 | 0.00 | 0.00 | 7026052.94 | 400295.22 | 31276325.25 | 0.796726E+10 | 0.00 | 0.75 |
| May | 0.814701E+10 | 0.00 | 0.00 | 12789990.63 | 24853.85 | 11845788.17 | 0.110165E+11 | 0.00 | 0.85 |
| June | 0.913337E+10 | 28850502.64 | 0.00 | 10663653.22 | 40217199.93 | 0.00 | 0.748786E+10 | 0.00 | 1.12 |
| July | 0.846168E+10 | 0.00 | 910726.32 | 0.00 | 95424242.38 | 19255858.63 | 0.00 | 13484.43 | 0.98 |
| August | 0.745564E+10 | 0.00 | 0.00 | 0.00 | 14710345.90 | 31555951.91 | 0.00 | 0.00 | 1.10 |
| September | 0.807289E+10 | 0.00 | 0.00 | 7429757.47 | 1575869.60 | 8543303.76 | 0.461322E+10 | 0.00 | 0.95 |
| October | 0.115813E+11 | 0.00 | 0.00 | 3219905.74 | 0.00 | 38323783.78 | 0.581504E+10 | 0.00 | 0.72 |
| November | 0.175699E+11 | 0.00 | 0.00 | 245292.86 | 0.00 | 0.220943E+09 | 0.121364E+10 | 0.00 | 0.68 |
| December | 0.185578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139925E+10 | 0.00 | 0.00 | 0.62 |
| Annual Sum or Average | 0.155341E+12 | 28850502.64 | 910726.32 | 41483889.92 | 0.152353E+09 | 0.535224E+10 | 0.391014E+11 | 13484.43 | 0.82 |
| Minimum of Months | 0.745564E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
| Maximum of Months | 0.201020E+11 | 28850502.64 | 910726.32 | 12789990.63 | 95424242.38 | 0.290236E+10 | 0.110165E+11 | 13484.43 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.353913E+10 | 0.00 | 0.00 | 35786.51 | 0.00 | 0.850485E+09 | 94143320.83 | 0.00 | 0.65 |
| February | 0.341810E+10 | 0.00 | 0.00 | 87858.09 | 0.00 | 0.207807E+09 | 0.246846E+09 | 0.00 | 0.65 |
| March | 0.412941E+10 | 0.00 | 0.00 | 22695.58 | 0.00 | 0.192459E+09 | 0.115437E+09 | 0.00 | 0.71 |
| April | 0.157487E+10 | 0.00 | 0.00 | 3385090.47 | 83171.62 | 10626980.15 | 0.228542E+10 | 0.00 | 0.82 |
| May | 0.154107E+10 | 0.00 | 0.00 | 3958983.50 | 5164.03 | 3864822.28 | 0.271682E+10 | 0.00 | 0.92 |
| June | 0.154673E+10 | 8496454.19 | 0.00 | 3604612.36 | 8356157.17 | 734849.06 | 0.204243E+10 | 0.00 | 1.19 |
| July | 0.150231E+10 | 13192473.80 | 18743.84 | 462562.12 | 7009837.11 | 4053529.12 | 0.256121E+09 | 772.94 | 0.98 |
| August | 0.133572E+10 | 1766579.49 | 0.00 | 536236.26 | 1293789.70 | 4166478.30 | 0.216130E+09 | 0.00 | 1.11 |
| September | 0.104583E+10 | 0.00 | 0.00 | 4043387.88 | 327427.42 | 1167472.16 | 0.193764E+10 | 0.00 | 1.11 |
| October | 0.227032E+10 | 0.00 | 0.00 | 1906255.19 | 0.00 | 13775916.65 | 0.155904E+10 | 0.00 | 0.78 |
| November | 0.343231E+10 | 0.00 | 0.00 | 280137.62 | 0.00 | 0.188883E+09 | 0.330575E+09 | 0.00 | 0.68 |
| December | 0.325147E+10 | 0.00 | 0.00 | 2617.68 | 0.00 | 0.880845E+09 | 17808599.83 | 0.00 | 0.62 |
| Annual Sum or Average | 0.285873E+11 | 23455507.47 | 18743.84 | 18326223.28 | 17075547.05 | 0.235887E+10 | 0.118184E+11 | 772.94 | 0.85 |
| Minimum of Months | 0.104583E+10 | 0.00 | 0.00 | 2617.68 | 0.00 | 734849.06 | 17808599.83 | 0.00 | 0.62 |
| Maximum of Months | 0.412941E+10 | 13192473.80 | 18743.84 | 4043387.88 | 8356157.17 | 0.880845E+09 | 0.271682E+10 | 772.94 | 1.19 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.187733E+11 | 0.00 | 0.00 | 579172.55 | 0.00 | 0.996436E+09 | 0.182993E+10 | 0.00 | 0.65 |
| February | 0.152583E+11 | 0.00 | 0.00 | 1387950.82 | 0.00 | 0.203029E+09 | 0.319640E+10 | 0.00 | 0.65 |
| March | 0.177609E+11 | 0.00 | 0.00 | 1095109.29 | 0.00 | 0.149317E+09 | 0.346703E+10 | 0.00 | 0.71 |
| April | 0.628582E+10 | 0.00 | 0.00 | 18595185.70 | 400915.19 | 12340059.59 | 0.127674E+11 | 0.00 | 0.83 |
| May | 0.636460E+10 | 0.00 | 0.00 | 22194713.16 | 24892.34 | 4920532.52 | 0.144201E+11 | 0.00 | 0.93 |
| June | 0.698019E+10 | 32701961.55 | 0.00 | 16947506.09 | 40279487.61 | 0.00 | 0.103582E+11 | 0.00 | 1.18 |
| July | 0.809213E+10 | 35186096.98 | 91462.06 | 335899.76 | 61217501.47 | 11517539.48 | 0.390359E+09 | 2615.40 | 0.98 |
| August | 0.703266E+10 | 3962983.20 | 0.00 | 798463.14 | 10770145.82 | 12290489.68 | 0.453293E+09 | 0.00 | 1.11 |
| September | 0.432164E+10 | 0.00 | 0.00 | 20757127.72 | 1578310.28 | 591769.11 | 0.101369E+11 | 0.00 | 1.10 |
| October | 0.795562E+10 | 0.00 | 0.00 | 12572642.54 | 0.00 | 20217633.21 | 0.107566E+11 | 0.00 | 0.79 |
| November | 0.143387E+11 | 0.00 | 0.00 | 2935348.82 | 0.00 | 0.123088E+09 | 0.461108E+10 | 0.00 | 0.68 |
| December | 0.187864E+11 | 0.00 | 0.00 | 175927.90 | 0.00 | 0.384977E+09 | 0.819080E+09 | 0.00 | 0.62 |
| Annual Sum or Average | 0.131950E+12 | 71851041.73 | 91462.06 | 98375047.50 | 0.114271E+09 | 0.191873E+10 | 0.732063E+11 | 2615.40 | 0.85 |
| Minimum of Months | 0.432164E+10 | 0.00 | 0.00 | 175927.90 | 0.00 | 0.00 | 0.390359E+09 | 0.00 | 0.62 |
| Maximum of Months | 0.187864E+11 | 35186096.98 | 91462.06 | 22194713.16 | 61217501.47 | 0.996436E+09 | 0.144201E+11 | 2615.40 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.132677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128253E+10 | 0.00 | 0.00 | 0.20 |
| February | 0.170527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512797E+09 | 0.00 | 0.00 | 0.19 |
| March | 0.231409E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218972E+09 | 0.00 | 0.00 | 0.21 |
| April | 0.132149E+10 | 0.00 | 0.00 | 1614697.86 | 47322.29 | 1747431.78 | 0.899446E+09 | 0.00 | 0.24 |
| May | 0.111457E+10 | 0.00 | 0.00 | 2923555.36 | 2938.18 | 0.00 | 0.156441E+10 | 0.00 | 0.31 |
| June | 0.675811E+09 | 7567990.18 | 0.00 | 3757151.66 | 4754416.01 | 0.00 | 0.173729E+10 | 0.00 | 0.43 |
| July | 0.943351E+09 | 5773349.12 | 0.00 | 193194.93 | 5660858.85 | 0.00 | 61775085.88 | 0.00 | 0.29 |
| August | 0.871459E+09 | 238898.72 | 0.00 | 59497.20 | 1500559.35 | 0.00 | 13606659.12 | 0.00 | 0.33 |
| September | 0.683131E+09 | 0.00 | 0.00 | 2612739.86 | 186296.90 | 0.00 | 0.110952E+10 | 0.00 | 0.35 |
| October | 0.175232E+10 | 0.00 | 0.00 | 598873.71 | 0.00 | 3246391.81 | 0.363465E+09 | 0.00 | 0.22 |
| November | 0.197010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283241E+09 | 0.00 | 0.00 | 0.20 |
| December | 0.123348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116246E+10 | 0.00 | 0.00 | 0.18 |
| Annual Sum or Average | 0.159118E+11 | 13580238.03 | 0.00 | 11759710.58 | 12152391.59 | 0.346500E+10 | 0.574951E+10 | 0.00 | 0.26 |
| Minimum of Months | 0.675811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
| Maximum of Months | 0.231409E+10 | 7567990.18 | 0.00 | 3757151.66 | 5660858.85 | 0.128253E+10 | 0.173729E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.316760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131026E+10 | 0.00 | 0.00 | 0.65 |
| February | 0.321577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.652507E+09 | 0.00 | 0.00 | 0.65 |
| March | 0.413646E+10 | 0.00 | 0.00 | 32.83 | 0.00 | 0.292908E+09 | 2727951.18 | 0.00 | 0.70 |
| April | 0.224183E+10 | 0.00 | 0.00 | 1153638.94 | 83123.58 | 22551522.61 | 0.134980E+10 | 0.00 | 0.75 |
| May | 0.192675E+10 | 0.00 | 0.00 | 2454052.92 | 5161.04 | 5239371.54 | 0.206531E+10 | 0.00 | 0.85 |
| June | 0.172448E+10 | 7472938.96 | 0.00 | 2702073.56 | 8351330.38 | 705792.18 | 0.173308E+10 | 0.00 | 1.13 |
| July | 0.173233E+10 | 7231095.48 | 17433.17 | 16103.51 | 12756703.47 | 5008050.54 | 23757302.08 | 2072.34 | 0.98 |
| August | 0.154630E+10 | 40104.66 | 0.00 | 4460.86 | 3014582.36 | 7443300.24 | 1012870.93 | 0.00 | 1.10 |
| September | 0.160713E+10 | 0.00 | 0.00 | 1745026.73 | 327238.29 | 3417706.37 | 0.102515E+10 | 0.00 | 0.95 |
| October | 0.286173E+10 | 0.00 | 0.00 | 394937.13 | 0.00 | 29490419.67 | 0.731375E+09 | 0.00 | 0.72 |
| November | 0.352776E+10 | 0.00 | 0.00 | 10298.78 | 0.00 | 0.361833E+09 | 56838772.27 | 0.00 | 0.68 |
| December | 0.294759E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119659E+10 | 0.00 | 0.00 | 0.62 |
| Annual Sum or Average | 0.306357E+11 | 14744139.10 | 17433.17 | 8480625.26 | 24538139.12 | 0.388795E+10 | 0.698905E+10 | 2072.34 | 0.82 |
| Minimum of Months | 0.154630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 705792.18 | 0.00 | 0.00 | 0.62 |
| Maximum of Months | 0.413646E+10 | 7472938.96 | 17433.17 | 2702073.56 | 12756703.47 | 0.131026E+10 | 0.206531E+10 | 2072.34 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.122913E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195120E+10 | 0.00 | 0.00 | 0.65 |
| February | 0.120207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282910E+09 | 0.00 | 0.00 | 0.65 |
| March | 0.130389E+11 | 0.00 | 0.00 | 128457.05 | 0.00 | 0.164086E+09 | 0.893804E+09 | 0.00 | 0.71 |
| April | 0.582068E+10 | 0.00 | 0.00 | 5643051.79 | 264387.06 | 16812571.32 | 0.570935E+10 | 0.00 | 0.76 |
| May | 0.511917E+10 | 0.00 | 0.00 | 9649226.64 | 16415.47 | 7823908.28 | 0.765436E+10 | 0.00 | 0.86 |
| June | 0.533051E+10 | 19486016.95 | 0.00 | 8213642.41 | 26562663.36 | 0.00 | 0.574850E+10 | 0.00 | 1.13 |
| July | 0.558919E+10 | 0.00 | 55755.73 | 0.00 | 63574203.24 | 12301949.08 | 0.00 | 6284.47 | 0.98 |
| August | 0.492698E+10 | 0.00 | 0.00 | 0.00 | 9715891.88 | 18156972.56 | 0.00 | 0.00 | 1.10 |
| September | 0.514531E+10 | 0.00 | 0.00 | 5330232.09 | 1040830.63 | 3612658.36 | 0.328409E+10 | 0.00 | 0.96 |
| October | 0.736850E+10 | 0.00 | 0.00 | 2557044.87 | 0.00 | 23560844.55 | 0.412630E+10 | 0.00 | 0.73 |
| November | 0.114511E+11 | 0.00 | 0.00 | 217525.29 | 0.00 | 0.140623E+09 | 0.960317E+09 | 0.00 | 0.68 |
| December | 0.122491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932153E+09 | 0.00 | 0.00 | 0.62 |
| Annual Sum or Average | 0.100351E+12 | 19486016.95 | 55755.73 | 31739180.13 | 0.101174E+09 | 0.355324E+10 | 0.283767E+11 | 6284.47 | 0.82 |
| Minimum of Months | 0.492698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
| Maximum of Months | 0.130389E+11 | 19486016.95 | 55755.73 | 9649226.64 | 63574203.24 | 0.195120E+10 | 0.765436E+10 | 6284.47 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.663955E+10 | 0.00 | 0.00 | 121570.29 | 0.00 | 0.218810E+09 | 0.469371E+09 | 0.00 | 0.65 |
| February | 0.547441E+10 | 0.00 | 0.00 | 162055.06 | 0.00 | 77575362.95 | 0.778140E+09 | 0.00 | 0.65 |
| March | 0.467256E+10 | 0.00 | 0.00 | 1215678.86 | 0.00 | 37209515.10 | 0.254198E+10 | 0.00 | 0.71 |
| April | 0.926796E+09 | 0.00 | 0.00 | 8749430.89 | 136028.62 | 2824980.11 | 0.548158E+10 | 0.00 | 0.82 |
| May | 0.744520E+09 | 0.00 | 0.00 | 12134588.97 | 8445.85 | 0.00 | 0.655669E+10 | 0.00 | 0.96 |
| June | 0.102657E+10 | 14109069.65 | 0.00 | 13465172.46 | 13666638.41 | 0.00 | 0.575954E+10 | 0.00 | 1.38 |
| July | 0.221093E+10 | 22237179.18 | 0.00 | 665717.80 | 10504022.91 | 1437399.36 | 0.668966E+09 | 0.00 | 0.98 |
| August | 0.230253E+10 | 2284623.05 | 0.00 | 243938.78 | 2714257.49 | 3807011.62 | 0.237723E+09 | 0.00 | 1.11 |
| September | 0.742173E+09 | 0.00 | 0.00 | 10057804.12 | 535513.16 | 194359.34 | 0.417002E+10 | 0.00 | 1.12 |
| October | 0.138278E+10 | 0.00 | 0.00 | 5690831.04 | 0.00 | 4838811.45 | 0.469957E+10 | 0.00 | 0.75 |
| November | 0.429213E+10 | 0.00 | 0.00 | 1346494.70 | 0.00 | 43931408.94 | 0.212237E+10 | 0.00 | 0.68 |
| December | 0.647010E+10 | 0.00 | 0.00 | 23836.78 | 0.00 | 0.104484E+09 | 0.207195E+09 | 0.00 | 0.62 |
| Annual Sum or Average | 0.368850E+11 | 38630871.87 | 0.00 | 53877119.75 | 27564906.45 | 0.495113E+09 | 0.336931E+11 | 0.00 | 0.87 |
| Minimum of Months | 0.742173E+09 | 0.00 | 0.00 | 23836.78 | 0.00 | 0.00 | 0.207195E+09 | 0.00 | 0.62 |
| Maximum of Months | 0.663955E+10 | 22237179.18 | 0.00 | 13465172.46 | 13666638.41 | 0.218810E+09 | 0.655669E+10 | 0.00 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.194973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356809E+10 | 0.00 | 0.00 | 0.15 |
| February | 0.299576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162089E+10 | 0.00 | 0.00 | 0.14 |
| March | 0.466930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.607921E+09 | 0.00 | 0.00 | 0.15 |
| April | 0.239484E+10 | 0.00 | 0.00 | 4637195.56 | 98555.76 | 1476343.01 | 0.257896E+10 | 0.00 | 0.19 |
| May | 0.117961E+10 | 0.00 | 0.00 | 10756282.81 | 6119.21 | 0.00 | 0.554895E+10 | 0.00 | 0.27 |
| June | 0.756264E+09 | 20365912.25 | 0.00 | 14197820.79 | 9901783.85 | 0.00 | 0.588141E+10 | 0.00 | 0.42 |
| July | 0.100213E+10 | 32208723.09 | 0.00 | 5265926.09 | 6311758.41 | 0.00 | 0.144044E+10 | 0.00 | 0.26 |
| August | 0.127629E+10 | 3610348.03 | 0.00 | 3031071.19 | 665576.79 | 0.00 | 0.641475E+09 | 0.00 | 0.26 |
| September | 0.105980E+10 | 0.00 | 0.00 | 7043866.38 | 387991.21 | 0.00 | 0.296949E+10 | 0.00 | 0.28 |
| October | 0.367488E+10 | 0.00 | 0.00 | 1136176.17 | 0.00 | 7736378.32 | 0.721139E+09 | 0.00 | 0.16 |
| November | 0.383323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.863788E+09 | 0.00 | 0.00 | 0.15 |
| December | 0.174062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323240E+10 | 0.00 | 0.00 | 0.13 |
| Annual Sum or Average | 0.265325E+11 | 56184983.36 | 0.00 | 46068338.99 | 17371785.22 | 0.990230E+10 | 0.197819E+11 | 0.00 | 0.21 |
| Minimum of Months | 0.756264E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.13 |
| Maximum of Months | 0.466930E+10 | 32208723.09 | 0.00 | 14197820.79 | 9901783.85 | 0.356809E+10 | 0.588141E+10 | 0.00 | 0.42 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 59583161.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492190E+10 | 0.00 | 0.00 | 0.41 |
| February | 60031354.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416863E+10 | 0.00 | 0.00 | 0.41 |
| March | 0.255479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.449067E+10 | 0.00 | 0.00 | 0.43 |
| April | 0.105534E+10 | 0.00 | 0.00 | 29552.56 | 63084.60 | 0.204507E+10 | 28861789.41 | 0.00 | 0.37 |
| May | 0.129195E+10 | 0.00 | 0.00 | 260784.28 | 3916.85 | 0.191574E+10 | 97994357.53 | 0.00 | 0.40 |
| June | 0.172708E+10 | 10089562.54 | 0.00 | 567840.32 | 6368385.67 | 0.891897E+09 | 0.139023E+09 | 0.00 | 0.53 |
| July | 0.946917E+09 | 20934339.26 | 10705.23 | 63473.76 | 4589326.48 | 0.468264E+09 | 18042352.58 | 4097.99 | 0.46 |
| August | 0.887767E+09 | 1383229.39 | 0.00 | 205121.89 | 1150716.52 | 0.364249E+09 | 24280961.30 | 0.00 | 0.52 |
| September | 0.127984E+10 | 0.00 | 0.00 | 876129.35 | 248349.47 | 0.637277E+09 | 0.283251E+09 | 0.00 | 0.46 |
| October | 0.992342E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219471E+10 | 0.00 | 0.00 | 0.36 |
| November | 0.289597E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376257E+10 | 0.00 | 0.00 | 0.39 |
| December | 58299217.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467267E+10 | 0.00 | 0.00 | 0.40 |
| Annual Sum or Average | 0.890423E+10 | 32407131.19 | 10705.23 | 2002902.17 | 12423779.60 | 0.305336E+11 | 0.591453E+09 | 4097.99 | 0.43 |
| Minimum of Months | 58299217.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364249E+09 | 0.00 | 0.00 | 0.36 |
| Maximum of Months | 0.172708E+10 | 20934339.26 | 10705.23 | 876129.35 | 6368385.67 | 0.492190E+10 | 0.283251E+09 | 4097.99 | 0.53 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.389177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
| February | 0.336197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
| March | 0.385200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
| April | 0.211808E+10 | 0.00 | 0.00 | 1955001.38 | 72243.90 | 0.00 | 0.105307E+10 | 0.00 | 0.26 |
| May | 0.144504E+10 | 0.00 | 0.00 | 4435492.10 | 4485.54 | 0.00 | 0.215898E+10 | 0.00 | 0.31 |
| June | 0.681524E+09 | 10543708.97 | 0.00 | 7492133.95 | 5420557.84 | 0.00 | 0.257723E+10 | 0.00 | 0.43 |
| July | 0.148787E+10 | 1436719.77 | 0.00 | 410864.82 | 16050773.18 | 0.00 | 54699665.37 | 0.00 | 0.34 |
| August | 0.134391E+10 | 0.00 | 0.00 | 190842.74 | 2654872.53 | 0.00 | 11989101.05 | 0.00 | 0.38 |
| September | 0.102034E+10 | 0.00 | 0.00 | 3470470.27 | 284407.51 | 0.00 | 0.130858E+10 | 0.00 | 0.34 |
| October | 0.290838E+10 | 0.00 | 0.00 | 156609.63 | 0.00 | 0.00 | 0.238578E+09 | 0.00 | 0.25 |
| November | 0.342991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
| December | 0.360177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
| Annual Sum or Average | 0.291426E+11 | 11980428.73 | 0.00 | 18111414.90 | 24487340.50 | 0.00 | 0.740312E+10 | 0.00 | 0.29 |
| Minimum of Months | 0.681524E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
| Maximum of Months | 0.389177E+10 | 10543708.97 | 0.00 | 7492133.95 | 16050773.18 | 0.00 | 0.257723E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.245534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15555882.54 | 0.00 | 0.00 | 0.19 |
| February | 0.213452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
| March | 0.244565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.20 |
| April | 0.198048E+10 | 0.00 | 0.00 | 17.93 | 45867.84 | 0.00 | 524475.34 | 0.00 | 0.21 |
| May | 0.204975E+10 | 0.00 | 0.00 | 121588.04 | 2847.88 | 0.00 | 96834261.72 | 0.00 | 0.24 |
| June | 0.172315E+10 | 4542001.80 | 0.00 | 296146.89 | 4019373.45 | 0.00 | 0.120287E+09 | 0.00 | 0.32 |
| July | 0.971402E+09 | 56412.59 | 0.00 | 23551.30 | 11002807.17 | 0.00 | 663425.99 | 0.00 | 0.28 |
| August | 0.857920E+09 | 0.00 | 0.00 | 0.00 | 1685585.37 | 0.00 | 0.00 | 0.00 | 0.32 |
| September | 0.142676E+10 | 0.00 | 0.00 | 0.00 | 180571.06 | 0.00 | 0.00 | 0.00 | 0.27 |
| October | 0.199811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
| November | 0.217766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
| December | 0.228677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
| Annual Sum or Average | 0.225075E+11 | 4598414.39 | 0.00 | 441304.16 | 16937052.77 | 15555882.54 | 0.218309E+09 | 0.00 | 0.23 |
| Minimum of Months | 0.857920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
| Maximum of Months | 0.245534E+10 | 4542001.80 | 0.00 | 296146.89 | 11002807.17 | 15555882.54 | 0.120287E+09 | 0.00 | 0.32 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.447032E+10 | 0.00 | 0.00 | 19583.28 | 0.00 | 0.225226E+10 | 3775551.46 | 0.00 | 0.22 |
| February | 0.538596E+10 | 0.00 | 0.00 | 47132.90 | 0.00 | 0.365630E+09 | 15204893.78 | 0.00 | 0.22 |
| March | 0.635616E+10 | 0.00 | 0.00 | 222382.24 | 0.00 | 0.145144E+09 | 64162338.99 | 0.00 | 0.24 |
| April | 0.174071E+10 | 0.00 | 0.00 | 13260824.55 | 145706.85 | 546909.09 | 0.643242E+10 | 0.00 | 0.39 |
| May | 0.131304E+10 | 0.00 | 0.00 | 18485770.92 | 9046.76 | 0.00 | 0.853469E+10 | 0.00 | 0.49 |
| June | 0.105358E+10 | 27569936.61 | 0.00 | 21696254.93 | 13387741.02 | 0.00 | 0.836224E+10 | 0.00 | 0.73 |
| July | 0.938731E+09 | 53920261.95 | 0.00 | 10435063.69 | 5647834.66 | 0.00 | 0.280547E+10 | 0.00 | 0.51 |
| August | 0.100935E+10 | 8979575.92 | 0.00 | 10995759.37 | 0.00 | 0.00 | 0.219754E+10 | 0.00 | 0.55 |
| September | 0.656009E+09 | 0.00 | 0.00 | 19029952.61 | 573614.12 | 0.00 | 0.677668E+10 | 0.00 | 0.65 |
| October | 0.328063E+10 | 0.00 | 0.00 | 6013997.23 | 0.00 | 4272321.06 | 0.331874E+10 | 0.00 | 0.31 |
| November | 0.544823E+10 | 0.00 | 0.00 | 463971.00 | 0.00 | 0.216830E+09 | 0.230410E+09 | 0.00 | 0.23 |
| December | 0.431840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189949E+10 | 0.00 | 0.00 | 0.21 |
| Annual Sum or Average | 0.359711E+11 | 90469774.48 | 0.00 | 0.100671E+09 | 19763943.40 | 0.488417E+10 | 0.387413E+11 | 0.00 | 0.40 |
| Minimum of Months | 0.656009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
| Maximum of Months | 0.635616E+10 | 53920261.95 | 0.00 | 21696254.93 | 13387741.02 | 0.225226E+10 | 0.853469E+10 | 0.00 | 0.73 |
Report: MechanicalVentilationLoadsMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.124617E+11 | 0.00 | 0.00 | 2494.56 | 0.00 | 0.603839E+09 | 27151899.78 | 0.00 | 0.53 |
| February | 0.109900E+11 | 0.00 | 0.00 | 18231.42 | 0.00 | 0.179545E+09 | 0.136876E+09 | 0.00 | 0.53 |
| March | 0.104080E+11 | 0.00 | 0.00 | 1361205.31 | 0.00 | 63152086.58 | 0.248179E+10 | 0.00 | 0.57 |
| April | 0.200955E+10 | 0.00 | 0.00 | 18322601.18 | 242929.46 | 0.00 | 0.104839E+11 | 0.00 | 0.74 |
| May | 0.139032E+10 | 0.00 | 0.00 | 25762554.95 | 15083.20 | 0.00 | 0.134870E+11 | 0.00 | 0.91 |
| June | 0.160872E+10 | 35878092.66 | 0.00 | 28878983.01 | 22643047.35 | 0.00 | 0.119202E+11 | 0.00 | 1.27 |
| July | 0.108288E+10 | 67970388.59 | 0.00 | 15529496.52 | 9301851.40 | 0.00 | 0.460906E+10 | 0.00 | 0.92 |
| August | 0.148697E+10 | 11510584.78 | 0.00 | 13455229.53 | 0.00 | 0.00 | 0.331233E+10 | 0.00 | 0.98 |
| September | 0.128448E+10 | 0.00 | 0.00 | 20354868.51 | 956357.04 | 0.00 | 0.822836E+10 | 0.00 | 0.99 |
| October | 0.549017E+10 | 0.00 | 0.00 | 6447016.63 | 0.00 | 0.00 | 0.534645E+10 | 0.00 | 0.61 |
| November | 0.101549E+11 | 0.00 | 0.00 | 378459.73 | 0.00 | 0.129883E+09 | 0.124926E+10 | 0.00 | 0.55 |
| December | 0.117810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334103E+09 | 0.00 | 0.00 | 0.50 |
| Annual Sum or Average | 0.701487E+11 | 0.115359E+09 | 0.00 | 0.130511E+09 | 33159268.44 | 0.131052E+10 | 0.612824E+11 | 0.00 | 0.76 |
| Minimum of Months | 0.108288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 |
| Maximum of Months | 0.124617E+11 | 67970388.59 | 0.00 | 28878983.01 | 22643047.35 | 0.603839E+09 | 0.134870E+11 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 25730539.94 | 0.00 | 0.00 | 31985443.59 | 0.00 | 0.00 | 0.198877E+11 | 0.00 | 1.16 |
| February | 4507.05 | 0.00 | 0.00 | 31942196.45 | 0.00 | 0.00 | 0.186711E+11 | 0.00 | 1.24 |
| March | 54724.18 | 0.00 | 0.00 | 40841060.88 | 0.00 | 0.00 | 0.235018E+11 | 0.00 | 1.53 |
| April | 0.00 | 0.00 | 0.00 | 46425293.38 | 0.00 | 0.00 | 0.242047E+11 | 0.00 | 2.25 |
| May | 86140.51 | 0.00 | 0.00 | 52805349.32 | 0.00 | 0.00 | 0.261788E+11 | 0.00 | 2.57 |
| June | 0.00 | 7917248.31 | 0.00 | 51917400.09 | 0.00 | 0.00 | 0.231853E+11 | 0.00 | 3.19 |
| July | 0.00 | 14067605.09 | 0.00 | 42561411.18 | 0.00 | 0.00 | 0.198311E+11 | 0.00 | 3.22 |
| August | 162300.89 | 0.00 | 0.00 | 43033716.01 | 0.00 | 0.00 | 0.203659E+11 | 0.00 | 3.66 |
| September | 0.00 | 0.00 | 0.00 | 45208385.84 | 0.00 | 0.00 | 0.208765E+11 | 0.00 | 3.08 |
| October | 38008.87 | 0.00 | 0.00 | 42860783.20 | 0.00 | 0.00 | 0.235703E+11 | 0.00 | 2.09 |
| November | 0.00 | 0.00 | 0.00 | 37219878.02 | 0.00 | 0.00 | 0.212537E+11 | 0.00 | 1.51 |
| December | 25666944.29 | 0.00 | 0.00 | 30955282.26 | 0.00 | 0.00 | 0.188645E+11 | 0.00 | 1.09 |
| Annual Sum or Average | 51743165.73 | 21984853.40 | 0.00 | 0.497756E+09 | 0.00 | 0.00 | 0.260392E+12 | 0.00 | 2.22 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 30955282.26 | 0.00 | 0.00 | 0.186711E+11 | 0.00 | 1.09 |
| Maximum of Months | 25730539.94 | 14067605.09 | 0.00 | 52805349.32 | 0.00 | 0.00 | 0.261788E+11 | 0.00 | 3.66 |
Report: MechanicalVentilationLoadsMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.181197E+11 | 0.00 | 0.00 | 4071329.64 | 0.00 | 0.357306E+10 | 0.159475E+11 | 0.00 | 1.60 |
| February | 0.166700E+11 | 0.00 | 0.00 | 3535152.83 | 0.00 | 0.115717E+10 | 0.140106E+11 | 0.00 | 1.60 |
| March | 0.176950E+11 | 0.00 | 0.00 | 6861461.40 | 0.00 | 0.563368E+09 | 0.181379E+11 | 0.00 | 1.73 |
| April | 0.100947E+11 | 0.00 | 0.00 | 15836873.24 | 0.00 | 20529617.19 | 0.190377E+11 | 0.00 | 1.69 |
| May | 0.993634E+10 | 0.00 | 0.00 | 21131132.15 | 0.00 | 12801056.46 | 0.217179E+11 | 0.00 | 1.89 |
| June | 0.328768E+10 | 16260734.79 | 0.00 | 30665897.01 | 0.00 | 1095653.42 | 0.250177E+11 | 0.00 | 2.28 |
| July | 0.556198E+10 | 57932076.26 | 0.00 | 8221494.70 | 0.00 | 0.00 | 0.781345E+10 | 0.00 | 1.78 |
| August | 0.430302E+10 | 880771.13 | 0.00 | 9390265.82 | 0.00 | 0.00 | 0.996174E+10 | 0.00 | 2.07 |
| September | 0.333121E+10 | 0.00 | 0.00 | 24721717.97 | 0.00 | 2787156.55 | 0.207506E+11 | 0.00 | 2.13 |
| October | 0.117045E+11 | 0.00 | 0.00 | 14649876.38 | 0.00 | 32945365.18 | 0.182526E+11 | 0.00 | 1.67 |
| November | 0.159584E+11 | 0.00 | 0.00 | 7358230.01 | 0.00 | 0.746168E+09 | 0.160643E+11 | 0.00 | 1.64 |
| December | 0.168214E+11 | 0.00 | 0.00 | 3001926.03 | 0.00 | 0.224132E+10 | 0.155081E+11 | 0.00 | 1.53 |
| Annual Sum or Average | 0.133484E+12 | 75073582.18 | 0.00 | 0.149445E+09 | 0.00 | 0.835125E+10 | 0.202220E+12 | 0.00 | 1.80 |
| Minimum of Months | 0.328768E+10 | 0.00 | 0.00 | 3001926.03 | 0.00 | 0.00 | 0.781345E+10 | 0.00 | 1.53 |
| Maximum of Months | 0.181197E+11 | 57932076.26 | 0.00 | 30665897.01 | 0.00 | 0.357306E+10 | 0.250177E+11 | 0.00 | 2.28 |
Report: MechanicalVentilationLoadsMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.685817E+10 | 0.00 | 0.00 | 70537.62 | 0.00 | 0.122006E+10 | 0.247917E+09 | 0.00 | 0.30 |
| February | 0.673484E+10 | 0.00 | 0.00 | 217160.12 | 0.00 | 96342937.17 | 0.351971E+09 | 0.00 | 0.30 |
| March | 0.604794E+10 | 0.00 | 0.00 | 3485999.68 | 0.00 | 35944088.68 | 0.229578E+10 | 0.00 | 0.33 |
| April | 0.987802E+09 | 0.00 | 0.00 | 17924686.30 | 154051.03 | 0.00 | 0.932547E+10 | 0.00 | 0.54 |
| May | 0.685795E+09 | 0.00 | 0.00 | 25024246.02 | 9564.84 | 0.00 | 0.119671E+11 | 0.00 | 0.68 |
| June | 0.105226E+10 | 28040028.60 | 0.00 | 26682690.29 | 14358838.35 | 0.00 | 0.104667E+11 | 0.00 | 0.96 |
| July | 0.940008E+09 | 50362026.35 | 0.00 | 9728803.10 | 6249113.46 | 0.00 | 0.286570E+10 | 0.00 | 0.56 |
| August | 0.123105E+10 | 7969722.79 | 0.00 | 8452015.66 | 0.00 | 0.00 | 0.190562E+10 | 0.00 | 0.58 |
| September | 0.660332E+09 | 0.00 | 0.00 | 19912393.21 | 606463.25 | 0.00 | 0.742509E+10 | 0.00 | 0.76 |
| October | 0.197013E+10 | 0.00 | 0.00 | 11320876.34 | 0.00 | 1109244.07 | 0.638158E+10 | 0.00 | 0.42 |
| November | 0.525105E+10 | 0.00 | 0.00 | 3562685.48 | 0.00 | 41121348.55 | 0.223598E+10 | 0.00 | 0.32 |
| December | 0.724838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452412E+09 | 0.00 | 0.00 | 0.29 |
| Annual Sum or Average | 0.396678E+11 | 86371777.74 | 0.00 | 0.126382E+09 | 21378030.94 | 0.184699E+10 | 0.554689E+11 | 0.00 | 0.50 |
| Minimum of Months | 0.660332E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
| Maximum of Months | 0.724838E+10 | 50362026.35 | 0.00 | 26682690.29 | 14358838.35 | 0.122006E+10 | 0.119671E+11 | 0.00 | 0.96 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:27:52
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.173856E+12 | 0.123993E+11 | 0.153685E+12 | 0.366244E+12 | 0.586041E+11 |
| February | 0.317884E+12 | 0.125564E+11 | 0.139271E+12 | 0.336180E+12 | 0.440237E+11 |
| March | 0.438560E+12 | 0.121162E+11 | 0.168237E+12 | 0.399970E+12 | 0.440513E+11 |
| April | 0.122756E+13 | 0.106329E+11 | 0.151378E+12 | 0.528232E+12 | 0.377975E+11 |
| May | 0.149182E+13 | 0.162803E+11 | 0.145778E+12 | 0.566263E+12 | 0.496286E+11 |
| June | 0.152682E+13 | 0.117480E+11 | 0.108324E+12 | 0.527655E+12 | 0.995227E+11 |
| July | 0.154067E+13 | 0.906883E+10 | 0.999336E+11 | 0.434595E+12 | 0.110409E+12 |
| August | 0.124208E+13 | 0.724545E+10 | 0.939612E+11 | 0.413699E+12 | 0.133253E+12 |
| September | 0.888744E+12 | 0.995807E+10 | 0.117840E+12 | 0.568817E+12 | 0.941805E+11 |
| October | 0.360490E+12 | 0.123290E+11 | 0.176290E+12 | 0.495114E+12 | 0.296748E+11 |
| November | 0.106312E+12 | 0.150088E+11 | 0.188093E+12 | 0.401096E+12 | 0.395215E+11 |
| December | -0.882437E+10 | 0.167065E+11 | 0.171993E+12 | 0.306660E+12 | 0.536656E+11 |
| Annual Sum or Average | 0.930597E+13 | 0.146050E+12 | 0.171478E+13 | 0.534453E+13 | 0.794333E+12 |
| Minimum of Months | -0.882437E+10 | 0.724545E+10 | 0.939612E+11 | 0.306660E+12 | 0.296748E+11 |
| Maximum of Months | 0.154067E+13 | 0.167065E+11 | 0.188093E+12 | 0.568817E+12 | 0.133253E+12 |