Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:30
Tabular Output Report in Format: HTML
Building: SchoolPrimary
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2024-07-03 12:30:24
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 4116.41 | 599.10 | 599.10 |
| Net Site Energy | 4116.41 | 599.10 | 599.10 |
| Total Source Energy | 10747.24 | 1564.14 | 1564.14 |
| Net Source Energy | 10747.24 | 1564.14 | 1564.14 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 6871.00 |
| Net Conditioned Building Area | 6871.00 |
| Unconditioned Building Area | 0.00 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 583.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 157.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 1218.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 92.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1151.36 | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 334.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 154.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.47 |
| Refrigeration | 44.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 3017.31 | 1099.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.47 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 321.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Boiler | 0.00 | 261.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Cooling | General | 157.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 1218.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 92.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooking | 149.71 | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInFreezer | 31.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInRefrigerator | 23.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | Transformer | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | General | 334.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | General | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Heater | 0.00 | 154.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.99 | |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.48 | |
| Refrigeration | General | 7.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LowTempRefrigeration | 15.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MedTempRefrigeration | 21.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 583.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 157.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 1218.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 92.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 1151.36 | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 334.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 0.00 | 154.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.47 |
| Refrigeration | Unassigned | 44.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 190.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 71.71 | 107.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Other | 176.67 | 52.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 439.14 | 159.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 190.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 71.71 | 107.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Other | 176.67 | 52.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 439.14 | 159.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 3017.308 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 3017.308 | 100.00 |
| Total On-Site and Utility Electric Sources | 3017.308 | 100.00 |
| Total Electricity End Uses | 3017.308 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | |
| Air to Air Heat Recovery for Cooling | 0.00 | |
| Air to Air Heat Recovery for Heating | 0.00 | |
| High-Temperature Geothermal* | 0.00 | |
| Solar Water Thermal | 0.00 | |
| Solar Air Thermal | 0.00 | |
| Total On-Site Thermal Sources | 0.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 718.47 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 718.47 | 100.00 |
| Total Water End Uses | 718.47 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 627.83 |
| Time Setpoint Not Met During Occupied Cooling | 12.00 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1149.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME SCHOOLPRIMARY
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |ZoneHeatingSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |ZoneElectricSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |SpaceGainsMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |PeakSpaceGainsMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |SpaceGainComponentsAtCoolingPeakMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |ComfortReportSimple55Monthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |OccupantComfortDataSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_POD_1 COOLING COIL | PSZ-AC_1:6 COOLING COIL | PSZ-AC_2:7 COOLING COIL |WindowReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 |WindowEnergyReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 |WindowZoneSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |WindowEnergyZoneSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | VAV_POD_1 HEATING COIL | PSZ-AC_1:6 HEATING COIL | PSZ-AC_2:7 HEATING COIL | VAV_POD_1 COOLING COIL | PSZ-AC_1:6 COOLING COIL | PSZ-AC_2:7 COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| VAV_POD_1 FAN | BATH_ZN_1_FLR_1 EXHAUST FAN | GYM_ZN_1_FLR_1 EXHAUST FAN | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN | KITCHEN_ZN_1_FLR_1 EXHAUST FAN | CAFETERIA_ZN_1_FLR_1 EXHAUST FAN | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_POD_1 | PSZ-AC_1:6 | PSZ-AC_2:7 |AirLoopSystemComponentLoadsMonthly
| VAV_POD_1 | PSZ-AC_1:6 | PSZ-AC_2:7 |AirLoopSystemComponentEnergyUseMonthly
| VAV_POD_1 | PSZ-AC_1:6 | PSZ-AC_2:7 |MechanicalVentilationLoadsMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:30 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
| Latitude [deg] | 47.47 |
| Longitude [deg] | -122.3 |
| Elevation [m] | 122.00 |
| Time Zone | -8.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Above Ground Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Window Opening Area [m2] | 552.60 | 204.13 | 72.16 | 204.16 | 72.16 |
| Gross Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Above Ground Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Above Ground Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Window Opening Area [m2] | 552.60 | 204.13 | 72.16 | 204.16 | 72.16 |
| Gross Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Above Ground Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Total | |
| Gross Roof Area [m2] | 6871.00 |
| Skylight Area [m2] | 13.38 |
| Skylight-Roof Ratio [%] | 0.19 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | Yes | Yes | 768.00 | 1.00 | 12.00 | 0.00 | 2.64 | 2.64 | 5.4810 | 18.58 | 4.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | Yes | Yes | 768.00 | 1.00 | 12.00 | 0.00 | 2.64 | 2.64 | 5.4810 | 18.58 | 4.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | Yes | Yes | 768.00 | 1.00 | 12.00 | 0.00 | 2.64 | 2.64 | 5.4810 | 18.58 | 4.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.57 | 17.57 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1260.00 | 1.00 | 140.00 | 0.00 | 30.80 | 30.80 | 15.0695 | 3.72 | 15.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | Yes | Yes | 648.00 | 1.00 | 72.00 | 0.00 | 15.84 | 15.84 | 15.0695 | 3.72 | 20.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | Yes | Yes | 2184.00 | 1.00 | 36.00 | 0.00 | 7.92 | 7.92 | 5.4810 | 18.58 | 4.0000 |
| LOBBY_ZN_1_FLR_1 | 171.00 | Yes | Yes | 684.00 | 1.00 | 76.00 | 0.00 | 16.72 | 16.72 | 13.9931 | 9.29 | 4.0000 |
| MECH_ZN_1_FLR_1 | 252.00 | Yes | Yes | 1008.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.1458 | 61.93 | 10.0000 |
| BATH_ZN_1_FLR_1 | 190.00 | Yes | Yes | 760.00 | 1.00 | 40.00 | 0.00 | 8.80 | 8.80 | 9.6875 | 18.58 | 4.0000 |
| OFFICES_ZN_1_FLR_1 | 441.00 | Yes | Yes | 1764.00 | 1.00 | 168.00 | 0.00 | 36.96 | 36.96 | 11.8403 | 18.58 | 10.8000 |
| GYM_ZN_1_FLR_1 | 357.00 | Yes | Yes | 1428.00 | 1.00 | 68.00 | 0.00 | 14.96 | 14.96 | 13.3472 | 3.10 | 5.0000 |
| KITCHEN_ZN_1_FLR_1 | 168.00 | Yes | Yes | 672.00 | 1.00 | 32.00 | 0.00 | 7.04 | 7.04 | 12.9167 | 6.22 | 1631.7643 |
| CAFETERIA_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1260.00 | 1.00 | 144.00 | 0.00 | 31.68 | 31.68 | 9.6875 | 0.93 | 25.3900 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | Yes | Yes | 1596.00 | 1.00 | 160.00 | 0.00 | 35.20 | 35.20 | 16.6840 | 9.29 | 15.0000 |
| Total | 6871.00 | 27484.00 | 2512.00 | 0.00 | 552.60 | 552.60 | 12.8652 | 4.37 | 51.7784 | |||
| Conditioned Total | 6871.00 | 27484.00 | 2512.00 | 0.00 | 552.60 | 552.60 | 12.8652 | 4.37 | 51.7784 | |||
| Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | Yes | Yes | 1.00 | CORRIDOR_POD_1_ZN_1_FLR_1 | GENERAL | CORRIDOR_POD_1_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | Yes | Yes | 1.00 | CORRIDOR_POD_2_ZN_1_FLR_1 | GENERAL | CORRIDOR_POD_2_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | Yes | Yes | 1.00 | CORRIDOR_POD_3_ZN_1_FLR_1 | GENERAL | CORRIDOR_POD_3_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | Yes | Yes | 1.00 | COMPUTER_CLASS_ZN_1_FLR_1 | GENERAL | COMPUTER_CLASS_ZN_1_FLR_1 | 15.0695 | 3.72 | 20.0000 | |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | Yes | Yes | 1.00 | MAIN_CORRIDOR_ZN_1_FLR_1 | GENERAL | MAIN_CORRIDOR_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| LOBBY_ZN_1_FLR_1 | 171.00 | Yes | Yes | 1.00 | LOBBY_ZN_1_FLR_1 | GENERAL | LOBBY_ZN_1_FLR_1 | 13.9931 | 9.29 | 4.0000 | |
| MECH_ZN_1_FLR_1 | 252.00 | Yes | Yes | 1.00 | MECH_ZN_1_FLR_1 | GENERAL | MECH_ZN_1_FLR_1 | 16.1458 | 61.93 | 10.0000 | |
| BATH_ZN_1_FLR_1 | 190.00 | Yes | Yes | 1.00 | BATH_ZN_1_FLR_1 | GENERAL | BATH_ZN_1_FLR_1 | 9.6875 | 18.58 | 4.0000 | |
| OFFICES_ZN_1_FLR_1 | 441.00 | Yes | Yes | 1.00 | OFFICES_ZN_1_FLR_1 | GENERAL | OFFICES_ZN_1_FLR_1 | 11.8403 | 18.58 | 10.8000 | |
| GYM_ZN_1_FLR_1 | 357.00 | Yes | Yes | 1.00 | GYM_ZN_1_FLR_1 | GENERAL | GYM_ZN_1_FLR_1 | 13.3472 | 3.10 | 5.0000 | |
| KITCHEN_ZN_1_FLR_1 | 168.00 | Yes | Yes | 1.00 | KITCHEN_ZN_1_FLR_1 | GENERAL | KITCHEN_ZN_1_FLR_1 | 12.9167 | 6.22 | 1631.7643 | |
| CAFETERIA_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1.00 | CAFETERIA_ZN_1_FLR_1 | GENERAL | CAFETERIA_ZN_1_FLR_1 | 9.6875 | 0.93 | 25.3900 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | Yes | Yes | 1.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | GENERAL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 16.6840 | 9.29 | 15.0000 | |
| Total | 6871.00 | 12.8652 | 2.19 | 51.7784 | |||||||
| Conditioned Total | 6871.00 | 12.8652 | 2.19 | 51.7784 | |||||||
| Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 6871.00 | 6871.00 | 0.00 | 0.00 | 12.8652 | 4.37 | 51.7784 |
| Total | 6871.00 | 6871.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 27-APR-13:00 | 26-DEC-08:09 | - | - | - | - | - | - | - | - | - | - | 02-JAN-13:09 |
| Heating | 0.00 | 494623.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 93623.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 79557.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 72814.64 | 36063.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 1213.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 50094.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 13.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 12143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 1388.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 298705.41 | 542830.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 221704.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Boiler | 0.00 | 272918.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Cooling | General | 93623.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 79557.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 65099.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooking | 5999.02 | 36063.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInFreezer | 986.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInRefrigerator | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | Transformer | 1213.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | General | 50094.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | General | 13.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Heater | 0.00 | 12143.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 241.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LowTempRefrigeration | 431.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MedTempRefrigeration | 715.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 632.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 498.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 3858.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 292.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 3646.35 | 391.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 55.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 1059.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 3.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 167.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 142.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 9555.81 | 1191.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 92.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 72.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 561.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 42.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 530.69 | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 8.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 154.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 24.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 20.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1390.75 | 173.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 92.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 72.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 561.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 42.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 530.69 | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 8.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 154.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 24.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 20.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1390.75 | 173.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
AirTerminal:SingleDuct:VAV:Reheat| Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 0.681316 | 0.110724 | 0.403000 | 0.274570 | 0.403000 | 0.500000 | 0.003441 | 0.000060 | 0.293602 | 12.89 | 0.008000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 2.86 | 0.127021 | 0.462000 | 1.32 | 0.462000 | 0.500000 | 0.003000 | 0.000221 | 1.32 | 12.89 | 0.008000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 0.528639 | 0.276756 | 0.300000 | 0.158592 | 0.738016 | 0.500000 | 0.001377 | 0.000054 | 0.263076 | 12.89 | 0.008000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 0.571542 | 0.131990 | 0.480000 | 0.274340 | 0.480000 | 0.500000 | 0.002887 | 0.000060 | 0.293529 | 12.89 | 0.008000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 2.23 | 0.163261 | 0.594000 | 1.32 | 0.594000 | 0.500000 | 0.002334 | 0.000220 | 1.32 | 12.89 | 0.008000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 0.677716 | 0.111312 | 0.405000 | 0.274475 | 0.405000 | 0.500000 | 0.003423 | 0.000059 | 0.291485 | 12.89 | 0.008000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 2.83 | 0.128359 | 0.467000 | 1.32 | 0.467000 | 0.500000 | 0.002968 | 0.000219 | 1.32 | 12.89 | 0.008000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 0.527083 | 0.277573 | 0.300000 | 0.158125 | 0.740194 | 0.500000 | 0.001373 | 0.000053 | 0.262346 | 12.89 | 0.008000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 0.571756 | 0.131941 | 0.480000 | 0.274443 | 0.480000 | 0.500000 | 0.002888 | 0.000060 | 0.293695 | 12.89 | 0.008000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 2.23 | 0.163197 | 0.593000 | 1.32 | 0.593000 | 0.500000 | 0.002335 | 0.000220 | 1.32 | 12.89 | 0.008000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 0.678162 | 0.111239 | 0.404000 | 0.273977 | 0.404000 | 0.500000 | 0.003425 | 0.000059 | 0.291717 | 12.89 | 0.008000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 2.84 | 0.127861 | 0.465000 | 1.32 | 0.465000 | 0.500000 | 0.002980 | 0.000219 | 1.32 | 12.89 | 0.008000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 0.531878 | 0.275070 | 0.300000 | 0.159564 | 0.733521 | 0.500000 | 0.001385 | 0.000053 | 0.262691 | 12.89 | 0.008000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 0.575041 | 0.131187 | 0.477000 | 0.274294 | 0.477000 | 0.500000 | 0.002904 | 0.000060 | 0.295324 | 12.89 | 0.008000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 1.49 | 0.160787 | 0.585000 | 0.873311 | 0.585000 | 0.500000 | 0.002370 | 0.000147 | 0.873311 | 12.89 | 0.008000 |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | 0.827351 | 0.149204 | 0.542000 | 0.448424 | 0.542000 | 0.500000 | 0.002554 | 0.000073 | 0.448424 | 12.89 | 0.008000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | 1.11 | 0.374571 | 0.300000 | 0.333223 | 0.998855 | 0.500000 | 0.001017 | 0.000125 | 0.613499 | 12.89 | 0.008000 |
| LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | 0.739632 | 0.176171 | 0.300000 | 0.221890 | 0.469790 | 0.500000 | 0.002163 | 0.000078 | 0.382364 | 12.89 | 0.008000 |
| MECH_ZN_1_FLR_1 VAV BOX COMPONENT | 0.792982 | 0.242154 | 0.300000 | 0.237895 | 0.645745 | 0.500000 | 0.001573 | 0.000039 | 0.237895 | 12.89 | 0.008000 |
| BATH_ZN_1_FLR_1 VAV BOX COMPONENT | 0.526358 | 0.275060 | 0.300000 | 0.157907 | 0.733493 | 0.500000 | 0.001385 | 0.000059 | 0.290198 | 12.89 | 0.008000 |
| OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | 1.70 | 0.528244 | 0.500000 | 0.001923 | 0.000166 | 0.817999 | 12.89 | 0.008000 | |||
| GYM_ZN_1_FLR_1 VAV BOX COMPONENT | 1.80 | 0.151521 | 0.447000 | 0.802525 | 0.447000 | 0.500000 | 0.002515 | 0.000136 | 0.802525 | 12.89 | 0.008000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | 1.71 | 0.177789 | 0.300000 | 0.513032 | 0.474104 | 0.500000 | 0.002143 | 0.000146 | 0.717160 | 12.89 | 0.008000 |
| Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6829.66 | 0.000060 | 159.29 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 25208.11 | 0.000221 | 560.34 |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6120.61 | 0.000054 | 142.76 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6827.97 | 0.000060 | 159.25 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 25102.16 | 0.000220 | 557.44 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6780.42 | 0.000059 | 158.15 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 24988.48 | 0.000219 | 554.39 |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6103.60 | 0.000053 | 142.37 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6831.83 | 0.000060 | 159.34 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 25095.30 | 0.000220 | 557.41 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6785.81 | 0.000059 | 158.27 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 25033.32 | 0.000219 | 555.64 |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6111.64 | 0.000053 | 142.55 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6869.74 | 0.000060 | 160.23 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 16800.71 | 0.000147 | 374.16 |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | 8310.13 | 0.000073 | 183.62 |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | 14273.22 | 0.000125 | 332.92 |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | 8894.87 | 0.000078 | 207.47 |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 4416.02 | 0.000039 | 97.61 |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6751.12 | 0.000059 | 157.47 |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | 19028.88 | 0.000166 | 443.83 |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | 15583.28 | 0.000136 | 347.75 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | 16682.89 | 0.000146 | 389.11 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| KITCHEN_ZN_1_FLR_1 DIRECT AIR | 1.55 |
| CAFETERIA_ZN_1_FLR_1 DIRECT AIR | 2.65 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| VAV_POD_1 | 15.09 | 12.83 | 29.02 | 12.83 | 28.77 | 28.77 | 0.300000 | 0.445920 | 28.77 |
| PSZ-AC_1:6 | 1.55 | 1.55 | 1.55 | 1.55 | 1.55 | 1.55 | 1.00 | 1.00 | 1.55 |
| PSZ-AC_2:7 | 2.65 | 2.65 | 2.65 | 2.65 | 2.65 | 2.65 | 1.00 | 1.00 | 2.65 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| VAV_POD_1_OA_CONTROLLER | 28.77 | |
| PSZ-AC_1:6_OA_CONTROLLER | 1.55 | 0.254814 |
| PSZ-AC_2:7_OA_CONTROLLER | 2.65 | 1.49 |
| Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
| VAV_POD_1 COOLING COIL | 28.77 | 559642.04 | 0.786865 | 9.59 | 186528.69 | 0.786865 |
| Design Size Nominal Capacity [W] | |
| VAV_POD_1 HEATING COIL | 175923.10 |
| PSZ-AC_1:6 HEATING COIL | 60785.56 |
| PSZ-AC_2:7 HEATING COIL | 79793.61 |
| Design Size Maximum Flow Rate [m3/s] | |
| VAV_POD_1 FAN | 28.77 |
| Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
| PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.55 | 2582.38 |
| PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | 2.65 | 4291.96 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| PSZ-AC_1:6_UNITARY_PACKAGE_DX | 1.55 | 1.55 | 1.55 | 1.55 | 31432.26 | 60785.56 | 32.11 | 1.00 |
| PSZ-AC_2:7_UNITARY_PACKAGE_DX | 2.65 | 2.65 | 2.65 | 2.65 | 56155.15 | 79793.61 | 32.11 | 1.00 |
| User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
| PSZ-AC_1:6 COOLING COIL | 1.55 | 0.776892 | 1.04 | 31432.26 | 15716.13 | 0.771850 | 0.771850 |
| PSZ-AC_2:7 COOLING COIL | 2.65 | 1.32 | 1.76 | 56155.15 | 28077.58 | 0.753760 | 0.753760 |
| Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
| HEATSYS1 | 0.002585 | 0.310146 |
| SWHSYS1 | 0.000105 | 0.012650 |
| Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
| HEATSYS1 PUMP | 0.002585 | 778.35 | 0.000000 |
| Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
| HEATSYS1 BOILER | 295429.77 | 295429.77 | 0.002585 |
| Design Flow Rate [m3/s] | Design Power Consumption [W] | |
| SWHSYS1 PUMP | 0.000105 | 13.47 |
| Use Side Design Flow Rate [m3/s] | |
| SWHSYS1 WATER HEATER | 0.000105 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| Possible Shadow Receivers | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | BATH_ZN_1_FLR_1_WALL_5 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | BATH_ZN_1_FLR_1_WALL_5 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | |
| BATH_ZN_1_FLR_1_WALL_5 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | |
| CAFETERIA_ZN_1_FLR_1_WALL_3 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | CAFETERIA_ZN_1_FLR_1_WALL_3 | |
| Possible Shadow Receivers | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | |
| LOBBY_ZN_1_FLR_1_WALL_1 | LOBBY_ZN_1_FLR_1_WALL_1_DOOR | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| BATH_ZN_1_FLR_1_WALL_5 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | |
| OFFICES_ZN_1_FLR_1_WALL_1 | OFFICES_ZN_1_FLR_1_WALL_1_DOOR | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| OFFICES_ZN_1_FLR_1_WALL_2 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | |
| GYM_ZN_1_FLR_1_WALL_2 | GYM_ZN_1_FLR_1_WALL_2_DOOR | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | |
| GYM_ZN_1_FLR_1_CEILING | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | |
| KITCHEN_ZN_1_FLR_1_WALL_2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | |
| CAFETERIA_ZN_1_FLR_1_WALL_2 | CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | |
| CAFETERIA_ZN_1_FLR_1_WALL_3 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | Yes | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 11.22 | 14.30 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | SchoolPrimary | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 25 | 288 | 92 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.0 | -64.00 | 0.00 | 0.00 | -58.50 | 4.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 0.00 | 9.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 0.0 | -53.00 | 0.00 | 0.00 | -26.50 | 4.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 0.00 | 9.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | 0.0 | -64.00 | 9.00 | 0.00 | -32.00 | 10.50 | 2.00 | 1 | 1 | 1 | -64.00 | 0.00 | 9.00 | 12.00 | 0.00 | 4.00 | 4.00 | 768.00 | TARP | TARP | 192.00 | 12.00 | 9.36 | 2.64 | 8 | 1 | 0 | Yes |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.0 | -64.00 | 12.00 | 0.00 | -58.50 | 16.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 12.00 | 21.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 0.0 | -53.00 | 12.00 | 0.00 | -26.50 | 16.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 12.00 | 21.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.0 | -64.00 | 30.00 | 0.00 | -58.50 | 34.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 30.00 | 39.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 0.0 | -53.00 | 30.00 | 0.00 | -26.50 | 34.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 30.00 | 39.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | 0.0 | -64.00 | 39.00 | 0.00 | -32.00 | 40.50 | 2.00 | 1 | 1 | 1 | -64.00 | 0.00 | 39.00 | 42.00 | 0.00 | 4.00 | 4.00 | 768.00 | TARP | TARP | 192.00 | 12.00 | 9.36 | 2.64 | 8 | 1 | 0 | Yes |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.0 | -64.00 | 42.00 | 0.00 | -58.50 | 46.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 42.00 | 51.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 0.0 | -53.00 | 42.00 | 0.00 | -26.50 | 46.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 42.00 | 51.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.0 | -64.00 | 61.00 | 0.00 | -58.50 | 65.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 61.00 | 70.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 0.0 | -53.00 | 61.00 | 0.00 | -26.50 | 65.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 61.00 | 70.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | 0.0 | -64.00 | 70.00 | 0.00 | -32.00 | 71.50 | 2.00 | 1 | 1 | 1 | -64.00 | 0.00 | 70.00 | 73.00 | 0.00 | 4.00 | 4.00 | 768.00 | TARP | TARP | 192.00 | 12.00 | 9.36 | 2.64 | 9 | 1 | 0 | Yes |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.0 | -64.00 | 73.00 | 0.00 | -58.50 | 77.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 73.00 | 82.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.48 | 17.57 | 6 | 4 | 0 | Yes |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.0 | -53.00 | 73.00 | 0.00 | -35.50 | 77.50 | 2.00 | 1 | 1 | 1 | -53.00 | -18.00 | 73.00 | 82.00 | 0.00 | 4.00 | 4.00 | 1260.00 | TARP | TARP | 315.00 | 140.00 | 105.30 | 30.80 | 6 | 5 | 0 | Yes |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | 0.0 | -18.00 | 73.00 | 0.00 | -9.00 | 77.50 | 2.00 | 1 | 1 | 1 | -18.00 | 0.00 | 73.00 | 82.00 | 0.00 | 4.00 | 4.00 | 648.00 | TARP | TARP | 162.00 | 72.00 | 54.21 | 15.84 | 6 | 3 | 0 | Yes |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | 0.0 | 0.00 | 9.00 | 0.00 | 6.50 | 30.00 | 2.00 | 1 | 1 | 1 | 0.00 | 13.00 | 9.00 | 51.00 | 0.00 | 4.00 | 4.00 | 2184.00 | TARP | TARP | 546.00 | 36.00 | 26.13 | 7.92 | 11 | 3 | 0 | Yes |
| 18 | LOBBY_ZN_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 9.50 | 4.50 | 2.00 | 1 | 1 | 1 | 0.00 | 19.00 | 0.00 | 9.00 | 0.00 | 4.00 | 4.00 | 684.00 | TARP | TARP | 171.00 | 76.00 | 57.33 | 16.72 | 7 | 3 | 0 | Yes |
| 19 | MECH_ZN_1_FLR_1 | 0.0 | 13.00 | 9.00 | 0.00 | 16.00 | 30.00 | 2.00 | 1 | 1 | 1 | 13.00 | 19.00 | 9.00 | 51.00 | 0.00 | 4.00 | 4.00 | 1008.00 | TARP | TARP | 252.00 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
| 20 | BATH_ZN_1_FLR_1 | 0.0 | 0.00 | 51.00 | 0.00 | 9.50 | 56.00 | 2.00 | 1 | 1 | 1 | 0.00 | 19.00 | 51.00 | 61.00 | 0.00 | 4.00 | 4.00 | 760.00 | TARP | TARP | 190.00 | 40.00 | 31.20 | 8.80 | 7 | 1 | 0 | Yes |
| 21 | OFFICES_ZN_1_FLR_1 | 0.0 | 19.00 | 0.00 | 0.00 | 29.50 | 10.50 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 0.00 | 21.00 | 0.00 | 4.00 | 4.00 | 1764.00 | TARP | TARP | 441.00 | 168.00 | 129.09 | 36.96 | 7 | 4 | 0 | Yes |
| 22 | GYM_ZN_1_FLR_1 | 0.0 | 19.00 | 21.00 | 0.00 | 29.50 | 29.50 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 21.00 | 38.00 | 0.00 | 4.00 | 4.00 | 1428.00 | TARP | TARP | 357.00 | 68.00 | 51.09 | 28.34 | 6 | 12 | 0 | Yes |
| 23 | KITCHEN_ZN_1_FLR_1 | 0.0 | 19.00 | 38.00 | 0.00 | 29.50 | 42.00 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 38.00 | 46.00 | 0.00 | 4.00 | 4.00 | 672.00 | TARP | TARP | 168.00 | 32.00 | 24.96 | 7.04 | 6 | 1 | 0 | Yes |
| 24 | CAFETERIA_ZN_1_FLR_1 | 0.0 | 19.00 | 46.00 | 0.00 | 29.50 | 53.50 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 46.00 | 61.00 | 0.00 | 4.00 | 4.00 | 1260.00 | TARP | TARP | 315.00 | 144.00 | 110.37 | 31.68 | 7 | 4 | 0 | Yes |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.0 | 0.00 | 61.00 | 0.00 | 9.50 | 71.50 | 2.00 | 1 | 1 | 1 | 0.00 | 19.00 | 61.00 | 82.00 | 0.00 | 4.00 | 4.00 | 1596.00 | TARP | TARP | 399.00 | 160.00 | 122.85 | 35.20 | 8 | 4 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 3.716 | 0.269 | 15.069 | 20.000 | 0.000 | 0.000 | 0.000 | 0.000 | 35.069 | No |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 18 | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 9.289 | 0.108 | 13.993 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.993 | No |
| 19 | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 61.932 | 1.615E-002 | 16.146 | 10.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26.146 | No |
| 20 | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 18.578 | 5.383E-002 | 9.688 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.688 | No |
| 21 | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 18.579 | 5.382E-002 | 11.840 | 10.800 | 0.000 | 0.000 | 0.000 | 0.000 | 22.640 | No |
| 22 | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 3.096 | 0.323 | 13.347 | 5.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.347 | No |
| 23 | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 6.224 | 0.161 | 12.917 | 200.664 | 1431.100 | 0.000 | 0.000 | 0.000 | 1644.681 | No |
| 24 | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 0.929 | 1.076 | 9.688 | 25.390 | 0.000 | 0.000 | 0.000 | 0.000 | 35.078 | No |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 9.289 | 0.108 | 16.684 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 31.684 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 10.3 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 10.3 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 10.3 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 84.8 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 81 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | BLDG_OCC_SCH_EXTEND | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 43.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 41 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 17 | MECH_ZN_1_FLR_1 | BLDG_OCC_SCH | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 4.1 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 4 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 18 | BATH_ZN_1_FLR_1 | BLDG_OCC_SCH | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 10.2 | 5.383E-002 | 18.578 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 19 | OFFICES_ZN_1_FLR_1 | BLDG_OCC_SCH_OFFICES_W_SB | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 23.7 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 23 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 20 | GYM_ZN_1_FLR_1 | BLDG_OCC_SCH_GYM | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 115.3 | 0.323 | 3.096 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 110 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 21 | KITCHEN_ZN_1_FLR_1 | BLDG_OCC_SCH | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 27.0 | 0.161 | 6.224 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 26 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 22 | CAFETERIA_ZN_1_FLR_1 | BLDG_OCC_SCH_CAFETERIA | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 339.1 | 1.076 | 0.929 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 322 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 23 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | BLDG_OCC_SCH | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 43.0 | 0.108 | 9.289 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 41 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 24 | MAIN_CORRIDOR_ZN_1_FLR_1 | BLDG_OCC_SCH | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 29.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 25 | LOBBY_ZN_1_FLR_1 | BLDG_OCC_SCH | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 18.4 | 0.108 | 9.289 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 1052.352 | 5.481 | 101.834 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1052.352 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 1052.352 | 5.481 | 101.834 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1052.352 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 1052.352 | 5.481 | 101.834 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1052.352 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 4746.880 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 4746.880 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1_LIGHTS | LTG_SCH_COMPUTER_ROOM | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 2441.253 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2441.253 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 2992.626 | 5.481 | 101.832 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2992.626 |
| 18 | LOBBY_ZN_1_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 2392.815 | 13.993 | 129.988 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2392.815 |
| 19 | MECH_ZN_1_FLR_1_LIGHTS | LTG_SCH_MECHANICAL | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 4068.754 | 16.146 | 999.940 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 4068.754 |
| 20 | BATH_ZN_1_FLR_1_LIGHTS | LTG_SCH_BATH | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 1840.627 | 9.688 | 179.977 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1840.627 |
| 21 | OFFICES_ZN_1_FLR_1_LIGHTS | LTG_SCH_OFFICE | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 5221.568 | 11.840 | 219.981 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 5221.568 |
| 22 | GYM_ZN_1_FLR_1_LIGHTS | LTG_SCH_GYM | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 4764.965 | 13.347 | 41.323 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 4764.965 |
| 23 | KITCHEN_ZN_1_FLR_1_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 2170.002 | 12.917 | 80.391 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2170.002 |
| 24 | CAFETERIA_ZN_1_FLR_1_LIGHTS | LTG_SCH_CAFETERIA | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 3051.566 | 9.688 | 9.000 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 3051.566 |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_LIGHTS | LTG_SCH_LIBRARY | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 6656.932 | 16.684 | 154.978 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 6656.932 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 768.000 | 4.000 | 74.318 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 149.700 | 729.600 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 768.000 | 4.000 | 74.318 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 149.700 | 729.600 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 768.000 | 4.000 | 74.318 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 149.700 | 729.600 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 4725.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 921.003 | 4488.750 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 3240.000 | 20.000 | 74.320 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 631.545 | 3078.000 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 2184.000 | 4.000 | 74.316 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 425.708 | 2074.800 |
| 18 | LOBBY_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 684.000 | 4.000 | 37.158 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 133.326 | 649.800 |
| 19 | MECH_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 2520.000 | 10.000 | 619.317 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 491.202 | 2394.000 |
| 20 | BATH_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 760.000 | 4.000 | 74.313 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 148.140 | 722.000 |
| 21 | OFFICES_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 4762.800 | 10.800 | 200.653 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 928.371 | 4524.660 |
| 22 | GYM_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 1785.000 | 5.000 | 15.480 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 347.935 | 1695.750 |
| 23 | KITCHEN_ZN_1_FLR_1_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 31995.600 | 190.450 | 1185.330 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 3199.560 | 7998.900 |
| 24 | KITCHEN_ZN_1_FLR_1_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 986.000 | 5.869 | 36.528 | 0.000 | 0.000 | 1.000 | 0.000 | ReachInFreezer | 986.000 | 986.000 |
| 25 | KITCHEN_ZN_1_FLR_1_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 730.000 | 4.345 | 27.044 | 0.000 | 0.000 | 1.000 | 0.000 | ReachInRefrigerator | 730.000 | 730.000 |
| 26 | CAFETERIA_ZN_1_FLR_1_PLUGMISC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 7997.850 | 25.390 | 23.587 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 799.785 | 1999.463 |
| 27 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 5985.000 | 15.000 | 139.335 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1166.604 | 5685.750 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | KITCHEN_ZN_1_FLR_1_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 240424.800 | 1431.100 | 8906.931 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 4808.496 | 48084.960 |
| Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
| 1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
| 2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 6 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 7 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 8 | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1980E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 9 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 10 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 11 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 12 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 13 | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1980E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 14 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 15 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 46 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 16 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 47 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 17 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 48 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 18 | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1980E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 19 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 20 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 21 | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR | 52 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 22 | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR | 53 | 2 | 7 | 0.167 | 0.2090E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 23 | LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR | 54 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 24 | MECH_ZN_1_FLR_1_FLOOR_FFACTOR | 55 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 25 | BATH_ZN_1_FLR_1_FLOOR_FFACTOR | 56 | 2 | 7 | 0.167 | 0.6720E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 26 | OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR | 57 | 2 | 7 | 0.167 | 0.1226 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 27 | GYM_ZN_1_FLR_1_FLOOR_FFACTOR | 58 | 2 | 7 | 0.167 | 0.6074E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 28 | KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR | 59 | 2 | 7 | 0.167 | 0.6074E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 29 | CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR | 60 | 2 | 7 | 0.167 | 0.1477 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 30 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR | 61 | 2 | 7 | 0.167 | 0.1292 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
| 1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
| 2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
| 3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
| 4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
| 5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
| 6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
| 7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
| 8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
| 9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
| 11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 50.42 |
| 17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 50.42 |
| 27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 32 | ~FC_Insulation_11 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 34 | ~FC_Insulation_12 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 36 | ~FC_Insulation_13 | 0.0000 | 0.000 | 0.000 | 0.000 | 50.42 |
| 37 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 38 | ~FC_Insulation_14 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 39 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 40 | ~FC_Insulation_15 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 41 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 42 | ~FC_Insulation_16 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 43 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 44 | ~FC_Insulation_17 | 0.0000 | 0.000 | 0.000 | 0.000 | 47.78 |
| 45 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 46 | ~FC_Insulation_18 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 47 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 48 | ~FC_Insulation_19 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
| 49 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 50 | ~FC_Insulation_20 | 0.0000 | 0.000 | 0.000 | 0.000 | 14.80 |
| 51 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 52 | ~FC_Insulation_21 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.077 |
| 53 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 54 | ~FC_Insulation_22 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.39 |
| 55 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 56 | ~FC_Insulation_23 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.39 |
| 57 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 58 | ~FC_Insulation_24 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.693 |
| 59 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 60 | ~FC_Insulation_25 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.662 |
| 61 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| Time | Outside | Cross | Inside | Flux (except final one) | |
| 1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
| 2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
| 3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
| 4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
| 5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
| 6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
| 7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
| 8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
| 9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
| 10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
| 11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
| 12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
| 13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
| 14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
| 15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
| 16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
| 17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
| 18 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
| 19 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
| 20 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
| 21 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
| 22 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
| 23 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
| 24 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
| 25 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
| 26 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
| 27 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
| 28 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
| 29 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
| 30 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 31 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 32 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 33 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 34 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 35 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 36 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 37 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 38 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 39 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 40 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 41 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 42 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 43 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 44 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 45 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 46 | 7 | -0.21707302E-07 | -0.21810081E-14 | -0.84952625E-14 | 0.13770899E-15 |
| 47 | 6 | 0.21407607E-05 | 0.45739277E-09 | 0.32038929E-02 | -0.26876939E-04 |
| 48 | 5 | -0.77205346E-04 | 0.24803070E-06 | -0.22452059 | 0.19631768E-02 |
| 49 | 4 | 0.12599243E-02 | 0.10780209E-04 | 4.8427850 | -0.45392265E-01 |
| 50 | 3 | -0.93942915E-02 | 0.82583168E-04 | -38.096111 | 0.39947953 |
| 51 | 2 | 0.30967349E-01 | 0.13253122E-03 | 116.62920 | -1.4198824 |
| 52 | 1 | -0.43132160E-01 | 0.38654114E-04 | -143.99276 | 2.0504445 |
| 53 | 0 | 0.20639933E-01 | 0.87079362E-06 | 60.838472 | |
| 54 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 55 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 56 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 57 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 58 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 59 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 60 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 61 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 62 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 63 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 64 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 65 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 66 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 67 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 68 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 69 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 70 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 71 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 72 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 73 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 74 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 75 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 76 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 77 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 78 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 79 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 80 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 81 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 82 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 83 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 84 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 85 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 86 | 7 | -0.21707302E-07 | -0.21810081E-14 | -0.84952625E-14 | 0.13770899E-15 |
| 87 | 6 | 0.21407607E-05 | 0.45739277E-09 | 0.32038929E-02 | -0.26876939E-04 |
| 88 | 5 | -0.77205346E-04 | 0.24803070E-06 | -0.22452059 | 0.19631768E-02 |
| 89 | 4 | 0.12599243E-02 | 0.10780209E-04 | 4.8427850 | -0.45392265E-01 |
| 90 | 3 | -0.93942915E-02 | 0.82583168E-04 | -38.096111 | 0.39947953 |
| 91 | 2 | 0.30967349E-01 | 0.13253122E-03 | 116.62920 | -1.4198824 |
| 92 | 1 | -0.43132160E-01 | 0.38654114E-04 | -143.99276 | 2.0504445 |
| 93 | 0 | 0.20639933E-01 | 0.87079362E-06 | 60.838472 | |
| 94 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 95 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 96 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 97 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 98 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 99 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 100 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 101 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 102 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 103 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 104 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 105 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 106 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 107 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 108 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 109 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 110 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 111 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 112 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 113 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 114 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 115 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 116 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 117 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 118 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 119 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 120 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 121 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 122 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 123 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 124 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 125 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 126 | 7 | -0.21707302E-07 | -0.21810081E-14 | -0.84952625E-14 | 0.13770899E-15 |
| 127 | 6 | 0.21407607E-05 | 0.45739277E-09 | 0.32038929E-02 | -0.26876939E-04 |
| 128 | 5 | -0.77205346E-04 | 0.24803070E-06 | -0.22452059 | 0.19631768E-02 |
| 129 | 4 | 0.12599243E-02 | 0.10780209E-04 | 4.8427850 | -0.45392265E-01 |
| 130 | 3 | -0.93942915E-02 | 0.82583168E-04 | -38.096111 | 0.39947953 |
| 131 | 2 | 0.30967349E-01 | 0.13253122E-03 | 116.62920 | -1.4198824 |
| 132 | 1 | -0.43132160E-01 | 0.38654114E-04 | -143.99276 | 2.0504445 |
| 133 | 0 | 0.20639933E-01 | 0.87079362E-06 | 60.838472 | |
| 134 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 135 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 136 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 137 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 138 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 139 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 140 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 141 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 142 | 7 | -0.29578731E-08 | -0.18610472E-14 | 0.16360026E-14 | -0.48190060E-16 |
| 143 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 144 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 145 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 146 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 147 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 148 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 149 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 150 | 7 | -0.29578731E-08 | -0.18610472E-14 | 0.16360026E-14 | -0.48190060E-16 |
| 151 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 152 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 153 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 154 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 155 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 156 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 157 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 158 | 7 | -0.20570949E-07 | -0.14658537E-14 | -0.76832012E-14 | 0.12671469E-15 |
| 159 | 6 | 0.20860838E-05 | 0.47270270E-09 | 0.32038024E-02 | -0.26876180E-04 |
| 160 | 5 | -0.77354338E-04 | 0.25871613E-06 | -0.22451551 | 0.19631320E-02 |
| 161 | 4 | 0.12908389E-02 | 0.11299182E-04 | 4.8427016 | -0.45391462E-01 |
| 162 | 3 | -0.97548753E-02 | 0.86890235E-04 | -38.095646 | 0.39947438 |
| 163 | 2 | 0.32375441E-01 | 0.13995703E-03 | 116.62830 | -1.4198704 |
| 164 | 1 | -0.45248243E-01 | 0.40996175E-04 | -143.99224 | 2.0504359 |
| 165 | 0 | 0.21692461E-01 | 0.93166815E-06 | 60.838472 | |
| 166 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 167 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 168 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 169 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 170 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 171 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 172 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 173 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 174 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
| 175 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
| 176 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
| 177 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
| 178 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
| 179 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
| 180 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
| 181 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
| 182 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 | |
| 183 | 7 | -0.63667935E-08 | -0.10874325E-13 | 0.11269204E-14 | -0.19557179E-16 |
| 184 | 6 | 0.22887183E-05 | 0.12967685E-08 | 0.32001644E-02 | -0.26845660E-04 |
| 185 | 5 | -0.14389595E-03 | 0.76205050E-06 | -0.22430950 | 0.19613133E-02 |
| 186 | 4 | 0.31719958E-02 | 0.34552480E-04 | 4.8392847 | -0.45358602E-01 |
| 187 | 3 | -0.27412176E-01 | 0.27382890E-03 | -38.076416 | 0.39926170 |
| 188 | 2 | 0.96706121E-01 | 0.45412367E-03 | 116.59097 | -1.4193709 |
| 189 | 1 | -0.13917125 | 0.13776341E-03 | -143.97030 | 2.0500753 |
| 190 | 0 | 0.67751290E-01 | 0.33403087E-05 | 60.838472 | |
| 191 | 7 | -0.34692083E-08 | -0.29835039E-14 | 0.22457095E-14 | -0.46878358E-16 |
| 192 | 6 | 0.35887165E-05 | 0.23456121E-08 | 0.31958645E-02 | -0.26809589E-04 |
| 193 | 5 | -0.24929292E-03 | 0.13860889E-05 | -0.22406525 | 0.19591573E-02 |
| 194 | 4 | 0.56768486E-02 | 0.63026314E-04 | 4.8352193 | -0.45319520E-01 |
| 195 | 3 | -0.49670058E-01 | 0.50068761E-03 | -38.053464 | 0.39900799 |
| 196 | 2 | 0.17611533 | 0.83223021E-03 | 116.54632 | -1.4187736 |
| 197 | 1 | -0.25403345 | 0.25321776E-03 | -143.94402 | 2.0496434 |
| 198 | 0 | 0.12381374 | 0.61501487E-05 | 60.838472 | |
| 199 | 7 | -0.70485818E-08 | -0.82048821E-14 | -0.11525862E-14 | 0.12346975E-16 |
| 200 | 6 | 0.21636134E-05 | 0.11761400E-08 | 0.32006654E-02 | -0.26849864E-04 |
| 201 | 5 | -0.13228193E-03 | 0.68999669E-06 | -0.22433795 | 0.19615643E-02 |
| 202 | 4 | 0.28871477E-02 | 0.31257738E-04 | 4.8397578 | -0.45363150E-01 |
| 203 | 3 | -0.24853202E-01 | 0.24753724E-03 | -38.079085 | 0.39929121 |
| 204 | 2 | 0.87536903E-01 | 0.41023195E-03 | 116.59616 | -1.4194403 |
| 205 | 1 | -0.12588244 | 0.12433901E-03 | -143.97335 | 2.0501255 |
| 206 | 0 | 0.61258788E-01 | 0.30111189E-05 | 60.838472 | |
| 207 | 7 | -0.70485818E-08 | -0.82048821E-14 | -0.11525862E-14 | 0.12346975E-16 |
| 208 | 6 | 0.21636134E-05 | 0.11761400E-08 | 0.32006654E-02 | -0.26849864E-04 |
| 209 | 5 | -0.13228193E-03 | 0.68999669E-06 | -0.22433795 | 0.19615643E-02 |
| 210 | 4 | 0.28871477E-02 | 0.31257738E-04 | 4.8397578 | -0.45363150E-01 |
| 211 | 3 | -0.24853202E-01 | 0.24753724E-03 | -38.079085 | 0.39929121 |
| 212 | 2 | 0.87536903E-01 | 0.41023195E-03 | 116.59616 | -1.4194403 |
| 213 | 1 | -0.12588244 | 0.12433901E-03 | -143.97335 | 2.0501255 |
| 214 | 0 | 0.61258788E-01 | 0.30111189E-05 | 60.838472 | |
| 215 | 7 | -0.28726507E-08 | -0.17143581E-14 | 0.24267693E-14 | -0.55541839E-16 |
| 216 | 6 | 0.42346750E-05 | 0.28245518E-08 | 0.31939123E-02 | -0.26793213E-04 |
| 217 | 5 | -0.29857172E-03 | 0.16707368E-05 | -0.22395432 | 0.19581782E-02 |
| 218 | 4 | 0.68293023E-02 | 0.76000496E-04 | 4.8333721 | -0.45301763E-01 |
| 219 | 3 | -0.59851213E-01 | 0.60399479E-03 | -38.043031 | 0.39889267 |
| 220 | 2 | 0.21235346 | 0.10042645E-02 | 116.52602 | -1.4185020 |
| 221 | 1 | -0.30639453 | 0.30573542E-03 | -143.93207 | 2.0494469 |
| 222 | 0 | 0.14935640 | 0.74123768E-05 | 60.838472 | |
| 223 | 7 | -0.32902409E-08 | -0.25529066E-14 | 0.11988885E-14 | -0.45014903E-16 |
| 224 | 6 | 0.37562854E-05 | 0.24712502E-08 | 0.31953527E-02 | -0.26805296E-04 |
| 225 | 5 | -0.26216584E-03 | 0.14606656E-05 | -0.22403617 | 0.19589006E-02 |
| 226 | 4 | 0.59784819E-02 | 0.66426580E-04 | 4.8347351 | -0.45314865E-01 |
| 227 | 3 | -0.52336689E-01 | 0.52775921E-03 | -38.050729 | 0.39897776 |
| 228 | 2 | 0.18560952 | 0.87732663E-03 | 116.54100 | -1.4187024 |
| 229 | 1 | -0.26775360 | 0.26697134E-03 | -143.94089 | 2.0495919 |
| 230 | 0 | 0.13050713 | 0.64865099E-05 | 60.838472 |
| Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
| 1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
| 2 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | 36 | 1 | VerySmooth | 3.922 | 3.922 | 1.000 | 0.493 |
| Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
| 1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
| 2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.36905 | 0.28585 | 0.28585 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 2.30798E-002 | 1.00000 | No |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Number of Refrigeration Compressor Racks | |
| 1 | 2 |
| Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
| 1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
| 2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | SWH BOOSTER G WATER HEATER | 2.2712E-002 | 6000.0 | 1.092 | 0.9931 |
| 2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 14.749 | 0.4701 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 2 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 3 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 4 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 5 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 6 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 7 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 8 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 9 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 10 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 11 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 12 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 13 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 14 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 15 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 16 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 17 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 18 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 19 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 20 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 21 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 22 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 23 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 24 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 25 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 26 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 27 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 28 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 29 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 3 | No | No |
| 30 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 2 | No | No |
| 31 | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 32 | CORRIDOR_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 33 | CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 34 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 35 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 36 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 37 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 38 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 39 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 40 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 41 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 42 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 43 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 44 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 45 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 46 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 47 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 48 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 49 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 50 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 51 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 52 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 53 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 54 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 55 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 56 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 57 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 58 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 59 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 60 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 61 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 62 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 63 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 64 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 65 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 66 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 67 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 68 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 69 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 70 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 71 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 72 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 73 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 74 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 75 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 76 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 77 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 78 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 79 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 80 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 81 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 82 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 83 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 84 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 85 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 3 | No | No |
| 86 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 2 | No | No |
| 87 | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 88 | CORRIDOR_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 89 | CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 90 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 91 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 92 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 93 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 94 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 95 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 96 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 97 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 98 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 99 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 100 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 101 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 102 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 103 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 104 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 105 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 106 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 107 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 108 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 109 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 110 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 111 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 112 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 113 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 114 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 115 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 116 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 117 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 118 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 119 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 120 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 121 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 122 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 123 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 124 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 125 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 126 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 127 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 128 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 129 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 130 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 131 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 132 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 133 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 134 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 135 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 136 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 137 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 138 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 139 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 140 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 141 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 142 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 3 | No | No |
| 143 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 2 | No | No |
| 144 | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 145 | CORRIDOR_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 146 | CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 147 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 148 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 149 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 150 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 151 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 152 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 153 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 154 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 155 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 156 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 157 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 158 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 159 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 160 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 3 | No | No |
| 161 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 2 | No | No |
| 162 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 2 | No | No |
| 163 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 2 | No | No |
| 164 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 165 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 166 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 167 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 168 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 169 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 170 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 171 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 172 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 3 | No | No |
| 173 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 2 | No | No |
| 174 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 2 | No | No |
| 175 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 176 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 177 | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 178 | COMPUTER_CLASS_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 179 | COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 180 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 181 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 182 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 183 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 184 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 185 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 186 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 3 | No | No |
| 187 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 2 | No | No |
| 188 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 2 | No | No |
| 189 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 190 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 191 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 192 | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 193 | MAIN_CORRIDOR_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 194 | MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 195 | LOBBY_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 3 | No | No |
| 196 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 2 | No | No |
| 197 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 2 | No | No |
| 198 | LOBBY_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 199 | LOBBY_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 200 | LOBBY_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 201 | LOBBY_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 202 | LOBBY_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 203 | LOBBY_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 204 | LOBBY_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 205 | LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 206 | MECH_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 207 | MECH_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 208 | MECH_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 209 | MECH_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 210 | MECH_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 211 | MECH_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 212 | MECH_ZN_1_FLR_1_WALL_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 213 | MECH_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 214 | MECH_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 215 | MECH_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 216 | BATH_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 217 | BATH_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 218 | BATH_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 219 | BATH_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 220 | BATH_ZN_1_FLR_1_WALL_5 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 3 | No | No |
| 221 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 2 | No | No |
| 222 | BATH_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 223 | BATH_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 224 | BATH_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 225 | OFFICES_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 3 | No | No |
| 226 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 2 | No | No |
| 227 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 2 | No | No |
| 228 | OFFICES_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 229 | OFFICES_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 3 | No | No |
| 230 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 2 | No | No |
| 231 | OFFICES_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 232 | OFFICES_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 233 | OFFICES_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 234 | OFFICES_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 235 | OFFICES_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 236 | OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 237 | GYM_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 238 | GYM_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 3 | No | No |
| 239 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 240 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 241 | GYM_ZN_1_FLR_1_WALL_2_DOOR | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 242 | GYM_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 243 | GYM_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 244 | GYM_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 245 | GYM_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 246 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 247 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 248 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 249 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 250 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 251 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 252 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 253 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 254 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 255 | GYM_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 256 | KITCHEN_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 257 | KITCHEN_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 3 | No | No |
| 258 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 2 | No | No |
| 259 | KITCHEN_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 260 | KITCHEN_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 261 | KITCHEN_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 262 | KITCHEN_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 263 | KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 264 | CAFETERIA_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 265 | CAFETERIA_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 3 | No | No |
| 266 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 2 | No | No |
| 267 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 2 | No | No |
| 268 | CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 269 | CAFETERIA_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 3 | No | No |
| 270 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 2 | No | No |
| 271 | CAFETERIA_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 272 | CAFETERIA_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 273 | CAFETERIA_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 274 | CAFETERIA_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 275 | CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 276 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 277 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 3 | No | No |
| 278 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 2 | No | No |
| 279 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 2 | No | No |
| 280 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 281 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 3 | No | No |
| 282 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 2 | No | No |
| 283 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 284 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 285 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 286 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 287 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 288 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
| 1 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.786 | 0.497 | 0.492 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 6.835E-003 | 3.560E-005 | 3.350E-005 | 3.204E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 6.835E-003 | 3.560E-005 | 3.350E-005 | 3.204E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 6.835E-003 | 3.560E-005 | 3.350E-005 | 3.204E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 7.974E-002 | 2.531E-004 | 1.738E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 4.101E-002 | 2.531E-004 | 1.738E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 2.050E-002 | 3.755E-005 | 3.511E-005 | 3.380E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | LOBBY_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 4.329E-002 | 2.531E-004 | 1.739E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | LOBBY_ZN_1_FLR_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 3.031 | 1.773E-002 | 1.218E-002 | 15.954 | 1.000 | 0.000 | 0.000 | 0.000 |
| 20 | MECH_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | BATH_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 2.278E-002 | 1.199E-004 | 9.906E-005 | 0.108 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | OFFICES_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 9.569E-002 | 2.170E-004 | 1.566E-004 | 0.195 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | GYM_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 3.873E-002 | 1.085E-004 | 9.072E-005 | 9.764E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | KITCHEN_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 1.823E-002 | 1.085E-004 | 9.113E-005 | 9.764E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | CAFETERIA_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 8.202E-002 | 2.604E-004 | 1.779E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 9.113E-002 | 2.284E-004 | 1.625E-004 | 0.206 | 0.000 | 0.000 | 0.224 | 0.000 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 18 | LOBBY_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 19 | MECH_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 20 | BATH_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 21 | OFFICES_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 22 | GYM_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 23 | KITCHEN_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 24 | CAFETERIA_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2500 |
| 2 | Zone CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1.2500 |
| 3 | Zone MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.2500 |
| 4 | Zone CORRIDOR_POD_1_ZN_1_FLR_1 | 1.2500 |
| 5 | Zone CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1.2500 |
| 6 | Zone MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.2500 |
| 7 | Zone CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1.2500 |
| 8 | Zone MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.2500 |
| 9 | Zone CORRIDOR_POD_2_ZN_1_FLR_1 | 1.2500 |
| 10 | Zone CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1.2500 |
| 11 | Zone MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.2500 |
| 12 | Zone CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1.2500 |
| 13 | Zone MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.2500 |
| 14 | Zone CORRIDOR_POD_3_ZN_1_FLR_1 | 1.2500 |
| 15 | Zone CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1.2500 |
| 16 | Zone MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1.2500 |
| 17 | Zone COMPUTER_CLASS_ZN_1_FLR_1 | 1.2500 |
| 18 | Zone MAIN_CORRIDOR_ZN_1_FLR_1 | 1.2500 |
| 19 | Zone LOBBY_ZN_1_FLR_1 | 1.2500 |
| 20 | Zone MECH_ZN_1_FLR_1 | 1.2500 |
| 21 | Zone BATH_ZN_1_FLR_1 | 1.2500 |
| 22 | Zone OFFICES_ZN_1_FLR_1 | 1.2500 |
| 23 | Zone GYM_ZN_1_FLR_1 | 1.2500 |
| 24 | Zone KITCHEN_ZN_1_FLR_1 | 1.2500 |
| 25 | Zone CAFETERIA_ZN_1_FLR_1 | 1.2500 |
| 26 | Zone LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 1.2500 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.1500 |
| 2 | Zone CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1.1500 |
| 3 | Zone MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.1500 |
| 4 | Zone CORRIDOR_POD_1_ZN_1_FLR_1 | 1.1500 |
| 5 | Zone CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1.1500 |
| 6 | Zone MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.1500 |
| 7 | Zone CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1.1500 |
| 8 | Zone MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.1500 |
| 9 | Zone CORRIDOR_POD_2_ZN_1_FLR_1 | 1.1500 |
| 10 | Zone CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1.1500 |
| 11 | Zone MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.1500 |
| 12 | Zone CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1.1500 |
| 13 | Zone MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.1500 |
| 14 | Zone CORRIDOR_POD_3_ZN_1_FLR_1 | 1.1500 |
| 15 | Zone CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1.1500 |
| 16 | Zone MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1.1500 |
| 17 | Zone COMPUTER_CLASS_ZN_1_FLR_1 | 1.1500 |
| 18 | Zone MAIN_CORRIDOR_ZN_1_FLR_1 | 1.1500 |
| 19 | Zone LOBBY_ZN_1_FLR_1 | 1.1500 |
| 20 | Zone MECH_ZN_1_FLR_1 | 1.1500 |
| 21 | Zone BATH_ZN_1_FLR_1 | 1.1500 |
| 22 | Zone OFFICES_ZN_1_FLR_1 | 1.1500 |
| 23 | Zone GYM_ZN_1_FLR_1 | 1.1500 |
| 24 | Zone KITCHEN_ZN_1_FLR_1 | 1.1500 |
| 25 | Zone CAFETERIA_ZN_1_FLR_1 | 1.1500 |
| 26 | Zone LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 1.1500 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | Cooling | 7972.08478 | 9167.89750 | 0.59245 | 0.68132 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 28.98400 | 8.82083E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 2 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | Heating | 3158.99435 | 3948.74294 | 0.23488 | 0.29360 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 3 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | Cooling | 33481.95918 | 38504.25305 | 2.48828 | 2.86153 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 29.40000 | 8.82150E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 4 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | Heating | 9787.86503 | 12234.83129 | 0.72777 | 0.90971 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 5 | CORRIDOR_POD_1_ZN_1_FLR_1 | Cooling | 6187.37565 | 7115.48200 | 0.45969 | 0.52864 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 29.08800 | 8.82100E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 6 | CORRIDOR_POD_1_ZN_1_FLR_1 | Heating | 2830.44893 | 3538.06117 | 0.21046 | 0.26308 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 7 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | Cooling | 6687.54990 | 7690.68239 | 0.49699 | 0.57154 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 28.08267 | 8.81938E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 8 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | Heating | 3158.21210 | 3947.76512 | 0.23482 | 0.29353 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 9 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | Cooling | 26049.50506 | 29956.93082 | 1.93595 | 2.22634 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40000 | 8.82150E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 10 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | Heating | 9699.82165 | 12124.77706 | 0.72123 | 0.90153 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 11 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | Cooling | 7929.96045 | 9119.45451 | 0.58932 | 0.67772 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 28.98400 | 8.82083E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 12 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | Heating | 3136.22428 | 3920.28035 | 0.23319 | 0.29149 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 13 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | Cooling | 33132.93908 | 38102.87994 | 2.46235 | 2.83170 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 29.40000 | 8.82150E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 14 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | Heating | 9609.26990 | 12011.58737 | 0.71449 | 0.89657 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 15 | CORRIDOR_POD_2_ZN_1_FLR_1 | Cooling | 6169.16685 | 7094.54188 | 0.45833 | 0.52708 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 29.08800 | 8.82100E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 16 | CORRIDOR_POD_2_ZN_1_FLR_1 | Heating | 2822.58709 | 3528.23387 | 0.20988 | 0.26235 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 17 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | Cooling | 6690.05537 | 7693.56368 | 0.49718 | 0.57176 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 28.08267 | 8.81938E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 18 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | Heating | 3159.99634 | 3949.99542 | 0.23496 | 0.29369 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 19 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | Cooling | 26059.63832 | 29968.58406 | 1.93670 | 2.22721 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40000 | 8.82150E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 20 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | Heating | 9707.77937 | 12134.72422 | 0.72182 | 0.90227 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 21 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | Cooling | 7935.17643 | 9125.45290 | 0.58971 | 0.67816 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 28.98400 | 8.82083E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 22 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | Heating | 3138.71329 | 3923.39161 | 0.23337 | 0.29172 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 23 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | Cooling | 33262.12015 | 38251.43817 | 2.47195 | 2.84274 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 29.40000 | 8.82150E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 24 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | Heating | 9649.28520 | 12061.60650 | 0.71747 | 0.89683 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 25 | CORRIDOR_POD_3_ZN_1_FLR_1 | Cooling | 6225.29059 | 7159.08418 | 0.46250 | 0.53188 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 29.08800 | 8.82100E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 26 | CORRIDOR_POD_3_ZN_1_FLR_1 | Heating | 2826.30449 | 3532.88062 | 0.21015 | 0.26269 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 27 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | Cooling | 6728.49521 | 7737.76949 | 0.50004 | 0.57504 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 28.08267 | 8.81938E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 28 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | Heating | 3177.52661 | 3971.90826 | 0.23626 | 0.29532 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 29 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | Cooling | 17467.13984 | 20087.21082 | 1.29812 | 1.49284 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40000 | 8.82150E-003 | 315.00000 | 84.76857 | 0.59207 | 0.00000 |
| 30 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | Heating | 6584.54674 | 8230.68342 | 0.48959 | 0.61199 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 315.00000 | 84.76857 | 0.59207 | 0.00000 |
| 31 | COMPUTER_CLASS_ZN_1_FLR_1 | Cooling | 9680.58057 | 11132.66765 | 0.71944 | 0.82735 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40000 | 8.82150E-003 | 162.00000 | 43.59526 | 0.30449 | 0.00000 |
| 32 | COMPUTER_CLASS_ZN_1_FLR_1 | Heating | 3127.82147 | 3909.77684 | 0.23257 | 0.30449 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 162.00000 | 43.59526 | 0.30449 | 0.00000 |
| 33 | MAIN_CORRIDOR_ZN_1_FLR_1 | Cooling | 13000.37169 | 14950.42744 | 0.96586 | 1.11074 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 29.08800 | 8.82100E-003 | 546.00000 | 29.38800 | 0.16642 | 0.00000 |
| 34 | MAIN_CORRIDOR_ZN_1_FLR_1 | Heating | 6600.66370 | 8250.82963 | 0.49080 | 0.61350 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 546.00000 | 29.38800 | 0.16642 | 0.00000 |
| 35 | LOBBY_ZN_1_FLR_1 | Cooling | 8656.22007 | 9954.65309 | 0.64316 | 0.73963 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 29.40000 | 8.82150E-003 | 171.00000 | 18.40800 | 9.55546E-002 | 0.00000 |
| 36 | LOBBY_ZN_1_FLR_1 | Heating | 4113.95166 | 5142.43957 | 0.30589 | 0.38236 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 171.00000 | 18.40800 | 9.55546E-002 | 0.00000 |
| 37 | MECH_ZN_1_FLR_1 | Cooling | 9281.80510 | 10674.07587 | 0.68955 | 0.79298 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 29.40000 | 8.82150E-003 | 252.00000 | 4.06900 | 0.00000 | 0.00000 |
| 38 | MECH_ZN_1_FLR_1 | Heating | 1664.37588 | 2080.46985 | 0.12376 | 0.15470 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:40:00 | -4.20000 | 2.69032E-003 | 252.00000 | 4.06900 | 0.00000 | 0.00000 |
| 39 | BATH_ZN_1_FLR_1 | Cooling | 6160.63319 | 7084.72817 | 0.45770 | 0.52636 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 28.22133 | 8.81961E-003 | 190.00000 | 10.22700 | 0.00000 | 0.00000 |
| 40 | BATH_ZN_1_FLR_1 | Heating | 3122.27316 | 3902.84146 | 0.23216 | 0.29020 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 190.00000 | 10.22700 | 0.00000 | 0.00000 |
| 41 | OFFICES_ZN_1_FLR_1 | Cooling | 19855.11253 | 22833.37941 | 1.47513 | 1.69640 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40000 | 8.82150E-003 | 441.00000 | 23.73648 | 0.19042 | 0.00000 |
| 42 | OFFICES_ZN_1_FLR_1 | Heating | 8801.03825 | 11001.29781 | 0.65440 | 0.81800 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 441.00000 | 23.73648 | 0.19042 | 0.00000 |
| 43 | GYM_ZN_1_FLR_1 | Cooling | 21005.06586 | 24155.82574 | 1.56118 | 1.79536 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 29.14000 | 8.82108E-003 | 357.00000 | 115.31008 | 0.54407 | 0.00000 |
| 44 | GYM_ZN_1_FLR_1 | Heating | 6165.06790 | 7706.33488 | 0.45841 | 0.57301 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | -4.20000 | 2.69032E-003 | 357.00000 | 115.31008 | 0.54407 | 0.00000 |
| 45 | KITCHEN_ZN_1_FLR_1 | Cooling | 18162.78261 | 20887.20000 | 1.35112 | 1.55378 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 28.46400 | 8.82000E-003 | 168.00000 | 26.99300 | 0.25481 | 0.00000 |
| 46 | KITCHEN_ZN_1_FLR_1 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.25481 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | -4.20000 | 2.69032E-003 | 168.00000 | 26.99300 | 0.25481 | 0.00000 |
| 47 | CAFETERIA_ZN_1_FLR_1 | Cooling | 30923.00509 | 35561.45586 | 2.30077 | 2.64589 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 28.88000 | 8.82066E-003 | 315.00000 | 339.07427 | 1.48818 | 0.00000 |
| 48 | CAFETERIA_ZN_1_FLR_1 | Heating | 6883.87520 | 8604.84400 | 0.51184 | 1.48818 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | -4.20000 | 2.69032E-003 | 315.00000 | 339.07427 | 1.48818 | 0.00000 |
| 49 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | Cooling | 20013.95584 | 23016.04922 | 1.48705 | 1.71011 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 399.00000 | 42.95403 | 0.34458 | 0.00000 |
| 50 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | Heating | 7716.10165 | 9645.12706 | 0.57373 | 0.71716 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | -4.20000 | 2.69032E-003 | 399.00000 | 42.95403 | 0.34458 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | VAV_POD_1 | Cooling | Sensible | 450016.37 | 28.76969 | 28.76969 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
| 2 | VAV_POD_1 | Heating | Sensible | 209744.35 | 11.51845 | 11.51845 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 01:00:00 |
| 3 | PSZ-AC_1:6 | Cooling | Sensible | 21868.42 | 1.55378 | 1.55378 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 4 | PSZ-AC_1:6 | Heating | Sensible | 11035.75 | 0.25481 | 0.25481 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| 5 | PSZ-AC_2:7 | Cooling | Sensible | 44091.51 | 2.64589 | 2.64589 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
| 6 | PSZ-AC_2:7 | Heating | Sensible | 64451.84 | 1.48818 | 1.48818 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.68132 |
| 2 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11072 |
| 3 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.40300 |
| 4 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27457 |
| 5 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40300 |
| 6 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 7 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.44099E-003 |
| 8 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.97489E-005 |
| 9 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29360 |
| 10 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 11 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 12 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6829.66238 |
| 13 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.97489E-005 |
| 14 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 159.29435 |
| 15 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.86153 |
| 16 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12702 |
| 17 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46200 |
| 18 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.32202 |
| 19 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46200 |
| 20 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 21 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.99950E-003 |
| 22 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.20531E-004 |
| 23 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.32202 |
| 24 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 25 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 26 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25208.10505 |
| 27 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.20531E-004 |
| 28 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 560.33511 |
| 29 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.52864 |
| 30 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27676 |
| 31 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 32 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15859 |
| 33 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73802 |
| 34 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 35 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37666E-003 |
| 36 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.35457E-005 |
| 37 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26308 |
| 38 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 39 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 40 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6120.60510 |
| 41 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.35457E-005 |
| 42 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 142.76285 |
| 43 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57154 |
| 44 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13199 |
| 45 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48000 |
| 46 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27434 |
| 47 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48000 |
| 48 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 49 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88657E-003 |
| 50 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.97341E-005 |
| 51 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29353 |
| 52 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 53 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 54 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6827.97082 |
| 55 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.97341E-005 |
| 56 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 159.25490 |
| 57 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22634 |
| 58 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16326 |
| 59 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59400 |
| 60 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.32245 |
| 61 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59400 |
| 62 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 63 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33369E-003 |
| 64 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.19605E-004 |
| 65 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.32245 |
| 66 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 67 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 68 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25102.15736 |
| 69 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.19605E-004 |
| 70 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 557.44393 |
| 71 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67772 |
| 72 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11131 |
| 73 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.40500 |
| 74 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27448 |
| 75 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40500 |
| 76 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 77 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.42281E-003 |
| 78 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.93181E-005 |
| 79 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29149 |
| 80 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 81 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 82 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6780.42437 |
| 83 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.93181E-005 |
| 84 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 158.14587 |
| 85 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.83170 |
| 86 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12836 |
| 87 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46700 |
| 88 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.32240 |
| 89 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46700 |
| 90 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 91 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.96824E-003 |
| 92 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.18610E-004 |
| 93 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.32240 |
| 94 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 95 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 96 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24988.47709 |
| 97 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.18610E-004 |
| 98 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 554.39243 |
| 99 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.52708 |
| 100 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27757 |
| 101 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 102 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15812 |
| 103 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.74019 |
| 104 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 105 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37261E-003 |
| 106 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.33970E-005 |
| 107 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26235 |
| 108 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 109 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 110 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6103.60393 |
| 111 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.33970E-005 |
| 112 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 142.36629 |
| 113 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57176 |
| 114 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13194 |
| 115 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48000 |
| 116 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27444 |
| 117 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48000 |
| 118 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 119 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88765E-003 |
| 120 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.97678E-005 |
| 121 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29369 |
| 122 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 123 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 124 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6831.82907 |
| 125 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.97678E-005 |
| 126 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 159.34489 |
| 127 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.22721 |
| 128 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16320 |
| 129 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.59300 |
| 130 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.32074 |
| 131 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.59300 |
| 132 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 133 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.33460E-003 |
| 134 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.19545E-004 |
| 135 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.32074 |
| 136 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 137 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 138 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25095.30084 |
| 139 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.19545E-004 |
| 140 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 557.41233 |
| 141 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67816 |
| 142 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11124 |
| 143 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.40400 |
| 144 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27398 |
| 145 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40400 |
| 146 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 147 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.42506E-003 |
| 148 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.93652E-005 |
| 149 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29172 |
| 150 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 151 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 152 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6785.80660 |
| 153 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.93652E-005 |
| 154 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 158.27141 |
| 155 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.84274 |
| 156 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12786 |
| 157 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.46500 |
| 158 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.32187 |
| 159 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46500 |
| 160 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 161 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.97981E-003 |
| 162 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.19002E-004 |
| 163 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.32187 |
| 164 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 165 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 166 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25033.31772 |
| 167 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.19002E-004 |
| 168 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 555.64391 |
| 169 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.53188 |
| 170 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27507 |
| 171 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 172 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15956 |
| 173 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73352 |
| 174 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 175 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38510E-003 |
| 176 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.34673E-005 |
| 177 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26269 |
| 178 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 179 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 180 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6111.64278 |
| 181 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.34673E-005 |
| 182 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 142.55380 |
| 183 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.57504 |
| 184 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13119 |
| 185 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.47700 |
| 186 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27429 |
| 187 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47700 |
| 188 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 189 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.90425E-003 |
| 190 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.00995E-005 |
| 191 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29532 |
| 192 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 193 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 194 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6869.73653 |
| 195 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.00995E-005 |
| 196 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 160.22909 |
| 197 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.49284 |
| 198 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16079 |
| 199 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.58500 |
| 200 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.87331 |
| 201 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58500 |
| 202 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 203 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.36959E-003 |
| 204 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.46980E-004 |
| 205 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.87331 |
| 206 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 207 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 208 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16800.71471 |
| 209 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.46980E-004 |
| 210 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 374.16293 |
| 211 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.82735 |
| 212 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14920 |
| 213 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.54200 |
| 214 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.44842 |
| 215 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54200 |
| 216 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 217 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.55355E-003 |
| 218 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.27007E-005 |
| 219 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.44842 |
| 220 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 221 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 222 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8310.13399 |
| 223 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.27007E-005 |
| 224 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 183.62371 |
| 225 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11074 |
| 226 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.37457 |
| 227 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 228 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33322 |
| 229 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.99886 |
| 230 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 231 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.01716E-003 |
| 232 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.24868E-004 |
| 233 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.61350 |
| 234 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 235 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 236 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14273.22144 |
| 237 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.24868E-004 |
| 238 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 332.92134 |
| 239 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73963 |
| 240 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17617 |
| 241 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 242 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.22189 |
| 243 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46979 |
| 244 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 245 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16267E-003 |
| 246 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.78162E-005 |
| 247 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.38236 |
| 248 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 249 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 250 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8894.87023 |
| 251 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.78162E-005 |
| 252 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 207.46597 |
| 253 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.79298 |
| 254 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.24215 |
| 255 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 256 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23789 |
| 257 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.64574 |
| 258 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 259 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.57338E-003 |
| 260 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.86333E-005 |
| 261 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23789 |
| 262 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 263 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 264 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4416.01889 |
| 265 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.86333E-005 |
| 266 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 97.61151 |
| 267 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.52636 |
| 268 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27506 |
| 269 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 270 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.15791 |
| 271 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73349 |
| 272 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 273 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.38515E-003 |
| 274 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.90617E-005 |
| 275 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29020 |
| 276 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 277 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 278 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 6751.11937 |
| 279 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.90617E-005 |
| 280 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 157.46654 |
| 281 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.69640 |
| 282 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52824 |
| 283 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 284 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.92336E-003 |
| 285 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.66473E-004 |
| 286 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.81800 |
| 287 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 288 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 289 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19028.88199 |
| 290 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.66473E-004 |
| 291 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 443.83332 |
| 292 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.79536 |
| 293 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15152 |
| 294 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.44700 |
| 295 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.80252 |
| 296 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44700 |
| 297 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 298 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.51451E-003 |
| 299 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.36329E-004 |
| 300 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.80252 |
| 301 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 302 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 303 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15583.28245 |
| 304 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.36329E-004 |
| 305 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 347.74967 |
| 306 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN_ZN_1_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.55378 |
| 307 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CAFETERIA_ZN_1_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.64589 |
| 308 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.71011 |
| 309 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17779 |
| 310 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 311 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.51303 |
| 312 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.47410 |
| 313 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 314 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.14299E-003 |
| 315 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.45949E-004 |
| 316 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71716 |
| 317 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 318 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 319 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16682.88832 |
| 320 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45949E-004 |
| 321 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 389.11353 |
| 322 | AirLoopHVAC | VAV_POD_1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 15.09026 |
| 323 | AirLoopHVAC | VAV_POD_1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 12.82899 |
| 324 | AirLoopHVAC | VAV_POD_1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 29.02442 |
| 325 | AirLoopHVAC | VAV_POD_1 | Adjusted Heating Design Air Flow Rate [m3/s] | 12.82899 |
| 326 | AirLoopHVAC | VAV_POD_1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 28.76969 |
| 327 | AirLoopHVAC | VAV_POD_1 | Adjusted Main Design Air Flow Rate [m3/s] | 28.76969 |
| 328 | AirLoopHVAC | VAV_POD_1 | User Heating Air Flow Ratio [] | 0.30000 |
| 329 | AirLoopHVAC | VAV_POD_1 | Calculated Heating Air Flow Ratio [] | 0.44592 |
| 330 | AirLoopHVAC | PSZ-AC_1:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.55378 |
| 331 | AirLoopHVAC | PSZ-AC_1:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.55378 |
| 332 | AirLoopHVAC | PSZ-AC_1:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.55378 |
| 333 | AirLoopHVAC | PSZ-AC_1:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.55378 |
| 334 | AirLoopHVAC | PSZ-AC_1:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.55378 |
| 335 | AirLoopHVAC | PSZ-AC_1:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.55378 |
| 336 | AirLoopHVAC | PSZ-AC_1:6 | User Heating Air Flow Ratio [] | 1.00000 |
| 337 | AirLoopHVAC | PSZ-AC_1:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 338 | AirLoopHVAC | PSZ-AC_2:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.64589 |
| 339 | AirLoopHVAC | PSZ-AC_2:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.64589 |
| 340 | AirLoopHVAC | PSZ-AC_2:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.64589 |
| 341 | AirLoopHVAC | PSZ-AC_2:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.64589 |
| 342 | AirLoopHVAC | PSZ-AC_2:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.64589 |
| 343 | AirLoopHVAC | PSZ-AC_2:7 | Adjusted Main Design Air Flow Rate [m3/s] | 2.64589 |
| 344 | AirLoopHVAC | PSZ-AC_2:7 | User Heating Air Flow Ratio [] | 1.00000 |
| 345 | AirLoopHVAC | PSZ-AC_2:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 346 | AirLoopHVAC | VAV_POD_1 | Design Supply Air Flow Rate [m3/s] | 28.76969 |
| 347 | AirLoopHVAC | PSZ-AC_1:6 | Design Supply Air Flow Rate [m3/s] | 1.55378 |
| 348 | AirLoopHVAC | PSZ-AC_2:7 | Design Supply Air Flow Rate [m3/s] | 2.64589 |
| 349 | Controller:OutdoorAir | VAV_POD_1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 28.76969 |
| 350 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 28.76969 |
| 351 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 559642.03697 |
| 352 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.78686 |
| 353 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 9.58894 |
| 354 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 186528.69092 |
| 355 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.78686 |
| 356 | Coil:Heating:Fuel | VAV_POD_1 HEATING COIL | Design Size Nominal Capacity [W] | 175923.10282 |
| 357 | Fan:VariableVolume | VAV_POD_1 FAN | Design Size Maximum Flow Rate [m3/s] | 28.76969 |
| 358 | Controller:OutdoorAir | PSZ-AC_1:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.55378 |
| 359 | Controller:OutdoorAir | PSZ-AC_1:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.25481 |
| 360 | Fan:SystemModel | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.55378 |
| 361 | Fan:SystemModel | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2582.38350 |
| 362 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.55378 |
| 363 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.55378 |
| 364 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.55378 |
| 365 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.55378 |
| 366 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.55378 |
| 367 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.77689 |
| 368 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.03585 |
| 369 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31432.26000 |
| 370 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15716.13000 |
| 371 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77185 |
| 372 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77185 |
| 373 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31432.26000 |
| 374 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 60785.55836 |
| 375 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
| 376 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 377 | Coil:Heating:Fuel | PSZ-AC_1:6 HEATING COIL | Design Size Nominal Capacity [W] | 60785.55836 |
| 378 | Controller:OutdoorAir | PSZ-AC_2:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.64589 |
| 379 | Controller:OutdoorAir | PSZ-AC_2:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.48818 |
| 380 | Fan:SystemModel | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.64589 |
| 381 | Fan:SystemModel | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 4291.96007 |
| 382 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.64589 |
| 383 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.64589 |
| 384 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.64589 |
| 385 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.64589 |
| 386 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.64589 |
| 387 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.32294 |
| 388 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.76393 |
| 389 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 56155.15000 |
| 390 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 28077.57500 |
| 391 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75376 |
| 392 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75376 |
| 393 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 56155.15000 |
| 394 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 79793.61043 |
| 395 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
| 396 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 397 | Coil:Heating:Fuel | PSZ-AC_2:7 HEATING COIL | Design Size Nominal Capacity [W] | 79793.61043 |
| 398 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.58455E-003 |
| 399 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.31015 |
| 400 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.58455E-003 |
| 401 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 778.35251 |
| 402 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
| 403 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 295429.77104 |
| 404 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 295429.77000 |
| 405 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.58455E-003 |
| 406 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.05414E-004 |
| 407 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.26497E-002 |
| 408 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.05414E-004 |
| 409 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 13.46550 |
| 410 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.05414E-004 |
| Component Type | Name | Nominal Total Capacity {W} | |
| 1 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6479.17 |
| 2 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23921.00 |
| 3 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5806.50 |
| 4 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6477.56 |
| 5 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23820.56 |
| 6 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6432.46 |
| 7 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23712.79 |
| 8 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5790.37 |
| 9 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6481.22 |
| 10 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23814.03 |
| 11 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6437.56 |
| 12 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23755.29 |
| 13 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 5797.99 |
| 14 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6517.18 |
| 15 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 15942.75 |
| 16 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | 7886.03 |
| 17 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | 13540.72 |
| 18 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | 8438.39 |
| 19 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 4190.64 |
| 20 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 6404.65 |
| 21 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | 18052.33 |
| 22 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | 14787.36 |
| 23 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | 15826.73 |
| DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
| 1 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | N/A | N/A | 538342.18 | 1836899.77 | 10.98 | 3.05 | 3.20 | 3.19 | 3.36 | 10.41 | 10.93 | 10.87 | 11.47 | 32.8007 | 26.1748 | 17.5743 | 6.9531 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | 30211.0 | 10.79 | 10.79 | |||
| 2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | 54073.8 | 10.61 | 10.61 |
| Zone Name | # Surfaces | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 11 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 12 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | 10 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 11 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 12 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 11 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 12 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | 10 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 11 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 12 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 11 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 12 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | 11 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 11 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 12 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | 10 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | 15 |
| 18 | LOBBY_ZN_1_FLR_1 | 11 |
| 19 | MECH_ZN_1_FLR_1 | 10 |
| 20 | BATH_ZN_1_FLR_1 | 9 |
| 21 | OFFICES_ZN_1_FLR_1 | 12 |
| 22 | GYM_ZN_1_FLR_1 | 19 |
| 23 | KITCHEN_ZN_1_FLR_1 | 8 |
| 24 | CAFETERIA_ZN_1_FLR_1 | 12 |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 32.37 | 44.00 | 32.37 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 180.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 180.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 4 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | Door | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 5 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 8 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 9 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 10 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 11 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 12 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 161.46 | 212.00 | 161.46 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 15 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | Window | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 16 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | Door | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 17 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | Door | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 18 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 19 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 21 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 22 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 23 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 24 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 26 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 90.00 | 90.00 | 3.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 27 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 28 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 9.36 | 12.00 | 9.36 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 30 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | Window | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.64 | 2.64 | 2.64 | 270.00 | 90.00 | 2.90 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 31 | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.980E-002 | 1.971E-002 | 192.00 | 192.00 | 192.00 | 270.00 | 180.00 | 3.00 | 64.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 32 | CORRIDOR_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 192.00 | 192.00 | 192.00 | 90.00 | 0.00 | 3.00 | 64.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 33 | CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 384.00 | 384.00 | 384.00 | 0.00 | 90.00 | 384.00 | 1.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 34 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 35 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 36 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 32.37 | 44.00 | 32.37 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 | ||
| 37 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 0.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 38 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 0.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 |
| 39 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | Door | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | |
| 40 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 42 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 47 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 161.46 | 212.00 | 161.46 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 | ||
| 48 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 49 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 50 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | Window | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 51 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | Door | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 | |
| 52 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | Door | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 53 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 55 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 56 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 57 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 32.37 | 44.00 | 32.37 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 | ||
| 58 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 180.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 |
| 59 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 180.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.61 | 0.39 | 4 |
| 60 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | Door | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 | |
| 61 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 63 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 65 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 66 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 67 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 68 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 161.46 | 212.00 | 161.46 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 | ||
| 69 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 70 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 71 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | Window | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 72 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | Door | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 73 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | Door | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 | |
| 74 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 76 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 77 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 78 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 79 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 80 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 82 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 90.00 | 90.00 | 3.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 85 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 9.36 | 12.00 | 9.36 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 86 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | Window | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.64 | 2.64 | 2.64 | 270.00 | 90.00 | 2.90 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 87 | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.980E-002 | 1.971E-002 | 192.00 | 192.00 | 192.00 | 270.00 | 180.00 | 3.00 | 64.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 88 | CORRIDOR_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 192.00 | 192.00 | 192.00 | 90.00 | 0.00 | 3.00 | 64.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 89 | CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 384.00 | 384.00 | 384.00 | 0.00 | 90.00 | 384.00 | 1.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 90 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 91 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 32.37 | 44.00 | 32.37 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.56 | 0.44 | 4 | ||
| 93 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 0.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 94 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 0.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 |
| 95 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | Door | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 | |
| 96 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 99 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 100 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 101 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 103 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 161.46 | 212.00 | 161.46 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 | ||
| 104 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 |
| 105 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 106 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | Window | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 107 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | Door | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 108 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | Door | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | |
| 109 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 32.37 | 44.00 | 32.37 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.56 | 0.44 | 4 | ||
| 114 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 180.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 |
| 115 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 180.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 |
| 116 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | Door | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.58 | 0.42 | 4 | |
| 117 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 119 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 120 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 121 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 122 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 123 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 124 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 161.46 | 212.00 | 161.46 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 | ||
| 125 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 126 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 127 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | Window | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 |
| 128 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | Door | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | |
| 129 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | Door | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 130 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 131 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 134 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 135 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 136 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 137 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 90.00 | 90.00 | 3.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 139 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 72.00 | 72.00 | 72.00 | 0.00 | 90.00 | 18.00 | 4.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 140.00 | 140.00 | 140.00 | 0.00 | 90.00 | 35.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 141 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 9.36 | 12.00 | 9.36 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | Window | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.64 | 2.64 | 2.64 | 270.00 | 90.00 | 2.90 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 144 | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.980E-002 | 1.971E-002 | 192.00 | 192.00 | 192.00 | 270.00 | 180.00 | 3.00 | 64.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 145 | CORRIDOR_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 192.00 | 192.00 | 192.00 | 90.00 | 0.00 | 3.00 | 64.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 146 | CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 384.00 | 384.00 | 384.00 | 0.00 | 90.00 | 384.00 | 1.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 147 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 148 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 32.40 | 44.00 | 32.40 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 150 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 0.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 151 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.43 | 8.43 | 8.43 | 0.00 | 90.00 | 8.43 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 152 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | Door | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 153 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 154 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 155 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 156 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 157 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 158 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 140.00 | 140.00 | 140.00 | 180.00 | 90.00 | 35.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 159 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 105.30 | 140.00 | 105.30 | 0.00 | 90.00 | 35.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 10.27 | 10.27 | 10.27 | 0.00 | 90.00 | 10.82 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 162 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 10.27 | 10.27 | 10.27 | 0.00 | 90.00 | 10.82 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 163 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | Window | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 10.27 | 10.27 | 10.27 | 0.00 | 90.00 | 10.82 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 164 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | Door | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 165 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | Door | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 166 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 315.00 | 315.00 | 315.00 | 270.00 | 180.00 | 9.00 | 35.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 168 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 315.00 | 315.00 | 315.00 | 90.00 | 0.00 | 9.00 | 35.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 169 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 630.00 | 630.00 | 630.00 | 0.00 | 90.00 | 630.00 | 1.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 170 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 72.00 | 72.00 | 72.00 | 180.00 | 90.00 | 18.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 171 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 172 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 54.21 | 72.00 | 54.21 | 0.00 | 90.00 | 18.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 173 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.16 | 1.16 | 1.16 | 0.00 | 90.00 | 1.22 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 174 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 14.68 | 14.68 | 14.68 | 0.00 | 90.00 | 15.46 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | Door | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 176 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 162.00 | 162.00 | 162.00 | 270.00 | 180.00 | 9.00 | 18.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 178 | COMPUTER_CLASS_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 162.00 | 162.00 | 162.00 | 90.00 | 0.00 | 9.00 | 18.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 179 | COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 324.00 | 324.00 | 324.00 | 0.00 | 90.00 | 324.00 | 1.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 180 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 180.00 | 90.00 | 13.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 181 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 168.00 | 168.00 | 168.00 | 90.00 | 90.00 | 42.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 0.00 | 90.00 | 13.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 183 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 26.13 | 36.00 | 26.13 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | ||
| 187 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | Window | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.26 | 1.26 | 1.26 | 270.00 | 90.00 | 1.22 | 1.03 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.73 | 0.27 | 4 |
| 188 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | Window | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 6.66 | 6.66 | 6.66 | 270.00 | 90.00 | 6.46 | 1.03 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 189 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | Door | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.71 | 0.29 | 4 | |
| 190 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 191 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR | 2.090E-002 | 2.079E-002 | 546.00 | 546.00 | 546.00 | 270.00 | 180.00 | 42.00 | 13.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 193 | MAIN_CORRIDOR_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 546.00 | 546.00 | 546.00 | 90.00 | 0.00 | 42.00 | 13.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 194 | MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1092.00 | 1092.00 | 1092.00 | 0.00 | 90.00 | 1092.00 | 1.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 195 | LOBBY_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 57.33 | 76.00 | 57.33 | 180.00 | 90.00 | 19.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 196 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | LOBBY_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.15 | 1.15 | 1.15 | 180.00 | 90.00 | 1.22 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 197 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | LOBBY_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.57 | 15.57 | 15.57 | 180.00 | 90.00 | 16.46 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 198 | LOBBY_ZN_1_FLR_1_WALL_1_DOOR | Door | LOBBY_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 199 | LOBBY_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | OFFICES_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | LOBBY_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 6.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | LOBBY_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 0.00 | 90.00 | 13.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | LOBBY_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 203 | LOBBY_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 171.00 | 171.00 | 171.00 | 270.00 | 180.00 | 9.00 | 19.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 204 | LOBBY_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 171.00 | 171.00 | 171.00 | 90.00 | 0.00 | 9.00 | 19.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 205 | LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 342.00 | 342.00 | 342.00 | 0.00 | 90.00 | 342.00 | 1.00 | 0.00 | LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 206 | MECH_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 180.00 | 90.00 | 6.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | MECH_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 48.00 | 48.00 | 48.00 | 90.00 | 90.00 | 12.00 | 4.00 | 0.00 | OFFICES_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 208 | MECH_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.00 | 68.00 | 68.00 | 90.00 | 90.00 | 17.00 | 4.00 | 0.00 | GYM_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | MECH_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 32.00 | 32.00 | 32.00 | 90.00 | 90.00 | 8.00 | 4.00 | 0.00 | KITCHEN_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | MECH_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.00 | 20.00 | 20.00 | 90.00 | 90.00 | 5.00 | 4.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | MECH_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 6.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | MECH_ZN_1_FLR_1_WALL_7 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 168.00 | 168.00 | 168.00 | 270.00 | 90.00 | 42.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | MECH_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MECH_ZN_1_FLR_1_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 252.00 | 252.00 | 252.00 | 270.00 | 180.00 | 42.00 | 6.00 | 0.00 | MECH_ZN_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 214 | MECH_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 252.00 | 252.00 | 252.00 | 90.00 | 0.00 | 42.00 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 215 | MECH_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 504.00 | 504.00 | 504.00 | 0.00 | 90.00 | 504.00 | 1.00 | 0.00 | MECH_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 216 | BATH_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 180.00 | 90.00 | 13.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 217 | BATH_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 180.00 | 90.00 | 6.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 218 | BATH_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.00 | 40.00 | 40.00 | 90.00 | 90.00 | 10.00 | 4.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | BATH_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 76.00 | 76.00 | 76.00 | 0.00 | 90.00 | 19.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | BATH_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 31.20 | 40.00 | 31.20 | 270.00 | 90.00 | 10.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | ||
| 221 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | Window | BATH_ZN_1_FLR_1_WALL_5 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.80 | 8.80 | 8.80 | 270.00 | 90.00 | 9.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 222 | BATH_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | BATH_ZN_1_FLR_1_FLOOR_FFACTOR | 6.720E-002 | 6.612E-002 | 190.00 | 190.00 | 190.00 | 270.00 | 180.00 | 10.00 | 19.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 223 | BATH_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 190.00 | 190.00 | 190.00 | 90.00 | 0.00 | 10.00 | 19.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 224 | BATH_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 380.00 | 380.00 | 380.00 | 0.00 | 90.00 | 380.00 | 1.00 | 0.00 | BATH_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 225 | OFFICES_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 63.57 | 84.00 | 63.57 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | OFFICES_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.14 | 1.14 | 1.14 | 180.00 | 90.00 | 1.22 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 227 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | OFFICES_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 17.34 | 17.34 | 17.34 | 180.00 | 90.00 | 18.46 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 228 | OFFICES_ZN_1_FLR_1_WALL_1_DOOR | Door | OFFICES_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 229 | OFFICES_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 65.52 | 84.00 | 65.52 | 90.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 230 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | Window | OFFICES_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 18.48 | 18.48 | 18.48 | 90.00 | 90.00 | 20.90 | 0.88 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 231 | OFFICES_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | GYM_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | OFFICES_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 48.00 | 48.00 | 48.00 | 270.00 | 90.00 | 12.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | OFFICES_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 234 | OFFICES_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR | 0.123 | 0.119 | 441.00 | 441.00 | 441.00 | 270.00 | 180.00 | 21.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 235 | OFFICES_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 441.00 | 441.00 | 441.00 | 90.00 | 0.00 | 21.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 236 | OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 882.00 | 882.00 | 882.00 | 0.00 | 90.00 | 882.00 | 1.00 | 0.00 | OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 237 | GYM_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | OFFICES_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | GYM_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 51.09 | 68.00 | 51.09 | 90.00 | 90.00 | 17.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | Window | GYM_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.17 | 1.17 | 1.17 | 90.00 | 90.00 | 1.22 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 240 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | Window | GYM_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 13.79 | 13.79 | 13.79 | 90.00 | 90.00 | 14.46 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 241 | GYM_ZN_1_FLR_1_WALL_2_DOOR | Door | GYM_ZN_1_FLR_1_WALL_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 242 | GYM_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | KITCHEN_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 243 | GYM_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.00 | 68.00 | 68.00 | 270.00 | 90.00 | 17.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 244 | GYM_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | GYM_ZN_1_FLR_1_FLOOR_FFACTOR | 6.074E-002 | 5.986E-002 | 357.00 | 357.00 | 357.00 | 270.00 | 180.00 | 17.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 245 | GYM_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 343.62 | 357.00 | 343.62 | 90.00 | 0.00 | 17.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 246 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 247 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 248 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 249 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 250 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 251 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 252 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 253 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 254 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 255 | GYM_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 714.00 | 714.00 | 714.00 | 0.00 | 90.00 | 714.00 | 1.00 | 0.00 | GYM_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 256 | KITCHEN_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | GYM_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 257 | KITCHEN_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 24.96 | 32.00 | 24.96 | 90.00 | 90.00 | 8.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 258 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | Window | KITCHEN_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.04 | 7.04 | 7.04 | 90.00 | 90.00 | 7.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 259 | KITCHEN_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 260 | KITCHEN_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 32.00 | 32.00 | 32.00 | 270.00 | 90.00 | 8.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 261 | KITCHEN_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR | 6.074E-002 | 5.986E-002 | 168.00 | 168.00 | 168.00 | 270.00 | 180.00 | 8.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 262 | KITCHEN_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 168.00 | 168.00 | 168.00 | 90.00 | 0.00 | 8.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 263 | KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 336.00 | 336.00 | 336.00 | 0.00 | 90.00 | 336.00 | 1.00 | 0.00 | KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 264 | CAFETERIA_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | KITCHEN_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 265 | CAFETERIA_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 44.85 | 60.00 | 44.85 | 90.00 | 90.00 | 15.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 266 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | Window | CAFETERIA_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.18 | 1.18 | 1.18 | 90.00 | 90.00 | 1.22 | 0.96 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 267 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | Window | CAFETERIA_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 12.02 | 12.02 | 12.02 | 90.00 | 90.00 | 12.46 | 0.96 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 268 | CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | Door | CAFETERIA_ZN_1_FLR_1_WALL_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 269 | CAFETERIA_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 65.52 | 84.00 | 65.52 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.54 | 0.46 | 4 | ||
| 270 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | Window | CAFETERIA_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 18.48 | 18.48 | 18.48 | 0.00 | 90.00 | 20.90 | 0.88 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.54 | 0.46 | 4 |
| 271 | CAFETERIA_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.00 | 40.00 | 40.00 | 270.00 | 90.00 | 10.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 272 | CAFETERIA_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.00 | 20.00 | 20.00 | 270.00 | 90.00 | 5.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 273 | CAFETERIA_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR | 0.148 | 0.143 | 315.00 | 315.00 | 315.00 | 270.00 | 180.00 | 15.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 274 | CAFETERIA_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 315.00 | 315.00 | 315.00 | 90.00 | 0.00 | 15.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 275 | CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 630.00 | 630.00 | 630.00 | 0.00 | 90.00 | 630.00 | 1.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 276 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 76.00 | 76.00 | 76.00 | 180.00 | 90.00 | 19.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 277 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 63.57 | 84.00 | 63.57 | 90.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.54 | 0.46 | 4 | ||
| 278 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | Window | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.14 | 1.14 | 1.14 | 90.00 | 90.00 | 1.22 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.69 | 0.31 | 4 |
| 279 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | Window | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 17.33 | 17.33 | 17.33 | 90.00 | 90.00 | 18.46 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.53 | 0.47 | 4 |
| 280 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | Door | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 281 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 59.28 | 76.00 | 59.28 | 0.00 | 90.00 | 19.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 282 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | Window | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 16.72 | 16.72 | 16.72 | 0.00 | 90.00 | 18.90 | 0.88 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 283 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 284 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 285 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 286 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR | 0.129 | 0.125 | 399.00 | 399.00 | 399.00 | 270.00 | 180.00 | 21.00 | 19.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 287 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 399.00 | 399.00 | 399.00 | 90.00 | 0.00 | 21.00 | 19.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 288 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 798.00 | 798.00 | 798.00 | 0.00 | 90.00 | 798.00 | 1.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1878171716 | 0.1786033139 | Pass | Pass | 3.8434619238 | 11.0263391528 | Pass | Pass |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.7665803194E-002 | 7.4927975624E-002 | Pass | Pass | 3.9322701849 | 11.2972948711 | Pass | Pass |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.4694241255E-002 | 8.7919939315E-002 | Pass | Pass | 7.8215050407 | 24.3906802478 | Pass | Pass |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1909343933 | 0.1813639617 | Pass | Pass | 3.8611771677 | 11.0982896971 | Pass | Pass |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.9231306060E-002 | 7.2603156385E-002 | Pass | Pass | 3.7667471589 | 9.8468052785 | Pass | Pass |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1879406211 | 0.1783117001 | Pass | Pass | 3.8080998524 | 10.8982719343 | Pass | Pass |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.6274858711E-002 | 7.2815993815E-002 | Pass | Pass | 3.8474478897 | 10.9403969012 | Pass | Pass |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.4602621007E-002 | 8.7891859017E-002 | Pass | Pass | 7.8570109629 | 24.5219892223 | Pass | Pass |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1910452361 | 0.1813269340 | Pass | Pass | 3.8646424141 | 11.1117187982 | Pass | Pass |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.9308742049E-002 | 7.2727753300E-002 | Pass | Pass | 3.7979066244 | 9.9454584009 | Pass | Pass |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1874666894 | 0.1780008521 | Pass | Pass | 3.8180952257 | 10.9445440830 | Pass | Pass |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.6188813563E-002 | 7.2819937867E-002 | Pass | Pass | 3.8937030081 | 11.0573661961 | Pass | Pass |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.2720523580E-002 | 8.6072571650E-002 | Pass | Pass | 7.7916362999 | 24.2857193486 | Pass | Pass |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1919699187 | 0.1821791254 | Pass | Pass | 3.8265547378 | 10.9637287420 | Pass | Pass |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.3052156219E-002 | 7.6548978554E-002 | Pass | Pass | 3.7045887244 | 9.8738116629 | Pass | Pass |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.0583029155E-002 | 4.2980497597E-002 | Pass | Pass | 5.0435895454 | 19.6159722784 | Pass | Pass |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.0460276436E-002 | 5.4005637824E-002 | Pass | Pass | 64.6886684337 | 468.2673687968 | Pass | Pass |
| 18 | LOBBY_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1610070631 | 0.1460440311 | Pass | Pass | 5.4979538342 | 15.9507702665 | Pass | Pass |
| 19 | MECH_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.6826444021E-002 | 2.6776060487E-002 | Pass | Pass | 0.4753654275 | 0.6954505385 | Pass | Pass |
| 20 | BATH_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.9791434096E-002 | 8.8592477439E-002 | Pass | Pass | 7.5043544061 | 21.5915015213 | Pass | Pass |
| 21 | OFFICES_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.4420450329E-002 | 8.1509504641E-002 | Pass | Pass | 61.8518602784 | 669.8906651872 | Pass | Pass |
| 22 | GYM_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.3224131926E-002 | 3.5303177398E-002 | Pass | Pass | 0.4454263716 | 0.5542740526 | Pass | Pass |
| 23 | KITCHEN_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 5.9720377242E-002 | 0.1650418233 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 24 | CAFETERIA_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 1.2277434903E-002 | 1.1975193663E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.8986238546E-002 | 5.3271013733E-002 | Pass | Pass | 9.9755935475 | 47.9841565214 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 9150.23 | 169.85 | 1483.62 | 5248.90 | 1118.75 | 17171.38 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
| SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 0.00 | 0 | |||
| Feb | 0.00 | 0 | |||
| Mar | 22.00 | 23 | |||
| Apr | 0.00 | 0 | |||
| May | 0.00 | 0 | |||
| Jun | 16.00 | 20 | |||
| Jul | 0.00 | 0 | |||
| Aug | 24.00 | 18 | |||
| Sep | 12.00 | 15 | |||
| Oct | 61.00 | 41 | |||
| Nov | 0.00 | 0 | |||
| Dec | 45.00 | 41 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 44.00 | 32.37 | 180.00 | 90.00 | S |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 212.00 | 161.46 | 180.00 | 90.00 | S |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 12.00 | 9.36 | 270.00 | 90.00 | W |
| CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.020 | 0.020 | 192.00 | 192.00 | 270.00 | 180.00 | |
| CORRIDOR_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 192.00 | 192.00 | 90.00 | 0.00 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 44.00 | 32.37 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 212.00 | 161.46 | 0.00 | 90.00 | N |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 44.00 | 32.37 | 180.00 | 90.00 | S |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 212.00 | 161.46 | 180.00 | 90.00 | S |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 12.00 | 9.36 | 270.00 | 90.00 | W |
| CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.020 | 0.020 | 192.00 | 192.00 | 270.00 | 180.00 | |
| CORRIDOR_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 192.00 | 192.00 | 90.00 | 0.00 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 44.00 | 32.37 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 212.00 | 161.46 | 0.00 | 90.00 | N |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 44.00 | 32.37 | 180.00 | 90.00 | S |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 212.00 | 161.46 | 180.00 | 90.00 | S |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 12.00 | 9.36 | 270.00 | 90.00 | W |
| CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.020 | 0.020 | 192.00 | 192.00 | 270.00 | 180.00 | |
| CORRIDOR_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 192.00 | 192.00 | 90.00 | 0.00 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 44.00 | 32.40 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 140.00 | 105.30 | 0.00 | 90.00 | N |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 315.00 | 315.00 | 270.00 | 180.00 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 315.00 | 315.00 | 90.00 | 0.00 | |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 72.00 | 54.21 | 0.00 | 90.00 | N |
| COMPUTER_CLASS_ZN_1_FLR_1_FLOOR | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 162.00 | 162.00 | 270.00 | 180.00 | |
| COMPUTER_CLASS_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 162.00 | 162.00 | 90.00 | 0.00 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 36.00 | 26.13 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.021 | 0.021 | 546.00 | 546.00 | 270.00 | 180.00 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 546.00 | 546.00 | 90.00 | 0.00 | |
| LOBBY_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 76.00 | 57.33 | 180.00 | 90.00 | S |
| LOBBY_ZN_1_FLR_1_FLOOR | LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 171.00 | 171.00 | 270.00 | 180.00 | |
| LOBBY_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 171.00 | 171.00 | 90.00 | 0.00 | |
| MECH_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 252.00 | 252.00 | 90.00 | 0.00 | |
| BATH_ZN_1_FLR_1_WALL_5 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 40.00 | 31.20 | 270.00 | 90.00 | W |
| BATH_ZN_1_FLR_1_FLOOR | BATH_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.066 | 0.067 | 190.00 | 190.00 | 270.00 | 180.00 | |
| BATH_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 190.00 | 190.00 | 90.00 | 0.00 | |
| OFFICES_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 84.00 | 63.57 | 180.00 | 90.00 | S |
| OFFICES_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 84.00 | 65.52 | 90.00 | 90.00 | E |
| OFFICES_ZN_1_FLR_1_FLOOR | OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.120 | 0.123 | 441.00 | 441.00 | 270.00 | 180.00 | |
| OFFICES_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 441.00 | 441.00 | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 68.00 | 51.09 | 90.00 | 90.00 | E |
| GYM_ZN_1_FLR_1_FLOOR | GYM_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.060 | 0.061 | 357.00 | 357.00 | 270.00 | 180.00 | |
| GYM_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 357.00 | 343.62 | 90.00 | 0.00 | |
| KITCHEN_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 32.00 | 24.96 | 90.00 | 90.00 | E |
| KITCHEN_ZN_1_FLR_1_FLOOR | KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.060 | 0.061 | 168.00 | 168.00 | 270.00 | 180.00 | |
| KITCHEN_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 168.00 | 168.00 | 90.00 | 0.00 | |
| CAFETERIA_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 60.00 | 44.85 | 90.00 | 90.00 | E |
| CAFETERIA_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 84.00 | 65.52 | 0.00 | 90.00 | N |
| CAFETERIA_ZN_1_FLR_1_FLOOR | CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.144 | 0.148 | 315.00 | 315.00 | 270.00 | 180.00 | |
| CAFETERIA_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 315.00 | 315.00 | 90.00 | 0.00 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 84.00 | 63.57 | 90.00 | 90.00 | E |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 76.00 | 59.28 | 0.00 | 90.00 | N |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.127 | 0.129 | 399.00 | 399.00 | 270.00 | 180.00 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 399.00 | 399.00 | 90.00 | 0.00 |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 90.00 | 90.00 | E |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 90.00 | 90.00 | E |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 90.00 | 90.00 | E |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 72.00 | 72.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 140.00 | 140.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 140.00 | 140.00 | 180.00 | 90.00 | S |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 72.00 | 72.00 | 180.00 | 90.00 | S |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 180.00 | 90.00 | S |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 168.00 | 168.00 | 90.00 | 90.00 | E |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 0.00 | 90.00 | N |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 270.00 | 90.00 | W |
| LOBBY_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| LOBBY_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 0.00 | 90.00 | N |
| LOBBY_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 0.00 | 90.00 | N |
| LOBBY_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MECH_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 180.00 | 90.00 | S |
| MECH_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 48.00 | 48.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 68.00 | 68.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 32.00 | 32.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 20.00 | 20.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 0.00 | 90.00 | N |
| MECH_ZN_1_FLR_1_WALL_7 | INT_WALL | 0.30 | 2.511 | 6.299 | 168.00 | 168.00 | 270.00 | 90.00 | W |
| MECH_ZN_1_FLR_1_FLOOR | MECH_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 252.00 | 252.00 | 270.00 | 180.00 | |
| BATH_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 180.00 | 90.00 | S |
| BATH_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 180.00 | 90.00 | S |
| BATH_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 40.00 | 40.00 | 90.00 | 90.00 | E |
| BATH_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 76.00 | 76.00 | 0.00 | 90.00 | N |
| OFFICES_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 0.00 | 90.00 | N |
| OFFICES_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 48.00 | 48.00 | 270.00 | 90.00 | W |
| OFFICES_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| GYM_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 180.00 | 90.00 | S |
| GYM_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 0.00 | 90.00 | N |
| GYM_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 68.00 | 68.00 | 270.00 | 90.00 | W |
| KITCHEN_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 180.00 | 90.00 | S |
| KITCHEN_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 0.00 | 90.00 | N |
| KITCHEN_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 32.00 | 32.00 | 270.00 | 90.00 | W |
| CAFETERIA_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 180.00 | 90.00 | S |
| CAFETERIA_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 40.00 | 40.00 | 270.00 | 90.00 | W |
| CAFETERIA_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 20.00 | 20.00 | 270.00 | 90.00 | W |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 76.00 | 76.00 | 180.00 | 90.00 | S |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 270.00 | 90.00 | W |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 384.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 384.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 384.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 630.00 | 0.00 | 90.00 | N | ||
| COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 324.00 | 0.00 | 90.00 | N | ||
| MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1092.00 | 0.00 | 90.00 | N | ||
| LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 342.00 | 0.00 | 90.00 | N | ||
| MECH_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 504.00 | 0.00 | 90.00 | N | ||
| BATH_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 380.00 | 0.00 | 90.00 | N | ||
| OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 882.00 | 0.00 | 90.00 | N | ||
| GYM_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 714.00 | 0.00 | 90.00 | N | ||
| KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 336.00 | 0.00 | 90.00 | N | ||
| CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 630.00 | 0.00 | 90.00 | N | ||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 798.00 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.64 | 0.00 | 0.00 | 2.64 | 2.64 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | 270.00 | 90.00 | W | |||||||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.64 | 0.00 | 0.00 | 2.64 | 2.64 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | 270.00 | 90.00 | W | |||||||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.64 | 0.00 | 0.00 | 2.64 | 2.64 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | 270.00 | 90.00 | W | |||||||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.43 | 0.00 | 0.00 | 8.43 | 8.43 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 10.27 | 0.00 | 0.00 | 10.27 | 10.27 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 10.27 | 0.00 | 0.00 | 10.27 | 10.27 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 10.27 | 0.00 | 0.00 | 10.27 | 10.27 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.16 | 0.00 | 0.00 | 1.16 | 1.16 | 3.241 | 0.391 | 0.431 | No | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 14.68 | 0.00 | 0.00 | 14.68 | 14.68 | 3.241 | 0.391 | 0.431 | No | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.26 | 0.00 | 0.00 | 1.26 | 1.26 | 3.241 | 0.391 | 0.431 | No | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | 270.00 | 90.00 | W | |||||||
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 6.66 | 0.00 | 0.00 | 6.66 | 6.66 | 3.241 | 0.391 | 0.431 | No | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | 270.00 | 90.00 | W | |||||||
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.15 | 0.00 | 0.00 | 1.15 | 1.15 | 3.241 | 0.391 | 0.431 | No | LOBBY_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.57 | 0.00 | 0.00 | 15.57 | 15.57 | 3.241 | 0.391 | 0.431 | No | LOBBY_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.80 | 0.00 | 0.00 | 8.80 | 8.80 | 3.241 | 0.391 | 0.431 | No | BATH_ZN_1_FLR_1_WALL_5 | 270.00 | 90.00 | W | |||||||
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.14 | 0.00 | 0.00 | 1.14 | 1.14 | 3.241 | 0.391 | 0.431 | No | OFFICES_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 17.34 | 0.00 | 0.00 | 17.34 | 17.34 | 3.241 | 0.391 | 0.431 | No | OFFICES_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 18.48 | 0.00 | 0.00 | 18.48 | 18.48 | 3.241 | 0.391 | 0.431 | No | OFFICES_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.17 | 0.00 | 0.00 | 1.17 | 1.17 | 3.241 | 0.391 | 0.431 | No | GYM_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 13.79 | 0.00 | 0.00 | 13.79 | 13.79 | 3.241 | 0.391 | 0.431 | No | GYM_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.04 | 0.00 | 0.00 | 7.04 | 7.04 | 3.241 | 0.391 | 0.431 | No | KITCHEN_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.18 | 0.00 | 0.00 | 1.18 | 1.18 | 3.241 | 0.391 | 0.431 | No | CAFETERIA_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 12.02 | 0.00 | 0.00 | 12.02 | 12.02 | 3.241 | 0.391 | 0.431 | No | CAFETERIA_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 18.48 | 0.00 | 0.00 | 18.48 | 18.48 | 3.241 | 0.391 | 0.431 | No | CAFETERIA_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.14 | 0.00 | 0.00 | 1.14 | 1.14 | 3.241 | 0.391 | 0.431 | No | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 17.33 | 0.00 | 0.00 | 17.33 | 17.33 | 3.241 | 0.391 | 0.431 | No | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 16.72 | 0.00 | 0.00 | 16.72 | 16.72 | 3.241 | 0.391 | 0.431 | No | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| Total or Average | 565.98 | 3.257 | 0.394 | 0.432 | |||||||||||||||||
| North Total or Average | 204.13 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
| Non-North Total or Average | 361.86 | 3.266 | 0.395 | 0.433 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 |
| LOBBY_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LOBBY_ZN_1_FLR_1_WALL_1 |
| OFFICES_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | OFFICES_ZN_1_FLR_1_WALL_1 |
| GYM_ZN_1_FLR_1_WALL_2_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | GYM_ZN_1_FLR_1_WALL_2 |
| CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CAFETERIA_ZN_1_FLR_1_WALL_2 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.89 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.82 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.82 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | 0.75 | 0.97 | 1.00 | 0.88 | 0.99 | 1.00 | 0.00 | 0.97 | 0.82 |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.11 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.11 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.11 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.11 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | 0.75 | 0.97 | 1.00 | 0.88 | 0.99 | 1.00 | 0.05 | 0.97 | 1.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.59 |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | 0.00 | 0.00 | 0.64 | 0.00 | 0.00 | 0.90 | 0.00 | 0.00 | 0.01 |
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | 0.00 | 0.00 | 0.78 | 0.00 | 0.00 | 0.94 | 0.00 | 0.00 | 0.23 |
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.68 | 0.31 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | 0.99 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.47 | 0.84 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORRIDOR_POD_1_ZN_1_FLR_1_LIGHTS | CORRIDOR_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | GENERAL | 5.4810 | 192.00 | 1052.35 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 14.50 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORRIDOR_POD_2_ZN_1_FLR_1_LIGHTS | CORRIDOR_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | GENERAL | 5.4810 | 192.00 | 1052.35 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 14.50 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORRIDOR_POD_3_ZN_1_FLR_1_LIGHTS | CORRIDOR_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | GENERAL | 5.4810 | 192.00 | 1052.35 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 14.50 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 315.00 | 4746.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 65.42 |
| COMPUTER_CLASS_ZN_1_FLR_1_LIGHTS | COMPUTER_CLASS_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | GENERAL | 15.0695 | 162.00 | 2441.25 | LightsWired | LTG_SCH_COMPUTER_ROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 33.64 |
| MAIN_CORRIDOR_ZN_1_FLR_1_LIGHTS | MAIN_CORRIDOR_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | GENERAL | 5.4810 | 546.00 | 2992.63 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 41.24 |
| LOBBY_ZN_1_FLR_1_LIGHTS | LOBBY_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | GENERAL | 13.9931 | 171.00 | 2392.81 | LightsWired | LTG_SCH_LOBBY | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 32.97 |
| MECH_ZN_1_FLR_1_LIGHTS | MECH_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | GENERAL | 16.1458 | 252.00 | 4068.75 | LightsWired | LTG_SCH_MECHANICAL | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 56.07 |
| BATH_ZN_1_FLR_1_LIGHTS | BATH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | GENERAL | 9.6875 | 190.00 | 1840.63 | LightsWired | LTG_SCH_BATH | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 25.37 |
| OFFICES_ZN_1_FLR_1_LIGHTS | OFFICES_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GENERAL | 11.8403 | 441.00 | 5221.57 | LightsWired | LTG_SCH_OFFICE | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 71.96 |
| GYM_ZN_1_FLR_1_LIGHTS | GYM_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | GENERAL | 13.3472 | 357.00 | 4764.96 | LightsWired | LTG_SCH_GYM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 65.67 |
| KITCHEN_ZN_1_FLR_1_LIGHTS | KITCHEN_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | GENERAL | 12.9167 | 168.00 | 2170.00 | LightsWired | LTG_SCH_KITCHEN | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 29.90 |
| CAFETERIA_ZN_1_FLR_1_LIGHTS | CAFETERIA_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | GENERAL | 9.6875 | 315.00 | 3051.57 | LightsWired | LTG_SCH_CAFETERIA | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 42.05 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_LIGHTS | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | GENERAL | 16.6840 | 399.00 | 6656.93 | LightsWired | LTG_SCH_LIBRARY | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 91.74 |
| Interior Lighting Total | 12.8652 | 6871.00 | 88396.96 | 1218.18 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| EXTERIOR_LIGHTS | 5897.73 | AstronomicalClock | - | 83.55 | 83.55 | 92.49 | |
| Exterior Lighting Total | 5897.73 | 92.49 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| HEATSYS1 BOILER | Boiler:HotWater | 295429.77 | 0.75 |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | 559642.04 | 440362.67 | 119279.36 | 0.79 | 3.60 | |||
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31432.26 | 24260.99 | 7171.27 | 0.77 | 3.50 | |||
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 56155.15 | 42327.51 | 13827.64 | 0.75 | 3.40 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| VAV_POD_1 COOLING COIL | 538342.2 | 3.05 | 10.41 | N/A | N/A | 10.98 | |
| PSZ-AC_1:6 COOLING COIL | 30211.0 | 10.79 | 10.79 | ||||
| PSZ-AC_2:7 COOLING COIL | 54073.8 | 10.61 | 10.61 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6829.66 | 6479.17 | - |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25208.11 | 23921.00 | - |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6120.61 | 5806.50 | - |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6827.97 | 6477.56 | - |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25102.16 | 23820.56 | - |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6780.42 | 6432.46 | - |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 24988.48 | 23712.79 | - |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6103.60 | 5790.37 | - |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6831.83 | 6481.22 | - |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25095.30 | 23814.03 | - |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6785.81 | 6437.56 | - |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25033.32 | 23755.29 | - |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6111.64 | 5797.99 | - |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6869.74 | 6517.18 | - |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16800.71 | 15942.75 | - |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8310.13 | 7886.03 | - |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 14273.22 | 13540.72 | - |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8894.87 | 8438.39 | - |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 4416.02 | 4190.64 | - |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 6751.12 | 6404.65 | - |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19028.88 | 18052.33 | - |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15583.28 | 14787.36 | - |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 16682.89 | 15826.73 | - |
| VAV_POD_1 HEATING COIL | Coil:Heating:Fuel | 175923.10 | 0.79 | |
| PSZ-AC_1:6 HEATING COIL | Coil:Heating:Fuel | 60785.56 | 0.80 | |
| PSZ-AC_2:7 HEATING COIL | Coil:Heating:Fuel | 79793.61 | 0.79 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| BATH_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 0.28 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| GYM_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.54 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| KITCHEN_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 2.12 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| CAFETERIA_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.38 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.28 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| VAV_POD_1 FAN | Fan:VariableVolume | 0.62 | 1337.13 | 28.77 | 62036.48 | 2156.31 | 1.00 | 1.11 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 |
| PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.55 | 2582.38 | 1662.00 | 1.00 | 1.26 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
| PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 2.65 | 4291.96 | 1622.12 | 1.00 | 1.22 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 01:40:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002585 | 778.35 | 301156.09 | 0.90 | General |
| SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000105 | 13.47 | 127739.32 | 0.30 | General |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| SWH BOOSTER G WATER HEATER | WaterHeater:Mixed | 0.02 | 6000.00 | 0.80 | 1.09 | 0.99 |
| SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 14.75 | 0.47 |
| DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 538342.18 | 3.05 | 10.41 | 10.98 | 32.8007 | 3.20 | 10.93 | 26.1748 | 3.19 | 10.87 | 17.5743 | 3.36 | 11.47 | 6.9531 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 7972.08 | 9167.90 | 92.61 | 0.592 | 0.681 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 24.00 | 24.00 | 0.00921 | 28.98 | 0.00882 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 33481.96 | 38504.25 | 80.72 | 2.488 | 2.862 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00931 | 29.40 | 0.00882 | 0.897 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 6187.38 | 7115.48 | 37.06 | 0.460 | 0.529 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00886 | 29.09 | 0.00882 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 6687.55 | 7690.68 | 77.68 | 0.497 | 0.572 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 24.00 | 24.00 | 0.00934 | 28.08 | 0.00882 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 26049.51 | 29956.93 | 62.80 | 1.936 | 2.226 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00954 | 29.40 | 0.00882 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 7929.96 | 9119.45 | 92.12 | 0.589 | 0.678 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 24.00 | 24.00 | 0.00921 | 28.98 | 0.00882 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 33132.94 | 38102.88 | 79.88 | 2.462 | 2.832 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00932 | 29.40 | 0.00882 | 0.897 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 6169.17 | 7094.54 | 36.95 | 0.458 | 0.527 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00886 | 29.09 | 0.00882 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 6690.06 | 7693.56 | 77.71 | 0.497 | 0.572 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 24.00 | 24.00 | 0.00934 | 28.08 | 0.00882 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 26059.64 | 29968.58 | 62.83 | 1.937 | 2.227 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00954 | 29.40 | 0.00882 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 7935.18 | 9125.45 | 92.18 | 0.590 | 0.678 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:40:00 | 24.00 | 24.00 | 0.00921 | 28.98 | 0.00882 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 33262.12 | 38251.44 | 80.19 | 2.472 | 2.843 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00932 | 29.40 | 0.00882 | 0.897 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 6225.29 | 7159.08 | 37.29 | 0.463 | 0.532 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00886 | 29.09 | 0.00882 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 6728.50 | 7737.77 | 78.16 | 0.500 | 0.575 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:50:00 | 24.00 | 24.00 | 0.00933 | 28.08 | 0.00882 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 17467.14 | 20087.21 | 63.77 | 1.298 | 1.493 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00953 | 29.40 | 0.00882 | 0.592 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 9680.58 | 11132.67 | 68.72 | 0.719 | 0.827 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 24.00 | 24.00 | 0.00945 | 29.40 | 0.00882 | 0.304 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 13000.37 | 14950.43 | 27.38 | 0.966 | 1.111 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 15:30:00 | 24.00 | 24.00 | 0.00898 | 29.09 | 0.00882 | 0.166 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 8656.22 | 9954.65 | 58.21 | 0.643 | 0.740 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:20:00 | 24.00 | 24.00 | 0.00895 | 29.40 | 0.00882 | 0.096 | 0.00 |
| MECH_ZN_1_FLR_1 | 9281.81 | 10674.08 | 42.36 | 0.690 | 0.793 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00859 | 29.40 | 0.00882 | 0.000 | 0.00 |
| BATH_ZN_1_FLR_1 | 6160.63 | 7084.73 | 37.29 | 0.458 | 0.526 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 16:40:00 | 24.00 | 24.00 | 0.00885 | 28.22 | 0.00882 | 0.000 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 19855.11 | 22833.38 | 51.78 | 1.475 | 1.696 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 24.00 | 24.00 | 0.00876 | 29.40 | 0.00882 | 0.190 | 0.00 |
| GYM_ZN_1_FLR_1 | 21005.07 | 24155.83 | 67.66 | 1.561 | 1.795 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 23.99 | 0.00967 | 29.14 | 0.00882 | 0.544 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 18162.78 | 20887.20 | 124.33 | 1.351 | 1.554 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 24.00 | 23.99 | 0.01052 | 28.46 | 0.00882 | 0.255 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 30923.01 | 35561.46 | 112.89 | 2.301 | 2.646 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 24.00 | 23.98 | 0.01082 | 28.88 | 0.00882 | 1.488 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 20013.96 | 23016.05 | 57.68 | 1.487 | 1.710 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 24.00 | 24.00 | 0.00896 | 29.31 | 0.00882 | 0.345 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 3158.99 | 3948.74 | 39.89 | 0.235 | 0.294 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 9787.87 | 12234.83 | 25.65 | 0.728 | 0.910 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.897 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 2830.45 | 3538.06 | 18.43 | 0.210 | 0.263 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00795 | -4.20 | 0.00269 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 3158.21 | 3947.77 | 39.88 | 0.235 | 0.294 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 9699.82 | 12124.78 | 25.42 | 0.721 | 0.902 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 3136.22 | 3920.28 | 39.60 | 0.233 | 0.291 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 9609.27 | 12011.59 | 25.18 | 0.714 | 0.897 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00776 | -4.20 | 0.00269 | 0.897 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 2822.59 | 3528.23 | 18.38 | 0.210 | 0.262 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00795 | -4.20 | 0.00269 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 3160.00 | 3950.00 | 39.90 | 0.235 | 0.294 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 9707.78 | 12134.72 | 25.44 | 0.722 | 0.902 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 3138.71 | 3923.39 | 39.63 | 0.233 | 0.292 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 9649.29 | 12061.61 | 25.29 | 0.717 | 0.897 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00776 | -4.20 | 0.00269 | 0.897 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 2826.30 | 3532.88 | 18.40 | 0.210 | 0.263 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00795 | -4.20 | 0.00269 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 3177.53 | 3971.91 | 40.12 | 0.236 | 0.295 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00773 | -4.20 | 0.00269 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 6584.55 | 8230.68 | 26.13 | 0.490 | 0.612 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00777 | -4.20 | 0.00269 | 0.592 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 3127.82 | 3909.78 | 24.13 | 0.233 | 0.304 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00775 | -4.20 | 0.00269 | 0.304 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 6600.66 | 8250.83 | 15.11 | 0.491 | 0.613 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00794 | -4.20 | 0.00269 | 0.166 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 4113.95 | 5142.44 | 30.07 | 0.306 | 0.382 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00780 | -4.20 | 0.00269 | 0.096 | 0.00 |
| MECH_ZN_1_FLR_1 | 1664.38 | 2080.47 | 8.26 | 0.124 | 0.155 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:40:00 | 21.00 | 21.00 | 0.00800 | -4.20 | 0.00269 | 0.000 | 0.00 |
| BATH_ZN_1_FLR_1 | 3122.27 | 3902.84 | 20.54 | 0.232 | 0.290 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00786 | -4.20 | 0.00269 | 0.000 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 8801.04 | 11001.30 | 24.95 | 0.654 | 0.818 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00779 | -4.20 | 0.00269 | 0.190 | 0.00 |
| GYM_ZN_1_FLR_1 | 6165.07 | 7706.33 | 21.59 | 0.458 | 0.573 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00788 | -4.20 | 0.00269 | 0.544 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.000 | 0.255 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 23:30:00 | 21.00 | 23.16 | 0.01819 | -4.20 | 0.00269 | 0.255 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 6883.88 | 8604.84 | 27.32 | 0.512 | 1.488 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 21.00 | 21.00 | 0.00778 | -4.20 | 0.00269 | 1.488 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 7716.10 | 9645.13 | 24.17 | 0.574 | 0.717 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 21.00 | 21.00 | 0.00778 | -4.20 | 0.00269 | 0.345 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| VAV_POD_1 | 28.77 | 28.77 | 11.52 | 11.52 | 28.7697 | 12.8290 | 28.7697 | 0.4459 | 0.3000 |
| PSZ-AC_1:6 | 1.55 | 1.55 | 0.25 | 0.25 | 1.5538 | 1.5538 | 1.5538 | 1.0000 | 1.0000 |
| PSZ-AC_2:7 | 2.65 | 2.65 | 1.49 | 1.49 | 2.6459 | 2.6459 | 2.6459 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | 6829.662 | 6829.662 | 0.293602 | 0.00005975 | 159.294 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6829.66 | 6829.66 | 0.293602 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00773051 | 49.2845 | 3948.74 | 0.00 | 6860.99 | 6860.99 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | 25208.105 | 25208.105 | 1.322025 | 0.00022053 | 560.335 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 25208.11 | 25208.11 | 1.322025 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00776781 | 49.5189 | 12234.83 | 0.00 | 25327.43 | 25327.43 |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX | 6120.605 | 6120.605 | 0.263076 | 0.00005355 | 142.763 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6120.61 | 6120.61 | 0.263076 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00795290 | 50.6834 | 3538.06 | 0.00 | 6148.68 | 6148.68 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | 6827.971 | 6827.971 | 0.293529 | 0.00005973 | 159.255 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6827.97 | 6827.97 | 0.293529 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00773045 | 49.2841 | 3947.77 | 0.00 | 6859.29 | 6859.29 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | 25102.157 | 25102.157 | 1.322448 | 0.00021960 | 557.444 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 25102.16 | 25102.16 | 1.322448 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00776579 | 49.5062 | 12124.78 | 0.00 | 25221.02 | 25221.02 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | 6780.424 | 6780.424 | 0.291485 | 0.00005932 | 158.146 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6780.42 | 6780.42 | 0.291485 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772865 | 49.2728 | 3920.28 | 0.00 | 6811.53 | 6811.53 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | 24988.477 | 24988.477 | 1.322403 | 0.00021861 | 554.392 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 24988.48 | 24988.48 | 1.322403 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00776368 | 49.4929 | 12011.59 | 0.00 | 25106.84 | 25106.84 |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX | 6103.604 | 6103.604 | 0.262346 | 0.00005340 | 142.366 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6103.60 | 6103.60 | 0.262346 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00795277 | 50.6826 | 3528.23 | 0.00 | 6131.60 | 6131.60 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | 6831.829 | 6831.829 | 0.293695 | 0.00005977 | 159.345 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6831.83 | 6831.83 | 0.293695 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00773059 | 49.2850 | 3950.00 | 0.00 | 6863.17 | 6863.17 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | 25095.301 | 25095.301 | 1.320735 | 0.00021954 | 557.412 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 25095.30 | 25095.30 | 1.320735 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00776598 | 49.5074 | 12134.72 | 0.00 | 25214.12 | 25214.12 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | 6785.807 | 6785.807 | 0.291717 | 0.00005937 | 158.271 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6785.81 | 6785.81 | 0.291717 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00772886 | 49.2741 | 3923.39 | 0.00 | 6816.94 | 6816.94 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | 25033.318 | 25033.318 | 1.321873 | 0.00021900 | 555.644 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 25033.32 | 25033.32 | 1.321873 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00776462 | 49.4988 | 12061.61 | 0.00 | 25151.87 | 25151.87 |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX | 6111.643 | 6111.643 | 0.262691 | 0.00005347 | 142.554 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6111.64 | 6111.64 | 0.262691 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00795283 | 50.6830 | 3532.88 | 0.00 | 6139.68 | 6139.68 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | 6869.737 | 6869.737 | 0.295324 | 0.00006010 | 160.229 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6869.74 | 6869.74 | 0.295324 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00773200 | 49.2939 | 3971.91 | 0.00 | 6901.25 | 6901.25 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | 16800.715 | 16800.715 | 0.873311 | 0.00014698 | 374.163 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 16800.71 | 16800.71 | 0.873311 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00777189 | 49.5446 | 8230.68 | 0.00 | 16880.19 | 16880.19 |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX | 8310.134 | 8310.134 | 0.448424 | 0.00007270 | 183.624 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8310.13 | 8310.13 | 0.448424 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00775390 | 49.4313 | 3909.78 | 0.00 | 8349.55 | 8349.55 |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX | 14273.221 | 14273.221 | 0.613499 | 0.00012487 | 332.921 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 14273.22 | 14273.22 | 0.613499 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00793955 | 50.5994 | 8250.83 | 0.00 | 14338.70 | 14338.70 |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | LOBBY_ZN_1_FLR_1 VAV BOX | 8894.870 | 8894.870 | 0.382364 | 0.00007782 | 207.466 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 8894.87 | 8894.87 | 0.382364 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00780068 | 49.7258 | 5142.44 | 0.00 | 8935.68 | 8935.68 |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_ZN_1_FLR_1 VAV BOX | 4416.019 | 4416.019 | 0.237895 | 0.00003863 | 97.612 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:40:00 | 4416.02 | 4416.02 | 0.237895 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00800000 | 50.9797 | 2080.47 | 0.00 | 4436.96 | 4436.96 |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 6751.119 | 6751.119 | 0.290198 | 0.00005906 | 157.467 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 6751.12 | 6751.12 | 0.290198 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00786016 | 50.1000 | 3902.84 | 0.00 | 6782.09 | 6782.09 |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | OFFICES_ZN_1_FLR_1 VAV BOX | 19028.882 | 19028.882 | 0.817999 | 0.00016647 | 443.833 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 19028.88 | 19028.88 | 0.817999 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00779430 | 49.6856 | 11001.30 | 0.00 | 19116.18 | 19116.18 |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 15583.282 | 15583.282 | 0.802525 | 0.00013633 | 347.750 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | 15583.28 | 15583.28 | 0.802525 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00787915 | 50.2197 | 7706.33 | 0.00 | 15656.94 | 15656.94 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 16682.888 | 16682.888 | 0.717160 | 0.00014595 | 389.114 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 16682.89 | 16682.89 | 0.717160 | 12.89 | 11.51 | 0.00800000 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 0.0000 | 21.00 | 0.00777729 | 49.5786 | 9645.13 | 0.00 | 16759.42 | 16759.42 |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | VAV_POD_1 | 559642.037 | 440362.673 | 28.769692 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | 553624.03 | 502456.00 | 28.769692 | 26.00 | 17.43 | 0.00909614 | 11.11 | 11.11 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 37.1339 | 24.00 | 0.00925837 | 49.0788 | 336651.49 | 0.00 | 561260.64 | 437427.13 |
| VAV_POD_1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | VAV_POD_1 | 175923.103 | 175923.103 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 01:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | 175923.10 | 175923.10 | 8.630908 | -4.20 | -4.20 | 0.00269032 | 12.89 | 11.51 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 123.7796 | 21.00 | 0.00779729 | 49.7050 | 123656.78 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:6 | 31432.260 | 24260.990 | 1.553780 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | 15716.13 | 11846.41 | 1.035853 | 24.69 | 17.92 | 0.01024202 | 11.52 | 11.44 | 0.00850000 | 28.46 | 0.00882000 | 18.03 | 24.5994 | 23.99 | 0.01052097 | 55.6944 | 18162.78 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_1:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:6 | 60785.558 | 60785.558 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 60785.56 | 60785.56 | 1.553783 | -0.69 | -0.69 | 0.01585941 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 16.3996 | 23.38 | 0.01844274 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:7 | 56155.150 | 42327.506 | 2.645890 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 28077.58 | 23592.41 | 1.763927 | 27.08 | 18.27 | 0.00969372 | 11.55 | 11.45 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 84.3677 | 23.98 | 0.01085556 | 57.4473 | 30552.67 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_2:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:7 | 79793.610 | 79793.610 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 01:40:00 | 79793.61 | 79793.61 | 2.645889 | 6.83 | 5.22 | 0.00491503 | 32.11 | 18.58 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 56.2452 | 21.00 | 0.00777480 | 49.5635 | 6870.76 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6829.662 | 6829.662 | 0.293602 | 0.00005975 | 159.294 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 2.2662 | 2.311772 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6829.66 | 6829.66 | 1.0000 | 0.34850238 | 0.293602 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.05974277 | 60.00 | 32.22 | 27.78 | 0.000 | 6829.66 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00773051 | 21.00 | 0.00773051 | 49.2845 | 3948.74 | 0.00 | 6860.99 | 6860.99 | 0.34850238 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52746.9 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25208.105 | 25208.105 | 1.322025 | 0.00022053 | 560.335 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 8.3644 | 8.532689 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 25208.11 | 25208.11 | 1.0000 | 1.56923121 | 1.322025 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.22050900 | 60.00 | 32.22 | 27.78 | 0.000 | 25208.11 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00776781 | 21.00 | 0.00776781 | 49.5189 | 12234.83 | 0.00 | 25327.43 | 25327.43 | 1.56923121 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.63 | 17.58 | 0.00800000 | 49199.9 | |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX | CORRIDOR_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6120.605 | 6120.605 | 0.263076 | 0.00005355 | 142.763 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 2.0309 | 2.071763 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6120.61 | 6120.61 | 1.0000 | 0.31226938 | 0.263076 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.05354026 | 60.00 | 32.22 | 27.78 | 0.000 | 6120.61 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00795290 | 21.00 | 0.00795290 | 50.6834 | 3538.06 | 0.00 | 6148.68 | 6148.68 | 0.31226938 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.1 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6827.971 | 6827.971 | 0.293529 | 0.00005973 | 159.255 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 2.2656 | 2.311199 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6827.97 | 6827.97 | 1.0000 | 0.34841608 | 0.293529 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.05972797 | 60.00 | 32.22 | 27.78 | 0.000 | 6827.97 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00773045 | 21.00 | 0.00773045 | 49.2841 | 3947.77 | 0.00 | 6859.29 | 6859.29 | 0.34841608 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52746.9 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25102.157 | 25102.157 | 1.322448 | 0.00021960 | 557.444 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 8.3292 | 8.496827 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 25102.16 | 25102.16 | 1.0000 | 1.56973371 | 1.322448 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.21958222 | 60.00 | 32.22 | 27.78 | 0.000 | 25102.16 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00776579 | 21.00 | 0.00776579 | 49.5062 | 12124.78 | 0.00 | 25221.02 | 25221.02 | 1.56973371 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.56 | 17.55 | 0.00800000 | 49126.9 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6780.424 | 6780.424 | 0.291485 | 0.00005932 | 158.146 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 2.2498 | 2.295105 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6780.42 | 6780.42 | 1.0000 | 0.34599037 | 0.291485 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.05931206 | 60.00 | 32.22 | 27.78 | 0.000 | 6780.42 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00772865 | 21.00 | 0.00772865 | 49.2728 | 3920.28 | 0.00 | 6811.53 | 6811.53 | 0.34599037 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52746.9 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24988.477 | 24988.477 | 1.322403 | 0.00021861 | 554.392 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 8.2915 | 8.458348 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 24988.48 | 24988.48 | 1.0000 | 1.56968040 | 1.322403 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.21858780 | 60.00 | 32.22 | 27.78 | 0.000 | 24988.48 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00776368 | 21.00 | 0.00776368 | 49.4929 | 12011.59 | 0.00 | 25106.84 | 25106.84 | 1.56968040 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.49 | 17.53 | 0.00800000 | 49054.7 | |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX | CORRIDOR_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6103.604 | 6103.604 | 0.262346 | 0.00005340 | 142.366 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 2.0252 | 2.066008 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6103.60 | 6103.60 | 1.0000 | 0.31140202 | 0.262346 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.05339154 | 60.00 | 32.22 | 27.78 | 0.000 | 6103.60 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00795277 | 21.00 | 0.00795277 | 50.6826 | 3528.23 | 0.00 | 6131.60 | 6131.60 | 0.31140202 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.1 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6831.829 | 6831.829 | 0.293695 | 0.00005977 | 159.345 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 2.2669 | 2.312505 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6831.83 | 6831.83 | 1.0000 | 0.34861292 | 0.293695 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.05976172 | 60.00 | 32.22 | 27.78 | 0.000 | 6831.83 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00773059 | 21.00 | 0.00773059 | 49.2850 | 3950.00 | 0.00 | 6863.17 | 6863.17 | 0.34861292 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52746.9 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25095.301 | 25095.301 | 1.320735 | 0.00021954 | 557.412 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 8.3269 | 8.494506 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 25095.30 | 25095.30 | 1.0000 | 1.56770062 | 1.320735 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.21952224 | 60.00 | 32.22 | 27.78 | 0.000 | 25095.30 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00776598 | 21.00 | 0.00776598 | 49.5074 | 12134.72 | 0.00 | 25214.12 | 25214.12 | 1.56770062 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.57 | 17.56 | 0.00800000 | 49143.3 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6785.807 | 6785.807 | 0.291717 | 0.00005937 | 158.271 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 2.2516 | 2.296927 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6785.81 | 6785.81 | 1.0000 | 0.34626496 | 0.291717 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.05935914 | 60.00 | 32.22 | 27.78 | 0.000 | 6785.81 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00772886 | 21.00 | 0.00772886 | 49.2741 | 3923.39 | 0.00 | 6816.94 | 6816.94 | 0.34626496 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52746.9 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25033.318 | 25033.318 | 1.321873 | 0.00021900 | 555.644 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 8.3064 | 8.473526 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 25033.32 | 25033.32 | 1.0000 | 1.56905133 | 1.321873 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.21898004 | 60.00 | 32.22 | 27.78 | 0.000 | 25033.32 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00776462 | 21.00 | 0.00776462 | 49.4988 | 12061.61 | 0.00 | 25151.87 | 25151.87 | 1.56905133 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.52 | 17.54 | 0.00800000 | 49089.8 | |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX | CORRIDOR_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6111.643 | 6111.643 | 0.262691 | 0.00005347 | 142.554 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 2.0279 | 2.068729 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6111.64 | 6111.64 | 1.0000 | 0.31181214 | 0.262691 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.05346186 | 60.00 | 32.22 | 27.78 | 0.000 | 6111.64 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00795283 | 21.00 | 0.00795283 | 50.6830 | 3532.88 | 0.00 | 6139.68 | 6139.68 | 0.31181214 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.1 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6869.737 | 6869.737 | 0.295324 | 0.00006010 | 160.229 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 2.2795 | 2.325337 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6869.74 | 6869.74 | 1.0000 | 0.35054688 | 0.295324 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.06009332 | 60.00 | 32.22 | 27.78 | 0.000 | 6869.74 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00773200 | 21.00 | 0.00773200 | 49.2939 | 3971.91 | 0.00 | 6901.25 | 6901.25 | 0.35054688 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52746.9 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16800.715 | 16800.715 | 0.873311 | 0.00014698 | 374.163 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 5.5747 | 5.686873 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 16800.71 | 16800.71 | 1.0000 | 1.03661266 | 0.873311 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.14696499 | 60.00 | 32.22 | 27.78 | 0.000 | 16800.71 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00777189 | 21.00 | 0.00777189 | 49.5446 | 8230.68 | 0.00 | 16880.19 | 16880.19 | 1.03661266 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.77 | 17.62 | 0.00800000 | 49343.8 | |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX | COMPUTER_CLASS_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8310.134 | 8310.134 | 0.448424 | 0.00007270 | 183.624 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 2.7574 | 2.812897 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8310.13 | 8310.13 | 1.0000 | 0.53227516 | 0.448424 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.07269326 | 60.00 | 32.22 | 27.78 | 0.000 | 8310.13 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00775390 | 21.00 | 0.00775390 | 49.4313 | 3909.78 | 0.00 | 8349.55 | 8349.55 | 0.53227516 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.18 | 17.42 | 0.00800000 | 48746.4 | |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX | MAIN_CORRIDOR_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14273.221 | 14273.221 | 0.613499 | 0.00012487 | 332.921 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 4.7360 | 4.831342 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 14273.22 | 14273.22 | 1.0000 | 0.72821804 | 0.613499 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.12485563 | 60.00 | 32.22 | 27.78 | 0.000 | 14273.22 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00793955 | 21.00 | 0.00793955 | 50.5994 | 8250.83 | 0.00 | 14338.70 | 14338.70 | 0.72821804 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.9 | |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | LOBBY_ZN_1_FLR_1 VAV BOX | LOBBY_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8894.870 | 8894.870 | 0.382364 | 0.00007782 | 207.466 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 2.9514 | 3.010824 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 8894.87 | 8894.87 | 1.0000 | 0.45386210 | 0.382364 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.07780827 | 60.00 | 32.22 | 27.78 | 0.000 | 8894.87 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00780068 | 21.00 | 0.00780068 | 49.7258 | 5142.44 | 0.00 | 8935.68 | 8935.68 | 0.45386210 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52747.9 | |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_ZN_1_FLR_1 VAV BOX | MECH_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4416.019 | 4416.019 | 0.237895 | 0.00003863 | 97.612 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 1.4653 | 1.494778 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:40:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:40:00 | Sensible | 4416.02 | 4416.02 | 1.0000 | 0.28237866 | 0.237895 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.03862932 | 60.00 | 32.22 | 27.78 | 0.000 | 4416.02 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 50.9797 | 2080.47 | 0.00 | 4436.96 | 4436.96 | 0.28237866 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.21 | 17.43 | 0.00800000 | 48772.6 | |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BATH_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6751.119 | 6751.119 | 0.290198 | 0.00005906 | 157.467 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 2.2401 | 2.285186 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 6751.12 | 6751.12 | 1.0000 | 0.34446185 | 0.290198 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.05905571 | 60.00 | 32.22 | 27.78 | 0.000 | 6751.12 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00786016 | 21.00 | 0.00786016 | 50.1000 | 3902.84 | 0.00 | 6782.09 | 6782.09 | 0.34446185 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.8 | |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | OFFICES_ZN_1_FLR_1 VAV BOX | OFFICES_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19028.882 | 19028.882 | 0.817999 | 0.00016647 | 443.833 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 6.3140 | 6.441085 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 19028.88 | 19028.88 | 1.0000 | 0.97095672 | 0.817999 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.16645598 | 60.00 | 32.22 | 27.78 | 0.000 | 19028.88 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00779430 | 21.00 | 0.00779430 | 49.6856 | 11001.30 | 0.00 | 19116.18 | 19116.18 | 0.97095672 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52747.8 | |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | GYM_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15583.282 | 15583.282 | 0.802525 | 0.00013633 | 347.750 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 5.1707 | 5.274784 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 04:30:00 | Sensible | 15583.28 | 15583.28 | 1.0000 | 0.95258946 | 0.802525 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.13631545 | 60.00 | 32.22 | 27.78 | 0.000 | 15583.28 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00787915 | 21.00 | 0.00787915 | 50.2197 | 7706.33 | 0.00 | 15656.94 | 15656.94 | 0.95258946 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 28.92 | 17.67 | 0.00800000 | 49496.0 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 16682.888 | 16682.888 | 0.717160 | 0.00014595 | 389.114 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 2.58428486 | 54.44 | 82.22 | 27.78 | 301375.41 | 5.5356 | 5.646990 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 16682.89 | 16682.89 | 1.0000 | 0.85126239 | 0.717160 | 12.89 | 11.51 | 0.00800000 | 33150.5 | 32.11 | 18.58 | 0.00800000 | 52751.6 | 0.14593430 | 60.00 | 32.22 | 27.78 | 0.000 | 16682.89 | -4.20 | 0.00269032 | -4.20 | 0.00000000 | 0.0000 | 21.00 | 0.00777729 | 21.00 | 0.00777729 | 49.5786 | 9645.13 | 0.00 | 16759.42 | 16759.42 | 0.85126239 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52747.6 | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | VAV_POD_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1; MULT_CLASS_1_POD_1_ZN_1_FLR_1; CORRIDOR_POD_1_ZN_1_FLR_1; CORNER_CLASS_2_POD_1_ZN_1_FLR_1; MULT_CLASS_2_POD_1_ZN_1_FLR_1; CORNER_CLASS_1_POD_2_ZN_1_FLR_1; MULT_CLASS_1_POD_2_ZN_1_FLR_1; CORRIDOR_POD_2_ZN_1_FLR_1; CORNER_CLASS_2_POD_2_ZN_1_FLR_1; MULT_CLASS_2_POD_2_ZN_1_FLR_1; CORNER_CLASS_1_POD_3_ZN_1_FLR_1; MULT_CLASS_1_POD_3_ZN_1_FLR_1; CORRIDOR_POD_3_ZN_1_FLR_1; CORNER_CLASS_2_POD_3_ZN_1_FLR_1; MULT_CLASS_2_POD_3_ZN_1_FLR_1; COMPUTER_CLASS_ZN_1_FLR_1; MAIN_CORRIDOR_ZN_1_FLR_1; LOBBY_ZN_1_FLR_1; MECH_ZN_1_FLR_1; BATH_ZN_1_FLR_1; OFFICES_ZN_1_FLR_1; GYM_ZN_1_FLR_1; LIBRARY_MEDIA_CENTER_ZN_1_FLR_1; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 559642.037 | 440362.673 | 28.769692 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.7493 | 1004.8586 | 1.1870 | VAV_POD_1 FAN | Fan:VariableVolume | 28.769692 | 34.14935961 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | Sensible | 553624.03 | 502456.00 | 0.9892 | 34.14935961 | 28.769692 | 26.00 | 17.43 | 0.00909614 | 49317.5 | 11.11 | 11.11 | 0.00850000 | 32598.3 | -999.0 | -999.00 | -999.00 | -999.00 | 62036.476 | 491587.55 | 29.40 | 0.00882150 | 18.34 | 10.68330000 | 37.1339 | 24.00 | 0.00925837 | 24.00 | 0.00925837 | 49.0788 | 336651.49 | 0.00 | 561260.64 | 437427.13 | 32.80071805 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.63 | 13.61 | 0.00970444 | 38211.2 | |
| VAV_POD_1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | VAV_POD_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1; MULT_CLASS_1_POD_1_ZN_1_FLR_1; CORRIDOR_POD_1_ZN_1_FLR_1; CORNER_CLASS_2_POD_1_ZN_1_FLR_1; MULT_CLASS_2_POD_1_ZN_1_FLR_1; CORNER_CLASS_1_POD_2_ZN_1_FLR_1; MULT_CLASS_1_POD_2_ZN_1_FLR_1; CORRIDOR_POD_2_ZN_1_FLR_1; CORNER_CLASS_2_POD_2_ZN_1_FLR_1; MULT_CLASS_2_POD_2_ZN_1_FLR_1; CORNER_CLASS_1_POD_3_ZN_1_FLR_1; MULT_CLASS_1_POD_3_ZN_1_FLR_1; CORRIDOR_POD_3_ZN_1_FLR_1; CORNER_CLASS_2_POD_3_ZN_1_FLR_1; MULT_CLASS_2_POD_3_ZN_1_FLR_1; COMPUTER_CLASS_ZN_1_FLR_1; MAIN_CORRIDOR_ZN_1_FLR_1; LOBBY_ZN_1_FLR_1; MECH_ZN_1_FLR_1; BATH_ZN_1_FLR_1; OFFICES_ZN_1_FLR_1; GYM_ZN_1_FLR_1; LIBRARY_MEDIA_CENTER_ZN_1_FLR_1; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 175923.103 | 175923.103 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | VAV_POD_1 FAN | Fan:VariableVolume | 28.769692 | 34.14935961 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 01:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 24:00:00 | Sensible | 175923.10 | 175923.10 | 1.0000 | 10.24480788 | 8.630908 | -4.20 | -4.20 | 0.00269032 | 2487.0 | 12.89 | 11.51 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 175923.10 | -4.20 | 0.00269032 | -4.20 | 10.68330000 | 123.7796 | 21.00 | 0.00779722 | 21.00 | 0.00779729 | 49.7050 | 123656.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:6 | KITCHEN_ZN_1_FLR_1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31432.260 | 24260.990 | 1.553780 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8794 | 1004.8586 | 1.1870 | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.553783 | 1.84432622 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 12:30:00 | Sensible | 15716.13 | 11846.41 | 1.0000 | 1.22954836 | 1.035853 | 24.69 | 17.92 | 0.01024202 | 50892.9 | 11.52 | 11.44 | 0.00850000 | 33017.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15716.13 | 28.46 | 0.00882000 | 18.03 | 0.25481392 | 24.5994 | 23.95 | 0.01052097 | 23.99 | 0.01052097 | 55.6944 | 18162.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_1:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:6 | KITCHEN_ZN_1_FLR_1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 60785.558 | 60785.558 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.553783 | 1.84432622 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 60785.56 | 60785.56 | 1.0000 | 1.84432622 | 1.553783 | -0.69 | -0.69 | 0.01585941 | 38951.0 | 32.11 | 18.58 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 60785.56 | -4.20 | 0.00269032 | -4.20 | 0.25481392 | 16.3996 | 0.00 | 0.01844274 | 23.38 | 0.01844274 | 99.9999 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:7 | CAFETERIA_ZN_1_FLR_1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 56155.150 | 42327.506 | 2.645890 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.8601 | 1004.8586 | 1.1870 | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.645889 | 3.14064591 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | Sensible | 28077.58 | 23592.41 | 1.0000 | 2.09376470 | 1.763927 | 27.08 | 18.27 | 0.00969372 | 51939.6 | 11.55 | 11.45 | 0.00850000 | 33049.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28077.58 | 29.40 | 0.00882150 | 18.34 | 1.48818443 | 84.3677 | 23.98 | 0.01085556 | 23.98 | 0.01085556 | 57.4473 | 30552.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_2:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:7 | CAFETERIA_ZN_1_FLR_1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 79793.610 | 79793.610 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.645889 | 3.14064591 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 01:40:00 | Sensible | 79793.61 | 79793.61 | 1.0000 | 3.14064591 | 2.645889 | 6.83 | 5.22 | 0.00491503 | 19213.7 | 32.11 | 18.58 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 79793.61 | -4.20 | 0.00269032 | -4.20 | 1.48818443 | 56.2452 | 21.00 | 0.00777480 | 21.00 | 0.00777480 | 49.5635 | 6870.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| VAV_POD_1_OA_CONTROLLER | FixedDryBulb | 0.00 | 28.77 | - | |||
| PSZ-AC_1:6_OA_CONTROLLER | FixedDryBulb | 0.25 | 1.55 | - | |||
| PSZ-AC_2:7_OA_CONTROLLER | FixedDryBulb | 1.49 | 2.65 | - |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| LOBBY_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000559 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MECH_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| BATH_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| OFFICES_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| GYM_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001524 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000864 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1013.50 | 2398.00 | 504.33 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 758.00 | 2305.67 | 240.83 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 605.00 | 2564.67 | 441.17 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 908.50 | 2831.17 | 738.17 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 510.67 | 2899.33 | 418.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1008.50 | 2429.00 | 523.83 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 733.17 | 2348.17 | 249.83 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 605.00 | 2582.67 | 449.17 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 909.83 | 2830.00 | 739.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 514.67 | 2895.50 | 419.33 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1008.83 | 2408.17 | 508.67 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 751.33 | 2301.00 | 238.17 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 618.00 | 2452.50 | 409.83 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 920.33 | 2766.17 | 723.50 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 534.50 | 2829.83 | 408.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 812.17 | 2007.83 | 163.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 984.00 | 2027.33 | 561.50 |
| LOBBY_ZN_1_FLR_1 | 1322.67 | 2844.00 | 1044.00 |
| MECH_ZN_1_FLR_1 | 1926.83 | 1205.50 | 138.50 |
| BATH_ZN_1_FLR_1 | 1886.67 | 1896.17 | 814.83 |
| OFFICES_ZN_1_FLR_1 | 1041.67 | 1611.67 | 441.67 |
| GYM_ZN_1_FLR_1 | 1291.17 | 1636.17 | 120.50 |
| KITCHEN_ZN_1_FLR_1 | 2853.67 | 29.67 | 11.83 |
| CAFETERIA_ZN_1_FLR_1 | 1094.17 | 1438.33 | 78.50 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 1146.67 | 1705.17 | 301.33 |
| Facility | 3217.67 | 3199.00 | 1149.83 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 6.17 | 0.33 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 3.00 | 0.33 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 18.50 | 0.00 | 8.17 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 13.67 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 5.17 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 6.17 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 3.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 18.83 | 0.00 | 8.33 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 14.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 5.17 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 6.00 | 0.33 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 3.00 | 0.17 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 17.33 | 0.00 | 7.83 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 13.67 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 5.33 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 3.33 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 14.00 | 0.00 | 5.83 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 850.67 | 12.00 | 627.83 | 12.00 |
| MECH_ZN_1_FLR_1 | 0.00 | 1.17 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 0.00 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 8.17 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 7.83 | 0.67 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 0.00 | 729.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 6.17 | 0.50 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 3.33 | 0.00 | 0.00 | 0.00 |
| Facility | 866.33 | 743.33 | 627.83 | 12.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.163 | 0.026 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.152 | 0.014 | 0.000 | 0.000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.667 | 0.002 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.047 | 0.026 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.048 | 0.014 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.153 | 0.026 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.142 | 0.014 | 0.000 | 0.000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.664 | 0.002 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.048 | 0.026 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.045 | 0.014 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.155 | 0.026 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.150 | 0.014 | 0.000 | 0.000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.688 | 0.002 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.053 | 0.026 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 45.65 | 84.77 | 1260.00 | 2.055 | 0.014 | 0.000 | 0.000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 38.16 | 43.60 | 648.00 | 2.214 | 0.014 | 0.000 | 0.000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 15.83 | 29.39 | 2184.00 | 0.591 | 0.002 | 0.000 | 0.000 |
| LOBBY_ZN_1_FLR_1 | 9.91 | 18.41 | 684.00 | 1.144 | 2.746 | 0.000 | 0.000 |
| MECH_ZN_1_FLR_1 | 2.19 | 4.07 | 1008.00 | 0.721 | 0.000 | 0.000 | 0.000 |
| BATH_ZN_1_FLR_1 | 5.51 | 10.23 | 760.00 | 0.609 | 0.007 | 0.000 | 0.000 |
| OFFICES_ZN_1_FLR_1 | 14.92 | 23.74 | 1764.00 | 1.127 | 0.012 | 0.000 | 0.000 |
| GYM_ZN_1_FLR_1 | 64.64 | 115.31 | 1428.00 | 1.937 | 0.006 | 0.000 | 0.000 |
| KITCHEN_ZN_1_FLR_1 | 14.54 | 26.99 | 672.00 | 5.156 | 0.006 | 0.000 | 0.000 |
| CAFETERIA_ZN_1_FLR_1 | 209.95 | 339.07 | 1260.00 | 5.152 | 0.015 | 0.000 | 0.000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 23.13 | 42.95 | 1596.00 | 1.358 | 0.013 | 0.000 | 0.000 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.549 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.464 | 0.000 | 0.000 | 0.000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.464 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.285 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.130 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.549 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.423 | 0.000 | 0.000 | 0.000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.463 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.286 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.132 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.546 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.443 | 0.000 | 0.000 | 0.000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.473 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.313 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 45.65 | 84.77 | 1260.00 | 1.183 | 0.000 | 0.000 | 0.000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 38.16 | 43.60 | 648.00 | 1.408 | 0.000 | 0.000 | 0.000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 15.83 | 29.39 | 2184.00 | 0.352 | 0.000 | 0.000 | 0.000 |
| LOBBY_ZN_1_FLR_1 | 9.91 | 18.41 | 684.00 | 0.694 | 0.000 | 0.000 | 0.000 |
| MECH_ZN_1_FLR_1 | 2.19 | 4.07 | 1008.00 | 0.461 | 0.000 | 0.000 | 0.000 |
| BATH_ZN_1_FLR_1 | 5.51 | 10.23 | 760.00 | 0.292 | 0.000 | 0.000 | 0.000 |
| OFFICES_ZN_1_FLR_1 | 14.92 | 23.74 | 1764.00 | 0.664 | 0.000 | 0.000 | 0.000 |
| GYM_ZN_1_FLR_1 | 64.64 | 115.31 | 1428.00 | 1.207 | 0.000 | 0.000 | 0.000 |
| KITCHEN_ZN_1_FLR_1 | 14.54 | 26.99 | 672.00 | 0.000 | 0.000 | 0.000 | 0.000 |
| CAFETERIA_ZN_1_FLR_1 | 209.95 | 339.07 | 1260.00 | 4.193 | 0.000 | 0.000 | 0.000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 23.13 | 42.95 | 1596.00 | 0.733 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 5.56 | 10.33 | 768.00 | 192.00 | 0.0000 | 0.059 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 5.56 | 10.33 | 768.00 | 192.00 | 0.0000 | 0.059 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 5.56 | 10.33 | 768.00 | 192.00 | 0.0000 | 0.059 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 45.65 | 84.77 | 1260.00 | 315.00 | 0.0000 | 0.592 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | 38.16 | 43.60 | 648.00 | 162.00 | 0.0000 | 0.304 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | 15.83 | 29.39 | 2184.00 | 546.00 | 0.0000 | 0.166 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | 9.91 | 18.41 | 684.00 | 171.00 | 0.0000 | 0.096 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | 2.19 | 4.07 | 1008.00 | 252.00 | 0.0000 | 0.000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | 5.51 | 10.23 | 760.00 | 190.00 | 0.0000 | 0.000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | 14.92 | 23.74 | 1764.00 | 441.00 | 0.0000 | 0.190 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | 64.64 | 115.31 | 1428.00 | 357.00 | 0.0000 | 0.544 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | 14.54 | 26.99 | 672.00 | 168.00 | 0.4528 | 0.198 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | 209.95 | 339.07 | 1260.00 | 315.00 | 1.4882 | 1.488 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | 23.13 | 42.95 | 1596.00 | 399.00 | 0.0000 | 0.345 |
| Total Facility | 892.82 | 1571.19 | 27484.00 | 6871.00 | 1.9410 | 9.699 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 3122786.80 | 0.00 | 3122786.80 | 221353.90 | 3344140.71 | 5868225.25 | 6430.89 | 168.32 | 2160.79 | 648.40 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 14968712.06 | 0.00 | 14968712.06 | 586587.84 | 15555299.89 | 28274176.21 | 6528.20 | 144.44 | 2087.37 | 648.40 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 1861725.35 | 0.00 | 1861725.35 | 33203.09 | 1894928.44 | 1845537.18 | 5076.35 | 3.47 | 3680.17 | 648.40 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 2978206.65 | 0.00 | 2978206.65 | 221353.90 | 3199560.55 | 5868225.25 | 6571.68 | 145.33 | 2042.99 | 648.40 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 14348886.33 | 0.00 | 14348886.33 | 586587.84 | 14935474.17 | 28274176.21 | 6569.51 | 153.90 | 2036.60 | 648.40 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 3109461.82 | 0.00 | 3109461.82 | 221353.90 | 3330815.72 | 5868225.25 | 6447.91 | 160.69 | 2151.41 | 648.40 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 14909810.60 | 0.00 | 14909810.60 | 586587.84 | 15496398.44 | 28274176.21 | 6527.10 | 157.97 | 2074.94 | 648.40 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 1852010.07 | 0.00 | 1852010.07 | 33203.09 | 1885213.15 | 1845537.18 | 5077.21 | 2.80 | 3680.00 | 648.40 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 2979516.35 | 0.00 | 2979516.35 | 221353.90 | 3200870.25 | 5868225.25 | 6560.59 | 155.32 | 2044.08 | 648.40 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 14333227.27 | 0.00 | 14333227.27 | 586587.84 | 14919815.11 | 28274176.21 | 6600.98 | 125.50 | 2033.52 | 648.40 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 3111283.96 | 0.00 | 3111283.96 | 221353.90 | 3332637.86 | 5868225.25 | 6482.41 | 125.90 | 2151.69 | 648.40 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 14953098.34 | 0.00 | 14953098.34 | 586587.84 | 15539686.18 | 28274176.21 | 6533.50 | 143.43 | 2083.07 | 648.40 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 1912622.17 | 0.00 | 1912622.17 | 33203.09 | 1945825.26 | 1845537.18 | 5076.29 | 3.86 | 3679.85 | 648.40 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 2984608.46 | 0.00 | 2984608.46 | 221353.90 | 3205962.36 | 5868225.25 | 6569.40 | 138.40 | 2052.21 | 648.40 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 9504660.49 | 0.00 | 9504660.49 | 387369.33 | 9892029.82 | 18671625.80 | 6569.34 | 154.06 | 2036.60 | 648.40 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 5202247.60 | 0.00 | 5202247.60 | 199218.51 | 5401466.11 | 9602550.41 | 6553.39 | 121.45 | 2085.16 | 648.40 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 4595194.77 | 0.00 | 4595194.77 | 99609.26 | 4694804.02 | 5248246.35 | 5128.97 | 4.99 | 3626.04 | 648.40 |
| LOBBY_ZN_1_FLR_1 | 2896305.03 | 0.00 | 2896305.03 | 9132215.93 | 12028520.95 | 3013410.78 | 5035.09 | 1.31 | 3723.60 | 648.40 |
| MECH_ZN_1_FLR_1 | 2660923.60 | 0.00 | 2660923.60 | 0.00 | 2660923.60 | 0.00 | 0.00 | 0.00 | 3924.40 | 648.40 |
| BATH_ZN_1_FLR_1 | 1698750.33 | 0.00 | 1698750.33 | 110676.95 | 1809427.28 | 0.00 | 0.00 | 0.00 | 3924.40 | 648.40 |
| OFFICES_ZN_1_FLR_1 | 6741295.74 | 0.00 | 6741295.74 | 464843.19 | 7206138.93 | 6005204.96 | 5316.64 | 3.45 | 3439.90 | 958.70 |
| GYM_ZN_1_FLR_1 | 9957117.35 | 0.00 | 9957117.35 | 188150.82 | 10145268.17 | 17157717.19 | 6350.94 | 157.70 | 2251.36 | 648.40 |
| KITCHEN_ZN_1_FLR_1 | 13904798.01 | 0.00 | 13904798.01 | 88541.56 | 13993339.57 | 6482703.52 | 4171.61 | 17.52 | 4570.87 | 2773.21 |
| CAFETERIA_ZN_1_FLR_1 | 20810906.94 | 0.00 | 20810906.94 | 398437.02 | 21209343.97 | 46931384.03 | 5480.48 | 2241.70 | 1037.82 | 786.20 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 7642991.25 | 0.00 | 7642991.25 | 442707.80 | 8085699.05 | 10866548.77 | 5824.35 | 541.61 | 2394.03 | 648.40 |
| Total Facility | 0.18E+09 | 0.00 | 0.18E+09 | 15872442.23 | 0.20E+09 | 0.31E+09 | 7052.78 | 2283.51 | 4854.37 | 3876.99 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.2338 | 0.0000 | 0.2338 | 0.0028 | 0.2366 | 0.1861 | 1237.44 | 163.90 | 1874.66 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.1204 | 0.0000 | 1.1204 | 0.0073 | 1.1277 | 0.8966 | 1334.48 | 139.77 | 1801.75 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 0.1399 | 0.0000 | 0.1399 | 0.0004 | 0.1403 | 0.0585 | 0.00 | 0.00 | 3276.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.2217 | 0.0000 | 0.2217 | 0.0028 | 0.2244 | 0.1861 | 1377.97 | 140.64 | 1757.39 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.0679 | 0.0000 | 1.0679 | 0.0073 | 1.0752 | 0.8966 | 1375.85 | 149.34 | 1750.81 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.2327 | 0.0000 | 0.2327 | 0.0028 | 0.2355 | 0.1861 | 1254.41 | 156.11 | 1865.48 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.1154 | 0.0000 | 1.1154 | 0.0073 | 1.1227 | 0.8966 | 1333.43 | 153.25 | 1789.32 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 0.1391 | 0.0000 | 0.1391 | 0.0004 | 0.1395 | 0.0585 | 0.00 | 0.00 | 3276.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.2218 | 0.0000 | 0.2218 | 0.0028 | 0.2245 | 0.1861 | 1366.93 | 150.60 | 1758.46 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.0667 | 0.0000 | 1.0667 | 0.0073 | 1.0741 | 0.8966 | 1407.21 | 120.70 | 1748.09 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.2329 | 0.0000 | 0.2329 | 0.0028 | 0.2357 | 0.1861 | 1288.67 | 121.14 | 1866.19 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.1191 | 0.0000 | 1.1191 | 0.0073 | 1.1264 | 0.8966 | 1339.79 | 138.74 | 1797.47 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 0.1441 | 0.0000 | 0.1441 | 0.0004 | 0.1445 | 0.0585 | 0.00 | 0.00 | 3276.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.2222 | 0.0000 | 0.2222 | 0.0028 | 0.2250 | 0.1861 | 1375.65 | 133.73 | 1766.62 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.7077 | 0.0000 | 0.7077 | 0.0048 | 0.7125 | 0.5921 | 1375.68 | 149.51 | 1750.81 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 0.3907 | 0.0000 | 0.3907 | 0.0025 | 0.3931 | 0.3045 | 1359.52 | 116.75 | 1799.73 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 0.3518 | 0.0000 | 0.3518 | 0.0012 | 0.3531 | 0.1664 | 0.00 | 0.00 | 3276.00 |
| LOBBY_ZN_1_FLR_1 | 0.2149 | 0.0000 | 0.2149 | 0.5184 | 0.7334 | 0.0956 | 0.00 | 0.00 | 3276.00 |
| MECH_ZN_1_FLR_1 | 0.1971 | 0.0000 | 0.1971 | 0.0000 | 0.1971 | 0.0000 | 0.00 | 0.00 | 3276.00 |
| BATH_ZN_1_FLR_1 | 0.1263 | 0.0000 | 0.1263 | 0.0014 | 0.1276 | 0.0000 | 0.00 | 0.00 | 3276.00 |
| OFFICES_ZN_1_FLR_1 | 0.5420 | 0.0000 | 0.5420 | 0.0058 | 0.5477 | 0.1904 | 0.00 | 0.00 | 2772.00 |
| GYM_ZN_1_FLR_1 | 0.7529 | 0.0000 | 0.7529 | 0.0023 | 0.7552 | 0.5441 | 1157.60 | 153.12 | 1965.27 |
| KITCHEN_ZN_1_FLR_1 | 0.9399 | 0.0000 | 0.9399 | 0.0011 | 0.9410 | 0.2182 | 14.33 | 0.00 | 3261.67 |
| CAFETERIA_ZN_1_FLR_1 | 1.7679 | 0.0000 | 1.7679 | 0.0050 | 1.7730 | 1.4882 | 0.00 | 1741.93 | 986.07 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.5902 | 0.0000 | 0.5902 | 0.0055 | 0.5957 | 0.3446 | 633.38 | 537.09 | 2105.52 |
| Total Facility | 13.8590 | 0.0000 | 13.8590 | 0.6025 | 14.4615 | 9.7189 | 1570.94 | 2245.60 | 3276.00 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| VAV_POD_1 | 0.21E+09 | 0.00 | 0.21E+09 | 0.25E+09 | 5117.81 | 4.07 | 3638.11 | 648.40 |
| PSZ-AC_1:6 | 19591125.11 | 0.00 | 19591125.11 | 6482703.52 | 3891.28 | 15.14 | 4853.58 | 2773.18 |
| PSZ-AC_2:7 | 29321470.02 | 0.00 | 29321470.02 | 46931384.03 | 5468.76 | 0.47 | 3290.77 | 786.20 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| VAV_POD_1 | 15.6716 | 0.0000 | 15.6716 | 8.0125 | 0.00 | 0.00 | 3276.00 |
| PSZ-AC_1:6 | 1.3243 | 0.0000 | 1.3243 | 0.2182 | 14.33 | 0.00 | 3261.67 |
| PSZ-AC_2:7 | 2.4909 | 0.0000 | 2.4909 | 1.4882 | 0.00 | 0.00 | 2728.00 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| VAV_POD_1 | 0.00 | 68.49 | 3605.76 | 71.36 | 0.00 | 0.00 | 178.79 | 0.00 | 0.00 | 0.00 |
| PSZ-AC_1:6 | 0.00 | 172.85 | 4226.86 | 1635.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| PSZ-AC_2:7 | 0.00 | 2231.99 | 1191.91 | 90.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| VAV_POD_1 | 0.0000 | 15.1862 | 15.8319 | 0.0000 | 0.0000 | 0.0000 | 13.3065 | 0.0000 | 0.0000 | 0.0000 |
| PSZ-AC_1:6 | 0.0000 | 0.3608 | 1.3849 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| PSZ-AC_2:7 | 0.0000 | 2.0970 | 3.1803 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Surfaces by Class| Total | Outdoors | |
| Wall | 121 | 33 |
| Floor | 25 | 24 |
| Roof | 25 | 25 |
| Internal Mass | 25 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 67 | 67 |
| Door | 25 | 25 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 3 |
| Conditioned Zones | 25 |
| Unconditioned Zones | 0 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1159 |
| Defaulted Fields | 890 |
| Fields with Defaults | 3720 |
| Autosized Fields | 267 |
| Autosizable Fields | 376 |
| Autocalculated Fields | 317 |
| Autocalculatable Fields | 632 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 3017.31 | 37021.34 | 01-JUL-10:30 | 298705.41 | 27-APR-14:00 |
| Electricity:Building | 2377.40 | 35841.46 | 01-JUL-10:30 | 158543.84 | 02-JAN-11:10 |
| Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| Electricity:SpaceType:GENERAL | 2369.55 | 35741.12 | 30-JUN-23:10 | 156371.25 | 02-JAN-10:10 |
| InteriorLights:Electricity | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 24.39 | 336.28 | 30-JUN-23:10 | 1626.10 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 24.39 | 336.28 | 30-JUN-23:10 | 1626.10 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 24.39 | 336.28 | 30-JUN-23:10 | 1626.10 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 126.22 | 1762.63 | 30-JUN-23:10 | 8449.51 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 65.42 | 841.62 | 01-JAN-00:10 | 4272.19 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 65.42 | 841.62 | 01-JAN-00:10 | 4272.19 | 02-JAN-07:10 |
| Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 75.34 | 1064.38 | 30-JUN-23:10 | 5061.57 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 33.64 | 432.83 | 01-JAN-00:10 | 2197.13 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 33.64 | 432.83 | 01-JAN-00:10 | 2197.13 | 02-JAN-07:10 |
| Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 69.34 | 956.30 | 30-JUN-23:10 | 4624.21 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 41.24 | 530.59 | 01-JAN-00:10 | 2693.36 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 41.24 | 530.59 | 01-JAN-00:10 | 2693.36 | 02-JAN-07:10 |
| Electricity:Zone:LOBBY_ZN_1_FLR_1 | 41.78 | 557.57 | 30-JUN-23:10 | 2758.25 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 32.98 | 424.25 | 01-JAN-00:10 | 2153.53 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 32.98 | 424.25 | 01-JAN-00:10 | 2153.53 | 02-JAN-07:10 |
| Electricity:Zone:MECH_ZN_1_FLR_1 | 88.50 | 1212.59 | 30-JUN-23:10 | 5889.78 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MECH_ZN_1_FLR_1 | 56.07 | 721.39 | 01-JAN-00:10 | 3661.88 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MECH_ZN_1_FLR_1 | 56.07 | 721.39 | 01-JAN-00:10 | 3661.88 | 02-JAN-07:10 |
| Electricity:Zone:BATH_ZN_1_FLR_1 | 35.15 | 474.48 | 30-JUN-23:10 | 2328.47 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:BATH_ZN_1_FLR_1 | 25.37 | 326.34 | 01-JAN-00:10 | 1656.56 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:BATH_ZN_1_FLR_1 | 25.37 | 326.34 | 01-JAN-00:10 | 1656.56 | 02-JAN-07:10 |
| Electricity:Zone:OFFICES_ZN_1_FLR_1 | 133.25 | 1854.16 | 30-JUN-23:10 | 8910.14 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 71.96 | 925.78 | 01-JAN-00:10 | 4699.41 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 71.96 | 925.78 | 01-JAN-00:10 | 4699.41 | 02-JAN-07:10 |
| Electricity:Zone:GYM_ZN_1_FLR_1 | 88.64 | 1192.76 | 30-JUN-23:10 | 5866.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:GYM_ZN_1_FLR_1 | 65.67 | 844.83 | 01-JAN-00:10 | 4288.47 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:GYM_ZN_1_FLR_1 | 65.67 | 844.83 | 01-JAN-00:10 | 4288.47 | 02-JAN-07:10 |
| Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 211.64 | 5400.64 | 01-JAN-11:30 | 13840.49 | 02-JAN-11:10 |
| InteriorLights:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 29.90 | 384.74 | 01-JAN-00:10 | 1953.00 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 29.90 | 384.74 | 01-JAN-00:10 | 1953.00 | 02-JAN-07:10 |
| Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 71.99 | 1340.83 | 01-JAN-00:10 | 4745.87 | 02-JAN-10:10 |
| InteriorLights:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 42.05 | 541.04 | 01-JAN-00:10 | 2746.41 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 42.05 | 541.04 | 01-JAN-00:10 | 2746.41 | 02-JAN-07:10 |
| Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 168.75 | 2346.88 | 30-JUN-23:10 | 11282.50 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 91.74 | 1180.27 | 01-JAN-00:10 | 5991.24 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 91.74 | 1180.27 | 01-JAN-00:10 | 5991.24 | 02-JAN-07:10 |
| InteriorEquipment:Electricity | 1151.36 | 20068.34 | 30-JUN-23:10 | 76813.98 | 02-JAN-10:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 1151.36 | 20068.34 | 30-JUN-23:10 | 76813.98 | 02-JAN-10:10 |
| MiscPlug:InteriorEquipment:Electricity | 947.54 | 14352.99 | 30-JUN-23:10 | 65099.62 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 947.54 | 14352.99 | 30-JUN-23:10 | 65099.62 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 60.80 | 921.00 | 30-JUN-23:10 | 4177.31 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 60.80 | 921.00 | 30-JUN-23:10 | 4177.31 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 41.69 | 631.55 | 30-JUN-23:10 | 2864.44 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 41.69 | 631.55 | 30-JUN-23:10 | 2864.44 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 28.10 | 425.71 | 30-JUN-23:10 | 1930.85 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 28.10 | 425.71 | 30-JUN-23:10 | 1930.85 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 8.80 | 133.33 | 30-JUN-23:10 | 604.72 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 8.80 | 133.33 | 30-JUN-23:10 | 604.72 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MECH_ZN_1_FLR_1 | 32.43 | 491.20 | 30-JUN-23:10 | 2227.90 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MECH_ZN_1_FLR_1 | 32.43 | 491.20 | 30-JUN-23:10 | 2227.90 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:BATH_ZN_1_FLR_1 | 9.78 | 148.14 | 30-JUN-23:10 | 671.91 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:BATH_ZN_1_FLR_1 | 9.78 | 148.14 | 30-JUN-23:10 | 671.91 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 61.29 | 928.37 | 30-JUN-23:10 | 4210.73 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 61.29 | 928.37 | 30-JUN-23:10 | 4210.73 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GYM_ZN_1_FLR_1 | 22.97 | 347.93 | 30-JUN-23:10 | 1578.10 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GYM_ZN_1_FLR_1 | 22.97 | 347.93 | 30-JUN-23:10 | 1578.10 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 173.88 | 4915.56 | 01-JAN-00:10 | 9714.90 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity | 149.71 | 3999.34 | 01-JAN-00:10 | 9998.36 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 119.77 | 3199.56 | 01-JAN-00:10 | 7998.90 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 149.71 | 3999.34 | 01-JAN-00:10 | 9998.36 | 02-JAN-10:10 |
| ReachInFreezer:InteriorEquipment:Electricity | 31.09 | 986.00 | 01-JAN-00:10 | 986.00 | 01-JAN-00:10 |
| ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 31.09 | 986.00 | 01-JAN-00:10 | 986.00 | 01-JAN-00:10 |
| ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 31.09 | 986.00 | 01-JAN-00:10 | 986.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 29.94 | 799.79 | 01-JAN-00:10 | 1999.46 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 29.94 | 799.79 | 01-JAN-00:10 | 1999.46 | 02-JAN-10:10 |
| InteriorEquipment:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 77.02 | 1166.60 | 30-JUN-23:10 | 5291.26 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 77.02 | 1166.60 | 30-JUN-23:10 | 5291.26 | 02-JAN-08:10 |
| Refrigeration:Electricity | 44.95 | 779.06 | 03-JUN-22:30 | 2907.46 | 09-JAN-11:10 |
| Refrigeration:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 7.85 | 100.34 | 01-JAN-11:30 | 2172.58 | 02-JAN-11:10 |
| General:Refrigeration:Electricity | 7.85 | 100.34 | 01-JAN-11:30 | 2172.58 | 02-JAN-11:10 |
| General:Refrigeration:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 7.85 | 100.34 | 01-JAN-11:30 | 2172.58 | 02-JAN-11:10 |
| Electricity:Plant | 38.08 | 657.66 | 22-AUG-22:10 | 2485.22 | 26-DEC-11:40 |
| LowTempRefrigeration:Refrigeration:Electricity | 15.12 | 0.00 | 01-JAN-11:10 | 1474.24 | 01-APR-10:50 |
| MedTempRefrigeration:Refrigeration:Electricity | 21.98 | 634.14 | 18-MAR-16:00 | 734.88 | 01-JAN-07:10 |
| Electricity:HVAC | 509.33 | 321.20 | 01-JUL-10:50 | 144931.74 | 27-APR-14:00 |
| ExteriorEquipment:Electricity | 17.61 | 321.20 | 01-JUL-10:50 | 1336.02 | 02-JAN-10:10 |
| Transformer:ExteriorEquipment:Electricity | 17.61 | 321.20 | 01-JUL-10:50 | 1336.02 | 02-JAN-10:10 |
| ElectricityPurchased:Facility | 3017.31 | 37021.34 | 01-JUL-10:30 | 298705.41 | 27-APR-14:00 |
| ElectricityPurchased:Plant | 3017.31 | 37021.34 | 01-JUL-10:30 | 298705.41 | 27-APR-14:00 |
| Cogeneration:ElectricityPurchased | 3017.31 | 37021.34 | 01-JUL-10:30 | 298705.41 | 27-APR-14:00 |
| General:Cogeneration:ElectricityPurchased | 3017.31 | 37021.34 | 01-JUL-10:30 | 298705.41 | 27-APR-14:00 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 3017.31 | 37021.34 | 01-JUL-10:30 | 298705.41 | 27-APR-14:00 |
| ElectricityNet:Plant | 3017.31 | 37021.34 | 01-JUL-10:30 | 298705.41 | 27-APR-14:00 |
| Cogeneration:ElectricityNet | 3017.31 | 37021.34 | 01-JUL-10:30 | 298705.41 | 27-APR-14:00 |
| General:Cogeneration:ElectricityNet | 3017.31 | 37021.34 | 01-JUL-10:30 | 298705.41 | 27-APR-14:00 |
| Fans:Electricity | 334.43 | 0.00 | 01-JAN-00:10 | 53859.25 | 04-MAY-14:30 |
| General:Fans:Electricity | 334.43 | 0.00 | 01-JAN-00:10 | 53859.25 | 04-MAY-14:30 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 157.29 | 0.00 | 01-JAN-00:10 | 101509.42 | 29-AUG-14:10 |
| General:Cooling:Electricity | 157.29 | 0.00 | 01-JAN-00:10 | 101509.42 | 29-AUG-14:10 |
| ExteriorLights:Electricity | 92.49 | 0.00 | 01-JAN-08:10 | 5897.73 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 92.49 | 0.00 | 01-JAN-08:10 | 5897.73 | 01-JAN-00:10 |
| Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Pumps:Electricity | 0.98 | 0.00 | 01-JAN-00:10 | 780.81 | 02-JAN-07:30 |
| General:Pumps:Electricity | 0.98 | 0.00 | 01-JAN-00:10 | 780.81 | 02-JAN-07:30 |
| WIRED_LTG_ELECTRICITY | 14.50 | 0.00 | 01-JAN-00:10 | 946.73 | 02-JAN-07:20 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 1099.10 | 4866.92 | 18-JUN-10:50 | 542830.59 | 26-DEC-08:10 |
| NaturalGas:Building | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| NaturalGas:SpaceType:GENERAL | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| InteriorEquipment:NaturalGas | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| InteriorEquipment:NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| InteriorEquipment:NaturalGas:SpaceType:GENERAL | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:NaturalGas | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| NaturalGas:HVAC | 321.74 | 0.00 | 01-JAN-00:10 | 239121.92 | 06-JAN-08:10 |
| Heating:NaturalGas | 583.21 | 0.00 | 01-JAN-00:10 | 494623.63 | 26-DEC-08:10 |
| General:Heating:NaturalGas | 321.74 | 0.00 | 01-JAN-00:10 | 239121.92 | 06-JAN-08:10 |
| NaturalGas:Plant | 416.33 | 58.43 | 18-JUN-10:50 | 387560.41 | 26-DEC-07:10 |
| WaterSystems:NaturalGas | 154.86 | 58.43 | 18-JUN-10:50 | 29275.26 | 15-FEB-13:40 |
| Water Heater:WaterSystems:NaturalGas | 154.86 | 58.43 | 18-JUN-10:50 | 29275.26 | 15-FEB-13:40 |
| Boiler:Heating:NaturalGas | 261.48 | 0.00 | 01-JAN-00:10 | 387482.45 | 26-DEC-07:10 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Water:Plant | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| WaterSystems:Water | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Water Heater:WaterSystems:Water | 268.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| MainsWater:Facility | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| MainsWater:Plant | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| WaterSystems:MainsWater | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Water Heater:WaterSystems:MainsWater | 268.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| WaterUse:WaterSystems:Water | 449.48 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-13:10 |
| WaterUse:WaterSystems:MainsWater | 449.48 | 0.00 | 01-JAN-00:10 | 0.00 | 09-JAN-13:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 3333.28 | 4294.96 | 22-AUG-22:10 | 825495.77 | 02-JAN-07:20 |
| EnergyTransfer:Building | 1961.19 | 2147.48 | 22-AUG-22:10 | 290965.59 | 15-MAY-14:00 |
| EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 257.88 | 2147.48 | 22-AUG-22:10 | 27132.81 | 15-MAY-10:50 |
| Refrigeration:EnergyTransfer | 188.89 | 4294.96 | 22-AUG-22:10 | 10745.76 | 01-JAN-11:40 |
| Refrigeration:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 94.44 | 2147.48 | 22-AUG-22:10 | 5372.88 | 01-JAN-11:40 |
| General:Refrigeration:EnergyTransfer | 94.44 | 2147.48 | 22-AUG-22:10 | 5372.88 | 01-JAN-11:40 |
| General:Refrigeration:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 94.44 | 2147.48 | 22-AUG-22:10 | 5372.88 | 01-JAN-11:40 |
| EnergyTransfer:Plant | 356.23 | 2147.48 | 22-AUG-22:10 | 294008.37 | 26-DEC-07:10 |
| LowTempRefrigeration:Refrigeration:EnergyTransfer | 18.04 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
| MedTempRefrigeration:Refrigeration:EnergyTransfer | 76.40 | 1983.32 | 18-MAR-16:00 | 2686.44 | 01-JAN-07:10 |
| EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 30.66 | 0.00 | 01-JAN-00:10 | 6432.38 | 04-OCT-15:00 |
| Heating:EnergyTransfer | 73.94 | 0.00 | 01-JAN-00:10 | 248186.34 | 02-JAN-07:20 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1.03 | 0.00 | 01-JAN-00:10 | 5667.73 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer | 73.94 | 0.00 | 01-JAN-00:10 | 248186.34 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1.03 | 0.00 | 01-JAN-00:10 | 5667.73 | 02-JAN-07:20 |
| Cooling:EnergyTransfer | 1792.80 | 0.00 | 01-JAN-00:10 | 288016.47 | 15-MAY-14:00 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 29.63 | 0.00 | 01-JAN-00:10 | 6432.38 | 04-OCT-15:00 |
| General:Cooling:EnergyTransfer | 1792.80 | 0.00 | 01-JAN-00:10 | 288016.47 | 15-MAY-14:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 29.63 | 0.00 | 01-JAN-00:10 | 6432.38 | 04-OCT-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 153.82 | 0.00 | 01-JAN-00:10 | 28199.25 | 04-OCT-13:50 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.42 | 0.00 | 01-JAN-00:10 | 20882.50 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.42 | 0.00 | 01-JAN-00:10 | 20882.50 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 152.40 | 0.00 | 01-JAN-00:10 | 28199.25 | 04-OCT-13:50 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 152.40 | 0.00 | 01-JAN-00:10 | 28199.25 | 04-OCT-13:50 |
| EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 19.81 | 0.00 | 01-JAN-00:10 | 5504.89 | 02-JAN-07:20 |
| Heating:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 2.20 | 0.00 | 01-JAN-00:10 | 5504.89 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 2.20 | 0.00 | 01-JAN-00:10 | 5504.89 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 17.60 | 0.00 | 01-JAN-00:10 | 4343.11 | 04-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 17.60 | 0.00 | 01-JAN-00:10 | 4343.11 | 04-MAY-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 26.48 | 0.00 | 01-JAN-00:10 | 5645.49 | 21-FEB-07:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1.55 | 0.00 | 01-JAN-00:10 | 5645.49 | 21-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1.55 | 0.00 | 01-JAN-00:10 | 5645.49 | 21-FEB-07:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 24.93 | 0.00 | 01-JAN-00:10 | 4727.63 | 04-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 24.93 | 0.00 | 01-JAN-00:10 | 4727.63 | 04-MAY-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 132.38 | 0.00 | 01-JAN-00:10 | 20571.68 | 21-FEB-07:10 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 2.16 | 0.00 | 01-JAN-00:10 | 20571.68 | 21-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 2.16 | 0.00 | 01-JAN-00:10 | 20571.68 | 21-FEB-07:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 130.22 | 0.00 | 01-JAN-00:10 | 19387.99 | 09-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 130.22 | 0.00 | 01-JAN-00:10 | 19387.99 | 09-JUN-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 30.32 | 0.00 | 01-JAN-00:10 | 6396.96 | 04-OCT-15:00 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1.06 | 0.00 | 01-JAN-00:10 | 5662.31 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1.06 | 0.00 | 01-JAN-00:10 | 5662.31 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 29.26 | 0.00 | 01-JAN-00:10 | 6396.96 | 04-OCT-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 29.26 | 0.00 | 01-JAN-00:10 | 6396.96 | 04-OCT-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 152.18 | 0.00 | 01-JAN-00:10 | 27815.13 | 04-OCT-13:50 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.40 | 0.00 | 01-JAN-00:10 | 20610.62 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.40 | 0.00 | 01-JAN-00:10 | 20610.62 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 150.78 | 0.00 | 01-JAN-00:10 | 27815.13 | 04-OCT-13:50 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 150.78 | 0.00 | 01-JAN-00:10 | 27815.13 | 04-OCT-13:50 |
| EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 19.68 | 0.00 | 01-JAN-00:10 | 5490.13 | 02-JAN-07:20 |
| Heating:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 2.25 | 0.00 | 01-JAN-00:10 | 5490.13 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 2.25 | 0.00 | 01-JAN-00:10 | 5490.13 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 17.43 | 0.00 | 01-JAN-00:10 | 4317.71 | 04-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 17.43 | 0.00 | 01-JAN-00:10 | 4317.71 | 04-MAY-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 26.49 | 0.00 | 01-JAN-00:10 | 5647.88 | 21-FEB-07:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1.55 | 0.00 | 01-JAN-00:10 | 5647.88 | 21-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1.55 | 0.00 | 01-JAN-00:10 | 5647.88 | 21-FEB-07:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 24.94 | 0.00 | 01-JAN-00:10 | 4732.34 | 04-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 24.94 | 0.00 | 01-JAN-00:10 | 4732.34 | 04-MAY-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 132.31 | 0.00 | 01-JAN-00:10 | 20571.33 | 21-FEB-07:10 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 2.17 | 0.00 | 01-JAN-00:10 | 20571.33 | 21-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 2.17 | 0.00 | 01-JAN-00:10 | 20571.33 | 21-FEB-07:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 130.14 | 0.00 | 01-JAN-00:10 | 19417.26 | 09-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 130.14 | 0.00 | 01-JAN-00:10 | 19417.26 | 09-JUN-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 30.52 | 0.00 | 01-JAN-00:10 | 6419.37 | 04-OCT-15:00 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1.03 | 0.00 | 01-JAN-00:10 | 5660.70 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1.03 | 0.00 | 01-JAN-00:10 | 5660.70 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 29.49 | 0.00 | 01-JAN-00:10 | 6419.37 | 04-OCT-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 29.49 | 0.00 | 01-JAN-00:10 | 6419.37 | 04-OCT-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 153.89 | 0.00 | 01-JAN-00:10 | 28021.23 | 04-OCT-13:50 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.36 | 0.00 | 01-JAN-00:10 | 20677.62 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.36 | 0.00 | 01-JAN-00:10 | 20677.62 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 152.53 | 0.00 | 01-JAN-00:10 | 28021.23 | 04-OCT-13:50 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 152.53 | 0.00 | 01-JAN-00:10 | 28021.23 | 04-OCT-13:50 |
| EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 20.62 | 0.00 | 01-JAN-00:10 | 5514.72 | 02-JAN-07:20 |
| Heating:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 2.06 | 0.00 | 01-JAN-00:10 | 5514.72 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 2.06 | 0.00 | 01-JAN-00:10 | 5514.72 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 18.56 | 0.00 | 01-JAN-00:10 | 4492.52 | 04-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 18.56 | 0.00 | 01-JAN-00:10 | 4492.52 | 04-MAY-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 26.86 | 0.00 | 01-JAN-00:10 | 5655.60 | 21-FEB-07:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1.54 | 0.00 | 01-JAN-00:10 | 5655.60 | 21-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1.54 | 0.00 | 01-JAN-00:10 | 5655.60 | 21-FEB-07:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 25.32 | 0.00 | 01-JAN-00:10 | 4825.41 | 04-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 25.32 | 0.00 | 01-JAN-00:10 | 4825.41 | 04-MAY-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 89.05 | 0.00 | 01-JAN-00:10 | 13790.55 | 21-FEB-07:10 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1.48 | 0.00 | 01-JAN-00:10 | 13790.55 | 21-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1.48 | 0.00 | 01-JAN-00:10 | 13790.55 | 21-FEB-07:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 87.57 | 0.00 | 01-JAN-00:10 | 13308.68 | 09-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 87.57 | 0.00 | 01-JAN-00:10 | 13308.68 | 09-JUN-15:00 |
| EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 57.79 | 0.00 | 01-JAN-00:10 | 8221.47 | 28-JUN-15:00 |
| Heating:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 0.41 | 0.00 | 01-JAN-00:10 | 6770.33 | 21-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 0.41 | 0.00 | 01-JAN-00:10 | 6770.33 | 21-FEB-07:10 |
| Cooling:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 57.38 | 0.00 | 01-JAN-00:10 | 8221.47 | 28-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 57.38 | 0.00 | 01-JAN-00:10 | 8221.47 | 28-JUN-15:00 |
| EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 51.48 | 0.00 | 01-JAN-00:10 | 12267.28 | 02-JAN-07:20 |
| Heating:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 5.10 | 0.00 | 01-JAN-00:10 | 12267.28 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 5.10 | 0.00 | 01-JAN-00:10 | 12267.28 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 46.38 | 0.00 | 01-JAN-00:10 | 12020.66 | 15-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 46.38 | 0.00 | 01-JAN-00:10 | 12020.66 | 15-MAY-15:00 |
| EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 49.77 | 0.00 | 01-JAN-00:10 | 13124.24 | 29-AUG-15:00 |
| Heating:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 35.58 | 0.00 | 01-JAN-00:10 | 12949.96 | 06-JAN-08:00 |
| General:Heating:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 35.58 | 0.00 | 01-JAN-00:10 | 12949.96 | 06-JAN-08:00 |
| Cooling:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 14.20 | 0.00 | 01-JAN-00:10 | 13124.24 | 29-AUG-15:00 |
| General:Cooling:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 14.20 | 0.00 | 01-JAN-00:10 | 13124.24 | 29-AUG-15:00 |
| EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 37.82 | 0.00 | 01-JAN-00:10 | 5567.91 | 28-JUN-14:20 |
| Heating:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 37.82 | 0.00 | 01-JAN-00:10 | 5567.91 | 28-JUN-14:20 |
| General:Cooling:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 37.82 | 0.00 | 01-JAN-00:10 | 5567.91 | 28-JUN-14:20 |
| EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 19.07 | 0.00 | 01-JAN-00:10 | 2864.41 | 23-JUL-17:30 |
| Heating:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 0.07 | 0.00 | 01-JAN-00:10 | 1361.11 | 01-JAN-06:20 |
| General:Heating:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 0.07 | 0.00 | 01-JAN-00:10 | 1361.11 | 01-JAN-06:20 |
| Cooling:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 19.00 | 0.00 | 01-JAN-00:10 | 2864.41 | 23-JUL-17:30 |
| General:Cooling:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 19.00 | 0.00 | 01-JAN-00:10 | 2864.41 | 23-JUL-17:30 |
| EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 75.54 | 0.00 | 01-JAN-00:10 | 19059.55 | 11-SEP-14:10 |
| Heating:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 2.69 | 0.00 | 01-JAN-00:10 | 16504.68 | 02-JAN-07:20 |
| General:Heating:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 2.69 | 0.00 | 01-JAN-00:10 | 16504.68 | 02-JAN-07:20 |
| Cooling:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 72.85 | 0.00 | 01-JAN-00:10 | 19059.55 | 11-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 72.85 | 0.00 | 01-JAN-00:10 | 19059.55 | 11-SEP-14:10 |
| EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 112.74 | 0.00 | 01-JAN-00:10 | 19096.63 | 15-MAY-15:20 |
| Heating:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 1.05 | 0.00 | 01-JAN-00:10 | 13325.34 | 02-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 1.05 | 0.00 | 01-JAN-00:10 | 13325.34 | 02-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 111.69 | 0.00 | 01-JAN-00:10 | 19096.63 | 15-MAY-15:20 |
| General:Cooling:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 111.69 | 0.00 | 01-JAN-00:10 | 19096.63 | 15-MAY-15:20 |
| Heating:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 567.96 | 24-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 0.01 | 0.00 | 01-JAN-00:10 | 567.96 | 24-FEB-07:10 |
| Cooling:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 163.43 | 0.00 | 01-JAN-00:10 | 22086.05 | 15-MAY-10:50 |
| General:Cooling:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 163.43 | 0.00 | 01-JAN-00:10 | 22086.05 | 15-MAY-10:50 |
| EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 165.95 | 0.00 | 01-JAN-00:10 | 27970.72 | 28-JUN-12:00 |
| Heating:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 3.52 | 0.00 | 01-JAN-00:10 | 21503.00 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 3.52 | 0.00 | 01-JAN-00:10 | 21503.00 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 162.43 | 0.00 | 01-JAN-00:10 | 27970.72 | 28-JUN-12:00 |
| General:Cooling:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 162.43 | 0.00 | 01-JAN-00:10 | 27970.72 | 28-JUN-12:00 |
| EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 88.08 | 0.00 | 01-JAN-00:10 | 16794.28 | 15-MAY-14:20 |
| Heating:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 1.25 | 0.00 | 01-JAN-00:10 | 15293.58 | 21-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 1.25 | 0.00 | 01-JAN-00:10 | 15293.58 | 21-FEB-07:10 |
| Cooling:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 86.83 | 0.00 | 01-JAN-00:10 | 16794.28 | 15-MAY-14:20 |
| General:Cooling:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 86.83 | 0.00 | 01-JAN-00:10 | 16794.28 | 15-MAY-14:20 |
| PlantLoopHeatingDemand:Facility | 263.41 | 0.00 | 01-JAN-00:10 | 280128.08 | 02-JAN-07:30 |
| PlantLoopHeatingDemand:Plant | 86.72 | 0.00 | 01-JAN-00:10 | 17882.12 | 10-FEB-13:10 |
| WaterSystems:PlantLoopHeatingDemand | 86.72 | 0.00 | 01-JAN-00:10 | 17882.12 | 10-FEB-13:10 |
| General:WaterSystems:PlantLoopHeatingDemand | 86.72 | 0.00 | 01-JAN-00:10 | 17882.12 | 10-FEB-13:10 |
| EnergyTransfer:HVAC | 1015.87 | 0.00 | 01-JAN-00:10 | 406881.79 | 29-AUG-14:10 |
| HeatingCoils:EnergyTransfer | 431.67 | 0.00 | 01-JAN-00:10 | 383017.05 | 26-DEC-08:10 |
| PlantLoopHeatingDemand:HVAC | 176.69 | 0.00 | 01-JAN-00:10 | 280128.08 | 02-JAN-07:30 |
| HeatingCoils:PlantLoopHeatingDemand | 176.69 | 0.00 | 01-JAN-00:10 | 280128.08 | 02-JAN-07:30 |
| CoolingCoils:EnergyTransfer | 584.20 | 0.00 | 01-JAN-00:10 | 406881.79 | 29-AUG-14:10 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:EnergyTransfer | 86.72 | 0.00 | 01-JAN-00:10 | 17882.12 | 10-FEB-13:10 |
| WaterUse:WaterSystems:EnergyTransfer | 86.72 | 0.00 | 01-JAN-00:10 | 17882.12 | 10-FEB-13:10 |
| Boilers:EnergyTransfer | 175.07 | 0.00 | 01-JAN-00:10 | 290832.30 | 26-DEC-07:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 1.031 | -29.631 | 0.000 | 0.000 | 12.399 | 20.559 | 19.109 | 14.252 | 0.000 | 0.008 | 0.000 | 0.000 | -10.530 | 0.000 | -2.840 | -24.357 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 1.417 | -152.400 | 0.000 | 0.000 | 58.597 | 99.059 | 92.071 | 43.139 | 0.000 | 0.026 | 0.000 | 0.000 | -30.001 | 0.000 | -8.099 | -103.809 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 2.202 | -17.603 | 0.000 | 0.000 | 4.853 | 14.502 | 9.883 | 1.807 | 0.000 | 0.001 | 0.000 | 0.000 | -1.757 | 0.000 | -0.446 | -13.441 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 1.547 | -24.930 | 0.000 | 0.000 | 12.682 | 20.559 | 19.109 | 7.059 | 0.000 | 0.013 | 0.000 | 0.000 | -10.227 | 0.000 | -2.670 | -23.142 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 2.161 | -130.220 | 0.000 | 0.000 | 60.084 | 99.059 | 92.071 | 6.775 | 0.000 | 0.046 | 0.000 | 0.000 | -29.777 | 0.000 | -7.591 | -92.608 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 1.056 | -29.259 | 0.000 | 0.000 | 12.419 | 20.559 | 19.109 | 13.676 | 0.000 | 0.008 | 0.000 | 0.000 | -10.472 | 0.000 | -2.829 | -24.267 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 1.397 | -150.784 | 0.000 | 0.000 | 58.693 | 99.059 | 92.071 | 38.853 | 0.000 | 0.027 | 0.000 | 0.000 | -29.928 | 0.000 | -8.075 | -101.313 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 2.250 | -17.430 | 0.000 | 0.000 | 4.855 | 14.502 | 9.883 | 1.808 | 0.000 | 0.001 | 0.000 | 0.000 | -1.754 | 0.000 | -0.446 | -13.669 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 1.555 | -24.935 | 0.000 | 0.000 | 12.682 | 20.559 | 19.109 | 7.095 | 0.000 | 0.013 | 0.000 | 0.000 | -10.225 | 0.000 | -2.669 | -23.183 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 2.172 | -130.139 | 0.000 | 0.000 | 60.075 | 99.059 | 92.071 | 6.940 | 0.000 | 0.046 | 0.000 | 0.000 | -29.757 | 0.000 | -7.591 | -92.876 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 1.029 | -29.488 | 0.000 | 0.000 | 12.402 | 20.559 | 19.109 | 13.712 | 0.000 | 0.008 | 0.000 | 0.000 | -10.514 | 0.000 | -2.842 | -23.976 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 1.360 | -152.531 | 0.000 | 0.000 | 58.571 | 99.059 | 92.071 | 39.060 | 0.000 | 0.026 | 0.000 | 0.000 | -30.080 | 0.000 | -8.126 | -99.412 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 2.064 | -18.555 | 0.000 | 0.000 | 4.832 | 14.502 | 9.883 | 1.798 | 0.000 | 0.001 | 0.000 | 0.000 | -1.778 | 0.000 | -0.452 | -12.294 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 1.539 | -25.317 | 0.000 | 0.000 | 12.655 | 20.559 | 19.109 | 7.514 | 0.000 | 0.012 | 0.000 | 0.000 | -10.285 | 0.000 | -2.687 | -23.100 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 1.483 | -87.571 | 0.000 | 0.000 | 39.567 | 65.416 | 60.801 | 6.447 | 0.000 | 0.029 | 0.000 | 0.000 | -19.714 | 0.000 | -5.049 | -61.410 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 0.000 | 0.000 | 0.406 | -57.384 | 0.000 | 0.000 | 33.107 | 33.643 | 41.692 | 3.082 | 0.000 | 0.011 | 0.000 | 0.000 | -10.881 | 0.000 | -2.793 | -40.881 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 0.000 | 0.000 | 5.096 | -46.380 | 0.000 | 0.000 | 13.630 | 41.241 | 28.104 | 3.895 | 0.000 | 0.003 | 0.000 | 0.000 | -5.437 | 0.000 | -1.387 | -38.765 |
| LOBBY_ZN_1_FLR_1 | 0.000 | 0.000 | 35.576 | -14.196 | 0.000 | 0.000 | 9.490 | 32.975 | 8.802 | 15.932 | 0.000 | 1.026 | 0.000 | 0.000 | -9.723 | 0.000 | -69.275 | -10.608 |
| MECH_ZN_1_FLR_1 | 0.000 | 0.000 | 0.000 | -37.823 | 0.000 | 0.000 | 1.655 | 56.071 | 32.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -52.330 |
| BATH_ZN_1_FLR_1 | 0.000 | 0.000 | 0.072 | -19.001 | 0.000 | 0.000 | 4.765 | 25.366 | 9.780 | 4.473 | 0.000 | 0.002 | 0.000 | 0.000 | -5.935 | 0.000 | -1.525 | -17.996 |
| OFFICES_ZN_1_FLR_1 | 0.000 | 0.000 | 2.694 | -72.847 | 0.000 | 0.000 | 10.719 | 71.958 | 61.288 | 27.673 | 0.000 | 0.012 | 0.000 | 0.000 | -23.694 | 0.000 | -6.538 | -71.265 |
| GYM_ZN_1_FLR_1 | 0.000 | 0.000 | 1.052 | -111.687 | 0.000 | 0.000 | 53.920 | 65.666 | 22.969 | 28.756 | 0.000 | 0.006 | 0.000 | 0.000 | -23.216 | 0.000 | -2.813 | -34.653 |
| KITCHEN_ZN_1_FLR_1 | 0.000 | 0.000 | 0.007 | -163.420 | 0.000 | 0.000 | 11.455 | 29.905 | 138.079 | 4.121 | 0.000 | 0.002 | 0.000 | 0.000 | -6.119 | 0.000 | -1.651 | -12.378 |
| CAFETERIA_ZN_1_FLR_1 | 0.000 | 0.000 | 3.520 | -162.432 | 0.000 | 0.000 | 149.530 | 42.053 | 29.938 | 10.675 | 0.000 | 0.010 | 0.000 | 0.000 | -21.167 | 0.000 | -5.642 | -46.486 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.000 | 0.000 | 1.254 | -86.830 | 0.000 | 0.000 | 19.184 | 91.739 | 77.015 | 13.133 | 0.000 | 0.013 | 0.000 | 0.000 | -23.624 | 0.000 | -6.354 | -85.530 |
| Total Facility | 0.000 | 0.000 | 73.941 | -1792.793 | 0.000 | 0.000 | 732.822 | 1218.192 | 1115.552 | 321.674 | 0.000 | 1.353 | 0.000 | 0.000 | -366.596 | 0.000 | -160.392 | -1143.752 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 23-SEP-15:00 | 0.00 | 0.00 | 0.00 | -7086.20 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 2946.48 | 0.00 | 0.00 | 3486.41 | 0.00 | -0.00 | 0.00 | -16.44 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 04-OCT-13:50 | 0.00 | 0.00 | 0.00 | -28198.78 | 0.00 | 0.00 | 8480.36 | 6469.32 | 6325.65 | 12861.55 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -25.87 | -5912.23 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 | -4343.03 | 0.00 | 0.00 | 682.65 | 947.12 | 678.98 | 717.10 | 0.00 | 0.17 | 1317.01 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 | -4727.26 | 0.00 | 0.00 | 1760.08 | 1342.69 | 1312.87 | 2458.54 | 0.00 | 1.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2148.06 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 09-JUN-15:00 | 0.00 | 0.00 | 0.00 | -19382.99 | 0.00 | 0.00 | 8480.74 | 6469.32 | 6325.65 | 1137.48 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7.92 | -3022.28 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 23-SEP-15:00 | 0.00 | 0.00 | 0.00 | -6450.38 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 2888.70 | 0.00 | 0.00 | 2908.32 | 0.00 | -0.00 | 0.00 | -16.39 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 04-OCT-13:50 | 0.00 | 0.00 | 0.00 | -27814.64 | 0.00 | 0.00 | 8480.36 | 6469.32 | 6325.65 | 12602.52 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -25.87 | -6037.34 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 | -4317.64 | 0.00 | 0.00 | 682.65 | 947.12 | 678.98 | 717.14 | 0.00 | 0.17 | 1291.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 | -4731.98 | 0.00 | 0.00 | 1760.08 | 1342.69 | 1312.87 | 2463.32 | 0.00 | 1.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2148.12 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 09-JUN-15:00 | 0.00 | 0.00 | 0.00 | -19412.25 | 0.00 | 0.00 | 8480.74 | 6469.32 | 6325.65 | 1163.22 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7.92 | -3018.75 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 23-SEP-15:00 | 0.00 | 0.00 | 0.00 | -6736.95 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 2891.56 | 0.00 | 0.00 | 3192.05 | 0.00 | -0.00 | 0.00 | -16.41 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 04-OCT-13:50 | 0.00 | 0.00 | 0.00 | -28020.75 | 0.00 | 0.00 | 8480.36 | 6469.32 | 6325.65 | 12614.65 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -25.87 | -5843.36 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 | -4492.44 | 0.00 | 0.00 | 682.65 | 947.12 | 678.98 | 716.84 | 0.00 | 0.17 | 1466.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 04-MAY-15:00 | 0.00 | 0.00 | 0.00 | -4825.04 | 0.00 | 0.00 | 1760.08 | 1342.69 | 1312.87 | 2522.48 | 0.00 | 1.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2114.21 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 09-JUN-15:00 | 0.00 | 0.00 | 0.00 | -13305.25 | 0.00 | 0.00 | 5600.48 | 4272.19 | 4177.31 | 1050.60 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5.23 | -1790.11 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 28-JUN-15:00 | 0.00 | 0.00 | 0.00 | -8220.31 | 0.00 | 0.00 | 2880.29 | 2197.13 | 2864.44 | 689.38 | 0.00 | 6.87 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -417.79 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 12-JUN-07:02 | 0.00 | 0.00 | 0.00 | -15067.01 | 0.00 | 0.00 | 1905.19 | 2693.36 | 1930.85 | 7.78 | 0.00 | 0.00 | 8542.42 | 0.00 | -0.00 | 0.00 | -12.58 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 29-AUG-15:00 | 0.00 | 0.00 | 0.00 | -13121.09 | 0.00 | 0.00 | 146.40 | 1196.41 | 318.27 | 3007.62 | 0.00 | 12169.84 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3717.46 |
| MECH_ZN_1_FLR_1 | 15-JUL-17:21 | 0.00 | 0.00 | 0.00 | -13452.71 | 0.00 | 0.00 | 0.00 | 721.39 | 491.20 | 0.00 | 0.00 | 0.00 | 12240.12 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 22-JUL-18:47 | 0.00 | 0.00 | 0.00 | -8245.99 | 0.00 | 0.00 | 0.00 | 326.34 | 148.14 | 813.52 | 0.00 | 0.00 | 6994.58 | 0.00 | -0.00 | 0.00 | -36.59 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 06-AUG-15:21 | 0.00 | 0.00 | 0.00 | -27824.22 | 0.00 | 0.00 | 0.00 | 925.78 | 928.37 | 2200.97 | 0.00 | 0.00 | 23866.72 | 0.00 | -0.00 | 0.00 | -97.62 | 0.00 |
| GYM_ZN_1_FLR_1 | 24-JUL-05:01 | 0.00 | 0.00 | 0.00 | -28280.55 | 0.00 | 0.00 | 0.00 | 844.83 | 347.93 | 483.89 | 0.00 | 0.00 | 26615.94 | 0.00 | -0.00 | 0.00 | -12.04 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 08-FEB-06:01 | 0.00 | 0.00 | 0.00 | -68414.65 | 0.00 | 0.00 | 0.00 | 384.74 | 2721.46 | 0.00 | 0.00 | 0.00 | 65871.89 | 0.00 | -502.85 | 0.00 | -60.59 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 26-JUN-05:01 | 0.00 | 0.00 | 0.00 | -63277.93 | 0.00 | 0.00 | 0.00 | 541.04 | 799.79 | 0.00 | 0.00 | 0.00 | 63170.05 | 0.00 | -850.04 | 0.00 | -382.91 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 12-JUN-07:02 | 0.00 | 0.00 | 0.00 | -23472.61 | 0.00 | 0.00 | 2717.45 | 5991.24 | 5291.26 | 2890.77 | 0.00 | 0.00 | 6638.63 | 0.00 | -0.00 | 0.00 | -56.74 | 0.00 |
| Total Facility | 24-JUL-05:01 | 0.00 | 0.00 | 0.00 | -294316.48 | 0.00 | 0.00 | 0.00 | 15672.78 | 17874.24 | 5033.11 | 0.00 | 0.00 | 260905.66 | 0.00 | -4791.70 | 0.00 | -377.61 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 7035.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.69 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -619.97 | 0.00 | -31.67 | -8132.23 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 24555.59 | 0.00 | 0.00 | 0.00 | 0.00 | 6469.32 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1742.08 | 0.00 | -85.62 | -31149.74 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 5868.82 | 0.00 | 0.00 | 0.00 | 0.00 | 947.12 | 209.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -98.10 | 0.00 | -4.76 | -6922.66 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 6508.12 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.69 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -588.83 | 0.00 | -31.29 | -7635.92 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 23957.60 | 0.00 | 0.00 | 0.00 | 0.00 | 6469.32 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1579.98 | 0.00 | -84.14 | -30715.32 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 6992.96 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.69 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -610.36 | 0.00 | -31.66 | -8098.87 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 24220.67 | 0.00 | 0.00 | 0.00 | 0.00 | 6469.32 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1683.33 | 0.00 | -85.60 | -30873.58 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 5852.98 | 0.00 | 0.00 | 0.00 | 0.00 | 947.12 | 209.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -98.06 | 0.00 | -4.76 | -6906.87 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 6511.30 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.69 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -589.48 | 0.00 | -31.29 | -7638.46 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 23951.98 | 0.00 | 0.00 | 0.00 | 0.00 | 6469.32 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1583.26 | 0.00 | -84.14 | -30706.42 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 6997.34 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.69 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -611.26 | 0.00 | -31.66 | -8102.34 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 24322.05 | 0.00 | 0.00 | 0.00 | 0.00 | 6469.32 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1685.50 | 0.00 | -85.57 | -30972.83 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 5881.21 | 0.00 | 0.00 | 0.00 | 0.00 | 947.12 | 209.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -98.16 | 0.00 | -4.76 | -6934.99 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 6547.55 | 0.00 | 0.00 | 0.00 | 0.00 | 1342.69 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -597.26 | 0.00 | -31.29 | -7666.92 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 16046.85 | 0.00 | 0.00 | 0.00 | 0.00 | 4272.19 | 1289.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1082.84 | 0.00 | -55.53 | -20470.08 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 7887.42 | 0.00 | 0.00 | 0.00 | 0.00 | 2197.13 | 884.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -565.49 | 0.00 | -28.73 | -10374.49 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 02-JAN-07:11 | 0.00 | 0.00 | 12935.25 | 0.00 | 0.00 | 0.00 | 0.00 | 2693.36 | 595.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -182.30 | 0.00 | -16.84 | -16025.46 |
| LOBBY_ZN_1_FLR_1 | 06-JAN-07:10 | 0.00 | 0.00 | 13137.81 | 0.00 | 0.00 | 0.00 | 0.00 | 2153.53 | 186.66 | 0.00 | 0.00 | 0.00 | 14017.83 | 0.00 | -875.67 | 0.00 | -28620.16 | 0.00 |
| MECH_ZN_1_FLR_1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 02-JAN-07:01 | 0.00 | 0.00 | 4013.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1656.56 | 207.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -201.27 | 0.00 | -19.56 | -5656.48 |
| OFFICES_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 18433.50 | 0.00 | 0.00 | 0.00 | 0.00 | 4699.41 | 1299.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1378.59 | 0.00 | -67.10 | -22986.95 |
| GYM_ZN_1_FLR_1 | 02-JAN-06:01 | 0.00 | 0.00 | 15213.45 | 0.00 | 0.00 | 0.00 | 0.00 | 844.83 | 487.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -862.58 | 0.00 | -187.24 | -15495.56 |
| KITCHEN_ZN_1_FLR_1 | 21-NOV-07:02 | 0.00 | 0.00 | 3422.64 | 0.00 | 0.00 | 0.00 | 0.00 | 1953.00 | 2721.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -270.05 | 0.00 | -27.14 | -7799.91 |
| CAFETERIA_ZN_1_FLR_1 | 02-JAN-06:01 | 0.00 | 0.00 | 64558.75 | 0.00 | 0.00 | 0.00 | 0.00 | 541.04 | 799.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -749.57 | 0.00 | -411.71 | -64738.31 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 21-FEB-07:01 | 0.00 | 0.00 | 17312.09 | 0.00 | 0.00 | 0.00 | 0.00 | 5991.24 | 1633.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1265.50 | 0.00 | -63.76 | -23607.32 |
| Total Facility | 17-JAN-06:01 | -64411.66 | 64411.66 | 312884.72 | -64411.66 | 0.00 | 0.00 | 0.00 | 15672.78 | 23615.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20326.41 | 0.00 | -3930.22 | -263504.65 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| VAV_POD_1 | 29.0244 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 28.7697 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| PSZ-AC_1:6 | 1.5538 | 0.0000 | 26.9930 | 1.0000 | Calculated from schedules | 0.4528 | 1.5538 | 0.2914 | 1.0000 | Not calculated | 0.4528 | 0.2914 | ||
| PSZ-AC_2:7 | 2.6459 | 0.0000 | 339.0743 | 1.0000 | Calculated from schedules | 1.4882 | 2.6459 | 0.5625 | 1.0000 | Not calculated | 1.4882 | 0.5625 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| VAV_POD_1 | 15.0903 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 12.8290 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| PSZ-AC_1:6 | 1.5538 | 0.0000 | 26.9930 | 1.0000 | Calculated from schedules | 0.4528 | 1.5538 | 1.0000 | 1.0000 | Not calculated | 0.4528 | 0.2914 | ||
| PSZ-AC_2:7 | 2.6459 | 0.0000 | 339.0743 | 1.0000 | Calculated from schedules | 1.4882 | 2.6459 | 1.0000 | 1.0000 | Not calculated | 1.4882 | 0.5625 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.3340 | 0.000305 | 192.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.3340 | 0.000305 | 192.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.3340 | 0.000305 | 192.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 84.7686 | 0.001880 | 315.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 43.5953 | 0.001880 | 162.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 29.3880 | 0.000305 | 546.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 18.4080 | 0.000559 | 171.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 4.0690 | 0.000000 | 252.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.2270 | 0.000000 | 190.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 23.7365 | 0.000432 | 441.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 115.3101 | 0.001524 | 357.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | 0.009440 | 26.9930 | 0.001179 | 168.00 | 0.4528 | 1.0000 | 0.4528 | 1.000 | 0.4528 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | 0.000000 | 339.0743 | 0.004724 | 315.00 | 1.4882 | 1.0000 | 1.4882 | 1.000 | 1.4882 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 42.9540 | 0.000864 | 399.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| VAV_POD_1 | 0.00 | 0.001254 | 6388.0000 | 0.0000 | 0.0000 | 0.0000 | |
| PSZ-AC_1:6 | 0.009440 | 26.99 | 0.001179 | 168.0000 | 0.4528 | 0.4528 | 0.4528 |
| PSZ-AC_2:7 | 0.000000 | 339.07 | 0.004724 | 315.0000 | 1.4882 | 1.4882 | 1.4882 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6813 | 0.6813 | 0.2746 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8615 | 2.8615 | 1.3220 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5286 | 0.5286 | 0.1586 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5715 | 0.5715 | 0.2743 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2263 | 2.2263 | 1.3224 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6777 | 0.6777 | 0.2745 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8317 | 2.8317 | 1.3224 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5271 | 0.5271 | 0.1581 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5718 | 0.5718 | 0.2744 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.2272 | 2.2272 | 1.3207 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6782 | 0.6782 | 0.2740 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8427 | 2.8427 | 1.3219 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5319 | 0.5319 | 0.1596 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5750 | 0.5750 | 0.2743 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4928 | 1.4928 | 0.8733 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8274 | 0.8274 | 0.4484 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1107 | 1.1107 | 0.3332 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7396 | 0.7396 | 0.2219 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7930 | 0.7930 | 0.2379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5264 | 0.5264 | 0.1579 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6964 | 1.6964 | 0.5089 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7954 | 1.7954 | 0.8025 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5538 | 1.5538 | 1.5538 | No | 0.4528 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6459 | 2.6459 | 2.6459 | No | 1.4882 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7101 | 1.7101 | 0.5130 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| VAV_POD_1 | 29.0244 | 28.7697 | 29.0244 | 12.8290 | 0.0000 | 1.0000 |
| PSZ-AC_1:6 | 1.5538 | 1.5538 | 1.5538 | 1.5538 | 0.4528 | 1.0000 |
| PSZ-AC_2:7 | 2.6459 | 2.6459 | 2.6459 | 2.6459 | 1.4882 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3407 | 0.3407 | 0.2746 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4308 | 1.4308 | 1.3220 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2643 | 0.2643 | 0.1586 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2858 | 0.2858 | 0.2743 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3224 | 1.3224 | 1.3224 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3389 | 0.3389 | 0.2745 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4158 | 1.4158 | 1.3224 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2635 | 0.2635 | 0.1581 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2859 | 0.2859 | 0.2744 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3207 | 1.3207 | 1.3207 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3391 | 0.3391 | 0.2740 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4214 | 1.4214 | 1.3219 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2659 | 0.2659 | 0.1596 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2875 | 0.2875 | 0.2743 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8733 | 0.8733 | 0.8733 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4484 | 0.4484 | 0.4484 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5554 | 0.5554 | 0.3332 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3698 | 0.3698 | 0.2219 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3965 | 0.3965 | 0.2379 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.2632 | 0.2632 | 0.1579 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8482 | 0.8482 | 0.5089 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8977 | 0.8977 | 0.8025 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5538 | 1.5538 | 1.5538 | No | 0.4528 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6459 | 2.6459 | 2.6459 | No | 1.4882 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8551 | 0.8551 | 0.5130 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| VAV_POD_1 | 15.0903 | 12.8290 | 12.8290 | 12.8290 | 0.0000 | 1.0000 |
| PSZ-AC_1:6 | 1.5538 | 1.5538 | 1.5538 | 1.5538 | 0.4528 | 1.0000 |
| PSZ-AC_2:7 | 2.6459 | 2.6459 | 2.6459 | 2.6459 | 1.4882 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
| Total gross floor area [m2] | 6871.00 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 192.00 | 0.00 | 62.83 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 192.00 | 0.00 | 62.83 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 192.00 | 0.00 | 62.83 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 315.00 | 0.00 | 62.83 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 162.00 | 0.00 | 62.83 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 546.00 | 0.00 | 62.83 |
| LOBBY_ZN_1_FLR_1 | 171.00 | 171.00 | 0.00 | 62.83 |
| MECH_ZN_1_FLR_1 | 252.00 | 252.00 | 0.00 | 62.83 |
| BATH_ZN_1_FLR_1 | 190.00 | 190.00 | 0.00 | 62.83 |
| OFFICES_ZN_1_FLR_1 | 441.00 | 441.00 | 0.00 | 53.16 |
| GYM_ZN_1_FLR_1 | 357.00 | 357.00 | 0.00 | 62.83 |
| KITCHEN_ZN_1_FLR_1 | 168.00 | 168.00 | 0.00 | 62.83 |
| CAFETERIA_ZN_1_FLR_1 | 315.00 | 315.00 | 0.00 | 52.32 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 399.00 | 0.00 | 62.83 |
| Totals | 6871.00 | 6871.00 | 0.00 |
| Data | |
| Number of hours heating loads not met | 627.83 |
| Number of hours cooling loads not met | 12.00 |
| Number of hours not met | 639.83 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 321.74 | 239121.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heating -- Boiler | 0.00 | 0.00 | 261.48 | 387482.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 157.29 | 101509.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 1218.19 | 79557.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 92.49 | 5897.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 947.54 | 65099.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- Cooking | 149.71 | 9998.36 | 361.03 | 48084.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ReachInFreezer | 31.09 | 986.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ReachInRefrigerator | 23.02 | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Transformer | 17.61 | 1336.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 334.43 | 53859.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- General | 0.98 | 780.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 0.00 | 0.00 | 154.86 | 29275.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- General | 7.85 | 2172.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- LowTempRefrigeration | 15.12 | 1474.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- MedTempRefrigeration | 21.98 | 734.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 1196.31 | 3017.31 |
| Natural Gas | 361.03 | 1099.10 |
| Additional | 0.00 | 0.00 |
| Total | 1557.34 | 4116.41 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 177.29 |
| Space Heating | 0.00 |
| Space Cooling | 22.89 |
| Fans (All) | 48.67 |
| Service Water Heating | 0.00 |
| Receptacle Equipment | 167.57 |
| Miscellaneous (All) | 439.14 |
| Subtotal | 439.14 |
| Natural Gas [MJ/m2] | |
| Space Heating | 84.88 |
| Service Water Heating | 22.54 |
| Miscellaneous (All) | 159.96 |
| Subtotal | 159.96 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 29.59 |
| Space Heating | 14.17 |
| Space Cooling | 3.82 |
| Fans (All) | 8.12 |
| Service Water Heating | 3.76 |
| Receptacle Equipment | 36.74 |
| Miscellaneous | 3.79 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| LTG_SCH_GYM | 3903. | 8760. |
| LTG_SCH_CLASSROOM | 3903. | 8760. |
| LTG_SCH_LIBRARY | 3903. | 8760. |
| LTG_SCH_BATH | 3903. | 8760. |
| LTG_SCH_KITCHEN | 3903. | 8760. |
| LTG_SCH_OFFICE | 3903. | 8760. |
| LTG_SCH_LOBBY | 3903. | 8760. |
| LTG_SCH_MECHANICAL | 3903. | 8760. |
| LTG_SCH_COMPUTER_ROOM | 3903. | 8760. |
| LTG_SCH_CAFETERIA | 3903. | 8760. |
| LTG_SCH_CORRIDOR | 3903. | 8760. |
| BLDG_EQUIP_SCH | 3617. | 8760. |
| WALKIN_OCC_LGHT_SCH_2 | 2473. | 8760. |
| KITCHEN_ELEC_EQUIP_SCH | 1045. | 8760. |
| KITCHEN_GAS_EQUIP_SCH | 425. | 8760. |
| BLDG_OCC_SCH | 1755. | 3380. |
| BLDG_OCC_SCH_EXTEND | 2948. | 3380. |
| BLDG_OCC_SCH_OFFICES | 2197. | 3380. |
| BLDG_OCC_SCH_OFFICES_W_SB | 1743. | 2860. |
| OFFICES BINARY OCCUPANCY | 3380. | 3380. |
| BLDG_OCC_SCH_GYM | 1828. | 3380. |
| BLDG_OCC_SCH_CAFETERIA | 1687. | 2815. |
| INFIL_SCH | 6205. | 8760. |
| INFIL_SCH_PNNL | 6030. | 8760. |
| INFIL_DOOR_OPENING_SCH | 827. | 2860. |
| BLDG_SWH_SCH | 1227. | 3120. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| EXTERIOR_LGT_189_1 | 5940. | 8760. |
| WORK_EFF_SCH | 0. | 0. |
| KITCHEN_EXHAUST_SCH | 2860. | 2860. |
| MINOA_SCHED | 8760. | 8760. |
| BATH_ZN_1_FLR_1 SHW_DEFAULT LATENT FRACT SCHED | 438. | 8760. |
| BATH_ZN_1_FLR_1 SHW_DEFAULT SENSIBLE FRACT SCHED | 1752. | 8760. |
| KITCHEN_ZN_1_FLR_1 SHW_DEFAULT LATENT FRACT SCHED | 438. | 8760. |
| KITCHEN_ZN_1_FLR_1 SHW_DEFAULT SENSIBLE FRACT SCHED | 1752. | 8760. |
| KITCHEN_ZN_1_FLR_1_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
| EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 3380. | 3380. |
| EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6570. | 8760. |
| KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 2594. | 2860. |
| OFFICES_ZN_1_FLR_1_MDP_SCH | 2472. | 8240. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_SCH_YES_OPTIMUM | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
| CLGSETP_SCH_YES_OPTIMUM | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
| HTGSETP_SCH_SETBACK | MECH_ZN_1_FLR_1 DUAL SP CONTROL | January | 15.60 | 365 | 15.60 | 365 |
| CLGSETP_SCH_SETUP | MECH_ZN_1_FLR_1 DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
| HTGSETP_SCH_YES_OPTIMUM_W_SB | OFFICES_ZN_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
| CLGSETP_SCH_YES_OPTIMUM_W_SB | OFFICES_ZN_1_FLR_1 DUAL SP CONTROL | July | 24.56 | 63 | 26.70 | 365 |
| HTGSETP_SCH_NO_OPTIMUM | GYM_ZN_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
| CLGSETP_SCH_NO_OPTIMUM | GYM_ZN_1_FLR_1 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 8755.67 | 4.33 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 8755.67 | 4.33 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 8449.00 | 311.00 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 8753.33 | 6.67 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 8743.00 | 17.00 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 5362.33 | 3342.67 | 55.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 8693.50 | 66.50 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 5362.33 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 3342.67 | 55.00 | 0.00 | 0.00 |
| Average | 8607.06 | 150.74 | 2.20 | 0.00 | 0.00 |
| Sum | 215176.50 | 3768.50 | 55.00 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 141584.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 122876.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 47696.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 29108.33 | 3.67 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 4460.50 | 51.50 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 15303.50 | 4.50 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 38444.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 202800.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 44688.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 552560.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 70792.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 4460.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 552560.00 | 51.50 | 0.00 | 0.00 | 0.00 |
| Average | 106079.69 | 2.39 | 0.00 | 0.00 | 0.00 |
| Sum | 2651992.33 | 59.67 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 8750.00 | 10.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 8755.00 | 5.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 8751.50 | 8.50 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 8750.17 | 9.83 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 8755.00 | 5.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 8753.83 | 6.17 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 8309.00 | 451.00 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 8691.83 | 68.17 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 8659.67 | 100.33 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 4801.83 | 3808.50 | 149.67 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 8678.83 | 81.17 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 8745.67 | 14.33 | 0.00 | 0.00 | 0.00 |
| Min | 4801.83 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 3808.50 | 149.67 | 0.00 | 0.00 |
| Average | 8570.25 | 183.77 | 5.99 | 0.00 | 0.00 |
| Sum | 214256.17 | 4594.17 | 149.67 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 141584.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 122876.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 47696.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 29105.33 | 6.67 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 4414.50 | 97.50 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 15156.33 | 151.67 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 38444.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 202800.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 44533.67 | 154.33 | 0.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 550586.33 | 1973.67 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 70792.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 4414.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 550586.33 | 1973.67 | 0.00 | 0.00 | 0.00 |
| Average | 105986.73 | 95.35 | 0.00 | 0.00 | 0.00 |
| Sum | 2649668.17 | 2383.83 | 0.00 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:24
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME SCHOOLPRIMARY
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 4.496 |
| February | 5.822 |
| March | 8.326 |
| April | 10.851 |
| May | 12.973 |
| June | 15.587 |
| July | 17.665 |
| August | 18.800 |
| September | 15.086 |
| October | 11.426 |
| November | 8.070 |
| December | 5.416 |
| Annual Sum or Average | 11.241 |
| Minimum of Months | 4.496 |
| Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.101541E+10 | 2483.29 | 20-JAN-15:30 | 6.40 | 4.52 | 0.644526E+09 | 1171.76 | 20-JAN-15:39 | 6.13 | 4.37 |
| February | 0.134176E+10 | 3703.09 | 27-FEB-15:30 | 19.70 | 12.30 | 0.616649E+09 | 1277.21 | 27-FEB-15:20 | 19.70 | 12.30 |
| March | 0.221378E+10 | 3884.22 | 02-MAR-15:40 | 13.30 | 8.42 | 0.789031E+09 | 1277.23 | 17-MAR-14:20 | 12.40 | 8.39 |
| April | 0.253258E+10 | 6275.63 | 27-APR-14:50 | 27.02 | 17.21 | 0.734877E+09 | 1277.23 | 19-APR-14:20 | 27.02 | 17.21 |
| May | 0.354454E+10 | 6104.06 | 15-MAY-15:00 | 23.30 | 12.62 | 0.848967E+09 | 1277.23 | 09-MAY-14:20 | 23.30 | 12.62 |
| June | 0.376435E+10 | 5312.17 | 09-JUN-15:00 | 22.80 | 13.00 | 0.526452E+09 | 1277.24 | 13-JUN-14:20 | 11.67 | 9.65 |
| July | 0.295504E+10 | 4851.87 | 30-JUL-16:36 | 27.07 | 18.02 | 0.168335E+09 | 201.69 | 31-JUL-15:39 | 28.70 | 19.09 |
| August | 0.327460E+10 | 5891.90 | 12-AUG-16:00 | 25.10 | 16.77 | 0.193688E+09 | 201.69 | 09-AUG-15:39 | 25.10 | 16.77 |
| September | 0.334376E+10 | 7086.03 | 23-SEP-15:00 | 23.30 | 17.22 | 0.475609E+09 | 1277.23 | 27-SEP-14:20 | 12.97 | 9.79 |
| October | 0.274370E+10 | 6432.38 | 04-OCT-15:00 | 21.70 | 11.49 | 0.776812E+09 | 1277.23 | 03-OCT-14:20 | 21.70 | 11.49 |
| November | 0.174700E+10 | 3875.17 | 04-NOV-15:32 | 20.37 | 15.93 | 0.699856E+09 | 1277.05 | 02-NOV-14:39 | 20.37 | 15.93 |
| December | 0.115500E+10 | 2704.57 | 05-DEC-15:01 | 9.35 | 6.62 | 0.629386E+09 | 1248.50 | 05-DEC-15:09 | 9.35 | 6.62 |
| Annual Sum or Average | 0.296315E+11 | 0.710419E+10 | ||||||||
| Minimum of Months | 0.101541E+10 | 2483.29 | 6.40 | 4.52 | 0.168335E+09 | 201.69 | 6.13 | 4.37 | ||
| Maximum of Months | 0.376435E+10 | 7086.03 | 27.07 | 18.02 | 0.848967E+09 | 1277.24 | 28.70 | 19.09 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.715884E+10 | 12589.71 | 20-JAN-13:50 | 6.70 | 4.72 | 0.322622E+10 | 5865.87 | 20-JAN-13:00 | 6.70 | 4.72 |
| February | 0.835002E+10 | 17694.66 | 28-FEB-15:01 | 13.90 | 10.77 | 0.310877E+10 | 6153.96 | 07-FEB-15:20 | 13.90 | 10.77 |
| March | 0.124061E+11 | 18514.96 | 02-MAR-14:20 | 13.30 | 8.28 | 0.400870E+10 | 6153.96 | 23-MAR-14:20 | 11.83 | 8.08 |
| April | 0.130696E+11 | 26908.29 | 27-APR-14:20 | 26.47 | 16.98 | 0.366951E+10 | 6157.81 | 19-APR-11:50 | 26.47 | 16.98 |
| May | 0.174375E+11 | 25747.67 | 04-MAY-14:10 | 23.98 | 15.25 | 0.416248E+10 | 6153.94 | 09-MAY-14:20 | 12.03 | 9.99 |
| June | 0.180105E+11 | 23590.88 | 09-JUN-13:40 | 22.03 | 13.54 | 0.256613E+10 | 6153.96 | 13-JUN-14:20 | 11.67 | 9.65 |
| July | 0.133863E+11 | 19985.75 | 22-JUL-13:21 | 23.30 | 15.36 | 0.783831E+09 | 971.71 | 31-JUL-16:10 | 28.80 | 19.11 |
| August | 0.146955E+11 | 19805.34 | 06-AUG-15:21 | 23.75 | 15.72 | 0.916226E+09 | 971.72 | 09-AUG-16:10 | 29.25 | 19.08 |
| September | 0.158812E+11 | 26313.36 | 22-SEP-14:20 | 22.97 | 17.15 | 0.232867E+10 | 6153.93 | 27-SEP-14:20 | 12.97 | 9.79 |
| October | 0.141922E+11 | 28199.25 | 04-OCT-13:50 | 21.02 | 11.37 | 0.387229E+10 | 6153.92 | 03-OCT-14:20 | 21.02 | 11.37 |
| November | 0.101507E+11 | 17824.24 | 02-NOV-14:01 | 14.22 | 11.35 | 0.355567E+10 | 6153.90 | 02-NOV-14:20 | 14.03 | 11.32 |
| December | 0.766198E+10 | 13404.35 | 05-DEC-14:40 | 10.20 | 6.81 | 0.317549E+10 | 6152.74 | 05-DEC-14:50 | 10.10 | 6.91 |
| Annual Sum or Average | 0.152400E+12 | 0.353740E+11 | ||||||||
| Minimum of Months | 0.715884E+10 | 12589.71 | 6.70 | 4.72 | 0.783831E+09 | 971.71 | 6.70 | 4.72 | ||
| Maximum of Months | 0.180105E+11 | 28199.25 | 26.47 | 17.15 | 0.416248E+10 | 6157.81 | 29.25 | 19.11 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.310180E+09 | 1126.67 | 11-JAN-16:00 | 14.40 | 10.49 | 0.242911E+09 | 385.78 | 11-JAN-15:00 | 14.40 | 10.49 |
| February | 0.584669E+09 | 1927.26 | 28-FEB-15:01 | 13.90 | 10.77 | 0.226323E+09 | 447.72 | 28-FEB-15:00 | 13.90 | 10.60 |
| March | 0.128616E+10 | 2017.14 | 02-MAR-15:01 | 13.30 | 8.53 | 0.292423E+09 | 468.35 | 02-MAR-15:00 | 13.30 | 8.35 |
| April | 0.150144E+10 | 3897.31 | 27-APR-15:00 | 27.20 | 17.29 | 0.281131E+09 | 495.44 | 27-APR-13:50 | 27.20 | 17.29 |
| May | 0.236330E+10 | 4343.11 | 04-MAY-15:00 | 24.40 | 14.85 | 0.334561E+09 | 495.44 | 05-MAY-11:30 | 20.55 | 15.46 |
| June | 0.268449E+10 | 4124.56 | 09-JUN-15:00 | 22.80 | 13.00 | 0.208974E+09 | 495.44 | 09-JUN-13:09 | 22.80 | 13.00 |
| July | 0.182680E+10 | 2833.31 | 24-JUL-14:13 | 29.80 | 18.34 | 67926498.74 | 78.23 | 31-JUL-16:10 | 28.80 | 19.11 |
| August | 0.200165E+10 | 3103.36 | 10-AUG-15:40 | 30.87 | 18.81 | 77914130.31 | 78.23 | 09-AUG-15:50 | 30.87 | 18.81 |
| September | 0.208384E+10 | 3982.37 | 22-SEP-15:00 | 23.30 | 17.23 | 0.187257E+09 | 495.44 | 29-SEP-14:00 | 20.00 | 14.18 |
| October | 0.158992E+10 | 3496.83 | 04-OCT-15:00 | 21.70 | 11.49 | 0.297401E+09 | 495.44 | 03-OCT-14:20 | 21.70 | 11.49 |
| November | 0.949986E+09 | 2010.36 | 06-NOV-15:01 | 11.10 | 10.26 | 0.262380E+09 | 465.06 | 06-NOV-14:39 | 11.10 | 10.26 |
| December | 0.421078E+09 | 1210.87 | 05-DEC-15:50 | 6.75 | 4.97 | 0.233272E+09 | 404.54 | 05-DEC-15:00 | 6.10 | 4.53 |
| Annual Sum or Average | 0.176035E+11 | 0.271247E+10 | ||||||||
| Minimum of Months | 0.310180E+09 | 1126.67 | 6.75 | 4.97 | 67926498.74 | 78.23 | 6.10 | 4.53 | ||
| Maximum of Months | 0.268449E+10 | 4343.11 | 30.87 | 18.81 | 0.334561E+09 | 495.44 | 30.87 | 19.11 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.801092E+09 | 2091.73 | 11-JAN-15:10 | 14.40 | 10.49 | 0.632190E+09 | 1039.97 | 11-JAN-15:20 | 14.40 | 10.49 |
| February | 0.989389E+09 | 3317.43 | 28-FEB-15:01 | 13.90 | 10.77 | 0.585952E+09 | 1183.83 | 27-FEB-15:00 | 13.90 | 10.77 |
| March | 0.179851E+10 | 3361.20 | 02-MAR-15:01 | 13.30 | 8.53 | 0.739200E+09 | 1188.66 | 10-MAR-14:00 | 16.10 | 11.51 |
| April | 0.212529E+10 | 4460.64 | 27-APR-15:00 | 27.20 | 17.29 | 0.696753E+09 | 1277.21 | 28-APR-14:20 | 18.13 | 12.83 |
| May | 0.313194E+10 | 4727.63 | 04-MAY-15:00 | 24.40 | 14.85 | 0.833171E+09 | 1277.23 | 10-MAY-14:20 | 13.53 | 9.09 |
| June | 0.341629E+10 | 4485.85 | 09-JUN-15:00 | 22.80 | 13.00 | 0.519828E+09 | 1277.22 | 01-JUN-14:20 | 22.80 | 13.00 |
| July | 0.263419E+10 | 4271.95 | 15-JUL-17:21 | 23.05 | 17.76 | 0.158453E+09 | 201.04 | 24-JUL-16:10 | 28.80 | 18.46 |
| August | 0.275631E+10 | 3902.65 | 13-AUG-20:01 | 22.95 | 16.48 | 0.180883E+09 | 201.68 | 10-AUG-18:10 | 22.95 | 16.48 |
| September | 0.267496E+10 | 4395.45 | 22-SEP-15:00 | 23.30 | 17.23 | 0.460153E+09 | 1277.23 | 20-SEP-14:20 | 23.30 | 17.23 |
| October | 0.221934E+10 | 3903.25 | 04-OCT-15:00 | 21.70 | 11.49 | 0.737183E+09 | 1277.23 | 03-OCT-14:20 | 21.70 | 11.49 |
| November | 0.150409E+10 | 3394.38 | 02-NOV-14:01 | 14.22 | 11.35 | 0.672247E+09 | 1179.43 | 02-NOV-14:50 | 13.48 | 11.22 |
| December | 0.879048E+09 | 2134.73 | 01-DEC-15:40 | 8.33 | 6.41 | 0.605084E+09 | 1054.69 | 01-DEC-15:50 | 8.07 | 6.28 |
| Annual Sum or Average | 0.249305E+11 | 0.682110E+10 | ||||||||
| Minimum of Months | 0.801092E+09 | 2091.73 | 8.33 | 6.41 | 0.158453E+09 | 201.04 | 8.07 | 6.28 | ||
| Maximum of Months | 0.341629E+10 | 4727.63 | 27.20 | 17.76 | 0.833171E+09 | 1277.23 | 28.80 | 18.46 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.594934E+10 | 10824.22 | 27-JAN-14:10 | 9.72 | 8.09 | 0.312715E+10 | 5240.84 | 27-JAN-14:09 | 9.72 | 8.09 |
| February | 0.652702E+10 | 16349.02 | 28-FEB-15:01 | 13.90 | 10.77 | 0.291945E+10 | 5674.50 | 28-FEB-15:50 | 13.90 | 10.63 |
| March | 0.103888E+11 | 16603.42 | 17-MAR-14:01 | 12.30 | 8.34 | 0.375896E+10 | 5878.01 | 10-MAR-14:00 | 12.30 | 8.34 |
| April | 0.110932E+11 | 18283.58 | 28-APR-14:01 | 18.22 | 12.85 | 0.350727E+10 | 6153.81 | 28-APR-14:20 | 18.13 | 12.83 |
| May | 0.154241E+11 | 19286.98 | 04-MAY-14:50 | 24.32 | 14.93 | 0.410589E+10 | 6153.93 | 09-MAY-14:20 | 12.03 | 9.99 |
| June | 0.164413E+11 | 19387.99 | 09-JUN-15:00 | 22.80 | 13.00 | 0.253434E+10 | 6153.96 | 13-JUN-14:20 | 11.67 | 9.65 |
| July | 0.119363E+11 | 17805.82 | 15-JUL-17:21 | 23.05 | 17.76 | 0.729612E+09 | 878.05 | 24-JUL-13:00 | 29.40 | 18.12 |
| August | 0.125409E+11 | 17716.78 | 26-AUG-13:11 | 21.63 | 16.89 | 0.834063E+09 | 869.76 | 10-AUG-13:50 | 21.63 | 16.89 |
| September | 0.128180E+11 | 18285.89 | 20-SEP-14:01 | 17.88 | 13.25 | 0.225489E+10 | 6153.91 | 20-SEP-14:20 | 17.97 | 13.28 |
| October | 0.116251E+11 | 18092.39 | 04-OCT-14:03 | 21.20 | 11.42 | 0.369734E+10 | 6153.91 | 03-OCT-14:20 | 21.20 | 11.42 |
| November | 0.909761E+10 | 16758.41 | 02-NOV-14:01 | 14.22 | 11.35 | 0.340075E+10 | 5811.56 | 02-NOV-14:50 | 13.48 | 11.22 |
| December | 0.637820E+10 | 10985.47 | 29-DEC-15:02 | 10.60 | 8.76 | 0.301693E+10 | 5255.87 | 29-DEC-15:09 | 10.60 | 8.76 |
| Annual Sum or Average | 0.130220E+12 | 0.338866E+11 | ||||||||
| Minimum of Months | 0.594934E+10 | 10824.22 | 9.72 | 8.09 | 0.729612E+09 | 869.76 | 9.72 | 8.09 | ||
| Maximum of Months | 0.164413E+11 | 19387.99 | 24.32 | 17.76 | 0.410589E+10 | 6153.96 | 29.40 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.986273E+09 | 2436.40 | 20-JAN-15:30 | 6.40 | 4.52 | 0.642730E+09 | 1156.00 | 20-JAN-15:39 | 6.13 | 4.37 |
| February | 0.133225E+10 | 3648.23 | 27-FEB-15:30 | 19.70 | 12.30 | 0.615603E+09 | 1277.21 | 27-FEB-15:20 | 19.70 | 12.30 |
| March | 0.219763E+10 | 3848.76 | 02-MAR-15:40 | 13.30 | 8.42 | 0.787017E+09 | 1277.23 | 17-MAR-14:20 | 12.40 | 8.39 |
| April | 0.250498E+10 | 6208.28 | 27-APR-14:50 | 27.02 | 17.21 | 0.732771E+09 | 1277.23 | 19-APR-14:20 | 27.02 | 17.21 |
| May | 0.349637E+10 | 6006.78 | 15-MAY-15:00 | 23.30 | 12.62 | 0.847284E+09 | 1277.23 | 09-MAY-14:20 | 23.30 | 12.62 |
| June | 0.371136E+10 | 5227.86 | 09-JUN-15:00 | 22.80 | 13.00 | 0.525219E+09 | 1277.24 | 13-JUN-14:20 | 11.67 | 9.65 |
| July | 0.291665E+10 | 4570.26 | 15-JUL-17:21 | 23.05 | 17.76 | 0.167191E+09 | 201.69 | 31-JUL-15:39 | 28.70 | 19.09 |
| August | 0.323631E+10 | 5388.64 | 12-AUG-16:00 | 25.10 | 16.77 | 0.192957E+09 | 201.69 | 09-AUG-15:39 | 25.10 | 16.77 |
| September | 0.331183E+10 | 6450.24 | 23-SEP-15:00 | 23.30 | 17.22 | 0.475092E+09 | 1277.23 | 27-SEP-14:20 | 12.97 | 9.79 |
| October | 0.272782E+10 | 6396.96 | 04-OCT-15:00 | 21.70 | 11.49 | 0.775909E+09 | 1277.23 | 03-OCT-14:20 | 21.70 | 11.49 |
| November | 0.173325E+10 | 3692.26 | 02-NOV-14:01 | 14.22 | 11.35 | 0.697834E+09 | 1276.93 | 02-NOV-14:09 | 14.22 | 11.35 |
| December | 0.110428E+10 | 2604.90 | 05-DEC-14:50 | 10.10 | 6.91 | 0.624617E+09 | 1214.00 | 05-DEC-14:00 | 10.00 | 7.01 |
| Annual Sum or Average | 0.292590E+11 | 0.708422E+10 | ||||||||
| Minimum of Months | 0.986273E+09 | 2436.40 | 6.40 | 4.52 | 0.167191E+09 | 201.69 | 6.13 | 4.37 | ||
| Maximum of Months | 0.371136E+10 | 6450.24 | 27.02 | 17.76 | 0.847284E+09 | 1277.24 | 28.70 | 19.09 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.703027E+10 | 12316.96 | 20-JAN-13:50 | 6.70 | 4.72 | 0.321248E+10 | 5769.58 | 20-JAN-13:00 | 6.70 | 4.72 |
| February | 0.832183E+10 | 17694.02 | 08-FEB-15:01 | 7.70 | 3.86 | 0.310216E+10 | 6153.95 | 08-FEB-15:20 | 7.60 | 3.86 |
| March | 0.123472E+11 | 18215.34 | 02-MAR-14:20 | 13.30 | 8.28 | 0.400223E+10 | 6153.96 | 23-MAR-14:20 | 11.83 | 8.08 |
| April | 0.129669E+11 | 26505.37 | 27-APR-14:20 | 26.47 | 16.98 | 0.366538E+10 | 6153.96 | 18-APR-14:20 | 26.47 | 16.98 |
| May | 0.172495E+11 | 25318.26 | 04-MAY-14:10 | 23.98 | 15.25 | 0.415994E+10 | 6153.94 | 09-MAY-14:20 | 12.03 | 9.99 |
| June | 0.177902E+11 | 23175.62 | 09-JUN-13:40 | 22.03 | 13.54 | 0.256260E+10 | 6153.96 | 13-JUN-14:20 | 11.67 | 9.65 |
| July | 0.132228E+11 | 19847.56 | 22-JUL-13:21 | 23.30 | 15.36 | 0.777288E+09 | 971.70 | 31-JUL-16:10 | 28.80 | 19.11 |
| August | 0.145225E+11 | 19593.33 | 06-AUG-15:21 | 23.75 | 15.72 | 0.910293E+09 | 971.70 | 09-AUG-16:10 | 29.25 | 19.08 |
| September | 0.157027E+11 | 26015.24 | 22-SEP-14:20 | 22.97 | 17.15 | 0.232793E+10 | 6153.93 | 27-SEP-14:20 | 12.97 | 9.79 |
| October | 0.140930E+11 | 27815.13 | 04-OCT-13:50 | 21.02 | 11.37 | 0.386986E+10 | 6153.92 | 03-OCT-14:20 | 21.02 | 11.37 |
| November | 0.101085E+11 | 17820.76 | 02-NOV-14:01 | 14.22 | 11.35 | 0.354641E+10 | 6153.90 | 02-NOV-14:20 | 14.03 | 11.32 |
| December | 0.742850E+10 | 12824.07 | 05-DEC-14:30 | 10.30 | 6.71 | 0.314139E+10 | 5946.35 | 05-DEC-14:39 | 10.20 | 6.81 |
| Annual Sum or Average | 0.150784E+12 | 0.352780E+11 | ||||||||
| Minimum of Months | 0.703027E+10 | 12316.96 | 6.70 | 3.86 | 0.777288E+09 | 971.70 | 6.70 | 3.86 | ||
| Maximum of Months | 0.177902E+11 | 27815.13 | 26.47 | 17.15 | 0.415994E+10 | 6153.96 | 29.25 | 19.11 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.299507E+09 | 1119.56 | 27-JAN-14:10 | 9.72 | 8.09 | 0.242818E+09 | 384.29 | 11-JAN-15:00 | 9.72 | 8.09 |
| February | 0.580958E+09 | 1917.64 | 28-FEB-15:01 | 13.90 | 10.77 | 0.226208E+09 | 446.84 | 28-FEB-15:00 | 13.90 | 10.60 |
| March | 0.128069E+10 | 2007.63 | 02-MAR-15:01 | 13.30 | 8.53 | 0.292223E+09 | 467.56 | 02-MAR-15:00 | 13.30 | 8.35 |
| April | 0.149403E+10 | 3874.89 | 27-APR-15:00 | 27.20 | 17.29 | 0.280923E+09 | 495.44 | 27-APR-13:50 | 27.20 | 17.29 |
| May | 0.234473E+10 | 4317.71 | 04-MAY-15:00 | 24.40 | 14.85 | 0.334443E+09 | 495.44 | 05-MAY-09:09 | 15.97 | 13.48 |
| June | 0.265779E+10 | 4098.32 | 09-JUN-15:00 | 22.80 | 13.00 | 0.208891E+09 | 495.44 | 09-JUN-13:09 | 22.80 | 13.00 |
| July | 0.181029E+10 | 2783.87 | 24-JUL-14:13 | 29.80 | 18.34 | 67718007.63 | 78.23 | 31-JUL-16:10 | 28.80 | 19.11 |
| August | 0.198150E+10 | 3058.24 | 10-AUG-15:40 | 30.87 | 18.81 | 77758094.66 | 78.23 | 09-AUG-15:50 | 30.87 | 18.81 |
| September | 0.206782E+10 | 3970.52 | 22-SEP-15:00 | 23.30 | 17.23 | 0.187242E+09 | 495.44 | 29-SEP-14:00 | 20.00 | 14.18 |
| October | 0.158163E+10 | 3476.16 | 04-OCT-15:00 | 21.70 | 11.49 | 0.297315E+09 | 495.44 | 03-OCT-14:20 | 21.70 | 11.49 |
| November | 0.942646E+09 | 1996.59 | 06-NOV-15:01 | 11.10 | 10.26 | 0.262099E+09 | 463.19 | 06-NOV-14:39 | 11.10 | 10.26 |
| December | 0.388471E+09 | 1174.78 | 01-DEC-15:35 | 8.33 | 6.41 | 0.232785E+09 | 397.15 | 01-DEC-15:50 | 8.07 | 6.28 |
| Annual Sum or Average | 0.174300E+11 | 0.271042E+10 | ||||||||
| Minimum of Months | 0.299507E+09 | 1119.56 | 8.33 | 6.41 | 67718007.63 | 78.23 | 8.07 | 6.28 | ||
| Maximum of Months | 0.265779E+10 | 4317.71 | 30.87 | 18.81 | 0.334443E+09 | 495.44 | 30.87 | 19.11 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.800370E+09 | 2091.09 | 11-JAN-15:10 | 14.40 | 10.49 | 0.632166E+09 | 1039.51 | 11-JAN-15:20 | 14.40 | 10.49 |
| February | 0.989772E+09 | 3318.50 | 28-FEB-15:01 | 13.90 | 10.77 | 0.585953E+09 | 1183.81 | 27-FEB-15:00 | 13.90 | 10.77 |
| March | 0.179928E+10 | 3361.71 | 02-MAR-15:01 | 13.30 | 8.53 | 0.739254E+09 | 1188.96 | 10-MAR-14:00 | 16.10 | 11.51 |
| April | 0.212671E+10 | 4464.51 | 27-APR-15:00 | 27.20 | 17.29 | 0.696850E+09 | 1277.21 | 28-APR-14:20 | 18.13 | 12.83 |
| May | 0.313479E+10 | 4732.34 | 04-MAY-15:00 | 24.40 | 14.85 | 0.833273E+09 | 1277.23 | 10-MAY-14:20 | 13.53 | 9.09 |
| June | 0.341926E+10 | 4492.19 | 09-JUN-15:00 | 22.80 | 13.00 | 0.519887E+09 | 1277.22 | 01-JUN-14:20 | 22.80 | 13.00 |
| July | 0.263453E+10 | 4273.20 | 15-JUL-17:21 | 23.05 | 17.76 | 0.158442E+09 | 201.09 | 24-JUL-16:10 | 28.80 | 18.46 |
| August | 0.275656E+10 | 3902.72 | 13-AUG-20:01 | 22.95 | 16.48 | 0.180861E+09 | 201.68 | 10-AUG-18:10 | 22.95 | 16.48 |
| September | 0.267576E+10 | 4399.48 | 22-SEP-15:00 | 23.30 | 17.23 | 0.460150E+09 | 1277.23 | 20-SEP-14:20 | 23.30 | 17.23 |
| October | 0.221986E+10 | 3904.03 | 04-OCT-15:00 | 21.70 | 11.49 | 0.737150E+09 | 1277.23 | 03-OCT-14:20 | 21.70 | 11.49 |
| November | 0.150306E+10 | 3394.92 | 02-NOV-14:01 | 14.22 | 11.35 | 0.672130E+09 | 1179.18 | 02-NOV-14:50 | 13.48 | 11.22 |
| December | 0.875549E+09 | 2135.23 | 01-DEC-15:40 | 8.33 | 6.41 | 0.604927E+09 | 1054.59 | 01-DEC-15:50 | 8.07 | 6.28 |
| Annual Sum or Average | 0.249355E+11 | 0.682104E+10 | ||||||||
| Minimum of Months | 0.800370E+09 | 2091.09 | 8.33 | 6.41 | 0.158442E+09 | 201.09 | 8.07 | 6.28 | ||
| Maximum of Months | 0.341926E+10 | 4732.34 | 27.20 | 17.76 | 0.833273E+09 | 1277.23 | 28.80 | 18.46 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.593842E+10 | 10817.53 | 27-JAN-14:10 | 9.72 | 8.09 | 0.312743E+10 | 5243.28 | 27-JAN-14:09 | 9.72 | 8.09 |
| February | 0.652370E+10 | 16335.71 | 28-FEB-15:01 | 13.90 | 10.77 | 0.292034E+10 | 5676.92 | 28-FEB-15:50 | 13.90 | 10.63 |
| March | 0.103856E+11 | 16595.87 | 17-MAR-14:01 | 12.30 | 8.34 | 0.376067E+10 | 5882.48 | 10-MAR-14:00 | 12.30 | 8.34 |
| April | 0.110910E+11 | 18261.41 | 28-APR-14:01 | 18.22 | 12.85 | 0.350927E+10 | 6153.81 | 28-APR-14:20 | 18.13 | 12.83 |
| May | 0.154286E+11 | 19311.18 | 04-MAY-14:50 | 24.32 | 14.93 | 0.410736E+10 | 6153.93 | 09-MAY-14:20 | 12.03 | 9.99 |
| June | 0.164436E+11 | 19417.26 | 09-JUN-15:00 | 22.80 | 13.00 | 0.253528E+10 | 6153.96 | 13-JUN-14:20 | 11.67 | 9.65 |
| July | 0.119280E+11 | 17786.01 | 15-JUL-17:21 | 23.05 | 17.76 | 0.729907E+09 | 878.71 | 24-JUL-13:00 | 29.40 | 18.12 |
| August | 0.125312E+11 | 17697.69 | 26-AUG-13:11 | 21.63 | 16.89 | 0.834310E+09 | 870.13 | 10-AUG-13:50 | 21.63 | 16.89 |
| September | 0.128112E+11 | 18284.70 | 22-SEP-14:40 | 23.13 | 17.19 | 0.225565E+10 | 6153.91 | 20-SEP-14:20 | 23.13 | 17.19 |
| October | 0.116187E+11 | 18070.89 | 04-OCT-14:03 | 21.20 | 11.42 | 0.369874E+10 | 6153.91 | 03-OCT-14:20 | 21.20 | 11.42 |
| November | 0.908718E+10 | 16741.79 | 02-NOV-14:01 | 14.22 | 11.35 | 0.340129E+10 | 5813.21 | 02-NOV-14:50 | 13.48 | 11.22 |
| December | 0.635166E+10 | 10977.24 | 29-DEC-15:02 | 10.60 | 8.76 | 0.301601E+10 | 5257.85 | 29-DEC-15:09 | 10.60 | 8.76 |
| Annual Sum or Average | 0.130139E+12 | 0.338963E+11 | ||||||||
| Minimum of Months | 0.593842E+10 | 10817.53 | 9.72 | 8.09 | 0.729907E+09 | 870.13 | 9.72 | 8.09 | ||
| Maximum of Months | 0.164436E+11 | 19417.26 | 24.32 | 17.76 | 0.410736E+10 | 6153.96 | 29.40 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.100001E+10 | 2459.46 | 20-JAN-15:30 | 6.40 | 4.52 | 0.643739E+09 | 1165.41 | 20-JAN-15:39 | 6.13 | 4.37 |
| February | 0.134135E+10 | 3686.35 | 27-FEB-15:30 | 19.70 | 12.30 | 0.616533E+09 | 1277.21 | 27-FEB-15:20 | 19.70 | 12.30 |
| March | 0.221709E+10 | 3883.52 | 02-MAR-15:40 | 13.30 | 8.42 | 0.789387E+09 | 1277.23 | 17-MAR-14:20 | 12.40 | 8.39 |
| April | 0.252518E+10 | 6240.07 | 27-APR-14:50 | 27.02 | 17.21 | 0.734940E+09 | 1277.23 | 19-APR-14:20 | 27.02 | 17.21 |
| May | 0.351490E+10 | 6042.97 | 15-MAY-15:00 | 23.30 | 12.62 | 0.848578E+09 | 1277.23 | 09-MAY-14:20 | 23.30 | 12.62 |
| June | 0.373273E+10 | 5254.69 | 09-JUN-15:00 | 22.80 | 13.00 | 0.526067E+09 | 1277.24 | 13-JUN-14:20 | 11.67 | 9.65 |
| July | 0.293880E+10 | 4843.49 | 30-JUL-16:36 | 27.07 | 18.02 | 0.167974E+09 | 201.69 | 31-JUL-15:39 | 28.70 | 19.09 |
| August | 0.326087E+10 | 5685.78 | 12-AUG-16:00 | 25.10 | 16.77 | 0.193553E+09 | 201.69 | 09-AUG-15:39 | 25.10 | 16.77 |
| September | 0.333216E+10 | 6736.79 | 23-SEP-15:00 | 23.30 | 17.22 | 0.475929E+09 | 1277.23 | 27-SEP-14:20 | 12.97 | 9.79 |
| October | 0.274624E+10 | 6419.37 | 04-OCT-15:00 | 21.70 | 11.49 | 0.777934E+09 | 1277.23 | 03-OCT-14:20 | 21.70 | 11.49 |
| November | 0.175356E+10 | 3893.60 | 04-NOV-15:32 | 20.37 | 15.93 | 0.700369E+09 | 1277.01 | 02-NOV-14:09 | 20.37 | 15.93 |
| December | 0.112491E+10 | 2643.77 | 05-DEC-14:50 | 10.10 | 6.91 | 0.626544E+09 | 1229.30 | 05-DEC-14:00 | 10.00 | 7.01 |
| Annual Sum or Average | 0.294878E+11 | 0.710155E+10 | ||||||||
| Minimum of Months | 0.100001E+10 | 2459.46 | 6.40 | 4.52 | 0.167974E+09 | 201.69 | 6.13 | 4.37 | ||
| Maximum of Months | 0.373273E+10 | 6736.79 | 27.07 | 18.02 | 0.848578E+09 | 1277.24 | 28.70 | 19.09 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.714111E+10 | 12461.67 | 20-JAN-13:50 | 6.70 | 4.72 | 0.322199E+10 | 5821.65 | 20-JAN-13:00 | 6.70 | 4.72 |
| February | 0.840325E+10 | 17709.56 | 28-FEB-15:01 | 13.90 | 10.77 | 0.311054E+10 | 6153.96 | 07-FEB-15:20 | 13.90 | 10.77 |
| March | 0.125076E+11 | 18552.84 | 02-MAR-14:20 | 13.30 | 8.28 | 0.401888E+10 | 6153.96 | 23-MAR-14:20 | 11.83 | 8.08 |
| April | 0.131254E+11 | 26767.16 | 27-APR-14:20 | 26.47 | 16.98 | 0.367747E+10 | 6158.22 | 19-APR-11:50 | 26.47 | 16.98 |
| May | 0.174001E+11 | 25526.87 | 04-MAY-14:10 | 23.98 | 15.25 | 0.416612E+10 | 6153.94 | 09-MAY-14:20 | 12.03 | 9.99 |
| June | 0.179638E+11 | 23410.80 | 09-JUN-13:40 | 22.03 | 13.54 | 0.256746E+10 | 6153.96 | 13-JUN-14:20 | 11.67 | 9.65 |
| July | 0.133611E+11 | 19996.79 | 22-JUL-13:21 | 23.30 | 15.36 | 0.782484E+09 | 971.71 | 31-JUL-16:10 | 28.80 | 19.11 |
| August | 0.146697E+11 | 19738.75 | 06-AUG-15:21 | 23.75 | 15.72 | 0.915361E+09 | 971.71 | 09-AUG-16:10 | 29.25 | 19.08 |
| September | 0.158697E+11 | 26221.52 | 22-SEP-14:20 | 22.97 | 17.15 | 0.233253E+10 | 6153.95 | 25-SEP-08:20 | 13.90 | 13.90 |
| October | 0.142478E+11 | 28021.23 | 04-OCT-13:50 | 21.02 | 11.37 | 0.388297E+10 | 6153.95 | 13-OCT-14:20 | 11.70 | 8.32 |
| November | 0.102712E+11 | 17824.10 | 02-NOV-14:01 | 14.22 | 11.35 | 0.356709E+10 | 6153.97 | 10-NOV-15:20 | 9.63 | 6.72 |
| December | 0.757009E+10 | 13028.66 | 05-DEC-14:40 | 10.20 | 6.81 | 0.315665E+10 | 6019.93 | 05-DEC-14:50 | 10.10 | 6.91 |
| Annual Sum or Average | 0.152531E+12 | 0.353996E+11 | ||||||||
| Minimum of Months | 0.714111E+10 | 12461.67 | 6.70 | 4.72 | 0.782484E+09 | 971.71 | 6.70 | 4.72 | ||
| Maximum of Months | 0.179638E+11 | 28021.23 | 26.47 | 17.15 | 0.416612E+10 | 6158.22 | 29.25 | 19.11 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.339277E+09 | 1146.62 | 27-JAN-14:10 | 9.72 | 8.09 | 0.243115E+09 | 387.85 | 12-JAN-15:00 | 9.72 | 8.09 |
| February | 0.631202E+09 | 1965.75 | 28-FEB-15:01 | 13.90 | 10.77 | 0.227255E+09 | 453.78 | 28-FEB-15:00 | 13.90 | 10.60 |
| March | 0.134552E+10 | 2055.47 | 02-MAR-15:01 | 13.30 | 8.53 | 0.296323E+09 | 474.38 | 02-MAR-15:00 | 13.30 | 8.35 |
| April | 0.156700E+10 | 4095.20 | 27-APR-15:00 | 27.20 | 17.29 | 0.285021E+09 | 495.44 | 27-APR-13:50 | 27.20 | 17.29 |
| May | 0.247879E+10 | 4492.52 | 04-MAY-15:00 | 24.40 | 14.85 | 0.336272E+09 | 495.44 | 05-MAY-11:30 | 20.55 | 15.46 |
| June | 0.285401E+10 | 4283.60 | 09-JUN-15:00 | 22.80 | 13.00 | 0.209823E+09 | 495.44 | 09-JUN-13:09 | 22.80 | 13.00 |
| July | 0.190217E+10 | 3137.76 | 24-JUL-14:13 | 29.80 | 18.34 | 68892195.63 | 78.23 | 31-JUL-15:00 | 28.90 | 19.18 |
| August | 0.210144E+10 | 3374.91 | 10-AUG-15:40 | 30.87 | 18.81 | 78809659.86 | 78.23 | 09-AUG-15:50 | 30.87 | 18.81 |
| September | 0.221636E+10 | 4136.44 | 22-SEP-15:00 | 23.30 | 17.23 | 0.188484E+09 | 495.44 | 29-SEP-14:00 | 20.00 | 14.18 |
| October | 0.165229E+10 | 3641.65 | 04-OCT-15:00 | 21.70 | 11.49 | 0.300980E+09 | 495.44 | 05-OCT-11:20 | 15.37 | 10.16 |
| November | 0.102110E+10 | 2051.81 | 06-NOV-15:01 | 11.10 | 10.26 | 0.265183E+09 | 471.80 | 06-NOV-14:39 | 11.10 | 10.26 |
| December | 0.446032E+09 | 1210.82 | 01-DEC-15:40 | 8.33 | 6.41 | 0.233457E+09 | 402.63 | 01-DEC-15:50 | 8.07 | 6.28 |
| Annual Sum or Average | 0.185552E+11 | 0.273362E+10 | ||||||||
| Minimum of Months | 0.339277E+09 | 1146.62 | 8.33 | 6.41 | 68892195.63 | 78.23 | 8.07 | 6.28 | ||
| Maximum of Months | 0.285401E+10 | 4492.52 | 30.87 | 18.81 | 0.336272E+09 | 495.44 | 30.87 | 19.18 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.806266E+09 | 2095.39 | 11-JAN-15:10 | 14.40 | 10.49 | 0.632448E+09 | 1041.27 | 11-JAN-15:20 | 14.40 | 10.49 |
| February | 0.100159E+10 | 3335.38 | 28-FEB-15:01 | 13.90 | 10.77 | 0.586894E+09 | 1190.86 | 27-FEB-15:00 | 13.90 | 10.77 |
| March | 0.183079E+10 | 3376.38 | 02-MAR-15:01 | 13.30 | 8.53 | 0.742570E+09 | 1196.49 | 10-MAR-14:00 | 16.10 | 11.51 |
| April | 0.216464E+10 | 4551.84 | 27-APR-15:00 | 27.20 | 17.29 | 0.701839E+09 | 1277.21 | 28-APR-14:20 | 18.13 | 12.83 |
| May | 0.318818E+10 | 4825.41 | 04-MAY-15:00 | 24.40 | 14.85 | 0.837391E+09 | 1277.23 | 09-MAY-14:20 | 12.03 | 9.99 |
| June | 0.348199E+10 | 4600.20 | 09-JUN-15:00 | 22.80 | 13.00 | 0.522530E+09 | 1277.23 | 13-JUN-14:20 | 11.67 | 9.65 |
| July | 0.268721E+10 | 4324.04 | 15-JUL-17:21 | 23.05 | 17.76 | 0.160263E+09 | 201.67 | 24-JUL-18:19 | 28.53 | 17.76 |
| August | 0.280201E+10 | 3935.93 | 13-AUG-20:01 | 22.95 | 16.48 | 0.182406E+09 | 201.68 | 10-AUG-18:10 | 22.95 | 16.48 |
| September | 0.270873E+10 | 4469.15 | 22-SEP-15:00 | 23.30 | 17.23 | 0.462134E+09 | 1277.23 | 20-SEP-14:20 | 23.30 | 17.23 |
| October | 0.224359E+10 | 3950.61 | 04-OCT-15:00 | 21.70 | 11.49 | 0.740235E+09 | 1277.23 | 03-OCT-14:20 | 21.70 | 11.49 |
| November | 0.152069E+10 | 3412.39 | 02-NOV-14:01 | 14.22 | 11.35 | 0.673978E+09 | 1185.74 | 02-NOV-14:50 | 13.48 | 11.22 |
| December | 0.881075E+09 | 2141.69 | 01-DEC-15:40 | 8.33 | 6.41 | 0.605353E+09 | 1057.07 | 01-DEC-15:50 | 8.07 | 6.28 |
| Annual Sum or Average | 0.253167E+11 | 0.684804E+10 | ||||||||
| Minimum of Months | 0.806266E+09 | 2095.39 | 8.33 | 6.41 | 0.160263E+09 | 201.67 | 8.07 | 6.28 | ||
| Maximum of Months | 0.348199E+10 | 4825.41 | 27.20 | 17.76 | 0.837391E+09 | 1277.23 | 28.53 | 17.76 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.392729E+10 | 7182.84 | 27-JAN-14:10 | 9.72 | 8.09 | 0.206688E+10 | 3472.85 | 27-JAN-14:09 | 9.72 | 8.09 |
| February | 0.434917E+10 | 10896.76 | 28-FEB-15:01 | 13.90 | 10.77 | 0.193303E+10 | 3779.58 | 28-FEB-15:50 | 13.90 | 10.63 |
| March | 0.699372E+10 | 11079.51 | 17-MAR-14:01 | 12.30 | 8.34 | 0.249718E+10 | 3922.41 | 10-MAR-14:00 | 12.30 | 8.34 |
| April | 0.747499E+10 | 12220.66 | 27-APR-15:00 | 27.20 | 17.29 | 0.233667E+10 | 4063.84 | 28-APR-14:20 | 18.13 | 12.83 |
| May | 0.104320E+11 | 13182.08 | 04-MAY-14:50 | 24.32 | 14.93 | 0.272378E+10 | 4063.92 | 09-MAY-14:20 | 12.03 | 9.99 |
| June | 0.111384E+11 | 13308.68 | 09-JUN-15:00 | 22.80 | 13.00 | 0.168380E+10 | 4063.94 | 13-JUN-14:20 | 11.67 | 9.65 |
| July | 0.810812E+10 | 11993.17 | 15-JUL-17:21 | 23.05 | 17.76 | 0.489996E+09 | 591.14 | 24-JUL-13:00 | 29.40 | 18.12 |
| August | 0.847711E+10 | 11910.38 | 26-AUG-13:11 | 21.63 | 16.89 | 0.557747E+09 | 582.60 | 10-AUG-13:50 | 21.63 | 16.89 |
| September | 0.861472E+10 | 12412.74 | 22-SEP-14:40 | 23.13 | 17.19 | 0.149683E+10 | 4063.91 | 27-SEP-14:20 | 12.97 | 9.79 |
| October | 0.777744E+10 | 11962.05 | 04-OCT-14:03 | 21.20 | 11.42 | 0.245445E+10 | 4063.91 | 03-OCT-14:20 | 21.20 | 11.42 |
| November | 0.607500E+10 | 11164.63 | 02-NOV-14:01 | 14.22 | 11.35 | 0.225499E+10 | 3870.91 | 02-NOV-14:50 | 13.48 | 11.22 |
| December | 0.420331E+10 | 7283.21 | 29-DEC-15:02 | 10.60 | 8.76 | 0.199357E+10 | 3480.38 | 29-DEC-15:09 | 10.60 | 8.76 |
| Annual Sum or Average | 0.875713E+11 | 0.224889E+11 | ||||||||
| Minimum of Months | 0.392729E+10 | 7182.84 | 9.72 | 8.09 | 0.489996E+09 | 582.60 | 9.72 | 8.09 | ||
| Maximum of Months | 0.111384E+11 | 13308.68 | 27.20 | 17.76 | 0.272378E+10 | 4063.94 | 29.40 | 18.12 |
Report: ZoneCoolingSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.315048E+10 | 4014.34 | 27-JAN-14:10 | 9.72 | 8.09 | 0.162830E+10 | 1895.49 | 27-JAN-14:09 | 9.72 | 8.09 |
| February | 0.316582E+10 | 5948.73 | 28-FEB-15:01 | 13.90 | 10.77 | 0.154228E+10 | 2067.22 | 28-FEB-15:50 | 13.90 | 10.63 |
| March | 0.448169E+10 | 6047.40 | 17-MAR-14:01 | 12.30 | 8.34 | 0.203983E+10 | 2090.03 | 15-MAR-15:20 | 12.30 | 8.34 |
| April | 0.464858E+10 | 7421.33 | 27-APR-14:50 | 27.02 | 17.21 | 0.188121E+10 | 2090.03 | 18-APR-15:20 | 27.02 | 17.21 |
| May | 0.649263E+10 | 7834.75 | 04-MAY-14:40 | 24.23 | 15.01 | 0.213205E+10 | 2090.03 | 10-MAY-15:20 | 13.17 | 9.27 |
| June | 0.756012E+10 | 8221.47 | 28-JUN-15:00 | 26.10 | 15.54 | 0.214294E+10 | 2090.03 | 13-JUN-14:20 | 26.10 | 15.54 |
| July | 0.486074E+10 | 6548.08 | 15-JUL-17:21 | 23.05 | 17.76 | 0.943706E+09 | 1099.97 | 24-JUL-13:20 | 28.67 | 18.27 |
| August | 0.515709E+10 | 6558.16 | 26-AUG-13:11 | 21.63 | 16.89 | 0.107572E+10 | 1099.98 | 09-AUG-13:20 | 21.63 | 16.89 |
| September | 0.585576E+10 | 7715.18 | 14-SEP-14:30 | 23.90 | 17.04 | 0.188964E+10 | 2090.02 | 26-SEP-15:20 | 12.23 | 11.32 |
| October | 0.478843E+10 | 6601.75 | 04-OCT-14:40 | 21.50 | 11.47 | 0.197443E+10 | 2090.03 | 20-OCT-14:20 | 12.40 | 11.26 |
| November | 0.400122E+10 | 6049.81 | 03-NOV-14:01 | 13.30 | 12.64 | 0.182332E+10 | 2090.03 | 08-NOV-15:20 | 9.60 | 8.82 |
| December | 0.322153E+10 | 4050.88 | 29-DEC-15:02 | 10.60 | 8.76 | 0.158449E+10 | 1894.46 | 29-DEC-15:09 | 10.60 | 8.76 |
| Annual Sum or Average | 0.573841E+11 | 0.206579E+11 | ||||||||
| Minimum of Months | 0.315048E+10 | 4014.34 | 9.72 | 8.09 | 0.943706E+09 | 1099.97 | 9.60 | 8.09 | ||
| Maximum of Months | 0.756012E+10 | 8221.47 | 27.02 | 17.76 | 0.214294E+10 | 2090.03 | 28.67 | 18.27 |
Report: ZoneCoolingSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.558664E+09 | 2348.88 | 27-JAN-14:10 | 9.72 | 8.09 | 0.690204E+09 | 1088.78 | 27-JAN-14:20 | 9.43 | 7.91 |
| February | 0.118701E+10 | 3992.02 | 28-FEB-15:01 | 13.90 | 10.77 | 0.642052E+09 | 1250.18 | 28-FEB-15:50 | 13.90 | 10.63 |
| March | 0.293764E+10 | 4256.31 | 21-MAR-14:01 | 12.38 | 7.69 | 0.857789E+09 | 1341.04 | 17-MAR-14:00 | 12.38 | 7.69 |
| April | 0.363534E+10 | 9565.26 | 27-APR-14:50 | 27.02 | 17.21 | 0.845792E+09 | 1408.95 | 27-APR-13:50 | 27.02 | 17.21 |
| May | 0.671259E+10 | 12020.66 | 15-MAY-15:00 | 23.30 | 12.62 | 0.976630E+09 | 1410.88 | 15-MAY-14:20 | 23.30 | 12.62 |
| June | 0.805074E+10 | 15067.10 | 12-JUN-07:02 | 15.50 | 13.88 | 0.604236E+09 | 1445.04 | 12-JUN-07:10 | 15.50 | 13.88 |
| July | 0.585236E+10 | 12611.98 | 24-JUL-07:03 | 19.37 | 15.37 | 0.206576E+09 | 227.48 | 24-JUL-07:10 | 19.37 | 15.37 |
| August | 0.591332E+10 | 9741.21 | 14-AUG-15:40 | 27.33 | 17.15 | 0.236126E+09 | 222.89 | 14-AUG-07:10 | 27.33 | 17.15 |
| September | 0.537140E+10 | 9228.35 | 22-SEP-14:50 | 23.22 | 17.21 | 0.545591E+09 | 1408.95 | 22-SEP-08:00 | 23.22 | 17.21 |
| October | 0.348470E+10 | 7223.42 | 04-OCT-14:40 | 21.50 | 11.47 | 0.866868E+09 | 1408.93 | 03-OCT-14:20 | 21.50 | 11.47 |
| November | 0.199108E+10 | 4244.11 | 07-NOV-15:01 | 12.43 | 10.19 | 0.752158E+09 | 1330.32 | 08-NOV-15:09 | 9.50 | 8.82 |
| December | 0.684993E+09 | 2360.88 | 01-DEC-14:30 | 9.40 | 6.93 | 0.659962E+09 | 1095.87 | 01-DEC-14:39 | 9.40 | 6.93 |
| Annual Sum or Average | 0.463799E+11 | 0.788398E+10 | ||||||||
| Minimum of Months | 0.558664E+09 | 2348.88 | 9.40 | 6.93 | 0.206576E+09 | 222.89 | 9.40 | 6.93 | ||
| Maximum of Months | 0.805074E+10 | 15067.10 | 27.33 | 17.21 | 0.976630E+09 | 1445.04 | 27.33 | 17.21 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 23928395.97 | 1454.39 | 24-JAN-18:07 | 5.40 | 4.90 | 0.344182E+09 | 653.20 | 12-JAN-14:09 | 5.40 | 4.90 |
| February | 0.103453E+09 | 2360.31 | 27-FEB-15:02 | 19.90 | 12.22 | 0.331772E+09 | 786.28 | 27-FEB-15:09 | 19.90 | 12.22 |
| March | 0.295404E+09 | 1736.30 | 14-MAR-17:30 | 16.15 | 10.41 | 0.438036E+09 | 707.27 | 14-MAR-14:09 | 16.15 | 10.41 |
| April | 0.855474E+09 | 11097.17 | 27-APR-15:00 | 27.20 | 17.29 | 0.407383E+09 | 972.38 | 27-APR-14:00 | 27.20 | 17.29 |
| May | 0.168337E+10 | 6673.38 | 04-MAY-15:00 | 24.40 | 14.85 | 0.477199E+09 | 882.58 | 04-MAY-14:00 | 24.40 | 14.85 |
| June | 0.237001E+10 | 10335.19 | 28-JUN-15:00 | 26.10 | 15.54 | 0.305617E+09 | 882.53 | 09-JUN-13:09 | 26.10 | 15.54 |
| July | 0.248953E+10 | 12924.56 | 24-JUL-15:00 | 30.60 | 18.78 | 0.114093E+09 | 184.09 | 24-JUL-15:09 | 30.32 | 18.75 |
| August | 0.342338E+10 | 13124.24 | 29-AUG-15:00 | 30.90 | 19.65 | 0.134695E+09 | 187.02 | 29-AUG-15:09 | 31.00 | 19.61 |
| September | 0.198301E+10 | 9983.97 | 10-SEP-13:54 | 22.20 | 14.64 | 0.274507E+09 | 882.51 | 22-SEP-13:20 | 21.67 | 16.70 |
| October | 0.815238E+09 | 4566.93 | 04-OCT-14:00 | 21.10 | 11.41 | 0.433328E+09 | 882.51 | 04-OCT-13:20 | 21.10 | 11.41 |
| November | 0.132916E+09 | 2654.83 | 04-NOV-15:32 | 20.37 | 15.93 | 0.388229E+09 | 653.24 | 21-NOV-11:39 | 9.23 | 8.43 |
| December | 19993452.27 | 1505.33 | 05-DEC-18:07 | 5.00 | 3.89 | 0.336582E+09 | 653.19 | 12-DEC-14:00 | 8.30 | 5.43 |
| Annual Sum or Average | 0.141957E+11 | 0.398562E+10 | ||||||||
| Minimum of Months | 19993452.27 | 1454.39 | 5.00 | 3.89 | 0.114093E+09 | 184.09 | 5.40 | 4.90 | ||
| Maximum of Months | 0.342338E+10 | 13124.24 | 30.90 | 19.65 | 0.477199E+09 | 972.38 | 31.00 | 19.61 |
Report: ZoneCoolingSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.216265E+10 | 2299.31 | 27-JAN-14:10 | 9.72 | 8.09 | 0.106364E+09 | 187.51 | 27-JAN-14:20 | 9.43 | 7.91 |
| February | 0.214438E+10 | 3468.37 | 28-FEB-15:01 | 13.90 | 10.77 | 0.106132E+09 | 212.37 | 28-FEB-15:50 | 13.90 | 10.63 |
| March | 0.289542E+10 | 3652.03 | 17-MAR-14:01 | 12.30 | 8.34 | 0.147836E+09 | 224.97 | 17-MAR-14:00 | 12.80 | 8.60 |
| April | 0.298813E+10 | 12572.61 | 29-APR-14:58 | 22.20 | 15.23 | 0.143592E+09 | 247.13 | 27-APR-13:50 | 22.20 | 15.23 |
| May | 0.421201E+10 | 13304.28 | 14-MAY-18:11 | 21.47 | 11.73 | 0.168602E+09 | 247.13 | 05-MAY-11:30 | 21.47 | 11.73 |
| June | 0.494797E+10 | 12563.09 | 11-JUN-16:07 | 21.70 | 14.99 | 0.105003E+09 | 247.13 | 09-JUN-13:09 | 21.70 | 14.99 |
| July | 0.358513E+10 | 13453.01 | 15-JUL-17:21 | 23.05 | 17.76 | 33451402.86 | 39.02 | 24-JUL-12:20 | 26.83 | 17.94 |
| August | 0.373173E+10 | 13425.15 | 13-AUG-20:01 | 22.95 | 16.48 | 37987273.02 | 39.02 | 14-AUG-14:09 | 26.50 | 17.61 |
| September | 0.364112E+10 | 13326.90 | 09-SEP-18:12 | 18.67 | 13.70 | 92994542.01 | 247.12 | 29-SEP-14:00 | 20.00 | 14.18 |
| October | 0.296586E+10 | 4041.94 | 04-OCT-14:03 | 21.20 | 11.42 | 0.146918E+09 | 247.12 | 05-OCT-12:09 | 16.10 | 10.94 |
| November | 0.247874E+10 | 3623.76 | 07-NOV-15:01 | 12.43 | 10.19 | 0.127885E+09 | 223.03 | 08-NOV-15:09 | 9.50 | 8.82 |
| December | 0.207022E+10 | 2318.20 | 01-DEC-14:40 | 9.40 | 6.93 | 0.106959E+09 | 189.29 | 01-DEC-14:50 | 9.40 | 6.93 |
| Annual Sum or Average | 0.378234E+11 | 0.132373E+10 | ||||||||
| Minimum of Months | 0.207022E+10 | 2299.31 | 9.40 | 6.93 | 33451402.86 | 39.02 | 9.40 | 6.93 | ||
| Maximum of Months | 0.494797E+10 | 13453.01 | 23.05 | 17.76 | 0.168602E+09 | 247.13 | 26.83 | 17.94 |
Report: ZoneCoolingSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.731074E+09 | 1052.25 | 27-JAN-14:10 | 9.72 | 8.09 | 0.198195E+09 | 366.26 | 27-JAN-14:20 | 9.43 | 7.91 |
| February | 0.843589E+09 | 1904.77 | 28-FEB-15:01 | 13.90 | 10.77 | 0.201895E+09 | 438.49 | 28-FEB-15:50 | 13.90 | 10.63 |
| March | 0.138452E+10 | 2011.75 | 17-MAR-14:01 | 12.30 | 8.34 | 0.293467E+09 | 469.12 | 17-MAR-14:00 | 12.80 | 8.60 |
| April | 0.153471E+10 | 2534.90 | 27-APR-15:02 | 27.20 | 17.22 | 0.295962E+09 | 590.38 | 27-APR-14:09 | 27.20 | 17.22 |
| May | 0.219613E+10 | 2656.75 | 15-MAY-14:05 | 23.30 | 13.36 | 0.369684E+09 | 621.06 | 04-MAY-14:00 | 23.30 | 13.36 |
| June | 0.252097E+10 | 2884.59 | 28-JUN-15:10 | 26.10 | 15.67 | 0.235479E+09 | 616.14 | 09-JUN-14:00 | 26.10 | 15.67 |
| July | 0.213765E+10 | 8246.00 | 22-JUL-18:47 | 21.57 | 14.92 | 77704099.17 | 95.80 | 31-JUL-17:10 | 28.03 | 18.67 |
| August | 0.223561E+10 | 5829.99 | 12-AUG-16:35 | 24.77 | 16.62 | 88049841.02 | 96.47 | 10-AUG-17:40 | 24.77 | 16.62 |
| September | 0.193046E+10 | 2557.08 | 14-SEP-14:05 | 23.90 | 17.09 | 0.201682E+09 | 593.01 | 22-SEP-14:00 | 23.30 | 17.23 |
| October | 0.153193E+10 | 2419.93 | 04-OCT-14:03 | 21.20 | 11.42 | 0.303647E+09 | 559.26 | 04-OCT-14:00 | 21.70 | 11.49 |
| November | 0.115790E+10 | 2008.86 | 07-NOV-15:01 | 12.43 | 10.19 | 0.254812E+09 | 464.15 | 08-NOV-15:09 | 9.50 | 8.82 |
| December | 0.796700E+09 | 1090.63 | 01-DEC-14:40 | 9.40 | 6.93 | 0.201514E+09 | 375.52 | 01-DEC-14:50 | 9.40 | 6.93 |
| Annual Sum or Average | 0.190012E+11 | 0.272209E+10 | ||||||||
| Minimum of Months | 0.731074E+09 | 1052.25 | 9.40 | 6.93 | 77704099.17 | 95.80 | 9.40 | 6.93 | ||
| Maximum of Months | 0.252097E+10 | 8246.00 | 27.20 | 17.22 | 0.369684E+09 | 621.06 | 28.03 | 18.67 |
Report: ZoneCoolingSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.124510E+10 | 4527.76 | 20-JAN-15:01 | 6.93 | 4.80 | 0.492278E+09 | 1037.96 | 20-JAN-15:09 | 6.93 | 4.80 |
| February | 0.216345E+10 | 23201.94 | 03-FEB-15:01 | 9.82 | 6.92 | 0.474306E+09 | 1197.57 | 27-FEB-13:09 | 17.88 | 11.31 |
| March | 0.442865E+10 | 23515.81 | 17-MAR-14:01 | 12.30 | 8.34 | 0.637563E+09 | 1197.57 | 21-MAR-12:09 | 8.87 | 7.30 |
| April | 0.596939E+10 | 24042.94 | 28-APR-14:01 | 18.22 | 12.85 | 0.601259E+09 | 1197.63 | 27-APR-12:09 | 18.22 | 12.85 |
| May | 0.920820E+10 | 25309.43 | 14-MAY-14:59 | 23.30 | 12.44 | 0.683033E+09 | 1197.60 | 05-MAY-12:09 | 23.30 | 12.44 |
| June | 0.116072E+11 | 24060.80 | 01-JUN-14:01 | 17.88 | 10.64 | 0.688135E+09 | 1197.61 | 05-JUN-14:09 | 14.82 | 12.14 |
| July | 0.869710E+10 | 26358.58 | 08-JUL-13:19 | 21.87 | 16.02 | 0.349974E+09 | 630.33 | 06-JUL-11:09 | 21.87 | 16.02 |
| August | 0.962011E+10 | 27824.39 | 06-AUG-15:21 | 23.75 | 15.72 | 0.401873E+09 | 630.33 | 09-AUG-11:09 | 24.65 | 16.53 |
| September | 0.917555E+10 | 24115.15 | 20-SEP-14:01 | 17.88 | 13.25 | 0.609025E+09 | 1197.61 | 15-SEP-12:09 | 17.88 | 13.25 |
| October | 0.586537E+10 | 23901.90 | 03-OCT-14:01 | 18.40 | 10.43 | 0.626469E+09 | 1197.60 | 05-OCT-12:09 | 16.10 | 10.94 |
| November | 0.324188E+10 | 23429.88 | 07-NOV-15:01 | 12.43 | 10.19 | 0.552796E+09 | 1197.59 | 06-NOV-13:09 | 12.43 | 10.19 |
| December | 0.162460E+10 | 5081.99 | 05-DEC-15:01 | 9.35 | 6.62 | 0.477864E+09 | 1132.23 | 05-DEC-15:09 | 9.35 | 6.62 |
| Annual Sum or Average | 0.728466E+11 | 0.659457E+10 | ||||||||
| Minimum of Months | 0.124510E+10 | 4527.76 | 6.93 | 4.80 | 0.349974E+09 | 630.33 | 6.93 | 4.80 | ||
| Maximum of Months | 0.116072E+11 | 27824.39 | 23.75 | 16.02 | 0.688135E+09 | 1197.63 | 24.65 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.511118E+10 | 6981.20 | 11-JAN-17:00 | 12.20 | 9.27 | 0.262891E+10 | 4922.19 | 11-JAN-17:10 | 12.30 | 9.33 |
| February | 0.552478E+10 | 9672.73 | 28-FEB-15:01 | 13.90 | 10.77 | 0.251749E+10 | 5482.47 | 27-FEB-16:49 | 13.90 | 10.77 |
| March | 0.806218E+10 | 11422.99 | 14-MAR-15:20 | 16.47 | 10.52 | 0.337207E+10 | 5528.19 | 15-MAR-15:20 | 11.10 | 7.47 |
| April | 0.926310E+10 | 25221.61 | 28-APR-05:01 | 11.10 | 9.92 | 0.310971E+10 | 5528.18 | 18-APR-15:20 | 11.10 | 9.92 |
| May | 0.132454E+11 | 26013.06 | 16-MAY-05:01 | 11.70 | 10.43 | 0.346163E+10 | 5528.18 | 10-MAY-15:20 | 11.70 | 10.43 |
| June | 0.155794E+11 | 27040.94 | 12-JUN-05:01 | 14.40 | 13.42 | 0.347318E+10 | 5528.17 | 05-JUN-15:20 | 14.40 | 13.42 |
| July | 0.115749E+11 | 28280.55 | 24-JUL-05:01 | 15.87 | 13.15 | 0.188124E+10 | 2036.78 | 31-JUL-15:39 | 28.70 | 19.09 |
| August | 0.119055E+11 | 27321.04 | 14-AUG-05:01 | 15.37 | 13.48 | 0.214349E+10 | 2036.90 | 09-AUG-10:09 | 15.37 | 13.48 |
| September | 0.112280E+11 | 25627.04 | 11-SEP-05:01 | 12.12 | 10.60 | 0.306904E+10 | 5528.16 | 26-SEP-15:20 | 12.23 | 11.32 |
| October | 0.841980E+10 | 22070.03 | 10-OCT-06:01 | 12.12 | 10.88 | 0.318822E+10 | 5528.17 | 25-OCT-15:20 | 14.27 | 10.87 |
| November | 0.662152E+10 | 9914.38 | 02-NOV-14:01 | 14.22 | 11.35 | 0.289071E+10 | 5526.54 | 02-NOV-16:10 | 13.12 | 10.80 |
| December | 0.514943E+10 | 7020.13 | 29-DEC-17:00 | 9.40 | 7.98 | 0.254491E+10 | 4938.86 | 29-DEC-17:10 | 9.40 | 7.98 |
| Annual Sum or Average | 0.111685E+12 | 0.342806E+11 | ||||||||
| Minimum of Months | 0.511118E+10 | 6981.20 | 9.40 | 7.98 | 0.188124E+10 | 2036.78 | 9.40 | 7.47 | ||
| Maximum of Months | 0.155794E+11 | 28280.55 | 16.47 | 13.48 | 0.347318E+10 | 5528.19 | 28.70 | 19.09 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.929061E+10 | 67592.71 | 06-JAN-06:11 | -1.9 | -1.9 | 0.642765E+10 | 8101.54 | 02-JAN-12:20 | -1.9 | -1.9 |
| February | 0.958680E+10 | 68579.49 | 08-FEB-06:01 | -0.6 | -2.0 | 0.581022E+10 | 8102.40 | 27-FEB-12:09 | 16.88 | 10.88 |
| March | 0.134557E+11 | 65942.39 | 01-MAR-06:01 | -0.1 | -1.5 | 0.671307E+10 | 8102.47 | 10-MAR-12:00 | 16.70 | 12.26 |
| April | 0.143571E+11 | 60749.64 | 19-APR-05:01 | 1.78 | 1.27 | 0.617431E+10 | 8102.44 | 27-APR-09:09 | 17.98 | 12.34 |
| May | 0.172651E+11 | 54014.38 | 11-MAY-05:11 | 5.20 | 4.42 | 0.657062E+10 | 8102.51 | 05-MAY-09:50 | 5.20 | 4.42 |
| June | 0.174092E+11 | 46256.52 | 15-JUN-05:01 | 8.98 | 8.04 | 0.611493E+10 | 8102.52 | 12-JUN-09:20 | 8.98 | 8.04 |
| July | 0.152225E+11 | 43851.40 | 03-JUL-05:01 | 11.70 | 8.33 | 0.565775E+10 | 7012.59 | 11-JUL-10:39 | 19.07 | 16.35 |
| August | 0.159823E+11 | 40338.21 | 18-AUG-05:01 | 11.50 | 11.07 | 0.599186E+10 | 7012.59 | 30-AUG-09:20 | 19.47 | 17.21 |
| September | 0.153201E+11 | 48512.31 | 27-SEP-05:01 | 7.38 | 6.94 | 0.586080E+10 | 8102.53 | 22-SEP-10:20 | 7.38 | 6.94 |
| October | 0.143224E+11 | 53931.89 | 13-OCT-05:01 | 5.78 | 4.69 | 0.642769E+10 | 8102.46 | 06-OCT-11:00 | 5.78 | 4.69 |
| November | 0.117034E+11 | 61516.54 | 13-NOV-06:01 | 1.70 | 1.50 | 0.631696E+10 | 8102.26 | 06-NOV-11:00 | 1.70 | 1.50 |
| December | 0.951759E+10 | 66194.44 | 26-DEC-06:01 | -0.8 | -0.8 | 0.628490E+10 | 8101.71 | 26-DEC-12:30 | 0.40 | 0.34 |
| Annual Sum or Average | 0.163433E+12 | 0.743508E+11 | ||||||||
| Minimum of Months | 0.929061E+10 | 40338.21 | -1.9 | -2.0 | 0.565775E+10 | 7012.59 | -1.9 | -1.9 | ||
| Maximum of Months | 0.174092E+11 | 68579.49 | 11.70 | 11.07 | 0.671307E+10 | 8102.53 | 19.47 | 17.21 |
Report: ZoneCoolingSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.124021E+11 | 30857.60 | 05-JAN-08:61 | 0.40 | 0.40 | 0.733579E+10 | 16247.45 | 11-JAN-14:30 | 14.40 | 10.49 |
| February | 0.116421E+11 | 33681.46 | 09-FEB-08:61 | -0.6 | -1.1 | 0.704873E+10 | 16256.62 | 27-FEB-14:39 | 19.43 | 11.93 |
| March | 0.155423E+11 | 31225.46 | 02-MAR-08:61 | 2.15 | 1.10 | 0.905988E+10 | 16256.52 | 10-MAR-13:00 | 16.70 | 12.02 |
| April | 0.143470E+11 | 28515.60 | 19-APR-07:01 | 4.18 | 3.15 | 0.851183E+10 | 16258.22 | 28-APR-13:39 | 17.77 | 13.44 |
| May | 0.170720E+11 | 52398.94 | 14-MAY-14:43 | 23.22 | 12.41 | 0.984592E+10 | 16258.55 | 05-MAY-10:39 | 23.22 | 12.41 |
| June | 0.184251E+11 | 63293.05 | 26-JUN-05:01 | 12.80 | 10.67 | 0.100124E+11 | 16258.76 | 12-JUN-12:50 | 12.80 | 10.67 |
| July | 0.828941E+10 | 58654.17 | 10-JUL-05:01 | 13.22 | 11.65 | 0.229425E+10 | 5989.94 | 26-JUL-16:49 | 23.22 | 17.09 |
| August | 0.923947E+10 | 59053.81 | 15-AUG-05:01 | 13.05 | 11.44 | 0.263892E+10 | 5989.91 | 11-AUG-17:10 | 13.05 | 11.44 |
| September | 0.149761E+11 | 62698.60 | 11-SEP-05:01 | 12.12 | 10.60 | 0.872794E+10 | 16258.94 | 22-SEP-10:00 | 18.30 | 15.61 |
| October | 0.144169E+11 | 25650.44 | 13-OCT-07:01 | 6.28 | 4.94 | 0.907838E+10 | 16257.22 | 06-OCT-13:00 | 6.28 | 4.94 |
| November | 0.138963E+11 | 29412.25 | 22-NOV-08:61 | 2.88 | 2.41 | 0.803515E+10 | 16247.18 | 06-NOV-13:20 | 2.88 | 2.41 |
| December | 0.121778E+11 | 32510.92 | 22-DEC-08:61 | 0.10 | -1.2 | 0.711242E+10 | 16247.58 | 14-DEC-12:20 | 0.10 | -1.2 |
| Annual Sum or Average | 0.162426E+12 | 0.897016E+11 | ||||||||
| Minimum of Months | 0.828941E+10 | 25650.44 | -0.6 | -1.2 | 0.229425E+10 | 5989.91 | 0.10 | -1.2 | ||
| Maximum of Months | 0.184251E+11 | 63293.05 | 23.22 | 12.41 | 0.100124E+11 | 16258.94 | 23.22 | 17.09 |
Report: ZoneCoolingSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.282263E+10 | 4716.99 | 27-JAN-14:10 | 9.72 | 8.09 | 0.108021E+10 | 1904.45 | 27-JAN-14:09 | 9.72 | 8.09 |
| February | 0.340567E+10 | 6952.00 | 28-FEB-15:04 | 13.90 | 10.77 | 0.104585E+10 | 2059.30 | 28-FEB-15:20 | 13.90 | 10.74 |
| March | 0.583658E+10 | 8507.86 | 10-MAR-14:20 | 16.50 | 11.85 | 0.142313E+10 | 2059.31 | 31-MAR-14:20 | 9.23 | 7.64 |
| April | 0.740468E+10 | 15253.13 | 27-APR-14:30 | 26.65 | 17.06 | 0.128761E+10 | 2060.89 | 19-APR-11:50 | 26.65 | 17.06 |
| May | 0.113492E+11 | 23083.61 | 15-MAY-07:01 | 13.58 | 10.19 | 0.143123E+10 | 2107.57 | 15-MAY-07:10 | 13.58 | 10.19 |
| June | 0.133217E+11 | 23473.62 | 12-JUN-07:02 | 15.50 | 13.88 | 0.883915E+09 | 2179.31 | 12-JUN-07:10 | 15.50 | 13.88 |
| July | 0.848972E+10 | 17135.08 | 24-JUL-07:03 | 19.37 | 15.37 | 0.301821E+09 | 336.91 | 24-JUL-07:10 | 19.37 | 15.37 |
| August | 0.905401E+10 | 12098.69 | 14-AUG-13:30 | 26.05 | 17.52 | 0.346080E+09 | 325.20 | 09-AUG-10:09 | 26.05 | 17.52 |
| September | 0.978993E+10 | 16593.79 | 14-SEP-07:01 | 14.18 | 13.39 | 0.802132E+09 | 2059.33 | 25-SEP-07:40 | 13.70 | 13.70 |
| October | 0.715907E+10 | 12715.60 | 04-OCT-14:07 | 21.20 | 11.42 | 0.134976E+10 | 2059.35 | 12-OCT-08:20 | 8.17 | 7.43 |
| November | 0.497798E+10 | 8137.40 | 02-NOV-14:03 | 14.22 | 11.35 | 0.125113E+10 | 2059.32 | 06-NOV-15:20 | 11.10 | 10.31 |
| December | 0.321924E+10 | 4753.15 | 29-DEC-15:02 | 10.60 | 8.76 | 0.105795E+10 | 1919.68 | 01-DEC-14:39 | 10.60 | 8.76 |
| Annual Sum or Average | 0.868304E+11 | 0.122608E+11 | ||||||||
| Minimum of Months | 0.282263E+10 | 4716.99 | 9.72 | 8.09 | 0.301821E+09 | 325.20 | 8.17 | 7.43 | ||
| Maximum of Months | 0.133217E+11 | 23473.62 | 26.65 | 17.52 | 0.143123E+10 | 2179.31 | 26.65 | 17.52 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.451523E+09 | 6874.29 | 02-JAN-07:11 | 6.30 |
| February | 0.216335E+09 | 7035.94 | 21-FEB-07:01 | 1.60 |
| March | 45260644.31 | 6167.32 | 06-MAR-07:11 | 6.70 |
| April | 14277555.31 | 5743.63 | 18-APR-06:11 | 3.50 |
| May | 3170669.56 | 5072.99 | 18-MAY-07:01 | 6.10 |
| June | 449042.74 | 2549.47 | 14-JUN-07:01 | 10.68 |
| July | 3269447.40 | 5034.98 | 13-JUL-07:01 | 14.08 |
| August | 2628754.55 | 5105.75 | 18-AUG-07:01 | 12.45 |
| September | 781310.23 | 4965.41 | 28-SEP-07:01 | 9.08 |
| October | 5740464.43 | 5096.14 | 16-OCT-07:01 | 6.38 |
| November | 50670915.28 | 6236.28 | 24-NOV-06:42 | 1.28 |
| December | 0.236753E+09 | 6790.00 | 18-DEC-07:11 | 2.80 |
| Annual Sum or Average | 0.103086E+10 | |||
| Minimum of Months | 449042.74 | 2549.47 | 1.28 | |
| Maximum of Months | 0.451523E+09 | 7035.94 | 14.08 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.696517E+09 | 24239.00 | 02-JAN-07:11 | 6.30 |
| February | 0.231008E+09 | 24555.61 | 21-FEB-07:01 | 1.60 |
| March | 45122381.53 | 19243.02 | 06-MAR-07:11 | 6.70 |
| April | 15895968.24 | 17063.47 | 18-APR-07:01 | 3.98 |
| May | 1207741.35 | 16094.26 | 18-MAY-07:01 | 6.10 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 8981589.62 | 16598.03 | 13-JUL-07:01 | 14.08 |
| August | 9702901.25 | 17034.88 | 18-AUG-07:01 | 12.45 |
| September | 560852.37 | 7478.03 | 01-SEP-07:01 | 15.18 |
| October | 8706106.77 | 16956.50 | 23-OCT-07:01 | 9.50 |
| November | 70437015.27 | 20243.27 | 24-NOV-07:01 | 1.20 |
| December | 0.328738E+09 | 22857.33 | 26-DEC-06:11 | -1.0 |
| Annual Sum or Average | 0.141688E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.696517E+09 | 24555.61 | 15.18 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.108319E+10 | 5861.30 | 02-JAN-07:11 | 6.30 |
| February | 0.432427E+09 | 5868.83 | 21-FEB-07:01 | 1.60 |
| March | 36289086.47 | 4756.80 | 06-MAR-07:11 | 6.70 |
| April | 3086087.26 | 4391.08 | 18-APR-07:01 | 3.98 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 1643308.71 | 4360.05 | 30-OCT-07:01 | 7.20 |
| November | 0.101108E+09 | 4969.27 | 27-NOV-07:11 | 11.70 |
| December | 0.544447E+09 | 5510.38 | 26-DEC-06:22 | -1.1 |
| Annual Sum or Average | 0.220220E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.1 | |
| Maximum of Months | 0.108319E+10 | 5868.83 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.639792E+09 | 6326.38 | 02-JAN-07:11 | 6.30 |
| February | 0.376321E+09 | 6508.12 | 21-FEB-07:01 | 1.60 |
| March | 80177087.82 | 5853.75 | 06-MAR-07:11 | 6.70 |
| April | 23477044.81 | 5453.44 | 19-APR-06:11 | 2.77 |
| May | 4250876.52 | 4811.58 | 18-MAY-07:01 | 6.10 |
| June | 1068316.17 | 4506.97 | 06-JUN-07:01 | 11.78 |
| July | 4987459.92 | 4819.42 | 14-JUL-07:01 | 14.50 |
| August | 4682749.75 | 4843.09 | 18-AUG-07:01 | 12.45 |
| September | 2399726.84 | 4799.04 | 28-SEP-07:01 | 9.08 |
| October | 11995704.38 | 5337.20 | 30-OCT-06:12 | 7.20 |
| November | 77124159.54 | 6067.02 | 13-NOV-06:52 | 1.70 |
| December | 0.321169E+09 | 6257.04 | 18-DEC-07:11 | 2.80 |
| Annual Sum or Average | 0.154744E+10 | |||
| Minimum of Months | 1068316.17 | 4506.97 | 1.60 | |
| Maximum of Months | 0.639792E+09 | 6508.12 | 14.50 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.953276E+09 | 23280.66 | 02-JAN-07:11 | 6.30 |
| February | 0.499250E+09 | 23957.62 | 21-FEB-07:01 | 1.60 |
| March | 85830690.62 | 19334.87 | 06-MAR-07:11 | 6.70 |
| April | 26130820.83 | 16656.33 | 18-APR-07:01 | 3.98 |
| May | 2449101.89 | 15859.45 | 18-MAY-07:01 | 6.10 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 21068055.77 | 16597.90 | 14-JUL-07:01 | 14.50 |
| August | 20524791.68 | 16680.90 | 03-AUG-07:01 | 11.92 |
| September | 1537743.26 | 16205.99 | 01-SEP-07:01 | 15.18 |
| October | 17548202.57 | 16646.10 | 30-OCT-07:01 | 7.20 |
| November | 0.108399E+09 | 20058.72 | 13-NOV-07:01 | 1.52 |
| December | 0.424895E+09 | 22051.75 | 26-DEC-06:11 | -1.0 |
| Annual Sum or Average | 0.216091E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.953276E+09 | 23957.62 | 15.18 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.464256E+09 | 6830.68 | 02-JAN-07:11 | 6.30 |
| February | 0.218317E+09 | 6992.96 | 21-FEB-07:01 | 1.60 |
| March | 45602042.41 | 6129.47 | 06-MAR-07:11 | 6.70 |
| April | 14594733.24 | 5713.69 | 18-APR-06:11 | 3.50 |
| May | 3411782.90 | 5039.90 | 18-MAY-07:01 | 6.10 |
| June | 583421.30 | 3092.86 | 14-JUN-07:01 | 10.68 |
| July | 3560500.55 | 5024.39 | 13-JUL-07:01 | 14.08 |
| August | 2678327.38 | 5073.60 | 18-AUG-07:01 | 12.45 |
| September | 815836.56 | 4941.38 | 28-SEP-07:01 | 9.08 |
| October | 5800376.10 | 5063.59 | 30-OCT-07:01 | 7.20 |
| November | 51830960.81 | 6189.46 | 24-NOV-06:42 | 1.28 |
| December | 0.244576E+09 | 6744.22 | 18-DEC-07:11 | 2.80 |
| Annual Sum or Average | 0.105603E+10 | |||
| Minimum of Months | 583421.30 | 3092.86 | 1.28 | |
| Maximum of Months | 0.464256E+09 | 6992.96 | 14.08 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.689338E+09 | 23898.15 | 02-JAN-07:11 | 6.30 |
| February | 0.225691E+09 | 24220.69 | 21-FEB-07:01 | 1.60 |
| March | 43888113.95 | 18917.57 | 06-MAR-07:11 | 6.70 |
| April | 15510694.29 | 16801.81 | 18-APR-07:01 | 3.98 |
| May | 958362.47 | 15344.17 | 18-MAY-07:01 | 6.10 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 9630743.93 | 16390.67 | 13-JUL-07:01 | 14.08 |
| August | 9688887.65 | 16759.89 | 18-AUG-07:01 | 12.45 |
| September | 654150.15 | 8722.00 | 01-SEP-07:01 | 15.18 |
| October | 8161982.36 | 16698.25 | 23-OCT-07:01 | 9.50 |
| November | 68958946.32 | 19947.12 | 24-NOV-07:01 | 1.20 |
| December | 0.324829E+09 | 22540.23 | 26-DEC-06:11 | -1.0 |
| Annual Sum or Average | 0.139731E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.689338E+09 | 24220.69 | 15.18 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.110254E+10 | 5844.75 | 02-JAN-07:11 | 6.30 |
| February | 0.433756E+09 | 5852.99 | 21-FEB-07:01 | 1.60 |
| March | 36114664.13 | 4741.67 | 06-MAR-07:11 | 6.70 |
| April | 3087295.46 | 4377.31 | 18-APR-07:01 | 3.98 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 1615575.81 | 4361.07 | 30-OCT-07:01 | 7.20 |
| November | 0.102552E+09 | 4950.22 | 27-NOV-07:11 | 11.70 |
| December | 0.570429E+09 | 5496.46 | 26-DEC-06:22 | -1.1 |
| Annual Sum or Average | 0.225010E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.1 | |
| Maximum of Months | 0.110254E+10 | 5852.99 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.642656E+09 | 6329.46 | 02-JAN-07:11 | 6.30 |
| February | 0.376781E+09 | 6511.30 | 21-FEB-07:01 | 1.60 |
| March | 80290406.84 | 5856.76 | 06-MAR-07:11 | 6.70 |
| April | 23474953.52 | 5455.29 | 19-APR-06:11 | 2.77 |
| May | 4251104.73 | 4814.26 | 18-MAY-07:01 | 6.10 |
| June | 1067431.65 | 4509.60 | 06-JUN-07:01 | 11.78 |
| July | 5003623.03 | 4821.92 | 14-JUL-07:01 | 14.50 |
| August | 4715861.72 | 4845.15 | 18-AUG-07:01 | 12.45 |
| September | 2427030.01 | 4801.96 | 28-SEP-07:01 | 9.08 |
| October | 12028439.02 | 5342.51 | 30-OCT-06:12 | 7.20 |
| November | 77414857.91 | 6073.04 | 13-NOV-06:52 | 1.70 |
| December | 0.324445E+09 | 6260.39 | 18-DEC-07:11 | 2.80 |
| Annual Sum or Average | 0.155456E+10 | |||
| Minimum of Months | 1067431.65 | 4509.60 | 1.60 | |
| Maximum of Months | 0.642656E+09 | 6511.30 | 14.50 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.959534E+09 | 23275.04 | 02-JAN-07:11 | 6.30 |
| February | 0.499823E+09 | 23952.00 | 21-FEB-07:01 | 1.60 |
| March | 85873443.62 | 19333.68 | 06-MAR-07:11 | 6.70 |
| April | 26139071.92 | 16658.80 | 18-APR-07:01 | 3.98 |
| May | 2382553.69 | 15855.89 | 18-MAY-07:01 | 6.10 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 21051507.98 | 16601.39 | 14-JUL-07:01 | 14.50 |
| August | 20530716.30 | 16680.29 | 03-AUG-07:01 | 11.92 |
| September | 1519979.75 | 16213.39 | 01-SEP-07:01 | 15.18 |
| October | 17598842.91 | 16648.84 | 30-OCT-07:01 | 7.20 |
| November | 0.108667E+09 | 20055.76 | 13-NOV-07:01 | 1.52 |
| December | 0.429176E+09 | 22047.45 | 26-DEC-06:11 | -1.0 |
| Annual Sum or Average | 0.217230E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.959534E+09 | 23952.00 | 15.18 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.453761E+09 | 6835.48 | 02-JAN-07:11 | 6.30 |
| February | 0.214893E+09 | 6997.34 | 21-FEB-07:01 | 1.60 |
| March | 43558768.83 | 6113.51 | 06-MAR-07:11 | 6.70 |
| April | 13689478.71 | 5694.49 | 18-APR-06:11 | 3.50 |
| May | 3157564.01 | 5042.97 | 18-MAY-07:01 | 6.10 |
| June | 450460.50 | 2575.94 | 14-JUN-07:01 | 10.68 |
| July | 3242782.84 | 5005.17 | 13-JUL-07:01 | 14.08 |
| August | 2617381.54 | 5076.26 | 18-AUG-07:01 | 12.45 |
| September | 750000.22 | 4928.21 | 28-SEP-07:01 | 9.08 |
| October | 5318536.99 | 5064.68 | 30-OCT-07:01 | 7.20 |
| November | 49493480.92 | 6076.79 | 27-NOV-07:11 | 11.70 |
| December | 0.238061E+09 | 6741.65 | 18-DEC-07:11 | 2.80 |
| Annual Sum or Average | 0.102899E+10 | |||
| Minimum of Months | 450460.50 | 2575.94 | 1.60 | |
| Maximum of Months | 0.453761E+09 | 6997.34 | 14.08 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.677864E+09 | 23988.44 | 02-JAN-07:11 | 6.30 |
| February | 0.222187E+09 | 24322.07 | 21-FEB-07:01 | 1.60 |
| March | 40505226.87 | 18895.58 | 06-MAR-07:11 | 6.70 |
| April | 15167485.03 | 16858.55 | 18-APR-07:01 | 3.98 |
| May | 766021.41 | 12767.02 | 18-MAY-07:01 | 6.10 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 8489721.95 | 16344.55 | 13-JUL-07:01 | 14.08 |
| August | 9103295.04 | 16738.51 | 18-AUG-07:01 | 12.45 |
| September | 388424.78 | 5179.00 | 01-SEP-07:01 | 15.18 |
| October | 6911495.72 | 16723.95 | 23-OCT-07:01 | 9.50 |
| November | 63859206.23 | 20002.24 | 24-NOV-07:01 | 1.20 |
| December | 0.314794E+09 | 22613.97 | 26-DEC-06:11 | -1.0 |
| Annual Sum or Average | 0.136004E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.677864E+09 | 24322.07 | 15.18 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.104260E+10 | 5875.22 | 02-JAN-07:11 | 6.30 |
| February | 0.399714E+09 | 5881.21 | 21-FEB-07:01 | 1.60 |
| March | 26061216.13 | 4717.92 | 06-MAR-07:11 | 6.70 |
| April | 1938226.74 | 4342.25 | 18-APR-07:01 | 3.98 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 1267886.31 | 4317.71 | 30-OCT-07:01 | 7.20 |
| November | 78665030.09 | 4932.43 | 27-NOV-07:11 | 11.70 |
| December | 0.513645E+09 | 5515.25 | 26-DEC-06:22 | -1.1 |
| Annual Sum or Average | 0.206389E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.1 | |
| Maximum of Months | 0.104260E+10 | 5881.21 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.642764E+09 | 6365.39 | 02-JAN-07:11 | 6.30 |
| February | 0.373295E+09 | 6547.55 | 21-FEB-07:01 | 1.60 |
| March | 76732795.83 | 5874.04 | 06-MAR-07:11 | 6.70 |
| April | 21231176.93 | 5459.16 | 19-APR-06:11 | 2.77 |
| May | 3955066.20 | 4839.17 | 18-MAY-07:01 | 6.10 |
| June | 677864.86 | 3470.07 | 06-JUN-07:01 | 11.78 |
| July | 4340070.14 | 4845.57 | 14-JUL-07:01 | 14.50 |
| August | 4227421.53 | 4870.71 | 18-AUG-07:01 | 12.45 |
| September | 1941372.83 | 4826.03 | 28-SEP-07:01 | 9.08 |
| October | 11468827.50 | 5347.41 | 30-OCT-06:12 | 7.20 |
| November | 75060703.12 | 6090.12 | 13-NOV-06:52 | 1.70 |
| December | 0.323318E+09 | 6294.47 | 18-DEC-07:11 | 2.80 |
| Annual Sum or Average | 0.153901E+10 | |||
| Minimum of Months | 677864.86 | 3470.07 | 1.60 | |
| Maximum of Months | 0.642764E+09 | 6547.55 | 14.50 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.664779E+09 | 15596.58 | 02-JAN-07:11 | 6.30 |
| February | 0.343749E+09 | 16046.86 | 21-FEB-07:01 | 1.60 |
| March | 55559161.66 | 12974.22 | 06-MAR-07:11 | 6.70 |
| April | 15992878.84 | 11207.89 | 18-APR-07:01 | 3.98 |
| May | 994075.41 | 10634.24 | 18-MAY-07:01 | 6.10 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 10879323.77 | 11068.11 | 14-JUL-07:01 | 14.50 |
| August | 11231988.44 | 11220.16 | 18-AUG-07:01 | 12.45 |
| September | 908009.26 | 10823.58 | 01-SEP-07:01 | 15.18 |
| October | 11003446.92 | 11203.34 | 30-OCT-07:01 | 7.20 |
| November | 71971152.90 | 13456.75 | 13-NOV-07:01 | 1.52 |
| December | 0.295499E+09 | 14774.89 | 26-DEC-06:11 | -1.0 |
| Annual Sum or Average | 0.148257E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.664779E+09 | 16046.86 | 15.18 |
Report: ZoneHeatingSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.194697E+09 | 7673.07 | 02-JAN-07:11 | 6.30 |
| February | 88457202.33 | 7887.42 | 21-FEB-07:01 | 1.60 |
| March | 12250729.98 | 6017.07 | 06-MAR-07:11 | 6.70 |
| April | 2822505.45 | 5415.09 | 18-APR-07:01 | 3.98 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.43 |
| August | 838592.88 | 5127.62 | 03-AUG-07:01 | 11.92 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 1850262.58 | 5430.95 | 30-OCT-07:01 | 7.20 |
| November | 17200457.07 | 6533.53 | 13-NOV-07:01 | 1.52 |
| December | 87519746.99 | 7197.26 | 26-DEC-06:11 | -1.0 |
| Annual Sum or Average | 0.405637E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.194697E+09 | 7887.42 | 16.38 |
Report: ZoneHeatingSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.267215E+10 | 12935.23 | 02-JAN-07:11 | 6.30 |
| February | 0.894763E+09 | 12639.30 | 21-FEB-07:01 | 1.60 |
| March | 26214751.89 | 9941.84 | 02-MAR-08:61 | 2.15 |
| April | 0.00 | 0.00 | 01-APR-00:05 | 7.93 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 574365.92 | 9572.77 | 30-OCT-07:01 | 7.20 |
| November | 0.184180E+09 | 10758.06 | 27-NOV-07:11 | 11.70 |
| December | 0.131857E+10 | 11941.29 | 26-DEC-06:22 | -1.1 |
| Annual Sum or Average | 0.509645E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.1 | |
| Maximum of Months | 0.267215E+10 | 12935.23 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.667876E+10 | 13138.37 | 06-JAN-07:10 | -2.3 |
| February | 0.486533E+10 | 12478.72 | 09-FEB-07:10 | -0.7 |
| March | 0.424221E+10 | 12173.36 | 01-MAR-07:10 | -0.1 |
| April | 0.240893E+10 | 11410.78 | 19-APR-06:10 | 2.48 |
| May | 0.153736E+10 | 10305.13 | 18-MAY-06:10 | 5.68 |
| June | 0.920915E+09 | 9046.34 | 15-JUN-06:10 | 9.60 |
| July | 0.566274E+09 | 7839.57 | 06-JUL-06:50 | 12.80 |
| August | 0.603486E+09 | 8504.10 | 03-AUG-06:06 | 11.82 |
| September | 0.934058E+09 | 9462.16 | 28-SEP-06:10 | 8.40 |
| October | 0.223837E+10 | 10182.99 | 24-OCT-06:10 | 6.28 |
| November | 0.462650E+10 | 12067.75 | 24-NOV-07:10 | 1.20 |
| December | 0.595314E+10 | 12744.22 | 26-DEC-08:00 | -1.1 |
| Annual Sum or Average | 0.355753E+11 | |||
| Minimum of Months | 0.566274E+09 | 7839.57 | -2.3 | |
| Maximum of Months | 0.667876E+10 | 13138.37 | 12.80 |
Report: ZoneHeatingSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 5.92 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
| April | 0.00 | 0.00 | 01-APR-00:05 | 7.93 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 4.40 | |
| Maximum of Months | 0.00 | 0.00 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 66051185.10 | 4013.35 | 02-JAN-07:01 | 6.20 |
| February | 5987253.94 | 1661.16 | 21-FEB-07:01 | 1.60 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 5.92 |
| April | 0.00 | 0.00 | 01-APR-00:05 | 7.93 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 0.00 | 0.00 | 01-NOV-00:05 | 9.22 |
| December | 250666.91 | 320.58 | 26-DEC-06:53 | -1.7 |
| Annual Sum or Average | 72289105.96 | |||
| Minimum of Months | 0.00 | 0.00 | -1.7 | |
| Maximum of Months | 66051185.10 | 4013.35 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.146122E+10 | 18213.30 | 02-JAN-07:11 | 6.30 |
| February | 0.454965E+09 | 18433.52 | 21-FEB-07:01 | 1.60 |
| March | 29634853.03 | 14415.98 | 06-MAR-07:11 | 6.70 |
| April | 1216098.37 | 13432.45 | 18-APR-07:01 | 3.98 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 886989.13 | 10370.65 | 30-OCT-07:01 | 7.20 |
| November | 74263525.85 | 15501.28 | 24-NOV-07:01 | 1.20 |
| December | 0.671867E+09 | 17065.92 | 26-DEC-06:11 | -1.0 |
| Annual Sum or Average | 0.269405E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.146122E+10 | 18433.52 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.539451E+09 | 15213.45 | 02-JAN-06:01 | 6.10 |
| February | 0.198769E+09 | 14398.67 | 21-FEB-06:01 | 1.70 |
| March | 749726.85 | 10256.00 | 06-MAR-07:01 | 6.70 |
| April | 0.00 | 0.00 | 01-APR-00:05 | 7.93 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 39381495.00 | 11090.04 | 28-NOV-06:50 | 3.98 |
| December | 0.273475E+09 | 13143.99 | 26-DEC-06:11 | -1.0 |
| Annual Sum or Average | 0.105183E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.539451E+09 | 15213.45 | 17.17 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 390037.15 | 3034.95 | 25-JAN-07:02 | 4.90 |
| February | 1042904.07 | 3311.77 | 24-FEB-07:02 | 13.90 |
| March | 1307377.29 | 3361.60 | 07-MAR-07:02 | 7.12 |
| April | 316477.04 | 3216.67 | 20-APR-06:02 | 4.18 |
| May | 551289.16 | 1586.45 | 30-MAY-06:01 | 10.68 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 193812.70 | 1650.68 | 12-JUL-06:01 | 12.80 |
| August | 98065.92 | 1634.43 | 23-AUG-06:01 | 14.68 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 1768948.77 | 3422.76 | 31-OCT-06:02 | 10.18 |
| November | 1639405.95 | 3423.48 | 21-NOV-07:02 | 11.10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.40 |
| Annual Sum or Average | 7308318.06 | |||
| Minimum of Months | 0.00 | 0.00 | 4.18 | |
| Maximum of Months | 1768948.77 | 3423.48 | 16.38 |
Report: ZoneHeatingSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.982976E+09 | 64558.90 | 02-JAN-06:01 | 6.10 |
| February | 0.629788E+09 | 61291.96 | 22-FEB-06:01 | 7.62 |
| March | 0.380876E+09 | 59677.30 | 06-MAR-06:01 | 6.70 |
| April | 0.203159E+09 | 23081.53 | 19-APR-05:07 | 1.78 |
| May | 50803597.46 | 5335.32 | 18-MAY-07:05 | 6.10 |
| June | 5915568.32 | 4625.91 | 23-JUN-06:02 | 13.40 |
| July | 5222231.40 | 4735.58 | 20-JUL-06:02 | 14.45 |
| August | 16719251.79 | 4735.68 | 11-AUG-06:02 | 13.93 |
| September | 18925834.48 | 4610.85 | 14-SEP-06:02 | 12.07 |
| October | 0.178720E+09 | 12198.38 | 30-OCT-05:56 | 7.20 |
| November | 0.373019E+09 | 57074.10 | 14-NOV-06:01 | 5.60 |
| December | 0.673954E+09 | 62919.85 | 28-DEC-06:01 | 9.40 |
| Annual Sum or Average | 0.352008E+10 | |||
| Minimum of Months | 5222231.40 | 4610.85 | 1.78 | |
| Maximum of Months | 0.982976E+09 | 64558.90 | 14.45 |
Report: ZoneHeatingSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.699566E+09 | 16847.23 | 02-JAN-07:11 | 6.30 |
| February | 0.254511E+09 | 17312.12 | 21-FEB-07:01 | 1.60 |
| March | 10034876.25 | 12945.09 | 06-MAR-07:11 | 6.70 |
| April | 0.00 | 0.00 | 01-APR-00:05 | 7.93 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.38 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 12.83 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 15.43 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 17.17 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 16.38 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.35 |
| November | 30538853.79 | 14274.53 | 13-NOV-07:01 | 1.52 |
| December | 0.259727E+09 | 15835.59 | 26-DEC-06:11 | -1.0 |
| Annual Sum or Average | 0.125438E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -1.0 | |
| Maximum of Months | 0.699566E+09 | 17312.12 | 17.17 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.130469E+10 | 947.12 | 02-JAN-07:10 | 0.892986E+09 | 678.98 | 02-JAN-08:09 |
| February | 0.117967E+10 | 947.12 | 01-FEB-07:10 | 0.807077E+09 | 678.98 | 01-FEB-08:09 |
| March | 0.138135E+10 | 947.12 | 01-MAR-07:10 | 0.924571E+09 | 678.98 | 01-MAR-08:09 |
| April | 0.125024E+10 | 947.12 | 03-APR-06:10 | 0.859085E+09 | 678.98 | 03-APR-07:10 |
| May | 0.134302E+10 | 947.12 | 01-MAY-06:10 | 0.908779E+09 | 678.98 | 01-MAY-07:10 |
| June | 0.132690E+10 | 947.12 | 01-JUN-06:10 | 0.890455E+09 | 678.98 | 01-JUN-07:10 |
| July | 0.793150E+09 | 526.18 | 03-JUL-07:10 | 0.543864E+09 | 357.36 | 03-JUL-07:10 |
| August | 0.837162E+09 | 526.18 | 01-AUG-07:10 | 0.565300E+09 | 357.36 | 01-AUG-07:10 |
| September | 0.122658E+10 | 947.12 | 05-SEP-06:10 | 0.845480E+09 | 678.98 | 05-SEP-07:10 |
| October | 0.130469E+10 | 947.12 | 02-OCT-06:10 | 0.892986E+09 | 678.98 | 02-OCT-07:10 |
| November | 0.128857E+10 | 947.12 | 01-NOV-06:10 | 0.874878E+09 | 678.98 | 01-NOV-07:10 |
| December | 0.126636E+10 | 947.12 | 01-DEC-07:10 | 0.877193E+09 | 678.98 | 01-DEC-08:09 |
| Annual Sum or Average | 0.145024E+11 | 0.988265E+10 | ||||
| Minimum of Months | 0.793150E+09 | 526.18 | 0.543864E+09 | 357.36 | ||
| Maximum of Months | 0.138135E+10 | 947.12 | 0.924571E+09 | 678.98 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.130469E+10 | 947.12 | 02-JAN-07:10 | 0.892986E+09 | 678.98 | 02-JAN-08:09 |
| February | 0.117967E+10 | 947.12 | 01-FEB-07:10 | 0.807077E+09 | 678.98 | 01-FEB-08:09 |
| March | 0.138135E+10 | 947.12 | 01-MAR-07:10 | 0.924571E+09 | 678.98 | 01-MAR-08:09 |
| April | 0.125024E+10 | 947.12 | 03-APR-06:10 | 0.859085E+09 | 678.98 | 03-APR-07:10 |
| May | 0.134302E+10 | 947.12 | 01-MAY-06:10 | 0.908779E+09 | 678.98 | 01-MAY-07:10 |
| June | 0.132690E+10 | 947.12 | 01-JUN-06:10 | 0.890455E+09 | 678.98 | 01-JUN-07:10 |
| July | 0.793150E+09 | 526.18 | 03-JUL-07:10 | 0.543864E+09 | 357.36 | 03-JUL-07:10 |
| August | 0.837162E+09 | 526.18 | 01-AUG-07:10 | 0.565300E+09 | 357.36 | 01-AUG-07:10 |
| September | 0.122658E+10 | 947.12 | 05-SEP-06:10 | 0.845480E+09 | 678.98 | 05-SEP-07:10 |
| October | 0.130469E+10 | 947.12 | 02-OCT-06:10 | 0.892986E+09 | 678.98 | 02-OCT-07:10 |
| November | 0.128857E+10 | 947.12 | 01-NOV-06:10 | 0.874878E+09 | 678.98 | 01-NOV-07:10 |
| December | 0.126636E+10 | 947.12 | 01-DEC-07:10 | 0.877193E+09 | 678.98 | 01-DEC-08:09 |
| Annual Sum or Average | 0.145024E+11 | 0.988265E+10 | ||||
| Minimum of Months | 0.793150E+09 | 526.18 | 0.543864E+09 | 357.36 | ||
| Maximum of Months | 0.138135E+10 | 947.12 | 0.924571E+09 | 678.98 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.130469E+10 | 947.12 | 02-JAN-07:10 | 0.892986E+09 | 678.98 | 02-JAN-08:09 |
| February | 0.117967E+10 | 947.12 | 01-FEB-07:10 | 0.807077E+09 | 678.98 | 01-FEB-08:09 |
| March | 0.138135E+10 | 947.12 | 01-MAR-07:10 | 0.924571E+09 | 678.98 | 01-MAR-08:09 |
| April | 0.125024E+10 | 947.12 | 03-APR-06:10 | 0.859085E+09 | 678.98 | 03-APR-07:10 |
| May | 0.134302E+10 | 947.12 | 01-MAY-06:10 | 0.908779E+09 | 678.98 | 01-MAY-07:10 |
| June | 0.132690E+10 | 947.12 | 01-JUN-06:10 | 0.890455E+09 | 678.98 | 01-JUN-07:10 |
| July | 0.793150E+09 | 526.18 | 03-JUL-07:10 | 0.543864E+09 | 357.36 | 03-JUL-07:10 |
| August | 0.837162E+09 | 526.18 | 01-AUG-07:10 | 0.565300E+09 | 357.36 | 01-AUG-07:10 |
| September | 0.122658E+10 | 947.12 | 05-SEP-06:10 | 0.845480E+09 | 678.98 | 05-SEP-07:10 |
| October | 0.130469E+10 | 947.12 | 02-OCT-06:10 | 0.892986E+09 | 678.98 | 02-OCT-07:10 |
| November | 0.128857E+10 | 947.12 | 01-NOV-06:10 | 0.874878E+09 | 678.98 | 01-NOV-07:10 |
| December | 0.126636E+10 | 947.12 | 01-DEC-07:10 | 0.877193E+09 | 678.98 | 01-DEC-08:09 |
| Annual Sum or Average | 0.145024E+11 | 0.988265E+10 | ||||
| Minimum of Months | 0.793150E+09 | 526.18 | 0.543864E+09 | 357.36 | ||
| Maximum of Months | 0.138135E+10 | 947.12 | 0.924571E+09 | 678.98 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.588512E+10 | 4272.19 | 02-JAN-07:10 | 0.549396E+10 | 4177.31 | 02-JAN-08:09 |
| February | 0.532117E+10 | 4272.19 | 01-FEB-07:10 | 0.496542E+10 | 4177.31 | 01-FEB-08:09 |
| March | 0.623092E+10 | 4272.19 | 01-MAR-07:10 | 0.568828E+10 | 4177.31 | 01-MAR-08:09 |
| April | 0.563950E+10 | 4272.19 | 03-APR-06:10 | 0.528539E+10 | 4177.31 | 03-APR-07:10 |
| May | 0.605802E+10 | 4272.19 | 01-MAY-06:10 | 0.559112E+10 | 4177.31 | 01-MAY-07:10 |
| June | 0.598530E+10 | 4272.19 | 01-JUN-06:10 | 0.547839E+10 | 4177.31 | 01-JUN-07:10 |
| July | 0.357769E+10 | 2373.44 | 03-JUL-07:10 | 0.334604E+10 | 2198.59 | 03-JUL-07:10 |
| August | 0.377621E+10 | 2373.44 | 01-AUG-07:10 | 0.347792E+10 | 2198.59 | 01-AUG-07:10 |
| September | 0.553277E+10 | 4272.19 | 05-SEP-06:10 | 0.520168E+10 | 4177.31 | 05-SEP-07:10 |
| October | 0.588512E+10 | 4272.19 | 02-OCT-06:10 | 0.549396E+10 | 4177.31 | 02-OCT-07:10 |
| November | 0.581240E+10 | 4272.19 | 01-NOV-06:10 | 0.538255E+10 | 4177.31 | 01-NOV-07:10 |
| December | 0.571221E+10 | 4272.19 | 01-DEC-07:10 | 0.539679E+10 | 4177.31 | 01-DEC-08:09 |
| Annual Sum or Average | 0.654164E+11 | 0.608015E+11 | ||||
| Minimum of Months | 0.357769E+10 | 2373.44 | 0.334604E+10 | 2198.59 | ||
| Maximum of Months | 0.623092E+10 | 4272.19 | 0.568828E+10 | 4177.31 |
Report: ZoneElectricSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.302663E+10 | 2197.13 | 02-JAN-07:10 | 0.376728E+10 | 2864.44 | 02-JAN-08:09 |
| February | 0.273660E+10 | 2197.13 | 01-FEB-07:10 | 0.340486E+10 | 2864.44 | 01-FEB-08:09 |
| March | 0.320447E+10 | 2197.13 | 01-MAR-07:10 | 0.390054E+10 | 2864.44 | 01-MAR-08:09 |
| April | 0.290031E+10 | 2197.13 | 03-APR-06:10 | 0.362427E+10 | 2864.44 | 03-APR-07:10 |
| May | 0.311555E+10 | 2197.13 | 01-MAY-06:10 | 0.383391E+10 | 2864.44 | 01-MAY-07:10 |
| June | 0.307815E+10 | 2197.13 | 01-JUN-06:10 | 0.375661E+10 | 2864.44 | 01-JUN-07:10 |
| July | 0.183996E+10 | 1220.63 | 03-JUL-07:10 | 0.229443E+10 | 1507.60 | 03-JUL-07:10 |
| August | 0.194205E+10 | 1220.63 | 01-AUG-07:10 | 0.238486E+10 | 1507.60 | 01-AUG-07:10 |
| September | 0.284543E+10 | 2197.13 | 05-SEP-06:10 | 0.356687E+10 | 2864.44 | 05-SEP-07:10 |
| October | 0.302663E+10 | 2197.13 | 02-OCT-06:10 | 0.376728E+10 | 2864.44 | 02-OCT-07:10 |
| November | 0.298923E+10 | 2197.13 | 01-NOV-06:10 | 0.369089E+10 | 2864.44 | 01-NOV-07:10 |
| December | 0.293771E+10 | 2197.13 | 01-DEC-07:10 | 0.370066E+10 | 2864.44 | 01-DEC-08:09 |
| Annual Sum or Average | 0.336427E+11 | 0.416925E+11 | ||||
| Minimum of Months | 0.183996E+10 | 1220.63 | 0.229443E+10 | 1507.60 | ||
| Maximum of Months | 0.320447E+10 | 2197.13 | 0.390054E+10 | 2864.44 |
Report: ZoneElectricSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.371022E+10 | 2693.36 | 02-JAN-07:10 | 0.253943E+10 | 1930.85 | 02-JAN-08:09 |
| February | 0.335468E+10 | 2693.36 | 01-FEB-07:10 | 0.229513E+10 | 1930.85 | 01-FEB-08:09 |
| March | 0.392822E+10 | 2693.36 | 01-MAR-07:10 | 0.262925E+10 | 1930.85 | 01-MAR-08:09 |
| April | 0.355537E+10 | 2693.36 | 03-APR-06:10 | 0.244302E+10 | 1930.85 | 03-APR-07:10 |
| May | 0.381922E+10 | 2693.36 | 01-MAY-06:10 | 0.258434E+10 | 1930.85 | 01-MAY-07:10 |
| June | 0.377338E+10 | 2693.36 | 01-JUN-06:10 | 0.253223E+10 | 1930.85 | 01-JUN-07:10 |
| July | 0.225552E+10 | 1496.31 | 03-JUL-07:10 | 0.154661E+10 | 1016.24 | 03-JUL-07:10 |
| August | 0.238068E+10 | 1496.31 | 01-AUG-07:10 | 0.160757E+10 | 1016.24 | 01-AUG-07:10 |
| September | 0.348808E+10 | 2693.36 | 05-SEP-06:10 | 0.240433E+10 | 1930.85 | 05-SEP-07:10 |
| October | 0.371022E+10 | 2693.36 | 02-OCT-06:10 | 0.253943E+10 | 1930.85 | 02-OCT-07:10 |
| November | 0.366437E+10 | 2693.36 | 01-NOV-06:10 | 0.248793E+10 | 1930.85 | 01-NOV-07:10 |
| December | 0.360121E+10 | 2693.36 | 01-DEC-07:10 | 0.249452E+10 | 1930.85 | 01-DEC-08:09 |
| Annual Sum or Average | 0.412412E+11 | 0.281038E+11 | ||||
| Minimum of Months | 0.225552E+10 | 1496.31 | 0.154661E+10 | 1016.24 | ||
| Maximum of Months | 0.392822E+10 | 2693.36 | 0.262925E+10 | 1930.85 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.296658E+10 | 2153.53 | 02-JAN-07:10 | 0.795316E+09 | 604.72 | 02-JAN-08:09 |
| February | 0.268230E+10 | 2153.53 | 01-FEB-07:10 | 0.718803E+09 | 604.72 | 01-FEB-08:09 |
| March | 0.314089E+10 | 2153.53 | 01-MAR-07:10 | 0.823446E+09 | 604.72 | 01-MAR-08:09 |
| April | 0.284277E+10 | 2153.53 | 03-APR-06:10 | 0.765123E+09 | 604.72 | 03-APR-07:10 |
| May | 0.305373E+10 | 2153.53 | 01-MAY-06:10 | 0.809381E+09 | 604.72 | 01-MAY-07:10 |
| June | 0.301708E+10 | 2153.53 | 01-JUN-06:10 | 0.793062E+09 | 604.72 | 01-JUN-07:10 |
| July | 0.180345E+10 | 1196.41 | 03-JUL-07:10 | 0.484379E+09 | 318.27 | 03-JUL-07:10 |
| August | 0.190352E+10 | 1196.41 | 01-AUG-07:10 | 0.503470E+09 | 318.27 | 01-AUG-07:10 |
| September | 0.278897E+10 | 2153.53 | 05-SEP-06:10 | 0.753006E+09 | 604.72 | 05-SEP-07:10 |
| October | 0.296658E+10 | 2153.53 | 02-OCT-06:10 | 0.795316E+09 | 604.72 | 02-OCT-07:10 |
| November | 0.292992E+10 | 2153.53 | 01-NOV-06:10 | 0.779188E+09 | 604.72 | 01-NOV-07:10 |
| December | 0.287942E+10 | 2153.53 | 01-DEC-07:10 | 0.781250E+09 | 604.72 | 01-DEC-08:09 |
| Annual Sum or Average | 0.329752E+11 | 0.880174E+10 | ||||
| Minimum of Months | 0.180345E+10 | 1196.41 | 0.484379E+09 | 318.27 | ||
| Maximum of Months | 0.314089E+10 | 2153.53 | 0.823446E+09 | 604.72 |
Report: ZoneElectricSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.504438E+10 | 3661.88 | 02-JAN-07:10 | 0.293011E+10 | 2227.90 | 02-JAN-08:09 |
| February | 0.456100E+10 | 3661.88 | 01-FEB-07:10 | 0.264822E+10 | 2227.90 | 01-FEB-08:09 |
| March | 0.534079E+10 | 3661.88 | 01-MAR-07:10 | 0.303375E+10 | 2227.90 | 01-MAR-08:09 |
| April | 0.483386E+10 | 3661.88 | 03-APR-06:10 | 0.281887E+10 | 2227.90 | 03-APR-07:10 |
| May | 0.519259E+10 | 3661.88 | 01-MAY-06:10 | 0.298193E+10 | 2227.90 | 01-MAY-07:10 |
| June | 0.513026E+10 | 3661.88 | 01-JUN-06:10 | 0.292181E+10 | 2227.90 | 01-JUN-07:10 |
| July | 0.306659E+10 | 2034.38 | 03-JUL-07:10 | 0.178455E+10 | 1172.58 | 03-JUL-07:10 |
| August | 0.323676E+10 | 2034.38 | 01-AUG-07:10 | 0.185489E+10 | 1172.58 | 01-AUG-07:10 |
| September | 0.474238E+10 | 3661.88 | 05-SEP-06:10 | 0.277423E+10 | 2227.90 | 05-SEP-07:10 |
| October | 0.504438E+10 | 3661.88 | 02-OCT-06:10 | 0.293011E+10 | 2227.90 | 02-OCT-07:10 |
| November | 0.498206E+10 | 3661.88 | 01-NOV-06:10 | 0.287069E+10 | 2227.90 | 01-NOV-07:10 |
| December | 0.489618E+10 | 3661.88 | 01-DEC-07:10 | 0.287829E+10 | 2227.90 | 01-DEC-08:09 |
| Annual Sum or Average | 0.560712E+11 | 0.324275E+11 | ||||
| Minimum of Months | 0.306659E+10 | 2034.38 | 0.178455E+10 | 1172.58 | ||
| Maximum of Months | 0.534079E+10 | 3661.88 | 0.303375E+10 | 2227.90 |
Report: ZoneElectricSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.228198E+10 | 1656.56 | 02-JAN-07:10 | 0.883684E+09 | 671.91 | 02-JAN-08:09 |
| February | 0.206331E+10 | 1656.56 | 01-FEB-07:10 | 0.798670E+09 | 671.91 | 01-FEB-08:09 |
| March | 0.241607E+10 | 1656.56 | 01-MAR-07:10 | 0.914940E+09 | 671.91 | 01-MAR-08:09 |
| April | 0.218674E+10 | 1656.56 | 03-APR-06:10 | 0.850137E+09 | 671.91 | 03-APR-07:10 |
| May | 0.234903E+10 | 1656.56 | 01-MAY-06:10 | 0.899312E+09 | 671.91 | 01-MAY-07:10 |
| June | 0.232083E+10 | 1656.56 | 01-JUN-06:10 | 0.881180E+09 | 671.91 | 01-JUN-07:10 |
| July | 0.138727E+10 | 920.31 | 03-JUL-07:10 | 0.538198E+09 | 353.64 | 03-JUL-07:10 |
| August | 0.146425E+10 | 920.31 | 01-AUG-07:10 | 0.559411E+09 | 353.64 | 01-AUG-07:10 |
| September | 0.214536E+10 | 1656.56 | 05-SEP-06:10 | 0.836673E+09 | 671.91 | 05-SEP-07:10 |
| October | 0.228198E+10 | 1656.56 | 02-OCT-06:10 | 0.883684E+09 | 671.91 | 02-OCT-07:10 |
| November | 0.225379E+10 | 1656.56 | 01-NOV-06:10 | 0.865765E+09 | 671.91 | 01-NOV-07:10 |
| December | 0.221494E+10 | 1656.56 | 01-DEC-07:10 | 0.868056E+09 | 671.91 | 01-DEC-08:09 |
| Annual Sum or Average | 0.253655E+11 | 0.977971E+10 | ||||
| Minimum of Months | 0.138727E+10 | 920.31 | 0.538198E+09 | 353.64 | ||
| Maximum of Months | 0.241607E+10 | 1656.56 | 0.914940E+09 | 671.91 |
Report: ZoneElectricSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.647363E+10 | 4699.41 | 02-JAN-07:10 | 0.553791E+10 | 4210.73 | 02-JAN-08:09 |
| February | 0.585328E+10 | 4699.41 | 01-FEB-07:10 | 0.500514E+10 | 4210.73 | 01-FEB-08:09 |
| March | 0.685401E+10 | 4699.41 | 01-MAR-07:10 | 0.573379E+10 | 4210.73 | 01-MAR-08:09 |
| April | 0.620345E+10 | 4699.41 | 03-APR-06:10 | 0.532767E+10 | 4210.73 | 03-APR-07:10 |
| May | 0.666382E+10 | 4699.41 | 01-MAY-06:10 | 0.563585E+10 | 4210.73 | 01-MAY-07:10 |
| June | 0.658383E+10 | 4699.41 | 01-JUN-06:10 | 0.552221E+10 | 4210.73 | 01-JUN-07:10 |
| July | 0.393546E+10 | 2610.78 | 03-JUL-07:10 | 0.337280E+10 | 2216.18 | 03-JUL-07:10 |
| August | 0.415384E+10 | 2610.78 | 01-AUG-07:10 | 0.350574E+10 | 2216.18 | 01-AUG-07:10 |
| September | 0.608605E+10 | 4699.41 | 05-SEP-06:10 | 0.524330E+10 | 4210.73 | 05-SEP-07:10 |
| October | 0.647363E+10 | 4699.41 | 02-OCT-06:10 | 0.553791E+10 | 4210.73 | 02-OCT-07:10 |
| November | 0.639364E+10 | 4699.41 | 01-NOV-06:10 | 0.542561E+10 | 4210.73 | 01-NOV-07:10 |
| December | 0.628344E+10 | 4699.41 | 01-DEC-07:10 | 0.543997E+10 | 4210.73 | 01-DEC-08:09 |
| Annual Sum or Average | 0.719581E+11 | 0.612879E+11 | ||||
| Minimum of Months | 0.393546E+10 | 2610.78 | 0.337280E+10 | 2216.18 | ||
| Maximum of Months | 0.685401E+10 | 4699.41 | 0.573379E+10 | 4210.73 |
Report: ZoneElectricSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.590754E+10 | 4288.47 | 02-JAN-07:10 | 0.207549E+10 | 1578.10 | 02-JAN-08:09 |
| February | 0.534144E+10 | 4288.47 | 01-FEB-07:10 | 0.187582E+10 | 1578.10 | 01-FEB-08:09 |
| March | 0.625466E+10 | 4288.47 | 01-MAR-07:10 | 0.214891E+10 | 1578.10 | 01-MAR-08:09 |
| April | 0.566098E+10 | 4288.47 | 03-APR-06:10 | 0.199670E+10 | 1578.10 | 03-APR-07:10 |
| May | 0.608110E+10 | 4288.47 | 01-MAY-06:10 | 0.211220E+10 | 1578.10 | 01-MAY-07:10 |
| June | 0.600810E+10 | 4288.47 | 01-JUN-06:10 | 0.206961E+10 | 1578.10 | 01-JUN-07:10 |
| July | 0.359132E+10 | 2382.48 | 03-JUL-07:10 | 0.126406E+10 | 830.58 | 03-JUL-07:10 |
| August | 0.379060E+10 | 2382.48 | 01-AUG-07:10 | 0.131388E+10 | 830.58 | 01-AUG-07:10 |
| September | 0.555385E+10 | 4288.47 | 05-SEP-06:10 | 0.196508E+10 | 1578.10 | 05-SEP-07:10 |
| October | 0.590754E+10 | 4288.47 | 02-OCT-06:10 | 0.207549E+10 | 1578.10 | 02-OCT-07:10 |
| November | 0.583454E+10 | 4288.47 | 01-NOV-06:10 | 0.203341E+10 | 1578.10 | 01-NOV-07:10 |
| December | 0.573398E+10 | 4288.47 | 01-DEC-07:10 | 0.203879E+10 | 1578.10 | 01-DEC-08:09 |
| Annual Sum or Average | 0.656656E+11 | 0.229695E+11 | ||||
| Minimum of Months | 0.359132E+10 | 2382.48 | 0.126406E+10 | 830.58 | ||
| Maximum of Months | 0.625466E+10 | 4288.47 | 0.214891E+10 | 1578.10 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.269034E+10 | 1953.00 | 02-JAN-07:10 | 0.147381E+11 | 9714.90 | 02-JAN-10:09 |
| February | 0.243253E+10 | 1953.00 | 01-FEB-07:10 | 0.133142E+11 | 9714.90 | 01-FEB-10:09 |
| March | 0.284842E+10 | 1953.00 | 01-MAR-07:10 | 0.148878E+11 | 9714.90 | 01-MAR-10:09 |
| April | 0.257806E+10 | 1953.00 | 03-APR-06:10 | 0.142385E+11 | 9714.90 | 03-APR-09:09 |
| May | 0.276938E+10 | 1953.00 | 01-MAY-06:10 | 0.148130E+11 | 9714.90 | 01-MAY-09:09 |
| June | 0.273614E+10 | 1953.00 | 01-JUN-06:10 | 0.143883E+11 | 9714.90 | 01-JUN-09:09 |
| July | 0.163552E+10 | 1085.00 | 03-JUL-07:10 | 0.146632E+11 | 9714.90 | 03-JUL-09:09 |
| August | 0.172627E+10 | 1085.00 | 01-AUG-07:10 | 0.148878E+11 | 9714.90 | 01-AUG-09:09 |
| September | 0.252927E+10 | 1953.00 | 05-SEP-06:10 | 0.142385E+11 | 9714.90 | 01-SEP-09:09 |
| October | 0.269034E+10 | 1953.00 | 02-OCT-06:10 | 0.147381E+11 | 9714.90 | 02-OCT-09:09 |
| November | 0.265710E+10 | 1953.00 | 01-NOV-06:10 | 0.143134E+11 | 9714.90 | 01-NOV-09:09 |
| December | 0.261130E+10 | 1953.00 | 01-DEC-07:10 | 0.146632E+11 | 9714.90 | 01-DEC-10:09 |
| Annual Sum or Average | 0.299046E+11 | 0.173884E+12 | ||||
| Minimum of Months | 0.163552E+10 | 1085.00 | 0.133142E+11 | 9714.90 | ||
| Maximum of Months | 0.284842E+10 | 1953.00 | 0.148878E+11 | 9714.90 |
Report: ZoneElectricSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.378329E+10 | 2746.41 | 02-JAN-07:10 | 0.253516E+10 | 1999.46 | 02-JAN-10:09 |
| February | 0.342075E+10 | 2746.41 | 01-FEB-07:10 | 0.229042E+10 | 1999.46 | 01-FEB-10:09 |
| March | 0.400559E+10 | 2746.41 | 01-MAR-07:10 | 0.257259E+10 | 1999.46 | 01-MAR-10:09 |
| April | 0.362539E+10 | 2746.41 | 03-APR-06:10 | 0.244734E+10 | 1999.46 | 03-APR-09:09 |
| May | 0.389444E+10 | 2746.41 | 01-MAY-06:10 | 0.255387E+10 | 1999.46 | 01-MAY-09:09 |
| June | 0.384769E+10 | 2746.41 | 01-JUN-06:10 | 0.248477E+10 | 1999.46 | 01-JUN-09:09 |
| July | 0.229994E+10 | 1525.78 | 03-JUL-07:10 | 0.251644E+10 | 1999.46 | 03-JUL-09:09 |
| August | 0.242757E+10 | 1525.78 | 01-AUG-07:10 | 0.257259E+10 | 1999.46 | 01-AUG-09:09 |
| September | 0.355678E+10 | 2746.41 | 05-SEP-06:10 | 0.244734E+10 | 1999.46 | 01-SEP-09:09 |
| October | 0.378329E+10 | 2746.41 | 02-OCT-06:10 | 0.253516E+10 | 1999.46 | 02-OCT-09:09 |
| November | 0.373654E+10 | 2746.41 | 01-NOV-06:10 | 0.246606E+10 | 1999.46 | 01-NOV-09:09 |
| December | 0.367214E+10 | 2746.41 | 01-DEC-07:10 | 0.251644E+10 | 1999.46 | 01-DEC-10:09 |
| Annual Sum or Average | 0.420534E+11 | 0.299382E+11 | ||||
| Minimum of Months | 0.229994E+10 | 1525.78 | 0.229042E+10 | 1999.46 | ||
| Maximum of Months | 0.400559E+10 | 2746.41 | 0.257259E+10 | 1999.46 |
Report: ZoneElectricSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.825317E+10 | 5991.24 | 02-JAN-07:10 | 0.695901E+10 | 5291.26 | 02-JAN-08:09 |
| February | 0.746230E+10 | 5991.24 | 01-FEB-07:10 | 0.628953E+10 | 5291.26 | 01-FEB-08:09 |
| March | 0.873812E+10 | 5991.24 | 01-MAR-07:10 | 0.720516E+10 | 5291.26 | 01-MAR-08:09 |
| April | 0.790872E+10 | 5991.24 | 03-APR-06:10 | 0.669483E+10 | 5291.26 | 03-APR-07:10 |
| May | 0.849564E+10 | 5991.24 | 01-MAY-06:10 | 0.708208E+10 | 5291.26 | 01-MAY-07:10 |
| June | 0.839367E+10 | 5991.24 | 01-JUN-06:10 | 0.693929E+10 | 5291.26 | 01-JUN-07:10 |
| July | 0.501728E+10 | 3328.47 | 03-JUL-07:10 | 0.423831E+10 | 2784.88 | 03-JUL-07:10 |
| August | 0.529569E+10 | 3328.47 | 01-AUG-07:10 | 0.440537E+10 | 2784.88 | 01-AUG-07:10 |
| September | 0.775905E+10 | 5991.24 | 05-SEP-06:10 | 0.658880E+10 | 5291.26 | 05-SEP-07:10 |
| October | 0.825317E+10 | 5991.24 | 02-OCT-06:10 | 0.695901E+10 | 5291.26 | 02-OCT-07:10 |
| November | 0.815120E+10 | 5991.24 | 01-NOV-06:10 | 0.681790E+10 | 5291.26 | 01-NOV-07:10 |
| December | 0.801070E+10 | 5991.24 | 01-DEC-07:10 | 0.683594E+10 | 5291.26 | 01-DEC-08:09 |
| Annual Sum or Average | 0.917387E+11 | 0.770152E+11 | ||||
| Minimum of Months | 0.501728E+10 | 3328.47 | 0.423831E+10 | 2784.88 | ||
| Maximum of Months | 0.873812E+10 | 5991.24 | 0.720516E+10 | 5291.26 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325114E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293689E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294393E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 260521.74 | 0.295960E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20154.23 | 0.234166E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 176251.61 | 0.184623E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2857936.10 | 0.152654E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4306599.19 | 0.127306E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17127.79 | 0.122997E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265979E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262546E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280745E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7638590.66 | 0.284017E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122997E+09 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4306599.19 | 0.325114E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929583E+09 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846060E+09 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.858014E+09 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 849074.59 | 0.858917E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62947.12 | 0.657075E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 513741.06 | 0.514821E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11244557.75 | 0.404028E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13613037.49 | 0.342495E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45389.83 | 0.342100E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768918E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761715E+09 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815029E+09 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26328747.83 | 0.809876E+10 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342100E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13613037.49 | 0.929583E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51983361.56 |
| February | 0.708259E+09 | 0.117967E+10 | 0.807077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46358462.76 |
| March | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46548158.17 |
| April | 0.745536E+09 | 0.125024E+10 | 0.859085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 154926.63 | 47039749.50 |
| May | 0.820090E+09 | 0.134302E+10 | 0.908779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2572.61 | 37188246.66 |
| June | 0.505804E+09 | 0.132690E+10 | 0.890455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26043.55 | 29716228.98 |
| July | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 519963.40 | 22936142.58 |
| August | 0.200223E+09 | 0.837162E+09 | 0.565300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 676269.43 | 18696445.58 |
| September | 0.459822E+09 | 0.122658E+10 | 0.845480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2568.08 | 18214006.49 |
| October | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41088857.81 |
| November | 0.782813E+09 | 0.128857E+10 | 0.874878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41593187.93 |
| December | 0.745536E+09 | 0.126636E+10 | 0.877193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44905430.18 |
| Annual Sum or Average | 0.756518E+10 | 0.145024E+11 | 0.988265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1382343.71 | 0.446268E+09 |
| Minimum of Months | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18214006.49 |
| Maximum of Months | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 676269.43 | 51983361.56 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317286E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279591E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273087E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 948136.51 | 0.276001E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 114727.26 | 0.221894E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 215395.74 | 0.176370E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4800633.48 | 0.139470E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6731515.36 | 0.112707E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24750.96 | 0.109763E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243370E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251328E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268751E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12835159.32 | 0.266962E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109763E+09 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6731515.36 | 0.317286E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.902083E+09 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799668E+09 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795480E+09 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2762101.28 | 0.801991E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 634431.17 | 0.623763E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 922325.93 | 0.490533E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18302213.84 | 0.366355E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23533045.19 | 0.297724E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 306863.62 | 0.302976E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703062E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.728068E+09 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779762E+09 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46460981.04 | 0.759147E+10 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297724E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23533045.19 | 0.902083E+09 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324392E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293400E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293868E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 280823.39 | 0.294732E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22814.74 | 0.233006E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 178459.73 | 0.183421E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2926071.01 | 0.151050E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4374600.28 | 0.126415E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17127.82 | 0.122539E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265504E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262137E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278801E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7799896.98 | 0.282926E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122539E+09 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4374600.28 | 0.324392E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.927578E+09 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.845765E+09 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.857655E+09 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 922295.90 | 0.857513E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 75565.18 | 0.655580E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 540899.68 | 0.512408E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11638802.16 | 0.399893E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14114838.64 | 0.339652E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45389.98 | 0.340753E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767944E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761154E+09 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.809154E+09 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27337791.55 | 0.807505E+10 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.339652E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14114838.64 | 0.927578E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51922822.11 |
| February | 0.708259E+09 | 0.117967E+10 | 0.807077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46342871.80 |
| March | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46519871.42 |
| April | 0.745536E+09 | 0.125024E+10 | 0.859085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 156720.91 | 46990175.45 |
| May | 0.820090E+09 | 0.134302E+10 | 0.908779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2572.62 | 37143604.36 |
| June | 0.505804E+09 | 0.132690E+10 | 0.890455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26043.56 | 29656120.71 |
| July | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 526577.83 | 22819401.75 |
| August | 0.200223E+09 | 0.837162E+09 | 0.565300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 683400.52 | 18615021.95 |
| September | 0.459822E+09 | 0.122658E+10 | 0.845480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2568.09 | 18175371.59 |
| October | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41059761.30 |
| November | 0.782813E+09 | 0.128857E+10 | 0.874878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41551696.59 |
| December | 0.745536E+09 | 0.126636E+10 | 0.877193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44747515.25 |
| Annual Sum or Average | 0.756518E+10 | 0.145024E+11 | 0.988265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1397883.52 | 0.445544E+09 |
| Minimum of Months | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18175371.59 |
| Maximum of Months | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 683400.52 | 51922822.11 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317220E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279582E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273081E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 947024.42 | 0.276036E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 113495.20 | 0.221943E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 214943.82 | 0.176399E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4804430.77 | 0.139408E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6735856.55 | 0.112644E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24732.32 | 0.109727E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243354E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251242E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268518E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12840483.08 | 0.266915E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109727E+09 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6735856.55 | 0.317220E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901868E+09 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.799683E+09 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795539E+09 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2757822.59 | 0.802214E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 625250.97 | 0.624051E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 912474.39 | 0.490828E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18282463.75 | 0.366387E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23512437.79 | 0.297666E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 304346.74 | 0.302948E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703134E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.727873E+09 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.779106E+09 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 46394796.23 | 0.759130E+10 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297666E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23512437.79 | 0.901868E+09 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325090E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293987E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295176E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 264400.88 | 0.296362E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21758.75 | 0.233932E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 177351.46 | 0.184358E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2855723.25 | 0.152503E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4324730.70 | 0.127460E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17127.81 | 0.123201E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266859E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263406E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279909E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 7661092.86 | 0.284224E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123201E+09 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4324730.70 | 0.325090E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930374E+09 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.848247E+09 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862995E+09 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 838104.11 | 0.863567E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70036.28 | 0.658775E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 522805.42 | 0.516044E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11250272.49 | 0.404909E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13773330.25 | 0.343765E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45389.91 | 0.343376E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773662E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766935E+09 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.813306E+09 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 26499938.45 | 0.812596E+10 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343376E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13773330.25 | 0.930374E+09 |
Report: SpaceGainsMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52170856.38 |
| February | 0.708259E+09 | 0.117967E+10 | 0.807077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46659212.08 |
| March | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47199711.01 |
| April | 0.745536E+09 | 0.125024E+10 | 0.859085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 142416.18 | 47798455.19 |
| May | 0.820090E+09 | 0.134302E+10 | 0.908779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2572.59 | 37621214.74 |
| June | 0.505804E+09 | 0.132690E+10 | 0.890455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26043.45 | 30142273.21 |
| July | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 487565.05 | 23524287.54 |
| August | 0.200223E+09 | 0.837162E+09 | 0.565300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 650660.63 | 19177821.10 |
| September | 0.459822E+09 | 0.122658E+10 | 0.845480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2568.07 | 18520805.06 |
| October | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41742137.08 |
| November | 0.782813E+09 | 0.128857E+10 | 0.874878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42129714.38 |
| December | 0.745536E+09 | 0.126636E+10 | 0.877193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45082606.12 |
| Annual Sum or Average | 0.756518E+10 | 0.145024E+11 | 0.988265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1311825.97 | 0.451769E+09 |
| Minimum of Months | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18520805.06 |
| Maximum of Months | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 650660.63 | 52170856.38 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317382E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280108E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274629E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 887258.69 | 0.278772E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85944.06 | 0.224070E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 204113.13 | 0.178648E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4579880.04 | 0.142236E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6481256.26 | 0.114440E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21324.39 | 0.110852E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.244859E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252117E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268789E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12259776.57 | 0.268690E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110852E+09 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6481256.26 | 0.317382E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.642132E+10 | 0.588512E+10 | 0.549396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595440E+09 |
| February | 0.580977E+10 | 0.532117E+10 | 0.496542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528847E+09 |
| March | 0.703288E+10 | 0.623092E+10 | 0.568828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528228E+09 |
| April | 0.611554E+10 | 0.563950E+10 | 0.528539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1678593.93 | 0.535310E+09 |
| May | 0.672710E+10 | 0.605802E+10 | 0.559112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 312413.39 | 0.416149E+09 |
| June | 0.414905E+10 | 0.598530E+10 | 0.547839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 496625.85 | 0.329243E+09 |
| July | 0.142818E+10 | 0.357769E+10 | 0.334604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11405041.65 | 0.248179E+09 |
| August | 0.164241E+10 | 0.377621E+10 | 0.347792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14775913.13 | 0.200200E+09 |
| September | 0.377186E+10 | 0.553277E+10 | 0.520168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 154603.57 | 0.202392E+09 |
| October | 0.642132E+10 | 0.588512E+10 | 0.549396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.467440E+09 |
| November | 0.642132E+10 | 0.581240E+10 | 0.538255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482668E+09 |
| December | 0.611554E+10 | 0.571221E+10 | 0.539679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514575E+09 |
| Annual Sum or Average | 0.620563E+11 | 0.654164E+11 | 0.608015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 28823191.53 | 0.504867E+10 |
| Minimum of Months | 0.142818E+10 | 0.357769E+10 | 0.334604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200200E+09 |
| Maximum of Months | 0.703288E+10 | 0.623092E+10 | 0.568828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14775913.13 | 0.595440E+09 |
Report: SpaceGainsMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.488438E+10 | 0.302663E+10 | 0.376728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318820E+09 |
| February | 0.441920E+10 | 0.273660E+10 | 0.340486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285854E+09 |
| March | 0.534956E+10 | 0.320447E+10 | 0.390054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292801E+09 |
| April | 0.465179E+10 | 0.290031E+10 | 0.362427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 548918.49 | 0.297711E+09 |
| May | 0.511697E+10 | 0.311555E+10 | 0.383391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47403.15 | 0.229460E+09 |
| June | 0.511697E+10 | 0.307815E+10 | 0.375661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166692.60 | 0.183981E+09 |
| July | 0.244831E+10 | 0.183996E+10 | 0.229443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4385681.82 | 0.143743E+09 |
| August | 0.281556E+10 | 0.194205E+10 | 0.238486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5418363.31 | 0.118327E+09 |
| September | 0.454162E+10 | 0.284543E+10 | 0.356687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17953.57 | 0.115029E+09 |
| October | 0.488438E+10 | 0.302663E+10 | 0.376728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261512E+09 |
| November | 0.488438E+10 | 0.298923E+10 | 0.369089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266808E+09 |
| December | 0.465179E+10 | 0.293771E+10 | 0.370066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279192E+09 |
| Annual Sum or Average | 0.537649E+11 | 0.336427E+11 | 0.416925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10585012.94 | 0.279324E+10 |
| Minimum of Months | 0.244831E+10 | 0.183996E+10 | 0.229443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115029E+09 |
| Maximum of Months | 0.534956E+10 | 0.320447E+10 | 0.390054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5418363.31 | 0.318820E+09 |
Report: SpaceGainsMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.222618E+10 | 0.371022E+10 | 0.253943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156549E+09 |
| February | 0.201416E+10 | 0.335468E+10 | 0.229513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140112E+09 |
| March | 0.243819E+10 | 0.392822E+10 | 0.262925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142643E+09 |
| April | 0.212017E+10 | 0.355537E+10 | 0.244302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 438676.26 | 0.148167E+09 |
| May | 0.233218E+10 | 0.381922E+10 | 0.258434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7718.31 | 0.118426E+09 |
| June | 0.143841E+10 | 0.377338E+10 | 0.253223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78131.10 | 95757220.26 |
| July | 0.495129E+09 | 0.225552E+10 | 0.154661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 964534.34 | 78863205.55 |
| August | 0.569398E+09 | 0.238068E+10 | 0.160757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1717663.44 | 64303401.06 |
| September | 0.130765E+10 | 0.348808E+10 | 0.240433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7704.33 | 57372643.63 |
| October | 0.222618E+10 | 0.371022E+10 | 0.253943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125320E+09 |
| November | 0.222618E+10 | 0.366437E+10 | 0.248793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124912E+09 |
| December | 0.212017E+10 | 0.360121E+10 | 0.249452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134656E+09 |
| Annual Sum or Average | 0.215140E+11 | 0.412412E+11 | 0.281038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3214427.77 | 0.138708E+10 |
| Minimum of Months | 0.495129E+09 | 0.225552E+10 | 0.154661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57372643.63 |
| Maximum of Months | 0.243819E+10 | 0.392822E+10 | 0.262925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1717663.44 | 0.156549E+09 |
Report: SpaceGainsMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.139443E+10 | 0.296658E+10 | 0.795316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.846324E+10 |
| February | 0.126163E+10 | 0.268230E+10 | 0.718803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.726619E+10 |
| March | 0.152723E+10 | 0.314089E+10 | 0.823446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795827E+10 |
| April | 0.132803E+10 | 0.284277E+10 | 0.765123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49085920.23 | 0.597140E+10 |
| May | 0.146083E+10 | 0.305373E+10 | 0.809381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9810267.23 | 0.537051E+10 |
| June | 0.900991E+09 | 0.301708E+10 | 0.793062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 38235837.77 | 0.404835E+10 |
| July | 0.310138E+09 | 0.180345E+10 | 0.484379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248661E+09 | 0.234152E+10 |
| August | 0.356659E+09 | 0.190352E+10 | 0.503470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672017E+09 | 0.224958E+10 |
| September | 0.819082E+09 | 0.278897E+10 | 0.753006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8577850.43 | 0.384626E+10 |
| October | 0.139443E+10 | 0.296658E+10 | 0.795316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.599264E+10 |
| November | 0.139443E+10 | 0.292992E+10 | 0.779188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761168E+10 |
| December | 0.132803E+10 | 0.287942E+10 | 0.781250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.815579E+10 |
| Annual Sum or Average | 0.134759E+11 | 0.329752E+11 | 0.880174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102639E+10 | 0.692754E+11 |
| Minimum of Months | 0.310138E+09 | 0.180345E+10 | 0.484379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224958E+10 |
| Maximum of Months | 0.152723E+10 | 0.314089E+10 | 0.823446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.672017E+09 | 0.846324E+10 |
Report: SpaceGainsMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.308232E+09 | 0.504438E+10 | 0.293011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.278876E+09 | 0.456100E+10 | 0.264822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.337587E+09 | 0.534079E+10 | 0.303375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.293554E+09 | 0.483386E+10 | 0.281887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.322909E+09 | 0.519259E+10 | 0.298193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.199160E+09 | 0.513026E+10 | 0.292181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 68554512.00 | 0.306659E+10 | 0.178455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 78837688.80 | 0.323676E+10 | 0.185489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.181054E+09 | 0.474238E+10 | 0.277423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.308232E+09 | 0.504438E+10 | 0.293011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.308232E+09 | 0.498206E+10 | 0.287069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.293554E+09 | 0.489618E+10 | 0.287829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.297878E+10 | 0.560712E+11 | 0.324275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68554512.00 | 0.306659E+10 | 0.178455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.337587E+09 | 0.534079E+10 | 0.303375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.774708E+09 | 0.228198E+10 | 0.883684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162245E+09 |
| February | 0.700926E+09 | 0.206331E+10 | 0.798670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147279E+09 |
| March | 0.848489E+09 | 0.241607E+10 | 0.914940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155213E+09 |
| April | 0.737817E+09 | 0.218674E+10 | 0.850137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 365040.87 | 0.162564E+09 |
| May | 0.811598E+09 | 0.234903E+10 | 0.899312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134915E+09 |
| June | 0.500567E+09 | 0.232083E+10 | 0.881180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113028E+09 |
| July | 0.172304E+09 | 0.138727E+10 | 0.538198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 555434.07 | 93046878.02 |
| August | 0.198150E+09 | 0.146425E+10 | 0.559411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1136734.79 | 76039019.81 |
| September | 0.455061E+09 | 0.214536E+10 | 0.836673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66080020.72 |
| October | 0.774708E+09 | 0.228198E+10 | 0.883684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138131E+09 |
| November | 0.774708E+09 | 0.225379E+10 | 0.865765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135864E+09 |
| December | 0.737817E+09 | 0.221494E+10 | 0.868056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140958E+09 |
| Annual Sum or Average | 0.748685E+10 | 0.253655E+11 | 0.977971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2057209.73 | 0.152536E+10 |
| Minimum of Months | 0.172304E+09 | 0.138727E+10 | 0.538198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66080020.72 |
| Maximum of Months | 0.848489E+09 | 0.241607E+10 | 0.914940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1136734.79 | 0.162564E+09 |
Report: SpaceGainsMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.156120E+10 | 0.647363E+10 | 0.553791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716275E+09 |
| February | 0.141251E+10 | 0.585328E+10 | 0.500514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651556E+09 |
| March | 0.170988E+10 | 0.685401E+10 | 0.573379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.676101E+09 |
| April | 0.148685E+10 | 0.620345E+10 | 0.532767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 925756.21 | 0.697626E+09 |
| May | 0.163554E+10 | 0.666382E+10 | 0.563585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33632.02 | 0.550524E+09 |
| June | 0.163554E+10 | 0.658383E+10 | 0.552221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 351396.74 | 0.451936E+09 |
| July | 0.840841E+09 | 0.393546E+10 | 0.337280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3510572.23 | 0.377921E+09 |
| August | 0.966967E+09 | 0.415384E+10 | 0.350574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7232354.61 | 0.317934E+09 |
| September | 0.145455E+10 | 0.608605E+10 | 0.524330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34196.33 | 0.280749E+09 |
| October | 0.156120E+10 | 0.647363E+10 | 0.553791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604840E+09 |
| November | 0.156120E+10 | 0.639364E+10 | 0.542561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.590927E+09 |
| December | 0.148685E+10 | 0.628344E+10 | 0.543997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621674E+09 |
| Annual Sum or Average | 0.173131E+11 | 0.719581E+11 | 0.612879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 12087908.14 | 0.653806E+10 |
| Minimum of Months | 0.840841E+09 | 0.393546E+10 | 0.337280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280749E+09 |
| Maximum of Months | 0.170988E+10 | 0.685401E+10 | 0.573379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7232354.61 | 0.716275E+09 |
Report: SpaceGainsMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.789800E+10 | 0.590754E+10 | 0.207549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314163E+09 |
| February | 0.714581E+10 | 0.534144E+10 | 0.187582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286359E+09 |
| March | 0.865019E+10 | 0.625466E+10 | 0.214891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294664E+09 |
| April | 0.752191E+10 | 0.566098E+10 | 0.199670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 217849.29 | 0.304296E+09 |
| May | 0.827410E+10 | 0.608110E+10 | 0.211220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14619.36 | 0.233195E+09 |
| June | 0.827410E+10 | 0.600810E+10 | 0.206961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 147843.74 | 0.188178E+09 |
| July | 0.453307E+10 | 0.359132E+10 | 0.126406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1876261.63 | 0.160155E+09 |
| August | 0.521303E+10 | 0.379060E+10 | 0.131388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3320535.83 | 0.132195E+09 |
| September | 0.737247E+10 | 0.555385E+10 | 0.196508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14602.83 | 0.114763E+09 |
| October | 0.789800E+10 | 0.590754E+10 | 0.207549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254375E+09 |
| November | 0.789800E+10 | 0.583454E+10 | 0.203341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.256412E+09 |
| December | 0.752191E+10 | 0.573398E+10 | 0.203879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.274112E+09 |
| Annual Sum or Average | 0.882006E+11 | 0.656656E+11 | 0.229695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 5591712.68 | 0.281287E+10 |
| Minimum of Months | 0.453307E+10 | 0.359132E+10 | 0.126406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114763E+09 |
| Maximum of Months | 0.865019E+10 | 0.625466E+10 | 0.214891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3320535.83 | 0.314163E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.204475E+10 | 0.269034E+10 | 0.811357E+10 | 0.909844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207529E+09 |
| February | 0.185001E+10 | 0.243253E+10 | 0.733032E+10 | 0.822599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182194E+09 |
| March | 0.223949E+10 | 0.284842E+10 | 0.823336E+10 | 0.959699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171465E+09 |
| April | 0.194738E+10 | 0.257806E+10 | 0.783252E+10 | 0.872454E+10 | 0.00 | 0.00 | 0.00 | 73490.55 | 0.165232E+09 |
| May | 0.214212E+10 | 0.276938E+10 | 0.817347E+10 | 0.934772E+10 | 0.00 | 0.00 | 0.00 | 11597.10 | 0.122961E+09 |
| June | 0.132119E+10 | 0.273614E+10 | 0.795231E+10 | 0.922308E+10 | 0.00 | 0.00 | 0.00 | 69421.92 | 99521631.84 |
| July | 0.454778E+09 | 0.163552E+10 | 0.805368E+10 | 0.884917E+10 | 0.00 | 0.00 | 0.00 | 575560.88 | 85609012.77 |
| August | 0.522995E+09 | 0.172627E+10 | 0.823336E+10 | 0.959699E+10 | 0.00 | 0.00 | 0.00 | 1388990.97 | 72128987.46 |
| September | 0.120108E+10 | 0.252927E+10 | 0.783252E+10 | 0.872454E+10 | 0.00 | 0.00 | 0.00 | 6841.44 | 62267404.96 |
| October | 0.204475E+10 | 0.269034E+10 | 0.811357E+10 | 0.909844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144773E+09 |
| November | 0.204475E+10 | 0.265710E+10 | 0.789242E+10 | 0.897381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158080E+09 |
| December | 0.194738E+10 | 0.261130E+10 | 0.805368E+10 | 0.884917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179574E+09 |
| Annual Sum or Average | 0.197607E+11 | 0.299046E+11 | 0.958148E+11 | 0.108309E+12 | 0.00 | 0.00 | 0.00 | 2125902.85 | 0.165133E+10 |
| Minimum of Months | 0.454778E+09 | 0.163552E+10 | 0.733032E+10 | 0.822599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 62267404.96 |
| Maximum of Months | 0.223949E+10 | 0.284842E+10 | 0.823336E+10 | 0.959699E+10 | 0.00 | 0.00 | 0.00 | 1388990.97 | 0.207529E+09 |
Report: SpaceGainsMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.229168E+11 | 0.378329E+10 | 0.253516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.642363E+09 |
| February | 0.207343E+11 | 0.342075E+10 | 0.229042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576021E+09 |
| March | 0.250994E+11 | 0.400559E+10 | 0.257259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.568145E+09 |
| April | 0.218255E+11 | 0.362539E+10 | 0.244734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1171485.53 | 0.577899E+09 |
| May | 0.240081E+11 | 0.389444E+10 | 0.255387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33047.78 | 0.465789E+09 |
| June | 0.240081E+11 | 0.384769E+10 | 0.248477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 315612.00 | 0.398076E+09 |
| July | 0.556624E+10 | 0.229994E+10 | 0.251644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2653410.53 | 0.332708E+09 |
| August | 0.640118E+10 | 0.242757E+10 | 0.257259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6264233.04 | 0.270704E+09 |
| September | 0.210126E+11 | 0.355678E+10 | 0.244734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30756.27 | 0.234748E+09 |
| October | 0.229168E+11 | 0.378329E+10 | 0.253516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.500144E+09 |
| November | 0.229168E+11 | 0.373654E+10 | 0.246606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516134E+09 |
| December | 0.218255E+11 | 0.367214E+10 | 0.251644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559493E+09 |
| Annual Sum or Average | 0.239231E+12 | 0.420534E+11 | 0.299382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10468545.15 | 0.564223E+10 |
| Minimum of Months | 0.556624E+10 | 0.229994E+10 | 0.229042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234748E+09 |
| Maximum of Months | 0.250994E+11 | 0.400559E+10 | 0.257259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6264233.04 | 0.642363E+09 |
Report: SpaceGainsMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.325382E+10 | 0.825317E+10 | 0.695901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696558E+09 |
| February | 0.294393E+10 | 0.746230E+10 | 0.628953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.629570E+09 |
| March | 0.356371E+10 | 0.873812E+10 | 0.720516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.658117E+09 |
| April | 0.309888E+10 | 0.790872E+10 | 0.669483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 994706.76 | 0.677956E+09 |
| May | 0.340876E+10 | 0.849564E+10 | 0.708208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34322.73 | 0.533646E+09 |
| June | 0.210241E+10 | 0.839367E+10 | 0.693929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 347260.94 | 0.439654E+09 |
| July | 0.723690E+09 | 0.501728E+10 | 0.423831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4152176.51 | 0.362132E+09 |
| August | 0.832243E+09 | 0.529569E+10 | 0.440537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7477321.17 | 0.302497E+09 |
| September | 0.191128E+10 | 0.775905E+10 | 0.658880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34244.29 | 0.268560E+09 |
| October | 0.325382E+10 | 0.825317E+10 | 0.695901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.588242E+09 |
| November | 0.325382E+10 | 0.815120E+10 | 0.681790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.589027E+09 |
| December | 0.309888E+10 | 0.801070E+10 | 0.683594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608508E+09 |
| Annual Sum or Average | 0.314452E+11 | 0.917387E+11 | 0.770152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 13040032.40 | 0.635447E+10 |
| Minimum of Months | 0.723690E+09 | 0.501728E+10 | 0.423831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268560E+09 |
| Maximum of Months | 0.356371E+10 | 0.873812E+10 | 0.720516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7477321.17 | 0.696558E+09 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 472.75 | 12-JAN-24:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 461.29 | 16-FEB-21:03 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 421.02 | 28-MAR-24:00 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 | 01-APR-16:00 | 451.92 | 07-APR-24:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.03 | 06-MAY-14:50 | 401.70 | 17-MAY-20:10 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.62 | 28-JUN-15:00 | 445.70 | 13-JUN-02:55 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.57 | 23-JUL-14:10 | 226.52 | 02-JUL-04:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.68 | 13-AUG-14:52 | 337.58 | 11-AUG-04:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 14-SEP-17:00 | 259.79 | 30-SEP-07:00 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 444.72 | 31-OCT-20:03 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 549.24 | 29-NOV-21:03 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 461.97 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.52 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 82.57 | 549.24 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1384.72 | 12-JAN-24:00 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1242.40 | 16-FEB-04:00 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1247.96 | 28-MAR-24:00 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.20 | 01-APR-16:00 | 1330.20 | 07-APR-24:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.44 | 06-MAY-14:50 | 1134.28 | 17-MAY-20:10 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 | 28-JUN-15:00 | 1315.12 | 13-JUN-02:55 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.40 | 23-JUL-15:50 | 651.03 | 02-JUL-04:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.93 | 13-AUG-14:52 | 918.94 | 11-AUG-04:00 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 14-SEP-17:00 | 756.79 | 30-SEP-07:00 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1223.13 | 31-OCT-20:20 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1468.12 | 29-NOV-21:03 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1237.71 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.03 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 278.40 | 1468.12 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1178.08 | 02-JAN-08:09 | 947.12 | 02-JAN-07:10 | 678.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 79.61 | 28-JAN-08:00 |
| February | 1178.08 | 01-FEB-08:09 | 947.12 | 01-FEB-07:10 | 678.98 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 71.58 | 16-FEB-04:00 |
| March | 1178.08 | 01-MAR-08:09 | 947.12 | 01-MAR-07:10 | 678.98 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 68.26 | 28-MAR-24:00 |
| April | 1178.08 | 03-APR-07:10 | 947.12 | 03-APR-06:10 | 678.98 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.06 | 01-APR-16:00 | 75.41 | 07-APR-24:00 |
| May | 1178.08 | 01-MAY-07:10 | 947.12 | 01-MAY-06:10 | 678.98 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 | 05-MAY-16:00 | 67.03 | 17-MAY-20:10 |
| June | 1178.08 | 01-JUN-07:10 | 947.12 | 01-JUN-06:10 | 678.98 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 | 28-JUN-15:00 | 76.05 | 13-JUN-02:55 |
| July | 186.01 | 03-JUL-07:10 | 526.18 | 03-JUL-07:10 | 357.36 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 23-JUL-13:53 | 37.40 | 02-JUL-04:00 |
| August | 186.01 | 01-AUG-07:10 | 526.18 | 01-AUG-07:10 | 357.36 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.61 | 13-AUG-14:53 | 51.06 | 11-AUG-04:00 |
| September | 1178.08 | 18-SEP-07:10 | 947.12 | 05-SEP-06:10 | 678.98 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 14-SEP-17:00 | 41.77 | 30-SEP-07:00 |
| October | 1178.08 | 02-OCT-07:10 | 947.12 | 02-OCT-06:10 | 678.98 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 69.00 | 31-OCT-20:10 |
| November | 1178.08 | 01-NOV-07:10 | 947.12 | 01-NOV-06:10 | 678.98 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 83.15 | 29-NOV-21:03 |
| December | 1178.08 | 01-DEC-08:09 | 947.12 | 01-DEC-07:10 | 678.98 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 70.08 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.40 | |||||
| Maximum of Months | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 12.77 | 83.15 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 466.95 | 12-JAN-24:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 461.00 | 16-FEB-21:03 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 385.80 | 28-MAR-24:00 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.06 | 01-APR-16:00 | 433.63 | 07-APR-24:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 | 06-MAY-14:50 | 398.67 | 17-MAY-20:10 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.76 | 10-JUN-15:00 | 436.08 | 13-JUN-02:55 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.75 | 23-JUL-14:10 | 218.95 | 02-JUL-04:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.26 | 13-AUG-14:52 | 316.58 | 11-AUG-04:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 23-SEP-14:00 | 245.55 | 30-SEP-07:00 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 443.38 | 31-OCT-20:03 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 548.78 | 29-NOV-21:03 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 461.23 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.95 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 114.75 | 548.78 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1372.20 | 28-JAN-08:00 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1232.53 | 16-FEB-21:03 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1139.84 | 28-MAR-24:00 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 206.10 | 01-APR-16:00 | 1280.01 | 07-APR-24:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.00 | 14-MAY-15:10 | 1122.22 | 17-MAY-20:10 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.45 | 10-JUN-15:00 | 1288.91 | 13-JUN-02:55 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 363.14 | 23-JUL-15:50 | 629.05 | 02-JUL-04:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.59 | 13-AUG-14:52 | 831.56 | 11-AUG-04:00 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.21 | 10-SEP-15:00 | 716.05 | 30-SEP-07:00 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1197.32 | 31-OCT-20:10 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1467.22 | 29-NOV-21:03 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1235.56 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 629.05 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 363.14 | 1467.22 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 472.23 | 12-JAN-24:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 461.31 | 16-FEB-21:03 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 419.93 | 28-MAR-24:00 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.64 | 01-APR-16:00 | 450.88 | 07-APR-24:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.57 | 06-MAY-14:50 | 401.05 | 17-MAY-20:10 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.62 | 28-JUN-15:00 | 444.04 | 13-JUN-02:55 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.82 | 23-JUL-14:10 | 225.37 | 02-JUL-04:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.90 | 13-AUG-14:52 | 337.47 | 11-AUG-04:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 14-SEP-17:00 | 259.88 | 30-SEP-07:00 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 444.57 | 31-OCT-20:03 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 549.12 | 29-NOV-21:03 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 461.86 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.37 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 83.82 | 549.12 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1383.92 | 12-JAN-24:00 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1246.66 | 16-FEB-04:00 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1245.63 | 28-MAR-24:00 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.47 | 01-APR-16:00 | 1331.64 | 07-APR-24:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 | 06-MAY-14:50 | 1135.13 | 17-MAY-20:10 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 | 28-JUN-15:00 | 1313.26 | 13-JUN-02:55 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 283.07 | 23-JUL-15:50 | 649.40 | 02-JUL-04:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.09 | 13-AUG-14:52 | 916.69 | 11-AUG-04:00 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 14-SEP-17:00 | 759.32 | 30-SEP-07:00 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1220.99 | 31-OCT-20:20 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1467.96 | 29-NOV-21:03 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1237.43 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.40 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 283.07 | 1467.96 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1178.08 | 02-JAN-08:09 | 947.12 | 02-JAN-07:10 | 678.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 79.69 | 28-JAN-08:00 |
| February | 1178.08 | 01-FEB-08:09 | 947.12 | 01-FEB-07:10 | 678.98 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 71.62 | 16-FEB-04:00 |
| March | 1178.08 | 01-MAR-08:09 | 947.12 | 01-MAR-07:10 | 678.98 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 68.16 | 28-MAR-24:00 |
| April | 1178.08 | 03-APR-07:10 | 947.12 | 03-APR-06:10 | 678.98 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 01-APR-16:00 | 75.39 | 07-APR-24:00 |
| May | 1178.08 | 01-MAY-07:10 | 947.12 | 01-MAY-06:10 | 678.98 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 | 05-MAY-16:00 | 67.02 | 17-MAY-20:10 |
| June | 1178.08 | 01-JUN-07:10 | 947.12 | 01-JUN-06:10 | 678.98 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 | 28-JUN-15:00 | 75.93 | 13-JUN-02:55 |
| July | 186.01 | 03-JUL-07:10 | 526.18 | 03-JUL-07:10 | 357.36 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.87 | 23-JUL-13:53 | 37.33 | 02-JUL-04:00 |
| August | 186.01 | 01-AUG-07:10 | 526.18 | 01-AUG-07:10 | 357.36 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.70 | 13-AUG-14:53 | 50.99 | 11-AUG-04:00 |
| September | 1178.08 | 18-SEP-07:10 | 947.12 | 05-SEP-06:10 | 678.98 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 14-SEP-17:00 | 41.80 | 30-SEP-07:00 |
| October | 1178.08 | 02-OCT-07:10 | 947.12 | 02-OCT-06:10 | 678.98 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 68.88 | 31-OCT-20:10 |
| November | 1178.08 | 01-NOV-07:10 | 947.12 | 01-NOV-06:10 | 678.98 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 83.15 | 29-NOV-21:03 |
| December | 1178.08 | 01-DEC-08:09 | 947.12 | 01-DEC-07:10 | 678.98 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 70.07 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.33 | |||||
| Maximum of Months | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 12.87 | 83.15 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 466.75 | 12-JAN-24:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 461.01 | 16-FEB-21:03 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 385.67 | 28-MAR-24:00 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.99 | 01-APR-16:00 | 433.67 | 07-APR-24:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.82 | 06-MAY-14:50 | 398.70 | 17-MAY-20:10 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.71 | 10-JUN-15:00 | 436.00 | 13-JUN-02:55 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.79 | 23-JUL-14:10 | 218.94 | 02-JUL-04:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.27 | 13-AUG-14:52 | 316.45 | 11-AUG-04:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 | 23-SEP-14:00 | 245.59 | 30-SEP-07:00 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 443.46 | 31-OCT-20:03 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 548.75 | 29-NOV-21:03 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 461.17 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218.94 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 114.79 | 548.75 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1372.22 | 28-JAN-08:00 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1232.48 | 16-FEB-21:03 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1139.56 | 28-MAR-24:00 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 205.91 | 01-APR-16:00 | 1280.31 | 07-APR-24:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.47 | 14-MAY-15:10 | 1122.63 | 17-MAY-20:10 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.21 | 10-JUN-15:00 | 1288.89 | 13-JUN-02:55 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.94 | 23-JUL-15:50 | 629.13 | 02-JUL-04:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 227.44 | 13-AUG-14:52 | 831.41 | 11-AUG-04:00 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.18 | 10-SEP-15:00 | 716.27 | 30-SEP-07:00 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1197.07 | 31-OCT-20:10 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1467.02 | 29-NOV-21:03 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1235.71 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 629.13 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 362.94 | 1467.02 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 473.23 | 12-JAN-24:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 461.40 | 16-FEB-21:03 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 421.75 | 28-MAR-24:00 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.92 | 01-APR-16:00 | 453.03 | 07-APR-24:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 06-MAY-14:50 | 401.83 | 17-MAY-20:10 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.62 | 28-JUN-15:00 | 445.87 | 13-JUN-02:55 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.47 | 23-JUL-14:10 | 226.78 | 02-JUL-04:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.24 | 13-AUG-14:52 | 338.47 | 11-AUG-04:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.45 | 14-SEP-17:00 | 260.82 | 30-SEP-07:00 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 444.82 | 31-OCT-20:03 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 549.24 | 29-NOV-21:03 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 461.95 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 226.78 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 82.47 | 549.24 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1388.99 | 12-JAN-24:00 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1248.84 | 16-FEB-04:00 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1253.31 | 28-MAR-24:00 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.67 | 01-APR-16:00 | 1340.02 | 07-APR-24:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.36 | 06-MAY-14:50 | 1138.81 | 17-MAY-20:10 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.20 | 28-JUN-15:00 | 1320.39 | 13-JUN-02:55 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 277.42 | 23-JUL-15:50 | 654.25 | 02-JUL-04:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.30 | 13-AUG-14:52 | 921.74 | 11-AUG-04:00 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 14-SEP-17:00 | 763.06 | 30-SEP-07:00 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1228.18 | 31-OCT-20:20 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1468.44 | 29-NOV-21:03 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1237.82 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 654.25 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 277.42 | 1468.44 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1178.08 | 02-JAN-08:09 | 947.12 | 02-JAN-07:10 | 678.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 80.37 | 28-JAN-08:00 |
| February | 1178.08 | 01-FEB-08:09 | 947.12 | 01-FEB-07:10 | 678.98 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 71.97 | 16-FEB-04:00 |
| March | 1178.08 | 01-MAR-08:09 | 947.12 | 01-MAR-07:10 | 678.98 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 69.14 | 28-MAR-24:00 |
| April | 1178.08 | 03-APR-07:10 | 947.12 | 03-APR-06:10 | 678.98 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.34 | 01-APR-16:00 | 76.55 | 07-APR-24:00 |
| May | 1178.08 | 01-MAY-07:10 | 947.12 | 01-MAY-06:10 | 678.98 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 | 05-MAY-16:00 | 67.71 | 17-MAY-20:10 |
| June | 1178.08 | 01-JUN-07:10 | 947.12 | 01-JUN-06:10 | 678.98 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 | 28-JUN-15:00 | 76.83 | 13-JUN-02:55 |
| July | 186.01 | 03-JUL-07:10 | 526.18 | 03-JUL-07:10 | 357.36 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.14 | 23-JUL-13:53 | 37.98 | 02-JUL-04:00 |
| August | 186.01 | 01-AUG-07:10 | 526.18 | 01-AUG-07:10 | 357.36 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.36 | 13-AUG-14:52 | 51.69 | 11-AUG-04:00 |
| September | 1178.08 | 18-SEP-07:10 | 947.12 | 05-SEP-06:10 | 678.98 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 14-SEP-17:00 | 42.34 | 30-SEP-07:00 |
| October | 1178.08 | 02-OCT-07:10 | 947.12 | 02-OCT-06:10 | 678.98 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 69.94 | 31-OCT-20:10 |
| November | 1178.08 | 01-NOV-07:10 | 947.12 | 01-NOV-06:10 | 678.98 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 83.21 | 29-NOV-21:03 |
| December | 1178.08 | 01-DEC-08:09 | 947.12 | 01-DEC-07:10 | 678.98 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 70.11 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.98 | |||||
| Maximum of Months | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 12.14 | 83.21 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 466.94 | 12-JAN-24:00 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 461.01 | 16-FEB-21:03 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 387.88 | 28-MAR-24:00 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.63 | 01-APR-16:00 | 436.79 | 07-APR-24:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.01 | 06-MAY-14:50 | 399.89 | 17-MAY-20:10 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 10-JUN-15:00 | 439.10 | 13-JUN-02:55 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.04 | 23-JUL-14:10 | 221.54 | 02-JUL-04:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.50 | 13-AUG-14:52 | 318.33 | 11-AUG-04:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.22 | 23-SEP-14:00 | 246.76 | 30-SEP-07:00 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 443.53 | 31-OCT-20:03 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 548.79 | 29-NOV-21:03 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 461.15 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.54 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 112.04 | 548.79 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 9663.62 | 02-JAN-08:09 | 4272.19 | 02-JAN-07:10 | 4177.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 906.65 | 28-JAN-08:00 |
| February | 9663.62 | 01-FEB-08:09 | 4272.19 | 01-FEB-07:10 | 4177.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 813.97 | 16-FEB-21:03 |
| March | 9663.62 | 01-MAR-08:09 | 4272.19 | 01-MAR-07:10 | 4177.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 757.11 | 28-MAR-24:00 |
| April | 9663.62 | 03-APR-07:10 | 4272.19 | 03-APR-06:10 | 4177.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 128.23 | 01-APR-16:00 | 852.53 | 07-APR-24:00 |
| May | 9663.62 | 01-MAY-07:10 | 4272.19 | 01-MAY-06:10 | 4177.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.80 | 14-MAY-15:10 | 745.61 | 17-MAY-20:10 |
| June | 9663.62 | 01-JUN-07:10 | 4272.19 | 01-JUN-06:10 | 4177.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 | 10-JUN-15:00 | 856.30 | 13-JUN-02:55 |
| July | 1525.83 | 03-JUL-07:10 | 2373.44 | 03-JUL-07:10 | 2198.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.14 | 23-JUL-15:50 | 420.75 | 02-JUL-04:00 |
| August | 1525.83 | 01-AUG-07:10 | 2373.44 | 01-AUG-07:10 | 2198.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.19 | 13-AUG-14:52 | 554.26 | 11-AUG-04:00 |
| September | 9663.62 | 18-SEP-07:10 | 4272.19 | 05-SEP-06:10 | 4177.31 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 | 10-SEP-15:00 | 475.07 | 30-SEP-07:00 |
| October | 9663.62 | 02-OCT-07:10 | 4272.19 | 02-OCT-06:10 | 4177.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 793.09 | 31-OCT-20:10 |
| November | 9663.62 | 01-NOV-07:10 | 4272.19 | 01-NOV-06:10 | 4177.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 968.84 | 29-NOV-21:03 |
| December | 9663.62 | 01-DEC-08:09 | 4272.19 | 01-DEC-07:10 | 4177.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 815.96 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 1525.83 | 2373.44 | 2198.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.75 | |||||
| Maximum of Months | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 233.14 | 968.84 |
Report: PeakSpaceGainsMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 4969.86 | 02-JAN-08:09 | 2197.13 | 02-JAN-07:10 | 2864.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 495.42 | 28-JAN-08:00 |
| February | 4969.86 | 01-FEB-08:09 | 2197.13 | 01-FEB-07:10 | 2864.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 436.86 | 16-FEB-04:00 |
| March | 4969.86 | 01-MAR-08:09 | 2197.13 | 01-MAR-07:10 | 2864.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 419.92 | 28-MAR-24:00 |
| April | 4969.86 | 03-APR-07:10 | 2197.13 | 03-APR-06:10 | 2864.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.49 | 01-APR-16:00 | 470.85 | 07-APR-24:00 |
| May | 4969.86 | 01-MAY-07:10 | 2197.13 | 01-MAY-06:10 | 2864.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.25 | 06-MAY-14:50 | 419.36 | 17-MAY-20:10 |
| June | 4969.86 | 01-JUN-07:10 | 2197.13 | 01-JUN-06:10 | 2864.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 | 28-JUN-15:00 | 469.03 | 13-JUN-02:55 |
| July | 2615.72 | 03-JUL-07:10 | 1220.63 | 03-JUL-07:10 | 1507.60 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.24 | 23-JUL-15:50 | 231.33 | 02-JUL-04:00 |
| August | 2615.72 | 01-AUG-07:10 | 1220.63 | 01-AUG-07:10 | 1507.60 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.91 | 13-AUG-14:52 | 308.22 | 11-AUG-04:00 |
| September | 4969.86 | 05-SEP-07:10 | 2197.13 | 05-SEP-06:10 | 2864.44 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 | 23-SEP-15:50 | 263.42 | 30-SEP-07:00 |
| October | 4969.86 | 02-OCT-07:10 | 2197.13 | 02-OCT-06:10 | 2864.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 446.62 | 31-OCT-20:10 |
| November | 4969.86 | 01-NOV-07:10 | 2197.13 | 01-NOV-06:10 | 2864.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 520.90 | 29-NOV-21:03 |
| December | 4969.86 | 01-DEC-08:09 | 2197.13 | 01-DEC-07:10 | 2864.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 432.37 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2615.72 | 1220.63 | 1507.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.33 | |||||
| Maximum of Months | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 108.24 | 520.90 |
Report: PeakSpaceGainsMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3350.23 | 02-JAN-08:09 | 2693.36 | 02-JAN-07:10 | 1930.85 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 239.89 | 28-JAN-08:00 |
| February | 3350.23 | 01-FEB-08:09 | 2693.36 | 01-FEB-07:10 | 1930.85 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 215.53 | 16-FEB-04:00 |
| March | 3350.23 | 01-MAR-08:09 | 2693.36 | 01-MAR-07:10 | 1930.85 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 206.40 | 28-MAR-24:00 |
| April | 3350.23 | 03-APR-07:10 | 2693.36 | 03-APR-06:10 | 1930.85 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.85 | 01-APR-16:00 | 234.14 | 07-APR-24:00 |
| May | 3350.23 | 01-MAY-07:10 | 2693.36 | 01-MAY-06:10 | 1930.85 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.92 | 05-MAY-16:00 | 209.61 | 17-MAY-20:10 |
| June | 3350.23 | 01-JUN-07:10 | 2693.36 | 01-JUN-06:10 | 1930.85 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.43 | 28-JUN-15:00 | 241.94 | 13-JUN-02:55 |
| July | 528.98 | 03-JUL-07:10 | 1496.31 | 03-JUL-07:10 | 1016.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.23 | 23-JUL-13:53 | 121.39 | 02-JUL-04:00 |
| August | 528.98 | 01-AUG-07:10 | 1496.31 | 01-AUG-07:10 | 1016.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.56 | 13-AUG-15:00 | 159.57 | 11-AUG-04:00 |
| September | 3350.23 | 18-SEP-07:10 | 2693.36 | 05-SEP-06:10 | 1930.85 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 | 14-SEP-17:00 | 128.62 | 30-SEP-07:00 |
| October | 3350.23 | 02-OCT-07:10 | 2693.36 | 02-OCT-06:10 | 1930.85 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 208.32 | 31-OCT-20:10 |
| November | 3350.23 | 01-NOV-07:10 | 2693.36 | 01-NOV-06:10 | 1930.85 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 249.19 | 29-NOV-21:03 |
| December | 3350.23 | 01-DEC-08:09 | 2693.36 | 01-DEC-07:10 | 1930.85 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 210.00 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 528.98 | 1496.31 | 1016.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.39 | |||||
| Maximum of Months | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 34.85 | 249.19 |
Report: PeakSpaceGainsMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 2098.51 | 02-JAN-08:09 | 2153.53 | 02-JAN-07:10 | 604.72 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 69972.41 | 06-JAN-07:01 |
| February | 2098.51 | 01-FEB-08:09 | 2153.53 | 01-FEB-07:10 | 604.72 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 64206.48 | 09-FEB-07:01 |
| March | 2098.51 | 01-MAR-08:09 | 2153.53 | 01-MAR-07:10 | 604.72 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 66532.85 | 01-MAR-07:01 |
| April | 2098.51 | 03-APR-07:10 | 2153.53 | 03-APR-06:10 | 604.72 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7129.56 | 27-APR-15:00 | 55865.97 | 19-APR-06:01 |
| May | 2098.51 | 01-MAY-07:10 | 2153.53 | 01-MAY-06:10 | 604.72 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1420.44 | 04-MAY-15:00 | 49222.48 | 11-MAY-06:01 |
| June | 2098.51 | 01-JUN-07:10 | 2153.53 | 01-JUN-06:10 | 604.72 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6171.21 | 28-JUN-15:00 | 39599.48 | 01-JUN-06:01 |
| July | 331.34 | 03-JUL-07:10 | 1196.41 | 03-JUL-07:10 | 318.27 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17139.10 | 24-JUL-14:02 | 35200.00 | 03-JUL-06:01 |
| August | 331.34 | 01-AUG-07:10 | 1196.41 | 01-AUG-07:10 | 318.27 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18332.92 | 29-AUG-14:01 | 38805.75 | 01-AUG-06:01 |
| September | 2098.51 | 18-SEP-07:10 | 2153.53 | 05-SEP-06:10 | 604.72 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1417.90 | 12-SEP-14:05 | 42282.06 | 27-SEP-06:01 |
| October | 2098.51 | 02-OCT-07:10 | 2153.53 | 02-OCT-06:10 | 604.72 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 48160.91 | 13-OCT-06:01 |
| November | 2098.51 | 01-NOV-07:10 | 2153.53 | 01-NOV-06:10 | 604.72 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 58123.74 | 24-NOV-07:01 |
| December | 2098.51 | 01-DEC-08:09 | 2153.53 | 01-DEC-07:10 | 604.72 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 67409.68 | 26-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35200.00 | |||||
| Maximum of Months | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 18332.92 | 69972.41 |
Report: PeakSpaceGainsMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 463.87 | 02-JAN-08:09 | 3661.88 | 02-JAN-07:10 | 2227.90 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
| February | 463.87 | 01-FEB-08:09 | 3661.88 | 01-FEB-07:10 | 2227.90 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 463.87 | 01-MAR-08:09 | 3661.88 | 01-MAR-07:10 | 2227.90 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 463.87 | 03-APR-07:10 | 3661.88 | 03-APR-06:10 | 2227.90 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 01-APR-00:05 |
| May | 463.87 | 01-MAY-07:10 | 3661.88 | 01-MAY-06:10 | 2227.90 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 463.87 | 01-JUN-07:10 | 3661.88 | 01-JUN-06:10 | 2227.90 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 01-JUN-00:03 |
| July | 73.24 | 03-JUL-07:10 | 2034.38 | 03-JUL-07:10 | 1172.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 01-JUL-00:03 |
| August | 73.24 | 01-AUG-07:10 | 2034.38 | 01-AUG-07:10 | 1172.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:03 |
| September | 463.87 | 18-SEP-07:10 | 3661.88 | 05-SEP-06:10 | 2227.90 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
| October | 463.87 | 02-OCT-07:10 | 3661.88 | 02-OCT-06:10 | 2227.90 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 463.87 | 01-NOV-07:10 | 3661.88 | 01-NOV-06:10 | 2227.90 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
| December | 463.87 | 01-DEC-08:09 | 3661.88 | 01-DEC-07:10 | 2227.90 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 73.24 | 2034.38 | 1172.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
| Maximum of Months | 463.87 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1165.88 | 02-JAN-08:09 | 1656.56 | 02-JAN-07:10 | 671.91 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 252.92 | 28-JAN-08:00 |
| February | 1165.88 | 01-FEB-08:09 | 1656.56 | 01-FEB-07:10 | 671.91 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 224.47 | 16-FEB-04:00 |
| March | 1165.88 | 01-MAR-08:09 | 1656.56 | 01-MAR-07:10 | 671.91 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 223.18 | 28-MAR-24:00 |
| April | 1165.88 | 03-APR-07:10 | 1656.56 | 03-APR-06:10 | 671.91 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.52 | 01-APR-16:00 | 255.40 | 07-APR-24:00 |
| May | 1165.88 | 01-MAY-07:10 | 1656.56 | 01-MAY-06:10 | 671.91 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 235.36 | 17-MAY-20:10 |
| June | 1165.88 | 01-JUN-07:10 | 1656.56 | 01-JUN-06:10 | 671.91 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 272.58 | 13-JUN-02:55 |
| July | 184.09 | 03-JUL-07:10 | 920.31 | 03-JUL-07:10 | 353.64 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.22 | 23-JUL-13:53 | 138.17 | 02-JUL-04:00 |
| August | 184.09 | 01-AUG-07:10 | 920.31 | 01-AUG-07:10 | 353.64 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.96 | 13-AUG-14:53 | 188.81 | 11-AUG-04:00 |
| September | 1165.88 | 18-SEP-07:10 | 1656.56 | 05-SEP-06:10 | 671.91 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 142.43 | 30-SEP-07:00 |
| October | 1165.88 | 02-OCT-07:10 | 1656.56 | 02-OCT-06:10 | 671.91 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 229.60 | 31-OCT-20:10 |
| November | 1165.88 | 01-NOV-07:10 | 1656.56 | 01-NOV-06:10 | 671.91 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 256.91 | 29-NOV-21:03 |
| December | 1165.88 | 01-DEC-08:09 | 1656.56 | 01-DEC-07:10 | 671.91 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 210.57 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 184.09 | 920.31 | 353.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.17 | |||||
| Maximum of Months | 1165.88 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 34.52 | 272.58 |
Report: PeakSpaceGainsMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 2705.96 | 02-JAN-08:09 | 4699.41 | 02-JAN-07:10 | 4210.73 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1061.82 | 28-JAN-08:00 |
| February | 2705.96 | 01-FEB-08:09 | 4699.41 | 01-FEB-07:10 | 4210.73 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 975.55 | 16-FEB-21:03 |
| March | 2705.96 | 01-MAR-08:09 | 4699.41 | 01-MAR-07:10 | 4210.73 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 984.39 | 28-MAR-24:00 |
| April | 2705.96 | 03-APR-07:10 | 4699.41 | 03-APR-06:10 | 4210.73 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.07 | 01-APR-16:00 | 1082.99 | 07-APR-24:00 |
| May | 2705.96 | 01-MAY-07:10 | 4699.41 | 01-MAY-06:10 | 4210.73 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 | 05-MAY-16:00 | 951.66 | 17-MAY-20:10 |
| June | 2705.96 | 01-JUN-07:10 | 4699.41 | 01-JUN-06:10 | 4210.73 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.01 | 28-JUN-15:00 | 1104.38 | 13-JUN-02:55 |
| July | 1424.19 | 03-JUL-07:10 | 2610.78 | 03-JUL-07:10 | 2216.18 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.85 | 23-JUL-15:50 | 549.29 | 02-JUL-04:00 |
| August | 1424.19 | 01-AUG-07:10 | 2610.78 | 01-AUG-07:10 | 2216.18 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 63.73 | 08-AUG-17:00 | 752.22 | 11-AUG-04:00 |
| September | 2705.96 | 05-SEP-07:10 | 4699.41 | 05-SEP-06:10 | 4210.73 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.15 | 14-SEP-17:00 | 594.24 | 30-SEP-07:00 |
| October | 2705.96 | 02-OCT-07:10 | 4699.41 | 02-OCT-06:10 | 4210.73 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 980.18 | 31-OCT-20:10 |
| November | 2705.96 | 01-NOV-07:10 | 4699.41 | 01-NOV-06:10 | 4210.73 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1160.87 | 29-NOV-21:03 |
| December | 2705.96 | 01-DEC-08:09 | 4699.41 | 01-DEC-07:10 | 4210.73 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 977.47 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 1424.19 | 2610.78 | 2216.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 549.29 | |||||
| Maximum of Months | 2705.96 | 4699.41 | 4210.73 | 0.00 | 0.00 | 0.00 | 0.00 | 87.85 | 1160.87 |
Report: PeakSpaceGainsMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 13145.35 | 02-JAN-16:10 | 4288.47 | 02-JAN-07:10 | 1578.10 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 486.92 | 28-JAN-08:00 |
| February | 13145.35 | 01-FEB-16:10 | 4288.47 | 01-FEB-07:10 | 1578.10 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 434.72 | 16-FEB-04:00 |
| March | 13145.35 | 01-MAR-16:10 | 4288.47 | 01-MAR-07:10 | 1578.10 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 434.11 | 28-MAR-24:00 |
| April | 13145.35 | 03-APR-15:09 | 4288.47 | 03-APR-06:10 | 1578.10 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.63 | 01-APR-16:00 | 470.67 | 07-APR-24:00 |
| May | 13145.35 | 01-MAY-15:09 | 4288.47 | 01-MAY-06:10 | 1578.10 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.75 | 05-MAY-16:00 | 408.80 | 17-MAY-20:10 |
| June | 13145.35 | 01-JUN-15:09 | 4288.47 | 01-JUN-06:10 | 1578.10 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.48 | 28-JUN-16:00 | 472.08 | 13-JUN-02:55 |
| July | 4843.02 | 03-JUL-07:10 | 2382.48 | 03-JUL-07:10 | 830.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.76 | 23-JUL-15:50 | 238.94 | 02-JUL-04:00 |
| August | 4843.02 | 01-AUG-07:10 | 2382.48 | 01-AUG-07:10 | 830.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.65 | 13-AUG-14:53 | 316.97 | 11-AUG-04:00 |
| September | 13145.35 | 05-SEP-15:09 | 4288.47 | 05-SEP-06:10 | 1578.10 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.09 | 14-SEP-17:00 | 252.94 | 30-SEP-07:00 |
| October | 13145.35 | 02-OCT-15:09 | 4288.47 | 02-OCT-06:10 | 1578.10 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 439.41 | 31-OCT-20:03 |
| November | 13145.35 | 01-NOV-15:09 | 4288.47 | 01-NOV-06:10 | 1578.10 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 513.19 | 29-NOV-21:03 |
| December | 13145.35 | 01-DEC-16:10 | 4288.47 | 01-DEC-07:10 | 1578.10 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 426.09 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 4843.02 | 2382.48 | 830.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.94 | |||||
| Maximum of Months | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.76 | 513.19 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3077.20 | 02-JAN-08:09 | 1953.00 | 02-JAN-07:10 | 6399.12 | 02-JAN-10:09 | 14425.49 | 02-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 329.55 | 28-JAN-08:00 |
| February | 3077.20 | 01-FEB-08:09 | 1953.00 | 01-FEB-07:10 | 6399.12 | 01-FEB-10:09 | 14425.49 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 281.90 | 16-FEB-04:00 |
| March | 3077.20 | 01-MAR-08:09 | 1953.00 | 01-MAR-07:10 | 6399.12 | 01-MAR-10:09 | 14425.49 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 258.84 | 28-MAR-24:00 |
| April | 3077.20 | 03-APR-07:10 | 1953.00 | 03-APR-06:10 | 6399.12 | 03-APR-09:09 | 14425.49 | 03-APR-09:09 | 0.00 | 0.00 | 0.00 | 4.48 | 01-APR-16:00 | 256.74 | 07-APR-24:00 |
| May | 3077.20 | 01-MAY-07:10 | 1953.00 | 01-MAY-06:10 | 6399.12 | 01-MAY-09:09 | 14425.49 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 8.41 | 14-MAY-14:40 | 215.39 | 17-MAY-20:20 |
| June | 3077.20 | 01-JUN-07:10 | 1953.00 | 01-JUN-06:10 | 6399.12 | 01-JUN-09:09 | 14425.49 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 3.05 | 28-JUN-16:00 | 253.75 | 13-JUN-02:55 |
| July | 485.87 | 03-JUL-07:10 | 1085.00 | 03-JUL-07:10 | 6399.12 | 03-JUL-09:09 | 14425.49 | 03-JUL-09:09 | 0.00 | 0.00 | 0.00 | 11.30 | 23-JUL-15:58 | 132.79 | 02-JUL-04:10 |
| August | 485.87 | 01-AUG-07:10 | 1085.00 | 01-AUG-07:10 | 6399.12 | 01-AUG-09:09 | 14425.49 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 12.14 | 08-AUG-17:00 | 189.63 | 11-AUG-04:10 |
| September | 3077.20 | 18-SEP-07:10 | 1953.00 | 05-SEP-06:10 | 6399.12 | 01-SEP-09:09 | 14425.49 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.98 | 14-SEP-17:00 | 152.20 | 30-SEP-07:10 |
| October | 3077.20 | 02-OCT-07:10 | 1953.00 | 02-OCT-06:10 | 6399.12 | 02-OCT-09:09 | 14425.49 | 02-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 248.93 | 31-OCT-20:20 |
| November | 3077.20 | 01-NOV-07:10 | 1953.00 | 01-NOV-06:10 | 6399.12 | 01-NOV-09:09 | 14425.49 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 287.75 | 29-NOV-21:10 |
| December | 3077.20 | 01-DEC-08:09 | 1953.00 | 01-DEC-07:10 | 6399.12 | 01-DEC-10:09 | 14425.49 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 236.77 | 22-DEC-21:10 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 485.87 | 1085.00 | 6399.12 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 132.79 | ||||||
| Maximum of Months | 3077.20 | 1953.00 | 6399.12 | 14425.49 | 0.00 | 0.00 | 0.00 | 12.14 | 329.55 |
Report: PeakSpaceGainsMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 38654.47 | 02-JAN-09:09 | 2746.41 | 02-JAN-07:10 | 1999.46 | 02-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 983.16 | 28-JAN-08:00 |
| February | 38654.47 | 01-FEB-09:09 | 2746.41 | 01-FEB-07:10 | 1999.46 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 878.49 | 16-FEB-04:00 |
| March | 38654.47 | 01-MAR-09:09 | 2746.41 | 01-MAR-07:10 | 1999.46 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 824.48 | 28-MAR-24:00 |
| April | 38654.47 | 03-APR-08:09 | 2746.41 | 03-APR-06:10 | 1999.46 | 03-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 100.05 | 01-APR-16:00 | 906.61 | 07-APR-24:00 |
| May | 38654.47 | 01-MAY-08:09 | 2746.41 | 01-MAY-06:10 | 1999.46 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.92 | 14-MAY-14:48 | 753.09 | 17-MAY-20:10 |
| June | 38654.47 | 01-JUN-08:09 | 2746.41 | 01-JUN-06:10 | 1999.46 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 13.72 | 28-JUN-16:00 | 950.71 | 13-JUN-02:55 |
| July | 14241.12 | 03-JUL-16:10 | 1525.78 | 03-JUL-07:10 | 1999.46 | 03-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.92 | 23-JUL-15:34 | 488.27 | 02-JUL-04:00 |
| August | 14241.12 | 01-AUG-16:10 | 1525.78 | 01-AUG-07:10 | 1999.46 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.62 | 08-AUG-17:00 | 637.86 | 11-AUG-04:00 |
| September | 38654.47 | 05-SEP-08:09 | 2746.41 | 05-SEP-06:10 | 1999.46 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 14-SEP-17:00 | 504.95 | 30-SEP-07:00 |
| October | 38654.47 | 02-OCT-08:09 | 2746.41 | 02-OCT-06:10 | 1999.46 | 02-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 831.04 | 31-OCT-20:20 |
| November | 38654.47 | 01-NOV-08:09 | 2746.41 | 01-NOV-06:10 | 1999.46 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 998.98 | 29-NOV-21:03 |
| December | 38654.47 | 01-DEC-09:09 | 2746.41 | 01-DEC-07:10 | 1999.46 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 841.66 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 14241.12 | 1525.78 | 1999.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 488.27 | |||||
| Maximum of Months | 38654.47 | 2746.41 | 1999.46 | 0.00 | 0.00 | 0.00 | 0.00 | 100.05 | 998.98 |
Report: PeakSpaceGainsMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 4896.76 | 02-JAN-08:09 | 5991.24 | 02-JAN-07:10 | 5291.26 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1071.92 | 28-JAN-08:00 |
| February | 4896.76 | 01-FEB-08:09 | 5991.24 | 01-FEB-07:10 | 5291.26 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 947.32 | 16-FEB-04:00 |
| March | 4896.76 | 01-MAR-08:09 | 5991.24 | 01-MAR-07:10 | 5291.26 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 943.57 | 28-MAR-24:00 |
| April | 4896.76 | 03-APR-07:10 | 5991.24 | 03-APR-06:10 | 5291.26 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.15 | 01-APR-16:00 | 1061.25 | 07-APR-24:00 |
| May | 4896.76 | 01-MAY-07:10 | 5991.24 | 01-MAY-06:10 | 5291.26 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.11 | 05-MAY-16:00 | 938.55 | 17-MAY-20:10 |
| June | 4896.76 | 01-JUN-07:10 | 5991.24 | 01-JUN-06:10 | 5291.26 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.24 | 28-JUN-15:00 | 1079.98 | 13-JUN-02:55 |
| July | 773.17 | 03-JUL-07:10 | 3328.47 | 03-JUL-07:10 | 2784.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.57 | 23-JUL-15:50 | 534.95 | 02-JUL-04:00 |
| August | 773.17 | 01-AUG-07:10 | 3328.47 | 01-AUG-07:10 | 2784.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.64 | 13-AUG-15:00 | 719.91 | 11-AUG-04:00 |
| September | 4896.76 | 18-SEP-07:10 | 5991.24 | 05-SEP-06:10 | 5291.26 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 | 14-SEP-17:00 | 586.12 | 30-SEP-07:00 |
| October | 4896.76 | 02-OCT-07:10 | 5991.24 | 02-OCT-06:10 | 5291.26 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 978.96 | 31-OCT-20:10 |
| November | 4896.76 | 01-NOV-07:10 | 5991.24 | 01-NOV-06:10 | 5291.26 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 1109.82 | 29-NOV-21:03 |
| December | 4896.76 | 01-DEC-08:09 | 5991.24 | 01-DEC-07:10 | 5291.26 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 934.68 | 22-DEC-21:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 773.17 | 3328.47 | 2784.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.95 | |||||
| Maximum of Months | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 101.57 | 1109.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2483.29 | 20-JAN-15:30 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.02 |
| February | 3703.09 | 27-FEB-15:30 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 |
| March | 3884.22 | 02-MAR-15:40 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.87 |
| April | 6275.63 | 27-APR-14:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 | 0.00 |
| May | 6104.06 | 15-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 |
| June | 5312.17 | 09-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
| July | 4851.87 | 30-JUL-16:36 | 0.00 | 1322.55 | 1447.29 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 | 0.00 |
| August | 5891.90 | 12-AUG-16:00 | 0.00 | 1322.55 | 1447.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.02 |
| September | 7086.03 | 23-SEP-15:00 | 0.00 | 1587.06 | 2431.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.44 |
| October | 6432.38 | 04-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 |
| November | 3875.17 | 04-NOV-15:32 | 0.00 | 1322.55 | 2026.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 |
| December | 2704.57 | 05-DEC-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.07 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2483.29 | 0.00 | 1322.55 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 7086.03 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 | 37.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 12589.71 | 20-JAN-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.40 |
| February | 17694.66 | 28-FEB-15:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.44 |
| March | 18514.96 | 02-MAR-14:20 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.49 |
| April | 26908.29 | 27-APR-14:20 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 | 0.00 |
| May | 25747.67 | 04-MAY-14:10 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
| June | 23590.88 | 09-JUN-13:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.53 |
| July | 19985.75 | 22-JUL-13:21 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.16 |
| August | 19805.34 | 06-AUG-15:21 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.38 |
| September | 26313.36 | 22-SEP-14:20 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 |
| October | 28199.25 | 04-OCT-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.87 |
| November | 17824.24 | 02-NOV-14:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.23 |
| December | 13404.35 | 05-DEC-14:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.63 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 12589.71 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 28199.25 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 | 77.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1126.67 | 11-JAN-16:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 |
| February | 1927.26 | 28-FEB-15:01 | 8246.53 | 6629.82 | 4752.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
| March | 2017.14 | 02-MAR-15:01 | 9424.61 | 7576.93 | 5431.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.53 |
| April | 3897.31 | 27-APR-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 0.00 |
| May | 4343.11 | 04-MAY-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 0.00 |
| June | 4124.56 | 09-JUN-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
| July | 2833.31 | 24-JUL-14:13 | 558.04 | 1578.53 | 1072.07 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 0.00 |
| August | 3103.36 | 10-AUG-15:40 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
| September | 3982.37 | 22-SEP-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
| October | 3496.83 | 04-OCT-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 |
| November | 2010.36 | 06-NOV-15:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 |
| December | 1210.87 | 05-DEC-15:50 | 3534.23 | 2841.35 | 2036.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1126.67 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4343.11 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 9.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2091.73 | 11-JAN-15:10 | 24297.09 | 10741.51 | 10502.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.42 |
| February | 3317.43 | 28-FEB-15:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 |
| March | 3361.20 | 02-MAR-15:01 | 24297.09 | 10741.51 | 10502.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 |
| April | 4460.64 | 27-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 0.00 |
| May | 4727.63 | 04-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 | 0.00 |
| June | 4485.85 | 09-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
| July | 4271.95 | 15-JUL-17:21 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.84 |
| August | 3902.65 | 13-AUG-20:01 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.68 |
| September | 4395.45 | 22-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 |
| October | 3903.25 | 04-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 |
| November | 3394.38 | 02-NOV-14:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.95 |
| December | 2134.73 | 01-DEC-15:40 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.56 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2091.73 | 0.00 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4727.63 | 24297.09 | 10741.51 | 10502.96 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 51.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 10824.22 | 27-JAN-14:10 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.48 |
| February | 16349.02 | 28-FEB-15:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.64 |
| March | 16603.42 | 17-MAR-14:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.90 |
| April | 18283.58 | 28-APR-14:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.61 |
| May | 19286.98 | 04-MAY-14:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 0.00 |
| June | 19387.99 | 09-JUN-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 |
| July | 17805.82 | 15-JUL-17:21 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.68 |
| August | 17716.78 | 26-AUG-13:11 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.73 |
| September | 18285.89 | 20-SEP-14:01 | 117067.81 | 51754.55 | 50605.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.54 |
| October | 18092.39 | 04-OCT-14:03 | 43900.43 | 19407.96 | 18976.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.47 |
| November | 16758.41 | 02-NOV-14:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.80 |
| December | 10985.47 | 29-DEC-15:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.18 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 10824.22 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 19387.99 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 105.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2436.40 | 20-JAN-15:30 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.71 |
| February | 3648.23 | 27-FEB-15:30 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 |
| March | 3848.76 | 02-MAR-15:40 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.87 |
| April | 6208.28 | 27-APR-14:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 | 0.00 |
| May | 6006.78 | 15-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 |
| June | 5227.86 | 09-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
| July | 4570.26 | 15-JUL-17:21 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.23 |
| August | 5388.64 | 12-AUG-16:00 | 0.00 | 1322.55 | 1447.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.85 |
| September | 6450.24 | 23-SEP-15:00 | 0.00 | 1587.06 | 2431.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.39 |
| October | 6396.96 | 04-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 |
| November | 3692.26 | 02-NOV-14:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 |
| December | 2604.90 | 05-DEC-14:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.33 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2436.40 | 0.00 | 1322.55 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6450.24 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 | 36.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 12316.96 | 20-JAN-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.91 |
| February | 17694.02 | 08-FEB-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.61 |
| March | 18215.34 | 02-MAR-14:20 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.49 |
| April | 26505.37 | 27-APR-14:20 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 | 0.00 |
| May | 25318.26 | 04-MAY-14:10 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
| June | 23175.62 | 09-JUN-13:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.53 |
| July | 19847.56 | 22-JUL-13:21 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.41 |
| August | 19593.33 | 06-AUG-15:21 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.74 |
| September | 26015.24 | 22-SEP-14:20 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 |
| October | 27815.13 | 04-OCT-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.87 |
| November | 17820.76 | 02-NOV-14:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.19 |
| December | 12824.07 | 05-DEC-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.19 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 12316.96 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 27815.13 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 | 112.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1119.56 | 27-JAN-14:10 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.54 |
| February | 1917.64 | 28-FEB-15:01 | 8246.53 | 6629.82 | 4752.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
| March | 2007.63 | 02-MAR-15:01 | 9424.61 | 7576.93 | 5431.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.52 |
| April | 3874.89 | 27-APR-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 0.00 |
| May | 4317.71 | 04-MAY-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 0.00 |
| June | 4098.32 | 09-JUN-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
| July | 2783.87 | 24-JUL-14:13 | 558.04 | 1578.53 | 1072.07 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 0.00 |
| August | 3058.24 | 10-AUG-15:40 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
| September | 3970.52 | 22-SEP-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
| October | 3476.16 | 04-OCT-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 |
| November | 1996.59 | 06-NOV-15:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.04 |
| December | 1174.78 | 01-DEC-15:35 | 2356.15 | 1894.23 | 1357.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.57 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1119.56 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4317.71 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 9.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2091.09 | 11-JAN-15:10 | 24297.09 | 10741.51 | 10502.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.39 |
| February | 3318.50 | 28-FEB-15:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.18 |
| March | 3361.71 | 02-MAR-15:01 | 24297.09 | 10741.51 | 10502.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.99 |
| April | 4464.51 | 27-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 0.00 |
| May | 4732.34 | 04-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 | 0.00 |
| June | 4492.19 | 09-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
| July | 4273.20 | 15-JUL-17:21 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.84 |
| August | 3902.72 | 13-AUG-20:01 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.62 |
| September | 4399.48 | 22-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 |
| October | 3904.03 | 04-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 |
| November | 3394.92 | 02-NOV-14:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.95 |
| December | 2135.23 | 01-DEC-15:40 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.56 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2091.09 | 0.00 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4732.34 | 24297.09 | 10741.51 | 10502.96 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 51.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 10817.53 | 27-JAN-14:10 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.52 |
| February | 16335.71 | 28-FEB-15:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.65 |
| March | 16595.87 | 17-MAR-14:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.98 |
| April | 18261.41 | 28-APR-14:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.61 |
| May | 19311.18 | 04-MAY-14:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 0.00 |
| June | 19417.26 | 09-JUN-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.92 |
| July | 17786.01 | 15-JUL-17:21 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.73 |
| August | 17697.69 | 26-AUG-13:11 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.81 |
| September | 18284.70 | 22-SEP-14:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.79 |
| October | 18070.89 | 04-OCT-14:03 | 43900.43 | 19407.96 | 18976.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.48 |
| November | 16741.79 | 02-NOV-14:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.83 |
| December | 10977.24 | 29-DEC-15:02 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.21 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 10817.53 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 19417.26 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 105.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2459.46 | 20-JAN-15:30 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.90 |
| February | 3686.35 | 27-FEB-15:30 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.02 |
| March | 3883.52 | 02-MAR-15:40 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.87 |
| April | 6240.07 | 27-APR-14:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 | 0.00 |
| May | 6042.97 | 15-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.45 |
| June | 5254.69 | 09-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
| July | 4843.49 | 30-JUL-16:36 | 0.00 | 1322.55 | 1447.29 | 0.00 | 0.00 | 0.00 | 0.00 | 5.91 | 0.00 |
| August | 5685.78 | 12-AUG-16:00 | 0.00 | 1322.55 | 1447.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.95 |
| September | 6736.79 | 23-SEP-15:00 | 0.00 | 1587.06 | 2431.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.41 |
| October | 6419.37 | 04-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 |
| November | 3893.60 | 04-NOV-15:32 | 0.00 | 1322.55 | 2026.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.35 |
| December | 2643.77 | 05-DEC-14:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2459.46 | 0.00 | 1322.55 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6736.79 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 9.10 | 36.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 12461.67 | 20-JAN-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.17 |
| February | 17709.56 | 28-FEB-15:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.45 |
| March | 18552.84 | 02-MAR-14:20 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.49 |
| April | 26767.16 | 27-APR-14:20 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 | 0.00 |
| May | 25526.87 | 04-MAY-14:10 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
| June | 23410.80 | 09-JUN-13:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.53 |
| July | 19996.79 | 22-JUL-13:21 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.41 |
| August | 19738.75 | 06-AUG-15:21 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.71 |
| September | 26221.52 | 22-SEP-14:20 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.26 |
| October | 28021.23 | 04-OCT-13:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.87 |
| November | 17824.10 | 02-NOV-14:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.24 |
| December | 13028.66 | 05-DEC-14:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.32 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 12461.67 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 28021.23 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 | 76.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1146.62 | 27-JAN-14:10 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.58 |
| February | 1965.75 | 28-FEB-15:01 | 8246.53 | 6629.82 | 4752.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 |
| March | 2055.47 | 02-MAR-15:01 | 9424.61 | 7576.93 | 5431.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.59 |
| April | 4095.20 | 27-APR-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.54 | 0.00 |
| May | 4492.52 | 04-MAY-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 0.00 |
| June | 4283.60 | 09-JUN-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
| July | 3137.76 | 24-JUL-14:13 | 558.04 | 1578.53 | 1072.07 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 0.00 |
| August | 3374.91 | 10-AUG-15:40 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 1.62 | 0.00 |
| September | 4136.44 | 22-SEP-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
| October | 3641.65 | 04-OCT-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 |
| November | 2051.81 | 06-NOV-15:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.18 |
| December | 1210.82 | 01-DEC-15:40 | 2356.15 | 1894.23 | 1357.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.65 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1146.62 | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4492.52 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 2.77 | 9.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2095.39 | 11-JAN-15:10 | 24297.09 | 10741.51 | 10502.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.50 |
| February | 3335.38 | 28-FEB-15:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.20 |
| March | 3376.38 | 02-MAR-15:01 | 24297.09 | 10741.51 | 10502.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.14 |
| April | 4551.84 | 27-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 0.00 |
| May | 4825.41 | 04-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 1.14 | 0.00 |
| June | 4600.20 | 09-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.99 |
| July | 4324.04 | 15-JUL-17:21 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.16 |
| August | 3935.93 | 13-AUG-20:01 | 0.00 | 2645.10 | 2894.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.98 |
| September | 4469.15 | 22-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.73 |
| October | 3950.61 | 04-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.52 |
| November | 3412.39 | 02-NOV-14:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.09 |
| December | 2141.69 | 01-DEC-15:40 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.65 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2095.39 | 0.00 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4825.41 | 24297.09 | 10741.51 | 10502.96 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 51.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 7182.84 | 27-JAN-14:10 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.84 |
| February | 10896.76 | 28-FEB-15:01 | 67645.32 | 29905.34 | 29241.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.77 |
| March | 11079.51 | 17-MAR-14:01 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.30 |
| April | 12220.66 | 27-APR-15:00 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 17.98 | 0.00 |
| May | 13182.08 | 04-MAY-14:50 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 1.65 | 0.00 |
| June | 13308.68 | 09-JUN-15:00 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
| July | 11993.17 | 15-JUL-17:21 | 0.00 | 8416.22 | 9210.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 |
| August | 11910.38 | 26-AUG-13:11 | 0.00 | 8416.22 | 9210.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.30 |
| September | 12412.74 | 22-SEP-14:40 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 |
| October | 11962.05 | 04-OCT-14:03 | 28990.85 | 12816.58 | 12531.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 |
| November | 11164.63 | 02-NOV-14:01 | 67645.32 | 29905.34 | 29241.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.90 |
| December | 7283.21 | 29-DEC-15:02 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.34 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 7182.84 | 0.00 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 13308.68 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 17.98 | 69.84 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 4014.34 | 27-JAN-14:10 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.62 |
| February | 5948.73 | 28-FEB-15:01 | 34789.02 | 15379.89 | 20051.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 |
| March | 6047.40 | 17-MAR-14:01 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.69 |
| April | 7421.33 | 27-APR-14:50 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 | 0.00 |
| May | 7834.75 | 04-MAY-14:40 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 | 0.00 |
| June | 8221.47 | 28-JUN-15:00 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 6.87 | 0.00 |
| July | 6548.08 | 15-JUL-17:21 | 0.00 | 4328.34 | 6315.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.69 |
| August | 6558.16 | 26-AUG-13:11 | 0.00 | 4328.34 | 6315.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.81 |
| September | 7715.18 | 14-SEP-14:30 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
| October | 6601.75 | 04-OCT-14:40 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.66 |
| November | 6049.81 | 03-NOV-14:01 | 44728.74 | 19774.15 | 25780.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.93 |
| December | 4050.88 | 29-DEC-15:02 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.62 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4014.34 | 0.00 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 8221.47 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 8.19 | 37.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2348.88 | 27-JAN-14:10 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.59 |
| February | 3992.02 | 28-FEB-15:01 | 23451.62 | 18853.54 | 13515.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 |
| March | 4256.31 | 21-MAR-14:01 | 30152.09 | 24240.27 | 17377.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.65 |
| April | 9565.26 | 27-APR-14:50 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 0.00 |
| May | 12020.66 | 15-MAY-15:00 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.65 |
| June | 15067.10 | 12-JUN-07:02 | 16751.16 | 13466.82 | 9654.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.58 |
| July | 12611.98 | 24-JUL-07:03 | 2115.94 | 5985.25 | 4064.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
| August | 9741.21 | 14-AUG-15:40 | 528.98 | 1496.31 | 1016.24 | 0.00 | 0.00 | 0.00 | 0.00 | 3.46 | 0.00 |
| September | 9228.35 | 22-SEP-14:50 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 |
| October | 7223.42 | 04-OCT-14:40 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 |
| November | 4244.11 | 07-NOV-15:01 | 33502.32 | 26933.63 | 19308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.68 |
| December | 2360.88 | 01-DEC-14:30 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.18 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2348.88 | 528.98 | 1496.31 | 1016.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 15067.10 | 33502.32 | 26933.63 | 19308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 31.68 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1454.39 | 24-JAN-18:07 | 1988.06 | 12921.20 | 1336.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.16 |
| February | 2360.31 | 27-FEB-15:02 | 10492.56 | 10767.67 | 3023.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8470.77 |
| March | 1736.30 | 14-MAR-17:30 | 331.34 | 2153.53 | 222.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.00 |
| April | 11097.17 | 27-APR-15:00 | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 7129.56 | 0.00 |
| May | 6673.38 | 04-MAY-15:00 | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 1420.44 | 0.00 |
| June | 10335.19 | 28-JUN-15:00 | 331.34 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 6171.21 | 0.00 |
| July | 12924.56 | 24-JUL-15:00 | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 11828.56 | 0.00 |
| August | 13124.24 | 29-AUG-15:00 | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 12169.84 | 0.00 |
| September | 9983.97 | 10-SEP-13:54 | 0.00 | 2121.23 | 933.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.92 |
| October | 4566.93 | 04-OCT-14:00 | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.29 |
| November | 2654.83 | 04-NOV-15:32 | 0.00 | 2121.23 | 933.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.93 |
| December | 1505.33 | 05-DEC-18:07 | 994.03 | 6460.60 | 668.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.57 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1454.39 | 0.00 | 1196.41 | 222.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 13124.24 | 10492.56 | 12921.20 | 3023.58 | 0.00 | 0.00 | 0.00 | 0.00 | 12169.84 | 8470.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2299.31 | 27-JAN-14:10 | 463.87 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3468.37 | 28-FEB-15:01 | 3247.06 | 25633.15 | 15595.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 3652.03 | 17-MAR-14:01 | 4638.66 | 36618.79 | 22279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 12572.61 | 29-APR-14:58 | 0.00 | 7213.90 | 6876.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 13304.28 | 14-MAY-18:11 | 0.00 | 7213.90 | 6876.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 12563.09 | 11-JUN-16:07 | 0.00 | 7213.90 | 6876.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 13453.01 | 15-JUL-17:21 | 0.00 | 7213.90 | 4912.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 13425.15 | 13-AUG-20:01 | 0.00 | 7213.90 | 4912.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 13326.90 | 09-SEP-18:12 | 0.00 | 4328.34 | 4126.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4041.94 | 04-OCT-14:03 | 1391.60 | 10985.64 | 6683.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 3623.76 | 07-NOV-15:01 | 4638.66 | 36618.79 | 22279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 2318.20 | 01-DEC-14:40 | 463.87 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2299.31 | 0.00 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 13453.01 | 4638.66 | 36618.79 | 22279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1052.25 | 27-JAN-14:10 | 1165.88 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.93 |
| February | 1904.77 | 28-FEB-15:01 | 8161.15 | 11595.95 | 4703.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 |
| March | 2011.75 | 17-MAR-14:01 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.32 |
| April | 2534.90 | 27-APR-15:02 | 736.34 | 6626.26 | 2687.63 | 0.00 | 0.00 | 0.00 | 0.00 | 2.12 | 0.00 |
| May | 2656.75 | 15-MAY-14:05 | 2331.76 | 3313.13 | 1343.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.09 |
| June | 2884.59 | 28-JUN-15:10 | 368.17 | 3313.13 | 1343.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 |
| July | 8246.00 | 22-JUL-18:47 | 0.00 | 3263.43 | 1481.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.59 |
| August | 5829.99 | 12-AUG-16:35 | 0.00 | 1305.37 | 592.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.76 |
| September | 2557.08 | 14-SEP-14:05 | 368.17 | 3313.13 | 1343.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.72 |
| October | 2419.93 | 04-OCT-14:03 | 3497.63 | 4969.69 | 2015.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 |
| November | 2008.86 | 07-NOV-15:01 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.18 |
| December | 1090.63 | 01-DEC-14:40 | 1165.88 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1052.25 | 0.00 | 1305.37 | 592.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 8246.00 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 2.12 | 36.59 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 4527.76 | 20-JAN-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.62 |
| February | 23201.94 | 03-FEB-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.70 |
| March | 23515.81 | 17-MAR-14:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.06 |
| April | 24042.94 | 28-APR-14:01 | 18941.71 | 32895.88 | 29475.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.23 |
| May | 25309.43 | 14-MAY-14:59 | 0.00 | 9257.84 | 12997.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.88 |
| June | 24060.80 | 01-JUN-14:01 | 21647.67 | 37595.29 | 33685.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.63 |
| July | 26358.58 | 08-JUL-13:19 | 0.00 | 9257.84 | 9283.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.75 |
| August | 27824.39 | 06-AUG-15:21 | 0.00 | 9257.84 | 9283.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.62 |
| September | 24115.15 | 20-SEP-14:01 | 21647.67 | 37595.29 | 33685.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.11 |
| October | 23901.90 | 03-OCT-14:01 | 21647.67 | 37595.29 | 33685.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.43 |
| November | 23429.88 | 07-NOV-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.05 |
| December | 5081.99 | 05-DEC-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.43 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4527.76 | 0.00 | 9257.84 | 9283.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.11 | |
| Maximum of Months | 27824.39 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6981.20 | 11-JAN-17:00 | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.62 |
| February | 9672.73 | 28-FEB-15:01 | 33901.16 | 30019.28 | 11046.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 |
| March | 11422.99 | 14-MAR-15:20 | 26290.70 | 8576.94 | 3156.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.74 |
| April | 25221.61 | 28-APR-05:01 | 0.00 | 6758.63 | 3896.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.93 |
| May | 26013.06 | 16-MAY-05:01 | 0.00 | 6758.63 | 3896.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.20 |
| June | 27040.94 | 12-JUN-05:01 | 0.00 | 8448.28 | 4871.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.97 |
| July | 28280.55 | 24-JUL-05:01 | 0.00 | 8448.28 | 3479.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.04 |
| August | 27321.04 | 14-AUG-05:01 | 0.00 | 8448.28 | 3479.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.05 |
| September | 25627.04 | 11-SEP-05:01 | 0.00 | 8448.28 | 4871.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.27 |
| October | 22070.03 | 10-OCT-06:01 | 0.00 | 42884.68 | 4871.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.90 |
| November | 9914.38 | 02-NOV-14:01 | 33901.16 | 30019.28 | 11046.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.65 |
| December | 7020.13 | 29-DEC-17:00 | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.68 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 6981.20 | 0.00 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.70 | |
| Maximum of Months | 28280.55 | 33901.16 | 42884.68 | 11046.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 67592.71 | 06-JAN-06:11 | 0.00 | 3462.67 | 23036.83 | 12982.94 | 0.00 | 0.00 | 0.00 | 0.00 | 88.04 |
| February | 68579.49 | 08-FEB-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 60.59 |
| March | 65942.39 | 01-MAR-06:01 | 0.00 | 3462.67 | 23036.83 | 12982.94 | 0.00 | 0.00 | 0.00 | 0.00 | 50.34 |
| April | 60749.64 | 19-APR-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 98.51 |
| May | 54014.38 | 11-MAY-05:11 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 93.40 |
| June | 46256.52 | 15-JUN-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 81.86 |
| July | 43851.40 | 03-JUL-05:01 | 0.00 | 3077.93 | 20477.18 | 11540.39 | 0.00 | 0.00 | 0.00 | 0.00 | 52.13 |
| August | 40338.21 | 18-AUG-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 51.68 |
| September | 48512.31 | 27-SEP-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 53931.89 | 13-OCT-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 63.15 |
| November | 61516.54 | 13-NOV-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 83.12 |
| December | 66194.44 | 26-DEC-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 12.34 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 40338.21 | 0.00 | 3077.93 | 20477.18 | 11540.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 68579.49 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 98.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 30857.60 | 05-JAN-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.16 |
| February | 33681.46 | 09-FEB-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.32 |
| March | 31225.46 | 02-MAR-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.65 |
| April | 28515.60 | 19-APR-07:01 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.13 |
| May | 52398.94 | 14-MAY-14:43 | 0.00 | 2164.17 | 3199.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.96 |
| June | 63293.05 | 26-JUN-05:01 | 0.00 | 5410.43 | 7997.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.91 |
| July | 58654.17 | 10-JUL-05:01 | 0.00 | 4328.34 | 6398.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.06 |
| August | 59053.81 | 15-AUG-05:01 | 0.00 | 4328.34 | 6398.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.87 |
| September | 62698.60 | 11-SEP-05:01 | 0.00 | 5410.43 | 7997.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.63 |
| October | 25650.44 | 13-OCT-07:01 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.99 |
| November | 29412.25 | 22-NOV-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.61 |
| December | 32510.92 | 22-DEC-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.32 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 25650.44 | 0.00 | 2164.17 | 3199.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.16 | |
| Maximum of Months | 63293.05 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 4716.99 | 27-JAN-14:10 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.89 |
| February | 6952.00 | 28-FEB-15:04 | 34277.32 | 41938.67 | 37038.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 |
| March | 8507.86 | 10-MAR-14:20 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.95 |
| April | 15253.13 | 27-APR-14:30 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 13.93 | 0.00 |
| May | 23083.61 | 15-MAY-07:01 | 48967.60 | 59912.39 | 52912.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.89 |
| June | 23473.62 | 12-JUN-07:02 | 24483.80 | 29956.19 | 26456.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.74 |
| July | 17135.08 | 24-JUL-07:03 | 3092.69 | 13313.86 | 11139.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.26 |
| August | 12098.69 | 14-AUG-13:30 | 773.17 | 3328.47 | 2784.88 | 0.00 | 0.00 | 0.00 | 0.00 | 11.66 | 0.00 |
| September | 16593.79 | 14-SEP-07:01 | 6958.55 | 53921.15 | 47621.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 12715.60 | 04-OCT-14:07 | 14690.28 | 17973.72 | 15873.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.14 |
| November | 8137.40 | 02-NOV-14:03 | 34277.32 | 41938.67 | 37038.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.78 |
| December | 4753.15 | 29-DEC-15:02 | 48967.60 | 59912.39 | 52912.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.87 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4716.99 | 773.17 | 3328.47 | 2784.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 23473.62 | 48967.60 | 59912.39 | 52912.65 | 0.00 | 0.00 | 0.00 | 0.00 | 13.93 | 84.89 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.256958E+12 | 184643.70 | 02-JAN-11:09 | 0.214147E+12 | 507372.55 | 17-JAN-08:09 |
| February | 0.229901E+12 | 209838.62 | 27-FEB-14:00 | 0.149032E+12 | 500261.26 | 21-FEB-08:09 |
| March | 0.262617E+12 | 202361.32 | 10-MAR-12:00 | 0.100420E+12 | 289977.03 | 24-MAR-07:10 |
| April | 0.247205E+12 | 298705.41 | 27-APR-13:00 | 0.643768E+11 | 249149.59 | 18-APR-07:10 |
| May | 0.276772E+12 | 292706.36 | 04-MAY-13:00 | 0.534781E+11 | 168901.63 | 18-MAY-07:10 |
| June | 0.287119E+12 | 270673.41 | 09-JUN-14:00 | 0.432890E+11 | 76489.58 | 07-JUN-11:09 |
| July | 0.210014E+12 | 209897.78 | 31-JUL-14:09 | 0.358917E+11 | 92306.36 | 13-JUL-07:10 |
| August | 0.230340E+12 | 212941.10 | 29-AUG-14:09 | 0.398037E+11 | 119250.93 | 18-AUG-07:10 |
| September | 0.264409E+12 | 276407.06 | 22-SEP-13:00 | 0.411130E+11 | 104795.72 | 28-SEP-07:10 |
| October | 0.256286E+12 | 254592.03 | 04-OCT-14:00 | 0.583729E+11 | 193681.59 | 30-OCT-07:10 |
| November | 0.247876E+12 | 183299.19 | 06-NOV-11:50 | 0.119253E+12 | 372545.39 | 13-NOV-08:09 |
| December | 0.247813E+12 | 183863.67 | 26-DEC-11:09 | 0.179923E+12 | 542830.59 | 26-DEC-08:09 |
| Annual Sum or Average | 0.301731E+13 | 0.109910E+13 | ||||
| Minimum of Months | 0.210014E+12 | 183299.19 | 0.358917E+11 | 76489.58 | ||
| Maximum of Months | 0.287119E+12 | 298705.41 | 0.214147E+12 | 542830.59 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 0.109593E+12 | 0.100568E+11 | 0.102892E+12 | 0.158194E+10 | 0.287088E+11 | 0.255796E+09 | 0.00 | 25952124.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.990914E+11 | 0.829103E+10 | 0.929862E+11 | 0.142979E+10 | 0.238985E+11 | 0.152203E+09 | 0.00 | 0.581932E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.116033E+12 | 0.809287E+10 | 0.106107E+12 | 0.164017E+10 | 0.261967E+11 | 83100202.20 | 0.00 | 0.642730E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.105019E+12 | 0.674111E+10 | 0.990538E+11 | 0.152152E+10 | 0.251153E+11 | 40961084.41 | 0.00 | 0.602262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.112813E+12 | 0.598738E+10 | 0.104499E+12 | 0.161106E+10 | 0.328955E+11 | 29016140.24 | 0.00 | 0.151161E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.111459E+12 | 0.526903E+10 | 0.102249E+12 | 0.157960E+10 | 0.354196E+11 | 22718754.77 | 0.00 | 0.274203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.666242E+11 | 0.568659E+10 | 0.693246E+11 | 0.102075E+10 | 0.279894E+11 | 19147488.36 | 0.00 | 0.355978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.703211E+11 | 0.652879E+10 | 0.716606E+11 | 0.104481E+10 | 0.305017E+11 | 22961143.55 | 0.00 | 0.465039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.103032E+12 | 0.735683E+10 | 0.977493E+11 | 0.149702E+10 | 0.293945E+11 | 21899248.47 | 0.00 | 0.216501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.109593E+12 | 0.872982E+10 | 0.102892E+12 | 0.158194E+10 | 0.261053E+11 | 38737098.59 | 0.00 | 0.352180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.108239E+12 | 0.943755E+10 | 0.100662E+12 | 0.155064E+10 | 0.239945E+11 | 0.104644E+09 | 0.00 | 0.173635E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.106374E+12 | 0.103151E+11 | 0.101284E+12 | 0.155283E+10 | 0.242084E+11 | 0.189779E+09 | 0.00 | 35689457.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.121819E+13 | 0.924929E+11 | 0.115136E+13 | 0.176121E+11 | 0.334428E+12 | 0.980963E+09 | 0.00 | 0.157293E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.666242E+11 | 0.526903E+10 | 0.693246E+11 | 0.102075E+10 | 0.238985E+11 | 19147488.36 | 0.00 | 25952124.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.116033E+12 | 0.103151E+11 | 0.106107E+12 | 0.164017E+10 | 0.354196E+11 | 0.255796E+09 | 0.00 | 0.465039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.303281E+11 | 0.00 | 0.167467E+12 | 0.00 | 0.163513E+11 | 0.00 | 0.00 |
| February | 0.274200E+11 | 0.00 | 0.106781E+12 | 0.00 | 0.148310E+11 | 0.00 | 0.00 |
| March | 0.319900E+11 | 0.00 | 0.508152E+11 | 0.00 | 0.176149E+11 | 0.00 | 0.00 |
| April | 0.290818E+11 | 0.00 | 0.201848E+11 | 0.00 | 0.151102E+11 | 0.00 | 0.00 |
| May | 0.311591E+11 | 0.00 | 0.623312E+10 | 0.00 | 0.160859E+11 | 0.00 | 0.00 |
| June | 0.307436E+11 | 0.00 | 0.231988E+10 | 0.00 | 0.102256E+11 | 0.00 | 0.00 |
| July | 0.294972E+11 | 0.00 | 0.194162E+10 | 0.00 | 0.445281E+10 | 0.00 | 0.00 |
| August | 0.319900E+11 | 0.00 | 0.290073E+10 | 0.00 | 0.491298E+10 | 0.00 | 0.00 |
| September | 0.290818E+11 | 0.00 | 0.276070E+10 | 0.00 | 0.927051E+10 | 0.00 | 0.00 |
| October | 0.303281E+11 | 0.00 | 0.129256E+11 | 0.00 | 0.151191E+11 | 0.00 | 0.00 |
| November | 0.299127E+11 | 0.00 | 0.737959E+11 | 0.00 | 0.155442E+11 | 0.00 | 0.00 |
| December | 0.294972E+11 | 0.00 | 0.135087E+12 | 0.00 | 0.153390E+11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.361030E+12 | 0.00 | 0.583213E+12 | 0.00 | 0.154857E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.274200E+11 | 0.00 | 0.194162E+10 | 0.00 | 0.445281E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.319900E+11 | 0.00 | 0.167467E+12 | 0.00 | 0.176149E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 79557.27 | 02-JAN-07:10 | 5897.73 | 01-JAN-00:10 | 76813.98 | 02-JAN-10:09 | 1336.02 | 02-JAN-10:09 | 26469.18 | 02-JAN-07:30 | 780.81 | 02-JAN-07:30 | 0.00 | 01-JAN-00:10 |
| February | 79557.27 | 01-FEB-07:10 | 5897.73 | 01-FEB-00:10 | 76813.98 | 01-FEB-10:09 | 1336.02 | 01-FEB-10:09 | 26346.70 | 21-FEB-07:19 | 774.18 | 21-FEB-07:19 | 0.00 | 01-FEB-00:10 |
| March | 79557.27 | 01-MAR-07:10 | 5897.73 | 01-MAR-00:10 | 76813.98 | 01-MAR-10:09 | 1336.02 | 01-MAR-10:09 | 27086.80 | 14-MAR-14:30 | 510.06 | 06-MAR-07:19 | 0.00 | 01-MAR-00:10 |
| April | 79557.27 | 03-APR-06:10 | 5897.73 | 01-APR-00:10 | 76813.98 | 03-APR-09:09 | 1336.02 | 03-APR-09:09 | 50094.88 | 27-APR-13:00 | 237.10 | 19-APR-06:19 | 0.00 | 01-APR-00:10 |
| May | 79557.27 | 01-MAY-06:10 | 5897.73 | 01-MAY-00:10 | 76813.98 | 01-MAY-09:09 | 1336.02 | 01-MAY-09:09 | 53859.25 | 04-MAY-14:30 | 144.50 | 18-MAY-07:10 | 0.00 | 01-MAY-00:10 |
| June | 79557.27 | 01-JUN-06:10 | 5897.73 | 01-JUN-00:10 | 76813.98 | 01-JUN-09:09 | 1336.02 | 01-JUN-09:09 | 49087.24 | 09-JUN-14:30 | 105.53 | 14-JUN-07:10 | 0.00 | 01-JUN-00:10 |
| July | 44198.48 | 03-JUL-07:10 | 5897.73 | 01-JUL-00:10 | 45977.32 | 03-JUL-09:09 | 606.14 | 03-JUL-09:09 | 32459.42 | 24-JUL-13:39 | 177.15 | 13-JUL-07:10 | 0.00 | 01-JUL-00:10 |
| August | 44198.48 | 01-AUG-07:10 | 5897.73 | 01-AUG-00:10 | 45977.32 | 01-AUG-09:09 | 606.14 | 01-AUG-09:09 | 32807.62 | 10-AUG-13:20 | 223.43 | 18-AUG-07:10 | 0.00 | 01-AUG-00:10 |
| September | 79557.27 | 05-SEP-06:10 | 5897.73 | 01-SEP-00:10 | 76813.98 | 05-SEP-09:09 | 1336.02 | 05-SEP-09:09 | 48933.23 | 22-SEP-14:30 | 122.84 | 28-SEP-07:10 | 0.00 | 01-SEP-00:10 |
| October | 79557.27 | 02-OCT-06:10 | 5897.73 | 01-OCT-00:10 | 76813.98 | 02-OCT-09:09 | 1336.02 | 02-OCT-09:09 | 46833.66 | 04-OCT-14:30 | 201.98 | 30-OCT-06:19 | 0.00 | 01-OCT-00:10 |
| November | 79557.27 | 01-NOV-06:10 | 5897.73 | 01-NOV-00:10 | 76813.98 | 01-NOV-09:09 | 1336.02 | 01-NOV-09:09 | 24206.76 | 24-NOV-07:10 | 556.89 | 24-NOV-07:10 | 0.00 | 01-NOV-00:10 |
| December | 79557.27 | 01-DEC-07:10 | 5897.73 | 01-DEC-00:10 | 76813.98 | 01-DEC-10:09 | 1336.02 | 01-DEC-10:09 | 26426.31 | 26-DEC-07:10 | 778.15 | 26-DEC-07:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | ||||||||||||||
| Minimum of Months | 44198.48 | 5897.73 | 45977.32 | 606.14 | 24206.76 | 105.53 | 0.00 | |||||||
| Maximum of Months | 79557.27 | 5897.73 | 76813.98 | 1336.02 | 53859.25 | 780.81 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 1359.45 | 27-JAN-06:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 30715.00 | 27-FEB-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 20592.34 | 10-MAR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 96257.61 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 86130.24 | 04-MAY-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 78444.80 | 28-JUN-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 96366.42 | 31-JUL-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 101509.42 | 29-AUG-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 80502.50 | 14-SEP-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 55918.26 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 35190.44 | 04-NOV-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 924.92 | 27-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 924.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 101509.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 184643.70 | 02-JAN-11:09 | 79557.27 | 76813.98 | 0.00 | 1336.02 | 23614.33 | 454.80 | 0.00 | 0.00 | 0.00 |
| February | 209838.62 | 27-FEB-14:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 24150.22 | 13.47 | 0.00 | 30715.00 | 0.00 |
| March | 202361.32 | 10-MAR-12:00 | 79557.27 | 76813.98 | 0.00 | 1336.02 | 22685.44 | 13.47 | 0.00 | 20592.34 | 0.00 |
| April | 298705.41 | 27-APR-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 50094.88 | 13.47 | 0.00 | 93623.04 | 0.00 |
| May | 292706.36 | 04-MAY-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 51594.82 | 13.47 | 0.00 | 86130.24 | 0.00 |
| June | 270673.41 | 09-JUN-14:00 | 79557.27 | 70814.97 | 0.00 | 1156.20 | 49042.69 | 13.47 | 0.00 | 68722.42 | 0.00 |
| July | 209897.78 | 31-JUL-14:09 | 44198.48 | 39978.30 | 0.00 | 518.12 | 27502.86 | 13.47 | 0.00 | 96366.42 | 0.00 |
| August | 212941.10 | 29-AUG-14:09 | 44198.48 | 39978.30 | 0.00 | 518.12 | 25401.03 | 13.47 | 0.00 | 101509.42 | 0.00 |
| September | 276407.06 | 22-SEP-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 47483.79 | 13.47 | 0.00 | 73935.51 | 0.00 |
| October | 254592.03 | 04-OCT-14:00 | 79557.27 | 70814.97 | 0.00 | 1156.20 | 45771.09 | 13.47 | 0.00 | 55918.26 | 0.00 |
| November | 183299.19 | 06-NOV-11:50 | 79557.27 | 76813.98 | 0.00 | 1336.02 | 22642.62 | 16.57 | 0.00 | 696.70 | 0.00 |
| December | 183863.67 | 26-DEC-11:09 | 79557.27 | 76813.98 | 0.00 | 1336.02 | 22785.50 | 463.44 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | ||||||||||
| Minimum of Months | 183299.19 | 44198.48 | 39978.30 | 0.00 | 518.12 | 22642.62 | 13.47 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 298705.41 | 79557.27 | 76813.98 | 0.00 | 1336.02 | 51594.82 | 463.44 | 0.00 | 101509.42 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
| January | 48084.96 | 02-JAN-10:09 | 0.00 | 459122.06 | 17-JAN-08:09 | 0.00 | 29236.59 | 31-JAN-13:00 | 0.00 |
| February | 48084.96 | 01-FEB-10:09 | 0.00 | 452062.91 | 21-FEB-08:09 | 0.00 | 29275.26 | 15-FEB-13:39 | 0.00 |
| March | 48084.96 | 01-MAR-10:09 | 0.00 | 242472.02 | 24-MAR-07:10 | 0.00 | 29073.89 | 01-MAR-13:39 | 0.00 |
| April | 48084.96 | 03-APR-09:09 | 0.00 | 201206.23 | 18-APR-07:10 | 0.00 | 28386.95 | 04-APR-12:39 | 0.00 |
| May | 48084.96 | 01-MAY-09:09 | 0.00 | 121473.63 | 18-MAY-07:10 | 0.00 | 28100.08 | 01-MAY-12:20 | 0.00 |
| June | 48084.96 | 01-JUN-09:09 | 0.00 | 25334.35 | 14-JUN-07:10 | 0.00 | 26855.26 | 01-JUN-12:20 | 0.00 |
| July | 48084.96 | 03-JUL-09:09 | 0.00 | 52063.11 | 13-JUL-07:10 | 0.00 | 8267.27 | 03-JUL-18:30 | 0.00 |
| August | 48084.96 | 01-AUG-09:09 | 0.00 | 79661.51 | 18-AUG-07:10 | 0.00 | 8259.48 | 31-AUG-18:00 | 0.00 |
| September | 48084.96 | 01-SEP-09:09 | 0.00 | 57826.20 | 27-SEP-07:10 | 0.00 | 26601.44 | 26-SEP-12:39 | 0.00 |
| October | 48084.96 | 02-OCT-09:09 | 0.00 | 146283.88 | 30-OCT-07:10 | 0.00 | 27019.07 | 31-OCT-12:39 | 0.00 |
| November | 48084.96 | 01-NOV-09:09 | 0.00 | 325118.87 | 13-NOV-08:09 | 0.00 | 28189.51 | 30-NOV-13:20 | 0.00 |
| December | 48084.96 | 01-DEC-10:09 | 0.00 | 494623.63 | 26-DEC-08:09 | 0.00 | 28473.73 | 29-DEC-13:39 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 48084.96 | 0.00 | 25334.35 | 0.00 | 8259.48 | 0.00 | |||
| Maximum of Months | 48084.96 | 0.00 | 494623.63 | 0.00 | 29275.26 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 3.00 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
| February | 1.50 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 |
| March | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.27 | 0.00 | 27.27 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.17 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
| December | 1.33 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
| Annual Sum or Average | 6.17 | 18.18 | 0.00 | 18.18 | 0.33 | 18.64 | 0.00 | 18.64 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3.00 | 19.31 | 0.00 | 19.31 | 0.33 | 27.27 | 0.00 | 27.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 1.67 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 |
| February | 0.50 | 17.74 | 0.00 | 17.74 | 0.00 | 17.74 | 0.00 | 17.74 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.34 | 0.00 | 27.34 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.83 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 |
| Annual Sum or Average | 3.00 | 18.13 | 0.00 | 18.13 | 0.33 | 19.05 | 0.00 | 19.05 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1.67 | 18.29 | 0.00 | 18.29 | 0.33 | 27.34 | 0.00 | 27.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 11.00 | 19.04 | 5.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
| February | 3.50 | 18.99 | 1.50 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 4.00 | 19.01 | 1.50 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
| Annual Sum or Average | 18.50 | 19.02 | 8.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 11.00 | 19.04 | 5.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 4.67 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 | 0.00 | 17.10 |
| February | 4.83 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 |
| March | 0.33 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.50 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
| December | 3.33 | 17.48 | 0.00 | 17.48 | 0.00 | 17.48 | 0.00 | 17.48 |
| Annual Sum or Average | 13.67 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 4.83 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.83 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
| February | 1.00 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1.33 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
| Annual Sum or Average | 5.17 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2.83 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 3.00 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 |
| February | 1.50 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
| March | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.17 | 16.80 | 0.00 | 16.80 | 0.00 | 16.80 | 0.00 | 16.80 |
| December | 1.33 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 | 0.00 | 18.36 |
| Annual Sum or Average | 6.17 | 18.17 | 0.00 | 18.17 | 0.00 | 18.17 | 0.00 | 18.17 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 1.67 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
| February | 0.50 | 17.73 | 0.00 | 17.73 | 0.00 | 17.73 | 0.00 | 17.73 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.83 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
| Annual Sum or Average | 3.00 | 18.12 | 0.00 | 18.12 | 0.00 | 18.12 | 0.00 | 18.12 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1.67 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 11.33 | 19.04 | 5.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
| February | 3.50 | 18.98 | 1.50 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 4.00 | 19.00 | 1.50 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
| Annual Sum or Average | 18.83 | 19.02 | 8.33 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 11.33 | 19.04 | 5.33 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 5.00 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 | 0.00 | 17.11 |
| February | 4.83 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 | 0.00 | 16.31 |
| March | 0.33 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.50 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 | 0.00 | 18.46 |
| December | 3.33 | 17.47 | 0.00 | 17.47 | 0.00 | 17.47 | 0.00 | 17.47 |
| Annual Sum or Average | 14.00 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 5.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 | 0.00 | 19.21 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.83 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 |
| February | 1.00 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1.33 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 |
| Annual Sum or Average | 5.17 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2.83 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 3.00 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
| February | 1.50 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 |
| March | 0.17 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.00 | 27.26 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.17 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
| December | 1.17 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 |
| Annual Sum or Average | 6.00 | 18.14 | 0.00 | 18.14 | 0.33 | 18.62 | 0.00 | 18.62 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3.00 | 19.32 | 0.00 | 19.32 | 0.33 | 27.26 | 0.00 | 27.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 1.67 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 |
| February | 0.50 | 17.73 | 0.00 | 17.73 | 0.00 | 17.73 | 0.00 | 17.73 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.28 | 0.00 | 27.28 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.83 | 18.06 | 0.00 | 18.06 | 0.00 | 18.06 | 0.00 | 18.06 |
| Annual Sum or Average | 3.00 | 18.13 | 0.00 | 18.13 | 0.17 | 18.61 | 0.00 | 18.61 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1.67 | 18.28 | 0.00 | 18.28 | 0.17 | 27.28 | 0.00 | 27.28 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 10.33 | 19.02 | 4.83 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
| February | 3.33 | 18.99 | 1.50 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 3.67 | 19.01 | 1.50 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
| Annual Sum or Average | 17.33 | 19.01 | 7.83 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 10.33 | 19.02 | 4.83 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 5.00 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
| February | 4.50 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 | 0.00 | 16.41 |
| March | 0.33 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.50 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
| December | 3.33 | 17.48 | 0.00 | 17.48 | 0.00 | 17.48 | 0.00 | 17.48 |
| Annual Sum or Average | 13.67 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 | 0.00 | 17.02 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 5.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.83 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 | 0.00 | 18.34 |
| February | 1.17 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1.33 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 | 0.00 | 18.22 |
| Annual Sum or Average | 5.33 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 | 0.00 | 18.32 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2.83 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 1.83 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 | 0.00 | 18.04 |
| February | 0.83 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.67 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
| Annual Sum or Average | 3.33 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1.83 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 9.67 | 19.20 | 4.50 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
| February | 2.17 | 18.86 | 0.67 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 2.17 | 19.22 | 0.67 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
| Annual Sum or Average | 14.00 | 19.15 | 5.83 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 9.67 | 19.22 | 4.50 | 19.45 | 0.00 | 19.45 | 0.00 | 19.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 184.67 | 17.15 | 162.67 | 17.57 | 0.00 | 17.57 | 0.00 | 17.57 |
| February | 119.83 | 16.77 | 101.00 | 17.27 | 0.00 | 17.27 | 0.00 | 17.27 |
| March | 80.83 | 16.49 | 58.33 | 17.21 | 0.00 | 17.21 | 0.00 | 17.21 |
| April | 49.17 | 16.41 | 29.83 | 17.15 | 0.83 | 17.23 | 0.83 | 17.31 |
| May | 38.50 | 17.23 | 19.00 | 17.81 | 0.00 | 17.81 | 0.00 | 17.81 |
| June | 26.83 | 17.93 | 8.67 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 |
| July | 16.50 | 18.32 | 1.83 | 18.51 | 2.17 | 19.31 | 2.17 | 19.96 |
| August | 12.83 | 18.08 | 1.33 | 18.25 | 9.00 | 21.20 | 9.00 | 22.49 |
| September | 24.50 | 17.59 | 7.50 | 17.93 | 0.00 | 17.93 | 0.00 | 17.93 |
| October | 43.00 | 16.73 | 24.00 | 17.33 | 0.00 | 17.33 | 0.00 | 17.33 |
| November | 99.67 | 16.98 | 79.83 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
| December | 154.33 | 16.90 | 133.83 | 17.36 | 0.00 | 17.36 | 0.00 | 17.36 |
| Annual Sum or Average | 850.67 | 16.98 | 627.83 | 17.45 | 12.00 | 17.52 | 12.00 | 17.59 |
| Minimum of Months | 12.83 | 16.41 | 1.33 | 17.15 | 0.00 | 17.21 | 0.00 | 17.21 |
| Maximum of Months | 184.67 | 18.32 | 162.67 | 18.51 | 9.00 | 21.20 | 9.00 | 22.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.00 | 27.29 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.26 | 0.00 | 27.26 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.27 | 0.00 | 27.27 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.00 | 27.30 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 1.17 | 27.28 | 0.00 | 27.28 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.30 | 0.00 | 27.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 5.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
| February | 1.00 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 2.17 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 | 0.00 | 18.76 |
| Annual Sum or Average | 8.17 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 | 0.00 | 18.80 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 5.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 | 0.00 | 18.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 4.67 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
| February | 1.33 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.44 | 0.00 | 26.44 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.34 | 0.00 | 27.34 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1.83 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 | 0.00 | 19.68 |
| Annual Sum or Average | 7.83 | 19.41 | 0.00 | 19.41 | 0.67 | 19.98 | 0.00 | 19.98 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 4.67 | 19.68 | 0.00 | 19.68 | 0.50 | 27.34 | 0.00 | 27.34 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 26.55 | 0.00 | 26.55 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 | 26.96 | 0.00 | 26.96 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 39.33 | 27.24 | 0.00 | 27.24 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 63.50 | 27.45 | 0.00 | 27.45 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 89.50 | 27.53 | 0.00 | 27.53 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 95.50 | 27.63 | 0.00 | 27.63 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 109.33 | 27.64 | 0.00 | 27.64 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 95.50 | 27.60 | 0.00 | 27.60 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 99.33 | 27.57 | 0.00 | 27.57 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 66.00 | 27.40 | 0.00 | 27.40 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 33.50 | 27.20 | 0.00 | 27.20 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 26.79 | 0.00 | 26.79 |
| Annual Sum or Average | 0.00 | 0.00 | 729.00 | 27.49 | 0.00 | 27.49 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 26.55 | 0.00 | 26.55 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 109.33 | 27.64 | 0.00 | 27.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.67 | 20.08 | 0.00 | 20.08 | 0.00 | 20.08 | 0.00 | 20.08 |
| February | 1.50 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 |
| March | 0.17 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 | 0.00 | 20.41 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.69 | 0.00 | 24.69 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.66 | 0.00 | 24.66 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.67 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
| December | 1.17 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 | 0.00 | 20.19 |
| Annual Sum or Average | 6.17 | 20.17 | 0.00 | 20.17 | 0.50 | 20.50 | 0.00 | 20.50 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2.67 | 20.41 | 0.00 | 20.41 | 0.33 | 24.69 | 0.00 | 24.69 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.17 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 |
| February | 0.67 | 17.80 | 0.00 | 17.80 | 0.00 | 17.80 | 0.00 | 17.80 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.50 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 | 0.00 | 17.29 |
| Annual Sum or Average | 3.33 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2.17 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 | 0.00 | 17.89 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.18 | 180.00 | 21.11 | 180.00 | 21.08 |
| February | 244.50 | 21.57 | 97.83 | 21.41 | 97.83 | 21.32 |
| March | 284.00 | 21.99 | 26.00 | 21.91 | 26.00 | 21.84 |
| April | 196.17 | 22.45 | 30.00 | 22.60 | 4.83 | 22.56 |
| May | 135.33 | 22.74 | 69.50 | 23.17 | 0.00 | 23.17 |
| June | 119.83 | 22.77 | 87.50 | 23.29 | 0.00 | 23.29 |
| July | 143.83 | 22.12 | 69.50 | 22.67 | 0.00 | 22.67 |
| August | 168.17 | 22.04 | 106.00 | 22.76 | 0.00 | 22.76 |
| September | 105.17 | 22.62 | 116.17 | 23.33 | 0.00 | 23.33 |
| October | 197.00 | 22.38 | 35.67 | 22.63 | 0.33 | 22.63 |
| November | 271.00 | 21.74 | 57.33 | 21.61 | 57.33 | 21.52 |
| December | 260.00 | 21.35 | 138.00 | 21.23 | 138.00 | 21.17 |
| Annual Sum or Average | 2398.00 | 21.95 | 1013.50 | 22.11 | 504.33 | 21.97 |
| Minimum of Months | 105.17 | 21.18 | 26.00 | 21.11 | 0.00 | 21.08 |
| Maximum of Months | 284.00 | 22.77 | 180.00 | 23.33 | 180.00 | 23.33 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.43 | 112.83 | 21.31 | 112.83 | 21.25 |
| February | 240.33 | 21.86 | 48.33 | 21.72 | 48.33 | 21.62 |
| March | 266.33 | 22.33 | 2.17 | 22.32 | 2.17 | 22.31 |
| April | 161.67 | 22.61 | 30.33 | 22.83 | 0.00 | 22.83 |
| May | 110.67 | 22.85 | 96.83 | 23.38 | 0.00 | 23.38 |
| June | 111.33 | 22.87 | 101.17 | 23.40 | 0.00 | 23.40 |
| July | 190.83 | 22.14 | 27.17 | 22.32 | 0.00 | 22.32 |
| August | 182.83 | 22.02 | 83.50 | 22.55 | 0.00 | 22.55 |
| September | 82.67 | 22.62 | 129.33 | 23.44 | 0.00 | 23.44 |
| October | 169.67 | 22.66 | 48.83 | 22.96 | 0.00 | 22.96 |
| November | 256.33 | 22.06 | 8.33 | 22.03 | 8.33 | 22.00 |
| December | 260.00 | 21.66 | 69.17 | 21.53 | 69.17 | 21.44 |
| Annual Sum or Average | 2305.67 | 22.13 | 758.00 | 22.35 | 240.83 | 22.25 |
| Minimum of Months | 82.67 | 21.43 | 2.17 | 21.31 | 0.00 | 21.25 |
| Maximum of Months | 273.00 | 22.87 | 129.33 | 23.44 | 112.83 | 23.44 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.00 | 164.00 | 20.98 | 164.00 | 20.97 |
| February | 247.00 | 21.24 | 97.17 | 21.16 | 97.17 | 21.12 |
| March | 299.00 | 21.87 | 13.17 | 21.84 | 13.17 | 21.80 |
| April | 231.50 | 22.76 | 7.50 | 22.80 | 0.33 | 22.80 |
| May | 143.17 | 23.42 | 20.83 | 23.50 | 0.00 | 23.50 |
| June | 94.67 | 23.51 | 19.00 | 23.59 | 0.00 | 23.59 |
| July | 194.33 | 22.99 | 22.83 | 23.09 | 0.00 | 23.09 |
| August | 195.17 | 22.80 | 45.67 | 23.02 | 0.00 | 23.02 |
| September | 115.00 | 23.25 | 48.33 | 23.47 | 0.00 | 23.47 |
| October | 238.83 | 22.76 | 0.00 | 22.76 | 0.00 | 22.76 |
| November | 273.00 | 21.63 | 36.17 | 21.56 | 36.17 | 21.50 |
| December | 260.00 | 21.05 | 130.33 | 21.03 | 130.33 | 21.02 |
| Annual Sum or Average | 2564.67 | 22.14 | 605.00 | 22.07 | 441.17 | 21.94 |
| Minimum of Months | 94.67 | 21.00 | 0.00 | 20.98 | 0.00 | 20.97 |
| Maximum of Months | 299.00 | 23.51 | 164.00 | 23.59 | 164.00 | 23.59 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.06 | 223.50 | 21.03 | 223.50 | 21.02 |
| February | 247.00 | 21.22 | 147.17 | 21.14 | 147.17 | 21.10 |
| March | 299.00 | 21.53 | 70.83 | 21.43 | 70.83 | 21.37 |
| April | 240.17 | 22.15 | 20.67 | 22.18 | 10.50 | 22.13 |
| May | 183.50 | 22.72 | 37.67 | 22.93 | 0.00 | 22.93 |
| June | 162.50 | 22.74 | 42.33 | 23.00 | 0.00 | 23.00 |
| July | 220.50 | 22.00 | 15.83 | 22.11 | 0.00 | 22.11 |
| August | 241.00 | 21.82 | 27.33 | 22.01 | 0.00 | 22.01 |
| September | 177.00 | 22.49 | 37.00 | 22.74 | 0.00 | 22.74 |
| October | 254.50 | 22.16 | 2.67 | 22.15 | 2.67 | 22.14 |
| November | 273.00 | 21.47 | 90.33 | 21.35 | 90.33 | 21.28 |
| December | 260.00 | 21.09 | 193.17 | 21.05 | 193.17 | 21.04 |
| Annual Sum or Average | 2831.17 | 21.79 | 908.50 | 21.73 | 738.17 | 21.61 |
| Minimum of Months | 162.50 | 21.06 | 2.67 | 21.03 | 0.00 | 21.02 |
| Maximum of Months | 299.00 | 22.74 | 223.50 | 23.00 | 223.50 | 23.00 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.23 | 153.17 | 21.15 | 153.17 | 21.11 |
| February | 247.00 | 21.44 | 95.83 | 21.32 | 95.83 | 21.26 |
| March | 299.00 | 21.90 | 16.17 | 21.86 | 16.17 | 21.82 |
| April | 239.00 | 22.46 | 8.67 | 22.51 | 0.33 | 22.51 |
| May | 158.67 | 22.78 | 35.33 | 23.00 | 0.00 | 23.00 |
| June | 166.83 | 22.79 | 16.00 | 22.89 | 0.00 | 22.89 |
| July | 259.00 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
| August | 297.67 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
| September | 178.83 | 22.49 | 33.00 | 22.70 | 0.00 | 22.70 |
| October | 247.33 | 22.44 | 0.17 | 22.44 | 0.17 | 22.44 |
| November | 273.00 | 21.82 | 36.33 | 21.73 | 36.33 | 21.65 |
| December | 260.00 | 21.31 | 116.00 | 21.22 | 116.00 | 21.17 |
| Annual Sum or Average | 2899.33 | 21.93 | 510.67 | 21.87 | 418.00 | 21.78 |
| Minimum of Months | 158.67 | 21.23 | 0.00 | 21.15 | 0.00 | 21.11 |
| Maximum of Months | 299.00 | 22.79 | 153.17 | 23.00 | 153.17 | 23.00 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.16 | 185.67 | 21.10 | 185.67 | 21.07 |
| February | 244.67 | 21.56 | 100.17 | 21.40 | 100.17 | 21.31 |
| March | 285.33 | 21.97 | 27.00 | 21.89 | 27.00 | 21.83 |
| April | 199.50 | 22.44 | 29.33 | 22.57 | 5.00 | 22.54 |
| May | 139.50 | 22.73 | 65.67 | 23.13 | 0.00 | 23.13 |
| June | 124.83 | 22.75 | 81.83 | 23.24 | 0.00 | 23.24 |
| July | 152.00 | 22.10 | 62.17 | 22.60 | 0.00 | 22.60 |
| August | 173.67 | 22.02 | 104.17 | 22.73 | 0.00 | 22.73 |
| September | 107.17 | 22.61 | 114.00 | 23.32 | 0.00 | 23.32 |
| October | 198.17 | 22.38 | 32.83 | 22.60 | 0.33 | 22.60 |
| November | 271.17 | 21.72 | 59.33 | 21.59 | 59.33 | 21.51 |
| December | 260.00 | 21.30 | 146.33 | 21.19 | 146.33 | 21.14 |
| Annual Sum or Average | 2429.00 | 21.93 | 1008.50 | 22.08 | 523.83 | 21.94 |
| Minimum of Months | 107.17 | 21.16 | 27.00 | 21.10 | 0.00 | 21.07 |
| Maximum of Months | 285.33 | 22.75 | 185.67 | 23.32 | 185.67 | 23.32 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.40 | 117.50 | 21.29 | 117.50 | 21.23 |
| February | 240.83 | 21.84 | 48.00 | 21.71 | 48.00 | 21.61 |
| March | 268.17 | 22.32 | 2.00 | 22.31 | 2.00 | 22.30 |
| April | 165.50 | 22.62 | 29.50 | 22.82 | 0.00 | 22.82 |
| May | 114.50 | 22.85 | 89.33 | 23.34 | 0.00 | 23.34 |
| June | 116.33 | 22.85 | 94.50 | 23.36 | 0.00 | 23.36 |
| July | 203.17 | 22.11 | 23.00 | 22.26 | 0.00 | 22.26 |
| August | 190.50 | 22.00 | 76.00 | 22.48 | 0.00 | 22.48 |
| September | 84.17 | 22.61 | 124.83 | 23.42 | 0.00 | 23.42 |
| October | 172.50 | 22.67 | 46.17 | 22.95 | 0.00 | 22.95 |
| November | 259.50 | 22.06 | 8.00 | 22.04 | 8.00 | 22.01 |
| December | 260.00 | 21.58 | 74.33 | 21.46 | 74.33 | 21.38 |
| Annual Sum or Average | 2348.17 | 22.12 | 733.17 | 22.31 | 249.83 | 22.22 |
| Minimum of Months | 84.17 | 21.40 | 2.00 | 21.29 | 0.00 | 21.23 |
| Maximum of Months | 273.00 | 22.85 | 124.83 | 23.42 | 117.50 | 23.42 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 20.99 | 165.83 | 20.98 | 165.83 | 20.97 |
| February | 247.00 | 21.23 | 97.17 | 21.16 | 97.17 | 21.12 |
| March | 299.00 | 21.87 | 13.67 | 21.83 | 13.67 | 21.79 |
| April | 231.50 | 22.75 | 7.50 | 22.79 | 0.33 | 22.79 |
| May | 144.67 | 23.42 | 20.33 | 23.49 | 0.00 | 23.49 |
| June | 97.33 | 23.51 | 16.67 | 23.58 | 0.00 | 23.58 |
| July | 200.67 | 22.98 | 21.67 | 23.07 | 0.00 | 23.07 |
| August | 199.33 | 22.79 | 42.33 | 23.00 | 0.00 | 23.00 |
| September | 116.17 | 23.25 | 47.67 | 23.47 | 0.00 | 23.47 |
| October | 241.00 | 22.76 | 0.00 | 22.76 | 0.00 | 22.76 |
| November | 273.00 | 21.63 | 36.83 | 21.55 | 36.83 | 21.49 |
| December | 260.00 | 21.04 | 135.33 | 21.02 | 135.33 | 21.01 |
| Annual Sum or Average | 2582.67 | 22.14 | 605.00 | 22.06 | 449.17 | 21.93 |
| Minimum of Months | 97.33 | 20.99 | 0.00 | 20.98 | 0.00 | 20.97 |
| Maximum of Months | 299.00 | 23.51 | 165.83 | 23.58 | 165.83 | 23.58 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.06 | 223.50 | 21.03 | 223.50 | 21.02 |
| February | 247.00 | 21.22 | 147.00 | 21.14 | 147.00 | 21.10 |
| March | 299.00 | 21.53 | 71.00 | 21.43 | 71.00 | 21.37 |
| April | 240.00 | 22.15 | 20.83 | 22.18 | 10.50 | 22.13 |
| May | 182.83 | 22.72 | 37.83 | 22.93 | 0.00 | 22.93 |
| June | 162.17 | 22.74 | 42.50 | 23.00 | 0.00 | 23.00 |
| July | 220.67 | 22.00 | 15.83 | 22.11 | 0.00 | 22.11 |
| August | 240.83 | 21.82 | 27.33 | 22.01 | 0.00 | 22.01 |
| September | 177.00 | 22.49 | 37.00 | 22.74 | 0.00 | 22.74 |
| October | 254.50 | 22.16 | 2.67 | 22.15 | 2.67 | 22.14 |
| November | 273.00 | 21.47 | 90.50 | 21.35 | 90.50 | 21.28 |
| December | 260.00 | 21.09 | 193.83 | 21.05 | 193.83 | 21.04 |
| Annual Sum or Average | 2830.00 | 21.79 | 909.83 | 21.73 | 739.00 | 21.61 |
| Minimum of Months | 162.17 | 21.06 | 2.67 | 21.03 | 0.00 | 21.02 |
| Maximum of Months | 299.00 | 22.74 | 223.50 | 23.00 | 223.50 | 23.00 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.23 | 153.17 | 21.15 | 153.17 | 21.11 |
| February | 247.00 | 21.44 | 95.67 | 21.32 | 95.67 | 21.26 |
| March | 299.00 | 21.90 | 16.17 | 21.86 | 16.17 | 21.82 |
| April | 238.67 | 22.47 | 8.83 | 22.51 | 0.33 | 22.51 |
| May | 157.67 | 22.78 | 35.67 | 23.00 | 0.00 | 23.00 |
| June | 164.83 | 22.80 | 18.00 | 22.91 | 0.00 | 22.91 |
| July | 259.00 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
| August | 297.67 | 21.70 | 0.00 | 21.70 | 0.00 | 21.70 |
| September | 178.33 | 22.49 | 33.17 | 22.70 | 0.00 | 22.70 |
| October | 247.33 | 22.45 | 0.17 | 22.44 | 0.17 | 22.44 |
| November | 273.00 | 21.82 | 36.50 | 21.73 | 36.50 | 21.65 |
| December | 260.00 | 21.31 | 117.33 | 21.22 | 117.33 | 21.17 |
| Annual Sum or Average | 2895.50 | 21.93 | 514.67 | 21.88 | 419.33 | 21.78 |
| Minimum of Months | 157.67 | 21.23 | 0.00 | 21.15 | 0.00 | 21.11 |
| Maximum of Months | 299.00 | 22.80 | 153.17 | 23.00 | 153.17 | 23.00 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.17 | 182.50 | 21.11 | 182.50 | 21.08 |
| February | 244.50 | 21.57 | 97.67 | 21.41 | 97.67 | 21.32 |
| March | 284.17 | 21.99 | 24.67 | 21.92 | 24.67 | 21.85 |
| April | 197.33 | 22.46 | 29.67 | 22.60 | 4.67 | 22.57 |
| May | 137.67 | 22.75 | 67.33 | 23.15 | 0.00 | 23.15 |
| June | 122.33 | 22.77 | 84.00 | 23.27 | 0.00 | 23.27 |
| July | 147.33 | 22.12 | 67.33 | 22.65 | 0.00 | 22.65 |
| August | 169.83 | 22.04 | 105.83 | 22.76 | 0.00 | 22.76 |
| September | 104.67 | 22.63 | 116.00 | 23.34 | 0.00 | 23.34 |
| October | 196.33 | 22.40 | 35.00 | 22.64 | 0.33 | 22.64 |
| November | 271.00 | 21.75 | 56.67 | 21.62 | 56.67 | 21.53 |
| December | 260.00 | 21.32 | 142.17 | 21.21 | 142.17 | 21.16 |
| Annual Sum or Average | 2408.17 | 21.95 | 1008.83 | 22.10 | 508.67 | 21.96 |
| Minimum of Months | 104.67 | 21.17 | 24.67 | 21.11 | 0.00 | 21.08 |
| Maximum of Months | 284.17 | 22.77 | 182.50 | 23.34 | 182.50 | 23.34 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.42 | 113.17 | 21.31 | 113.17 | 21.24 |
| February | 240.67 | 21.87 | 47.50 | 21.73 | 47.50 | 21.63 |
| March | 266.33 | 22.36 | 1.67 | 22.35 | 1.67 | 22.35 |
| April | 160.00 | 22.64 | 30.83 | 22.86 | 0.00 | 22.86 |
| May | 109.50 | 22.86 | 95.33 | 23.38 | 0.00 | 23.38 |
| June | 111.00 | 22.88 | 99.33 | 23.40 | 0.00 | 23.40 |
| July | 194.00 | 22.14 | 25.83 | 22.31 | 0.00 | 22.31 |
| August | 184.50 | 22.03 | 81.83 | 22.54 | 0.00 | 22.54 |
| September | 81.00 | 22.63 | 130.67 | 23.46 | 0.00 | 23.46 |
| October | 167.00 | 22.70 | 49.33 | 22.99 | 0.00 | 22.99 |
| November | 254.00 | 22.08 | 5.33 | 22.06 | 5.33 | 22.04 |
| December | 260.00 | 21.62 | 70.50 | 21.49 | 70.50 | 21.41 |
| Annual Sum or Average | 2301.00 | 22.14 | 751.33 | 22.35 | 238.17 | 22.26 |
| Minimum of Months | 81.00 | 21.42 | 1.67 | 21.31 | 0.00 | 21.24 |
| Maximum of Months | 273.00 | 22.88 | 130.67 | 23.46 | 113.17 | 23.46 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.00 | 158.67 | 20.98 | 158.67 | 20.98 |
| February | 247.00 | 21.28 | 88.00 | 21.20 | 88.00 | 21.15 |
| March | 299.00 | 22.01 | 9.67 | 21.98 | 9.67 | 21.95 |
| April | 226.17 | 22.90 | 8.17 | 22.94 | 0.00 | 22.94 |
| May | 126.17 | 23.47 | 22.83 | 23.55 | 0.00 | 23.55 |
| June | 71.33 | 23.55 | 29.33 | 23.68 | 0.00 | 23.68 |
| July | 171.17 | 23.07 | 27.83 | 23.20 | 0.00 | 23.20 |
| August | 178.00 | 22.88 | 63.33 | 23.17 | 0.00 | 23.17 |
| September | 96.67 | 23.31 | 56.67 | 23.57 | 0.00 | 23.57 |
| October | 231.00 | 22.87 | 0.00 | 22.87 | 0.00 | 22.87 |
| November | 273.00 | 21.73 | 27.00 | 21.67 | 27.00 | 21.61 |
| December | 260.00 | 21.06 | 126.50 | 21.03 | 126.50 | 21.02 |
| Annual Sum or Average | 2452.50 | 22.16 | 618.00 | 22.13 | 409.83 | 21.99 |
| Minimum of Months | 71.33 | 21.00 | 0.00 | 20.98 | 0.00 | 20.98 |
| Maximum of Months | 299.00 | 23.55 | 158.67 | 23.68 | 158.67 | 23.68 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.06 | 221.83 | 21.03 | 221.83 | 21.03 |
| February | 247.00 | 21.23 | 143.83 | 21.15 | 143.83 | 21.11 |
| March | 299.00 | 21.57 | 65.67 | 21.47 | 65.67 | 21.40 |
| April | 237.83 | 22.21 | 19.83 | 22.25 | 8.67 | 22.21 |
| May | 172.17 | 22.73 | 42.83 | 22.98 | 0.00 | 22.98 |
| June | 146.50 | 22.76 | 47.50 | 23.06 | 0.00 | 23.06 |
| July | 205.33 | 22.04 | 20.33 | 22.19 | 0.00 | 22.19 |
| August | 231.33 | 21.86 | 33.00 | 22.08 | 0.00 | 22.08 |
| September | 169.17 | 22.51 | 42.00 | 22.79 | 0.00 | 22.79 |
| October | 251.83 | 22.18 | 2.67 | 22.17 | 2.67 | 22.16 |
| November | 273.00 | 21.49 | 88.50 | 21.37 | 88.50 | 21.30 |
| December | 260.00 | 21.09 | 192.33 | 21.06 | 192.33 | 21.04 |
| Annual Sum or Average | 2766.17 | 21.80 | 920.33 | 21.75 | 723.50 | 21.63 |
| Minimum of Months | 146.50 | 21.06 | 2.67 | 21.03 | 0.00 | 21.03 |
| Maximum of Months | 299.00 | 22.76 | 221.83 | 23.06 | 221.83 | 23.06 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.23 | 151.67 | 21.15 | 151.67 | 21.12 |
| February | 247.00 | 21.46 | 93.50 | 21.34 | 93.50 | 21.27 |
| March | 299.00 | 21.95 | 13.50 | 21.91 | 13.50 | 21.88 |
| April | 232.83 | 22.53 | 9.67 | 22.59 | 0.33 | 22.58 |
| May | 144.67 | 22.81 | 43.33 | 23.08 | 0.00 | 23.08 |
| June | 137.83 | 22.83 | 33.17 | 23.04 | 0.00 | 23.04 |
| July | 256.67 | 21.91 | 0.00 | 21.91 | 0.00 | 21.91 |
| August | 296.17 | 21.81 | 0.00 | 21.81 | 0.00 | 21.81 |
| September | 166.17 | 22.54 | 40.67 | 22.79 | 0.00 | 22.79 |
| October | 243.50 | 22.48 | 0.00 | 22.48 | 0.00 | 22.48 |
| November | 273.00 | 21.86 | 33.67 | 21.77 | 33.67 | 21.69 |
| December | 260.00 | 21.31 | 115.33 | 21.22 | 115.33 | 21.18 |
| Annual Sum or Average | 2829.83 | 21.97 | 534.50 | 21.93 | 408.00 | 21.83 |
| Minimum of Months | 137.83 | 21.23 | 0.00 | 21.15 | 0.00 | 21.12 |
| Maximum of Months | 299.00 | 22.83 | 151.67 | 23.08 | 151.67 | 23.08 |
Report: ComfortReportSimple55Monthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.65 | 78.83 | 21.51 | 78.83 | 21.43 |
| February | 247.00 | 22.09 | 41.17 | 21.95 | 41.17 | 21.84 |
| March | 292.67 | 22.96 | 1.17 | 22.96 | 1.17 | 22.95 |
| April | 161.33 | 23.36 | 28.83 | 23.46 | 0.00 | 23.46 |
| May | 34.17 | 23.41 | 116.50 | 23.86 | 0.00 | 23.86 |
| June | 11.17 | 23.30 | 208.33 | 23.96 | 0.00 | 23.96 |
| July | 136.50 | 22.73 | 43.17 | 22.95 | 0.00 | 22.95 |
| August | 169.50 | 22.62 | 74.33 | 22.93 | 0.00 | 22.93 |
| September | 30.83 | 22.98 | 170.83 | 23.84 | 0.00 | 23.84 |
| October | 152.00 | 23.28 | 5.17 | 23.31 | 0.00 | 23.31 |
| November | 239.67 | 22.60 | 6.00 | 22.58 | 4.00 | 22.56 |
| December | 260.00 | 21.86 | 37.83 | 21.76 | 37.83 | 21.68 |
| Annual Sum or Average | 2007.83 | 22.51 | 812.17 | 22.76 | 163.00 | 22.66 |
| Minimum of Months | 11.17 | 21.65 | 1.17 | 21.51 | 0.00 | 21.43 |
| Maximum of Months | 292.67 | 23.41 | 208.33 | 23.96 | 78.83 | 23.96 |
Report: ComfortReportSimple55Monthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 20.99 | 203.67 | 20.98 | 203.67 | 20.98 |
| February | 247.00 | 21.19 | 118.00 | 21.13 | 118.00 | 21.09 |
| March | 299.00 | 22.10 | 5.17 | 22.08 | 5.17 | 22.06 |
| April | 221.50 | 23.31 | 9.50 | 23.34 | 0.00 | 23.34 |
| May | 58.33 | 23.83 | 42.67 | 23.90 | 0.00 | 23.90 |
| June | 9.33 | 23.84 | 65.00 | 23.98 | 0.00 | 23.98 |
| July | 39.00 | 23.56 | 102.33 | 23.88 | 0.00 | 23.88 |
| August | 57.50 | 23.39 | 135.00 | 23.82 | 0.00 | 23.82 |
| September | 50.17 | 23.63 | 68.00 | 23.84 | 0.00 | 23.84 |
| October | 239.50 | 22.98 | 0.00 | 22.98 | 0.00 | 22.98 |
| November | 273.00 | 21.68 | 55.83 | 21.56 | 55.83 | 21.48 |
| December | 260.00 | 21.01 | 178.83 | 21.00 | 178.83 | 21.00 |
| Annual Sum or Average | 2027.33 | 22.04 | 984.00 | 22.12 | 561.50 | 21.94 |
| Minimum of Months | 9.33 | 20.99 | 0.00 | 20.98 | 0.00 | 20.98 |
| Maximum of Months | 299.00 | 23.84 | 203.67 | 23.98 | 203.67 | 23.98 |
Report: ComfortReportSimple55Monthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 19.21 | 266.50 | 19.19 | 266.50 | 19.18 |
| February | 247.00 | 19.72 | 178.50 | 19.50 | 178.50 | 19.42 |
| March | 299.00 | 20.46 | 121.67 | 20.22 | 121.67 | 20.09 |
| April | 244.33 | 20.91 | 41.17 | 20.74 | 34.33 | 20.54 |
| May | 247.00 | 21.40 | 28.00 | 21.46 | 10.17 | 21.35 |
| June | 222.00 | 21.82 | 33.83 | 22.06 | 2.17 | 22.04 |
| July | 174.17 | 22.01 | 47.33 | 22.45 | 0.50 | 22.46 |
| August | 155.00 | 21.83 | 118.17 | 22.82 | 1.50 | 22.83 |
| September | 186.00 | 21.61 | 62.00 | 22.12 | 3.17 | 22.07 |
| October | 263.50 | 21.09 | 21.17 | 20.90 | 21.17 | 20.73 |
| November | 273.00 | 20.11 | 163.33 | 19.88 | 163.33 | 19.78 |
| December | 260.00 | 19.37 | 241.00 | 19.31 | 241.00 | 19.29 |
| Annual Sum or Average | 2844.00 | 20.67 | 1322.67 | 20.55 | 1044.00 | 20.29 |
| Minimum of Months | 155.00 | 19.21 | 21.17 | 19.19 | 0.50 | 19.18 |
| Maximum of Months | 299.00 | 22.01 | 266.50 | 22.82 | 266.50 | 22.83 |
Report: ComfortReportSimple55Monthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.95 | 57.00 | 21.71 | 57.00 | 21.54 |
| February | 238.83 | 22.84 | 16.17 | 22.72 | 16.17 | 22.61 |
| March | 165.67 | 23.98 | 24.00 | 24.15 | 0.00 | 24.15 |
| April | 8.83 | 24.31 | 199.17 | 25.85 | 0.00 | 25.85 |
| May | 7.33 | 26.70 | 286.00 | 26.45 | 7.33 | 26.45 |
| June | 13.83 | 26.70 | 286.00 | 26.59 | 13.83 | 26.60 |
| July | 4.50 | 26.67 | 258.17 | 25.68 | 4.50 | 25.70 |
| August | 2.00 | 26.62 | 292.33 | 25.54 | 2.00 | 25.55 |
| September | 21.67 | 26.70 | 259.17 | 26.31 | 21.67 | 26.34 |
| October | 25.50 | 24.01 | 188.50 | 25.50 | 0.00 | 25.50 |
| November | 184.33 | 23.19 | 44.33 | 23.57 | 0.00 | 23.57 |
| December | 260.00 | 22.46 | 16.00 | 22.36 | 16.00 | 22.27 |
| Annual Sum or Average | 1205.50 | 22.96 | 1926.83 | 24.68 | 138.50 | 24.60 |
| Minimum of Months | 2.00 | 21.95 | 16.00 | 21.71 | 0.00 | 21.54 |
| Maximum of Months | 273.00 | 26.70 | 292.33 | 26.59 | 57.00 | 26.60 |
Report: ComfortReportSimple55Monthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 19.21 | 265.67 | 19.19 | 265.67 | 19.18 |
| February | 247.00 | 20.22 | 170.33 | 20.00 | 170.33 | 19.90 |
| March | 299.00 | 21.99 | 18.83 | 21.90 | 18.83 | 21.83 |
| April | 198.67 | 23.14 | 31.33 | 23.43 | 0.00 | 23.43 |
| May | 31.50 | 23.72 | 189.67 | 25.09 | 0.00 | 25.09 |
| June | 2.67 | 23.81 | 261.00 | 25.51 | 0.00 | 25.51 |
| July | 22.17 | 23.54 | 193.33 | 24.92 | 0.00 | 24.92 |
| August | 35.83 | 23.31 | 210.17 | 24.74 | 0.00 | 24.74 |
| September | 30.83 | 23.61 | 170.00 | 24.94 | 0.00 | 24.94 |
| October | 222.50 | 22.89 | 16.50 | 23.03 | 0.17 | 23.03 |
| November | 273.00 | 21.37 | 110.00 | 21.06 | 110.00 | 20.89 |
| December | 260.00 | 19.74 | 249.83 | 19.72 | 249.83 | 19.71 |
| Annual Sum or Average | 1896.17 | 21.29 | 1886.67 | 22.05 | 814.83 | 21.62 |
| Minimum of Months | 2.67 | 19.21 | 16.50 | 19.19 | 0.00 | 19.18 |
| Maximum of Months | 299.00 | 23.81 | 265.67 | 25.51 | 265.67 | 25.51 |
Report: ComfortReportSimple55Monthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 231.00 | 21.09 | 172.17 | 21.05 | 172.17 | 21.04 |
| February | 209.00 | 21.54 | 86.50 | 21.39 | 86.50 | 21.30 |
| March | 253.00 | 22.55 | 4.83 | 22.52 | 4.83 | 22.50 |
| April | 150.33 | 23.25 | 16.67 | 23.33 | 0.00 | 23.33 |
| May | 55.00 | 23.58 | 55.67 | 23.79 | 0.00 | 23.79 |
| June | 8.83 | 23.66 | 111.83 | 23.98 | 0.00 | 23.98 |
| July | 27.17 | 23.31 | 135.17 | 23.88 | 0.00 | 23.88 |
| August | 32.83 | 23.14 | 171.83 | 23.86 | 0.00 | 23.86 |
| September | 31.67 | 23.50 | 105.50 | 23.89 | 0.00 | 23.89 |
| October | 161.83 | 23.10 | 3.33 | 23.12 | 0.00 | 23.12 |
| November | 231.00 | 22.00 | 45.00 | 21.84 | 45.00 | 21.72 |
| December | 220.00 | 21.21 | 133.17 | 21.13 | 133.17 | 21.10 |
| Annual Sum or Average | 1611.67 | 22.15 | 1041.67 | 22.38 | 441.67 | 22.18 |
| Minimum of Months | 8.83 | 21.09 | 3.33 | 21.05 | 0.00 | 21.04 |
| Maximum of Months | 253.00 | 23.66 | 172.17 | 23.98 | 172.17 | 23.98 |
Report: ComfortReportSimple55Monthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.42 | 70.00 | 21.34 | 70.00 | 21.29 |
| February | 247.00 | 21.92 | 20.83 | 21.85 | 20.83 | 21.79 |
| March | 284.33 | 22.88 | 0.00 | 22.88 | 0.00 | 22.88 |
| April | 72.00 | 23.11 | 50.50 | 23.48 | 0.00 | 23.48 |
| May | 17.17 | 23.13 | 214.00 | 23.93 | 0.00 | 23.93 |
| June | 3.67 | 23.21 | 265.83 | 23.99 | 0.00 | 23.99 |
| July | 13.33 | 23.00 | 211.83 | 23.91 | 0.00 | 23.91 |
| August | 28.67 | 22.87 | 224.00 | 23.82 | 0.00 | 23.82 |
| September | 27.17 | 23.04 | 186.00 | 23.87 | 0.00 | 23.87 |
| October | 147.83 | 22.93 | 17.00 | 23.04 | 0.00 | 23.04 |
| November | 262.00 | 22.23 | 3.33 | 22.23 | 1.83 | 22.23 |
| December | 260.00 | 21.54 | 27.83 | 21.49 | 27.83 | 21.45 |
| Annual Sum or Average | 1636.17 | 22.20 | 1291.17 | 22.86 | 120.50 | 22.79 |
| Minimum of Months | 3.67 | 21.42 | 0.00 | 21.34 | 0.00 | 21.29 |
| Maximum of Months | 284.33 | 23.21 | 265.83 | 23.99 | 70.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 16.00 | 24.00 | 171.17 | 23.99 | 1.83 | 23.99 |
| February | 1.67 | 24.00 | 177.67 | 23.99 | 0.00 | 23.99 |
| March | 0.00 | 0.00 | 234.33 | 23.99 | 0.00 | 23.99 |
| April | 0.00 | 0.00 | 236.67 | 23.99 | 0.00 | 23.99 |
| May | 0.00 | 0.00 | 284.50 | 24.00 | 0.00 | 24.00 |
| June | 0.00 | 0.00 | 286.00 | 24.00 | 0.00 | 24.00 |
| July | 1.67 | 24.00 | 260.00 | 24.00 | 1.67 | 24.00 |
| August | 4.33 | 24.00 | 299.00 | 24.00 | 4.33 | 24.00 |
| September | 3.83 | 23.99 | 260.00 | 24.00 | 3.83 | 24.00 |
| October | 0.00 | 0.00 | 262.83 | 23.99 | 0.00 | 23.99 |
| November | 0.00 | 0.00 | 213.17 | 23.99 | 0.00 | 23.99 |
| December | 2.17 | 24.00 | 168.33 | 23.99 | 0.17 | 23.99 |
| Annual Sum or Average | 29.67 | 24.00 | 2853.67 | 24.00 | 11.83 | 24.00 |
| Minimum of Months | 0.00 | 0.00 | 168.33 | 23.99 | 0.00 | 23.99 |
| Maximum of Months | 16.00 | 24.00 | 299.00 | 24.00 | 4.33 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 231.00 | 21.19 | 40.67 | 21.16 | 40.67 | 21.14 |
| February | 197.83 | 21.53 | 23.00 | 21.56 | 16.67 | 21.52 |
| March | 222.33 | 21.91 | 6.50 | 21.97 | 0.00 | 21.97 |
| April | 117.83 | 22.18 | 50.33 | 22.72 | 0.00 | 22.72 |
| May | 45.33 | 22.35 | 165.83 | 23.64 | 0.00 | 23.64 |
| June | 6.67 | 22.60 | 208.67 | 23.95 | 0.00 | 23.95 |
| July | 26.33 | 22.39 | 151.83 | 23.76 | 0.00 | 23.76 |
| August | 28.00 | 22.14 | 173.33 | 23.73 | 1.00 | 23.73 |
| September | 29.00 | 22.95 | 177.50 | 23.84 | 6.17 | 23.85 |
| October | 112.83 | 22.26 | 63.67 | 22.88 | 0.00 | 22.88 |
| November | 201.17 | 21.55 | 19.33 | 21.76 | 0.50 | 21.76 |
| December | 220.00 | 21.31 | 13.50 | 21.29 | 13.50 | 21.27 |
| Annual Sum or Average | 1438.33 | 21.70 | 1094.17 | 22.60 | 78.50 | 22.56 |
| Minimum of Months | 6.67 | 21.19 | 6.50 | 21.16 | 0.00 | 21.14 |
| Maximum of Months | 231.00 | 22.95 | 208.67 | 23.95 | 40.67 | 23.95 |
Report: ComfortReportSimple55Monthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.48 | 133.00 | 21.33 | 133.00 | 21.26 |
| February | 247.00 | 22.06 | 71.67 | 21.83 | 71.67 | 21.69 |
| March | 293.67 | 23.26 | 0.83 | 23.26 | 0.83 | 23.25 |
| April | 144.83 | 23.68 | 26.33 | 23.73 | 0.00 | 23.73 |
| May | 20.83 | 23.88 | 108.33 | 23.98 | 0.00 | 23.98 |
| June | 1.17 | 23.88 | 194.83 | 24.00 | 0.00 | 24.00 |
| July | 24.67 | 23.35 | 162.83 | 23.91 | 0.00 | 23.91 |
| August | 32.33 | 23.20 | 203.83 | 23.89 | 0.00 | 23.89 |
| September | 16.00 | 23.62 | 145.17 | 23.96 | 0.00 | 23.96 |
| October | 149.83 | 23.59 | 4.00 | 23.60 | 0.00 | 23.60 |
| November | 241.83 | 22.66 | 7.83 | 22.61 | 7.83 | 22.57 |
| December | 260.00 | 21.68 | 88.00 | 21.52 | 88.00 | 21.42 |
| Annual Sum or Average | 1705.17 | 22.55 | 1146.67 | 22.82 | 301.33 | 22.65 |
| Minimum of Months | 1.17 | 21.48 | 0.83 | 21.33 | 0.00 | 21.26 |
| Maximum of Months | 293.67 | 23.88 | 203.83 | 24.00 | 133.00 | 24.00 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.18262 | 37.19164 | -0.3891 | 8.59509 |
| February | 247.00000 | 21.59109 | 37.55704 | -0.2365 | 7.60095 |
| March | 299.00000 | 22.08822 | 37.10794 | -0.0591 | 6.40573 |
| April | 260.00000 | 22.82383 | 38.23277 | 0.18292 | 7.43941 |
| May | 286.00000 | 23.37713 | 42.37143 | -0.4368 | 10.80969 |
| June | 286.00000 | 23.43236 | 42.22029 | -0.3793 | 9.28901 |
| July | 260.00000 | 22.80033 | 47.14301 | -0.5037 | 12.75507 |
| August | 299.00000 | 22.79867 | 50.83192 | -0.4693 | 12.65563 |
| September | 260.00000 | 23.39204 | 47.54743 | -0.3402 | 9.47332 |
| October | 273.00000 | 22.82523 | 42.28193 | 0.21776 | 7.38434 |
| November | 273.00000 | 21.75844 | 42.35540 | -0.1347 | 6.61828 |
| December | 260.00000 | 21.34782 | 36.97171 | -0.3266 | 7.96486 |
| Annual Sum or Average | 3276.00000 | 22.46353 | 41.87907 | -0.2412 | 8.93732 |
| Minimum of Months | 247.00000 | 21.18262 | 36.97171 | -0.5037 | 6.40573 |
| Maximum of Months | 299.00000 | 23.43236 | 50.83192 | 0.21776 | 12.75507 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.43484 | 36.80159 | -0.2954 | 7.46384 |
| February | 247.00000 | 21.91394 | 37.04362 | -0.1251 | 6.88155 |
| March | 299.00000 | 22.50801 | 36.38601 | 0.07191 | 6.25961 |
| April | 260.00000 | 23.11488 | 37.60400 | 0.27695 | 7.86731 |
| May | 286.00000 | 23.50435 | 42.02100 | -0.3671 | 9.01535 |
| June | 286.00000 | 23.47705 | 42.07126 | -0.3473 | 8.37767 |
| July | 260.00000 | 22.45628 | 48.10889 | -0.6017 | 14.13170 |
| August | 299.00000 | 22.61204 | 51.41103 | -0.5226 | 13.01038 |
| September | 260.00000 | 23.47627 | 47.29550 | -0.2955 | 8.41718 |
| October | 273.00000 | 23.14785 | 41.47675 | 0.31861 | 8.12721 |
| November | 273.00000 | 22.17509 | 41.55437 | -0.0052 | 6.35221 |
| December | 260.00000 | 21.66106 | 36.49803 | -0.2159 | 6.93040 |
| Annual Sum or Average | 3276.00000 | 22.63413 | 41.58653 | -0.1778 | 8.58867 |
| Minimum of Months | 247.00000 | 21.43484 | 36.38601 | -0.6017 | 6.25961 |
| Maximum of Months | 299.00000 | 23.50435 | 51.41103 | 0.31861 | 14.13170 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 20.99529 | 35.84240 | -0.3994 | 8.55832 |
| February | 247.00000 | 21.23566 | 36.54580 | -0.3014 | 7.45047 |
| March | 299.00000 | 21.87417 | 35.75697 | -0.1133 | 5.80500 |
| April | 260.00000 | 22.89785 | 36.47730 | 0.15114 | 6.39837 |
| May | 286.00000 | 23.70620 | 39.76756 | -0.4297 | 9.44502 |
| June | 286.00000 | 23.82914 | 40.02483 | -0.3692 | 8.11793 |
| July | 260.00000 | 23.20925 | 45.53718 | -0.5368 | 11.87546 |
| August | 299.00000 | 23.17743 | 49.34358 | -0.5192 | 11.78872 |
| September | 260.00000 | 23.65621 | 45.76838 | -0.3985 | 8.98898 |
| October | 273.00000 | 22.91081 | 40.56965 | 0.18034 | 6.36769 |
| November | 273.00000 | 21.63439 | 40.88285 | -0.1516 | 6.46114 |
| December | 260.00000 | 21.05217 | 35.80834 | -0.3620 | 7.91330 |
| Annual Sum or Average | 3276.00000 | 22.53215 | 40.24656 | -0.2721 | 8.27481 |
| Minimum of Months | 247.00000 | 20.99529 | 35.75697 | -0.5368 | 5.80500 |
| Maximum of Months | 299.00000 | 23.82914 | 49.34358 | 0.18034 | 11.87546 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.05558 | 37.40565 | -0.4436 | 9.34784 |
| February | 247.00000 | 21.21882 | 38.19485 | -0.3644 | 8.45111 |
| March | 299.00000 | 21.53076 | 38.05030 | -0.2259 | 6.70516 |
| April | 260.00000 | 22.28235 | 39.49428 | 0.02151 | 6.39389 |
| May | 286.00000 | 23.14786 | 43.29341 | -0.5509 | 13.11835 |
| June | 286.00000 | 23.22543 | 42.93156 | -0.4749 | 10.90227 |
| July | 260.00000 | 22.20273 | 48.80979 | -0.7121 | 17.32556 |
| August | 299.00000 | 22.12363 | 52.93986 | -0.7164 | 17.69499 |
| September | 260.00000 | 22.89975 | 49.18227 | -0.5608 | 13.31558 |
| October | 273.00000 | 22.28225 | 43.84270 | 0.04822 | 6.03688 |
| November | 273.00000 | 21.46720 | 42.92491 | -0.2275 | 6.97650 |
| December | 260.00000 | 21.08779 | 37.40202 | -0.4184 | 8.89278 |
| Annual Sum or Average | 3276.00000 | 22.05468 | 42.93980 | -0.3875 | 10.46972 |
| Minimum of Months | 247.00000 | 21.05558 | 37.40202 | -0.7164 | 6.03688 |
| Maximum of Months | 299.00000 | 23.22543 | 52.93986 | 0.04822 | 17.69499 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.22610 | 37.12887 | -0.3682 | 8.22374 |
| February | 247.00000 | 21.43911 | 37.82265 | -0.2795 | 7.41874 |
| March | 299.00000 | 21.89667 | 37.47428 | -0.1104 | 5.93141 |
| April | 260.00000 | 22.57441 | 39.01657 | 0.11171 | 6.33817 |
| May | 286.00000 | 23.28138 | 43.01251 | -0.4830 | 11.07328 |
| June | 286.00000 | 23.20449 | 42.95006 | -0.4622 | 10.20017 |
| July | 260.00000 | 21.76392 | 50.09423 | -0.8386 | 20.47456 |
| August | 299.00000 | 21.70537 | 54.22337 | -0.8361 | 20.49409 |
| September | 260.00000 | 22.86970 | 49.29443 | -0.5523 | 12.67320 |
| October | 273.00000 | 22.58369 | 43.20681 | 0.14033 | 6.25018 |
| November | 273.00000 | 21.81918 | 42.24608 | -0.1133 | 6.30222 |
| December | 260.00000 | 21.31060 | 37.04711 | -0.3290 | 7.61754 |
| Annual Sum or Average | 3276.00000 | 22.14865 | 42.86554 | -0.3461 | 10.29812 |
| Minimum of Months | 247.00000 | 21.22610 | 37.04711 | -0.8386 | 5.93141 |
| Maximum of Months | 299.00000 | 23.28138 | 54.22337 | 0.14033 | 20.49409 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.16417 | 37.22261 | -0.3963 | 8.68600 |
| February | 247.00000 | 21.57868 | 37.58129 | -0.2405 | 7.61087 |
| March | 299.00000 | 22.06525 | 37.15150 | -0.0659 | 6.39600 |
| April | 260.00000 | 22.79223 | 38.31683 | 0.17320 | 7.36620 |
| May | 286.00000 | 23.35077 | 42.47987 | -0.4501 | 11.07786 |
| June | 286.00000 | 23.39962 | 42.33199 | -0.3944 | 9.56175 |
| July | 260.00000 | 22.73119 | 47.33030 | -0.5283 | 13.30529 |
| August | 299.00000 | 22.75996 | 50.95205 | -0.4844 | 12.98734 |
| September | 260.00000 | 23.37507 | 47.60867 | -0.3486 | 9.61648 |
| October | 273.00000 | 22.81339 | 42.32368 | 0.21371 | 7.34046 |
| November | 273.00000 | 21.73697 | 42.40103 | -0.1411 | 6.62338 |
| December | 260.00000 | 21.29671 | 37.05453 | -0.3436 | 8.08937 |
| Annual Sum or Average | 3276.00000 | 22.43410 | 41.95789 | -0.2522 | 9.07813 |
| Minimum of Months | 247.00000 | 21.16417 | 37.05453 | -0.5283 | 6.39600 |
| Maximum of Months | 299.00000 | 23.39962 | 50.95205 | 0.21371 | 13.30529 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.40413 | 36.84720 | -0.3050 | 7.53420 |
| February | 247.00000 | 21.89646 | 37.07549 | -0.1299 | 6.85061 |
| March | 299.00000 | 22.49078 | 36.42762 | 0.06679 | 6.21222 |
| April | 260.00000 | 23.09876 | 37.66739 | 0.27136 | 7.78278 |
| May | 286.00000 | 23.48966 | 42.10227 | -0.3757 | 9.13172 |
| June | 286.00000 | 23.44680 | 42.17590 | -0.3612 | 8.57711 |
| July | 260.00000 | 22.37335 | 48.33795 | -0.6302 | 14.82897 |
| August | 299.00000 | 22.54726 | 51.60694 | -0.5457 | 13.45779 |
| September | 260.00000 | 23.46157 | 47.35223 | -0.3040 | 8.51120 |
| October | 273.00000 | 23.14046 | 41.51807 | 0.31529 | 8.06477 |
| November | 273.00000 | 22.15371 | 41.59890 | -0.0111 | 6.31482 |
| December | 260.00000 | 21.58240 | 36.61784 | -0.2396 | 6.96641 |
| Annual Sum or Average | 3276.00000 | 22.60117 | 41.67502 | -0.1895 | 8.70692 |
| Minimum of Months | 247.00000 | 21.40413 | 36.42762 | -0.6302 | 6.21222 |
| Maximum of Months | 299.00000 | 23.48966 | 51.60694 | 0.31529 | 14.82897 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 20.99248 | 35.85569 | -0.4012 | 8.58939 |
| February | 247.00000 | 21.23130 | 36.56295 | -0.3026 | 7.45900 |
| March | 299.00000 | 21.86694 | 35.77723 | -0.1151 | 5.81005 |
| April | 260.00000 | 22.88947 | 36.50496 | 0.14901 | 6.38240 |
| May | 286.00000 | 23.70175 | 39.79897 | -0.4320 | 9.48789 |
| June | 286.00000 | 23.82382 | 40.05352 | -0.3721 | 8.16706 |
| July | 260.00000 | 23.17732 | 45.62248 | -0.5472 | 12.12280 |
| August | 299.00000 | 23.15662 | 49.40918 | -0.5264 | 11.94869 |
| September | 260.00000 | 23.65063 | 45.79143 | -0.4011 | 9.03901 |
| October | 273.00000 | 22.90752 | 40.59149 | 0.17932 | 6.36013 |
| November | 273.00000 | 21.62513 | 40.91350 | -0.1540 | 6.46169 |
| December | 260.00000 | 21.03591 | 35.84674 | -0.3684 | 7.99620 |
| Annual Sum or Average | 3276.00000 | 22.52220 | 40.28026 | -0.2756 | 8.32946 |
| Minimum of Months | 247.00000 | 20.99248 | 35.77723 | -0.5472 | 5.81005 |
| Maximum of Months | 299.00000 | 23.82382 | 49.40918 | 0.17932 | 12.12280 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.05529 | 37.40446 | -0.4438 | 9.35170 |
| February | 247.00000 | 21.21884 | 38.19302 | -0.3643 | 8.45126 |
| March | 299.00000 | 21.53133 | 38.04744 | -0.2257 | 6.70464 |
| April | 260.00000 | 22.28377 | 39.48987 | 0.02198 | 6.39540 |
| May | 286.00000 | 23.14940 | 43.28670 | -0.5501 | 13.10031 |
| June | 286.00000 | 23.22704 | 42.92557 | -0.4741 | 10.88728 |
| July | 260.00000 | 22.20206 | 48.81139 | -0.7123 | 17.33240 |
| August | 299.00000 | 22.12249 | 52.94316 | -0.7167 | 17.70337 |
| September | 260.00000 | 22.89894 | 49.18304 | -0.5609 | 13.32313 |
| October | 273.00000 | 22.28183 | 43.84159 | 0.04817 | 6.03778 |
| November | 273.00000 | 21.46593 | 42.92597 | -0.2279 | 6.97790 |
| December | 260.00000 | 21.08613 | 37.40301 | -0.4193 | 8.90823 |
| Annual Sum or Average | 3276.00000 | 22.05460 | 42.93841 | -0.3875 | 10.47057 |
| Minimum of Months | 247.00000 | 21.05529 | 37.40301 | -0.7167 | 6.03778 |
| Maximum of Months | 299.00000 | 23.22704 | 52.94316 | 0.04817 | 17.70337 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.22669 | 37.13406 | -0.3683 | 8.22578 |
| February | 247.00000 | 21.44121 | 37.82496 | -0.2791 | 7.41644 |
| March | 299.00000 | 21.90032 | 37.47438 | -0.1097 | 5.93122 |
| April | 260.00000 | 22.58018 | 39.01190 | 0.11298 | 6.34590 |
| May | 286.00000 | 23.28627 | 43.00174 | -0.4813 | 11.03585 |
| June | 286.00000 | 23.21100 | 42.93403 | -0.4602 | 10.15822 |
| July | 260.00000 | 21.76780 | 50.08424 | -0.8376 | 20.44110 |
| August | 299.00000 | 21.70820 | 54.21601 | -0.8354 | 20.47103 |
| September | 260.00000 | 22.87314 | 49.28673 | -0.5514 | 12.65605 |
| October | 273.00000 | 22.58747 | 43.20385 | 0.14106 | 6.25577 |
| November | 273.00000 | 21.82018 | 42.25077 | -0.1133 | 6.30194 |
| December | 260.00000 | 21.30861 | 37.05641 | -0.3301 | 7.63234 |
| Annual Sum or Average | 3276.00000 | 22.15172 | 42.86225 | -0.3453 | 10.28728 |
| Minimum of Months | 247.00000 | 21.22669 | 37.05641 | -0.8376 | 5.93122 |
| Maximum of Months | 299.00000 | 23.28627 | 54.21601 | 0.14106 | 20.47103 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.17463 | 37.21390 | -0.3923 | 8.63642 |
| February | 247.00000 | 21.59047 | 37.56752 | -0.2367 | 7.59679 |
| March | 299.00000 | 22.09251 | 37.10982 | -0.0577 | 6.38582 |
| April | 260.00000 | 22.82385 | 38.24912 | 0.18239 | 7.41461 |
| May | 286.00000 | 23.36897 | 42.42440 | -0.4424 | 10.89853 |
| June | 286.00000 | 23.42092 | 42.27028 | -0.3858 | 9.38842 |
| July | 260.00000 | 22.77849 | 47.20231 | -0.5118 | 12.92403 |
| August | 299.00000 | 22.79147 | 50.85618 | -0.4726 | 12.71585 |
| September | 260.00000 | 23.39676 | 47.54400 | -0.3398 | 9.43383 |
| October | 273.00000 | 22.84067 | 42.25733 | 0.22166 | 7.39055 |
| November | 273.00000 | 21.76556 | 42.34814 | -0.1323 | 6.60968 |
| December | 260.00000 | 21.31754 | 37.02934 | -0.3365 | 8.03075 |
| Annual Sum or Average | 3276.00000 | 22.45896 | 41.90074 | -0.2436 | 8.97391 |
| Minimum of Months | 247.00000 | 21.17463 | 37.02934 | -0.5118 | 6.38582 |
| Maximum of Months | 299.00000 | 23.42092 | 50.85618 | 0.22166 | 12.92403 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.42464 | 36.81535 | -0.2977 | 7.47336 |
| February | 247.00000 | 21.92039 | 37.03076 | -0.1222 | 6.84997 |
| March | 299.00000 | 22.53630 | 36.33295 | 0.08070 | 6.25317 |
| April | 260.00000 | 23.14040 | 37.55524 | 0.28433 | 7.90211 |
| May | 286.00000 | 23.51128 | 42.02088 | -0.3654 | 8.93845 |
| June | 286.00000 | 23.47861 | 42.07617 | -0.3478 | 8.34762 |
| July | 260.00000 | 22.43916 | 48.15367 | -0.6074 | 14.23466 |
| August | 299.00000 | 22.60274 | 51.43846 | -0.5260 | 13.01258 |
| September | 260.00000 | 23.49080 | 47.25536 | -0.2910 | 8.28943 |
| October | 273.00000 | 23.18233 | 41.39688 | 0.32807 | 8.19596 |
| November | 273.00000 | 22.20675 | 41.48352 | 0.00511 | 6.36138 |
| December | 260.00000 | 21.61674 | 36.56499 | -0.2281 | 6.91270 |
| Annual Sum or Average | 3276.00000 | 22.64005 | 41.57404 | -0.1760 | 8.58325 |
| Minimum of Months | 247.00000 | 21.42464 | 36.33295 | -0.6074 | 6.25317 |
| Maximum of Months | 299.00000 | 23.51128 | 51.43846 | 0.32807 | 14.23466 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.00142 | 35.81339 | -0.3949 | 8.49497 |
| February | 247.00000 | 21.27516 | 36.44292 | -0.2887 | 7.35056 |
| March | 299.00000 | 22.01362 | 35.48133 | -0.0795 | 5.70289 |
| April | 260.00000 | 23.04420 | 36.14433 | 0.18660 | 6.58980 |
| May | 286.00000 | 23.76250 | 39.52260 | -0.4064 | 8.95347 |
| June | 286.00000 | 23.87809 | 39.81908 | -0.3457 | 7.71516 |
| July | 260.00000 | 23.35654 | 45.14519 | -0.4882 | 10.77780 |
| August | 299.00000 | 23.29712 | 48.97641 | -0.4781 | 10.84030 |
| September | 260.00000 | 23.73046 | 45.49893 | -0.3682 | 8.39949 |
| October | 273.00000 | 23.04234 | 40.20682 | 0.21202 | 6.55862 |
| November | 273.00000 | 21.73277 | 40.63511 | -0.1254 | 6.42207 |
| December | 260.00000 | 21.05684 | 35.78220 | -0.3581 | 7.85806 |
| Annual Sum or Average | 3276.00000 | 22.61721 | 40.00649 | -0.2456 | 7.97760 |
| Minimum of Months | 247.00000 | 21.00142 | 35.48133 | -0.4882 | 5.70289 |
| Maximum of Months | 299.00000 | 23.87809 | 48.97641 | 0.21202 | 10.84030 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.05822 | 37.40154 | -0.4425 | 9.33188 |
| February | 247.00000 | 21.22989 | 38.17351 | -0.3602 | 8.41337 |
| March | 299.00000 | 21.56639 | 37.99028 | -0.2144 | 6.63152 |
| April | 260.00000 | 22.35249 | 39.35893 | 0.04168 | 6.44095 |
| May | 286.00000 | 23.20603 | 43.11670 | -0.5263 | 12.52787 |
| June | 286.00000 | 23.29546 | 42.72774 | -0.4469 | 10.32351 |
| July | 260.00000 | 22.31395 | 48.49804 | -0.6733 | 16.22843 |
| August | 299.00000 | 22.20513 | 52.68954 | -0.6876 | 16.88857 |
| September | 260.00000 | 22.95740 | 49.01357 | -0.5390 | 12.80337 |
| October | 273.00000 | 22.32028 | 43.75478 | 0.05947 | 6.07917 |
| November | 273.00000 | 21.48550 | 42.88589 | -0.2214 | 6.95142 |
| December | 260.00000 | 21.09064 | 37.39758 | -0.4175 | 8.88302 |
| Annual Sum or Average | 3276.00000 | 22.10150 | 42.81650 | -0.3709 | 10.15982 |
| Minimum of Months | 247.00000 | 21.05822 | 37.39758 | -0.6876 | 6.07917 |
| Maximum of Months | 299.00000 | 23.29546 | 52.68954 | 0.05947 | 16.88857 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.23184 | 37.11851 | -0.3650 | 8.18764 |
| February | 247.00000 | 21.45821 | 37.78540 | -0.2720 | 7.37689 |
| March | 299.00000 | 21.94880 | 37.38418 | -0.0936 | 5.90454 |
| April | 260.00000 | 22.67440 | 38.81631 | 0.13914 | 6.50055 |
| May | 286.00000 | 23.35203 | 42.76315 | -0.4533 | 10.44044 |
| June | 286.00000 | 23.32256 | 42.60231 | -0.4196 | 9.37199 |
| July | 260.00000 | 21.92564 | 49.62635 | -0.7851 | 18.67131 |
| August | 299.00000 | 21.82445 | 53.84637 | -0.7967 | 19.20052 |
| September | 260.00000 | 22.96109 | 49.01350 | -0.5206 | 11.93904 |
| October | 273.00000 | 22.64375 | 43.05889 | 0.15694 | 6.36036 |
| November | 273.00000 | 21.85549 | 42.16353 | -0.1017 | 6.30634 |
| December | 260.00000 | 21.31484 | 37.03928 | -0.3265 | 7.59537 |
| Annual Sum or Average | 3276.00000 | 22.21906 | 42.67196 | -0.3223 | 9.86316 |
| Minimum of Months | 247.00000 | 21.23184 | 37.03928 | -0.7967 | 5.90454 |
| Maximum of Months | 299.00000 | 23.35203 | 53.84637 | 0.15694 | 19.20052 |
Report: OccupantComfortDataSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.65252 | 38.46900 | -0.2486 | 6.96784 |
| February | 247.00000 | 22.09169 | 38.75628 | -0.1156 | 6.42237 |
| March | 299.00000 | 22.98485 | 37.79984 | 0.13967 | 6.01526 |
| April | 260.00000 | 23.59612 | 39.08817 | 0.35144 | 8.14971 |
| May | 286.00000 | 23.91289 | 43.05760 | -0.2637 | 6.81799 |
| June | 286.00000 | 23.96521 | 43.95001 | -0.1927 | 5.96175 |
| July | 260.00000 | 23.08841 | 49.13009 | -0.4462 | 9.92991 |
| August | 299.00000 | 22.99544 | 53.02593 | -0.4534 | 10.21692 |
| September | 260.00000 | 23.86163 | 49.69995 | -0.2260 | 6.58585 |
| October | 273.00000 | 23.58928 | 43.00686 | 0.37197 | 8.27088 |
| November | 273.00000 | 22.75970 | 42.45634 | 0.10795 | 6.43585 |
| December | 260.00000 | 21.86107 | 38.22033 | -0.1840 | 6.23787 |
| Annual Sum or Average | 3276.00000 | 23.04279 | 43.11459 | -0.0980 | 7.34029 |
| Minimum of Months | 247.00000 | 21.65252 | 37.79984 | -0.4534 | 5.96175 |
| Maximum of Months | 299.00000 | 23.96521 | 53.02593 | 0.37197 | 10.21692 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.94793 | 31.61701 | -0.1893 | 6.82628 |
| February | 247.00000 | 22.90014 | 30.98837 | 0.03726 | 6.11601 |
| March | 299.00000 | 24.40717 | 28.82160 | 0.38952 | 8.57576 |
| April | 260.00000 | 25.65970 | 29.16657 | 0.70730 | 16.15897 |
| May | 286.00000 | 26.43921 | 32.37718 | 0.34439 | 7.85708 |
| June | 286.00000 | 26.58929 | 33.13532 | 0.42650 | 8.98070 |
| July | 260.00000 | 25.65696 | 38.90870 | 0.20076 | 6.44055 |
| August | 299.00000 | 25.50893 | 42.47400 | 0.17807 | 6.41909 |
| September | 260.00000 | 26.27224 | 38.23234 | 0.33645 | 8.04261 |
| October | 273.00000 | 25.31886 | 33.35731 | 0.64915 | 14.43221 |
| November | 273.00000 | 23.74818 | 33.96105 | 0.26518 | 7.76914 |
| December | 260.00000 | 22.45821 | 30.80877 | -0.0709 | 5.64208 |
| Annual Sum or Average | 3276.00000 | 24.77006 | 33.68977 | 0.27547 | 8.59834 |
| Minimum of Months | 247.00000 | 21.94793 | 28.82160 | -0.1893 | 5.64208 |
| Maximum of Months | 299.00000 | 26.58929 | 42.47400 | 0.70730 | 16.15897 |
Report: OccupantComfortDataSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 19.21253 | 39.38805 | -0.7505 | 17.94988 |
| February | 247.00000 | 20.22051 | 38.53061 | -0.5124 | 12.08481 |
| March | 299.00000 | 21.98927 | 35.62154 | -0.1001 | 5.82632 |
| April | 260.00000 | 23.53836 | 35.48269 | 0.28349 | 7.89680 |
| May | 286.00000 | 24.92085 | 38.11177 | -0.0767 | 6.43206 |
| June | 286.00000 | 25.42171 | 37.28100 | 0.09902 | 6.21381 |
| July | 260.00000 | 24.76135 | 41.60985 | -0.0390 | 6.28217 |
| August | 299.00000 | 24.59208 | 45.50822 | -0.0678 | 6.60473 |
| September | 260.00000 | 24.76263 | 43.37849 | -0.0796 | 6.58731 |
| October | 273.00000 | 23.20490 | 40.31358 | 0.23101 | 6.95944 |
| November | 273.00000 | 21.37292 | 41.47216 | -0.2131 | 7.68327 |
| December | 260.00000 | 19.74180 | 38.45907 | -0.6279 | 13.94830 |
| Annual Sum or Average | 3276.00000 | 22.85229 | 39.60301 | -0.1498 | 8.62091 |
| Minimum of Months | 247.00000 | 19.21253 | 35.48269 | -0.7505 | 5.82632 |
| Maximum of Months | 299.00000 | 25.42171 | 45.50822 | 0.28349 | 17.94988 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 231.00000 | 21.08909 | 34.43017 | -0.4255 | 9.04203 |
| February | 209.00000 | 21.54478 | 34.66230 | -0.2676 | 7.54036 |
| March | 253.00000 | 22.55153 | 33.21378 | 0.01710 | 5.85492 |
| April | 220.00000 | 23.48888 | 33.66126 | 0.29904 | 7.65525 |
| May | 242.00000 | 23.89953 | 37.96747 | -0.3068 | 7.39810 |
| June | 242.00000 | 23.98521 | 39.27684 | -0.2119 | 6.13902 |
| July | 220.00000 | 23.88436 | 43.95178 | -0.2052 | 6.34567 |
| August | 253.00000 | 23.85296 | 47.38273 | -0.1881 | 6.36443 |
| September | 220.00000 | 23.91173 | 44.57037 | -0.2289 | 6.62748 |
| October | 231.00000 | 23.37122 | 38.07281 | 0.28901 | 7.38575 |
| November | 231.00000 | 22.00159 | 38.74536 | -0.0995 | 6.63112 |
| December | 220.00000 | 21.20981 | 34.21992 | -0.3710 | 8.22179 |
| Annual Sum or Average | 2772.00000 | 22.91950 | 38.39667 | -0.1409 | 7.07686 |
| Minimum of Months | 209.00000 | 21.08909 | 33.21378 | -0.4255 | 5.85492 |
| Maximum of Months | 253.00000 | 23.98521 | 47.38273 | 0.29904 | 9.04203 |
Report: OccupantComfortDataSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.41921 | 38.04115 | -0.2556 | 6.85293 |
| February | 247.00000 | 21.92093 | 38.30872 | -0.0912 | 6.05766 |
| March | 299.00000 | 22.93480 | 37.06286 | 0.19514 | 6.39496 |
| April | 260.00000 | 23.72111 | 37.49526 | 0.45221 | 9.72915 |
| May | 286.00000 | 23.91846 | 41.55128 | -0.1712 | 5.96757 |
| June | 286.00000 | 23.97372 | 42.53916 | -0.0995 | 5.40130 |
| July | 260.00000 | 23.86172 | 46.67188 | -0.1104 | 5.71367 |
| August | 299.00000 | 23.76071 | 50.56331 | -0.1330 | 6.07495 |
| September | 260.00000 | 23.83316 | 48.67579 | -0.1711 | 6.15514 |
| October | 273.00000 | 23.39033 | 42.58757 | 0.36812 | 8.32047 |
| November | 273.00000 | 22.29755 | 42.51661 | 0.05059 | 6.08801 |
| December | 260.00000 | 21.54293 | 37.92128 | -0.2044 | 6.25799 |
| Annual Sum or Average | 3276.00000 | 23.06568 | 42.04204 | -0.0139 | 6.56995 |
| Minimum of Months | 247.00000 | 21.41921 | 37.06286 | -0.2556 | 5.40130 |
| Maximum of Months | 299.00000 | 23.97372 | 50.56331 | 0.45221 | 9.72915 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 23.99464 | 45.98418 | 0.59422 | 12.64787 |
| February | 247.00000 | 23.99454 | 44.46702 | 0.62454 | 13.47490 |
| March | 299.00000 | 23.99419 | 40.83586 | 0.65387 | 14.23030 |
| April | 260.00000 | 23.99491 | 41.11286 | 0.71259 | 15.98495 |
| May | 286.00000 | 23.99662 | 44.29226 | 0.08445 | 5.55460 |
| June | 286.00000 | 23.99816 | 44.61316 | 0.11610 | 5.63835 |
| July | 260.00000 | 23.99960 | 48.21473 | 0.12789 | 5.71035 |
| August | 299.00000 | 23.99978 | 51.77341 | 0.14019 | 5.82139 |
| September | 260.00000 | 23.99796 | 49.42201 | 0.11081 | 5.64899 |
| October | 273.00000 | 23.99491 | 44.27289 | 0.70836 | 15.78723 |
| November | 273.00000 | 23.99433 | 46.43793 | 0.66110 | 14.45601 |
| December | 260.00000 | 23.99450 | 45.20230 | 0.60571 | 12.93014 |
| Annual Sum or Average | 3276.00000 | 23.99620 | 45.55730 | 0.42428 | 10.59388 |
| Minimum of Months | 247.00000 | 23.99419 | 40.83586 | 0.08445 | 5.55460 |
| Maximum of Months | 299.00000 | 23.99978 | 51.77341 | 0.71259 | 15.98495 |
Report: OccupantComfortDataSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 231.00000 | 21.19100 | 42.18574 | -0.2351 | 6.69957 |
| February | 209.00000 | 21.65747 | 42.31346 | -0.0934 | 6.75648 |
| March | 253.00000 | 22.15649 | 42.22100 | 0.08419 | 6.42300 |
| April | 220.00000 | 23.00147 | 43.00192 | 0.32945 | 8.68620 |
| May | 242.00000 | 23.63327 | 46.30111 | -0.2312 | 7.26026 |
| June | 242.00000 | 23.90504 | 45.96950 | -0.0948 | 5.57377 |
| July | 200.00000 | 23.74948 | 46.52168 | -0.1931 | 6.58267 |
| August | 230.00000 | 23.74280 | 50.17986 | -0.1795 | 6.64103 |
| September | 219.00000 | 23.82871 | 51.51672 | -0.1409 | 6.10484 |
| October | 231.00000 | 23.11777 | 47.17953 | 0.35665 | 8.71845 |
| November | 231.00000 | 21.85697 | 47.26935 | 0.02889 | 6.62633 |
| December | 220.00000 | 21.30538 | 42.18632 | -0.1856 | 6.31803 |
| Annual Sum or Average | 2728.00000 | 22.76294 | 45.55967 | -0.0445 | 6.86109 |
| Minimum of Months | 200.00000 | 21.19100 | 42.18574 | -0.2351 | 5.57377 |
| Maximum of Months | 253.00000 | 23.90504 | 51.51672 | 0.35665 | 8.71845 |
Report: OccupantComfortDataSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.47950 | 35.89118 | -0.3269 | 7.89311 |
| February | 247.00000 | 22.05955 | 35.82773 | -0.1608 | 6.94460 |
| March | 299.00000 | 23.27555 | 33.84774 | 0.16387 | 6.23207 |
| April | 260.00000 | 23.82256 | 34.40231 | 0.38001 | 8.43147 |
| May | 286.00000 | 23.98998 | 38.69938 | -0.2430 | 6.44892 |
| June | 286.00000 | 23.99909 | 39.24508 | -0.1743 | 5.75889 |
| July | 260.00000 | 23.91332 | 43.78210 | -0.2037 | 6.21222 |
| August | 299.00000 | 23.88018 | 47.40191 | -0.1951 | 6.24905 |
| September | 260.00000 | 23.97127 | 44.71911 | -0.2049 | 6.14550 |
| October | 273.00000 | 23.77197 | 38.52894 | 0.37708 | 8.27674 |
| November | 273.00000 | 22.81255 | 39.05703 | 0.07967 | 6.63100 |
| December | 260.00000 | 21.68305 | 35.62509 | -0.2603 | 7.03278 |
| Annual Sum or Average | 3276.00000 | 23.24056 | 38.95968 | -0.0635 | 6.83668 |
| Minimum of Months | 247.00000 | 21.47950 | 33.84774 | -0.3269 | 5.75889 |
| Maximum of Months | 299.00000 | 23.99909 | 47.40191 | 0.38001 | 8.43147 |
Report: OccupantComfortDataSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 20.98706 | 36.87009 | -0.4282 | 9.03335 |
| February | 247.00000 | 21.19360 | 37.70339 | -0.3299 | 7.72007 |
| March | 299.00000 | 22.10178 | 36.49562 | -0.0741 | 5.57588 |
| April | 260.00000 | 23.41466 | 36.41052 | 0.26314 | 6.99847 |
| May | 286.00000 | 23.96319 | 39.13280 | -0.3188 | 7.30734 |
| June | 286.00000 | 23.99423 | 39.50164 | -0.2679 | 6.58069 |
| July | 260.00000 | 23.91854 | 43.70215 | -0.2680 | 6.74106 |
| August | 299.00000 | 23.85190 | 47.51703 | -0.2757 | 6.93907 |
| September | 260.00000 | 23.91709 | 45.31453 | -0.3023 | 7.16025 |
| October | 273.00000 | 23.10820 | 41.15496 | 0.21314 | 6.51360 |
| November | 273.00000 | 21.67945 | 41.92181 | -0.1590 | 6.61429 |
| December | 260.00000 | 21.01208 | 36.95614 | -0.3962 | 8.38078 |
| Annual Sum or Average | 3276.00000 | 22.78251 | 40.25859 | -0.1950 | 7.10738 |
| Minimum of Months | 247.00000 | 20.98706 | 36.41052 | -0.4282 | 5.57588 |
| Maximum of Months | 299.00000 | 23.99423 | 47.51703 | 0.26314 | 9.03335 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 19.21040 | 36.48179 | -0.7965 | 20.90944 |
| February | 247.00000 | 19.71932 | 36.42446 | -0.6297 | 16.35177 |
| March | 299.00000 | 20.45911 | 35.46784 | -0.4064 | 9.73311 |
| April | 260.00000 | 21.09571 | 37.56002 | -0.1850 | 7.59758 |
| May | 286.00000 | 21.73772 | 42.87259 | -0.9113 | 25.04228 |
| June | 286.00000 | 22.28905 | 43.15467 | -0.7209 | 18.40904 |
| July | 260.00000 | 22.61807 | 47.62446 | -0.5886 | 14.92787 |
| August | 299.00000 | 22.87317 | 50.91551 | -0.4846 | 13.45744 |
| September | 260.00000 | 22.24843 | 49.05402 | -0.6878 | 18.53994 |
| October | 273.00000 | 21.18393 | 42.18873 | -0.1325 | 6.64282 |
| November | 273.00000 | 20.10926 | 41.40148 | -0.4847 | 12.14674 |
| December | 260.00000 | 19.37041 | 36.21026 | -0.7415 | 19.31795 |
| Annual Sum or Average | 3276.00000 | 21.09971 | 41.67448 | -0.5639 | 15.24342 |
| Minimum of Months | 247.00000 | 19.21040 | 35.46784 | -0.9113 | 6.64282 |
| Maximum of Months | 299.00000 | 22.87317 | 50.91551 | -0.1325 | 25.04228 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| BOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
| January | 0.574247E+11 | 0.00 | 371.92 | 354515.72 | 03-JAN-08:61 | 0.00 | 34.39 | 55.45 | 0.13 | 0.00 | 0.07 | 1.20 | 03-JAN-08:61 |
| February | 0.315179E+11 | 0.00 | 300.48 | 354515.72 | 01-FEB-08:61 | 0.00 | 33.04 | 51.11 | 0.08 | 0.00 | 0.04 | 1.20 | 01-FEB-08:61 |
| March | 0.121602E+11 | 0.00 | 311.51 | 354515.72 | 01-MAR-08:61 | 0.00 | 35.32 | 50.09 | 0.03 | 0.00 | 0.02 | 1.20 | 01-MAR-08:61 |
| April | 0.436801E+10 | 0.00 | 203.85 | 337393.40 | 18-APR-07:01 | 0.00 | 44.61 | 53.90 | 0.01 | 0.00 | 0.01 | 1.14 | 18-APR-07:01 |
| May | 0.207815E+10 | 0.00 | 129.17 | 199848.33 | 18-MAY-07:01 | 0.00 | 51.07 | 56.47 | 0.01 | 0.00 | 0.00 | 0.68 | 18-MAY-07:01 |
| June | 0.123366E+10 | 0.00 | 85.27 | 34751.70 | 14-JUN-07:01 | 0.00 | 52.07 | 55.63 | 0.00 | 0.00 | 0.00 | 0.12 | 14-JUN-07:01 |
| July | 0.112736E+10 | 0.00 | 61.57 | 210110.60 | 14-JUL-07:01 | 0.00 | 47.51 | 50.35 | 0.00 | 0.00 | 0.00 | 0.71 | 14-JUL-07:01 |
| August | 0.165369E+10 | 0.00 | 69.09 | 240736.81 | 18-AUG-07:01 | 0.00 | 43.30 | 47.02 | 0.00 | 0.00 | 0.00 | 0.81 | 18-AUG-07:01 |
| September | 0.133672E+10 | 0.00 | 92.18 | 147135.17 | 01-SEP-07:01 | 0.00 | 49.53 | 53.65 | 0.00 | 0.00 | 0.00 | 0.50 | 01-SEP-07:01 |
| October | 0.386659E+10 | 0.00 | 207.21 | 337248.88 | 30-OCT-07:01 | 0.00 | 46.14 | 55.52 | 0.01 | 0.00 | 0.00 | 1.14 | 30-OCT-07:01 |
| November | 0.179528E+11 | 0.00 | 296.73 | 354515.72 | 13-NOV-07:01 | 0.00 | 35.63 | 50.58 | 0.04 | 0.00 | 0.02 | 1.20 | 13-NOV-07:01 |
| December | 0.403493E+11 | 0.00 | 306.67 | 354515.72 | 01-DEC-07:11 | 0.00 | 33.38 | 49.80 | 0.09 | 0.00 | 0.05 | 1.20 | 01-DEC-07:11 |
| Annual Sum or Average | 0.175069E+12 | 0.00 | 2435.64 | 0.00 | 42.20 | 52.47 | 0.03 | 0.00 | 0.02 | ||||
| Minimum of Months | 0.112736E+10 | 0.00 | 61.57 | 34751.70 | 0.00 | 33.04 | 47.02 | 0.00 | 0.00 | 0.00 | 0.12 | ||
| Maximum of Months | 0.574247E+11 | 0.00 | 371.92 | 354515.72 | 0.00 | 52.07 | 56.47 | 0.13 | 0.00 | 0.07 | 1.20 |
Report: DXReportMonthly
For: VAV_POD_1 COOLING COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.169006E+10 | 0.505890E+09 | 9.17 | 0.162604E+10 | 64021697.99 | 0.00 | 0.75 | 27-FEB-15:02 | 0.00 | 01-FEB-00:10 | 127600.59 | 27-FEB-15:02 | 127600.59 | 27-FEB-15:02 | 16475.98 | 28-FEB-15:01 | 34836.85 | 27-FEB-15:02 | 0.00 |
| March | 0.178060E+10 | 0.559536E+09 | 21.95 | 0.153154E+10 | 0.249059E+09 | 0.00 | 0.46 | 14-MAR-14:02 | 0.00 | 01-MAR-00:10 | 72336.96 | 14-MAR-14:02 | 67854.69 | 14-MAR-14:02 | 21676.64 | 09-MAR-15:01 | 21333.10 | 14-MAR-14:02 | 0.00 |
| April | 0.192836E+11 | 0.523981E+10 | 62.26 | 0.188683E+11 | 0.415291E+09 | 0.00 | 1.00 | 26-APR-13:10 | 0.00 | 01-APR-00:05 | 334651.12 | 27-APR-15:00 | 317211.70 | 27-APR-15:00 | 26181.39 | 28-APR-13:00 | 84562.86 | 27-APR-15:00 | 0.00 |
| May | 0.487080E+11 | 0.133793E+11 | 154.43 | 0.460150E+11 | 0.269295E+10 | 0.00 | 1.00 | 03-MAY-14:02 | 0.00 | 01-MAY-00:10 | 301002.84 | 04-MAY-15:00 | 301002.84 | 04-MAY-15:00 | 40949.51 | 08-MAY-14:02 | 76367.93 | 04-MAY-15:00 | 0.00 |
| June | 0.872780E+11 | 0.241277E+11 | 263.67 | 0.833748E+11 | 0.390313E+10 | 0.00 | 1.00 | 09-JUN-12:05 | 0.00 | 01-JUN-00:03 | 270181.17 | 28-JUN-15:05 | 270181.17 | 28-JUN-15:05 | 74966.64 | 12-JUN-14:02 | 68572.02 | 28-JUN-15:05 | 0.00 |
| July | 0.117262E+12 | 0.318648E+11 | 298.27 | 0.107228E+12 | 0.100345E+11 | 0.00 | 1.00 | 07-JUL-14:05 | 0.00 | 01-JUL-00:03 | 354646.01 | 31-JUL-14:02 | 304477.90 | 24-JUL-14:02 | 81283.38 | 15-JUL-17:21 | 87832.53 | 31-JUL-14:02 | 0.00 |
| August | 0.153705E+12 | 0.408602E+11 | 318.87 | 0.139034E+12 | 0.146712E+11 | 0.00 | 1.00 | 06-AUG-15:21 | 0.00 | 01-AUG-00:03 | 377600.50 | 29-AUG-14:01 | 301141.09 | 10-AUG-15:25 | 89225.81 | 29-AUG-14:01 | 93819.93 | 29-AUG-14:01 | 0.00 |
| September | 0.696637E+11 | 0.190698E+11 | 203.67 | 0.620663E+11 | 0.759735E+10 | 0.00 | 1.00 | 08-SEP-14:02 | 0.00 | 01-SEP-00:10 | 316572.98 | 14-SEP-14:05 | 259667.51 | 12-SEP-14:05 | 95229.29 | 14-SEP-12:05 | 79845.82 | 14-SEP-14:05 | 0.00 |
| October | 0.110975E+11 | 0.321378E+10 | 62.62 | 0.108076E+11 | 0.289929E+09 | 0.00 | 1.00 | 04-OCT-14:00 | 0.00 | 01-OCT-00:10 | 208816.57 | 04-OCT-14:03 | 208816.57 | 04-OCT-14:03 | 38528.87 | 26-OCT-14:01 | 53034.47 | 04-OCT-14:03 | 0.00 |
| November | 0.434401E+09 | 0.122320E+09 | 2.49 | 0.322641E+09 | 0.111761E+09 | 0.00 | 0.73 | 04-NOV-13:56 | 0.00 | 01-NOV-00:05 | 123094.45 | 04-NOV-13:56 | 100840.74 | 04-NOV-13:56 | 45164.57 | 03-NOV-14:01 | 33811.32 | 04-NOV-13:56 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 |
| Annual Sum or Average | 0.510903E+12 | 0.138943E+12 | 1397.39 | 0.470874E+12 | 0.400291E+11 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.153705E+12 | 0.408602E+11 | 318.87 | 0.139034E+12 | 0.146712E+11 | 0.00 | 1.00 | 0.00 | 377600.50 | 317211.70 | 95229.29 | 93819.93 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_1:6 COOLING COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.100475E+09 | 25952124.27 | 18.63 | 66081726.60 | 34393497.38 | 0.00 | 1.00 | 03-JAN-06:01 | 0.00 | 01-JAN-00:05 | 29579.75 | 13-JAN-06:01 | 22255.36 | 17-JAN-06:01 | 12734.65 | 12-JAN-06:01 | 6797.24 | 03-JAN-06:01 | 0.00 | 01-JAN-00:05 |
| February | 0.241477E+09 | 62682721.68 | 43.73 | 0.187184E+09 | 54292734.89 | 0.00 | 1.00 | 01-FEB-06:01 | 0.00 | 01-FEB-00:10 | 29579.75 | 28-FEB-06:11 | 25455.66 | 13-FEB-06:01 | 13260.96 | 28-FEB-06:11 | 6797.24 | 01-FEB-06:01 | 0.00 | 01-FEB-00:10 |
| March | 0.306033E+09 | 80472230.93 | 77.17 | 0.213888E+09 | 92144736.51 | 0.00 | 1.00 | 01-MAR-06:01 | 0.00 | 01-MAR-00:10 | 29579.75 | 01-MAR-06:01 | 29579.75 | 18-MAR-15:43 | 15238.85 | 10-MAR-06:11 | 6797.24 | 01-MAR-06:01 | 0.00 | 01-MAR-00:10 |
| April | 0.164340E+10 | 0.405764E+09 | 111.94 | 0.139772E+10 | 0.245681E+09 | 0.00 | 1.00 | 01-APR-10:42 | 0.00 | 01-APR-00:05 | 30923.21 | 29-APR-14:32 | 30037.00 | 01-APR-13:42 | 14736.44 | 14-APR-05:11 | 7259.87 | 01-APR-13:42 | 0.00 | 01-APR-00:05 |
| May | 0.375333E+10 | 0.902875E+09 | 159.59 | 0.304217E+10 | 0.711159E+09 | 0.00 | 1.00 | 01-MAY-05:11 | 0.00 | 01-MAY-00:10 | 32098.19 | 06-MAY-12:34 | 29601.62 | 14-MAY-14:55 | 15213.83 | 06-MAY-22:52 | 7637.28 | 06-MAY-12:34 | 0.00 | 01-MAY-00:10 |
| June | 0.597693E+10 | 0.144896E+10 | 205.81 | 0.507060E+10 | 0.906336E+09 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:03 | 31225.86 | 11-JUN-11:43 | 30286.07 | 10-JUN-15:02 | 15177.29 | 12-JUN-05:42 | 7358.24 | 10-JUN-17:20 | 0.00 | 01-JUN-00:03 |
| July | 0.891923E+10 | 0.217596E+10 | 252.34 | 0.710305E+10 | 0.181618E+10 | 0.00 | 1.00 | 01-JUL-10:52 | 0.00 | 01-JUL-00:03 | 32524.85 | 15-JUL-17:45 | 29498.91 | 30-JUL-15:52 | 15680.45 | 25-JUL-05:32 | 8142.75 | 30-JUL-15:52 | 0.00 | 01-JUL-00:03 |
| August | 0.120843E+11 | 0.294243E+10 | 287.27 | 0.940278E+10 | 0.268151E+10 | 0.00 | 1.00 | 01-AUG-05:01 | 0.00 | 01-AUG-00:03 | 32394.28 | 26-AUG-16:53 | 28880.03 | 08-AUG-21:33 | 16897.93 | 02-AUG-05:11 | 7689.81 | 24-AUG-20:40 | 0.00 | 01-AUG-00:03 |
| September | 0.475492E+10 | 0.113908E+10 | 164.55 | 0.349157E+10 | 0.126335E+10 | 0.00 | 1.00 | 01-SEP-03:42 | 0.00 | 01-SEP-00:10 | 32590.10 | 23-SEP-13:57 | 28557.90 | 10-SEP-15:02 | 16927.91 | 25-SEP-05:01 | 7690.11 | 23-SEP-13:57 | 0.00 | 01-SEP-00:10 |
| October | 0.783097E+09 | 0.199801E+09 | 104.63 | 0.658211E+09 | 0.124885E+09 | 0.00 | 1.00 | 02-OCT-05:11 | 0.00 | 01-OCT-00:10 | 30432.49 | 08-OCT-13:52 | 23886.98 | 08-OCT-13:52 | 14126.15 | 06-OCT-05:11 | 7026.01 | 08-OCT-13:52 | 0.00 | 01-OCT-00:10 |
| November | 0.196915E+09 | 51315279.80 | 55.73 | 0.123866E+09 | 73049094.46 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:05 | 31519.16 | 04-NOV-13:42 | 25217.00 | 14-NOV-06:01 | 13978.13 | 27-NOV-06:11 | 7282.37 | 04-NOV-13:42 | 0.00 | 01-NOV-00:05 |
| December | 0.134985E+09 | 35689457.44 | 33.99 | 88810322.46 | 46175132.72 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 | 29579.75 | 05-DEC-06:01 | 23703.80 | 14-DEC-06:01 | 12068.86 | 29-DEC-06:01 | 6797.24 | 01-DEC-06:01 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.388951E+11 | 0.947098E+10 | 1515.40 | 0.308459E+11 | 0.804916E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.100475E+09 | 25952124.27 | 18.63 | 66081726.60 | 34393497.38 | 0.00 | 1.00 | 0.00 | 29579.75 | 22255.36 | 12068.86 | 6797.24 | 0.00 | |||||||
| Maximum of Months | 0.120843E+11 | 0.294243E+10 | 287.27 | 0.940278E+10 | 0.268151E+10 | 0.00 | 1.00 | 0.00 | 32590.10 | 30286.07 | 16927.91 | 8142.75 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:7 COOLING COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
| February | 48096315.45 | 13359319.98 | 2.83 | 44749561.69 | 3346753.76 | 0.00 | 0.43 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 | 10424.96 | 27-FEB-15:00 | 10074.94 | 27-FEB-15:00 | 455.23 | 27-FEB-14:30 | 2776.58 | 27-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 9260267.68 | 2721800.00 | 2.33 | 6964133.03 | 2296134.65 | 0.00 | 0.08 | 10-MAR-13:00 | 0.00 | 01-MAR-00:10 | 1871.31 | 10-MAR-13:00 | 1387.62 | 10-MAR-13:00 | 483.69 | 10-MAR-13:00 | 546.65 | 10-MAR-13:00 | 0.00 | 01-MAR-00:10 |
| April | 0.147392E+10 | 0.377052E+09 | 26.99 | 0.134848E+10 | 0.125444E+09 | 0.00 | 1.00 | 27-APR-11:50 | 0.00 | 01-APR-00:05 | 39677.50 | 27-APR-14:00 | 33454.26 | 27-APR-14:00 | 6223.24 | 27-APR-14:00 | 9832.12 | 27-APR-14:00 | 0.00 | 01-APR-00:05 |
| May | 0.330467E+10 | 0.833896E+09 | 74.92 | 0.275338E+10 | 0.551295E+09 | 0.00 | 1.00 | 04-MAY-13:20 | 0.00 | 01-MAY-00:10 | 56662.20 | 06-MAY-11:51 | 52681.33 | 14-MAY-14:43 | 17761.78 | 07-MAY-14:31 | 13781.61 | 06-MAY-11:51 | 0.00 | 01-MAY-00:10 |
| June | 0.729616E+10 | 0.184357E+10 | 163.35 | 0.627203E+10 | 0.102413E+10 | 0.00 | 1.00 | 10-JUN-13:43 | 0.00 | 01-JUN-00:03 | 55765.31 | 11-JUN-12:01 | 52270.93 | 10-JUN-13:43 | 27121.57 | 12-JUN-05:01 | 13532.47 | 10-JUN-16:51 | 0.00 | 01-JUN-00:03 |
| July | 0.583624E+10 | 0.155705E+10 | 153.56 | 0.495582E+10 | 0.880425E+09 | 0.00 | 1.00 | 10-JUL-05:01 | 0.00 | 01-JUL-00:03 | 55850.99 | 22-JUL-11:21 | 48023.92 | 29-JUL-15:42 | 27731.98 | 25-JUL-05:01 | 13602.20 | 29-JUL-15:42 | 0.00 | 01-JUL-00:03 |
| August | 0.101944E+11 | 0.270122E+10 | 188.54 | 0.873971E+10 | 0.145465E+10 | 0.00 | 1.00 | 06-AUG-16:12 | 0.00 | 01-AUG-00:03 | 55803.13 | 30-AUG-05:01 | 48794.57 | 06-AUG-16:12 | 28315.01 | 30-AUG-05:01 | 13678.49 | 06-AUG-16:12 | 0.00 | 01-AUG-00:03 |
| September | 0.583171E+10 | 0.144120E+10 | 106.38 | 0.426847E+10 | 0.156324E+10 | 0.00 | 1.00 | 10-SEP-13:42 | 0.00 | 01-SEP-00:10 | 58084.48 | 23-SEP-14:02 | 50255.12 | 10-SEP-14:52 | 22382.22 | 11-SEP-05:01 | 14121.58 | 23-SEP-14:02 | 0.00 | 01-SEP-00:10 |
| October | 0.405435E+09 | 0.108218E+09 | 18.49 | 0.391596E+09 | 13838387.96 | 0.00 | 0.70 | 04-OCT-14:00 | 0.00 | 01-OCT-00:10 | 18235.52 | 04-OCT-14:00 | 18235.52 | 04-OCT-14:00 | 1235.59 | 06-OCT-14:00 | 4494.59 | 04-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.343998E+11 | 0.887829E+10 | 737.40 | 0.287812E+11 | 0.561866E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.101944E+11 | 0.270122E+10 | 188.54 | 0.873971E+10 | 0.156324E+10 | 0.00 | 1.00 | 0.00 | 58084.48 | 52681.33 | 28315.01 | 14121.58 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.20 | 16.28 | 38.92 | 19.38 | 226.91 | 0.00 | 0.00 | 0.00 |
| February | 98.96 | 37.19 | 61.77 | 61.48 | 202.63 | 0.00 | 0.00 | 0.00 |
| March | 138.67 | 46.80 | 91.86 | 102.83 | 173.16 | 0.00 | 0.00 | 0.00 |
| April | 210.97 | 80.66 | 130.31 | 196.68 | 144.96 | 0.00 | 0.00 | 0.00 |
| May | 271.47 | 110.28 | 161.19 | 282.78 | 124.23 | 0.00 | 0.00 | 0.00 |
| June | 261.08 | 101.37 | 159.71 | 280.69 | 97.41 | 0.00 | 0.00 | 0.00 |
| July | 322.53 | 169.54 | 152.99 | 394.33 | 84.27 | 0.00 | 0.00 | 0.00 |
| August | 266.81 | 136.24 | 130.57 | 331.79 | 83.23 | 0.00 | 0.00 | 0.00 |
| September | 217.27 | 104.25 | 113.02 | 235.96 | 127.38 | 0.00 | 0.00 | 0.00 |
| October | 123.69 | 50.40 | 73.30 | 99.05 | 169.85 | 0.00 | 0.00 | 0.00 |
| November | 61.60 | 17.37 | 44.23 | 26.97 | 197.48 | 0.00 | 0.00 | 0.00 |
| December | 51.79 | 17.75 | 34.04 | 23.80 | 234.41 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 173.79 | 74.29 | 99.50 | 172.06 | 155.26 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.79 | 16.28 | 34.04 | 19.38 | 83.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 322.53 | 169.54 | 161.19 | 394.33 | 234.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 22.15 | 13.15 | 9.00 | 18.72 | 32.05 | 0.00 | 0.00 | 0.00 |
| February | 34.06 | 21.08 | 12.98 | 33.33 | 29.02 | 0.00 | 0.00 | 0.00 |
| March | 36.64 | 19.54 | 17.10 | 37.25 | 26.31 | 0.00 | 0.00 | 0.00 |
| April | 38.68 | 16.80 | 21.89 | 41.50 | 22.83 | 0.00 | 0.00 | 0.00 |
| May | 35.37 | 10.54 | 24.83 | 37.81 | 19.81 | 0.00 | 0.00 | 0.00 |
| June | 32.36 | 8.69 | 23.67 | 35.58 | 15.59 | 0.00 | 0.00 | 0.00 |
| July | 35.29 | 12.93 | 22.37 | 44.47 | 13.48 | 0.00 | 0.00 | 0.00 |
| August | 37.92 | 17.68 | 20.24 | 49.86 | 13.05 | 0.00 | 0.00 | 0.00 |
| September | 42.01 | 23.20 | 18.81 | 50.20 | 19.59 | 0.00 | 0.00 | 0.00 |
| October | 38.05 | 23.50 | 14.56 | 41.11 | 25.23 | 0.00 | 0.00 | 0.00 |
| November | 22.50 | 12.89 | 9.61 | 20.11 | 28.69 | 0.00 | 0.00 | 0.00 |
| December | 23.54 | 15.23 | 8.31 | 22.16 | 33.65 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 33.20 | 16.24 | 16.96 | 36.02 | 23.24 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 22.15 | 8.69 | 8.31 | 18.72 | 13.05 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 42.01 | 23.50 | 24.83 | 50.20 | 33.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 153.72 | 91.28 | 62.44 | 129.95 | 222.45 | 0.00 | 0.00 | 0.00 |
| February | 236.39 | 146.33 | 90.06 | 231.33 | 201.43 | 0.00 | 0.00 | 0.00 |
| March | 254.29 | 135.61 | 118.68 | 258.51 | 182.59 | 0.00 | 0.00 | 0.00 |
| April | 268.48 | 116.57 | 151.91 | 288.00 | 158.43 | 0.00 | 0.00 | 0.00 |
| May | 245.49 | 73.13 | 172.36 | 262.34 | 137.80 | 0.00 | 0.00 | 0.00 |
| June | 224.60 | 60.30 | 164.30 | 246.53 | 108.59 | 0.00 | 0.00 | 0.00 |
| July | 244.94 | 89.71 | 155.23 | 308.04 | 94.00 | 0.00 | 0.00 | 0.00 |
| August | 263.15 | 122.71 | 140.44 | 345.90 | 90.70 | 0.00 | 0.00 | 0.00 |
| September | 291.56 | 161.01 | 130.55 | 348.43 | 135.93 | 0.00 | 0.00 | 0.00 |
| October | 264.11 | 163.07 | 101.04 | 285.28 | 175.10 | 0.00 | 0.00 | 0.00 |
| November | 156.15 | 89.49 | 66.66 | 139.54 | 199.09 | 0.00 | 0.00 | 0.00 |
| December | 163.38 | 105.73 | 57.65 | 153.79 | 233.54 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 230.42 | 112.70 | 117.72 | 249.89 | 161.43 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 153.72 | 60.30 | 57.65 | 129.95 | 90.70 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 291.56 | 163.07 | 172.36 | 348.43 | 233.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 282.46 | 167.72 | 114.73 | 233.41 | 437.76 | 0.00 | 0.00 | 0.00 |
| February | 434.37 | 268.88 | 165.49 | 417.08 | 400.19 | 0.00 | 0.00 | 0.00 |
| March | 467.26 | 249.19 | 218.08 | 467.05 | 368.00 | 0.00 | 0.00 | 0.00 |
| April | 493.34 | 214.21 | 279.13 | 521.72 | 315.66 | 0.00 | 0.00 | 0.00 |
| May | 451.10 | 134.39 | 316.71 | 479.26 | 268.76 | 0.00 | 0.00 | 0.00 |
| June | 412.71 | 110.81 | 301.90 | 451.93 | 209.73 | 0.00 | 0.00 | 0.00 |
| July | 450.08 | 164.84 | 285.23 | 572.89 | 172.02 | 0.00 | 0.00 | 0.00 |
| August | 483.55 | 225.49 | 258.06 | 640.00 | 168.23 | 0.00 | 0.00 | 0.00 |
| September | 535.75 | 295.86 | 239.89 | 639.51 | 261.46 | 0.00 | 0.00 | 0.00 |
| October | 485.30 | 299.64 | 185.66 | 518.84 | 348.47 | 0.00 | 0.00 | 0.00 |
| November | 286.93 | 164.43 | 122.49 | 250.47 | 396.76 | 0.00 | 0.00 | 0.00 |
| December | 300.21 | 194.28 | 105.93 | 277.11 | 463.64 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 423.40 | 207.09 | 216.31 | 455.98 | 317.11 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 282.46 | 110.81 | 105.93 | 233.41 | 168.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 535.75 | 299.64 | 316.71 | 640.00 | 463.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 282.46 | 167.72 | 114.73 | 233.41 | 437.76 | 0.00 | 0.00 | 0.00 |
| February | 434.37 | 268.88 | 165.49 | 417.08 | 400.19 | 0.00 | 0.00 | 0.00 |
| March | 467.26 | 249.19 | 218.08 | 467.05 | 368.00 | 0.00 | 0.00 | 0.00 |
| April | 493.34 | 214.21 | 279.13 | 521.72 | 315.66 | 0.00 | 0.00 | 0.00 |
| May | 451.10 | 134.39 | 316.71 | 479.26 | 268.76 | 0.00 | 0.00 | 0.00 |
| June | 412.71 | 110.81 | 301.90 | 451.93 | 209.73 | 0.00 | 0.00 | 0.00 |
| July | 450.08 | 164.84 | 285.23 | 572.89 | 172.02 | 0.00 | 0.00 | 0.00 |
| August | 483.55 | 225.49 | 258.06 | 640.00 | 168.23 | 0.00 | 0.00 | 0.00 |
| September | 535.75 | 295.86 | 239.89 | 639.51 | 261.46 | 0.00 | 0.00 | 0.00 |
| October | 485.30 | 299.64 | 185.66 | 518.84 | 348.47 | 0.00 | 0.00 | 0.00 |
| November | 286.93 | 164.43 | 122.49 | 250.47 | 396.76 | 0.00 | 0.00 | 0.00 |
| December | 300.21 | 194.28 | 105.93 | 277.11 | 463.64 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 423.40 | 207.09 | 216.31 | 455.98 | 317.11 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 282.46 | 110.81 | 105.93 | 233.41 | 168.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 535.75 | 299.64 | 316.71 | 640.00 | 463.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 282.45 | 167.72 | 114.73 | 233.41 | 437.75 | 0.00 | 0.00 | 0.00 |
| February | 434.37 | 268.88 | 165.49 | 417.07 | 400.18 | 0.00 | 0.00 | 0.00 |
| March | 467.25 | 249.18 | 218.07 | 467.04 | 367.99 | 0.00 | 0.00 | 0.00 |
| April | 493.33 | 214.20 | 279.13 | 521.71 | 315.66 | 0.00 | 0.00 | 0.00 |
| May | 451.09 | 134.38 | 316.70 | 479.25 | 268.76 | 0.00 | 0.00 | 0.00 |
| June | 412.70 | 110.80 | 301.90 | 451.92 | 209.72 | 0.00 | 0.00 | 0.00 |
| July | 450.07 | 164.84 | 285.23 | 572.88 | 172.01 | 0.00 | 0.00 | 0.00 |
| August | 483.54 | 225.48 | 258.06 | 639.99 | 168.23 | 0.00 | 0.00 | 0.00 |
| September | 535.74 | 295.86 | 239.89 | 639.49 | 261.46 | 0.00 | 0.00 | 0.00 |
| October | 485.29 | 299.63 | 185.66 | 518.83 | 348.47 | 0.00 | 0.00 | 0.00 |
| November | 286.92 | 164.43 | 122.49 | 250.46 | 396.75 | 0.00 | 0.00 | 0.00 |
| December | 300.20 | 194.27 | 105.93 | 277.11 | 463.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 423.40 | 207.09 | 216.31 | 455.97 | 317.11 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 282.45 | 110.80 | 105.93 | 233.41 | 168.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 535.74 | 299.63 | 316.70 | 639.99 | 463.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 18.40 | 5.43 | 12.97 | 6.35 | 82.79 | 0.00 | 0.00 | 0.00 |
| February | 32.99 | 12.40 | 20.59 | 20.48 | 73.50 | 0.00 | 0.00 | 0.00 |
| March | 46.22 | 15.60 | 30.62 | 34.22 | 63.19 | 0.00 | 0.00 | 0.00 |
| April | 70.32 | 26.89 | 43.44 | 64.92 | 53.03 | 0.00 | 0.00 | 0.00 |
| May | 90.49 | 36.76 | 53.73 | 93.10 | 45.33 | 0.00 | 0.00 | 0.00 |
| June | 87.03 | 33.79 | 53.24 | 92.25 | 35.21 | 0.00 | 0.00 | 0.00 |
| July | 107.51 | 56.51 | 51.00 | 131.82 | 28.59 | 0.00 | 0.00 | 0.00 |
| August | 88.94 | 45.41 | 43.52 | 111.39 | 27.79 | 0.00 | 0.00 | 0.00 |
| September | 72.42 | 34.75 | 37.67 | 79.38 | 43.60 | 0.00 | 0.00 | 0.00 |
| October | 41.23 | 16.80 | 24.43 | 33.35 | 60.33 | 0.00 | 0.00 | 0.00 |
| November | 20.53 | 5.79 | 14.74 | 9.06 | 71.28 | 0.00 | 0.00 | 0.00 |
| December | 17.26 | 5.92 | 11.35 | 8.07 | 85.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 57.93 | 24.76 | 33.17 | 57.29 | 55.71 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 17.26 | 5.43 | 11.35 | 6.35 | 27.79 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 107.51 | 56.51 | 53.73 | 131.82 | 85.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.20 | 16.28 | 38.92 | 21.31 | 220.91 | 0.00 | 0.00 | 0.00 |
| February | 98.96 | 37.19 | 61.77 | 66.22 | 193.05 | 0.00 | 0.00 | 0.00 |
| March | 138.67 | 46.80 | 91.86 | 110.61 | 162.00 | 0.00 | 0.00 | 0.00 |
| April | 210.97 | 80.66 | 130.31 | 205.46 | 135.78 | 0.00 | 0.00 | 0.00 |
| May | 271.47 | 110.28 | 161.19 | 288.98 | 118.90 | 0.00 | 0.00 | 0.00 |
| June | 261.08 | 101.37 | 159.71 | 285.82 | 93.93 | 0.00 | 0.00 | 0.00 |
| July | 322.53 | 169.54 | 152.99 | 403.12 | 78.75 | 0.00 | 0.00 | 0.00 |
| August | 266.81 | 136.24 | 130.57 | 341.72 | 75.71 | 0.00 | 0.00 | 0.00 |
| September | 217.27 | 104.25 | 113.02 | 244.95 | 116.55 | 0.00 | 0.00 | 0.00 |
| October | 123.69 | 50.40 | 73.30 | 106.60 | 156.34 | 0.00 | 0.00 | 0.00 |
| November | 61.60 | 17.37 | 44.23 | 29.90 | 188.11 | 0.00 | 0.00 | 0.00 |
| December | 51.79 | 17.75 | 34.04 | 26.34 | 225.97 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 173.79 | 74.29 | 99.50 | 178.35 | 146.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.79 | 16.28 | 34.04 | 21.31 | 75.71 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 322.53 | 169.54 | 161.19 | 403.12 | 225.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.10 | 0.00 | 4.10 | 0.03 | 35.67 | 0.00 | 0.00 | 0.00 |
| February | 6.30 | 0.00 | 6.30 | 0.69 | 31.95 | 0.00 | 0.00 | 0.00 |
| March | 9.24 | 0.00 | 9.24 | 2.06 | 25.96 | 0.00 | 0.00 | 0.00 |
| April | 12.93 | 0.05 | 12.88 | 5.84 | 21.06 | 0.00 | 0.00 | 0.00 |
| May | 16.90 | 0.55 | 16.35 | 10.38 | 17.65 | 0.00 | 0.00 | 0.00 |
| June | 17.62 | 1.31 | 16.31 | 12.90 | 13.50 | 0.00 | 0.00 | 0.00 |
| July | 16.92 | 1.51 | 15.41 | 16.49 | 11.27 | 0.00 | 0.00 | 0.00 |
| August | 13.53 | 0.39 | 13.14 | 14.04 | 10.70 | 0.00 | 0.00 | 0.00 |
| September | 10.37 | 0.00 | 10.37 | 5.83 | 17.90 | 0.00 | 0.00 | 0.00 |
| October | 7.16 | 0.00 | 7.16 | 1.47 | 24.59 | 0.00 | 0.00 | 0.00 |
| November | 4.65 | 0.00 | 4.65 | 0.20 | 30.31 | 0.00 | 0.00 | 0.00 |
| December | 3.43 | 0.00 | 3.43 | 0.01 | 36.03 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 10.28 | 0.32 | 9.96 | 5.87 | 23.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3.43 | 0.00 | 3.43 | 0.01 | 10.70 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 17.62 | 1.51 | 16.35 | 16.49 | 36.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 29.96 | 0.00 | 29.96 | 0.31 | 246.85 | 0.00 | 0.00 | 0.00 |
| February | 46.13 | 0.00 | 46.13 | 5.60 | 220.33 | 0.00 | 0.00 | 0.00 |
| March | 67.78 | 0.00 | 67.78 | 17.31 | 179.45 | 0.00 | 0.00 | 0.00 |
| April | 95.06 | 0.32 | 94.74 | 46.23 | 145.89 | 0.00 | 0.00 | 0.00 |
| May | 123.65 | 3.85 | 119.79 | 79.52 | 122.73 | 0.00 | 0.00 | 0.00 |
| June | 129.04 | 9.12 | 119.92 | 97.76 | 94.20 | 0.00 | 0.00 | 0.00 |
| July | 123.55 | 10.45 | 113.10 | 121.92 | 78.85 | 0.00 | 0.00 | 0.00 |
| August | 99.24 | 2.70 | 96.54 | 103.89 | 74.99 | 0.00 | 0.00 | 0.00 |
| September | 76.46 | 0.02 | 76.45 | 45.78 | 124.64 | 0.00 | 0.00 | 0.00 |
| October | 52.70 | 0.00 | 52.70 | 12.62 | 170.09 | 0.00 | 0.00 | 0.00 |
| November | 33.94 | 0.00 | 33.94 | 1.80 | 209.68 | 0.00 | 0.00 | 0.00 |
| December | 25.12 | 0.00 | 25.12 | 0.13 | 249.50 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 75.37 | 2.22 | 73.14 | 44.69 | 159.45 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.12 | 0.00 | 25.12 | 0.13 | 74.99 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.04 | 10.45 | 119.92 | 121.92 | 249.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 49.63 | 0.00 | 49.63 | 0.03 | 486.08 | 0.00 | 0.00 | 0.00 |
| February | 76.18 | 0.00 | 76.18 | 6.24 | 440.68 | 0.00 | 0.00 | 0.00 |
| March | 111.88 | 0.00 | 111.88 | 17.96 | 365.39 | 0.00 | 0.00 | 0.00 |
| April | 155.44 | 0.22 | 155.23 | 60.83 | 295.84 | 0.00 | 0.00 | 0.00 |
| May | 201.09 | 4.50 | 196.60 | 117.07 | 246.51 | 0.00 | 0.00 | 0.00 |
| June | 206.14 | 11.06 | 195.08 | 144.01 | 185.83 | 0.00 | 0.00 | 0.00 |
| July | 197.43 | 12.34 | 185.09 | 198.44 | 145.89 | 0.00 | 0.00 | 0.00 |
| August | 160.85 | 2.65 | 158.20 | 175.86 | 138.39 | 0.00 | 0.00 | 0.00 |
| September | 125.58 | 0.02 | 125.56 | 68.59 | 236.52 | 0.00 | 0.00 | 0.00 |
| October | 86.66 | 0.00 | 86.66 | 13.22 | 340.83 | 0.00 | 0.00 | 0.00 |
| November | 56.26 | 0.00 | 56.26 | 1.43 | 421.24 | 0.00 | 0.00 | 0.00 |
| December | 41.36 | 0.00 | 41.36 | 0.05 | 496.99 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 122.61 | 2.58 | 120.02 | 67.46 | 316.01 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41.36 | 0.00 | 41.36 | 0.03 | 138.39 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 206.14 | 12.34 | 196.60 | 198.44 | 496.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 52.36 | 0.00 | 52.36 | 0.10 | 485.40 | 0.00 | 0.00 | 0.00 |
| February | 80.33 | 0.00 | 80.33 | 7.34 | 439.26 | 0.00 | 0.00 | 0.00 |
| March | 117.89 | 0.00 | 117.89 | 21.62 | 363.94 | 0.00 | 0.00 | 0.00 |
| April | 164.51 | 0.46 | 164.05 | 68.23 | 293.53 | 0.00 | 0.00 | 0.00 |
| May | 213.79 | 6.03 | 207.76 | 128.74 | 242.62 | 0.00 | 0.00 | 0.00 |
| June | 221.64 | 14.73 | 206.91 | 161.37 | 183.29 | 0.00 | 0.00 | 0.00 |
| July | 210.99 | 15.58 | 195.41 | 213.79 | 144.20 | 0.00 | 0.00 | 0.00 |
| August | 171.21 | 4.10 | 167.11 | 185.23 | 135.82 | 0.00 | 0.00 | 0.00 |
| September | 132.24 | 0.02 | 132.22 | 74.94 | 237.23 | 0.00 | 0.00 | 0.00 |
| October | 91.37 | 0.00 | 91.37 | 15.88 | 340.26 | 0.00 | 0.00 | 0.00 |
| November | 59.33 | 0.00 | 59.33 | 1.79 | 420.20 | 0.00 | 0.00 | 0.00 |
| December | 43.70 | 0.00 | 43.70 | 0.07 | 497.03 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 130.20 | 3.43 | 126.76 | 73.76 | 314.56 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 43.70 | 0.00 | 43.70 | 0.07 | 135.82 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 221.64 | 15.58 | 207.76 | 213.79 | 497.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 52.37 | 0.00 | 52.37 | 0.10 | 485.38 | 0.00 | 0.00 | 0.00 |
| February | 80.35 | 0.00 | 80.35 | 7.35 | 439.24 | 0.00 | 0.00 | 0.00 |
| March | 117.92 | 0.00 | 117.92 | 21.64 | 363.93 | 0.00 | 0.00 | 0.00 |
| April | 164.94 | 0.59 | 164.36 | 68.33 | 292.91 | 0.00 | 0.00 | 0.00 |
| May | 214.79 | 6.55 | 208.24 | 129.10 | 241.44 | 0.00 | 0.00 | 0.00 |
| June | 222.48 | 15.22 | 207.26 | 161.75 | 182.44 | 0.00 | 0.00 | 0.00 |
| July | 212.78 | 16.86 | 195.92 | 215.24 | 142.88 | 0.00 | 0.00 | 0.00 |
| August | 172.58 | 4.89 | 167.69 | 186.74 | 135.05 | 0.00 | 0.00 | 0.00 |
| September | 132.31 | 0.03 | 132.29 | 74.99 | 237.17 | 0.00 | 0.00 | 0.00 |
| October | 91.40 | 0.00 | 91.40 | 15.90 | 340.25 | 0.00 | 0.00 | 0.00 |
| November | 59.35 | 0.00 | 59.35 | 1.79 | 420.19 | 0.00 | 0.00 | 0.00 |
| December | 43.71 | 0.00 | 43.71 | 0.07 | 497.02 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 130.67 | 3.70 | 126.96 | 74.09 | 314.15 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 43.71 | 0.00 | 43.71 | 0.07 | 135.05 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 222.48 | 16.86 | 208.24 | 215.24 | 497.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.20 | 16.28 | 38.92 | 19.56 | 226.33 | 0.00 | 0.00 | 0.00 |
| February | 98.96 | 37.19 | 61.77 | 61.63 | 202.49 | 0.00 | 0.00 | 0.00 |
| March | 138.67 | 46.80 | 91.86 | 103.13 | 172.91 | 0.00 | 0.00 | 0.00 |
| April | 210.97 | 80.66 | 130.31 | 197.26 | 144.48 | 0.00 | 0.00 | 0.00 |
| May | 271.47 | 110.28 | 161.19 | 283.48 | 123.73 | 0.00 | 0.00 | 0.00 |
| June | 261.08 | 101.37 | 159.71 | 281.47 | 96.92 | 0.00 | 0.00 | 0.00 |
| July | 322.53 | 169.54 | 152.99 | 395.34 | 83.63 | 0.00 | 0.00 | 0.00 |
| August | 266.81 | 136.24 | 130.57 | 332.46 | 82.83 | 0.00 | 0.00 | 0.00 |
| September | 217.27 | 104.25 | 113.02 | 236.36 | 127.09 | 0.00 | 0.00 | 0.00 |
| October | 123.69 | 50.40 | 73.30 | 99.28 | 169.63 | 0.00 | 0.00 | 0.00 |
| November | 61.60 | 17.37 | 44.23 | 27.12 | 197.13 | 0.00 | 0.00 | 0.00 |
| December | 51.79 | 17.75 | 34.04 | 24.16 | 233.02 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 173.79 | 74.29 | 99.50 | 172.53 | 154.77 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.79 | 16.28 | 34.04 | 19.56 | 82.83 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 322.53 | 169.54 | 161.19 | 395.34 | 233.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 20.94 | 12.70 | 8.25 | 17.92 | 32.23 | 0.00 | 0.00 | 0.00 |
| February | 33.03 | 21.00 | 12.03 | 32.43 | 28.87 | 0.00 | 0.00 | 0.00 |
| March | 35.29 | 19.52 | 15.76 | 35.87 | 26.08 | 0.00 | 0.00 | 0.00 |
| April | 36.73 | 16.80 | 19.94 | 39.37 | 22.63 | 0.00 | 0.00 | 0.00 |
| May | 33.07 | 10.54 | 22.53 | 35.24 | 19.66 | 0.00 | 0.00 | 0.00 |
| June | 29.91 | 8.69 | 21.22 | 32.83 | 15.42 | 0.00 | 0.00 | 0.00 |
| July | 33.06 | 12.93 | 20.14 | 42.01 | 13.19 | 0.00 | 0.00 | 0.00 |
| August | 35.98 | 17.68 | 18.30 | 47.72 | 12.72 | 0.00 | 0.00 | 0.00 |
| September | 40.37 | 23.20 | 17.17 | 48.36 | 19.21 | 0.00 | 0.00 | 0.00 |
| October | 36.89 | 23.45 | 13.44 | 39.94 | 24.98 | 0.00 | 0.00 | 0.00 |
| November | 21.57 | 12.69 | 8.88 | 19.42 | 28.68 | 0.00 | 0.00 | 0.00 |
| December | 21.66 | 14.22 | 7.44 | 20.70 | 33.92 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 31.52 | 16.09 | 15.44 | 34.33 | 23.10 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.94 | 8.69 | 7.44 | 17.92 | 12.72 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 40.37 | 23.45 | 22.53 | 48.36 | 33.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 142.93 | 87.67 | 55.27 | 122.12 | 222.83 | 0.00 | 0.00 | 0.00 |
| February | 226.25 | 145.77 | 80.48 | 221.99 | 199.32 | 0.00 | 0.00 | 0.00 |
| March | 240.40 | 135.49 | 104.92 | 244.21 | 180.39 | 0.00 | 0.00 | 0.00 |
| April | 248.34 | 116.57 | 131.76 | 265.83 | 156.70 | 0.00 | 0.00 | 0.00 |
| May | 221.72 | 73.13 | 148.59 | 235.60 | 136.68 | 0.00 | 0.00 | 0.00 |
| June | 199.29 | 60.30 | 138.99 | 218.04 | 107.33 | 0.00 | 0.00 | 0.00 |
| July | 221.93 | 89.71 | 132.22 | 282.39 | 91.56 | 0.00 | 0.00 | 0.00 |
| August | 243.17 | 122.71 | 120.46 | 323.58 | 87.54 | 0.00 | 0.00 | 0.00 |
| September | 274.61 | 160.99 | 113.62 | 329.23 | 132.27 | 0.00 | 0.00 | 0.00 |
| October | 252.36 | 162.76 | 89.60 | 273.28 | 172.37 | 0.00 | 0.00 | 0.00 |
| November | 147.54 | 88.05 | 59.49 | 132.82 | 198.17 | 0.00 | 0.00 | 0.00 |
| December | 146.25 | 96.86 | 49.38 | 139.04 | 234.38 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 213.59 | 111.44 | 102.14 | 232.38 | 159.76 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 142.93 | 60.30 | 49.38 | 122.12 | 87.54 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 274.61 | 162.76 | 148.59 | 329.23 | 234.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 253.36 | 155.70 | 97.66 | 213.94 | 444.90 | 0.00 | 0.00 | 0.00 |
| February | 412.55 | 267.35 | 145.19 | 397.72 | 397.25 | 0.00 | 0.00 | 0.00 |
| March | 438.17 | 248.87 | 189.30 | 437.63 | 364.75 | 0.00 | 0.00 | 0.00 |
| April | 451.28 | 214.21 | 237.07 | 475.46 | 313.40 | 0.00 | 0.00 | 0.00 |
| May | 401.46 | 134.39 | 267.07 | 423.33 | 267.69 | 0.00 | 0.00 | 0.00 |
| June | 359.86 | 110.81 | 249.06 | 392.63 | 208.09 | 0.00 | 0.00 | 0.00 |
| July | 402.03 | 164.84 | 237.19 | 519.26 | 167.05 | 0.00 | 0.00 | 0.00 |
| August | 441.83 | 225.49 | 216.34 | 593.75 | 161.47 | 0.00 | 0.00 | 0.00 |
| September | 500.37 | 295.82 | 204.55 | 599.70 | 254.11 | 0.00 | 0.00 | 0.00 |
| October | 459.86 | 298.30 | 161.56 | 493.39 | 343.91 | 0.00 | 0.00 | 0.00 |
| November | 266.09 | 159.83 | 106.26 | 235.26 | 398.17 | 0.00 | 0.00 | 0.00 |
| December | 254.18 | 168.26 | 85.92 | 240.09 | 473.73 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 386.46 | 203.23 | 183.23 | 418.60 | 315.79 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 253.36 | 110.81 | 85.92 | 213.94 | 161.47 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 500.37 | 298.30 | 267.07 | 599.70 | 473.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 253.16 | 155.59 | 97.58 | 213.93 | 445.16 | 0.00 | 0.00 | 0.00 |
| February | 411.30 | 266.69 | 144.61 | 397.65 | 399.12 | 0.00 | 0.00 | 0.00 |
| March | 437.84 | 248.71 | 189.13 | 437.54 | 365.18 | 0.00 | 0.00 | 0.00 |
| April | 451.22 | 214.21 | 237.02 | 475.40 | 313.40 | 0.00 | 0.00 | 0.00 |
| May | 401.40 | 134.39 | 267.01 | 423.26 | 267.69 | 0.00 | 0.00 | 0.00 |
| June | 359.79 | 110.81 | 248.99 | 392.56 | 208.09 | 0.00 | 0.00 | 0.00 |
| July | 401.97 | 164.84 | 237.13 | 519.19 | 167.05 | 0.00 | 0.00 | 0.00 |
| August | 441.77 | 225.49 | 216.29 | 593.68 | 161.46 | 0.00 | 0.00 | 0.00 |
| September | 500.23 | 295.76 | 204.47 | 599.59 | 254.22 | 0.00 | 0.00 | 0.00 |
| October | 459.11 | 297.86 | 161.25 | 493.25 | 345.00 | 0.00 | 0.00 | 0.00 |
| November | 265.36 | 159.39 | 105.97 | 235.12 | 399.14 | 0.00 | 0.00 | 0.00 |
| December | 254.05 | 168.17 | 85.87 | 240.08 | 473.89 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 386.15 | 203.06 | 183.08 | 418.53 | 316.19 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 253.16 | 110.81 | 85.87 | 213.93 | 161.46 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 500.23 | 297.86 | 267.01 | 599.59 | 473.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 237.18 | 145.82 | 91.36 | 196.15 | 446.80 | 0.00 | 0.00 | 0.00 |
| February | 383.44 | 248.42 | 135.02 | 365.14 | 403.16 | 0.00 | 0.00 | 0.00 |
| March | 414.42 | 235.74 | 178.68 | 410.07 | 369.04 | 0.00 | 0.00 | 0.00 |
| April | 432.97 | 206.99 | 225.98 | 451.97 | 314.19 | 0.00 | 0.00 | 0.00 |
| May | 387.00 | 131.42 | 255.57 | 405.38 | 268.02 | 0.00 | 0.00 | 0.00 |
| June | 346.51 | 108.46 | 238.05 | 376.13 | 208.11 | 0.00 | 0.00 | 0.00 |
| July | 388.90 | 161.49 | 227.41 | 502.28 | 166.27 | 0.00 | 0.00 | 0.00 |
| August | 425.96 | 219.13 | 206.83 | 571.97 | 160.20 | 0.00 | 0.00 | 0.00 |
| September | 478.62 | 284.07 | 194.55 | 570.71 | 254.66 | 0.00 | 0.00 | 0.00 |
| October | 429.50 | 278.13 | 151.37 | 457.22 | 349.08 | 0.00 | 0.00 | 0.00 |
| November | 247.02 | 147.83 | 99.19 | 214.10 | 401.13 | 0.00 | 0.00 | 0.00 |
| December | 237.53 | 156.97 | 80.56 | 220.54 | 474.24 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 367.19 | 193.33 | 173.86 | 395.30 | 317.46 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 237.18 | 108.46 | 80.56 | 196.15 | 160.20 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 478.62 | 284.07 | 255.57 | 571.97 | 474.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 18.40 | 5.43 | 12.97 | 6.37 | 82.67 | 0.00 | 0.00 | 0.00 |
| February | 32.99 | 12.40 | 20.59 | 20.50 | 73.48 | 0.00 | 0.00 | 0.00 |
| March | 46.22 | 15.60 | 30.62 | 34.25 | 63.16 | 0.00 | 0.00 | 0.00 |
| April | 70.32 | 26.89 | 43.44 | 64.96 | 52.98 | 0.00 | 0.00 | 0.00 |
| May | 90.49 | 36.76 | 53.73 | 93.14 | 45.29 | 0.00 | 0.00 | 0.00 |
| June | 87.03 | 33.79 | 53.24 | 92.31 | 35.15 | 0.00 | 0.00 | 0.00 |
| July | 107.51 | 56.51 | 51.00 | 131.96 | 28.47 | 0.00 | 0.00 | 0.00 |
| August | 88.94 | 45.41 | 43.52 | 111.49 | 27.69 | 0.00 | 0.00 | 0.00 |
| September | 72.42 | 34.75 | 37.67 | 79.43 | 43.53 | 0.00 | 0.00 | 0.00 |
| October | 41.23 | 16.80 | 24.43 | 33.38 | 60.29 | 0.00 | 0.00 | 0.00 |
| November | 20.53 | 5.79 | 14.74 | 9.07 | 71.21 | 0.00 | 0.00 | 0.00 |
| December | 17.26 | 5.92 | 11.35 | 8.12 | 84.73 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 57.93 | 24.76 | 33.17 | 57.33 | 55.63 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 17.26 | 5.43 | 11.35 | 6.37 | 27.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 107.51 | 56.51 | 53.73 | 131.96 | 84.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.20 | 16.28 | 38.92 | 21.32 | 220.85 | 0.00 | 0.00 | 0.00 |
| February | 98.96 | 37.19 | 61.77 | 66.22 | 193.04 | 0.00 | 0.00 | 0.00 |
| March | 138.67 | 46.80 | 91.86 | 110.60 | 161.99 | 0.00 | 0.00 | 0.00 |
| April | 210.97 | 80.66 | 130.31 | 205.43 | 135.78 | 0.00 | 0.00 | 0.00 |
| May | 271.47 | 110.28 | 161.19 | 288.94 | 118.91 | 0.00 | 0.00 | 0.00 |
| June | 261.08 | 101.37 | 159.71 | 285.78 | 93.94 | 0.00 | 0.00 | 0.00 |
| July | 322.53 | 169.54 | 152.99 | 403.13 | 78.70 | 0.00 | 0.00 | 0.00 |
| August | 266.81 | 136.24 | 130.57 | 341.73 | 75.66 | 0.00 | 0.00 | 0.00 |
| September | 217.27 | 104.25 | 113.02 | 244.95 | 116.52 | 0.00 | 0.00 | 0.00 |
| October | 123.69 | 50.40 | 73.30 | 106.59 | 156.31 | 0.00 | 0.00 | 0.00 |
| November | 61.60 | 17.37 | 44.23 | 29.91 | 188.05 | 0.00 | 0.00 | 0.00 |
| December | 51.79 | 17.75 | 34.04 | 26.36 | 225.79 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 173.79 | 74.29 | 99.50 | 178.34 | 146.90 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.79 | 16.28 | 34.04 | 21.32 | 75.66 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 322.53 | 169.54 | 161.19 | 403.13 | 225.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.18 | 0.00 | 4.18 | 0.04 | 35.65 | 0.00 | 0.00 | 0.00 |
| February | 6.42 | 0.00 | 6.42 | 0.72 | 31.90 | 0.00 | 0.00 | 0.00 |
| March | 9.42 | 0.00 | 9.42 | 2.20 | 25.93 | 0.00 | 0.00 | 0.00 |
| April | 13.20 | 0.05 | 13.15 | 6.11 | 21.04 | 0.00 | 0.00 | 0.00 |
| May | 17.23 | 0.56 | 16.67 | 10.74 | 17.65 | 0.00 | 0.00 | 0.00 |
| June | 17.98 | 1.33 | 16.66 | 13.31 | 13.50 | 0.00 | 0.00 | 0.00 |
| July | 17.25 | 1.52 | 15.73 | 16.87 | 11.28 | 0.00 | 0.00 | 0.00 |
| August | 13.81 | 0.39 | 13.41 | 14.35 | 10.71 | 0.00 | 0.00 | 0.00 |
| September | 10.59 | 0.00 | 10.59 | 6.07 | 17.92 | 0.00 | 0.00 | 0.00 |
| October | 7.31 | 0.00 | 7.31 | 1.58 | 24.58 | 0.00 | 0.00 | 0.00 |
| November | 4.73 | 0.00 | 4.73 | 0.22 | 30.28 | 0.00 | 0.00 | 0.00 |
| December | 3.49 | 0.00 | 3.49 | 0.01 | 36.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 10.49 | 0.32 | 10.17 | 6.06 | 22.99 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3.49 | 0.00 | 3.49 | 0.01 | 10.71 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 17.98 | 1.52 | 16.67 | 16.87 | 36.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 30.30 | 0.00 | 30.30 | 0.33 | 246.73 | 0.00 | 0.00 | 0.00 |
| February | 46.70 | 0.00 | 46.70 | 5.79 | 220.14 | 0.00 | 0.00 | 0.00 |
| March | 68.63 | 0.00 | 68.63 | 17.98 | 179.37 | 0.00 | 0.00 | 0.00 |
| April | 96.33 | 0.33 | 96.00 | 47.49 | 145.82 | 0.00 | 0.00 | 0.00 |
| May | 125.19 | 3.89 | 121.29 | 81.19 | 122.68 | 0.00 | 0.00 | 0.00 |
| June | 130.76 | 9.22 | 121.55 | 99.69 | 94.16 | 0.00 | 0.00 | 0.00 |
| July | 125.10 | 10.53 | 114.57 | 123.71 | 78.85 | 0.00 | 0.00 | 0.00 |
| August | 100.54 | 2.74 | 97.80 | 105.33 | 75.00 | 0.00 | 0.00 | 0.00 |
| September | 77.51 | 0.02 | 77.49 | 46.91 | 124.72 | 0.00 | 0.00 | 0.00 |
| October | 53.39 | 0.00 | 53.39 | 13.15 | 170.06 | 0.00 | 0.00 | 0.00 |
| November | 34.32 | 0.00 | 34.32 | 1.90 | 209.54 | 0.00 | 0.00 | 0.00 |
| December | 25.44 | 0.00 | 25.44 | 0.14 | 249.28 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 76.33 | 2.24 | 74.09 | 45.59 | 159.38 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.44 | 0.00 | 25.44 | 0.14 | 75.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 130.76 | 10.53 | 121.55 | 123.71 | 249.28 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 50.16 | 0.00 | 50.16 | 0.04 | 485.81 | 0.00 | 0.00 | 0.00 |
| February | 77.06 | 0.00 | 77.06 | 6.46 | 440.34 | 0.00 | 0.00 | 0.00 |
| March | 113.20 | 0.00 | 113.20 | 18.79 | 365.09 | 0.00 | 0.00 | 0.00 |
| April | 157.42 | 0.23 | 157.20 | 62.59 | 295.62 | 0.00 | 0.00 | 0.00 |
| May | 203.59 | 4.61 | 198.98 | 119.74 | 246.47 | 0.00 | 0.00 | 0.00 |
| June | 208.84 | 11.22 | 197.61 | 147.01 | 185.92 | 0.00 | 0.00 | 0.00 |
| July | 200.05 | 12.62 | 187.43 | 201.62 | 146.06 | 0.00 | 0.00 | 0.00 |
| August | 162.91 | 2.73 | 160.18 | 178.16 | 138.48 | 0.00 | 0.00 | 0.00 |
| September | 127.21 | 0.02 | 127.19 | 70.25 | 236.62 | 0.00 | 0.00 | 0.00 |
| October | 87.74 | 0.00 | 87.74 | 13.84 | 340.65 | 0.00 | 0.00 | 0.00 |
| November | 56.87 | 0.00 | 56.87 | 1.51 | 420.96 | 0.00 | 0.00 | 0.00 |
| December | 41.85 | 0.00 | 41.85 | 0.05 | 496.52 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 124.14 | 2.64 | 121.51 | 68.82 | 315.88 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 41.85 | 0.00 | 41.85 | 0.04 | 138.48 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 208.84 | 12.62 | 198.98 | 201.62 | 496.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 53.12 | 0.00 | 53.12 | 0.13 | 485.09 | 0.00 | 0.00 | 0.00 |
| February | 81.58 | 0.00 | 81.58 | 7.67 | 438.79 | 0.00 | 0.00 | 0.00 |
| March | 119.77 | 0.00 | 119.77 | 22.89 | 363.59 | 0.00 | 0.00 | 0.00 |
| April | 167.37 | 0.49 | 166.87 | 70.89 | 293.24 | 0.00 | 0.00 | 0.00 |
| May | 217.36 | 6.20 | 211.16 | 132.55 | 242.47 | 0.00 | 0.00 | 0.00 |
| June | 225.69 | 15.09 | 210.60 | 165.80 | 183.17 | 0.00 | 0.00 | 0.00 |
| July | 214.76 | 16.00 | 198.77 | 218.26 | 144.31 | 0.00 | 0.00 | 0.00 |
| August | 174.17 | 4.23 | 169.94 | 188.53 | 135.96 | 0.00 | 0.00 | 0.00 |
| September | 134.56 | 0.02 | 134.53 | 77.35 | 237.44 | 0.00 | 0.00 | 0.00 |
| October | 92.91 | 0.00 | 92.91 | 16.85 | 340.08 | 0.00 | 0.00 | 0.00 |
| November | 60.19 | 0.00 | 60.19 | 1.93 | 419.87 | 0.00 | 0.00 | 0.00 |
| December | 44.39 | 0.00 | 44.39 | 0.08 | 496.55 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 132.41 | 3.53 | 128.88 | 75.76 | 314.38 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 44.39 | 0.00 | 44.39 | 0.08 | 135.96 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 225.69 | 16.00 | 211.16 | 218.26 | 496.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 53.12 | 0.00 | 53.12 | 0.13 | 485.08 | 0.00 | 0.00 | 0.00 |
| February | 81.58 | 0.00 | 81.58 | 7.67 | 438.79 | 0.00 | 0.00 | 0.00 |
| March | 119.76 | 0.00 | 119.76 | 22.89 | 363.58 | 0.00 | 0.00 | 0.00 |
| April | 167.67 | 0.59 | 167.07 | 70.90 | 292.71 | 0.00 | 0.00 | 0.00 |
| May | 218.41 | 6.79 | 211.62 | 132.82 | 241.09 | 0.00 | 0.00 | 0.00 |
| June | 226.66 | 15.71 | 210.95 | 166.15 | 182.06 | 0.00 | 0.00 | 0.00 |
| July | 216.81 | 17.52 | 199.29 | 219.87 | 142.73 | 0.00 | 0.00 | 0.00 |
| August | 175.51 | 5.03 | 170.47 | 189.98 | 135.14 | 0.00 | 0.00 | 0.00 |
| September | 134.58 | 0.03 | 134.56 | 77.35 | 237.38 | 0.00 | 0.00 | 0.00 |
| October | 92.91 | 0.00 | 92.91 | 16.85 | 340.07 | 0.00 | 0.00 | 0.00 |
| November | 60.19 | 0.00 | 60.19 | 1.93 | 419.86 | 0.00 | 0.00 | 0.00 |
| December | 44.39 | 0.00 | 44.39 | 0.08 | 496.54 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 132.89 | 3.83 | 129.06 | 76.07 | 313.91 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 44.39 | 0.00 | 44.39 | 0.08 | 135.14 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 226.66 | 17.52 | 211.62 | 219.87 | 496.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.20 | 16.28 | 38.92 | 19.46 | 226.83 | 0.00 | 0.00 | 0.00 |
| February | 98.96 | 37.19 | 61.77 | 61.51 | 202.92 | 0.00 | 0.00 | 0.00 |
| March | 138.67 | 46.80 | 91.86 | 102.83 | 173.74 | 0.00 | 0.00 | 0.00 |
| April | 210.97 | 80.66 | 130.31 | 196.80 | 145.31 | 0.00 | 0.00 | 0.00 |
| May | 271.47 | 110.28 | 161.19 | 283.12 | 124.24 | 0.00 | 0.00 | 0.00 |
| June | 261.08 | 101.37 | 159.71 | 281.06 | 97.39 | 0.00 | 0.00 | 0.00 |
| July | 322.53 | 169.54 | 152.99 | 394.65 | 84.33 | 0.00 | 0.00 | 0.00 |
| August | 266.81 | 136.24 | 130.57 | 331.97 | 83.41 | 0.00 | 0.00 | 0.00 |
| September | 217.27 | 104.25 | 113.02 | 236.04 | 127.71 | 0.00 | 0.00 | 0.00 |
| October | 123.69 | 50.40 | 73.30 | 99.03 | 170.53 | 0.00 | 0.00 | 0.00 |
| November | 61.60 | 17.37 | 44.23 | 26.95 | 198.19 | 0.00 | 0.00 | 0.00 |
| December | 51.79 | 17.75 | 34.04 | 24.01 | 233.87 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 173.79 | 74.29 | 99.50 | 172.20 | 155.47 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.79 | 16.28 | 34.04 | 19.46 | 83.41 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 322.53 | 169.54 | 161.19 | 394.65 | 233.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.16 | 12.83 | 8.33 | 18.08 | 32.21 | 0.00 | 0.00 | 0.00 |
| February | 33.12 | 21.02 | 12.10 | 32.47 | 28.91 | 0.00 | 0.00 | 0.00 |
| March | 35.37 | 19.53 | 15.85 | 35.91 | 26.22 | 0.00 | 0.00 | 0.00 |
| April | 36.86 | 16.80 | 20.06 | 39.44 | 22.76 | 0.00 | 0.00 | 0.00 |
| May | 33.21 | 10.54 | 22.68 | 35.36 | 19.74 | 0.00 | 0.00 | 0.00 |
| June | 30.06 | 8.69 | 21.38 | 32.95 | 15.50 | 0.00 | 0.00 | 0.00 |
| July | 33.20 | 12.93 | 20.28 | 42.08 | 13.32 | 0.00 | 0.00 | 0.00 |
| August | 36.10 | 17.68 | 18.42 | 47.79 | 12.83 | 0.00 | 0.00 | 0.00 |
| September | 40.47 | 23.20 | 17.27 | 48.43 | 19.33 | 0.00 | 0.00 | 0.00 |
| October | 36.98 | 23.47 | 13.52 | 39.98 | 25.11 | 0.00 | 0.00 | 0.00 |
| November | 21.68 | 12.74 | 8.94 | 19.47 | 28.78 | 0.00 | 0.00 | 0.00 |
| December | 22.02 | 14.47 | 7.55 | 21.02 | 33.94 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 31.67 | 16.13 | 15.54 | 34.42 | 23.19 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21.16 | 8.69 | 7.55 | 18.08 | 12.83 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 40.47 | 23.47 | 22.68 | 48.43 | 33.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 145.18 | 88.98 | 56.20 | 124.03 | 222.68 | 0.00 | 0.00 | 0.00 |
| February | 227.20 | 145.91 | 81.29 | 222.60 | 199.69 | 0.00 | 0.00 | 0.00 |
| March | 241.50 | 135.51 | 105.99 | 245.03 | 181.41 | 0.00 | 0.00 | 0.00 |
| April | 249.90 | 116.57 | 133.33 | 267.12 | 157.70 | 0.00 | 0.00 | 0.00 |
| May | 223.56 | 73.13 | 150.43 | 237.38 | 137.29 | 0.00 | 0.00 | 0.00 |
| June | 201.26 | 60.30 | 140.95 | 219.89 | 107.90 | 0.00 | 0.00 | 0.00 |
| July | 223.71 | 89.71 | 134.00 | 283.80 | 92.51 | 0.00 | 0.00 | 0.00 |
| August | 244.72 | 122.71 | 122.01 | 324.87 | 88.39 | 0.00 | 0.00 | 0.00 |
| September | 275.93 | 160.99 | 114.94 | 330.40 | 133.18 | 0.00 | 0.00 | 0.00 |
| October | 253.38 | 162.86 | 90.53 | 273.98 | 173.39 | 0.00 | 0.00 | 0.00 |
| November | 148.64 | 88.42 | 60.22 | 133.42 | 198.97 | 0.00 | 0.00 | 0.00 |
| December | 150.58 | 99.87 | 50.71 | 143.68 | 234.53 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 215.33 | 111.86 | 103.47 | 233.90 | 160.44 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 145.18 | 60.30 | 50.71 | 124.03 | 88.39 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 275.93 | 162.86 | 150.43 | 330.40 | 234.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 259.10 | 159.30 | 99.81 | 218.15 | 443.62 | 0.00 | 0.00 | 0.00 |
| February | 414.79 | 267.95 | 146.85 | 398.76 | 397.81 | 0.00 | 0.00 | 0.00 |
| March | 440.17 | 248.98 | 191.19 | 438.76 | 367.62 | 0.00 | 0.00 | 0.00 |
| April | 454.01 | 214.22 | 239.79 | 477.33 | 315.99 | 0.00 | 0.00 | 0.00 |
| May | 404.68 | 134.39 | 270.28 | 426.20 | 269.17 | 0.00 | 0.00 | 0.00 |
| June | 363.28 | 110.81 | 252.47 | 395.43 | 209.64 | 0.00 | 0.00 | 0.00 |
| July | 405.15 | 164.85 | 240.30 | 521.23 | 169.26 | 0.00 | 0.00 | 0.00 |
| August | 444.54 | 225.50 | 219.04 | 595.43 | 163.63 | 0.00 | 0.00 | 0.00 |
| September | 502.68 | 295.85 | 206.84 | 601.43 | 256.40 | 0.00 | 0.00 | 0.00 |
| October | 462.04 | 298.78 | 163.25 | 494.67 | 346.66 | 0.00 | 0.00 | 0.00 |
| November | 269.24 | 161.27 | 107.97 | 236.77 | 400.18 | 0.00 | 0.00 | 0.00 |
| December | 263.42 | 174.83 | 88.59 | 248.61 | 473.08 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 389.98 | 204.31 | 185.67 | 421.17 | 317.34 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 259.10 | 110.81 | 88.59 | 218.15 | 163.63 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 502.68 | 298.78 | 270.28 | 601.43 | 473.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 258.56 | 158.95 | 99.61 | 218.14 | 444.36 | 0.00 | 0.00 | 0.00 |
| February | 413.51 | 267.26 | 146.26 | 398.63 | 399.67 | 0.00 | 0.00 | 0.00 |
| March | 439.84 | 248.80 | 191.03 | 438.67 | 368.04 | 0.00 | 0.00 | 0.00 |
| April | 453.98 | 214.21 | 239.78 | 477.30 | 315.97 | 0.00 | 0.00 | 0.00 |
| May | 404.65 | 134.39 | 270.26 | 426.17 | 269.15 | 0.00 | 0.00 | 0.00 |
| June | 363.26 | 110.81 | 252.45 | 395.41 | 209.63 | 0.00 | 0.00 | 0.00 |
| July | 405.12 | 164.84 | 240.28 | 521.20 | 169.25 | 0.00 | 0.00 | 0.00 |
| August | 444.51 | 225.49 | 219.02 | 595.39 | 163.62 | 0.00 | 0.00 | 0.00 |
| September | 502.59 | 295.79 | 206.80 | 601.36 | 256.47 | 0.00 | 0.00 | 0.00 |
| October | 461.23 | 298.27 | 162.95 | 494.51 | 347.80 | 0.00 | 0.00 | 0.00 |
| November | 268.31 | 160.71 | 107.60 | 236.50 | 401.27 | 0.00 | 0.00 | 0.00 |
| December | 262.96 | 174.49 | 88.47 | 248.59 | 473.69 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 389.60 | 204.08 | 185.52 | 421.10 | 317.82 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 258.56 | 110.81 | 88.47 | 218.14 | 163.62 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 502.59 | 298.27 | 270.26 | 601.36 | 473.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 241.10 | 148.30 | 92.80 | 198.90 | 446.34 | 0.00 | 0.00 | 0.00 |
| February | 384.81 | 248.71 | 136.11 | 365.60 | 404.10 | 0.00 | 0.00 | 0.00 |
| March | 415.78 | 235.77 | 180.01 | 410.56 | 371.85 | 0.00 | 0.00 | 0.00 |
| April | 434.89 | 206.98 | 227.91 | 452.94 | 316.72 | 0.00 | 0.00 | 0.00 |
| May | 389.27 | 131.42 | 257.85 | 407.17 | 269.45 | 0.00 | 0.00 | 0.00 |
| June | 348.93 | 108.45 | 240.48 | 377.80 | 209.63 | 0.00 | 0.00 | 0.00 |
| July | 391.09 | 161.48 | 229.61 | 503.19 | 168.41 | 0.00 | 0.00 | 0.00 |
| August | 427.86 | 219.12 | 208.74 | 572.72 | 162.25 | 0.00 | 0.00 | 0.00 |
| September | 480.25 | 284.07 | 196.18 | 571.64 | 256.76 | 0.00 | 0.00 | 0.00 |
| October | 431.00 | 278.43 | 152.57 | 457.85 | 351.83 | 0.00 | 0.00 | 0.00 |
| November | 248.98 | 148.68 | 100.30 | 214.71 | 403.66 | 0.00 | 0.00 | 0.00 |
| December | 244.36 | 161.87 | 82.49 | 226.71 | 474.32 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 369.65 | 194.07 | 175.57 | 396.82 | 319.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 241.10 | 108.45 | 82.49 | 198.90 | 162.25 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 480.25 | 284.07 | 257.85 | 572.72 | 474.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 18.40 | 5.43 | 12.97 | 6.34 | 83.07 | 0.00 | 0.00 | 0.00 |
| February | 32.99 | 12.40 | 20.59 | 20.37 | 74.03 | 0.00 | 0.00 | 0.00 |
| March | 46.22 | 15.60 | 30.62 | 33.92 | 64.19 | 0.00 | 0.00 | 0.00 |
| April | 70.32 | 26.89 | 43.44 | 64.45 | 53.95 | 0.00 | 0.00 | 0.00 |
| May | 90.49 | 36.76 | 53.73 | 92.77 | 45.90 | 0.00 | 0.00 | 0.00 |
| June | 87.03 | 33.79 | 53.24 | 91.86 | 35.73 | 0.00 | 0.00 | 0.00 |
| July | 107.51 | 56.51 | 51.00 | 131.21 | 29.22 | 0.00 | 0.00 | 0.00 |
| August | 88.94 | 45.41 | 43.52 | 110.89 | 28.38 | 0.00 | 0.00 | 0.00 |
| September | 72.42 | 34.75 | 37.67 | 79.06 | 44.28 | 0.00 | 0.00 | 0.00 |
| October | 41.23 | 16.80 | 24.43 | 33.12 | 61.35 | 0.00 | 0.00 | 0.00 |
| November | 20.53 | 5.79 | 14.74 | 8.94 | 72.28 | 0.00 | 0.00 | 0.00 |
| December | 17.26 | 5.92 | 11.35 | 8.06 | 85.33 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 57.93 | 24.76 | 33.17 | 57.00 | 56.39 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 17.26 | 5.43 | 11.35 | 6.34 | 28.38 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 107.51 | 56.51 | 53.73 | 131.21 | 85.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.01 | 0.00 | 5.01 | 0.10 | 35.54 | 0.00 | 0.00 | 0.00 |
| February | 7.80 | 0.00 | 7.80 | 1.21 | 31.57 | 0.00 | 0.00 | 0.00 |
| March | 11.49 | 0.00 | 11.49 | 3.90 | 25.99 | 0.00 | 0.00 | 0.00 |
| April | 16.26 | 0.06 | 16.21 | 9.19 | 21.18 | 0.00 | 0.00 | 0.00 |
| May | 20.93 | 0.62 | 20.30 | 14.85 | 17.86 | 0.00 | 0.00 | 0.00 |
| June | 22.00 | 1.45 | 20.55 | 17.82 | 13.74 | 0.00 | 0.00 | 0.00 |
| July | 20.91 | 1.64 | 19.27 | 20.86 | 11.63 | 0.00 | 0.00 | 0.00 |
| August | 16.93 | 0.46 | 16.47 | 17.72 | 11.16 | 0.00 | 0.00 | 0.00 |
| September | 13.15 | 0.00 | 13.15 | 8.74 | 18.41 | 0.00 | 0.00 | 0.00 |
| October | 9.01 | 0.00 | 9.01 | 2.90 | 24.78 | 0.00 | 0.00 | 0.00 |
| November | 5.68 | 0.00 | 5.68 | 0.45 | 30.25 | 0.00 | 0.00 | 0.00 |
| December | 4.26 | 0.00 | 4.26 | 0.05 | 36.04 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 12.81 | 0.36 | 12.46 | 8.20 | 23.14 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4.26 | 0.00 | 4.26 | 0.05 | 11.16 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 22.00 | 1.64 | 20.55 | 20.86 | 36.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 55.20 | 16.28 | 38.92 | 21.27 | 220.95 | 0.00 | 0.00 | 0.00 |
| February | 98.96 | 37.19 | 61.77 | 66.02 | 193.36 | 0.00 | 0.00 | 0.00 |
| March | 138.67 | 46.80 | 91.86 | 110.06 | 162.86 | 0.00 | 0.00 | 0.00 |
| April | 210.97 | 80.66 | 130.31 | 204.36 | 137.00 | 0.00 | 0.00 | 0.00 |
| May | 271.47 | 110.28 | 161.19 | 287.84 | 119.92 | 0.00 | 0.00 | 0.00 |
| June | 261.08 | 101.37 | 159.71 | 284.50 | 94.91 | 0.00 | 0.00 | 0.00 |
| July | 322.53 | 169.54 | 152.99 | 401.51 | 79.91 | 0.00 | 0.00 | 0.00 |
| August | 266.81 | 136.24 | 130.57 | 340.55 | 76.58 | 0.00 | 0.00 | 0.00 |
| September | 217.27 | 104.25 | 113.02 | 244.16 | 117.44 | 0.00 | 0.00 | 0.00 |
| October | 123.69 | 50.40 | 73.30 | 106.14 | 157.22 | 0.00 | 0.00 | 0.00 |
| November | 61.60 | 17.37 | 44.23 | 29.73 | 188.76 | 0.00 | 0.00 | 0.00 |
| December | 51.79 | 17.75 | 34.04 | 26.30 | 225.98 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 173.79 | 74.29 | 99.50 | 177.63 | 147.68 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.79 | 16.28 | 34.04 | 21.27 | 76.58 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 322.53 | 169.54 | 161.19 | 401.51 | 225.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 34.65 | 0.00 | 34.65 | 0.73 | 245.24 | 0.00 | 0.00 | 0.00 |
| February | 53.92 | 0.00 | 53.92 | 8.49 | 217.72 | 0.00 | 0.00 | 0.00 |
| March | 79.44 | 0.00 | 79.44 | 27.19 | 179.47 | 0.00 | 0.00 | 0.00 |
| April | 112.42 | 0.40 | 112.02 | 63.74 | 146.43 | 0.00 | 0.00 | 0.00 |
| May | 144.65 | 4.30 | 140.36 | 102.78 | 123.49 | 0.00 | 0.00 | 0.00 |
| June | 152.10 | 10.04 | 142.06 | 123.25 | 94.96 | 0.00 | 0.00 | 0.00 |
| July | 144.56 | 11.33 | 133.23 | 144.38 | 80.36 | 0.00 | 0.00 | 0.00 |
| August | 117.03 | 3.16 | 113.86 | 122.78 | 77.16 | 0.00 | 0.00 | 0.00 |
| September | 90.90 | 0.03 | 90.87 | 60.98 | 127.25 | 0.00 | 0.00 | 0.00 |
| October | 62.28 | 0.00 | 62.28 | 20.33 | 170.96 | 0.00 | 0.00 | 0.00 |
| November | 39.23 | 0.00 | 39.23 | 3.16 | 208.77 | 0.00 | 0.00 | 0.00 |
| December | 29.45 | 0.00 | 29.45 | 0.39 | 248.61 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 88.56 | 2.46 | 86.10 | 56.84 | 159.73 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.45 | 0.00 | 29.45 | 0.39 | 77.16 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 152.10 | 11.33 | 142.06 | 144.38 | 248.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.22 | 0.00 | 42.22 | 0.49 | 319.28 | 0.00 | 0.00 | 0.00 |
| February | 65.69 | 0.00 | 65.69 | 8.66 | 286.63 | 0.00 | 0.00 | 0.00 |
| March | 96.78 | 0.00 | 96.78 | 28.42 | 239.91 | 0.00 | 0.00 | 0.00 |
| April | 136.96 | 0.49 | 136.47 | 72.20 | 194.34 | 0.00 | 0.00 | 0.00 |
| May | 176.23 | 5.24 | 171.00 | 122.28 | 160.40 | 0.00 | 0.00 | 0.00 |
| June | 185.30 | 12.24 | 173.07 | 148.37 | 121.76 | 0.00 | 0.00 | 0.00 |
| July | 176.12 | 13.81 | 162.31 | 180.72 | 97.38 | 0.00 | 0.00 | 0.00 |
| August | 142.57 | 3.85 | 138.72 | 153.75 | 93.38 | 0.00 | 0.00 | 0.00 |
| September | 110.74 | 0.03 | 110.71 | 73.38 | 161.16 | 0.00 | 0.00 | 0.00 |
| October | 75.88 | 0.00 | 75.88 | 21.49 | 225.99 | 0.00 | 0.00 | 0.00 |
| November | 47.80 | 0.00 | 47.80 | 2.85 | 277.22 | 0.00 | 0.00 | 0.00 |
| December | 35.87 | 0.00 | 35.87 | 0.21 | 328.12 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 107.89 | 2.99 | 104.90 | 68.15 | 208.38 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.87 | 0.00 | 35.87 | 0.21 | 93.38 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 185.30 | 13.81 | 173.07 | 180.72 | 328.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.22 | 0.00 | 42.22 | 0.49 | 319.28 | 0.00 | 0.00 | 0.00 |
| February | 65.69 | 0.00 | 65.69 | 8.66 | 286.63 | 0.00 | 0.00 | 0.00 |
| March | 96.78 | 0.00 | 96.78 | 28.42 | 239.91 | 0.00 | 0.00 | 0.00 |
| April | 136.96 | 0.49 | 136.47 | 72.19 | 194.34 | 0.00 | 0.00 | 0.00 |
| May | 176.23 | 5.24 | 171.00 | 122.28 | 160.40 | 0.00 | 0.00 | 0.00 |
| June | 185.30 | 12.24 | 173.07 | 148.37 | 121.76 | 0.00 | 0.00 | 0.00 |
| July | 176.12 | 13.81 | 162.31 | 180.72 | 97.38 | 0.00 | 0.00 | 0.00 |
| August | 142.57 | 3.85 | 138.72 | 153.75 | 93.38 | 0.00 | 0.00 | 0.00 |
| September | 110.74 | 0.03 | 110.71 | 73.37 | 161.16 | 0.00 | 0.00 | 0.00 |
| October | 75.88 | 0.00 | 75.88 | 21.49 | 225.99 | 0.00 | 0.00 | 0.00 |
| November | 47.80 | 0.00 | 47.80 | 2.85 | 277.22 | 0.00 | 0.00 | 0.00 |
| December | 35.87 | 0.00 | 35.87 | 0.21 | 328.12 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 107.89 | 2.99 | 104.90 | 68.15 | 208.38 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.87 | 0.00 | 35.87 | 0.21 | 93.38 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 185.30 | 13.81 | 173.07 | 180.72 | 328.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.22 | 0.00 | 42.22 | 0.49 | 319.27 | 0.00 | 0.00 | 0.00 |
| February | 65.69 | 0.00 | 65.69 | 8.66 | 286.62 | 0.00 | 0.00 | 0.00 |
| March | 96.78 | 0.00 | 96.78 | 28.42 | 239.90 | 0.00 | 0.00 | 0.00 |
| April | 136.95 | 0.49 | 136.47 | 72.19 | 194.33 | 0.00 | 0.00 | 0.00 |
| May | 176.23 | 5.24 | 170.99 | 122.28 | 160.39 | 0.00 | 0.00 | 0.00 |
| June | 185.30 | 12.24 | 173.06 | 148.36 | 121.75 | 0.00 | 0.00 | 0.00 |
| July | 176.12 | 13.81 | 162.31 | 180.71 | 97.38 | 0.00 | 0.00 | 0.00 |
| August | 142.57 | 3.85 | 138.71 | 153.75 | 93.38 | 0.00 | 0.00 | 0.00 |
| September | 110.74 | 0.03 | 110.71 | 73.37 | 161.16 | 0.00 | 0.00 | 0.00 |
| October | 75.88 | 0.00 | 75.88 | 21.49 | 225.98 | 0.00 | 0.00 | 0.00 |
| November | 47.79 | 0.00 | 47.79 | 2.85 | 277.21 | 0.00 | 0.00 | 0.00 |
| December | 35.87 | 0.00 | 35.87 | 0.21 | 328.11 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 107.89 | 2.99 | 104.89 | 68.15 | 208.37 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.87 | 0.00 | 35.87 | 0.21 | 93.38 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 185.30 | 13.81 | 173.06 | 180.71 | 328.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.76 | 0.00 | 4.76 | 0.03 | 37.45 | 0.00 | 0.00 | 0.00 |
| February | 7.41 | 0.00 | 7.41 | 0.85 | 34.12 | 0.00 | 0.00 | 0.00 |
| March | 10.91 | 0.00 | 10.91 | 2.74 | 29.40 | 0.00 | 0.00 | 0.00 |
| April | 15.44 | 0.05 | 15.39 | 7.44 | 23.87 | 0.00 | 0.00 | 0.00 |
| May | 19.87 | 0.59 | 19.28 | 13.15 | 19.43 | 0.00 | 0.00 | 0.00 |
| June | 20.90 | 1.38 | 19.52 | 15.88 | 14.81 | 0.00 | 0.00 | 0.00 |
| July | 19.86 | 1.56 | 18.30 | 19.10 | 12.09 | 0.00 | 0.00 | 0.00 |
| August | 16.08 | 0.43 | 15.64 | 16.09 | 11.78 | 0.00 | 0.00 | 0.00 |
| September | 12.49 | 0.00 | 12.48 | 7.60 | 19.89 | 0.00 | 0.00 | 0.00 |
| October | 8.56 | 0.00 | 8.56 | 2.08 | 27.79 | 0.00 | 0.00 | 0.00 |
| November | 5.39 | 0.00 | 5.39 | 0.23 | 33.70 | 0.00 | 0.00 | 0.00 |
| December | 4.05 | 0.00 | 4.05 | 0.01 | 38.89 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 12.17 | 0.34 | 11.83 | 7.14 | 25.22 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4.05 | 0.00 | 4.05 | 0.01 | 11.78 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 20.90 | 1.56 | 19.52 | 19.10 | 38.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 60.37 | 0.00 | 60.37 | 0.41 | 474.94 | 0.00 | 0.00 | 0.00 |
| February | 93.94 | 0.00 | 93.94 | 10.76 | 432.71 | 0.00 | 0.00 | 0.00 |
| March | 138.41 | 0.00 | 138.41 | 34.71 | 372.81 | 0.00 | 0.00 | 0.00 |
| April | 195.86 | 0.69 | 195.17 | 94.39 | 302.65 | 0.00 | 0.00 | 0.00 |
| May | 252.02 | 7.49 | 244.54 | 166.83 | 246.35 | 0.00 | 0.00 | 0.00 |
| June | 265.00 | 17.50 | 247.50 | 201.34 | 187.87 | 0.00 | 0.00 | 0.00 |
| July | 251.86 | 19.75 | 232.12 | 242.22 | 153.31 | 0.00 | 0.00 | 0.00 |
| August | 203.89 | 5.51 | 198.37 | 203.99 | 149.42 | 0.00 | 0.00 | 0.00 |
| September | 158.37 | 0.05 | 158.32 | 96.35 | 252.27 | 0.00 | 0.00 | 0.00 |
| October | 108.51 | 0.00 | 108.51 | 26.34 | 352.41 | 0.00 | 0.00 | 0.00 |
| November | 68.35 | 0.00 | 68.35 | 2.89 | 427.37 | 0.00 | 0.00 | 0.00 |
| December | 51.30 | 0.00 | 51.30 | 0.17 | 493.22 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 154.29 | 4.28 | 150.01 | 90.59 | 319.83 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.30 | 0.00 | 51.30 | 0.17 | 149.42 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 265.00 | 19.75 | 247.50 | 242.22 | 493.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.82 | 1.73 | 4.09 | 1.90 | 39.55 | 0.00 | 0.00 | 0.00 |
| February | 12.42 | 5.48 | 6.94 | 8.27 | 35.14 | 0.00 | 0.00 | 0.00 |
| March | 18.09 | 7.35 | 10.74 | 13.59 | 30.72 | 0.00 | 0.00 | 0.00 |
| April | 26.91 | 11.86 | 15.05 | 24.45 | 26.87 | 0.00 | 0.00 | 0.00 |
| May | 32.18 | 13.96 | 18.22 | 31.97 | 23.70 | 0.00 | 0.00 | 0.00 |
| June | 29.54 | 11.61 | 17.93 | 29.84 | 18.50 | 0.00 | 0.00 | 0.00 |
| July | 37.14 | 19.63 | 17.50 | 44.48 | 15.45 | 0.00 | 0.00 | 0.00 |
| August | 33.07 | 18.02 | 15.06 | 41.06 | 14.26 | 0.00 | 0.00 | 0.00 |
| September | 29.68 | 16.13 | 13.54 | 32.82 | 21.02 | 0.00 | 0.00 | 0.00 |
| October | 15.99 | 7.51 | 8.48 | 13.31 | 28.90 | 0.00 | 0.00 | 0.00 |
| November | 7.05 | 2.26 | 4.79 | 3.20 | 34.00 | 0.00 | 0.00 | 0.00 |
| December | 4.83 | 1.39 | 3.44 | 1.81 | 40.20 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 21.11 | 9.77 | 11.33 | 20.64 | 27.32 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4.83 | 1.39 | 3.44 | 1.81 | 14.26 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 37.14 | 19.63 | 18.22 | 44.48 | 40.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 22.28 | 0.86 | 21.42 | 0.06 | 216.10 | 0.00 | 0.00 | 0.00 |
| February | 44.19 | 9.09 | 35.10 | 12.28 | 189.64 | 0.00 | 0.00 | 0.00 |
| March | 79.80 | 23.14 | 56.66 | 45.47 | 162.83 | 0.00 | 0.00 | 0.00 |
| April | 141.34 | 56.57 | 84.77 | 120.94 | 139.68 | 0.00 | 0.00 | 0.00 |
| May | 191.30 | 84.09 | 107.21 | 190.11 | 121.57 | 0.00 | 0.00 | 0.00 |
| June | 183.68 | 77.72 | 105.95 | 188.98 | 95.46 | 0.00 | 0.00 | 0.00 |
| July | 230.23 | 127.84 | 102.40 | 275.78 | 80.52 | 0.00 | 0.00 | 0.00 |
| August | 185.76 | 99.54 | 86.22 | 226.98 | 75.67 | 0.00 | 0.00 | 0.00 |
| September | 134.77 | 63.16 | 71.62 | 137.49 | 111.49 | 0.00 | 0.00 | 0.00 |
| October | 59.86 | 17.45 | 42.41 | 33.05 | 154.77 | 0.00 | 0.00 | 0.00 |
| November | 26.96 | 2.19 | 24.77 | 2.32 | 184.11 | 0.00 | 0.00 | 0.00 |
| December | 18.27 | 0.42 | 17.86 | 0.03 | 218.66 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 110.28 | 47.12 | 63.17 | 103.43 | 145.66 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.27 | 0.42 | 17.86 | 0.03 | 75.67 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 230.23 | 127.84 | 107.21 | 275.78 | 218.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 20.95 | 12.44 | 8.51 | 18.29 | 28.79 | 0.00 | 0.00 | 0.00 |
| February | 32.21 | 19.94 | 12.27 | 32.43 | 26.34 | 0.00 | 0.00 | 0.00 |
| March | 34.65 | 18.48 | 16.17 | 36.33 | 24.14 | 0.00 | 0.00 | 0.00 |
| April | 36.59 | 15.89 | 20.70 | 40.45 | 20.93 | 0.00 | 0.00 | 0.00 |
| May | 33.45 | 9.97 | 23.49 | 37.07 | 18.22 | 0.00 | 0.00 | 0.00 |
| June | 30.61 | 8.22 | 22.39 | 34.55 | 14.65 | 0.00 | 0.00 | 0.00 |
| July | 33.38 | 12.22 | 21.15 | 42.21 | 12.97 | 0.00 | 0.00 | 0.00 |
| August | 35.86 | 16.72 | 19.14 | 47.17 | 12.64 | 0.00 | 0.00 | 0.00 |
| September | 39.73 | 21.94 | 17.79 | 48.34 | 17.96 | 0.00 | 0.00 | 0.00 |
| October | 35.99 | 22.22 | 13.77 | 39.87 | 22.86 | 0.00 | 0.00 | 0.00 |
| November | 21.28 | 12.19 | 9.08 | 19.66 | 25.74 | 0.00 | 0.00 | 0.00 |
| December | 22.26 | 14.41 | 7.86 | 21.55 | 30.17 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 31.40 | 15.36 | 16.04 | 34.84 | 21.26 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.95 | 8.22 | 7.86 | 18.29 | 12.64 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 39.73 | 22.22 | 23.49 | 48.34 | 30.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 282.83 | 167.94 | 114.88 | 246.96 | 388.75 | 0.00 | 0.00 | 0.00 |
| February | 434.94 | 269.24 | 165.71 | 437.83 | 355.63 | 0.00 | 0.00 | 0.00 |
| March | 467.87 | 249.51 | 218.36 | 490.51 | 325.94 | 0.00 | 0.00 | 0.00 |
| April | 493.99 | 214.49 | 279.50 | 546.16 | 282.59 | 0.00 | 0.00 | 0.00 |
| May | 451.69 | 134.56 | 317.12 | 500.47 | 246.02 | 0.00 | 0.00 | 0.00 |
| June | 413.25 | 110.95 | 302.30 | 466.52 | 197.80 | 0.00 | 0.00 | 0.00 |
| July | 450.67 | 165.06 | 285.61 | 569.89 | 175.10 | 0.00 | 0.00 | 0.00 |
| August | 484.18 | 225.78 | 258.40 | 636.90 | 170.71 | 0.00 | 0.00 | 0.00 |
| September | 536.46 | 296.25 | 240.21 | 652.70 | 242.50 | 0.00 | 0.00 | 0.00 |
| October | 485.94 | 300.03 | 185.91 | 538.34 | 308.62 | 0.00 | 0.00 | 0.00 |
| November | 287.30 | 164.65 | 122.65 | 265.50 | 347.58 | 0.00 | 0.00 | 0.00 |
| December | 300.60 | 194.53 | 106.07 | 291.03 | 407.39 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 423.96 | 207.37 | 216.59 | 470.36 | 287.04 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 282.83 | 110.95 | 106.07 | 246.96 | 170.71 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 536.46 | 300.03 | 317.12 | 652.70 | 407.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BATH_ZN_1_FLR_1_WALL_5_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 35.04 | 5.07 | 29.97 | 3.16 | 256.94 | 0.00 | 0.00 | 0.00 |
| February | 71.16 | 21.69 | 49.47 | 32.30 | 233.11 | 0.00 | 0.00 | 0.00 |
| March | 116.51 | 38.28 | 78.23 | 75.09 | 210.80 | 0.00 | 0.00 | 0.00 |
| April | 193.15 | 78.91 | 114.24 | 168.31 | 183.40 | 0.00 | 0.00 | 0.00 |
| May | 253.61 | 110.74 | 142.88 | 247.51 | 164.62 | 0.00 | 0.00 | 0.00 |
| June | 241.34 | 100.42 | 140.92 | 238.73 | 133.83 | 0.00 | 0.00 | 0.00 |
| July | 302.33 | 166.10 | 136.22 | 355.56 | 112.69 | 0.00 | 0.00 | 0.00 |
| August | 249.39 | 133.94 | 115.46 | 299.71 | 106.30 | 0.00 | 0.00 | 0.00 |
| September | 192.88 | 94.67 | 98.21 | 198.11 | 153.20 | 0.00 | 0.00 | 0.00 |
| October | 93.67 | 33.94 | 59.73 | 62.14 | 202.36 | 0.00 | 0.00 | 0.00 |
| November | 42.35 | 7.59 | 34.76 | 9.42 | 236.02 | 0.00 | 0.00 | 0.00 |
| December | 28.87 | 3.85 | 25.02 | 2.83 | 267.78 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 152.18 | 66.59 | 85.59 | 141.83 | 188.18 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 28.87 | 3.85 | 25.02 | 2.83 | 106.30 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 302.33 | 166.10 | 142.88 | 355.56 | 267.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 122.10 | 30.96 | 91.15 | 34.49 | 550.25 | 0.00 | 0.00 | 0.00 |
| February | 224.05 | 79.52 | 144.53 | 126.75 | 496.87 | 0.00 | 0.00 | 0.00 |
| March | 334.52 | 121.10 | 213.42 | 240.80 | 438.55 | 0.00 | 0.00 | 0.00 |
| April | 518.56 | 215.47 | 303.09 | 474.70 | 360.95 | 0.00 | 0.00 | 0.00 |
| May | 551.79 | 191.85 | 359.95 | 531.96 | 313.15 | 0.00 | 0.00 | 0.00 |
| June | 660.83 | 287.53 | 373.30 | 703.09 | 247.73 | 0.00 | 0.00 | 0.00 |
| July | 615.39 | 276.22 | 339.17 | 695.31 | 212.13 | 0.00 | 0.00 | 0.00 |
| August | 604.84 | 302.58 | 302.27 | 714.69 | 206.90 | 0.00 | 0.00 | 0.00 |
| September | 447.19 | 206.25 | 240.94 | 446.50 | 311.84 | 0.00 | 0.00 | 0.00 |
| October | 291.48 | 123.85 | 167.63 | 225.95 | 420.35 | 0.00 | 0.00 | 0.00 |
| November | 142.87 | 40.33 | 102.53 | 58.82 | 494.49 | 0.00 | 0.00 | 0.00 |
| December | 117.18 | 37.72 | 79.46 | 45.55 | 571.73 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 386.61 | 159.80 | 226.81 | 359.44 | 384.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 117.18 | 30.96 | 79.46 | 34.49 | 206.90 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 660.83 | 302.58 | 373.30 | 714.69 | 571.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 20.80 | 12.35 | 8.45 | 17.45 | 31.42 | 0.00 | 0.00 | 0.00 |
| February | 31.99 | 19.80 | 12.19 | 31.03 | 28.74 | 0.00 | 0.00 | 0.00 |
| March | 34.41 | 18.35 | 16.06 | 34.38 | 27.16 | 0.00 | 0.00 | 0.00 |
| April | 36.33 | 15.77 | 20.55 | 37.96 | 24.00 | 0.00 | 0.00 | 0.00 |
| May | 33.22 | 9.90 | 23.32 | 34.57 | 20.85 | 0.00 | 0.00 | 0.00 |
| June | 30.39 | 8.16 | 22.23 | 32.04 | 16.82 | 0.00 | 0.00 | 0.00 |
| July | 33.14 | 12.14 | 21.00 | 40.20 | 14.58 | 0.00 | 0.00 | 0.00 |
| August | 35.61 | 16.60 | 19.00 | 45.44 | 14.06 | 0.00 | 0.00 | 0.00 |
| September | 39.45 | 21.79 | 17.66 | 46.61 | 19.86 | 0.00 | 0.00 | 0.00 |
| October | 35.74 | 22.06 | 13.67 | 38.23 | 25.67 | 0.00 | 0.00 | 0.00 |
| November | 21.13 | 12.11 | 9.02 | 18.60 | 28.76 | 0.00 | 0.00 | 0.00 |
| December | 22.11 | 14.31 | 7.80 | 20.74 | 33.13 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 31.18 | 15.25 | 15.93 | 33.11 | 23.73 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.80 | 8.16 | 7.80 | 17.45 | 14.06 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 39.45 | 22.06 | 23.32 | 46.61 | 33.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 314.94 | 187.01 | 127.93 | 264.28 | 475.84 | 0.00 | 0.00 | 0.00 |
| February | 484.33 | 299.81 | 184.52 | 469.90 | 435.24 | 0.00 | 0.00 | 0.00 |
| March | 521.00 | 277.85 | 243.16 | 520.65 | 411.26 | 0.00 | 0.00 | 0.00 |
| April | 550.08 | 238.84 | 311.24 | 574.87 | 363.40 | 0.00 | 0.00 | 0.00 |
| May | 502.98 | 149.84 | 353.14 | 523.44 | 315.50 | 0.00 | 0.00 | 0.00 |
| June | 460.18 | 123.55 | 336.62 | 485.21 | 254.43 | 0.00 | 0.00 | 0.00 |
| July | 501.84 | 183.80 | 318.04 | 608.66 | 220.43 | 0.00 | 0.00 | 0.00 |
| August | 539.17 | 251.42 | 287.74 | 688.10 | 212.67 | 0.00 | 0.00 | 0.00 |
| September | 597.37 | 329.89 | 267.48 | 705.74 | 300.76 | 0.00 | 0.00 | 0.00 |
| October | 541.12 | 334.10 | 207.02 | 578.92 | 388.77 | 0.00 | 0.00 | 0.00 |
| November | 319.93 | 183.35 | 136.58 | 281.71 | 435.47 | 0.00 | 0.00 | 0.00 |
| December | 334.74 | 216.62 | 118.12 | 314.00 | 501.74 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 472.10 | 230.91 | 241.19 | 501.43 | 359.23 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 314.94 | 123.55 | 118.12 | 264.28 | 212.67 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 597.37 | 334.10 | 353.14 | 705.74 | 501.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.42 | 3.80 | 13.62 | 6.55 | 62.84 | 0.00 | 0.00 | 0.00 |
| February | 32.05 | 11.83 | 20.22 | 23.47 | 58.34 | 0.00 | 0.00 | 0.00 |
| March | 52.31 | 22.06 | 30.26 | 47.85 | 52.07 | 0.00 | 0.00 | 0.00 |
| April | 84.39 | 42.97 | 41.42 | 90.69 | 44.25 | 0.00 | 0.00 | 0.00 |
| May | 109.45 | 56.36 | 53.08 | 126.41 | 37.82 | 0.00 | 0.00 | 0.00 |
| June | 119.44 | 69.80 | 49.64 | 141.63 | 31.00 | 0.00 | 0.00 | 0.00 |
| July | 124.78 | 82.20 | 42.59 | 155.57 | 28.69 | 0.00 | 0.00 | 0.00 |
| August | 99.50 | 62.94 | 36.56 | 124.56 | 28.79 | 0.00 | 0.00 | 0.00 |
| September | 70.24 | 38.82 | 31.42 | 80.30 | 38.99 | 0.00 | 0.00 | 0.00 |
| October | 40.62 | 18.38 | 22.24 | 37.64 | 49.92 | 0.00 | 0.00 | 0.00 |
| November | 20.48 | 5.13 | 15.35 | 11.19 | 55.84 | 0.00 | 0.00 | 0.00 |
| December | 14.64 | 3.54 | 11.09 | 5.27 | 67.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 65.63 | 34.96 | 30.67 | 71.21 | 46.24 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14.64 | 3.54 | 11.09 | 5.27 | 28.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.78 | 82.20 | 53.08 | 155.57 | 67.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.42 | 3.80 | 13.62 | 6.55 | 62.84 | 0.00 | 0.00 | 0.00 |
| February | 32.05 | 11.83 | 20.22 | 23.47 | 58.34 | 0.00 | 0.00 | 0.00 |
| March | 52.31 | 22.06 | 30.26 | 47.85 | 52.07 | 0.00 | 0.00 | 0.00 |
| April | 84.39 | 42.97 | 41.42 | 90.69 | 44.25 | 0.00 | 0.00 | 0.00 |
| May | 109.45 | 56.36 | 53.08 | 126.41 | 37.82 | 0.00 | 0.00 | 0.00 |
| June | 119.44 | 69.80 | 49.64 | 141.63 | 31.00 | 0.00 | 0.00 | 0.00 |
| July | 124.78 | 82.20 | 42.59 | 155.57 | 28.69 | 0.00 | 0.00 | 0.00 |
| August | 99.50 | 62.94 | 36.56 | 124.56 | 28.79 | 0.00 | 0.00 | 0.00 |
| September | 70.24 | 38.82 | 31.42 | 80.30 | 38.99 | 0.00 | 0.00 | 0.00 |
| October | 40.62 | 18.38 | 22.24 | 37.64 | 49.92 | 0.00 | 0.00 | 0.00 |
| November | 20.48 | 5.13 | 15.35 | 11.19 | 55.84 | 0.00 | 0.00 | 0.00 |
| December | 14.64 | 3.54 | 11.09 | 5.27 | 67.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 65.63 | 34.96 | 30.67 | 71.21 | 46.24 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14.64 | 3.54 | 11.09 | 5.27 | 28.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.78 | 82.20 | 53.08 | 155.57 | 67.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.42 | 3.80 | 13.62 | 6.55 | 62.84 | 0.00 | 0.00 | 0.00 |
| February | 32.05 | 11.83 | 20.22 | 23.47 | 58.34 | 0.00 | 0.00 | 0.00 |
| March | 52.31 | 22.06 | 30.26 | 47.85 | 52.07 | 0.00 | 0.00 | 0.00 |
| April | 84.39 | 42.97 | 41.42 | 90.69 | 44.25 | 0.00 | 0.00 | 0.00 |
| May | 109.45 | 56.36 | 53.08 | 126.41 | 37.82 | 0.00 | 0.00 | 0.00 |
| June | 119.44 | 69.80 | 49.64 | 141.63 | 31.00 | 0.00 | 0.00 | 0.00 |
| July | 124.78 | 82.20 | 42.59 | 155.57 | 28.69 | 0.00 | 0.00 | 0.00 |
| August | 99.50 | 62.94 | 36.56 | 124.56 | 28.79 | 0.00 | 0.00 | 0.00 |
| September | 70.24 | 38.82 | 31.42 | 80.30 | 38.99 | 0.00 | 0.00 | 0.00 |
| October | 40.62 | 18.38 | 22.24 | 37.64 | 49.92 | 0.00 | 0.00 | 0.00 |
| November | 20.48 | 5.13 | 15.35 | 11.19 | 55.84 | 0.00 | 0.00 | 0.00 |
| December | 14.64 | 3.54 | 11.09 | 5.27 | 67.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 65.63 | 34.96 | 30.67 | 71.21 | 46.24 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14.64 | 3.54 | 11.09 | 5.27 | 28.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.78 | 82.20 | 53.08 | 155.57 | 67.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.42 | 3.80 | 13.62 | 6.55 | 62.84 | 0.00 | 0.00 | 0.00 |
| February | 32.05 | 11.83 | 20.22 | 23.47 | 58.34 | 0.00 | 0.00 | 0.00 |
| March | 52.31 | 22.06 | 30.26 | 47.85 | 52.07 | 0.00 | 0.00 | 0.00 |
| April | 84.39 | 42.97 | 41.42 | 90.69 | 44.25 | 0.00 | 0.00 | 0.00 |
| May | 109.45 | 56.36 | 53.08 | 126.41 | 37.82 | 0.00 | 0.00 | 0.00 |
| June | 119.44 | 69.80 | 49.64 | 141.63 | 31.00 | 0.00 | 0.00 | 0.00 |
| July | 124.78 | 82.20 | 42.59 | 155.57 | 28.69 | 0.00 | 0.00 | 0.00 |
| August | 99.50 | 62.94 | 36.56 | 124.56 | 28.79 | 0.00 | 0.00 | 0.00 |
| September | 70.24 | 38.82 | 31.42 | 80.30 | 38.99 | 0.00 | 0.00 | 0.00 |
| October | 40.62 | 18.38 | 22.24 | 37.64 | 49.92 | 0.00 | 0.00 | 0.00 |
| November | 20.48 | 5.13 | 15.35 | 11.19 | 55.84 | 0.00 | 0.00 | 0.00 |
| December | 14.64 | 3.54 | 11.09 | 5.27 | 67.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 65.63 | 34.96 | 30.67 | 71.21 | 46.24 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14.64 | 3.54 | 11.09 | 5.27 | 28.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.78 | 82.20 | 53.08 | 155.57 | 67.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.42 | 3.80 | 13.62 | 6.55 | 62.84 | 0.00 | 0.00 | 0.00 |
| February | 32.05 | 11.83 | 20.22 | 23.47 | 58.34 | 0.00 | 0.00 | 0.00 |
| March | 52.31 | 22.06 | 30.26 | 47.85 | 52.07 | 0.00 | 0.00 | 0.00 |
| April | 84.39 | 42.97 | 41.42 | 90.69 | 44.25 | 0.00 | 0.00 | 0.00 |
| May | 109.45 | 56.36 | 53.08 | 126.41 | 37.82 | 0.00 | 0.00 | 0.00 |
| June | 119.44 | 69.80 | 49.64 | 141.63 | 31.00 | 0.00 | 0.00 | 0.00 |
| July | 124.78 | 82.20 | 42.59 | 155.57 | 28.69 | 0.00 | 0.00 | 0.00 |
| August | 99.50 | 62.94 | 36.56 | 124.56 | 28.79 | 0.00 | 0.00 | 0.00 |
| September | 70.24 | 38.82 | 31.42 | 80.30 | 38.99 | 0.00 | 0.00 | 0.00 |
| October | 40.62 | 18.38 | 22.24 | 37.64 | 49.92 | 0.00 | 0.00 | 0.00 |
| November | 20.48 | 5.13 | 15.35 | 11.19 | 55.84 | 0.00 | 0.00 | 0.00 |
| December | 14.64 | 3.54 | 11.09 | 5.27 | 67.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 65.63 | 34.96 | 30.67 | 71.21 | 46.24 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14.64 | 3.54 | 11.09 | 5.27 | 28.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.78 | 82.20 | 53.08 | 155.57 | 67.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.42 | 3.80 | 13.62 | 6.55 | 62.84 | 0.00 | 0.00 | 0.00 |
| February | 32.05 | 11.83 | 20.22 | 23.47 | 58.34 | 0.00 | 0.00 | 0.00 |
| March | 52.31 | 22.06 | 30.26 | 47.85 | 52.07 | 0.00 | 0.00 | 0.00 |
| April | 84.39 | 42.97 | 41.42 | 90.69 | 44.25 | 0.00 | 0.00 | 0.00 |
| May | 109.45 | 56.36 | 53.08 | 126.41 | 37.82 | 0.00 | 0.00 | 0.00 |
| June | 119.44 | 69.80 | 49.64 | 141.63 | 31.00 | 0.00 | 0.00 | 0.00 |
| July | 124.78 | 82.20 | 42.59 | 155.57 | 28.69 | 0.00 | 0.00 | 0.00 |
| August | 99.50 | 62.94 | 36.56 | 124.56 | 28.79 | 0.00 | 0.00 | 0.00 |
| September | 70.24 | 38.82 | 31.42 | 80.30 | 38.99 | 0.00 | 0.00 | 0.00 |
| October | 40.62 | 18.38 | 22.24 | 37.64 | 49.92 | 0.00 | 0.00 | 0.00 |
| November | 20.48 | 5.13 | 15.35 | 11.19 | 55.84 | 0.00 | 0.00 | 0.00 |
| December | 14.64 | 3.54 | 11.09 | 5.27 | 67.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 65.63 | 34.96 | 30.67 | 71.21 | 46.24 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14.64 | 3.54 | 11.09 | 5.27 | 28.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.78 | 82.20 | 53.08 | 155.57 | 67.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.42 | 3.80 | 13.62 | 6.55 | 62.84 | 0.00 | 0.00 | 0.00 |
| February | 32.05 | 11.83 | 20.22 | 23.47 | 58.34 | 0.00 | 0.00 | 0.00 |
| March | 52.31 | 22.06 | 30.26 | 47.85 | 52.07 | 0.00 | 0.00 | 0.00 |
| April | 84.39 | 42.97 | 41.42 | 90.69 | 44.25 | 0.00 | 0.00 | 0.00 |
| May | 109.45 | 56.36 | 53.08 | 126.41 | 37.82 | 0.00 | 0.00 | 0.00 |
| June | 119.44 | 69.80 | 49.64 | 141.63 | 31.00 | 0.00 | 0.00 | 0.00 |
| July | 124.78 | 82.20 | 42.59 | 155.57 | 28.69 | 0.00 | 0.00 | 0.00 |
| August | 99.50 | 62.94 | 36.56 | 124.56 | 28.79 | 0.00 | 0.00 | 0.00 |
| September | 70.24 | 38.82 | 31.42 | 80.30 | 38.99 | 0.00 | 0.00 | 0.00 |
| October | 40.62 | 18.38 | 22.24 | 37.64 | 49.92 | 0.00 | 0.00 | 0.00 |
| November | 20.48 | 5.13 | 15.35 | 11.19 | 55.84 | 0.00 | 0.00 | 0.00 |
| December | 14.64 | 3.54 | 11.09 | 5.27 | 67.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 65.63 | 34.96 | 30.67 | 71.21 | 46.24 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14.64 | 3.54 | 11.09 | 5.27 | 28.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.78 | 82.20 | 53.08 | 155.57 | 67.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.42 | 3.80 | 13.62 | 6.55 | 62.84 | 0.00 | 0.00 | 0.00 |
| February | 32.05 | 11.83 | 20.22 | 23.47 | 58.34 | 0.00 | 0.00 | 0.00 |
| March | 52.31 | 22.06 | 30.26 | 47.85 | 52.07 | 0.00 | 0.00 | 0.00 |
| April | 84.39 | 42.97 | 41.42 | 90.69 | 44.25 | 0.00 | 0.00 | 0.00 |
| May | 109.45 | 56.36 | 53.08 | 126.41 | 37.82 | 0.00 | 0.00 | 0.00 |
| June | 119.44 | 69.80 | 49.64 | 141.63 | 31.00 | 0.00 | 0.00 | 0.00 |
| July | 124.78 | 82.20 | 42.59 | 155.57 | 28.69 | 0.00 | 0.00 | 0.00 |
| August | 99.50 | 62.94 | 36.56 | 124.56 | 28.79 | 0.00 | 0.00 | 0.00 |
| September | 70.24 | 38.82 | 31.42 | 80.30 | 38.99 | 0.00 | 0.00 | 0.00 |
| October | 40.62 | 18.38 | 22.24 | 37.64 | 49.92 | 0.00 | 0.00 | 0.00 |
| November | 20.48 | 5.13 | 15.35 | 11.19 | 55.84 | 0.00 | 0.00 | 0.00 |
| December | 14.64 | 3.54 | 11.09 | 5.27 | 67.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 65.63 | 34.96 | 30.67 | 71.21 | 46.24 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14.64 | 3.54 | 11.09 | 5.27 | 28.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.78 | 82.20 | 53.08 | 155.57 | 67.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.42 | 3.80 | 13.62 | 6.55 | 62.84 | 0.00 | 0.00 | 0.00 |
| February | 32.05 | 11.83 | 20.22 | 23.47 | 58.34 | 0.00 | 0.00 | 0.00 |
| March | 52.31 | 22.06 | 30.26 | 47.85 | 52.07 | 0.00 | 0.00 | 0.00 |
| April | 84.39 | 42.97 | 41.42 | 90.69 | 44.25 | 0.00 | 0.00 | 0.00 |
| May | 109.45 | 56.36 | 53.08 | 126.41 | 37.82 | 0.00 | 0.00 | 0.00 |
| June | 119.44 | 69.80 | 49.64 | 141.63 | 31.00 | 0.00 | 0.00 | 0.00 |
| July | 124.78 | 82.20 | 42.59 | 155.57 | 28.69 | 0.00 | 0.00 | 0.00 |
| August | 99.50 | 62.94 | 36.56 | 124.56 | 28.79 | 0.00 | 0.00 | 0.00 |
| September | 70.24 | 38.82 | 31.42 | 80.30 | 38.99 | 0.00 | 0.00 | 0.00 |
| October | 40.62 | 18.38 | 22.24 | 37.64 | 49.92 | 0.00 | 0.00 | 0.00 |
| November | 20.48 | 5.13 | 15.35 | 11.19 | 55.84 | 0.00 | 0.00 | 0.00 |
| December | 14.64 | 3.54 | 11.09 | 5.27 | 67.01 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 65.63 | 34.96 | 30.67 | 71.21 | 46.24 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14.64 | 3.54 | 11.09 | 5.27 | 28.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 124.78 | 82.20 | 53.08 | 155.57 | 67.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 7.70 | 1.95 | 5.75 | 1.98 | 37.89 | 0.00 | 0.00 | 0.00 |
| February | 14.13 | 5.01 | 9.11 | 7.53 | 34.36 | 0.00 | 0.00 | 0.00 |
| March | 21.09 | 7.64 | 13.46 | 14.65 | 30.30 | 0.00 | 0.00 | 0.00 |
| April | 32.70 | 13.59 | 19.11 | 28.98 | 24.76 | 0.00 | 0.00 | 0.00 |
| May | 34.79 | 12.10 | 22.70 | 32.73 | 21.07 | 0.00 | 0.00 | 0.00 |
| June | 41.67 | 18.13 | 23.54 | 43.66 | 16.48 | 0.00 | 0.00 | 0.00 |
| July | 38.81 | 17.42 | 21.39 | 43.18 | 14.23 | 0.00 | 0.00 | 0.00 |
| August | 38.14 | 19.08 | 19.06 | 44.71 | 13.58 | 0.00 | 0.00 | 0.00 |
| September | 28.20 | 13.01 | 15.19 | 28.03 | 20.15 | 0.00 | 0.00 | 0.00 |
| October | 18.38 | 7.81 | 10.57 | 14.10 | 27.73 | 0.00 | 0.00 | 0.00 |
| November | 9.01 | 2.54 | 6.47 | 3.55 | 33.65 | 0.00 | 0.00 | 0.00 |
| December | 7.39 | 2.38 | 5.01 | 2.68 | 39.36 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 24.38 | 10.08 | 14.30 | 22.23 | 26.09 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 7.39 | 1.95 | 5.01 | 1.98 | 13.58 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 41.67 | 19.08 | 23.54 | 44.71 | 39.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 91.13 | 23.10 | 68.03 | 23.39 | 448.50 | 0.00 | 0.00 | 0.00 |
| February | 167.22 | 59.35 | 107.87 | 89.16 | 406.53 | 0.00 | 0.00 | 0.00 |
| March | 249.67 | 90.38 | 159.29 | 173.57 | 358.58 | 0.00 | 0.00 | 0.00 |
| April | 387.03 | 160.81 | 226.22 | 343.65 | 293.06 | 0.00 | 0.00 | 0.00 |
| May | 411.84 | 143.18 | 268.66 | 388.38 | 249.41 | 0.00 | 0.00 | 0.00 |
| June | 493.22 | 214.60 | 278.62 | 517.63 | 195.08 | 0.00 | 0.00 | 0.00 |
| July | 459.30 | 206.15 | 253.15 | 512.49 | 168.45 | 0.00 | 0.00 | 0.00 |
| August | 451.43 | 225.82 | 225.61 | 530.43 | 160.78 | 0.00 | 0.00 | 0.00 |
| September | 333.76 | 153.93 | 179.83 | 332.68 | 238.53 | 0.00 | 0.00 | 0.00 |
| October | 217.55 | 92.43 | 125.11 | 167.08 | 328.14 | 0.00 | 0.00 | 0.00 |
| November | 106.63 | 30.10 | 76.53 | 41.98 | 398.31 | 0.00 | 0.00 | 0.00 |
| December | 87.46 | 28.16 | 59.30 | 31.76 | 465.87 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 288.55 | 119.26 | 169.29 | 263.60 | 308.78 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 87.46 | 23.10 | 59.30 | 23.39 | 160.78 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 493.22 | 225.82 | 278.62 | 530.43 | 465.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 46.51 | 11.79 | 34.72 | 8.66 | 311.80 | 326.83 | 0.00 | 0.00 |
| February | 85.35 | 30.29 | 55.06 | 37.92 | 273.07 | 200.00 | 0.00 | 0.00 |
| March | 127.43 | 46.13 | 81.30 | 81.62 | 222.82 | 37.50 | 0.00 | 0.00 |
| April | 197.54 | 82.08 | 115.46 | 169.90 | 170.48 | 0.00 | 0.00 | 0.00 |
| May | 210.20 | 73.08 | 137.12 | 195.49 | 141.68 | 0.00 | 0.00 | 0.00 |
| June | 251.74 | 109.53 | 142.21 | 262.16 | 110.85 | 0.00 | 0.00 | 0.00 |
| July | 234.43 | 105.22 | 129.20 | 259.27 | 96.59 | 0.00 | 0.00 | 0.00 |
| August | 230.41 | 115.26 | 115.15 | 268.58 | 93.30 | 0.00 | 0.00 | 0.00 |
| September | 170.35 | 78.57 | 91.79 | 166.75 | 137.84 | 0.00 | 0.00 | 0.00 |
| October | 111.04 | 47.18 | 63.86 | 80.82 | 198.57 | 0.00 | 0.00 | 0.00 |
| November | 54.42 | 15.36 | 39.06 | 18.12 | 259.46 | 129.67 | 0.00 | 0.00 |
| December | 44.64 | 14.37 | 30.27 | 12.91 | 316.50 | 309.83 | 0.00 | 0.00 |
| Annual Sum or Average | 147.28 | 60.87 | 86.40 | 130.68 | 194.04 | 1003.83 | 0.00 | 0.00 |
| Minimum of Months | 44.64 | 11.79 | 30.27 | 8.66 | 93.30 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 251.74 | 115.26 | 142.21 | 268.58 | 316.50 | 326.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 71.55 | 0.00 | 71.55 | 0.14 | 611.10 | 0.00 | 0.00 | 0.00 |
| February | 111.24 | 0.00 | 111.24 | 10.07 | 556.31 | 0.00 | 0.00 | 0.00 |
| March | 163.92 | 0.00 | 163.92 | 36.32 | 460.71 | 0.00 | 0.00 | 0.00 |
| April | 230.73 | 0.51 | 230.22 | 103.57 | 375.44 | 0.00 | 0.00 | 0.00 |
| May | 293.70 | 6.03 | 287.67 | 178.41 | 313.96 | 0.00 | 0.00 | 0.00 |
| June | 306.49 | 16.09 | 290.40 | 206.03 | 251.24 | 0.00 | 0.00 | 0.00 |
| July | 287.80 | 15.23 | 272.57 | 239.93 | 217.69 | 0.00 | 0.00 | 0.00 |
| August | 238.12 | 4.34 | 233.78 | 210.56 | 210.90 | 0.00 | 0.00 | 0.00 |
| September | 187.17 | 0.03 | 187.14 | 102.46 | 322.19 | 0.00 | 0.00 | 0.00 |
| October | 128.34 | 0.00 | 128.34 | 27.20 | 429.39 | 0.00 | 0.00 | 0.00 |
| November | 81.03 | 0.00 | 81.03 | 2.78 | 527.30 | 0.00 | 0.00 | 0.00 |
| December | 60.66 | 0.00 | 60.66 | 0.11 | 629.60 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 180.39 | 3.54 | 176.85 | 93.70 | 408.04 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 60.66 | 0.00 | 60.66 | 0.11 | 210.90 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 306.49 | 16.09 | 290.40 | 239.93 | 629.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 7.77 | 1.97 | 5.80 | 2.12 | 36.78 | 0.00 | 0.00 | 0.00 |
| February | 14.26 | 5.06 | 9.20 | 7.91 | 32.67 | 0.00 | 0.00 | 0.00 |
| March | 21.29 | 7.71 | 13.59 | 15.64 | 27.53 | 0.00 | 0.00 | 0.00 |
| April | 33.01 | 13.72 | 19.29 | 30.79 | 22.19 | 0.00 | 0.00 | 0.00 |
| May | 35.12 | 12.21 | 22.91 | 34.24 | 19.55 | 0.00 | 0.00 | 0.00 |
| June | 42.07 | 18.30 | 23.76 | 44.80 | 16.04 | 0.00 | 0.00 | 0.00 |
| July | 39.17 | 17.58 | 21.59 | 44.33 | 13.62 | 0.00 | 0.00 | 0.00 |
| August | 38.50 | 19.26 | 19.24 | 45.81 | 13.05 | 0.00 | 0.00 | 0.00 |
| September | 28.47 | 13.13 | 15.34 | 28.89 | 19.46 | 0.00 | 0.00 | 0.00 |
| October | 18.55 | 7.88 | 10.67 | 14.80 | 25.86 | 0.00 | 0.00 | 0.00 |
| November | 9.09 | 2.57 | 6.53 | 3.75 | 32.02 | 0.00 | 0.00 | 0.00 |
| December | 7.46 | 2.40 | 5.06 | 2.83 | 38.23 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 24.61 | 10.17 | 14.44 | 23.07 | 24.71 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 7.46 | 1.97 | 5.06 | 2.12 | 13.05 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 42.07 | 19.26 | 23.76 | 45.81 | 38.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 79.44 | 20.14 | 59.30 | 21.66 | 375.88 | 0.00 | 0.00 | 0.00 |
| February | 145.77 | 51.74 | 94.03 | 80.84 | 333.89 | 0.00 | 0.00 | 0.00 |
| March | 217.65 | 78.79 | 138.86 | 159.85 | 281.39 | 0.00 | 0.00 | 0.00 |
| April | 337.39 | 140.19 | 197.20 | 314.71 | 226.79 | 0.00 | 0.00 | 0.00 |
| May | 359.01 | 124.82 | 234.19 | 349.98 | 199.78 | 0.00 | 0.00 | 0.00 |
| June | 429.96 | 187.08 | 242.88 | 457.98 | 163.81 | 0.00 | 0.00 | 0.00 |
| July | 400.39 | 179.72 | 220.67 | 453.14 | 139.13 | 0.00 | 0.00 | 0.00 |
| August | 393.53 | 196.87 | 196.66 | 468.29 | 133.33 | 0.00 | 0.00 | 0.00 |
| September | 290.96 | 134.19 | 156.77 | 295.27 | 198.92 | 0.00 | 0.00 | 0.00 |
| October | 189.65 | 80.58 | 109.06 | 151.24 | 264.34 | 0.00 | 0.00 | 0.00 |
| November | 92.95 | 26.24 | 66.71 | 38.31 | 327.31 | 0.00 | 0.00 | 0.00 |
| December | 76.24 | 24.54 | 51.70 | 28.94 | 390.76 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 251.54 | 103.97 | 147.57 | 235.83 | 252.54 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 76.24 | 20.14 | 51.70 | 21.66 | 133.33 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 429.96 | 196.87 | 242.88 | 468.29 | 390.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 68.75 | 0.00 | 68.75 | 0.51 | 532.01 | 0.00 | 0.00 | 0.00 |
| February | 106.98 | 0.00 | 106.98 | 12.05 | 489.03 | 0.00 | 0.00 | 0.00 |
| March | 157.61 | 0.00 | 157.61 | 35.90 | 431.09 | 0.00 | 0.00 | 0.00 |
| April | 223.04 | 0.79 | 222.25 | 100.65 | 355.18 | 0.00 | 0.00 | 0.00 |
| May | 286.99 | 8.53 | 278.47 | 179.60 | 290.70 | 0.00 | 0.00 | 0.00 |
| June | 301.77 | 19.93 | 281.84 | 213.73 | 224.83 | 0.00 | 0.00 | 0.00 |
| July | 286.81 | 22.49 | 264.33 | 250.96 | 191.96 | 0.00 | 0.00 | 0.00 |
| August | 232.18 | 6.28 | 225.90 | 209.42 | 190.54 | 0.00 | 0.00 | 0.00 |
| September | 180.35 | 0.05 | 180.29 | 101.87 | 299.14 | 0.00 | 0.00 | 0.00 |
| October | 123.57 | 0.00 | 123.57 | 27.59 | 408.30 | 0.00 | 0.00 | 0.00 |
| November | 77.84 | 0.00 | 77.84 | 3.05 | 486.48 | 0.00 | 0.00 | 0.00 |
| December | 58.42 | 0.00 | 58.42 | 0.21 | 552.21 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 175.70 | 4.87 | 170.82 | 95.20 | 370.31 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 58.42 | 0.00 | 58.42 | 0.21 | 190.54 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 301.77 | 22.49 | 281.84 | 250.96 | 552.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 3.37 | 0.00 | 3.37 | 0.00 | 37.04 | 0.00 | 0.00 | 0.00 |
| February | 5.33 | 0.00 | 5.33 | 0.29 | 34.30 | 0.00 | 0.00 | 0.00 |
| March | 7.92 | 0.00 | 7.92 | 0.83 | 30.49 | 0.00 | 0.00 | 0.00 |
| April | 16.26 | 3.92 | 12.33 | 8.42 | 22.85 | 0.00 | 0.00 | 0.00 |
| May | 23.54 | 7.45 | 16.09 | 18.96 | 19.64 | 0.00 | 0.00 | 0.00 |
| June | 31.24 | 13.82 | 17.42 | 30.68 | 15.31 | 0.00 | 0.00 | 0.00 |
| July | 28.09 | 12.15 | 15.94 | 29.66 | 12.56 | 0.00 | 0.00 | 0.00 |
| August | 23.34 | 9.91 | 13.43 | 25.08 | 12.00 | 0.00 | 0.00 | 0.00 |
| September | 10.72 | 1.23 | 9.50 | 5.48 | 19.46 | 0.00 | 0.00 | 0.00 |
| October | 6.24 | 0.00 | 6.24 | 0.69 | 28.40 | 0.00 | 0.00 | 0.00 |
| November | 3.83 | 0.00 | 3.83 | 0.06 | 34.32 | 0.00 | 0.00 | 0.00 |
| December | 2.87 | 0.00 | 2.87 | 0.00 | 38.21 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 13.61 | 4.07 | 9.54 | 10.08 | 25.34 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 2.87 | 0.00 | 2.87 | 0.00 | 12.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 31.24 | 13.82 | 17.42 | 30.68 | 38.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 99.40 | 20.45 | 78.95 | 18.85 | 527.25 | 0.00 | 0.00 | 0.00 |
| February | 193.36 | 65.25 | 128.11 | 100.07 | 471.25 | 0.00 | 0.00 | 0.00 |
| March | 305.10 | 111.65 | 193.45 | 215.83 | 419.61 | 0.00 | 0.00 | 0.00 |
| April | 477.29 | 202.09 | 275.20 | 435.11 | 342.56 | 0.00 | 0.00 | 0.00 |
| May | 506.80 | 179.93 | 326.87 | 486.57 | 297.41 | 0.00 | 0.00 | 0.00 |
| June | 608.51 | 269.68 | 338.83 | 645.59 | 235.23 | 0.00 | 0.00 | 0.00 |
| July | 566.95 | 259.07 | 307.88 | 643.26 | 197.00 | 0.00 | 0.00 | 0.00 |
| August | 558.36 | 283.79 | 274.57 | 664.42 | 190.69 | 0.00 | 0.00 | 0.00 |
| September | 411.12 | 192.89 | 218.22 | 412.89 | 291.23 | 0.00 | 0.00 | 0.00 |
| October | 258.82 | 108.67 | 150.15 | 196.04 | 399.43 | 0.00 | 0.00 | 0.00 |
| November | 120.16 | 30.19 | 89.97 | 40.03 | 484.94 | 0.00 | 0.00 | 0.00 |
| December | 89.20 | 22.12 | 67.08 | 22.21 | 552.54 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 350.27 | 145.83 | 204.44 | 324.58 | 366.89 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 89.20 | 20.45 | 67.08 | 18.85 | 190.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 608.51 | 283.79 | 338.83 | 664.42 | 552.54 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.147835E+09 | 43593760.64 | 0.104241E+09 | 51914996.67 | 0.607751E+09 |
| February | 0.239405E+09 | 89975294.78 | 0.149430E+09 | 0.148727E+09 | 0.490195E+09 |
| March | 0.371411E+09 | 0.125361E+09 | 0.246050E+09 | 0.275411E+09 | 0.463804E+09 |
| April | 0.546834E+09 | 0.209076E+09 | 0.337758E+09 | 0.509787E+09 | 0.375737E+09 |
| May | 0.727103E+09 | 0.295383E+09 | 0.431721E+09 | 0.757408E+09 | 0.332749E+09 |
| June | 0.676717E+09 | 0.262747E+09 | 0.413970E+09 | 0.727538E+09 | 0.252499E+09 |
| July | 0.863858E+09 | 0.454088E+09 | 0.409770E+09 | 0.105617E+10 | 0.225713E+09 |
| August | 0.714617E+09 | 0.364904E+09 | 0.349713E+09 | 0.888675E+09 | 0.222910E+09 |
| September | 0.563174E+09 | 0.270223E+09 | 0.292951E+09 | 0.611604E+09 | 0.330160E+09 |
| October | 0.331304E+09 | 0.134991E+09 | 0.196314E+09 | 0.265282E+09 | 0.454914E+09 |
| November | 0.159665E+09 | 45032238.26 | 0.114633E+09 | 69899489.93 | 0.511868E+09 |
| December | 0.138704E+09 | 47530277.11 | 91173554.66 | 63741210.56 | 0.627845E+09 |
| Annual Sum or Average | 0.548063E+10 | 0.234290E+10 | 0.313772E+10 | 0.542616E+10 | 0.489615E+10 |
| Minimum of Months | 0.138704E+09 | 43593760.64 | 91173554.66 | 51914996.67 | 0.222910E+09 |
| Maximum of Months | 0.863858E+09 | 0.454088E+09 | 0.431721E+09 | 0.105617E+10 | 0.627845E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 59321879.34 | 35225560.34 | 24096319.00 | 50149359.59 | 85847418.84 |
| February | 82399436.64 | 51006309.56 | 31393127.09 | 80634739.94 | 70214206.22 |
| March | 98134959.90 | 52334211.29 | 45800748.61 | 99765962.02 | 70464793.30 |
| April | 0.100270E+09 | 43536421.87 | 56733237.99 | 0.107560E+09 | 59164045.07 |
| May | 94739956.41 | 28223894.04 | 66516062.36 | 0.101274E+09 | 53056235.22 |
| June | 83881813.75 | 22521115.87 | 61360697.89 | 92212194.00 | 40415541.77 |
| July | 94525982.48 | 34620310.11 | 59905672.36 | 0.119098E+09 | 36096858.61 |
| August | 0.101556E+09 | 47357183.19 | 54198976.02 | 0.133539E+09 | 34960476.25 |
| September | 0.108890E+09 | 60132686.37 | 48757580.29 | 0.130129E+09 | 50768250.82 |
| October | 0.101924E+09 | 62930431.80 | 38993516.36 | 0.110096E+09 | 67575107.58 |
| November | 58316921.67 | 33420467.44 | 24896454.24 | 52112671.89 | 74353440.10 |
| December | 63050052.84 | 40802147.70 | 22247905.14 | 59350706.07 | 90129152.94 |
| Annual Sum or Average | 0.104701E+10 | 0.512111E+09 | 0.534900E+09 | 0.113592E+10 | 0.733046E+09 |
| Minimum of Months | 58316921.67 | 22521115.87 | 22247905.14 | 50149359.59 | 34960476.25 |
| Maximum of Months | 0.108890E+09 | 62930431.80 | 66516062.36 | 0.133539E+09 | 90129152.94 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.411711E+09 | 0.244476E+09 | 0.167235E+09 | 0.348051E+09 | 0.595806E+09 |
| February | 0.571876E+09 | 0.353999E+09 | 0.217877E+09 | 0.559628E+09 | 0.487307E+09 |
| March | 0.681085E+09 | 0.363215E+09 | 0.317870E+09 | 0.692405E+09 | 0.489046E+09 |
| April | 0.695900E+09 | 0.302155E+09 | 0.393745E+09 | 0.746494E+09 | 0.410644E+09 |
| May | 0.657523E+09 | 0.195882E+09 | 0.461641E+09 | 0.702648E+09 | 0.369089E+09 |
| June | 0.582164E+09 | 0.156303E+09 | 0.425861E+09 | 0.639009E+09 | 0.281465E+09 |
| July | 0.656038E+09 | 0.240275E+09 | 0.415763E+09 | 0.825046E+09 | 0.251776E+09 |
| August | 0.704829E+09 | 0.328673E+09 | 0.376157E+09 | 0.926455E+09 | 0.242924E+09 |
| September | 0.755730E+09 | 0.417338E+09 | 0.338392E+09 | 0.903133E+09 | 0.352339E+09 |
| October | 0.707382E+09 | 0.436755E+09 | 0.270626E+09 | 0.764100E+09 | 0.468991E+09 |
| November | 0.404736E+09 | 0.231948E+09 | 0.172789E+09 | 0.361677E+09 | 0.516034E+09 |
| December | 0.437586E+09 | 0.283179E+09 | 0.154407E+09 | 0.411911E+09 | 0.625522E+09 |
| Annual Sum or Average | 0.726656E+10 | 0.355420E+10 | 0.371236E+10 | 0.788056E+10 | 0.509094E+10 |
| Minimum of Months | 0.404736E+09 | 0.156303E+09 | 0.154407E+09 | 0.348051E+09 | 0.242924E+09 |
| Maximum of Months | 0.755730E+09 | 0.436755E+09 | 0.461641E+09 | 0.926455E+09 | 0.625522E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.756530E+09 | 0.449231E+09 | 0.307299E+09 | 0.625171E+09 | 0.117249E+10 |
| February | 0.105084E+10 | 0.650483E+09 | 0.400355E+09 | 0.100899E+10 | 0.968128E+09 |
| March | 0.125151E+10 | 0.667418E+09 | 0.584094E+09 | 0.125096E+10 | 0.985655E+09 |
| April | 0.127873E+10 | 0.555219E+09 | 0.723515E+09 | 0.135230E+10 | 0.818195E+09 |
| May | 0.120821E+10 | 0.359939E+09 | 0.848274E+09 | 0.128364E+10 | 0.719858E+09 |
| June | 0.106974E+10 | 0.287212E+09 | 0.782528E+09 | 0.117139E+10 | 0.543609E+09 |
| July | 0.120548E+10 | 0.441512E+09 | 0.763972E+09 | 0.153444E+10 | 0.460726E+09 |
| August | 0.129514E+10 | 0.603946E+09 | 0.691195E+09 | 0.171417E+10 | 0.450594E+09 |
| September | 0.138867E+10 | 0.766871E+09 | 0.621802E+09 | 0.165760E+10 | 0.677717E+09 |
| October | 0.129983E+10 | 0.802551E+09 | 0.497282E+09 | 0.138965E+10 | 0.933351E+09 |
| November | 0.743714E+09 | 0.426211E+09 | 0.317503E+09 | 0.649209E+09 | 0.102839E+10 |
| December | 0.804076E+09 | 0.520349E+09 | 0.283727E+09 | 0.742223E+09 | 0.124182E+10 |
| Annual Sum or Average | 0.133525E+11 | 0.653094E+10 | 0.682155E+10 | 0.143797E+11 | 0.100005E+11 |
| Minimum of Months | 0.743714E+09 | 0.287212E+09 | 0.283727E+09 | 0.625171E+09 | 0.450594E+09 |
| Maximum of Months | 0.138867E+10 | 0.802551E+09 | 0.848274E+09 | 0.171417E+10 | 0.124182E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.756530E+09 | 0.449231E+09 | 0.307299E+09 | 0.625171E+09 | 0.117249E+10 |
| February | 0.105084E+10 | 0.650483E+09 | 0.400355E+09 | 0.100899E+10 | 0.968128E+09 |
| March | 0.125151E+10 | 0.667418E+09 | 0.584094E+09 | 0.125096E+10 | 0.985655E+09 |
| April | 0.127873E+10 | 0.555219E+09 | 0.723515E+09 | 0.135230E+10 | 0.818195E+09 |
| May | 0.120821E+10 | 0.359939E+09 | 0.848274E+09 | 0.128364E+10 | 0.719858E+09 |
| June | 0.106974E+10 | 0.287212E+09 | 0.782528E+09 | 0.117139E+10 | 0.543609E+09 |
| July | 0.120548E+10 | 0.441512E+09 | 0.763972E+09 | 0.153444E+10 | 0.460726E+09 |
| August | 0.129514E+10 | 0.603946E+09 | 0.691195E+09 | 0.171417E+10 | 0.450594E+09 |
| September | 0.138867E+10 | 0.766871E+09 | 0.621802E+09 | 0.165760E+10 | 0.677717E+09 |
| October | 0.129983E+10 | 0.802551E+09 | 0.497282E+09 | 0.138965E+10 | 0.933351E+09 |
| November | 0.743714E+09 | 0.426211E+09 | 0.317503E+09 | 0.649209E+09 | 0.102839E+10 |
| December | 0.804076E+09 | 0.520349E+09 | 0.283727E+09 | 0.742223E+09 | 0.124182E+10 |
| Annual Sum or Average | 0.133525E+11 | 0.653094E+10 | 0.682155E+10 | 0.143797E+11 | 0.100005E+11 |
| Minimum of Months | 0.743714E+09 | 0.287212E+09 | 0.283727E+09 | 0.625171E+09 | 0.450594E+09 |
| Maximum of Months | 0.138867E+10 | 0.802551E+09 | 0.848274E+09 | 0.171417E+10 | 0.124182E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.756516E+09 | 0.449222E+09 | 0.307293E+09 | 0.625159E+09 | 0.117247E+10 |
| February | 0.105082E+10 | 0.650470E+09 | 0.400347E+09 | 0.100897E+10 | 0.968109E+09 |
| March | 0.125149E+10 | 0.667405E+09 | 0.584083E+09 | 0.125093E+10 | 0.985636E+09 |
| April | 0.127871E+10 | 0.555209E+09 | 0.723501E+09 | 0.135227E+10 | 0.818179E+09 |
| May | 0.120819E+10 | 0.359932E+09 | 0.848258E+09 | 0.128362E+10 | 0.719844E+09 |
| June | 0.106972E+10 | 0.287206E+09 | 0.782513E+09 | 0.117137E+10 | 0.543599E+09 |
| July | 0.120546E+10 | 0.441504E+09 | 0.763957E+09 | 0.153441E+10 | 0.460717E+09 |
| August | 0.129512E+10 | 0.603934E+09 | 0.691182E+09 | 0.171414E+10 | 0.450585E+09 |
| September | 0.138865E+10 | 0.766857E+09 | 0.621790E+09 | 0.165757E+10 | 0.677704E+09 |
| October | 0.129981E+10 | 0.802536E+09 | 0.497272E+09 | 0.138962E+10 | 0.933333E+09 |
| November | 0.743700E+09 | 0.426203E+09 | 0.317497E+09 | 0.649197E+09 | 0.102837E+10 |
| December | 0.804060E+09 | 0.520339E+09 | 0.283721E+09 | 0.742208E+09 | 0.124180E+10 |
| Annual Sum or Average | 0.133522E+11 | 0.653082E+10 | 0.682141E+10 | 0.143795E+11 | 0.100003E+11 |
| Minimum of Months | 0.743700E+09 | 0.287206E+09 | 0.283721E+09 | 0.625159E+09 | 0.450585E+09 |
| Maximum of Months | 0.138865E+10 | 0.802536E+09 | 0.848258E+09 | 0.171414E+10 | 0.124180E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 49278394.98 | 14531301.98 | 34747093.00 | 17017250.77 | 0.221741E+09 |
| February | 79802069.13 | 29991864.90 | 49810204.23 | 49555266.10 | 0.177813E+09 |
| March | 0.123804E+09 | 41787206.48 | 82016913.83 | 91661656.19 | 0.169255E+09 |
| April | 0.182279E+09 | 69692155.54 | 0.112587E+09 | 0.168269E+09 | 0.137454E+09 |
| May | 0.242369E+09 | 98461254.39 | 0.143907E+09 | 0.249347E+09 | 0.121425E+09 |
| June | 0.225573E+09 | 87582538.84 | 0.137991E+09 | 0.239101E+09 | 91268864.80 |
| July | 0.287954E+09 | 0.151363E+09 | 0.136590E+09 | 0.353073E+09 | 76578582.49 |
| August | 0.238207E+09 | 0.121635E+09 | 0.116571E+09 | 0.298358E+09 | 74428965.78 |
| September | 0.187725E+09 | 90074743.68 | 97650664.86 | 0.205764E+09 | 0.112998E+09 |
| October | 0.110435E+09 | 44997027.39 | 65438053.22 | 89336947.43 | 0.161588E+09 |
| November | 53221922.87 | 15010796.12 | 38211126.74 | 23474422.97 | 0.184769E+09 |
| December | 46234764.70 | 15843478.51 | 30391286.19 | 21621572.79 | 0.227682E+09 |
| Annual Sum or Average | 0.182688E+10 | 0.780971E+09 | 0.104591E+10 | 0.180658E+10 | 0.175700E+10 |
| Minimum of Months | 46234764.70 | 14531301.98 | 30391286.19 | 17017250.77 | 74428965.78 |
| Maximum of Months | 0.287954E+09 | 0.151363E+09 | 0.143907E+09 | 0.353073E+09 | 0.227682E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.147835E+09 | 43593760.64 | 0.104241E+09 | 57081207.89 | 0.591682E+09 |
| February | 0.239405E+09 | 89975294.78 | 0.149430E+09 | 0.160205E+09 | 0.467030E+09 |
| March | 0.371411E+09 | 0.125361E+09 | 0.246050E+09 | 0.296263E+09 | 0.433904E+09 |
| April | 0.546834E+09 | 0.209076E+09 | 0.337758E+09 | 0.532552E+09 | 0.351946E+09 |
| May | 0.727103E+09 | 0.295383E+09 | 0.431721E+09 | 0.774001E+09 | 0.318457E+09 |
| June | 0.676717E+09 | 0.262747E+09 | 0.413970E+09 | 0.740853E+09 | 0.243478E+09 |
| July | 0.863858E+09 | 0.454088E+09 | 0.409770E+09 | 0.107972E+10 | 0.210923E+09 |
| August | 0.714617E+09 | 0.364904E+09 | 0.349713E+09 | 0.915274E+09 | 0.202782E+09 |
| September | 0.563174E+09 | 0.270223E+09 | 0.292951E+09 | 0.634898E+09 | 0.302107E+09 |
| October | 0.331304E+09 | 0.134991E+09 | 0.196314E+09 | 0.285510E+09 | 0.418734E+09 |
| November | 0.159665E+09 | 45032238.26 | 0.114633E+09 | 77504713.58 | 0.487584E+09 |
| December | 0.138704E+09 | 47530277.11 | 91173554.66 | 70549902.61 | 0.605243E+09 |
| Annual Sum or Average | 0.548063E+10 | 0.234290E+10 | 0.313772E+10 | 0.562442E+10 | 0.463387E+10 |
| Minimum of Months | 0.138704E+09 | 43593760.64 | 91173554.66 | 57081207.89 | 0.202782E+09 |
| Maximum of Months | 0.863858E+09 | 0.454088E+09 | 0.431721E+09 | 0.107972E+10 | 0.605243E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 10992825.48 | 0.00 | 10992825.48 | 84575.92 | 95539302.11 |
| February | 15232019.72 | 0.00 | 15232019.72 | 1662287.94 | 77282076.15 |
| March | 24749986.40 | 0.00 | 24749986.40 | 5517075.09 | 69522169.56 |
| April | 33502861.78 | 119990.70 | 33382871.08 | 15133834.10 | 54576833.96 |
| May | 45277417.51 | 1486181.69 | 43791235.82 | 27799671.76 | 47279018.85 |
| June | 45677518.91 | 3405455.28 | 42272063.63 | 33446565.47 | 34982306.19 |
| July | 45319808.86 | 4033082.14 | 41286726.72 | 44166680.41 | 30173783.03 |
| August | 36246215.89 | 1041421.53 | 35204794.36 | 37609563.05 | 28650225.96 |
| September | 26875359.46 | 6258.49 | 26869100.97 | 15111929.87 | 46402664.99 |
| October | 19181801.24 | 0.00 | 19181801.24 | 3941962.40 | 65869560.63 |
| November | 12055025.38 | 0.00 | 12055025.38 | 516565.83 | 78563165.83 |
| December | 9174342.71 | 0.00 | 9174342.71 | 35733.40 | 96514956.83 |
| Annual Sum or Average | 0.324285E+09 | 10092389.83 | 0.314193E+09 | 0.185026E+09 | 0.725356E+09 |
| Minimum of Months | 9174342.71 | 0.00 | 9174342.71 | 35733.40 | 28650225.96 |
| Maximum of Months | 45677518.91 | 4033082.14 | 43791235.82 | 44166680.41 | 96514956.83 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 80235444.37 | 0.00 | 80235444.37 | 828473.10 | 0.661171E+09 |
| February | 0.111608E+09 | 0.00 | 0.111608E+09 | 13554244.31 | 0.533028E+09 |
| March | 0.181541E+09 | 0.00 | 0.181541E+09 | 46362368.01 | 0.480649E+09 |
| April | 0.246406E+09 | 832770.11 | 0.245573E+09 | 0.119830E+09 | 0.378139E+09 |
| May | 0.331172E+09 | 10314529.98 | 0.320858E+09 | 0.212979E+09 | 0.328708E+09 |
| June | 0.334463E+09 | 23634842.85 | 0.310828E+09 | 0.253401E+09 | 0.244162E+09 |
| July | 0.330923E+09 | 27990754.48 | 0.302933E+09 | 0.326549E+09 | 0.211197E+09 |
| August | 0.265797E+09 | 7228299.86 | 0.258569E+09 | 0.278257E+09 | 0.200844E+09 |
| September | 0.198196E+09 | 46982.93 | 0.198149E+09 | 0.118662E+09 | 0.323056E+09 |
| October | 0.141146E+09 | 0.00 | 0.141146E+09 | 33801783.04 | 0.455570E+09 |
| November | 87966796.76 | 0.00 | 87966796.76 | 4678273.82 | 0.543495E+09 |
| December | 67292390.43 | 0.00 | 67292390.43 | 341036.75 | 0.668264E+09 |
| Annual Sum or Average | 0.237675E+10 | 70048180.20 | 0.230670E+10 | 0.140924E+10 | 0.502828E+10 |
| Minimum of Months | 67292390.43 | 0.00 | 67292390.43 | 341036.75 | 0.200844E+09 |
| Maximum of Months | 0.334463E+09 | 27990754.48 | 0.320858E+09 | 0.326549E+09 | 0.668264E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.132930E+09 | 0.00 | 0.132930E+09 | 86121.15 | 0.130191E+10 |
| February | 0.184287E+09 | 0.00 | 0.184287E+09 | 15102202.63 | 0.106610E+10 |
| March | 0.299648E+09 | 0.00 | 0.299648E+09 | 48107365.06 | 0.978647E+09 |
| April | 0.402904E+09 | 558727.13 | 0.402345E+09 | 0.157675E+09 | 0.766830E+09 |
| May | 0.538603E+09 | 12041777.56 | 0.526561E+09 | 0.313563E+09 | 0.660242E+09 |
| June | 0.534314E+09 | 28665744.83 | 0.505648E+09 | 0.373285E+09 | 0.481675E+09 |
| July | 0.528800E+09 | 33052257.76 | 0.495748E+09 | 0.531512E+09 | 0.390740E+09 |
| August | 0.430812E+09 | 7097319.53 | 0.423714E+09 | 0.471025E+09 | 0.370656E+09 |
| September | 0.325503E+09 | 53250.84 | 0.325450E+09 | 0.177797E+09 | 0.613048E+09 |
| October | 0.232104E+09 | 0.00 | 0.232104E+09 | 35409995.11 | 0.912875E+09 |
| November | 0.145834E+09 | 0.00 | 0.145834E+09 | 3703139.87 | 0.109186E+10 |
| December | 0.110792E+09 | 0.00 | 0.110792E+09 | 121955.32 | 0.133114E+10 |
| Annual Sum or Average | 0.386653E+10 | 81469077.65 | 0.378506E+10 | 0.212739E+10 | 0.996574E+10 |
| Minimum of Months | 0.110792E+09 | 0.00 | 0.110792E+09 | 86121.15 | 0.370656E+09 |
| Maximum of Months | 0.538603E+09 | 33052257.76 | 0.526561E+09 | 0.531512E+09 | 0.133114E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.140238E+09 | 0.00 | 0.140238E+09 | 279938.69 | 0.130009E+10 |
| February | 0.194323E+09 | 0.00 | 0.194323E+09 | 17767990.27 | 0.106266E+10 |
| March | 0.315752E+09 | 0.00 | 0.315752E+09 | 57906578.12 | 0.974777E+09 |
| April | 0.426421E+09 | 1193276.33 | 0.425228E+09 | 0.176843E+09 | 0.760819E+09 |
| May | 0.572607E+09 | 16144419.81 | 0.556462E+09 | 0.344819E+09 | 0.649841E+09 |
| June | 0.574504E+09 | 38188573.39 | 0.536315E+09 | 0.418277E+09 | 0.475095E+09 |
| July | 0.565124E+09 | 41736508.89 | 0.523388E+09 | 0.572616E+09 | 0.386224E+09 |
| August | 0.458575E+09 | 10980063.01 | 0.447595E+09 | 0.496120E+09 | 0.363775E+09 |
| September | 0.342767E+09 | 57191.21 | 0.342709E+09 | 0.194251E+09 | 0.614894E+09 |
| October | 0.244720E+09 | 0.00 | 0.244720E+09 | 42527290.36 | 0.911362E+09 |
| November | 0.153788E+09 | 0.00 | 0.153788E+09 | 4640547.24 | 0.108916E+10 |
| December | 0.117043E+09 | 0.00 | 0.117043E+09 | 192350.09 | 0.133125E+10 |
| Annual Sum or Average | 0.410586E+10 | 0.108300E+09 | 0.399756E+10 | 0.232624E+10 | 0.991994E+10 |
| Minimum of Months | 0.117043E+09 | 0.00 | 0.117043E+09 | 192350.09 | 0.363775E+09 |
| Maximum of Months | 0.574504E+09 | 41736508.89 | 0.556462E+09 | 0.572616E+09 | 0.133125E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.140275E+09 | 0.00 | 0.140275E+09 | 281119.00 | 0.130005E+10 |
| February | 0.194379E+09 | 0.00 | 0.194379E+09 | 17783443.38 | 0.106262E+10 |
| March | 0.315845E+09 | 0.00 | 0.315845E+09 | 57973344.03 | 0.974737E+09 |
| April | 0.427536E+09 | 1522734.80 | 0.426013E+09 | 0.177113E+09 | 0.759215E+09 |
| May | 0.575289E+09 | 17541272.42 | 0.557747E+09 | 0.345774E+09 | 0.646661E+09 |
| June | 0.576662E+09 | 39456813.85 | 0.537206E+09 | 0.419266E+09 | 0.472891E+09 |
| July | 0.569906E+09 | 45145494.57 | 0.524760E+09 | 0.576499E+09 | 0.382683E+09 |
| August | 0.462231E+09 | 13087122.42 | 0.449144E+09 | 0.500168E+09 | 0.361730E+09 |
| September | 0.342954E+09 | 70569.90 | 0.342884E+09 | 0.194371E+09 | 0.614756E+09 |
| October | 0.244797E+09 | 0.00 | 0.244797E+09 | 42578253.98 | 0.911333E+09 |
| November | 0.153829E+09 | 0.00 | 0.153829E+09 | 4647226.35 | 0.108913E+10 |
| December | 0.117078E+09 | 0.00 | 0.117078E+09 | 192706.58 | 0.133122E+10 |
| Annual Sum or Average | 0.412078E+10 | 0.116824E+09 | 0.400396E+10 | 0.233665E+10 | 0.990702E+10 |
| Minimum of Months | 0.117078E+09 | 0.00 | 0.117078E+09 | 192706.58 | 0.361730E+09 |
| Maximum of Months | 0.576662E+09 | 45145494.57 | 0.557747E+09 | 0.576499E+09 | 0.133122E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.147835E+09 | 43593760.64 | 0.104241E+09 | 52392995.56 | 0.606199E+09 |
| February | 0.239405E+09 | 89975294.78 | 0.149430E+09 | 0.149099E+09 | 0.489853E+09 |
| March | 0.371411E+09 | 0.125361E+09 | 0.246050E+09 | 0.276227E+09 | 0.463115E+09 |
| April | 0.546834E+09 | 0.209076E+09 | 0.337758E+09 | 0.511310E+09 | 0.374504E+09 |
| May | 0.727103E+09 | 0.295383E+09 | 0.431721E+09 | 0.759265E+09 | 0.331403E+09 |
| June | 0.676717E+09 | 0.262747E+09 | 0.413970E+09 | 0.729580E+09 | 0.251219E+09 |
| July | 0.863858E+09 | 0.454088E+09 | 0.409770E+09 | 0.105887E+10 | 0.224003E+09 |
| August | 0.714617E+09 | 0.364904E+09 | 0.349713E+09 | 0.890453E+09 | 0.221842E+09 |
| September | 0.563174E+09 | 0.270223E+09 | 0.292951E+09 | 0.612652E+09 | 0.329416E+09 |
| October | 0.331304E+09 | 0.134991E+09 | 0.196314E+09 | 0.265914E+09 | 0.454329E+09 |
| November | 0.159665E+09 | 45032238.26 | 0.114633E+09 | 70282655.61 | 0.510964E+09 |
| December | 0.138704E+09 | 47530277.11 | 91173554.66 | 64710622.86 | 0.624128E+09 |
| Annual Sum or Average | 0.548063E+10 | 0.234290E+10 | 0.313772E+10 | 0.544075E+10 | 0.488097E+10 |
| Minimum of Months | 0.138704E+09 | 43593760.64 | 91173554.66 | 52392995.56 | 0.221842E+09 |
| Maximum of Months | 0.863858E+09 | 0.454088E+09 | 0.431721E+09 | 0.105887E+10 | 0.624128E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 56098411.63 | 34007753.26 | 22090658.37 | 47999873.82 | 86334628.41 |
| February | 79908824.53 | 50810734.65 | 29098089.88 | 78445033.44 | 69852849.15 |
| March | 94510947.90 | 52287588.41 | 42223359.50 | 96072321.38 | 69864192.35 |
| April | 95210318.82 | 43536421.87 | 51673896.95 | 0.102047E+09 | 58644324.88 |
| May | 88570322.36 | 28223894.04 | 60346428.32 | 94378242.09 | 52644921.45 |
| June | 77525067.38 | 22521115.87 | 55003951.51 | 85094766.70 | 39968203.54 |
| July | 88554225.17 | 34620310.11 | 53933915.05 | 0.112526E+09 | 35324041.61 |
| August | 96370218.72 | 47357183.19 | 49013035.53 | 0.127815E+09 | 34059336.99 |
| September | 0.104627E+09 | 60124050.75 | 44503431.13 | 0.125349E+09 | 49803766.74 |
| October | 98812612.95 | 62810978.00 | 36001634.96 | 0.106978E+09 | 66899323.79 |
| November | 55900550.84 | 32896313.40 | 23004237.43 | 50337133.65 | 74337512.65 |
| December | 58024977.13 | 38099453.13 | 19925524.00 | 55445189.46 | 90849910.06 |
| Annual Sum or Average | 0.994114E+09 | 0.507296E+09 | 0.486818E+09 | 0.108249E+10 | 0.728583E+09 |
| Minimum of Months | 55900550.84 | 22521115.87 | 19925524.00 | 47999873.82 | 34059336.99 |
| Maximum of Months | 0.104627E+09 | 62810978.00 | 60346428.32 | 0.127815E+09 | 90849910.06 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.382837E+09 | 0.234802E+09 | 0.148035E+09 | 0.327083E+09 | 0.596818E+09 |
| February | 0.547334E+09 | 0.352641E+09 | 0.194693E+09 | 0.537032E+09 | 0.482190E+09 |
| March | 0.643897E+09 | 0.362889E+09 | 0.281007E+09 | 0.654102E+09 | 0.483154E+09 |
| April | 0.643688E+09 | 0.302155E+09 | 0.341533E+09 | 0.689029E+09 | 0.406164E+09 |
| May | 0.593852E+09 | 0.195882E+09 | 0.397970E+09 | 0.631037E+09 | 0.366073E+09 |
| June | 0.516563E+09 | 0.156303E+09 | 0.360260E+09 | 0.565153E+09 | 0.278193E+09 |
| July | 0.594409E+09 | 0.240275E+09 | 0.354135E+09 | 0.756345E+09 | 0.245236E+09 |
| August | 0.651310E+09 | 0.328673E+09 | 0.322638E+09 | 0.866688E+09 | 0.234457E+09 |
| September | 0.711788E+09 | 0.417278E+09 | 0.294510E+09 | 0.853368E+09 | 0.342846E+09 |
| October | 0.675914E+09 | 0.435926E+09 | 0.239988E+09 | 0.731941E+09 | 0.461683E+09 |
| November | 0.382423E+09 | 0.228222E+09 | 0.154201E+09 | 0.344268E+09 | 0.513652E+09 |
| December | 0.391707E+09 | 0.259436E+09 | 0.132271E+09 | 0.372393E+09 | 0.627768E+09 |
| Annual Sum or Average | 0.673572E+10 | 0.351448E+10 | 0.322124E+10 | 0.732844E+10 | 0.503823E+10 |
| Minimum of Months | 0.382423E+09 | 0.156303E+09 | 0.132271E+09 | 0.327083E+09 | 0.234457E+09 |
| Maximum of Months | 0.711788E+09 | 0.435926E+09 | 0.397970E+09 | 0.866688E+09 | 0.627768E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.678599E+09 | 0.417024E+09 | 0.261575E+09 | 0.573021E+09 | 0.119162E+10 |
| February | 0.998029E+09 | 0.646782E+09 | 0.351247E+09 | 0.962171E+09 | 0.961030E+09 |
| March | 0.117360E+10 | 0.666571E+09 | 0.507027E+09 | 0.117215E+10 | 0.976946E+09 |
| April | 0.116972E+10 | 0.555219E+09 | 0.614496E+09 | 0.123239E+10 | 0.812328E+09 |
| May | 0.107527E+10 | 0.359939E+09 | 0.715331E+09 | 0.113386E+10 | 0.716993E+09 |
| June | 0.932764E+09 | 0.287212E+09 | 0.645552E+09 | 0.101770E+10 | 0.539377E+09 |
| July | 0.107680E+10 | 0.441512E+09 | 0.635292E+09 | 0.139078E+10 | 0.447424E+09 |
| August | 0.118339E+10 | 0.603946E+09 | 0.579448E+09 | 0.159029E+10 | 0.432482E+09 |
| September | 0.129696E+10 | 0.766765E+09 | 0.530190E+09 | 0.155443E+10 | 0.658663E+09 |
| October | 0.123169E+10 | 0.798979E+09 | 0.432711E+09 | 0.132150E+10 | 0.921121E+09 |
| November | 0.689716E+09 | 0.414282E+09 | 0.275433E+09 | 0.609782E+09 | 0.103206E+10 |
| December | 0.680794E+09 | 0.450674E+09 | 0.230120E+09 | 0.643047E+09 | 0.126883E+10 |
| Annual Sum or Average | 0.121873E+11 | 0.640891E+10 | 0.577842E+10 | 0.132011E+11 | 0.995888E+10 |
| Minimum of Months | 0.678599E+09 | 0.287212E+09 | 0.230120E+09 | 0.573021E+09 | 0.432482E+09 |
| Maximum of Months | 0.129696E+10 | 0.798979E+09 | 0.715331E+09 | 0.159029E+10 | 0.126883E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.678075E+09 | 0.416721E+09 | 0.261354E+09 | 0.572989E+09 | 0.119232E+10 |
| February | 0.995026E+09 | 0.645185E+09 | 0.349841E+09 | 0.961990E+09 | 0.965549E+09 |
| March | 0.117272E+10 | 0.666151E+09 | 0.506570E+09 | 0.117191E+10 | 0.978111E+09 |
| April | 0.116957E+10 | 0.555219E+09 | 0.614355E+09 | 0.123223E+10 | 0.812323E+09 |
| May | 0.107510E+10 | 0.359939E+09 | 0.715159E+09 | 0.113367E+10 | 0.716994E+09 |
| June | 0.932587E+09 | 0.287212E+09 | 0.645375E+09 | 0.101751E+10 | 0.539379E+09 |
| July | 0.107664E+10 | 0.441512E+09 | 0.635126E+09 | 0.139059E+10 | 0.447413E+09 |
| August | 0.118325E+10 | 0.603946E+09 | 0.579304E+09 | 0.159013E+10 | 0.432464E+09 |
| September | 0.129660E+10 | 0.766617E+09 | 0.529985E+09 | 0.155415E+10 | 0.658930E+09 |
| October | 0.122967E+10 | 0.797785E+09 | 0.431889E+09 | 0.132112E+10 | 0.924052E+09 |
| November | 0.687801E+09 | 0.413131E+09 | 0.274670E+09 | 0.609444E+09 | 0.103457E+10 |
| December | 0.680439E+09 | 0.450434E+09 | 0.230005E+09 | 0.643019E+09 | 0.126927E+10 |
| Annual Sum or Average | 0.121775E+11 | 0.640385E+10 | 0.577363E+10 | 0.131987E+11 | 0.997138E+10 |
| Minimum of Months | 0.678075E+09 | 0.287212E+09 | 0.230005E+09 | 0.572989E+09 | 0.432464E+09 |
| Maximum of Months | 0.129660E+10 | 0.797785E+09 | 0.715159E+09 | 0.159013E+10 | 0.126927E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.635261E+09 | 0.390560E+09 | 0.244700E+09 | 0.525362E+09 | 0.119670E+10 |
| February | 0.927621E+09 | 0.600987E+09 | 0.326633E+09 | 0.883352E+09 | 0.975318E+09 |
| March | 0.110999E+10 | 0.631399E+09 | 0.478589E+09 | 0.109832E+10 | 0.988436E+09 |
| April | 0.112226E+10 | 0.536520E+09 | 0.585738E+09 | 0.117151E+10 | 0.814383E+09 |
| May | 0.103653E+10 | 0.352003E+09 | 0.684528E+09 | 0.108578E+10 | 0.717856E+09 |
| June | 0.898152E+09 | 0.281119E+09 | 0.617034E+09 | 0.974933E+09 | 0.539414E+09 |
| July | 0.104163E+10 | 0.432542E+09 | 0.609083E+09 | 0.134530E+10 | 0.445341E+09 |
| August | 0.114089E+10 | 0.586921E+09 | 0.553970E+09 | 0.153195E+10 | 0.429086E+09 |
| September | 0.124058E+10 | 0.736309E+09 | 0.504274E+09 | 0.147929E+10 | 0.660086E+09 |
| October | 0.115038E+10 | 0.744939E+09 | 0.405441E+09 | 0.122462E+10 | 0.934982E+09 |
| November | 0.640277E+09 | 0.383184E+09 | 0.257094E+09 | 0.554953E+09 | 0.103972E+10 |
| December | 0.636191E+09 | 0.420429E+09 | 0.215761E+09 | 0.590695E+09 | 0.127021E+10 |
| Annual Sum or Average | 0.115798E+11 | 0.609691E+10 | 0.548285E+10 | 0.124661E+11 | 0.100115E+11 |
| Minimum of Months | 0.635261E+09 | 0.281119E+09 | 0.215761E+09 | 0.525362E+09 | 0.429086E+09 |
| Maximum of Months | 0.124058E+10 | 0.744939E+09 | 0.684528E+09 | 0.153195E+10 | 0.127021E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 49278394.98 | 14531301.98 | 34747093.00 | 17059487.33 | 0.221427E+09 |
| February | 79802069.13 | 29991864.90 | 49810204.23 | 49590230.33 | 0.177768E+09 |
| March | 0.123804E+09 | 41787206.48 | 82016913.83 | 91728541.05 | 0.169178E+09 |
| April | 0.182279E+09 | 69692155.54 | 0.112587E+09 | 0.168379E+09 | 0.137333E+09 |
| May | 0.242369E+09 | 98461254.39 | 0.143907E+09 | 0.249467E+09 | 0.121300E+09 |
| June | 0.225573E+09 | 87582538.84 | 0.137991E+09 | 0.239260E+09 | 91112619.33 |
| July | 0.287954E+09 | 0.151363E+09 | 0.136590E+09 | 0.353431E+09 | 76261180.47 |
| August | 0.238207E+09 | 0.121635E+09 | 0.116571E+09 | 0.298615E+09 | 74173023.84 |
| September | 0.187725E+09 | 90074743.68 | 97650664.86 | 0.205890E+09 | 0.112841E+09 |
| October | 0.110435E+09 | 44997027.39 | 65438053.22 | 89399210.65 | 0.161490E+09 |
| November | 53221922.87 | 15010796.12 | 38211126.74 | 23518976.58 | 0.184573E+09 |
| December | 46234764.70 | 15843478.51 | 30391286.19 | 21744174.80 | 0.226932E+09 |
| Annual Sum or Average | 0.182688E+10 | 0.780971E+09 | 0.104591E+10 | 0.180808E+10 | 0.175439E+10 |
| Minimum of Months | 46234764.70 | 14531301.98 | 30391286.19 | 17059487.33 | 74173023.84 |
| Maximum of Months | 0.287954E+09 | 0.151363E+09 | 0.143907E+09 | 0.353431E+09 | 0.226932E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.147835E+09 | 43593760.64 | 0.104241E+09 | 57094773.08 | 0.591518E+09 |
| February | 0.239405E+09 | 89975294.78 | 0.149430E+09 | 0.160194E+09 | 0.467002E+09 |
| March | 0.371411E+09 | 0.125361E+09 | 0.246050E+09 | 0.296225E+09 | 0.433882E+09 |
| April | 0.546834E+09 | 0.209076E+09 | 0.337758E+09 | 0.532469E+09 | 0.351950E+09 |
| May | 0.727103E+09 | 0.295383E+09 | 0.431721E+09 | 0.773884E+09 | 0.318488E+09 |
| June | 0.676717E+09 | 0.262747E+09 | 0.413970E+09 | 0.740745E+09 | 0.243484E+09 |
| July | 0.863858E+09 | 0.454088E+09 | 0.409770E+09 | 0.107974E+10 | 0.210797E+09 |
| August | 0.714617E+09 | 0.364904E+09 | 0.349713E+09 | 0.915295E+09 | 0.202651E+09 |
| September | 0.563174E+09 | 0.270223E+09 | 0.292951E+09 | 0.634903E+09 | 0.302008E+09 |
| October | 0.331304E+09 | 0.134991E+09 | 0.196314E+09 | 0.285494E+09 | 0.418673E+09 |
| November | 0.159665E+09 | 45032238.26 | 0.114633E+09 | 77521183.03 | 0.487416E+09 |
| December | 0.138704E+09 | 47530277.11 | 91173554.66 | 70605892.10 | 0.604745E+09 |
| Annual Sum or Average | 0.548063E+10 | 0.234290E+10 | 0.313772E+10 | 0.562417E+10 | 0.463261E+10 |
| Minimum of Months | 0.138704E+09 | 43593760.64 | 91173554.66 | 57094773.08 | 0.202651E+09 |
| Maximum of Months | 0.863858E+09 | 0.454088E+09 | 0.431721E+09 | 0.107974E+10 | 0.604745E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 11190489.54 | 0.00 | 11190489.54 | 95370.97 | 95475574.20 |
| February | 15527514.25 | 0.00 | 15527514.25 | 1750374.27 | 77174005.01 |
| March | 25239836.72 | 0.00 | 25239836.72 | 5888051.35 | 69454773.25 |
| April | 34207840.47 | 122950.56 | 34084889.91 | 15829487.86 | 54529504.22 |
| May | 46155540.01 | 1502365.07 | 44653174.94 | 28766816.27 | 47263078.66 |
| June | 46614712.92 | 3443262.28 | 43171450.64 | 34511994.75 | 34982933.43 |
| July | 46190241.90 | 4063431.60 | 42126810.30 | 45184995.56 | 30200988.80 |
| August | 36986590.71 | 1056876.69 | 35929714.01 | 38438303.44 | 28685748.81 |
| September | 27459982.29 | 6258.52 | 27453723.77 | 15728987.63 | 46446022.11 |
| October | 19583878.44 | 0.00 | 19583878.44 | 4224485.03 | 65830987.71 |
| November | 12270709.50 | 0.00 | 12270709.50 | 562847.09 | 78489135.78 |
| December | 9355847.99 | 0.00 | 9355847.99 | 40076.11 | 96424564.06 |
| Annual Sum or Average | 0.330783E+09 | 10195144.72 | 0.320588E+09 | 0.191022E+09 | 0.724957E+09 |
| Minimum of Months | 9355847.99 | 0.00 | 9355847.99 | 40076.11 | 28685748.81 |
| Maximum of Months | 46614712.92 | 4063431.60 | 44653174.94 | 45184995.56 | 96424564.06 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 81149965.90 | 0.00 | 81149965.90 | 893307.20 | 0.660831E+09 |
| February | 0.112975E+09 | 0.00 | 0.112975E+09 | 13998570.41 | 0.532561E+09 |
| March | 0.183808E+09 | 0.00 | 0.183808E+09 | 48169285.07 | 0.480436E+09 |
| April | 0.249688E+09 | 853312.41 | 0.248834E+09 | 0.123106E+09 | 0.377977E+09 |
| May | 0.335302E+09 | 10426847.36 | 0.324875E+09 | 0.217471E+09 | 0.328599E+09 |
| June | 0.338943E+09 | 23897234.32 | 0.315046E+09 | 0.258407E+09 | 0.244067E+09 |
| July | 0.335063E+09 | 28201388.47 | 0.306861E+09 | 0.331355E+09 | 0.211195E+09 |
| August | 0.269284E+09 | 7335563.18 | 0.261949E+09 | 0.282128E+09 | 0.200891E+09 |
| September | 0.200901E+09 | 46983.00 | 0.200854E+09 | 0.121579E+09 | 0.323286E+09 |
| October | 0.143006E+09 | 0.00 | 0.143006E+09 | 35225731.16 | 0.455496E+09 |
| November | 88964690.73 | 0.00 | 88964690.73 | 4921696.72 | 0.543119E+09 |
| December | 68132150.99 | 0.00 | 68132150.99 | 377300.96 | 0.667667E+09 |
| Annual Sum or Average | 0.240722E+10 | 70761328.74 | 0.233645E+10 | 0.143763E+10 | 0.502612E+10 |
| Minimum of Months | 68132150.99 | 0.00 | 68132150.99 | 377300.96 | 0.200891E+09 |
| Maximum of Months | 0.338943E+09 | 28201388.47 | 0.324875E+09 | 0.331355E+09 | 0.667667E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.134359E+09 | 0.00 | 0.134359E+09 | 111969.95 | 0.130120E+10 |
| February | 0.186424E+09 | 0.00 | 0.186424E+09 | 15621250.64 | 0.106528E+10 |
| March | 0.303191E+09 | 0.00 | 0.303191E+09 | 50324005.75 | 0.977861E+09 |
| April | 0.408041E+09 | 589919.10 | 0.407452E+09 | 0.162239E+09 | 0.766246E+09 |
| May | 0.545289E+09 | 12338103.94 | 0.532951E+09 | 0.320704E+09 | 0.660149E+09 |
| June | 0.541304E+09 | 29088681.45 | 0.512216E+09 | 0.381049E+09 | 0.481900E+09 |
| July | 0.535820E+09 | 33804528.35 | 0.502015E+09 | 0.540014E+09 | 0.391198E+09 |
| August | 0.436348E+09 | 7320521.66 | 0.429027E+09 | 0.477171E+09 | 0.370904E+09 |
| September | 0.329732E+09 | 53250.84 | 0.329679E+09 | 0.182088E+09 | 0.613330E+09 |
| October | 0.235012E+09 | 0.00 | 0.235012E+09 | 37071372.66 | 0.912394E+09 |
| November | 0.147394E+09 | 0.00 | 0.147394E+09 | 3913350.60 | 0.109112E+10 |
| December | 0.112104E+09 | 0.00 | 0.112104E+09 | 138370.70 | 0.132988E+10 |
| Annual Sum or Average | 0.391502E+10 | 83195005.34 | 0.383183E+10 | 0.217045E+10 | 0.996147E+10 |
| Minimum of Months | 0.112104E+09 | 0.00 | 0.112104E+09 | 111969.95 | 0.370904E+09 |
| Maximum of Months | 0.545289E+09 | 33804528.35 | 0.532951E+09 | 0.540014E+09 | 0.132988E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.142267E+09 | 0.00 | 0.142267E+09 | 342516.51 | 0.129928E+10 |
| February | 0.197357E+09 | 0.00 | 0.197357E+09 | 18563633.88 | 0.106153E+10 |
| March | 0.320781E+09 | 0.00 | 0.320781E+09 | 61307570.36 | 0.973844E+09 |
| April | 0.433815E+09 | 1277000.35 | 0.432538E+09 | 0.183737E+09 | 0.760070E+09 |
| May | 0.582166E+09 | 16603513.59 | 0.565563E+09 | 0.355024E+09 | 0.649432E+09 |
| June | 0.584976E+09 | 39113136.72 | 0.545863E+09 | 0.429753E+09 | 0.474771E+09 |
| July | 0.575225E+09 | 42852553.30 | 0.532372E+09 | 0.584591E+09 | 0.386523E+09 |
| August | 0.466499E+09 | 11333868.23 | 0.455165E+09 | 0.504970E+09 | 0.364151E+09 |
| September | 0.348769E+09 | 57191.21 | 0.348712E+09 | 0.200496E+09 | 0.615443E+09 |
| October | 0.248848E+09 | 0.00 | 0.248848E+09 | 45126439.35 | 0.910873E+09 |
| November | 0.156003E+09 | 0.00 | 0.156003E+09 | 5005696.82 | 0.108830E+10 |
| December | 0.118907E+09 | 0.00 | 0.118907E+09 | 214458.69 | 0.132997E+10 |
| Annual Sum or Average | 0.417561E+10 | 0.111237E+09 | 0.406438E+10 | 0.238913E+10 | 0.991418E+10 |
| Minimum of Months | 0.118907E+09 | 0.00 | 0.118907E+09 | 214458.69 | 0.364151E+09 |
| Maximum of Months | 0.584976E+09 | 42852553.30 | 0.565563E+09 | 0.584591E+09 | 0.132997E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.142265E+09 | 0.00 | 0.142265E+09 | 342509.43 | 0.129925E+10 |
| February | 0.197353E+09 | 0.00 | 0.197353E+09 | 18563268.42 | 0.106151E+10 |
| March | 0.320775E+09 | 0.00 | 0.320775E+09 | 61306357.91 | 0.973825E+09 |
| April | 0.434600E+09 | 1541840.25 | 0.433058E+09 | 0.183785E+09 | 0.758712E+09 |
| May | 0.584992E+09 | 18185025.95 | 0.566806E+09 | 0.355746E+09 | 0.645727E+09 |
| June | 0.587491E+09 | 40721251.35 | 0.546770E+09 | 0.430660E+09 | 0.471893E+09 |
| July | 0.580699E+09 | 46914649.49 | 0.533785E+09 | 0.588911E+09 | 0.382292E+09 |
| August | 0.470073E+09 | 13480541.30 | 0.456593E+09 | 0.508830E+09 | 0.361965E+09 |
| September | 0.348838E+09 | 70570.15 | 0.348768E+09 | 0.200492E+09 | 0.615293E+09 |
| October | 0.248843E+09 | 0.00 | 0.248843E+09 | 45125546.25 | 0.910855E+09 |
| November | 0.156000E+09 | 0.00 | 0.156000E+09 | 5005597.32 | 0.108828E+10 |
| December | 0.118904E+09 | 0.00 | 0.118904E+09 | 214454.37 | 0.132994E+10 |
| Annual Sum or Average | 0.419083E+10 | 0.120914E+09 | 0.406992E+10 | 0.239898E+10 | 0.989955E+10 |
| Minimum of Months | 0.118904E+09 | 0.00 | 0.118904E+09 | 214454.37 | 0.361965E+09 |
| Maximum of Months | 0.587491E+09 | 46914649.49 | 0.566806E+09 | 0.588911E+09 | 0.132994E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.147835E+09 | 43593760.64 | 0.104241E+09 | 52128003.72 | 0.607546E+09 |
| February | 0.239405E+09 | 89975294.78 | 0.149430E+09 | 0.148813E+09 | 0.490914E+09 |
| March | 0.371411E+09 | 0.125361E+09 | 0.246050E+09 | 0.275420E+09 | 0.465345E+09 |
| April | 0.546834E+09 | 0.209076E+09 | 0.337758E+09 | 0.510099E+09 | 0.376651E+09 |
| May | 0.727103E+09 | 0.295383E+09 | 0.431721E+09 | 0.758302E+09 | 0.332769E+09 |
| June | 0.676717E+09 | 0.262747E+09 | 0.413970E+09 | 0.728514E+09 | 0.252446E+09 |
| July | 0.863858E+09 | 0.454088E+09 | 0.409770E+09 | 0.105703E+10 | 0.225876E+09 |
| August | 0.714617E+09 | 0.364904E+09 | 0.349713E+09 | 0.889141E+09 | 0.223395E+09 |
| September | 0.563174E+09 | 0.270223E+09 | 0.292951E+09 | 0.611809E+09 | 0.331029E+09 |
| October | 0.331304E+09 | 0.134991E+09 | 0.196314E+09 | 0.265229E+09 | 0.456754E+09 |
| November | 0.159665E+09 | 45032238.26 | 0.114633E+09 | 69856991.04 | 0.513700E+09 |
| December | 0.138704E+09 | 47530277.11 | 91173554.66 | 64304751.89 | 0.626409E+09 |
| Annual Sum or Average | 0.548063E+10 | 0.234290E+10 | 0.313772E+10 | 0.543064E+10 | 0.490283E+10 |
| Minimum of Months | 0.138704E+09 | 43593760.64 | 91173554.66 | 52128003.72 | 0.223395E+09 |
| Maximum of Months | 0.863858E+09 | 0.454088E+09 | 0.431721E+09 | 0.105703E+10 | 0.626409E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 56680318.05 | 34358530.80 | 22321787.25 | 48421138.87 | 86279306.91 |
| February | 80129488.76 | 50861604.94 | 29267883.82 | 78546679.11 | 69943226.25 |
| March | 94747713.55 | 52296935.77 | 42450777.78 | 96190471.20 | 70230218.19 |
| April | 95530030.95 | 43536421.87 | 51993609.09 | 0.102235E+09 | 59004335.69 |
| May | 88960196.63 | 28223894.04 | 60736302.58 | 94699734.80 | 52881395.74 |
| June | 77926765.73 | 22521115.87 | 55405649.86 | 85412145.43 | 40183835.87 |
| July | 88931595.12 | 34620310.11 | 54311285.00 | 0.112711E+09 | 35668333.08 |
| August | 96697930.99 | 47357183.19 | 49340747.79 | 0.128003E+09 | 34354922.14 |
| September | 0.104899E+09 | 60125844.59 | 44772875.73 | 0.125531E+09 | 50101270.72 |
| October | 99054917.30 | 62849335.34 | 36205581.96 | 0.107085E+09 | 67249596.82 |
| November | 56205035.03 | 33027175.33 | 23177859.69 | 50460171.82 | 74608814.28 |
| December | 58973432.04 | 38757947.93 | 20215484.11 | 56301990.32 | 90901228.34 |
| Annual Sum or Average | 0.998736E+09 | 0.508536E+09 | 0.490200E+09 | 0.108560E+10 | 0.731406E+09 |
| Minimum of Months | 56205035.03 | 22521115.87 | 20215484.11 | 48421138.87 | 34354922.14 |
| Maximum of Months | 0.104899E+09 | 62849335.34 | 60736302.58 | 0.128003E+09 | 90901228.34 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.388856E+09 | 0.238319E+09 | 0.150538E+09 | 0.332193E+09 | 0.596417E+09 |
| February | 0.549644E+09 | 0.352994E+09 | 0.196650E+09 | 0.538522E+09 | 0.483087E+09 |
| March | 0.646830E+09 | 0.362954E+09 | 0.283876E+09 | 0.656279E+09 | 0.485878E+09 |
| April | 0.647742E+09 | 0.302155E+09 | 0.345586E+09 | 0.692385E+09 | 0.408752E+09 |
| May | 0.598795E+09 | 0.195882E+09 | 0.402913E+09 | 0.635800E+09 | 0.367714E+09 |
| June | 0.521655E+09 | 0.156303E+09 | 0.365352E+09 | 0.569959E+09 | 0.279686E+09 |
| July | 0.599194E+09 | 0.240275E+09 | 0.358919E+09 | 0.760122E+09 | 0.247767E+09 |
| August | 0.655465E+09 | 0.328673E+09 | 0.326793E+09 | 0.870143E+09 | 0.236744E+09 |
| September | 0.715211E+09 | 0.417291E+09 | 0.297920E+09 | 0.856408E+09 | 0.345206E+09 |
| October | 0.678655E+09 | 0.436193E+09 | 0.242463E+09 | 0.733816E+09 | 0.464395E+09 |
| November | 0.385279E+09 | 0.229193E+09 | 0.156086E+09 | 0.345818E+09 | 0.515720E+09 |
| December | 0.403325E+09 | 0.267495E+09 | 0.135830E+09 | 0.384836E+09 | 0.628178E+09 |
| Annual Sum or Average | 0.679065E+10 | 0.352773E+10 | 0.326293E+10 | 0.737628E+10 | 0.505954E+10 |
| Minimum of Months | 0.385279E+09 | 0.156303E+09 | 0.135830E+09 | 0.332193E+09 | 0.236744E+09 |
| Maximum of Months | 0.715211E+09 | 0.436193E+09 | 0.402913E+09 | 0.870143E+09 | 0.628178E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.693982E+09 | 0.426657E+09 | 0.267326E+09 | 0.584305E+09 | 0.118818E+10 |
| February | 0.100347E+10 | 0.648219E+09 | 0.355251E+09 | 0.964683E+09 | 0.962371E+09 |
| March | 0.117895E+10 | 0.666878E+09 | 0.512070E+09 | 0.117518E+10 | 0.984620E+09 |
| April | 0.117680E+10 | 0.555256E+09 | 0.621546E+09 | 0.123723E+10 | 0.819052E+09 |
| May | 0.108389E+10 | 0.359963E+09 | 0.723925E+09 | 0.114152E+10 | 0.720941E+09 |
| June | 0.941632E+09 | 0.287230E+09 | 0.654401E+09 | 0.102496E+10 | 0.543397E+09 |
| July | 0.108515E+10 | 0.441541E+09 | 0.643607E+09 | 0.139607E+10 | 0.453351E+09 |
| August | 0.119066E+10 | 0.603985E+09 | 0.586671E+09 | 0.159480E+10 | 0.438263E+09 |
| September | 0.130295E+10 | 0.766834E+09 | 0.536120E+09 | 0.155890E+10 | 0.664584E+09 |
| October | 0.123753E+10 | 0.800265E+09 | 0.437260E+09 | 0.132493E+10 | 0.928485E+09 |
| November | 0.697863E+09 | 0.418007E+09 | 0.279857E+09 | 0.613712E+09 | 0.103725E+10 |
| December | 0.705540E+09 | 0.468265E+09 | 0.237275E+09 | 0.665868E+09 | 0.126710E+10 |
| Annual Sum or Average | 0.122984E+11 | 0.644310E+10 | 0.585531E+10 | 0.132822E+11 | 0.100076E+11 |
| Minimum of Months | 0.693982E+09 | 0.287230E+09 | 0.237275E+09 | 0.584305E+09 | 0.438263E+09 |
| Maximum of Months | 0.130295E+10 | 0.800265E+09 | 0.723925E+09 | 0.159480E+10 | 0.126710E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.692526E+09 | 0.425724E+09 | 0.266802E+09 | 0.584265E+09 | 0.119017E+10 |
| February | 0.100037E+10 | 0.646550E+09 | 0.353821E+09 | 0.964376E+09 | 0.966879E+09 |
| March | 0.117806E+10 | 0.666397E+09 | 0.511666E+09 | 0.117494E+10 | 0.985759E+09 |
| April | 0.117672E+10 | 0.555219E+09 | 0.621504E+09 | 0.123715E+10 | 0.818998E+09 |
| May | 0.108382E+10 | 0.359939E+09 | 0.723877E+09 | 0.114145E+10 | 0.720894E+09 |
| June | 0.941569E+09 | 0.287212E+09 | 0.654358E+09 | 0.102489E+10 | 0.543361E+09 |
| July | 0.108508E+10 | 0.441512E+09 | 0.643564E+09 | 0.139598E+10 | 0.453322E+09 |
| August | 0.119058E+10 | 0.603946E+09 | 0.586632E+09 | 0.159470E+10 | 0.438234E+09 |
| September | 0.130271E+10 | 0.766680E+09 | 0.536027E+09 | 0.155874E+10 | 0.664778E+09 |
| October | 0.123535E+10 | 0.798890E+09 | 0.436458E+09 | 0.132450E+10 | 0.931551E+09 |
| November | 0.695447E+09 | 0.416549E+09 | 0.278899E+09 | 0.612995E+09 | 0.104009E+10 |
| December | 0.704313E+09 | 0.467365E+09 | 0.236948E+09 | 0.665821E+09 | 0.126873E+10 |
| Annual Sum or Average | 0.122865E+11 | 0.643598E+10 | 0.585056E+10 | 0.132798E+11 | 0.100228E+11 |
| Minimum of Months | 0.692526E+09 | 0.287212E+09 | 0.236948E+09 | 0.584265E+09 | 0.438234E+09 |
| Maximum of Months | 0.130271E+10 | 0.798890E+09 | 0.723877E+09 | 0.159470E+10 | 0.126873E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.645760E+09 | 0.397195E+09 | 0.248565E+09 | 0.532726E+09 | 0.119548E+10 |
| February | 0.930942E+09 | 0.601675E+09 | 0.329267E+09 | 0.884450E+09 | 0.977600E+09 |
| March | 0.111363E+10 | 0.631494E+09 | 0.482137E+09 | 0.109965E+10 | 0.995957E+09 |
| April | 0.112723E+10 | 0.536490E+09 | 0.590737E+09 | 0.117402E+10 | 0.820929E+09 |
| May | 0.104261E+10 | 0.351983E+09 | 0.690626E+09 | 0.109056E+10 | 0.721693E+09 |
| June | 0.904426E+09 | 0.281104E+09 | 0.623322E+09 | 0.979265E+09 | 0.543362E+09 |
| July | 0.104750E+10 | 0.432517E+09 | 0.614988E+09 | 0.134775E+10 | 0.451071E+09 |
| August | 0.114598E+10 | 0.586888E+09 | 0.559096E+09 | 0.153397E+10 | 0.434560E+09 |
| September | 0.124482E+10 | 0.736317E+09 | 0.508502E+09 | 0.148169E+10 | 0.665527E+09 |
| October | 0.115440E+10 | 0.745744E+09 | 0.408651E+09 | 0.122630E+10 | 0.942329E+09 |
| November | 0.645349E+09 | 0.385373E+09 | 0.259977E+09 | 0.556540E+09 | 0.104629E+10 |
| December | 0.654494E+09 | 0.433564E+09 | 0.220930E+09 | 0.607213E+09 | 0.127041E+10 |
| Annual Sum or Average | 0.116571E+11 | 0.612034E+10 | 0.553680E+10 | 0.125141E+11 | 0.100652E+11 |
| Minimum of Months | 0.645349E+09 | 0.281104E+09 | 0.220930E+09 | 0.532726E+09 | 0.434560E+09 |
| Maximum of Months | 0.124482E+10 | 0.745744E+09 | 0.690626E+09 | 0.153397E+10 | 0.127041E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 49278394.98 | 14531301.98 | 34747093.00 | 16971827.48 | 0.222491E+09 |
| February | 79802069.13 | 29991864.90 | 49810204.23 | 49289979.53 | 0.179093E+09 |
| March | 0.123804E+09 | 41787206.48 | 82016913.83 | 90857301.47 | 0.171927E+09 |
| April | 0.182279E+09 | 69692155.54 | 0.112587E+09 | 0.167060E+09 | 0.139840E+09 |
| May | 0.242369E+09 | 98461254.39 | 0.143907E+09 | 0.248483E+09 | 0.122941E+09 |
| June | 0.225573E+09 | 87582538.84 | 0.137991E+09 | 0.238108E+09 | 92622972.76 |
| July | 0.287954E+09 | 0.151363E+09 | 0.136590E+09 | 0.351442E+09 | 78267909.22 |
| August | 0.238207E+09 | 0.121635E+09 | 0.116571E+09 | 0.297014E+09 | 76012138.82 |
| September | 0.187725E+09 | 90074743.68 | 97650664.86 | 0.204929E+09 | 0.114766E+09 |
| October | 0.110435E+09 | 44997027.39 | 65438053.22 | 88705095.01 | 0.164308E+09 |
| November | 53221922.87 | 15010796.12 | 38211126.74 | 23180439.88 | 0.187355E+09 |
| December | 46234764.70 | 15843478.51 | 30391286.19 | 21591286.69 | 0.228549E+09 |
| Annual Sum or Average | 0.182688E+10 | 0.780971E+09 | 0.104591E+10 | 0.179763E+10 | 0.177817E+10 |
| Minimum of Months | 46234764.70 | 14531301.98 | 30391286.19 | 16971827.48 | 76012138.82 |
| Maximum of Months | 0.287954E+09 | 0.151363E+09 | 0.143907E+09 | 0.351442E+09 | 0.228549E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13426417.84 | 0.00 | 13426417.84 | 280273.21 | 95190753.44 |
| February | 18870077.30 | 0.00 | 18870077.30 | 2935227.86 | 76372842.08 |
| March | 30780905.71 | 0.00 | 30780905.71 | 10445613.32 | 69614953.29 |
| April | 42153015.58 | 149528.68 | 42003486.90 | 23811127.04 | 54909606.04 |
| May | 56048340.95 | 1665104.67 | 54383236.28 | 39775717.22 | 47846020.79 |
| June | 57032375.89 | 3766156.37 | 53266219.52 | 46188664.85 | 35607563.38 |
| July | 56013049.30 | 4391658.76 | 51621390.54 | 55884518.19 | 31136754.83 |
| August | 45342966.68 | 1225748.27 | 44117218.41 | 47463988.20 | 29897923.81 |
| September | 34084630.46 | 10050.98 | 34074579.49 | 22646018.01 | 47729016.57 |
| October | 24132079.04 | 0.00 | 24132079.04 | 7758149.76 | 66378796.81 |
| November | 14710476.39 | 0.00 | 14710476.39 | 1160902.45 | 78400934.72 |
| December | 11408991.99 | 0.00 | 11408991.99 | 146360.65 | 96537410.07 |
| Annual Sum or Average | 0.404003E+09 | 11208247.73 | 0.392795E+09 | 0.258497E+09 | 0.729623E+09 |
| Minimum of Months | 11408991.99 | 0.00 | 11408991.99 | 146360.65 | 29897923.81 |
| Maximum of Months | 57032375.89 | 4391658.76 | 54383236.28 | 55884518.19 | 96537410.07 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.147835E+09 | 43593760.64 | 0.104241E+09 | 56982727.72 | 0.591782E+09 |
| February | 0.239405E+09 | 89975294.78 | 0.149430E+09 | 0.159722E+09 | 0.467786E+09 |
| March | 0.371411E+09 | 0.125361E+09 | 0.246050E+09 | 0.294788E+09 | 0.436207E+09 |
| April | 0.546834E+09 | 0.209076E+09 | 0.337758E+09 | 0.529705E+09 | 0.355105E+09 |
| May | 0.727103E+09 | 0.295383E+09 | 0.431721E+09 | 0.770964E+09 | 0.321202E+09 |
| June | 0.676717E+09 | 0.262747E+09 | 0.413970E+09 | 0.737434E+09 | 0.246007E+09 |
| July | 0.863858E+09 | 0.454088E+09 | 0.409770E+09 | 0.107540E+10 | 0.214029E+09 |
| August | 0.714617E+09 | 0.364904E+09 | 0.349713E+09 | 0.912121E+09 | 0.205119E+09 |
| September | 0.563174E+09 | 0.270223E+09 | 0.292951E+09 | 0.632868E+09 | 0.304405E+09 |
| October | 0.331304E+09 | 0.134991E+09 | 0.196314E+09 | 0.284276E+09 | 0.421101E+09 |
| November | 0.159665E+09 | 45032238.26 | 0.114633E+09 | 77072160.47 | 0.489264E+09 |
| December | 0.138704E+09 | 47530277.11 | 91173554.66 | 70455273.57 | 0.605276E+09 |
| Annual Sum or Average | 0.548063E+10 | 0.234290E+10 | 0.313772E+10 | 0.560178E+10 | 0.465728E+10 |
| Minimum of Months | 0.138704E+09 | 43593760.64 | 91173554.66 | 56982727.72 | 0.205119E+09 |
| Maximum of Months | 0.863858E+09 | 0.454088E+09 | 0.431721E+09 | 0.107540E+10 | 0.605276E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 92812201.91 | 0.00 | 92812201.91 | 1952518.92 | 0.656850E+09 |
| February | 0.130442E+09 | 0.00 | 0.130442E+09 | 20537193.12 | 0.526700E+09 |
| March | 0.212778E+09 | 0.00 | 0.212778E+09 | 72813440.71 | 0.480698E+09 |
| April | 0.291389E+09 | 1033639.10 | 0.290356E+09 | 0.165219E+09 | 0.379544E+09 |
| May | 0.387443E+09 | 11510281.85 | 0.375933E+09 | 0.275286E+09 | 0.330744E+09 |
| June | 0.394245E+09 | 26034111.93 | 0.368211E+09 | 0.319473E+09 | 0.246143E+09 |
| July | 0.387199E+09 | 30357989.52 | 0.356841E+09 | 0.386719E+09 | 0.215238E+09 |
| August | 0.313440E+09 | 8473165.92 | 0.304967E+09 | 0.328844E+09 | 0.206675E+09 |
| September | 0.235615E+09 | 69478.86 | 0.235546E+09 | 0.158056E+09 | 0.329822E+09 |
| October | 0.166817E+09 | 0.00 | 0.166817E+09 | 54444805.43 | 0.457911E+09 |
| November | 0.101688E+09 | 0.00 | 0.101688E+09 | 8200430.71 | 0.541136E+09 |
| December | 78866435.73 | 0.00 | 78866435.73 | 1038769.95 | 0.665888E+09 |
| Annual Sum or Average | 0.279274E+10 | 77478667.17 | 0.271526E+10 | 0.179258E+10 | 0.503735E+10 |
| Minimum of Months | 78866435.73 | 0.00 | 78866435.73 | 1038769.95 | 0.206675E+09 |
| Maximum of Months | 0.394245E+09 | 30357989.52 | 0.375933E+09 | 0.386719E+09 | 0.665888E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.113073E+09 | 0.00 | 0.113073E+09 | 1315209.46 | 0.855158E+09 |
| February | 0.158918E+09 | 0.00 | 0.158918E+09 | 20961946.02 | 0.693403E+09 |
| March | 0.259227E+09 | 0.00 | 0.259227E+09 | 76129892.61 | 0.642581E+09 |
| April | 0.355000E+09 | 1259282.06 | 0.353740E+09 | 0.187131E+09 | 0.503723E+09 |
| May | 0.472022E+09 | 14022971.41 | 0.457999E+09 | 0.327516E+09 | 0.429616E+09 |
| June | 0.480309E+09 | 31717347.32 | 0.448592E+09 | 0.384575E+09 | 0.315590E+09 |
| July | 0.471725E+09 | 36985125.52 | 0.434739E+09 | 0.484044E+09 | 0.260835E+09 |
| August | 0.381864E+09 | 10322854.38 | 0.371542E+09 | 0.411807E+09 | 0.250108E+09 |
| September | 0.287050E+09 | 84646.07 | 0.286966E+09 | 0.190189E+09 | 0.417737E+09 |
| October | 0.203233E+09 | 0.00 | 0.203233E+09 | 57566860.00 | 0.605285E+09 |
| November | 0.123887E+09 | 0.00 | 0.123887E+09 | 7377994.47 | 0.718555E+09 |
| December | 96082950.19 | 0.00 | 96082950.19 | 559837.01 | 0.878836E+09 |
| Annual Sum or Average | 0.340239E+10 | 94392226.75 | 0.330800E+10 | 0.214917E+10 | 0.657143E+10 |
| Minimum of Months | 96082950.19 | 0.00 | 96082950.19 | 559837.01 | 0.250108E+09 |
| Maximum of Months | 0.480309E+09 | 36985125.52 | 0.457999E+09 | 0.484044E+09 | 0.878836E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.113072E+09 | 0.00 | 0.113072E+09 | 1315133.33 | 0.855158E+09 |
| February | 0.158917E+09 | 0.00 | 0.158917E+09 | 20961532.35 | 0.693404E+09 |
| March | 0.259226E+09 | 0.00 | 0.259226E+09 | 76128610.09 | 0.642581E+09 |
| April | 0.354997E+09 | 1259270.43 | 0.353738E+09 | 0.187129E+09 | 0.503723E+09 |
| May | 0.472019E+09 | 14022841.82 | 0.457996E+09 | 0.327513E+09 | 0.429616E+09 |
| June | 0.480306E+09 | 31717054.20 | 0.448589E+09 | 0.384572E+09 | 0.315590E+09 |
| July | 0.471722E+09 | 36984783.72 | 0.434737E+09 | 0.484041E+09 | 0.260835E+09 |
| August | 0.381862E+09 | 10322758.98 | 0.371539E+09 | 0.411804E+09 | 0.250108E+09 |
| September | 0.287048E+09 | 84645.28 | 0.286964E+09 | 0.190187E+09 | 0.417737E+09 |
| October | 0.203232E+09 | 0.00 | 0.203232E+09 | 57565935.49 | 0.605285E+09 |
| November | 0.123886E+09 | 0.00 | 0.123886E+09 | 7377803.09 | 0.718555E+09 |
| December | 96082296.40 | 0.00 | 96082296.40 | 559810.85 | 0.878836E+09 |
| Annual Sum or Average | 0.340237E+10 | 94391354.42 | 0.330798E+10 | 0.214915E+10 | 0.657143E+10 |
| Minimum of Months | 96082296.40 | 0.00 | 96082296.40 | 559810.85 | 0.250108E+09 |
| Maximum of Months | 0.480306E+09 | 36984783.72 | 0.457996E+09 | 0.484041E+09 | 0.878836E+09 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.113069E+09 | 0.00 | 0.113069E+09 | 1315136.53 | 0.855129E+09 |
| February | 0.158912E+09 | 0.00 | 0.158912E+09 | 20961087.56 | 0.693380E+09 |
| March | 0.259218E+09 | 0.00 | 0.259218E+09 | 76126858.38 | 0.642559E+09 |
| April | 0.354987E+09 | 1259235.51 | 0.353728E+09 | 0.187124E+09 | 0.503706E+09 |
| May | 0.472005E+09 | 14022453.03 | 0.457982E+09 | 0.327504E+09 | 0.429602E+09 |
| June | 0.480292E+09 | 31716174.85 | 0.448576E+09 | 0.384561E+09 | 0.315579E+09 |
| July | 0.471708E+09 | 36983758.32 | 0.434724E+09 | 0.484026E+09 | 0.260826E+09 |
| August | 0.381851E+09 | 10322472.78 | 0.371528E+09 | 0.411792E+09 | 0.250099E+09 |
| September | 0.287040E+09 | 84642.94 | 0.286955E+09 | 0.190182E+09 | 0.417723E+09 |
| October | 0.203226E+09 | 0.00 | 0.203226E+09 | 57564582.83 | 0.605265E+09 |
| November | 0.123883E+09 | 0.00 | 0.123883E+09 | 7377674.92 | 0.718531E+09 |
| December | 96079487.35 | 0.00 | 96079487.35 | 559808.34 | 0.878806E+09 |
| Annual Sum or Average | 0.340227E+10 | 94388737.43 | 0.330788E+10 | 0.214909E+10 | 0.657121E+10 |
| Minimum of Months | 96079487.35 | 0.00 | 96079487.35 | 559808.34 | 0.250099E+09 |
| Maximum of Months | 0.480292E+09 | 36983758.32 | 0.457982E+09 | 0.484026E+09 | 0.878806E+09 |
Report: WindowEnergyReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 12750725.75 | 0.00 | 12750725.75 | 85546.39 | 0.100308E+09 |
| February | 17920418.51 | 0.00 | 17920418.51 | 2052930.26 | 82544631.82 |
| March | 29231810.45 | 0.00 | 29231810.45 | 7330037.05 | 78738017.92 |
| April | 40031580.96 | 142004.22 | 39889576.74 | 19291864.39 | 61858909.46 |
| May | 53227602.41 | 1581314.55 | 51646287.86 | 35234122.80 | 52028590.67 |
| June | 54162104.07 | 3576638.74 | 50585465.33 | 41151545.31 | 38397626.31 |
| July | 53194044.56 | 4170665.08 | 49023379.48 | 51156824.51 | 32380254.94 |
| August | 43060959.08 | 1164067.11 | 41896891.97 | 43083037.39 | 31556646.51 |
| September | 32369242.32 | 9545.20 | 32359697.12 | 19693149.15 | 51561660.65 |
| October | 22917591.24 | 0.00 | 22917591.24 | 5562659.27 | 74430358.92 |
| November | 13970161.95 | 0.00 | 13970161.95 | 589839.82 | 87349239.98 |
| December | 10834825.91 | 0.00 | 10834825.91 | 36351.22 | 0.104169E+09 |
| Annual Sum or Average | 0.383671E+09 | 10644234.89 | 0.373027E+09 | 0.225268E+09 | 0.795323E+09 |
| Minimum of Months | 10834825.91 | 0.00 | 10834825.91 | 36351.22 | 31556646.51 |
| Maximum of Months | 54162104.07 | 4170665.08 | 51646287.86 | 51156824.51 | 0.104169E+09 |
Report: WindowEnergyReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.161702E+09 | 0.00 | 0.161702E+09 | 1084878.67 | 0.127208E+10 |
| February | 0.227262E+09 | 0.00 | 0.227262E+09 | 26034765.84 | 0.104681E+10 |
| March | 0.370711E+09 | 0.00 | 0.370711E+09 | 92957759.83 | 0.998537E+09 |
| April | 0.507671E+09 | 1800863.17 | 0.505870E+09 | 0.244655E+09 | 0.784480E+09 |
| May | 0.675020E+09 | 20053849.28 | 0.654966E+09 | 0.446831E+09 | 0.659814E+09 |
| June | 0.686871E+09 | 45358068.85 | 0.641513E+09 | 0.521874E+09 | 0.486949E+09 |
| July | 0.674594E+09 | 52891367.40 | 0.621703E+09 | 0.648758E+09 | 0.410639E+09 |
| August | 0.546089E+09 | 14762418.02 | 0.531326E+09 | 0.546369E+09 | 0.400194E+09 |
| September | 0.410499E+09 | 121049.91 | 0.410378E+09 | 0.249744E+09 | 0.653893E+09 |
| October | 0.290635E+09 | 0.00 | 0.290635E+09 | 70544301.70 | 0.943908E+09 |
| November | 0.177166E+09 | 0.00 | 0.177166E+09 | 7480206.16 | 0.110774E+10 |
| December | 0.137405E+09 | 0.00 | 0.137405E+09 | 460997.39 | 0.132104E+10 |
| Annual Sum or Average | 0.486562E+10 | 0.134988E+09 | 0.473064E+10 | 0.285679E+10 | 0.100861E+11 |
| Minimum of Months | 0.137405E+09 | 0.00 | 0.137405E+09 | 460997.39 | 0.400194E+09 |
| Maximum of Months | 0.686871E+09 | 52891367.40 | 0.654966E+09 | 0.648758E+09 | 0.132104E+10 |
Report: WindowEnergyReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 15582543.94 | 4632775.73 | 10949768.21 | 5076213.27 | 0.105926E+09 |
| February | 30042890.20 | 13253473.36 | 16789416.84 | 19999736.16 | 85017320.32 |
| March | 48449803.61 | 19689845.71 | 28759957.90 | 36412103.09 | 82281605.18 |
| April | 69749915.22 | 30736212.00 | 39013703.22 | 63373319.71 | 69640740.64 |
| May | 86190363.38 | 37383501.94 | 48806861.44 | 85625306.81 | 63468466.88 |
| June | 76568722.93 | 30089445.43 | 46479277.50 | 77354918.77 | 47961241.88 |
| July | 99469010.74 | 52587104.24 | 46881906.50 | 0.119142E+09 | 41390264.99 |
| August | 88587585.86 | 48255462.51 | 40332123.35 | 0.109964E+09 | 38205118.32 |
| September | 76917625.36 | 41816197.23 | 35101428.13 | 85066234.00 | 54484320.99 |
| October | 42815383.02 | 20109257.30 | 22706125.71 | 35656989.29 | 77394866.70 |
| November | 18261522.45 | 5856027.95 | 12405494.51 | 8296242.31 | 88127537.72 |
| December | 12934488.87 | 3732895.40 | 9201593.47 | 4834749.94 | 0.107676E+09 |
| Annual Sum or Average | 0.665570E+09 | 0.308142E+09 | 0.357428E+09 | 0.650802E+09 | 0.861573E+09 |
| Minimum of Months | 12934488.87 | 3732895.40 | 9201593.47 | 4834749.94 | 38205118.32 |
| Maximum of Months | 99469010.74 | 52587104.24 | 48806861.44 | 0.119142E+09 | 0.107676E+09 |
Report: WindowEnergyReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 59680542.77 | 2301086.49 | 57379456.28 | 159784.86 | 0.578813E+09 |
| February | 0.106906E+09 | 21985687.06 | 84920683.59 | 29710428.53 | 0.458778E+09 |
| March | 0.213746E+09 | 61987019.87 | 0.151758E+09 | 0.121792E+09 | 0.436132E+09 |
| April | 0.366366E+09 | 0.146631E+09 | 0.219735E+09 | 0.313479E+09 | 0.362052E+09 |
| May | 0.512374E+09 | 0.225223E+09 | 0.287151E+09 | 0.509197E+09 | 0.325619E+09 |
| June | 0.476090E+09 | 0.201455E+09 | 0.274635E+09 | 0.489844E+09 | 0.247434E+09 |
| July | 0.616660E+09 | 0.342404E+09 | 0.274256E+09 | 0.738652E+09 | 0.215664E+09 |
| August | 0.497550E+09 | 0.266608E+09 | 0.230942E+09 | 0.607937E+09 | 0.202669E+09 |
| September | 0.349337E+09 | 0.163701E+09 | 0.185636E+09 | 0.356379E+09 | 0.288989E+09 |
| October | 0.160328E+09 | 46741062.80 | 0.113587E+09 | 88509539.81 | 0.414525E+09 |
| November | 69869991.29 | 5678001.70 | 64191989.59 | 6011822.41 | 0.477218E+09 |
| December | 48942433.36 | 1112868.89 | 47829564.47 | 70328.10 | 0.585663E+09 |
| Annual Sum or Average | 0.347785E+10 | 0.148583E+10 | 0.199202E+10 | 0.326174E+10 | 0.459356E+10 |
| Minimum of Months | 48942433.36 | 1112868.89 | 47829564.47 | 70328.10 | 0.202669E+09 |
| Maximum of Months | 0.616660E+09 | 0.342404E+09 | 0.287151E+09 | 0.738652E+09 | 0.585663E+09 |
Report: WindowEnergyReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 56104500.24 | 33315102.66 | 22789397.58 | 48989596.23 | 77117017.81 |
| February | 77930411.68 | 48239983.20 | 29690428.48 | 78447293.91 | 63719479.99 |
| March | 92812450.48 | 49495866.20 | 43316584.28 | 97303574.67 | 64657409.21 |
| April | 94831294.57 | 41175224.75 | 53656069.83 | 0.104847E+09 | 54248865.65 |
| May | 89601420.78 | 26693171.61 | 62908249.17 | 99279268.35 | 48802834.35 |
| June | 79332153.95 | 21299683.52 | 58032470.43 | 89559740.37 | 37972620.59 |
| July | 89399009.77 | 32742678.17 | 56656331.60 | 0.113050E+09 | 34735214.46 |
| August | 96047970.16 | 44788767.14 | 51259203.01 | 0.126343E+09 | 33863617.75 |
| September | 0.102984E+09 | 56871391.12 | 46113007.04 | 0.125301E+09 | 46553774.57 |
| October | 96395973.21 | 59517400.87 | 36878572.34 | 0.106792E+09 | 61221572.37 |
| November | 55154039.51 | 31607908.94 | 23546130.57 | 50967927.06 | 66725842.33 |
| December | 59630482.93 | 38589243.89 | 21041239.04 | 57731864.94 | 80814405.99 |
| Annual Sum or Average | 0.990224E+09 | 0.484336E+09 | 0.505888E+09 | 0.109861E+10 | 0.670433E+09 |
| Minimum of Months | 55154039.51 | 21299683.52 | 21041239.04 | 48989596.23 | 33863617.75 |
| Maximum of Months | 0.102984E+09 | 59517400.87 | 62908249.17 | 0.126343E+09 | 80814405.99 |
Report: WindowEnergyReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.757521E+09 | 0.449819E+09 | 0.307702E+09 | 0.661456E+09 | 0.104123E+10 |
| February | 0.105221E+10 | 0.651335E+09 | 0.400879E+09 | 0.105919E+10 | 0.860338E+09 |
| March | 0.125315E+10 | 0.668292E+09 | 0.584859E+09 | 0.131379E+10 | 0.873002E+09 |
| April | 0.128041E+10 | 0.555947E+09 | 0.724463E+09 | 0.141564E+10 | 0.732466E+09 |
| May | 0.120980E+10 | 0.360410E+09 | 0.849385E+09 | 0.134047E+10 | 0.658934E+09 |
| June | 0.107114E+10 | 0.287588E+09 | 0.783553E+09 | 0.120923E+10 | 0.512705E+09 |
| July | 0.120706E+10 | 0.442091E+09 | 0.764972E+09 | 0.152639E+10 | 0.468994E+09 |
| August | 0.129684E+10 | 0.604737E+09 | 0.692100E+09 | 0.170588E+10 | 0.457226E+09 |
| September | 0.139049E+10 | 0.767876E+09 | 0.622616E+09 | 0.169181E+10 | 0.628568E+09 |
| October | 0.130154E+10 | 0.803602E+09 | 0.497933E+09 | 0.144190E+10 | 0.826612E+09 |
| November | 0.744688E+09 | 0.426769E+09 | 0.317919E+09 | 0.688167E+09 | 0.900930E+09 |
| December | 0.805129E+09 | 0.521031E+09 | 0.284098E+09 | 0.779494E+09 | 0.109115E+10 |
| Annual Sum or Average | 0.133700E+11 | 0.653950E+10 | 0.683048E+10 | 0.148334E+11 | 0.905216E+10 |
| Minimum of Months | 0.744688E+09 | 0.287588E+09 | 0.284098E+09 | 0.661456E+09 | 0.457226E+09 |
| Maximum of Months | 0.139049E+10 | 0.803602E+09 | 0.849385E+09 | 0.170588E+10 | 0.109115E+10 |
Report: WindowEnergyReportMonthly
For: BATH_ZN_1_FLR_1_WALL_5_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 93848763.71 | 13579400.41 | 80269363.30 | 8456499.08 | 0.688201E+09 |
| February | 0.172146E+09 | 52464696.09 | 0.119681E+09 | 78133564.13 | 0.563933E+09 |
| March | 0.312072E+09 | 0.102540E+09 | 0.209533E+09 | 0.201117E+09 | 0.564607E+09 |
| April | 0.500646E+09 | 0.204531E+09 | 0.296116E+09 | 0.436267E+09 | 0.475379E+09 |
| May | 0.679275E+09 | 0.296594E+09 | 0.382681E+09 | 0.662932E+09 | 0.440918E+09 |
| June | 0.625554E+09 | 0.260300E+09 | 0.365254E+09 | 0.618795E+09 | 0.346888E+09 |
| July | 0.809749E+09 | 0.444895E+09 | 0.364854E+09 | 0.952344E+09 | 0.301830E+09 |
| August | 0.667976E+09 | 0.358734E+09 | 0.309243E+09 | 0.802755E+09 | 0.284722E+09 |
| September | 0.499942E+09 | 0.245390E+09 | 0.254552E+09 | 0.513494E+09 | 0.397107E+09 |
| October | 0.250888E+09 | 90905830.07 | 0.159982E+09 | 0.166443E+09 | 0.541992E+09 |
| November | 0.109775E+09 | 19671711.10 | 90102852.38 | 24412198.80 | 0.611768E+09 |
| December | 77321584.59 | 10299449.76 | 67022134.83 | 7592259.15 | 0.717218E+09 |
| Annual Sum or Average | 0.479919E+10 | 0.209990E+10 | 0.269929E+10 | 0.447274E+10 | 0.593456E+10 |
| Minimum of Months | 77321584.59 | 10299449.76 | 67022134.83 | 7592259.15 | 0.284722E+09 |
| Maximum of Months | 0.809749E+09 | 0.444895E+09 | 0.382681E+09 | 0.952344E+09 | 0.717218E+09 |
Report: WindowEnergyReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.327040E+09 | 82915440.71 | 0.244124E+09 | 92381751.63 | 0.147380E+10 |
| February | 0.542013E+09 | 0.192372E+09 | 0.349641E+09 | 0.306632E+09 | 0.120203E+10 |
| March | 0.895971E+09 | 0.324349E+09 | 0.571622E+09 | 0.644956E+09 | 0.117462E+10 |
| April | 0.134410E+10 | 0.558495E+09 | 0.785610E+09 | 0.123043E+10 | 0.935570E+09 |
| May | 0.147792E+10 | 0.513840E+09 | 0.964083E+09 | 0.142480E+10 | 0.838738E+09 |
| June | 0.171288E+10 | 0.745287E+09 | 0.967595E+09 | 0.182242E+10 | 0.642122E+09 |
| July | 0.164826E+10 | 0.739834E+09 | 0.908427E+09 | 0.186232E+10 | 0.568175E+09 |
| August | 0.162001E+10 | 0.810422E+09 | 0.809589E+09 | 0.191423E+10 | 0.554152E+09 |
| September | 0.115912E+10 | 0.534597E+09 | 0.624525E+09 | 0.115734E+10 | 0.808294E+09 |
| October | 0.780698E+09 | 0.331723E+09 | 0.448975E+09 | 0.605193E+09 | 0.112587E+10 |
| November | 0.370311E+09 | 0.104543E+09 | 0.265769E+09 | 0.152455E+09 | 0.128172E+10 |
| December | 0.313863E+09 | 0.101042E+09 | 0.212821E+09 | 0.122003E+09 | 0.153133E+10 |
| Annual Sum or Average | 0.121922E+11 | 0.503942E+10 | 0.715278E+10 | 0.113352E+11 | 0.121364E+11 |
| Minimum of Months | 0.313863E+09 | 82915440.71 | 0.212821E+09 | 92381751.63 | 0.554152E+09 |
| Maximum of Months | 0.171288E+10 | 0.810422E+09 | 0.967595E+09 | 0.191423E+10 | 0.153133E+10 |
Report: WindowEnergyReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 55707468.25 | 33079343.29 | 22628124.96 | 46746653.89 | 84166951.05 |
| February | 77378925.33 | 47898605.66 | 29480319.67 | 75073373.74 | 69536033.88 |
| March | 92155649.13 | 49145601.21 | 43010047.92 | 92093826.83 | 72743906.65 |
| April | 94160206.56 | 40883842.04 | 53276364.53 | 98403414.29 | 62214248.95 |
| May | 88967342.77 | 26504273.35 | 62463069.42 | 92586792.06 | 55833972.03 |
| June | 78770747.95 | 21148953.08 | 57621794.87 | 83054599.25 | 43600862.67 |
| July | 88766364.15 | 32510969.65 | 56255394.50 | 0.107660E+09 | 39044735.21 |
| August | 95368272.16 | 44471812.65 | 50896459.50 | 0.121712E+09 | 37655369.65 |
| September | 0.102256E+09 | 56468932.11 | 45786681.37 | 0.120804E+09 | 51483229.07 |
| October | 95713812.52 | 59096216.98 | 36617595.54 | 0.102400E+09 | 68766188.61 |
| November | 54763733.60 | 31384230.79 | 23379502.81 | 48220919.41 | 74540846.65 |
| December | 59208498.79 | 38316161.27 | 20892337.52 | 55540494.45 | 88747427.34 |
| Annual Sum or Average | 0.983217E+09 | 0.480909E+09 | 0.502308E+09 | 0.104430E+10 | 0.748334E+09 |
| Minimum of Months | 54763733.60 | 21148953.08 | 20892337.52 | 46746653.89 | 37655369.65 |
| Maximum of Months | 0.102256E+09 | 59096216.98 | 62463069.42 | 0.121712E+09 | 88747427.34 |
Report: WindowEnergyReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.843544E+09 | 0.500900E+09 | 0.342644E+09 | 0.707856E+09 | 0.127449E+10 |
| February | 0.117170E+10 | 0.725299E+09 | 0.446402E+09 | 0.113679E+10 | 0.105294E+10 |
| March | 0.139546E+10 | 0.744182E+09 | 0.651275E+09 | 0.139452E+10 | 0.110152E+10 |
| April | 0.142581E+10 | 0.619079E+09 | 0.806731E+09 | 0.149006E+10 | 0.941946E+09 |
| May | 0.134718E+10 | 0.401338E+09 | 0.945840E+09 | 0.140199E+10 | 0.845024E+09 |
| June | 0.119278E+10 | 0.320246E+09 | 0.872532E+09 | 0.125765E+10 | 0.659479E+09 |
| July | 0.134413E+10 | 0.492294E+09 | 0.851841E+09 | 0.163024E+10 | 0.590390E+09 |
| August | 0.144410E+10 | 0.673409E+09 | 0.770694E+09 | 0.184301E+10 | 0.569616E+09 |
| September | 0.154839E+10 | 0.855075E+09 | 0.693320E+09 | 0.182927E+10 | 0.779566E+09 |
| October | 0.144934E+10 | 0.894858E+09 | 0.554478E+09 | 0.155058E+10 | 0.104128E+10 |
| November | 0.829254E+09 | 0.475232E+09 | 0.354022E+09 | 0.730180E+09 | 0.112873E+10 |
| December | 0.896558E+09 | 0.580198E+09 | 0.316360E+09 | 0.841016E+09 | 0.134385E+10 |
| Annual Sum or Average | 0.148882E+11 | 0.728211E+10 | 0.760614E+10 | 0.158132E+11 | 0.113288E+11 |
| Minimum of Months | 0.829254E+09 | 0.320246E+09 | 0.316360E+09 | 0.707856E+09 | 0.569616E+09 |
| Maximum of Months | 0.154839E+10 | 0.894858E+09 | 0.945840E+09 | 0.184301E+10 | 0.134385E+10 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 46654281.46 | 10180633.63 | 36473647.83 | 17552268.84 | 0.168313E+09 |
| February | 77537425.01 | 28629215.42 | 48908209.59 | 56784031.80 | 0.141137E+09 |
| March | 0.140117E+09 | 59081272.82 | 81035712.33 | 0.128160E+09 | 0.139467E+09 |
| April | 0.218750E+09 | 0.111380E+09 | 0.107369E+09 | 0.235066E+09 | 0.114685E+09 |
| May | 0.293147E+09 | 0.150965E+09 | 0.142182E+09 | 0.338586E+09 | 0.101287E+09 |
| June | 0.309591E+09 | 0.180919E+09 | 0.128672E+09 | 0.367114E+09 | 80359442.96 |
| July | 0.334217E+09 | 0.220155E+09 | 0.114062E+09 | 0.416671E+09 | 76845289.96 |
| August | 0.266505E+09 | 0.168584E+09 | 97921574.14 | 0.333619E+09 | 77102243.97 |
| September | 0.182070E+09 | 0.100632E+09 | 81437954.66 | 0.208132E+09 | 0.101068E+09 |
| October | 0.108797E+09 | 49234496.97 | 59562351.07 | 0.100823E+09 | 0.133718E+09 |
| November | 53092413.78 | 13298925.03 | 39793488.75 | 28999849.93 | 0.144743E+09 |
| December | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 0.179476E+09 |
| Annual Sum or Average | 0.206968E+10 | 0.110255E+10 | 0.967134E+09 | 0.224563E+10 | 0.145820E+10 |
| Minimum of Months | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 76845289.96 |
| Maximum of Months | 0.334217E+09 | 0.220155E+09 | 0.142182E+09 | 0.416671E+09 | 0.179476E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 46654281.46 | 10180633.63 | 36473647.83 | 17552268.84 | 0.168313E+09 |
| February | 77537425.01 | 28629215.42 | 48908209.59 | 56784031.80 | 0.141137E+09 |
| March | 0.140117E+09 | 59081272.82 | 81035712.33 | 0.128160E+09 | 0.139467E+09 |
| April | 0.218750E+09 | 0.111380E+09 | 0.107369E+09 | 0.235066E+09 | 0.114685E+09 |
| May | 0.293147E+09 | 0.150965E+09 | 0.142182E+09 | 0.338586E+09 | 0.101287E+09 |
| June | 0.309591E+09 | 0.180919E+09 | 0.128672E+09 | 0.367114E+09 | 80359442.96 |
| July | 0.334217E+09 | 0.220155E+09 | 0.114062E+09 | 0.416671E+09 | 76845289.96 |
| August | 0.266505E+09 | 0.168584E+09 | 97921574.14 | 0.333619E+09 | 77102243.97 |
| September | 0.182070E+09 | 0.100632E+09 | 81437954.66 | 0.208132E+09 | 0.101068E+09 |
| October | 0.108797E+09 | 49234496.97 | 59562351.07 | 0.100823E+09 | 0.133718E+09 |
| November | 53092413.78 | 13298925.03 | 39793488.75 | 28999849.93 | 0.144743E+09 |
| December | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 0.179476E+09 |
| Annual Sum or Average | 0.206968E+10 | 0.110255E+10 | 0.967134E+09 | 0.224563E+10 | 0.145820E+10 |
| Minimum of Months | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 76845289.96 |
| Maximum of Months | 0.334217E+09 | 0.220155E+09 | 0.142182E+09 | 0.416671E+09 | 0.179476E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 46654281.46 | 10180633.63 | 36473647.83 | 17552268.84 | 0.168313E+09 |
| February | 77537425.01 | 28629215.42 | 48908209.59 | 56784031.80 | 0.141137E+09 |
| March | 0.140117E+09 | 59081272.82 | 81035712.33 | 0.128160E+09 | 0.139467E+09 |
| April | 0.218750E+09 | 0.111380E+09 | 0.107369E+09 | 0.235066E+09 | 0.114685E+09 |
| May | 0.293147E+09 | 0.150965E+09 | 0.142182E+09 | 0.338586E+09 | 0.101287E+09 |
| June | 0.309591E+09 | 0.180919E+09 | 0.128672E+09 | 0.367114E+09 | 80359442.96 |
| July | 0.334217E+09 | 0.220155E+09 | 0.114062E+09 | 0.416671E+09 | 76845289.96 |
| August | 0.266505E+09 | 0.168584E+09 | 97921574.14 | 0.333619E+09 | 77102243.97 |
| September | 0.182070E+09 | 0.100632E+09 | 81437954.66 | 0.208132E+09 | 0.101068E+09 |
| October | 0.108797E+09 | 49234496.97 | 59562351.07 | 0.100823E+09 | 0.133718E+09 |
| November | 53092413.78 | 13298925.03 | 39793488.75 | 28999849.93 | 0.144743E+09 |
| December | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 0.179476E+09 |
| Annual Sum or Average | 0.206968E+10 | 0.110255E+10 | 0.967134E+09 | 0.224563E+10 | 0.145820E+10 |
| Minimum of Months | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 76845289.96 |
| Maximum of Months | 0.334217E+09 | 0.220155E+09 | 0.142182E+09 | 0.416671E+09 | 0.179476E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 46654281.46 | 10180633.63 | 36473647.83 | 17552268.84 | 0.168313E+09 |
| February | 77537425.01 | 28629215.42 | 48908209.59 | 56784031.80 | 0.141137E+09 |
| March | 0.140117E+09 | 59081272.82 | 81035712.33 | 0.128160E+09 | 0.139467E+09 |
| April | 0.218750E+09 | 0.111380E+09 | 0.107369E+09 | 0.235066E+09 | 0.114685E+09 |
| May | 0.293147E+09 | 0.150965E+09 | 0.142182E+09 | 0.338586E+09 | 0.101287E+09 |
| June | 0.309591E+09 | 0.180919E+09 | 0.128672E+09 | 0.367114E+09 | 80359442.96 |
| July | 0.334217E+09 | 0.220155E+09 | 0.114062E+09 | 0.416671E+09 | 76845289.96 |
| August | 0.266505E+09 | 0.168584E+09 | 97921574.14 | 0.333619E+09 | 77102243.97 |
| September | 0.182070E+09 | 0.100632E+09 | 81437954.66 | 0.208132E+09 | 0.101068E+09 |
| October | 0.108797E+09 | 49234496.97 | 59562351.07 | 0.100823E+09 | 0.133718E+09 |
| November | 53092413.78 | 13298925.03 | 39793488.75 | 28999849.93 | 0.144743E+09 |
| December | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 0.179476E+09 |
| Annual Sum or Average | 0.206968E+10 | 0.110255E+10 | 0.967134E+09 | 0.224563E+10 | 0.145820E+10 |
| Minimum of Months | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 76845289.96 |
| Maximum of Months | 0.334217E+09 | 0.220155E+09 | 0.142182E+09 | 0.416671E+09 | 0.179476E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 46654281.46 | 10180633.63 | 36473647.83 | 17552268.84 | 0.168313E+09 |
| February | 77537425.01 | 28629215.42 | 48908209.59 | 56784031.80 | 0.141137E+09 |
| March | 0.140117E+09 | 59081272.82 | 81035712.33 | 0.128160E+09 | 0.139467E+09 |
| April | 0.218750E+09 | 0.111380E+09 | 0.107369E+09 | 0.235066E+09 | 0.114685E+09 |
| May | 0.293147E+09 | 0.150965E+09 | 0.142182E+09 | 0.338586E+09 | 0.101287E+09 |
| June | 0.309591E+09 | 0.180919E+09 | 0.128672E+09 | 0.367114E+09 | 80359442.96 |
| July | 0.334217E+09 | 0.220155E+09 | 0.114062E+09 | 0.416671E+09 | 76845289.96 |
| August | 0.266505E+09 | 0.168584E+09 | 97921574.14 | 0.333619E+09 | 77102243.97 |
| September | 0.182070E+09 | 0.100632E+09 | 81437954.66 | 0.208132E+09 | 0.101068E+09 |
| October | 0.108797E+09 | 49234496.97 | 59562351.07 | 0.100823E+09 | 0.133718E+09 |
| November | 53092413.78 | 13298925.03 | 39793488.75 | 28999849.93 | 0.144743E+09 |
| December | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 0.179476E+09 |
| Annual Sum or Average | 0.206968E+10 | 0.110255E+10 | 0.967134E+09 | 0.224563E+10 | 0.145820E+10 |
| Minimum of Months | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 76845289.96 |
| Maximum of Months | 0.334217E+09 | 0.220155E+09 | 0.142182E+09 | 0.416671E+09 | 0.179476E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 46654281.46 | 10180633.63 | 36473647.83 | 17552268.84 | 0.168313E+09 |
| February | 77537425.01 | 28629215.42 | 48908209.59 | 56784031.80 | 0.141137E+09 |
| March | 0.140117E+09 | 59081272.82 | 81035712.33 | 0.128160E+09 | 0.139467E+09 |
| April | 0.218750E+09 | 0.111380E+09 | 0.107369E+09 | 0.235066E+09 | 0.114685E+09 |
| May | 0.293147E+09 | 0.150965E+09 | 0.142182E+09 | 0.338586E+09 | 0.101287E+09 |
| June | 0.309591E+09 | 0.180919E+09 | 0.128672E+09 | 0.367114E+09 | 80359442.96 |
| July | 0.334217E+09 | 0.220155E+09 | 0.114062E+09 | 0.416671E+09 | 76845289.96 |
| August | 0.266505E+09 | 0.168584E+09 | 97921574.14 | 0.333619E+09 | 77102243.97 |
| September | 0.182070E+09 | 0.100632E+09 | 81437954.66 | 0.208132E+09 | 0.101068E+09 |
| October | 0.108797E+09 | 49234496.97 | 59562351.07 | 0.100823E+09 | 0.133718E+09 |
| November | 53092413.78 | 13298925.03 | 39793488.75 | 28999849.93 | 0.144743E+09 |
| December | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 0.179476E+09 |
| Annual Sum or Average | 0.206968E+10 | 0.110255E+10 | 0.967134E+09 | 0.224563E+10 | 0.145820E+10 |
| Minimum of Months | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 76845289.96 |
| Maximum of Months | 0.334217E+09 | 0.220155E+09 | 0.142182E+09 | 0.416671E+09 | 0.179476E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 46654281.46 | 10180633.63 | 36473647.83 | 17552268.84 | 0.168313E+09 |
| February | 77537425.01 | 28629215.42 | 48908209.59 | 56784031.80 | 0.141137E+09 |
| March | 0.140117E+09 | 59081272.82 | 81035712.33 | 0.128160E+09 | 0.139467E+09 |
| April | 0.218750E+09 | 0.111380E+09 | 0.107369E+09 | 0.235066E+09 | 0.114685E+09 |
| May | 0.293147E+09 | 0.150965E+09 | 0.142182E+09 | 0.338586E+09 | 0.101287E+09 |
| June | 0.309591E+09 | 0.180919E+09 | 0.128672E+09 | 0.367114E+09 | 80359442.96 |
| July | 0.334217E+09 | 0.220155E+09 | 0.114062E+09 | 0.416671E+09 | 76845289.96 |
| August | 0.266505E+09 | 0.168584E+09 | 97921574.14 | 0.333619E+09 | 77102243.97 |
| September | 0.182070E+09 | 0.100632E+09 | 81437954.66 | 0.208132E+09 | 0.101068E+09 |
| October | 0.108797E+09 | 49234496.97 | 59562351.07 | 0.100823E+09 | 0.133718E+09 |
| November | 53092413.78 | 13298925.03 | 39793488.75 | 28999849.93 | 0.144743E+09 |
| December | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 0.179476E+09 |
| Annual Sum or Average | 0.206968E+10 | 0.110255E+10 | 0.967134E+09 | 0.224563E+10 | 0.145820E+10 |
| Minimum of Months | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 76845289.96 |
| Maximum of Months | 0.334217E+09 | 0.220155E+09 | 0.142182E+09 | 0.416671E+09 | 0.179476E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 46654281.46 | 10180633.63 | 36473647.83 | 17552268.84 | 0.168313E+09 |
| February | 77537425.01 | 28629215.42 | 48908209.59 | 56784031.80 | 0.141137E+09 |
| March | 0.140117E+09 | 59081272.82 | 81035712.33 | 0.128160E+09 | 0.139467E+09 |
| April | 0.218750E+09 | 0.111380E+09 | 0.107369E+09 | 0.235066E+09 | 0.114685E+09 |
| May | 0.293147E+09 | 0.150965E+09 | 0.142182E+09 | 0.338586E+09 | 0.101287E+09 |
| June | 0.309591E+09 | 0.180919E+09 | 0.128672E+09 | 0.367114E+09 | 80359442.96 |
| July | 0.334217E+09 | 0.220155E+09 | 0.114062E+09 | 0.416671E+09 | 76845289.96 |
| August | 0.266505E+09 | 0.168584E+09 | 97921574.14 | 0.333619E+09 | 77102243.97 |
| September | 0.182070E+09 | 0.100632E+09 | 81437954.66 | 0.208132E+09 | 0.101068E+09 |
| October | 0.108797E+09 | 49234496.97 | 59562351.07 | 0.100823E+09 | 0.133718E+09 |
| November | 53092413.78 | 13298925.03 | 39793488.75 | 28999849.93 | 0.144743E+09 |
| December | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 0.179476E+09 |
| Annual Sum or Average | 0.206968E+10 | 0.110255E+10 | 0.967134E+09 | 0.224563E+10 | 0.145820E+10 |
| Minimum of Months | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 76845289.96 |
| Maximum of Months | 0.334217E+09 | 0.220155E+09 | 0.142182E+09 | 0.416671E+09 | 0.179476E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 46654281.46 | 10180633.63 | 36473647.83 | 17552268.84 | 0.168313E+09 |
| February | 77537425.01 | 28629215.42 | 48908209.59 | 56784031.80 | 0.141137E+09 |
| March | 0.140117E+09 | 59081272.82 | 81035712.33 | 0.128160E+09 | 0.139467E+09 |
| April | 0.218750E+09 | 0.111380E+09 | 0.107369E+09 | 0.235066E+09 | 0.114685E+09 |
| May | 0.293147E+09 | 0.150965E+09 | 0.142182E+09 | 0.338586E+09 | 0.101287E+09 |
| June | 0.309591E+09 | 0.180919E+09 | 0.128672E+09 | 0.367114E+09 | 80359442.96 |
| July | 0.334217E+09 | 0.220155E+09 | 0.114062E+09 | 0.416671E+09 | 76845289.96 |
| August | 0.266505E+09 | 0.168584E+09 | 97921574.14 | 0.333619E+09 | 77102243.97 |
| September | 0.182070E+09 | 0.100632E+09 | 81437954.66 | 0.208132E+09 | 0.101068E+09 |
| October | 0.108797E+09 | 49234496.97 | 59562351.07 | 0.100823E+09 | 0.133718E+09 |
| November | 53092413.78 | 13298925.03 | 39793488.75 | 28999849.93 | 0.144743E+09 |
| December | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 0.179476E+09 |
| Annual Sum or Average | 0.206968E+10 | 0.110255E+10 | 0.967134E+09 | 0.224563E+10 | 0.145820E+10 |
| Minimum of Months | 39206260.98 | 9489648.56 | 29716612.41 | 14119776.08 | 76845289.96 |
| Maximum of Months | 0.334217E+09 | 0.220155E+09 | 0.142182E+09 | 0.416671E+09 | 0.179476E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 20622343.40 | 5228449.22 | 15393894.18 | 5294790.65 | 0.101493E+09 |
| February | 34178057.02 | 12130514.28 | 22047542.74 | 18217362.70 | 83112674.84 |
| March | 56497751.93 | 20452669.66 | 36045082.27 | 39238019.31 | 81167469.37 |
| April | 84756001.45 | 35217361.34 | 49538640.12 | 75122564.69 | 64187773.36 |
| May | 93194187.48 | 32401491.62 | 60792695.86 | 87661852.97 | 56430584.70 |
| June | 0.108010E+09 | 46996024.60 | 61014208.45 | 0.113178E+09 | 42722737.53 |
| July | 0.103935E+09 | 46652177.56 | 57283182.33 | 0.115642E+09 | 38115150.70 |
| August | 0.102154E+09 | 51103256.73 | 51050684.53 | 0.119756E+09 | 36370988.31 |
| September | 73091482.81 | 33710427.36 | 39381055.45 | 72644993.94 | 52234560.64 |
| October | 49228957.59 | 20917681.59 | 28311276.00 | 37762111.39 | 74264148.19 |
| November | 23350945.86 | 6592204.58 | 16758741.28 | 9189972.14 | 87226813.84 |
| December | 19791456.73 | 6371455.54 | 13420001.19 | 7188136.93 | 0.105421E+09 |
| Annual Sum or Average | 0.768811E+09 | 0.317774E+09 | 0.451037E+09 | 0.700895E+09 | 0.822747E+09 |
| Minimum of Months | 19791456.73 | 5228449.22 | 13420001.19 | 5294790.65 | 36370988.31 |
| Maximum of Months | 0.108010E+09 | 51103256.73 | 61014208.45 | 0.119756E+09 | 0.105421E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.244088E+09 | 61882546.45 | 0.182206E+09 | 62654591.59 | 0.120127E+10 |
| February | 0.404535E+09 | 0.143574E+09 | 0.260961E+09 | 0.215690E+09 | 0.983469E+09 |
| March | 0.668714E+09 | 0.242072E+09 | 0.426641E+09 | 0.464891E+09 | 0.960421E+09 |
| April | 0.100318E+10 | 0.416823E+09 | 0.586358E+09 | 0.890739E+09 | 0.759612E+09 |
| May | 0.110306E+10 | 0.383496E+09 | 0.719568E+09 | 0.104025E+10 | 0.668027E+09 |
| June | 0.127842E+10 | 0.556233E+09 | 0.722192E+09 | 0.134168E+10 | 0.505645E+09 |
| July | 0.123020E+10 | 0.552163E+09 | 0.678036E+09 | 0.137264E+10 | 0.451168E+09 |
| August | 0.120911E+10 | 0.604845E+09 | 0.604261E+09 | 0.142071E+10 | 0.430627E+09 |
| September | 0.865119E+09 | 0.398988E+09 | 0.466131E+09 | 0.862313E+09 | 0.618270E+09 |
| October | 0.582678E+09 | 0.247576E+09 | 0.335102E+09 | 0.447495E+09 | 0.878898E+09 |
| November | 0.276384E+09 | 78023595.29 | 0.198361E+09 | 0.108815E+09 | 0.103241E+10 |
| December | 0.234253E+09 | 75410867.87 | 0.158842E+09 | 85062548.90 | 0.124778E+10 |
| Annual Sum or Average | 0.909974E+10 | 0.376109E+10 | 0.533866E+10 | 0.831295E+10 | 0.973760E+10 |
| Minimum of Months | 0.234253E+09 | 61882546.45 | 0.158842E+09 | 62654591.59 | 0.430627E+09 |
| Maximum of Months | 0.127842E+10 | 0.604845E+09 | 0.722192E+09 | 0.142071E+10 | 0.124778E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.124583E+09 | 31585819.68 | 92997450.63 | 23207720.16 | 0.835112E+09 |
| February | 0.206476E+09 | 73282195.22 | 0.133194E+09 | 91738907.46 | 0.660615E+09 |
| March | 0.341313E+09 | 0.123558E+09 | 0.217756E+09 | 0.218622E+09 | 0.596793E+09 |
| April | 0.512026E+09 | 0.212753E+09 | 0.299273E+09 | 0.440390E+09 | 0.441886E+09 |
| May | 0.563003E+09 | 0.195742E+09 | 0.367261E+09 | 0.523592E+09 | 0.379486E+09 |
| June | 0.652509E+09 | 0.283910E+09 | 0.368600E+09 | 0.679516E+09 | 0.287320E+09 |
| July | 0.627893E+09 | 0.281833E+09 | 0.346060E+09 | 0.694439E+09 | 0.258703E+09 |
| August | 0.617130E+09 | 0.308722E+09 | 0.308408E+09 | 0.719378E+09 | 0.249904E+09 |
| September | 0.441559E+09 | 0.203650E+09 | 0.237909E+09 | 0.432215E+09 | 0.357270E+09 |
| October | 0.297401E+09 | 0.126367E+09 | 0.171034E+09 | 0.216479E+09 | 0.531863E+09 |
| November | 0.141067E+09 | 39824463.49 | 0.101243E+09 | 46957401.98 | 0.672513E+09 |
| December | 0.119564E+09 | 38490886.54 | 81072796.48 | 34565499.85 | 0.847726E+09 |
| Annual Sum or Average | 0.464453E+10 | 0.191972E+10 | 0.272481E+10 | 0.412110E+10 | 0.611919E+10 |
| Minimum of Months | 0.119564E+09 | 31585819.68 | 81072796.48 | 23207720.16 | 0.249904E+09 |
| Maximum of Months | 0.652509E+09 | 0.308722E+09 | 0.368600E+09 | 0.719378E+09 | 0.847726E+09 |
Report: WindowEnergyReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.191640E+09 | 0.00 | 0.191640E+09 | 374353.36 | 0.163677E+10 |
| February | 0.269115E+09 | 0.00 | 0.269115E+09 | 24364620.31 | 0.134583E+10 |
| March | 0.439036E+09 | 0.00 | 0.439036E+09 | 97284600.44 | 0.123397E+10 |
| April | 0.598042E+09 | 1317224.13 | 0.596724E+09 | 0.268459E+09 | 0.973149E+09 |
| May | 0.786648E+09 | 16153406.87 | 0.770494E+09 | 0.477847E+09 | 0.840915E+09 |
| June | 0.794426E+09 | 41702111.53 | 0.752723E+09 | 0.534038E+09 | 0.651223E+09 |
| July | 0.770849E+09 | 40786617.67 | 0.730063E+09 | 0.642621E+09 | 0.583050E+09 |
| August | 0.637776E+09 | 11617804.04 | 0.626158E+09 | 0.563965E+09 | 0.564880E+09 |
| September | 0.485146E+09 | 89065.39 | 0.485057E+09 | 0.265579E+09 | 0.835117E+09 |
| October | 0.343756E+09 | 0.00 | 0.343756E+09 | 72861163.53 | 0.115009E+10 |
| November | 0.210040E+09 | 0.00 | 0.210040E+09 | 7213844.81 | 0.136676E+10 |
| December | 0.162464E+09 | 0.00 | 0.162464E+09 | 288158.64 | 0.168632E+10 |
| Annual Sum or Average | 0.568894E+10 | 0.111666E+09 | 0.557727E+10 | 0.295490E+10 | 0.128681E+11 |
| Minimum of Months | 0.162464E+09 | 0.00 | 0.162464E+09 | 288158.64 | 0.564880E+09 |
| Maximum of Months | 0.794426E+09 | 41702111.53 | 0.770494E+09 | 0.642621E+09 | 0.168632E+10 |
Report: WindowEnergyReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 20817909.84 | 5278031.81 | 15539878.03 | 5675460.66 | 98498922.77 |
| February | 34502175.42 | 12245550.74 | 22256624.68 | 19134116.14 | 79027086.87 |
| March | 57033533.15 | 20646627.05 | 36386906.10 | 41889182.04 | 73737766.68 |
| April | 85559762.18 | 35551335.70 | 50008426.47 | 79807490.39 | 57513407.58 |
| May | 94077969.47 | 32708762.44 | 61369207.03 | 91708559.14 | 52365718.15 |
| June | 0.109035E+09 | 47441698.75 | 61592820.27 | 0.116133E+09 | 41563181.87 |
| July | 0.104921E+09 | 47094590.92 | 57826411.97 | 0.118732E+09 | 36487193.68 |
| August | 0.103123E+09 | 51587880.71 | 51534809.95 | 0.122710E+09 | 34942417.86 |
| September | 73784626.21 | 34030111.12 | 39754515.09 | 74879012.45 | 50445276.86 |
| October | 49695807.16 | 21116048.80 | 28579758.36 | 39632425.43 | 69268222.43 |
| November | 23572388.27 | 6654719.98 | 16917668.29 | 9716187.07 | 83002770.72 |
| December | 19979143.68 | 6431877.52 | 13547266.16 | 7583789.69 | 0.102396E+09 |
| Annual Sum or Average | 0.776102E+09 | 0.320787E+09 | 0.455314E+09 | 0.727601E+09 | 0.779248E+09 |
| Minimum of Months | 19979143.68 | 5278031.81 | 13547266.16 | 5675460.66 | 34942417.86 |
| Maximum of Months | 0.109035E+09 | 51587880.71 | 61592820.27 | 0.122710E+09 | 0.102396E+09 |
Report: WindowEnergyReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.212783E+09 | 53947441.96 | 0.158835E+09 | 58009613.29 | 0.100677E+10 |
| February | 0.352651E+09 | 0.125163E+09 | 0.227488E+09 | 0.195572E+09 | 0.807746E+09 |
| March | 0.582947E+09 | 0.211032E+09 | 0.371915E+09 | 0.428155E+09 | 0.753683E+09 |
| April | 0.874517E+09 | 0.363375E+09 | 0.511143E+09 | 0.815724E+09 | 0.587848E+09 |
| May | 0.961583E+09 | 0.334320E+09 | 0.627263E+09 | 0.937379E+09 | 0.535096E+09 |
| June | 0.111446E+10 | 0.484908E+09 | 0.629548E+09 | 0.118710E+10 | 0.424608E+09 |
| July | 0.107241E+10 | 0.481360E+09 | 0.591051E+09 | 0.121369E+10 | 0.372635E+09 |
| August | 0.105403E+10 | 0.527286E+09 | 0.526744E+09 | 0.125428E+10 | 0.357101E+09 |
| September | 0.754162E+09 | 0.347826E+09 | 0.406336E+09 | 0.765348E+09 | 0.515608E+09 |
| October | 0.507947E+09 | 0.215830E+09 | 0.292117E+09 | 0.405088E+09 | 0.707999E+09 |
| November | 0.240936E+09 | 68018748.74 | 0.172918E+09 | 99310397.64 | 0.848382E+09 |
| December | 0.204209E+09 | 65741047.37 | 0.138468E+09 | 77514889.75 | 0.104661E+10 |
| Annual Sum or Average | 0.793263E+10 | 0.327881E+10 | 0.465383E+10 | 0.743716E+10 | 0.796408E+10 |
| Minimum of Months | 0.204209E+09 | 53947441.96 | 0.138468E+09 | 58009613.29 | 0.357101E+09 |
| Maximum of Months | 0.111446E+10 | 0.527286E+09 | 0.629548E+09 | 0.125428E+10 | 0.104661E+10 |
Report: WindowEnergyReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.184138E+09 | 0.00 | 0.184138E+09 | 1357854.61 | 0.142493E+10 |
| February | 0.258796E+09 | 0.00 | 0.258796E+09 | 29153601.17 | 0.118305E+10 |
| March | 0.422149E+09 | 0.00 | 0.422149E+09 | 96143472.23 | 0.115464E+10 |
| April | 0.578114E+09 | 2050698.08 | 0.576064E+09 | 0.260885E+09 | 0.920635E+09 |
| May | 0.768684E+09 | 22835932.74 | 0.745848E+09 | 0.481041E+09 | 0.778609E+09 |
| June | 0.782180E+09 | 51650623.03 | 0.730529E+09 | 0.553990E+09 | 0.582754E+09 |
| July | 0.768202E+09 | 60229020.95 | 0.707973E+09 | 0.672183E+09 | 0.514141E+09 |
| August | 0.621865E+09 | 16810417.80 | 0.605055E+09 | 0.560915E+09 | 0.510348E+09 |
| September | 0.467460E+09 | 137843.24 | 0.467322E+09 | 0.264038E+09 | 0.775377E+09 |
| October | 0.330963E+09 | 0.00 | 0.330963E+09 | 73906801.00 | 0.109358E+10 |
| November | 0.201748E+09 | 0.00 | 0.201748E+09 | 7898008.49 | 0.126096E+10 |
| December | 0.156470E+09 | 0.00 | 0.156470E+09 | 572475.20 | 0.147905E+10 |
| Annual Sum or Average | 0.554077E+10 | 0.153715E+09 | 0.538705E+10 | 0.300208E+10 | 0.116781E+11 |
| Minimum of Months | 0.156470E+09 | 0.00 | 0.156470E+09 | 572475.20 | 0.510348E+09 |
| Maximum of Months | 0.782180E+09 | 60229020.95 | 0.745848E+09 | 0.672183E+09 | 0.147905E+10 |
Report: WindowEnergyReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 9032875.85 | 0.00 | 9032875.85 | 0.00 | 99215988.25 |
| February | 12896743.23 | 0.00 | 12896743.23 | 693746.77 | 82970801.51 |
| March | 21223709.20 | 654.15 | 21223055.05 | 2211235.48 | 81667763.85 |
| April | 42136164.10 | 10168161.89 | 31968002.22 | 21833090.85 | 59236466.60 |
| May | 63037968.09 | 19949772.43 | 43088195.66 | 50776798.10 | 52614049.66 |
| June | 80972927.42 | 35830608.38 | 45142319.05 | 79521053.78 | 39677683.57 |
| July | 75236695.24 | 32555778.88 | 42680916.35 | 79432613.53 | 33642935.88 |
| August | 62510940.59 | 26541673.13 | 35969267.46 | 67179451.61 | 32150322.50 |
| September | 27797430.15 | 3183922.67 | 24613507.49 | 14204297.03 | 50440152.55 |
| October | 16708677.18 | 0.00 | 16708677.18 | 1860262.20 | 76065079.46 |
| November | 9924739.01 | 0.00 | 9924739.01 | 151454.39 | 88959312.99 |
| December | 7700175.18 | 0.00 | 7700175.18 | 0.00 | 0.102340E+09 |
| Annual Sum or Average | 0.429179E+09 | 0.128231E+09 | 0.300948E+09 | 0.317864E+09 | 0.798981E+09 |
| Minimum of Months | 7700175.18 | 0.00 | 7700175.18 | 0.00 | 32150322.50 |
| Maximum of Months | 80972927.42 | 35830608.38 | 45142319.05 | 79521053.78 | 0.102340E+09 |
Report: WindowEnergyReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.266240E+09 | 54783683.49 | 0.211456E+09 | 50496403.28 | 0.141218E+10 |
| February | 0.467782E+09 | 0.157847E+09 | 0.309934E+09 | 0.242083E+09 | 0.114004E+10 |
| March | 0.817168E+09 | 0.299032E+09 | 0.518136E+09 | 0.578089E+09 | 0.112389E+10 |
| April | 0.123715E+10 | 0.523820E+09 | 0.713326E+09 | 0.112780E+10 | 0.887917E+09 |
| May | 0.135741E+10 | 0.481937E+09 | 0.875476E+09 | 0.130322E+10 | 0.796594E+09 |
| June | 0.157727E+10 | 0.699015E+09 | 0.878254E+09 | 0.167338E+10 | 0.609711E+09 |
| July | 0.151852E+10 | 0.693900E+09 | 0.824622E+09 | 0.172291E+10 | 0.527653E+09 |
| August | 0.149552E+10 | 0.760105E+09 | 0.735419E+09 | 0.177959E+10 | 0.510751E+09 |
| September | 0.106561E+10 | 0.499975E+09 | 0.565637E+09 | 0.107022E+10 | 0.754858E+09 |
| October | 0.693216E+09 | 0.291057E+09 | 0.402159E+09 | 0.525073E+09 | 0.106983E+10 |
| November | 0.311454E+09 | 78239700.91 | 0.233215E+09 | 0.103769E+09 | 0.125697E+10 |
| December | 0.238918E+09 | 59237846.79 | 0.179680E+09 | 59488176.97 | 0.147992E+10 |
| Annual Sum or Average | 0.110463E+11 | 0.459895E+10 | 0.644731E+10 | 0.102361E+11 | 0.115703E+11 |
| Minimum of Months | 0.238918E+09 | 54783683.49 | 0.179680E+09 | 50496403.28 | 0.510751E+09 |
| Maximum of Months | 0.157727E+10 | 0.760105E+09 | 0.878254E+09 | 0.177959E+10 | 0.147992E+10 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 156.30 | 469.65 | 231.06 | 120.70 | 110.35 | 0.00 | 0.00 |
| February | 314.69 | 421.64 | 369.41 | 204.60 | 164.81 | 0.00 | 0.00 |
| March | 393.04 | 376.52 | 429.60 | 201.95 | 227.64 | 0.00 | 0.00 |
| April | 521.59 | 321.63 | 518.13 | 214.03 | 304.10 | 0.00 | 0.00 |
| May | 579.09 | 278.00 | 552.33 | 193.95 | 358.38 | 0.00 | 0.00 |
| June | 560.11 | 218.91 | 518.04 | 170.36 | 347.68 | 0.00 | 0.00 |
| July | 743.78 | 188.70 | 602.76 | 272.17 | 330.58 | 0.00 | 0.00 |
| August | 725.85 | 185.27 | 567.88 | 276.63 | 291.24 | 0.00 | 0.00 |
| September | 631.63 | 279.93 | 550.85 | 288.46 | 262.38 | 0.00 | 0.00 |
| October | 420.18 | 364.92 | 425.85 | 236.96 | 188.89 | 0.00 | 0.00 |
| November | 178.46 | 417.11 | 240.25 | 119.75 | 120.49 | 0.00 | 0.00 |
| December | 187.99 | 489.85 | 238.70 | 138.71 | 100.00 | 0.00 | 0.00 |
| Annual Sum or Average | 451.94 | 333.90 | 437.41 | 203.23 | 234.18 | 0.00 | 0.00 |
| Minimum of Months | 156.30 | 185.27 | 231.06 | 119.75 | 100.00 | 0.00 | 0.00 |
| Maximum of Months | 743.78 | 489.85 | 602.76 | 288.46 | 358.38 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 700.23 | 1313.27 | 847.36 | 503.17 | 344.20 | 0.00 | 0.00 |
| February | 1251.22 | 1200.55 | 1303.11 | 806.65 | 496.47 | 0.00 | 0.00 |
| March | 1401.15 | 1104.00 | 1401.77 | 747.55 | 654.22 | 0.00 | 0.00 |
| April | 1565.15 | 946.98 | 1480.01 | 642.61 | 837.40 | 0.00 | 0.00 |
| May | 1437.76 | 806.29 | 1353.28 | 403.15 | 950.12 | 0.00 | 0.00 |
| June | 1355.77 | 629.17 | 1238.12 | 332.42 | 905.70 | 0.00 | 0.00 |
| July | 1718.67 | 516.04 | 1350.22 | 494.52 | 855.70 | 0.00 | 0.00 |
| August | 1919.98 | 504.69 | 1450.64 | 676.46 | 774.18 | 0.00 | 0.00 |
| September | 1918.50 | 784.39 | 1607.25 | 887.58 | 719.67 | 0.00 | 0.00 |
| October | 1556.50 | 1045.41 | 1455.90 | 898.91 | 556.99 | 0.00 | 0.00 |
| November | 751.39 | 1190.26 | 860.77 | 493.30 | 367.48 | 0.00 | 0.00 |
| December | 831.34 | 1390.92 | 900.62 | 582.82 | 317.79 | 0.00 | 0.00 |
| Annual Sum or Average | 1367.93 | 951.34 | 1270.21 | 621.28 | 648.93 | 0.00 | 0.00 |
| Minimum of Months | 700.23 | 504.69 | 847.36 | 332.42 | 317.79 | 0.00 | 0.00 |
| Maximum of Months | 1919.98 | 1390.92 | 1607.25 | 898.91 | 950.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 6.35 | 82.79 | 18.40 | 5.43 | 12.97 | 0.00 | 0.00 |
| February | 20.48 | 73.50 | 32.99 | 12.40 | 20.59 | 0.00 | 0.00 |
| March | 34.22 | 63.19 | 46.22 | 15.60 | 30.62 | 0.00 | 0.00 |
| April | 64.92 | 53.03 | 70.32 | 26.89 | 43.44 | 0.00 | 0.00 |
| May | 93.10 | 45.33 | 90.49 | 36.76 | 53.73 | 0.00 | 0.00 |
| June | 92.25 | 35.21 | 87.03 | 33.79 | 53.24 | 0.00 | 0.00 |
| July | 131.82 | 28.59 | 107.51 | 56.51 | 51.00 | 0.00 | 0.00 |
| August | 111.39 | 27.79 | 88.94 | 45.41 | 43.52 | 0.00 | 0.00 |
| September | 79.38 | 43.60 | 72.42 | 34.75 | 37.67 | 0.00 | 0.00 |
| October | 33.35 | 60.33 | 41.23 | 16.80 | 24.43 | 0.00 | 0.00 |
| November | 9.06 | 71.28 | 20.53 | 5.79 | 14.74 | 0.00 | 0.00 |
| December | 8.07 | 85.01 | 17.26 | 5.92 | 11.35 | 0.00 | 0.00 |
| Annual Sum or Average | 57.29 | 55.71 | 57.93 | 24.76 | 33.17 | 0.00 | 0.00 |
| Minimum of Months | 6.35 | 27.79 | 17.26 | 5.43 | 11.35 | 0.00 | 0.00 |
| Maximum of Months | 131.82 | 85.01 | 107.51 | 56.51 | 53.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 12.93 | 494.71 | 89.26 | 16.28 | 72.98 | 0.00 | 0.00 |
| February | 61.12 | 433.94 | 151.39 | 37.19 | 114.20 | 0.00 | 0.00 |
| March | 123.74 | 361.17 | 215.69 | 46.80 | 168.88 | 0.00 | 0.00 |
| April | 253.54 | 298.74 | 318.96 | 81.03 | 237.93 | 0.00 | 0.00 |
| May | 377.13 | 257.53 | 412.02 | 114.69 | 297.33 | 0.00 | 0.00 |
| June | 393.91 | 199.05 | 407.74 | 111.80 | 295.94 | 0.00 | 0.00 |
| July | 539.70 | 167.03 | 463.00 | 181.49 | 281.51 | 0.00 | 0.00 |
| August | 458.69 | 160.43 | 379.58 | 139.33 | 240.25 | 0.00 | 0.00 |
| September | 293.83 | 256.36 | 304.11 | 104.27 | 199.83 | 0.00 | 0.00 |
| October | 115.08 | 345.41 | 183.55 | 50.40 | 133.15 | 0.00 | 0.00 |
| November | 25.62 | 421.81 | 100.19 | 17.37 | 82.81 | 0.00 | 0.00 |
| December | 17.20 | 502.23 | 80.34 | 17.75 | 62.59 | 0.00 | 0.00 |
| Annual Sum or Average | 223.83 | 324.31 | 259.44 | 76.83 | 182.60 | 0.00 | 0.00 |
| Minimum of Months | 12.93 | 160.43 | 80.34 | 16.28 | 62.59 | 0.00 | 0.00 |
| Maximum of Months | 539.70 | 502.23 | 463.00 | 181.49 | 297.33 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.23 | 1456.84 | 154.36 | 0.00 | 154.36 | 0.00 | 0.00 |
| February | 20.90 | 1319.15 | 236.85 | 0.00 | 236.85 | 0.00 | 0.00 |
| March | 61.14 | 1093.17 | 347.69 | 0.00 | 347.69 | 0.00 | 0.00 |
| April | 197.23 | 882.12 | 484.90 | 1.26 | 483.64 | 0.00 | 0.00 |
| May | 373.59 | 729.24 | 629.67 | 17.07 | 612.59 | 0.00 | 0.00 |
| June | 465.92 | 550.35 | 650.26 | 41.02 | 609.25 | 0.00 | 0.00 |
| July | 626.05 | 431.53 | 621.20 | 44.78 | 576.42 | 0.00 | 0.00 |
| August | 546.37 | 407.79 | 504.64 | 11.64 | 493.00 | 0.00 | 0.00 |
| September | 218.48 | 710.87 | 390.13 | 0.07 | 390.06 | 0.00 | 0.00 |
| October | 44.91 | 1021.26 | 269.42 | 0.00 | 269.42 | 0.00 | 0.00 |
| November | 4.98 | 1261.61 | 174.94 | 0.00 | 174.94 | 0.00 | 0.00 |
| December | 0.19 | 1491.04 | 128.78 | 0.00 | 128.78 | 0.00 | 0.00 |
| Annual Sum or Average | 214.82 | 944.23 | 383.47 | 9.72 | 373.75 | 0.00 | 0.00 |
| Minimum of Months | 0.19 | 407.79 | 128.78 | 0.00 | 128.78 | 0.00 | 0.00 |
| Maximum of Months | 626.05 | 1491.04 | 650.26 | 44.78 | 612.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 149.89 | 471.67 | 219.07 | 116.64 | 102.44 | 0.00 | 0.00 |
| February | 305.24 | 419.87 | 358.24 | 203.96 | 154.27 | 0.00 | 0.00 |
| March | 377.85 | 374.01 | 414.36 | 201.81 | 212.55 | 0.00 | 0.00 |
| April | 497.54 | 318.89 | 496.04 | 214.03 | 282.01 | 0.00 | 0.00 |
| May | 549.63 | 275.37 | 526.26 | 193.95 | 332.30 | 0.00 | 0.00 |
| June | 528.96 | 216.28 | 490.28 | 170.36 | 319.92 | 0.00 | 0.00 |
| July | 716.28 | 184.93 | 577.52 | 272.17 | 305.35 | 0.00 | 0.00 |
| August | 701.82 | 181.14 | 545.96 | 276.63 | 269.33 | 0.00 | 0.00 |
| September | 610.97 | 275.59 | 532.25 | 288.44 | 243.81 | 0.00 | 0.00 |
| October | 407.57 | 362.05 | 412.94 | 236.61 | 176.34 | 0.00 | 0.00 |
| November | 172.31 | 416.94 | 230.71 | 118.11 | 112.59 | 0.00 | 0.00 |
| December | 175.84 | 493.27 | 219.70 | 128.83 | 90.86 | 0.00 | 0.00 |
| Annual Sum or Average | 433.66 | 332.06 | 418.90 | 201.82 | 217.08 | 0.00 | 0.00 |
| Minimum of Months | 149.89 | 181.14 | 219.07 | 116.64 | 90.86 | 0.00 | 0.00 |
| Maximum of Months | 716.28 | 493.27 | 577.52 | 288.44 | 332.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 623.67 | 1336.51 | 743.70 | 457.10 | 286.60 | 0.00 | 0.00 |
| February | 1159.06 | 1198.07 | 1207.29 | 782.47 | 424.82 | 0.00 | 0.00 |
| March | 1284.65 | 1098.39 | 1290.44 | 733.32 | 557.12 | 0.00 | 0.00 |
| April | 1402.69 | 940.85 | 1335.47 | 635.40 | 700.07 | 0.00 | 0.00 |
| May | 1251.93 | 803.35 | 1189.85 | 400.19 | 789.66 | 0.00 | 0.00 |
| June | 1161.28 | 624.26 | 1066.17 | 330.07 | 736.10 | 0.00 | 0.00 |
| July | 1540.71 | 500.35 | 1192.90 | 491.18 | 701.73 | 0.00 | 0.00 |
| August | 1759.37 | 483.11 | 1309.56 | 670.11 | 639.46 | 0.00 | 0.00 |
| September | 1769.63 | 762.61 | 1479.22 | 875.65 | 603.57 | 0.00 | 0.00 |
| October | 1442.64 | 1036.77 | 1348.47 | 874.29 | 474.18 | 0.00 | 0.00 |
| November | 683.83 | 1197.78 | 778.47 | 467.05 | 311.42 | 0.00 | 0.00 |
| December | 700.45 | 1421.61 | 745.75 | 493.41 | 252.35 | 0.00 | 0.00 |
| Annual Sum or Average | 1232.01 | 949.02 | 1139.79 | 599.62 | 540.17 | 0.00 | 0.00 |
| Minimum of Months | 623.67 | 483.11 | 743.70 | 330.07 | 252.35 | 0.00 | 0.00 |
| Maximum of Months | 1769.63 | 1421.61 | 1479.22 | 875.65 | 789.66 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 6.37 | 82.67 | 18.40 | 5.43 | 12.97 | 0.00 | 0.00 |
| February | 20.50 | 73.48 | 32.99 | 12.40 | 20.59 | 0.00 | 0.00 |
| March | 34.25 | 63.16 | 46.22 | 15.60 | 30.62 | 0.00 | 0.00 |
| April | 64.96 | 52.98 | 70.32 | 26.89 | 43.44 | 0.00 | 0.00 |
| May | 93.14 | 45.29 | 90.49 | 36.76 | 53.73 | 0.00 | 0.00 |
| June | 92.31 | 35.15 | 87.03 | 33.79 | 53.24 | 0.00 | 0.00 |
| July | 131.96 | 28.47 | 107.51 | 56.51 | 51.00 | 0.00 | 0.00 |
| August | 111.49 | 27.69 | 88.94 | 45.41 | 43.52 | 0.00 | 0.00 |
| September | 79.43 | 43.53 | 72.42 | 34.75 | 37.67 | 0.00 | 0.00 |
| October | 33.38 | 60.29 | 41.23 | 16.80 | 24.43 | 0.00 | 0.00 |
| November | 9.07 | 71.21 | 20.53 | 5.79 | 14.74 | 0.00 | 0.00 |
| December | 8.12 | 84.73 | 17.26 | 5.92 | 11.35 | 0.00 | 0.00 |
| Annual Sum or Average | 57.33 | 55.63 | 57.93 | 24.76 | 33.17 | 0.00 | 0.00 |
| Minimum of Months | 6.37 | 27.69 | 17.26 | 5.43 | 11.35 | 0.00 | 0.00 |
| Maximum of Months | 131.96 | 84.73 | 107.51 | 56.51 | 53.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 13.04 | 494.57 | 89.67 | 16.28 | 73.40 | 0.00 | 0.00 |
| February | 61.52 | 433.87 | 152.08 | 37.19 | 114.89 | 0.00 | 0.00 |
| March | 124.68 | 361.20 | 216.72 | 46.80 | 169.91 | 0.00 | 0.00 |
| April | 255.15 | 298.76 | 320.50 | 81.04 | 239.46 | 0.00 | 0.00 |
| May | 379.15 | 257.52 | 413.89 | 114.74 | 299.15 | 0.00 | 0.00 |
| June | 396.12 | 198.93 | 409.83 | 111.92 | 297.91 | 0.00 | 0.00 |
| July | 541.77 | 166.89 | 464.87 | 181.58 | 283.29 | 0.00 | 0.00 |
| August | 460.46 | 160.42 | 381.16 | 139.37 | 241.78 | 0.00 | 0.00 |
| September | 295.25 | 256.49 | 305.38 | 104.27 | 201.10 | 0.00 | 0.00 |
| October | 115.83 | 345.47 | 184.40 | 50.40 | 134.00 | 0.00 | 0.00 |
| November | 25.82 | 421.67 | 100.66 | 17.37 | 83.28 | 0.00 | 0.00 |
| December | 17.35 | 501.89 | 80.72 | 17.75 | 62.97 | 0.00 | 0.00 |
| Annual Sum or Average | 224.97 | 324.25 | 260.61 | 76.86 | 183.75 | 0.00 | 0.00 |
| Minimum of Months | 13.04 | 160.42 | 80.72 | 16.28 | 62.97 | 0.00 | 0.00 |
| Maximum of Months | 541.77 | 501.89 | 464.87 | 181.58 | 299.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.28 | 1455.98 | 156.40 | 0.00 | 156.40 | 0.00 | 0.00 |
| February | 21.76 | 1317.88 | 240.22 | 0.00 | 240.22 | 0.00 | 0.00 |
| March | 64.47 | 1092.17 | 352.73 | 0.00 | 352.73 | 0.00 | 0.00 |
| April | 204.24 | 881.43 | 492.46 | 1.32 | 491.15 | 0.00 | 0.00 |
| May | 383.74 | 728.66 | 639.35 | 17.60 | 621.76 | 0.00 | 0.00 |
| June | 477.33 | 549.51 | 661.18 | 42.02 | 619.15 | 0.00 | 0.00 |
| July | 637.71 | 431.06 | 631.62 | 46.14 | 585.49 | 0.00 | 0.00 |
| August | 555.24 | 408.15 | 512.59 | 12.00 | 500.59 | 0.00 | 0.00 |
| September | 224.89 | 711.38 | 396.35 | 0.07 | 396.28 | 0.00 | 0.00 |
| October | 47.45 | 1020.72 | 273.56 | 0.00 | 273.56 | 0.00 | 0.00 |
| November | 5.34 | 1260.65 | 177.24 | 0.00 | 177.24 | 0.00 | 0.00 |
| December | 0.21 | 1489.62 | 130.64 | 0.00 | 130.64 | 0.00 | 0.00 |
| Annual Sum or Average | 220.07 | 943.58 | 389.44 | 10.00 | 379.44 | 0.00 | 0.00 |
| Minimum of Months | 0.21 | 408.15 | 130.64 | 0.00 | 130.64 | 0.00 | 0.00 |
| Maximum of Months | 637.71 | 1489.62 | 661.18 | 46.14 | 621.76 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 151.39 | 471.54 | 221.54 | 118.08 | 103.46 | 0.00 | 0.00 |
| February | 305.61 | 420.55 | 359.28 | 204.13 | 155.15 | 0.00 | 0.00 |
| March | 378.33 | 375.92 | 415.54 | 201.84 | 213.70 | 0.00 | 0.00 |
| April | 498.43 | 320.84 | 497.73 | 214.03 | 283.70 | 0.00 | 0.00 |
| May | 551.22 | 276.64 | 528.25 | 193.95 | 334.29 | 0.00 | 0.00 |
| June | 530.58 | 217.47 | 492.40 | 170.36 | 322.04 | 0.00 | 0.00 |
| July | 717.06 | 186.69 | 579.44 | 272.17 | 307.27 | 0.00 | 0.00 |
| August | 702.69 | 182.68 | 547.63 | 276.63 | 271.00 | 0.00 | 0.00 |
| September | 611.86 | 277.21 | 533.67 | 288.44 | 245.23 | 0.00 | 0.00 |
| October | 407.95 | 364.00 | 414.06 | 236.72 | 177.34 | 0.00 | 0.00 |
| November | 172.50 | 418.60 | 231.92 | 118.54 | 113.39 | 0.00 | 0.00 |
| December | 180.10 | 493.73 | 224.39 | 132.09 | 92.30 | 0.00 | 0.00 |
| Annual Sum or Average | 434.82 | 333.39 | 420.79 | 202.28 | 218.51 | 0.00 | 0.00 |
| Minimum of Months | 151.39 | 182.68 | 221.54 | 118.08 | 92.30 | 0.00 | 0.00 |
| Maximum of Months | 717.06 | 493.73 | 579.44 | 288.44 | 334.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 634.78 | 1333.91 | 758.76 | 466.54 | 292.22 | 0.00 | 0.00 |
| February | 1161.20 | 1199.78 | 1213.12 | 783.91 | 429.21 | 0.00 | 0.00 |
| March | 1287.30 | 1106.81 | 1295.79 | 733.56 | 562.23 | 0.00 | 0.00 |
| April | 1407.42 | 948.54 | 1342.88 | 635.40 | 707.48 | 0.00 | 0.00 |
| May | 1259.48 | 807.71 | 1198.59 | 400.20 | 798.40 | 0.00 | 0.00 |
| June | 1168.59 | 628.86 | 1075.47 | 330.07 | 745.40 | 0.00 | 0.00 |
| July | 1545.60 | 506.90 | 1201.36 | 491.18 | 710.18 | 0.00 | 0.00 |
| August | 1763.51 | 489.46 | 1316.91 | 670.11 | 646.80 | 0.00 | 0.00 |
| September | 1774.04 | 769.25 | 1485.53 | 875.71 | 609.82 | 0.00 | 0.00 |
| October | 1445.69 | 1044.94 | 1354.27 | 875.48 | 478.78 | 0.00 | 0.00 |
| November | 687.20 | 1204.33 | 786.52 | 470.65 | 315.87 | 0.00 | 0.00 |
| December | 723.56 | 1420.75 | 770.74 | 511.20 | 259.54 | 0.00 | 0.00 |
| Annual Sum or Average | 1238.60 | 953.83 | 1149.23 | 602.47 | 546.76 | 0.00 | 0.00 |
| Minimum of Months | 634.78 | 489.46 | 758.76 | 330.07 | 259.54 | 0.00 | 0.00 |
| Maximum of Months | 1774.04 | 1420.75 | 1485.53 | 875.71 | 798.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 6.34 | 83.07 | 18.40 | 5.43 | 12.97 | 0.00 | 0.00 |
| February | 20.37 | 74.03 | 32.99 | 12.40 | 20.59 | 0.00 | 0.00 |
| March | 33.92 | 64.19 | 46.22 | 15.60 | 30.62 | 0.00 | 0.00 |
| April | 64.45 | 53.95 | 70.32 | 26.89 | 43.44 | 0.00 | 0.00 |
| May | 92.77 | 45.90 | 90.49 | 36.76 | 53.73 | 0.00 | 0.00 |
| June | 91.86 | 35.73 | 87.03 | 33.79 | 53.24 | 0.00 | 0.00 |
| July | 131.21 | 29.22 | 107.51 | 56.51 | 51.00 | 0.00 | 0.00 |
| August | 110.89 | 28.38 | 88.94 | 45.41 | 43.52 | 0.00 | 0.00 |
| September | 79.06 | 44.28 | 72.42 | 34.75 | 37.67 | 0.00 | 0.00 |
| October | 33.12 | 61.35 | 41.23 | 16.80 | 24.43 | 0.00 | 0.00 |
| November | 8.94 | 72.28 | 20.53 | 5.79 | 14.74 | 0.00 | 0.00 |
| December | 8.06 | 85.33 | 17.26 | 5.92 | 11.35 | 0.00 | 0.00 |
| Annual Sum or Average | 57.00 | 56.39 | 57.93 | 24.76 | 33.17 | 0.00 | 0.00 |
| Minimum of Months | 6.34 | 28.38 | 17.26 | 5.43 | 11.35 | 0.00 | 0.00 |
| Maximum of Months | 131.21 | 85.33 | 107.51 | 56.51 | 53.73 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 14.40 | 494.02 | 94.86 | 16.28 | 78.58 | 0.00 | 0.00 |
| February | 66.59 | 433.51 | 160.68 | 37.19 | 123.49 | 0.00 | 0.00 |
| March | 136.16 | 363.34 | 229.60 | 46.80 | 182.80 | 0.00 | 0.00 |
| April | 274.26 | 301.58 | 339.65 | 81.12 | 258.53 | 0.00 | 0.00 |
| May | 403.66 | 259.46 | 437.05 | 115.20 | 321.85 | 0.00 | 0.00 |
| June | 422.46 | 200.50 | 435.18 | 112.87 | 322.32 | 0.00 | 0.00 |
| July | 564.31 | 169.45 | 488.00 | 182.51 | 305.49 | 0.00 | 0.00 |
| August | 479.87 | 163.73 | 400.76 | 139.86 | 260.90 | 0.00 | 0.00 |
| September | 311.61 | 260.83 | 321.32 | 104.28 | 217.04 | 0.00 | 0.00 |
| October | 124.88 | 348.49 | 194.99 | 50.40 | 144.59 | 0.00 | 0.00 |
| November | 28.20 | 422.63 | 106.51 | 17.37 | 89.13 | 0.00 | 0.00 |
| December | 18.74 | 502.63 | 85.49 | 17.75 | 67.75 | 0.00 | 0.00 |
| Annual Sum or Average | 238.25 | 326.13 | 275.16 | 77.11 | 198.05 | 0.00 | 0.00 |
| Minimum of Months | 14.40 | 163.73 | 85.49 | 16.28 | 67.75 | 0.00 | 0.00 |
| Maximum of Months | 564.31 | 502.63 | 488.00 | 182.51 | 322.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.47 | 957.83 | 126.65 | 0.00 | 126.65 | 0.00 | 0.00 |
| February | 25.99 | 859.87 | 197.07 | 0.00 | 197.07 | 0.00 | 0.00 |
| March | 85.27 | 719.73 | 290.35 | 0.00 | 290.35 | 0.00 | 0.00 |
| April | 216.58 | 583.01 | 410.87 | 1.46 | 409.42 | 0.00 | 0.00 |
| May | 366.84 | 481.20 | 528.69 | 15.71 | 512.98 | 0.00 | 0.00 |
| June | 445.10 | 365.26 | 555.91 | 36.71 | 519.20 | 0.00 | 0.00 |
| July | 542.16 | 292.15 | 528.36 | 41.43 | 486.93 | 0.00 | 0.00 |
| August | 461.25 | 280.14 | 427.71 | 11.56 | 416.15 | 0.00 | 0.00 |
| September | 220.12 | 483.49 | 332.23 | 0.10 | 332.13 | 0.00 | 0.00 |
| October | 64.48 | 677.95 | 227.63 | 0.00 | 227.63 | 0.00 | 0.00 |
| November | 8.54 | 831.65 | 143.39 | 0.00 | 143.39 | 0.00 | 0.00 |
| December | 0.63 | 984.35 | 107.62 | 0.00 | 107.62 | 0.00 | 0.00 |
| Annual Sum or Average | 204.45 | 625.13 | 323.66 | 8.98 | 314.68 | 0.00 | 0.00 |
| Minimum of Months | 0.63 | 280.14 | 107.62 | 0.00 | 107.62 | 0.00 | 0.00 |
| Maximum of Months | 542.16 | 984.35 | 555.91 | 41.43 | 519.20 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.44 | 512.39 | 65.13 | 0.00 | 65.13 | 0.00 | 0.00 |
| February | 11.61 | 466.83 | 101.35 | 0.00 | 101.35 | 0.00 | 0.00 |
| March | 37.44 | 402.21 | 149.32 | 0.00 | 149.32 | 0.00 | 0.00 |
| April | 101.83 | 326.52 | 211.30 | 0.75 | 210.56 | 0.00 | 0.00 |
| May | 179.98 | 265.77 | 271.90 | 8.08 | 263.82 | 0.00 | 0.00 |
| June | 217.22 | 202.68 | 285.89 | 18.88 | 267.01 | 0.00 | 0.00 |
| July | 261.32 | 165.40 | 271.72 | 21.30 | 250.42 | 0.00 | 0.00 |
| August | 220.08 | 161.20 | 219.96 | 5.95 | 214.02 | 0.00 | 0.00 |
| September | 103.95 | 272.17 | 170.86 | 0.05 | 170.81 | 0.00 | 0.00 |
| October | 28.42 | 380.20 | 117.07 | 0.00 | 117.07 | 0.00 | 0.00 |
| November | 3.11 | 461.07 | 73.74 | 0.00 | 73.74 | 0.00 | 0.00 |
| December | 0.19 | 532.11 | 55.35 | 0.00 | 55.35 | 0.00 | 0.00 |
| Annual Sum or Average | 97.73 | 345.05 | 166.45 | 4.62 | 161.84 | 0.00 | 0.00 |
| Minimum of Months | 0.19 | 161.20 | 55.35 | 0.00 | 55.35 | 0.00 | 0.00 |
| Maximum of Months | 261.32 | 532.11 | 285.89 | 21.30 | 267.01 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.28 | 253.97 | 28.10 | 2.59 | 25.51 | 0.00 | 0.00 |
| February | 19.72 | 223.96 | 56.61 | 14.57 | 42.04 | 0.00 | 0.00 |
| March | 58.89 | 193.38 | 97.89 | 30.49 | 67.40 | 0.00 | 0.00 |
| April | 145.17 | 166.32 | 168.25 | 68.43 | 99.83 | 0.00 | 0.00 |
| May | 221.67 | 144.85 | 223.48 | 98.05 | 125.43 | 0.00 | 0.00 |
| June | 218.47 | 113.61 | 213.22 | 89.33 | 123.89 | 0.00 | 0.00 |
| July | 319.98 | 95.68 | 267.37 | 147.47 | 119.90 | 0.00 | 0.00 |
| August | 267.87 | 89.77 | 218.84 | 117.56 | 101.28 | 0.00 | 0.00 |
| September | 170.18 | 132.39 | 164.45 | 79.29 | 85.16 | 0.00 | 0.00 |
| October | 45.83 | 183.13 | 75.84 | 24.96 | 50.89 | 0.00 | 0.00 |
| November | 4.84 | 217.43 | 34.00 | 4.45 | 29.55 | 0.00 | 0.00 |
| December | 0.53 | 257.57 | 23.10 | 1.81 | 21.29 | 0.00 | 0.00 |
| Annual Sum or Average | 123.50 | 172.42 | 131.39 | 56.89 | 74.50 | 0.00 | 0.00 |
| Minimum of Months | 0.28 | 89.77 | 23.10 | 1.81 | 21.29 | 0.00 | 0.00 |
| Maximum of Months | 319.98 | 257.57 | 267.37 | 147.47 | 125.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 265.25 | 417.54 | 303.77 | 180.38 | 123.39 | 0.00 | 0.00 |
| February | 470.25 | 381.97 | 467.16 | 289.18 | 177.98 | 0.00 | 0.00 |
| March | 526.84 | 350.08 | 502.53 | 267.99 | 234.53 | 0.00 | 0.00 |
| April | 586.61 | 303.52 | 530.57 | 230.37 | 300.20 | 0.00 | 0.00 |
| May | 537.54 | 264.24 | 485.14 | 144.53 | 340.61 | 0.00 | 0.00 |
| June | 501.08 | 212.45 | 443.86 | 119.17 | 324.69 | 0.00 | 0.00 |
| July | 612.10 | 188.07 | 484.04 | 177.28 | 306.76 | 0.00 | 0.00 |
| August | 684.08 | 183.35 | 520.04 | 242.50 | 277.54 | 0.00 | 0.00 |
| September | 701.05 | 260.46 | 576.19 | 318.19 | 258.00 | 0.00 | 0.00 |
| October | 578.22 | 331.48 | 521.93 | 322.25 | 199.68 | 0.00 | 0.00 |
| November | 285.16 | 373.32 | 308.58 | 176.84 | 131.74 | 0.00 | 0.00 |
| December | 312.58 | 437.56 | 322.86 | 208.94 | 113.93 | 0.00 | 0.00 |
| Annual Sum or Average | 505.20 | 308.30 | 455.36 | 222.72 | 232.63 | 0.00 | 0.00 |
| Minimum of Months | 265.25 | 183.35 | 303.77 | 119.17 | 113.93 | 0.00 | 0.00 |
| Maximum of Months | 701.05 | 437.56 | 576.19 | 322.25 | 340.61 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 3.16 | 256.94 | 35.04 | 5.07 | 29.97 | 0.00 | 0.00 |
| February | 32.30 | 233.11 | 71.16 | 21.69 | 49.47 | 0.00 | 0.00 |
| March | 75.09 | 210.80 | 116.51 | 38.28 | 78.23 | 0.00 | 0.00 |
| April | 168.31 | 183.40 | 193.15 | 78.91 | 114.24 | 0.00 | 0.00 |
| May | 247.51 | 164.62 | 253.61 | 110.74 | 142.88 | 0.00 | 0.00 |
| June | 238.73 | 133.83 | 241.34 | 100.42 | 140.92 | 0.00 | 0.00 |
| July | 355.56 | 112.69 | 302.33 | 166.10 | 136.22 | 0.00 | 0.00 |
| August | 299.71 | 106.30 | 249.39 | 133.94 | 115.46 | 0.00 | 0.00 |
| September | 198.11 | 153.20 | 192.88 | 94.67 | 98.21 | 0.00 | 0.00 |
| October | 62.14 | 202.36 | 93.67 | 33.94 | 59.73 | 0.00 | 0.00 |
| November | 9.42 | 236.02 | 42.35 | 7.59 | 34.76 | 0.00 | 0.00 |
| December | 2.83 | 267.78 | 28.87 | 3.85 | 25.02 | 0.00 | 0.00 |
| Annual Sum or Average | 141.83 | 188.18 | 152.18 | 66.59 | 85.59 | 0.00 | 0.00 |
| Minimum of Months | 2.83 | 106.30 | 28.87 | 3.85 | 25.02 | 0.00 | 0.00 |
| Maximum of Months | 355.56 | 267.78 | 302.33 | 166.10 | 142.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 289.88 | 1031.17 | 457.84 | 230.32 | 227.52 | 0.00 | 0.00 |
| February | 603.98 | 937.15 | 740.37 | 399.13 | 341.24 | 0.00 | 0.00 |
| March | 784.06 | 865.20 | 889.93 | 417.29 | 472.64 | 0.00 | 0.00 |
| April | 1071.05 | 731.87 | 1104.97 | 470.08 | 634.88 | 0.00 | 0.00 |
| May | 1076.93 | 636.45 | 1087.99 | 351.58 | 736.40 | 0.00 | 0.00 |
| June | 1206.07 | 504.70 | 1151.40 | 419.24 | 732.16 | 0.00 | 0.00 |
| July | 1332.04 | 435.01 | 1150.37 | 472.16 | 678.21 | 0.00 | 0.00 |
| August | 1433.31 | 418.70 | 1179.62 | 570.60 | 609.01 | 0.00 | 0.00 |
| September | 1187.81 | 621.43 | 1084.02 | 557.92 | 526.09 | 0.00 | 0.00 |
| October | 832.59 | 824.28 | 868.33 | 480.02 | 388.32 | 0.00 | 0.00 |
| November | 341.01 | 940.59 | 483.92 | 235.79 | 248.14 | 0.00 | 0.00 |
| December | 354.26 | 1080.57 | 474.03 | 268.65 | 205.37 | 0.00 | 0.00 |
| Annual Sum or Average | 877.49 | 751.32 | 889.89 | 405.96 | 483.93 | 0.00 | 0.00 |
| Minimum of Months | 289.88 | 418.70 | 457.84 | 230.32 | 205.37 | 0.00 | 0.00 |
| Maximum of Months | 1433.31 | 1080.57 | 1179.62 | 570.60 | 736.40 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 61.23 | 1028.84 | 255.60 | 59.27 | 196.33 | 0.00 | 0.00 |
| February | 282.46 | 940.47 | 469.80 | 170.87 | 298.93 | 0.00 | 0.00 |
| March | 602.16 | 840.82 | 741.59 | 296.54 | 445.04 | 0.00 | 0.00 |
| April | 1174.92 | 702.13 | 1179.28 | 561.14 | 618.14 | 0.00 | 0.00 |
| May | 1549.29 | 601.28 | 1431.67 | 662.55 | 769.11 | 0.00 | 0.00 |
| June | 1828.22 | 482.82 | 1609.86 | 860.92 | 748.94 | 0.00 | 0.00 |
| July | 1948.58 | 433.71 | 1621.15 | 963.34 | 657.81 | 0.00 | 0.00 |
| August | 1685.87 | 423.13 | 1385.08 | 811.38 | 573.70 | 0.00 | 0.00 |
| September | 1070.72 | 596.94 | 994.15 | 516.35 | 477.80 | 0.00 | 0.00 |
| October | 504.71 | 789.93 | 601.51 | 265.68 | 335.83 | 0.00 | 0.00 |
| November | 128.52 | 916.84 | 299.99 | 78.82 | 221.17 | 0.00 | 0.00 |
| December | 62.65 | 1089.07 | 226.59 | 62.42 | 164.17 | 0.00 | 0.00 |
| Annual Sum or Average | 911.86 | 736.18 | 903.59 | 443.99 | 459.60 | 0.00 | 0.00 |
| Minimum of Months | 61.23 | 423.13 | 226.59 | 59.27 | 164.17 | 0.00 | 0.00 |
| Maximum of Months | 1948.58 | 1089.07 | 1621.15 | 963.34 | 769.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 8.66 | 311.80 | 46.51 | 11.79 | 34.72 | 0.00 | 0.00 |
| February | 37.92 | 273.07 | 85.35 | 30.29 | 55.06 | 0.00 | 0.00 |
| March | 81.62 | 222.82 | 127.43 | 46.13 | 81.30 | 0.00 | 0.00 |
| April | 169.90 | 170.48 | 197.54 | 82.08 | 115.46 | 0.00 | 0.00 |
| May | 195.49 | 141.68 | 210.20 | 73.08 | 137.12 | 0.00 | 0.00 |
| June | 262.16 | 110.85 | 251.74 | 109.53 | 142.21 | 0.00 | 0.00 |
| July | 259.27 | 96.59 | 234.43 | 105.22 | 129.20 | 0.00 | 0.00 |
| August | 268.58 | 93.30 | 230.41 | 115.26 | 115.15 | 0.00 | 0.00 |
| September | 166.75 | 137.84 | 170.35 | 78.57 | 91.79 | 0.00 | 0.00 |
| October | 80.82 | 198.57 | 111.04 | 47.18 | 63.86 | 0.00 | 0.00 |
| November | 18.12 | 259.46 | 54.42 | 15.36 | 39.06 | 0.00 | 0.00 |
| December | 12.91 | 316.50 | 44.64 | 14.37 | 30.27 | 0.00 | 0.00 |
| Annual Sum or Average | 130.68 | 194.04 | 147.28 | 60.87 | 86.40 | 0.00 | 0.00 |
| Minimum of Months | 8.66 | 93.30 | 44.64 | 11.79 | 30.27 | 0.00 | 0.00 |
| Maximum of Months | 268.58 | 316.50 | 251.74 | 115.26 | 142.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 7.99 | 1007.83 | 158.77 | 22.11 | 136.65 | 0.00 | 0.00 |
| February | 70.83 | 894.88 | 271.27 | 56.80 | 214.48 | 0.00 | 0.00 |
| March | 190.71 | 748.53 | 402.86 | 86.50 | 316.36 | 0.00 | 0.00 |
| April | 429.49 | 604.85 | 601.13 | 154.41 | 446.71 | 0.00 | 0.00 |
| May | 556.46 | 527.13 | 687.84 | 143.06 | 544.78 | 0.00 | 0.00 |
| June | 706.13 | 428.40 | 778.52 | 221.47 | 557.05 | 0.00 | 0.00 |
| July | 734.15 | 367.19 | 727.37 | 212.53 | 514.84 | 0.00 | 0.00 |
| August | 718.20 | 350.81 | 670.15 | 220.46 | 449.69 | 0.00 | 0.00 |
| September | 411.22 | 525.17 | 506.59 | 147.36 | 359.24 | 0.00 | 0.00 |
| October | 174.74 | 701.08 | 336.54 | 88.47 | 248.08 | 0.00 | 0.00 |
| November | 29.12 | 870.90 | 183.08 | 28.81 | 154.27 | 0.00 | 0.00 |
| December | 14.33 | 1041.04 | 144.36 | 26.95 | 117.41 | 0.00 | 0.00 |
| Annual Sum or Average | 338.51 | 671.20 | 456.55 | 117.68 | 338.86 | 0.00 | 0.00 |
| Minimum of Months | 7.99 | 350.81 | 144.36 | 22.11 | 117.41 | 0.00 | 0.00 |
| Maximum of Months | 734.15 | 1041.04 | 778.52 | 221.47 | 557.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 7.73 | 1084.67 | 171.52 | 20.45 | 151.07 | 0.00 | 0.00 |
| February | 87.52 | 969.69 | 305.67 | 65.25 | 240.42 | 0.00 | 0.00 |
| March | 230.66 | 859.30 | 470.63 | 111.65 | 358.99 | 0.00 | 0.00 |
| April | 525.31 | 701.73 | 716.59 | 206.81 | 509.78 | 0.00 | 0.00 |
| May | 677.08 | 599.71 | 817.33 | 195.91 | 621.42 | 0.00 | 0.00 |
| June | 884.76 | 470.12 | 941.52 | 303.43 | 638.09 | 0.00 | 0.00 |
| July | 917.18 | 394.82 | 881.86 | 293.71 | 588.14 | 0.00 | 0.00 |
| August | 892.27 | 386.59 | 813.88 | 299.98 | 513.91 | 0.00 | 0.00 |
| September | 505.14 | 594.73 | 602.19 | 194.17 | 408.01 | 0.00 | 0.00 |
| October | 205.51 | 817.30 | 388.62 | 108.67 | 279.95 | 0.00 | 0.00 |
| November | 29.38 | 991.98 | 201.82 | 30.19 | 171.64 | 0.00 | 0.00 |
| December | 11.82 | 1132.36 | 150.50 | 22.12 | 128.38 | 0.00 | 0.00 |
| Annual Sum or Average | 416.43 | 749.11 | 539.58 | 154.77 | 384.81 | 0.00 | 0.00 |
| Minimum of Months | 7.73 | 386.59 | 150.50 | 20.45 | 128.38 | 0.00 | 0.00 |
| Maximum of Months | 917.18 | 1132.36 | 941.52 | 303.43 | 638.09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.418621E+09 | 0.125791E+10 | 0.618868E+09 | 0.323295E+09 | 0.295573E+09 | 0.00 | 0.00 |
| February | 0.761309E+09 | 0.102003E+10 | 0.893681E+09 | 0.494980E+09 | 0.398701E+09 | 0.00 | 0.00 |
| March | 0.105273E+10 | 0.100846E+10 | 0.115063E+10 | 0.540910E+09 | 0.609721E+09 | 0.00 | 0.00 |
| April | 0.135196E+10 | 0.833663E+09 | 0.134300E+10 | 0.554768E+09 | 0.788237E+09 | 0.00 | 0.00 |
| May | 0.155103E+10 | 0.744591E+09 | 0.147937E+10 | 0.519489E+09 | 0.959877E+09 | 0.00 | 0.00 |
| June | 0.145180E+10 | 0.567426E+09 | 0.134276E+10 | 0.441571E+09 | 0.901192E+09 | 0.00 | 0.00 |
| July | 0.199214E+10 | 0.505407E+09 | 0.161442E+10 | 0.728983E+09 | 0.885438E+09 | 0.00 | 0.00 |
| August | 0.194411E+10 | 0.496235E+09 | 0.152100E+10 | 0.740934E+09 | 0.780069E+09 | 0.00 | 0.00 |
| September | 0.163718E+10 | 0.725586E+09 | 0.142779E+10 | 0.747694E+09 | 0.680100E+09 | 0.00 | 0.00 |
| October | 0.112541E+10 | 0.977414E+09 | 0.114061E+10 | 0.634676E+09 | 0.505933E+09 | 0.00 | 0.00 |
| November | 0.462577E+09 | 0.108114E+10 | 0.622718E+09 | 0.310400E+09 | 0.312318E+09 | 0.00 | 0.00 |
| December | 0.503515E+09 | 0.131201E+10 | 0.639339E+09 | 0.371511E+09 | 0.267828E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.142524E+11 | 0.105299E+11 | 0.137942E+11 | 0.640921E+10 | 0.738499E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.418621E+09 | 0.496235E+09 | 0.618868E+09 | 0.310400E+09 | 0.267828E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.199214E+10 | 0.131201E+10 | 0.161442E+10 | 0.747694E+09 | 0.959877E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.187550E+10 | 0.351745E+10 | 0.226958E+10 | 0.134768E+10 | 0.921892E+09 | 0.00 | 0.00 |
| February | 0.302696E+10 | 0.290436E+10 | 0.315249E+10 | 0.195144E+10 | 0.120106E+10 | 0.00 | 0.00 |
| March | 0.375284E+10 | 0.295695E+10 | 0.375451E+10 | 0.200224E+10 | 0.175227E+10 | 0.00 | 0.00 |
| April | 0.405688E+10 | 0.245457E+10 | 0.383618E+10 | 0.166565E+10 | 0.217053E+10 | 0.00 | 0.00 |
| May | 0.385091E+10 | 0.215956E+10 | 0.362462E+10 | 0.107981E+10 | 0.254481E+10 | 0.00 | 0.00 |
| June | 0.351415E+10 | 0.163082E+10 | 0.320920E+10 | 0.861629E+09 | 0.234757E+10 | 0.00 | 0.00 |
| July | 0.460329E+10 | 0.138217E+10 | 0.361643E+10 | 0.132453E+10 | 0.229190E+10 | 0.00 | 0.00 |
| August | 0.514248E+10 | 0.135177E+10 | 0.388540E+10 | 0.181183E+10 | 0.207357E+10 | 0.00 | 0.00 |
| September | 0.497276E+10 | 0.203314E+10 | 0.416599E+10 | 0.230060E+10 | 0.186539E+10 | 0.00 | 0.00 |
| October | 0.416892E+10 | 0.280003E+10 | 0.389947E+10 | 0.240764E+10 | 0.149184E+10 | 0.00 | 0.00 |
| November | 0.194761E+10 | 0.308515E+10 | 0.223113E+10 | 0.127862E+10 | 0.952504E+09 | 0.00 | 0.00 |
| December | 0.222665E+10 | 0.372544E+10 | 0.241221E+10 | 0.156104E+10 | 0.851174E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.431390E+11 | 0.300014E+11 | 0.400572E+11 | 0.195927E+11 | 0.204645E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.187550E+10 | 0.135177E+10 | 0.223113E+10 | 0.861629E+09 | 0.851174E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.514248E+10 | 0.372544E+10 | 0.416599E+10 | 0.240764E+10 | 0.254481E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 17017250.77 | 0.221741E+09 | 49278394.98 | 14531301.98 | 34747093.00 | 0.00 | 0.00 |
| February | 49555266.10 | 0.177813E+09 | 79802069.13 | 29991864.90 | 49810204.23 | 0.00 | 0.00 |
| March | 91661656.19 | 0.169255E+09 | 0.123804E+09 | 41787206.48 | 82016913.83 | 0.00 | 0.00 |
| April | 0.168269E+09 | 0.137454E+09 | 0.182279E+09 | 69692155.54 | 0.112587E+09 | 0.00 | 0.00 |
| May | 0.249347E+09 | 0.121425E+09 | 0.242369E+09 | 98461254.39 | 0.143907E+09 | 0.00 | 0.00 |
| June | 0.239101E+09 | 91268864.80 | 0.225573E+09 | 87582538.84 | 0.137991E+09 | 0.00 | 0.00 |
| July | 0.353073E+09 | 76578582.49 | 0.287954E+09 | 0.151363E+09 | 0.136590E+09 | 0.00 | 0.00 |
| August | 0.298358E+09 | 74428965.78 | 0.238207E+09 | 0.121635E+09 | 0.116571E+09 | 0.00 | 0.00 |
| September | 0.205764E+09 | 0.112998E+09 | 0.187725E+09 | 90074743.68 | 97650664.86 | 0.00 | 0.00 |
| October | 89336947.43 | 0.161588E+09 | 0.110435E+09 | 44997027.39 | 65438053.22 | 0.00 | 0.00 |
| November | 23474422.97 | 0.184769E+09 | 53221922.87 | 15010796.12 | 38211126.74 | 0.00 | 0.00 |
| December | 21621572.79 | 0.227682E+09 | 46234764.70 | 15843478.51 | 30391286.19 | 0.00 | 0.00 |
| Annual Sum or Average | 0.180658E+10 | 0.175700E+10 | 0.182688E+10 | 0.780971E+09 | 0.104591E+10 | 0.00 | 0.00 |
| Minimum of Months | 17017250.77 | 74428965.78 | 46234764.70 | 14531301.98 | 30391286.19 | 0.00 | 0.00 |
| Maximum of Months | 0.353073E+09 | 0.227682E+09 | 0.287954E+09 | 0.151363E+09 | 0.143907E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 34625984.82 | 0.132502E+10 | 0.239063E+09 | 43593760.64 | 0.195469E+09 | 0.00 | 0.00 |
| February | 0.147868E+09 | 0.104979E+10 | 0.366245E+09 | 89975294.78 | 0.276270E+09 | 0.00 | 0.00 |
| March | 0.331438E+09 | 0.967370E+09 | 0.577702E+09 | 0.125361E+09 | 0.452341E+09 | 0.00 | 0.00 |
| April | 0.657181E+09 | 0.774328E+09 | 0.826743E+09 | 0.210029E+09 | 0.616715E+09 | 0.00 | 0.00 |
| May | 0.101011E+10 | 0.689771E+09 | 0.110355E+10 | 0.307183E+09 | 0.796370E+09 | 0.00 | 0.00 |
| June | 0.102101E+10 | 0.515930E+09 | 0.105686E+10 | 0.289787E+09 | 0.767070E+09 | 0.00 | 0.00 |
| July | 0.144552E+10 | 0.447378E+09 | 0.124010E+10 | 0.486112E+09 | 0.753989E+09 | 0.00 | 0.00 |
| August | 0.122857E+10 | 0.429700E+09 | 0.101666E+10 | 0.373174E+09 | 0.643487E+09 | 0.00 | 0.00 |
| September | 0.761599E+09 | 0.664493E+09 | 0.788245E+09 | 0.270277E+09 | 0.517969E+09 | 0.00 | 0.00 |
| October | 0.308230E+09 | 0.925149E+09 | 0.491632E+09 | 0.134991E+09 | 0.356641E+09 | 0.00 | 0.00 |
| November | 66397349.21 | 0.109334E+10 | 0.259687E+09 | 45032238.26 | 0.214655E+09 | 0.00 | 0.00 |
| December | 46067895.40 | 0.134516E+10 | 0.215171E+09 | 47530277.11 | 0.167640E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.705861E+10 | 0.102274E+11 | 0.818166E+10 | 0.242304E+10 | 0.575862E+10 | 0.00 | 0.00 |
| Minimum of Months | 34625984.82 | 0.429700E+09 | 0.215171E+09 | 43593760.64 | 0.167640E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.144552E+10 | 0.134516E+10 | 0.124010E+10 | 0.486112E+09 | 0.796370E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 603538.97 | 0.390200E+10 | 0.413443E+09 | 0.00 | 0.413443E+09 | 0.00 | 0.00 |
| February | 50570020.96 | 0.319129E+10 | 0.572990E+09 | 0.00 | 0.572990E+09 | 0.00 | 0.00 |
| March | 0.163766E+09 | 0.292794E+10 | 0.931245E+09 | 0.00 | 0.931245E+09 | 0.00 | 0.00 |
| April | 0.511230E+09 | 0.228646E+10 | 0.125686E+10 | 3274738.26 | 0.125359E+10 | 0.00 | 0.00 |
| May | 0.100062E+10 | 0.195321E+10 | 0.168650E+10 | 45727469.80 | 0.164077E+10 | 0.00 | 0.00 |
| June | 0.120767E+10 | 0.142651E+10 | 0.168548E+10 | 0.106311E+09 | 0.157917E+10 | 0.00 | 0.00 |
| July | 0.167680E+10 | 0.115582E+10 | 0.166383E+10 | 0.119934E+09 | 0.154390E+10 | 0.00 | 0.00 |
| August | 0.146339E+10 | 0.109224E+10 | 0.135162E+10 | 31164504.96 | 0.132045E+10 | 0.00 | 0.00 |
| September | 0.566293E+09 | 0.184257E+10 | 0.101122E+10 | 181011.95 | 0.101104E+10 | 0.00 | 0.00 |
| October | 0.120296E+09 | 0.273535E+10 | 0.721621E+09 | 0.00 | 0.721621E+09 | 0.00 | 0.00 |
| November | 12914030.53 | 0.327008E+10 | 0.453452E+09 | 0.00 | 0.453452E+09 | 0.00 | 0.00 |
| December | 507011.99 | 0.399361E+10 | 0.344912E+09 | 0.00 | 0.344912E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.677466E+10 | 0.297771E+11 | 0.120932E+11 | 0.306593E+09 | 0.117866E+11 | 0.00 | 0.00 |
| Minimum of Months | 507011.99 | 0.109224E+10 | 0.344912E+09 | 0.00 | 0.344912E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.167680E+10 | 0.399361E+10 | 0.168650E+10 | 0.119934E+09 | 0.164077E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.401455E+09 | 0.126333E+10 | 0.586770E+09 | 0.312403E+09 | 0.274367E+09 | 0.00 | 0.00 |
| February | 0.738429E+09 | 0.101575E+10 | 0.866648E+09 | 0.493427E+09 | 0.373221E+09 | 0.00 | 0.00 |
| March | 0.101202E+10 | 0.100175E+10 | 0.110982E+10 | 0.540538E+09 | 0.569281E+09 | 0.00 | 0.00 |
| April | 0.128963E+10 | 0.826553E+09 | 0.128573E+10 | 0.554768E+09 | 0.730965E+09 | 0.00 | 0.00 |
| May | 0.147212E+10 | 0.737561E+09 | 0.140953E+10 | 0.519489E+09 | 0.890038E+09 | 0.00 | 0.00 |
| June | 0.137106E+10 | 0.560610E+09 | 0.127080E+10 | 0.441571E+09 | 0.829234E+09 | 0.00 | 0.00 |
| July | 0.191849E+10 | 0.495313E+09 | 0.154682E+10 | 0.728983E+09 | 0.817838E+09 | 0.00 | 0.00 |
| August | 0.187976E+10 | 0.485163E+09 | 0.146230E+10 | 0.740934E+09 | 0.721364E+09 | 0.00 | 0.00 |
| September | 0.158363E+10 | 0.714327E+09 | 0.137959E+10 | 0.747626E+09 | 0.631965E+09 | 0.00 | 0.00 |
| October | 0.109164E+10 | 0.969719E+09 | 0.110603E+10 | 0.633728E+09 | 0.472303E+09 | 0.00 | 0.00 |
| November | 0.446633E+09 | 0.108070E+10 | 0.597989E+09 | 0.306151E+09 | 0.291838E+09 | 0.00 | 0.00 |
| December | 0.470974E+09 | 0.132117E+10 | 0.588436E+09 | 0.345066E+09 | 0.243370E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.136758E+11 | 0.104719E+11 | 0.132105E+11 | 0.636468E+10 | 0.684578E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.401455E+09 | 0.485163E+09 | 0.586770E+09 | 0.306151E+09 | 0.243370E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.191849E+10 | 0.132117E+10 | 0.154682E+10 | 0.747626E+09 | 0.890038E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.167043E+10 | 0.357970E+10 | 0.199193E+10 | 0.122430E+10 | 0.767630E+09 | 0.00 | 0.00 |
| February | 0.280399E+10 | 0.289838E+10 | 0.292068E+10 | 0.189295E+10 | 0.102772E+10 | 0.00 | 0.00 |
| March | 0.344081E+10 | 0.294192E+10 | 0.345631E+10 | 0.196412E+10 | 0.149219E+10 | 0.00 | 0.00 |
| April | 0.363577E+10 | 0.243867E+10 | 0.346155E+10 | 0.164696E+10 | 0.181459E+10 | 0.00 | 0.00 |
| May | 0.335316E+10 | 0.215170E+10 | 0.318690E+10 | 0.107188E+10 | 0.211502E+10 | 0.00 | 0.00 |
| June | 0.301005E+10 | 0.161807E+10 | 0.276350E+10 | 0.855542E+09 | 0.190796E+10 | 0.00 | 0.00 |
| July | 0.412663E+10 | 0.134013E+10 | 0.319507E+10 | 0.131557E+10 | 0.187950E+10 | 0.00 | 0.00 |
| August | 0.471230E+10 | 0.129396E+10 | 0.350753E+10 | 0.179481E+10 | 0.171272E+10 | 0.00 | 0.00 |
| September | 0.458687E+10 | 0.197668E+10 | 0.383414E+10 | 0.226969E+10 | 0.156445E+10 | 0.00 | 0.00 |
| October | 0.386397E+10 | 0.277688E+10 | 0.361174E+10 | 0.234170E+10 | 0.127004E+10 | 0.00 | 0.00 |
| November | 0.177248E+10 | 0.310465E+10 | 0.201779E+10 | 0.121060E+10 | 0.807197E+09 | 0.00 | 0.00 |
| December | 0.187609E+10 | 0.380764E+10 | 0.199742E+10 | 0.132154E+10 | 0.675886E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.388526E+11 | 0.299284E+11 | 0.359446E+11 | 0.189097E+11 | 0.170349E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.167043E+10 | 0.129396E+10 | 0.199193E+10 | 0.855542E+09 | 0.675886E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.471230E+10 | 0.380764E+10 | 0.383414E+10 | 0.234170E+10 | 0.211502E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 17059487.33 | 0.221427E+09 | 49278394.98 | 14531301.98 | 34747093.00 | 0.00 | 0.00 |
| February | 49590230.33 | 0.177768E+09 | 79802069.13 | 29991864.90 | 49810204.23 | 0.00 | 0.00 |
| March | 91728541.05 | 0.169178E+09 | 0.123804E+09 | 41787206.48 | 82016913.83 | 0.00 | 0.00 |
| April | 0.168379E+09 | 0.137333E+09 | 0.182279E+09 | 69692155.54 | 0.112587E+09 | 0.00 | 0.00 |
| May | 0.249467E+09 | 0.121300E+09 | 0.242369E+09 | 98461254.39 | 0.143907E+09 | 0.00 | 0.00 |
| June | 0.239260E+09 | 91112619.33 | 0.225573E+09 | 87582538.84 | 0.137991E+09 | 0.00 | 0.00 |
| July | 0.353431E+09 | 76261180.47 | 0.287954E+09 | 0.151363E+09 | 0.136590E+09 | 0.00 | 0.00 |
| August | 0.298615E+09 | 74173023.84 | 0.238207E+09 | 0.121635E+09 | 0.116571E+09 | 0.00 | 0.00 |
| September | 0.205890E+09 | 0.112841E+09 | 0.187725E+09 | 90074743.68 | 97650664.86 | 0.00 | 0.00 |
| October | 89399210.65 | 0.161490E+09 | 0.110435E+09 | 44997027.39 | 65438053.22 | 0.00 | 0.00 |
| November | 23518976.58 | 0.184573E+09 | 53221922.87 | 15010796.12 | 38211126.74 | 0.00 | 0.00 |
| December | 21744174.80 | 0.226932E+09 | 46234764.70 | 15843478.51 | 30391286.19 | 0.00 | 0.00 |
| Annual Sum or Average | 0.180808E+10 | 0.175439E+10 | 0.182688E+10 | 0.780971E+09 | 0.104591E+10 | 0.00 | 0.00 |
| Minimum of Months | 17059487.33 | 74173023.84 | 46234764.70 | 14531301.98 | 30391286.19 | 0.00 | 0.00 |
| Maximum of Months | 0.353431E+09 | 0.226932E+09 | 0.287954E+09 | 0.151363E+09 | 0.143907E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 34924513.05 | 0.132467E+10 | 0.240175E+09 | 43593760.64 | 0.196581E+09 | 0.00 | 0.00 |
| February | 0.148827E+09 | 0.104962E+10 | 0.367908E+09 | 89975294.78 | 0.277933E+09 | 0.00 | 0.00 |
| March | 0.333948E+09 | 0.967438E+09 | 0.580459E+09 | 0.125361E+09 | 0.455097E+09 | 0.00 | 0.00 |
| April | 0.661340E+09 | 0.774392E+09 | 0.830730E+09 | 0.210052E+09 | 0.620678E+09 | 0.00 | 0.00 |
| May | 0.101552E+10 | 0.689743E+09 | 0.110856E+10 | 0.307312E+09 | 0.801249E+09 | 0.00 | 0.00 |
| June | 0.102674E+10 | 0.515616E+09 | 0.106227E+10 | 0.290087E+09 | 0.772187E+09 | 0.00 | 0.00 |
| July | 0.145109E+10 | 0.447004E+09 | 0.124511E+10 | 0.486353E+09 | 0.758758E+09 | 0.00 | 0.00 |
| August | 0.123329E+10 | 0.429658E+09 | 0.102089E+10 | 0.373297E+09 | 0.647591E+09 | 0.00 | 0.00 |
| September | 0.765283E+09 | 0.664811E+09 | 0.791535E+09 | 0.270277E+09 | 0.521258E+09 | 0.00 | 0.00 |
| October | 0.310252E+09 | 0.925308E+09 | 0.493894E+09 | 0.134991E+09 | 0.358904E+09 | 0.00 | 0.00 |
| November | 66937066.92 | 0.109296E+10 | 0.260901E+09 | 45032238.26 | 0.215868E+09 | 0.00 | 0.00 |
| December | 46459619.49 | 0.134427E+10 | 0.216192E+09 | 47530277.11 | 0.168662E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.709461E+10 | 0.102255E+11 | 0.821863E+10 | 0.242386E+10 | 0.579477E+10 | 0.00 | 0.00 |
| Minimum of Months | 34924513.05 | 0.429658E+09 | 0.216192E+09 | 43593760.64 | 0.168662E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.145109E+10 | 0.134427E+10 | 0.124511E+10 | 0.486353E+09 | 0.801249E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 752742.77 | 0.389969E+10 | 0.418891E+09 | 0.00 | 0.418891E+09 | 0.00 | 0.00 |
| February | 52641938.69 | 0.318822E+10 | 0.581135E+09 | 0.00 | 0.581135E+09 | 0.00 | 0.00 |
| March | 0.172679E+09 | 0.292527E+10 | 0.944747E+09 | 0.00 | 0.944747E+09 | 0.00 | 0.00 |
| April | 0.529401E+09 | 0.228467E+10 | 0.127646E+10 | 3408759.70 | 0.127305E+10 | 0.00 | 0.00 |
| May | 0.102781E+10 | 0.195164E+10 | 0.171245E+10 | 47126643.48 | 0.166532E+10 | 0.00 | 0.00 |
| June | 0.123723E+10 | 0.142433E+10 | 0.171377E+10 | 0.108923E+09 | 0.160485E+10 | 0.00 | 0.00 |
| July | 0.170804E+10 | 0.115454E+10 | 0.169174E+10 | 0.123572E+09 | 0.156817E+10 | 0.00 | 0.00 |
| August | 0.148715E+10 | 0.109320E+10 | 0.137292E+10 | 32134931.19 | 0.134079E+10 | 0.00 | 0.00 |
| September | 0.582914E+09 | 0.184390E+10 | 0.102734E+10 | 181012.19 | 0.102716E+10 | 0.00 | 0.00 |
| October | 0.127096E+09 | 0.273390E+10 | 0.732703E+09 | 0.00 | 0.732703E+09 | 0.00 | 0.00 |
| November | 13837260.37 | 0.326762E+10 | 0.459397E+09 | 0.00 | 0.459397E+09 | 0.00 | 0.00 |
| December | 566698.20 | 0.398979E+10 | 0.349915E+09 | 0.00 | 0.349915E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.694012E+10 | 0.297568E+11 | 0.122815E+11 | 0.315346E+09 | 0.119661E+11 | 0.00 | 0.00 |
| Minimum of Months | 566698.20 | 0.109320E+10 | 0.349915E+09 | 0.00 | 0.349915E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.170804E+10 | 0.398979E+10 | 0.171377E+10 | 0.123572E+09 | 0.166532E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.405485E+09 | 0.126299E+10 | 0.593371E+09 | 0.316271E+09 | 0.277101E+09 | 0.00 | 0.00 |
| February | 0.739342E+09 | 0.101740E+10 | 0.869179E+09 | 0.493831E+09 | 0.375348E+09 | 0.00 | 0.00 |
| March | 0.101331E+10 | 0.100688E+10 | 0.111299E+10 | 0.540612E+09 | 0.572377E+09 | 0.00 | 0.00 |
| April | 0.129193E+10 | 0.831619E+09 | 0.129011E+10 | 0.554768E+09 | 0.735338E+09 | 0.00 | 0.00 |
| May | 0.147638E+10 | 0.740945E+09 | 0.141486E+10 | 0.519489E+09 | 0.895370E+09 | 0.00 | 0.00 |
| June | 0.137525E+10 | 0.563684E+09 | 0.127630E+10 | 0.441571E+09 | 0.834728E+09 | 0.00 | 0.00 |
| July | 0.192058E+10 | 0.500034E+09 | 0.155198E+10 | 0.728983E+09 | 0.823000E+09 | 0.00 | 0.00 |
| August | 0.188208E+10 | 0.489290E+09 | 0.146678E+10 | 0.740934E+09 | 0.725846E+09 | 0.00 | 0.00 |
| September | 0.158595E+10 | 0.718541E+09 | 0.138328E+10 | 0.747640E+09 | 0.635644E+09 | 0.00 | 0.00 |
| October | 0.109266E+10 | 0.974928E+09 | 0.110901E+10 | 0.634033E+09 | 0.474982E+09 | 0.00 | 0.00 |
| November | 0.447110E+09 | 0.108500E+10 | 0.601149E+09 | 0.307252E+09 | 0.293897E+09 | 0.00 | 0.00 |
| December | 0.482371E+09 | 0.132242E+10 | 0.601002E+09 | 0.353784E+09 | 0.247219E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.137125E+11 | 0.105137E+11 | 0.132700E+11 | 0.637917E+10 | 0.689085E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.405485E+09 | 0.489290E+09 | 0.593371E+09 | 0.307252E+09 | 0.247219E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.192058E+10 | 0.132242E+10 | 0.155198E+10 | 0.747640E+09 | 0.895370E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.170020E+10 | 0.357275E+10 | 0.203227E+10 | 0.124958E+10 | 0.782693E+09 | 0.00 | 0.00 |
| February | 0.280917E+10 | 0.290251E+10 | 0.293478E+10 | 0.189644E+10 | 0.103834E+10 | 0.00 | 0.00 |
| March | 0.344790E+10 | 0.296448E+10 | 0.347064E+10 | 0.196477E+10 | 0.150587E+10 | 0.00 | 0.00 |
| April | 0.364803E+10 | 0.245860E+10 | 0.348075E+10 | 0.164697E+10 | 0.183379E+10 | 0.00 | 0.00 |
| May | 0.337338E+10 | 0.216338E+10 | 0.321031E+10 | 0.107188E+10 | 0.213843E+10 | 0.00 | 0.00 |
| June | 0.302899E+10 | 0.163000E+10 | 0.278763E+10 | 0.855546E+09 | 0.193208E+10 | 0.00 | 0.00 |
| July | 0.413974E+10 | 0.135768E+10 | 0.321773E+10 | 0.131557E+10 | 0.190216E+10 | 0.00 | 0.00 |
| August | 0.472339E+10 | 0.131098E+10 | 0.352722E+10 | 0.179482E+10 | 0.173240E+10 | 0.00 | 0.00 |
| September | 0.459832E+10 | 0.199389E+10 | 0.385048E+10 | 0.226983E+10 | 0.158065E+10 | 0.00 | 0.00 |
| October | 0.387214E+10 | 0.279877E+10 | 0.362727E+10 | 0.234490E+10 | 0.128237E+10 | 0.00 | 0.00 |
| November | 0.178122E+10 | 0.312161E+10 | 0.203866E+10 | 0.121993E+10 | 0.818732E+09 | 0.00 | 0.00 |
| December | 0.193799E+10 | 0.380533E+10 | 0.206435E+10 | 0.136919E+10 | 0.695153E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.390605E+11 | 0.300800E+11 | 0.362421E+11 | 0.189994E+11 | 0.172427E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.170020E+10 | 0.131098E+10 | 0.203227E+10 | 0.855546E+09 | 0.695153E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.472339E+10 | 0.380533E+10 | 0.385048E+10 | 0.234490E+10 | 0.213843E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 16971827.48 | 0.222491E+09 | 49278394.98 | 14531301.98 | 34747093.00 | 0.00 | 0.00 |
| February | 49289979.53 | 0.179093E+09 | 79802069.13 | 29991864.90 | 49810204.23 | 0.00 | 0.00 |
| March | 90857301.47 | 0.171927E+09 | 0.123804E+09 | 41787206.48 | 82016913.83 | 0.00 | 0.00 |
| April | 0.167060E+09 | 0.139840E+09 | 0.182279E+09 | 69692155.54 | 0.112587E+09 | 0.00 | 0.00 |
| May | 0.248483E+09 | 0.122941E+09 | 0.242369E+09 | 98461254.39 | 0.143907E+09 | 0.00 | 0.00 |
| June | 0.238108E+09 | 92622972.76 | 0.225573E+09 | 87582538.84 | 0.137991E+09 | 0.00 | 0.00 |
| July | 0.351442E+09 | 78267909.22 | 0.287954E+09 | 0.151363E+09 | 0.136590E+09 | 0.00 | 0.00 |
| August | 0.297014E+09 | 76012138.82 | 0.238207E+09 | 0.121635E+09 | 0.116571E+09 | 0.00 | 0.00 |
| September | 0.204929E+09 | 0.114766E+09 | 0.187725E+09 | 90074743.68 | 97650664.86 | 0.00 | 0.00 |
| October | 88705095.01 | 0.164308E+09 | 0.110435E+09 | 44997027.39 | 65438053.22 | 0.00 | 0.00 |
| November | 23180439.88 | 0.187355E+09 | 53221922.87 | 15010796.12 | 38211126.74 | 0.00 | 0.00 |
| December | 21591286.69 | 0.228549E+09 | 46234764.70 | 15843478.51 | 30391286.19 | 0.00 | 0.00 |
| Annual Sum or Average | 0.179763E+10 | 0.177817E+10 | 0.182688E+10 | 0.780971E+09 | 0.104591E+10 | 0.00 | 0.00 |
| Minimum of Months | 16971827.48 | 76012138.82 | 46234764.70 | 14531301.98 | 30391286.19 | 0.00 | 0.00 |
| Maximum of Months | 0.351442E+09 | 0.228549E+09 | 0.287954E+09 | 0.151363E+09 | 0.143907E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 38564137.48 | 0.132317E+10 | 0.254073E+09 | 43593760.64 | 0.210480E+09 | 0.00 | 0.00 |
| February | 0.161089E+09 | 0.104875E+10 | 0.388718E+09 | 89975294.78 | 0.298743E+09 | 0.00 | 0.00 |
| March | 0.364688E+09 | 0.973161E+09 | 0.614970E+09 | 0.125361E+09 | 0.489609E+09 | 0.00 | 0.00 |
| April | 0.710879E+09 | 0.781704E+09 | 0.880377E+09 | 0.210259E+09 | 0.670118E+09 | 0.00 | 0.00 |
| May | 0.108117E+10 | 0.694939E+09 | 0.117059E+10 | 0.308558E+09 | 0.862037E+09 | 0.00 | 0.00 |
| June | 0.109503E+10 | 0.519689E+09 | 0.112799E+10 | 0.292547E+09 | 0.835448E+09 | 0.00 | 0.00 |
| July | 0.151145E+10 | 0.453850E+09 | 0.130707E+10 | 0.488838E+09 | 0.818233E+09 | 0.00 | 0.00 |
| August | 0.128528E+10 | 0.438544E+09 | 0.107340E+10 | 0.374603E+09 | 0.698798E+09 | 0.00 | 0.00 |
| September | 0.807682E+09 | 0.676069E+09 | 0.832874E+09 | 0.270303E+09 | 0.562572E+09 | 0.00 | 0.00 |
| October | 0.334471E+09 | 0.933383E+09 | 0.522253E+09 | 0.134991E+09 | 0.387262E+09 | 0.00 | 0.00 |
| November | 73091801.28 | 0.109546E+10 | 0.276064E+09 | 45032238.26 | 0.231032E+09 | 0.00 | 0.00 |
| December | 50191866.64 | 0.134625E+10 | 0.228979E+09 | 47530277.11 | 0.181449E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.751359E+10 | 0.102850E+11 | 0.867737E+10 | 0.243159E+10 | 0.624578E+10 | 0.00 | 0.00 |
| Minimum of Months | 38564137.48 | 0.438544E+09 | 0.228979E+09 | 43593760.64 | 0.181449E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.151145E+10 | 0.134625E+10 | 0.130707E+10 | 0.488838E+09 | 0.862037E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 3945479.33 | 0.256544E+10 | 0.339214E+09 | 0.00 | 0.339214E+09 | 0.00 | 0.00 |
| February | 62884565.94 | 0.208019E+10 | 0.476747E+09 | 0.00 | 0.476747E+09 | 0.00 | 0.00 |
| March | 0.228385E+09 | 0.192772E+10 | 0.777671E+09 | 0.00 | 0.777671E+09 | 0.00 | 0.00 |
| April | 0.561383E+09 | 0.151115E+10 | 0.106498E+10 | 3777788.01 | 0.106121E+10 | 0.00 | 0.00 |
| May | 0.982532E+09 | 0.128883E+10 | 0.141605E+10 | 42068266.26 | 0.137398E+10 | 0.00 | 0.00 |
| June | 0.115371E+10 | 0.946758E+09 | 0.144091E+10 | 95150576.36 | 0.134576E+10 | 0.00 | 0.00 |
| July | 0.145211E+10 | 0.782496E+09 | 0.141515E+10 | 0.110954E+09 | 0.130420E+10 | 0.00 | 0.00 |
| August | 0.123540E+10 | 0.750315E+09 | 0.114558E+10 | 30968086.13 | 0.111461E+10 | 0.00 | 0.00 |
| September | 0.570559E+09 | 0.125320E+10 | 0.861139E+09 | 253934.29 | 0.860885E+09 | 0.00 | 0.00 |
| October | 0.172697E+09 | 0.181583E+10 | 0.609690E+09 | 0.00 | 0.609690E+09 | 0.00 | 0.00 |
| November | 22133472.48 | 0.215564E+10 | 0.371656E+09 | 0.00 | 0.371656E+09 | 0.00 | 0.00 |
| December | 1679456.19 | 0.263648E+10 | 0.288245E+09 | 0.00 | 0.288245E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.644742E+10 | 0.197141E+11 | 0.102070E+11 | 0.283172E+09 | 0.992386E+10 | 0.00 | 0.00 |
| Minimum of Months | 1679456.19 | 0.750315E+09 | 0.288245E+09 | 0.00 | 0.288245E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.145211E+10 | 0.263648E+10 | 0.144091E+10 | 0.110954E+09 | 0.137398E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 1170425.07 | 0.137239E+10 | 0.174452E+09 | 0.00 | 0.174452E+09 | 0.00 | 0.00 |
| February | 28087696.10 | 0.112936E+10 | 0.245183E+09 | 0.00 | 0.245183E+09 | 0.00 | 0.00 |
| March | 0.100288E+09 | 0.107727E+10 | 0.399943E+09 | 0.00 | 0.399943E+09 | 0.00 | 0.00 |
| April | 0.263947E+09 | 0.846339E+09 | 0.547702E+09 | 1942867.38 | 0.545760E+09 | 0.00 | 0.00 |
| May | 0.482065E+09 | 0.711843E+09 | 0.728247E+09 | 21635163.83 | 0.706612E+09 | 0.00 | 0.00 |
| June | 0.563026E+09 | 0.525347E+09 | 0.741033E+09 | 48934707.59 | 0.692098E+09 | 0.00 | 0.00 |
| July | 0.699915E+09 | 0.443019E+09 | 0.727788E+09 | 57062032.47 | 0.670726E+09 | 0.00 | 0.00 |
| August | 0.589452E+09 | 0.431750E+09 | 0.589150E+09 | 15926485.13 | 0.573223E+09 | 0.00 | 0.00 |
| September | 0.269437E+09 | 0.705454E+09 | 0.442868E+09 | 130595.11 | 0.442738E+09 | 0.00 | 0.00 |
| October | 76106960.97 | 0.101834E+10 | 0.313553E+09 | 0.00 | 0.313553E+09 | 0.00 | 0.00 |
| November | 8070045.98 | 0.119509E+10 | 0.191136E+09 | 0.00 | 0.191136E+09 | 0.00 | 0.00 |
| December | 497348.61 | 0.142521E+10 | 0.148239E+09 | 0.00 | 0.148239E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.308206E+10 | 0.108814E+11 | 0.524929E+10 | 0.145632E+09 | 0.510366E+10 | 0.00 | 0.00 |
| Minimum of Months | 497348.61 | 0.431750E+09 | 0.148239E+09 | 0.00 | 0.148239E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.699915E+09 | 0.142521E+10 | 0.741033E+09 | 57062032.47 | 0.706612E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 743027.55 | 0.680246E+09 | 75263086.72 | 6933862.22 | 68329224.49 | 0.00 | 0.00 |
| February | 47713203.26 | 0.541798E+09 | 0.136949E+09 | 35239160.42 | 0.101710E+09 | 0.00 | 0.00 |
| March | 0.157742E+09 | 0.517952E+09 | 0.262195E+09 | 81676865.58 | 0.180518E+09 | 0.00 | 0.00 |
| April | 0.376269E+09 | 0.431110E+09 | 0.436116E+09 | 0.177367E+09 | 0.258749E+09 | 0.00 | 0.00 |
| May | 0.593708E+09 | 0.387973E+09 | 0.598564E+09 | 0.262606E+09 | 0.335958E+09 | 0.00 | 0.00 |
| June | 0.566286E+09 | 0.294483E+09 | 0.552658E+09 | 0.231544E+09 | 0.321114E+09 | 0.00 | 0.00 |
| July | 0.857022E+09 | 0.256282E+09 | 0.716129E+09 | 0.394991E+09 | 0.321138E+09 | 0.00 | 0.00 |
| August | 0.717476E+09 | 0.240449E+09 | 0.586138E+09 | 0.314863E+09 | 0.271274E+09 | 0.00 | 0.00 |
| September | 0.441118E+09 | 0.343146E+09 | 0.426254E+09 | 0.205517E+09 | 0.220737E+09 | 0.00 | 0.00 |
| October | 0.122741E+09 | 0.490494E+09 | 0.203143E+09 | 66850320.11 | 0.136293E+09 | 0.00 | 0.00 |
| November | 12536972.49 | 0.563574E+09 | 88131513.74 | 11534029.65 | 76597484.09 | 0.00 | 0.00 |
| December | 1430930.92 | 0.689865E+09 | 61876922.23 | 4845764.30 | 57031157.93 | 0.00 | 0.00 |
| Annual Sum or Average | 0.389479E+10 | 0.543737E+10 | 0.414342E+10 | 0.179397E+10 | 0.234945E+10 | 0.00 | 0.00 |
| Minimum of Months | 743027.55 | 0.240449E+09 | 61876922.23 | 4845764.30 | 57031157.93 | 0.00 | 0.00 |
| Maximum of Months | 0.857022E+09 | 0.689865E+09 | 0.716129E+09 | 0.394991E+09 | 0.335958E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.710446E+09 | 0.111835E+10 | 0.813626E+09 | 0.483135E+09 | 0.330491E+09 | 0.00 | 0.00 |
| February | 0.113764E+10 | 0.924058E+09 | 0.113014E+10 | 0.699575E+09 | 0.430570E+09 | 0.00 | 0.00 |
| March | 0.141109E+10 | 0.937660E+09 | 0.134596E+10 | 0.717787E+09 | 0.628176E+09 | 0.00 | 0.00 |
| April | 0.152049E+10 | 0.786715E+09 | 0.137524E+10 | 0.597122E+09 | 0.778119E+09 | 0.00 | 0.00 |
| May | 0.143974E+10 | 0.707737E+09 | 0.129940E+10 | 0.387104E+09 | 0.912293E+09 | 0.00 | 0.00 |
| June | 0.129879E+10 | 0.550678E+09 | 0.115047E+10 | 0.308887E+09 | 0.841585E+09 | 0.00 | 0.00 |
| July | 0.163944E+10 | 0.503729E+09 | 0.129646E+10 | 0.474833E+09 | 0.821628E+09 | 0.00 | 0.00 |
| August | 0.183223E+10 | 0.491089E+09 | 0.139288E+10 | 0.649525E+09 | 0.743359E+09 | 0.00 | 0.00 |
| September | 0.181711E+10 | 0.675121E+09 | 0.149348E+10 | 0.824747E+09 | 0.668729E+09 | 0.00 | 0.00 |
| October | 0.154869E+10 | 0.887833E+09 | 0.139793E+10 | 0.863119E+09 | 0.534812E+09 | 0.00 | 0.00 |
| November | 0.739135E+09 | 0.967656E+09 | 0.799842E+09 | 0.458377E+09 | 0.341465E+09 | 0.00 | 0.00 |
| December | 0.837226E+09 | 0.117197E+10 | 0.864759E+09 | 0.559620E+09 | 0.305139E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.159320E+11 | 0.972259E+10 | 0.143602E+11 | 0.702383E+10 | 0.733637E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.710446E+09 | 0.491089E+09 | 0.799842E+09 | 0.308887E+09 | 0.305139E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.183223E+10 | 0.117197E+10 | 0.149348E+10 | 0.863119E+09 | 0.912293E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 8456499.08 | 0.688201E+09 | 93848763.71 | 13579400.41 | 80269363.30 | 0.00 | 0.00 |
| February | 78133564.13 | 0.563933E+09 | 0.172146E+09 | 52464696.09 | 0.119681E+09 | 0.00 | 0.00 |
| March | 0.201117E+09 | 0.564607E+09 | 0.312072E+09 | 0.102540E+09 | 0.209533E+09 | 0.00 | 0.00 |
| April | 0.436267E+09 | 0.475379E+09 | 0.500646E+09 | 0.204531E+09 | 0.296116E+09 | 0.00 | 0.00 |
| May | 0.662932E+09 | 0.440918E+09 | 0.679275E+09 | 0.296594E+09 | 0.382681E+09 | 0.00 | 0.00 |
| June | 0.618795E+09 | 0.346888E+09 | 0.625554E+09 | 0.260300E+09 | 0.365254E+09 | 0.00 | 0.00 |
| July | 0.952344E+09 | 0.301830E+09 | 0.809749E+09 | 0.444895E+09 | 0.364854E+09 | 0.00 | 0.00 |
| August | 0.802755E+09 | 0.284722E+09 | 0.667976E+09 | 0.358734E+09 | 0.309243E+09 | 0.00 | 0.00 |
| September | 0.513494E+09 | 0.397107E+09 | 0.499942E+09 | 0.245390E+09 | 0.254552E+09 | 0.00 | 0.00 |
| October | 0.166443E+09 | 0.541992E+09 | 0.250888E+09 | 90905830.07 | 0.159982E+09 | 0.00 | 0.00 |
| November | 24412198.80 | 0.611768E+09 | 0.109775E+09 | 19671711.10 | 90102852.38 | 0.00 | 0.00 |
| December | 7592259.15 | 0.717218E+09 | 77321584.59 | 10299449.76 | 67022134.83 | 0.00 | 0.00 |
| Annual Sum or Average | 0.447274E+10 | 0.593456E+10 | 0.479919E+10 | 0.209990E+10 | 0.269929E+10 | 0.00 | 0.00 |
| Minimum of Months | 7592259.15 | 0.284722E+09 | 77321584.59 | 10299449.76 | 67022134.83 | 0.00 | 0.00 |
| Maximum of Months | 0.952344E+09 | 0.717218E+09 | 0.809749E+09 | 0.444895E+09 | 0.382681E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.776404E+09 | 0.276187E+10 | 0.122629E+10 | 0.616895E+09 | 0.609396E+09 | 0.00 | 0.00 |
| February | 0.146114E+10 | 0.226715E+10 | 0.179109E+10 | 0.965570E+09 | 0.825524E+09 | 0.00 | 0.00 |
| March | 0.210003E+10 | 0.231734E+10 | 0.238358E+10 | 0.111768E+10 | 0.126591E+10 | 0.00 | 0.00 |
| April | 0.277617E+10 | 0.189701E+10 | 0.286408E+10 | 0.121846E+10 | 0.164562E+10 | 0.00 | 0.00 |
| May | 0.288444E+10 | 0.170467E+10 | 0.291407E+10 | 0.941682E+09 | 0.197239E+10 | 0.00 | 0.00 |
| June | 0.312612E+10 | 0.130820E+10 | 0.298443E+10 | 0.108668E+10 | 0.189775E+10 | 0.00 | 0.00 |
| July | 0.356775E+10 | 0.116514E+10 | 0.308116E+10 | 0.126464E+10 | 0.181652E+10 | 0.00 | 0.00 |
| August | 0.383899E+10 | 0.112146E+10 | 0.315948E+10 | 0.152830E+10 | 0.163118E+10 | 0.00 | 0.00 |
| September | 0.307881E+10 | 0.161074E+10 | 0.280977E+10 | 0.144614E+10 | 0.136363E+10 | 0.00 | 0.00 |
| October | 0.223000E+10 | 0.220775E+10 | 0.232575E+10 | 0.128568E+10 | 0.104007E+10 | 0.00 | 0.00 |
| November | 0.883886E+09 | 0.243802E+10 | 0.125433E+10 | 0.611159E+09 | 0.643170E+09 | 0.00 | 0.00 |
| December | 0.948841E+09 | 0.289421E+10 | 0.126963E+10 | 0.719556E+09 | 0.550074E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.276726E+11 | 0.236935E+11 | 0.280637E+11 | 0.128024E+11 | 0.152612E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.776404E+09 | 0.112146E+10 | 0.122629E+10 | 0.611159E+09 | 0.550074E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.383899E+10 | 0.289421E+10 | 0.315948E+10 | 0.152830E+10 | 0.197239E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.163997E+09 | 0.275565E+10 | 0.684599E+09 | 0.158737E+09 | 0.525862E+09 | 0.00 | 0.00 |
| February | 0.683321E+09 | 0.227518E+10 | 0.113655E+10 | 0.413367E+09 | 0.723183E+09 | 0.00 | 0.00 |
| March | 0.161282E+10 | 0.225204E+10 | 0.198626E+10 | 0.794257E+09 | 0.119201E+10 | 0.00 | 0.00 |
| April | 0.304540E+10 | 0.181991E+10 | 0.305668E+10 | 0.145446E+10 | 0.160222E+10 | 0.00 | 0.00 |
| May | 0.414962E+10 | 0.161047E+10 | 0.383458E+10 | 0.177459E+10 | 0.205999E+10 | 0.00 | 0.00 |
| June | 0.473875E+10 | 0.125146E+10 | 0.417275E+10 | 0.223150E+10 | 0.194125E+10 | 0.00 | 0.00 |
| July | 0.521907E+10 | 0.116164E+10 | 0.434208E+10 | 0.258021E+10 | 0.176187E+10 | 0.00 | 0.00 |
| August | 0.451544E+10 | 0.113332E+10 | 0.370981E+10 | 0.217320E+10 | 0.153661E+10 | 0.00 | 0.00 |
| September | 0.277530E+10 | 0.154727E+10 | 0.257684E+10 | 0.133838E+10 | 0.123845E+10 | 0.00 | 0.00 |
| October | 0.135180E+10 | 0.211576E+10 | 0.161108E+10 | 0.711604E+09 | 0.899475E+09 | 0.00 | 0.00 |
| November | 0.333134E+09 | 0.237646E+10 | 0.777567E+09 | 0.204306E+09 | 0.573261E+09 | 0.00 | 0.00 |
| December | 0.167798E+09 | 0.291696E+10 | 0.606901E+09 | 0.167189E+09 | 0.439712E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.287565E+11 | 0.232161E+11 | 0.284957E+11 | 0.140018E+11 | 0.144939E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.163997E+09 | 0.113332E+10 | 0.606901E+09 | 0.158737E+09 | 0.439712E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.521907E+10 | 0.291696E+10 | 0.434208E+10 | 0.258021E+10 | 0.205999E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 23207720.16 | 0.835112E+09 | 0.124583E+09 | 31585819.68 | 92997450.63 | 0.00 | 0.00 |
| February | 91738907.46 | 0.660615E+09 | 0.206476E+09 | 73282195.22 | 0.133194E+09 | 0.00 | 0.00 |
| March | 0.218622E+09 | 0.596793E+09 | 0.341313E+09 | 0.123558E+09 | 0.217756E+09 | 0.00 | 0.00 |
| April | 0.440390E+09 | 0.441886E+09 | 0.512026E+09 | 0.212753E+09 | 0.299273E+09 | 0.00 | 0.00 |
| May | 0.523592E+09 | 0.379486E+09 | 0.563003E+09 | 0.195742E+09 | 0.367261E+09 | 0.00 | 0.00 |
| June | 0.679516E+09 | 0.287320E+09 | 0.652509E+09 | 0.283910E+09 | 0.368600E+09 | 0.00 | 0.00 |
| July | 0.694439E+09 | 0.258703E+09 | 0.627893E+09 | 0.281833E+09 | 0.346060E+09 | 0.00 | 0.00 |
| August | 0.719378E+09 | 0.249904E+09 | 0.617130E+09 | 0.308722E+09 | 0.308408E+09 | 0.00 | 0.00 |
| September | 0.432215E+09 | 0.357270E+09 | 0.441559E+09 | 0.203650E+09 | 0.237909E+09 | 0.00 | 0.00 |
| October | 0.216479E+09 | 0.531863E+09 | 0.297401E+09 | 0.126367E+09 | 0.171034E+09 | 0.00 | 0.00 |
| November | 46957401.98 | 0.672513E+09 | 0.141067E+09 | 39824463.49 | 0.101243E+09 | 0.00 | 0.00 |
| December | 34565499.85 | 0.847726E+09 | 0.119564E+09 | 38490886.54 | 81072796.48 | 0.00 | 0.00 |
| Annual Sum or Average | 0.412110E+10 | 0.611919E+10 | 0.464453E+10 | 0.191972E+10 | 0.272481E+10 | 0.00 | 0.00 |
| Minimum of Months | 23207720.16 | 0.249904E+09 | 0.119564E+09 | 31585819.68 | 81072796.48 | 0.00 | 0.00 |
| Maximum of Months | 0.719378E+09 | 0.847726E+09 | 0.652509E+09 | 0.308722E+09 | 0.368600E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 21388953.17 | 0.269936E+10 | 0.425240E+09 | 59225473.78 | 0.366015E+09 | 0.00 | 0.00 |
| February | 0.171362E+09 | 0.216489E+10 | 0.656268E+09 | 0.137409E+09 | 0.518859E+09 | 0.00 | 0.00 |
| March | 0.510809E+09 | 0.200487E+10 | 0.107902E+10 | 0.231678E+09 | 0.847338E+09 | 0.00 | 0.00 |
| April | 0.111324E+10 | 0.156776E+10 | 0.155812E+10 | 0.400243E+09 | 0.115788E+10 | 0.00 | 0.00 |
| May | 0.149041E+10 | 0.141185E+10 | 0.184231E+10 | 0.383183E+09 | 0.145913E+10 | 0.00 | 0.00 |
| June | 0.183028E+10 | 0.111040E+10 | 0.201792E+10 | 0.574052E+09 | 0.144386E+10 | 0.00 | 0.00 |
| July | 0.196635E+10 | 0.983481E+09 | 0.194818E+10 | 0.569241E+09 | 0.137894E+10 | 0.00 | 0.00 |
| August | 0.192364E+10 | 0.939608E+09 | 0.179493E+10 | 0.590492E+09 | 0.120444E+10 | 0.00 | 0.00 |
| September | 0.106588E+10 | 0.136125E+10 | 0.131309E+10 | 0.381945E+09 | 0.931148E+09 | 0.00 | 0.00 |
| October | 0.468012E+09 | 0.187778E+10 | 0.901399E+09 | 0.236946E+09 | 0.664453E+09 | 0.00 | 0.00 |
| November | 75467246.17 | 0.225737E+10 | 0.474549E+09 | 74673468.72 | 0.399875E+09 | 0.00 | 0.00 |
| December | 38392514.67 | 0.278833E+10 | 0.386652E+09 | 72172924.90 | 0.314479E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.106752E+11 | 0.211670E+11 | 0.143977E+11 | 0.371126E+10 | 0.106864E+11 | 0.00 | 0.00 |
| Minimum of Months | 21388953.17 | 0.939608E+09 | 0.386652E+09 | 59225473.78 | 0.314479E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.196635E+10 | 0.278833E+10 | 0.201792E+10 | 0.590492E+09 | 0.145913E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 20713973.46 | 0.290518E+10 | 0.459411E+09 | 54783683.49 | 0.404627E+09 | 0.00 | 0.00 |
| February | 0.211740E+09 | 0.234587E+10 | 0.739474E+09 | 0.157847E+09 | 0.581627E+09 | 0.00 | 0.00 |
| March | 0.617795E+09 | 0.230156E+10 | 0.126054E+10 | 0.299032E+09 | 0.961508E+09 | 0.00 | 0.00 |
| April | 0.136160E+10 | 0.181888E+10 | 0.185740E+10 | 0.536039E+09 | 0.132136E+10 | 0.00 | 0.00 |
| May | 0.181348E+10 | 0.160626E+10 | 0.218913E+10 | 0.524723E+09 | 0.166441E+10 | 0.00 | 0.00 |
| June | 0.229329E+10 | 0.121854E+10 | 0.244042E+10 | 0.786496E+09 | 0.165393E+10 | 0.00 | 0.00 |
| July | 0.245658E+10 | 0.105749E+10 | 0.236196E+10 | 0.786685E+09 | 0.157528E+10 | 0.00 | 0.00 |
| August | 0.238987E+10 | 0.103543E+10 | 0.217990E+10 | 0.803457E+09 | 0.137644E+10 | 0.00 | 0.00 |
| September | 0.130933E+10 | 0.154154E+10 | 0.156087E+10 | 0.503297E+09 | 0.105757E+10 | 0.00 | 0.00 |
| October | 0.550441E+09 | 0.218907E+10 | 0.104089E+10 | 0.291057E+09 | 0.749830E+09 | 0.00 | 0.00 |
| November | 76141823.69 | 0.257121E+10 | 0.523128E+09 | 78239700.91 | 0.444888E+09 | 0.00 | 0.00 |
| December | 31660527.55 | 0.303292E+10 | 0.403088E+09 | 59237846.79 | 0.343850E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.131326E+11 | 0.236239E+11 | 0.170162E+11 | 0.488089E+10 | 0.121353E+11 | 0.00 | 0.00 |
| Minimum of Months | 20713973.46 | 0.103543E+10 | 0.403088E+09 | 54783683.49 | 0.343850E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.245658E+10 | 0.303292E+10 | 0.244042E+10 | 0.803457E+09 | 0.166441E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
| February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
| March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
| April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
| May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
| June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
| July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
| August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
| September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
| October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
| November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
| December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
| Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
| Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
| Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
| February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
| March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
| April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
| May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
| June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
| July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
| August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
| September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
| October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
| November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
| December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
| Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
| February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
| March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
| April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
| May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
| June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
| July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
| August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
| September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
| October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
| November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
| December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
| Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
| February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
| March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
| April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
| May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
| June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
| July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
| August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
| September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
| October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
| November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
| December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
| Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
| February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
| March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
| April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
| May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
| June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
| July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
| August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
| September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
| October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
| November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
| December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
| Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER G WATER HEATER
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.274135E+10 | -0.258087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160479935.5 | 82.17 | 0.00 | 0.00 |
| February | 0.247950E+10 | -0.233507E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -144427982.8 | 82.17 | 0.00 | 0.00 |
| March | 0.298651E+10 | -0.282667E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159846642.9 | 82.17 | 0.00 | 0.00 |
| April | 0.261233E+10 | -0.245797E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154360635.9 | 82.17 | 0.00 | 0.00 |
| May | 0.286350E+10 | -0.270377E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159734449.0 | 82.17 | 0.00 | 0.00 |
| June | 0.184164E+10 | -0.168695E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154694870.5 | 82.17 | 0.00 | 0.00 |
| July | 0.768591E+09 | -609202485.8 | 0.00 | 0.00 | 744.00 | 0.00 | -159388780.5 | 82.17 | 0.00 | 0.00 |
| August | 0.860459E+09 | -700582937.5 | 0.00 | 0.00 | 744.00 | 0.00 | -159876056.1 | 82.17 | 0.00 | 0.00 |
| September | 0.168790E+10 | -0.153359E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154312114.8 | 82.17 | 0.00 | 0.00 |
| October | 0.274041E+10 | -0.258087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159535878.3 | 82.17 | 0.00 | 0.00 |
| November | 0.273534E+10 | -0.258087E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154467554.1 | 82.17 | 0.00 | 0.00 |
| December | 0.261751E+10 | -0.245797E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159537343.4 | 82.17 | 0.00 | 0.00 |
| Annual Sum or Average | 0.269350E+11 | -0.250544E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.188066E+10 | 82.17 | 0.00 | 0.00 |
| Minimum of Months | 0.768591E+09 | -0.282667E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -160479935.5 | 82.17 | 0.00 | 0.00 |
| Maximum of Months | 0.298651E+10 | -609202485.8 | 0.00 | 0.00 | 744.00 | 0.00 | -144427982.8 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.104062E+11 | -0.939832E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100786E+10 | 60.05 | 0.00 | 0.00 |
| February | 0.944544E+10 | -0.856201E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -883430261.3 | 60.05 | 0.00 | 0.00 |
| March | 0.111766E+11 | -0.102468E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -929782427.1 | 60.05 | 0.00 | 0.00 |
| April | 0.953640E+10 | -0.867210E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -864297741.1 | 60.05 | 0.00 | 0.00 |
| May | 0.100693E+11 | -0.919932E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -869998094.9 | 60.05 | 0.00 | 0.00 |
| June | 0.637930E+10 | -0.554362E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -835681644.2 | 60.05 | 0.00 | 0.00 |
| July | 0.281184E+10 | -0.193529E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -876549451.6 | 60.05 | 0.00 | 0.00 |
| August | 0.308933E+10 | -0.220809E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -881231469.4 | 60.05 | 0.00 | 0.00 |
| September | 0.576517E+10 | -0.492255E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -842623832.9 | 60.05 | 0.00 | 0.00 |
| October | 0.941502E+10 | -0.851423E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -900794379.1 | 60.05 | 0.00 | 0.00 |
| November | 0.976211E+10 | -0.884516E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -916952393.6 | 60.05 | 0.00 | 0.00 |
| December | 0.971571E+10 | -0.872854E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -987175522.4 | 60.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.975724E+11 | -0.867760E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.107964E+11 | 60.05 | 0.00 | 0.00 |
| Minimum of Months | 0.281184E+10 | -0.102468E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.100786E+10 | 60.05 | 0.00 | 0.00 |
| Maximum of Months | 0.111766E+11 | -0.193529E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -835681644.2 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3714.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.137646E+10 | 7101.29 | 27-JAN-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.760861E+09 | 7100.89 | 01-FEB-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.290010E+09 | 7099.61 | 13-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 76419321.85 | 7096.52 | 14-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 6404801.64 | 7095.29 | 02-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 908652.83 | 4337.79 | 14-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 7735807.61 | 7098.14 | 14-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 22532649.97 | 7100.07 | 02-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 1344518.91 | 7096.33 | 27-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 47142418.37 | 7097.00 | 27-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.437395E+09 | 7097.91 | 30-NOV-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.982865E+09 | 7098.15 | 15-DEC-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.401008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 908652.83 | 4337.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.137646E+10 | 7101.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.357875E+10 | 25294.36 | 04-JAN-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.164031E+10 | 25290.40 | 22-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.376404E+09 | 25295.51 | 10-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 61980746.79 | 25289.79 | 04-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 2273516.80 | 25284.23 | 18-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 19912950.78 | 25300.01 | 14-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 45657345.19 | 25311.60 | 18-AUG-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 1578682.02 | 16121.45 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 22232203.98 | 25291.69 | 18-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.924310E+09 | 25288.90 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.241679E+10 | 25299.51 | 28-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.909020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.357875E+10 | 25311.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.192994E+10 | 5926.73 | 03-JAN-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.911087E+09 | 5926.91 | 22-FEB-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.119171E+09 | 5925.10 | 17-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 4897256.44 | 5923.99 | 11-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 2460385.02 | 5925.43 | 30-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.372355E+09 | 5932.68 | 21-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.120484E+10 | 5926.52 | 28-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.454475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.192994E+10 | 5932.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.172451E+10 | 6506.45 | 27-JAN-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.114474E+10 | 6506.03 | 01-FEB-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.507832E+09 | 6504.86 | 13-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.140695E+09 | 6503.23 | 03-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 9507219.06 | 6505.44 | 30-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1980168.08 | 6295.83 | 06-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 22869951.75 | 6509.29 | 11-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 53769054.09 | 6509.39 | 31-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 5397240.14 | 6507.97 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.119822E+09 | 6504.92 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.601561E+09 | 6505.35 | 29-NOV-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.125208E+10 | 6503.64 | 11-DEC-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.558476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 1980168.08 | 6295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.172451E+10 | 6509.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.450116E+10 | 24248.19 | 24-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.283755E+10 | 24249.52 | 23-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.108869E+10 | 24258.81 | 13-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.183281E+09 | 24250.63 | 03-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 6001395.51 | 24235.89 | 18-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 78332561.80 | 24268.39 | 11-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.194917E+09 | 24268.68 | 31-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 18386506.04 | 24264.31 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.147391E+09 | 24249.01 | 27-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.139735E+10 | 24248.30 | 08-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.321332E+10 | 24250.65 | 28-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.136664E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.450116E+10 | 24268.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.141011E+10 | 7056.60 | 27-JAN-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.767242E+09 | 7056.20 | 01-FEB-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.294792E+09 | 7054.93 | 13-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 79572703.86 | 7051.85 | 14-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 6871504.16 | 7055.10 | 30-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1147614.80 | 4879.98 | 14-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 9871559.16 | 7053.46 | 14-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 25357594.63 | 7055.38 | 02-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 1385063.92 | 7051.66 | 27-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 48144904.72 | 7052.33 | 27-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.444146E+09 | 7053.55 | 15-NOV-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.102397E+10 | 7053.48 | 15-DEC-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.411261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 1147614.80 | 4879.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.141011E+10 | 7056.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.363312E+10 | 24945.23 | 04-JAN-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.163211E+10 | 24941.32 | 22-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.369416E+09 | 24946.34 | 10-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 59008099.09 | 24940.72 | 04-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1986578.75 | 23903.26 | 18-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 24172652.91 | 24950.77 | 14-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 49871538.21 | 24962.20 | 18-AUG-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 1963218.85 | 17367.45 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 22307929.66 | 24942.58 | 18-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.925489E+09 | 24939.83 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.252571E+10 | 24950.29 | 28-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.924515E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.363312E+10 | 24962.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.195486E+10 | 5909.77 | 03-JAN-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.912250E+09 | 5909.95 | 22-FEB-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.118909E+09 | 5908.15 | 17-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 4883269.40 | 5907.03 | 11-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 2620272.24 | 5908.47 | 30-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.375703E+09 | 5915.70 | 21-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.125715E+10 | 5909.56 | 28-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.462637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.195486E+10 | 5915.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.172866E+10 | 6509.48 | 27-JAN-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.114547E+10 | 6509.06 | 01-FEB-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.508207E+09 | 6507.89 | 13-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.140672E+09 | 6506.26 | 03-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 9486451.00 | 6508.47 | 30-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1975728.25 | 6298.77 | 06-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 23183795.10 | 6512.33 | 11-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 53981021.29 | 6512.43 | 31-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 5468437.68 | 6511.00 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.120036E+09 | 6507.95 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.603182E+09 | 6508.38 | 29-NOV-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.125880E+10 | 6506.67 | 11-DEC-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.559913E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 1975728.25 | 6298.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.172866E+10 | 6512.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.450496E+10 | 24241.51 | 24-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.283292E+10 | 24242.85 | 23-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.108349E+10 | 24252.14 | 13-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.181247E+09 | 24243.96 | 03-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 5852801.90 | 24229.22 | 18-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 77836848.75 | 24261.74 | 11-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.193134E+09 | 24262.03 | 31-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 18381454.93 | 24257.66 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.146650E+09 | 24242.34 | 27-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.139594E+10 | 24241.63 | 08-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.322797E+10 | 24243.98 | 28-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.136684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.450496E+10 | 24262.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.138686E+10 | 7061.74 | 27-JAN-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.755737E+09 | 7061.34 | 01-FEB-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.281137E+09 | 7060.07 | 13-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 73693992.75 | 7056.99 | 14-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 6270665.33 | 7055.78 | 02-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 918333.90 | 4360.16 | 14-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 7771940.51 | 7058.60 | 14-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 22047731.86 | 7060.52 | 02-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 1258767.27 | 7056.80 | 27-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 42894425.39 | 7057.47 | 27-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.427832E+09 | 7058.38 | 30-NOV-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.100053E+10 | 7058.62 | 15-DEC-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.400695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 918333.90 | 4360.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.138686E+10 | 7061.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.355290E+10 | 25041.21 | 04-JAN-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.158743E+10 | 25037.29 | 22-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.322824E+09 | 25042.32 | 10-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 49937183.26 | 25031.62 | 07-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1662562.38 | 21323.96 | 18-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 17747427.73 | 25046.76 | 14-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 39437984.69 | 25052.52 | 02-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 1212096.95 | 13822.46 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 15716351.80 | 25034.83 | 31-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.853645E+09 | 25035.78 | 01-NOV-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.242902E+10 | 25046.29 | 28-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.887154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.355290E+10 | 25052.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.186896E+10 | 5940.95 | 03-JAN-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.846079E+09 | 5941.13 | 22-FEB-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 88291338.09 | 5937.67 | 29-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 2867533.76 | 5937.73 | 18-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 1773599.05 | 5936.45 | 31-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.306445E+09 | 5946.90 | 21-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.115665E+10 | 5940.74 | 28-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.427107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.186896E+10 | 5946.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.172298E+10 | 6546.27 | 27-JAN-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.113267E+10 | 6545.84 | 01-FEB-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.484790E+09 | 6544.67 | 13-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.126222E+09 | 6543.03 | 03-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 8141215.52 | 6545.25 | 30-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 1352099.02 | 5259.08 | 06-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 15105963.34 | 6549.13 | 11-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 43640089.94 | 6549.23 | 31-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 4229540.07 | 6547.80 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.110865E+09 | 6544.73 | 26-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.588940E+09 | 6545.16 | 29-NOV-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.125272E+10 | 6543.44 | 11-DEC-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.549165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 1352099.02 | 5259.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.172298E+10 | 6549.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.300961E+10 | 16228.68 | 24-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.186560E+10 | 16229.66 | 23-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.644754E+09 | 16235.85 | 13-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 95090173.55 | 16230.44 | 03-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 2353916.53 | 16220.48 | 18-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 30812596.23 | 16242.51 | 11-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 92485691.89 | 16242.70 | 31-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 8420525.88 | 16239.74 | 01-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 81228595.79 | 16229.37 | 27-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.896124E+09 | 16228.89 | 08-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.214704E+10 | 16230.39 | 28-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.887352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.300961E+10 | 16242.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.535585E+09 | 8026.85 | 02-JAN-07:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.275620E+09 | 8025.69 | 22-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 51669910.41 | 8022.25 | 09-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 5153291.92 | 8023.38 | 10-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 292043.04 | 2517.65 | 14-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 1813540.14 | 8028.36 | 03-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 3863836.05 | 8025.04 | 31-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 71353438.68 | 8021.36 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.283373E+09 | 8027.30 | 11-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.122872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.535585E+09 | 8028.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.458174E+10 | 13087.53 | 03-JAN-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.195398E+10 | 13087.87 | 22-FEB-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 73362677.95 | 13076.57 | 02-MAR-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 784029.11 | 13067.15 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.781943E+09 | 13101.12 | 21-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.290108E+10 | 13087.19 | 28-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.102929E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.458174E+10 | 13101.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.781110E+10 | 8447.12 | 27-JAN-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.584416E+10 | 8744.07 | 28-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.540375E+10 | 8749.87 | 02-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.311096E+10 | 8756.83 | 04-APR-14:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.203309E+10 | 8761.56 | 26-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.123960E+10 | 8761.46 | 14-JUN-14:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.805040E+09 | 8451.29 | 11-JUL-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.837655E+09 | 8453.20 | 02-AUG-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.128057E+10 | 8757.19 | 25-SEP-14:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.298036E+10 | 8754.17 | 25-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.583604E+10 | 8747.98 | 03-NOV-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.704255E+10 | 8454.90 | 28-DEC-16:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.442249E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.805040E+09 | 8447.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.781110E+10 | 8761.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 64508537.42 | 4012.83 | 02-JAN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 5858358.96 | 1660.91 | 21-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 163910.08 | 305.21 | 26-DEC-06:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 70530806.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 64508537.42 | 4012.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.336040E+10 | 18719.82 | 03-JAN-07:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.136263E+10 | 18719.34 | 22-FEB-07:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 80773676.79 | 18694.13 | 13-MAR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 1952148.24 | 18686.30 | 18-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 1405840.82 | 13646.21 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.489053E+09 | 18699.75 | 21-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.205899E+10 | 18715.49 | 27-DEC-07:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.735521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.336040E+10 | 18719.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.190559E+10 | 15885.95 | 09-JAN-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.865518E+09 | 15890.04 | 21-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 77002023.89 | 15880.56 | 06-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 5854660.75 | 2365.36 | 30-OCT-06:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.304634E+09 | 15887.71 | 27-NOV-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.121632E+10 | 15890.68 | 26-DEC-06:55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.437491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.190559E+10 | 15890.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.178919E+10 | 17557.76 | 02-JAN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.725757E+09 | 17554.41 | 22-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 18225239.85 | 17176.06 | 27-MAR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 157765.37 | 2629.42 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 88749826.92 | 17524.47 | 13-NOV-07:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.862651E+09 | 17556.85 | 28-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.348473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.178919E+10 | 17557.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_POD_1 HEATING COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.558808E+11 | 159305.75 | 06-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.395033E+11 | 137437.77 | 09-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.205602E+11 | 105356.65 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.819177E+10 | 83007.58 | 18-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.139173E+10 | 56574.14 | 18-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 3125720.14 | 5122.13 | 07-JUN-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 7124102.56 | 11873.50 | 12-JUL-10:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.125859E+09 | 25350.47 | 27-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.354655E+10 | 58816.28 | 17-OCT-11:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.306344E+11 | 121783.91 | 13-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.504038E+11 | 139882.62 | 26-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.210249E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.558808E+11 | 159305.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:6 HEATING COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:7 HEATING COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.118058E+11 | 79793.61 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.843676E+10 | 79793.61 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.401372E+10 | 79793.61 | 02-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.190543E+10 | 79657.08 | 19-APR-05:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.640197E+09 | 27708.23 | 18-MAY-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.100889E+09 | 11858.03 | 14-JUN-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 6523942.83 | 8663.78 | 12-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 52782003.11 | 10371.58 | 18-AUG-07:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.188469E+09 | 19402.78 | 27-SEP-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.137717E+10 | 32398.27 | 30-OCT-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.591126E+10 | 79793.61 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.102880E+11 | 79793.61 | 04-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.447270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 6523942.83 | 8663.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.118058E+11 | 79793.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_POD_1 COOLING COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.169006E+10 | 0.162604E+10 | 127600.59 | 27-FEB-15:02 | 127600.59 | 0.00 |
| March | 0.00 | 0.00 | 0.178060E+10 | 0.153154E+10 | 72336.96 | 14-MAR-14:02 | 67854.69 | 0.00 |
| April | 0.00 | 0.00 | 0.192836E+11 | 0.188683E+11 | 334651.12 | 27-APR-15:00 | 317211.70 | 0.00 |
| May | 0.00 | 0.00 | 0.487080E+11 | 0.460150E+11 | 301002.84 | 04-MAY-15:00 | 301002.84 | 0.00 |
| June | 0.00 | 0.00 | 0.872780E+11 | 0.833748E+11 | 270181.17 | 28-JUN-15:05 | 270181.17 | 0.00 |
| July | 0.00 | 0.00 | 0.117262E+12 | 0.107228E+12 | 354646.01 | 31-JUL-14:02 | 284364.33 | 0.00 |
| August | 0.00 | 0.00 | 0.153705E+12 | 0.139034E+12 | 377600.50 | 29-AUG-14:01 | 288374.69 | 0.00 |
| September | 0.00 | 0.00 | 0.696637E+11 | 0.620663E+11 | 316572.98 | 14-SEP-14:05 | 255723.35 | 0.00 |
| October | 0.00 | 0.00 | 0.110975E+11 | 0.108076E+11 | 208816.57 | 04-OCT-14:03 | 208816.57 | 0.00 |
| November | 0.00 | 0.00 | 0.434401E+09 | 0.322641E+09 | 123094.45 | 04-NOV-13:56 | 100840.74 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.510903E+12 | 0.470874E+12 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.153705E+12 | 0.139034E+12 | 377600.50 | 317211.70 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:6 COOLING COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.100475E+09 | 66081726.60 | 29579.75 | 13-JAN-06:01 | 19857.87 | 0.00 |
| February | 0.00 | 0.00 | 0.241477E+09 | 0.187184E+09 | 29579.75 | 28-FEB-06:11 | 16318.79 | 0.00 |
| March | 0.00 | 0.00 | 0.306033E+09 | 0.213888E+09 | 29579.75 | 01-MAR-06:01 | 22507.86 | 0.00 |
| April | 0.00 | 0.00 | 0.164340E+10 | 0.139772E+10 | 30923.21 | 29-APR-14:32 | 25333.49 | 0.00 |
| May | 0.00 | 0.00 | 0.375333E+10 | 0.304217E+10 | 32098.19 | 06-MAY-12:34 | 24063.68 | 0.00 |
| June | 0.00 | 0.00 | 0.597693E+10 | 0.507060E+10 | 31225.86 | 11-JUN-11:43 | 23876.44 | 0.00 |
| July | 0.00 | 0.00 | 0.891923E+10 | 0.710305E+10 | 32524.85 | 15-JUL-17:45 | 21606.00 | 0.00 |
| August | 0.00 | 0.00 | 0.120843E+11 | 0.940278E+10 | 32394.28 | 26-AUG-16:53 | 19864.82 | 0.00 |
| September | 0.00 | 0.00 | 0.475492E+10 | 0.349157E+10 | 32590.10 | 23-SEP-13:57 | 22001.07 | 0.00 |
| October | 0.00 | 0.00 | 0.783097E+09 | 0.658211E+09 | 30432.49 | 08-OCT-13:52 | 23886.98 | 0.00 |
| November | 0.00 | 0.00 | 0.196915E+09 | 0.123866E+09 | 31519.16 | 04-NOV-13:42 | 22062.33 | 0.00 |
| December | 0.00 | 0.00 | 0.134985E+09 | 88810322.46 | 29579.75 | 05-DEC-06:01 | 19192.61 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.388951E+11 | 0.308459E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.100475E+09 | 66081726.60 | 29579.75 | 16318.79 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.120843E+11 | 0.940278E+10 | 32590.10 | 25333.49 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:7 COOLING COIL
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 48096315.45 | 44749561.69 | 10424.96 | 27-FEB-15:00 | 10074.94 | 0.00 |
| March | 0.00 | 0.00 | 9260267.68 | 6964133.03 | 1871.31 | 10-MAR-13:00 | 1387.62 | 0.00 |
| April | 0.00 | 0.00 | 0.147392E+10 | 0.134848E+10 | 39677.50 | 27-APR-14:00 | 33454.26 | 0.00 |
| May | 0.00 | 0.00 | 0.330467E+10 | 0.275338E+10 | 56662.20 | 06-MAY-11:51 | 42382.93 | 0.00 |
| June | 0.00 | 0.00 | 0.729616E+10 | 0.627203E+10 | 55765.31 | 11-JUN-12:01 | 42388.61 | 0.00 |
| July | 0.00 | 0.00 | 0.583624E+10 | 0.495582E+10 | 55850.99 | 22-JUL-11:21 | 44032.81 | 0.00 |
| August | 0.00 | 0.00 | 0.101944E+11 | 0.873971E+10 | 55803.13 | 30-AUG-05:01 | 27488.12 | 0.00 |
| September | 0.00 | 0.00 | 0.583171E+10 | 0.426847E+10 | 58084.48 | 23-SEP-14:02 | 39029.33 | 0.00 |
| October | 0.00 | 0.00 | 0.405435E+09 | 0.391596E+09 | 18235.52 | 04-OCT-14:00 | 18235.52 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.343998E+11 | 0.287812E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.101944E+11 | 0.873971E+10 | 58084.48 | 44032.81 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 21465.88 | 475888.93 | 17-JAN-06:01 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 13053.63 | 436480.37 | 10-FEB-07:01 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 4548.25 | 419556.15 | 06-MAR-07:11 |
| April | 0.00 | 0.00 | 01-APR-00:05 | 1685.19 | 337393.40 | 18-APR-07:01 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 775.89 | 199848.33 | 18-MAY-07:01 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 475.95 | 34751.70 | 14-JUN-07:01 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 420.91 | 210110.60 | 14-JUL-07:01 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 617.42 | 240736.81 | 18-AUG-07:01 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 515.71 | 147135.17 | 01-SEP-07:01 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 1443.62 | 337248.88 | 30-OCT-07:01 |
| November | 0.00 | 0.00 | 01-NOV-00:05 | 6940.47 | 405220.86 | 24-NOV-07:01 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 15088.11 | 467783.07 | 26-DEC-06:11 |
| Annual Sum or Average | 0.00 | 5559.41 | ||||
| Minimum of Months | 0.00 | 0.00 | 420.91 | 34751.70 | ||
| Maximum of Months | 0.00 | 0.00 | 21465.88 | 475888.93 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 3497.44 | 17840.47 | 31-JAN-13:50 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 3527.68 | 17862.27 | 10-FEB-13:40 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 3813.13 | 17800.62 | 01-MAR-13:20 |
| April | 0.00 | 0.00 | 01-APR-00:05 | 3334.47 | 17401.43 | 03-APR-12:20 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 3422.73 | 16857.67 | 01-MAY-12:40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 2128.36 | 16192.06 | 01-JUN-12:30 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 715.07 | 4690.54 | 03-JUL-18:25 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 815.80 | 4621.76 | 31-AUG-19:00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 1889.75 | 15733.55 | 29-SEP-12:30 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 3167.56 | 16344.78 | 31-OCT-12:20 |
| November | 0.00 | 0.00 | 01-NOV-00:05 | 3400.73 | 16989.33 | 30-NOV-13:20 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 3247.96 | 17516.79 | 29-DEC-14:00 |
| Annual Sum or Average | 0.00 | 2740.94 | ||||
| Minimum of Months | 0.00 | 0.00 | 715.07 | 4621.76 | ||
| Maximum of Months | 0.00 | 0.00 | 3813.13 | 17862.27 |
Report: FanReportMonthly
For: VAV_POD_1 FAN
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.213307E+11 | 0.51 | 19594.84 | 02-JAN-07:11 | 1.10 |
| February | 0.171967E+11 | 0.46 | 19594.84 | 21-FEB-07:01 | 1.10 |
| March | 0.180652E+11 | 0.43 | 20664.96 | 02-MAR-15:13 | 1.12 |
| April | 0.178735E+11 | 0.41 | 43220.54 | 27-APR-14:00 | 1.52 |
| May | 0.248312E+11 | 0.51 | 47308.02 | 04-MAY-14:10 | 1.58 |
| June | 0.271921E+11 | 0.57 | 42333.89 | 09-JUN-14:10 | 1.52 |
| July | 0.202940E+11 | 0.46 | 25859.23 | 24-JUL-13:10 | 1.22 |
| August | 0.218128E+11 | 0.49 | 26394.78 | 10-AUG-13:10 | 1.23 |
| September | 0.219382E+11 | 0.47 | 42058.89 | 22-SEP-14:30 | 1.50 |
| October | 0.185270E+11 | 0.41 | 41268.74 | 04-OCT-14:10 | 1.50 |
| November | 0.165489E+11 | 0.41 | 19380.50 | 13-NOV-07:01 | 1.09 |
| December | 0.171716E+11 | 0.41 | 19594.84 | 26-DEC-06:11 | 1.10 |
| Annual Sum or Average | 0.242782E+12 | 0.46 | |||
| Minimum of Months | 0.165489E+11 | 0.41 | 19380.50 | 1.09 | |
| Maximum of Months | 0.271921E+11 | 0.57 | 47308.02 | 1.58 |
Report: FanReportMonthly
For: BATH_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
| May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 |
| August | 0.00 | -0.0 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: GYM_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | -0.0 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 |
| August | 0.00 | -0.0 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
| May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 |
| August | 0.00 | -0.0 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
| December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | -0.0 | 0.00 | 01-APR-00:05 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | -0.0 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | -0.0 |
| November | 0.00 | -0.0 | 0.00 | 01-NOV-00:05 | 0.00 |
| December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: CAFETERIA_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:05 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | -0.0 | 0.00 | 01-JUL-00:03 | 0.00 |
| August | 0.00 | -0.0 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:10 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 |
| December | 0.00 | -0.0 | 0.00 | 01-DEC-00:10 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.277374E+10 | 0.64 | 2582.38 | 02-JAN-08:00 | 1.36 |
| February | 0.255381E+10 | 0.77 | 2582.38 | 01-FEB-07:01 | 1.38 |
| March | 0.314909E+10 | 0.99 | 2582.38 | 03-MAR-07:01 | 1.38 |
| April | 0.291508E+10 | 1.09 | 2582.38 | 05-APR-10:40 | 1.38 |
| May | 0.329612E+10 | 1.11 | 2582.38 | 01-MAY-12:05 | 1.37 |
| June | 0.342147E+10 | 1.11 | 2582.38 | 01-JUN-09:30 | 1.38 |
| July | 0.331105E+10 | 1.09 | 2582.38 | 03-JUL-11:05 | 1.38 |
| August | 0.366515E+10 | 1.11 | 2582.38 | 01-AUG-13:40 | 1.37 |
| September | 0.312355E+10 | 1.11 | 2582.38 | 07-SEP-15:10 | 1.38 |
| October | 0.303556E+10 | 1.10 | 2582.38 | 02-OCT-14:03 | 1.38 |
| November | 0.289170E+10 | 0.91 | 2582.38 | 07-NOV-07:13 | 1.38 |
| December | 0.266789E+10 | 0.69 | 2582.38 | 05-DEC-07:01 | 1.37 |
| Annual Sum or Average | 0.368042E+11 | 0.98 | |||
| Minimum of Months | 0.255381E+10 | 0.64 | 2582.38 | 1.36 | |
| Maximum of Months | 0.366515E+10 | 1.11 | 2582.38 | 1.38 |
Report: FanReportMonthly
For: PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.460435E+10 | 0.56 | 4291.96 | 02-JAN-07:03 | 1.35 |
| February | 0.414799E+10 | 0.55 | 4291.96 | 01-FEB-08:06 | 1.35 |
| March | 0.498241E+10 | 0.59 | 4291.96 | 01-MAR-08:03 | 1.35 |
| April | 0.432678E+10 | 0.52 | 4291.96 | 03-APR-07:06 | 1.34 |
| May | 0.476825E+10 | 0.56 | 4291.96 | 01-MAY-06:30 | 1.34 |
| June | 0.480607E+10 | 0.61 | 4291.96 | 07-JUN-12:05 | 1.34 |
| July | 0.438434E+10 | 0.55 | 4291.96 | 03-JUL-06:04 | 1.34 |
| August | 0.502381E+10 | 0.61 | 4291.96 | 01-AUG-15:20 | 1.34 |
| September | 0.433278E+10 | 0.53 | 4291.96 | 01-SEP-06:35 | 1.34 |
| October | 0.454277E+10 | 0.53 | 4291.96 | 02-OCT-06:30 | 1.34 |
| November | 0.455388E+10 | 0.56 | 4291.96 | 02-NOV-07:07 | 1.34 |
| December | 0.436897E+10 | 0.53 | 4291.96 | 01-DEC-08:07 | 1.35 |
| Annual Sum or Average | 0.548424E+11 | 0.56 | |||
| Minimum of Months | 0.414799E+10 | 0.52 | 4291.96 | 1.34 | |
| Maximum of Months | 0.502381E+10 | 0.61 | 4291.96 | 1.35 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 0.243580E+09 | 0.219222E+09 | 785.10 | 17-JAN-07:01 | 706.59 | 706.59 | 48.57 | 2.51 |
| February | 0.141150E+09 | 0.127035E+09 | 780.81 | 21-FEB-07:07 | 702.73 | 702.73 | 55.24 | 2.49 |
| March | 69720883.30 | 62748794.97 | 738.62 | 06-MAR-07:12 | 664.76 | 664.76 | 48.09 | 2.37 |
| April | 29326894.06 | 26394204.65 | 672.41 | 18-APR-07:01 | 605.17 | 605.17 | 43.18 | 2.08 |
| May | 16218530.86 | 14596677.77 | 620.66 | 18-MAY-07:01 | 558.60 | 558.60 | 52.49 | 1.62 |
| June | 9921145.39 | 8929030.85 | 256.12 | 14-JUN-07:01 | 230.51 | 230.51 | 55.14 | 0.31 |
| July | 7513298.01 | 6761968.21 | 626.97 | 14-JUL-07:01 | 564.27 | 564.27 | 52.29 | 1.69 |
| August | 9581824.65 | 8623642.19 | 632.47 | 03-AUG-07:01 | 569.22 | 569.22 | 50.40 | 1.75 |
| September | 10265058.12 | 9238552.30 | 577.55 | 01-SEP-07:01 | 519.80 | 519.80 | 52.73 | 1.20 |
| October | 26521198.73 | 23869078.86 | 695.13 | 30-OCT-07:01 | 625.62 | 625.62 | 45.30 | 2.20 |
| November | 92428015.41 | 83185213.87 | 743.04 | 13-NOV-07:03 | 668.74 | 668.74 | 53.08 | 2.38 |
| December | 0.178145E+09 | 0.160330E+09 | 780.82 | 26-DEC-07:08 | 702.73 | 702.73 | 55.25 | 2.49 |
| Annual Sum or Average | 0.834372E+09 | 0.750935E+09 | ||||||
| Minimum of Months | 7513298.01 | 6761968.21 | 256.12 | 230.51 | 230.51 | 43.18 | 0.31 | |
| Maximum of Months | 0.243580E+09 | 0.219222E+09 | 785.10 | 706.59 | 706.59 | 55.25 | 2.51 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 12215899.87 | 3664769.96 | 13.47 | 02-JAN-08:61 | 4.04 | 4.04 | 53.99 | 0.11 |
| February | 11052480.83 | 3315744.25 | 13.47 | 01-FEB-08:61 | 4.04 | 4.04 | 46.23 | 0.11 |
| March | 13379318.90 | 4013795.67 | 13.47 | 01-MAR-08:61 | 4.04 | 4.04 | 46.26 | 0.11 |
| April | 11634190.35 | 3490257.10 | 13.47 | 03-APR-07:01 | 4.04 | 4.04 | 46.55 | 0.11 |
| May | 12797609.38 | 3839282.82 | 13.47 | 01-MAY-07:01 | 4.04 | 4.04 | 46.96 | 0.11 |
| June | 12797609.38 | 3839282.82 | 13.47 | 01-JUN-07:01 | 4.04 | 4.04 | 47.49 | 0.11 |
| July | 11634190.35 | 3490257.10 | 13.47 | 03-JUL-07:01 | 4.04 | 4.04 | 51.70 | 0.11 |
| August | 13379318.90 | 4013795.67 | 13.47 | 01-AUG-07:01 | 4.04 | 4.04 | 51.86 | 0.11 |
| September | 11634190.35 | 3490257.10 | 13.47 | 01-SEP-07:01 | 4.04 | 4.04 | 52.23 | 0.11 |
| October | 12215899.87 | 3664769.96 | 13.47 | 02-OCT-07:01 | 4.04 | 4.04 | 47.84 | 0.11 |
| November | 12215899.87 | 3664769.96 | 13.47 | 01-NOV-07:01 | 4.04 | 4.04 | 47.26 | 0.11 |
| December | 11634190.35 | 3490257.10 | 13.47 | 01-DEC-08:61 | 4.04 | 4.04 | 46.88 | 0.11 |
| Annual Sum or Average | 0.146591E+09 | 43977239.52 | ||||||
| Minimum of Months | 11052480.83 | 3315744.25 | 13.47 | 4.04 | 4.04 | 46.23 | 0.11 | |
| Maximum of Months | 13379318.90 | 4013795.67 | 13.47 | 4.04 | 4.04 | 53.99 | 0.11 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 26.81 | 26.81 | 21465.88 | 475888.93 | 17-JAN-06:01 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 27.83 | 27.83 | 13053.63 | 436480.37 | 10-FEB-07:01 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 24.18 | 24.18 | 4548.25 | 419556.15 | 06-MAR-07:11 |
| April | 0.00 | 0.00 | 01-APR-00:05 | 22.52 | 22.52 | 1685.19 | 337393.40 | 18-APR-07:01 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 48.19 | 48.19 | 775.89 | 199848.33 | 18-MAY-07:01 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 51.81 | 51.81 | 475.95 | 34751.70 | 14-JUN-07:01 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 52.23 | 52.23 | 420.91 | 210110.60 | 14-JUL-07:01 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 50.32 | 50.32 | 617.42 | 240736.81 | 18-AUG-07:01 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 41.29 | 41.29 | 515.71 | 147135.17 | 01-SEP-07:01 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 45.17 | 45.17 | 1443.62 | 337248.88 | 30-OCT-07:01 |
| November | 0.00 | 0.00 | 01-NOV-00:05 | 22.41 | 22.41 | 6940.47 | 405220.86 | 24-NOV-07:01 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 27.14 | 27.14 | 15088.11 | 467783.07 | 26-DEC-06:11 |
| Annual Sum or Average | 0.00 | 5559.41 | ||||||
| Minimum of Months | 0.00 | 0.00 | 22.41 | 22.41 | 420.91 | 34751.70 | ||
| Maximum of Months | 0.00 | 0.00 | 52.23 | 52.23 | 21465.88 | 475888.93 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:05 | 60.00 | 60.00 | 3497.44 | 17840.47 | 31-JAN-13:50 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 47.85 | 47.85 | 3527.68 | 17862.27 | 10-FEB-13:40 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 47.87 | 47.87 | 3813.13 | 17800.62 | 01-MAR-13:20 |
| April | 0.00 | 0.00 | 01-APR-00:05 | 48.11 | 48.11 | 3334.47 | 17401.43 | 03-APR-12:20 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 48.47 | 48.47 | 3422.73 | 16857.67 | 01-MAY-12:40 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 48.96 | 48.96 | 2128.36 | 16192.06 | 01-JUN-12:30 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 49.33 | 49.33 | 715.07 | 4690.54 | 03-JUL-18:25 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 49.54 | 49.54 | 815.80 | 4621.76 | 31-AUG-19:00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 49.51 | 49.51 | 1889.75 | 15733.55 | 29-SEP-12:30 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 49.28 | 49.28 | 3167.56 | 16344.78 | 31-OCT-12:20 |
| November | 0.00 | 0.00 | 01-NOV-00:05 | 48.87 | 48.87 | 3400.73 | 16989.33 | 30-NOV-13:20 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 48.43 | 48.43 | 3247.96 | 17516.79 | 29-DEC-14:00 |
| Annual Sum or Average | 0.00 | 2740.94 | ||||||
| Minimum of Months | 0.00 | 0.00 | 47.85 | 47.85 | 715.07 | 4621.76 | ||
| Maximum of Months | 0.00 | 0.00 | 60.00 | 60.00 | 3813.13 | 17862.27 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_POD_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.579319E+11 | 0.00 | 0.00 | 0.213307E+11 | 0.00 | 0.00 |
| February | 0.318056E+11 | 0.00 | 0.00 | 0.177026E+11 | 0.00 | 0.00 |
| March | 0.122835E+11 | 0.00 | 0.00 | 0.186247E+11 | 0.00 | 0.00 |
| April | 0.439853E+10 | 0.00 | 0.00 | 0.231133E+11 | 0.00 | 0.00 |
| May | 0.209990E+10 | 0.00 | 0.00 | 0.382105E+11 | 0.00 | 0.00 |
| June | 0.124788E+10 | 0.00 | 0.00 | 0.513198E+11 | 0.00 | 0.00 |
| July | 0.114069E+10 | 0.00 | 0.00 | 0.521589E+11 | 0.00 | 0.00 |
| August | 0.167630E+10 | 0.00 | 0.00 | 0.626730E+11 | 0.00 | 0.00 |
| September | 0.134959E+10 | 0.00 | 0.00 | 0.410081E+11 | 0.00 | 0.00 |
| October | 0.392371E+10 | 0.00 | 0.00 | 0.217408E+11 | 0.00 | 0.00 |
| November | 0.181222E+11 | 0.00 | 0.00 | 0.166712E+11 | 0.00 | 0.00 |
| December | 0.407146E+11 | 0.00 | 0.00 | 0.171716E+11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.176694E+12 | 0.00 | 0.00 | 0.381725E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.114069E+10 | 0.00 | 0.00 | 0.166712E+11 | 0.00 | 0.00 |
| Maximum of Months | 0.579319E+11 | 0.00 | 0.00 | 0.626730E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:6
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.279970E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.261649E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.322956E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.332085E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.419899E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.487042E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.548701E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.660759E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.426263E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.323536E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.294302E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.270358E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.462752E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.261649E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.660759E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:7
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.460435E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.416135E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.498513E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.470383E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.560215E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.664964E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.594138E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.772503E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.577398E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.465098E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.455388E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.436897E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.637207E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.416135E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.772503E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_POD_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.213307E+11 | 0.00 | 0.113813E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.171967E+11 | 0.169006E+10 | 0.713089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.180652E+11 | 0.178060E+10 | 0.328437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.178735E+11 | 0.192836E+11 | 0.125903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.248312E+11 | 0.487080E+11 | 0.349163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.271921E+11 | 0.872780E+11 | 0.125101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.202940E+11 | 0.117262E+12 | 0.114781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.218128E+11 | 0.153705E+12 | 0.167630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.219382E+11 | 0.696637E+11 | 0.147545E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.185270E+11 | 0.110975E+11 | 0.747026E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.165489E+11 | 0.434401E+09 | 0.487566E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.171716E+11 | 0.00 | 0.911184E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.242782E+12 | 0.510903E+12 | 0.386943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.165489E+11 | 0.00 | 0.114781E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.271921E+11 | 0.153705E+12 | 0.113813E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:6
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.277374E+10 | 0.100475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.255381E+10 | 0.241477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.314909E+10 | 0.306033E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.291508E+10 | 0.164340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.329612E+10 | 0.375333E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.342147E+10 | 0.597693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.331105E+10 | 0.891923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.366515E+10 | 0.120843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.312355E+10 | 0.475492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.303556E+10 | 0.783097E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.289170E+10 | 0.196915E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.266789E+10 | 0.134985E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.368042E+11 | 0.388951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.255381E+10 | 0.100475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.366515E+10 | 0.120843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:7
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.460435E+10 | 0.00 | 0.118058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.414799E+10 | 48096315.45 | 0.843676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.498241E+10 | 9260267.68 | 0.401372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.432678E+10 | 0.147392E+10 | 0.190543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.476825E+10 | 0.330467E+10 | 0.640197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.480607E+10 | 0.729616E+10 | 0.100889E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.438434E+10 | 0.583624E+10 | 6523942.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.502381E+10 | 0.101944E+11 | 52782003.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.433278E+10 | 0.583171E+10 | 0.188469E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.454277E+10 | 0.405435E+09 | 0.137717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.455388E+10 | 0.00 | 0.591126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.436897E+10 | 0.00 | 0.102880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.548424E+11 | 0.343998E+11 | 0.447270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.414799E+10 | 0.00 | 6523942.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.502381E+10 | 0.101944E+11 | 0.118058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_POD_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.213307E+11 | 0.579319E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.171967E+11 | 0.318056E+11 | 0.00 | 0.00 | 0.505890E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.180652E+11 | 0.122835E+11 | 0.00 | 0.00 | 0.559536E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.178735E+11 | 0.439853E+10 | 0.00 | 0.00 | 0.523981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.248312E+11 | 0.209990E+10 | 0.00 | 0.00 | 0.133793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.271921E+11 | 0.124788E+10 | 0.00 | 0.00 | 0.241277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.202940E+11 | 0.114069E+10 | 0.00 | 0.00 | 0.318648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.218128E+11 | 0.167630E+10 | 0.00 | 0.00 | 0.408602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.219382E+11 | 0.134959E+10 | 0.00 | 0.00 | 0.190698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.185270E+11 | 0.392371E+10 | 0.00 | 0.00 | 0.321378E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.165489E+11 | 0.181222E+11 | 0.00 | 0.00 | 0.122320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.171716E+11 | 0.407146E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.242782E+12 | 0.176694E+12 | 0.00 | 0.00 | 0.138943E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.165489E+11 | 0.114069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.271921E+11 | 0.579319E+11 | 0.00 | 0.00 | 0.408602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:6
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.277374E+10 | 0.00 | 0.00 | 0.00 | 25952124.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.255381E+10 | 0.00 | 0.00 | 0.00 | 62682721.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.314909E+10 | 0.00 | 0.00 | 0.00 | 80472230.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.291508E+10 | 0.00 | 0.00 | 0.00 | 0.405764E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.329612E+10 | 0.00 | 0.00 | 0.00 | 0.902875E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.342147E+10 | 0.00 | 0.00 | 0.00 | 0.144896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.331105E+10 | 0.00 | 0.00 | 0.00 | 0.217596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.366515E+10 | 0.00 | 0.00 | 0.00 | 0.294243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.312355E+10 | 0.00 | 0.00 | 0.00 | 0.113908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.303556E+10 | 0.00 | 0.00 | 0.00 | 0.199801E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.289170E+10 | 0.00 | 0.00 | 0.00 | 51315279.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.266789E+10 | 0.00 | 0.00 | 0.00 | 35689457.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.368042E+11 | 0.00 | 0.00 | 0.00 | 0.947098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.255381E+10 | 0.00 | 0.00 | 0.00 | 25952124.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.366515E+10 | 0.00 | 0.00 | 0.00 | 0.294243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:7
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.460435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.414799E+10 | 0.00 | 0.00 | 0.00 | 13359319.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.498241E+10 | 0.00 | 0.00 | 0.00 | 2721800.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.432678E+10 | 0.00 | 0.00 | 0.00 | 0.377052E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.476825E+10 | 0.00 | 0.00 | 0.00 | 0.833896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.480607E+10 | 0.00 | 0.00 | 0.00 | 0.184357E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.438434E+10 | 0.00 | 0.00 | 0.00 | 0.155705E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.502381E+10 | 0.00 | 0.00 | 0.00 | 0.270122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.433278E+10 | 0.00 | 0.00 | 0.00 | 0.144120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.454277E+10 | 0.00 | 0.00 | 0.00 | 0.108218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.455388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.436897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.548424E+11 | 0.00 | 0.00 | 0.00 | 0.887829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.414799E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.502381E+10 | 0.00 | 0.00 | 0.00 | 0.270122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.308503E+10 | 0.00 | 0.00 | 5069.08 | 0.00 | 0.114094E+10 | 26250128.35 | 0.00 | 0.68 |
| February | 0.281000E+10 | 0.00 | 0.00 | 297309.91 | 0.00 | 0.510938E+09 | 0.354662E+09 | 0.00 | 0.70 |
| March | 0.305859E+10 | 0.00 | 0.00 | 1039868.17 | 0.00 | 72223170.13 | 0.948604E+09 | 0.00 | 0.78 |
| April | 0.168109E+10 | 2282528.88 | 0.00 | 2381991.18 | 0.00 | 22823691.15 | 0.177148E+10 | 0.00 | 0.82 |
| May | 0.134517E+10 | 0.00 | 0.00 | 4340404.72 | 1567104.06 | 2270768.95 | 0.258159E+10 | 0.00 | 1.15 |
| June | 0.132153E+10 | 7335565.41 | 0.00 | 3831184.79 | 1352558.38 | 569141.47 | 0.185136E+10 | 0.00 | 1.33 |
| July | 0.103196E+10 | 0.107810E+09 | 0.00 | 646519.58 | 11024211.36 | 1882317.52 | 0.189369E+09 | 0.00 | 1.04 |
| August | 0.897875E+09 | 0.295763E+09 | 0.00 | 393345.45 | 21486985.67 | 1376831.77 | 63243564.92 | 0.00 | 1.08 |
| September | 0.998212E+09 | 537557.07 | 0.00 | 4035285.89 | 1538940.25 | 652169.05 | 0.173901E+10 | 0.00 | 1.17 |
| October | 0.174984E+10 | 0.00 | 0.00 | 2705212.53 | 0.00 | 4492724.62 | 0.204594E+10 | 0.00 | 0.90 |
| November | 0.323541E+10 | 0.00 | 0.00 | 313566.89 | 0.00 | 0.115953E+09 | 0.523488E+09 | 0.00 | 0.71 |
| December | 0.312062E+10 | 0.00 | 0.00 | 62819.80 | 0.00 | 0.670101E+09 | 0.156692E+09 | 0.00 | 0.62 |
| Annual Sum or Average | 0.243353E+11 | 0.413728E+09 | 0.00 | 20052578.00 | 36969799.72 | 0.254423E+10 | 0.122517E+11 | 0.00 | 0.92 |
| Minimum of Months | 0.897875E+09 | 0.00 | 0.00 | 5069.08 | 0.00 | 569141.47 | 26250128.35 | 0.00 | 0.62 |
| Maximum of Months | 0.323541E+10 | 0.295763E+09 | 0.00 | 4340404.72 | 21486985.67 | 0.114094E+10 | 0.258159E+10 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.182366E+11 | 0.00 | 0.00 | 142528.55 | 0.00 | 0.171586E+10 | 0.505387E+09 | 0.00 | 0.68 |
| February | 0.135844E+11 | 0.00 | 0.00 | 3446525.23 | 0.00 | 0.577223E+09 | 0.353685E+10 | 0.00 | 0.70 |
| March | 0.116984E+11 | 0.00 | 0.00 | 8514676.27 | 0.00 | 66248472.77 | 0.807138E+10 | 0.00 | 0.78 |
| April | 0.663582E+10 | 8750437.26 | 0.00 | 14713994.45 | 0.00 | 18749352.33 | 0.104137E+11 | 0.00 | 0.83 |
| May | 0.559954E+10 | 0.00 | 0.00 | 22431995.47 | 7545424.04 | 1802916.46 | 0.136543E+11 | 0.00 | 1.15 |
| June | 0.584757E+10 | 26398901.34 | 0.00 | 18280957.53 | 6512411.50 | 0.00 | 0.960562E+10 | 0.00 | 1.32 |
| July | 0.544341E+10 | 0.354772E+09 | 0.00 | 741230.17 | 0.155391E+09 | 6377175.58 | 0.441000E+09 | 0.00 | 1.03 |
| August | 0.442725E+10 | 0.114331E+10 | 0.00 | 1015788.54 | 0.171103E+09 | 6041697.52 | 0.188790E+09 | 0.00 | 1.04 |
| September | 0.426237E+10 | 2200901.81 | 0.00 | 19501655.67 | 7409818.60 | 530938.62 | 0.897254E+10 | 0.00 | 1.14 |
| October | 0.588031E+10 | 0.00 | 0.00 | 17110104.19 | 0.00 | 9162754.02 | 0.127589E+11 | 0.00 | 0.91 |
| November | 0.134337E+11 | 0.00 | 0.00 | 3780604.31 | 0.00 | 0.113985E+09 | 0.512543E+10 | 0.00 | 0.71 |
| December | 0.164855E+11 | 0.00 | 0.00 | 1215637.95 | 0.00 | 0.806655E+09 | 0.169903E+10 | 0.00 | 0.62 |
| Annual Sum or Average | 0.111535E+12 | 0.153543E+10 | 0.00 | 0.110896E+09 | 0.347961E+09 | 0.332264E+10 | 0.749729E+11 | 0.00 | 0.91 |
| Minimum of Months | 0.426237E+10 | 0.00 | 0.00 | 142528.55 | 0.00 | 0.00 | 0.188790E+09 | 0.00 | 0.62 |
| Maximum of Months | 0.182366E+11 | 0.114331E+10 | 0.00 | 22431995.47 | 0.171103E+09 | 0.171586E+10 | 0.136543E+11 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.102395E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151143E+10 | 0.00 | 0.00 | 0.21 |
| February | 0.141480E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.735577E+09 | 0.00 | 0.00 | 0.21 |
| March | 0.228022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58044536.95 | 0.00 | 0.00 | 0.23 |
| April | 0.160656E+10 | 1541334.53 | 0.00 | 629804.15 | 0.00 | 2372884.79 | 0.359047E+09 | 0.00 | 0.24 |
| May | 0.872047E+09 | 0.00 | 0.00 | 3109263.04 | 905158.32 | 0.00 | 0.156112E+10 | 0.00 | 0.38 |
| June | 0.687531E+09 | 6063885.88 | 0.00 | 3352817.29 | 781236.87 | 0.00 | 0.135871E+10 | 0.00 | 0.46 |
| July | 0.676505E+09 | 58276454.73 | 0.00 | 127144.28 | 13582912.89 | 0.00 | 30344790.85 | 0.00 | 0.31 |
| August | 0.534204E+09 | 0.147331E+09 | 0.00 | 156016.41 | 33258657.56 | 0.00 | 22437029.29 | 0.00 | 0.32 |
| September | 0.742195E+09 | 335296.02 | 0.00 | 2352884.68 | 896587.75 | 0.00 | 0.874253E+09 | 0.00 | 0.36 |
| October | 0.157085E+10 | 0.00 | 0.00 | 980115.88 | 0.00 | 973883.68 | 0.560552E+09 | 0.00 | 0.26 |
| November | 0.196145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281135E+09 | 0.00 | 0.00 | 0.21 |
| December | 0.133752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984702E+09 | 0.00 | 0.00 | 0.19 |
| Annual Sum or Average | 0.147078E+11 | 0.213548E+09 | 0.00 | 10708045.74 | 49424553.38 | 0.357424E+10 | 0.476647E+10 | 0.00 | 0.28 |
| Minimum of Months | 0.534204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
| Maximum of Months | 0.228022E+10 | 0.147331E+09 | 0.00 | 3352817.29 | 33258657.56 | 0.151143E+10 | 0.156112E+10 | 0.00 | 0.46 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.268665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155803E+10 | 0.00 | 0.00 | 0.68 |
| February | 0.271773E+10 | 0.00 | 0.00 | 7842.23 | 0.00 | 0.911766E+09 | 36349847.82 | 0.00 | 0.69 |
| March | 0.377154E+10 | 0.00 | 0.00 | 31659.57 | 0.00 | 0.142117E+09 | 0.123435E+09 | 0.00 | 0.77 |
| April | 0.249330E+10 | 1566507.39 | 0.00 | 700116.38 | 0.00 | 37243283.79 | 0.811900E+09 | 0.00 | 0.77 |
| May | 0.154905E+10 | 0.00 | 0.00 | 2962887.77 | 1565788.60 | 2906993.19 | 0.211747E+10 | 0.00 | 1.06 |
| June | 0.153089E+10 | 6142154.58 | 0.00 | 2578671.83 | 1351423.01 | 1052442.90 | 0.151445E+10 | 0.00 | 1.26 |
| July | 0.119706E+10 | 65718389.46 | 0.00 | 36685.90 | 39093310.18 | 2830069.18 | 22653337.39 | 0.00 | 1.03 |
| August | 0.943959E+09 | 0.137819E+09 | 0.00 | 33822.52 | 0.130986E+09 | 2920801.51 | 12080268.08 | 0.00 | 1.04 |
| September | 0.141784E+10 | 304253.27 | 0.00 | 1647145.82 | 1550962.79 | 1718798.83 | 0.111129E+10 | 0.00 | 1.02 |
| October | 0.247386E+10 | 0.00 | 0.00 | 847025.19 | 0.00 | 16433582.94 | 0.101938E+10 | 0.00 | 0.81 |
| November | 0.329015E+10 | 0.00 | 0.00 | 28387.07 | 0.00 | 0.375658E+09 | 0.204456E+09 | 0.00 | 0.71 |
| December | 0.274402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119697E+10 | 0.00 | 0.00 | 0.62 |
| Annual Sum or Average | 0.268161E+11 | 0.211551E+09 | 0.00 | 8874244.27 | 0.174548E+09 | 0.424965E+10 | 0.697346E+10 | 0.00 | 0.87 |
| Minimum of Months | 0.943959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1052442.90 | 0.00 | 0.00 | 0.62 |
| Maximum of Months | 0.377154E+10 | 0.137819E+09 | 0.00 | 2962887.77 | 0.130986E+09 | 0.155803E+10 | 0.211747E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.178374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261876E+10 | 0.00 | 0.00 | 0.68 |
| February | 0.158717E+11 | 0.00 | 0.00 | 104394.06 | 0.00 | 0.133487E+10 | 0.460398E+09 | 0.00 | 0.70 |
| March | 0.165532E+11 | 0.00 | 0.00 | 705134.81 | 0.00 | 0.113353E+09 | 0.279099E+10 | 0.00 | 0.77 |
| April | 0.915546E+10 | 6962738.73 | 0.00 | 5188911.74 | 0.00 | 29380324.12 | 0.692022E+10 | 0.00 | 0.77 |
| May | 0.690955E+10 | 0.00 | 0.00 | 15732664.20 | 7547840.23 | 3938812.69 | 0.109006E+11 | 0.00 | 1.06 |
| June | 0.736685E+10 | 24409139.79 | 0.00 | 11518173.33 | 6514496.89 | 0.00 | 0.745875E+10 | 0.00 | 1.26 |
| July | 0.587828E+10 | 7737852.98 | 0.00 | 0.00 | 0.497504E+09 | 14844066.48 | 0.00 | 0.00 | 1.03 |
| August | 0.460908E+10 | 0.00 | 0.00 | 0.00 | 0.129104E+10 | 13529228.14 | 0.00 | 0.00 | 1.04 |
| September | 0.687241E+10 | 1260969.84 | 0.00 | 7324584.97 | 7546961.33 | 1296701.51 | 0.534880E+10 | 0.00 | 1.02 |
| October | 0.926805E+10 | 0.00 | 0.00 | 5959462.04 | 0.00 | 17950232.90 | 0.763406E+10 | 0.00 | 0.81 |
| November | 0.157995E+11 | 0.00 | 0.00 | 882636.22 | 0.00 | 0.164345E+09 | 0.268997E+10 | 0.00 | 0.71 |
| December | 0.180104E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982726E+09 | 0.00 | 0.00 | 0.62 |
| Annual Sum or Average | 0.134132E+12 | 40370701.34 | 0.00 | 47415961.36 | 0.181016E+10 | 0.529499E+10 | 0.442038E+11 | 0.00 | 0.87 |
| Minimum of Months | 0.460908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
| Maximum of Months | 0.180104E+11 | 24409139.79 | 0.00 | 15732664.20 | 0.129104E+10 | 0.261876E+10 | 0.109006E+11 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.304567E+10 | 0.00 | 0.00 | 2019.08 | 0.00 | 0.118138E+10 | 23691494.51 | 0.00 | 0.68 |
| February | 0.281101E+10 | 0.00 | 0.00 | 272313.95 | 0.00 | 0.514231E+09 | 0.348603E+09 | 0.00 | 0.70 |
| March | 0.308306E+10 | 0.00 | 0.00 | 968626.99 | 0.00 | 75830725.18 | 0.915403E+09 | 0.00 | 0.77 |
| April | 0.174010E+10 | 2250820.89 | 0.00 | 2261306.53 | 0.00 | 22780392.44 | 0.169674E+10 | 0.00 | 0.81 |
| May | 0.136960E+10 | 0.00 | 0.00 | 4185729.03 | 1566560.02 | 2597949.90 | 0.252077E+10 | 0.00 | 1.14 |
| June | 0.135855E+10 | 7195560.32 | 0.00 | 3652511.93 | 1352088.82 | 568943.89 | 0.179134E+10 | 0.00 | 1.32 |
| July | 0.105891E+10 | 0.105634E+09 | 0.00 | 533149.65 | 11587188.54 | 1900178.24 | 0.162037E+09 | 0.00 | 1.04 |
| August | 0.902910E+09 | 0.291192E+09 | 0.00 | 359040.15 | 22062205.25 | 1747709.11 | 57106015.50 | 0.00 | 1.08 |
| September | 0.102129E+10 | 530047.17 | 0.00 | 3931094.65 | 1538406.00 | 649936.37 | 0.170086E+10 | 0.00 | 1.16 |
| October | 0.177031E+10 | 0.00 | 0.00 | 2649794.72 | 0.00 | 4479627.57 | 0.201184E+10 | 0.00 | 0.90 |
| November | 0.325197E+10 | 0.00 | 0.00 | 276620.55 | 0.00 | 0.123767E+09 | 0.497559E+09 | 0.00 | 0.71 |
| December | 0.315952E+10 | 0.00 | 0.00 | 22403.21 | 0.00 | 0.706867E+09 | 79688639.11 | 0.00 | 0.62 |
| Annual Sum or Average | 0.245729E+11 | 0.406802E+09 | 0.00 | 19114610.44 | 38106448.64 | 0.263680E+10 | 0.118056E+11 | 0.00 | 0.91 |
| Minimum of Months | 0.902910E+09 | 0.00 | 0.00 | 2019.08 | 0.00 | 568943.89 | 23691494.51 | 0.00 | 0.62 |
| Maximum of Months | 0.325197E+10 | 0.291192E+09 | 0.00 | 4185729.03 | 22062205.25 | 0.118138E+10 | 0.252077E+10 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.183690E+11 | 0.00 | 0.00 | 77559.55 | 0.00 | 0.177941E+10 | 0.314274E+09 | 0.00 | 0.68 |
| February | 0.137012E+11 | 0.00 | 0.00 | 3072363.84 | 0.00 | 0.573139E+09 | 0.341959E+10 | 0.00 | 0.70 |
| March | 0.118358E+11 | 0.00 | 0.00 | 8054082.57 | 0.00 | 64321502.73 | 0.788471E+10 | 0.00 | 0.78 |
| April | 0.672164E+10 | 8562198.51 | 0.00 | 14219096.24 | 0.00 | 17839056.06 | 0.102359E+11 | 0.00 | 0.82 |
| May | 0.568791E+10 | 0.00 | 0.00 | 21810330.62 | 7547583.92 | 1727117.73 | 0.134067E+11 | 0.00 | 1.14 |
| June | 0.603483E+10 | 25932654.60 | 0.00 | 17404011.24 | 6514275.68 | 0.00 | 0.931688E+10 | 0.00 | 1.31 |
| July | 0.559557E+10 | 0.328012E+09 | 0.00 | 479044.68 | 0.180752E+09 | 7684175.46 | 0.289486E+09 | 0.00 | 1.03 |
| August | 0.445202E+10 | 0.109001E+10 | 0.00 | 846949.47 | 0.215912E+09 | 5991193.02 | 0.164408E+09 | 0.00 | 1.04 |
| September | 0.431967E+10 | 2144220.88 | 0.00 | 18933870.25 | 7411939.66 | 531090.61 | 0.884039E+10 | 0.00 | 1.13 |
| October | 0.597153E+10 | 0.00 | 0.00 | 16629975.55 | 0.00 | 8404793.51 | 0.125591E+11 | 0.00 | 0.91 |
| November | 0.136062E+11 | 0.00 | 0.00 | 3435547.23 | 0.00 | 98962434.78 | 0.496118E+10 | 0.00 | 0.71 |
| December | 0.170861E+11 | 0.00 | 0.00 | 430900.30 | 0.00 | 0.796406E+09 | 0.111446E+10 | 0.00 | 0.62 |
| Annual Sum or Average | 0.113381E+12 | 0.145466E+10 | 0.00 | 0.105394E+09 | 0.418137E+09 | 0.335442E+10 | 0.725071E+11 | 0.00 | 0.91 |
| Minimum of Months | 0.431967E+10 | 0.00 | 0.00 | 77559.55 | 0.00 | 0.00 | 0.164408E+09 | 0.00 | 0.62 |
| Maximum of Months | 0.183690E+11 | 0.109001E+10 | 0.00 | 21810330.62 | 0.215912E+09 | 0.177941E+10 | 0.134067E+11 | 0.00 | 1.31 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.995697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153417E+10 | 0.00 | 0.00 | 0.21 |
| February | 0.141147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.732973E+09 | 0.00 | 0.00 | 0.21 |
| March | 0.227367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 57675949.43 | 0.00 | 0.00 | 0.23 |
| April | 0.161547E+10 | 1530343.28 | 0.00 | 611512.14 | 0.00 | 2395463.30 | 0.343349E+09 | 0.00 | 0.24 |
| May | 0.883029E+09 | 0.00 | 0.00 | 3057696.31 | 902494.56 | 0.00 | 0.153289E+10 | 0.00 | 0.37 |
| June | 0.700560E+09 | 6001594.90 | 0.00 | 3283395.68 | 778937.80 | 0.00 | 0.132890E+10 | 0.00 | 0.45 |
| July | 0.678326E+09 | 56056208.06 | 0.00 | 101794.82 | 14861391.87 | 0.00 | 26416052.33 | 0.00 | 0.31 |
| August | 0.533108E+09 | 0.142016E+09 | 0.00 | 144255.70 | 35997017.09 | 0.00 | 21708032.36 | 0.00 | 0.32 |
| September | 0.744935E+09 | 330995.64 | 0.00 | 2315622.41 | 893949.21 | 0.00 | 0.862778E+09 | 0.00 | 0.36 |
| October | 0.157154E+10 | 0.00 | 0.00 | 962130.97 | 0.00 | 1024862.98 | 0.550221E+09 | 0.00 | 0.26 |
| November | 0.194800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288054E+09 | 0.00 | 0.00 | 0.21 |
| December | 0.126783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104876E+10 | 0.00 | 0.00 | 0.19 |
| Annual Sum or Average | 0.146236E+11 | 0.205936E+09 | 0.00 | 10476408.04 | 53433790.53 | 0.366506E+10 | 0.466626E+10 | 0.00 | 0.28 |
| Minimum of Months | 0.533108E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
| Maximum of Months | 0.227367E+10 | 0.142016E+09 | 0.00 | 3283395.68 | 35997017.09 | 0.153417E+10 | 0.153289E+10 | 0.00 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.268424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156203E+10 | 0.00 | 0.00 | 0.68 |
| February | 0.271875E+10 | 0.00 | 0.00 | 7845.94 | 0.00 | 0.912107E+09 | 36363464.47 | 0.00 | 0.69 |
| March | 0.377315E+10 | 0.00 | 0.00 | 31859.27 | 0.00 | 0.141976E+09 | 0.123481E+09 | 0.00 | 0.77 |
| April | 0.249183E+10 | 1568302.06 | 0.00 | 702977.04 | 0.00 | 37038098.08 | 0.814883E+09 | 0.00 | 0.77 |
| May | 0.154963E+10 | 0.00 | 0.00 | 2972166.24 | 1566375.18 | 2908082.21 | 0.211915E+10 | 0.00 | 1.06 |
| June | 0.152965E+10 | 6150498.48 | 0.00 | 2587840.87 | 1351929.29 | 1052837.17 | 0.151737E+10 | 0.00 | 1.26 |
| July | 0.119751E+10 | 65743008.95 | 0.00 | 36684.47 | 39107955.35 | 2831129.38 | 22661838.98 | 0.00 | 1.03 |
| August | 0.944343E+09 | 0.137203E+09 | 0.00 | 33870.87 | 0.131697E+09 | 2921895.71 | 12054193.09 | 0.00 | 1.04 |
| September | 0.141734E+10 | 304371.26 | 0.00 | 1649116.54 | 1551543.81 | 1719442.72 | 0.111293E+10 | 0.00 | 1.02 |
| October | 0.247479E+10 | 0.00 | 0.00 | 847075.93 | 0.00 | 16439739.31 | 0.101978E+10 | 0.00 | 0.81 |
| November | 0.329570E+10 | 0.00 | 0.00 | 27717.51 | 0.00 | 0.373855E+09 | 0.202160E+09 | 0.00 | 0.71 |
| December | 0.273791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120456E+10 | 0.00 | 0.00 | 0.62 |
| Annual Sum or Average | 0.268148E+11 | 0.210969E+09 | 0.00 | 8897154.68 | 0.175275E+09 | 0.425944E+10 | 0.698083E+10 | 0.00 | 0.87 |
| Minimum of Months | 0.944343E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1052837.17 | 0.00 | 0.00 | 0.62 |
| Maximum of Months | 0.377315E+10 | 0.137203E+09 | 0.00 | 2972166.24 | 0.131697E+09 | 0.156203E+10 | 0.211915E+10 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.178142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261550E+10 | 0.00 | 0.00 | 0.68 |
| February | 0.158511E+11 | 0.00 | 0.00 | 105955.54 | 0.00 | 0.133313E+10 | 0.459800E+09 | 0.00 | 0.69 |
| March | 0.164845E+11 | 0.00 | 0.00 | 718318.18 | 0.00 | 0.113206E+09 | 0.283457E+10 | 0.00 | 0.77 |
| April | 0.911002E+10 | 6953720.75 | 0.00 | 5248099.16 | 0.00 | 29342271.37 | 0.694575E+10 | 0.00 | 0.77 |
| May | 0.687347E+10 | 0.00 | 0.00 | 15811070.88 | 7538064.43 | 3121542.49 | 0.109300E+11 | 0.00 | 1.06 |
| June | 0.731587E+10 | 24377525.61 | 0.00 | 11605131.20 | 6506059.46 | 0.00 | 0.750077E+10 | 0.00 | 1.26 |
| July | 0.587067E+10 | 7727831.08 | 0.00 | 0.00 | 0.496860E+09 | 14824840.77 | 0.00 | 0.00 | 1.03 |
| August | 0.460311E+10 | 0.00 | 0.00 | 0.00 | 0.128937E+10 | 13511705.38 | 0.00 | 0.00 | 1.04 |
| September | 0.685189E+10 | 1259336.66 | 0.00 | 7367626.91 | 7537186.67 | 1295022.05 | 0.535795E+10 | 0.00 | 1.02 |
| October | 0.921239E+10 | 0.00 | 0.00 | 5994051.95 | 0.00 | 17152459.25 | 0.767077E+10 | 0.00 | 0.81 |
| November | 0.157736E+11 | 0.00 | 0.00 | 882249.38 | 0.00 | 0.167706E+09 | 0.268840E+10 | 0.00 | 0.71 |
| December | 0.179269E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104158E+10 | 0.00 | 0.00 | 0.62 |
| Annual Sum or Average | 0.133688E+12 | 40318414.10 | 0.00 | 47732503.19 | 0.180781E+10 | 0.535037E+10 | 0.443880E+11 | 0.00 | 0.87 |
| Minimum of Months | 0.460311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
| Maximum of Months | 0.179269E+11 | 24377525.61 | 0.00 | 15811070.88 | 0.128937E+10 | 0.261550E+10 | 0.109300E+11 | 0.00 | 1.26 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.306710E+10 | 0.00 | 0.00 | 3588.87 | 0.00 | 0.114973E+10 | 26194908.60 | 0.00 | 0.68 |
| February | 0.280976E+10 | 0.00 | 0.00 | 292696.33 | 0.00 | 0.508047E+09 | 0.349730E+09 | 0.00 | 0.70 |
| March | 0.305899E+10 | 0.00 | 0.00 | 1024231.14 | 0.00 | 71939702.52 | 0.939155E+09 | 0.00 | 0.77 |
| April | 0.168559E+10 | 2265542.04 | 0.00 | 2344996.99 | 0.00 | 22379306.81 | 0.175514E+10 | 0.00 | 0.82 |
| May | 0.134405E+10 | 0.00 | 0.00 | 4258484.19 | 1563719.79 | 2262711.48 | 0.255551E+10 | 0.00 | 1.14 |
| June | 0.133202E+10 | 7249441.07 | 0.00 | 3738967.85 | 1349637.43 | 567912.37 | 0.182228E+10 | 0.00 | 1.32 |
| July | 0.104487E+10 | 0.107109E+09 | 0.00 | 601129.21 | 11053477.51 | 1875523.10 | 0.173817E+09 | 0.00 | 1.04 |
| August | 0.897896E+09 | 0.294533E+09 | 0.00 | 380960.02 | 21097465.79 | 1371324.59 | 60993484.13 | 0.00 | 1.08 |
| September | 0.992849E+09 | 533318.07 | 0.00 | 4013480.56 | 1535616.80 | 514563.07 | 0.173498E+10 | 0.00 | 1.16 |
| October | 0.172813E+10 | 0.00 | 0.00 | 2712848.93 | 0.00 | 4477249.79 | 0.205820E+10 | 0.00 | 0.90 |
| November | 0.324882E+10 | 0.00 | 0.00 | 316015.56 | 0.00 | 99289958.75 | 0.518255E+09 | 0.00 | 0.71 |
| December | 0.316132E+10 | 0.00 | 0.00 | 33587.12 | 0.00 | 0.683253E+09 | 94344234.21 | 0.00 | 0.62 |
| Annual Sum or Average | 0.243714E+11 | 0.411690E+09 | 0.00 | 19720986.75 | 36599917.32 | 0.254571E+10 | 0.120886E+11 | 0.00 | 0.91 |
| Minimum of Months | 0.897896E+09 | 0.00 | 0.00 | 3588.87 | 0.00 | 514563.07 | 26194908.60 | 0.00 | 0.62 |
| Maximum of Months | 0.324882E+10 | 0.294533E+09 | 0.00 | 4258484.19 | 21097465.79 | 0.114973E+10 | 0.255551E+10 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.184570E+11 | 0.00 | 0.00 | 105484.56 | 0.00 | 0.162573E+10 | 0.372005E+09 | 0.00 | 0.68 |
| February | 0.135199E+11 | 0.00 | 0.00 | 3380144.03 | 0.00 | 0.571747E+09 | 0.360215E+10 | 0.00 | 0.70 |
| March | 0.114034E+11 | 0.00 | 0.00 | 8608380.09 | 0.00 | 58764890.17 | 0.837089E+10 | 0.00 | 0.78 |
| April | 0.651186E+10 | 8678084.54 | 0.00 | 14890572.35 | 0.00 | 17828502.45 | 0.105415E+11 | 0.00 | 0.83 |
| May | 0.555588E+10 | 0.00 | 0.00 | 22397303.92 | 7544559.11 | 927455.65 | 0.136496E+11 | 0.00 | 1.15 |
| June | 0.581260E+10 | 26156286.60 | 0.00 | 18140050.16 | 6511664.98 | 0.00 | 0.961038E+10 | 0.00 | 1.32 |
| July | 0.550889E+10 | 0.347356E+09 | 0.00 | 642775.52 | 0.162467E+09 | 6351654.02 | 0.374943E+09 | 0.00 | 1.03 |
| August | 0.443581E+10 | 0.112298E+10 | 0.00 | 950298.44 | 0.187694E+09 | 5970003.53 | 0.179252E+09 | 0.00 | 1.04 |
| September | 0.418114E+10 | 2170338.59 | 0.00 | 19617140.14 | 7408969.21 | 530877.76 | 0.905234E+10 | 0.00 | 1.14 |
| October | 0.569369E+10 | 0.00 | 0.00 | 17426120.48 | 0.00 | 7622303.16 | 0.129353E+11 | 0.00 | 0.91 |
| November | 0.131812E+11 | 0.00 | 0.00 | 4031067.16 | 0.00 | 93328039.77 | 0.539741E+10 | 0.00 | 0.71 |
| December | 0.169906E+11 | 0.00 | 0.00 | 581107.56 | 0.00 | 0.777852E+09 | 0.122093E+10 | 0.00 | 0.62 |
| Annual Sum or Average | 0.111252E+12 | 0.150734E+10 | 0.00 | 0.110770E+09 | 0.371627E+09 | 0.316665E+10 | 0.753067E+11 | 0.00 | 0.91 |
| Minimum of Months | 0.418114E+10 | 0.00 | 0.00 | 105484.56 | 0.00 | 0.00 | 0.179252E+09 | 0.00 | 0.62 |
| Maximum of Months | 0.184570E+11 | 0.112298E+10 | 0.00 | 22397303.92 | 0.187694E+09 | 0.162573E+10 | 0.136496E+11 | 0.00 | 1.32 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.108471E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146442E+10 | 0.00 | 0.00 | 0.21 |
| February | 0.147534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.686342E+09 | 0.00 | 0.00 | 0.21 |
| March | 0.231140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39910103.02 | 0.00 | 0.00 | 0.23 |
| April | 0.150768E+10 | 1647442.44 | 0.00 | 857034.04 | 0.00 | 1739433.03 | 0.490535E+09 | 0.00 | 0.24 |
| May | 0.770776E+09 | 0.00 | 0.00 | 3495195.27 | 910704.86 | 0.00 | 0.176416E+10 | 0.00 | 0.39 |
| June | 0.610331E+09 | 6493118.09 | 0.00 | 3869417.84 | 786024.06 | 0.00 | 0.153544E+10 | 0.00 | 0.48 |
| July | 0.645176E+09 | 68700666.75 | 0.00 | 313401.30 | 9129708.29 | 0.00 | 66252783.05 | 0.00 | 0.32 |
| August | 0.532422E+09 | 0.173541E+09 | 0.00 | 222550.25 | 21587475.59 | 0.00 | 29144876.27 | 0.00 | 0.33 |
| September | 0.632939E+09 | 361731.48 | 0.00 | 2770180.32 | 902081.77 | 0.00 | 0.105220E+10 | 0.00 | 0.38 |
| October | 0.150312E+10 | 0.00 | 0.00 | 1121878.40 | 0.00 | 718590.67 | 0.669603E+09 | 0.00 | 0.27 |
| November | 0.207926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176498E+09 | 0.00 | 0.00 | 0.21 |
| December | 0.140840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925311E+09 | 0.00 | 0.00 | 0.19 |
| Annual Sum or Average | 0.145615E+11 | 0.250744E+09 | 0.00 | 12649657.42 | 33315994.57 | 0.329494E+10 | 0.560733E+10 | 0.00 | 0.29 |
| Minimum of Months | 0.532422E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
| Maximum of Months | 0.231140E+10 | 0.173541E+09 | 0.00 | 3869417.84 | 21587475.59 | 0.146442E+10 | 0.176416E+10 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.269453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154961E+10 | 0.00 | 0.00 | 0.68 |
| February | 0.272818E+10 | 0.00 | 0.00 | 10266.28 | 0.00 | 0.896902E+09 | 40257366.65 | 0.00 | 0.69 |
| March | 0.375551E+10 | 0.00 | 0.00 | 40677.98 | 0.00 | 0.133555E+09 | 0.147415E+09 | 0.00 | 0.77 |
| April | 0.240018E+10 | 1610879.05 | 0.00 | 807425.82 | 0.00 | 33192822.81 | 0.910510E+09 | 0.00 | 0.77 |
| May | 0.150492E+10 | 0.00 | 0.00 | 3208162.39 | 1565528.60 | 2615332.51 | 0.218772E+10 | 0.00 | 1.07 |
| June | 0.146094E+10 | 6366022.89 | 0.00 | 2866095.15 | 1351198.60 | 705765.16 | 0.160185E+10 | 0.00 | 1.27 |
| July | 0.118450E+10 | 72086042.47 | 0.00 | 69154.29 | 32860992.21 | 2432907.59 | 35371393.78 | 0.00 | 1.03 |
| August | 0.941147E+09 | 0.158139E+09 | 0.00 | 44551.18 | 0.111249E+09 | 2710290.32 | 14938926.11 | 0.00 | 1.04 |
| September | 0.136772E+10 | 314634.75 | 0.00 | 1801322.51 | 1550705.24 | 1568942.50 | 0.116690E+10 | 0.00 | 1.02 |
| October | 0.242373E+10 | 0.00 | 0.00 | 921588.36 | 0.00 | 14213265.23 | 0.107427E+10 | 0.00 | 0.81 |
| November | 0.327244E+10 | 0.00 | 0.00 | 37034.61 | 0.00 | 0.358966E+09 | 0.238262E+09 | 0.00 | 0.71 |
| December | 0.274259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119789E+10 | 0.00 | 0.00 | 0.62 |
| Annual Sum or Average | 0.264764E+11 | 0.238517E+09 | 0.00 | 9806278.57 | 0.148578E+09 | 0.419437E+10 | 0.741750E+10 | 0.00 | 0.87 |
| Minimum of Months | 0.941147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 705765.16 | 0.00 | 0.00 | 0.62 |
| Maximum of Months | 0.375551E+10 | 0.158139E+09 | 0.00 | 3208162.39 | 0.111249E+09 | 0.154961E+10 | 0.218772E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.117545E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175422E+10 | 0.00 | 0.00 | 0.68 |
| February | 0.104168E+11 | 0.00 | 0.00 | 93032.27 | 0.00 | 0.882241E+09 | 0.367773E+09 | 0.00 | 0.70 |
| March | 0.106576E+11 | 0.00 | 0.00 | 619431.28 | 0.00 | 71531766.48 | 0.211996E+10 | 0.00 | 0.77 |
| April | 0.576195E+10 | 4606792.79 | 0.00 | 4194652.67 | 0.00 | 18213298.54 | 0.486766E+10 | 0.00 | 0.77 |
| May | 0.429604E+10 | 0.00 | 0.00 | 11342093.71 | 4984403.83 | 1559389.47 | 0.762102E+10 | 0.00 | 1.07 |
| June | 0.435895E+10 | 16219626.11 | 0.00 | 8947267.59 | 4302009.89 | 0.00 | 0.553546E+10 | 0.00 | 1.27 |
| July | 0.388411E+10 | 20062507.46 | 0.00 | 0.00 | 0.313587E+09 | 7557063.77 | 0.00 | 0.00 | 1.03 |
| August | 0.304495E+10 | 18075833.66 | 0.00 | 0.00 | 0.834497E+09 | 7708613.94 | 0.00 | 0.00 | 1.04 |
| September | 0.428308E+10 | 879327.65 | 0.00 | 5461477.06 | 4937208.54 | 856309.06 | 0.382682E+10 | 0.00 | 1.02 |
| October | 0.587320E+10 | 0.00 | 0.00 | 4383376.91 | 0.00 | 11341742.22 | 0.530960E+10 | 0.00 | 0.81 |
| November | 0.103229E+11 | 0.00 | 0.00 | 708921.83 | 0.00 | 0.112693E+09 | 0.188282E+10 | 0.00 | 0.71 |
| December | 0.118236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719018E+09 | 0.00 | 0.00 | 0.62 |
| Annual Sum or Average | 0.864776E+11 | 59844087.67 | 0.00 | 35750253.31 | 0.116231E+10 | 0.358694E+10 | 0.315311E+11 | 0.00 | 0.87 |
| Minimum of Months | 0.304495E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.62 |
| Maximum of Months | 0.118236E+11 | 20062507.46 | 0.00 | 11342093.71 | 0.834497E+09 | 0.175422E+10 | 0.762102E+10 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.647708E+10 | 0.00 | 0.00 | 21303.66 | 0.00 | 0.281742E+09 | 0.177554E+09 | 0.00 | 0.68 |
| February | 0.517121E+10 | 0.00 | 0.00 | 416870.94 | 0.00 | 0.140040E+09 | 0.678980E+09 | 0.00 | 0.70 |
| March | 0.289061E+10 | 0.00 | 0.00 | 2750620.12 | 0.00 | 16836972.70 | 0.369845E+10 | 0.00 | 0.77 |
| April | 0.845289E+09 | 3293691.96 | 0.00 | 7112680.84 | 0.00 | 3182568.35 | 0.489136E+10 | 0.00 | 0.82 |
| May | 0.829214E+09 | 0.00 | 0.00 | 11929215.49 | 2559369.02 | 0.00 | 0.605968E+10 | 0.00 | 1.22 |
| June | 0.108943E+10 | 12793395.83 | 0.00 | 12551923.67 | 2208976.48 | 0.00 | 0.487678E+10 | 0.00 | 1.55 |
| July | 0.143197E+10 | 0.149516E+09 | 0.00 | 1150793.23 | 22342289.24 | 0.00 | 0.565158E+09 | 0.00 | 1.03 |
| August | 0.134587E+10 | 0.394056E+09 | 0.00 | 496827.25 | 44481061.84 | 535591.32 | 0.220565E+09 | 0.00 | 1.04 |
| September | 0.775901E+09 | 732404.89 | 0.00 | 9987874.97 | 2535135.40 | 0.00 | 0.395168E+10 | 0.00 | 1.21 |
| October | 0.903354E+09 | 0.00 | 0.00 | 7327349.94 | 0.00 | 1778997.35 | 0.510396E+10 | 0.00 | 0.86 |
| November | 0.386314E+10 | 0.00 | 0.00 | 2587892.33 | 0.00 | 28482006.14 | 0.244180E+10 | 0.00 | 0.71 |
| December | 0.618172E+10 | 0.00 | 0.00 | 19108.71 | 0.00 | 0.130477E+09 | 0.128088E+09 | 0.00 | 0.62 |
| Annual Sum or Average | 0.318048E+11 | 0.560392E+09 | 0.00 | 56352461.16 | 74126832.00 | 0.603075E+09 | 0.327941E+11 | 0.00 | 0.93 |
| Minimum of Months | 0.775901E+09 | 0.00 | 0.00 | 19108.71 | 0.00 | 0.00 | 0.128088E+09 | 0.00 | 0.62 |
| Maximum of Months | 0.647708E+10 | 0.394056E+09 | 0.00 | 12551923.67 | 44481061.84 | 0.281742E+09 | 0.605968E+10 | 0.00 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.185900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347255E+10 | 0.00 | 0.00 | 0.15 |
| February | 0.278346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172083E+10 | 0.00 | 0.00 | 0.15 |
| March | 0.488606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23216720.42 | 0.00 | 0.00 | 0.17 |
| April | 0.255520E+10 | 3777082.74 | 0.00 | 3200191.61 | 0.00 | 0.00 | 0.181696E+10 | 0.00 | 0.19 |
| May | 0.709942E+09 | 0.00 | 0.00 | 12761599.28 | 1901862.27 | 0.00 | 0.612898E+10 | 0.00 | 0.37 |
| June | 0.784074E+09 | 17463091.71 | 0.00 | 14226027.82 | 1641486.24 | 0.00 | 0.521544E+10 | 0.00 | 0.47 |
| July | 0.694957E+09 | 0.259988E+09 | 0.00 | 5253847.29 | 9709287.06 | 0.00 | 0.104753E+10 | 0.00 | 0.32 |
| August | 0.722508E+09 | 0.600356E+09 | 0.00 | 2894296.93 | 8086029.15 | 0.00 | 0.523005E+09 | 0.00 | 0.30 |
| September | 0.773194E+09 | 866035.67 | 0.00 | 8468111.73 | 1883854.31 | 0.00 | 0.323186E+10 | 0.00 | 0.32 |
| October | 0.315152E+10 | 0.00 | 0.00 | 2348992.40 | 0.00 | 336978.45 | 0.140572E+10 | 0.00 | 0.19 |
| November | 0.402725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.684962E+09 | 0.00 | 0.00 | 0.16 |
| December | 0.220252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265254E+10 | 0.00 | 0.00 | 0.14 |
| Annual Sum or Average | 0.251497E+11 | 0.882450E+09 | 0.00 | 49153067.05 | 23222519.03 | 0.855444E+10 | 0.193695E+11 | 0.00 | 0.24 |
| Minimum of Months | 0.694957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.14 |
| Maximum of Months | 0.488606E+10 | 0.600356E+09 | 0.00 | 14226027.82 | 9709287.06 | 0.347255E+10 | 0.612898E+10 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.123934E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493067E+10 | 0.00 | 0.00 | 0.46 |
| February | 0.268334E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376520E+10 | 0.00 | 0.00 | 0.43 |
| March | 0.735618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325820E+10 | 0.00 | 0.00 | 0.43 |
| April | 0.112168E+10 | 2742771.47 | 0.00 | 364061.15 | 0.00 | 0.191123E+10 | 36366430.98 | 0.00 | 0.41 |
| May | 0.184587E+10 | 0.00 | 0.00 | 707488.57 | 1266430.01 | 0.117903E+10 | 0.173766E+09 | 0.00 | 0.53 |
| June | 0.183954E+10 | 7942180.40 | 0.00 | 996529.53 | 1093048.36 | 0.592703E+09 | 0.165500E+09 | 0.00 | 0.63 |
| July | 0.736183E+09 | 0.158720E+09 | 4808.28 | 215309.68 | 12402033.96 | 0.298538E+09 | 29705273.59 | 641.77 | 0.54 |
| August | 0.525730E+09 | 0.495828E+09 | 9113.88 | 342751.33 | 11401362.99 | 0.281198E+09 | 33555566.68 | 460.82 | 0.63 |
| September | 0.137976E+10 | 661657.48 | 0.00 | 1432109.44 | 1243669.88 | 0.637957E+09 | 0.225469E+09 | 0.00 | 0.55 |
| October | 0.123651E+10 | 0.00 | 0.00 | 168302.97 | 0.00 | 0.184326E+10 | 82632709.11 | 0.00 | 0.42 |
| November | 0.369113E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370740E+10 | 0.00 | 0.00 | 0.42 |
| December | 63239837.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454976E+10 | 0.00 | 0.00 | 0.41 |
| Annual Sum or Average | 0.102455E+11 | 0.665895E+09 | 13922.16 | 4226552.66 | 27406545.19 | 0.269551E+11 | 0.746996E+09 | 1102.59 | 0.49 |
| Minimum of Months | 63239837.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281198E+09 | 0.00 | 0.00 | 0.41 |
| Maximum of Months | 0.184587E+10 | 0.495828E+09 | 9113.88 | 1432109.44 | 12402033.96 | 0.493067E+10 | 0.225469E+09 | 641.77 | 0.63 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.367985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
| February | 0.317811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
| March | 0.350033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
| April | 0.221017E+10 | 1419441.48 | 0.00 | 1050885.99 | 0.00 | 0.00 | 0.699059E+09 | 0.00 | 0.27 |
| May | 0.952673E+09 | 101137.64 | 0.00 | 5983677.44 | 1316139.10 | 0.00 | 0.238971E+10 | 0.00 | 0.39 |
| June | 0.674119E+09 | 6337018.65 | 0.00 | 7926041.53 | 1111500.76 | 0.00 | 0.223244E+10 | 0.00 | 0.49 |
| July | 0.101904E+10 | 49383877.23 | 0.00 | 929354.08 | 41939957.32 | 0.00 | 61639305.53 | 0.00 | 0.36 |
| August | 0.814312E+09 | 81528978.62 | 0.00 | 363456.93 | 0.150775E+09 | 0.00 | 23673481.75 | 0.00 | 0.36 |
| September | 0.940912E+09 | 387135.45 | 0.00 | 3799728.37 | 1326418.82 | 0.00 | 0.130685E+10 | 0.00 | 0.37 |
| October | 0.253726E+10 | 0.00 | 0.00 | 760970.81 | 0.00 | 0.00 | 0.498680E+09 | 0.00 | 0.28 |
| November | 0.335579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
| December | 0.341666E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
| Annual Sum or Average | 0.262792E+11 | 0.139158E+09 | 0.00 | 20814115.16 | 0.196469E+09 | 0.00 | 0.721205E+10 | 0.00 | 0.31 |
| Minimum of Months | 0.674119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
| Maximum of Months | 0.367985E+10 | 81528978.62 | 0.00 | 7926041.53 | 0.150775E+09 | 0.00 | 0.238971E+10 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.241825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24324262.13 | 0.00 | 0.00 | 0.20 |
| February | 0.210280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6737929.65 | 0.00 | 0.00 | 0.21 |
| March | 0.232342E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
| April | 0.191885E+10 | 0.00 | 0.00 | 0.00 | 831388.51 | 0.00 | 0.00 | 0.00 | 0.23 |
| May | 0.203728E+10 | 0.00 | 0.00 | 116020.05 | 901252.79 | 0.00 | 27759138.47 | 0.00 | 0.31 |
| June | 0.166875E+10 | 3336364.65 | 0.00 | 307268.90 | 777866.02 | 0.00 | 47844301.01 | 0.00 | 0.37 |
| July | 0.703328E+09 | 13398875.40 | 0.00 | 58621.87 | 46991758.09 | 0.00 | 426079.73 | 0.00 | 0.31 |
| August | 0.551790E+09 | 12645414.69 | 0.00 | 13612.30 | 0.141527E+09 | 0.00 | 253421.21 | 0.00 | 0.31 |
| September | 0.143466E+10 | 95509.28 | 0.00 | 37085.39 | 956205.15 | 0.00 | 7258390.65 | 0.00 | 0.30 |
| October | 0.201291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.24 |
| November | 0.222747E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.21 |
| December | 0.226672E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1163370.34 | 0.00 | 0.00 | 0.19 |
| Annual Sum or Average | 0.216662E+11 | 29476164.02 | 0.00 | 532608.50 | 0.191986E+09 | 32225562.12 | 83541331.08 | 0.00 | 0.26 |
| Minimum of Months | 0.551790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.19 |
| Maximum of Months | 0.241825E+10 | 13398875.40 | 0.00 | 307268.90 | 0.141527E+09 | 24324262.13 | 47844301.01 | 0.00 | 0.37 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.395796E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279535E+10 | 0.00 | 0.00 | 0.24 |
| February | 0.448334E+10 | 0.00 | 0.00 | 333741.42 | 0.00 | 0.117779E+10 | 0.147306E+09 | 0.00 | 0.25 |
| March | 0.502526E+10 | 0.00 | 0.00 | 3452817.51 | 0.00 | 22462924.86 | 0.166794E+10 | 0.00 | 0.29 |
| April | 0.222075E+10 | 6160432.86 | 0.00 | 9489982.17 | 0.00 | 1007189.57 | 0.474644E+10 | 0.00 | 0.38 |
| May | 0.120068E+10 | 70065.72 | 0.00 | 17281362.72 | 2834581.51 | 0.00 | 0.808572E+10 | 0.00 | 0.62 |
| June | 0.117660E+10 | 22539494.73 | 0.00 | 20980583.34 | 2506984.09 | 0.00 | 0.733191E+10 | 0.00 | 0.84 |
| July | 0.922933E+09 | 0.366752E+09 | 0.00 | 8534261.63 | 13098534.76 | 0.00 | 0.167967E+10 | 0.00 | 0.58 |
| August | 0.874722E+09 | 0.961542E+09 | 0.00 | 6341246.52 | 8372287.77 | 0.00 | 0.103242E+10 | 0.00 | 0.59 |
| September | 0.920861E+09 | 1635113.39 | 0.00 | 16814955.41 | 2852445.26 | 0.00 | 0.562097E+10 | 0.00 | 0.67 |
| October | 0.258813E+10 | 0.00 | 0.00 | 8638198.71 | 0.00 | 558876.83 | 0.462628E+10 | 0.00 | 0.39 |
| November | 0.530814E+10 | 0.00 | 0.00 | 1130768.68 | 0.00 | 88739718.17 | 0.759261E+09 | 0.00 | 0.26 |
| December | 0.469252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.153509E+10 | 0.00 | 0.00 | 0.22 |
| Annual Sum or Average | 0.333719E+11 | 0.135870E+10 | 0.00 | 92997918.09 | 29664833.38 | 0.562100E+10 | 0.356979E+11 | 0.00 | 0.44 |
| Minimum of Months | 0.874722E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
| Maximum of Months | 0.530814E+10 | 0.961542E+09 | 0.00 | 20980583.34 | 13098534.76 | 0.279535E+10 | 0.808572E+10 | 0.00 | 0.84 |
Report: MechanicalVentilationLoadsMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.116790E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742063E+09 | 0.00 | 0.00 | 0.55 |
| February | 0.989109E+10 | 0.00 | 0.00 | 366235.10 | 0.00 | 0.266485E+09 | 0.565674E+09 | 0.00 | 0.57 |
| March | 0.692714E+10 | 0.00 | 0.00 | 4553870.22 | 0.00 | 1221165.95 | 0.492067E+10 | 0.00 | 0.63 |
| April | 0.200897E+10 | 7989747.21 | 0.00 | 14895107.80 | 0.00 | 0.00 | 0.886677E+10 | 0.00 | 0.73 |
| May | 0.158146E+10 | 102634.44 | 0.00 | 24466606.58 | 4477755.85 | 0.00 | 0.118346E+11 | 0.00 | 1.11 |
| June | 0.164064E+10 | 31373847.67 | 0.00 | 27242412.06 | 3953308.15 | 0.00 | 0.994168E+10 | 0.00 | 1.41 |
| July | 0.120257E+10 | 0.404674E+09 | 0.00 | 13151994.93 | 23016712.97 | 0.00 | 0.268724E+10 | 0.00 | 0.98 |
| August | 0.120368E+10 | 0.101278E+10 | 0.00 | 8525223.25 | 18337346.65 | 0.00 | 0.169443E+10 | 0.00 | 0.96 |
| September | 0.153394E+10 | 1442228.67 | 0.00 | 17958622.36 | 4537020.44 | 0.00 | 0.705363E+10 | 0.00 | 1.04 |
| October | 0.402061E+10 | 0.00 | 0.00 | 9385143.67 | 0.00 | 0.00 | 0.664281E+10 | 0.00 | 0.70 |
| November | 0.987886E+10 | 0.00 | 0.00 | 1147388.71 | 0.00 | 57753503.49 | 0.138352E+10 | 0.00 | 0.58 |
| December | 0.110347E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494893E+09 | 0.00 | 0.00 | 0.51 |
| Annual Sum or Average | 0.626027E+11 | 0.145836E+10 | 0.00 | 0.121693E+09 | 54322144.06 | 0.156242E+10 | 0.555910E+11 | 0.00 | 0.81 |
| Minimum of Months | 0.120257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.51 |
| Maximum of Months | 0.116790E+11 | 0.101278E+10 | 0.00 | 27242412.06 | 23016712.97 | 0.742063E+09 | 0.118346E+11 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 173330.78 | 0.00 | 0.00 | 29904642.98 | 0.00 | 0.00 | 0.190312E+11 | 0.00 | 1.15 |
| February | 258830.15 | 0.00 | 0.00 | 30778285.74 | 0.00 | 0.00 | 0.186178E+11 | 0.00 | 1.45 |
| March | 99271.91 | 0.00 | 0.00 | 42327567.42 | 0.00 | 0.00 | 0.244685E+11 | 0.00 | 1.98 |
| April | 0.00 | 589145.94 | 0.00 | 42968235.03 | 0.00 | 0.00 | 0.230039E+11 | 0.00 | 2.35 |
| May | 0.00 | 1239481.72 | 0.00 | 52361207.64 | 0.00 | 0.00 | 0.247421E+11 | 0.00 | 3.14 |
| June | 0.00 | 0.00 | 0.00 | 52299118.67 | 0.00 | 0.00 | 0.220711E+11 | 0.00 | 3.65 |
| July | 73094.46 | 79593845.03 | 0.00 | 42573678.24 | 0.00 | 0.00 | 0.159002E+11 | 0.00 | 3.37 |
| August | 122659.09 | 0.220892E+09 | 0.00 | 39232333.12 | 0.00 | 0.00 | 0.144138E+11 | 0.00 | 3.25 |
| September | 0.00 | 4913703.96 | 0.00 | 45425312.32 | 0.00 | 0.00 | 0.202417E+11 | 0.00 | 3.32 |
| October | 19343.70 | 0.00 | 0.00 | 43512895.06 | 0.00 | 0.00 | 0.241441E+11 | 0.00 | 2.48 |
| November | 85105.90 | 0.00 | 0.00 | 37745741.04 | 0.00 | 0.00 | 0.217820E+11 | 0.00 | 1.70 |
| December | 0.00 | 0.00 | 0.00 | 31538035.46 | 0.00 | 0.00 | 0.192163E+11 | 0.00 | 1.16 |
| Annual Sum or Average | 831635.98 | 0.307228E+09 | 0.00 | 0.490667E+09 | 0.00 | 0.00 | 0.247633E+12 | 0.00 | 2.42 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 29904642.98 | 0.00 | 0.00 | 0.144138E+11 | 0.00 | 1.15 |
| Maximum of Months | 258830.15 | 0.220892E+09 | 0.00 | 52361207.64 | 0.00 | 0.00 | 0.247421E+11 | 0.00 | 3.65 |
Report: MechanicalVentilationLoadsMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.172362E+11 | 0.00 | 0.00 | 3015652.77 | 0.00 | 0.323829E+10 | 0.145353E+11 | 0.00 | 1.61 |
| February | 0.138307E+11 | 0.00 | 0.00 | 5771432.63 | 0.00 | 0.192106E+10 | 0.146896E+11 | 0.00 | 1.65 |
| March | 0.139585E+11 | 0.00 | 0.00 | 11302446.25 | 0.00 | 0.190604E+09 | 0.188748E+11 | 0.00 | 1.79 |
| April | 0.785439E+10 | 9695177.14 | 0.00 | 16366482.27 | 0.00 | 20120002.66 | 0.194157E+11 | 0.00 | 1.75 |
| May | 0.438587E+10 | 1179067.45 | 0.00 | 27031116.49 | 0.00 | 8349164.28 | 0.245117E+11 | 0.00 | 2.18 |
| June | 0.201822E+10 | 3807900.34 | 0.00 | 34657357.58 | 0.00 | 0.00 | 0.239486E+11 | 0.00 | 2.58 |
| July | 0.228095E+10 | 0.635145E+09 | 0.00 | 11125115.73 | 0.00 | 0.00 | 0.743913E+10 | 0.00 | 2.08 |
| August | 0.267861E+10 | 0.183625E+10 | 0.00 | 8950417.32 | 0.00 | 0.00 | 0.590858E+10 | 0.00 | 2.23 |
| September | 0.271096E+10 | 425573.56 | 0.00 | 25976533.05 | 0.00 | 1373754.88 | 0.196062E+11 | 0.00 | 2.21 |
| October | 0.834719E+10 | 0.00 | 0.00 | 17726411.32 | 0.00 | 13859033.48 | 0.203988E+11 | 0.00 | 1.79 |
| November | 0.147511E+11 | 0.00 | 0.00 | 8196843.41 | 0.00 | 0.446008E+09 | 0.166943E+11 | 0.00 | 1.67 |
| December | 0.165393E+11 | 0.00 | 0.00 | 3749126.99 | 0.00 | 0.218195E+10 | 0.144140E+11 | 0.00 | 1.52 |
| Annual Sum or Average | 0.106592E+12 | 0.248650E+10 | 0.00 | 0.173869E+09 | 0.00 | 0.802161E+10 | 0.200437E+12 | 0.00 | 1.92 |
| Minimum of Months | 0.201822E+10 | 0.00 | 0.00 | 3015652.77 | 0.00 | 0.00 | 0.590858E+10 | 0.00 | 1.52 |
| Maximum of Months | 0.172362E+11 | 0.183625E+10 | 0.00 | 34657357.58 | 0.00 | 0.323829E+10 | 0.245117E+11 | 0.00 | 2.58 |
Report: MechanicalVentilationLoadsMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.675311E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121546E+10 | 0.00 | 0.00 | 0.32 |
| February | 0.581847E+10 | 0.00 | 0.00 | 876349.30 | 0.00 | 0.479716E+09 | 0.615888E+09 | 0.00 | 0.33 |
| March | 0.365208E+10 | 0.00 | 0.00 | 7793360.87 | 0.00 | 8858071.69 | 0.452831E+10 | 0.00 | 0.39 |
| April | 0.110998E+10 | 5803187.59 | 0.00 | 14489130.46 | 0.00 | 0.00 | 0.769595E+10 | 0.00 | 0.52 |
| May | 0.813386E+09 | 65611.36 | 0.00 | 24175548.64 | 2862505.35 | 0.00 | 0.111153E+11 | 0.00 | 0.85 |
| June | 0.109712E+10 | 22974950.22 | 0.00 | 25716994.64 | 2500649.75 | 0.00 | 0.925853E+10 | 0.00 | 1.07 |
| July | 0.865516E+09 | 0.333713E+09 | 0.00 | 8444995.94 | 14923485.90 | 0.00 | 0.179043E+10 | 0.00 | 0.63 |
| August | 0.840802E+09 | 0.847429E+09 | 0.00 | 6028294.70 | 11720004.55 | 0.00 | 0.110884E+10 | 0.00 | 0.63 |
| September | 0.698227E+09 | 1341958.52 | 0.00 | 19259496.33 | 2900391.56 | 0.00 | 0.697242E+10 | 0.00 | 0.80 |
| October | 0.134193E+10 | 0.00 | 0.00 | 13680378.61 | 0.00 | 0.00 | 0.748707E+10 | 0.00 | 0.51 |
| November | 0.492026E+10 | 0.00 | 0.00 | 4555687.88 | 0.00 | 23607832.79 | 0.278963E+10 | 0.00 | 0.36 |
| December | 0.695027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437378E+09 | 0.00 | 0.00 | 0.29 |
| Annual Sum or Average | 0.348612E+11 | 0.121133E+10 | 0.00 | 0.125020E+09 | 34907037.11 | 0.216502E+10 | 0.533624E+11 | 0.00 | 0.56 |
| Minimum of Months | 0.698227E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
| Maximum of Months | 0.695027E+10 | 0.847429E+09 | 0.00 | 25716994.64 | 14923485.90 | 0.121546E+10 | 0.111153E+11 | 0.00 | 1.07 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:30:24
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.101415E+12 | 0.204091E+11 | 0.129205E+12 | 0.304072E+12 | 0.592726E+11 |
| February | 0.305786E+12 | 0.180910E+11 | 0.128785E+12 | 0.330605E+12 | 0.451678E+11 |
| March | 0.623136E+12 | 0.189340E+11 | 0.156973E+12 | 0.458217E+12 | 0.344558E+11 |
| April | 0.105212E+13 | 0.168494E+11 | 0.133266E+12 | 0.501230E+12 | 0.521811E+11 |
| May | 0.143719E+13 | 0.136825E+11 | 0.117300E+12 | 0.552612E+12 | 0.938034E+11 |
| June | 0.146040E+13 | 0.104499E+11 | 0.910747E+11 | 0.481786E+12 | 0.150456E+12 |
| July | 0.154729E+13 | 0.675054E+10 | 0.708594E+11 | 0.411299E+12 | 0.190114E+12 |
| August | 0.117651E+13 | 0.505884E+10 | 0.579845E+11 | 0.331434E+12 | 0.244318E+12 |
| September | 0.798455E+12 | 0.791716E+10 | 0.101755E+12 | 0.551333E+12 | 0.123108E+12 |
| October | 0.449809E+12 | 0.157003E+11 | 0.154159E+12 | 0.565492E+12 | 0.384351E+11 |
| November | 0.150212E+12 | 0.174724E+11 | 0.172577E+12 | 0.426950E+12 | 0.369221E+11 |
| December | 0.479151E+11 | 0.185330E+11 | 0.169682E+12 | 0.333874E+12 | 0.505152E+11 |
| Annual Sum or Average | 0.915023E+13 | 0.169848E+12 | 0.148362E+13 | 0.524890E+13 | 0.111875E+13 |
| Minimum of Months | 0.479151E+11 | 0.505884E+10 | 0.579845E+11 | 0.304072E+12 | 0.344558E+11 |
| Maximum of Months | 0.154729E+13 | 0.204091E+11 | 0.172577E+12 | 0.565492E+12 | 0.244318E+12 |