Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:30
Tabular Output Report in Format: HTML
Building: SchoolPrimary
Environment: RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750
Simulation Timestamp: 2024-07-03 12:30:47
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 5355.48 | 779.43 | 779.43 |
| Net Site Energy | 5355.48 | 779.43 | 779.43 |
| Total Source Energy | 12336.07 | 1795.38 | 1795.38 |
| Net Source Energy | 12336.07 | 1795.38 | 1795.38 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 6871.00 |
| Net Conditioned Building Area | 6871.00 |
| Unconditioned Building Area | 0.00 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 1692.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 213.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 1218.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 92.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1151.36 | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 394.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 2.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 166.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.47 |
| Refrigeration | 44.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 3135.25 | 2220.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.47 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 980.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Boiler | 0.00 | 712.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Cooling | General | 213.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 1218.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 92.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 947.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooking | 149.71 | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInFreezer | 31.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInRefrigerator | 23.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | Transformer | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | General | 394.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | General | 2.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Heater | 0.00 | 166.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.99 | |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.48 | |
| Refrigeration | General | 7.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LowTempRefrigeration | 14.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MedTempRefrigeration | 21.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 1692.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 213.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 1218.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 92.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 1151.36 | 361.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 17.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 394.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 2.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 0.00 | 166.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.47 |
| Refrigeration | Unassigned | 44.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 190.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 88.93 | 270.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Other | 176.61 | 52.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 456.30 | 323.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 190.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 88.93 | 270.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Other | 176.61 | 52.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 456.30 | 323.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 3135.254 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 3135.254 | 100.00 |
| Total On-Site and Utility Electric Sources | 3135.254 | 100.00 |
| Total Electricity End Uses | 3135.254 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | |
| Air to Air Heat Recovery for Cooling | 0.00 | |
| Air to Air Heat Recovery for Heating | 0.00 | |
| High-Temperature Geothermal* | 0.00 | |
| Solar Water Thermal | 0.00 | |
| Solar Air Thermal | 0.00 | |
| Total On-Site Thermal Sources | 0.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 718.47 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 718.47 | 100.00 |
| Total Water End Uses | 718.47 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 855.17 |
| Time Setpoint Not Met During Occupied Cooling | 37.83 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1692.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME SCHOOLPRIMARY
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |ZoneHeatingSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |ZoneElectricSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |SpaceGainsMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |PeakSpaceGainsMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |SpaceGainComponentsAtCoolingPeakMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |ComfortReportSimple55Monthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |OccupantComfortDataSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| VAV_POD_1 COOLING COIL | PSZ-AC_1:6 COOLING COIL | PSZ-AC_2:7 COOLING COIL |WindowReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 |WindowEnergyReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 |WindowZoneSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |WindowEnergyZoneSummaryMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | VAV_POD_1 HEATING COIL | PSZ-AC_1:6 HEATING COIL | PSZ-AC_2:7 HEATING COIL | VAV_POD_1 COOLING COIL | PSZ-AC_1:6 COOLING COIL | PSZ-AC_2:7 COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |FanReportMonthly
| VAV_POD_1 FAN | BATH_ZN_1_FLR_1 EXHAUST FAN | GYM_ZN_1_FLR_1 EXHAUST FAN | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN | KITCHEN_ZN_1_FLR_1 EXHAUST FAN | CAFETERIA_ZN_1_FLR_1 EXHAUST FAN | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYS1 PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_POD_1 | PSZ-AC_1:6 | PSZ-AC_2:7 |AirLoopSystemComponentLoadsMonthly
| VAV_POD_1 | PSZ-AC_1:6 | PSZ-AC_2:7 |AirLoopSystemComponentEnergyUseMonthly
| VAV_POD_1 | PSZ-AC_1:6 | PSZ-AC_2:7 |MechanicalVentilationLoadsMonthly
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:30 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
| Latitude [deg] | 47.47 |
| Longitude [deg] | -111.4 |
| Elevation [m] | 1117.00 |
| Time Zone | -7.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Above Ground Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Window Opening Area [m2] | 552.60 | 204.13 | 72.16 | 204.16 | 72.16 |
| Gross Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Above Ground Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Above Ground Wall Area [m2] | 2512.00 | 928.00 | 328.00 | 928.00 | 328.00 |
| Window Opening Area [m2] | 552.60 | 204.13 | 72.16 | 204.16 | 72.16 |
| Gross Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Above Ground Window-Wall Ratio [%] | 22.00 | 22.00 | 22.00 | 22.00 | 22.00 |
| Total | |
| Gross Roof Area [m2] | 6871.00 |
| Skylight Area [m2] | 13.38 |
| Skylight-Roof Ratio [%] | 0.19 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | Yes | Yes | 768.00 | 1.00 | 12.00 | 0.00 | 2.64 | 2.64 | 5.4810 | 18.58 | 4.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | Yes | Yes | 768.00 | 1.00 | 12.00 | 0.00 | 2.64 | 2.64 | 5.4810 | 18.58 | 4.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.60 | 17.60 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1908.00 | 1.00 | 212.00 | 0.00 | 46.64 | 46.64 | 15.0695 | 3.72 | 15.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | Yes | Yes | 768.00 | 1.00 | 12.00 | 0.00 | 2.64 | 2.64 | 5.4810 | 18.58 | 4.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 396.00 | 1.00 | 80.00 | 0.00 | 17.57 | 17.57 | 15.0695 | 3.72 | 15.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1260.00 | 1.00 | 140.00 | 0.00 | 30.80 | 30.80 | 15.0695 | 3.72 | 15.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | Yes | Yes | 648.00 | 1.00 | 72.00 | 0.00 | 15.84 | 15.84 | 15.0695 | 3.72 | 20.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | Yes | Yes | 2184.00 | 1.00 | 36.00 | 0.00 | 7.92 | 7.92 | 5.4810 | 18.58 | 4.0000 |
| LOBBY_ZN_1_FLR_1 | 171.00 | Yes | Yes | 684.00 | 1.00 | 76.00 | 0.00 | 16.72 | 16.72 | 13.9931 | 9.29 | 4.0000 |
| MECH_ZN_1_FLR_1 | 252.00 | Yes | Yes | 1008.00 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.1458 | 61.93 | 10.0000 |
| BATH_ZN_1_FLR_1 | 190.00 | Yes | Yes | 760.00 | 1.00 | 40.00 | 0.00 | 8.80 | 8.80 | 9.6875 | 18.58 | 4.0000 |
| OFFICES_ZN_1_FLR_1 | 441.00 | Yes | Yes | 1764.00 | 1.00 | 168.00 | 0.00 | 36.96 | 36.96 | 11.8403 | 18.58 | 10.8000 |
| GYM_ZN_1_FLR_1 | 357.00 | Yes | Yes | 1428.00 | 1.00 | 68.00 | 0.00 | 14.96 | 14.96 | 13.3472 | 3.10 | 5.0000 |
| KITCHEN_ZN_1_FLR_1 | 168.00 | Yes | Yes | 672.00 | 1.00 | 32.00 | 0.00 | 7.04 | 7.04 | 12.9167 | 6.22 | 1631.7643 |
| CAFETERIA_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1260.00 | 1.00 | 144.00 | 0.00 | 31.68 | 31.68 | 9.6875 | 0.93 | 25.3900 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | Yes | Yes | 1596.00 | 1.00 | 160.00 | 0.00 | 35.20 | 35.20 | 16.6840 | 9.29 | 15.0000 |
| Total | 6871.00 | 27484.00 | 2512.00 | 0.00 | 552.60 | 552.60 | 12.8652 | 4.37 | 51.7784 | |||
| Conditioned Total | 6871.00 | 27484.00 | 2512.00 | 0.00 | 552.60 | 552.60 | 12.8652 | 4.37 | 51.7784 | |||
| Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | Yes | Yes | 1.00 | CORRIDOR_POD_1_ZN_1_FLR_1 | GENERAL | CORRIDOR_POD_1_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | Yes | Yes | 1.00 | CORRIDOR_POD_2_ZN_1_FLR_1 | GENERAL | CORRIDOR_POD_2_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | Yes | Yes | 1.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | Yes | Yes | 1.00 | CORRIDOR_POD_3_ZN_1_FLR_1 | GENERAL | CORRIDOR_POD_3_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | Yes | Yes | 1.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 15.0695 | 3.72 | 15.0000 | |
| COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | Yes | Yes | 1.00 | COMPUTER_CLASS_ZN_1_FLR_1 | GENERAL | COMPUTER_CLASS_ZN_1_FLR_1 | 15.0695 | 3.72 | 20.0000 | |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | Yes | Yes | 1.00 | MAIN_CORRIDOR_ZN_1_FLR_1 | GENERAL | MAIN_CORRIDOR_ZN_1_FLR_1 | 5.4810 | 18.58 | 4.0000 | |
| LOBBY_ZN_1_FLR_1 | 171.00 | Yes | Yes | 1.00 | LOBBY_ZN_1_FLR_1 | GENERAL | LOBBY_ZN_1_FLR_1 | 13.9931 | 9.29 | 4.0000 | |
| MECH_ZN_1_FLR_1 | 252.00 | Yes | Yes | 1.00 | MECH_ZN_1_FLR_1 | GENERAL | MECH_ZN_1_FLR_1 | 16.1458 | 61.93 | 10.0000 | |
| BATH_ZN_1_FLR_1 | 190.00 | Yes | Yes | 1.00 | BATH_ZN_1_FLR_1 | GENERAL | BATH_ZN_1_FLR_1 | 9.6875 | 18.58 | 4.0000 | |
| OFFICES_ZN_1_FLR_1 | 441.00 | Yes | Yes | 1.00 | OFFICES_ZN_1_FLR_1 | GENERAL | OFFICES_ZN_1_FLR_1 | 11.8403 | 18.58 | 10.8000 | |
| GYM_ZN_1_FLR_1 | 357.00 | Yes | Yes | 1.00 | GYM_ZN_1_FLR_1 | GENERAL | GYM_ZN_1_FLR_1 | 13.3472 | 3.10 | 5.0000 | |
| KITCHEN_ZN_1_FLR_1 | 168.00 | Yes | Yes | 1.00 | KITCHEN_ZN_1_FLR_1 | GENERAL | KITCHEN_ZN_1_FLR_1 | 12.9167 | 6.22 | 1631.7643 | |
| CAFETERIA_ZN_1_FLR_1 | 315.00 | Yes | Yes | 1.00 | CAFETERIA_ZN_1_FLR_1 | GENERAL | CAFETERIA_ZN_1_FLR_1 | 9.6875 | 0.93 | 25.3900 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | Yes | Yes | 1.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | GENERAL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 16.6840 | 9.29 | 15.0000 | |
| Total | 6871.00 | 12.8652 | 2.19 | 51.7784 | |||||||
| Conditioned Total | 6871.00 | 12.8652 | 2.19 | 51.7784 | |||||||
| Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 6871.00 | 6871.00 | 0.00 | 0.00 | 12.8652 | 4.37 | 51.7784 |
| Total | 6871.00 | 6871.00 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 27-SEP-12:00 | 09-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | 02-JAN-13:09 |
| Heating | 0.00 | 1035709.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 98936.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 79557.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 72814.64 | 36063.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 1213.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 55553.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 13.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 12567.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 1379.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 309467.74 | 1084341.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 574936.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Boiler | 0.00 | 460772.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Cooling | General | 98936.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 79557.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | MiscPlug | 65099.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooking | 5999.02 | 36063.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInFreezer | 986.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInRefrigerator | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | Transformer | 1213.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | General | 55553.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | General | 13.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Heater | 0.00 | 12567.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 241.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LowTempRefrigeration | 430.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MedTempRefrigeration | 706.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 1835.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 676.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 3858.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 293.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 3646.35 | 391.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 55.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 1250.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 7.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 180.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 141.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 9929.35 | 2406.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 267.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 98.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 561.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 42.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 530.69 | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 8.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 182.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 1.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 26.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1445.11 | 350.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 267.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 98.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 561.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 42.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 530.69 | 56.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 8.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 182.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 1.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 26.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 20.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1445.11 | 350.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
AirTerminal:SingleDuct:VAV:Reheat| Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 0.739929 | 0.101953 | 0.391000 | 0.289312 | 0.391000 | 0.500000 | 0.003737 | 0.000104 | 0.576920 | 12.89 | 0.008000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 3.10 | 0.117336 | 0.450000 | 1.39 | 0.450000 | 0.500000 | 0.003247 | 0.000334 | 1.85 | 12.89 | 0.008000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 0.621370 | 0.235454 | 0.300000 | 0.186411 | 0.627877 | 0.500000 | 0.001618 | 0.000094 | 0.522643 | 12.89 | 0.008000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 0.665236 | 0.113400 | 0.435000 | 0.289378 | 0.435000 | 0.500000 | 0.003360 | 0.000103 | 0.570366 | 12.89 | 0.008000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | 2.64 | 0.137671 | 0.528000 | 1.39 | 0.528000 | 0.500000 | 0.002767 | 0.000328 | 1.82 | 12.89 | 0.008000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 0.734442 | 0.102715 | 0.394000 | 0.289370 | 0.394000 | 0.500000 | 0.003709 | 0.000104 | 0.575043 | 12.89 | 0.008000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 3.06 | 0.118703 | 0.455000 | 1.39 | 0.455000 | 0.500000 | 0.003210 | 0.000331 | 1.83 | 12.89 | 0.008000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 0.619292 | 0.236244 | 0.300000 | 0.185788 | 0.629984 | 0.500000 | 0.001613 | 0.000094 | 0.521990 | 12.89 | 0.008000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 0.665622 | 0.113335 | 0.434000 | 0.288880 | 0.434000 | 0.500000 | 0.003362 | 0.000103 | 0.570544 | 12.89 | 0.008000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | 2.64 | 0.137586 | 0.527000 | 1.39 | 0.527000 | 0.500000 | 0.002769 | 0.000328 | 1.82 | 12.89 | 0.008000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 0.735074 | 0.102626 | 0.393000 | 0.288884 | 0.393000 | 0.500000 | 0.003712 | 0.000104 | 0.575261 | 12.89 | 0.008000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 3.08 | 0.118201 | 0.453000 | 1.39 | 0.453000 | 0.500000 | 0.003223 | 0.000332 | 1.84 | 12.89 | 0.008000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 0.625451 | 0.233918 | 0.300000 | 0.187635 | 0.623781 | 0.500000 | 0.001629 | 0.000094 | 0.522736 | 12.89 | 0.008000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 0.670976 | 0.112430 | 0.431000 | 0.289191 | 0.431000 | 0.500000 | 0.003389 | 0.000103 | 0.572184 | 12.89 | 0.008000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | 1.78 | 0.135029 | 0.517000 | 0.919031 | 0.517000 | 0.500000 | 0.002822 | 0.000222 | 1.23 | 12.89 | 0.008000 |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | 0.981372 | 0.125787 | 0.482000 | 0.473021 | 0.482000 | 0.500000 | 0.003029 | 0.000109 | 0.603507 | 12.89 | 0.008000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | 1.35 | 0.309023 | 0.300000 | 0.403904 | 0.824060 | 0.500000 | 0.001233 | 0.000225 | 1.24 | 12.89 | 0.008000 |
| LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | 0.787069 | 0.165554 | 0.300000 | 0.236121 | 0.441476 | 0.500000 | 0.002301 | 0.000132 | 0.732930 | 12.89 | 0.008000 |
| MECH_ZN_1_FLR_1 VAV BOX COMPONENT | 0.935496 | 0.205264 | 0.300000 | 0.280649 | 0.547372 | 0.500000 | 0.001856 | 0.000075 | 0.415399 | 12.89 | 0.008000 |
| BATH_ZN_1_FLR_1 VAV BOX COMPONENT | 0.625945 | 0.231298 | 0.300000 | 0.187784 | 0.616795 | 0.500000 | 0.001647 | 0.000103 | 0.570768 | 12.89 | 0.008000 |
| OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | 1.91 | 0.469881 | 0.500000 | 0.002162 | 0.000293 | 1.62 | 12.89 | 0.008000 | |||
| GYM_ZN_1_FLR_1 VAV BOX COMPONENT | 2.13 | 0.127964 | 0.398000 | 0.846093 | 0.398000 | 0.500000 | 0.002977 | 0.000217 | 1.20 | 12.89 | 0.008000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | 2.02 | 0.150372 | 0.300000 | 0.606573 | 0.400991 | 0.500000 | 0.002534 | 0.000261 | 1.45 | 12.89 | 0.008000 |
| Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11907.98 | 0.000104 | 277.75 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 38222.10 | 0.000334 | 891.52 |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 10788.57 | 0.000094 | 251.64 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11772.67 | 0.000103 | 274.59 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 37498.14 | 0.000328 | 874.63 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11869.23 | 0.000104 | 276.84 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 37869.19 | 0.000331 | 883.28 |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 10775.08 | 0.000094 | 251.33 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11776.35 | 0.000103 | 274.68 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 37513.27 | 0.000328 | 874.98 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11873.72 | 0.000104 | 276.95 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 37986.14 | 0.000332 | 886.01 |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 10790.49 | 0.000094 | 251.69 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11810.21 | 0.000103 | 275.47 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 25329.04 | 0.000222 | 590.79 |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | 12456.90 | 0.000109 | 290.55 |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | 25693.54 | 0.000225 | 599.30 |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | 15128.47 | 0.000132 | 352.87 |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 8574.96 | 0.000075 | 200.01 |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11781.56 | 0.000103 | 274.80 |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | 33470.24 | 0.000293 | 780.68 |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | 24777.59 | 0.000217 | 577.93 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | 29844.87 | 0.000261 | 696.12 |
| Design Size Maximum Air Flow Rate [m3/s] | |
| KITCHEN_ZN_1_FLR_1 DIRECT AIR | 1.77 |
| CAFETERIA_ZN_1_FLR_1 DIRECT AIR | 3.05 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| VAV_POD_1 | 16.73 | 13.79 | 33.10 | 23.23 | 32.89 | 32.89 | 0.300000 | 0.706377 | 32.89 |
| PSZ-AC_1:6 | 1.77 | 1.77 | 1.77 | 1.77 | 1.77 | 1.77 | 1.00 | 1.00 | 1.77 |
| PSZ-AC_2:7 | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 1.00 | 1.00 | 3.05 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| VAV_POD_1_OA_CONTROLLER | 32.89 | |
| PSZ-AC_1:6_OA_CONTROLLER | 1.77 | 0.254814 |
| PSZ-AC_2:7_OA_CONTROLLER | 3.05 | 1.49 |
| Design Size High Speed Rated Air Flow Rate [m3/s] | Design Size High Speed Gross Rated Total Cooling Capacity [W] | Design Size High Speed Rated Sensible Heat Ratio | Design Size Low Speed Rated Air Flow Rate [m3/s] | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | Design Size Low Speed Gross Rated Sensible Heat Ratio | |
| VAV_POD_1 COOLING COIL | 32.89 | 601222.91 | 0.800906 | 10.96 | 200387.60 | 0.800906 |
| Design Size Nominal Capacity [W] | |
| VAV_POD_1 HEATING COIL | 422739.69 |
| PSZ-AC_1:6 HEATING COIL | 34404.54 |
| PSZ-AC_2:7 HEATING COIL | 112439.17 |
| Design Size Maximum Flow Rate [m3/s] | |
| VAV_POD_1 FAN | 32.89 |
| Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
| PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.77 | 2936.62 |
| PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | 3.05 | 4952.98 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| PSZ-AC_1:6_UNITARY_PACKAGE_DX | 1.77 | 1.77 | 1.77 | 1.77 | 35017.39 | 34404.54 | 32.11 | 1.00 |
| PSZ-AC_2:7_UNITARY_PACKAGE_DX | 3.05 | 3.05 | 3.05 | 3.05 | 64918.53 | 112439.17 | 32.11 | 1.00 |
| User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
| PSZ-AC_1:6 COOLING COIL | 1.77 | 0.883462 | 1.18 | 35017.39 | 17508.69 | 0.780090 | 0.780090 |
| PSZ-AC_2:7 COOLING COIL | 3.05 | 1.53 | 2.04 | 64918.53 | 32459.26 | 0.753250 | 0.753250 |
| Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
| HEATSYS1 | 0.004195 | 0.503396 |
| SWHSYS1 | 0.000105 | 0.012650 |
| Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
| HEATSYS1 PUMP | 0.004195 | 1263.34 | 0.000000 |
| Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
| HEATSYS1 BOILER | 479510.31 | 479510.31 | 0.004195 |
| Design Flow Rate [m3/s] | Design Power Consumption [W] | |
| SWHSYS1 PUMP | 0.000105 | 13.47 |
| Use Side Design Flow Rate [m3/s] | |
| SWHSYS1 WATER HEATER | 0.000105 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| Possible Shadow Receivers | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | BATH_ZN_1_FLR_1_WALL_5 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | BATH_ZN_1_FLR_1_WALL_5 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | BATH_ZN_1_FLR_1_WALL_5 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | |
| BATH_ZN_1_FLR_1_WALL_5 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | |
| CAFETERIA_ZN_1_FLR_1_WALL_3 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | CAFETERIA_ZN_1_FLR_1_WALL_3 | |
| Possible Shadow Receivers | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | |
| LOBBY_ZN_1_FLR_1_WALL_1 | LOBBY_ZN_1_FLR_1_WALL_1_DOOR | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| BATH_ZN_1_FLR_1_WALL_5 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | |
| OFFICES_ZN_1_FLR_1_WALL_1 | OFFICES_ZN_1_FLR_1_WALL_1_DOOR | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | |
| OFFICES_ZN_1_FLR_1_WALL_2 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | |
| GYM_ZN_1_FLR_1_WALL_2 | GYM_ZN_1_FLR_1_WALL_2_DOOR | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | |
| GYM_ZN_1_FLR_1_CEILING | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | |
| KITCHEN_ZN_1_FLR_1_WALL_2 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | |
| CAFETERIA_ZN_1_FLR_1_WALL_2 | CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | |
| CAFETERIA_ZN_1_FLR_1_WALL_3 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | Yes | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 8.60 | 2.80 | -4.10 | -8.80 | -2.20 | 0.30 | 6.70 | 10.10 | 16.50 | 20.60 | 19.20 | 14.70 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | Great Falls Intl Arpt MT USA TMY3 WMO#=727750 | 47.47 | -111.38 | -7.00 | 1117.00 | 88606 | 1.0531 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 7.03 | 29.40 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | SchoolPrimary | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 25 | 288 | 92 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.0 | -64.00 | 0.00 | 0.00 | -58.50 | 4.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 0.00 | 9.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 0.0 | -53.00 | 0.00 | 0.00 | -26.50 | 4.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 0.00 | 9.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | 0.0 | -64.00 | 9.00 | 0.00 | -32.00 | 10.50 | 2.00 | 1 | 1 | 1 | -64.00 | 0.00 | 9.00 | 12.00 | 0.00 | 4.00 | 4.00 | 768.00 | TARP | TARP | 192.00 | 12.00 | 9.36 | 2.64 | 8 | 1 | 0 | Yes |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.0 | -64.00 | 12.00 | 0.00 | -58.50 | 16.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 12.00 | 21.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 0.0 | -53.00 | 12.00 | 0.00 | -26.50 | 16.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 12.00 | 21.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.0 | -64.00 | 30.00 | 0.00 | -58.50 | 34.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 30.00 | 39.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 0.0 | -53.00 | 30.00 | 0.00 | -26.50 | 34.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 30.00 | 39.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | 0.0 | -64.00 | 39.00 | 0.00 | -32.00 | 40.50 | 2.00 | 1 | 1 | 1 | -64.00 | 0.00 | 39.00 | 42.00 | 0.00 | 4.00 | 4.00 | 768.00 | TARP | TARP | 192.00 | 12.00 | 9.36 | 2.64 | 8 | 1 | 0 | Yes |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.0 | -64.00 | 42.00 | 0.00 | -58.50 | 46.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 42.00 | 51.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 0.0 | -53.00 | 42.00 | 0.00 | -26.50 | 46.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 42.00 | 51.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.0 | -64.00 | 61.00 | 0.00 | -58.50 | 65.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 61.00 | 70.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.45 | 17.60 | 6 | 4 | 0 | Yes |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 0.0 | -53.00 | 61.00 | 0.00 | -26.50 | 65.50 | 2.00 | 1 | 1 | 1 | -53.00 | 0.00 | 61.00 | 70.00 | 0.00 | 4.00 | 4.00 | 1908.00 | TARP | TARP | 477.00 | 212.00 | 161.46 | 46.64 | 6 | 5 | 0 | Yes |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | 0.0 | -64.00 | 70.00 | 0.00 | -32.00 | 71.50 | 2.00 | 1 | 1 | 1 | -64.00 | 0.00 | 70.00 | 73.00 | 0.00 | 4.00 | 4.00 | 768.00 | TARP | TARP | 192.00 | 12.00 | 9.36 | 2.64 | 9 | 1 | 0 | Yes |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.0 | -64.00 | 73.00 | 0.00 | -58.50 | 77.50 | 2.00 | 1 | 1 | 1 | -64.00 | -53.00 | 73.00 | 82.00 | 0.00 | 4.00 | 4.00 | 396.00 | TARP | TARP | 99.00 | 80.00 | 60.48 | 17.57 | 6 | 4 | 0 | Yes |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.0 | -53.00 | 73.00 | 0.00 | -35.50 | 77.50 | 2.00 | 1 | 1 | 1 | -53.00 | -18.00 | 73.00 | 82.00 | 0.00 | 4.00 | 4.00 | 1260.00 | TARP | TARP | 315.00 | 140.00 | 105.30 | 30.80 | 6 | 5 | 0 | Yes |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | 0.0 | -18.00 | 73.00 | 0.00 | -9.00 | 77.50 | 2.00 | 1 | 1 | 1 | -18.00 | 0.00 | 73.00 | 82.00 | 0.00 | 4.00 | 4.00 | 648.00 | TARP | TARP | 162.00 | 72.00 | 54.21 | 15.84 | 6 | 3 | 0 | Yes |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | 0.0 | 0.00 | 9.00 | 0.00 | 6.50 | 30.00 | 2.00 | 1 | 1 | 1 | 0.00 | 13.00 | 9.00 | 51.00 | 0.00 | 4.00 | 4.00 | 2184.00 | TARP | TARP | 546.00 | 36.00 | 26.13 | 7.92 | 11 | 3 | 0 | Yes |
| 18 | LOBBY_ZN_1_FLR_1 | 0.0 | 0.00 | 0.00 | 0.00 | 9.50 | 4.50 | 2.00 | 1 | 1 | 1 | 0.00 | 19.00 | 0.00 | 9.00 | 0.00 | 4.00 | 4.00 | 684.00 | TARP | TARP | 171.00 | 76.00 | 57.33 | 16.72 | 7 | 3 | 0 | Yes |
| 19 | MECH_ZN_1_FLR_1 | 0.0 | 13.00 | 9.00 | 0.00 | 16.00 | 30.00 | 2.00 | 1 | 1 | 1 | 13.00 | 19.00 | 9.00 | 51.00 | 0.00 | 4.00 | 4.00 | 1008.00 | TARP | TARP | 252.00 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
| 20 | BATH_ZN_1_FLR_1 | 0.0 | 0.00 | 51.00 | 0.00 | 9.50 | 56.00 | 2.00 | 1 | 1 | 1 | 0.00 | 19.00 | 51.00 | 61.00 | 0.00 | 4.00 | 4.00 | 760.00 | TARP | TARP | 190.00 | 40.00 | 31.20 | 8.80 | 7 | 1 | 0 | Yes |
| 21 | OFFICES_ZN_1_FLR_1 | 0.0 | 19.00 | 0.00 | 0.00 | 29.50 | 10.50 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 0.00 | 21.00 | 0.00 | 4.00 | 4.00 | 1764.00 | TARP | TARP | 441.00 | 168.00 | 129.09 | 36.96 | 7 | 4 | 0 | Yes |
| 22 | GYM_ZN_1_FLR_1 | 0.0 | 19.00 | 21.00 | 0.00 | 29.50 | 29.50 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 21.00 | 38.00 | 0.00 | 4.00 | 4.00 | 1428.00 | TARP | TARP | 357.00 | 68.00 | 51.09 | 28.34 | 6 | 12 | 0 | Yes |
| 23 | KITCHEN_ZN_1_FLR_1 | 0.0 | 19.00 | 38.00 | 0.00 | 29.50 | 42.00 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 38.00 | 46.00 | 0.00 | 4.00 | 4.00 | 672.00 | TARP | TARP | 168.00 | 32.00 | 24.96 | 7.04 | 6 | 1 | 0 | Yes |
| 24 | CAFETERIA_ZN_1_FLR_1 | 0.0 | 19.00 | 46.00 | 0.00 | 29.50 | 53.50 | 2.00 | 1 | 1 | 1 | 19.00 | 40.00 | 46.00 | 61.00 | 0.00 | 4.00 | 4.00 | 1260.00 | TARP | TARP | 315.00 | 144.00 | 110.37 | 31.68 | 7 | 4 | 0 | Yes |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.0 | 0.00 | 61.00 | 0.00 | 9.50 | 71.50 | 2.00 | 1 | 1 | 1 | 0.00 | 19.00 | 61.00 | 82.00 | 0.00 | 4.00 | 4.00 | 1596.00 | TARP | TARP | 399.00 | 160.00 | 122.85 | 35.20 | 8 | 4 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 3.716 | 0.269 | 15.069 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 30.069 | No |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 3.716 | 0.269 | 15.069 | 20.000 | 0.000 | 0.000 | 0.000 | 0.000 | 35.069 | No |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 18.579 | 5.382E-002 | 5.481 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.481 | No |
| 18 | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 9.289 | 0.108 | 13.993 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 17.993 | No |
| 19 | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 61.932 | 1.615E-002 | 16.146 | 10.000 | 0.000 | 0.000 | 0.000 | 0.000 | 26.146 | No |
| 20 | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 18.578 | 5.383E-002 | 9.688 | 4.000 | 0.000 | 0.000 | 0.000 | 0.000 | 13.688 | No |
| 21 | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 18.579 | 5.382E-002 | 11.840 | 10.800 | 0.000 | 0.000 | 0.000 | 0.000 | 22.640 | No |
| 22 | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 3.096 | 0.323 | 13.347 | 5.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18.347 | No |
| 23 | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 6.224 | 0.161 | 12.917 | 200.664 | 1431.100 | 0.000 | 0.000 | 0.000 | 1644.681 | No |
| 24 | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 0.929 | 1.076 | 9.688 | 25.390 | 0.000 | 0.000 | 0.000 | 0.000 | 35.078 | No |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 9.289 | 0.108 | 16.684 | 15.000 | 0.000 | 0.000 | 0.000 | 0.000 | 31.684 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 10.3 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 10.3 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 128.4 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 122 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 10.3 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 26.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 25 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | BLDG_OCC_SCH | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 84.8 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 81 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | BLDG_OCC_SCH_EXTEND | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 43.6 | 0.269 | 3.716 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 41 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 17 | MECH_ZN_1_FLR_1 | BLDG_OCC_SCH | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 4.1 | 1.615E-002 | 61.932 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 4 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 18 | BATH_ZN_1_FLR_1 | BLDG_OCC_SCH | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 10.2 | 5.383E-002 | 18.578 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 19 | OFFICES_ZN_1_FLR_1 | BLDG_OCC_SCH_OFFICES_W_SB | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 23.7 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 23 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 20 | GYM_ZN_1_FLR_1 | BLDG_OCC_SCH_GYM | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 115.3 | 0.323 | 3.096 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 110 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 21 | KITCHEN_ZN_1_FLR_1 | BLDG_OCC_SCH | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 27.0 | 0.161 | 6.224 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 26 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 22 | CAFETERIA_ZN_1_FLR_1 | BLDG_OCC_SCH_CAFETERIA | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 339.1 | 1.076 | 0.929 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 322 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 23 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | BLDG_OCC_SCH | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 43.0 | 0.108 | 9.289 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 41 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 24 | MAIN_CORRIDOR_ZN_1_FLR_1 | BLDG_OCC_SCH | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 29.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 25 | LOBBY_ZN_1_FLR_1 | BLDG_OCC_SCH | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 18.4 | 0.108 | 9.289 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 1052.352 | 5.481 | 101.834 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1052.352 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 1052.352 | 5.481 | 101.834 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1052.352 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 7188.132 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 7188.132 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 1052.352 | 5.481 | 101.834 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1052.352 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1491.877 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1491.877 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | LTG_SCH_CLASSROOM | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 4746.880 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 4746.880 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1_LIGHTS | LTG_SCH_COMPUTER_ROOM | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 2441.253 | 15.069 | 55.998 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2441.253 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1_LIGHTS | LTG_SCH_CORRIDOR | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 2992.626 | 5.481 | 101.832 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2992.626 |
| 18 | LOBBY_ZN_1_FLR_1_LIGHTS | LTG_SCH_LOBBY | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 2392.815 | 13.993 | 129.988 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2392.815 |
| 19 | MECH_ZN_1_FLR_1_LIGHTS | LTG_SCH_MECHANICAL | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 4068.754 | 16.146 | 999.940 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 4068.754 |
| 20 | BATH_ZN_1_FLR_1_LIGHTS | LTG_SCH_BATH | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 1840.627 | 9.688 | 179.977 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 1840.627 |
| 21 | OFFICES_ZN_1_FLR_1_LIGHTS | LTG_SCH_OFFICE | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 5221.568 | 11.840 | 219.981 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 5221.568 |
| 22 | GYM_ZN_1_FLR_1_LIGHTS | LTG_SCH_GYM | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 4764.965 | 13.347 | 41.323 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 4764.965 |
| 23 | KITCHEN_ZN_1_FLR_1_LIGHTS | LTG_SCH_KITCHEN | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 2170.002 | 12.917 | 80.391 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 2170.002 |
| 24 | CAFETERIA_ZN_1_FLR_1_LIGHTS | LTG_SCH_CAFETERIA | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 3051.566 | 9.688 | 9.000 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 3051.566 |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_LIGHTS | LTG_SCH_LIBRARY | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 6656.932 | 16.684 | 154.978 | 0.000 | 0.370 | 0.200 | 0.430 | 1.000 | LightsWired | 0.000 | 6656.932 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 768.000 | 4.000 | 74.318 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 149.700 | 729.600 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 768.000 | 4.000 | 74.318 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 149.700 | 729.600 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 7155.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1394.662 | 6797.250 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 768.000 | 4.000 | 74.318 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 149.700 | 729.600 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 1485.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 289.458 | 1410.750 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 4725.000 | 15.000 | 55.740 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 921.003 | 4488.750 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 3240.000 | 20.000 | 74.320 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 631.545 | 3078.000 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 2184.000 | 4.000 | 74.316 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 425.708 | 2074.800 |
| 18 | LOBBY_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 684.000 | 4.000 | 37.158 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 133.326 | 649.800 |
| 19 | MECH_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 2520.000 | 10.000 | 619.317 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 491.202 | 2394.000 |
| 20 | BATH_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 760.000 | 4.000 | 74.313 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 148.140 | 722.000 |
| 21 | OFFICES_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 4762.800 | 10.800 | 200.653 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 928.371 | 4524.660 |
| 22 | GYM_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 1785.000 | 5.000 | 15.480 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 347.935 | 1695.750 |
| 23 | KITCHEN_ZN_1_FLR_1_MISCELEC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 31995.600 | 190.450 | 1185.330 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 3199.560 | 7998.900 |
| 24 | KITCHEN_ZN_1_FLR_1_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 986.000 | 5.869 | 36.528 | 0.000 | 0.000 | 1.000 | 0.000 | ReachInFreezer | 986.000 | 986.000 |
| 25 | KITCHEN_ZN_1_FLR_1_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 730.000 | 4.345 | 27.044 | 0.000 | 0.000 | 1.000 | 0.000 | ReachInRefrigerator | 730.000 | 730.000 |
| 26 | CAFETERIA_ZN_1_FLR_1_PLUGMISC_EQUIP | KITCHEN_ELEC_EQUIP_SCH | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 7997.850 | 25.390 | 23.587 | 0.000 | 0.500 | 0.000 | 0.500 | Cooking | 799.785 | 1999.463 |
| 27 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_PLUGMISC_EQUIP | BLDG_EQUIP_SCH | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 5985.000 | 15.000 | 139.335 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 1166.604 | 5685.750 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | KITCHEN_ZN_1_FLR_1_MISCGAS_EQUIP | KITCHEN_GAS_EQUIP_SCH | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 240424.800 | 1431.100 | 8906.931 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 4808.496 | 48084.960 |
| Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
| 1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
| 2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 6 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 7 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 8 | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1980E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 9 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 10 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 11 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 12 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 13 | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1980E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 14 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 15 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 46 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 16 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 47 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 17 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 48 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 18 | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1980E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 19 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 50 | 2 | 7 | 0.167 | 0.2658 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 20 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 51 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 21 | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR | 52 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 22 | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR | 53 | 2 | 7 | 0.167 | 0.2090E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 23 | LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR | 54 | 2 | 7 | 0.167 | 0.1435 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 24 | MECH_ZN_1_FLR_1_FLOOR_FFACTOR | 55 | 2 | 8 | 0.167 | 0.5650E-02 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 25 | BATH_ZN_1_FLR_1_FLOOR_FFACTOR | 56 | 2 | 7 | 0.167 | 0.6720E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 26 | OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR | 57 | 2 | 7 | 0.167 | 0.1226 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 27 | GYM_ZN_1_FLR_1_FLOOR_FFACTOR | 58 | 2 | 7 | 0.167 | 0.6074E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 28 | KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR | 59 | 2 | 7 | 0.167 | 0.6074E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 29 | CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR | 60 | 2 | 7 | 0.167 | 0.1477 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 30 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR | 61 | 2 | 7 | 0.167 | 0.1292 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
| 1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
| 2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
| 3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
| 4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
| 5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
| 6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
| 7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
| 8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
| 9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
| 11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 50.42 |
| 17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 50.42 |
| 27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 32 | ~FC_Insulation_11 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 34 | ~FC_Insulation_12 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 36 | ~FC_Insulation_13 | 0.0000 | 0.000 | 0.000 | 0.000 | 50.42 |
| 37 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 38 | ~FC_Insulation_14 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.685 |
| 39 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 40 | ~FC_Insulation_15 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 41 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 42 | ~FC_Insulation_16 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 43 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 44 | ~FC_Insulation_17 | 0.0000 | 0.000 | 0.000 | 0.000 | 47.78 |
| 45 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 46 | ~FC_Insulation_18 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.890 |
| 47 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 48 | ~FC_Insulation_19 | 0.0000 | 0.000 | 0.000 | 0.000 | 176.9 |
| 49 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 50 | ~FC_Insulation_20 | 0.0000 | 0.000 | 0.000 | 0.000 | 14.80 |
| 51 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 52 | ~FC_Insulation_21 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.077 |
| 53 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 54 | ~FC_Insulation_22 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.39 |
| 55 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 56 | ~FC_Insulation_23 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.39 |
| 57 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 58 | ~FC_Insulation_24 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.693 |
| 59 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 60 | ~FC_Insulation_25 | 0.0000 | 0.000 | 0.000 | 0.000 | 7.662 |
| 61 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| Time | Outside | Cross | Inside | Flux (except final one) | |
| 1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
| 2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
| 3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
| 4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
| 5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
| 6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
| 7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
| 8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
| 9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
| 10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
| 11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
| 12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
| 13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
| 14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
| 15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
| 16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
| 17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
| 18 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
| 19 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
| 20 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
| 21 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
| 22 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
| 23 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
| 24 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
| 25 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
| 26 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
| 27 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
| 28 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
| 29 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
| 30 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 31 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 32 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 33 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 34 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 35 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 36 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 37 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 38 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 39 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 40 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 41 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 42 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 43 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 44 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 45 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 46 | 7 | -0.21707302E-07 | -0.21810081E-14 | -0.84952625E-14 | 0.13770899E-15 |
| 47 | 6 | 0.21407607E-05 | 0.45739277E-09 | 0.32038929E-02 | -0.26876939E-04 |
| 48 | 5 | -0.77205346E-04 | 0.24803070E-06 | -0.22452059 | 0.19631768E-02 |
| 49 | 4 | 0.12599243E-02 | 0.10780209E-04 | 4.8427850 | -0.45392265E-01 |
| 50 | 3 | -0.93942915E-02 | 0.82583168E-04 | -38.096111 | 0.39947953 |
| 51 | 2 | 0.30967349E-01 | 0.13253122E-03 | 116.62920 | -1.4198824 |
| 52 | 1 | -0.43132160E-01 | 0.38654114E-04 | -143.99276 | 2.0504445 |
| 53 | 0 | 0.20639933E-01 | 0.87079362E-06 | 60.838472 | |
| 54 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 55 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 56 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 57 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 58 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 59 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 60 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 61 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 62 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 63 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 64 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 65 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 66 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 67 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 68 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 69 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 70 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 71 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 72 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 73 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 74 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 75 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 76 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 77 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 78 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 79 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 80 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 81 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 82 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 83 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 84 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 85 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 86 | 7 | -0.21707302E-07 | -0.21810081E-14 | -0.84952625E-14 | 0.13770899E-15 |
| 87 | 6 | 0.21407607E-05 | 0.45739277E-09 | 0.32038929E-02 | -0.26876939E-04 |
| 88 | 5 | -0.77205346E-04 | 0.24803070E-06 | -0.22452059 | 0.19631768E-02 |
| 89 | 4 | 0.12599243E-02 | 0.10780209E-04 | 4.8427850 | -0.45392265E-01 |
| 90 | 3 | -0.93942915E-02 | 0.82583168E-04 | -38.096111 | 0.39947953 |
| 91 | 2 | 0.30967349E-01 | 0.13253122E-03 | 116.62920 | -1.4198824 |
| 92 | 1 | -0.43132160E-01 | 0.38654114E-04 | -143.99276 | 2.0504445 |
| 93 | 0 | 0.20639933E-01 | 0.87079362E-06 | 60.838472 | |
| 94 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 95 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 96 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 97 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 98 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 99 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 100 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 101 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 102 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 103 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 104 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 105 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 106 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 107 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 108 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 109 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 110 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 111 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 112 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 113 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 114 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 115 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 116 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 117 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 118 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 119 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 120 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 121 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 122 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 123 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 124 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 125 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 126 | 7 | -0.21707302E-07 | -0.21810081E-14 | -0.84952625E-14 | 0.13770899E-15 |
| 127 | 6 | 0.21407607E-05 | 0.45739277E-09 | 0.32038929E-02 | -0.26876939E-04 |
| 128 | 5 | -0.77205346E-04 | 0.24803070E-06 | -0.22452059 | 0.19631768E-02 |
| 129 | 4 | 0.12599243E-02 | 0.10780209E-04 | 4.8427850 | -0.45392265E-01 |
| 130 | 3 | -0.93942915E-02 | 0.82583168E-04 | -38.096111 | 0.39947953 |
| 131 | 2 | 0.30967349E-01 | 0.13253122E-03 | 116.62920 | -1.4198824 |
| 132 | 1 | -0.43132160E-01 | 0.38654114E-04 | -143.99276 | 2.0504445 |
| 133 | 0 | 0.20639933E-01 | 0.87079362E-06 | 60.838472 | |
| 134 | 7 | -0.15772792E-08 | -0.28680592E-15 | 0.12691911E-13 | -0.18935729E-15 |
| 135 | 6 | 0.74265588E-05 | 0.51025248E-08 | 0.31846465E-02 | -0.26715484E-04 |
| 136 | 5 | -0.53586969E-03 | 0.30237275E-05 | -0.22342768 | 0.19535297E-02 |
| 137 | 4 | 0.12337436E-01 | 0.13766923E-03 | 4.8246004 | -0.45217444E-01 |
| 138 | 3 | -0.10837303 | 0.10950400E-02 | -37.993479 | 0.39834495 |
| 139 | 2 | 0.38485319 | 0.18220149E-02 | 116.42957 | -1.4172120 |
| 140 | 1 | -0.55550401 | 0.55531650E-03 | -143.87530 | 2.0485138 |
| 141 | 0 | 0.27084135 | 0.13419224E-04 | 60.838472 | |
| 142 | 7 | -0.29578731E-08 | -0.18610472E-14 | 0.16360026E-14 | -0.48190060E-16 |
| 143 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 144 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 145 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 146 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 147 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 148 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 149 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 150 | 7 | -0.29578731E-08 | -0.18610472E-14 | 0.16360026E-14 | -0.48190060E-16 |
| 151 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 152 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 153 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 154 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 155 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 156 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 157 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 158 | 7 | -0.20570949E-07 | -0.14658537E-14 | -0.76832012E-14 | 0.12671469E-15 |
| 159 | 6 | 0.20860838E-05 | 0.47270270E-09 | 0.32038024E-02 | -0.26876180E-04 |
| 160 | 5 | -0.77354338E-04 | 0.25871613E-06 | -0.22451551 | 0.19631320E-02 |
| 161 | 4 | 0.12908389E-02 | 0.11299182E-04 | 4.8427016 | -0.45391462E-01 |
| 162 | 3 | -0.97548753E-02 | 0.86890235E-04 | -38.095646 | 0.39947438 |
| 163 | 2 | 0.32375441E-01 | 0.13995703E-03 | 116.62830 | -1.4198704 |
| 164 | 1 | -0.45248243E-01 | 0.40996175E-04 | -143.99224 | 2.0504359 |
| 165 | 0 | 0.21692461E-01 | 0.93166815E-06 | 60.838472 | |
| 166 | 7 | -0.29578731E-08 | -0.18610471E-14 | 0.16360024E-14 | -0.48190056E-16 |
| 167 | 6 | 0.41253938E-05 | 0.27444675E-08 | 0.31942391E-02 | -0.26795954E-04 |
| 168 | 5 | -0.29029299E-03 | 0.16230583E-05 | -0.22397289 | 0.19583421E-02 |
| 169 | 4 | 0.66360716E-02 | 0.73828161E-04 | 4.8336813 | -0.45304736E-01 |
| 170 | 3 | -0.58145393E-01 | 0.58669454E-03 | -38.044778 | 0.39891197 |
| 171 | 2 | 0.20628369 | 0.97546675E-03 | 116.52942 | -1.4185475 |
| 172 | 1 | -0.29762541 | 0.29693282E-03 | -143.93407 | 2.0494798 |
| 173 | 0 | 0.14507897 | 0.72057125E-05 | 60.838472 | |
| 174 | 8 | 0.57026216E-10 | -0.29656739E-13 | 0.26072253E-13 | -0.16907584E-15 |
| 175 | 7 | -0.80728763E-07 | 0.14958947E-11 | -0.10196182E-04 | 0.85534123E-07 |
| 176 | 6 | 0.59163330E-05 | 0.23390251E-08 | 0.39199948E-02 | -0.33137873E-04 |
| 177 | 5 | -0.14678961E-03 | 0.29443049E-06 | -0.24001665 | 0.21083805E-02 |
| 178 | 4 | 0.15257864E-02 | 0.63469284E-05 | 4.9653291 | -0.46676227E-01 |
| 179 | 3 | -0.74362311E-02 | 0.30151767E-04 | -38.474208 | 0.40407555 |
| 180 | 2 | 0.17883035E-01 | 0.32406056E-04 | 117.10039 | -1.4265819 |
| 181 | 1 | -0.20235698E-01 | 0.62001922E-05 | -144.19380 | 2.0537490 |
| 182 | 0 | 0.84795330E-02 | 0.69040512E-07 | 60.838472 | |
| 183 | 7 | -0.63667935E-08 | -0.10874325E-13 | 0.11269204E-14 | -0.19557179E-16 |
| 184 | 6 | 0.22887183E-05 | 0.12967685E-08 | 0.32001644E-02 | -0.26845660E-04 |
| 185 | 5 | -0.14389595E-03 | 0.76205050E-06 | -0.22430950 | 0.19613133E-02 |
| 186 | 4 | 0.31719958E-02 | 0.34552480E-04 | 4.8392847 | -0.45358602E-01 |
| 187 | 3 | -0.27412176E-01 | 0.27382890E-03 | -38.076416 | 0.39926170 |
| 188 | 2 | 0.96706121E-01 | 0.45412367E-03 | 116.59097 | -1.4193709 |
| 189 | 1 | -0.13917125 | 0.13776341E-03 | -143.97030 | 2.0500753 |
| 190 | 0 | 0.67751290E-01 | 0.33403087E-05 | 60.838472 | |
| 191 | 7 | -0.34692083E-08 | -0.29835039E-14 | 0.22457095E-14 | -0.46878358E-16 |
| 192 | 6 | 0.35887165E-05 | 0.23456121E-08 | 0.31958645E-02 | -0.26809589E-04 |
| 193 | 5 | -0.24929292E-03 | 0.13860889E-05 | -0.22406525 | 0.19591573E-02 |
| 194 | 4 | 0.56768486E-02 | 0.63026314E-04 | 4.8352193 | -0.45319520E-01 |
| 195 | 3 | -0.49670058E-01 | 0.50068761E-03 | -38.053464 | 0.39900799 |
| 196 | 2 | 0.17611533 | 0.83223021E-03 | 116.54632 | -1.4187736 |
| 197 | 1 | -0.25403345 | 0.25321776E-03 | -143.94402 | 2.0496434 |
| 198 | 0 | 0.12381374 | 0.61501487E-05 | 60.838472 | |
| 199 | 7 | -0.70485818E-08 | -0.82048821E-14 | -0.11525862E-14 | 0.12346975E-16 |
| 200 | 6 | 0.21636134E-05 | 0.11761400E-08 | 0.32006654E-02 | -0.26849864E-04 |
| 201 | 5 | -0.13228193E-03 | 0.68999669E-06 | -0.22433795 | 0.19615643E-02 |
| 202 | 4 | 0.28871477E-02 | 0.31257738E-04 | 4.8397578 | -0.45363150E-01 |
| 203 | 3 | -0.24853202E-01 | 0.24753724E-03 | -38.079085 | 0.39929121 |
| 204 | 2 | 0.87536903E-01 | 0.41023195E-03 | 116.59616 | -1.4194403 |
| 205 | 1 | -0.12588244 | 0.12433901E-03 | -143.97335 | 2.0501255 |
| 206 | 0 | 0.61258788E-01 | 0.30111189E-05 | 60.838472 | |
| 207 | 7 | -0.70485818E-08 | -0.82048821E-14 | -0.11525862E-14 | 0.12346975E-16 |
| 208 | 6 | 0.21636134E-05 | 0.11761400E-08 | 0.32006654E-02 | -0.26849864E-04 |
| 209 | 5 | -0.13228193E-03 | 0.68999669E-06 | -0.22433795 | 0.19615643E-02 |
| 210 | 4 | 0.28871477E-02 | 0.31257738E-04 | 4.8397578 | -0.45363150E-01 |
| 211 | 3 | -0.24853202E-01 | 0.24753724E-03 | -38.079085 | 0.39929121 |
| 212 | 2 | 0.87536903E-01 | 0.41023195E-03 | 116.59616 | -1.4194403 |
| 213 | 1 | -0.12588244 | 0.12433901E-03 | -143.97335 | 2.0501255 |
| 214 | 0 | 0.61258788E-01 | 0.30111189E-05 | 60.838472 | |
| 215 | 7 | -0.28726507E-08 | -0.17143581E-14 | 0.24267693E-14 | -0.55541839E-16 |
| 216 | 6 | 0.42346750E-05 | 0.28245518E-08 | 0.31939123E-02 | -0.26793213E-04 |
| 217 | 5 | -0.29857172E-03 | 0.16707368E-05 | -0.22395432 | 0.19581782E-02 |
| 218 | 4 | 0.68293023E-02 | 0.76000496E-04 | 4.8333721 | -0.45301763E-01 |
| 219 | 3 | -0.59851213E-01 | 0.60399479E-03 | -38.043031 | 0.39889267 |
| 220 | 2 | 0.21235346 | 0.10042645E-02 | 116.52602 | -1.4185020 |
| 221 | 1 | -0.30639453 | 0.30573542E-03 | -143.93207 | 2.0494469 |
| 222 | 0 | 0.14935640 | 0.74123768E-05 | 60.838472 | |
| 223 | 7 | -0.32902409E-08 | -0.25529066E-14 | 0.11988885E-14 | -0.45014903E-16 |
| 224 | 6 | 0.37562854E-05 | 0.24712502E-08 | 0.31953527E-02 | -0.26805296E-04 |
| 225 | 5 | -0.26216584E-03 | 0.14606656E-05 | -0.22403617 | 0.19589006E-02 |
| 226 | 4 | 0.59784819E-02 | 0.66426580E-04 | 4.8347351 | -0.45314865E-01 |
| 227 | 3 | -0.52336689E-01 | 0.52775921E-03 | -38.050729 | 0.39897776 |
| 228 | 2 | 0.18560952 | 0.87732663E-03 | 116.54100 | -1.4187024 |
| 229 | 1 | -0.26775360 | 0.26697134E-03 | -143.94089 | 2.0495919 |
| 230 | 0 | 0.13050713 | 0.64865099E-05 | 60.838472 |
| Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
| 1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
| 2 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | 36 | 1 | VerySmooth | 3.922 | 3.922 | 1.000 | 0.493 |
| Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
| 1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
| 2 | NONRES SKYLIGHT GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.36905 | 0.28585 | 0.28585 | 0.49000 | 0.13099 | 0.16159 | 0.00000 | 0.84000 | 0.84000 | 2.30798E-002 | 1.00000 | No |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Number of Refrigeration Compressor Racks | |
| 1 | 2 |
| Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
| 1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.320 |
| 2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 6.980 |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | SWH BOOSTER G WATER HEATER | 2.2712E-002 | 6000.0 | 1.092 | 0.9931 |
| 2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 14.749 | 0.4701 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 2 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 3 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 4 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 5 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 6 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 7 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 8 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 9 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 10 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 11 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 12 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 13 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 14 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 15 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 16 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 17 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 18 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 19 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 20 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 21 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 22 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 23 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 24 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 25 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 26 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 27 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 28 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 29 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 3 | No | No |
| 30 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 2 | No | No |
| 31 | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 32 | CORRIDOR_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 33 | CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 34 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 35 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 36 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 37 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 38 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 39 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 40 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 41 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 42 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 43 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 44 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 45 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 46 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 47 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 48 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 49 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 50 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 51 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 52 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 53 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 54 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 55 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 56 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 57 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 58 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 59 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 60 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 61 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 62 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 63 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 64 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 65 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 66 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 67 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 68 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 69 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 70 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 71 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 72 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 73 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 74 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 75 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 76 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 77 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 78 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 79 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 80 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 81 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 82 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 83 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 84 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 85 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 3 | No | No |
| 86 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 2 | No | No |
| 87 | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 88 | CORRIDOR_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 89 | CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 90 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 91 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 92 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 93 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 94 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 95 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 96 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 97 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 98 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 99 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 100 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 101 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 102 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 103 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 104 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 105 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 106 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 107 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 108 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 109 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 110 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 111 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 112 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 113 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 114 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 115 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 116 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 117 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 118 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 119 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 120 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 121 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 122 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 123 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 124 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 3 | No | No |
| 125 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 126 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 127 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 2 | No | No |
| 128 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 129 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 130 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 131 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 132 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 133 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 134 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 135 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 53.00 | 15.39 | 0.22 | 0 | No | No |
| 136 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 137 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 138 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 139 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 140 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 141 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 142 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 3 | No | No |
| 143 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 2 | No | No |
| 144 | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 145 | CORRIDOR_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 146 | CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 3.00 | 5.73 | 0.22 | 0 | No | No |
| 147 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 148 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 149 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 150 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 151 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 152 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 153 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 3 | No | No |
| 154 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 2 | No | No |
| 155 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 156 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 157 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 20.00 | 9.90 | 0.22 | 0 | No | No |
| 158 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 159 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 160 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 3 | No | No |
| 161 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 2 | No | No |
| 162 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 2 | No | No |
| 163 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 2 | No | No |
| 164 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 165 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 166 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 167 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 168 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 169 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 35.00 | 14.32 | 0.22 | 0 | No | No |
| 170 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 171 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 172 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 3 | No | No |
| 173 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 2 | No | No |
| 174 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 2 | No | No |
| 175 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 176 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 177 | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 178 | COMPUTER_CLASS_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 179 | COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 18.00 | 12.00 | 0.22 | 0 | No | No |
| 180 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 181 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 182 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 183 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 184 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 185 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 186 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 3 | No | No |
| 187 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 2 | No | No |
| 188 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 2 | No | No |
| 189 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 190 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 191 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 192 | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 193 | MAIN_CORRIDOR_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 194 | MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 9.00 | 19.85 | 0.22 | 0 | No | No |
| 195 | LOBBY_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 3 | No | No |
| 196 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 2 | No | No |
| 197 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 2 | No | No |
| 198 | LOBBY_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 199 | LOBBY_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 200 | LOBBY_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 201 | LOBBY_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 202 | LOBBY_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 203 | LOBBY_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 204 | LOBBY_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 205 | LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 19.00 | 12.21 | 0.22 | 0 | No | No |
| 206 | MECH_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 207 | MECH_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 208 | MECH_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 209 | MECH_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 210 | MECH_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 211 | MECH_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 212 | MECH_ZN_1_FLR_1_WALL_7 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 213 | MECH_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 214 | MECH_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 215 | MECH_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 0.00 | 10.50 | -999.00 | 0 | No | No |
| 216 | BATH_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 217 | BATH_ZN_1_FLR_1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 218 | BATH_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 219 | BATH_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 220 | BATH_ZN_1_FLR_1_WALL_5 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 3 | No | No |
| 221 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | 0 | 328.00 | 216.04 | 4.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 2 | No | No |
| 222 | BATH_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 223 | BATH_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 224 | BATH_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 10.00 | 13.10 | 0.22 | 0 | No | No |
| 225 | OFFICES_ZN_1_FLR_1_WALL_1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 3 | No | No |
| 226 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 2 | No | No |
| 227 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 2 | No | No |
| 228 | OFFICES_ZN_1_FLR_1_WALL_1_DOOR | 0 | 928.00 | 249.14 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 229 | OFFICES_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 3 | No | No |
| 230 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 2 | No | No |
| 231 | OFFICES_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 232 | OFFICES_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 233 | OFFICES_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 234 | OFFICES_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 235 | OFFICES_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 236 | OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 42.00 | 21.00 | 0.22 | 0 | No | No |
| 237 | GYM_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 238 | GYM_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 3 | No | No |
| 239 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 240 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 241 | GYM_ZN_1_FLR_1_WALL_2_DOOR | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 242 | GYM_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 243 | GYM_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 244 | GYM_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 245 | GYM_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 246 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 247 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 248 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 249 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 250 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 251 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 252 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 253 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 254 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 2 | No | No |
| 255 | GYM_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 17.00 | 18.79 | 0.42 | 0 | No | No |
| 256 | KITCHEN_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 257 | KITCHEN_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 3 | No | No |
| 258 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 2 | No | No |
| 259 | KITCHEN_ZN_1_FLR_1_WALL_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 260 | KITCHEN_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 261 | KITCHEN_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 262 | KITCHEN_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 263 | KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 8.00 | 11.59 | 0.22 | 0 | No | No |
| 264 | CAFETERIA_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 265 | CAFETERIA_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 3 | No | No |
| 266 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 2 | No | No |
| 267 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 2 | No | No |
| 268 | CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 269 | CAFETERIA_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 3 | No | No |
| 270 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 2 | No | No |
| 271 | CAFETERIA_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 272 | CAFETERIA_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 273 | CAFETERIA_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 274 | CAFETERIA_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 275 | CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 36.00 | 17.50 | 0.22 | 0 | No | No |
| 276 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 277 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 3 | No | No |
| 278 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 2 | No | No |
| 279 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 2 | No | No |
| 280 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | 0 | 328.00 | 190.47 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 281 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 3 | No | No |
| 282 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0 | 928.00 | 272.88 | 4.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 2 | No | No |
| 283 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 284 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 285 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 286 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 287 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING | 0 | 6871.00 | 354.65 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| 288 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 4.00 | 40.00 | 19.95 | 0.22 | 0 | No | No |
| Construction Name | Frame and Divider Name | NFRC Product Type | Assembly U-Factor {W/m2-K} | Assembly SHGC | Assembly Visible Transmittance | |
| 1 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | CurtainWall | 3.786 | 0.497 | 0.492 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 10.3 | 6.835E-003 | 3.560E-005 | 3.350E-005 | 3.204E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 10.3 | 6.835E-003 | 3.560E-005 | 3.350E-005 | 3.204E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 128.4 | 0.121 | 2.531E-004 | 1.743E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 10.3 | 6.835E-003 | 3.560E-005 | 3.350E-005 | 3.204E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 26.6 | 4.557E-002 | 4.603E-004 | 2.518E-004 | 0.414 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 84.8 | 7.974E-002 | 2.531E-004 | 1.738E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 43.6 | 4.101E-002 | 2.531E-004 | 1.738E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 29.4 | 2.050E-002 | 3.755E-005 | 3.511E-005 | 3.380E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | LOBBY_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 4.329E-002 | 2.531E-004 | 1.739E-004 | 0.228 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | LOBBY_ZN_1_FLR_1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LOBBY_ZN_1_FLR_1 | 171.00 | 18.4 | 3.031 | 1.773E-002 | 1.218E-002 | 15.954 | 1.000 | 0.000 | 0.000 | 0.000 |
| 20 | MECH_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | MECH_ZN_1_FLR_1 | 252.00 | 4.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | BATH_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | BATH_ZN_1_FLR_1 | 190.00 | 10.2 | 2.278E-002 | 1.199E-004 | 9.906E-005 | 0.108 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | OFFICES_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | OFFICES_ZN_1_FLR_1 | 441.00 | 23.7 | 9.569E-002 | 2.170E-004 | 1.566E-004 | 0.195 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | GYM_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | GYM_ZN_1_FLR_1 | 357.00 | 115.3 | 3.873E-002 | 1.085E-004 | 9.072E-005 | 9.764E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | KITCHEN_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | KITCHEN_ZN_1_FLR_1 | 168.00 | 27.0 | 1.823E-002 | 1.085E-004 | 9.113E-005 | 9.764E-002 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | CAFETERIA_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | CAFETERIA_ZN_1_FLR_1 | 315.00 | 339.1 | 8.202E-002 | 2.604E-004 | 1.779E-004 | 0.234 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INFILTRATION | INFIL_SCH_PNNL | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 43.0 | 9.113E-002 | 2.284E-004 | 1.625E-004 | 0.206 | 0.000 | 0.000 | 0.224 | 0.000 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 18 | LOBBY_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 19 | MECH_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 20 | BATH_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 21 | OFFICES_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 22 | GYM_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 23 | KITCHEN_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 24 | CAFETERIA_ZN_1_FLR_1 | Mixing/Well-Stirred |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2500 |
| 2 | Zone CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1.2500 |
| 3 | Zone MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.2500 |
| 4 | Zone CORRIDOR_POD_1_ZN_1_FLR_1 | 1.2500 |
| 5 | Zone CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1.2500 |
| 6 | Zone MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.2500 |
| 7 | Zone CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1.2500 |
| 8 | Zone MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.2500 |
| 9 | Zone CORRIDOR_POD_2_ZN_1_FLR_1 | 1.2500 |
| 10 | Zone CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1.2500 |
| 11 | Zone MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.2500 |
| 12 | Zone CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1.2500 |
| 13 | Zone MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.2500 |
| 14 | Zone CORRIDOR_POD_3_ZN_1_FLR_1 | 1.2500 |
| 15 | Zone CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1.2500 |
| 16 | Zone MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1.2500 |
| 17 | Zone COMPUTER_CLASS_ZN_1_FLR_1 | 1.2500 |
| 18 | Zone MAIN_CORRIDOR_ZN_1_FLR_1 | 1.2500 |
| 19 | Zone LOBBY_ZN_1_FLR_1 | 1.2500 |
| 20 | Zone MECH_ZN_1_FLR_1 | 1.2500 |
| 21 | Zone BATH_ZN_1_FLR_1 | 1.2500 |
| 22 | Zone OFFICES_ZN_1_FLR_1 | 1.2500 |
| 23 | Zone GYM_ZN_1_FLR_1 | 1.2500 |
| 24 | Zone KITCHEN_ZN_1_FLR_1 | 1.2500 |
| 25 | Zone CAFETERIA_ZN_1_FLR_1 | 1.2500 |
| 26 | Zone LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 1.2500 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.1500 |
| 2 | Zone CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1.1500 |
| 3 | Zone MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.1500 |
| 4 | Zone CORRIDOR_POD_1_ZN_1_FLR_1 | 1.1500 |
| 5 | Zone CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1.1500 |
| 6 | Zone MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.1500 |
| 7 | Zone CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1.1500 |
| 8 | Zone MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.1500 |
| 9 | Zone CORRIDOR_POD_2_ZN_1_FLR_1 | 1.1500 |
| 10 | Zone CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1.1500 |
| 11 | Zone MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.1500 |
| 12 | Zone CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1.1500 |
| 13 | Zone MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.1500 |
| 14 | Zone CORRIDOR_POD_3_ZN_1_FLR_1 | 1.1500 |
| 15 | Zone CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1.1500 |
| 16 | Zone MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1.1500 |
| 17 | Zone COMPUTER_CLASS_ZN_1_FLR_1 | 1.1500 |
| 18 | Zone MAIN_CORRIDOR_ZN_1_FLR_1 | 1.1500 |
| 19 | Zone LOBBY_ZN_1_FLR_1 | 1.1500 |
| 20 | Zone MECH_ZN_1_FLR_1 | 1.1500 |
| 21 | Zone BATH_ZN_1_FLR_1 | 1.1500 |
| 22 | Zone OFFICES_ZN_1_FLR_1 | 1.1500 |
| 23 | Zone GYM_ZN_1_FLR_1 | 1.1500 |
| 24 | Zone KITCHEN_ZN_1_FLR_1 | 1.1500 |
| 25 | Zone CAFETERIA_ZN_1_FLR_1 | 1.1500 |
| 26 | Zone LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 1.1500 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | Cooling | 7660.48459 | 8809.55728 | 0.64342 | 0.73993 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 32.60000 | 6.30558E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 2 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | Heating | 5507.39453 | 6884.24317 | 0.46154 | 0.57692 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 3 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | Cooling | 32069.80720 | 36880.27828 | 2.69368 | 3.09773 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.40000 | 6.30683E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 4 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | Heating | 17676.95986 | 22096.19983 | 1.48141 | 1.85176 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 5 | CORRIDOR_POD_1_ZN_1_FLR_1 | Cooling | 6434.96802 | 7400.21323 | 0.54032 | 0.62137 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 32.76000 | 6.30583E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 6 | CORRIDOR_POD_1_ZN_1_FLR_1 | Heating | 4989.03990 | 6236.29988 | 0.41811 | 0.52264 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 7 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | Cooling | 6887.14973 | 7920.22218 | 0.57847 | 0.66524 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.37333 | 6.30368E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 8 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | Heating | 5444.82374 | 6806.02967 | 0.45629 | 0.57037 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 9 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | Cooling | 27332.50277 | 31432.37818 | 2.29579 | 2.64016 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40000 | 6.30683E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 10 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | Heating | 17342.17628 | 21677.72035 | 1.45335 | 1.81669 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 11 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | Cooling | 7603.68033 | 8744.23238 | 0.63865 | 0.73444 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 32.60000 | 6.30558E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 12 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | Heating | 5489.47499 | 6861.84374 | 0.46003 | 0.57504 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 13 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | Cooling | 31700.42014 | 36455.48316 | 2.66265 | 3.06205 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.40000 | 6.30683E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 14 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | Heating | 17513.76182 | 21892.20228 | 1.46773 | 1.83467 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 15 | CORRIDOR_POD_2_ZN_1_FLR_1 | Cooling | 6413.45117 | 7375.46885 | 0.53851 | 0.61929 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 32.76000 | 6.30583E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 16 | CORRIDOR_POD_2_ZN_1_FLR_1 | Heating | 4982.80546 | 6228.50683 | 0.41759 | 0.52199 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 17 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | Cooling | 6891.14817 | 7924.82039 | 0.57880 | 0.66562 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.37333 | 6.30368E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 18 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | Heating | 5446.52213 | 6808.15266 | 0.45643 | 0.57054 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 19 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | Cooling | 27349.51589 | 31451.94328 | 2.29722 | 2.64180 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40000 | 6.30683E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 20 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | Heating | 17349.17343 | 21686.46679 | 1.45394 | 1.81743 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 21 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | Cooling | 7610.21652 | 8751.74899 | 0.63919 | 0.73507 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 32.60000 | 6.30558E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 22 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | Heating | 5491.55474 | 6864.44342 | 0.46021 | 0.57526 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 23 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | Cooling | 31835.00815 | 36610.25937 | 2.67396 | 3.07505 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.40000 | 6.30683E-003 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 24 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | Heating | 17567.84325 | 21959.80406 | 1.47227 | 1.84033 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 477.00000 | 128.36383 | 0.89657 | 0.00000 |
| 25 | CORRIDOR_POD_3_ZN_1_FLR_1 | Cooling | 6477.22998 | 7448.81448 | 0.54387 | 0.62545 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 32.76000 | 6.30583E-003 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 26 | CORRIDOR_POD_3_ZN_1_FLR_1 | Heating | 4989.92718 | 6237.40897 | 0.41819 | 0.52274 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 192.00000 | 10.33400 | 5.85216E-002 | 0.00000 |
| 27 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | Cooling | 6946.57862 | 7988.56541 | 0.58346 | 0.67098 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.37333 | 6.30368E-003 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 28 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | Heating | 5462.18320 | 6827.72900 | 0.45775 | 0.57218 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 99.00000 | 26.64155 | 0.18608 | 0.00000 |
| 29 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | Cooling | 18403.05932 | 21163.51822 | 1.54576 | 1.77762 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40000 | 6.30683E-003 | 315.00000 | 84.76857 | 0.59207 | 0.00000 |
| 30 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | Heating | 11714.17245 | 14642.71556 | 0.98170 | 1.22713 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 315.00000 | 84.76857 | 0.59207 | 0.00000 |
| 31 | COMPUTER_CLASS_ZN_1_FLR_1 | Cooling | 10159.86570 | 11683.84555 | 0.85337 | 0.98137 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 33.40000 | 6.30683E-003 | 162.00000 | 43.59526 | 0.30449 | 0.00000 |
| 32 | COMPUTER_CLASS_ZN_1_FLR_1 | Heating | 5761.08992 | 7201.36241 | 0.48281 | 0.60351 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 162.00000 | 43.59526 | 0.30449 | 0.00000 |
| 33 | MAIN_CORRIDOR_ZN_1_FLR_1 | Cooling | 13942.72791 | 16034.13710 | 1.17074 | 1.34635 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 32.60000 | 6.30558E-003 | 546.00000 | 29.38800 | 0.16642 | 0.00000 |
| 34 | MAIN_CORRIDOR_ZN_1_FLR_1 | Heating | 11881.72550 | 14852.15687 | 0.99577 | 1.24471 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 546.00000 | 29.38800 | 0.16642 | 0.00000 |
| 35 | LOBBY_ZN_1_FLR_1 | Cooling | 8150.28686 | 9372.82989 | 0.68441 | 0.78707 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.40000 | 6.30683E-003 | 171.00000 | 18.40800 | 9.55546E-002 | 0.00000 |
| 36 | LOBBY_ZN_1_FLR_1 | Heating | 6996.55514 | 8745.69393 | 0.58634 | 0.73293 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 171.00000 | 18.40800 | 9.55546E-002 | 0.00000 |
| 37 | MECH_ZN_1_FLR_1 | Cooling | 9688.60234 | 11141.89270 | 0.81347 | 0.93550 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.40000 | 6.30683E-003 | 252.00000 | 4.06900 | 0.00000 | 0.00000 |
| 38 | MECH_ZN_1_FLR_1 | Heating | 3965.29804 | 4956.62255 | 0.33232 | 0.41540 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -27.60000 | 3.41898E-004 | 252.00000 | 4.06900 | 0.00000 | 0.00000 |
| 39 | BATH_ZN_1_FLR_1 | Cooling | 6482.31174 | 7454.65850 | 0.54430 | 0.62595 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 31.37333 | 6.30368E-003 | 190.00000 | 10.22700 | 0.00000 | 0.00000 |
| 40 | BATH_ZN_1_FLR_1 | Heating | 5448.48555 | 6810.60694 | 0.45661 | 0.57077 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 190.00000 | 10.22700 | 0.00000 | 0.00000 |
| 41 | OFFICES_ZN_1_FLR_1 | Cooling | 19750.09294 | 22712.60688 | 1.65835 | 1.90711 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 33.40000 | 6.30683E-003 | 441.00000 | 23.73648 | 0.19042 | 0.00000 |
| 42 | OFFICES_ZN_1_FLR_1 | Heating | 15479.14484 | 19348.93105 | 1.29723 | 1.62153 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 441.00000 | 23.73648 | 0.19042 | 0.00000 |
| 43 | GYM_ZN_1_FLR_1 | Cooling | 22006.26927 | 25307.20966 | 1.84858 | 2.12586 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 33.40000 | 6.30683E-003 | 357.00000 | 115.31008 | 0.54407 | 0.00000 |
| 44 | GYM_ZN_1_FLR_1 | Heating | 11458.50315 | 14323.12894 | 0.96029 | 1.20036 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -27.60000 | 3.41898E-004 | 357.00000 | 115.31008 | 0.54407 | 0.00000 |
| 45 | KITCHEN_ZN_1_FLR_1 | Cooling | 18273.34265 | 21014.34404 | 1.53646 | 1.76692 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.96000 | 6.30459E-003 | 168.00000 | 26.99300 | 0.25481 | 0.00000 |
| 46 | KITCHEN_ZN_1_FLR_1 | Heating | 1542.07361 | 1927.59201 | 0.12927 | 0.25481 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -27.60000 | 3.41898E-004 | 168.00000 | 26.99300 | 0.25481 | 0.00000 |
| 47 | CAFETERIA_ZN_1_FLR_1 | Cooling | 31571.83183 | 36307.60660 | 2.65512 | 3.05339 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 32.60000 | 6.30558E-003 | 315.00000 | 339.07427 | 1.48818 | 0.00000 |
| 48 | CAFETERIA_ZN_1_FLR_1 | Heating | 12361.32514 | 15451.65642 | 1.03593 | 1.48818 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | -27.60000 | 3.41898E-004 | 315.00000 | 339.07427 | 1.48818 | 0.00000 |
| 49 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | Cooling | 20937.24517 | 24077.83195 | 1.75818 | 2.02191 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 33.40000 | 6.30683E-003 | 399.00000 | 42.95403 | 0.34458 | 0.00000 |
| 50 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | Heating | 13802.59353 | 17253.24191 | 1.15672 | 1.44590 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -27.60000 | 3.41898E-004 | 399.00000 | 42.95403 | 0.34458 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | VAV_POD_1 | Cooling | Sensible | 492887.31 | 32.88704 | 32.88704 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
| 2 | VAV_POD_1 | Heating | Sensible | 350135.06 | 23.23064 | 23.23064 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 |
| 3 | PSZ-AC_1:6 | Cooling | Sensible | 22838.29 | 1.76692 | 1.76692 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 4 | PSZ-AC_1:6 | Heating | Sensible | 16101.31 | 0.25481 | 0.25481 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 5 | PSZ-AC_2:7 | Cooling | Sensible | 50281.99 | 3.05339 | 3.05339 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 6 | PSZ-AC_2:7 | Heating | Sensible | 94036.15 | 1.48818 | 1.48818 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73993 |
| 2 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10195 |
| 3 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.39100 |
| 4 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28931 |
| 5 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39100 |
| 6 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 7 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.73701E-003 |
| 8 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.04176E-004 |
| 9 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57692 |
| 10 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 11 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 12 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11907.97651 |
| 13 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.04176E-004 |
| 14 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 277.74794 |
| 15 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.09773 |
| 16 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11734 |
| 17 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45000 |
| 18 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.39398 |
| 19 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45000 |
| 20 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 21 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.24709E-003 |
| 22 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.34384E-004 |
| 23 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.85176 |
| 24 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 25 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 26 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 38222.09651 |
| 27 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.34384E-004 |
| 28 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 891.51635 |
| 29 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62137 |
| 30 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23545 |
| 31 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 32 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18641 |
| 33 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62788 |
| 34 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 35 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61815E-003 |
| 36 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.43831E-005 |
| 37 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.52264 |
| 38 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 39 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 40 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10788.56647 |
| 41 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.43831E-005 |
| 42 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 251.64408 |
| 43 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66524 |
| 44 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11340 |
| 45 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43500 |
| 46 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28938 |
| 47 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43500 |
| 48 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 49 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.35978E-003 |
| 50 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.02992E-004 |
| 51 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57037 |
| 52 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 53 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 54 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11772.67249 |
| 55 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.02992E-004 |
| 56 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 274.59194 |
| 57 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.64016 |
| 58 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13767 |
| 59 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52800 |
| 60 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.39400 |
| 61 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52800 |
| 62 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 63 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.76746E-003 |
| 64 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.28050E-004 |
| 65 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.81669 |
| 66 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 67 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 68 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37498.14394 |
| 69 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.28050E-004 |
| 70 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 874.63002 |
| 71 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73444 |
| 72 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10271 |
| 73 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.39400 |
| 74 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28937 |
| 75 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39400 |
| 76 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 77 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.70931E-003 |
| 78 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03837E-004 |
| 79 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57504 |
| 80 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 81 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 82 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11869.22701 |
| 83 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03837E-004 |
| 84 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 276.84410 |
| 85 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.06205 |
| 86 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11870 |
| 87 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45500 |
| 88 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.39323 |
| 89 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45500 |
| 90 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 91 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.20970E-003 |
| 92 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.31296E-004 |
| 93 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.83467 |
| 94 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 95 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 96 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37869.18888 |
| 97 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.31296E-004 |
| 98 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 883.28471 |
| 99 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.61929 |
| 100 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23624 |
| 101 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 102 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18579 |
| 103 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62998 |
| 104 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 105 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.61274E-003 |
| 106 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.42651E-005 |
| 107 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.52199 |
| 108 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 109 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 110 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10775.08453 |
| 111 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.42651E-005 |
| 112 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 251.32961 |
| 113 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.66562 |
| 114 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11333 |
| 115 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43400 |
| 116 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28888 |
| 117 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43400 |
| 118 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 119 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.36173E-003 |
| 120 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03025E-004 |
| 121 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57054 |
| 122 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 123 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 124 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11776.34512 |
| 125 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03025E-004 |
| 126 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 274.67761 |
| 127 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.64180 |
| 128 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13759 |
| 129 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.52700 |
| 130 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.39223 |
| 131 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52700 |
| 132 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 133 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.76919E-003 |
| 134 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.28182E-004 |
| 135 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.81743 |
| 136 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 137 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 138 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37513.27492 |
| 139 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.28182E-004 |
| 140 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 874.98295 |
| 141 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.73507 |
| 142 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10263 |
| 143 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.39300 |
| 144 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28888 |
| 145 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39300 |
| 146 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 147 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.71249E-003 |
| 148 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03877E-004 |
| 149 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57526 |
| 150 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 151 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 152 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11873.72428 |
| 153 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03877E-004 |
| 154 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 276.94900 |
| 155 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 3.07505 |
| 156 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11820 |
| 157 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.45300 |
| 158 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.39300 |
| 159 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45300 |
| 160 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 161 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.22332E-003 |
| 162 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.32319E-004 |
| 163 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.84033 |
| 164 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 165 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 166 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 37986.13734 |
| 167 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.32319E-004 |
| 168 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 886.01256 |
| 169 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62545 |
| 170 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23392 |
| 171 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 172 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18764 |
| 173 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.62378 |
| 174 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 175 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.62878E-003 |
| 176 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.43999E-005 |
| 177 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.52274 |
| 178 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 179 | AirTerminal:SingleDuct:VAV:Reheat | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 180 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10790.48519 |
| 181 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.43999E-005 |
| 182 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 251.68884 |
| 183 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.67098 |
| 184 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11243 |
| 185 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.43100 |
| 186 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28919 |
| 187 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.43100 |
| 188 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 189 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.38877E-003 |
| 190 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03321E-004 |
| 191 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57218 |
| 192 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 193 | AirTerminal:SingleDuct:VAV:Reheat | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 194 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11810.21086 |
| 195 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03321E-004 |
| 196 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 275.46753 |
| 197 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.77762 |
| 198 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13503 |
| 199 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.51700 |
| 200 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.91903 |
| 201 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.51700 |
| 202 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 203 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.82162E-003 |
| 204 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.21589E-004 |
| 205 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.22713 |
| 206 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 207 | AirTerminal:SingleDuct:VAV:Reheat | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 208 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25329.03934 |
| 209 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.21589E-004 |
| 210 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 590.79058 |
| 211 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.98137 |
| 212 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12579 |
| 213 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.48200 |
| 214 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.47302 |
| 215 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48200 |
| 216 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 217 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.02893E-003 |
| 218 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.08978E-004 |
| 219 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.60351 |
| 220 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 221 | AirTerminal:SingleDuct:VAV:Reheat | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 222 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12456.90354 |
| 223 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.08978E-004 |
| 224 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 290.55239 |
| 225 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.34635 |
| 226 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.30902 |
| 227 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 228 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.40390 |
| 229 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.82406 |
| 230 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 231 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.23292E-003 |
| 232 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.24778E-004 |
| 233 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.24471 |
| 234 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 235 | AirTerminal:SingleDuct:VAV:Reheat | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 236 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 25693.54259 |
| 237 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.24778E-004 |
| 238 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 599.30296 |
| 239 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.78707 |
| 240 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16555 |
| 241 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 242 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23612 |
| 243 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.44148 |
| 244 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 245 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.30137E-003 |
| 246 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.32350E-004 |
| 247 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.73293 |
| 248 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 249 | AirTerminal:SingleDuct:VAV:Reheat | LOBBY_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 250 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15128.46953 |
| 251 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.32350E-004 |
| 252 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 352.86679 |
| 253 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.93550 |
| 254 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.20526 |
| 255 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 256 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28065 |
| 257 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.54737 |
| 258 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 259 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.85614E-003 |
| 260 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.50175E-005 |
| 261 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.41540 |
| 262 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 263 | AirTerminal:SingleDuct:VAV:Reheat | MECH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 264 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8574.95568 |
| 265 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.50175E-005 |
| 266 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 200.01243 |
| 267 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.62595 |
| 268 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.23130 |
| 269 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 270 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.18778 |
| 271 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.61680 |
| 272 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 273 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.64722E-003 |
| 274 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.03070E-004 |
| 275 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.57077 |
| 276 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 277 | AirTerminal:SingleDuct:VAV:Reheat | BATH_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 278 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 11781.56388 |
| 279 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.03070E-004 |
| 280 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 274.80311 |
| 281 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.90711 |
| 282 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.46988 |
| 283 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 284 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.16225E-003 |
| 285 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.92812E-004 |
| 286 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.62153 |
| 287 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 288 | AirTerminal:SingleDuct:VAV:Reheat | OFFICES_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 289 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 33470.23863 |
| 290 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.92812E-004 |
| 291 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 780.68273 |
| 292 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.12586 |
| 293 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12796 |
| 294 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.39800 |
| 295 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.84609 |
| 296 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39800 |
| 297 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 298 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.97740E-003 |
| 299 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.16765E-004 |
| 300 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.20036 |
| 301 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 302 | AirTerminal:SingleDuct:VAV:Reheat | GYM_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 303 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24777.58574 |
| 304 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.16765E-004 |
| 305 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 577.93483 |
| 306 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN_ZN_1_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.76692 |
| 307 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | CAFETERIA_ZN_1_FLR_1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.05339 |
| 308 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 2.02191 |
| 309 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15037 |
| 310 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30000 |
| 311 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.60657 |
| 312 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.40099 |
| 313 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
| 314 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.53372E-003 |
| 315 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.61096E-004 |
| 316 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.44590 |
| 317 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.88890 |
| 318 | AirTerminal:SingleDuct:VAV:Reheat | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
| 319 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 29844.87304 |
| 320 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.61096E-004 |
| 321 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 696.12121 |
| 322 | AirLoopHVAC | VAV_POD_1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 16.72693 |
| 323 | AirLoopHVAC | VAV_POD_1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 13.78660 |
| 324 | AirLoopHVAC | VAV_POD_1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 33.10291 |
| 325 | AirLoopHVAC | VAV_POD_1 | Adjusted Heating Design Air Flow Rate [m3/s] | 23.23064 |
| 326 | AirLoopHVAC | VAV_POD_1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 32.88704 |
| 327 | AirLoopHVAC | VAV_POD_1 | Adjusted Main Design Air Flow Rate [m3/s] | 32.88704 |
| 328 | AirLoopHVAC | VAV_POD_1 | User Heating Air Flow Ratio [] | 0.30000 |
| 329 | AirLoopHVAC | VAV_POD_1 | Calculated Heating Air Flow Ratio [] | 0.70638 |
| 330 | AirLoopHVAC | PSZ-AC_1:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.76692 |
| 331 | AirLoopHVAC | PSZ-AC_1:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.76692 |
| 332 | AirLoopHVAC | PSZ-AC_1:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.76692 |
| 333 | AirLoopHVAC | PSZ-AC_1:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.76692 |
| 334 | AirLoopHVAC | PSZ-AC_1:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.76692 |
| 335 | AirLoopHVAC | PSZ-AC_1:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.76692 |
| 336 | AirLoopHVAC | PSZ-AC_1:6 | User Heating Air Flow Ratio [] | 1.00000 |
| 337 | AirLoopHVAC | PSZ-AC_1:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 338 | AirLoopHVAC | PSZ-AC_2:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.05339 |
| 339 | AirLoopHVAC | PSZ-AC_2:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.05339 |
| 340 | AirLoopHVAC | PSZ-AC_2:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.05339 |
| 341 | AirLoopHVAC | PSZ-AC_2:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.05339 |
| 342 | AirLoopHVAC | PSZ-AC_2:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.05339 |
| 343 | AirLoopHVAC | PSZ-AC_2:7 | Adjusted Main Design Air Flow Rate [m3/s] | 3.05339 |
| 344 | AirLoopHVAC | PSZ-AC_2:7 | User Heating Air Flow Ratio [] | 1.00000 |
| 345 | AirLoopHVAC | PSZ-AC_2:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 346 | AirLoopHVAC | VAV_POD_1 | Design Supply Air Flow Rate [m3/s] | 32.88704 |
| 347 | AirLoopHVAC | PSZ-AC_1:6 | Design Supply Air Flow Rate [m3/s] | 1.76692 |
| 348 | AirLoopHVAC | PSZ-AC_2:7 | Design Supply Air Flow Rate [m3/s] | 3.05339 |
| 349 | Controller:OutdoorAir | VAV_POD_1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 32.88704 |
| 350 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size High Speed Rated Air Flow Rate [m3/s] | 32.88704 |
| 351 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size High Speed Gross Rated Total Cooling Capacity [W] | 601222.90753 |
| 352 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size High Speed Rated Sensible Heat Ratio | 0.80091 |
| 353 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size Low Speed Rated Air Flow Rate [m3/s] | 10.96125 |
| 354 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size Low Speed Gross Rated Total Cooling Capacity [W] | 200387.59508 |
| 355 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | Design Size Low Speed Gross Rated Sensible Heat Ratio | 0.80091 |
| 356 | Coil:Heating:Fuel | VAV_POD_1 HEATING COIL | Design Size Nominal Capacity [W] | 422739.69464 |
| 357 | Fan:VariableVolume | VAV_POD_1 FAN | Design Size Maximum Flow Rate [m3/s] | 32.88704 |
| 358 | Controller:OutdoorAir | PSZ-AC_1:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.76692 |
| 359 | Controller:OutdoorAir | PSZ-AC_1:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.25481 |
| 360 | Fan:SystemModel | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.76692 |
| 361 | Fan:SystemModel | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2936.62211 |
| 362 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.76692 |
| 363 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.76692 |
| 364 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.76692 |
| 365 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.76692 |
| 366 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.76692 |
| 367 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.88346 |
| 368 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.17795 |
| 369 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 35017.39000 |
| 370 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17508.69500 |
| 371 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.78009 |
| 372 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.78009 |
| 373 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35017.39000 |
| 374 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34404.54200 |
| 375 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
| 376 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 377 | Coil:Heating:Fuel | PSZ-AC_1:6 HEATING COIL | Design Size Nominal Capacity [W] | 34404.54200 |
| 378 | Controller:OutdoorAir | PSZ-AC_2:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.05339 |
| 379 | Controller:OutdoorAir | PSZ-AC_2:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.48818 |
| 380 | Fan:SystemModel | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.05339 |
| 381 | Fan:SystemModel | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 4952.98045 |
| 382 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.05339 |
| 383 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.05339 |
| 384 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.05339 |
| 385 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.05339 |
| 386 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.05339 |
| 387 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.52670 |
| 388 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.03559 |
| 389 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 64918.53000 |
| 390 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32459.26500 |
| 391 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.75325 |
| 392 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.75325 |
| 393 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 64918.53000 |
| 394 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 112439.17167 |
| 395 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
| 396 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 397 | Coil:Heating:Fuel | PSZ-AC_2:7 HEATING COIL | Design Size Nominal Capacity [W] | 112439.17167 |
| 398 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 4.19497E-003 |
| 399 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.50340 |
| 400 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 4.19497E-003 |
| 401 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 1263.33934 |
| 402 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
| 403 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 479510.30602 |
| 404 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 479510.31000 |
| 405 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 4.19497E-003 |
| 406 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.05414E-004 |
| 407 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.26497E-002 |
| 408 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.05414E-004 |
| 409 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 13.46550 |
| 410 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.05414E-004 |
| Component Type | Name | Nominal Total Capacity {W} | |
| 1 | Coil:Heating:Water | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11299.63 |
| 2 | Coil:Heating:Water | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 36269.44 |
| 3 | Coil:Heating:Water | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 10237.41 |
| 4 | Coil:Heating:Water | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11171.24 |
| 5 | Coil:Heating:Water | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | 35582.47 |
| 6 | Coil:Heating:Water | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11262.86 |
| 7 | Coil:Heating:Water | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 35934.56 |
| 8 | Coil:Heating:Water | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 10224.62 |
| 9 | Coil:Heating:Water | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11174.73 |
| 10 | Coil:Heating:Water | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | 35596.83 |
| 11 | Coil:Heating:Water | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11267.13 |
| 12 | Coil:Heating:Water | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 36045.54 |
| 13 | Coil:Heating:Water | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 10239.23 |
| 14 | Coil:Heating:Water | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11206.86 |
| 15 | Coil:Heating:Water | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | 24035.05 |
| 16 | Coil:Heating:Water | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11820.52 |
| 17 | Coil:Heating:Water | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | 24380.93 |
| 18 | Coil:Heating:Water | LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | 14355.60 |
| 19 | Coil:Heating:Water | MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 8136.89 |
| 20 | Coil:Heating:Water | BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | 11179.68 |
| 21 | Coil:Heating:Water | OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | 31760.34 |
| 22 | Coil:Heating:Water | GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | 23511.77 |
| 23 | Coil:Heating:Water | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | 28320.19 |
| DX Coil Type | DX Coil Name | Fan Type | Fan Name | Standard Net Cooling Capacity {W} | Standard Net Cooling Capacity {Btu/h} | IEER {Btu/W-h} | COP 100% Capacity {W/W} | COP 75% Capacity {W/W} | COP 50% Capacity {W/W} | COP 25% Capacity {W/W} | EER 100% Capacity {Btu/W-h} | EER 75% Capacity {Btu/W-h} | EER 50% Capacity {Btu/W-h} | EER 25% Capacity {Btu/W-h} | Supply Air Flow 100% {kg/s} | Supply Air Flow 75% {kg/s} | Supply Air Flow 50% {kg/s} | Supply Air Flow 25% {kg/s} | |
| 1 | Coil:Cooling:DX:TwoSpeed | VAV_POD_1 COOLING COIL | N/A | N/A | 576809.52 | 1968155.79 | 11.09 | 3.02 | 3.24 | 3.22 | 3.38 | 10.30 | 11.06 | 11.00 | 11.54 | 33.2668 | 26.4192 | 17.7220 | 7.1494 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:6 COOLING COIL | 33629.0 | 10.75 | 10.75 | |||
| 2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:7 COOLING COIL | 62516.5 | 10.62 | 10.62 |
| Zone Name | # Surfaces | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 11 |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 12 |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | 10 |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 11 |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 12 |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 11 |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 12 |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | 10 |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 11 |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 12 |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 11 |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 12 |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | 11 |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 11 |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 12 |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | 10 |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | 15 |
| 18 | LOBBY_ZN_1_FLR_1 | 11 |
| 19 | MECH_ZN_1_FLR_1 | 10 |
| 20 | BATH_ZN_1_FLR_1 | 9 |
| 21 | OFFICES_ZN_1_FLR_1 | 12 |
| 22 | GYM_ZN_1_FLR_1 | 19 |
| 23 | KITCHEN_ZN_1_FLR_1 | 8 |
| 24 | CAFETERIA_ZN_1_FLR_1 | 12 |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 13 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 32.37 | 44.00 | 32.37 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 180.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 180.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 4 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | Door | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 5 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 7 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 8 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 9 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 10 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 11 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 12 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 161.46 | 212.00 | 161.46 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 14 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 15 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | Window | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 16 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | Door | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 17 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | Door | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 18 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 19 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 21 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 22 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 23 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 24 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 25 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 26 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 90.00 | 90.00 | 3.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 27 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 28 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 9.36 | 12.00 | 9.36 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 30 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | Window | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.64 | 2.64 | 2.64 | 270.00 | 90.00 | 2.90 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 31 | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.980E-002 | 1.971E-002 | 192.00 | 192.00 | 192.00 | 270.00 | 180.00 | 3.00 | 64.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 32 | CORRIDOR_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 192.00 | 192.00 | 192.00 | 90.00 | 0.00 | 3.00 | 64.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 33 | CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 384.00 | 384.00 | 384.00 | 0.00 | 90.00 | 384.00 | 1.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 34 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 35 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 36 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 32.37 | 44.00 | 32.37 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 | ||
| 37 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 0.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 38 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 0.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 |
| 39 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | Door | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | |
| 40 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 41 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 42 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 43 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 44 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 45 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 46 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 47 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 161.46 | 212.00 | 161.46 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 | ||
| 48 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 49 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 50 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | Window | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 51 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | Door | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 | |
| 52 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | Door | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 53 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 54 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 55 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 56 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 57 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 32.37 | 44.00 | 32.37 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 | ||
| 58 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 180.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 |
| 59 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 180.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.61 | 0.39 | 4 |
| 60 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | Door | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 | |
| 61 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 63 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 64 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 65 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 66 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 67 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 68 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 161.46 | 212.00 | 161.46 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 | ||
| 69 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 70 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.63 | 0.37 | 4 |
| 71 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | Window | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 72 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | Door | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 73 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | Door | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 | |
| 74 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 75 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 76 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 77 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 78 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 79 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 80 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 81 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 82 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 90.00 | 90.00 | 3.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 85 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 9.36 | 12.00 | 9.36 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 86 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | Window | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.64 | 2.64 | 2.64 | 270.00 | 90.00 | 2.90 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 87 | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.980E-002 | 1.971E-002 | 192.00 | 192.00 | 192.00 | 270.00 | 180.00 | 3.00 | 64.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 88 | CORRIDOR_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 192.00 | 192.00 | 192.00 | 90.00 | 0.00 | 3.00 | 64.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 89 | CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 384.00 | 384.00 | 384.00 | 0.00 | 90.00 | 384.00 | 1.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 90 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 91 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 32.37 | 44.00 | 32.37 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.56 | 0.44 | 4 | ||
| 93 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 0.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 94 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 0.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 |
| 95 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | Door | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 | |
| 96 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 98 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 99 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 100 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 101 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 102 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 103 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 161.46 | 212.00 | 161.46 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 | ||
| 104 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 |
| 105 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 106 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | Window | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 0.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 107 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | Door | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 108 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | Door | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | |
| 109 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 111 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 112 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 113 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 32.37 | 44.00 | 32.37 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.56 | 0.44 | 4 | ||
| 114 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 180.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.57 | 0.43 | 4 |
| 115 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.46 | 8.46 | 8.46 | 180.00 | 90.00 | 8.46 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.60 | 0.40 | 4 |
| 116 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | Door | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.58 | 0.42 | 4 | |
| 117 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 119 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 120 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 121 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 122 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 123 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 124 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 161.46 | 212.00 | 161.46 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.59 | 0.41 | 4 | ||
| 125 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 126 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.62 | 0.38 | 4 |
| 127 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | Window | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.55 | 15.55 | 15.55 | 180.00 | 90.00 | 16.82 | 0.92 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 |
| 128 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | Door | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | |
| 129 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | Door | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 130 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 131 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 0.00 | 90.00 | 53.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 132 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 133 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 477.00 | 477.00 | 477.00 | 270.00 | 180.00 | 9.00 | 53.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 134 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 477.00 | 477.00 | 477.00 | 90.00 | 0.00 | 9.00 | 53.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 135 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 954.00 | 954.00 | 954.00 | 0.00 | 90.00 | 954.00 | 1.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 136 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 137 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 212.00 | 212.00 | 212.00 | 180.00 | 90.00 | 53.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 138 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 90.00 | 90.00 | 3.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 139 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 72.00 | 72.00 | 72.00 | 0.00 | 90.00 | 18.00 | 4.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 140.00 | 140.00 | 140.00 | 0.00 | 90.00 | 35.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 141 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 9.36 | 12.00 | 9.36 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 143 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | Window | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.64 | 2.64 | 2.64 | 270.00 | 90.00 | 2.90 | 0.91 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 144 | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.980E-002 | 1.971E-002 | 192.00 | 192.00 | 192.00 | 270.00 | 180.00 | 3.00 | 64.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 145 | CORRIDOR_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 192.00 | 192.00 | 192.00 | 90.00 | 0.00 | 3.00 | 64.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 146 | CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 384.00 | 384.00 | 384.00 | 0.00 | 90.00 | 384.00 | 1.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 147 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 44.00 | 44.00 | 44.00 | 180.00 | 90.00 | 11.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 148 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 32.40 | 44.00 | 32.40 | 0.00 | 90.00 | 11.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 150 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.22 | 1.22 | 1.22 | 0.00 | 90.00 | 1.22 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 151 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.43 | 8.43 | 8.43 | 0.00 | 90.00 | 8.43 | 1.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 152 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | Door | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 153 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 28.08 | 36.00 | 28.08 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 154 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | Window | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.92 | 7.92 | 7.92 | 270.00 | 90.00 | 8.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 155 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.266 | 0.250 | 99.00 | 99.00 | 99.00 | 270.00 | 180.00 | 9.00 | 11.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 156 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 99.00 | 99.00 | 99.00 | 90.00 | 0.00 | 9.00 | 11.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 157 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 198.00 | 198.00 | 198.00 | 0.00 | 90.00 | 198.00 | 1.00 | 0.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 158 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 140.00 | 140.00 | 140.00 | 180.00 | 90.00 | 35.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 159 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 105.30 | 140.00 | 105.30 | 0.00 | 90.00 | 35.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 161 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 10.27 | 10.27 | 10.27 | 0.00 | 90.00 | 10.82 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 162 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 10.27 | 10.27 | 10.27 | 0.00 | 90.00 | 10.82 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 163 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | Window | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 10.27 | 10.27 | 10.27 | 0.00 | 90.00 | 10.82 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 164 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | Door | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 165 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | Door | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 166 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 315.00 | 315.00 | 315.00 | 270.00 | 180.00 | 9.00 | 35.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 168 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 315.00 | 315.00 | 315.00 | 90.00 | 0.00 | 9.00 | 35.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 169 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 630.00 | 630.00 | 630.00 | 0.00 | 90.00 | 630.00 | 1.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 170 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 72.00 | 72.00 | 72.00 | 180.00 | 90.00 | 18.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 171 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 172 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 54.21 | 72.00 | 54.21 | 0.00 | 90.00 | 18.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 173 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | Window | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.16 | 1.16 | 1.16 | 0.00 | 90.00 | 1.22 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 174 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | Window | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 14.68 | 14.68 | 14.68 | 0.00 | 90.00 | 15.46 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 175 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | Door | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 176 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 162.00 | 162.00 | 162.00 | 270.00 | 180.00 | 9.00 | 18.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 178 | COMPUTER_CLASS_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 162.00 | 162.00 | 162.00 | 90.00 | 0.00 | 9.00 | 18.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 179 | COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 324.00 | 324.00 | 324.00 | 0.00 | 90.00 | 324.00 | 1.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 180 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 180.00 | 90.00 | 13.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 181 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 168.00 | 168.00 | 168.00 | 90.00 | 90.00 | 42.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_7 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 0.00 | 90.00 | 13.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 183 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 26.13 | 36.00 | 26.13 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | ||
| 187 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | Window | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.26 | 1.26 | 1.26 | 270.00 | 90.00 | 1.22 | 1.03 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.73 | 0.27 | 4 |
| 188 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | Window | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 6.66 | 6.66 | 6.66 | 270.00 | 90.00 | 6.46 | 1.03 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 189 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | Door | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.71 | 0.29 | 4 | |
| 190 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 191 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 192 | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR | 2.090E-002 | 2.079E-002 | 546.00 | 546.00 | 546.00 | 270.00 | 180.00 | 42.00 | 13.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 193 | MAIN_CORRIDOR_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 546.00 | 546.00 | 546.00 | 90.00 | 0.00 | 42.00 | 13.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 194 | MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 1092.00 | 1092.00 | 1092.00 | 0.00 | 90.00 | 1092.00 | 1.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 195 | LOBBY_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 57.33 | 76.00 | 57.33 | 180.00 | 90.00 | 19.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 196 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | LOBBY_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.15 | 1.15 | 1.15 | 180.00 | 90.00 | 1.22 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 197 | LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | LOBBY_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 15.57 | 15.57 | 15.57 | 180.00 | 90.00 | 16.46 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 198 | LOBBY_ZN_1_FLR_1_WALL_1_DOOR | Door | LOBBY_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 199 | LOBBY_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 90.00 | 90.00 | 9.00 | 4.00 | 0.00 | OFFICES_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 200 | LOBBY_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 6.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | LOBBY_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 0.00 | 90.00 | 13.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | LOBBY_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 203 | LOBBY_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR | 0.144 | 0.139 | 171.00 | 171.00 | 171.00 | 270.00 | 180.00 | 9.00 | 19.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 204 | LOBBY_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 171.00 | 171.00 | 171.00 | 90.00 | 0.00 | 9.00 | 19.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 205 | LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 342.00 | 342.00 | 342.00 | 0.00 | 90.00 | 342.00 | 1.00 | 0.00 | LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 206 | MECH_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 180.00 | 90.00 | 6.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | MECH_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 48.00 | 48.00 | 48.00 | 90.00 | 90.00 | 12.00 | 4.00 | 0.00 | OFFICES_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 208 | MECH_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.00 | 68.00 | 68.00 | 90.00 | 90.00 | 17.00 | 4.00 | 0.00 | GYM_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | MECH_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 32.00 | 32.00 | 32.00 | 90.00 | 90.00 | 8.00 | 4.00 | 0.00 | KITCHEN_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | MECH_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.00 | 20.00 | 20.00 | 90.00 | 90.00 | 5.00 | 4.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 211 | MECH_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 0.00 | 90.00 | 6.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 212 | MECH_ZN_1_FLR_1_WALL_7 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 168.00 | 168.00 | 168.00 | 270.00 | 90.00 | 42.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 213 | MECH_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | MECH_ZN_1_FLR_1_FLOOR_FFACTOR | 5.650E-003 | 5.642E-003 | 252.00 | 252.00 | 252.00 | 270.00 | 180.00 | 42.00 | 6.00 | 0.00 | MECH_ZN_1_FLR_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 214 | MECH_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 252.00 | 252.00 | 252.00 | 90.00 | 0.00 | 42.00 | 6.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 215 | MECH_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 504.00 | 504.00 | 504.00 | 0.00 | 90.00 | 504.00 | 1.00 | 0.00 | MECH_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 216 | BATH_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 52.00 | 52.00 | 52.00 | 180.00 | 90.00 | 13.00 | 4.00 | 0.00 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 217 | BATH_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 24.00 | 24.00 | 24.00 | 180.00 | 90.00 | 6.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_6 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 218 | BATH_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.00 | 40.00 | 40.00 | 90.00 | 90.00 | 10.00 | 4.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 219 | BATH_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 76.00 | 76.00 | 76.00 | 0.00 | 90.00 | 19.00 | 4.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 220 | BATH_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 31.20 | 40.00 | 31.20 | 270.00 | 90.00 | 10.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.64 | 0.36 | 4 | ||
| 221 | BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | Window | BATH_ZN_1_FLR_1_WALL_5 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 8.80 | 8.80 | 8.80 | 270.00 | 90.00 | 9.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.66 | 0.34 | 4 |
| 222 | BATH_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | BATH_ZN_1_FLR_1_FLOOR_FFACTOR | 6.720E-002 | 6.612E-002 | 190.00 | 190.00 | 190.00 | 270.00 | 180.00 | 10.00 | 19.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 223 | BATH_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 190.00 | 190.00 | 190.00 | 90.00 | 0.00 | 10.00 | 19.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 224 | BATH_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 380.00 | 380.00 | 380.00 | 0.00 | 90.00 | 380.00 | 1.00 | 0.00 | BATH_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 225 | OFFICES_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 63.57 | 84.00 | 63.57 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | Window | OFFICES_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.14 | 1.14 | 1.14 | 180.00 | 90.00 | 1.22 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 227 | OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | Window | OFFICES_ZN_1_FLR_1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 17.34 | 17.34 | 17.34 | 180.00 | 90.00 | 18.46 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 228 | OFFICES_ZN_1_FLR_1_WALL_1_DOOR | Door | OFFICES_ZN_1_FLR_1_WALL_1 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 229 | OFFICES_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 65.52 | 84.00 | 65.52 | 90.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 230 | OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | Window | OFFICES_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 18.48 | 18.48 | 18.48 | 90.00 | 90.00 | 20.90 | 0.88 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 231 | OFFICES_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | GYM_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 232 | OFFICES_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 48.00 | 48.00 | 48.00 | 270.00 | 90.00 | 12.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 233 | OFFICES_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | LOBBY_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 234 | OFFICES_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR | 0.123 | 0.119 | 441.00 | 441.00 | 441.00 | 270.00 | 180.00 | 21.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 235 | OFFICES_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 441.00 | 441.00 | 441.00 | 90.00 | 0.00 | 21.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 236 | OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 882.00 | 882.00 | 882.00 | 0.00 | 90.00 | 882.00 | 1.00 | 0.00 | OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 237 | GYM_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | OFFICES_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | GYM_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 51.09 | 68.00 | 51.09 | 90.00 | 90.00 | 17.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 239 | GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | Window | GYM_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.17 | 1.17 | 1.17 | 90.00 | 90.00 | 1.22 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 240 | GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | Window | GYM_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 13.79 | 13.79 | 13.79 | 90.00 | 90.00 | 14.46 | 0.95 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 241 | GYM_ZN_1_FLR_1_WALL_2_DOOR | Door | GYM_ZN_1_FLR_1_WALL_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 242 | GYM_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | KITCHEN_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 243 | GYM_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.00 | 68.00 | 68.00 | 270.00 | 90.00 | 17.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 244 | GYM_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | GYM_ZN_1_FLR_1_FLOOR_FFACTOR | 6.074E-002 | 5.986E-002 | 357.00 | 357.00 | 357.00 | 270.00 | 180.00 | 17.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 245 | GYM_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 343.62 | 357.00 | 343.62 | 90.00 | 0.00 | 17.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 246 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 247 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 248 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 249 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 250 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 251 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 252 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 253 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 254 | GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | Window | GYM_ZN_1_FLR_1_CEILING | Window5 Detailed Fenestration | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | N/A | 3.922 | No | 1.49 | 1.49 | 1.49 | 90.00 | 0.00 | 1.22 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 4.44E-016 | 1.00 | 4 |
| 255 | GYM_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 714.00 | 714.00 | 714.00 | 0.00 | 90.00 | 714.00 | 1.00 | 0.00 | GYM_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 256 | KITCHEN_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | GYM_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 257 | KITCHEN_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 24.96 | 32.00 | 24.96 | 90.00 | 90.00 | 8.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 258 | KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | Window | KITCHEN_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 7.04 | 7.04 | 7.04 | 90.00 | 90.00 | 7.90 | 0.89 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 259 | KITCHEN_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_WALL_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 260 | KITCHEN_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 32.00 | 32.00 | 32.00 | 270.00 | 90.00 | 8.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 261 | KITCHEN_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR | 6.074E-002 | 5.986E-002 | 168.00 | 168.00 | 168.00 | 270.00 | 180.00 | 8.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 262 | KITCHEN_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 168.00 | 168.00 | 168.00 | 90.00 | 0.00 | 8.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 263 | KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 336.00 | 336.00 | 336.00 | 0.00 | 90.00 | 336.00 | 1.00 | 0.00 | KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 264 | CAFETERIA_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 84.00 | 84.00 | 84.00 | 180.00 | 90.00 | 21.00 | 4.00 | 0.00 | KITCHEN_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 265 | CAFETERIA_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 44.85 | 60.00 | 44.85 | 90.00 | 90.00 | 15.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 266 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | Window | CAFETERIA_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.18 | 1.18 | 1.18 | 90.00 | 90.00 | 1.22 | 0.96 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 267 | CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | Window | CAFETERIA_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 12.02 | 12.02 | 12.02 | 90.00 | 90.00 | 12.46 | 0.96 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 268 | CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | Door | CAFETERIA_ZN_1_FLR_1_WALL_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 269 | CAFETERIA_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 65.52 | 84.00 | 65.52 | 0.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.54 | 0.46 | 4 | ||
| 270 | CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | Window | CAFETERIA_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 18.48 | 18.48 | 18.48 | 0.00 | 90.00 | 20.90 | 0.88 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.54 | 0.46 | 4 |
| 271 | CAFETERIA_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 40.00 | 40.00 | 40.00 | 270.00 | 90.00 | 10.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 272 | CAFETERIA_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 20.00 | 20.00 | 20.00 | 270.00 | 90.00 | 5.00 | 4.00 | 0.00 | MECH_ZN_1_FLR_1_WALL_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 273 | CAFETERIA_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR | 0.148 | 0.143 | 315.00 | 315.00 | 315.00 | 270.00 | 180.00 | 15.00 | 21.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 274 | CAFETERIA_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 315.00 | 315.00 | 315.00 | 90.00 | 0.00 | 15.00 | 21.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 275 | CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 630.00 | 630.00 | 630.00 | 0.00 | 90.00 | 630.00 | 1.00 | 0.00 | CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 276 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 76.00 | 76.00 | 76.00 | 180.00 | 90.00 | 19.00 | 4.00 | 0.00 | BATH_ZN_1_FLR_1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 277 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 63.57 | 84.00 | 63.57 | 90.00 | 90.00 | 21.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.54 | 0.46 | 4 | ||
| 278 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | Window | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.14 | 1.14 | 1.14 | 90.00 | 90.00 | 1.22 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.69 | 0.31 | 4 |
| 279 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | Window | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 17.33 | 17.33 | 17.33 | 90.00 | 90.00 | 18.46 | 0.94 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.53 | 0.47 | 4 |
| 280 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | Door | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.65 | 0.35 | 4 | |
| 281 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 59.28 | 76.00 | 59.28 | 0.00 | 90.00 | 19.00 | 4.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 282 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | Window | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 16.72 | 16.72 | 16.72 | 0.00 | 90.00 | 18.90 | 0.88 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 283 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 284 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 12.00 | 12.00 | 12.00 | 270.00 | 90.00 | 3.00 | 4.00 | 0.00 | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 285 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 36.00 | 36.00 | 36.00 | 270.00 | 90.00 | 9.00 | 4.00 | 0.00 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 286 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR | Floor | CTF - ConductionTransferFunction | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR | 0.129 | 0.125 | 399.00 | 399.00 | 399.00 | 270.00 | 180.00 | 21.00 | 19.00 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 287 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 399.00 | 399.00 | 399.00 | 90.00 | 0.00 | 21.00 | 19.00 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 288 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 798.00 | 798.00 | 798.00 | 0.00 | 90.00 | 798.00 | 1.00 | 0.00 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1320180328 | 0.1436817111 | Pass | Pass | 4.7981571442 | 23.4918076517 | Pass | Pass |
| 2 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.2498801680E-002 | 9.9994855477E-002 | Pass | Pass | 0.9712191386 | 4.7777551179 | Pass | Pass |
| 3 | CORRIDOR_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.3039277391E-002 | 7.3330680051E-002 | Pass | Pass | 7.0260541198 | 21.2468330323 | Pass | Pass |
| 4 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.2378440411 | 0.2571586671 | Pass | Pass | 4.3182788167 | 12.5106470943 | Pass | Pass |
| 5 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1263064366 | 0.1431544570 | Pass | Pass | 3.8208141540 | 10.7900577375 | Pass | Pass |
| 6 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1394103227 | 0.1537851065 | Pass | Pass | 3.5869631888 | 12.2005447059 | Pass | Pass |
| 7 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.3967465223E-002 | 8.6619109674E-002 | Pass | Pass | 0.9568321953 | 3.4971738457 | Pass | Pass |
| 8 | CORRIDOR_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.2417339671E-002 | 8.4512294332E-002 | Pass | Pass | 17.0619323846 | 88.0777764255 | Pass | Pass |
| 9 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.2395428398 | 0.2589866957 | Pass | Pass | 4.3888387526 | 12.7473905900 | Pass | Pass |
| 10 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1281992037 | 0.1450492850 | Pass | Pass | 3.8371101116 | 10.8678116718 | Pass | Pass |
| 11 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1371284283 | 0.1512294261 | Pass | Pass | 2.9916253278 | 9.9567130648 | Pass | Pass |
| 12 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.5521059787E-002 | 9.0077474683E-002 | Pass | Pass | 0.6834310181 | 1.1746057129 | Pass | Pass |
| 13 | CORRIDOR_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.9196135764E-002 | 8.1185152663E-002 | Pass | Pass | 8.7368294048 | 25.3475841799 | Pass | Pass |
| 14 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.2394361796 | 0.2592271187 | Pass | Pass | 4.3475555489 | 12.6190561886 | Pass | Pass |
| 15 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1315869958 | 0.1494419347 | Pass | Pass | 3.8920399299 | 11.0715985066 | Pass | Pass |
| 16 | COMPUTER_CLASS_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.7082811629E-002 | 0.1170014059 | Pass | Pass | 14.6716260275 | 129.8580384804 | Pass | Pass |
| 17 | MAIN_CORRIDOR_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.1404300498E-002 | 9.1225542114E-002 | Pass | Pass | 8.2442159208 | 24.6383974677 | Pass | Pass |
| 18 | LOBBY_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 8.5899712571E-002 | 8.8995005626E-002 | Pass | Pass | 3.3689143465 | 18.4816272365 | Pass | Pass |
| 19 | MECH_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.5368527388E-002 | 3.1969512828E-002 | Pass | Pass | 0.5224933428 | 0.8681811089 | Pass | Pass |
| 20 | BATH_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1278102974 | 0.1366481164 | Pass | Pass | 7.0614525052 | 21.4638088045 | Pass | Pass |
| 21 | OFFICES_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 7.2394743405E-002 | 7.8673498415E-002 | Pass | Pass | 29.8398265291 | 308.2478662880 | Pass | Pass |
| 22 | GYM_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 4.8706694728E-002 | 4.7335659952E-002 | Pass | Pass | 1.6173796851 | 5.6902444657 | Pass | Pass |
| 23 | KITCHEN_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 6.5808461828E-002 | 0.1700061553 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 24 | CAFETERIA_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 0.1075774186 | 0.1546352120 | Pass | Pass | 0.4852958754 | 2.1422039714 | Pass | Pass |
| 25 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | RunPeriod: RUNPERIOD 1 | 9.3426383157E-002 | 0.1132398840 | Pass | Pass | 5.1562298207 | 15.0115975628 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 10380.48 | 240.79 | 1596.97 | 4490.12 | 1671.42 | 18379.85 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | -27.60 | 0.00 | -27.60 | Wetbulb [C] | 2.70 | 230.00 |
| GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 33.40 | 16.00 | 16.30 | Wetbulb [C] | 4.90 | 240.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 0.00 | 0 | |||
| Feb | 0.00 | 0 | |||
| Mar | 0.00 | 0 | |||
| Apr | 11.00 | 18 | |||
| May | 24.00 | 14 | |||
| Jun | 29.00 | 21 | |||
| Jul | 6.00 | 9 | |||
| Aug | 0.00 | 0 | |||
| Sep | 0.00 | 0 | |||
| Oct | 0.00 | 0 | |||
| Nov | 0.00 | 0 | |||
| Dec | 0.00 | 0 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 44.00 | 32.37 | 180.00 | 90.00 | S |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 212.00 | 161.46 | 180.00 | 90.00 | S |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR | MULT_CLASS_1_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 12.00 | 9.36 | 270.00 | 90.00 | W |
| CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR | CORRIDOR_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.020 | 0.020 | 192.00 | 192.00 | 270.00 | 180.00 | |
| CORRIDOR_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 192.00 | 192.00 | 90.00 | 0.00 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 44.00 | 32.37 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 212.00 | 161.46 | 0.00 | 90.00 | N |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR | MULT_CLASS_2_POD_1_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 44.00 | 32.37 | 180.00 | 90.00 | S |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 212.00 | 161.46 | 180.00 | 90.00 | S |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR | MULT_CLASS_1_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 12.00 | 9.36 | 270.00 | 90.00 | W |
| CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR | CORRIDOR_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.020 | 0.020 | 192.00 | 192.00 | 270.00 | 180.00 | |
| CORRIDOR_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 192.00 | 192.00 | 90.00 | 0.00 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 44.00 | 32.37 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 212.00 | 161.46 | 0.00 | 90.00 | N |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR | MULT_CLASS_2_POD_2_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 44.00 | 32.37 | 180.00 | 90.00 | S |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 212.00 | 161.46 | 180.00 | 90.00 | S |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR | MULT_CLASS_1_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 477.00 | 477.00 | 270.00 | 180.00 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 477.00 | 477.00 | 90.00 | 0.00 | |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 12.00 | 9.36 | 270.00 | 90.00 | W |
| CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR | CORRIDOR_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.020 | 0.020 | 192.00 | 192.00 | 270.00 | 180.00 | |
| CORRIDOR_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 192.00 | 192.00 | 90.00 | 0.00 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 44.00 | 32.40 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 36.00 | 28.08 | 270.00 | 90.00 | W |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.255 | 0.266 | 99.00 | 99.00 | 270.00 | 180.00 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 99.00 | 99.00 | 90.00 | 0.00 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 140.00 | 105.30 | 0.00 | 90.00 | N |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR | MULT_CLASS_2_POD_3_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 315.00 | 315.00 | 270.00 | 180.00 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 315.00 | 315.00 | 90.00 | 0.00 | |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 72.00 | 54.21 | 0.00 | 90.00 | N |
| COMPUTER_CLASS_ZN_1_FLR_1_FLOOR | COMPUTER_CLASS_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 162.00 | 162.00 | 270.00 | 180.00 | |
| COMPUTER_CLASS_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 162.00 | 162.00 | 90.00 | 0.00 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 36.00 | 26.13 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR | MAIN_CORRIDOR_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.021 | 0.021 | 546.00 | 546.00 | 270.00 | 180.00 | |
| MAIN_CORRIDOR_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 546.00 | 546.00 | 90.00 | 0.00 | |
| LOBBY_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 76.00 | 57.33 | 180.00 | 90.00 | S |
| LOBBY_ZN_1_FLR_1_FLOOR | LOBBY_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.140 | 0.144 | 171.00 | 171.00 | 270.00 | 180.00 | |
| LOBBY_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 171.00 | 171.00 | 90.00 | 0.00 | |
| MECH_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 252.00 | 252.00 | 90.00 | 0.00 | |
| BATH_ZN_1_FLR_1_WALL_5 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 40.00 | 31.20 | 270.00 | 90.00 | W |
| BATH_ZN_1_FLR_1_FLOOR | BATH_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.066 | 0.067 | 190.00 | 190.00 | 270.00 | 180.00 | |
| BATH_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 190.00 | 190.00 | 90.00 | 0.00 | |
| OFFICES_ZN_1_FLR_1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 84.00 | 63.57 | 180.00 | 90.00 | S |
| OFFICES_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 84.00 | 65.52 | 90.00 | 90.00 | E |
| OFFICES_ZN_1_FLR_1_FLOOR | OFFICES_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.120 | 0.123 | 441.00 | 441.00 | 270.00 | 180.00 | |
| OFFICES_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 441.00 | 441.00 | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 68.00 | 51.09 | 90.00 | 90.00 | E |
| GYM_ZN_1_FLR_1_FLOOR | GYM_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.060 | 0.061 | 357.00 | 357.00 | 270.00 | 180.00 | |
| GYM_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 357.00 | 343.62 | 90.00 | 0.00 | |
| KITCHEN_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 32.00 | 24.96 | 90.00 | 90.00 | E |
| KITCHEN_ZN_1_FLR_1_FLOOR | KITCHEN_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.060 | 0.061 | 168.00 | 168.00 | 270.00 | 180.00 | |
| KITCHEN_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 168.00 | 168.00 | 90.00 | 0.00 | |
| CAFETERIA_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 60.00 | 44.85 | 90.00 | 90.00 | E |
| CAFETERIA_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 84.00 | 65.52 | 0.00 | 90.00 | N |
| CAFETERIA_ZN_1_FLR_1_FLOOR | CAFETERIA_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.144 | 0.148 | 315.00 | 315.00 | 270.00 | 180.00 | |
| CAFETERIA_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 315.00 | 315.00 | 90.00 | 0.00 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 84.00 | 63.57 | 90.00 | 90.00 | E |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 76.00 | 59.28 | 0.00 | 90.00 | N |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.127 | 0.129 | 399.00 | 399.00 | 270.00 | 180.00 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_CEILING | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 399.00 | 399.00 | 90.00 | 0.00 |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 90.00 | 90.00 | E |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 90.00 | 90.00 | E |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 0.00 | 90.00 | N |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 212.00 | 212.00 | 180.00 | 90.00 | S |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 90.00 | 90.00 | E |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 72.00 | 72.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 140.00 | 140.00 | 0.00 | 90.00 | N |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 0.00 | 90.00 | N |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 44.00 | 44.00 | 180.00 | 90.00 | S |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 140.00 | 140.00 | 180.00 | 90.00 | S |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 72.00 | 72.00 | 180.00 | 90.00 | S |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 180.00 | 90.00 | S |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 168.00 | 168.00 | 90.00 | 90.00 | E |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 0.00 | 90.00 | N |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_8 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_9 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 270.00 | 90.00 | W |
| LOBBY_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 90.00 | 90.00 | E |
| LOBBY_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 0.00 | 90.00 | N |
| LOBBY_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 0.00 | 90.00 | N |
| LOBBY_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| MECH_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 180.00 | 90.00 | S |
| MECH_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 48.00 | 48.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 68.00 | 68.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 32.00 | 32.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 20.00 | 20.00 | 90.00 | 90.00 | E |
| MECH_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 0.00 | 90.00 | N |
| MECH_ZN_1_FLR_1_WALL_7 | INT_WALL | 0.30 | 2.511 | 6.299 | 168.00 | 168.00 | 270.00 | 90.00 | W |
| MECH_ZN_1_FLR_1_FLOOR | MECH_ZN_1_FLR_1_FLOOR_FFACTOR | 1.00 | 0.006 | 0.006 | 252.00 | 252.00 | 270.00 | 180.00 | |
| BATH_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 52.00 | 52.00 | 180.00 | 90.00 | S |
| BATH_ZN_1_FLR_1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 24.00 | 24.00 | 180.00 | 90.00 | S |
| BATH_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 40.00 | 40.00 | 90.00 | 90.00 | E |
| BATH_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 76.00 | 76.00 | 0.00 | 90.00 | N |
| OFFICES_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 0.00 | 90.00 | N |
| OFFICES_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 48.00 | 48.00 | 270.00 | 90.00 | W |
| OFFICES_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| GYM_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 180.00 | 90.00 | S |
| GYM_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 0.00 | 90.00 | N |
| GYM_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 68.00 | 68.00 | 270.00 | 90.00 | W |
| KITCHEN_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 180.00 | 90.00 | S |
| KITCHEN_ZN_1_FLR_1_WALL_3 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 0.00 | 90.00 | N |
| KITCHEN_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 32.00 | 32.00 | 270.00 | 90.00 | W |
| CAFETERIA_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 84.00 | 84.00 | 180.00 | 90.00 | S |
| CAFETERIA_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 40.00 | 40.00 | 270.00 | 90.00 | W |
| CAFETERIA_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 20.00 | 20.00 | 270.00 | 90.00 | W |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_1 | INT_WALL | 0.30 | 2.511 | 6.299 | 76.00 | 76.00 | 180.00 | 90.00 | S |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_5 | INT_WALL | 0.30 | 2.511 | 6.299 | 12.00 | 12.00 | 270.00 | 90.00 | W |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_6 | INT_WALL | 0.30 | 2.511 | 6.299 | 36.00 | 36.00 | 270.00 | 90.00 | W |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORRIDOR_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 384.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORRIDOR_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 384.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 954.00 | 0.00 | 90.00 | N | ||
| CORRIDOR_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 384.00 | 0.00 | 90.00 | N | ||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 198.00 | 0.00 | 90.00 | N | ||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 630.00 | 0.00 | 90.00 | N | ||
| COMPUTER_CLASS_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 324.00 | 0.00 | 90.00 | N | ||
| MAIN_CORRIDOR_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 1092.00 | 0.00 | 90.00 | N | ||
| LOBBY_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 342.00 | 0.00 | 90.00 | N | ||
| MECH_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 504.00 | 0.00 | 90.00 | N | ||
| BATH_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 380.00 | 0.00 | 90.00 | N | ||
| OFFICES_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 882.00 | 0.00 | 90.00 | N | ||
| GYM_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 714.00 | 0.00 | 90.00 | N | ||
| KITCHEN_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 336.00 | 0.00 | 90.00 | N | ||
| CAFETERIA_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 630.00 | 0.00 | 90.00 | N | ||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 798.00 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.64 | 0.00 | 0.00 | 2.64 | 2.64 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6 | 270.00 | 90.00 | W | |||||||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.64 | 0.00 | 0.00 | 2.64 | 2.64 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6 | 270.00 | 90.00 | W | |||||||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.46 | 0.00 | 0.00 | 8.46 | 8.46 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.55 | 0.00 | 0.00 | 15.55 | 15.55 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.64 | 0.00 | 0.00 | 2.64 | 2.64 | 3.241 | 0.391 | 0.431 | No | CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7 | 270.00 | 90.00 | W | |||||||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.22 | 0.00 | 0.00 | 1.22 | 1.22 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.43 | 0.00 | 0.00 | 8.43 | 8.43 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.92 | 0.00 | 0.00 | 7.92 | 7.92 | 3.241 | 0.391 | 0.431 | No | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4 | 270.00 | 90.00 | W | |||||||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 10.27 | 0.00 | 0.00 | 10.27 | 10.27 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 10.27 | 0.00 | 0.00 | 10.27 | 10.27 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 10.27 | 0.00 | 0.00 | 10.27 | 10.27 | 3.241 | 0.391 | 0.431 | No | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.16 | 0.00 | 0.00 | 1.16 | 1.16 | 3.241 | 0.391 | 0.431 | No | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 14.68 | 0.00 | 0.00 | 14.68 | 14.68 | 3.241 | 0.391 | 0.431 | No | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.26 | 0.00 | 0.00 | 1.26 | 1.26 | 3.241 | 0.391 | 0.431 | No | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | 270.00 | 90.00 | W | |||||||
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 6.66 | 0.00 | 0.00 | 6.66 | 6.66 | 3.241 | 0.391 | 0.431 | No | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 | 270.00 | 90.00 | W | |||||||
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.15 | 0.00 | 0.00 | 1.15 | 1.15 | 3.241 | 0.391 | 0.431 | No | LOBBY_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 15.57 | 0.00 | 0.00 | 15.57 | 15.57 | 3.241 | 0.391 | 0.431 | No | LOBBY_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 8.80 | 0.00 | 0.00 | 8.80 | 8.80 | 3.241 | 0.391 | 0.431 | No | BATH_ZN_1_FLR_1_WALL_5 | 270.00 | 90.00 | W | |||||||
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.14 | 0.00 | 0.00 | 1.14 | 1.14 | 3.241 | 0.391 | 0.431 | No | OFFICES_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 17.34 | 0.00 | 0.00 | 17.34 | 17.34 | 3.241 | 0.391 | 0.431 | No | OFFICES_ZN_1_FLR_1_WALL_1 | 180.00 | 90.00 | S | |||||||
| OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 18.48 | 0.00 | 0.00 | 18.48 | 18.48 | 3.241 | 0.391 | 0.431 | No | OFFICES_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.17 | 0.00 | 0.00 | 1.17 | 1.17 | 3.241 | 0.391 | 0.431 | No | GYM_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 13.79 | 0.00 | 0.00 | 13.79 | 13.79 | 3.241 | 0.391 | 0.431 | No | GYM_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | NONRESSKYLIGHT_U_0.69_SHGC_0.49 | SKYLIGHT_FRAME_NONRES | 1.49 | 0.00 | 0.00 | 1.49 | 1.49 | 3.922 | 0.493 | 0.492 | 0.000 | 0.000 | CurtainWall | 3.786 | 0.497 | 0.492 | No | GYM_ZN_1_FLR_1_CEILING | 90.00 | 0.00 | |
| KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 7.04 | 0.00 | 0.00 | 7.04 | 7.04 | 3.241 | 0.391 | 0.431 | No | KITCHEN_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.18 | 0.00 | 0.00 | 1.18 | 1.18 | 3.241 | 0.391 | 0.431 | No | CAFETERIA_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 12.02 | 0.00 | 0.00 | 12.02 | 12.02 | 3.241 | 0.391 | 0.431 | No | CAFETERIA_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 18.48 | 0.00 | 0.00 | 18.48 | 18.48 | 3.241 | 0.391 | 0.431 | No | CAFETERIA_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.14 | 0.00 | 0.00 | 1.14 | 1.14 | 3.241 | 0.391 | 0.431 | No | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 17.33 | 0.00 | 0.00 | 17.33 | 17.33 | 3.241 | 0.391 | 0.431 | No | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 | 90.00 | 90.00 | E | |||||||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 16.72 | 0.00 | 0.00 | 16.72 | 16.72 | 3.241 | 0.391 | 0.431 | No | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3 | 0.00 | 90.00 | N | |||||||
| Total or Average | 565.98 | 3.257 | 0.394 | 0.432 | |||||||||||||||||
| North Total or Average | 204.13 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
| Non-North Total or Average | 361.86 | 3.266 | 0.395 | 0.433 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR1 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_DOOR2 | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3 |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | COMPUTER_CLASS_ZN_1_FLR_1_WALL_3 |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7 |
| LOBBY_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LOBBY_ZN_1_FLR_1_WALL_1 |
| OFFICES_ZN_1_FLR_1_WALL_1_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | OFFICES_ZN_1_FLR_1_WALL_1 |
| GYM_ZN_1_FLR_1_WALL_2_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | GYM_ZN_1_FLR_1_WALL_2 |
| CAFETERIA_ZN_1_FLR_1_WALL_2_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | CAFETERIA_ZN_1_FLR_1_WALL_2 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2 |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.99 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3 | 0.70 | 0.96 | 1.00 | 0.86 | 0.98 | 1.00 | 0.00 | 0.95 | 1.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3 | 0.70 | 0.96 | 1.00 | 0.86 | 0.98 | 1.00 | 0.00 | 0.95 | 1.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 0.78 |
| MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2 | 0.00 | 0.00 | 0.64 | 0.00 | 0.00 | 0.89 | 0.00 | 0.00 | 0.03 |
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| BATH_ZN_1_FLR_1_WALL_5_WINDOW_1 | 0.00 | 0.00 | 0.78 | 0.00 | 0.00 | 0.93 | 0.00 | 0.00 | 0.30 |
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GYM_ZN_1_FLR_1_WALL_2_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GYM_ZN_1_FLR_1_WALL_2_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.76 | 0.32 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2 | 0.99 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 0.24 | 0.83 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1_LIGHTS | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORRIDOR_POD_1_ZN_1_FLR_1_LIGHTS | CORRIDOR_POD_1_ZN_1_FLR_1 | CORRIDOR_POD_1_ZN_1_FLR_1 | GENERAL | 5.4810 | 192.00 | 1052.35 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 14.50 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1_LIGHTS | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1_LIGHTS | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORRIDOR_POD_2_ZN_1_FLR_1_LIGHTS | CORRIDOR_POD_2_ZN_1_FLR_1 | CORRIDOR_POD_2_ZN_1_FLR_1 | GENERAL | 5.4810 | 192.00 | 1052.35 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 14.50 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1_LIGHTS | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1_LIGHTS | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 477.00 | 7188.13 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 99.06 |
| CORRIDOR_POD_3_ZN_1_FLR_1_LIGHTS | CORRIDOR_POD_3_ZN_1_FLR_1 | CORRIDOR_POD_3_ZN_1_FLR_1 | GENERAL | 5.4810 | 192.00 | 1052.35 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 14.50 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 99.00 | 1491.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 20.56 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1_LIGHTS | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | GENERAL | 15.0695 | 315.00 | 4746.88 | LightsWired | LTG_SCH_CLASSROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 65.42 |
| COMPUTER_CLASS_ZN_1_FLR_1_LIGHTS | COMPUTER_CLASS_ZN_1_FLR_1 | COMPUTER_CLASS_ZN_1_FLR_1 | GENERAL | 15.0695 | 162.00 | 2441.25 | LightsWired | LTG_SCH_COMPUTER_ROOM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 33.64 |
| MAIN_CORRIDOR_ZN_1_FLR_1_LIGHTS | MAIN_CORRIDOR_ZN_1_FLR_1 | MAIN_CORRIDOR_ZN_1_FLR_1 | GENERAL | 5.4810 | 546.00 | 2992.63 | LightsWired | LTG_SCH_CORRIDOR | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 41.24 |
| LOBBY_ZN_1_FLR_1_LIGHTS | LOBBY_ZN_1_FLR_1 | LOBBY_ZN_1_FLR_1 | GENERAL | 13.9931 | 171.00 | 2392.81 | LightsWired | LTG_SCH_LOBBY | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 32.97 |
| MECH_ZN_1_FLR_1_LIGHTS | MECH_ZN_1_FLR_1 | MECH_ZN_1_FLR_1 | GENERAL | 16.1458 | 252.00 | 4068.75 | LightsWired | LTG_SCH_MECHANICAL | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 56.07 |
| BATH_ZN_1_FLR_1_LIGHTS | BATH_ZN_1_FLR_1 | BATH_ZN_1_FLR_1 | GENERAL | 9.6875 | 190.00 | 1840.63 | LightsWired | LTG_SCH_BATH | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 25.37 |
| OFFICES_ZN_1_FLR_1_LIGHTS | OFFICES_ZN_1_FLR_1 | OFFICES_ZN_1_FLR_1 | GENERAL | 11.8403 | 441.00 | 5221.57 | LightsWired | LTG_SCH_OFFICE | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 71.96 |
| GYM_ZN_1_FLR_1_LIGHTS | GYM_ZN_1_FLR_1 | GYM_ZN_1_FLR_1 | GENERAL | 13.3472 | 357.00 | 4764.96 | LightsWired | LTG_SCH_GYM | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 65.67 |
| KITCHEN_ZN_1_FLR_1_LIGHTS | KITCHEN_ZN_1_FLR_1 | KITCHEN_ZN_1_FLR_1 | GENERAL | 12.9167 | 168.00 | 2170.00 | LightsWired | LTG_SCH_KITCHEN | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 29.90 |
| CAFETERIA_ZN_1_FLR_1_LIGHTS | CAFETERIA_ZN_1_FLR_1 | CAFETERIA_ZN_1_FLR_1 | GENERAL | 9.6875 | 315.00 | 3051.57 | LightsWired | LTG_SCH_CAFETERIA | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 42.05 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_LIGHTS | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | GENERAL | 16.6840 | 399.00 | 6656.93 | LightsWired | LTG_SCH_LIBRARY | 74.85 | 168.00 | 73.41 | 0.0000 | Y | 91.74 |
| Interior Lighting Total | 12.8652 | 6871.00 | 88396.96 | 1218.18 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| EXTERIOR_LIGHTS | 5897.73 | AstronomicalClock | - | 83.57 | 83.57 | 92.52 | |
| Exterior Lighting Total | 5897.73 | 92.52 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| HEATSYS1 BOILER | Boiler:HotWater | 479510.31 | 0.75 |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | 601222.91 | 481522.85 | 119700.06 | 0.80 | 3.60 | |||
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35017.39 | 27316.72 | 7700.67 | 0.78 | 3.50 | |||
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 64918.53 | 48899.88 | 16018.65 | 0.75 | 3.40 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| VAV_POD_1 COOLING COIL | 576809.5 | 3.02 | 10.30 | N/A | N/A | 11.09 | |
| PSZ-AC_1:6 COOLING COIL | 33629.0 | 10.75 | 10.75 | ||||
| PSZ-AC_2:7 COOLING COIL | 62516.5 | 10.62 | 10.62 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | ||||||||
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11907.98 | 11299.63 | - |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 38222.10 | 36269.44 | - |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10788.57 | 10237.41 | - |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11772.67 | 11171.24 | - |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 37498.14 | 35582.47 | - |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11869.23 | 11262.86 | - |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 37869.19 | 35934.56 | - |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10775.08 | 10224.62 | - |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11776.35 | 11174.73 | - |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 37513.27 | 35596.83 | - |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11873.72 | 11267.13 | - |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 37986.14 | 36045.54 | - |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 10790.49 | 10239.23 | - |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11810.21 | 11206.86 | - |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25329.04 | 24035.05 | - |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 12456.90 | 11820.52 | - |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 25693.54 | 24380.93 | - |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 15128.47 | 14355.60 | - |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 8574.96 | 8136.89 | - |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 11781.56 | 11179.68 | - |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 33470.24 | 31760.34 | - |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 24777.59 | 23511.77 | - |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 29844.87 | 28320.19 | - |
| VAV_POD_1 HEATING COIL | Coil:Heating:Fuel | 422739.69 | 0.79 | |
| PSZ-AC_1:6 HEATING COIL | Coil:Heating:Fuel | 34404.54 | 0.80 | |
| PSZ-AC_2:7 HEATING COIL | Coil:Heating:Fuel | 112439.17 | 0.79 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| BATH_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 0.28 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| GYM_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.54 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| KITCHEN_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 2.12 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| CAFETERIA_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.38 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 0.28 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| VAV_POD_1 FAN | Fan:VariableVolume | 0.62 | 1337.13 | 32.89 | 70914.77 | 2156.31 | 1.00 | 1.11 | General | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
| PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 966.87 | 1.77 | 2936.62 | 1662.00 | 1.00 | 1.24 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.60 | 966.87 | 3.05 | 4952.98 | 1622.12 | 1.00 | 1.21 | General | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.004195 | 1263.34 | 301156.09 | 0.90 | General |
| SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000105 | 13.47 | 127739.32 | 0.30 | General |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| SWH BOOSTER G WATER HEATER | WaterHeater:Mixed | 0.02 | 6000.00 | 0.80 | 1.09 | 0.99 |
| SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 14.75 | 0.47 |
| DX Cooling Coil Type | Assocated Fan | Net Cooling Capacity [W] | COP [W/W] | EER [Btu/W-h] | IEER [Btu/W-h] | Supply Air Flow 100% [kg/s] | COP 75% Capacity [W/W] | EER 75% Capacity [Btu/W-h] | Supply Air Flow 75% [kg/s] | COP 50% Capacity [W/W] | EER 50% Capacity [Btu/W-h] | Supply Air Flow 50% [kg/s] | COP 25% Capacity [W/W] | EER 25% Capacity [Btu/W-h] | Supply Air Flow 25% [kg/s] | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | None | 576809.52 | 3.02 | 10.30 | 11.09 | 33.2668 | 3.24 | 11.06 | 26.4192 | 3.22 | 11.00 | 17.7220 | 3.38 | 11.54 | 7.1494 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 7660.48 | 8809.56 | 88.99 | 0.643 | 0.740 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00771 | 32.60 | 0.00631 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 32069.81 | 36880.28 | 77.32 | 2.694 | 3.098 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00783 | 33.40 | 0.00631 | 0.897 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 6434.97 | 7400.21 | 38.54 | 0.540 | 0.621 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00734 | 32.76 | 0.00631 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 6887.15 | 7920.22 | 80.00 | 0.578 | 0.665 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00779 | 31.37 | 0.00630 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 27332.50 | 31432.38 | 65.90 | 2.296 | 2.640 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00798 | 33.40 | 0.00631 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 7603.68 | 8744.23 | 88.33 | 0.639 | 0.734 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00772 | 32.60 | 0.00631 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 31700.42 | 36455.48 | 76.43 | 2.663 | 3.062 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00784 | 33.40 | 0.00631 | 0.897 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 6413.45 | 7375.47 | 38.41 | 0.539 | 0.619 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00734 | 32.76 | 0.00631 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 6891.15 | 7924.82 | 80.05 | 0.579 | 0.666 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00779 | 31.37 | 0.00630 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 27349.52 | 31451.94 | 65.94 | 2.297 | 2.642 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00797 | 33.40 | 0.00631 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 7610.22 | 8751.75 | 88.40 | 0.639 | 0.735 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00772 | 32.60 | 0.00631 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 31835.01 | 36610.26 | 76.75 | 2.674 | 3.075 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00784 | 33.40 | 0.00631 | 0.897 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 6477.23 | 7448.81 | 38.80 | 0.544 | 0.625 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:40:00 | 24.00 | 24.00 | 0.00734 | 32.76 | 0.00631 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 6946.58 | 7988.57 | 80.69 | 0.583 | 0.671 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00778 | 31.37 | 0.00630 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 18403.06 | 21163.52 | 67.19 | 1.546 | 1.778 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00796 | 33.40 | 0.00631 | 0.592 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 10159.87 | 11683.85 | 72.12 | 0.853 | 0.981 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00789 | 33.40 | 0.00631 | 0.304 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 13942.73 | 16034.14 | 29.37 | 1.171 | 1.346 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:50:00 | 24.00 | 24.00 | 0.00744 | 32.60 | 0.00631 | 0.166 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 8150.29 | 9372.83 | 54.81 | 0.684 | 0.787 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00746 | 33.40 | 0.00631 | 0.096 | 0.00 |
| MECH_ZN_1_FLR_1 | 9688.60 | 11141.89 | 44.21 | 0.813 | 0.935 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00709 | 33.40 | 0.00631 | 0.000 | 0.00 |
| BATH_ZN_1_FLR_1 | 6482.31 | 7454.66 | 39.24 | 0.544 | 0.626 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00732 | 31.37 | 0.00630 | 0.000 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 19750.09 | 22712.61 | 51.50 | 1.658 | 1.907 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 24.00 | 24.00 | 0.00724 | 33.40 | 0.00631 | 0.190 | 0.00 |
| GYM_ZN_1_FLR_1 | 22006.27 | 25307.21 | 70.89 | 1.849 | 2.126 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 24.00 | 23.99 | 0.00810 | 33.40 | 0.00631 | 0.544 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 18273.34 | 21014.34 | 125.09 | 1.536 | 1.767 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 24.00 | 23.99 | 0.00903 | 31.96 | 0.00630 | 0.255 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 31571.83 | 36307.61 | 115.26 | 2.655 | 3.053 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 24.00 | 23.98 | 0.00925 | 32.60 | 0.00631 | 1.488 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 20937.25 | 24077.83 | 60.35 | 1.758 | 2.022 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00742 | 33.40 | 0.00631 | 0.345 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 5507.39 | 6884.24 | 69.54 | 0.462 | 0.577 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00786 | -27.60 | 0.00034 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 17676.96 | 22096.20 | 46.32 | 1.481 | 1.852 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -27.60 | 0.00034 | 0.897 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 4989.04 | 6236.30 | 32.48 | 0.418 | 0.523 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00798 | -27.60 | 0.00034 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 5444.82 | 6806.03 | 68.75 | 0.456 | 0.570 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00786 | -27.60 | 0.00034 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 17342.18 | 21677.72 | 45.45 | 1.453 | 1.817 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -27.60 | 0.00034 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 5489.47 | 6861.84 | 69.31 | 0.460 | 0.575 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00786 | -27.60 | 0.00034 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 17513.76 | 21892.20 | 45.90 | 1.468 | 1.835 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -27.60 | 0.00034 | 0.897 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 4982.81 | 6228.51 | 32.44 | 0.418 | 0.522 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00798 | -27.60 | 0.00034 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 5446.52 | 6808.15 | 68.77 | 0.456 | 0.571 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00786 | -27.60 | 0.00034 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 17349.17 | 21686.47 | 45.46 | 1.454 | 1.817 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -27.60 | 0.00034 | 0.897 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 5491.55 | 6864.44 | 69.34 | 0.460 | 0.575 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00786 | -27.60 | 0.00034 | 0.186 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 17567.84 | 21959.80 | 46.04 | 1.472 | 1.840 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -27.60 | 0.00034 | 0.897 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 4989.93 | 6237.41 | 32.49 | 0.418 | 0.523 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00798 | -27.60 | 0.00034 | 0.059 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 5462.18 | 6827.73 | 68.97 | 0.458 | 0.572 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00786 | -27.60 | 0.00034 | 0.186 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 11714.17 | 14642.72 | 46.48 | 0.982 | 1.227 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -27.60 | 0.00034 | 0.592 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 5761.09 | 7201.36 | 44.45 | 0.483 | 0.604 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00788 | -27.60 | 0.00034 | 0.304 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 11881.73 | 14852.16 | 27.20 | 0.996 | 1.245 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00797 | -27.60 | 0.00034 | 0.166 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 6996.56 | 8745.69 | 51.14 | 0.586 | 0.733 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -27.60 | 0.00034 | 0.096 | 0.00 |
| MECH_ZN_1_FLR_1 | 3965.30 | 4956.62 | 19.67 | 0.332 | 0.415 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00800 | -27.60 | 0.00034 | 0.000 | 0.00 |
| BATH_ZN_1_FLR_1 | 5448.49 | 6810.61 | 35.85 | 0.457 | 0.571 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00793 | -27.60 | 0.00034 | 0.000 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 15479.14 | 19348.93 | 43.88 | 1.297 | 1.622 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -27.60 | 0.00034 | 0.190 | 0.00 |
| GYM_ZN_1_FLR_1 | 11458.50 | 14323.13 | 40.12 | 0.960 | 1.200 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00794 | -27.60 | 0.00034 | 0.544 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 1542.07 | 1927.59 | 11.47 | 0.129 | 0.255 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 21.00 | 21.00 | 0.01179 | -27.60 | 0.00034 | 0.255 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 12361.33 | 15451.66 | 49.05 | 1.036 | 1.488 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 21.00 | 21.00 | 0.00789 | -27.60 | 0.00034 | 1.488 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 13802.59 | 17253.24 | 43.24 | 1.157 | 1.446 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.00 | 21.00 | 0.00789 | -27.60 | 0.00034 | 0.345 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| VAV_POD_1 | 32.89 | 32.89 | 23.23 | 23.23 | 32.8870 | 23.2306 | 32.8870 | 0.7064 | 0.3000 |
| PSZ-AC_1:6 | 1.77 | 1.77 | 0.25 | 0.25 | 1.7669 | 1.7669 | 1.7669 | 1.0000 | 1.0000 |
| PSZ-AC_2:7 | 3.05 | 3.05 | 1.49 | 1.49 | 3.0534 | 3.0534 | 3.0534 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | 11907.977 | 11907.977 | 0.576920 | 0.00010418 | 277.748 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11907.98 | 11907.98 | 0.576920 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00785880 | 44.4437 | 6884.24 | 0.00 | 11962.60 | 11962.60 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | 38222.097 | 38222.097 | 1.851763 | 0.00033438 | 891.516 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 38222.10 | 38222.10 | 1.851763 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00788305 | 44.5786 | 22096.20 | 0.00 | 38397.44 | 38397.44 |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX | 10788.566 | 10788.566 | 0.522643 | 0.00009438 | 251.644 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10788.57 | 10788.57 | 0.522643 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00797626 | 45.0985 | 6236.30 | 0.00 | 10838.06 | 10838.06 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | 11772.672 | 11772.672 | 0.570366 | 0.00010299 | 274.592 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11772.67 | 11772.67 | 0.570366 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00785721 | 44.4348 | 6806.03 | 0.00 | 11826.68 | 11826.68 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | 37498.144 | 37498.144 | 1.816692 | 0.00032805 | 874.630 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 37498.14 | 37498.14 | 1.816692 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00788083 | 44.5662 | 21677.72 | 0.00 | 37670.16 | 37670.16 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | 11869.227 | 11869.227 | 0.575043 | 0.00010384 | 276.844 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11869.23 | 11869.23 | 0.575043 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00785835 | 44.4411 | 6861.84 | 0.00 | 11923.68 | 11923.68 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | 37869.189 | 37869.189 | 1.834667 | 0.00033130 | 883.285 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 37869.19 | 37869.19 | 1.834667 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00788198 | 44.5726 | 21892.20 | 0.00 | 38042.91 | 38042.91 |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX | 10775.085 | 10775.085 | 0.521990 | 0.00009427 | 251.330 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10775.08 | 10775.08 | 0.521990 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00797623 | 45.0983 | 6228.51 | 0.00 | 10824.51 | 10824.51 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | 11776.345 | 11776.345 | 0.570544 | 0.00010302 | 274.678 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11776.35 | 11776.35 | 0.570544 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00785726 | 44.4350 | 6808.15 | 0.00 | 11830.37 | 11830.37 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | 37513.275 | 37513.275 | 1.817425 | 0.00032818 | 874.983 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 37513.27 | 37513.27 | 1.817425 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00788088 | 44.5665 | 21686.47 | 0.00 | 37685.36 | 37685.36 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | 11873.724 | 11873.724 | 0.575261 | 0.00010388 | 276.949 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11873.72 | 11873.72 | 0.575261 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00785841 | 44.4414 | 6864.44 | 0.00 | 11928.19 | 11928.19 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | 37986.137 | 37986.137 | 1.840332 | 0.00033232 | 886.013 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 37986.14 | 37986.14 | 1.840332 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00788234 | 44.5746 | 21959.80 | 0.00 | 38160.40 | 38160.40 |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX | 10790.485 | 10790.485 | 0.522736 | 0.00009440 | 251.689 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 10790.49 | 10790.49 | 0.522736 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00797626 | 45.0985 | 6237.41 | 0.00 | 10839.99 | 10839.99 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | 11810.211 | 11810.211 | 0.572184 | 0.00010332 | 275.468 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11810.21 | 11810.21 | 0.572184 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00785766 | 44.4373 | 6827.73 | 0.00 | 11864.39 | 11864.39 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | 25329.039 | 25329.039 | 1.227127 | 0.00022159 | 590.791 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 25329.04 | 25329.04 | 1.227127 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00788345 | 44.5809 | 14642.72 | 0.00 | 25445.23 | 25445.23 |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX | 12456.904 | 12456.904 | 0.603507 | 0.00010898 | 290.552 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 12456.90 | 12456.90 | 0.603507 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00787821 | 44.5516 | 7201.36 | 0.00 | 12514.05 | 12514.05 |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX | 25693.543 | 25693.543 | 1.244707 | 0.00022478 | 599.303 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 25693.54 | 25693.54 | 1.244707 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00797011 | 45.0642 | 14852.16 | 0.00 | 25811.41 | 25811.41 |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | LOBBY_ZN_1_FLR_1 VAV BOX | 15128.470 | 15128.470 | 0.732930 | 0.00013235 | 352.867 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 15128.47 | 15128.47 | 0.732930 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00789392 | 44.6393 | 8745.69 | 0.00 | 15197.87 | 15197.87 |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_ZN_1_FLR_1 VAV BOX | 8574.956 | 8574.956 | 0.415399 | 0.00007502 | 200.012 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 8574.96 | 8574.96 | 0.415399 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00800000 | 45.2310 | 4956.62 | 0.00 | 8614.29 | 8614.29 |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 11781.564 | 11781.564 | 0.570768 | 0.00010307 | 274.803 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11781.56 | 11781.56 | 0.570768 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00792798 | 44.8292 | 6810.61 | 0.00 | 11835.61 | 11835.61 |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | OFFICES_ZN_1_FLR_1 VAV BOX | 33470.239 | 33470.239 | 1.621535 | 0.00029281 | 780.683 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 33470.24 | 33470.24 | 1.621535 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00789401 | 44.6398 | 19348.93 | 0.00 | 33623.78 | 33623.78 |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 24777.586 | 24777.586 | 1.200360 | 0.00021677 | 577.935 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | 24777.59 | 24777.59 | 1.200360 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00794168 | 44.9057 | 14323.13 | 0.00 | 24891.25 | 24891.25 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | 29844.873 | 29844.873 | 1.445904 | 0.00026110 | 696.121 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 29844.87 | 29844.87 | 1.445904 | 12.89 | 10.44 | 0.00800000 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 0.0000 | 21.00 | 0.00788690 | 44.6001 | 17253.24 | 0.00 | 29981.78 | 29981.78 |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoopHVAC | VAV_POD_1 | 601222.908 | 481522.847 | 32.887040 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 575928.98 | 557273.15 | 32.887040 | 27.05 | 15.04 | 0.00727091 | 10.88 | 8.59 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 32.4848 | 24.00 | 0.00773477 | 36.4669 | 340497.41 | 0.00 | 602961.77 | 450355.66 |
| VAV_POD_1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | VAV_POD_1 | 422739.695 | 422739.695 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 422739.69 | 422739.69 | 9.866112 | -27.60 | -27.60 | 0.00034190 | 12.89 | 10.44 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 108.2828 | 21.00 | 0.00789723 | 44.6581 | 221673.71 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:6 | 35017.390 | 27316.716 | 1.766920 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 17508.69 | 14314.07 | 1.177947 | 25.10 | 15.50 | 0.00863489 | 11.34 | 8.79 | 0.00700000 | 31.96 | 0.00630459 | 15.89 | 21.6320 | 23.99 | 0.00902758 | 42.5030 | 18273.34 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_1:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:6 | 34404.542 | 34404.542 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 34404.54 | 34404.54 | 1.766923 | 13.71 | 12.47 | 0.00980745 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 14.4213 | 21.00 | 0.01140255 | 64.1132 | 937.50 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:7 | 64918.530 | 48899.883 | 3.053390 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 32459.26 | 29681.08 | 2.035593 | 28.62 | 16.01 | 0.00781523 | 11.38 | 8.81 | 0.00700000 | 33.40 | 0.00630683 | 16.37 | 73.1081 | 23.98 | 0.00928089 | 43.6875 | 31224.33 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_2:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:7 | 112439.172 | 112439.172 | -999.0 | -999.0 | -999.000 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 112439.17 | 112439.17 | 3.053392 | -2.69 | -2.69 | 0.00420926 | 32.11 | 17.27 | 0.00800000 | -27.60 | 0.00034190 | -27.60 | 48.7387 | 21.00 | 0.00788632 | 44.5973 | 12359.47 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11907.977 | 11907.977 | 0.576920 | 0.00010418 | 277.748 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 2.4344 | 2.483362 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11907.98 | 11907.98 | 1.0000 | 0.60757782 | 0.576920 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.10416555 | 60.00 | 32.22 | 27.78 | 0.000 | 11907.98 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00785880 | 21.00 | 0.00785880 | 44.4437 | 6884.24 | 0.00 | 11962.60 | 11962.60 | 0.60757782 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.8 | |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX | MULT_CLASS_1_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 38222.097 | 38222.097 | 1.851763 | 0.00033438 | 891.516 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 7.8138 | 7.971069 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 38222.10 | 38222.10 | 1.0000 | 1.95016530 | 1.851763 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.33434946 | 60.00 | 32.22 | 27.78 | 0.000 | 38222.10 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00788305 | 21.00 | 0.00788305 | 44.5786 | 22096.20 | 0.00 | 38397.44 | 38397.44 | 1.95016530 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.2 | |
| CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX | CORRIDOR_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10788.566 | 10788.566 | 0.522643 | 0.00009438 | 251.644 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 2.2055 | 2.249913 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 10788.57 | 10788.57 | 1.0000 | 0.55041594 | 0.522643 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.09437346 | 60.00 | 32.22 | 27.78 | 0.000 | 10788.57 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00797626 | 21.00 | 0.00797626 | 45.0985 | 6236.30 | 0.00 | 10838.06 | 10838.06 | 0.55041594 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.5 | |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11772.672 | 11772.672 | 0.570366 | 0.00010299 | 274.592 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 2.4067 | 2.455145 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11772.67 | 11772.67 | 1.0000 | 0.60067496 | 0.570366 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.10298197 | 60.00 | 32.22 | 27.78 | 0.000 | 11772.67 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00785721 | 21.00 | 0.00785721 | 44.4348 | 6806.03 | 0.00 | 11826.68 | 11826.68 | 0.60067496 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.8 | |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX | MULT_CLASS_2_POD_1_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37498.144 | 37498.144 | 1.816692 | 0.00032805 | 874.630 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 7.6658 | 7.820091 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 37498.14 | 37498.14 | 1.0000 | 1.91323110 | 1.816692 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.32801666 | 60.00 | 32.22 | 27.78 | 0.000 | 37498.14 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00788083 | 21.00 | 0.00788083 | 44.5662 | 21677.72 | 0.00 | 37670.16 | 37670.16 | 1.91323110 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.1 | |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11869.227 | 11869.227 | 0.575043 | 0.00010384 | 276.844 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 2.4264 | 2.475281 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11869.23 | 11869.23 | 1.0000 | 0.60560092 | 0.575043 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.10382658 | 60.00 | 32.22 | 27.78 | 0.000 | 11869.23 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00785835 | 21.00 | 0.00785835 | 44.4411 | 6861.84 | 0.00 | 11923.68 | 11923.68 | 0.60560092 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.8 | |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX | MULT_CLASS_1_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37869.189 | 37869.189 | 1.834667 | 0.00033130 | 883.285 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 7.7417 | 7.897471 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 37869.19 | 37869.19 | 1.0000 | 1.93216086 | 1.834667 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.33126239 | 60.00 | 32.22 | 27.78 | 0.000 | 37869.19 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00788198 | 21.00 | 0.00788198 | 44.5726 | 21892.20 | 0.00 | 38042.91 | 38042.91 | 1.93216086 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.1 | |
| CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX | CORRIDOR_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10775.085 | 10775.085 | 0.521990 | 0.00009427 | 251.330 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 2.2028 | 2.247102 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 10775.08 | 10775.08 | 1.0000 | 0.54972813 | 0.521990 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.09425552 | 60.00 | 32.22 | 27.78 | 0.000 | 10775.08 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00797623 | 21.00 | 0.00797623 | 45.0983 | 6228.51 | 0.00 | 10824.51 | 10824.51 | 0.54972813 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.5 | |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11776.345 | 11776.345 | 0.570544 | 0.00010302 | 274.678 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 2.4075 | 2.455911 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11776.35 | 11776.35 | 1.0000 | 0.60086233 | 0.570544 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.10301409 | 60.00 | 32.22 | 27.78 | 0.000 | 11776.35 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00785726 | 21.00 | 0.00785726 | 44.4350 | 6808.15 | 0.00 | 11830.37 | 11830.37 | 0.60086233 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.8 | |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX | MULT_CLASS_2_POD_2_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37513.275 | 37513.275 | 1.817425 | 0.00032818 | 874.983 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 7.6689 | 7.823247 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 37513.27 | 37513.27 | 1.0000 | 1.91400305 | 1.817425 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.32814902 | 60.00 | 32.22 | 27.78 | 0.000 | 37513.27 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00788088 | 21.00 | 0.00788088 | 44.5665 | 21686.47 | 0.00 | 37685.36 | 37685.36 | 1.91400305 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.1 | |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11873.724 | 11873.724 | 0.575261 | 0.00010388 | 276.949 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 2.4274 | 2.476219 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11873.72 | 11873.72 | 1.0000 | 0.60583036 | 0.575261 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.10386592 | 60.00 | 32.22 | 27.78 | 0.000 | 11873.72 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00785841 | 21.00 | 0.00785841 | 44.4414 | 6864.44 | 0.00 | 11928.19 | 11928.19 | 0.60583036 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.8 | |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX | MULT_CLASS_1_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 37986.137 | 37986.137 | 1.840332 | 0.00033232 | 886.013 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 7.7656 | 7.921860 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 37986.14 | 37986.14 | 1.0000 | 1.93812727 | 1.840332 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.33228540 | 60.00 | 32.22 | 27.78 | 0.000 | 37986.14 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00788234 | 21.00 | 0.00788234 | 44.5746 | 21959.80 | 0.00 | 38160.40 | 38160.40 | 1.93812727 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.1 | |
| CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX | CORRIDOR_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10790.485 | 10790.485 | 0.522736 | 0.00009440 | 251.689 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 2.2059 | 2.250314 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 10790.49 | 10790.49 | 1.0000 | 0.55051383 | 0.522736 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.09439024 | 60.00 | 32.22 | 27.78 | 0.000 | 10790.49 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00797626 | 21.00 | 0.00797626 | 45.0985 | 6237.41 | 0.00 | 10839.99 | 10839.99 | 0.55051383 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.5 | |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11810.211 | 11810.211 | 0.572184 | 0.00010332 | 275.468 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 2.4144 | 2.462973 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11810.21 | 11810.21 | 1.0000 | 0.60259007 | 0.572184 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.10331034 | 60.00 | 32.22 | 27.78 | 0.000 | 11810.21 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00785766 | 21.00 | 0.00785766 | 44.4373 | 6827.73 | 0.00 | 11864.39 | 11864.39 | 0.60259007 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52748.8 | |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX | MULT_CLASS_2_POD_3_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25329.039 | 25329.039 | 1.227127 | 0.00022159 | 590.791 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 5.1781 | 5.282272 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 25329.04 | 25329.04 | 1.0000 | 1.29233623 | 1.227127 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.22156688 | 60.00 | 32.22 | 27.78 | 0.000 | 25329.04 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00788345 | 21.00 | 0.00788345 | 44.5809 | 14642.72 | 0.00 | 25445.23 | 25445.23 | 1.29233623 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.2 | |
| COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX | COMPUTER_CLASS_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12456.904 | 12456.904 | 0.603507 | 0.00010898 | 290.552 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 2.5466 | 2.597839 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 12456.90 | 12456.90 | 1.0000 | 0.63557775 | 0.603507 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.10896731 | 60.00 | 32.22 | 27.78 | 0.000 | 12456.90 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00787821 | 21.00 | 0.00787821 | 44.5516 | 7201.36 | 0.00 | 12514.05 | 12514.05 | 0.63557775 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.1 | |
| MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX | MAIN_CORRIDOR_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 25693.543 | 25693.543 | 1.244707 | 0.00022478 | 599.303 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 5.2526 | 5.358288 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 25693.54 | 25693.54 | 1.0000 | 1.31085075 | 1.244707 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.22475539 | 60.00 | 32.22 | 27.78 | 0.000 | 25693.54 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00797011 | 21.00 | 0.00797011 | 45.0642 | 14852.16 | 0.00 | 25811.41 | 25811.41 | 1.31085075 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.4 | |
| LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | LOBBY_ZN_1_FLR_1 VAV BOX | LOBBY_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15128.470 | 15128.470 | 0.732930 | 0.00013235 | 352.867 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 3.0927 | 3.154983 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 15128.47 | 15128.47 | 1.0000 | 0.77187741 | 0.732930 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.13233695 | 60.00 | 32.22 | 27.78 | 0.000 | 15128.47 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00789392 | 21.00 | 0.00789392 | 44.6393 | 8745.69 | 0.00 | 15197.87 | 15197.87 | 0.77187741 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.3 | |
| MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | MECH_ZN_1_FLR_1 VAV BOX | MECH_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8574.956 | 8574.956 | 0.415399 | 0.00007502 | 200.012 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 1.7530 | 1.788273 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 8574.96 | 8574.96 | 1.0000 | 0.43747318 | 0.415399 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.07500980 | 60.00 | 32.22 | 27.78 | 0.000 | 8574.96 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 45.2310 | 4956.62 | 0.00 | 8614.29 | 8614.29 | 0.43747318 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.8 | |
| BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | BATH_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11781.564 | 11781.564 | 0.570768 | 0.00010307 | 274.803 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 2.4085 | 2.456999 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11781.56 | 11781.56 | 1.0000 | 0.60109862 | 0.570768 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.10305975 | 60.00 | 32.22 | 27.78 | 0.000 | 11781.56 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00792798 | 21.00 | 0.00792798 | 44.8292 | 6810.61 | 0.00 | 11835.61 | 11835.61 | 0.60109862 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.8 | |
| OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | OFFICES_ZN_1_FLR_1 VAV BOX | OFFICES_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 33470.239 | 33470.239 | 1.621535 | 0.00029281 | 780.683 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 6.8424 | 6.980087 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 33470.24 | 33470.24 | 1.0000 | 1.70770268 | 1.621535 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.29278238 | 60.00 | 32.22 | 27.78 | 0.000 | 33470.24 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00789401 | 21.00 | 0.00789401 | 44.6398 | 19348.93 | 0.00 | 33623.78 | 33623.78 | 1.70770268 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.3 | |
| GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | GYM_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 24777.586 | 24777.586 | 1.200360 | 0.00021677 | 577.935 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 5.0653 | 5.167269 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 23:40:00 | Sensible | 24777.59 | 24777.59 | 1.0000 | 1.26414680 | 1.200360 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.21674302 | 60.00 | 32.22 | 27.78 | 0.000 | 24777.59 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00794168 | 21.00 | 0.00794168 | 44.9057 | 14323.13 | 0.00 | 24891.25 | 24891.25 | 1.26414680 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52750.0 | |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Unknown | Unknown | Unknown | LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 29844.873 | 29844.873 | 1.445904 | 0.00026110 | 696.121 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 4.19453741 | 54.44 | 82.22 | 27.78 | 489160.64 | 6.1012 | 6.224032 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 29844.87 | 29844.87 | 1.0000 | 1.52273907 | 1.445904 | 12.89 | 10.44 | 0.00800000 | 33150.5 | 32.11 | 17.27 | 0.00800000 | 52751.6 | 0.26106933 | 60.00 | 32.22 | 27.78 | 0.000 | 29844.87 | -27.60 | 0.00034190 | -27.60 | 0.00000000 | 0.0000 | 21.00 | 0.00788690 | 21.00 | 0.00788690 | 44.6001 | 17253.24 | 0.00 | 29981.78 | 29981.78 | 1.52273907 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 32.11 | 18.73 | 0.00800000 | 52749.2 | |
| VAV_POD_1 COOLING COIL | Coil:Cooling:DX:TwoSpeed | AirLoop | AirLoopHVAC | VAV_POD_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1; MULT_CLASS_1_POD_1_ZN_1_FLR_1; CORRIDOR_POD_1_ZN_1_FLR_1; CORNER_CLASS_2_POD_1_ZN_1_FLR_1; MULT_CLASS_2_POD_1_ZN_1_FLR_1; CORNER_CLASS_1_POD_2_ZN_1_FLR_1; MULT_CLASS_1_POD_2_ZN_1_FLR_1; CORRIDOR_POD_2_ZN_1_FLR_1; CORNER_CLASS_2_POD_2_ZN_1_FLR_1; MULT_CLASS_2_POD_2_ZN_1_FLR_1; CORNER_CLASS_1_POD_3_ZN_1_FLR_1; MULT_CLASS_1_POD_3_ZN_1_FLR_1; CORRIDOR_POD_3_ZN_1_FLR_1; CORNER_CLASS_2_POD_3_ZN_1_FLR_1; MULT_CLASS_2_POD_3_ZN_1_FLR_1; COMPUTER_CLASS_ZN_1_FLR_1; MAIN_CORRIDOR_ZN_1_FLR_1; LOBBY_ZN_1_FLR_1; MECH_ZN_1_FLR_1; BATH_ZN_1_FLR_1; OFFICES_ZN_1_FLR_1; GYM_ZN_1_FLR_1; LIBRARY_MEDIA_CENTER_ZN_1_FLR_1; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | unknown | No | 601222.908 | 481522.847 | 32.887040 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.3563 | 1004.8586 | 1.0531 | VAV_POD_1 FAN | Fan:VariableVolume | 32.887040 | 34.63465352 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 575928.98 | 557273.15 | 0.9579 | 34.63465352 | 32.887040 | 27.05 | 15.04 | 0.00727091 | 45731.8 | 10.88 | 8.59 | 0.00700000 | 28579.1 | -999.0 | -999.00 | -999.00 | -999.00 | 70914.769 | 505014.21 | 33.40 | 0.00630683 | 16.37 | 10.68330000 | 32.4848 | 24.00 | 0.00773477 | 24.00 | 0.00773477 | 36.4669 | 340497.41 | 0.00 | 602961.77 | 450355.66 | 33.26684653 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.42 | 13.22 | 0.00938607 | 37197.4 | |
| VAV_POD_1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | VAV_POD_1 | CORNER_CLASS_1_POD_1_ZN_1_FLR_1; MULT_CLASS_1_POD_1_ZN_1_FLR_1; CORRIDOR_POD_1_ZN_1_FLR_1; CORNER_CLASS_2_POD_1_ZN_1_FLR_1; MULT_CLASS_2_POD_1_ZN_1_FLR_1; CORNER_CLASS_1_POD_2_ZN_1_FLR_1; MULT_CLASS_1_POD_2_ZN_1_FLR_1; CORRIDOR_POD_2_ZN_1_FLR_1; CORNER_CLASS_2_POD_2_ZN_1_FLR_1; MULT_CLASS_2_POD_2_ZN_1_FLR_1; CORNER_CLASS_1_POD_3_ZN_1_FLR_1; MULT_CLASS_1_POD_3_ZN_1_FLR_1; CORRIDOR_POD_3_ZN_1_FLR_1; CORNER_CLASS_2_POD_3_ZN_1_FLR_1; MULT_CLASS_2_POD_3_ZN_1_FLR_1; COMPUTER_CLASS_ZN_1_FLR_1; MAIN_CORRIDOR_ZN_1_FLR_1; LOBBY_ZN_1_FLR_1; MECH_ZN_1_FLR_1; BATH_ZN_1_FLR_1; OFFICES_ZN_1_FLR_1; GYM_ZN_1_FLR_1; LIBRARY_MEDIA_CENTER_ZN_1_FLR_1; | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 422739.695 | 422739.695 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | VAV_POD_1 FAN | Fan:VariableVolume | 32.887040 | 34.63465352 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 01:00:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 422739.69 | 422739.69 | 1.0000 | 10.39039606 | 9.866112 | -27.60 | -27.60 | 0.00034190 | -26896.1 | 12.89 | 10.44 | 0.00800000 | 33150.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 422739.69 | -27.60 | 0.00034190 | -27.60 | 10.68330000 | 108.2828 | 21.00 | 0.00789723 | 21.00 | 0.00789723 | 44.6581 | 221673.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_1:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:6 | KITCHEN_ZN_1_FLR_1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35017.390 | 27316.716 | 1.766920 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8918 | 1004.8586 | 1.0531 | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.766923 | 1.86081748 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 17508.69 | 14314.07 | 1.0000 | 1.24054261 | 1.177947 | 25.10 | 15.50 | 0.00863489 | 47222.6 | 11.34 | 8.79 | 0.00700000 | 29052.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17508.69 | 31.96 | 0.00630459 | 15.89 | 0.25481392 | 21.6320 | 23.95 | 0.00902758 | 23.99 | 0.00902758 | 42.5030 | 18273.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_1:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:6 | KITCHEN_ZN_1_FLR_1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34404.542 | 34404.542 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.766923 | 1.86081748 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 34404.54 | 34404.54 | 1.0000 | 1.86081748 | 1.766923 | 13.71 | 12.47 | 0.00980745 | 38554.6 | 32.11 | 17.27 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34404.54 | -27.60 | 0.00034190 | -27.60 | 0.25481392 | 14.4213 | 20.67 | 0.01140255 | 21.00 | 0.01140255 | 64.1132 | 937.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_2:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:7 | CAFETERIA_ZN_1_FLR_1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 64918.530 | 48899.883 | 3.053390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.3681 | 1004.8586 | 1.0531 | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.053392 | 3.21564892 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | GREAT FALLS INTL ARPT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 32459.26 | 29681.08 | 1.0000 | 2.14376452 | 2.035593 | 28.62 | 16.01 | 0.00781523 | 48723.1 | 11.38 | 8.81 | 0.00700000 | 29087.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32459.26 | 33.40 | 0.00630683 | 16.37 | 1.48818443 | 73.1081 | 23.98 | 0.00928089 | 23.98 | 0.00928089 | 43.6875 | 31224.33 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_2:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:7 | CAFETERIA_ZN_1_FLR_1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 112439.172 | 112439.172 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0531 | PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.053392 | 3.21564892 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | GREAT FALLS INTL ARPT ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 112439.17 | 112439.17 | 1.0000 | 3.21564892 | 3.053392 | -2.69 | -2.69 | 0.00420926 | 7805.9 | 32.11 | 17.27 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 112439.17 | -27.60 | 0.00034190 | -27.60 | 1.48818443 | 48.7387 | 21.00 | 0.00788632 | 21.00 | 0.00788632 | 44.5973 | 12359.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| VAV_POD_1_OA_CONTROLLER | FixedDryBulb | 0.00 | 32.89 | - | |||
| PSZ-AC_1:6_OA_CONTROLLER | FixedDryBulb | 0.25 | 1.77 | - | |||
| PSZ-AC_2:7_OA_CONTROLLER | FixedDryBulb | 1.49 | 3.05 | - |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001880 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000305 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| LOBBY_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000559 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| MECH_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| BATH_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000000 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| OFFICES_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| GYM_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.001524 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1_DCV | 0.000000 | 0.000864 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 1377.33 | 2477.17 | 990.67 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1066.83 | 2443.17 | 747.83 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 1257.50 | 2797.17 | 1162.50 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 1500.50 | 2893.83 | 1356.33 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1210.67 | 2999.83 | 1113.67 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 1377.67 | 2510.00 | 1013.67 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1051.67 | 2494.67 | 774.17 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 1265.50 | 2810.00 | 1172.17 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 1501.00 | 2891.50 | 1356.17 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1212.83 | 2997.50 | 1115.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 1378.67 | 2488.50 | 1002.33 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1063.17 | 2451.67 | 760.50 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 1236.00 | 2723.50 | 1132.17 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 1503.17 | 2846.83 | 1337.50 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 1207.00 | 2945.33 | 1091.83 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 1128.00 | 2381.67 | 796.50 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 1463.00 | 2426.17 | 1238.83 |
| LOBBY_ZN_1_FLR_1 | 1827.83 | 2728.50 | 1579.00 |
| MECH_ZN_1_FLR_1 | 1965.17 | 1750.50 | 732.83 |
| BATH_ZN_1_FLR_1 | 2087.00 | 2289.17 | 1320.00 |
| OFFICES_ZN_1_FLR_1 | 1319.00 | 1874.17 | 888.83 |
| GYM_ZN_1_FLR_1 | 1550.33 | 1923.17 | 731.17 |
| KITCHEN_ZN_1_FLR_1 | 2427.50 | 422.00 | 127.50 |
| CAFETERIA_ZN_1_FLR_1 | 1197.67 | 1676.17 | 557.17 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 1457.00 | 2174.33 | 953.00 |
| Facility | 3154.50 | 3174.00 | 1692.33 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 107.83 | 1.83 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 47.33 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 69.00 | 0.00 | 16.50 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 144.17 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 66.33 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 109.83 | 1.33 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 48.50 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 70.17 | 0.00 | 17.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 144.83 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 66.33 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 108.50 | 1.67 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 48.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 69.00 | 0.00 | 16.17 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 144.33 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 67.33 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 57.17 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 76.67 | 0.00 | 30.83 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 1185.17 | 41.17 | 855.17 | 37.83 |
| MECH_ZN_1_FLR_1 | 0.00 | 2.17 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 57.50 | 0.67 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 86.67 | 5.33 | 2.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 56.83 | 0.67 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 2.83 | 598.67 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 130.33 | 12.33 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 59.50 | 0.00 | 0.17 | 0.00 |
| Facility | 1312.00 | 655.33 | 855.17 | 37.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.065 | 0.037 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.053 | 0.020 | 0.000 | 0.000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.699 | 0.003 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.955 | 0.037 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.951 | 0.020 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.055 | 0.037 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.040 | 0.020 | 0.000 | 0.000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.695 | 0.003 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.952 | 0.037 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.949 | 0.020 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 2.058 | 0.037 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 2.049 | 0.020 | 0.000 | 0.000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.717 | 0.003 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.960 | 0.037 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 45.65 | 84.77 | 1260.00 | 1.956 | 0.020 | 0.000 | 0.000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 38.16 | 43.60 | 648.00 | 2.106 | 0.020 | 0.000 | 0.000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 15.83 | 29.39 | 2184.00 | 0.611 | 0.003 | 0.000 | 0.000 |
| LOBBY_ZN_1_FLR_1 | 9.91 | 18.41 | 684.00 | 1.209 | 2.775 | 0.000 | 0.000 |
| MECH_ZN_1_FLR_1 | 2.19 | 4.07 | 1008.00 | 0.756 | 0.000 | 0.000 | 0.000 |
| BATH_ZN_1_FLR_1 | 5.51 | 10.23 | 760.00 | 0.652 | 0.010 | 0.000 | 0.000 |
| OFFICES_ZN_1_FLR_1 | 14.92 | 23.74 | 1764.00 | 1.127 | 0.017 | 0.000 | 0.000 |
| GYM_ZN_1_FLR_1 | 64.64 | 115.31 | 1428.00 | 1.885 | 0.009 | 0.000 | 0.000 |
| KITCHEN_ZN_1_FLR_1 | 14.54 | 26.99 | 672.00 | 4.518 | 0.009 | 0.000 | 0.000 |
| CAFETERIA_ZN_1_FLR_1 | 209.95 | 339.07 | 1260.00 | 5.211 | 0.022 | 0.000 | 0.000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 23.13 | 42.95 | 1596.00 | 1.335 | 0.018 | 0.000 | 0.000 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.491 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.277 | 0.000 | 0.000 | 0.000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.499 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.224 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.210 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.479 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.249 | 0.000 | 0.000 | 0.000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.497 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.222 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.209 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.489 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 69.12 | 128.36 | 1908.00 | 1.267 | 0.000 | 0.000 | 0.000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 5.56 | 10.33 | 768.00 | 0.509 | 0.000 | 0.000 | 0.000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 14.35 | 26.64 | 396.00 | 1.224 | 0.000 | 0.000 | 0.000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 45.65 | 84.77 | 1260.00 | 1.209 | 0.000 | 0.000 | 0.000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 38.16 | 43.60 | 648.00 | 1.405 | 0.000 | 0.000 | 0.000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 15.83 | 29.39 | 2184.00 | 0.359 | 0.000 | 0.000 | 0.000 |
| LOBBY_ZN_1_FLR_1 | 9.91 | 18.41 | 684.00 | 0.704 | 0.000 | 0.000 | 0.000 |
| MECH_ZN_1_FLR_1 | 2.19 | 4.07 | 1008.00 | 0.431 | 0.000 | 0.000 | 0.000 |
| BATH_ZN_1_FLR_1 | 5.51 | 10.23 | 760.00 | 0.319 | 0.000 | 0.000 | 0.000 |
| OFFICES_ZN_1_FLR_1 | 14.92 | 23.74 | 1764.00 | 0.697 | 0.000 | 0.000 | 0.000 |
| GYM_ZN_1_FLR_1 | 64.64 | 115.31 | 1428.00 | 1.056 | 0.000 | 0.000 | 0.000 |
| KITCHEN_ZN_1_FLR_1 | 14.54 | 26.99 | 672.00 | 0.000 | 0.000 | 0.000 | 0.000 |
| CAFETERIA_ZN_1_FLR_1 | 209.95 | 339.07 | 1260.00 | 4.179 | 0.000 | 0.000 | 0.000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 23.13 | 42.95 | 1596.00 | 0.805 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 5.56 | 10.33 | 768.00 | 192.00 | 0.0000 | 0.059 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 5.56 | 10.33 | 768.00 | 192.00 | 0.0000 | 0.059 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 69.12 | 128.36 | 1908.00 | 477.00 | 0.0000 | 0.897 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 5.56 | 10.33 | 768.00 | 192.00 | 0.0000 | 0.059 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 14.35 | 26.64 | 396.00 | 99.00 | 0.0000 | 0.186 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 45.65 | 84.77 | 1260.00 | 315.00 | 0.0000 | 0.592 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | 38.16 | 43.60 | 648.00 | 162.00 | 0.0000 | 0.304 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | 15.83 | 29.39 | 2184.00 | 546.00 | 0.0000 | 0.166 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | 9.91 | 18.41 | 684.00 | 171.00 | 0.0000 | 0.096 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | 2.19 | 4.07 | 1008.00 | 252.00 | 0.0000 | 0.000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | 5.51 | 10.23 | 760.00 | 190.00 | 0.0000 | 0.000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | 14.92 | 23.74 | 1764.00 | 441.00 | 0.0000 | 0.190 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | 64.64 | 115.31 | 1428.00 | 357.00 | 0.0000 | 0.544 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | 14.54 | 26.99 | 672.00 | 168.00 | 0.4528 | 0.198 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | 209.95 | 339.07 | 1260.00 | 315.00 | 1.4882 | 1.488 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | 23.13 | 42.95 | 1596.00 | 399.00 | 0.0000 | 0.345 |
| Total Facility | 892.82 | 1571.19 | 27484.00 | 6871.00 | 1.9410 | 9.699 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 3027613.98 | 0.00 | 3027613.98 | 310260.46 | 3337874.43 | 5868225.25 | 7021.92 | 68.78 | 1669.31 | 1275.85 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 14507216.50 | 0.00 | 14507216.50 | 822190.22 | 15329406.72 | 28274176.21 | 7178.27 | 72.17 | 1509.56 | 1275.85 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 1987988.43 | 0.00 | 1987988.43 | 46539.07 | 2034527.50 | 1845537.18 | 5153.70 | 2.69 | 3603.62 | 1275.85 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 2890706.65 | 0.00 | 2890706.65 | 310260.46 | 3200967.11 | 5868225.25 | 7251.95 | 71.89 | 1436.16 | 1275.85 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 13902387.73 | 0.00 | 13902387.73 | 822190.22 | 14724577.95 | 28274176.21 | 7292.37 | 61.19 | 1406.44 | 1275.85 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 3014637.80 | 0.00 | 3014637.80 | 310260.46 | 3324898.26 | 5868225.25 | 7036.29 | 73.95 | 1649.76 | 1275.85 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 14426688.02 | 0.00 | 14426688.02 | 822190.22 | 15248878.24 | 28274176.21 | 7202.67 | 67.80 | 1489.53 | 1275.85 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 1976886.09 | 0.00 | 1976886.09 | 46539.07 | 2023425.15 | 1845537.18 | 5154.03 | 3.06 | 3602.91 | 1275.85 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 2886452.79 | 0.00 | 2886452.79 | 310260.46 | 3196713.25 | 5868225.25 | 7270.30 | 53.94 | 1435.76 | 1275.85 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 13886915.09 | 0.00 | 13886915.09 | 822190.22 | 14709105.31 | 28274176.21 | 7306.60 | 47.94 | 1405.46 | 1275.85 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 3017764.28 | 0.00 | 3017764.28 | 310260.46 | 3328024.73 | 5868225.25 | 7045.18 | 55.85 | 1658.97 | 1275.85 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 14478351.99 | 0.00 | 14478351.99 | 822190.22 | 15300542.21 | 28274176.21 | 7192.64 | 64.07 | 1503.29 | 1275.85 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 2032412.65 | 0.00 | 2032412.65 | 46539.07 | 2078951.71 | 1845537.18 | 5153.72 | 2.55 | 3603.72 | 1275.85 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 2896823.15 | 0.00 | 2896823.15 | 310260.46 | 3207083.61 | 5868225.25 | 7240.78 | 67.81 | 1451.41 | 1275.85 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 9195056.70 | 0.00 | 9195056.70 | 542955.80 | 9738012.50 | 18671625.80 | 7309.71 | 44.52 | 1405.76 | 1275.85 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 5029381.39 | 0.00 | 5029381.39 | 279234.41 | 5308615.80 | 9602550.41 | 7133.08 | 62.24 | 1564.68 | 1275.85 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 4856514.39 | 0.00 | 4856514.39 | 139617.21 | 4996131.60 | 5248246.35 | 5193.57 | 2.44 | 3563.99 | 1275.85 |
| LOBBY_ZN_1_FLR_1 | 3060443.32 | 0.00 | 3060443.32 | 9383068.35 | 12443511.67 | 3013410.78 | 5119.43 | 4.03 | 3636.54 | 1275.85 |
| MECH_ZN_1_FLR_1 | 2840012.11 | 0.00 | 2840012.11 | 0.00 | 2840012.11 | 0.00 | 0.00 | 0.00 | 4551.85 | 1275.85 |
| BATH_ZN_1_FLR_1 | 1855073.92 | 0.00 | 1855073.92 | 155130.23 | 2010204.14 | 0.00 | 0.00 | 0.00 | 4551.85 | 1275.85 |
| OFFICES_ZN_1_FLR_1 | 6762587.69 | 0.00 | 6762587.69 | 651546.96 | 7414134.66 | 6005204.96 | 5440.54 | 4.55 | 3314.91 | 1544.80 |
| GYM_ZN_1_FLR_1 | 9814399.38 | 0.00 | 9814399.38 | 263721.39 | 10078120.77 | 17157717.19 | 6811.28 | 68.13 | 1880.60 | 1275.85 |
| KITCHEN_ZN_1_FLR_1 | 12724156.40 | 0.00 | 12724156.40 | 124104.18 | 12848260.58 | 6482703.52 | 4413.64 | 13.32 | 4333.04 | 2265.47 |
| CAFETERIA_ZN_1_FLR_1 | 22034446.02 | 0.00 | 22034446.02 | 558468.83 | 22592914.85 | 46931384.03 | 5465.88 | 2440.20 | 853.92 | 1076.46 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 7678687.70 | 0.00 | 7678687.70 | 620520.92 | 8299208.62 | 10866548.77 | 5231.32 | 3.12 | 3525.56 | 1275.85 |
| Total Facility | 0.18E+09 | 0.00 | 0.18E+09 | 18830499.31 | 0.20E+09 | 0.31E+09 | 7616.32 | 2483.70 | 5330.64 | 3918.24 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.2240 | 0.0000 | 0.2240 | 0.0040 | 0.2281 | 0.1861 | 1776.72 | 66.00 | 1433.28 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 1.0729 | 0.0000 | 1.0729 | 0.0107 | 1.0835 | 0.8966 | 1933.07 | 69.39 | 1273.54 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 0.1472 | 0.0000 | 0.1472 | 0.0006 | 0.1478 | 0.0585 | 0.00 | 0.00 | 3276.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.2124 | 0.0000 | 0.2124 | 0.0040 | 0.2165 | 0.1861 | 2006.78 | 69.08 | 1200.14 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 1.0217 | 0.0000 | 1.0217 | 0.0107 | 1.0323 | 0.8966 | 2047.18 | 58.41 | 1170.41 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.2229 | 0.0000 | 0.2229 | 0.0040 | 0.2270 | 0.1861 | 1791.12 | 71.15 | 1413.73 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 1.0661 | 0.0000 | 1.0661 | 0.0107 | 1.0768 | 0.8966 | 1957.47 | 65.02 | 1253.50 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 0.1463 | 0.0000 | 0.1463 | 0.0006 | 0.1470 | 0.0585 | 0.00 | 0.00 | 3276.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.2121 | 0.0000 | 0.2121 | 0.0040 | 0.2162 | 0.1861 | 2024.96 | 51.28 | 1199.76 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 1.0205 | 0.0000 | 1.0205 | 0.0107 | 1.0312 | 0.8966 | 2061.34 | 45.21 | 1169.45 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.2232 | 0.0000 | 0.2232 | 0.0040 | 0.2273 | 0.1861 | 1799.84 | 53.19 | 1422.96 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 1.0705 | 0.0000 | 1.0705 | 0.0107 | 1.0812 | 0.8966 | 1947.44 | 61.29 | 1267.26 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 0.1509 | 0.0000 | 0.1509 | 0.0006 | 0.1515 | 0.0585 | 0.00 | 0.00 | 3276.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.2130 | 0.0000 | 0.2130 | 0.0040 | 0.2170 | 0.1861 | 1995.59 | 65.03 | 1215.38 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.6761 | 0.0000 | 0.6761 | 0.0070 | 0.6831 | 0.5921 | 2064.32 | 41.93 | 1169.76 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 0.3731 | 0.0000 | 0.3731 | 0.0036 | 0.3767 | 0.3045 | 1887.86 | 59.49 | 1328.65 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 0.3656 | 0.0000 | 0.3656 | 0.0018 | 0.3674 | 0.1664 | 0.00 | 0.00 | 3276.00 |
| LOBBY_ZN_1_FLR_1 | 0.2284 | 0.0000 | 0.2284 | 0.5281 | 0.7565 | 0.0956 | 0.00 | 0.00 | 3276.00 |
| MECH_ZN_1_FLR_1 | 0.2079 | 0.0000 | 0.2079 | 0.0000 | 0.2079 | 0.0000 | 0.00 | 0.00 | 3276.00 |
| BATH_ZN_1_FLR_1 | 0.1361 | 0.0000 | 0.1361 | 0.0020 | 0.1381 | 0.0000 | 0.00 | 0.00 | 3276.00 |
| OFFICES_ZN_1_FLR_1 | 0.5438 | 0.0000 | 0.5438 | 0.0083 | 0.5521 | 0.1904 | 0.00 | 0.00 | 2772.00 |
| GYM_ZN_1_FLR_1 | 0.7355 | 0.0000 | 0.7355 | 0.0034 | 0.7389 | 0.5441 | 1566.29 | 65.42 | 1644.29 |
| KITCHEN_ZN_1_FLR_1 | 0.8252 | 0.0000 | 0.8252 | 0.0016 | 0.8268 | 0.2182 | 105.32 | 1.50 | 3169.18 |
| CAFETERIA_ZN_1_FLR_1 | 1.7948 | 0.0000 | 1.7948 | 0.0074 | 1.8023 | 1.4882 | 0.00 | 1951.34 | 776.66 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.5823 | 0.0000 | 0.5823 | 0.0080 | 0.5904 | 0.3446 | 0.00 | 0.00 | 3276.00 |
| Total Facility | 13.4727 | 0.0000 | 13.4727 | 0.6507 | 14.1233 | 9.7189 | 2147.57 | 2451.78 | 3276.00 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| VAV_POD_1 | 0.16E+09 | 0.00 | 0.16E+09 | 0.25E+09 | 5219.05 | 2.16 | 3538.78 | 1275.85 |
| PSZ-AC_1:6 | 14112407.76 | 0.00 | 14112407.76 | 6482703.52 | 4340.77 | 15.13 | 4404.11 | 2265.47 |
| PSZ-AC_2:7 | 24438478.85 | 0.00 | 24438478.85 | 46931384.03 | 5409.98 | 3.12 | 3346.90 | 1076.29 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| VAV_POD_1 | 11.9971 | 0.0000 | 11.9971 | 8.0125 | 0.00 | 0.00 | 3276.00 |
| PSZ-AC_1:6 | 0.9153 | 0.0000 | 0.9153 | 0.2182 | 99.20 | 2.67 | 3174.14 |
| PSZ-AC_2:7 | 1.9907 | 0.0000 | 1.9907 | 1.4882 | 0.00 | 0.00 | 2728.00 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| VAV_POD_1 | 0.00 | 72.58 | 3104.13 | 572.90 | 0.00 | 0.00 | 802.24 | 0.00 | 0.00 | 0.00 |
| PSZ-AC_1:6 | 0.00 | 558.74 | 3495.09 | 1449.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| PSZ-AC_2:7 | 0.00 | 2433.68 | 963.71 | 406.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| VAV_POD_1 | 0.0000 | 11.8680 | 12.6263 | 0.0000 | 0.0000 | 0.0000 | 10.1403 | 0.0000 | 0.0000 | 0.0000 |
| PSZ-AC_1:6 | 0.0000 | 0.2830 | 1.0607 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| PSZ-AC_2:7 | 0.0000 | 1.6506 | 2.8406 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Surfaces by Class| Total | Outdoors | |
| Wall | 121 | 33 |
| Floor | 25 | 24 |
| Roof | 25 | 25 |
| Internal Mass | 25 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 67 | 67 |
| Door | 25 | 25 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 3 |
| Conditioned Zones | 25 |
| Unconditioned Zones | 0 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1159 |
| Defaulted Fields | 890 |
| Fields with Defaults | 3720 |
| Autosized Fields | 267 |
| Autosizable Fields | 376 |
| Autocalculated Fields | 317 |
| Autocalculatable Fields | 632 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 3135.25 | 36994.66 | 04-JUL-10:30 | 309467.74 | 27-SEP-13:00 |
| Electricity:Building | 2377.40 | 35841.46 | 01-JUL-10:30 | 158543.84 | 02-JAN-11:10 |
| Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| Electricity:SpaceType:GENERAL | 2369.55 | 35741.12 | 30-JUN-23:10 | 156371.25 | 02-JAN-10:10 |
| InteriorLights:Electricity | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 1218.19 | 15672.78 | 01-JAN-00:10 | 79557.27 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 24.39 | 336.28 | 30-JUN-23:10 | 1626.10 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 24.39 | 336.28 | 30-JUN-23:10 | 1626.10 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 191.13 | 2669.12 | 30-JUN-23:10 | 12794.97 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 99.06 | 1274.46 | 01-JAN-00:10 | 6469.32 | 02-JAN-07:10 |
| Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 24.39 | 336.28 | 30-JUN-23:10 | 1626.10 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 14.50 | 186.58 | 01-JAN-00:10 | 947.12 | 02-JAN-07:10 |
| Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 39.67 | 553.97 | 30-JUN-23:10 | 2655.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 20.56 | 264.51 | 01-JAN-00:10 | 1342.69 | 02-JAN-07:10 |
| Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 126.22 | 1762.63 | 30-JUN-23:10 | 8449.51 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 65.42 | 841.62 | 01-JAN-00:10 | 4272.19 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 65.42 | 841.62 | 01-JAN-00:10 | 4272.19 | 02-JAN-07:10 |
| Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 75.34 | 1064.38 | 30-JUN-23:10 | 5061.57 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 33.64 | 432.83 | 01-JAN-00:10 | 2197.13 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 33.64 | 432.83 | 01-JAN-00:10 | 2197.13 | 02-JAN-07:10 |
| Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 69.34 | 956.30 | 30-JUN-23:10 | 4624.21 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 41.24 | 530.59 | 01-JAN-00:10 | 2693.36 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 41.24 | 530.59 | 01-JAN-00:10 | 2693.36 | 02-JAN-07:10 |
| Electricity:Zone:LOBBY_ZN_1_FLR_1 | 41.78 | 557.57 | 30-JUN-23:10 | 2758.25 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 32.98 | 424.25 | 01-JAN-00:10 | 2153.53 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 32.98 | 424.25 | 01-JAN-00:10 | 2153.53 | 02-JAN-07:10 |
| Electricity:Zone:MECH_ZN_1_FLR_1 | 88.50 | 1212.59 | 30-JUN-23:10 | 5889.78 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:MECH_ZN_1_FLR_1 | 56.07 | 721.39 | 01-JAN-00:10 | 3661.88 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:MECH_ZN_1_FLR_1 | 56.07 | 721.39 | 01-JAN-00:10 | 3661.88 | 02-JAN-07:10 |
| Electricity:Zone:BATH_ZN_1_FLR_1 | 35.15 | 474.48 | 30-JUN-23:10 | 2328.47 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:BATH_ZN_1_FLR_1 | 25.37 | 326.34 | 01-JAN-00:10 | 1656.56 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:BATH_ZN_1_FLR_1 | 25.37 | 326.34 | 01-JAN-00:10 | 1656.56 | 02-JAN-07:10 |
| Electricity:Zone:OFFICES_ZN_1_FLR_1 | 133.25 | 1854.16 | 30-JUN-23:10 | 8910.14 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 71.96 | 925.78 | 01-JAN-00:10 | 4699.41 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 71.96 | 925.78 | 01-JAN-00:10 | 4699.41 | 02-JAN-07:10 |
| Electricity:Zone:GYM_ZN_1_FLR_1 | 88.64 | 1192.76 | 30-JUN-23:10 | 5866.56 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:GYM_ZN_1_FLR_1 | 65.67 | 844.83 | 01-JAN-00:10 | 4288.47 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:GYM_ZN_1_FLR_1 | 65.67 | 844.83 | 01-JAN-00:10 | 4288.47 | 02-JAN-07:10 |
| Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 211.64 | 5400.64 | 01-JAN-11:30 | 13840.49 | 02-JAN-11:10 |
| InteriorLights:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 29.90 | 384.74 | 01-JAN-00:10 | 1953.00 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 29.90 | 384.74 | 01-JAN-00:10 | 1953.00 | 02-JAN-07:10 |
| Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 71.99 | 1340.83 | 01-JAN-00:10 | 4745.87 | 02-JAN-10:10 |
| InteriorLights:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 42.05 | 541.04 | 01-JAN-00:10 | 2746.41 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 42.05 | 541.04 | 01-JAN-00:10 | 2746.41 | 02-JAN-07:10 |
| Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 168.75 | 2346.88 | 30-JUN-23:10 | 11282.50 | 02-JAN-08:10 |
| InteriorLights:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 91.74 | 1180.27 | 01-JAN-00:10 | 5991.24 | 02-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 91.74 | 1180.27 | 01-JAN-00:10 | 5991.24 | 02-JAN-07:10 |
| InteriorEquipment:Electricity | 1151.36 | 20068.34 | 30-JUN-23:10 | 76813.98 | 02-JAN-10:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 1151.36 | 20068.34 | 30-JUN-23:10 | 76813.98 | 02-JAN-10:10 |
| MiscPlug:InteriorEquipment:Electricity | 947.54 | 14352.99 | 30-JUN-23:10 | 65099.62 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 947.54 | 14352.99 | 30-JUN-23:10 | 65099.62 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 92.07 | 1394.66 | 30-JUN-23:10 | 6325.65 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 9.88 | 149.70 | 30-JUN-23:10 | 678.98 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 19.11 | 289.46 | 30-JUN-23:10 | 1312.87 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 60.80 | 921.00 | 30-JUN-23:10 | 4177.31 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 60.80 | 921.00 | 30-JUN-23:10 | 4177.31 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 41.69 | 631.55 | 30-JUN-23:10 | 2864.44 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 41.69 | 631.55 | 30-JUN-23:10 | 2864.44 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 28.10 | 425.71 | 30-JUN-23:10 | 1930.85 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 28.10 | 425.71 | 30-JUN-23:10 | 1930.85 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 8.80 | 133.33 | 30-JUN-23:10 | 604.72 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:LOBBY_ZN_1_FLR_1 | 8.80 | 133.33 | 30-JUN-23:10 | 604.72 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MECH_ZN_1_FLR_1 | 32.43 | 491.20 | 30-JUN-23:10 | 2227.90 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MECH_ZN_1_FLR_1 | 32.43 | 491.20 | 30-JUN-23:10 | 2227.90 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:BATH_ZN_1_FLR_1 | 9.78 | 148.14 | 30-JUN-23:10 | 671.91 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:BATH_ZN_1_FLR_1 | 9.78 | 148.14 | 30-JUN-23:10 | 671.91 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 61.29 | 928.37 | 30-JUN-23:10 | 4210.73 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:OFFICES_ZN_1_FLR_1 | 61.29 | 928.37 | 30-JUN-23:10 | 4210.73 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GYM_ZN_1_FLR_1 | 22.97 | 347.93 | 30-JUN-23:10 | 1578.10 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GYM_ZN_1_FLR_1 | 22.97 | 347.93 | 30-JUN-23:10 | 1578.10 | 02-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 173.88 | 4915.56 | 01-JAN-00:10 | 9714.90 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity | 149.71 | 3999.34 | 01-JAN-00:10 | 9998.36 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 119.77 | 3199.56 | 01-JAN-00:10 | 7998.90 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 149.71 | 3999.34 | 01-JAN-00:10 | 9998.36 | 02-JAN-10:10 |
| ReachInFreezer:InteriorEquipment:Electricity | 31.09 | 986.00 | 01-JAN-00:10 | 986.00 | 01-JAN-00:10 |
| ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 31.09 | 986.00 | 01-JAN-00:10 | 986.00 | 01-JAN-00:10 |
| ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 31.09 | 986.00 | 01-JAN-00:10 | 986.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 29.94 | 799.79 | 01-JAN-00:10 | 1999.46 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:Electricity:Zone:CAFETERIA_ZN_1_FLR_1 | 29.94 | 799.79 | 01-JAN-00:10 | 1999.46 | 02-JAN-10:10 |
| InteriorEquipment:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 77.02 | 1166.60 | 30-JUN-23:10 | 5291.26 | 02-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 77.02 | 1166.60 | 30-JUN-23:10 | 5291.26 | 02-JAN-08:10 |
| Refrigeration:Electricity | 44.53 | 725.27 | 31-DEC-23:30 | 2873.93 | 07-SEP-10:20 |
| Refrigeration:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 7.85 | 100.34 | 01-JAN-11:30 | 2172.58 | 02-JAN-11:10 |
| General:Refrigeration:Electricity | 7.85 | 100.34 | 01-JAN-11:30 | 2172.58 | 02-JAN-11:10 |
| General:Refrigeration:Electricity:Zone:KITCHEN_ZN_1_FLR_1 | 7.85 | 100.34 | 01-JAN-11:30 | 2172.58 | 02-JAN-11:10 |
| Electricity:Plant | 39.15 | 625.10 | 12-AUG-22:30 | 2811.23 | 09-JAN-11:50 |
| LowTempRefrigeration:Refrigeration:Electricity | 14.93 | 0.00 | 01-JAN-11:10 | 1488.83 | 18-JUN-10:50 |
| MedTempRefrigeration:Refrigeration:Electricity | 21.74 | 405.48 | 09-JAN-07:00 | 734.88 | 01-JAN-09:30 |
| Electricity:HVAC | 626.18 | 321.20 | 01-JUL-08:10 | 163913.75 | 17-JUL-16:00 |
| ExteriorEquipment:Electricity | 17.61 | 321.20 | 01-JUL-00:50 | 1336.02 | 02-JAN-10:10 |
| Transformer:ExteriorEquipment:Electricity | 17.61 | 321.20 | 01-JUL-00:50 | 1336.02 | 02-JAN-10:10 |
| ElectricityPurchased:Facility | 3135.25 | 36994.66 | 04-JUL-10:30 | 309467.74 | 27-SEP-13:00 |
| ElectricityPurchased:Plant | 3135.25 | 36994.66 | 04-JUL-10:30 | 309467.74 | 27-SEP-13:00 |
| Cogeneration:ElectricityPurchased | 3135.25 | 36994.66 | 04-JUL-10:30 | 309467.74 | 27-SEP-13:00 |
| General:Cogeneration:ElectricityPurchased | 3135.25 | 36994.66 | 04-JUL-10:30 | 309467.74 | 27-SEP-13:00 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 3135.25 | 36994.66 | 04-JUL-10:30 | 309467.74 | 27-SEP-13:00 |
| ElectricityNet:Plant | 3135.25 | 36994.66 | 04-JUL-10:30 | 309467.74 | 27-SEP-13:00 |
| Cogeneration:ElectricityNet | 3135.25 | 36994.66 | 04-JUL-10:30 | 309467.74 | 27-SEP-13:00 |
| General:Cogeneration:ElectricityNet | 3135.25 | 36994.66 | 04-JUL-10:30 | 309467.74 | 27-SEP-13:00 |
| Fans:Electricity | 394.92 | 0.00 | 01-JAN-00:10 | 56420.32 | 26-SEP-14:30 |
| General:Fans:Electricity | 394.92 | 0.00 | 01-JAN-00:10 | 56420.32 | 26-SEP-14:30 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 213.65 | 0.00 | 01-JAN-00:10 | 131373.90 | 17-JUL-16:00 |
| General:Cooling:Electricity | 213.65 | 0.00 | 01-JAN-00:10 | 131373.90 | 17-JUL-16:00 |
| ExteriorLights:Electricity | 92.52 | 0.00 | 01-JAN-08:20 | 5897.73 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 92.52 | 0.00 | 01-JAN-08:20 | 5897.73 | 01-JAN-00:10 |
| Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Pumps:Electricity | 2.48 | 0.00 | 01-JAN-00:10 | 1264.26 | 09-JAN-07:10 |
| General:Pumps:Electricity | 2.48 | 0.00 | 01-JAN-00:10 | 1264.26 | 09-JAN-07:10 |
| WIRED_LTG_ELECTRICITY | 14.50 | 0.00 | 01-JAN-00:10 | 946.73 | 02-JAN-07:20 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 2220.23 | 4866.92 | 04-JUL-10:50 | 1084341.02 | 09-JAN-08:10 |
| NaturalGas:Building | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| NaturalGas:SpaceType:GENERAL | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| InteriorEquipment:NaturalGas | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| InteriorEquipment:NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| InteriorEquipment:NaturalGas:SpaceType:GENERAL | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:NaturalGas | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN_ZN_1_FLR_1 | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 361.03 | 4808.50 | 01-JAN-00:10 | 48084.96 | 02-JAN-10:10 |
| NaturalGas:HVAC | 980.51 | 0.00 | 01-JAN-00:10 | 593334.24 | 10-JAN-21:00 |
| Heating:NaturalGas | 1692.98 | 0.00 | 01-JAN-00:10 | 1035709.31 | 09-JAN-08:10 |
| General:Heating:NaturalGas | 980.51 | 0.00 | 01-JAN-00:10 | 593334.24 | 10-JAN-21:00 |
| NaturalGas:Plant | 878.69 | 58.42 | 04-JUL-10:50 | 527747.26 | 09-JAN-06:10 |
| WaterSystems:NaturalGas | 166.21 | 58.42 | 04-JUL-10:50 | 32121.16 | 13-FEB-13:40 |
| Water Heater:WaterSystems:NaturalGas | 166.21 | 58.42 | 04-JUL-10:50 | 32121.16 | 13-FEB-13:40 |
| Boiler:Heating:NaturalGas | 712.47 | 0.00 | 01-JAN-00:10 | 526999.98 | 09-JAN-06:10 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Water:Plant | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| WaterSystems:Water | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Water Heater:WaterSystems:Water | 268.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| MainsWater:Facility | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| MainsWater:Plant | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| WaterSystems:MainsWater | 718.47 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| Water Heater:WaterSystems:MainsWater | 268.99 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-13:10 |
| WaterUse:WaterSystems:Water | 449.48 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-13:10 |
| WaterUse:WaterSystems:MainsWater | 449.48 | 0.00 | 01-JAN-00:10 | 0.00 | 05-JAN-13:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 4764.57 | 3842.60 | 08-AUG-22:30 | 1458649.98 | 09-JAN-08:10 |
| EnergyTransfer:Building | 2021.04 | 1921.30 | 08-AUG-22:30 | 419213.27 | 09-JAN-06:10 |
| EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 243.71 | 1109.04 | 09-JAN-06:40 | 33919.84 | 09-JAN-06:10 |
| Refrigeration:EnergyTransfer | 185.37 | 1818.15 | 09-JAN-07:00 | 10745.76 | 01-JAN-11:50 |
| Refrigeration:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 92.69 | 909.08 | 09-JAN-07:00 | 5372.88 | 01-JAN-11:50 |
| General:Refrigeration:EnergyTransfer | 92.69 | 909.08 | 09-JAN-07:00 | 5372.88 | 01-JAN-11:50 |
| General:Refrigeration:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 92.69 | 909.08 | 09-JAN-07:00 | 5372.88 | 01-JAN-11:50 |
| EnergyTransfer:Plant | 680.01 | 1180.65 | 09-JAN-06:30 | 396506.09 | 09-JAN-06:10 |
| LowTempRefrigeration:Refrigeration:EnergyTransfer | 17.95 | 0.00 | 01-JAN-11:10 | 2686.44 | 01-JAN-11:40 |
| MedTempRefrigeration:Refrigeration:EnergyTransfer | 74.74 | 387.22 | 09-JAN-07:00 | 2686.44 | 01-JAN-09:30 |
| EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 32.95 | 0.00 | 01-JAN-00:10 | 8229.55 | 09-JAN-06:10 |
| Heating:EnergyTransfer | 309.44 | 0.00 | 01-JAN-00:10 | 379512.15 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 6.46 | 0.00 | 01-JAN-00:10 | 8229.55 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer | 309.44 | 0.00 | 01-JAN-00:10 | 379512.15 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 6.46 | 0.00 | 01-JAN-00:10 | 8229.55 | 09-JAN-06:10 |
| Cooling:EnergyTransfer | 1618.92 | 0.00 | 01-JAN-00:10 | 290853.06 | 25-SEP-14:00 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 26.49 | 0.00 | 01-JAN-00:10 | 6481.51 | 25-SEP-14:30 |
| General:Cooling:EnergyTransfer | 1618.92 | 0.00 | 01-JAN-00:10 | 290853.06 | 25-SEP-14:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 26.49 | 0.00 | 01-JAN-00:10 | 6481.51 | 25-SEP-14:30 |
| EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 150.47 | 0.00 | 01-JAN-00:10 | 28960.79 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 12.06 | 0.00 | 01-JAN-00:10 | 28960.79 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 12.06 | 0.00 | 01-JAN-00:10 | 28960.79 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 138.41 | 0.00 | 01-JAN-00:10 | 28301.32 | 25-SEP-14:30 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 138.41 | 0.00 | 01-JAN-00:10 | 28301.32 | 25-SEP-14:30 |
| EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 25.93 | 0.00 | 01-JAN-00:10 | 7601.95 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 9.61 | 0.00 | 01-JAN-00:10 | 7601.95 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 9.61 | 0.00 | 01-JAN-00:10 | 7601.95 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 16.32 | 0.00 | 01-JAN-00:10 | 4207.59 | 25-SEP-14:50 |
| General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_1_ZN_1_FLR_1 | 16.32 | 0.00 | 01-JAN-00:10 | 4207.59 | 25-SEP-14:50 |
| EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 29.81 | 0.00 | 01-JAN-00:10 | 8024.07 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 8.84 | 0.00 | 01-JAN-00:10 | 8024.07 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 8.84 | 0.00 | 01-JAN-00:10 | 8024.07 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 20.97 | 0.00 | 01-JAN-00:10 | 4553.70 | 19-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 20.97 | 0.00 | 01-JAN-00:10 | 4553.70 | 19-MAY-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 128.53 | 0.00 | 01-JAN-00:10 | 29231.50 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 17.83 | 0.00 | 01-JAN-00:10 | 29231.50 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 17.83 | 0.00 | 01-JAN-00:10 | 29231.50 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 110.70 | 0.00 | 01-JAN-00:10 | 19251.27 | 06-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 110.70 | 0.00 | 01-JAN-00:10 | 19251.27 | 06-JUN-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 32.68 | 0.00 | 01-JAN-00:10 | 8208.56 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 6.63 | 0.00 | 01-JAN-00:10 | 8208.56 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 6.63 | 0.00 | 01-JAN-00:10 | 8208.56 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 26.05 | 0.00 | 01-JAN-00:10 | 6416.34 | 25-SEP-14:30 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 26.05 | 0.00 | 01-JAN-00:10 | 6416.34 | 25-SEP-14:30 |
| EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 148.13 | 0.00 | 01-JAN-00:10 | 28814.99 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 12.14 | 0.00 | 01-JAN-00:10 | 28814.99 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 12.14 | 0.00 | 01-JAN-00:10 | 28814.99 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 135.99 | 0.00 | 01-JAN-00:10 | 27776.66 | 25-SEP-14:30 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 135.99 | 0.00 | 01-JAN-00:10 | 27776.66 | 25-SEP-14:30 |
| EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 25.91 | 0.00 | 01-JAN-00:10 | 7585.52 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 9.81 | 0.00 | 01-JAN-00:10 | 7585.52 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 9.81 | 0.00 | 01-JAN-00:10 | 7585.52 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 16.10 | 0.00 | 01-JAN-00:10 | 4175.99 | 30-JUN-16:00 |
| General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_2_ZN_1_FLR_1 | 16.10 | 0.00 | 01-JAN-00:10 | 4175.99 | 30-JUN-16:00 |
| EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 29.81 | 0.00 | 01-JAN-00:10 | 8027.41 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 8.86 | 0.00 | 01-JAN-00:10 | 8027.41 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 8.86 | 0.00 | 01-JAN-00:10 | 8027.41 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 20.95 | 0.00 | 01-JAN-00:10 | 4559.79 | 19-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 20.95 | 0.00 | 01-JAN-00:10 | 4559.79 | 19-MAY-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 128.48 | 0.00 | 01-JAN-00:10 | 29234.38 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 17.88 | 0.00 | 01-JAN-00:10 | 29234.38 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 17.88 | 0.00 | 01-JAN-00:10 | 29234.38 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 110.60 | 0.00 | 01-JAN-00:10 | 19281.38 | 06-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 110.60 | 0.00 | 01-JAN-00:10 | 19281.38 | 06-JUN-15:00 |
| EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 32.83 | 0.00 | 01-JAN-00:10 | 8209.47 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 6.55 | 0.00 | 01-JAN-00:10 | 8209.47 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 6.55 | 0.00 | 01-JAN-00:10 | 8209.47 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 26.27 | 0.00 | 01-JAN-00:10 | 6461.70 | 25-SEP-14:30 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 26.27 | 0.00 | 01-JAN-00:10 | 6461.70 | 25-SEP-14:30 |
| EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 149.70 | 0.00 | 01-JAN-00:10 | 28882.36 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 11.98 | 0.00 | 01-JAN-00:10 | 28882.36 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 11.98 | 0.00 | 01-JAN-00:10 | 28882.36 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 137.72 | 0.00 | 01-JAN-00:10 | 28155.30 | 25-SEP-14:30 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 137.72 | 0.00 | 01-JAN-00:10 | 28155.30 | 25-SEP-14:30 |
| EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 26.63 | 0.00 | 01-JAN-00:10 | 7627.87 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 9.48 | 0.00 | 01-JAN-00:10 | 7627.87 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 9.48 | 0.00 | 01-JAN-00:10 | 7627.87 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 17.15 | 0.00 | 01-JAN-00:10 | 4404.89 | 25-SEP-14:50 |
| General:Cooling:EnergyTransfer:Zone:CORRIDOR_POD_3_ZN_1_FLR_1 | 17.15 | 0.00 | 01-JAN-00:10 | 4404.89 | 25-SEP-14:50 |
| EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 30.18 | 0.00 | 01-JAN-00:10 | 8067.15 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 8.82 | 0.00 | 01-JAN-00:10 | 8067.15 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 8.82 | 0.00 | 01-JAN-00:10 | 8067.15 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 21.36 | 0.00 | 01-JAN-00:10 | 4663.78 | 19-MAY-15:00 |
| General:Cooling:EnergyTransfer:Zone:CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 21.36 | 0.00 | 01-JAN-00:10 | 4663.78 | 19-MAY-15:00 |
| EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 86.69 | 0.00 | 01-JAN-00:10 | 19516.46 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 12.19 | 0.00 | 01-JAN-00:10 | 19516.46 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 12.19 | 0.00 | 01-JAN-00:10 | 19516.46 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 74.50 | 0.00 | 01-JAN-00:10 | 13305.18 | 06-JUN-15:00 |
| General:Cooling:EnergyTransfer:Zone:MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 74.50 | 0.00 | 01-JAN-00:10 | 13305.18 | 06-JUN-15:00 |
| EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 54.74 | 0.00 | 01-JAN-00:10 | 9898.35 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 4.12 | 0.00 | 01-JAN-00:10 | 9898.35 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 4.12 | 0.00 | 01-JAN-00:10 | 9898.35 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 50.62 | 0.00 | 01-JAN-00:10 | 8604.48 | 23-JUN-13:40 |
| General:Cooling:EnergyTransfer:Zone:COMPUTER_CLASS_ZN_1_FLR_1 | 50.62 | 0.00 | 01-JAN-00:10 | 8604.48 | 23-JUN-13:40 |
| EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 68.40 | 0.00 | 01-JAN-00:10 | 17026.84 | 09-JAN-06:40 |
| Heating:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 25.62 | 0.00 | 01-JAN-00:10 | 17026.84 | 09-JAN-06:40 |
| General:Heating:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 25.62 | 0.00 | 01-JAN-00:10 | 17026.84 | 09-JAN-06:40 |
| Cooling:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 42.78 | 0.00 | 01-JAN-00:10 | 12872.61 | 17-JUL-15:20 |
| General:Cooling:EnergyTransfer:Zone:MAIN_CORRIDOR_ZN_1_FLR_1 | 42.78 | 0.00 | 01-JAN-00:10 | 12872.61 | 17-JUL-15:20 |
| EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 77.81 | 0.00 | 01-JAN-00:10 | 21208.80 | 29-DEC-08:00 |
| Heating:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 60.69 | 0.00 | 01-JAN-00:10 | 21208.80 | 29-DEC-08:00 |
| General:Heating:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 60.69 | 0.00 | 01-JAN-00:10 | 21208.80 | 29-DEC-08:00 |
| Cooling:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 17.13 | 0.00 | 01-JAN-00:10 | 15099.99 | 17-JUL-14:50 |
| General:Cooling:EnergyTransfer:Zone:LOBBY_ZN_1_FLR_1 | 17.13 | 0.00 | 01-JAN-00:10 | 15099.99 | 17-JUL-14:50 |
| EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 37.80 | 0.00 | 01-JAN-00:10 | 5900.31 | 23-JUN-13:40 |
| Heating:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 0.20 | 0.00 | 01-JAN-00:10 | 2579.05 | 09-JAN-06:40 |
| General:Heating:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 0.20 | 0.00 | 01-JAN-00:10 | 2579.05 | 09-JAN-06:40 |
| Cooling:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 37.60 | 0.00 | 01-JAN-00:10 | 5900.31 | 23-JUN-13:40 |
| General:Cooling:EnergyTransfer:Zone:MECH_ZN_1_FLR_1 | 37.60 | 0.00 | 01-JAN-00:10 | 5900.31 | 23-JUN-13:40 |
| EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 21.29 | 0.00 | 01-JAN-00:10 | 5190.24 | 09-JAN-06:40 |
| Heating:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 3.40 | 0.00 | 01-JAN-00:10 | 5190.24 | 09-JAN-06:40 |
| General:Heating:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 3.40 | 0.00 | 01-JAN-00:10 | 5190.24 | 09-JAN-06:40 |
| Cooling:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 17.89 | 0.00 | 01-JAN-00:10 | 3239.64 | 16-JUL-17:10 |
| General:Cooling:EnergyTransfer:Zone:BATH_ZN_1_FLR_1 | 17.89 | 0.00 | 01-JAN-00:10 | 3239.64 | 16-JUL-17:10 |
| EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 86.84 | 0.00 | 01-JAN-00:10 | 23095.70 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 19.38 | 0.00 | 01-JAN-00:10 | 23095.70 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 19.38 | 0.00 | 01-JAN-00:10 | 23095.70 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 67.46 | 0.00 | 01-JAN-00:10 | 19906.67 | 05-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:OFFICES_ZN_1_FLR_1 | 67.46 | 0.00 | 01-JAN-00:10 | 19906.67 | 05-SEP-14:10 |
| EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 111.33 | 0.00 | 01-JAN-00:10 | 20459.11 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 8.15 | 0.00 | 01-JAN-00:10 | 20459.11 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 8.15 | 0.00 | 01-JAN-00:10 | 20459.11 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 103.18 | 0.00 | 01-JAN-00:10 | 19578.56 | 30-JUN-15:40 |
| General:Cooling:EnergyTransfer:Zone:GYM_ZN_1_FLR_1 | 103.18 | 0.00 | 01-JAN-00:10 | 19578.56 | 30-JUN-15:40 |
| Heating:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 0.15 | 0.00 | 01-JAN-00:10 | 23844.07 | 09-JAN-07:10 |
| General:Heating:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 0.15 | 0.00 | 01-JAN-00:10 | 23844.07 | 09-JAN-07:10 |
| Cooling:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 150.88 | 0.00 | 01-JAN-00:10 | 31133.38 | 09-JAN-06:10 |
| General:Cooling:EnergyTransfer:Zone:KITCHEN_ZN_1_FLR_1 | 150.88 | 0.00 | 01-JAN-00:10 | 31133.38 | 09-JAN-06:10 |
| EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 168.73 | 0.00 | 01-JAN-00:10 | 43484.97 | 11-JAN-06:30 |
| Heating:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 14.32 | 0.00 | 01-JAN-00:10 | 35525.26 | 28-DEC-06:20 |
| General:Heating:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 14.32 | 0.00 | 01-JAN-00:10 | 35525.26 | 28-DEC-06:20 |
| Cooling:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 154.41 | 0.00 | 01-JAN-00:10 | 29254.48 | 23-JUN-12:00 |
| General:Cooling:EnergyTransfer:Zone:CAFETERIA_ZN_1_FLR_1 | 154.41 | 0.00 | 01-JAN-00:10 | 29254.48 | 23-JUN-12:00 |
| EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 91.65 | 0.00 | 01-JAN-00:10 | 22282.67 | 09-JAN-06:10 |
| Heating:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 14.28 | 0.00 | 01-JAN-00:10 | 22282.67 | 09-JAN-06:10 |
| General:Heating:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 14.28 | 0.00 | 01-JAN-00:10 | 22282.67 | 09-JAN-06:10 |
| Cooling:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 77.36 | 0.00 | 01-JAN-00:10 | 16467.16 | 23-JUN-13:30 |
| General:Cooling:EnergyTransfer:Zone:LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 77.36 | 0.00 | 01-JAN-00:10 | 16467.16 | 23-JUN-13:30 |
| PlantLoopHeatingDemand:Facility | 591.92 | 0.00 | 01-JAN-00:10 | 371253.72 | 09-JAN-07:10 |
| PlantLoopHeatingDemand:Plant | 95.48 | 0.00 | 01-JAN-00:10 | 20337.41 | 17-FEB-13:10 |
| WaterSystems:PlantLoopHeatingDemand | 95.48 | 0.00 | 01-JAN-00:10 | 20337.41 | 17-FEB-13:10 |
| General:WaterSystems:PlantLoopHeatingDemand | 95.48 | 0.00 | 01-JAN-00:10 | 20337.41 | 17-FEB-13:10 |
| EnergyTransfer:HVAC | 2063.52 | 0.00 | 01-JAN-00:10 | 804656.79 | 09-JAN-08:10 |
| HeatingCoils:EnergyTransfer | 1273.50 | 0.00 | 01-JAN-00:10 | 804656.79 | 09-JAN-08:10 |
| PlantLoopHeatingDemand:HVAC | 496.44 | 0.00 | 01-JAN-00:10 | 371253.72 | 09-JAN-07:10 |
| HeatingCoils:PlantLoopHeatingDemand | 496.44 | 0.00 | 01-JAN-00:10 | 371253.72 | 09-JAN-07:10 |
| CoolingCoils:EnergyTransfer | 790.02 | 0.00 | 01-JAN-00:10 | 475761.65 | 07-SEP-14:50 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:EnergyTransfer | 95.48 | 0.00 | 01-JAN-00:10 | 20337.41 | 17-FEB-13:10 |
| WaterUse:WaterSystems:EnergyTransfer | 95.48 | 0.00 | 01-JAN-00:10 | 20337.41 | 17-FEB-13:10 |
| Boilers:EnergyTransfer | 491.84 | 0.00 | 01-JAN-00:10 | 393719.63 | 09-JAN-06:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 6.460 | -26.491 | 0.000 | 0.000 | 12.546 | 20.559 | 19.109 | 18.140 | 0.000 | 0.053 | 0.000 | 0.000 | -14.658 | 0.000 | -4.564 | -31.155 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 12.057 | -138.410 | 0.000 | 0.000 | 59.424 | 99.059 | 92.071 | 58.102 | 0.000 | 0.159 | 0.000 | 0.000 | -40.491 | 0.000 | -12.806 | -129.164 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 9.609 | -16.320 | 0.000 | 0.000 | 4.964 | 14.502 | 9.883 | 2.169 | 0.000 | 0.009 | 0.000 | 0.000 | -2.506 | 0.000 | -0.707 | -21.603 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 8.839 | -20.971 | 0.000 | 0.000 | 12.865 | 20.559 | 19.109 | 8.301 | 0.000 | 0.068 | 0.000 | 0.000 | -14.984 | 0.000 | -4.321 | -29.465 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 0.000 | 0.000 | 17.826 | -110.702 | 0.000 | 0.000 | 61.262 | 99.059 | 92.071 | 8.223 | 0.000 | 0.208 | 0.000 | 0.000 | -42.871 | 0.000 | -12.034 | -113.043 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 6.631 | -26.051 | 0.000 | 0.000 | 12.568 | 20.559 | 19.109 | 17.481 | 0.000 | 0.054 | 0.000 | 0.000 | -14.658 | 0.000 | -4.550 | -31.144 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 12.138 | -135.994 | 0.000 | 0.000 | 59.554 | 99.059 | 92.071 | 52.741 | 0.000 | 0.163 | 0.000 | 0.000 | -40.724 | 0.000 | -12.756 | -126.253 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 9.806 | -16.103 | 0.000 | 0.000 | 4.967 | 14.502 | 9.883 | 2.170 | 0.000 | 0.009 | 0.000 | 0.000 | -2.502 | 0.000 | -0.705 | -22.027 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 8.857 | -20.954 | 0.000 | 0.000 | 12.863 | 20.559 | 19.109 | 8.340 | 0.000 | 0.068 | 0.000 | 0.000 | -14.979 | 0.000 | -4.321 | -29.544 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 0.000 | 0.000 | 17.883 | -110.601 | 0.000 | 0.000 | 61.257 | 99.059 | 92.071 | 8.396 | 0.000 | 0.208 | 0.000 | 0.000 | -42.829 | 0.000 | -12.032 | -113.412 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 6.551 | -26.275 | 0.000 | 0.000 | 12.555 | 20.559 | 19.109 | 17.539 | 0.000 | 0.054 | 0.000 | 0.000 | -14.677 | 0.000 | -4.562 | -30.853 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 11.983 | -137.721 | 0.000 | 0.000 | 59.460 | 99.059 | 92.071 | 53.083 | 0.000 | 0.160 | 0.000 | 0.000 | -40.776 | 0.000 | -12.807 | -124.512 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 9.478 | -17.154 | 0.000 | 0.000 | 4.949 | 14.502 | 9.883 | 2.160 | 0.000 | 0.008 | 0.000 | 0.000 | -2.521 | 0.000 | -0.712 | -20.595 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 8.820 | -21.359 | 0.000 | 0.000 | 12.843 | 20.559 | 19.109 | 8.785 | 0.000 | 0.066 | 0.000 | 0.000 | -15.000 | 0.000 | -4.338 | -29.485 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 0.000 | 0.000 | 12.185 | -74.502 | 0.000 | 0.000 | 40.358 | 65.416 | 60.801 | 7.483 | 0.000 | 0.132 | 0.000 | 0.000 | -28.215 | 0.000 | -7.979 | -75.680 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 0.000 | 0.000 | 4.119 | -50.619 | 0.000 | 0.000 | 33.817 | 33.643 | 41.692 | 3.621 | 0.000 | 0.057 | 0.000 | 0.000 | -15.132 | 0.000 | -4.301 | -46.897 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 0.000 | 0.000 | 25.619 | -42.785 | 0.000 | 0.000 | 14.035 | 41.241 | 28.104 | 4.643 | 0.000 | 0.022 | 0.000 | 0.000 | -7.635 | 0.000 | -2.148 | -61.096 |
| LOBBY_ZN_1_FLR_1 | 0.000 | 0.000 | 60.687 | -17.126 | 0.000 | 0.000 | 9.797 | 32.975 | 8.802 | 21.391 | 0.000 | 3.021 | 0.000 | 0.000 | -13.263 | 0.000 | -88.267 | -18.017 |
| MECH_ZN_1_FLR_1 | 0.000 | 0.000 | 0.202 | -37.600 | 0.000 | 0.000 | 1.786 | 56.071 | 32.427 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -52.887 |
| BATH_ZN_1_FLR_1 | 0.000 | 0.000 | 3.399 | -17.886 | 0.000 | 0.000 | 5.107 | 25.366 | 9.780 | 5.384 | 0.000 | 0.019 | 0.000 | 0.000 | -8.136 | 0.000 | -2.309 | -20.725 |
| OFFICES_ZN_1_FLR_1 | 0.000 | 0.000 | 19.384 | -67.456 | 0.000 | 0.000 | 10.938 | 71.958 | 61.288 | 37.364 | 0.000 | 0.090 | 0.000 | 0.000 | -31.600 | 0.000 | -10.151 | -91.816 |
| GYM_ZN_1_FLR_1 | 0.000 | 0.000 | 8.152 | -103.182 | 0.000 | 0.000 | 54.758 | 65.666 | 22.969 | 34.563 | 0.000 | 0.042 | 0.000 | 0.000 | -30.877 | 0.000 | -4.319 | -47.771 |
| KITCHEN_ZN_1_FLR_1 | 0.000 | 0.000 | 0.148 | -150.863 | 0.000 | 0.000 | 11.520 | 29.905 | 138.079 | 5.664 | 0.000 | 0.016 | 0.000 | 0.000 | -7.940 | 0.000 | -2.527 | -23.999 |
| CAFETERIA_ZN_1_FLR_1 | 0.000 | 0.000 | 14.322 | -154.417 | 0.000 | 0.000 | 152.215 | 42.053 | 29.938 | 13.852 | 0.000 | 0.074 | 0.000 | 0.000 | -29.084 | 0.000 | -8.767 | -60.186 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 0.000 | 0.000 | 14.285 | -77.361 | 0.000 | 0.000 | 19.852 | 91.739 | 77.015 | 17.364 | 0.000 | 0.093 | 0.000 | 0.000 | -32.009 | 0.000 | -9.671 | -101.307 |
| Total Facility | 0.000 | 0.000 | 309.441 | -1618.901 | 0.000 | 0.000 | 746.260 | 1218.192 | 1115.552 | 416.960 | 0.000 | 4.854 | 0.000 | 0.000 | -508.070 | 0.000 | -231.654 | -1452.635 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 02-SEP-15:22 | 0.00 | 0.00 | 0.00 | -11102.43 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 3934.90 | 0.00 | 115.10 | 6382.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 25-SEP-14:15 | 0.00 | 0.00 | 0.00 | -28301.05 | 0.00 | 0.00 | 8480.08 | 6469.32 | 6325.65 | 10818.13 | 0.00 | 18.26 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3810.39 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 25-SEP-14:50 | 0.00 | 0.00 | 0.00 | -4207.27 | 0.00 | 0.00 | 682.67 | 947.12 | 678.98 | 528.33 | 0.00 | 1.04 | 1369.13 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | -4552.84 | 0.00 | 0.00 | 1760.22 | 1342.69 | 1312.87 | 2578.16 | 0.00 | 32.31 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2473.41 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 06-JUN-15:00 | 0.00 | 0.00 | 0.00 | -19253.20 | 0.00 | 0.00 | 8480.21 | 6469.32 | 6325.65 | 2281.44 | 0.00 | 5.68 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4309.11 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 02-SEP-15:22 | 0.00 | 0.00 | 0.00 | -10980.07 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 3878.69 | 0.00 | 115.92 | 6315.71 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 25-SEP-14:30 | 0.00 | 0.00 | 0.00 | -27775.58 | 0.00 | 0.00 | 8480.32 | 6469.32 | 6325.65 | 10148.85 | 0.00 | 18.34 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3666.89 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 30-JUN-16:00 | 0.00 | 0.00 | 0.00 | -4175.66 | 0.00 | 0.00 | 107.79 | 947.12 | 678.98 | 829.51 | 0.00 | 2.27 | 1610.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | -4558.93 | 0.00 | 0.00 | 1760.22 | 1342.69 | 1312.87 | 2583.14 | 0.00 | 32.31 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2472.29 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 06-JUN-15:00 | 0.00 | 0.00 | 0.00 | -19283.30 | 0.00 | 0.00 | 8480.21 | 6469.32 | 6325.65 | 2319.49 | 0.00 | 5.68 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4317.06 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 02-SEP-15:22 | 0.00 | 0.00 | 0.00 | -11023.03 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 3880.70 | 0.00 | 115.24 | 6357.34 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 25-SEP-14:30 | 0.00 | 0.00 | 0.00 | -28154.20 | 0.00 | 0.00 | 8480.32 | 6469.32 | 6325.65 | 10159.82 | 0.00 | 18.34 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -3299.24 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 25-SEP-14:50 | 0.00 | 0.00 | 0.00 | -4404.55 | 0.00 | 0.00 | 682.67 | 947.12 | 678.98 | 527.98 | 0.00 | 1.04 | 1566.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 19-MAY-15:00 | 0.00 | 0.00 | 0.00 | -4662.91 | 0.00 | 0.00 | 1760.22 | 1342.69 | 1312.87 | 2645.38 | 0.00 | 32.31 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2430.56 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 06-JUN-15:00 | 0.00 | 0.00 | 0.00 | -13306.41 | 0.00 | 0.00 | 5600.13 | 4272.19 | 4177.31 | 1957.70 | 0.00 | 3.75 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2704.68 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 23-JUN-13:40 | 0.00 | 0.00 | 0.00 | -8603.20 | 0.00 | 0.00 | 2880.29 | 2197.13 | 2864.44 | 1115.97 | 0.00 | 12.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -467.45 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 05-SEP-07:02 | 0.00 | 0.00 | 0.00 | -16410.45 | 0.00 | 0.00 | 295.72 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 11543.88 | 0.00 | -46.74 | 0.00 | -6.62 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 17-JUL-14:50 | 0.00 | 0.00 | 0.00 | -15100.96 | 0.00 | 0.00 | 91.76 | 1196.41 | 318.27 | 2365.53 | 0.00 | 16795.97 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5666.99 |
| MECH_ZN_1_FLR_1 | 24-JUN-10:41 | 0.00 | 0.00 | 0.00 | -14169.13 | 0.00 | 0.00 | 0.00 | 721.39 | 687.68 | 0.00 | 0.00 | 0.00 | 12760.06 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 02-JUL-18:50 | 0.00 | 0.00 | 0.00 | -8107.64 | 0.00 | 0.00 | 0.00 | 326.34 | 148.14 | 1240.68 | 0.00 | 0.00 | 6402.29 | 0.00 | -0.00 | 0.00 | -9.82 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 02-SEP-15:22 | 0.00 | 0.00 | 0.00 | -28482.57 | 0.00 | 0.00 | 0.00 | 925.78 | 1299.72 | 4052.37 | 0.00 | 243.91 | 21960.79 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 17-JUL-05:01 | 0.00 | 0.00 | 0.00 | -28855.05 | 0.00 | 0.00 | 0.00 | 844.83 | 347.93 | 362.53 | 0.00 | 0.00 | 27348.08 | 0.00 | -0.00 | 0.00 | -48.32 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | -89441.96 | 0.00 | 0.00 | 0.00 | 384.74 | 2721.46 | 0.00 | 0.00 | 0.00 | 87017.21 | 0.00 | -628.03 | 0.00 | -53.42 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 26-JUN-05:01 | 0.00 | 0.00 | 0.00 | -71340.57 | 0.00 | 0.00 | 0.00 | 541.04 | 799.79 | 344.03 | 0.00 | 0.00 | 69880.45 | 0.00 | -0.00 | 0.00 | -224.74 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 05-SEP-07:02 | 0.00 | 0.00 | 0.00 | -24801.66 | 0.00 | 0.00 | 421.27 | 5991.24 | 5291.26 | 157.23 | 0.00 | 0.00 | 12970.49 | 0.00 | -0.00 | 0.00 | -29.83 | 0.00 |
| Total Facility | 07-AUG-05:01 | 0.00 | 0.00 | 0.00 | -304984.02 | 0.00 | 0.00 | 0.00 | 15672.78 | 17874.24 | 0.00 | 0.00 | 0.00 | 287443.15 | 0.00 | -13613.15 | 0.00 | -2393.00 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 9838.45 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1383.75 | 0.00 | -406.23 | -8718.23 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 35501.19 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3765.51 | 0.00 | -1107.51 | -33855.16 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 8126.47 | 0.00 | 0.00 | 0.00 | 0.00 | 186.58 | 209.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -223.10 | 0.00 | -63.39 | -8236.14 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 9248.57 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1343.24 | 0.00 | -404.62 | -8170.46 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 33325.25 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3558.65 | 0.00 | -1102.17 | -31891.41 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 9782.39 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1372.14 | 0.00 | -406.25 | -8673.75 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 35109.07 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3693.83 | 0.00 | -1107.88 | -33534.35 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 8107.13 | 0.00 | 0.00 | 0.00 | 0.00 | 186.58 | 209.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -223.10 | 0.00 | -63.39 | -8216.81 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 9253.34 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1344.03 | 0.00 | -404.60 | -8174.45 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 33306.72 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3562.83 | 0.00 | -1102.13 | -31868.74 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 9788.63 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1373.05 | 0.00 | -406.26 | -8679.08 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 35250.68 | 0.00 | 0.00 | 0.00 | 0.00 | 1274.46 | 1952.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3696.67 | 0.00 | -1107.68 | -33673.31 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 8156.53 | 0.00 | 0.00 | 0.00 | 0.00 | 186.58 | 209.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -223.10 | 0.00 | -63.39 | -8266.20 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 9308.83 | 0.00 | 0.00 | 0.00 | 0.00 | 264.51 | 405.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1352.45 | 0.00 | -404.58 | -8221.55 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 22216.81 | 0.00 | 0.00 | 0.00 | 0.00 | 841.62 | 1289.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2399.19 | 0.00 | -727.02 | -21221.61 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 11393.31 | 0.00 | 0.00 | 0.00 | 0.00 | 432.83 | 884.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1241.44 | 0.00 | -375.84 | -11093.04 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 17890.68 | 0.00 | 0.00 | 0.00 | 0.00 | 530.59 | 595.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -645.75 | 0.00 | -191.24 | -18180.27 |
| LOBBY_ZN_1_FLR_1 | 11-JAN-07:10 | 0.00 | 0.00 | 22255.20 | 0.00 | 0.00 | 0.00 | 0.00 | 2153.53 | 186.66 | 0.00 | 0.00 | 0.00 | 29738.23 | 0.00 | -1673.84 | 0.00 | -52659.77 | 0.00 |
| MECH_ZN_1_FLR_1 | 09-JAN-06:31 | 0.00 | 0.00 | 8950.10 | 0.00 | 0.00 | 0.00 | 0.00 | 721.39 | 687.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10359.17 |
| BATH_ZN_1_FLR_1 | 09-JAN-06:31 | 0.00 | 0.00 | 8604.20 | 0.00 | 0.00 | 0.00 | 0.00 | 326.34 | 207.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -867.59 | 0.00 | -203.90 | -8066.45 |
| OFFICES_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 25509.37 | 0.00 | 0.00 | 0.00 | 0.00 | 925.78 | 1299.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2948.13 | 0.00 | -874.97 | -23911.78 |
| GYM_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 23145.90 | 0.00 | 0.00 | 0.00 | 0.00 | 844.83 | 487.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2717.25 | 0.00 | -361.61 | -21398.98 |
| KITCHEN_ZN_1_FLR_1 | 30-JAN-07:01 | 0.00 | 0.00 | 33890.44 | 0.00 | 0.00 | 0.00 | 0.00 | 1953.00 | 2721.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -520.53 | 0.00 | -69.67 | -37974.71 |
| CAFETERIA_ZN_1_FLR_1 | 30-JAN-07:01 | 0.00 | 0.00 | 114978.33 | 0.00 | 0.00 | 0.00 | 0.00 | 2746.41 | 799.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2475.57 | 0.00 | -370.52 | -115678.44 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 06-MAR-06:11 | 0.00 | 0.00 | 24997.62 | 0.00 | 0.00 | 0.00 | 0.00 | 1180.27 | 1633.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2749.74 | 0.00 | -834.50 | -24226.91 |
| Total Facility | 30-JAN-07:01 | 0.00 | 0.00 | 543228.77 | 0.00 | 0.00 | 0.00 | 0.00 | 79557.27 | 23615.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -43615.50 | 0.00 | -100947.26 | -501838.71 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| VAV_POD_1 | 33.1029 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 32.8870 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| PSZ-AC_1:6 | 1.7669 | 0.0000 | 26.9930 | 1.0000 | Calculated from schedules | 0.4528 | 1.7669 | 0.2563 | 1.0000 | Not calculated | 0.4528 | 0.2563 | ||
| PSZ-AC_2:7 | 3.0534 | 0.0000 | 339.0743 | 1.0000 | Calculated from schedules | 1.4882 | 3.0534 | 0.4874 | 1.0000 | Not calculated | 1.4882 | 0.4874 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| VAV_POD_1 | 16.7269 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 13.7866 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| PSZ-AC_1:6 | 1.7669 | 0.0000 | 26.9930 | 1.0000 | Calculated from schedules | 0.4528 | 1.7669 | 1.0000 | 1.0000 | Not calculated | 0.4528 | 0.2563 | ||
| PSZ-AC_2:7 | 3.0534 | 0.0000 | 339.0743 | 1.0000 | Calculated from schedules | 1.4882 | 3.0534 | 1.0000 | 1.0000 | Not calculated | 1.4882 | 0.4874 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.3340 | 0.000305 | 192.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.3340 | 0.000305 | 192.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 128.3638 | 0.001880 | 477.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.3340 | 0.000305 | 192.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 26.6416 | 0.001880 | 99.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 84.7686 | 0.001880 | 315.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 43.5953 | 0.001880 | 162.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 29.3880 | 0.000305 | 546.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 18.4080 | 0.000559 | 171.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 4.0690 | 0.000000 | 252.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 10.2270 | 0.000000 | 190.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 23.7365 | 0.000432 | 441.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 115.3101 | 0.001524 | 357.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | 0.009440 | 26.9930 | 0.001179 | 168.00 | 0.4528 | 1.0000 | 0.4528 | 1.000 | 0.4528 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | 0.000000 | 339.0743 | 0.004724 | 315.00 | 1.4882 | 1.0000 | 1.4882 | 1.000 | 1.4882 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | 0.000000 | 42.9540 | 0.000864 | 399.00 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| VAV_POD_1 | 0.00 | 0.001254 | 6388.0000 | 0.0000 | 0.0000 | 0.0000 | |
| PSZ-AC_1:6 | 0.009440 | 26.99 | 0.001179 | 168.0000 | 0.4528 | 0.4528 | 0.4528 |
| PSZ-AC_2:7 | 0.000000 | 339.07 | 0.004724 | 315.0000 | 1.4882 | 1.4882 | 1.4882 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7399 | 0.7399 | 0.2893 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0977 | 3.0977 | 1.3940 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6214 | 0.6214 | 0.1864 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6652 | 0.6652 | 0.2894 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6402 | 2.6402 | 1.3940 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7344 | 0.7344 | 0.2894 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0621 | 3.0621 | 1.3932 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6193 | 0.6193 | 0.1858 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6656 | 0.6656 | 0.2889 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6418 | 2.6418 | 1.3922 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7351 | 0.7351 | 0.2889 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.0751 | 3.0751 | 1.3930 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6255 | 0.6255 | 0.1876 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6710 | 0.6710 | 0.2892 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7776 | 1.7776 | 0.9190 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9814 | 0.9814 | 0.4730 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3463 | 1.3463 | 0.4039 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7871 | 0.7871 | 0.2361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9355 | 0.9355 | 0.2806 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6259 | 0.6259 | 0.1878 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.9071 | 1.9071 | 0.5721 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.1259 | 2.1259 | 0.8461 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7669 | 1.7669 | 1.7669 | No | 0.4528 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.0534 | 3.0534 | 3.0534 | No | 1.4882 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.0219 | 2.0219 | 0.6066 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| VAV_POD_1 | 33.1029 | 32.8870 | 33.1029 | 13.7866 | 0.0000 | 1.0000 |
| PSZ-AC_1:6 | 1.7669 | 1.7669 | 1.7669 | 1.7669 | 0.4528 | 1.0000 |
| PSZ-AC_2:7 | 3.0534 | 3.0534 | 3.0534 | 3.0534 | 1.4882 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3700 | 0.3700 | 0.2893 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5489 | 1.5489 | 1.3940 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3107 | 0.3107 | 0.1864 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3326 | 0.3326 | 0.2894 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3940 | 1.3940 | 1.3940 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3672 | 0.3672 | 0.2894 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5310 | 1.5310 | 1.3932 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3096 | 0.3096 | 0.1858 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3328 | 0.3328 | 0.2889 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3922 | 1.3922 | 1.3922 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3675 | 0.3675 | 0.2889 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5375 | 1.5375 | 1.3930 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3127 | 0.3127 | 0.1876 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3355 | 0.3355 | 0.2892 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9190 | 0.9190 | 0.9190 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| COMPUTER_CLASS_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4907 | 0.4907 | 0.4730 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6732 | 0.6732 | 0.4039 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LOBBY_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3935 | 0.3935 | 0.2361 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| MECH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4677 | 0.4677 | 0.2806 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| BATH_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3130 | 0.3130 | 0.1878 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| OFFICES_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9536 | 0.9536 | 0.5721 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| GYM_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0629 | 1.0629 | 0.8461 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| KITCHEN_ZN_1_FLR_1 | PSZ-AC_1:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7669 | 1.7669 | 1.7669 | No | 0.4528 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| CAFETERIA_ZN_1_FLR_1 | PSZ-AC_2:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.0534 | 3.0534 | 3.0534 | No | 1.4882 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | VAV_POD_1 | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0110 | 1.0110 | 0.6066 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| VAV_POD_1 | 16.7269 | 13.7866 | 13.7866 | 13.7866 | 0.0000 | 1.0000 |
| PSZ-AC_1:6 | 1.7669 | 1.7669 | 1.7669 | 1.7669 | 0.4528 | 1.0000 |
| PSZ-AC_2:7 | 3.0534 | 3.0534 | 3.0534 | 3.0534 | 1.4882 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** Great Falls Intl Arpt MT USA TMY3 WMO#=727750 |
| Total gross floor area [m2] | 6871.00 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 192.00 | 192.00 | 0.00 | 62.83 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 192.00 | 192.00 | 0.00 | 62.83 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 477.00 | 477.00 | 0.00 | 62.83 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 192.00 | 192.00 | 0.00 | 62.83 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 99.00 | 99.00 | 0.00 | 62.83 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 315.00 | 315.00 | 0.00 | 62.83 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 162.00 | 162.00 | 0.00 | 62.83 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 546.00 | 546.00 | 0.00 | 62.83 |
| LOBBY_ZN_1_FLR_1 | 171.00 | 171.00 | 0.00 | 62.83 |
| MECH_ZN_1_FLR_1 | 252.00 | 252.00 | 0.00 | 62.83 |
| BATH_ZN_1_FLR_1 | 190.00 | 190.00 | 0.00 | 62.83 |
| OFFICES_ZN_1_FLR_1 | 441.00 | 441.00 | 0.00 | 53.16 |
| GYM_ZN_1_FLR_1 | 357.00 | 357.00 | 0.00 | 62.83 |
| KITCHEN_ZN_1_FLR_1 | 168.00 | 168.00 | 0.00 | 62.83 |
| CAFETERIA_ZN_1_FLR_1 | 315.00 | 315.00 | 0.00 | 52.32 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 399.00 | 399.00 | 0.00 | 62.83 |
| Totals | 6871.00 | 6871.00 | 0.00 |
| Data | |
| Number of hours heating loads not met | 855.17 |
| Number of hours cooling loads not met | 37.83 |
| Number of hours not met | 893.00 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 980.51 | 593334.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heating -- Boiler | 0.00 | 0.00 | 712.47 | 526999.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 213.65 | 131373.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 1218.19 | 79557.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 92.52 | 5897.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 947.54 | 65099.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- Cooking | 149.71 | 9998.36 | 361.03 | 48084.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ReachInFreezer | 31.09 | 986.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ReachInRefrigerator | 23.02 | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Transformer | 17.61 | 1336.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 394.92 | 56420.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- General | 2.48 | 1264.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 0.00 | 0.00 | 166.21 | 32121.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- General | 7.85 | 2172.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- LowTempRefrigeration | 14.93 | 1488.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- MedTempRefrigeration | 21.74 | 734.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 1195.88 | 3135.25 |
| Natural Gas | 361.03 | 2220.23 |
| Additional | 0.00 | 0.00 |
| Total | 1556.91 | 5355.48 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 177.29 |
| Space Heating | 0.00 |
| Space Cooling | 31.09 |
| Fans (All) | 57.48 |
| Service Water Heating | 0.00 |
| Receptacle Equipment | 167.57 |
| Miscellaneous (All) | 456.30 |
| Subtotal | 456.30 |
| Natural Gas [MJ/m2] | |
| Space Heating | 246.40 |
| Service Water Heating | 24.19 |
| Miscellaneous (All) | 323.13 |
| Subtotal | 323.13 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 22.75 |
| Space Heating | 31.61 |
| Space Cooling | 3.99 |
| Fans (All) | 7.37 |
| Service Water Heating | 3.10 |
| Receptacle Equipment | 28.24 |
| Miscellaneous | 2.93 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| LTG_SCH_GYM | 3903. | 8760. |
| LTG_SCH_CLASSROOM | 3903. | 8760. |
| LTG_SCH_LIBRARY | 3903. | 8760. |
| LTG_SCH_BATH | 3903. | 8760. |
| LTG_SCH_KITCHEN | 3903. | 8760. |
| LTG_SCH_OFFICE | 3903. | 8760. |
| LTG_SCH_LOBBY | 3903. | 8760. |
| LTG_SCH_MECHANICAL | 3903. | 8760. |
| LTG_SCH_COMPUTER_ROOM | 3903. | 8760. |
| LTG_SCH_CAFETERIA | 3903. | 8760. |
| LTG_SCH_CORRIDOR | 3903. | 8760. |
| BLDG_EQUIP_SCH | 3617. | 8760. |
| WALKIN_OCC_LGHT_SCH_2 | 2473. | 8760. |
| KITCHEN_ELEC_EQUIP_SCH | 1045. | 8760. |
| KITCHEN_GAS_EQUIP_SCH | 425. | 8760. |
| BLDG_OCC_SCH | 1755. | 3380. |
| BLDG_OCC_SCH_EXTEND | 2948. | 3380. |
| BLDG_OCC_SCH_OFFICES | 2197. | 3380. |
| BLDG_OCC_SCH_OFFICES_W_SB | 1743. | 2860. |
| OFFICES BINARY OCCUPANCY | 3380. | 3380. |
| BLDG_OCC_SCH_GYM | 1828. | 3380. |
| BLDG_OCC_SCH_CAFETERIA | 1687. | 2815. |
| INFIL_SCH | 6205. | 8760. |
| INFIL_SCH_PNNL | 6030. | 8760. |
| INFIL_DOOR_OPENING_SCH | 827. | 2860. |
| BLDG_SWH_SCH | 1227. | 3120. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| EXTERIOR_LGT_189_1 | 5940. | 8760. |
| WORK_EFF_SCH | 0. | 0. |
| KITCHEN_EXHAUST_SCH | 2860. | 2860. |
| MINOA_SCHED | 8760. | 8760. |
| BATH_ZN_1_FLR_1 SHW_DEFAULT LATENT FRACT SCHED | 438. | 8760. |
| BATH_ZN_1_FLR_1 SHW_DEFAULT SENSIBLE FRACT SCHED | 1752. | 8760. |
| KITCHEN_ZN_1_FLR_1 SHW_DEFAULT LATENT FRACT SCHED | 438. | 8760. |
| KITCHEN_ZN_1_FLR_1 SHW_DEFAULT SENSIBLE FRACT SCHED | 1752. | 8760. |
| KITCHEN_ZN_1_FLR_1_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
| EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 3380. | 3380. |
| EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6570. | 8760. |
| KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 2594. | 2860. |
| OFFICES_ZN_1_FLR_1_MDP_SCH | 2472. | 8240. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_SCH_YES_OPTIMUM | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
| CLGSETP_SCH_YES_OPTIMUM | CORNER_CLASS_1_POD_1_ZN_1_FLR_1 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
| HTGSETP_SCH_SETBACK | MECH_ZN_1_FLR_1 DUAL SP CONTROL | January | 15.60 | 365 | 15.60 | 365 |
| CLGSETP_SCH_SETUP | MECH_ZN_1_FLR_1 DUAL SP CONTROL | July | 26.70 | 365 | 26.70 | 365 |
| HTGSETP_SCH_YES_OPTIMUM_W_SB | OFFICES_ZN_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
| CLGSETP_SCH_YES_OPTIMUM_W_SB | OFFICES_ZN_1_FLR_1 DUAL SP CONTROL | July | 24.56 | 63 | 26.70 | 365 |
| HTGSETP_SCH_NO_OPTIMUM | GYM_ZN_1_FLR_1 DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
| CLGSETP_SCH_NO_OPTIMUM | GYM_ZN_1_FLR_1 DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 8752.50 | 7.50 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 8697.50 | 62.50 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 8758.50 | 1.50 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 8758.00 | 2.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 7066.67 | 1681.33 | 12.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 7066.67 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 1681.33 | 12.00 | 0.00 | 0.00 |
| Average | 8688.80 | 70.72 | 0.48 | 0.00 | 0.00 |
| Sum | 217220.00 | 1768.00 | 12.00 | 0.00 | 0.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 141584.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 122876.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 47696.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 29098.00 | 14.00 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 4512.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 15307.67 | 0.33 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 38444.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 202800.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 44688.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 552560.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 70792.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 4512.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 552560.00 | 14.00 | 0.00 | 0.00 | 0.00 |
| Average | 106081.51 | 0.57 | 0.00 | 0.00 | 0.00 |
| Sum | 2652037.67 | 14.33 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 8686.67 | 73.33 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 8743.33 | 16.67 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 6384.67 | 2320.33 | 55.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 8727.67 | 32.33 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 6384.67 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 2320.33 | 55.00 | 0.00 | 0.00 |
| Average | 8659.65 | 98.15 | 2.20 | 0.00 | 0.00 |
| Sum | 216491.33 | 2453.67 | 55.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| CORNER_CLASS_1_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_1_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_1_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_1_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_2_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_2_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_2_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_1_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_1_POD_3_ZN_1_FLR_1 | 215652.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDOR_POD_3_ZN_1_FLR_1 | 15308.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORNER_CLASS_2_POD_3_ZN_1_FLR_1 | 42916.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MULT_CLASS_2_POD_3_ZN_1_FLR_1 | 141584.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| COMPUTER_CLASS_ZN_1_FLR_1 | 122876.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MAIN_CORRIDOR_ZN_1_FLR_1 | 47696.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LOBBY_ZN_1_FLR_1 | 29107.33 | 4.67 | 0.00 | 0.00 | 0.00 |
| MECH_ZN_1_FLR_1 | 4511.00 | 1.00 | 0.00 | 0.00 | 0.00 |
| BATH_ZN_1_FLR_1 | 15287.00 | 21.00 | 0.00 | 0.00 | 0.00 |
| OFFICES_ZN_1_FLR_1 | 38444.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GYM_ZN_1_FLR_1 | 202800.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| KITCHEN_ZN_1_FLR_1 | 44358.17 | 329.83 | 0.00 | 0.00 | 0.00 |
| CAFETERIA_ZN_1_FLR_1 | 552198.67 | 361.33 | 0.00 | 0.00 | 0.00 |
| LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 | 70792.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 4511.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 552198.67 | 361.33 | 0.00 | 0.00 | 0.00 |
| Average | 106053.37 | 28.71 | 0.00 | 0.00 | 0.00 |
| Sum | 2651334.17 | 717.83 | 0.00 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:30:47
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 6B
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -8.80 |
| February | -2.17 |
| March | 0.301 |
| April | 6.668 |
| May | 10.099 |
| June | 16.456 |
| July | 20.571 |
| August | 19.174 |
| September | 14.689 |
| October | 8.635 |
| November | 2.839 |
| December | -4.07 |
| Annual Sum or Average | 7.074 |
| Minimum of Months | -8.80 |
| Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -8.80 |
| February | -2.17 |
| March | 0.301 |
| April | 6.668 |
| May | 10.099 |
| June | 16.456 |
| July | 20.571 |
| August | 19.174 |
| September | 14.689 |
| October | 8.635 |
| November | 2.839 |
| December | -4.07 |
| Annual Sum or Average | 7.074 |
| Minimum of Months | -8.80 |
| Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -8.80 |
| February | -2.17 |
| March | 0.301 |
| April | 6.668 |
| May | 10.099 |
| June | 16.456 |
| July | 20.571 |
| August | 19.174 |
| September | 14.689 |
| October | 8.635 |
| November | 2.839 |
| December | -4.07 |
| Annual Sum or Average | 7.074 |
| Minimum of Months | -8.80 |
| Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -8.80 |
| February | -2.17 |
| March | 0.301 |
| April | 6.668 |
| May | 10.099 |
| June | 16.456 |
| July | 20.571 |
| August | 19.174 |
| September | 14.689 |
| October | 8.635 |
| November | 2.839 |
| December | -4.07 |
| Annual Sum or Average | 7.074 |
| Minimum of Months | -8.80 |
| Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME SCHOOLPRIMARY
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -8.80 |
| February | -2.17 |
| March | 0.301 |
| April | 6.668 |
| May | 10.099 |
| June | 16.456 |
| July | 20.571 |
| August | 19.174 |
| September | 14.689 |
| October | 8.635 |
| November | 2.839 |
| December | -4.07 |
| Annual Sum or Average | 7.074 |
| Minimum of Months | -8.80 |
| Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MT_GREATFALLS
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -8.80 |
| February | -2.17 |
| March | 0.301 |
| April | 6.668 |
| May | 10.099 |
| June | 16.456 |
| July | 20.571 |
| August | 19.174 |
| September | 14.689 |
| October | 8.635 |
| November | 2.839 |
| December | -4.07 |
| Annual Sum or Average | 7.074 |
| Minimum of Months | -8.80 |
| Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -8.80 |
| February | -2.17 |
| March | 0.301 |
| April | 6.668 |
| May | 10.099 |
| June | 16.456 |
| July | 20.571 |
| August | 19.174 |
| September | 14.689 |
| October | 8.635 |
| November | 2.839 |
| December | -4.07 |
| Annual Sum or Average | 7.074 |
| Minimum of Months | -8.80 |
| Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -8.80 |
| February | -2.17 |
| March | 0.301 |
| April | 6.668 |
| May | 10.099 |
| June | 16.456 |
| July | 20.571 |
| August | 19.174 |
| September | 14.689 |
| October | 8.635 |
| November | 2.839 |
| December | -4.07 |
| Annual Sum or Average | 7.074 |
| Minimum of Months | -8.80 |
| Maximum of Months | 20.571 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -8.80 |
| February | -2.17 |
| March | 0.301 |
| April | 6.668 |
| May | 10.099 |
| June | 16.456 |
| July | 20.571 |
| August | 19.174 |
| September | 14.689 |
| October | 8.635 |
| November | 2.839 |
| December | -4.07 |
| Annual Sum or Average | 7.074 |
| Minimum of Months | -8.80 |
| Maximum of Months | 20.571 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.487917E+09 | 2233.81 | 13-JAN-15:50 | 9.08 | 4.76 | 0.632796E+09 | 1139.84 | 13-JAN-15:00 | 8.90 | 4.67 |
| February | 0.901399E+09 | 3462.24 | 28-FEB-15:01 | 10.68 | 4.79 | 0.597792E+09 | 1277.23 | 28-FEB-15:20 | 10.77 | 4.80 |
| March | 0.148567E+10 | 3457.68 | 01-MAR-15:01 | 8.48 | 3.51 | 0.743464E+09 | 1277.84 | 01-MAR-15:30 | 8.85 | 3.64 |
| April | 0.175290E+10 | 4232.27 | 25-APR-15:00 | 17.00 | 7.46 | 0.680728E+09 | 1277.22 | 13-APR-14:20 | 17.00 | 7.46 |
| May | 0.261620E+10 | 5608.81 | 19-MAY-15:00 | 28.30 | 14.88 | 0.790435E+09 | 1277.23 | 15-MAY-14:20 | 28.30 | 14.88 |
| June | 0.387954E+10 | 5104.10 | 06-JUN-15:00 | 25.00 | 16.30 | 0.531357E+09 | 1277.22 | 13-JUN-14:20 | 18.33 | 11.39 |
| July | 0.344815E+10 | 4850.21 | 17-JUL-16:00 | 37.20 | 17.28 | 0.174988E+09 | 201.68 | 14-JUL-18:00 | 37.20 | 17.28 |
| August | 0.334991E+10 | 5457.85 | 06-AUG-16:02 | 35.50 | 16.24 | 0.198191E+09 | 201.68 | 08-AUG-12:09 | 26.78 | 16.55 |
| September | 0.339948E+10 | 11102.44 | 02-SEP-15:22 | 34.15 | 16.29 | 0.473617E+09 | 1277.23 | 28-SEP-14:20 | 13.90 | 8.42 |
| October | 0.270446E+10 | 6114.45 | 18-OCT-15:00 | 25.00 | 11.61 | 0.791588E+09 | 1277.24 | 30-OCT-14:20 | 10.37 | 4.65 |
| November | 0.165128E+10 | 4005.37 | 03-NOV-15:00 | 14.60 | 7.68 | 0.716938E+09 | 1277.24 | 10-NOV-15:20 | 5.33 | 0.72 |
| December | 0.814541E+09 | 2472.46 | 06-DEC-15:35 | 9.97 | 4.80 | 0.625047E+09 | 1228.18 | 06-DEC-15:50 | 9.68 | 4.65 |
| Annual Sum or Average | 0.264914E+11 | 0.695694E+10 | ||||||||
| Minimum of Months | 0.487917E+09 | 2233.81 | 8.48 | 3.51 | 0.174988E+09 | 201.68 | 5.33 | 0.72 | ||
| Maximum of Months | 0.387954E+10 | 11102.44 | 37.20 | 17.28 | 0.791588E+09 | 1277.84 | 37.20 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.433453E+10 | 10916.06 | 13-JAN-15:40 | 9.27 | 4.85 | 0.310101E+10 | 5547.45 | 13-JAN-15:50 | 9.08 | 4.76 |
| February | 0.631608E+10 | 16690.93 | 28-FEB-15:01 | 10.68 | 4.79 | 0.298723E+10 | 6153.95 | 28-FEB-15:20 | 10.77 | 4.80 |
| March | 0.953587E+10 | 16674.53 | 01-MAR-15:01 | 8.48 | 3.51 | 0.377207E+10 | 6157.05 | 01-MAR-15:30 | 8.85 | 3.64 |
| April | 0.100010E+11 | 19225.27 | 25-APR-14:40 | 16.70 | 7.20 | 0.346540E+10 | 6153.90 | 04-APR-14:20 | 16.70 | 7.20 |
| May | 0.134370E+11 | 24335.37 | 19-MAY-14:07 | 27.38 | 15.01 | 0.393064E+10 | 6153.95 | 15-MAY-14:20 | 27.38 | 15.01 |
| June | 0.182975E+11 | 22593.04 | 06-JUN-14:50 | 24.82 | 16.15 | 0.258515E+10 | 6153.88 | 13-JUN-14:20 | 18.33 | 11.39 |
| July | 0.153054E+11 | 18150.30 | 29-JUL-11:51 | 22.80 | 13.24 | 0.821317E+09 | 971.67 | 26-JUL-13:20 | 22.80 | 13.24 |
| August | 0.150625E+11 | 18620.19 | 07-AUG-14:02 | 32.80 | 15.97 | 0.942841E+09 | 971.74 | 08-AUG-12:09 | 26.78 | 16.55 |
| September | 0.163048E+11 | 28301.73 | 25-SEP-14:15 | 26.87 | 14.37 | 0.232417E+10 | 6161.90 | 26-SEP-07:00 | 8.30 | 6.33 |
| October | 0.139752E+11 | 26753.42 | 18-OCT-14:20 | 25.00 | 11.47 | 0.392149E+10 | 6153.96 | 30-OCT-14:20 | 10.37 | 4.65 |
| November | 0.972374E+10 | 19148.26 | 03-NOV-14:04 | 14.93 | 7.82 | 0.358722E+10 | 6153.96 | 10-NOV-15:20 | 5.33 | 0.72 |
| December | 0.611740E+10 | 12105.70 | 07-DEC-14:20 | 8.30 | 2.68 | 0.310844E+10 | 5997.83 | 07-DEC-14:30 | 8.30 | 2.65 |
| Annual Sum or Average | 0.138411E+12 | 0.345470E+11 | ||||||||
| Minimum of Months | 0.433453E+10 | 10916.06 | 8.30 | 2.68 | 0.821317E+09 | 971.67 | 5.33 | 0.72 | ||
| Maximum of Months | 0.182975E+11 | 28301.73 | 32.80 | 16.15 | 0.393064E+10 | 6161.90 | 27.38 | 16.55 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.107844E+09 | 1089.31 | 13-JAN-16:00 | 8.90 | 4.67 | 0.241156E+09 | 368.25 | 13-JAN-15:00 | 8.90 | 4.67 |
| February | 0.271183E+09 | 1863.90 | 28-FEB-15:01 | 10.68 | 4.79 | 0.220899E+09 | 420.23 | 28-FEB-15:00 | 11.10 | 4.84 |
| March | 0.662683E+09 | 1927.31 | 02-MAR-15:01 | 11.02 | 4.78 | 0.270699E+09 | 434.21 | 02-MAR-15:00 | 10.60 | 4.73 |
| April | 0.107443E+10 | 2159.72 | 25-APR-14:02 | 16.25 | 6.82 | 0.250721E+09 | 484.29 | 25-APR-14:00 | 17.00 | 7.46 |
| May | 0.167636E+10 | 4022.89 | 19-MAY-15:00 | 28.30 | 14.88 | 0.298468E+09 | 495.44 | 19-MAY-12:20 | 28.30 | 14.88 |
| June | 0.302912E+10 | 4193.63 | 30-JUN-16:00 | 31.10 | 14.62 | 0.208819E+09 | 495.45 | 06-JUN-14:50 | 31.10 | 14.62 |
| July | 0.241044E+10 | 3784.51 | 17-JUL-15:35 | 36.83 | 17.19 | 69687201.55 | 78.23 | 14-JUL-19:10 | 36.83 | 17.19 |
| August | 0.225137E+10 | 3599.36 | 07-AUG-15:13 | 32.60 | 16.04 | 78006095.03 | 78.23 | 08-AUG-12:09 | 26.78 | 16.55 |
| September | 0.225457E+10 | 4207.59 | 25-SEP-14:50 | 27.12 | 14.54 | 0.181737E+09 | 495.44 | 27-SEP-11:20 | 24.83 | 14.03 |
| October | 0.153014E+10 | 3097.43 | 18-OCT-15:00 | 25.00 | 11.61 | 0.293141E+09 | 495.44 | 18-OCT-13:39 | 25.00 | 11.61 |
| November | 0.799318E+09 | 2034.42 | 01-NOV-14:01 | 12.13 | 5.62 | 0.256135E+09 | 459.02 | 03-NOV-14:00 | 14.60 | 7.68 |
| December | 0.252756E+09 | 1235.12 | 06-DEC-16:00 | 9.40 | 4.51 | 0.231656E+09 | 398.69 | 07-DEC-15:00 | 6.70 | 2.23 |
| Annual Sum or Average | 0.163202E+11 | 0.260112E+10 | ||||||||
| Minimum of Months | 0.107844E+09 | 1089.31 | 8.90 | 4.51 | 69687201.55 | 78.23 | 6.70 | 2.23 | ||
| Maximum of Months | 0.302912E+10 | 4207.59 | 36.83 | 17.19 | 0.298468E+09 | 495.45 | 36.83 | 17.19 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.194432E+09 | 1895.53 | 13-JAN-15:50 | 9.08 | 4.76 | 0.627278E+09 | 1020.34 | 13-JAN-15:00 | 8.90 | 4.67 |
| February | 0.439850E+09 | 2867.48 | 28-FEB-15:01 | 10.68 | 4.79 | 0.570680E+09 | 1090.51 | 27-FEB-15:00 | 10.68 | 4.79 |
| March | 0.953866E+09 | 3023.82 | 02-MAR-15:01 | 11.02 | 4.78 | 0.699742E+09 | 1132.32 | 02-MAR-15:00 | 10.60 | 4.73 |
| April | 0.141630E+10 | 3286.64 | 25-APR-14:02 | 16.25 | 6.82 | 0.640856E+09 | 1257.48 | 07-APR-14:00 | 16.25 | 6.82 |
| May | 0.229450E+10 | 4553.70 | 19-MAY-15:00 | 28.30 | 14.88 | 0.765193E+09 | 1277.22 | 30-MAY-14:20 | 19.07 | 10.51 |
| June | 0.350045E+10 | 4423.74 | 06-JUN-15:00 | 25.00 | 16.30 | 0.527124E+09 | 1277.22 | 13-JUN-14:20 | 18.33 | 11.39 |
| July | 0.305823E+10 | 3720.64 | 17-JUL-16:00 | 37.20 | 17.28 | 0.166301E+09 | 201.68 | 14-JUL-19:10 | 37.20 | 17.28 |
| August | 0.274936E+10 | 3691.82 | 06-AUG-15:22 | 35.00 | 15.86 | 0.183445E+09 | 201.67 | 07-AUG-19:10 | 28.85 | 14.72 |
| September | 0.269525E+10 | 4422.80 | 27-SEP-15:00 | 27.20 | 14.13 | 0.453953E+09 | 1277.23 | 28-SEP-14:20 | 13.90 | 8.42 |
| October | 0.205994E+10 | 3793.09 | 18-OCT-15:00 | 25.00 | 11.61 | 0.739756E+09 | 1277.23 | 20-OCT-14:20 | 12.93 | 6.60 |
| November | 0.114387E+10 | 3192.39 | 08-NOV-15:01 | 13.07 | 7.56 | 0.662900E+09 | 1188.81 | 03-NOV-14:00 | 13.07 | 7.56 |
| December | 0.464654E+09 | 2060.02 | 06-DEC-15:50 | 9.68 | 4.65 | 0.601615E+09 | 1077.97 | 06-DEC-15:00 | 9.40 | 4.51 |
| Annual Sum or Average | 0.209707E+11 | 0.663884E+10 | ||||||||
| Minimum of Months | 0.194432E+09 | 1895.53 | 9.08 | 4.65 | 0.166301E+09 | 201.67 | 8.90 | 4.51 | ||
| Maximum of Months | 0.350045E+10 | 4553.70 | 37.20 | 17.28 | 0.765193E+09 | 1277.23 | 37.20 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.241851E+10 | 9306.95 | 13-JAN-15:50 | 9.08 | 4.76 | 0.302872E+10 | 4976.47 | 13-JAN-15:00 | 8.90 | 4.67 |
| February | 0.370047E+10 | 14086.82 | 28-FEB-15:01 | 10.68 | 4.79 | 0.278329E+10 | 5248.25 | 28-FEB-15:00 | 11.10 | 4.84 |
| March | 0.671570E+10 | 14770.89 | 02-MAR-15:01 | 11.02 | 4.78 | 0.348120E+10 | 5476.16 | 02-MAR-15:09 | 11.02 | 4.78 |
| April | 0.835289E+10 | 16174.24 | 25-APR-14:02 | 16.25 | 6.82 | 0.326025E+10 | 6132.13 | 07-APR-14:00 | 16.25 | 6.82 |
| May | 0.118806E+11 | 19142.62 | 19-MAY-15:00 | 28.30 | 14.88 | 0.382075E+10 | 6153.88 | 30-MAY-14:20 | 19.07 | 10.51 |
| June | 0.165758E+11 | 19251.27 | 06-JUN-15:00 | 25.00 | 16.30 | 0.256294E+10 | 6153.87 | 13-JUN-14:20 | 18.33 | 11.39 |
| July | 0.137612E+11 | 16538.75 | 30-JUL-19:51 | 23.30 | 12.48 | 0.762298E+09 | 896.15 | 19-JUL-14:09 | 23.30 | 12.48 |
| August | 0.126237E+11 | 16144.70 | 07-AUG-05:01 | 17.48 | 9.94 | 0.848049E+09 | 891.51 | 08-AUG-13:39 | 27.93 | 15.72 |
| September | 0.130359E+11 | 19065.24 | 27-SEP-14:30 | 27.50 | 14.10 | 0.222883E+10 | 6153.91 | 28-SEP-14:20 | 13.90 | 8.42 |
| October | 0.107237E+11 | 16891.74 | 20-OCT-14:01 | 13.12 | 6.68 | 0.369929E+10 | 6153.92 | 20-OCT-14:20 | 12.93 | 6.60 |
| November | 0.697754E+10 | 15591.48 | 08-NOV-15:01 | 13.07 | 7.56 | 0.329655E+10 | 5789.03 | 08-NOV-15:50 | 12.53 | 7.20 |
| December | 0.393586E+10 | 9989.62 | 06-DEC-15:10 | 10.82 | 5.21 | 0.293662E+10 | 5217.32 | 06-DEC-15:20 | 10.53 | 5.07 |
| Annual Sum or Average | 0.110702E+12 | 0.327088E+11 | ||||||||
| Minimum of Months | 0.241851E+10 | 9306.95 | 9.08 | 4.76 | 0.762298E+09 | 891.51 | 8.90 | 4.67 | ||
| Maximum of Months | 0.165758E+11 | 19251.27 | 28.30 | 16.30 | 0.382075E+10 | 6153.92 | 27.93 | 15.72 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.451423E+09 | 2209.32 | 13-JAN-15:40 | 9.27 | 4.85 | 0.632096E+09 | 1130.86 | 13-JAN-15:50 | 9.08 | 4.76 |
| February | 0.884680E+09 | 3461.48 | 28-FEB-15:01 | 10.68 | 4.79 | 0.596517E+09 | 1277.23 | 28-FEB-15:20 | 10.77 | 4.80 |
| March | 0.146509E+10 | 3456.79 | 01-MAR-15:01 | 8.48 | 3.51 | 0.741387E+09 | 1277.83 | 01-MAR-15:30 | 8.85 | 3.64 |
| April | 0.173356E+10 | 4176.84 | 25-APR-15:00 | 17.00 | 7.46 | 0.678676E+09 | 1277.22 | 13-APR-14:20 | 17.00 | 7.46 |
| May | 0.257833E+10 | 5526.79 | 19-MAY-15:00 | 28.30 | 14.88 | 0.787895E+09 | 1277.23 | 15-MAY-14:20 | 28.30 | 14.88 |
| June | 0.381727E+10 | 4991.35 | 06-JUN-15:00 | 25.00 | 16.30 | 0.530369E+09 | 1277.22 | 13-JUN-14:20 | 18.33 | 11.39 |
| July | 0.339672E+10 | 4767.50 | 17-JUL-16:00 | 37.20 | 17.28 | 0.174168E+09 | 201.68 | 14-JUL-18:00 | 37.20 | 17.28 |
| August | 0.330452E+10 | 4960.92 | 07-AUG-15:13 | 32.60 | 16.04 | 0.197349E+09 | 201.68 | 08-AUG-12:09 | 26.78 | 16.55 |
| September | 0.336660E+10 | 10980.08 | 02-SEP-15:22 | 34.15 | 16.29 | 0.472972E+09 | 1277.23 | 28-SEP-14:20 | 13.90 | 8.42 |
| October | 0.268402E+10 | 6085.00 | 18-OCT-15:00 | 25.00 | 11.61 | 0.790138E+09 | 1277.24 | 30-OCT-14:20 | 10.37 | 4.65 |
| November | 0.161656E+10 | 3919.88 | 03-NOV-15:00 | 14.60 | 7.68 | 0.713319E+09 | 1277.24 | 10-NOV-15:20 | 5.33 | 0.72 |
| December | 0.752428E+09 | 2407.89 | 06-DEC-15:35 | 9.97 | 4.80 | 0.620849E+09 | 1203.79 | 06-DEC-15:39 | 9.97 | 4.80 |
| Annual Sum or Average | 0.260512E+11 | 0.693573E+10 | ||||||||
| Minimum of Months | 0.451423E+09 | 2209.32 | 8.48 | 3.51 | 0.174168E+09 | 201.68 | 5.33 | 0.72 | ||
| Maximum of Months | 0.381727E+10 | 10980.08 | 37.20 | 17.28 | 0.790138E+09 | 1277.83 | 37.20 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.412396E+10 | 10753.32 | 13-JAN-15:10 | 9.82 | 5.10 | 0.308728E+10 | 5489.89 | 13-JAN-15:30 | 9.45 | 4.93 |
| February | 0.624287E+10 | 16670.45 | 28-FEB-15:01 | 10.68 | 4.79 | 0.297626E+10 | 6153.94 | 28-FEB-15:20 | 10.77 | 4.80 |
| March | 0.944546E+10 | 16653.82 | 01-MAR-15:01 | 8.48 | 3.51 | 0.375966E+10 | 6156.94 | 01-MAR-15:30 | 8.85 | 3.64 |
| April | 0.994593E+10 | 18975.92 | 25-APR-14:40 | 16.70 | 7.20 | 0.346134E+10 | 6153.89 | 13-APR-14:20 | 16.70 | 7.20 |
| May | 0.133066E+11 | 23935.72 | 19-MAY-14:30 | 27.75 | 14.96 | 0.392538E+10 | 6153.95 | 15-MAY-14:20 | 27.75 | 14.96 |
| June | 0.180047E+11 | 21976.49 | 06-JUN-14:50 | 24.82 | 16.15 | 0.258225E+10 | 6153.88 | 13-JUN-14:20 | 18.33 | 11.39 |
| July | 0.150872E+11 | 17875.30 | 29-JUL-11:51 | 22.80 | 13.24 | 0.813496E+09 | 971.67 | 31-JUL-13:20 | 30.20 | 14.55 |
| August | 0.148182E+11 | 18430.67 | 11-AUG-15:10 | 30.60 | 13.32 | 0.936161E+09 | 971.74 | 08-AUG-12:09 | 30.60 | 13.32 |
| September | 0.160885E+11 | 27776.66 | 25-SEP-14:30 | 26.95 | 14.43 | 0.232215E+10 | 6161.61 | 26-SEP-07:00 | 8.30 | 6.33 |
| October | 0.137883E+11 | 26363.33 | 18-OCT-14:20 | 25.00 | 11.47 | 0.391643E+10 | 6153.96 | 30-OCT-14:20 | 10.37 | 4.65 |
| November | 0.946189E+10 | 18461.46 | 03-NOV-14:04 | 14.93 | 7.82 | 0.356345E+10 | 6153.96 | 10-NOV-15:20 | 5.33 | 0.72 |
| December | 0.568077E+10 | 11775.62 | 07-DEC-14:30 | 8.30 | 2.65 | 0.307280E+10 | 5875.92 | 07-DEC-14:39 | 8.30 | 2.62 |
| Annual Sum or Average | 0.135994E+12 | 0.344167E+11 | ||||||||
| Minimum of Months | 0.412396E+10 | 10753.32 | 8.30 | 2.65 | 0.813496E+09 | 971.67 | 5.33 | 0.72 | ||
| Maximum of Months | 0.180047E+11 | 27776.66 | 30.60 | 16.15 | 0.392538E+10 | 6161.61 | 30.60 | 14.96 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.103103E+09 | 1081.56 | 13-JAN-16:00 | 8.90 | 4.67 | 0.241096E+09 | 367.66 | 13-JAN-15:00 | 8.90 | 4.67 |
| February | 0.262997E+09 | 1845.76 | 28-FEB-15:01 | 10.68 | 4.79 | 0.220779E+09 | 417.82 | 28-FEB-15:00 | 11.10 | 4.84 |
| March | 0.650469E+09 | 1911.73 | 02-MAR-15:01 | 11.02 | 4.78 | 0.270482E+09 | 432.33 | 02-MAR-15:00 | 10.60 | 4.73 |
| April | 0.106899E+10 | 2149.48 | 25-APR-14:02 | 16.25 | 6.82 | 0.250541E+09 | 483.62 | 25-APR-14:00 | 17.00 | 7.46 |
| May | 0.166435E+10 | 3993.94 | 19-MAY-15:00 | 28.30 | 14.88 | 0.298265E+09 | 495.44 | 19-MAY-12:20 | 28.30 | 14.88 |
| June | 0.299754E+10 | 4175.99 | 30-JUN-16:00 | 31.10 | 14.62 | 0.208734E+09 | 495.45 | 06-JUN-14:50 | 31.10 | 14.62 |
| July | 0.237346E+10 | 3714.09 | 17-JUL-15:23 | 36.65 | 17.14 | 69540977.93 | 78.23 | 14-JUL-19:10 | 36.65 | 17.14 |
| August | 0.222710E+10 | 3545.78 | 07-AUG-15:13 | 32.60 | 16.04 | 77794615.86 | 78.23 | 08-AUG-12:09 | 26.78 | 16.55 |
| September | 0.223398E+10 | 4158.49 | 25-SEP-14:50 | 27.12 | 14.54 | 0.181617E+09 | 495.44 | 28-SEP-14:20 | 13.90 | 8.42 |
| October | 0.151833E+10 | 3064.30 | 18-OCT-15:00 | 25.00 | 11.61 | 0.292691E+09 | 495.44 | 18-OCT-13:20 | 25.00 | 11.61 |
| November | 0.776188E+09 | 2017.88 | 01-NOV-14:01 | 12.13 | 5.62 | 0.255342E+09 | 456.52 | 03-NOV-14:00 | 14.60 | 7.68 |
| December | 0.226309E+09 | 1198.05 | 06-DEC-15:50 | 9.68 | 4.65 | 0.231450E+09 | 392.21 | 06-DEC-15:00 | 9.40 | 4.51 |
| Annual Sum or Average | 0.161028E+11 | 0.259833E+10 | ||||||||
| Minimum of Months | 0.103103E+09 | 1081.56 | 8.90 | 4.65 | 69540977.93 | 78.23 | 8.90 | 4.51 | ||
| Maximum of Months | 0.299754E+10 | 4175.99 | 36.65 | 17.14 | 0.298265E+09 | 495.45 | 36.65 | 17.14 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.193869E+09 | 1893.42 | 13-JAN-15:50 | 9.08 | 4.76 | 0.627278E+09 | 1020.73 | 13-JAN-15:00 | 8.90 | 4.67 |
| February | 0.439435E+09 | 2861.87 | 28-FEB-15:01 | 10.68 | 4.79 | 0.570685E+09 | 1090.03 | 27-FEB-15:00 | 10.68 | 4.79 |
| March | 0.953612E+09 | 3019.29 | 02-MAR-15:01 | 11.02 | 4.78 | 0.699868E+09 | 1132.49 | 02-MAR-15:00 | 10.60 | 4.73 |
| April | 0.141618E+10 | 3282.97 | 25-APR-14:02 | 16.25 | 6.82 | 0.641133E+09 | 1258.41 | 07-APR-14:00 | 16.25 | 6.82 |
| May | 0.229488E+10 | 4559.79 | 19-MAY-15:00 | 28.30 | 14.88 | 0.765636E+09 | 1277.22 | 30-MAY-14:20 | 19.07 | 10.51 |
| June | 0.350227E+10 | 4430.56 | 06-JUN-15:00 | 25.00 | 16.30 | 0.527342E+09 | 1277.22 | 13-JUN-14:20 | 18.33 | 11.39 |
| July | 0.305584E+10 | 3726.79 | 17-JUL-16:00 | 37.20 | 17.28 | 0.166394E+09 | 201.68 | 14-JUL-19:10 | 37.20 | 17.28 |
| August | 0.274600E+10 | 3687.68 | 06-AUG-15:22 | 35.00 | 15.86 | 0.183501E+09 | 201.67 | 07-AUG-19:10 | 28.85 | 14.72 |
| September | 0.269318E+10 | 4426.20 | 27-SEP-15:00 | 27.20 | 14.13 | 0.454076E+09 | 1277.23 | 28-SEP-14:20 | 13.90 | 8.42 |
| October | 0.205708E+10 | 3790.66 | 18-OCT-15:00 | 25.00 | 11.61 | 0.739905E+09 | 1277.23 | 20-OCT-14:20 | 12.93 | 6.60 |
| November | 0.113935E+10 | 3185.83 | 08-NOV-15:01 | 13.07 | 7.56 | 0.662774E+09 | 1188.43 | 03-NOV-14:00 | 13.07 | 7.56 |
| December | 0.462170E+09 | 2056.10 | 06-DEC-15:50 | 9.68 | 4.65 | 0.601596E+09 | 1077.84 | 06-DEC-15:00 | 9.40 | 4.51 |
| Annual Sum or Average | 0.209539E+11 | 0.664019E+10 | ||||||||
| Minimum of Months | 0.193869E+09 | 1893.42 | 9.08 | 4.65 | 0.166394E+09 | 201.67 | 8.90 | 4.51 | ||
| Maximum of Months | 0.350227E+10 | 4559.79 | 37.20 | 17.28 | 0.765636E+09 | 1277.23 | 37.20 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.241056E+10 | 9299.82 | 13-JAN-15:50 | 9.08 | 4.76 | 0.302877E+10 | 4978.09 | 13-JAN-15:00 | 8.90 | 4.67 |
| February | 0.369627E+10 | 14062.15 | 28-FEB-15:01 | 10.68 | 4.79 | 0.278340E+10 | 5246.02 | 28-FEB-15:00 | 11.10 | 4.84 |
| March | 0.671210E+10 | 14752.73 | 02-MAR-15:01 | 11.02 | 4.78 | 0.348198E+10 | 5476.31 | 02-MAR-15:09 | 11.02 | 4.78 |
| April | 0.835165E+10 | 16161.56 | 25-APR-14:02 | 16.25 | 6.82 | 0.326179E+10 | 6135.83 | 07-APR-14:00 | 16.25 | 6.82 |
| May | 0.118847E+11 | 19168.69 | 19-MAY-15:00 | 28.30 | 14.88 | 0.382267E+10 | 6153.88 | 30-MAY-14:20 | 19.07 | 10.51 |
| June | 0.165836E+11 | 19281.38 | 06-JUN-15:00 | 25.00 | 16.30 | 0.256382E+10 | 6153.87 | 13-JUN-14:20 | 18.33 | 11.39 |
| July | 0.137505E+11 | 16510.02 | 30-JUL-19:51 | 23.30 | 12.48 | 0.762574E+09 | 896.78 | 19-JUL-14:09 | 23.30 | 12.48 |
| August | 0.126096E+11 | 16114.59 | 07-AUG-05:01 | 17.48 | 9.94 | 0.848191E+09 | 891.89 | 08-AUG-13:39 | 27.93 | 15.72 |
| September | 0.130266E+11 | 19077.74 | 27-SEP-14:30 | 27.50 | 14.10 | 0.222927E+10 | 6153.91 | 28-SEP-14:20 | 13.90 | 8.42 |
| October | 0.107112E+11 | 16870.92 | 20-OCT-14:01 | 13.12 | 6.68 | 0.369974E+10 | 6153.92 | 20-OCT-14:20 | 12.93 | 6.60 |
| November | 0.695113E+10 | 15563.98 | 08-NOV-15:01 | 13.07 | 7.56 | 0.329542E+10 | 5786.03 | 08-NOV-15:50 | 12.53 | 7.20 |
| December | 0.391373E+10 | 9971.78 | 06-DEC-15:10 | 10.82 | 5.21 | 0.293620E+10 | 5215.50 | 06-DEC-15:20 | 10.53 | 5.07 |
| Annual Sum or Average | 0.110602E+12 | 0.327138E+11 | ||||||||
| Minimum of Months | 0.241056E+10 | 9299.82 | 9.08 | 4.76 | 0.762574E+09 | 891.89 | 8.90 | 4.67 | ||
| Maximum of Months | 0.165836E+11 | 19281.38 | 28.30 | 16.30 | 0.382267E+10 | 6153.92 | 27.93 | 15.72 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.464304E+09 | 2221.49 | 13-JAN-15:40 | 9.27 | 4.85 | 0.632389E+09 | 1136.61 | 13-JAN-15:50 | 9.08 | 4.76 |
| February | 0.888993E+09 | 3456.23 | 28-FEB-15:01 | 10.68 | 4.79 | 0.596912E+09 | 1277.23 | 28-FEB-15:20 | 10.77 | 4.80 |
| March | 0.147369E+10 | 3451.57 | 01-MAR-15:01 | 8.48 | 3.51 | 0.742241E+09 | 1277.83 | 01-MAR-15:30 | 8.85 | 3.64 |
| April | 0.174959E+10 | 4218.67 | 25-APR-15:00 | 17.00 | 7.46 | 0.680385E+09 | 1277.22 | 13-APR-14:20 | 17.00 | 7.46 |
| May | 0.259875E+10 | 5559.91 | 19-MAY-15:00 | 28.30 | 14.88 | 0.789672E+09 | 1277.23 | 15-MAY-14:20 | 28.30 | 14.88 |
| June | 0.384124E+10 | 5020.35 | 06-JUN-15:00 | 25.00 | 16.30 | 0.530967E+09 | 1277.22 | 13-JUN-14:20 | 18.33 | 11.39 |
| July | 0.342278E+10 | 4813.84 | 17-JUL-16:00 | 37.20 | 17.28 | 0.174723E+09 | 201.68 | 14-JUL-18:00 | 37.20 | 17.28 |
| August | 0.333157E+10 | 5114.87 | 06-AUG-16:02 | 35.50 | 16.24 | 0.197937E+09 | 201.68 | 08-AUG-12:09 | 26.78 | 16.55 |
| September | 0.339087E+10 | 11023.04 | 02-SEP-15:22 | 34.15 | 16.29 | 0.473888E+09 | 1277.23 | 28-SEP-14:20 | 13.90 | 8.42 |
| October | 0.270459E+10 | 6116.87 | 18-OCT-15:00 | 25.00 | 11.61 | 0.791843E+09 | 1277.24 | 30-OCT-14:20 | 10.37 | 4.65 |
| November | 0.163690E+10 | 3973.60 | 03-NOV-15:00 | 14.60 | 7.68 | 0.715391E+09 | 1277.24 | 10-NOV-15:20 | 5.33 | 0.72 |
| December | 0.771701E+09 | 2433.88 | 06-DEC-15:35 | 9.97 | 4.80 | 0.622333E+09 | 1215.04 | 06-DEC-15:50 | 9.68 | 4.65 |
| Annual Sum or Average | 0.262750E+11 | 0.694868E+10 | ||||||||
| Minimum of Months | 0.464304E+09 | 2221.49 | 8.48 | 3.51 | 0.174723E+09 | 201.68 | 5.33 | 0.72 | ||
| Maximum of Months | 0.384124E+10 | 11023.04 | 37.20 | 17.28 | 0.791843E+09 | 1277.83 | 37.20 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.421398E+10 | 10848.51 | 13-JAN-15:35 | 9.27 | 4.85 | 0.309257E+10 | 5525.52 | 13-JAN-15:50 | 9.08 | 4.76 |
| February | 0.627989E+10 | 16671.22 | 28-FEB-15:01 | 10.68 | 4.79 | 0.297928E+10 | 6153.94 | 28-FEB-15:20 | 10.77 | 4.80 |
| March | 0.952608E+10 | 16654.94 | 01-MAR-15:01 | 8.48 | 3.51 | 0.376734E+10 | 6156.97 | 01-MAR-15:30 | 8.85 | 3.64 |
| April | 0.100758E+11 | 19268.94 | 25-APR-14:40 | 16.70 | 7.20 | 0.347416E+10 | 6153.94 | 26-APR-14:20 | 10.93 | 4.79 |
| May | 0.134708E+11 | 24194.86 | 19-MAY-14:30 | 27.75 | 14.96 | 0.393654E+10 | 6153.95 | 15-MAY-14:20 | 27.75 | 14.96 |
| June | 0.181932E+11 | 22200.23 | 06-JUN-14:50 | 24.82 | 16.15 | 0.258561E+10 | 6153.95 | 01-JUN-08:20 | 24.82 | 16.15 |
| July | 0.152314E+11 | 18013.61 | 29-JUL-11:51 | 22.80 | 13.24 | 0.818841E+09 | 971.67 | 31-JUL-13:20 | 30.20 | 14.55 |
| August | 0.149880E+11 | 18489.92 | 06-AUG-14:02 | 34.40 | 15.37 | 0.941134E+09 | 971.74 | 08-AUG-12:09 | 26.78 | 16.55 |
| September | 0.162860E+11 | 28155.30 | 25-SEP-14:30 | 26.95 | 14.43 | 0.232761E+10 | 6161.95 | 26-SEP-07:00 | 8.30 | 6.33 |
| October | 0.139902E+11 | 26673.29 | 18-OCT-14:20 | 25.00 | 11.47 | 0.392565E+10 | 6153.96 | 30-OCT-14:20 | 10.37 | 4.65 |
| November | 0.964236E+10 | 18977.80 | 03-NOV-14:04 | 14.93 | 7.82 | 0.357801E+10 | 6153.96 | 10-NOV-15:20 | 5.33 | 0.72 |
| December | 0.582383E+10 | 11890.69 | 07-DEC-14:30 | 8.30 | 2.65 | 0.308398E+10 | 5919.93 | 07-DEC-14:39 | 8.30 | 2.62 |
| Annual Sum or Average | 0.137721E+12 | 0.345107E+11 | ||||||||
| Minimum of Months | 0.421398E+10 | 10848.51 | 8.30 | 2.65 | 0.818841E+09 | 971.67 | 5.33 | 0.72 | ||
| Maximum of Months | 0.181932E+11 | 28155.30 | 34.40 | 16.15 | 0.393654E+10 | 6161.95 | 30.20 | 16.55 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.108970E+09 | 1102.35 | 13-JAN-16:00 | 8.90 | 4.67 | 0.241189E+09 | 369.48 | 13-JAN-15:00 | 8.90 | 4.67 |
| February | 0.283008E+09 | 1879.20 | 28-FEB-15:01 | 10.68 | 4.79 | 0.220936E+09 | 421.07 | 28-FEB-15:00 | 11.10 | 4.84 |
| March | 0.714477E+09 | 1951.39 | 02-MAR-15:01 | 11.02 | 4.78 | 0.271370E+09 | 436.84 | 02-MAR-15:00 | 10.60 | 4.73 |
| April | 0.114178E+10 | 2204.13 | 25-APR-14:02 | 16.25 | 6.82 | 0.253511E+09 | 491.00 | 25-APR-14:00 | 17.00 | 7.46 |
| May | 0.176404E+10 | 4213.96 | 19-MAY-15:00 | 28.30 | 14.88 | 0.301445E+09 | 495.44 | 19-MAY-12:20 | 28.30 | 14.88 |
| June | 0.320202E+10 | 4404.53 | 30-JUN-16:00 | 31.10 | 14.62 | 0.209544E+09 | 495.45 | 01-JUN-09:39 | 31.10 | 14.62 |
| July | 0.254381E+10 | 4067.43 | 17-JUL-15:23 | 36.65 | 17.14 | 70339004.70 | 78.23 | 14-JUL-19:10 | 36.65 | 17.14 |
| August | 0.236208E+10 | 3877.27 | 07-AUG-15:13 | 32.60 | 16.04 | 78852868.15 | 78.23 | 08-AUG-12:09 | 26.78 | 16.55 |
| September | 0.236163E+10 | 4404.89 | 25-SEP-14:50 | 27.12 | 14.54 | 0.183411E+09 | 495.44 | 27-SEP-11:39 | 25.77 | 14.36 |
| October | 0.158863E+10 | 3257.34 | 18-OCT-15:00 | 25.00 | 11.61 | 0.296141E+09 | 495.44 | 18-OCT-13:39 | 25.00 | 11.61 |
| November | 0.832414E+09 | 2073.34 | 01-NOV-14:01 | 12.13 | 5.62 | 0.257455E+09 | 464.32 | 03-NOV-14:00 | 14.60 | 7.68 |
| December | 0.250947E+09 | 1231.76 | 07-DEC-15:50 | 6.97 | 2.29 | 0.231646E+09 | 397.09 | 07-DEC-15:00 | 6.70 | 2.23 |
| Annual Sum or Average | 0.171538E+11 | 0.261584E+10 | ||||||||
| Minimum of Months | 0.108970E+09 | 1102.35 | 6.97 | 2.29 | 70339004.70 | 78.23 | 6.70 | 2.23 | ||
| Maximum of Months | 0.320202E+10 | 4404.89 | 36.65 | 17.14 | 0.301445E+09 | 495.45 | 36.65 | 17.14 |
Report: ZoneCoolingSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.197524E+09 | 1899.28 | 13-JAN-15:50 | 9.08 | 4.76 | 0.627300E+09 | 1022.05 | 13-JAN-15:00 | 8.90 | 4.67 |
| February | 0.449097E+09 | 2873.20 | 28-FEB-15:01 | 10.68 | 4.79 | 0.570920E+09 | 1092.81 | 27-FEB-15:00 | 10.68 | 4.79 |
| March | 0.977857E+09 | 3039.87 | 02-MAR-15:01 | 11.02 | 4.78 | 0.701145E+09 | 1138.47 | 02-MAR-15:00 | 10.60 | 4.73 |
| April | 0.144849E+10 | 3309.16 | 25-APR-14:02 | 16.25 | 6.82 | 0.644134E+09 | 1266.63 | 07-APR-14:50 | 16.25 | 6.82 |
| May | 0.234730E+10 | 4663.78 | 19-MAY-15:00 | 28.30 | 14.88 | 0.770256E+09 | 1277.22 | 30-MAY-14:20 | 19.07 | 10.51 |
| June | 0.358500E+10 | 4553.76 | 06-JUN-15:00 | 25.00 | 16.30 | 0.529389E+09 | 1277.22 | 13-JUN-14:20 | 18.33 | 11.39 |
| July | 0.311949E+10 | 3870.26 | 17-JUL-16:00 | 37.20 | 17.28 | 0.168178E+09 | 201.68 | 14-JUL-19:10 | 37.20 | 17.28 |
| August | 0.279931E+10 | 3739.14 | 06-AUG-15:22 | 35.00 | 15.86 | 0.185049E+09 | 201.67 | 11-AUG-16:30 | 30.85 | 14.16 |
| September | 0.273493E+10 | 4500.93 | 25-SEP-15:00 | 27.20 | 14.60 | 0.455828E+09 | 1277.23 | 28-SEP-14:20 | 13.90 | 8.42 |
| October | 0.208044E+10 | 3831.62 | 18-OCT-15:00 | 25.00 | 11.61 | 0.742507E+09 | 1277.23 | 20-OCT-14:20 | 12.93 | 6.60 |
| November | 0.115314E+10 | 3204.01 | 08-NOV-15:01 | 13.07 | 7.56 | 0.664069E+09 | 1193.41 | 03-NOV-14:00 | 13.07 | 7.56 |
| December | 0.466680E+09 | 2062.50 | 06-DEC-15:50 | 9.68 | 4.65 | 0.601771E+09 | 1079.32 | 06-DEC-15:00 | 9.40 | 4.51 |
| Annual Sum or Average | 0.213593E+11 | 0.666055E+10 | ||||||||
| Minimum of Months | 0.197524E+09 | 1899.28 | 9.08 | 4.65 | 0.168178E+09 | 201.67 | 8.90 | 4.51 | ||
| Maximum of Months | 0.358500E+10 | 4663.78 | 37.20 | 17.28 | 0.770256E+09 | 1277.23 | 37.20 | 17.28 |
Report: ZoneCoolingSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.157603E+10 | 6161.07 | 13-JAN-15:50 | 9.08 | 4.76 | 0.200040E+10 | 3295.07 | 13-JAN-15:00 | 8.90 | 4.67 |
| February | 0.244280E+10 | 9316.17 | 28-FEB-15:01 | 10.68 | 4.79 | 0.183982E+10 | 3476.40 | 28-FEB-15:00 | 11.10 | 4.84 |
| March | 0.450331E+10 | 9817.24 | 02-MAR-15:01 | 11.02 | 4.78 | 0.230727E+10 | 3645.11 | 02-MAR-15:09 | 11.02 | 4.78 |
| April | 0.562418E+10 | 10765.90 | 25-APR-14:02 | 16.25 | 6.82 | 0.216798E+10 | 4063.54 | 07-APR-14:20 | 16.25 | 6.82 |
| May | 0.806422E+10 | 13161.43 | 19-MAY-15:00 | 28.30 | 14.88 | 0.254221E+10 | 4063.93 | 15-MAY-14:20 | 28.30 | 14.88 |
| June | 0.112832E+11 | 13305.18 | 06-JUN-15:00 | 25.00 | 16.30 | 0.170195E+10 | 4063.88 | 13-JUN-14:20 | 18.33 | 11.39 |
| July | 0.932470E+10 | 11120.39 | 22-JUL-18:31 | 22.57 | 12.81 | 0.512679E+09 | 604.06 | 20-JUL-14:09 | 22.57 | 12.81 |
| August | 0.853770E+10 | 10737.20 | 07-AUG-05:01 | 17.48 | 9.94 | 0.567946E+09 | 597.46 | 08-AUG-13:39 | 27.93 | 15.72 |
| September | 0.876651E+10 | 12966.76 | 27-SEP-14:05 | 27.70 | 14.08 | 0.147984E+10 | 4063.90 | 28-SEP-14:20 | 13.90 | 8.42 |
| October | 0.717219E+10 | 11143.54 | 20-OCT-14:01 | 13.12 | 6.68 | 0.245472E+10 | 4063.91 | 20-OCT-14:20 | 12.93 | 6.60 |
| November | 0.464007E+10 | 10358.51 | 08-NOV-15:01 | 13.07 | 7.56 | 0.218317E+10 | 3850.79 | 08-NOV-15:50 | 12.53 | 7.20 |
| December | 0.256769E+10 | 6613.16 | 06-DEC-15:10 | 10.82 | 5.21 | 0.194010E+10 | 3455.06 | 06-DEC-15:20 | 10.53 | 5.07 |
| Annual Sum or Average | 0.745026E+11 | 0.216981E+11 | ||||||||
| Minimum of Months | 0.157603E+10 | 6161.07 | 9.08 | 4.76 | 0.512679E+09 | 597.46 | 8.90 | 4.67 | ||
| Maximum of Months | 0.112832E+11 | 13305.18 | 28.30 | 16.30 | 0.254221E+10 | 4063.93 | 28.30 | 15.72 |
Report: ZoneCoolingSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.160937E+10 | 3410.35 | 13-JAN-15:50 | 9.08 | 4.76 | 0.153237E+10 | 1778.40 | 13-JAN-15:00 | 8.90 | 4.67 |
| February | 0.218200E+10 | 5087.12 | 28-FEB-15:01 | 10.68 | 4.79 | 0.143081E+10 | 1896.10 | 28-FEB-16:19 | 10.73 | 4.66 |
| March | 0.342695E+10 | 5361.19 | 02-MAR-15:01 | 11.02 | 4.78 | 0.184642E+10 | 1992.40 | 29-MAR-15:00 | 12.20 | 4.07 |
| April | 0.368498E+10 | 5683.42 | 25-APR-14:02 | 16.25 | 6.82 | 0.177794E+10 | 2090.02 | 26-APR-14:20 | 10.93 | 4.79 |
| May | 0.515534E+10 | 7853.28 | 19-MAY-15:04 | 28.22 | 14.82 | 0.203746E+10 | 2090.02 | 05-MAY-14:20 | 28.22 | 14.82 |
| June | 0.779464E+10 | 8604.48 | 23-JUN-13:40 | 31.50 | 15.23 | 0.214315E+10 | 2090.07 | 22-JUN-18:10 | 31.50 | 15.23 |
| July | 0.552224E+10 | 6051.27 | 22-JUL-18:31 | 22.57 | 12.81 | 0.980191E+09 | 1100.03 | 14-JUL-19:10 | 22.57 | 12.81 |
| August | 0.520836E+10 | 6158.91 | 11-AUG-15:10 | 30.60 | 13.32 | 0.109252E+10 | 1100.02 | 10-AUG-15:20 | 30.60 | 13.32 |
| September | 0.592742E+10 | 8002.85 | 06-SEP-14:50 | 26.02 | 18.81 | 0.188223E+10 | 2092.35 | 26-SEP-07:00 | 8.30 | 6.33 |
| October | 0.451727E+10 | 6508.94 | 18-OCT-15:00 | 25.00 | 11.61 | 0.196767E+10 | 2090.02 | 30-OCT-14:20 | 10.37 | 4.65 |
| November | 0.332547E+10 | 5639.50 | 01-NOV-14:01 | 12.13 | 5.62 | 0.174729E+10 | 2090.02 | 08-NOV-16:19 | 12.17 | 6.99 |
| December | 0.226515E+10 | 3680.71 | 06-DEC-15:10 | 10.82 | 5.21 | 0.151017E+10 | 1876.33 | 06-DEC-15:20 | 10.53 | 5.07 |
| Annual Sum or Average | 0.506192E+11 | 0.199482E+11 | ||||||||
| Minimum of Months | 0.160937E+10 | 3410.35 | 9.08 | 4.76 | 0.980191E+09 | 1100.02 | 8.30 | 4.07 | ||
| Maximum of Months | 0.779464E+10 | 8604.48 | 31.50 | 18.81 | 0.214315E+10 | 2092.35 | 31.50 | 15.23 |
Report: ZoneCoolingSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.184573E+09 | 1905.18 | 24-JAN-07:18 | 7.43 | 2.20 | 0.680804E+09 | 1042.97 | 10-JAN-13:50 | 7.43 | 2.20 |
| February | 0.415745E+09 | 3773.61 | 28-FEB-15:01 | 10.68 | 4.79 | 0.625603E+09 | 1110.71 | 28-FEB-15:00 | 11.10 | 4.84 |
| March | 0.134730E+10 | 4027.61 | 23-MAR-14:01 | 9.63 | 2.29 | 0.767266E+09 | 1182.98 | 23-MAR-14:09 | 9.63 | 2.29 |
| April | 0.277272E+10 | 4852.90 | 25-APR-14:02 | 16.25 | 6.82 | 0.745877E+09 | 1408.87 | 25-APR-14:00 | 17.00 | 7.46 |
| May | 0.449705E+10 | 10899.07 | 31-MAY-15:00 | 23.30 | 9.75 | 0.887150E+09 | 1408.97 | 30-MAY-07:00 | 23.30 | 9.75 |
| June | 0.896384E+10 | 13426.60 | 26-JUN-07:03 | 17.67 | 12.36 | 0.603350E+09 | 1409.07 | 01-JUN-07:49 | 17.67 | 12.36 |
| July | 0.771657E+10 | 14598.86 | 17-JUL-07:03 | 23.17 | 14.94 | 0.207054E+09 | 231.33 | 17-JUL-07:10 | 23.17 | 14.94 |
| August | 0.652781E+10 | 11253.64 | 07-AUG-15:01 | 32.70 | 16.01 | 0.233813E+09 | 225.86 | 07-AUG-07:10 | 32.70 | 16.01 |
| September | 0.552193E+10 | 16410.29 | 05-SEP-07:02 | 18.98 | 12.62 | 0.529862E+09 | 1408.94 | 28-SEP-14:20 | 13.90 | 8.42 |
| October | 0.317693E+10 | 5280.48 | 18-OCT-15:00 | 25.00 | 11.61 | 0.828374E+09 | 1408.93 | 20-OCT-14:20 | 12.93 | 6.60 |
| November | 0.134361E+10 | 4267.94 | 01-NOV-14:01 | 12.13 | 5.62 | 0.713950E+09 | 1249.30 | 01-NOV-14:00 | 11.80 | 5.37 |
| December | 0.316855E+09 | 2351.70 | 06-DEC-15:00 | 11.10 | 5.34 | 0.656331E+09 | 1047.66 | 06-DEC-15:09 | 10.82 | 5.21 |
| Annual Sum or Average | 0.427849E+11 | 0.747943E+10 | ||||||||
| Minimum of Months | 0.184573E+09 | 1905.18 | 7.43 | 2.20 | 0.207054E+09 | 225.86 | 7.43 | 2.20 | ||
| Maximum of Months | 0.896384E+10 | 16410.29 | 32.70 | 16.01 | 0.887150E+09 | 1409.07 | 32.70 | 16.01 |
Report: ZoneCoolingSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 16581375.90 | 933.65 | 02-JAN-18:06 | 2.38 | -1.5 | 0.228274E+09 | 653.27 | 23-JAN-14:50 | 6.70 | 2.28 |
| February | 64018780.82 | 1715.98 | 27-FEB-15:00 | 18.90 | 7.23 | 0.271782E+09 | 758.39 | 27-FEB-15:09 | 18.90 | 7.20 |
| March | 67690195.05 | 1388.24 | 14-MAR-15:17 | 12.77 | 6.04 | 0.390707E+09 | 653.26 | 24-MAR-13:39 | 2.60 | -0.9 |
| April | 0.399248E+09 | 2304.00 | 24-APR-14:02 | 17.80 | 9.77 | 0.386322E+09 | 860.68 | 07-APR-14:09 | 17.80 | 9.77 |
| May | 0.105790E+10 | 10890.37 | 19-MAY-15:00 | 28.30 | 14.88 | 0.449544E+09 | 1018.16 | 19-MAY-14:00 | 28.30 | 14.88 |
| June | 0.350813E+10 | 12916.96 | 29-JUN-15:00 | 32.20 | 14.68 | 0.322782E+09 | 882.58 | 06-JUN-14:50 | 32.20 | 14.68 |
| July | 0.457205E+10 | 15099.99 | 17-JUL-14:50 | 36.20 | 17.00 | 0.125578E+09 | 240.14 | 17-JUL-14:00 | 36.10 | 17.00 |
| August | 0.393596E+10 | 13814.44 | 10-AUG-15:00 | 33.90 | 14.71 | 0.138238E+09 | 215.75 | 10-AUG-15:09 | 33.53 | 14.51 |
| September | 0.236603E+10 | 11909.57 | 02-SEP-15:22 | 34.15 | 16.29 | 0.282982E+09 | 1000.84 | 27-SEP-14:20 | 27.60 | 14.09 |
| October | 0.950098E+09 | 8554.84 | 18-OCT-14:10 | 25.00 | 11.44 | 0.437113E+09 | 882.76 | 18-OCT-14:30 | 25.00 | 11.51 |
| November | 0.166788E+09 | 1536.04 | 03-NOV-17:30 | 13.25 | 7.17 | 0.366165E+09 | 701.79 | 03-NOV-14:09 | 13.25 | 7.17 |
| December | 21572186.27 | 1379.72 | 20-DEC-18:07 | 1.32 | -2.4 | 0.279482E+09 | 653.25 | 14-DEC-15:09 | 1.32 | -2.4 |
| Annual Sum or Average | 0.171261E+11 | 0.367897E+10 | ||||||||
| Minimum of Months | 16581375.90 | 933.65 | 1.32 | -2.4 | 0.125578E+09 | 215.75 | 1.32 | -2.4 | ||
| Maximum of Months | 0.457205E+10 | 15099.99 | 36.20 | 17.00 | 0.449544E+09 | 1018.16 | 36.10 | 17.00 |
Report: ZoneCoolingSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.172495E+10 | 1890.21 | 13-JAN-15:50 | 9.08 | 4.76 | 85517854.91 | 158.91 | 13-JAN-15:00 | 8.90 | 4.67 |
| February | 0.190917E+10 | 3267.45 | 28-FEB-15:01 | 10.68 | 4.79 | 89180523.90 | 190.56 | 28-FEB-15:00 | 11.10 | 4.84 |
| March | 0.268047E+10 | 3468.13 | 23-MAR-14:01 | 9.63 | 2.29 | 0.124248E+09 | 203.65 | 23-MAR-14:09 | 9.63 | 2.29 |
| April | 0.270147E+10 | 3999.40 | 25-APR-14:02 | 16.25 | 6.82 | 0.128862E+09 | 236.44 | 25-APR-14:00 | 17.00 | 7.46 |
| May | 0.357978E+10 | 12821.22 | 28-MAY-10:40 | 20.93 | 13.03 | 0.151446E+09 | 247.13 | 19-MAY-12:09 | 20.93 | 13.03 |
| June | 0.535384E+10 | 14169.59 | 24-JUN-10:41 | 24.13 | 15.60 | 0.104860E+09 | 247.13 | 06-JUN-14:50 | 24.13 | 15.60 |
| July | 0.437175E+10 | 13930.92 | 22-JUL-18:31 | 22.57 | 12.81 | 34072239.34 | 39.02 | 17-JUL-15:20 | 22.57 | 12.81 |
| August | 0.407181E+10 | 12921.46 | 06-AUG-22:39 | 21.30 | 11.04 | 37732399.43 | 38.89 | 08-AUG-13:50 | 28.12 | 15.77 |
| September | 0.389363E+10 | 13859.46 | 03-SEP-21:51 | 23.30 | 13.41 | 90521953.65 | 247.13 | 27-SEP-11:50 | 26.23 | 14.52 |
| October | 0.292534E+10 | 4099.32 | 20-OCT-14:01 | 13.12 | 6.68 | 0.140083E+09 | 240.44 | 18-OCT-14:09 | 13.12 | 6.68 |
| November | 0.237762E+10 | 3622.90 | 01-NOV-14:01 | 12.13 | 5.62 | 0.114431E+09 | 212.54 | 01-NOV-14:50 | 11.87 | 5.42 |
| December | 0.200979E+10 | 2245.48 | 07-DEC-15:00 | 8.30 | 2.55 | 91832464.74 | 179.15 | 07-DEC-15:09 | 8.03 | 2.51 |
| Annual Sum or Average | 0.375996E+11 | 0.119279E+10 | ||||||||
| Minimum of Months | 0.172495E+10 | 1890.21 | 8.30 | 2.29 | 34072239.34 | 38.89 | 8.03 | 2.29 | ||
| Maximum of Months | 0.535384E+10 | 14169.59 | 24.13 | 15.60 | 0.151446E+09 | 247.13 | 28.12 | 15.77 |
Report: ZoneCoolingSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.309819E+09 | 759.39 | 13-JAN-15:40 | 9.27 | 4.85 | 0.152094E+09 | 301.93 | 13-JAN-15:50 | 9.08 | 4.76 |
| February | 0.507324E+09 | 1662.53 | 28-FEB-15:01 | 10.68 | 4.79 | 0.160167E+09 | 371.90 | 28-FEB-15:00 | 11.10 | 4.84 |
| March | 0.978780E+09 | 1808.18 | 23-MAR-14:01 | 9.63 | 2.29 | 0.230220E+09 | 398.72 | 23-MAR-14:09 | 9.63 | 2.29 |
| April | 0.128768E+10 | 2256.97 | 25-APR-14:02 | 16.25 | 6.82 | 0.253889E+09 | 499.29 | 25-APR-14:00 | 17.00 | 7.46 |
| May | 0.181929E+10 | 2680.67 | 19-MAY-15:02 | 28.22 | 14.82 | 0.312696E+09 | 603.98 | 31-MAY-14:00 | 23.30 | 9.75 |
| June | 0.278406E+10 | 4794.94 | 24-JUN-16:02 | 28.22 | 12.89 | 0.236250E+09 | 611.15 | 06-JUN-14:00 | 28.22 | 12.89 |
| July | 0.268633E+10 | 8107.73 | 02-JUL-18:50 | 24.18 | 14.38 | 80317067.91 | 98.07 | 17-JUL-17:19 | 36.10 | 16.88 |
| August | 0.245189E+10 | 6125.20 | 06-AUG-16:42 | 35.10 | 15.80 | 87127706.17 | 96.92 | 07-AUG-17:40 | 31.47 | 15.44 |
| September | 0.212783E+10 | 2738.83 | 05-SEP-14:05 | 24.40 | 15.08 | 0.194096E+09 | 585.22 | 27-SEP-14:09 | 27.70 | 14.08 |
| October | 0.149849E+10 | 2369.99 | 20-OCT-14:01 | 13.12 | 6.68 | 0.287503E+09 | 519.92 | 18-OCT-14:09 | 13.12 | 6.68 |
| November | 0.934330E+09 | 1993.36 | 01-NOV-14:01 | 12.13 | 5.62 | 0.219561E+09 | 438.90 | 01-NOV-14:00 | 11.80 | 5.37 |
| December | 0.499996E+09 | 987.84 | 07-DEC-14:50 | 8.30 | 2.58 | 0.165450E+09 | 344.51 | 07-DEC-14:00 | 8.30 | 2.55 |
| Annual Sum or Average | 0.178858E+11 | 0.237937E+10 | ||||||||
| Minimum of Months | 0.309819E+09 | 759.39 | 8.30 | 2.29 | 80317067.91 | 96.92 | 8.30 | 2.29 | ||
| Maximum of Months | 0.278406E+10 | 8107.73 | 35.10 | 15.80 | 0.312696E+09 | 611.15 | 36.10 | 16.88 |
Report: ZoneCoolingSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.263485E+09 | 3942.33 | 13-JAN-15:01 | 9.82 | 5.10 | 0.482317E+09 | 945.61 | 13-JAN-15:09 | 9.82 | 5.10 |
| February | 0.108309E+10 | 23255.43 | 28-FEB-15:01 | 10.68 | 4.79 | 0.451772E+09 | 1197.57 | 27-FEB-15:09 | 10.68 | 4.79 |
| March | 0.256458E+10 | 23226.67 | 01-MAR-15:01 | 8.48 | 3.51 | 0.573775E+09 | 1197.57 | 29-MAR-14:09 | 12.80 | 4.46 |
| April | 0.399673E+10 | 23191.14 | 24-APR-14:02 | 17.80 | 9.77 | 0.551846E+09 | 1197.59 | 13-APR-14:09 | 17.80 | 9.77 |
| May | 0.636262E+10 | 23856.68 | 30-MAY-14:01 | 18.98 | 10.43 | 0.637856E+09 | 1197.63 | 19-MAY-12:09 | 18.98 | 10.43 |
| June | 0.125333E+11 | 23890.75 | 02-JUN-14:01 | 18.48 | 10.02 | 0.686678E+09 | 1197.64 | 20-JUN-12:09 | 25.87 | 16.85 |
| July | 0.113091E+11 | 26067.24 | 02-JUL-10:48 | 24.82 | 14.36 | 0.352511E+09 | 642.74 | 17-JUL-07:10 | 23.17 | 14.94 |
| August | 0.105752E+11 | 28066.93 | 06-AUG-14:02 | 34.40 | 15.37 | 0.401312E+09 | 633.24 | 07-AUG-07:10 | 22.77 | 12.39 |
| September | 0.946826E+10 | 28482.61 | 02-SEP-15:22 | 34.15 | 16.29 | 0.604708E+09 | 1246.31 | 05-SEP-07:10 | 18.98 | 12.62 |
| October | 0.568701E+10 | 23663.76 | 20-OCT-14:01 | 13.12 | 6.68 | 0.622420E+09 | 1197.61 | 18-OCT-14:09 | 13.12 | 6.68 |
| November | 0.271233E+10 | 23333.53 | 09-NOV-15:01 | 8.95 | 3.78 | 0.541876E+09 | 1197.57 | 07-NOV-15:09 | 8.95 | 3.78 |
| December | 0.900601E+09 | 4741.52 | 07-DEC-15:01 | 8.03 | 2.51 | 0.467710E+09 | 1077.86 | 07-DEC-15:09 | 8.03 | 2.51 |
| Annual Sum or Average | 0.674563E+11 | 0.637478E+10 | ||||||||
| Minimum of Months | 0.263485E+09 | 3942.33 | 8.03 | 2.51 | 0.352511E+09 | 633.24 | 8.03 | 2.51 | ||
| Maximum of Months | 0.125333E+11 | 28482.61 | 34.40 | 16.29 | 0.686678E+09 | 1246.31 | 25.87 | 16.85 |
Report: ZoneCoolingSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.254558E+10 | 5946.52 | 13-JAN-17:00 | 7.80 | 3.93 | 0.248755E+10 | 4623.37 | 13-JAN-17:10 | 7.80 | 3.93 |
| February | 0.393988E+10 | 8697.00 | 28-FEB-15:01 | 10.68 | 4.79 | 0.236077E+10 | 5324.66 | 27-FEB-16:40 | 10.68 | 4.79 |
| March | 0.651548E+10 | 9445.79 | 23-MAR-14:01 | 9.63 | 2.29 | 0.314406E+10 | 5528.14 | 16-MAR-15:30 | 9.63 | 2.29 |
| April | 0.752931E+10 | 14146.33 | 25-APR-15:30 | 17.40 | 7.58 | 0.301997E+10 | 5528.21 | 17-APR-15:20 | 17.40 | 7.58 |
| May | 0.108315E+11 | 26552.22 | 30-MAY-05:01 | 15.60 | 11.34 | 0.339221E+10 | 5528.17 | 05-MAY-15:20 | 15.60 | 11.34 |
| June | 0.166035E+11 | 27754.21 | 26-JUN-05:01 | 9.87 | 8.82 | 0.347271E+10 | 5544.91 | 20-JUN-15:30 | 9.87 | 8.82 |
| July | 0.139931E+11 | 28856.11 | 17-JUL-05:01 | 16.47 | 12.08 | 0.189790E+10 | 2036.75 | 14-JUL-19:10 | 16.47 | 12.08 |
| August | 0.126952E+11 | 28744.64 | 07-AUG-05:01 | 17.48 | 9.94 | 0.216075E+10 | 2036.76 | 15-AUG-18:40 | 18.90 | 13.11 |
| September | 0.114950E+11 | 27061.95 | 26-SEP-05:01 | 12.65 | 8.86 | 0.307307E+10 | 5528.45 | 06-SEP-15:20 | 12.65 | 8.86 |
| October | 0.789668E+10 | 13140.35 | 18-OCT-15:20 | 24.80 | 11.42 | 0.319221E+10 | 5528.16 | 06-OCT-15:20 | 24.80 | 11.42 |
| November | 0.554321E+10 | 9208.16 | 01-NOV-14:01 | 12.13 | 5.62 | 0.280433E+10 | 5527.04 | 03-NOV-16:10 | 14.23 | 7.66 |
| December | 0.359228E+10 | 6452.25 | 06-DEC-16:50 | 7.15 | 2.74 | 0.243724E+10 | 4892.29 | 06-DEC-16:00 | 6.70 | 2.38 |
| Annual Sum or Average | 0.103181E+12 | 0.334428E+11 | ||||||||
| Minimum of Months | 0.254558E+10 | 5946.52 | 7.15 | 2.29 | 0.189790E+10 | 2036.75 | 6.70 | 2.29 | ||
| Maximum of Months | 0.166035E+11 | 28856.11 | 24.80 | 12.08 | 0.347271E+10 | 5544.91 | 24.80 | 13.11 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.705716E+10 | 69832.13 | 13-JAN-06:01 | 0.50 | -2.4 | 0.639075E+10 | 8101.90 | 30-JAN-12:20 | -7.9 | -10.5 |
| February | 0.761027E+10 | 76658.59 | 14-FEB-06:01 | -4.1 | -4.9 | 0.580236E+10 | 8102.34 | 27-FEB-12:00 | 17.20 | 6.49 |
| March | 0.109246E+11 | 74216.64 | 21-MAR-05:01 | -2.7 | -4.1 | 0.671180E+10 | 8101.70 | 06-MAR-10:09 | -2.7 | -4.1 |
| April | 0.122295E+11 | 81720.50 | 28-APR-05:01 | -6.5 | -7.1 | 0.617426E+10 | 8102.45 | 24-APR-10:00 | -6.5 | -7.1 |
| May | 0.155245E+11 | 72739.03 | 09-MAY-05:01 | -2.0 | -3.5 | 0.657046E+10 | 8102.51 | 30-MAY-09:30 | 17.80 | 12.14 |
| June | 0.177360E+11 | 59068.30 | 15-JUN-05:01 | 3.17 | 1.44 | 0.611497E+10 | 8102.53 | 13-JUN-09:30 | 3.17 | 1.44 |
| July | 0.163879E+11 | 54400.83 | 12-JUL-05:01 | 6.85 | 3.54 | 0.565775E+10 | 7012.59 | 07-JUL-10:00 | 6.85 | 3.54 |
| August | 0.163018E+11 | 53514.79 | 28-AUG-05:01 | 7.12 | 4.05 | 0.599186E+10 | 7012.58 | 22-AUG-10:39 | 7.12 | 4.05 |
| September | 0.152752E+11 | 61551.86 | 18-SEP-05:11 | 3.70 | 1.36 | 0.586076E+10 | 8102.49 | 26-SEP-11:00 | 15.60 | 10.62 |
| October | 0.136414E+11 | 80783.68 | 10-OCT-05:01 | -6.1 | -6.6 | 0.642769E+10 | 8102.35 | 24-OCT-11:00 | 14.40 | 7.48 |
| November | 0.102534E+11 | 89663.70 | 21-NOV-06:01 | -9.3 | -10.6 | 0.631562E+10 | 8102.34 | 17-NOV-12:00 | -9.3 | -10.6 |
| December | 0.793761E+10 | 80641.31 | 22-DEC-06:01 | -6.1 | -6.5 | 0.626795E+10 | 8101.80 | 27-DEC-12:20 | -14.1 | -14.5 |
| Annual Sum or Average | 0.150879E+12 | 0.742862E+11 | ||||||||
| Minimum of Months | 0.705716E+10 | 53514.79 | -9.3 | -10.6 | 0.565775E+10 | 7012.58 | -14.1 | -14.5 | ||
| Maximum of Months | 0.177360E+11 | 89663.70 | 7.12 | 4.05 | 0.671180E+10 | 8102.53 | 17.80 | 12.14 |
Report: ZoneCoolingSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.107086E+11 | 48412.96 | 11-JAN-06:16 | -31.5 | -31.7 | 0.716471E+10 | 14793.10 | 13-JAN-14:00 | 10.00 | 5.18 |
| February | 0.996077E+10 | 34264.07 | 28-FEB-08:61 | -4.5 | -4.7 | 0.671345E+10 | 16256.14 | 27-FEB-14:30 | -4.5 | -4.7 |
| March | 0.139108E+11 | 31969.50 | 31-MAR-07:01 | -2.8 | -4.0 | 0.837855E+10 | 16246.51 | 14-MAR-11:30 | -2.8 | -4.0 |
| April | 0.130285E+11 | 33236.39 | 28-APR-07:01 | -3.2 | -4.7 | 0.810205E+10 | 16256.68 | 24-APR-13:00 | -3.2 | -4.7 |
| May | 0.155600E+11 | 31406.49 | 22-MAY-07:01 | -0.6 | -0.8 | 0.925642E+10 | 16259.70 | 02-MAY-13:09 | -0.6 | -0.8 |
| June | 0.190945E+11 | 71376.27 | 26-JUN-05:01 | 9.87 | 8.82 | 0.998225E+10 | 16258.91 | 13-JUN-09:00 | 9.87 | 8.82 |
| July | 0.994670E+10 | 70595.38 | 03-JUL-05:01 | 10.65 | 9.22 | 0.233045E+10 | 5989.96 | 03-JUL-16:30 | 19.75 | 14.55 |
| August | 0.963508E+10 | 70986.89 | 07-AUG-05:01 | 17.48 | 9.94 | 0.263749E+10 | 5989.37 | 21-AUG-17:00 | 25.00 | 14.47 |
| September | 0.154143E+11 | 67074.89 | 05-SEP-05:01 | 18.40 | 11.40 | 0.852713E+10 | 16260.09 | 07-SEP-10:00 | 17.80 | 16.68 |
| October | 0.143869E+11 | 32834.32 | 05-OCT-07:01 | -2.5 | -2.9 | 0.884464E+10 | 16256.33 | 16-OCT-10:30 | 18.30 | 9.50 |
| November | 0.123610E+11 | 35742.46 | 10-NOV-08:61 | -4.6 | -5.6 | 0.801959E+10 | 16248.47 | 01-NOV-11:20 | -4.6 | -5.6 |
| December | 0.104034E+11 | 30877.75 | 07-DEC-08:61 | -1.8 | -2.9 | 0.705971E+10 | 16246.71 | 06-DEC-12:30 | -1.8 | -2.9 |
| Annual Sum or Average | 0.154411E+12 | 0.870164E+11 | ||||||||
| Minimum of Months | 0.963508E+10 | 30877.75 | -31.5 | -31.7 | 0.233045E+10 | 5989.37 | -4.6 | -5.6 | ||
| Maximum of Months | 0.190945E+11 | 71376.27 | 18.40 | 11.40 | 0.998225E+10 | 16260.09 | 25.00 | 16.68 |
Report: ZoneCoolingSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.775196E+09 | 4152.11 | 13-JAN-15:50 | 9.08 | 4.76 | 0.101344E+10 | 1693.54 | 13-JAN-15:00 | 8.90 | 4.67 |
| February | 0.172790E+10 | 6649.70 | 28-FEB-15:01 | 10.68 | 4.79 | 0.945875E+09 | 1898.27 | 28-FEB-15:00 | 11.10 | 4.84 |
| March | 0.386258E+10 | 7182.19 | 23-MAR-14:01 | 9.63 | 2.29 | 0.122663E+10 | 2053.89 | 23-MAR-14:09 | 9.63 | 2.29 |
| April | 0.529790E+10 | 10020.11 | 25-APR-15:00 | 17.00 | 7.46 | 0.121406E+10 | 2059.33 | 17-APR-14:50 | 17.00 | 7.46 |
| May | 0.832014E+10 | 15817.24 | 19-MAY-15:00 | 28.30 | 14.88 | 0.137830E+10 | 2059.43 | 02-MAY-12:39 | 28.30 | 14.88 |
| June | 0.142219E+11 | 24598.34 | 21-JUN-07:03 | 18.58 | 13.69 | 0.883229E+09 | 2059.49 | 01-JUN-07:49 | 18.58 | 13.69 |
| July | 0.110401E+11 | 17473.25 | 02-JUL-10:48 | 24.82 | 14.36 | 0.302934E+09 | 341.64 | 17-JUL-07:10 | 23.17 | 14.94 |
| August | 0.984367E+10 | 14047.66 | 06-AUG-09:30 | 28.60 | 14.63 | 0.343993E+09 | 333.20 | 07-AUG-07:10 | 22.77 | 12.39 |
| September | 0.995551E+10 | 24801.52 | 05-SEP-07:02 | 18.98 | 12.62 | 0.798799E+09 | 2061.64 | 26-SEP-07:00 | 8.30 | 6.33 |
| October | 0.681953E+10 | 12182.27 | 18-OCT-14:40 | 25.00 | 11.54 | 0.132913E+10 | 2059.33 | 25-OCT-07:00 | 13.30 | 9.33 |
| November | 0.377523E+10 | 7271.08 | 09-NOV-15:01 | 8.95 | 3.78 | 0.116656E+10 | 2059.31 | 02-NOV-14:20 | 8.95 | 3.78 |
| December | 0.172164E+10 | 4620.67 | 06-DEC-15:10 | 10.82 | 5.21 | 0.990315E+09 | 1821.91 | 06-DEC-15:20 | 10.53 | 5.07 |
| Annual Sum or Average | 0.773613E+11 | 0.115933E+11 | ||||||||
| Minimum of Months | 0.775196E+09 | 4152.11 | 8.95 | 2.29 | 0.302934E+09 | 333.20 | 8.30 | 2.29 | ||
| Maximum of Months | 0.142219E+11 | 24801.52 | 28.60 | 14.88 | 0.137830E+10 | 2061.64 | 28.30 | 14.94 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.268621E+10 | 9802.88 | 11-JAN-04:21 | -28.9 |
| February | 0.103901E+10 | 9579.18 | 05-FEB-07:32 | -20.0 |
| March | 0.718403E+09 | 9838.44 | 06-MAR-06:11 | -17.1 |
| April | 85734976.08 | 8322.30 | 03-APR-05:01 | 1.02 |
| May | 0.111456E+09 | 8908.96 | 08-MAY-05:11 | -2.8 |
| June | 863212.55 | 7014.57 | 16-JUN-07:01 | 2.30 |
| July | 1886558.49 | 7038.49 | 05-JUL-07:01 | 9.50 |
| August | 5443179.13 | 7076.16 | 18-AUG-07:01 | 10.37 |
| September | 3741955.51 | 7046.90 | 13-SEP-07:01 | 5.78 |
| October | 24130959.13 | 8413.34 | 10-OCT-05:01 | -6.1 |
| November | 0.356895E+09 | 9207.80 | 27-NOV-01:32 | -15.9 |
| December | 0.142621E+10 | 9659.80 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.645999E+10 | |||
| Minimum of Months | 863212.55 | 7014.57 | -28.9 | |
| Maximum of Months | 0.268621E+10 | 9838.44 | 10.37 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.558734E+10 | 35091.70 | 11-JAN-04:21 | -28.9 |
| February | 0.177873E+10 | 34727.48 | 05-FEB-07:32 | -20.0 |
| March | 0.119752E+10 | 35501.16 | 06-MAR-06:11 | -17.1 |
| April | 77566900.54 | 28254.02 | 03-APR-06:01 | 0.78 |
| May | 0.159949E+09 | 31317.36 | 08-MAY-05:11 | -2.8 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 15.42 |
| July | 5180885.37 | 24915.12 | 05-JUL-07:01 | 9.50 |
| August | 10125195.87 | 25537.70 | 18-AUG-07:01 | 10.37 |
| September | 5884730.69 | 25320.33 | 13-SEP-07:01 | 5.78 |
| October | 30699370.40 | 28898.80 | 10-OCT-06:01 | -6.1 |
| November | 0.560976E+09 | 32138.90 | 27-NOV-06:11 | -14.4 |
| December | 0.264282E+10 | 34925.22 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.120568E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -28.9 | |
| Maximum of Months | 0.558734E+10 | 35501.16 | 15.42 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.379953E+10 | 8112.12 | 09-JAN-06:31 | -27.2 |
| February | 0.175376E+10 | 8036.01 | 05-FEB-08:12 | -20.2 |
| March | 0.961281E+09 | 8126.46 | 06-MAR-06:11 | -17.1 |
| April | 72583092.49 | 6762.52 | 03-APR-06:01 | 0.78 |
| May | 0.149301E+09 | 7295.43 | 01-MAY-05:12 | -0.4 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 15.42 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
| August | 972298.13 | 6263.74 | 18-AUG-07:01 | 10.37 |
| September | 709145.88 | 6091.57 | 20-SEP-07:01 | 4.78 |
| October | 32783697.24 | 6880.48 | 10-OCT-06:01 | -6.1 |
| November | 0.700762E+09 | 7520.76 | 13-NOV-06:11 | -5.8 |
| December | 0.213731E+10 | 8019.97 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.960899E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -27.2 | |
| Maximum of Months | 0.379953E+10 | 8126.46 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.342127E+10 | 9188.30 | 11-JAN-04:21 | -28.9 |
| February | 0.151001E+10 | 9017.81 | 05-FEB-08:12 | -20.2 |
| March | 0.102787E+10 | 9248.56 | 06-MAR-06:11 | -17.1 |
| April | 0.146975E+09 | 8224.04 | 03-APR-05:01 | 1.02 |
| May | 0.131661E+09 | 8415.35 | 08-MAY-05:11 | -2.8 |
| June | 890748.91 | 6691.23 | 16-JUN-07:01 | 2.30 |
| July | 2919467.95 | 6707.06 | 05-JUL-07:01 | 9.50 |
| August | 8988454.67 | 6732.68 | 18-AUG-07:01 | 10.37 |
| September | 7225159.73 | 7081.36 | 19-SEP-06:11 | 2.20 |
| October | 45321443.27 | 8176.82 | 10-OCT-05:01 | -6.1 |
| November | 0.589999E+09 | 8737.23 | 13-NOV-06:11 | -5.8 |
| December | 0.194588E+10 | 9100.26 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.883901E+10 | |||
| Minimum of Months | 890748.91 | 6691.23 | -28.9 | |
| Maximum of Months | 0.342127E+10 | 9248.56 | 10.37 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.777899E+10 | 32798.09 | 09-JAN-06:31 | -27.2 |
| February | 0.289832E+10 | 32588.71 | 05-FEB-08:12 | -20.2 |
| March | 0.186026E+10 | 33325.22 | 06-MAR-06:11 | -17.1 |
| April | 0.148059E+09 | 26770.30 | 10-APR-06:11 | 3.90 |
| May | 0.184508E+09 | 29679.13 | 08-MAY-05:11 | -2.8 |
| June | 482512.00 | 8041.87 | 16-JUN-07:01 | 2.30 |
| July | 11370871.96 | 24058.89 | 05-JUL-07:01 | 9.50 |
| August | 25930815.19 | 24182.00 | 18-AUG-07:01 | 10.37 |
| September | 10781812.97 | 24048.14 | 13-SEP-07:01 | 5.78 |
| October | 59650050.58 | 27244.38 | 10-OCT-06:01 | -6.1 |
| November | 0.967821E+09 | 31433.31 | 13-NOV-06:11 | -5.8 |
| December | 0.387982E+10 | 32781.28 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.178260E+11 | |||
| Minimum of Months | 482512.00 | 8041.87 | -27.2 | |
| Maximum of Months | 0.777899E+10 | 33325.22 | 10.37 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.275569E+10 | 9744.72 | 11-JAN-04:21 | -28.9 |
| February | 0.104821E+10 | 9525.46 | 05-FEB-06:12 | -20.0 |
| March | 0.724096E+09 | 9782.38 | 06-MAR-06:11 | -17.1 |
| April | 87439142.70 | 8289.63 | 03-APR-05:01 | 1.02 |
| May | 0.113807E+09 | 8866.00 | 08-MAY-05:11 | -2.8 |
| June | 960994.26 | 6991.98 | 16-JUN-07:01 | 2.30 |
| July | 2117503.73 | 7006.88 | 05-JUL-07:01 | 9.50 |
| August | 5796180.40 | 7042.36 | 18-AUG-07:01 | 10.37 |
| September | 3797711.61 | 7013.21 | 13-SEP-07:01 | 5.78 |
| October | 24364690.24 | 8375.60 | 10-OCT-05:01 | -6.1 |
| November | 0.368065E+09 | 9163.52 | 27-NOV-01:32 | -15.9 |
| December | 0.149637E+10 | 9606.71 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.663070E+10 | |||
| Minimum of Months | 960994.26 | 6991.98 | -28.9 | |
| Maximum of Months | 0.275569E+10 | 9782.38 | 10.37 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.564060E+10 | 34635.29 | 11-JAN-04:21 | -28.9 |
| February | 0.173469E+10 | 34331.76 | 05-FEB-07:32 | -20.0 |
| March | 0.117918E+10 | 35109.04 | 06-MAR-06:11 | -17.1 |
| April | 74477634.65 | 27966.48 | 03-APR-06:01 | 0.78 |
| May | 0.154993E+09 | 30941.93 | 08-MAY-05:11 | -2.8 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 15.42 |
| July | 5922696.21 | 24745.26 | 05-JUL-07:01 | 9.50 |
| August | 10499597.34 | 25284.53 | 18-AUG-07:01 | 10.37 |
| September | 5792513.86 | 24981.09 | 13-SEP-07:01 | 5.78 |
| October | 30470217.33 | 28607.82 | 10-OCT-06:01 | -6.1 |
| November | 0.568590E+09 | 31803.86 | 27-NOV-06:11 | -14.4 |
| December | 0.273241E+10 | 34539.83 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.121376E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -28.9 | |
| Maximum of Months | 0.564060E+10 | 35109.04 | 15.42 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.386861E+10 | 8093.58 | 09-JAN-06:31 | -27.2 |
| February | 0.176531E+10 | 8017.28 | 05-FEB-08:12 | -20.2 |
| March | 0.968588E+09 | 8107.12 | 06-MAR-06:11 | -17.1 |
| April | 72488198.14 | 6748.21 | 03-APR-06:01 | 0.78 |
| May | 0.149577E+09 | 7277.42 | 01-MAY-05:12 | -0.4 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 15.42 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
| August | 972641.13 | 6253.02 | 18-AUG-07:01 | 10.37 |
| September | 718900.24 | 6080.73 | 20-SEP-07:01 | 4.78 |
| October | 33127656.14 | 6866.49 | 10-OCT-06:01 | -6.1 |
| November | 0.721055E+09 | 7539.14 | 13-NOV-06:11 | -5.8 |
| December | 0.222572E+10 | 8000.74 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.980616E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -27.2 | |
| Maximum of Months | 0.386861E+10 | 8107.12 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.342721E+10 | 9192.64 | 11-JAN-04:21 | -28.9 |
| February | 0.151100E+10 | 9021.68 | 05-FEB-08:12 | -20.2 |
| March | 0.102848E+10 | 9253.33 | 06-MAR-06:11 | -17.1 |
| April | 0.146800E+09 | 8227.55 | 03-APR-05:01 | 1.02 |
| May | 0.131333E+09 | 8419.28 | 08-MAY-05:11 | -2.8 |
| June | 863991.52 | 6694.75 | 16-JUN-07:01 | 2.30 |
| July | 2904858.39 | 6709.47 | 05-JUL-07:01 | 9.50 |
| August | 9006085.01 | 6736.43 | 18-AUG-07:01 | 10.37 |
| September | 7240654.35 | 7085.72 | 19-SEP-06:11 | 2.20 |
| October | 45457009.42 | 8180.76 | 10-OCT-05:01 | -6.1 |
| November | 0.593408E+09 | 8744.86 | 13-NOV-06:11 | -5.8 |
| December | 0.195377E+10 | 9104.63 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.885748E+10 | |||
| Minimum of Months | 863991.52 | 6694.75 | -28.9 | |
| Maximum of Months | 0.342721E+10 | 9253.33 | 10.37 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.780043E+10 | 32780.30 | 09-JAN-06:31 | -27.2 |
| February | 0.290060E+10 | 32570.37 | 05-FEB-08:12 | -20.2 |
| March | 0.186225E+10 | 33306.69 | 06-MAR-06:11 | -17.1 |
| April | 0.147953E+09 | 26759.10 | 10-APR-06:11 | 3.90 |
| May | 0.183875E+09 | 29661.26 | 08-MAY-05:11 | -2.8 |
| June | 453106.08 | 7551.77 | 16-JUN-07:01 | 2.30 |
| July | 11343632.34 | 24051.92 | 05-JUL-07:01 | 9.50 |
| August | 26000238.08 | 24173.37 | 18-AUG-07:01 | 10.37 |
| September | 10773450.01 | 24037.73 | 13-SEP-07:01 | 5.78 |
| October | 59777075.49 | 27231.89 | 10-OCT-06:01 | -6.1 |
| November | 0.975773E+09 | 31441.32 | 13-NOV-06:11 | -5.8 |
| December | 0.390356E+10 | 32762.94 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.178828E+11 | |||
| Minimum of Months | 453106.08 | 7551.77 | -27.2 | |
| Maximum of Months | 0.780043E+10 | 33306.69 | 10.37 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.272888E+10 | 9750.97 | 11-JAN-04:21 | -28.9 |
| February | 0.104368E+10 | 9531.45 | 05-FEB-07:32 | -20.0 |
| March | 0.718266E+09 | 9788.62 | 06-MAR-06:11 | -17.1 |
| April | 83306668.17 | 8276.37 | 03-APR-05:01 | 1.02 |
| May | 0.109916E+09 | 8862.04 | 08-MAY-05:11 | -2.8 |
| June | 883189.17 | 6989.65 | 16-JUN-07:01 | 2.30 |
| July | 1861743.61 | 7009.07 | 05-JUL-07:01 | 9.50 |
| August | 5329064.03 | 7046.48 | 18-AUG-07:01 | 10.37 |
| September | 3527269.09 | 7016.56 | 13-SEP-07:01 | 5.78 |
| October | 23313735.40 | 8345.94 | 10-OCT-05:01 | -6.1 |
| November | 0.360219E+09 | 9161.59 | 27-NOV-01:32 | -15.9 |
| December | 0.147201E+10 | 9611.78 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.655120E+10 | |||
| Minimum of Months | 883189.17 | 6989.65 | -28.9 | |
| Maximum of Months | 0.272888E+10 | 9788.62 | 10.37 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.556523E+10 | 34763.28 | 11-JAN-04:21 | -28.9 |
| February | 0.173370E+10 | 34466.71 | 05-FEB-07:32 | -20.0 |
| March | 0.117627E+10 | 35250.64 | 06-MAR-06:11 | -17.1 |
| April | 71314388.85 | 28060.77 | 03-APR-06:01 | 0.78 |
| May | 0.149356E+09 | 30942.93 | 08-MAY-05:11 | -2.8 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 15.42 |
| July | 4442910.72 | 24732.50 | 05-JUL-07:01 | 9.50 |
| August | 9293912.47 | 25367.06 | 18-AUG-07:01 | 10.37 |
| September | 5103648.63 | 24958.42 | 13-SEP-07:01 | 5.78 |
| October | 28700190.17 | 28692.09 | 10-OCT-06:01 | -6.1 |
| November | 0.553524E+09 | 31907.00 | 27-NOV-06:11 | -14.4 |
| December | 0.268638E+10 | 34666.46 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.119833E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -28.9 | |
| Maximum of Months | 0.556523E+10 | 35250.64 | 15.42 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.380315E+10 | 8142.54 | 09-JAN-06:31 | -27.2 |
| February | 0.171965E+10 | 8066.26 | 05-FEB-08:12 | -20.2 |
| March | 0.913348E+09 | 8156.53 | 06-MAR-06:11 | -17.1 |
| April | 55284158.48 | 6748.97 | 03-APR-06:01 | 0.78 |
| May | 0.129902E+09 | 7280.71 | 01-MAY-05:12 | -0.4 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 15.42 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
| August | 775620.83 | 6238.40 | 18-AUG-07:01 | 10.37 |
| September | 132133.87 | 2202.23 | 20-SEP-07:01 | 4.78 |
| October | 26791742.74 | 6845.45 | 10-OCT-06:01 | -6.1 |
| November | 0.676926E+09 | 7545.45 | 13-NOV-06:11 | -5.8 |
| December | 0.215217E+10 | 8049.12 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.947813E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -27.2 | |
| Maximum of Months | 0.380315E+10 | 8156.53 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.342759E+10 | 9248.99 | 11-JAN-04:21 | -28.9 |
| February | 0.150694E+10 | 9073.83 | 05-FEB-08:12 | -20.2 |
| March | 0.101577E+10 | 9308.82 | 06-MAR-06:11 | -17.1 |
| April | 0.139097E+09 | 8248.80 | 03-APR-05:01 | 1.02 |
| May | 0.123816E+09 | 8455.03 | 08-MAY-05:11 | -2.8 |
| June | 538216.14 | 6724.54 | 16-JUN-07:01 | 2.30 |
| July | 2388521.49 | 6739.88 | 05-JUL-07:01 | 9.50 |
| August | 8374963.68 | 6767.80 | 18-AUG-07:01 | 10.37 |
| September | 6619360.28 | 7091.84 | 19-SEP-06:11 | 2.20 |
| October | 43545802.79 | 8193.22 | 10-OCT-05:01 | -6.1 |
| November | 0.588561E+09 | 8794.16 | 13-NOV-06:11 | -5.8 |
| December | 0.195628E+10 | 9159.06 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.881952E+10 | |||
| Minimum of Months | 538216.14 | 6724.54 | -28.9 | |
| Maximum of Months | 0.342759E+10 | 9308.82 | 10.37 |
Report: ZoneHeatingSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.531895E+10 | 21881.27 | 09-JAN-06:31 | -27.2 |
| February | 0.198118E+10 | 21726.07 | 05-FEB-08:12 | -20.2 |
| March | 0.125660E+10 | 22216.79 | 06-MAR-06:11 | -17.1 |
| April | 94299582.66 | 17838.18 | 28-APR-06:01 | -5.2 |
| May | 0.116955E+09 | 19723.31 | 08-MAY-05:11 | -2.8 |
| June | 63676.21 | 1061.27 | 16-JUN-07:01 | 2.30 |
| July | 5084216.86 | 15966.79 | 05-JUL-07:01 | 9.50 |
| August | 15485756.07 | 16147.51 | 18-AUG-07:01 | 10.37 |
| September | 6367492.36 | 16060.91 | 13-SEP-07:01 | 5.78 |
| October | 38332626.39 | 18166.57 | 10-OCT-06:01 | -6.1 |
| November | 0.665950E+09 | 20979.60 | 13-NOV-06:11 | -5.8 |
| December | 0.268584E+10 | 21861.38 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.121851E+11 | |||
| Minimum of Months | 63676.21 | 1061.27 | -27.2 | |
| Maximum of Months | 0.531895E+10 | 22216.79 | 10.37 |
Report: ZoneHeatingSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.188073E+10 | 11233.03 | 09-JAN-06:31 | -27.2 |
| February | 0.633831E+09 | 11135.66 | 05-FEB-08:12 | -20.2 |
| March | 0.455458E+09 | 11393.30 | 06-MAR-06:11 | -17.1 |
| April | 22795165.92 | 9103.91 | 03-APR-06:01 | 0.78 |
| May | 36968583.46 | 9788.47 | 08-MAY-05:11 | -2.8 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 15.42 |
| July | 169896.04 | 2831.60 | 05-JUL-07:01 | 9.50 |
| August | 1638867.20 | 8194.36 | 18-AUG-07:01 | 10.37 |
| September | 985400.87 | 6738.01 | 19-SEP-07:01 | 2.48 |
| October | 10395887.48 | 9296.49 | 10-OCT-06:01 | -6.1 |
| November | 0.196674E+09 | 10638.07 | 13-NOV-06:11 | -5.8 |
| December | 0.879507E+09 | 11211.34 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.411916E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -27.2 | |
| Maximum of Months | 0.188073E+10 | 11393.30 | 15.42 |
Report: ZoneHeatingSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.104959E+11 | 17833.28 | 09-JAN-06:31 | -27.2 |
| February | 0.476472E+10 | 17737.08 | 05-FEB-08:12 | -20.2 |
| March | 0.202320E+10 | 17890.67 | 06-MAR-06:11 | -17.1 |
| April | 49752776.66 | 14901.93 | 03-APR-06:01 | 0.78 |
| May | 93573676.53 | 15700.45 | 01-MAY-06:01 | 0.10 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 15.42 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
| October | 51163704.53 | 15242.38 | 10-OCT-06:01 | -6.1 |
| November | 0.202373E+10 | 16897.62 | 27-NOV-06:11 | -14.4 |
| December | 0.611695E+10 | 17880.73 | 31-DEC-05:02 | -24.7 |
| Annual Sum or Average | 0.256190E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -27.2 | |
| Maximum of Months | 0.104959E+11 | 17890.67 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.133788E+11 | 22255.28 | 11-JAN-07:10 | -27.2 |
| February | 0.871069E+10 | 20189.81 | 01-FEB-07:10 | -24.9 |
| March | 0.801085E+10 | 18624.97 | 06-MAR-07:10 | -19.7 |
| April | 0.419678E+10 | 15205.11 | 28-APR-06:10 | -5.2 |
| May | 0.358983E+10 | 14337.45 | 08-MAY-06:10 | -2.7 |
| June | 0.104241E+10 | 12459.64 | 16-JUN-06:10 | 2.70 |
| July | 0.378692E+09 | 10541.66 | 05-JUL-06:10 | 9.40 |
| August | 0.864164E+09 | 11094.15 | 18-AUG-06:10 | 8.17 |
| September | 0.161013E+10 | 12704.89 | 19-SEP-06:10 | 2.20 |
| October | 0.292873E+10 | 15511.12 | 10-OCT-06:10 | -6.1 |
| November | 0.602348E+10 | 17104.22 | 27-NOV-07:10 | -13.5 |
| December | 0.995204E+10 | 21255.64 | 29-DEC-08:00 | -27.8 |
| Annual Sum or Average | 0.606866E+11 | |||
| Minimum of Months | 0.378692E+09 | 10541.66 | -27.8 | |
| Maximum of Months | 0.133788E+11 | 22255.28 | 9.40 |
Report: ZoneHeatingSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.159481E+09 | 8950.09 | 09-JAN-06:31 | -27.2 |
| February | 877222.71 | 494.06 | 05-FEB-21:33 | -15.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -3.0 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 15.42 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 4.98 |
| December | 41709380.71 | 6313.08 | 31-DEC-07:41 | -27.9 |
| Annual Sum or Average | 0.202068E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -27.9 | |
| Maximum of Months | 0.159481E+09 | 8950.09 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.174614E+10 | 8604.19 | 09-JAN-06:31 | -27.2 |
| February | 0.498062E+09 | 8378.29 | 05-FEB-08:12 | -20.2 |
| March | 0.235679E+09 | 8467.48 | 06-MAR-06:11 | -17.1 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 2.68 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | -1.1 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 15.42 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 11.57 |
| November | 48116934.58 | 7879.95 | 27-NOV-06:11 | -14.4 |
| December | 0.871379E+09 | 8456.73 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.339937E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -27.2 | |
| Maximum of Months | 0.174614E+10 | 8604.19 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.868504E+10 | 25417.35 | 11-JAN-04:21 | -28.9 |
| February | 0.331368E+10 | 25154.06 | 05-FEB-07:32 | -20.0 |
| March | 0.155888E+10 | 25509.35 | 06-MAR-06:11 | -17.1 |
| April | 53863694.43 | 20678.42 | 03-APR-06:01 | 0.78 |
| May | 0.104340E+09 | 22096.92 | 08-MAY-05:11 | -2.8 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 15.42 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
| October | 25116212.60 | 21274.12 | 10-OCT-06:01 | -6.1 |
| November | 0.110485E+10 | 23319.46 | 27-NOV-06:11 | -14.4 |
| December | 0.453848E+10 | 25259.06 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.193843E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -28.9 | |
| Maximum of Months | 0.868504E+10 | 25509.35 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.382657E+10 | 23140.87 | 09-JAN-05:51 | -27.2 |
| February | 0.131753E+10 | 22823.65 | 05-FEB-07:32 | -20.0 |
| March | 0.633800E+09 | 23145.88 | 06-MAR-06:11 | -17.1 |
| April | 4211307.30 | 16071.43 | 03-APR-05:01 | 1.02 |
| May | 41205281.37 | 18044.54 | 08-MAY-05:11 | -2.8 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 15.42 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
| October | 18489117.68 | 17175.97 | 10-OCT-05:01 | -6.1 |
| November | 0.463913E+09 | 21134.88 | 27-NOV-06:11 | -14.4 |
| December | 0.184611E+10 | 23077.35 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.815182E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -27.2 | |
| Maximum of Months | 0.382657E+10 | 23145.88 | 19.45 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.109050E+09 | 33899.81 | 30-JAN-07:01 | -14.9 |
| February | 11031907.60 | 2801.52 | 06-FEB-07:12 | 0.40 |
| March | 7512140.93 | 3396.87 | 10-MAR-07:02 | -3.8 |
| April | 1416870.25 | 3793.18 | 18-APR-06:02 | 2.30 |
| May | 729366.82 | 3786.74 | 05-MAY-06:02 | 3.27 |
| June | 240455.55 | 3772.06 | 19-JUN-06:02 | 12.77 |
| July | 1357240.14 | 5233.63 | 26-JUL-05:37 | 19.80 |
| August | 1838006.20 | 3977.28 | 07-AUG-05:37 | 18.33 |
| September | 319181.56 | 3479.56 | 20-SEP-06:02 | 3.48 |
| October | 2144985.33 | 5007.07 | 18-OCT-05:44 | 11.02 |
| November | 784474.72 | 3737.20 | 17-NOV-07:02 | 12.63 |
| December | 11422140.97 | 2811.72 | 28-DEC-07:12 | -22.8 |
| Annual Sum or Average | 0.147847E+09 | |||
| Minimum of Months | 240455.55 | 2801.52 | -22.8 | |
| Maximum of Months | 0.109050E+09 | 33899.81 | 19.80 |
Report: ZoneHeatingSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.588958E+10 | 114978.19 | 30-JAN-07:01 | -14.9 |
| February | 0.211597E+10 | 95106.05 | 21-FEB-06:01 | 6.70 |
| March | 0.157182E+10 | 87107.68 | 09-MAR-06:01 | 2.30 |
| April | 0.420639E+09 | 85061.73 | 03-APR-05:01 | 1.02 |
| May | 0.360876E+09 | 85128.44 | 01-MAY-05:01 | -0.5 |
| June | 11262445.75 | 5241.56 | 06-JUN-06:02 | 14.60 |
| July | 4487488.38 | 6011.46 | 26-JUL-05:44 | 19.90 |
| August | 35760925.12 | 11731.49 | 11-AUG-05:04 | 18.80 |
| September | 83725011.44 | 5543.87 | 19-SEP-07:04 | 2.48 |
| October | 0.280421E+09 | 75700.68 | 10-OCT-05:01 | -6.1 |
| November | 0.943886E+09 | 83395.07 | 29-NOV-06:01 | -1.1 |
| December | 0.260426E+10 | 90655.86 | 19-DEC-06:01 | 3.80 |
| Annual Sum or Average | 0.143227E+11 | |||
| Minimum of Months | 4487488.38 | 5241.56 | -14.9 | |
| Maximum of Months | 0.588958E+10 | 114978.19 | 19.90 |
Report: ZoneHeatingSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.667129E+10 | 24672.44 | 11-JAN-04:21 | -28.9 |
| February | 0.235670E+10 | 24529.29 | 05-FEB-07:32 | -20.0 |
| March | 0.121406E+10 | 24997.60 | 06-MAR-06:11 | -17.1 |
| April | 29966098.69 | 20140.00 | 03-APR-06:01 | 0.78 |
| May | 53446557.69 | 20932.04 | 01-MAY-05:11 | -0.4 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 15.42 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 19.45 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 18.90 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 18.43 |
| October | 14059686.52 | 20384.33 | 10-OCT-06:01 | -6.1 |
| November | 0.685321E+09 | 23370.72 | 13-NOV-06:11 | -5.8 |
| December | 0.326000E+10 | 24664.85 | 31-DEC-03:42 | -24.9 |
| Annual Sum or Average | 0.142848E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -28.9 | |
| Maximum of Months | 0.667129E+10 | 24997.60 | 19.45 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.130469E+10 | 947.12 | 02-JAN-07:10 | 0.892986E+09 | 678.98 | 02-JAN-08:09 |
| February | 0.117967E+10 | 947.12 | 01-FEB-07:10 | 0.807077E+09 | 678.98 | 01-FEB-08:09 |
| March | 0.138135E+10 | 947.12 | 01-MAR-07:10 | 0.924571E+09 | 678.98 | 01-MAR-08:09 |
| April | 0.125024E+10 | 947.12 | 03-APR-06:10 | 0.859085E+09 | 678.98 | 03-APR-07:10 |
| May | 0.134302E+10 | 947.12 | 01-MAY-06:10 | 0.908779E+09 | 678.98 | 01-MAY-07:10 |
| June | 0.132690E+10 | 947.12 | 01-JUN-06:10 | 0.890455E+09 | 678.98 | 01-JUN-07:10 |
| July | 0.793150E+09 | 526.18 | 03-JUL-07:10 | 0.543864E+09 | 357.36 | 03-JUL-07:10 |
| August | 0.837162E+09 | 526.18 | 01-AUG-07:10 | 0.565300E+09 | 357.36 | 01-AUG-07:10 |
| September | 0.122658E+10 | 947.12 | 05-SEP-06:10 | 0.845480E+09 | 678.98 | 05-SEP-07:10 |
| October | 0.130469E+10 | 947.12 | 02-OCT-06:10 | 0.892986E+09 | 678.98 | 02-OCT-07:10 |
| November | 0.128857E+10 | 947.12 | 01-NOV-06:10 | 0.874878E+09 | 678.98 | 01-NOV-07:10 |
| December | 0.126636E+10 | 947.12 | 01-DEC-07:10 | 0.877193E+09 | 678.98 | 01-DEC-08:09 |
| Annual Sum or Average | 0.145024E+11 | 0.988265E+10 | ||||
| Minimum of Months | 0.793150E+09 | 526.18 | 0.543864E+09 | 357.36 | ||
| Maximum of Months | 0.138135E+10 | 947.12 | 0.924571E+09 | 678.98 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.130469E+10 | 947.12 | 02-JAN-07:10 | 0.892986E+09 | 678.98 | 02-JAN-08:09 |
| February | 0.117967E+10 | 947.12 | 01-FEB-07:10 | 0.807077E+09 | 678.98 | 01-FEB-08:09 |
| March | 0.138135E+10 | 947.12 | 01-MAR-07:10 | 0.924571E+09 | 678.98 | 01-MAR-08:09 |
| April | 0.125024E+10 | 947.12 | 03-APR-06:10 | 0.859085E+09 | 678.98 | 03-APR-07:10 |
| May | 0.134302E+10 | 947.12 | 01-MAY-06:10 | 0.908779E+09 | 678.98 | 01-MAY-07:10 |
| June | 0.132690E+10 | 947.12 | 01-JUN-06:10 | 0.890455E+09 | 678.98 | 01-JUN-07:10 |
| July | 0.793150E+09 | 526.18 | 03-JUL-07:10 | 0.543864E+09 | 357.36 | 03-JUL-07:10 |
| August | 0.837162E+09 | 526.18 | 01-AUG-07:10 | 0.565300E+09 | 357.36 | 01-AUG-07:10 |
| September | 0.122658E+10 | 947.12 | 05-SEP-06:10 | 0.845480E+09 | 678.98 | 05-SEP-07:10 |
| October | 0.130469E+10 | 947.12 | 02-OCT-06:10 | 0.892986E+09 | 678.98 | 02-OCT-07:10 |
| November | 0.128857E+10 | 947.12 | 01-NOV-06:10 | 0.874878E+09 | 678.98 | 01-NOV-07:10 |
| December | 0.126636E+10 | 947.12 | 01-DEC-07:10 | 0.877193E+09 | 678.98 | 01-DEC-08:09 |
| Annual Sum or Average | 0.145024E+11 | 0.988265E+10 | ||||
| Minimum of Months | 0.793150E+09 | 526.18 | 0.543864E+09 | 357.36 | ||
| Maximum of Months | 0.138135E+10 | 947.12 | 0.924571E+09 | 678.98 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.891175E+10 | 6469.32 | 02-JAN-07:10 | 0.831942E+10 | 6325.65 | 02-JAN-08:09 |
| February | 0.805776E+10 | 6469.32 | 01-FEB-07:10 | 0.751906E+10 | 6325.65 | 01-FEB-08:09 |
| March | 0.943539E+10 | 6469.32 | 01-MAR-07:10 | 0.861368E+10 | 6325.65 | 01-MAR-08:09 |
| April | 0.853981E+10 | 6469.32 | 03-APR-06:10 | 0.800359E+10 | 6325.65 | 03-APR-07:10 |
| May | 0.917357E+10 | 6469.32 | 01-MAY-06:10 | 0.846655E+10 | 6325.65 | 01-MAY-07:10 |
| June | 0.906345E+10 | 6469.32 | 01-JUN-06:10 | 0.829584E+10 | 6325.65 | 01-JUN-07:10 |
| July | 0.541765E+10 | 3594.07 | 03-JUL-07:10 | 0.506686E+10 | 3329.29 | 03-JUL-07:10 |
| August | 0.571827E+10 | 3594.07 | 01-AUG-07:10 | 0.526656E+10 | 3329.29 | 01-AUG-07:10 |
| September | 0.837820E+10 | 6469.32 | 05-SEP-06:10 | 0.787684E+10 | 6325.65 | 05-SEP-07:10 |
| October | 0.891175E+10 | 6469.32 | 02-OCT-06:10 | 0.831942E+10 | 6325.65 | 02-OCT-07:10 |
| November | 0.880163E+10 | 6469.32 | 01-NOV-06:10 | 0.815072E+10 | 6325.65 | 01-NOV-07:10 |
| December | 0.864992E+10 | 6469.32 | 01-DEC-07:10 | 0.817229E+10 | 6325.65 | 01-DEC-08:09 |
| Annual Sum or Average | 0.990591E+11 | 0.920708E+11 | ||||
| Minimum of Months | 0.541765E+10 | 3594.07 | 0.506686E+10 | 3329.29 | ||
| Maximum of Months | 0.943539E+10 | 6469.32 | 0.861368E+10 | 6325.65 |
Report: ZoneElectricSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.130469E+10 | 947.12 | 02-JAN-07:10 | 0.892986E+09 | 678.98 | 02-JAN-08:09 |
| February | 0.117967E+10 | 947.12 | 01-FEB-07:10 | 0.807077E+09 | 678.98 | 01-FEB-08:09 |
| March | 0.138135E+10 | 947.12 | 01-MAR-07:10 | 0.924571E+09 | 678.98 | 01-MAR-08:09 |
| April | 0.125024E+10 | 947.12 | 03-APR-06:10 | 0.859085E+09 | 678.98 | 03-APR-07:10 |
| May | 0.134302E+10 | 947.12 | 01-MAY-06:10 | 0.908779E+09 | 678.98 | 01-MAY-07:10 |
| June | 0.132690E+10 | 947.12 | 01-JUN-06:10 | 0.890455E+09 | 678.98 | 01-JUN-07:10 |
| July | 0.793150E+09 | 526.18 | 03-JUL-07:10 | 0.543864E+09 | 357.36 | 03-JUL-07:10 |
| August | 0.837162E+09 | 526.18 | 01-AUG-07:10 | 0.565300E+09 | 357.36 | 01-AUG-07:10 |
| September | 0.122658E+10 | 947.12 | 05-SEP-06:10 | 0.845480E+09 | 678.98 | 05-SEP-07:10 |
| October | 0.130469E+10 | 947.12 | 02-OCT-06:10 | 0.892986E+09 | 678.98 | 02-OCT-07:10 |
| November | 0.128857E+10 | 947.12 | 01-NOV-06:10 | 0.874878E+09 | 678.98 | 01-NOV-07:10 |
| December | 0.126636E+10 | 947.12 | 01-DEC-07:10 | 0.877193E+09 | 678.98 | 01-DEC-08:09 |
| Annual Sum or Average | 0.145024E+11 | 0.988265E+10 | ||||
| Minimum of Months | 0.793150E+09 | 526.18 | 0.543864E+09 | 357.36 | ||
| Maximum of Months | 0.138135E+10 | 947.12 | 0.924571E+09 | 678.98 |
Report: ZoneElectricSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.184961E+10 | 1342.69 | 02-JAN-07:10 | 0.172667E+10 | 1312.87 | 02-JAN-08:09 |
| February | 0.167237E+10 | 1342.69 | 01-FEB-07:10 | 0.156056E+10 | 1312.87 | 01-FEB-08:09 |
| March | 0.195829E+10 | 1342.69 | 01-MAR-07:10 | 0.178775E+10 | 1312.87 | 01-MAR-08:09 |
| April | 0.177241E+10 | 1342.69 | 03-APR-06:10 | 0.166112E+10 | 1312.87 | 03-APR-07:10 |
| May | 0.190395E+10 | 1342.69 | 01-MAY-06:10 | 0.175721E+10 | 1312.87 | 01-MAY-07:10 |
| June | 0.188109E+10 | 1342.69 | 01-JUN-06:10 | 0.172178E+10 | 1312.87 | 01-JUN-07:10 |
| July | 0.112442E+10 | 745.94 | 03-JUL-07:10 | 0.105161E+10 | 690.98 | 03-JUL-07:10 |
| August | 0.118681E+10 | 745.94 | 01-AUG-07:10 | 0.109306E+10 | 690.98 | 01-AUG-07:10 |
| September | 0.173887E+10 | 1342.69 | 05-SEP-06:10 | 0.163481E+10 | 1312.87 | 05-SEP-07:10 |
| October | 0.184961E+10 | 1342.69 | 02-OCT-06:10 | 0.172667E+10 | 1312.87 | 02-OCT-07:10 |
| November | 0.182675E+10 | 1342.69 | 01-NOV-06:10 | 0.169166E+10 | 1312.87 | 01-NOV-07:10 |
| December | 0.179527E+10 | 1342.69 | 01-DEC-07:10 | 0.169614E+10 | 1312.87 | 01-DEC-08:09 |
| Annual Sum or Average | 0.205594E+11 | 0.191090E+11 | ||||
| Minimum of Months | 0.112442E+10 | 745.94 | 0.105161E+10 | 690.98 | ||
| Maximum of Months | 0.195829E+10 | 1342.69 | 0.178775E+10 | 1312.87 |
Report: ZoneElectricSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.588512E+10 | 4272.19 | 02-JAN-07:10 | 0.549396E+10 | 4177.31 | 02-JAN-08:09 |
| February | 0.532117E+10 | 4272.19 | 01-FEB-07:10 | 0.496542E+10 | 4177.31 | 01-FEB-08:09 |
| March | 0.623092E+10 | 4272.19 | 01-MAR-07:10 | 0.568828E+10 | 4177.31 | 01-MAR-08:09 |
| April | 0.563950E+10 | 4272.19 | 03-APR-06:10 | 0.528539E+10 | 4177.31 | 03-APR-07:10 |
| May | 0.605802E+10 | 4272.19 | 01-MAY-06:10 | 0.559112E+10 | 4177.31 | 01-MAY-07:10 |
| June | 0.598530E+10 | 4272.19 | 01-JUN-06:10 | 0.547839E+10 | 4177.31 | 01-JUN-07:10 |
| July | 0.357769E+10 | 2373.44 | 03-JUL-07:10 | 0.334604E+10 | 2198.59 | 03-JUL-07:10 |
| August | 0.377621E+10 | 2373.44 | 01-AUG-07:10 | 0.347792E+10 | 2198.59 | 01-AUG-07:10 |
| September | 0.553277E+10 | 4272.19 | 05-SEP-06:10 | 0.520168E+10 | 4177.31 | 05-SEP-07:10 |
| October | 0.588512E+10 | 4272.19 | 02-OCT-06:10 | 0.549396E+10 | 4177.31 | 02-OCT-07:10 |
| November | 0.581240E+10 | 4272.19 | 01-NOV-06:10 | 0.538255E+10 | 4177.31 | 01-NOV-07:10 |
| December | 0.571221E+10 | 4272.19 | 01-DEC-07:10 | 0.539679E+10 | 4177.31 | 01-DEC-08:09 |
| Annual Sum or Average | 0.654164E+11 | 0.608015E+11 | ||||
| Minimum of Months | 0.357769E+10 | 2373.44 | 0.334604E+10 | 2198.59 | ||
| Maximum of Months | 0.623092E+10 | 4272.19 | 0.568828E+10 | 4177.31 |
Report: ZoneElectricSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.302663E+10 | 2197.13 | 02-JAN-07:10 | 0.376728E+10 | 2864.44 | 02-JAN-08:09 |
| February | 0.273660E+10 | 2197.13 | 01-FEB-07:10 | 0.340486E+10 | 2864.44 | 01-FEB-08:09 |
| March | 0.320447E+10 | 2197.13 | 01-MAR-07:10 | 0.390054E+10 | 2864.44 | 01-MAR-08:09 |
| April | 0.290031E+10 | 2197.13 | 03-APR-06:10 | 0.362427E+10 | 2864.44 | 03-APR-07:10 |
| May | 0.311555E+10 | 2197.13 | 01-MAY-06:10 | 0.383391E+10 | 2864.44 | 01-MAY-07:10 |
| June | 0.307815E+10 | 2197.13 | 01-JUN-06:10 | 0.375661E+10 | 2864.44 | 01-JUN-07:10 |
| July | 0.183996E+10 | 1220.63 | 03-JUL-07:10 | 0.229443E+10 | 1507.60 | 03-JUL-07:10 |
| August | 0.194205E+10 | 1220.63 | 01-AUG-07:10 | 0.238486E+10 | 1507.60 | 01-AUG-07:10 |
| September | 0.284543E+10 | 2197.13 | 05-SEP-06:10 | 0.356687E+10 | 2864.44 | 05-SEP-07:10 |
| October | 0.302663E+10 | 2197.13 | 02-OCT-06:10 | 0.376728E+10 | 2864.44 | 02-OCT-07:10 |
| November | 0.298923E+10 | 2197.13 | 01-NOV-06:10 | 0.369089E+10 | 2864.44 | 01-NOV-07:10 |
| December | 0.293771E+10 | 2197.13 | 01-DEC-07:10 | 0.370066E+10 | 2864.44 | 01-DEC-08:09 |
| Annual Sum or Average | 0.336427E+11 | 0.416925E+11 | ||||
| Minimum of Months | 0.183996E+10 | 1220.63 | 0.229443E+10 | 1507.60 | ||
| Maximum of Months | 0.320447E+10 | 2197.13 | 0.390054E+10 | 2864.44 |
Report: ZoneElectricSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.371022E+10 | 2693.36 | 02-JAN-07:10 | 0.253943E+10 | 1930.85 | 02-JAN-08:09 |
| February | 0.335468E+10 | 2693.36 | 01-FEB-07:10 | 0.229513E+10 | 1930.85 | 01-FEB-08:09 |
| March | 0.392822E+10 | 2693.36 | 01-MAR-07:10 | 0.262925E+10 | 1930.85 | 01-MAR-08:09 |
| April | 0.355537E+10 | 2693.36 | 03-APR-06:10 | 0.244302E+10 | 1930.85 | 03-APR-07:10 |
| May | 0.381922E+10 | 2693.36 | 01-MAY-06:10 | 0.258434E+10 | 1930.85 | 01-MAY-07:10 |
| June | 0.377338E+10 | 2693.36 | 01-JUN-06:10 | 0.253223E+10 | 1930.85 | 01-JUN-07:10 |
| July | 0.225552E+10 | 1496.31 | 03-JUL-07:10 | 0.154661E+10 | 1016.24 | 03-JUL-07:10 |
| August | 0.238068E+10 | 1496.31 | 01-AUG-07:10 | 0.160757E+10 | 1016.24 | 01-AUG-07:10 |
| September | 0.348808E+10 | 2693.36 | 05-SEP-06:10 | 0.240433E+10 | 1930.85 | 05-SEP-07:10 |
| October | 0.371022E+10 | 2693.36 | 02-OCT-06:10 | 0.253943E+10 | 1930.85 | 02-OCT-07:10 |
| November | 0.366437E+10 | 2693.36 | 01-NOV-06:10 | 0.248793E+10 | 1930.85 | 01-NOV-07:10 |
| December | 0.360121E+10 | 2693.36 | 01-DEC-07:10 | 0.249452E+10 | 1930.85 | 01-DEC-08:09 |
| Annual Sum or Average | 0.412412E+11 | 0.281038E+11 | ||||
| Minimum of Months | 0.225552E+10 | 1496.31 | 0.154661E+10 | 1016.24 | ||
| Maximum of Months | 0.392822E+10 | 2693.36 | 0.262925E+10 | 1930.85 |
Report: ZoneElectricSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.296658E+10 | 2153.53 | 02-JAN-07:10 | 0.795316E+09 | 604.72 | 02-JAN-08:09 |
| February | 0.268230E+10 | 2153.53 | 01-FEB-07:10 | 0.718803E+09 | 604.72 | 01-FEB-08:09 |
| March | 0.314089E+10 | 2153.53 | 01-MAR-07:10 | 0.823446E+09 | 604.72 | 01-MAR-08:09 |
| April | 0.284277E+10 | 2153.53 | 03-APR-06:10 | 0.765123E+09 | 604.72 | 03-APR-07:10 |
| May | 0.305373E+10 | 2153.53 | 01-MAY-06:10 | 0.809381E+09 | 604.72 | 01-MAY-07:10 |
| June | 0.301708E+10 | 2153.53 | 01-JUN-06:10 | 0.793062E+09 | 604.72 | 01-JUN-07:10 |
| July | 0.180345E+10 | 1196.41 | 03-JUL-07:10 | 0.484379E+09 | 318.27 | 03-JUL-07:10 |
| August | 0.190352E+10 | 1196.41 | 01-AUG-07:10 | 0.503470E+09 | 318.27 | 01-AUG-07:10 |
| September | 0.278897E+10 | 2153.53 | 05-SEP-06:10 | 0.753006E+09 | 604.72 | 05-SEP-07:10 |
| October | 0.296658E+10 | 2153.53 | 02-OCT-06:10 | 0.795316E+09 | 604.72 | 02-OCT-07:10 |
| November | 0.292992E+10 | 2153.53 | 01-NOV-06:10 | 0.779188E+09 | 604.72 | 01-NOV-07:10 |
| December | 0.287942E+10 | 2153.53 | 01-DEC-07:10 | 0.781250E+09 | 604.72 | 01-DEC-08:09 |
| Annual Sum or Average | 0.329752E+11 | 0.880174E+10 | ||||
| Minimum of Months | 0.180345E+10 | 1196.41 | 0.484379E+09 | 318.27 | ||
| Maximum of Months | 0.314089E+10 | 2153.53 | 0.823446E+09 | 604.72 |
Report: ZoneElectricSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.504438E+10 | 3661.88 | 02-JAN-07:10 | 0.293011E+10 | 2227.90 | 02-JAN-08:09 |
| February | 0.456100E+10 | 3661.88 | 01-FEB-07:10 | 0.264822E+10 | 2227.90 | 01-FEB-08:09 |
| March | 0.534079E+10 | 3661.88 | 01-MAR-07:10 | 0.303375E+10 | 2227.90 | 01-MAR-08:09 |
| April | 0.483386E+10 | 3661.88 | 03-APR-06:10 | 0.281887E+10 | 2227.90 | 03-APR-07:10 |
| May | 0.519259E+10 | 3661.88 | 01-MAY-06:10 | 0.298193E+10 | 2227.90 | 01-MAY-07:10 |
| June | 0.513026E+10 | 3661.88 | 01-JUN-06:10 | 0.292181E+10 | 2227.90 | 01-JUN-07:10 |
| July | 0.306659E+10 | 2034.38 | 03-JUL-07:10 | 0.178455E+10 | 1172.58 | 03-JUL-07:10 |
| August | 0.323676E+10 | 2034.38 | 01-AUG-07:10 | 0.185489E+10 | 1172.58 | 01-AUG-07:10 |
| September | 0.474238E+10 | 3661.88 | 05-SEP-06:10 | 0.277423E+10 | 2227.90 | 05-SEP-07:10 |
| October | 0.504438E+10 | 3661.88 | 02-OCT-06:10 | 0.293011E+10 | 2227.90 | 02-OCT-07:10 |
| November | 0.498206E+10 | 3661.88 | 01-NOV-06:10 | 0.287069E+10 | 2227.90 | 01-NOV-07:10 |
| December | 0.489618E+10 | 3661.88 | 01-DEC-07:10 | 0.287829E+10 | 2227.90 | 01-DEC-08:09 |
| Annual Sum or Average | 0.560712E+11 | 0.324275E+11 | ||||
| Minimum of Months | 0.306659E+10 | 2034.38 | 0.178455E+10 | 1172.58 | ||
| Maximum of Months | 0.534079E+10 | 3661.88 | 0.303375E+10 | 2227.90 |
Report: ZoneElectricSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.228198E+10 | 1656.56 | 02-JAN-07:10 | 0.883684E+09 | 671.91 | 02-JAN-08:09 |
| February | 0.206331E+10 | 1656.56 | 01-FEB-07:10 | 0.798670E+09 | 671.91 | 01-FEB-08:09 |
| March | 0.241607E+10 | 1656.56 | 01-MAR-07:10 | 0.914940E+09 | 671.91 | 01-MAR-08:09 |
| April | 0.218674E+10 | 1656.56 | 03-APR-06:10 | 0.850137E+09 | 671.91 | 03-APR-07:10 |
| May | 0.234903E+10 | 1656.56 | 01-MAY-06:10 | 0.899312E+09 | 671.91 | 01-MAY-07:10 |
| June | 0.232083E+10 | 1656.56 | 01-JUN-06:10 | 0.881180E+09 | 671.91 | 01-JUN-07:10 |
| July | 0.138727E+10 | 920.31 | 03-JUL-07:10 | 0.538198E+09 | 353.64 | 03-JUL-07:10 |
| August | 0.146425E+10 | 920.31 | 01-AUG-07:10 | 0.559411E+09 | 353.64 | 01-AUG-07:10 |
| September | 0.214536E+10 | 1656.56 | 05-SEP-06:10 | 0.836673E+09 | 671.91 | 05-SEP-07:10 |
| October | 0.228198E+10 | 1656.56 | 02-OCT-06:10 | 0.883684E+09 | 671.91 | 02-OCT-07:10 |
| November | 0.225379E+10 | 1656.56 | 01-NOV-06:10 | 0.865765E+09 | 671.91 | 01-NOV-07:10 |
| December | 0.221494E+10 | 1656.56 | 01-DEC-07:10 | 0.868056E+09 | 671.91 | 01-DEC-08:09 |
| Annual Sum or Average | 0.253655E+11 | 0.977971E+10 | ||||
| Minimum of Months | 0.138727E+10 | 920.31 | 0.538198E+09 | 353.64 | ||
| Maximum of Months | 0.241607E+10 | 1656.56 | 0.914940E+09 | 671.91 |
Report: ZoneElectricSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.647363E+10 | 4699.41 | 02-JAN-07:10 | 0.553791E+10 | 4210.73 | 02-JAN-08:09 |
| February | 0.585328E+10 | 4699.41 | 01-FEB-07:10 | 0.500514E+10 | 4210.73 | 01-FEB-08:09 |
| March | 0.685401E+10 | 4699.41 | 01-MAR-07:10 | 0.573379E+10 | 4210.73 | 01-MAR-08:09 |
| April | 0.620345E+10 | 4699.41 | 03-APR-06:10 | 0.532767E+10 | 4210.73 | 03-APR-07:10 |
| May | 0.666382E+10 | 4699.41 | 01-MAY-06:10 | 0.563585E+10 | 4210.73 | 01-MAY-07:10 |
| June | 0.658383E+10 | 4699.41 | 01-JUN-06:10 | 0.552221E+10 | 4210.73 | 01-JUN-07:10 |
| July | 0.393546E+10 | 2610.78 | 03-JUL-07:10 | 0.337280E+10 | 2216.18 | 03-JUL-07:10 |
| August | 0.415384E+10 | 2610.78 | 01-AUG-07:10 | 0.350574E+10 | 2216.18 | 01-AUG-07:10 |
| September | 0.608605E+10 | 4699.41 | 05-SEP-06:10 | 0.524330E+10 | 4210.73 | 05-SEP-07:10 |
| October | 0.647363E+10 | 4699.41 | 02-OCT-06:10 | 0.553791E+10 | 4210.73 | 02-OCT-07:10 |
| November | 0.639364E+10 | 4699.41 | 01-NOV-06:10 | 0.542561E+10 | 4210.73 | 01-NOV-07:10 |
| December | 0.628344E+10 | 4699.41 | 01-DEC-07:10 | 0.543997E+10 | 4210.73 | 01-DEC-08:09 |
| Annual Sum or Average | 0.719581E+11 | 0.612879E+11 | ||||
| Minimum of Months | 0.393546E+10 | 2610.78 | 0.337280E+10 | 2216.18 | ||
| Maximum of Months | 0.685401E+10 | 4699.41 | 0.573379E+10 | 4210.73 |
Report: ZoneElectricSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.590754E+10 | 4288.47 | 02-JAN-07:10 | 0.207549E+10 | 1578.10 | 02-JAN-08:09 |
| February | 0.534144E+10 | 4288.47 | 01-FEB-07:10 | 0.187582E+10 | 1578.10 | 01-FEB-08:09 |
| March | 0.625466E+10 | 4288.47 | 01-MAR-07:10 | 0.214891E+10 | 1578.10 | 01-MAR-08:09 |
| April | 0.566098E+10 | 4288.47 | 03-APR-06:10 | 0.199670E+10 | 1578.10 | 03-APR-07:10 |
| May | 0.608110E+10 | 4288.47 | 01-MAY-06:10 | 0.211220E+10 | 1578.10 | 01-MAY-07:10 |
| June | 0.600810E+10 | 4288.47 | 01-JUN-06:10 | 0.206961E+10 | 1578.10 | 01-JUN-07:10 |
| July | 0.359132E+10 | 2382.48 | 03-JUL-07:10 | 0.126406E+10 | 830.58 | 03-JUL-07:10 |
| August | 0.379060E+10 | 2382.48 | 01-AUG-07:10 | 0.131388E+10 | 830.58 | 01-AUG-07:10 |
| September | 0.555385E+10 | 4288.47 | 05-SEP-06:10 | 0.196508E+10 | 1578.10 | 05-SEP-07:10 |
| October | 0.590754E+10 | 4288.47 | 02-OCT-06:10 | 0.207549E+10 | 1578.10 | 02-OCT-07:10 |
| November | 0.583454E+10 | 4288.47 | 01-NOV-06:10 | 0.203341E+10 | 1578.10 | 01-NOV-07:10 |
| December | 0.573398E+10 | 4288.47 | 01-DEC-07:10 | 0.203879E+10 | 1578.10 | 01-DEC-08:09 |
| Annual Sum or Average | 0.656656E+11 | 0.229695E+11 | ||||
| Minimum of Months | 0.359132E+10 | 2382.48 | 0.126406E+10 | 830.58 | ||
| Maximum of Months | 0.625466E+10 | 4288.47 | 0.214891E+10 | 1578.10 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.269034E+10 | 1953.00 | 02-JAN-07:10 | 0.147381E+11 | 9714.90 | 02-JAN-10:09 |
| February | 0.243253E+10 | 1953.00 | 01-FEB-07:10 | 0.133142E+11 | 9714.90 | 01-FEB-10:09 |
| March | 0.284842E+10 | 1953.00 | 01-MAR-07:10 | 0.148878E+11 | 9714.90 | 01-MAR-10:09 |
| April | 0.257806E+10 | 1953.00 | 03-APR-06:10 | 0.142385E+11 | 9714.90 | 03-APR-09:09 |
| May | 0.276938E+10 | 1953.00 | 01-MAY-06:10 | 0.148130E+11 | 9714.90 | 01-MAY-09:09 |
| June | 0.273614E+10 | 1953.00 | 01-JUN-06:10 | 0.143883E+11 | 9714.90 | 01-JUN-09:09 |
| July | 0.163552E+10 | 1085.00 | 03-JUL-07:10 | 0.146632E+11 | 9714.90 | 03-JUL-09:09 |
| August | 0.172627E+10 | 1085.00 | 01-AUG-07:10 | 0.148878E+11 | 9714.90 | 01-AUG-09:09 |
| September | 0.252927E+10 | 1953.00 | 05-SEP-06:10 | 0.142385E+11 | 9714.90 | 01-SEP-09:09 |
| October | 0.269034E+10 | 1953.00 | 02-OCT-06:10 | 0.147381E+11 | 9714.90 | 02-OCT-09:09 |
| November | 0.265710E+10 | 1953.00 | 01-NOV-06:10 | 0.143134E+11 | 9714.90 | 01-NOV-09:09 |
| December | 0.261130E+10 | 1953.00 | 01-DEC-07:10 | 0.146632E+11 | 9714.90 | 01-DEC-10:09 |
| Annual Sum or Average | 0.299046E+11 | 0.173884E+12 | ||||
| Minimum of Months | 0.163552E+10 | 1085.00 | 0.133142E+11 | 9714.90 | ||
| Maximum of Months | 0.284842E+10 | 1953.00 | 0.148878E+11 | 9714.90 |
Report: ZoneElectricSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.378329E+10 | 2746.41 | 02-JAN-07:10 | 0.253516E+10 | 1999.46 | 02-JAN-10:09 |
| February | 0.342075E+10 | 2746.41 | 01-FEB-07:10 | 0.229042E+10 | 1999.46 | 01-FEB-10:09 |
| March | 0.400559E+10 | 2746.41 | 01-MAR-07:10 | 0.257259E+10 | 1999.46 | 01-MAR-10:09 |
| April | 0.362539E+10 | 2746.41 | 03-APR-06:10 | 0.244734E+10 | 1999.46 | 03-APR-09:09 |
| May | 0.389444E+10 | 2746.41 | 01-MAY-06:10 | 0.255387E+10 | 1999.46 | 01-MAY-09:09 |
| June | 0.384769E+10 | 2746.41 | 01-JUN-06:10 | 0.248477E+10 | 1999.46 | 01-JUN-09:09 |
| July | 0.229994E+10 | 1525.78 | 03-JUL-07:10 | 0.251644E+10 | 1999.46 | 03-JUL-09:09 |
| August | 0.242757E+10 | 1525.78 | 01-AUG-07:10 | 0.257259E+10 | 1999.46 | 01-AUG-09:09 |
| September | 0.355678E+10 | 2746.41 | 05-SEP-06:10 | 0.244734E+10 | 1999.46 | 01-SEP-09:09 |
| October | 0.378329E+10 | 2746.41 | 02-OCT-06:10 | 0.253516E+10 | 1999.46 | 02-OCT-09:09 |
| November | 0.373654E+10 | 2746.41 | 01-NOV-06:10 | 0.246606E+10 | 1999.46 | 01-NOV-09:09 |
| December | 0.367214E+10 | 2746.41 | 01-DEC-07:10 | 0.251644E+10 | 1999.46 | 01-DEC-10:09 |
| Annual Sum or Average | 0.420534E+11 | 0.299382E+11 | ||||
| Minimum of Months | 0.229994E+10 | 1525.78 | 0.229042E+10 | 1999.46 | ||
| Maximum of Months | 0.400559E+10 | 2746.41 | 0.257259E+10 | 1999.46 |
Report: ZoneElectricSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.825317E+10 | 5991.24 | 02-JAN-07:10 | 0.695901E+10 | 5291.26 | 02-JAN-08:09 |
| February | 0.746230E+10 | 5991.24 | 01-FEB-07:10 | 0.628953E+10 | 5291.26 | 01-FEB-08:09 |
| March | 0.873812E+10 | 5991.24 | 01-MAR-07:10 | 0.720516E+10 | 5291.26 | 01-MAR-08:09 |
| April | 0.790872E+10 | 5991.24 | 03-APR-06:10 | 0.669483E+10 | 5291.26 | 03-APR-07:10 |
| May | 0.849564E+10 | 5991.24 | 01-MAY-06:10 | 0.708208E+10 | 5291.26 | 01-MAY-07:10 |
| June | 0.839367E+10 | 5991.24 | 01-JUN-06:10 | 0.693929E+10 | 5291.26 | 01-JUN-07:10 |
| July | 0.501728E+10 | 3328.47 | 03-JUL-07:10 | 0.423831E+10 | 2784.88 | 03-JUL-07:10 |
| August | 0.529569E+10 | 3328.47 | 01-AUG-07:10 | 0.440537E+10 | 2784.88 | 01-AUG-07:10 |
| September | 0.775905E+10 | 5991.24 | 05-SEP-06:10 | 0.658880E+10 | 5291.26 | 05-SEP-07:10 |
| October | 0.825317E+10 | 5991.24 | 02-OCT-06:10 | 0.695901E+10 | 5291.26 | 02-OCT-07:10 |
| November | 0.815120E+10 | 5991.24 | 01-NOV-06:10 | 0.681790E+10 | 5291.26 | 01-NOV-07:10 |
| December | 0.801070E+10 | 5991.24 | 01-DEC-07:10 | 0.683594E+10 | 5291.26 | 01-DEC-08:09 |
| Annual Sum or Average | 0.917387E+11 | 0.770152E+11 | ||||
| Minimum of Months | 0.501728E+10 | 3328.47 | 0.423831E+10 | 2784.88 | ||
| Maximum of Months | 0.873812E+10 | 5991.24 | 0.720516E+10 | 5291.26 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693602E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.530456E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482605E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345041E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1494020.79 | 0.337478E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6200280.01 | 0.175638E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19122065.54 | 0.115332E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15978567.94 | 0.128749E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10622026.97 | 0.272171E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48710.79 | 0.377723E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494275E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.611361E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53465672.06 | 0.456443E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115332E+09 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19122065.54 | 0.693602E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189480E+10 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149379E+10 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136434E+10 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100657E+10 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4249076.66 | 0.956888E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18091204.20 | 0.489934E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58237589.10 | 0.308980E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46703596.46 | 0.351926E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31311082.01 | 0.765998E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 129089.31 | 0.107536E+10 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139857E+10 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169884E+10 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158722E+09 | 0.128060E+11 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308980E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58237589.10 | 0.189480E+10 |
Report: SpaceGainsMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106917E+09 |
| February | 0.708259E+09 | 0.117967E+10 | 0.807077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82055255.10 |
| March | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75385519.78 |
| April | 0.745536E+09 | 0.125024E+10 | 0.859085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55120086.35 |
| May | 0.820090E+09 | 0.134302E+10 | 0.908779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 242630.59 | 53916182.30 |
| June | 0.505804E+09 | 0.132690E+10 | 0.890455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 892403.42 | 28320513.32 |
| July | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2971393.81 | 17500862.58 |
| August | 0.200223E+09 | 0.837162E+09 | 0.565300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2580220.95 | 19207530.87 |
| September | 0.459822E+09 | 0.122658E+10 | 0.845480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1873838.52 | 41006886.10 |
| October | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7709.32 | 56593183.14 |
| November | 0.782813E+09 | 0.128857E+10 | 0.874878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75893431.98 |
| December | 0.745536E+09 | 0.126636E+10 | 0.877193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94821192.47 |
| Annual Sum or Average | 0.756518E+10 | 0.145024E+11 | 0.988265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8568196.61 | 0.706738E+09 |
| Minimum of Months | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17500862.58 |
| Maximum of Months | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2971393.81 | 0.106917E+09 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682085E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501246E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460201E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321065E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2246807.06 | 0.323429E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7417916.85 | 0.169944E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23700792.89 | 0.106130E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19569295.05 | 0.115142E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14931096.39 | 0.245676E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 284871.58 | 0.337973E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464521E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593916E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68150779.83 | 0.432133E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106130E+09 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23700792.89 | 0.682085E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184953E+10 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139203E+10 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129049E+10 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937042E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6703478.21 | 0.917533E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22189357.51 | 0.473018E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74038147.21 | 0.280831E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59906566.35 | 0.310044E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44680427.47 | 0.686884E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 927241.67 | 0.960166E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130299E+10 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163385E+10 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208445E+09 | 0.120344E+11 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280831E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74038147.21 | 0.184953E+10 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692235E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529528E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481838E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344025E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1548317.85 | 0.335883E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6335537.82 | 0.174569E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19537773.29 | 0.114188E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16135964.36 | 0.127826E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10765908.78 | 0.271448E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48710.95 | 0.376713E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492633E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608637E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54372213.04 | 0.454952E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114188E+09 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19537773.29 | 0.692235E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188824E+10 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149008E+10 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136252E+10 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100607E+10 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4429810.62 | 0.954748E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18588315.53 | 0.487855E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60185220.56 | 0.305303E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47547765.45 | 0.348780E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32151794.52 | 0.763632E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 129090.46 | 0.107097E+10 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139116E+10 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168659E+10 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163032E+09 | 0.127559E+11 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305303E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 60185220.56 | 0.188824E+10 |
Report: SpaceGainsMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106765E+09 |
| February | 0.708259E+09 | 0.117967E+10 | 0.807077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81974416.34 |
| March | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75335855.04 |
| April | 0.745536E+09 | 0.125024E+10 | 0.859085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55087008.53 |
| May | 0.820090E+09 | 0.134302E+10 | 0.908779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 245493.01 | 53845146.72 |
| June | 0.505804E+09 | 0.132690E+10 | 0.890455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 898332.56 | 28268668.30 |
| July | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3000509.57 | 17402910.48 |
| August | 0.200223E+09 | 0.837162E+09 | 0.565300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2594681.27 | 19115362.94 |
| September | 0.459822E+09 | 0.122658E+10 | 0.845480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1890865.67 | 40944205.59 |
| October | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7894.87 | 56473502.80 |
| November | 0.782813E+09 | 0.128857E+10 | 0.874878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75677015.14 |
| December | 0.745536E+09 | 0.126636E+10 | 0.877193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94548503.43 |
| Annual Sum or Average | 0.756518E+10 | 0.145024E+11 | 0.988265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8637776.96 | 0.705438E+09 |
| Minimum of Months | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17402910.48 |
| Maximum of Months | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3000509.57 | 0.106765E+09 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.681983E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501171E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460194E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321119E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2238304.04 | 0.323526E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7397660.82 | 0.170044E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23666803.82 | 0.106139E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19551932.75 | 0.115097E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14929018.75 | 0.245674E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 286550.65 | 0.337864E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464217E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593701E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 68070270.83 | 0.432073E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106139E+09 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23666803.82 | 0.681983E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184915E+10 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139181E+10 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129048E+10 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.937209E+09 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6678412.39 | 0.917819E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22115130.56 | 0.473342E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73982126.34 | 0.280786E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59875385.38 | 0.309890E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44687897.92 | 0.686862E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 932991.28 | 0.959851E+09 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130207E+10 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163308E+10 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208272E+09 | 0.120323E+11 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280786E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73982126.34 | 0.184915E+10 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692829E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529918E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.482405E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345381E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1516246.12 | 0.337503E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6272463.45 | 0.175327E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19285052.76 | 0.115181E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16022694.58 | 0.128777E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10664298.38 | 0.272780E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48710.76 | 0.378413E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.494155E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.609744E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53809466.06 | 0.456241E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115181E+09 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19285052.76 | 0.692829E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189068E+10 |
| February | 0.879765E+10 | 0.805776E+10 | 0.751906E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149118E+10 |
| March | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136470E+10 |
| April | 0.926068E+10 | 0.853981E+10 | 0.800359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101109E+10 |
| May | 0.101867E+11 | 0.917357E+10 | 0.846655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4287579.49 | 0.960899E+09 |
| June | 0.628284E+10 | 0.906345E+10 | 0.829584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18287373.53 | 0.490727E+09 |
| July | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58943179.64 | 0.309103E+09 |
| August | 0.248707E+10 | 0.571827E+10 | 0.526656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46949858.75 | 0.352470E+09 |
| September | 0.571168E+10 | 0.837820E+10 | 0.787684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31677047.56 | 0.769128E+09 |
| October | 0.972371E+10 | 0.891175E+10 | 0.831942E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 129089.56 | 0.107832E+10 |
| November | 0.972371E+10 | 0.880163E+10 | 0.815072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139819E+10 |
| December | 0.926068E+10 | 0.864992E+10 | 0.817229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169072E+10 |
| Annual Sum or Average | 0.939710E+11 | 0.990591E+11 | 0.920708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160274E+09 | 0.128072E+11 |
| Minimum of Months | 0.216267E+10 | 0.541765E+10 | 0.506686E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309103E+09 |
| Maximum of Months | 0.106498E+11 | 0.943539E+10 | 0.861368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58943179.64 | 0.189068E+10 |
Report: SpaceGainsMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106906E+09 |
| February | 0.708259E+09 | 0.117967E+10 | 0.807077E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82173177.14 |
| March | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75683056.11 |
| April | 0.745536E+09 | 0.125024E+10 | 0.859085E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55794218.76 |
| May | 0.820090E+09 | 0.134302E+10 | 0.908779E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 226440.13 | 54657629.20 |
| June | 0.505804E+09 | 0.132690E+10 | 0.890455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 869459.90 | 28676367.64 |
| July | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2878847.22 | 17919284.27 |
| August | 0.200223E+09 | 0.837162E+09 | 0.565300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2522518.20 | 19610484.23 |
| September | 0.459822E+09 | 0.122658E+10 | 0.845480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1830218.93 | 41673119.89 |
| October | 0.782813E+09 | 0.130469E+10 | 0.892986E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7361.94 | 57290664.65 |
| November | 0.782813E+09 | 0.128857E+10 | 0.874878E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76322828.49 |
| December | 0.745536E+09 | 0.126636E+10 | 0.877193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94802750.22 |
| Annual Sum or Average | 0.756518E+10 | 0.145024E+11 | 0.988265E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8334846.33 | 0.711510E+09 |
| Minimum of Months | 0.174107E+09 | 0.793150E+09 | 0.543864E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17919284.27 |
| Maximum of Months | 0.857367E+09 | 0.138135E+10 | 0.924571E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2878847.22 | 0.106906E+09 |
Report: SpaceGainsMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.682019E+09 |
| February | 0.182593E+10 | 0.167237E+10 | 0.156056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.501477E+09 |
| March | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461083E+09 |
| April | 0.192203E+10 | 0.177241E+10 | 0.166112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.323218E+09 |
| May | 0.211423E+10 | 0.190395E+10 | 0.175721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2091587.94 | 0.326646E+09 |
| June | 0.130399E+10 | 0.188109E+10 | 0.172178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7130877.54 | 0.172052E+09 |
| July | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22833789.34 | 0.108274E+09 |
| August | 0.516185E+09 | 0.118681E+10 | 0.109306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19160022.67 | 0.116700E+09 |
| September | 0.118544E+10 | 0.173887E+10 | 0.163481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14651144.16 | 0.247576E+09 |
| October | 0.201813E+10 | 0.184961E+10 | 0.172667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 264348.91 | 0.339706E+09 |
| November | 0.201813E+10 | 0.182675E+10 | 0.169166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465055E+09 |
| December | 0.192203E+10 | 0.179527E+10 | 0.169614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593810E+09 |
| Annual Sum or Average | 0.195034E+11 | 0.205594E+11 | 0.191090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 66131770.55 | 0.433761E+10 |
| Minimum of Months | 0.448857E+09 | 0.112442E+10 | 0.105161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108274E+09 |
| Maximum of Months | 0.221033E+10 | 0.195829E+10 | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22833789.34 | 0.682019E+09 |
Report: SpaceGainsMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.642132E+10 | 0.588512E+10 | 0.549396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122063E+10 |
| February | 0.580977E+10 | 0.532117E+10 | 0.496542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.918657E+09 |
| March | 0.703288E+10 | 0.623092E+10 | 0.568828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.853677E+09 |
| April | 0.611554E+10 | 0.563950E+10 | 0.528539E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622639E+09 |
| May | 0.672710E+10 | 0.605802E+10 | 0.559112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3977077.54 | 0.612704E+09 |
| June | 0.414905E+10 | 0.598530E+10 | 0.547839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13719111.45 | 0.317391E+09 |
| July | 0.142818E+10 | 0.357769E+10 | 0.334604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46494487.26 | 0.190027E+09 |
| August | 0.164241E+10 | 0.377621E+10 | 0.347792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38299820.27 | 0.208058E+09 |
| September | 0.377186E+10 | 0.553277E+10 | 0.520168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 28747203.15 | 0.457857E+09 |
| October | 0.642132E+10 | 0.588512E+10 | 0.549396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 541385.98 | 0.637776E+09 |
| November | 0.642132E+10 | 0.581240E+10 | 0.538255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.861670E+09 |
| December | 0.611554E+10 | 0.571221E+10 | 0.539679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107799E+10 |
| Annual Sum or Average | 0.620563E+11 | 0.654164E+11 | 0.608015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131779E+09 | 0.797907E+10 |
| Minimum of Months | 0.142818E+10 | 0.357769E+10 | 0.334604E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190027E+09 |
| Maximum of Months | 0.703288E+10 | 0.623092E+10 | 0.568828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46494487.26 | 0.122063E+10 |
Report: SpaceGainsMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.488438E+10 | 0.302663E+10 | 0.376728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.634908E+09 |
| February | 0.441920E+10 | 0.273660E+10 | 0.340486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.485479E+09 |
| March | 0.534956E+10 | 0.320447E+10 | 0.390054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455545E+09 |
| April | 0.465179E+10 | 0.290031E+10 | 0.362427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.343721E+09 |
| May | 0.511697E+10 | 0.311555E+10 | 0.383391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1561627.10 | 0.336320E+09 |
| June | 0.511697E+10 | 0.307815E+10 | 0.375661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6143771.46 | 0.174820E+09 |
| July | 0.244831E+10 | 0.183996E+10 | 0.229443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19682084.94 | 0.109750E+09 |
| August | 0.281556E+10 | 0.194205E+10 | 0.238486E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16714747.30 | 0.120290E+09 |
| September | 0.454162E+10 | 0.284543E+10 | 0.356687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13183269.56 | 0.257902E+09 |
| October | 0.488438E+10 | 0.302663E+10 | 0.376728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 127710.50 | 0.351146E+09 |
| November | 0.488438E+10 | 0.298923E+10 | 0.369089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464444E+09 |
| December | 0.465179E+10 | 0.293771E+10 | 0.370066E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566391E+09 |
| Annual Sum or Average | 0.537649E+11 | 0.336427E+11 | 0.416925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57413210.87 | 0.430072E+10 |
| Minimum of Months | 0.244831E+10 | 0.183996E+10 | 0.229443E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109750E+09 |
| Maximum of Months | 0.534956E+10 | 0.320447E+10 | 0.390054E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19682084.94 | 0.634908E+09 |
Report: SpaceGainsMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.222618E+10 | 0.371022E+10 | 0.253943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318668E+09 |
| February | 0.201416E+10 | 0.335468E+10 | 0.229513E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245500E+09 |
| March | 0.243819E+10 | 0.392822E+10 | 0.262925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226884E+09 |
| April | 0.212017E+10 | 0.355537E+10 | 0.244302E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172523E+09 |
| May | 0.233218E+10 | 0.381922E+10 | 0.258434E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 589433.45 | 0.170309E+09 |
| June | 0.143841E+10 | 0.377338E+10 | 0.253223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2270134.90 | 90888500.07 |
| July | 0.495129E+09 | 0.225552E+10 | 0.154661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7378277.21 | 60707626.06 |
| August | 0.569398E+09 | 0.238068E+10 | 0.160757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7019063.73 | 63874908.74 |
| September | 0.130765E+10 | 0.348808E+10 | 0.240433E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5151995.50 | 0.127075E+09 |
| October | 0.222618E+10 | 0.371022E+10 | 0.253943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40705.70 | 0.166500E+09 |
| November | 0.222618E+10 | 0.366437E+10 | 0.248793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222388E+09 |
| December | 0.212017E+10 | 0.360121E+10 | 0.249452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282571E+09 |
| Annual Sum or Average | 0.215140E+11 | 0.412412E+11 | 0.281038E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 22449610.49 | 0.214789E+10 |
| Minimum of Months | 0.495129E+09 | 0.225552E+10 | 0.154661E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60707626.06 |
| Maximum of Months | 0.243819E+10 | 0.392822E+10 | 0.262925E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7378277.21 | 0.318668E+09 |
Report: SpaceGainsMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.139443E+10 | 0.296658E+10 | 0.795316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143140E+11 |
| February | 0.126163E+10 | 0.268230E+10 | 0.718803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106931E+11 |
| March | 0.152723E+10 | 0.314089E+10 | 0.823446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108113E+11 |
| April | 0.132803E+10 | 0.284277E+10 | 0.765123E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.707267E+10 |
| May | 0.146083E+10 | 0.305373E+10 | 0.809381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47310160.71 | 0.667696E+10 |
| June | 0.900991E+09 | 0.301708E+10 | 0.793062E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555639E+09 | 0.326432E+10 |
| July | 0.310138E+09 | 0.180345E+10 | 0.484379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127418E+10 | 0.123536E+10 |
| August | 0.356659E+09 | 0.190352E+10 | 0.503470E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.949873E+09 | 0.236336E+10 |
| September | 0.819082E+09 | 0.278897E+10 | 0.753006E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179929E+09 | 0.446026E+10 |
| October | 0.139443E+10 | 0.296658E+10 | 0.795316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13610934.80 | 0.667597E+10 |
| November | 0.139443E+10 | 0.292992E+10 | 0.779188E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.911908E+10 |
| December | 0.132803E+10 | 0.287942E+10 | 0.781250E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115802E+11 |
| Annual Sum or Average | 0.134759E+11 | 0.329752E+11 | 0.880174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302054E+10 | 0.882666E+11 |
| Minimum of Months | 0.310138E+09 | 0.180345E+10 | 0.484379E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123536E+10 |
| Maximum of Months | 0.152723E+10 | 0.314089E+10 | 0.823446E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127418E+10 | 0.143140E+11 |
Report: SpaceGainsMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.308232E+09 | 0.504438E+10 | 0.293011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.278876E+09 | 0.456100E+10 | 0.264822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.337587E+09 | 0.534079E+10 | 0.303375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.293554E+09 | 0.483386E+10 | 0.281887E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.322909E+09 | 0.519259E+10 | 0.298193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.199160E+09 | 0.513026E+10 | 0.292181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 68554512.00 | 0.306659E+10 | 0.178455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 78837688.80 | 0.323676E+10 | 0.185489E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.181054E+09 | 0.474238E+10 | 0.277423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.308232E+09 | 0.504438E+10 | 0.293011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.308232E+09 | 0.498206E+10 | 0.287069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.293554E+09 | 0.489618E+10 | 0.287829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.297878E+10 | 0.560712E+11 | 0.324275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 68554512.00 | 0.306659E+10 | 0.178455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.337587E+09 | 0.534079E+10 | 0.303375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.774708E+09 | 0.228198E+10 | 0.883684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330725E+09 |
| February | 0.700926E+09 | 0.206331E+10 | 0.798670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250827E+09 |
| March | 0.848489E+09 | 0.241607E+10 | 0.914940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238928E+09 |
| April | 0.737817E+09 | 0.218674E+10 | 0.850137E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186869E+09 |
| May | 0.811598E+09 | 0.234903E+10 | 0.899312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 403386.92 | 0.188470E+09 |
| June | 0.500567E+09 | 0.232083E+10 | 0.881180E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1348673.65 | 0.106888E+09 |
| July | 0.172304E+09 | 0.138727E+10 | 0.538198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6146052.11 | 72988721.30 |
| August | 0.198150E+09 | 0.146425E+10 | 0.559411E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6430185.85 | 74227462.95 |
| September | 0.455061E+09 | 0.214536E+10 | 0.836673E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5057680.78 | 0.144211E+09 |
| October | 0.774708E+09 | 0.228198E+10 | 0.883684E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 28243.11 | 0.183684E+09 |
| November | 0.774708E+09 | 0.225379E+10 | 0.865765E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235941E+09 |
| December | 0.737817E+09 | 0.221494E+10 | 0.868056E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294987E+09 |
| Annual Sum or Average | 0.748685E+10 | 0.253655E+11 | 0.977971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19414222.41 | 0.230875E+10 |
| Minimum of Months | 0.172304E+09 | 0.138727E+10 | 0.538198E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72988721.30 |
| Maximum of Months | 0.848489E+09 | 0.241607E+10 | 0.914940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6430185.85 | 0.330725E+09 |
Report: SpaceGainsMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.156120E+10 | 0.647363E+10 | 0.553791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147427E+10 |
| February | 0.141251E+10 | 0.585328E+10 | 0.500514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114416E+10 |
| March | 0.170988E+10 | 0.685401E+10 | 0.573379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106141E+10 |
| April | 0.148685E+10 | 0.620345E+10 | 0.532767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.807344E+09 |
| May | 0.163554E+10 | 0.666382E+10 | 0.563585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2158355.01 | 0.792061E+09 |
| June | 0.163554E+10 | 0.658383E+10 | 0.552221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9691094.86 | 0.426318E+09 |
| July | 0.840841E+09 | 0.393546E+10 | 0.337280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30558473.40 | 0.297820E+09 |
| August | 0.966967E+09 | 0.415384E+10 | 0.350574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29375788.94 | 0.316231E+09 |
| September | 0.145455E+10 | 0.608605E+10 | 0.524330E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18618920.20 | 0.626103E+09 |
| October | 0.156120E+10 | 0.647363E+10 | 0.553791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79565.63 | 0.829170E+09 |
| November | 0.156120E+10 | 0.639364E+10 | 0.542561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106685E+10 |
| December | 0.148685E+10 | 0.628344E+10 | 0.543997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130903E+10 |
| Annual Sum or Average | 0.173131E+11 | 0.719581E+11 | 0.612879E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90482198.04 | 0.101508E+11 |
| Minimum of Months | 0.840841E+09 | 0.393546E+10 | 0.337280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297820E+09 |
| Maximum of Months | 0.170988E+10 | 0.685401E+10 | 0.573379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30558473.40 | 0.147427E+10 |
Report: SpaceGainsMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.789800E+10 | 0.590754E+10 | 0.207549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.615360E+09 |
| February | 0.714581E+10 | 0.534144E+10 | 0.187582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488133E+09 |
| March | 0.865019E+10 | 0.625466E+10 | 0.214891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460500E+09 |
| April | 0.752191E+10 | 0.566098E+10 | 0.199670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363632E+09 |
| May | 0.827410E+10 | 0.608110E+10 | 0.211220E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 969389.86 | 0.349437E+09 |
| June | 0.827410E+10 | 0.600810E+10 | 0.206961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4395918.24 | 0.179448E+09 |
| July | 0.453307E+10 | 0.359132E+10 | 0.126406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13343876.58 | 0.125619E+09 |
| August | 0.521303E+10 | 0.379060E+10 | 0.131388E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12972762.84 | 0.132197E+09 |
| September | 0.737247E+10 | 0.555385E+10 | 0.196508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9778264.72 | 0.258212E+09 |
| October | 0.789800E+10 | 0.590754E+10 | 0.207549E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41881.06 | 0.344600E+09 |
| November | 0.789800E+10 | 0.583454E+10 | 0.203341E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450692E+09 |
| December | 0.752191E+10 | 0.573398E+10 | 0.203879E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.551029E+09 |
| Annual Sum or Average | 0.882006E+11 | 0.656656E+11 | 0.229695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 41502093.29 | 0.431886E+10 |
| Minimum of Months | 0.453307E+10 | 0.359132E+10 | 0.126406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125619E+09 |
| Maximum of Months | 0.865019E+10 | 0.625466E+10 | 0.214891E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13343876.58 | 0.615360E+09 |
Report: SpaceGainsMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.204475E+10 | 0.269034E+10 | 0.811357E+10 | 0.909844E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366590E+09 |
| February | 0.185001E+10 | 0.243253E+10 | 0.733032E+10 | 0.822599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308347E+09 |
| March | 0.223949E+10 | 0.284842E+10 | 0.823336E+10 | 0.959699E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269510E+09 |
| April | 0.194738E+10 | 0.257806E+10 | 0.783252E+10 | 0.872454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207821E+09 |
| May | 0.214212E+10 | 0.276938E+10 | 0.817347E+10 | 0.934772E+10 | 0.00 | 0.00 | 0.00 | 345915.47 | 0.189100E+09 |
| June | 0.132119E+10 | 0.273614E+10 | 0.795231E+10 | 0.922308E+10 | 0.00 | 0.00 | 0.00 | 1705902.49 | 94898783.60 |
| July | 0.454778E+09 | 0.163552E+10 | 0.805368E+10 | 0.884917E+10 | 0.00 | 0.00 | 0.00 | 5269028.01 | 66724547.64 |
| August | 0.522995E+09 | 0.172627E+10 | 0.823336E+10 | 0.959699E+10 | 0.00 | 0.00 | 0.00 | 5243623.42 | 71176624.08 |
| September | 0.120108E+10 | 0.252927E+10 | 0.783252E+10 | 0.872454E+10 | 0.00 | 0.00 | 0.00 | 3164579.06 | 0.137286E+09 |
| October | 0.204475E+10 | 0.269034E+10 | 0.811357E+10 | 0.909844E+10 | 0.00 | 0.00 | 0.00 | 20171.02 | 0.196122E+09 |
| November | 0.204475E+10 | 0.265710E+10 | 0.789242E+10 | 0.897381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275247E+09 |
| December | 0.194738E+10 | 0.261130E+10 | 0.805368E+10 | 0.884917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344675E+09 |
| Annual Sum or Average | 0.197607E+11 | 0.299046E+11 | 0.958148E+11 | 0.108309E+12 | 0.00 | 0.00 | 0.00 | 15749219.47 | 0.252750E+10 |
| Minimum of Months | 0.454778E+09 | 0.163552E+10 | 0.733032E+10 | 0.822599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66724547.64 |
| Maximum of Months | 0.223949E+10 | 0.284842E+10 | 0.823336E+10 | 0.959699E+10 | 0.00 | 0.00 | 0.00 | 5269028.01 | 0.366590E+09 |
Report: SpaceGainsMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.229168E+11 | 0.378329E+10 | 0.253516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128210E+10 |
| February | 0.207343E+11 | 0.342075E+10 | 0.229042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.997397E+09 |
| March | 0.250994E+11 | 0.400559E+10 | 0.257259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.919562E+09 |
| April | 0.218255E+11 | 0.362539E+10 | 0.244734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.690000E+09 |
| May | 0.240081E+11 | 0.389444E+10 | 0.255387E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1501115.55 | 0.686920E+09 |
| June | 0.240081E+11 | 0.384769E+10 | 0.248477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7852837.52 | 0.377801E+09 |
| July | 0.556624E+10 | 0.229994E+10 | 0.251644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24699112.01 | 0.266057E+09 |
| August | 0.640118E+10 | 0.242757E+10 | 0.257259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24366200.80 | 0.269903E+09 |
| September | 0.210126E+11 | 0.355678E+10 | 0.244734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15043238.60 | 0.520052E+09 |
| October | 0.229168E+11 | 0.378329E+10 | 0.253516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87527.25 | 0.683412E+09 |
| November | 0.229168E+11 | 0.373654E+10 | 0.246606E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.929092E+09 |
| December | 0.218255E+11 | 0.367214E+10 | 0.251644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114508E+10 |
| Annual Sum or Average | 0.239231E+12 | 0.420534E+11 | 0.299382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73550031.72 | 0.876738E+10 |
| Minimum of Months | 0.556624E+10 | 0.229994E+10 | 0.229042E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.266057E+09 |
| Maximum of Months | 0.250994E+11 | 0.400559E+10 | 0.257259E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24699112.01 | 0.128210E+10 |
Report: SpaceGainsMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.325382E+10 | 0.825317E+10 | 0.695901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140193E+10 |
| February | 0.294393E+10 | 0.746230E+10 | 0.628953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107256E+10 |
| March | 0.356371E+10 | 0.873812E+10 | 0.720516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100636E+10 |
| April | 0.309888E+10 | 0.790872E+10 | 0.669483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777333E+09 |
| May | 0.340876E+10 | 0.849564E+10 | 0.708208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2195235.25 | 0.771722E+09 |
| June | 0.210241E+10 | 0.839367E+10 | 0.693929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9774829.63 | 0.414088E+09 |
| July | 0.723690E+09 | 0.501728E+10 | 0.423831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31047140.96 | 0.283438E+09 |
| August | 0.832243E+09 | 0.529569E+10 | 0.440537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29569771.76 | 0.298212E+09 |
| September | 0.191128E+10 | 0.775905E+10 | 0.658880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20338546.72 | 0.595272E+09 |
| October | 0.325382E+10 | 0.825317E+10 | 0.695901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 99935.69 | 0.786956E+09 |
| November | 0.325382E+10 | 0.815120E+10 | 0.681790E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101923E+10 |
| December | 0.309888E+10 | 0.801070E+10 | 0.683594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124406E+10 |
| Annual Sum or Average | 0.314452E+11 | 0.917387E+11 | 0.770152E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 93025460.02 | 0.967116E+10 |
| Minimum of Months | 0.723690E+09 | 0.501728E+10 | 0.423831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.283438E+09 |
| Maximum of Months | 0.356371E+10 | 0.873812E+10 | 0.720516E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 31047140.96 | 0.140193E+10 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1061.15 | 05-JAN-21:55 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 759.41 | 01-FEB-21:01 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 781.70 | 02-MAR-23:00 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 527.01 | 27-APR-02:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 94.55 | 20-MAY-16:20 | 1008.17 | 22-MAY-04:05 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.05 | 24-JUN-14:10 | 438.06 | 14-JUN-02:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.94 | 30-JUL-11:53 | 247.55 | 08-JUL-10:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.43 | 05-AUG-13:55 | 315.52 | 22-AUG-21:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.64 | 02-SEP-14:10 | 590.41 | 12-SEP-02:55 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 | 18-OCT-14:20 | 527.49 | 30-OCT-22:00 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 628.86 | 28-NOV-06:50 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 826.75 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.55 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 187.64 | 1061.15 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2911.85 | 05-JAN-21:55 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2021.40 | 01-FEB-21:01 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2218.59 | 02-MAR-23:00 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1522.88 | 27-APR-02:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 262.63 | 20-MAY-16:20 | 2999.95 | 22-MAY-04:05 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 464.80 | 24-JUN-14:10 | 1265.64 | 14-JUN-02:00 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 478.36 | 30-JUL-11:53 | 712.81 | 08-JUL-10:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 530.71 | 05-AUG-13:55 | 871.65 | 23-AUG-02:55 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 553.69 | 02-SEP-14:50 | 1709.71 | 12-SEP-02:55 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 | 18-OCT-14:20 | 1509.22 | 30-OCT-22:00 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1666.42 | 28-NOV-06:42 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2423.37 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.81 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 553.69 | 2999.95 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1178.08 | 02-JAN-08:09 | 947.12 | 02-JAN-07:10 | 678.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 170.77 | 05-JAN-21:55 |
| February | 1178.08 | 01-FEB-08:09 | 947.12 | 01-FEB-07:10 | 678.98 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 114.43 | 01-FEB-21:01 |
| March | 1178.08 | 01-MAR-08:09 | 947.12 | 01-MAR-07:10 | 678.98 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 124.64 | 02-MAR-23:00 |
| April | 1178.08 | 03-APR-07:10 | 947.12 | 03-APR-06:10 | 678.98 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 86.99 | 27-APR-02:00 |
| May | 1178.08 | 01-MAY-07:10 | 947.12 | 01-MAY-06:10 | 678.98 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.27 | 20-MAY-15:53 | 179.35 | 22-MAY-04:00 |
| June | 1178.08 | 01-JUN-07:10 | 947.12 | 01-JUN-06:10 | 678.98 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.26 | 24-JUN-14:10 | 73.21 | 14-JUN-02:00 |
| July | 186.01 | 03-JUL-07:10 | 526.18 | 03-JUL-07:10 | 357.36 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.21 | 30-JUL-11:53 | 38.88 | 05-JUL-00:53 |
| August | 186.01 | 01-AUG-07:10 | 526.18 | 01-AUG-07:10 | 357.36 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.56 | 05-AUG-13:55 | 48.91 | 23-AUG-02:55 |
| September | 1178.08 | 18-SEP-07:10 | 947.12 | 05-SEP-06:10 | 678.98 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 02-SEP-14:10 | 98.74 | 12-SEP-02:55 |
| October | 1178.08 | 02-OCT-07:10 | 947.12 | 02-OCT-06:10 | 678.98 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.86 | 15-OCT-14:00 | 81.96 | 30-OCT-22:00 |
| November | 1178.08 | 01-NOV-07:10 | 947.12 | 01-NOV-06:10 | 678.98 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 94.33 | 28-NOV-06:47 |
| December | 1178.08 | 01-DEC-08:09 | 947.12 | 01-DEC-07:10 | 678.98 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 141.51 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.88 | |||||
| Maximum of Months | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 31.50 | 179.35 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1058.72 | 05-JAN-21:55 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 757.69 | 01-FEB-21:01 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 739.36 | 02-MAR-23:00 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 505.14 | 27-APR-02:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.38 | 20-MAY-15:53 | 988.74 | 22-MAY-04:05 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.82 | 24-JUN-14:10 | 430.97 | 14-JUN-02:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.44 | 30-JUL-11:53 | 230.76 | 05-JUL-00:53 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.08 | 05-AUG-13:55 | 290.73 | 22-AUG-20:55 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.70 | 02-SEP-14:10 | 573.54 | 12-SEP-02:55 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.16 | 15-OCT-14:10 | 483.51 | 30-OCT-22:00 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 628.87 | 28-NOV-06:47 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 821.60 | 31-DEC-02:52 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.76 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 236.70 | 1058.72 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2902.08 | 05-JAN-21:55 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2016.43 | 01-FEB-21:01 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2081.30 | 02-MAR-23:00 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1457.81 | 27-APR-02:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.43 | 20-MAY-15:53 | 2944.27 | 22-MAY-04:05 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 537.20 | 24-JUN-14:10 | 1245.68 | 14-JUN-02:00 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 552.50 | 30-JUL-11:53 | 652.54 | 05-JUL-00:53 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 618.36 | 05-AUG-13:55 | 800.87 | 23-AUG-02:55 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 686.59 | 02-SEP-14:10 | 1657.89 | 12-SEP-02:55 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.48 | 15-OCT-14:10 | 1372.76 | 30-OCT-22:00 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1666.48 | 28-NOV-06:50 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2382.55 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.54 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 686.59 | 2944.27 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1061.18 | 05-JAN-21:55 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 759.37 | 01-FEB-21:01 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 780.43 | 02-MAR-23:00 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 526.19 | 27-APR-02:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.96 | 20-MAY-16:20 | 1005.74 | 22-MAY-04:05 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.78 | 24-JUN-14:10 | 436.58 | 14-JUN-02:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 174.26 | 30-JUL-11:53 | 243.46 | 08-JUL-10:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 185.57 | 05-AUG-13:55 | 313.48 | 22-AUG-21:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 188.76 | 02-SEP-14:10 | 589.54 | 12-SEP-02:55 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 | 18-OCT-14:20 | 524.91 | 30-OCT-22:00 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 628.85 | 28-NOV-06:47 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 826.09 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.46 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 188.76 | 1061.18 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2914.63 | 05-JAN-21:55 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2021.67 | 01-FEB-21:01 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2212.77 | 02-MAR-23:00 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1523.19 | 27-APR-02:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 266.77 | 20-MAY-16:20 | 2999.01 | 22-MAY-04:05 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 475.93 | 24-JUN-14:10 | 1263.68 | 14-JUN-02:00 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 490.48 | 30-JUL-11:53 | 701.89 | 08-JUL-10:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 535.45 | 05-AUG-13:55 | 867.63 | 23-AUG-02:55 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 559.54 | 02-SEP-14:50 | 1710.48 | 12-SEP-02:55 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 | 18-OCT-14:00 | 1496.92 | 30-OCT-22:00 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1666.47 | 28-NOV-06:47 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2425.06 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 701.89 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 559.54 | 2999.01 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1178.08 | 02-JAN-08:09 | 947.12 | 02-JAN-07:10 | 678.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 170.78 | 05-JAN-21:55 |
| February | 1178.08 | 01-FEB-08:09 | 947.12 | 01-FEB-07:10 | 678.98 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 114.43 | 01-FEB-21:01 |
| March | 1178.08 | 01-MAR-08:09 | 947.12 | 01-MAR-07:10 | 678.98 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 124.46 | 02-MAR-23:00 |
| April | 1178.08 | 03-APR-07:10 | 947.12 | 03-APR-06:10 | 678.98 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 86.95 | 27-APR-02:00 |
| May | 1178.08 | 01-MAY-07:10 | 947.12 | 01-MAY-06:10 | 678.98 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 | 20-MAY-15:53 | 179.19 | 22-MAY-04:00 |
| June | 1178.08 | 01-JUN-07:10 | 947.12 | 01-JUN-06:10 | 678.98 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.45 | 24-JUN-14:10 | 73.12 | 14-JUN-02:00 |
| July | 186.01 | 03-JUL-07:10 | 526.18 | 03-JUL-07:10 | 357.36 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.46 | 30-JUL-11:53 | 38.75 | 05-JUL-00:53 |
| August | 186.01 | 01-AUG-07:10 | 526.18 | 01-AUG-07:10 | 357.36 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.65 | 05-AUG-13:55 | 48.74 | 23-AUG-02:55 |
| September | 1178.08 | 18-SEP-07:10 | 947.12 | 05-SEP-06:10 | 678.98 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 | 02-SEP-14:10 | 98.67 | 12-SEP-02:55 |
| October | 1178.08 | 02-OCT-07:10 | 947.12 | 02-OCT-06:10 | 678.98 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.08 | 15-OCT-14:00 | 81.60 | 30-OCT-22:00 |
| November | 1178.08 | 01-NOV-07:10 | 947.12 | 01-NOV-06:10 | 678.98 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 94.33 | 28-NOV-06:45 |
| December | 1178.08 | 01-DEC-08:09 | 947.12 | 01-DEC-07:10 | 678.98 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 141.46 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.75 | |||||
| Maximum of Months | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 | 179.19 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1058.78 | 05-JAN-21:55 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 757.69 | 01-FEB-21:01 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 739.13 | 02-MAR-23:00 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 505.14 | 27-APR-02:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.21 | 20-MAY-15:53 | 988.67 | 22-MAY-04:05 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.60 | 24-JUN-14:10 | 431.00 | 14-JUN-02:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 196.36 | 30-JUL-11:53 | 230.72 | 05-JUL-00:53 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 215.00 | 05-AUG-13:55 | 290.64 | 22-AUG-20:55 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 236.58 | 02-SEP-14:10 | 573.46 | 12-SEP-02:55 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 55.28 | 15-OCT-14:10 | 483.02 | 30-OCT-22:00 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 628.86 | 28-NOV-06:45 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 821.60 | 31-DEC-02:52 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.72 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 236.58 | 1058.78 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2902.02 | 05-JAN-21:55 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2016.46 | 01-FEB-21:01 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2080.60 | 02-MAR-23:00 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1457.84 | 27-APR-02:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.01 | 20-MAY-15:53 | 2944.16 | 22-MAY-04:05 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 536.24 | 24-JUN-14:10 | 1245.96 | 14-JUN-02:00 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 552.52 | 30-JUL-11:53 | 652.40 | 05-JUL-00:53 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 618.24 | 05-AUG-13:55 | 800.26 | 23-AUG-02:55 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 686.58 | 02-SEP-14:10 | 1657.64 | 12-SEP-02:55 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 154.86 | 15-OCT-14:10 | 1371.39 | 30-OCT-22:00 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1666.45 | 28-NOV-06:50 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2382.26 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 652.40 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 686.58 | 2944.16 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1061.29 | 05-JAN-21:55 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 759.40 | 01-FEB-21:01 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 781.32 | 02-MAR-23:00 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 528.02 | 27-APR-02:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.24 | 20-MAY-16:20 | 1008.67 | 22-MAY-04:05 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 161.90 | 24-JUN-14:10 | 437.83 | 14-JUN-02:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 172.59 | 30-JUL-11:53 | 246.13 | 08-JUL-10:00 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 184.53 | 05-AUG-13:55 | 315.30 | 22-AUG-21:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 187.84 | 02-SEP-14:10 | 591.67 | 12-SEP-02:55 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 | 18-OCT-14:20 | 527.45 | 30-OCT-22:00 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 628.85 | 28-NOV-06:50 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 827.12 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 246.13 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 187.84 | 1061.29 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 14633.48 | 02-JAN-08:09 | 6469.32 | 02-JAN-07:10 | 6325.65 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2915.22 | 05-JAN-21:55 |
| February | 14633.48 | 01-FEB-08:09 | 6469.32 | 01-FEB-07:10 | 6325.65 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 2021.66 | 01-FEB-21:01 |
| March | 14633.48 | 01-MAR-08:09 | 6469.32 | 01-MAR-07:10 | 6325.65 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2216.92 | 02-MAR-23:00 |
| April | 14633.48 | 03-APR-07:10 | 6469.32 | 03-APR-06:10 | 6325.65 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1530.22 | 27-APR-02:00 |
| May | 14633.48 | 01-MAY-07:10 | 6469.32 | 01-MAY-06:10 | 6325.65 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.12 | 20-MAY-16:20 | 3006.78 | 22-MAY-04:05 |
| June | 14633.48 | 01-JUN-07:10 | 6469.32 | 01-JUN-06:10 | 6325.65 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 472.36 | 24-JUN-14:10 | 1268.20 | 14-JUN-02:00 |
| July | 2310.55 | 03-JUL-07:10 | 3594.07 | 03-JUL-07:10 | 3329.29 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 484.03 | 30-JUL-11:53 | 711.62 | 08-JUL-10:00 |
| August | 2310.55 | 01-AUG-07:10 | 3594.07 | 01-AUG-07:10 | 3329.29 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 531.25 | 05-AUG-13:55 | 874.84 | 23-AUG-02:55 |
| September | 14633.48 | 18-SEP-07:10 | 6469.32 | 05-SEP-06:10 | 6325.65 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 557.39 | 02-SEP-14:50 | 1718.17 | 12-SEP-02:55 |
| October | 14633.48 | 02-OCT-07:10 | 6469.32 | 02-OCT-06:10 | 6325.65 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 | 18-OCT-14:20 | 1507.65 | 30-OCT-22:00 |
| November | 14633.48 | 01-NOV-07:10 | 6469.32 | 01-NOV-06:10 | 6325.65 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1666.43 | 28-NOV-06:50 |
| December | 14633.48 | 01-DEC-08:09 | 6469.32 | 01-DEC-07:10 | 6325.65 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 2429.19 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2310.55 | 3594.07 | 3329.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 711.62 | |||||
| Maximum of Months | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 557.39 | 3006.78 |
Report: PeakSpaceGainsMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1178.08 | 02-JAN-08:09 | 947.12 | 02-JAN-07:10 | 678.98 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 170.88 | 05-JAN-21:55 |
| February | 1178.08 | 01-FEB-08:09 | 947.12 | 01-FEB-07:10 | 678.98 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 114.43 | 01-FEB-21:01 |
| March | 1178.08 | 01-MAR-08:09 | 947.12 | 01-MAR-07:10 | 678.98 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 125.04 | 02-MAR-23:00 |
| April | 1178.08 | 03-APR-07:10 | 947.12 | 03-APR-06:10 | 678.98 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 87.88 | 27-APR-02:00 |
| May | 1178.08 | 01-MAY-07:10 | 947.12 | 01-MAY-06:10 | 678.98 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.92 | 20-MAY-15:53 | 180.35 | 22-MAY-04:00 |
| June | 1178.08 | 01-JUN-07:10 | 947.12 | 01-JUN-06:10 | 678.98 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.87 | 24-JUN-14:10 | 73.77 | 14-JUN-02:00 |
| July | 186.01 | 03-JUL-07:10 | 526.18 | 03-JUL-07:10 | 357.36 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.66 | 30-JUL-11:53 | 39.35 | 05-JUL-00:53 |
| August | 186.01 | 01-AUG-07:10 | 526.18 | 01-AUG-07:10 | 357.36 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.08 | 05-AUG-13:55 | 49.66 | 23-AUG-02:55 |
| September | 1178.08 | 18-SEP-07:10 | 947.12 | 05-SEP-06:10 | 678.98 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.11 | 02-SEP-14:10 | 99.78 | 12-SEP-02:55 |
| October | 1178.08 | 02-OCT-07:10 | 947.12 | 02-OCT-06:10 | 678.98 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 18-OCT-14:00 | 82.70 | 30-OCT-22:00 |
| November | 1178.08 | 01-NOV-07:10 | 947.12 | 01-NOV-06:10 | 678.98 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 94.33 | 28-NOV-06:50 |
| December | 1178.08 | 01-DEC-08:09 | 947.12 | 01-DEC-07:10 | 678.98 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 141.90 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 186.01 | 526.18 | 357.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.35 | |||||
| Maximum of Months | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 31.11 | 180.35 |
Report: PeakSpaceGainsMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3037.14 | 02-JAN-08:09 | 1342.69 | 02-JAN-07:10 | 1312.87 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1058.71 | 05-JAN-21:55 |
| February | 3037.14 | 01-FEB-08:09 | 1342.69 | 01-FEB-07:10 | 1312.87 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 757.60 | 01-FEB-21:01 |
| March | 3037.14 | 01-MAR-08:09 | 1342.69 | 01-MAR-07:10 | 1312.87 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 740.28 | 02-MAR-23:00 |
| April | 3037.14 | 03-APR-07:10 | 1342.69 | 03-APR-06:10 | 1312.87 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 507.61 | 27-APR-02:00 |
| May | 3037.14 | 01-MAY-07:10 | 1342.69 | 01-MAY-06:10 | 1312.87 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.12 | 20-MAY-16:20 | 993.70 | 22-MAY-04:05 |
| June | 3037.14 | 01-JUN-07:10 | 1342.69 | 01-JUN-06:10 | 1312.87 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.44 | 24-JUN-14:10 | 433.72 | 14-JUN-02:00 |
| July | 479.55 | 03-JUL-07:10 | 745.94 | 03-JUL-07:10 | 690.98 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 192.21 | 30-JUL-11:53 | 233.70 | 05-JUL-00:53 |
| August | 479.55 | 01-AUG-07:10 | 745.94 | 01-AUG-07:10 | 690.98 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.95 | 05-AUG-13:55 | 293.30 | 22-AUG-21:00 |
| September | 3037.14 | 18-SEP-07:10 | 1342.69 | 05-SEP-06:10 | 1312.87 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 234.85 | 02-SEP-14:10 | 576.01 | 12-SEP-02:55 |
| October | 3037.14 | 02-OCT-07:10 | 1342.69 | 02-OCT-06:10 | 1312.87 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.23 | 15-OCT-14:10 | 485.28 | 30-OCT-22:00 |
| November | 3037.14 | 01-NOV-07:10 | 1342.69 | 01-NOV-06:10 | 1312.87 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 628.85 | 28-NOV-06:50 |
| December | 3037.14 | 01-DEC-08:09 | 1342.69 | 01-DEC-07:10 | 1312.87 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 821.59 | 31-DEC-02:52 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.70 | |||||
| Maximum of Months | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 234.85 | 1058.71 |
Report: PeakSpaceGainsMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 9663.62 | 02-JAN-08:09 | 4272.19 | 02-JAN-07:10 | 4177.31 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1915.47 | 05-JAN-21:55 |
| February | 9663.62 | 01-FEB-08:09 | 4272.19 | 01-FEB-07:10 | 4177.31 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1331.36 | 01-FEB-21:01 |
| March | 9663.62 | 01-MAR-08:09 | 4272.19 | 01-MAR-07:10 | 4177.31 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1376.51 | 02-MAR-23:00 |
| April | 9663.62 | 03-APR-07:10 | 4272.19 | 03-APR-06:10 | 4177.31 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 967.45 | 27-APR-02:00 |
| May | 9663.62 | 01-MAY-07:10 | 4272.19 | 01-MAY-06:10 | 4177.31 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 189.82 | 20-MAY-15:53 | 1949.71 | 22-MAY-04:05 |
| June | 9663.62 | 01-JUN-07:10 | 4272.19 | 01-JUN-06:10 | 4177.31 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 343.93 | 24-JUN-14:10 | 828.52 | 14-JUN-02:00 |
| July | 1525.83 | 03-JUL-07:10 | 2373.44 | 03-JUL-07:10 | 2198.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 354.60 | 30-JUL-11:53 | 442.56 | 08-JUL-10:00 |
| August | 1525.83 | 01-AUG-07:10 | 2373.44 | 01-AUG-07:10 | 2198.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 402.30 | 05-AUG-13:55 | 533.00 | 23-AUG-02:55 |
| September | 9663.62 | 18-SEP-07:10 | 4272.19 | 05-SEP-06:10 | 4177.31 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 448.47 | 02-SEP-14:10 | 1098.83 | 12-SEP-02:55 |
| October | 9663.62 | 02-OCT-07:10 | 4272.19 | 02-OCT-06:10 | 4177.31 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.79 | 15-OCT-14:10 | 910.99 | 30-OCT-22:00 |
| November | 9663.62 | 01-NOV-07:10 | 4272.19 | 01-NOV-06:10 | 4177.31 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1100.49 | 28-NOV-06:47 |
| December | 9663.62 | 01-DEC-08:09 | 4272.19 | 01-DEC-07:10 | 4177.31 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1571.09 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 1525.83 | 2373.44 | 2198.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 442.56 | |||||
| Maximum of Months | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 448.47 | 1949.71 |
Report: PeakSpaceGainsMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 4969.86 | 02-JAN-08:09 | 2197.13 | 02-JAN-07:10 | 2864.44 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 994.66 | 05-JAN-21:55 |
| February | 4969.86 | 01-FEB-08:09 | 2197.13 | 01-FEB-07:10 | 2864.44 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 685.58 | 01-FEB-21:01 |
| March | 4969.86 | 01-MAR-08:09 | 2197.13 | 01-MAR-07:10 | 2864.44 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 732.99 | 02-MAR-23:00 |
| April | 4969.86 | 03-APR-07:10 | 2197.13 | 03-APR-06:10 | 2864.44 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 525.09 | 27-APR-02:00 |
| May | 4969.86 | 01-MAY-07:10 | 2197.13 | 01-MAY-06:10 | 2864.44 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.16 | 20-MAY-16:20 | 1035.66 | 22-MAY-04:00 |
| June | 4969.86 | 01-JUN-07:10 | 2197.13 | 01-JUN-06:10 | 2864.44 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 167.23 | 24-JUN-14:10 | 446.32 | 14-JUN-02:00 |
| July | 2615.72 | 03-JUL-07:10 | 1220.63 | 03-JUL-07:10 | 1507.60 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.40 | 30-JUL-11:53 | 257.87 | 08-JUL-10:00 |
| August | 2615.72 | 01-AUG-07:10 | 1220.63 | 01-AUG-07:10 | 1507.60 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 195.86 | 05-AUG-13:55 | 298.65 | 23-AUG-02:55 |
| September | 4969.86 | 05-SEP-07:10 | 2197.13 | 05-SEP-06:10 | 2864.44 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 219.75 | 02-SEP-14:10 | 603.73 | 12-SEP-02:55 |
| October | 4969.86 | 02-OCT-07:10 | 2197.13 | 02-OCT-06:10 | 2864.44 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.26 | 15-OCT-14:10 | 498.31 | 30-OCT-22:00 |
| November | 4969.86 | 01-NOV-07:10 | 2197.13 | 01-NOV-06:10 | 2864.44 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 565.96 | 28-NOV-06:50 |
| December | 4969.86 | 01-DEC-08:09 | 2197.13 | 01-DEC-07:10 | 2864.44 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 837.10 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2615.72 | 1220.63 | 1507.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.87 | |||||
| Maximum of Months | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 219.75 | 1035.66 |
Report: PeakSpaceGainsMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3350.23 | 02-JAN-08:09 | 2693.36 | 02-JAN-07:10 | 1930.85 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 508.09 | 05-JAN-21:55 |
| February | 3350.23 | 01-FEB-08:09 | 2693.36 | 01-FEB-07:10 | 1930.85 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 343.02 | 01-FEB-21:01 |
| March | 3350.23 | 01-MAR-08:09 | 2693.36 | 01-MAR-07:10 | 1930.85 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 366.24 | 02-MAR-23:00 |
| April | 3350.23 | 03-APR-07:10 | 2693.36 | 03-APR-06:10 | 1930.85 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 267.44 | 27-APR-02:00 |
| May | 3350.23 | 01-MAY-07:10 | 2693.36 | 01-MAY-06:10 | 1930.85 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.46 | 20-MAY-15:53 | 567.90 | 22-MAY-04:00 |
| June | 3350.23 | 01-JUN-07:10 | 2693.36 | 01-JUN-06:10 | 1930.85 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.54 | 24-JUN-13:52 | 228.23 | 14-JUN-02:00 |
| July | 528.98 | 03-JUL-07:10 | 1496.31 | 03-JUL-07:10 | 1016.24 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.43 | 30-JUL-11:53 | 138.22 | 08-JUL-10:00 |
| August | 528.98 | 01-AUG-07:10 | 1496.31 | 01-AUG-07:10 | 1016.24 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 82.01 | 05-AUG-13:55 | 158.17 | 23-AUG-02:55 |
| September | 3350.23 | 18-SEP-07:10 | 2693.36 | 05-SEP-06:10 | 1930.85 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.27 | 02-SEP-14:10 | 310.30 | 12-SEP-02:55 |
| October | 3350.23 | 02-OCT-07:10 | 2693.36 | 02-OCT-06:10 | 1930.85 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 | 15-OCT-14:10 | 239.17 | 30-OCT-22:00 |
| November | 3350.23 | 01-NOV-07:10 | 2693.36 | 01-NOV-06:10 | 1930.85 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 282.98 | 28-NOV-06:47 |
| December | 3350.23 | 01-DEC-08:09 | 2693.36 | 01-DEC-07:10 | 1930.85 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 420.74 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 528.98 | 1496.31 | 1016.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.22 | |||||
| Maximum of Months | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 89.27 | 567.90 |
Report: PeakSpaceGainsMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 2098.51 | 02-JAN-08:09 | 2153.53 | 02-JAN-07:10 | 604.72 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 147916.34 | 27-JAN-07:01 |
| February | 2098.51 | 01-FEB-08:09 | 2153.53 | 01-FEB-07:10 | 604.72 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 142547.18 | 01-FEB-07:01 |
| March | 2098.51 | 01-MAR-08:09 | 2153.53 | 01-MAR-07:10 | 604.72 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 121486.55 | 06-MAR-07:01 |
| April | 2098.51 | 03-APR-07:10 | 2153.53 | 03-APR-06:10 | 604.72 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 71860.10 | 28-APR-06:01 |
| May | 2098.51 | 01-MAY-07:10 | 2153.53 | 01-MAY-06:10 | 604.72 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9007.10 | 19-MAY-14:03 | 63746.47 | 08-MAY-06:01 |
| June | 2098.51 | 01-JUN-07:10 | 2153.53 | 01-JUN-06:10 | 604.72 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21581.13 | 29-JUN-14:01 | 54649.06 | 16-JUN-06:01 |
| July | 331.34 | 03-JUL-07:10 | 1196.41 | 03-JUL-07:10 | 318.27 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32935.03 | 17-JUL-14:01 | 38005.32 | 05-JUL-06:01 |
| August | 331.34 | 01-AUG-07:10 | 1196.41 | 01-AUG-07:10 | 318.27 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26773.70 | 09-AUG-14:01 | 47235.26 | 28-AUG-06:01 |
| September | 2098.51 | 18-SEP-07:10 | 2153.53 | 05-SEP-06:10 | 604.72 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10438.39 | 01-SEP-14:02 | 55845.08 | 18-SEP-06:01 |
| October | 2098.51 | 02-OCT-07:10 | 2153.53 | 02-OCT-06:10 | 604.72 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3156.97 | 18-OCT-14:10 | 75540.32 | 10-OCT-06:01 |
| November | 2098.51 | 01-NOV-07:10 | 2153.53 | 01-NOV-06:10 | 604.72 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 100120.30 | 27-NOV-07:01 |
| December | 2098.51 | 01-DEC-08:09 | 2153.53 | 01-DEC-07:10 | 604.72 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 145602.13 | 29-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38005.32 | |||||
| Maximum of Months | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 32935.03 | 147916.34 |
Report: PeakSpaceGainsMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 463.87 | 02-JAN-08:09 | 3661.88 | 02-JAN-07:10 | 2227.90 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 463.87 | 01-FEB-08:09 | 3661.88 | 01-FEB-07:10 | 2227.90 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 01-FEB-00:05 |
| March | 463.87 | 01-MAR-08:09 | 3661.88 | 01-MAR-07:10 | 2227.90 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 463.87 | 03-APR-07:10 | 3661.88 | 03-APR-06:10 | 2227.90 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 463.87 | 01-MAY-07:10 | 3661.88 | 01-MAY-06:10 | 2227.90 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 463.87 | 01-JUN-07:10 | 3661.88 | 01-JUN-06:10 | 2227.90 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 01-JUN-00:03 |
| July | 73.24 | 03-JUL-07:10 | 2034.38 | 03-JUL-07:10 | 1172.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 01-JUL-00:03 |
| August | 73.24 | 01-AUG-07:10 | 2034.38 | 01-AUG-07:10 | 1172.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 01-AUG-00:03 |
| September | 463.87 | 18-SEP-07:10 | 3661.88 | 05-SEP-06:10 | 2227.90 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 01-SEP-00:03 |
| October | 463.87 | 02-OCT-07:10 | 3661.88 | 02-OCT-06:10 | 2227.90 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 463.87 | 01-NOV-07:10 | 3661.88 | 01-NOV-06:10 | 2227.90 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 463.87 | 01-DEC-08:09 | 3661.88 | 01-DEC-07:10 | 2227.90 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 73.24 | 2034.38 | 1172.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
| Maximum of Months | 463.87 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1165.88 | 02-JAN-08:09 | 1656.56 | 02-JAN-07:10 | 671.91 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 529.20 | 05-JAN-21:55 |
| February | 1165.88 | 01-FEB-08:09 | 1656.56 | 01-FEB-07:10 | 671.91 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 326.30 | 01-FEB-21:01 |
| March | 1165.88 | 01-MAR-08:09 | 1656.56 | 01-MAR-07:10 | 671.91 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 392.92 | 02-MAR-23:00 |
| April | 1165.88 | 03-APR-07:10 | 1656.56 | 03-APR-06:10 | 671.91 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 292.28 | 27-APR-02:00 |
| May | 1165.88 | 01-MAY-07:10 | 1656.56 | 01-MAY-06:10 | 671.91 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 38.93 | 20-MAY-15:53 | 610.58 | 22-MAY-04:00 |
| June | 1165.88 | 01-JUN-07:10 | 1656.56 | 01-JUN-06:10 | 671.91 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.52 | 24-JUN-14:10 | 257.50 | 14-JUN-02:00 |
| July | 184.09 | 03-JUL-07:10 | 920.31 | 03-JUL-07:10 | 353.64 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 68.55 | 30-JUL-11:53 | 156.58 | 08-JUL-10:00 |
| August | 184.09 | 01-AUG-07:10 | 920.31 | 01-AUG-07:10 | 353.64 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.74 | 05-AUG-13:55 | 175.65 | 23-AUG-02:55 |
| September | 1165.88 | 18-SEP-07:10 | 1656.56 | 05-SEP-06:10 | 671.91 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 96.09 | 02-SEP-14:10 | 341.75 | 12-SEP-02:55 |
| October | 1165.88 | 02-OCT-07:10 | 1656.56 | 02-OCT-06:10 | 671.91 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.08 | 15-OCT-14:00 | 262.20 | 30-OCT-22:00 |
| November | 1165.88 | 01-NOV-07:10 | 1656.56 | 01-NOV-06:10 | 671.91 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 299.53 | 26-NOV-20:00 |
| December | 1165.88 | 01-DEC-08:09 | 1656.56 | 01-DEC-07:10 | 671.91 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 425.33 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 184.09 | 920.31 | 353.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.58 | |||||
| Maximum of Months | 1165.88 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 96.09 | 610.58 |
Report: PeakSpaceGainsMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 2705.96 | 02-JAN-08:09 | 4699.41 | 02-JAN-07:10 | 4210.73 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2301.00 | 05-JAN-21:55 |
| February | 2705.96 | 01-FEB-08:09 | 4699.41 | 01-FEB-07:10 | 4210.73 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1598.84 | 01-FEB-21:01 |
| March | 2705.96 | 01-MAR-08:09 | 4699.41 | 01-MAR-07:10 | 4210.73 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1709.25 | 02-MAR-23:00 |
| April | 2705.96 | 03-APR-07:10 | 4699.41 | 03-APR-06:10 | 4210.73 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1228.47 | 27-APR-02:00 |
| May | 2705.96 | 01-MAY-07:10 | 4699.41 | 01-MAY-06:10 | 4210.73 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 156.36 | 20-MAY-15:53 | 2458.13 | 22-MAY-04:00 |
| June | 2705.96 | 01-JUN-07:10 | 4699.41 | 01-JUN-06:10 | 4210.73 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 212.95 | 24-JUN-14:10 | 1031.20 | 14-JUN-02:00 |
| July | 1424.19 | 03-JUL-07:10 | 2610.78 | 03-JUL-07:10 | 2216.18 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 256.14 | 30-JUL-11:53 | 709.59 | 08-JUL-10:00 |
| August | 1424.19 | 01-AUG-07:10 | 2610.78 | 01-AUG-07:10 | 2216.18 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 344.78 | 05-AUG-14:00 | 746.13 | 22-AUG-21:00 |
| September | 2705.96 | 05-SEP-07:10 | 4699.41 | 05-SEP-06:10 | 4210.73 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 372.00 | 02-SEP-14:50 | 1414.71 | 12-SEP-02:55 |
| October | 2705.96 | 02-OCT-07:10 | 4699.41 | 02-OCT-06:10 | 4210.73 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.31 | 18-OCT-14:30 | 1161.57 | 30-OCT-22:00 |
| November | 2705.96 | 01-NOV-07:10 | 4699.41 | 01-NOV-06:10 | 4210.73 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1320.56 | 28-NOV-06:42 |
| December | 2705.96 | 01-DEC-08:09 | 4699.41 | 01-DEC-07:10 | 4210.73 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1862.62 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 1424.19 | 2610.78 | 2216.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 709.59 | |||||
| Maximum of Months | 2705.96 | 4699.41 | 4210.73 | 0.00 | 0.00 | 0.00 | 0.00 | 372.00 | 2458.13 |
Report: PeakSpaceGainsMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 13145.35 | 02-JAN-16:10 | 4288.47 | 02-JAN-07:10 | 1578.10 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 953.07 | 05-JAN-21:55 |
| February | 13145.35 | 01-FEB-16:10 | 4288.47 | 01-FEB-07:10 | 1578.10 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 648.62 | 01-FEB-21:01 |
| March | 13145.35 | 01-MAR-16:10 | 4288.47 | 01-MAR-07:10 | 1578.10 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 727.07 | 02-MAR-23:00 |
| April | 13145.35 | 03-APR-15:09 | 4288.47 | 03-APR-06:10 | 1578.10 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 540.38 | 15-APR-08:00 |
| May | 13145.35 | 01-MAY-15:09 | 4288.47 | 01-MAY-06:10 | 1578.10 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.57 | 20-MAY-16:20 | 1066.77 | 22-MAY-04:00 |
| June | 13145.35 | 01-JUN-15:09 | 4288.47 | 01-JUN-06:10 | 1578.10 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.98 | 24-JUN-14:10 | 442.75 | 14-JUN-02:00 |
| July | 4843.02 | 03-JUL-07:10 | 2382.48 | 03-JUL-07:10 | 830.58 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 115.40 | 30-JUL-11:50 | 329.09 | 08-JUL-10:00 |
| August | 4843.02 | 01-AUG-07:10 | 2382.48 | 01-AUG-07:10 | 830.58 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 157.29 | 05-AUG-13:55 | 320.08 | 23-AUG-02:55 |
| September | 13145.35 | 05-SEP-15:09 | 4288.47 | 05-SEP-06:10 | 1578.10 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.11 | 02-SEP-14:10 | 593.53 | 12-SEP-02:55 |
| October | 13145.35 | 02-OCT-15:09 | 4288.47 | 02-OCT-06:10 | 1578.10 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.58 | 18-OCT-14:00 | 484.24 | 30-OCT-22:00 |
| November | 13145.35 | 01-NOV-15:09 | 4288.47 | 01-NOV-06:10 | 1578.10 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 609.98 | 28-NOV-06:45 |
| December | 13145.35 | 01-DEC-16:10 | 4288.47 | 01-DEC-07:10 | 1578.10 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 822.39 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 4843.02 | 2382.48 | 830.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.08 | |||||
| Maximum of Months | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 176.11 | 1066.77 |
Report: PeakSpaceGainsMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 3077.20 | 02-JAN-08:09 | 1953.00 | 02-JAN-07:10 | 6399.12 | 02-JAN-10:09 | 14425.49 | 02-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 522.08 | 05-JAN-21:55 |
| February | 3077.20 | 01-FEB-08:09 | 1953.00 | 01-FEB-07:10 | 6399.12 | 01-FEB-10:09 | 14425.49 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 362.84 | 17-FEB-04:10 |
| March | 3077.20 | 01-MAR-08:09 | 1953.00 | 01-MAR-07:10 | 6399.12 | 01-MAR-10:09 | 14425.49 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 421.50 | 17-MAR-05:00 |
| April | 3077.20 | 03-APR-07:10 | 1953.00 | 03-APR-06:10 | 6399.12 | 03-APR-09:09 | 14425.49 | 03-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 315.41 | 15-APR-08:20 |
| May | 3077.20 | 01-MAY-07:10 | 1953.00 | 01-MAY-06:10 | 6399.12 | 01-MAY-09:09 | 14425.49 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 24.23 | 20-MAY-16:00 | 594.46 | 22-MAY-04:10 |
| June | 3077.20 | 01-JUN-07:10 | 1953.00 | 01-JUN-06:10 | 6399.12 | 01-JUN-09:09 | 14425.49 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 33.63 | 24-JUN-14:00 | 242.22 | 14-JUN-02:10 |
| July | 485.87 | 03-JUL-07:10 | 1085.00 | 03-JUL-07:10 | 6399.12 | 03-JUL-09:09 | 14425.49 | 03-JUL-09:09 | 0.00 | 0.00 | 0.00 | 42.21 | 30-JUL-12:00 | 173.49 | 08-JUL-09:30 |
| August | 485.87 | 01-AUG-07:10 | 1085.00 | 01-AUG-07:10 | 6399.12 | 01-AUG-09:09 | 14425.49 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 60.59 | 05-AUG-14:00 | 185.88 | 22-AUG-22:50 |
| September | 3077.20 | 18-SEP-07:10 | 1953.00 | 05-SEP-06:10 | 6399.12 | 01-SEP-09:09 | 14425.49 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 64.53 | 02-SEP-14:40 | 322.76 | 12-SEP-02:55 |
| October | 3077.20 | 02-OCT-07:10 | 1953.00 | 02-OCT-06:10 | 6399.12 | 02-OCT-09:09 | 14425.49 | 02-OCT-09:09 | 0.00 | 0.00 | 0.00 | 3.62 | 15-OCT-15:17 | 286.90 | 30-OCT-22:34 |
| November | 3077.20 | 01-NOV-07:10 | 1953.00 | 01-NOV-06:10 | 6399.12 | 01-NOV-09:09 | 14425.49 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 334.93 | 28-NOV-06:00 |
| December | 3077.20 | 01-DEC-08:09 | 1953.00 | 01-DEC-07:10 | 6399.12 | 01-DEC-10:09 | 14425.49 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 570.66 | 01-DEC-05:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 485.87 | 1085.00 | 6399.12 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 173.49 | ||||||
| Maximum of Months | 3077.20 | 1953.00 | 6399.12 | 14425.49 | 0.00 | 0.00 | 0.00 | 64.53 | 594.46 |
Report: PeakSpaceGainsMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 38654.47 | 02-JAN-09:09 | 2746.41 | 02-JAN-07:10 | 1999.46 | 02-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2004.85 | 05-JAN-21:55 |
| February | 38654.47 | 01-FEB-09:09 | 2746.41 | 01-FEB-07:10 | 1999.46 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1370.30 | 01-FEB-21:01 |
| March | 38654.47 | 01-MAR-09:09 | 2746.41 | 01-MAR-07:10 | 1999.46 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1505.69 | 17-MAR-05:03 |
| April | 38654.47 | 03-APR-08:09 | 2746.41 | 03-APR-06:10 | 1999.46 | 03-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1037.64 | 27-APR-02:00 |
| May | 38654.47 | 01-MAY-08:09 | 2746.41 | 01-MAY-06:10 | 1999.46 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 101.80 | 20-MAY-16:04 | 2088.43 | 22-MAY-04:00 |
| June | 38654.47 | 01-JUN-08:09 | 2746.41 | 01-JUN-06:10 | 1999.46 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.35 | 24-JUN-14:00 | 887.71 | 14-JUN-02:00 |
| July | 14241.12 | 03-JUL-16:10 | 1525.78 | 03-JUL-07:10 | 1999.46 | 03-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 189.98 | 30-JUL-12:00 | 612.14 | 08-JUL-10:00 |
| August | 14241.12 | 01-AUG-16:10 | 1525.78 | 01-AUG-07:10 | 1999.46 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 266.44 | 05-AUG-13:50 | 625.83 | 23-AUG-02:55 |
| September | 38654.47 | 05-SEP-08:09 | 2746.41 | 05-SEP-06:10 | 1999.46 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 292.83 | 02-SEP-14:34 | 1188.62 | 12-SEP-02:55 |
| October | 38654.47 | 02-OCT-08:09 | 2746.41 | 02-OCT-06:10 | 1999.46 | 02-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9.70 | 18-OCT-14:00 | 958.10 | 30-OCT-22:00 |
| November | 38654.47 | 01-NOV-08:09 | 2746.41 | 01-NOV-06:10 | 1999.46 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1319.72 | 28-NOV-06:03 |
| December | 38654.47 | 01-DEC-09:09 | 2746.41 | 01-DEC-07:10 | 1999.46 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1677.80 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 14241.12 | 1525.78 | 1999.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 612.14 | |||||
| Maximum of Months | 38654.47 | 2746.41 | 1999.46 | 0.00 | 0.00 | 0.00 | 0.00 | 292.83 | 2088.43 |
Report: PeakSpaceGainsMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 4896.76 | 02-JAN-08:09 | 5991.24 | 02-JAN-07:10 | 5291.26 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2201.67 | 05-JAN-21:55 |
| February | 4896.76 | 01-FEB-08:09 | 5991.24 | 01-FEB-07:10 | 5291.26 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 1522.44 | 01-FEB-21:01 |
| March | 4896.76 | 01-MAR-08:09 | 5991.24 | 01-MAR-07:10 | 5291.26 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1606.02 | 02-MAR-23:00 |
| April | 4896.76 | 03-APR-07:10 | 5991.24 | 03-APR-06:10 | 5291.26 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1181.89 | 27-APR-02:00 |
| May | 4896.76 | 01-MAY-07:10 | 5991.24 | 01-MAY-06:10 | 5291.26 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.93 | 20-MAY-15:53 | 2357.63 | 22-MAY-04:00 |
| June | 4896.76 | 01-JUN-07:10 | 5991.24 | 01-JUN-06:10 | 5291.26 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 226.29 | 24-JUN-14:10 | 1005.71 | 14-JUN-02:00 |
| July | 773.17 | 03-JUL-07:10 | 3328.47 | 03-JUL-07:10 | 2784.88 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 263.26 | 30-JUL-11:53 | 684.15 | 08-JUL-10:00 |
| August | 773.17 | 01-AUG-07:10 | 3328.47 | 01-AUG-07:10 | 2784.88 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 359.43 | 05-AUG-14:00 | 704.15 | 23-AUG-02:55 |
| September | 4896.76 | 18-SEP-07:10 | 5991.24 | 05-SEP-06:10 | 5291.26 | 05-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 383.36 | 02-SEP-14:10 | 1364.90 | 12-SEP-02:55 |
| October | 4896.76 | 02-OCT-07:10 | 5991.24 | 02-OCT-06:10 | 5291.26 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.78 | 18-OCT-14:00 | 1102.93 | 30-OCT-22:00 |
| November | 4896.76 | 01-NOV-07:10 | 5991.24 | 01-NOV-06:10 | 5291.26 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1257.66 | 28-NOV-06:45 |
| December | 4896.76 | 01-DEC-08:09 | 5991.24 | 01-DEC-07:10 | 5291.26 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 1810.66 | 01-DEC-04:55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 773.17 | 3328.47 | 2784.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 684.15 | |||||
| Maximum of Months | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 383.36 | 2357.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2233.81 | 13-JAN-15:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.46 |
| February | 3462.24 | 28-FEB-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 |
| March | 3457.68 | 01-MAR-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.20 |
| April | 4232.27 | 25-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 |
| May | 5608.81 | 19-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 0.00 |
| June | 5104.10 | 06-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 | 0.00 |
| July | 4850.21 | 17-JUL-16:00 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 41.29 | 0.00 |
| August | 5457.85 | 06-AUG-16:02 | 0.00 | 1587.06 | 1736.75 | 0.00 | 0.00 | 0.00 | 0.00 | 126.12 | 0.00 |
| September | 11102.44 | 02-SEP-15:22 | 0.00 | 1322.55 | 2026.21 | 0.00 | 0.00 | 0.00 | 0.00 | 115.10 | 0.00 |
| October | 6114.45 | 18-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 | 0.00 |
| November | 4005.37 | 03-NOV-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.55 |
| December | 2472.46 | 06-DEC-15:35 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.17 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2233.81 | 0.00 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 11102.44 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 126.12 | 137.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 10916.06 | 13-JAN-15:40 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.26 |
| February | 16690.93 | 28-FEB-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.39 |
| March | 16674.53 | 01-MAR-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.15 |
| April | 19225.27 | 25-APR-14:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.61 |
| May | 24335.37 | 19-MAY-14:07 | 43900.43 | 19407.96 | 18976.94 | 0.00 | 0.00 | 0.00 | 0.00 | 59.72 | 0.00 |
| June | 22593.04 | 06-JUN-14:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 | 0.00 |
| July | 18150.30 | 29-JUL-11:51 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.88 |
| August | 18620.19 | 07-AUG-14:02 | 23105.49 | 35940.66 | 33292.88 | 0.00 | 0.00 | 0.00 | 0.00 | 51.15 | 0.00 |
| September | 28301.73 | 25-SEP-14:15 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 18.26 | 0.00 |
| October | 26753.42 | 18-OCT-14:20 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 | 0.00 |
| November | 19148.26 | 03-NOV-14:04 | 73167.38 | 32346.60 | 31628.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.06 |
| December | 12105.70 | 07-DEC-14:20 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 271.22 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 10916.06 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 28301.73 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 59.72 | 271.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1089.31 | 13-JAN-16:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 |
| February | 1863.90 | 28-FEB-15:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 |
| March | 1927.31 | 02-MAR-15:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.78 |
| April | 2159.72 | 25-APR-14:02 | 5890.38 | 4735.58 | 3394.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 |
| May | 4022.89 | 19-MAY-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 0.00 |
| June | 4193.63 | 30-JUN-16:00 | 186.01 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 | 0.00 |
| July | 3784.51 | 17-JUL-15:35 | 372.02 | 1052.35 | 714.72 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 | 0.00 |
| August | 3599.36 | 07-AUG-15:13 | 1116.07 | 3157.06 | 2144.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 | 0.00 |
| September | 4207.59 | 25-SEP-14:50 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 | 0.00 |
| October | 3097.43 | 18-OCT-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.00 |
| November | 2034.42 | 01-NOV-14:01 | 9424.61 | 7576.93 | 5431.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.40 |
| December | 1235.12 | 06-DEC-16:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.92 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1089.31 | 186.01 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4207.59 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 16.92 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1895.53 | 13-JAN-15:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.16 |
| February | 2867.48 | 28-FEB-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.64 |
| March | 3023.82 | 02-MAR-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.85 |
| April | 3286.64 | 25-APR-14:02 | 15185.68 | 6713.44 | 6564.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.97 |
| May | 4553.70 | 19-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 0.00 |
| June | 4423.74 | 06-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 | 0.00 |
| July | 3720.64 | 17-JUL-16:00 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 41.29 | 0.00 |
| August | 3691.82 | 06-AUG-15:22 | 0.00 | 1587.06 | 1736.75 | 0.00 | 0.00 | 0.00 | 0.00 | 126.63 | 0.00 |
| September | 4422.80 | 27-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 8.01 | 0.00 |
| October | 3793.09 | 18-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 | 0.00 |
| November | 3192.39 | 08-NOV-15:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.56 |
| December | 2060.02 | 06-DEC-15:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.49 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1895.53 | 0.00 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4553.70 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 126.63 | 120.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 9306.95 | 13-JAN-15:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.18 |
| February | 14086.82 | 28-FEB-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.27 |
| March | 14770.89 | 02-MAR-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.16 |
| April | 16174.24 | 25-APR-14:02 | 73167.38 | 32346.60 | 31628.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.69 |
| May | 19142.62 | 19-MAY-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 85.61 | 0.00 |
| June | 19251.27 | 06-JUN-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 | 0.00 |
| July | 16538.75 | 30-JUL-19:51 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.95 |
| August | 16144.70 | 07-AUG-05:01 | 0.00 | 10195.65 | 11157.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 176.05 |
| September | 19065.24 | 27-SEP-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 | 0.00 |
| October | 16891.74 | 20-OCT-14:01 | 117067.81 | 51754.55 | 50605.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.07 |
| November | 15591.48 | 08-NOV-15:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.12 |
| December | 9989.62 | 06-DEC-15:10 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.65 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 9306.95 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 19251.27 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 85.61 | 350.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2209.32 | 13-JAN-15:40 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.13 |
| February | 3461.48 | 28-FEB-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.48 |
| March | 3456.79 | 01-MAR-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.18 |
| April | 4176.84 | 25-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 |
| May | 5526.79 | 19-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 0.00 |
| June | 4991.35 | 06-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 | 0.00 |
| July | 4767.50 | 17-JUL-16:00 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 41.29 | 0.00 |
| August | 4960.92 | 07-AUG-15:13 | 2877.29 | 4475.63 | 4145.91 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 | 0.00 |
| September | 10980.08 | 02-SEP-15:22 | 0.00 | 1322.55 | 2026.21 | 0.00 | 0.00 | 0.00 | 0.00 | 115.92 | 0.00 |
| October | 6085.00 | 18-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 | 0.00 |
| November | 3919.88 | 03-NOV-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.55 |
| December | 2407.89 | 06-DEC-15:35 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.06 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2209.32 | 0.00 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 10980.08 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 115.92 | 135.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 10753.32 | 13-JAN-15:10 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.67 |
| February | 16670.45 | 28-FEB-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.32 |
| March | 16653.82 | 01-MAR-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.07 |
| April | 18975.92 | 25-APR-14:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.61 |
| May | 23935.72 | 19-MAY-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 69.60 | 0.00 |
| June | 21976.49 | 06-JUN-14:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 | 0.00 |
| July | 17875.30 | 29-JUL-11:51 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.87 |
| August | 18430.67 | 11-AUG-15:10 | 18484.39 | 28752.53 | 26634.31 | 0.00 | 0.00 | 0.00 | 0.00 | 98.02 | 0.00 |
| September | 27776.66 | 25-SEP-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 0.00 |
| October | 26363.33 | 18-OCT-14:20 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 | 0.00 |
| November | 18461.46 | 03-NOV-14:04 | 73167.38 | 32346.60 | 31628.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.06 |
| December | 11775.62 | 07-DEC-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.44 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 10753.32 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 27776.66 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 98.02 | 285.44 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1081.56 | 13-JAN-16:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.32 |
| February | 1845.76 | 28-FEB-15:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 |
| March | 1911.73 | 02-MAR-15:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.76 |
| April | 2149.48 | 25-APR-14:02 | 5890.38 | 4735.58 | 3394.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.47 |
| May | 3993.94 | 19-MAY-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 0.00 |
| June | 4175.99 | 30-JUN-16:00 | 186.01 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 | 0.00 |
| July | 3714.09 | 17-JUL-15:23 | 558.04 | 1578.53 | 1072.07 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 | 0.00 |
| August | 3545.78 | 07-AUG-15:13 | 1116.07 | 3157.06 | 2144.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 | 0.00 |
| September | 4158.49 | 25-SEP-14:50 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 | 0.00 |
| October | 3064.30 | 18-OCT-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.00 |
| November | 2017.88 | 01-NOV-14:01 | 9424.61 | 7576.93 | 5431.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.34 |
| December | 1198.05 | 06-DEC-15:50 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.18 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1081.56 | 186.01 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4175.99 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 17.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1893.42 | 13-JAN-15:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.19 |
| February | 2861.87 | 28-FEB-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.63 |
| March | 3019.29 | 02-MAR-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.85 |
| April | 3282.97 | 25-APR-14:02 | 15185.68 | 6713.44 | 6564.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.99 |
| May | 4559.79 | 19-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 0.00 |
| June | 4430.56 | 06-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 | 0.00 |
| July | 3726.79 | 17-JUL-16:00 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 41.29 | 0.00 |
| August | 3687.68 | 06-AUG-15:22 | 0.00 | 1587.06 | 1736.75 | 0.00 | 0.00 | 0.00 | 0.00 | 126.54 | 0.00 |
| September | 4426.20 | 27-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 8.01 | 0.00 |
| October | 3790.66 | 18-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 | 0.00 |
| November | 3185.83 | 08-NOV-15:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.54 |
| December | 2056.10 | 06-DEC-15:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.48 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1893.42 | 0.00 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4559.79 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 126.54 | 120.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 9299.82 | 13-JAN-15:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.24 |
| February | 14062.15 | 28-FEB-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.23 |
| March | 14752.73 | 02-MAR-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.16 |
| April | 16161.56 | 25-APR-14:02 | 73167.38 | 32346.60 | 31628.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.72 |
| May | 19168.69 | 19-MAY-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 85.61 | 0.00 |
| June | 19281.38 | 06-JUN-15:00 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 5.68 | 0.00 |
| July | 16510.02 | 30-JUL-19:51 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.81 |
| August | 16114.59 | 07-AUG-05:01 | 0.00 | 10195.65 | 11157.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.86 |
| September | 19077.74 | 27-SEP-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 26.43 | 0.00 |
| October | 16870.92 | 20-OCT-14:01 | 117067.81 | 51754.55 | 50605.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.07 |
| November | 15563.98 | 08-NOV-15:01 | 102434.34 | 45285.23 | 44279.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.03 |
| December | 9971.78 | 06-DEC-15:10 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.54 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 9299.82 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 19281.38 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 85.61 | 350.54 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2221.49 | 13-JAN-15:40 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.51 |
| February | 3456.23 | 28-FEB-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.49 |
| March | 3451.57 | 01-MAR-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.19 |
| April | 4218.67 | 25-APR-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 |
| May | 5559.91 | 19-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 0.00 |
| June | 5020.35 | 06-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 | 0.00 |
| July | 4813.84 | 17-JUL-16:00 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 41.29 | 0.00 |
| August | 5114.87 | 06-AUG-16:02 | 0.00 | 1587.06 | 1736.75 | 0.00 | 0.00 | 0.00 | 0.00 | 126.17 | 0.00 |
| September | 11023.04 | 02-SEP-15:22 | 0.00 | 1322.55 | 2026.21 | 0.00 | 0.00 | 0.00 | 0.00 | 115.24 | 0.00 |
| October | 6116.87 | 18-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5.39 | 0.00 |
| November | 3973.60 | 03-NOV-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.55 |
| December | 2433.88 | 06-DEC-15:35 | 6074.27 | 2685.38 | 2625.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2221.49 | 0.00 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 11023.04 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 126.17 | 136.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 10848.51 | 13-JAN-15:35 | 29266.95 | 12938.64 | 12651.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265.48 |
| February | 16671.22 | 28-FEB-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.34 |
| March | 16654.94 | 01-MAR-15:01 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.09 |
| April | 19268.94 | 25-APR-14:40 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.61 |
| May | 24194.86 | 19-MAY-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 69.60 | 0.00 |
| June | 22200.23 | 06-JUN-14:50 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 | 0.00 |
| July | 18013.61 | 29-JUL-11:51 | 0.00 | 12744.56 | 13946.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.94 |
| August | 18489.92 | 06-AUG-14:02 | 0.00 | 7646.74 | 8367.97 | 0.00 | 0.00 | 0.00 | 0.00 | 327.16 | 0.00 |
| September | 28155.30 | 25-SEP-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 18.34 | 0.00 |
| October | 26673.29 | 18-OCT-14:20 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 14.30 | 0.00 |
| November | 18977.80 | 03-NOV-14:04 | 73167.38 | 32346.60 | 31628.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.06 |
| December | 11890.69 | 07-DEC-14:30 | 14633.48 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.91 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 10848.51 | 0.00 | 6469.32 | 6325.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 28155.30 | 146334.77 | 64693.19 | 63256.47 | 0.00 | 0.00 | 0.00 | 0.00 | 327.16 | 286.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1102.35 | 13-JAN-16:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.37 |
| February | 1879.20 | 28-FEB-15:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.24 |
| March | 1951.39 | 02-MAR-15:01 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 |
| April | 2204.13 | 25-APR-14:02 | 5890.38 | 4735.58 | 3394.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.52 |
| May | 4213.96 | 19-MAY-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 0.00 |
| June | 4404.53 | 30-JUN-16:00 | 186.01 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 2.27 | 0.00 |
| July | 4067.43 | 17-JUL-15:23 | 558.04 | 1578.53 | 1072.07 | 0.00 | 0.00 | 0.00 | 0.00 | 2.97 | 0.00 |
| August | 3877.27 | 07-AUG-15:13 | 1116.07 | 3157.06 | 2144.15 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 | 0.00 |
| September | 4404.89 | 25-SEP-14:50 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 1.04 | 0.00 |
| October | 3257.34 | 18-OCT-15:00 | 1178.08 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 0.00 |
| November | 2073.34 | 01-NOV-14:01 | 9424.61 | 7576.93 | 5431.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.57 |
| December | 1231.76 | 07-DEC-15:50 | 2356.15 | 1894.23 | 1357.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1102.35 | 186.01 | 947.12 | 678.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4404.89 | 11780.76 | 9471.17 | 6789.79 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 | 16.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1899.28 | 13-JAN-15:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.28 |
| February | 2873.20 | 28-FEB-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.71 |
| March | 3039.87 | 02-MAR-15:01 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.04 |
| April | 3309.16 | 25-APR-14:02 | 15185.68 | 6713.44 | 6564.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.15 |
| May | 4663.78 | 19-MAY-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 32.31 | 0.00 |
| June | 4553.76 | 06-JUN-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 2.15 | 0.00 |
| July | 3870.26 | 17-JUL-16:00 | 479.55 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 41.29 | 0.00 |
| August | 3739.14 | 06-AUG-15:22 | 0.00 | 1587.06 | 1736.75 | 0.00 | 0.00 | 0.00 | 0.00 | 124.59 | 0.00 |
| September | 4500.93 | 25-SEP-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 6.94 | 0.00 |
| October | 3831.62 | 18-OCT-15:00 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 | 0.00 |
| November | 3204.01 | 08-NOV-15:01 | 21259.96 | 9398.82 | 9190.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.83 |
| December | 2062.50 | 06-DEC-15:50 | 3037.14 | 1342.69 | 1312.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.61 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1899.28 | 0.00 | 745.94 | 690.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4663.78 | 30371.37 | 13426.89 | 13128.70 | 0.00 | 0.00 | 0.00 | 0.00 | 124.59 | 120.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6161.07 | 13-JAN-15:50 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.18 |
| February | 9316.17 | 28-FEB-15:01 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.75 |
| March | 9817.24 | 02-MAR-15:01 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.26 |
| April | 10765.90 | 25-APR-14:02 | 48318.08 | 21360.96 | 20886.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.27 |
| May | 13161.43 | 19-MAY-15:00 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 56.54 | 0.00 |
| June | 13305.18 | 06-JUN-15:00 | 9663.62 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 3.75 | 0.00 |
| July | 11120.39 | 22-JUL-18:31 | 0.00 | 8416.22 | 9210.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.74 |
| August | 10737.20 | 07-AUG-05:01 | 0.00 | 6732.97 | 7368.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.03 |
| September | 12966.76 | 27-SEP-14:05 | 38654.47 | 17088.77 | 16709.26 | 0.00 | 0.00 | 0.00 | 0.00 | 19.93 | 0.00 |
| October | 11143.54 | 20-OCT-14:01 | 77308.93 | 34177.54 | 33418.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.35 |
| November | 10358.51 | 08-NOV-15:01 | 67645.32 | 29905.34 | 29241.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.90 |
| December | 6613.16 | 06-DEC-15:10 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.12 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 6161.07 | 0.00 | 4272.19 | 4177.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 13305.18 | 96636.17 | 42721.92 | 41773.14 | 0.00 | 0.00 | 0.00 | 0.00 | 56.54 | 232.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 3410.35 | 13-JAN-15:50 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.75 |
| February | 5087.12 | 28-FEB-15:01 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.34 |
| March | 5361.19 | 02-MAR-15:01 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.46 |
| April | 5683.42 | 25-APR-14:02 | 24849.30 | 10985.64 | 14322.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.63 |
| May | 7853.28 | 19-MAY-15:04 | 24849.30 | 10985.64 | 14322.22 | 0.00 | 0.00 | 0.00 | 0.00 | 29.65 | 0.00 |
| June | 8604.48 | 23-JUN-13:40 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 12.81 | 0.00 |
| July | 6051.27 | 22-JUL-18:31 | 0.00 | 4328.34 | 6315.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.32 |
| August | 6158.91 | 11-AUG-15:10 | 20925.73 | 9765.01 | 12060.82 | 0.00 | 0.00 | 0.00 | 0.00 | 33.29 | 0.00 |
| September | 8002.85 | 06-SEP-14:50 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 3.71 | 0.00 |
| October | 6508.94 | 18-OCT-15:00 | 4969.86 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 | 0.00 |
| November | 5639.50 | 01-NOV-14:01 | 39758.88 | 17577.02 | 22915.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.82 |
| December | 3680.71 | 06-DEC-15:10 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.04 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3410.35 | 0.00 | 2197.13 | 2864.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 8604.48 | 49698.60 | 21971.27 | 28644.44 | 0.00 | 0.00 | 0.00 | 0.00 | 33.29 | 125.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1905.18 | 24-JAN-07:18 | 0.00 | 26933.63 | 5959.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 |
| February | 3773.61 | 28-FEB-15:01 | 33502.32 | 26933.63 | 19308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 |
| March | 4027.61 | 23-MAR-14:01 | 33502.32 | 26933.63 | 19308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.29 |
| April | 4852.90 | 25-APR-14:02 | 16751.16 | 13466.82 | 9654.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.82 |
| May | 10899.07 | 31-MAY-15:00 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
| June | 13426.60 | 26-JUN-07:03 | 2115.94 | 10773.45 | 7723.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.81 |
| July | 14598.86 | 17-JUL-07:03 | 1586.95 | 4488.94 | 3048.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.76 |
| August | 11253.64 | 07-AUG-15:01 | 4760.86 | 13466.82 | 9146.12 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 | 0.00 |
| September | 16410.29 | 05-SEP-07:02 | 2644.92 | 13466.82 | 9654.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.62 |
| October | 5280.48 | 18-OCT-15:00 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 2.42 | 0.00 |
| November | 4267.94 | 01-NOV-14:01 | 26801.86 | 21546.91 | 15446.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.90 |
| December | 2351.70 | 06-DEC-15:00 | 3350.23 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.73 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1905.18 | 0.00 | 2693.36 | 1930.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 16410.29 | 33502.32 | 26933.63 | 19308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 9.49 | 54.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 933.65 | 02-JAN-18:06 | 1656.72 | 10767.67 | 1113.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.01 |
| February | 1715.98 | 27-FEB-15:00 | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1511.44 |
| March | 1388.24 | 14-MAR-15:17 | 994.03 | 6460.60 | 1814.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3591.28 |
| April | 2304.00 | 24-APR-14:02 | 12591.07 | 12921.20 | 3628.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13205.16 |
| May | 10890.37 | 19-MAY-15:00 | 2098.51 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 8129.63 | 0.00 |
| June | 12916.96 | 29-JUN-15:00 | 331.34 | 2153.53 | 604.72 | 0.00 | 0.00 | 0.00 | 0.00 | 12421.08 | 0.00 |
| July | 15099.99 | 17-JUL-14:50 | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 16795.97 | 0.00 |
| August | 13814.44 | 10-AUG-15:00 | 331.34 | 1196.41 | 318.27 | 0.00 | 0.00 | 0.00 | 0.00 | 14185.75 | 0.00 |
| September | 11909.57 | 02-SEP-15:22 | 0.00 | 2121.23 | 933.28 | 0.00 | 0.00 | 0.00 | 0.00 | 107.54 | 0.00 |
| October | 8554.84 | 18-OCT-14:10 | 4197.02 | 4307.07 | 1209.43 | 0.00 | 0.00 | 0.00 | 0.00 | 3156.97 | 0.00 |
| November | 1536.04 | 03-NOV-17:30 | 331.34 | 2153.53 | 222.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.82 |
| December | 1379.72 | 20-DEC-18:07 | 994.03 | 6460.60 | 668.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.41 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 933.65 | 0.00 | 1196.41 | 222.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 15099.99 | 12591.07 | 12921.20 | 3628.30 | 0.00 | 0.00 | 0.00 | 0.00 | 16795.97 | 13205.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1890.21 | 13-JAN-15:50 | 463.87 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3267.45 | 28-FEB-15:01 | 4638.66 | 36618.79 | 22279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 3468.13 | 23-MAR-14:01 | 4638.66 | 36618.79 | 22279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 3999.40 | 25-APR-14:02 | 2319.33 | 18309.39 | 11139.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 12821.22 | 28-MAY-10:40 | 0.00 | 7213.90 | 6876.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 14169.59 | 24-JUN-10:41 | 0.00 | 6492.51 | 6189.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 13930.92 | 22-JUL-18:31 | 0.00 | 7213.90 | 4912.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 12921.46 | 06-AUG-22:39 | 0.00 | 7213.90 | 4912.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 13859.46 | 03-SEP-21:51 | 0.00 | 7213.90 | 6876.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 4099.32 | 20-OCT-14:01 | 3710.93 | 29295.03 | 17823.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 3622.90 | 01-NOV-14:01 | 3710.93 | 29295.03 | 17823.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 2245.48 | 07-DEC-15:00 | 463.87 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1890.21 | 0.00 | 3661.88 | 2227.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 14169.59 | 4638.66 | 36618.79 | 22279.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 759.39 | 13-JAN-15:40 | 2331.76 | 3313.13 | 1343.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.25 |
| February | 1662.53 | 28-FEB-15:01 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 |
| March | 1808.18 | 23-MAR-14:01 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.13 |
| April | 2256.97 | 25-APR-14:02 | 5829.39 | 8282.82 | 3359.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.69 |
| May | 2680.67 | 19-MAY-15:02 | 920.43 | 8282.82 | 3359.53 | 0.00 | 0.00 | 0.00 | 0.00 | 8.93 | 0.00 |
| June | 4794.94 | 24-JUN-16:02 | 0.00 | 1958.06 | 1244.38 | 0.00 | 0.00 | 0.00 | 0.00 | 18.66 | 0.00 |
| July | 8107.73 | 02-JUL-18:50 | 0.00 | 1958.06 | 888.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.82 |
| August | 6125.20 | 06-AUG-16:42 | 0.00 | 1958.06 | 888.84 | 0.00 | 0.00 | 0.00 | 0.00 | 64.19 | 0.00 |
| September | 2738.83 | 05-SEP-14:05 | 368.17 | 3313.13 | 1343.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.97 |
| October | 2369.99 | 20-OCT-14:01 | 9327.02 | 13252.51 | 5375.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.66 |
| November | 1993.36 | 01-NOV-14:01 | 9327.02 | 13252.51 | 5375.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.77 |
| December | 987.84 | 07-DEC-14:50 | 1165.88 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.78 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 759.39 | 0.00 | 1656.56 | 671.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 8107.73 | 11658.78 | 16565.64 | 6719.07 | 0.00 | 0.00 | 0.00 | 0.00 | 64.19 | 50.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 3942.33 | 13-JAN-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.26 |
| February | 23255.43 | 28-FEB-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.50 |
| March | 23226.67 | 01-MAR-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.99 |
| April | 23191.14 | 24-APR-14:02 | 16235.75 | 28196.47 | 25264.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.47 |
| May | 23856.68 | 30-MAY-14:01 | 18941.71 | 32895.88 | 29475.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 23890.75 | 02-JUN-14:01 | 18941.71 | 32895.88 | 29475.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.37 |
| July | 26067.24 | 02-JUL-10:48 | 0.00 | 8332.06 | 8355.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.95 |
| August | 28066.93 | 06-AUG-14:02 | 0.00 | 5554.70 | 5570.23 | 0.00 | 0.00 | 0.00 | 0.00 | 220.44 | 0.00 |
| September | 28482.61 | 02-SEP-15:22 | 0.00 | 4628.92 | 6498.60 | 0.00 | 0.00 | 0.00 | 0.00 | 243.91 | 0.00 |
| October | 23663.76 | 20-OCT-14:01 | 21647.67 | 37595.29 | 33685.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.80 |
| November | 23333.53 | 09-NOV-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.07 |
| December | 4741.52 | 07-DEC-15:01 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 263.56 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3942.33 | 0.00 | 4628.92 | 5570.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 28482.61 | 27059.58 | 46994.11 | 42107.33 | 0.00 | 0.00 | 0.00 | 0.00 | 243.91 | 263.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5946.52 | 13-JAN-17:00 | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.27 |
| February | 8697.00 | 28-FEB-15:01 | 48430.23 | 42884.68 | 15780.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.36 |
| March | 9445.79 | 23-MAR-14:01 | 48430.23 | 42884.68 | 15780.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.26 |
| April | 14146.33 | 25-APR-15:30 | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 |
| May | 26552.22 | 30-MAY-05:01 | 0.00 | 5913.80 | 3409.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.82 |
| June | 27754.21 | 26-JUN-05:01 | 0.00 | 6758.63 | 3896.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.43 |
| July | 28856.11 | 17-JUL-05:01 | 0.00 | 6758.63 | 2783.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.32 |
| August | 28744.64 | 07-AUG-05:01 | 0.00 | 6758.63 | 2783.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.94 |
| September | 27061.95 | 26-SEP-05:01 | 0.00 | 6758.63 | 3896.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 167.27 |
| October | 13140.35 | 18-OCT-15:20 | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 0.00 |
| November | 9208.16 | 01-NOV-14:01 | 38744.19 | 34307.75 | 12624.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.42 |
| December | 6452.25 | 06-DEC-16:50 | 13145.35 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.97 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 5946.52 | 0.00 | 4288.47 | 1578.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 28856.11 | 48430.23 | 42884.68 | 15780.97 | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 167.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 69832.13 | 13-JAN-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 92.05 |
| February | 76658.59 | 14-FEB-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 101.75 |
| March | 74216.64 | 21-MAR-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 74.45 |
| April | 81720.50 | 28-APR-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 72739.03 | 09-MAY-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 193.09 |
| June | 59068.30 | 15-JUN-05:01 | 0.00 | 3077.93 | 20477.18 | 11540.39 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 |
| July | 54400.83 | 12-JUL-05:01 | 0.00 | 3077.93 | 20477.18 | 11540.39 | 0.00 | 0.00 | 0.00 | 0.00 | 85.15 |
| August | 53514.79 | 28-AUG-05:01 | 0.00 | 3077.93 | 20477.18 | 11540.39 | 0.00 | 0.00 | 0.00 | 0.00 | 49.21 |
| September | 61551.86 | 18-SEP-05:11 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 99.50 |
| October | 80783.68 | 10-OCT-05:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 138.82 |
| November | 89663.70 | 21-NOV-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 53.42 |
| December | 80641.31 | 22-DEC-06:01 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 112.79 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 53514.79 | 0.00 | 3077.93 | 20477.18 | 11540.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 89663.70 | 0.00 | 3847.41 | 25596.48 | 14425.49 | 0.00 | 0.00 | 0.00 | 0.00 | 193.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 48412.96 | 11-JAN-06:16 | 0.00 | 5410.43 | 7997.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.55 |
| February | 34264.07 | 28-FEB-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.66 |
| March | 31969.50 | 31-MAR-07:01 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.95 |
| April | 33236.39 | 28-APR-07:01 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.76 |
| May | 31406.49 | 22-MAY-07:01 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.88 |
| June | 71376.27 | 26-JUN-05:01 | 0.00 | 4328.34 | 6398.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.74 |
| July | 70595.38 | 03-JUL-05:01 | 0.00 | 3787.30 | 5598.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.51 |
| August | 70986.89 | 07-AUG-05:01 | 0.00 | 4328.34 | 6398.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.58 |
| September | 67074.89 | 05-SEP-05:01 | 0.00 | 4869.38 | 7198.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.87 |
| October | 32834.32 | 05-OCT-07:01 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 |
| November | 35742.46 | 10-NOV-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.15 |
| December | 30877.75 | 07-DEC-08:61 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.23 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 30877.75 | 0.00 | 3787.30 | 5598.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.76 | |
| Maximum of Months | 71376.27 | 0.00 | 27464.09 | 11996.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 4152.11 | 13-JAN-15:50 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.58 |
| February | 6649.70 | 28-FEB-15:01 | 48967.60 | 59912.39 | 52912.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.29 |
| March | 7182.19 | 23-MAR-14:01 | 48967.60 | 59912.39 | 52912.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.43 |
| April | 10020.11 | 25-APR-15:00 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 |
| May | 15817.24 | 19-MAY-15:00 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 64.59 | 0.00 |
| June | 24598.34 | 21-JUN-07:03 | 3092.69 | 23964.96 | 21165.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.40 |
| July | 17473.25 | 02-JUL-10:48 | 0.00 | 10622.47 | 10499.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.91 |
| August | 14047.66 | 06-AUG-09:30 | 0.00 | 7081.64 | 6999.63 | 0.00 | 0.00 | 0.00 | 0.00 | 45.74 | 0.00 |
| September | 24801.52 | 05-SEP-07:02 | 3865.86 | 29956.19 | 26456.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 |
| October | 12182.27 | 18-OCT-14:40 | 4896.76 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 10.78 | 0.00 |
| November | 7271.08 | 09-NOV-15:01 | 48967.60 | 59912.39 | 52912.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.35 |
| December | 4620.67 | 06-DEC-15:10 | 48967.60 | 59912.39 | 52912.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.45 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 4152.11 | 0.00 | 5991.24 | 5291.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 24801.52 | 48967.60 | 59912.39 | 52912.65 | 0.00 | 0.00 | 0.00 | 0.00 | 64.59 | 274.45 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.268947E+12 | 190127.50 | 09-JAN-08:09 | 0.593645E+12 | 1084341.02 | 09-JAN-08:09 |
| February | 0.237041E+12 | 208102.09 | 27-FEB-14:00 | 0.336307E+12 | 880887.37 | 01-FEB-08:09 |
| March | 0.268814E+12 | 185494.04 | 06-MAR-11:09 | 0.251743E+12 | 850099.00 | 06-MAR-08:09 |
| April | 0.244824E+12 | 233609.01 | 07-APR-13:00 | 0.106859E+12 | 384142.73 | 28-APR-07:10 |
| May | 0.273481E+12 | 304153.53 | 19-MAY-13:00 | 0.939415E+11 | 447871.95 | 08-MAY-07:10 |
| June | 0.311162E+12 | 299568.22 | 29-JUN-12:00 | 0.463557E+11 | 184583.35 | 16-JUN-07:10 |
| July | 0.243560E+12 | 249373.83 | 17-JUL-15:00 | 0.352714E+11 | 109172.25 | 05-JUL-07:10 |
| August | 0.238005E+12 | 225320.04 | 07-AUG-11:00 | 0.428562E+11 | 173701.42 | 18-AUG-07:10 |
| September | 0.275446E+12 | 309467.74 | 27-SEP-12:00 | 0.517334E+11 | 224446.36 | 19-SEP-07:10 |
| October | 0.261773E+12 | 280382.99 | 18-OCT-13:00 | 0.833765E+11 | 460028.79 | 10-OCT-07:10 |
| November | 0.252690E+12 | 194672.40 | 17-NOV-16:00 | 0.189491E+12 | 736416.94 | 27-NOV-08:09 |
| December | 0.259511E+12 | 188447.86 | 26-DEC-08:09 | 0.388646E+12 | 969571.00 | 29-DEC-08:09 |
| Annual Sum or Average | 0.313525E+13 | 0.222023E+13 | ||||
| Minimum of Months | 0.237041E+12 | 185494.04 | 0.352714E+11 | 109172.25 | ||
| Maximum of Months | 0.311162E+12 | 309467.74 | 0.593645E+12 | 1084341.02 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 0.109593E+12 | 0.100356E+11 | 0.102892E+12 | 0.158194E+10 | 0.403508E+11 | 0.753739E+09 | 0.00 | 4910634.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.990914E+11 | 0.829103E+10 | 0.929862E+11 | 0.142979E+10 | 0.311003E+11 | 0.396405E+09 | 0.00 | 0.323214E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.116033E+12 | 0.809640E+10 | 0.106107E+12 | 0.164017E+10 | 0.328043E+11 | 0.290323E+09 | 0.00 | 39203283.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.105019E+12 | 0.674111E+10 | 0.990538E+11 | 0.152152E+10 | 0.251625E+11 | 95051972.89 | 0.00 | 0.354718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.112813E+12 | 0.599445E+10 | 0.104499E+12 | 0.161106E+10 | 0.316090E+11 | 83191250.83 | 0.00 | 0.130698E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.111459E+12 | 0.529380E+10 | 0.102249E+12 | 0.157960E+10 | 0.403222E+11 | 26430017.14 | 0.00 | 0.465470E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.666242E+11 | 0.570428E+10 | 0.693246E+11 | 0.102075E+10 | 0.339585E+11 | 17297560.75 | 0.00 | 0.631738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.703211E+11 | 0.652879E+10 | 0.716606E+11 | 0.104481E+10 | 0.341027E+11 | 30189308.57 | 0.00 | 0.505902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.103032E+12 | 0.735683E+10 | 0.977493E+11 | 0.149702E+10 | 0.331914E+11 | 33034653.91 | 0.00 | 0.289040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.109593E+12 | 0.872628E+10 | 0.102892E+12 | 0.158194E+10 | 0.280256E+11 | 57850709.64 | 0.00 | 0.709556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.108239E+12 | 0.943401E+10 | 0.100662E+12 | 0.155064E+10 | 0.285599E+11 | 0.212373E+09 | 0.00 | 0.347527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.106374E+12 | 0.103151E+11 | 0.101284E+12 | 0.155283E+10 | 0.357306E+11 | 0.482183E+09 | 0.00 | 9900571.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.121819E+13 | 0.925177E+11 | 0.115136E+13 | 0.176121E+11 | 0.394918E+12 | 0.247807E+10 | 0.00 | 0.213652E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.666242E+11 | 0.529380E+10 | 0.693246E+11 | 0.102075E+10 | 0.251625E+11 | 17297560.75 | 0.00 | 4910634.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.116033E+12 | 0.103151E+11 | 0.106107E+12 | 0.164017E+10 | 0.403508E+11 | 0.753739E+09 | 0.00 | 0.631738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.303281E+11 | 0.00 | 0.545426E+12 | 0.00 | 0.178900E+11 | 0.00 | 0.00 |
| February | 0.274200E+11 | 0.00 | 0.292541E+12 | 0.00 | 0.163460E+11 | 0.00 | 0.00 |
| March | 0.319900E+11 | 0.00 | 0.200308E+12 | 0.00 | 0.194455E+11 | 0.00 | 0.00 |
| April | 0.290818E+11 | 0.00 | 0.612463E+11 | 0.00 | 0.165313E+11 | 0.00 | 0.00 |
| May | 0.311591E+11 | 0.00 | 0.454307E+11 | 0.00 | 0.173518E+11 | 0.00 | 0.00 |
| June | 0.307436E+11 | 0.00 | 0.480708E+10 | 0.00 | 0.108050E+11 | 0.00 | 0.00 |
| July | 0.294972E+11 | 0.00 | 0.119285E+10 | 0.00 | 0.458127E+10 | 0.00 | 0.00 |
| August | 0.319900E+11 | 0.00 | 0.583967E+10 | 0.00 | 0.502658E+10 | 0.00 | 0.00 |
| September | 0.290818E+11 | 0.00 | 0.131170E+11 | 0.00 | 0.953463E+10 | 0.00 | 0.00 |
| October | 0.303281E+11 | 0.00 | 0.373244E+11 | 0.00 | 0.157239E+11 | 0.00 | 0.00 |
| November | 0.299127E+11 | 0.00 | 0.143132E+12 | 0.00 | 0.164467E+11 | 0.00 | 0.00 |
| December | 0.294972E+11 | 0.00 | 0.342616E+12 | 0.00 | 0.165321E+11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.361030E+12 | 0.00 | 0.169298E+13 | 0.00 | 0.166215E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.274200E+11 | 0.00 | 0.119285E+10 | 0.00 | 0.458127E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.319900E+11 | 0.00 | 0.545426E+12 | 0.00 | 0.194455E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 79557.27 | 02-JAN-07:10 | 5897.73 | 01-JAN-00:10 | 76813.98 | 02-JAN-10:09 | 1336.02 | 02-JAN-10:09 | 29098.62 | 09-JAN-07:10 | 1264.26 | 09-JAN-07:10 | 0.00 | 01-JAN-00:10 |
| February | 79557.27 | 01-FEB-07:10 | 5897.73 | 01-FEB-00:10 | 76813.98 | 01-FEB-10:09 | 1336.02 | 01-FEB-10:09 | 28342.89 | 06-FEB-07:10 | 1190.20 | 06-FEB-07:10 | 0.00 | 01-FEB-00:10 |
| March | 79557.27 | 01-MAR-07:10 | 5897.73 | 01-MAR-00:10 | 76813.98 | 01-MAR-10:09 | 1336.02 | 01-MAR-10:09 | 29098.62 | 06-MAR-07:10 | 1260.06 | 06-MAR-07:19 | 0.00 | 01-MAR-00:10 |
| April | 79557.27 | 03-APR-06:10 | 5897.73 | 01-APR-00:10 | 76813.98 | 03-APR-09:09 | 1336.02 | 03-APR-09:09 | 33083.64 | 25-APR-14:50 | 703.53 | 03-APR-06:10 | 0.00 | 01-APR-00:10 |
| May | 79557.27 | 01-MAY-06:10 | 5897.73 | 01-MAY-00:10 | 76813.98 | 01-MAY-09:09 | 1336.02 | 01-MAY-09:09 | 54173.15 | 19-MAY-13:00 | 956.47 | 01-MAY-06:10 | 0.00 | 01-MAY-00:10 |
| June | 79557.27 | 01-JUN-06:10 | 5897.73 | 01-JUN-00:10 | 76813.98 | 01-JUN-09:09 | 1336.02 | 01-JUN-09:09 | 53936.13 | 06-JUN-14:39 | 195.55 | 16-JUN-07:10 | 0.00 | 01-JUN-00:10 |
| July | 44198.48 | 03-JUL-07:10 | 5897.73 | 01-JUL-00:10 | 45977.32 | 03-JUL-09:09 | 606.14 | 03-JUL-09:09 | 35465.44 | 17-JUL-17:19 | 234.36 | 05-JUL-07:10 | 0.00 | 01-JUL-00:10 |
| August | 44198.48 | 01-AUG-07:10 | 5897.73 | 01-AUG-00:10 | 45977.32 | 01-AUG-09:09 | 606.14 | 01-AUG-09:09 | 36521.03 | 08-AUG-13:20 | 384.43 | 18-AUG-07:10 | 0.00 | 01-AUG-00:10 |
| September | 79557.27 | 05-SEP-06:10 | 5897.73 | 01-SEP-00:10 | 76813.98 | 05-SEP-09:09 | 1336.02 | 05-SEP-09:09 | 56420.32 | 26-SEP-14:30 | 255.00 | 13-SEP-07:10 | 0.00 | 01-SEP-00:10 |
| October | 79557.27 | 02-OCT-06:10 | 5897.73 | 01-OCT-00:10 | 76813.98 | 02-OCT-09:09 | 1336.02 | 02-OCT-09:09 | 47227.26 | 18-OCT-13:00 | 733.74 | 10-OCT-06:10 | 0.00 | 01-OCT-00:10 |
| November | 79557.27 | 01-NOV-06:10 | 5897.73 | 01-NOV-00:10 | 76813.98 | 01-NOV-09:09 | 1336.02 | 01-NOV-09:09 | 30421.42 | 03-NOV-14:30 | 1187.91 | 27-NOV-07:10 | 0.00 | 01-NOV-00:10 |
| December | 79557.27 | 01-DEC-07:10 | 5897.73 | 01-DEC-00:10 | 76813.98 | 01-DEC-10:09 | 1336.02 | 01-DEC-10:09 | 28548.01 | 26-DEC-07:10 | 1214.11 | 26-DEC-07:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | ||||||||||||||
| Minimum of Months | 44198.48 | 5897.73 | 45977.32 | 606.14 | 28342.89 | 195.55 | 0.00 | |||||||
| Maximum of Months | 79557.27 | 5897.73 | 76813.98 | 1336.02 | 56420.32 | 1264.26 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 885.24 | 24-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 27934.59 | 27-FEB-15:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 3112.77 | 29-MAR-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 50343.23 | 07-APR-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 94996.52 | 19-MAY-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 107474.96 | 29-JUN-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 131373.90 | 17-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 107647.93 | 09-AUG-14:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 114363.70 | 07-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 78176.17 | 18-OCT-13:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 12235.26 | 17-NOV-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 896.42 | 05-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 885.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 131373.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 190127.50 | 09-JAN-08:09 | 79557.27 | 72814.64 | 5897.73 | 1213.82 | 28209.27 | 1173.58 | 0.00 | 0.00 | 0.00 |
| February | 208102.09 | 27-FEB-14:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 25283.73 | 13.47 | 0.00 | 27861.22 | 0.00 |
| March | 185494.04 | 06-MAR-11:09 | 79557.27 | 76813.98 | 0.00 | 1336.02 | 24349.14 | 569.29 | 0.00 | 0.00 | 0.00 |
| April | 233609.01 | 07-APR-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 28307.45 | 13.47 | 0.00 | 50343.23 | 0.00 |
| May | 304153.53 | 19-MAY-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 54173.15 | 13.47 | 0.00 | 94996.52 | 0.00 |
| June | 299568.22 | 29-JUN-12:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 37116.85 | 13.47 | 0.00 | 107474.96 | 0.00 |
| July | 249373.83 | 17-JUL-15:00 | 44198.48 | 39978.30 | 0.00 | 518.12 | 32021.73 | 13.47 | 0.00 | 131373.90 | 0.00 |
| August | 225320.04 | 07-AUG-11:00 | 44198.48 | 45977.32 | 0.00 | 606.14 | 30411.62 | 13.47 | 0.00 | 102810.06 | 0.00 |
| September | 309467.74 | 27-SEP-12:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 55553.24 | 13.47 | 0.00 | 98936.04 | 0.00 |
| October | 280382.99 | 18-OCT-13:00 | 79557.27 | 72814.64 | 0.00 | 1213.82 | 47227.26 | 13.47 | 0.00 | 78176.17 | 0.00 |
| November | 194672.40 | 17-NOV-16:00 | 79557.27 | 70814.97 | 5897.73 | 1156.20 | 23677.20 | 18.18 | 0.00 | 12235.26 | 0.00 |
| December | 188447.86 | 26-DEC-08:09 | 79557.27 | 72814.64 | 5897.73 | 1213.82 | 26549.78 | 1010.95 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | ||||||||||
| Minimum of Months | 185494.04 | 44198.48 | 39978.30 | 0.00 | 518.12 | 23677.20 | 13.47 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 309467.74 | 79557.27 | 76813.98 | 5897.73 | 1336.02 | 55553.24 | 1173.58 | 0.00 | 131373.90 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
| January | 48084.96 | 02-JAN-10:09 | 0.00 | 1035709.31 | 09-JAN-08:09 | 0.00 | 32063.19 | 31-JAN-13:20 | 0.00 |
| February | 48084.96 | 01-FEB-10:09 | 0.00 | 831671.27 | 01-FEB-08:09 | 0.00 | 32121.16 | 13-FEB-13:39 | 0.00 |
| March | 48084.96 | 01-MAR-10:09 | 0.00 | 800881.79 | 06-MAR-08:09 | 0.00 | 32089.05 | 01-MAR-13:39 | 0.00 |
| April | 48084.96 | 03-APR-09:09 | 0.00 | 335816.24 | 28-APR-07:10 | 0.00 | 31654.30 | 05-APR-12:20 | 0.00 |
| May | 48084.96 | 01-MAY-09:09 | 0.00 | 399544.38 | 08-MAY-07:10 | 0.00 | 30191.23 | 01-MAY-12:20 | 0.00 |
| June | 48084.96 | 01-JUN-09:09 | 0.00 | 144300.80 | 16-JUN-07:10 | 0.00 | 28775.01 | 01-JUN-12:39 | 0.00 |
| July | 48084.96 | 03-JUL-09:09 | 0.00 | 68916.28 | 05-JUL-07:10 | 0.00 | 9013.40 | 03-JUL-18:49 | 0.00 |
| August | 48084.96 | 01-AUG-09:09 | 0.00 | 133433.10 | 18-AUG-07:10 | 0.00 | 8802.11 | 04-AUG-18:49 | 0.00 |
| September | 48084.96 | 01-SEP-09:09 | 0.00 | 177766.01 | 19-SEP-07:10 | 0.00 | 27175.80 | 28-SEP-12:20 | 0.00 |
| October | 48084.96 | 02-OCT-09:09 | 0.00 | 412577.81 | 10-OCT-07:10 | 0.00 | 28411.37 | 31-OCT-12:39 | 0.00 |
| November | 48084.96 | 01-NOV-09:09 | 0.00 | 688118.33 | 27-NOV-08:09 | 0.00 | 29984.76 | 30-NOV-13:39 | 0.00 |
| December | 48084.96 | 01-DEC-10:09 | 0.00 | 920429.49 | 29-DEC-08:09 | 0.00 | 31272.70 | 26-DEC-13:20 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 48084.96 | 0.00 | 68916.28 | 0.00 | 8802.11 | 0.00 | |||
| Maximum of Months | 48084.96 | 0.00 | 1035709.31 | 0.00 | 32121.16 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 42.50 | 14.76 | 0.00 | 14.76 | 0.00 | 14.76 | 0.00 | 14.76 |
| February | 17.50 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
| March | 11.50 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.83 | 16.14 | 0.00 | 16.14 | 0.00 | 16.14 | 0.00 | 16.14 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.31 | 0.00 | 27.31 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.43 | 0.00 | 27.43 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 5.50 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 | 0.00 | 15.51 |
| December | 30.00 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
| Annual Sum or Average | 107.83 | 14.89 | 0.00 | 14.89 | 1.83 | 15.10 | 0.00 | 15.10 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 42.50 | 16.14 | 0.00 | 16.14 | 1.50 | 27.43 | 0.00 | 27.43 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 23.50 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
| February | 8.17 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
| March | 6.50 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.33 | 16.21 | 0.00 | 16.21 | 0.00 | 16.21 | 0.00 | 16.21 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 1.00 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
| December | 7.83 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 | 0.00 | 15.21 |
| Annual Sum or Average | 47.33 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 23.50 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 36.50 | 17.41 | 10.17 | 17.94 | 0.00 | 17.94 | 0.00 | 17.94 |
| February | 9.33 | 17.65 | 1.33 | 17.95 | 0.00 | 17.95 | 0.00 | 17.95 |
| March | 5.83 | 17.36 | 1.33 | 17.79 | 0.00 | 17.79 | 0.00 | 17.79 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.50 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 3.33 | 18.57 | 0.83 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
| December | 13.50 | 17.60 | 2.83 | 18.03 | 0.00 | 18.03 | 0.00 | 18.03 |
| Annual Sum or Average | 69.00 | 17.54 | 16.50 | 17.99 | 0.00 | 17.99 | 0.00 | 17.99 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 36.50 | 18.57 | 10.17 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 55.67 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 |
| February | 22.50 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
| March | 16.00 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
| April | 0.17 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
| May | 0.83 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.17 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
| November | 9.33 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
| December | 39.50 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
| Annual Sum or Average | 144.17 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 | 0.00 | 14.90 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 55.67 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 31.67 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
| February | 12.00 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
| March | 8.17 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.50 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 3.00 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
| December | 11.00 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 |
| Annual Sum or Average | 66.33 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 31.67 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 43.67 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
| February | 17.17 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
| March | 11.50 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.83 | 16.13 | 0.00 | 16.13 | 0.00 | 16.13 | 0.00 | 16.13 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.36 | 0.00 | 27.36 |
| October | 0.17 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 | 0.00 | 17.24 |
| November | 5.50 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 | 0.00 | 15.50 |
| December | 31.00 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
| Annual Sum or Average | 109.83 | 14.89 | 0.00 | 14.89 | 1.33 | 15.04 | 0.00 | 15.04 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 43.67 | 17.24 | 0.00 | 17.24 | 1.33 | 27.36 | 0.00 | 27.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 23.83 | 15.24 | 0.00 | 15.24 | 0.00 | 15.24 | 0.00 | 15.24 |
| February | 8.33 | 15.49 | 0.00 | 15.49 | 0.00 | 15.49 | 0.00 | 15.49 |
| March | 6.50 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.33 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 | 0.00 | 16.25 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 1.00 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
| December | 8.50 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
| Annual Sum or Average | 48.50 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 23.83 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 | 0.00 | 16.94 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 37.00 | 17.41 | 10.33 | 17.94 | 0.00 | 17.94 | 0.00 | 17.94 |
| February | 9.50 | 17.68 | 1.33 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 |
| March | 5.83 | 17.36 | 1.33 | 17.78 | 0.00 | 17.78 | 0.00 | 17.78 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.50 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 | 0.00 | 18.27 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 3.50 | 18.59 | 0.83 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
| December | 13.83 | 17.65 | 3.17 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 |
| Annual Sum or Average | 70.17 | 17.55 | 17.00 | 18.01 | 0.00 | 18.01 | 0.00 | 18.01 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 37.00 | 18.59 | 10.33 | 18.88 | 0.00 | 18.88 | 0.00 | 18.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 56.17 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 |
| February | 22.67 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
| March | 16.00 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 | 0.00 | 15.12 |
| April | 0.17 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
| May | 0.83 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 | 0.00 | 16.07 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.17 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
| November | 9.33 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
| December | 39.50 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
| Annual Sum or Average | 144.83 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 56.17 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 | 0.00 | 17.13 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 31.67 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
| February | 12.00 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
| March | 8.17 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.50 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 3.00 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
| December | 11.00 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 |
| Annual Sum or Average | 66.33 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 | 0.00 | 15.32 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 31.67 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 | 0.00 | 16.32 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 42.83 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
| February | 17.17 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 | 0.00 | 15.01 |
| March | 11.50 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.83 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 | 0.00 | 16.15 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.30 | 0.00 | 27.30 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.40 | 0.00 | 27.40 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 5.33 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
| December | 30.83 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
| Annual Sum or Average | 108.50 | 14.89 | 0.00 | 14.89 | 1.67 | 15.08 | 0.00 | 15.08 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 42.83 | 16.15 | 0.00 | 16.15 | 1.50 | 27.40 | 0.00 | 27.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 23.50 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 | 0.00 | 15.25 |
| February | 8.33 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 | 0.00 | 15.48 |
| March | 6.50 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.33 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 | 0.00 | 16.29 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 1.00 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
| December | 8.33 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
| Annual Sum or Average | 48.00 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 23.50 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 36.67 | 17.39 | 10.00 | 17.92 | 0.00 | 17.92 | 0.00 | 17.92 |
| February | 9.33 | 17.66 | 1.33 | 17.96 | 0.00 | 17.96 | 0.00 | 17.96 |
| March | 5.83 | 17.37 | 1.33 | 17.80 | 0.00 | 17.80 | 0.00 | 17.80 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.50 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 3.17 | 18.49 | 0.67 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
| December | 13.50 | 17.60 | 2.83 | 18.02 | 0.00 | 18.02 | 0.00 | 18.02 |
| Annual Sum or Average | 69.00 | 17.53 | 16.17 | 17.98 | 0.00 | 17.98 | 0.00 | 17.98 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 36.67 | 18.49 | 10.00 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 56.00 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 |
| February | 22.83 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 | 0.00 | 14.98 |
| March | 15.67 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
| April | 0.17 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
| May | 0.83 | 16.10 | 0.00 | 16.10 | 0.00 | 16.10 | 0.00 | 16.10 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.17 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
| November | 9.33 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 | 0.00 | 15.22 |
| December | 39.33 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
| Annual Sum or Average | 144.33 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 56.00 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 | 0.00 | 17.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 32.00 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 | 0.00 | 15.17 |
| February | 12.17 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 | 0.00 | 15.46 |
| March | 8.17 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 | 0.00 | 15.15 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.50 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 3.17 | 16.08 | 0.00 | 16.08 | 0.00 | 16.08 | 0.00 | 16.08 |
| December | 11.33 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
| Annual Sum or Average | 67.33 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 | 0.00 | 15.30 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 32.00 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 | 0.00 | 16.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 28.00 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 | 0.00 | 15.19 |
| February | 10.50 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 | 0.00 | 15.41 |
| March | 6.83 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 | 0.00 | 15.09 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.33 | 16.58 | 0.00 | 16.58 | 0.00 | 16.58 | 0.00 | 16.58 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 1.83 | 16.26 | 0.00 | 16.26 | 0.00 | 16.26 | 0.00 | 16.26 |
| December | 9.67 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 | 0.00 | 15.36 |
| Annual Sum or Average | 57.17 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 28.00 | 16.58 | 0.00 | 16.58 | 0.00 | 16.58 | 0.00 | 16.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 47.17 | 18.11 | 22.33 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
| February | 6.83 | 18.70 | 1.67 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
| March | 4.17 | 18.70 | 1.50 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.17 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 3.17 | 18.51 | 0.50 | 18.75 | 0.00 | 18.75 | 0.00 | 18.75 |
| December | 15.17 | 18.20 | 4.83 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
| Annual Sum or Average | 76.67 | 18.23 | 30.83 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 47.17 | 19.38 | 22.33 | 19.38 | 0.00 | 19.38 | 0.00 | 19.38 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 286.17 | 13.23 | 213.00 | 13.58 | 0.00 | 13.58 | 0.00 | 13.58 |
| February | 181.50 | 14.30 | 137.83 | 14.81 | 0.00 | 14.81 | 0.00 | 14.81 |
| March | 152.83 | 15.61 | 118.67 | 16.33 | 0.00 | 16.33 | 0.00 | 16.33 |
| April | 72.67 | 16.08 | 52.83 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
| May | 61.67 | 16.06 | 40.00 | 16.82 | 1.00 | 16.91 | 1.00 | 16.99 |
| June | 19.17 | 17.38 | 5.17 | 17.67 | 7.50 | 19.66 | 7.50 | 20.89 |
| July | 6.67 | 18.12 | 0.17 | 18.15 | 16.17 | 24.05 | 16.17 | 25.07 |
| August | 16.67 | 17.28 | 3.17 | 17.47 | 10.83 | 20.81 | 10.17 | 22.32 |
| September | 23.83 | 15.92 | 10.33 | 16.43 | 5.67 | 17.83 | 3.00 | 18.35 |
| October | 50.17 | 15.92 | 30.33 | 16.69 | 0.00 | 16.69 | 0.00 | 16.69 |
| November | 115.00 | 15.58 | 90.83 | 16.21 | 0.00 | 16.21 | 0.00 | 16.21 |
| December | 198.83 | 14.15 | 152.83 | 14.62 | 0.00 | 14.62 | 0.00 | 14.62 |
| Annual Sum or Average | 1185.17 | 14.73 | 855.17 | 15.22 | 41.17 | 15.44 | 37.83 | 15.64 |
| Minimum of Months | 6.67 | 13.23 | 0.17 | 13.58 | 0.00 | 13.58 | 0.00 | 13.58 |
| Maximum of Months | 286.17 | 18.12 | 213.00 | 18.15 | 16.17 | 24.05 | 16.17 | 25.07 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.00 | 27.26 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.26 | 0.00 | 27.26 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.27 | 0.00 | 27.27 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 2.17 | 27.27 | 0.00 | 27.27 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.27 | 0.00 | 27.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 30.83 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 | 0.00 | 14.73 |
| February | 8.67 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
| March | 4.83 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.35 | 0.00 | 27.35 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 13.17 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 | 0.00 | 14.85 |
| Annual Sum or Average | 57.50 | 14.80 | 0.00 | 14.80 | 0.67 | 14.94 | 0.00 | 14.94 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 30.83 | 14.91 | 0.00 | 14.91 | 0.67 | 27.35 | 0.00 | 27.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 44.67 | 16.73 | 2.00 | 16.87 | 0.00 | 16.87 | 0.00 | 16.87 |
| February | 12.67 | 16.36 | 0.00 | 16.36 | 0.00 | 16.36 | 0.00 | 16.36 |
| March | 6.83 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 | 0.00 | 15.31 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.17 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.41 | 0.00 | 27.41 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.42 | 0.00 | 27.42 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.42 | 0.00 | 27.42 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 4.00 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 | 0.00 | 18.48 |
| December | 18.33 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 | 0.00 | 17.19 |
| Annual Sum or Average | 86.67 | 16.74 | 2.00 | 16.82 | 5.33 | 17.42 | 0.00 | 17.42 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 44.67 | 18.48 | 2.00 | 18.48 | 2.83 | 27.42 | 0.00 | 27.42 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 27.50 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 | 0.00 | 16.95 |
| February | 9.83 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 |
| March | 4.17 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.50 | 19.27 | 0.00 | 19.27 | 0.17 | 21.28 | 0.00 | 21.28 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.72 | 0.00 | 24.72 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.92 | 0.00 | 25.92 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 3.33 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 | 0.00 | 19.18 |
| December | 11.50 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 | 0.00 | 17.67 |
| Annual Sum or Average | 56.83 | 17.57 | 0.00 | 17.57 | 0.67 | 17.67 | 0.00 | 17.67 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 27.50 | 19.27 | 0.00 | 19.27 | 0.33 | 25.92 | 0.00 | 25.92 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 2.33 | 11.05 | 0.00 | 11.05 | 2.17 | 18.27 | 0.00 | 18.27 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 26.60 | 0.00 | 26.60 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 26.78 | 0.00 | 26.78 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 42.50 | 27.34 | 0.00 | 27.34 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 69.17 | 27.57 | 0.00 | 27.57 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 92.83 | 27.72 | 0.00 | 27.72 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 109.17 | 27.82 | 0.00 | 27.82 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 97.33 | 27.71 | 0.00 | 27.71 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 91.67 | 27.69 | 0.00 | 27.69 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 52.83 | 27.38 | 0.00 | 27.38 |
| November | 0.50 | 18.79 | 0.00 | 18.79 | 18.33 | 26.83 | 0.00 | 26.83 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 25.97 | 0.00 | 25.97 |
| Annual Sum or Average | 2.83 | 12.42 | 0.00 | 12.42 | 598.67 | 27.52 | 0.00 | 27.52 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 18.27 | 0.00 | 18.27 |
| Maximum of Months | 2.33 | 18.79 | 0.00 | 18.79 | 109.17 | 27.82 | 0.00 | 27.82 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 65.50 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 | 0.00 | 15.06 |
| February | 18.00 | 16.21 | 0.00 | 16.21 | 0.00 | 16.21 | 0.00 | 16.21 |
| March | 14.33 | 15.74 | 0.00 | 15.74 | 0.00 | 15.74 | 0.00 | 15.74 |
| April | 0.33 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 | 0.00 | 20.34 |
| May | 0.50 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 | 0.00 | 19.98 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 26.27 | 0.00 | 26.27 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.06 | 0.00 | 27.06 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.20 | 0.00 | 27.20 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.18 | 0.00 | 27.18 |
| October | 0.33 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 | 0.00 | 20.27 |
| November | 2.17 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 | 0.00 | 19.48 |
| December | 29.17 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 | 0.00 | 15.13 |
| Annual Sum or Average | 130.33 | 15.43 | 0.00 | 15.43 | 12.33 | 16.43 | 0.00 | 16.43 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.06 | 0.00 | 15.06 |
| Maximum of Months | 65.50 | 20.34 | 0.00 | 20.34 | 5.83 | 27.20 | 0.00 | 27.20 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 30.50 | 15.32 | 0.17 | 15.35 | 0.00 | 15.35 | 0.00 | 15.35 |
| February | 10.50 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 | 0.00 | 15.52 |
| March | 6.67 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 | 0.00 | 15.11 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.17 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 | 0.00 | 16.60 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 1.67 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
| December | 10.00 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
| Annual Sum or Average | 59.50 | 15.40 | 0.17 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 30.50 | 17.04 | 0.17 | 17.04 | 0.00 | 17.04 | 0.00 | 17.04 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.06 | 255.33 | 21.04 | 255.33 | 21.03 |
| February | 245.83 | 21.37 | 176.67 | 21.23 | 176.67 | 21.17 |
| March | 298.17 | 21.61 | 156.33 | 21.41 | 156.33 | 21.31 |
| April | 247.33 | 22.01 | 64.50 | 21.81 | 64.50 | 21.68 |
| May | 226.83 | 22.34 | 51.83 | 22.27 | 36.50 | 22.12 |
| June | 98.17 | 22.82 | 99.17 | 23.41 | 0.00 | 23.41 |
| July | 108.50 | 22.33 | 88.33 | 23.06 | 0.00 | 23.06 |
| August | 150.83 | 22.22 | 88.33 | 22.86 | 0.83 | 22.85 |
| September | 121.83 | 22.45 | 87.17 | 23.09 | 0.33 | 23.08 |
| October | 186.67 | 22.68 | 19.33 | 22.66 | 9.83 | 22.59 |
| November | 260.00 | 21.91 | 97.33 | 21.67 | 97.33 | 21.53 |
| December | 260.00 | 21.30 | 193.00 | 21.18 | 193.00 | 21.13 |
| Annual Sum or Average | 2477.17 | 21.87 | 1377.33 | 21.86 | 990.67 | 21.69 |
| Minimum of Months | 98.17 | 21.06 | 19.33 | 21.04 | 0.00 | 21.03 |
| Maximum of Months | 298.17 | 22.82 | 255.33 | 23.41 | 255.33 | 23.41 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.17 | 237.67 | 21.12 | 237.67 | 21.10 |
| February | 243.83 | 21.60 | 144.17 | 21.40 | 144.17 | 21.31 |
| March | 294.17 | 21.94 | 91.83 | 21.73 | 91.83 | 21.61 |
| April | 240.33 | 22.38 | 15.33 | 22.30 | 15.33 | 22.24 |
| May | 210.67 | 22.49 | 39.83 | 22.47 | 21.83 | 22.36 |
| June | 89.50 | 22.90 | 96.00 | 23.46 | 0.00 | 23.46 |
| July | 146.33 | 22.40 | 42.33 | 22.71 | 0.00 | 22.71 |
| August | 172.33 | 22.28 | 57.83 | 22.69 | 0.17 | 22.69 |
| September | 108.33 | 22.66 | 89.50 | 23.25 | 0.00 | 23.25 |
| October | 158.67 | 22.88 | 17.67 | 22.96 | 2.17 | 22.94 |
| November | 246.00 | 22.14 | 73.50 | 21.89 | 73.50 | 21.73 |
| December | 260.00 | 21.52 | 161.17 | 21.33 | 161.17 | 21.25 |
| Annual Sum or Average | 2443.17 | 22.06 | 1066.83 | 22.02 | 747.83 | 21.85 |
| Minimum of Months | 89.50 | 21.17 | 15.33 | 21.12 | 0.00 | 21.10 |
| Maximum of Months | 294.17 | 22.90 | 237.67 | 23.46 | 237.67 | 23.46 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 20.95 | 270.50 | 20.95 | 270.50 | 20.95 |
| February | 247.00 | 21.04 | 226.50 | 21.02 | 226.50 | 21.01 |
| March | 299.00 | 21.15 | 199.83 | 21.09 | 199.83 | 21.06 |
| April | 260.00 | 21.78 | 37.83 | 21.68 | 37.83 | 21.60 |
| May | 254.17 | 22.38 | 43.33 | 22.22 | 39.83 | 22.07 |
| June | 116.67 | 23.54 | 41.00 | 23.66 | 0.00 | 23.66 |
| July | 147.33 | 23.11 | 9.67 | 23.16 | 0.00 | 23.16 |
| August | 231.33 | 22.96 | 5.17 | 22.98 | 0.00 | 22.98 |
| September | 165.00 | 22.96 | 35.67 | 23.14 | 0.00 | 23.14 |
| October | 270.67 | 22.79 | 12.67 | 22.71 | 12.67 | 22.64 |
| November | 273.00 | 21.46 | 134.17 | 21.31 | 134.17 | 21.23 |
| December | 260.00 | 21.01 | 241.17 | 21.00 | 241.17 | 20.99 |
| Annual Sum or Average | 2797.17 | 21.93 | 1257.50 | 21.70 | 1162.50 | 21.54 |
| Minimum of Months | 116.67 | 20.95 | 5.17 | 20.95 | 0.00 | 20.95 |
| Maximum of Months | 299.00 | 23.54 | 270.50 | 23.66 | 270.50 | 23.66 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.00 | 270.83 | 21.00 | 270.83 | 21.00 |
| February | 247.00 | 21.04 | 236.50 | 21.03 | 236.50 | 21.02 |
| March | 299.00 | 21.13 | 250.67 | 21.09 | 250.67 | 21.07 |
| April | 260.00 | 21.56 | 107.33 | 21.41 | 107.33 | 21.32 |
| May | 255.67 | 22.15 | 58.67 | 22.02 | 50.67 | 21.88 |
| June | 137.50 | 22.92 | 64.17 | 23.25 | 0.00 | 23.25 |
| July | 184.00 | 22.31 | 20.33 | 22.45 | 0.00 | 22.45 |
| August | 254.67 | 22.02 | 14.00 | 22.10 | 1.50 | 22.09 |
| September | 184.33 | 22.29 | 42.00 | 22.55 | 2.83 | 22.53 |
| October | 265.67 | 22.31 | 29.67 | 22.19 | 29.67 | 22.08 |
| November | 273.00 | 21.39 | 162.00 | 21.25 | 162.00 | 21.19 |
| December | 260.00 | 21.05 | 244.33 | 21.03 | 244.33 | 21.03 |
| Annual Sum or Average | 2893.83 | 21.68 | 1500.50 | 21.55 | 1356.33 | 21.42 |
| Minimum of Months | 137.50 | 21.00 | 14.00 | 21.00 | 0.00 | 21.00 |
| Maximum of Months | 299.00 | 22.92 | 270.83 | 23.25 | 270.83 | 23.25 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.02 | 267.33 | 21.01 | 267.33 | 21.01 |
| February | 247.00 | 21.12 | 220.67 | 21.08 | 220.67 | 21.07 |
| March | 299.00 | 21.34 | 192.17 | 21.23 | 192.17 | 21.18 |
| April | 260.00 | 21.91 | 39.00 | 21.80 | 39.00 | 21.72 |
| May | 248.67 | 22.34 | 37.83 | 22.23 | 32.17 | 22.11 |
| June | 135.50 | 22.94 | 57.67 | 23.21 | 0.00 | 23.21 |
| July | 256.83 | 22.18 | 0.00 | 22.18 | 0.00 | 22.18 |
| August | 297.33 | 21.86 | 0.17 | 21.86 | 0.17 | 21.86 |
| September | 187.33 | 22.40 | 33.67 | 22.61 | 0.00 | 22.61 |
| October | 262.17 | 22.55 | 13.00 | 22.48 | 13.00 | 22.42 |
| November | 273.00 | 21.59 | 127.17 | 21.43 | 127.17 | 21.34 |
| December | 260.00 | 21.13 | 222.00 | 21.08 | 222.00 | 21.07 |
| Annual Sum or Average | 2999.83 | 21.80 | 1210.67 | 21.64 | 1113.67 | 21.52 |
| Minimum of Months | 135.50 | 21.02 | 0.00 | 21.01 | 0.00 | 21.01 |
| Maximum of Months | 299.00 | 22.94 | 267.33 | 23.21 | 267.33 | 23.21 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.06 | 256.83 | 21.03 | 256.83 | 21.02 |
| February | 246.17 | 21.36 | 179.67 | 21.22 | 179.67 | 21.16 |
| March | 298.33 | 21.58 | 160.17 | 21.39 | 160.17 | 21.30 |
| April | 248.33 | 21.99 | 67.17 | 21.79 | 67.17 | 21.66 |
| May | 231.33 | 22.33 | 51.83 | 22.24 | 37.50 | 22.10 |
| June | 105.00 | 22.83 | 92.17 | 23.37 | 0.00 | 23.37 |
| July | 115.17 | 22.32 | 82.67 | 23.00 | 0.00 | 23.00 |
| August | 156.83 | 22.20 | 82.50 | 22.80 | 1.00 | 22.80 |
| September | 123.17 | 22.44 | 85.17 | 23.06 | 0.50 | 23.06 |
| October | 189.83 | 22.67 | 19.00 | 22.65 | 10.33 | 22.57 |
| November | 262.83 | 21.89 | 100.17 | 21.65 | 100.17 | 21.52 |
| December | 260.00 | 21.26 | 200.33 | 21.16 | 200.33 | 21.11 |
| Annual Sum or Average | 2510.00 | 21.86 | 1377.67 | 21.84 | 1013.67 | 21.67 |
| Minimum of Months | 105.00 | 21.06 | 19.00 | 21.03 | 0.00 | 21.02 |
| Maximum of Months | 298.33 | 22.83 | 256.83 | 23.37 | 256.83 | 23.37 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.14 | 243.67 | 21.10 | 243.67 | 21.08 |
| February | 244.33 | 21.57 | 147.33 | 21.38 | 147.33 | 21.29 |
| March | 295.33 | 21.92 | 93.67 | 21.71 | 93.67 | 21.59 |
| April | 241.50 | 22.37 | 14.50 | 22.30 | 14.50 | 22.24 |
| May | 214.17 | 22.49 | 38.67 | 22.46 | 22.33 | 22.35 |
| June | 95.67 | 22.91 | 89.50 | 23.42 | 0.00 | 23.42 |
| July | 161.83 | 22.40 | 26.67 | 22.59 | 0.00 | 22.59 |
| August | 182.00 | 22.26 | 47.33 | 22.60 | 0.17 | 22.60 |
| September | 112.00 | 22.67 | 85.67 | 23.23 | 0.00 | 23.23 |
| October | 164.67 | 22.89 | 14.50 | 22.94 | 2.33 | 22.92 |
| November | 250.17 | 22.09 | 77.17 | 21.85 | 77.17 | 21.69 |
| December | 260.00 | 21.43 | 173.00 | 21.27 | 173.00 | 21.20 |
| Annual Sum or Average | 2494.67 | 22.05 | 1051.67 | 21.98 | 774.17 | 21.81 |
| Minimum of Months | 95.67 | 21.14 | 14.50 | 21.10 | 0.00 | 21.08 |
| Maximum of Months | 295.33 | 22.91 | 243.67 | 23.42 | 243.67 | 23.42 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 20.95 | 270.67 | 20.95 | 270.67 | 20.95 |
| February | 247.00 | 21.03 | 227.67 | 21.01 | 227.67 | 21.01 |
| March | 299.00 | 21.15 | 202.67 | 21.08 | 202.67 | 21.06 |
| April | 260.00 | 21.77 | 37.83 | 21.67 | 37.83 | 21.60 |
| May | 255.00 | 22.38 | 43.33 | 22.21 | 39.83 | 22.07 |
| June | 119.17 | 23.54 | 40.83 | 23.66 | 0.00 | 23.66 |
| July | 152.17 | 23.10 | 8.83 | 23.15 | 0.00 | 23.15 |
| August | 234.83 | 22.94 | 5.17 | 22.96 | 0.00 | 22.96 |
| September | 166.00 | 22.95 | 35.00 | 23.14 | 0.00 | 23.14 |
| October | 270.83 | 22.78 | 12.83 | 22.70 | 12.83 | 22.62 |
| November | 273.00 | 21.43 | 137.17 | 21.28 | 137.17 | 21.21 |
| December | 260.00 | 21.00 | 243.50 | 20.99 | 243.50 | 20.99 |
| Annual Sum or Average | 2810.00 | 21.92 | 1265.50 | 21.70 | 1172.17 | 21.54 |
| Minimum of Months | 119.17 | 20.95 | 5.17 | 20.95 | 0.00 | 20.95 |
| Maximum of Months | 299.00 | 23.54 | 270.67 | 23.66 | 270.67 | 23.66 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.00 | 270.83 | 21.00 | 270.83 | 21.00 |
| February | 247.00 | 21.04 | 236.67 | 21.03 | 236.67 | 21.02 |
| March | 299.00 | 21.14 | 250.50 | 21.09 | 250.50 | 21.07 |
| April | 260.00 | 21.56 | 107.17 | 21.41 | 107.17 | 21.32 |
| May | 255.00 | 22.15 | 58.33 | 22.02 | 50.33 | 21.88 |
| June | 136.50 | 22.92 | 64.50 | 23.26 | 0.00 | 23.26 |
| July | 183.67 | 22.31 | 20.33 | 22.46 | 0.00 | 22.46 |
| August | 254.33 | 22.02 | 14.33 | 22.10 | 1.50 | 22.10 |
| September | 184.17 | 22.29 | 42.00 | 22.55 | 2.83 | 22.54 |
| October | 265.83 | 22.32 | 30.00 | 22.19 | 30.00 | 22.08 |
| November | 273.00 | 21.39 | 162.00 | 21.25 | 162.00 | 21.19 |
| December | 260.00 | 21.05 | 244.33 | 21.03 | 244.33 | 21.03 |
| Annual Sum or Average | 2891.50 | 21.68 | 1501.00 | 21.55 | 1356.17 | 21.42 |
| Minimum of Months | 136.50 | 21.00 | 14.33 | 21.00 | 0.00 | 21.00 |
| Maximum of Months | 299.00 | 22.92 | 270.83 | 23.26 | 270.83 | 23.26 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.02 | 267.17 | 21.01 | 267.17 | 21.01 |
| February | 247.00 | 21.12 | 220.83 | 21.08 | 220.83 | 21.07 |
| March | 299.00 | 21.34 | 192.17 | 21.23 | 192.17 | 21.18 |
| April | 260.00 | 21.91 | 38.67 | 21.80 | 38.67 | 21.72 |
| May | 248.33 | 22.34 | 37.50 | 22.24 | 31.83 | 22.12 |
| June | 134.17 | 22.94 | 58.50 | 23.22 | 0.00 | 23.22 |
| July | 256.67 | 22.18 | 0.00 | 22.18 | 0.00 | 22.18 |
| August | 297.17 | 21.86 | 0.17 | 21.86 | 0.17 | 21.86 |
| September | 187.00 | 22.40 | 33.67 | 22.61 | 0.00 | 22.61 |
| October | 262.17 | 22.55 | 13.33 | 22.48 | 13.33 | 22.42 |
| November | 273.00 | 21.59 | 128.50 | 21.43 | 128.50 | 21.34 |
| December | 260.00 | 21.13 | 222.33 | 21.08 | 222.33 | 21.07 |
| Annual Sum or Average | 2997.50 | 21.80 | 1212.83 | 21.64 | 1115.00 | 21.52 |
| Minimum of Months | 134.17 | 21.02 | 0.00 | 21.01 | 0.00 | 21.01 |
| Maximum of Months | 299.00 | 22.94 | 267.17 | 23.22 | 267.17 | 23.22 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.06 | 256.33 | 21.03 | 256.33 | 21.03 |
| February | 246.00 | 21.36 | 179.00 | 21.22 | 179.00 | 21.17 |
| March | 298.33 | 21.59 | 158.50 | 21.40 | 158.50 | 21.30 |
| April | 247.50 | 22.01 | 64.17 | 21.81 | 64.17 | 21.68 |
| May | 229.17 | 22.35 | 51.50 | 22.26 | 36.67 | 22.12 |
| June | 102.00 | 22.84 | 95.00 | 23.39 | 0.00 | 23.39 |
| July | 110.50 | 22.33 | 86.00 | 23.04 | 0.00 | 23.04 |
| August | 153.50 | 22.22 | 85.50 | 22.84 | 0.83 | 22.83 |
| September | 121.67 | 22.46 | 86.67 | 23.09 | 0.33 | 23.09 |
| October | 186.00 | 22.68 | 19.17 | 22.67 | 9.67 | 22.60 |
| November | 260.83 | 21.90 | 99.00 | 21.66 | 99.00 | 21.53 |
| December | 260.00 | 21.28 | 197.83 | 21.16 | 197.83 | 21.12 |
| Annual Sum or Average | 2488.50 | 21.87 | 1378.67 | 21.85 | 1002.33 | 21.68 |
| Minimum of Months | 102.00 | 21.06 | 19.17 | 21.03 | 0.00 | 21.03 |
| Maximum of Months | 298.33 | 22.84 | 256.33 | 23.39 | 256.33 | 23.39 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.15 | 242.00 | 21.11 | 242.00 | 21.09 |
| February | 244.17 | 21.58 | 146.33 | 21.39 | 146.33 | 21.30 |
| March | 294.67 | 21.93 | 91.67 | 21.73 | 91.67 | 21.60 |
| April | 240.00 | 22.40 | 13.17 | 22.33 | 13.17 | 22.28 |
| May | 210.50 | 22.51 | 38.83 | 22.49 | 21.00 | 22.38 |
| June | 89.67 | 22.91 | 94.33 | 23.45 | 0.00 | 23.45 |
| July | 152.67 | 22.42 | 33.50 | 22.66 | 0.00 | 22.66 |
| August | 175.17 | 22.28 | 52.83 | 22.66 | 0.00 | 22.66 |
| September | 106.83 | 22.69 | 89.17 | 23.27 | 0.00 | 23.27 |
| October | 157.50 | 22.90 | 17.00 | 22.97 | 2.00 | 22.95 |
| November | 247.50 | 22.12 | 74.83 | 21.87 | 74.83 | 21.72 |
| December | 260.00 | 21.46 | 169.50 | 21.29 | 169.50 | 21.22 |
| Annual Sum or Average | 2451.67 | 22.06 | 1063.17 | 22.00 | 760.50 | 21.84 |
| Minimum of Months | 89.67 | 21.15 | 13.17 | 21.11 | 0.00 | 21.09 |
| Maximum of Months | 294.67 | 22.91 | 242.00 | 23.45 | 242.00 | 23.45 |
Report: ComfortReportSimple55Monthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 20.95 | 270.50 | 20.95 | 270.50 | 20.95 |
| February | 247.00 | 21.04 | 224.83 | 21.02 | 224.83 | 21.01 |
| March | 299.00 | 21.18 | 189.17 | 21.11 | 189.17 | 21.07 |
| April | 260.00 | 21.90 | 30.33 | 21.80 | 30.33 | 21.73 |
| May | 248.17 | 22.47 | 39.67 | 22.31 | 35.67 | 22.16 |
| June | 103.17 | 23.59 | 43.00 | 23.71 | 0.00 | 23.71 |
| July | 130.50 | 23.18 | 12.50 | 23.25 | 0.00 | 23.25 |
| August | 204.50 | 22.99 | 5.83 | 23.02 | 0.00 | 23.02 |
| September | 155.00 | 23.07 | 38.50 | 23.26 | 0.00 | 23.26 |
| October | 270.17 | 22.90 | 10.67 | 22.83 | 10.67 | 22.76 |
| November | 273.00 | 21.51 | 131.00 | 21.34 | 131.00 | 21.26 |
| December | 260.00 | 21.00 | 240.00 | 20.99 | 240.00 | 20.99 |
| Annual Sum or Average | 2723.50 | 21.95 | 1236.00 | 21.72 | 1132.17 | 21.56 |
| Minimum of Months | 103.17 | 20.95 | 5.83 | 20.95 | 0.00 | 20.95 |
| Maximum of Months | 299.00 | 23.59 | 270.50 | 23.71 | 270.50 | 23.71 |
Report: ComfortReportSimple55Monthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.01 | 270.83 | 21.00 | 270.83 | 21.00 |
| February | 247.00 | 21.05 | 236.17 | 21.03 | 236.17 | 21.03 |
| March | 299.00 | 21.15 | 246.00 | 21.10 | 246.00 | 21.07 |
| April | 260.00 | 21.60 | 102.33 | 21.44 | 102.33 | 21.35 |
| May | 251.67 | 22.20 | 55.50 | 22.07 | 47.17 | 21.93 |
| June | 124.33 | 22.94 | 72.00 | 23.32 | 0.00 | 23.32 |
| July | 168.17 | 22.34 | 27.33 | 22.55 | 0.00 | 22.55 |
| August | 247.00 | 22.07 | 16.50 | 22.17 | 1.17 | 22.16 |
| September | 180.00 | 22.32 | 44.83 | 22.61 | 2.17 | 22.59 |
| October | 263.67 | 22.34 | 27.67 | 22.22 | 27.67 | 22.12 |
| November | 273.00 | 21.40 | 160.17 | 21.26 | 160.17 | 21.20 |
| December | 260.00 | 21.05 | 243.83 | 21.04 | 243.83 | 21.03 |
| Annual Sum or Average | 2846.83 | 21.69 | 1503.17 | 21.57 | 1337.50 | 21.44 |
| Minimum of Months | 124.33 | 21.01 | 16.50 | 21.00 | 0.00 | 21.00 |
| Maximum of Months | 299.00 | 22.94 | 270.83 | 23.32 | 270.83 | 23.32 |
Report: ComfortReportSimple55Monthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.02 | 266.67 | 21.01 | 266.67 | 21.01 |
| February | 247.00 | 21.13 | 220.17 | 21.09 | 220.17 | 21.07 |
| March | 299.00 | 21.37 | 185.00 | 21.25 | 185.00 | 21.19 |
| April | 260.00 | 21.97 | 32.83 | 21.87 | 32.83 | 21.80 |
| May | 242.67 | 22.41 | 36.17 | 22.30 | 30.00 | 22.18 |
| June | 111.83 | 22.97 | 70.17 | 23.33 | 0.00 | 23.33 |
| July | 243.50 | 22.32 | 2.00 | 22.33 | 0.00 | 22.33 |
| August | 296.50 | 21.99 | 0.17 | 21.99 | 0.17 | 21.99 |
| September | 181.00 | 22.46 | 36.83 | 22.69 | 0.00 | 22.69 |
| October | 257.83 | 22.59 | 12.00 | 22.52 | 12.00 | 22.46 |
| November | 273.00 | 21.62 | 124.00 | 21.45 | 124.00 | 21.36 |
| December | 260.00 | 21.14 | 221.00 | 21.09 | 221.00 | 21.07 |
| Annual Sum or Average | 2945.33 | 21.83 | 1207.00 | 21.68 | 1091.83 | 21.55 |
| Minimum of Months | 111.83 | 21.02 | 0.17 | 21.01 | 0.00 | 21.01 |
| Maximum of Months | 299.00 | 22.97 | 266.67 | 23.33 | 266.67 | 23.33 |
Report: ComfortReportSimple55Monthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.09 | 255.67 | 21.06 | 255.67 | 21.06 |
| February | 247.00 | 21.38 | 171.17 | 21.26 | 171.17 | 21.21 |
| March | 299.00 | 21.99 | 85.83 | 21.80 | 85.83 | 21.69 |
| April | 260.00 | 23.01 | 5.50 | 22.97 | 5.50 | 22.94 |
| May | 188.83 | 23.14 | 26.67 | 23.13 | 8.50 | 23.05 |
| June | 23.83 | 23.64 | 143.50 | 23.95 | 2.67 | 23.95 |
| July | 93.33 | 22.91 | 68.67 | 23.34 | 0.00 | 23.34 |
| August | 178.50 | 22.75 | 29.83 | 22.92 | 0.00 | 22.92 |
| September | 83.83 | 23.56 | 86.17 | 23.78 | 12.17 | 23.80 |
| October | 201.33 | 23.40 | 3.00 | 23.36 | 3.00 | 23.33 |
| November | 273.00 | 22.33 | 78.83 | 22.06 | 78.83 | 21.89 |
| December | 260.00 | 21.40 | 173.17 | 21.28 | 173.17 | 21.22 |
| Annual Sum or Average | 2381.67 | 22.28 | 1128.00 | 22.18 | 796.50 | 21.99 |
| Minimum of Months | 23.83 | 21.09 | 3.00 | 21.06 | 0.00 | 21.06 |
| Maximum of Months | 299.00 | 23.64 | 255.67 | 23.95 | 255.67 | 23.95 |
Report: ComfortReportSimple55Monthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 20.88 | 273.00 | 20.88 | 273.00 | 20.88 |
| February | 247.00 | 21.00 | 240.33 | 20.99 | 240.33 | 20.99 |
| March | 299.00 | 21.10 | 235.00 | 21.06 | 235.00 | 21.04 |
| April | 260.00 | 22.15 | 16.67 | 22.09 | 16.67 | 22.03 |
| May | 228.83 | 22.69 | 33.33 | 22.55 | 27.33 | 22.40 |
| June | 47.33 | 23.77 | 77.00 | 23.91 | 0.00 | 23.91 |
| July | 27.83 | 23.52 | 67.17 | 23.86 | 0.00 | 23.86 |
| August | 102.33 | 23.27 | 28.00 | 23.43 | 0.00 | 23.43 |
| September | 134.83 | 23.31 | 46.00 | 23.48 | 0.00 | 23.48 |
| October | 273.00 | 22.66 | 16.50 | 22.56 | 16.50 | 22.48 |
| November | 273.00 | 21.24 | 173.33 | 21.15 | 173.33 | 21.10 |
| December | 260.00 | 20.98 | 256.67 | 20.98 | 256.67 | 20.98 |
| Annual Sum or Average | 2426.17 | 21.80 | 1463.00 | 21.66 | 1238.83 | 21.49 |
| Minimum of Months | 27.83 | 20.88 | 16.50 | 20.88 | 0.00 | 20.88 |
| Maximum of Months | 299.00 | 23.77 | 273.00 | 23.91 | 273.00 | 23.91 |
Report: ComfortReportSimple55Monthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 15.56 | 273.00 | 15.56 | 273.00 | 15.56 |
| February | 247.00 | 17.91 | 232.17 | 17.81 | 232.17 | 17.77 |
| March | 299.00 | 19.50 | 270.33 | 19.43 | 270.33 | 19.40 |
| April | 260.00 | 20.58 | 147.17 | 20.34 | 147.17 | 20.23 |
| May | 270.00 | 20.96 | 108.67 | 20.69 | 104.33 | 20.50 |
| June | 160.50 | 21.99 | 62.33 | 22.52 | 5.00 | 22.45 |
| July | 90.50 | 22.67 | 84.67 | 23.55 | 4.67 | 23.67 |
| August | 148.83 | 22.17 | 67.83 | 22.80 | 5.83 | 22.82 |
| September | 185.50 | 21.61 | 65.17 | 21.95 | 20.00 | 21.84 |
| October | 261.17 | 21.17 | 62.50 | 20.86 | 62.50 | 20.66 |
| November | 273.00 | 19.66 | 199.33 | 19.45 | 199.33 | 19.37 |
| December | 260.00 | 17.60 | 254.67 | 17.56 | 254.67 | 17.55 |
| Annual Sum or Average | 2728.50 | 19.74 | 1827.83 | 19.48 | 1579.00 | 19.17 |
| Minimum of Months | 90.50 | 15.56 | 62.33 | 15.56 | 4.67 | 15.56 |
| Maximum of Months | 299.00 | 22.67 | 273.00 | 23.55 | 273.00 | 23.67 |
Report: ComfortReportSimple55Monthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 19.94 | 267.00 | 19.93 | 267.00 | 19.92 |
| February | 247.00 | 21.22 | 142.00 | 20.91 | 142.00 | 20.77 |
| March | 299.00 | 22.62 | 44.67 | 22.36 | 44.67 | 22.16 |
| April | 154.50 | 23.97 | 30.00 | 24.25 | 0.00 | 24.25 |
| May | 88.50 | 23.77 | 149.17 | 25.26 | 1.83 | 25.26 |
| June | 37.50 | 26.70 | 286.00 | 26.58 | 37.50 | 26.59 |
| July | 1.50 | 26.51 | 257.17 | 25.89 | 1.50 | 25.89 |
| August | 9.83 | 23.78 | 255.33 | 25.56 | 0.00 | 25.56 |
| September | 20.67 | 26.26 | 230.83 | 26.14 | 17.00 | 26.17 |
| October | 96.00 | 23.88 | 81.67 | 24.74 | 0.00 | 24.74 |
| November | 263.00 | 22.54 | 62.83 | 22.19 | 62.83 | 21.96 |
| December | 260.00 | 20.99 | 158.50 | 20.72 | 158.50 | 20.60 |
| Annual Sum or Average | 1750.50 | 22.14 | 1965.17 | 23.15 | 732.83 | 22.75 |
| Minimum of Months | 1.50 | 19.94 | 30.00 | 19.93 | 0.00 | 19.92 |
| Maximum of Months | 299.00 | 26.70 | 286.00 | 26.58 | 267.00 | 26.59 |
Report: ComfortReportSimple55Monthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 17.13 | 273.00 | 17.13 | 273.00 | 17.13 |
| February | 247.00 | 18.29 | 245.33 | 18.28 | 245.33 | 18.28 |
| March | 299.00 | 19.79 | 269.83 | 19.71 | 269.83 | 19.68 |
| April | 260.00 | 22.02 | 33.00 | 21.85 | 33.00 | 21.72 |
| May | 202.17 | 22.42 | 75.17 | 22.67 | 30.33 | 22.44 |
| June | 23.67 | 24.31 | 239.33 | 25.62 | 5.83 | 25.64 |
| July | 15.83 | 23.48 | 219.17 | 25.23 | 0.00 | 25.23 |
| August | 71.00 | 23.09 | 158.83 | 24.56 | 0.00 | 24.56 |
| September | 103.83 | 23.22 | 110.67 | 24.31 | 0.00 | 24.31 |
| October | 260.67 | 22.61 | 20.33 | 22.45 | 20.33 | 22.31 |
| November | 273.00 | 20.03 | 182.33 | 19.69 | 182.33 | 19.54 |
| December | 260.00 | 18.10 | 260.00 | 18.10 | 260.00 | 18.10 |
| Annual Sum or Average | 2289.17 | 20.29 | 2087.00 | 20.67 | 1320.00 | 20.19 |
| Minimum of Months | 15.83 | 17.13 | 20.33 | 17.13 | 0.00 | 17.13 |
| Maximum of Months | 299.00 | 24.31 | 273.00 | 25.62 | 273.00 | 25.64 |
Report: ComfortReportSimple55Monthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 231.00 | 20.99 | 229.33 | 20.99 | 229.33 | 20.99 |
| February | 209.00 | 21.20 | 175.17 | 21.12 | 175.17 | 21.09 |
| March | 253.00 | 21.56 | 138.67 | 21.37 | 138.67 | 21.28 |
| April | 212.83 | 22.51 | 20.17 | 22.38 | 20.17 | 22.28 |
| May | 177.00 | 22.81 | 28.50 | 22.69 | 19.67 | 22.55 |
| June | 28.67 | 23.65 | 109.67 | 23.93 | 0.00 | 23.93 |
| July | 12.67 | 23.37 | 137.67 | 23.95 | 0.00 | 23.95 |
| August | 39.67 | 23.06 | 104.00 | 23.74 | 0.00 | 23.74 |
| September | 70.33 | 23.51 | 70.00 | 23.75 | 0.00 | 23.75 |
| October | 189.00 | 23.18 | 4.83 | 23.12 | 4.83 | 23.07 |
| November | 231.00 | 21.86 | 99.17 | 21.61 | 99.17 | 21.48 |
| December | 220.00 | 21.09 | 201.83 | 21.05 | 201.83 | 21.04 |
| Annual Sum or Average | 1874.17 | 21.97 | 1319.00 | 21.98 | 888.83 | 21.77 |
| Minimum of Months | 12.67 | 20.99 | 4.83 | 20.99 | 0.00 | 20.99 |
| Maximum of Months | 253.00 | 23.65 | 229.33 | 23.95 | 229.33 | 23.95 |
Report: ComfortReportSimple55Monthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.07 | 257.00 | 21.05 | 257.00 | 21.05 |
| February | 247.00 | 21.41 | 140.17 | 21.27 | 140.17 | 21.20 |
| March | 299.00 | 22.19 | 56.33 | 22.01 | 56.33 | 21.88 |
| April | 180.33 | 22.99 | 0.83 | 22.99 | 0.17 | 22.99 |
| May | 112.00 | 22.99 | 58.00 | 23.29 | 2.50 | 23.26 |
| June | 12.50 | 23.44 | 213.50 | 23.97 | 2.67 | 23.97 |
| July | 4.17 | 23.14 | 228.67 | 23.98 | 0.00 | 23.98 |
| August | 31.00 | 22.90 | 208.33 | 23.85 | 0.00 | 23.85 |
| September | 52.33 | 23.39 | 126.83 | 23.82 | 11.67 | 23.83 |
| October | 178.83 | 23.09 | 1.17 | 23.08 | 1.17 | 23.07 |
| November | 273.00 | 22.02 | 78.00 | 21.80 | 78.00 | 21.67 |
| December | 260.00 | 21.25 | 181.50 | 21.17 | 181.50 | 21.14 |
| Annual Sum or Average | 1923.17 | 22.04 | 1550.33 | 22.30 | 731.17 | 22.09 |
| Minimum of Months | 4.17 | 21.07 | 0.83 | 21.05 | 0.00 | 21.05 |
| Maximum of Months | 299.00 | 23.44 | 257.00 | 23.98 | 257.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 160.00 | 23.31 | 128.50 | 23.43 | 50.67 | 23.36 |
| February | 83.83 | 23.69 | 130.67 | 23.80 | 25.83 | 23.75 |
| March | 25.50 | 23.86 | 175.67 | 23.96 | 6.00 | 23.95 |
| April | 0.17 | 24.00 | 180.33 | 23.99 | 0.00 | 23.99 |
| May | 0.00 | 0.00 | 237.67 | 23.99 | 0.00 | 23.99 |
| June | 1.83 | 24.00 | 282.00 | 24.00 | 1.83 | 24.00 |
| July | 2.50 | 24.00 | 258.00 | 24.00 | 2.50 | 24.00 |
| August | 0.83 | 24.00 | 295.83 | 24.00 | 0.83 | 24.00 |
| September | 6.17 | 24.00 | 252.00 | 24.00 | 6.17 | 24.00 |
| October | 0.00 | 0.00 | 202.50 | 23.99 | 0.00 | 23.99 |
| November | 39.83 | 23.69 | 153.67 | 23.92 | 5.67 | 23.92 |
| December | 101.33 | 22.93 | 130.67 | 23.45 | 28.00 | 23.43 |
| Annual Sum or Average | 422.00 | 23.38 | 2427.50 | 23.87 | 127.50 | 23.85 |
| Minimum of Months | 0.00 | 0.00 | 128.50 | 23.43 | 0.00 | 23.36 |
| Maximum of Months | 160.00 | 24.00 | 295.83 | 24.00 | 50.67 | 24.00 |
Report: ComfortReportSimple55Monthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 231.00 | 21.03 | 194.67 | 21.02 | 194.67 | 21.01 |
| February | 209.00 | 21.28 | 119.50 | 21.18 | 119.50 | 21.13 |
| March | 253.00 | 21.50 | 43.50 | 21.43 | 43.50 | 21.37 |
| April | 176.83 | 22.18 | 0.67 | 22.18 | 0.67 | 22.17 |
| May | 123.83 | 22.03 | 47.00 | 22.55 | 1.33 | 22.54 |
| June | 15.50 | 22.29 | 183.83 | 23.86 | 2.83 | 23.87 |
| July | 5.17 | 22.18 | 166.83 | 23.94 | 0.00 | 23.94 |
| August | 26.00 | 22.11 | 125.67 | 23.67 | 0.00 | 23.67 |
| September | 60.67 | 22.53 | 122.17 | 23.51 | 13.00 | 23.54 |
| October | 133.67 | 22.20 | 12.67 | 22.34 | 0.50 | 22.34 |
| November | 221.50 | 21.82 | 57.33 | 21.66 | 57.33 | 21.54 |
| December | 220.00 | 21.26 | 123.83 | 21.17 | 123.83 | 21.12 |
| Annual Sum or Average | 1676.17 | 21.64 | 1197.67 | 22.06 | 557.17 | 21.90 |
| Minimum of Months | 5.17 | 21.03 | 0.67 | 21.02 | 0.00 | 21.01 |
| Maximum of Months | 253.00 | 22.53 | 194.67 | 23.94 | 194.67 | 23.94 |
Report: ComfortReportSimple55Monthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 273.00 | 21.02 | 267.83 | 21.01 | 267.83 | 21.01 |
| February | 247.00 | 21.24 | 205.83 | 21.16 | 205.83 | 21.13 |
| March | 299.00 | 21.81 | 135.50 | 21.58 | 135.50 | 21.47 |
| April | 260.00 | 23.11 | 5.33 | 23.08 | 5.33 | 23.04 |
| May | 182.33 | 23.26 | 27.17 | 23.21 | 10.83 | 23.10 |
| June | 17.83 | 23.73 | 151.50 | 23.97 | 0.00 | 23.97 |
| July | 14.83 | 23.35 | 161.33 | 23.94 | 0.00 | 23.94 |
| August | 56.17 | 23.09 | 95.67 | 23.66 | 0.00 | 23.66 |
| September | 71.00 | 23.72 | 79.17 | 23.87 | 0.00 | 23.87 |
| October | 220.17 | 23.50 | 3.00 | 23.47 | 3.00 | 23.44 |
| November | 273.00 | 22.17 | 106.17 | 21.87 | 106.17 | 21.70 |
| December | 260.00 | 21.20 | 218.50 | 21.12 | 218.50 | 21.10 |
| Annual Sum or Average | 2174.33 | 22.19 | 1457.00 | 22.14 | 953.00 | 21.91 |
| Minimum of Months | 14.83 | 21.02 | 3.00 | 21.01 | 0.00 | 21.01 |
| Maximum of Months | 299.00 | 23.73 | 267.83 | 23.97 | 267.83 | 23.97 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.06357 | 16.38082 | -0.6274 | 13.78816 |
| February | 247.00000 | 21.38145 | 18.98913 | -0.4575 | 10.70705 |
| March | 299.00000 | 21.61289 | 21.88462 | -0.3349 | 8.78277 |
| April | 260.00000 | 22.10782 | 26.21138 | -0.1420 | 7.13263 |
| May | 286.00000 | 22.68222 | 27.78640 | -0.8622 | 24.52300 |
| June | 286.00000 | 23.56910 | 33.23686 | -0.3917 | 10.07673 |
| July | 260.00000 | 23.19988 | 35.17510 | -0.4385 | 11.09917 |
| August | 299.00000 | 23.03716 | 32.45968 | -0.5188 | 13.66968 |
| September | 260.00000 | 23.24892 | 35.15799 | -0.4887 | 13.36621 |
| October | 273.00000 | 23.08947 | 26.22555 | 0.17646 | 7.25271 |
| November | 273.00000 | 22.00870 | 22.54719 | -0.2082 | 8.15073 |
| December | 260.00000 | 21.30450 | 19.20294 | -0.4907 | 11.07982 |
| Annual Sum or Average | 3276.00000 | 22.37042 | 26.33491 | -0.4006 | 11.69688 |
| Minimum of Months | 247.00000 | 21.06357 | 16.38082 | -0.8622 | 7.13263 |
| Maximum of Months | 299.00000 | 23.56910 | 35.17510 | 0.17646 | 24.52300 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.17174 | 16.36628 | -0.5584 | 12.15229 |
| February | 247.00000 | 21.62784 | 18.86042 | -0.3618 | 9.22239 |
| March | 299.00000 | 21.97236 | 21.61514 | -0.2146 | 7.48085 |
| April | 260.00000 | 22.49829 | 25.76525 | -0.0188 | 6.38634 |
| May | 286.00000 | 22.87734 | 27.51617 | -0.7696 | 20.87313 |
| June | 286.00000 | 23.60666 | 33.13517 | -0.3647 | 9.06010 |
| July | 260.00000 | 22.92822 | 35.74582 | -0.5215 | 12.19299 |
| August | 299.00000 | 22.90451 | 32.75704 | -0.5543 | 13.77371 |
| September | 260.00000 | 23.39905 | 34.87884 | -0.4213 | 10.99749 |
| October | 273.00000 | 23.33985 | 25.81580 | 0.25821 | 7.52878 |
| November | 273.00000 | 22.31928 | 22.25562 | -0.1067 | 7.53429 |
| December | 260.00000 | 21.51546 | 19.09195 | -0.4031 | 9.69208 |
| Annual Sum or Average | 3276.00000 | 22.52386 | 26.21455 | -0.3387 | 10.63298 |
| Minimum of Months | 247.00000 | 21.17174 | 16.36628 | -0.7696 | 6.38634 |
| Maximum of Months | 299.00000 | 23.60666 | 35.74582 | 0.25821 | 20.87313 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 20.94707 | 14.53911 | -0.6091 | 13.08276 |
| February | 247.00000 | 21.03714 | 17.45057 | -0.5179 | 10.87423 |
| March | 299.00000 | 21.15428 | 20.43898 | -0.4218 | 9.07442 |
| April | 260.00000 | 21.77915 | 24.77489 | -0.2046 | 6.56667 |
| May | 286.00000 | 22.56294 | 26.08249 | -0.9274 | 26.07487 |
| June | 286.00000 | 23.80849 | 31.55047 | -0.4182 | 9.28363 |
| July | 260.00000 | 23.47636 | 34.16931 | -0.5076 | 11.22869 |
| August | 299.00000 | 23.18865 | 31.73830 | -0.6244 | 14.57829 |
| September | 260.00000 | 23.33331 | 34.03306 | -0.5811 | 13.89317 |
| October | 273.00000 | 22.80212 | 25.07161 | 0.05202 | 6.07925 |
| November | 273.00000 | 21.45877 | 21.23428 | -0.3381 | 8.32201 |
| December | 260.00000 | 21.00505 | 17.65197 | -0.5304 | 11.15761 |
| Annual Sum or Average | 3276.00000 | 22.22623 | 24.95989 | -0.4713 | 11.75634 |
| Minimum of Months | 247.00000 | 20.94707 | 14.53911 | -0.9274 | 6.07925 |
| Maximum of Months | 299.00000 | 23.80849 | 34.16931 | 0.05202 | 26.07487 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.00496 | 16.42323 | -0.6870 | 15.22934 |
| February | 247.00000 | 21.04387 | 19.27820 | -0.5999 | 12.86771 |
| March | 299.00000 | 21.13399 | 22.32254 | -0.5009 | 10.64776 |
| April | 260.00000 | 21.55851 | 26.87855 | -0.3031 | 7.71830 |
| May | 286.00000 | 22.34425 | 28.42696 | -1.0058 | 29.53432 |
| June | 286.00000 | 23.44519 | 33.70684 | -0.4671 | 11.30586 |
| July | 260.00000 | 22.67967 | 36.29191 | -0.6292 | 15.06631 |
| August | 299.00000 | 22.26155 | 34.03046 | -0.8054 | 20.86234 |
| September | 260.00000 | 22.74553 | 36.46840 | -0.7170 | 19.00415 |
| October | 273.00000 | 22.35831 | 27.60784 | -0.0487 | 6.43339 |
| November | 273.00000 | 21.38792 | 23.25105 | -0.4056 | 9.43790 |
| December | 260.00000 | 21.05123 | 19.41481 | -0.5984 | 12.89178 |
| Annual Sum or Average | 3276.00000 | 21.92767 | 27.07677 | -0.5665 | 14.34296 |
| Minimum of Months | 247.00000 | 21.00496 | 16.42323 | -1.0058 | 6.43339 |
| Maximum of Months | 299.00000 | 23.44519 | 36.46840 | -0.0487 | 29.53432 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.01857 | 16.46526 | -0.6385 | 13.84325 |
| February | 247.00000 | 21.12024 | 19.27226 | -0.5457 | 11.57874 |
| March | 299.00000 | 21.34161 | 22.19526 | -0.4197 | 9.18663 |
| April | 260.00000 | 21.90645 | 26.54984 | -0.1934 | 6.51734 |
| May | 286.00000 | 22.54830 | 28.20293 | -0.9145 | 25.60275 |
| June | 286.00000 | 23.41010 | 33.74610 | -0.4617 | 10.57466 |
| July | 260.00000 | 22.18748 | 37.24937 | -0.7727 | 18.34506 |
| August | 299.00000 | 21.86444 | 34.76246 | -0.9147 | 23.61097 |
| September | 260.00000 | 22.78165 | 36.47886 | -0.6873 | 17.14504 |
| October | 273.00000 | 22.60979 | 27.37763 | 0.02530 | 6.19397 |
| November | 273.00000 | 21.59253 | 23.10117 | -0.3335 | 8.47380 |
| December | 260.00000 | 21.13407 | 19.38803 | -0.5407 | 11.56889 |
| Annual Sum or Average | 3276.00000 | 21.96801 | 27.13582 | -0.5361 | 13.65279 |
| Minimum of Months | 247.00000 | 21.01857 | 16.46526 | -0.9147 | 6.19397 |
| Maximum of Months | 299.00000 | 23.41010 | 37.24937 | 0.02530 | 25.60275 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.05608 | 16.38573 | -0.6343 | 13.94843 |
| February | 247.00000 | 21.36569 | 19.00385 | -0.4633 | 10.77646 |
| March | 299.00000 | 21.58974 | 21.90739 | -0.3422 | 8.83780 |
| April | 260.00000 | 22.07861 | 26.25023 | -0.1508 | 7.15208 |
| May | 286.00000 | 22.64523 | 27.85902 | -0.8782 | 25.06335 |
| June | 286.00000 | 23.54448 | 33.31900 | -0.4056 | 10.34012 |
| July | 260.00000 | 23.15078 | 35.29025 | -0.4581 | 11.50085 |
| August | 299.00000 | 22.99318 | 32.55299 | -0.5362 | 14.07640 |
| September | 260.00000 | 23.23149 | 35.20580 | -0.4974 | 13.56241 |
| October | 273.00000 | 23.07017 | 26.26530 | 0.17028 | 7.21841 |
| November | 273.00000 | 21.96711 | 22.59991 | -0.2212 | 8.21285 |
| December | 260.00000 | 21.25886 | 19.23880 | -0.5090 | 11.35137 |
| Annual Sum or Average | 3276.00000 | 22.34081 | 26.38710 | -0.4125 | 11.90065 |
| Minimum of Months | 247.00000 | 21.05608 | 16.38573 | -0.8782 | 7.15208 |
| Maximum of Months | 299.00000 | 23.54448 | 35.29025 | 0.17028 | 25.06335 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.14177 | 16.38980 | -0.5683 | 12.31460 |
| February | 247.00000 | 21.59793 | 18.89609 | -0.3704 | 9.25237 |
| March | 299.00000 | 21.94251 | 21.65656 | -0.2234 | 7.48938 |
| April | 260.00000 | 22.48234 | 25.80029 | -0.0238 | 6.34205 |
| May | 286.00000 | 22.85704 | 27.57238 | -0.7793 | 21.13694 |
| June | 286.00000 | 23.58178 | 33.22120 | -0.3787 | 9.27100 |
| July | 260.00000 | 22.83154 | 35.94343 | -0.5549 | 12.86506 |
| August | 299.00000 | 22.83221 | 32.90217 | -0.5810 | 14.36051 |
| September | 260.00000 | 23.38355 | 34.93495 | -0.4306 | 11.11689 |
| October | 273.00000 | 23.32149 | 25.88650 | 0.25053 | 7.43988 |
| November | 273.00000 | 22.25078 | 22.35271 | -0.1277 | 7.53856 |
| December | 260.00000 | 21.43120 | 19.16173 | -0.4313 | 9.96716 |
| Annual Sum or Average | 3276.00000 | 22.48175 | 26.29108 | -0.3539 | 10.81863 |
| Minimum of Months | 247.00000 | 21.14177 | 16.38980 | -0.7793 | 6.34205 |
| Maximum of Months | 299.00000 | 23.58178 | 35.94343 | 0.25053 | 21.13694 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 20.94556 | 14.54530 | -0.6111 | 13.13641 |
| February | 247.00000 | 21.03244 | 17.46364 | -0.5198 | 10.90451 |
| March | 299.00000 | 21.14674 | 20.45556 | -0.4242 | 9.10565 |
| April | 260.00000 | 21.77116 | 24.79351 | -0.2065 | 6.57371 |
| May | 286.00000 | 22.55499 | 26.10534 | -0.9305 | 26.18035 |
| June | 286.00000 | 23.80427 | 31.57532 | -0.4210 | 9.33708 |
| July | 260.00000 | 23.45411 | 34.23231 | -0.5161 | 11.42643 |
| August | 299.00000 | 23.16042 | 31.79736 | -0.6339 | 14.84062 |
| September | 260.00000 | 23.32631 | 34.05493 | -0.5843 | 13.97104 |
| October | 273.00000 | 22.78678 | 25.10385 | 0.04818 | 6.07334 |
| November | 273.00000 | 21.42923 | 21.27810 | -0.3462 | 8.39677 |
| December | 260.00000 | 20.99763 | 17.66730 | -0.5361 | 11.27150 |
| Annual Sum or Average | 3276.00000 | 22.21413 | 24.98823 | -0.4758 | 11.84097 |
| Minimum of Months | 247.00000 | 20.94556 | 14.54530 | -0.9305 | 6.07334 |
| Maximum of Months | 299.00000 | 23.80427 | 34.23231 | 0.04818 | 26.18035 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.00496 | 16.43078 | -0.6872 | 15.23274 |
| February | 247.00000 | 21.04391 | 19.28578 | -0.6000 | 12.86805 |
| March | 299.00000 | 21.13522 | 22.32899 | -0.5006 | 10.64326 |
| April | 260.00000 | 21.56219 | 26.88232 | -0.3023 | 7.71107 |
| May | 286.00000 | 22.34999 | 28.42547 | -1.0040 | 29.46345 |
| June | 286.00000 | 23.45053 | 33.69698 | -0.4652 | 11.26534 |
| July | 260.00000 | 22.68523 | 36.28208 | -0.6277 | 15.03104 |
| August | 299.00000 | 22.26454 | 34.02661 | -0.8048 | 20.84949 |
| September | 260.00000 | 22.74867 | 36.46522 | -0.7162 | 18.98131 |
| October | 273.00000 | 22.36015 | 27.61257 | -0.0486 | 6.43505 |
| November | 273.00000 | 21.38651 | 23.26036 | -0.4064 | 9.44882 |
| December | 260.00000 | 21.05100 | 19.42263 | -0.5989 | 12.90323 |
| Annual Sum or Average | 3276.00000 | 21.93002 | 27.07827 | -0.5660 | 14.32874 |
| Minimum of Months | 247.00000 | 21.00496 | 16.43078 | -1.0040 | 6.43505 |
| Maximum of Months | 299.00000 | 23.45053 | 36.46522 | -0.0486 | 29.46345 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.01871 | 16.47082 | -0.6386 | 13.84741 |
| February | 247.00000 | 21.12054 | 19.27782 | -0.5457 | 11.57855 |
| March | 299.00000 | 21.34314 | 22.19973 | -0.4194 | 9.18301 |
| April | 260.00000 | 21.91037 | 26.55156 | -0.1925 | 6.51273 |
| May | 286.00000 | 22.55359 | 28.19976 | -0.9127 | 25.53754 |
| June | 286.00000 | 23.41690 | 33.73239 | -0.4594 | 10.52741 |
| July | 260.00000 | 22.19101 | 37.24316 | -0.7718 | 18.31983 |
| August | 299.00000 | 21.86603 | 34.76089 | -0.9145 | 23.60780 |
| September | 260.00000 | 22.78434 | 36.47557 | -0.6866 | 17.12667 |
| October | 273.00000 | 22.61089 | 27.38161 | 0.02526 | 6.19496 |
| November | 273.00000 | 21.58994 | 23.10971 | -0.3347 | 8.48542 |
| December | 260.00000 | 21.13321 | 19.39449 | -0.5415 | 11.58410 |
| Annual Sum or Average | 3276.00000 | 21.97000 | 27.13643 | -0.5357 | 13.64111 |
| Minimum of Months | 247.00000 | 21.01871 | 16.47082 | -0.9145 | 6.19496 |
| Maximum of Months | 299.00000 | 23.41690 | 37.24316 | 0.02526 | 25.53754 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.05925 | 16.39062 | -0.6317 | 13.89009 |
| February | 247.00000 | 21.37076 | 19.00617 | -0.4615 | 10.75401 |
| March | 299.00000 | 21.59950 | 21.90502 | -0.3391 | 8.80915 |
| April | 260.00000 | 22.10259 | 26.22606 | -0.1435 | 7.12202 |
| May | 286.00000 | 22.66999 | 27.81925 | -0.8679 | 24.69957 |
| June | 286.00000 | 23.55868 | 33.28085 | -0.3987 | 10.19537 |
| July | 260.00000 | 23.18402 | 35.21552 | -0.4455 | 11.21986 |
| August | 299.00000 | 23.02390 | 32.48950 | -0.5244 | 13.78082 |
| September | 260.00000 | 23.25410 | 35.15529 | -0.4877 | 13.29439 |
| October | 273.00000 | 23.09479 | 26.22379 | 0.17769 | 7.25061 |
| November | 273.00000 | 21.99348 | 22.57119 | -0.2131 | 8.17844 |
| December | 260.00000 | 21.27527 | 19.23292 | -0.5027 | 11.26084 |
| Annual Sum or Average | 3276.00000 | 22.36044 | 26.35669 | -0.4051 | 11.76678 |
| Minimum of Months | 247.00000 | 21.05925 | 16.39062 | -0.8679 | 7.12202 |
| Maximum of Months | 299.00000 | 23.55868 | 35.21552 | 0.17769 | 24.69957 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.15329 | 16.38304 | -0.5635 | 12.22134 |
| February | 247.00000 | 21.60684 | 18.88756 | -0.3672 | 9.22530 |
| March | 299.00000 | 21.96157 | 21.63567 | -0.2173 | 7.45557 |
| April | 260.00000 | 22.52099 | 25.74360 | -0.0119 | 6.33931 |
| May | 286.00000 | 22.89171 | 27.50246 | -0.7638 | 20.62966 |
| June | 286.00000 | 23.60497 | 33.15415 | -0.3675 | 9.06168 |
| July | 260.00000 | 22.89791 | 35.80671 | -0.5321 | 12.34314 |
| August | 299.00000 | 22.88604 | 32.79548 | -0.5613 | 13.87791 |
| September | 260.00000 | 23.41839 | 34.84512 | -0.4151 | 10.75146 |
| October | 273.00000 | 23.35589 | 25.79902 | 0.26231 | 7.53055 |
| November | 273.00000 | 22.29519 | 22.28684 | -0.1137 | 7.52805 |
| December | 260.00000 | 21.45650 | 19.14290 | -0.4222 | 9.86627 |
| Annual Sum or Average | 3276.00000 | 22.51476 | 26.22952 | -0.3417 | 10.62715 |
| Minimum of Months | 247.00000 | 21.15329 | 16.38304 | -0.7638 | 6.33931 |
| Maximum of Months | 299.00000 | 23.60497 | 35.80671 | 0.26231 | 20.62966 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 20.94824 | 14.52543 | -0.6084 | 13.06543 |
| February | 247.00000 | 21.03901 | 17.43234 | -0.5155 | 10.82648 |
| March | 299.00000 | 21.17968 | 20.39630 | -0.4122 | 8.93450 |
| April | 260.00000 | 21.89503 | 24.61849 | -0.1751 | 6.38758 |
| May | 286.00000 | 22.66865 | 25.88678 | -0.8895 | 24.66000 |
| June | 286.00000 | 23.84741 | 31.41150 | -0.3978 | 8.85381 |
| July | 260.00000 | 23.57540 | 33.91079 | -0.4709 | 10.36790 |
| August | 299.00000 | 23.30172 | 31.49529 | -0.5850 | 13.50024 |
| September | 260.00000 | 23.44416 | 33.78164 | -0.5416 | 12.70541 |
| October | 273.00000 | 22.91503 | 24.87937 | 0.07982 | 6.13325 |
| November | 273.00000 | 21.51078 | 21.15441 | -0.3241 | 8.22209 |
| December | 260.00000 | 21.00397 | 17.63721 | -0.5309 | 11.16905 |
| Annual Sum or Average | 3276.00000 | 22.29124 | 24.82535 | -0.4497 | 11.29937 |
| Minimum of Months | 247.00000 | 20.94824 | 14.52543 | -0.8895 | 6.13325 |
| Maximum of Months | 299.00000 | 23.84741 | 33.91079 | 0.07982 | 24.66000 |
Report: OccupantComfortDataSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.00523 | 16.42578 | -0.6866 | 15.21733 |
| February | 247.00000 | 21.04676 | 19.27868 | -0.5980 | 12.82628 |
| March | 299.00000 | 21.14835 | 22.31230 | -0.4949 | 10.54692 |
| April | 260.00000 | 21.60361 | 26.83249 | -0.2891 | 7.59433 |
| May | 286.00000 | 22.41159 | 28.32113 | -0.9781 | 28.49317 |
| June | 286.00000 | 23.50320 | 33.55383 | -0.4405 | 10.74566 |
| July | 260.00000 | 22.79264 | 36.05381 | -0.5896 | 14.05444 |
| August | 299.00000 | 22.34710 | 33.86247 | -0.7748 | 19.90748 |
| September | 260.00000 | 22.79531 | 36.35560 | -0.6970 | 18.39210 |
| October | 273.00000 | 22.39494 | 27.55654 | -0.0381 | 6.43034 |
| November | 273.00000 | 21.40082 | 23.23984 | -0.4015 | 9.40131 |
| December | 260.00000 | 21.05294 | 19.41595 | -0.5979 | 12.88527 |
| Annual Sum or Average | 3276.00000 | 21.96873 | 27.00153 | -0.5512 | 13.96014 |
| Minimum of Months | 247.00000 | 21.00523 | 16.42578 | -0.9781 | 6.43034 |
| Maximum of Months | 299.00000 | 23.50320 | 36.35560 | -0.0381 | 28.49317 |
Report: OccupantComfortDataSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.01953 | 16.47175 | -0.6370 | 13.80771 |
| February | 247.00000 | 21.12666 | 19.27502 | -0.5421 | 11.51025 |
| March | 299.00000 | 21.36803 | 22.17965 | -0.4096 | 9.05015 |
| April | 260.00000 | 21.97267 | 26.48407 | -0.1735 | 6.41884 |
| May | 286.00000 | 22.63882 | 28.04679 | -0.8774 | 24.29862 |
| June | 286.00000 | 23.52552 | 33.46087 | -0.4176 | 9.70671 |
| July | 260.00000 | 22.36639 | 36.87323 | -0.7148 | 16.58757 |
| August | 299.00000 | 21.99926 | 34.49731 | -0.8705 | 22.05747 |
| September | 260.00000 | 22.86866 | 36.27546 | -0.6563 | 16.24590 |
| October | 273.00000 | 22.66674 | 27.29237 | 0.04134 | 6.23101 |
| November | 273.00000 | 21.61582 | 23.08307 | -0.3256 | 8.42591 |
| December | 260.00000 | 21.13681 | 19.39292 | -0.5392 | 11.54544 |
| Annual Sum or Average | 3276.00000 | 22.03454 | 27.01297 | -0.5129 | 13.07936 |
| Minimum of Months | 247.00000 | 21.01953 | 16.47175 | -0.8774 | 6.23101 |
| Maximum of Months | 299.00000 | 23.52552 | 36.87323 | 0.04134 | 24.29862 |
Report: OccupantComfortDataSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.08587 | 18.39917 | -0.5873 | 12.62034 |
| February | 247.00000 | 21.37543 | 21.08910 | -0.4580 | 10.00879 |
| March | 299.00000 | 21.98548 | 23.68227 | -0.2575 | 7.24723 |
| April | 260.00000 | 23.00805 | 27.43183 | 0.05830 | 5.80069 |
| May | 286.00000 | 23.42777 | 28.81974 | -0.6277 | 15.78455 |
| June | 286.00000 | 23.96632 | 35.15275 | -0.2437 | 6.60417 |
| July | 260.00000 | 23.48319 | 37.20079 | -0.3885 | 8.93324 |
| August | 299.00000 | 23.15413 | 34.90980 | -0.5312 | 12.18183 |
| September | 260.00000 | 23.84172 | 37.37197 | -0.3438 | 8.28571 |
| October | 273.00000 | 23.55284 | 28.05859 | 0.24397 | 6.98649 |
| November | 273.00000 | 22.32626 | 24.43106 | -0.1557 | 7.32120 |
| December | 260.00000 | 21.40085 | 21.17348 | -0.4519 | 10.01785 |
| Annual Sum or Average | 3276.00000 | 22.72998 | 28.20608 | -0.3135 | 9.34851 |
| Minimum of Months | 247.00000 | 21.08587 | 18.39917 | -0.6277 | 5.80069 |
| Maximum of Months | 299.00000 | 23.96632 | 37.37197 | 0.24397 | 15.78455 |
Report: OccupantComfortDataSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 19.94400 | 13.09496 | -0.7587 | 18.75726 |
| February | 247.00000 | 21.21826 | 15.17640 | -0.4547 | 11.00299 |
| March | 299.00000 | 22.61610 | 16.92626 | -0.1155 | 6.66239 |
| April | 260.00000 | 24.47139 | 19.49292 | 0.34726 | 8.13659 |
| May | 286.00000 | 25.21124 | 20.74958 | -0.1696 | 9.33399 |
| June | 286.00000 | 26.56525 | 26.10624 | 0.37904 | 8.42543 |
| July | 260.00000 | 25.87265 | 29.27969 | 0.21302 | 6.49590 |
| August | 299.00000 | 25.43045 | 27.39466 | 0.04746 | 6.06265 |
| September | 260.00000 | 25.97803 | 28.22672 | 0.15996 | 6.87964 |
| October | 273.00000 | 24.80761 | 20.57043 | 0.43684 | 9.89073 |
| November | 273.00000 | 22.61789 | 17.83792 | -0.1078 | 7.50093 |
| December | 260.00000 | 20.98678 | 15.43954 | -0.5049 | 12.14480 |
| Annual Sum or Average | 3276.00000 | 23.84221 | 20.90836 | -0.0409 | 9.22502 |
| Minimum of Months | 247.00000 | 19.94400 | 13.09496 | -0.7587 | 6.06265 |
| Maximum of Months | 299.00000 | 26.56525 | 29.27969 | 0.43684 | 18.75726 |
Report: OccupantComfortDataSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 17.13485 | 17.05460 | -1.3365 | 42.65372 |
| February | 247.00000 | 18.29370 | 19.71058 | -1.0587 | 30.02886 |
| March | 299.00000 | 19.79474 | 21.79659 | -0.7000 | 16.77553 |
| April | 260.00000 | 22.01863 | 24.54717 | -0.1557 | 6.51321 |
| May | 286.00000 | 23.17164 | 25.46600 | -0.7445 | 21.96699 |
| June | 286.00000 | 25.49794 | 29.25383 | 0.07563 | 6.80404 |
| July | 260.00000 | 25.13236 | 31.20089 | 0.02009 | 6.19871 |
| August | 299.00000 | 24.47016 | 29.57326 | -0.2131 | 8.13513 |
| September | 260.00000 | 24.30726 | 32.35823 | -0.3007 | 9.99630 |
| October | 273.00000 | 22.68705 | 25.32640 | 0.01377 | 6.29491 |
| November | 273.00000 | 20.03177 | 22.60700 | -0.6369 | 16.58472 |
| December | 260.00000 | 18.10089 | 19.99038 | -1.0994 | 31.79426 |
| Annual Sum or Average | 3276.00000 | 21.76394 | 24.94653 | -0.5067 | 16.83614 |
| Minimum of Months | 247.00000 | 17.13485 | 17.05460 | -1.3365 | 6.19871 |
| Maximum of Months | 299.00000 | 25.49794 | 32.35823 | 0.07563 | 42.65372 |
Report: OccupantComfortDataSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 231.00000 | 20.98948 | 13.56083 | -0.6749 | 14.88856 |
| February | 209.00000 | 21.20229 | 16.43255 | -0.5288 | 11.60736 |
| March | 253.00000 | 21.56030 | 19.06360 | -0.3595 | 8.74997 |
| April | 220.00000 | 22.55808 | 22.90718 | -0.0426 | 6.38605 |
| May | 242.00000 | 23.13159 | 24.17562 | -0.7338 | 19.54442 |
| June | 242.00000 | 23.95703 | 30.93181 | -0.2573 | 6.92106 |
| July | 220.00000 | 23.95415 | 32.90546 | -0.2066 | 6.19424 |
| August | 253.00000 | 23.84127 | 30.40072 | -0.2921 | 7.57089 |
| September | 220.00000 | 23.83918 | 32.70605 | -0.3449 | 8.48748 |
| October | 231.00000 | 23.32591 | 23.11804 | 0.17673 | 6.68893 |
| November | 231.00000 | 21.86251 | 19.72358 | -0.2811 | 8.42874 |
| December | 220.00000 | 21.08517 | 16.61230 | -0.5697 | 12.26914 |
| Annual Sum or Average | 2772.00000 | 22.62499 | 23.60846 | -0.3432 | 9.82154 |
| Minimum of Months | 209.00000 | 20.98948 | 13.56083 | -0.7338 | 6.19424 |
| Maximum of Months | 253.00000 | 23.95703 | 32.90546 | 0.17673 | 19.54442 |
Report: OccupantComfortDataSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.06850 | 17.58511 | -0.5622 | 11.97598 |
| February | 247.00000 | 21.40832 | 20.25494 | -0.3940 | 9.00434 |
| March | 299.00000 | 22.19471 | 22.75897 | -0.1286 | 6.51301 |
| April | 260.00000 | 23.29516 | 25.88285 | 0.22169 | 6.90766 |
| May | 286.00000 | 23.59809 | 27.22035 | -0.4442 | 11.06152 |
| June | 286.00000 | 23.97011 | 33.74676 | -0.1335 | 5.79535 |
| July | 260.00000 | 23.95726 | 35.28784 | -0.1113 | 5.51290 |
| August | 299.00000 | 23.84874 | 33.02172 | -0.2092 | 6.55870 |
| September | 260.00000 | 23.85830 | 36.27183 | -0.2639 | 7.14824 |
| October | 273.00000 | 23.39872 | 27.45422 | 0.25572 | 7.07853 |
| November | 273.00000 | 22.02264 | 23.95213 | -0.1753 | 7.10550 |
| December | 260.00000 | 21.25017 | 20.52549 | -0.4500 | 9.77380 |
| Annual Sum or Average | 3276.00000 | 22.84033 | 27.05261 | -0.1990 | 7.85236 |
| Minimum of Months | 247.00000 | 21.06850 | 17.58511 | -0.5622 | 5.51290 |
| Maximum of Months | 299.00000 | 23.97011 | 36.27183 | 0.25572 | 11.97598 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 23.58642 | 45.68752 | 0.39017 | 9.22134 |
| February | 247.00000 | 23.88873 | 39.42703 | 0.49097 | 10.42070 |
| March | 299.00000 | 23.98076 | 33.83919 | 0.54334 | 11.46053 |
| April | 260.00000 | 23.99446 | 31.29810 | 0.60418 | 12.88816 |
| May | 286.00000 | 23.99530 | 32.22921 | -0.0474 | 5.49941 |
| June | 286.00000 | 23.99885 | 38.38705 | 0.09082 | 5.67000 |
| July | 260.00000 | 24.00003 | 43.30011 | 0.12960 | 5.78902 |
| August | 299.00000 | 23.99944 | 39.81375 | 0.07159 | 5.59286 |
| September | 260.00000 | 23.99743 | 39.24223 | 0.03117 | 5.49941 |
| October | 273.00000 | 23.99482 | 31.67113 | 0.61653 | 13.22206 |
| November | 273.00000 | 23.94932 | 33.84477 | 0.53125 | 11.28812 |
| December | 260.00000 | 23.57628 | 39.97701 | 0.42361 | 9.93482 |
| Annual Sum or Average | 3276.00000 | 23.91590 | 37.33456 | 0.31943 | 8.83547 |
| Minimum of Months | 247.00000 | 23.57628 | 31.29810 | -0.0474 | 5.49941 |
| Maximum of Months | 299.00000 | 24.00003 | 45.68752 | 0.61653 | 13.22206 |
Report: OccupantComfortDataSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 231.00000 | 21.03227 | 21.32987 | -0.5258 | 11.19652 |
| February | 209.00000 | 21.28146 | 24.01711 | -0.3783 | 8.84432 |
| March | 253.00000 | 21.50249 | 27.10164 | -0.2270 | 7.07732 |
| April | 220.00000 | 22.53703 | 30.08768 | 0.08098 | 6.69843 |
| May | 242.00000 | 22.98446 | 31.44083 | -0.6077 | 16.42908 |
| June | 242.00000 | 23.87636 | 37.69522 | -0.1316 | 6.34755 |
| July | 200.00000 | 23.94389 | 34.70728 | -0.1565 | 5.83797 |
| August | 230.00000 | 23.77265 | 32.68754 | -0.2739 | 7.74520 |
| September | 219.00000 | 23.58114 | 39.94939 | -0.2951 | 8.84793 |
| October | 231.00000 | 22.95132 | 31.19523 | 0.21344 | 7.50930 |
| November | 231.00000 | 21.91389 | 27.90784 | -0.1400 | 7.37348 |
| December | 220.00000 | 21.25920 | 24.25107 | -0.3915 | 9.16209 |
| Annual Sum or Average | 2728.00000 | 22.54638 | 30.18704 | -0.2372 | 8.63317 |
| Minimum of Months | 200.00000 | 21.03227 | 21.32987 | -0.6077 | 5.83797 |
| Maximum of Months | 253.00000 | 23.94389 | 39.94939 | 0.21344 | 16.42908 |
Report: OccupantComfortDataSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 21.01895 | 15.32956 | -0.6503 | 14.17159 |
| February | 247.00000 | 21.24142 | 18.03108 | -0.5241 | 11.31066 |
| March | 299.00000 | 21.80611 | 20.58236 | -0.3188 | 8.11201 |
| April | 260.00000 | 23.11415 | 23.62505 | 0.06650 | 5.99369 |
| May | 286.00000 | 23.52781 | 24.87936 | -0.6019 | 15.05545 |
| June | 286.00000 | 23.98284 | 30.99922 | -0.2183 | 6.37697 |
| July | 260.00000 | 23.95164 | 32.97393 | -0.2122 | 6.20551 |
| August | 299.00000 | 23.81479 | 30.52038 | -0.3184 | 7.86696 |
| September | 260.00000 | 23.92027 | 32.81987 | -0.3228 | 7.84459 |
| October | 273.00000 | 23.59705 | 24.12517 | 0.22870 | 6.81493 |
| November | 273.00000 | 22.16914 | 21.18255 | -0.2243 | 8.08413 |
| December | 260.00000 | 21.19585 | 18.20327 | -0.5391 | 11.64816 |
| Annual Sum or Average | 3276.00000 | 22.79456 | 24.49646 | -0.3031 | 9.12006 |
| Minimum of Months | 247.00000 | 21.01895 | 15.32956 | -0.6503 | 5.99369 |
| Maximum of Months | 299.00000 | 23.98284 | 32.97393 | 0.22870 | 15.05545 |
Report: OccupantComfortDataSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 20.87956 | 15.17763 | -0.6744 | 15.01257 |
| February | 247.00000 | 20.99941 | 18.27245 | -0.5674 | 11.94331 |
| March | 299.00000 | 21.10413 | 21.28373 | -0.4548 | 9.60051 |
| April | 260.00000 | 22.15394 | 25.20337 | -0.1256 | 6.01164 |
| May | 286.00000 | 22.95562 | 26.05388 | -0.7985 | 21.52431 |
| June | 286.00000 | 23.96087 | 31.15631 | -0.3177 | 7.42542 |
| July | 260.00000 | 23.94243 | 32.99804 | -0.2988 | 7.06995 |
| August | 299.00000 | 23.74585 | 30.64968 | -0.4150 | 9.27334 |
| September | 260.00000 | 23.63815 | 33.82181 | -0.4812 | 11.02110 |
| October | 273.00000 | 22.65801 | 26.18858 | 0.00420 | 5.95884 |
| November | 273.00000 | 21.24220 | 22.30146 | -0.4214 | 9.32773 |
| December | 260.00000 | 20.97768 | 18.38510 | -0.5854 | 12.43959 |
| Annual Sum or Average | 3276.00000 | 22.37032 | 25.18038 | -0.4289 | 10.57557 |
| Minimum of Months | 247.00000 | 20.87956 | 15.17763 | -0.7985 | 5.95884 |
| Maximum of Months | 299.00000 | 23.96087 | 33.82181 | 0.00420 | 21.52431 |
Report: OccupantComfortDataSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 273.00000 | 15.55595 | 14.45856 | -1.6734 | 52.59664 |
| February | 247.00000 | 17.90786 | 16.87348 | -1.1477 | 34.87817 |
| March | 299.00000 | 19.50154 | 19.19817 | -0.7848 | 20.92476 |
| April | 260.00000 | 20.58336 | 23.71873 | -0.4697 | 11.92234 |
| May | 286.00000 | 21.12969 | 25.97226 | -1.3283 | 42.85473 |
| June | 286.00000 | 22.90940 | 32.58279 | -0.6112 | 16.59470 |
| July | 260.00000 | 23.59231 | 33.51894 | -0.3774 | 10.70292 |
| August | 299.00000 | 23.13306 | 31.58089 | -0.5369 | 14.88380 |
| September | 260.00000 | 22.28582 | 35.30816 | -0.7886 | 22.87533 |
| October | 273.00000 | 21.29500 | 24.94234 | -0.2199 | 8.62884 |
| November | 273.00000 | 19.66210 | 20.48259 | -0.7085 | 19.18072 |
| December | 260.00000 | 17.59528 | 17.07463 | -1.2224 | 36.75718 |
| Annual Sum or Average | 3276.00000 | 20.46673 | 24.70908 | -0.8201 | 24.31689 |
| Minimum of Months | 247.00000 | 15.55595 | 14.45856 | -1.6734 | 8.62884 |
| Maximum of Months | 299.00000 | 23.59231 | 35.30816 | -0.2199 | 52.59664 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| BOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
| January | 0.169713E+12 | 0.00 | 516.37 | 575412.37 | 02-JAN-06:01 | 0.00 | 38.89 | 66.65 | 0.44 | 0.00 | 0.13 | 1.20 | 02-JAN-06:01 |
| February | 0.837596E+11 | 0.00 | 388.50 | 575412.37 | 02-FEB-06:01 | 0.00 | 36.60 | 59.91 | 0.22 | 0.00 | 0.07 | 1.20 | 02-FEB-06:01 |
| March | 0.570834E+11 | 0.00 | 400.48 | 575412.37 | 01-MAR-07:01 | 0.00 | 35.54 | 55.92 | 0.14 | 0.00 | 0.04 | 1.20 | 01-MAR-07:01 |
| April | 0.133913E+11 | 0.00 | 245.90 | 575412.37 | 03-APR-06:01 | 0.00 | 39.16 | 50.25 | 0.04 | 0.00 | 0.01 | 1.20 | 03-APR-06:01 |
| May | 0.112708E+11 | 0.00 | 209.27 | 575412.37 | 01-MAY-05:11 | 0.00 | 50.49 | 58.97 | 0.03 | 0.00 | 0.01 | 1.20 | 01-MAY-05:11 |
| June | 0.127902E+10 | 0.00 | 57.36 | 88110.17 | 16-JUN-07:01 | 0.00 | 58.75 | 60.54 | 0.01 | 0.00 | 0.00 | 0.18 | 16-JUN-07:01 |
| July | 0.655311E+09 | 0.00 | 27.96 | 240293.09 | 05-JUL-07:01 | 0.00 | 56.19 | 57.31 | 0.00 | 0.00 | 0.00 | 0.50 | 05-JUL-07:01 |
| August | 0.267998E+10 | 0.00 | 64.88 | 442874.41 | 18-AUG-07:01 | 0.00 | 48.60 | 51.78 | 0.01 | 0.00 | 0.00 | 0.92 | 18-AUG-07:01 |
| September | 0.236036E+10 | 0.00 | 96.30 | 341058.09 | 20-SEP-07:01 | 0.00 | 54.59 | 58.10 | 0.01 | 0.00 | 0.00 | 0.71 | 20-SEP-07:01 |
| October | 0.594698E+10 | 0.00 | 181.55 | 575412.37 | 10-OCT-06:01 | 0.00 | 53.77 | 60.41 | 0.02 | 0.00 | 0.00 | 1.20 | 10-OCT-06:01 |
| November | 0.401539E+11 | 0.00 | 340.02 | 575412.37 | 14-NOV-07:01 | 0.00 | 37.84 | 55.45 | 0.10 | 0.00 | 0.03 | 1.20 | 14-NOV-07:01 |
| December | 0.103549E+12 | 0.00 | 460.71 | 575412.37 | 01-DEC-08:61 | 0.00 | 36.49 | 62.06 | 0.25 | 0.00 | 0.08 | 1.20 | 01-DEC-08:61 |
| Annual Sum or Average | 0.491843E+12 | 0.00 | 2989.30 | 0.00 | 45.63 | 58.12 | 0.10 | 0.00 | 0.03 | ||||
| Minimum of Months | 0.655311E+09 | 0.00 | 27.96 | 88110.17 | 0.00 | 35.54 | 50.25 | 0.00 | 0.00 | 0.00 | 0.18 | ||
| Maximum of Months | 0.169713E+12 | 0.00 | 516.37 | 575412.37 | 0.00 | 58.75 | 66.65 | 0.44 | 0.00 | 0.13 | 1.20 |
Report: DXReportMonthly
For: VAV_POD_1 COOLING COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 0.954678E+09 | 0.288124E+09 | 5.52 | 0.954678E+09 | 0.00 | 0.00 | 0.60 | 27-FEB-15:02 | 0.00 | 01-FEB-00:05 | 106496.12 | 27-FEB-15:02 | 106496.12 | 27-FEB-15:02 | 0.00 | 27-FEB-12:25 | 30231.44 | 27-FEB-15:02 | 0.00 |
| March | 50032396.78 | 16202317.08 | 2.23 | 50032396.78 | -0.0 | 0.00 | 0.31 | 29-MAR-14:01 | 0.00 | 01-MAR-00:10 | 50862.41 | 29-MAR-14:01 | 50862.41 | 29-MAR-14:01 | 0.00 | 14-MAR-12:40 | 15564.55 | 29-MAR-14:01 | 0.00 |
| April | 0.106558E+11 | 0.314091E+10 | 52.35 | 0.106489E+11 | 6843324.58 | 0.00 | 0.83 | 07-APR-14:05 | 0.00 | 01-APR-00:10 | 156505.37 | 07-APR-14:05 | 156505.37 | 07-APR-14:05 | 2186.57 | 13-APR-14:01 | 41714.89 | 07-APR-14:05 | 0.00 |
| May | 0.415497E+11 | 0.115657E+11 | 130.50 | 0.411490E+11 | 0.400719E+09 | 0.00 | 1.00 | 19-MAY-11:20 | 0.00 | 01-MAY-00:10 | 322303.74 | 19-MAY-15:00 | 322303.74 | 19-MAY-15:00 | 30873.70 | 02-MAY-13:00 | 81773.13 | 19-MAY-15:00 | 0.00 |
| June | 0.149293E+12 | 0.399649E+11 | 304.70 | 0.145229E+12 | 0.406461E+10 | 0.00 | 1.00 | 05-JUN-12:05 | 0.00 | 01-JUN-00:03 | 374203.30 | 20-JUN-14:02 | 341742.10 | 29-JUN-15:03 | 80942.03 | 20-JUN-14:02 | 93338.21 | 20-JUN-14:02 | 0.00 |
| July | 0.201372E+12 | 0.545312E+11 | 353.33 | 0.196561E+12 | 0.481053E+10 | 0.00 | 1.00 | 02-JUL-10:48 | 0.00 | 01-JUL-00:03 | 378458.23 | 17-JUL-14:03 | 378458.23 | 17-JUL-14:03 | 99129.50 | 01-JUL-00:53 | 113723.54 | 17-JUL-16:00 | 0.00 |
| August | 0.160340E+12 | 0.435475E+11 | 316.36 | 0.159019E+12 | 0.132168E+10 | 0.00 | 1.00 | 04-AUG-11:05 | 0.00 | 01-AUG-00:03 | 342857.46 | 09-AUG-14:02 | 342857.46 | 09-AUG-14:02 | 22776.52 | 01-AUG-14:02 | 95524.60 | 09-AUG-14:02 | 0.00 |
| September | 0.926819E+11 | 0.250988E+11 | 210.28 | 0.858695E+11 | 0.681245E+10 | 0.00 | 1.00 | 01-SEP-12:40 | 0.00 | 01-SEP-00:03 | 414331.42 | 07-SEP-14:50 | 328621.20 | 27-SEP-13:10 | 198632.53 | 07-SEP-14:50 | 100358.48 | 07-SEP-14:50 | 0.00 |
| October | 0.223408E+11 | 0.627177E+10 | 82.09 | 0.223300E+11 | 10765344.02 | 0.00 | 1.00 | 18-OCT-12:00 | 0.00 | 01-OCT-00:10 | 266136.52 | 18-OCT-14:05 | 266136.52 | 18-OCT-14:05 | 1893.25 | 25-OCT-14:01 | 67562.64 | 18-OCT-14:05 | 0.00 |
| November | 0.997280E+09 | 0.316638E+09 | 16.41 | 0.992459E+09 | 4821239.98 | 0.00 | 0.35 | 07-NOV-15:01 | 0.00 | 01-NOV-00:10 | 58051.02 | 07-NOV-15:01 | 58051.02 | 07-NOV-15:01 | 2262.37 | 08-NOV-15:01 | 17587.13 | 07-NOV-15:01 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.680235E+12 | 0.184742E+12 | 1473.78 | 0.662803E+12 | 0.174324E+11 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Maximum of Months | 0.201372E+12 | 0.545312E+11 | 353.33 | 0.196561E+12 | 0.681245E+10 | 0.00 | 1.00 | 0.00 | 414331.42 | 378458.23 | 198632.53 | 113723.54 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_1:6 COOLING COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 18977774.27 | 4910634.02 | 10.60 | 15949374.42 | 3028399.85 | 0.00 | 1.00 | 03-JAN-06:01 | 0.00 | 01-JAN-00:10 | 32953.58 | 03-JAN-06:01 | 29114.80 | 24-JAN-06:01 | 6018.70 | 17-JAN-06:01 | 7572.53 | 03-JAN-06:01 | 0.00 | 01-JAN-00:10 |
| February | 0.111389E+09 | 29594095.67 | 20.09 | 0.105095E+09 | 6293931.62 | 0.00 | 1.00 | 14-FEB-06:01 | 0.00 | 01-FEB-00:05 | 32953.58 | 14-FEB-06:01 | 31474.68 | 21-FEB-06:01 | 8945.39 | 15-FEB-06:01 | 7572.53 | 14-FEB-06:01 | 0.00 | 01-FEB-00:05 |
| March | 87021805.29 | 23000966.91 | 27.22 | 72317292.69 | 14704512.59 | 0.00 | 1.00 | 02-MAR-06:01 | 0.00 | 01-MAR-00:10 | 32953.58 | 02-MAR-06:01 | 29998.28 | 13-MAR-05:01 | 7572.31 | 15-MAR-05:01 | 7572.53 | 02-MAR-06:01 | 0.00 | 01-MAR-00:10 |
| April | 0.982515E+09 | 0.251109E+09 | 95.27 | 0.940492E+09 | 42022295.07 | 0.00 | 1.00 | 03-APR-05:01 | 0.00 | 01-APR-00:10 | 32953.58 | 03-APR-05:01 | 32953.58 | 16-APR-11:02 | 12819.50 | 21-APR-05:01 | 7572.53 | 03-APR-05:01 | 0.00 | 01-APR-00:10 |
| May | 0.329264E+10 | 0.821497E+09 | 145.63 | 0.307036E+10 | 0.222284E+09 | 0.00 | 1.00 | 01-MAY-05:01 | 0.00 | 01-MAY-00:10 | 33390.76 | 20-MAY-11:08 | 32953.58 | 13-MAY-10:13 | 13602.39 | 26-MAY-05:01 | 8057.27 | 20-MAY-18:12 | 0.00 | 01-MAY-00:10 |
| June | 0.108150E+11 | 0.268012E+10 | 267.26 | 0.946592E+10 | 0.134907E+10 | 0.00 | 1.00 | 01-JUN-05:01 | 0.00 | 01-JUN-00:03 | 34925.94 | 21-JUN-20:53 | 32990.46 | 25-JUN-13:32 | 18061.00 | 13-JUN-03:32 | 8330.37 | 18-JUN-14:28 | 0.00 | 01-JUN-00:03 |
| July | 0.160925E+11 | 0.413300E+10 | 342.90 | 0.144114E+11 | 0.168104E+10 | 0.00 | 1.00 | 01-JUL-03:32 | 0.00 | 01-JUL-00:03 | 35859.65 | 18-JUL-22:52 | 35749.05 | 16-JUL-14:52 | 17631.31 | 01-JUL-03:32 | 9887.11 | 16-JUL-14:52 | 0.00 | 01-JUL-00:03 |
| August | 0.134636E+11 | 0.345350E+10 | 305.27 | 0.124520E+11 | 0.101163E+10 | 0.00 | 1.00 | 01-AUG-03:32 | 0.00 | 01-AUG-00:03 | 33757.06 | 08-AUG-22:38 | 32953.58 | 11-AUG-03:32 | 13544.50 | 14-AUG-05:32 | 9068.86 | 05-AUG-18:52 | 0.00 | 01-AUG-00:03 |
| September | 0.716134E+10 | 0.180380E+10 | 202.86 | 0.624324E+10 | 0.918109E+09 | 0.00 | 1.00 | 01-SEP-03:32 | 0.00 | 01-SEP-00:03 | 35412.10 | 06-SEP-20:53 | 34592.19 | 04-SEP-16:12 | 19557.53 | 08-SEP-03:32 | 9834.15 | 04-SEP-16:12 | 0.00 | 01-SEP-00:03 |
| October | 0.171507E+10 | 0.421994E+09 | 118.37 | 0.166801E+10 | 47064515.88 | 0.00 | 1.00 | 02-OCT-05:11 | 0.00 | 01-OCT-00:10 | 32953.58 | 23-OCT-05:52 | 32953.58 | 15-OCT-17:13 | 12201.48 | 03-OCT-05:11 | 7802.06 | 15-OCT-13:52 | 0.00 | 01-OCT-00:10 |
| November | 0.116179E+09 | 30889028.85 | 40.51 | 99567394.97 | 16611768.91 | 0.00 | 1.00 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 | 32953.58 | 20-NOV-06:01 | 32545.93 | 24-NOV-06:01 | 9782.42 | 03-NOV-05:01 | 7572.53 | 01-NOV-05:01 | 0.00 | 01-NOV-00:10 |
| December | 37893024.54 | 9900571.40 | 13.01 | 31124710.11 | 6768314.43 | 0.00 | 1.00 | 01-DEC-06:01 | 0.00 | 01-DEC-00:05 | 32953.58 | 01-DEC-06:01 | 30007.42 | 05-DEC-06:01 | 8790.48 | 06-DEC-06:01 | 7572.53 | 01-DEC-06:01 | 0.00 | 01-DEC-00:05 |
| Annual Sum or Average | 0.538941E+11 | 0.136633E+11 | 1588.99 | 0.485755E+11 | 0.531862E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 18977774.27 | 4910634.02 | 10.60 | 15949374.42 | 3028399.85 | 0.00 | 1.00 | 0.00 | 32953.58 | 29114.80 | 6018.70 | 7572.53 | 0.00 | |||||||
| Maximum of Months | 0.160925E+11 | 0.413300E+10 | 342.90 | 0.144114E+11 | 0.168104E+10 | 0.00 | 1.00 | 0.00 | 35859.65 | 35749.05 | 19557.53 | 9887.11 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:7 COOLING COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 19091236.62 | 5495889.10 | 1.83 | 19091236.62 | 0.00 | 0.00 | 0.19 | 27-FEB-15:00 | 0.00 | 01-FEB-00:05 | 4983.82 | 27-FEB-15:00 | 4983.82 | 27-FEB-15:00 | 0.00 | 27-FEB-14:40 | 1416.77 | 27-FEB-15:00 | 0.00 | 01-FEB-00:05 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.571373E+09 | 0.155166E+09 | 22.77 | 0.569061E+09 | 2311468.50 | 0.00 | 0.78 | 07-APR-14:00 | 0.00 | 01-APR-00:10 | 24094.39 | 07-APR-14:00 | 24094.39 | 07-APR-14:00 | 372.10 | 24-APR-14:00 | 6020.15 | 07-APR-14:00 | 0.00 | 01-APR-00:10 |
| May | 0.258253E+10 | 0.682669E+09 | 68.42 | 0.244200E+10 | 0.140533E+09 | 0.00 | 1.00 | 19-MAY-12:00 | 0.00 | 01-MAY-00:10 | 39672.59 | 19-MAY-14:00 | 36034.95 | 19-MAY-14:00 | 4847.22 | 19-MAY-12:20 | 10036.52 | 19-MAY-14:00 | 0.00 | 01-MAY-00:10 |
| June | 0.150821E+11 | 0.390197E+10 | 205.84 | 0.137061E+11 | 0.137604E+10 | 0.00 | 1.00 | 04-JUN-11:21 | 0.00 | 01-JUN-00:03 | 63873.44 | 24-JUN-10:23 | 60395.91 | 11-JUN-11:11 | 26227.16 | 26-JUN-05:01 | 15792.92 | 24-JUN-10:23 | 0.00 | 01-JUN-00:03 |
| July | 0.158748E+11 | 0.450953E+10 | 276.82 | 0.154583E+11 | 0.416501E+09 | 0.00 | 1.00 | 01-JUL-10:13 | 0.00 | 01-JUL-00:03 | 65358.43 | 16-JUL-09:43 | 59607.36 | 22-JUL-17:21 | 30191.38 | 19-JUL-05:02 | 15975.80 | 16-JUL-09:43 | 0.00 | 01-JUL-00:03 |
| August | 0.126157E+11 | 0.358916E+10 | 229.00 | 0.124909E+11 | 0.124743E+09 | 0.00 | 1.00 | 05-AUG-15:27 | 0.00 | 01-AUG-00:03 | 61092.43 | 07-AUG-05:42 | 61092.43 | 11-AUG-05:02 | 24402.41 | 14-AUG-05:01 | 14780.13 | 27-AUG-14:32 | 0.00 | 01-AUG-00:03 |
| September | 0.761769E+10 | 0.200141E+10 | 143.70 | 0.639375E+10 | 0.122394E+10 | 0.00 | 1.00 | 03-SEP-15:53 | 0.00 | 01-SEP-00:03 | 61593.44 | 07-SEP-05:01 | 58819.11 | 03-SEP-21:12 | 28576.61 | 07-SEP-05:01 | 15208.57 | 03-SEP-21:12 | 0.00 | 01-SEP-00:03 |
| October | 0.152701E+10 | 0.401794E+09 | 41.07 | 0.152572E+10 | 1289790.74 | 0.00 | 0.92 | 18-OCT-14:00 | 0.00 | 01-OCT-00:10 | 29542.04 | 18-OCT-14:00 | 29542.04 | 18-OCT-14:00 | 139.94 | 12-OCT-10:50 | 7321.27 | 18-OCT-14:00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 | 0.00 | 01-DEC-00:05 |
| Annual Sum or Average | 0.558903E+11 | 0.152472E+11 | 989.45 | 0.526050E+11 | 0.328536E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.158748E+11 | 0.450953E+10 | 276.82 | 0.154583E+11 | 0.137604E+10 | 0.00 | 1.00 | 0.00 | 65358.43 | 61092.43 | 30191.38 | 15975.80 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 82.85 | 33.39 | 49.46 | 34.94 | 454.91 | 0.00 | 0.00 | 0.00 |
| February | 141.42 | 69.51 | 71.90 | 97.06 | 324.78 | 0.00 | 0.00 | 0.00 |
| March | 180.98 | 66.31 | 114.67 | 129.20 | 267.38 | 0.00 | 0.00 | 0.00 |
| April | 236.27 | 104.68 | 131.59 | 222.50 | 185.13 | 0.00 | 0.00 | 0.00 |
| May | 292.25 | 133.28 | 158.97 | 304.86 | 151.91 | 0.00 | 0.00 | 0.00 |
| June | 317.95 | 146.05 | 171.91 | 381.32 | 105.85 | 0.00 | 0.00 | 0.00 |
| July | 325.71 | 164.59 | 161.12 | 438.77 | 82.80 | 0.00 | 0.00 | 0.00 |
| August | 276.57 | 135.73 | 140.84 | 357.57 | 93.62 | 0.00 | 0.00 | 0.00 |
| September | 222.48 | 112.48 | 110.00 | 249.00 | 149.88 | 0.00 | 0.00 | 0.00 |
| October | 159.01 | 79.01 | 80.01 | 136.44 | 219.06 | 0.00 | 0.00 | 0.00 |
| November | 112.57 | 55.84 | 56.72 | 74.75 | 287.15 | 0.00 | 0.00 | 0.00 |
| December | 75.67 | 31.94 | 43.73 | 32.42 | 380.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 202.25 | 94.49 | 107.76 | 205.49 | 224.91 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 75.67 | 31.94 | 43.73 | 32.42 | 82.80 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 325.71 | 164.59 | 171.91 | 438.77 | 454.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 43.22 | 30.87 | 12.35 | 38.16 | 60.53 | 0.00 | 0.00 | 0.00 |
| February | 55.04 | 39.59 | 15.45 | 55.11 | 44.22 | 0.00 | 0.00 | 0.00 |
| March | 49.20 | 27.63 | 21.57 | 48.85 | 39.25 | 0.00 | 0.00 | 0.00 |
| April | 39.55 | 18.92 | 20.63 | 41.57 | 28.79 | 0.00 | 0.00 | 0.00 |
| May | 35.14 | 11.67 | 23.47 | 36.76 | 23.98 | 0.00 | 0.00 | 0.00 |
| June | 34.91 | 10.18 | 24.73 | 42.97 | 16.98 | 0.00 | 0.00 | 0.00 |
| July | 37.64 | 13.90 | 23.74 | 53.76 | 12.77 | 0.00 | 0.00 | 0.00 |
| August | 44.73 | 22.55 | 22.18 | 61.51 | 14.59 | 0.00 | 0.00 | 0.00 |
| September | 49.61 | 30.40 | 19.21 | 61.16 | 22.57 | 0.00 | 0.00 | 0.00 |
| October | 51.87 | 35.87 | 16.00 | 57.20 | 31.51 | 0.00 | 0.00 | 0.00 |
| November | 47.29 | 34.25 | 13.03 | 46.94 | 38.56 | 0.00 | 0.00 | 0.00 |
| December | 41.10 | 29.68 | 11.42 | 37.53 | 51.03 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 44.03 | 25.36 | 18.67 | 48.41 | 32.02 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 34.91 | 10.18 | 11.42 | 36.76 | 12.77 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 55.04 | 39.59 | 24.73 | 61.51 | 60.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 299.96 | 214.24 | 85.72 | 264.85 | 420.07 | 0.00 | 0.00 | 0.00 |
| February | 382.00 | 274.75 | 107.25 | 382.48 | 306.89 | 0.00 | 0.00 | 0.00 |
| March | 341.46 | 191.75 | 149.71 | 339.05 | 272.44 | 0.00 | 0.00 | 0.00 |
| April | 274.48 | 131.28 | 143.19 | 288.49 | 199.82 | 0.00 | 0.00 | 0.00 |
| May | 243.86 | 80.99 | 162.87 | 254.87 | 166.92 | 0.00 | 0.00 | 0.00 |
| June | 242.30 | 70.67 | 171.64 | 297.40 | 118.34 | 0.00 | 0.00 | 0.00 |
| July | 261.23 | 96.50 | 164.73 | 372.39 | 88.75 | 0.00 | 0.00 | 0.00 |
| August | 310.45 | 156.52 | 153.93 | 426.77 | 101.31 | 0.00 | 0.00 | 0.00 |
| September | 344.33 | 210.98 | 133.35 | 424.47 | 156.65 | 0.00 | 0.00 | 0.00 |
| October | 359.98 | 248.92 | 111.06 | 397.01 | 218.72 | 0.00 | 0.00 | 0.00 |
| November | 328.19 | 237.73 | 90.46 | 325.81 | 267.62 | 0.00 | 0.00 | 0.00 |
| December | 285.25 | 205.98 | 79.27 | 260.49 | 354.18 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 305.60 | 176.04 | 129.56 | 335.82 | 222.36 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 242.30 | 70.67 | 79.27 | 254.87 | 88.75 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 382.00 | 274.75 | 171.64 | 426.77 | 420.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 551.19 | 393.67 | 157.52 | 483.38 | 793.86 | 0.00 | 0.00 | 0.00 |
| February | 701.94 | 504.86 | 197.08 | 696.42 | 590.23 | 0.00 | 0.00 | 0.00 |
| March | 627.44 | 352.34 | 275.10 | 615.29 | 531.80 | 0.00 | 0.00 | 0.00 |
| April | 504.36 | 241.24 | 263.12 | 520.63 | 399.06 | 0.00 | 0.00 | 0.00 |
| May | 448.11 | 148.83 | 299.28 | 464.74 | 326.77 | 0.00 | 0.00 | 0.00 |
| June | 445.24 | 129.85 | 315.39 | 545.78 | 227.60 | 0.00 | 0.00 | 0.00 |
| July | 480.01 | 177.32 | 302.70 | 691.35 | 163.00 | 0.00 | 0.00 | 0.00 |
| August | 570.46 | 287.62 | 282.85 | 788.87 | 189.26 | 0.00 | 0.00 | 0.00 |
| September | 632.71 | 387.68 | 245.03 | 780.51 | 300.54 | 0.00 | 0.00 | 0.00 |
| October | 661.47 | 457.40 | 204.07 | 724.93 | 425.77 | 0.00 | 0.00 | 0.00 |
| November | 603.06 | 436.83 | 166.23 | 591.64 | 519.56 | 0.00 | 0.00 | 0.00 |
| December | 524.15 | 378.49 | 145.66 | 473.44 | 675.60 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 561.54 | 323.48 | 238.06 | 614.13 | 427.99 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 445.24 | 129.85 | 145.66 | 464.74 | 163.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 701.94 | 504.86 | 315.39 | 788.87 | 793.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 551.19 | 393.67 | 157.52 | 483.38 | 793.86 | 0.00 | 0.00 | 0.00 |
| February | 701.94 | 504.86 | 197.08 | 696.42 | 590.23 | 0.00 | 0.00 | 0.00 |
| March | 627.44 | 352.34 | 275.10 | 615.29 | 531.80 | 0.00 | 0.00 | 0.00 |
| April | 504.36 | 241.24 | 263.12 | 520.63 | 399.06 | 0.00 | 0.00 | 0.00 |
| May | 448.11 | 148.83 | 299.28 | 464.74 | 326.77 | 0.00 | 0.00 | 0.00 |
| June | 445.24 | 129.85 | 315.39 | 545.78 | 227.60 | 0.00 | 0.00 | 0.00 |
| July | 480.01 | 177.32 | 302.70 | 691.35 | 163.00 | 0.00 | 0.00 | 0.00 |
| August | 570.46 | 287.62 | 282.85 | 788.87 | 189.26 | 0.00 | 0.00 | 0.00 |
| September | 632.71 | 387.68 | 245.03 | 780.51 | 300.54 | 0.00 | 0.00 | 0.00 |
| October | 661.47 | 457.40 | 204.07 | 724.93 | 425.77 | 0.00 | 0.00 | 0.00 |
| November | 603.06 | 436.83 | 166.23 | 591.64 | 519.56 | 0.00 | 0.00 | 0.00 |
| December | 524.15 | 378.49 | 145.66 | 473.44 | 675.60 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 561.54 | 323.48 | 238.06 | 614.13 | 427.99 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 445.24 | 129.85 | 145.66 | 464.74 | 163.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 701.94 | 504.86 | 315.39 | 788.87 | 793.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 551.18 | 393.67 | 157.52 | 483.37 | 793.84 | 0.00 | 0.00 | 0.00 |
| February | 701.92 | 504.85 | 197.07 | 696.40 | 590.21 | 0.00 | 0.00 | 0.00 |
| March | 627.43 | 352.33 | 275.09 | 615.28 | 531.79 | 0.00 | 0.00 | 0.00 |
| April | 504.35 | 241.23 | 263.11 | 520.62 | 399.05 | 0.00 | 0.00 | 0.00 |
| May | 448.10 | 148.83 | 299.27 | 464.74 | 326.76 | 0.00 | 0.00 | 0.00 |
| June | 445.23 | 129.85 | 315.38 | 545.77 | 227.60 | 0.00 | 0.00 | 0.00 |
| July | 480.00 | 177.31 | 302.69 | 691.34 | 162.99 | 0.00 | 0.00 | 0.00 |
| August | 570.45 | 287.61 | 282.84 | 788.86 | 189.25 | 0.00 | 0.00 | 0.00 |
| September | 632.70 | 387.68 | 245.02 | 780.50 | 300.53 | 0.00 | 0.00 | 0.00 |
| October | 661.45 | 457.39 | 204.07 | 724.92 | 425.76 | 0.00 | 0.00 | 0.00 |
| November | 603.05 | 436.83 | 166.22 | 591.63 | 519.55 | 0.00 | 0.00 | 0.00 |
| December | 524.14 | 378.48 | 145.66 | 473.43 | 675.58 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 561.53 | 323.47 | 238.06 | 614.12 | 427.98 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 445.23 | 129.85 | 145.66 | 464.74 | 162.99 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 701.92 | 504.85 | 315.38 | 788.86 | 793.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 27.62 | 11.13 | 16.49 | 11.63 | 160.53 | 0.00 | 0.00 | 0.00 |
| February | 47.14 | 23.17 | 23.97 | 32.73 | 115.22 | 0.00 | 0.00 | 0.00 |
| March | 60.33 | 22.10 | 38.22 | 42.87 | 96.28 | 0.00 | 0.00 | 0.00 |
| April | 78.76 | 34.89 | 43.86 | 73.45 | 68.08 | 0.00 | 0.00 | 0.00 |
| May | 97.42 | 44.43 | 52.99 | 100.86 | 55.64 | 0.00 | 0.00 | 0.00 |
| June | 105.98 | 48.68 | 57.30 | 126.08 | 38.24 | 0.00 | 0.00 | 0.00 |
| July | 108.57 | 54.86 | 53.71 | 147.06 | 27.93 | 0.00 | 0.00 | 0.00 |
| August | 92.19 | 45.25 | 46.95 | 120.69 | 31.26 | 0.00 | 0.00 | 0.00 |
| September | 74.16 | 37.49 | 36.67 | 84.39 | 51.39 | 0.00 | 0.00 | 0.00 |
| October | 53.01 | 26.34 | 26.67 | 46.55 | 75.63 | 0.00 | 0.00 | 0.00 |
| November | 37.52 | 18.61 | 18.91 | 25.62 | 100.51 | 0.00 | 0.00 | 0.00 |
| December | 25.22 | 10.65 | 14.58 | 10.86 | 134.35 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 67.42 | 31.50 | 35.92 | 68.76 | 79.46 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.22 | 10.65 | 14.58 | 10.86 | 27.93 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 108.57 | 54.86 | 57.30 | 147.06 | 160.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 82.85 | 33.39 | 49.46 | 37.70 | 447.93 | 0.00 | 0.00 | 0.00 |
| February | 141.42 | 69.51 | 71.90 | 104.45 | 313.12 | 0.00 | 0.00 | 0.00 |
| March | 180.98 | 66.31 | 114.67 | 137.04 | 256.45 | 0.00 | 0.00 | 0.00 |
| April | 236.27 | 104.68 | 131.59 | 231.51 | 175.53 | 0.00 | 0.00 | 0.00 |
| May | 292.25 | 133.28 | 158.97 | 311.07 | 146.51 | 0.00 | 0.00 | 0.00 |
| June | 317.95 | 146.05 | 171.91 | 386.02 | 102.90 | 0.00 | 0.00 | 0.00 |
| July | 325.71 | 164.59 | 161.12 | 446.96 | 77.41 | 0.00 | 0.00 | 0.00 |
| August | 276.57 | 135.73 | 140.84 | 368.73 | 85.03 | 0.00 | 0.00 | 0.00 |
| September | 222.48 | 112.48 | 110.00 | 259.87 | 137.17 | 0.00 | 0.00 | 0.00 |
| October | 159.01 | 79.01 | 80.01 | 146.46 | 200.97 | 0.00 | 0.00 | 0.00 |
| November | 112.57 | 55.84 | 56.72 | 81.70 | 270.81 | 0.00 | 0.00 | 0.00 |
| December | 75.67 | 31.94 | 43.73 | 35.74 | 371.74 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 202.25 | 94.49 | 107.76 | 212.86 | 215.14 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 75.67 | 31.94 | 43.73 | 35.74 | 77.41 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 325.71 | 164.59 | 171.91 | 446.96 | 447.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.89 | 0.00 | 4.89 | 0.03 | 71.82 | 0.00 | 0.00 | 0.00 |
| February | 6.75 | 0.00 | 6.75 | 0.65 | 52.28 | 0.00 | 0.00 | 0.00 |
| March | 11.33 | 0.00 | 11.33 | 1.69 | 41.11 | 0.00 | 0.00 | 0.00 |
| April | 12.80 | 0.08 | 12.72 | 4.80 | 27.60 | 0.00 | 0.00 | 0.00 |
| May | 16.88 | 1.09 | 15.79 | 9.73 | 21.98 | 0.00 | 0.00 | 0.00 |
| June | 19.26 | 2.43 | 16.83 | 18.12 | 14.35 | 0.00 | 0.00 | 0.00 |
| July | 17.47 | 1.67 | 15.80 | 23.00 | 10.67 | 0.00 | 0.00 | 0.00 |
| August | 14.05 | 0.41 | 13.64 | 16.47 | 12.05 | 0.00 | 0.00 | 0.00 |
| September | 10.49 | 0.00 | 10.49 | 7.81 | 21.00 | 0.00 | 0.00 | 0.00 |
| October | 7.70 | 0.00 | 7.70 | 1.71 | 31.89 | 0.00 | 0.00 | 0.00 |
| November | 5.20 | 0.00 | 5.20 | 0.26 | 44.40 | 0.00 | 0.00 | 0.00 |
| December | 4.00 | 0.00 | 4.00 | 0.01 | 60.28 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 10.92 | 0.48 | 10.45 | 7.07 | 34.05 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4.00 | 0.00 | 4.00 | 0.01 | 10.67 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 19.26 | 2.43 | 16.83 | 23.00 | 71.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 35.93 | 0.00 | 35.93 | 0.26 | 497.09 | 0.00 | 0.00 | 0.00 |
| February | 49.96 | 0.00 | 49.96 | 5.60 | 360.79 | 0.00 | 0.00 | 0.00 |
| March | 83.04 | 0.00 | 83.04 | 14.61 | 283.57 | 0.00 | 0.00 | 0.00 |
| April | 94.03 | 0.53 | 93.50 | 37.93 | 191.00 | 0.00 | 0.00 | 0.00 |
| May | 123.57 | 7.54 | 116.03 | 74.23 | 152.12 | 0.00 | 0.00 | 0.00 |
| June | 141.31 | 16.90 | 124.41 | 134.92 | 100.17 | 0.00 | 0.00 | 0.00 |
| July | 128.33 | 11.59 | 116.74 | 168.21 | 75.15 | 0.00 | 0.00 | 0.00 |
| August | 103.64 | 2.86 | 100.79 | 121.51 | 84.50 | 0.00 | 0.00 | 0.00 |
| September | 77.59 | 0.02 | 77.57 | 59.37 | 145.93 | 0.00 | 0.00 | 0.00 |
| October | 56.83 | 0.00 | 56.83 | 14.05 | 220.16 | 0.00 | 0.00 | 0.00 |
| November | 38.48 | 0.00 | 38.48 | 2.31 | 306.69 | 0.00 | 0.00 | 0.00 |
| December | 29.59 | 0.00 | 29.59 | 0.10 | 417.27 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 80.36 | 3.30 | 77.06 | 53.08 | 235.73 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 29.59 | 0.00 | 29.59 | 0.10 | 75.15 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 141.31 | 16.90 | 124.41 | 168.21 | 497.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 59.11 | 0.00 | 59.11 | 0.12 | 937.29 | 0.00 | 0.00 | 0.00 |
| February | 81.74 | 0.00 | 81.74 | 5.84 | 691.25 | 0.00 | 0.00 | 0.00 |
| March | 137.30 | 0.00 | 137.30 | 14.82 | 555.80 | 0.00 | 0.00 | 0.00 |
| April | 153.92 | 0.32 | 153.60 | 49.05 | 388.16 | 0.00 | 0.00 | 0.00 |
| May | 198.92 | 8.90 | 190.02 | 108.87 | 309.54 | 0.00 | 0.00 | 0.00 |
| June | 218.54 | 19.24 | 199.29 | 201.34 | 199.72 | 0.00 | 0.00 | 0.00 |
| July | 203.29 | 13.53 | 189.77 | 278.01 | 134.80 | 0.00 | 0.00 | 0.00 |
| August | 166.43 | 2.48 | 163.95 | 206.55 | 157.20 | 0.00 | 0.00 | 0.00 |
| September | 127.18 | 0.03 | 127.15 | 95.75 | 277.10 | 0.00 | 0.00 | 0.00 |
| October | 93.19 | 0.00 | 93.19 | 17.90 | 430.70 | 0.00 | 0.00 | 0.00 |
| November | 62.88 | 0.00 | 62.88 | 1.70 | 593.41 | 0.00 | 0.00 | 0.00 |
| December | 48.20 | 0.00 | 48.20 | 0.08 | 793.26 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 129.49 | 3.73 | 125.76 | 82.23 | 454.75 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 48.20 | 0.00 | 48.20 | 0.08 | 134.80 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 218.54 | 19.24 | 199.29 | 278.01 | 937.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 62.33 | 0.00 | 62.33 | 0.19 | 937.02 | 0.00 | 0.00 | 0.00 |
| February | 86.17 | 0.00 | 86.17 | 6.64 | 690.23 | 0.00 | 0.00 | 0.00 |
| March | 144.50 | 0.00 | 144.50 | 17.93 | 552.89 | 0.00 | 0.00 | 0.00 |
| April | 162.78 | 0.72 | 162.06 | 54.38 | 384.85 | 0.00 | 0.00 | 0.00 |
| May | 213.16 | 12.25 | 200.91 | 119.53 | 302.10 | 0.00 | 0.00 | 0.00 |
| June | 239.29 | 26.71 | 212.58 | 224.65 | 195.07 | 0.00 | 0.00 | 0.00 |
| July | 222.70 | 21.24 | 201.46 | 303.02 | 134.16 | 0.00 | 0.00 | 0.00 |
| August | 177.78 | 4.34 | 173.44 | 216.48 | 154.39 | 0.00 | 0.00 | 0.00 |
| September | 133.80 | 0.03 | 133.77 | 101.24 | 277.59 | 0.00 | 0.00 | 0.00 |
| October | 98.19 | 0.00 | 98.19 | 19.96 | 430.39 | 0.00 | 0.00 | 0.00 |
| November | 66.38 | 0.00 | 66.38 | 2.33 | 593.78 | 0.00 | 0.00 | 0.00 |
| December | 50.99 | 0.00 | 50.99 | 0.12 | 793.79 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 138.46 | 5.47 | 132.99 | 89.47 | 452.91 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 50.99 | 0.00 | 50.99 | 0.12 | 134.16 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 239.29 | 26.71 | 212.58 | 303.02 | 937.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 62.35 | 0.00 | 62.35 | 0.19 | 936.99 | 0.00 | 0.00 | 0.00 |
| February | 86.20 | 0.00 | 86.20 | 6.64 | 690.21 | 0.00 | 0.00 | 0.00 |
| March | 144.54 | 0.00 | 144.54 | 17.95 | 552.87 | 0.00 | 0.00 | 0.00 |
| April | 163.32 | 0.95 | 162.37 | 54.45 | 383.96 | 0.00 | 0.00 | 0.00 |
| May | 214.40 | 13.12 | 201.28 | 119.96 | 300.56 | 0.00 | 0.00 | 0.00 |
| June | 240.95 | 27.77 | 213.18 | 225.73 | 193.68 | 0.00 | 0.00 | 0.00 |
| July | 222.96 | 21.35 | 201.60 | 303.38 | 134.12 | 0.00 | 0.00 | 0.00 |
| August | 179.19 | 5.17 | 174.03 | 218.07 | 153.63 | 0.00 | 0.00 | 0.00 |
| September | 133.89 | 0.04 | 133.85 | 101.28 | 277.49 | 0.00 | 0.00 | 0.00 |
| October | 98.22 | 0.00 | 98.22 | 19.98 | 430.38 | 0.00 | 0.00 | 0.00 |
| November | 66.40 | 0.00 | 66.40 | 2.33 | 593.77 | 0.00 | 0.00 | 0.00 |
| December | 51.01 | 0.00 | 51.01 | 0.12 | 793.77 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 138.91 | 5.73 | 133.18 | 89.78 | 452.51 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.01 | 0.00 | 51.01 | 0.12 | 134.12 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 240.95 | 27.77 | 213.18 | 303.38 | 936.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 82.85 | 33.39 | 49.46 | 35.20 | 454.29 | 0.00 | 0.00 | 0.00 |
| February | 141.42 | 69.51 | 71.90 | 97.31 | 324.50 | 0.00 | 0.00 | 0.00 |
| March | 180.98 | 66.31 | 114.67 | 129.55 | 267.04 | 0.00 | 0.00 | 0.00 |
| April | 236.27 | 104.68 | 131.59 | 223.00 | 184.76 | 0.00 | 0.00 | 0.00 |
| May | 292.25 | 133.28 | 158.97 | 305.56 | 151.34 | 0.00 | 0.00 | 0.00 |
| June | 317.95 | 146.05 | 171.91 | 382.15 | 105.35 | 0.00 | 0.00 | 0.00 |
| July | 325.71 | 164.59 | 161.12 | 439.70 | 82.23 | 0.00 | 0.00 | 0.00 |
| August | 276.57 | 135.73 | 140.84 | 358.32 | 93.12 | 0.00 | 0.00 | 0.00 |
| September | 222.48 | 112.48 | 110.00 | 249.41 | 149.54 | 0.00 | 0.00 | 0.00 |
| October | 159.01 | 79.01 | 80.01 | 136.74 | 218.68 | 0.00 | 0.00 | 0.00 |
| November | 112.57 | 55.84 | 56.72 | 75.10 | 286.27 | 0.00 | 0.00 | 0.00 |
| December | 75.67 | 31.94 | 43.73 | 32.86 | 379.30 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 202.25 | 94.49 | 107.76 | 206.00 | 224.36 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 75.67 | 31.94 | 43.73 | 32.86 | 82.23 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 325.71 | 164.59 | 171.91 | 439.70 | 454.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.70 | 29.39 | 11.31 | 36.40 | 61.36 | 0.00 | 0.00 | 0.00 |
| February | 53.47 | 39.28 | 14.19 | 53.83 | 44.29 | 0.00 | 0.00 | 0.00 |
| March | 47.56 | 27.62 | 19.94 | 47.17 | 38.98 | 0.00 | 0.00 | 0.00 |
| April | 37.66 | 18.92 | 18.74 | 39.71 | 28.61 | 0.00 | 0.00 | 0.00 |
| May | 32.79 | 11.67 | 21.12 | 34.35 | 23.94 | 0.00 | 0.00 | 0.00 |
| June | 32.14 | 10.18 | 21.96 | 39.90 | 16.83 | 0.00 | 0.00 | 0.00 |
| July | 35.06 | 13.90 | 21.16 | 50.91 | 12.38 | 0.00 | 0.00 | 0.00 |
| August | 42.50 | 22.55 | 19.95 | 59.08 | 14.20 | 0.00 | 0.00 | 0.00 |
| September | 47.87 | 30.40 | 17.47 | 59.26 | 22.21 | 0.00 | 0.00 | 0.00 |
| October | 50.38 | 35.68 | 14.70 | 55.76 | 31.22 | 0.00 | 0.00 | 0.00 |
| November | 45.40 | 33.51 | 11.89 | 45.64 | 38.89 | 0.00 | 0.00 | 0.00 |
| December | 37.94 | 27.79 | 10.15 | 35.23 | 52.04 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 41.87 | 24.98 | 16.90 | 46.38 | 32.04 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 32.14 | 10.18 | 10.15 | 34.35 | 12.38 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 53.47 | 39.28 | 21.96 | 59.26 | 61.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 278.98 | 203.16 | 75.82 | 249.11 | 424.59 | 0.00 | 0.00 | 0.00 |
| February | 367.31 | 272.64 | 94.67 | 369.65 | 306.04 | 0.00 | 0.00 | 0.00 |
| March | 324.62 | 191.66 | 132.96 | 321.58 | 269.76 | 0.00 | 0.00 | 0.00 |
| April | 254.95 | 131.28 | 123.66 | 269.10 | 198.26 | 0.00 | 0.00 | 0.00 |
| May | 219.67 | 80.99 | 138.68 | 229.83 | 167.01 | 0.00 | 0.00 | 0.00 |
| June | 213.67 | 70.67 | 143.00 | 265.55 | 117.23 | 0.00 | 0.00 | 0.00 |
| July | 234.61 | 96.50 | 138.11 | 342.60 | 85.09 | 0.00 | 0.00 | 0.00 |
| August | 287.40 | 156.52 | 130.88 | 401.37 | 97.70 | 0.00 | 0.00 | 0.00 |
| September | 326.35 | 210.97 | 115.38 | 404.69 | 153.10 | 0.00 | 0.00 | 0.00 |
| October | 345.44 | 247.62 | 97.82 | 382.47 | 215.13 | 0.00 | 0.00 | 0.00 |
| November | 311.83 | 232.33 | 79.50 | 313.60 | 268.38 | 0.00 | 0.00 | 0.00 |
| December | 256.77 | 189.57 | 67.21 | 237.23 | 360.27 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 284.55 | 172.98 | 111.57 | 315.15 | 221.60 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 213.67 | 70.67 | 67.21 | 229.83 | 85.09 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 367.31 | 272.64 | 143.00 | 404.69 | 424.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 495.64 | 361.27 | 134.37 | 443.18 | 812.07 | 0.00 | 0.00 | 0.00 |
| February | 670.20 | 499.74 | 170.45 | 668.99 | 589.05 | 0.00 | 0.00 | 0.00 |
| March | 592.14 | 352.05 | 240.10 | 579.14 | 526.89 | 0.00 | 0.00 | 0.00 |
| April | 463.58 | 241.24 | 222.35 | 480.30 | 397.34 | 0.00 | 0.00 | 0.00 |
| May | 397.59 | 148.83 | 248.77 | 412.43 | 328.40 | 0.00 | 0.00 | 0.00 |
| June | 385.45 | 129.85 | 255.60 | 479.72 | 226.40 | 0.00 | 0.00 | 0.00 |
| July | 424.42 | 177.32 | 247.11 | 629.95 | 155.22 | 0.00 | 0.00 | 0.00 |
| August | 522.34 | 287.62 | 234.72 | 736.44 | 181.47 | 0.00 | 0.00 | 0.00 |
| September | 595.18 | 387.66 | 207.52 | 739.60 | 292.99 | 0.00 | 0.00 | 0.00 |
| October | 630.34 | 454.20 | 176.14 | 694.43 | 418.52 | 0.00 | 0.00 | 0.00 |
| November | 559.14 | 418.47 | 140.66 | 559.93 | 527.65 | 0.00 | 0.00 | 0.00 |
| December | 447.02 | 331.12 | 115.91 | 416.20 | 703.34 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 514.14 | 314.50 | 199.64 | 569.27 | 429.39 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 385.45 | 129.85 | 115.91 | 412.43 | 155.22 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 670.20 | 499.74 | 255.60 | 739.60 | 812.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 495.01 | 360.79 | 134.22 | 443.17 | 812.95 | 0.00 | 0.00 | 0.00 |
| February | 667.21 | 497.72 | 169.49 | 668.11 | 592.94 | 0.00 | 0.00 | 0.00 |
| March | 591.67 | 351.78 | 239.89 | 579.02 | 527.57 | 0.00 | 0.00 | 0.00 |
| April | 463.53 | 241.24 | 222.29 | 480.25 | 397.34 | 0.00 | 0.00 | 0.00 |
| May | 397.53 | 148.83 | 248.70 | 412.36 | 328.40 | 0.00 | 0.00 | 0.00 |
| June | 385.38 | 129.85 | 255.52 | 479.63 | 226.40 | 0.00 | 0.00 | 0.00 |
| July | 424.35 | 177.32 | 247.04 | 629.87 | 155.21 | 0.00 | 0.00 | 0.00 |
| August | 522.28 | 287.62 | 234.66 | 736.37 | 181.46 | 0.00 | 0.00 | 0.00 |
| September | 595.06 | 387.63 | 207.43 | 739.53 | 293.09 | 0.00 | 0.00 | 0.00 |
| October | 629.31 | 453.60 | 175.70 | 694.25 | 420.04 | 0.00 | 0.00 | 0.00 |
| November | 556.52 | 416.53 | 139.99 | 559.60 | 531.23 | 0.00 | 0.00 | 0.00 |
| December | 446.82 | 330.98 | 115.84 | 416.18 | 703.60 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 513.46 | 314.06 | 199.40 | 569.11 | 430.28 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 385.38 | 129.85 | 115.84 | 412.36 | 155.21 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 667.21 | 497.72 | 255.52 | 739.53 | 812.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 458.52 | 332.62 | 125.90 | 400.20 | 816.49 | 0.00 | 0.00 | 0.00 |
| February | 619.17 | 461.38 | 157.80 | 611.71 | 600.66 | 0.00 | 0.00 | 0.00 |
| March | 559.99 | 332.96 | 227.02 | 541.54 | 532.86 | 0.00 | 0.00 | 0.00 |
| April | 444.61 | 232.50 | 212.11 | 456.79 | 398.36 | 0.00 | 0.00 | 0.00 |
| May | 383.14 | 145.46 | 237.68 | 395.43 | 329.32 | 0.00 | 0.00 | 0.00 |
| June | 371.41 | 127.04 | 244.37 | 462.55 | 226.36 | 0.00 | 0.00 | 0.00 |
| July | 409.79 | 173.11 | 236.68 | 610.63 | 153.67 | 0.00 | 0.00 | 0.00 |
| August | 502.66 | 278.37 | 224.30 | 709.24 | 180.15 | 0.00 | 0.00 | 0.00 |
| September | 567.48 | 370.82 | 196.67 | 703.10 | 294.21 | 0.00 | 0.00 | 0.00 |
| October | 586.74 | 422.52 | 164.22 | 642.15 | 425.59 | 0.00 | 0.00 | 0.00 |
| November | 517.66 | 386.96 | 130.69 | 512.57 | 534.22 | 0.00 | 0.00 | 0.00 |
| December | 415.99 | 307.52 | 108.47 | 379.15 | 704.89 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 485.46 | 296.46 | 189.00 | 534.81 | 432.45 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 371.41 | 127.04 | 108.47 | 379.15 | 153.67 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 619.17 | 461.38 | 244.37 | 709.24 | 816.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 27.62 | 11.13 | 16.49 | 11.66 | 160.35 | 0.00 | 0.00 | 0.00 |
| February | 47.14 | 23.17 | 23.97 | 32.76 | 115.15 | 0.00 | 0.00 | 0.00 |
| March | 60.33 | 22.10 | 38.22 | 42.90 | 96.22 | 0.00 | 0.00 | 0.00 |
| April | 78.76 | 34.89 | 43.86 | 73.48 | 68.06 | 0.00 | 0.00 | 0.00 |
| May | 97.42 | 44.43 | 52.99 | 100.91 | 55.59 | 0.00 | 0.00 | 0.00 |
| June | 105.98 | 48.68 | 57.30 | 126.14 | 38.18 | 0.00 | 0.00 | 0.00 |
| July | 108.57 | 54.86 | 53.71 | 147.20 | 27.81 | 0.00 | 0.00 | 0.00 |
| August | 92.19 | 45.25 | 46.95 | 120.81 | 31.13 | 0.00 | 0.00 | 0.00 |
| September | 74.16 | 37.49 | 36.67 | 84.45 | 51.31 | 0.00 | 0.00 | 0.00 |
| October | 53.01 | 26.34 | 26.67 | 46.61 | 75.51 | 0.00 | 0.00 | 0.00 |
| November | 37.52 | 18.61 | 18.91 | 25.69 | 100.21 | 0.00 | 0.00 | 0.00 |
| December | 25.22 | 10.65 | 14.58 | 10.91 | 134.04 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 67.42 | 31.50 | 35.92 | 68.83 | 79.33 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.22 | 10.65 | 14.58 | 10.91 | 27.81 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 108.57 | 54.86 | 57.30 | 147.20 | 160.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 82.85 | 33.39 | 49.46 | 37.71 | 447.87 | 0.00 | 0.00 | 0.00 |
| February | 141.42 | 69.51 | 71.90 | 104.45 | 313.08 | 0.00 | 0.00 | 0.00 |
| March | 180.98 | 66.31 | 114.67 | 137.03 | 256.43 | 0.00 | 0.00 | 0.00 |
| April | 236.27 | 104.68 | 131.59 | 231.47 | 175.54 | 0.00 | 0.00 | 0.00 |
| May | 292.25 | 133.28 | 158.97 | 311.01 | 146.54 | 0.00 | 0.00 | 0.00 |
| June | 317.95 | 146.05 | 171.91 | 385.94 | 102.93 | 0.00 | 0.00 | 0.00 |
| July | 325.71 | 164.59 | 161.12 | 446.91 | 77.38 | 0.00 | 0.00 | 0.00 |
| August | 276.57 | 135.73 | 140.84 | 368.71 | 84.99 | 0.00 | 0.00 | 0.00 |
| September | 222.48 | 112.48 | 110.00 | 259.86 | 137.15 | 0.00 | 0.00 | 0.00 |
| October | 159.01 | 79.01 | 80.01 | 146.46 | 200.91 | 0.00 | 0.00 | 0.00 |
| November | 112.57 | 55.84 | 56.72 | 81.74 | 270.63 | 0.00 | 0.00 | 0.00 |
| December | 75.67 | 31.94 | 43.73 | 35.75 | 371.61 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 202.25 | 94.49 | 107.76 | 212.84 | 215.10 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 75.67 | 31.94 | 43.73 | 35.75 | 77.38 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 325.71 | 164.59 | 171.91 | 446.91 | 447.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.99 | 0.00 | 4.99 | 0.03 | 71.78 | 0.00 | 0.00 | 0.00 |
| February | 6.91 | 0.00 | 6.91 | 0.70 | 52.22 | 0.00 | 0.00 | 0.00 |
| March | 11.55 | 0.00 | 11.55 | 1.82 | 41.03 | 0.00 | 0.00 | 0.00 |
| April | 13.07 | 0.08 | 12.99 | 5.01 | 27.56 | 0.00 | 0.00 | 0.00 |
| May | 17.23 | 1.11 | 16.12 | 10.06 | 21.93 | 0.00 | 0.00 | 0.00 |
| June | 19.72 | 2.49 | 17.24 | 18.62 | 14.33 | 0.00 | 0.00 | 0.00 |
| July | 17.90 | 1.73 | 16.17 | 23.49 | 10.68 | 0.00 | 0.00 | 0.00 |
| August | 14.37 | 0.42 | 13.95 | 16.82 | 12.07 | 0.00 | 0.00 | 0.00 |
| September | 10.73 | 0.00 | 10.73 | 8.04 | 21.01 | 0.00 | 0.00 | 0.00 |
| October | 7.87 | 0.00 | 7.87 | 1.80 | 31.85 | 0.00 | 0.00 | 0.00 |
| November | 5.32 | 0.00 | 5.32 | 0.28 | 44.35 | 0.00 | 0.00 | 0.00 |
| December | 4.09 | 0.00 | 4.09 | 0.01 | 60.25 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 11.17 | 0.49 | 10.68 | 7.27 | 34.02 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4.09 | 0.00 | 4.09 | 0.01 | 10.68 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 19.72 | 2.49 | 17.24 | 23.49 | 71.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 36.40 | 0.00 | 36.40 | 0.28 | 496.91 | 0.00 | 0.00 | 0.00 |
| February | 50.67 | 0.00 | 50.67 | 5.81 | 360.51 | 0.00 | 0.00 | 0.00 |
| March | 84.07 | 0.00 | 84.07 | 15.26 | 283.29 | 0.00 | 0.00 | 0.00 |
| April | 95.27 | 0.55 | 94.72 | 38.95 | 190.84 | 0.00 | 0.00 | 0.00 |
| May | 125.26 | 7.69 | 117.57 | 75.84 | 151.88 | 0.00 | 0.00 | 0.00 |
| June | 143.61 | 17.26 | 126.35 | 137.34 | 99.94 | 0.00 | 0.00 | 0.00 |
| July | 130.51 | 11.99 | 118.52 | 170.60 | 75.06 | 0.00 | 0.00 | 0.00 |
| August | 105.18 | 2.92 | 102.26 | 123.19 | 84.55 | 0.00 | 0.00 | 0.00 |
| September | 78.70 | 0.02 | 78.68 | 60.45 | 145.99 | 0.00 | 0.00 | 0.00 |
| October | 57.62 | 0.00 | 57.62 | 14.51 | 220.04 | 0.00 | 0.00 | 0.00 |
| November | 39.03 | 0.00 | 39.03 | 2.45 | 306.42 | 0.00 | 0.00 | 0.00 |
| December | 30.02 | 0.00 | 30.02 | 0.11 | 417.08 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 81.53 | 3.39 | 78.14 | 54.06 | 235.57 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 30.02 | 0.00 | 30.02 | 0.11 | 75.06 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 143.61 | 17.26 | 126.35 | 170.60 | 496.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 59.85 | 0.00 | 59.85 | 0.13 | 936.94 | 0.00 | 0.00 | 0.00 |
| February | 82.86 | 0.00 | 82.86 | 6.09 | 690.72 | 0.00 | 0.00 | 0.00 |
| March | 138.91 | 0.00 | 138.91 | 15.57 | 555.10 | 0.00 | 0.00 | 0.00 |
| April | 155.80 | 0.32 | 155.48 | 50.43 | 387.87 | 0.00 | 0.00 | 0.00 |
| May | 201.51 | 9.07 | 192.44 | 111.10 | 309.03 | 0.00 | 0.00 | 0.00 |
| June | 222.01 | 19.72 | 202.29 | 205.12 | 199.64 | 0.00 | 0.00 | 0.00 |
| July | 205.89 | 13.54 | 192.35 | 281.02 | 135.13 | 0.00 | 0.00 | 0.00 |
| August | 168.81 | 2.57 | 166.24 | 209.24 | 157.35 | 0.00 | 0.00 | 0.00 |
| September | 128.91 | 0.03 | 128.88 | 97.34 | 277.08 | 0.00 | 0.00 | 0.00 |
| October | 94.43 | 0.00 | 94.43 | 18.45 | 430.30 | 0.00 | 0.00 | 0.00 |
| November | 63.74 | 0.00 | 63.74 | 1.85 | 592.79 | 0.00 | 0.00 | 0.00 |
| December | 48.87 | 0.00 | 48.87 | 0.09 | 792.86 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 131.23 | 3.79 | 127.44 | 83.61 | 454.46 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 48.87 | 0.00 | 48.87 | 0.09 | 135.13 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 222.01 | 19.72 | 202.29 | 281.02 | 936.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 63.37 | 0.00 | 63.37 | 0.22 | 936.60 | 0.00 | 0.00 | 0.00 |
| February | 87.75 | 0.00 | 87.75 | 7.03 | 689.55 | 0.00 | 0.00 | 0.00 |
| March | 146.78 | 0.00 | 146.78 | 19.11 | 552.03 | 0.00 | 0.00 | 0.00 |
| April | 165.55 | 0.74 | 164.81 | 56.45 | 384.36 | 0.00 | 0.00 | 0.00 |
| May | 216.99 | 12.62 | 204.37 | 122.96 | 301.29 | 0.00 | 0.00 | 0.00 |
| June | 244.86 | 27.82 | 217.04 | 230.50 | 194.34 | 0.00 | 0.00 | 0.00 |
| July | 227.28 | 21.94 | 205.34 | 308.09 | 134.02 | 0.00 | 0.00 | 0.00 |
| August | 181.15 | 4.46 | 176.69 | 220.26 | 154.61 | 0.00 | 0.00 | 0.00 |
| September | 136.25 | 0.03 | 136.22 | 103.56 | 277.63 | 0.00 | 0.00 | 0.00 |
| October | 99.95 | 0.00 | 99.95 | 20.79 | 429.94 | 0.00 | 0.00 | 0.00 |
| November | 67.60 | 0.00 | 67.60 | 2.57 | 593.14 | 0.00 | 0.00 | 0.00 |
| December | 51.95 | 0.00 | 51.95 | 0.13 | 793.37 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 141.09 | 5.66 | 135.42 | 91.58 | 452.46 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.95 | 0.00 | 51.95 | 0.13 | 134.02 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 244.86 | 27.82 | 217.04 | 308.09 | 936.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 63.37 | 0.00 | 63.37 | 0.22 | 936.58 | 0.00 | 0.00 | 0.00 |
| February | 87.75 | 0.00 | 87.75 | 7.03 | 689.54 | 0.00 | 0.00 | 0.00 |
| March | 146.78 | 0.00 | 146.78 | 19.11 | 552.02 | 0.00 | 0.00 | 0.00 |
| April | 165.96 | 0.97 | 165.00 | 56.46 | 383.56 | 0.00 | 0.00 | 0.00 |
| May | 218.37 | 13.66 | 204.72 | 123.55 | 299.65 | 0.00 | 0.00 | 0.00 |
| June | 246.78 | 29.11 | 217.67 | 231.75 | 192.70 | 0.00 | 0.00 | 0.00 |
| July | 227.55 | 22.12 | 205.44 | 308.48 | 133.95 | 0.00 | 0.00 | 0.00 |
| August | 182.62 | 5.37 | 177.25 | 221.90 | 153.74 | 0.00 | 0.00 | 0.00 |
| September | 136.30 | 0.04 | 136.26 | 103.56 | 277.53 | 0.00 | 0.00 | 0.00 |
| October | 99.94 | 0.00 | 99.94 | 20.79 | 429.94 | 0.00 | 0.00 | 0.00 |
| November | 67.60 | 0.00 | 67.60 | 2.57 | 593.13 | 0.00 | 0.00 | 0.00 |
| December | 51.95 | 0.00 | 51.95 | 0.13 | 793.35 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 141.55 | 5.97 | 135.58 | 91.91 | 452.03 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 51.95 | 0.00 | 51.95 | 0.13 | 133.95 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 246.78 | 29.11 | 217.67 | 308.48 | 936.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 82.85 | 33.39 | 49.46 | 35.09 | 454.63 | 0.00 | 0.00 | 0.00 |
| February | 141.42 | 69.51 | 71.90 | 97.24 | 324.67 | 0.00 | 0.00 | 0.00 |
| March | 180.98 | 66.31 | 114.67 | 129.41 | 267.35 | 0.00 | 0.00 | 0.00 |
| April | 236.27 | 104.68 | 131.59 | 222.63 | 185.44 | 0.00 | 0.00 | 0.00 |
| May | 292.25 | 133.28 | 158.97 | 305.11 | 152.04 | 0.00 | 0.00 | 0.00 |
| June | 317.95 | 146.05 | 171.91 | 381.75 | 105.77 | 0.00 | 0.00 | 0.00 |
| July | 325.71 | 164.59 | 161.12 | 439.13 | 82.80 | 0.00 | 0.00 | 0.00 |
| August | 276.57 | 135.73 | 140.84 | 357.83 | 93.72 | 0.00 | 0.00 | 0.00 |
| September | 222.48 | 112.48 | 110.00 | 249.06 | 150.27 | 0.00 | 0.00 | 0.00 |
| October | 159.01 | 79.01 | 80.01 | 136.47 | 219.59 | 0.00 | 0.00 | 0.00 |
| November | 112.57 | 55.84 | 56.72 | 74.88 | 287.19 | 0.00 | 0.00 | 0.00 |
| December | 75.67 | 31.94 | 43.73 | 32.70 | 379.86 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 202.25 | 94.49 | 107.76 | 205.70 | 224.93 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 75.67 | 31.94 | 43.73 | 32.70 | 82.80 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 325.71 | 164.59 | 171.91 | 439.13 | 454.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 41.19 | 29.76 | 11.43 | 36.82 | 61.23 | 0.00 | 0.00 | 0.00 |
| February | 53.64 | 39.36 | 14.29 | 53.95 | 44.25 | 0.00 | 0.00 | 0.00 |
| March | 47.67 | 27.62 | 20.05 | 47.26 | 39.04 | 0.00 | 0.00 | 0.00 |
| April | 37.78 | 18.92 | 18.86 | 39.77 | 28.73 | 0.00 | 0.00 | 0.00 |
| May | 32.94 | 11.67 | 21.27 | 34.44 | 24.05 | 0.00 | 0.00 | 0.00 |
| June | 32.31 | 10.18 | 22.13 | 40.04 | 16.90 | 0.00 | 0.00 | 0.00 |
| July | 35.22 | 13.90 | 21.32 | 51.01 | 12.48 | 0.00 | 0.00 | 0.00 |
| August | 42.64 | 22.55 | 20.09 | 59.17 | 14.32 | 0.00 | 0.00 | 0.00 |
| September | 47.98 | 30.40 | 17.58 | 59.33 | 22.34 | 0.00 | 0.00 | 0.00 |
| October | 50.50 | 35.72 | 14.79 | 55.83 | 31.34 | 0.00 | 0.00 | 0.00 |
| November | 45.69 | 33.68 | 12.00 | 45.83 | 38.90 | 0.00 | 0.00 | 0.00 |
| December | 38.63 | 28.31 | 10.32 | 35.87 | 51.89 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 42.10 | 25.08 | 17.03 | 46.56 | 32.08 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 32.31 | 10.18 | 10.32 | 34.44 | 12.48 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 53.64 | 39.36 | 22.13 | 59.33 | 61.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 283.51 | 206.46 | 77.06 | 253.44 | 423.68 | 0.00 | 0.00 | 0.00 |
| February | 368.91 | 273.15 | 95.76 | 370.95 | 305.92 | 0.00 | 0.00 | 0.00 |
| March | 325.95 | 191.68 | 134.27 | 322.82 | 270.24 | 0.00 | 0.00 | 0.00 |
| April | 256.46 | 131.28 | 125.18 | 270.27 | 199.09 | 0.00 | 0.00 | 0.00 |
| May | 221.55 | 80.99 | 140.56 | 231.38 | 167.73 | 0.00 | 0.00 | 0.00 |
| June | 215.89 | 70.67 | 145.23 | 267.68 | 117.73 | 0.00 | 0.00 | 0.00 |
| July | 236.67 | 96.50 | 140.18 | 344.38 | 85.94 | 0.00 | 0.00 | 0.00 |
| August | 289.19 | 156.52 | 132.67 | 402.89 | 98.60 | 0.00 | 0.00 | 0.00 |
| September | 327.74 | 210.97 | 116.77 | 405.86 | 154.09 | 0.00 | 0.00 | 0.00 |
| October | 346.74 | 247.88 | 98.87 | 383.43 | 216.19 | 0.00 | 0.00 | 0.00 |
| November | 314.38 | 233.71 | 80.67 | 315.43 | 268.48 | 0.00 | 0.00 | 0.00 |
| December | 264.80 | 195.50 | 69.29 | 245.58 | 358.90 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 287.08 | 173.94 | 113.14 | 317.44 | 221.94 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 215.89 | 70.67 | 69.29 | 231.38 | 85.94 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 368.91 | 273.15 | 145.23 | 405.86 | 423.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 507.36 | 370.10 | 137.26 | 452.92 | 807.70 | 0.00 | 0.00 | 0.00 |
| February | 674.10 | 501.40 | 172.70 | 672.05 | 588.07 | 0.00 | 0.00 | 0.00 |
| March | 594.57 | 352.18 | 242.39 | 581.20 | 528.02 | 0.00 | 0.00 | 0.00 |
| April | 466.23 | 241.25 | 224.98 | 481.98 | 399.51 | 0.00 | 0.00 | 0.00 |
| May | 400.87 | 148.84 | 252.03 | 414.70 | 330.41 | 0.00 | 0.00 | 0.00 |
| June | 389.32 | 129.86 | 259.46 | 482.98 | 227.75 | 0.00 | 0.00 | 0.00 |
| July | 428.03 | 177.33 | 250.70 | 632.30 | 157.31 | 0.00 | 0.00 | 0.00 |
| August | 525.47 | 287.64 | 237.83 | 738.49 | 183.70 | 0.00 | 0.00 | 0.00 |
| September | 597.63 | 387.69 | 209.94 | 741.18 | 295.61 | 0.00 | 0.00 | 0.00 |
| October | 633.10 | 455.00 | 178.09 | 696.12 | 421.35 | 0.00 | 0.00 | 0.00 |
| November | 567.27 | 423.69 | 143.58 | 565.45 | 526.54 | 0.00 | 0.00 | 0.00 |
| December | 463.97 | 343.83 | 120.14 | 431.55 | 698.18 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 519.57 | 316.98 | 202.59 | 573.51 | 429.79 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 389.32 | 129.86 | 120.14 | 414.70 | 157.31 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 674.10 | 501.40 | 259.46 | 741.18 | 807.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 505.96 | 368.99 | 136.98 | 452.89 | 809.65 | 0.00 | 0.00 | 0.00 |
| February | 670.88 | 499.21 | 171.68 | 670.96 | 592.10 | 0.00 | 0.00 | 0.00 |
| March | 594.08 | 351.87 | 242.20 | 581.08 | 528.69 | 0.00 | 0.00 | 0.00 |
| April | 466.20 | 241.24 | 224.97 | 481.95 | 399.49 | 0.00 | 0.00 | 0.00 |
| May | 400.84 | 148.83 | 252.01 | 414.68 | 330.39 | 0.00 | 0.00 | 0.00 |
| June | 389.30 | 129.85 | 259.44 | 482.95 | 227.74 | 0.00 | 0.00 | 0.00 |
| July | 428.00 | 177.32 | 250.68 | 632.26 | 157.30 | 0.00 | 0.00 | 0.00 |
| August | 525.43 | 287.62 | 237.81 | 738.45 | 183.69 | 0.00 | 0.00 | 0.00 |
| September | 597.54 | 387.64 | 209.90 | 741.13 | 295.68 | 0.00 | 0.00 | 0.00 |
| October | 632.05 | 454.37 | 177.68 | 695.92 | 422.83 | 0.00 | 0.00 | 0.00 |
| November | 563.88 | 421.16 | 142.72 | 564.85 | 531.01 | 0.00 | 0.00 | 0.00 |
| December | 463.22 | 343.29 | 119.94 | 431.52 | 699.16 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 518.71 | 316.37 | 202.34 | 573.32 | 430.90 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 389.30 | 129.85 | 119.94 | 414.68 | 157.30 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 670.88 | 499.21 | 259.44 | 741.13 | 809.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 466.04 | 338.19 | 127.85 | 406.17 | 813.85 | 0.00 | 0.00 | 0.00 |
| February | 621.28 | 462.06 | 159.21 | 613.36 | 600.58 | 0.00 | 0.00 | 0.00 |
| March | 561.64 | 333.01 | 228.63 | 542.81 | 533.88 | 0.00 | 0.00 | 0.00 |
| April | 446.47 | 232.49 | 213.98 | 457.68 | 400.45 | 0.00 | 0.00 | 0.00 |
| May | 385.45 | 145.45 | 240.00 | 396.70 | 331.33 | 0.00 | 0.00 | 0.00 |
| June | 374.15 | 127.04 | 247.11 | 464.54 | 227.69 | 0.00 | 0.00 | 0.00 |
| July | 412.34 | 173.10 | 239.24 | 611.75 | 155.62 | 0.00 | 0.00 | 0.00 |
| August | 504.86 | 278.35 | 226.51 | 710.22 | 182.26 | 0.00 | 0.00 | 0.00 |
| September | 569.21 | 370.81 | 198.40 | 703.84 | 296.65 | 0.00 | 0.00 | 0.00 |
| October | 588.58 | 422.95 | 165.62 | 642.84 | 428.30 | 0.00 | 0.00 | 0.00 |
| November | 522.46 | 389.91 | 132.55 | 515.36 | 534.80 | 0.00 | 0.00 | 0.00 |
| December | 428.49 | 316.94 | 111.55 | 389.94 | 700.96 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 489.13 | 298.06 | 191.07 | 537.34 | 433.25 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 374.15 | 127.04 | 111.55 | 389.94 | 155.62 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 621.28 | 462.06 | 247.11 | 710.22 | 813.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 27.62 | 11.13 | 16.49 | 11.64 | 160.52 | 0.00 | 0.00 | 0.00 |
| February | 47.14 | 23.17 | 23.97 | 32.70 | 115.36 | 0.00 | 0.00 | 0.00 |
| March | 60.33 | 22.10 | 38.22 | 42.74 | 96.66 | 0.00 | 0.00 | 0.00 |
| April | 78.76 | 34.89 | 43.86 | 73.06 | 68.88 | 0.00 | 0.00 | 0.00 |
| May | 97.42 | 44.43 | 52.99 | 100.40 | 56.40 | 0.00 | 0.00 | 0.00 |
| June | 105.98 | 48.68 | 57.30 | 125.70 | 38.72 | 0.00 | 0.00 | 0.00 |
| July | 108.57 | 54.86 | 53.71 | 146.55 | 28.46 | 0.00 | 0.00 | 0.00 |
| August | 92.19 | 45.25 | 46.95 | 120.21 | 31.83 | 0.00 | 0.00 | 0.00 |
| September | 74.16 | 37.49 | 36.67 | 84.01 | 52.19 | 0.00 | 0.00 | 0.00 |
| October | 53.01 | 26.34 | 26.67 | 46.30 | 76.53 | 0.00 | 0.00 | 0.00 |
| November | 37.52 | 18.61 | 18.91 | 25.50 | 101.05 | 0.00 | 0.00 | 0.00 |
| December | 25.22 | 10.65 | 14.58 | 10.87 | 134.32 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 67.42 | 31.50 | 35.92 | 68.50 | 79.95 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 25.22 | 10.65 | 14.58 | 10.87 | 28.46 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 108.57 | 54.86 | 57.30 | 146.55 | 160.52 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 6.13 | 0.00 | 6.13 | 0.10 | 71.56 | 0.00 | 0.00 | 0.00 |
| February | 8.66 | 0.00 | 8.66 | 1.23 | 51.69 | 0.00 | 0.00 | 0.00 |
| March | 14.06 | 0.00 | 14.06 | 3.49 | 40.56 | 0.00 | 0.00 | 0.00 |
| April | 16.04 | 0.09 | 15.94 | 7.56 | 27.55 | 0.00 | 0.00 | 0.00 |
| May | 21.06 | 1.25 | 19.81 | 13.80 | 21.78 | 0.00 | 0.00 | 0.00 |
| June | 24.52 | 2.82 | 21.70 | 23.76 | 14.29 | 0.00 | 0.00 | 0.00 |
| July | 22.40 | 2.10 | 20.30 | 28.30 | 11.03 | 0.00 | 0.00 | 0.00 |
| August | 17.95 | 0.48 | 17.47 | 20.62 | 12.61 | 0.00 | 0.00 | 0.00 |
| September | 13.44 | 0.00 | 13.44 | 10.67 | 21.41 | 0.00 | 0.00 | 0.00 |
| October | 9.81 | 0.00 | 9.81 | 2.95 | 31.94 | 0.00 | 0.00 | 0.00 |
| November | 6.67 | 0.00 | 6.67 | 0.61 | 44.36 | 0.00 | 0.00 | 0.00 |
| December | 5.14 | 0.00 | 5.14 | 0.03 | 60.19 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 13.85 | 0.56 | 13.29 | 9.48 | 34.02 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 5.14 | 0.00 | 5.14 | 0.03 | 11.03 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 24.52 | 2.82 | 21.70 | 28.30 | 71.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 82.85 | 33.39 | 49.46 | 37.68 | 447.87 | 0.00 | 0.00 | 0.00 |
| February | 141.42 | 69.51 | 71.90 | 104.33 | 313.17 | 0.00 | 0.00 | 0.00 |
| March | 180.98 | 66.31 | 114.67 | 136.69 | 256.82 | 0.00 | 0.00 | 0.00 |
| April | 236.27 | 104.68 | 131.59 | 230.70 | 176.44 | 0.00 | 0.00 | 0.00 |
| May | 292.25 | 133.28 | 158.97 | 309.86 | 147.73 | 0.00 | 0.00 | 0.00 |
| June | 317.95 | 146.05 | 171.91 | 384.58 | 103.83 | 0.00 | 0.00 | 0.00 |
| July | 325.71 | 164.59 | 161.12 | 445.26 | 78.40 | 0.00 | 0.00 | 0.00 |
| August | 276.57 | 135.73 | 140.84 | 367.48 | 85.96 | 0.00 | 0.00 | 0.00 |
| September | 222.48 | 112.48 | 110.00 | 259.09 | 138.09 | 0.00 | 0.00 | 0.00 |
| October | 159.01 | 79.01 | 80.01 | 145.99 | 201.78 | 0.00 | 0.00 | 0.00 |
| November | 112.57 | 55.84 | 56.72 | 81.53 | 271.09 | 0.00 | 0.00 | 0.00 |
| December | 75.67 | 31.94 | 43.73 | 35.71 | 371.64 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 202.25 | 94.49 | 107.76 | 212.15 | 215.75 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 75.67 | 31.94 | 43.73 | 35.71 | 78.40 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 325.71 | 164.59 | 171.91 | 445.26 | 447.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 42.39 | 0.00 | 42.39 | 0.73 | 493.84 | 0.00 | 0.00 | 0.00 |
| February | 59.85 | 0.00 | 59.85 | 8.79 | 356.47 | 0.00 | 0.00 | 0.00 |
| March | 97.22 | 0.00 | 97.22 | 24.40 | 280.08 | 0.00 | 0.00 | 0.00 |
| April | 110.85 | 0.65 | 110.20 | 52.57 | 190.41 | 0.00 | 0.00 | 0.00 |
| May | 145.57 | 8.63 | 136.94 | 95.54 | 150.58 | 0.00 | 0.00 | 0.00 |
| June | 169.51 | 19.48 | 150.02 | 164.31 | 98.77 | 0.00 | 0.00 | 0.00 |
| July | 154.85 | 14.50 | 140.35 | 195.78 | 76.27 | 0.00 | 0.00 | 0.00 |
| August | 124.09 | 3.33 | 120.76 | 142.87 | 87.15 | 0.00 | 0.00 | 0.00 |
| September | 92.93 | 0.03 | 92.90 | 74.31 | 147.92 | 0.00 | 0.00 | 0.00 |
| October | 67.79 | 0.00 | 67.79 | 20.87 | 220.18 | 0.00 | 0.00 | 0.00 |
| November | 46.08 | 0.00 | 46.08 | 4.34 | 305.51 | 0.00 | 0.00 | 0.00 |
| December | 35.54 | 0.00 | 35.54 | 0.20 | 415.10 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 95.75 | 3.90 | 91.84 | 65.77 | 234.74 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 35.54 | 0.00 | 35.54 | 0.20 | 76.27 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 169.51 | 19.48 | 150.02 | 195.78 | 493.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.64 | 0.00 | 51.64 | 0.58 | 616.37 | 0.00 | 0.00 | 0.00 |
| February | 72.91 | 0.00 | 72.91 | 8.82 | 450.43 | 0.00 | 0.00 | 0.00 |
| March | 118.44 | 0.00 | 118.44 | 25.97 | 359.91 | 0.00 | 0.00 | 0.00 |
| April | 135.05 | 0.79 | 134.26 | 57.95 | 252.33 | 0.00 | 0.00 | 0.00 |
| May | 177.35 | 10.51 | 166.84 | 112.78 | 196.27 | 0.00 | 0.00 | 0.00 |
| June | 206.51 | 23.74 | 182.77 | 198.22 | 125.96 | 0.00 | 0.00 | 0.00 |
| July | 188.66 | 17.67 | 170.99 | 243.66 | 91.78 | 0.00 | 0.00 | 0.00 |
| August | 151.17 | 4.05 | 147.12 | 178.23 | 106.39 | 0.00 | 0.00 | 0.00 |
| September | 113.22 | 0.04 | 113.18 | 90.22 | 186.91 | 0.00 | 0.00 | 0.00 |
| October | 82.59 | 0.00 | 82.59 | 22.70 | 284.50 | 0.00 | 0.00 | 0.00 |
| November | 56.14 | 0.00 | 56.14 | 4.13 | 391.84 | 0.00 | 0.00 | 0.00 |
| December | 43.30 | 0.00 | 43.30 | 0.19 | 523.22 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.65 | 4.76 | 111.89 | 79.10 | 298.23 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 43.30 | 0.00 | 43.30 | 0.19 | 91.78 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 206.51 | 23.74 | 182.77 | 243.66 | 616.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.64 | 0.00 | 51.64 | 0.58 | 616.37 | 0.00 | 0.00 | 0.00 |
| February | 72.91 | 0.00 | 72.91 | 8.82 | 450.43 | 0.00 | 0.00 | 0.00 |
| March | 118.44 | 0.00 | 118.44 | 25.97 | 359.91 | 0.00 | 0.00 | 0.00 |
| April | 135.05 | 0.79 | 134.26 | 57.95 | 252.33 | 0.00 | 0.00 | 0.00 |
| May | 177.35 | 10.51 | 166.84 | 112.78 | 196.27 | 0.00 | 0.00 | 0.00 |
| June | 206.51 | 23.74 | 182.77 | 198.22 | 125.96 | 0.00 | 0.00 | 0.00 |
| July | 188.66 | 17.67 | 170.99 | 243.65 | 91.78 | 0.00 | 0.00 | 0.00 |
| August | 151.17 | 4.05 | 147.12 | 178.23 | 106.39 | 0.00 | 0.00 | 0.00 |
| September | 113.22 | 0.04 | 113.18 | 90.22 | 186.91 | 0.00 | 0.00 | 0.00 |
| October | 82.59 | 0.00 | 82.59 | 22.70 | 284.50 | 0.00 | 0.00 | 0.00 |
| November | 56.14 | 0.00 | 56.14 | 4.13 | 391.84 | 0.00 | 0.00 | 0.00 |
| December | 43.30 | 0.00 | 43.30 | 0.19 | 523.22 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.65 | 4.76 | 111.89 | 79.09 | 298.23 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 43.30 | 0.00 | 43.30 | 0.19 | 91.78 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 206.51 | 23.74 | 182.77 | 243.65 | 616.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 51.64 | 0.00 | 51.64 | 0.58 | 616.34 | 0.00 | 0.00 | 0.00 |
| February | 72.91 | 0.00 | 72.91 | 8.82 | 450.42 | 0.00 | 0.00 | 0.00 |
| March | 118.44 | 0.00 | 118.44 | 25.97 | 359.90 | 0.00 | 0.00 | 0.00 |
| April | 135.04 | 0.79 | 134.25 | 57.95 | 252.32 | 0.00 | 0.00 | 0.00 |
| May | 177.34 | 10.51 | 166.83 | 112.77 | 196.26 | 0.00 | 0.00 | 0.00 |
| June | 206.50 | 23.74 | 182.77 | 198.22 | 125.96 | 0.00 | 0.00 | 0.00 |
| July | 188.65 | 17.67 | 170.98 | 243.65 | 91.78 | 0.00 | 0.00 | 0.00 |
| August | 151.17 | 4.05 | 147.12 | 178.22 | 106.39 | 0.00 | 0.00 | 0.00 |
| September | 113.21 | 0.04 | 113.17 | 90.21 | 186.90 | 0.00 | 0.00 | 0.00 |
| October | 82.58 | 0.00 | 82.58 | 22.70 | 284.49 | 0.00 | 0.00 | 0.00 |
| November | 56.14 | 0.00 | 56.14 | 4.13 | 391.82 | 0.00 | 0.00 | 0.00 |
| December | 43.30 | 0.00 | 43.30 | 0.19 | 523.20 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 116.64 | 4.76 | 111.89 | 79.09 | 298.22 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 43.30 | 0.00 | 43.30 | 0.19 | 91.78 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 206.50 | 23.74 | 182.77 | 243.65 | 616.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 5.82 | 0.00 | 5.82 | 0.05 | 70.25 | 0.00 | 0.00 | 0.00 |
| February | 8.22 | 0.00 | 8.22 | 0.88 | 51.86 | 0.00 | 0.00 | 0.00 |
| March | 13.36 | 0.00 | 13.36 | 2.60 | 42.14 | 0.00 | 0.00 | 0.00 |
| April | 15.23 | 0.09 | 15.14 | 5.85 | 30.54 | 0.00 | 0.00 | 0.00 |
| May | 20.00 | 1.19 | 18.81 | 11.90 | 23.67 | 0.00 | 0.00 | 0.00 |
| June | 23.29 | 2.68 | 20.61 | 21.61 | 15.12 | 0.00 | 0.00 | 0.00 |
| July | 21.27 | 1.99 | 19.28 | 26.20 | 11.29 | 0.00 | 0.00 | 0.00 |
| August | 17.05 | 0.46 | 16.59 | 18.89 | 13.22 | 0.00 | 0.00 | 0.00 |
| September | 12.77 | 0.00 | 12.76 | 9.51 | 22.95 | 0.00 | 0.00 | 0.00 |
| October | 9.31 | 0.00 | 9.31 | 2.25 | 34.28 | 0.00 | 0.00 | 0.00 |
| November | 6.33 | 0.00 | 6.33 | 0.34 | 46.21 | 0.00 | 0.00 | 0.00 |
| December | 4.88 | 0.00 | 4.88 | 0.02 | 60.12 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 13.15 | 0.54 | 12.62 | 8.39 | 35.07 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 4.88 | 0.00 | 4.88 | 0.02 | 11.29 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 23.29 | 2.68 | 20.61 | 26.20 | 70.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 73.85 | 0.00 | 73.85 | 0.65 | 890.93 | 0.00 | 0.00 | 0.00 |
| February | 104.27 | 0.00 | 104.27 | 11.19 | 657.62 | 0.00 | 0.00 | 0.00 |
| March | 169.38 | 0.00 | 169.38 | 32.95 | 534.42 | 0.00 | 0.00 | 0.00 |
| April | 193.12 | 1.13 | 192.00 | 74.24 | 387.26 | 0.00 | 0.00 | 0.00 |
| May | 253.62 | 15.03 | 238.59 | 150.92 | 300.19 | 0.00 | 0.00 | 0.00 |
| June | 295.32 | 33.94 | 261.38 | 274.04 | 191.77 | 0.00 | 0.00 | 0.00 |
| July | 269.79 | 25.27 | 244.53 | 332.28 | 143.16 | 0.00 | 0.00 | 0.00 |
| August | 216.19 | 5.79 | 210.39 | 239.55 | 167.62 | 0.00 | 0.00 | 0.00 |
| September | 161.91 | 0.06 | 161.85 | 120.59 | 291.07 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 0.00 | 118.10 | 28.48 | 434.75 | 0.00 | 0.00 | 0.00 |
| November | 80.29 | 0.00 | 80.29 | 4.35 | 586.06 | 0.00 | 0.00 | 0.00 |
| December | 61.92 | 0.00 | 61.92 | 0.21 | 762.43 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 166.81 | 6.80 | 160.01 | 106.43 | 444.76 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 61.92 | 0.00 | 61.92 | 0.21 | 143.16 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 295.32 | 33.94 | 261.38 | 332.28 | 890.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 8.76 | 3.40 | 5.36 | 3.31 | 75.18 | 0.00 | 0.00 | 0.00 |
| February | 18.05 | 9.80 | 8.24 | 13.37 | 54.17 | 0.00 | 0.00 | 0.00 |
| March | 24.00 | 10.40 | 13.60 | 17.75 | 45.84 | 0.00 | 0.00 | 0.00 |
| April | 30.66 | 15.45 | 15.21 | 28.83 | 33.93 | 0.00 | 0.00 | 0.00 |
| May | 32.32 | 14.78 | 17.55 | 32.20 | 28.88 | 0.00 | 0.00 | 0.00 |
| June | 34.99 | 15.75 | 19.24 | 41.27 | 19.98 | 0.00 | 0.00 | 0.00 |
| July | 38.32 | 19.79 | 18.53 | 52.21 | 13.93 | 0.00 | 0.00 | 0.00 |
| August | 34.86 | 18.41 | 16.45 | 46.19 | 15.48 | 0.00 | 0.00 | 0.00 |
| September | 30.47 | 17.37 | 13.10 | 35.65 | 24.60 | 0.00 | 0.00 | 0.00 |
| October | 21.31 | 11.98 | 9.33 | 19.98 | 34.71 | 0.00 | 0.00 | 0.00 |
| November | 13.00 | 6.82 | 6.18 | 9.31 | 46.31 | 0.00 | 0.00 | 0.00 |
| December | 6.93 | 2.55 | 4.38 | 2.34 | 63.49 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 24.50 | 12.21 | 12.29 | 25.26 | 37.98 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 6.93 | 2.55 | 4.38 | 2.34 | 13.93 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 38.32 | 19.79 | 19.24 | 52.21 | 75.18 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 28.34 | 2.11 | 26.23 | 0.21 | 413.01 | 0.00 | 0.00 | 0.00 |
| February | 54.99 | 15.87 | 39.12 | 17.76 | 296.97 | 0.00 | 0.00 | 0.00 |
| March | 103.74 | 32.88 | 70.86 | 57.03 | 243.27 | 0.00 | 0.00 | 0.00 |
| April | 160.95 | 74.66 | 86.28 | 142.59 | 176.82 | 0.00 | 0.00 | 0.00 |
| May | 206.38 | 100.70 | 105.69 | 209.46 | 148.15 | 0.00 | 0.00 | 0.00 |
| June | 223.10 | 110.16 | 112.94 | 263.78 | 103.80 | 0.00 | 0.00 | 0.00 |
| July | 238.14 | 129.97 | 108.17 | 320.45 | 74.78 | 0.00 | 0.00 | 0.00 |
| August | 190.84 | 98.33 | 92.51 | 247.46 | 82.52 | 0.00 | 0.00 | 0.00 |
| September | 140.12 | 70.21 | 69.90 | 153.82 | 130.50 | 0.00 | 0.00 | 0.00 |
| October | 73.59 | 27.68 | 45.91 | 48.69 | 187.44 | 0.00 | 0.00 | 0.00 |
| November | 35.29 | 6.44 | 28.85 | 5.14 | 255.40 | 0.00 | 0.00 | 0.00 |
| December | 22.03 | 0.79 | 21.24 | 0.01 | 351.48 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 123.50 | 56.04 | 67.46 | 122.85 | 205.02 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 22.03 | 0.79 | 21.24 | 0.01 | 74.78 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 238.14 | 129.97 | 112.94 | 320.45 | 413.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.88 | 29.19 | 11.68 | 37.87 | 52.63 | 0.00 | 0.00 | 0.00 |
| February | 52.06 | 37.44 | 14.62 | 54.01 | 39.39 | 0.00 | 0.00 | 0.00 |
| March | 46.53 | 26.13 | 20.40 | 47.55 | 35.68 | 0.00 | 0.00 | 0.00 |
| April | 37.40 | 17.89 | 19.51 | 40.18 | 26.67 | 0.00 | 0.00 | 0.00 |
| May | 33.23 | 11.04 | 22.19 | 35.95 | 22.05 | 0.00 | 0.00 | 0.00 |
| June | 33.02 | 9.63 | 23.39 | 41.04 | 16.16 | 0.00 | 0.00 | 0.00 |
| July | 35.60 | 13.15 | 22.45 | 50.27 | 12.72 | 0.00 | 0.00 | 0.00 |
| August | 42.31 | 21.33 | 20.98 | 58.15 | 14.10 | 0.00 | 0.00 | 0.00 |
| September | 46.92 | 28.75 | 18.17 | 58.58 | 20.86 | 0.00 | 0.00 | 0.00 |
| October | 49.05 | 33.92 | 15.13 | 55.59 | 28.45 | 0.00 | 0.00 | 0.00 |
| November | 44.72 | 32.40 | 12.33 | 46.01 | 34.59 | 0.00 | 0.00 | 0.00 |
| December | 38.87 | 28.07 | 10.80 | 36.73 | 45.13 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 41.64 | 23.99 | 17.65 | 46.77 | 29.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 33.02 | 9.63 | 10.80 | 35.95 | 12.72 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 52.06 | 37.44 | 23.39 | 58.58 | 52.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 551.91 | 394.19 | 157.73 | 511.34 | 710.54 | 0.00 | 0.00 | 0.00 |
| February | 702.85 | 505.52 | 197.34 | 729.23 | 531.85 | 0.00 | 0.00 | 0.00 |
| March | 628.26 | 352.80 | 275.46 | 642.06 | 481.70 | 0.00 | 0.00 | 0.00 |
| April | 505.02 | 241.55 | 263.46 | 542.56 | 360.14 | 0.00 | 0.00 | 0.00 |
| May | 448.69 | 149.02 | 299.67 | 485.35 | 297.76 | 0.00 | 0.00 | 0.00 |
| June | 445.82 | 130.02 | 315.80 | 554.14 | 218.25 | 0.00 | 0.00 | 0.00 |
| July | 480.64 | 177.55 | 303.09 | 678.80 | 171.77 | 0.00 | 0.00 | 0.00 |
| August | 571.21 | 287.99 | 283.22 | 785.10 | 190.42 | 0.00 | 0.00 | 0.00 |
| September | 633.54 | 388.19 | 245.35 | 790.91 | 281.63 | 0.00 | 0.00 | 0.00 |
| October | 662.33 | 458.00 | 204.34 | 750.61 | 384.07 | 0.00 | 0.00 | 0.00 |
| November | 603.85 | 437.41 | 166.45 | 621.22 | 467.09 | 0.00 | 0.00 | 0.00 |
| December | 524.84 | 378.99 | 145.85 | 495.87 | 609.38 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 562.28 | 323.90 | 238.38 | 631.52 | 391.56 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 445.82 | 130.02 | 145.85 | 485.35 | 171.77 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 702.85 | 505.52 | 315.80 | 790.91 | 710.54 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: BATH_ZN_1_FLR_1_WALL_5_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 47.72 | 10.35 | 37.37 | 5.79 | 495.05 | 0.00 | 0.00 | 0.00 |
| February | 94.49 | 38.44 | 56.05 | 51.38 | 353.41 | 0.00 | 0.00 | 0.00 |
| March | 152.36 | 54.29 | 98.07 | 98.35 | 301.63 | 0.00 | 0.00 | 0.00 |
| April | 219.70 | 103.67 | 116.02 | 199.20 | 229.00 | 0.00 | 0.00 | 0.00 |
| May | 270.31 | 130.10 | 140.21 | 271.50 | 195.08 | 0.00 | 0.00 | 0.00 |
| June | 291.79 | 141.50 | 150.29 | 334.19 | 144.28 | 0.00 | 0.00 | 0.00 |
| July | 312.30 | 168.44 | 143.85 | 411.25 | 106.48 | 0.00 | 0.00 | 0.00 |
| August | 257.56 | 133.34 | 124.22 | 328.70 | 114.67 | 0.00 | 0.00 | 0.00 |
| September | 199.42 | 103.95 | 95.47 | 219.08 | 177.50 | 0.00 | 0.00 | 0.00 |
| October | 118.83 | 53.97 | 64.86 | 91.95 | 245.42 | 0.00 | 0.00 | 0.00 |
| November | 64.49 | 22.75 | 41.74 | 26.09 | 315.68 | 0.00 | 0.00 | 0.00 |
| December | 37.45 | 7.06 | 30.39 | 2.79 | 421.50 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 172.60 | 80.87 | 91.74 | 170.73 | 257.98 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 37.45 | 7.06 | 30.39 | 2.79 | 106.48 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 312.30 | 168.44 | 150.29 | 411.25 | 495.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 213.43 | 97.85 | 115.58 | 93.88 | 1023.20 | 0.00 | 0.00 | 0.00 |
| February | 333.82 | 165.74 | 168.09 | 229.85 | 755.02 | 0.00 | 0.00 | 0.00 |
| March | 448.86 | 185.72 | 263.13 | 330.34 | 622.13 | 0.00 | 0.00 | 0.00 |
| April | 572.70 | 283.82 | 288.87 | 525.78 | 458.92 | 0.00 | 0.00 | 0.00 |
| May | 632.62 | 281.47 | 351.14 | 621.60 | 377.12 | 0.00 | 0.00 | 0.00 |
| June | 818.84 | 421.37 | 397.47 | 958.85 | 254.26 | 0.00 | 0.00 | 0.00 |
| July | 859.40 | 485.84 | 373.56 | 1115.90 | 200.04 | 0.00 | 0.00 | 0.00 |
| August | 746.85 | 416.12 | 330.73 | 939.80 | 227.30 | 0.00 | 0.00 | 0.00 |
| September | 528.33 | 272.72 | 255.61 | 571.82 | 352.69 | 0.00 | 0.00 | 0.00 |
| October | 379.05 | 192.47 | 186.57 | 316.87 | 505.46 | 0.00 | 0.00 | 0.00 |
| November | 240.23 | 112.16 | 128.08 | 138.67 | 661.52 | 0.00 | 0.00 | 0.00 |
| December | 177.18 | 76.10 | 101.08 | 70.78 | 871.63 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 496.79 | 249.71 | 247.08 | 494.39 | 524.92 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 177.18 | 76.10 | 101.08 | 70.78 | 200.04 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 859.40 | 485.84 | 397.47 | 1115.90 | 1023.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 40.59 | 28.99 | 11.60 | 35.98 | 57.61 | 0.00 | 0.00 | 0.00 |
| February | 51.69 | 37.18 | 14.51 | 51.88 | 42.43 | 0.00 | 0.00 | 0.00 |
| March | 46.20 | 25.94 | 20.26 | 45.57 | 38.58 | 0.00 | 0.00 | 0.00 |
| April | 37.14 | 17.76 | 19.37 | 38.04 | 29.92 | 0.00 | 0.00 | 0.00 |
| May | 33.00 | 10.96 | 22.04 | 33.53 | 25.09 | 0.00 | 0.00 | 0.00 |
| June | 32.79 | 9.56 | 23.22 | 38.88 | 18.10 | 0.00 | 0.00 | 0.00 |
| July | 35.35 | 13.06 | 22.29 | 48.72 | 13.83 | 0.00 | 0.00 | 0.00 |
| August | 42.01 | 21.18 | 20.83 | 56.58 | 15.45 | 0.00 | 0.00 | 0.00 |
| September | 46.59 | 28.55 | 18.04 | 56.88 | 22.94 | 0.00 | 0.00 | 0.00 |
| October | 48.71 | 33.68 | 15.03 | 53.61 | 30.84 | 0.00 | 0.00 | 0.00 |
| November | 44.41 | 32.17 | 12.24 | 44.18 | 37.11 | 0.00 | 0.00 | 0.00 |
| December | 38.60 | 27.87 | 10.73 | 35.37 | 48.71 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 41.35 | 23.82 | 17.53 | 44.88 | 31.68 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 32.79 | 9.56 | 10.73 | 33.53 | 13.83 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 51.69 | 37.18 | 23.22 | 56.88 | 57.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 614.59 | 438.95 | 175.64 | 544.83 | 872.35 | 0.00 | 0.00 | 0.00 |
| February | 782.67 | 562.93 | 219.74 | 785.53 | 642.51 | 0.00 | 0.00 | 0.00 |
| March | 699.60 | 392.87 | 306.74 | 690.11 | 584.21 | 0.00 | 0.00 | 0.00 |
| April | 562.36 | 268.98 | 293.38 | 576.00 | 453.00 | 0.00 | 0.00 | 0.00 |
| May | 499.65 | 165.95 | 333.70 | 507.78 | 379.63 | 0.00 | 0.00 | 0.00 |
| June | 496.45 | 144.79 | 351.66 | 588.79 | 273.40 | 0.00 | 0.00 | 0.00 |
| July | 535.22 | 197.71 | 337.51 | 737.74 | 208.69 | 0.00 | 0.00 | 0.00 |
| August | 636.08 | 320.70 | 315.38 | 856.70 | 233.71 | 0.00 | 0.00 | 0.00 |
| September | 705.49 | 432.27 | 273.21 | 861.29 | 347.29 | 0.00 | 0.00 | 0.00 |
| October | 737.55 | 510.00 | 227.54 | 811.85 | 466.92 | 0.00 | 0.00 | 0.00 |
| November | 672.42 | 487.08 | 185.35 | 668.94 | 561.89 | 0.00 | 0.00 | 0.00 |
| December | 584.44 | 422.02 | 162.42 | 535.54 | 737.53 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 626.13 | 360.68 | 265.45 | 679.64 | 479.54 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 496.45 | 144.79 | 162.42 | 507.78 | 208.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 782.67 | 562.93 | 351.66 | 861.29 | 872.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 24.31 | 9.32 | 14.99 | 8.50 | 111.46 | 0.00 | 0.00 | 0.00 |
| February | 41.12 | 22.06 | 19.06 | 29.87 | 84.25 | 0.00 | 0.00 | 0.00 |
| March | 67.86 | 31.57 | 36.29 | 61.53 | 72.82 | 0.00 | 0.00 | 0.00 |
| April | 87.24 | 49.35 | 37.89 | 89.31 | 56.41 | 0.00 | 0.00 | 0.00 |
| May | 111.26 | 63.87 | 47.40 | 124.66 | 45.91 | 0.00 | 0.00 | 0.00 |
| June | 133.91 | 86.34 | 47.57 | 164.97 | 33.68 | 0.00 | 0.00 | 0.00 |
| July | 138.87 | 97.56 | 41.31 | 181.15 | 29.59 | 0.00 | 0.00 | 0.00 |
| August | 113.81 | 77.36 | 36.44 | 145.49 | 31.99 | 0.00 | 0.00 | 0.00 |
| September | 79.97 | 50.87 | 29.09 | 93.66 | 43.77 | 0.00 | 0.00 | 0.00 |
| October | 49.51 | 27.53 | 21.98 | 47.36 | 61.40 | 0.00 | 0.00 | 0.00 |
| November | 28.49 | 13.25 | 15.23 | 17.69 | 77.31 | 0.00 | 0.00 | 0.00 |
| December | 19.21 | 6.96 | 12.25 | 5.50 | 98.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74.82 | 44.80 | 30.02 | 81.11 | 62.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19.21 | 6.96 | 12.25 | 5.50 | 29.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.87 | 97.56 | 47.57 | 181.15 | 111.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 24.31 | 9.32 | 14.99 | 8.50 | 111.46 | 0.00 | 0.00 | 0.00 |
| February | 41.12 | 22.06 | 19.06 | 29.87 | 84.25 | 0.00 | 0.00 | 0.00 |
| March | 67.86 | 31.57 | 36.29 | 61.53 | 72.82 | 0.00 | 0.00 | 0.00 |
| April | 87.24 | 49.35 | 37.89 | 89.31 | 56.41 | 0.00 | 0.00 | 0.00 |
| May | 111.26 | 63.87 | 47.40 | 124.66 | 45.91 | 0.00 | 0.00 | 0.00 |
| June | 133.91 | 86.34 | 47.57 | 164.97 | 33.68 | 0.00 | 0.00 | 0.00 |
| July | 138.87 | 97.56 | 41.31 | 181.15 | 29.59 | 0.00 | 0.00 | 0.00 |
| August | 113.81 | 77.36 | 36.44 | 145.49 | 31.99 | 0.00 | 0.00 | 0.00 |
| September | 79.97 | 50.87 | 29.09 | 93.66 | 43.77 | 0.00 | 0.00 | 0.00 |
| October | 49.51 | 27.53 | 21.98 | 47.36 | 61.40 | 0.00 | 0.00 | 0.00 |
| November | 28.49 | 13.25 | 15.23 | 17.69 | 77.31 | 0.00 | 0.00 | 0.00 |
| December | 19.21 | 6.96 | 12.25 | 5.50 | 98.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74.82 | 44.80 | 30.02 | 81.11 | 62.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19.21 | 6.96 | 12.25 | 5.50 | 29.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.87 | 97.56 | 47.57 | 181.15 | 111.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 24.31 | 9.32 | 14.99 | 8.50 | 111.46 | 0.00 | 0.00 | 0.00 |
| February | 41.12 | 22.06 | 19.06 | 29.87 | 84.25 | 0.00 | 0.00 | 0.00 |
| March | 67.86 | 31.57 | 36.29 | 61.53 | 72.82 | 0.00 | 0.00 | 0.00 |
| April | 87.24 | 49.35 | 37.89 | 89.31 | 56.41 | 0.00 | 0.00 | 0.00 |
| May | 111.26 | 63.87 | 47.40 | 124.66 | 45.91 | 0.00 | 0.00 | 0.00 |
| June | 133.91 | 86.34 | 47.57 | 164.97 | 33.68 | 0.00 | 0.00 | 0.00 |
| July | 138.87 | 97.56 | 41.31 | 181.15 | 29.59 | 0.00 | 0.00 | 0.00 |
| August | 113.81 | 77.36 | 36.44 | 145.49 | 31.99 | 0.00 | 0.00 | 0.00 |
| September | 79.97 | 50.87 | 29.09 | 93.66 | 43.77 | 0.00 | 0.00 | 0.00 |
| October | 49.51 | 27.53 | 21.98 | 47.36 | 61.40 | 0.00 | 0.00 | 0.00 |
| November | 28.49 | 13.25 | 15.23 | 17.69 | 77.31 | 0.00 | 0.00 | 0.00 |
| December | 19.21 | 6.96 | 12.25 | 5.50 | 98.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74.82 | 44.80 | 30.02 | 81.11 | 62.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19.21 | 6.96 | 12.25 | 5.50 | 29.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.87 | 97.56 | 47.57 | 181.15 | 111.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 24.31 | 9.32 | 14.99 | 8.50 | 111.46 | 0.00 | 0.00 | 0.00 |
| February | 41.12 | 22.06 | 19.06 | 29.87 | 84.25 | 0.00 | 0.00 | 0.00 |
| March | 67.86 | 31.57 | 36.29 | 61.53 | 72.82 | 0.00 | 0.00 | 0.00 |
| April | 87.24 | 49.35 | 37.89 | 89.31 | 56.41 | 0.00 | 0.00 | 0.00 |
| May | 111.26 | 63.87 | 47.40 | 124.66 | 45.91 | 0.00 | 0.00 | 0.00 |
| June | 133.91 | 86.34 | 47.57 | 164.97 | 33.68 | 0.00 | 0.00 | 0.00 |
| July | 138.87 | 97.56 | 41.31 | 181.15 | 29.59 | 0.00 | 0.00 | 0.00 |
| August | 113.81 | 77.36 | 36.44 | 145.49 | 31.99 | 0.00 | 0.00 | 0.00 |
| September | 79.97 | 50.87 | 29.09 | 93.66 | 43.77 | 0.00 | 0.00 | 0.00 |
| October | 49.51 | 27.53 | 21.98 | 47.36 | 61.40 | 0.00 | 0.00 | 0.00 |
| November | 28.49 | 13.25 | 15.23 | 17.69 | 77.31 | 0.00 | 0.00 | 0.00 |
| December | 19.21 | 6.96 | 12.25 | 5.50 | 98.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74.82 | 44.80 | 30.02 | 81.11 | 62.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19.21 | 6.96 | 12.25 | 5.50 | 29.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.87 | 97.56 | 47.57 | 181.15 | 111.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 24.31 | 9.32 | 14.99 | 8.50 | 111.46 | 0.00 | 0.00 | 0.00 |
| February | 41.12 | 22.06 | 19.06 | 29.87 | 84.25 | 0.00 | 0.00 | 0.00 |
| March | 67.86 | 31.57 | 36.29 | 61.53 | 72.82 | 0.00 | 0.00 | 0.00 |
| April | 87.24 | 49.35 | 37.89 | 89.31 | 56.41 | 0.00 | 0.00 | 0.00 |
| May | 111.26 | 63.87 | 47.40 | 124.66 | 45.91 | 0.00 | 0.00 | 0.00 |
| June | 133.91 | 86.34 | 47.57 | 164.97 | 33.68 | 0.00 | 0.00 | 0.00 |
| July | 138.87 | 97.56 | 41.31 | 181.15 | 29.59 | 0.00 | 0.00 | 0.00 |
| August | 113.81 | 77.36 | 36.44 | 145.49 | 31.99 | 0.00 | 0.00 | 0.00 |
| September | 79.97 | 50.87 | 29.09 | 93.66 | 43.77 | 0.00 | 0.00 | 0.00 |
| October | 49.51 | 27.53 | 21.98 | 47.36 | 61.40 | 0.00 | 0.00 | 0.00 |
| November | 28.49 | 13.25 | 15.23 | 17.69 | 77.31 | 0.00 | 0.00 | 0.00 |
| December | 19.21 | 6.96 | 12.25 | 5.50 | 98.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74.82 | 44.80 | 30.02 | 81.11 | 62.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19.21 | 6.96 | 12.25 | 5.50 | 29.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.87 | 97.56 | 47.57 | 181.15 | 111.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 24.31 | 9.32 | 14.99 | 8.50 | 111.46 | 0.00 | 0.00 | 0.00 |
| February | 41.12 | 22.06 | 19.06 | 29.87 | 84.25 | 0.00 | 0.00 | 0.00 |
| March | 67.86 | 31.57 | 36.29 | 61.53 | 72.82 | 0.00 | 0.00 | 0.00 |
| April | 87.24 | 49.35 | 37.89 | 89.31 | 56.41 | 0.00 | 0.00 | 0.00 |
| May | 111.26 | 63.87 | 47.40 | 124.66 | 45.91 | 0.00 | 0.00 | 0.00 |
| June | 133.91 | 86.34 | 47.57 | 164.97 | 33.68 | 0.00 | 0.00 | 0.00 |
| July | 138.87 | 97.56 | 41.31 | 181.15 | 29.59 | 0.00 | 0.00 | 0.00 |
| August | 113.81 | 77.36 | 36.44 | 145.49 | 31.99 | 0.00 | 0.00 | 0.00 |
| September | 79.97 | 50.87 | 29.09 | 93.66 | 43.77 | 0.00 | 0.00 | 0.00 |
| October | 49.51 | 27.53 | 21.98 | 47.36 | 61.40 | 0.00 | 0.00 | 0.00 |
| November | 28.49 | 13.25 | 15.23 | 17.69 | 77.31 | 0.00 | 0.00 | 0.00 |
| December | 19.21 | 6.96 | 12.25 | 5.50 | 98.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74.82 | 44.80 | 30.02 | 81.11 | 62.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19.21 | 6.96 | 12.25 | 5.50 | 29.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.87 | 97.56 | 47.57 | 181.15 | 111.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 24.31 | 9.32 | 14.99 | 8.50 | 111.46 | 0.00 | 0.00 | 0.00 |
| February | 41.12 | 22.06 | 19.06 | 29.87 | 84.25 | 0.00 | 0.00 | 0.00 |
| March | 67.86 | 31.57 | 36.29 | 61.53 | 72.82 | 0.00 | 0.00 | 0.00 |
| April | 87.24 | 49.35 | 37.89 | 89.31 | 56.41 | 0.00 | 0.00 | 0.00 |
| May | 111.26 | 63.87 | 47.40 | 124.66 | 45.91 | 0.00 | 0.00 | 0.00 |
| June | 133.91 | 86.34 | 47.57 | 164.97 | 33.68 | 0.00 | 0.00 | 0.00 |
| July | 138.87 | 97.56 | 41.31 | 181.15 | 29.59 | 0.00 | 0.00 | 0.00 |
| August | 113.81 | 77.36 | 36.44 | 145.49 | 31.99 | 0.00 | 0.00 | 0.00 |
| September | 79.97 | 50.87 | 29.09 | 93.66 | 43.77 | 0.00 | 0.00 | 0.00 |
| October | 49.51 | 27.53 | 21.98 | 47.36 | 61.40 | 0.00 | 0.00 | 0.00 |
| November | 28.49 | 13.25 | 15.23 | 17.69 | 77.31 | 0.00 | 0.00 | 0.00 |
| December | 19.21 | 6.96 | 12.25 | 5.50 | 98.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74.82 | 44.80 | 30.02 | 81.11 | 62.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19.21 | 6.96 | 12.25 | 5.50 | 29.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.87 | 97.56 | 47.57 | 181.15 | 111.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 24.31 | 9.32 | 14.99 | 8.50 | 111.46 | 0.00 | 0.00 | 0.00 |
| February | 41.12 | 22.06 | 19.06 | 29.87 | 84.25 | 0.00 | 0.00 | 0.00 |
| March | 67.86 | 31.57 | 36.29 | 61.53 | 72.82 | 0.00 | 0.00 | 0.00 |
| April | 87.24 | 49.35 | 37.89 | 89.31 | 56.41 | 0.00 | 0.00 | 0.00 |
| May | 111.26 | 63.87 | 47.40 | 124.66 | 45.91 | 0.00 | 0.00 | 0.00 |
| June | 133.91 | 86.34 | 47.57 | 164.97 | 33.68 | 0.00 | 0.00 | 0.00 |
| July | 138.87 | 97.56 | 41.31 | 181.15 | 29.59 | 0.00 | 0.00 | 0.00 |
| August | 113.81 | 77.36 | 36.44 | 145.49 | 31.99 | 0.00 | 0.00 | 0.00 |
| September | 79.97 | 50.87 | 29.09 | 93.66 | 43.77 | 0.00 | 0.00 | 0.00 |
| October | 49.51 | 27.53 | 21.98 | 47.36 | 61.40 | 0.00 | 0.00 | 0.00 |
| November | 28.49 | 13.25 | 15.23 | 17.69 | 77.31 | 0.00 | 0.00 | 0.00 |
| December | 19.21 | 6.96 | 12.25 | 5.50 | 98.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74.82 | 44.80 | 30.02 | 81.11 | 62.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19.21 | 6.96 | 12.25 | 5.50 | 29.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.87 | 97.56 | 47.57 | 181.15 | 111.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 24.31 | 9.32 | 14.99 | 8.50 | 111.46 | 0.00 | 0.00 | 0.00 |
| February | 41.12 | 22.06 | 19.06 | 29.87 | 84.25 | 0.00 | 0.00 | 0.00 |
| March | 67.86 | 31.57 | 36.29 | 61.53 | 72.82 | 0.00 | 0.00 | 0.00 |
| April | 87.24 | 49.35 | 37.89 | 89.31 | 56.41 | 0.00 | 0.00 | 0.00 |
| May | 111.26 | 63.87 | 47.40 | 124.66 | 45.91 | 0.00 | 0.00 | 0.00 |
| June | 133.91 | 86.34 | 47.57 | 164.97 | 33.68 | 0.00 | 0.00 | 0.00 |
| July | 138.87 | 97.56 | 41.31 | 181.15 | 29.59 | 0.00 | 0.00 | 0.00 |
| August | 113.81 | 77.36 | 36.44 | 145.49 | 31.99 | 0.00 | 0.00 | 0.00 |
| September | 79.97 | 50.87 | 29.09 | 93.66 | 43.77 | 0.00 | 0.00 | 0.00 |
| October | 49.51 | 27.53 | 21.98 | 47.36 | 61.40 | 0.00 | 0.00 | 0.00 |
| November | 28.49 | 13.25 | 15.23 | 17.69 | 77.31 | 0.00 | 0.00 | 0.00 |
| December | 19.21 | 6.96 | 12.25 | 5.50 | 98.40 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74.82 | 44.80 | 30.02 | 81.11 | 62.17 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 19.21 | 6.96 | 12.25 | 5.50 | 29.59 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 138.87 | 97.56 | 47.57 | 181.15 | 111.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.46 | 6.17 | 7.29 | 5.76 | 66.50 | 0.00 | 0.00 | 0.00 |
| February | 21.05 | 10.45 | 10.60 | 14.07 | 49.87 | 0.00 | 0.00 | 0.00 |
| March | 28.30 | 11.71 | 16.59 | 20.04 | 42.46 | 0.00 | 0.00 | 0.00 |
| April | 36.11 | 17.90 | 18.22 | 31.72 | 32.40 | 0.00 | 0.00 | 0.00 |
| May | 39.89 | 17.75 | 22.14 | 37.86 | 26.29 | 0.00 | 0.00 | 0.00 |
| June | 51.63 | 26.57 | 25.06 | 59.55 | 16.99 | 0.00 | 0.00 | 0.00 |
| July | 54.19 | 30.64 | 23.56 | 69.71 | 13.24 | 0.00 | 0.00 | 0.00 |
| August | 47.09 | 26.24 | 20.86 | 58.86 | 14.90 | 0.00 | 0.00 | 0.00 |
| September | 33.31 | 17.20 | 16.12 | 35.97 | 22.68 | 0.00 | 0.00 | 0.00 |
| October | 23.90 | 12.14 | 11.76 | 19.84 | 32.92 | 0.00 | 0.00 | 0.00 |
| November | 15.15 | 7.07 | 8.08 | 8.55 | 43.42 | 0.00 | 0.00 | 0.00 |
| December | 11.17 | 4.80 | 6.37 | 4.28 | 57.07 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 31.33 | 15.75 | 15.58 | 30.61 | 34.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11.17 | 4.80 | 6.37 | 4.28 | 13.24 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 54.19 | 30.64 | 25.06 | 69.71 | 66.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 159.29 | 73.03 | 86.27 | 68.18 | 787.07 | 0.00 | 0.00 | 0.00 |
| February | 249.15 | 123.69 | 125.46 | 166.58 | 590.03 | 0.00 | 0.00 | 0.00 |
| March | 335.01 | 138.61 | 196.39 | 237.34 | 502.29 | 0.00 | 0.00 | 0.00 |
| April | 427.43 | 211.83 | 215.61 | 376.12 | 383.27 | 0.00 | 0.00 | 0.00 |
| May | 472.16 | 210.07 | 262.08 | 448.93 | 310.97 | 0.00 | 0.00 | 0.00 |
| June | 611.15 | 314.49 | 296.66 | 705.91 | 201.04 | 0.00 | 0.00 | 0.00 |
| July | 641.41 | 362.60 | 278.82 | 826.60 | 156.76 | 0.00 | 0.00 | 0.00 |
| August | 557.42 | 310.57 | 246.85 | 697.79 | 176.42 | 0.00 | 0.00 | 0.00 |
| September | 394.32 | 203.54 | 190.78 | 426.62 | 268.39 | 0.00 | 0.00 | 0.00 |
| October | 282.90 | 143.65 | 139.25 | 235.04 | 389.50 | 0.00 | 0.00 | 0.00 |
| November | 179.30 | 83.71 | 95.59 | 101.15 | 513.71 | 0.00 | 0.00 | 0.00 |
| December | 132.24 | 56.80 | 75.45 | 50.63 | 675.47 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 370.78 | 186.37 | 184.41 | 362.90 | 412.24 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 132.24 | 56.80 | 75.45 | 50.63 | 156.76 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 641.41 | 362.60 | 296.66 | 826.60 | 787.07 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 81.30 | 37.27 | 44.03 | 29.22 | 483.74 | 493.00 | 0.00 | 0.00 |
| February | 127.17 | 63.14 | 64.03 | 74.33 | 375.96 | 338.83 | 0.00 | 0.00 |
| March | 170.99 | 70.75 | 100.24 | 110.53 | 314.39 | 242.00 | 0.00 | 0.00 |
| April | 218.16 | 108.12 | 110.04 | 182.73 | 230.92 | 86.17 | 0.00 | 0.00 |
| May | 240.99 | 107.22 | 133.77 | 223.84 | 181.62 | 31.50 | 0.00 | 0.00 |
| June | 311.93 | 160.52 | 151.41 | 358.45 | 113.70 | 0.00 | 0.00 | 0.00 |
| July | 327.38 | 185.08 | 142.30 | 420.59 | 88.21 | 0.00 | 0.00 | 0.00 |
| August | 284.51 | 158.52 | 125.99 | 355.01 | 100.83 | 0.00 | 0.00 | 0.00 |
| September | 201.26 | 103.89 | 97.37 | 213.85 | 153.07 | 0.00 | 0.00 | 0.00 |
| October | 144.39 | 73.32 | 71.07 | 114.29 | 232.33 | 23.67 | 0.00 | 0.00 |
| November | 91.51 | 42.72 | 48.79 | 44.57 | 325.78 | 194.00 | 0.00 | 0.00 |
| December | 67.50 | 28.99 | 38.51 | 20.15 | 427.02 | 413.33 | 0.00 | 0.00 |
| Annual Sum or Average | 189.25 | 95.13 | 94.12 | 179.59 | 251.79 | 1822.50 | 0.00 | 0.00 |
| Minimum of Months | 67.50 | 28.99 | 38.51 | 20.15 | 88.21 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 327.38 | 185.08 | 151.41 | 420.59 | 483.74 | 493.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 87.35 | 0.00 | 87.35 | 0.31 | 1132.24 | 0.00 | 0.00 | 0.00 |
| February | 123.16 | 0.00 | 123.16 | 8.50 | 847.24 | 0.00 | 0.00 | 0.00 |
| March | 200.78 | 0.00 | 200.78 | 30.77 | 686.76 | 0.00 | 0.00 | 0.00 |
| April | 227.13 | 1.05 | 226.09 | 76.00 | 497.49 | 0.00 | 0.00 | 0.00 |
| May | 292.23 | 12.66 | 279.57 | 155.72 | 390.49 | 0.00 | 0.00 | 0.00 |
| June | 335.99 | 31.43 | 304.56 | 283.33 | 258.10 | 0.00 | 0.00 | 0.00 |
| July | 316.32 | 28.21 | 288.11 | 351.86 | 202.45 | 0.00 | 0.00 | 0.00 |
| August | 252.47 | 4.90 | 247.57 | 253.17 | 233.88 | 0.00 | 0.00 | 0.00 |
| September | 191.30 | 0.04 | 191.26 | 128.88 | 372.83 | 0.00 | 0.00 | 0.00 |
| October | 139.61 | 0.00 | 139.61 | 30.20 | 534.55 | 0.00 | 0.00 | 0.00 |
| November | 94.75 | 0.00 | 94.75 | 3.59 | 740.65 | 0.00 | 0.00 | 0.00 |
| December | 72.96 | 0.00 | 72.96 | 0.06 | 972.54 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 194.90 | 6.56 | 188.34 | 110.89 | 571.33 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 72.96 | 0.00 | 72.96 | 0.06 | 202.45 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 335.99 | 31.43 | 304.56 | 351.86 | 1132.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.59 | 6.23 | 7.36 | 6.02 | 65.75 | 0.00 | 0.00 | 0.00 |
| February | 21.25 | 10.55 | 10.70 | 14.62 | 48.69 | 0.00 | 0.00 | 0.00 |
| March | 28.57 | 11.82 | 16.75 | 21.10 | 40.07 | 0.00 | 0.00 | 0.00 |
| April | 36.46 | 18.07 | 18.39 | 33.53 | 29.27 | 0.00 | 0.00 | 0.00 |
| May | 40.27 | 17.92 | 22.35 | 39.55 | 24.11 | 0.00 | 0.00 | 0.00 |
| June | 52.12 | 26.82 | 25.30 | 60.97 | 16.50 | 0.00 | 0.00 | 0.00 |
| July | 54.71 | 30.93 | 23.78 | 70.87 | 13.00 | 0.00 | 0.00 | 0.00 |
| August | 47.54 | 26.49 | 21.05 | 60.03 | 14.34 | 0.00 | 0.00 | 0.00 |
| September | 33.63 | 17.36 | 16.27 | 36.87 | 21.85 | 0.00 | 0.00 | 0.00 |
| October | 24.13 | 12.25 | 11.88 | 20.69 | 31.12 | 0.00 | 0.00 | 0.00 |
| November | 15.29 | 7.14 | 8.15 | 8.84 | 42.35 | 0.00 | 0.00 | 0.00 |
| December | 11.28 | 4.84 | 6.43 | 4.46 | 56.53 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 31.62 | 15.90 | 15.73 | 31.56 | 33.58 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11.28 | 4.84 | 6.43 | 4.46 | 13.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 54.71 | 30.93 | 25.30 | 70.87 | 65.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 138.86 | 63.66 | 75.20 | 61.51 | 672.02 | 0.00 | 0.00 | 0.00 |
| February | 217.20 | 107.83 | 109.36 | 149.39 | 497.68 | 0.00 | 0.00 | 0.00 |
| March | 292.04 | 120.84 | 171.20 | 215.64 | 409.58 | 0.00 | 0.00 | 0.00 |
| April | 372.61 | 184.66 | 187.95 | 342.68 | 299.12 | 0.00 | 0.00 | 0.00 |
| May | 411.60 | 183.14 | 228.46 | 404.23 | 246.30 | 0.00 | 0.00 | 0.00 |
| June | 532.76 | 274.16 | 258.60 | 623.32 | 168.58 | 0.00 | 0.00 | 0.00 |
| July | 559.15 | 316.10 | 243.05 | 724.40 | 132.84 | 0.00 | 0.00 | 0.00 |
| August | 485.93 | 270.74 | 215.18 | 613.59 | 146.59 | 0.00 | 0.00 | 0.00 |
| September | 343.75 | 177.44 | 166.31 | 376.82 | 223.30 | 0.00 | 0.00 | 0.00 |
| October | 246.62 | 125.23 | 121.39 | 211.48 | 318.13 | 0.00 | 0.00 | 0.00 |
| November | 156.30 | 72.97 | 83.33 | 90.31 | 432.89 | 0.00 | 0.00 | 0.00 |
| December | 115.28 | 49.51 | 65.77 | 45.60 | 577.81 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 323.23 | 162.47 | 160.76 | 322.59 | 343.16 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 115.28 | 49.51 | 65.77 | 45.60 | 132.84 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 559.15 | 316.10 | 258.60 | 724.40 | 672.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 84.09 | 0.00 | 84.09 | 0.76 | 1008.73 | 0.00 | 0.00 | 0.00 |
| February | 118.73 | 0.00 | 118.73 | 12.35 | 743.29 | 0.00 | 0.00 | 0.00 |
| March | 192.88 | 0.00 | 192.88 | 36.30 | 604.45 | 0.00 | 0.00 | 0.00 |
| April | 219.92 | 1.28 | 218.64 | 78.56 | 448.84 | 0.00 | 0.00 | 0.00 |
| May | 288.81 | 17.11 | 271.70 | 162.52 | 350.97 | 0.00 | 0.00 | 0.00 |
| June | 336.30 | 38.65 | 297.65 | 294.38 | 228.06 | 0.00 | 0.00 | 0.00 |
| July | 307.23 | 28.78 | 278.46 | 350.92 | 180.20 | 0.00 | 0.00 | 0.00 |
| August | 246.19 | 6.60 | 239.59 | 251.62 | 209.80 | 0.00 | 0.00 | 0.00 |
| September | 184.38 | 0.07 | 184.31 | 127.25 | 345.53 | 0.00 | 0.00 | 0.00 |
| October | 134.49 | 0.00 | 134.49 | 30.43 | 499.22 | 0.00 | 0.00 | 0.00 |
| November | 91.43 | 0.00 | 91.43 | 4.98 | 661.28 | 0.00 | 0.00 | 0.00 |
| December | 70.52 | 0.00 | 70.52 | 0.28 | 858.69 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 189.96 | 7.75 | 182.22 | 113.20 | 510.68 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 70.52 | 0.00 | 70.52 | 0.28 | 180.20 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 336.30 | 38.65 | 297.65 | 350.92 | 1008.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 4.23 | 0.00 | 4.23 | 0.00 | 68.41 | 0.00 | 0.00 | 0.00 |
| February | 6.09 | 0.00 | 6.09 | 0.46 | 51.05 | 0.00 | 0.00 | 0.00 |
| March | 9.79 | 0.00 | 9.79 | 0.95 | 42.17 | 0.00 | 0.00 | 0.00 |
| April | 18.32 | 6.20 | 12.12 | 10.59 | 29.17 | 0.00 | 0.00 | 0.00 |
| May | 27.99 | 12.15 | 15.84 | 24.17 | 24.08 | 0.00 | 0.00 | 0.00 |
| June | 40.10 | 21.16 | 18.94 | 45.35 | 15.58 | 0.00 | 0.00 | 0.00 |
| July | 40.72 | 22.97 | 17.76 | 52.38 | 11.38 | 0.00 | 0.00 | 0.00 |
| August | 27.63 | 12.99 | 14.64 | 32.86 | 13.01 | 0.00 | 0.00 | 0.00 |
| September | 11.37 | 1.44 | 9.93 | 7.78 | 22.20 | 0.00 | 0.00 | 0.00 |
| October | 6.89 | 0.00 | 6.89 | 1.12 | 34.12 | 0.00 | 0.00 | 0.00 |
| November | 4.63 | 0.00 | 4.63 | 0.05 | 44.81 | 0.00 | 0.00 | 0.00 |
| December | 3.52 | 0.00 | 3.52 | 0.00 | 58.22 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 16.84 | 6.45 | 10.39 | 14.75 | 34.45 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 3.52 | 0.00 | 3.52 | 0.00 | 11.38 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 40.72 | 22.97 | 18.94 | 52.38 | 68.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 163.69 | 64.62 | 99.07 | 52.82 | 965.91 | 0.00 | 0.00 | 0.00 |
| February | 280.98 | 133.68 | 147.30 | 182.51 | 700.52 | 0.00 | 0.00 | 0.00 |
| March | 410.74 | 172.13 | 238.61 | 303.18 | 576.62 | 0.00 | 0.00 | 0.00 |
| April | 528.36 | 266.20 | 262.16 | 485.22 | 433.55 | 0.00 | 0.00 | 0.00 |
| May | 582.50 | 264.00 | 318.51 | 569.01 | 360.10 | 0.00 | 0.00 | 0.00 |
| June | 755.39 | 395.21 | 360.18 | 884.15 | 240.73 | 0.00 | 0.00 | 0.00 |
| July | 794.35 | 455.68 | 338.67 | 1037.11 | 184.12 | 0.00 | 0.00 | 0.00 |
| August | 690.31 | 390.29 | 300.03 | 876.16 | 207.47 | 0.00 | 0.00 | 0.00 |
| September | 486.31 | 254.84 | 231.47 | 531.58 | 326.24 | 0.00 | 0.00 | 0.00 |
| October | 332.86 | 166.49 | 166.37 | 273.17 | 471.70 | 0.00 | 0.00 | 0.00 |
| November | 191.38 | 81.34 | 110.05 | 91.96 | 619.84 | 0.00 | 0.00 | 0.00 |
| December | 129.60 | 45.88 | 83.71 | 32.14 | 826.18 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 446.40 | 224.66 | 221.74 | 444.79 | 492.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 129.60 | 45.88 | 83.71 | 32.14 | 184.12 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 794.35 | 455.68 | 360.18 | 1037.11 | 965.91 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.221912E+09 | 89432082.68 | 0.132480E+09 | 93580944.94 | 0.121843E+10 |
| February | 0.342115E+09 | 0.168167E+09 | 0.173948E+09 | 0.234808E+09 | 0.785709E+09 |
| March | 0.484733E+09 | 0.177614E+09 | 0.307120E+09 | 0.346041E+09 | 0.716145E+09 |
| April | 0.612408E+09 | 0.271325E+09 | 0.341083E+09 | 0.576727E+09 | 0.479844E+09 |
| May | 0.782755E+09 | 0.356978E+09 | 0.425777E+09 | 0.816528E+09 | 0.406884E+09 |
| June | 0.824137E+09 | 0.378557E+09 | 0.445580E+09 | 0.988376E+09 | 0.274354E+09 |
| July | 0.872377E+09 | 0.440825E+09 | 0.431552E+09 | 0.117519E+10 | 0.221758E+09 |
| August | 0.740766E+09 | 0.363552E+09 | 0.377214E+09 | 0.957727E+09 | 0.250753E+09 |
| September | 0.576677E+09 | 0.291545E+09 | 0.285133E+09 | 0.645405E+09 | 0.388485E+09 |
| October | 0.425905E+09 | 0.211609E+09 | 0.214296E+09 | 0.365440E+09 | 0.586730E+09 |
| November | 0.291774E+09 | 0.144745E+09 | 0.147029E+09 | 0.193764E+09 | 0.744296E+09 |
| December | 0.202663E+09 | 85538378.79 | 0.117125E+09 | 86828236.44 | 0.101928E+10 |
| Annual Sum or Average | 0.637822E+10 | 0.297989E+10 | 0.339834E+10 | 0.648042E+10 | 0.709267E+10 |
| Minimum of Months | 0.202663E+09 | 85538378.79 | 0.117125E+09 | 86828236.44 | 0.221758E+09 |
| Maximum of Months | 0.872377E+09 | 0.440825E+09 | 0.445580E+09 | 0.117519E+10 | 0.121843E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.115762E+09 | 82679662.22 | 33082610.31 | 0.102211E+09 | 0.162115E+09 |
| February | 0.133155E+09 | 95769924.14 | 37385043.78 | 0.133321E+09 | 0.106974E+09 |
| March | 0.131776E+09 | 73999077.41 | 57776659.27 | 0.130846E+09 | 0.105140E+09 |
| April | 0.102509E+09 | 49030467.10 | 53478280.15 | 0.107744E+09 | 74622203.71 |
| May | 94112397.91 | 31257195.49 | 62855202.42 | 98464457.35 | 64230251.49 |
| June | 90493722.22 | 26392172.21 | 64101550.01 | 0.111367E+09 | 44024605.31 |
| July | 0.100813E+09 | 37239985.02 | 63573372.57 | 0.143985E+09 | 34203654.79 |
| August | 0.119810E+09 | 60405818.54 | 59404092.03 | 0.164752E+09 | 39071562.83 |
| September | 0.128597E+09 | 78795316.68 | 49801562.18 | 0.158529E+09 | 58505321.18 |
| October | 0.138922E+09 | 96062970.00 | 42859455.63 | 0.153214E+09 | 84409704.55 |
| November | 0.122570E+09 | 88784982.82 | 33785402.11 | 0.121680E+09 | 99947861.17 |
| December | 0.110083E+09 | 79491294.70 | 30592120.46 | 0.100530E+09 | 0.136684E+09 |
| Annual Sum or Average | 0.138860E+10 | 0.799909E+09 | 0.588695E+09 | 0.152664E+10 | 0.100993E+10 |
| Minimum of Months | 90493722.22 | 26392172.21 | 30592120.46 | 98464457.35 | 34203654.79 |
| Maximum of Months | 0.138922E+09 | 96062970.00 | 64101550.01 | 0.164752E+09 | 0.162115E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.803424E+09 | 0.573821E+09 | 0.229603E+09 | 0.709377E+09 | 0.112513E+10 |
| February | 0.924134E+09 | 0.664671E+09 | 0.259463E+09 | 0.925285E+09 | 0.742429E+09 |
| March | 0.914562E+09 | 0.513575E+09 | 0.400987E+09 | 0.908111E+09 | 0.729703E+09 |
| April | 0.711440E+09 | 0.340286E+09 | 0.371155E+09 | 0.747776E+09 | 0.517942E+09 |
| May | 0.653167E+09 | 0.216934E+09 | 0.436233E+09 | 0.682631E+09 | 0.447079E+09 |
| June | 0.628053E+09 | 0.183169E+09 | 0.444883E+09 | 0.770868E+09 | 0.306736E+09 |
| July | 0.699674E+09 | 0.258456E+09 | 0.441218E+09 | 0.997404E+09 | 0.237707E+09 |
| August | 0.831515E+09 | 0.419234E+09 | 0.412282E+09 | 0.114306E+10 | 0.271339E+09 |
| September | 0.892499E+09 | 0.546862E+09 | 0.345637E+09 | 0.110024E+10 | 0.406038E+09 |
| October | 0.964162E+09 | 0.666705E+09 | 0.297457E+09 | 0.106335E+10 | 0.585828E+09 |
| November | 0.850674E+09 | 0.616193E+09 | 0.234480E+09 | 0.844492E+09 | 0.693667E+09 |
| December | 0.764011E+09 | 0.551693E+09 | 0.212318E+09 | 0.697709E+09 | 0.948625E+09 |
| Annual Sum or Average | 0.963731E+10 | 0.555160E+10 | 0.408572E+10 | 0.105903E+11 | 0.701222E+10 |
| Minimum of Months | 0.628053E+09 | 0.183169E+09 | 0.212318E+09 | 0.682631E+09 | 0.237707E+09 |
| Maximum of Months | 0.964162E+09 | 0.666705E+09 | 0.444883E+09 | 0.114306E+10 | 0.112513E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.147631E+10 | 0.105441E+10 | 0.421901E+09 | 0.129467E+10 | 0.212627E+10 |
| February | 0.169812E+10 | 0.122135E+10 | 0.476769E+09 | 0.168477E+10 | 0.142787E+10 |
| March | 0.168053E+10 | 0.943709E+09 | 0.736822E+09 | 0.164800E+10 | 0.142437E+10 |
| April | 0.130729E+10 | 0.625285E+09 | 0.682005E+09 | 0.134947E+10 | 0.103435E+10 |
| May | 0.120021E+10 | 0.398623E+09 | 0.801587E+09 | 0.124477E+10 | 0.875212E+09 |
| June | 0.115406E+10 | 0.336579E+09 | 0.817481E+09 | 0.141466E+10 | 0.589938E+09 |
| July | 0.128567E+10 | 0.474921E+09 | 0.810745E+09 | 0.185172E+10 | 0.436573E+09 |
| August | 0.152793E+10 | 0.770355E+09 | 0.757575E+09 | 0.211292E+10 | 0.506905E+09 |
| September | 0.163999E+10 | 0.100488E+10 | 0.635116E+09 | 0.202309E+10 | 0.778994E+09 |
| October | 0.177167E+10 | 0.122509E+10 | 0.546584E+09 | 0.194166E+10 | 0.114039E+10 |
| November | 0.156314E+10 | 0.113227E+10 | 0.430864E+09 | 0.153353E+10 | 0.134671E+10 |
| December | 0.140389E+10 | 0.101375E+10 | 0.390140E+09 | 0.126806E+10 | 0.180952E+10 |
| Annual Sum or Average | 0.177088E+11 | 0.102012E+11 | 0.750759E+10 | 0.193673E+11 | 0.134971E+11 |
| Minimum of Months | 0.115406E+10 | 0.336579E+09 | 0.390140E+09 | 0.124477E+10 | 0.436573E+09 |
| Maximum of Months | 0.177167E+10 | 0.122509E+10 | 0.817481E+09 | 0.211292E+10 | 0.212627E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.147631E+10 | 0.105441E+10 | 0.421901E+09 | 0.129467E+10 | 0.212627E+10 |
| February | 0.169812E+10 | 0.122135E+10 | 0.476769E+09 | 0.168477E+10 | 0.142787E+10 |
| March | 0.168053E+10 | 0.943709E+09 | 0.736822E+09 | 0.164800E+10 | 0.142437E+10 |
| April | 0.130729E+10 | 0.625285E+09 | 0.682005E+09 | 0.134947E+10 | 0.103435E+10 |
| May | 0.120021E+10 | 0.398623E+09 | 0.801587E+09 | 0.124477E+10 | 0.875212E+09 |
| June | 0.115406E+10 | 0.336579E+09 | 0.817481E+09 | 0.141466E+10 | 0.589938E+09 |
| July | 0.128567E+10 | 0.474921E+09 | 0.810745E+09 | 0.185172E+10 | 0.436573E+09 |
| August | 0.152793E+10 | 0.770355E+09 | 0.757575E+09 | 0.211292E+10 | 0.506905E+09 |
| September | 0.163999E+10 | 0.100488E+10 | 0.635116E+09 | 0.202309E+10 | 0.778994E+09 |
| October | 0.177167E+10 | 0.122509E+10 | 0.546584E+09 | 0.194166E+10 | 0.114039E+10 |
| November | 0.156314E+10 | 0.113227E+10 | 0.430864E+09 | 0.153353E+10 | 0.134671E+10 |
| December | 0.140389E+10 | 0.101375E+10 | 0.390140E+09 | 0.126806E+10 | 0.180952E+10 |
| Annual Sum or Average | 0.177088E+11 | 0.102012E+11 | 0.750759E+10 | 0.193673E+11 | 0.134971E+11 |
| Minimum of Months | 0.115406E+10 | 0.336579E+09 | 0.390140E+09 | 0.124477E+10 | 0.436573E+09 |
| Maximum of Months | 0.177167E+10 | 0.122509E+10 | 0.817481E+09 | 0.211292E+10 | 0.212627E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.147629E+10 | 0.105439E+10 | 0.421893E+09 | 0.129465E+10 | 0.212623E+10 |
| February | 0.169809E+10 | 0.122133E+10 | 0.476760E+09 | 0.168474E+10 | 0.142785E+10 |
| March | 0.168050E+10 | 0.943691E+09 | 0.736808E+09 | 0.164797E+10 | 0.142434E+10 |
| April | 0.130726E+10 | 0.625273E+09 | 0.681991E+09 | 0.134944E+10 | 0.103433E+10 |
| May | 0.120019E+10 | 0.398615E+09 | 0.801572E+09 | 0.124475E+10 | 0.875195E+09 |
| June | 0.115404E+10 | 0.336573E+09 | 0.817465E+09 | 0.141463E+10 | 0.589927E+09 |
| July | 0.128564E+10 | 0.474912E+09 | 0.810729E+09 | 0.185169E+10 | 0.436564E+09 |
| August | 0.152790E+10 | 0.770340E+09 | 0.757561E+09 | 0.211288E+10 | 0.506896E+09 |
| September | 0.163996E+10 | 0.100486E+10 | 0.635103E+09 | 0.202305E+10 | 0.778979E+09 |
| October | 0.177164E+10 | 0.122507E+10 | 0.546573E+09 | 0.194162E+10 | 0.114037E+10 |
| November | 0.156311E+10 | 0.113225E+10 | 0.430855E+09 | 0.153350E+10 | 0.134668E+10 |
| December | 0.140386E+10 | 0.101373E+10 | 0.390132E+09 | 0.126803E+10 | 0.180948E+10 |
| Annual Sum or Average | 0.177085E+11 | 0.102010E+11 | 0.750744E+10 | 0.193670E+11 | 0.134968E+11 |
| Minimum of Months | 0.115404E+10 | 0.336573E+09 | 0.390132E+09 | 0.124475E+10 | 0.436564E+09 |
| Maximum of Months | 0.177164E+10 | 0.122507E+10 | 0.817465E+09 | 0.211288E+10 | 0.212623E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 73970815.50 | 29810793.60 | 44160021.90 | 31150865.41 | 0.429959E+09 |
| February | 0.114039E+09 | 56055770.97 | 57982836.54 | 79171468.92 | 0.278746E+09 |
| March | 0.161578E+09 | 59204732.84 | 0.102374E+09 | 0.114820E+09 | 0.257875E+09 |
| April | 0.204137E+09 | 90442042.89 | 0.113695E+09 | 0.190379E+09 | 0.176468E+09 |
| May | 0.260919E+09 | 0.118993E+09 | 0.141926E+09 | 0.270146E+09 | 0.149030E+09 |
| June | 0.274713E+09 | 0.126186E+09 | 0.148527E+09 | 0.326787E+09 | 99108255.97 |
| July | 0.290793E+09 | 0.146942E+09 | 0.143851E+09 | 0.393897E+09 | 74812117.93 |
| August | 0.246923E+09 | 0.121185E+09 | 0.125738E+09 | 0.323263E+09 | 83720853.69 |
| September | 0.192226E+09 | 97181884.34 | 95044555.50 | 0.218735E+09 | 0.133208E+09 |
| October | 0.141969E+09 | 70536604.45 | 71432123.70 | 0.124690E+09 | 0.202567E+09 |
| November | 97258402.11 | 48248465.95 | 49009936.16 | 66406740.62 | 0.260513E+09 |
| December | 67554597.73 | 28512887.97 | 39041709.75 | 29080289.15 | 0.359841E+09 |
| Annual Sum or Average | 0.212608E+10 | 0.993299E+09 | 0.113278E+10 | 0.216853E+10 | 0.250585E+10 |
| Minimum of Months | 67554597.73 | 28512887.97 | 39041709.75 | 29080289.15 | 74812117.93 |
| Maximum of Months | 0.290793E+09 | 0.146942E+09 | 0.148527E+09 | 0.393897E+09 | 0.429959E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.221912E+09 | 89432082.68 | 0.132480E+09 | 0.100988E+09 | 0.119975E+10 |
| February | 0.342115E+09 | 0.168167E+09 | 0.173948E+09 | 0.252674E+09 | 0.757509E+09 |
| March | 0.484733E+09 | 0.177614E+09 | 0.307120E+09 | 0.367056E+09 | 0.686875E+09 |
| April | 0.612408E+09 | 0.271325E+09 | 0.341083E+09 | 0.600078E+09 | 0.454982E+09 |
| May | 0.782755E+09 | 0.356978E+09 | 0.425777E+09 | 0.833181E+09 | 0.392424E+09 |
| June | 0.824137E+09 | 0.378557E+09 | 0.445580E+09 | 0.100057E+10 | 0.266713E+09 |
| July | 0.872377E+09 | 0.440825E+09 | 0.431552E+09 | 0.119714E+10 | 0.207325E+09 |
| August | 0.740766E+09 | 0.363552E+09 | 0.377214E+09 | 0.987610E+09 | 0.227745E+09 |
| September | 0.576677E+09 | 0.291545E+09 | 0.285133E+09 | 0.673596E+09 | 0.355546E+09 |
| October | 0.425905E+09 | 0.211609E+09 | 0.214296E+09 | 0.392267E+09 | 0.538267E+09 |
| November | 0.291774E+09 | 0.144745E+09 | 0.147029E+09 | 0.211771E+09 | 0.701942E+09 |
| December | 0.202663E+09 | 85538378.79 | 0.117125E+09 | 95715196.17 | 0.995675E+09 |
| Annual Sum or Average | 0.637822E+10 | 0.297989E+10 | 0.339834E+10 | 0.671264E+10 | 0.678475E+10 |
| Minimum of Months | 0.202663E+09 | 85538378.79 | 0.117125E+09 | 95715196.17 | 0.207325E+09 |
| Maximum of Months | 0.872377E+09 | 0.440825E+09 | 0.445580E+09 | 0.119714E+10 | 0.119975E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13086661.39 | 0.00 | 13086661.39 | 71316.21 | 0.192352E+09 |
| February | 16338489.80 | 0.00 | 16338489.80 | 1581326.69 | 0.126474E+09 |
| March | 30336336.89 | 0.00 | 30336336.89 | 4539049.99 | 0.110099E+09 |
| April | 33176794.73 | 196539.46 | 32980255.27 | 12430861.54 | 71541444.68 |
| May | 45203243.28 | 2908583.04 | 42294660.24 | 26051943.55 | 58859494.19 |
| June | 49930162.39 | 6309965.30 | 43620197.09 | 46971338.63 | 37203432.26 |
| July | 46793642.71 | 4472238.52 | 42321404.19 | 61614217.80 | 28581062.21 |
| August | 37632805.71 | 1102398.71 | 36530407.00 | 44108083.22 | 32283089.37 |
| September | 27196176.10 | 8883.79 | 27187292.31 | 20245080.23 | 54441253.03 |
| October | 20612796.23 | 0.00 | 20612796.23 | 4589456.82 | 85405000.28 |
| November | 13485796.01 | 0.00 | 13485796.01 | 664122.30 | 0.115088E+09 |
| December | 10705062.59 | 0.00 | 10705062.59 | 32364.75 | 0.161464E+09 |
| Annual Sum or Average | 0.344498E+09 | 14998608.83 | 0.329499E+09 | 0.222899E+09 | 0.107379E+10 |
| Minimum of Months | 10705062.59 | 0.00 | 10705062.59 | 32364.75 | 28581062.21 |
| Maximum of Months | 49930162.39 | 6309965.30 | 43620197.09 | 61614217.80 | 0.192352E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 96229364.35 | 0.00 | 96229364.35 | 690398.94 | 0.133141E+10 |
| February | 0.120854E+09 | 0.00 | 0.120854E+09 | 13546902.95 | 0.872833E+09 |
| March | 0.222419E+09 | 0.00 | 0.222419E+09 | 39133300.01 | 0.759519E+09 |
| April | 0.243718E+09 | 1364040.62 | 0.242354E+09 | 98323368.20 | 0.495061E+09 |
| May | 0.330957E+09 | 20186406.04 | 0.310770E+09 | 0.198809E+09 | 0.407430E+09 |
| June | 0.366269E+09 | 43792980.98 | 0.322476E+09 | 0.349722E+09 | 0.259644E+09 |
| July | 0.343726E+09 | 31038626.52 | 0.312687E+09 | 0.450532E+09 | 0.201282E+09 |
| August | 0.277601E+09 | 7650965.31 | 0.269950E+09 | 0.325451E+09 | 0.226322E+09 |
| September | 0.201120E+09 | 61656.09 | 0.201058E+09 | 0.153878E+09 | 0.378246E+09 |
| October | 0.152215E+09 | 0.00 | 0.152215E+09 | 37630232.83 | 0.589685E+09 |
| November | 99740624.18 | 0.00 | 99740624.18 | 6000062.93 | 0.794951E+09 |
| December | 79263397.92 | 0.00 | 79263397.92 | 277360.67 | 0.111761E+10 |
| Annual Sum or Average | 0.253411E+10 | 0.104095E+09 | 0.243002E+10 | 0.167399E+10 | 0.743399E+10 |
| Minimum of Months | 79263397.92 | 0.00 | 79263397.92 | 277360.67 | 0.201282E+09 |
| Maximum of Months | 0.366269E+09 | 43792980.98 | 0.322476E+09 | 0.450532E+09 | 0.133141E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.158330E+09 | 0.00 | 0.158330E+09 | 317160.51 | 0.251043E+10 |
| February | 0.197757E+09 | 0.00 | 0.197757E+09 | 14125577.33 | 0.167226E+10 |
| March | 0.367745E+09 | 0.00 | 0.367745E+09 | 39696965.16 | 0.148866E+10 |
| April | 0.398951E+09 | 829858.38 | 0.398121E+09 | 0.127147E+09 | 0.100611E+10 |
| May | 0.532792E+09 | 23846550.90 | 0.508946E+09 | 0.291595E+09 | 0.829069E+09 |
| June | 0.566443E+09 | 49878874.75 | 0.516565E+09 | 0.521870E+09 | 0.517680E+09 |
| July | 0.544496E+09 | 36227174.81 | 0.508269E+09 | 0.744632E+09 | 0.361042E+09 |
| August | 0.445768E+09 | 6636895.15 | 0.439131E+09 | 0.553224E+09 | 0.421049E+09 |
| September | 0.329658E+09 | 80067.49 | 0.329578E+09 | 0.248182E+09 | 0.718249E+09 |
| October | 0.249597E+09 | 0.00 | 0.249597E+09 | 47933111.22 | 0.115358E+10 |
| November | 0.162976E+09 | 0.00 | 0.162976E+09 | 4397663.84 | 0.153811E+10 |
| December | 0.129094E+09 | 0.00 | 0.129094E+09 | 220126.95 | 0.212467E+10 |
| Annual Sum or Average | 0.408361E+10 | 0.117499E+09 | 0.396611E+10 | 0.259334E+10 | 0.143409E+11 |
| Minimum of Months | 0.129094E+09 | 0.00 | 0.129094E+09 | 220126.95 | 0.361042E+09 |
| Maximum of Months | 0.566443E+09 | 49878874.75 | 0.516565E+09 | 0.744632E+09 | 0.251043E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.166958E+09 | 0.00 | 0.166958E+09 | 509433.97 | 0.250970E+10 |
| February | 0.208453E+09 | 0.00 | 0.208453E+09 | 16053054.17 | 0.166981E+10 |
| March | 0.387019E+09 | 0.00 | 0.387019E+09 | 48011183.84 | 0.148087E+10 |
| April | 0.421933E+09 | 1879076.11 | 0.420054E+09 | 0.140945E+09 | 0.997534E+09 |
| May | 0.570928E+09 | 32805007.37 | 0.538123E+09 | 0.320162E+09 | 0.809155E+09 |
| June | 0.620238E+09 | 69235929.75 | 0.551002E+09 | 0.582296E+09 | 0.505630E+09 |
| July | 0.596473E+09 | 56881960.26 | 0.539591E+09 | 0.811613E+09 | 0.359325E+09 |
| August | 0.476165E+09 | 11613581.99 | 0.464551E+09 | 0.579823E+09 | 0.413518E+09 |
| September | 0.346803E+09 | 84191.23 | 0.346719E+09 | 0.262414E+09 | 0.719506E+09 |
| October | 0.262983E+09 | 0.00 | 0.262983E+09 | 53461471.65 | 0.115276E+10 |
| November | 0.172057E+09 | 0.00 | 0.172057E+09 | 6038682.10 | 0.153908E+10 |
| December | 0.136580E+09 | 0.00 | 0.136580E+09 | 319341.91 | 0.212609E+10 |
| Annual Sum or Average | 0.436659E+10 | 0.172500E+09 | 0.419409E+10 | 0.282165E+10 | 0.142830E+11 |
| Minimum of Months | 0.136580E+09 | 0.00 | 0.136580E+09 | 319341.91 | 0.359325E+09 |
| Maximum of Months | 0.620238E+09 | 69235929.75 | 0.551002E+09 | 0.811613E+09 | 0.250970E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.167009E+09 | 0.00 | 0.167009E+09 | 510572.48 | 0.250964E+10 |
| February | 0.208524E+09 | 0.00 | 0.208524E+09 | 16070704.98 | 0.166975E+10 |
| March | 0.387132E+09 | 0.00 | 0.387132E+09 | 48072716.76 | 0.148080E+10 |
| April | 0.423318E+09 | 2465093.68 | 0.420853E+09 | 0.141135E+09 | 0.995215E+09 |
| May | 0.574256E+09 | 35137865.91 | 0.539118E+09 | 0.321297E+09 | 0.805019E+09 |
| June | 0.624532E+09 | 71979863.24 | 0.552553E+09 | 0.585097E+09 | 0.502014E+09 |
| July | 0.597167E+09 | 57192560.56 | 0.539974E+09 | 0.812570E+09 | 0.359225E+09 |
| August | 0.479944E+09 | 13835003.03 | 0.466109E+09 | 0.584089E+09 | 0.411474E+09 |
| September | 0.347055E+09 | 105488.94 | 0.346950E+09 | 0.262528E+09 | 0.719261E+09 |
| October | 0.263070E+09 | 0.00 | 0.263070E+09 | 53503670.47 | 0.115272E+10 |
| November | 0.172116E+09 | 0.00 | 0.172116E+09 | 6049510.46 | 0.153905E+10 |
| December | 0.136628E+09 | 0.00 | 0.136628E+09 | 319777.86 | 0.212604E+10 |
| Annual Sum or Average | 0.438075E+10 | 0.180716E+09 | 0.420004E+10 | 0.283124E+10 | 0.142702E+11 |
| Minimum of Months | 0.136628E+09 | 0.00 | 0.136628E+09 | 319777.86 | 0.359225E+09 |
| Maximum of Months | 0.624532E+09 | 71979863.24 | 0.552553E+09 | 0.812570E+09 | 0.250964E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.221912E+09 | 89432082.68 | 0.132480E+09 | 94289782.97 | 0.121676E+10 |
| February | 0.342115E+09 | 0.168167E+09 | 0.173948E+09 | 0.235405E+09 | 0.785040E+09 |
| March | 0.484733E+09 | 0.177614E+09 | 0.307120E+09 | 0.346975E+09 | 0.715245E+09 |
| April | 0.612408E+09 | 0.271325E+09 | 0.341083E+09 | 0.578009E+09 | 0.478891E+09 |
| May | 0.782755E+09 | 0.356978E+09 | 0.425777E+09 | 0.818419E+09 | 0.405359E+09 |
| June | 0.824137E+09 | 0.378557E+09 | 0.445580E+09 | 0.990522E+09 | 0.273070E+09 |
| July | 0.872377E+09 | 0.440825E+09 | 0.431552E+09 | 0.117770E+10 | 0.220254E+09 |
| August | 0.740766E+09 | 0.363552E+09 | 0.377214E+09 | 0.959736E+09 | 0.249407E+09 |
| September | 0.576677E+09 | 0.291545E+09 | 0.285133E+09 | 0.646475E+09 | 0.387613E+09 |
| October | 0.425905E+09 | 0.211609E+09 | 0.214296E+09 | 0.366242E+09 | 0.585708E+09 |
| November | 0.291774E+09 | 0.144745E+09 | 0.147029E+09 | 0.194670E+09 | 0.742002E+09 |
| December | 0.202663E+09 | 85538378.79 | 0.117125E+09 | 88019229.94 | 0.101592E+10 |
| Annual Sum or Average | 0.637822E+10 | 0.297989E+10 | 0.339834E+10 | 0.649646E+10 | 0.707527E+10 |
| Minimum of Months | 0.202663E+09 | 85538378.79 | 0.117125E+09 | 88019229.94 | 0.220254E+09 |
| Maximum of Months | 0.872377E+09 | 0.440825E+09 | 0.445580E+09 | 0.117770E+10 | 0.121676E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109015E+09 | 78722354.52 | 30292615.70 | 97493907.76 | 0.164355E+09 |
| February | 0.129358E+09 | 95035766.20 | 34322245.91 | 0.130215E+09 | 0.107153E+09 |
| March | 0.127385E+09 | 73965671.50 | 53419148.91 | 0.126347E+09 | 0.104416E+09 |
| April | 97604083.83 | 49030467.10 | 48573616.73 | 0.102916E+09 | 74156577.43 |
| May | 87833701.83 | 31257195.49 | 56576506.34 | 91994578.45 | 64109219.34 |
| June | 83302106.43 | 26392172.21 | 56909934.23 | 0.103412E+09 | 43612378.32 |
| July | 93903821.51 | 37239985.02 | 56663836.49 | 0.136357E+09 | 33148105.44 |
| August | 0.113828E+09 | 60405818.54 | 53422153.22 | 0.158243E+09 | 38043898.31 |
| September | 0.124076E+09 | 78790549.83 | 45285352.19 | 0.153611E+09 | 57570561.37 |
| October | 0.134937E+09 | 95563481.72 | 39373486.55 | 0.149348E+09 | 83606973.11 |
| November | 0.117672E+09 | 86846934.84 | 30825218.13 | 0.118306E+09 | 0.100812E+09 |
| December | 0.101620E+09 | 74437352.12 | 27183116.16 | 94355503.93 | 0.139397E+09 |
| Annual Sum or Average | 0.132053E+10 | 0.787688E+09 | 0.532847E+09 | 0.146260E+10 | 0.101038E+10 |
| Minimum of Months | 83302106.43 | 26392172.21 | 27183116.16 | 91994578.45 | 33148105.44 |
| Maximum of Months | 0.134937E+09 | 95563481.72 | 56909934.23 | 0.158243E+09 | 0.164355E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.747208E+09 | 0.544142E+09 | 0.203066E+09 | 0.667211E+09 | 0.113721E+10 |
| February | 0.888596E+09 | 0.659576E+09 | 0.229020E+09 | 0.894264E+09 | 0.740376E+09 |
| March | 0.869464E+09 | 0.513343E+09 | 0.356121E+09 | 0.861324E+09 | 0.722519E+09 |
| April | 0.660824E+09 | 0.340286E+09 | 0.320539E+09 | 0.697499E+09 | 0.513894E+09 |
| May | 0.588371E+09 | 0.216934E+09 | 0.371438E+09 | 0.615577E+09 | 0.447330E+09 |
| June | 0.553836E+09 | 0.183169E+09 | 0.370666E+09 | 0.688317E+09 | 0.303851E+09 |
| July | 0.628368E+09 | 0.258456E+09 | 0.369912E+09 | 0.917613E+09 | 0.227898E+09 |
| August | 0.769782E+09 | 0.419234E+09 | 0.350548E+09 | 0.107503E+10 | 0.261678E+09 |
| September | 0.845890E+09 | 0.546829E+09 | 0.299061E+09 | 0.104895E+10 | 0.396842E+09 |
| October | 0.925227E+09 | 0.663238E+09 | 0.261989E+09 | 0.102442E+10 | 0.576215E+09 |
| November | 0.808253E+09 | 0.602201E+09 | 0.206052E+09 | 0.812857E+09 | 0.695629E+09 |
| December | 0.687734E+09 | 0.507731E+09 | 0.180003E+09 | 0.635405E+09 | 0.964950E+09 |
| Annual Sum or Average | 0.897355E+10 | 0.545514E+10 | 0.351841E+10 | 0.993847E+10 | 0.698840E+10 |
| Minimum of Months | 0.553836E+09 | 0.183169E+09 | 0.180003E+09 | 0.615577E+09 | 0.227898E+09 |
| Maximum of Months | 0.925227E+09 | 0.663238E+09 | 0.371438E+09 | 0.107503E+10 | 0.113721E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.132752E+10 | 0.967636E+09 | 0.359887E+09 | 0.118702E+10 | 0.217504E+10 |
| February | 0.162134E+10 | 0.120898E+10 | 0.412365E+09 | 0.161841E+10 | 0.142504E+10 |
| March | 0.158600E+10 | 0.942919E+09 | 0.643079E+09 | 0.155116E+10 | 0.141123E+10 |
| April | 0.120160E+10 | 0.625285E+09 | 0.576319E+09 | 0.124494E+10 | 0.102991E+10 |
| May | 0.106492E+10 | 0.398623E+09 | 0.666294E+09 | 0.110465E+10 | 0.879576E+09 |
| June | 0.999095E+09 | 0.336579E+09 | 0.662516E+09 | 0.124343E+10 | 0.586832E+09 |
| July | 0.113678E+10 | 0.474921E+09 | 0.661858E+09 | 0.168727E+10 | 0.415745E+09 |
| August | 0.139903E+10 | 0.770355E+09 | 0.628676E+09 | 0.197248E+10 | 0.486042E+09 |
| September | 0.154270E+10 | 0.100482E+10 | 0.537880E+09 | 0.191704E+10 | 0.759433E+09 |
| October | 0.168831E+10 | 0.121653E+10 | 0.471781E+09 | 0.185997E+10 | 0.112097E+10 |
| November | 0.144928E+10 | 0.108469E+10 | 0.364593E+09 | 0.145135E+10 | 0.136767E+10 |
| December | 0.119731E+10 | 0.886864E+09 | 0.310447E+09 | 0.111475E+10 | 0.188381E+10 |
| Annual Sum or Average | 0.162139E+11 | 0.991819E+10 | 0.629569E+10 | 0.179525E+11 | 0.135413E+11 |
| Minimum of Months | 0.999095E+09 | 0.336579E+09 | 0.310447E+09 | 0.110465E+10 | 0.415745E+09 |
| Maximum of Months | 0.168831E+10 | 0.121653E+10 | 0.666294E+09 | 0.197248E+10 | 0.217504E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.132584E+10 | 0.966353E+09 | 0.359485E+09 | 0.118698E+10 | 0.217741E+10 |
| February | 0.161412E+10 | 0.120410E+10 | 0.410028E+09 | 0.161629E+10 | 0.143444E+10 |
| March | 0.158473E+10 | 0.942205E+09 | 0.642522E+09 | 0.155085E+10 | 0.141303E+10 |
| April | 0.120147E+10 | 0.625285E+09 | 0.576182E+09 | 0.124480E+10 | 0.102990E+10 |
| May | 0.106474E+10 | 0.398623E+09 | 0.666119E+09 | 0.110447E+10 | 0.879587E+09 |
| June | 0.998895E+09 | 0.336579E+09 | 0.662316E+09 | 0.124321E+10 | 0.586836E+09 |
| July | 0.113659E+10 | 0.474921E+09 | 0.661666E+09 | 0.168705E+10 | 0.415726E+09 |
| August | 0.139886E+10 | 0.770355E+09 | 0.628510E+09 | 0.197229E+10 | 0.486022E+09 |
| September | 0.154238E+10 | 0.100473E+10 | 0.537655E+09 | 0.191686E+10 | 0.759690E+09 |
| October | 0.168553E+10 | 0.121493E+10 | 0.470605E+09 | 0.185948E+10 | 0.112504E+10 |
| November | 0.144251E+10 | 0.107965E+10 | 0.362866E+09 | 0.145048E+10 | 0.137694E+10 |
| December | 0.119675E+10 | 0.886496E+09 | 0.310254E+09 | 0.111471E+10 | 0.188452E+10 |
| Annual Sum or Average | 0.161924E+11 | 0.990421E+10 | 0.628821E+10 | 0.179475E+11 | 0.135692E+11 |
| Minimum of Months | 0.998895E+09 | 0.336579E+09 | 0.310254E+09 | 0.110447E+10 | 0.415726E+09 |
| Maximum of Months | 0.168553E+10 | 0.121493E+10 | 0.666119E+09 | 0.197229E+10 | 0.217741E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.122811E+10 | 0.890897E+09 | 0.337215E+09 | 0.107190E+10 | 0.218688E+10 |
| February | 0.149791E+10 | 0.111616E+10 | 0.381744E+09 | 0.147986E+10 | 0.145313E+10 |
| March | 0.149986E+10 | 0.891811E+09 | 0.608053E+09 | 0.145047E+10 | 0.142722E+10 |
| April | 0.115243E+10 | 0.602646E+09 | 0.549782E+09 | 0.118400E+10 | 0.103256E+10 |
| May | 0.102621E+10 | 0.389595E+09 | 0.636614E+09 | 0.105912E+10 | 0.882038E+09 |
| June | 0.962702E+09 | 0.329299E+09 | 0.633403E+09 | 0.119893E+10 | 0.586731E+09 |
| July | 0.109759E+10 | 0.463659E+09 | 0.633931E+09 | 0.163552E+10 | 0.411581E+09 |
| August | 0.134634E+10 | 0.745576E+09 | 0.600759E+09 | 0.189963E+10 | 0.482525E+09 |
| September | 0.147092E+10 | 0.961155E+09 | 0.509762E+09 | 0.182243E+10 | 0.762586E+09 |
| October | 0.157154E+10 | 0.113168E+10 | 0.439857E+09 | 0.171993E+10 | 0.113989E+10 |
| November | 0.134176E+10 | 0.100301E+10 | 0.338756E+09 | 0.132859E+10 | 0.138470E+10 |
| December | 0.111419E+10 | 0.823668E+09 | 0.290526E+09 | 0.101550E+10 | 0.188797E+10 |
| Annual Sum or Average | 0.153096E+11 | 0.934915E+10 | 0.596040E+10 | 0.168659E+11 | 0.136378E+11 |
| Minimum of Months | 0.962702E+09 | 0.329299E+09 | 0.290526E+09 | 0.101550E+10 | 0.411581E+09 |
| Maximum of Months | 0.157154E+10 | 0.113168E+10 | 0.636614E+09 | 0.189963E+10 | 0.218688E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1_WALL_6_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 73970815.50 | 29810793.60 | 44160021.90 | 31239494.91 | 0.429475E+09 |
| February | 0.114039E+09 | 56055770.97 | 57982836.54 | 79256714.69 | 0.278572E+09 |
| March | 0.161578E+09 | 59204732.84 | 0.102374E+09 | 0.114911E+09 | 0.257716E+09 |
| April | 0.204137E+09 | 90442042.89 | 0.113695E+09 | 0.190462E+09 | 0.176400E+09 |
| May | 0.260919E+09 | 0.118993E+09 | 0.141926E+09 | 0.270282E+09 | 0.148889E+09 |
| June | 0.274713E+09 | 0.126186E+09 | 0.148527E+09 | 0.326954E+09 | 98959514.52 |
| July | 0.290793E+09 | 0.146942E+09 | 0.143851E+09 | 0.394254E+09 | 74486503.87 |
| August | 0.246923E+09 | 0.121185E+09 | 0.125738E+09 | 0.323589E+09 | 83383416.16 |
| September | 0.192226E+09 | 97181884.34 | 95044555.50 | 0.218891E+09 | 0.133002E+09 |
| October | 0.141969E+09 | 70536604.45 | 71432123.70 | 0.124832E+09 | 0.202259E+09 |
| November | 97258402.11 | 48248465.95 | 49009936.16 | 66600012.63 | 0.259754E+09 |
| December | 67554597.73 | 28512887.97 | 39041709.75 | 29214624.20 | 0.359000E+09 |
| Annual Sum or Average | 0.212608E+10 | 0.993299E+09 | 0.113278E+10 | 0.217049E+10 | 0.250189E+10 |
| Minimum of Months | 67554597.73 | 28512887.97 | 39041709.75 | 29214624.20 | 74486503.87 |
| Maximum of Months | 0.290793E+09 | 0.146942E+09 | 0.148527E+09 | 0.394254E+09 | 0.429475E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.221912E+09 | 89432082.68 | 0.132480E+09 | 0.101014E+09 | 0.119957E+10 |
| February | 0.342115E+09 | 0.168167E+09 | 0.173948E+09 | 0.252688E+09 | 0.757413E+09 |
| March | 0.484733E+09 | 0.177614E+09 | 0.307120E+09 | 0.367018E+09 | 0.686822E+09 |
| April | 0.612408E+09 | 0.271325E+09 | 0.341083E+09 | 0.599977E+09 | 0.455013E+09 |
| May | 0.782755E+09 | 0.356978E+09 | 0.425777E+09 | 0.833014E+09 | 0.392495E+09 |
| June | 0.824137E+09 | 0.378557E+09 | 0.445580E+09 | 0.100034E+10 | 0.266789E+09 |
| July | 0.872377E+09 | 0.440825E+09 | 0.431552E+09 | 0.119700E+10 | 0.207266E+09 |
| August | 0.740766E+09 | 0.363552E+09 | 0.377214E+09 | 0.987565E+09 | 0.227640E+09 |
| September | 0.576677E+09 | 0.291545E+09 | 0.285133E+09 | 0.673556E+09 | 0.355490E+09 |
| October | 0.425905E+09 | 0.211609E+09 | 0.214296E+09 | 0.392276E+09 | 0.538111E+09 |
| November | 0.291774E+09 | 0.144745E+09 | 0.147029E+09 | 0.211869E+09 | 0.701464E+09 |
| December | 0.202663E+09 | 85538378.79 | 0.117125E+09 | 95756045.89 | 0.995325E+09 |
| Annual Sum or Average | 0.637822E+10 | 0.297989E+10 | 0.339834E+10 | 0.671208E+10 | 0.678339E+10 |
| Minimum of Months | 0.202663E+09 | 85538378.79 | 0.117125E+09 | 95756045.89 | 0.207266E+09 |
| Maximum of Months | 0.872377E+09 | 0.440825E+09 | 0.445580E+09 | 0.119700E+10 | 0.119957E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 13357638.23 | 0.00 | 13357638.23 | 81019.01 | 0.192260E+09 |
| February | 16712567.94 | 0.00 | 16712567.94 | 1681463.24 | 0.126324E+09 |
| March | 30931836.61 | 0.00 | 30931836.61 | 4884000.16 | 0.109908E+09 |
| April | 33867696.00 | 205652.54 | 33662043.46 | 12981903.78 | 71443157.81 |
| May | 46144940.81 | 2967594.70 | 43177346.11 | 26953568.35 | 58732764.70 |
| June | 51119074.34 | 6445064.36 | 44674009.98 | 48259800.17 | 37132514.53 |
| July | 47951399.70 | 4628691.53 | 43322708.17 | 62914061.81 | 28593427.87 |
| August | 38501115.83 | 1128704.39 | 37372411.44 | 45059932.02 | 32333634.60 |
| September | 27816477.26 | 8883.79 | 27807593.47 | 20839701.90 | 54463084.77 |
| October | 21071925.50 | 0.00 | 21071925.50 | 4826471.45 | 85315230.60 |
| November | 13793935.83 | 0.00 | 13793935.83 | 729928.50 | 0.114967E+09 |
| December | 10954128.08 | 0.00 | 10954128.08 | 35042.11 | 0.161385E+09 |
| Annual Sum or Average | 0.352223E+09 | 15384591.33 | 0.336838E+09 | 0.229247E+09 | 0.107286E+10 |
| Minimum of Months | 10954128.08 | 0.00 | 10954128.08 | 35042.11 | 28593427.87 |
| Maximum of Months | 51119074.34 | 6445064.36 | 44674009.98 | 62914061.81 | 0.192260E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 97483078.09 | 0.00 | 97483078.09 | 753009.00 | 0.133093E+10 |
| February | 0.122585E+09 | 0.00 | 0.122585E+09 | 14058093.18 | 0.872154E+09 |
| March | 0.225174E+09 | 0.00 | 0.225174E+09 | 40869247.77 | 0.758770E+09 |
| April | 0.246952E+09 | 1427288.01 | 0.245524E+09 | 0.100950E+09 | 0.494662E+09 |
| May | 0.335493E+09 | 20595964.03 | 0.314897E+09 | 0.203123E+09 | 0.406783E+09 |
| June | 0.372230E+09 | 44730607.46 | 0.327499E+09 | 0.355991E+09 | 0.259036E+09 |
| July | 0.349561E+09 | 32124455.59 | 0.317437E+09 | 0.456946E+09 | 0.201037E+09 |
| August | 0.281723E+09 | 7833534.36 | 0.273889E+09 | 0.329951E+09 | 0.226453E+09 |
| September | 0.203990E+09 | 61656.09 | 0.203928E+09 | 0.156697E+09 | 0.378413E+09 |
| October | 0.154340E+09 | 0.00 | 0.154340E+09 | 38864240.08 | 0.589356E+09 |
| November | 0.101166E+09 | 0.00 | 0.101166E+09 | 6356961.41 | 0.794251E+09 |
| December | 80415735.64 | 0.00 | 80415735.64 | 291693.03 | 0.111712E+10 |
| Annual Sum or Average | 0.257111E+10 | 0.106774E+09 | 0.246434E+10 | 0.170485E+10 | 0.742896E+10 |
| Minimum of Months | 80415735.64 | 0.00 | 80415735.64 | 291693.03 | 0.201037E+09 |
| Maximum of Months | 0.372230E+09 | 44730607.46 | 0.327499E+09 | 0.456946E+09 | 0.133093E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.160290E+09 | 0.00 | 0.160290E+09 | 360191.54 | 0.250949E+10 |
| February | 0.200463E+09 | 0.00 | 0.200463E+09 | 14734852.53 | 0.167098E+10 |
| March | 0.372052E+09 | 0.00 | 0.372052E+09 | 41694997.55 | 0.148678E+10 |
| April | 0.403833E+09 | 829858.38 | 0.403003E+09 | 0.130724E+09 | 0.100536E+10 |
| May | 0.539719E+09 | 24298731.01 | 0.515420E+09 | 0.297577E+09 | 0.827708E+09 |
| June | 0.575451E+09 | 51112176.83 | 0.524339E+09 | 0.531665E+09 | 0.517461E+09 |
| July | 0.551446E+09 | 36258282.73 | 0.515188E+09 | 0.752672E+09 | 0.361931E+09 |
| August | 0.452141E+09 | 6877988.78 | 0.445264E+09 | 0.560427E+09 | 0.421444E+09 |
| September | 0.334144E+09 | 80067.49 | 0.334064E+09 | 0.252317E+09 | 0.718199E+09 |
| October | 0.252918E+09 | 0.00 | 0.252918E+09 | 49406363.76 | 0.115252E+10 |
| November | 0.165205E+09 | 0.00 | 0.165205E+09 | 4795006.54 | 0.153652E+10 |
| December | 0.130895E+09 | 0.00 | 0.130895E+09 | 234714.66 | 0.212360E+10 |
| Annual Sum or Average | 0.413856E+10 | 0.119457E+09 | 0.401910E+10 | 0.263661E+10 | 0.143320E+11 |
| Minimum of Months | 0.130895E+09 | 0.00 | 0.130895E+09 | 234714.66 | 0.361931E+09 |
| Maximum of Months | 0.575451E+09 | 51112176.83 | 0.524339E+09 | 0.752672E+09 | 0.250949E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.169740E+09 | 0.00 | 0.169740E+09 | 586174.67 | 0.250858E+10 |
| February | 0.212293E+09 | 0.00 | 0.212293E+09 | 16998287.44 | 0.166816E+10 |
| March | 0.393133E+09 | 0.00 | 0.393133E+09 | 51186845.63 | 0.147856E+10 |
| April | 0.429108E+09 | 1927754.46 | 0.427180E+09 | 0.146321E+09 | 0.996263E+09 |
| May | 0.581187E+09 | 33796968.31 | 0.547390E+09 | 0.329337E+09 | 0.806969E+09 |
| June | 0.634665E+09 | 72103503.63 | 0.562561E+09 | 0.597453E+09 | 0.503719E+09 |
| July | 0.608750E+09 | 58762793.78 | 0.549988E+09 | 0.825200E+09 | 0.358959E+09 |
| August | 0.485184E+09 | 11940747.52 | 0.473243E+09 | 0.589933E+09 | 0.414096E+09 |
| September | 0.353172E+09 | 84191.23 | 0.353088E+09 | 0.268422E+09 | 0.719608E+09 |
| October | 0.267697E+09 | 0.00 | 0.267697E+09 | 55696699.59 | 0.115156E+10 |
| November | 0.175220E+09 | 0.00 | 0.175220E+09 | 6661079.55 | 0.153742E+10 |
| December | 0.139137E+09 | 0.00 | 0.139137E+09 | 343771.80 | 0.212496E+10 |
| Annual Sum or Average | 0.444929E+10 | 0.178616E+09 | 0.427067E+10 | 0.288814E+10 | 0.142689E+11 |
| Minimum of Months | 0.139137E+09 | 0.00 | 0.139137E+09 | 343771.80 | 0.358959E+09 |
| Maximum of Months | 0.634665E+09 | 72103503.63 | 0.562561E+09 | 0.825200E+09 | 0.250858E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.169737E+09 | 0.00 | 0.169737E+09 | 586162.82 | 0.250854E+10 |
| February | 0.212289E+09 | 0.00 | 0.212289E+09 | 16997951.64 | 0.166813E+10 |
| March | 0.393125E+09 | 0.00 | 0.393125E+09 | 51185830.99 | 0.147853E+10 |
| April | 0.430175E+09 | 2501379.84 | 0.427674E+09 | 0.146349E+09 | 0.994177E+09 |
| May | 0.584890E+09 | 36580972.46 | 0.548309E+09 | 0.330923E+09 | 0.802590E+09 |
| June | 0.639642E+09 | 75443052.85 | 0.564199E+09 | 0.600699E+09 | 0.499466E+09 |
| July | 0.609479E+09 | 59234246.51 | 0.550245E+09 | 0.826237E+09 | 0.358780E+09 |
| August | 0.489136E+09 | 14388449.45 | 0.474747E+09 | 0.594327E+09 | 0.411770E+09 |
| September | 0.353298E+09 | 105488.94 | 0.353193E+09 | 0.268417E+09 | 0.719360E+09 |
| October | 0.267691E+09 | 0.00 | 0.267691E+09 | 55695604.82 | 0.115154E+10 |
| November | 0.175217E+09 | 0.00 | 0.175217E+09 | 6660946.48 | 0.153739E+10 |
| December | 0.139135E+09 | 0.00 | 0.139135E+09 | 343764.97 | 0.212492E+10 |
| Annual Sum or Average | 0.446381E+10 | 0.188254E+09 | 0.427556E+10 | 0.289842E+10 | 0.142552E+11 |
| Minimum of Months | 0.139135E+09 | 0.00 | 0.139135E+09 | 343764.97 | 0.358780E+09 |
| Maximum of Months | 0.639642E+09 | 75443052.85 | 0.564199E+09 | 0.826237E+09 | 0.250854E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.221912E+09 | 89432082.68 | 0.132480E+09 | 93997653.03 | 0.121767E+10 |
| February | 0.342115E+09 | 0.168167E+09 | 0.173948E+09 | 0.235240E+09 | 0.785442E+09 |
| March | 0.484733E+09 | 0.177614E+09 | 0.307120E+09 | 0.346606E+09 | 0.716080E+09 |
| April | 0.612408E+09 | 0.271325E+09 | 0.341083E+09 | 0.577064E+09 | 0.480668E+09 |
| May | 0.782755E+09 | 0.356978E+09 | 0.425777E+09 | 0.817205E+09 | 0.407234E+09 |
| June | 0.824137E+09 | 0.378557E+09 | 0.445580E+09 | 0.989492E+09 | 0.274167E+09 |
| July | 0.872377E+09 | 0.440825E+09 | 0.431552E+09 | 0.117618E+10 | 0.221773E+09 |
| August | 0.740766E+09 | 0.363552E+09 | 0.377214E+09 | 0.958407E+09 | 0.251018E+09 |
| September | 0.576677E+09 | 0.291545E+09 | 0.285133E+09 | 0.645561E+09 | 0.389494E+09 |
| October | 0.425905E+09 | 0.211609E+09 | 0.214296E+09 | 0.365521E+09 | 0.588150E+09 |
| November | 0.291774E+09 | 0.144745E+09 | 0.147029E+09 | 0.194096E+09 | 0.744397E+09 |
| December | 0.202663E+09 | 85538378.79 | 0.117125E+09 | 87575735.65 | 0.101742E+10 |
| Annual Sum or Average | 0.637822E+10 | 0.297989E+10 | 0.339834E+10 | 0.648694E+10 | 0.709351E+10 |
| Minimum of Months | 0.202663E+09 | 85538378.79 | 0.117125E+09 | 87575735.65 | 0.221773E+09 |
| Maximum of Months | 0.872377E+09 | 0.440825E+09 | 0.445580E+09 | 0.117618E+10 | 0.121767E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.110316E+09 | 79713530.58 | 30602899.11 | 98631631.78 | 0.163990E+09 |
| February | 0.129774E+09 | 95211964.57 | 34561670.35 | 0.130521E+09 | 0.107060E+09 |
| March | 0.127670E+09 | 73973192.23 | 53696944.30 | 0.126586E+09 | 0.104571E+09 |
| April | 97914021.51 | 49030467.10 | 48883554.41 | 0.103096E+09 | 74455696.31 |
| May | 88230467.99 | 31257195.49 | 56973272.50 | 92252509.55 | 64405320.42 |
| June | 83756562.22 | 26392172.21 | 57364390.02 | 0.103787E+09 | 43804928.18 |
| July | 94340451.99 | 37239985.02 | 57100466.97 | 0.136632E+09 | 33438810.43 |
| August | 0.114206E+09 | 60405818.54 | 53800166.56 | 0.158477E+09 | 38352807.79 |
| September | 0.124362E+09 | 78791212.26 | 45571276.22 | 0.153782E+09 | 57899065.74 |
| October | 0.135266E+09 | 95660076.19 | 39605436.36 | 0.149531E+09 | 83951116.54 |
| November | 0.118421E+09 | 87306356.49 | 31114627.41 | 0.118798E+09 | 0.100830E+09 |
| December | 0.103469E+09 | 75829578.12 | 27639451.51 | 96081075.20 | 0.138990E+09 |
| Annual Sum or Average | 0.132773E+10 | 0.790812E+09 | 0.536914E+09 | 0.146818E+10 | 0.101175E+10 |
| Minimum of Months | 83756562.22 | 26392172.21 | 27639451.51 | 92252509.55 | 33438810.43 |
| Maximum of Months | 0.135266E+09 | 95660076.19 | 57364390.02 | 0.158477E+09 | 0.163990E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.759364E+09 | 0.552973E+09 | 0.206391E+09 | 0.678818E+09 | 0.113479E+10 |
| February | 0.892466E+09 | 0.660799E+09 | 0.231667E+09 | 0.897392E+09 | 0.740076E+09 |
| March | 0.873013E+09 | 0.513395E+09 | 0.359617E+09 | 0.864640E+09 | 0.723814E+09 |
| April | 0.664754E+09 | 0.340286E+09 | 0.324468E+09 | 0.700542E+09 | 0.516050E+09 |
| May | 0.593402E+09 | 0.216934E+09 | 0.376468E+09 | 0.619732E+09 | 0.449256E+09 |
| June | 0.559597E+09 | 0.183169E+09 | 0.376428E+09 | 0.693815E+09 | 0.305150E+09 |
| July | 0.633903E+09 | 0.258456E+09 | 0.375447E+09 | 0.922394E+09 | 0.230173E+09 |
| August | 0.774574E+09 | 0.419234E+09 | 0.355341E+09 | 0.107911E+10 | 0.264088E+09 |
| September | 0.849513E+09 | 0.546834E+09 | 0.302679E+09 | 0.105198E+10 | 0.399409E+09 |
| October | 0.928716E+09 | 0.663909E+09 | 0.264808E+09 | 0.102698E+10 | 0.579032E+09 |
| November | 0.814870E+09 | 0.605773E+09 | 0.209097E+09 | 0.817587E+09 | 0.695898E+09 |
| December | 0.709233E+09 | 0.523638E+09 | 0.185595E+09 | 0.657768E+09 | 0.961266E+09 |
| Annual Sum or Average | 0.905341E+10 | 0.548540E+10 | 0.356801E+10 | 0.100107E+11 | 0.699900E+10 |
| Minimum of Months | 0.559597E+09 | 0.183169E+09 | 0.185595E+09 | 0.619732E+09 | 0.230173E+09 |
| Maximum of Months | 0.928716E+09 | 0.663909E+09 | 0.376468E+09 | 0.107911E+10 | 0.113479E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.135892E+10 | 0.991265E+09 | 0.367650E+09 | 0.121310E+10 | 0.216335E+10 |
| February | 0.163078E+10 | 0.121298E+10 | 0.417799E+09 | 0.162581E+10 | 0.142265E+10 |
| March | 0.159249E+10 | 0.943271E+09 | 0.649218E+09 | 0.155668E+10 | 0.141425E+10 |
| April | 0.120848E+10 | 0.625326E+09 | 0.583151E+09 | 0.124930E+10 | 0.103553E+10 |
| May | 0.107368E+10 | 0.398649E+09 | 0.675036E+09 | 0.111074E+10 | 0.884967E+09 |
| June | 0.100912E+10 | 0.336601E+09 | 0.672523E+09 | 0.125188E+10 | 0.590331E+09 |
| July | 0.114643E+10 | 0.474952E+09 | 0.671474E+09 | 0.169357E+10 | 0.421327E+09 |
| August | 0.140741E+10 | 0.770405E+09 | 0.637005E+09 | 0.197798E+10 | 0.492032E+09 |
| September | 0.154906E+10 | 0.100489E+10 | 0.544172E+09 | 0.192114E+10 | 0.766220E+09 |
| October | 0.169568E+10 | 0.121868E+10 | 0.477007E+09 | 0.186449E+10 | 0.112855E+10 |
| November | 0.147036E+10 | 0.109820E+10 | 0.372156E+09 | 0.146566E+10 | 0.136480E+10 |
| December | 0.124269E+10 | 0.920910E+09 | 0.321783E+09 | 0.115586E+10 | 0.186999E+10 |
| Annual Sum or Average | 0.163851E+11 | 0.999612E+10 | 0.638898E+10 | 0.180862E+11 | 0.135540E+11 |
| Minimum of Months | 0.100912E+10 | 0.336601E+09 | 0.321783E+09 | 0.111074E+10 | 0.421327E+09 |
| Maximum of Months | 0.169568E+10 | 0.121868E+10 | 0.675036E+09 | 0.197798E+10 | 0.216335E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.135518E+10 | 0.988299E+09 | 0.366877E+09 | 0.121302E+10 | 0.216856E+10 |
| February | 0.162300E+10 | 0.120768E+10 | 0.415325E+09 | 0.162319E+10 | 0.143242E+10 |
| March | 0.159118E+10 | 0.942458E+09 | 0.648717E+09 | 0.155635E+10 | 0.141603E+10 |
| April | 0.120840E+10 | 0.625285E+09 | 0.583113E+09 | 0.124922E+10 | 0.103547E+10 |
| May | 0.107361E+10 | 0.398623E+09 | 0.674991E+09 | 0.111067E+10 | 0.884909E+09 |
| June | 0.100906E+10 | 0.336579E+09 | 0.672478E+09 | 0.125180E+10 | 0.590293E+09 |
| July | 0.114635E+10 | 0.474921E+09 | 0.671429E+09 | 0.169345E+10 | 0.421299E+09 |
| August | 0.140732E+10 | 0.770355E+09 | 0.636962E+09 | 0.197785E+10 | 0.492000E+09 |
| September | 0.154881E+10 | 0.100476E+10 | 0.544051E+09 | 0.192101E+10 | 0.766411E+09 |
| October | 0.169288E+10 | 0.121698E+10 | 0.475904E+09 | 0.186395E+10 | 0.113250E+10 |
| November | 0.146157E+10 | 0.109163E+10 | 0.369932E+09 | 0.146409E+10 | 0.137637E+10 |
| December | 0.124069E+10 | 0.919460E+09 | 0.321235E+09 | 0.115578E+10 | 0.187264E+10 |
| Annual Sum or Average | 0.163580E+11 | 0.997703E+10 | 0.638101E+10 | 0.180804E+11 | 0.135889E+11 |
| Minimum of Months | 0.100906E+10 | 0.336579E+09 | 0.321235E+09 | 0.111067E+10 | 0.421299E+09 |
| Maximum of Months | 0.169288E+10 | 0.121698E+10 | 0.674991E+09 | 0.197785E+10 | 0.216856E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1_WALL_1_WINDOW3
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.124825E+10 | 0.905817E+09 | 0.342429E+09 | 0.108789E+10 | 0.217982E+10 |
| February | 0.150299E+10 | 0.111783E+10 | 0.385165E+09 | 0.148385E+10 | 0.145292E+10 |
| March | 0.150429E+10 | 0.891937E+09 | 0.612357E+09 | 0.145386E+10 | 0.142994E+10 |
| April | 0.115724E+10 | 0.602615E+09 | 0.554629E+09 | 0.118630E+10 | 0.103797E+10 |
| May | 0.103240E+10 | 0.389573E+09 | 0.642823E+09 | 0.106253E+10 | 0.887444E+09 |
| June | 0.969802E+09 | 0.329281E+09 | 0.640521E+09 | 0.120409E+10 | 0.590171E+09 |
| July | 0.110440E+10 | 0.463634E+09 | 0.640768E+09 | 0.163852E+10 | 0.416823E+09 |
| August | 0.135221E+10 | 0.745536E+09 | 0.606675E+09 | 0.190226E+10 | 0.488155E+09 |
| September | 0.147538E+10 | 0.961134E+09 | 0.514247E+09 | 0.182436E+10 | 0.768922E+09 |
| October | 0.157644E+10 | 0.113283E+10 | 0.443609E+09 | 0.172179E+10 | 0.114715E+10 |
| November | 0.135422E+10 | 0.101064E+10 | 0.343579E+09 | 0.133580E+10 | 0.138619E+10 |
| December | 0.114766E+10 | 0.848887E+09 | 0.298768E+09 | 0.104441E+10 | 0.187745E+10 |
| Annual Sum or Average | 0.154253E+11 | 0.939972E+10 | 0.602557E+10 | 0.169457E+11 | 0.136629E+11 |
| Minimum of Months | 0.969802E+09 | 0.329281E+09 | 0.298768E+09 | 0.104441E+10 | 0.416823E+09 |
| Maximum of Months | 0.157644E+10 | 0.113283E+10 | 0.642823E+09 | 0.190226E+10 | 0.217982E+10 |
Report: WindowEnergyReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1_WALL_7_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 73970815.50 | 29810793.60 | 44160021.90 | 31175900.39 | 0.429935E+09 |
| February | 0.114039E+09 | 56055770.97 | 57982836.54 | 79108503.64 | 0.279074E+09 |
| March | 0.161578E+09 | 59204732.84 | 0.102374E+09 | 0.114477E+09 | 0.258905E+09 |
| April | 0.204137E+09 | 90442042.89 | 0.113695E+09 | 0.189371E+09 | 0.178547E+09 |
| May | 0.260919E+09 | 0.118993E+09 | 0.141926E+09 | 0.268904E+09 | 0.151058E+09 |
| June | 0.274713E+09 | 0.126186E+09 | 0.148527E+09 | 0.325808E+09 | 0.100362E+09 |
| July | 0.290793E+09 | 0.146942E+09 | 0.143851E+09 | 0.392514E+09 | 76219859.44 |
| August | 0.246923E+09 | 0.121185E+09 | 0.125738E+09 | 0.321962E+09 | 85256782.72 |
| September | 0.192226E+09 | 97181884.34 | 95044555.50 | 0.217752E+09 | 0.135269E+09 |
| October | 0.141969E+09 | 70536604.45 | 71432123.70 | 0.123998E+09 | 0.204966E+09 |
| November | 97258402.11 | 48248465.95 | 49009936.16 | 66103852.73 | 0.261923E+09 |
| December | 67554597.73 | 28512887.97 | 39041709.75 | 29101723.37 | 0.359773E+09 |
| Annual Sum or Average | 0.212608E+10 | 0.993299E+09 | 0.113278E+10 | 0.216028E+10 | 0.252129E+10 |
| Minimum of Months | 67554597.73 | 28512887.97 | 39041709.75 | 29101723.37 | 76219859.44 |
| Maximum of Months | 0.290793E+09 | 0.146942E+09 | 0.148527E+09 | 0.392514E+09 | 0.429935E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 16422862.97 | 0.00 | 16422862.97 | 279199.67 | 0.191678E+09 |
| February | 20944049.87 | 0.00 | 20944049.87 | 2972652.32 | 0.125060E+09 |
| March | 37667986.22 | 0.00 | 37667986.22 | 9354434.78 | 0.108647E+09 |
| April | 41564017.89 | 242556.78 | 41321461.11 | 19605158.75 | 71403475.53 |
| May | 56402927.76 | 3342202.32 | 53060725.44 | 36971974.39 | 58346701.45 |
| June | 63559449.84 | 7305571.90 | 56253877.94 | 61574493.61 | 37034580.60 |
| July | 60000575.14 | 5619734.52 | 54380840.61 | 75799411.48 | 29549936.47 |
| August | 48078791.36 | 1288726.60 | 46790064.76 | 55237576.33 | 33766078.45 |
| September | 34846135.05 | 12504.59 | 34833630.46 | 27665849.09 | 55497045.47 |
| October | 26265485.32 | 0.00 | 26265485.32 | 7913119.81 | 85542776.73 |
| November | 17279539.33 | 0.00 | 17279539.33 | 1593676.05 | 0.114983E+09 |
| December | 13771496.99 | 0.00 | 13771496.99 | 77530.53 | 0.161208E+09 |
| Annual Sum or Average | 0.436803E+09 | 17811296.72 | 0.418992E+09 | 0.299045E+09 | 0.107272E+10 |
| Minimum of Months | 13771496.99 | 0.00 | 13771496.99 | 77530.53 | 29549936.47 |
| Maximum of Months | 63559449.84 | 7305571.90 | 56253877.94 | 75799411.48 | 0.191678E+09 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_4_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.221912E+09 | 89432082.68 | 0.132480E+09 | 0.100916E+09 | 0.119959E+10 |
| February | 0.342115E+09 | 0.168167E+09 | 0.173948E+09 | 0.252383E+09 | 0.757625E+09 |
| March | 0.484733E+09 | 0.177614E+09 | 0.307120E+09 | 0.366098E+09 | 0.687864E+09 |
| April | 0.612408E+09 | 0.271325E+09 | 0.341083E+09 | 0.597986E+09 | 0.457323E+09 |
| May | 0.782755E+09 | 0.356978E+09 | 0.425777E+09 | 0.829925E+09 | 0.395673E+09 |
| June | 0.824137E+09 | 0.378557E+09 | 0.445580E+09 | 0.996835E+09 | 0.269125E+09 |
| July | 0.872377E+09 | 0.440825E+09 | 0.431552E+09 | 0.119259E+10 | 0.209995E+09 |
| August | 0.740766E+09 | 0.363552E+09 | 0.377214E+09 | 0.984257E+09 | 0.230235E+09 |
| September | 0.576677E+09 | 0.291545E+09 | 0.285133E+09 | 0.671551E+09 | 0.357941E+09 |
| October | 0.425905E+09 | 0.211609E+09 | 0.214296E+09 | 0.391010E+09 | 0.540457E+09 |
| November | 0.291774E+09 | 0.144745E+09 | 0.147029E+09 | 0.211322E+09 | 0.702655E+09 |
| December | 0.202663E+09 | 85538378.79 | 0.117125E+09 | 95636180.82 | 0.995390E+09 |
| Annual Sum or Average | 0.637822E+10 | 0.297989E+10 | 0.339834E+10 | 0.669051E+10 | 0.680387E+10 |
| Minimum of Months | 0.202663E+09 | 85538378.79 | 0.117125E+09 | 95636180.82 | 0.209995E+09 |
| Maximum of Months | 0.872377E+09 | 0.440825E+09 | 0.445580E+09 | 0.119259E+10 | 0.119959E+10 |
Report: WindowEnergyReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.113526E+09 | 0.00 | 0.113526E+09 | 1955863.87 | 0.132270E+10 |
| February | 0.144779E+09 | 0.00 | 0.144779E+09 | 21260750.08 | 0.862374E+09 |
| March | 0.260386E+09 | 0.00 | 0.260386E+09 | 65361743.29 | 0.750161E+09 |
| April | 0.287318E+09 | 1676709.54 | 0.285641E+09 | 0.136254E+09 | 0.493547E+09 |
| May | 0.389894E+09 | 23103466.97 | 0.366791E+09 | 0.255901E+09 | 0.403314E+09 |
| June | 0.439365E+09 | 50500844.35 | 0.388864E+09 | 0.425899E+09 | 0.256008E+09 |
| July | 0.414764E+09 | 38847244.56 | 0.375916E+09 | 0.524370E+09 | 0.204269E+09 |
| August | 0.332352E+09 | 8908512.88 | 0.323444E+09 | 0.382657E+09 | 0.233413E+09 |
| September | 0.240879E+09 | 86439.86 | 0.240793E+09 | 0.192613E+09 | 0.383408E+09 |
| October | 0.181564E+09 | 0.00 | 0.181564E+09 | 55894727.75 | 0.589732E+09 |
| November | 0.119448E+09 | 0.00 | 0.119448E+09 | 11257757.81 | 0.791891E+09 |
| December | 95197636.64 | 0.00 | 95197636.64 | 539871.36 | 0.111180E+10 |
| Annual Sum or Average | 0.301947E+10 | 0.123123E+09 | 0.289635E+10 | 0.207397E+10 | 0.740262E+10 |
| Minimum of Months | 95197636.64 | 0.00 | 95197636.64 | 539871.36 | 0.204269E+09 |
| Maximum of Months | 0.439365E+09 | 50500844.35 | 0.388864E+09 | 0.524370E+09 | 0.132270E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.138308E+09 | 0.00 | 0.138308E+09 | 1556790.89 | 0.165087E+10 |
| February | 0.176384E+09 | 0.00 | 0.176384E+09 | 21343578.72 | 0.108969E+10 |
| March | 0.317228E+09 | 0.00 | 0.317228E+09 | 69551911.65 | 0.963980E+09 |
| April | 0.350039E+09 | 2042734.51 | 0.347997E+09 | 0.150202E+09 | 0.654037E+09 |
| May | 0.475008E+09 | 28146943.84 | 0.446861E+09 | 0.302066E+09 | 0.525678E+09 |
| June | 0.535278E+09 | 61525156.87 | 0.473753E+09 | 0.513796E+09 | 0.326489E+09 |
| July | 0.505306E+09 | 47327581.28 | 0.457979E+09 | 0.652607E+09 | 0.245836E+09 |
| August | 0.404905E+09 | 10853237.40 | 0.394052E+09 | 0.477369E+09 | 0.284960E+09 |
| September | 0.293463E+09 | 105309.64 | 0.293358E+09 | 0.233840E+09 | 0.484466E+09 |
| October | 0.221200E+09 | 0.00 | 0.221200E+09 | 60812042.24 | 0.762001E+09 |
| November | 0.145523E+09 | 0.00 | 0.145523E+09 | 10698439.26 | 0.101564E+10 |
| December | 0.115979E+09 | 0.00 | 0.115979E+09 | 501988.66 | 0.140139E+10 |
| Annual Sum or Average | 0.367862E+10 | 0.150001E+09 | 0.352862E+10 | 0.249434E+10 | 0.940503E+10 |
| Minimum of Months | 0.115979E+09 | 0.00 | 0.115979E+09 | 501988.66 | 0.245836E+09 |
| Maximum of Months | 0.535278E+09 | 61525156.87 | 0.473753E+09 | 0.652607E+09 | 0.165087E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.138307E+09 | 0.00 | 0.138307E+09 | 1556724.94 | 0.165087E+10 |
| February | 0.176383E+09 | 0.00 | 0.176383E+09 | 21343315.89 | 0.108969E+10 |
| March | 0.317226E+09 | 0.00 | 0.317226E+09 | 69550681.43 | 0.963981E+09 |
| April | 0.350037E+09 | 2042715.63 | 0.347994E+09 | 0.150201E+09 | 0.654037E+09 |
| May | 0.475005E+09 | 28146683.71 | 0.446858E+09 | 0.302063E+09 | 0.525679E+09 |
| June | 0.535275E+09 | 61524588.28 | 0.473750E+09 | 0.513792E+09 | 0.326489E+09 |
| July | 0.505303E+09 | 47327143.90 | 0.457976E+09 | 0.652603E+09 | 0.245835E+09 |
| August | 0.404903E+09 | 10853137.10 | 0.394049E+09 | 0.477366E+09 | 0.284959E+09 |
| September | 0.293462E+09 | 105308.67 | 0.293356E+09 | 0.233839E+09 | 0.484466E+09 |
| October | 0.221198E+09 | 0.00 | 0.221198E+09 | 60811284.45 | 0.762001E+09 |
| November | 0.145522E+09 | 0.00 | 0.145522E+09 | 10698174.83 | 0.101564E+10 |
| December | 0.115978E+09 | 0.00 | 0.115978E+09 | 501968.85 | 0.140139E+10 |
| Annual Sum or Average | 0.367860E+10 | 0.150000E+09 | 0.352860E+10 | 0.249433E+10 | 0.940503E+10 |
| Minimum of Months | 0.115978E+09 | 0.00 | 0.115978E+09 | 501968.85 | 0.245835E+09 |
| Maximum of Months | 0.535275E+09 | 61524588.28 | 0.473750E+09 | 0.652603E+09 | 0.165087E+10 |
Report: WindowEnergyReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1_WALL_3_WINDOW3
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.138303E+09 | 0.00 | 0.138303E+09 | 1556713.75 | 0.165082E+10 |
| February | 0.176378E+09 | 0.00 | 0.176378E+09 | 21342764.81 | 0.108965E+10 |
| March | 0.317217E+09 | 0.00 | 0.317217E+09 | 69549117.35 | 0.963948E+09 |
| April | 0.350027E+09 | 2042659.00 | 0.347984E+09 | 0.150197E+09 | 0.654015E+09 |
| May | 0.474991E+09 | 28145903.35 | 0.446845E+09 | 0.302055E+09 | 0.525661E+09 |
| June | 0.535259E+09 | 61522882.52 | 0.473736E+09 | 0.513777E+09 | 0.326478E+09 |
| July | 0.505288E+09 | 47325831.76 | 0.457962E+09 | 0.652584E+09 | 0.245827E+09 |
| August | 0.404890E+09 | 10852836.20 | 0.394038E+09 | 0.477352E+09 | 0.284950E+09 |
| September | 0.293453E+09 | 105305.75 | 0.293348E+09 | 0.233832E+09 | 0.484450E+09 |
| October | 0.221192E+09 | 0.00 | 0.221192E+09 | 60809719.86 | 0.761976E+09 |
| November | 0.145518E+09 | 0.00 | 0.145518E+09 | 10697980.87 | 0.101560E+10 |
| December | 0.115975E+09 | 0.00 | 0.115975E+09 | 501964.33 | 0.140134E+10 |
| Annual Sum or Average | 0.367849E+10 | 0.149995E+09 | 0.352850E+10 | 0.249425E+10 | 0.940472E+10 |
| Minimum of Months | 0.115975E+09 | 0.00 | 0.115975E+09 | 501964.33 | 0.245827E+09 |
| Maximum of Months | 0.535259E+09 | 61522882.52 | 0.473736E+09 | 0.652584E+09 | 0.165082E+10 |
Report: WindowEnergyReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 15596356.48 | 0.00 | 15596356.48 | 138271.11 | 0.188166E+09 |
| February | 19889991.19 | 0.00 | 19889991.19 | 2134299.67 | 0.125448E+09 |
| March | 35772276.22 | 0.00 | 35772276.22 | 6959212.57 | 0.112870E+09 |
| April | 39472215.16 | 230351.02 | 39241864.14 | 15173592.24 | 79152251.29 |
| May | 53564339.75 | 3174018.58 | 50390321.17 | 31875233.73 | 63401020.58 |
| June | 60360685.84 | 6937946.52 | 53422739.32 | 56010432.30 | 39195516.58 |
| July | 56980872.20 | 5336942.56 | 51643929.64 | 70176914.78 | 30235337.08 |
| August | 45659072.61 | 1223876.29 | 44435196.32 | 50593554.45 | 35402445.82 |
| September | 33092401.75 | 11875.35 | 33080526.40 | 24647238.19 | 59491889.12 |
| October | 24943614.48 | 0.00 | 24943614.48 | 6014718.15 | 91820454.34 |
| November | 16409913.64 | 0.00 | 16409913.64 | 889353.87 | 0.119784E+09 |
| December | 13078426.88 | 0.00 | 13078426.88 | 43398.44 | 0.161026E+09 |
| Annual Sum or Average | 0.414820E+09 | 16915010.32 | 0.397905E+09 | 0.264656E+09 | 0.110599E+10 |
| Minimum of Months | 13078426.88 | 0.00 | 13078426.88 | 43398.44 | 30235337.08 |
| Maximum of Months | 60360685.84 | 6937946.52 | 53422739.32 | 70176914.78 | 0.188166E+09 |
Report: WindowEnergyReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1_WALL_3_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.197789E+09 | 0.00 | 0.197789E+09 | 1753520.89 | 0.238627E+10 |
| February | 0.252240E+09 | 0.00 | 0.252240E+09 | 27066673.01 | 0.159091E+10 |
| March | 0.453655E+09 | 0.00 | 0.453655E+09 | 88255053.41 | 0.143139E+10 |
| April | 0.500577E+09 | 2921256.05 | 0.497656E+09 | 0.192428E+09 | 0.100379E+10 |
| May | 0.679290E+09 | 40252137.22 | 0.639038E+09 | 0.404234E+09 | 0.804036E+09 |
| June | 0.765480E+09 | 87985362.50 | 0.677494E+09 | 0.710311E+09 | 0.497068E+09 |
| July | 0.722618E+09 | 67681816.79 | 0.654936E+09 | 0.889967E+09 | 0.383437E+09 |
| August | 0.579037E+09 | 15520903.57 | 0.563516E+09 | 0.641615E+09 | 0.448965E+09 |
| September | 0.419670E+09 | 150600.30 | 0.419519E+09 | 0.312570E+09 | 0.754462E+09 |
| October | 0.316329E+09 | 0.00 | 0.316329E+09 | 76277203.18 | 0.116444E+10 |
| November | 0.208107E+09 | 0.00 | 0.208107E+09 | 11278571.03 | 0.151907E+10 |
| December | 0.165857E+09 | 0.00 | 0.165857E+09 | 550368.49 | 0.204210E+10 |
| Annual Sum or Average | 0.526065E+10 | 0.214512E+09 | 0.504614E+10 | 0.335631E+10 | 0.140259E+11 |
| Minimum of Months | 0.165857E+09 | 0.00 | 0.165857E+09 | 550368.49 | 0.383437E+09 |
| Maximum of Months | 0.765480E+09 | 87985362.50 | 0.677494E+09 | 0.889967E+09 | 0.238627E+10 |
Report: WindowEnergyReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 23473809.37 | 9113298.55 | 14360510.82 | 8857219.22 | 0.201355E+09 |
| February | 43654977.06 | 23714314.50 | 19940662.56 | 32339494.83 | 0.131037E+09 |
| March | 64293016.61 | 27863606.95 | 36429409.66 | 47553976.89 | 0.122786E+09 |
| April | 79471904.90 | 40036077.79 | 39435827.11 | 74734096.85 | 87937166.12 |
| May | 86575786.48 | 39574696.53 | 47001089.96 | 86256096.40 | 77349732.41 |
| June | 90693213.68 | 40828086.37 | 49865127.31 | 0.106965E+09 | 51793621.46 |
| July | 0.102629E+09 | 52992500.76 | 49636238.82 | 0.139849E+09 | 37296956.43 |
| August | 93380936.39 | 49321607.44 | 44059328.95 | 0.123703E+09 | 41469006.14 |
| September | 78983526.54 | 45015947.53 | 33967579.00 | 92416827.37 | 63754669.73 |
| October | 57088518.32 | 32092248.49 | 24996269.83 | 53502923.60 | 92972539.71 |
| November | 33702096.41 | 17678732.59 | 16023363.82 | 24122399.65 | 0.120039E+09 |
| December | 18574678.51 | 6833303.47 | 11741375.04 | 6277512.18 | 0.170043E+09 |
| Annual Sum or Average | 0.772521E+09 | 0.385064E+09 | 0.387457E+09 | 0.796578E+09 | 0.119783E+10 |
| Minimum of Months | 18574678.51 | 6833303.47 | 11741375.04 | 6277512.18 | 37296956.43 |
| Maximum of Months | 0.102629E+09 | 52992500.76 | 49865127.31 | 0.139849E+09 | 0.201355E+09 |
Report: WindowEnergyReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1_WALL_7_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 75901669.63 | 5656992.21 | 70244677.42 | 550190.28 | 0.110620E+10 |
| February | 0.133028E+09 | 38388689.50 | 94639596.54 | 42973853.56 | 0.718428E+09 |
| March | 0.277857E+09 | 88065804.43 | 0.189792E+09 | 0.152740E+09 | 0.651585E+09 |
| April | 0.417177E+09 | 0.193527E+09 | 0.223650E+09 | 0.369606E+09 | 0.458307E+09 |
| May | 0.552778E+09 | 0.269710E+09 | 0.283069E+09 | 0.561028E+09 | 0.396810E+09 |
| June | 0.578270E+09 | 0.285532E+09 | 0.292738E+09 | 0.683710E+09 | 0.269062E+09 |
| July | 0.637822E+09 | 0.348108E+09 | 0.289714E+09 | 0.858301E+09 | 0.200304E+09 |
| August | 0.511156E+09 | 0.263368E+09 | 0.247788E+09 | 0.662801E+09 | 0.221031E+09 |
| September | 0.363180E+09 | 0.181993E+09 | 0.181187E+09 | 0.398713E+09 | 0.338253E+09 |
| October | 0.197092E+09 | 74129270.15 | 0.122963E+09 | 0.130419E+09 | 0.502029E+09 |
| November | 91481357.64 | 16693560.07 | 74787797.58 | 13318512.74 | 0.661988E+09 |
| December | 59005694.77 | 2108709.97 | 56896984.80 | 35268.03 | 0.941406E+09 |
| Annual Sum or Average | 0.389475E+10 | 0.176728E+10 | 0.212747E+10 | 0.387420E+10 | 0.646540E+10 |
| Minimum of Months | 59005694.77 | 2108709.97 | 56896984.80 | 35268.03 | 0.200304E+09 |
| Maximum of Months | 0.637822E+09 | 0.348108E+09 | 0.292738E+09 | 0.858301E+09 | 0.110620E+10 |
Report: WindowEnergyReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.109484E+09 | 78195532.10 | 31288288.05 | 0.101435E+09 | 0.140951E+09 |
| February | 0.125933E+09 | 90575843.88 | 35357338.79 | 0.130659E+09 | 95293958.41 |
| March | 0.124629E+09 | 69985738.67 | 54642933.46 | 0.127366E+09 | 95554920.48 |
| April | 96948937.94 | 46371300.52 | 50577637.41 | 0.104156E+09 | 69137539.62 |
| May | 89007891.70 | 29561962.01 | 59445929.69 | 96279928.44 | 59066815.16 |
| June | 85585424.06 | 24960793.18 | 60624630.88 | 0.106379E+09 | 41898434.41 |
| July | 95345348.38 | 35220275.04 | 60125073.34 | 0.134654E+09 | 34074683.47 |
| August | 0.113312E+09 | 57129709.97 | 56181978.73 | 0.155741E+09 | 37774476.48 |
| September | 0.121622E+09 | 74521853.98 | 47100343.38 | 0.151833E+09 | 54066003.31 |
| October | 0.131388E+09 | 90852996.41 | 40534815.16 | 0.148900E+09 | 76187972.21 |
| November | 0.115923E+09 | 83969730.75 | 31952953.81 | 0.119256E+09 | 89668738.21 |
| December | 0.104113E+09 | 75180085.64 | 28932886.19 | 98367150.84 | 0.120883E+09 |
| Annual Sum or Average | 0.131329E+10 | 0.756526E+09 | 0.556765E+09 | 0.147503E+10 | 0.914558E+09 |
| Minimum of Months | 85585424.06 | 24960793.18 | 28932886.19 | 96279928.44 | 34074683.47 |
| Maximum of Months | 0.131388E+09 | 90852996.41 | 60624630.88 | 0.155741E+09 | 0.140951E+09 |
Report: WindowEnergyReportMonthly
For: LOBBY_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.147825E+10 | 0.105579E+10 | 0.422453E+09 | 0.136957E+10 | 0.190312E+10 |
| February | 0.170035E+10 | 0.122295E+10 | 0.477394E+09 | 0.176416E+10 | 0.128666E+10 |
| March | 0.168273E+10 | 0.944945E+09 | 0.737787E+09 | 0.171969E+10 | 0.129018E+10 |
| April | 0.130900E+10 | 0.626104E+09 | 0.682898E+09 | 0.140631E+10 | 0.933493E+09 |
| May | 0.120178E+10 | 0.399145E+09 | 0.802637E+09 | 0.129997E+10 | 0.797518E+09 |
| June | 0.115557E+10 | 0.337020E+09 | 0.818552E+09 | 0.143632E+10 | 0.565711E+09 |
| July | 0.128735E+10 | 0.475543E+09 | 0.811807E+09 | 0.181810E+10 | 0.460075E+09 |
| August | 0.152993E+10 | 0.771364E+09 | 0.758567E+09 | 0.210281E+10 | 0.510030E+09 |
| September | 0.164214E+10 | 0.100619E+10 | 0.635947E+09 | 0.205005E+10 | 0.729997E+09 |
| October | 0.177399E+10 | 0.122669E+10 | 0.547300E+09 | 0.201044E+10 | 0.102869E+10 |
| November | 0.156518E+10 | 0.113376E+10 | 0.431428E+09 | 0.161020E+10 | 0.121070E+10 |
| December | 0.140573E+10 | 0.101508E+10 | 0.390651E+09 | 0.132815E+10 | 0.163216E+10 |
| Annual Sum or Average | 0.177320E+11 | 0.102146E+11 | 0.751742E+10 | 0.199158E+11 | 0.123483E+11 |
| Minimum of Months | 0.115557E+10 | 0.337020E+09 | 0.390651E+09 | 0.129997E+10 | 0.460075E+09 |
| Maximum of Months | 0.177399E+10 | 0.122669E+10 | 0.818552E+09 | 0.210281E+10 | 0.190312E+10 |
Report: WindowEnergyReportMonthly
For: BATH_ZN_1_FLR_1_WALL_5_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.127823E+09 | 27726321.49 | 0.100097E+09 | 15504182.24 | 0.132595E+10 |
| February | 0.228600E+09 | 92995772.55 | 0.135604E+09 | 0.124293E+09 | 0.854981E+09 |
| March | 0.408087E+09 | 0.145407E+09 | 0.262680E+09 | 0.263411E+09 | 0.807878E+09 |
| April | 0.569453E+09 | 0.268724E+09 | 0.300729E+09 | 0.516339E+09 | 0.593565E+09 |
| May | 0.723988E+09 | 0.348452E+09 | 0.375536E+09 | 0.727186E+09 | 0.522493E+09 |
| June | 0.756328E+09 | 0.366779E+09 | 0.389549E+09 | 0.866213E+09 | 0.373965E+09 |
| July | 0.836456E+09 | 0.451160E+09 | 0.385296E+09 | 0.110150E+10 | 0.285192E+09 |
| August | 0.689859E+09 | 0.357149E+09 | 0.332710E+09 | 0.880377E+09 | 0.307122E+09 |
| September | 0.516886E+09 | 0.269438E+09 | 0.247447E+09 | 0.567861E+09 | 0.460074E+09 |
| October | 0.318266E+09 | 0.144547E+09 | 0.173718E+09 | 0.246268E+09 | 0.657328E+09 |
| November | 0.167164E+09 | 58973517.77 | 0.108191E+09 | 67627471.37 | 0.818237E+09 |
| December | 0.100312E+09 | 18903554.67 | 81408890.99 | 7476225.43 | 0.112894E+10 |
| Annual Sum or Average | 0.544322E+10 | 0.255026E+10 | 0.289297E+10 | 0.538406E+10 | 0.813573E+10 |
| Minimum of Months | 0.100312E+09 | 18903554.67 | 81408890.99 | 7476225.43 | 0.285192E+09 |
| Maximum of Months | 0.836456E+09 | 0.451160E+09 | 0.389549E+09 | 0.110150E+10 | 0.132595E+10 |
Report: WindowEnergyReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.571650E+09 | 0.262078E+09 | 0.309572E+09 | 0.251459E+09 | 0.274055E+10 |
| February | 0.807585E+09 | 0.400946E+09 | 0.406638E+09 | 0.556044E+09 | 0.182654E+10 |
| March | 0.120221E+10 | 0.497443E+09 | 0.704772E+09 | 0.884782E+09 | 0.166630E+10 |
| April | 0.148443E+10 | 0.735671E+09 | 0.748756E+09 | 0.136282E+10 | 0.118953E+10 |
| May | 0.169440E+10 | 0.753902E+09 | 0.940499E+09 | 0.166489E+10 | 0.101007E+10 |
| June | 0.212243E+10 | 0.109220E+10 | 0.103023E+10 | 0.248533E+10 | 0.659033E+09 |
| July | 0.230181E+10 | 0.130127E+10 | 0.100053E+10 | 0.298883E+10 | 0.535797E+09 |
| August | 0.200037E+10 | 0.111454E+10 | 0.885827E+09 | 0.251717E+10 | 0.608791E+09 |
| September | 0.136942E+10 | 0.706889E+09 | 0.662530E+09 | 0.148215E+10 | 0.914166E+09 |
| October | 0.101524E+10 | 0.515521E+09 | 0.499715E+09 | 0.848694E+09 | 0.135382E+10 |
| November | 0.622681E+09 | 0.290710E+09 | 0.331971E+09 | 0.359427E+09 | 0.171466E+10 |
| December | 0.474572E+09 | 0.203830E+09 | 0.270742E+09 | 0.189577E+09 | 0.233456E+10 |
| Annual Sum or Average | 0.156668E+11 | 0.787501E+10 | 0.779179E+10 | 0.155912E+11 | 0.165538E+11 |
| Minimum of Months | 0.474572E+09 | 0.203830E+09 | 0.270742E+09 | 0.189577E+09 | 0.535797E+09 |
| Maximum of Months | 0.230181E+10 | 0.130127E+10 | 0.103023E+10 | 0.298883E+10 | 0.274055E+10 |
Report: WindowEnergyReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.108709E+09 | 77642169.58 | 31066871.75 | 96369605.42 | 0.154302E+09 |
| February | 0.125042E+09 | 89934870.21 | 35107127.23 | 0.125500E+09 | 0.102650E+09 |
| March | 0.123747E+09 | 69490474.00 | 54256244.47 | 0.122067E+09 | 0.103335E+09 |
| April | 96262864.10 | 46043147.00 | 50219717.11 | 98597082.39 | 77561631.71 |
| May | 88378013.88 | 29352762.31 | 59025251.57 | 89816958.81 | 67214281.50 |
| June | 84979765.85 | 24784154.35 | 60195611.50 | 0.100783E+09 | 46907518.47 |
| July | 94670622.59 | 34971033.44 | 59699589.15 | 0.130486E+09 | 37037854.61 |
| August | 0.112510E+09 | 56725422.93 | 55784398.45 | 0.151533E+09 | 41387162.78 |
| September | 0.120762E+09 | 73994488.80 | 46767030.67 | 0.147432E+09 | 59448983.24 |
| October | 0.130458E+09 | 90210061.43 | 40247964.41 | 0.143602E+09 | 82588981.22 |
| November | 0.115102E+09 | 83375506.24 | 31726833.89 | 0.114506E+09 | 96181207.19 |
| December | 0.103376E+09 | 74648062.39 | 28728138.25 | 94727007.18 | 0.130454E+09 |
| Annual Sum or Average | 0.130400E+10 | 0.751172E+09 | 0.552825E+09 | 0.141542E+10 | 0.999069E+09 |
| Minimum of Months | 84979765.85 | 24784154.35 | 28728138.25 | 89816958.81 | 37037854.61 |
| Maximum of Months | 0.130458E+09 | 90210061.43 | 60195611.50 | 0.151533E+09 | 0.154302E+09 |
Report: WindowEnergyReportMonthly
For: OFFICES_ZN_1_FLR_1_WALL_1_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.164611E+10 | 0.117569E+10 | 0.470427E+09 | 0.145927E+10 | 0.233651E+10 |
| February | 0.189343E+10 | 0.136183E+10 | 0.531606E+09 | 0.190037E+10 | 0.155436E+10 |
| March | 0.187382E+10 | 0.105225E+10 | 0.821569E+09 | 0.184839E+10 | 0.156475E+10 |
| April | 0.145765E+10 | 0.697203E+09 | 0.760446E+09 | 0.149300E+10 | 0.117417E+10 |
| May | 0.133825E+10 | 0.444471E+09 | 0.893783E+09 | 0.136004E+10 | 0.101680E+10 |
| June | 0.128680E+10 | 0.375291E+09 | 0.911505E+09 | 0.152614E+10 | 0.708651E+09 |
| July | 0.143354E+10 | 0.529545E+09 | 0.903994E+09 | 0.197597E+10 | 0.558958E+09 |
| August | 0.170367E+10 | 0.858958E+09 | 0.844709E+09 | 0.229458E+10 | 0.625975E+09 |
| September | 0.182862E+10 | 0.112045E+10 | 0.708165E+09 | 0.223247E+10 | 0.900183E+09 |
| October | 0.197545E+10 | 0.136600E+10 | 0.609450E+09 | 0.217447E+10 | 0.125059E+10 |
| November | 0.174292E+10 | 0.126250E+10 | 0.480420E+09 | 0.173390E+10 | 0.145641E+10 |
| December | 0.156536E+10 | 0.113035E+10 | 0.435013E+09 | 0.143439E+10 | 0.197539E+10 |
| Annual Sum or Average | 0.197456E+11 | 0.113745E+11 | 0.837109E+10 | 0.214330E+11 | 0.151228E+11 |
| Minimum of Months | 0.128680E+10 | 0.375291E+09 | 0.435013E+09 | 0.136004E+10 | 0.558958E+09 |
| Maximum of Months | 0.197545E+10 | 0.136600E+10 | 0.911505E+09 | 0.229458E+10 | 0.233651E+10 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 65103026.25 | 24952264.22 | 40150762.03 | 22755263.16 | 0.298541E+09 |
| February | 99485030.50 | 53364261.91 | 46120768.60 | 72260845.73 | 0.203809E+09 |
| March | 0.181751E+09 | 84547902.93 | 97202650.84 | 0.164796E+09 | 0.195044E+09 |
| April | 0.226136E+09 | 0.127921E+09 | 98215723.15 | 0.231497E+09 | 0.146220E+09 |
| May | 0.298012E+09 | 0.171059E+09 | 0.126953E+09 | 0.333878E+09 | 0.122959E+09 |
| June | 0.347105E+09 | 0.223792E+09 | 0.123313E+09 | 0.427590E+09 | 87305218.42 |
| July | 0.371944E+09 | 0.261307E+09 | 0.110637E+09 | 0.485185E+09 | 79255863.60 |
| August | 0.304823E+09 | 0.207212E+09 | 97611180.70 | 0.389693E+09 | 85677749.98 |
| September | 0.207270E+09 | 0.131866E+09 | 75403324.72 | 0.242755E+09 | 0.113445E+09 |
| October | 0.132616E+09 | 73732423.58 | 58883367.07 | 0.126838E+09 | 0.164443E+09 |
| November | 73835930.39 | 34352403.97 | 39483526.42 | 45853922.55 | 0.200376E+09 |
| December | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 0.263554E+09 |
| Annual Sum or Average | 0.235954E+10 | 0.141275E+10 | 0.946789E+09 | 0.255784E+10 | 0.196063E+10 |
| Minimum of Months | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 79255863.60 |
| Maximum of Months | 0.371944E+09 | 0.261307E+09 | 0.126953E+09 | 0.485185E+09 | 0.298541E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 65103026.25 | 24952264.22 | 40150762.03 | 22755263.16 | 0.298541E+09 |
| February | 99485030.50 | 53364261.91 | 46120768.60 | 72260845.73 | 0.203809E+09 |
| March | 0.181751E+09 | 84547902.93 | 97202650.84 | 0.164796E+09 | 0.195044E+09 |
| April | 0.226136E+09 | 0.127921E+09 | 98215723.15 | 0.231497E+09 | 0.146220E+09 |
| May | 0.298012E+09 | 0.171059E+09 | 0.126953E+09 | 0.333878E+09 | 0.122959E+09 |
| June | 0.347105E+09 | 0.223792E+09 | 0.123313E+09 | 0.427590E+09 | 87305218.42 |
| July | 0.371944E+09 | 0.261307E+09 | 0.110637E+09 | 0.485185E+09 | 79255863.60 |
| August | 0.304823E+09 | 0.207212E+09 | 97611180.70 | 0.389693E+09 | 85677749.98 |
| September | 0.207270E+09 | 0.131866E+09 | 75403324.72 | 0.242755E+09 | 0.113445E+09 |
| October | 0.132616E+09 | 73732423.58 | 58883367.07 | 0.126838E+09 | 0.164443E+09 |
| November | 73835930.39 | 34352403.97 | 39483526.42 | 45853922.55 | 0.200376E+09 |
| December | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 0.263554E+09 |
| Annual Sum or Average | 0.235954E+10 | 0.141275E+10 | 0.946789E+09 | 0.255784E+10 | 0.196063E+10 |
| Minimum of Months | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 79255863.60 |
| Maximum of Months | 0.371944E+09 | 0.261307E+09 | 0.126953E+09 | 0.485185E+09 | 0.298541E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_3
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 65103026.25 | 24952264.22 | 40150762.03 | 22755263.16 | 0.298541E+09 |
| February | 99485030.50 | 53364261.91 | 46120768.60 | 72260845.73 | 0.203809E+09 |
| March | 0.181751E+09 | 84547902.93 | 97202650.84 | 0.164796E+09 | 0.195044E+09 |
| April | 0.226136E+09 | 0.127921E+09 | 98215723.15 | 0.231497E+09 | 0.146220E+09 |
| May | 0.298012E+09 | 0.171059E+09 | 0.126953E+09 | 0.333878E+09 | 0.122959E+09 |
| June | 0.347105E+09 | 0.223792E+09 | 0.123313E+09 | 0.427590E+09 | 87305218.42 |
| July | 0.371944E+09 | 0.261307E+09 | 0.110637E+09 | 0.485185E+09 | 79255863.60 |
| August | 0.304823E+09 | 0.207212E+09 | 97611180.70 | 0.389693E+09 | 85677749.98 |
| September | 0.207270E+09 | 0.131866E+09 | 75403324.72 | 0.242755E+09 | 0.113445E+09 |
| October | 0.132616E+09 | 73732423.58 | 58883367.07 | 0.126838E+09 | 0.164443E+09 |
| November | 73835930.39 | 34352403.97 | 39483526.42 | 45853922.55 | 0.200376E+09 |
| December | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 0.263554E+09 |
| Annual Sum or Average | 0.235954E+10 | 0.141275E+10 | 0.946789E+09 | 0.255784E+10 | 0.196063E+10 |
| Minimum of Months | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 79255863.60 |
| Maximum of Months | 0.371944E+09 | 0.261307E+09 | 0.126953E+09 | 0.485185E+09 | 0.298541E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_4
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 65103026.25 | 24952264.22 | 40150762.03 | 22755263.16 | 0.298541E+09 |
| February | 99485030.50 | 53364261.91 | 46120768.60 | 72260845.73 | 0.203809E+09 |
| March | 0.181751E+09 | 84547902.93 | 97202650.84 | 0.164796E+09 | 0.195044E+09 |
| April | 0.226136E+09 | 0.127921E+09 | 98215723.15 | 0.231497E+09 | 0.146220E+09 |
| May | 0.298012E+09 | 0.171059E+09 | 0.126953E+09 | 0.333878E+09 | 0.122959E+09 |
| June | 0.347105E+09 | 0.223792E+09 | 0.123313E+09 | 0.427590E+09 | 87305218.42 |
| July | 0.371944E+09 | 0.261307E+09 | 0.110637E+09 | 0.485185E+09 | 79255863.60 |
| August | 0.304823E+09 | 0.207212E+09 | 97611180.70 | 0.389693E+09 | 85677749.98 |
| September | 0.207270E+09 | 0.131866E+09 | 75403324.72 | 0.242755E+09 | 0.113445E+09 |
| October | 0.132616E+09 | 73732423.58 | 58883367.07 | 0.126838E+09 | 0.164443E+09 |
| November | 73835930.39 | 34352403.97 | 39483526.42 | 45853922.55 | 0.200376E+09 |
| December | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 0.263554E+09 |
| Annual Sum or Average | 0.235954E+10 | 0.141275E+10 | 0.946789E+09 | 0.255784E+10 | 0.196063E+10 |
| Minimum of Months | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 79255863.60 |
| Maximum of Months | 0.371944E+09 | 0.261307E+09 | 0.126953E+09 | 0.485185E+09 | 0.298541E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_5
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 65103026.25 | 24952264.22 | 40150762.03 | 22755263.16 | 0.298541E+09 |
| February | 99485030.50 | 53364261.91 | 46120768.60 | 72260845.73 | 0.203809E+09 |
| March | 0.181751E+09 | 84547902.93 | 97202650.84 | 0.164796E+09 | 0.195044E+09 |
| April | 0.226136E+09 | 0.127921E+09 | 98215723.15 | 0.231497E+09 | 0.146220E+09 |
| May | 0.298012E+09 | 0.171059E+09 | 0.126953E+09 | 0.333878E+09 | 0.122959E+09 |
| June | 0.347105E+09 | 0.223792E+09 | 0.123313E+09 | 0.427590E+09 | 87305218.42 |
| July | 0.371944E+09 | 0.261307E+09 | 0.110637E+09 | 0.485185E+09 | 79255863.60 |
| August | 0.304823E+09 | 0.207212E+09 | 97611180.70 | 0.389693E+09 | 85677749.98 |
| September | 0.207270E+09 | 0.131866E+09 | 75403324.72 | 0.242755E+09 | 0.113445E+09 |
| October | 0.132616E+09 | 73732423.58 | 58883367.07 | 0.126838E+09 | 0.164443E+09 |
| November | 73835930.39 | 34352403.97 | 39483526.42 | 45853922.55 | 0.200376E+09 |
| December | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 0.263554E+09 |
| Annual Sum or Average | 0.235954E+10 | 0.141275E+10 | 0.946789E+09 | 0.255784E+10 | 0.196063E+10 |
| Minimum of Months | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 79255863.60 |
| Maximum of Months | 0.371944E+09 | 0.261307E+09 | 0.126953E+09 | 0.485185E+09 | 0.298541E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_6
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 65103026.25 | 24952264.22 | 40150762.03 | 22755263.16 | 0.298541E+09 |
| February | 99485030.50 | 53364261.91 | 46120768.60 | 72260845.73 | 0.203809E+09 |
| March | 0.181751E+09 | 84547902.93 | 97202650.84 | 0.164796E+09 | 0.195044E+09 |
| April | 0.226136E+09 | 0.127921E+09 | 98215723.15 | 0.231497E+09 | 0.146220E+09 |
| May | 0.298012E+09 | 0.171059E+09 | 0.126953E+09 | 0.333878E+09 | 0.122959E+09 |
| June | 0.347105E+09 | 0.223792E+09 | 0.123313E+09 | 0.427590E+09 | 87305218.42 |
| July | 0.371944E+09 | 0.261307E+09 | 0.110637E+09 | 0.485185E+09 | 79255863.60 |
| August | 0.304823E+09 | 0.207212E+09 | 97611180.70 | 0.389693E+09 | 85677749.98 |
| September | 0.207270E+09 | 0.131866E+09 | 75403324.72 | 0.242755E+09 | 0.113445E+09 |
| October | 0.132616E+09 | 73732423.58 | 58883367.07 | 0.126838E+09 | 0.164443E+09 |
| November | 73835930.39 | 34352403.97 | 39483526.42 | 45853922.55 | 0.200376E+09 |
| December | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 0.263554E+09 |
| Annual Sum or Average | 0.235954E+10 | 0.141275E+10 | 0.946789E+09 | 0.255784E+10 | 0.196063E+10 |
| Minimum of Months | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 79255863.60 |
| Maximum of Months | 0.371944E+09 | 0.261307E+09 | 0.126953E+09 | 0.485185E+09 | 0.298541E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_7
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 65103026.25 | 24952264.22 | 40150762.03 | 22755263.16 | 0.298541E+09 |
| February | 99485030.50 | 53364261.91 | 46120768.60 | 72260845.73 | 0.203809E+09 |
| March | 0.181751E+09 | 84547902.93 | 97202650.84 | 0.164796E+09 | 0.195044E+09 |
| April | 0.226136E+09 | 0.127921E+09 | 98215723.15 | 0.231497E+09 | 0.146220E+09 |
| May | 0.298012E+09 | 0.171059E+09 | 0.126953E+09 | 0.333878E+09 | 0.122959E+09 |
| June | 0.347105E+09 | 0.223792E+09 | 0.123313E+09 | 0.427590E+09 | 87305218.42 |
| July | 0.371944E+09 | 0.261307E+09 | 0.110637E+09 | 0.485185E+09 | 79255863.60 |
| August | 0.304823E+09 | 0.207212E+09 | 97611180.70 | 0.389693E+09 | 85677749.98 |
| September | 0.207270E+09 | 0.131866E+09 | 75403324.72 | 0.242755E+09 | 0.113445E+09 |
| October | 0.132616E+09 | 73732423.58 | 58883367.07 | 0.126838E+09 | 0.164443E+09 |
| November | 73835930.39 | 34352403.97 | 39483526.42 | 45853922.55 | 0.200376E+09 |
| December | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 0.263554E+09 |
| Annual Sum or Average | 0.235954E+10 | 0.141275E+10 | 0.946789E+09 | 0.255784E+10 | 0.196063E+10 |
| Minimum of Months | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 79255863.60 |
| Maximum of Months | 0.371944E+09 | 0.261307E+09 | 0.126953E+09 | 0.485185E+09 | 0.298541E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_8
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 65103026.25 | 24952264.22 | 40150762.03 | 22755263.16 | 0.298541E+09 |
| February | 99485030.50 | 53364261.91 | 46120768.60 | 72260845.73 | 0.203809E+09 |
| March | 0.181751E+09 | 84547902.93 | 97202650.84 | 0.164796E+09 | 0.195044E+09 |
| April | 0.226136E+09 | 0.127921E+09 | 98215723.15 | 0.231497E+09 | 0.146220E+09 |
| May | 0.298012E+09 | 0.171059E+09 | 0.126953E+09 | 0.333878E+09 | 0.122959E+09 |
| June | 0.347105E+09 | 0.223792E+09 | 0.123313E+09 | 0.427590E+09 | 87305218.42 |
| July | 0.371944E+09 | 0.261307E+09 | 0.110637E+09 | 0.485185E+09 | 79255863.60 |
| August | 0.304823E+09 | 0.207212E+09 | 97611180.70 | 0.389693E+09 | 85677749.98 |
| September | 0.207270E+09 | 0.131866E+09 | 75403324.72 | 0.242755E+09 | 0.113445E+09 |
| October | 0.132616E+09 | 73732423.58 | 58883367.07 | 0.126838E+09 | 0.164443E+09 |
| November | 73835930.39 | 34352403.97 | 39483526.42 | 45853922.55 | 0.200376E+09 |
| December | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 0.263554E+09 |
| Annual Sum or Average | 0.235954E+10 | 0.141275E+10 | 0.946789E+09 | 0.255784E+10 | 0.196063E+10 |
| Minimum of Months | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 79255863.60 |
| Maximum of Months | 0.371944E+09 | 0.261307E+09 | 0.126953E+09 | 0.485185E+09 | 0.298541E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_CEILING_SKYLIGHT_9
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 65103026.25 | 24952264.22 | 40150762.03 | 22755263.16 | 0.298541E+09 |
| February | 99485030.50 | 53364261.91 | 46120768.60 | 72260845.73 | 0.203809E+09 |
| March | 0.181751E+09 | 84547902.93 | 97202650.84 | 0.164796E+09 | 0.195044E+09 |
| April | 0.226136E+09 | 0.127921E+09 | 98215723.15 | 0.231497E+09 | 0.146220E+09 |
| May | 0.298012E+09 | 0.171059E+09 | 0.126953E+09 | 0.333878E+09 | 0.122959E+09 |
| June | 0.347105E+09 | 0.223792E+09 | 0.123313E+09 | 0.427590E+09 | 87305218.42 |
| July | 0.371944E+09 | 0.261307E+09 | 0.110637E+09 | 0.485185E+09 | 79255863.60 |
| August | 0.304823E+09 | 0.207212E+09 | 97611180.70 | 0.389693E+09 | 85677749.98 |
| September | 0.207270E+09 | 0.131866E+09 | 75403324.72 | 0.242755E+09 | 0.113445E+09 |
| October | 0.132616E+09 | 73732423.58 | 58883367.07 | 0.126838E+09 | 0.164443E+09 |
| November | 73835930.39 | 34352403.97 | 39483526.42 | 45853922.55 | 0.200376E+09 |
| December | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 0.263554E+09 |
| Annual Sum or Average | 0.235954E+10 | 0.141275E+10 | 0.946789E+09 | 0.255784E+10 | 0.196063E+10 |
| Minimum of Months | 51458139.27 | 18643537.02 | 32814602.24 | 14738575.64 | 79255863.60 |
| Maximum of Months | 0.371944E+09 | 0.261307E+09 | 0.126953E+09 | 0.485185E+09 | 0.298541E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 36046874.78 | 16526032.59 | 19520842.19 | 15430702.33 | 0.178111E+09 |
| February | 50924342.23 | 25282725.47 | 25641616.76 | 34027685.74 | 0.120634E+09 |
| March | 75808730.36 | 31367535.77 | 44441194.59 | 53681355.14 | 0.113728E+09 |
| April | 93604345.58 | 46389629.89 | 47214715.69 | 82226204.47 | 83976064.70 |
| May | 0.106845E+09 | 47539237.85 | 59305558.73 | 0.101414E+09 | 70406502.21 |
| June | 0.133836E+09 | 68871679.59 | 64963865.23 | 0.154348E+09 | 44029043.09 |
| July | 0.145146E+09 | 82055084.12 | 63091215.73 | 0.186707E+09 | 35470672.64 |
| August | 0.126139E+09 | 70280515.10 | 55858089.34 | 0.157646E+09 | 39913956.43 |
| September | 86352260.87 | 44574708.72 | 41777552.15 | 93244078.45 | 58798900.92 |
| October | 64018340.50 | 32507517.24 | 31510823.26 | 53134352.30 | 88178251.21 |
| November | 39264763.24 | 18331482.31 | 20933280.93 | 22148907.96 | 0.112535E+09 |
| December | 29925374.48 | 12853015.98 | 17072358.50 | 11459718.11 | 0.152857E+09 |
| Annual Sum or Average | 0.987910E+09 | 0.496579E+09 | 0.491331E+09 | 0.965468E+09 | 0.109864E+10 |
| Minimum of Months | 29925374.48 | 12853015.98 | 17072358.50 | 11459718.11 | 35470672.64 |
| Maximum of Months | 0.145146E+09 | 82055084.12 | 64963865.23 | 0.186707E+09 | 0.178111E+09 |
Report: WindowEnergyReportMonthly
For: GYM_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.426653E+09 | 0.195598E+09 | 0.231055E+09 | 0.182603E+09 | 0.210808E+10 |
| February | 0.602744E+09 | 0.299240E+09 | 0.303504E+09 | 0.402979E+09 | 0.142741E+10 |
| March | 0.897280E+09 | 0.371258E+09 | 0.526022E+09 | 0.635695E+09 | 0.134533E+10 |
| April | 0.110791E+10 | 0.549055E+09 | 0.558854E+09 | 0.974913E+09 | 0.993444E+09 |
| May | 0.126463E+10 | 0.562662E+09 | 0.701967E+09 | 0.120243E+10 | 0.832905E+09 |
| June | 0.158409E+10 | 0.815147E+09 | 0.768944E+09 | 0.182973E+10 | 0.521088E+09 |
| July | 0.171797E+10 | 0.971182E+09 | 0.746783E+09 | 0.221396E+10 | 0.419865E+09 |
| August | 0.149299E+10 | 0.831822E+09 | 0.661165E+09 | 0.186896E+10 | 0.472526E+09 |
| September | 0.102207E+10 | 0.527574E+09 | 0.494499E+09 | 0.110581E+10 | 0.695655E+09 |
| October | 0.757725E+09 | 0.384750E+09 | 0.372975E+09 | 0.629529E+09 | 0.104323E+10 |
| November | 0.464740E+09 | 0.216967E+09 | 0.247774E+09 | 0.262184E+09 | 0.133153E+10 |
| December | 0.354198E+09 | 0.152125E+09 | 0.202073E+09 | 0.135606E+09 | 0.180917E+10 |
| Annual Sum or Average | 0.116930E+11 | 0.587738E+10 | 0.581562E+10 | 0.114444E+11 | 0.130002E+11 |
| Minimum of Months | 0.354198E+09 | 0.152125E+09 | 0.202073E+09 | 0.135606E+09 | 0.419865E+09 |
| Maximum of Months | 0.171797E+10 | 0.971182E+09 | 0.768944E+09 | 0.221396E+10 | 0.210808E+10 |
Report: WindowEnergyReportMonthly
For: KITCHEN_ZN_1_FLR_1_WALL_2_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.217765E+09 | 99836158.53 | 0.117929E+09 | 78274452.05 | 0.129565E+10 |
| February | 0.307643E+09 | 0.152737E+09 | 0.154906E+09 | 0.179819E+09 | 0.909515E+09 |
| March | 0.457974E+09 | 0.189496E+09 | 0.268478E+09 | 0.296042E+09 | 0.842059E+09 |
| April | 0.565480E+09 | 0.280246E+09 | 0.285234E+09 | 0.473628E+09 | 0.598553E+09 |
| May | 0.645469E+09 | 0.287191E+09 | 0.358277E+09 | 0.599544E+09 | 0.486461E+09 |
| June | 0.808524E+09 | 0.416064E+09 | 0.392461E+09 | 0.929112E+09 | 0.294715E+09 |
| July | 0.876855E+09 | 0.495707E+09 | 0.381148E+09 | 0.112651E+10 | 0.236265E+09 |
| August | 0.762026E+09 | 0.424575E+09 | 0.337451E+09 | 0.950858E+09 | 0.270064E+09 |
| September | 0.521669E+09 | 0.269282E+09 | 0.252387E+09 | 0.554293E+09 | 0.396765E+09 |
| October | 0.386746E+09 | 0.196383E+09 | 0.190363E+09 | 0.306101E+09 | 0.622269E+09 |
| November | 0.237205E+09 | 0.110743E+09 | 0.126462E+09 | 0.115526E+09 | 0.844409E+09 |
| December | 0.180784E+09 | 77646932.71 | 0.103137E+09 | 53979727.79 | 0.114374E+10 |
| Annual Sum or Average | 0.596814E+10 | 0.299991E+10 | 0.296823E+10 | 0.566368E+10 | 0.794046E+10 |
| Minimum of Months | 0.180784E+09 | 77646932.71 | 0.103137E+09 | 53979727.79 | 0.236265E+09 |
| Maximum of Months | 0.876855E+09 | 0.495707E+09 | 0.392461E+09 | 0.112651E+10 | 0.129565E+10 |
Report: WindowEnergyReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.233967E+09 | 0.00 | 0.233967E+09 | 817431.74 | 0.303258E+10 |
| February | 0.297949E+09 | 0.00 | 0.297949E+09 | 20554970.48 | 0.204964E+10 |
| March | 0.537777E+09 | 0.00 | 0.537777E+09 | 82405915.50 | 0.183943E+10 |
| April | 0.588726E+09 | 2709229.68 | 0.586017E+09 | 0.196992E+09 | 0.128950E+10 |
| May | 0.782706E+09 | 33904153.18 | 0.748802E+09 | 0.417069E+09 | 0.104590E+10 |
| June | 0.870886E+09 | 81467962.63 | 0.789418E+09 | 0.734402E+09 | 0.668996E+09 |
| July | 0.847239E+09 | 75556515.26 | 0.771682E+09 | 0.942418E+09 | 0.542254E+09 |
| August | 0.676221E+09 | 13125998.16 | 0.663095E+09 | 0.678098E+09 | 0.626428E+09 |
| September | 0.495853E+09 | 94457.28 | 0.495759E+09 | 0.334052E+09 | 0.966368E+09 |
| October | 0.373930E+09 | 0.00 | 0.373930E+09 | 80878529.38 | 0.143173E+10 |
| November | 0.245588E+09 | 0.00 | 0.245588E+09 | 9314255.46 | 0.191976E+10 |
| December | 0.195406E+09 | 0.00 | 0.195406E+09 | 153905.11 | 0.260485E+10 |
| Annual Sum or Average | 0.614625E+10 | 0.206858E+09 | 0.593939E+10 | 0.349716E+10 | 0.180174E+11 |
| Minimum of Months | 0.195406E+09 | 0.00 | 0.195406E+09 | 153905.11 | 0.542254E+09 |
| Maximum of Months | 0.870886E+09 | 81467962.63 | 0.789418E+09 | 0.942418E+09 | 0.303258E+10 |
Report: WindowEnergyReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 36388715.61 | 16682752.77 | 19705962.84 | 16119177.36 | 0.176100E+09 |
| February | 51407269.52 | 25522487.39 | 25884782.13 | 35359625.38 | 0.117793E+09 |
| March | 76527642.05 | 31665001.35 | 44862640.70 | 56507236.87 | 0.107329E+09 |
| April | 94492017.19 | 46829553.46 | 47662463.73 | 86900826.31 | 75855676.40 |
| May | 0.107858E+09 | 47990063.42 | 59867967.03 | 0.105921E+09 | 64563888.78 |
| June | 0.135105E+09 | 69524805.63 | 65579932.56 | 0.158046E+09 | 42777193.34 |
| July | 0.146523E+09 | 82833231.42 | 63689524.29 | 0.189808E+09 | 34818045.60 |
| August | 0.127335E+09 | 70947001.44 | 56387804.49 | 0.160783E+09 | 38414991.63 |
| September | 87171159.29 | 44997420.97 | 42173738.32 | 95558903.56 | 56627494.51 |
| October | 64625441.20 | 32815793.53 | 31809647.67 | 55416927.80 | 83365157.08 |
| November | 39637120.05 | 18505323.99 | 21131796.07 | 22901914.05 | 0.109776E+09 |
| December | 30209163.71 | 12974904.09 | 17234259.62 | 11948326.91 | 0.151412E+09 |
| Annual Sum or Average | 0.997279E+09 | 0.501288E+09 | 0.495991E+09 | 0.995271E+09 | 0.105883E+10 |
| Minimum of Months | 30209163.71 | 12974904.09 | 17234259.62 | 11948326.91 | 34818045.60 |
| Maximum of Months | 0.146523E+09 | 82833231.42 | 65579932.56 | 0.189808E+09 | 0.176100E+09 |
Report: WindowEnergyReportMonthly
For: CAFETERIA_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.371934E+09 | 0.170517E+09 | 0.201417E+09 | 0.164756E+09 | 0.179994E+10 |
| February | 0.525440E+09 | 0.260869E+09 | 0.264572E+09 | 0.361415E+09 | 0.120398E+10 |
| March | 0.782199E+09 | 0.323652E+09 | 0.458547E+09 | 0.577568E+09 | 0.109702E+10 |
| April | 0.965815E+09 | 0.478651E+09 | 0.487164E+09 | 0.888225E+09 | 0.775324E+09 |
| May | 0.110243E+10 | 0.490513E+09 | 0.611918E+09 | 0.108269E+10 | 0.659680E+09 |
| June | 0.138092E+10 | 0.710622E+09 | 0.670301E+09 | 0.161563E+10 | 0.436948E+09 |
| July | 0.149763E+10 | 0.846649E+09 | 0.650979E+09 | 0.194023E+10 | 0.355806E+09 |
| August | 0.130151E+10 | 0.725158E+09 | 0.576347E+09 | 0.164343E+10 | 0.392620E+09 |
| September | 0.890988E+09 | 0.459924E+09 | 0.431063E+09 | 0.976720E+09 | 0.578797E+09 |
| October | 0.660545E+09 | 0.335414E+09 | 0.325130E+09 | 0.566424E+09 | 0.852086E+09 |
| November | 0.405136E+09 | 0.189145E+09 | 0.215991E+09 | 0.234083E+09 | 0.112204E+10 |
| December | 0.308772E+09 | 0.132618E+09 | 0.176154E+09 | 0.122125E+09 | 0.154760E+10 |
| Annual Sum or Average | 0.101933E+11 | 0.512373E+10 | 0.506958E+10 | 0.101733E+11 | 0.108218E+11 |
| Minimum of Months | 0.308772E+09 | 0.132618E+09 | 0.176154E+09 | 0.122125E+09 | 0.355806E+09 |
| Maximum of Months | 0.149763E+10 | 0.846649E+09 | 0.670301E+09 | 0.194023E+10 | 0.179994E+10 |
Report: WindowEnergyReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_3_WINDOW_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.225234E+09 | 0.00 | 0.225234E+09 | 2037328.14 | 0.270178E+10 |
| February | 0.287241E+09 | 0.00 | 0.287241E+09 | 29887140.08 | 0.179816E+10 |
| March | 0.516603E+09 | 0.00 | 0.516603E+09 | 97213902.08 | 0.161896E+10 |
| April | 0.570037E+09 | 3326523.79 | 0.566710E+09 | 0.203616E+09 | 0.116339E+10 |
| May | 0.773547E+09 | 45836342.21 | 0.727711E+09 | 0.435302E+09 | 0.940039E+09 |
| June | 0.871697E+09 | 0.100192E+09 | 0.771505E+09 | 0.763035E+09 | 0.591136E+09 |
| July | 0.822890E+09 | 77071358.94 | 0.745819E+09 | 0.939915E+09 | 0.482636E+09 |
| August | 0.659387E+09 | 17674128.55 | 0.641713E+09 | 0.673934E+09 | 0.561932E+09 |
| September | 0.477904E+09 | 171493.17 | 0.477733E+09 | 0.329830E+09 | 0.895624E+09 |
| October | 0.360223E+09 | 0.00 | 0.360223E+09 | 81514980.02 | 0.133712E+10 |
| November | 0.236983E+09 | 0.00 | 0.236983E+09 | 12901484.83 | 0.171404E+10 |
| December | 0.188871E+09 | 0.00 | 0.188871E+09 | 748730.13 | 0.229992E+10 |
| Annual Sum or Average | 0.599062E+10 | 0.244271E+09 | 0.574635E+10 | 0.356994E+10 | 0.161047E+11 |
| Minimum of Months | 0.188871E+09 | 0.00 | 0.188871E+09 | 748730.13 | 0.482636E+09 |
| Maximum of Months | 0.871697E+09 | 0.100192E+09 | 0.771505E+09 | 0.939915E+09 | 0.270178E+10 |
Report: WindowEnergyReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 11336524.41 | 0.00 | 11336524.41 | 3504.95 | 0.183219E+09 |
| February | 14740522.76 | 0.00 | 14740522.76 | 1117124.77 | 0.123503E+09 |
| March | 26210627.34 | 0.00 | 26210627.34 | 2551571.90 | 0.112949E+09 |
| April | 47476718.49 | 16059086.92 | 31417631.57 | 27451294.54 | 75608382.00 |
| May | 74965606.49 | 32547659.91 | 42417946.58 | 64725228.46 | 64490899.31 |
| June | 0.103935E+09 | 54849085.71 | 49086038.95 | 0.117544E+09 | 40373038.50 |
| July | 0.109072E+09 | 61515057.15 | 47556766.99 | 0.140298E+09 | 30492873.36 |
| August | 74005026.18 | 34802233.17 | 39202793.00 | 88024591.50 | 34851785.15 |
| September | 29477369.54 | 3732715.41 | 25744654.13 | 20175491.56 | 57542927.35 |
| October | 18466128.33 | 0.00 | 18466128.33 | 2997642.37 | 91378620.31 |
| November | 12009328.14 | 0.00 | 12009328.14 | 130047.09 | 0.116137E+09 |
| December | 9437436.78 | 0.00 | 9437436.78 | 836.34 | 0.155939E+09 |
| Annual Sum or Average | 0.531132E+09 | 0.203506E+09 | 0.327626E+09 | 0.465020E+09 | 0.108649E+10 |
| Minimum of Months | 9437436.78 | 0.00 | 9437436.78 | 836.34 | 30492873.36 |
| Maximum of Months | 0.109072E+09 | 61515057.15 | 49086038.95 | 0.140298E+09 | 0.183219E+09 |
Report: WindowEnergyReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1_WALL_2_WINDOW2
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.438421E+09 | 0.173070E+09 | 0.265352E+09 | 0.141462E+09 | 0.258710E+10 |
| February | 0.679748E+09 | 0.323394E+09 | 0.356354E+09 | 0.441537E+09 | 0.169471E+10 |
| March | 0.110013E+10 | 0.461038E+09 | 0.639096E+09 | 0.812040E+09 | 0.154441E+10 |
| April | 0.136951E+10 | 0.689995E+09 | 0.679511E+09 | 0.125770E+10 | 0.112377E+10 |
| May | 0.156018E+10 | 0.707094E+09 | 0.853086E+09 | 0.152405E+10 | 0.964482E+09 |
| June | 0.195798E+10 | 0.102439E+10 | 0.933587E+09 | 0.229173E+10 | 0.623982E+09 |
| July | 0.212759E+10 | 0.122048E+10 | 0.907107E+09 | 0.277781E+10 | 0.493148E+09 |
| August | 0.184894E+10 | 0.104535E+10 | 0.803590E+09 | 0.234670E+10 | 0.555680E+09 |
| September | 0.126051E+10 | 0.660552E+09 | 0.599960E+09 | 0.137785E+10 | 0.845620E+09 |
| October | 0.891534E+09 | 0.445926E+09 | 0.445608E+09 | 0.731671E+09 | 0.126341E+10 |
| November | 0.496067E+09 | 0.210824E+09 | 0.285243E+09 | 0.238364E+09 | 0.160663E+10 |
| December | 0.347108E+09 | 0.122892E+09 | 0.224217E+09 | 86077823.57 | 0.221283E+10 |
| Annual Sum or Average | 0.140777E+11 | 0.708500E+10 | 0.699271E+10 | 0.140270E+11 | 0.155158E+11 |
| Minimum of Months | 0.347108E+09 | 0.122892E+09 | 0.224217E+09 | 86077823.57 | 0.493148E+09 |
| Maximum of Months | 0.212759E+10 | 0.122048E+10 | 0.933587E+09 | 0.277781E+10 | 0.258710E+10 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 299.76 | 897.31 | 426.04 | 278.50 | 147.54 | 0.00 | 0.00 |
| February | 507.10 | 648.35 | 578.46 | 383.85 | 194.61 | 0.00 | 0.00 |
| March | 506.20 | 568.17 | 571.64 | 285.69 | 285.95 | 0.00 | 0.00 |
| April | 545.51 | 406.69 | 550.29 | 254.88 | 295.42 | 0.00 | 0.00 |
| May | 589.61 | 335.93 | 571.25 | 225.94 | 345.31 | 0.00 | 0.00 |
| June | 717.26 | 236.75 | 595.17 | 226.90 | 368.27 | 0.00 | 0.00 |
| July | 864.17 | 183.58 | 624.58 | 274.99 | 349.59 | 0.00 | 0.00 |
| August | 844.32 | 207.98 | 631.75 | 314.81 | 316.94 | 0.00 | 0.00 |
| September | 729.54 | 324.00 | 616.43 | 353.86 | 262.57 | 0.00 | 0.00 |
| October | 578.43 | 457.08 | 570.86 | 363.79 | 207.07 | 0.00 | 0.00 |
| November | 420.74 | 566.57 | 488.05 | 327.83 | 160.22 | 0.00 | 0.00 |
| December | 297.15 | 752.46 | 402.02 | 267.59 | 134.42 | 0.00 | 0.00 |
| Annual Sum or Average | 575.23 | 464.80 | 551.88 | 295.90 | 255.99 | 0.00 | 0.00 |
| Minimum of Months | 297.15 | 183.58 | 402.02 | 225.94 | 134.42 | 0.00 | 0.00 |
| Maximum of Months | 864.17 | 897.31 | 631.75 | 383.85 | 368.27 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1450.12 | 2381.56 | 1653.57 | 1181.01 | 472.56 | 0.00 | 0.00 |
| February | 2089.24 | 1770.66 | 2105.79 | 1514.56 | 591.23 | 0.00 | 0.00 |
| March | 1845.87 | 1595.38 | 1882.30 | 1057.02 | 825.29 | 0.00 | 0.00 |
| April | 1561.88 | 1197.16 | 1513.06 | 723.70 | 789.35 | 0.00 | 0.00 |
| May | 1394.22 | 980.29 | 1344.31 | 446.48 | 897.83 | 0.00 | 0.00 |
| June | 1637.33 | 682.79 | 1335.71 | 389.56 | 946.15 | 0.00 | 0.00 |
| July | 2074.05 | 488.99 | 1440.03 | 531.94 | 908.09 | 0.00 | 0.00 |
| August | 2366.61 | 567.77 | 1711.38 | 862.85 | 848.53 | 0.00 | 0.00 |
| September | 2341.53 | 901.61 | 1898.13 | 1163.04 | 735.08 | 0.00 | 0.00 |
| October | 2174.78 | 1277.31 | 1984.39 | 1372.18 | 612.21 | 0.00 | 0.00 |
| November | 1774.91 | 1558.68 | 1809.18 | 1310.49 | 498.68 | 0.00 | 0.00 |
| December | 1420.31 | 2026.78 | 1572.45 | 1135.47 | 436.98 | 0.00 | 0.00 |
| Annual Sum or Average | 1842.39 | 1283.96 | 1684.62 | 970.43 | 714.19 | 0.00 | 0.00 |
| Minimum of Months | 1394.22 | 488.99 | 1335.71 | 389.56 | 436.98 | 0.00 | 0.00 |
| Maximum of Months | 2366.61 | 2381.56 | 2105.79 | 1514.56 | 946.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 11.63 | 160.53 | 27.62 | 11.13 | 16.49 | 0.00 | 0.00 |
| February | 32.73 | 115.22 | 47.14 | 23.17 | 23.97 | 0.00 | 0.00 |
| March | 42.87 | 96.28 | 60.33 | 22.10 | 38.22 | 0.00 | 0.00 |
| April | 73.45 | 68.08 | 78.76 | 34.89 | 43.86 | 0.00 | 0.00 |
| May | 100.86 | 55.64 | 97.42 | 44.43 | 52.99 | 0.00 | 0.00 |
| June | 126.08 | 38.24 | 105.98 | 48.68 | 57.30 | 0.00 | 0.00 |
| July | 147.06 | 27.93 | 108.57 | 54.86 | 53.71 | 0.00 | 0.00 |
| August | 120.69 | 31.26 | 92.19 | 45.25 | 46.95 | 0.00 | 0.00 |
| September | 84.39 | 51.39 | 74.16 | 37.49 | 36.67 | 0.00 | 0.00 |
| October | 46.55 | 75.63 | 53.01 | 26.34 | 26.67 | 0.00 | 0.00 |
| November | 25.62 | 100.51 | 37.52 | 18.61 | 18.91 | 0.00 | 0.00 |
| December | 10.86 | 134.35 | 25.22 | 10.65 | 14.58 | 0.00 | 0.00 |
| Annual Sum or Average | 68.76 | 79.46 | 67.42 | 31.50 | 35.92 | 0.00 | 0.00 |
| Minimum of Months | 10.86 | 27.93 | 25.22 | 10.65 | 14.58 | 0.00 | 0.00 |
| Maximum of Months | 147.06 | 160.53 | 108.57 | 54.86 | 57.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 19.84 | 998.70 | 123.67 | 33.39 | 90.28 | 0.00 | 0.00 |
| February | 92.50 | 708.00 | 198.13 | 69.51 | 128.61 | 0.00 | 0.00 |
| March | 143.27 | 571.05 | 275.35 | 66.31 | 209.03 | 0.00 | 0.00 |
| April | 267.44 | 387.33 | 343.10 | 105.28 | 237.82 | 0.00 | 0.00 |
| May | 391.47 | 317.05 | 432.69 | 141.90 | 290.79 | 0.00 | 0.00 |
| June | 534.53 | 212.89 | 478.52 | 165.38 | 313.15 | 0.00 | 0.00 |
| July | 635.34 | 160.39 | 471.51 | 177.84 | 293.67 | 0.00 | 0.00 |
| August | 505.56 | 180.43 | 394.27 | 139.00 | 255.26 | 0.00 | 0.00 |
| September | 322.84 | 299.89 | 310.57 | 112.51 | 198.06 | 0.00 | 0.00 |
| October | 151.72 | 442.51 | 223.54 | 79.01 | 144.54 | 0.00 | 0.00 |
| November | 63.41 | 601.04 | 156.25 | 55.84 | 100.41 | 0.00 | 0.00 |
| December | 18.76 | 832.20 | 109.26 | 31.94 | 77.32 | 0.00 | 0.00 |
| Annual Sum or Average | 263.24 | 475.15 | 293.53 | 98.27 | 195.26 | 0.00 | 0.00 |
| Minimum of Months | 18.76 | 160.39 | 109.26 | 31.94 | 77.32 | 0.00 | 0.00 |
| Maximum of Months | 635.34 | 998.70 | 478.52 | 177.84 | 313.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.50 | 2811.29 | 183.80 | 0.00 | 183.80 | 0.00 | 0.00 |
| February | 19.08 | 2071.64 | 254.11 | 0.00 | 254.11 | 0.00 | 0.00 |
| March | 50.56 | 1661.43 | 426.34 | 0.00 | 426.34 | 0.00 | 0.00 |
| April | 157.78 | 1156.87 | 480.02 | 2.00 | 478.02 | 0.00 | 0.00 |
| May | 346.23 | 910.07 | 626.48 | 34.27 | 592.21 | 0.00 | 0.00 |
| June | 648.86 | 585.62 | 698.77 | 73.72 | 625.05 | 0.00 | 0.00 |
| July | 882.50 | 401.16 | 648.95 | 56.12 | 592.83 | 0.00 | 0.00 |
| August | 639.72 | 463.83 | 523.40 | 11.98 | 511.42 | 0.00 | 0.00 |
| September | 298.23 | 832.13 | 394.88 | 0.10 | 394.77 | 0.00 | 0.00 |
| October | 57.78 | 1291.41 | 289.59 | 0.00 | 289.59 | 0.00 | 0.00 |
| November | 6.33 | 1780.93 | 195.66 | 0.00 | 195.66 | 0.00 | 0.00 |
| December | 0.32 | 2380.82 | 150.20 | 0.00 | 150.20 | 0.00 | 0.00 |
| Annual Sum or Average | 260.76 | 1359.43 | 406.87 | 14.93 | 391.94 | 0.00 | 0.00 |
| Minimum of Months | 0.32 | 401.16 | 150.20 | 0.00 | 150.20 | 0.00 | 0.00 |
| Maximum of Months | 882.50 | 2811.29 | 698.77 | 73.72 | 625.05 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 287.91 | 907.44 | 402.53 | 265.94 | 136.59 | 0.00 | 0.00 |
| February | 495.01 | 649.06 | 562.20 | 381.44 | 180.76 | 0.00 | 0.00 |
| March | 487.81 | 565.29 | 553.16 | 285.59 | 267.57 | 0.00 | 0.00 |
| April | 524.01 | 403.84 | 528.87 | 254.88 | 274.00 | 0.00 | 0.00 |
| May | 561.75 | 334.30 | 544.71 | 225.94 | 318.77 | 0.00 | 0.00 |
| June | 682.43 | 234.23 | 563.76 | 226.90 | 336.87 | 0.00 | 0.00 |
| July | 832.30 | 178.78 | 595.37 | 274.99 | 320.39 | 0.00 | 0.00 |
| August | 817.01 | 203.26 | 606.47 | 314.81 | 291.66 | 0.00 | 0.00 |
| September | 708.28 | 319.77 | 596.70 | 353.84 | 242.85 | 0.00 | 0.00 |
| October | 563.55 | 453.60 | 554.83 | 362.31 | 192.52 | 0.00 | 0.00 |
| November | 411.01 | 570.19 | 469.79 | 321.68 | 148.11 | 0.00 | 0.00 |
| December | 278.67 | 764.96 | 370.38 | 249.29 | 121.08 | 0.00 | 0.00 |
| Annual Sum or Average | 554.33 | 464.80 | 528.68 | 292.45 | 236.23 | 0.00 | 0.00 |
| Minimum of Months | 278.67 | 178.78 | 370.38 | 225.94 | 121.08 | 0.00 | 0.00 |
| Maximum of Months | 832.30 | 907.44 | 606.47 | 381.44 | 336.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1285.70 | 2440.65 | 1449.18 | 1054.69 | 394.48 | 0.00 | 0.00 |
| February | 1945.65 | 1779.50 | 1956.58 | 1458.84 | 497.74 | 0.00 | 0.00 |
| March | 1698.83 | 1586.45 | 1743.80 | 1036.79 | 707.01 | 0.00 | 0.00 |
| April | 1417.17 | 1192.87 | 1371.72 | 714.98 | 656.75 | 0.00 | 0.00 |
| May | 1220.18 | 986.07 | 1178.27 | 443.12 | 735.15 | 0.00 | 0.00 |
| June | 1421.86 | 679.13 | 1142.24 | 386.75 | 755.49 | 0.00 | 0.00 |
| July | 1870.45 | 464.09 | 1258.57 | 527.74 | 730.83 | 0.00 | 0.00 |
| August | 2182.02 | 543.05 | 1547.28 | 853.60 | 693.68 | 0.00 | 0.00 |
| September | 2181.88 | 879.94 | 1757.71 | 1146.10 | 611.61 | 0.00 | 0.00 |
| October | 2028.96 | 1262.29 | 1846.39 | 1330.32 | 516.07 | 0.00 | 0.00 |
| November | 1630.50 | 1591.49 | 1633.32 | 1221.97 | 411.35 | 0.00 | 0.00 |
| December | 1211.03 | 2111.32 | 1309.83 | 969.62 | 340.21 | 0.00 | 0.00 |
| Annual Sum or Average | 1672.42 | 1291.34 | 1513.06 | 925.02 | 588.04 | 0.00 | 0.00 |
| Minimum of Months | 1211.03 | 464.09 | 1142.24 | 386.75 | 340.21 | 0.00 | 0.00 |
| Maximum of Months | 2182.02 | 2440.65 | 1956.58 | 1458.84 | 755.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 11.66 | 160.35 | 27.62 | 11.13 | 16.49 | 0.00 | 0.00 |
| February | 32.76 | 115.15 | 47.14 | 23.17 | 23.97 | 0.00 | 0.00 |
| March | 42.90 | 96.22 | 60.33 | 22.10 | 38.22 | 0.00 | 0.00 |
| April | 73.48 | 68.06 | 78.76 | 34.89 | 43.86 | 0.00 | 0.00 |
| May | 100.91 | 55.59 | 97.42 | 44.43 | 52.99 | 0.00 | 0.00 |
| June | 126.14 | 38.18 | 105.98 | 48.68 | 57.30 | 0.00 | 0.00 |
| July | 147.20 | 27.81 | 108.57 | 54.86 | 53.71 | 0.00 | 0.00 |
| August | 120.81 | 31.13 | 92.19 | 45.25 | 46.95 | 0.00 | 0.00 |
| September | 84.45 | 51.31 | 74.16 | 37.49 | 36.67 | 0.00 | 0.00 |
| October | 46.61 | 75.51 | 53.01 | 26.34 | 26.67 | 0.00 | 0.00 |
| November | 25.69 | 100.21 | 37.52 | 18.61 | 18.91 | 0.00 | 0.00 |
| December | 10.91 | 134.04 | 25.22 | 10.65 | 14.58 | 0.00 | 0.00 |
| Annual Sum or Average | 68.83 | 79.33 | 67.42 | 31.50 | 35.92 | 0.00 | 0.00 |
| Minimum of Months | 10.91 | 27.81 | 25.22 | 10.65 | 14.58 | 0.00 | 0.00 |
| Maximum of Months | 147.20 | 160.35 | 108.57 | 54.86 | 57.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 19.99 | 998.53 | 124.24 | 33.39 | 90.85 | 0.00 | 0.00 |
| February | 92.95 | 707.80 | 199.00 | 69.51 | 129.48 | 0.00 | 0.00 |
| March | 144.27 | 570.92 | 276.60 | 66.31 | 210.28 | 0.00 | 0.00 |
| April | 268.79 | 387.32 | 344.61 | 105.31 | 239.30 | 0.00 | 0.00 |
| May | 393.33 | 316.76 | 434.73 | 142.08 | 292.66 | 0.00 | 0.00 |
| June | 537.12 | 212.41 | 481.28 | 165.79 | 315.49 | 0.00 | 0.00 |
| July | 638.01 | 160.12 | 474.12 | 178.31 | 295.82 | 0.00 | 0.00 |
| August | 507.51 | 180.39 | 396.13 | 139.08 | 257.05 | 0.00 | 0.00 |
| September | 324.23 | 300.03 | 311.92 | 112.51 | 199.41 | 0.00 | 0.00 |
| October | 152.48 | 442.51 | 224.51 | 79.01 | 145.50 | 0.00 | 0.00 |
| November | 63.81 | 600.75 | 156.92 | 55.84 | 101.08 | 0.00 | 0.00 |
| December | 18.90 | 831.98 | 109.78 | 31.94 | 77.84 | 0.00 | 0.00 |
| Annual Sum or Average | 264.47 | 474.99 | 294.95 | 98.37 | 196.59 | 0.00 | 0.00 |
| Minimum of Months | 18.90 | 160.12 | 109.78 | 31.94 | 77.84 | 0.00 | 0.00 |
| Maximum of Months | 638.01 | 998.53 | 481.28 | 178.31 | 315.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.56 | 2810.10 | 186.59 | 0.00 | 186.59 | 0.00 | 0.00 |
| February | 20.11 | 2069.78 | 258.37 | 0.00 | 258.37 | 0.00 | 0.00 |
| March | 53.63 | 1658.99 | 432.46 | 0.00 | 432.46 | 0.00 | 0.00 |
| April | 163.20 | 1155.64 | 487.31 | 2.03 | 485.28 | 0.00 | 0.00 |
| May | 355.22 | 907.58 | 636.87 | 35.35 | 601.52 | 0.00 | 0.00 |
| June | 663.80 | 583.10 | 713.64 | 76.64 | 637.00 | 0.00 | 0.00 |
| July | 895.48 | 400.99 | 660.72 | 57.59 | 603.13 | 0.00 | 0.00 |
| August | 649.80 | 464.10 | 532.58 | 12.40 | 520.18 | 0.00 | 0.00 |
| September | 304.41 | 832.19 | 401.47 | 0.10 | 401.37 | 0.00 | 0.00 |
| October | 59.99 | 1290.13 | 294.32 | 0.00 | 294.32 | 0.00 | 0.00 |
| November | 6.96 | 1779.03 | 198.94 | 0.00 | 198.94 | 0.00 | 0.00 |
| December | 0.34 | 2379.58 | 152.77 | 0.00 | 152.77 | 0.00 | 0.00 |
| Annual Sum or Average | 266.25 | 1358.11 | 413.87 | 15.42 | 398.44 | 0.00 | 0.00 |
| Minimum of Months | 0.34 | 400.99 | 152.77 | 0.00 | 152.77 | 0.00 | 0.00 |
| Maximum of Months | 895.48 | 2810.10 | 713.64 | 76.64 | 637.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 291.33 | 905.51 | 407.55 | 269.61 | 137.95 | 0.00 | 0.00 |
| February | 495.94 | 648.65 | 563.97 | 382.02 | 181.95 | 0.00 | 0.00 |
| March | 488.93 | 566.08 | 554.59 | 285.61 | 268.98 | 0.00 | 0.00 |
| April | 524.90 | 405.49 | 530.51 | 254.88 | 275.63 | 0.00 | 0.00 |
| May | 563.00 | 335.89 | 546.74 | 225.94 | 320.80 | 0.00 | 0.00 |
| June | 684.36 | 235.29 | 566.16 | 226.90 | 339.26 | 0.00 | 0.00 |
| July | 833.63 | 180.32 | 597.60 | 274.99 | 322.62 | 0.00 | 0.00 |
| August | 818.12 | 204.87 | 608.40 | 314.81 | 293.59 | 0.00 | 0.00 |
| September | 709.11 | 321.57 | 598.21 | 353.85 | 244.36 | 0.00 | 0.00 |
| October | 564.11 | 455.50 | 556.26 | 362.60 | 193.66 | 0.00 | 0.00 |
| November | 411.89 | 570.32 | 472.63 | 323.23 | 149.40 | 0.00 | 0.00 |
| December | 286.07 | 762.57 | 379.09 | 255.75 | 123.34 | 0.00 | 0.00 |
| Annual Sum or Average | 556.15 | 465.41 | 531.44 | 293.51 | 237.93 | 0.00 | 0.00 |
| Minimum of Months | 286.07 | 180.32 | 379.09 | 225.94 | 123.34 | 0.00 | 0.00 |
| Maximum of Months | 833.63 | 905.51 | 608.40 | 382.02 | 339.26 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1310.90 | 2430.12 | 1479.37 | 1077.28 | 402.09 | 0.00 | 0.00 |
| February | 1952.56 | 1776.94 | 1966.26 | 1462.67 | 503.59 | 0.00 | 0.00 |
| March | 1704.17 | 1589.68 | 1750.28 | 1037.06 | 713.22 | 0.00 | 0.00 |
| April | 1421.43 | 1199.27 | 1378.90 | 714.98 | 663.92 | 0.00 | 0.00 |
| May | 1226.03 | 992.08 | 1187.16 | 443.12 | 744.04 | 0.00 | 0.00 |
| June | 1430.43 | 683.14 | 1152.77 | 386.75 | 766.02 | 0.00 | 0.00 |
| July | 1876.31 | 470.21 | 1268.36 | 527.74 | 740.62 | 0.00 | 0.00 |
| August | 2187.13 | 549.62 | 1555.76 | 853.61 | 702.15 | 0.00 | 0.00 |
| September | 2185.81 | 887.60 | 1764.37 | 1146.14 | 618.24 | 0.00 | 0.00 |
| October | 2032.94 | 1270.54 | 1853.72 | 1332.32 | 521.40 | 0.00 | 0.00 |
| November | 1643.47 | 1590.15 | 1653.61 | 1234.75 | 418.85 | 0.00 | 0.00 |
| December | 1252.12 | 2097.41 | 1355.68 | 1004.05 | 351.62 | 0.00 | 0.00 |
| Annual Sum or Average | 1683.24 | 1293.01 | 1527.41 | 931.41 | 596.00 | 0.00 | 0.00 |
| Minimum of Months | 1226.03 | 470.21 | 1152.77 | 386.75 | 351.62 | 0.00 | 0.00 |
| Maximum of Months | 2187.13 | 2430.12 | 1966.26 | 1462.67 | 766.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 11.64 | 160.52 | 27.62 | 11.13 | 16.49 | 0.00 | 0.00 |
| February | 32.70 | 115.36 | 47.14 | 23.17 | 23.97 | 0.00 | 0.00 |
| March | 42.74 | 96.66 | 60.33 | 22.10 | 38.22 | 0.00 | 0.00 |
| April | 73.06 | 68.88 | 78.76 | 34.89 | 43.86 | 0.00 | 0.00 |
| May | 100.40 | 56.40 | 97.42 | 44.43 | 52.99 | 0.00 | 0.00 |
| June | 125.70 | 38.72 | 105.98 | 48.68 | 57.30 | 0.00 | 0.00 |
| July | 146.55 | 28.46 | 108.57 | 54.86 | 53.71 | 0.00 | 0.00 |
| August | 120.21 | 31.83 | 92.19 | 45.25 | 46.95 | 0.00 | 0.00 |
| September | 84.01 | 52.19 | 74.16 | 37.49 | 36.67 | 0.00 | 0.00 |
| October | 46.30 | 76.53 | 53.01 | 26.34 | 26.67 | 0.00 | 0.00 |
| November | 25.50 | 101.05 | 37.52 | 18.61 | 18.91 | 0.00 | 0.00 |
| December | 10.87 | 134.32 | 25.22 | 10.65 | 14.58 | 0.00 | 0.00 |
| Annual Sum or Average | 68.50 | 79.95 | 67.42 | 31.50 | 35.92 | 0.00 | 0.00 |
| Minimum of Months | 10.87 | 28.46 | 25.22 | 10.65 | 14.58 | 0.00 | 0.00 |
| Maximum of Months | 146.55 | 160.52 | 108.57 | 54.86 | 57.30 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 21.70 | 996.46 | 131.37 | 33.39 | 97.98 | 0.00 | 0.00 |
| February | 98.45 | 705.44 | 209.92 | 69.51 | 140.41 | 0.00 | 0.00 |
| March | 157.02 | 569.90 | 292.26 | 66.31 | 225.95 | 0.00 | 0.00 |
| April | 285.70 | 389.27 | 363.15 | 105.42 | 257.73 | 0.00 | 0.00 |
| May | 415.93 | 316.82 | 458.88 | 143.15 | 315.72 | 0.00 | 0.00 |
| June | 566.75 | 210.99 | 511.98 | 168.35 | 343.63 | 0.00 | 0.00 |
| July | 664.67 | 161.03 | 502.97 | 181.19 | 321.78 | 0.00 | 0.00 |
| August | 529.57 | 184.31 | 418.61 | 139.54 | 279.06 | 0.00 | 0.00 |
| September | 340.55 | 303.90 | 328.86 | 112.52 | 216.34 | 0.00 | 0.00 |
| October | 161.48 | 445.57 | 236.61 | 79.01 | 157.60 | 0.00 | 0.00 |
| November | 67.82 | 602.29 | 165.32 | 55.84 | 109.47 | 0.00 | 0.00 |
| December | 20.40 | 831.38 | 116.35 | 31.94 | 84.41 | 0.00 | 0.00 |
| Annual Sum or Average | 278.56 | 475.66 | 311.85 | 98.96 | 212.89 | 0.00 | 0.00 |
| Minimum of Months | 20.40 | 161.03 | 116.35 | 31.94 | 84.41 | 0.00 | 0.00 |
| Maximum of Months | 664.67 | 996.46 | 511.98 | 181.19 | 343.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.74 | 1849.08 | 154.91 | 0.00 | 154.91 | 0.00 | 0.00 |
| February | 26.47 | 1351.28 | 218.73 | 0.00 | 218.73 | 0.00 | 0.00 |
| March | 77.90 | 1079.72 | 355.31 | 0.00 | 355.31 | 0.00 | 0.00 |
| April | 173.84 | 756.98 | 405.13 | 2.36 | 402.77 | 0.00 | 0.00 |
| May | 338.33 | 588.79 | 532.04 | 31.53 | 500.51 | 0.00 | 0.00 |
| June | 594.66 | 377.88 | 619.53 | 71.21 | 548.32 | 0.00 | 0.00 |
| July | 730.96 | 275.35 | 565.97 | 53.01 | 512.96 | 0.00 | 0.00 |
| August | 534.68 | 319.17 | 453.52 | 12.16 | 441.36 | 0.00 | 0.00 |
| September | 270.64 | 560.72 | 339.65 | 0.12 | 339.53 | 0.00 | 0.00 |
| October | 68.11 | 853.49 | 247.76 | 0.00 | 247.76 | 0.00 | 0.00 |
| November | 12.38 | 1175.49 | 168.43 | 0.00 | 168.43 | 0.00 | 0.00 |
| December | 0.56 | 1569.64 | 129.90 | 0.00 | 129.90 | 0.00 | 0.00 |
| Annual Sum or Average | 237.28 | 894.69 | 349.94 | 14.27 | 335.67 | 0.00 | 0.00 |
| Minimum of Months | 0.56 | 275.35 | 129.90 | 0.00 | 129.90 | 0.00 | 0.00 |
| Maximum of Months | 730.96 | 1849.08 | 619.53 | 71.21 | 548.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.71 | 961.18 | 79.67 | 0.00 | 79.67 | 0.00 | 0.00 |
| February | 12.07 | 709.47 | 112.49 | 0.00 | 112.49 | 0.00 | 0.00 |
| March | 35.55 | 576.56 | 182.73 | 0.00 | 182.73 | 0.00 | 0.00 |
| April | 80.09 | 417.80 | 208.35 | 1.22 | 207.14 | 0.00 | 0.00 |
| May | 162.82 | 323.86 | 273.62 | 16.21 | 257.40 | 0.00 | 0.00 |
| June | 295.65 | 206.89 | 318.61 | 36.62 | 281.99 | 0.00 | 0.00 |
| July | 358.48 | 154.45 | 291.07 | 27.26 | 263.81 | 0.00 | 0.00 |
| August | 258.44 | 180.84 | 233.23 | 6.25 | 226.98 | 0.00 | 0.00 |
| September | 130.10 | 314.03 | 174.68 | 0.06 | 174.61 | 0.00 | 0.00 |
| October | 30.72 | 469.04 | 127.42 | 0.00 | 127.42 | 0.00 | 0.00 |
| November | 4.69 | 632.27 | 86.62 | 0.00 | 86.62 | 0.00 | 0.00 |
| December | 0.22 | 822.55 | 66.81 | 0.00 | 66.81 | 0.00 | 0.00 |
| Annual Sum or Average | 114.82 | 479.83 | 179.97 | 7.34 | 172.63 | 0.00 | 0.00 |
| Minimum of Months | 0.22 | 154.45 | 66.81 | 0.00 | 66.81 | 0.00 | 0.00 |
| Maximum of Months | 358.48 | 961.18 | 318.61 | 36.62 | 281.99 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.17 | 485.85 | 37.10 | 5.51 | 31.59 | 0.00 | 0.00 |
| February | 29.73 | 349.74 | 73.03 | 25.67 | 47.36 | 0.00 | 0.00 |
| March | 74.58 | 288.92 | 127.74 | 43.28 | 84.46 | 0.00 | 0.00 |
| April | 171.09 | 210.41 | 191.61 | 90.11 | 101.50 | 0.00 | 0.00 |
| May | 241.04 | 176.40 | 238.71 | 115.47 | 123.23 | 0.00 | 0.00 |
| June | 304.69 | 123.43 | 258.09 | 125.91 | 132.18 | 0.00 | 0.00 |
| July | 372.54 | 88.59 | 276.45 | 149.75 | 126.70 | 0.00 | 0.00 |
| August | 293.50 | 97.86 | 225.71 | 116.75 | 108.96 | 0.00 | 0.00 |
| September | 189.36 | 154.98 | 170.59 | 87.58 | 83.01 | 0.00 | 0.00 |
| October | 68.09 | 221.57 | 94.90 | 39.66 | 55.24 | 0.00 | 0.00 |
| November | 12.12 | 299.38 | 48.30 | 13.26 | 35.04 | 0.00 | 0.00 |
| December | 0.17 | 412.78 | 28.97 | 3.34 | 25.63 | 0.00 | 0.00 |
| Annual Sum or Average | 147.22 | 242.11 | 148.00 | 68.25 | 79.75 | 0.00 | 0.00 |
| Minimum of Months | 0.17 | 88.59 | 28.97 | 3.34 | 25.63 | 0.00 | 0.00 |
| Maximum of Months | 372.54 | 485.85 | 276.45 | 149.75 | 132.18 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 549.21 | 763.17 | 592.79 | 423.38 | 169.41 | 0.00 | 0.00 |
| February | 783.24 | 571.24 | 754.91 | 542.96 | 211.95 | 0.00 | 0.00 |
| March | 689.61 | 517.37 | 674.79 | 378.93 | 295.86 | 0.00 | 0.00 |
| April | 582.74 | 386.82 | 542.42 | 259.44 | 282.98 | 0.00 | 0.00 |
| May | 521.30 | 319.81 | 481.93 | 160.06 | 321.86 | 0.00 | 0.00 |
| June | 595.18 | 234.42 | 478.84 | 139.65 | 339.19 | 0.00 | 0.00 |
| July | 729.07 | 184.49 | 516.24 | 190.70 | 325.54 | 0.00 | 0.00 |
| August | 843.25 | 204.53 | 613.52 | 309.32 | 304.19 | 0.00 | 0.00 |
| September | 849.49 | 302.49 | 680.46 | 416.94 | 263.52 | 0.00 | 0.00 |
| October | 806.21 | 412.51 | 711.39 | 491.92 | 219.47 | 0.00 | 0.00 |
| November | 667.23 | 501.69 | 648.58 | 469.80 | 178.77 | 0.00 | 0.00 |
| December | 532.60 | 654.51 | 563.71 | 407.06 | 156.65 | 0.00 | 0.00 |
| Annual Sum or Average | 678.30 | 420.56 | 603.92 | 347.89 | 256.03 | 0.00 | 0.00 |
| Minimum of Months | 521.30 | 184.49 | 478.84 | 139.65 | 156.65 | 0.00 | 0.00 |
| Maximum of Months | 849.49 | 763.17 | 754.91 | 542.96 | 339.19 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 5.79 | 495.05 | 47.72 | 10.35 | 37.37 | 0.00 | 0.00 |
| February | 51.38 | 353.41 | 94.49 | 38.44 | 56.05 | 0.00 | 0.00 |
| March | 98.35 | 301.63 | 152.36 | 54.29 | 98.07 | 0.00 | 0.00 |
| April | 199.20 | 229.00 | 219.70 | 103.67 | 116.02 | 0.00 | 0.00 |
| May | 271.50 | 195.08 | 270.31 | 130.10 | 140.21 | 0.00 | 0.00 |
| June | 334.19 | 144.28 | 291.79 | 141.50 | 150.29 | 0.00 | 0.00 |
| July | 411.25 | 106.48 | 312.30 | 168.44 | 143.85 | 0.00 | 0.00 |
| August | 328.70 | 114.67 | 257.56 | 133.34 | 124.22 | 0.00 | 0.00 |
| September | 219.08 | 177.50 | 199.42 | 103.95 | 95.47 | 0.00 | 0.00 |
| October | 91.95 | 245.42 | 118.83 | 53.97 | 64.86 | 0.00 | 0.00 |
| November | 26.09 | 315.68 | 64.49 | 22.75 | 41.74 | 0.00 | 0.00 |
| December | 2.79 | 421.50 | 37.45 | 7.06 | 30.39 | 0.00 | 0.00 |
| Annual Sum or Average | 170.73 | 257.98 | 172.60 | 80.87 | 91.74 | 0.00 | 0.00 |
| Minimum of Months | 2.79 | 106.48 | 37.45 | 7.06 | 30.39 | 0.00 | 0.00 |
| Maximum of Months | 411.25 | 495.05 | 312.30 | 168.44 | 150.29 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 604.01 | 1882.48 | 868.61 | 565.79 | 302.82 | 0.00 | 0.00 |
| February | 1010.19 | 1382.90 | 1168.18 | 765.84 | 402.34 | 0.00 | 0.00 |
| March | 1047.36 | 1226.25 | 1194.66 | 604.53 | 590.13 | 0.00 | 0.00 |
| April | 1114.97 | 916.99 | 1172.20 | 570.57 | 601.63 | 0.00 | 0.00 |
| May | 1139.45 | 758.38 | 1165.26 | 458.38 | 706.88 | 0.00 | 0.00 |
| June | 1561.13 | 520.36 | 1348.07 | 575.72 | 772.35 | 0.00 | 0.00 |
| July | 1883.25 | 403.46 | 1429.96 | 696.61 | 733.36 | 0.00 | 0.00 |
| August | 1835.75 | 459.14 | 1424.94 | 758.00 | 666.94 | 0.00 | 0.00 |
| September | 1475.52 | 708.45 | 1280.40 | 733.54 | 546.86 | 0.00 | 0.00 |
| October | 1162.31 | 983.19 | 1165.30 | 736.16 | 429.14 | 0.00 | 0.00 |
| November | 794.91 | 1203.64 | 957.06 | 631.40 | 325.66 | 0.00 | 0.00 |
| December | 578.69 | 1594.86 | 800.22 | 526.00 | 274.22 | 0.00 | 0.00 |
| Annual Sum or Average | 1184.81 | 1002.04 | 1164.27 | 634.22 | 530.05 | 0.00 | 0.00 |
| Minimum of Months | 578.69 | 403.46 | 800.22 | 458.38 | 274.22 | 0.00 | 0.00 |
| Maximum of Months | 1883.25 | 1882.48 | 1429.96 | 765.84 | 772.35 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 108.15 | 1814.48 | 391.51 | 163.04 | 228.47 | 0.00 | 0.00 |
| February | 400.34 | 1348.98 | 640.31 | 332.67 | 307.64 | 0.00 | 0.00 |
| March | 784.98 | 1173.99 | 974.03 | 434.42 | 539.61 | 0.00 | 0.00 |
| April | 1183.69 | 895.42 | 1248.74 | 673.89 | 574.85 | 0.00 | 0.00 |
| May | 1586.15 | 727.88 | 1513.43 | 802.62 | 710.82 | 0.00 | 0.00 |
| June | 2234.83 | 505.85 | 1868.01 | 1118.11 | 749.90 | 0.00 | 0.00 |
| July | 2512.26 | 421.94 | 1945.42 | 1271.28 | 674.14 | 0.00 | 0.00 |
| August | 2053.01 | 466.13 | 1628.78 | 1033.08 | 595.70 | 0.00 | 0.00 |
| September | 1290.21 | 669.69 | 1147.32 | 678.61 | 468.71 | 0.00 | 0.00 |
| October | 655.78 | 949.69 | 752.42 | 403.54 | 348.88 | 0.00 | 0.00 |
| November | 226.27 | 1210.23 | 450.82 | 210.06 | 240.76 | 0.00 | 0.00 |
| December | 66.59 | 1580.29 | 316.33 | 124.24 | 192.08 | 0.00 | 0.00 |
| Annual Sum or Average | 1095.98 | 979.10 | 1075.49 | 605.30 | 470.19 | 0.00 | 0.00 |
| Minimum of Months | 66.59 | 421.94 | 316.33 | 124.24 | 192.08 | 0.00 | 0.00 |
| Maximum of Months | 2512.26 | 1814.48 | 1945.42 | 1271.28 | 749.90 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 29.22 | 483.74 | 81.30 | 37.27 | 44.03 | 0.00 | 0.00 |
| February | 74.33 | 375.96 | 127.17 | 63.14 | 64.03 | 0.00 | 0.00 |
| March | 110.53 | 314.39 | 170.99 | 70.75 | 100.24 | 0.00 | 0.00 |
| April | 182.73 | 230.92 | 218.16 | 108.12 | 110.04 | 0.00 | 0.00 |
| May | 223.84 | 181.62 | 240.99 | 107.22 | 133.77 | 0.00 | 0.00 |
| June | 358.45 | 113.70 | 311.93 | 160.52 | 151.41 | 0.00 | 0.00 |
| July | 420.59 | 88.21 | 327.38 | 185.08 | 142.30 | 0.00 | 0.00 |
| August | 355.01 | 100.83 | 284.51 | 158.52 | 125.99 | 0.00 | 0.00 |
| September | 213.85 | 153.07 | 201.26 | 103.89 | 97.37 | 0.00 | 0.00 |
| October | 114.29 | 232.33 | 144.39 | 73.32 | 71.07 | 0.00 | 0.00 |
| November | 44.57 | 325.78 | 91.51 | 42.72 | 48.79 | 0.00 | 0.00 |
| December | 20.15 | 427.02 | 67.50 | 28.99 | 38.51 | 0.00 | 0.00 |
| Annual Sum or Average | 179.59 | 251.79 | 189.25 | 95.13 | 94.12 | 0.00 | 0.00 |
| Minimum of Months | 20.15 | 88.21 | 67.50 | 28.99 | 38.51 | 0.00 | 0.00 |
| Maximum of Months | 420.59 | 483.74 | 327.38 | 185.08 | 151.41 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 27.54 | 1829.71 | 239.80 | 69.89 | 169.91 | 0.00 | 0.00 |
| February | 124.35 | 1345.44 | 361.61 | 118.38 | 243.22 | 0.00 | 0.00 |
| March | 234.35 | 1103.27 | 521.39 | 132.66 | 388.73 | 0.00 | 0.00 |
| April | 423.83 | 797.50 | 636.20 | 203.78 | 432.42 | 0.00 | 0.00 |
| May | 589.08 | 650.49 | 744.10 | 213.71 | 530.39 | 0.00 | 0.00 |
| June | 964.58 | 440.14 | 920.88 | 332.41 | 588.46 | 0.00 | 0.00 |
| July | 1145.95 | 347.12 | 930.18 | 375.24 | 554.94 | 0.00 | 0.00 |
| August | 918.26 | 386.28 | 785.94 | 302.13 | 483.81 | 0.00 | 0.00 |
| September | 520.79 | 596.20 | 568.68 | 194.84 | 373.84 | 0.00 | 0.00 |
| October | 227.51 | 848.95 | 410.36 | 137.48 | 272.88 | 0.00 | 0.00 |
| November | 57.67 | 1170.82 | 266.34 | 80.11 | 186.23 | 0.00 | 0.00 |
| December | 13.32 | 1570.08 | 199.52 | 54.36 | 145.16 | 0.00 | 0.00 |
| Annual Sum or Average | 439.24 | 922.26 | 549.75 | 184.93 | 364.82 | 0.00 | 0.00 |
| Minimum of Months | 13.32 | 347.12 | 199.52 | 54.36 | 145.16 | 0.00 | 0.00 |
| Maximum of Months | 1145.95 | 1829.71 | 930.18 | 375.24 | 588.46 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 27.35 | 2016.83 | 252.01 | 64.62 | 187.40 | 0.00 | 0.00 |
| February | 153.57 | 1453.11 | 405.81 | 133.68 | 272.13 | 0.00 | 0.00 |
| March | 309.33 | 1192.15 | 613.41 | 172.13 | 441.27 | 0.00 | 0.00 |
| April | 549.05 | 886.24 | 766.60 | 273.68 | 492.92 | 0.00 | 0.00 |
| May | 743.41 | 722.86 | 899.30 | 293.26 | 606.04 | 0.00 | 0.00 |
| June | 1216.84 | 477.33 | 1131.79 | 455.03 | 676.77 | 0.00 | 0.00 |
| July | 1438.70 | 373.99 | 1142.30 | 507.42 | 634.89 | 0.00 | 0.00 |
| August | 1152.91 | 422.55 | 964.13 | 409.88 | 554.25 | 0.00 | 0.00 |
| September | 644.97 | 672.33 | 682.06 | 256.35 | 425.71 | 0.00 | 0.00 |
| October | 270.95 | 971.26 | 474.25 | 166.49 | 307.76 | 0.00 | 0.00 |
| November | 60.68 | 1289.62 | 287.45 | 81.34 | 206.11 | 0.00 | 0.00 |
| December | 9.94 | 1720.60 | 203.64 | 45.88 | 157.75 | 0.00 | 0.00 |
| Annual Sum or Average | 550.62 | 1015.01 | 653.20 | 238.86 | 414.34 | 0.00 | 0.00 |
| Minimum of Months | 9.94 | 373.99 | 203.64 | 45.88 | 157.75 | 0.00 | 0.00 |
| Maximum of Months | 1438.70 | 2016.83 | 1142.30 | 507.42 | 676.77 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.802867E+09 | 0.240337E+10 | 0.114110E+10 | 0.745932E+09 | 0.395165E+09 | 0.00 | 0.00 |
| February | 0.122678E+10 | 0.156848E+10 | 0.139940E+10 | 0.928608E+09 | 0.470796E+09 | 0.00 | 0.00 |
| March | 0.135581E+10 | 0.152180E+10 | 0.153107E+10 | 0.765188E+09 | 0.765883E+09 | 0.00 | 0.00 |
| April | 0.141397E+10 | 0.105413E+10 | 0.142636E+10 | 0.660641E+09 | 0.765716E+09 | 0.00 | 0.00 |
| May | 0.157920E+10 | 0.899767E+09 | 0.153003E+10 | 0.605169E+09 | 0.924865E+09 | 0.00 | 0.00 |
| June | 0.185914E+10 | 0.613644E+09 | 0.154268E+10 | 0.588118E+09 | 0.954565E+09 | 0.00 | 0.00 |
| July | 0.231460E+10 | 0.491691E+09 | 0.167286E+10 | 0.736521E+09 | 0.936343E+09 | 0.00 | 0.00 |
| August | 0.226142E+10 | 0.557044E+09 | 0.169209E+10 | 0.843192E+09 | 0.848899E+09 | 0.00 | 0.00 |
| September | 0.189095E+10 | 0.839811E+09 | 0.159777E+10 | 0.917202E+09 | 0.680571E+09 | 0.00 | 0.00 |
| October | 0.154927E+10 | 0.122423E+10 | 0.152899E+10 | 0.974377E+09 | 0.554612E+09 | 0.00 | 0.00 |
| November | 0.109056E+10 | 0.146854E+10 | 0.126502E+10 | 0.849723E+09 | 0.415295E+09 | 0.00 | 0.00 |
| December | 0.795877E+09 | 0.201540E+10 | 0.107676E+10 | 0.716722E+09 | 0.360035E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.181405E+11 | 0.146579E+11 | 0.174041E+11 | 0.933139E+10 | 0.807275E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.795877E+09 | 0.491691E+09 | 0.107676E+10 | 0.588118E+09 | 0.360035E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.231460E+10 | 0.240337E+10 | 0.169209E+10 | 0.974377E+09 | 0.954565E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.388399E+10 | 0.637877E+10 | 0.442891E+10 | 0.316322E+10 | 0.126569E+10 | 0.00 | 0.00 |
| February | 0.505429E+10 | 0.428359E+10 | 0.509433E+10 | 0.366403E+10 | 0.143030E+10 | 0.00 | 0.00 |
| March | 0.494398E+10 | 0.427307E+10 | 0.504156E+10 | 0.283111E+10 | 0.221045E+10 | 0.00 | 0.00 |
| April | 0.404838E+10 | 0.310303E+10 | 0.392184E+10 | 0.187584E+10 | 0.204600E+10 | 0.00 | 0.00 |
| May | 0.373429E+10 | 0.262562E+10 | 0.360061E+10 | 0.119586E+10 | 0.240475E+10 | 0.00 | 0.00 |
| June | 0.424395E+10 | 0.176980E+10 | 0.346216E+10 | 0.100973E+10 | 0.245243E+10 | 0.00 | 0.00 |
| July | 0.555513E+10 | 0.130971E+10 | 0.385697E+10 | 0.142475E+10 | 0.243222E+10 | 0.00 | 0.00 |
| August | 0.633872E+10 | 0.152071E+10 | 0.458376E+10 | 0.231105E+10 | 0.227271E+10 | 0.00 | 0.00 |
| September | 0.606924E+10 | 0.233697E+10 | 0.491994E+10 | 0.301461E+10 | 0.190533E+10 | 0.00 | 0.00 |
| October | 0.582493E+10 | 0.342115E+10 | 0.531499E+10 | 0.367525E+10 | 0.163974E+10 | 0.00 | 0.00 |
| November | 0.460056E+10 | 0.404010E+10 | 0.468938E+10 | 0.339680E+10 | 0.129258E+10 | 0.00 | 0.00 |
| December | 0.380415E+10 | 0.542852E+10 | 0.421165E+10 | 0.304124E+10 | 0.117041E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.581016E+11 | 0.404910E+11 | 0.531261E+11 | 0.306035E+11 | 0.225226E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.373429E+10 | 0.130971E+10 | 0.346216E+10 | 0.100973E+10 | 0.117041E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.633872E+10 | 0.637877E+10 | 0.531499E+10 | 0.367525E+10 | 0.245243E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 31150865.41 | 0.429959E+09 | 73970815.50 | 29810793.60 | 44160021.90 | 0.00 | 0.00 |
| February | 79171468.92 | 0.278746E+09 | 0.114039E+09 | 56055770.97 | 57982836.54 | 0.00 | 0.00 |
| March | 0.114820E+09 | 0.257875E+09 | 0.161578E+09 | 59204732.84 | 0.102374E+09 | 0.00 | 0.00 |
| April | 0.190379E+09 | 0.176468E+09 | 0.204137E+09 | 90442042.89 | 0.113695E+09 | 0.00 | 0.00 |
| May | 0.270146E+09 | 0.149030E+09 | 0.260919E+09 | 0.118993E+09 | 0.141926E+09 | 0.00 | 0.00 |
| June | 0.326787E+09 | 99108255.97 | 0.274713E+09 | 0.126186E+09 | 0.148527E+09 | 0.00 | 0.00 |
| July | 0.393897E+09 | 74812117.93 | 0.290793E+09 | 0.146942E+09 | 0.143851E+09 | 0.00 | 0.00 |
| August | 0.323263E+09 | 83720853.69 | 0.246923E+09 | 0.121185E+09 | 0.125738E+09 | 0.00 | 0.00 |
| September | 0.218735E+09 | 0.133208E+09 | 0.192226E+09 | 97181884.34 | 95044555.50 | 0.00 | 0.00 |
| October | 0.124690E+09 | 0.202567E+09 | 0.141969E+09 | 70536604.45 | 71432123.70 | 0.00 | 0.00 |
| November | 66406740.62 | 0.260513E+09 | 97258402.11 | 48248465.95 | 49009936.16 | 0.00 | 0.00 |
| December | 29080289.15 | 0.359841E+09 | 67554597.73 | 28512887.97 | 39041709.75 | 0.00 | 0.00 |
| Annual Sum or Average | 0.216853E+10 | 0.250585E+10 | 0.212608E+10 | 0.993299E+09 | 0.113278E+10 | 0.00 | 0.00 |
| Minimum of Months | 29080289.15 | 74812117.93 | 67554597.73 | 28512887.97 | 39041709.75 | 0.00 | 0.00 |
| Maximum of Months | 0.393897E+09 | 0.429959E+09 | 0.290793E+09 | 0.146942E+09 | 0.148527E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 53150828.15 | 0.267491E+10 | 0.331228E+09 | 89432082.68 | 0.241796E+09 | 0.00 | 0.00 |
| February | 0.223776E+09 | 0.171279E+10 | 0.479307E+09 | 0.168167E+09 | 0.311141E+09 | 0.00 | 0.00 |
| March | 0.383741E+09 | 0.152951E+10 | 0.737489E+09 | 0.177614E+09 | 0.559875E+09 | 0.00 | 0.00 |
| April | 0.693199E+09 | 0.100395E+10 | 0.889303E+09 | 0.272886E+09 | 0.616418E+09 | 0.00 | 0.00 |
| May | 0.104852E+10 | 0.849190E+09 | 0.115892E+10 | 0.380073E+09 | 0.778842E+09 | 0.00 | 0.00 |
| June | 0.138551E+10 | 0.551815E+09 | 0.124034E+10 | 0.428660E+09 | 0.811676E+09 | 0.00 | 0.00 |
| July | 0.170169E+10 | 0.429599E+09 | 0.126290E+10 | 0.476336E+09 | 0.786561E+09 | 0.00 | 0.00 |
| August | 0.135409E+10 | 0.483271E+09 | 0.105600E+10 | 0.372306E+09 | 0.683694E+09 | 0.00 | 0.00 |
| September | 0.836810E+09 | 0.777323E+09 | 0.804994E+09 | 0.291615E+09 | 0.513378E+09 | 0.00 | 0.00 |
| October | 0.406357E+09 | 0.118523E+10 | 0.598733E+09 | 0.211609E+09 | 0.387124E+09 | 0.00 | 0.00 |
| November | 0.164350E+09 | 0.155790E+10 | 0.405001E+09 | 0.144745E+09 | 0.260256E+09 | 0.00 | 0.00 |
| December | 50250474.21 | 0.222898E+10 | 0.292632E+09 | 85538378.79 | 0.207093E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.830145E+10 | 0.149845E+11 | 0.925683E+10 | 0.309898E+10 | 0.615785E+10 | 0.00 | 0.00 |
| Minimum of Months | 50250474.21 | 0.429599E+09 | 0.292632E+09 | 85538378.79 | 0.207093E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.170169E+10 | 0.267491E+10 | 0.126290E+10 | 0.476336E+09 | 0.811676E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 1325989.26 | 0.752977E+10 | 0.492297E+09 | 0.00 | 0.492297E+09 | 0.00 | 0.00 |
| February | 46148602.08 | 0.501172E+10 | 0.614734E+09 | 0.00 | 0.614734E+09 | 0.00 | 0.00 |
| March | 0.135430E+09 | 0.444998E+10 | 0.114190E+10 | 0.00 | 0.114190E+10 | 0.00 | 0.00 |
| April | 0.408976E+09 | 0.299861E+10 | 0.124420E+10 | 5174028.17 | 0.123903E+10 | 0.00 | 0.00 |
| May | 0.927334E+09 | 0.243752E+10 | 0.167798E+10 | 91789424.18 | 0.158619E+10 | 0.00 | 0.00 |
| June | 0.168186E+10 | 0.151792E+10 | 0.181121E+10 | 0.191095E+09 | 0.162012E+10 | 0.00 | 0.00 |
| July | 0.236370E+10 | 0.107447E+10 | 0.173814E+10 | 0.150302E+09 | 0.158783E+10 | 0.00 | 0.00 |
| August | 0.171343E+10 | 0.124233E+10 | 0.140188E+10 | 32085480.17 | 0.136979E+10 | 0.00 | 0.00 |
| September | 0.773001E+09 | 0.215689E+10 | 0.102352E+10 | 269747.67 | 0.102325E+10 | 0.00 | 0.00 |
| October | 0.154751E+09 | 0.345892E+10 | 0.775651E+09 | 0.00 | 0.775651E+09 | 0.00 | 0.00 |
| November | 16406799.07 | 0.461616E+10 | 0.507149E+09 | 0.00 | 0.507149E+09 | 0.00 | 0.00 |
| December | 852032.16 | 0.637679E+10 | 0.402302E+09 | 0.00 | 0.402302E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.822321E+10 | 0.428711E+11 | 0.128309E+11 | 0.470715E+09 | 0.123602E+11 | 0.00 | 0.00 |
| Minimum of Months | 852032.16 | 0.107447E+10 | 0.402302E+09 | 0.00 | 0.402302E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.236370E+10 | 0.752977E+10 | 0.181121E+10 | 0.191095E+09 | 0.162012E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.771138E+09 | 0.243048E+10 | 0.107813E+10 | 0.712297E+09 | 0.365838E+09 | 0.00 | 0.00 |
| February | 0.119752E+10 | 0.157021E+10 | 0.136007E+10 | 0.922778E+09 | 0.437290E+09 | 0.00 | 0.00 |
| March | 0.130654E+10 | 0.151407E+10 | 0.148158E+10 | 0.764922E+09 | 0.716659E+09 | 0.00 | 0.00 |
| April | 0.135824E+10 | 0.104676E+10 | 0.137084E+10 | 0.660641E+09 | 0.710196E+09 | 0.00 | 0.00 |
| May | 0.150459E+10 | 0.895394E+09 | 0.145896E+10 | 0.605169E+09 | 0.853791E+09 | 0.00 | 0.00 |
| June | 0.176885E+10 | 0.607131E+09 | 0.146127E+10 | 0.588118E+09 | 0.873156E+09 | 0.00 | 0.00 |
| July | 0.222923E+10 | 0.478855E+09 | 0.159465E+10 | 0.736521E+09 | 0.858128E+09 | 0.00 | 0.00 |
| August | 0.218829E+10 | 0.544405E+09 | 0.162438E+10 | 0.843192E+09 | 0.781184E+09 | 0.00 | 0.00 |
| September | 0.183586E+10 | 0.828855E+09 | 0.154664E+10 | 0.917164E+09 | 0.629479E+09 | 0.00 | 0.00 |
| October | 0.150940E+10 | 0.121493E+10 | 0.148607E+10 | 0.970411E+09 | 0.515658E+09 | 0.00 | 0.00 |
| November | 0.106533E+10 | 0.147794E+10 | 0.121770E+10 | 0.833793E+09 | 0.383906E+09 | 0.00 | 0.00 |
| December | 0.746378E+09 | 0.204887E+10 | 0.992018E+09 | 0.667707E+09 | 0.324311E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.174814E+11 | 0.146579E+11 | 0.166723E+11 | 0.922271E+10 | 0.744960E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.746378E+09 | 0.478855E+09 | 0.992018E+09 | 0.588118E+09 | 0.324311E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.222923E+10 | 0.243048E+10 | 0.162438E+10 | 0.970411E+09 | 0.873156E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.344361E+10 | 0.653703E+10 | 0.388147E+10 | 0.282489E+10 | 0.105659E+10 | 0.00 | 0.00 |
| February | 0.470691E+10 | 0.430496E+10 | 0.473337E+10 | 0.352923E+10 | 0.120414E+10 | 0.00 | 0.00 |
| March | 0.455015E+10 | 0.424915E+10 | 0.467059E+10 | 0.277694E+10 | 0.189365E+10 | 0.00 | 0.00 |
| April | 0.367330E+10 | 0.309193E+10 | 0.355550E+10 | 0.185322E+10 | 0.170228E+10 | 0.00 | 0.00 |
| May | 0.326813E+10 | 0.264108E+10 | 0.315587E+10 | 0.118684E+10 | 0.196903E+10 | 0.00 | 0.00 |
| June | 0.368547E+10 | 0.176031E+10 | 0.296069E+10 | 0.100246E+10 | 0.195824E+10 | 0.00 | 0.00 |
| July | 0.500982E+10 | 0.124303E+10 | 0.337096E+10 | 0.141350E+10 | 0.195745E+10 | 0.00 | 0.00 |
| August | 0.584433E+10 | 0.145451E+10 | 0.414423E+10 | 0.228629E+10 | 0.185794E+10 | 0.00 | 0.00 |
| September | 0.565543E+10 | 0.228080E+10 | 0.455600E+10 | 0.297070E+10 | 0.158530E+10 | 0.00 | 0.00 |
| October | 0.543438E+10 | 0.338091E+10 | 0.494538E+10 | 0.356314E+10 | 0.138224E+10 | 0.00 | 0.00 |
| November | 0.422626E+10 | 0.412515E+10 | 0.423355E+10 | 0.316734E+10 | 0.106621E+10 | 0.00 | 0.00 |
| December | 0.324361E+10 | 0.565496E+10 | 0.350826E+10 | 0.259703E+10 | 0.911227E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.527414E+11 | 0.407238E+11 | 0.477159E+11 | 0.291716E+11 | 0.185443E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.324361E+10 | 0.124303E+10 | 0.296069E+10 | 0.100246E+10 | 0.911227E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.584433E+10 | 0.653703E+10 | 0.494538E+10 | 0.356314E+10 | 0.196903E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 31239494.91 | 0.429475E+09 | 73970815.50 | 29810793.60 | 44160021.90 | 0.00 | 0.00 |
| February | 79256714.69 | 0.278572E+09 | 0.114039E+09 | 56055770.97 | 57982836.54 | 0.00 | 0.00 |
| March | 0.114911E+09 | 0.257716E+09 | 0.161578E+09 | 59204732.84 | 0.102374E+09 | 0.00 | 0.00 |
| April | 0.190462E+09 | 0.176400E+09 | 0.204137E+09 | 90442042.89 | 0.113695E+09 | 0.00 | 0.00 |
| May | 0.270282E+09 | 0.148889E+09 | 0.260919E+09 | 0.118993E+09 | 0.141926E+09 | 0.00 | 0.00 |
| June | 0.326954E+09 | 98959514.52 | 0.274713E+09 | 0.126186E+09 | 0.148527E+09 | 0.00 | 0.00 |
| July | 0.394254E+09 | 74486503.87 | 0.290793E+09 | 0.146942E+09 | 0.143851E+09 | 0.00 | 0.00 |
| August | 0.323589E+09 | 83383416.16 | 0.246923E+09 | 0.121185E+09 | 0.125738E+09 | 0.00 | 0.00 |
| September | 0.218891E+09 | 0.133002E+09 | 0.192226E+09 | 97181884.34 | 95044555.50 | 0.00 | 0.00 |
| October | 0.124832E+09 | 0.202259E+09 | 0.141969E+09 | 70536604.45 | 71432123.70 | 0.00 | 0.00 |
| November | 66600012.63 | 0.259754E+09 | 97258402.11 | 48248465.95 | 49009936.16 | 0.00 | 0.00 |
| December | 29214624.20 | 0.359000E+09 | 67554597.73 | 28512887.97 | 39041709.75 | 0.00 | 0.00 |
| Annual Sum or Average | 0.217049E+10 | 0.250189E+10 | 0.212608E+10 | 0.993299E+09 | 0.113278E+10 | 0.00 | 0.00 |
| Minimum of Months | 29214624.20 | 74486503.87 | 67554597.73 | 28512887.97 | 39041709.75 | 0.00 | 0.00 |
| Maximum of Months | 0.394254E+09 | 0.429475E+09 | 0.290793E+09 | 0.146942E+09 | 0.148527E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 53541292.69 | 0.267445E+10 | 0.332752E+09 | 89432082.68 | 0.243320E+09 | 0.00 | 0.00 |
| February | 0.224856E+09 | 0.171232E+10 | 0.481412E+09 | 0.168167E+09 | 0.313245E+09 | 0.00 | 0.00 |
| March | 0.386418E+09 | 0.152915E+10 | 0.740839E+09 | 0.177614E+09 | 0.563226E+09 | 0.00 | 0.00 |
| April | 0.696716E+09 | 0.100392E+10 | 0.893228E+09 | 0.272958E+09 | 0.620270E+09 | 0.00 | 0.00 |
| May | 0.105350E+10 | 0.848423E+09 | 0.116439E+10 | 0.380542E+09 | 0.783852E+09 | 0.00 | 0.00 |
| June | 0.139221E+10 | 0.550575E+09 | 0.124749E+10 | 0.429732E+09 | 0.817753E+09 | 0.00 | 0.00 |
| July | 0.170884E+10 | 0.428872E+09 | 0.126989E+10 | 0.477578E+09 | 0.792312E+09 | 0.00 | 0.00 |
| August | 0.135931E+10 | 0.483166E+09 | 0.106099E+10 | 0.372515E+09 | 0.688475E+09 | 0.00 | 0.00 |
| September | 0.840395E+09 | 0.777668E+09 | 0.808484E+09 | 0.291615E+09 | 0.516869E+09 | 0.00 | 0.00 |
| October | 0.408406E+09 | 0.118522E+10 | 0.601316E+09 | 0.211609E+09 | 0.389707E+09 | 0.00 | 0.00 |
| November | 0.165408E+09 | 0.155713E+10 | 0.406734E+09 | 0.144745E+09 | 0.261990E+09 | 0.00 | 0.00 |
| December | 50617636.82 | 0.222836E+10 | 0.294033E+09 | 85538378.79 | 0.208495E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.834023E+10 | 0.149793E+11 | 0.930156E+10 | 0.310205E+10 | 0.619951E+10 | 0.00 | 0.00 |
| Minimum of Months | 50617636.82 | 0.428872E+09 | 0.294033E+09 | 85538378.79 | 0.208495E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.170884E+10 | 0.267445E+10 | 0.126989E+10 | 0.477578E+09 | 0.817753E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 1504095.13 | 0.752658E+10 | 0.499766E+09 | 0.00 | 0.499766E+09 | 0.00 | 0.00 |
| February | 48660258.00 | 0.500721E+10 | 0.625045E+09 | 0.00 | 0.625045E+09 | 0.00 | 0.00 |
| March | 0.143637E+09 | 0.444344E+10 | 0.115831E+10 | 0.00 | 0.115831E+10 | 0.00 | 0.00 |
| April | 0.423020E+09 | 0.299543E+10 | 0.126312E+10 | 5258992.68 | 0.125786E+10 | 0.00 | 0.00 |
| May | 0.951426E+09 | 0.243086E+10 | 0.170580E+10 | 94676671.78 | 0.161112E+10 | 0.00 | 0.00 |
| June | 0.172058E+10 | 0.151141E+10 | 0.184976E+10 | 0.198659E+09 | 0.165110E+10 | 0.00 | 0.00 |
| July | 0.239845E+10 | 0.107401E+10 | 0.176968E+10 | 0.154255E+09 | 0.161542E+10 | 0.00 | 0.00 |
| August | 0.174041E+10 | 0.124304E+10 | 0.142646E+10 | 33207185.75 | 0.139325E+10 | 0.00 | 0.00 |
| September | 0.789033E+09 | 0.215704E+10 | 0.104061E+10 | 269747.67 | 0.104034E+10 | 0.00 | 0.00 |
| October | 0.160669E+09 | 0.345550E+10 | 0.788306E+09 | 0.00 | 0.788306E+09 | 0.00 | 0.00 |
| November | 18042551.33 | 0.461125E+10 | 0.515642E+09 | 0.00 | 0.515642E+09 | 0.00 | 0.00 |
| December | 917771.52 | 0.637347E+10 | 0.409167E+09 | 0.00 | 0.409167E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.839635E+10 | 0.428292E+11 | 0.130517E+11 | 0.486327E+09 | 0.125653E+11 | 0.00 | 0.00 |
| Minimum of Months | 917771.52 | 0.107401E+10 | 0.409167E+09 | 0.00 | 0.409167E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.239845E+10 | 0.752658E+10 | 0.184976E+10 | 0.198659E+09 | 0.165110E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.780310E+09 | 0.242531E+10 | 0.109159E+10 | 0.722118E+09 | 0.369474E+09 | 0.00 | 0.00 |
| February | 0.119979E+10 | 0.156921E+10 | 0.136435E+10 | 0.924177E+09 | 0.440177E+09 | 0.00 | 0.00 |
| March | 0.130955E+10 | 0.151618E+10 | 0.148542E+10 | 0.764982E+09 | 0.720434E+09 | 0.00 | 0.00 |
| April | 0.136055E+10 | 0.105102E+10 | 0.137508E+10 | 0.660641E+09 | 0.714435E+09 | 0.00 | 0.00 |
| May | 0.150794E+10 | 0.899642E+09 | 0.146439E+10 | 0.605169E+09 | 0.859218E+09 | 0.00 | 0.00 |
| June | 0.177385E+10 | 0.609882E+09 | 0.146749E+10 | 0.588118E+09 | 0.879372E+09 | 0.00 | 0.00 |
| July | 0.223279E+10 | 0.482968E+09 | 0.160062E+10 | 0.736521E+09 | 0.864100E+09 | 0.00 | 0.00 |
| August | 0.219126E+10 | 0.548732E+09 | 0.162955E+10 | 0.843192E+09 | 0.786355E+09 | 0.00 | 0.00 |
| September | 0.183802E+10 | 0.833499E+09 | 0.155055E+10 | 0.917170E+09 | 0.633383E+09 | 0.00 | 0.00 |
| October | 0.151091E+10 | 0.122002E+10 | 0.148989E+10 | 0.971178E+09 | 0.518709E+09 | 0.00 | 0.00 |
| November | 0.106763E+10 | 0.147827E+10 | 0.122507E+10 | 0.837824E+09 | 0.387241E+09 | 0.00 | 0.00 |
| December | 0.766219E+09 | 0.204247E+10 | 0.101537E+10 | 0.685006E+09 | 0.330359E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.175388E+11 | 0.146772E+11 | 0.167594E+11 | 0.925610E+10 | 0.750326E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.766219E+09 | 0.482968E+09 | 0.101537E+10 | 0.588118E+09 | 0.330359E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.223279E+10 | 0.242531E+10 | 0.162955E+10 | 0.971178E+09 | 0.879372E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.351112E+10 | 0.650884E+10 | 0.396234E+10 | 0.288538E+10 | 0.107696E+10 | 0.00 | 0.00 |
| February | 0.472364E+10 | 0.429878E+10 | 0.475677E+10 | 0.353848E+10 | 0.121829E+10 | 0.00 | 0.00 |
| March | 0.456446E+10 | 0.425779E+10 | 0.468796E+10 | 0.277767E+10 | 0.191029E+10 | 0.00 | 0.00 |
| April | 0.368435E+10 | 0.310850E+10 | 0.357412E+10 | 0.185323E+10 | 0.172089E+10 | 0.00 | 0.00 |
| May | 0.328380E+10 | 0.265718E+10 | 0.317969E+10 | 0.118684E+10 | 0.199285E+10 | 0.00 | 0.00 |
| June | 0.370766E+10 | 0.177069E+10 | 0.298798E+10 | 0.100246E+10 | 0.198552E+10 | 0.00 | 0.00 |
| July | 0.502551E+10 | 0.125942E+10 | 0.339718E+10 | 0.141351E+10 | 0.198367E+10 | 0.00 | 0.00 |
| August | 0.585802E+10 | 0.147210E+10 | 0.416694E+10 | 0.228630E+10 | 0.188064E+10 | 0.00 | 0.00 |
| September | 0.566562E+10 | 0.230066E+10 | 0.457325E+10 | 0.297078E+10 | 0.160247E+10 | 0.00 | 0.00 |
| October | 0.544504E+10 | 0.340302E+10 | 0.496501E+10 | 0.356849E+10 | 0.139652E+10 | 0.00 | 0.00 |
| November | 0.425987E+10 | 0.412168E+10 | 0.428614E+10 | 0.320048E+10 | 0.108567E+10 | 0.00 | 0.00 |
| December | 0.335367E+10 | 0.561771E+10 | 0.363104E+10 | 0.268926E+10 | 0.941785E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.530827E+11 | 0.407764E+11 | 0.481684E+11 | 0.293729E+11 | 0.187956E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.328380E+10 | 0.125942E+10 | 0.298798E+10 | 0.100246E+10 | 0.941785E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.585802E+10 | 0.650884E+10 | 0.496501E+10 | 0.356849E+10 | 0.199285E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 31175900.39 | 0.429935E+09 | 73970815.50 | 29810793.60 | 44160021.90 | 0.00 | 0.00 |
| February | 79108503.64 | 0.279074E+09 | 0.114039E+09 | 56055770.97 | 57982836.54 | 0.00 | 0.00 |
| March | 0.114477E+09 | 0.258905E+09 | 0.161578E+09 | 59204732.84 | 0.102374E+09 | 0.00 | 0.00 |
| April | 0.189371E+09 | 0.178547E+09 | 0.204137E+09 | 90442042.89 | 0.113695E+09 | 0.00 | 0.00 |
| May | 0.268904E+09 | 0.151058E+09 | 0.260919E+09 | 0.118993E+09 | 0.141926E+09 | 0.00 | 0.00 |
| June | 0.325808E+09 | 0.100362E+09 | 0.274713E+09 | 0.126186E+09 | 0.148527E+09 | 0.00 | 0.00 |
| July | 0.392514E+09 | 76219859.44 | 0.290793E+09 | 0.146942E+09 | 0.143851E+09 | 0.00 | 0.00 |
| August | 0.321962E+09 | 85256782.72 | 0.246923E+09 | 0.121185E+09 | 0.125738E+09 | 0.00 | 0.00 |
| September | 0.217752E+09 | 0.135269E+09 | 0.192226E+09 | 97181884.34 | 95044555.50 | 0.00 | 0.00 |
| October | 0.123998E+09 | 0.204966E+09 | 0.141969E+09 | 70536604.45 | 71432123.70 | 0.00 | 0.00 |
| November | 66103852.73 | 0.261923E+09 | 97258402.11 | 48248465.95 | 49009936.16 | 0.00 | 0.00 |
| December | 29101723.37 | 0.359773E+09 | 67554597.73 | 28512887.97 | 39041709.75 | 0.00 | 0.00 |
| Annual Sum or Average | 0.216028E+10 | 0.252129E+10 | 0.212608E+10 | 0.993299E+09 | 0.113278E+10 | 0.00 | 0.00 |
| Minimum of Months | 29101723.37 | 76219859.44 | 67554597.73 | 28512887.97 | 39041709.75 | 0.00 | 0.00 |
| Maximum of Months | 0.392514E+09 | 0.429935E+09 | 0.290793E+09 | 0.146942E+09 | 0.148527E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 58111614.15 | 0.266892E+10 | 0.351860E+09 | 89432082.68 | 0.262428E+09 | 0.00 | 0.00 |
| February | 0.238163E+09 | 0.170660E+10 | 0.507838E+09 | 0.168167E+09 | 0.339671E+09 | 0.00 | 0.00 |
| March | 0.420551E+09 | 0.152641E+10 | 0.782787E+09 | 0.177614E+09 | 0.605173E+09 | 0.00 | 0.00 |
| April | 0.740546E+09 | 0.100898E+10 | 0.941290E+09 | 0.273244E+09 | 0.668046E+09 | 0.00 | 0.00 |
| May | 0.111403E+10 | 0.848571E+09 | 0.122905E+10 | 0.383424E+09 | 0.845628E+09 | 0.00 | 0.00 |
| June | 0.146903E+10 | 0.546885E+09 | 0.132706E+10 | 0.436363E+09 | 0.890698E+09 | 0.00 | 0.00 |
| July | 0.178024E+10 | 0.431298E+09 | 0.134714E+10 | 0.485292E+09 | 0.861849E+09 | 0.00 | 0.00 |
| August | 0.141839E+10 | 0.493652E+09 | 0.112120E+10 | 0.373750E+09 | 0.747448E+09 | 0.00 | 0.00 |
| September | 0.882693E+09 | 0.787709E+09 | 0.852403E+09 | 0.291644E+09 | 0.560759E+09 | 0.00 | 0.00 |
| October | 0.432504E+09 | 0.119342E+10 | 0.633735E+09 | 0.211609E+09 | 0.422125E+09 | 0.00 | 0.00 |
| November | 0.175779E+09 | 0.156113E+10 | 0.428501E+09 | 0.144745E+09 | 0.283756E+09 | 0.00 | 0.00 |
| December | 54635736.26 | 0.222678E+10 | 0.311632E+09 | 85538378.79 | 0.226094E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.878467E+10 | 0.150004E+11 | 0.983450E+10 | 0.312082E+10 | 0.671368E+10 | 0.00 | 0.00 |
| Minimum of Months | 54635736.26 | 0.431298E+09 | 0.311632E+09 | 85538378.79 | 0.226094E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.178024E+10 | 0.266892E+10 | 0.134714E+10 | 0.485292E+09 | 0.890698E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 4670229.59 | 0.495257E+10 | 0.414919E+09 | 0.00 | 0.414919E+09 | 0.00 | 0.00 |
| February | 64029659.42 | 0.326902E+10 | 0.529146E+09 | 0.00 | 0.529146E+09 | 0.00 | 0.00 |
| March | 0.208652E+09 | 0.289191E+10 | 0.951671E+09 | 0.00 | 0.951671E+09 | 0.00 | 0.00 |
| April | 0.450600E+09 | 0.196209E+10 | 0.105010E+10 | 6128109.15 | 0.104398E+10 | 0.00 | 0.00 |
| May | 0.906184E+09 | 0.157702E+10 | 0.142500E+10 | 84439530.90 | 0.134056E+10 | 0.00 | 0.00 |
| June | 0.154137E+10 | 0.979457E+09 | 0.160581E+10 | 0.184573E+09 | 0.142124E+10 | 0.00 | 0.00 |
| July | 0.195779E+10 | 0.737498E+09 | 0.151590E+10 | 0.141981E+09 | 0.137392E+10 | 0.00 | 0.00 |
| August | 0.143209E+10 | 0.854869E+09 | 0.121470E+10 | 32559210.70 | 0.118214E+10 | 0.00 | 0.00 |
| September | 0.701510E+09 | 0.145338E+10 | 0.880378E+09 | 315924.05 | 0.880062E+09 | 0.00 | 0.00 |
| October | 0.182433E+09 | 0.228598E+10 | 0.663590E+09 | 0.00 | 0.663590E+09 | 0.00 | 0.00 |
| November | 32094594.96 | 0.304688E+10 | 0.436563E+09 | 0.00 | 0.436563E+09 | 0.00 | 0.00 |
| December | 1505921.83 | 0.420412E+10 | 0.347933E+09 | 0.00 | 0.347933E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.748293E+10 | 0.282148E+11 | 0.110357E+11 | 0.449996E+09 | 0.105857E+11 | 0.00 | 0.00 |
| Minimum of Months | 1505921.83 | 0.737498E+09 | 0.347933E+09 | 0.00 | 0.347933E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.195779E+10 | 0.495257E+10 | 0.160581E+10 | 0.184573E+09 | 0.142124E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 1891792.01 | 0.257444E+10 | 0.213386E+09 | 0.00 | 0.213386E+09 | 0.00 | 0.00 |
| February | 29200972.68 | 0.171635E+10 | 0.272130E+09 | 0.00 | 0.272130E+09 | 0.00 | 0.00 |
| March | 95214265.98 | 0.154426E+10 | 0.489428E+09 | 0.00 | 0.489428E+09 | 0.00 | 0.00 |
| April | 0.207601E+09 | 0.108294E+10 | 0.540049E+09 | 3151607.07 | 0.536898E+09 | 0.00 | 0.00 |
| May | 0.436109E+09 | 0.867437E+09 | 0.732854E+09 | 43426155.80 | 0.689428E+09 | 0.00 | 0.00 |
| June | 0.766321E+09 | 0.536264E+09 | 0.825840E+09 | 94923309.02 | 0.730917E+09 | 0.00 | 0.00 |
| July | 0.960144E+09 | 0.413673E+09 | 0.779599E+09 | 73018759.34 | 0.706580E+09 | 0.00 | 0.00 |
| August | 0.692209E+09 | 0.484368E+09 | 0.624696E+09 | 16744779.86 | 0.607952E+09 | 0.00 | 0.00 |
| September | 0.337218E+09 | 0.813954E+09 | 0.452762E+09 | 162475.64 | 0.452600E+09 | 0.00 | 0.00 |
| October | 82291921.33 | 0.125627E+10 | 0.341273E+09 | 0.00 | 0.341273E+09 | 0.00 | 0.00 |
| November | 12167924.90 | 0.163886E+10 | 0.224516E+09 | 0.00 | 0.224516E+09 | 0.00 | 0.00 |
| December | 593766.93 | 0.220312E+10 | 0.178936E+09 | 0.00 | 0.178936E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.362096E+10 | 0.151319E+11 | 0.567547E+10 | 0.231427E+09 | 0.544404E+10 | 0.00 | 0.00 |
| Minimum of Months | 593766.93 | 0.413673E+09 | 0.178936E+09 | 0.00 | 0.178936E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.960144E+09 | 0.257444E+10 | 0.825840E+09 | 94923309.02 | 0.730917E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 3141030.88 | 0.130129E+10 | 99375479.00 | 14770290.76 | 84605188.24 | 0.00 | 0.00 |
| February | 71934692.81 | 0.846086E+09 | 0.176683E+09 | 62103004.00 | 0.114580E+09 | 0.00 | 0.00 |
| March | 0.199768E+09 | 0.773845E+09 | 0.342150E+09 | 0.115929E+09 | 0.226221E+09 | 0.00 | 0.00 |
| April | 0.443467E+09 | 0.545371E+09 | 0.496649E+09 | 0.233563E+09 | 0.263086E+09 | 0.00 | 0.00 |
| May | 0.645603E+09 | 0.472479E+09 | 0.639354E+09 | 0.309284E+09 | 0.330070E+09 | 0.00 | 0.00 |
| June | 0.789745E+09 | 0.319926E+09 | 0.668964E+09 | 0.326360E+09 | 0.342603E+09 | 0.00 | 0.00 |
| July | 0.997823E+09 | 0.237274E+09 | 0.740451E+09 | 0.401100E+09 | 0.339350E+09 | 0.00 | 0.00 |
| August | 0.786119E+09 | 0.262114E+09 | 0.604537E+09 | 0.312690E+09 | 0.291847E+09 | 0.00 | 0.00 |
| September | 0.490832E+09 | 0.401710E+09 | 0.442163E+09 | 0.227009E+09 | 0.215154E+09 | 0.00 | 0.00 |
| October | 0.182363E+09 | 0.593442E+09 | 0.254180E+09 | 0.106222E+09 | 0.147959E+09 | 0.00 | 0.00 |
| November | 31419371.06 | 0.776005E+09 | 0.125183E+09 | 34372292.65 | 90811161.40 | 0.00 | 0.00 |
| December | 465606.87 | 0.110560E+10 | 77580373.28 | 8942013.44 | 68638359.84 | 0.00 | 0.00 |
| Annual Sum or Average | 0.464268E+10 | 0.763514E+10 | 0.466727E+10 | 0.215235E+10 | 0.251493E+10 | 0.00 | 0.00 |
| Minimum of Months | 465606.87 | 0.237274E+09 | 77580373.28 | 8942013.44 | 68638359.84 | 0.00 | 0.00 |
| Maximum of Months | 0.997823E+09 | 0.130129E+10 | 0.740451E+09 | 0.401100E+09 | 0.342603E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.147101E+10 | 0.204407E+10 | 0.158773E+10 | 0.113399E+10 | 0.453742E+09 | 0.00 | 0.00 |
| February | 0.189482E+10 | 0.138195E+10 | 0.182628E+10 | 0.131353E+10 | 0.512751E+09 | 0.00 | 0.00 |
| March | 0.184706E+10 | 0.138573E+10 | 0.180736E+10 | 0.101493E+10 | 0.792430E+09 | 0.00 | 0.00 |
| April | 0.151047E+10 | 0.100263E+10 | 0.140595E+10 | 0.672475E+09 | 0.733475E+09 | 0.00 | 0.00 |
| May | 0.139625E+10 | 0.856585E+09 | 0.129079E+10 | 0.428707E+09 | 0.862083E+09 | 0.00 | 0.00 |
| June | 0.154270E+10 | 0.607610E+09 | 0.124116E+10 | 0.361981E+09 | 0.879176E+09 | 0.00 | 0.00 |
| July | 0.195275E+10 | 0.494150E+09 | 0.138270E+10 | 0.510763E+09 | 0.871932E+09 | 0.00 | 0.00 |
| August | 0.225856E+10 | 0.547804E+09 | 0.164324E+10 | 0.828493E+09 | 0.814749E+09 | 0.00 | 0.00 |
| September | 0.220188E+10 | 0.784063E+09 | 0.176376E+10 | 0.108071E+10 | 0.683048E+09 | 0.00 | 0.00 |
| October | 0.215934E+10 | 0.110488E+10 | 0.190538E+10 | 0.131755E+10 | 0.587835E+09 | 0.00 | 0.00 |
| November | 0.172945E+10 | 0.130037E+10 | 0.168111E+10 | 0.121773E+10 | 0.463381E+09 | 0.00 | 0.00 |
| December | 0.142652E+10 | 0.175304E+10 | 0.150984E+10 | 0.109026E+10 | 0.419584E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.213908E+11 | 0.132629E+11 | 0.190453E+11 | 0.109711E+11 | 0.807419E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.139625E+10 | 0.494150E+09 | 0.124116E+10 | 0.361981E+09 | 0.419584E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.225856E+10 | 0.204407E+10 | 0.190538E+10 | 0.131755E+10 | 0.879176E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 15504182.24 | 0.132595E+10 | 0.127823E+09 | 27726321.49 | 0.100097E+09 | 0.00 | 0.00 |
| February | 0.124293E+09 | 0.854981E+09 | 0.228600E+09 | 92995772.55 | 0.135604E+09 | 0.00 | 0.00 |
| March | 0.263411E+09 | 0.807878E+09 | 0.408087E+09 | 0.145407E+09 | 0.262680E+09 | 0.00 | 0.00 |
| April | 0.516339E+09 | 0.593565E+09 | 0.569453E+09 | 0.268724E+09 | 0.300729E+09 | 0.00 | 0.00 |
| May | 0.727186E+09 | 0.522493E+09 | 0.723988E+09 | 0.348452E+09 | 0.375536E+09 | 0.00 | 0.00 |
| June | 0.866213E+09 | 0.373965E+09 | 0.756328E+09 | 0.366779E+09 | 0.389549E+09 | 0.00 | 0.00 |
| July | 0.110150E+10 | 0.285192E+09 | 0.836456E+09 | 0.451160E+09 | 0.385296E+09 | 0.00 | 0.00 |
| August | 0.880377E+09 | 0.307122E+09 | 0.689859E+09 | 0.357149E+09 | 0.332710E+09 | 0.00 | 0.00 |
| September | 0.567861E+09 | 0.460074E+09 | 0.516886E+09 | 0.269438E+09 | 0.247447E+09 | 0.00 | 0.00 |
| October | 0.246268E+09 | 0.657328E+09 | 0.318266E+09 | 0.144547E+09 | 0.173718E+09 | 0.00 | 0.00 |
| November | 67627471.37 | 0.818237E+09 | 0.167164E+09 | 58973517.77 | 0.108191E+09 | 0.00 | 0.00 |
| December | 7476225.43 | 0.112894E+10 | 0.100312E+09 | 18903554.67 | 81408890.99 | 0.00 | 0.00 |
| Annual Sum or Average | 0.538406E+10 | 0.813573E+10 | 0.544322E+10 | 0.255026E+10 | 0.289297E+10 | 0.00 | 0.00 |
| Minimum of Months | 7476225.43 | 0.285192E+09 | 0.100312E+09 | 18903554.67 | 81408890.99 | 0.00 | 0.00 |
| Maximum of Months | 0.110150E+10 | 0.132595E+10 | 0.836456E+09 | 0.451160E+09 | 0.389549E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.161778E+10 | 0.504205E+10 | 0.232647E+10 | 0.151541E+10 | 0.811065E+09 | 0.00 | 0.00 |
| February | 0.244386E+10 | 0.334550E+10 | 0.282606E+10 | 0.185271E+10 | 0.973351E+09 | 0.00 | 0.00 |
| March | 0.280525E+10 | 0.328439E+10 | 0.319978E+10 | 0.161918E+10 | 0.158060E+10 | 0.00 | 0.00 |
| April | 0.288999E+10 | 0.237684E+10 | 0.303834E+10 | 0.147892E+10 | 0.155942E+10 | 0.00 | 0.00 |
| May | 0.305190E+10 | 0.203124E+10 | 0.312103E+10 | 0.122773E+10 | 0.189331E+10 | 0.00 | 0.00 |
| June | 0.404644E+10 | 0.134878E+10 | 0.349421E+10 | 0.149228E+10 | 0.200193E+10 | 0.00 | 0.00 |
| July | 0.504411E+10 | 0.108062E+10 | 0.383002E+10 | 0.186579E+10 | 0.196423E+10 | 0.00 | 0.00 |
| August | 0.491688E+10 | 0.122975E+10 | 0.381655E+10 | 0.203023E+10 | 0.178632E+10 | 0.00 | 0.00 |
| September | 0.382455E+10 | 0.183629E+10 | 0.331880E+10 | 0.190134E+10 | 0.141746E+10 | 0.00 | 0.00 |
| October | 0.311313E+10 | 0.263337E+10 | 0.312114E+10 | 0.197173E+10 | 0.114941E+10 | 0.00 | 0.00 |
| November | 0.206040E+10 | 0.311982E+10 | 0.248071E+10 | 0.163659E+10 | 0.844118E+09 | 0.00 | 0.00 |
| December | 0.154995E+10 | 0.427166E+10 | 0.214331E+10 | 0.140883E+10 | 0.734483E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.373643E+11 | 0.316003E+11 | 0.367164E+11 | 0.200007E+11 | 0.167157E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.154995E+10 | 0.108062E+10 | 0.214331E+10 | 0.122773E+10 | 0.734483E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.504411E+10 | 0.504205E+10 | 0.383002E+10 | 0.203023E+10 | 0.200193E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.289663E+09 | 0.485989E+10 | 0.104863E+10 | 0.436694E+09 | 0.611933E+09 | 0.00 | 0.00 |
| February | 0.968491E+09 | 0.326346E+10 | 0.154903E+10 | 0.804801E+09 | 0.744233E+09 | 0.00 | 0.00 |
| March | 0.210248E+10 | 0.314440E+10 | 0.260884E+10 | 0.116356E+10 | 0.144529E+10 | 0.00 | 0.00 |
| April | 0.306812E+10 | 0.232092E+10 | 0.323674E+10 | 0.174673E+10 | 0.149001E+10 | 0.00 | 0.00 |
| May | 0.424834E+10 | 0.194955E+10 | 0.405358E+10 | 0.214973E+10 | 0.190385E+10 | 0.00 | 0.00 |
| June | 0.579268E+10 | 0.131115E+10 | 0.484188E+10 | 0.289815E+10 | 0.194373E+10 | 0.00 | 0.00 |
| July | 0.672883E+10 | 0.113013E+10 | 0.521061E+10 | 0.340500E+10 | 0.180561E+10 | 0.00 | 0.00 |
| August | 0.549878E+10 | 0.124847E+10 | 0.436254E+10 | 0.276701E+10 | 0.159552E+10 | 0.00 | 0.00 |
| September | 0.334422E+10 | 0.173583E+10 | 0.297385E+10 | 0.175895E+10 | 0.121491E+10 | 0.00 | 0.00 |
| October | 0.175645E+10 | 0.254364E+10 | 0.201529E+10 | 0.108085E+10 | 0.934436E+09 | 0.00 | 0.00 |
| November | 0.586489E+09 | 0.313692E+10 | 0.116853E+10 | 0.544470E+09 | 0.624059E+09 | 0.00 | 0.00 |
| December | 0.178347E+09 | 0.423264E+10 | 0.847247E+09 | 0.332770E+09 | 0.514477E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.345629E+11 | 0.308770E+11 | 0.339168E+11 | 0.190887E+11 | 0.148281E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.178347E+09 | 0.113013E+10 | 0.847247E+09 | 0.332770E+09 | 0.514477E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.672883E+10 | 0.485989E+10 | 0.521061E+10 | 0.340500E+10 | 0.194373E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 78274452.05 | 0.129565E+10 | 0.217765E+09 | 99836158.53 | 0.117929E+09 | 0.00 | 0.00 |
| February | 0.179819E+09 | 0.909515E+09 | 0.307643E+09 | 0.152737E+09 | 0.154906E+09 | 0.00 | 0.00 |
| March | 0.296042E+09 | 0.842059E+09 | 0.457974E+09 | 0.189496E+09 | 0.268478E+09 | 0.00 | 0.00 |
| April | 0.473628E+09 | 0.598553E+09 | 0.565480E+09 | 0.280246E+09 | 0.285234E+09 | 0.00 | 0.00 |
| May | 0.599544E+09 | 0.486461E+09 | 0.645469E+09 | 0.287191E+09 | 0.358277E+09 | 0.00 | 0.00 |
| June | 0.929112E+09 | 0.294715E+09 | 0.808524E+09 | 0.416064E+09 | 0.392461E+09 | 0.00 | 0.00 |
| July | 0.112651E+10 | 0.236265E+09 | 0.876855E+09 | 0.495707E+09 | 0.381148E+09 | 0.00 | 0.00 |
| August | 0.950858E+09 | 0.270064E+09 | 0.762026E+09 | 0.424575E+09 | 0.337451E+09 | 0.00 | 0.00 |
| September | 0.554293E+09 | 0.396765E+09 | 0.521669E+09 | 0.269282E+09 | 0.252387E+09 | 0.00 | 0.00 |
| October | 0.306101E+09 | 0.622269E+09 | 0.386746E+09 | 0.196383E+09 | 0.190363E+09 | 0.00 | 0.00 |
| November | 0.115526E+09 | 0.844409E+09 | 0.237205E+09 | 0.110743E+09 | 0.126462E+09 | 0.00 | 0.00 |
| December | 53979727.79 | 0.114374E+10 | 0.180784E+09 | 77646932.71 | 0.103137E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.566368E+10 | 0.794046E+10 | 0.596814E+10 | 0.299991E+10 | 0.296823E+10 | 0.00 | 0.00 |
| Minimum of Months | 53979727.79 | 0.236265E+09 | 0.180784E+09 | 77646932.71 | 0.103137E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.112651E+10 | 0.129565E+10 | 0.876855E+09 | 0.495707E+09 | 0.392461E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 73758014.57 | 0.490069E+10 | 0.642289E+09 | 0.187199E+09 | 0.455090E+09 | 0.00 | 0.00 |
| February | 0.300818E+09 | 0.325489E+10 | 0.874797E+09 | 0.286391E+09 | 0.588406E+09 | 0.00 | 0.00 |
| March | 0.627696E+09 | 0.295499E+10 | 0.139650E+10 | 0.355317E+09 | 0.104119E+10 | 0.00 | 0.00 |
| April | 0.109856E+10 | 0.206712E+10 | 0.164903E+10 | 0.528190E+09 | 0.112084E+10 | 0.00 | 0.00 |
| May | 0.157780E+10 | 0.174226E+10 | 0.199299E+10 | 0.572407E+09 | 0.142059E+10 | 0.00 | 0.00 |
| June | 0.250020E+10 | 0.114084E+10 | 0.238691E+10 | 0.861615E+09 | 0.152530E+10 | 0.00 | 0.00 |
| July | 0.306931E+10 | 0.929736E+09 | 0.249139E+10 | 0.100504E+10 | 0.148635E+10 | 0.00 | 0.00 |
| August | 0.245946E+10 | 0.103462E+10 | 0.210506E+10 | 0.809231E+09 | 0.129583E+10 | 0.00 | 0.00 |
| September | 0.134988E+10 | 0.154534E+10 | 0.147401E+10 | 0.505016E+09 | 0.968995E+09 | 0.00 | 0.00 |
| October | 0.609358E+09 | 0.227382E+10 | 0.109910E+10 | 0.368230E+09 | 0.730870E+09 | 0.00 | 0.00 |
| November | 0.149487E+09 | 0.303476E+10 | 0.690361E+09 | 0.207651E+09 | 0.482711E+09 | 0.00 | 0.00 |
| December | 35664344.46 | 0.420530E+10 | 0.534387E+09 | 0.145593E+09 | 0.388794E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.138520E+11 | 0.290844E+11 | 0.173368E+11 | 0.583188E+10 | 0.115050E+11 | 0.00 | 0.00 |
| Minimum of Months | 35664344.46 | 0.929736E+09 | 0.534387E+09 | 0.145593E+09 | 0.388794E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.306931E+10 | 0.490069E+10 | 0.249139E+10 | 0.100504E+10 | 0.152530E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 73266340.11 | 0.540187E+10 | 0.674992E+09 | 0.173070E+09 | 0.501922E+09 | 0.00 | 0.00 |
| February | 0.371525E+09 | 0.351536E+10 | 0.981729E+09 | 0.323394E+09 | 0.658335E+09 | 0.00 | 0.00 |
| March | 0.828522E+09 | 0.319304E+10 | 0.164295E+10 | 0.461038E+09 | 0.118191E+10 | 0.00 | 0.00 |
| April | 0.142313E+10 | 0.229713E+10 | 0.198702E+10 | 0.709381E+09 | 0.127764E+10 | 0.00 | 0.00 |
| May | 0.199116E+10 | 0.193610E+10 | 0.240869E+10 | 0.785478E+09 | 0.162321E+10 | 0.00 | 0.00 |
| June | 0.315405E+10 | 0.123723E+10 | 0.293361E+10 | 0.117943E+10 | 0.175418E+10 | 0.00 | 0.00 |
| July | 0.385342E+10 | 0.100168E+10 | 0.305955E+10 | 0.135907E+10 | 0.170048E+10 | 0.00 | 0.00 |
| August | 0.308794E+10 | 0.113175E+10 | 0.258233E+10 | 0.109782E+10 | 0.148451E+10 | 0.00 | 0.00 |
| September | 0.167176E+10 | 0.174268E+10 | 0.176789E+10 | 0.664457E+09 | 0.110344E+10 | 0.00 | 0.00 |
| October | 0.725710E+09 | 0.260144E+10 | 0.127022E+10 | 0.445926E+09 | 0.824297E+09 | 0.00 | 0.00 |
| November | 0.157279E+09 | 0.334269E+10 | 0.745060E+09 | 0.210824E+09 | 0.534235E+09 | 0.00 | 0.00 |
| December | 26611659.02 | 0.460847E+10 | 0.545417E+09 | 0.122892E+09 | 0.422525E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.173644E+11 | 0.320094E+11 | 0.205995E+11 | 0.753278E+10 | 0.130667E+11 | 0.00 | 0.00 |
| Minimum of Months | 26611659.02 | 0.100168E+10 | 0.545417E+09 | 0.122892E+09 | 0.422525E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.385342E+10 | 0.540187E+10 | 0.305955E+10 | 0.135907E+10 | 0.175418E+10 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | -8.8 | -10.9 | -16.1 | 5.70 | -23.3 | 32.48 | 106.19 | 0.00 |
| February | -2.2 | -5.0 | -9.9 | 6.21 | -16.1 | 41.31 | 158.25 | 0.00 |
| March | 0.30 | -2.9 | -8.4 | 5.38 | -12.8 | 78.62 | 145.02 | 0.00 |
| April | 6.67 | 2.34 | -2.9 | 4.89 | -6.2 | 82.10 | 182.32 | 0.01 |
| May | 10.10 | 5.18 | 0.22 | 5.28 | -1.1 | 102.67 | 205.47 | 0.01 |
| June | 16.46 | 10.06 | 4.91 | 4.56 | 5.05 | 103.05 | 264.47 | 0.02 |
| July | 20.57 | 12.46 | 6.56 | 4.24 | 8.00 | 89.47 | 301.47 | 0.00 |
| August | 19.17 | 11.04 | 4.61 | 4.29 | 7.19 | 78.96 | 261.05 | 0.00 |
| September | 14.69 | 9.08 | 4.37 | 5.43 | 3.42 | 63.03 | 204.21 | 0.00 |
| October | 8.64 | 4.13 | -1.0 | 5.38 | -4.2 | 47.64 | 162.42 | 0.00 |
| November | 2.84 | -0.9 | -6.9 | 5.91 | -11.0 | 33.00 | 125.52 | 0.00 |
| December | -4.1 | -6.5 | -11.1 | 5.64 | -18.2 | 26.54 | 97.81 | 0.00 |
| Annual Sum or Average | 7.07 | 2.37 | -2.9 | 5.23 | -5.7 | 65.04 | 184.63 | 0.00 |
| Minimum of Months | -8.8 | -10.9 | -16.1 | 4.24 | -23.3 | 26.54 | 97.81 | 0.00 |
| Maximum of Months | 20.57 | 12.46 | 6.56 | 6.21 | 8.00 | 103.05 | 301.47 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 10.60 | 14-JAN-12:00 | 5.16 | -1.1 | 8.20 | -2.3 | 105.00 | 464.50 |
| February | 18.90 | 27-FEB-14:00 | 7.23 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
| March | 15.00 | 14-MAR-13:20 | 6.67 | -2.4 | 9.30 | 1.23 | 201.67 | 711.67 |
| April | 23.30 | 07-APR-13:00 | 9.68 | -4.4 | 9.30 | 4.92 | 314.50 | 110.00 |
| May | 30.00 | 20-MAY-15:00 | 15.22 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
| June | 32.20 | 29-JUN-12:00 | 14.40 | 0.60 | 9.30 | 17.03 | 187.00 | 729.00 |
| July | 37.20 | 17-JUL-15:00 | 17.28 | 4.40 | 4.60 | 20.22 | 119.50 | 797.00 |
| August | 35.60 | 05-AUG-15:00 | 17.65 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
| September | 34.40 | 02-SEP-14:00 | 16.28 | 4.40 | 7.70 | 20.75 | 95.50 | 789.50 |
| October | 25.00 | 18-OCT-13:00 | 11.40 | -1.1 | 7.70 | 7.35 | 48.00 | 913.00 |
| November | 17.20 | 04-NOV-13:00 | 8.18 | -1.1 | 11.30 | 2.22 | 81.00 | 689.50 |
| December | 13.90 | 10-DEC-01:00 | 5.50 | -5.0 | 13.90 | 5.74 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 10.60 | 5.16 | -7.8 | 4.60 | -2.3 | 0.00 | 0.00 | |
| Maximum of Months | 37.20 | 17.65 | 6.70 | 13.90 | 22.47 | 314.50 | 913.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -33.9 | 10-JAN-21:00 | -34.1 | -37.8 | 3.10 | -54.3 | 0.00 | 0.00 |
| February | -25.0 | 01-FEB-03:00 | -25.2 | -27.8 | 2.10 | -45.6 | 0.00 | 0.00 |
| March | -23.3 | 04-MAR-23:00 | -23.8 | -28.9 | 3.60 | -44.5 | 0.00 | 0.00 |
| April | -7.8 | 29-APR-03:00 | -8.7 | -10.6 | 4.10 | -25.6 | 0.00 | 0.00 |
| May | -2.8 | 08-MAY-00:10 | -3.3 | -3.9 | 6.18 | -10.2 | 0.00 | 0.00 |
| June | 0.60 | 15-JUN-03:00 | -0.5 | -1.7 | 2.60 | -15.7 | 0.00 | 0.00 |
| July | 5.60 | 08-JUL-03:00 | 2.99 | 0.00 | 4.10 | -9.2 | 0.00 | 0.00 |
| August | 6.70 | 17-AUG-00:00 | 4.32 | 1.70 | 2.60 | -7.1 | 0.00 | 0.00 |
| September | 0.00 | 17-SEP-02:00 | -1.6 | -3.9 | 4.10 | -16.8 | 0.00 | 0.00 |
| October | -6.1 | 10-OCT-05:19 | -6.6 | -7.8 | 3.77 | -20.6 | 0.00 | 0.00 |
| November | -16.7 | 26-NOV-07:00 | -17.3 | -20.6 | 4.60 | -33.8 | 19.50 | 94.00 |
| December | -28.3 | 29-DEC-08:00 | -28.6 | -32.2 | 2.10 | -48.7 | 69.50 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -33.9 | -34.1 | -37.8 | 2.10 | -54.3 | 0.00 | 0.00 | |
| Maximum of Months | 6.70 | 4.32 | 1.70 | 6.18 | -7.1 | 69.50 | 94.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 5.18 | 13-JAN-14:00 | 10.00 | 0.00 | 8.80 | -3.0 | 40.00 | 694.00 |
| February | 7.23 | 27-FEB-14:00 | 18.90 | -7.8 | 5.20 | 1.37 | 76.00 | 634.50 |
| March | 6.94 | 14-MAR-13:00 | 15.00 | -1.7 | 10.30 | 1.80 | 241.00 | 538.00 |
| April | 11.02 | 06-APR-15:00 | 22.20 | 1.10 | 3.60 | 5.33 | 110.00 | 779.00 |
| May | 15.22 | 20-MAY-15:00 | 30.00 | 5.60 | 6.70 | 20.57 | 215.50 | 18.50 |
| June | 19.20 | 20-JUN-14:00 | 29.40 | 14.40 | 2.60 | 18.28 | 204.00 | 614.00 |
| July | 19.21 | 19-JUL-11:00 | 29.40 | 14.40 | 8.80 | 19.52 | 306.50 | 563.50 |
| August | 17.65 | 05-AUG-15:00 | 35.60 | 6.70 | 5.20 | 22.47 | 136.50 | 625.50 |
| September | 20.12 | 07-SEP-15:20 | 25.17 | 17.93 | 4.10 | 15.88 | 127.67 | 652.00 |
| October | 11.61 | 18-OCT-14:00 | 25.00 | -0.6 | 7.70 | 7.55 | 40.50 | 852.00 |
| November | 8.89 | 17-NOV-16:00 | 17.20 | 1.10 | 11.30 | 4.10 | 0.00 | 0.00 |
| December | 7.62 | 19-DEC-14:00 | 12.80 | 2.80 | 8.20 | 1.37 | 74.00 | 138.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 5.18 | 10.00 | -7.8 | 2.60 | -3.0 | 0.00 | 0.00 | |
| Maximum of Months | 20.12 | 35.60 | 17.93 | 11.30 | 22.47 | 306.50 | 852.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 1.70 | 12-JAN-14:00 | 7.20 | 4.48 | 5.20 | -1.0 | 107.00 | 61.00 |
| February | -0.6 | 11-FEB-08:00 | 4.40 | 2.16 | 10.80 | -5.7 | 69.50 | 50.50 |
| March | -0.6 | 10-MAR-12:00 | 8.90 | 4.51 | 10.30 | -2.3 | 253.00 | 140.50 |
| April | 6.10 | 17-APR-16:19 | 7.97 | 6.96 | 4.50 | 0.87 | 201.50 | 117.50 |
| May | 12.20 | 02-MAY-12:00 | 18.90 | 14.61 | 12.90 | 14.84 | 108.50 | 934.50 |
| June | 15.60 | 20-JUN-19:00 | 25.60 | 18.76 | 3.60 | 20.22 | 17.50 | 17.00 |
| July | 16.70 | 18-JUL-21:00 | 19.40 | 17.51 | 4.10 | 16.49 | 0.00 | 0.00 |
| August | 11.10 | 08-AUG-11:00 | 26.70 | 16.75 | 2.60 | 12.03 | 134.50 | 869.00 |
| September | 18.30 | 07-SEP-14:00 | 24.40 | 20.10 | 4.10 | 15.57 | 111.00 | 720.00 |
| October | 6.70 | 01-OCT-14:09 | 9.08 | 7.78 | 2.10 | 4.07 | 260.33 | 0.33 |
| November | 3.30 | 16-NOV-19:00 | 10.60 | 6.88 | 9.80 | -1.7 | 0.00 | 0.00 |
| December | 2.80 | 19-DEC-14:09 | 10.97 | 6.81 | 10.78 | -1.0 | 95.00 | 292.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -0.6 | 4.40 | 2.16 | 2.10 | -5.7 | 0.00 | 0.00 | |
| Maximum of Months | 18.30 | 26.70 | 20.10 | 12.90 | 20.22 | 260.33 | 934.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 5.41 | 12.59 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 4.46 | 20.37 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 5.03 | 30.19 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 7.01 | 37.07 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 9.90 | 46.35 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 12.91 | 55.45 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 15.24 | 57.38 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 16.26 | 48.01 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 15.67 | 34.51 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 13.64 | 22.84 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 10.74 | 14.52 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 7.74 | 10.24 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 10.37 | 32.53 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 4.46 | 10.24 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 16.26 | 57.38 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER G WATER HEATER
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.274555E+10 | -0.258087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -164682610.5 | 82.17 | 0.00 | 0.00 |
| February | 0.248136E+10 | -0.233507E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -146292444.2 | 82.17 | 0.00 | 0.00 |
| March | 0.298763E+10 | -0.282667E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160961869.7 | 82.17 | 0.00 | 0.00 |
| April | 0.261232E+10 | -0.245797E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154352018.4 | 82.17 | 0.00 | 0.00 |
| May | 0.286356E+10 | -0.270377E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159794914.9 | 82.17 | 0.00 | 0.00 |
| June | 0.184167E+10 | -0.168695E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154728508.4 | 82.17 | 0.00 | 0.00 |
| July | 0.768632E+09 | -609202540.8 | 0.00 | 0.00 | 744.00 | 0.00 | -159429293.9 | 82.17 | 0.00 | 0.00 |
| August | 0.860511E+09 | -700582939.3 | 0.00 | 0.00 | 744.00 | 0.00 | -159928492.3 | 82.17 | 0.00 | 0.00 |
| September | 0.168795E+10 | -0.153359E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -154364136.2 | 82.17 | 0.00 | 0.00 |
| October | 0.274043E+10 | -0.258087E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -159563959.8 | 82.17 | 0.00 | 0.00 |
| November | 0.273601E+10 | -0.258087E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -155142745.0 | 82.17 | 0.00 | 0.00 |
| December | 0.262114E+10 | -0.245797E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -163168551.1 | 82.17 | 0.00 | 0.00 |
| Annual Sum or Average | 0.269468E+11 | -0.250544E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.189241E+10 | 82.17 | 0.00 | 0.00 |
| Minimum of Months | 0.768632E+09 | -0.282667E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -164682610.5 | 82.17 | 0.00 | 0.00 |
| Maximum of Months | 0.298763E+10 | -609202540.8 | 0.00 | 0.00 | 744.00 | 0.00 | -146292444.2 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.116407E+11 | -0.105740E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.106678E+10 | 60.05 | 0.00 | 0.00 |
| February | 0.106635E+11 | -0.973276E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -930706340.6 | 60.05 | 0.00 | 0.00 |
| March | 0.126490E+11 | -0.116586E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -990411768.4 | 60.05 | 0.00 | 0.00 |
| April | 0.106810E+11 | -0.977708E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -903874679.3 | 60.05 | 0.00 | 0.00 |
| May | 0.110884E+11 | -0.101866E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -901758733.4 | 60.05 | 0.00 | 0.00 |
| June | 0.684598E+10 | -0.600779E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -838185606.6 | 60.05 | 0.00 | 0.00 |
| July | 0.291474E+10 | -0.204118E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -873561394.8 | 60.05 | 0.00 | 0.00 |
| August | 0.318114E+10 | -0.229703E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -884107586.2 | 60.05 | 0.00 | 0.00 |
| September | 0.597763E+10 | -0.512772E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -849909741.6 | 60.05 | 0.00 | 0.00 |
| October | 0.990185E+10 | -0.898371E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -918143738.4 | 60.05 | 0.00 | 0.00 |
| November | 0.104881E+11 | -0.953831E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -949743145.5 | 60.05 | 0.00 | 0.00 |
| December | 0.106726E+11 | -0.963053E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -0.104205E+10 | 60.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.106705E+12 | -0.955553E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.111492E+11 | 60.05 | 0.00 | 0.00 |
| Minimum of Months | 0.291474E+10 | -0.116586E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.106678E+10 | 60.05 | 0.00 | 0.00 |
| Maximum of Months | 0.126490E+11 | -0.204118E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -838185606.6 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 304.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 325.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 385.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 417.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 421.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 352.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 317.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 269.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 236.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3965.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 226.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 434.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.399661E+10 | 9020.31 | 08-JAN-03:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.186146E+10 | 9023.78 | 08-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.138667E+10 | 9019.84 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.360702E+09 | 9028.78 | 21-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.278178E+09 | 9025.11 | 08-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 5824610.85 | 9019.33 | 16-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 7149754.39 | 9023.50 | 05-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 57903382.07 | 9024.20 | 21-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 27355799.09 | 9023.20 | 12-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 77454317.82 | 9018.78 | 02-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.825988E+09 | 9018.66 | 15-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.240269E+10 | 9020.61 | 14-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.112880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 5824610.85 | 9018.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.399661E+10 | 9028.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.105040E+11 | 33514.77 | 12-JAN-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.455667E+10 | 33520.20 | 15-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.295059E+10 | 33508.90 | 09-MAR-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.581043E+09 | 33520.60 | 10-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.563776E+09 | 33514.55 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 457053.86 | 7617.56 | 16-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 11454934.34 | 33549.02 | 05-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.122919E+09 | 33535.67 | 24-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 9904242.35 | 33545.21 | 14-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 96651571.70 | 33504.70 | 04-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.189410E+10 | 33506.34 | 22-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.589381E+10 | 33527.52 | 06-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.271854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 457053.86 | 7617.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.105040E+11 | 33549.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.501167E+10 | 7850.07 | 12-JAN-07:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.263657E+10 | 7850.31 | 15-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.164972E+10 | 7849.78 | 02-MAR-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.232614E+09 | 7855.66 | 17-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.283353E+09 | 7852.19 | 08-MAY-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 4621288.43 | 7852.18 | 18-AUG-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 944590.88 | 7839.80 | 20-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 70174478.30 | 7851.37 | 05-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.118137E+10 | 7850.85 | 07-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.309275E+10 | 7850.97 | 19-DEC-07:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.141638E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.501167E+10 | 7855.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.498641E+10 | 8474.21 | 03-JAN-06:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.267545E+10 | 8474.58 | 08-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.205471E+10 | 8476.90 | 02-MAR-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.556971E+09 | 8479.64 | 21-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.344134E+09 | 8476.84 | 26-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 9113817.48 | 8470.73 | 16-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 16751100.88 | 8475.23 | 05-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.106851E+09 | 8478.14 | 22-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 64551847.53 | 8474.69 | 12-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.189211E+09 | 8472.01 | 03-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.131909E+10 | 8477.61 | 16-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.317942E+10 | 8472.57 | 05-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.155027E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 9113817.48 | 8470.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.498641E+10 | 8479.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.140288E+11 | 31323.84 | 17-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.721705E+10 | 31336.79 | 21-FEB-07:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.512443E+10 | 31346.17 | 02-MAR-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.111675E+10 | 31333.86 | 18-APR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.751898E+09 | 31342.20 | 08-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 962409.62 | 16040.16 | 16-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 41229511.50 | 31361.99 | 06-JUL-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.313159E+09 | 31361.42 | 22-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 59095830.18 | 31347.48 | 14-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.355054E+09 | 31321.34 | 17-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.340089E+10 | 31347.28 | 16-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.842724E+10 | 31329.07 | 06-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.408366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 962409.62 | 16040.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.140288E+11 | 31361.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.409651E+10 | 8971.00 | 08-JAN-03:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.188130E+10 | 8974.47 | 08-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.140382E+10 | 8970.55 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.369257E+09 | 8979.47 | 21-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.286270E+09 | 8975.80 | 08-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 6962869.32 | 8970.06 | 16-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 8784927.67 | 8974.24 | 05-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 61525715.31 | 8974.93 | 21-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 28429318.04 | 8973.93 | 12-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 79399390.90 | 8969.51 | 02-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.850959E+09 | 8969.37 | 15-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.251670E+10 | 8971.31 | 14-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.115899E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 6962869.32 | 8969.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.409651E+10 | 8979.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.106553E+11 | 33162.80 | 12-JAN-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.452570E+10 | 33168.19 | 15-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.294124E+10 | 33156.99 | 09-MAR-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.574176E+09 | 33168.56 | 10-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.557359E+09 | 33162.58 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 405258.00 | 6754.30 | 16-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 13359154.01 | 33196.78 | 05-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.131022E+09 | 33198.12 | 21-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 8789126.96 | 33181.74 | 13-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 94883914.54 | 33152.85 | 04-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.196609E+10 | 33154.45 | 22-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.622414E+10 | 33175.43 | 06-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.276925E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 405258.00 | 6754.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.106553E+11 | 33198.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.508023E+10 | 7831.26 | 12-JAN-07:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.265186E+10 | 7831.50 | 15-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.166300E+10 | 7830.97 | 02-MAR-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.232339E+09 | 7836.84 | 17-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.283651E+09 | 7833.37 | 08-MAY-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 4710064.38 | 7833.38 | 18-AUG-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 960123.02 | 7821.01 | 20-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 70744990.03 | 7832.56 | 05-OCT-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.121363E+10 | 7834.06 | 17-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.319959E+10 | 7832.16 | 19-DEC-07:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.144007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.508023E+10 | 7836.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.498992E+10 | 8478.11 | 03-JAN-06:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.267410E+10 | 8478.48 | 08-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.205260E+10 | 8480.80 | 02-MAR-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.554862E+09 | 8483.54 | 21-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.342504E+09 | 8480.73 | 26-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 8877052.40 | 8474.63 | 16-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 16600432.18 | 8479.12 | 05-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.106787E+09 | 8482.04 | 22-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 64253656.26 | 8478.58 | 12-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.189184E+09 | 8475.91 | 03-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.132335E+10 | 8481.51 | 16-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.318679E+10 | 8476.47 | 05-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.155098E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 8877052.40 | 8474.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.498992E+10 | 8483.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.140450E+11 | 31306.25 | 17-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.721317E+10 | 31319.18 | 21-FEB-07:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.511951E+10 | 31328.57 | 02-MAR-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.111163E+10 | 31316.30 | 18-APR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.746434E+09 | 31324.60 | 08-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 932359.92 | 15539.33 | 16-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 41097850.72 | 31338.87 | 10-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.313469E+09 | 31343.87 | 22-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 58899722.41 | 31329.93 | 14-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.355746E+09 | 31303.77 | 17-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.341767E+10 | 31329.67 | 16-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.845744E+10 | 31311.49 | 06-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.408810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 932359.92 | 15539.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.140450E+11 | 31343.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.405644E+10 | 8976.69 | 08-JAN-03:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.187188E+10 | 8980.16 | 08-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.138993E+10 | 8976.24 | 10-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.355919E+09 | 8985.16 | 21-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.277093E+09 | 8981.49 | 08-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 6069845.91 | 8975.75 | 16-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 7281090.26 | 8979.93 | 05-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 57882398.81 | 8980.62 | 21-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 25529393.06 | 8979.61 | 12-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 74824406.40 | 8975.20 | 02-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.833218E+09 | 8975.06 | 15-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.247669E+10 | 8977.00 | 14-DEC-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.114328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 6069845.91 | 8975.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.405644E+10 | 8985.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.105256E+11 | 33286.52 | 12-JAN-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.450367E+10 | 33291.92 | 15-FEB-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.290201E+10 | 33280.69 | 09-MAR-07:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.530635E+09 | 33280.67 | 19-APR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.529604E+09 | 33286.30 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 267233.09 | 4453.88 | 16-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 10052508.06 | 33320.58 | 05-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.115266E+09 | 33294.39 | 23-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 7277199.77 | 33305.50 | 13-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 85905769.74 | 33276.52 | 04-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.190074E+10 | 33278.14 | 22-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.608958E+10 | 33299.19 | 06-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.272006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 267233.09 | 4453.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.105256E+11 | 33320.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.502060E+10 | 7878.84 | 12-JAN-07:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.259925E+10 | 7879.07 | 15-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.156604E+10 | 7878.55 | 02-MAR-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.179554E+09 | 7884.43 | 17-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.250400E+09 | 7880.96 | 08-MAY-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 3345884.60 | 7870.18 | 18-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 196254.11 | 3270.90 | 20-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 58294976.04 | 7867.09 | 12-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.114510E+10 | 7879.62 | 07-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.311526E+10 | 7879.74 | 19-DEC-07:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.139380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.502060E+10 | 7884.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.498881E+10 | 8526.60 | 03-JAN-06:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.266298E+10 | 8526.96 | 08-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.202233E+10 | 8529.29 | 02-MAR-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.528999E+09 | 8532.04 | 21-APR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.322918E+09 | 8529.19 | 26-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 6606690.06 | 8523.07 | 16-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 11977862.35 | 8527.56 | 05-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 95263099.34 | 8530.50 | 22-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 58143207.03 | 8527.03 | 12-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.180726E+09 | 8524.36 | 03-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.131114E+10 | 8530.02 | 16-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.318717E+10 | 8524.96 | 05-DEC-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.153771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 6606690.06 | 8523.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.498881E+10 | 8532.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.945108E+10 | 20863.52 | 17-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.482398E+10 | 20872.16 | 13-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.336054E+10 | 20878.45 | 02-MAR-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.679020E+09 | 20870.56 | 18-APR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.448083E+09 | 20875.82 | 08-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 380229.68 | 6337.16 | 16-JUN-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 15494751.08 | 20882.57 | 05-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.170604E+09 | 20889.15 | 22-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 27832327.42 | 20879.84 | 14-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.214121E+09 | 20862.03 | 17-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.225055E+10 | 20879.11 | 16-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.570477E+10 | 20867.22 | 06-DEC-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.271465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 380229.68 | 6337.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.945108E+10 | 20889.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.329032E+10 | 10753.96 | 17-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.133947E+10 | 10756.39 | 13-FEB-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.808958E+09 | 10749.98 | 07-MAR-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 91150909.14 | 10748.08 | 17-APR-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 89095539.00 | 10751.22 | 01-MAY-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 332766.70 | 5546.11 | 05-JUL-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 4416551.27 | 10753.45 | 17-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 1472212.07 | 9444.99 | 19-SEP-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 28250328.25 | 10745.26 | 12-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.470405E+09 | 10751.69 | 15-NOV-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.166954E+10 | 10754.09 | 20-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.779340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.329032E+10 | 10756.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.132468E+11 | 17559.18 | 12-JAN-07:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.685394E+10 | 17559.84 | 15-FEB-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.360767E+10 | 17560.12 | 02-MAR-07:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.129747E+09 | 17613.73 | 19-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.224021E+09 | 17560.99 | 01-MAY-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.135186E+09 | 17570.72 | 10-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.336709E+10 | 17610.70 | 17-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.848753E+10 | 17574.93 | 06-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.360520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.132468E+11 | 17613.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LOBBY_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.128216E+11 | 10271.75 | 12-JAN-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.898965E+10 | 10762.31 | 28-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.899438E+10 | 10760.93 | 01-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.500103E+10 | 10765.59 | 13-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.427715E+10 | 10775.85 | 15-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.124825E+10 | 10761.03 | 16-JUN-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.465993E+09 | 10331.50 | 11-JUL-06:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.104893E+10 | 10645.85 | 17-AUG-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.193738E+10 | 10773.14 | 11-SEP-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.350020E+10 | 10770.61 | 06-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.685663E+10 | 10764.25 | 09-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.101855E+11 | 10308.22 | 19-DEC-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.653267E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.465993E+09 | 10271.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.128216E+11 | 10775.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECH_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.159203E+09 | 8764.87 | 09-JAN-06:31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 861128.27 | 472.68 | 05-FEB-21:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 41606327.54 | 6275.99 | 31-DEC-07:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.201671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.159203E+09 | 8764.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: BATH_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.174129E+10 | 8132.40 | 08-JAN-10:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.496114E+09 | 8133.77 | 05-FEB-08:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.235197E+09 | 8099.73 | 06-MAR-06:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 48040580.02 | 7817.36 | 27-NOV-06:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.868631E+09 | 8139.87 | 31-DEC-16:24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.338927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.174129E+10 | 8139.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: OFFICES_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.116592E+11 | 24208.51 | 12-JAN-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.520671E+10 | 24203.39 | 13-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.275397E+10 | 24201.86 | 09-MAR-07:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.167709E+09 | 24220.53 | 21-APR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.250305E+09 | 24204.57 | 08-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 57918588.74 | 24161.49 | 06-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.208285E+10 | 24199.20 | 29-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.670938E+10 | 24206.96 | 19-DEC-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.288880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.116592E+11 | 24220.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: GYM_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.716181E+10 | 22435.13 | 20-JAN-06:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.304365E+10 | 22431.09 | 08-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.154019E+10 | 22433.17 | 07-MAR-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.120617E+09 | 21848.15 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.137240E+09 | 22435.16 | 01-MAY-05:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 98689951.40 | 22423.51 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.135495E+10 | 22429.92 | 28-NOV-06:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.404417E+10 | 22431.12 | 04-DEC-06:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.175013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.716181E+10 | 22435.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 VAV BOX REHEAT COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.974341E+10 | 23655.54 | 12-JAN-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.425625E+10 | 23655.12 | 13-FEB-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.209293E+10 | 23649.07 | 27-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 58092589.92 | 23614.90 | 21-APR-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.109612E+09 | 23638.84 | 01-MAY-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 32755275.39 | 23573.19 | 11-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.152203E+10 | 23651.67 | 29-NOV-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.532455E+10 | 23654.19 | 19-DEC-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.231396E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.974341E+10 | 23655.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_POD_1 HEATING COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.180333E+12 | 383254.89 | 10-JAN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.107223E+12 | 344943.76 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.726979E+11 | 267756.80 | 06-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.268354E+11 | 143062.51 | 28-APR-20:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.189550E+11 | 130632.36 | 08-MAY-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.184454E+10 | 83009.97 | 16-JUN-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 29489599.00 | 29631.98 | 05-JUL-10:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.679715E+09 | 22828.20 | 17-AUG-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.623148E+10 | 92227.56 | 12-SEP-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.187237E+11 | 168819.93 | 10-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.552413E+11 | 231047.26 | 27-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.119886E+12 | 376738.22 | 29-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.608681E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 29489599.00 | 22828.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.180333E+12 | 383254.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:6 HEATING COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.418037E+09 | 34404.54 | 09-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 991161.77 | 1717.41 | 01-FEB-08:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 694345.79 | 5786.21 | 07-APR-05:34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 12521.13 | 83.47 | 06-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 1026384.67 | 5131.92 | 26-JUL-05:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 846899.02 | 4234.50 | 07-AUG-05:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 2773291.31 | 9578.65 | 23-OCT-05:54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 57799630.56 | 34404.54 | 21-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.196755E+09 | 5725.58 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.678937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.418037E+09 | 34404.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:7 HEATING COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.631277E+11 | 112439.17 | 02-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.293648E+11 | 112439.17 | 01-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.188450E+11 | 112439.17 | 01-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.443020E+10 | 112439.17 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.291696E+10 | 112439.17 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.166869E+09 | 24957.82 | 16-JUN-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 16650790.59 | 8968.09 | 05-JUL-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.320943E+09 | 15706.07 | 17-AUG-07:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.882697E+09 | 29664.02 | 19-SEP-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.297106E+10 | 112439.17 | 10-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.108445E+11 | 112439.17 | 13-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.338141E+11 | 112439.17 | 01-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.167701E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 16650790.59 | 8968.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.631277E+11 | 112439.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_POD_1 COOLING COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.954678E+09 | 0.954678E+09 | 106496.12 | 27-FEB-15:02 | 106496.12 | 0.00 |
| March | 0.00 | 0.00 | 50032396.78 | 50032396.78 | 50862.41 | 29-MAR-14:01 | 50862.41 | 0.00 |
| April | 0.00 | 0.00 | 0.106558E+11 | 0.106489E+11 | 156505.37 | 07-APR-14:05 | 156505.37 | 0.00 |
| May | 0.00 | 0.00 | 0.415497E+11 | 0.411490E+11 | 322303.74 | 19-MAY-15:00 | 322303.74 | 0.00 |
| June | 0.00 | 0.00 | 0.149293E+12 | 0.145229E+12 | 374203.30 | 20-JUN-14:02 | 293261.26 | 0.00 |
| July | 0.00 | 0.00 | 0.201372E+12 | 0.196561E+12 | 378458.23 | 17-JUL-14:03 | 378458.23 | 0.00 |
| August | 0.00 | 0.00 | 0.160340E+12 | 0.159019E+12 | 342857.46 | 09-AUG-14:02 | 342857.46 | 0.00 |
| September | 0.00 | 0.00 | 0.926819E+11 | 0.858695E+11 | 414331.42 | 07-SEP-14:50 | 215698.89 | 0.00 |
| October | 0.00 | 0.00 | 0.223408E+11 | 0.223300E+11 | 266136.52 | 18-OCT-14:05 | 266136.52 | 0.00 |
| November | 0.00 | 0.00 | 0.997280E+09 | 0.992459E+09 | 58051.02 | 07-NOV-15:01 | 58051.02 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.680235E+12 | 0.662803E+12 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.201372E+12 | 0.196561E+12 | 414331.42 | 378458.23 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:6 COOLING COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 18977774.27 | 15949374.42 | 32953.58 | 03-JAN-06:01 | 28085.34 | 0.00 |
| February | 0.00 | 0.00 | 0.111389E+09 | 0.105095E+09 | 32953.58 | 14-FEB-06:01 | 25336.08 | 0.00 |
| March | 0.00 | 0.00 | 87021805.29 | 72317292.69 | 32953.58 | 02-MAR-06:01 | 27118.86 | 0.00 |
| April | 0.00 | 0.00 | 0.982515E+09 | 0.940492E+09 | 32953.58 | 03-APR-05:01 | 25602.99 | 0.00 |
| May | 0.00 | 0.00 | 0.329264E+10 | 0.307036E+10 | 33390.76 | 20-MAY-11:08 | 30295.56 | 0.00 |
| June | 0.00 | 0.00 | 0.108150E+11 | 0.946592E+10 | 34925.94 | 21-JUN-20:53 | 26024.75 | 0.00 |
| July | 0.00 | 0.00 | 0.160925E+11 | 0.144114E+11 | 35859.65 | 18-JUL-22:52 | 18244.45 | 0.00 |
| August | 0.00 | 0.00 | 0.134636E+11 | 0.124520E+11 | 33757.06 | 08-AUG-22:38 | 29576.81 | 0.00 |
| September | 0.00 | 0.00 | 0.716134E+10 | 0.624324E+10 | 35412.10 | 06-SEP-20:53 | 19618.35 | 0.00 |
| October | 0.00 | 0.00 | 0.171507E+10 | 0.166801E+10 | 32953.58 | 23-OCT-05:52 | 29567.39 | 0.00 |
| November | 0.00 | 0.00 | 0.116179E+09 | 99567394.97 | 32953.58 | 20-NOV-06:01 | 29341.85 | 0.00 |
| December | 0.00 | 0.00 | 37893024.54 | 31124710.11 | 32953.58 | 01-DEC-06:01 | 28637.37 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.538941E+11 | 0.485755E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 18977774.27 | 15949374.42 | 32953.58 | 18244.45 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.160925E+11 | 0.144114E+11 | 35859.65 | 30295.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:7 COOLING COIL
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 19091236.62 | 19091236.62 | 4983.82 | 27-FEB-15:00 | 4983.82 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.571373E+09 | 0.569061E+09 | 24094.39 | 07-APR-14:00 | 24094.39 | 0.00 |
| May | 0.00 | 0.00 | 0.258253E+10 | 0.244200E+10 | 39672.59 | 19-MAY-14:00 | 36034.95 | 0.00 |
| June | 0.00 | 0.00 | 0.150821E+11 | 0.137061E+11 | 63873.44 | 24-JUN-10:23 | 51286.91 | 0.00 |
| July | 0.00 | 0.00 | 0.158748E+11 | 0.154583E+11 | 65358.43 | 16-JUL-09:43 | 45997.99 | 0.00 |
| August | 0.00 | 0.00 | 0.126157E+11 | 0.124909E+11 | 61092.43 | 07-AUG-05:42 | 54812.08 | 0.00 |
| September | 0.00 | 0.00 | 0.761769E+10 | 0.639375E+10 | 61593.44 | 07-SEP-05:01 | 33016.83 | 0.00 |
| October | 0.00 | 0.00 | 0.152701E+10 | 0.152572E+10 | 29542.04 | 18-OCT-14:00 | 29542.04 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.558903E+11 | 0.526050E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.158748E+11 | 0.154583E+11 | 65358.43 | 54812.08 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 63422.98 | 724209.17 | 02-JAN-06:01 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 34668.01 | 744994.39 | 09-FEB-06:11 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 21367.81 | 759191.28 | 13-MAR-05:01 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 5176.33 | 719700.72 | 04-APR-06:01 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 4213.90 | 684046.10 | 09-MAY-06:01 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 493.45 | 88110.17 | 16-JUN-07:01 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 244.67 | 240293.09 | 05-JUL-07:01 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 1000.59 | 442874.41 | 18-AUG-07:01 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 910.63 | 341058.09 | 20-SEP-07:01 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 2223.94 | 701237.77 | 11-OCT-06:01 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 15507.00 | 707587.68 | 27-NOV-06:11 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 38705.54 | 783986.54 | 04-DEC-06:01 |
| Annual Sum or Average | 0.00 | 15616.14 | ||||
| Minimum of Months | 0.00 | 0.00 | 244.67 | 88110.17 | ||
| Maximum of Months | 0.00 | 0.00 | 63422.98 | 783986.54 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 3936.74 | 20233.20 | 31-JAN-13:30 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 4012.14 | 20342.16 | 17-FEB-14:00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 4340.70 | 20305.53 | 01-MAR-14:00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 3760.90 | 19746.26 | 03-APR-12:50 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 3791.26 | 18864.66 | 01-MAY-12:50 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 2307.32 | 17705.43 | 01-JUN-12:20 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 754.56 | 4995.59 | 03-JUL-18:20 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 848.97 | 4818.62 | 01-AUG-18:15 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 1968.82 | 16440.02 | 29-SEP-13:00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 3342.73 | 17421.18 | 31-OCT-13:00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 3668.05 | 18542.78 | 30-NOV-13:50 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 3584.81 | 19530.40 | 29-DEC-13:30 |
| Annual Sum or Average | 0.00 | 3019.41 | ||||
| Minimum of Months | 0.00 | 0.00 | 754.56 | 4818.62 | ||
| Maximum of Months | 0.00 | 0.00 | 4340.70 | 20342.16 |
Report: FanReportMonthly
For: VAV_POD_1 FAN
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.306032E+11 | 0.77 | 21901.89 | 08-JAN-23:51 | 1.24 |
| February | 0.230482E+11 | 0.65 | 21485.55 | 01-FEB-06:11 | 1.22 |
| March | 0.232973E+11 | 0.59 | 21485.55 | 06-MAR-06:11 | 1.23 |
| April | 0.170154E+11 | 0.44 | 25486.40 | 25-APR-14:08 | 1.31 |
| May | 0.224371E+11 | 0.52 | 46283.54 | 19-MAY-14:00 | 1.67 |
| June | 0.308459E+11 | 0.66 | 46046.52 | 06-JUN-14:40 | 1.66 |
| July | 0.247289E+11 | 0.57 | 27776.40 | 17-JUL-17:10 | 1.35 |
| August | 0.239393E+11 | 0.56 | 30811.92 | 11-AUG-15:10 | 1.42 |
| September | 0.243438E+11 | 0.54 | 51459.59 | 26-SEP-14:03 | 1.75 |
| October | 0.194058E+11 | 0.45 | 39337.65 | 18-OCT-14:00 | 1.57 |
| November | 0.200589E+11 | 0.52 | 22531.81 | 03-NOV-14:30 | 1.24 |
| December | 0.272020E+11 | 0.69 | 21485.55 | 26-DEC-06:11 | 1.22 |
| Annual Sum or Average | 0.286926E+12 | 0.58 | |||
| Minimum of Months | 0.170154E+11 | 0.44 | 21485.55 | 1.22 | |
| Maximum of Months | 0.308459E+11 | 0.77 | 51459.59 | 1.75 |
Report: FanReportMonthly
For: BATH_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:03 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: GYM_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:03 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | -0.0 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | -0.0 | 0.00 | 01-JUL-00:03 | 0.00 |
| August | 0.00 | -0.0 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:03 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | -0.0 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | -0.0 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 |
| August | 0.00 | -0.0 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:03 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | -0.0 |
| November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: CAFETERIA_ZN_1_FLR_1 EXHAUST FAN
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 0.00 | -0.0 | 0.00 | 01-FEB-00:05 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | -0.0 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | -0.0 | 0.00 | 01-JUN-00:03 | 0.00 |
| July | 0.00 | -0.0 | 0.00 | 01-JUL-00:03 | 0.00 |
| August | 0.00 | -0.0 | 0.00 | 01-AUG-00:03 | 0.00 |
| September | 0.00 | -0.0 | 0.00 | 01-SEP-00:03 | 0.00 |
| October | 0.00 | -0.0 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | -0.0 | 0.00 | 01-DEC-00:05 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.313669E+10 | 0.65 | 2936.62 | 19-JAN-08:00 | 1.53 |
| February | 0.284370E+10 | 0.71 | 2936.62 | 01-FEB-08:18 | 1.53 |
| March | 0.345826E+10 | 0.83 | 2936.62 | 07-MAR-07:12 | 1.53 |
| April | 0.314470E+10 | 1.05 | 2936.62 | 17-APR-12:20 | 1.56 |
| May | 0.366485E+10 | 1.17 | 2936.62 | 02-MAY-15:20 | 1.56 |
| June | 0.391558E+10 | 1.25 | 2936.62 | 01-JUN-12:00 | 1.54 |
| July | 0.397892E+10 | 1.23 | 2936.62 | 01-JUL-13:32 | 1.54 |
| August | 0.423509E+10 | 1.25 | 2936.62 | 04-AUG-09:40 | 1.55 |
| September | 0.370026E+10 | 1.24 | 2936.62 | 03-SEP-13:44 | 1.55 |
| October | 0.337229E+10 | 1.18 | 2936.62 | 12-OCT-15:05 | 1.56 |
| November | 0.320253E+10 | 0.89 | 2936.62 | 17-NOV-13:00 | 1.56 |
| December | 0.297996E+10 | 0.64 | 2936.62 | 26-DEC-07:40 | 1.52 |
| Annual Sum or Average | 0.416328E+11 | 1.01 | |||
| Minimum of Months | 0.284370E+10 | 0.64 | 2936.62 | 1.52 | |
| Maximum of Months | 0.423509E+10 | 1.25 | 2936.62 | 1.56 |
Report: FanReportMonthly
For: PSZ-AC_2:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.661085E+10 | 0.80 | 4952.98 | 06-JAN-11:40 | 1.53 |
| February | 0.520840E+10 | 0.71 | 4952.98 | 22-FEB-08:10 | 1.53 |
| March | 0.604869E+10 | 0.74 | 4952.98 | 15-MAR-07:05 | 1.52 |
| April | 0.500248E+10 | 0.60 | 4952.98 | 11-APR-07:23 | 1.53 |
| May | 0.550704E+10 | 0.64 | 4952.98 | 22-MAY-14:50 | 1.52 |
| June | 0.556072E+10 | 0.71 | 4952.98 | 01-JUN-06:40 | 1.51 |
| July | 0.525067E+10 | 0.72 | 4952.98 | 03-JUL-06:02 | 1.51 |
| August | 0.592831E+10 | 0.72 | 4952.98 | 01-AUG-06:20 | 1.51 |
| September | 0.514738E+10 | 0.66 | 4952.98 | 01-SEP-06:07 | 1.51 |
| October | 0.524750E+10 | 0.60 | 4952.98 | 16-OCT-15:00 | 1.52 |
| November | 0.529846E+10 | 0.65 | 4952.98 | 01-NOV-07:07 | 1.52 |
| December | 0.554867E+10 | 0.72 | 4952.98 | 06-DEC-08:30 | 1.52 |
| Annual Sum or Average | 0.663592E+11 | 0.69 | |||
| Minimum of Months | 0.500248E+10 | 0.60 | 4952.98 | 1.51 | |
| Maximum of Months | 0.661085E+10 | 0.80 | 4952.98 | 1.53 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 0.741523E+09 | 0.667370E+09 | 1305.91 | 08-JAN-20:31 | 1175.32 | 1175.32 | 47.36 | 4.18 |
| February | 0.385353E+09 | 0.346818E+09 | 1292.17 | 01-FEB-06:52 | 1162.96 | 1162.96 | 56.70 | 4.10 |
| March | 0.276944E+09 | 0.249249E+09 | 1293.55 | 06-MAR-06:52 | 1164.20 | 1164.20 | 59.21 | 4.10 |
| April | 83417782.55 | 75076004.29 | 1192.62 | 03-APR-06:02 | 1073.36 | 1073.36 | 51.87 | 3.82 |
| May | 70393641.44 | 63354277.30 | 1200.14 | 01-MAY-06:01 | 1080.13 | 1080.13 | 50.20 | 3.84 |
| June | 13632407.76 | 12269166.98 | 696.54 | 16-JUN-07:01 | 626.89 | 626.89 | 61.34 | 1.02 |
| July | 5663370.40 | 5097033.36 | 1010.59 | 05-JUL-07:01 | 909.53 | 909.53 | 60.37 | 2.65 |
| August | 16809989.66 | 15128990.70 | 1043.37 | 18-AUG-07:01 | 939.03 | 939.03 | 46.86 | 3.01 |
| September | 21400463.56 | 19260417.21 | 1032.43 | 20-SEP-07:01 | 929.19 | 929.19 | 53.89 | 2.90 |
| October | 45634809.78 | 41071328.80 | 1195.50 | 10-OCT-06:02 | 1075.95 | 1075.95 | 53.63 | 3.82 |
| November | 0.200158E+09 | 0.180142E+09 | 1289.40 | 27-NOV-06:11 | 1160.46 | 1160.46 | 40.91 | 4.12 |
| December | 0.470548E+09 | 0.423494E+09 | 1305.91 | 31-DEC-07:01 | 1175.32 | 1175.32 | 45.87 | 4.16 |
| Annual Sum or Average | 0.233148E+10 | 0.209833E+10 | ||||||
| Minimum of Months | 5663370.40 | 5097033.36 | 696.54 | 626.89 | 626.89 | 40.91 | 1.02 | |
| Maximum of Months | 0.741523E+09 | 0.667370E+09 | 1305.91 | 1175.32 | 1175.32 | 61.34 | 4.18 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 12215899.87 | 3664769.96 | 13.47 | 02-JAN-08:61 | 4.04 | 4.04 | 53.29 | 0.11 |
| February | 11052480.83 | 3315744.25 | 13.47 | 01-FEB-08:61 | 4.04 | 4.04 | 44.39 | 0.11 |
| March | 13379318.90 | 4013795.67 | 13.47 | 01-MAR-08:61 | 4.04 | 4.04 | 44.34 | 0.11 |
| April | 11634190.35 | 3490257.10 | 13.47 | 03-APR-07:01 | 4.04 | 4.04 | 44.74 | 0.11 |
| May | 12797609.38 | 3839282.82 | 13.47 | 01-MAY-07:01 | 4.04 | 4.04 | 45.40 | 0.11 |
| June | 12797609.38 | 3839282.82 | 13.47 | 01-JUN-07:01 | 4.04 | 4.04 | 46.32 | 0.11 |
| July | 11634190.35 | 3490257.10 | 13.47 | 03-JUL-07:03 | 4.04 | 4.04 | 52.97 | 0.11 |
| August | 13379318.90 | 4013795.67 | 13.47 | 01-AUG-07:01 | 4.04 | 4.04 | 52.15 | 0.11 |
| September | 11634190.35 | 3490257.10 | 13.47 | 01-SEP-07:03 | 4.04 | 4.04 | 53.27 | 0.11 |
| October | 12215899.87 | 3664769.96 | 13.47 | 02-OCT-07:01 | 4.04 | 4.04 | 47.29 | 0.11 |
| November | 12215899.87 | 3664769.96 | 13.47 | 01-NOV-07:01 | 4.04 | 4.04 | 46.54 | 0.11 |
| December | 11634190.35 | 3490257.10 | 13.47 | 01-DEC-08:61 | 4.04 | 4.04 | 45.68 | 0.11 |
| Annual Sum or Average | 0.146591E+09 | 43977239.52 | ||||||
| Minimum of Months | 11052480.83 | 3315744.25 | 13.47 | 4.04 | 4.04 | 44.34 | 0.11 | |
| Maximum of Months | 13379318.90 | 4013795.67 | 13.47 | 4.04 | 4.04 | 53.29 | 0.11 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 25.65 | 25.65 | 63422.98 | 724209.17 | 02-JAN-06:01 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 37.99 | 37.99 | 34668.01 | 744994.39 | 09-FEB-06:11 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 24.25 | 24.25 | 21367.81 | 759191.28 | 13-MAR-05:01 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 26.56 | 26.56 | 5176.33 | 719700.72 | 04-APR-06:01 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 23.91 | 82.00 | 4213.90 | 684046.10 | 09-MAY-06:01 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 61.77 | 61.77 | 493.45 | 88110.17 | 16-JUN-07:01 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 62.77 | 62.77 | 244.67 | 240293.09 | 05-JUL-07:01 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 58.62 | 58.62 | 1000.59 | 442874.41 | 18-AUG-07:01 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 48.37 | 48.37 | 910.63 | 341058.09 | 20-SEP-07:01 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 56.42 | 56.42 | 2223.94 | 701237.77 | 11-OCT-06:01 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 27.27 | 27.27 | 15507.00 | 707587.68 | 27-NOV-06:11 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 30.52 | 30.52 | 38705.54 | 783986.54 | 04-DEC-06:01 |
| Annual Sum or Average | 0.00 | 15616.14 | ||||||
| Minimum of Months | 0.00 | 0.00 | 23.91 | 24.25 | 244.67 | 88110.17 | ||
| Maximum of Months | 0.00 | 0.00 | 62.77 | 82.00 | 63422.98 | 783986.54 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 60.00 | 60.00 | 3936.74 | 20233.20 | 31-JAN-13:30 |
| February | 0.00 | 0.00 | 01-FEB-00:05 | 46.23 | 46.23 | 4012.14 | 20342.16 | 17-FEB-14:00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 46.18 | 46.18 | 4340.70 | 20305.53 | 01-MAR-14:00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 46.51 | 46.51 | 3760.90 | 19746.26 | 03-APR-12:50 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 47.08 | 47.08 | 3791.26 | 18864.66 | 01-MAY-12:50 |
| June | 0.00 | 0.00 | 01-JUN-00:03 | 47.91 | 47.91 | 2307.32 | 17705.43 | 01-JUN-12:20 |
| July | 0.00 | 0.00 | 01-JUL-00:03 | 48.61 | 48.61 | 754.56 | 4995.59 | 03-JUL-18:20 |
| August | 0.00 | 0.00 | 01-AUG-00:03 | 49.06 | 49.06 | 848.97 | 4818.62 | 01-AUG-18:15 |
| September | 0.00 | 0.00 | 01-SEP-00:03 | 49.12 | 49.12 | 1968.82 | 16440.02 | 29-SEP-13:00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 48.80 | 48.80 | 3342.73 | 17421.18 | 31-OCT-13:00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 48.13 | 48.13 | 3668.05 | 18542.78 | 30-NOV-13:50 |
| December | 0.00 | 0.00 | 01-DEC-00:05 | 47.37 | 47.37 | 3584.81 | 19530.40 | 29-DEC-13:30 |
| Annual Sum or Average | 0.00 | 3019.41 | ||||||
| Minimum of Months | 0.00 | 0.00 | 46.18 | 46.18 | 754.56 | 4818.62 | ||
| Maximum of Months | 0.00 | 0.00 | 60.00 | 60.00 | 4340.70 | 20342.16 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_POD_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.171261E+12 | 0.00 | 0.00 | 0.306032E+11 | 0.00 | 0.00 |
| February | 0.845417E+11 | 0.00 | 0.00 | 0.233363E+11 | 0.00 | 0.00 |
| March | 0.576204E+11 | 0.00 | 0.00 | 0.233135E+11 | 0.00 | 0.00 |
| April | 0.135328E+11 | 0.00 | 0.00 | 0.201563E+11 | 0.00 | 0.00 |
| May | 0.113531E+11 | 0.00 | 0.00 | 0.340027E+11 | 0.00 | 0.00 |
| June | 0.129511E+10 | 0.00 | 0.00 | 0.708108E+11 | 0.00 | 0.00 |
| July | 0.667560E+09 | 0.00 | 0.00 | 0.792602E+11 | 0.00 | 0.00 |
| August | 0.271867E+10 | 0.00 | 0.00 | 0.674868E+11 | 0.00 | 0.00 |
| September | 0.238102E+10 | 0.00 | 0.00 | 0.494426E+11 | 0.00 | 0.00 |
| October | 0.604538E+10 | 0.00 | 0.00 | 0.256775E+11 | 0.00 | 0.00 |
| November | 0.405359E+11 | 0.00 | 0.00 | 0.203755E+11 | 0.00 | 0.00 |
| December | 0.104485E+12 | 0.00 | 0.00 | 0.272020E+11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.496437E+12 | 0.00 | 0.00 | 0.471667E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.667560E+09 | 0.00 | 0.00 | 0.201563E+11 | 0.00 | 0.00 |
| Maximum of Months | 0.171261E+12 | 0.00 | 0.00 | 0.792602E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:6
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.314160E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.287330E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.348126E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.339581E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.448634E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.659570E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.811192E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.768860E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.550407E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.379428E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.323342E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.298986E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.552962E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.287330E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.811192E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:7
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.661085E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.521389E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.604869E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.515765E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.618971E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.946268E+10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.976019E+10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.951746E+10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.714880E+10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.564929E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.529846E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.554867E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.816063E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.515765E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.976019E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_POD_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.306032E+11 | 0.00 | 0.351594E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.230482E+11 | 0.954678E+09 | 0.191765E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.232973E+11 | 50032396.78 | 0.130318E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.170154E+11 | 0.106558E+11 | 0.403682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.224371E+11 | 0.415497E+11 | 0.303081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.308459E+11 | 0.149293E+12 | 0.313966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.247289E+11 | 0.201372E+12 | 0.697049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.239393E+11 | 0.160340E+12 | 0.339839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.243438E+11 | 0.926819E+11 | 0.861249E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.194058E+11 | 0.223408E+11 | 0.247691E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.200589E+11 | 0.997280E+09 | 0.957772E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.272020E+11 | 0.00 | 0.224371E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.286926E+12 | 0.680235E+12 | 0.110512E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.170154E+11 | 0.00 | 0.697049E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.308459E+11 | 0.201372E+12 | 0.351594E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:6
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.313669E+10 | 18977774.27 | 0.418037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.284370E+10 | 0.111389E+09 | 991161.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.345826E+10 | 87021805.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.314470E+10 | 0.982515E+09 | 694345.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.366485E+10 | 0.329264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.391558E+10 | 0.108150E+11 | 12521.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.397892E+10 | 0.160925E+11 | 1026384.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.423509E+10 | 0.134636E+11 | 846899.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.370026E+10 | 0.716134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.337229E+10 | 0.171507E+10 | 2773291.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.320253E+10 | 0.116179E+09 | 57799630.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.297996E+10 | 37893024.54 | 0.196755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.416328E+11 | 0.538941E+11 | 0.678937E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.284370E+10 | 18977774.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.423509E+10 | 0.160925E+11 | 0.418037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:7
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.661085E+10 | 0.00 | 0.631277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.520840E+10 | 19091236.62 | 0.293648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.604869E+10 | 0.00 | 0.188450E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.500248E+10 | 0.571373E+09 | 0.443020E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.550704E+10 | 0.258253E+10 | 0.291696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.556072E+10 | 0.150821E+11 | 0.166869E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.525067E+10 | 0.158748E+11 | 16650790.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.592831E+10 | 0.126157E+11 | 0.320943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.514738E+10 | 0.761769E+10 | 0.882697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.524750E+10 | 0.152701E+10 | 0.297106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.529846E+10 | 0.00 | 0.108445E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.554867E+10 | 0.00 | 0.338141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.663592E+11 | 0.558903E+11 | 0.167701E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.500248E+10 | 0.00 | 16650790.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.661085E+10 | 0.158748E+11 | 0.631277E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_POD_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.306032E+11 | 0.171261E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.230482E+11 | 0.845417E+11 | 0.00 | 0.00 | 0.288124E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.232973E+11 | 0.576204E+11 | 0.00 | 0.00 | 16202317.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.170154E+11 | 0.135328E+11 | 0.00 | 0.00 | 0.314091E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.224371E+11 | 0.113531E+11 | 0.00 | 0.00 | 0.115657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.308459E+11 | 0.129511E+10 | 0.00 | 0.00 | 0.399649E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.247289E+11 | 0.667560E+09 | 0.00 | 0.00 | 0.545312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.239393E+11 | 0.271867E+10 | 0.00 | 0.00 | 0.435475E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.243438E+11 | 0.238102E+10 | 0.00 | 0.00 | 0.250988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.194058E+11 | 0.604538E+10 | 0.00 | 0.00 | 0.627177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.200589E+11 | 0.405359E+11 | 0.00 | 0.00 | 0.316638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.272020E+11 | 0.104485E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.286926E+12 | 0.496437E+12 | 0.00 | 0.00 | 0.184742E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.170154E+11 | 0.667560E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.308459E+11 | 0.171261E+12 | 0.00 | 0.00 | 0.545312E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:6
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.313669E+10 | 0.00 | 0.00 | 0.00 | 4910634.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.284370E+10 | 0.00 | 0.00 | 0.00 | 29594095.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.345826E+10 | 0.00 | 0.00 | 0.00 | 23000966.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.314470E+10 | 0.00 | 0.00 | 0.00 | 0.251109E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.366485E+10 | 0.00 | 0.00 | 0.00 | 0.821497E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.391558E+10 | 0.00 | 0.00 | 0.00 | 0.268012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.397892E+10 | 0.00 | 0.00 | 0.00 | 0.413300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.423509E+10 | 0.00 | 0.00 | 0.00 | 0.345350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.370026E+10 | 0.00 | 0.00 | 0.00 | 0.180380E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.337229E+10 | 0.00 | 0.00 | 0.00 | 0.421994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.320253E+10 | 0.00 | 0.00 | 0.00 | 30889028.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.297996E+10 | 0.00 | 0.00 | 0.00 | 9900571.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.416328E+11 | 0.00 | 0.00 | 0.00 | 0.136633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.284370E+10 | 0.00 | 0.00 | 0.00 | 4910634.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.423509E+10 | 0.00 | 0.00 | 0.00 | 0.413300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:7
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.661085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.520840E+10 | 0.00 | 0.00 | 0.00 | 5495889.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.604869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.500248E+10 | 0.00 | 0.00 | 0.00 | 0.155166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.550704E+10 | 0.00 | 0.00 | 0.00 | 0.682669E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.556072E+10 | 0.00 | 0.00 | 0.00 | 0.390197E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.525067E+10 | 0.00 | 0.00 | 0.00 | 0.450953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.592831E+10 | 0.00 | 0.00 | 0.00 | 0.358916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.514738E+10 | 0.00 | 0.00 | 0.00 | 0.200141E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.524750E+10 | 0.00 | 0.00 | 0.00 | 0.401794E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.529846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.554867E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.663592E+11 | 0.00 | 0.00 | 0.00 | 0.152472E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.500248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.661085E+10 | 0.00 | 0.00 | 0.00 | 0.450953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.229374E+10 | 0.00 | 0.00 | 34.75 | 0.00 | 0.440053E+10 | 1916649.33 | 0.00 | 0.69 |
| February | 0.268563E+10 | 0.00 | 0.00 | 266530.60 | 0.00 | 0.208333E+10 | 0.192975E+09 | 0.00 | 0.70 |
| March | 0.337347E+10 | 0.00 | 0.00 | 475414.55 | 0.00 | 0.104174E+10 | 0.453283E+09 | 0.00 | 0.74 |
| April | 0.249719E+10 | 0.00 | 0.00 | 941553.19 | 0.00 | 0.141771E+09 | 0.794641E+09 | 0.00 | 0.76 |
| May | 0.204275E+10 | 1411759.52 | 0.00 | 2319883.16 | 912297.06 | 0.143487E+09 | 0.140735E+10 | 0.00 | 0.97 |
| June | 0.847693E+09 | 0.182500E+09 | 0.00 | 3094065.58 | 10049479.51 | 695736.83 | 0.151380E+10 | 0.00 | 1.30 |
| July | 0.506497E+09 | 0.473614E+09 | 0.00 | 301260.16 | 62241339.40 | 877701.60 | 86312269.10 | 0.00 | 0.96 |
| August | 0.913658E+09 | 0.360340E+09 | 0.00 | 694738.13 | 21705189.88 | 7855788.89 | 0.150852E+09 | 0.00 | 1.06 |
| September | 0.110440E+10 | 83650545.60 | 0.00 | 3411090.32 | 14598108.27 | 2074746.14 | 0.149403E+10 | 0.00 | 1.09 |
| October | 0.154416E+10 | 0.00 | 0.00 | 3349727.95 | 14663.47 | 31933799.16 | 0.217156E+10 | 0.00 | 0.93 |
| November | 0.251320E+10 | 0.00 | 0.00 | 1090022.52 | 0.00 | 0.747942E+09 | 0.102055E+10 | 0.00 | 0.74 |
| December | 0.277839E+10 | 0.00 | 0.00 | 38031.80 | 0.00 | 0.250211E+10 | 0.116257E+09 | 0.00 | 0.66 |
| Annual Sum or Average | 0.231008E+11 | 0.110152E+10 | 0.00 | 15982352.72 | 0.109521E+09 | 0.111044E+11 | 0.940352E+10 | 0.00 | 0.88 |
| Minimum of Months | 0.506497E+09 | 0.00 | 0.00 | 34.75 | 0.00 | 695736.83 | 1916649.33 | 0.00 | 0.66 |
| Maximum of Months | 0.337347E+10 | 0.473614E+09 | 0.00 | 3411090.32 | 62241339.40 | 0.440053E+10 | 0.217156E+10 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_1_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.181199E+11 | 0.00 | 0.00 | 5140.15 | 0.00 | 0.140547E+11 | 45278942.51 | 0.00 | 0.69 |
| February | 0.170004E+11 | 0.00 | 0.00 | 1945749.77 | 0.00 | 0.518423E+10 | 0.174866E+10 | 0.00 | 0.71 |
| March | 0.177106E+11 | 0.00 | 0.00 | 4919190.36 | 0.00 | 0.179782E+10 | 0.403854E+10 | 0.00 | 0.74 |
| April | 0.109374E+11 | 0.00 | 0.00 | 6932973.81 | 0.00 | 0.113366E+09 | 0.563574E+10 | 0.00 | 0.76 |
| May | 0.873200E+10 | 5231132.15 | 0.00 | 12871498.02 | 4395671.05 | 0.151096E+09 | 0.864746E+10 | 0.00 | 0.98 |
| June | 0.387925E+10 | 0.749633E+09 | 0.00 | 15198055.50 | 48420857.80 | 0.00 | 0.774045E+10 | 0.00 | 1.28 |
| July | 0.258544E+10 | 0.180182E+10 | 0.00 | 745041.97 | 0.459956E+09 | 4096271.36 | 0.269692E+09 | 0.00 | 0.93 |
| August | 0.455057E+10 | 0.137696E+10 | 0.00 | 2265915.01 | 0.183671E+09 | 8100951.19 | 0.600940E+09 | 0.00 | 1.02 |
| September | 0.446239E+10 | 0.331747E+09 | 0.00 | 17688547.94 | 81156916.98 | 3520415.55 | 0.817368E+10 | 0.00 | 1.07 |
| October | 0.567928E+10 | 0.00 | 0.00 | 20194683.26 | 70652.19 | 43569500.94 | 0.128471E+11 | 0.00 | 0.95 |
| November | 0.122985E+11 | 0.00 | 0.00 | 7739473.18 | 0.00 | 0.168795E+10 | 0.684590E+10 | 0.00 | 0.75 |
| December | 0.182667E+11 | 0.00 | 0.00 | 680676.36 | 0.00 | 0.608476E+10 | 0.163285E+10 | 0.00 | 0.66 |
| Annual Sum or Average | 0.124222E+12 | 0.426538E+10 | 0.00 | 91186945.33 | 0.777671E+09 | 0.291332E+11 | 0.582263E+11 | 0.00 | 0.88 |
| Minimum of Months | 0.258544E+10 | 0.00 | 0.00 | 5140.15 | 0.00 | 0.00 | 45278942.51 | 0.00 | 0.66 |
| Maximum of Months | 0.182667E+11 | 0.180182E+10 | 0.00 | 20194683.26 | 0.459956E+09 | 0.140547E+11 | 0.128471E+11 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.290607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448459E+10 | 0.00 | 0.00 | 0.25 |
| February | 0.783719E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249856E+10 | 0.00 | 0.00 | 0.24 |
| March | 0.189130E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128713E+10 | 0.00 | 0.00 | 0.25 |
| April | 0.203983E+10 | 0.00 | 0.00 | 6026.26 | 0.00 | 0.136497E+09 | 14396320.60 | 0.00 | 0.25 |
| May | 0.165197E+10 | 1156449.70 | 0.00 | 1030982.47 | 587815.47 | 0.224392E+09 | 0.415094E+09 | 0.00 | 0.32 |
| June | 0.557736E+09 | 0.158434E+09 | 0.00 | 2562229.17 | 6475127.21 | 0.00 | 0.110181E+10 | 0.00 | 0.49 |
| July | 0.353173E+09 | 0.323160E+09 | 0.00 | 149742.67 | 53680066.73 | 0.00 | 30801685.94 | 0.00 | 0.33 |
| August | 0.654638E+09 | 0.213038E+09 | 0.00 | 225004.72 | 43684883.10 | 525037.09 | 35264964.86 | 0.00 | 0.35 |
| September | 0.103598E+10 | 58960492.48 | 0.00 | 1766959.92 | 11183226.48 | 433844.04 | 0.623342E+09 | 0.00 | 0.36 |
| October | 0.181859E+10 | 0.00 | 0.00 | 672114.63 | 9448.03 | 54745496.69 | 0.388693E+09 | 0.00 | 0.28 |
| November | 0.168166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107842E+10 | 0.00 | 0.00 | 0.25 |
| December | 0.857899E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275370E+10 | 0.00 | 0.00 | 0.23 |
| Annual Sum or Average | 0.136171E+11 | 0.754749E+09 | 0.00 | 6413059.83 | 0.115621E+09 | 0.125190E+11 | 0.260940E+10 | 0.00 | 0.30 |
| Minimum of Months | 0.290607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
| Maximum of Months | 0.203983E+10 | 0.323160E+09 | 0.00 | 2562229.17 | 53680066.73 | 0.448459E+10 | 0.110181E+10 | 0.00 | 0.49 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.122138E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547317E+10 | 0.00 | 0.00 | 0.69 |
| February | 0.194507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300550E+10 | 0.00 | 0.00 | 0.70 |
| March | 0.319733E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.166116E+10 | 0.00 | 0.00 | 0.73 |
| April | 0.297391E+10 | 0.00 | 0.00 | 92630.20 | 0.00 | 0.249235E+09 | 0.172530E+09 | 0.00 | 0.74 |
| May | 0.239924E+10 | 1160054.70 | 0.00 | 1284008.91 | 912503.65 | 0.169120E+09 | 0.909684E+09 | 0.00 | 0.92 |
| June | 0.937209E+09 | 0.154166E+09 | 0.00 | 2341114.42 | 10051755.22 | 825402.60 | 0.130685E+10 | 0.00 | 1.21 |
| July | 0.572029E+09 | 0.344237E+09 | 0.00 | 31132.56 | 0.133839E+09 | 1326921.70 | 20342051.27 | 0.00 | 0.93 |
| August | 0.104610E+10 | 0.221071E+09 | 0.00 | 17581.82 | 96124968.21 | 10647047.45 | 14620756.95 | 0.00 | 1.01 |
| September | 0.156968E+10 | 53791369.92 | 0.00 | 1575114.87 | 22405128.20 | 8483898.26 | 0.805894E+09 | 0.00 | 0.95 |
| October | 0.237267E+10 | 0.00 | 0.00 | 1001337.48 | 14666.79 | 85950569.08 | 0.100838E+10 | 0.00 | 0.82 |
| November | 0.286320E+10 | 0.00 | 0.00 | 30914.56 | 0.00 | 0.124274E+10 | 0.118078E+09 | 0.00 | 0.73 |
| December | 0.192777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346837E+10 | 0.00 | 0.00 | 0.66 |
| Annual Sum or Average | 0.230256E+11 | 0.774425E+09 | 0.00 | 6373834.83 | 0.263348E+09 | 0.153765E+11 | 0.435638E+10 | 0.00 | 0.84 |
| Minimum of Months | 0.572029E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 825402.60 | 0.00 | 0.00 | 0.66 |
| Maximum of Months | 0.319733E+10 | 0.344237E+09 | 0.00 | 2341114.42 | 0.133839E+09 | 0.547317E+10 | 0.130685E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_2_POD_1_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.132456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189567E+11 | 0.00 | 0.00 | 0.69 |
| February | 0.152021E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862896E+10 | 0.00 | 0.00 | 0.70 |
| March | 0.199499E+11 | 0.00 | 0.00 | 4035.24 | 0.00 | 0.330389E+10 | 0.133160E+09 | 0.00 | 0.73 |
| April | 0.139658E+11 | 0.00 | 0.00 | 1157986.82 | 0.00 | 0.242353E+09 | 0.214275E+10 | 0.00 | 0.74 |
| May | 0.105807E+11 | 4825231.19 | 0.00 | 7664433.74 | 4395758.59 | 0.187827E+09 | 0.604731E+10 | 0.00 | 0.93 |
| June | 0.454442E+10 | 0.638392E+09 | 0.00 | 11100606.16 | 63214915.00 | 1043920.42 | 0.648106E+10 | 0.00 | 1.21 |
| July | 0.285370E+10 | 0.471455E+09 | 0.00 | 0.00 | 0.178605E+10 | 6257608.08 | 0.00 | 0.00 | 0.93 |
| August | 0.514370E+10 | 0.218919E+09 | 0.00 | 0.00 | 0.129600E+10 | 16298065.52 | 0.00 | 0.00 | 1.01 |
| September | 0.697774E+10 | 0.211313E+09 | 0.00 | 7282250.55 | 0.130520E+09 | 8545117.30 | 0.453518E+10 | 0.00 | 0.95 |
| October | 0.977494E+10 | 0.00 | 0.00 | 6748870.16 | 70653.59 | 94510210.95 | 0.683990E+10 | 0.00 | 0.82 |
| November | 0.156841E+11 | 0.00 | 0.00 | 514348.48 | 0.00 | 0.290873E+10 | 0.174556E+10 | 0.00 | 0.73 |
| December | 0.162887E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968854E+10 | 0.00 | 0.00 | 0.66 |
| Annual Sum or Average | 0.134211E+12 | 0.154490E+10 | 0.00 | 34472531.15 | 0.328025E+10 | 0.440436E+11 | 0.279249E+11 | 0.00 | 0.84 |
| Minimum of Months | 0.285370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1043920.42 | 0.00 | 0.00 | 0.66 |
| Maximum of Months | 0.199499E+11 | 0.638392E+09 | 0.00 | 11100606.16 | 0.178605E+10 | 0.189567E+11 | 0.683990E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.218847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450887E+10 | 0.00 | 0.00 | 0.69 |
| February | 0.268533E+10 | 0.00 | 0.00 | 246789.76 | 0.00 | 0.209828E+10 | 0.177585E+09 | 0.00 | 0.70 |
| March | 0.337967E+10 | 0.00 | 0.00 | 422311.85 | 0.00 | 0.105218E+10 | 0.435380E+09 | 0.00 | 0.74 |
| April | 0.250653E+10 | 0.00 | 0.00 | 886732.84 | 0.00 | 0.152517E+09 | 0.770911E+09 | 0.00 | 0.75 |
| May | 0.207949E+10 | 1381383.63 | 0.00 | 2202553.76 | 912480.36 | 0.148066E+09 | 0.135027E+10 | 0.00 | 0.97 |
| June | 0.871568E+09 | 0.179281E+09 | 0.00 | 2956372.69 | 10051498.66 | 851300.96 | 0.146668E+10 | 0.00 | 1.28 |
| July | 0.514929E+09 | 0.462445E+09 | 0.00 | 259709.91 | 64747473.68 | 892081.67 | 77769135.53 | 0.00 | 0.96 |
| August | 0.931394E+09 | 0.353690E+09 | 0.00 | 611532.10 | 23250386.55 | 8479631.52 | 0.132239E+09 | 0.00 | 1.06 |
| September | 0.112406E+10 | 81728318.92 | 0.00 | 3325119.22 | 15167435.87 | 2065179.39 | 0.146350E+10 | 0.00 | 1.08 |
| October | 0.156896E+10 | 0.00 | 0.00 | 3260900.93 | 14666.41 | 35001864.92 | 0.212983E+10 | 0.00 | 0.92 |
| November | 0.252800E+10 | 0.00 | 0.00 | 1003293.43 | 0.00 | 0.780676E+09 | 0.964045E+09 | 0.00 | 0.74 |
| December | 0.270512E+10 | 0.00 | 0.00 | 19380.02 | 0.00 | 0.263800E+10 | 54617843.14 | 0.00 | 0.66 |
| Annual Sum or Average | 0.230835E+11 | 0.107853E+10 | 0.00 | 15194696.49 | 0.114144E+09 | 0.114259E+11 | 0.902284E+10 | 0.00 | 0.88 |
| Minimum of Months | 0.514929E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 851300.96 | 0.00 | 0.00 | 0.66 |
| Maximum of Months | 0.337967E+10 | 0.462445E+09 | 0.00 | 3325119.22 | 64747473.68 | 0.450887E+10 | 0.212983E+10 | 0.00 | 1.28 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_1_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.176091E+11 | 0.00 | 0.00 | 379.37 | 0.00 | 0.145830E+11 | 8725327.68 | 0.00 | 0.69 |
| February | 0.174180E+11 | 0.00 | 0.00 | 1714685.50 | 0.00 | 0.497534E+10 | 0.150369E+10 | 0.00 | 0.70 |
| March | 0.180082E+11 | 0.00 | 0.00 | 4419211.87 | 0.00 | 0.177539E+10 | 0.370855E+10 | 0.00 | 0.74 |
| April | 0.110159E+11 | 0.00 | 0.00 | 6565120.13 | 0.00 | 0.100281E+09 | 0.552294E+10 | 0.00 | 0.76 |
| May | 0.887079E+10 | 5108723.20 | 0.00 | 12394320.72 | 4393325.52 | 0.145937E+09 | 0.842091E+10 | 0.00 | 0.97 |
| June | 0.397220E+10 | 0.733687E+09 | 0.00 | 14503785.85 | 48395020.53 | 0.00 | 0.752884E+10 | 0.00 | 1.27 |
| July | 0.262447E+10 | 0.168483E+10 | 0.00 | 555225.76 | 0.572710E+09 | 4085763.84 | 0.229327E+09 | 0.00 | 0.93 |
| August | 0.470144E+10 | 0.133143E+10 | 0.00 | 1825042.58 | 0.209041E+09 | 8657954.44 | 0.446413E+09 | 0.00 | 1.02 |
| September | 0.452648E+10 | 0.323114E+09 | 0.00 | 17113986.59 | 81601783.70 | 3487085.38 | 0.802025E+10 | 0.00 | 1.06 |
| October | 0.577068E+10 | 0.00 | 0.00 | 19396162.08 | 70614.49 | 43499073.92 | 0.125738E+11 | 0.00 | 0.94 |
| November | 0.126883E+11 | 0.00 | 0.00 | 6821666.46 | 0.00 | 0.165397E+10 | 0.637200E+10 | 0.00 | 0.75 |
| December | 0.184684E+11 | 0.00 | 0.00 | 318702.47 | 0.00 | 0.643511E+10 | 0.106647E+10 | 0.00 | 0.66 |
| Annual Sum or Average | 0.125674E+12 | 0.407816E+10 | 0.00 | 85628289.38 | 0.916212E+09 | 0.297288E+11 | 0.554019E+11 | 0.00 | 0.87 |
| Minimum of Months | 0.262447E+10 | 0.00 | 0.00 | 379.37 | 0.00 | 0.00 | 8725327.68 | 0.00 | 0.66 |
| Maximum of Months | 0.184684E+11 | 0.168483E+10 | 0.00 | 19396162.08 | 0.572710E+09 | 0.145830E+11 | 0.125738E+11 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.281054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448941E+10 | 0.00 | 0.00 | 0.25 |
| February | 0.765812E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250676E+10 | 0.00 | 0.00 | 0.24 |
| March | 0.187255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129580E+10 | 0.00 | 0.00 | 0.25 |
| April | 0.203687E+10 | 0.00 | 0.00 | 5134.48 | 0.00 | 0.136229E+09 | 10321618.32 | 0.00 | 0.24 |
| May | 0.165066E+10 | 1145510.98 | 0.00 | 1001593.85 | 585849.99 | 0.226662E+09 | 0.403982E+09 | 0.00 | 0.32 |
| June | 0.564182E+09 | 0.157010E+09 | 0.00 | 2505119.61 | 6453476.28 | 0.00 | 0.107978E+10 | 0.00 | 0.48 |
| July | 0.353541E+09 | 0.311156E+09 | 0.00 | 134585.08 | 57760534.70 | 0.00 | 28808645.22 | 0.00 | 0.33 |
| August | 0.656763E+09 | 0.208216E+09 | 0.00 | 190035.90 | 45331825.88 | 523281.52 | 30510536.38 | 0.00 | 0.35 |
| September | 0.103926E+10 | 57959995.47 | 0.00 | 1736677.49 | 11373149.73 | 446515.84 | 0.610483E+09 | 0.00 | 0.36 |
| October | 0.182489E+10 | 0.00 | 0.00 | 646915.48 | 9416.44 | 54700766.82 | 0.372615E+09 | 0.00 | 0.28 |
| November | 0.164408E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110898E+10 | 0.00 | 0.00 | 0.24 |
| December | 0.761231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284520E+10 | 0.00 | 0.00 | 0.23 |
| Annual Sum or Average | 0.134509E+11 | 0.735487E+09 | 0.00 | 6220061.90 | 0.121514E+09 | 0.126647E+11 | 0.253650E+10 | 0.00 | 0.30 |
| Minimum of Months | 0.281054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
| Maximum of Months | 0.203687E+10 | 0.311156E+09 | 0.00 | 2505119.61 | 57760534.70 | 0.448941E+10 | 0.107978E+10 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.121674E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546650E+10 | 0.00 | 0.00 | 0.69 |
| February | 0.193917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300295E+10 | 0.00 | 0.00 | 0.70 |
| March | 0.319283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165737E+10 | 0.00 | 0.00 | 0.73 |
| April | 0.296901E+10 | 0.00 | 0.00 | 93986.94 | 0.00 | 0.245940E+09 | 0.174910E+09 | 0.00 | 0.74 |
| May | 0.238951E+10 | 1162309.14 | 0.00 | 1292875.71 | 910934.45 | 0.168296E+09 | 0.915010E+09 | 0.00 | 0.92 |
| June | 0.928969E+09 | 0.154412E+09 | 0.00 | 2356237.67 | 10034469.61 | 824556.13 | 0.131333E+10 | 0.00 | 1.21 |
| July | 0.571045E+09 | 0.345306E+09 | 0.00 | 31980.48 | 0.132171E+09 | 1325311.68 | 20306168.39 | 0.00 | 0.93 |
| August | 0.104430E+10 | 0.222089E+09 | 0.00 | 17860.53 | 94676345.73 | 10632709.01 | 14595305.27 | 0.00 | 1.01 |
| September | 0.156301E+10 | 53799924.00 | 0.00 | 1579675.12 | 22366598.98 | 7924259.32 | 0.809743E+09 | 0.00 | 0.95 |
| October | 0.236370E+10 | 0.00 | 0.00 | 1003638.77 | 14641.57 | 86075588.35 | 0.101150E+10 | 0.00 | 0.81 |
| November | 0.285554E+10 | 0.00 | 0.00 | 30386.22 | 0.00 | 0.124339E+10 | 0.117875E+09 | 0.00 | 0.73 |
| December | 0.191839E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346856E+10 | 0.00 | 0.00 | 0.66 |
| Annual Sum or Average | 0.229522E+11 | 0.776770E+09 | 0.00 | 6406641.43 | 0.260174E+09 | 0.153598E+11 | 0.437726E+10 | 0.00 | 0.84 |
| Minimum of Months | 0.571045E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 824556.13 | 0.00 | 0.00 | 0.66 |
| Maximum of Months | 0.319283E+10 | 0.345306E+09 | 0.00 | 2356237.67 | 0.132171E+09 | 0.546650E+10 | 0.131333E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_2_POD_2_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.132218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189394E+11 | 0.00 | 0.00 | 0.69 |
| February | 0.151804E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.862036E+10 | 0.00 | 0.00 | 0.70 |
| March | 0.199248E+11 | 0.00 | 0.00 | 4157.80 | 0.00 | 0.329942E+10 | 0.132991E+09 | 0.00 | 0.73 |
| April | 0.139152E+11 | 0.00 | 0.00 | 1169852.54 | 0.00 | 0.244463E+09 | 0.217038E+10 | 0.00 | 0.74 |
| May | 0.105307E+11 | 4819478.33 | 0.00 | 7719827.97 | 4390164.10 | 0.186983E+09 | 0.608150E+10 | 0.00 | 0.93 |
| June | 0.451973E+10 | 0.638471E+09 | 0.00 | 11172191.19 | 62754189.10 | 1042591.82 | 0.650270E+10 | 0.00 | 1.21 |
| July | 0.285007E+10 | 0.490973E+09 | 0.00 | 0.00 | 0.176366E+10 | 6249644.01 | 0.00 | 0.00 | 0.93 |
| August | 0.513716E+10 | 0.224441E+09 | 0.00 | 0.00 | 0.128855E+10 | 16277322.93 | 0.00 | 0.00 | 1.01 |
| September | 0.696365E+10 | 0.211076E+09 | 0.00 | 7302993.26 | 0.130354E+09 | 8534241.91 | 0.453744E+10 | 0.00 | 0.94 |
| October | 0.976249E+10 | 0.00 | 0.00 | 6754537.59 | 70563.67 | 94389927.55 | 0.683211E+10 | 0.00 | 0.82 |
| November | 0.156439E+11 | 0.00 | 0.00 | 503290.58 | 0.00 | 0.294686E+10 | 0.172173E+10 | 0.00 | 0.73 |
| December | 0.162412E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.970304E+10 | 0.00 | 0.00 | 0.66 |
| Annual Sum or Average | 0.133891E+12 | 0.156978E+10 | 0.00 | 34626850.93 | 0.324977E+10 | 0.440671E+11 | 0.279788E+11 | 0.00 | 0.84 |
| Minimum of Months | 0.285007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1042591.82 | 0.00 | 0.00 | 0.66 |
| Maximum of Months | 0.199248E+11 | 0.638471E+09 | 0.00 | 11172191.19 | 0.176366E+10 | 0.189394E+11 | 0.683211E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.222671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445947E+10 | 0.00 | 0.00 | 0.69 |
| February | 0.267912E+10 | 0.00 | 0.00 | 252590.65 | 0.00 | 0.209037E+10 | 0.183991E+09 | 0.00 | 0.70 |
| March | 0.337713E+10 | 0.00 | 0.00 | 441217.16 | 0.00 | 0.104216E+10 | 0.440542E+09 | 0.00 | 0.74 |
| April | 0.250245E+10 | 0.00 | 0.00 | 923611.71 | 0.00 | 0.136086E+09 | 0.788641E+09 | 0.00 | 0.75 |
| May | 0.205205E+10 | 1392948.07 | 0.00 | 2266125.99 | 910946.75 | 0.143105E+09 | 0.138588E+10 | 0.00 | 0.97 |
| June | 0.858823E+09 | 0.180661E+09 | 0.00 | 3012830.88 | 10034605.10 | 693299.20 | 0.148454E+10 | 0.00 | 1.29 |
| July | 0.509809E+09 | 0.468065E+09 | 0.00 | 281892.12 | 63224785.17 | 872203.32 | 81967117.98 | 0.00 | 0.96 |
| August | 0.922071E+09 | 0.357740E+09 | 0.00 | 658200.76 | 21971451.09 | 7697313.54 | 0.140770E+09 | 0.00 | 1.06 |
| September | 0.110516E+10 | 82683236.31 | 0.00 | 3400597.11 | 14786662.52 | 2040874.64 | 0.148745E+10 | 0.00 | 1.08 |
| October | 0.153187E+10 | 0.00 | 0.00 | 3348548.26 | 14641.76 | 30724147.12 | 0.217905E+10 | 0.00 | 0.93 |
| November | 0.251312E+10 | 0.00 | 0.00 | 1057777.86 | 0.00 | 0.764222E+09 | 0.994959E+09 | 0.00 | 0.74 |
| December | 0.272073E+10 | 0.00 | 0.00 | 25482.33 | 0.00 | 0.258939E+10 | 78577623.94 | 0.00 | 0.66 |
| Annual Sum or Average | 0.229990E+11 | 0.109054E+10 | 0.00 | 15668874.84 | 0.110943E+09 | 0.112668E+11 | 0.924637E+10 | 0.00 | 0.88 |
| Minimum of Months | 0.509809E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 693299.20 | 0.00 | 0.00 | 0.66 |
| Maximum of Months | 0.337713E+10 | 0.468065E+09 | 0.00 | 3400597.11 | 63224785.17 | 0.445947E+10 | 0.217905E+10 | 0.00 | 1.29 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_1_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.178584E+11 | 0.00 | 0.00 | 2620.40 | 0.00 | 0.143015E+11 | 36219875.07 | 0.00 | 0.69 |
| February | 0.174043E+11 | 0.00 | 0.00 | 1775148.91 | 0.00 | 0.493132E+10 | 0.156291E+10 | 0.00 | 0.70 |
| March | 0.178553E+11 | 0.00 | 0.00 | 4627150.82 | 0.00 | 0.175483E+10 | 0.389455E+10 | 0.00 | 0.74 |
| April | 0.107555E+11 | 0.00 | 0.00 | 6960021.82 | 0.00 | 86884665.63 | 0.583218E+10 | 0.00 | 0.76 |
| May | 0.862482E+10 | 5174616.46 | 0.00 | 12916101.10 | 4392583.08 | 0.146012E+09 | 0.874378E+10 | 0.00 | 0.98 |
| June | 0.385379E+10 | 0.743155E+09 | 0.00 | 14989757.99 | 48386842.05 | 0.00 | 0.771234E+10 | 0.00 | 1.27 |
| July | 0.259581E+10 | 0.176364E+10 | 0.00 | 659183.18 | 0.494546E+09 | 3184504.34 | 0.258312E+09 | 0.00 | 0.93 |
| August | 0.459283E+10 | 0.136340E+10 | 0.00 | 2083923.12 | 0.186667E+09 | 6641203.52 | 0.556292E+09 | 0.00 | 1.02 |
| September | 0.435163E+10 | 0.327098E+09 | 0.00 | 17780518.52 | 81543781.02 | 3435890.85 | 0.827745E+10 | 0.00 | 1.07 |
| October | 0.557489E+10 | 0.00 | 0.00 | 20290930.66 | 70602.55 | 42926576.59 | 0.129304E+11 | 0.00 | 0.95 |
| November | 0.125227E+11 | 0.00 | 0.00 | 7371142.72 | 0.00 | 0.161251E+10 | 0.665346E+10 | 0.00 | 0.75 |
| December | 0.183891E+11 | 0.00 | 0.00 | 411418.72 | 0.00 | 0.632383E+10 | 0.125294E+10 | 0.00 | 0.66 |
| Annual Sum or Average | 0.124379E+12 | 0.420247E+10 | 0.00 | 89867917.96 | 0.815607E+09 | 0.292130E+11 | 0.577108E+11 | 0.00 | 0.88 |
| Minimum of Months | 0.259581E+10 | 0.00 | 0.00 | 2620.40 | 0.00 | 0.00 | 36219875.07 | 0.00 | 0.66 |
| Maximum of Months | 0.183891E+11 | 0.176364E+10 | 0.00 | 20290930.66 | 0.494546E+09 | 0.143015E+11 | 0.129304E+11 | 0.00 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDOR_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.293987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.450166E+10 | 0.00 | 0.00 | 0.25 |
| February | 0.812357E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248813E+10 | 0.00 | 0.00 | 0.24 |
| March | 0.197593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122111E+10 | 0.00 | 0.00 | 0.25 |
| April | 0.207326E+10 | 0.00 | 0.00 | 23274.05 | 0.00 | 0.103531E+09 | 27809154.14 | 0.00 | 0.25 |
| May | 0.162709E+10 | 1230992.44 | 0.00 | 1267578.01 | 591675.91 | 0.181936E+09 | 0.521526E+09 | 0.00 | 0.33 |
| June | 0.522014E+09 | 0.170105E+09 | 0.00 | 2873301.40 | 6517652.26 | 0.00 | 0.120302E+10 | 0.00 | 0.51 |
| July | 0.343256E+09 | 0.364027E+09 | 0.00 | 217418.43 | 42677347.04 | 0.00 | 45032820.90 | 0.00 | 0.34 |
| August | 0.646289E+09 | 0.245659E+09 | 0.00 | 342399.59 | 29677594.26 | 343251.26 | 50215152.31 | 0.00 | 0.36 |
| September | 0.966016E+09 | 62916327.50 | 0.00 | 2034430.37 | 11104082.41 | 115150.15 | 0.736224E+09 | 0.00 | 0.38 |
| October | 0.174088E+10 | 0.00 | 0.00 | 833439.82 | 9510.08 | 48643974.78 | 0.500812E+09 | 0.00 | 0.28 |
| November | 0.172427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105253E+10 | 0.00 | 0.00 | 0.25 |
| December | 0.862988E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276898E+10 | 0.00 | 0.00 | 0.23 |
| Annual Sum or Average | 0.135883E+11 | 0.843939E+09 | 0.00 | 7591841.68 | 90577861.97 | 0.123670E+11 | 0.308463E+10 | 0.00 | 0.31 |
| Minimum of Months | 0.293987E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.23 |
| Maximum of Months | 0.207326E+10 | 0.364027E+09 | 0.00 | 2873301.40 | 42677347.04 | 0.450166E+10 | 0.120302E+10 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: CORNER_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.124223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.544856E+10 | 0.00 | 0.00 | 0.69 |
| February | 0.197226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.297533E+10 | 0.00 | 0.00 | 0.70 |
| March | 0.322976E+10 | 0.00 | 0.00 | 129.07 | 0.00 | 0.162152E+10 | 4285862.11 | 0.00 | 0.73 |
| April | 0.296352E+10 | 0.00 | 0.00 | 114134.11 | 0.00 | 0.231756E+09 | 0.198268E+09 | 0.00 | 0.74 |
| May | 0.234179E+10 | 1201363.96 | 0.00 | 1437035.85 | 911913.81 | 0.156291E+09 | 0.987119E+09 | 0.00 | 0.93 |
| June | 0.885615E+09 | 0.158977E+09 | 0.00 | 2562204.02 | 10045257.82 | 827179.27 | 0.137909E+10 | 0.00 | 1.23 |
| July | 0.563007E+09 | 0.368877E+09 | 0.00 | 53202.56 | 0.112894E+09 | 1022209.61 | 29265505.90 | 0.00 | 0.94 |
| August | 0.104011E+10 | 0.236435E+09 | 0.00 | 38353.75 | 82216642.92 | 8855835.45 | 21681286.28 | 0.00 | 1.02 |
| September | 0.152155E+10 | 57087842.58 | 0.00 | 1670188.81 | 20300757.79 | 7032154.15 | 0.860403E+09 | 0.00 | 0.95 |
| October | 0.231619E+10 | 0.00 | 0.00 | 1074223.32 | 14657.31 | 79750258.00 | 0.107179E+10 | 0.00 | 0.82 |
| November | 0.285624E+10 | 0.00 | 0.00 | 35686.91 | 0.00 | 0.123846E+10 | 0.126709E+09 | 0.00 | 0.73 |
| December | 0.192728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346563E+10 | 0.00 | 0.00 | 0.66 |
| Annual Sum or Average | 0.228595E+11 | 0.822580E+09 | 0.00 | 6985158.38 | 0.226383E+09 | 0.152350E+11 | 0.467862E+10 | 0.00 | 0.84 |
| Minimum of Months | 0.563007E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 827179.27 | 0.00 | 0.00 | 0.66 |
| Maximum of Months | 0.322976E+10 | 0.368877E+09 | 0.00 | 2562204.02 | 0.112894E+09 | 0.544856E+10 | 0.137909E+10 | 0.00 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: MULT_CLASS_2_POD_3_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.863481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125953E+11 | 0.00 | 0.00 | 0.69 |
| February | 0.996365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.574756E+10 | 0.00 | 0.00 | 0.70 |
| March | 0.131193E+11 | 0.00 | 0.00 | 10979.10 | 0.00 | 0.216955E+10 | 0.129574E+09 | 0.00 | 0.73 |
| April | 0.888774E+10 | 0.00 | 0.00 | 956629.36 | 0.00 | 0.156963E+09 | 0.173537E+10 | 0.00 | 0.74 |
| May | 0.672320E+10 | 3185917.94 | 0.00 | 5783936.34 | 2898008.37 | 0.115356E+09 | 0.431393E+10 | 0.00 | 0.93 |
| June | 0.262961E+10 | 0.436234E+09 | 0.00 | 8418877.84 | 36408758.82 | 688229.36 | 0.475773E+10 | 0.00 | 1.22 |
| July | 0.186119E+10 | 0.660122E+09 | 0.00 | 10467.63 | 0.828190E+09 | 3119323.90 | 21179049.90 | 0.00 | 0.93 |
| August | 0.339228E+10 | 0.380609E+09 | 0.00 | 0.00 | 0.618137E+09 | 9572690.78 | 0.00 | 0.00 | 1.01 |
| September | 0.438631E+10 | 0.141397E+09 | 0.00 | 5358148.15 | 86048165.92 | 4690368.40 | 0.323721E+10 | 0.00 | 0.95 |
| October | 0.624448E+10 | 0.00 | 0.00 | 4867659.91 | 46580.06 | 62654999.94 | 0.473289E+10 | 0.00 | 0.82 |
| November | 0.101027E+11 | 0.00 | 0.00 | 413101.88 | 0.00 | 0.194945E+10 | 0.135637E+10 | 0.00 | 0.73 |
| December | 0.106165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.650966E+10 | 0.00 | 0.00 | 0.66 |
| Annual Sum or Average | 0.865617E+11 | 0.162155E+10 | 0.00 | 25819800.20 | 0.157173E+10 | 0.293245E+11 | 0.202843E+11 | 0.00 | 0.84 |
| Minimum of Months | 0.186119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 688229.36 | 0.00 | 0.00 | 0.66 |
| Maximum of Months | 0.131193E+11 | 0.660122E+09 | 0.00 | 8418877.84 | 0.828190E+09 | 0.125953E+11 | 0.475773E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: COMPUTER_CLASS_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.745897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347067E+10 | 0.00 | 0.00 | 0.69 |
| February | 0.727388E+10 | 0.00 | 0.00 | 7882.59 | 0.00 | 0.763580E+09 | 49998924.22 | 0.00 | 0.70 |
| March | 0.687053E+10 | 0.00 | 0.00 | 209440.91 | 0.00 | 0.440848E+09 | 0.625189E+09 | 0.00 | 0.73 |
| April | 0.278396E+10 | 0.00 | 0.00 | 2688093.63 | 0.00 | 26037303.87 | 0.277751E+10 | 0.00 | 0.75 |
| May | 0.173233E+10 | 2471268.14 | 0.00 | 7105086.29 | 1491593.14 | 39377708.52 | 0.431614E+10 | 0.00 | 1.02 |
| June | 0.748974E+09 | 0.361588E+09 | 0.00 | 9315398.39 | 16430760.71 | 0.00 | 0.369467E+10 | 0.00 | 1.52 |
| July | 0.680987E+09 | 0.714723E+09 | 0.00 | 821103.56 | 70193872.65 | 231396.03 | 0.289308E+09 | 0.00 | 0.94 |
| August | 0.133343E+10 | 0.477737E+09 | 0.00 | 998708.93 | 42627933.32 | 950904.13 | 0.415558E+09 | 0.00 | 1.02 |
| September | 0.583792E+09 | 0.131301E+09 | 0.00 | 8822836.51 | 28687914.75 | 938516.47 | 0.382472E+10 | 0.00 | 1.13 |
| October | 0.119190E+10 | 0.00 | 0.00 | 7099496.98 | 23974.57 | 17820545.21 | 0.477427E+10 | 0.00 | 0.88 |
| November | 0.474684E+10 | 0.00 | 0.00 | 1605995.38 | 0.00 | 0.280072E+09 | 0.187872E+10 | 0.00 | 0.73 |
| December | 0.731806E+10 | 0.00 | 0.00 | 3218.84 | 0.00 | 0.143680E+10 | 60929918.78 | 0.00 | 0.66 |
| Annual Sum or Average | 0.427236E+11 | 0.168782E+10 | 0.00 | 38677262.03 | 0.159456E+09 | 0.647732E+10 | 0.227070E+11 | 0.00 | 0.90 |
| Minimum of Months | 0.583792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 |
| Maximum of Months | 0.745897E+10 | 0.714723E+09 | 0.00 | 9315398.39 | 70193872.65 | 0.347067E+10 | 0.477427E+10 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: MAIN_CORRIDOR_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.490961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105364E+11 | 0.00 | 0.00 | 0.20 |
| February | 0.120713E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.598845E+10 | 0.00 | 0.00 | 0.18 |
| March | 0.387080E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301736E+10 | 0.00 | 0.00 | 0.19 |
| April | 0.461105E+10 | 0.00 | 0.00 | 85009.65 | 0.00 | 58295181.03 | 75775274.93 | 0.00 | 0.19 |
| May | 0.322504E+10 | 3100491.35 | 0.00 | 4450982.24 | 1273644.03 | 0.150589E+09 | 0.197139E+10 | 0.00 | 0.28 |
| June | 0.842208E+09 | 0.467142E+09 | 0.00 | 10428588.44 | 14029925.31 | 0.00 | 0.387303E+10 | 0.00 | 0.50 |
| July | 0.483011E+09 | 0.125313E+10 | 0.00 | 2655672.70 | 50777018.14 | 0.00 | 0.462942E+09 | 0.00 | 0.34 |
| August | 0.100590E+10 | 0.770711E+09 | 0.00 | 2976532.94 | 25312842.22 | 0.00 | 0.594342E+09 | 0.00 | 0.33 |
| September | 0.183122E+10 | 0.157718E+09 | 0.00 | 5655672.96 | 23883394.77 | 0.00 | 0.197784E+10 | 0.00 | 0.31 |
| October | 0.421039E+10 | 0.00 | 0.00 | 843476.27 | 20471.44 | 0.121509E+09 | 0.527262E+09 | 0.00 | 0.21 |
| November | 0.314971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285944E+10 | 0.00 | 0.00 | 0.19 |
| December | 0.105146E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719042E+10 | 0.00 | 0.00 | 0.18 |
| Annual Sum or Average | 0.259789E+11 | 0.265180E+10 | 0.00 | 27095935.20 | 0.115297E+09 | 0.299224E+11 | 0.948257E+10 | 0.00 | 0.26 |
| Minimum of Months | 0.483011E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 |
| Maximum of Months | 0.461105E+10 | 0.125313E+10 | 0.00 | 10428588.44 | 50777018.14 | 0.105364E+11 | 0.387303E+10 | 0.00 | 0.50 |
Report: MechanicalVentilationLoadsMonthly
For: LOBBY_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 77557897.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.839951E+10 | 0.00 | 0.00 | 0.49 |
| February | 0.175017E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.578308E+10 | 0.00 | 0.00 | 0.46 |
| March | 0.317747E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512232E+10 | 0.00 | 0.00 | 0.46 |
| April | 0.672452E+09 | 0.00 | 0.00 | 3909.42 | 0.00 | 0.280752E+10 | 3801096.10 | 0.00 | 0.41 |
| May | 0.105508E+10 | 1482619.49 | 0.00 | 570989.59 | 744566.48 | 0.226289E+10 | 73603966.17 | 0.00 | 0.49 |
| June | 0.121336E+10 | 0.293470E+09 | 0.00 | 1116638.59 | 8201830.22 | 0.488018E+09 | 0.224972E+09 | 0.00 | 0.70 |
| July | 0.366233E+09 | 0.898554E+09 | 0.00 | 365727.48 | 36285718.75 | 0.120393E+09 | 32507961.60 | 0.00 | 0.65 |
| August | 0.557050E+09 | 0.635957E+09 | 0.00 | 674437.02 | 14791190.69 | 0.336518E+09 | 62751645.68 | 0.00 | 0.66 |
| September | 0.957641E+09 | 0.104466E+09 | 0.00 | 1561392.12 | 10935500.77 | 0.932345E+09 | 0.267189E+09 | 0.00 | 0.53 |
| October | 0.124489E+10 | 0.00 | 0.00 | 407147.33 | 11967.51 | 0.190605E+10 | 0.144696E+09 | 0.00 | 0.44 |
| November | 0.485358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407671E+10 | 0.00 | 0.00 | 0.43 |
| December | 98618260.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.637189E+10 | 0.00 | 0.00 | 0.44 |
| Annual Sum or Average | 0.722100E+10 | 0.193393E+10 | 0.00 | 4700241.54 | 70970774.42 | 0.386072E+11 | 0.809522E+09 | 0.00 | 0.51 |
| Minimum of Months | 77557897.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120393E+09 | 0.00 | 0.00 | 0.41 |
| Maximum of Months | 0.124489E+10 | 0.898554E+09 | 0.00 | 1561392.12 | 36285718.75 | 0.839951E+10 | 0.267189E+09 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: MECH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.634356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140747E+09 | 0.00 | 0.00 | 0.26 |
| February | 0.479232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5486617.23 | 0.00 | 0.00 | 0.27 |
| March | 0.470840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
| April | 0.326554E+10 | 0.00 | 0.00 | 7911.89 | 0.00 | 0.00 | 26537247.58 | 0.00 | 0.28 |
| May | 0.259046E+10 | 1174053.98 | 0.00 | 1964973.31 | 833423.50 | 0.00 | 0.789464E+09 | 0.00 | 0.36 |
| June | 0.646082E+09 | 0.182936E+09 | 0.00 | 5792478.61 | 9008971.93 | 0.00 | 0.162987E+10 | 0.00 | 0.51 |
| July | 0.536234E+09 | 0.306707E+09 | 0.00 | 1151059.26 | 0.149712E+09 | 0.00 | 51613047.31 | 0.00 | 0.36 |
| August | 0.101031E+10 | 0.152270E+09 | 0.00 | 451599.98 | 0.153091E+09 | 0.00 | 37139150.70 | 0.00 | 0.39 |
| September | 0.149471E+10 | 53337943.87 | 0.00 | 2628159.03 | 25093555.01 | 0.00 | 0.814197E+09 | 0.00 | 0.37 |
| October | 0.322407E+10 | 0.00 | 0.00 | 100129.95 | 14224.38 | 0.00 | 0.126994E+09 | 0.00 | 0.31 |
| November | 0.409474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
| December | 0.518873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41167064.91 | 0.00 | 0.00 | 0.25 |
| Annual Sum or Average | 0.378952E+11 | 0.696426E+09 | 0.00 | 12096312.03 | 0.337753E+09 | 0.187400E+09 | 0.347581E+10 | 0.00 | 0.33 |
| Minimum of Months | 0.536234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
| Maximum of Months | 0.634356E+10 | 0.306707E+09 | 0.00 | 5792478.61 | 0.153091E+09 | 0.140747E+09 | 0.162987E+10 | 0.00 | 0.51 |
Report: MechanicalVentilationLoadsMonthly
For: BATH_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.341379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.938237E+09 | 0.00 | 0.00 | 0.23 |
| February | 0.303830E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175859E+09 | 0.00 | 0.00 | 0.23 |
| March | 0.307344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 78342365.45 | 0.00 | 0.00 | 0.25 |
| April | 0.220275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
| May | 0.223290E+10 | 104926.22 | 0.00 | 14562.09 | 1136148.87 | 0.00 | 4367875.17 | 0.00 | 0.31 |
| June | 0.137366E+10 | 75717101.83 | 0.00 | 109805.75 | 20660717.95 | 0.00 | 26593412.46 | 0.00 | 0.39 |
| July | 0.384799E+09 | 84632357.22 | 0.00 | 58965.81 | 0.221294E+09 | 0.00 | 462352.77 | 0.00 | 0.32 |
| August | 0.695083E+09 | 30446556.35 | 0.00 | 1567.92 | 0.173673E+09 | 0.00 | 8626.13 | 0.00 | 0.35 |
| September | 0.151644E+10 | 13674425.40 | 0.00 | 10606.32 | 32333092.79 | 0.00 | 3366131.59 | 0.00 | 0.31 |
| October | 0.224228E+10 | 0.00 | 0.00 | 0.00 | 9517.60 | 0.00 | 0.00 | 0.00 | 0.27 |
| November | 0.271012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29786548.94 | 0.00 | 0.00 | 0.25 |
| December | 0.311073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394582E+09 | 0.00 | 0.00 | 0.22 |
| Annual Sum or Average | 0.259943E+11 | 0.204575E+09 | 0.00 | 195507.88 | 0.449106E+09 | 0.161681E+10 | 34798398.12 | 0.00 | 0.28 |
| Minimum of Months | 0.384799E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.22 |
| Maximum of Months | 0.341379E+10 | 84632357.22 | 0.00 | 109805.75 | 0.221294E+09 | 0.938237E+09 | 26593412.46 | 0.00 | 0.39 |
Report: MechanicalVentilationLoadsMonthly
For: OFFICES_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.133971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106642E+11 | 0.00 | 0.00 | 0.27 |
| February | 0.294572E+10 | 0.00 | 0.00 | 138925.17 | 0.00 | 0.543953E+10 | 96005554.17 | 0.00 | 0.27 |
| March | 0.594696E+10 | 0.00 | 0.00 | 471660.56 | 0.00 | 0.199386E+10 | 0.317643E+09 | 0.00 | 0.28 |
| April | 0.435997E+10 | 0.00 | 0.00 | 3217977.10 | 0.00 | 40763407.70 | 0.174292E+10 | 0.00 | 0.32 |
| May | 0.323493E+10 | 3999138.71 | 0.00 | 8272810.56 | 1776072.27 | 0.170691E+09 | 0.380632E+10 | 0.00 | 0.47 |
| June | 0.104566E+10 | 0.644176E+09 | 0.00 | 15133931.77 | 19807177.10 | 0.00 | 0.523624E+10 | 0.00 | 0.86 |
| July | 0.569068E+09 | 0.172335E+10 | 0.00 | 5045584.43 | 59863361.91 | 0.00 | 0.812916E+09 | 0.00 | 0.62 |
| August | 0.978639E+09 | 0.118867E+10 | 0.00 | 7382465.57 | 24910055.93 | 0.00 | 0.142978E+10 | 0.00 | 0.65 |
| September | 0.110399E+10 | 0.265087E+09 | 0.00 | 14339926.87 | 17484184.75 | 0.00 | 0.513476E+10 | 0.00 | 0.64 |
| October | 0.290820E+10 | 0.00 | 0.00 | 8110299.70 | 28997.86 | 32766763.27 | 0.426801E+10 | 0.00 | 0.41 |
| November | 0.437381E+10 | 0.00 | 0.00 | 1358905.81 | 0.00 | 0.206537E+10 | 0.869708E+09 | 0.00 | 0.29 |
| December | 0.305853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.626455E+10 | 0.00 | 0.00 | 0.25 |
| Annual Sum or Average | 0.318652E+11 | 0.382528E+10 | 0.00 | 63472487.54 | 0.123870E+09 | 0.266717E+11 | 0.237143E+11 | 0.00 | 0.44 |
| Minimum of Months | 0.569068E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.25 |
| Maximum of Months | 0.594696E+10 | 0.172335E+10 | 0.00 | 15133931.77 | 59863361.91 | 0.106642E+11 | 0.523624E+10 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: GYM_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.119526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.763850E+10 | 0.00 | 0.00 | 0.56 |
| February | 0.121649E+11 | 0.00 | 0.00 | 74904.83 | 0.00 | 0.211969E+10 | 0.193198E+09 | 0.00 | 0.57 |
| March | 0.109510E+11 | 0.00 | 0.00 | 1555406.40 | 0.00 | 0.771368E+09 | 0.248503E+10 | 0.00 | 0.60 |
| April | 0.437139E+10 | 0.00 | 0.00 | 9282432.11 | 0.00 | 20343980.04 | 0.609037E+10 | 0.00 | 0.66 |
| May | 0.318423E+10 | 6360917.84 | 0.00 | 16969572.71 | 2626532.48 | 40100946.40 | 0.863508E+10 | 0.00 | 0.94 |
| June | 0.114167E+10 | 0.798970E+09 | 0.00 | 21383363.52 | 28197604.20 | 0.00 | 0.771875E+10 | 0.00 | 1.43 |
| July | 0.630624E+09 | 0.190556E+10 | 0.00 | 8270785.05 | 97963539.91 | 0.00 | 0.135135E+10 | 0.00 | 0.98 |
| August | 0.127745E+10 | 0.124862E+10 | 0.00 | 10106941.64 | 48566926.82 | 0.00 | 0.212825E+10 | 0.00 | 1.00 |
| September | 0.125186E+10 | 0.262779E+09 | 0.00 | 16405086.44 | 49531368.41 | 0.00 | 0.696202E+10 | 0.00 | 0.97 |
| October | 0.381710E+10 | 0.00 | 0.00 | 9525661.63 | 42883.29 | 40150018.29 | 0.669338E+10 | 0.00 | 0.71 |
| November | 0.996419E+10 | 0.00 | 0.00 | 1008080.57 | 0.00 | 0.917568E+09 | 0.146942E+10 | 0.00 | 0.59 |
| December | 0.117123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407194E+10 | 0.00 | 0.00 | 0.54 |
| Annual Sum or Average | 0.724193E+11 | 0.422229E+10 | 0.00 | 94582234.88 | 0.226929E+09 | 0.156196E+11 | 0.437269E+11 | 0.00 | 0.80 |
| Minimum of Months | 0.630624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.54 |
| Maximum of Months | 0.121649E+11 | 0.190556E+10 | 0.00 | 21383363.52 | 97963539.91 | 0.763850E+10 | 0.863508E+10 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.246061E+10 | 0.00 | 0.00 | 17337639.40 | 0.00 | 0.419216E+09 | 0.144332E+11 | 0.00 | 0.73 |
| February | 0.753307E+09 | 0.00 | 0.00 | 22320284.75 | 0.00 | 0.00 | 0.163121E+11 | 0.00 | 1.04 |
| March | 0.141315E+09 | 0.00 | 0.00 | 34594959.79 | 0.00 | 0.00 | 0.226585E+11 | 0.00 | 1.44 |
| April | 778090.58 | 0.00 | 0.00 | 37541506.81 | 0.00 | 511559.03 | 0.221157E+11 | 0.00 | 2.20 |
| May | 0.00 | 2741557.53 | 0.00 | 46872533.75 | 0.00 | 0.00 | 0.244179E+11 | 0.00 | 2.92 |
| June | 105944.46 | 39349476.73 | 0.00 | 49125807.65 | 0.00 | 6961.80 | 0.183553E+11 | 0.00 | 3.43 |
| July | 390108.97 | 0.411055E+09 | 0.00 | 43743672.45 | 0.00 | 132615.46 | 0.111793E+11 | 0.00 | 2.97 |
| August | 0.00 | 0.516348E+09 | 0.00 | 43801765.58 | 0.00 | 190041.61 | 0.146263E+11 | 0.00 | 3.34 |
| September | 277757.96 | 0.534174E+09 | 0.00 | 43797323.43 | 0.00 | 0.00 | 0.193658E+11 | 0.00 | 3.36 |
| October | 0.00 | 0.00 | 0.00 | 40011803.84 | 0.00 | 2603975.77 | 0.233571E+11 | 0.00 | 2.53 |
| November | 0.264786E+09 | 0.00 | 0.00 | 31293399.07 | 0.00 | 0.133260E+09 | 0.207990E+11 | 0.00 | 1.61 |
| December | 0.193089E+10 | 0.00 | 0.00 | 21192331.04 | 0.00 | 0.00 | 0.161323E+11 | 0.00 | 0.93 |
| Annual Sum or Average | 0.555246E+10 | 0.150367E+10 | 0.00 | 0.431633E+09 | 0.00 | 0.555920E+09 | 0.223753E+12 | 0.00 | 2.21 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 17337639.40 | 0.00 | 0.00 | 0.111793E+11 | 0.00 | 0.73 |
| Maximum of Months | 0.246061E+10 | 0.534174E+09 | 0.00 | 49125807.65 | 0.00 | 0.419216E+09 | 0.244179E+11 | 0.00 | 3.43 |
Report: MechanicalVentilationLoadsMonthly
For: CAFETERIA_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.320509E+11 | 0.00 | 0.00 | 1044579.39 | 0.00 | 0.399351E+11 | 0.958297E+10 | 0.00 | 1.86 |
| February | 0.212641E+11 | 0.00 | 0.00 | 3124471.65 | 0.00 | 0.150909E+11 | 0.126356E+11 | 0.00 | 1.72 |
| March | 0.183519E+11 | 0.00 | 0.00 | 6468714.21 | 0.00 | 0.944636E+10 | 0.175932E+11 | 0.00 | 1.83 |
| April | 0.107503E+11 | 0.00 | 0.00 | 12562369.71 | 0.00 | 0.259344E+09 | 0.184231E+11 | 0.00 | 1.83 |
| May | 0.800425E+10 | 1925174.47 | 0.00 | 19623377.01 | 0.00 | 0.377725E+09 | 0.217713E+11 | 0.00 | 2.18 |
| June | 0.180304E+10 | 0.471606E+09 | 0.00 | 32777327.34 | 0.00 | 0.00 | 0.182838E+11 | 0.00 | 2.63 |
| July | 0.637464E+09 | 0.321485E+10 | 0.00 | 11506804.04 | 4204.59 | 14200.91 | 0.427832E+10 | 0.00 | 2.16 |
| August | 0.250873E+10 | 0.250572E+10 | 0.00 | 9348414.90 | 0.00 | 1450092.76 | 0.586874E+10 | 0.00 | 2.40 |
| September | 0.410313E+10 | 0.665974E+09 | 0.00 | 24035761.29 | 0.00 | 6477498.57 | 0.187545E+11 | 0.00 | 2.35 |
| October | 0.880729E+10 | 0.00 | 0.00 | 17113827.24 | 0.00 | 0.249028E+09 | 0.204841E+11 | 0.00 | 1.98 |
| November | 0.155967E+11 | 0.00 | 0.00 | 8203798.27 | 0.00 | 0.321106E+10 | 0.166160E+11 | 0.00 | 1.71 |
| December | 0.250639E+11 | 0.00 | 0.00 | 3024425.61 | 0.00 | 0.171664E+11 | 0.118659E+11 | 0.00 | 1.65 |
| Annual Sum or Average | 0.148942E+12 | 0.686007E+10 | 0.00 | 0.148834E+09 | 4204.59 | 0.857438E+11 | 0.176158E+12 | 0.00 | 2.03 |
| Minimum of Months | 0.637464E+09 | 0.00 | 0.00 | 1044579.39 | 0.00 | 0.00 | 0.427832E+10 | 0.00 | 1.65 |
| Maximum of Months | 0.320509E+11 | 0.321485E+10 | 0.00 | 32777327.34 | 4204.59 | 0.399351E+11 | 0.217713E+11 | 0.00 | 2.63 |
Report: MechanicalVentilationLoadsMonthly
For: LIBRARY_MEDIA_CENTER_ZN_1_FLR_1
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.384159E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103019E+11 | 0.00 | 0.00 | 0.36 |
| February | 0.583621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456730E+10 | 0.00 | 0.00 | 0.36 |
| March | 0.837740E+10 | 0.00 | 0.00 | 210378.64 | 0.00 | 0.145866E+10 | 0.370855E+09 | 0.00 | 0.38 |
| April | 0.423798E+10 | 0.00 | 0.00 | 5412078.30 | 0.00 | 23221061.03 | 0.340570E+10 | 0.00 | 0.43 |
| May | 0.253299E+10 | 4223131.66 | 0.00 | 13493581.82 | 1912724.29 | 41350456.34 | 0.681608E+10 | 0.00 | 0.66 |
| June | 0.896674E+09 | 0.672554E+09 | 0.00 | 19039160.81 | 21017616.80 | 0.00 | 0.696905E+10 | 0.00 | 1.10 |
| July | 0.610194E+09 | 0.162264E+10 | 0.00 | 4638147.05 | 73341381.55 | 0.00 | 0.822394E+09 | 0.00 | 0.68 |
| August | 0.111276E+10 | 0.106243E+10 | 0.00 | 6213663.81 | 34084184.73 | 0.00 | 0.136255E+10 | 0.00 | 0.69 |
| September | 0.908609E+09 | 0.231453E+09 | 0.00 | 16118919.00 | 34356764.48 | 0.00 | 0.617475E+10 | 0.00 | 0.75 |
| October | 0.224095E+10 | 0.00 | 0.00 | 11354066.32 | 30743.46 | 15807711.67 | 0.654693E+10 | 0.00 | 0.54 |
| November | 0.566086E+10 | 0.00 | 0.00 | 2220140.90 | 0.00 | 0.155735E+10 | 0.176280E+10 | 0.00 | 0.39 |
| December | 0.550869E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.583336E+10 | 0.00 | 0.00 | 0.34 |
| Annual Sum or Average | 0.417649E+11 | 0.359330E+10 | 0.00 | 78700136.66 | 0.164743E+09 | 0.237990E+11 | 0.342311E+11 | 0.00 | 0.56 |
| Minimum of Months | 0.610194E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.34 |
| Maximum of Months | 0.837740E+10 | 0.162264E+10 | 0.00 | 19039160.81 | 73341381.55 | 0.103019E+11 | 0.696905E+10 | 0.00 | 1.10 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:30:47
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.254467E+12 | 0.374685E+11 | 0.209295E+12 | 0.339957E+12 | 0.158113E+12 |
| February | 0.458009E+12 | 0.286076E+11 | 0.149390E+12 | 0.311436E+12 | 0.905921E+11 |
| March | 0.915897E+12 | 0.279222E+11 | 0.159242E+12 | 0.348208E+12 | 0.697951E+11 |
| April | 0.103821E+13 | 0.196788E+11 | 0.135952E+12 | 0.384488E+12 | 0.492449E+11 |
| May | 0.144037E+13 | 0.186859E+11 | 0.126631E+12 | 0.447718E+12 | 0.934056E+11 |
| June | 0.159501E+13 | 0.878034E+10 | 0.756436E+11 | 0.370855E+12 | 0.245732E+12 |
| July | 0.159662E+13 | 0.309082E+10 | 0.449029E+11 | 0.257217E+12 | 0.321382E+12 |
| August | 0.130026E+13 | 0.505574E+10 | 0.596612E+11 | 0.318232E+12 | 0.261247E+12 |
| September | 0.936179E+12 | 0.132467E+11 | 0.100255E+12 | 0.464900E+12 | 0.161661E+12 |
| October | 0.536916E+12 | 0.198327E+11 | 0.158933E+12 | 0.555898E+12 | 0.601121E+11 |
| November | 0.208679E+12 | 0.262182E+11 | 0.170539E+12 | 0.398215E+12 | 0.549879E+11 |
| December | 0.998579E+11 | 0.322016E+11 | 0.206528E+12 | 0.292981E+12 | 0.105147E+12 |
| Annual Sum or Average | 0.103805E+14 | 0.240789E+12 | 0.159697E+13 | 0.449011E+13 | 0.167142E+13 |
| Minimum of Months | 0.998579E+11 | 0.309082E+10 | 0.449029E+11 | 0.257217E+12 | 0.492449E+11 |
| Maximum of Months | 0.159662E+13 | 0.374685E+11 | 0.209295E+12 | 0.555898E+12 | 0.321382E+12 |