Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21
Tabular Output Report in Format: HTML
Building: HotelSmall
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2024-07-03 12:21:21
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 3268.19 | 814.28 | 877.35 |
| Net Site Energy | 3268.19 | 814.28 | 877.35 |
| Total Source Energy | 6789.66 | 1691.67 | 1822.68 |
| Net Source Energy | 6789.66 | 1691.67 | 1822.68 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 4013.58 |
| Net Conditioned Building Area | 3725.09 |
| Unconditioned Building Area | 288.49 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 467.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 248.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 512.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 107.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 452.79 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 235.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 1.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 820.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.17 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 1558.78 | 1709.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.17 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 0.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Boiler | 0.00 | 466.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Cooling | General | 248.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 512.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 107.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | ElevatorLift | 134.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLightsFan | 10.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MiscPlug | 279.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Laundry | 28.48 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 235.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 1.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.17 | |
| Water Heater | 0.00 | 820.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 467.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 248.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 512.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 107.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 452.79 | 421.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 235.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 1.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 0.00 | 820.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2578.17 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 166.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 130.46 | 345.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
| Other | 121.55 | 113.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 418.45 | 458.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 154.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 121.09 | 320.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
| Other | 112.82 | 105.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 388.38 | 425.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.64 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 1558.779 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 1558.779 | 100.00 |
| Total On-Site and Utility Electric Sources | 1558.779 | 100.00 |
| Total Electricity End Uses | 1558.779 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | |
| Air to Air Heat Recovery for Cooling | 0.00 | |
| Air to Air Heat Recovery for Heating | 0.00 | |
| High-Temperature Geothermal* | 0.00 | |
| Solar Water Thermal | 0.00 | |
| Solar Air Thermal | 0.00 | |
| Total On-Site Thermal Sources | 0.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 2578.17 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 2578.17 | 100.00 |
| Total Water End Uses | 2578.17 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.33 |
| Time Setpoint Not Met During Occupied Cooling | 239.67 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 6673.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELSMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |ZoneHeatingSummaryMonthly
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |ZoneElectricSummaryMonthly
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |SpaceGainsMonthly
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |PeakSpaceGainsMonthly
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |SpaceGainComponentsAtCoolingPeakMonthly
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |ComfortReportSimple55Monthly
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |OccupantComfortDataSummaryMonthly
| CORRIDORFLR1_PEOPLE | CORRIDORFLR2_PEOPLE | CORRIDORFLR3_PEOPLE | CORRIDORFLR4_PEOPLE | ELEVATORCOREFLR1_PEOPLE | ELEVATORCOREFLR2_PEOPLE | ELEVATORCOREFLR3_PEOPLE | ELEVATORCOREFLR4_PEOPLE | EMPLOYEELOUNGEFLR1_PEOPLE | EXERCISECENTERFLR1_PEOPLE | FRONTLOUNGEFLR1_PEOPLE | FRONTOFFICEFLR1_PEOPLE | FRONTSTAIRSFLR1_PEOPLE | FRONTSTAIRSFLR2_PEOPLE | FRONTSTAIRSFLR3_PEOPLE | FRONTSTAIRSFLR4_PEOPLE | FRONTSTORAGEFLR1_PEOPLE | FRONTSTORAGEFLR2_PEOPLE | FRONTSTORAGEFLR3_PEOPLE | FRONTSTORAGEFLR4_PEOPLE | GUESTROOM101_PEOPLE | GUESTROOM102_PEOPLE | GUESTROOM103_PEOPLE | GUESTROOM104_PEOPLE | GUESTROOM105_PEOPLE | GUESTROOM201_PEOPLE | GUESTROOM202_205_PEOPLE | GUESTROOM206_208_PEOPLE | GUESTROOM209_212_PEOPLE | GUESTROOM213_PEOPLE | GUESTROOM214_PEOPLE | GUESTROOM215_218_PEOPLE | GUESTROOM219_PEOPLE | GUESTROOM220_223_PEOPLE | GUESTROOM224_PEOPLE | GUESTROOM301_PEOPLE | GUESTROOM302_305_PEOPLE | GUESTROOM306_308_PEOPLE | GUESTROOM309_312_PEOPLE | GUESTROOM313_PEOPLE | GUESTROOM314_PEOPLE | GUESTROOM315_318_PEOPLE | GUESTROOM319_PEOPLE | GUESTROOM320_323_PEOPLE | GUESTROOM324_PEOPLE | GUESTROOM401_PEOPLE | GUESTROOM402_405_PEOPLE | GUESTROOM406_408_PEOPLE | GUESTROOM409_412_PEOPLE | GUESTROOM413_PEOPLE | GUESTROOM414_PEOPLE | GUESTROOM415_418_PEOPLE | GUESTROOM419_PEOPLE | GUESTROOM420_423_PEOPLE | GUESTROOM424_PEOPLE | LAUNDRYROOMFLR1_PEOPLE | MECHANICALROOMFLR1_PEOPLE | MEETINGROOMFLR1_PEOPLE | REARSTAIRSFLR1_PEOPLE | REARSTAIRSFLR2_PEOPLE | REARSTAIRSFLR3_PEOPLE | REARSTAIRSFLR4_PEOPLE | REARSTORAGEFLR1_PEOPLE | REARSTORAGEFLR2_PEOPLE | REARSTORAGEFLR3_PEOPLE | REARSTORAGEFLR4_PEOPLE | RESTROOMFLR1_PEOPLE |BoilerReportMonthly
| HEATSYS1 BOILER |DXReportMonthly
| 101 PTAC PTAC COOLING COIL | 102 PTAC PTAC COOLING COIL | 103 PTAC PTAC COOLING COIL | 104 PTAC PTAC COOLING COIL | 105 PTAC PTAC COOLING COIL | 201 PTAC PTAC COOLING COIL | 202_205 PTAC PTAC COOLING COIL | 206_208 PTAC PTAC COOLING COIL | 209_212 PTAC PTAC COOLING COIL | 213 PTAC PTAC COOLING COIL | 214 PTAC PTAC COOLING COIL | 215_218 PTAC PTAC COOLING COIL | 219 PTAC PTAC COOLING COIL | 220_223 PTAC PTAC COOLING COIL | 224 PTAC PTAC COOLING COIL | 301 PTAC PTAC COOLING COIL | 302_305 PTAC PTAC COOLING COIL | 306_308 PTAC PTAC COOLING COIL | 309_312 PTAC PTAC COOLING COIL | 313 PTAC PTAC COOLING COIL | 314 PTAC PTAC COOLING COIL | 315_318 PTAC PTAC COOLING COIL | 319 PTAC PTAC COOLING COIL | 320_323 PTAC PTAC COOLING COIL | 324 PTAC PTAC COOLING COIL | 401 PTAC PTAC COOLING COIL | 402_405 PTAC PTAC COOLING COIL | 406_408 PTAC PTAC COOLING COIL | 409_412 PTAC PTAC COOLING COIL | 413 PTAC PTAC COOLING COIL | 414 PTAC PTAC COOLING COIL | 415_418 PTAC PTAC COOLING COIL | 419 PTAC PTAC COOLING COIL | 420_423 PTAC PTAC COOLING COIL | 424 PTAC PTAC COOLING COIL | CORRIDORFLR1 PTAC PTAC COOLING COIL | CORRIDORFLR2 PTAC PTAC COOLING COIL | CORRIDORFLR3 PTAC PTAC COOLING COIL | CORRIDORFLR4 PTAC PTAC COOLING COIL | SAC_FRONTOFFICE PTAC COOLING COIL | SAC_FRONTLOUNGE PTAC COOLING COIL | SAC_MEETINGROOM PTAC COOLING COIL | SAC_EMPLOYEELOUNGE PTAC COOLING COIL | SAC_EXERCISECENTER PTAC COOLING COIL | SAC_RESTROOM PTAC COOLING COIL |WindowReportMonthly
| W_CORRIDORFLR1_2_0_0_0_0 | D_CORRIDORFLR1_16_0_0_0_0 | W_CORRIDORFLR1_20_0_0_0_0 | W_FRONTLOUNGEFLR1_5_0_0_0_0 | W_FRONTLOUNGEFLR1_5_0_0_0_1 | W_FRONTLOUNGEFLR1_5_0_0_0_2 | W_FRONTLOUNGEFLR1_5_0_0_0_3 | W_FRONTLOUNGEFLR1_5_0_0_0_4 | W_MEETINGROOMFLR1_5_0_0_0_0 | W_MEETINGROOMFLR1_5_0_0_0_1 | W_MEETINGROOMFLR1_5_0_0_0_2 | W_GUESTROOM101_5_0_0_0_0 | W_GUESTROOM102_5_0_0_0_0 | W_GUESTROOM103_5_0_0_0_0 | W_GUESTROOM104_3_0_0_0_0 | W_GUESTROOM105_3_0_0_0_0 | W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | W_LAUNDRYROOMFLR1_3_0_0_0_0 | W_LAUNDRYROOMFLR1_3_0_0_0_1 | W_LAUNDRYROOMFLR1_3_0_0_0_2 | W_EXERCISECENTERFLR1_3_0_0_0_0 | W_FRONTOFFICEFLR1_3_0_0_0_0 | W_FRONTOFFICEFLR1_3_0_0_0_1 | W_FRONTOFFICEFLR1_3_0_0_0_2 | W_FRONTOFFICEFLR1_3_0_0_0_3 | W_CORRIDORFLR2_2_0_0_0_0 | W_CORRIDORFLR2_15_0_0_0_0 | W_GUESTROOM201_5_0_0_0_0 | W_GUESTROOM202_205_5_0_0_0_0 | W_GUESTROOM202_205_5_0_0_0_1 | W_GUESTROOM202_205_5_0_0_0_2 | W_GUESTROOM202_205_5_0_0_0_3 | W_GUESTROOM206_208_5_0_0_0_0 | W_GUESTROOM206_208_5_0_0_0_1 | W_GUESTROOM206_208_5_0_0_0_2 | W_GUESTROOM209_212_5_0_0_0_0 | W_GUESTROOM209_212_5_0_0_0_1 | W_GUESTROOM209_212_5_0_0_0_2 | W_GUESTROOM209_212_5_0_0_0_3 | W_GUESTROOM213_5_0_0_0_0 | W_GUESTROOM214_3_0_0_0_0 | W_GUESTROOM215_218_3_0_0_0_0 | W_GUESTROOM215_218_3_0_0_0_1 | W_GUESTROOM215_218_3_0_0_0_2 | W_GUESTROOM215_218_3_0_0_0_3 | W_GUESTROOM219_3_0_0_0_0 | W_GUESTROOM220_223_3_0_0_0_0 | W_GUESTROOM220_223_3_0_0_0_1 | W_GUESTROOM220_223_3_0_0_0_2 | W_GUESTROOM220_223_3_0_0_0_3 | W_GUESTROOM224_3_0_0_0_0 | W_CORRIDORFLR3_2_0_0_0_0 | W_CORRIDORFLR3_15_0_0_0_0 | W_GUESTROOM301_5_0_0_0_0 | W_GUESTROOM302_305_5_0_0_0_0 | W_GUESTROOM302_305_5_0_0_0_1 | W_GUESTROOM302_305_5_0_0_0_2 | W_GUESTROOM302_305_5_0_0_0_3 | W_GUESTROOM306_308_5_0_0_0_0 | W_GUESTROOM306_308_5_0_0_0_1 | W_GUESTROOM306_308_5_0_0_0_2 | W_GUESTROOM309_312_5_0_0_0_0 | W_GUESTROOM309_312_5_0_0_0_1 | W_GUESTROOM309_312_5_0_0_0_2 | W_GUESTROOM309_312_5_0_0_0_3 | W_GUESTROOM313_5_0_0_0_0 | W_GUESTROOM314_3_0_0_0_0 | W_GUESTROOM315_318_3_0_0_0_0 | W_GUESTROOM315_318_3_0_0_0_1 | W_GUESTROOM315_318_3_0_0_0_2 | W_GUESTROOM315_318_3_0_0_0_3 | W_GUESTROOM319_3_0_0_0_0 | W_GUESTROOM320_323_3_0_0_0_0 | W_GUESTROOM320_323_3_0_0_0_1 | W_GUESTROOM320_323_3_0_0_0_2 | W_GUESTROOM320_323_3_0_0_0_3 | W_GUESTROOM324_3_0_0_0_0 | W_CORRIDORFLR4_2_0_0_0_0 | W_CORRIDORFLR4_15_0_0_0_0 | W_GUESTROOM401_5_0_0_0_0 | W_GUESTROOM402_405_5_0_0_0_0 | W_GUESTROOM402_405_5_0_0_0_1 | W_GUESTROOM402_405_5_0_0_0_2 | W_GUESTROOM402_405_5_0_0_0_3 | W_GUESTROOM406_408_5_0_0_0_0 | W_GUESTROOM406_408_5_0_0_0_1 | W_GUESTROOM406_408_5_0_0_0_2 | W_GUESTROOM409_412_5_0_0_0_0 | W_GUESTROOM409_412_5_0_0_0_1 | W_GUESTROOM409_412_5_0_0_0_2 | W_GUESTROOM409_412_5_0_0_0_3 | W_GUESTROOM413_5_0_0_0_0 | W_GUESTROOM414_3_0_0_0_0 | W_GUESTROOM415_418_3_0_0_0_0 | W_GUESTROOM415_418_3_0_0_0_1 | W_GUESTROOM415_418_3_0_0_0_2 | W_GUESTROOM415_418_3_0_0_0_3 | W_GUESTROOM419_3_0_0_0_0 | W_GUESTROOM420_423_3_0_0_0_0 | W_GUESTROOM420_423_3_0_0_0_1 | W_GUESTROOM420_423_3_0_0_0_2 | W_GUESTROOM420_423_3_0_0_0_3 | W_GUESTROOM424_3_0_0_0_0 |WindowEnergyReportMonthly
| W_CORRIDORFLR1_2_0_0_0_0 | D_CORRIDORFLR1_16_0_0_0_0 | W_CORRIDORFLR1_20_0_0_0_0 | W_FRONTLOUNGEFLR1_5_0_0_0_0 | W_FRONTLOUNGEFLR1_5_0_0_0_1 | W_FRONTLOUNGEFLR1_5_0_0_0_2 | W_FRONTLOUNGEFLR1_5_0_0_0_3 | W_FRONTLOUNGEFLR1_5_0_0_0_4 | W_MEETINGROOMFLR1_5_0_0_0_0 | W_MEETINGROOMFLR1_5_0_0_0_1 | W_MEETINGROOMFLR1_5_0_0_0_2 | W_GUESTROOM101_5_0_0_0_0 | W_GUESTROOM102_5_0_0_0_0 | W_GUESTROOM103_5_0_0_0_0 | W_GUESTROOM104_3_0_0_0_0 | W_GUESTROOM105_3_0_0_0_0 | W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | W_LAUNDRYROOMFLR1_3_0_0_0_0 | W_LAUNDRYROOMFLR1_3_0_0_0_1 | W_LAUNDRYROOMFLR1_3_0_0_0_2 | W_EXERCISECENTERFLR1_3_0_0_0_0 | W_FRONTOFFICEFLR1_3_0_0_0_0 | W_FRONTOFFICEFLR1_3_0_0_0_1 | W_FRONTOFFICEFLR1_3_0_0_0_2 | W_FRONTOFFICEFLR1_3_0_0_0_3 | W_CORRIDORFLR2_2_0_0_0_0 | W_CORRIDORFLR2_15_0_0_0_0 | W_GUESTROOM201_5_0_0_0_0 | W_GUESTROOM202_205_5_0_0_0_0 | W_GUESTROOM202_205_5_0_0_0_1 | W_GUESTROOM202_205_5_0_0_0_2 | W_GUESTROOM202_205_5_0_0_0_3 | W_GUESTROOM206_208_5_0_0_0_0 | W_GUESTROOM206_208_5_0_0_0_1 | W_GUESTROOM206_208_5_0_0_0_2 | W_GUESTROOM209_212_5_0_0_0_0 | W_GUESTROOM209_212_5_0_0_0_1 | W_GUESTROOM209_212_5_0_0_0_2 | W_GUESTROOM209_212_5_0_0_0_3 | W_GUESTROOM213_5_0_0_0_0 | W_GUESTROOM214_3_0_0_0_0 | W_GUESTROOM215_218_3_0_0_0_0 | W_GUESTROOM215_218_3_0_0_0_1 | W_GUESTROOM215_218_3_0_0_0_2 | W_GUESTROOM215_218_3_0_0_0_3 | W_GUESTROOM219_3_0_0_0_0 | W_GUESTROOM220_223_3_0_0_0_0 | W_GUESTROOM220_223_3_0_0_0_1 | W_GUESTROOM220_223_3_0_0_0_2 | W_GUESTROOM220_223_3_0_0_0_3 | W_GUESTROOM224_3_0_0_0_0 | W_CORRIDORFLR3_2_0_0_0_0 | W_CORRIDORFLR3_15_0_0_0_0 | W_GUESTROOM301_5_0_0_0_0 | W_GUESTROOM302_305_5_0_0_0_0 | W_GUESTROOM302_305_5_0_0_0_1 | W_GUESTROOM302_305_5_0_0_0_2 | W_GUESTROOM302_305_5_0_0_0_3 | W_GUESTROOM306_308_5_0_0_0_0 | W_GUESTROOM306_308_5_0_0_0_1 | W_GUESTROOM306_308_5_0_0_0_2 | W_GUESTROOM309_312_5_0_0_0_0 | W_GUESTROOM309_312_5_0_0_0_1 | W_GUESTROOM309_312_5_0_0_0_2 | W_GUESTROOM309_312_5_0_0_0_3 | W_GUESTROOM313_5_0_0_0_0 | W_GUESTROOM314_3_0_0_0_0 | W_GUESTROOM315_318_3_0_0_0_0 | W_GUESTROOM315_318_3_0_0_0_1 | W_GUESTROOM315_318_3_0_0_0_2 | W_GUESTROOM315_318_3_0_0_0_3 | W_GUESTROOM319_3_0_0_0_0 | W_GUESTROOM320_323_3_0_0_0_0 | W_GUESTROOM320_323_3_0_0_0_1 | W_GUESTROOM320_323_3_0_0_0_2 | W_GUESTROOM320_323_3_0_0_0_3 | W_GUESTROOM324_3_0_0_0_0 | W_CORRIDORFLR4_2_0_0_0_0 | W_CORRIDORFLR4_15_0_0_0_0 | W_GUESTROOM401_5_0_0_0_0 | W_GUESTROOM402_405_5_0_0_0_0 | W_GUESTROOM402_405_5_0_0_0_1 | W_GUESTROOM402_405_5_0_0_0_2 | W_GUESTROOM402_405_5_0_0_0_3 | W_GUESTROOM406_408_5_0_0_0_0 | W_GUESTROOM406_408_5_0_0_0_1 | W_GUESTROOM406_408_5_0_0_0_2 | W_GUESTROOM409_412_5_0_0_0_0 | W_GUESTROOM409_412_5_0_0_0_1 | W_GUESTROOM409_412_5_0_0_0_2 | W_GUESTROOM409_412_5_0_0_0_3 | W_GUESTROOM413_5_0_0_0_0 | W_GUESTROOM414_3_0_0_0_0 | W_GUESTROOM415_418_3_0_0_0_0 | W_GUESTROOM415_418_3_0_0_0_1 | W_GUESTROOM415_418_3_0_0_0_2 | W_GUESTROOM415_418_3_0_0_0_3 | W_GUESTROOM419_3_0_0_0_0 | W_GUESTROOM420_423_3_0_0_0_0 | W_GUESTROOM420_423_3_0_0_0_1 | W_GUESTROOM420_423_3_0_0_0_2 | W_GUESTROOM420_423_3_0_0_0_3 | W_GUESTROOM424_3_0_0_0_0 |WindowZoneSummaryMonthly
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |WindowEnergyZoneSummaryMonthly
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH SHOWER WATER HEATER | SWH LAUNDRY WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| FRONTSTAIRSFLR1 UNITHEATER HEATING COIL | FRONTSTAIRSFLR2 UNITHEATER HEATING COIL | FRONTSTAIRSFLR3 UNITHEATER HEATING COIL | FRONTSTAIRSFLR4 UNITHEATER HEATING COIL | REARSTAIRSFLR1 UNITHEATER HEATING COIL | REARSTAIRSFLR2 UNITHEATER HEATING COIL | REARSTAIRSFLR3 UNITHEATER HEATING COIL | REARSTAIRSFLR4 UNITHEATER HEATING COIL | MECHRM UNITHEATER HEATING COIL | 101 PTAC HEATING COIL | 102 PTAC HEATING COIL | 103 PTAC HEATING COIL | 104 PTAC HEATING COIL | 105 PTAC HEATING COIL | 201 PTAC HEATING COIL | 202_205 PTAC HEATING COIL | 206_208 PTAC HEATING COIL | 209_212 PTAC HEATING COIL | 213 PTAC HEATING COIL | 214 PTAC HEATING COIL | 215_218 PTAC HEATING COIL | 219 PTAC HEATING COIL | 220_223 PTAC HEATING COIL | 224 PTAC HEATING COIL | 301 PTAC HEATING COIL | 302_305 PTAC HEATING COIL | 306_308 PTAC HEATING COIL | 309_312 PTAC HEATING COIL | 313 PTAC HEATING COIL | 314 PTAC HEATING COIL | 315_318 PTAC HEATING COIL | 319 PTAC HEATING COIL | 320_323 PTAC HEATING COIL | 324 PTAC HEATING COIL | 401 PTAC HEATING COIL | 402_405 PTAC HEATING COIL | 406_408 PTAC HEATING COIL | 409_412 PTAC HEATING COIL | 413 PTAC HEATING COIL | 414 PTAC HEATING COIL | 415_418 PTAC HEATING COIL | 419 PTAC HEATING COIL | 420_423 PTAC HEATING COIL | 424 PTAC HEATING COIL | CORRIDORFLR1 PTAC HEATING COIL | CORRIDORFLR2 PTAC HEATING COIL | CORRIDORFLR3 PTAC HEATING COIL | CORRIDORFLR4 PTAC HEATING COIL | SAC_FRONTOFFICE HEATING COIL | SAC_FRONTLOUNGE HEATING COIL | SAC_MEETINGROOM HEATING COIL | SAC_EMPLOYEELOUNGE HEATING COIL | SAC_EXERCISECENTER HEATING COIL | SAC_RESTROOM HEATING COIL | 101 PTAC PTAC COOLING COIL | 102 PTAC PTAC COOLING COIL | 103 PTAC PTAC COOLING COIL | 104 PTAC PTAC COOLING COIL | 105 PTAC PTAC COOLING COIL | 201 PTAC PTAC COOLING COIL | 202_205 PTAC PTAC COOLING COIL | 206_208 PTAC PTAC COOLING COIL | 209_212 PTAC PTAC COOLING COIL | 213 PTAC PTAC COOLING COIL | 214 PTAC PTAC COOLING COIL | 215_218 PTAC PTAC COOLING COIL | 219 PTAC PTAC COOLING COIL | 220_223 PTAC PTAC COOLING COIL | 224 PTAC PTAC COOLING COIL | 301 PTAC PTAC COOLING COIL | 302_305 PTAC PTAC COOLING COIL | 306_308 PTAC PTAC COOLING COIL | 309_312 PTAC PTAC COOLING COIL | 313 PTAC PTAC COOLING COIL | 314 PTAC PTAC COOLING COIL | 315_318 PTAC PTAC COOLING COIL | 319 PTAC PTAC COOLING COIL | 320_323 PTAC PTAC COOLING COIL | 324 PTAC PTAC COOLING COIL | 401 PTAC PTAC COOLING COIL | 402_405 PTAC PTAC COOLING COIL | 406_408 PTAC PTAC COOLING COIL | 409_412 PTAC PTAC COOLING COIL | 413 PTAC PTAC COOLING COIL | 414 PTAC PTAC COOLING COIL | 415_418 PTAC PTAC COOLING COIL | 419 PTAC PTAC COOLING COIL | 420_423 PTAC PTAC COOLING COIL | 424 PTAC PTAC COOLING COIL | CORRIDORFLR1 PTAC PTAC COOLING COIL | CORRIDORFLR2 PTAC PTAC COOLING COIL | CORRIDORFLR3 PTAC PTAC COOLING COIL | CORRIDORFLR4 PTAC PTAC COOLING COIL | SAC_FRONTOFFICE PTAC COOLING COIL | SAC_FRONTLOUNGE PTAC COOLING COIL | SAC_MEETINGROOM PTAC COOLING COIL | SAC_EMPLOYEELOUNGE PTAC COOLING COIL | SAC_EXERCISECENTER PTAC COOLING COIL | SAC_RESTROOM PTAC COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | SWHSYSSHOWER | SWHSYSLAUNDRY |FanReportMonthly
| FRONTSTAIRSFLR1 UNITHEATER FAN | FRONTSTAIRSFLR2 UNITHEATER FAN | FRONTSTAIRSFLR3 UNITHEATER FAN | FRONTSTAIRSFLR4 UNITHEATER FAN | REARSTAIRSFLR1 UNITHEATER FAN | REARSTAIRSFLR2 UNITHEATER FAN | REARSTAIRSFLR3 UNITHEATER FAN | REARSTAIRSFLR4 UNITHEATER FAN | MECHRM UNITHEATER FAN | 101 PTAC_PTAC_SUPPLY FAN | 102 PTAC_PTAC_SUPPLY FAN | 103 PTAC_PTAC_SUPPLY FAN | 104 PTAC_PTAC_SUPPLY FAN | 105 PTAC_PTAC_SUPPLY FAN | 201 PTAC_PTAC_SUPPLY FAN | 202_205 PTAC_PTAC_SUPPLY FAN | 206_208 PTAC_PTAC_SUPPLY FAN | 209_212 PTAC_PTAC_SUPPLY FAN | 213 PTAC_PTAC_SUPPLY FAN | 214 PTAC_PTAC_SUPPLY FAN | 215_218 PTAC_PTAC_SUPPLY FAN | 219 PTAC_PTAC_SUPPLY FAN | 220_223 PTAC_PTAC_SUPPLY FAN | 224 PTAC_PTAC_SUPPLY FAN | 301 PTAC_PTAC_SUPPLY FAN | 302_305 PTAC_PTAC_SUPPLY FAN | 306_308 PTAC_PTAC_SUPPLY FAN | 309_312 PTAC_PTAC_SUPPLY FAN | 313 PTAC_PTAC_SUPPLY FAN | 314 PTAC_PTAC_SUPPLY FAN | 315_318 PTAC_PTAC_SUPPLY FAN | 319 PTAC_PTAC_SUPPLY FAN | 320_323 PTAC_PTAC_SUPPLY FAN | 324 PTAC_PTAC_SUPPLY FAN | 401 PTAC_PTAC_SUPPLY FAN | 402_405 PTAC_PTAC_SUPPLY FAN | 406_408 PTAC_PTAC_SUPPLY FAN | 409_412 PTAC_PTAC_SUPPLY FAN | 413 PTAC_PTAC_SUPPLY FAN | 414 PTAC_PTAC_SUPPLY FAN | 415_418 PTAC_PTAC_SUPPLY FAN | 419 PTAC_PTAC_SUPPLY FAN | 420_423 PTAC_PTAC_SUPPLY FAN | 424 PTAC_PTAC_SUPPLY FAN | CORRIDORFLR1 PTAC_PTAC_SUPPLY FAN | CORRIDORFLR2 PTAC_PTAC_SUPPLY FAN | CORRIDORFLR3 PTAC_PTAC_SUPPLY FAN | CORRIDORFLR4 PTAC_PTAC_SUPPLY FAN | SAC_FRONTOFFICE_PTAC_SUPPLY FAN | SAC_FRONTLOUNGE_PTAC_SUPPLY FAN | SAC_MEETINGROOM_PTAC_SUPPLY FAN | SAC_EMPLOYEELOUNGE_PTAC_SUPPLY FAN | SAC_EXERCISECENTER_PTAC_SUPPLY FAN | SAC_RESTROOM_PTAC_SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | SWHSYSSHOWER PUMP | SWHSYSLAUNDRY PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | SWHSYSSHOWER | SWHSYSLAUNDRY |ZoneTemperatureOscillationReportMonthly
| REARSTAIRSFLR1 | CORRIDORFLR1 | REARSTORAGEFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | LAUNDRYROOMFLR1 | ELEVATORCOREFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | FRONTSTORAGEFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | REARSTORAGEFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | ELEVATORCOREFLR2 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTORAGEFLR2 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | REARSTORAGEFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | ELEVATORCOREFLR3 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTORAGEFLR3 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | REARSTORAGEFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | ELEVATORCOREFLR4 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTORAGEFLR4 | FRONTSTAIRSFLR4 |MechanicalVentilationLoadsMonthly
| REARSTAIRSFLR1 | CORRIDORFLR1 | FRONTLOUNGEFLR1 | RESTROOMFLR1 | MEETINGROOMFLR1 | MECHANICALROOMFLR1 | GUESTROOM101 | GUESTROOM102 | GUESTROOM103 | GUESTROOM104 | GUESTROOM105 | EMPLOYEELOUNGEFLR1 | EXERCISECENTERFLR1 | FRONTOFFICEFLR1 | FRONTSTAIRSFLR1 | REARSTAIRSFLR2 | CORRIDORFLR2 | GUESTROOM201 | GUESTROOM202_205 | GUESTROOM206_208 | GUESTROOM209_212 | GUESTROOM213 | GUESTROOM214 | GUESTROOM215_218 | GUESTROOM219 | GUESTROOM220_223 | GUESTROOM224 | FRONTSTAIRSFLR2 | REARSTAIRSFLR3 | CORRIDORFLR3 | GUESTROOM301 | GUESTROOM302_305 | GUESTROOM306_308 | GUESTROOM309_312 | GUESTROOM313 | GUESTROOM314 | GUESTROOM315_318 | GUESTROOM319 | GUESTROOM320_323 | GUESTROOM324 | FRONTSTAIRSFLR3 | REARSTAIRSFLR4 | CORRIDORFLR4 | GUESTROOM401 | GUESTROOM402_405 | GUESTROOM406_408 | GUESTROOM409_412 | GUESTROOM413 | GUESTROOM414 | GUESTROOM415_418 | GUESTROOM419 | GUESTROOM420_423 | GUESTROOM424 | FRONTSTAIRSFLR4 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:21 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
| Latitude [deg] | 42.93 |
| Longitude [deg] | -78.7 |
| Elevation [m] | 215.00 |
| Time Zone | -5.0 |
| North Axis Angle [deg] | 180.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
| Above Ground Wall Area [m2] | 1694.58 | 635.46 | 211.83 | 635.46 | 211.83 |
| Window Opening Area [m2] | 369.78 | 187.47 | 8.38 | 167.31 | 6.62 |
| Gross Window-Wall Ratio [%] | 21.82 | 29.50 | 3.95 | 26.33 | 3.13 |
| Above Ground Window-Wall Ratio [%] | 21.82 | 29.50 | 3.95 | 26.33 | 3.13 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
| Above Ground Wall Area [m2] | 1492.32 | 607.21 | 211.83 | 556.77 | 116.50 |
| Window Opening Area [m2] | 358.39 | 187.47 | 8.38 | 155.92 | 6.62 |
| Gross Window-Wall Ratio [%] | 24.02 | 30.87 | 3.95 | 28.00 | 5.68 |
| Above Ground Window-Wall Ratio [%] | 24.02 | 30.87 | 3.95 | 28.00 | 5.68 |
| Total | |
| Gross Roof Area [m2] | 1003.40 |
| Skylight Area [m2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| REARSTAIRSFLR1 | 20.07 | Yes | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 0.00 | 0.00 | 6.4583 | 18.59 | 0.0000 |
| CORRIDORFLR1 | 150.51 | Yes | Yes | 504.62 | 1.00 | 32.70 | 0.00 | 9.82 | 9.82 | 5.3819 | 18.58 | 0.0000 |
| REARSTORAGEFLR1 | 20.07 | No | Yes | 67.30 | 1.00 | 35.77 | 0.00 | 0.00 | 0.00 | 8.6111 | 46.47 | 0.0000 |
| FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 546.70 | 1.00 | 94.02 | 0.00 | 14.83 | 14.83 | 13.9931 | 3.08 | 26.0600 |
| RESTROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 0.00 | 0.00 | 9.6875 | 18.58 | 0.0000 |
| MEETINGROOMFLR1 | 80.27 | Yes | Yes | 269.14 | 1.00 | 32.70 | 0.00 | 11.39 | 11.39 | 13.9931 | 1.87 | 6.1800 |
| MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 0.00 | 0.00 | 16.1458 | 61.88 | 0.0000 |
| GUESTROOM101 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 3.80 | 3.80 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM102 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 3.80 | 3.80 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM103 | 32.61 | Yes | Yes | 109.34 | 1.00 | 13.29 | 0.00 | 3.80 | 3.80 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM104 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 0.00 | 3.80 | 3.80 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM105 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 0.00 | 3.80 | 3.80 | 12.2708 | 21.74 | 11.8935 |
| EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 0.00 | 3.80 | 3.80 | 12.9167 | 1.81 | 21.5100 |
| LAUNDRYROOMFLR1 | 97.83 | No | Yes | 327.99 | 1.00 | 39.86 | 0.00 | 11.39 | 11.39 | 6.4583 | 9.29 | 437.5596 |
| ELEVATORCOREFLR1 | 15.05 | No | Yes | 50.46 | 1.00 | 6.13 | 0.00 | 0.00 | 0.00 | 0.0000 | 61.94 | 5331.9894 |
| EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 109.33 | 1.00 | 13.29 | 0.00 | 3.80 | 3.80 | 9.6875 | 4.66 | 18.5900 |
| FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 437.33 | 1.00 | 53.14 | 0.00 | 15.19 | 15.19 | 11.8403 | 13.04 | 13.7800 |
| FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 67.28 | 1.00 | 35.77 | 0.00 | 0.00 | 0.00 | 6.4583 | 18.58 | 0.0000 |
| FRONTSTORAGEFLR1 | 12.54 | No | Yes | 42.05 | 1.00 | 5.11 | 0.00 | 0.00 | 0.00 | 8.6111 | 46.45 | 0.0000 |
| REARSTAIRSFLR2 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 0.00 | 0.00 | 6.4583 | 18.59 | 0.0000 |
| CORRIDORFLR2 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 0.00 | 2.62 | 2.62 | 5.3819 | 18.58 | 0.0000 |
| REARSTORAGEFLR2 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 0.00 | 0.00 | 8.6111 | 46.47 | 0.0000 |
| GUESTROOM201 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 0.00 | 3.81 | 3.81 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM202_205 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 0.00 | 15.24 | 15.24 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM206_208 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 0.00 | 11.02 | 11.02 | 12.2708 | 23.41 | 11.8935 |
| GUESTROOM209_212 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 0.00 | 15.24 | 15.24 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM213 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 0.00 | 3.81 | 3.81 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM214 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 0.00 | 3.81 | 3.81 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM215_218 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 0.00 | 15.24 | 15.24 | 12.2708 | 21.74 | 11.8935 |
| ELEVATORCOREFLR2 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.00 | 0.00 | 0.0000 | 61.94 | 0.0000 |
| GUESTROOM219 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 0.00 | 3.81 | 3.81 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM220_223 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 0.00 | 15.24 | 15.24 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM224 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 0.00 | 3.81 | 3.81 | 12.2708 | 21.74 | 11.8935 |
| FRONTSTORAGEFLR2 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 0.00 | 0.00 | 8.6111 | 46.45 | 0.0000 |
| FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 0.00 | 0.00 | 6.4583 | 18.58 | 0.0000 |
| REARSTAIRSFLR3 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 0.00 | 0.00 | 6.4583 | 18.59 | 0.0000 |
| CORRIDORFLR3 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 0.00 | 2.62 | 2.62 | 5.3819 | 18.58 | 0.0000 |
| REARSTORAGEFLR3 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 0.00 | 0.00 | 8.6111 | 46.47 | 0.0000 |
| GUESTROOM301 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 0.00 | 3.80 | 3.80 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM302_305 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 0.00 | 15.21 | 15.21 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM306_308 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 0.00 | 11.01 | 11.01 | 12.2708 | 23.41 | 11.8935 |
| GUESTROOM309_312 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 0.00 | 15.21 | 15.21 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM313 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 0.00 | 3.80 | 3.80 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM314 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 0.00 | 3.80 | 3.80 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM315_318 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 0.00 | 15.21 | 15.21 | 12.2708 | 21.74 | 11.8935 |
| ELEVATORCOREFLR3 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.00 | 0.00 | 0.0000 | 61.94 | 0.0000 |
| GUESTROOM319 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 0.00 | 3.80 | 3.80 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM320_323 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 0.00 | 15.21 | 15.21 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM324 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 0.00 | 3.80 | 3.80 | 12.2708 | 21.74 | 11.8935 |
| FRONTSTORAGEFLR3 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 0.00 | 0.00 | 8.6111 | 46.45 | 0.0000 |
| FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 0.00 | 0.00 | 6.4583 | 18.58 | 0.0000 |
| REARSTAIRSFLR4 | 20.07 | Yes | Yes | 55.06 | 1.00 | 29.27 | 0.00 | 0.00 | 0.00 | 6.4583 | 18.59 | 0.0000 |
| CORRIDORFLR4 | 125.42 | Yes | Yes | 344.05 | 1.00 | 18.39 | 0.00 | 2.62 | 2.62 | 5.3819 | 18.58 | 0.0000 |
| REARSTORAGEFLR4 | 20.07 | No | Yes | 55.07 | 1.00 | 29.27 | 0.00 | 0.00 | 0.00 | 8.6111 | 46.47 | 0.0000 |
| GUESTROOM401 | 32.61 | Yes | Yes | 89.46 | 1.00 | 33.45 | 0.00 | 3.80 | 3.80 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM402_405 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 0.00 | 15.21 | 15.21 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM406_408 | 105.36 | Yes | Yes | 289.02 | 1.00 | 35.12 | 0.00 | 11.01 | 11.01 | 12.2708 | 23.41 | 11.8935 |
| GUESTROOM409_412 | 130.45 | Yes | Yes | 357.84 | 1.00 | 43.48 | 0.00 | 15.21 | 15.21 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM413 | 32.61 | Yes | Yes | 89.46 | 1.00 | 10.87 | 0.00 | 3.80 | 3.80 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM414 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 0.00 | 3.80 | 3.80 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM415_418 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 0.00 | 15.21 | 15.21 | 12.2708 | 21.74 | 11.8935 |
| ELEVATORCOREFLR4 | 15.05 | No | Yes | 41.29 | 1.00 | 5.02 | 0.00 | 0.00 | 0.00 | 0.0000 | 61.94 | 0.0000 |
| GUESTROOM419 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 0.00 | 3.80 | 3.80 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM420_423 | 130.44 | Yes | Yes | 357.81 | 1.00 | 43.48 | 0.00 | 15.21 | 15.21 | 12.2708 | 21.74 | 11.8935 |
| GUESTROOM424 | 32.61 | Yes | Yes | 89.45 | 1.00 | 10.87 | 0.00 | 3.80 | 3.80 | 12.2708 | 21.74 | 11.8935 |
| FRONTSTORAGEFLR4 | 12.54 | No | Yes | 34.40 | 1.00 | 4.18 | 0.00 | 0.00 | 0.00 | 8.6111 | 46.45 | 0.0000 |
| FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 55.05 | 1.00 | 29.26 | 0.00 | 0.00 | 0.00 | 6.4583 | 18.58 | 0.0000 |
| Total | 4013.58 | 11621.73 | 1694.58 | 0.00 | 369.78 | 369.78 | 10.7747 | 13.37 | 40.1228 | |||
| Conditioned Total | 3725.09 | 10741.65 | 1492.32 | 0.00 | 358.39 | 358.39 | 11.1379 | 13.04 | 10.1966 | |||
| Unconditioned Total | 288.49 | 880.07 | 202.26 | 0.00 | 11.39 | 11.39 | 6.0842 | 20.16 | 426.5437 | |||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| REARSTAIRSFLR1 | 20.07 | Yes | Yes | 1.00 | REARSTAIRSFLR1 | GENERAL | REARSTAIRSFLR1 | 6.4583 | 18.59 | 0.0000 | |
| CORRIDORFLR1 | 150.51 | Yes | Yes | 1.00 | CORRIDORFLR1 | GENERAL | CORRIDORFLR1 | 5.3819 | 18.58 | 0.0000 | |
| REARSTORAGEFLR1 | 20.07 | No | Yes | 1.00 | REARSTORAGEFLR1 | GENERAL | REARSTORAGEFLR1 | 8.6111 | 46.47 | 0.0000 | |
| FRONTLOUNGEFLR1 | 163.06 | Yes | Yes | 1.00 | FRONTLOUNGEFLR1 | GENERAL | FRONTLOUNGEFLR1 | 13.9931 | 3.08 | 26.0600 | |
| RESTROOMFLR1 | 32.61 | Yes | Yes | 1.00 | RESTROOMFLR1 | GENERAL | RESTROOMFLR1 | 9.6875 | 18.58 | 0.0000 | |
| MEETINGROOMFLR1 | 80.27 | Yes | Yes | 1.00 | MEETINGROOMFLR1 | GENERAL | MEETINGROOMFLR1 | 13.9931 | 1.87 | 6.1800 | |
| MECHANICALROOMFLR1 | 32.61 | Yes | Yes | 1.00 | MECHANICALROOMFLR1 | GENERAL | MECHANICALROOMFLR1 | 16.1458 | 61.88 | 0.0000 | |
| GUESTROOM101 | 32.61 | Yes | Yes | 1.00 | GUESTROOM101 | GENERAL | GUESTROOM101 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM102 | 32.61 | Yes | Yes | 1.00 | GUESTROOM102 | GENERAL | GUESTROOM102 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM103 | 32.61 | Yes | Yes | 1.00 | GUESTROOM103 | GENERAL | GUESTROOM103 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM104 | 32.61 | Yes | Yes | 1.00 | GUESTROOM104 | GENERAL | GUESTROOM104 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM105 | 32.61 | Yes | Yes | 1.00 | GUESTROOM105 | GENERAL | GUESTROOM105 | 12.2708 | 21.74 | 11.8935 | |
| EMPLOYEELOUNGEFLR1 | 32.61 | Yes | Yes | 1.00 | EMPLOYEELOUNGEFLR1 | GENERAL | EMPLOYEELOUNGEFLR1 | 12.9167 | 1.81 | 21.5100 | |
| LAUNDRYROOMFLR1 | 97.83 | No | Yes | 1.00 | LAUNDRYROOMFLR1 | GENERAL | LAUNDRYROOMFLR1 | 6.4583 | 9.29 | 437.5596 | |
| ELEVATORCOREFLR1 | 15.05 | No | Yes | 1.00 | ELEVATORCOREFLR1 | GENERAL | ELEVATORCOREFLR1 | 0.0000 | 61.94 | 5331.9894 | |
| EXERCISECENTERFLR1 | 32.61 | Yes | Yes | 1.00 | EXERCISECENTERFLR1 | GENERAL | EXERCISECENTERFLR1 | 9.6875 | 4.66 | 18.5900 | |
| FRONTOFFICEFLR1 | 130.44 | Yes | Yes | 1.00 | FRONTOFFICEFLR1 | GENERAL | FRONTOFFICEFLR1 | 11.8403 | 13.04 | 13.7800 | |
| FRONTSTAIRSFLR1 | 20.07 | Yes | Yes | 1.00 | FRONTSTAIRSFLR1 | GENERAL | FRONTSTAIRSFLR1 | 6.4583 | 18.58 | 0.0000 | |
| FRONTSTORAGEFLR1 | 12.54 | No | Yes | 1.00 | FRONTSTORAGEFLR1 | GENERAL | FRONTSTORAGEFLR1 | 8.6111 | 46.45 | 0.0000 | |
| REARSTAIRSFLR2 | 20.07 | Yes | Yes | 1.00 | REARSTAIRSFLR2 | GENERAL | REARSTAIRSFLR2 | 6.4583 | 18.59 | 0.0000 | |
| CORRIDORFLR2 | 125.42 | Yes | Yes | 1.00 | CORRIDORFLR2 | GENERAL | CORRIDORFLR2 | 5.3819 | 18.58 | 0.0000 | |
| REARSTORAGEFLR2 | 20.07 | No | Yes | 1.00 | REARSTORAGEFLR2 | GENERAL | REARSTORAGEFLR2 | 8.6111 | 46.47 | 0.0000 | |
| GUESTROOM201 | 32.61 | Yes | Yes | 1.00 | GUESTROOM201 | GENERAL | GUESTROOM201 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM202_205 | 130.45 | Yes | Yes | 1.00 | GUESTROOM202_205 | GENERAL | GUESTROOM202_205 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM206_208 | 105.36 | Yes | Yes | 1.00 | GUESTROOM206_208 | GENERAL | GUESTROOM206_208 | 12.2708 | 23.41 | 11.8935 | |
| GUESTROOM209_212 | 130.45 | Yes | Yes | 1.00 | GUESTROOM209_212 | GENERAL | GUESTROOM209_212 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM213 | 32.61 | Yes | Yes | 1.00 | GUESTROOM213 | GENERAL | GUESTROOM213 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM214 | 32.61 | Yes | Yes | 1.00 | GUESTROOM214 | GENERAL | GUESTROOM214 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM215_218 | 130.44 | Yes | Yes | 1.00 | GUESTROOM215_218 | GENERAL | GUESTROOM215_218 | 12.2708 | 21.74 | 11.8935 | |
| ELEVATORCOREFLR2 | 15.05 | No | Yes | 1.00 | ELEVATORCOREFLR2 | GENERAL | ELEVATORCOREFLR2 | 0.0000 | 61.94 | 0.0000 | |
| GUESTROOM219 | 32.61 | Yes | Yes | 1.00 | GUESTROOM219 | GENERAL | GUESTROOM219 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM220_223 | 130.44 | Yes | Yes | 1.00 | GUESTROOM220_223 | GENERAL | GUESTROOM220_223 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM224 | 32.61 | Yes | Yes | 1.00 | GUESTROOM224 | GENERAL | GUESTROOM224 | 12.2708 | 21.74 | 11.8935 | |
| FRONTSTORAGEFLR2 | 12.54 | No | Yes | 1.00 | FRONTSTORAGEFLR2 | GENERAL | FRONTSTORAGEFLR2 | 8.6111 | 46.45 | 0.0000 | |
| FRONTSTAIRSFLR2 | 20.07 | Yes | Yes | 1.00 | FRONTSTAIRSFLR2 | GENERAL | FRONTSTAIRSFLR2 | 6.4583 | 18.58 | 0.0000 | |
| REARSTAIRSFLR3 | 20.07 | Yes | Yes | 1.00 | REARSTAIRSFLR3 | GENERAL | REARSTAIRSFLR3 | 6.4583 | 18.59 | 0.0000 | |
| CORRIDORFLR3 | 125.42 | Yes | Yes | 1.00 | CORRIDORFLR3 | GENERAL | CORRIDORFLR3 | 5.3819 | 18.58 | 0.0000 | |
| REARSTORAGEFLR3 | 20.07 | No | Yes | 1.00 | REARSTORAGEFLR3 | GENERAL | REARSTORAGEFLR3 | 8.6111 | 46.47 | 0.0000 | |
| GUESTROOM301 | 32.61 | Yes | Yes | 1.00 | GUESTROOM301 | GENERAL | GUESTROOM301 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM302_305 | 130.45 | Yes | Yes | 1.00 | GUESTROOM302_305 | GENERAL | GUESTROOM302_305 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM306_308 | 105.36 | Yes | Yes | 1.00 | GUESTROOM306_308 | GENERAL | GUESTROOM306_308 | 12.2708 | 23.41 | 11.8935 | |
| GUESTROOM309_312 | 130.45 | Yes | Yes | 1.00 | GUESTROOM309_312 | GENERAL | GUESTROOM309_312 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM313 | 32.61 | Yes | Yes | 1.00 | GUESTROOM313 | GENERAL | GUESTROOM313 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM314 | 32.61 | Yes | Yes | 1.00 | GUESTROOM314 | GENERAL | GUESTROOM314 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM315_318 | 130.44 | Yes | Yes | 1.00 | GUESTROOM315_318 | GENERAL | GUESTROOM315_318 | 12.2708 | 21.74 | 11.8935 | |
| ELEVATORCOREFLR3 | 15.05 | No | Yes | 1.00 | ELEVATORCOREFLR3 | GENERAL | ELEVATORCOREFLR3 | 0.0000 | 61.94 | 0.0000 | |
| GUESTROOM319 | 32.61 | Yes | Yes | 1.00 | GUESTROOM319 | GENERAL | GUESTROOM319 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM320_323 | 130.44 | Yes | Yes | 1.00 | GUESTROOM320_323 | GENERAL | GUESTROOM320_323 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM324 | 32.61 | Yes | Yes | 1.00 | GUESTROOM324 | GENERAL | GUESTROOM324 | 12.2708 | 21.74 | 11.8935 | |
| FRONTSTORAGEFLR3 | 12.54 | No | Yes | 1.00 | FRONTSTORAGEFLR3 | GENERAL | FRONTSTORAGEFLR3 | 8.6111 | 46.45 | 0.0000 | |
| FRONTSTAIRSFLR3 | 20.07 | Yes | Yes | 1.00 | FRONTSTAIRSFLR3 | GENERAL | FRONTSTAIRSFLR3 | 6.4583 | 18.58 | 0.0000 | |
| REARSTAIRSFLR4 | 20.07 | Yes | Yes | 1.00 | REARSTAIRSFLR4 | GENERAL | REARSTAIRSFLR4 | 6.4583 | 18.59 | 0.0000 | |
| CORRIDORFLR4 | 125.42 | Yes | Yes | 1.00 | CORRIDORFLR4 | GENERAL | CORRIDORFLR4 | 5.3819 | 18.58 | 0.0000 | |
| REARSTORAGEFLR4 | 20.07 | No | Yes | 1.00 | REARSTORAGEFLR4 | GENERAL | REARSTORAGEFLR4 | 8.6111 | 46.47 | 0.0000 | |
| GUESTROOM401 | 32.61 | Yes | Yes | 1.00 | GUESTROOM401 | GENERAL | GUESTROOM401 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM402_405 | 130.45 | Yes | Yes | 1.00 | GUESTROOM402_405 | GENERAL | GUESTROOM402_405 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM406_408 | 105.36 | Yes | Yes | 1.00 | GUESTROOM406_408 | GENERAL | GUESTROOM406_408 | 12.2708 | 23.41 | 11.8935 | |
| GUESTROOM409_412 | 130.45 | Yes | Yes | 1.00 | GUESTROOM409_412 | GENERAL | GUESTROOM409_412 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM413 | 32.61 | Yes | Yes | 1.00 | GUESTROOM413 | GENERAL | GUESTROOM413 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM414 | 32.61 | Yes | Yes | 1.00 | GUESTROOM414 | GENERAL | GUESTROOM414 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM415_418 | 130.44 | Yes | Yes | 1.00 | GUESTROOM415_418 | GENERAL | GUESTROOM415_418 | 12.2708 | 21.74 | 11.8935 | |
| ELEVATORCOREFLR4 | 15.05 | No | Yes | 1.00 | ELEVATORCOREFLR4 | GENERAL | ELEVATORCOREFLR4 | 0.0000 | 61.94 | 0.0000 | |
| GUESTROOM419 | 32.61 | Yes | Yes | 1.00 | GUESTROOM419 | GENERAL | GUESTROOM419 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM420_423 | 130.44 | Yes | Yes | 1.00 | GUESTROOM420_423 | GENERAL | GUESTROOM420_423 | 12.2708 | 21.74 | 11.8935 | |
| GUESTROOM424 | 32.61 | Yes | Yes | 1.00 | GUESTROOM424 | GENERAL | GUESTROOM424 | 12.2708 | 21.74 | 11.8935 | |
| FRONTSTORAGEFLR4 | 12.54 | No | Yes | 1.00 | FRONTSTORAGEFLR4 | GENERAL | FRONTSTORAGEFLR4 | 8.6111 | 46.45 | 0.0000 | |
| FRONTSTAIRSFLR4 | 20.07 | Yes | Yes | 1.00 | FRONTSTAIRSFLR4 | GENERAL | FRONTSTAIRSFLR4 | 6.4583 | 18.58 | 0.0000 | |
| Total | 4013.58 | 10.7747 | 6.69 | 40.1228 | |||||||
| Conditioned Total | 3725.09 | 11.1379 | 6.52 | 10.1966 | |||||||
| Unconditioned Total | 288.49 | 6.0842 | 10.08 | 426.5437 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 4013.58 | 3725.09 | 288.49 | 0.00 | 10.7747 | 13.37 | 40.1228 |
| Total | 4013.58 | 3725.09 | 288.49 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 30-JUL-19:40 | 06-FEB-10:09 | - | - | - | - | - | - | - | - | - | - | 02-JAN-08:09 |
| Heating | 0.00 | 115770.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 35305.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 26471.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 6812.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 19724.73 | 40096.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 8413.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 8.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 61694.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 96735.42 | 217560.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 2401.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Boiler | 0.00 | 113368.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Cooling | General | 35305.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 26471.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 6812.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | ElevatorLift | 4884.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ElevatorLightsFan | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MiscPlug | 14516.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Laundry | 0.00 | 40096.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| General | 8413.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 8.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Water Heater | 0.00 | 61694.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 506.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 786.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 1624.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 338.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1434.00 | 456.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 747.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 889.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 4936.65 | 1853.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 135.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 211.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 436.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 90.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 384.96 | 122.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 200.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 1.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 238.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1325.24 | 497.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 126.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 195.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 404.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 84.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 357.29 | 113.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 186.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 1.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 221.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1229.99 | 461.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
ZoneHVAC:UnitHeater| Design Size Maximum Supply Air Flow Rate [m3/s] | |
| REARSTAIRSFLR1 UNIT HEATER | 0.006118 |
| MECHANICALROOMFLR1 UNIT HEATER | 0.000000 |
| FRONTSTAIRSFLR1 UNIT HEATER | 0.027040 |
| REARSTAIRSFLR2 UNIT HEATER | 0.006118 |
| FRONTSTAIRSFLR2 UNIT HEATER | 0.024410 |
| REARSTAIRSFLR3 UNIT HEATER | 0.006118 |
| FRONTSTAIRSFLR3 UNIT HEATER | 0.030385 |
| REARSTAIRSFLR4 UNIT HEATER | 0.021838 |
| FRONTSTAIRSFLR4 UNIT HEATER | 0.049011 |
| Design Size Maximum Flow Rate [m3/s] | |
| REARSTAIRSFLR1 UNITHEATER FAN | 0.006118 |
| MECHRM UNITHEATER FAN | 0.000000 |
| FRONTSTAIRSFLR1 UNITHEATER FAN | 0.027040 |
| REARSTAIRSFLR2 UNITHEATER FAN | 0.006118 |
| FRONTSTAIRSFLR2 UNITHEATER FAN | 0.024410 |
| REARSTAIRSFLR3 UNITHEATER FAN | 0.006118 |
| FRONTSTAIRSFLR3 UNITHEATER FAN | 0.030385 |
| REARSTAIRSFLR4 UNITHEATER FAN | 0.021838 |
| FRONTSTAIRSFLR4 UNITHEATER FAN | 0.049011 |
| Design Size Nominal Capacity [W] | |
| REARSTAIRSFLR1 UNITHEATER HEATING COIL | 81.38 |
| MECHRM UNITHEATER HEATING COIL | 0.000000 |
| FRONTSTAIRSFLR1 UNITHEATER HEATING COIL | 359.76 |
| REARSTAIRSFLR2 UNITHEATER HEATING COIL | 81.37 |
| FRONTSTAIRSFLR2 UNITHEATER HEATING COIL | 324.77 |
| REARSTAIRSFLR3 UNITHEATER HEATING COIL | 81.38 |
| FRONTSTAIRSFLR3 UNITHEATER HEATING COIL | 404.27 |
| REARSTAIRSFLR4 UNITHEATER HEATING COIL | 290.54 |
| FRONTSTAIRSFLR4 UNITHEATER HEATING COIL | 652.14 |
| Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | |
| CORRIDORFLR1 PTAC | 3.05 | 3.05 | 3.05 | 0.045874 | 0.045874 | 0.045874 |
| SAC_FRONTLOUNGE | 0.780683 | 0.780683 | 0.780683 | 0.236073 | 0.236073 | 0.236073 |
| SAC_RESTROOM | 0.066536 | 0.066536 | 0.066536 | 0.000000 | 0.000000 | 0.000000 |
| SAC_MEETINGROOM | 0.378047 | 0.378047 | 0.378047 | 0.126415 | 0.126415 | 0.126415 |
| 101 PTAC | 0.067379 | 0.067379 | 0.067379 | 0.013480 | 0.013480 | 0.013480 |
| 102 PTAC | 0.062629 | 0.062629 | 0.062629 | 0.013480 | 0.013480 | 0.013480 |
| 103 PTAC | 0.109373 | 0.109373 | 0.109373 | 0.013480 | 0.013480 | 0.013480 |
| 104 PTAC | 0.132211 | 0.132211 | 0.132211 | 0.013479 | 0.013479 | 0.013479 |
| 105 PTAC | 0.176542 | 0.176542 | 0.176542 | 0.013479 | 0.013479 | 0.013479 |
| SAC_EMPLOYEELOUNGE | 0.672673 | 0.672673 | 0.672673 | 0.051353 | 0.051353 | 0.051353 |
| SAC_EXERCISECENTER | 0.136166 | 0.136166 | 0.136166 | 0.043070 | 0.043070 | 0.043070 |
| SAC_FRONTOFFICE | 0.391600 | 0.391600 | 0.391600 | 0.056322 | 0.056322 | 0.056322 |
| CORRIDORFLR2 PTAC | 0.298218 | 0.298218 | 0.298218 | 0.038228 | 0.038228 | 0.038228 |
| 201 PTAC | 0.085442 | 0.085442 | 0.085442 | 0.013480 | 0.013480 | 0.013480 |
| 202_205 PTAC | 0.408786 | 0.408786 | 0.408786 | 0.053919 | 0.053919 | 0.053919 |
| 206_208 PTAC | 0.324970 | 0.324970 | 0.324970 | 0.042733 | 0.042733 | 0.042733 |
| 209_212 PTAC | 0.396430 | 0.396430 | 0.396430 | 0.053919 | 0.053919 | 0.053919 |
| 213 PTAC | 0.110899 | 0.110899 | 0.110899 | 0.013480 | 0.013480 | 0.013480 |
| 214 PTAC | 0.143572 | 0.143572 | 0.143572 | 0.013479 | 0.013479 | 0.013479 |
| 215_218 PTAC | 1.15 | 1.15 | 1.15 | 0.053915 | 0.053915 | 0.053915 |
| 219 PTAC | 0.612359 | 0.612359 | 0.612359 | 0.013479 | 0.013479 | 0.013479 |
| 220_223 PTAC | 0.490203 | 0.490203 | 0.490203 | 0.053915 | 0.053915 | 0.053915 |
| 224 PTAC | 0.141280 | 0.141280 | 0.141280 | 0.013479 | 0.013479 | 0.013479 |
| CORRIDORFLR3 PTAC | 0.216818 | 0.216818 | 0.216818 | 0.038228 | 0.038228 | 0.038228 |
| 301 PTAC | 0.090749 | 0.090749 | 0.090749 | 0.013480 | 0.013480 | 0.013480 |
| 302_305 PTAC | 0.216789 | 0.216789 | 0.216789 | 0.053919 | 0.053919 | 0.053919 |
| 306_308 PTAC | 0.166399 | 0.166399 | 0.166399 | 0.042733 | 0.042733 | 0.042733 |
| 309_312 PTAC | 0.383875 | 0.383875 | 0.383875 | 0.053919 | 0.053919 | 0.053919 |
| 313 PTAC | 0.101990 | 0.101990 | 0.101990 | 0.013480 | 0.013480 | 0.013480 |
| 314 PTAC | 0.131002 | 0.131002 | 0.131002 | 0.013479 | 0.013479 | 0.013479 |
| 315_318 PTAC | 0.543195 | 0.543195 | 0.543195 | 0.053915 | 0.053915 | 0.053915 |
| 319 PTAC | 0.119849 | 0.119849 | 0.119849 | 0.013479 | 0.013479 | 0.013479 |
| 320_323 PTAC | 0.462510 | 0.462510 | 0.462510 | 0.053915 | 0.053915 | 0.053915 |
| 324 PTAC | 0.083073 | 0.083073 | 0.083073 | 0.013479 | 0.013479 | 0.013479 |
| CORRIDORFLR4 PTAC | 0.361442 | 0.361442 | 0.361442 | 0.038228 | 0.038228 | 0.038228 |
| 401 PTAC | 0.134734 | 0.134734 | 0.134734 | 0.013480 | 0.013480 | 0.013480 |
| 402_405 PTAC | 0.329696 | 0.329696 | 0.329696 | 0.053919 | 0.053919 | 0.053919 |
| 406_408 PTAC | 0.259762 | 0.259762 | 0.259762 | 0.042733 | 0.042733 | 0.042733 |
| 409_412 PTAC | 0.496474 | 0.496474 | 0.496474 | 0.053919 | 0.053919 | 0.053919 |
| 413 PTAC | 0.137436 | 0.137436 | 0.137436 | 0.013480 | 0.013480 | 0.013480 |
| 414 PTAC | 0.130505 | 0.130505 | 0.130505 | 0.013479 | 0.013479 | 0.013479 |
| 415_418 PTAC | 0.616396 | 0.616396 | 0.616396 | 0.053915 | 0.053915 | 0.053915 |
| 419 PTAC | 0.166006 | 0.166006 | 0.166006 | 0.013479 | 0.013479 | 0.013479 |
| 420_423 PTAC | 0.607648 | 0.607648 | 0.607648 | 0.053915 | 0.053915 | 0.053915 |
| 424 PTAC | 0.169550 | 0.169550 | 0.169550 | 0.013479 | 0.013479 | 0.013479 |
| Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
| CORRIDORFLR1 PTAC HEATING COIL | 42709.16 | 0.000374 | 1073.09 |
| SAC_FRONTLOUNGE HEATING COIL | 20956.11 | 0.000183 | 477.98 |
| SAC_RESTROOM HEATING COIL | 885.01 | 0.000008 | 22.36 |
| SAC_MEETINGROOM HEATING COIL | 10689.71 | 0.000094 | 241.60 |
| 101 PTAC HEATING COIL | 1499.88 | 0.000013 | 35.29 |
| 102 PTAC HEATING COIL | 1436.70 | 0.000013 | 33.64 |
| 103 PTAC HEATING COIL | 2058.45 | 0.000018 | 49.69 |
| 104 PTAC HEATING COIL | 2362.17 | 0.000021 | 57.45 |
| 105 PTAC HEATING COIL | 2951.82 | 0.000026 | 72.45 |
| SAC_EMPLOYEELOUNGE HEATING COIL | 11247.01 | 0.000098 | 276.07 |
| SAC_EXERCISECENTER HEATING COIL | 3739.96 | 0.000033 | 84.96 |
| SAC_FRONTOFFICE HEATING COIL | 7731.01 | 0.000068 | 185.31 |
| CORRIDORFLR2 PTAC HEATING COIL | 5678.69 | 0.000050 | 136.86 |
| 201 PTAC HEATING COIL | 1740.19 | 0.000015 | 41.52 |
| 202_205 PTAC HEATING COIL | 7851.97 | 0.000069 | 188.98 |
| 206_208 PTAC HEATING COIL | 6236.20 | 0.000055 | 150.11 |
| 209_212 PTAC HEATING COIL | 7687.66 | 0.000067 | 184.76 |
| 213 PTAC HEATING COIL | 2078.75 | 0.000018 | 50.21 |
| 214 PTAC HEATING COIL | 2513.30 | 0.000022 | 61.30 |
| 215_218 PTAC HEATING COIL | 17702.71 | 0.000155 | 439.31 |
| 219 PTAC HEATING COIL | 8748.72 | 0.000077 | 219.18 |
| 220_223 PTAC HEATING COIL | 8934.78 | 0.000078 | 216.69 |
| 224 PTAC HEATING COIL | 2482.81 | 0.000022 | 60.52 |
| CORRIDORFLR3 PTAC HEATING COIL | 4595.94 | 0.000040 | 108.98 |
| 301 PTAC HEATING COIL | 1810.79 | 0.000016 | 43.34 |
| 302_305 PTAC HEATING COIL | 5298.20 | 0.000046 | 122.78 |
| 306_308 PTAC HEATING COIL | 4127.01 | 0.000036 | 95.41 |
| 309_312 PTAC HEATING COIL | 7520.64 | 0.000066 | 180.48 |
| 313 PTAC HEATING COIL | 1960.25 | 0.000017 | 47.17 |
| 314 PTAC HEATING COIL | 2346.09 | 0.000021 | 57.04 |
| 315_318 PTAC HEATING COIL | 9639.66 | 0.000084 | 234.67 |
| 319 PTAC HEATING COIL | 2197.76 | 0.000019 | 53.25 |
| 320_323 PTAC HEATING COIL | 8566.45 | 0.000075 | 207.27 |
| 324 PTAC HEATING COIL | 1708.58 | 0.000015 | 40.70 |
| CORRIDORFLR4 PTAC HEATING COIL | 6519.65 | 0.000057 | 158.35 |
| 401 PTAC HEATING COIL | 2395.89 | 0.000021 | 58.31 |
| 402_405 PTAC HEATING COIL | 6800.00 | 0.000059 | 161.91 |
| 406_408 PTAC HEATING COIL | 5368.86 | 0.000047 | 127.80 |
| 409_412 PTAC HEATING COIL | 9018.34 | 0.000079 | 218.81 |
| 413 PTAC HEATING COIL | 2431.72 | 0.000021 | 59.22 |
| 414 PTAC HEATING COIL | 2339.48 | 0.000020 | 56.87 |
| 415_418 PTAC HEATING COIL | 10613.28 | 0.000093 | 259.46 |
| 419 PTAC HEATING COIL | 2811.68 | 0.000025 | 68.89 |
| 420_423 PTAC HEATING COIL | 10496.92 | 0.000092 | 256.50 |
| 424 PTAC HEATING COIL | 2858.83 | 0.000025 | 70.09 |
| Design Size Rated Air Flow Rate [m3/s] | Design Size Gross Rated Total Cooling Capacity [W] | Design Size Gross Rated Sensible Heat Ratio | |
| CORRIDORFLR1 PTAC PTAC COOLING COIL | 3.05 | 57197.49 | 0.800544 |
| SAC_FRONTLOUNGE PTAC COOLING COIL | 0.780683 | 17965.84 | 0.725460 |
| SAC_RESTROOM PTAC COOLING COIL | 0.066536 | 1101.41 | 0.800655 |
| SAC_MEETINGROOM PTAC COOLING COIL | 0.378047 | 9387.81 | 0.701083 |
| 101 PTAC PTAC COOLING COIL | 0.067379 | 1354.40 | 0.773769 |
| 102 PTAC PTAC COOLING COIL | 0.062629 | 1351.88 | 0.746950 |
| 103 PTAC PTAC COOLING COIL | 0.109373 | 1954.16 | 0.800629 |
| 104 PTAC PTAC COOLING COIL | 0.132211 | 2432.32 | 0.800811 |
| 105 PTAC PTAC COOLING COIL | 0.176542 | 3118.37 | 0.800551 |
| SAC_EMPLOYEELOUNGE PTAC COOLING COIL | 0.672673 | 11942.53 | 0.800799 |
| SAC_EXERCISECENTER PTAC COOLING COIL | 0.136166 | 3011.23 | 0.739206 |
| SAC_FRONTOFFICE PTAC COOLING COIL | 0.391600 | 7443.65 | 0.797176 |
| CORRIDORFLR2 PTAC PTAC COOLING COIL | 0.298218 | 5515.62 | 0.800056 |
| 201 PTAC PTAC COOLING COIL | 0.085442 | 1711.21 | 0.775878 |
| 202_205 PTAC PTAC COOLING COIL | 0.408786 | 7388.41 | 0.800726 |
| 206_208 PTAC PTAC COOLING COIL | 0.324970 | 5861.35 | 0.800425 |
| 209_212 PTAC PTAC COOLING COIL | 0.396430 | 7203.26 | 0.800942 |
| 213 PTAC PTAC COOLING COIL | 0.110899 | 1977.30 | 0.800340 |
| 214 PTAC PTAC COOLING COIL | 0.143572 | 2608.89 | 0.800925 |
| 215_218 PTAC PTAC COOLING COIL | 1.15 | 19026.41 | 0.800655 |
| 219 PTAC PTAC COOLING COIL | 0.612359 | 10136.72 | 0.800655 |
| 220_223 PTAC PTAC COOLING COIL | 0.490203 | 9117.95 | 0.800198 |
| 224 PTAC PTAC COOLING COIL | 0.141280 | 2573.36 | 0.800127 |
| CORRIDORFLR3 PTAC PTAC COOLING COIL | 0.216818 | 4633.66 | 0.750775 |
| 301 PTAC PTAC COOLING COIL | 0.090749 | 1997.16 | 0.740542 |
| 302_305 PTAC PTAC COOLING COIL | 0.216789 | 4732.70 | 0.743779 |
| 306_308 PTAC PTAC COOLING COIL | 0.166399 | 3594.10 | 0.746768 |
| 309_312 PTAC PTAC COOLING COIL | 0.383875 | 7051.15 | 0.800331 |
| 313 PTAC PTAC COOLING COIL | 0.101990 | 1966.48 | 0.790646 |
| 314 PTAC PTAC COOLING COIL | 0.131002 | 2415.53 | 0.800062 |
| 315_318 PTAC PTAC COOLING COIL | 0.543195 | 9959.94 | 0.800918 |
| 319 PTAC PTAC COOLING COIL | 0.119849 | 2179.78 | 0.800621 |
| 320_323 PTAC PTAC COOLING COIL | 0.462510 | 8705.61 | 0.800336 |
| 324 PTAC PTAC COOLING COIL | 0.083073 | 1612.96 | 0.788449 |
| CORRIDORFLR4 PTAC PTAC COOLING COIL | 0.361442 | 7018.70 | 0.788411 |
| 401 PTAC PTAC COOLING COIL | 0.134734 | 2498.50 | 0.800194 |
| 402_405 PTAC PTAC COOLING COIL | 0.329696 | 6912.99 | 0.758255 |
| 406_408 PTAC PTAC COOLING COIL | 0.259762 | 5414.23 | 0.759992 |
| 409_412 PTAC PTAC COOLING COIL | 0.496474 | 9239.10 | 0.800038 |
| 413 PTAC PTAC COOLING COIL | 0.137436 | 2649.59 | 0.790685 |
| 414 PTAC PTAC COOLING COIL | 0.130505 | 2392.17 | 0.800022 |
| 415_418 PTAC PTAC COOLING COIL | 0.616396 | 11070.48 | 0.800864 |
| 419 PTAC PTAC COOLING COIL | 0.166006 | 2955.20 | 0.800876 |
| 420_423 PTAC PTAC COOLING COIL | 0.607648 | 10935.32 | 0.800183 |
| 424 PTAC PTAC COOLING COIL | 0.169550 | 3013.75 | 0.800390 |
| Design Size Maximum Flow Rate [m3/s] | |
| CORRIDORFLR1 PTAC_PTAC_SUPPLY FAN | 3.05 |
| SAC_FRONTLOUNGE_PTAC_SUPPLY FAN | 0.780683 |
| SAC_RESTROOM_PTAC_SUPPLY FAN | 0.066536 |
| SAC_MEETINGROOM_PTAC_SUPPLY FAN | 0.378047 |
| 101 PTAC_PTAC_SUPPLY FAN | 0.067379 |
| 102 PTAC_PTAC_SUPPLY FAN | 0.062629 |
| 103 PTAC_PTAC_SUPPLY FAN | 0.109373 |
| 104 PTAC_PTAC_SUPPLY FAN | 0.132211 |
| 105 PTAC_PTAC_SUPPLY FAN | 0.176542 |
| SAC_EMPLOYEELOUNGE_PTAC_SUPPLY FAN | 0.672673 |
| SAC_EXERCISECENTER_PTAC_SUPPLY FAN | 0.136166 |
| SAC_FRONTOFFICE_PTAC_SUPPLY FAN | 0.391600 |
| CORRIDORFLR2 PTAC_PTAC_SUPPLY FAN | 0.298218 |
| 201 PTAC_PTAC_SUPPLY FAN | 0.085442 |
| 202_205 PTAC_PTAC_SUPPLY FAN | 0.408786 |
| 206_208 PTAC_PTAC_SUPPLY FAN | 0.324970 |
| 209_212 PTAC_PTAC_SUPPLY FAN | 0.396430 |
| 213 PTAC_PTAC_SUPPLY FAN | 0.110899 |
| 214 PTAC_PTAC_SUPPLY FAN | 0.143572 |
| 215_218 PTAC_PTAC_SUPPLY FAN | 1.15 |
| 219 PTAC_PTAC_SUPPLY FAN | 0.612359 |
| 220_223 PTAC_PTAC_SUPPLY FAN | 0.490203 |
| 224 PTAC_PTAC_SUPPLY FAN | 0.141280 |
| CORRIDORFLR3 PTAC_PTAC_SUPPLY FAN | 0.216818 |
| 301 PTAC_PTAC_SUPPLY FAN | 0.090749 |
| 302_305 PTAC_PTAC_SUPPLY FAN | 0.216789 |
| 306_308 PTAC_PTAC_SUPPLY FAN | 0.166399 |
| 309_312 PTAC_PTAC_SUPPLY FAN | 0.383875 |
| 313 PTAC_PTAC_SUPPLY FAN | 0.101990 |
| 314 PTAC_PTAC_SUPPLY FAN | 0.131002 |
| 315_318 PTAC_PTAC_SUPPLY FAN | 0.543195 |
| 319 PTAC_PTAC_SUPPLY FAN | 0.119849 |
| 320_323 PTAC_PTAC_SUPPLY FAN | 0.462510 |
| 324 PTAC_PTAC_SUPPLY FAN | 0.083073 |
| CORRIDORFLR4 PTAC_PTAC_SUPPLY FAN | 0.361442 |
| 401 PTAC_PTAC_SUPPLY FAN | 0.134734 |
| 402_405 PTAC_PTAC_SUPPLY FAN | 0.329696 |
| 406_408 PTAC_PTAC_SUPPLY FAN | 0.259762 |
| 409_412 PTAC_PTAC_SUPPLY FAN | 0.496474 |
| 413 PTAC_PTAC_SUPPLY FAN | 0.137436 |
| 414 PTAC_PTAC_SUPPLY FAN | 0.130505 |
| 415_418 PTAC_PTAC_SUPPLY FAN | 0.616396 |
| 419 PTAC_PTAC_SUPPLY FAN | 0.166006 |
| 420_423 PTAC_PTAC_SUPPLY FAN | 0.607648 |
| 424 PTAC_PTAC_SUPPLY FAN | 0.169550 |
| Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
| HEATSYS1 | 0.002549 | 0.305862 |
| SWHSYSSHOWER | 0.000180 | 0.021594 |
| SWHSYSLAUNDRY | 0.000129 | 0.015520 |
| Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
| HEATSYS1 PUMP | 0.002549 | 767.60 | 0.000000 |
| Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
| HEATSYS1 BOILER | 291348.79 | 291348.79 | 0.002549 |
| Design Flow Rate [m3/s] | Design Power Consumption [W] | |
| SWHSYSSHOWER PUMP | 0.000180 | 8.11 |
| SWHSYSLAUNDRY PUMP | 0.000129 | 0.000001 |
| Use Side Design Flow Rate [m3/s] | |
| SWH SHOWER WATER HEATER | 0.000180 |
| SWH LAUNDRY WATER HEATER | 0.000129 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| Possible Shadow Receivers | |
| ENTRY CANOPY | W_CORRIDORFLR1_16_0_0 | W_FRONTLOUNGEFLR1_4_0_0 | W_FRONTSTAIRSFLR1_4_0_0 | W_CORRIDORFLR2_15_0_0 | W_GUESTROOM201_4_0_0 | W_FRONTSTAIRSFLR2_4_0_0 | W_CORRIDORFLR3_15_0_0 | W_GUESTROOM301_4_0_0 | W_FRONTSTAIRSFLR3_4_0_0 | W_CORRIDORFLR4_15_0_0 | W_GUESTROOM401_4_0_0 | W_FRONTSTAIRSFLR4_4_0_0 | |
| Mir-ENTRY CANOPY | W_CORRIDORFLR1_16_0_0 | W_FRONTLOUNGEFLR1_4_0_0 | W_FRONTSTAIRSFLR1_4_0_0 | |
| W_CORRIDORFLR1_16_0_0 | Mir-ENTRY CANOPY | |
| W_FRONTLOUNGEFLR1_4_0_0 | Mir-ENTRY CANOPY | |
| W_FRONTSTAIRSFLR1_4_0_0 | Mir-ENTRY CANOPY | |
| Possible Shadow Receivers | |
| W_REARSTAIRSFLR1_3_0_0 | W_REARSTAIRSFLR1_3_0_0_DOOR | |
| W_CORRIDORFLR1_2_0_0 | W_CORRIDORFLR1_2_0_0_0_0 | |
| W_CORRIDORFLR1_10_0_0 | W_CORRIDORFLR1_10_0_0_DOOR | |
| W_CORRIDORFLR1_16_0_0 | D_CORRIDORFLR1_16_0_0_0_0 | |
| W_CORRIDORFLR1_20_0_0 | W_CORRIDORFLR1_20_0_0_0_0 | |
| W_FRONTLOUNGEFLR1_5_0_0 | W_FRONTLOUNGEFLR1_5_0_0_0_0 | W_FRONTLOUNGEFLR1_5_0_0_0_1 | W_FRONTLOUNGEFLR1_5_0_0_0_2 | W_FRONTLOUNGEFLR1_5_0_0_0_3 | W_FRONTLOUNGEFLR1_5_0_0_0_4 | |
| W_MEETINGROOMFLR1_5_0_0 | W_MEETINGROOMFLR1_5_0_0_0_0 | W_MEETINGROOMFLR1_5_0_0_0_1 | W_MEETINGROOMFLR1_5_0_0_0_2 | |
| W_GUESTROOM101_5_0_0 | W_GUESTROOM101_5_0_0_0_0 | |
| W_GUESTROOM102_5_0_0 | W_GUESTROOM102_5_0_0_0_0 | |
| W_GUESTROOM103_5_0_0 | W_GUESTROOM103_5_0_0_0_0 | |
| W_GUESTROOM104_3_0_0 | W_GUESTROOM104_3_0_0_0_0 | |
| W_GUESTROOM105_3_0_0 | W_GUESTROOM105_3_0_0_0_0 | |
| W_EMPLOYEELOUNGEFLR1_3_0_0 | W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | |
| W_LAUNDRYROOMFLR1_3_0_0 | W_LAUNDRYROOMFLR1_3_0_0_0_0 | W_LAUNDRYROOMFLR1_3_0_0_0_1 | W_LAUNDRYROOMFLR1_3_0_0_0_2 | |
| W_EXERCISECENTERFLR1_3_0_0 | W_EXERCISECENTERFLR1_3_0_0_0_0 | |
| W_FRONTOFFICEFLR1_3_0_0 | W_FRONTOFFICEFLR1_3_0_0_0_0 | W_FRONTOFFICEFLR1_3_0_0_0_1 | W_FRONTOFFICEFLR1_3_0_0_0_2 | W_FRONTOFFICEFLR1_3_0_0_0_3 | |
| W_FRONTSTAIRSFLR1_3_0_0 | W_FRONTSTAIRSFLR1_3_0_0_DOOR | |
| W_CORRIDORFLR2_2_0_0 | W_CORRIDORFLR2_2_0_0_0_0 | |
| W_CORRIDORFLR2_15_0_0 | W_CORRIDORFLR2_15_0_0_0_0 | |
| W_GUESTROOM201_5_0_0 | W_GUESTROOM201_5_0_0_0_0 | |
| W_GUESTROOM202_205_5_0_0 | W_GUESTROOM202_205_5_0_0_0_0 | W_GUESTROOM202_205_5_0_0_0_1 | W_GUESTROOM202_205_5_0_0_0_2 | W_GUESTROOM202_205_5_0_0_0_3 | |
| W_GUESTROOM206_208_5_0_0 | W_GUESTROOM206_208_5_0_0_0_0 | W_GUESTROOM206_208_5_0_0_0_1 | W_GUESTROOM206_208_5_0_0_0_2 | |
| W_GUESTROOM209_212_5_0_0 | W_GUESTROOM209_212_5_0_0_0_0 | W_GUESTROOM209_212_5_0_0_0_1 | W_GUESTROOM209_212_5_0_0_0_2 | W_GUESTROOM209_212_5_0_0_0_3 | |
| W_GUESTROOM213_5_0_0 | W_GUESTROOM213_5_0_0_0_0 | |
| W_GUESTROOM214_3_0_0 | W_GUESTROOM214_3_0_0_0_0 | |
| W_GUESTROOM215_218_3_0_0 | W_GUESTROOM215_218_3_0_0_0_0 | W_GUESTROOM215_218_3_0_0_0_1 | W_GUESTROOM215_218_3_0_0_0_2 | W_GUESTROOM215_218_3_0_0_0_3 | |
| W_GUESTROOM219_3_0_0 | W_GUESTROOM219_3_0_0_0_0 | |
| W_GUESTROOM220_223_3_0_0 | W_GUESTROOM220_223_3_0_0_0_0 | W_GUESTROOM220_223_3_0_0_0_1 | W_GUESTROOM220_223_3_0_0_0_2 | W_GUESTROOM220_223_3_0_0_0_3 | |
| W_GUESTROOM224_3_0_0 | W_GUESTROOM224_3_0_0_0_0 | |
| W_CORRIDORFLR3_2_0_0 | W_CORRIDORFLR3_2_0_0_0_0 | |
| W_CORRIDORFLR3_15_0_0 | W_CORRIDORFLR3_15_0_0_0_0 | |
| W_GUESTROOM301_5_0_0 | W_GUESTROOM301_5_0_0_0_0 | |
| W_GUESTROOM302_305_5_0_0 | W_GUESTROOM302_305_5_0_0_0_0 | W_GUESTROOM302_305_5_0_0_0_1 | W_GUESTROOM302_305_5_0_0_0_2 | W_GUESTROOM302_305_5_0_0_0_3 | |
| W_GUESTROOM306_308_5_0_0 | W_GUESTROOM306_308_5_0_0_0_0 | W_GUESTROOM306_308_5_0_0_0_1 | W_GUESTROOM306_308_5_0_0_0_2 | |
| W_GUESTROOM309_312_5_0_0 | W_GUESTROOM309_312_5_0_0_0_0 | W_GUESTROOM309_312_5_0_0_0_1 | W_GUESTROOM309_312_5_0_0_0_2 | W_GUESTROOM309_312_5_0_0_0_3 | |
| W_GUESTROOM313_5_0_0 | W_GUESTROOM313_5_0_0_0_0 | |
| W_GUESTROOM314_3_0_0 | W_GUESTROOM314_3_0_0_0_0 | |
| W_GUESTROOM315_318_3_0_0 | W_GUESTROOM315_318_3_0_0_0_0 | W_GUESTROOM315_318_3_0_0_0_1 | W_GUESTROOM315_318_3_0_0_0_2 | W_GUESTROOM315_318_3_0_0_0_3 | |
| W_GUESTROOM319_3_0_0 | W_GUESTROOM319_3_0_0_0_0 | |
| W_GUESTROOM320_323_3_0_0 | W_GUESTROOM320_323_3_0_0_0_0 | W_GUESTROOM320_323_3_0_0_0_1 | W_GUESTROOM320_323_3_0_0_0_2 | W_GUESTROOM320_323_3_0_0_0_3 | |
| W_GUESTROOM324_3_0_0 | W_GUESTROOM324_3_0_0_0_0 | |
| W_CORRIDORFLR4_2_0_0 | W_CORRIDORFLR4_2_0_0_0_0 | |
| W_CORRIDORFLR4_15_0_0 | W_CORRIDORFLR4_15_0_0_0_0 | |
| W_GUESTROOM401_5_0_0 | W_GUESTROOM401_5_0_0_0_0 | |
| W_GUESTROOM402_405_5_0_0 | W_GUESTROOM402_405_5_0_0_0_0 | W_GUESTROOM402_405_5_0_0_0_1 | W_GUESTROOM402_405_5_0_0_0_2 | W_GUESTROOM402_405_5_0_0_0_3 | |
| W_GUESTROOM406_408_5_0_0 | W_GUESTROOM406_408_5_0_0_0_0 | W_GUESTROOM406_408_5_0_0_0_1 | W_GUESTROOM406_408_5_0_0_0_2 | |
| W_GUESTROOM409_412_5_0_0 | W_GUESTROOM409_412_5_0_0_0_0 | W_GUESTROOM409_412_5_0_0_0_1 | W_GUESTROOM409_412_5_0_0_0_2 | W_GUESTROOM409_412_5_0_0_0_3 | |
| W_GUESTROOM413_5_0_0 | W_GUESTROOM413_5_0_0_0_0 | |
| W_GUESTROOM414_3_0_0 | W_GUESTROOM414_3_0_0_0_0 | |
| W_GUESTROOM415_418_3_0_0 | W_GUESTROOM415_418_3_0_0_0_0 | W_GUESTROOM415_418_3_0_0_0_1 | W_GUESTROOM415_418_3_0_0_0_2 | W_GUESTROOM415_418_3_0_0_0_3 | |
| W_GUESTROOM419_3_0_0 | W_GUESTROOM419_3_0_0_0_0 | |
| W_GUESTROOM420_423_3_0_0 | W_GUESTROOM420_423_3_0_0_0_0 | W_GUESTROOM420_423_3_0_0_0_1 | W_GUESTROOM420_423_3_0_0_0_2 | W_GUESTROOM420_423_3_0_0_0_3 | |
| W_GUESTROOM424_3_0_0 | W_GUESTROOM424_3_0_0_0_0 | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | Yes | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 8.97 | 26.20 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | HotelSmall | 180.000 | Suburbs | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.220 | 370.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 2 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 67 | 591 | 106 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | REARSTAIRSFLR1 | 0.0 | 0.00 | 0.00 | 0.00 | -53.69 | -14.22 | 1.68 | 1 | 1 | 1 | -54.91 | -52.47 | -18.34 | -10.11 | 0.00 | 3.35 | 3.35 | 67.30 | TARP | TARP | 20.07 | 35.77 | 33.82 | 0.00 | 6 | 1 | 0 | Yes |
| 2 | CORRIDORFLR1 | 0.0 | 0.00 | 0.00 | 0.00 | -26.68 | -9.43 | 1.68 | 1 | 1 | 1 | -54.91 | -4.87E-002 | -18.34 | -4.88E-002 | 0.00 | 3.35 | 3.35 | 504.62 | TARP | TARP | 150.51 | 32.70 | 20.94 | 9.82 | 29 | 4 | 2 | Yes |
| 3 | REARSTORAGEFLR1 | 0.0 | 0.00 | 0.00 | 0.00 | -53.69 | -4.16 | 1.68 | 1 | 1 | 1 | -54.91 | -52.47 | -8.28 | -4.88E-002 | 0.00 | 3.35 | 3.35 | 67.30 | TARP | TARP | 20.07 | 35.77 | 35.77 | 0.00 | 6 | 0 | 0 | Yes |
| 4 | FRONTLOUNGEFLR1 | 0.0 | 0.00 | 0.00 | 0.00 | -9.95 | -4.16 | 1.68 | 1 | 1 | 1 | -19.86 | -4.87E-002 | -8.28 | -4.88E-002 | 0.00 | 3.35 | 3.35 | 546.70 | TARP | TARP | 163.06 | 94.02 | 79.19 | 14.83 | 7 | 5 | 0 | Yes |
| 5 | RESTROOMFLR1 | 0.0 | 0.00 | 0.00 | 0.00 | -21.84 | -4.16 | 1.68 | 1 | 1 | 1 | -23.82 | -19.86 | -8.28 | -4.88E-002 | 0.00 | 3.35 | 3.35 | 109.34 | TARP | TARP | 32.61 | 13.29 | 13.29 | 0.00 | 6 | 0 | 0 | Yes |
| 6 | MEETINGROOMFLR1 | 0.0 | 0.00 | 0.00 | 0.00 | -31.75 | -4.16 | 1.68 | 1 | 1 | 1 | -36.62 | -26.87 | -8.28 | -4.88E-002 | 0.00 | 3.35 | 3.35 | 269.14 | TARP | TARP | 80.27 | 32.70 | 21.31 | 11.39 | 7 | 3 | 0 | Yes |
| 7 | MECHANICALROOMFLR1 | 0.0 | 0.00 | 0.00 | 0.00 | -38.61 | -4.16 | 1.68 | 1 | 1 | 1 | -40.59 | -36.62 | -8.28 | -4.88E-002 | 0.00 | 3.35 | 3.35 | 109.34 | TARP | TARP | 32.61 | 13.29 | 13.29 | 0.00 | 6 | 0 | 0 | Yes |
| 8 | GUESTROOM101 | 0.0 | 0.00 | 0.00 | 0.00 | -42.57 | -4.16 | 1.68 | 1 | 1 | 1 | -44.55 | -40.59 | -8.28 | -4.88E-002 | 0.00 | 3.35 | 3.35 | 109.34 | TARP | TARP | 32.61 | 13.29 | 9.49 | 3.80 | 6 | 1 | 0 | Yes |
| 9 | GUESTROOM102 | 0.0 | 0.00 | 0.00 | 0.00 | -46.53 | -4.16 | 1.68 | 1 | 1 | 1 | -48.51 | -44.55 | -8.28 | -4.88E-002 | 0.00 | 3.35 | 3.35 | 109.34 | TARP | TARP | 32.61 | 13.29 | 9.49 | 3.80 | 6 | 1 | 0 | Yes |
| 10 | GUESTROOM103 | 0.0 | 0.00 | 0.00 | 0.00 | -50.49 | -4.16 | 1.68 | 1 | 1 | 1 | -52.47 | -48.51 | -8.28 | -4.88E-002 | 0.00 | 3.35 | 3.35 | 109.34 | TARP | TARP | 32.61 | 13.29 | 9.49 | 3.80 | 6 | 1 | 0 | Yes |
| 11 | GUESTROOM104 | 0.0 | 0.00 | 0.00 | 0.00 | -50.49 | -14.22 | 1.68 | 1 | 1 | 1 | -52.47 | -48.51 | -18.34 | -10.11 | 0.00 | 3.35 | 3.35 | 109.33 | TARP | TARP | 32.61 | 13.29 | 9.49 | 3.80 | 6 | 1 | 0 | Yes |
| 12 | GUESTROOM105 | 0.0 | 0.00 | 0.00 | 0.00 | -46.53 | -14.22 | 1.68 | 1 | 1 | 1 | -48.51 | -44.55 | -18.34 | -10.11 | 0.00 | 3.35 | 3.35 | 109.33 | TARP | TARP | 32.61 | 13.29 | 9.49 | 3.80 | 6 | 1 | 0 | Yes |
| 13 | EMPLOYEELOUNGEFLR1 | 0.0 | 0.00 | 0.00 | 0.00 | -42.57 | -14.22 | 1.68 | 1 | 1 | 1 | -44.55 | -40.59 | -18.34 | -10.11 | 0.00 | 3.35 | 3.35 | 109.33 | TARP | TARP | 32.61 | 13.29 | 9.49 | 3.80 | 6 | 1 | 0 | Yes |
| 14 | LAUNDRYROOMFLR1 | 0.0 | 0.00 | 0.00 | 0.00 | -34.64 | -14.22 | 1.68 | 1 | 1 | 1 | -40.59 | -28.70 | -18.34 | -10.11 | 0.00 | 3.35 | 3.35 | 327.99 | TARP | TARP | 97.83 | 39.86 | 28.46 | 11.39 | 7 | 3 | 0 | Yes |
| 15 | ELEVATORCOREFLR1 | 0.0 | 0.00 | 0.00 | 0.00 | -27.79 | -14.22 | 1.68 | 1 | 1 | 1 | -28.70 | -26.87 | -18.34 | -10.11 | 0.00 | 3.35 | 3.35 | 50.46 | TARP | TARP | 15.05 | 6.13 | 6.13 | 0.00 | 6 | 0 | 0 | Yes |
| 16 | EXERCISECENTERFLR1 | 0.0 | 0.00 | 0.00 | 0.00 | -21.84 | -14.22 | 1.68 | 1 | 1 | 1 | -23.82 | -19.86 | -18.34 | -10.11 | 0.00 | 3.35 | 3.35 | 109.33 | TARP | TARP | 32.61 | 13.29 | 9.49 | 3.80 | 6 | 1 | 0 | Yes |
| 17 | FRONTOFFICEFLR1 | 0.0 | 0.00 | 0.00 | 0.00 | -11.94 | -14.22 | 1.68 | 1 | 1 | 1 | -19.86 | -4.01 | -18.34 | -10.11 | 0.00 | 3.35 | 3.35 | 437.33 | TARP | TARP | 130.44 | 53.14 | 37.95 | 15.19 | 7 | 4 | 0 | Yes |
| 18 | FRONTSTAIRSFLR1 | 0.0 | 0.00 | 0.00 | 0.00 | -1.27 | -14.22 | 1.68 | 1 | 1 | 1 | -2.49 | -4.87E-002 | -18.34 | -10.11 | 0.00 | 3.35 | 3.35 | 67.28 | TARP | TARP | 20.07 | 35.77 | 33.82 | 0.00 | 6 | 1 | 0 | Yes |
| 19 | FRONTSTORAGEFLR1 | 0.0 | 0.00 | 0.00 | 0.00 | -3.25 | -14.22 | 1.68 | 1 | 1 | 1 | -4.01 | -2.49 | -18.34 | -10.11 | 0.00 | 3.35 | 3.35 | 42.05 | TARP | TARP | 12.54 | 5.11 | 5.11 | 0.00 | 6 | 0 | 0 | Yes |
| 20 | REARSTAIRSFLR2 | 0.0 | 0.00 | 0.00 | 0.00 | -53.69 | -14.22 | 4.72 | 1 | 1 | 1 | -54.91 | -52.47 | -18.34 | -10.11 | 3.35 | 6.10 | 2.74 | 55.06 | TARP | TARP | 20.07 | 29.27 | 29.27 | 0.00 | 6 | 0 | 0 | Yes |
| 21 | CORRIDORFLR2 | 0.0 | 0.00 | 0.00 | 0.00 | -26.88 | -10.72 | 4.72 | 1 | 1 | 1 | -54.91 | -4.87E-002 | -18.34 | -8.28 | 3.35 | 6.10 | 2.74 | 344.05 | TARP | TARP | 125.42 | 18.39 | 15.77 | 2.62 | 22 | 2 | 0 | Yes |
| 22 | REARSTORAGEFLR2 | 0.0 | 0.00 | 0.00 | 0.00 | -53.69 | -4.16 | 4.72 | 1 | 1 | 1 | -54.91 | -52.47 | -8.28 | -4.88E-002 | 3.35 | 6.10 | 2.74 | 55.07 | TARP | TARP | 20.07 | 29.27 | 29.27 | 0.00 | 6 | 0 | 0 | Yes |
| 23 | GUESTROOM201 | 0.0 | 0.00 | 0.00 | 0.00 | -2.03 | -4.16 | 4.72 | 1 | 1 | 1 | -4.01 | -4.87E-002 | -8.28 | -4.88E-002 | 3.35 | 6.10 | 2.74 | 89.46 | TARP | TARP | 32.61 | 33.45 | 29.64 | 3.81 | 6 | 1 | 0 | Yes |
| 24 | GUESTROOM202_205 | 0.0 | 0.00 | 0.00 | 0.00 | -11.94 | -4.16 | 4.72 | 1 | 1 | 1 | -19.86 | -4.01 | -8.28 | -4.88E-002 | 3.35 | 6.10 | 2.74 | 357.84 | TARP | TARP | 130.45 | 43.48 | 28.24 | 15.24 | 6 | 4 | 0 | Yes |
| 25 | GUESTROOM206_208 | 0.0 | 0.00 | 0.00 | 0.00 | -26.26 | -4.16 | 4.72 | 1 | 1 | 1 | -32.66 | -19.86 | -8.28 | -4.88E-002 | 3.35 | 6.10 | 2.74 | 289.02 | TARP | TARP | 105.36 | 35.12 | 24.09 | 11.02 | 8 | 3 | 0 | Yes |
| 26 | GUESTROOM209_212 | 0.0 | 0.00 | 0.00 | 0.00 | -40.59 | -4.16 | 4.72 | 1 | 1 | 1 | -48.51 | -32.66 | -8.28 | -4.88E-002 | 3.35 | 6.10 | 2.74 | 357.84 | TARP | TARP | 130.45 | 43.48 | 28.24 | 15.24 | 9 | 4 | 0 | Yes |
| 27 | GUESTROOM213 | 0.0 | 0.00 | 0.00 | 0.00 | -50.49 | -4.16 | 4.72 | 1 | 1 | 1 | -52.47 | -48.51 | -8.28 | -4.88E-002 | 3.35 | 6.10 | 2.74 | 89.46 | TARP | TARP | 32.61 | 10.87 | 7.06 | 3.81 | 6 | 1 | 0 | Yes |
| 28 | GUESTROOM214 | 0.0 | 0.00 | 0.00 | 0.00 | -50.49 | -14.22 | 4.72 | 1 | 1 | 1 | -52.47 | -48.51 | -18.34 | -10.11 | 3.35 | 6.10 | 2.74 | 89.45 | TARP | TARP | 32.61 | 10.87 | 7.06 | 3.81 | 6 | 1 | 0 | Yes |
| 29 | GUESTROOM215_218 | 0.0 | 0.00 | 0.00 | 0.00 | -40.59 | -14.22 | 4.72 | 1 | 1 | 1 | -48.51 | -32.66 | -18.34 | -10.11 | 3.35 | 6.10 | 2.74 | 357.81 | TARP | TARP | 130.44 | 43.48 | 28.24 | 15.24 | 8 | 4 | 0 | Yes |
| 30 | ELEVATORCOREFLR2 | 0.0 | 0.00 | 0.00 | 0.00 | -27.79 | -14.22 | 4.72 | 1 | 1 | 1 | -28.70 | -26.87 | -18.34 | -10.11 | 3.35 | 6.10 | 2.74 | 41.29 | TARP | TARP | 15.05 | 5.02 | 5.02 | 0.00 | 6 | 0 | 0 | Yes |
| 31 | GUESTROOM219 | 0.0 | 0.00 | 0.00 | 0.00 | -30.68 | -14.22 | 4.72 | 1 | 1 | 1 | -32.66 | -28.70 | -18.34 | -10.11 | 3.35 | 6.10 | 2.74 | 89.45 | TARP | TARP | 32.61 | 10.87 | 7.06 | 3.81 | 6 | 1 | 0 | Yes |
| 32 | GUESTROOM220_223 | 0.0 | 0.00 | 0.00 | 0.00 | -15.90 | -14.22 | 4.72 | 1 | 1 | 1 | -23.82 | -7.97 | -18.34 | -10.11 | 3.35 | 6.10 | 2.74 | 357.81 | TARP | TARP | 130.44 | 43.48 | 28.24 | 15.24 | 7 | 4 | 0 | Yes |
| 33 | GUESTROOM224 | 0.0 | 0.00 | 0.00 | 0.00 | -5.99 | -14.22 | 4.72 | 1 | 1 | 1 | -7.97 | -4.01 | -18.34 | -10.11 | 3.35 | 6.10 | 2.74 | 89.45 | TARP | TARP | 32.61 | 10.87 | 7.06 | 3.81 | 6 | 1 | 0 | Yes |
| 34 | FRONTSTORAGEFLR2 | 0.0 | 0.00 | 0.00 | 0.00 | -3.25 | -14.22 | 4.72 | 1 | 1 | 1 | -4.01 | -2.49 | -18.34 | -10.11 | 3.35 | 6.10 | 2.74 | 34.40 | TARP | TARP | 12.54 | 4.18 | 4.18 | 0.00 | 6 | 0 | 0 | Yes |
| 35 | FRONTSTAIRSFLR2 | 0.0 | 0.00 | 0.00 | 0.00 | -1.27 | -14.22 | 4.72 | 1 | 1 | 1 | -2.49 | -4.87E-002 | -18.34 | -10.11 | 3.35 | 6.10 | 2.74 | 55.05 | TARP | TARP | 20.07 | 29.26 | 29.26 | 0.00 | 6 | 0 | 0 | Yes |
| 36 | REARSTAIRSFLR3 | 0.0 | 0.00 | 0.00 | 0.00 | -53.69 | -14.22 | 7.47 | 1 | 1 | 1 | -54.91 | -52.47 | -18.34 | -10.11 | 6.10 | 8.84 | 2.74 | 55.06 | TARP | TARP | 20.07 | 29.27 | 29.27 | 0.00 | 6 | 0 | 0 | Yes |
| 37 | CORRIDORFLR3 | 0.0 | 0.00 | 0.00 | 0.00 | -26.88 | -10.72 | 7.47 | 1 | 1 | 1 | -54.91 | -4.87E-002 | -18.34 | -8.28 | 6.10 | 8.84 | 2.74 | 344.05 | TARP | TARP | 125.42 | 18.39 | 15.77 | 2.62 | 22 | 2 | 0 | Yes |
| 38 | REARSTORAGEFLR3 | 0.0 | 0.00 | 0.00 | 0.00 | -53.69 | -4.16 | 7.47 | 1 | 1 | 1 | -54.91 | -52.47 | -8.28 | -4.88E-002 | 6.10 | 8.84 | 2.74 | 55.07 | TARP | TARP | 20.07 | 29.27 | 29.27 | 0.00 | 6 | 0 | 0 | Yes |
| 39 | GUESTROOM301 | 0.0 | 0.00 | 0.00 | 0.00 | -2.03 | -4.16 | 7.47 | 1 | 1 | 1 | -4.01 | -4.87E-002 | -8.28 | -4.88E-002 | 6.10 | 8.84 | 2.74 | 89.46 | TARP | TARP | 32.61 | 33.45 | 29.64 | 3.80 | 6 | 1 | 0 | Yes |
| 40 | GUESTROOM302_305 | 0.0 | 0.00 | 0.00 | 0.00 | -11.94 | -4.16 | 7.47 | 1 | 1 | 1 | -19.86 | -4.01 | -8.28 | -4.88E-002 | 6.10 | 8.84 | 2.74 | 357.84 | TARP | TARP | 130.45 | 43.48 | 28.27 | 15.21 | 6 | 4 | 0 | Yes |
| 41 | GUESTROOM306_308 | 0.0 | 0.00 | 0.00 | 0.00 | -26.26 | -4.16 | 7.47 | 1 | 1 | 1 | -32.66 | -19.86 | -8.28 | -4.88E-002 | 6.10 | 8.84 | 2.74 | 289.02 | TARP | TARP | 105.36 | 35.12 | 24.11 | 11.01 | 6 | 3 | 0 | Yes |
| 42 | GUESTROOM309_312 | 0.0 | 0.00 | 0.00 | 0.00 | -40.59 | -4.16 | 7.47 | 1 | 1 | 1 | -48.51 | -32.66 | -8.28 | -4.88E-002 | 6.10 | 8.84 | 2.74 | 357.84 | TARP | TARP | 130.45 | 43.48 | 28.27 | 15.21 | 6 | 4 | 0 | Yes |
| 43 | GUESTROOM313 | 0.0 | 0.00 | 0.00 | 0.00 | -50.49 | -4.16 | 7.47 | 1 | 1 | 1 | -52.47 | -48.51 | -8.28 | -4.88E-002 | 6.10 | 8.84 | 2.74 | 89.46 | TARP | TARP | 32.61 | 10.87 | 7.07 | 3.80 | 6 | 1 | 0 | Yes |
| 44 | GUESTROOM314 | 0.0 | 0.00 | 0.00 | 0.00 | -50.49 | -14.22 | 7.47 | 1 | 1 | 1 | -52.47 | -48.51 | -18.34 | -10.11 | 6.10 | 8.84 | 2.74 | 89.45 | TARP | TARP | 32.61 | 10.87 | 7.07 | 3.80 | 6 | 1 | 0 | Yes |
| 45 | GUESTROOM315_318 | 0.0 | 0.00 | 0.00 | 0.00 | -40.59 | -14.22 | 7.47 | 1 | 1 | 1 | -48.51 | -32.66 | -18.34 | -10.11 | 6.10 | 8.84 | 2.74 | 357.81 | TARP | TARP | 130.44 | 43.48 | 28.27 | 15.21 | 6 | 4 | 0 | Yes |
| 46 | ELEVATORCOREFLR3 | 0.0 | 0.00 | 0.00 | 0.00 | -27.79 | -14.22 | 7.47 | 1 | 1 | 1 | -28.70 | -26.87 | -18.34 | -10.11 | 6.10 | 8.84 | 2.74 | 41.29 | TARP | TARP | 15.05 | 5.02 | 5.02 | 0.00 | 6 | 0 | 0 | Yes |
| 47 | GUESTROOM319 | 0.0 | 0.00 | 0.00 | 0.00 | -30.68 | -14.22 | 7.47 | 1 | 1 | 1 | -32.66 | -28.70 | -18.34 | -10.11 | 6.10 | 8.84 | 2.74 | 89.45 | TARP | TARP | 32.61 | 10.87 | 7.07 | 3.80 | 6 | 1 | 0 | Yes |
| 48 | GUESTROOM320_323 | 0.0 | 0.00 | 0.00 | 0.00 | -15.90 | -14.22 | 7.47 | 1 | 1 | 1 | -23.82 | -7.97 | -18.34 | -10.11 | 6.10 | 8.84 | 2.74 | 357.81 | TARP | TARP | 130.44 | 43.48 | 28.27 | 15.21 | 6 | 4 | 0 | Yes |
| 49 | GUESTROOM324 | 0.0 | 0.00 | 0.00 | 0.00 | -5.99 | -14.22 | 7.47 | 1 | 1 | 1 | -7.97 | -4.01 | -18.34 | -10.11 | 6.10 | 8.84 | 2.74 | 89.45 | TARP | TARP | 32.61 | 10.87 | 7.07 | 3.80 | 6 | 1 | 0 | Yes |
| 50 | FRONTSTORAGEFLR3 | 0.0 | 0.00 | 0.00 | 0.00 | -3.25 | -14.22 | 7.47 | 1 | 1 | 1 | -4.01 | -2.49 | -18.34 | -10.11 | 6.10 | 8.84 | 2.74 | 34.40 | TARP | TARP | 12.54 | 4.18 | 4.18 | 0.00 | 6 | 0 | 0 | Yes |
| 51 | FRONTSTAIRSFLR3 | 0.0 | 0.00 | 0.00 | 0.00 | -1.27 | -14.22 | 7.47 | 1 | 1 | 1 | -2.49 | -4.87E-002 | -18.34 | -10.11 | 6.10 | 8.84 | 2.74 | 55.05 | TARP | TARP | 20.07 | 29.26 | 29.26 | 0.00 | 6 | 0 | 0 | Yes |
| 52 | REARSTAIRSFLR4 | 0.0 | 0.00 | 0.00 | 0.00 | -53.69 | -14.22 | 10.21 | 1 | 1 | 1 | -54.91 | -52.47 | -18.34 | -10.11 | 8.84 | 11.58 | 2.74 | 55.06 | TARP | TARP | 20.07 | 29.27 | 29.27 | 0.00 | 6 | 0 | 0 | Yes |
| 53 | CORRIDORFLR4 | 0.0 | 0.00 | 0.00 | 0.00 | -26.88 | -10.72 | 10.21 | 1 | 1 | 1 | -54.91 | -4.87E-002 | -18.34 | -8.28 | 8.84 | 11.58 | 2.74 | 344.05 | TARP | TARP | 125.42 | 18.39 | 15.77 | 2.62 | 22 | 2 | 0 | Yes |
| 54 | REARSTORAGEFLR4 | 0.0 | 0.00 | 0.00 | 0.00 | -53.69 | -4.16 | 10.21 | 1 | 1 | 1 | -54.91 | -52.47 | -8.28 | -4.88E-002 | 8.84 | 11.58 | 2.74 | 55.07 | TARP | TARP | 20.07 | 29.27 | 29.27 | 0.00 | 6 | 0 | 0 | Yes |
| 55 | GUESTROOM401 | 0.0 | 0.00 | 0.00 | 0.00 | -2.03 | -4.16 | 10.21 | 1 | 1 | 1 | -4.01 | -4.87E-002 | -8.28 | -4.88E-002 | 8.84 | 11.58 | 2.74 | 89.46 | TARP | TARP | 32.61 | 33.45 | 29.64 | 3.80 | 6 | 1 | 0 | Yes |
| 56 | GUESTROOM402_405 | 0.0 | 0.00 | 0.00 | 0.00 | -11.94 | -4.16 | 10.21 | 1 | 1 | 1 | -19.86 | -4.01 | -8.28 | -4.88E-002 | 8.84 | 11.58 | 2.74 | 357.84 | TARP | TARP | 130.45 | 43.48 | 28.27 | 15.21 | 6 | 4 | 0 | Yes |
| 57 | GUESTROOM406_408 | 0.0 | 0.00 | 0.00 | 0.00 | -26.26 | -4.16 | 10.21 | 1 | 1 | 1 | -32.66 | -19.86 | -8.28 | -4.88E-002 | 8.84 | 11.58 | 2.74 | 289.02 | TARP | TARP | 105.36 | 35.12 | 24.11 | 11.01 | 6 | 3 | 0 | Yes |
| 58 | GUESTROOM409_412 | 0.0 | 0.00 | 0.00 | 0.00 | -40.59 | -4.16 | 10.21 | 1 | 1 | 1 | -48.51 | -32.66 | -8.28 | -4.88E-002 | 8.84 | 11.58 | 2.74 | 357.84 | TARP | TARP | 130.45 | 43.48 | 28.27 | 15.21 | 6 | 4 | 0 | Yes |
| 59 | GUESTROOM413 | 0.0 | 0.00 | 0.00 | 0.00 | -50.49 | -4.16 | 10.21 | 1 | 1 | 1 | -52.47 | -48.51 | -8.28 | -4.88E-002 | 8.84 | 11.58 | 2.74 | 89.46 | TARP | TARP | 32.61 | 10.87 | 7.07 | 3.80 | 6 | 1 | 0 | Yes |
| 60 | GUESTROOM414 | 0.0 | 0.00 | 0.00 | 0.00 | -50.49 | -14.22 | 10.21 | 1 | 1 | 1 | -52.47 | -48.51 | -18.34 | -10.11 | 8.84 | 11.58 | 2.74 | 89.45 | TARP | TARP | 32.61 | 10.87 | 7.07 | 3.80 | 6 | 1 | 0 | Yes |
| 61 | GUESTROOM415_418 | 0.0 | 0.00 | 0.00 | 0.00 | -40.59 | -14.22 | 10.21 | 1 | 1 | 1 | -48.51 | -32.66 | -18.34 | -10.11 | 8.84 | 11.58 | 2.74 | 357.81 | TARP | TARP | 130.44 | 43.48 | 28.27 | 15.21 | 6 | 4 | 0 | Yes |
| 62 | ELEVATORCOREFLR4 | 0.0 | 0.00 | 0.00 | 0.00 | -27.79 | -14.22 | 10.21 | 1 | 1 | 1 | -28.70 | -26.87 | -18.34 | -10.11 | 8.84 | 11.58 | 2.74 | 41.29 | TARP | TARP | 15.05 | 5.02 | 5.02 | 0.00 | 6 | 0 | 0 | Yes |
| 63 | GUESTROOM419 | 0.0 | 0.00 | 0.00 | 0.00 | -30.68 | -14.22 | 10.21 | 1 | 1 | 1 | -32.66 | -28.70 | -18.34 | -10.11 | 8.84 | 11.58 | 2.74 | 89.45 | TARP | TARP | 32.61 | 10.87 | 7.07 | 3.80 | 6 | 1 | 0 | Yes |
| 64 | GUESTROOM420_423 | 0.0 | 0.00 | 0.00 | 0.00 | -15.90 | -14.22 | 10.21 | 1 | 1 | 1 | -23.82 | -7.97 | -18.34 | -10.11 | 8.84 | 11.58 | 2.74 | 357.81 | TARP | TARP | 130.44 | 43.48 | 28.27 | 15.21 | 6 | 4 | 0 | Yes |
| 65 | GUESTROOM424 | 0.0 | 0.00 | 0.00 | 0.00 | -5.99 | -14.22 | 10.21 | 1 | 1 | 1 | -7.97 | -4.01 | -18.34 | -10.11 | 8.84 | 11.58 | 2.74 | 89.45 | TARP | TARP | 32.61 | 10.87 | 7.07 | 3.80 | 6 | 1 | 0 | Yes |
| 66 | FRONTSTORAGEFLR4 | 0.0 | 0.00 | 0.00 | 0.00 | -3.25 | -14.22 | 10.21 | 1 | 1 | 1 | -4.01 | -2.49 | -18.34 | -10.11 | 8.84 | 11.58 | 2.74 | 34.40 | TARP | TARP | 12.54 | 4.18 | 4.18 | 0.00 | 6 | 0 | 0 | Yes |
| 67 | FRONTSTAIRSFLR4 | 0.0 | 0.00 | 0.00 | 0.00 | -1.27 | -14.22 | 10.21 | 1 | 1 | 1 | -2.49 | -4.87E-002 | -18.34 | -10.11 | 8.84 | 11.58 | 2.74 | 55.05 | TARP | TARP | 20.07 | 29.26 | 29.26 | 0.00 | 6 | 0 | 0 | Yes |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | REARSTAIRSFLR1 | 20.07 | 1.1 | 18.585 | 5.381E-002 | 6.458 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.458 | No |
| 2 | CORRIDORFLR1 | 150.51 | 8.1 | 18.581 | 5.382E-002 | 5.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.382 | No |
| 3 | REARSTORAGEFLR1 | 20.07 | 0.4 | 46.466 | 2.152E-002 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
| 4 | FRONTLOUNGEFLR1 | 163.06 | 53.0 | 3.077 | 0.325 | 13.993 | 26.060 | 0.000 | 0.000 | 0.000 | 0.000 | 40.053 | No |
| 5 | RESTROOMFLR1 | 32.61 | 1.8 | 18.582 | 5.382E-002 | 9.688 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 9.688 | No |
| 6 | MEETINGROOMFLR1 | 80.27 | 43.0 | 1.867 | 0.536 | 13.993 | 6.180 | 0.000 | 0.000 | 0.000 | 0.000 | 20.173 | No |
| 7 | MECHANICALROOMFLR1 | 32.61 | 0.5 | 61.881 | 1.616E-002 | 16.146 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 16.146 | No |
| 8 | GUESTROOM101 | 32.61 | 1.5 | 21.741 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 9 | GUESTROOM102 | 32.61 | 1.5 | 21.741 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 10 | GUESTROOM103 | 32.61 | 1.5 | 21.741 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 11 | GUESTROOM104 | 32.61 | 1.5 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 12 | GUESTROOM105 | 32.61 | 1.5 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 13 | EMPLOYEELOUNGEFLR1 | 32.61 | 18.0 | 1.812 | 0.552 | 12.917 | 21.510 | 0.000 | 0.000 | 0.000 | 0.000 | 34.427 | No |
| 14 | LAUNDRYROOMFLR1 | 97.83 | 10.5 | 9.290 | 0.108 | 6.458 | 27.693 | 409.867 | 0.000 | 0.000 | 0.000 | 444.018 | No |
| 15 | ELEVATORCOREFLR1 | 15.05 | 0.2 | 61.935 | 1.615E-002 | 0.000 | 5331.989 | 0.000 | 0.000 | 0.000 | 0.000 | 5331.989 | No |
| 16 | EXERCISECENTERFLR1 | 32.61 | 7.0 | 4.658 | 0.215 | 9.688 | 18.590 | 0.000 | 0.000 | 0.000 | 0.000 | 28.278 | No |
| 17 | FRONTOFFICEFLR1 | 130.44 | 10.0 | 13.044 | 7.667E-002 | 11.840 | 13.780 | 0.000 | 0.000 | 0.000 | 0.000 | 25.620 | No |
| 18 | FRONTSTAIRSFLR1 | 20.07 | 1.1 | 18.581 | 5.382E-002 | 6.458 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.458 | No |
| 19 | FRONTSTORAGEFLR1 | 12.54 | 0.3 | 46.452 | 2.153E-002 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
| 20 | REARSTAIRSFLR2 | 20.07 | 1.1 | 18.585 | 5.381E-002 | 6.458 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.458 | No |
| 21 | CORRIDORFLR2 | 125.42 | 6.8 | 18.581 | 5.382E-002 | 5.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.382 | No |
| 22 | REARSTORAGEFLR2 | 20.07 | 0.4 | 46.466 | 2.152E-002 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
| 23 | GUESTROOM201 | 32.61 | 1.5 | 21.741 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 24 | GUESTROOM202_205 | 130.45 | 6.0 | 21.741 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 25 | GUESTROOM206_208 | 105.36 | 4.5 | 23.413 | 4.271E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 26 | GUESTROOM209_212 | 130.45 | 6.0 | 21.741 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 27 | GUESTROOM213 | 32.61 | 1.5 | 21.741 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 28 | GUESTROOM214 | 32.61 | 1.5 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 29 | GUESTROOM215_218 | 130.44 | 6.0 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 30 | ELEVATORCOREFLR2 | 15.05 | 0.2 | 61.935 | 1.615E-002 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
| 31 | GUESTROOM219 | 32.61 | 1.5 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 32 | GUESTROOM220_223 | 130.44 | 6.0 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 33 | GUESTROOM224 | 32.61 | 1.5 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 34 | FRONTSTORAGEFLR2 | 12.54 | 0.3 | 46.452 | 2.153E-002 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
| 35 | FRONTSTAIRSFLR2 | 20.07 | 1.1 | 18.581 | 5.382E-002 | 6.458 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.458 | No |
| 36 | REARSTAIRSFLR3 | 20.07 | 1.1 | 18.585 | 5.381E-002 | 6.458 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.458 | No |
| 37 | CORRIDORFLR3 | 125.42 | 6.8 | 18.581 | 5.382E-002 | 5.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.382 | No |
| 38 | REARSTORAGEFLR3 | 20.07 | 0.4 | 46.466 | 2.152E-002 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
| 39 | GUESTROOM301 | 32.61 | 1.5 | 21.741 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 40 | GUESTROOM302_305 | 130.45 | 6.0 | 21.741 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 41 | GUESTROOM306_308 | 105.36 | 4.5 | 23.413 | 4.271E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 42 | GUESTROOM309_312 | 130.45 | 6.0 | 21.741 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 43 | GUESTROOM313 | 32.61 | 1.5 | 21.741 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 44 | GUESTROOM314 | 32.61 | 1.5 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 45 | GUESTROOM315_318 | 130.44 | 6.0 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 46 | ELEVATORCOREFLR3 | 15.05 | 0.2 | 61.935 | 1.615E-002 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
| 47 | GUESTROOM319 | 32.61 | 1.5 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 48 | GUESTROOM320_323 | 130.44 | 6.0 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 49 | GUESTROOM324 | 32.61 | 1.5 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 50 | FRONTSTORAGEFLR3 | 12.54 | 0.3 | 46.452 | 2.153E-002 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
| 51 | FRONTSTAIRSFLR3 | 20.07 | 1.1 | 18.581 | 5.382E-002 | 6.458 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.458 | No |
| 52 | REARSTAIRSFLR4 | 20.07 | 1.1 | 18.585 | 5.381E-002 | 6.458 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.458 | No |
| 53 | CORRIDORFLR4 | 125.42 | 6.8 | 18.581 | 5.382E-002 | 5.382 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 5.382 | No |
| 54 | REARSTORAGEFLR4 | 20.07 | 0.4 | 46.466 | 2.152E-002 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
| 55 | GUESTROOM401 | 32.61 | 1.5 | 21.741 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 56 | GUESTROOM402_405 | 130.45 | 6.0 | 21.741 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 57 | GUESTROOM406_408 | 105.36 | 4.5 | 23.413 | 4.271E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 58 | GUESTROOM409_412 | 130.45 | 6.0 | 21.741 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 59 | GUESTROOM413 | 32.61 | 1.5 | 21.741 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 60 | GUESTROOM414 | 32.61 | 1.5 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 61 | GUESTROOM415_418 | 130.44 | 6.0 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 62 | ELEVATORCOREFLR4 | 15.05 | 0.2 | 61.935 | 1.615E-002 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
| 63 | GUESTROOM419 | 32.61 | 1.5 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 64 | GUESTROOM420_423 | 130.44 | 6.0 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 65 | GUESTROOM424 | 32.61 | 1.5 | 21.739 | 4.600E-002 | 12.271 | 11.893 | 0.000 | 0.000 | 0.000 | 0.000 | 24.164 | No |
| 66 | FRONTSTORAGEFLR4 | 12.54 | 0.3 | 46.452 | 2.153E-002 | 8.611 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 8.611 | No |
| 67 | FRONTSTAIRSFLR4 | 20.07 | 1.1 | 18.581 | 5.382E-002 | 6.458 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 6.458 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | CORRIDORFLR1_PEOPLE | LOBBY_OCC_SCH | CORRIDORFLR1 | 150.51 | 8.1 | 8.1 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 |
| 2 | CORRIDORFLR2_PEOPLE | LOBBY_OCC_SCH | CORRIDORFLR2 | 125.42 | 6.8 | 6.8 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 |
| 3 | CORRIDORFLR3_PEOPLE | LOBBY_OCC_SCH | CORRIDORFLR3 | 125.42 | 6.8 | 6.8 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 |
| 4 | CORRIDORFLR4_PEOPLE | LOBBY_OCC_SCH | CORRIDORFLR4 | 125.42 | 6.8 | 6.8 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 |
| 5 | ELEVATORCOREFLR1_PEOPLE | ALWAYSOFF | ELEVATORCOREFLR1 | 15.05 | 0.2 | 0.2 | 1.615E-002 | 61.935 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 6 | ELEVATORCOREFLR2_PEOPLE | ALWAYSOFF | ELEVATORCOREFLR2 | 15.05 | 0.2 | 0.2 | 1.615E-002 | 61.935 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 7 | ELEVATORCOREFLR3_PEOPLE | ALWAYSOFF | ELEVATORCOREFLR3 | 15.05 | 0.2 | 0.2 | 1.615E-002 | 61.935 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 8 | ELEVATORCOREFLR4_PEOPLE | ALWAYSOFF | ELEVATORCOREFLR4 | 15.05 | 0.2 | 0.2 | 1.615E-002 | 61.935 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 9 | EMPLOYEELOUNGEFLR1_PEOPLE | EMPLOYEELOUNGE_OCC_SCH | EMPLOYEELOUNGEFLR1 | 32.61 | 18.0 | 18.0 | 0.552 | 1.812 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 18 |
| 10 | EXERCISECENTERFLR1_PEOPLE | EXERCISECENTER_OCC_SCH | EXERCISECENTERFLR1 | 32.61 | 7.0 | 7.0 | 0.215 | 4.658 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 7 |
| 11 | FRONTLOUNGEFLR1_PEOPLE | LOBBY_OCC_SCH | FRONTLOUNGEFLR1 | 163.06 | 53.0 | 53.0 | 0.325 | 3.077 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 53 |
| 12 | FRONTOFFICEFLR1_PEOPLE | OFFICE_OCC_W_SB_SCH | FRONTOFFICEFLR1 | 130.44 | 10.0 | 10.0 | 7.667E-002 | 13.044 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 10 |
| 13 | FRONTSTAIRSFLR1_PEOPLE | ALWAYSOFF | FRONTSTAIRSFLR1 | 20.07 | 1.1 | 1.1 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 14 | FRONTSTAIRSFLR2_PEOPLE | ALWAYSOFF | FRONTSTAIRSFLR2 | 20.07 | 1.1 | 1.1 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 15 | FRONTSTAIRSFLR3_PEOPLE | ALWAYSOFF | FRONTSTAIRSFLR3 | 20.07 | 1.1 | 1.1 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 16 | FRONTSTAIRSFLR4_PEOPLE | ALWAYSOFF | FRONTSTAIRSFLR4 | 20.07 | 1.1 | 1.1 | 5.382E-002 | 18.581 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 17 | FRONTSTORAGEFLR1_PEOPLE | ALWAYSOFF | FRONTSTORAGEFLR1 | 12.54 | 0.3 | 0.3 | 2.153E-002 | 46.452 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 18 | FRONTSTORAGEFLR2_PEOPLE | ALWAYSOFF | FRONTSTORAGEFLR2 | 12.54 | 0.3 | 0.3 | 2.153E-002 | 46.452 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 19 | FRONTSTORAGEFLR3_PEOPLE | ALWAYSOFF | FRONTSTORAGEFLR3 | 12.54 | 0.3 | 0.3 | 2.153E-002 | 46.452 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 20 | FRONTSTORAGEFLR4_PEOPLE | ALWAYSOFF | FRONTSTORAGEFLR4 | 12.54 | 0.3 | 0.3 | 2.153E-002 | 46.452 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 21 | GUESTROOM101_PEOPLE | ALWAYSOFF | GUESTROOM101 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.741 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 22 | GUESTROOM102_PEOPLE | ALWAYSOFF | GUESTROOM102 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.741 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 23 | GUESTROOM103_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM103 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.741 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 24 | GUESTROOM104_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM104 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 25 | GUESTROOM105_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM105 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 26 | GUESTROOM201_PEOPLE | ALWAYSOFF | GUESTROOM201 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.741 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 27 | GUESTROOM202_205_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM202_205 | 130.45 | 6.0 | 6.0 | 4.600E-002 | 21.741 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 |
| 28 | GUESTROOM206_208_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM206_208 | 105.36 | 4.5 | 4.5 | 4.271E-002 | 23.413 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 5 |
| 29 | GUESTROOM209_212_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM209_212 | 130.45 | 6.0 | 6.0 | 4.600E-002 | 21.741 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 |
| 30 | GUESTROOM213_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM213 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.741 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 31 | GUESTROOM214_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM214 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 32 | GUESTROOM215_218_PEOPLE | ALWAYSOFF | GUESTROOM215_218 | 130.44 | 6.0 | 6.0 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 33 | GUESTROOM219_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM219 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 34 | GUESTROOM220_223_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM220_223 | 130.44 | 6.0 | 6.0 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 |
| 35 | GUESTROOM224_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM224 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 36 | GUESTROOM301_PEOPLE | ALWAYSOFF | GUESTROOM301 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.741 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 37 | GUESTROOM302_305_PEOPLE | ALWAYSOFF | GUESTROOM302_305 | 130.45 | 6.0 | 6.0 | 4.600E-002 | 21.741 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 38 | GUESTROOM306_308_PEOPLE | ALWAYSOFF | GUESTROOM306_308 | 105.36 | 4.5 | 4.5 | 4.271E-002 | 23.413 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 39 | GUESTROOM309_312_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM309_312 | 130.45 | 6.0 | 6.0 | 4.600E-002 | 21.741 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 |
| 40 | GUESTROOM313_PEOPLE | ALWAYSOFF | GUESTROOM313 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.741 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 41 | GUESTROOM314_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM314 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 42 | GUESTROOM315_318_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM315_318 | 130.44 | 6.0 | 6.0 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 |
| 43 | GUESTROOM319_PEOPLE | ALWAYSOFF | GUESTROOM319 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 44 | GUESTROOM320_323_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM320_323 | 130.44 | 6.0 | 6.0 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 |
| 45 | GUESTROOM324_PEOPLE | ALWAYSOFF | GUESTROOM324 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 46 | GUESTROOM401_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM401 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.741 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 47 | GUESTROOM402_405_PEOPLE | ALWAYSOFF | GUESTROOM402_405 | 130.45 | 6.0 | 6.0 | 4.600E-002 | 21.741 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 48 | GUESTROOM406_408_PEOPLE | ALWAYSOFF | GUESTROOM406_408 | 105.36 | 4.5 | 4.5 | 4.271E-002 | 23.413 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 49 | GUESTROOM409_412_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM409_412 | 130.45 | 6.0 | 6.0 | 4.600E-002 | 21.741 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 |
| 50 | GUESTROOM413_PEOPLE | ALWAYSOFF | GUESTROOM413 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.741 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 51 | GUESTROOM414_PEOPLE | ALWAYSOFF | GUESTROOM414 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 52 | GUESTROOM415_418_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM415_418 | 130.44 | 6.0 | 6.0 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 |
| 53 | GUESTROOM419_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM419 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 54 | GUESTROOM420_423_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM420_423 | 130.44 | 6.0 | 6.0 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 6 |
| 55 | GUESTROOM424_PEOPLE | GUESTROOM_OCC_SCH | GUESTROOM424 | 32.61 | 1.5 | 1.5 | 4.600E-002 | 21.739 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 56 | LAUNDRYROOMFLR1_PEOPLE | LAUNDRYROOM_OCC_SCH | LAUNDRYROOMFLR1 | 97.83 | 10.5 | 10.5 | 0.108 | 9.290 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 |
| 57 | MECHANICALROOMFLR1_PEOPLE | ALWAYSOFF | MECHANICALROOMFLR1 | 32.61 | 0.5 | 0.5 | 1.616E-002 | 61.881 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 58 | MEETINGROOMFLR1_PEOPLE | MEETINGROOM_OCC_W_SB_SCH | MEETINGROOMFLR1 | 80.27 | 43.0 | 43.0 | 0.536 | 1.867 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 43 |
| 59 | REARSTAIRSFLR1_PEOPLE | ALWAYSOFF | REARSTAIRSFLR1 | 20.07 | 1.1 | 1.1 | 5.381E-002 | 18.585 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 60 | REARSTAIRSFLR2_PEOPLE | ALWAYSOFF | REARSTAIRSFLR2 | 20.07 | 1.1 | 1.1 | 5.381E-002 | 18.585 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 61 | REARSTAIRSFLR3_PEOPLE | ALWAYSOFF | REARSTAIRSFLR3 | 20.07 | 1.1 | 1.1 | 5.381E-002 | 18.585 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 62 | REARSTAIRSFLR4_PEOPLE | ALWAYSOFF | REARSTAIRSFLR4 | 20.07 | 1.1 | 1.1 | 5.381E-002 | 18.585 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 63 | REARSTORAGEFLR1_PEOPLE | ALWAYSOFF | REARSTORAGEFLR1 | 20.07 | 0.4 | 0.4 | 2.152E-002 | 46.466 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 64 | REARSTORAGEFLR2_PEOPLE | ALWAYSOFF | REARSTORAGEFLR2 | 20.07 | 0.4 | 0.4 | 2.152E-002 | 46.466 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 65 | REARSTORAGEFLR3_PEOPLE | ALWAYSOFF | REARSTORAGEFLR3 | 20.07 | 0.4 | 0.4 | 2.152E-002 | 46.466 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 66 | REARSTORAGEFLR4_PEOPLE | ALWAYSOFF | REARSTORAGEFLR4 | 20.07 | 0.4 | 0.4 | 2.152E-002 | 46.466 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 0 |
| 67 | RESTROOMFLR1_PEOPLE | LOBBY_OCC_SCH | RESTROOMFLR1 | 32.61 | 1.8 | 1.8 | 5.382E-002 | 18.582 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | CORRIDORFLR1_LIGHTS | LTG_SCH_CORRIDOR | CORRIDORFLR1 | 150.51 | 8.1 | 810.015 | 5.382 | 100.002 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 810.015 |
| 2 | CORRIDORFLR2_LIGHTS | LTG_SCH_CORRIDOR | CORRIDORFLR2 | 125.42 | 6.8 | 675.005 | 5.382 | 100.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 675.005 |
| 3 | CORRIDORFLR3_LIGHTS | LTG_SCH_CORRIDOR | CORRIDORFLR3 | 125.42 | 6.8 | 675.005 | 5.382 | 100.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 675.005 |
| 4 | CORRIDORFLR4_LIGHTS | LTG_SCH_CORRIDOR | CORRIDORFLR4 | 125.42 | 6.8 | 675.005 | 5.382 | 100.001 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 675.005 |
| 5 | ELEVATORCOREFLR1_LIGHTS | LTG_SCH_ELEVATOR | ELEVATORCOREFLR1 | 15.05 | 0.2 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 6 | ELEVATORCOREFLR2_LIGHTS | LTG_SCH_ELEVATOR | ELEVATORCOREFLR2 | 15.05 | 0.2 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 7 | ELEVATORCOREFLR3_LIGHTS | LTG_SCH_ELEVATOR | ELEVATORCOREFLR3 | 15.05 | 0.2 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 8 | ELEVATORCOREFLR4_LIGHTS | LTG_SCH_ELEVATOR | ELEVATORCOREFLR4 | 15.05 | 0.2 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 9 | EMPLOYEELOUNGEFLR1_LIGHTS | LTG_SCH_LOUNGE | EMPLOYEELOUNGEFLR1 | 32.61 | 18.0 | 421.200 | 12.917 | 23.400 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 421.200 |
| 10 | EXERCISECENTERFLR1_LIGHTS | LTG_SCH_EXERCISE | EXERCISECENTERFLR1 | 32.61 | 7.0 | 315.900 | 9.688 | 45.129 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 315.900 |
| 11 | FRONTLOUNGEFLR1_LIGHTS | LTG_SCH_LOBBY | FRONTLOUNGEFLR1 | 163.06 | 53.0 | 2281.660 | 13.993 | 43.050 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2281.660 |
| 12 | FRONTOFFICEFLR1_LIGHTS | LTG_SCH_OFFICE | FRONTOFFICEFLR1 | 130.44 | 10.0 | 1544.399 | 11.840 | 154.440 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1544.399 |
| 13 | FRONTSTAIRSFLR1_LIGHTS | LTG_SCH_STAIR | FRONTSTAIRSFLR1 | 20.07 | 1.1 | 129.600 | 6.458 | 120.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 129.600 |
| 14 | FRONTSTAIRSFLR2_LIGHTS | LTG_SCH_STAIR | FRONTSTAIRSFLR2 | 20.07 | 1.1 | 129.600 | 6.458 | 120.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 129.600 |
| 15 | FRONTSTAIRSFLR3_LIGHTS | LTG_SCH_STAIR | FRONTSTAIRSFLR3 | 20.07 | 1.1 | 129.600 | 6.458 | 120.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 129.600 |
| 16 | FRONTSTAIRSFLR4_LIGHTS | LTG_SCH_STAIR | FRONTSTAIRSFLR4 | 20.07 | 1.1 | 129.600 | 6.458 | 120.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 129.600 |
| 17 | FRONTSTORAGEFLR1_LIGHTS | LTG_SCH_STORAGE | FRONTSTORAGEFLR1 | 12.54 | 0.3 | 108.000 | 8.611 | 400.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.000 |
| 18 | FRONTSTORAGEFLR2_LIGHTS | LTG_SCH_STORAGE | FRONTSTORAGEFLR2 | 12.54 | 0.3 | 108.000 | 8.611 | 400.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.000 |
| 19 | FRONTSTORAGEFLR3_LIGHTS | LTG_SCH_STORAGE | FRONTSTORAGEFLR3 | 12.54 | 0.3 | 108.000 | 8.611 | 400.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.000 |
| 20 | FRONTSTORAGEFLR4_LIGHTS | LTG_SCH_STORAGE | FRONTSTORAGEFLR4 | 12.54 | 0.3 | 108.000 | 8.611 | 400.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 108.000 |
| 21 | GUESTROOM101_LIGHTS | ALWAYSOFF | GUESTROOM101 | 32.61 | 1.5 | 400.168 | 12.271 | 266.779 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 22 | GUESTROOM102_LIGHTS | ALWAYSOFF | GUESTROOM102 | 32.61 | 1.5 | 400.168 | 12.271 | 266.779 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 23 | GUESTROOM103_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM103 | 32.61 | 1.5 | 400.168 | 12.271 | 266.779 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.168 |
| 24 | GUESTROOM104_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM104 | 32.61 | 1.5 | 400.140 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.140 |
| 25 | GUESTROOM105_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM105 | 32.61 | 1.5 | 400.140 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.140 |
| 26 | GUESTROOM201_LIGHTS | ALWAYSOFF | GUESTROOM201 | 32.61 | 1.5 | 400.168 | 12.271 | 266.779 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 27 | GUESTROOM202_205_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM202_205 | 130.45 | 6.0 | 1600.673 | 12.271 | 266.779 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1600.673 |
| 28 | GUESTROOM206_208_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM206_208 | 105.36 | 4.5 | 1292.851 | 12.271 | 287.300 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1292.851 |
| 29 | GUESTROOM209_212_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM209_212 | 130.45 | 6.0 | 1600.673 | 12.271 | 266.779 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1600.673 |
| 30 | GUESTROOM213_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM213 | 32.61 | 1.5 | 400.168 | 12.271 | 266.779 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.168 |
| 31 | GUESTROOM214_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM214 | 32.61 | 1.5 | 400.140 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.140 |
| 32 | GUESTROOM215_218_LIGHTS | ALWAYSOFF | GUESTROOM215_218 | 130.44 | 6.0 | 1600.559 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 33 | GUESTROOM219_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM219 | 32.61 | 1.5 | 400.140 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.140 |
| 34 | GUESTROOM220_223_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM220_223 | 130.44 | 6.0 | 1600.559 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1600.559 |
| 35 | GUESTROOM224_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM224 | 32.61 | 1.5 | 400.140 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.140 |
| 36 | GUESTROOM301_LIGHTS | ALWAYSOFF | GUESTROOM301 | 32.61 | 1.5 | 400.168 | 12.271 | 266.779 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 37 | GUESTROOM302_305_LIGHTS | ALWAYSOFF | GUESTROOM302_305 | 130.45 | 6.0 | 1600.673 | 12.271 | 266.779 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 38 | GUESTROOM306_308_LIGHTS | ALWAYSOFF | GUESTROOM306_308 | 105.36 | 4.5 | 1292.851 | 12.271 | 287.300 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 39 | GUESTROOM309_312_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM309_312 | 130.45 | 6.0 | 1600.673 | 12.271 | 266.779 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1600.673 |
| 40 | GUESTROOM313_LIGHTS | ALWAYSOFF | GUESTROOM313 | 32.61 | 1.5 | 400.168 | 12.271 | 266.779 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 41 | GUESTROOM314_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM314 | 32.61 | 1.5 | 400.140 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.140 |
| 42 | GUESTROOM315_318_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM315_318 | 130.44 | 6.0 | 1600.559 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1600.559 |
| 43 | GUESTROOM319_LIGHTS | ALWAYSOFF | GUESTROOM319 | 32.61 | 1.5 | 400.140 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 44 | GUESTROOM320_323_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM320_323 | 130.44 | 6.0 | 1600.559 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1600.559 |
| 45 | GUESTROOM324_LIGHTS | ALWAYSOFF | GUESTROOM324 | 32.61 | 1.5 | 400.140 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 46 | GUESTROOM401_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM401 | 32.61 | 1.5 | 400.168 | 12.271 | 266.779 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.168 |
| 47 | GUESTROOM402_405_LIGHTS | ALWAYSOFF | GUESTROOM402_405 | 130.45 | 6.0 | 1600.673 | 12.271 | 266.779 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 48 | GUESTROOM406_408_LIGHTS | ALWAYSOFF | GUESTROOM406_408 | 105.36 | 4.5 | 1292.851 | 12.271 | 287.300 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 49 | GUESTROOM409_412_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM409_412 | 130.45 | 6.0 | 1600.673 | 12.271 | 266.779 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1600.673 |
| 50 | GUESTROOM413_LIGHTS | ALWAYSOFF | GUESTROOM413 | 32.61 | 1.5 | 400.168 | 12.271 | 266.779 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 51 | GUESTROOM414_LIGHTS | ALWAYSOFF | GUESTROOM414 | 32.61 | 1.5 | 400.140 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
| 52 | GUESTROOM415_418_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM415_418 | 130.44 | 6.0 | 1600.559 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1600.559 |
| 53 | GUESTROOM419_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM419 | 32.61 | 1.5 | 400.140 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.140 |
| 54 | GUESTROOM420_423_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM420_423 | 130.44 | 6.0 | 1600.559 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1600.559 |
| 55 | GUESTROOM424_LIGHTS | LTG_SCH_GUESTROOM | GUESTROOM424 | 32.61 | 1.5 | 400.140 | 12.271 | 266.760 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 400.140 |
| 56 | LAUNDRYROOMFLR1_LIGHTS | LTG_SCH_LAUNDRY | LAUNDRYROOMFLR1 | 97.83 | 10.5 | 631.799 | 6.458 | 60.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 631.799 |
| 57 | MECHANICALROOMFLR1_LIGHTS | LTG_SCH_MECHANICAL | MECHANICALROOMFLR1 | 32.61 | 0.5 | 526.537 | 16.146 | 999.121 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 526.537 |
| 58 | MEETINGROOMFLR1_LIGHTS | LTG_SCH_MEETING | MEETINGROOMFLR1 | 80.27 | 43.0 | 1123.279 | 13.993 | 26.123 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1123.279 |
| 59 | REARSTAIRSFLR1_LIGHTS | LTG_SCH_STAIR | REARSTAIRSFLR1 | 20.07 | 1.1 | 129.631 | 6.458 | 120.029 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 129.631 |
| 60 | REARSTAIRSFLR2_LIGHTS | LTG_SCH_STAIR | REARSTAIRSFLR2 | 20.07 | 1.1 | 129.631 | 6.458 | 120.029 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 129.631 |
| 61 | REARSTAIRSFLR3_LIGHTS | LTG_SCH_STAIR | REARSTAIRSFLR3 | 20.07 | 1.1 | 129.631 | 6.458 | 120.029 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 129.631 |
| 62 | REARSTAIRSFLR4_LIGHTS | LTG_SCH_STAIR | REARSTAIRSFLR4 | 20.07 | 1.1 | 129.631 | 6.458 | 120.029 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 129.631 |
| 63 | REARSTORAGEFLR1_LIGHTS | LTG_SCH_STORAGE | REARSTORAGEFLR1 | 20.07 | 0.4 | 172.853 | 8.611 | 400.124 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.853 |
| 64 | REARSTORAGEFLR2_LIGHTS | LTG_SCH_STORAGE | REARSTORAGEFLR2 | 20.07 | 0.4 | 172.853 | 8.611 | 400.124 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.853 |
| 65 | REARSTORAGEFLR3_LIGHTS | LTG_SCH_STORAGE | REARSTORAGEFLR3 | 20.07 | 0.4 | 172.853 | 8.611 | 400.124 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.853 |
| 66 | REARSTORAGEFLR4_LIGHTS | LTG_SCH_STORAGE | REARSTORAGEFLR4 | 20.07 | 0.4 | 172.853 | 8.611 | 400.124 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 172.853 |
| 67 | RESTROOMFLR1_LIGHTS | LTG_SCH_RESTROOM | RESTROOMFLR1 | 32.61 | 1.8 | 315.922 | 9.688 | 180.013 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 315.922 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | ELEVATOR_LIFT_RUNNING | ELEVATOR_RUNNING_SCH | ELEVATORCOREFLR1 | 15.05 | 0.2 | 76724.000 | 5097.841 | 315736.626 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 0.000 | 4890.388 |
| 2 | ELEVATOR_LIFT_STANDBY | ELEVATOR_STANDBY_SCH | ELEVATORCOREFLR1 | 15.05 | 0.2 | 3200.000 | 212.620 | 13168.724 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLift | 2419.072 | 3200.000 |
| 3 | ELEVATORS_LIGHTS_FAN | ELEV_LIGHT_FAN_SCH_24_7 | ELEVATORCOREFLR1 | 15.05 | 0.2 | 324.000 | 21.528 | 1333.333 | 0.000 | 0.500 | 0.000 | 0.500 | ElevatorLightsFan | 324.000 | 324.000 |
| 4 | CORRIDORFLR1_PLUGLOAD | ALWAYSOFF | CORRIDORFLR1 | 150.51 | 8.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 5 | CORRIDORFLR2_PLUGLOAD | ALWAYSOFF | CORRIDORFLR2 | 125.42 | 6.8 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 6 | CORRIDORFLR3_PLUGLOAD | ALWAYSOFF | CORRIDORFLR3 | 125.42 | 6.8 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 7 | CORRIDORFLR4_PLUGLOAD | ALWAYSOFF | CORRIDORFLR4 | 125.42 | 6.8 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 8 | ELEVATORCOREFLR2_PLUGLOAD | ALWAYSOFF | ELEVATORCOREFLR2 | 15.05 | 0.2 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 9 | ELEVATORCOREFLR3_PLUGLOAD | ALWAYSOFF | ELEVATORCOREFLR3 | 15.05 | 0.2 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 10 | ELEVATORCOREFLR4_PLUGLOAD | ALWAYSOFF | ELEVATORCOREFLR4 | 15.05 | 0.2 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 11 | EMPLOYEELOUNGEFLR1_PLUGLOAD | EMPLOYEELOUNGE_EQP_SCH | EMPLOYEELOUNGEFLR1 | 32.61 | 18.0 | 701.419 | 21.510 | 38.968 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 701.419 |
| 12 | EXERCISECENTERFLR1_PLUGLOAD | EXERCISECENTER_EQP_SCH | EXERCISECENTERFLR1 | 32.61 | 7.0 | 606.201 | 18.590 | 86.600 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 606.201 |
| 13 | FRONTLOUNGEFLR1_PLUGLOAD | LOBBY_EQP_SCH | FRONTLOUNGEFLR1 | 163.06 | 53.0 | 4249.250 | 26.060 | 80.175 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 4249.250 |
| 14 | FRONTOFFICEFLR1_PLUGLOAD | OFF_EQUIP_SCH | FRONTOFFICEFLR1 | 130.44 | 10.0 | 1797.406 | 13.780 | 179.741 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1797.406 |
| 15 | FRONTSTAIRSFLR1_PLUGLOAD | ALWAYSOFF | FRONTSTAIRSFLR1 | 20.07 | 1.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 16 | FRONTSTAIRSFLR2_PLUGLOAD | ALWAYSOFF | FRONTSTAIRSFLR2 | 20.07 | 1.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 17 | FRONTSTAIRSFLR3_PLUGLOAD | ALWAYSOFF | FRONTSTAIRSFLR3 | 20.07 | 1.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 18 | FRONTSTAIRSFLR4_PLUGLOAD | ALWAYSOFF | FRONTSTAIRSFLR4 | 20.07 | 1.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 19 | FRONTSTORAGEFLR1_PLUGLOAD | ALWAYSOFF | FRONTSTORAGEFLR1 | 12.54 | 0.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 20 | FRONTSTORAGEFLR2_PLUGLOAD | ALWAYSOFF | FRONTSTORAGEFLR2 | 12.54 | 0.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 21 | FRONTSTORAGEFLR3_PLUGLOAD | ALWAYSOFF | FRONTSTORAGEFLR3 | 12.54 | 0.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 22 | FRONTSTORAGEFLR4_PLUGLOAD | ALWAYSOFF | FRONTSTORAGEFLR4 | 12.54 | 0.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 23 | GUESTROOM101_PLUGLOAD | ALWAYSOFF | GUESTROOM101 | 32.61 | 1.5 | 387.861 | 11.893 | 258.574 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 24 | GUESTROOM102_PLUGLOAD | ALWAYSOFF | GUESTROOM102 | 32.61 | 1.5 | 387.861 | 11.893 | 258.574 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 25 | GUESTROOM103_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM103 | 32.61 | 1.5 | 387.861 | 11.893 | 258.574 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 387.861 |
| 26 | GUESTROOM104_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM104 | 32.61 | 1.5 | 387.833 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 387.833 |
| 27 | GUESTROOM105_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM105 | 32.61 | 1.5 | 387.833 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 387.833 |
| 28 | GUESTROOM201_PLUGLOAD | ALWAYSOFF | GUESTROOM201 | 32.61 | 1.5 | 387.861 | 11.893 | 258.574 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 29 | GUESTROOM202_205_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM202_205 | 130.45 | 6.0 | 1551.444 | 11.893 | 258.574 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1551.444 |
| 30 | GUESTROOM206_208_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM206_208 | 105.36 | 4.5 | 1253.089 | 11.893 | 278.464 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1253.089 |
| 31 | GUESTROOM209_212_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM209_212 | 130.45 | 6.0 | 1551.444 | 11.893 | 258.574 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1551.444 |
| 32 | GUESTROOM213_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM213 | 32.61 | 1.5 | 387.861 | 11.893 | 258.574 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 387.861 |
| 33 | GUESTROOM214_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM214 | 32.61 | 1.5 | 387.833 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 387.833 |
| 34 | GUESTROOM215_218_PLUGLOAD | ALWAYSOFF | GUESTROOM215_218 | 130.44 | 6.0 | 1551.334 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 35 | GUESTROOM219_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM219 | 32.61 | 1.5 | 387.833 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 387.833 |
| 36 | GUESTROOM220_223_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM220_223 | 130.44 | 6.0 | 1551.334 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1551.334 |
| 37 | GUESTROOM224_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM224 | 32.61 | 1.5 | 387.833 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 387.833 |
| 38 | GUESTROOM301_PLUGLOAD | ALWAYSOFF | GUESTROOM301 | 32.61 | 1.5 | 387.861 | 11.893 | 258.574 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 39 | GUESTROOM302_305_PLUGLOAD | ALWAYSOFF | GUESTROOM302_305 | 130.45 | 6.0 | 1551.444 | 11.893 | 258.574 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 40 | GUESTROOM306_308_PLUGLOAD | ALWAYSOFF | GUESTROOM306_308 | 105.36 | 4.5 | 1253.089 | 11.893 | 278.464 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 41 | GUESTROOM309_312_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM309_312 | 130.45 | 6.0 | 1551.444 | 11.893 | 258.574 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1551.444 |
| 42 | GUESTROOM313_PLUGLOAD | ALWAYSOFF | GUESTROOM313 | 32.61 | 1.5 | 387.861 | 11.893 | 258.574 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 43 | GUESTROOM314_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM314 | 32.61 | 1.5 | 387.833 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 387.833 |
| 44 | GUESTROOM315_318_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM315_318 | 130.44 | 6.0 | 1551.334 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1551.334 |
| 45 | GUESTROOM319_PLUGLOAD | ALWAYSOFF | GUESTROOM319 | 32.61 | 1.5 | 387.833 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 46 | GUESTROOM320_323_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM320_323 | 130.44 | 6.0 | 1551.334 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1551.334 |
| 47 | GUESTROOM324_PLUGLOAD | ALWAYSOFF | GUESTROOM324 | 32.61 | 1.5 | 387.833 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 48 | GUESTROOM401_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM401 | 32.61 | 1.5 | 387.861 | 11.893 | 258.574 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 387.861 |
| 49 | GUESTROOM402_405_PLUGLOAD | ALWAYSOFF | GUESTROOM402_405 | 130.45 | 6.0 | 1551.444 | 11.893 | 258.574 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 50 | GUESTROOM406_408_PLUGLOAD | ALWAYSOFF | GUESTROOM406_408 | 105.36 | 4.5 | 1253.089 | 11.893 | 278.464 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 51 | GUESTROOM409_412_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM409_412 | 130.45 | 6.0 | 1551.444 | 11.893 | 258.574 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1551.444 |
| 52 | GUESTROOM413_PLUGLOAD | ALWAYSOFF | GUESTROOM413 | 32.61 | 1.5 | 387.861 | 11.893 | 258.574 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 53 | GUESTROOM414_PLUGLOAD | ALWAYSOFF | GUESTROOM414 | 32.61 | 1.5 | 387.833 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 54 | GUESTROOM415_418_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM415_418 | 130.44 | 6.0 | 1551.334 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1551.334 |
| 55 | GUESTROOM419_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM419 | 32.61 | 1.5 | 387.833 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 387.833 |
| 56 | GUESTROOM420_423_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM420_423 | 130.44 | 6.0 | 1551.334 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1551.334 |
| 57 | GUESTROOM424_PLUGLOAD | GUESTROOM_EQP_SCH_ADVA | GUESTROOM424 | 32.61 | 1.5 | 387.833 | 11.893 | 258.556 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 387.833 |
| 58 | MECHANICALROOMFLR1_PLUGLOAD | ALWAYSOFF | MECHANICALROOMFLR1 | 32.61 | 0.5 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 59 | MEETINGROOMFLR1_PLUGLOAD | MEETINGROOM_EQP_SCH | MEETINGROOMFLR1 | 80.27 | 43.0 | 496.093 | 6.180 | 11.537 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 237.692 |
| 60 | REARSTAIRSFLR1_PLUGLOAD | ALWAYSOFF | REARSTAIRSFLR1 | 20.07 | 1.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 61 | REARSTAIRSFLR2_PLUGLOAD | ALWAYSOFF | REARSTAIRSFLR2 | 20.07 | 1.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 62 | REARSTAIRSFLR3_PLUGLOAD | ALWAYSOFF | REARSTAIRSFLR3 | 20.07 | 1.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 63 | REARSTAIRSFLR4_PLUGLOAD | ALWAYSOFF | REARSTAIRSFLR4 | 20.07 | 1.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 64 | REARSTORAGEFLR1_PLUGLOAD | ALWAYSOFF | REARSTORAGEFLR1 | 20.07 | 0.4 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 65 | REARSTORAGEFLR2_PLUGLOAD | ALWAYSOFF | REARSTORAGEFLR2 | 20.07 | 0.4 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 66 | REARSTORAGEFLR3_PLUGLOAD | ALWAYSOFF | REARSTORAGEFLR3 | 20.07 | 0.4 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 67 | REARSTORAGEFLR4_PLUGLOAD | ALWAYSOFF | REARSTORAGEFLR4 | 20.07 | 0.4 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 68 | RESTROOMFLR1_PLUGLOAD | ALWAYSOFF | RESTROOMFLR1 | 32.61 | 1.8 | 0.000 | 0.000 | 0.000 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 0.000 |
| 69 | LAUNDRY EQUIPMENT 1 | LAUNDRYROOM_EQP_ELEC_SCH | LAUNDRYROOMFLR1 | 97.83 | 10.5 | 2709.075 | 27.693 | 257.272 | 0.000 | 0.200 | 0.000 | 0.800 | Laundry | 0.000 | 2709.075 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | DRYER EQUIPMENT 1 | LAUNDRYROOM_EQP_GAS_SCH | LAUNDRYROOMFLR1 | 97.83 | 10.5 | 40096.028 | 409.867 | 3807.790 | 0.000 | 0.200 | 0.000 | 0.800 | Laundry | 0.000 | 40096.028 |
| Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
| 1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
| 2 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 3 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
| 4 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
| 5 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 6 | RES_ROOF | 18 | 3 | 3 | 0.167 | 0.3762 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 7 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 8 | NONRES_EXT_WALL_MID | 21 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 9 | NONRES_EXT_WALL_TOP | 22 | 4 | 7 | 0.167 | 0.5136 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 10 | RES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 11 | RES_EXT_WALL_MID | 24 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 12 | RES_EXT_WALL_TOP | 25 | 4 | 7 | 0.167 | 0.3843 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 13 | S_REARSTAIRSFLR1_0_0_0_FFACTOR | 37 | 2 | 7 | 0.167 | 0.7497 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 14 | S_CORRIDORFLR1_0_0_0_FFACTOR | 38 | 2 | 7 | 0.167 | 0.8294E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 15 | S_REARSTORAGEFLR1_0_0_0_FFACTOR | 39 | 2 | 7 | 0.167 | 0.7497 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 16 | S_FRONTLOUNGEFLR1_0_0_0_FFACTOR | 40 | 2 | 7 | 0.167 | 0.2249 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 17 | S_RESTROOMFLR1_0_0_0_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1573 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 18 | S_MEETINGROOMFLR1_0_0_0_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1573 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 19 | S_MECHANICALROOMFLR1_0_0_0_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1573 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 20 | S_GUESTROOM101_0_0_0_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1573 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 21 | S_GUESTROOM102_0_0_0_FFACTOR | 45 | 2 | 7 | 0.167 | 0.1573 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 22 | S_GUESTROOM103_0_0_0_FFACTOR | 46 | 2 | 7 | 0.167 | 0.1573 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 23 | S_GUESTROOM104_0_0_0_FFACTOR | 47 | 2 | 7 | 0.167 | 0.1573 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 24 | S_GUESTROOM105_0_0_0_FFACTOR | 48 | 2 | 7 | 0.167 | 0.1573 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 25 | S_EMPLOYEELOUNGEFLR1_0_0_0_FFACTOR | 49 | 2 | 7 | 0.167 | 0.1573 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 26 | S_LAUNDRYROOMFLR1_0_0_0_FFACTOR | 50 | 2 | 7 | 0.167 | 0.1573 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 27 | S_ELEVATORCOREFLR1_0_0_0_FFACTOR | 51 | 2 | 7 | 0.167 | 0.1573 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 28 | S_EXERCISECENTERFLR1_0_0_0_FFACTOR | 52 | 2 | 7 | 0.167 | 0.1573 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 29 | S_FRONTOFFICEFLR1_0_0_0_FFACTOR | 53 | 2 | 7 | 0.167 | 0.1573 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 30 | S_FRONTSTAIRSFLR1_0_0_0_FFACTOR | 54 | 2 | 7 | 0.167 | 0.7498 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 31 | S_FRONTSTORAGEFLR1_0_0_0_FFACTOR | 55 | 2 | 7 | 0.167 | 0.1573 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
| 1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
| 2 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
| 3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
| 4 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
| 5 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
| 6 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
| 7 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
| 8 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
| 9 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
| 10 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
| 11 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
| 12 | RES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.599 |
| 13 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
| 14 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
| 15 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
| 17 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 18 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
| 19 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 20 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
| 21 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 22 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
| 23 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 24 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 1.713 |
| 25 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 26 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
| 27 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 28 | RES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
| 29 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 30 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
| 31 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 32 | RES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
| 33 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 34 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
| 35 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 36 | RES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 2.368 |
| 37 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 38 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 1.257 |
| 39 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 40 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 11.98 |
| 41 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 42 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 1.257 |
| 43 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 44 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.370 |
| 45 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 46 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.281 |
| 47 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 48 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.281 |
| 49 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 50 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.281 |
| 51 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 52 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.281 |
| 53 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 54 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.281 |
| 55 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 56 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.281 |
| 57 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 58 | ~FC_Insulation_11 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.281 |
| 59 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 60 | ~FC_Insulation_12 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.281 |
| 61 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 62 | ~FC_Insulation_13 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.281 |
| 63 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 64 | ~FC_Insulation_14 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.281 |
| 65 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 66 | ~FC_Insulation_15 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.281 |
| 67 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 68 | ~FC_Insulation_16 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.281 |
| 69 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 70 | ~FC_Insulation_17 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.281 |
| 71 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 72 | ~FC_Insulation_18 | 0.0000 | 0.000 | 0.000 | 0.000 | 1.257 |
| 73 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 74 | ~FC_Insulation_19 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.281 |
| 75 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| Time | Outside | Cross | Inside | Flux (except final one) | |
| 1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
| 2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
| 3 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
| 4 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
| 5 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
| 6 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
| 7 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
| 8 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
| 9 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
| 10 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
| 11 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
| 12 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
| 13 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
| 14 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
| 15 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
| 16 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
| 17 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
| 18 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
| 19 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
| 20 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
| 21 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
| 22 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
| 23 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
| 24 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
| 25 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
| 26 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
| 27 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
| 28 | 3 | -0.61039648E-06 | 0.16815647E-08 | -0.37447326E-05 | 0.10149002E-16 |
| 29 | 2 | 0.76989337 | 0.22941655E-02 | 1.0458372 | -0.71793422E-06 |
| 30 | 1 | -21.843031 | 0.15409339 | -6.3407615 | 0.20050303 |
| 31 | 0 | 21.373924 | 0.14439780 | 5.5957134 | |
| 32 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
| 33 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
| 34 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
| 35 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
| 36 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
| 37 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
| 38 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
| 39 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
| 40 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
| 41 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
| 42 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
| 43 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
| 44 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
| 45 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
| 46 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
| 47 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
| 48 | 7 | -0.33207909E-12 | 0.79542070E-15 | -0.11586622E-12 | 0.10783435E-15 |
| 49 | 6 | 0.31762832E-07 | 0.14865645E-09 | 0.72503568E-08 | -0.15188138E-12 |
| 50 | 5 | -0.20568023E-03 | 0.12486053E-05 | -0.10556626E-03 | 0.71569697E-08 |
| 51 | 4 | 0.31018727 | 0.59758545E-03 | 0.10618022 | -0.36135240E-04 |
| 52 | 3 | -7.6231853 | 0.18239075E-01 | -2.4448349 | 0.30759039E-01 |
| 53 | 2 | 42.047589 | 0.63983780E-01 | 15.698525 | -0.34644559 |
| 54 | 1 | -81.446794 | 0.28535822E-01 | -29.529986 | 1.0978209 |
| 55 | 0 | 46.824333 | 0.56745654E-03 | 16.282146 | |
| 56 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
| 57 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
| 58 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
| 59 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
| 60 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
| 61 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
| 62 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
| 63 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
| 64 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
| 65 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
| 66 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
| 67 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
| 68 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
| 69 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
| 70 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
| 71 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
| 72 | 7 | -0.35963630E-12 | 0.61482467E-15 | -0.13288964E-12 | 0.15093609E-15 |
| 73 | 6 | 0.33258387E-07 | 0.11249777E-09 | 0.75805110E-08 | -0.16019892E-12 |
| 74 | 5 | -0.21313350E-03 | 0.93714421E-06 | -0.10927814E-03 | 0.74776115E-08 |
| 75 | 4 | 0.31870195 | 0.44521373E-03 | 0.10925225 | -0.37358013E-04 |
| 76 | 3 | -7.7913368 | 0.13499397E-01 | -2.4947666 | 0.31584435E-01 |
| 77 | 2 | 42.601618 | 0.47079245E-01 | 15.902165 | -0.35261900 |
| 78 | 1 | -81.870774 | 0.20888078E-01 | -29.712230 | 1.1068570 |
| 79 | 0 | 46.824331 | 0.41326549E-03 | 16.278015 | |
| 80 | 7 | -0.53128682E-09 | 0.24220376E-16 | 0.26514926E-14 | 0.16128612E-17 |
| 81 | 6 | 0.21546521E-04 | 0.14761233E-07 | 0.31451383E-02 | -0.26384056E-04 |
| 82 | 5 | -0.15649836E-02 | 0.87831386E-05 | -0.22118113 | 0.19337009E-02 |
| 83 | 4 | 0.36052469E-01 | 0.40055374E-03 | 4.7871640 | -0.44857599E-01 |
| 84 | 3 | -0.31659804 | 0.31924535E-02 | -37.781903 | 0.39600649 |
| 85 | 2 | 1.1239880 | 0.53187163E-02 | 116.01766 | -1.4117025 |
| 86 | 1 | -1.6220914 | 0.16257908E-02 | -143.63277 | 2.0445274 |
| 87 | 0 | 0.79077713 | 0.38479517E-04 | 60.838472 | |
| 88 | 7 | -0.51500745E-08 | -0.97097940E-14 | 0.12078333E-14 | -0.28423254E-16 |
| 89 | 6 | 0.26273275E-05 | 0.15924315E-08 | 0.31989440E-02 | -0.26835423E-04 |
| 90 | 5 | -0.17303723E-03 | 0.93841597E-06 | -0.22424021 | 0.19607016E-02 |
| 91 | 4 | 0.38747196E-02 | 0.42606369E-04 | 4.8381317 | -0.45347518E-01 |
| 92 | 3 | -0.33688598E-01 | 0.33804754E-03 | -38.069908 | 0.39918977 |
| 93 | 2 | 0.11914415 | 0.56121933E-03 | 116.57831 | -1.4192015 |
| 94 | 1 | -0.17165687 | 0.17050824E-03 | -143.96285 | 2.0499529 |
| 95 | 0 | 0.83614474E-01 | 0.41325042E-05 | 60.838472 | |
| 96 | 7 | -0.53129722E-09 | 0.23174307E-16 | 0.25222374E-14 | 0.13630250E-17 |
| 97 | 6 | 0.21546106E-04 | 0.14760998E-07 | 0.31451395E-02 | -0.26384065E-04 |
| 98 | 5 | -0.15649536E-02 | 0.87829689E-05 | -0.22118120 | 0.19337015E-02 |
| 99 | 4 | 0.36051778E-01 | 0.40054620E-03 | 4.7871651 | -0.44857610E-01 |
| 100 | 3 | -0.31659198 | 0.31923921E-02 | -37.781909 | 0.39600656 |
| 101 | 2 | 1.1239666 | 0.53186170E-02 | 116.01767 | -1.4117026 |
| 102 | 1 | -1.6220604 | 0.16257564E-02 | -143.63278 | 2.0445275 |
| 103 | 0 | 0.79076203 | 0.38480293E-04 | 60.838472 | |
| 104 | 7 | -0.18720363E-08 | -0.47896590E-15 | 0.65414493E-14 | -0.87102839E-16 |
| 105 | 6 | 0.63019258E-05 | 0.43089118E-08 | 0.31878718E-02 | -0.26742540E-04 |
| 106 | 5 | -0.45288328E-03 | 0.25526970E-05 | -0.22361101 | 0.19551479E-02 |
| 107 | 4 | 0.10415606E-01 | 0.11619496E-03 | 4.8276543 | -0.45246799E-01 |
| 108 | 3 | -0.91458955E-01 | 0.92404132E-03 | -38.010732 | 0.39853565 |
| 109 | 2 | 0.32474571 | 0.15371787E-02 | 116.46316 | -1.4176612 |
| 110 | 1 | -0.46871811 | 0.46842216E-03 | -143.89507 | 2.0488387 |
| 111 | 0 | 0.22852204 | 0.11310110E-04 | 60.838472 | |
| 112 | 7 | -0.26954509E-08 | -0.14165318E-14 | 0.79352360E-14 | -0.11582431E-15 |
| 113 | 6 | 0.44852355E-05 | 0.30071832E-08 | 0.31931672E-02 | -0.26786962E-04 |
| 114 | 5 | -0.31748557E-03 | 0.17794841E-05 | -0.22391198 | 0.19578044E-02 |
| 115 | 4 | 0.72703152E-02 | 0.80954923E-04 | 4.8326669 | -0.45294985E-01 |
| 116 | 3 | -0.63742948E-01 | 0.64345195E-03 | -38.039048 | 0.39884864 |
| 117 | 2 | 0.22619914 | 0.10699397E-02 | 116.51827 | -1.4183983 |
| 118 | 1 | -0.32639619 | 0.32581351E-03 | -143.92751 | 2.0493720 |
| 119 | 0 | 0.15911251 | 0.78822336E-05 | 60.838472 | |
| 120 | 7 | -0.26954509E-08 | -0.14160083E-14 | 0.76220666E-14 | -0.11181341E-15 |
| 121 | 6 | 0.44852355E-05 | 0.30071829E-08 | 0.31931672E-02 | -0.26786962E-04 |
| 122 | 5 | -0.31748557E-03 | 0.17794842E-05 | -0.22391198 | 0.19578044E-02 |
| 123 | 4 | 0.72703152E-02 | 0.80954923E-04 | 4.8326669 | -0.45294985E-01 |
| 124 | 3 | -0.63742948E-01 | 0.64345196E-03 | -38.039048 | 0.39884864 |
| 125 | 2 | 0.22619914 | 0.10699397E-02 | 116.51827 | -1.4183983 |
| 126 | 1 | -0.32639619 | 0.32581353E-03 | -143.92751 | 2.0493720 |
| 127 | 0 | 0.15911251 | 0.78822226E-05 | 60.838472 | |
| 128 | 7 | -0.26954509E-08 | -0.14163871E-14 | 0.77130239E-14 | -0.11173131E-15 |
| 129 | 6 | 0.44852355E-05 | 0.30071832E-08 | 0.31931672E-02 | -0.26786962E-04 |
| 130 | 5 | -0.31748557E-03 | 0.17794841E-05 | -0.22391198 | 0.19578044E-02 |
| 131 | 4 | 0.72703152E-02 | 0.80954923E-04 | 4.8326669 | -0.45294985E-01 |
| 132 | 3 | -0.63742948E-01 | 0.64345195E-03 | -38.039048 | 0.39884864 |
| 133 | 2 | 0.22619914 | 0.10699397E-02 | 116.51827 | -1.4183983 |
| 134 | 1 | -0.32639619 | 0.32581351E-03 | -143.92751 | 2.0493720 |
| 135 | 0 | 0.15911251 | 0.78822328E-05 | 60.838472 | |
| 136 | 7 | -0.26954509E-08 | -0.14163493E-14 | 0.78169427E-14 | -0.11082736E-15 |
| 137 | 6 | 0.44852355E-05 | 0.30071832E-08 | 0.31931672E-02 | -0.26786962E-04 |
| 138 | 5 | -0.31748557E-03 | 0.17794841E-05 | -0.22391198 | 0.19578044E-02 |
| 139 | 4 | 0.72703152E-02 | 0.80954923E-04 | 4.8326669 | -0.45294985E-01 |
| 140 | 3 | -0.63742948E-01 | 0.64345195E-03 | -38.039048 | 0.39884864 |
| 141 | 2 | 0.22619914 | 0.10699397E-02 | 116.51827 | -1.4183983 |
| 142 | 1 | -0.32639619 | 0.32581351E-03 | -143.92751 | 2.0493720 |
| 143 | 0 | 0.15911251 | 0.78822328E-05 | 60.838472 | |
| 144 | 7 | -0.26954509E-08 | -0.14163494E-14 | 0.78169428E-14 | -0.11082736E-15 |
| 145 | 6 | 0.44852355E-05 | 0.30071832E-08 | 0.31931672E-02 | -0.26786962E-04 |
| 146 | 5 | -0.31748557E-03 | 0.17794841E-05 | -0.22391198 | 0.19578044E-02 |
| 147 | 4 | 0.72703152E-02 | 0.80954923E-04 | 4.8326669 | -0.45294985E-01 |
| 148 | 3 | -0.63742948E-01 | 0.64345195E-03 | -38.039048 | 0.39884864 |
| 149 | 2 | 0.22619914 | 0.10699397E-02 | 116.51827 | -1.4183983 |
| 150 | 1 | -0.32639619 | 0.32581351E-03 | -143.92751 | 2.0493720 |
| 151 | 0 | 0.15911251 | 0.78822328E-05 | 60.838472 | |
| 152 | 7 | -0.26954509E-08 | -0.14165316E-14 | 0.79352360E-14 | -0.11582431E-15 |
| 153 | 6 | 0.44852355E-05 | 0.30071832E-08 | 0.31931672E-02 | -0.26786962E-04 |
| 154 | 5 | -0.31748557E-03 | 0.17794841E-05 | -0.22391198 | 0.19578044E-02 |
| 155 | 4 | 0.72703152E-02 | 0.80954923E-04 | 4.8326669 | -0.45294985E-01 |
| 156 | 3 | -0.63742948E-01 | 0.64345195E-03 | -38.039048 | 0.39884864 |
| 157 | 2 | 0.22619914 | 0.10699397E-02 | 116.51827 | -1.4183983 |
| 158 | 1 | -0.32639619 | 0.32581351E-03 | -143.92751 | 2.0493720 |
| 159 | 0 | 0.15911251 | 0.78822336E-05 | 60.838472 | |
| 160 | 7 | -0.26952518E-08 | -0.14162741E-14 | 0.77444661E-14 | -0.11458787E-15 |
| 161 | 6 | 0.44855364E-05 | 0.30074020E-08 | 0.31931663E-02 | -0.26786955E-04 |
| 162 | 5 | -0.31750824E-03 | 0.17796143E-05 | -0.22391193 | 0.19578040E-02 |
| 163 | 4 | 0.72708434E-02 | 0.80960854E-04 | 4.8326661 | -0.45294977E-01 |
| 164 | 3 | -0.63747607E-01 | 0.64349918E-03 | -38.039043 | 0.39884859 |
| 165 | 2 | 0.22621572 | 0.10700184E-02 | 116.51826 | -1.4183982 |
| 166 | 1 | -0.32642013 | 0.32583753E-03 | -143.92750 | 2.0493719 |
| 167 | 0 | 0.15912418 | 0.78828025E-05 | 60.838472 | |
| 168 | 7 | -0.26952518E-08 | -0.14160959E-14 | 0.76668815E-14 | -0.11323979E-15 |
| 169 | 6 | 0.44855364E-05 | 0.30074019E-08 | 0.31931663E-02 | -0.26786955E-04 |
| 170 | 5 | -0.31750824E-03 | 0.17796143E-05 | -0.22391193 | 0.19578040E-02 |
| 171 | 4 | 0.72708434E-02 | 0.80960854E-04 | 4.8326661 | -0.45294977E-01 |
| 172 | 3 | -0.63747607E-01 | 0.64349918E-03 | -38.039043 | 0.39884859 |
| 173 | 2 | 0.22621572 | 0.10700184E-02 | 116.51826 | -1.4183982 |
| 174 | 1 | -0.32642013 | 0.32583754E-03 | -143.92750 | 2.0493719 |
| 175 | 0 | 0.15912418 | 0.78827986E-05 | 60.838472 | |
| 176 | 7 | -0.26952518E-08 | -0.14160961E-14 | 0.76668817E-14 | -0.11323979E-15 |
| 177 | 6 | 0.44855364E-05 | 0.30074019E-08 | 0.31931663E-02 | -0.26786955E-04 |
| 178 | 5 | -0.31750824E-03 | 0.17796143E-05 | -0.22391193 | 0.19578040E-02 |
| 179 | 4 | 0.72708434E-02 | 0.80960854E-04 | 4.8326661 | -0.45294977E-01 |
| 180 | 3 | -0.63747607E-01 | 0.64349918E-03 | -38.039043 | 0.39884859 |
| 181 | 2 | 0.22621572 | 0.10700184E-02 | 116.51826 | -1.4183982 |
| 182 | 1 | -0.32642013 | 0.32583754E-03 | -143.92750 | 2.0493719 |
| 183 | 0 | 0.15912418 | 0.78827986E-05 | 60.838472 | |
| 184 | 7 | -0.26952518E-08 | -0.14161726E-14 | 0.78921355E-14 | -0.11583298E-15 |
| 185 | 6 | 0.44855364E-05 | 0.30074019E-08 | 0.31931663E-02 | -0.26786955E-04 |
| 186 | 5 | -0.31750824E-03 | 0.17796143E-05 | -0.22391193 | 0.19578040E-02 |
| 187 | 4 | 0.72708434E-02 | 0.80960854E-04 | 4.8326661 | -0.45294977E-01 |
| 188 | 3 | -0.63747607E-01 | 0.64349918E-03 | -38.039043 | 0.39884859 |
| 189 | 2 | 0.22621572 | 0.10700184E-02 | 116.51826 | -1.4183982 |
| 190 | 1 | -0.32642013 | 0.32583754E-03 | -143.92750 | 2.0493719 |
| 191 | 0 | 0.15912418 | 0.78827986E-05 | 60.838472 | |
| 192 | 7 | -0.26952518E-08 | -0.14158604E-14 | 0.78355877E-14 | -0.11409465E-15 |
| 193 | 6 | 0.44855364E-05 | 0.30074019E-08 | 0.31931663E-02 | -0.26786955E-04 |
| 194 | 5 | -0.31750824E-03 | 0.17796143E-05 | -0.22391193 | 0.19578040E-02 |
| 195 | 4 | 0.72708434E-02 | 0.80960854E-04 | 4.8326661 | -0.45294977E-01 |
| 196 | 3 | -0.63747607E-01 | 0.64349918E-03 | -38.039043 | 0.39884859 |
| 197 | 2 | 0.22621572 | 0.10700184E-02 | 116.51826 | -1.4183982 |
| 198 | 1 | -0.32642013 | 0.32583754E-03 | -143.92750 | 2.0493719 |
| 199 | 0 | 0.15912418 | 0.78827985E-05 | 60.838472 | |
| 200 | 7 | -0.26952518E-08 | -0.14161149E-14 | 0.76709449E-14 | -0.11600230E-15 |
| 201 | 6 | 0.44855364E-05 | 0.30074020E-08 | 0.31931663E-02 | -0.26786955E-04 |
| 202 | 5 | -0.31750824E-03 | 0.17796143E-05 | -0.22391193 | 0.19578040E-02 |
| 203 | 4 | 0.72708434E-02 | 0.80960854E-04 | 4.8326661 | -0.45294977E-01 |
| 204 | 3 | -0.63747607E-01 | 0.64349918E-03 | -38.039043 | 0.39884859 |
| 205 | 2 | 0.22621572 | 0.10700184E-02 | 116.51826 | -1.4183982 |
| 206 | 1 | -0.32642013 | 0.32583753E-03 | -143.92750 | 2.0493719 |
| 207 | 0 | 0.15912418 | 0.78828026E-05 | 60.838472 | |
| 208 | 7 | -0.26952518E-08 | -0.14161596E-14 | 0.76816470E-14 | -0.11359384E-15 |
| 209 | 6 | 0.44855364E-05 | 0.30074019E-08 | 0.31931663E-02 | -0.26786955E-04 |
| 210 | 5 | -0.31750824E-03 | 0.17796143E-05 | -0.22391193 | 0.19578040E-02 |
| 211 | 4 | 0.72708434E-02 | 0.80960854E-04 | 4.8326661 | -0.45294977E-01 |
| 212 | 3 | -0.63747607E-01 | 0.64349918E-03 | -38.039043 | 0.39884859 |
| 213 | 2 | 0.22621572 | 0.10700184E-02 | 116.51826 | -1.4183982 |
| 214 | 1 | -0.32642013 | 0.32583754E-03 | -143.92750 | 2.0493719 |
| 215 | 0 | 0.15912418 | 0.78827986E-05 | 60.838472 | |
| 216 | 7 | -0.53116838E-09 | 0.26696391E-16 | 0.25662770E-14 | 0.29950102E-17 |
| 217 | 6 | 0.21551244E-04 | 0.14764408E-07 | 0.31451253E-02 | -0.26383947E-04 |
| 218 | 5 | -0.15653260E-02 | 0.87850342E-05 | -0.22118039 | 0.19336943E-02 |
| 219 | 4 | 0.36060337E-01 | 0.40064042E-03 | 4.7871516 | -0.44857481E-01 |
| 220 | 3 | -0.31666702 | 0.31931462E-02 | -37.781833 | 0.39600572 |
| 221 | 2 | 1.1242327 | 0.53198728E-02 | 116.01752 | -1.4117006 |
| 222 | 1 | -1.6224443 | 0.16261452E-02 | -143.63269 | 2.0445261 |
| 223 | 0 | 0.79094913 | 0.38487883E-04 | 60.838472 | |
| 224 | 7 | -0.26952518E-08 | -0.14158604E-14 | 0.78355877E-14 | -0.11409465E-15 |
| 225 | 6 | 0.44855364E-05 | 0.30074019E-08 | 0.31931663E-02 | -0.26786955E-04 |
| 226 | 5 | -0.31750824E-03 | 0.17796143E-05 | -0.22391193 | 0.19578040E-02 |
| 227 | 4 | 0.72708434E-02 | 0.80960854E-04 | 4.8326661 | -0.45294977E-01 |
| 228 | 3 | -0.63747607E-01 | 0.64349918E-03 | -38.039043 | 0.39884859 |
| 229 | 2 | 0.22621572 | 0.10700184E-02 | 116.51826 | -1.4183982 |
| 230 | 1 | -0.32642013 | 0.32583754E-03 | -143.92750 | 2.0493719 |
| 231 | 0 | 0.15912418 | 0.78827986E-05 | 60.838472 |
| Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
| 1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 35 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
| 2 | RESWINDOW_U_0.57_SHGC_0.39 | 36 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
| Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
| 1 | GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
| 2 | RESIDENTIAL WINDOW GLAZING LAYER | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | SWH SHOWER WATER HEATER | 1.1356 | 87921.3 | 10.693 | 0.4398 |
| 2 | WaterHeater:Mixed | SWH LAUNDRY WATER HEATER | 0.7570 | 58614.2 | 14.749 | 0.4701 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | W_REARSTAIRSFLR1_2_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 2 | W_REARSTAIRSFLR1_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 3 | W_REARSTAIRSFLR1_3_0_0_DOOR | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 4 | P_REARSTAIRSFLR1_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 5 | P_REARSTAIRSFLR1_5_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 6 | S_REARSTAIRSFLR1_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 7 | C_REARSTAIRSFLR1_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 8 | P_CORRIDORFLR1_10003_0_10002 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 9 | W_CORRIDORFLR1_2_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 4 | No | No |
| 10 | W_CORRIDORFLR1_2_0_0_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 1 | No | No |
| 11 | P_CORRIDORFLR1_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 12 | P_CORRIDORFLR1_5_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 13 | P_CORRIDORFLR1_6_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 14 | P_CORRIDORFLR1_7_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 15 | P_CORRIDORFLR1_8_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 16 | P_CORRIDORFLR1_9_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 17 | W_CORRIDORFLR1_10_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 4 | No | No |
| 18 | W_CORRIDORFLR1_10_0_0_DOOR | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 19 | P_CORRIDORFLR1_11_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 20 | P_CORRIDORFLR1_12_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 21 | P_CORRIDORFLR1_13_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 22 | P_CORRIDORFLR1_14_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 23 | P_CORRIDORFLR1_15_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 24 | W_CORRIDORFLR1_16_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 4 | No | No |
| 25 | D_CORRIDORFLR1_16_0_0_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 1 | No | No |
| 26 | P_CORRIDORFLR1_17_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 27 | P_CORRIDORFLR1_18_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 28 | P_CORRIDORFLR1_19_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 29 | W_CORRIDORFLR1_20_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 4 | No | No |
| 30 | W_CORRIDORFLR1_20_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 1 | No | No |
| 31 | P_CORRIDORFLR1_21_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 32 | P_CORRIDORFLR1_22_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 33 | P_CORRIDORFLR1_23_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 34 | P_CORRIDORFLR1_24_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 35 | P_CORRIDORFLR1_25_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 36 | P_CORRIDORFLR1_26_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 37 | P_CORRIDORFLR1_27_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 38 | S_CORRIDORFLR1_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 39 | C_CORRIDORFLR1_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 40 | C_CORRIDORFLR1_1_1_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 4.11 | 0.30 | 0 | No | No |
| 41 | P_REARSTORAGEFLR1_10027_0_10025 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 42 | W_REARSTORAGEFLR1_2_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 43 | P_REARSTORAGEFLR1_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 44 | W_REARSTORAGEFLR1_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 45 | S_REARSTORAGEFLR1_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 46 | C_REARSTORAGEFLR1_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 47 | P_FRONTLOUNGEFLR1_10018_0_10016 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 28.04 | 11.63 | 0.16 | 0 | No | No |
| 48 | P_FRONTLOUNGEFLR1_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 28.04 | 11.63 | 0.16 | 0 | No | No |
| 49 | W_FRONTLOUNGEFLR1_4_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 3.35 | 28.04 | 11.63 | 0.16 | 4 | No | No |
| 50 | W_FRONTLOUNGEFLR1_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 28.04 | 11.63 | 0.16 | 3 | No | No |
| 51 | W_FRONTLOUNGEFLR1_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 28.04 | 11.63 | 0.16 | 2 | No | No |
| 52 | W_FRONTLOUNGEFLR1_5_0_0_0_1 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 28.04 | 11.63 | 0.16 | 2 | No | No |
| 53 | W_FRONTLOUNGEFLR1_5_0_0_0_2 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 28.04 | 11.63 | 0.16 | 2 | No | No |
| 54 | W_FRONTLOUNGEFLR1_5_0_0_0_3 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 28.04 | 11.63 | 0.16 | 2 | No | No |
| 55 | W_FRONTLOUNGEFLR1_5_0_0_0_4 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 28.04 | 11.63 | 0.16 | 2 | No | No |
| 56 | S_FRONTLOUNGEFLR1_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 28.04 | 11.63 | 0.16 | 0 | No | No |
| 57 | C_FRONTLOUNGEFLR1_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 28.04 | 11.63 | 0.16 | 0 | No | No |
| 58 | C_FRONTLOUNGEFLR1_1_1_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 28.04 | 11.63 | 0.16 | 0 | No | No |
| 59 | P_RESTROOMFLR1_10019_0_10017 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.00 | 0 | No | No |
| 60 | P_RESTROOMFLR1_10020_0_10018 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.00 | 0 | No | No |
| 61 | P_RESTROOMFLR1_10033_0_10030 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.00 | 0 | No | No |
| 62 | W_RESTROOMFLR1_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.00 | 0 | No | No |
| 63 | S_RESTROOMFLR1_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.00 | 0 | No | No |
| 64 | C_RESTROOMFLR1_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.00 | 0 | No | No |
| 65 | P_MEETINGROOMFLR1_10021_0_10019 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 8.93 | 0.35 | 0 | No | No |
| 66 | P_MEETINGROOMFLR1_10022_0_10020 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 8.93 | 0.35 | 0 | No | No |
| 67 | P_MEETINGROOMFLR1_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 8.93 | 0.35 | 0 | No | No |
| 68 | W_MEETINGROOMFLR1_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 9.75 | 8.93 | 0.35 | 3 | No | No |
| 69 | W_MEETINGROOMFLR1_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 9.75 | 8.93 | 0.35 | 2 | No | No |
| 70 | W_MEETINGROOMFLR1_5_0_0_0_1 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 9.75 | 8.93 | 0.35 | 2 | No | No |
| 71 | W_MEETINGROOMFLR1_5_0_0_0_2 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 9.75 | 8.93 | 0.35 | 2 | No | No |
| 72 | S_MEETINGROOMFLR1_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 8.93 | 0.35 | 0 | No | No |
| 73 | C_MEETINGROOMFLR1_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 8.93 | 0.35 | 0 | No | No |
| 74 | C_MEETINGROOMFLR1_1_1_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 9.75 | 8.93 | 0.35 | 0 | No | No |
| 75 | P_MECHANICALROOMFLR1_10023_0_10021 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.00 | 0 | No | No |
| 76 | P_MECHANICALROOMFLR1_10041_0_10034 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.00 | 0 | No | No |
| 77 | P_MECHANICALROOMFLR1_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.00 | 0 | No | No |
| 78 | W_MECHANICALROOMFLR1_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.00 | 0 | No | No |
| 79 | S_MECHANICALROOMFLR1_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.00 | 0 | No | No |
| 80 | C_MECHANICALROOMFLR1_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.00 | 0 | No | No |
| 81 | P_GUESTROOM101_10024_0_10022 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 82 | P_GUESTROOM101_10045_0_10036 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 83 | P_GUESTROOM101_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 84 | W_GUESTROOM101_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 3 | No | No |
| 85 | W_GUESTROOM101_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 2 | No | No |
| 86 | S_GUESTROOM101_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 87 | C_GUESTROOM101_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 88 | P_GUESTROOM102_10025_0_10023 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 89 | P_GUESTROOM102_10049_0_10038 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 90 | P_GUESTROOM102_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 91 | W_GUESTROOM102_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 3 | No | No |
| 92 | W_GUESTROOM102_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 2 | No | No |
| 93 | S_GUESTROOM102_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 94 | C_GUESTROOM102_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 95 | P_GUESTROOM103_10026_0_10024 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 96 | P_GUESTROOM103_10030_0_10027 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 97 | P_GUESTROOM103_10053_0_10040 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 98 | W_GUESTROOM103_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 3 | No | No |
| 99 | W_GUESTROOM103_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 2 | No | No |
| 100 | S_GUESTROOM103_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 101 | C_GUESTROOM103_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 102 | P_GUESTROOM104_10002_0_10001 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 103 | P_GUESTROOM104_10007_0_10005 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 104 | W_GUESTROOM104_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 3 | No | No |
| 105 | W_GUESTROOM104_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 2 | No | No |
| 106 | P_GUESTROOM104_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 107 | S_GUESTROOM104_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 108 | C_GUESTROOM104_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 109 | P_GUESTROOM105_10008_0_10006 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 110 | P_GUESTROOM105_10062_0_10043 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 111 | W_GUESTROOM105_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 3 | No | No |
| 112 | W_GUESTROOM105_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 2 | No | No |
| 113 | P_GUESTROOM105_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 114 | S_GUESTROOM105_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 115 | C_GUESTROOM105_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 116 | P_EMPLOYEELOUNGEFLR1_10009_0_10007 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 117 | P_EMPLOYEELOUNGEFLR1_10066_0_10045 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 118 | W_EMPLOYEELOUNGEFLR1_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 3 | No | No |
| 119 | W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 2 | No | No |
| 120 | P_EMPLOYEELOUNGEFLR1_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 121 | S_EMPLOYEELOUNGEFLR1_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 122 | C_EMPLOYEELOUNGEFLR1_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 123 | P_LAUNDRYROOMFLR1_10010_0_10008 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 11.89 | 9.73 | 0.29 | 0 | No | No |
| 124 | P_LAUNDRYROOMFLR1_10070_0_10047 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 11.89 | 9.73 | 0.29 | 0 | No | No |
| 125 | W_LAUNDRYROOMFLR1_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 11.89 | 9.73 | 0.29 | 3 | No | No |
| 126 | W_LAUNDRYROOMFLR1_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 11.89 | 9.73 | 0.29 | 2 | No | No |
| 127 | W_LAUNDRYROOMFLR1_3_0_0_0_1 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 11.89 | 9.73 | 0.29 | 2 | No | No |
| 128 | W_LAUNDRYROOMFLR1_3_0_0_0_2 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 11.89 | 9.73 | 0.29 | 2 | No | No |
| 129 | P_LAUNDRYROOMFLR1_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 11.89 | 9.73 | 0.29 | 0 | No | No |
| 130 | S_LAUNDRYROOMFLR1_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 11.89 | 9.73 | 0.29 | 0 | No | No |
| 131 | C_LAUNDRYROOMFLR1_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 11.89 | 9.73 | 0.29 | 0 | No | No |
| 132 | C_LAUNDRYROOMFLR1_1_1_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 11.89 | 9.73 | 0.29 | 0 | No | No |
| 133 | P_ELEVATORCOREFLR1_10011_0_10009 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 134 | P_ELEVATORCOREFLR1_10012_0_10010 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 135 | P_ELEVATORCOREFLR1_10075_0_10050 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 136 | W_ELEVATORCOREFLR1_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 137 | S_ELEVATORCOREFLR1_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 138 | C_ELEVATORCOREFLR1_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 139 | P_EXERCISECENTERFLR1_10013_0_10011 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 140 | P_EXERCISECENTERFLR1_10014_0_10012 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 141 | W_EXERCISECENTERFLR1_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 3 | No | No |
| 142 | W_EXERCISECENTERFLR1_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 2 | No | No |
| 143 | P_EXERCISECENTERFLR1_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 144 | S_EXERCISECENTERFLR1_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 145 | C_EXERCISECENTERFLR1_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 3.96 | 5.35 | 0.29 | 0 | No | No |
| 146 | P_FRONTOFFICEFLR1_10015_0_10013 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 15.85 | 10.83 | 0.29 | 0 | No | No |
| 147 | P_FRONTOFFICEFLR1_10083_0_10053 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 15.85 | 10.83 | 0.29 | 0 | No | No |
| 148 | W_FRONTOFFICEFLR1_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 15.85 | 10.83 | 0.29 | 3 | No | No |
| 149 | W_FRONTOFFICEFLR1_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 15.85 | 10.83 | 0.29 | 2 | No | No |
| 150 | W_FRONTOFFICEFLR1_3_0_0_0_1 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 15.85 | 10.83 | 0.29 | 2 | No | No |
| 151 | W_FRONTOFFICEFLR1_3_0_0_0_2 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 15.85 | 10.83 | 0.29 | 2 | No | No |
| 152 | W_FRONTOFFICEFLR1_3_0_0_0_3 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 15.85 | 10.83 | 0.29 | 2 | No | No |
| 153 | P_FRONTOFFICEFLR1_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 15.85 | 10.83 | 0.29 | 0 | No | No |
| 154 | S_FRONTOFFICEFLR1_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 15.85 | 10.83 | 0.29 | 0 | No | No |
| 155 | C_FRONTOFFICEFLR1_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 15.85 | 10.83 | 0.29 | 0 | No | No |
| 156 | C_FRONTOFFICEFLR1_1_1_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 15.85 | 10.83 | 0.29 | 0 | No | No |
| 157 | P_FRONTSTAIRSFLR1_10017_0_10015 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 158 | P_FRONTSTAIRSFLR1_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 159 | W_FRONTSTAIRSFLR1_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 160 | W_FRONTSTAIRSFLR1_3_0_0_DOOR | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 161 | W_FRONTSTAIRSFLR1_4_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 162 | S_FRONTSTAIRSFLR1_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 163 | C_FRONTSTAIRSFLR1_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 164 | P_FRONTSTORAGEFLR1_10016_0_10014 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 165 | P_FRONTSTORAGEFLR1_10088_0_10056 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 166 | P_FRONTSTORAGEFLR1_10091_0_10058 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 167 | W_FRONTSTORAGEFLR1_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 3.35 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 168 | S_FRONTSTORAGEFLR1_0_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 169 | C_FRONTSTORAGEFLR1_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.35 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 170 | W_REARSTAIRSFLR2_2_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 171 | W_REARSTAIRSFLR2_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 172 | P_REARSTAIRSFLR2_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 173 | P_REARSTAIRSFLR2_5_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 174 | F_REARSTAIRSFLR2_10001_0_10000 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 175 | C_REARSTAIRSFLR2_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 176 | P_CORRIDORFLR2_10100_0_10062 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 177 | W_CORRIDORFLR2_2_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 3 | No | No |
| 178 | W_CORRIDORFLR2_2_0_0_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 2 | No | No |
| 179 | P_CORRIDORFLR2_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 180 | P_CORRIDORFLR2_5_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 181 | P_CORRIDORFLR2_6_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 182 | P_CORRIDORFLR2_7_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 183 | P_CORRIDORFLR2_8_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 184 | W_CORRIDORFLR2_9_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 4 | No | No |
| 185 | P_CORRIDORFLR2_10_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 186 | P_CORRIDORFLR2_11_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 187 | P_CORRIDORFLR2_12_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 188 | P_CORRIDORFLR2_13_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 189 | P_CORRIDORFLR2_14_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 190 | W_CORRIDORFLR2_15_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 3 | No | No |
| 191 | W_CORRIDORFLR2_15_0_0_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 2 | No | No |
| 192 | P_CORRIDORFLR2_16_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 193 | P_CORRIDORFLR2_17_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 194 | P_CORRIDORFLR2_18_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 195 | P_CORRIDORFLR2_19_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 196 | P_CORRIDORFLR2_20_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 197 | P_CORRIDORFLR2_21_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 198 | F_CORRIDORFLR2_10004_0_10003 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 199 | C_CORRIDORFLR2_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 200 | P_REARSTORAGEFLR2_10119_0_10079 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 201 | W_REARSTORAGEFLR2_2_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 202 | P_REARSTORAGEFLR2_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 203 | W_REARSTORAGEFLR2_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 204 | F_REARSTORAGEFLR2_10028_0_10026 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 205 | C_REARSTORAGEFLR2_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 206 | P_GUESTROOM201_10114_0_10074 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 0 | No | No |
| 207 | P_GUESTROOM201_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 0 | No | No |
| 208 | W_GUESTROOM201_4_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 4 | No | No |
| 209 | W_GUESTROOM201_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 3 | No | No |
| 210 | W_GUESTROOM201_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 2 | No | No |
| 211 | F_GUESTROOM201_10031_0_10028 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 0 | No | No |
| 212 | C_GUESTROOM201_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 0 | No | No |
| 213 | P_GUESTROOM202_205_10115_0_10075 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 214 | P_GUESTROOM202_205_10126_0_10083 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 215 | P_GUESTROOM202_205_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 216 | W_GUESTROOM202_205_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 3 | No | No |
| 217 | W_GUESTROOM202_205_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 218 | W_GUESTROOM202_205_5_0_0_0_1 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 219 | W_GUESTROOM202_205_5_0_0_0_2 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 220 | W_GUESTROOM202_205_5_0_0_0_3 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 221 | F_GUESTROOM202_205_10032_0_10029 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 222 | C_GUESTROOM202_205_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 223 | P_GUESTROOM206_208_10116_0_10076 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 224 | P_GUESTROOM206_208_10130_0_10085 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 225 | P_GUESTROOM206_208_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 226 | W_GUESTROOM206_208_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 3 | No | No |
| 227 | W_GUESTROOM206_208_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 2 | No | No |
| 228 | W_GUESTROOM206_208_5_0_0_0_1 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 2 | No | No |
| 229 | W_GUESTROOM206_208_5_0_0_0_2 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 2 | No | No |
| 230 | F_GUESTROOM206_208_10005_0_10004 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 231 | F_GUESTROOM206_208_10035_0_10031 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 232 | F_GUESTROOM206_208_10039_0_10032 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 233 | C_GUESTROOM206_208_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 234 | P_GUESTROOM209_212_10117_0_10077 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 235 | P_GUESTROOM209_212_10137_0_10087 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 236 | P_GUESTROOM209_212_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 237 | W_GUESTROOM209_212_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 3 | No | No |
| 238 | W_GUESTROOM209_212_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 239 | W_GUESTROOM209_212_5_0_0_0_1 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 240 | W_GUESTROOM209_212_5_0_0_0_2 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 241 | W_GUESTROOM209_212_5_0_0_0_3 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 242 | F_GUESTROOM209_212_10040_0_10033 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 243 | F_GUESTROOM209_212_10044_0_10035 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 244 | F_GUESTROOM209_212_10048_0_10037 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 245 | F_GUESTROOM209_212_10052_0_10039 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 246 | C_GUESTROOM209_212_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 247 | P_GUESTROOM213_10118_0_10078 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 248 | P_GUESTROOM213_10123_0_10081 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 249 | P_GUESTROOM213_10145_0_10089 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 250 | W_GUESTROOM213_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 3 | No | No |
| 251 | W_GUESTROOM213_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 2 | No | No |
| 252 | F_GUESTROOM213_10056_0_10041 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 253 | C_GUESTROOM213_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 254 | P_GUESTROOM214_10099_0_10061 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 255 | P_GUESTROOM214_10104_0_10064 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 256 | W_GUESTROOM214_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 3 | No | No |
| 257 | W_GUESTROOM214_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 2 | No | No |
| 258 | P_GUESTROOM214_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 259 | F_GUESTROOM214_10060_0_10042 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 260 | C_GUESTROOM214_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 261 | P_GUESTROOM215_218_10105_0_10065 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 262 | P_GUESTROOM215_218_10156_0_10092 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 263 | W_GUESTROOM215_218_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 3 | No | No |
| 264 | W_GUESTROOM215_218_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 265 | W_GUESTROOM215_218_3_0_0_0_1 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 266 | W_GUESTROOM215_218_3_0_0_0_2 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 267 | W_GUESTROOM215_218_3_0_0_0_3 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 268 | P_GUESTROOM215_218_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 269 | F_GUESTROOM215_218_10064_0_10044 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 270 | F_GUESTROOM215_218_10068_0_10046 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 271 | F_GUESTROOM215_218_10072_0_10048 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 272 | C_GUESTROOM215_218_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 273 | P_ELEVATORCOREFLR2_10107_0_10067 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 274 | P_ELEVATORCOREFLR2_10108_0_10068 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 275 | P_ELEVATORCOREFLR2_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 276 | W_ELEVATORCOREFLR2_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 277 | F_ELEVATORCOREFLR2_10077_0_10051 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 278 | C_ELEVATORCOREFLR2_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 279 | P_GUESTROOM219_10106_0_10066 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 280 | P_GUESTROOM219_10163_0_10094 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 281 | P_GUESTROOM219_10167_0_10096 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 282 | W_GUESTROOM219_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 3 | No | No |
| 283 | W_GUESTROOM219_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 2 | No | No |
| 284 | F_GUESTROOM219_10073_0_10049 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 285 | C_GUESTROOM219_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 286 | P_GUESTROOM220_223_10109_0_10069 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 287 | P_GUESTROOM220_223_10110_0_10070 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 288 | W_GUESTROOM220_223_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 3 | No | No |
| 289 | W_GUESTROOM220_223_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 290 | W_GUESTROOM220_223_3_0_0_0_1 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 291 | W_GUESTROOM220_223_3_0_0_0_2 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 292 | W_GUESTROOM220_223_3_0_0_0_3 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 293 | P_GUESTROOM220_223_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 294 | F_GUESTROOM220_223_10081_0_10052 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 295 | F_GUESTROOM220_223_10085_0_10054 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 296 | C_GUESTROOM220_223_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 297 | P_GUESTROOM224_10111_0_10071 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 298 | P_GUESTROOM224_10179_0_10099 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 299 | W_GUESTROOM224_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 3 | No | No |
| 300 | W_GUESTROOM224_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 2 | No | No |
| 301 | P_GUESTROOM224_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 302 | F_GUESTROOM224_10086_0_10055 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 303 | C_GUESTROOM224_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 304 | P_FRONTSTORAGEFLR2_10112_0_10072 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 305 | P_FRONTSTORAGEFLR2_10184_0_10101 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 306 | W_FRONTSTORAGEFLR2_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 307 | P_FRONTSTORAGEFLR2_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 308 | F_FRONTSTORAGEFLR2_10093_0_10059 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 309 | C_FRONTSTORAGEFLR2_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 310 | P_FRONTSTAIRSFLR2_10113_0_10073 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 311 | P_FRONTSTAIRSFLR2_10189_0_10103 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 312 | W_FRONTSTAIRSFLR2_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 313 | W_FRONTSTAIRSFLR2_4_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 314 | F_FRONTSTAIRSFLR2_10090_0_10057 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 315 | C_FRONTSTAIRSFLR2_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 316 | W_REARSTAIRSFLR3_2_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 317 | W_REARSTAIRSFLR3_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 318 | P_REARSTAIRSFLR3_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 319 | P_REARSTAIRSFLR3_5_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 320 | F_REARSTAIRSFLR3_10098_0_10060 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 321 | C_REARSTAIRSFLR3_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 322 | P_CORRIDORFLR3_10198_0_10107 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 323 | W_CORRIDORFLR3_2_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 3 | No | No |
| 324 | W_CORRIDORFLR3_2_0_0_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 2 | No | No |
| 325 | P_CORRIDORFLR3_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 326 | P_CORRIDORFLR3_5_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 327 | P_CORRIDORFLR3_6_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 328 | P_CORRIDORFLR3_7_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 329 | P_CORRIDORFLR3_8_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 330 | W_CORRIDORFLR3_9_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 3 | No | No |
| 331 | P_CORRIDORFLR3_10_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 332 | P_CORRIDORFLR3_11_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 333 | P_CORRIDORFLR3_12_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 334 | P_CORRIDORFLR3_13_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 335 | P_CORRIDORFLR3_14_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 336 | W_CORRIDORFLR3_15_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 3 | No | No |
| 337 | W_CORRIDORFLR3_15_0_0_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 2 | No | No |
| 338 | P_CORRIDORFLR3_16_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 339 | P_CORRIDORFLR3_17_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 340 | P_CORRIDORFLR3_18_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 341 | P_CORRIDORFLR3_19_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 342 | P_CORRIDORFLR3_20_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 343 | P_CORRIDORFLR3_21_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 344 | F_CORRIDORFLR3_10102_0_10063 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 345 | C_CORRIDORFLR3_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 346 | P_REARSTORAGEFLR3_10217_0_10124 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 347 | W_REARSTORAGEFLR3_2_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 348 | P_REARSTORAGEFLR3_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 349 | W_REARSTORAGEFLR3_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 350 | F_REARSTORAGEFLR3_10121_0_10080 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 351 | C_REARSTORAGEFLR3_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 352 | P_GUESTROOM301_10212_0_10119 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 0 | No | No |
| 353 | P_GUESTROOM301_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 0 | No | No |
| 354 | W_GUESTROOM301_4_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 4 | No | No |
| 355 | W_GUESTROOM301_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 3 | No | No |
| 356 | W_GUESTROOM301_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 2 | No | No |
| 357 | F_GUESTROOM301_10125_0_10082 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 0 | No | No |
| 358 | C_GUESTROOM301_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 0 | No | No |
| 359 | P_GUESTROOM302_305_10213_0_10120 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 360 | P_GUESTROOM302_305_10224_0_10128 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 361 | P_GUESTROOM302_305_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 362 | W_GUESTROOM302_305_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 3 | No | No |
| 363 | W_GUESTROOM302_305_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 364 | W_GUESTROOM302_305_5_0_0_0_1 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 365 | W_GUESTROOM302_305_5_0_0_0_2 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 366 | W_GUESTROOM302_305_5_0_0_0_3 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 367 | F_GUESTROOM302_305_10129_0_10084 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 368 | C_GUESTROOM302_305_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 369 | P_GUESTROOM306_308_10214_0_10121 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 370 | P_GUESTROOM306_308_10228_0_10130 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 371 | P_GUESTROOM306_308_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 372 | W_GUESTROOM306_308_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 3 | No | No |
| 373 | W_GUESTROOM306_308_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 2 | No | No |
| 374 | W_GUESTROOM306_308_5_0_0_0_1 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 1 | No | No |
| 375 | W_GUESTROOM306_308_5_0_0_0_2 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 2 | No | No |
| 376 | F_GUESTROOM306_308_10136_0_10086 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 377 | C_GUESTROOM306_308_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 378 | P_GUESTROOM309_312_10215_0_10122 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 379 | P_GUESTROOM309_312_10233_0_10132 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 380 | P_GUESTROOM309_312_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 381 | W_GUESTROOM309_312_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 3 | No | No |
| 382 | W_GUESTROOM309_312_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 383 | W_GUESTROOM309_312_5_0_0_0_1 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 384 | W_GUESTROOM309_312_5_0_0_0_2 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 385 | W_GUESTROOM309_312_5_0_0_0_3 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 386 | F_GUESTROOM309_312_10144_0_10088 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 387 | C_GUESTROOM309_312_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 388 | P_GUESTROOM313_10216_0_10123 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 389 | P_GUESTROOM313_10221_0_10126 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 390 | P_GUESTROOM313_10238_0_10134 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 391 | W_GUESTROOM313_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 3 | No | No |
| 392 | W_GUESTROOM313_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 2 | No | No |
| 393 | F_GUESTROOM313_10149_0_10090 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 394 | C_GUESTROOM313_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 395 | P_GUESTROOM314_10197_0_10106 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 396 | P_GUESTROOM314_10202_0_10109 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 397 | W_GUESTROOM314_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 3 | No | No |
| 398 | W_GUESTROOM314_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 2 | No | No |
| 399 | P_GUESTROOM314_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 400 | F_GUESTROOM314_10154_0_10091 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 401 | C_GUESTROOM314_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 402 | P_GUESTROOM315_318_10203_0_10110 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 403 | P_GUESTROOM315_318_10249_0_10137 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 404 | W_GUESTROOM315_318_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 3 | No | No |
| 405 | W_GUESTROOM315_318_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 406 | W_GUESTROOM315_318_3_0_0_0_1 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 407 | W_GUESTROOM315_318_3_0_0_0_2 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 408 | W_GUESTROOM315_318_3_0_0_0_3 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 409 | P_GUESTROOM315_318_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 410 | F_GUESTROOM315_318_10161_0_10093 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 411 | C_GUESTROOM315_318_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 412 | P_ELEVATORCOREFLR3_10205_0_10112 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 413 | P_ELEVATORCOREFLR3_10206_0_10113 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 414 | P_ELEVATORCOREFLR3_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 415 | W_ELEVATORCOREFLR3_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 416 | F_ELEVATORCOREFLR3_10166_0_10095 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 417 | C_ELEVATORCOREFLR3_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 418 | P_GUESTROOM319_10204_0_10111 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 419 | P_GUESTROOM319_10254_0_10139 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 420 | P_GUESTROOM319_10258_0_10141 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 421 | W_GUESTROOM319_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 3 | No | No |
| 422 | W_GUESTROOM319_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 2 | No | No |
| 423 | F_GUESTROOM319_10171_0_10097 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 424 | C_GUESTROOM319_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 425 | P_GUESTROOM320_323_10207_0_10114 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 426 | P_GUESTROOM320_323_10208_0_10115 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 427 | W_GUESTROOM320_323_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 3 | No | No |
| 428 | W_GUESTROOM320_323_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 429 | W_GUESTROOM320_323_3_0_0_0_1 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 430 | W_GUESTROOM320_323_3_0_0_0_2 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 431 | W_GUESTROOM320_323_3_0_0_0_3 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 432 | P_GUESTROOM320_323_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 433 | F_GUESTROOM320_323_10177_0_10098 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 434 | C_GUESTROOM320_323_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 435 | P_GUESTROOM324_10209_0_10116 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 436 | P_GUESTROOM324_10269_0_10144 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 437 | W_GUESTROOM324_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 3 | No | No |
| 438 | W_GUESTROOM324_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 2 | No | No |
| 439 | P_GUESTROOM324_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 440 | F_GUESTROOM324_10182_0_10100 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 441 | C_GUESTROOM324_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 442 | P_FRONTSTORAGEFLR3_10210_0_10117 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 443 | P_FRONTSTORAGEFLR3_10274_0_10146 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 444 | W_FRONTSTORAGEFLR3_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 445 | P_FRONTSTORAGEFLR3_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 446 | F_FRONTSTORAGEFLR3_10187_0_10102 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 447 | C_FRONTSTORAGEFLR3_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 448 | P_FRONTSTAIRSFLR3_10211_0_10118 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 449 | P_FRONTSTAIRSFLR3_10279_0_10148 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 450 | W_FRONTSTAIRSFLR3_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 451 | W_FRONTSTAIRSFLR3_4_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 452 | F_FRONTSTAIRSFLR3_10192_0_10104 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 453 | C_FRONTSTAIRSFLR3_1_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 454 | W_REARSTAIRSFLR4_2_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 455 | W_REARSTAIRSFLR4_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 456 | P_REARSTAIRSFLR4_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 457 | P_REARSTAIRSFLR4_5_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 458 | F_REARSTAIRSFLR4_10196_0_10105 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 459 | R_REARSTAIRSFLR4_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 460 | P_CORRIDORFLR4_10287_0_10151 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 461 | W_CORRIDORFLR4_2_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 3 | No | No |
| 462 | W_CORRIDORFLR4_2_0_0_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 2 | No | No |
| 463 | P_CORRIDORFLR4_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 464 | P_CORRIDORFLR4_5_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 465 | P_CORRIDORFLR4_6_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 466 | P_CORRIDORFLR4_7_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 467 | P_CORRIDORFLR4_8_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 468 | W_CORRIDORFLR4_9_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 3 | No | No |
| 469 | P_CORRIDORFLR4_10_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 470 | P_CORRIDORFLR4_11_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 471 | P_CORRIDORFLR4_12_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 472 | P_CORRIDORFLR4_13_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 473 | P_CORRIDORFLR4_14_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 474 | W_CORRIDORFLR4_15_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 3 | No | No |
| 475 | W_CORRIDORFLR4_15_0_0_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 2 | No | No |
| 476 | P_CORRIDORFLR4_16_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 477 | P_CORRIDORFLR4_17_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 478 | P_CORRIDORFLR4_18_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 479 | P_CORRIDORFLR4_19_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 480 | P_CORRIDORFLR4_20_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 481 | P_CORRIDORFLR4_21_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 482 | F_CORRIDORFLR4_10200_0_10108 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 483 | R_CORRIDORFLR4_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 6.71 | 3.86 | 0.14 | 0 | No | No |
| 484 | P_REARSTORAGEFLR4_10305_0_10167 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 485 | W_REARSTORAGEFLR4_2_0_0 | 0 | 211.83 | 138.95 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 486 | P_REARSTORAGEFLR4_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 487 | W_REARSTORAGEFLR4_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 488 | F_REARSTORAGEFLR4_10219_0_10125 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 489 | R_REARSTORAGEFLR4_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 490 | P_GUESTROOM401_10300_0_10162 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 0 | No | No |
| 491 | P_GUESTROOM401_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 0 | No | No |
| 492 | W_GUESTROOM401_4_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 3 | No | No |
| 493 | W_GUESTROOM401_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 3 | No | No |
| 494 | W_GUESTROOM401_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 2 | No | No |
| 495 | F_GUESTROOM401_10223_0_10127 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 0 | No | No |
| 496 | R_GUESTROOM401_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 12.19 | 5.35 | 0.11 | 0 | No | No |
| 497 | P_GUESTROOM402_405_10301_0_10163 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 498 | P_GUESTROOM402_405_10310_0_10169 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 499 | P_GUESTROOM402_405_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 500 | W_GUESTROOM402_405_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 3 | No | No |
| 501 | W_GUESTROOM402_405_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 502 | W_GUESTROOM402_405_5_0_0_0_1 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 503 | W_GUESTROOM402_405_5_0_0_0_2 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 504 | W_GUESTROOM402_405_5_0_0_0_3 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 505 | F_GUESTROOM402_405_10227_0_10129 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 506 | R_GUESTROOM402_405_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 507 | P_GUESTROOM406_408_10302_0_10164 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 508 | P_GUESTROOM406_408_10313_0_10170 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 509 | P_GUESTROOM406_408_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 510 | W_GUESTROOM406_408_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 3 | No | No |
| 511 | W_GUESTROOM406_408_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 2 | No | No |
| 512 | W_GUESTROOM406_408_5_0_0_0_1 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 2 | No | No |
| 513 | W_GUESTROOM406_408_5_0_0_0_2 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 1 | No | No |
| 514 | F_GUESTROOM406_408_10232_0_10131 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 515 | R_GUESTROOM406_408_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 12.80 | 10.02 | 0.31 | 0 | No | No |
| 516 | P_GUESTROOM409_412_10303_0_10165 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 517 | P_GUESTROOM409_412_10317_0_10171 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 518 | P_GUESTROOM409_412_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 519 | W_GUESTROOM409_412_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 3 | No | No |
| 520 | W_GUESTROOM409_412_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 521 | W_GUESTROOM409_412_5_0_0_0_1 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 522 | W_GUESTROOM409_412_5_0_0_0_2 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 523 | W_GUESTROOM409_412_5_0_0_0_3 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 524 | F_GUESTROOM409_412_10237_0_10133 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 525 | R_GUESTROOM409_412_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 526 | P_GUESTROOM413_10304_0_10166 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 527 | P_GUESTROOM413_10308_0_10168 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 528 | P_GUESTROOM413_10321_0_10172 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 529 | W_GUESTROOM413_5_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 3 | No | No |
| 530 | W_GUESTROOM413_5_0_0_0_0 | 0 | 635.46 | 132.99 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 2 | No | No |
| 531 | F_GUESTROOM413_10242_0_10135 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 532 | R_GUESTROOM413_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 533 | P_GUESTROOM414_10286_0_10150 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 534 | P_GUESTROOM414_10290_0_10152 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 535 | W_GUESTROOM414_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 3 | No | No |
| 536 | W_GUESTROOM414_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 2 | No | No |
| 537 | P_GUESTROOM414_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 538 | F_GUESTROOM414_10247_0_10136 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 539 | R_GUESTROOM414_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 540 | P_GUESTROOM415_418_10291_0_10153 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 541 | P_GUESTROOM415_418_10330_0_10173 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 542 | W_GUESTROOM415_418_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 3 | No | No |
| 543 | W_GUESTROOM415_418_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 544 | W_GUESTROOM415_418_3_0_0_0_1 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 545 | W_GUESTROOM415_418_3_0_0_0_2 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 546 | W_GUESTROOM415_418_3_0_0_0_3 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 547 | P_GUESTROOM415_418_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 548 | F_GUESTROOM415_418_10252_0_10138 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 549 | R_GUESTROOM415_418_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 550 | P_ELEVATORCOREFLR4_10293_0_10155 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 551 | P_ELEVATORCOREFLR4_10294_0_10156 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 552 | P_ELEVATORCOREFLR4_2_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 553 | W_ELEVATORCOREFLR4_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 554 | F_ELEVATORCOREFLR4_10257_0_10140 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 555 | R_ELEVATORCOREFLR4_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 1.83 | 2.99 | 0.00 | 0 | No | No |
| 556 | P_GUESTROOM419_10292_0_10154 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 557 | P_GUESTROOM419_10334_0_10174 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 558 | P_GUESTROOM419_10337_0_10175 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 559 | W_GUESTROOM419_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 3 | No | No |
| 560 | W_GUESTROOM419_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 2 | No | No |
| 561 | F_GUESTROOM419_10262_0_10142 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 562 | R_GUESTROOM419_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 563 | P_GUESTROOM420_423_10295_0_10157 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 564 | P_GUESTROOM420_423_10296_0_10158 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 565 | W_GUESTROOM420_423_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 3 | No | No |
| 566 | W_GUESTROOM420_423_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 567 | W_GUESTROOM420_423_3_0_0_0_1 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 568 | W_GUESTROOM420_423_3_0_0_0_2 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 569 | W_GUESTROOM420_423_3_0_0_0_3 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 2 | No | No |
| 570 | P_GUESTROOM420_423_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 571 | F_GUESTROOM420_423_10267_0_10143 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 572 | R_GUESTROOM420_423_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 15.85 | 10.83 | 0.35 | 0 | No | No |
| 573 | P_GUESTROOM424_10297_0_10159 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 574 | P_GUESTROOM424_10346_0_10176 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 575 | W_GUESTROOM424_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 3 | No | No |
| 576 | W_GUESTROOM424_3_0_0_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 2 | No | No |
| 577 | P_GUESTROOM424_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 578 | F_GUESTROOM424_10272_0_10145 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 579 | R_GUESTROOM424_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 3.96 | 5.35 | 0.35 | 0 | No | No |
| 580 | P_FRONTSTORAGEFLR4_10298_0_10160 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 581 | P_FRONTSTORAGEFLR4_10350_0_10177 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 582 | W_FRONTSTORAGEFLR4_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 583 | P_FRONTSTORAGEFLR4_4_0_0 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 584 | F_FRONTSTORAGEFLR4_10277_0_10147 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 585 | R_FRONTSTORAGEFLR4_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 1.52 | 2.57 | 0.00 | 0 | No | No |
| 586 | P_FRONTSTAIRSFLR4_10299_0_10161 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 587 | P_FRONTSTAIRSFLR4_10354_0_10178 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 588 | W_FRONTSTAIRSFLR4_3_0_0 | 0 | 635.46 | 138.95 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 589 | W_FRONTSTAIRSFLR4_4_0_0 | 0 | 211.83 | 59.84 | 11.58 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 590 | F_FRONTSTAIRSFLR4_10282_0_10149 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| 591 | R_FRONTSTAIRSFLR4_1_0_0 | 0 | 1003.40 | 167.12 | 0.00 | 0 | 2.74 | 10.67 | 3.76 | 0.00 | 0 | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | CORRIDORFLR1_INFILTRATION | ALWAYSON | CORRIDORFLR1 | 150.51 | 8.1 | 1.863E-002 | 1.238E-004 | 5.375E-004 | 0.133 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | CORRIDORFLR1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | CORRIDORFLR1 | 150.51 | 8.1 | 0.592 | 3.932E-003 | 1.708E-002 | 4.222 | 1.000 | 0.000 | 0.000 | 0.000 |
| 3 | CORRIDORFLR2_INFILTRATION | ALWAYSON | CORRIDORFLR2 | 125.42 | 6.8 | 1.048E-002 | 8.354E-005 | 5.696E-004 | 0.110 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | CORRIDORFLR3_INFILTRATION | ALWAYSON | CORRIDORFLR3 | 125.42 | 6.8 | 1.048E-002 | 8.354E-005 | 5.696E-004 | 0.110 | 0.000 | 0.000 | 0.224 | 0.000 |
| 5 | CORRIDORFLR4_INFILTRATION | ALWAYSON | CORRIDORFLR4 | 125.42 | 6.8 | 1.048E-002 | 8.354E-005 | 7.285E-005 | 0.110 | 0.000 | 0.000 | 0.224 | 0.000 |
| 6 | ELEVATORCOREFLR1_INFILTRATION | ALWAYSON | ELEVATORCOREFLR1 | 15.05 | 0.2 | 3.492E-003 | 2.320E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 7 | ELEVATORCOREFLR2_INFILTRATION | ALWAYSON | ELEVATORCOREFLR2 | 15.05 | 0.2 | 2.857E-003 | 1.899E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 8 | ELEVATORCOREFLR3_INFILTRATION | ALWAYSON | ELEVATORCOREFLR3 | 15.05 | 0.2 | 2.857E-003 | 1.899E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 9 | ELEVATORCOREFLR4_INFILTRATION | ALWAYSON | ELEVATORCOREFLR4 | 15.05 | 0.2 | 2.857E-003 | 1.899E-004 | 1.424E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 10 | EMPLOYEELOUNGEFLR1_INFILTRATION | COMMONAREA_INFIL_SCH | EMPLOYEELOUNGEFLR1 | 32.61 | 18.0 | 7.567E-003 | 2.320E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 11 | EXERCISECENTERFLR1_INFILTRATION | COMMONAREA_INFIL_SCH | EXERCISECENTERFLR1 | 32.61 | 7.0 | 7.567E-003 | 2.320E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 12 | FRONTLOUNGEFLR1_INFILTRATION | COMMONAREA_INFIL_SCH | FRONTLOUNGEFLR1 | 163.06 | 53.0 | 5.355E-002 | 3.284E-004 | 5.696E-004 | 0.353 | 0.000 | 0.000 | 0.224 | 0.000 |
| 13 | FRONTOFFICEFLR1_INFILTRATION | COMMONAREA_INFIL_SCH | FRONTOFFICEFLR1 | 130.44 | 10.0 | 3.027E-002 | 2.320E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 14 | FRONTSTAIRSFLR1_INFILTRATION | ALWAYSON | FRONTSTAIRSFLR1 | 20.07 | 1.1 | 2.037E-002 | 1.015E-003 | 5.401E-004 | 1.090 | 0.000 | 0.000 | 0.224 | 0.000 |
| 15 | FRONTSTAIRSFLR2_INFILTRATION | ALWAYSON | FRONTSTAIRSFLR2 | 20.07 | 1.1 | 1.667E-002 | 8.306E-004 | 5.696E-004 | 1.090 | 0.000 | 0.000 | 0.224 | 0.000 |
| 16 | FRONTSTAIRSFLR3_INFILTRATION | ALWAYSON | FRONTSTAIRSFLR3 | 20.07 | 1.1 | 1.667E-002 | 8.306E-004 | 5.696E-004 | 1.090 | 0.000 | 0.000 | 0.224 | 0.000 |
| 17 | FRONTSTAIRSFLR4_INFILTRATION | ALWAYSON | FRONTSTAIRSFLR4 | 20.07 | 1.1 | 1.667E-002 | 8.306E-004 | 3.379E-004 | 1.090 | 0.000 | 0.000 | 0.224 | 0.000 |
| 18 | FRONTSTORAGEFLR1_INFILTRATION | ALWAYSON | FRONTSTORAGEFLR1 | 12.54 | 0.3 | 2.910E-003 | 2.320E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 19 | FRONTSTORAGEFLR2_INFILTRATION | ALWAYSON | FRONTSTORAGEFLR2 | 12.54 | 0.3 | 2.381E-003 | 1.899E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 20 | FRONTSTORAGEFLR3_INFILTRATION | ALWAYSON | FRONTSTORAGEFLR3 | 12.54 | 0.3 | 2.381E-003 | 1.899E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 21 | FRONTSTORAGEFLR4_INFILTRATION | ALWAYSON | FRONTSTORAGEFLR4 | 12.54 | 0.3 | 2.381E-003 | 1.899E-004 | 1.424E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 22 | GUESTROOM101_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM101 | 32.61 | 1.5 | 7.567E-003 | 2.320E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 23 | GUESTROOM102_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM102 | 32.61 | 1.5 | 7.567E-003 | 2.320E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 24 | GUESTROOM103_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM103 | 32.61 | 1.5 | 7.567E-003 | 2.320E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 25 | GUESTROOM104_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM104 | 32.61 | 1.5 | 7.567E-003 | 2.320E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 26 | GUESTROOM105_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM105 | 32.61 | 1.5 | 7.567E-003 | 2.320E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 27 | GUESTROOM201_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM201 | 32.61 | 1.5 | 1.905E-002 | 5.842E-004 | 5.696E-004 | 0.767 | 0.000 | 0.000 | 0.224 | 0.000 |
| 28 | GUESTROOM202_205_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM202_205 | 130.45 | 6.0 | 2.476E-002 | 1.898E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 29 | GUESTROOM206_208_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM206_208 | 105.36 | 4.5 | 2.000E-002 | 1.898E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 30 | GUESTROOM209_212_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM209_212 | 130.45 | 6.0 | 2.476E-002 | 1.898E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 31 | GUESTROOM213_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM213 | 32.61 | 1.5 | 6.191E-003 | 1.898E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 32 | GUESTROOM214_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM214 | 32.61 | 1.5 | 6.191E-003 | 1.899E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 33 | GUESTROOM215_218_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM215_218 | 130.44 | 6.0 | 2.476E-002 | 1.899E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 34 | GUESTROOM219_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM219 | 32.61 | 1.5 | 6.191E-003 | 1.899E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 35 | GUESTROOM220_223_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM220_223 | 130.44 | 6.0 | 2.476E-002 | 1.899E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 36 | GUESTROOM224_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM224 | 32.61 | 1.5 | 6.191E-003 | 1.899E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 37 | GUESTROOM301_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM301 | 32.61 | 1.5 | 1.905E-002 | 5.842E-004 | 5.696E-004 | 0.767 | 0.000 | 0.000 | 0.224 | 0.000 |
| 38 | GUESTROOM302_305_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM302_305 | 130.45 | 6.0 | 2.476E-002 | 1.898E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 39 | GUESTROOM306_308_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM306_308 | 105.36 | 4.5 | 2.000E-002 | 1.898E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 40 | GUESTROOM309_312_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM309_312 | 130.45 | 6.0 | 2.476E-002 | 1.898E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 41 | GUESTROOM313_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM313 | 32.61 | 1.5 | 6.191E-003 | 1.898E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 42 | GUESTROOM314_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM314 | 32.61 | 1.5 | 6.191E-003 | 1.899E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 43 | GUESTROOM315_318_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM315_318 | 130.44 | 6.0 | 2.476E-002 | 1.899E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 44 | GUESTROOM319_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM319 | 32.61 | 1.5 | 6.191E-003 | 1.899E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 45 | GUESTROOM320_323_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM320_323 | 130.44 | 6.0 | 2.476E-002 | 1.899E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 46 | GUESTROOM324_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM324 | 32.61 | 1.5 | 6.191E-003 | 1.899E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 47 | GUESTROOM401_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM401 | 32.61 | 1.5 | 1.905E-002 | 5.842E-004 | 2.884E-004 | 0.767 | 0.000 | 0.000 | 0.224 | 0.000 |
| 48 | GUESTROOM402_405_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM402_405 | 130.45 | 6.0 | 2.476E-002 | 1.898E-004 | 1.424E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 49 | GUESTROOM406_408_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM406_408 | 105.36 | 4.5 | 2.000E-002 | 1.898E-004 | 1.424E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 50 | GUESTROOM409_412_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM409_412 | 130.45 | 6.0 | 2.476E-002 | 1.898E-004 | 1.424E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 51 | GUESTROOM413_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM413 | 32.61 | 1.5 | 6.191E-003 | 1.898E-004 | 1.424E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 52 | GUESTROOM414_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM414 | 32.61 | 1.5 | 6.191E-003 | 1.899E-004 | 1.424E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 53 | GUESTROOM415_418_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM415_418 | 130.44 | 6.0 | 2.476E-002 | 1.899E-004 | 1.424E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 54 | GUESTROOM419_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM419 | 32.61 | 1.5 | 6.191E-003 | 1.899E-004 | 1.424E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 55 | GUESTROOM420_423_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM420_423 | 130.44 | 6.0 | 2.476E-002 | 1.899E-004 | 1.424E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 56 | GUESTROOM424_INFILTRATION | GUESTROOM_INFIL_SCH | GUESTROOM424 | 32.61 | 1.5 | 6.191E-003 | 1.899E-004 | 1.424E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 57 | LAUNDRYROOMFLR1_INFILTRATION | GUESTROOM_INFIL_SCH | LAUNDRYROOMFLR1 | 97.83 | 10.5 | 2.270E-002 | 2.320E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 58 | MECHANICALROOMFLR1_INFILTRATION | GUESTROOM_INFIL_SCH | MECHANICALROOMFLR1 | 32.61 | 0.5 | 7.567E-003 | 2.320E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 59 | MEETINGROOMFLR1_INFILTRATION | GUESTROOM_INFIL_SCH | MEETINGROOMFLR1 | 80.27 | 43.0 | 1.863E-002 | 2.320E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| 60 | REARSTAIRSFLR1_INFILTRATION | ALWAYSON | REARSTAIRSFLR1 | 20.07 | 1.1 | 2.037E-002 | 1.015E-003 | 5.401E-004 | 1.090 | 0.000 | 0.000 | 0.224 | 0.000 |
| 61 | REARSTAIRSFLR2_INFILTRATION | ALWAYSON | REARSTAIRSFLR2 | 20.07 | 1.1 | 1.667E-002 | 8.305E-004 | 5.696E-004 | 1.090 | 0.000 | 0.000 | 0.224 | 0.000 |
| 62 | REARSTAIRSFLR3_INFILTRATION | ALWAYSON | REARSTAIRSFLR3 | 20.07 | 1.1 | 1.667E-002 | 8.305E-004 | 5.696E-004 | 1.090 | 0.000 | 0.000 | 0.224 | 0.000 |
| 63 | REARSTAIRSFLR4_INFILTRATION | ALWAYSON | REARSTAIRSFLR4 | 20.07 | 1.1 | 1.667E-002 | 8.305E-004 | 3.379E-004 | 1.090 | 0.000 | 0.000 | 0.224 | 0.000 |
| 64 | REARSTORAGEFLR1_INFILTRATION | ALWAYSON | REARSTORAGEFLR1 | 20.07 | 0.4 | 2.037E-002 | 1.015E-003 | 5.696E-004 | 1.090 | 0.000 | 0.000 | 0.224 | 0.000 |
| 65 | REARSTORAGEFLR2_INFILTRATION | ALWAYSON | REARSTORAGEFLR2 | 20.07 | 0.4 | 1.667E-002 | 8.305E-004 | 5.696E-004 | 1.090 | 0.000 | 0.000 | 0.224 | 0.000 |
| 66 | REARSTORAGEFLR3_INFILTRATION | ALWAYSON | REARSTORAGEFLR3 | 20.07 | 0.4 | 1.667E-002 | 8.305E-004 | 5.696E-004 | 1.090 | 0.000 | 0.000 | 0.224 | 0.000 |
| 67 | REARSTORAGEFLR4_INFILTRATION | ALWAYSON | REARSTORAGEFLR4 | 20.07 | 0.4 | 1.667E-002 | 8.305E-004 | 3.379E-004 | 1.090 | 0.000 | 0.000 | 0.224 | 0.000 |
| 68 | RESTROOMFLR1_INFILTRATION | COMMONAREA_INFIL_SCH | RESTROOMFLR1 | 32.61 | 1.8 | 7.567E-003 | 2.320E-004 | 5.696E-004 | 0.249 | 0.000 | 0.000 | 0.224 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/person Area {m3/s-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {Pa} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{C}/Schedule | Maximum Indoor Temperature{C}/Schedule | Delta Temperature{C}/Schedule | Minimum Outdoor Temperature{C}/Schedule | Maximum Outdoor Temperature{C}/Schedule | Maximum WindSpeed{m/s} | |
| 1 | GUESTROOM103 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM103 | 32.61 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 2 | GUESTROOM104 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM104 | 32.61 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 3 | GUESTROOM105 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM105 | 32.61 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 4 | GUESTROOM202_205 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM202_205 | 130.45 | 6.0 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 5 | GUESTROOM206_208 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM206_208 | 105.36 | 4.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 6 | GUESTROOM209_212 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM209_212 | 130.45 | 6.0 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 7 | GUESTROOM213 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM213 | 32.61 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 8 | GUESTROOM214 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM214 | 32.61 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 9 | GUESTROOM219 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM219 | 32.61 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 10 | GUESTROOM220_223 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM220_223 | 130.44 | 6.0 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 11 | GUESTROOM224 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM224 | 32.61 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 12 | GUESTROOM309_312 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM309_312 | 130.45 | 6.0 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 13 | GUESTROOM314 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM314 | 32.61 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 14 | GUESTROOM315_318 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM315_318 | 130.44 | 6.0 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 15 | GUESTROOM320_323 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM320_323 | 130.44 | 6.0 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 16 | GUESTROOM401 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM401 | 32.61 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 17 | GUESTROOM409_412 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM409_412 | 130.45 | 6.0 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 18 | GUESTROOM415_418 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM415_418 | 130.44 | 6.0 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 19 | GUESTROOM419 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM419 | 32.61 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 20 | GUESTROOM420_423 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM420_423 | 130.44 | 6.0 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| 21 | GUESTROOM424 SLIDING DOOR VENTILATION | Constant-0.0 | GUESTROOM424 | 32.61 | 1.5 | 0.000 | 0.000 | 0.000 | 0.000 | Natural | 0.000 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 18.89 | 25.56 | -100.00 | 15.56 | 23.89 | 40.00 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | REARSTAIRSFLR1 | Mixing/Well-Stirred |
| 2 | CORRIDORFLR1 | Mixing/Well-Stirred |
| 3 | REARSTORAGEFLR1 | Mixing/Well-Stirred |
| 4 | FRONTLOUNGEFLR1 | Mixing/Well-Stirred |
| 5 | RESTROOMFLR1 | Mixing/Well-Stirred |
| 6 | MEETINGROOMFLR1 | Mixing/Well-Stirred |
| 7 | MECHANICALROOMFLR1 | Mixing/Well-Stirred |
| 8 | GUESTROOM101 | Mixing/Well-Stirred |
| 9 | GUESTROOM102 | Mixing/Well-Stirred |
| 10 | GUESTROOM103 | Mixing/Well-Stirred |
| 11 | GUESTROOM104 | Mixing/Well-Stirred |
| 12 | GUESTROOM105 | Mixing/Well-Stirred |
| 13 | EMPLOYEELOUNGEFLR1 | Mixing/Well-Stirred |
| 14 | LAUNDRYROOMFLR1 | Mixing/Well-Stirred |
| 15 | ELEVATORCOREFLR1 | Mixing/Well-Stirred |
| 16 | EXERCISECENTERFLR1 | Mixing/Well-Stirred |
| 17 | FRONTOFFICEFLR1 | Mixing/Well-Stirred |
| 18 | FRONTSTAIRSFLR1 | Mixing/Well-Stirred |
| 19 | FRONTSTORAGEFLR1 | Mixing/Well-Stirred |
| 20 | REARSTAIRSFLR2 | Mixing/Well-Stirred |
| 21 | CORRIDORFLR2 | Mixing/Well-Stirred |
| 22 | REARSTORAGEFLR2 | Mixing/Well-Stirred |
| 23 | GUESTROOM201 | Mixing/Well-Stirred |
| 24 | GUESTROOM202_205 | Mixing/Well-Stirred |
| 25 | GUESTROOM206_208 | Mixing/Well-Stirred |
| 26 | GUESTROOM209_212 | Mixing/Well-Stirred |
| 27 | GUESTROOM213 | Mixing/Well-Stirred |
| 28 | GUESTROOM214 | Mixing/Well-Stirred |
| 29 | GUESTROOM215_218 | Mixing/Well-Stirred |
| 30 | ELEVATORCOREFLR2 | Mixing/Well-Stirred |
| 31 | GUESTROOM219 | Mixing/Well-Stirred |
| 32 | GUESTROOM220_223 | Mixing/Well-Stirred |
| 33 | GUESTROOM224 | Mixing/Well-Stirred |
| 34 | FRONTSTORAGEFLR2 | Mixing/Well-Stirred |
| 35 | FRONTSTAIRSFLR2 | Mixing/Well-Stirred |
| 36 | REARSTAIRSFLR3 | Mixing/Well-Stirred |
| 37 | CORRIDORFLR3 | Mixing/Well-Stirred |
| 38 | REARSTORAGEFLR3 | Mixing/Well-Stirred |
| 39 | GUESTROOM301 | Mixing/Well-Stirred |
| 40 | GUESTROOM302_305 | Mixing/Well-Stirred |
| 41 | GUESTROOM306_308 | Mixing/Well-Stirred |
| 42 | GUESTROOM309_312 | Mixing/Well-Stirred |
| 43 | GUESTROOM313 | Mixing/Well-Stirred |
| 44 | GUESTROOM314 | Mixing/Well-Stirred |
| 45 | GUESTROOM315_318 | Mixing/Well-Stirred |
| 46 | ELEVATORCOREFLR3 | Mixing/Well-Stirred |
| 47 | GUESTROOM319 | Mixing/Well-Stirred |
| 48 | GUESTROOM320_323 | Mixing/Well-Stirred |
| 49 | GUESTROOM324 | Mixing/Well-Stirred |
| 50 | FRONTSTORAGEFLR3 | Mixing/Well-Stirred |
| 51 | FRONTSTAIRSFLR3 | Mixing/Well-Stirred |
| 52 | REARSTAIRSFLR4 | Mixing/Well-Stirred |
| 53 | CORRIDORFLR4 | Mixing/Well-Stirred |
| 54 | REARSTORAGEFLR4 | Mixing/Well-Stirred |
| 55 | GUESTROOM401 | Mixing/Well-Stirred |
| 56 | GUESTROOM402_405 | Mixing/Well-Stirred |
| 57 | GUESTROOM406_408 | Mixing/Well-Stirred |
| 58 | GUESTROOM409_412 | Mixing/Well-Stirred |
| 59 | GUESTROOM413 | Mixing/Well-Stirred |
| 60 | GUESTROOM414 | Mixing/Well-Stirred |
| 61 | GUESTROOM415_418 | Mixing/Well-Stirred |
| 62 | ELEVATORCOREFLR4 | Mixing/Well-Stirred |
| 63 | GUESTROOM419 | Mixing/Well-Stirred |
| 64 | GUESTROOM420_423 | Mixing/Well-Stirred |
| 65 | GUESTROOM424 | Mixing/Well-Stirred |
| 66 | FRONTSTORAGEFLR4 | Mixing/Well-Stirred |
| 67 | FRONTSTAIRSFLR4 | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2500 |
| 2 | Zone REARSTAIRSFLR1 | 1.2500 |
| 3 | Zone CORRIDORFLR1 | 1.2500 |
| 4 | Zone FRONTLOUNGEFLR1 | 1.2500 |
| 5 | Zone RESTROOMFLR1 | 1.2500 |
| 6 | Zone MEETINGROOMFLR1 | 1.2500 |
| 7 | Zone MECHANICALROOMFLR1 | 1.2500 |
| 8 | Zone GUESTROOM101 | 1.2500 |
| 9 | Zone GUESTROOM102 | 1.2500 |
| 10 | Zone GUESTROOM103 | 1.2500 |
| 11 | Zone GUESTROOM104 | 1.2500 |
| 12 | Zone GUESTROOM105 | 1.2500 |
| 13 | Zone EMPLOYEELOUNGEFLR1 | 1.2500 |
| 14 | Zone EXERCISECENTERFLR1 | 1.2500 |
| 15 | Zone FRONTOFFICEFLR1 | 1.2500 |
| 16 | Zone FRONTSTAIRSFLR1 | 1.2500 |
| 17 | Zone REARSTAIRSFLR2 | 1.2500 |
| 18 | Zone CORRIDORFLR2 | 1.2500 |
| 19 | Zone GUESTROOM201 | 1.2500 |
| 20 | Zone GUESTROOM202_205 | 1.2500 |
| 21 | Zone GUESTROOM206_208 | 1.2500 |
| 22 | Zone GUESTROOM209_212 | 1.2500 |
| 23 | Zone GUESTROOM213 | 1.2500 |
| 24 | Zone GUESTROOM214 | 1.2500 |
| 25 | Zone GUESTROOM215_218 | 1.2500 |
| 26 | Zone GUESTROOM219 | 1.2500 |
| 27 | Zone GUESTROOM220_223 | 1.2500 |
| 28 | Zone GUESTROOM224 | 1.2500 |
| 29 | Zone FRONTSTAIRSFLR2 | 1.2500 |
| 30 | Zone REARSTAIRSFLR3 | 1.2500 |
| 31 | Zone CORRIDORFLR3 | 1.2500 |
| 32 | Zone GUESTROOM301 | 1.2500 |
| 33 | Zone GUESTROOM302_305 | 1.2500 |
| 34 | Zone GUESTROOM306_308 | 1.2500 |
| 35 | Zone GUESTROOM309_312 | 1.2500 |
| 36 | Zone GUESTROOM313 | 1.2500 |
| 37 | Zone GUESTROOM314 | 1.2500 |
| 38 | Zone GUESTROOM315_318 | 1.2500 |
| 39 | Zone GUESTROOM319 | 1.2500 |
| 40 | Zone GUESTROOM320_323 | 1.2500 |
| 41 | Zone GUESTROOM324 | 1.2500 |
| 42 | Zone FRONTSTAIRSFLR3 | 1.2500 |
| 43 | Zone REARSTAIRSFLR4 | 1.2500 |
| 44 | Zone CORRIDORFLR4 | 1.2500 |
| 45 | Zone GUESTROOM401 | 1.2500 |
| 46 | Zone GUESTROOM402_405 | 1.2500 |
| 47 | Zone GUESTROOM406_408 | 1.2500 |
| 48 | Zone GUESTROOM409_412 | 1.2500 |
| 49 | Zone GUESTROOM413 | 1.2500 |
| 50 | Zone GUESTROOM414 | 1.2500 |
| 51 | Zone GUESTROOM415_418 | 1.2500 |
| 52 | Zone GUESTROOM419 | 1.2500 |
| 53 | Zone GUESTROOM420_423 | 1.2500 |
| 54 | Zone GUESTROOM424 | 1.2500 |
| 55 | Zone FRONTSTAIRSFLR4 | 1.2500 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.1500 |
| 2 | Zone REARSTAIRSFLR1 | 1.1500 |
| 3 | Zone CORRIDORFLR1 | 1.1500 |
| 4 | Zone FRONTLOUNGEFLR1 | 1.1500 |
| 5 | Zone RESTROOMFLR1 | 1.1500 |
| 6 | Zone MEETINGROOMFLR1 | 1.1500 |
| 7 | Zone MECHANICALROOMFLR1 | 1.1500 |
| 8 | Zone GUESTROOM101 | 1.1500 |
| 9 | Zone GUESTROOM102 | 1.1500 |
| 10 | Zone GUESTROOM103 | 1.1500 |
| 11 | Zone GUESTROOM104 | 1.1500 |
| 12 | Zone GUESTROOM105 | 1.1500 |
| 13 | Zone EMPLOYEELOUNGEFLR1 | 1.1500 |
| 14 | Zone EXERCISECENTERFLR1 | 1.1500 |
| 15 | Zone FRONTOFFICEFLR1 | 1.1500 |
| 16 | Zone FRONTSTAIRSFLR1 | 1.1500 |
| 17 | Zone REARSTAIRSFLR2 | 1.1500 |
| 18 | Zone CORRIDORFLR2 | 1.1500 |
| 19 | Zone GUESTROOM201 | 1.1500 |
| 20 | Zone GUESTROOM202_205 | 1.1500 |
| 21 | Zone GUESTROOM206_208 | 1.1500 |
| 22 | Zone GUESTROOM209_212 | 1.1500 |
| 23 | Zone GUESTROOM213 | 1.1500 |
| 24 | Zone GUESTROOM214 | 1.1500 |
| 25 | Zone GUESTROOM215_218 | 1.1500 |
| 26 | Zone GUESTROOM219 | 1.1500 |
| 27 | Zone GUESTROOM220_223 | 1.1500 |
| 28 | Zone GUESTROOM224 | 1.1500 |
| 29 | Zone FRONTSTAIRSFLR2 | 1.1500 |
| 30 | Zone REARSTAIRSFLR3 | 1.1500 |
| 31 | Zone CORRIDORFLR3 | 1.1500 |
| 32 | Zone GUESTROOM301 | 1.1500 |
| 33 | Zone GUESTROOM302_305 | 1.1500 |
| 34 | Zone GUESTROOM306_308 | 1.1500 |
| 35 | Zone GUESTROOM309_312 | 1.1500 |
| 36 | Zone GUESTROOM313 | 1.1500 |
| 37 | Zone GUESTROOM314 | 1.1500 |
| 38 | Zone GUESTROOM315_318 | 1.1500 |
| 39 | Zone GUESTROOM319 | 1.1500 |
| 40 | Zone GUESTROOM320_323 | 1.1500 |
| 41 | Zone GUESTROOM324 | 1.1500 |
| 42 | Zone FRONTSTAIRSFLR3 | 1.1500 |
| 43 | Zone REARSTAIRSFLR4 | 1.1500 |
| 44 | Zone CORRIDORFLR4 | 1.1500 |
| 45 | Zone GUESTROOM401 | 1.1500 |
| 46 | Zone GUESTROOM402_405 | 1.1500 |
| 47 | Zone GUESTROOM406_408 | 1.1500 |
| 48 | Zone GUESTROOM409_412 | 1.1500 |
| 49 | Zone GUESTROOM413 | 1.1500 |
| 50 | Zone GUESTROOM414 | 1.1500 |
| 51 | Zone GUESTROOM415_418 | 1.1500 |
| 52 | Zone GUESTROOM419 | 1.1500 |
| 53 | Zone GUESTROOM420_423 | 1.1500 |
| 54 | Zone GUESTROOM424 | 1.1500 |
| 55 | Zone FRONTSTAIRSFLR4 | 1.1500 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | REARSTAIRSFLR1 | Cooling | 0.00000 | 0.00000 | 0.00000 | 6.11790E-003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 28.22300 | 1.33633E-002 | 20.07186 | 1.08000 | 6.11790E-003 | 0.00000 |
| 2 | REARSTAIRSFLR1 | Heating | 13.51775 | 16.89718 | 1.01628E-003 | 6.11790E-003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 20.07186 | 1.08000 | 6.11790E-003 | 0.00000 |
| 3 | CORRIDORFLR1 | Cooling | 18841.14818 | 21667.32041 | 1.41766 | 1.63031 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 28.06800 | 1.33630E-002 | 150.50577 | 8.10000 | 4.58742E-002 | 0.00000 |
| 4 | CORRIDORFLR1 | Heating | 32507.83486 | 40634.79357 | 2.44010 | 3.05013 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 150.50577 | 8.10000 | 4.58742E-002 | 0.00000 |
| 5 | FRONTLOUNGEFLR1 | Cooling | 9021.87692 | 10375.15846 | 0.67886 | 0.78068 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 30.02100 | 1.33665E-002 | 163.05641 | 53.00000 | 0.23607 | 0.00000 |
| 6 | FRONTLOUNGEFLR1 | Heating | 3268.92294 | 4086.15368 | 0.24576 | 0.30720 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 163.05641 | 53.00000 | 0.23607 | 0.00000 |
| 7 | RESTROOMFLR1 | Cooling | 769.44112 | 884.85729 | 5.78577E-002 | 6.65363E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 29.24600 | 1.33651E-002 | 32.61128 | 1.75500 | 0.00000 | 0.00000 |
| 8 | RESTROOMFLR1 | Heating | 431.27033 | 539.08791 | 3.24237E-002 | 4.05296E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 19:10:00 | -16.30000 | 9.24091E-004 | 32.61128 | 1.75500 | 0.00000 | 0.00000 |
| 9 | MEETINGROOMFLR1 | Cooling | 4366.80329 | 5021.82378 | 0.32874 | 0.37805 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 80.27392 | 43.00000 | 0.12642 | 0.00000 |
| 10 | MEETINGROOMFLR1 | Heating | 1550.19345 | 1937.74181 | 0.11655 | 0.14568 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | -16.30000 | 9.24091E-004 | 80.27392 | 43.00000 | 0.12642 | 0.00000 |
| 11 | GUESTROOM101 | Cooling | 779.28217 | 896.17450 | 5.85907E-002 | 6.73793E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 30.02100 | 1.33665E-002 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 12 | GUESTROOM101 | Heating | 612.91125 | 766.13906 | 4.60798E-002 | 5.75997E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 13 | GUESTROOM102 | Cooling | 581.34933 | 668.55173 | 4.37090E-002 | 5.02654E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 30.02100 | 1.33665E-002 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 14 | GUESTROOM102 | Heating | 666.42986 | 833.03732 | 5.01034E-002 | 6.26292E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 15 | GUESTROOM103 | Cooling | 1264.86833 | 1454.59858 | 9.51070E-002 | 0.10937 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 26.90550 | 1.33609E-002 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 16 | GUESTROOM103 | Heating | 1129.15269 | 1411.44086 | 8.48918E-002 | 0.10611 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 17 | GUESTROOM104 | Cooling | 1528.98882 | 1758.33715 | 0.11497 | 0.13221 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30000 | 1.33670E-002 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 18 | GUESTROOM104 | Heating | 1166.60834 | 1458.26042 | 8.77078E-002 | 0.10963 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 19 | GUESTROOM105 | Cooling | 2041.66942 | 2347.91983 | 0.15351 | 0.17654 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.30000 | 1.33670E-002 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 20 | GUESTROOM105 | Heating | 677.99381 | 847.49226 | 5.09728E-002 | 6.37160E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 21 | EMPLOYEELOUNGEFLR1 | Cooling | 7772.31677 | 8938.16428 | 0.58493 | 0.67267 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.30000 | 1.33670E-002 | 32.60897 | 18.00000 | 5.13525E-002 | 0.00000 |
| 22 | EMPLOYEELOUNGEFLR1 | Heating | 686.72916 | 858.41145 | 5.16295E-002 | 6.45369E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 32.60897 | 18.00000 | 5.13525E-002 | 0.00000 |
| 23 | EXERCISECENTERFLR1 | Cooling | 1574.09057 | 1810.20415 | 0.11841 | 0.13617 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.99800 | 1.33646E-002 | 32.60897 | 7.00000 | 4.30699E-002 | 0.00000 |
| 24 | EXERCISECENTERFLR1 | Heating | 574.09418 | 717.61773 | 4.31614E-002 | 5.39518E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | -16.30000 | 9.24091E-004 | 32.60897 | 7.00000 | 4.30699E-002 | 0.00000 |
| 25 | FRONTOFFICEFLR1 | Cooling | 4528.23730 | 5207.47289 | 0.34052 | 0.39160 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.30000 | 1.33670E-002 | 130.43587 | 10.00000 | 5.63222E-002 | 0.00000 |
| 26 | FRONTOFFICEFLR1 | Heating | 2688.45788 | 3360.57234 | 0.20212 | 0.25265 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | -16.30000 | 9.24091E-004 | 130.43587 | 10.00000 | 5.63222E-002 | 0.00000 |
| 27 | FRONTSTAIRSFLR1 | Cooling | 0.00000 | 0.00000 | 0.00000 | 6.11644E-003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.30000 | 1.33670E-002 | 20.06706 | 1.08000 | 6.11644E-003 | 0.00000 |
| 28 | FRONTSTAIRSFLR1 | Heating | 287.80836 | 359.76045 | 2.16322E-002 | 2.70403E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 20.06706 | 1.08000 | 6.11644E-003 | 0.00000 |
| 29 | REARSTAIRSFLR2 | Cooling | 0.00000 | 0.00000 | 0.00000 | 6.11790E-003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 27.83550 | 1.33626E-002 | 20.07186 | 1.08000 | 6.11790E-003 | 0.00000 |
| 30 | REARSTAIRSFLR2 | Heating | 6.82366 | 8.52957 | 5.13019E-004 | 6.11790E-003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 20.07186 | 1.08000 | 6.11790E-003 | 0.00000 |
| 31 | CORRIDORFLR2 | Cooling | 3448.56220 | 3965.84653 | 0.25932 | 0.29822 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 29.49400 | 1.33655E-002 | 125.42017 | 6.75000 | 3.82281E-002 | 0.00000 |
| 32 | CORRIDORFLR2 | Heating | 1984.94173 | 2481.17716 | 0.14923 | 0.18653 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 16:30:00 | -16.30000 | 9.24091E-004 | 125.42017 | 6.75000 | 3.82281E-002 | 0.00000 |
| 33 | GUESTROOM201 | Cooling | 831.87247 | 956.65334 | 6.25478E-002 | 7.19300E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:40:00 | 29.58700 | 1.33657E-002 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 34 | GUESTROOM201 | Heating | 909.23973 | 1136.54966 | 6.83536E-002 | 8.54420E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 35 | GUESTROOM202_205 | Cooling | 4727.35083 | 5436.45346 | 0.35547 | 0.40879 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 26.90550 | 1.33609E-002 | 130.44512 | 6.00000 | 5.39191E-002 | 0.00000 |
| 36 | GUESTROOM202_205 | Heating | 2130.99719 | 2663.74649 | 0.16021 | 0.20026 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 130.44512 | 6.00000 | 5.39191E-002 | 0.00000 |
| 37 | GUESTROOM206_208 | Cooling | 3758.10098 | 4321.81613 | 0.28258 | 0.32497 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 26.90550 | 1.33609E-002 | 105.35952 | 4.50000 | 4.27331E-002 | 0.00000 |
| 38 | GUESTROOM206_208 | Heating | 1577.59420 | 1971.99274 | 0.11861 | 0.14826 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -16.30000 | 9.24091E-004 | 105.35952 | 4.50000 | 4.27331E-002 | 0.00000 |
| 39 | GUESTROOM209_212 | Cooling | 4584.46570 | 5272.13555 | 0.34472 | 0.39643 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 26.90550 | 1.33609E-002 | 130.44512 | 6.00000 | 5.39191E-002 | 0.00000 |
| 40 | GUESTROOM209_212 | Heating | 2067.05954 | 2583.82442 | 0.15540 | 0.19425 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 130.44512 | 6.00000 | 5.39191E-002 | 0.00000 |
| 41 | GUESTROOM213 | Cooling | 1282.49817 | 1474.87290 | 9.64342E-002 | 0.11090 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 26.90550 | 1.33609E-002 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 42 | GUESTROOM213 | Heating | 1009.39368 | 1261.74210 | 7.58877E-002 | 9.48596E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 43 | GUESTROOM214 | Cooling | 1660.35287 | 1909.40580 | 0.12485 | 0.14357 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30000 | 1.33670E-002 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 44 | GUESTROOM214 | Heating | 1008.61878 | 1260.77348 | 7.58294E-002 | 9.47868E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 45 | GUESTROOM215_218 | Cooling | 13293.30105 | 15287.29621 | 0.99947 | 1.14939 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22250 | 1.33668E-002 | 130.43587 | 6.00000 | 5.39153E-002 | 0.00000 |
| 46 | GUESTROOM215_218 | Heating | 2123.12037 | 2653.90046 | 0.15962 | 0.19952 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 130.43587 | 6.00000 | 5.39153E-002 | 0.00000 |
| 47 | GUESTROOM219 | Cooling | 7081.80489 | 8144.07562 | 0.53249 | 0.61236 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22250 | 1.33668E-002 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 48 | GUESTROOM219 | Heating | 545.84040 | 682.30050 | 4.10370E-002 | 5.12962E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 49 | GUESTROOM220_223 | Cooling | 5668.90068 | 6519.23578 | 0.42626 | 0.49020 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22250 | 1.33668E-002 | 130.43587 | 6.00000 | 5.39153E-002 | 0.00000 |
| 50 | GUESTROOM220_223 | Heating | 2079.52071 | 2599.40089 | 0.15634 | 0.19543 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | -16.30000 | 9.24091E-004 | 130.43587 | 6.00000 | 5.39153E-002 | 0.00000 |
| 51 | GUESTROOM224 | Cooling | 1633.84089 | 1878.91702 | 0.12285 | 0.14128 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30000 | 1.33670E-002 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 52 | GUESTROOM224 | Heating | 828.00745 | 1035.00931 | 6.22508E-002 | 7.78135E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | -16.30000 | 9.24091E-004 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 53 | FRONTSTAIRSFLR2 | Cooling | 0.00000 | 0.00000 | 0.00000 | 6.11644E-003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 30.20700 | 1.33668E-002 | 20.06706 | 1.08000 | 6.11644E-003 | 0.00000 |
| 54 | FRONTSTAIRSFLR2 | Heating | 259.82731 | 324.78414 | 1.95283E-002 | 2.44104E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 20.06706 | 1.08000 | 6.11644E-003 | 0.00000 |
| 55 | REARSTAIRSFLR3 | Cooling | 0.00000 | 0.00000 | 0.00000 | 6.11790E-003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 27.83550 | 1.33626E-002 | 20.07186 | 1.08000 | 6.11790E-003 | 0.00000 |
| 56 | REARSTAIRSFLR3 | Heating | 60.05004 | 75.06256 | 4.51416E-003 | 6.11790E-003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 20.07186 | 1.08000 | 6.11790E-003 | 0.00000 |
| 57 | CORRIDORFLR3 | Cooling | 1787.65726 | 2055.80585 | 0.13443 | 0.15459 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 29.24600 | 1.33651E-002 | 125.42017 | 6.75000 | 3.82281E-002 | 0.00000 |
| 58 | CORRIDORFLR3 | Heating | 2307.20409 | 2884.00511 | 0.17345 | 0.21682 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 125.42017 | 6.75000 | 3.82281E-002 | 0.00000 |
| 59 | GUESTROOM301 | Cooling | 586.74330 | 674.75480 | 4.41171E-002 | 5.07347E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 29.91250 | 1.33663E-002 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 60 | GUESTROOM301 | Heating | 965.72560 | 1207.15700 | 7.25993E-002 | 9.07492E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 61 | GUESTROOM302_305 | Cooling | 1755.70972 | 2019.06618 | 0.13201 | 0.15181 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.13800 | 1.33613E-002 | 130.44512 | 6.00000 | 5.39191E-002 | 0.00000 |
| 62 | GUESTROOM302_305 | Heating | 2306.84815 | 2883.56019 | 0.17343 | 0.21679 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 130.44512 | 6.00000 | 5.39191E-002 | 0.00000 |
| 63 | GUESTROOM306_308 | Cooling | 1445.86705 | 1662.74711 | 0.10871 | 0.12502 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.13800 | 1.33613E-002 | 105.35952 | 4.50000 | 4.27331E-002 | 0.00000 |
| 64 | GUESTROOM306_308 | Heating | 1770.64836 | 2213.31045 | 0.13312 | 0.16640 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:10:00 | -16.30000 | 9.24091E-004 | 105.35952 | 4.50000 | 4.27331E-002 | 0.00000 |
| 65 | GUESTROOM309_312 | Cooling | 4439.25670 | 5105.14520 | 0.33380 | 0.38387 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.13800 | 1.33613E-002 | 130.44512 | 6.00000 | 5.39191E-002 | 0.00000 |
| 66 | GUESTROOM309_312 | Heating | 2315.14169 | 2893.92711 | 0.17405 | 0.21757 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 130.44512 | 6.00000 | 5.39191E-002 | 0.00000 |
| 67 | GUESTROOM313 | Cooling | 701.90307 | 807.18853 | 5.27732E-002 | 6.06892E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 26.90550 | 1.33609E-002 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 68 | GUESTROOM313 | Heating | 1085.27015 | 1356.58768 | 8.15919E-002 | 0.10199 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 69 | GUESTROOM314 | Cooling | 1514.97077 | 1742.21639 | 0.11391 | 0.13100 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.30000 | 1.33670E-002 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 70 | GUESTROOM314 | Heating | 1051.79898 | 1314.74872 | 7.90756E-002 | 9.88445E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 71 | GUESTROOM315_318 | Cooling | 6281.71374 | 7223.97080 | 0.47234 | 0.54319 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30000 | 1.33670E-002 | 130.43587 | 6.00000 | 5.39153E-002 | 0.00000 |
| 72 | GUESTROOM315_318 | Heating | 2314.76172 | 2893.45215 | 0.17403 | 0.21753 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 130.43587 | 6.00000 | 5.39153E-002 | 0.00000 |
| 73 | GUESTROOM319 | Cooling | 1386.11769 | 1594.03535 | 0.10422 | 0.11985 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30000 | 1.33670E-002 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 74 | GUESTROOM319 | Heating | 647.52429 | 809.40536 | 4.86816E-002 | 6.08520E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | -16.30000 | 9.24091E-004 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 75 | GUESTROOM320_323 | Cooling | 5348.63282 | 6150.92775 | 0.40218 | 0.46251 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30000 | 1.33670E-002 | 130.43587 | 6.00000 | 5.39153E-002 | 0.00000 |
| 76 | GUESTROOM320_323 | Heating | 2278.05748 | 2847.57185 | 0.17127 | 0.21408 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:20:00 | -16.30000 | 9.24091E-004 | 130.43587 | 6.00000 | 5.39153E-002 | 0.00000 |
| 77 | GUESTROOM324 | Cooling | 950.18623 | 1092.71417 | 7.14406E-002 | 8.21567E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 30.30000 | 1.33670E-002 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 78 | GUESTROOM324 | Heating | 883.97450 | 1104.96813 | 6.64583E-002 | 8.30729E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 79 | FRONTSTAIRSFLR3 | Cooling | 0.00000 | 0.00000 | 0.00000 | 6.11644E-003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 30.02100 | 1.33665E-002 | 20.06706 | 1.08000 | 6.11644E-003 | 0.00000 |
| 80 | FRONTSTAIRSFLR3 | Heating | 323.43539 | 404.29424 | 2.43076E-002 | 3.03845E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 20.06706 | 1.08000 | 6.11644E-003 | 0.00000 |
| 81 | REARSTAIRSFLR4 | Cooling | 0.00000 | 0.00000 | 0.00000 | 6.11790E-003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 28.99800 | 1.33646E-002 | 20.07186 | 1.08000 | 6.11790E-003 | 0.00000 |
| 82 | REARSTAIRSFLR4 | Heating | 232.44558 | 290.55698 | 1.74705E-002 | 2.18381E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 20.07186 | 1.08000 | 6.11790E-003 | 0.00000 |
| 83 | CORRIDORFLR4 | Cooling | 2951.06015 | 3393.71917 | 0.22191 | 0.25520 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 30.30000 | 1.33670E-002 | 125.42017 | 6.75000 | 3.82281E-002 | 0.00000 |
| 84 | CORRIDORFLR4 | Heating | 3846.18587 | 4807.73233 | 0.28915 | 0.36144 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 125.42017 | 6.75000 | 3.82281E-002 | 0.00000 |
| 85 | GUESTROOM401 | Cooling | 1558.05717 | 1791.76575 | 0.11716 | 0.13473 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.99000 | 1.33664E-002 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 86 | GUESTROOM401 | Heating | 1309.36772 | 1636.70965 | 9.84326E-002 | 0.12304 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 87 | GUESTROOM402_405 | Cooling | 2693.46019 | 3097.47922 | 0.20251 | 0.23289 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.30000 | 1.33670E-002 | 130.44512 | 6.00000 | 5.39191E-002 | 0.00000 |
| 88 | GUESTROOM402_405 | Heating | 3508.30185 | 4385.37732 | 0.26376 | 0.32970 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 130.44512 | 6.00000 | 5.39191E-002 | 0.00000 |
| 89 | GUESTROOM406_408 | Cooling | 2189.74981 | 2518.21228 | 0.16464 | 0.18933 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.30000 | 1.33670E-002 | 105.35952 | 4.50000 | 4.27331E-002 | 0.00000 |
| 90 | GUESTROOM406_408 | Heating | 2764.13296 | 3455.16620 | 0.20781 | 0.25976 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 105.35952 | 4.50000 | 4.27331E-002 | 0.00000 |
| 91 | GUESTROOM409_412 | Cooling | 5741.39957 | 6602.60950 | 0.43172 | 0.49647 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 30.30000 | 1.33670E-002 | 130.44512 | 6.00000 | 5.39191E-002 | 0.00000 |
| 92 | GUESTROOM409_412 | Heating | 3529.68181 | 4412.10227 | 0.26536 | 0.33171 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 130.44512 | 6.00000 | 5.39191E-002 | 0.00000 |
| 93 | GUESTROOM413 | Cooling | 989.11488 | 1137.48211 | 7.43676E-002 | 8.55227E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 94 | GUESTROOM413 | Heating | 1462.45120 | 1828.06400 | 0.10995 | 0.13744 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 32.61128 | 1.50000 | 1.34798E-002 | 0.00000 |
| 95 | GUESTROOM414 | Cooling | 1322.28338 | 1520.62589 | 9.94171E-002 | 0.11433 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30000 | 1.33670E-002 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 96 | GUESTROOM414 | Heating | 1388.69465 | 1735.86832 | 0.10440 | 0.13050 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 97 | GUESTROOM415_418 | Cooling | 7128.24341 | 8197.47992 | 0.53600 | 0.61640 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 130.43587 | 6.00000 | 5.39153E-002 | 0.00000 |
| 98 | GUESTROOM415_418 | Heating | 3517.62373 | 4397.02966 | 0.26446 | 0.33057 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 130.43587 | 6.00000 | 5.39153E-002 | 0.00000 |
| 99 | GUESTROOM419 | Cooling | 1919.77823 | 2207.74497 | 0.14435 | 0.16601 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22250 | 1.33668E-002 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 100 | GUESTROOM419 | Heating | 1031.52109 | 1289.40136 | 7.75509E-002 | 9.69386E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 101 | GUESTROOM420_423 | Cooling | 7027.07088 | 8081.13152 | 0.52839 | 0.60765 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 30.14500 | 1.33667E-002 | 130.43587 | 6.00000 | 5.39153E-002 | 0.00000 |
| 102 | GUESTROOM420_423 | Heating | 3481.01322 | 4351.26652 | 0.26171 | 0.32713 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 130.43587 | 6.00000 | 5.39153E-002 | 0.00000 |
| 103 | GUESTROOM424 | Cooling | 1960.76757 | 2254.88270 | 0.14743 | 0.16955 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 30.30000 | 1.33670E-002 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 104 | GUESTROOM424 | Heating | 1249.11023 | 1561.38779 | 9.39096E-002 | 0.11739 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 32.60897 | 1.50000 | 1.34788E-002 | 0.00000 |
| 105 | FRONTSTAIRSFLR4 | Cooling | 0.00000 | 0.00000 | 0.00000 | 6.11644E-003 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 30.20700 | 1.33668E-002 | 20.06706 | 1.08000 | 6.11644E-003 | 0.00000 |
| 106 | FRONTSTAIRSFLR4 | Heating | 521.75023 | 652.18779 | 3.92092E-002 | 4.90115E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | -16.30000 | 9.24091E-004 | 20.06706 | 1.08000 | 6.11644E-003 | 0.00000 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | ZoneHVAC:UnitHeater | REARSTAIRSFLR1 UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.11790E-003 |
| 2 | Fan:ConstantVolume | REARSTAIRSFLR1 UNITHEATER FAN | Design Size Maximum Flow Rate [m3/s] | 6.11790E-003 |
| 3 | Coil:Heating:Fuel | REARSTAIRSFLR1 UNITHEATER HEATING COIL | Design Size Nominal Capacity [W] | 81.37520 |
| 4 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR1 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.05013 |
| 5 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR1 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 3.05013 |
| 6 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR1 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 3.05013 |
| 7 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR1 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 4.58742E-002 |
| 8 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR1 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 4.58742E-002 |
| 9 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR1 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.58742E-002 |
| 10 | Coil:Heating:Water | CORRIDORFLR1 PTAC HEATING COIL | Design Size Rated Capacity [W] | 42709.15647 |
| 11 | Coil:Heating:Water | CORRIDORFLR1 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.73638E-004 |
| 12 | Coil:Heating:Water | CORRIDORFLR1 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1073.08833 |
| 13 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR1 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 3.05013 |
| 14 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR1 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 57197.48837 |
| 15 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR1 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80054 |
| 16 | Fan:OnOff | CORRIDORFLR1 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 3.05013 |
| 17 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_FRONTLOUNGE | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.78068 |
| 18 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_FRONTLOUNGE | Design Size Heating Supply Air Flow Rate [m3/s] | 0.78068 |
| 19 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_FRONTLOUNGE | Design Size No Load Supply Air Flow Rate [m3/s] | 0.78068 |
| 20 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_FRONTLOUNGE | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.23607 |
| 21 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_FRONTLOUNGE | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.23607 |
| 22 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_FRONTLOUNGE | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.23607 |
| 23 | Coil:Heating:Water | SAC_FRONTLOUNGE HEATING COIL | Design Size Rated Capacity [W] | 20956.11401 |
| 24 | Coil:Heating:Water | SAC_FRONTLOUNGE HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.83333E-004 |
| 25 | Coil:Heating:Water | SAC_FRONTLOUNGE HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 477.97967 |
| 26 | Coil:Cooling:DX:SingleSpeed | SAC_FRONTLOUNGE PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.78068 |
| 27 | Coil:Cooling:DX:SingleSpeed | SAC_FRONTLOUNGE PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 17965.83701 |
| 28 | Coil:Cooling:DX:SingleSpeed | SAC_FRONTLOUNGE PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.72546 |
| 29 | Fan:OnOff | SAC_FRONTLOUNGE_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.78068 |
| 30 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_RESTROOM | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.65363E-002 |
| 31 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_RESTROOM | Design Size Heating Supply Air Flow Rate [m3/s] | 6.65363E-002 |
| 32 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_RESTROOM | Design Size No Load Supply Air Flow Rate [m3/s] | 6.65363E-002 |
| 33 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_RESTROOM | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.00000 |
| 34 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_RESTROOM | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.00000 |
| 35 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_RESTROOM | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.00000 |
| 36 | Coil:Heating:Water | SAC_RESTROOM HEATING COIL | Design Size Rated Capacity [W] | 885.00638 |
| 37 | Coil:Heating:Water | SAC_RESTROOM HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.74242E-006 |
| 38 | Coil:Heating:Water | SAC_RESTROOM HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 22.36489 |
| 39 | Coil:Cooling:DX:SingleSpeed | SAC_RESTROOM PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 6.65363E-002 |
| 40 | Coil:Cooling:DX:SingleSpeed | SAC_RESTROOM PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 1101.41257 |
| 41 | Coil:Cooling:DX:SingleSpeed | SAC_RESTROOM PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 42 | Fan:OnOff | SAC_RESTROOM_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 6.65363E-002 |
| 43 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_MEETINGROOM | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.37805 |
| 44 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_MEETINGROOM | Design Size Heating Supply Air Flow Rate [m3/s] | 0.37805 |
| 45 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_MEETINGROOM | Design Size No Load Supply Air Flow Rate [m3/s] | 0.37805 |
| 46 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_MEETINGROOM | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 0.12642 |
| 47 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_MEETINGROOM | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 0.12642 |
| 48 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_MEETINGROOM | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.12642 |
| 49 | Coil:Heating:Water | SAC_MEETINGROOM HEATING COIL | Design Size Rated Capacity [W] | 10689.70546 |
| 50 | Coil:Heating:Water | SAC_MEETINGROOM HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.35182E-005 |
| 51 | Coil:Heating:Water | SAC_MEETINGROOM HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 241.60488 |
| 52 | Coil:Cooling:DX:SingleSpeed | SAC_MEETINGROOM PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.37805 |
| 53 | Coil:Cooling:DX:SingleSpeed | SAC_MEETINGROOM PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 9387.81361 |
| 54 | Coil:Cooling:DX:SingleSpeed | SAC_MEETINGROOM PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.70108 |
| 55 | Fan:OnOff | SAC_MEETINGROOM_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.37805 |
| 56 | ZoneHVAC:UnitHeater | MECHANICALROOMFLR1 UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 0.00000 |
| 57 | Fan:ConstantVolume | MECHRM UNITHEATER FAN | Design Size Maximum Flow Rate [m3/s] | 0.00000 |
| 58 | Coil:Heating:Fuel | MECHRM UNITHEATER HEATING COIL | Design Size Nominal Capacity [W] | 0.00000 |
| 59 | ZoneHVAC:PackagedTerminalAirConditioner | 101 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.73793E-002 |
| 60 | ZoneHVAC:PackagedTerminalAirConditioner | 101 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 6.73793E-002 |
| 61 | ZoneHVAC:PackagedTerminalAirConditioner | 101 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 6.73793E-002 |
| 62 | ZoneHVAC:PackagedTerminalAirConditioner | 101 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34798E-002 |
| 63 | ZoneHVAC:PackagedTerminalAirConditioner | 101 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34798E-002 |
| 64 | ZoneHVAC:PackagedTerminalAirConditioner | 101 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34798E-002 |
| 65 | Coil:Heating:Water | 101 PTAC HEATING COIL | Design Size Rated Capacity [W] | 1499.88310 |
| 66 | Coil:Heating:Water | 101 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.31216E-005 |
| 67 | Coil:Heating:Water | 101 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 35.29089 |
| 68 | Coil:Cooling:DX:SingleSpeed | 101 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 6.73793E-002 |
| 69 | Coil:Cooling:DX:SingleSpeed | 101 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 1354.40124 |
| 70 | Coil:Cooling:DX:SingleSpeed | 101 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.77377 |
| 71 | Fan:OnOff | 101 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 6.73793E-002 |
| 72 | ZoneHVAC:PackagedTerminalAirConditioner | 102 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 6.26292E-002 |
| 73 | ZoneHVAC:PackagedTerminalAirConditioner | 102 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 6.26292E-002 |
| 74 | ZoneHVAC:PackagedTerminalAirConditioner | 102 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 6.26292E-002 |
| 75 | ZoneHVAC:PackagedTerminalAirConditioner | 102 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34798E-002 |
| 76 | ZoneHVAC:PackagedTerminalAirConditioner | 102 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34798E-002 |
| 77 | ZoneHVAC:PackagedTerminalAirConditioner | 102 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34798E-002 |
| 78 | Coil:Heating:Water | 102 PTAC HEATING COIL | Design Size Rated Capacity [W] | 1436.70247 |
| 79 | Coil:Heating:Water | 102 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.25689E-005 |
| 80 | Coil:Heating:Water | 102 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 33.64151 |
| 81 | Coil:Cooling:DX:SingleSpeed | 102 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 6.26292E-002 |
| 82 | Coil:Cooling:DX:SingleSpeed | 102 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 1351.87773 |
| 83 | Coil:Cooling:DX:SingleSpeed | 102 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.74695 |
| 84 | Fan:OnOff | 102 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 6.26292E-002 |
| 85 | ZoneHVAC:PackagedTerminalAirConditioner | 103 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.10937 |
| 86 | ZoneHVAC:PackagedTerminalAirConditioner | 103 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.10937 |
| 87 | ZoneHVAC:PackagedTerminalAirConditioner | 103 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.10937 |
| 88 | ZoneHVAC:PackagedTerminalAirConditioner | 103 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34798E-002 |
| 89 | ZoneHVAC:PackagedTerminalAirConditioner | 103 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34798E-002 |
| 90 | ZoneHVAC:PackagedTerminalAirConditioner | 103 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34798E-002 |
| 91 | Coil:Heating:Water | 103 PTAC HEATING COIL | Design Size Rated Capacity [W] | 2058.44510 |
| 92 | Coil:Heating:Water | 103 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.80082E-005 |
| 93 | Coil:Heating:Water | 103 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 49.68848 |
| 94 | Coil:Cooling:DX:SingleSpeed | 103 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.10937 |
| 95 | Coil:Cooling:DX:SingleSpeed | 103 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 1954.16149 |
| 96 | Coil:Cooling:DX:SingleSpeed | 103 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80063 |
| 97 | Fan:OnOff | 103 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.10937 |
| 98 | ZoneHVAC:PackagedTerminalAirConditioner | 104 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.13221 |
| 99 | ZoneHVAC:PackagedTerminalAirConditioner | 104 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.13221 |
| 100 | ZoneHVAC:PackagedTerminalAirConditioner | 104 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.13221 |
| 101 | ZoneHVAC:PackagedTerminalAirConditioner | 104 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34788E-002 |
| 102 | ZoneHVAC:PackagedTerminalAirConditioner | 104 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34788E-002 |
| 103 | ZoneHVAC:PackagedTerminalAirConditioner | 104 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34788E-002 |
| 104 | Coil:Heating:Water | 104 PTAC HEATING COIL | Design Size Rated Capacity [W] | 2362.17455 |
| 105 | Coil:Heating:Water | 104 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.06653E-005 |
| 106 | Coil:Heating:Water | 104 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 57.44810 |
| 107 | Coil:Cooling:DX:SingleSpeed | 104 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.13221 |
| 108 | Coil:Cooling:DX:SingleSpeed | 104 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 2432.31568 |
| 109 | Coil:Cooling:DX:SingleSpeed | 104 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80081 |
| 110 | Fan:OnOff | 104 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.13221 |
| 111 | ZoneHVAC:PackagedTerminalAirConditioner | 105 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.17654 |
| 112 | ZoneHVAC:PackagedTerminalAirConditioner | 105 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.17654 |
| 113 | ZoneHVAC:PackagedTerminalAirConditioner | 105 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.17654 |
| 114 | ZoneHVAC:PackagedTerminalAirConditioner | 105 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34788E-002 |
| 115 | ZoneHVAC:PackagedTerminalAirConditioner | 105 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34788E-002 |
| 116 | ZoneHVAC:PackagedTerminalAirConditioner | 105 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34788E-002 |
| 117 | Coil:Heating:Water | 105 PTAC HEATING COIL | Design Size Rated Capacity [W] | 2951.82428 |
| 118 | Coil:Heating:Water | 105 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.58238E-005 |
| 119 | Coil:Heating:Water | 105 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 72.45493 |
| 120 | Coil:Cooling:DX:SingleSpeed | 105 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.17654 |
| 121 | Coil:Cooling:DX:SingleSpeed | 105 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 3118.36598 |
| 122 | Coil:Cooling:DX:SingleSpeed | 105 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80055 |
| 123 | Fan:OnOff | 105 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.17654 |
| 124 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_EMPLOYEELOUNGE | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.67267 |
| 125 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_EMPLOYEELOUNGE | Design Size Heating Supply Air Flow Rate [m3/s] | 0.67267 |
| 126 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_EMPLOYEELOUNGE | Design Size No Load Supply Air Flow Rate [m3/s] | 0.67267 |
| 127 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_EMPLOYEELOUNGE | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 5.13525E-002 |
| 128 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_EMPLOYEELOUNGE | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 5.13525E-002 |
| 129 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_EMPLOYEELOUNGE | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.13525E-002 |
| 130 | Coil:Heating:Water | SAC_EMPLOYEELOUNGE HEATING COIL | Design Size Rated Capacity [W] | 11247.00560 |
| 131 | Coil:Heating:Water | SAC_EMPLOYEELOUNGE HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.83937E-005 |
| 132 | Coil:Heating:Water | SAC_EMPLOYEELOUNGE HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 276.06751 |
| 133 | Coil:Cooling:DX:SingleSpeed | SAC_EMPLOYEELOUNGE PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.67267 |
| 134 | Coil:Cooling:DX:SingleSpeed | SAC_EMPLOYEELOUNGE PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 11942.52512 |
| 135 | Coil:Cooling:DX:SingleSpeed | SAC_EMPLOYEELOUNGE PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80080 |
| 136 | Fan:OnOff | SAC_EMPLOYEELOUNGE_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.67267 |
| 137 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_EXERCISECENTER | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.13617 |
| 138 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_EXERCISECENTER | Design Size Heating Supply Air Flow Rate [m3/s] | 0.13617 |
| 139 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_EXERCISECENTER | Design Size No Load Supply Air Flow Rate [m3/s] | 0.13617 |
| 140 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_EXERCISECENTER | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 4.30699E-002 |
| 141 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_EXERCISECENTER | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 4.30699E-002 |
| 142 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_EXERCISECENTER | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.30699E-002 |
| 143 | Coil:Heating:Water | SAC_EXERCISECENTER HEATING COIL | Design Size Rated Capacity [W] | 3739.96361 |
| 144 | Coil:Heating:Water | SAC_EXERCISECENTER HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.27188E-005 |
| 145 | Coil:Heating:Water | SAC_EXERCISECENTER HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 84.96237 |
| 146 | Coil:Cooling:DX:SingleSpeed | SAC_EXERCISECENTER PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.13617 |
| 147 | Coil:Cooling:DX:SingleSpeed | SAC_EXERCISECENTER PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 3011.23028 |
| 148 | Coil:Cooling:DX:SingleSpeed | SAC_EXERCISECENTER PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.73921 |
| 149 | Fan:OnOff | SAC_EXERCISECENTER_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.13617 |
| 150 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_FRONTOFFICE | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.39160 |
| 151 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_FRONTOFFICE | Design Size Heating Supply Air Flow Rate [m3/s] | 0.39160 |
| 152 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_FRONTOFFICE | Design Size No Load Supply Air Flow Rate [m3/s] | 0.39160 |
| 153 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_FRONTOFFICE | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 5.63222E-002 |
| 154 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_FRONTOFFICE | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 5.63222E-002 |
| 155 | ZoneHVAC:PackagedTerminalAirConditioner | SAC_FRONTOFFICE | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.63222E-002 |
| 156 | Coil:Heating:Water | SAC_FRONTOFFICE HEATING COIL | Design Size Rated Capacity [W] | 7731.00554 |
| 157 | Coil:Heating:Water | SAC_FRONTOFFICE HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.76342E-005 |
| 158 | Coil:Heating:Water | SAC_FRONTOFFICE HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 185.30775 |
| 159 | Coil:Cooling:DX:SingleSpeed | SAC_FRONTOFFICE PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.39160 |
| 160 | Coil:Cooling:DX:SingleSpeed | SAC_FRONTOFFICE PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7443.65014 |
| 161 | Coil:Cooling:DX:SingleSpeed | SAC_FRONTOFFICE PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79718 |
| 162 | Fan:OnOff | SAC_FRONTOFFICE_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.39160 |
| 163 | ZoneHVAC:UnitHeater | FRONTSTAIRSFLR1 UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.70403E-002 |
| 164 | Fan:ConstantVolume | FRONTSTAIRSFLR1 UNITHEATER FAN | Design Size Maximum Flow Rate [m3/s] | 2.70403E-002 |
| 165 | Coil:Heating:Fuel | FRONTSTAIRSFLR1 UNITHEATER HEATING COIL | Design Size Nominal Capacity [W] | 359.76046 |
| 166 | ZoneHVAC:UnitHeater | REARSTAIRSFLR2 UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.11790E-003 |
| 167 | Fan:ConstantVolume | REARSTAIRSFLR2 UNITHEATER FAN | Design Size Maximum Flow Rate [m3/s] | 6.11790E-003 |
| 168 | Coil:Heating:Fuel | REARSTAIRSFLR2 UNITHEATER HEATING COIL | Design Size Nominal Capacity [W] | 81.37418 |
| 169 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR2 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.29822 |
| 170 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR2 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.29822 |
| 171 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR2 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.29822 |
| 172 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR2 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 3.82281E-002 |
| 173 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR2 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 3.82281E-002 |
| 174 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR2 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 3.82281E-002 |
| 175 | Coil:Heating:Water | CORRIDORFLR2 PTAC HEATING COIL | Design Size Rated Capacity [W] | 5678.68583 |
| 176 | Coil:Heating:Water | CORRIDORFLR2 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.96796E-005 |
| 177 | Coil:Heating:Water | CORRIDORFLR2 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 136.85592 |
| 178 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR2 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.29822 |
| 179 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR2 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5515.62465 |
| 180 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR2 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80006 |
| 181 | Fan:OnOff | CORRIDORFLR2 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.29822 |
| 182 | ZoneHVAC:PackagedTerminalAirConditioner | 201 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.54420E-002 |
| 183 | ZoneHVAC:PackagedTerminalAirConditioner | 201 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 8.54420E-002 |
| 184 | ZoneHVAC:PackagedTerminalAirConditioner | 201 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 8.54420E-002 |
| 185 | ZoneHVAC:PackagedTerminalAirConditioner | 201 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34798E-002 |
| 186 | ZoneHVAC:PackagedTerminalAirConditioner | 201 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34798E-002 |
| 187 | ZoneHVAC:PackagedTerminalAirConditioner | 201 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34798E-002 |
| 188 | Coil:Heating:Water | 201 PTAC HEATING COIL | Design Size Rated Capacity [W] | 1740.18912 |
| 189 | Coil:Heating:Water | 201 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.52239E-005 |
| 190 | Coil:Heating:Water | 201 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 41.51882 |
| 191 | Coil:Cooling:DX:SingleSpeed | 201 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 8.54420E-002 |
| 192 | Coil:Cooling:DX:SingleSpeed | 201 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 1711.21028 |
| 193 | Coil:Cooling:DX:SingleSpeed | 201 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.77588 |
| 194 | Fan:OnOff | 201 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 8.54420E-002 |
| 195 | ZoneHVAC:PackagedTerminalAirConditioner | 202_205 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.40879 |
| 196 | ZoneHVAC:PackagedTerminalAirConditioner | 202_205 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.40879 |
| 197 | ZoneHVAC:PackagedTerminalAirConditioner | 202_205 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.40879 |
| 198 | ZoneHVAC:PackagedTerminalAirConditioner | 202_205 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 5.39191E-002 |
| 199 | ZoneHVAC:PackagedTerminalAirConditioner | 202_205 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 5.39191E-002 |
| 200 | ZoneHVAC:PackagedTerminalAirConditioner | 202_205 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.39191E-002 |
| 201 | Coil:Heating:Water | 202_205 PTAC HEATING COIL | Design Size Rated Capacity [W] | 7851.96743 |
| 202 | Coil:Heating:Water | 202_205 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.86924E-005 |
| 203 | Coil:Heating:Water | 202_205 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 188.97909 |
| 204 | Coil:Cooling:DX:SingleSpeed | 202_205 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.40879 |
| 205 | Coil:Cooling:DX:SingleSpeed | 202_205 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7388.41052 |
| 206 | Coil:Cooling:DX:SingleSpeed | 202_205 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80073 |
| 207 | Fan:OnOff | 202_205 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.40879 |
| 208 | ZoneHVAC:PackagedTerminalAirConditioner | 206_208 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.32497 |
| 209 | ZoneHVAC:PackagedTerminalAirConditioner | 206_208 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.32497 |
| 210 | ZoneHVAC:PackagedTerminalAirConditioner | 206_208 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.32497 |
| 211 | ZoneHVAC:PackagedTerminalAirConditioner | 206_208 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 4.27331E-002 |
| 212 | ZoneHVAC:PackagedTerminalAirConditioner | 206_208 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 4.27331E-002 |
| 213 | ZoneHVAC:PackagedTerminalAirConditioner | 206_208 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.27331E-002 |
| 214 | Coil:Heating:Water | 206_208 PTAC HEATING COIL | Design Size Rated Capacity [W] | 6236.20335 |
| 215 | Coil:Heating:Water | 206_208 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.45570E-005 |
| 216 | Coil:Heating:Water | 206_208 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 150.11299 |
| 217 | Coil:Cooling:DX:SingleSpeed | 206_208 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.32497 |
| 218 | Coil:Cooling:DX:SingleSpeed | 206_208 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5861.34681 |
| 219 | Coil:Cooling:DX:SingleSpeed | 206_208 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80042 |
| 220 | Fan:OnOff | 206_208 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.32497 |
| 221 | ZoneHVAC:PackagedTerminalAirConditioner | 209_212 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.39643 |
| 222 | ZoneHVAC:PackagedTerminalAirConditioner | 209_212 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.39643 |
| 223 | ZoneHVAC:PackagedTerminalAirConditioner | 209_212 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.39643 |
| 224 | ZoneHVAC:PackagedTerminalAirConditioner | 209_212 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 5.39191E-002 |
| 225 | ZoneHVAC:PackagedTerminalAirConditioner | 209_212 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 5.39191E-002 |
| 226 | ZoneHVAC:PackagedTerminalAirConditioner | 209_212 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.39191E-002 |
| 227 | Coil:Heating:Water | 209_212 PTAC HEATING COIL | Design Size Rated Capacity [W] | 7687.65983 |
| 228 | Coil:Heating:Water | 209_212 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.72550E-005 |
| 229 | Coil:Heating:Water | 209_212 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 184.76404 |
| 230 | Coil:Cooling:DX:SingleSpeed | 209_212 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.39643 |
| 231 | Coil:Cooling:DX:SingleSpeed | 209_212 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7203.25784 |
| 232 | Coil:Cooling:DX:SingleSpeed | 209_212 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80094 |
| 233 | Fan:OnOff | 209_212 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.39643 |
| 234 | ZoneHVAC:PackagedTerminalAirConditioner | 213 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.11090 |
| 235 | ZoneHVAC:PackagedTerminalAirConditioner | 213 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.11090 |
| 236 | ZoneHVAC:PackagedTerminalAirConditioner | 213 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.11090 |
| 237 | ZoneHVAC:PackagedTerminalAirConditioner | 213 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34798E-002 |
| 238 | ZoneHVAC:PackagedTerminalAirConditioner | 213 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34798E-002 |
| 239 | ZoneHVAC:PackagedTerminalAirConditioner | 213 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34798E-002 |
| 240 | Coil:Heating:Water | 213 PTAC HEATING COIL | Design Size Rated Capacity [W] | 2078.75346 |
| 241 | Coil:Heating:Water | 213 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.81858E-005 |
| 242 | Coil:Heating:Water | 213 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 50.20852 |
| 243 | Coil:Cooling:DX:SingleSpeed | 213 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.11090 |
| 244 | Coil:Cooling:DX:SingleSpeed | 213 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 1977.30328 |
| 245 | Coil:Cooling:DX:SingleSpeed | 213 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80034 |
| 246 | Fan:OnOff | 213 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.11090 |
| 247 | ZoneHVAC:PackagedTerminalAirConditioner | 214 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.14357 |
| 248 | ZoneHVAC:PackagedTerminalAirConditioner | 214 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.14357 |
| 249 | ZoneHVAC:PackagedTerminalAirConditioner | 214 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.14357 |
| 250 | ZoneHVAC:PackagedTerminalAirConditioner | 214 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34788E-002 |
| 251 | ZoneHVAC:PackagedTerminalAirConditioner | 214 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34788E-002 |
| 252 | ZoneHVAC:PackagedTerminalAirConditioner | 214 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34788E-002 |
| 253 | Coil:Heating:Water | 214 PTAC HEATING COIL | Design Size Rated Capacity [W] | 2513.29979 |
| 254 | Coil:Heating:Water | 214 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.19874E-005 |
| 255 | Coil:Heating:Water | 214 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 61.29996 |
| 256 | Coil:Cooling:DX:SingleSpeed | 214 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.14357 |
| 257 | Coil:Cooling:DX:SingleSpeed | 214 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 2608.88829 |
| 258 | Coil:Cooling:DX:SingleSpeed | 214 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80092 |
| 259 | Fan:OnOff | 214 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.14357 |
| 260 | ZoneHVAC:PackagedTerminalAirConditioner | 215_218 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14939 |
| 261 | ZoneHVAC:PackagedTerminalAirConditioner | 215_218 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14939 |
| 262 | ZoneHVAC:PackagedTerminalAirConditioner | 215_218 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14939 |
| 263 | ZoneHVAC:PackagedTerminalAirConditioner | 215_218 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 5.39153E-002 |
| 264 | ZoneHVAC:PackagedTerminalAirConditioner | 215_218 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 5.39153E-002 |
| 265 | ZoneHVAC:PackagedTerminalAirConditioner | 215_218 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.39153E-002 |
| 266 | Coil:Heating:Water | 215_218 PTAC HEATING COIL | Design Size Rated Capacity [W] | 17702.71458 |
| 267 | Coil:Heating:Water | 215_218 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54871E-004 |
| 268 | Coil:Heating:Water | 215_218 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 439.30712 |
| 269 | Coil:Cooling:DX:SingleSpeed | 215_218 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 1.14939 |
| 270 | Coil:Cooling:DX:SingleSpeed | 215_218 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 19026.41307 |
| 271 | Coil:Cooling:DX:SingleSpeed | 215_218 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 272 | Fan:OnOff | 215_218 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 1.14939 |
| 273 | ZoneHVAC:PackagedTerminalAirConditioner | 219 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.61236 |
| 274 | ZoneHVAC:PackagedTerminalAirConditioner | 219 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.61236 |
| 275 | ZoneHVAC:PackagedTerminalAirConditioner | 219 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.61236 |
| 276 | ZoneHVAC:PackagedTerminalAirConditioner | 219 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34788E-002 |
| 277 | ZoneHVAC:PackagedTerminalAirConditioner | 219 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34788E-002 |
| 278 | ZoneHVAC:PackagedTerminalAirConditioner | 219 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34788E-002 |
| 279 | Coil:Heating:Water | 219 PTAC HEATING COIL | Design Size Rated Capacity [W] | 8748.72170 |
| 280 | Coil:Heating:Water | 219 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.65376E-005 |
| 281 | Coil:Heating:Water | 219 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 219.18276 |
| 282 | Coil:Cooling:DX:SingleSpeed | 219 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.61236 |
| 283 | Coil:Cooling:DX:SingleSpeed | 219 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 10136.72015 |
| 284 | Coil:Cooling:DX:SingleSpeed | 219 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 285 | Fan:OnOff | 219 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.61236 |
| 286 | ZoneHVAC:PackagedTerminalAirConditioner | 220_223 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.49020 |
| 287 | ZoneHVAC:PackagedTerminalAirConditioner | 220_223 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.49020 |
| 288 | ZoneHVAC:PackagedTerminalAirConditioner | 220_223 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.49020 |
| 289 | ZoneHVAC:PackagedTerminalAirConditioner | 220_223 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 5.39153E-002 |
| 290 | ZoneHVAC:PackagedTerminalAirConditioner | 220_223 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 5.39153E-002 |
| 291 | ZoneHVAC:PackagedTerminalAirConditioner | 220_223 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.39153E-002 |
| 292 | Coil:Heating:Water | 220_223 PTAC HEATING COIL | Design Size Rated Capacity [W] | 8934.77690 |
| 293 | Coil:Heating:Water | 220_223 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.81653E-005 |
| 294 | Coil:Heating:Water | 220_223 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 216.68626 |
| 295 | Coil:Cooling:DX:SingleSpeed | 220_223 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49020 |
| 296 | Coil:Cooling:DX:SingleSpeed | 220_223 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 9117.95456 |
| 297 | Coil:Cooling:DX:SingleSpeed | 220_223 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80020 |
| 298 | Fan:OnOff | 220_223 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49020 |
| 299 | ZoneHVAC:PackagedTerminalAirConditioner | 224 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.14128 |
| 300 | ZoneHVAC:PackagedTerminalAirConditioner | 224 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.14128 |
| 301 | ZoneHVAC:PackagedTerminalAirConditioner | 224 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.14128 |
| 302 | ZoneHVAC:PackagedTerminalAirConditioner | 224 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34788E-002 |
| 303 | ZoneHVAC:PackagedTerminalAirConditioner | 224 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34788E-002 |
| 304 | ZoneHVAC:PackagedTerminalAirConditioner | 224 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34788E-002 |
| 305 | Coil:Heating:Water | 224 PTAC HEATING COIL | Design Size Rated Capacity [W] | 2482.80815 |
| 306 | Coil:Heating:Water | 224 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.17207E-005 |
| 307 | Coil:Heating:Water | 224 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 60.52376 |
| 308 | Coil:Cooling:DX:SingleSpeed | 224 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.14128 |
| 309 | Coil:Cooling:DX:SingleSpeed | 224 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 2573.36298 |
| 310 | Coil:Cooling:DX:SingleSpeed | 224 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80013 |
| 311 | Fan:OnOff | 224 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.14128 |
| 312 | ZoneHVAC:UnitHeater | FRONTSTAIRSFLR2 UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.44104E-002 |
| 313 | Fan:ConstantVolume | FRONTSTAIRSFLR2 UNITHEATER FAN | Design Size Maximum Flow Rate [m3/s] | 2.44104E-002 |
| 314 | Coil:Heating:Fuel | FRONTSTAIRSFLR2 UNITHEATER HEATING COIL | Design Size Nominal Capacity [W] | 324.76764 |
| 315 | ZoneHVAC:UnitHeater | REARSTAIRSFLR3 UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 6.11790E-003 |
| 316 | Fan:ConstantVolume | REARSTAIRSFLR3 UNITHEATER FAN | Design Size Maximum Flow Rate [m3/s] | 6.11790E-003 |
| 317 | Coil:Heating:Fuel | REARSTAIRSFLR3 UNITHEATER HEATING COIL | Design Size Nominal Capacity [W] | 81.38220 |
| 318 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR3 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.21682 |
| 319 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR3 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.21682 |
| 320 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR3 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.21682 |
| 321 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR3 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 3.82281E-002 |
| 322 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR3 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 3.82281E-002 |
| 323 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR3 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 3.82281E-002 |
| 324 | Coil:Heating:Water | CORRIDORFLR3 PTAC HEATING COIL | Design Size Rated Capacity [W] | 4595.93678 |
| 325 | Coil:Heating:Water | CORRIDORFLR3 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.02073E-005 |
| 326 | Coil:Heating:Water | CORRIDORFLR3 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 108.98125 |
| 327 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR3 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.21682 |
| 328 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR3 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4633.66272 |
| 329 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR3 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.75078 |
| 330 | Fan:OnOff | CORRIDORFLR3 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.21682 |
| 331 | ZoneHVAC:PackagedTerminalAirConditioner | 301 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 9.07492E-002 |
| 332 | ZoneHVAC:PackagedTerminalAirConditioner | 301 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 9.07492E-002 |
| 333 | ZoneHVAC:PackagedTerminalAirConditioner | 301 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 9.07492E-002 |
| 334 | ZoneHVAC:PackagedTerminalAirConditioner | 301 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34798E-002 |
| 335 | ZoneHVAC:PackagedTerminalAirConditioner | 301 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34798E-002 |
| 336 | ZoneHVAC:PackagedTerminalAirConditioner | 301 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34798E-002 |
| 337 | Coil:Heating:Water | 301 PTAC HEATING COIL | Design Size Rated Capacity [W] | 1810.79259 |
| 338 | Coil:Heating:Water | 301 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.58416E-005 |
| 339 | Coil:Heating:Water | 301 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 43.33778 |
| 340 | Coil:Cooling:DX:SingleSpeed | 301 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 9.07492E-002 |
| 341 | Coil:Cooling:DX:SingleSpeed | 301 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 1997.16458 |
| 342 | Coil:Cooling:DX:SingleSpeed | 301 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.74054 |
| 343 | Fan:OnOff | 301 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 9.07492E-002 |
| 344 | ZoneHVAC:PackagedTerminalAirConditioner | 302_305 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.21679 |
| 345 | ZoneHVAC:PackagedTerminalAirConditioner | 302_305 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.21679 |
| 346 | ZoneHVAC:PackagedTerminalAirConditioner | 302_305 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.21679 |
| 347 | ZoneHVAC:PackagedTerminalAirConditioner | 302_305 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 5.39191E-002 |
| 348 | ZoneHVAC:PackagedTerminalAirConditioner | 302_305 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 5.39191E-002 |
| 349 | ZoneHVAC:PackagedTerminalAirConditioner | 302_305 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.39191E-002 |
| 350 | Coil:Heating:Water | 302_305 PTAC HEATING COIL | Design Size Rated Capacity [W] | 5298.19796 |
| 351 | Coil:Heating:Water | 302_305 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.63509E-005 |
| 352 | Coil:Heating:Water | 302_305 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 122.78278 |
| 353 | Coil:Cooling:DX:SingleSpeed | 302_305 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.21679 |
| 354 | Coil:Cooling:DX:SingleSpeed | 302_305 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 4732.69522 |
| 355 | Coil:Cooling:DX:SingleSpeed | 302_305 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.74378 |
| 356 | Fan:OnOff | 302_305 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.21679 |
| 357 | ZoneHVAC:PackagedTerminalAirConditioner | 306_308 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.16640 |
| 358 | ZoneHVAC:PackagedTerminalAirConditioner | 306_308 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.16640 |
| 359 | ZoneHVAC:PackagedTerminalAirConditioner | 306_308 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.16640 |
| 360 | ZoneHVAC:PackagedTerminalAirConditioner | 306_308 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 4.27331E-002 |
| 361 | ZoneHVAC:PackagedTerminalAirConditioner | 306_308 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 4.27331E-002 |
| 362 | ZoneHVAC:PackagedTerminalAirConditioner | 306_308 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.27331E-002 |
| 363 | Coil:Heating:Water | 306_308 PTAC HEATING COIL | Design Size Rated Capacity [W] | 4127.00993 |
| 364 | Coil:Heating:Water | 306_308 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.61049E-005 |
| 365 | Coil:Heating:Water | 306_308 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 95.40694 |
| 366 | Coil:Cooling:DX:SingleSpeed | 306_308 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.16640 |
| 367 | Coil:Cooling:DX:SingleSpeed | 306_308 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 3594.10439 |
| 368 | Coil:Cooling:DX:SingleSpeed | 306_308 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.74677 |
| 369 | Fan:OnOff | 306_308 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.16640 |
| 370 | ZoneHVAC:PackagedTerminalAirConditioner | 309_312 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.38387 |
| 371 | ZoneHVAC:PackagedTerminalAirConditioner | 309_312 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.38387 |
| 372 | ZoneHVAC:PackagedTerminalAirConditioner | 309_312 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.38387 |
| 373 | ZoneHVAC:PackagedTerminalAirConditioner | 309_312 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 5.39191E-002 |
| 374 | ZoneHVAC:PackagedTerminalAirConditioner | 309_312 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 5.39191E-002 |
| 375 | ZoneHVAC:PackagedTerminalAirConditioner | 309_312 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.39191E-002 |
| 376 | Coil:Heating:Water | 309_312 PTAC HEATING COIL | Design Size Rated Capacity [W] | 7520.63885 |
| 377 | Coil:Heating:Water | 309_312 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.57938E-005 |
| 378 | Coil:Heating:Water | 309_312 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 180.47528 |
| 379 | Coil:Cooling:DX:SingleSpeed | 309_312 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.38387 |
| 380 | Coil:Cooling:DX:SingleSpeed | 309_312 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7051.14770 |
| 381 | Coil:Cooling:DX:SingleSpeed | 309_312 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80033 |
| 382 | Fan:OnOff | 309_312 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.38387 |
| 383 | ZoneHVAC:PackagedTerminalAirConditioner | 313 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.10199 |
| 384 | ZoneHVAC:PackagedTerminalAirConditioner | 313 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.10199 |
| 385 | ZoneHVAC:PackagedTerminalAirConditioner | 313 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.10199 |
| 386 | ZoneHVAC:PackagedTerminalAirConditioner | 313 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34798E-002 |
| 387 | ZoneHVAC:PackagedTerminalAirConditioner | 313 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34798E-002 |
| 388 | ZoneHVAC:PackagedTerminalAirConditioner | 313 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34798E-002 |
| 389 | Coil:Heating:Water | 313 PTAC HEATING COIL | Design Size Rated Capacity [W] | 1960.25149 |
| 390 | Coil:Heating:Water | 313 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.71491E-005 |
| 391 | Coil:Heating:Water | 313 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 47.17282 |
| 392 | Coil:Cooling:DX:SingleSpeed | 313 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.10199 |
| 393 | Coil:Cooling:DX:SingleSpeed | 313 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 1966.47573 |
| 394 | Coil:Cooling:DX:SingleSpeed | 313 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79065 |
| 395 | Fan:OnOff | 313 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.10199 |
| 396 | ZoneHVAC:PackagedTerminalAirConditioner | 314 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.13100 |
| 397 | ZoneHVAC:PackagedTerminalAirConditioner | 314 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.13100 |
| 398 | ZoneHVAC:PackagedTerminalAirConditioner | 314 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.13100 |
| 399 | ZoneHVAC:PackagedTerminalAirConditioner | 314 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34788E-002 |
| 400 | ZoneHVAC:PackagedTerminalAirConditioner | 314 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34788E-002 |
| 401 | ZoneHVAC:PackagedTerminalAirConditioner | 314 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34788E-002 |
| 402 | Coil:Heating:Water | 314 PTAC HEATING COIL | Design Size Rated Capacity [W] | 2346.08888 |
| 403 | Coil:Heating:Water | 314 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.05246E-005 |
| 404 | Coil:Heating:Water | 314 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 57.03830 |
| 405 | Coil:Cooling:DX:SingleSpeed | 314 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.13100 |
| 406 | Coil:Cooling:DX:SingleSpeed | 314 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 2415.53267 |
| 407 | Coil:Cooling:DX:SingleSpeed | 314 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80006 |
| 408 | Fan:OnOff | 314 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.13100 |
| 409 | ZoneHVAC:PackagedTerminalAirConditioner | 315_318 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.54319 |
| 410 | ZoneHVAC:PackagedTerminalAirConditioner | 315_318 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.54319 |
| 411 | ZoneHVAC:PackagedTerminalAirConditioner | 315_318 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.54319 |
| 412 | ZoneHVAC:PackagedTerminalAirConditioner | 315_318 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 5.39153E-002 |
| 413 | ZoneHVAC:PackagedTerminalAirConditioner | 315_318 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 5.39153E-002 |
| 414 | ZoneHVAC:PackagedTerminalAirConditioner | 315_318 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.39153E-002 |
| 415 | Coil:Heating:Water | 315_318 PTAC HEATING COIL | Design Size Rated Capacity [W] | 9639.65661 |
| 416 | Coil:Heating:Water | 315_318 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.43319E-005 |
| 417 | Coil:Heating:Water | 315_318 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 234.67072 |
| 418 | Coil:Cooling:DX:SingleSpeed | 315_318 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.54319 |
| 419 | Coil:Cooling:DX:SingleSpeed | 315_318 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 9959.93687 |
| 420 | Coil:Cooling:DX:SingleSpeed | 315_318 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80092 |
| 421 | Fan:OnOff | 315_318 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.54319 |
| 422 | ZoneHVAC:PackagedTerminalAirConditioner | 319 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.11985 |
| 423 | ZoneHVAC:PackagedTerminalAirConditioner | 319 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.11985 |
| 424 | ZoneHVAC:PackagedTerminalAirConditioner | 319 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.11985 |
| 425 | ZoneHVAC:PackagedTerminalAirConditioner | 319 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34788E-002 |
| 426 | ZoneHVAC:PackagedTerminalAirConditioner | 319 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34788E-002 |
| 427 | ZoneHVAC:PackagedTerminalAirConditioner | 319 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34788E-002 |
| 428 | Coil:Heating:Water | 319 PTAC HEATING COIL | Design Size Rated Capacity [W] | 2197.75586 |
| 429 | Coil:Heating:Water | 319 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.92269E-005 |
| 430 | Coil:Heating:Water | 319 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 53.25309 |
| 431 | Coil:Cooling:DX:SingleSpeed | 319 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.11985 |
| 432 | Coil:Cooling:DX:SingleSpeed | 319 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 2179.78073 |
| 433 | Coil:Cooling:DX:SingleSpeed | 319 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80062 |
| 434 | Fan:OnOff | 319 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.11985 |
| 435 | ZoneHVAC:PackagedTerminalAirConditioner | 320_323 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.46251 |
| 436 | ZoneHVAC:PackagedTerminalAirConditioner | 320_323 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.46251 |
| 437 | ZoneHVAC:PackagedTerminalAirConditioner | 320_323 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.46251 |
| 438 | ZoneHVAC:PackagedTerminalAirConditioner | 320_323 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 5.39153E-002 |
| 439 | ZoneHVAC:PackagedTerminalAirConditioner | 320_323 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 5.39153E-002 |
| 440 | ZoneHVAC:PackagedTerminalAirConditioner | 320_323 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.39153E-002 |
| 441 | Coil:Heating:Water | 320_323 PTAC HEATING COIL | Design Size Rated Capacity [W] | 8566.45057 |
| 442 | Coil:Heating:Water | 320_323 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.49430E-005 |
| 443 | Coil:Heating:Water | 320_323 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 207.27427 |
| 444 | Coil:Cooling:DX:SingleSpeed | 320_323 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.46251 |
| 445 | Coil:Cooling:DX:SingleSpeed | 320_323 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 8705.61096 |
| 446 | Coil:Cooling:DX:SingleSpeed | 320_323 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80034 |
| 447 | Fan:OnOff | 320_323 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.46251 |
| 448 | ZoneHVAC:PackagedTerminalAirConditioner | 324 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 8.30729E-002 |
| 449 | ZoneHVAC:PackagedTerminalAirConditioner | 324 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 8.30729E-002 |
| 450 | ZoneHVAC:PackagedTerminalAirConditioner | 324 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 8.30729E-002 |
| 451 | ZoneHVAC:PackagedTerminalAirConditioner | 324 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34788E-002 |
| 452 | ZoneHVAC:PackagedTerminalAirConditioner | 324 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34788E-002 |
| 453 | ZoneHVAC:PackagedTerminalAirConditioner | 324 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34788E-002 |
| 454 | Coil:Heating:Water | 324 PTAC HEATING COIL | Design Size Rated Capacity [W] | 1708.58437 |
| 455 | Coil:Heating:Water | 324 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.49474E-005 |
| 456 | Coil:Heating:Water | 324 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 40.70039 |
| 457 | Coil:Cooling:DX:SingleSpeed | 324 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 8.30729E-002 |
| 458 | Coil:Cooling:DX:SingleSpeed | 324 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 1612.96496 |
| 459 | Coil:Cooling:DX:SingleSpeed | 324 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.78845 |
| 460 | Fan:OnOff | 324 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 8.30729E-002 |
| 461 | ZoneHVAC:UnitHeater | FRONTSTAIRSFLR3 UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 3.03845E-002 |
| 462 | Fan:ConstantVolume | FRONTSTAIRSFLR3 UNITHEATER FAN | Design Size Maximum Flow Rate [m3/s] | 3.03845E-002 |
| 463 | Coil:Heating:Fuel | FRONTSTAIRSFLR3 UNITHEATER HEATING COIL | Design Size Nominal Capacity [W] | 404.27030 |
| 464 | ZoneHVAC:UnitHeater | REARSTAIRSFLR4 UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 2.18381E-002 |
| 465 | Fan:ConstantVolume | REARSTAIRSFLR4 UNITHEATER FAN | Design Size Maximum Flow Rate [m3/s] | 2.18381E-002 |
| 466 | Coil:Heating:Fuel | REARSTAIRSFLR4 UNITHEATER HEATING COIL | Design Size Nominal Capacity [W] | 290.54334 |
| 467 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR4 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.36144 |
| 468 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR4 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.36144 |
| 469 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR4 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.36144 |
| 470 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR4 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 3.82281E-002 |
| 471 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR4 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 3.82281E-002 |
| 472 | ZoneHVAC:PackagedTerminalAirConditioner | CORRIDORFLR4 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 3.82281E-002 |
| 473 | Coil:Heating:Water | CORRIDORFLR4 PTAC HEATING COIL | Design Size Rated Capacity [W] | 6519.64865 |
| 474 | Coil:Heating:Water | CORRIDORFLR4 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.70367E-005 |
| 475 | Coil:Heating:Water | CORRIDORFLR4 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 158.35096 |
| 476 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR4 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.36144 |
| 477 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR4 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 7018.70338 |
| 478 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR4 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.78841 |
| 479 | Fan:OnOff | CORRIDORFLR4 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.36144 |
| 480 | ZoneHVAC:PackagedTerminalAirConditioner | 401 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.13473 |
| 481 | ZoneHVAC:PackagedTerminalAirConditioner | 401 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.13473 |
| 482 | ZoneHVAC:PackagedTerminalAirConditioner | 401 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.13473 |
| 483 | ZoneHVAC:PackagedTerminalAirConditioner | 401 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34798E-002 |
| 484 | ZoneHVAC:PackagedTerminalAirConditioner | 401 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34798E-002 |
| 485 | ZoneHVAC:PackagedTerminalAirConditioner | 401 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34798E-002 |
| 486 | Coil:Heating:Water | 401 PTAC HEATING COIL | Design Size Rated Capacity [W] | 2395.88661 |
| 487 | Coil:Heating:Water | 401 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.09603E-005 |
| 488 | Coil:Heating:Water | 401 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 58.31140 |
| 489 | Coil:Cooling:DX:SingleSpeed | 401 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.13473 |
| 490 | Coil:Cooling:DX:SingleSpeed | 401 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 2498.50259 |
| 491 | Coil:Cooling:DX:SingleSpeed | 401 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80019 |
| 492 | Fan:OnOff | 401 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.13473 |
| 493 | ZoneHVAC:PackagedTerminalAirConditioner | 402_405 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.32970 |
| 494 | ZoneHVAC:PackagedTerminalAirConditioner | 402_405 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.32970 |
| 495 | ZoneHVAC:PackagedTerminalAirConditioner | 402_405 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.32970 |
| 496 | ZoneHVAC:PackagedTerminalAirConditioner | 402_405 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 5.39191E-002 |
| 497 | ZoneHVAC:PackagedTerminalAirConditioner | 402_405 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 5.39191E-002 |
| 498 | ZoneHVAC:PackagedTerminalAirConditioner | 402_405 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.39191E-002 |
| 499 | Coil:Heating:Water | 402_405 PTAC HEATING COIL | Design Size Rated Capacity [W] | 6800.00488 |
| 500 | Coil:Heating:Water | 402_405 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.94894E-005 |
| 501 | Coil:Heating:Water | 402_405 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 161.91483 |
| 502 | Coil:Cooling:DX:SingleSpeed | 402_405 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.32970 |
| 503 | Coil:Cooling:DX:SingleSpeed | 402_405 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 6912.98701 |
| 504 | Coil:Cooling:DX:SingleSpeed | 402_405 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.75826 |
| 505 | Fan:OnOff | 402_405 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.32970 |
| 506 | ZoneHVAC:PackagedTerminalAirConditioner | 406_408 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.25976 |
| 507 | ZoneHVAC:PackagedTerminalAirConditioner | 406_408 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.25976 |
| 508 | ZoneHVAC:PackagedTerminalAirConditioner | 406_408 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.25976 |
| 509 | ZoneHVAC:PackagedTerminalAirConditioner | 406_408 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 4.27331E-002 |
| 510 | ZoneHVAC:PackagedTerminalAirConditioner | 406_408 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 4.27331E-002 |
| 511 | ZoneHVAC:PackagedTerminalAirConditioner | 406_408 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.27331E-002 |
| 512 | Coil:Heating:Water | 406_408 PTAC HEATING COIL | Design Size Rated Capacity [W] | 5368.85743 |
| 513 | Coil:Heating:Water | 406_408 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.69691E-005 |
| 514 | Coil:Heating:Water | 406_408 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 127.79690 |
| 515 | Coil:Cooling:DX:SingleSpeed | 406_408 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.25976 |
| 516 | Coil:Cooling:DX:SingleSpeed | 406_408 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 5414.23241 |
| 517 | Coil:Cooling:DX:SingleSpeed | 406_408 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.75999 |
| 518 | Fan:OnOff | 406_408 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.25976 |
| 519 | ZoneHVAC:PackagedTerminalAirConditioner | 409_412 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.49647 |
| 520 | ZoneHVAC:PackagedTerminalAirConditioner | 409_412 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.49647 |
| 521 | ZoneHVAC:PackagedTerminalAirConditioner | 409_412 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.49647 |
| 522 | ZoneHVAC:PackagedTerminalAirConditioner | 409_412 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 5.39191E-002 |
| 523 | ZoneHVAC:PackagedTerminalAirConditioner | 409_412 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 5.39191E-002 |
| 524 | ZoneHVAC:PackagedTerminalAirConditioner | 409_412 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.39191E-002 |
| 525 | Coil:Heating:Water | 409_412 PTAC HEATING COIL | Design Size Rated Capacity [W] | 9018.34401 |
| 526 | Coil:Heating:Water | 409_412 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.88964E-005 |
| 527 | Coil:Heating:Water | 409_412 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 218.81448 |
| 528 | Coil:Cooling:DX:SingleSpeed | 409_412 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49647 |
| 529 | Coil:Cooling:DX:SingleSpeed | 409_412 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 9239.09729 |
| 530 | Coil:Cooling:DX:SingleSpeed | 409_412 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80004 |
| 531 | Fan:OnOff | 409_412 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49647 |
| 532 | ZoneHVAC:PackagedTerminalAirConditioner | 413 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.13744 |
| 533 | ZoneHVAC:PackagedTerminalAirConditioner | 413 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.13744 |
| 534 | ZoneHVAC:PackagedTerminalAirConditioner | 413 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.13744 |
| 535 | ZoneHVAC:PackagedTerminalAirConditioner | 413 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34798E-002 |
| 536 | ZoneHVAC:PackagedTerminalAirConditioner | 413 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34798E-002 |
| 537 | ZoneHVAC:PackagedTerminalAirConditioner | 413 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34798E-002 |
| 538 | Coil:Heating:Water | 413 PTAC HEATING COIL | Design Size Rated Capacity [W] | 2431.71988 |
| 539 | Coil:Heating:Water | 413 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.12737E-005 |
| 540 | Coil:Heating:Water | 413 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 59.22085 |
| 541 | Coil:Cooling:DX:SingleSpeed | 413 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.13744 |
| 542 | Coil:Cooling:DX:SingleSpeed | 413 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 2649.59309 |
| 543 | Coil:Cooling:DX:SingleSpeed | 413 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.79068 |
| 544 | Fan:OnOff | 413 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.13744 |
| 545 | ZoneHVAC:PackagedTerminalAirConditioner | 414 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.13050 |
| 546 | ZoneHVAC:PackagedTerminalAirConditioner | 414 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.13050 |
| 547 | ZoneHVAC:PackagedTerminalAirConditioner | 414 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.13050 |
| 548 | ZoneHVAC:PackagedTerminalAirConditioner | 414 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34788E-002 |
| 549 | ZoneHVAC:PackagedTerminalAirConditioner | 414 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34788E-002 |
| 550 | ZoneHVAC:PackagedTerminalAirConditioner | 414 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34788E-002 |
| 551 | Coil:Heating:Water | 414 PTAC HEATING COIL | Design Size Rated Capacity [W] | 2339.48166 |
| 552 | Coil:Heating:Water | 414 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.04668E-005 |
| 553 | Coil:Heating:Water | 414 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 56.86931 |
| 554 | Coil:Cooling:DX:SingleSpeed | 414 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.13050 |
| 555 | Coil:Cooling:DX:SingleSpeed | 414 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 2392.16714 |
| 556 | Coil:Cooling:DX:SingleSpeed | 414 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80002 |
| 557 | Fan:OnOff | 414 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.13050 |
| 558 | ZoneHVAC:PackagedTerminalAirConditioner | 415_418 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.61640 |
| 559 | ZoneHVAC:PackagedTerminalAirConditioner | 415_418 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.61640 |
| 560 | ZoneHVAC:PackagedTerminalAirConditioner | 415_418 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.61640 |
| 561 | ZoneHVAC:PackagedTerminalAirConditioner | 415_418 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 5.39153E-002 |
| 562 | ZoneHVAC:PackagedTerminalAirConditioner | 415_418 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 5.39153E-002 |
| 563 | ZoneHVAC:PackagedTerminalAirConditioner | 415_418 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.39153E-002 |
| 564 | Coil:Heating:Water | 415_418 PTAC HEATING COIL | Design Size Rated Capacity [W] | 10613.28273 |
| 565 | Coil:Heating:Water | 415_418 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.28496E-005 |
| 566 | Coil:Heating:Water | 415_418 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 259.46143 |
| 567 | Coil:Cooling:DX:SingleSpeed | 415_418 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.61640 |
| 568 | Coil:Cooling:DX:SingleSpeed | 415_418 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 11070.48012 |
| 569 | Coil:Cooling:DX:SingleSpeed | 415_418 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80086 |
| 570 | Fan:OnOff | 415_418 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.61640 |
| 571 | ZoneHVAC:PackagedTerminalAirConditioner | 419 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.16601 |
| 572 | ZoneHVAC:PackagedTerminalAirConditioner | 419 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.16601 |
| 573 | ZoneHVAC:PackagedTerminalAirConditioner | 419 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.16601 |
| 574 | ZoneHVAC:PackagedTerminalAirConditioner | 419 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34788E-002 |
| 575 | ZoneHVAC:PackagedTerminalAirConditioner | 419 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34788E-002 |
| 576 | ZoneHVAC:PackagedTerminalAirConditioner | 419 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34788E-002 |
| 577 | Coil:Heating:Water | 419 PTAC HEATING COIL | Design Size Rated Capacity [W] | 2811.68471 |
| 578 | Coil:Heating:Water | 419 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.45978E-005 |
| 579 | Coil:Heating:Water | 419 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 68.89262 |
| 580 | Coil:Cooling:DX:SingleSpeed | 419 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.16601 |
| 581 | Coil:Cooling:DX:SingleSpeed | 419 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 2955.19532 |
| 582 | Coil:Cooling:DX:SingleSpeed | 419 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80088 |
| 583 | Fan:OnOff | 419 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.16601 |
| 584 | ZoneHVAC:PackagedTerminalAirConditioner | 420_423 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.60765 |
| 585 | ZoneHVAC:PackagedTerminalAirConditioner | 420_423 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.60765 |
| 586 | ZoneHVAC:PackagedTerminalAirConditioner | 420_423 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.60765 |
| 587 | ZoneHVAC:PackagedTerminalAirConditioner | 420_423 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 5.39153E-002 |
| 588 | ZoneHVAC:PackagedTerminalAirConditioner | 420_423 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 5.39153E-002 |
| 589 | ZoneHVAC:PackagedTerminalAirConditioner | 420_423 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.39153E-002 |
| 590 | Coil:Heating:Water | 420_423 PTAC HEATING COIL | Design Size Rated Capacity [W] | 10496.91755 |
| 591 | Coil:Heating:Water | 420_423 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.18316E-005 |
| 592 | Coil:Heating:Water | 420_423 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 256.50034 |
| 593 | Coil:Cooling:DX:SingleSpeed | 420_423 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.60765 |
| 594 | Coil:Cooling:DX:SingleSpeed | 420_423 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 10935.32223 |
| 595 | Coil:Cooling:DX:SingleSpeed | 420_423 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80018 |
| 596 | Fan:OnOff | 420_423 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.60765 |
| 597 | ZoneHVAC:PackagedTerminalAirConditioner | 424 PTAC | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.16955 |
| 598 | ZoneHVAC:PackagedTerminalAirConditioner | 424 PTAC | Design Size Heating Supply Air Flow Rate [m3/s] | 0.16955 |
| 599 | ZoneHVAC:PackagedTerminalAirConditioner | 424 PTAC | Design Size No Load Supply Air Flow Rate [m3/s] | 0.16955 |
| 600 | ZoneHVAC:PackagedTerminalAirConditioner | 424 PTAC | Design Size Outdoor Air Flow Rate During Cooling Operation [m3/s] | 1.34788E-002 |
| 601 | ZoneHVAC:PackagedTerminalAirConditioner | 424 PTAC | Design Size Outdoor Air Flow Rate During Heating Operation [m3/s] | 1.34788E-002 |
| 602 | ZoneHVAC:PackagedTerminalAirConditioner | 424 PTAC | Design Size Outdoor Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 1.34788E-002 |
| 603 | Coil:Heating:Water | 424 PTAC HEATING COIL | Design Size Rated Capacity [W] | 2858.82733 |
| 604 | Coil:Heating:Water | 424 PTAC HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.50103E-005 |
| 605 | Coil:Heating:Water | 424 PTAC HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 70.09043 |
| 606 | Coil:Cooling:DX:SingleSpeed | 424 PTAC PTAC COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.16955 |
| 607 | Coil:Cooling:DX:SingleSpeed | 424 PTAC PTAC COOLING COIL | Design Size Gross Rated Total Cooling Capacity [W] | 3013.75441 |
| 608 | Coil:Cooling:DX:SingleSpeed | 424 PTAC PTAC COOLING COIL | Design Size Gross Rated Sensible Heat Ratio | 0.80039 |
| 609 | Fan:OnOff | 424 PTAC_PTAC_SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.16955 |
| 610 | ZoneHVAC:UnitHeater | FRONTSTAIRSFLR4 UNIT HEATER | Design Size Maximum Supply Air Flow Rate [m3/s] | 4.90115E-002 |
| 611 | Fan:ConstantVolume | FRONTSTAIRSFLR4 UNITHEATER FAN | Design Size Maximum Flow Rate [m3/s] | 4.90115E-002 |
| 612 | Coil:Heating:Fuel | FRONTSTAIRSFLR4 UNITHEATER HEATING COIL | Design Size Nominal Capacity [W] | 652.14472 |
| 613 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.54885E-003 |
| 614 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 0.30586 |
| 615 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.54885E-003 |
| 616 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 767.60057 |
| 617 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
| 618 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 291348.78605 |
| 619 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 291348.79000 |
| 620 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.54885E-003 |
| 621 | PlantLoop | SWHSYSSHOWER | Maximum Loop Flow Rate [m3/s] | 1.79949E-004 |
| 622 | PlantLoop | SWHSYSSHOWER | Plant Loop Volume [m3] | 2.15939E-002 |
| 623 | Pump:ConstantSpeed | SWHSYSSHOWER PUMP | Design Flow Rate [m3/s] | 1.79949E-004 |
| 624 | Pump:ConstantSpeed | SWHSYSSHOWER PUMP | Design Power Consumption [W] | 8.11290 |
| 625 | WaterHeater:Mixed | SWH SHOWER WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.79949E-004 |
| 626 | PlantLoop | SWHSYSLAUNDRY | Maximum Loop Flow Rate [m3/s] | 1.29330E-004 |
| 627 | PlantLoop | SWHSYSLAUNDRY | Plant Loop Volume [m3] | 1.55196E-002 |
| 628 | Pump:ConstantSpeed | SWHSYSLAUNDRY PUMP | Design Flow Rate [m3/s] | 1.29330E-004 |
| 629 | Pump:ConstantSpeed | SWHSYSLAUNDRY PUMP | Design Power Consumption [W] | 5.52692E-007 |
| 630 | WaterHeater:Mixed | SWH LAUNDRY WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.29330E-004 |
| Component Type | Name | Nominal Total Capacity {W} | |
| 1 | Coil:Heating:Water | CORRIDORFLR1 PTAC HEATING COIL | 45595.97 |
| 2 | Coil:Heating:Water | SAC_FRONTLOUNGE HEATING COIL | 19041.48 |
| 3 | Coil:Heating:Water | SAC_RESTROOM HEATING COIL | 953.70 |
| 4 | Coil:Heating:Water | SAC_MEETINGROOM HEATING COIL | 9554.88 |
| 5 | Coil:Heating:Water | 101 PTAC HEATING COIL | 1439.06 |
| 6 | Coil:Heating:Water | 102 PTAC HEATING COIL | 1367.09 |
| 7 | Coil:Heating:Water | 103 PTAC HEATING COIL | 2061.63 |
| 8 | Coil:Heating:Water | 104 PTAC HEATING COIL | 2395.01 |
| 9 | Coil:Heating:Water | 105 PTAC HEATING COIL | 3037.96 |
| 10 | Coil:Heating:Water | SAC_EMPLOYEELOUNGE HEATING COIL | 11575.23 |
| 11 | Coil:Heating:Water | SAC_EXERCISECENTER HEATING COIL | 3373.97 |
| 12 | Coil:Heating:Water | SAC_FRONTOFFICE HEATING COIL | 7653.03 |
| 13 | Coil:Heating:Water | CORRIDORFLR2 PTAC HEATING COIL | 5671.79 |
| 14 | Coil:Heating:Water | 201 PTAC HEATING COIL | 1709.25 |
| 15 | Coil:Heating:Water | 202_205 PTAC HEATING COIL | 7825.59 |
| 16 | Coil:Heating:Water | 206_208 PTAC HEATING COIL | 6216.70 |
| 17 | Coil:Heating:Water | 209_212 PTAC HEATING COIL | 7643.96 |
| 18 | Coil:Heating:Water | 213 PTAC HEATING COIL | 2084.00 |
| 19 | Coil:Heating:Water | 214 PTAC HEATING COIL | 2560.21 |
| 20 | Coil:Heating:Water | 215_218 PTAC HEATING COIL | 18540.57 |
| 21 | Coil:Heating:Water | 219 PTAC HEATING COIL | 9301.49 |
| 22 | Coil:Heating:Water | 220_223 PTAC HEATING COIL | 9017.23 |
| 23 | Coil:Heating:Water | 224 PTAC HEATING COIL | 2526.92 |
| 24 | Coil:Heating:Water | CORRIDORFLR3 PTAC HEATING COIL | 4467.78 |
| 25 | Coil:Heating:Water | 301 PTAC HEATING COIL | 1787.85 |
| 26 | Coil:Heating:Water | 302_305 PTAC HEATING COIL | 4951.62 |
| 27 | Coil:Heating:Water | 306_308 PTAC HEATING COIL | 3840.50 |
| 28 | Coil:Heating:Water | 309_312 PTAC HEATING COIL | 7459.05 |
| 29 | Coil:Heating:Water | 313 PTAC HEATING COIL | 1953.33 |
| 30 | Coil:Heating:Water | 314 PTAC HEATING COIL | 2377.42 |
| 31 | Coil:Heating:Water | 315_318 PTAC HEATING COIL | 9789.16 |
| 32 | Coil:Heating:Water | 319 PTAC HEATING COIL | 2214.86 |
| 33 | Coil:Heating:Water | 320_323 PTAC HEATING COIL | 8612.82 |
| 34 | Coil:Heating:Water | 324 PTAC HEATING COIL | 1673.91 |
| 35 | Coil:Heating:Water | CORRIDORFLR4 PTAC HEATING COIL | 6595.88 |
| 36 | Coil:Heating:Water | 401 PTAC HEATING COIL | 2431.96 |
| 37 | Coil:Heating:Water | 402_405 PTAC HEATING COIL | 6657.24 |
| 38 | Coil:Heating:Water | 406_408 PTAC HEATING COIL | 5253.31 |
| 39 | Coil:Heating:Water | 409_412 PTAC HEATING COIL | 9108.70 |
| 40 | Coil:Heating:Water | 413 PTAC HEATING COIL | 2471.06 |
| 41 | Coil:Heating:Water | 414 PTAC HEATING COIL | 2370.17 |
| 42 | Coil:Heating:Water | 415_418 PTAC HEATING COIL | 10851.97 |
| 43 | Coil:Heating:Water | 419 PTAC HEATING COIL | 2885.48 |
| 44 | Coil:Heating:Water | 420_423 PTAC HEATING COIL | 10725.10 |
| 45 | Coil:Heating:Water | 424 PTAC HEATING COIL | 2936.77 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR1 PTAC PTAC COOLING COIL | 54829.6 | 3.16 | 10.77 | 11.41 | 10.79 | 10.70 |
| 2 | Coil:Cooling:DX:SingleSpeed | SAC_FRONTLOUNGE PTAC COOLING COIL | 17359.2 | 3.26 | 11.14 | 11.81 | 11.17 | 11.26 |
| 3 | Coil:Cooling:DX:SingleSpeed | SAC_RESTROOM PTAC COOLING COIL | 1049.8 | 3.08 | 10.52 | 11.14 | 10.54 | 10.33 |
| 4 | Coil:Cooling:DX:SingleSpeed | SAC_MEETINGROOM PTAC COOLING COIL | 9094.0 | 3.30 | 11.26 | 11.94 | 11.30 | 11.45 |
| 5 | Coil:Cooling:DX:SingleSpeed | 101 PTAC PTAC COOLING COIL | 1302.1 | 3.19 | 10.90 | 11.55 | 10.93 | 10.90 |
| 6 | Coil:Cooling:DX:SingleSpeed | 102 PTAC PTAC COOLING COIL | 1303.2 | 3.23 | 11.03 | 11.69 | 11.06 | 11.09 |
| 7 | Coil:Cooling:DX:SingleSpeed | 103 PTAC PTAC COOLING COIL | 1869.3 | 3.13 | 10.67 | 11.31 | 10.70 | 10.56 |
| 8 | Coil:Cooling:DX:SingleSpeed | 104 PTAC PTAC COOLING COIL | 2329.7 | 3.15 | 10.73 | 11.37 | 10.76 | 10.65 |
| 9 | Coil:Cooling:DX:SingleSpeed | 105 PTAC PTAC COOLING COIL | 2981.3 | 3.12 | 10.65 | 11.28 | 10.67 | 10.53 |
| 10 | Coil:Cooling:DX:SingleSpeed | SAC_EMPLOYEELOUNGE PTAC COOLING COIL | 11420.4 | 3.12 | 10.66 | 11.29 | 10.68 | 10.54 |
| 11 | Coil:Cooling:DX:SingleSpeed | SAC_EXERCISECENTER PTAC COOLING COIL | 2905.4 | 3.24 | 11.07 | 11.74 | 11.10 | 11.15 |
| 12 | Coil:Cooling:DX:SingleSpeed | SAC_FRONTOFFICE PTAC COOLING COIL | 7139.6 | 3.16 | 10.80 | 11.44 | 10.82 | 10.74 |
| 13 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR2 PTAC PTAC COOLING COIL | 5284.1 | 3.15 | 10.74 | 11.38 | 10.77 | 10.66 |
| 14 | Coil:Cooling:DX:SingleSpeed | 201 PTAC PTAC COOLING COIL | 1644.9 | 3.19 | 10.89 | 11.54 | 10.92 | 10.89 |
| 15 | Coil:Cooling:DX:SingleSpeed | 202_205 PTAC PTAC COOLING COIL | 7071.1 | 3.14 | 10.70 | 11.33 | 10.72 | 10.60 |
| 16 | Coil:Cooling:DX:SingleSpeed | 206_208 PTAC PTAC COOLING COIL | 5609.1 | 3.13 | 10.69 | 11.33 | 10.72 | 10.59 |
| 17 | Coil:Cooling:DX:SingleSpeed | 209_212 PTAC PTAC COOLING COIL | 6895.5 | 3.14 | 10.71 | 11.34 | 10.73 | 10.61 |
| 18 | Coil:Cooling:DX:SingleSpeed | 213 PTAC PTAC COOLING COIL | 1891.2 | 3.13 | 10.67 | 11.30 | 10.69 | 10.56 |
| 19 | Coil:Cooling:DX:SingleSpeed | 214 PTAC PTAC COOLING COIL | 2497.4 | 3.14 | 10.71 | 11.34 | 10.73 | 10.61 |
| 20 | Coil:Cooling:DX:SingleSpeed | 215_218 PTAC PTAC COOLING COIL | 18134.5 | 3.08 | 10.52 | 11.14 | 10.54 | 10.33 |
| 21 | Coil:Cooling:DX:SingleSpeed | 219 PTAC PTAC COOLING COIL | 9661.6 | 3.08 | 10.52 | 11.14 | 10.54 | 10.33 |
| 22 | Coil:Cooling:DX:SingleSpeed | 220_223 PTAC PTAC COOLING COIL | 8737.4 | 3.15 | 10.75 | 11.39 | 10.78 | 10.68 |
| 23 | Coil:Cooling:DX:SingleSpeed | 224 PTAC PTAC COOLING COIL | 2463.7 | 3.14 | 10.71 | 11.35 | 10.74 | 10.62 |
| 24 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR3 PTAC PTAC COOLING COIL | 4465.3 | 3.23 | 11.01 | 11.67 | 11.04 | 11.06 |
| 25 | Coil:Cooling:DX:SingleSpeed | 301 PTAC PTAC COOLING COIL | 1926.7 | 3.24 | 11.06 | 11.73 | 11.09 | 11.14 |
| 26 | Coil:Cooling:DX:SingleSpeed | 302_305 PTAC PTAC COOLING COIL | 4564.3 | 3.24 | 11.05 | 11.71 | 11.08 | 11.12 |
| 27 | Coil:Cooling:DX:SingleSpeed | 306_308 PTAC PTAC COOLING COIL | 3464.9 | 3.23 | 11.03 | 11.69 | 11.06 | 11.09 |
| 28 | Coil:Cooling:DX:SingleSpeed | 309_312 PTAC PTAC COOLING COIL | 6753.2 | 3.14 | 10.73 | 11.37 | 10.75 | 10.64 |
| 29 | Coil:Cooling:DX:SingleSpeed | 313 PTAC PTAC COOLING COIL | 1887.3 | 3.17 | 10.82 | 11.47 | 10.85 | 10.78 |
| 30 | Coil:Cooling:DX:SingleSpeed | 314 PTAC PTAC COOLING COIL | 2313.8 | 3.15 | 10.74 | 11.37 | 10.76 | 10.65 |
| 31 | Coil:Cooling:DX:SingleSpeed | 315_318 PTAC PTAC COOLING COIL | 9538.3 | 3.14 | 10.73 | 11.36 | 10.75 | 10.64 |
| 32 | Coil:Cooling:DX:SingleSpeed | 319 PTAC PTAC COOLING COIL | 2086.8 | 3.14 | 10.71 | 11.35 | 10.73 | 10.61 |
| 33 | Coil:Cooling:DX:SingleSpeed | 320_323 PTAC PTAC COOLING COIL | 8346.6 | 3.16 | 10.78 | 11.42 | 10.80 | 10.71 |
| 34 | Coil:Cooling:DX:SingleSpeed | 324 PTAC PTAC COOLING COIL | 1548.5 | 3.18 | 10.84 | 11.48 | 10.86 | 10.80 |
| 35 | Coil:Cooling:DX:SingleSpeed | CORRIDORFLR4 PTAC PTAC COOLING COIL | 6738.1 | 3.18 | 10.84 | 11.48 | 10.86 | 10.80 |
| 36 | Coil:Cooling:DX:SingleSpeed | 401 PTAC PTAC COOLING COIL | 2393.9 | 3.15 | 10.75 | 11.39 | 10.77 | 10.67 |
| 37 | Coil:Cooling:DX:SingleSpeed | 402_405 PTAC PTAC COOLING COIL | 6656.9 | 3.22 | 10.98 | 11.63 | 11.01 | 11.01 |
| 38 | Coil:Cooling:DX:SingleSpeed | 406_408 PTAC PTAC COOLING COIL | 5212.5 | 3.21 | 10.97 | 11.62 | 10.99 | 11.00 |
| 39 | Coil:Cooling:DX:SingleSpeed | 409_412 PTAC PTAC COOLING COIL | 8853.7 | 3.15 | 10.75 | 11.39 | 10.78 | 10.68 |
| 40 | Coil:Cooling:DX:SingleSpeed | 413 PTAC PTAC COOLING COIL | 2542.9 | 3.17 | 10.82 | 11.47 | 10.85 | 10.78 |
| 41 | Coil:Cooling:DX:SingleSpeed | 414 PTAC PTAC COOLING COIL | 2290.9 | 3.14 | 10.73 | 11.36 | 10.75 | 10.64 |
| 42 | Coil:Cooling:DX:SingleSpeed | 415_418 PTAC PTAC COOLING COIL | 10592.0 | 3.13 | 10.68 | 11.32 | 10.71 | 10.58 |
| 43 | Coil:Cooling:DX:SingleSpeed | 419 PTAC PTAC COOLING COIL | 2826.3 | 3.13 | 10.67 | 11.30 | 10.69 | 10.55 |
| 44 | Coil:Cooling:DX:SingleSpeed | 420_423 PTAC PTAC COOLING COIL | 10463.7 | 3.13 | 10.69 | 11.32 | 10.71 | 10.58 |
| 45 | Coil:Cooling:DX:SingleSpeed | 424 PTAC PTAC COOLING COIL | 2882.2 | 3.13 | 10.66 | 11.30 | 10.69 | 10.55 |
| Zone Name | # Surfaces | |
| 1 | REARSTAIRSFLR1 | 7 |
| 2 | CORRIDORFLR1 | 33 |
| 3 | REARSTORAGEFLR1 | 6 |
| 4 | FRONTLOUNGEFLR1 | 12 |
| 5 | RESTROOMFLR1 | 6 |
| 6 | MEETINGROOMFLR1 | 10 |
| 7 | MECHANICALROOMFLR1 | 6 |
| 8 | GUESTROOM101 | 7 |
| 9 | GUESTROOM102 | 7 |
| 10 | GUESTROOM103 | 7 |
| 11 | GUESTROOM104 | 7 |
| 12 | GUESTROOM105 | 7 |
| 13 | EMPLOYEELOUNGEFLR1 | 7 |
| 14 | LAUNDRYROOMFLR1 | 10 |
| 15 | ELEVATORCOREFLR1 | 6 |
| 16 | EXERCISECENTERFLR1 | 7 |
| 17 | FRONTOFFICEFLR1 | 11 |
| 18 | FRONTSTAIRSFLR1 | 7 |
| 19 | FRONTSTORAGEFLR1 | 6 |
| 20 | REARSTAIRSFLR2 | 6 |
| 21 | CORRIDORFLR2 | 24 |
| 22 | REARSTORAGEFLR2 | 6 |
| 23 | GUESTROOM201 | 7 |
| 24 | GUESTROOM202_205 | 10 |
| 25 | GUESTROOM206_208 | 11 |
| 26 | GUESTROOM209_212 | 13 |
| 27 | GUESTROOM213 | 7 |
| 28 | GUESTROOM214 | 7 |
| 29 | GUESTROOM215_218 | 12 |
| 30 | ELEVATORCOREFLR2 | 6 |
| 31 | GUESTROOM219 | 7 |
| 32 | GUESTROOM220_223 | 11 |
| 33 | GUESTROOM224 | 7 |
| 34 | FRONTSTORAGEFLR2 | 6 |
| 35 | FRONTSTAIRSFLR2 | 6 |
| 36 | REARSTAIRSFLR3 | 6 |
| 37 | CORRIDORFLR3 | 24 |
| 38 | REARSTORAGEFLR3 | 6 |
| 39 | GUESTROOM301 | 7 |
| 40 | GUESTROOM302_305 | 10 |
| 41 | GUESTROOM306_308 | 9 |
| 42 | GUESTROOM309_312 | 10 |
| 43 | GUESTROOM313 | 7 |
| 44 | GUESTROOM314 | 7 |
| 45 | GUESTROOM315_318 | 10 |
| 46 | ELEVATORCOREFLR3 | 6 |
| 47 | GUESTROOM319 | 7 |
| 48 | GUESTROOM320_323 | 10 |
| 49 | GUESTROOM324 | 7 |
| 50 | FRONTSTORAGEFLR3 | 6 |
| 51 | FRONTSTAIRSFLR3 | 6 |
| 52 | REARSTAIRSFLR4 | 6 |
| 53 | CORRIDORFLR4 | 24 |
| 54 | REARSTORAGEFLR4 | 6 |
| 55 | GUESTROOM401 | 7 |
| 56 | GUESTROOM402_405 | 10 |
| 57 | GUESTROOM406_408 | 9 |
| 58 | GUESTROOM409_412 | 10 |
| 59 | GUESTROOM413 | 7 |
| 60 | GUESTROOM414 | 7 |
| 61 | GUESTROOM415_418 | 10 |
| 62 | ELEVATORCOREFLR4 | 6 |
| 63 | GUESTROOM419 | 7 |
| 64 | GUESTROOM420_423 | 10 |
| 65 | GUESTROOM424 | 7 |
| 66 | FRONTSTORAGEFLR4 | 6 |
| 67 | FRONTSTAIRSFLR4 | 6 |
| Number of Shading Surfaces | # Surfaces | |
| 1 | Number of Shading Surfaces | 2 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | W_REARSTAIRSFLR1_2_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | W_REARSTAIRSFLR1_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 6.23 | 8.18 | 6.23 | 180.00 | 90.00 | 2.44 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 3 | W_REARSTAIRSFLR1_3_0_0_DOOR | Door | W_REARSTAIRSFLR1_3_0_0 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 4 | P_REARSTAIRSFLR1_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_GUESTROOM104_10002_0_10001 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 5 | P_REARSTAIRSFLR1_5_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 8.18 | 8.18 | 8.18 | 0.00 | 90.00 | 2.44 | 3.35 | 0.00 | P_CORRIDORFLR1_10003_0_10002 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | S_REARSTAIRSFLR1_0_0_0 | Floor | CTF - ConductionTransferFunction | S_REARSTAIRSFLR1_0_0_0_FFACTOR | 0.750 | 0.634 | 20.07 | 20.07 | 20.07 | 180.00 | 180.00 | 2.44 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 7 | C_REARSTAIRSFLR1_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 20.07 | 20.07 | 20.07 | 0.00 | 0.00 | 2.44 | 8.23 | 0.00 | F_REARSTAIRSFLR2_10001_0_10000 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 8 | P_CORRIDORFLR1_10003_0_10002 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 8.18 | 8.18 | 8.18 | 180.00 | 90.00 | 2.44 | 3.35 | 0.00 | P_REARSTAIRSFLR1_5_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 9 | W_CORRIDORFLR1_2_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 3.44 | 6.13 | 3.44 | 270.00 | 90.00 | 1.83 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 10 | W_CORRIDORFLR1_2_0_0_0_0 | Window | W_CORRIDORFLR1_2_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.69 | 2.69 | 2.69 | 270.00 | 90.00 | 1.14 | 2.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 11 | P_CORRIDORFLR1_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 180.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_GUESTROOM104_10007_0_10005 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 12 | P_CORRIDORFLR1_5_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 180.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_GUESTROOM105_10008_0_10006 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | P_CORRIDORFLR1_6_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 180.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_EMPLOYEELOUNGEFLR1_10009_0_10007 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 14 | P_CORRIDORFLR1_7_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 39.86 | 39.86 | 39.86 | 180.00 | 90.00 | 11.89 | 3.35 | 0.00 | P_LAUNDRYROOMFLR1_10010_0_10008 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 15 | P_CORRIDORFLR1_8_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.13 | 6.13 | 6.13 | 180.00 | 90.00 | 1.83 | 3.35 | 0.00 | P_ELEVATORCOREFLR1_10011_0_10009 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 16 | P_CORRIDORFLR1_9_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_ELEVATORCOREFLR1_10012_0_10010 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 17 | W_CORRIDORFLR1_10_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 8.27 | 10.22 | 8.27 | 180.00 | 90.00 | 3.05 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 18 | W_CORRIDORFLR1_10_0_0_DOOR | Door | W_CORRIDORFLR1_10_0_0 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 19 | P_CORRIDORFLR1_11_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_EXERCISECENTERFLR1_10013_0_10011 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 20 | P_CORRIDORFLR1_12_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 180.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_EXERCISECENTERFLR1_10014_0_10012 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 21 | P_CORRIDORFLR1_13_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 53.14 | 53.14 | 53.14 | 180.00 | 90.00 | 15.85 | 3.35 | 0.00 | P_FRONTOFFICEFLR1_10015_0_10013 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 22 | P_CORRIDORFLR1_14_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 5.11 | 5.11 | 5.11 | 180.00 | 90.00 | 1.52 | 3.35 | 0.00 | P_FRONTSTORAGEFLR1_10016_0_10014 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 23 | P_CORRIDORFLR1_15_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 8.18 | 8.18 | 8.18 | 180.00 | 90.00 | 2.44 | 3.35 | 0.00 | P_FRONTSTAIRSFLR1_10017_0_10015 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 24 | W_CORRIDORFLR1_16_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 1.69 | 6.13 | 1.69 | 90.00 | 90.00 | 1.83 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.96 | 3.65E-002 | 4 | ||
| 25 | D_CORRIDORFLR1_16_0_0_0_0 | Window | W_CORRIDORFLR1_16_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 4.44 | 4.44 | 4.44 | 90.00 | 90.00 | 1.82 | 2.43 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.83 | 0.17 | 4 |
| 26 | P_CORRIDORFLR1_17_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.43 | 66.43 | 66.43 | 0.00 | 90.00 | 19.81 | 3.35 | 0.00 | P_FRONTLOUNGEFLR1_10018_0_10016 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 27 | P_CORRIDORFLR1_18_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 0.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_RESTROOMFLR1_10019_0_10017 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 28 | P_CORRIDORFLR1_19_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_RESTROOMFLR1_10020_0_10018 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 29 | W_CORRIDORFLR1_20_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 7.53 | 10.22 | 7.53 | 0.00 | 90.00 | 3.05 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 30 | W_CORRIDORFLR1_20_0_0_0_0 | Window | W_CORRIDORFLR1_20_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.69 | 2.69 | 2.69 | 0.00 | 90.00 | 1.14 | 2.36 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 31 | P_CORRIDORFLR1_21_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_MEETINGROOMFLR1_10021_0_10019 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 32 | P_CORRIDORFLR1_22_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 32.70 | 32.70 | 32.70 | 0.00 | 90.00 | 9.75 | 3.35 | 0.00 | P_MEETINGROOMFLR1_10022_0_10020 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 33 | P_CORRIDORFLR1_23_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 0.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_MECHANICALROOMFLR1_10023_0_10021 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 34 | P_CORRIDORFLR1_24_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 0.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_GUESTROOM101_10024_0_10022 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 35 | P_CORRIDORFLR1_25_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 0.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_GUESTROOM102_10025_0_10023 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 36 | P_CORRIDORFLR1_26_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 0.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_GUESTROOM103_10026_0_10024 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 37 | P_CORRIDORFLR1_27_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 8.18 | 8.18 | 8.18 | 0.00 | 90.00 | 2.44 | 3.35 | 0.00 | P_REARSTORAGEFLR1_10027_0_10025 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 38 | S_CORRIDORFLR1_0_0_0 | Floor | CTF - ConductionTransferFunction | S_CORRIDORFLR1_0_0_0_FFACTOR | 8.294E-002 | 8.130E-002 | 150.51 | 150.51 | 150.51 | 180.00 | 180.00 | 12.27 | 12.27 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 12 | ||
| 39 | C_CORRIDORFLR1_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 125.42 | 125.42 | 125.42 | 0.00 | 0.00 | 11.20 | 11.20 | 0.00 | F_CORRIDORFLR2_10004_0_10003 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
| 40 | C_CORRIDORFLR1_1_1_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 25.09 | 25.09 | 25.09 | 0.00 | 0.00 | 3.05 | 8.23 | 0.00 | F_GUESTROOM206_208_10005_0_10004 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 41 | P_REARSTORAGEFLR1_10027_0_10025 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 8.18 | 8.18 | 8.18 | 180.00 | 90.00 | 2.44 | 3.35 | 0.00 | P_CORRIDORFLR1_27_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 42 | W_REARSTORAGEFLR1_2_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 43 | P_REARSTORAGEFLR1_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_GUESTROOM103_10030_0_10027 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 44 | W_REARSTORAGEFLR1_5_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 8.18 | 8.18 | 8.18 | 0.00 | 90.00 | 2.44 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 45 | S_REARSTORAGEFLR1_0_0_0 | Floor | CTF - ConductionTransferFunction | S_REARSTORAGEFLR1_0_0_0_FFACTOR | 0.750 | 0.634 | 20.07 | 20.07 | 20.07 | 180.00 | 180.00 | 2.44 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 46 | C_REARSTORAGEFLR1_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 20.07 | 20.07 | 20.07 | 0.00 | 0.00 | 2.44 | 8.23 | 0.00 | F_REARSTORAGEFLR2_10028_0_10026 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 47 | P_FRONTLOUNGEFLR1_10018_0_10016 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 66.43 | 66.43 | 66.43 | 180.00 | 90.00 | 19.81 | 3.35 | 0.00 | P_CORRIDORFLR1_17_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 48 | P_FRONTLOUNGEFLR1_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_RESTROOMFLR1_10033_0_10030 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 49 | W_FRONTLOUNGEFLR1_4_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.68 | 0.32 | 4 | ||
| 50 | W_FRONTLOUNGEFLR1_5_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 51.60 | 66.43 | 51.60 | 0.00 | 90.00 | 19.81 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 51 | W_FRONTLOUNGEFLR1_5_0_0_0_0 | Window | W_FRONTLOUNGEFLR1_5_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.97 | 2.97 | 2.97 | 0.00 | 90.00 | 2.05 | 1.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 52 | W_FRONTLOUNGEFLR1_5_0_0_0_1 | Window | W_FRONTLOUNGEFLR1_5_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.97 | 2.97 | 2.97 | 0.00 | 90.00 | 2.05 | 1.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 53 | W_FRONTLOUNGEFLR1_5_0_0_0_2 | Window | W_FRONTLOUNGEFLR1_5_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.97 | 2.97 | 2.97 | 0.00 | 90.00 | 2.05 | 1.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 54 | W_FRONTLOUNGEFLR1_5_0_0_0_3 | Window | W_FRONTLOUNGEFLR1_5_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.97 | 2.97 | 2.97 | 0.00 | 90.00 | 2.05 | 1.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 55 | W_FRONTLOUNGEFLR1_5_0_0_0_4 | Window | W_FRONTLOUNGEFLR1_5_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 2.97 | 2.97 | 2.97 | 0.00 | 90.00 | 2.05 | 1.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 56 | S_FRONTLOUNGEFLR1_0_0_0 | Floor | CTF - ConductionTransferFunction | S_FRONTLOUNGEFLR1_0_0_0_FFACTOR | 0.225 | 0.213 | 163.06 | 163.06 | 163.06 | 180.00 | 180.00 | 19.81 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 57 | C_FRONTLOUNGEFLR1_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM201_10031_0_10028 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 58 | C_FRONTLOUNGEFLR1_1_1_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 130.45 | 130.45 | 130.45 | 0.00 | 0.00 | 15.85 | 8.23 | 0.00 | F_GUESTROOM202_205_10032_0_10029 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 59 | P_RESTROOMFLR1_10019_0_10017 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 180.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_CORRIDORFLR1_18_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 60 | P_RESTROOMFLR1_10020_0_10018 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_CORRIDORFLR1_19_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 61 | P_RESTROOMFLR1_10033_0_10030 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_FRONTLOUNGEFLR1_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 62 | W_RESTROOMFLR1_5_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 13.29 | 13.29 | 13.29 | 0.00 | 90.00 | 3.96 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 63 | S_RESTROOMFLR1_0_0_0 | Floor | CTF - ConductionTransferFunction | S_RESTROOMFLR1_0_0_0_FFACTOR | 0.157 | 0.151 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 64 | C_RESTROOMFLR1_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM206_208_10035_0_10031 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 65 | P_MEETINGROOMFLR1_10021_0_10019 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_CORRIDORFLR1_21_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 66 | P_MEETINGROOMFLR1_10022_0_10020 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 32.70 | 32.70 | 32.70 | 180.00 | 90.00 | 9.75 | 3.35 | 0.00 | P_CORRIDORFLR1_22_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 67 | P_MEETINGROOMFLR1_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_MECHANICALROOMFLR1_10041_0_10034 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 68 | W_MEETINGROOMFLR1_5_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 21.31 | 32.70 | 21.31 | 0.00 | 90.00 | 9.75 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 69 | W_MEETINGROOMFLR1_5_0_0_0_0 | Window | W_MEETINGROOMFLR1_5_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 70 | W_MEETINGROOMFLR1_5_0_0_0_1 | Window | W_MEETINGROOMFLR1_5_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 71 | W_MEETINGROOMFLR1_5_0_0_0_2 | Window | W_MEETINGROOMFLR1_5_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 72 | S_MEETINGROOMFLR1_0_0_0 | Floor | CTF - ConductionTransferFunction | S_MEETINGROOMFLR1_0_0_0_FFACTOR | 0.157 | 0.151 | 80.27 | 80.27 | 80.27 | 180.00 | 180.00 | 9.75 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 73 | C_MEETINGROOMFLR1_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 47.66 | 47.66 | 47.66 | 0.00 | 0.00 | 5.79 | 8.23 | 0.00 | F_GUESTROOM206_208_10039_0_10032 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 74 | C_MEETINGROOMFLR1_1_1_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM209_212_10040_0_10033 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 75 | P_MECHANICALROOMFLR1_10023_0_10021 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 180.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_CORRIDORFLR1_23_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 76 | P_MECHANICALROOMFLR1_10041_0_10034 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_MEETINGROOMFLR1_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 77 | P_MECHANICALROOMFLR1_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_GUESTROOM101_10045_0_10036 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 78 | W_MECHANICALROOMFLR1_5_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 13.29 | 13.29 | 13.29 | 0.00 | 90.00 | 3.96 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 79 | S_MECHANICALROOMFLR1_0_0_0 | Floor | CTF - ConductionTransferFunction | S_MECHANICALROOMFLR1_0_0_0_FFACTOR | 0.157 | 0.151 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 80 | C_MECHANICALROOMFLR1_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM209_212_10044_0_10035 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 81 | P_GUESTROOM101_10024_0_10022 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 180.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_CORRIDORFLR1_24_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 82 | P_GUESTROOM101_10045_0_10036 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_MECHANICALROOMFLR1_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 83 | P_GUESTROOM101_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_GUESTROOM102_10049_0_10038 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 84 | W_GUESTROOM101_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.384 | 0.363 | 9.49 | 13.29 | 9.49 | 0.00 | 90.00 | 3.96 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 85 | W_GUESTROOM101_5_0_0_0_0 | Window | W_GUESTROOM101_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 86 | S_GUESTROOM101_0_0_0 | Floor | CTF - ConductionTransferFunction | S_GUESTROOM101_0_0_0_FFACTOR | 0.157 | 0.151 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 87 | C_GUESTROOM101_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM209_212_10048_0_10037 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 88 | P_GUESTROOM102_10025_0_10023 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 180.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_CORRIDORFLR1_25_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 89 | P_GUESTROOM102_10049_0_10038 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_GUESTROOM101_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 90 | P_GUESTROOM102_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_GUESTROOM103_10053_0_10040 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 91 | W_GUESTROOM102_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.384 | 0.363 | 9.49 | 13.29 | 9.49 | 0.00 | 90.00 | 3.96 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 92 | W_GUESTROOM102_5_0_0_0_0 | Window | W_GUESTROOM102_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 93 | S_GUESTROOM102_0_0_0 | Floor | CTF - ConductionTransferFunction | S_GUESTROOM102_0_0_0_FFACTOR | 0.157 | 0.151 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 94 | C_GUESTROOM102_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM209_212_10052_0_10039 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 95 | P_GUESTROOM103_10026_0_10024 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 180.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_CORRIDORFLR1_26_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 96 | P_GUESTROOM103_10030_0_10027 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_REARSTORAGEFLR1_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 97 | P_GUESTROOM103_10053_0_10040 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_GUESTROOM102_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 98 | W_GUESTROOM103_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.384 | 0.363 | 9.49 | 13.29 | 9.49 | 0.00 | 90.00 | 3.96 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 99 | W_GUESTROOM103_5_0_0_0_0 | Window | W_GUESTROOM103_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 100 | S_GUESTROOM103_0_0_0 | Floor | CTF - ConductionTransferFunction | S_GUESTROOM103_0_0_0_FFACTOR | 0.157 | 0.151 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 101 | C_GUESTROOM103_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM213_10056_0_10041 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 102 | P_GUESTROOM104_10002_0_10001 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_REARSTAIRSFLR1_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 103 | P_GUESTROOM104_10007_0_10005 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 0.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_CORRIDORFLR1_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 104 | W_GUESTROOM104_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.384 | 0.363 | 9.49 | 13.29 | 9.49 | 180.00 | 90.00 | 3.96 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 105 | W_GUESTROOM104_3_0_0_0_0 | Window | W_GUESTROOM104_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 106 | P_GUESTROOM104_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_GUESTROOM105_10062_0_10043 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 107 | S_GUESTROOM104_0_0_0 | Floor | CTF - ConductionTransferFunction | S_GUESTROOM104_0_0_0_FFACTOR | 0.157 | 0.151 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 108 | C_GUESTROOM104_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM214_10060_0_10042 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 109 | P_GUESTROOM105_10008_0_10006 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 0.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_CORRIDORFLR1_5_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 110 | P_GUESTROOM105_10062_0_10043 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_GUESTROOM104_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 111 | W_GUESTROOM105_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_GRD | 0.384 | 0.363 | 9.49 | 13.29 | 9.49 | 180.00 | 90.00 | 3.96 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 112 | W_GUESTROOM105_3_0_0_0_0 | Window | W_GUESTROOM105_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 113 | P_GUESTROOM105_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_EMPLOYEELOUNGEFLR1_10066_0_10045 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 114 | S_GUESTROOM105_0_0_0 | Floor | CTF - ConductionTransferFunction | S_GUESTROOM105_0_0_0_FFACTOR | 0.157 | 0.151 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 115 | C_GUESTROOM105_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM215_218_10064_0_10044 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 116 | P_EMPLOYEELOUNGEFLR1_10009_0_10007 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 0.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_CORRIDORFLR1_6_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 117 | P_EMPLOYEELOUNGEFLR1_10066_0_10045 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_GUESTROOM105_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 118 | W_EMPLOYEELOUNGEFLR1_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 9.49 | 13.29 | 9.49 | 180.00 | 90.00 | 3.96 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 119 | W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | Window | W_EMPLOYEELOUNGEFLR1_3_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 120 | P_EMPLOYEELOUNGEFLR1_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_LAUNDRYROOMFLR1_10070_0_10047 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 121 | S_EMPLOYEELOUNGEFLR1_0_0_0 | Floor | CTF - ConductionTransferFunction | S_EMPLOYEELOUNGEFLR1_0_0_0_FFACTOR | 0.157 | 0.151 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 122 | C_EMPLOYEELOUNGEFLR1_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM215_218_10068_0_10046 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 123 | P_LAUNDRYROOMFLR1_10010_0_10008 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 39.86 | 39.86 | 39.86 | 0.00 | 90.00 | 11.89 | 3.35 | 0.00 | P_CORRIDORFLR1_7_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 124 | P_LAUNDRYROOMFLR1_10070_0_10047 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_EMPLOYEELOUNGEFLR1_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 125 | W_LAUNDRYROOMFLR1_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 28.46 | 39.86 | 28.46 | 180.00 | 90.00 | 11.89 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 126 | W_LAUNDRYROOMFLR1_3_0_0_0_0 | Window | W_LAUNDRYROOMFLR1_3_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 127 | W_LAUNDRYROOMFLR1_3_0_0_0_1 | Window | W_LAUNDRYROOMFLR1_3_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 128 | W_LAUNDRYROOMFLR1_3_0_0_0_2 | Window | W_LAUNDRYROOMFLR1_3_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 129 | P_LAUNDRYROOMFLR1_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_ELEVATORCOREFLR1_10075_0_10050 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 130 | S_LAUNDRYROOMFLR1_0_0_0 | Floor | CTF - ConductionTransferFunction | S_LAUNDRYROOMFLR1_0_0_0_FFACTOR | 0.157 | 0.151 | 97.83 | 97.83 | 97.83 | 180.00 | 180.00 | 11.89 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 131 | C_LAUNDRYROOMFLR1_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 65.22 | 65.22 | 65.22 | 0.00 | 0.00 | 7.92 | 8.23 | 0.00 | F_GUESTROOM215_218_10072_0_10048 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 132 | C_LAUNDRYROOMFLR1_1_1_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM219_10073_0_10049 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 133 | P_ELEVATORCOREFLR1_10011_0_10009 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.13 | 6.13 | 6.13 | 0.00 | 90.00 | 1.83 | 3.35 | 0.00 | P_CORRIDORFLR1_8_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 134 | P_ELEVATORCOREFLR1_10012_0_10010 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_CORRIDORFLR1_9_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 135 | P_ELEVATORCOREFLR1_10075_0_10050 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_LAUNDRYROOMFLR1_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 136 | W_ELEVATORCOREFLR1_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 6.13 | 6.13 | 6.13 | 180.00 | 90.00 | 1.83 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 137 | S_ELEVATORCOREFLR1_0_0_0 | Floor | CTF - ConductionTransferFunction | S_ELEVATORCOREFLR1_0_0_0_FFACTOR | 0.157 | 0.151 | 15.05 | 15.05 | 15.05 | 180.00 | 180.00 | 1.83 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 138 | C_ELEVATORCOREFLR1_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 15.05 | 15.05 | 15.05 | 0.00 | 0.00 | 1.83 | 8.23 | 0.00 | F_ELEVATORCOREFLR2_10077_0_10051 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 139 | P_EXERCISECENTERFLR1_10013_0_10011 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_CORRIDORFLR1_11_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 140 | P_EXERCISECENTERFLR1_10014_0_10012 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 13.29 | 13.29 | 13.29 | 0.00 | 90.00 | 3.96 | 3.35 | 0.00 | P_CORRIDORFLR1_12_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 141 | W_EXERCISECENTERFLR1_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 9.49 | 13.29 | 9.49 | 180.00 | 90.00 | 3.96 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 142 | W_EXERCISECENTERFLR1_3_0_0_0_0 | Window | W_EXERCISECENTERFLR1_3_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 143 | P_EXERCISECENTERFLR1_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_FRONTOFFICEFLR1_10083_0_10053 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 144 | S_EXERCISECENTERFLR1_0_0_0 | Floor | CTF - ConductionTransferFunction | S_EXERCISECENTERFLR1_0_0_0_FFACTOR | 0.157 | 0.151 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 145 | C_EXERCISECENTERFLR1_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM220_223_10081_0_10052 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 146 | P_FRONTOFFICEFLR1_10015_0_10013 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 53.14 | 53.14 | 53.14 | 0.00 | 90.00 | 15.85 | 3.35 | 0.00 | P_CORRIDORFLR1_13_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 147 | P_FRONTOFFICEFLR1_10083_0_10053 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_EXERCISECENTERFLR1_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 148 | W_FRONTOFFICEFLR1_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 37.95 | 53.14 | 37.95 | 180.00 | 90.00 | 15.85 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 149 | W_FRONTOFFICEFLR1_3_0_0_0_0 | Window | W_FRONTOFFICEFLR1_3_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 150 | W_FRONTOFFICEFLR1_3_0_0_0_1 | Window | W_FRONTOFFICEFLR1_3_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 151 | W_FRONTOFFICEFLR1_3_0_0_0_2 | Window | W_FRONTOFFICEFLR1_3_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 152 | W_FRONTOFFICEFLR1_3_0_0_0_3 | Window | W_FRONTOFFICEFLR1_3_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 153 | P_FRONTOFFICEFLR1_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_FRONTSTORAGEFLR1_10088_0_10056 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 154 | S_FRONTOFFICEFLR1_0_0_0 | Floor | CTF - ConductionTransferFunction | S_FRONTOFFICEFLR1_0_0_0_FFACTOR | 0.157 | 0.151 | 130.44 | 130.44 | 130.44 | 180.00 | 180.00 | 15.85 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 155 | C_FRONTOFFICEFLR1_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 97.83 | 97.83 | 97.83 | 0.00 | 0.00 | 11.89 | 8.23 | 0.00 | F_GUESTROOM220_223_10085_0_10054 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 156 | C_FRONTOFFICEFLR1_1_1_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM224_10086_0_10055 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 157 | P_FRONTSTAIRSFLR1_10017_0_10015 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 8.18 | 8.18 | 8.18 | 0.00 | 90.00 | 2.44 | 3.35 | 0.00 | P_CORRIDORFLR1_15_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 158 | P_FRONTSTAIRSFLR1_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_FRONTSTORAGEFLR1_10091_0_10058 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 159 | W_FRONTSTAIRSFLR1_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 6.22 | 8.18 | 6.22 | 180.00 | 90.00 | 2.44 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 160 | W_FRONTSTAIRSFLR1_3_0_0_DOOR | Door | W_FRONTSTAIRSFLR1_3_0_0 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 161 | W_FRONTSTAIRSFLR1_4_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.68 | 0.32 | 4 | ||
| 162 | S_FRONTSTAIRSFLR1_0_0_0 | Floor | CTF - ConductionTransferFunction | S_FRONTSTAIRSFLR1_0_0_0_FFACTOR | 0.750 | 0.634 | 20.07 | 20.07 | 20.07 | 180.00 | 180.00 | 2.44 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 163 | C_FRONTSTAIRSFLR1_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 20.07 | 20.07 | 20.07 | 0.00 | 0.00 | 2.44 | 8.23 | 0.00 | F_FRONTSTAIRSFLR2_10090_0_10057 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 164 | P_FRONTSTORAGEFLR1_10016_0_10014 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 5.11 | 5.11 | 5.11 | 0.00 | 90.00 | 1.52 | 3.35 | 0.00 | P_CORRIDORFLR1_14_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 165 | P_FRONTSTORAGEFLR1_10088_0_10056 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 270.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_FRONTOFFICEFLR1_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 166 | P_FRONTSTORAGEFLR1_10091_0_10058 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 27.59 | 27.59 | 27.59 | 90.00 | 90.00 | 8.23 | 3.35 | 0.00 | P_FRONTSTAIRSFLR1_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 167 | W_FRONTSTORAGEFLR1_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.514 | 0.477 | 5.11 | 5.11 | 5.11 | 180.00 | 90.00 | 1.52 | 3.35 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 168 | S_FRONTSTORAGEFLR1_0_0_0 | Floor | CTF - ConductionTransferFunction | S_FRONTSTORAGEFLR1_0_0_0_FFACTOR | 0.157 | 0.151 | 12.54 | 12.54 | 12.54 | 180.00 | 180.00 | 1.52 | 8.23 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 169 | C_FRONTSTORAGEFLR1_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 12.54 | 12.54 | 12.54 | 0.00 | 0.00 | 1.52 | 8.23 | 0.00 | F_FRONTSTORAGEFLR2_10093_0_10059 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 170 | W_REARSTAIRSFLR2_2_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 171 | W_REARSTAIRSFLR2_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 2.44 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 172 | P_REARSTAIRSFLR2_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM214_10099_0_10061 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 173 | P_REARSTAIRSFLR2_5_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_CORRIDORFLR2_10100_0_10062 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 174 | F_REARSTAIRSFLR2_10001_0_10000 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 20.07 | 20.07 | 20.07 | 180.00 | 180.00 | 2.44 | 8.23 | 0.00 | C_REARSTAIRSFLR1_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 175 | C_REARSTAIRSFLR2_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 20.07 | 20.07 | 20.07 | 0.00 | 0.00 | 2.44 | 8.23 | 0.00 | F_REARSTAIRSFLR3_10098_0_10060 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 176 | P_CORRIDORFLR2_10100_0_10062 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_REARSTAIRSFLR2_5_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 177 | W_CORRIDORFLR2_2_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 3.71 | 5.02 | 3.71 | 270.00 | 90.00 | 1.83 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 178 | W_CORRIDORFLR2_2_0_0_0_0 | Window | W_CORRIDORFLR2_2_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.31 | 1.31 | 1.31 | 270.00 | 90.00 | 0.92 | 1.42 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 179 | P_CORRIDORFLR2_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_GUESTROOM214_10104_0_10064 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 180 | P_CORRIDORFLR2_5_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_GUESTROOM215_218_10105_0_10065 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 181 | P_CORRIDORFLR2_6_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_GUESTROOM219_10106_0_10066 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 182 | P_CORRIDORFLR2_7_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 5.02 | 5.02 | 5.02 | 180.00 | 90.00 | 1.83 | 2.74 | 0.00 | P_ELEVATORCOREFLR2_10107_0_10067 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 183 | P_CORRIDORFLR2_8_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_ELEVATORCOREFLR2_10108_0_10068 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 184 | W_CORRIDORFLR2_9_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 8.36 | 8.36 | 8.36 | 180.00 | 90.00 | 3.05 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 185 | P_CORRIDORFLR2_10_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM220_223_10109_0_10069 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 186 | P_CORRIDORFLR2_11_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_GUESTROOM220_223_10110_0_10070 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 187 | P_CORRIDORFLR2_12_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_GUESTROOM224_10111_0_10071 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 188 | P_CORRIDORFLR2_13_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 4.18 | 4.18 | 4.18 | 180.00 | 90.00 | 1.52 | 2.74 | 0.00 | P_FRONTSTORAGEFLR2_10112_0_10072 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 189 | P_CORRIDORFLR2_14_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_FRONTSTAIRSFLR2_10113_0_10073 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 190 | W_CORRIDORFLR2_15_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 3.71 | 5.02 | 3.71 | 90.00 | 90.00 | 1.83 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 191 | W_CORRIDORFLR2_15_0_0_0_0 | Window | W_CORRIDORFLR2_15_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.31 | 1.31 | 1.31 | 90.00 | 90.00 | 0.92 | 1.42 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 192 | P_CORRIDORFLR2_16_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_GUESTROOM201_10114_0_10074 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 193 | P_CORRIDORFLR2_17_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_GUESTROOM202_205_10115_0_10075 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 194 | P_CORRIDORFLR2_18_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.12 | 35.12 | 35.12 | 0.00 | 90.00 | 12.80 | 2.74 | 0.00 | P_GUESTROOM206_208_10116_0_10076 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 195 | P_CORRIDORFLR2_19_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_GUESTROOM209_212_10117_0_10077 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 196 | P_CORRIDORFLR2_20_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_GUESTROOM213_10118_0_10078 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 197 | P_CORRIDORFLR2_21_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_REARSTORAGEFLR2_10119_0_10079 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 198 | F_CORRIDORFLR2_10004_0_10003 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 125.42 | 125.42 | 125.42 | 180.00 | 180.00 | 11.20 | 11.20 | 0.00 | C_CORRIDORFLR1_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
| 199 | C_CORRIDORFLR2_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 125.42 | 125.42 | 125.42 | 0.00 | 0.00 | 11.20 | 11.20 | 0.00 | F_CORRIDORFLR3_10102_0_10063 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
| 200 | P_REARSTORAGEFLR2_10119_0_10079 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_CORRIDORFLR2_21_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 201 | W_REARSTORAGEFLR2_2_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 202 | P_REARSTORAGEFLR2_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM213_10123_0_10081 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 203 | W_REARSTORAGEFLR2_5_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 2.44 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 204 | F_REARSTORAGEFLR2_10028_0_10026 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 20.07 | 20.07 | 20.07 | 180.00 | 180.00 | 2.44 | 8.23 | 0.00 | C_REARSTORAGEFLR1_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 205 | C_REARSTORAGEFLR2_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 20.07 | 20.07 | 20.07 | 0.00 | 0.00 | 2.44 | 8.23 | 0.00 | F_REARSTORAGEFLR3_10121_0_10080 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 206 | P_GUESTROOM201_10114_0_10074 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_CORRIDORFLR2_16_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 207 | P_GUESTROOM201_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM202_205_10126_0_10083 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 208 | W_GUESTROOM201_4_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 209 | W_GUESTROOM201_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 7.06 | 10.87 | 7.06 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 210 | W_GUESTROOM201_5_0_0_0_0 | Window | W_GUESTROOM201_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 0.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 211 | F_GUESTROOM201_10031_0_10028 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_FRONTLOUNGEFLR1_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 212 | C_GUESTROOM201_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM301_10125_0_10082 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 213 | P_GUESTROOM202_205_10115_0_10075 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_CORRIDORFLR2_17_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 214 | P_GUESTROOM202_205_10126_0_10083 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM201_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 215 | P_GUESTROOM202_205_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM206_208_10130_0_10085 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 216 | W_GUESTROOM202_205_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 28.24 | 43.48 | 28.24 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 217 | W_GUESTROOM202_205_5_0_0_0_0 | Window | W_GUESTROOM202_205_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 0.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 218 | W_GUESTROOM202_205_5_0_0_0_1 | Window | W_GUESTROOM202_205_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 0.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 219 | W_GUESTROOM202_205_5_0_0_0_2 | Window | W_GUESTROOM202_205_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 0.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 220 | W_GUESTROOM202_205_5_0_0_0_3 | Window | W_GUESTROOM202_205_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 0.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 221 | F_GUESTROOM202_205_10032_0_10029 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 130.45 | 130.45 | 130.45 | 180.00 | 180.00 | 15.85 | 8.23 | 0.00 | C_FRONTLOUNGEFLR1_1_1_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 222 | C_GUESTROOM202_205_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 130.45 | 130.45 | 130.45 | 0.00 | 0.00 | 15.85 | 8.23 | 0.00 | F_GUESTROOM302_305_10129_0_10084 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 223 | P_GUESTROOM206_208_10116_0_10076 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.12 | 35.12 | 35.12 | 180.00 | 90.00 | 12.80 | 2.74 | 0.00 | P_CORRIDORFLR2_18_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 224 | P_GUESTROOM206_208_10130_0_10085 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM202_205_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 225 | P_GUESTROOM206_208_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM209_212_10137_0_10087 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 226 | W_GUESTROOM206_208_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 24.09 | 35.12 | 24.09 | 0.00 | 90.00 | 12.80 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 227 | W_GUESTROOM206_208_5_0_0_0_0 | Window | W_GUESTROOM206_208_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 0.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 228 | W_GUESTROOM206_208_5_0_0_0_1 | Window | W_GUESTROOM206_208_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.41 | 3.41 | 3.41 | 0.00 | 90.00 | 2.36 | 1.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 229 | W_GUESTROOM206_208_5_0_0_0_2 | Window | W_GUESTROOM206_208_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 0.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 230 | F_GUESTROOM206_208_10005_0_10004 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 25.09 | 25.09 | 25.09 | 180.00 | 180.00 | 3.05 | 8.23 | 0.00 | C_CORRIDORFLR1_1_1_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 231 | F_GUESTROOM206_208_10035_0_10031 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_RESTROOMFLR1_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 232 | F_GUESTROOM206_208_10039_0_10032 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 47.66 | 47.66 | 47.66 | 180.00 | 180.00 | 5.79 | 8.23 | 0.00 | C_MEETINGROOMFLR1_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 233 | C_GUESTROOM206_208_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 105.36 | 105.36 | 105.36 | 0.00 | 0.00 | 12.80 | 8.23 | 0.00 | F_GUESTROOM306_308_10136_0_10086 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 234 | P_GUESTROOM209_212_10117_0_10077 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_CORRIDORFLR2_19_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 235 | P_GUESTROOM209_212_10137_0_10087 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM206_208_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 236 | P_GUESTROOM209_212_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM213_10145_0_10089 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 237 | W_GUESTROOM209_212_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 28.24 | 43.48 | 28.24 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 238 | W_GUESTROOM209_212_5_0_0_0_0 | Window | W_GUESTROOM209_212_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 0.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 239 | W_GUESTROOM209_212_5_0_0_0_1 | Window | W_GUESTROOM209_212_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 0.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 240 | W_GUESTROOM209_212_5_0_0_0_2 | Window | W_GUESTROOM209_212_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 0.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 241 | W_GUESTROOM209_212_5_0_0_0_3 | Window | W_GUESTROOM209_212_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 0.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 242 | F_GUESTROOM209_212_10040_0_10033 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_MEETINGROOMFLR1_1_1_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 243 | F_GUESTROOM209_212_10044_0_10035 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_MECHANICALROOMFLR1_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 244 | F_GUESTROOM209_212_10048_0_10037 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_GUESTROOM101_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 245 | F_GUESTROOM209_212_10052_0_10039 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_GUESTROOM102_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 246 | C_GUESTROOM209_212_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 130.45 | 130.45 | 130.45 | 0.00 | 0.00 | 15.85 | 8.23 | 0.00 | F_GUESTROOM309_312_10144_0_10088 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 247 | P_GUESTROOM213_10118_0_10078 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_CORRIDORFLR2_20_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 248 | P_GUESTROOM213_10123_0_10081 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_REARSTORAGEFLR2_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 249 | P_GUESTROOM213_10145_0_10089 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM209_212_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 250 | W_GUESTROOM213_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 7.06 | 10.87 | 7.06 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 251 | W_GUESTROOM213_5_0_0_0_0 | Window | W_GUESTROOM213_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 0.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 252 | F_GUESTROOM213_10056_0_10041 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_GUESTROOM103_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 253 | C_GUESTROOM213_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM313_10149_0_10090 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 254 | P_GUESTROOM214_10099_0_10061 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_REARSTAIRSFLR2_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 255 | P_GUESTROOM214_10104_0_10064 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_CORRIDORFLR2_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 256 | W_GUESTROOM214_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 7.06 | 10.87 | 7.06 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 257 | W_GUESTROOM214_3_0_0_0_0 | Window | W_GUESTROOM214_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 180.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 258 | P_GUESTROOM214_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM215_218_10156_0_10092 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 259 | F_GUESTROOM214_10060_0_10042 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_GUESTROOM104_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 260 | C_GUESTROOM214_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM314_10154_0_10091 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 261 | P_GUESTROOM215_218_10105_0_10065 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_CORRIDORFLR2_5_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 262 | P_GUESTROOM215_218_10156_0_10092 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM214_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 263 | W_GUESTROOM215_218_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 28.24 | 43.48 | 28.24 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 264 | W_GUESTROOM215_218_3_0_0_0_0 | Window | W_GUESTROOM215_218_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 180.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 265 | W_GUESTROOM215_218_3_0_0_0_1 | Window | W_GUESTROOM215_218_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 180.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 266 | W_GUESTROOM215_218_3_0_0_0_2 | Window | W_GUESTROOM215_218_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 180.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 267 | W_GUESTROOM215_218_3_0_0_0_3 | Window | W_GUESTROOM215_218_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 180.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 268 | P_GUESTROOM215_218_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM219_10163_0_10094 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 269 | F_GUESTROOM215_218_10064_0_10044 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_GUESTROOM105_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 270 | F_GUESTROOM215_218_10068_0_10046 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_EMPLOYEELOUNGEFLR1_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 271 | F_GUESTROOM215_218_10072_0_10048 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 65.22 | 65.22 | 65.22 | 180.00 | 180.00 | 7.92 | 8.23 | 0.00 | C_LAUNDRYROOMFLR1_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 272 | C_GUESTROOM215_218_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 130.44 | 130.44 | 130.44 | 0.00 | 0.00 | 15.85 | 8.23 | 0.00 | F_GUESTROOM315_318_10161_0_10093 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 273 | P_ELEVATORCOREFLR2_10107_0_10067 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 5.02 | 5.02 | 5.02 | 0.00 | 90.00 | 1.83 | 2.74 | 0.00 | P_CORRIDORFLR2_7_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 274 | P_ELEVATORCOREFLR2_10108_0_10068 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_CORRIDORFLR2_8_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 275 | P_ELEVATORCOREFLR2_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM219_10167_0_10096 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 276 | W_ELEVATORCOREFLR2_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 5.02 | 5.02 | 5.02 | 180.00 | 90.00 | 1.83 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 277 | F_ELEVATORCOREFLR2_10077_0_10051 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 15.05 | 15.05 | 15.05 | 180.00 | 180.00 | 1.83 | 8.23 | 0.00 | C_ELEVATORCOREFLR1_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 278 | C_ELEVATORCOREFLR2_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 15.05 | 15.05 | 15.05 | 0.00 | 0.00 | 1.83 | 8.23 | 0.00 | F_ELEVATORCOREFLR3_10166_0_10095 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 279 | P_GUESTROOM219_10106_0_10066 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_CORRIDORFLR2_6_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 280 | P_GUESTROOM219_10163_0_10094 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM215_218_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 281 | P_GUESTROOM219_10167_0_10096 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_ELEVATORCOREFLR2_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 282 | W_GUESTROOM219_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 7.06 | 10.87 | 7.06 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 283 | W_GUESTROOM219_3_0_0_0_0 | Window | W_GUESTROOM219_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 180.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 284 | F_GUESTROOM219_10073_0_10049 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_LAUNDRYROOMFLR1_1_1_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 285 | C_GUESTROOM219_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM319_10171_0_10097 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 286 | P_GUESTROOM220_223_10109_0_10069 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_CORRIDORFLR2_10_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 287 | P_GUESTROOM220_223_10110_0_10070 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_CORRIDORFLR2_11_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 288 | W_GUESTROOM220_223_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 28.24 | 43.48 | 28.24 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 289 | W_GUESTROOM220_223_3_0_0_0_0 | Window | W_GUESTROOM220_223_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 180.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 290 | W_GUESTROOM220_223_3_0_0_0_1 | Window | W_GUESTROOM220_223_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 180.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 291 | W_GUESTROOM220_223_3_0_0_0_2 | Window | W_GUESTROOM220_223_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 180.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 292 | W_GUESTROOM220_223_3_0_0_0_3 | Window | W_GUESTROOM220_223_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 180.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 293 | P_GUESTROOM220_223_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM224_10179_0_10099 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 294 | F_GUESTROOM220_223_10081_0_10052 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_EXERCISECENTERFLR1_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 295 | F_GUESTROOM220_223_10085_0_10054 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 97.83 | 97.83 | 97.83 | 180.00 | 180.00 | 11.89 | 8.23 | 0.00 | C_FRONTOFFICEFLR1_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 296 | C_GUESTROOM220_223_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 130.44 | 130.44 | 130.44 | 0.00 | 0.00 | 15.85 | 8.23 | 0.00 | F_GUESTROOM320_323_10177_0_10098 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 297 | P_GUESTROOM224_10111_0_10071 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_CORRIDORFLR2_12_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 298 | P_GUESTROOM224_10179_0_10099 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM220_223_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 299 | W_GUESTROOM224_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 7.06 | 10.87 | 7.06 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 300 | W_GUESTROOM224_3_0_0_0_0 | Window | W_GUESTROOM224_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.81 | 3.81 | 3.81 | 180.00 | 90.00 | 1.81 | 2.11 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 301 | P_GUESTROOM224_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_FRONTSTORAGEFLR2_10184_0_10101 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 302 | F_GUESTROOM224_10086_0_10055 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_FRONTOFFICEFLR1_1_1_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 303 | C_GUESTROOM224_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM324_10182_0_10100 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 304 | P_FRONTSTORAGEFLR2_10112_0_10072 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 4.18 | 4.18 | 4.18 | 0.00 | 90.00 | 1.52 | 2.74 | 0.00 | P_CORRIDORFLR2_13_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 305 | P_FRONTSTORAGEFLR2_10184_0_10101 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM224_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 306 | W_FRONTSTORAGEFLR2_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 4.18 | 4.18 | 4.18 | 180.00 | 90.00 | 1.52 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 307 | P_FRONTSTORAGEFLR2_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_FRONTSTAIRSFLR2_10189_0_10103 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 308 | F_FRONTSTORAGEFLR2_10093_0_10059 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 12.54 | 12.54 | 12.54 | 180.00 | 180.00 | 1.52 | 8.23 | 0.00 | C_FRONTSTORAGEFLR1_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 309 | C_FRONTSTORAGEFLR2_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 12.54 | 12.54 | 12.54 | 0.00 | 0.00 | 1.52 | 8.23 | 0.00 | F_FRONTSTORAGEFLR3_10187_0_10102 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 310 | P_FRONTSTAIRSFLR2_10113_0_10073 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_CORRIDORFLR2_14_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 311 | P_FRONTSTAIRSFLR2_10189_0_10103 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_FRONTSTORAGEFLR2_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 312 | W_FRONTSTAIRSFLR2_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 2.44 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 313 | W_FRONTSTAIRSFLR2_4_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 314 | F_FRONTSTAIRSFLR2_10090_0_10057 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 20.07 | 20.07 | 20.07 | 180.00 | 180.00 | 2.44 | 8.23 | 0.00 | C_FRONTSTAIRSFLR1_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 315 | C_FRONTSTAIRSFLR2_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 20.07 | 20.07 | 20.07 | 0.00 | 0.00 | 2.44 | 8.23 | 0.00 | F_FRONTSTAIRSFLR3_10192_0_10104 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 316 | W_REARSTAIRSFLR3_2_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 317 | W_REARSTAIRSFLR3_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 2.44 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 318 | P_REARSTAIRSFLR3_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM314_10197_0_10106 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 319 | P_REARSTAIRSFLR3_5_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_CORRIDORFLR3_10198_0_10107 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 320 | F_REARSTAIRSFLR3_10098_0_10060 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 20.07 | 20.07 | 20.07 | 180.00 | 180.00 | 2.44 | 8.23 | 0.00 | C_REARSTAIRSFLR2_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 321 | C_REARSTAIRSFLR3_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 20.07 | 20.07 | 20.07 | 0.00 | 0.00 | 2.44 | 8.23 | 0.00 | F_REARSTAIRSFLR4_10196_0_10105 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 322 | P_CORRIDORFLR3_10198_0_10107 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_REARSTAIRSFLR3_5_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 323 | W_CORRIDORFLR3_2_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 3.71 | 5.02 | 3.71 | 270.00 | 90.00 | 1.83 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 324 | W_CORRIDORFLR3_2_0_0_0_0 | Window | W_CORRIDORFLR3_2_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.31 | 1.31 | 1.31 | 270.00 | 90.00 | 0.92 | 1.42 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 325 | P_CORRIDORFLR3_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_GUESTROOM314_10202_0_10109 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 326 | P_CORRIDORFLR3_5_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_GUESTROOM315_318_10203_0_10110 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 327 | P_CORRIDORFLR3_6_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_GUESTROOM319_10204_0_10111 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 328 | P_CORRIDORFLR3_7_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 5.02 | 5.02 | 5.02 | 180.00 | 90.00 | 1.83 | 2.74 | 0.00 | P_ELEVATORCOREFLR3_10205_0_10112 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 329 | P_CORRIDORFLR3_8_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_ELEVATORCOREFLR3_10206_0_10113 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 330 | W_CORRIDORFLR3_9_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 8.36 | 8.36 | 8.36 | 180.00 | 90.00 | 3.05 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 331 | P_CORRIDORFLR3_10_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM320_323_10207_0_10114 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 332 | P_CORRIDORFLR3_11_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_GUESTROOM320_323_10208_0_10115 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 333 | P_CORRIDORFLR3_12_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_GUESTROOM324_10209_0_10116 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 334 | P_CORRIDORFLR3_13_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 4.18 | 4.18 | 4.18 | 180.00 | 90.00 | 1.52 | 2.74 | 0.00 | P_FRONTSTORAGEFLR3_10210_0_10117 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 335 | P_CORRIDORFLR3_14_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_FRONTSTAIRSFLR3_10211_0_10118 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 336 | W_CORRIDORFLR3_15_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 3.71 | 5.02 | 3.71 | 90.00 | 90.00 | 1.83 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 337 | W_CORRIDORFLR3_15_0_0_0_0 | Window | W_CORRIDORFLR3_15_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.31 | 1.31 | 1.31 | 90.00 | 90.00 | 0.92 | 1.42 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 338 | P_CORRIDORFLR3_16_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_GUESTROOM301_10212_0_10119 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 339 | P_CORRIDORFLR3_17_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_GUESTROOM302_305_10213_0_10120 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 340 | P_CORRIDORFLR3_18_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.12 | 35.12 | 35.12 | 0.00 | 90.00 | 12.80 | 2.74 | 0.00 | P_GUESTROOM306_308_10214_0_10121 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 341 | P_CORRIDORFLR3_19_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_GUESTROOM309_312_10215_0_10122 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 342 | P_CORRIDORFLR3_20_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_GUESTROOM313_10216_0_10123 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 343 | P_CORRIDORFLR3_21_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_REARSTORAGEFLR3_10217_0_10124 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 344 | F_CORRIDORFLR3_10102_0_10063 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 125.42 | 125.42 | 125.42 | 180.00 | 180.00 | 11.20 | 11.20 | 0.00 | C_CORRIDORFLR2_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
| 345 | C_CORRIDORFLR3_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 125.42 | 125.42 | 125.42 | 0.00 | 0.00 | 11.20 | 11.20 | 0.00 | F_CORRIDORFLR4_10200_0_10108 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
| 346 | P_REARSTORAGEFLR3_10217_0_10124 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_CORRIDORFLR3_21_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 347 | W_REARSTORAGEFLR3_2_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 348 | P_REARSTORAGEFLR3_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM313_10221_0_10126 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 349 | W_REARSTORAGEFLR3_5_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 2.44 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 350 | F_REARSTORAGEFLR3_10121_0_10080 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 20.07 | 20.07 | 20.07 | 180.00 | 180.00 | 2.44 | 8.23 | 0.00 | C_REARSTORAGEFLR2_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 351 | C_REARSTORAGEFLR3_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 20.07 | 20.07 | 20.07 | 0.00 | 0.00 | 2.44 | 8.23 | 0.00 | F_REARSTORAGEFLR4_10219_0_10125 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 352 | P_GUESTROOM301_10212_0_10119 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_CORRIDORFLR3_16_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 353 | P_GUESTROOM301_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM302_305_10224_0_10128 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 354 | W_GUESTROOM301_4_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 355 | W_GUESTROOM301_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 7.07 | 10.87 | 7.07 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 356 | W_GUESTROOM301_5_0_0_0_0 | Window | W_GUESTROOM301_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 357 | F_GUESTROOM301_10125_0_10082 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_GUESTROOM201_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 358 | C_GUESTROOM301_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM401_10223_0_10127 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 359 | P_GUESTROOM302_305_10213_0_10120 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_CORRIDORFLR3_17_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 360 | P_GUESTROOM302_305_10224_0_10128 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM301_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 361 | P_GUESTROOM302_305_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM306_308_10228_0_10130 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 362 | W_GUESTROOM302_305_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 28.27 | 43.48 | 28.27 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 363 | W_GUESTROOM302_305_5_0_0_0_0 | Window | W_GUESTROOM302_305_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 364 | W_GUESTROOM302_305_5_0_0_0_1 | Window | W_GUESTROOM302_305_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 365 | W_GUESTROOM302_305_5_0_0_0_2 | Window | W_GUESTROOM302_305_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 366 | W_GUESTROOM302_305_5_0_0_0_3 | Window | W_GUESTROOM302_305_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 367 | F_GUESTROOM302_305_10129_0_10084 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 130.45 | 130.45 | 130.45 | 180.00 | 180.00 | 15.85 | 8.23 | 0.00 | C_GUESTROOM202_205_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 368 | C_GUESTROOM302_305_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 130.45 | 130.45 | 130.45 | 0.00 | 0.00 | 15.85 | 8.23 | 0.00 | F_GUESTROOM402_405_10227_0_10129 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 369 | P_GUESTROOM306_308_10214_0_10121 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.12 | 35.12 | 35.12 | 180.00 | 90.00 | 12.80 | 2.74 | 0.00 | P_CORRIDORFLR3_18_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 370 | P_GUESTROOM306_308_10228_0_10130 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM302_305_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 371 | P_GUESTROOM306_308_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM309_312_10233_0_10132 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 372 | W_GUESTROOM306_308_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 24.11 | 35.12 | 24.11 | 0.00 | 90.00 | 12.80 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 373 | W_GUESTROOM306_308_5_0_0_0_0 | Window | W_GUESTROOM306_308_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 374 | W_GUESTROOM306_308_5_0_0_0_1 | Window | W_GUESTROOM306_308_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.41 | 3.41 | 3.41 | 0.00 | 90.00 | 2.36 | 1.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 375 | W_GUESTROOM306_308_5_0_0_0_2 | Window | W_GUESTROOM306_308_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 376 | F_GUESTROOM306_308_10136_0_10086 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 105.36 | 105.36 | 105.36 | 180.00 | 180.00 | 12.80 | 8.23 | 0.00 | C_GUESTROOM206_208_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 377 | C_GUESTROOM306_308_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 105.36 | 105.36 | 105.36 | 0.00 | 0.00 | 12.80 | 8.23 | 0.00 | F_GUESTROOM406_408_10232_0_10131 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 378 | P_GUESTROOM309_312_10215_0_10122 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_CORRIDORFLR3_19_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 379 | P_GUESTROOM309_312_10233_0_10132 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM306_308_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 380 | P_GUESTROOM309_312_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM313_10238_0_10134 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 381 | W_GUESTROOM309_312_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 28.27 | 43.48 | 28.27 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 382 | W_GUESTROOM309_312_5_0_0_0_0 | Window | W_GUESTROOM309_312_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 383 | W_GUESTROOM309_312_5_0_0_0_1 | Window | W_GUESTROOM309_312_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 384 | W_GUESTROOM309_312_5_0_0_0_2 | Window | W_GUESTROOM309_312_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 385 | W_GUESTROOM309_312_5_0_0_0_3 | Window | W_GUESTROOM309_312_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 386 | F_GUESTROOM309_312_10144_0_10088 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 130.45 | 130.45 | 130.45 | 180.00 | 180.00 | 15.85 | 8.23 | 0.00 | C_GUESTROOM209_212_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 387 | C_GUESTROOM309_312_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 130.45 | 130.45 | 130.45 | 0.00 | 0.00 | 15.85 | 8.23 | 0.00 | F_GUESTROOM409_412_10237_0_10133 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 388 | P_GUESTROOM313_10216_0_10123 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_CORRIDORFLR3_20_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 389 | P_GUESTROOM313_10221_0_10126 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_REARSTORAGEFLR3_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 390 | P_GUESTROOM313_10238_0_10134 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM309_312_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 391 | W_GUESTROOM313_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 7.07 | 10.87 | 7.07 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 392 | W_GUESTROOM313_5_0_0_0_0 | Window | W_GUESTROOM313_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 393 | F_GUESTROOM313_10149_0_10090 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_GUESTROOM213_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 394 | C_GUESTROOM313_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM413_10242_0_10135 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 395 | P_GUESTROOM314_10197_0_10106 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_REARSTAIRSFLR3_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 396 | P_GUESTROOM314_10202_0_10109 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_CORRIDORFLR3_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 397 | W_GUESTROOM314_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 7.07 | 10.87 | 7.07 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 398 | W_GUESTROOM314_3_0_0_0_0 | Window | W_GUESTROOM314_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 399 | P_GUESTROOM314_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM315_318_10249_0_10137 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 400 | F_GUESTROOM314_10154_0_10091 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_GUESTROOM214_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 401 | C_GUESTROOM314_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM414_10247_0_10136 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 402 | P_GUESTROOM315_318_10203_0_10110 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_CORRIDORFLR3_5_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 403 | P_GUESTROOM315_318_10249_0_10137 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM314_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 404 | W_GUESTROOM315_318_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 28.27 | 43.48 | 28.27 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 405 | W_GUESTROOM315_318_3_0_0_0_0 | Window | W_GUESTROOM315_318_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 406 | W_GUESTROOM315_318_3_0_0_0_1 | Window | W_GUESTROOM315_318_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 407 | W_GUESTROOM315_318_3_0_0_0_2 | Window | W_GUESTROOM315_318_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 408 | W_GUESTROOM315_318_3_0_0_0_3 | Window | W_GUESTROOM315_318_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 409 | P_GUESTROOM315_318_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM319_10254_0_10139 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 410 | F_GUESTROOM315_318_10161_0_10093 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 130.44 | 130.44 | 130.44 | 180.00 | 180.00 | 15.85 | 8.23 | 0.00 | C_GUESTROOM215_218_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 411 | C_GUESTROOM315_318_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 130.44 | 130.44 | 130.44 | 0.00 | 0.00 | 15.85 | 8.23 | 0.00 | F_GUESTROOM415_418_10252_0_10138 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 412 | P_ELEVATORCOREFLR3_10205_0_10112 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 5.02 | 5.02 | 5.02 | 0.00 | 90.00 | 1.83 | 2.74 | 0.00 | P_CORRIDORFLR3_7_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 413 | P_ELEVATORCOREFLR3_10206_0_10113 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_CORRIDORFLR3_8_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 414 | P_ELEVATORCOREFLR3_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM319_10258_0_10141 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 415 | W_ELEVATORCOREFLR3_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 5.02 | 5.02 | 5.02 | 180.00 | 90.00 | 1.83 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 416 | F_ELEVATORCOREFLR3_10166_0_10095 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 15.05 | 15.05 | 15.05 | 180.00 | 180.00 | 1.83 | 8.23 | 0.00 | C_ELEVATORCOREFLR2_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 417 | C_ELEVATORCOREFLR3_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 15.05 | 15.05 | 15.05 | 0.00 | 0.00 | 1.83 | 8.23 | 0.00 | F_ELEVATORCOREFLR4_10257_0_10140 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 418 | P_GUESTROOM319_10204_0_10111 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_CORRIDORFLR3_6_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 419 | P_GUESTROOM319_10254_0_10139 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM315_318_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 420 | P_GUESTROOM319_10258_0_10141 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_ELEVATORCOREFLR3_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 421 | W_GUESTROOM319_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 7.07 | 10.87 | 7.07 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 422 | W_GUESTROOM319_3_0_0_0_0 | Window | W_GUESTROOM319_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 423 | F_GUESTROOM319_10171_0_10097 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_GUESTROOM219_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 424 | C_GUESTROOM319_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM419_10262_0_10142 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 425 | P_GUESTROOM320_323_10207_0_10114 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_CORRIDORFLR3_10_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 426 | P_GUESTROOM320_323_10208_0_10115 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_CORRIDORFLR3_11_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 427 | W_GUESTROOM320_323_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 28.27 | 43.48 | 28.27 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 428 | W_GUESTROOM320_323_3_0_0_0_0 | Window | W_GUESTROOM320_323_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 429 | W_GUESTROOM320_323_3_0_0_0_1 | Window | W_GUESTROOM320_323_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 430 | W_GUESTROOM320_323_3_0_0_0_2 | Window | W_GUESTROOM320_323_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 431 | W_GUESTROOM320_323_3_0_0_0_3 | Window | W_GUESTROOM320_323_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 432 | P_GUESTROOM320_323_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM324_10269_0_10144 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 433 | F_GUESTROOM320_323_10177_0_10098 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 130.44 | 130.44 | 130.44 | 180.00 | 180.00 | 15.85 | 8.23 | 0.00 | C_GUESTROOM220_223_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 434 | C_GUESTROOM320_323_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 130.44 | 130.44 | 130.44 | 0.00 | 0.00 | 15.85 | 8.23 | 0.00 | F_GUESTROOM420_423_10267_0_10143 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 435 | P_GUESTROOM324_10209_0_10116 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_CORRIDORFLR3_12_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 436 | P_GUESTROOM324_10269_0_10144 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM320_323_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 437 | W_GUESTROOM324_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 7.07 | 10.87 | 7.07 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 438 | W_GUESTROOM324_3_0_0_0_0 | Window | W_GUESTROOM324_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 439 | P_GUESTROOM324_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_FRONTSTORAGEFLR3_10274_0_10146 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 440 | F_GUESTROOM324_10182_0_10100 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_GUESTROOM224_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 441 | C_GUESTROOM324_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | F_GUESTROOM424_10272_0_10145 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 442 | P_FRONTSTORAGEFLR3_10210_0_10117 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 4.18 | 4.18 | 4.18 | 0.00 | 90.00 | 1.52 | 2.74 | 0.00 | P_CORRIDORFLR3_13_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 443 | P_FRONTSTORAGEFLR3_10274_0_10146 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM324_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 444 | W_FRONTSTORAGEFLR3_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 4.18 | 4.18 | 4.18 | 180.00 | 90.00 | 1.52 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 445 | P_FRONTSTORAGEFLR3_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_FRONTSTAIRSFLR3_10279_0_10148 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 446 | F_FRONTSTORAGEFLR3_10187_0_10102 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 12.54 | 12.54 | 12.54 | 180.00 | 180.00 | 1.52 | 8.23 | 0.00 | C_FRONTSTORAGEFLR2_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 447 | C_FRONTSTORAGEFLR3_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 12.54 | 12.54 | 12.54 | 0.00 | 0.00 | 1.52 | 8.23 | 0.00 | F_FRONTSTORAGEFLR4_10277_0_10147 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 448 | P_FRONTSTAIRSFLR3_10211_0_10118 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_CORRIDORFLR3_14_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 449 | P_FRONTSTAIRSFLR3_10279_0_10148 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_FRONTSTORAGEFLR3_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 450 | W_FRONTSTAIRSFLR3_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 2.44 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 451 | W_FRONTSTAIRSFLR3_4_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 0.514 | 0.477 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 452 | F_FRONTSTAIRSFLR3_10192_0_10104 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 20.07 | 20.07 | 20.07 | 180.00 | 180.00 | 2.44 | 8.23 | 0.00 | C_FRONTSTAIRSFLR2_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 453 | C_FRONTSTAIRSFLR3_1_0_0 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 20.07 | 20.07 | 20.07 | 0.00 | 0.00 | 2.44 | 8.23 | 0.00 | F_FRONTSTAIRSFLR4_10282_0_10149 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 454 | W_REARSTAIRSFLR4_2_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 455 | W_REARSTAIRSFLR4_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 2.44 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 456 | P_REARSTAIRSFLR4_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM414_10286_0_10150 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 457 | P_REARSTAIRSFLR4_5_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_CORRIDORFLR4_10287_0_10151 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 458 | F_REARSTAIRSFLR4_10196_0_10105 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 20.07 | 20.07 | 20.07 | 180.00 | 180.00 | 2.44 | 8.23 | 0.00 | C_REARSTAIRSFLR3_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 459 | R_REARSTAIRSFLR4_1_0_0 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 20.07 | 20.07 | 20.07 | 0.00 | 0.00 | 2.44 | 8.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 460 | P_CORRIDORFLR4_10287_0_10151 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_REARSTAIRSFLR4_5_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 461 | W_CORRIDORFLR4_2_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 3.71 | 5.02 | 3.71 | 270.00 | 90.00 | 1.83 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 462 | W_CORRIDORFLR4_2_0_0_0_0 | Window | W_CORRIDORFLR4_2_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.31 | 1.31 | 1.31 | 270.00 | 90.00 | 0.92 | 1.42 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 463 | P_CORRIDORFLR4_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_GUESTROOM414_10290_0_10152 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 464 | P_CORRIDORFLR4_5_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_GUESTROOM415_418_10291_0_10153 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 465 | P_CORRIDORFLR4_6_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_GUESTROOM419_10292_0_10154 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 466 | P_CORRIDORFLR4_7_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 5.02 | 5.02 | 5.02 | 180.00 | 90.00 | 1.83 | 2.74 | 0.00 | P_ELEVATORCOREFLR4_10293_0_10155 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 467 | P_CORRIDORFLR4_8_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_ELEVATORCOREFLR4_10294_0_10156 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 468 | W_CORRIDORFLR4_9_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 8.36 | 8.36 | 8.36 | 180.00 | 90.00 | 3.05 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 469 | P_CORRIDORFLR4_10_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM420_423_10295_0_10157 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 470 | P_CORRIDORFLR4_11_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_GUESTROOM420_423_10296_0_10158 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 471 | P_CORRIDORFLR4_12_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_GUESTROOM424_10297_0_10159 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 472 | P_CORRIDORFLR4_13_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 4.18 | 4.18 | 4.18 | 180.00 | 90.00 | 1.52 | 2.74 | 0.00 | P_FRONTSTORAGEFLR4_10298_0_10160 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 473 | P_CORRIDORFLR4_14_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_FRONTSTAIRSFLR4_10299_0_10161 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 474 | W_CORRIDORFLR4_15_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 3.71 | 5.02 | 3.71 | 90.00 | 90.00 | 1.83 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 475 | W_CORRIDORFLR4_15_0_0_0_0 | Window | W_CORRIDORFLR4_15_0_0 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 1.31 | 1.31 | 1.31 | 90.00 | 90.00 | 0.92 | 1.42 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 476 | P_CORRIDORFLR4_16_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_GUESTROOM401_10300_0_10162 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 477 | P_CORRIDORFLR4_17_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_GUESTROOM402_405_10301_0_10163 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 478 | P_CORRIDORFLR4_18_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.12 | 35.12 | 35.12 | 0.00 | 90.00 | 12.80 | 2.74 | 0.00 | P_GUESTROOM406_408_10302_0_10164 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 479 | P_CORRIDORFLR4_19_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_GUESTROOM409_412_10303_0_10165 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 480 | P_CORRIDORFLR4_20_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_GUESTROOM413_10304_0_10166 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 481 | P_CORRIDORFLR4_21_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_REARSTORAGEFLR4_10305_0_10167 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 482 | F_CORRIDORFLR4_10200_0_10108 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 125.42 | 125.42 | 125.42 | 180.00 | 180.00 | 11.20 | 11.20 | 0.00 | C_CORRIDORFLR3_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 8 | ||
| 483 | R_CORRIDORFLR4_1_0_0 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 125.42 | 125.42 | 125.42 | 0.00 | 0.00 | 11.20 | 11.20 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 8 | ||
| 484 | P_REARSTORAGEFLR4_10305_0_10167 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_CORRIDORFLR4_21_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 485 | W_REARSTORAGEFLR4_2_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 486 | P_REARSTORAGEFLR4_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM413_10308_0_10168 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 487 | W_REARSTORAGEFLR4_5_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 2.44 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 488 | F_REARSTORAGEFLR4_10219_0_10125 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 20.07 | 20.07 | 20.07 | 180.00 | 180.00 | 2.44 | 8.23 | 0.00 | C_REARSTORAGEFLR3_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 489 | R_REARSTORAGEFLR4_1_0_0 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 20.07 | 20.07 | 20.07 | 0.00 | 0.00 | 2.44 | 8.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 490 | P_GUESTROOM401_10300_0_10162 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_CORRIDORFLR4_16_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 491 | P_GUESTROOM401_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM402_405_10310_0_10169 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 492 | W_GUESTROOM401_4_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 493 | W_GUESTROOM401_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 7.07 | 10.87 | 7.07 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 494 | W_GUESTROOM401_5_0_0_0_0 | Window | W_GUESTROOM401_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 495 | F_GUESTROOM401_10223_0_10127 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_GUESTROOM301_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 496 | R_GUESTROOM401_1_0_0 | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 497 | P_GUESTROOM402_405_10301_0_10163 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_CORRIDORFLR4_17_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 498 | P_GUESTROOM402_405_10310_0_10169 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM401_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 499 | P_GUESTROOM402_405_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM406_408_10313_0_10170 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 500 | W_GUESTROOM402_405_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 28.27 | 43.48 | 28.27 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 501 | W_GUESTROOM402_405_5_0_0_0_0 | Window | W_GUESTROOM402_405_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 502 | W_GUESTROOM402_405_5_0_0_0_1 | Window | W_GUESTROOM402_405_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 503 | W_GUESTROOM402_405_5_0_0_0_2 | Window | W_GUESTROOM402_405_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 504 | W_GUESTROOM402_405_5_0_0_0_3 | Window | W_GUESTROOM402_405_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 505 | F_GUESTROOM402_405_10227_0_10129 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 130.45 | 130.45 | 130.45 | 180.00 | 180.00 | 15.85 | 8.23 | 0.00 | C_GUESTROOM302_305_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 506 | R_GUESTROOM402_405_1_0_0 | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 130.45 | 130.45 | 130.45 | 0.00 | 0.00 | 15.85 | 8.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 507 | P_GUESTROOM406_408_10302_0_10164 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 35.12 | 35.12 | 35.12 | 180.00 | 90.00 | 12.80 | 2.74 | 0.00 | P_CORRIDORFLR4_18_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 508 | P_GUESTROOM406_408_10313_0_10170 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM402_405_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 509 | P_GUESTROOM406_408_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM409_412_10317_0_10171 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 510 | W_GUESTROOM406_408_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 24.11 | 35.12 | 24.11 | 0.00 | 90.00 | 12.80 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 511 | W_GUESTROOM406_408_5_0_0_0_0 | Window | W_GUESTROOM406_408_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 512 | W_GUESTROOM406_408_5_0_0_0_1 | Window | W_GUESTROOM406_408_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 513 | W_GUESTROOM406_408_5_0_0_0_2 | Window | W_GUESTROOM406_408_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.41 | 3.41 | 3.41 | 0.00 | 90.00 | 2.36 | 1.44 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 514 | F_GUESTROOM406_408_10232_0_10131 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 105.36 | 105.36 | 105.36 | 180.00 | 180.00 | 12.80 | 8.23 | 0.00 | C_GUESTROOM306_308_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 515 | R_GUESTROOM406_408_1_0_0 | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 105.36 | 105.36 | 105.36 | 0.00 | 0.00 | 12.80 | 8.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 516 | P_GUESTROOM409_412_10303_0_10165 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_CORRIDORFLR4_19_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 517 | P_GUESTROOM409_412_10317_0_10171 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM406_408_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 518 | P_GUESTROOM409_412_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM413_10321_0_10172 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 519 | W_GUESTROOM409_412_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 28.27 | 43.48 | 28.27 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 520 | W_GUESTROOM409_412_5_0_0_0_0 | Window | W_GUESTROOM409_412_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 521 | W_GUESTROOM409_412_5_0_0_0_1 | Window | W_GUESTROOM409_412_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 522 | W_GUESTROOM409_412_5_0_0_0_2 | Window | W_GUESTROOM409_412_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 523 | W_GUESTROOM409_412_5_0_0_0_3 | Window | W_GUESTROOM409_412_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 524 | F_GUESTROOM409_412_10237_0_10133 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 130.45 | 130.45 | 130.45 | 180.00 | 180.00 | 15.85 | 8.23 | 0.00 | C_GUESTROOM309_312_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 525 | R_GUESTROOM409_412_1_0_0 | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 130.45 | 130.45 | 130.45 | 0.00 | 0.00 | 15.85 | 8.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 526 | P_GUESTROOM413_10304_0_10166 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_CORRIDORFLR4_20_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 527 | P_GUESTROOM413_10308_0_10168 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_REARSTORAGEFLR4_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 528 | P_GUESTROOM413_10321_0_10172 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM409_412_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 529 | W_GUESTROOM413_5_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 7.07 | 10.87 | 7.07 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 530 | W_GUESTROOM413_5_0_0_0_0 | Window | W_GUESTROOM413_5_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 0.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 531 | F_GUESTROOM413_10242_0_10135 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_GUESTROOM313_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 532 | R_GUESTROOM413_1_0_0 | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 533 | P_GUESTROOM414_10286_0_10150 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_REARSTAIRSFLR4_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 534 | P_GUESTROOM414_10290_0_10152 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_CORRIDORFLR4_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 535 | W_GUESTROOM414_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 7.07 | 10.87 | 7.07 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 536 | W_GUESTROOM414_3_0_0_0_0 | Window | W_GUESTROOM414_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 537 | P_GUESTROOM414_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM415_418_10330_0_10173 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 538 | F_GUESTROOM414_10247_0_10136 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_GUESTROOM314_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 539 | R_GUESTROOM414_1_0_0 | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 540 | P_GUESTROOM415_418_10291_0_10153 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_CORRIDORFLR4_5_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 541 | P_GUESTROOM415_418_10330_0_10173 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM414_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 542 | W_GUESTROOM415_418_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 28.27 | 43.48 | 28.27 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 543 | W_GUESTROOM415_418_3_0_0_0_0 | Window | W_GUESTROOM415_418_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 544 | W_GUESTROOM415_418_3_0_0_0_1 | Window | W_GUESTROOM415_418_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 545 | W_GUESTROOM415_418_3_0_0_0_2 | Window | W_GUESTROOM415_418_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 546 | W_GUESTROOM415_418_3_0_0_0_3 | Window | W_GUESTROOM415_418_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 547 | P_GUESTROOM415_418_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM419_10334_0_10174 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 548 | F_GUESTROOM415_418_10252_0_10138 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 130.44 | 130.44 | 130.44 | 180.00 | 180.00 | 15.85 | 8.23 | 0.00 | C_GUESTROOM315_318_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 549 | R_GUESTROOM415_418_1_0_0 | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 130.44 | 130.44 | 130.44 | 0.00 | 0.00 | 15.85 | 8.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 550 | P_ELEVATORCOREFLR4_10293_0_10155 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 5.02 | 5.02 | 5.02 | 0.00 | 90.00 | 1.83 | 2.74 | 0.00 | P_CORRIDORFLR4_7_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 551 | P_ELEVATORCOREFLR4_10294_0_10156 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_CORRIDORFLR4_8_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 552 | P_ELEVATORCOREFLR4_2_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM419_10337_0_10175 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 553 | W_ELEVATORCOREFLR4_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 5.02 | 5.02 | 5.02 | 180.00 | 90.00 | 1.83 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 554 | F_ELEVATORCOREFLR4_10257_0_10140 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 15.05 | 15.05 | 15.05 | 180.00 | 180.00 | 1.83 | 8.23 | 0.00 | C_ELEVATORCOREFLR3_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 555 | R_ELEVATORCOREFLR4_1_0_0 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 15.05 | 15.05 | 15.05 | 0.00 | 0.00 | 1.83 | 8.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 556 | P_GUESTROOM419_10292_0_10154 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_CORRIDORFLR4_6_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 557 | P_GUESTROOM419_10334_0_10174 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM415_418_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 558 | P_GUESTROOM419_10337_0_10175 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_ELEVATORCOREFLR4_2_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 559 | W_GUESTROOM419_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 7.07 | 10.87 | 7.07 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 560 | W_GUESTROOM419_3_0_0_0_0 | Window | W_GUESTROOM419_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 561 | F_GUESTROOM419_10262_0_10142 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_GUESTROOM319_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 562 | R_GUESTROOM419_1_0_0 | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 563 | P_GUESTROOM420_423_10295_0_10157 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_CORRIDORFLR4_10_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 564 | P_GUESTROOM420_423_10296_0_10158 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 43.48 | 43.48 | 43.48 | 0.00 | 90.00 | 15.85 | 2.74 | 0.00 | P_CORRIDORFLR4_11_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 565 | W_GUESTROOM420_423_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_MID | 0.384 | 0.363 | 28.27 | 43.48 | 28.27 | 180.00 | 90.00 | 15.85 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 566 | W_GUESTROOM420_423_3_0_0_0_0 | Window | W_GUESTROOM420_423_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 567 | W_GUESTROOM420_423_3_0_0_0_1 | Window | W_GUESTROOM420_423_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 568 | W_GUESTROOM420_423_3_0_0_0_2 | Window | W_GUESTROOM420_423_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 569 | W_GUESTROOM420_423_3_0_0_0_3 | Window | W_GUESTROOM420_423_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 570 | P_GUESTROOM420_423_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM424_10346_0_10176 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 571 | F_GUESTROOM420_423_10267_0_10143 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 130.44 | 130.44 | 130.44 | 180.00 | 180.00 | 15.85 | 8.23 | 0.00 | C_GUESTROOM320_323_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 572 | R_GUESTROOM420_423_1_0_0 | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 130.44 | 130.44 | 130.44 | 0.00 | 0.00 | 15.85 | 8.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 573 | P_GUESTROOM424_10297_0_10159 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 10.87 | 10.87 | 10.87 | 0.00 | 90.00 | 3.96 | 2.74 | 0.00 | P_CORRIDORFLR4_12_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 574 | P_GUESTROOM424_10346_0_10176 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM420_423_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 575 | W_GUESTROOM424_3_0_0 | Wall | CTF - ConductionTransferFunction | RES_EXT_WALL_TOP | 0.384 | 0.363 | 7.07 | 10.87 | 7.07 | 180.00 | 90.00 | 3.96 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 576 | W_GUESTROOM424_3_0_0_0_0 | Window | W_GUESTROOM424_3_0_0 | Window5 Detailed Fenestration | RESWINDOW_U_0.57_SHGC_0.39 | N/A | 3.241 | No | 3.80 | 3.80 | 3.80 | 180.00 | 90.00 | 1.81 | 2.10 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 577 | P_GUESTROOM424_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_FRONTSTORAGEFLR4_10350_0_10177 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 578 | F_GUESTROOM424_10272_0_10145 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 32.61 | 32.61 | 32.61 | 180.00 | 180.00 | 3.96 | 8.23 | 0.00 | C_GUESTROOM324_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 579 | R_GUESTROOM424_1_0_0 | Roof | CTF - ConductionTransferFunction | RES_ROOF | 0.376 | 0.351 | 32.61 | 32.61 | 32.61 | 0.00 | 0.00 | 3.96 | 8.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 580 | P_FRONTSTORAGEFLR4_10298_0_10160 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 4.18 | 4.18 | 4.18 | 0.00 | 90.00 | 1.52 | 2.74 | 0.00 | P_CORRIDORFLR4_13_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 581 | P_FRONTSTORAGEFLR4_10350_0_10177 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_GUESTROOM424_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 582 | W_FRONTSTORAGEFLR4_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 4.18 | 4.18 | 4.18 | 180.00 | 90.00 | 1.52 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 583 | P_FRONTSTORAGEFLR4_4_0_0 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_FRONTSTAIRSFLR4_10354_0_10178 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 584 | F_FRONTSTORAGEFLR4_10277_0_10147 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 12.54 | 12.54 | 12.54 | 180.00 | 180.00 | 1.52 | 8.23 | 0.00 | C_FRONTSTORAGEFLR3_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 585 | R_FRONTSTORAGEFLR4_1_0_0 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 12.54 | 12.54 | 12.54 | 0.00 | 0.00 | 1.52 | 8.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 586 | P_FRONTSTAIRSFLR4_10299_0_10161 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 6.69 | 6.69 | 6.69 | 0.00 | 90.00 | 2.44 | 2.74 | 0.00 | P_CORRIDORFLR4_14_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 587 | P_FRONTSTAIRSFLR4_10354_0_10178 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 22.58 | 22.58 | 22.58 | 270.00 | 90.00 | 8.23 | 2.74 | 0.00 | P_FRONTSTORAGEFLR4_4_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 588 | W_FRONTSTAIRSFLR4_3_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 6.69 | 6.69 | 6.69 | 180.00 | 90.00 | 2.44 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 589 | W_FRONTSTAIRSFLR4_4_0_0 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 0.514 | 0.477 | 22.58 | 22.58 | 22.58 | 90.00 | 90.00 | 8.23 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 590 | F_FRONTSTAIRSFLR4_10282_0_10149 | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 20.07 | 20.07 | 20.07 | 180.00 | 180.00 | 2.44 | 8.23 | 0.00 | C_FRONTSTAIRSFLR3_1_0_0 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 591 | R_FRONTSTAIRSFLR4_1_0_0 | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.376 | 0.351 | 20.07 | 20.07 | 20.07 | 0.00 | 0.00 | 2.44 | 8.23 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Transmittance Schedule | Min Schedule Value | Max Schedule Value | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | ENTRY CANOPY | Shading | W_CORRIDORFLR1_2_0_0 | None | 0.0 | 0.0 | 83.60 | 83.60 | 83.60 | 270.00 | 0.00 | 9.14 | 9.14 | 4 | ||||||||||||
| 2 | Mir-ENTRY CANOPY | Shading | W_CORRIDORFLR1_2_0_0 | None | 0.0 | 0.0 | 83.60 | 83.60 | 83.60 | 90.00 | 180.00 | 9.14 | 9.14 | 4 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | Yes | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEARS DAY | Holiday | InputFile | 01/02 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | REARSTAIRSFLR1 | RunPeriod: RUNPERIOD 1 | 4.3504522357E-002 | 3.3613469538E-002 | Pass | Pass | 2.8966495287E-002 | 3.8943308406E-002 | Pass | Pass |
| 2 | CORRIDORFLR1 | RunPeriod: RUNPERIOD 1 | 7.7161533961E-002 | 0.3043708803 | Pass | Pass | 2.2356250741 | 22.3039554042 | Pass | Pass |
| 3 | REARSTORAGEFLR1 | RunPeriod: RUNPERIOD 1 | 4.1366546292E-002 | 3.4073802846E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 4 | FRONTLOUNGEFLR1 | RunPeriod: RUNPERIOD 1 | 6.0519825764E-005 | 1.4287231541E-004 | Pass | Pass | 4.1747398398E-002 | 0.1640349382 | Pass | Pass |
| 5 | RESTROOMFLR1 | RunPeriod: RUNPERIOD 1 | 6.8418354609E-003 | 9.1819716532E-003 | Pass | Pass | 2.7424373676E-002 | 7.9449221583E-002 | Pass | Pass |
| 6 | MEETINGROOMFLR1 | RunPeriod: RUNPERIOD 1 | 1.6387158850E-002 | 8.8476684375E-002 | Pass | Pass | 7.0021641978E-002 | 0.1895757667 | Pass | Pass |
| 7 | MECHANICALROOMFLR1 | RunPeriod: RUNPERIOD 1 | 7.8480707972E-003 | 7.1820131716E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 8 | GUESTROOM101 | RunPeriod: RUNPERIOD 1 | 2.6188791375E-002 | 6.8587013727E-002 | Pass | Pass | 7.3678519832E-003 | 8.3938998925E-002 | Pass | Pass |
| 9 | GUESTROOM102 | RunPeriod: RUNPERIOD 1 | 2.3873839462E-002 | 6.6115933973E-002 | Pass | Pass | 7.2892519833E-003 | 8.3681978199E-002 | Pass | Pass |
| 10 | GUESTROOM103 | RunPeriod: RUNPERIOD 1 | 4.0051477107E-002 | 0.1214326668 | Pass | Pass | 0.2232865604 | 1.0499048118 | Pass | Pass |
| 11 | GUESTROOM104 | RunPeriod: RUNPERIOD 1 | 3.9513112999E-002 | 0.1157114990 | Pass | Pass | 0.2557049241 | 0.6051491222 | Pass | Pass |
| 12 | GUESTROOM105 | RunPeriod: RUNPERIOD 1 | 0.1025891662 | 0.3271653762 | Pass | Pass | 0.1084983981 | 0.2903812144 | Pass | Pass |
| 13 | EMPLOYEELOUNGEFLR1 | RunPeriod: RUNPERIOD 1 | 6.5407686551E-003 | 1.8510270685E-002 | Pass | Pass | 1.5820075413E-002 | 2.7253128737E-002 | Pass | Pass |
| 14 | LAUNDRYROOMFLR1 | RunPeriod: RUNPERIOD 1 | 0.6630330305 | 2.3418514707 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 15 | ELEVATORCOREFLR1 | RunPeriod: RUNPERIOD 1 | 0.4232185595 | 0.8225067433 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 16 | EXERCISECENTERFLR1 | RunPeriod: RUNPERIOD 1 | 5.1268779744E-003 | 2.6062591102E-002 | Pass | Pass | 5.9278931114E-002 | 0.2348599524 | Pass | Pass |
| 17 | FRONTOFFICEFLR1 | RunPeriod: RUNPERIOD 1 | 1.6599243141E-002 | 6.3764328363E-002 | Pass | Pass | 2.5255439369E-002 | 5.5939586530E-002 | Pass | Pass |
| 18 | FRONTSTAIRSFLR1 | RunPeriod: RUNPERIOD 1 | 4.1313790291E-002 | 3.1813409164E-002 | Pass | Pass | 2.7014312752E-002 | 3.5307252330E-002 | Pass | Pass |
| 19 | FRONTSTORAGEFLR1 | RunPeriod: RUNPERIOD 1 | 1.2400618707E-002 | 9.9356922087E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 20 | REARSTAIRSFLR2 | RunPeriod: RUNPERIOD 1 | 5.0098742659E-002 | 4.0112767253E-002 | Pass | Pass | 3.3697102414E-002 | 4.6577701204E-002 | Pass | Pass |
| 21 | CORRIDORFLR2 | RunPeriod: RUNPERIOD 1 | 1.1549194174E-002 | 1.2738001435E-002 | Pass | Pass | 3.0140259920E-003 | 2.8773871608E-003 | Pass | Pass |
| 22 | REARSTORAGEFLR2 | RunPeriod: RUNPERIOD 1 | 4.4270565583E-002 | 3.6506405734E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 23 | GUESTROOM201 | RunPeriod: RUNPERIOD 1 | 2.8872038736E-002 | 6.0953153985E-002 | Pass | Pass | 7.7219021966E-003 | 8.4998815272E-002 | Pass | Pass |
| 24 | GUESTROOM202_205 | RunPeriod: RUNPERIOD 1 | 4.6515336213E-002 | 0.1256271112 | Pass | Pass | 0.1372539751 | 0.3681851092 | Pass | Pass |
| 25 | GUESTROOM206_208 | RunPeriod: RUNPERIOD 1 | 5.7902834226E-002 | 0.1559994157 | Pass | Pass | 1.1724886451 | 7.5313192856 | Pass | Pass |
| 26 | GUESTROOM209_212 | RunPeriod: RUNPERIOD 1 | 7.0806266241E-002 | 0.1917847212 | Pass | Pass | 0.1850037824 | 0.9735625267 | Pass | Pass |
| 27 | GUESTROOM213 | RunPeriod: RUNPERIOD 1 | 4.5357909568E-002 | 0.1552255969 | Pass | Pass | 0.1557768266 | 0.6294006374 | Pass | Pass |
| 28 | GUESTROOM214 | RunPeriod: RUNPERIOD 1 | 6.6645956534E-002 | 0.1903641868 | Pass | Pass | 9.2351499300E-002 | 0.2722687005 | Pass | Pass |
| 29 | GUESTROOM215_218 | RunPeriod: RUNPERIOD 1 | 3.4388295785E-003 | 1.0054587398E-002 | Pass | Pass | 6.1618430699E-002 | 0.1503014029 | Pass | Pass |
| 30 | ELEVATORCOREFLR2 | RunPeriod: RUNPERIOD 1 | 2.0382570382E-002 | 1.5278057388E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 31 | GUESTROOM219 | RunPeriod: RUNPERIOD 1 | 9.2663313403E-002 | 0.4106054981 | Pass | Pass | 2.8388162986E-002 | 7.3969647877E-002 | Pass | Pass |
| 32 | GUESTROOM220_223 | RunPeriod: RUNPERIOD 1 | 8.9512033834E-002 | 0.2414813619 | Pass | Pass | 0.2146031774 | 1.5852908635 | Pass | Pass |
| 33 | GUESTROOM224 | RunPeriod: RUNPERIOD 1 | 4.0251986925E-002 | 0.1154764151 | Pass | Pass | 0.6671541771 | 4.4673766301 | Pass | Pass |
| 34 | FRONTSTORAGEFLR2 | RunPeriod: RUNPERIOD 1 | 1.1479267288E-002 | 9.6050980774E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 35 | FRONTSTAIRSFLR2 | RunPeriod: RUNPERIOD 1 | 4.6514953310E-002 | 3.6863872297E-002 | Pass | Pass | 3.0728998097E-002 | 4.1138976356E-002 | Pass | Pass |
| 36 | REARSTAIRSFLR3 | RunPeriod: RUNPERIOD 1 | 4.9974111577E-002 | 4.0443893249E-002 | Pass | Pass | 3.3087155292E-002 | 4.5849663435E-002 | Pass | Pass |
| 37 | CORRIDORFLR3 | RunPeriod: RUNPERIOD 1 | 1.1687472988E-005 | 1.3430648482E-005 | Pass | Pass | 3.6091777424E-002 | 8.5263805492E-002 | Pass | Pass |
| 38 | REARSTORAGEFLR3 | RunPeriod: RUNPERIOD 1 | 4.5030379187E-002 | 3.5760980348E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 39 | GUESTROOM301 | RunPeriod: RUNPERIOD 1 | 2.5184354427E-002 | 4.8878951671E-002 | Pass | Pass | 9.8385113480E-003 | 8.8095815071E-002 | Pass | Pass |
| 40 | GUESTROOM302_305 | RunPeriod: RUNPERIOD 1 | 2.8436475251E-002 | 7.4157193809E-002 | Pass | Pass | 7.5977929618E-003 | 8.4995797313E-002 | Pass | Pass |
| 41 | GUESTROOM306_308 | RunPeriod: RUNPERIOD 1 | 2.7934852868E-002 | 7.5237672860E-002 | Pass | Pass | 7.5301768854E-003 | 8.4765898157E-002 | Pass | Pass |
| 42 | GUESTROOM309_312 | RunPeriod: RUNPERIOD 1 | 5.0791752731E-002 | 0.1373355851 | Pass | Pass | 0.3345368636 | 1.3173805783 | Pass | Pass |
| 43 | GUESTROOM313 | RunPeriod: RUNPERIOD 1 | 1.9979930185E-002 | 5.4639870306E-002 | Pass | Pass | 7.8352844263E-003 | 8.5139628923E-002 | Pass | Pass |
| 44 | GUESTROOM314 | RunPeriod: RUNPERIOD 1 | 3.9235716453E-002 | 0.1176572917 | Pass | Pass | 0.1334112189 | 0.4144664392 | Pass | Pass |
| 45 | GUESTROOM315_318 | RunPeriod: RUNPERIOD 1 | 0.1112447439 | 0.3060753730 | Pass | Pass | 0.1068657897 | 0.3939482794 | Pass | Pass |
| 46 | ELEVATORCOREFLR3 | RunPeriod: RUNPERIOD 1 | 1.7171863595E-002 | 1.2297481922E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 47 | GUESTROOM319 | RunPeriod: RUNPERIOD 1 | 2.7254444080E-002 | 7.2028247750E-002 | Pass | Pass | 7.8956363084E-003 | 8.4994388655E-002 | Pass | Pass |
| 48 | GUESTROOM320_323 | RunPeriod: RUNPERIOD 1 | 6.2086905887E-002 | 0.1741811432 | Pass | Pass | 0.1691485866 | 0.5434555733 | Pass | Pass |
| 49 | GUESTROOM324 | RunPeriod: RUNPERIOD 1 | 2.4888905556E-002 | 6.7633437049E-002 | Pass | Pass | 7.5991182740E-003 | 8.4363016950E-002 | Pass | Pass |
| 50 | FRONTSTORAGEFLR3 | RunPeriod: RUNPERIOD 1 | 1.3078777714E-002 | 1.0041089306E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 51 | FRONTSTAIRSFLR3 | RunPeriod: RUNPERIOD 1 | 4.7981855245E-002 | 3.7419599620E-002 | Pass | Pass | 3.1356867006E-002 | 4.1174896959E-002 | Pass | Pass |
| 52 | REARSTAIRSFLR4 | RunPeriod: RUNPERIOD 1 | 5.2048195159E-002 | 3.7690422756E-002 | Pass | Pass | 3.3140001477E-002 | 4.0010954092E-002 | Pass | Pass |
| 53 | CORRIDORFLR4 | RunPeriod: RUNPERIOD 1 | 6.7133554167E-005 | 8.7591662724E-005 | Pass | Pass | 1.1687590058E-002 | 1.6733063003E-002 | Pass | Pass |
| 54 | REARSTORAGEFLR4 | RunPeriod: RUNPERIOD 1 | 4.7411775240E-002 | 3.4758108901E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 55 | GUESTROOM401 | RunPeriod: RUNPERIOD 1 | 9.1446909622E-002 | 0.3253280559 | Pass | Pass | 6.9991489170E-002 | 0.1629192312 | Pass | Pass |
| 56 | GUESTROOM402_405 | RunPeriod: RUNPERIOD 1 | 4.1281313610E-003 | 1.8932561961E-002 | Pass | Pass | 0.1287706411 | 0.7230009118 | Pass | Pass |
| 57 | GUESTROOM406_408 | RunPeriod: RUNPERIOD 1 | 1.1158238755E-002 | 4.0302324461E-002 | Pass | Pass | 0.1018414171 | 0.4932704382 | Pass | Pass |
| 58 | GUESTROOM409_412 | RunPeriod: RUNPERIOD 1 | 5.0233598197E-002 | 0.1822558677 | Pass | Pass | 0.2953591351 | 1.6000101152 | Pass | Pass |
| 59 | GUESTROOM413 | RunPeriod: RUNPERIOD 1 | 4.2400572396E-003 | 1.8441635037E-002 | Pass | Pass | 0.1081164820 | 0.3439492398 | Pass | Pass |
| 60 | GUESTROOM414 | RunPeriod: RUNPERIOD 1 | 3.0136942291E-002 | 5.0273629744E-002 | Pass | Pass | 8.3546585467E-003 | 8.6347976269E-002 | Pass | Pass |
| 61 | GUESTROOM415_418 | RunPeriod: RUNPERIOD 1 | 4.7387646796E-002 | 0.1260752406 | Pass | Pass | 0.5850804029 | 4.3619567917 | Pass | Pass |
| 62 | ELEVATORCOREFLR4 | RunPeriod: RUNPERIOD 1 | 1.6731902358E-002 | 1.2535167446E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 63 | GUESTROOM419 | RunPeriod: RUNPERIOD 1 | 3.9132592935E-002 | 0.1121067245 | Pass | Pass | 0.1232932305 | 0.3131245021 | Pass | Pass |
| 64 | GUESTROOM420_423 | RunPeriod: RUNPERIOD 1 | 4.8527917708E-002 | 0.1407893151 | Pass | Pass | 0.1222766839 | 0.2967270291 | Pass | Pass |
| 65 | GUESTROOM424 | RunPeriod: RUNPERIOD 1 | 5.7531327771E-002 | 0.2180266760 | Pass | Pass | 0.1177011292 | 0.3268673126 | Pass | Pass |
| 66 | FRONTSTORAGEFLR4 | RunPeriod: RUNPERIOD 1 | 1.5577668916E-002 | 1.1965538086E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
| 67 | FRONTSTAIRSFLR4 | RunPeriod: RUNPERIOD 1 | 4.7953914514E-002 | 3.5629578046E-002 | Pass | Pass | 3.0537050546E-002 | 3.6284572913E-002 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 2943.07 | 270.19 | 0.00 | 0.00 | 1434.04 | 4647.31 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
| BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 0.00 | 0 | |||
| Feb | 0.00 | 0 | |||
| Mar | 0.00 | 0 | |||
| Apr | 0.00 | 0 | |||
| May | 44.00 | 33 | |||
| Jun | 0.00 | 0 | |||
| Jul | 0.00 | 0 | |||
| Aug | 0.00 | 0 | |||
| Sep | 67.00 | 33 | |||
| Oct | 0.00 | 0 | |||
| Nov | 0.00 | 0 | |||
| Dec | 0.00 | 0 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| W_REARSTAIRSFLR1_2_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| W_REARSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 8.18 | 6.23 | 180.00 | 90.00 | S |
| S_REARSTAIRSFLR1_0_0_0 | S_REARSTAIRSFLR1_0_0_0_FFACTOR | 1.00 | 0.668 | 0.750 | 20.07 | 20.07 | 180.00 | 180.00 | |
| W_CORRIDORFLR1_2_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 6.13 | 3.44 | 270.00 | 90.00 | W |
| W_CORRIDORFLR1_10_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 10.22 | 8.27 | 180.00 | 90.00 | S |
| W_CORRIDORFLR1_16_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 6.13 | 1.69 | 90.00 | 90.00 | E |
| W_CORRIDORFLR1_20_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 10.22 | 7.53 | 0.00 | 90.00 | N |
| S_CORRIDORFLR1_0_0_0 | S_CORRIDORFLR1_0_0_0_FFACTOR | 1.00 | 0.082 | 0.083 | 150.51 | 150.51 | 180.00 | 180.00 | |
| W_REARSTORAGEFLR1_2_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| W_REARSTORAGEFLR1_5_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 8.18 | 8.18 | 0.00 | 90.00 | N |
| S_REARSTORAGEFLR1_0_0_0 | S_REARSTORAGEFLR1_0_0_0_FFACTOR | 1.00 | 0.668 | 0.750 | 20.07 | 20.07 | 180.00 | 180.00 | |
| W_FRONTLOUNGEFLR1_4_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| W_FRONTLOUNGEFLR1_5_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 66.43 | 51.60 | 0.00 | 90.00 | N |
| S_FRONTLOUNGEFLR1_0_0_0 | S_FRONTLOUNGEFLR1_0_0_0_FFACTOR | 1.00 | 0.217 | 0.225 | 163.06 | 163.06 | 180.00 | 180.00 | |
| W_RESTROOMFLR1_5_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 13.29 | 13.29 | 0.00 | 90.00 | N |
| S_RESTROOMFLR1_0_0_0 | S_RESTROOMFLR1_0_0_0_FFACTOR | 1.00 | 0.153 | 0.157 | 32.61 | 32.61 | 180.00 | 180.00 | |
| W_MEETINGROOMFLR1_5_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 32.70 | 21.31 | 0.00 | 90.00 | N |
| S_MEETINGROOMFLR1_0_0_0 | S_MEETINGROOMFLR1_0_0_0_FFACTOR | 1.00 | 0.153 | 0.157 | 80.27 | 80.27 | 180.00 | 180.00 | |
| W_MECHANICALROOMFLR1_5_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 13.29 | 13.29 | 0.00 | 90.00 | N |
| S_MECHANICALROOMFLR1_0_0_0 | S_MECHANICALROOMFLR1_0_0_0_FFACTOR | 1.00 | 0.153 | 0.157 | 32.61 | 32.61 | 180.00 | 180.00 | |
| W_GUESTROOM101_5_0_0 | RES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 13.29 | 9.49 | 0.00 | 90.00 | N |
| S_GUESTROOM101_0_0_0 | S_GUESTROOM101_0_0_0_FFACTOR | 1.00 | 0.153 | 0.157 | 32.61 | 32.61 | 180.00 | 180.00 | |
| W_GUESTROOM102_5_0_0 | RES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 13.29 | 9.49 | 0.00 | 90.00 | N |
| S_GUESTROOM102_0_0_0 | S_GUESTROOM102_0_0_0_FFACTOR | 1.00 | 0.153 | 0.157 | 32.61 | 32.61 | 180.00 | 180.00 | |
| W_GUESTROOM103_5_0_0 | RES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 13.29 | 9.49 | 0.00 | 90.00 | N |
| S_GUESTROOM103_0_0_0 | S_GUESTROOM103_0_0_0_FFACTOR | 1.00 | 0.153 | 0.157 | 32.61 | 32.61 | 180.00 | 180.00 | |
| W_GUESTROOM104_3_0_0 | RES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 13.29 | 9.49 | 180.00 | 90.00 | S |
| S_GUESTROOM104_0_0_0 | S_GUESTROOM104_0_0_0_FFACTOR | 1.00 | 0.153 | 0.157 | 32.61 | 32.61 | 180.00 | 180.00 | |
| W_GUESTROOM105_3_0_0 | RES_EXT_WALL_GRD | 0.30 | 0.363 | 0.384 | 13.29 | 9.49 | 180.00 | 90.00 | S |
| S_GUESTROOM105_0_0_0 | S_GUESTROOM105_0_0_0_FFACTOR | 1.00 | 0.153 | 0.157 | 32.61 | 32.61 | 180.00 | 180.00 | |
| W_EMPLOYEELOUNGEFLR1_3_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 13.29 | 9.49 | 180.00 | 90.00 | S |
| S_EMPLOYEELOUNGEFLR1_0_0_0 | S_EMPLOYEELOUNGEFLR1_0_0_0_FFACTOR | 1.00 | 0.153 | 0.157 | 32.61 | 32.61 | 180.00 | 180.00 | |
| W_LAUNDRYROOMFLR1_3_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 39.86 | 28.46 | 180.00 | 90.00 | S |
| S_LAUNDRYROOMFLR1_0_0_0 | S_LAUNDRYROOMFLR1_0_0_0_FFACTOR | 1.00 | 0.153 | 0.157 | 97.83 | 97.83 | 180.00 | 180.00 | |
| W_ELEVATORCOREFLR1_3_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 6.13 | 6.13 | 180.00 | 90.00 | S |
| S_ELEVATORCOREFLR1_0_0_0 | S_ELEVATORCOREFLR1_0_0_0_FFACTOR | 1.00 | 0.153 | 0.157 | 15.05 | 15.05 | 180.00 | 180.00 | |
| W_EXERCISECENTERFLR1_3_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 13.29 | 9.49 | 180.00 | 90.00 | S |
| S_EXERCISECENTERFLR1_0_0_0 | S_EXERCISECENTERFLR1_0_0_0_FFACTOR | 1.00 | 0.153 | 0.157 | 32.61 | 32.61 | 180.00 | 180.00 | |
| W_FRONTOFFICEFLR1_3_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 53.14 | 37.95 | 180.00 | 90.00 | S |
| S_FRONTOFFICEFLR1_0_0_0 | S_FRONTOFFICEFLR1_0_0_0_FFACTOR | 1.00 | 0.153 | 0.157 | 130.44 | 130.44 | 180.00 | 180.00 | |
| W_FRONTSTAIRSFLR1_3_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 8.18 | 6.22 | 180.00 | 90.00 | S |
| W_FRONTSTAIRSFLR1_4_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| S_FRONTSTAIRSFLR1_0_0_0 | S_FRONTSTAIRSFLR1_0_0_0_FFACTOR | 1.00 | 0.669 | 0.750 | 20.07 | 20.07 | 180.00 | 180.00 | |
| W_FRONTSTORAGEFLR1_3_0_0 | NONRES_EXT_WALL_GRD | 0.30 | 0.477 | 0.514 | 5.11 | 5.11 | 180.00 | 90.00 | S |
| S_FRONTSTORAGEFLR1_0_0_0 | S_FRONTSTORAGEFLR1_0_0_0_FFACTOR | 1.00 | 0.153 | 0.157 | 12.54 | 12.54 | 180.00 | 180.00 | |
| W_REARSTAIRSFLR2_2_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| W_REARSTAIRSFLR2_3_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 6.69 | 6.69 | 180.00 | 90.00 | S |
| W_CORRIDORFLR2_2_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 5.02 | 3.71 | 270.00 | 90.00 | W |
| W_CORRIDORFLR2_9_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 8.36 | 8.36 | 180.00 | 90.00 | S |
| W_CORRIDORFLR2_15_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 5.02 | 3.71 | 90.00 | 90.00 | E |
| W_REARSTORAGEFLR2_2_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| W_REARSTORAGEFLR2_5_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 6.69 | 6.69 | 0.00 | 90.00 | N |
| W_GUESTROOM201_4_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| W_GUESTROOM201_5_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 10.87 | 7.06 | 0.00 | 90.00 | N |
| W_GUESTROOM202_205_5_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 43.48 | 28.24 | 0.00 | 90.00 | N |
| W_GUESTROOM206_208_5_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 35.12 | 24.09 | 0.00 | 90.00 | N |
| W_GUESTROOM209_212_5_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 43.48 | 28.24 | 0.00 | 90.00 | N |
| W_GUESTROOM213_5_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 10.87 | 7.06 | 0.00 | 90.00 | N |
| W_GUESTROOM214_3_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 10.87 | 7.06 | 180.00 | 90.00 | S |
| W_GUESTROOM215_218_3_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 43.48 | 28.24 | 180.00 | 90.00 | S |
| W_ELEVATORCOREFLR2_3_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 5.02 | 5.02 | 180.00 | 90.00 | S |
| W_GUESTROOM219_3_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 10.87 | 7.06 | 180.00 | 90.00 | S |
| W_GUESTROOM220_223_3_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 43.48 | 28.24 | 180.00 | 90.00 | S |
| W_GUESTROOM224_3_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 10.87 | 7.06 | 180.00 | 90.00 | S |
| W_FRONTSTORAGEFLR2_3_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 4.18 | 4.18 | 180.00 | 90.00 | S |
| W_FRONTSTAIRSFLR2_3_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 6.69 | 6.69 | 180.00 | 90.00 | S |
| W_FRONTSTAIRSFLR2_4_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| W_REARSTAIRSFLR3_2_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| W_REARSTAIRSFLR3_3_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 6.69 | 6.69 | 180.00 | 90.00 | S |
| W_CORRIDORFLR3_2_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 5.02 | 3.71 | 270.00 | 90.00 | W |
| W_CORRIDORFLR3_9_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 8.36 | 8.36 | 180.00 | 90.00 | S |
| W_CORRIDORFLR3_15_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 5.02 | 3.71 | 90.00 | 90.00 | E |
| W_REARSTORAGEFLR3_2_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| W_REARSTORAGEFLR3_5_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 6.69 | 6.69 | 0.00 | 90.00 | N |
| W_GUESTROOM301_4_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| W_GUESTROOM301_5_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 10.87 | 7.07 | 0.00 | 90.00 | N |
| W_GUESTROOM302_305_5_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 43.48 | 28.27 | 0.00 | 90.00 | N |
| W_GUESTROOM306_308_5_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 35.12 | 24.11 | 0.00 | 90.00 | N |
| W_GUESTROOM309_312_5_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 43.48 | 28.27 | 0.00 | 90.00 | N |
| W_GUESTROOM313_5_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 10.87 | 7.07 | 0.00 | 90.00 | N |
| W_GUESTROOM314_3_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 10.87 | 7.07 | 180.00 | 90.00 | S |
| W_GUESTROOM315_318_3_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 43.48 | 28.27 | 180.00 | 90.00 | S |
| W_ELEVATORCOREFLR3_3_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 5.02 | 5.02 | 180.00 | 90.00 | S |
| W_GUESTROOM319_3_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 10.87 | 7.07 | 180.00 | 90.00 | S |
| W_GUESTROOM320_323_3_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 43.48 | 28.27 | 180.00 | 90.00 | S |
| W_GUESTROOM324_3_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 10.87 | 7.07 | 180.00 | 90.00 | S |
| W_FRONTSTORAGEFLR3_3_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 4.18 | 4.18 | 180.00 | 90.00 | S |
| W_FRONTSTAIRSFLR3_3_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 6.69 | 6.69 | 180.00 | 90.00 | S |
| W_FRONTSTAIRSFLR3_4_0_0 | NONRES_EXT_WALL_MID | 0.30 | 0.477 | 0.514 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| W_REARSTAIRSFLR4_2_0_0 | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| W_REARSTAIRSFLR4_3_0_0 | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 6.69 | 6.69 | 180.00 | 90.00 | S |
| R_REARSTAIRSFLR4_1_0_0 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 20.07 | 20.07 | 0.00 | 0.00 | |
| W_CORRIDORFLR4_2_0_0 | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 5.02 | 3.71 | 270.00 | 90.00 | W |
| W_CORRIDORFLR4_9_0_0 | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 8.36 | 8.36 | 180.00 | 90.00 | S |
| W_CORRIDORFLR4_15_0_0 | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 5.02 | 3.71 | 90.00 | 90.00 | E |
| R_CORRIDORFLR4_1_0_0 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 125.42 | 125.42 | 0.00 | 0.00 | |
| W_REARSTORAGEFLR4_2_0_0 | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| W_REARSTORAGEFLR4_5_0_0 | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 6.69 | 6.69 | 0.00 | 90.00 | N |
| R_REARSTORAGEFLR4_1_0_0 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 20.07 | 20.07 | 0.00 | 0.00 | |
| W_GUESTROOM401_4_0_0 | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| W_GUESTROOM401_5_0_0 | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 10.87 | 7.07 | 0.00 | 90.00 | N |
| R_GUESTROOM401_1_0_0 | RES_ROOF | 0.30 | 0.358 | 0.376 | 32.61 | 32.61 | 0.00 | 0.00 | |
| W_GUESTROOM402_405_5_0_0 | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 43.48 | 28.27 | 0.00 | 90.00 | N |
| R_GUESTROOM402_405_1_0_0 | RES_ROOF | 0.30 | 0.358 | 0.376 | 130.45 | 130.45 | 0.00 | 0.00 | |
| W_GUESTROOM406_408_5_0_0 | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 35.12 | 24.11 | 0.00 | 90.00 | N |
| R_GUESTROOM406_408_1_0_0 | RES_ROOF | 0.30 | 0.358 | 0.376 | 105.36 | 105.36 | 0.00 | 0.00 | |
| W_GUESTROOM409_412_5_0_0 | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 43.48 | 28.27 | 0.00 | 90.00 | N |
| R_GUESTROOM409_412_1_0_0 | RES_ROOF | 0.30 | 0.358 | 0.376 | 130.45 | 130.45 | 0.00 | 0.00 | |
| W_GUESTROOM413_5_0_0 | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 10.87 | 7.07 | 0.00 | 90.00 | N |
| R_GUESTROOM413_1_0_0 | RES_ROOF | 0.30 | 0.358 | 0.376 | 32.61 | 32.61 | 0.00 | 0.00 | |
| W_GUESTROOM414_3_0_0 | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 10.87 | 7.07 | 180.00 | 90.00 | S |
| R_GUESTROOM414_1_0_0 | RES_ROOF | 0.30 | 0.358 | 0.376 | 32.61 | 32.61 | 0.00 | 0.00 | |
| W_GUESTROOM415_418_3_0_0 | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 43.48 | 28.27 | 180.00 | 90.00 | S |
| R_GUESTROOM415_418_1_0_0 | RES_ROOF | 0.30 | 0.358 | 0.376 | 130.44 | 130.44 | 0.00 | 0.00 | |
| W_ELEVATORCOREFLR4_3_0_0 | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 5.02 | 5.02 | 180.00 | 90.00 | S |
| R_ELEVATORCOREFLR4_1_0_0 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 15.05 | 15.05 | 0.00 | 0.00 | |
| W_GUESTROOM419_3_0_0 | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 10.87 | 7.07 | 180.00 | 90.00 | S |
| R_GUESTROOM419_1_0_0 | RES_ROOF | 0.30 | 0.358 | 0.376 | 32.61 | 32.61 | 0.00 | 0.00 | |
| W_GUESTROOM420_423_3_0_0 | RES_EXT_WALL_MID | 0.30 | 0.363 | 0.384 | 43.48 | 28.27 | 180.00 | 90.00 | S |
| R_GUESTROOM420_423_1_0_0 | RES_ROOF | 0.30 | 0.358 | 0.376 | 130.44 | 130.44 | 0.00 | 0.00 | |
| W_GUESTROOM424_3_0_0 | RES_EXT_WALL_TOP | 0.30 | 0.363 | 0.384 | 10.87 | 7.07 | 180.00 | 90.00 | S |
| R_GUESTROOM424_1_0_0 | RES_ROOF | 0.30 | 0.358 | 0.376 | 32.61 | 32.61 | 0.00 | 0.00 | |
| W_FRONTSTORAGEFLR4_3_0_0 | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 4.18 | 4.18 | 180.00 | 90.00 | S |
| R_FRONTSTORAGEFLR4_1_0_0 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 12.54 | 12.54 | 0.00 | 0.00 | |
| W_FRONTSTAIRSFLR4_3_0_0 | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 6.69 | 6.69 | 180.00 | 90.00 | S |
| W_FRONTSTAIRSFLR4_4_0_0 | NONRES_EXT_WALL_TOP | 0.30 | 0.477 | 0.514 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| R_FRONTSTAIRSFLR4_1_0_0 | NONRES_ROOF | 0.30 | 0.358 | 0.376 | 20.07 | 20.07 | 0.00 | 0.00 |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| P_REARSTAIRSFLR1_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| P_REARSTAIRSFLR1_5_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 8.18 | 8.18 | 0.00 | 90.00 | N |
| C_REARSTAIRSFLR1_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 0.00 | 0.00 | |
| P_CORRIDORFLR1_10003_0_10002 | INT_WALL | 0.30 | 2.511 | 6.299 | 8.18 | 8.18 | 180.00 | 90.00 | S |
| P_CORRIDORFLR1_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 180.00 | 90.00 | S |
| P_CORRIDORFLR1_5_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 180.00 | 90.00 | S |
| P_CORRIDORFLR1_6_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 180.00 | 90.00 | S |
| P_CORRIDORFLR1_7_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 39.86 | 39.86 | 180.00 | 90.00 | S |
| P_CORRIDORFLR1_8_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.13 | 6.13 | 180.00 | 90.00 | S |
| P_CORRIDORFLR1_9_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| P_CORRIDORFLR1_11_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| P_CORRIDORFLR1_12_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 180.00 | 90.00 | S |
| P_CORRIDORFLR1_13_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 53.14 | 53.14 | 180.00 | 90.00 | S |
| P_CORRIDORFLR1_14_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 5.11 | 5.11 | 180.00 | 90.00 | S |
| P_CORRIDORFLR1_15_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 8.18 | 8.18 | 180.00 | 90.00 | S |
| P_CORRIDORFLR1_17_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 66.43 | 66.43 | 0.00 | 90.00 | N |
| P_CORRIDORFLR1_18_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 0.00 | 90.00 | N |
| P_CORRIDORFLR1_19_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| P_CORRIDORFLR1_21_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| P_CORRIDORFLR1_22_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 32.70 | 32.70 | 0.00 | 90.00 | N |
| P_CORRIDORFLR1_23_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 0.00 | 90.00 | N |
| P_CORRIDORFLR1_24_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 0.00 | 90.00 | N |
| P_CORRIDORFLR1_25_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 0.00 | 90.00 | N |
| P_CORRIDORFLR1_26_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 0.00 | 90.00 | N |
| P_CORRIDORFLR1_27_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 8.18 | 8.18 | 0.00 | 90.00 | N |
| C_CORRIDORFLR1_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 125.42 | 125.42 | 0.00 | 0.00 | |
| C_CORRIDORFLR1_1_1_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 25.09 | 25.09 | 0.00 | 0.00 | |
| P_REARSTORAGEFLR1_10027_0_10025 | INT_WALL | 0.30 | 2.511 | 6.299 | 8.18 | 8.18 | 180.00 | 90.00 | S |
| P_REARSTORAGEFLR1_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| C_REARSTORAGEFLR1_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 0.00 | 0.00 | |
| P_FRONTLOUNGEFLR1_10018_0_10016 | INT_WALL | 0.30 | 2.511 | 6.299 | 66.43 | 66.43 | 180.00 | 90.00 | S |
| P_FRONTLOUNGEFLR1_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| C_FRONTLOUNGEFLR1_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| C_FRONTLOUNGEFLR1_1_1_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 130.45 | 130.45 | 0.00 | 0.00 | |
| P_RESTROOMFLR1_10019_0_10017 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 180.00 | 90.00 | S |
| P_RESTROOMFLR1_10020_0_10018 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| P_RESTROOMFLR1_10033_0_10030 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| C_RESTROOMFLR1_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_MEETINGROOMFLR1_10021_0_10019 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| P_MEETINGROOMFLR1_10022_0_10020 | INT_WALL | 0.30 | 2.511 | 6.299 | 32.70 | 32.70 | 180.00 | 90.00 | S |
| P_MEETINGROOMFLR1_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| C_MEETINGROOMFLR1_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 47.66 | 47.66 | 0.00 | 0.00 | |
| C_MEETINGROOMFLR1_1_1_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_MECHANICALROOMFLR1_10023_0_10021 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 180.00 | 90.00 | S |
| P_MECHANICALROOMFLR1_10041_0_10034 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| P_MECHANICALROOMFLR1_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| C_MECHANICALROOMFLR1_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_GUESTROOM101_10024_0_10022 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 180.00 | 90.00 | S |
| P_GUESTROOM101_10045_0_10036 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| P_GUESTROOM101_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| C_GUESTROOM101_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_GUESTROOM102_10025_0_10023 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 180.00 | 90.00 | S |
| P_GUESTROOM102_10049_0_10038 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| P_GUESTROOM102_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| C_GUESTROOM102_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_GUESTROOM103_10026_0_10024 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 180.00 | 90.00 | S |
| P_GUESTROOM103_10030_0_10027 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| P_GUESTROOM103_10053_0_10040 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| C_GUESTROOM103_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_GUESTROOM104_10002_0_10001 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| P_GUESTROOM104_10007_0_10005 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 0.00 | 90.00 | N |
| P_GUESTROOM104_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| C_GUESTROOM104_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_GUESTROOM105_10008_0_10006 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 0.00 | 90.00 | N |
| P_GUESTROOM105_10062_0_10043 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| P_GUESTROOM105_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| C_GUESTROOM105_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_EMPLOYEELOUNGEFLR1_10009_0_10007 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 0.00 | 90.00 | N |
| P_EMPLOYEELOUNGEFLR1_10066_0_10045 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| P_EMPLOYEELOUNGEFLR1_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| C_EMPLOYEELOUNGEFLR1_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_LAUNDRYROOMFLR1_10010_0_10008 | INT_WALL | 0.30 | 2.511 | 6.299 | 39.86 | 39.86 | 0.00 | 90.00 | N |
| P_LAUNDRYROOMFLR1_10070_0_10047 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| P_LAUNDRYROOMFLR1_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| C_LAUNDRYROOMFLR1_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 65.22 | 65.22 | 0.00 | 0.00 | |
| C_LAUNDRYROOMFLR1_1_1_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_ELEVATORCOREFLR1_10011_0_10009 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.13 | 6.13 | 0.00 | 90.00 | N |
| P_ELEVATORCOREFLR1_10012_0_10010 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| P_ELEVATORCOREFLR1_10075_0_10050 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| C_ELEVATORCOREFLR1_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 15.05 | 15.05 | 0.00 | 0.00 | |
| P_EXERCISECENTERFLR1_10013_0_10011 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| P_EXERCISECENTERFLR1_10014_0_10012 | INT_WALL | 0.30 | 2.511 | 6.299 | 13.29 | 13.29 | 0.00 | 90.00 | N |
| P_EXERCISECENTERFLR1_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| C_EXERCISECENTERFLR1_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_FRONTOFFICEFLR1_10015_0_10013 | INT_WALL | 0.30 | 2.511 | 6.299 | 53.14 | 53.14 | 0.00 | 90.00 | N |
| P_FRONTOFFICEFLR1_10083_0_10053 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| P_FRONTOFFICEFLR1_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| C_FRONTOFFICEFLR1_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 97.83 | 97.83 | 0.00 | 0.00 | |
| C_FRONTOFFICEFLR1_1_1_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_FRONTSTAIRSFLR1_10017_0_10015 | INT_WALL | 0.30 | 2.511 | 6.299 | 8.18 | 8.18 | 0.00 | 90.00 | N |
| P_FRONTSTAIRSFLR1_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| C_FRONTSTAIRSFLR1_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 0.00 | 0.00 | |
| P_FRONTSTORAGEFLR1_10016_0_10014 | INT_WALL | 0.30 | 2.511 | 6.299 | 5.11 | 5.11 | 0.00 | 90.00 | N |
| P_FRONTSTORAGEFLR1_10088_0_10056 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 270.00 | 90.00 | W |
| P_FRONTSTORAGEFLR1_10091_0_10058 | INT_WALL | 0.30 | 2.511 | 6.299 | 27.59 | 27.59 | 90.00 | 90.00 | E |
| C_FRONTSTORAGEFLR1_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 12.54 | 12.54 | 0.00 | 0.00 | |
| P_REARSTAIRSFLR2_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_REARSTAIRSFLR2_5_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 0.00 | 90.00 | N |
| F_REARSTAIRSFLR2_10001_0_10000 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 180.00 | 180.00 | |
| C_REARSTAIRSFLR2_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 0.00 | 0.00 | |
| P_CORRIDORFLR2_10100_0_10062 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 180.00 | 90.00 | S |
| P_CORRIDORFLR2_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 180.00 | 90.00 | S |
| P_CORRIDORFLR2_5_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 180.00 | 90.00 | S |
| P_CORRIDORFLR2_6_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 180.00 | 90.00 | S |
| P_CORRIDORFLR2_7_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 5.02 | 5.02 | 180.00 | 90.00 | S |
| P_CORRIDORFLR2_8_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_CORRIDORFLR2_10_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_CORRIDORFLR2_11_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 180.00 | 90.00 | S |
| P_CORRIDORFLR2_12_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 180.00 | 90.00 | S |
| P_CORRIDORFLR2_13_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 4.18 | 4.18 | 180.00 | 90.00 | S |
| P_CORRIDORFLR2_14_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 180.00 | 90.00 | S |
| P_CORRIDORFLR2_16_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 0.00 | 90.00 | N |
| P_CORRIDORFLR2_17_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 0.00 | 90.00 | N |
| P_CORRIDORFLR2_18_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 35.12 | 35.12 | 0.00 | 90.00 | N |
| P_CORRIDORFLR2_19_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 0.00 | 90.00 | N |
| P_CORRIDORFLR2_20_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 0.00 | 90.00 | N |
| P_CORRIDORFLR2_21_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 0.00 | 90.00 | N |
| F_CORRIDORFLR2_10004_0_10003 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 125.42 | 125.42 | 180.00 | 180.00 | |
| C_CORRIDORFLR2_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 125.42 | 125.42 | 0.00 | 0.00 | |
| P_REARSTORAGEFLR2_10119_0_10079 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 180.00 | 90.00 | S |
| P_REARSTORAGEFLR2_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_REARSTORAGEFLR2_10028_0_10026 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 180.00 | 180.00 | |
| C_REARSTORAGEFLR2_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 0.00 | 0.00 | |
| P_GUESTROOM201_10114_0_10074 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 180.00 | 90.00 | S |
| P_GUESTROOM201_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_GUESTROOM201_10031_0_10028 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| C_GUESTROOM201_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_GUESTROOM202_205_10115_0_10075 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 180.00 | 90.00 | S |
| P_GUESTROOM202_205_10126_0_10083 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_GUESTROOM202_205_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_GUESTROOM202_205_10032_0_10029 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 130.45 | 130.45 | 180.00 | 180.00 | |
| C_GUESTROOM202_205_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 130.45 | 130.45 | 0.00 | 0.00 | |
| P_GUESTROOM206_208_10116_0_10076 | INT_WALL | 0.30 | 2.511 | 6.299 | 35.12 | 35.12 | 180.00 | 90.00 | S |
| P_GUESTROOM206_208_10130_0_10085 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_GUESTROOM206_208_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_GUESTROOM206_208_10005_0_10004 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 25.09 | 25.09 | 180.00 | 180.00 | |
| F_GUESTROOM206_208_10035_0_10031 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| F_GUESTROOM206_208_10039_0_10032 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 47.66 | 47.66 | 180.00 | 180.00 | |
| C_GUESTROOM206_208_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 105.36 | 105.36 | 0.00 | 0.00 | |
| P_GUESTROOM209_212_10117_0_10077 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 180.00 | 90.00 | S |
| P_GUESTROOM209_212_10137_0_10087 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_GUESTROOM209_212_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_GUESTROOM209_212_10040_0_10033 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| F_GUESTROOM209_212_10044_0_10035 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| F_GUESTROOM209_212_10048_0_10037 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| F_GUESTROOM209_212_10052_0_10039 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| C_GUESTROOM209_212_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 130.45 | 130.45 | 0.00 | 0.00 | |
| P_GUESTROOM213_10118_0_10078 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 180.00 | 90.00 | S |
| P_GUESTROOM213_10123_0_10081 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM213_10145_0_10089 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM213_10056_0_10041 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| C_GUESTROOM213_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_GUESTROOM214_10099_0_10061 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM214_10104_0_10064 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 0.00 | 90.00 | N |
| P_GUESTROOM214_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM214_10060_0_10042 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| C_GUESTROOM214_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_GUESTROOM215_218_10105_0_10065 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 0.00 | 90.00 | N |
| P_GUESTROOM215_218_10156_0_10092 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM215_218_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM215_218_10064_0_10044 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| F_GUESTROOM215_218_10068_0_10046 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| F_GUESTROOM215_218_10072_0_10048 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 65.22 | 65.22 | 180.00 | 180.00 | |
| C_GUESTROOM215_218_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 130.44 | 130.44 | 0.00 | 0.00 | |
| P_ELEVATORCOREFLR2_10107_0_10067 | INT_WALL | 0.30 | 2.511 | 6.299 | 5.02 | 5.02 | 0.00 | 90.00 | N |
| P_ELEVATORCOREFLR2_10108_0_10068 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_ELEVATORCOREFLR2_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_ELEVATORCOREFLR2_10077_0_10051 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 15.05 | 15.05 | 180.00 | 180.00 | |
| C_ELEVATORCOREFLR2_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 15.05 | 15.05 | 0.00 | 0.00 | |
| P_GUESTROOM219_10106_0_10066 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 0.00 | 90.00 | N |
| P_GUESTROOM219_10163_0_10094 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM219_10167_0_10096 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM219_10073_0_10049 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| C_GUESTROOM219_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_GUESTROOM220_223_10109_0_10069 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM220_223_10110_0_10070 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 0.00 | 90.00 | N |
| P_GUESTROOM220_223_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM220_223_10081_0_10052 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| F_GUESTROOM220_223_10085_0_10054 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 97.83 | 97.83 | 180.00 | 180.00 | |
| C_GUESTROOM220_223_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 130.44 | 130.44 | 0.00 | 0.00 | |
| P_GUESTROOM224_10111_0_10071 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 0.00 | 90.00 | N |
| P_GUESTROOM224_10179_0_10099 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM224_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM224_10086_0_10055 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| C_GUESTROOM224_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_FRONTSTORAGEFLR2_10112_0_10072 | INT_WALL | 0.30 | 2.511 | 6.299 | 4.18 | 4.18 | 0.00 | 90.00 | N |
| P_FRONTSTORAGEFLR2_10184_0_10101 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_FRONTSTORAGEFLR2_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_FRONTSTORAGEFLR2_10093_0_10059 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 12.54 | 12.54 | 180.00 | 180.00 | |
| C_FRONTSTORAGEFLR2_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 12.54 | 12.54 | 0.00 | 0.00 | |
| P_FRONTSTAIRSFLR2_10113_0_10073 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 0.00 | 90.00 | N |
| P_FRONTSTAIRSFLR2_10189_0_10103 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_FRONTSTAIRSFLR2_10090_0_10057 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 180.00 | 180.00 | |
| C_FRONTSTAIRSFLR2_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 0.00 | 0.00 | |
| P_REARSTAIRSFLR3_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_REARSTAIRSFLR3_5_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 0.00 | 90.00 | N |
| F_REARSTAIRSFLR3_10098_0_10060 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 180.00 | 180.00 | |
| C_REARSTAIRSFLR3_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 0.00 | 0.00 | |
| P_CORRIDORFLR3_10198_0_10107 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 180.00 | 90.00 | S |
| P_CORRIDORFLR3_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 180.00 | 90.00 | S |
| P_CORRIDORFLR3_5_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 180.00 | 90.00 | S |
| P_CORRIDORFLR3_6_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 180.00 | 90.00 | S |
| P_CORRIDORFLR3_7_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 5.02 | 5.02 | 180.00 | 90.00 | S |
| P_CORRIDORFLR3_8_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_CORRIDORFLR3_10_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_CORRIDORFLR3_11_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 180.00 | 90.00 | S |
| P_CORRIDORFLR3_12_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 180.00 | 90.00 | S |
| P_CORRIDORFLR3_13_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 4.18 | 4.18 | 180.00 | 90.00 | S |
| P_CORRIDORFLR3_14_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 180.00 | 90.00 | S |
| P_CORRIDORFLR3_16_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 0.00 | 90.00 | N |
| P_CORRIDORFLR3_17_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 0.00 | 90.00 | N |
| P_CORRIDORFLR3_18_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 35.12 | 35.12 | 0.00 | 90.00 | N |
| P_CORRIDORFLR3_19_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 0.00 | 90.00 | N |
| P_CORRIDORFLR3_20_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 0.00 | 90.00 | N |
| P_CORRIDORFLR3_21_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 0.00 | 90.00 | N |
| F_CORRIDORFLR3_10102_0_10063 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 125.42 | 125.42 | 180.00 | 180.00 | |
| C_CORRIDORFLR3_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 125.42 | 125.42 | 0.00 | 0.00 | |
| P_REARSTORAGEFLR3_10217_0_10124 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 180.00 | 90.00 | S |
| P_REARSTORAGEFLR3_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_REARSTORAGEFLR3_10121_0_10080 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 180.00 | 180.00 | |
| C_REARSTORAGEFLR3_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 0.00 | 0.00 | |
| P_GUESTROOM301_10212_0_10119 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 180.00 | 90.00 | S |
| P_GUESTROOM301_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_GUESTROOM301_10125_0_10082 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| C_GUESTROOM301_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_GUESTROOM302_305_10213_0_10120 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 180.00 | 90.00 | S |
| P_GUESTROOM302_305_10224_0_10128 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_GUESTROOM302_305_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_GUESTROOM302_305_10129_0_10084 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 130.45 | 130.45 | 180.00 | 180.00 | |
| C_GUESTROOM302_305_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 130.45 | 130.45 | 0.00 | 0.00 | |
| P_GUESTROOM306_308_10214_0_10121 | INT_WALL | 0.30 | 2.511 | 6.299 | 35.12 | 35.12 | 180.00 | 90.00 | S |
| P_GUESTROOM306_308_10228_0_10130 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_GUESTROOM306_308_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_GUESTROOM306_308_10136_0_10086 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 105.36 | 105.36 | 180.00 | 180.00 | |
| C_GUESTROOM306_308_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 105.36 | 105.36 | 0.00 | 0.00 | |
| P_GUESTROOM309_312_10215_0_10122 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 180.00 | 90.00 | S |
| P_GUESTROOM309_312_10233_0_10132 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_GUESTROOM309_312_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_GUESTROOM309_312_10144_0_10088 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 130.45 | 130.45 | 180.00 | 180.00 | |
| C_GUESTROOM309_312_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 130.45 | 130.45 | 0.00 | 0.00 | |
| P_GUESTROOM313_10216_0_10123 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 180.00 | 90.00 | S |
| P_GUESTROOM313_10221_0_10126 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM313_10238_0_10134 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM313_10149_0_10090 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| C_GUESTROOM313_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_GUESTROOM314_10197_0_10106 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM314_10202_0_10109 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 0.00 | 90.00 | N |
| P_GUESTROOM314_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM314_10154_0_10091 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| C_GUESTROOM314_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_GUESTROOM315_318_10203_0_10110 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 0.00 | 90.00 | N |
| P_GUESTROOM315_318_10249_0_10137 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM315_318_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM315_318_10161_0_10093 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 130.44 | 130.44 | 180.00 | 180.00 | |
| C_GUESTROOM315_318_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 130.44 | 130.44 | 0.00 | 0.00 | |
| P_ELEVATORCOREFLR3_10205_0_10112 | INT_WALL | 0.30 | 2.511 | 6.299 | 5.02 | 5.02 | 0.00 | 90.00 | N |
| P_ELEVATORCOREFLR3_10206_0_10113 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_ELEVATORCOREFLR3_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_ELEVATORCOREFLR3_10166_0_10095 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 15.05 | 15.05 | 180.00 | 180.00 | |
| C_ELEVATORCOREFLR3_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 15.05 | 15.05 | 0.00 | 0.00 | |
| P_GUESTROOM319_10204_0_10111 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 0.00 | 90.00 | N |
| P_GUESTROOM319_10254_0_10139 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM319_10258_0_10141 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM319_10171_0_10097 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| C_GUESTROOM319_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_GUESTROOM320_323_10207_0_10114 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM320_323_10208_0_10115 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 0.00 | 90.00 | N |
| P_GUESTROOM320_323_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM320_323_10177_0_10098 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 130.44 | 130.44 | 180.00 | 180.00 | |
| C_GUESTROOM320_323_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 130.44 | 130.44 | 0.00 | 0.00 | |
| P_GUESTROOM324_10209_0_10116 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 0.00 | 90.00 | N |
| P_GUESTROOM324_10269_0_10144 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM324_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM324_10182_0_10100 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| C_GUESTROOM324_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 0.00 | 0.00 | |
| P_FRONTSTORAGEFLR3_10210_0_10117 | INT_WALL | 0.30 | 2.511 | 6.299 | 4.18 | 4.18 | 0.00 | 90.00 | N |
| P_FRONTSTORAGEFLR3_10274_0_10146 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_FRONTSTORAGEFLR3_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_FRONTSTORAGEFLR3_10187_0_10102 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 12.54 | 12.54 | 180.00 | 180.00 | |
| C_FRONTSTORAGEFLR3_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 12.54 | 12.54 | 0.00 | 0.00 | |
| P_FRONTSTAIRSFLR3_10211_0_10118 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 0.00 | 90.00 | N |
| P_FRONTSTAIRSFLR3_10279_0_10148 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_FRONTSTAIRSFLR3_10192_0_10104 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 180.00 | 180.00 | |
| C_FRONTSTAIRSFLR3_1_0_0 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 0.00 | 0.00 | |
| P_REARSTAIRSFLR4_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_REARSTAIRSFLR4_5_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 0.00 | 90.00 | N |
| F_REARSTAIRSFLR4_10196_0_10105 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 180.00 | 180.00 | |
| P_CORRIDORFLR4_10287_0_10151 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 180.00 | 90.00 | S |
| P_CORRIDORFLR4_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 180.00 | 90.00 | S |
| P_CORRIDORFLR4_5_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 180.00 | 90.00 | S |
| P_CORRIDORFLR4_6_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 180.00 | 90.00 | S |
| P_CORRIDORFLR4_7_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 5.02 | 5.02 | 180.00 | 90.00 | S |
| P_CORRIDORFLR4_8_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_CORRIDORFLR4_10_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_CORRIDORFLR4_11_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 180.00 | 90.00 | S |
| P_CORRIDORFLR4_12_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 180.00 | 90.00 | S |
| P_CORRIDORFLR4_13_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 4.18 | 4.18 | 180.00 | 90.00 | S |
| P_CORRIDORFLR4_14_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 180.00 | 90.00 | S |
| P_CORRIDORFLR4_16_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 0.00 | 90.00 | N |
| P_CORRIDORFLR4_17_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 0.00 | 90.00 | N |
| P_CORRIDORFLR4_18_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 35.12 | 35.12 | 0.00 | 90.00 | N |
| P_CORRIDORFLR4_19_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 0.00 | 90.00 | N |
| P_CORRIDORFLR4_20_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 0.00 | 90.00 | N |
| P_CORRIDORFLR4_21_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 0.00 | 90.00 | N |
| F_CORRIDORFLR4_10200_0_10108 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 125.42 | 125.42 | 180.00 | 180.00 | |
| P_REARSTORAGEFLR4_10305_0_10167 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 180.00 | 90.00 | S |
| P_REARSTORAGEFLR4_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_REARSTORAGEFLR4_10219_0_10125 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 180.00 | 180.00 | |
| P_GUESTROOM401_10300_0_10162 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 180.00 | 90.00 | S |
| P_GUESTROOM401_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_GUESTROOM401_10223_0_10127 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| P_GUESTROOM402_405_10301_0_10163 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 180.00 | 90.00 | S |
| P_GUESTROOM402_405_10310_0_10169 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_GUESTROOM402_405_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_GUESTROOM402_405_10227_0_10129 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 130.45 | 130.45 | 180.00 | 180.00 | |
| P_GUESTROOM406_408_10302_0_10164 | INT_WALL | 0.30 | 2.511 | 6.299 | 35.12 | 35.12 | 180.00 | 90.00 | S |
| P_GUESTROOM406_408_10313_0_10170 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_GUESTROOM406_408_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_GUESTROOM406_408_10232_0_10131 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 105.36 | 105.36 | 180.00 | 180.00 | |
| P_GUESTROOM409_412_10303_0_10165 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 180.00 | 90.00 | S |
| P_GUESTROOM409_412_10317_0_10171 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_GUESTROOM409_412_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_GUESTROOM409_412_10237_0_10133 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 130.45 | 130.45 | 180.00 | 180.00 | |
| P_GUESTROOM413_10304_0_10166 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 180.00 | 90.00 | S |
| P_GUESTROOM413_10308_0_10168 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM413_10321_0_10172 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM413_10242_0_10135 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| P_GUESTROOM414_10286_0_10150 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM414_10290_0_10152 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 0.00 | 90.00 | N |
| P_GUESTROOM414_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM414_10247_0_10136 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| P_GUESTROOM415_418_10291_0_10153 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 0.00 | 90.00 | N |
| P_GUESTROOM415_418_10330_0_10173 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM415_418_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM415_418_10252_0_10138 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 130.44 | 130.44 | 180.00 | 180.00 | |
| P_ELEVATORCOREFLR4_10293_0_10155 | INT_WALL | 0.30 | 2.511 | 6.299 | 5.02 | 5.02 | 0.00 | 90.00 | N |
| P_ELEVATORCOREFLR4_10294_0_10156 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| P_ELEVATORCOREFLR4_2_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_ELEVATORCOREFLR4_10257_0_10140 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 15.05 | 15.05 | 180.00 | 180.00 | |
| P_GUESTROOM419_10292_0_10154 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 0.00 | 90.00 | N |
| P_GUESTROOM419_10334_0_10174 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM419_10337_0_10175 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM419_10262_0_10142 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| P_GUESTROOM420_423_10295_0_10157 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM420_423_10296_0_10158 | INT_WALL | 0.30 | 2.511 | 6.299 | 43.48 | 43.48 | 0.00 | 90.00 | N |
| P_GUESTROOM420_423_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM420_423_10267_0_10143 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 130.44 | 130.44 | 180.00 | 180.00 | |
| P_GUESTROOM424_10297_0_10159 | INT_WALL | 0.30 | 2.511 | 6.299 | 10.87 | 10.87 | 0.00 | 90.00 | N |
| P_GUESTROOM424_10346_0_10176 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_GUESTROOM424_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_GUESTROOM424_10272_0_10145 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 32.61 | 32.61 | 180.00 | 180.00 | |
| P_FRONTSTORAGEFLR4_10298_0_10160 | INT_WALL | 0.30 | 2.511 | 6.299 | 4.18 | 4.18 | 0.00 | 90.00 | N |
| P_FRONTSTORAGEFLR4_10350_0_10177 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| P_FRONTSTORAGEFLR4_4_0_0 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 90.00 | 90.00 | E |
| F_FRONTSTORAGEFLR4_10277_0_10147 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 12.54 | 12.54 | 180.00 | 180.00 | |
| P_FRONTSTAIRSFLR4_10299_0_10161 | INT_WALL | 0.30 | 2.511 | 6.299 | 6.69 | 6.69 | 0.00 | 90.00 | N |
| P_FRONTSTAIRSFLR4_10354_0_10178 | INT_WALL | 0.30 | 2.511 | 6.299 | 22.58 | 22.58 | 270.00 | 90.00 | W |
| F_FRONTSTAIRSFLR4_10282_0_10149 | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 20.07 | 20.07 | 180.00 | 180.00 |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| W_CORRIDORFLR1_2_0_0_0_0 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 3.241 | 0.391 | 0.431 | No | W_CORRIDORFLR1_2_0_0 | 270.00 | 90.00 | W | |||||||
| D_CORRIDORFLR1_16_0_0_0_0 | NONRESWINDOW_U_0.57_SHGC_0.39 | 4.44 | 0.00 | 0.00 | 4.44 | 4.44 | 3.241 | 0.391 | 0.431 | No | W_CORRIDORFLR1_16_0_0 | 90.00 | 90.00 | E | |||||||
| W_CORRIDORFLR1_20_0_0_0_0 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.69 | 0.00 | 0.00 | 2.69 | 2.69 | 3.241 | 0.391 | 0.431 | No | W_CORRIDORFLR1_20_0_0 | 0.00 | 90.00 | N | |||||||
| W_FRONTLOUNGEFLR1_5_0_0_0_0 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 3.241 | 0.391 | 0.431 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_FRONTLOUNGEFLR1_5_0_0_0_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 3.241 | 0.391 | 0.431 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_FRONTLOUNGEFLR1_5_0_0_0_2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 3.241 | 0.391 | 0.431 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_FRONTLOUNGEFLR1_5_0_0_0_3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 3.241 | 0.391 | 0.431 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_FRONTLOUNGEFLR1_5_0_0_0_4 | NONRESWINDOW_U_0.57_SHGC_0.39 | 2.97 | 0.00 | 0.00 | 2.97 | 2.97 | 3.241 | 0.391 | 0.431 | No | W_FRONTLOUNGEFLR1_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_MEETINGROOMFLR1_5_0_0_0_0 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_MEETINGROOMFLR1_5_0_0_0_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_MEETINGROOMFLR1_5_0_0_0_2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_MEETINGROOMFLR1_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM101_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM101_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM102_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM102_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM103_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM103_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM104_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM104_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM105_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM105_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_EMPLOYEELOUNGEFLR1_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_LAUNDRYROOMFLR1_3_0_0_0_0 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_LAUNDRYROOMFLR1_3_0_0_0_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_LAUNDRYROOMFLR1_3_0_0_0_2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_LAUNDRYROOMFLR1_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_EXERCISECENTERFLR1_3_0_0_0_0 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_EXERCISECENTERFLR1_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_FRONTOFFICEFLR1_3_0_0_0_0 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_FRONTOFFICEFLR1_3_0_0_0_1 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_FRONTOFFICEFLR1_3_0_0_0_2 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_FRONTOFFICEFLR1_3_0_0_0_3 | NONRESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_FRONTOFFICEFLR1_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_CORRIDORFLR2_2_0_0_0_0 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 3.241 | 0.391 | 0.431 | No | W_CORRIDORFLR2_2_0_0 | 270.00 | 90.00 | W | |||||||
| W_CORRIDORFLR2_15_0_0_0_0 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 3.241 | 0.391 | 0.431 | No | W_CORRIDORFLR2_15_0_0 | 90.00 | 90.00 | E | |||||||
| W_GUESTROOM201_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM201_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM202_205_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM202_205_5_0_0_0_1 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM202_205_5_0_0_0_2 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM202_205_5_0_0_0_3 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM202_205_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM206_208_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM206_208_5_0_0_0_1 | RESWINDOW_U_0.57_SHGC_0.39 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM206_208_5_0_0_0_2 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM206_208_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM209_212_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM209_212_5_0_0_0_1 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM209_212_5_0_0_0_2 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM209_212_5_0_0_0_3 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM209_212_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM213_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM213_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM214_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM214_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM215_218_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM215_218_3_0_0_0_1 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM215_218_3_0_0_0_2 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM215_218_3_0_0_0_3 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM215_218_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM219_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM219_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM220_223_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM220_223_3_0_0_0_1 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM220_223_3_0_0_0_2 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM220_223_3_0_0_0_3 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM220_223_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM224_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.81 | 0.00 | 0.00 | 3.81 | 3.81 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM224_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_CORRIDORFLR3_2_0_0_0_0 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 3.241 | 0.391 | 0.431 | No | W_CORRIDORFLR3_2_0_0 | 270.00 | 90.00 | W | |||||||
| W_CORRIDORFLR3_15_0_0_0_0 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 3.241 | 0.391 | 0.431 | No | W_CORRIDORFLR3_15_0_0 | 90.00 | 90.00 | E | |||||||
| W_GUESTROOM301_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM301_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM302_305_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM302_305_5_0_0_0_1 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM302_305_5_0_0_0_2 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM302_305_5_0_0_0_3 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM302_305_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM306_308_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM306_308_5_0_0_0_1 | RESWINDOW_U_0.57_SHGC_0.39 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM306_308_5_0_0_0_2 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM306_308_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM309_312_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM309_312_5_0_0_0_1 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM309_312_5_0_0_0_2 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM309_312_5_0_0_0_3 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM309_312_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM313_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM313_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM314_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM314_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM315_318_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM315_318_3_0_0_0_1 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM315_318_3_0_0_0_2 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM315_318_3_0_0_0_3 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM315_318_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM319_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM319_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM320_323_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM320_323_3_0_0_0_1 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM320_323_3_0_0_0_2 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM320_323_3_0_0_0_3 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM320_323_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM324_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM324_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_CORRIDORFLR4_2_0_0_0_0 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 3.241 | 0.391 | 0.431 | No | W_CORRIDORFLR4_2_0_0 | 270.00 | 90.00 | W | |||||||
| W_CORRIDORFLR4_15_0_0_0_0 | NONRESWINDOW_U_0.57_SHGC_0.39 | 1.31 | 0.00 | 0.00 | 1.31 | 1.31 | 3.241 | 0.391 | 0.431 | No | W_CORRIDORFLR4_15_0_0 | 90.00 | 90.00 | E | |||||||
| W_GUESTROOM401_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM401_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM402_405_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM402_405_5_0_0_0_1 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM402_405_5_0_0_0_2 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM402_405_5_0_0_0_3 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM402_405_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM406_408_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM406_408_5_0_0_0_1 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM406_408_5_0_0_0_2 | RESWINDOW_U_0.57_SHGC_0.39 | 3.41 | 0.00 | 0.00 | 3.41 | 3.41 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM406_408_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM409_412_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM409_412_5_0_0_0_1 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM409_412_5_0_0_0_2 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM409_412_5_0_0_0_3 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM409_412_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM413_5_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM413_5_0_0 | 0.00 | 90.00 | N | |||||||
| W_GUESTROOM414_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM414_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM415_418_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM415_418_3_0_0_0_1 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM415_418_3_0_0_0_2 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM415_418_3_0_0_0_3 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM415_418_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM419_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM419_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM420_423_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM420_423_3_0_0_0_1 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM420_423_3_0_0_0_2 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM420_423_3_0_0_0_3 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM420_423_3_0_0 | 180.00 | 90.00 | S | |||||||
| W_GUESTROOM424_3_0_0_0_0 | RESWINDOW_U_0.57_SHGC_0.39 | 3.80 | 0.00 | 0.00 | 3.80 | 3.80 | 3.241 | 0.391 | 0.431 | No | W_GUESTROOM424_3_0_0 | 180.00 | 90.00 | S | |||||||
| Total or Average | 369.78 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
| North Total or Average | 187.47 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
| Non-North Total or Average | 182.31 | 3.241 | 0.391 | 0.431 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| W_REARSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | W_REARSTAIRSFLR1_3_0_0 |
| W_CORRIDORFLR1_10_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | W_CORRIDORFLR1_10_0_0 |
| W_FRONTSTAIRSFLR1_3_0_0_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | W_FRONTSTAIRSFLR1_3_0_0 |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| W_CORRIDORFLR1_2_0_0_0_0 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| D_CORRIDORFLR1_16_0_0_0_0 | 0.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.97 | 0.56 | 0.00 |
| W_CORRIDORFLR1_20_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_FRONTLOUNGEFLR1_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_FRONTLOUNGEFLR1_5_0_0_0_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_FRONTLOUNGEFLR1_5_0_0_0_2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_FRONTLOUNGEFLR1_5_0_0_0_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_FRONTLOUNGEFLR1_5_0_0_0_4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_MEETINGROOMFLR1_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_MEETINGROOMFLR1_5_0_0_0_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_MEETINGROOMFLR1_5_0_0_0_2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM101_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM102_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM103_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM104_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM105_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_EMPLOYEELOUNGEFLR1_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_LAUNDRYROOMFLR1_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_LAUNDRYROOMFLR1_3_0_0_0_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_LAUNDRYROOMFLR1_3_0_0_0_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_EXERCISECENTERFLR1_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_FRONTOFFICEFLR1_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_FRONTOFFICEFLR1_3_0_0_0_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_FRONTOFFICEFLR1_3_0_0_0_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_FRONTOFFICEFLR1_3_0_0_0_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_CORRIDORFLR2_2_0_0_0_0 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| W_CORRIDORFLR2_15_0_0_0_0 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| W_GUESTROOM201_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM202_205_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM202_205_5_0_0_0_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM202_205_5_0_0_0_2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM202_205_5_0_0_0_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM206_208_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM206_208_5_0_0_0_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM206_208_5_0_0_0_2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM209_212_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM209_212_5_0_0_0_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM209_212_5_0_0_0_2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM209_212_5_0_0_0_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM213_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM214_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM215_218_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM215_218_3_0_0_0_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM215_218_3_0_0_0_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM215_218_3_0_0_0_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM219_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM220_223_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM220_223_3_0_0_0_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM220_223_3_0_0_0_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM220_223_3_0_0_0_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM224_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_CORRIDORFLR3_2_0_0_0_0 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| W_CORRIDORFLR3_15_0_0_0_0 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| W_GUESTROOM301_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM302_305_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM302_305_5_0_0_0_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM302_305_5_0_0_0_2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM302_305_5_0_0_0_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM306_308_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM306_308_5_0_0_0_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM306_308_5_0_0_0_2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM309_312_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM309_312_5_0_0_0_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM309_312_5_0_0_0_2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM309_312_5_0_0_0_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM313_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM314_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM315_318_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM315_318_3_0_0_0_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM315_318_3_0_0_0_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM315_318_3_0_0_0_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM319_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM320_323_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM320_323_3_0_0_0_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM320_323_3_0_0_0_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM320_323_3_0_0_0_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM324_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_CORRIDORFLR4_2_0_0_0_0 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| W_CORRIDORFLR4_15_0_0_0_0 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| W_GUESTROOM401_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM402_405_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM402_405_5_0_0_0_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM402_405_5_0_0_0_2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM402_405_5_0_0_0_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM406_408_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM406_408_5_0_0_0_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM406_408_5_0_0_0_2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM409_412_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM409_412_5_0_0_0_1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM409_412_5_0_0_0_2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM409_412_5_0_0_0_3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM413_5_0_0_0_0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| W_GUESTROOM414_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM415_418_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM415_418_3_0_0_0_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM415_418_3_0_0_0_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM415_418_3_0_0_0_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM419_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM420_423_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM420_423_3_0_0_0_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM420_423_3_0_0_0_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM420_423_3_0_0_0_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| W_GUESTROOM424_3_0_0_0_0 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| CORRIDORFLR1_LIGHTS | CORRIDORFLR1 | CORRIDORFLR1 | GENERAL | 5.3819 | 150.51 | 810.01 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | Y | 25.54 |
| CORRIDORFLR2_LIGHTS | CORRIDORFLR2 | CORRIDORFLR2 | GENERAL | 5.3819 | 125.42 | 675.01 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | Y | 21.29 |
| CORRIDORFLR3_LIGHTS | CORRIDORFLR3 | CORRIDORFLR3 | GENERAL | 5.3819 | 125.42 | 675.01 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | Y | 21.29 |
| CORRIDORFLR4_LIGHTS | CORRIDORFLR4 | CORRIDORFLR4 | GENERAL | 5.3819 | 125.42 | 675.01 | LightsWired | LTG_SCH_CORRIDOR | 168.00 | 168.00 | 168.00 | 0.0000 | Y | 21.29 |
| ELEVATORCOREFLR1_LIGHTS | ELEVATORCOREFLR1 | ELEVATORCOREFLR1 | GENERAL | 0.0000 | 15.05 | 0.00 | LightsWired | LTG_SCH_ELEVATOR | 0.00 | 0.00 | 0.0000 | N | 0.00 | |
| ELEVATORCOREFLR2_LIGHTS | ELEVATORCOREFLR2 | ELEVATORCOREFLR2 | GENERAL | 0.0000 | 15.05 | 0.00 | LightsWired | LTG_SCH_ELEVATOR | 0.00 | 0.00 | 0.0000 | N | 0.00 | |
| ELEVATORCOREFLR3_LIGHTS | ELEVATORCOREFLR3 | ELEVATORCOREFLR3 | GENERAL | 0.0000 | 15.05 | 0.00 | LightsWired | LTG_SCH_ELEVATOR | 0.00 | 0.00 | 0.0000 | N | 0.00 | |
| ELEVATORCOREFLR4_LIGHTS | ELEVATORCOREFLR4 | ELEVATORCOREFLR4 | GENERAL | 0.0000 | 15.05 | 0.00 | LightsWired | LTG_SCH_ELEVATOR | 0.00 | 0.00 | 0.0000 | N | 0.00 | |
| EMPLOYEELOUNGEFLR1_LIGHTS | EMPLOYEELOUNGEFLR1 | EMPLOYEELOUNGEFLR1 | GENERAL | 12.9167 | 32.61 | 421.20 | LightsWired | LTG_SCH_LOUNGE | 84.35 | 119.00 | 84.35 | 0.0000 | Y | 6.67 |
| EXERCISECENTERFLR1_LIGHTS | EXERCISECENTERFLR1 | EXERCISECENTERFLR1 | GENERAL | 9.6875 | 32.61 | 315.90 | LightsWired | LTG_SCH_EXERCISE | 112.00 | 119.00 | 112.00 | 0.0000 | Y | 6.64 |
| FRONTLOUNGEFLR1_LIGHTS | FRONTLOUNGEFLR1 | FRONTLOUNGEFLR1 | GENERAL | 13.9931 | 163.06 | 2281.66 | LightsWired | LTG_SCH_LOBBY | 84.35 | 119.00 | 84.35 | 0.0000 | Y | 36.13 |
| FRONTOFFICEFLR1_LIGHTS | FRONTOFFICEFLR1 | FRONTOFFICEFLR1 | GENERAL | 11.8403 | 130.44 | 1544.40 | LightsWired | LTG_SCH_OFFICE | 110.04 | 168.00 | 110.04 | 0.0000 | Y | 31.90 |
| FRONTSTAIRSFLR1_LIGHTS | FRONTSTAIRSFLR1 | FRONTSTAIRSFLR1 | GENERAL | 6.4583 | 20.07 | 129.60 | LightsWired | LTG_SCH_STAIR | 168.00 | 168.00 | 168.00 | 0.0000 | Y | 4.09 |
| FRONTSTAIRSFLR2_LIGHTS | FRONTSTAIRSFLR2 | FRONTSTAIRSFLR2 | GENERAL | 6.4583 | 20.07 | 129.60 | LightsWired | LTG_SCH_STAIR | 168.00 | 168.00 | 168.00 | 0.0000 | Y | 4.09 |
| FRONTSTAIRSFLR3_LIGHTS | FRONTSTAIRSFLR3 | FRONTSTAIRSFLR3 | GENERAL | 6.4583 | 20.07 | 129.60 | LightsWired | LTG_SCH_STAIR | 168.00 | 168.00 | 168.00 | 0.0000 | Y | 4.09 |
| FRONTSTAIRSFLR4_LIGHTS | FRONTSTAIRSFLR4 | FRONTSTAIRSFLR4 | GENERAL | 6.4583 | 20.07 | 129.60 | LightsWired | LTG_SCH_STAIR | 168.00 | 168.00 | 168.00 | 0.0000 | Y | 4.09 |
| FRONTSTORAGEFLR1_LIGHTS | FRONTSTORAGEFLR1 | FRONTSTORAGEFLR1 | GENERAL | 8.6111 | 12.54 | 108.00 | LightsWired | LTG_SCH_STORAGE | 42.00 | 168.00 | 42.00 | 0.0000 | N | 0.85 |
| FRONTSTORAGEFLR2_LIGHTS | FRONTSTORAGEFLR2 | FRONTSTORAGEFLR2 | GENERAL | 8.6111 | 12.54 | 108.00 | LightsWired | LTG_SCH_STORAGE | 42.00 | 168.00 | 42.00 | 0.0000 | N | 0.85 |
| FRONTSTORAGEFLR3_LIGHTS | FRONTSTORAGEFLR3 | FRONTSTORAGEFLR3 | GENERAL | 8.6111 | 12.54 | 108.00 | LightsWired | LTG_SCH_STORAGE | 42.00 | 168.00 | 42.00 | 0.0000 | N | 0.85 |
| FRONTSTORAGEFLR4_LIGHTS | FRONTSTORAGEFLR4 | FRONTSTORAGEFLR4 | GENERAL | 8.6111 | 12.54 | 108.00 | LightsWired | LTG_SCH_STORAGE | 42.00 | 168.00 | 42.00 | 0.0000 | N | 0.85 |
| GUESTROOM101_LIGHTS | GUESTROOM101 | GUESTROOM101 | GENERAL | 12.2708 | 32.61 | 400.17 | LightsWired | ALWAYSOFF | 0.00 | 0.00 | 0.00 | 0.0000 | Y | 0.00 |
| GUESTROOM102_LIGHTS | GUESTROOM102 | GUESTROOM102 | GENERAL | 12.2708 | 32.61 | 400.17 | LightsWired | ALWAYSOFF | 0.00 | 0.00 | 0.00 | 0.0000 | Y | 0.00 |
| GUESTROOM103_LIGHTS | GUESTROOM103 | GUESTROOM103 | GENERAL | 12.2708 | 32.61 | 400.17 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 5.20 |
| GUESTROOM104_LIGHTS | GUESTROOM104 | GUESTROOM104 | GENERAL | 12.2708 | 32.61 | 400.14 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 5.20 |
| GUESTROOM105_LIGHTS | GUESTROOM105 | GUESTROOM105 | GENERAL | 12.2708 | 32.61 | 400.14 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 5.20 |
| GUESTROOM201_LIGHTS | GUESTROOM201 | GUESTROOM201 | GENERAL | 12.2708 | 32.61 | 400.17 | LightsWired | ALWAYSOFF | 0.00 | 0.00 | 0.00 | 0.0000 | Y | 0.00 |
| GUESTROOM202_205_LIGHTS | GUESTROOM202_205 | GUESTROOM202_205 | GENERAL | 12.2708 | 130.45 | 1600.67 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 20.81 |
| GUESTROOM206_208_LIGHTS | GUESTROOM206_208 | GUESTROOM206_208 | GENERAL | 12.2708 | 105.36 | 1292.85 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 16.81 |
| GUESTROOM209_212_LIGHTS | GUESTROOM209_212 | GUESTROOM209_212 | GENERAL | 12.2708 | 130.45 | 1600.67 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 20.81 |
| GUESTROOM213_LIGHTS | GUESTROOM213 | GUESTROOM213 | GENERAL | 12.2708 | 32.61 | 400.17 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 5.20 |
| GUESTROOM214_LIGHTS | GUESTROOM214 | GUESTROOM214 | GENERAL | 12.2708 | 32.61 | 400.14 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 5.20 |
| GUESTROOM215_218_LIGHTS | GUESTROOM215_218 | GUESTROOM215_218 | GENERAL | 12.2708 | 130.44 | 1600.56 | LightsWired | ALWAYSOFF | 0.00 | 0.00 | 0.00 | 0.0000 | Y | 0.00 |
| GUESTROOM219_LIGHTS | GUESTROOM219 | GUESTROOM219 | GENERAL | 12.2708 | 32.61 | 400.14 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 5.20 |
| GUESTROOM220_223_LIGHTS | GUESTROOM220_223 | GUESTROOM220_223 | GENERAL | 12.2708 | 130.44 | 1600.56 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 20.81 |
| GUESTROOM224_LIGHTS | GUESTROOM224 | GUESTROOM224 | GENERAL | 12.2708 | 32.61 | 400.14 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 5.20 |
| GUESTROOM301_LIGHTS | GUESTROOM301 | GUESTROOM301 | GENERAL | 12.2708 | 32.61 | 400.17 | LightsWired | ALWAYSOFF | 0.00 | 0.00 | 0.00 | 0.0000 | Y | 0.00 |
| GUESTROOM302_305_LIGHTS | GUESTROOM302_305 | GUESTROOM302_305 | GENERAL | 12.2708 | 130.45 | 1600.67 | LightsWired | ALWAYSOFF | 0.00 | 0.00 | 0.00 | 0.0000 | Y | 0.00 |
| GUESTROOM306_308_LIGHTS | GUESTROOM306_308 | GUESTROOM306_308 | GENERAL | 12.2708 | 105.36 | 1292.85 | LightsWired | ALWAYSOFF | 0.00 | 0.00 | 0.00 | 0.0000 | Y | 0.00 |
| GUESTROOM309_312_LIGHTS | GUESTROOM309_312 | GUESTROOM309_312 | GENERAL | 12.2708 | 130.45 | 1600.67 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 20.81 |
| GUESTROOM313_LIGHTS | GUESTROOM313 | GUESTROOM313 | GENERAL | 12.2708 | 32.61 | 400.17 | LightsWired | ALWAYSOFF | 0.00 | 0.00 | 0.00 | 0.0000 | Y | 0.00 |
| GUESTROOM314_LIGHTS | GUESTROOM314 | GUESTROOM314 | GENERAL | 12.2708 | 32.61 | 400.14 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 5.20 |
| GUESTROOM315_318_LIGHTS | GUESTROOM315_318 | GUESTROOM315_318 | GENERAL | 12.2708 | 130.44 | 1600.56 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 20.81 |
| GUESTROOM319_LIGHTS | GUESTROOM319 | GUESTROOM319 | GENERAL | 12.2708 | 32.61 | 400.14 | LightsWired | ALWAYSOFF | 0.00 | 0.00 | 0.00 | 0.0000 | Y | 0.00 |
| GUESTROOM320_323_LIGHTS | GUESTROOM320_323 | GUESTROOM320_323 | GENERAL | 12.2708 | 130.44 | 1600.56 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 20.81 |
| GUESTROOM324_LIGHTS | GUESTROOM324 | GUESTROOM324 | GENERAL | 12.2708 | 32.61 | 400.14 | LightsWired | ALWAYSOFF | 0.00 | 0.00 | 0.00 | 0.0000 | Y | 0.00 |
| GUESTROOM401_LIGHTS | GUESTROOM401 | GUESTROOM401 | GENERAL | 12.2708 | 32.61 | 400.17 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 5.20 |
| GUESTROOM402_405_LIGHTS | GUESTROOM402_405 | GUESTROOM402_405 | GENERAL | 12.2708 | 130.45 | 1600.67 | LightsWired | ALWAYSOFF | 0.00 | 0.00 | 0.00 | 0.0000 | Y | 0.00 |
| GUESTROOM406_408_LIGHTS | GUESTROOM406_408 | GUESTROOM406_408 | GENERAL | 12.2708 | 105.36 | 1292.85 | LightsWired | ALWAYSOFF | 0.00 | 0.00 | 0.00 | 0.0000 | Y | 0.00 |
| GUESTROOM409_412_LIGHTS | GUESTROOM409_412 | GUESTROOM409_412 | GENERAL | 12.2708 | 130.45 | 1600.67 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 20.81 |
| GUESTROOM413_LIGHTS | GUESTROOM413 | GUESTROOM413 | GENERAL | 12.2708 | 32.61 | 400.17 | LightsWired | ALWAYSOFF | 0.00 | 0.00 | 0.00 | 0.0000 | Y | 0.00 |
| GUESTROOM414_LIGHTS | GUESTROOM414 | GUESTROOM414 | GENERAL | 12.2708 | 32.61 | 400.14 | LightsWired | ALWAYSOFF | 0.00 | 0.00 | 0.00 | 0.0000 | Y | 0.00 |
| GUESTROOM415_418_LIGHTS | GUESTROOM415_418 | GUESTROOM415_418 | GENERAL | 12.2708 | 130.44 | 1600.56 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 20.81 |
| GUESTROOM419_LIGHTS | GUESTROOM419 | GUESTROOM419 | GENERAL | 12.2708 | 32.61 | 400.14 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 5.20 |
| GUESTROOM420_423_LIGHTS | GUESTROOM420_423 | GUESTROOM420_423 | GENERAL | 12.2708 | 130.44 | 1600.56 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 20.81 |
| GUESTROOM424_LIGHTS | GUESTROOM424 | GUESTROOM424 | GENERAL | 12.2708 | 32.61 | 400.14 | LightsWired | LTG_SCH_GUESTROOM | 69.03 | 168.00 | 69.26 | 0.0000 | Y | 5.20 |
| LAUNDRYROOMFLR1_LIGHTS | LAUNDRYROOMFLR1 | LAUNDRYROOMFLR1 | GENERAL | 6.4583 | 97.83 | 631.80 | LightsWired | LTG_SCH_LAUNDRY | 63.00 | 63.00 | 63.00 | 0.0000 | N | 7.47 |
| MECHANICALROOMFLR1_LIGHTS | MECHANICALROOMFLR1 | MECHANICALROOMFLR1 | GENERAL | 16.1458 | 32.61 | 526.54 | LightsWired | LTG_SCH_MECHANICAL | 42.00 | 168.00 | 42.00 | 0.0000 | Y | 4.15 |
| MEETINGROOMFLR1_LIGHTS | MEETINGROOMFLR1 | MEETINGROOMFLR1 | GENERAL | 13.9931 | 80.27 | 1123.28 | LightsWired | LTG_SCH_MEETING | 84.35 | 119.00 | 84.35 | 0.0000 | Y | 17.79 |
| REARSTAIRSFLR1_LIGHTS | REARSTAIRSFLR1 | REARSTAIRSFLR1 | GENERAL | 6.4583 | 20.07 | 129.63 | LightsWired | LTG_SCH_STAIR | 168.00 | 168.00 | 168.00 | 0.0000 | Y | 4.09 |
| REARSTAIRSFLR2_LIGHTS | REARSTAIRSFLR2 | REARSTAIRSFLR2 | GENERAL | 6.4583 | 20.07 | 129.63 | LightsWired | LTG_SCH_STAIR | 168.00 | 168.00 | 168.00 | 0.0000 | Y | 4.09 |
| REARSTAIRSFLR3_LIGHTS | REARSTAIRSFLR3 | REARSTAIRSFLR3 | GENERAL | 6.4583 | 20.07 | 129.63 | LightsWired | LTG_SCH_STAIR | 168.00 | 168.00 | 168.00 | 0.0000 | Y | 4.09 |
| REARSTAIRSFLR4_LIGHTS | REARSTAIRSFLR4 | REARSTAIRSFLR4 | GENERAL | 6.4583 | 20.07 | 129.63 | LightsWired | LTG_SCH_STAIR | 168.00 | 168.00 | 168.00 | 0.0000 | Y | 4.09 |
| REARSTORAGEFLR1_LIGHTS | REARSTORAGEFLR1 | REARSTORAGEFLR1 | GENERAL | 8.6111 | 20.07 | 172.85 | LightsWired | LTG_SCH_STORAGE | 42.00 | 168.00 | 42.00 | 0.0000 | N | 1.36 |
| REARSTORAGEFLR2_LIGHTS | REARSTORAGEFLR2 | REARSTORAGEFLR2 | GENERAL | 8.6111 | 20.07 | 172.85 | LightsWired | LTG_SCH_STORAGE | 42.00 | 168.00 | 42.00 | 0.0000 | N | 1.36 |
| REARSTORAGEFLR3_LIGHTS | REARSTORAGEFLR3 | REARSTORAGEFLR3 | GENERAL | 8.6111 | 20.07 | 172.85 | LightsWired | LTG_SCH_STORAGE | 42.00 | 168.00 | 42.00 | 0.0000 | N | 1.36 |
| REARSTORAGEFLR4_LIGHTS | REARSTORAGEFLR4 | REARSTORAGEFLR4 | GENERAL | 8.6111 | 20.07 | 172.85 | LightsWired | LTG_SCH_STORAGE | 42.00 | 168.00 | 42.00 | 0.0000 | N | 1.36 |
| RESTROOMFLR1_LIGHTS | RESTROOMFLR1 | RESTROOMFLR1 | GENERAL | 9.6875 | 32.61 | 315.92 | LightsWired | LTG_SCH_RESTROOM | 168.00 | 168.00 | 168.00 | 0.0000 | Y | 9.96 |
| Interior Lighting Total | 10.7747 | 4013.58 | 43245.05 | 512.99 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| EXTERIOR_LIGHTS | 6812.70 | AstronomicalClock | - | 83.67 | 83.67 | 107.00 | |
| Exterior Lighting Total | 6812.70 | 107.00 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| HEATSYS1 BOILER | Boiler:HotWater | 291348.79 | 0.75 |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| CORRIDORFLR1 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 57197.49 | 45789.08 | 11408.40 | 0.80 | 3.81 | |||
| SAC_FRONTLOUNGE PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 17965.84 | 13033.49 | 4932.35 | 0.73 | 3.81 | |||
| SAC_RESTROOM PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1101.41 | 881.85 | 219.56 | 0.80 | 3.81 | |||
| SAC_MEETINGROOM PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9387.81 | 6581.64 | 2806.18 | 0.70 | 3.81 | |||
| 101 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1354.40 | 1047.99 | 306.41 | 0.77 | 3.81 | |||
| 102 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1351.88 | 1009.78 | 342.09 | 0.75 | 3.81 | |||
| 103 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1954.16 | 1564.56 | 389.60 | 0.80 | 3.81 | |||
| 104 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2432.32 | 1947.83 | 484.49 | 0.80 | 3.81 | |||
| 105 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3118.37 | 2496.41 | 621.96 | 0.80 | 3.81 | |||
| SAC_EMPLOYEELOUNGE PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11942.53 | 9563.56 | 2378.96 | 0.80 | 3.81 | |||
| SAC_EXERCISECENTER PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3011.23 | 2225.92 | 785.31 | 0.74 | 3.81 | |||
| SAC_FRONTOFFICE PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7443.65 | 5933.90 | 1509.75 | 0.80 | 3.81 | |||
| CORRIDORFLR2 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5515.62 | 4412.81 | 1102.81 | 0.80 | 3.81 | |||
| 201 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1711.21 | 1327.69 | 383.52 | 0.78 | 3.81 | |||
| 202_205 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7388.41 | 5916.09 | 1472.32 | 0.80 | 3.81 | |||
| 206_208 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5861.35 | 4691.57 | 1169.78 | 0.80 | 3.81 | |||
| 209_212 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7203.26 | 5769.39 | 1433.87 | 0.80 | 3.81 | |||
| 213 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1977.30 | 1582.52 | 394.79 | 0.80 | 3.81 | |||
| 214 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2608.89 | 2089.52 | 519.36 | 0.80 | 3.81 | |||
| 215_218 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 19026.41 | 15233.60 | 3792.82 | 0.80 | 3.81 | |||
| 219 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10136.72 | 8116.02 | 2020.70 | 0.80 | 3.81 | |||
| 220_223 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9117.95 | 7296.17 | 1821.79 | 0.80 | 3.81 | |||
| 224 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2573.36 | 2059.02 | 514.35 | 0.80 | 3.81 | |||
| CORRIDORFLR3 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4633.66 | 3478.84 | 1154.82 | 0.75 | 3.81 | |||
| 301 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1997.16 | 1478.98 | 518.18 | 0.74 | 3.81 | |||
| 302_305 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 4732.70 | 3520.08 | 1212.62 | 0.74 | 3.81 | |||
| 306_308 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3594.10 | 2683.96 | 910.14 | 0.75 | 3.81 | |||
| 309_312 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7051.15 | 5643.25 | 1407.90 | 0.80 | 3.81 | |||
| 313 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1966.48 | 1554.79 | 411.69 | 0.79 | 3.81 | |||
| 314 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2415.53 | 1932.58 | 482.96 | 0.80 | 3.81 | |||
| 315_318 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9959.94 | 7977.09 | 1982.84 | 0.80 | 3.81 | |||
| 319 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2179.78 | 1745.18 | 434.60 | 0.80 | 3.81 | |||
| 320_323 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 8705.61 | 6967.41 | 1738.20 | 0.80 | 3.81 | |||
| 324 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 1612.96 | 1271.74 | 341.23 | 0.79 | 3.81 | |||
| CORRIDORFLR4 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 7018.70 | 5533.62 | 1485.08 | 0.79 | 3.81 | |||
| 401 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2498.50 | 1999.29 | 499.22 | 0.80 | 3.81 | |||
| 402_405 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 6912.99 | 5241.81 | 1671.18 | 0.76 | 3.81 | |||
| 406_408 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 5414.23 | 4114.77 | 1299.46 | 0.76 | 3.81 | |||
| 409_412 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 9239.10 | 7391.63 | 1847.47 | 0.80 | 3.81 | |||
| 413 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2649.59 | 2094.99 | 554.60 | 0.79 | 3.81 | |||
| 414 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2392.17 | 1913.79 | 478.38 | 0.80 | 3.81 | |||
| 415_418 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 11070.48 | 8865.95 | 2204.53 | 0.80 | 3.81 | |||
| 419 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 2955.20 | 2366.74 | 588.45 | 0.80 | 3.81 | |||
| 420_423 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 10935.32 | 8750.26 | 2185.06 | 0.80 | 3.81 | |||
| 424 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | 3013.75 | 2412.18 | 601.57 | 0.80 | 3.81 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| CORRIDORFLR1 PTAC PTAC COOLING COIL | 54829.6 | 3.16 | 10.77 | 11.41 | 10.79 | 10.70 | |
| SAC_FRONTLOUNGE PTAC COOLING COIL | 17359.2 | 3.26 | 11.14 | 11.81 | 11.17 | 11.26 | |
| SAC_RESTROOM PTAC COOLING COIL | 1049.8 | 3.08 | 10.52 | 11.14 | 10.54 | 10.33 | |
| SAC_MEETINGROOM PTAC COOLING COIL | 9094.0 | 3.30 | 11.26 | 11.94 | 11.30 | 11.45 | |
| 101 PTAC PTAC COOLING COIL | 1302.1 | 3.19 | 10.90 | 11.55 | 10.93 | 10.90 | |
| 102 PTAC PTAC COOLING COIL | 1303.2 | 3.23 | 11.03 | 11.69 | 11.06 | 11.09 | |
| 103 PTAC PTAC COOLING COIL | 1869.3 | 3.13 | 10.67 | 11.31 | 10.70 | 10.56 | |
| 104 PTAC PTAC COOLING COIL | 2329.7 | 3.15 | 10.73 | 11.37 | 10.76 | 10.65 | |
| 105 PTAC PTAC COOLING COIL | 2981.3 | 3.12 | 10.65 | 11.28 | 10.67 | 10.53 | |
| SAC_EMPLOYEELOUNGE PTAC COOLING COIL | 11420.4 | 3.12 | 10.66 | 11.29 | 10.68 | 10.54 | |
| SAC_EXERCISECENTER PTAC COOLING COIL | 2905.4 | 3.24 | 11.07 | 11.74 | 11.10 | 11.15 | |
| SAC_FRONTOFFICE PTAC COOLING COIL | 7139.6 | 3.16 | 10.80 | 11.44 | 10.82 | 10.74 | |
| CORRIDORFLR2 PTAC PTAC COOLING COIL | 5284.1 | 3.15 | 10.74 | 11.38 | 10.77 | 10.66 | |
| 201 PTAC PTAC COOLING COIL | 1644.9 | 3.19 | 10.89 | 11.54 | 10.92 | 10.89 | |
| 202_205 PTAC PTAC COOLING COIL | 7071.1 | 3.14 | 10.70 | 11.33 | 10.72 | 10.60 | |
| 206_208 PTAC PTAC COOLING COIL | 5609.1 | 3.13 | 10.69 | 11.33 | 10.72 | 10.59 | |
| 209_212 PTAC PTAC COOLING COIL | 6895.5 | 3.14 | 10.71 | 11.34 | 10.73 | 10.61 | |
| 213 PTAC PTAC COOLING COIL | 1891.2 | 3.13 | 10.67 | 11.30 | 10.69 | 10.56 | |
| 214 PTAC PTAC COOLING COIL | 2497.4 | 3.14 | 10.71 | 11.34 | 10.73 | 10.61 | |
| 215_218 PTAC PTAC COOLING COIL | 18134.5 | 3.08 | 10.52 | 11.14 | 10.54 | 10.33 | |
| 219 PTAC PTAC COOLING COIL | 9661.6 | 3.08 | 10.52 | 11.14 | 10.54 | 10.33 | |
| 220_223 PTAC PTAC COOLING COIL | 8737.4 | 3.15 | 10.75 | 11.39 | 10.78 | 10.68 | |
| 224 PTAC PTAC COOLING COIL | 2463.7 | 3.14 | 10.71 | 11.35 | 10.74 | 10.62 | |
| CORRIDORFLR3 PTAC PTAC COOLING COIL | 4465.3 | 3.23 | 11.01 | 11.67 | 11.04 | 11.06 | |
| 301 PTAC PTAC COOLING COIL | 1926.7 | 3.24 | 11.06 | 11.73 | 11.09 | 11.14 | |
| 302_305 PTAC PTAC COOLING COIL | 4564.3 | 3.24 | 11.05 | 11.71 | 11.08 | 11.12 | |
| 306_308 PTAC PTAC COOLING COIL | 3464.9 | 3.23 | 11.03 | 11.69 | 11.06 | 11.09 | |
| 309_312 PTAC PTAC COOLING COIL | 6753.2 | 3.14 | 10.73 | 11.37 | 10.75 | 10.64 | |
| 313 PTAC PTAC COOLING COIL | 1887.3 | 3.17 | 10.82 | 11.47 | 10.85 | 10.78 | |
| 314 PTAC PTAC COOLING COIL | 2313.8 | 3.15 | 10.74 | 11.37 | 10.76 | 10.65 | |
| 315_318 PTAC PTAC COOLING COIL | 9538.3 | 3.14 | 10.73 | 11.36 | 10.75 | 10.64 | |
| 319 PTAC PTAC COOLING COIL | 2086.8 | 3.14 | 10.71 | 11.35 | 10.73 | 10.61 | |
| 320_323 PTAC PTAC COOLING COIL | 8346.6 | 3.16 | 10.78 | 11.42 | 10.80 | 10.71 | |
| 324 PTAC PTAC COOLING COIL | 1548.5 | 3.18 | 10.84 | 11.48 | 10.86 | 10.80 | |
| CORRIDORFLR4 PTAC PTAC COOLING COIL | 6738.1 | 3.18 | 10.84 | 11.48 | 10.86 | 10.80 | |
| 401 PTAC PTAC COOLING COIL | 2393.9 | 3.15 | 10.75 | 11.39 | 10.77 | 10.67 | |
| 402_405 PTAC PTAC COOLING COIL | 6656.9 | 3.22 | 10.98 | 11.63 | 11.01 | 11.01 | |
| 406_408 PTAC PTAC COOLING COIL | 5212.5 | 3.21 | 10.97 | 11.62 | 10.99 | 11.00 | |
| 409_412 PTAC PTAC COOLING COIL | 8853.7 | 3.15 | 10.75 | 11.39 | 10.78 | 10.68 | |
| 413 PTAC PTAC COOLING COIL | 2542.9 | 3.17 | 10.82 | 11.47 | 10.85 | 10.78 | |
| 414 PTAC PTAC COOLING COIL | 2290.9 | 3.14 | 10.73 | 11.36 | 10.75 | 10.64 | |
| 415_418 PTAC PTAC COOLING COIL | 10592.0 | 3.13 | 10.68 | 11.32 | 10.71 | 10.58 | |
| 419 PTAC PTAC COOLING COIL | 2826.3 | 3.13 | 10.67 | 11.30 | 10.69 | 10.55 | |
| 420_423 PTAC PTAC COOLING COIL | 10463.7 | 3.13 | 10.69 | 11.32 | 10.71 | 10.58 | |
| 424 PTAC PTAC COOLING COIL | 2882.2 | 3.13 | 10.66 | 11.30 | 10.69 | 10.55 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| CORRIDORFLR1 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SAC_FRONTLOUNGE PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SAC_RESTROOM PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SAC_MEETINGROOM PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 101 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 102 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 103 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 104 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 105 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SAC_EMPLOYEELOUNGE PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SAC_EXERCISECENTER PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| SAC_FRONTOFFICE PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| CORRIDORFLR2 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 201 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 202_205 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 206_208 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 209_212 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 213 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 214 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 215_218 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 219 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 220_223 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 224 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| CORRIDORFLR3 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 301 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 302_305 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 306_308 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 309_312 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 313 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 314 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 315_318 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 319 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 320_323 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 324 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| CORRIDORFLR4 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 401 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 402_405 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 406_408 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 409_412 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 413 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 414 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 415_418 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 419 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 420_423 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed | ||||||||
| 424 PTAC PTAC COOLING COIL | Coil:Cooling:DX:SingleSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| REARSTAIRSFLR1 UNITHEATER HEATING COIL | Coil:Heating:Fuel | 81.38 | 0.79 | |
| CORRIDORFLR1 PTAC HEATING COIL | Coil:Heating:Water | 42709.16 | 45595.97 | - |
| SAC_FRONTLOUNGE HEATING COIL | Coil:Heating:Water | 20956.11 | 19041.48 | - |
| SAC_RESTROOM HEATING COIL | Coil:Heating:Water | 885.01 | 953.70 | - |
| SAC_MEETINGROOM HEATING COIL | Coil:Heating:Water | 10689.71 | 9554.88 | - |
| MECHRM UNITHEATER HEATING COIL | Coil:Heating:Fuel | 0.00 | 0.79 | |
| 101 PTAC HEATING COIL | Coil:Heating:Water | 1499.88 | 1439.06 | - |
| 102 PTAC HEATING COIL | Coil:Heating:Water | 1436.70 | 1367.09 | - |
| 103 PTAC HEATING COIL | Coil:Heating:Water | 2058.45 | 2061.63 | - |
| 104 PTAC HEATING COIL | Coil:Heating:Water | 2362.17 | 2395.01 | - |
| 105 PTAC HEATING COIL | Coil:Heating:Water | 2951.82 | 3037.96 | - |
| SAC_EMPLOYEELOUNGE HEATING COIL | Coil:Heating:Water | 11247.01 | 11575.23 | - |
| SAC_EXERCISECENTER HEATING COIL | Coil:Heating:Water | 3739.96 | 3373.97 | - |
| SAC_FRONTOFFICE HEATING COIL | Coil:Heating:Water | 7731.01 | 7653.03 | - |
| FRONTSTAIRSFLR1 UNITHEATER HEATING COIL | Coil:Heating:Fuel | 359.76 | 0.79 | |
| REARSTAIRSFLR2 UNITHEATER HEATING COIL | Coil:Heating:Fuel | 81.37 | 0.79 | |
| CORRIDORFLR2 PTAC HEATING COIL | Coil:Heating:Water | 5678.69 | 5671.79 | - |
| 201 PTAC HEATING COIL | Coil:Heating:Water | 1740.19 | 1709.25 | - |
| 202_205 PTAC HEATING COIL | Coil:Heating:Water | 7851.97 | 7825.59 | - |
| 206_208 PTAC HEATING COIL | Coil:Heating:Water | 6236.20 | 6216.70 | - |
| 209_212 PTAC HEATING COIL | Coil:Heating:Water | 7687.66 | 7643.96 | - |
| 213 PTAC HEATING COIL | Coil:Heating:Water | 2078.75 | 2084.00 | - |
| 214 PTAC HEATING COIL | Coil:Heating:Water | 2513.30 | 2560.21 | - |
| 215_218 PTAC HEATING COIL | Coil:Heating:Water | 17702.71 | 18540.57 | - |
| 219 PTAC HEATING COIL | Coil:Heating:Water | 8748.72 | 9301.49 | - |
| 220_223 PTAC HEATING COIL | Coil:Heating:Water | 8934.78 | 9017.23 | - |
| 224 PTAC HEATING COIL | Coil:Heating:Water | 2482.81 | 2526.92 | - |
| FRONTSTAIRSFLR2 UNITHEATER HEATING COIL | Coil:Heating:Fuel | 324.77 | 0.79 | |
| REARSTAIRSFLR3 UNITHEATER HEATING COIL | Coil:Heating:Fuel | 81.38 | 0.79 | |
| CORRIDORFLR3 PTAC HEATING COIL | Coil:Heating:Water | 4595.94 | 4467.78 | - |
| 301 PTAC HEATING COIL | Coil:Heating:Water | 1810.79 | 1787.85 | - |
| 302_305 PTAC HEATING COIL | Coil:Heating:Water | 5298.20 | 4951.62 | - |
| 306_308 PTAC HEATING COIL | Coil:Heating:Water | 4127.01 | 3840.50 | - |
| 309_312 PTAC HEATING COIL | Coil:Heating:Water | 7520.64 | 7459.05 | - |
| 313 PTAC HEATING COIL | Coil:Heating:Water | 1960.25 | 1953.33 | - |
| 314 PTAC HEATING COIL | Coil:Heating:Water | 2346.09 | 2377.42 | - |
| 315_318 PTAC HEATING COIL | Coil:Heating:Water | 9639.66 | 9789.16 | - |
| 319 PTAC HEATING COIL | Coil:Heating:Water | 2197.76 | 2214.86 | - |
| 320_323 PTAC HEATING COIL | Coil:Heating:Water | 8566.45 | 8612.82 | - |
| 324 PTAC HEATING COIL | Coil:Heating:Water | 1708.58 | 1673.91 | - |
| FRONTSTAIRSFLR3 UNITHEATER HEATING COIL | Coil:Heating:Fuel | 404.27 | 0.79 | |
| REARSTAIRSFLR4 UNITHEATER HEATING COIL | Coil:Heating:Fuel | 290.54 | 0.79 | |
| CORRIDORFLR4 PTAC HEATING COIL | Coil:Heating:Water | 6519.65 | 6595.88 | - |
| 401 PTAC HEATING COIL | Coil:Heating:Water | 2395.89 | 2431.96 | - |
| 402_405 PTAC HEATING COIL | Coil:Heating:Water | 6800.00 | 6657.24 | - |
| 406_408 PTAC HEATING COIL | Coil:Heating:Water | 5368.86 | 5253.31 | - |
| 409_412 PTAC HEATING COIL | Coil:Heating:Water | 9018.34 | 9108.70 | - |
| 413 PTAC HEATING COIL | Coil:Heating:Water | 2431.72 | 2471.06 | - |
| 414 PTAC HEATING COIL | Coil:Heating:Water | 2339.48 | 2370.17 | - |
| 415_418 PTAC HEATING COIL | Coil:Heating:Water | 10613.28 | 10851.97 | - |
| 419 PTAC HEATING COIL | Coil:Heating:Water | 2811.68 | 2885.48 | - |
| 420_423 PTAC HEATING COIL | Coil:Heating:Water | 10496.92 | 10725.10 | - |
| 424 PTAC HEATING COIL | Coil:Heating:Water | 2858.83 | 2936.77 | - |
| FRONTSTAIRSFLR4 UNITHEATER HEATING COIL | Coil:Heating:Fuel | 652.14 | 0.79 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| REARSTAIRSFLR1 UNITHEATER FAN | Fan:ConstantVolume | 0.54 | 340.63 | 0.01 | 3.89 | 635.51 | 1.00 | 41.46 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
| CORRIDORFLR1 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 3.05 | 1942.52 | 636.87 | 1.00 | 1.29 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 |
| SAC_FRONTLOUNGE_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.78 | 497.19 | 636.87 | 1.00 | 1.59 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
| SAC_RESTROOM_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.07 | 42.37 | 636.87 | 1.00 | 5.02 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
| SAC_MEETINGROOM_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.38 | 240.77 | 636.87 | 1.00 | 1.97 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
| MECHRM UNITHEATER FAN | Fan:ConstantVolume | 0.54 | 340.63 | 0.00 | 0.00 | 1.00 | 0.00 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | |
| 101 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.07 | 42.91 | 636.87 | 1.00 | 4.97 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
| 102 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.06 | 39.89 | 636.87 | 1.00 | 5.24 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 |
| 103 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.11 | 69.66 | 636.87 | 1.00 | 3.59 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 |
| 104 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 84.20 | 636.87 | 1.00 | 3.20 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 |
| 105 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.18 | 112.43 | 636.87 | 1.00 | 2.73 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
| SAC_EMPLOYEELOUNGE_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.67 | 428.40 | 636.87 | 1.00 | 1.65 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
| SAC_EXERCISECENTER_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.14 | 86.72 | 636.87 | 1.00 | 3.15 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 |
| SAC_FRONTOFFICE_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.39 | 249.40 | 636.87 | 1.00 | 1.94 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
| FRONTSTAIRSFLR1 UNITHEATER FAN | Fan:ConstantVolume | 0.54 | 340.63 | 0.03 | 17.18 | 635.51 | 1.00 | 10.50 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
| REARSTAIRSFLR2 UNITHEATER FAN | Fan:ConstantVolume | 0.54 | 340.63 | 0.01 | 3.89 | 635.51 | 1.00 | 41.46 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 |
| CORRIDORFLR2 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.30 | 189.92 | 636.87 | 1.00 | 2.15 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 |
| 201 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.09 | 54.42 | 636.87 | 1.00 | 4.21 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:40:00 |
| 202_205 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.41 | 260.34 | 636.87 | 1.00 | 1.91 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 |
| 206_208 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.32 | 206.96 | 636.87 | 1.00 | 2.08 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 |
| 209_212 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.40 | 252.47 | 636.87 | 1.00 | 1.93 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 |
| 213 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.11 | 70.63 | 636.87 | 1.00 | 3.56 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 |
| 214 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.14 | 91.44 | 636.87 | 1.00 | 3.05 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
| 215_218 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 1.15 | 732.00 | 636.87 | 1.00 | 1.47 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
| 219 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.61 | 389.99 | 636.87 | 1.00 | 1.69 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
| 220_223 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.49 | 312.19 | 636.87 | 1.00 | 1.81 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
| 224 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.14 | 89.98 | 636.87 | 1.00 | 3.08 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
| FRONTSTAIRSFLR2 UNITHEATER FAN | Fan:ConstantVolume | 0.54 | 340.63 | 0.02 | 15.51 | 635.51 | 1.00 | 11.48 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 |
| REARSTAIRSFLR3 UNITHEATER FAN | Fan:ConstantVolume | 0.54 | 340.63 | 0.01 | 3.89 | 635.51 | 1.00 | 41.46 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 |
| CORRIDORFLR3 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.22 | 138.08 | 636.87 | 1.00 | 2.47 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 |
| 301 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.09 | 57.80 | 636.87 | 1.00 | 4.04 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 |
| 302_305 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.22 | 138.07 | 636.87 | 1.00 | 2.47 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 |
| 306_308 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.17 | 105.97 | 636.87 | 1.00 | 2.82 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 |
| 309_312 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.38 | 244.48 | 636.87 | 1.00 | 1.96 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 |
| 313 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.10 | 64.95 | 636.87 | 1.00 | 3.75 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 |
| 314 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 83.43 | 636.87 | 1.00 | 3.22 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
| 315_318 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.54 | 345.94 | 636.87 | 1.00 | 1.75 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
| 319 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.12 | 76.33 | 636.87 | 1.00 | 3.39 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
| 320_323 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.46 | 294.56 | 636.87 | 1.00 | 1.84 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
| 324 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.08 | 52.91 | 636.87 | 1.00 | 4.29 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 |
| FRONTSTAIRSFLR3 UNITHEATER FAN | Fan:ConstantVolume | 0.54 | 340.63 | 0.03 | 19.31 | 635.51 | 1.00 | 9.50 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 |
| REARSTAIRSFLR4 UNITHEATER FAN | Fan:ConstantVolume | 0.54 | 340.63 | 0.02 | 13.88 | 635.51 | 1.00 | 12.66 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 |
| CORRIDORFLR4 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.36 | 230.19 | 636.87 | 1.00 | 2.00 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 |
| 401 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 85.81 | 636.87 | 1.00 | 3.17 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 |
| 402_405 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.33 | 209.97 | 636.87 | 1.00 | 2.07 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
| 406_408 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.26 | 165.43 | 636.87 | 1.00 | 2.28 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
| 409_412 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.50 | 316.19 | 636.87 | 1.00 | 1.80 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 |
| 413 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.14 | 87.53 | 636.87 | 1.00 | 3.13 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 |
| 414 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.13 | 83.11 | 636.87 | 1.00 | 3.22 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
| 415_418 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.62 | 392.56 | 636.87 | 1.00 | 1.69 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
| 419 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.17 | 105.72 | 636.87 | 1.00 | 2.82 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
| 420_423 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.61 | 386.99 | 636.87 | 1.00 | 1.70 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
| 424 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.52 | 331.17 | 0.17 | 107.98 | 636.87 | 1.00 | 2.79 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
| FRONTSTAIRSFLR4 UNITHEATER FAN | Fan:ConstantVolume | 0.54 | 340.63 | 0.05 | 31.15 | 635.51 | 1.00 | 6.43 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.002549 | 767.60 | 301156.09 | 0.90 | General |
| SWHSYSSHOWER PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000180 | 8.11 | 45084.46 | 0.85 | General |
| SWHSYSLAUNDRY PUMP | Pump:ConstantSpeed | Intermittent | 0.00 | 0.000129 | 0.00 | 0.00 | 0.30 | General |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| SWH SHOWER WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 10.69 | 0.44 |
| SWH LAUNDRY WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 14.75 | 0.47 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 0.00 | 27.19 | 0.01337 | 28.22 | 0.01336 | 0.006 | 0.00 |
| CORRIDORFLR1 | 18841.15 | 21667.32 | 143.96 | 1.418 | 1.630 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 23.89 | 23.88 | 0.00962 | 28.07 | 0.01336 | 0.046 | 0.00 |
| FRONTLOUNGEFLR1 | 9021.88 | 10375.16 | 63.63 | 0.679 | 0.781 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 23.89 | 23.88 | 0.00962 | 30.02 | 0.01337 | 0.236 | 0.00 |
| RESTROOMFLR1 | 769.44 | 884.86 | 27.13 | 0.058 | 0.067 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 23.89 | 23.89 | 0.00870 | 29.25 | 0.01337 | 0.000 | 0.00 |
| MEETINGROOMFLR1 | 4366.80 | 5021.82 | 62.56 | 0.329 | 0.378 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 23.89 | 23.87 | 0.01066 | 30.30 | 0.01337 | 0.126 | 0.00 |
| MECHANICALROOMFLR1 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | N/A | N/A | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM101 | 779.28 | 896.17 | 27.48 | 0.059 | 0.067 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 21.11 | 21.11 | 0.00810 | 30.02 | 0.01337 | 0.013 | 0.00 |
| GUESTROOM102 | 581.35 | 668.55 | 20.50 | 0.044 | 0.050 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 21.11 | 21.11 | 0.00813 | 30.02 | 0.01337 | 0.013 | 0.00 |
| GUESTROOM103 | 1264.87 | 1454.60 | 44.60 | 0.095 | 0.109 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 21.11 | 21.11 | 0.00831 | 26.91 | 0.01336 | 0.013 | 0.00 |
| GUESTROOM104 | 1528.99 | 1758.34 | 53.92 | 0.115 | 0.132 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 21.11 | 21.11 | 0.00826 | 30.30 | 0.01337 | 0.013 | 0.00 |
| GUESTROOM105 | 2041.67 | 2347.92 | 72.00 | 0.154 | 0.177 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00819 | 30.30 | 0.01337 | 0.013 | 0.00 |
| EMPLOYEELOUNGEFLR1 | 7772.32 | 8938.16 | 274.10 | 0.585 | 0.673 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 23.89 | 23.88 | 0.00863 | 30.30 | 0.01337 | 0.051 | 0.00 |
| EXERCISECENTERFLR1 | 1574.09 | 1810.20 | 55.51 | 0.118 | 0.136 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 23.89 | 23.88 | 0.00924 | 29.00 | 0.01336 | 0.043 | 0.00 |
| FRONTOFFICEFLR1 | 4528.24 | 5207.47 | 39.92 | 0.341 | 0.392 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 23.89 | 23.89 | 0.00866 | 30.30 | 0.01337 | 0.056 | 0.00 |
| FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 0.00 | 28.65 | 0.01337 | 30.30 | 0.01337 | 0.006 | 0.00 |
| REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 0.00 | 28.25 | 0.01336 | 27.84 | 0.01336 | 0.006 | 0.00 |
| CORRIDORFLR2 | 3448.56 | 3965.85 | 31.62 | 0.259 | 0.298 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | 23.89 | 23.89 | 0.00867 | 29.49 | 0.01337 | 0.038 | 0.00 |
| GUESTROOM201 | 831.87 | 956.65 | 29.34 | 0.063 | 0.072 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:40:00 | 21.11 | 21.11 | 0.00829 | 29.59 | 0.01337 | 0.013 | 0.00 |
| GUESTROOM202_205 | 4727.35 | 5436.45 | 41.68 | 0.355 | 0.409 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 21.11 | 21.11 | 0.00833 | 26.91 | 0.01336 | 0.054 | 0.00 |
| GUESTROOM206_208 | 3758.10 | 4321.82 | 41.02 | 0.283 | 0.325 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 21.11 | 21.11 | 0.00832 | 26.91 | 0.01336 | 0.043 | 0.00 |
| GUESTROOM209_212 | 4584.47 | 5272.14 | 40.42 | 0.345 | 0.396 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 21.11 | 21.11 | 0.00834 | 26.91 | 0.01336 | 0.054 | 0.00 |
| GUESTROOM213 | 1282.50 | 1474.87 | 45.23 | 0.096 | 0.111 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 21.11 | 21.11 | 0.00831 | 26.91 | 0.01336 | 0.013 | 0.00 |
| GUESTROOM214 | 1660.35 | 1909.41 | 58.55 | 0.125 | 0.144 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21.11 | 21.11 | 0.00824 | 30.30 | 0.01337 | 0.013 | 0.00 |
| GUESTROOM215_218 | 13293.30 | 15287.30 | 117.20 | 0.999 | 1.149 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 21.11 | 21.11 | 0.00802 | 30.22 | 0.01337 | 0.054 | 0.00 |
| GUESTROOM219 | 7081.80 | 8144.08 | 249.75 | 0.532 | 0.612 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 21.11 | 21.11 | 0.00806 | 30.22 | 0.01337 | 0.013 | 0.00 |
| GUESTROOM220_223 | 5668.90 | 6519.24 | 49.98 | 0.426 | 0.490 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 21.11 | 21.11 | 0.00828 | 30.22 | 0.01337 | 0.054 | 0.00 |
| GUESTROOM224 | 1633.84 | 1878.92 | 57.62 | 0.123 | 0.141 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21.11 | 21.11 | 0.00824 | 30.30 | 0.01337 | 0.013 | 0.00 |
| FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 29.49 | 0.01337 | 30.21 | 0.01337 | 0.006 | 0.00 |
| REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | 0.00 | 28.35 | 0.01336 | 27.84 | 0.01336 | 0.006 | 0.00 |
| CORRIDORFLR3 | 1787.66 | 2055.81 | 16.39 | 0.134 | 0.155 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | 23.89 | 23.89 | 0.00928 | 29.25 | 0.01337 | 0.038 | 0.00 |
| GUESTROOM301 | 586.74 | 674.75 | 20.69 | 0.044 | 0.051 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 21.11 | 21.11 | 0.00844 | 29.91 | 0.01337 | 0.013 | 0.00 |
| GUESTROOM302_305 | 1755.71 | 2019.07 | 15.48 | 0.132 | 0.152 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 21.11 | 21.11 | 0.00820 | 27.14 | 0.01336 | 0.054 | 0.00 |
| GUESTROOM306_308 | 1445.87 | 1662.75 | 15.78 | 0.109 | 0.125 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 21.11 | 21.11 | 0.00820 | 27.14 | 0.01336 | 0.043 | 0.00 |
| GUESTROOM309_312 | 4439.26 | 5105.15 | 39.14 | 0.334 | 0.384 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 21.11 | 21.11 | 0.00836 | 27.14 | 0.01336 | 0.054 | 0.00 |
| GUESTROOM313 | 701.90 | 807.19 | 24.75 | 0.053 | 0.061 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 21.11 | 21.11 | 0.00813 | 26.91 | 0.01336 | 0.013 | 0.00 |
| GUESTROOM314 | 1514.97 | 1742.22 | 53.43 | 0.114 | 0.131 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00827 | 30.30 | 0.01337 | 0.013 | 0.00 |
| GUESTROOM315_318 | 6281.71 | 7223.97 | 55.38 | 0.472 | 0.543 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21.11 | 21.11 | 0.00826 | 30.30 | 0.01337 | 0.054 | 0.00 |
| GUESTROOM319 | 1386.12 | 1594.04 | 48.88 | 0.104 | 0.120 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21.11 | 21.11 | 0.00806 | 30.30 | 0.01337 | 0.013 | 0.00 |
| GUESTROOM320_323 | 5348.63 | 6150.93 | 47.16 | 0.402 | 0.463 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21.11 | 21.11 | 0.00830 | 30.30 | 0.01337 | 0.054 | 0.00 |
| GUESTROOM324 | 950.19 | 1092.71 | 33.51 | 0.071 | 0.082 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | 21.11 | 21.11 | 0.00809 | 30.30 | 0.01337 | 0.013 | 0.00 |
| FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | 0.00 | 29.59 | 0.01337 | 30.02 | 0.01337 | 0.006 | 0.00 |
| REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 0.00 | 29.66 | 0.01337 | 29.00 | 0.01336 | 0.006 | 0.00 |
| CORRIDORFLR4 | 2951.06 | 3393.72 | 27.06 | 0.222 | 0.255 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 23.89 | 23.89 | 0.00880 | 30.30 | 0.01337 | 0.038 | 0.00 |
| GUESTROOM401 | 1558.06 | 1791.77 | 54.94 | 0.117 | 0.135 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 21.11 | 21.11 | 0.00838 | 29.99 | 0.01337 | 0.013 | 0.00 |
| GUESTROOM402_405 | 2693.46 | 3097.48 | 23.75 | 0.203 | 0.233 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00814 | 30.30 | 0.01337 | 0.054 | 0.00 |
| GUESTROOM406_408 | 2189.75 | 2518.21 | 23.90 | 0.165 | 0.189 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00814 | 30.30 | 0.01337 | 0.043 | 0.00 |
| GUESTROOM409_412 | 5741.40 | 6602.61 | 50.62 | 0.432 | 0.496 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | 21.11 | 21.11 | 0.00828 | 30.30 | 0.01337 | 0.054 | 0.00 |
| GUESTROOM413 | 989.11 | 1137.48 | 34.88 | 0.074 | 0.086 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 21.11 | 21.11 | 0.00810 | 30.30 | 0.01337 | 0.013 | 0.00 |
| GUESTROOM414 | 1322.28 | 1520.63 | 46.63 | 0.099 | 0.114 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21.11 | 21.11 | 0.00807 | 30.30 | 0.01337 | 0.013 | 0.00 |
| GUESTROOM415_418 | 7128.24 | 8197.48 | 62.85 | 0.536 | 0.616 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00823 | 30.14 | 0.01337 | 0.054 | 0.00 |
| GUESTROOM419 | 1919.78 | 2207.74 | 67.70 | 0.144 | 0.166 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 21.11 | 21.11 | 0.00821 | 30.22 | 0.01337 | 0.013 | 0.00 |
| GUESTROOM420_423 | 7027.07 | 8081.13 | 61.95 | 0.528 | 0.608 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 21.11 | 21.11 | 0.00823 | 30.14 | 0.01337 | 0.054 | 0.00 |
| GUESTROOM424 | 1960.77 | 2254.88 | 69.15 | 0.147 | 0.170 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21.11 | 21.11 | 0.00821 | 30.30 | 0.01337 | 0.013 | 0.00 |
| FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.000 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 0.00 | 31.71 | 0.01337 | 30.21 | 0.01337 | 0.006 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| REARSTAIRSFLR1 | 13.52 | 16.90 | 0.84 | 0.001 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7.20 | 7.20 | 0.00144 | -16.30 | 0.00092 | 0.006 | 0.00 |
| CORRIDORFLR1 | 32507.83 | 40634.79 | 269.99 | 2.440 | 3.050 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.11 | 21.09 | 0.00645 | -16.30 | 0.00092 | 0.046 | 0.00 |
| FRONTLOUNGEFLR1 | 3268.92 | 4086.15 | 25.06 | 0.246 | 0.307 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00777 | -16.30 | 0.00092 | 0.236 | 0.00 |
| RESTROOMFLR1 | 431.27 | 539.09 | 16.53 | 0.032 | 0.041 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 19:10:00 | 21.11 | 21.11 | 0.00775 | -16.30 | 0.00092 | 0.000 | 0.00 |
| MEETINGROOMFLR1 | 1550.19 | 1937.74 | 24.14 | 0.117 | 0.146 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 21.11 | 21.11 | 0.00783 | -16.30 | 0.00092 | 0.126 | 0.00 |
| MECHANICALROOMFLR1 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | N/A | N/A | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 | 0.0 |
| GUESTROOM101 | 612.91 | 766.14 | 23.49 | 0.046 | 0.058 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00782 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM102 | 666.43 | 833.04 | 25.54 | 0.050 | 0.063 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00784 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM103 | 1129.15 | 1411.44 | 43.28 | 0.085 | 0.106 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00790 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM104 | 1166.61 | 1458.26 | 44.72 | 0.088 | 0.110 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00791 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM105 | 677.99 | 847.49 | 25.99 | 0.051 | 0.064 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00784 | -16.30 | 0.00092 | 0.013 | 0.00 |
| EMPLOYEELOUNGEFLR1 | 686.73 | 858.41 | 26.32 | 0.052 | 0.065 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00784 | -16.30 | 0.00092 | 0.051 | 0.00 |
| EXERCISECENTERFLR1 | 574.09 | 717.62 | 22.01 | 0.043 | 0.054 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 21.11 | 21.11 | 0.00781 | -16.30 | 0.00092 | 0.043 | 0.00 |
| FRONTOFFICEFLR1 | 2688.46 | 3360.57 | 25.76 | 0.202 | 0.253 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | 21.11 | 21.11 | 0.00784 | -16.30 | 0.00092 | 0.056 | 0.00 |
| FRONTSTAIRSFLR1 | 287.81 | 359.76 | 17.93 | 0.022 | 0.027 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7.20 | 7.20 | 0.00537 | -16.30 | 0.00092 | 0.006 | 0.00 |
| REARSTAIRSFLR2 | 6.82 | 8.53 | 0.42 | 0.001 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7.20 | 7.20 | 0.00119 | -16.30 | 0.00092 | 0.006 | 0.00 |
| CORRIDORFLR2 | 1984.94 | 2481.18 | 19.78 | 0.149 | 0.187 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 16:30:00 | 21.11 | 21.11 | 0.00763 | -16.30 | 0.00092 | 0.038 | 0.00 |
| GUESTROOM201 | 909.24 | 1136.55 | 34.85 | 0.068 | 0.085 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00763 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM202_205 | 2131.00 | 2663.75 | 20.42 | 0.160 | 0.200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00779 | -16.30 | 0.00092 | 0.054 | 0.00 |
| GUESTROOM206_208 | 1577.59 | 1971.99 | 18.72 | 0.119 | 0.148 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 21.11 | 21.11 | 0.00777 | -16.30 | 0.00092 | 0.043 | 0.00 |
| GUESTROOM209_212 | 2067.06 | 2583.82 | 19.81 | 0.155 | 0.194 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00778 | -16.30 | 0.00092 | 0.054 | 0.00 |
| GUESTROOM213 | 1009.39 | 1261.74 | 38.69 | 0.076 | 0.095 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00789 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM214 | 1008.62 | 1260.77 | 38.66 | 0.076 | 0.095 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00789 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM215_218 | 2123.12 | 2653.90 | 20.35 | 0.160 | 0.200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00779 | -16.30 | 0.00092 | 0.054 | 0.00 |
| GUESTROOM219 | 545.84 | 682.30 | 20.92 | 0.041 | 0.051 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00779 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM220_223 | 2079.52 | 2599.40 | 19.93 | 0.156 | 0.195 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | 21.11 | 21.11 | 0.00778 | -16.30 | 0.00092 | 0.054 | 0.00 |
| GUESTROOM224 | 828.01 | 1035.01 | 31.74 | 0.062 | 0.078 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 21.11 | 21.11 | 0.00786 | -16.30 | 0.00092 | 0.013 | 0.00 |
| FRONTSTAIRSFLR2 | 259.83 | 324.78 | 16.18 | 0.020 | 0.024 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 7.20 | 7.20 | 0.00515 | -16.30 | 0.00092 | 0.006 | 0.00 |
| REARSTAIRSFLR3 | 60.05 | 75.06 | 3.74 | 0.005 | 0.006 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 7.20 | 7.20 | 0.00260 | -16.30 | 0.00092 | 0.006 | 0.00 |
| CORRIDORFLR3 | 2307.20 | 2884.01 | 22.99 | 0.173 | 0.217 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00764 | -16.30 | 0.00092 | 0.038 | 0.00 |
| GUESTROOM301 | 965.73 | 1207.16 | 37.02 | 0.073 | 0.091 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00762 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM302_305 | 2306.85 | 2883.56 | 22.11 | 0.173 | 0.217 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00779 | -16.30 | 0.00092 | 0.054 | 0.00 |
| GUESTROOM306_308 | 1770.65 | 2213.31 | 21.01 | 0.133 | 0.166 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:10:00 | 21.11 | 21.11 | 0.00777 | -16.30 | 0.00092 | 0.043 | 0.00 |
| GUESTROOM309_312 | 2315.14 | 2893.93 | 22.19 | 0.174 | 0.218 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00779 | -16.30 | 0.00092 | 0.054 | 0.00 |
| GUESTROOM313 | 1085.27 | 1356.59 | 41.60 | 0.082 | 0.102 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00788 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM314 | 1051.80 | 1314.75 | 40.32 | 0.079 | 0.099 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00788 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM315_318 | 2314.76 | 2893.45 | 22.18 | 0.174 | 0.218 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00779 | -16.30 | 0.00092 | 0.054 | 0.00 |
| GUESTROOM319 | 647.52 | 809.41 | 24.82 | 0.049 | 0.061 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 21.11 | 21.11 | 0.00781 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM320_323 | 2278.06 | 2847.57 | 21.83 | 0.171 | 0.214 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:20:00 | 21.11 | 21.11 | 0.00778 | -16.30 | 0.00092 | 0.054 | 0.00 |
| GUESTROOM324 | 883.97 | 1104.97 | 33.89 | 0.066 | 0.083 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00786 | -16.30 | 0.00092 | 0.013 | 0.00 |
| FRONTSTAIRSFLR3 | 323.44 | 404.29 | 20.15 | 0.024 | 0.030 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 7.20 | 7.20 | 0.00535 | -16.30 | 0.00092 | 0.006 | 0.00 |
| REARSTAIRSFLR4 | 232.45 | 290.56 | 14.48 | 0.017 | 0.022 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 7.20 | 7.20 | 0.00466 | -16.30 | 0.00092 | 0.006 | 0.00 |
| CORRIDORFLR4 | 3846.19 | 4807.73 | 38.33 | 0.289 | 0.361 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00777 | -16.30 | 0.00092 | 0.038 | 0.00 |
| GUESTROOM401 | 1309.37 | 1636.71 | 50.19 | 0.098 | 0.123 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00769 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM402_405 | 3508.30 | 4385.38 | 33.62 | 0.264 | 0.330 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00785 | -16.30 | 0.00092 | 0.054 | 0.00 |
| GUESTROOM406_408 | 2764.13 | 3455.17 | 32.79 | 0.208 | 0.260 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00784 | -16.30 | 0.00092 | 0.043 | 0.00 |
| GUESTROOM409_412 | 3529.68 | 4412.10 | 33.82 | 0.265 | 0.332 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00785 | -16.30 | 0.00092 | 0.054 | 0.00 |
| GUESTROOM413 | 1462.45 | 1828.06 | 56.06 | 0.110 | 0.137 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00791 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM414 | 1388.69 | 1735.87 | 53.23 | 0.104 | 0.131 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00790 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM415_418 | 3517.62 | 4397.03 | 33.71 | 0.264 | 0.331 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00785 | -16.30 | 0.00092 | 0.054 | 0.00 |
| GUESTROOM419 | 1031.52 | 1289.40 | 39.54 | 0.078 | 0.097 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00787 | -16.30 | 0.00092 | 0.013 | 0.00 |
| GUESTROOM420_423 | 3481.01 | 4351.27 | 33.36 | 0.262 | 0.327 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00785 | -16.30 | 0.00092 | 0.054 | 0.00 |
| GUESTROOM424 | 1249.11 | 1561.39 | 47.88 | 0.094 | 0.117 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 21.11 | 21.11 | 0.00789 | -16.30 | 0.00092 | 0.013 | 0.00 |
| FRONTSTAIRSFLR4 | 521.75 | 652.19 | 32.50 | 0.039 | 0.049 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 7.20 | 7.20 | 0.00598 | -16.30 | 0.00092 | 0.006 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| None |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| REARSTAIRSFLR1 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | REARSTAIRSFLR1 UNIT HEATER | 81.375 | 81.375 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 81.38 | 81.38 | 0.006118 | 7.20 | 0.68 | 0.00144192 | 18.31 | 13.58 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 7.20 | 0.00144192 | 22.4896 | 16.90 | 0.00 | -999.00 | -999.00 |
| CORRIDORFLR1 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR1 PTAC | 42709.156 | 42709.156 | 3.050128 | 0.00037364 | 1073.088 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 42709.16 | 42709.16 | 3.050128 | 20.52 | 12.89 | 0.00636790 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 1.5040 | 21.09 | 0.00645103 | 40.5390 | 40634.79 | 0.00 | 48254.70 | 48254.70 |
| CORRIDORFLR1 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR1 PTAC | 57197.488 | 45789.083 | 3.050128 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | unknown | 7/21 18:00:00 | 57030.13 | 43350.99 | 3.050128 | 23.99 | 17.16 | 0.00972892 | 12.25 | 11.14 | 0.00800000 | 28.07 | 0.01336300 | 21.18 | 1.5040 | 23.88 | 0.00962370 | 50.7914 | 21667.32 | 0.00 | 57225.49 | 45167.42 |
| SAC_FRONTLOUNGE HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_FRONTLOUNGE | 20956.114 | 20956.114 | 0.780683 | 0.00018333 | 477.980 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 20956.11 | 20956.11 | 0.780683 | 9.80 | 7.54 | 0.00569651 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 30.2393 | 21.11 | 0.00776521 | 48.6258 | 4086.15 | 0.00 | 20148.00 | 20148.00 |
| SAC_FRONTLOUNGE PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_FRONTLOUNGE | 17965.837 | 13033.490 | 0.780683 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | 7/21 15:30:00 | 18373.42 | 12704.64 | 0.780683 | 25.74 | 18.55 | 0.01075284 | 12.25 | 11.14 | 0.00800000 | 30.02 | 0.01336647 | 21.75 | 30.2393 | 23.88 | 0.00961990 | 50.7597 | 10375.16 | 0.00 | 17974.63 | 12883.94 |
| SAC_RESTROOM HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_RESTROOM | 885.006 | 885.006 | 0.066536 | 0.00000774 | 22.365 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 19:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 19:10:00 | 885.01 | 885.01 | 0.066536 | 21.11 | 14.42 | 0.00774912 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.11 | 0.00774912 | 48.5257 | 539.09 | 0.00 | 1009.58 | 1009.58 |
| SAC_RESTROOM PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_RESTROOM | 1101.413 | 881.852 | 0.066536 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 1052.44 | 931.98 | 0.066536 | 23.89 | 16.26 | 0.00870273 | 12.25 | 11.14 | 0.00800000 | 29.25 | 0.01336509 | 21.53 | 0.0000 | 23.89 | 0.00870273 | 45.9662 | 884.86 | 0.00 | 1101.95 | 869.54 |
| SAC_MEETINGROOM HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_MEETINGROOM | 10689.705 | 10689.705 | 0.378047 | 0.00009352 | 241.605 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | 10689.71 | 10689.71 | 0.378047 | 8.60 | 6.76 | 0.00551823 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 33.4390 | 21.11 | 0.00782623 | 49.0027 | 1937.74 | 0.00 | 10109.37 | 10109.37 |
| SAC_MEETINGROOM PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_MEETINGROOM | 9387.814 | 6581.639 | 0.378047 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 9807.47 | 6255.83 | 0.378047 | 26.02 | 19.26 | 0.01156695 | 12.25 | 11.14 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 33.4390 | 23.87 | 0.01066266 | 56.1867 | 5021.82 | 0.00 | 9392.41 | 6511.26 |
| MECHRM UNITHEATER HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | MECHANICALROOMFLR1 UNIT HEATER | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 0.00 | 0.00 | -999.0 | 7.20 | 7.20 | 0.00800000 | 18.31 | 13.58 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | -999.0000 | 7.20 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 |
| 101 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 101 PTAC | 1499.883 | 1499.883 | 0.067379 | 0.00001312 | 35.291 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1499.88 | 1499.88 | 0.067379 | 13.63 | 10.11 | 0.00644169 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 20.0058 | 21.11 | 0.00782159 | 48.9740 | 766.14 | 0.00 | 1523.06 | 1523.06 |
| 101 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 101 PTAC | 1354.401 | 1047.993 | 0.067379 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | 7/21 15:30:00 | 1284.19 | 1045.16 | 0.067379 | 22.89 | 16.30 | 0.00915321 | 9.47 | 9.47 | 0.00800000 | 30.02 | 0.01336647 | 21.75 | 20.0058 | 21.11 | 0.00809951 | 50.6914 | 896.17 | 0.00 | 1355.06 | 1034.32 |
| 102 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 102 PTAC | 1436.702 | 1436.702 | 0.062629 | 0.00001257 | 33.642 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1436.70 | 1436.70 | 0.062629 | 13.06 | 9.76 | 0.00634802 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 21.5231 | 21.11 | 0.00783559 | 49.0605 | 833.04 | 0.00 | 1446.85 | 1446.85 |
| 102 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 102 PTAC | 1351.878 | 1009.785 | 0.062629 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | 7/21 15:30:00 | 1304.75 | 1010.81 | 0.062629 | 23.50 | 16.83 | 0.00953634 | 9.47 | 9.47 | 0.00800000 | 30.02 | 0.01336647 | 21.75 | 21.5231 | 21.11 | 0.00813282 | 50.8972 | 668.55 | 0.00 | 1352.54 | 997.18 |
| 103 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 103 PTAC | 2058.445 | 2058.445 | 0.109373 | 0.00001801 | 49.688 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2058.45 | 2058.45 | 0.109373 | 16.50 | 11.94 | 0.00704203 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 12.3246 | 21.11 | 0.00790204 | 49.4713 | 1411.44 | 0.00 | 2182.29 | 2182.29 |
| 103 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 103 PTAC | 1954.161 | 1564.559 | 0.109373 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | unknown | 7/21 18:50:00 | 1884.67 | 1567.92 | 0.109373 | 21.82 | 15.73 | 0.00893281 | 9.47 | 9.47 | 0.00800000 | 26.91 | 0.01336094 | 20.84 | 12.3246 | 21.11 | 0.00831034 | 51.9963 | 1454.60 | 0.00 | 1955.12 | 1543.05 |
| 104 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 104 PTAC | 2362.175 | 2362.175 | 0.132211 | 0.00002067 | 57.448 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2362.17 | 2362.17 | 0.132211 | 17.30 | 12.41 | 0.00719343 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 10.1949 | 21.11 | 0.00790514 | 49.4904 | 1458.26 | 0.00 | 2535.25 | 2535.25 |
| 104 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 104 PTAC | 2432.316 | 1947.826 | 0.132211 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | unknown | 7/21 14:30:00 | 2251.78 | 1932.39 | 0.132211 | 22.05 | 15.67 | 0.00877781 | 9.47 | 9.47 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 10.1949 | 21.11 | 0.00825684 | 51.6658 | 1758.34 | 0.00 | 2433.51 | 1920.76 |
| 105 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 105 PTAC | 2951.824 | 2951.824 | 0.176542 | 0.00002582 | 72.455 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2951.82 | 2951.82 | 0.176542 | 18.25 | 12.91 | 0.00731044 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 7.6349 | 21.11 | 0.00783833 | 49.0775 | 847.49 | 0.00 | 3215.87 | 3215.87 |
| 105 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 105 PTAC | 3118.366 | 2496.410 | 0.176542 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 2863.08 | 2539.44 | 0.176542 | 21.81 | 15.42 | 0.00858782 | 9.47 | 9.47 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 7.6349 | 21.11 | 0.00819278 | 51.2701 | 2347.92 | 0.00 | 3119.89 | 2462.47 |
| SAC_EMPLOYEELOUNGE HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_EMPLOYEELOUNGE | 11247.006 | 11247.006 | 0.672673 | 0.00009839 | 276.068 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 11247.01 | 11247.01 | 0.672673 | 18.25 | 12.91 | 0.00731235 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 7.6341 | 21.11 | 0.00784034 | 49.0899 | 858.41 | 0.00 | 12253.14 | 12253.14 |
| SAC_EMPLOYEELOUNGE PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_EMPLOYEELOUNGE | 11942.525 | 9563.564 | 0.672673 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 11430.44 | 9717.73 | 0.672673 | 24.37 | 16.67 | 0.00899184 | 12.25 | 11.14 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 7.6341 | 23.88 | 0.00863023 | 45.6144 | 8938.16 | 0.00 | 11948.37 | 9432.85 |
| SAC_EXERCISECENTER HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_EXERCISECENTER | 3739.964 | 3739.964 | 0.136166 | 0.00003272 | 84.962 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | 3739.96 | 3739.96 | 0.136166 | 9.28 | 7.22 | 0.00563166 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 31.6303 | 21.11 | 0.00780956 | 48.8996 | 717.62 | 0.00 | 3569.94 | 3569.94 |
| SAC_EXERCISECENTER PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_EXERCISECENTER | 3011.230 | 2225.920 | 0.136166 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | 7/21 17:00:00 | 3088.22 | 2177.21 | 0.136166 | 25.50 | 18.31 | 0.01054250 | 12.25 | 11.14 | 0.00800000 | 29.00 | 0.01336465 | 21.45 | 31.6303 | 23.88 | 0.00923687 | 48.7574 | 1810.20 | 0.00 | 3012.70 | 2199.08 |
| SAC_FRONTOFFICE HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_FRONTOFFICE | 7731.006 | 7731.006 | 0.391600 | 0.00006763 | 185.308 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | 7731.01 | 7731.01 | 0.391600 | 15.73 | 11.42 | 0.00684270 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 14.3826 | 21.11 | 0.00783694 | 49.0689 | 3360.57 | 0.00 | 8100.58 | 8100.58 |
| SAC_FRONTOFFICE PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_FRONTOFFICE | 7443.650 | 5933.902 | 0.391600 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 7228.94 | 5878.66 | 0.391600 | 24.81 | 17.11 | 0.00933272 | 12.25 | 11.14 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 14.3826 | 23.89 | 0.00865502 | 45.7198 | 5207.47 | 0.00 | 7447.29 | 5853.28 |
| FRONTSTAIRSFLR1 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONTSTAIRSFLR1 UNIT HEATER | 359.760 | 359.760 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 359.76 | 359.76 | 0.027040 | 7.20 | 5.89 | 0.00536501 | 18.31 | 13.58 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 7.20 | 0.00536501 | 83.1714 | 359.76 | 0.00 | -999.00 | -999.00 |
| REARSTAIRSFLR2 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | REARSTAIRSFLR2 UNIT HEATER | 81.374 | 81.374 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 81.37 | 81.37 | 0.006118 | 7.20 | 0.32 | 0.00118884 | 18.31 | 13.58 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 7.20 | 0.00118884 | 18.5497 | 8.53 | 0.00 | -999.00 | -999.00 |
| CORRIDORFLR2 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR2 PTAC | 5678.686 | 5678.686 | 0.298218 | 0.00004968 | 136.856 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 16:30:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 16:30:00 | 5678.69 | 5678.69 | 0.298218 | 16.31 | 11.59 | 0.00676824 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 12.8189 | 21.11 | 0.00762755 | 47.7746 | 2481.18 | 0.00 | 6003.31 | 6003.31 |
| CORRIDORFLR2 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR2 PTAC | 5515.625 | 4412.811 | 0.298218 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | unknown | 7/21 16:20:00 | 5382.98 | 4406.29 | 0.298218 | 24.61 | 16.99 | 0.00926827 | 12.25 | 11.14 | 0.00800000 | 29.49 | 0.01336553 | 21.60 | 12.8189 | 23.89 | 0.00866582 | 45.7747 | 3965.85 | 0.00 | 5518.32 | 4352.80 |
| 201 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 201 PTAC | 1740.189 | 1740.189 | 0.085442 | 0.00001522 | 41.519 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 1740.19 | 1740.19 | 0.085442 | 15.21 | 10.92 | 0.00657224 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 15.7765 | 21.11 | 0.00763023 | 47.7921 | 1136.55 | 0.00 | 1809.08 | 1809.08 |
| 201 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 201 PTAC | 1711.210 | 1327.691 | 0.085442 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:40:00 | unknown | 7/21 12:40:00 | 1630.76 | 1305.44 | 0.085442 | 22.70 | 16.30 | 0.00923734 | 9.47 | 9.47 | 0.00800000 | 29.59 | 0.01336569 | 21.62 | 15.7765 | 21.11 | 0.00828526 | 51.8404 | 956.65 | 0.00 | 1712.05 | 1310.36 |
| 202_205 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 202_205 PTAC | 7851.967 | 7851.967 | 0.408786 | 0.00006869 | 188.979 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 7851.97 | 7851.97 | 0.408786 | 16.18 | 11.65 | 0.00688441 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 13.1901 | 21.11 | 0.00779003 | 48.7789 | 2663.75 | 0.00 | 8283.28 | 8283.28 |
| 202_205 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 202_205 PTAC | 7388.411 | 5916.092 | 0.408786 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | unknown | 7/21 18:50:00 | 7142.31 | 5878.89 | 0.408786 | 21.87 | 15.80 | 0.00899656 | 9.47 | 9.47 | 0.00800000 | 26.91 | 0.01336094 | 20.84 | 13.1901 | 21.11 | 0.00833343 | 52.1398 | 5436.45 | 0.00 | 7392.03 | 5833.65 |
| 206_208 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 206_208 PTAC | 6236.203 | 6236.203 | 0.324970 | 0.00005456 | 150.113 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 6236.20 | 6236.20 | 0.324970 | 16.19 | 11.64 | 0.00687111 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 13.1499 | 21.11 | 0.00777154 | 48.6647 | 1971.99 | 0.00 | 6580.27 | 6580.27 |
| 206_208 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 206_208 PTAC | 5861.347 | 4691.568 | 0.324970 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | unknown | 7/21 18:50:00 | 5663.75 | 4673.45 | 0.324970 | 21.87 | 15.79 | 0.00898243 | 9.47 | 9.47 | 0.00800000 | 26.91 | 0.01336094 | 20.84 | 13.1499 | 21.11 | 0.00831948 | 52.0534 | 4321.82 | 0.00 | 5864.22 | 4626.42 |
| 209_212 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 209_212 PTAC | 7687.660 | 7687.660 | 0.396430 | 0.00006726 | 184.764 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 7687.66 | 7687.66 | 0.396430 | 16.02 | 11.55 | 0.00685074 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 13.6012 | 21.11 | 0.00778374 | 48.7402 | 2583.82 | 0.00 | 8090.97 | 8090.97 |
| 209_212 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 209_212 PTAC | 7203.258 | 5769.392 | 0.396430 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | unknown | 7/21 18:50:00 | 6970.89 | 5709.98 | 0.396430 | 21.90 | 15.84 | 0.00902610 | 9.47 | 9.47 | 0.00800000 | 26.91 | 0.01336094 | 20.84 | 13.6012 | 21.11 | 0.00834369 | 52.2032 | 5272.14 | 0.00 | 7206.78 | 5690.75 |
| 213 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 213 PTAC | 2078.753 | 2078.753 | 0.110899 | 0.00001819 | 50.209 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2078.75 | 2078.75 | 0.110899 | 16.56 | 11.96 | 0.00704120 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 12.1550 | 21.11 | 0.00788761 | 49.3823 | 1261.74 | 0.00 | 2205.97 | 2205.97 |
| 213 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 213 PTAC | 1977.303 | 1582.516 | 0.110899 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | unknown | 7/21 18:50:00 | 1906.19 | 1588.75 | 0.110899 | 21.81 | 15.72 | 0.00892179 | 9.47 | 9.47 | 0.00800000 | 26.91 | 0.01336094 | 20.84 | 12.1550 | 21.11 | 0.00830755 | 51.9796 | 1474.87 | 0.00 | 1978.27 | 1560.83 |
| 214 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 214 PTAC | 2513.300 | 2513.300 | 0.143572 | 0.00002199 | 61.300 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2513.30 | 2513.30 | 0.143572 | 17.60 | 12.57 | 0.00723379 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 9.3882 | 21.11 | 0.00788752 | 49.3817 | 1260.77 | 0.00 | 2710.13 | 2710.13 |
| 214 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 214 PTAC | 2608.888 | 2089.524 | 0.143572 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | 7/21 14:00:00 | 2409.06 | 2087.86 | 0.143572 | 21.97 | 15.60 | 0.00871942 | 9.47 | 9.47 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 9.3882 | 21.11 | 0.00823789 | 51.5493 | 1909.41 | 0.00 | 2610.17 | 2061.04 |
| 215_218 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 215_218 PTAC | 17702.715 | 17702.715 | 1.149386 | 0.00015487 | 439.307 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 17702.71 | 17702.71 | 1.149386 | 19.36 | 13.49 | 0.00746724 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 4.6908 | 21.11 | 0.00778928 | 48.7744 | 2653.90 | 0.00 | 19626.62 | 19626.62 |
| 215_218 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 215_218 PTAC | 19026.413 | 15233.598 | 1.149386 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | 7/21 13:50:00 | 17269.72 | 16276.18 | 1.149386 | 21.54 | 15.05 | 0.00827490 | 9.47 | 9.47 | 0.00800000 | 30.22 | 0.01336682 | 21.81 | 4.6908 | 21.11 | 0.00802430 | 50.2268 | 15287.30 | 0.00 | 19035.73 | 15020.98 |
| 219 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 219 PTAC | 8748.722 | 8748.722 | 0.612359 | 0.00007654 | 219.183 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 8748.72 | 8748.72 | 0.612359 | 20.29 | 14.01 | 0.00764368 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 2.2011 | 21.11 | 0.00779492 | 48.8092 | 682.30 | 0.00 | 9846.49 | 9846.49 |
| 219 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 219 PTAC | 10136.720 | 8116.018 | 0.612359 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | 7/21 13:50:00 | 9148.24 | 8802.99 | 0.612359 | 21.31 | 14.87 | 0.00817307 | 9.47 | 9.47 | 0.00800000 | 30.22 | 0.01336682 | 21.81 | 2.2011 | 21.11 | 0.00805618 | 50.4261 | 8144.08 | 0.00 | 10141.68 | 8002.74 |
| 220_223 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 220_223 PTAC | 8934.777 | 8934.777 | 0.490203 | 0.00007817 | 216.686 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | 8934.78 | 8934.78 | 0.490203 | 17.00 | 12.13 | 0.00703037 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 10.9986 | 21.11 | 0.00778497 | 48.7478 | 2599.40 | 0.00 | 9544.87 | 9544.87 |
| 220_223 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 220_223 PTAC | 9117.955 | 7296.166 | 0.490203 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | 7/21 13:50:00 | 8470.02 | 7195.69 | 0.490203 | 22.11 | 15.75 | 0.00883798 | 9.47 | 9.47 | 0.00800000 | 30.22 | 0.01336682 | 21.81 | 10.9986 | 21.11 | 0.00827831 | 51.7994 | 6519.24 | 0.00 | 9122.42 | 7195.83 |
| 224 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 224 PTAC | 2482.808 | 2482.808 | 0.141280 | 0.00002172 | 60.524 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | 2482.81 | 2482.81 | 0.141280 | 17.54 | 12.52 | 0.00720141 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 9.5405 | 21.11 | 0.00786346 | 49.2330 | 1035.01 | 0.00 | 2674.87 | 2674.87 |
| 224 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 224 PTAC | 2573.363 | 2059.017 | 0.141280 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | 7/21 14:00:00 | 2377.43 | 2056.47 | 0.141280 | 21.99 | 15.61 | 0.00873070 | 9.47 | 9.47 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 9.5405 | 21.11 | 0.00824173 | 51.5730 | 1878.92 | 0.00 | 2574.62 | 2030.90 |
| FRONTSTAIRSFLR2 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONTSTAIRSFLR2 UNIT HEATER | 324.768 | 324.768 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 324.77 | 324.77 | 0.024410 | 7.20 | 5.62 | 0.00514720 | 18.31 | 13.58 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 7.20 | 0.00514720 | 79.8219 | 324.78 | 0.00 | -999.00 | -999.00 |
| REARSTAIRSFLR3 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | REARSTAIRSFLR3 UNIT HEATER | 81.382 | 81.382 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 81.38 | 81.38 | 0.006118 | 7.20 | 2.31 | 0.00259572 | 18.31 | 13.58 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 7.20 | 0.00259572 | 40.4135 | 75.06 | 0.00 | -999.00 | -999.00 |
| CORRIDORFLR3 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR3 PTAC | 4595.937 | 4595.937 | 0.216818 | 0.00004021 | 108.981 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 4595.94 | 4595.94 | 0.216818 | 14.51 | 10.51 | 0.00645975 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 17.6314 | 21.11 | 0.00764468 | 47.8804 | 2884.01 | 0.00 | 4728.59 | 4728.59 |
| CORRIDORFLR3 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR3 PTAC | 4633.663 | 3478.840 | 0.216818 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | 7/21 16:40:00 | 4693.31 | 3390.51 | 0.216818 | 25.21 | 18.02 | 0.01029085 | 12.25 | 11.14 | 0.00800000 | 29.25 | 0.01336509 | 21.53 | 17.6314 | 23.89 | 0.00928089 | 48.9764 | 2055.81 | 0.00 | 4635.93 | 3435.65 |
| 301 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 301 PTAC | 1810.793 | 1810.793 | 0.090749 | 0.00001584 | 43.338 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 1810.79 | 1810.79 | 0.090749 | 15.55 | 11.12 | 0.00662180 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 14.8539 | 21.11 | 0.00761577 | 47.7028 | 1207.16 | 0.00 | 1892.29 | 1892.29 |
| 301 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 301 PTAC | 1997.165 | 1478.984 | 0.090749 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | unknown | 7/21 13:10:00 | 1939.94 | 1456.83 | 0.090749 | 23.45 | 16.98 | 0.00974525 | 9.47 | 9.47 | 0.00800000 | 29.91 | 0.01336627 | 21.72 | 14.8539 | 21.11 | 0.00843508 | 52.7655 | 674.75 | 0.00 | 1998.14 | 1460.93 |
| 302_305 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 302_305 PTAC | 5298.198 | 5298.198 | 0.216789 | 0.00004635 | 122.783 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 5298.20 | 5298.20 | 0.216789 | 11.81 | 8.91 | 0.00607903 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 24.8717 | 21.11 | 0.00778561 | 48.7516 | 2883.56 | 0.00 | 5240.09 | 5240.09 |
| 302_305 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 302_305 PTAC | 4732.695 | 3520.079 | 0.216789 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | unknown | 7/21 18:40:00 | 4766.45 | 3423.94 | 0.216789 | 23.25 | 17.15 | 0.01003284 | 9.47 | 9.47 | 0.00800000 | 27.14 | 0.01336135 | 20.91 | 24.8717 | 21.11 | 0.00819939 | 51.3087 | 2019.07 | 0.00 | 4735.01 | 3477.05 |
| 306_308 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 306_308 PTAC | 4127.010 | 4127.010 | 0.166399 | 0.00003610 | 95.407 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:10:00 | 4127.01 | 4127.01 | 0.166399 | 11.50 | 8.70 | 0.00601543 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 25.6811 | 21.11 | 0.00777476 | 48.6845 | 2213.31 | 0.00 | 4064.16 | 4064.16 |
| 306_308 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 306_308 PTAC | 3594.104 | 2683.961 | 0.166399 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | unknown | 7/21 18:40:00 | 3609.63 | 2614.44 | 0.166399 | 23.17 | 17.07 | 0.00996132 | 9.47 | 9.47 | 0.00800000 | 27.14 | 0.01336135 | 20.91 | 25.6811 | 21.11 | 0.00819553 | 51.2849 | 1662.75 | 0.00 | 3595.86 | 2650.40 |
| 309_312 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 309_312 PTAC | 7520.639 | 7520.639 | 0.383875 | 0.00006579 | 180.475 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 7520.64 | 7520.64 | 0.383875 | 15.86 | 11.45 | 0.00682248 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 14.0460 | 21.11 | 0.00778635 | 48.7562 | 2893.93 | 0.00 | 7895.21 | 7895.21 |
| 309_312 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 309_312 PTAC | 7051.148 | 5643.250 | 0.383875 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | unknown | 7/21 18:40:00 | 6817.51 | 5552.22 | 0.383875 | 21.96 | 15.89 | 0.00906421 | 9.47 | 9.47 | 0.00800000 | 27.14 | 0.01336135 | 20.91 | 14.0460 | 21.11 | 0.00836200 | 52.3164 | 5105.15 | 0.00 | 7054.60 | 5565.11 |
| 313 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 313 PTAC | 1960.251 | 1960.251 | 0.101990 | 0.00001715 | 47.173 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 1960.25 | 1960.25 | 0.101990 | 16.17 | 11.72 | 0.00696450 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 13.2168 | 21.11 | 0.00788443 | 49.3627 | 1356.59 | 0.00 | 2067.61 | 2067.61 |
| 313 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 313 PTAC | 1966.476 | 1554.787 | 0.101990 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | unknown | 7/21 18:50:00 | 1927.69 | 1522.67 | 0.101990 | 22.40 | 16.24 | 0.00928885 | 9.47 | 9.47 | 0.00800000 | 26.91 | 0.01336094 | 20.84 | 13.2168 | 21.11 | 0.00812614 | 50.8561 | 807.19 | 0.00 | 1967.44 | 1533.67 |
| 314 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 314 PTAC | 2346.089 | 2346.089 | 0.131002 | 0.00002052 | 57.038 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 2346.09 | 2346.09 | 0.131002 | 17.26 | 12.37 | 0.00716504 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 10.2891 | 21.11 | 0.00788082 | 49.3402 | 1314.75 | 0.00 | 2516.61 | 2516.61 |
| 314 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 314 PTAC | 2415.533 | 1932.576 | 0.131002 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 2237.30 | 1915.66 | 0.131002 | 22.06 | 15.69 | 0.00879067 | 9.47 | 9.47 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 10.2891 | 21.11 | 0.00826581 | 51.7219 | 1742.22 | 0.00 | 2416.72 | 1905.65 |
| 315_318 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 315_318 PTAC | 9639.657 | 9639.657 | 0.543195 | 0.00008433 | 234.671 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 9639.66 | 9639.66 | 0.543195 | 17.40 | 12.36 | 0.00710520 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 9.9256 | 21.11 | 0.00778632 | 48.7563 | 2893.45 | 0.00 | 10362.10 | 10362.10 |
| 315_318 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 315_318 PTAC | 9959.937 | 7977.092 | 0.543195 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | 7/21 14:00:00 | 9214.21 | 7925.21 | 0.543195 | 22.02 | 15.65 | 0.00876377 | 9.47 | 9.47 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 9.9256 | 21.11 | 0.00825653 | 51.6650 | 7223.97 | 0.00 | 9964.81 | 7866.85 |
| 319 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 319 PTAC | 2197.756 | 2197.756 | 0.119849 | 0.00001923 | 53.253 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | 2197.76 | 2197.76 | 0.119849 | 16.90 | 12.09 | 0.00703417 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 11.2465 | 21.11 | 0.00780842 | 48.8928 | 809.41 | 0.00 | 2344.47 | 2344.47 |
| 319 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 319 PTAC | 2179.781 | 1745.178 | 0.119849 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | 7/21 14:00:00 | 2013.50 | 1767.50 | 0.119849 | 22.14 | 15.61 | 0.00866035 | 9.47 | 9.47 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 11.2465 | 21.11 | 0.00806394 | 50.4718 | 1594.04 | 0.00 | 2180.85 | 1721.37 |
| 320_323 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 320_323 PTAC | 8566.451 | 8566.451 | 0.462510 | 0.00007494 | 207.274 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:20:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:20:00 | 8566.45 | 8566.45 | 0.462510 | 16.75 | 11.98 | 0.00698344 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 11.6571 | 21.11 | 0.00778298 | 48.7356 | 2847.57 | 0.00 | 9116.71 | 9116.71 |
| 320_323 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 320_323 PTAC | 8705.611 | 6967.412 | 0.462510 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | 7/21 14:00:00 | 8098.64 | 6821.10 | 0.462510 | 22.18 | 15.82 | 0.00889136 | 9.47 | 9.47 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 11.6571 | 21.11 | 0.00830079 | 51.9383 | 6150.93 | 0.00 | 8709.87 | 6872.03 |
| 324 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 324 PTAC | 1708.584 | 1708.584 | 0.083073 | 0.00001495 | 40.700 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 1708.58 | 1708.58 | 0.083073 | 15.04 | 11.02 | 0.00673349 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 16.2253 | 21.11 | 0.00785864 | 49.2031 | 1104.97 | 0.00 | 1771.77 | 1771.77 |
| 324 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 324 PTAC | 1612.965 | 1271.740 | 0.083073 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | 7/21 14:10:00 | 1511.15 | 1265.38 | 0.083073 | 22.62 | 16.03 | 0.00895815 | 9.47 | 9.47 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 16.2253 | 21.11 | 0.00809287 | 50.6506 | 1092.71 | 0.00 | 1613.75 | 1254.68 |
| FRONTSTAIRSFLR3 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONTSTAIRSFLR3 UNIT HEATER | 404.270 | 404.270 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 404.27 | 404.27 | 0.030385 | 7.20 | 5.86 | 0.00534588 | 18.31 | 13.58 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 7.20 | 0.00534588 | 82.8798 | 404.29 | 0.00 | -999.00 | -999.00 |
| REARSTAIRSFLR4 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | REARSTAIRSFLR4 UNIT HEATER | 290.543 | 290.543 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 290.54 | 290.54 | 0.021838 | 7.20 | 5.01 | 0.00465848 | 18.31 | 13.58 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 7.20 | 0.00465848 | 72.2989 | 290.56 | 0.00 | -999.00 | -999.00 |
| CORRIDORFLR4 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR4 PTAC | 6519.649 | 6519.649 | 0.361442 | 0.00005704 | 158.351 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 6519.65 | 6519.65 | 0.361442 | 17.15 | 12.20 | 0.00704369 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 10.5765 | 21.11 | 0.00776748 | 48.6401 | 4807.73 | 0.00 | 6981.84 | 6981.84 |
| CORRIDORFLR4 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR4 PTAC | 7018.703 | 5533.621 | 0.361442 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | unknown | 7/21 14:50:00 | 6848.50 | 5453.69 | 0.361442 | 24.85 | 17.25 | 0.00948787 | 12.25 | 11.14 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 10.5765 | 23.89 | 0.00880441 | 46.4968 | 3393.72 | 0.00 | 7022.14 | 5459.38 |
| 401 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 401 PTAC | 2395.887 | 2395.887 | 0.134734 | 0.00002096 | 58.311 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 2395.89 | 2395.89 | 0.134734 | 17.37 | 12.26 | 0.00701570 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 10.0047 | 21.11 | 0.00769290 | 48.1802 | 1636.71 | 0.00 | 2574.24 | 2574.24 |
| 401 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 401 PTAC | 2498.503 | 1999.286 | 0.134734 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | unknown | 7/21 13:20:00 | 2326.87 | 1959.32 | 0.134734 | 22.00 | 15.74 | 0.00887913 | 9.47 | 9.47 | 0.00800000 | 29.99 | 0.01336641 | 21.74 | 10.0047 | 21.11 | 0.00838028 | 52.4305 | 1791.77 | 0.00 | 2499.73 | 1971.96 |
| 402_405 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 402_405 PTAC | 6800.005 | 6800.005 | 0.329696 | 0.00005949 | 161.915 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 6800.00 | 6800.00 | 0.329696 | 14.99 | 10.98 | 0.00671533 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 16.3542 | 21.11 | 0.00784761 | 49.1350 | 4385.38 | 0.00 | 7046.36 | 7046.36 |
| 402_405 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 402_405 PTAC | 6912.987 | 5241.809 | 0.329696 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 6596.38 | 5232.62 | 0.329696 | 23.24 | 16.58 | 0.00934986 | 9.47 | 9.47 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 16.3542 | 21.11 | 0.00813960 | 50.9395 | 3097.48 | 0.00 | 6916.37 | 5176.00 |
| 406_408 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 406_408 PTAC | 5368.857 | 5368.857 | 0.259762 | 0.00004697 | 127.797 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 5368.86 | 5368.86 | 0.259762 | 14.96 | 10.95 | 0.00670550 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 16.4508 | 21.11 | 0.00784386 | 49.1119 | 3455.17 | 0.00 | 5560.35 | 5560.35 |
| 406_408 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 406_408 PTAC | 5414.232 | 4114.774 | 0.259762 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 5158.55 | 4108.22 | 0.259762 | 23.18 | 16.54 | 0.00931874 | 9.47 | 9.47 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 16.4508 | 21.11 | 0.00813872 | 50.9340 | 2518.21 | 0.00 | 5416.88 | 4062.54 |
| 409_412 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 409_412 PTAC | 9018.344 | 9018.344 | 0.496474 | 0.00007890 | 218.814 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 9018.34 | 9018.34 | 0.496474 | 17.05 | 12.21 | 0.00709649 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 10.8604 | 21.11 | 0.00784851 | 49.1406 | 4412.10 | 0.00 | 9641.85 | 9641.85 |
| 409_412 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 409_412 PTAC | 9239.097 | 7391.632 | 0.496474 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | 7/21 14:20:00 | 8573.99 | 7285.50 | 0.496474 | 22.11 | 15.75 | 0.00883655 | 9.47 | 9.47 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 10.8604 | 21.11 | 0.00828458 | 51.8383 | 6602.61 | 0.00 | 9243.62 | 7289.90 |
| 413 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 413 PTAC | 2431.720 | 2431.720 | 0.137436 | 0.00002127 | 59.221 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 2431.72 | 2431.72 | 0.137436 | 17.44 | 12.50 | 0.00722285 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 9.8080 | 21.11 | 0.00790781 | 49.5071 | 1828.06 | 0.00 | 2615.76 | 2615.76 |
| 413 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 413 PTAC | 2649.593 | 2094.993 | 0.137436 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | 7/21 15:00:00 | 2478.37 | 2084.97 | 0.137436 | 22.56 | 15.99 | 0.00892635 | 9.47 | 9.47 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 9.8080 | 21.11 | 0.00809548 | 50.6667 | 1137.48 | 0.00 | 2650.89 | 2066.55 |
| 414 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 414 PTAC | 2339.482 | 2339.482 | 0.130505 | 0.00002047 | 56.869 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 2339.48 | 2339.48 | 0.130505 | 17.25 | 12.38 | 0.00718219 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 10.3282 | 21.11 | 0.00790298 | 49.4773 | 1735.87 | 0.00 | 2508.95 | 2508.95 |
| 414 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 414 PTAC | 2392.167 | 1913.786 | 0.130505 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | 7/21 14:00:00 | 2213.27 | 1931.17 | 0.130505 | 22.19 | 15.66 | 0.00869598 | 9.47 | 9.47 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 10.3282 | 21.11 | 0.00807170 | 50.5198 | 1520.63 | 0.00 | 2393.34 | 1887.39 |
| 415_418 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 415_418 PTAC | 10613.283 | 10613.283 | 0.616396 | 0.00009285 | 259.461 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 10613.28 | 10613.28 | 0.616396 | 17.84 | 12.67 | 0.00724238 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 8.7469 | 21.11 | 0.00784800 | 49.1375 | 4397.03 | 0.00 | 11487.41 | 11487.41 |
| 415_418 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 415_418 PTAC | 11070.480 | 8865.948 | 0.616396 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 10220.46 | 8917.54 | 0.616396 | 21.90 | 15.54 | 0.00867903 | 9.47 | 9.47 | 0.00800000 | 30.14 | 0.01336669 | 21.78 | 8.7469 | 21.11 | 0.00822970 | 51.4993 | 8197.48 | 0.00 | 11075.90 | 8743.30 |
| 419 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 419 PTAC | 2811.685 | 2811.685 | 0.166006 | 0.00002460 | 68.893 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 2811.68 | 2811.68 | 0.166006 | 18.07 | 12.83 | 0.00730603 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 8.1195 | 21.11 | 0.00787001 | 49.2734 | 1289.40 | 0.00 | 3054.48 | 3054.48 |
| 419 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 419 PTAC | 2955.195 | 2366.744 | 0.166006 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | 7/21 13:50:00 | 2720.45 | 2393.65 | 0.166006 | 21.85 | 15.48 | 0.00863178 | 9.47 | 9.47 | 0.00800000 | 30.22 | 0.01336682 | 21.81 | 8.1195 | 21.11 | 0.00821335 | 51.3978 | 2207.74 | 0.00 | 2956.64 | 2334.31 |
| 420_423 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 420_423 PTAC | 10496.918 | 10496.918 | 0.607648 | 0.00009183 | 256.500 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 10496.92 | 10496.92 | 0.607648 | 17.79 | 12.65 | 0.00723224 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 8.8728 | 21.11 | 0.00784644 | 49.1278 | 4351.27 | 0.00 | 11353.09 | 11353.09 |
| 420_423 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 420_423 PTAC | 10935.322 | 8750.262 | 0.607648 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | 7/21 13:40:00 | 10099.80 | 8797.75 | 0.607648 | 21.91 | 15.55 | 0.00868848 | 9.47 | 9.47 | 0.00800000 | 30.14 | 0.01336669 | 21.78 | 8.8728 | 21.11 | 0.00823298 | 51.5195 | 8081.13 | 0.00 | 10940.68 | 8629.17 |
| 424 PTAC HEATING COIL | COIL:HEATING:WATER | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 424 PTAC | 2858.827 | 2858.827 | 0.169550 | 0.00002501 | 70.090 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 2858.83 | 2858.83 | 0.169550 | 18.14 | 12.89 | 0.00733835 | 32.22 | 18.49 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 7.9498 | 21.11 | 0.00789231 | 49.4113 | 1561.39 | 0.00 | 3108.79 | 3108.79 |
| 424 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 424 PTAC | 3013.754 | 2412.180 | 0.169550 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | 7/21 14:00:00 | 2770.49 | 2443.38 | 0.169550 | 21.84 | 15.46 | 0.00861901 | 9.47 | 9.47 | 0.00800000 | 30.30 | 0.01336696 | 21.83 | 7.9498 | 21.11 | 0.00820896 | 51.3707 | 2254.88 | 0.00 | 3015.23 | 2379.22 |
| FRONTSTAIRSFLR4 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | ZONEHVAC:UNITHEATER | FRONTSTAIRSFLR4 UNIT HEATER | 652.145 | 652.145 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | 652.14 | 652.14 | 0.049011 | 7.20 | 6.63 | 0.00598322 | 18.31 | 13.58 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 7.20 | 0.00598322 | 92.6711 | 652.19 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| REARSTAIRSFLR1 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | REARSTAIRSFLR1 UNIT HEATER | REARSTAIRSFLR1 | N/A | N/A | N/A | Yes | No | unknown | No | 81.375 | 81.375 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | REARSTAIRSFLR1 UNITHEATER FAN | Fan:ConstantVolume | 0.006118 | 0.00718196 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 81.38 | 81.38 | 1.0000 | 0.00718196 | 0.006118 | 7.20 | 0.68 | 0.00144192 | 10859.9 | 18.31 | 13.58 | 0.00800000 | 38679.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81.38 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 7.20 | 0.00144192 | 7.20 | 0.00144192 | 22.4896 | 16.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| CORRIDORFLR1 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR1 PTAC | CORRIDORFLR1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 42709.156 | 42709.156 | 3.050128 | 0.00037364 | 1073.088 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | CORRIDORFLR1 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 3.050128 | 3.58062247 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 14.3699 | 14.659116 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 42709.16 | 42709.16 | 1.0000 | 3.58062247 | 3.050128 | 20.52 | 12.89 | 0.00636790 | 36792.9 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.37360022 | 60.00 | 32.22 | 27.78 | 0.000 | 42709.16 | -16.30 | 0.00092409 | -16.30 | 0.04587416 | 1.5040 | 21.09 | 0.00645103 | 21.09 | 0.00645103 | 40.5390 | 40634.79 | 0.00 | 48254.70 | 48254.70 | 3.58062247 | 12.80 | 9.88 | 0.00636790 | 28939.2 | 26.06 | 15.25 | 0.00636790 | 42415.8 | |
| CORRIDORFLR1 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR1 PTAC | CORRIDORFLR1 | N/A | N/A | N/A | Yes | Yes | unknown | No | 57197.488 | 45789.083 | 3.050128 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9256 | 1004.8586 | 1.1739 | CORRIDORFLR1 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 3.050128 | 3.58062247 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | unknown | unknown | unknown | 7/21 18:00:00 | Sensible | 57030.13 | 43350.99 | 0.9971 | 3.58062247 | 3.050128 | 23.99 | 17.16 | 0.00972892 | 48875.5 | 12.25 | 11.14 | 0.00800000 | 32496.5 | -999.0 | -999.00 | -999.00 | -999.00 | 1942.521 | 55087.61 | 28.07 | 0.01336300 | 21.18 | 0.04587416 | 1.5040 | 23.88 | 0.00962370 | 23.88 | 0.00962370 | 50.7914 | 21667.32 | 0.00 | 57225.49 | 45167.42 | 3.43921495 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.83 | 13.78 | 0.00981002 | 38683.3 | |
| SAC_FRONTLOUNGE HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_FRONTLOUNGE | FRONTLOUNGEFLR1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20956.114 | 20956.114 | 0.780683 | 0.00018333 | 477.980 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SAC_FRONTLOUNGE_PTAC_SUPPLY FAN | Fan:OnOff | 0.780683 | 0.91646392 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 7.0509 | 7.192793 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 20956.11 | 20956.11 | 1.0000 | 0.91646392 | 0.780683 | 9.80 | 7.54 | 0.00569651 | 24195.6 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.18331453 | 60.00 | 32.22 | 27.78 | 0.000 | 20956.11 | -16.30 | 0.00092409 | -16.30 | 0.23607290 | 30.2393 | 21.11 | 0.00776521 | 21.11 | 0.00776521 | 48.6258 | 4086.15 | 0.00 | 20148.00 | 20148.00 | 0.91646392 | 12.80 | 9.14 | 0.00569651 | 27244.1 | 34.45 | 17.64 | 0.00569651 | 49228.6 | |
| SAC_FRONTLOUNGE PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_FRONTLOUNGE | FRONTLOUNGEFLR1 | N/A | N/A | N/A | Yes | Yes | unknown | No | 17965.837 | 13033.490 | 0.780683 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.8290 | 1004.8586 | 1.1739 | SAC_FRONTLOUNGE_PTAC_SUPPLY FAN | Fan:OnOff | 0.780683 | 0.91646392 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | unknown | unknown | 7/21 15:30:00 | Sensible | 18373.42 | 12704.64 | 1.0227 | 0.91646392 | 0.780683 | 25.74 | 18.55 | 0.01075284 | 53268.2 | 12.25 | 11.14 | 0.00800000 | 32497.5 | -999.0 | -999.00 | -999.00 | -999.00 | 497.190 | 17876.23 | 30.02 | 0.01336647 | 21.75 | 0.23607290 | 30.2393 | 23.88 | 0.00961990 | 23.88 | 0.00961990 | 50.7597 | 10375.16 | 0.00 | 17974.63 | 12883.94 | 0.88027053 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.34 | 12.33 | 0.00891724 | 34902.9 | |
| SAC_RESTROOM HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_RESTROOM | RESTROOMFLR1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 885.006 | 885.006 | 0.066536 | 0.00000774 | 22.365 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SAC_RESTROOM_PTAC_SUPPLY FAN | Fan:OnOff | 0.066536 | 0.07810869 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.2978 | 0.303762 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 19:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 19:10:00 | Sensible | 885.01 | 885.01 | 1.0000 | 0.07810869 | 0.066536 | 21.11 | 14.42 | 0.00774912 | 40897.0 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.00774163 | 60.00 | 32.22 | 27.78 | 0.000 | 885.01 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 21.11 | 0.00774912 | 21.11 | 0.00774912 | 48.5257 | 539.09 | 0.00 | 1009.58 | 1009.58 | 0.07810869 | 12.80 | 11.34 | 0.00774912 | 32426.4 | 25.48 | 16.27 | 0.00774912 | 45351.7 | |
| SAC_RESTROOM PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_RESTROOM | RESTROOMFLR1 | N/A | N/A | N/A | Yes | Yes | unknown | No | 1101.413 | 881.852 | 0.066536 | -999.0 | -999.000 | -999.0000 | 1.01235 | 1.00000 | 1021.0179 | 1004.8586 | 1.1739 | SAC_RESTROOM_PTAC_SUPPLY FAN | Fan:OnOff | 0.066536 | 0.07810869 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 1052.44 | 931.98 | 0.9555 | 0.07810869 | 0.066536 | 23.89 | 16.26 | 0.00870273 | 46154.5 | 12.25 | 11.14 | 0.00800000 | 32495.5 | -999.0 | -999.00 | -999.00 | -999.00 | 42.375 | 1010.06 | 29.25 | 0.01336509 | 21.53 | 0.00000000 | 0.0000 | 23.89 | 0.00870273 | 23.89 | 0.00870273 | 45.9662 | 884.86 | 0.00 | 1101.95 | 869.54 | 0.07502398 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.34 | 14.51 | 0.00997009 | 40634.4 | |
| SAC_MEETINGROOM HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_MEETINGROOM | MEETINGROOMFLR1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10689.705 | 10689.705 | 0.378047 | 0.00009352 | 241.605 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SAC_MEETINGROOM_PTAC_SUPPLY FAN | Fan:OnOff | 0.378047 | 0.44379924 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 3.5967 | 3.669041 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:00:00 | Sensible | 10689.71 | 10689.71 | 1.0000 | 0.44379924 | 0.378047 | 8.60 | 6.76 | 0.00551823 | 22531.5 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.09350867 | 60.00 | 32.22 | 27.78 | 0.000 | 10689.71 | -16.30 | 0.00092409 | -16.30 | 0.12641521 | 33.4390 | 21.11 | 0.00782623 | 21.11 | 0.00782623 | 49.0027 | 1937.74 | 0.00 | 10109.37 | 10109.37 | 0.44379924 | 12.80 | 8.94 | 0.00551823 | 26794.0 | 35.24 | 17.76 | 0.00551823 | 49573.2 | |
| SAC_MEETINGROOM PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_MEETINGROOM | MEETINGROOMFLR1 | N/A | N/A | N/A | Yes | Yes | unknown | No | 9387.814 | 6581.639 | 0.378047 | -999.0 | -999.000 | -999.0000 | 1.00000 | 0.99173 | 1026.3424 | 1004.8586 | 1.1739 | SAC_MEETINGROOM_PTAC_SUPPLY FAN | Fan:OnOff | 0.378047 | 0.44379924 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | Sensible | 9807.47 | 6255.83 | 1.0447 | 0.44379924 | 0.378047 | 26.02 | 19.26 | 0.01156695 | 55637.0 | 12.25 | 11.14 | 0.00800000 | 32498.3 | -999.0 | -999.00 | -999.00 | -999.00 | 240.765 | 9566.71 | 30.30 | 0.01336696 | 21.83 | 0.12641521 | 33.4390 | 23.87 | 0.01066266 | 23.87 | 0.01066266 | 56.1867 | 5021.82 | 0.00 | 9392.41 | 6511.26 | 0.42627253 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 11.70 | 11.68 | 0.00853463 | 33288.6 | |
| MECHRM UNITHEATER HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | MECHANICALROOMFLR1 UNIT HEATER | MECHANICALROOMFLR1 | N/A | N/A | N/A | Yes | No | unknown | No | 0.000 | 0.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | MECHRM UNITHEATER FAN | Fan:ConstantVolume | 0.000000 | 0.00000000 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 0.00 | 0.00 | 1.0000 | Too Big | -999.0 | 7.20 | 7.20 | 0.00800000 | 27349.4 | 18.31 | 13.58 | 0.00800000 | 38679.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 0.00 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | -999.0000 | 7.20 | 0.00800000 | 7.20 | 0.00800000 | 100.0000 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| 101 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 101 PTAC | GUESTROOM101 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1499.883 | 1499.883 | 0.067379 | 0.00001312 | 35.291 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 101 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.067379 | 0.07909822 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.5047 | 0.514807 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1499.88 | 1499.88 | 1.0000 | 0.07909822 | 0.067379 | 13.63 | 10.11 | 0.00644169 | 29965.8 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.01312029 | 60.00 | 32.22 | 27.78 | 0.000 | 1499.88 | -16.30 | 0.00092409 | -16.30 | 0.01347978 | 20.0058 | 21.11 | 0.00782159 | 21.11 | 0.00782159 | 48.9740 | 766.14 | 0.00 | 1523.06 | 1523.06 | 0.07909822 | 12.80 | 9.96 | 0.00644169 | 29125.5 | 31.74 | 17.34 | 0.00644169 | 48380.9 | |
| 101 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 101 PTAC | GUESTROOM101 | N/A | N/A | N/A | Yes | Yes | unknown | No | 1354.401 | 1047.993 | 0.067379 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.8554 | 1004.8586 | 1.1739 | 101 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.067379 | 0.07909822 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | unknown | unknown | 7/21 15:30:00 | Sensible | 1284.19 | 1045.16 | 0.9482 | 0.07909822 | 0.067379 | 22.89 | 16.30 | 0.00915321 | 46285.3 | 9.47 | 9.47 | 0.00800000 | 29663.2 | -999.0 | -999.00 | -999.00 | -999.00 | 42.912 | 1241.28 | 30.02 | 0.01336647 | 21.75 | 0.01347978 | 20.0058 | 21.11 | 0.00809951 | 21.11 | 0.00809951 | 50.6914 | 896.17 | 0.00 | 1355.06 | 1034.32 | 0.07597444 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.35 | 13.33 | 0.00952939 | 37486.6 | |
| 102 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 102 PTAC | GUESTROOM102 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1436.702 | 1436.702 | 0.062629 | 0.00001257 | 33.642 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 102 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.062629 | 0.07352205 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.4834 | 0.493121 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1436.70 | 1436.70 | 1.0000 | 0.07352205 | 0.062629 | 13.06 | 9.76 | 0.00634802 | 29152.1 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.01256762 | 60.00 | 32.22 | 27.78 | 0.000 | 1436.70 | -16.30 | 0.00092409 | -16.30 | 0.01347978 | 21.5231 | 21.11 | 0.00783559 | 21.11 | 0.00783559 | 49.0605 | 833.04 | 0.00 | 1446.85 | 1446.85 | 0.07352205 | 12.80 | 9.86 | 0.00634802 | 28889.0 | 32.16 | 17.41 | 0.00634802 | 48568.2 | |
| 102 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 102 PTAC | GUESTROOM102 | N/A | N/A | N/A | Yes | Yes | unknown | No | 1351.878 | 1009.785 | 0.062629 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.5676 | 1004.8586 | 1.1739 | 102 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.062629 | 0.07352205 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | unknown | unknown | unknown | 7/21 15:30:00 | Sensible | 1304.75 | 1010.81 | 0.9651 | 0.07352205 | 0.062629 | 23.50 | 16.83 | 0.00953634 | 47880.4 | 9.47 | 9.47 | 0.00800000 | 29663.5 | -999.0 | -999.00 | -999.00 | -999.00 | 39.886 | 1264.86 | 30.02 | 0.01336647 | 21.75 | 0.01347978 | 21.5231 | 21.11 | 0.00813282 | 21.11 | 0.00813282 | 50.8972 | 668.55 | 0.00 | 1352.54 | 997.18 | 0.07061849 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.85 | 12.82 | 0.00921168 | 36169.6 | |
| 103 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 103 PTAC | GUESTROOM103 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2058.445 | 2058.445 | 0.109373 | 0.00001801 | 49.688 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 103 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.109373 | 0.12839585 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.6926 | 0.706523 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2058.45 | 2058.45 | 1.0000 | 0.12839585 | 0.109373 | 16.50 | 11.94 | 0.00704203 | 34407.5 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.01800634 | 60.00 | 32.22 | 27.78 | 0.000 | 2058.45 | -16.30 | 0.00092409 | -16.30 | 0.01347978 | 12.3246 | 21.11 | 0.00790204 | 21.11 | 0.00790204 | 49.4713 | 1411.44 | 0.00 | 2182.29 | 2182.29 | 0.12839585 | 12.80 | 10.60 | 0.00704203 | 30641.2 | 29.50 | 17.07 | 0.00704203 | 47637.8 | |
| 103 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 103 PTAC | GUESTROOM103 | N/A | N/A | N/A | Yes | Yes | unknown | No | 1954.161 | 1564.559 | 0.109373 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4456 | 1004.8586 | 1.1739 | 103 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.109373 | 0.12839585 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | unknown | unknown | unknown | 7/21 18:50:00 | Sensible | 1884.67 | 1567.92 | 0.9644 | 0.12839585 | 0.109373 | 21.82 | 15.73 | 0.00893281 | 44632.6 | 9.47 | 9.47 | 0.00800000 | 29662.9 | -999.0 | -999.00 | -999.00 | -999.00 | 69.656 | 1815.02 | 26.91 | 0.01336094 | 20.84 | 0.01347978 | 12.3246 | 21.11 | 0.00831034 | 21.11 | 0.00831034 | 51.9963 | 1454.60 | 0.00 | 1955.12 | 1543.05 | 0.12332519 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.44 | 14.08 | 0.00987462 | 39469.0 | |
| 104 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 104 PTAC | GUESTROOM104 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2362.175 | 2362.175 | 0.132211 | 0.00002067 | 57.448 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 104 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.132211 | 0.15520618 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.7948 | 0.810772 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2362.17 | 2362.17 | 1.0000 | 0.15520618 | 0.132211 | 17.30 | 12.41 | 0.00719343 | 35602.1 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.02066323 | 60.00 | 32.22 | 27.78 | 0.000 | 2362.17 | -16.30 | 0.00092409 | -16.30 | 0.01347882 | 10.1949 | 21.11 | 0.00790514 | 21.11 | 0.00790514 | 49.4904 | 1458.26 | 0.00 | 2535.25 | 2535.25 | 0.15520618 | 12.80 | 10.76 | 0.00719343 | 31023.4 | 28.84 | 16.97 | 0.00719343 | 47358.1 | |
| 104 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 104 PTAC | GUESTROOM104 | N/A | N/A | N/A | Yes | Yes | unknown | No | 2432.316 | 1947.826 | 0.132211 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1575 | 1004.8586 | 1.1739 | 104 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.132211 | 0.15520618 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | unknown | unknown | unknown | 7/21 14:30:00 | Sensible | 2251.78 | 1932.39 | 0.9258 | 0.15520618 | 0.132211 | 22.05 | 15.67 | 0.00877781 | 44466.1 | 9.47 | 9.47 | 0.00800000 | 29662.8 | -999.0 | -999.00 | -999.00 | -999.00 | 84.201 | 2167.58 | 30.30 | 0.01336696 | 21.83 | 0.01347882 | 10.1949 | 21.11 | 0.00825684 | 21.11 | 0.00825684 | 51.6658 | 1758.34 | 0.00 | 2433.51 | 1920.76 | 0.14907671 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.07 | 13.90 | 0.00983613 | 38998.5 | |
| 105 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 105 PTAC | GUESTROOM105 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2951.824 | 2951.824 | 0.176542 | 0.00002582 | 72.455 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 105 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.176542 | 0.20724718 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.9932 | 1.013158 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2951.82 | 2951.82 | 1.0000 | 0.20724718 | 0.176542 | 18.25 | 12.91 | 0.00731044 | 36873.8 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.02582121 | 60.00 | 32.22 | 27.78 | 0.000 | 2951.82 | -16.30 | 0.00092409 | -16.30 | 0.01347882 | 7.6349 | 21.11 | 0.00783833 | 21.11 | 0.00783833 | 49.0775 | 847.49 | 0.00 | 3215.87 | 3215.87 | 0.20724718 | 12.80 | 10.88 | 0.00731044 | 31318.9 | 28.04 | 16.79 | 0.00731044 | 46836.0 | |
| 105 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 105 PTAC | GUESTROOM105 | N/A | N/A | N/A | Yes | Yes | unknown | No | 3118.366 | 2496.410 | 0.176542 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8043 | 1004.8586 | 1.1739 | 105 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.176542 | 0.20724718 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 2863.08 | 2539.44 | 0.9181 | 0.20724718 | 0.176542 | 21.81 | 15.42 | 0.00858782 | 43743.0 | 9.47 | 9.47 | 0.00800000 | 29662.6 | -999.0 | -999.00 | -999.00 | -999.00 | 112.434 | 2750.65 | 30.30 | 0.01336696 | 21.83 | 0.01347882 | 7.6349 | 21.11 | 0.00819278 | 21.11 | 0.00819278 | 51.2701 | 2347.92 | 0.00 | 3119.89 | 2462.47 | 0.19906248 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.58 | 14.15 | 0.00988979 | 39649.5 | |
| SAC_EMPLOYEELOUNGE HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_EMPLOYEELOUNGE | EMPLOYEELOUNGEFLR1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 11247.006 | 11247.006 | 0.672673 | 0.00009839 | 276.068 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SAC_EMPLOYEELOUNGE_PTAC_SUPPLY FAN | Fan:OnOff | 0.672673 | 0.78966771 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 3.7842 | 3.860323 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 11247.01 | 11247.01 | 1.0000 | 0.78966771 | 0.672673 | 18.25 | 12.91 | 0.00731235 | 36878.9 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.09838367 | 60.00 | 32.22 | 27.78 | 0.000 | 11247.01 | -16.30 | 0.00092409 | -16.30 | 0.05135254 | 7.6341 | 21.11 | 0.00784034 | 21.11 | 0.00784034 | 49.0899 | 858.41 | 0.00 | 12253.14 | 12253.14 | 0.78966771 | 12.80 | 10.89 | 0.00731235 | 31323.7 | 28.04 | 16.79 | 0.00731235 | 46840.5 | |
| SAC_EMPLOYEELOUNGE PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_EMPLOYEELOUNGE | EMPLOYEELOUNGEFLR1 | N/A | N/A | N/A | Yes | Yes | unknown | No | 11942.525 | 9563.564 | 0.672673 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5554 | 1004.8586 | 1.1739 | SAC_EMPLOYEELOUNGE_PTAC_SUPPLY FAN | Fan:OnOff | 0.672673 | 0.78966771 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 11430.44 | 9717.73 | 0.9571 | 0.78966771 | 0.672673 | 24.37 | 16.67 | 0.00899184 | 47381.6 | 12.25 | 11.14 | 0.00800000 | 32495.8 | -999.0 | -999.00 | -999.00 | -999.00 | 428.402 | 11002.04 | 30.30 | 0.01336696 | 21.83 | 0.05135254 | 7.6341 | 23.88 | 0.00863023 | 23.88 | 0.00863023 | 45.6144 | 8938.16 | 0.00 | 11948.37 | 9432.85 | 0.75848180 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.51 | 14.12 | 0.00988433 | 39569.4 | |
| SAC_EXERCISECENTER HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_EXERCISECENTER | EXERCISECENTERFLR1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 3739.964 | 3739.964 | 0.136166 | 0.00003272 | 84.962 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SAC_EXERCISECENTER_PTAC_SUPPLY FAN | Fan:OnOff | 0.136166 | 0.15984926 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 1.2583 | 1.283672 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:00:00 | Sensible | 3739.96 | 3739.96 | 1.0000 | 0.15984926 | 0.136166 | 9.28 | 7.22 | 0.00563166 | 23504.0 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.03271550 | 60.00 | 32.22 | 27.78 | 0.000 | 3739.96 | -16.30 | 0.00092409 | -16.30 | 0.04306989 | 31.6303 | 21.11 | 0.00780956 | 21.11 | 0.00780956 | 48.8996 | 717.62 | 0.00 | 3569.94 | 3569.94 | 0.15984926 | 12.80 | 9.07 | 0.00563166 | 27080.4 | 34.80 | 17.71 | 0.00563166 | 49413.5 | |
| SAC_EXERCISECENTER PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_EXERCISECENTER | EXERCISECENTERFLR1 | N/A | N/A | N/A | Yes | Yes | unknown | No | 3011.230 | 2225.920 | 0.136166 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.4380 | 1004.8586 | 1.1739 | SAC_EXERCISECENTER_PTAC_SUPPLY FAN | Fan:OnOff | 0.136166 | 0.15984926 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | unknown | unknown | unknown | 7/21 17:00:00 | Sensible | 3088.22 | 2177.21 | 1.0256 | 0.15984926 | 0.136166 | 25.50 | 18.31 | 0.01054250 | 52490.6 | 12.25 | 11.14 | 0.00800000 | 32497.3 | -999.0 | -999.00 | -999.00 | -999.00 | 86.720 | 3001.50 | 29.00 | 0.01336465 | 21.45 | 0.04306989 | 31.6303 | 23.88 | 0.00923687 | 23.88 | 0.00923687 | 48.7574 | 1810.20 | 0.00 | 3012.70 | 2199.08 | 0.15353642 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.65 | 12.64 | 0.00910695 | 35700.3 | |
| SAC_FRONTOFFICE HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_FRONTOFFICE | FRONTOFFICEFLR1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7731.006 | 7731.006 | 0.391600 | 0.00006763 | 185.308 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | SAC_FRONTOFFICE_PTAC_SUPPLY FAN | Fan:OnOff | 0.391600 | 0.45970973 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 2.6012 | 2.653522 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:20:00 | Sensible | 7731.01 | 7731.01 | 1.0000 | 0.45970973 | 0.391600 | 15.73 | 11.42 | 0.00684270 | 33119.4 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.06762731 | 60.00 | 32.22 | 27.78 | 0.000 | 7731.01 | -16.30 | 0.00092409 | -16.30 | 0.05632221 | 14.3826 | 21.11 | 0.00783694 | 21.11 | 0.00783694 | 49.0689 | 3360.57 | 0.00 | 8100.58 | 8100.58 | 0.45970973 | 12.80 | 10.39 | 0.00684270 | 30137.9 | 30.12 | 17.12 | 0.00684270 | 47759.0 | |
| SAC_FRONTOFFICE PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | SAC_FRONTOFFICE | FRONTOFFICEFLR1 | N/A | N/A | N/A | Yes | Yes | unknown | No | 7443.650 | 5933.902 | 0.391600 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1891 | 1004.8586 | 1.1739 | SAC_FRONTOFFICE_PTAC_SUPPLY FAN | Fan:OnOff | 0.391600 | 0.45970973 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 7228.94 | 5878.66 | 0.9712 | 0.45970973 | 0.391600 | 24.81 | 17.11 | 0.00933272 | 48700.1 | 12.25 | 11.14 | 0.00800000 | 32496.1 | -999.0 | -999.00 | -999.00 | -999.00 | 249.397 | 6979.54 | 30.30 | 0.01336696 | 21.83 | 0.05632221 | 14.3826 | 23.89 | 0.00865502 | 23.89 | 0.00865502 | 45.7198 | 5207.47 | 0.00 | 7447.29 | 5853.28 | 0.44155467 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.71 | 13.70 | 0.00976926 | 38456.3 | |
| FRONTSTAIRSFLR1 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONTSTAIRSFLR1 UNIT HEATER | FRONTSTAIRSFLR1 | N/A | N/A | N/A | Yes | No | unknown | No | 359.760 | 359.760 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | FRONTSTAIRSFLR1 UNITHEATER FAN | Fan:ConstantVolume | 0.027040 | 0.03174324 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 359.76 | 359.76 | 1.0000 | 0.03174324 | 0.027040 | 7.20 | 5.89 | 0.00536501 | 20720.9 | 18.31 | 13.58 | 0.00800000 | 38679.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 359.76 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 7.20 | 0.00536501 | 7.20 | 0.00536501 | 83.1714 | 359.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| REARSTAIRSFLR2 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | REARSTAIRSFLR2 UNIT HEATER | REARSTAIRSFLR2 | N/A | N/A | N/A | Yes | No | unknown | No | 81.374 | 81.374 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | REARSTAIRSFLR2 UNITHEATER FAN | Fan:ConstantVolume | 0.006118 | 0.00718196 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 81.37 | 81.37 | 1.0000 | 0.00718196 | 0.006118 | 7.20 | 0.32 | 0.00118884 | 10223.7 | 18.31 | 13.58 | 0.00800000 | 38679.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81.37 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 7.20 | 0.00118884 | 7.20 | 0.00118884 | 18.5497 | 8.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| CORRIDORFLR2 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR2 PTAC | CORRIDORFLR2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5678.686 | 5678.686 | 0.298218 | 0.00004968 | 136.856 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | CORRIDORFLR2 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.298218 | 0.35008512 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 1.9106 | 1.949102 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 16:30:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 16:30:00 | Sensible | 5678.69 | 5678.69 | 1.0000 | 0.35008512 | 0.298218 | 16.31 | 11.59 | 0.00676824 | 33526.0 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.04967455 | 60.00 | 32.22 | 27.78 | 0.000 | 5678.69 | -16.30 | 0.00092409 | -16.30 | 0.03822807 | 12.8189 | 21.11 | 0.00762755 | 21.11 | 0.00762755 | 47.7746 | 2481.18 | 0.00 | 6003.31 | 6003.31 | 0.35008512 | 12.80 | 10.31 | 0.00676824 | 29950.0 | 29.65 | 16.90 | 0.00676824 | 47098.1 | |
| CORRIDORFLR2 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR2 PTAC | CORRIDORFLR2 | N/A | N/A | N/A | Yes | Yes | unknown | No | 5515.625 | 4412.811 | 0.298218 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0692 | 1004.8586 | 1.1739 | CORRIDORFLR2 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.298218 | 0.35008512 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:20:00 | unknown | unknown | unknown | 7/21 16:20:00 | Sensible | 5382.98 | 4406.29 | 0.9760 | 0.35008512 | 0.298218 | 24.61 | 16.99 | 0.00926827 | 48328.3 | 12.25 | 11.14 | 0.00800000 | 32496.0 | -999.0 | -999.00 | -999.00 | -999.00 | 189.924 | 5193.05 | 29.49 | 0.01336553 | 21.60 | 0.03822807 | 12.8189 | 23.89 | 0.00866582 | 23.89 | 0.00866582 | 45.7747 | 3965.85 | 0.00 | 5518.32 | 4352.80 | 0.33625940 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.01 | 13.87 | 0.00982566 | 38911.5 | |
| 201 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 201 PTAC | GUESTROOM201 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1740.189 | 1740.189 | 0.085442 | 0.00001522 | 41.519 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 201 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.085442 | 0.10030252 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.5855 | 0.597287 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 1740.19 | 1740.19 | 1.0000 | 0.10030252 | 0.085442 | 15.21 | 10.92 | 0.00657224 | 31904.2 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.01522238 | 60.00 | 32.22 | 27.78 | 0.000 | 1740.19 | -16.30 | 0.00092409 | -16.30 | 0.01347978 | 15.7765 | 21.11 | 0.00763023 | 21.11 | 0.00763023 | 47.7921 | 1136.55 | 0.00 | 1809.08 | 1809.08 | 0.10030252 | 12.80 | 10.10 | 0.00657224 | 29455.1 | 30.53 | 17.04 | 0.00657224 | 47491.3 | |
| 201 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 201 PTAC | GUESTROOM201 | N/A | N/A | N/A | Yes | Yes | unknown | No | 1711.210 | 1327.691 | 0.085442 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.0117 | 1004.8586 | 1.1739 | 201 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.085442 | 0.10030252 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:40:00 | unknown | unknown | unknown | 7/21 12:40:00 | Sensible | 1630.76 | 1305.44 | 0.9530 | 0.10030252 | 0.085442 | 22.70 | 16.30 | 0.00923734 | 46300.5 | 9.47 | 9.47 | 0.00800000 | 29663.2 | -999.0 | -999.00 | -999.00 | -999.00 | 54.415 | 1576.35 | 29.59 | 0.01336569 | 21.62 | 0.01347978 | 15.7765 | 21.11 | 0.00828526 | 21.11 | 0.00828526 | 51.8404 | 956.65 | 0.00 | 1712.05 | 1310.36 | 0.09634133 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.37 | 13.35 | 0.00954994 | 37551.7 | |
| 202_205 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 202_205 PTAC | GUESTROOM202_205 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7851.967 | 7851.967 | 0.408786 | 0.00006869 | 188.979 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 202_205 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.408786 | 0.47988380 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 2.6419 | 2.695040 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 7851.97 | 7851.97 | 1.0000 | 0.47988380 | 0.408786 | 16.18 | 11.65 | 0.00688441 | 33679.0 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.06868543 | 60.00 | 32.22 | 27.78 | 0.000 | 7851.97 | -16.30 | 0.00092409 | -16.30 | 0.05391910 | 13.1901 | 21.11 | 0.00779003 | 21.11 | 0.00779003 | 48.7789 | 2663.75 | 0.00 | 8283.28 | 8283.28 | 0.47988380 | 12.80 | 10.43 | 0.00688441 | 30243.3 | 29.76 | 17.03 | 0.00688441 | 47504.3 | |
| 202_205 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 202_205 PTAC | GUESTROOM202_205 | N/A | N/A | N/A | Yes | Yes | unknown | No | 7388.411 | 5916.092 | 0.408786 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5642 | 1004.8586 | 1.1739 | 202_205 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.408786 | 0.47988380 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | unknown | unknown | unknown | 7/21 18:50:00 | Sensible | 7142.31 | 5878.89 | 0.9667 | 0.47988380 | 0.408786 | 21.87 | 15.80 | 0.00899656 | 44845.6 | 9.47 | 9.47 | 0.00800000 | 29663.0 | -999.0 | -999.00 | -999.00 | -999.00 | 260.341 | 6881.96 | 26.91 | 0.01336094 | 20.84 | 0.05391910 | 13.1901 | 21.11 | 0.00833343 | 21.11 | 0.00833343 | 52.1398 | 5436.45 | 0.00 | 7392.03 | 5833.65 | 0.46093202 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.30 | 14.01 | 0.00985907 | 39285.3 | |
| 206_208 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 206_208 PTAC | GUESTROOM206_208 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6236.203 | 6236.203 | 0.324970 | 0.00005456 | 150.113 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 206_208 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.324970 | 0.38149001 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 2.0982 | 2.140460 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 6236.20 | 6236.20 | 1.0000 | 0.38149001 | 0.324970 | 16.19 | 11.64 | 0.00687111 | 33660.5 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.05455146 | 60.00 | 32.22 | 27.78 | 0.000 | 6236.20 | -16.30 | 0.00092409 | -16.30 | 0.04273309 | 13.1499 | 21.11 | 0.00777154 | 21.11 | 0.00777154 | 48.6647 | 1971.99 | 0.00 | 6580.27 | 6580.27 | 0.38149001 | 12.80 | 10.42 | 0.00687111 | 30209.7 | 29.75 | 17.02 | 0.00687111 | 47458.5 | |
| 206_208 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 206_208 PTAC | GUESTROOM206_208 | N/A | N/A | N/A | Yes | Yes | unknown | No | 5861.347 | 4691.568 | 0.324970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5379 | 1004.8586 | 1.1739 | 206_208 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.324970 | 0.38149001 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | unknown | unknown | unknown | 7/21 18:50:00 | Sensible | 5663.75 | 4673.45 | 0.9663 | 0.38149001 | 0.324970 | 21.87 | 15.79 | 0.00898243 | 44807.4 | 9.47 | 9.47 | 0.00800000 | 29663.0 | -999.0 | -999.00 | -999.00 | -999.00 | 206.962 | 5456.79 | 26.91 | 0.01336094 | 20.84 | 0.04273309 | 13.1499 | 21.11 | 0.00831948 | 21.11 | 0.00831948 | 52.0534 | 4321.82 | 0.00 | 5864.22 | 4626.42 | 0.36642404 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.33 | 14.02 | 0.00986020 | 39318.5 | |
| 209_212 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 209_212 PTAC | GUESTROOM209_212 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7687.660 | 7687.660 | 0.396430 | 0.00006726 | 184.764 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 209_212 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.396430 | 0.46537945 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 2.5866 | 2.638645 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 7687.66 | 7687.66 | 1.0000 | 0.46537945 | 0.396430 | 16.02 | 11.55 | 0.00685074 | 33437.2 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.06724814 | 60.00 | 32.22 | 27.78 | 0.000 | 7687.66 | -16.30 | 0.00092409 | -16.30 | 0.05391910 | 13.6012 | 21.11 | 0.00778374 | 21.11 | 0.00778374 | 48.7402 | 2583.82 | 0.00 | 8090.97 | 8090.97 | 0.46537945 | 12.80 | 10.40 | 0.00685074 | 30158.3 | 29.89 | 17.05 | 0.00685074 | 47544.0 | |
| 209_212 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 209_212 PTAC | GUESTROOM209_212 | N/A | N/A | N/A | Yes | Yes | unknown | No | 7203.258 | 5769.392 | 0.396430 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6191 | 1004.8586 | 1.1739 | 209_212 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.396430 | 0.46537945 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | unknown | unknown | unknown | 7/21 18:50:00 | Sensible | 6970.89 | 5709.98 | 0.9677 | 0.46537945 | 0.396430 | 21.90 | 15.84 | 0.00902610 | 44945.0 | 9.47 | 9.47 | 0.00800000 | 29663.0 | -999.0 | -999.00 | -999.00 | -999.00 | 252.473 | 6718.42 | 26.91 | 0.01336094 | 20.84 | 0.05391910 | 13.6012 | 21.11 | 0.00834369 | 21.11 | 0.00834369 | 52.2032 | 5272.14 | 0.00 | 7206.78 | 5690.75 | 0.44700048 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.22 | 13.98 | 0.00985490 | 39199.8 | |
| 213 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 213 PTAC | GUESTROOM213 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2078.753 | 2078.753 | 0.110899 | 0.00001819 | 50.209 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 213 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.110899 | 0.13018757 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.6994 | 0.713493 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2078.75 | 2078.75 | 1.0000 | 0.13018757 | 0.110899 | 16.56 | 11.96 | 0.00704120 | 34470.0 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.01818399 | 60.00 | 32.22 | 27.78 | 0.000 | 2078.75 | -16.30 | 0.00092409 | -16.30 | 0.01347978 | 12.1550 | 21.11 | 0.00788761 | 21.11 | 0.00788761 | 49.3823 | 1261.74 | 0.00 | 2205.97 | 2205.97 | 0.13018757 | 12.80 | 10.60 | 0.00704120 | 30639.1 | 29.45 | 17.06 | 0.00704120 | 47583.6 | |
| 213 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 213 PTAC | GUESTROOM213 | N/A | N/A | N/A | Yes | Yes | unknown | No | 1977.303 | 1582.516 | 0.110899 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4252 | 1004.8586 | 1.1739 | 213 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.110899 | 0.13018757 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | unknown | unknown | unknown | 7/21 18:50:00 | Sensible | 1906.19 | 1588.75 | 0.9640 | 0.13018757 | 0.110899 | 21.81 | 15.72 | 0.00892179 | 44594.4 | 9.47 | 9.47 | 0.00800000 | 29662.9 | -999.0 | -999.00 | -999.00 | -999.00 | 70.628 | 1835.57 | 26.91 | 0.01336094 | 20.84 | 0.01347978 | 12.1550 | 21.11 | 0.00830755 | 21.11 | 0.00830755 | 51.9796 | 1474.87 | 0.00 | 1978.27 | 1560.83 | 0.12504614 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.47 | 14.09 | 0.00987580 | 39502.1 | |
| 214 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 214 PTAC | GUESTROOM214 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2513.300 | 2513.300 | 0.143572 | 0.00002199 | 61.300 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 214 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.143572 | 0.16854329 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.8456 | 0.862643 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2513.30 | 2513.30 | 1.0000 | 0.16854329 | 0.143572 | 17.60 | 12.57 | 0.00723379 | 36011.6 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.02198520 | 60.00 | 32.22 | 27.78 | 0.000 | 2513.30 | -16.30 | 0.00092409 | -16.30 | 0.01347882 | 9.3882 | 21.11 | 0.00788752 | 21.11 | 0.00788752 | 49.3817 | 1260.77 | 0.00 | 2710.13 | 2710.13 | 0.16854329 | 12.80 | 10.80 | 0.00723379 | 31125.3 | 28.59 | 16.92 | 0.00723379 | 47205.1 | |
| 214 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 214 PTAC | GUESTROOM214 | N/A | N/A | N/A | Yes | Yes | unknown | No | 2608.888 | 2089.524 | 0.143572 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0490 | 1004.8586 | 1.1739 | 214 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.143572 | 0.16854329 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | unknown | unknown | 7/21 14:00:00 | Sensible | 2409.06 | 2087.86 | 0.9234 | 0.16854329 | 0.143572 | 21.97 | 15.60 | 0.00871942 | 44241.8 | 9.47 | 9.47 | 0.00800000 | 29662.7 | -999.0 | -999.00 | -999.00 | -999.00 | 91.436 | 2317.62 | 30.30 | 0.01336696 | 21.83 | 0.01347882 | 9.3882 | 21.11 | 0.00823789 | 21.11 | 0.00823789 | 51.5493 | 1909.41 | 0.00 | 2610.17 | 2061.04 | 0.16188710 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.22 | 13.98 | 0.00985472 | 39199.0 | |
| 215_218 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 215_218 PTAC | GUESTROOM215_218 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17702.715 | 17702.715 | 1.149386 | 0.00015487 | 439.307 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 215_218 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 1.149386 | 1.34929287 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 5.9563 | 6.076124 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 17702.71 | 17702.71 | 1.0000 | 1.34929287 | 1.149386 | 19.36 | 13.49 | 0.00746724 | 38393.2 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.15485527 | 60.00 | 32.22 | 27.78 | 0.000 | 17702.71 | -16.30 | 0.00092409 | -16.30 | 0.05391527 | 4.6908 | 21.11 | 0.00778928 | 21.11 | 0.00778928 | 48.7744 | 2653.90 | 0.00 | 19626.62 | 19626.62 | 1.34929287 | 12.80 | 11.05 | 0.00746724 | 31714.8 | 27.08 | 16.59 | 0.00746724 | 46260.6 | |
| 215_218 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 215_218 PTAC | GUESTROOM215_218 | N/A | N/A | N/A | Yes | Yes | unknown | No | 19026.413 | 15233.598 | 1.149386 | -999.0 | -999.000 | -999.0000 | 1.00157 | 1.00000 | 1020.2226 | 1004.8586 | 1.1739 | 215_218 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 1.149386 | 1.34929287 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | unknown | unknown | 7/21 13:50:00 | Sensible | 17269.72 | 16276.18 | 0.9077 | 1.34929287 | 1.149386 | 21.54 | 15.05 | 0.00827490 | 42668.8 | 9.47 | 9.47 | 0.00800000 | 29662.3 | -999.0 | -999.00 | -999.00 | -999.00 | 732.004 | 16537.71 | 30.22 | 0.01336682 | 21.81 | 0.05391527 | 4.6908 | 21.11 | 0.00802430 | 21.11 | 0.00802430 | 50.2268 | 15287.30 | 0.00 | 19035.73 | 15020.98 | 1.29600600 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.34 | 14.51 | 0.00997009 | 40634.4 | |
| 219 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 219 PTAC | GUESTROOM219 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8748.722 | 8748.722 | 0.612359 | 0.00007654 | 219.183 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 219 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.612359 | 0.71886404 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 2.9436 | 3.002834 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 8748.72 | 8748.72 | 1.0000 | 0.71886404 | 0.612359 | 20.29 | 14.01 | 0.00764368 | 39790.0 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.07652983 | 60.00 | 32.22 | 27.78 | 0.000 | 8748.72 | -16.30 | 0.00092409 | -16.30 | 0.01347882 | 2.2011 | 21.11 | 0.00779492 | 21.11 | 0.00779492 | 48.8092 | 682.30 | 0.00 | 9846.49 | 9846.49 | 0.71886404 | 12.80 | 11.23 | 0.00764368 | 32160.2 | 26.24 | 16.45 | 0.00764368 | 45857.5 | |
| 219 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 219 PTAC | GUESTROOM219 | N/A | N/A | N/A | Yes | Yes | unknown | No | 10136.720 | 8116.018 | 0.612359 | -999.0 | -999.000 | -999.0000 | 1.03395 | 1.00000 | 1020.0333 | 1004.8586 | 1.1739 | 219 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.612359 | 0.71886404 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | unknown | unknown | 7/21 13:50:00 | Sensible | 9148.24 | 8802.99 | 0.9025 | 0.71886404 | 0.612359 | 21.31 | 14.87 | 0.00817307 | 42177.9 | 9.47 | 9.47 | 0.00800000 | 29662.2 | -999.0 | -999.00 | -999.00 | -999.00 | 389.990 | 8758.25 | 30.22 | 0.01336682 | 21.81 | 0.01347882 | 2.2011 | 21.11 | 0.00805618 | 21.11 | 0.00805618 | 50.4261 | 8144.08 | 0.00 | 10141.68 | 8002.74 | 0.69047435 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 15.34 | 14.51 | 0.00997009 | 40634.4 | |
| 220_223 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 220_223 PTAC | GUESTROOM220_223 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8934.777 | 8934.777 | 0.490203 | 0.00007817 | 216.686 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 220_223 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.490203 | 0.57546133 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 3.0062 | 3.066694 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 07:50:00 | Sensible | 8934.78 | 8934.78 | 1.0000 | 0.57546133 | 0.490203 | 17.00 | 12.13 | 0.00703037 | 34882.9 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.07815735 | 60.00 | 32.22 | 27.78 | 0.000 | 8934.78 | -16.30 | 0.00092409 | -16.30 | 0.05391527 | 10.9986 | 21.11 | 0.00778497 | 21.11 | 0.00778497 | 48.7478 | 2599.40 | 0.00 | 9544.87 | 9544.87 | 0.57546133 | 12.80 | 10.59 | 0.00703037 | 30611.8 | 29.09 | 16.92 | 0.00703037 | 47198.2 | |
| 220_223 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 220_223 PTAC | GUESTROOM220_223 | N/A | N/A | N/A | Yes | Yes | unknown | No | 9117.955 | 7296.166 | 0.490203 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2694 | 1004.8586 | 1.1739 | 220_223 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.490203 | 0.57546133 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | unknown | unknown | 7/21 13:50:00 | Sensible | 8470.02 | 7195.69 | 0.9289 | 0.57546133 | 0.490203 | 22.11 | 15.75 | 0.00883798 | 44685.5 | 9.47 | 9.47 | 0.00800000 | 29662.9 | -999.0 | -999.00 | -999.00 | -999.00 | 312.193 | 8157.83 | 30.22 | 0.01336682 | 21.81 | 0.05391527 | 10.9986 | 21.11 | 0.00827831 | 21.11 | 0.00827831 | 51.7994 | 6519.24 | 0.00 | 9122.42 | 7195.83 | 0.55273495 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.94 | 13.83 | 0.00981805 | 38818.2 | |
| 224 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 224 PTAC | GUESTROOM224 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2482.808 | 2482.808 | 0.141280 | 0.00002172 | 60.524 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 224 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.141280 | 0.16585208 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.8354 | 0.852177 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | Sensible | 2482.81 | 2482.81 | 1.0000 | 0.16585208 | 0.141280 | 17.54 | 12.52 | 0.00720141 | 35871.5 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.02171847 | 60.00 | 32.22 | 27.78 | 0.000 | 2482.81 | -16.30 | 0.00092409 | -16.30 | 0.01347882 | 9.5405 | 21.11 | 0.00786346 | 21.11 | 0.00786346 | 49.2330 | 1035.01 | 0.00 | 2674.87 | 2674.87 | 0.16585208 | 12.80 | 10.77 | 0.00720141 | 31043.6 | 28.64 | 16.91 | 0.00720141 | 47171.7 | |
| 224 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 224 PTAC | GUESTROOM224 | N/A | N/A | N/A | Yes | Yes | unknown | No | 2573.363 | 2059.017 | 0.141280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0699 | 1004.8586 | 1.1739 | 224 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.141280 | 0.16585208 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | unknown | unknown | 7/21 14:00:00 | Sensible | 2377.43 | 2056.47 | 0.9239 | 0.16585208 | 0.141280 | 21.99 | 15.61 | 0.00873070 | 44284.8 | 9.47 | 9.47 | 0.00800000 | 29662.7 | -999.0 | -999.00 | -999.00 | -999.00 | 89.976 | 2287.45 | 30.30 | 0.01336696 | 21.83 | 0.01347882 | 9.5405 | 21.11 | 0.00824173 | 21.11 | 0.00824173 | 51.5730 | 1878.92 | 0.00 | 2574.62 | 2030.90 | 0.15930218 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.21 | 13.96 | 0.00984644 | 39160.5 | |
| FRONTSTAIRSFLR2 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONTSTAIRSFLR2 UNIT HEATER | FRONTSTAIRSFLR2 | N/A | N/A | N/A | Yes | No | unknown | No | 324.768 | 324.768 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | FRONTSTAIRSFLR2 UNITHEATER FAN | Fan:ConstantVolume | 0.024410 | 0.02865597 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 324.77 | 324.77 | 1.0000 | 0.02865597 | 0.024410 | 7.20 | 5.62 | 0.00514720 | 20173.4 | 18.31 | 13.58 | 0.00800000 | 38679.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 324.77 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 7.20 | 0.00514720 | 7.20 | 0.00514720 | 79.8219 | 324.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| REARSTAIRSFLR3 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | REARSTAIRSFLR3 UNIT HEATER | REARSTAIRSFLR3 | N/A | N/A | N/A | Yes | No | unknown | No | 81.382 | 81.382 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | REARSTAIRSFLR3 UNITHEATER FAN | Fan:ConstantVolume | 0.006118 | 0.00718196 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 81.38 | 81.38 | 1.0000 | 0.00718196 | 0.006118 | 7.20 | 2.31 | 0.00259572 | 13760.0 | 18.31 | 13.58 | 0.00800000 | 38679.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 81.38 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 7.20 | 0.00259572 | 7.20 | 0.00259572 | 40.4135 | 75.06 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| CORRIDORFLR3 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR3 PTAC | CORRIDORFLR3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4595.937 | 4595.937 | 0.216818 | 0.00004021 | 108.981 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | CORRIDORFLR3 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.216818 | 0.25452795 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 1.5463 | 1.577469 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 4595.94 | 4595.94 | 1.0000 | 0.25452795 | 0.216818 | 14.51 | 10.51 | 0.00645975 | 30914.4 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.04020316 | 60.00 | 32.22 | 27.78 | 0.000 | 4595.94 | -16.30 | 0.00092409 | -16.30 | 0.03822807 | 17.6314 | 21.11 | 0.00764468 | 21.11 | 0.00764468 | 47.8804 | 2884.01 | 0.00 | 4728.59 | 4728.59 | 0.25452795 | 12.80 | 9.98 | 0.00645975 | 29171.1 | 31.07 | 17.13 | 0.00645975 | 47749.0 | |
| CORRIDORFLR3 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR3 PTAC | CORRIDORFLR3 | N/A | N/A | N/A | Yes | Yes | unknown | No | 4633.663 | 3478.840 | 0.216818 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.9702 | 1004.8586 | 1.1739 | CORRIDORFLR3 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.216818 | 0.25452795 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:40:00 | unknown | unknown | unknown | 7/21 16:40:00 | Sensible | 4693.31 | 3390.51 | 1.0129 | 0.25452795 | 0.216818 | 25.21 | 18.02 | 0.01029085 | 51553.3 | 12.25 | 11.14 | 0.00800000 | 32497.0 | -999.0 | -999.00 | -999.00 | -999.00 | 138.084 | 4555.22 | 29.25 | 0.01336509 | 21.53 | 0.03822807 | 17.6314 | 23.89 | 0.00928089 | 23.89 | 0.00928089 | 48.9764 | 2055.81 | 0.00 | 4635.93 | 3435.65 | 0.24447602 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.92 | 12.90 | 0.00925971 | 36359.7 | |
| 301 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 301 PTAC | GUESTROOM301 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1810.793 | 1810.793 | 0.090749 | 0.00001584 | 43.338 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 301 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.090749 | 0.10653275 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.6093 | 0.621521 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 1810.79 | 1810.79 | 1.0000 | 0.10653275 | 0.090749 | 15.55 | 11.12 | 0.00662180 | 32380.6 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.01583999 | 60.00 | 32.22 | 27.78 | 0.000 | 1810.79 | -16.30 | 0.00092409 | -16.30 | 0.01347978 | 14.8539 | 21.11 | 0.00761577 | 21.11 | 0.00761577 | 47.7028 | 1207.16 | 0.00 | 1892.29 | 1892.29 | 0.10653275 | 12.80 | 10.15 | 0.00662180 | 29580.2 | 30.26 | 16.98 | 0.00662180 | 47342.7 | |
| 301 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 301 PTAC | GUESTROOM301 | N/A | N/A | N/A | Yes | Yes | unknown | No | 1997.165 | 1478.984 | 0.090749 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.9559 | 1004.8586 | 1.1739 | 301 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.090749 | 0.10653275 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | unknown | unknown | unknown | 7/21 13:10:00 | Sensible | 1939.94 | 1456.83 | 0.9713 | 0.10653275 | 0.090749 | 23.45 | 16.98 | 0.00974525 | 48359.4 | 9.47 | 9.47 | 0.00800000 | 29663.7 | -999.0 | -999.00 | -999.00 | -999.00 | 57.795 | 1882.14 | 29.91 | 0.01336627 | 21.72 | 0.01347978 | 14.8539 | 21.11 | 0.00843508 | 21.11 | 0.00843508 | 52.7655 | 674.75 | 0.00 | 1998.14 | 1460.93 | 0.10232551 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.69 | 12.68 | 0.00912626 | 35795.1 | |
| 302_305 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 302_305 PTAC | GUESTROOM302_305 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5298.198 | 5298.198 | 0.216789 | 0.00004635 | 122.783 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 302_305 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.216789 | 0.25449365 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 1.7826 | 1.818507 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 5298.20 | 5298.20 | 1.0000 | 0.25449365 | 0.216789 | 11.81 | 8.91 | 0.00607903 | 27199.8 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.04634622 | 60.00 | 32.22 | 27.78 | 0.000 | 5298.20 | -16.30 | 0.00092409 | -16.30 | 0.05391910 | 24.8717 | 21.11 | 0.00778561 | 21.11 | 0.00778561 | 48.7516 | 2883.56 | 0.00 | 5240.09 | 5240.09 | 0.25449365 | 12.80 | 9.56 | 0.00607903 | 28209.9 | 33.06 | 17.49 | 0.00607903 | 48800.2 | |
| 302_305 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 302_305 PTAC | GUESTROOM302_305 | N/A | N/A | N/A | Yes | Yes | unknown | No | 4732.695 | 3520.079 | 0.216789 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.4905 | 1004.8586 | 1.1739 | 302_305 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.216789 | 0.25449365 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | unknown | unknown | unknown | 7/21 18:40:00 | Sensible | 4766.45 | 3423.94 | 1.0071 | 0.25449365 | 0.216789 | 23.25 | 17.15 | 0.01003284 | 48889.2 | 9.47 | 9.47 | 0.00800000 | 29664.0 | -999.0 | -999.00 | -999.00 | -999.00 | 138.065 | 4628.38 | 27.14 | 0.01336135 | 20.91 | 0.05391910 | 24.8717 | 21.11 | 0.00819939 | 21.11 | 0.00819939 | 51.3087 | 2019.07 | 0.00 | 4735.01 | 3477.05 | 0.24444308 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.75 | 12.74 | 0.00916694 | 35951.8 | |
| 306_308 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 306_308 PTAC | GUESTROOM306_308 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4127.010 | 4127.010 | 0.166399 | 0.00003610 | 95.407 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 306_308 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.166399 | 0.19533963 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 1.3886 | 1.416519 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 11:10:00 | Sensible | 4127.01 | 4127.01 | 1.0000 | 0.19533963 | 0.166399 | 11.50 | 8.70 | 0.00601543 | 26731.7 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.03610120 | 60.00 | 32.22 | 27.78 | 0.000 | 4127.01 | -16.30 | 0.00092409 | -16.30 | 0.04273309 | 25.6811 | 21.11 | 0.00777476 | 21.11 | 0.00777476 | 48.6845 | 2213.31 | 0.00 | 4064.16 | 4064.16 | 0.19533963 | 12.80 | 9.49 | 0.00601543 | 28049.3 | 33.28 | 17.51 | 0.00601543 | 48854.9 | |
| 306_308 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 306_308 PTAC | GUESTROOM306_308 | N/A | N/A | N/A | Yes | Yes | unknown | No | 3594.104 | 2683.961 | 0.166399 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.3576 | 1004.8586 | 1.1739 | 306_308 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.166399 | 0.19533963 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | unknown | unknown | unknown | 7/21 18:40:00 | Sensible | 3609.63 | 2614.44 | 1.0043 | 0.19533963 | 0.166399 | 23.17 | 17.07 | 0.00996132 | 48624.8 | 9.47 | 9.47 | 0.00800000 | 29664.0 | -999.0 | -999.00 | -999.00 | -999.00 | 105.974 | 3503.65 | 27.14 | 0.01336135 | 20.91 | 0.04273309 | 25.6811 | 21.11 | 0.00819553 | 21.11 | 0.00819553 | 51.2849 | 1662.75 | 0.00 | 3595.86 | 2650.40 | 0.18762519 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 12.84 | 12.82 | 0.00920895 | 36157.2 | |
| 309_312 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 309_312 PTAC | GUESTROOM309_312 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7520.639 | 7520.639 | 0.383875 | 0.00006579 | 180.475 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 309_312 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.383875 | 0.45064036 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 2.5304 | 2.581318 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 7520.64 | 7520.64 | 1.0000 | 0.45064036 | 0.383875 | 15.86 | 11.45 | 0.00682248 | 33196.4 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.06578712 | 60.00 | 32.22 | 27.78 | 0.000 | 7520.64 | -16.30 | 0.00092409 | -16.30 | 0.05391910 | 14.0460 | 21.11 | 0.00778635 | 21.11 | 0.00778635 | 48.7562 | 2893.93 | 0.00 | 7895.21 | 7895.21 | 0.45064036 | 12.80 | 10.37 | 0.00682248 | 30086.9 | 30.02 | 17.07 | 0.00682248 | 47606.9 | |
| 309_312 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 309_312 PTAC | GUESTROOM309_312 | N/A | N/A | N/A | Yes | Yes | unknown | No | 7051.148 | 5643.250 | 0.383875 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.6899 | 1004.8586 | 1.1739 | 309_312 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.383875 | 0.45064036 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | unknown | unknown | unknown | 7/21 18:40:00 | Sensible | 6817.51 | 5552.22 | 0.9669 | 0.45064036 | 0.383875 | 21.96 | 15.89 | 0.00906421 | 45101.6 | 9.47 | 9.47 | 0.00800000 | 29663.1 | -999.0 | -999.00 | -999.00 | -999.00 | 244.477 | 6573.03 | 27.14 | 0.01336135 | 20.91 | 0.05391910 | 14.0460 | 21.11 | 0.00836200 | 21.11 | 0.00836200 | 52.3164 | 5105.15 | 0.00 | 7054.60 | 5565.11 | 0.43284347 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.10 | 13.91 | 0.00983546 | 39024.1 | |
| 313 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 313 PTAC | GUESTROOM313 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1960.251 | 1960.251 | 0.101990 | 0.00001715 | 47.173 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 313 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.101990 | 0.11972856 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.6595 | 0.672820 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 1960.25 | 1960.25 | 1.0000 | 0.11972856 | 0.101990 | 16.17 | 11.72 | 0.00696450 | 33871.5 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.01714739 | 60.00 | 32.22 | 27.78 | 0.000 | 1960.25 | -16.30 | 0.00092409 | -16.30 | 0.01347978 | 13.2168 | 21.11 | 0.00788443 | 21.11 | 0.00788443 | 49.3627 | 1356.59 | 0.00 | 2067.61 | 2067.61 | 0.11972856 | 12.80 | 10.52 | 0.00696450 | 30445.5 | 29.77 | 17.10 | 0.00696450 | 47714.6 | |
| 313 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 313 PTAC | GUESTROOM313 | N/A | N/A | N/A | Yes | Yes | unknown | No | 1966.476 | 1554.787 | 0.101990 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1075 | 1004.8586 | 1.1739 | 313 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.101990 | 0.11972856 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | unknown | unknown | unknown | 7/21 18:50:00 | Sensible | 1927.69 | 1522.67 | 0.9803 | 0.11972856 | 0.101990 | 22.40 | 16.24 | 0.00928885 | 46123.8 | 9.47 | 9.47 | 0.00800000 | 29663.3 | -999.0 | -999.00 | -999.00 | -999.00 | 64.954 | 1862.74 | 26.91 | 0.01336094 | 20.84 | 0.01347978 | 13.2168 | 21.11 | 0.00812614 | 21.11 | 0.00812614 | 50.8561 | 807.19 | 0.00 | 1967.44 | 1533.67 | 0.11500019 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.63 | 13.61 | 0.00970580 | 38214.3 | |
| 314 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 314 PTAC | GUESTROOM314 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2346.089 | 2346.089 | 0.131002 | 0.00002052 | 57.038 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 314 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.131002 | 0.15378605 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.7894 | 0.805251 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 2346.09 | 2346.09 | 1.0000 | 0.15378605 | 0.131002 | 17.26 | 12.37 | 0.00716504 | 35494.2 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.02052252 | 60.00 | 32.22 | 27.78 | 0.000 | 2346.09 | -16.30 | 0.00092409 | -16.30 | 0.01347882 | 10.2891 | 21.11 | 0.00788082 | 21.11 | 0.00788082 | 49.3402 | 1314.75 | 0.00 | 2516.61 | 2516.61 | 0.15378605 | 12.80 | 10.73 | 0.00716504 | 30951.8 | 28.87 | 16.96 | 0.00716504 | 47316.1 | |
| 314 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 314 PTAC | GUESTROOM314 | N/A | N/A | N/A | Yes | Yes | unknown | No | 2415.533 | 1932.576 | 0.131002 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1814 | 1004.8586 | 1.1739 | 314 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.131002 | 0.15378605 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 2237.30 | 1915.66 | 0.9262 | 0.15378605 | 0.131002 | 22.06 | 15.69 | 0.00879067 | 44507.4 | 9.47 | 9.47 | 0.00800000 | 29662.8 | -999.0 | -999.00 | -999.00 | -999.00 | 83.430 | 2153.87 | 30.30 | 0.01336696 | 21.83 | 0.01347882 | 10.2891 | 21.11 | 0.00826581 | 21.11 | 0.00826581 | 51.7219 | 1742.22 | 0.00 | 2416.72 | 1905.65 | 0.14771267 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.06 | 13.89 | 0.00982813 | 38961.5 | |
| 315_318 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 315_318 PTAC | GUESTROOM315_318 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9639.657 | 9639.657 | 0.543195 | 0.00008433 | 234.671 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 315_318 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.543195 | 0.63766981 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 3.2434 | 3.308631 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 9639.66 | 9639.66 | 1.0000 | 0.63766981 | 0.543195 | 17.40 | 12.36 | 0.00710520 | 35481.0 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.08432332 | 60.00 | 32.22 | 27.78 | 0.000 | 9639.66 | -16.30 | 0.00092409 | -16.30 | 0.05391527 | 9.9256 | 21.11 | 0.00778632 | 21.11 | 0.00778632 | 48.7563 | 2893.45 | 0.00 | 10362.10 | 10362.10 | 0.63766981 | 12.80 | 10.67 | 0.00710520 | 30800.7 | 28.76 | 16.87 | 0.00710520 | 47050.7 | |
| 315_318 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 315_318 PTAC | GUESTROOM315_318 | N/A | N/A | N/A | Yes | Yes | unknown | No | 9959.937 | 7977.092 | 0.543195 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1314 | 1004.8586 | 1.1739 | 315_318 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.543195 | 0.63766981 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | unknown | unknown | 7/21 14:00:00 | Sensible | 9214.21 | 7925.21 | 0.9251 | 0.63766981 | 0.543195 | 22.02 | 15.65 | 0.00876377 | 44404.8 | 9.47 | 9.47 | 0.00800000 | 29662.8 | -999.0 | -999.00 | -999.00 | -999.00 | 345.942 | 8868.27 | 30.30 | 0.01336696 | 21.83 | 0.05391527 | 9.9256 | 21.11 | 0.00825653 | 21.11 | 0.00825653 | 51.6650 | 7223.97 | 0.00 | 9964.81 | 7866.85 | 0.61248667 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.11 | 13.92 | 0.00984167 | 39053.0 | |
| 319 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 319 PTAC | GUESTROOM319 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2197.756 | 2197.756 | 0.119849 | 0.00001923 | 53.253 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 319 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.119849 | 0.14069356 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.7395 | 0.754338 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 24:00:00 | Sensible | 2197.76 | 2197.76 | 1.0000 | 0.14069356 | 0.119849 | 16.90 | 12.09 | 0.00703417 | 34798.1 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.01922497 | 60.00 | 32.22 | 27.78 | 0.000 | 2197.76 | -16.30 | 0.00092409 | -16.30 | 0.01347882 | 11.2465 | 21.11 | 0.00780842 | 21.11 | 0.00780842 | 48.8928 | 809.41 | 0.00 | 2344.47 | 2344.47 | 0.14069356 | 12.80 | 10.59 | 0.00703417 | 30621.4 | 29.17 | 16.95 | 0.00703417 | 47285.0 | |
| 319 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 319 PTAC | GUESTROOM319 | N/A | N/A | N/A | Yes | Yes | unknown | No | 2179.781 | 1745.178 | 0.119849 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9392 | 1004.8586 | 1.1739 | 319 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.119849 | 0.14069356 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | unknown | unknown | 7/21 14:00:00 | Sensible | 2013.50 | 1767.50 | 0.9237 | 0.14069356 | 0.119849 | 22.14 | 15.61 | 0.00866035 | 44266.9 | 9.47 | 9.47 | 0.00800000 | 29662.7 | -999.0 | -999.00 | -999.00 | -999.00 | 76.328 | 1937.18 | 30.30 | 0.01336696 | 21.83 | 0.01347882 | 11.2465 | 21.11 | 0.00806394 | 21.11 | 0.00806394 | 50.4718 | 1594.04 | 0.00 | 2180.85 | 1721.37 | 0.13513723 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.22 | 13.97 | 0.00985157 | 39184.4 | |
| 320_323 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 320_323 PTAC | GUESTROOM320_323 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8566.451 | 8566.451 | 0.462510 | 0.00007494 | 207.274 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 320_323 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.462510 | 0.54295223 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 2.8823 | 2.940273 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:20:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 17:20:00 | Sensible | 8566.45 | 8566.45 | 1.0000 | 0.54295223 | 0.462510 | 16.75 | 11.98 | 0.00698344 | 34513.2 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.07493540 | 60.00 | 32.22 | 27.78 | 0.000 | 8566.45 | -16.30 | 0.00092409 | -16.30 | 0.05391527 | 11.6571 | 21.11 | 0.00778298 | 21.11 | 0.00778298 | 48.7356 | 2847.57 | 0.00 | 9116.71 | 9116.71 | 0.54295223 | 12.80 | 10.54 | 0.00698344 | 30493.3 | 29.30 | 16.95 | 0.00698344 | 47284.3 | |
| 320_323 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 320_323 PTAC | GUESTROOM320_323 | N/A | N/A | N/A | Yes | Yes | unknown | No | 8705.611 | 6967.412 | 0.462510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3686 | 1004.8586 | 1.1739 | 320_323 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.462510 | 0.54295223 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | unknown | unknown | 7/21 14:00:00 | Sensible | 8098.64 | 6821.10 | 0.9303 | 0.54295223 | 0.462510 | 22.18 | 15.82 | 0.00889136 | 44891.7 | 9.47 | 9.47 | 0.00800000 | 29662.9 | -999.0 | -999.00 | -999.00 | -999.00 | 294.557 | 7804.08 | 30.30 | 0.01336696 | 21.83 | 0.05391527 | 11.6571 | 21.11 | 0.00830079 | 21.11 | 0.00830079 | 51.9383 | 6150.93 | 0.00 | 8709.87 | 6872.03 | 0.52150972 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.79 | 13.76 | 0.00980295 | 38621.1 | |
| 324 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 324 PTAC | GUESTROOM324 | N/A | N/A | N/A | Yes | Yes | Yes | No | 1708.584 | 1708.584 | 0.083073 | 0.00001495 | 40.700 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 324 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.083073 | 0.09752137 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.5749 | 0.586440 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 1708.58 | 1708.58 | 1.0000 | 0.09752137 | 0.083073 | 15.04 | 11.02 | 0.00673349 | 32141.8 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.01494592 | 60.00 | 32.22 | 27.78 | 0.000 | 1708.58 | -16.30 | 0.00092409 | -16.30 | 0.01347882 | 16.2253 | 21.11 | 0.00785864 | 21.11 | 0.00785864 | 49.2031 | 1104.97 | 0.00 | 1771.77 | 1771.77 | 0.09752137 | 12.80 | 10.27 | 0.00673349 | 29862.2 | 30.66 | 17.21 | 0.00673349 | 48030.2 | |
| 324 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 324 PTAC | GUESTROOM324 | N/A | N/A | N/A | Yes | Yes | unknown | No | 1612.965 | 1271.740 | 0.083073 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4927 | 1004.8586 | 1.1739 | 324 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.083073 | 0.09752137 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:10:00 | unknown | unknown | unknown | 7/21 14:10:00 | Sensible | 1511.15 | 1265.38 | 0.9369 | 0.09752137 | 0.083073 | 22.62 | 16.03 | 0.00895815 | 45508.2 | 9.47 | 9.47 | 0.00800000 | 29663.0 | -999.0 | -999.00 | -999.00 | -999.00 | 52.906 | 1458.25 | 30.30 | 0.01336696 | 21.83 | 0.01347882 | 16.2253 | 21.11 | 0.00809287 | 21.11 | 0.00809287 | 50.6506 | 1092.71 | 0.00 | 1613.75 | 1254.68 | 0.09367001 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.57 | 13.56 | 0.00968168 | 38094.3 | |
| FRONTSTAIRSFLR3 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONTSTAIRSFLR3 UNIT HEATER | FRONTSTAIRSFLR3 | N/A | N/A | N/A | Yes | No | unknown | No | 404.270 | 404.270 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | FRONTSTAIRSFLR3 UNITHEATER FAN | Fan:ConstantVolume | 0.030385 | 0.03566919 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 404.27 | 404.27 | 1.0000 | 0.03566919 | 0.030385 | 7.20 | 5.86 | 0.00534588 | 20672.4 | 18.31 | 13.58 | 0.00800000 | 38679.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 404.27 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 7.20 | 0.00534588 | 7.20 | 0.00534588 | 82.8798 | 404.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| REARSTAIRSFLR4 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | REARSTAIRSFLR4 UNIT HEATER | REARSTAIRSFLR4 | N/A | N/A | N/A | Yes | No | unknown | No | 290.543 | 290.543 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | REARSTAIRSFLR4 UNITHEATER FAN | Fan:ConstantVolume | 0.021838 | 0.02563635 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 290.54 | 290.54 | 1.0000 | 0.02563635 | 0.021838 | 7.20 | 5.01 | 0.00465848 | 18944.7 | 18.31 | 13.58 | 0.00800000 | 38679.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 290.54 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 7.20 | 0.00465848 | 7.20 | 0.00465848 | 72.2989 | 290.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| CORRIDORFLR4 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR4 PTAC | CORRIDORFLR4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6519.649 | 6519.649 | 0.361442 | 0.00005704 | 158.351 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | CORRIDORFLR4 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.361442 | 0.42430605 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 2.1936 | 2.237747 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 6519.65 | 6519.65 | 1.0000 | 0.42430605 | 0.361442 | 17.15 | 12.20 | 0.00704369 | 35077.2 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.05703091 | 60.00 | 32.22 | 27.78 | 0.000 | 6519.65 | -16.30 | 0.00092409 | -16.30 | 0.03822807 | 10.5765 | 21.11 | 0.00776748 | 21.11 | 0.00776748 | 48.6401 | 4807.73 | 0.00 | 6981.84 | 6981.84 | 0.42430605 | 12.80 | 10.60 | 0.00704369 | 30645.4 | 28.96 | 16.89 | 0.00704369 | 47100.1 | |
| CORRIDORFLR4 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | CORRIDORFLR4 PTAC | CORRIDORFLR4 | N/A | N/A | N/A | Yes | Yes | unknown | No | 7018.703 | 5533.621 | 0.361442 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.4775 | 1004.8586 | 1.1739 | CORRIDORFLR4 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.361442 | 0.42430605 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | unknown | unknown | unknown | 7/21 14:50:00 | Sensible | 6848.50 | 5453.69 | 0.9757 | 0.42430605 | 0.361442 | 24.85 | 17.25 | 0.00948787 | 49134.8 | 12.25 | 11.14 | 0.00800000 | 32496.3 | -999.0 | -999.00 | -999.00 | -999.00 | 230.190 | 6618.31 | 30.30 | 0.01336696 | 21.83 | 0.03822807 | 10.5765 | 23.89 | 0.00880441 | 23.89 | 0.00880441 | 46.4968 | 3393.72 | 0.00 | 7022.14 | 5459.38 | 0.40754917 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.57 | 13.56 | 0.00968123 | 38092.2 | |
| 401 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 401 PTAC | GUESTROOM401 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2395.887 | 2395.887 | 0.134734 | 0.00002096 | 58.311 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 401 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.134734 | 0.15816801 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.8061 | 0.822343 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 2395.89 | 2395.89 | 1.0000 | 0.15816801 | 0.134734 | 17.37 | 12.26 | 0.00701570 | 35223.6 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.02095812 | 60.00 | 32.22 | 27.78 | 0.000 | 2395.89 | -16.30 | 0.00092409 | -16.30 | 0.01347978 | 10.0047 | 21.11 | 0.00769290 | 21.11 | 0.00769290 | 48.1802 | 1636.71 | 0.00 | 2574.24 | 2574.24 | 0.15816801 | 12.80 | 10.57 | 0.00701570 | 30574.7 | 28.79 | 16.81 | 0.00701570 | 46850.1 | |
| 401 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 401 PTAC | GUESTROOM401 | N/A | N/A | N/A | Yes | Yes | unknown | No | 2498.503 | 1999.286 | 0.134734 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3459 | 1004.8586 | 1.1739 | 401 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.134734 | 0.15816801 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | unknown | unknown | unknown | 7/21 13:20:00 | Sensible | 2326.87 | 1959.32 | 0.9313 | 0.15816801 | 0.134734 | 22.00 | 15.74 | 0.00887913 | 44673.4 | 9.47 | 9.47 | 0.00800000 | 29662.9 | -999.0 | -999.00 | -999.00 | -999.00 | 85.808 | 2241.07 | 29.99 | 0.01336641 | 21.74 | 0.01347978 | 10.0047 | 21.11 | 0.00838028 | 21.11 | 0.00838028 | 52.4305 | 1791.77 | 0.00 | 2499.73 | 1971.96 | 0.15192157 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.98 | 13.85 | 0.00982260 | 38868.3 | |
| 402_405 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 402_405 PTAC | GUESTROOM402_405 | N/A | N/A | N/A | Yes | Yes | Yes | No | 6800.005 | 6800.005 | 0.329696 | 0.00005949 | 161.915 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 402_405 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.329696 | 0.38703863 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 2.2879 | 2.333974 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 6800.00 | 6800.00 | 1.0000 | 0.38703863 | 0.329696 | 14.99 | 10.98 | 0.00671533 | 32046.8 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.05948334 | 60.00 | 32.22 | 27.78 | 0.000 | 6800.00 | -16.30 | 0.00092409 | -16.30 | 0.05391910 | 16.3542 | 21.11 | 0.00784761 | 21.11 | 0.00784761 | 49.1350 | 4385.38 | 0.00 | 7046.36 | 7046.36 | 0.38703863 | 12.80 | 10.25 | 0.00671533 | 29816.4 | 30.70 | 17.21 | 0.00671533 | 48022.2 | |
| 402_405 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 402_405 PTAC | GUESTROOM402_405 | N/A | N/A | N/A | Yes | Yes | unknown | No | 6912.987 | 5241.809 | 0.329696 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.2209 | 1004.8586 | 1.1739 | 402_405 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.329696 | 0.38703863 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 6596.38 | 5232.62 | 0.9542 | 0.38703863 | 0.329696 | 23.24 | 16.58 | 0.00934986 | 47138.0 | 9.47 | 9.47 | 0.00800000 | 29663.4 | -999.0 | -999.00 | -999.00 | -999.00 | 209.972 | 6386.41 | 30.30 | 0.01336696 | 21.83 | 0.05391910 | 16.3542 | 21.11 | 0.00813960 | 21.11 | 0.00813960 | 50.9395 | 3097.48 | 0.00 | 6916.37 | 5176.00 | 0.37175353 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.05 | 13.03 | 0.00934914 | 36717.7 | |
| 406_408 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 406_408 PTAC | GUESTROOM406_408 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5368.857 | 5368.857 | 0.259762 | 0.00004697 | 127.797 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 406_408 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.259762 | 0.30494142 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 1.8064 | 1.842759 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 5368.86 | 5368.86 | 1.0000 | 0.30494142 | 0.259762 | 14.96 | 10.95 | 0.00670550 | 31985.1 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.04696432 | 60.00 | 32.22 | 27.78 | 0.000 | 5368.86 | -16.30 | 0.00092409 | -16.30 | 0.04273309 | 16.4508 | 21.11 | 0.00784386 | 21.11 | 0.00784386 | 49.1119 | 3455.17 | 0.00 | 5560.35 | 5560.35 | 0.30494142 | 12.80 | 10.24 | 0.00670550 | 29791.6 | 30.72 | 17.21 | 0.00670550 | 48025.7 | |
| 406_408 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 406_408 PTAC | GUESTROOM406_408 | N/A | N/A | N/A | Yes | Yes | unknown | No | 5414.232 | 4114.774 | 0.259762 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1022.1631 | 1004.8586 | 1.1739 | 406_408 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.259762 | 0.30494142 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 5158.55 | 4108.22 | 0.9528 | 0.30494142 | 0.259762 | 23.18 | 16.54 | 0.00931874 | 47004.2 | 9.47 | 9.47 | 0.00800000 | 29663.3 | -999.0 | -999.00 | -999.00 | -999.00 | 165.434 | 4993.12 | 30.30 | 0.01336696 | 21.83 | 0.04273309 | 16.4508 | 21.11 | 0.00813872 | 21.11 | 0.00813872 | 50.9340 | 2518.21 | 0.00 | 5416.88 | 4062.54 | 0.29289854 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.10 | 13.08 | 0.00937172 | 36828.3 | |
| 409_412 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 409_412 PTAC | GUESTROOM409_412 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9018.344 | 9018.344 | 0.496474 | 0.00007890 | 218.814 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 409_412 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.496474 | 0.58282303 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 3.0343 | 3.095377 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 9018.34 | 9018.34 | 1.0000 | 0.58282303 | 0.496474 | 17.05 | 12.21 | 0.00709649 | 35103.0 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.07888836 | 60.00 | 32.22 | 27.78 | 0.000 | 9018.34 | -16.30 | 0.00092409 | -16.30 | 0.05391910 | 10.8604 | 21.11 | 0.00784851 | 21.11 | 0.00784851 | 49.1406 | 4412.10 | 0.00 | 9641.85 | 9641.85 | 0.58282303 | 12.80 | 10.66 | 0.00709649 | 30778.7 | 29.05 | 16.96 | 0.00709649 | 47322.1 | |
| 409_412 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 409_412 PTAC | GUESTROOM409_412 | N/A | N/A | N/A | Yes | Yes | unknown | No | 9239.097 | 7391.632 | 0.496474 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2667 | 1004.8586 | 1.1739 | 409_412 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.496474 | 0.58282303 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | unknown | unknown | unknown | 7/21 14:20:00 | Sensible | 8573.99 | 7285.50 | 0.9280 | 0.58282303 | 0.496474 | 22.11 | 15.75 | 0.00883655 | 44677.5 | 9.47 | 9.47 | 0.00800000 | 29662.9 | -999.0 | -999.00 | -999.00 | -999.00 | 316.187 | 8257.80 | 30.30 | 0.01336696 | 21.83 | 0.05391910 | 10.8604 | 21.11 | 0.00828458 | 21.11 | 0.00828458 | 51.8383 | 6602.61 | 0.00 | 9243.62 | 7289.90 | 0.55980593 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.94 | 13.83 | 0.00981631 | 38810.2 | |
| 413 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 413 PTAC | GUESTROOM413 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2431.720 | 2431.720 | 0.137436 | 0.00002127 | 59.221 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 413 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.137436 | 0.16133968 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.8182 | 0.834642 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 2431.72 | 2431.72 | 1.0000 | 0.16133968 | 0.137436 | 17.44 | 12.50 | 0.00722285 | 35823.9 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.02127158 | 60.00 | 32.22 | 27.78 | 0.000 | 2431.72 | -16.30 | 0.00092409 | -16.30 | 0.01347978 | 9.8080 | 21.11 | 0.00790781 | 21.11 | 0.00790781 | 49.5071 | 1828.06 | 0.00 | 2615.76 | 2615.76 | 0.16133968 | 12.80 | 10.79 | 0.00722285 | 31097.7 | 28.72 | 16.96 | 0.00722285 | 47310.5 | |
| 413 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 413 PTAC | GUESTROOM413 | N/A | N/A | N/A | Yes | Yes | unknown | No | 2649.593 | 2094.993 | 0.137436 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4336 | 1004.8586 | 1.1739 | 413 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.137436 | 0.16133968 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | unknown | unknown | unknown | 7/21 15:00:00 | Sensible | 2478.37 | 2084.97 | 0.9354 | 0.16133968 | 0.137436 | 22.56 | 15.99 | 0.00892635 | 45366.9 | 9.47 | 9.47 | 0.00800000 | 29662.9 | -999.0 | -999.00 | -999.00 | -999.00 | 87.528 | 2390.84 | 30.30 | 0.01336696 | 21.83 | 0.01347978 | 9.8080 | 21.11 | 0.00809548 | 21.11 | 0.00809548 | 50.6667 | 1137.48 | 0.00 | 2650.89 | 2066.55 | 0.15496798 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 13.63 | 13.61 | 0.00970625 | 38216.3 | |
| 414 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 414 PTAC | GUESTROOM414 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2339.482 | 2339.482 | 0.130505 | 0.00002047 | 56.869 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 414 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.130505 | 0.15320273 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.7871 | 0.802983 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 2339.48 | 2339.48 | 1.0000 | 0.15320273 | 0.130505 | 17.25 | 12.38 | 0.00718219 | 35522.8 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.02046472 | 60.00 | 32.22 | 27.78 | 0.000 | 2339.48 | -16.30 | 0.00092409 | -16.30 | 0.01347882 | 10.3282 | 21.11 | 0.00790298 | 21.11 | 0.00790298 | 49.4773 | 1735.87 | 0.00 | 2508.95 | 2508.95 | 0.15320273 | 12.80 | 10.75 | 0.00718219 | 30995.1 | 28.88 | 16.98 | 0.00718219 | 47371.7 | |
| 414 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 414 PTAC | GUESTROOM414 | N/A | N/A | N/A | Yes | Yes | unknown | No | 2392.167 | 1913.786 | 0.130505 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0054 | 1004.8586 | 1.1739 | 414 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.130505 | 0.15320273 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | unknown | unknown | 7/21 14:00:00 | Sensible | 2213.27 | 1931.17 | 0.9252 | 0.15320273 | 0.130505 | 22.19 | 15.66 | 0.00869598 | 44408.4 | 9.47 | 9.47 | 0.00800000 | 29662.7 | -999.0 | -999.00 | -999.00 | -999.00 | 83.114 | 2130.16 | 30.30 | 0.01336696 | 21.83 | 0.01347882 | 10.3282 | 21.11 | 0.00807170 | 21.11 | 0.00807170 | 50.5198 | 1520.63 | 0.00 | 2393.34 | 1887.39 | 0.14715238 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.13 | 13.93 | 0.00983661 | 39058.0 | |
| 415_418 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 415_418 PTAC | GUESTROOM415_418 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10613.283 | 10613.283 | 0.616396 | 0.00009285 | 259.461 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 415_418 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.616396 | 0.72360297 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 3.5709 | 3.642810 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 10613.28 | 10613.28 | 1.0000 | 0.72360297 | 0.616396 | 17.84 | 12.67 | 0.00724238 | 36277.6 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.09284016 | 60.00 | 32.22 | 27.78 | 0.000 | 10613.28 | -16.30 | 0.00092409 | -16.30 | 0.05391527 | 8.7469 | 21.11 | 0.00784800 | 21.11 | 0.00784800 | 49.1375 | 4397.03 | 0.00 | 11487.41 | 11487.41 | 0.72360297 | 12.80 | 10.81 | 0.00724238 | 31147.0 | 28.39 | 16.86 | 0.00724238 | 47022.3 | |
| 415_418 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 415_418 PTAC | GUESTROOM415_418 | N/A | N/A | N/A | Yes | Yes | unknown | No | 11070.480 | 8865.948 | 0.616396 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9739 | 1004.8586 | 1.1739 | 415_418 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.616396 | 0.72360297 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 10220.46 | 8917.54 | 0.9232 | 0.72360297 | 0.616396 | 21.90 | 15.54 | 0.00867903 | 44065.0 | 9.47 | 9.47 | 0.00800000 | 29662.7 | -999.0 | -999.00 | -999.00 | -999.00 | 392.561 | 9827.90 | 30.14 | 0.01336669 | 21.78 | 0.05391527 | 8.7469 | 21.11 | 0.00822970 | 21.11 | 0.00822970 | 51.4993 | 8197.48 | 0.00 | 11075.90 | 8743.30 | 0.69502612 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.37 | 14.05 | 0.00986880 | 39386.4 | |
| 419 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 419 PTAC | GUESTROOM419 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2811.685 | 2811.685 | 0.166006 | 0.00002460 | 68.893 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 419 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.166006 | 0.19487808 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.9460 | 0.965058 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 2811.68 | 2811.68 | 1.0000 | 0.19487808 | 0.166006 | 18.07 | 12.83 | 0.00730603 | 36678.0 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.02459534 | 60.00 | 32.22 | 27.78 | 0.000 | 2811.68 | -16.30 | 0.00092409 | -16.30 | 0.01347882 | 8.1195 | 21.11 | 0.00787001 | 21.11 | 0.00787001 | 49.2734 | 1289.40 | 0.00 | 3054.48 | 3054.48 | 0.19487808 | 12.80 | 10.88 | 0.00730603 | 31307.7 | 28.19 | 16.84 | 0.00730603 | 46981.5 | |
| 419 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 419 PTAC | GUESTROOM419 | N/A | N/A | N/A | Yes | Yes | unknown | No | 2955.195 | 2366.744 | 0.166006 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8861 | 1004.8586 | 1.1739 | 419 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.166006 | 0.19487808 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | unknown | unknown | unknown | 7/21 13:50:00 | Sensible | 2720.45 | 2393.65 | 0.9206 | 0.19487808 | 0.166006 | 21.85 | 15.48 | 0.00863178 | 43893.6 | 9.47 | 9.47 | 0.00800000 | 29662.6 | -999.0 | -999.00 | -999.00 | -999.00 | 105.723 | 2614.73 | 30.22 | 0.01336682 | 21.81 | 0.01347882 | 8.1195 | 21.11 | 0.00821335 | 21.11 | 0.00821335 | 51.3978 | 2207.74 | 0.00 | 2956.64 | 2334.31 | 0.18718187 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.48 | 14.10 | 0.00988109 | 39526.8 | |
| 420_423 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 420_423 PTAC | GUESTROOM420_423 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10496.918 | 10496.918 | 0.607648 | 0.00009183 | 256.500 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 420_423 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.607648 | 0.71333289 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 3.5318 | 3.602870 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 10496.92 | 10496.92 | 1.0000 | 0.71333289 | 0.607648 | 17.79 | 12.65 | 0.00723224 | 36203.9 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.09182225 | 60.00 | 32.22 | 27.78 | 0.000 | 10496.92 | -16.30 | 0.00092409 | -16.30 | 0.05391527 | 8.8728 | 21.11 | 0.00784644 | 21.11 | 0.00784644 | 49.1278 | 4351.27 | 0.00 | 11353.09 | 11353.09 | 0.71333289 | 12.80 | 10.80 | 0.00723224 | 31121.4 | 28.43 | 16.86 | 0.00723224 | 47037.0 | |
| 420_423 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 420_423 PTAC | GUESTROOM420_423 | N/A | N/A | N/A | Yes | Yes | unknown | No | 10935.322 | 8750.262 | 0.607648 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.9915 | 1004.8586 | 1.1739 | 420_423 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.607648 | 0.71333289 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | unknown | unknown | unknown | 7/21 13:40:00 | Sensible | 10099.80 | 8797.75 | 0.9236 | 0.71333289 | 0.607648 | 21.91 | 15.55 | 0.00868848 | 44100.6 | 9.47 | 9.47 | 0.00800000 | 29662.7 | -999.0 | -999.00 | -999.00 | -999.00 | 386.990 | 9712.81 | 30.14 | 0.01336669 | 21.78 | 0.05391527 | 8.8728 | 21.11 | 0.00823298 | 21.11 | 0.00823298 | 51.5195 | 8081.13 | 0.00 | 10940.68 | 8629.17 | 0.68516163 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.36 | 14.04 | 0.00986193 | 39354.4 | |
| 424 PTAC HEATING COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 424 PTAC | GUESTROOM424 | N/A | N/A | N/A | Yes | Yes | Yes | No | 2858.827 | 2858.827 | 0.169550 | 0.00002501 | 70.090 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | 424 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.169550 | 0.19903886 | 4197.9300 | 999.8980 | 2.54858627 | 54.44 | 82.22 | 27.78 | 297212.30 | 0.9619 | 0.981239 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 2858.83 | 2858.83 | 1.0000 | 0.19903886 | 0.169550 | 18.14 | 12.89 | 0.00733835 | 36824.6 | 32.22 | 18.49 | 0.00800000 | 52864.8 | 0.02500772 | 60.00 | 32.22 | 27.78 | 0.000 | 2858.83 | -16.30 | 0.00092409 | -16.30 | 0.01347882 | 7.9498 | 21.11 | 0.00789231 | 21.11 | 0.00789231 | 49.4113 | 1561.39 | 0.00 | 3108.79 | 3108.79 | 0.19903886 | 12.80 | 10.91 | 0.00733835 | 31389.3 | 28.14 | 16.85 | 0.00733835 | 47008.3 | |
| 424 PTAC PTAC COOLING COIL | COIL:COOLING:DX:SINGLESPEED | Zone Equipment | ZONEHVAC:PACKAGEDTERMINALAIRCONDITIONER | 424 PTAC | GUESTROOM424 | N/A | N/A | N/A | Yes | Yes | unknown | No | 3013.754 | 2412.180 | 0.169550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.8623 | 1004.8586 | 1.1739 | 424 PTAC_PTAC_SUPPLY FAN | Fan:OnOff | 0.169550 | 0.19903886 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | unknown | unknown | unknown | 7/21 14:00:00 | Sensible | 2770.49 | 2443.38 | 0.9193 | 0.19903886 | 0.169550 | 21.84 | 15.46 | 0.00861901 | 43851.6 | 9.47 | 9.47 | 0.00800000 | 29662.6 | -999.0 | -999.00 | -999.00 | -999.00 | 107.980 | 2662.51 | 30.30 | 0.01336696 | 21.83 | 0.01347882 | 7.9498 | 21.11 | 0.00820896 | 21.11 | 0.00820896 | 51.3707 | 2254.88 | 0.00 | 3015.23 | 2379.22 | 0.19117833 | 26.67 | 19.44 | 0.01118466 | 55322.4 | 14.50 | 14.11 | 0.00988031 | 39550.6 | |
| FRONTSTAIRSFLR4 UNITHEATER HEATING COIL | COIL:HEATING:FUEL | Zone Equipment | ZONEHVAC:UNITHEATER | FRONTSTAIRSFLR4 UNIT HEATER | FRONTSTAIRSFLR4 | N/A | N/A | N/A | Yes | No | unknown | No | 652.145 | 652.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | FRONTSTAIRSFLR4 UNITHEATER FAN | Fan:ConstantVolume | 0.049011 | 0.05753580 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 22:10:00 | Sensible | 652.14 | 652.14 | 1.0000 | 0.05753580 | 0.049011 | 7.20 | 6.63 | 0.00598322 | 22274.2 | 18.31 | 13.58 | 0.00800000 | 38679.6 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 652.14 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 7.19 | 0.00598322 | 7.20 | 0.00598322 | 92.6711 | 652.19 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR1 | 4044.00 | 2764.00 | 10.67 |
| FRONTLOUNGEFLR1 | 3600.00 | 5982.67 | 1641.83 |
| RESTROOMFLR1 | 980.33 | 3975.83 | 134.00 |
| MEETINGROOMFLR1 | 728.00 | 1382.83 | 338.17 |
| MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 |
| GUESTROOM101 | 0.00 | 0.00 | 0.00 |
| GUESTROOM102 | 0.00 | 0.00 | 0.00 |
| GUESTROOM103 | 2839.67 | 8107.17 | 2524.67 |
| GUESTROOM104 | 1362.17 | 7662.50 | 892.00 |
| GUESTROOM105 | 1204.83 | 6764.33 | 40.00 |
| EMPLOYEELOUNGEFLR1 | 5025.50 | 1729.67 | 1513.33 |
| EXERCISECENTERFLR1 | 2334.33 | 2785.83 | 80.17 |
| FRONTOFFICEFLR1 | 2821.17 | 4314.67 | 589.00 |
| FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR2 | 2304.83 | 4857.17 | 296.33 |
| GUESTROOM201 | 0.00 | 0.00 | 0.00 |
| GUESTROOM202_205 | 2678.00 | 7482.50 | 1837.17 |
| GUESTROOM206_208 | 2088.33 | 7471.33 | 1306.00 |
| GUESTROOM209_212 | 1853.50 | 7539.17 | 1144.33 |
| GUESTROOM213 | 3164.33 | 7825.17 | 2710.00 |
| GUESTROOM214 | 1540.33 | 7201.33 | 598.83 |
| GUESTROOM215_218 | 0.00 | 0.00 | 0.00 |
| GUESTROOM219 | 5111.83 | 2818.83 | 1095.17 |
| GUESTROOM220_223 | 1278.83 | 7111.83 | 270.00 |
| GUESTROOM224 | 1786.17 | 7269.17 | 933.50 |
| FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR3 | 3368.50 | 5792.67 | 2175.83 |
| GUESTROOM301 | 0.00 | 0.00 | 0.00 |
| GUESTROOM302_305 | 0.00 | 0.00 | 0.00 |
| GUESTROOM306_308 | 0.00 | 0.00 | 0.00 |
| GUESTROOM309_312 | 2484.00 | 7628.67 | 1831.67 |
| GUESTROOM313 | 0.00 | 0.00 | 0.00 |
| GUESTROOM314 | 2616.67 | 7383.17 | 1808.33 |
| GUESTROOM315_318 | 1522.50 | 6759.67 | 126.33 |
| GUESTROOM319 | 0.00 | 0.00 | 0.00 |
| GUESTROOM320_323 | 1524.67 | 7280.83 | 637.83 |
| GUESTROOM324 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR4 | 4827.17 | 6391.33 | 3474.33 |
| GUESTROOM401 | 4938.67 | 7440.50 | 4011.33 |
| GUESTROOM402_405 | 0.00 | 0.00 | 0.00 |
| GUESTROOM406_408 | 0.00 | 0.00 | 0.00 |
| GUESTROOM409_412 | 3911.00 | 7281.50 | 2824.67 |
| GUESTROOM413 | 0.00 | 0.00 | 0.00 |
| GUESTROOM414 | 0.00 | 0.00 | 0.00 |
| GUESTROOM415_418 | 3003.33 | 6863.00 | 1486.83 |
| GUESTROOM419 | 2825.67 | 6995.83 | 1532.83 |
| GUESTROOM420_423 | 3120.33 | 6942.83 | 1702.67 |
| GUESTROOM424 | 3676.17 | 7142.00 | 2508.83 |
| FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
| LAUNDRYROOMFLR1 | 2920.00 | 2920.00 | 2920.00 |
| ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 |
| Facility | 8502.83 | 8744.33 | 6673.17 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTLOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
| RESTROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
| MEETINGROOMFLR1 | 0.33 | 0.00 | 0.17 | 0.00 |
| MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM103 | 0.00 | 118.50 | 0.00 | 118.50 |
| GUESTROOM104 | 0.00 | 121.50 | 0.00 | 121.50 |
| GUESTROOM105 | 0.00 | 109.33 | 0.00 | 109.33 |
| EMPLOYEELOUNGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
| EXERCISECENTERFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTOFFICEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM202_205 | 0.00 | 134.83 | 0.00 | 134.83 |
| GUESTROOM206_208 | 0.00 | 136.67 | 0.00 | 136.67 |
| GUESTROOM209_212 | 0.00 | 136.50 | 0.00 | 136.50 |
| GUESTROOM213 | 0.00 | 119.50 | 0.00 | 119.50 |
| GUESTROOM214 | 0.00 | 114.00 | 0.00 | 114.00 |
| GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM219 | 0.00 | 2.17 | 0.00 | 2.17 |
| GUESTROOM220_223 | 0.00 | 115.33 | 0.00 | 115.33 |
| GUESTROOM224 | 0.00 | 112.50 | 0.00 | 112.50 |
| FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR3 | 3.33 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM309_312 | 0.00 | 137.83 | 0.00 | 137.83 |
| GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM314 | 0.00 | 121.17 | 0.00 | 121.17 |
| GUESTROOM315_318 | 0.00 | 116.00 | 0.00 | 116.00 |
| GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM320_323 | 0.00 | 119.33 | 0.00 | 119.33 |
| GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR3 | 0.33 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR4 | 26.17 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM401 | 0.17 | 96.17 | 0.17 | 96.17 |
| GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM409_412 | 0.00 | 94.83 | 0.00 | 94.83 |
| GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM415_418 | 0.00 | 106.33 | 0.00 | 106.33 |
| GUESTROOM419 | 0.00 | 107.17 | 0.00 | 107.17 |
| GUESTROOM420_423 | 0.00 | 105.33 | 0.00 | 105.33 |
| GUESTROOM424 | 0.00 | 103.67 | 0.00 | 103.67 |
| FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
| LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 26.67 | 239.67 | 0.33 | 239.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| REARSTAIRSFLR1 | 1.08 | 67.30 | |||||
| CORRIDORFLR1 | 2.24 | 8.10 | 504.62 | 0.333 | 0.785 | 0.000 | 0.000 |
| FRONTLOUNGEFLR1 | 14.68 | 53.00 | 546.70 | 1.575 | 0.053 | 0.000 | 0.000 |
| RESTROOMFLR1 | 0.49 | 1.75 | 109.34 | 0.000 | 0.037 | 0.000 | 0.000 |
| MEETINGROOMFLR1 | 15.31 | 43.00 | 269.14 | 1.435 | 0.039 | 0.000 | 0.000 |
| MECHANICALROOMFLR1 | 0.53 | 109.34 | |||||
| GUESTROOM101 | 1.50 | 109.34 | |||||
| GUESTROOM102 | 1.50 | 109.34 | |||||
| GUESTROOM103 | 0.96 | 1.50 | 109.34 | 0.332 | 0.037 | 0.000 | 0.007 |
| GUESTROOM104 | 0.96 | 1.50 | 109.33 | 0.332 | 0.037 | 0.000 | 0.007 |
| GUESTROOM105 | 0.96 | 1.50 | 109.33 | 0.341 | 0.037 | 0.000 | 0.004 |
| EMPLOYEELOUNGEFLR1 | 3.53 | 18.00 | 109.33 | 1.720 | 0.040 | 0.000 | 0.000 |
| EXERCISECENTERFLR1 | 6.34 | 7.00 | 109.33 | 1.440 | 0.039 | 0.000 | 0.000 |
| FRONTOFFICEFLR1 | 4.37 | 10.00 | 437.33 | 0.471 | 0.037 | 0.000 | 0.000 |
| FRONTSTAIRSFLR1 | 1.08 | 67.28 | |||||
| REARSTAIRSFLR2 | 1.08 | 55.06 | |||||
| CORRIDORFLR2 | 1.87 | 6.75 | 344.05 | 0.406 | 0.082 | 0.000 | 0.000 |
| GUESTROOM201 | 1.50 | 89.46 | |||||
| GUESTROOM202_205 | 3.82 | 6.00 | 357.84 | 0.409 | 0.047 | 0.000 | 0.002 |
| GUESTROOM206_208 | 2.87 | 4.50 | 289.02 | 0.401 | 0.047 | 0.000 | 0.002 |
| GUESTROOM209_212 | 3.82 | 6.00 | 357.84 | 0.408 | 0.047 | 0.000 | 0.002 |
| GUESTROOM213 | 0.96 | 1.50 | 89.46 | 0.409 | 0.047 | 0.000 | 0.009 |
| GUESTROOM214 | 0.96 | 1.50 | 89.45 | 0.412 | 0.047 | 0.000 | 0.007 |
| GUESTROOM215_218 | 6.00 | 357.81 | |||||
| GUESTROOM219 | 0.96 | 1.50 | 89.45 | 0.432 | 0.047 | 0.000 | 0.002 |
| GUESTROOM220_223 | 3.82 | 6.00 | 357.81 | 0.412 | 0.047 | 0.000 | 0.002 |
| GUESTROOM224 | 0.96 | 1.50 | 89.45 | 0.411 | 0.047 | 0.000 | 0.008 |
| FRONTSTAIRSFLR2 | 1.08 | 55.05 | |||||
| REARSTAIRSFLR3 | 1.08 | 55.06 | |||||
| CORRIDORFLR3 | 1.87 | 6.75 | 344.05 | 0.405 | 0.091 | 0.000 | 0.000 |
| GUESTROOM301 | 1.50 | 89.46 | |||||
| GUESTROOM302_305 | 6.00 | 357.84 | |||||
| GUESTROOM306_308 | 4.50 | 289.02 | |||||
| GUESTROOM309_312 | 3.82 | 6.00 | 357.84 | 0.407 | 0.052 | 0.000 | 0.002 |
| GUESTROOM313 | 1.50 | 89.46 | |||||
| GUESTROOM314 | 0.96 | 1.50 | 89.45 | 0.410 | 0.052 | 0.000 | 0.009 |
| GUESTROOM315_318 | 3.82 | 6.00 | 357.81 | 0.417 | 0.052 | 0.000 | 0.001 |
| GUESTROOM319 | 1.50 | 89.45 | |||||
| GUESTROOM320_323 | 3.82 | 6.00 | 357.81 | 0.410 | 0.052 | 0.000 | 0.002 |
| GUESTROOM324 | 1.50 | 89.45 | |||||
| FRONTSTAIRSFLR3 | 1.08 | 55.05 | |||||
| REARSTAIRSFLR4 | 1.08 | 55.06 | |||||
| CORRIDORFLR4 | 1.87 | 6.75 | 344.05 | 0.405 | 0.097 | 0.000 | 0.000 |
| GUESTROOM401 | 0.96 | 1.50 | 89.46 | 0.423 | 0.170 | 0.000 | 0.008 |
| GUESTROOM402_405 | 6.00 | 357.84 | |||||
| GUESTROOM406_408 | 4.50 | 289.02 | |||||
| GUESTROOM409_412 | 3.82 | 6.00 | 357.84 | 0.412 | 0.055 | 0.000 | 0.002 |
| GUESTROOM413 | 1.50 | 89.46 | |||||
| GUESTROOM414 | 1.50 | 89.45 | |||||
| GUESTROOM415_418 | 3.82 | 6.00 | 357.81 | 0.415 | 0.055 | 0.000 | 0.002 |
| GUESTROOM419 | 0.96 | 1.50 | 89.45 | 0.414 | 0.055 | 0.000 | 0.007 |
| GUESTROOM420_423 | 3.82 | 6.00 | 357.81 | 0.413 | 0.055 | 0.000 | 0.002 |
| GUESTROOM424 | 0.96 | 1.50 | 89.45 | 0.414 | 0.055 | 0.000 | 0.008 |
| FRONTSTAIRSFLR4 | 1.08 | 55.05 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| REARSTAIRSFLR1 | 1.08 | 67.30 | |||||
| CORRIDORFLR1 | 2.24 | 8.10 | 504.62 | 0.318 | 0.000 | 0.000 | 0.000 |
| FRONTLOUNGEFLR1 | 14.68 | 53.00 | 546.70 | 1.510 | 0.000 | 0.000 | 0.000 |
| RESTROOMFLR1 | 0.49 | 1.75 | 109.34 | 0.000 | 0.000 | 0.000 | 0.000 |
| MEETINGROOMFLR1 | 15.31 | 43.00 | 269.14 | 0.000 | 0.000 | 0.000 | 0.000 |
| MECHANICALROOMFLR1 | 0.53 | 109.34 | |||||
| GUESTROOM101 | 1.50 | 109.34 | |||||
| GUESTROOM102 | 1.50 | 109.34 | |||||
| GUESTROOM103 | 0.96 | 1.50 | 109.34 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM104 | 0.96 | 1.50 | 109.33 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM105 | 0.96 | 1.50 | 109.33 | 0.000 | 0.000 | 0.000 | 0.000 |
| EMPLOYEELOUNGEFLR1 | 3.53 | 18.00 | 109.33 | 1.645 | 0.000 | 0.000 | 0.000 |
| EXERCISECENTERFLR1 | 6.34 | 7.00 | 109.33 | 1.378 | 0.000 | 0.000 | 0.000 |
| FRONTOFFICEFLR1 | 4.37 | 10.00 | 437.33 | 0.450 | 0.000 | 0.000 | 0.000 |
| FRONTSTAIRSFLR1 | 1.08 | 67.28 | |||||
| REARSTAIRSFLR2 | 1.08 | 55.06 | |||||
| CORRIDORFLR2 | 1.87 | 6.75 | 344.05 | 0.389 | 0.000 | 0.000 | 0.000 |
| GUESTROOM201 | 1.50 | 89.46 | |||||
| GUESTROOM202_205 | 3.82 | 6.00 | 357.84 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM206_208 | 2.87 | 4.50 | 289.02 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM209_212 | 3.82 | 6.00 | 357.84 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM213 | 0.96 | 1.50 | 89.46 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM214 | 0.96 | 1.50 | 89.45 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM215_218 | 6.00 | 357.81 | |||||
| GUESTROOM219 | 0.96 | 1.50 | 89.45 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM220_223 | 3.82 | 6.00 | 357.81 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM224 | 0.96 | 1.50 | 89.45 | 0.000 | 0.000 | 0.000 | 0.000 |
| FRONTSTAIRSFLR2 | 1.08 | 55.05 | |||||
| REARSTAIRSFLR3 | 1.08 | 55.06 | |||||
| CORRIDORFLR3 | 1.87 | 6.75 | 344.05 | 0.389 | 0.000 | 0.000 | 0.000 |
| GUESTROOM301 | 1.50 | 89.46 | |||||
| GUESTROOM302_305 | 6.00 | 357.84 | |||||
| GUESTROOM306_308 | 4.50 | 289.02 | |||||
| GUESTROOM309_312 | 3.82 | 6.00 | 357.84 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM313 | 1.50 | 89.46 | |||||
| GUESTROOM314 | 0.96 | 1.50 | 89.45 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM315_318 | 3.82 | 6.00 | 357.81 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM319 | 1.50 | 89.45 | |||||
| GUESTROOM320_323 | 3.82 | 6.00 | 357.81 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM324 | 1.50 | 89.45 | |||||
| FRONTSTAIRSFLR3 | 1.08 | 55.05 | |||||
| REARSTAIRSFLR4 | 1.08 | 55.06 | |||||
| CORRIDORFLR4 | 1.87 | 6.75 | 344.05 | 0.389 | 0.000 | 0.000 | 0.000 |
| GUESTROOM401 | 0.96 | 1.50 | 89.46 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM402_405 | 6.00 | 357.84 | |||||
| GUESTROOM406_408 | 4.50 | 289.02 | |||||
| GUESTROOM409_412 | 3.82 | 6.00 | 357.84 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM413 | 1.50 | 89.46 | |||||
| GUESTROOM414 | 1.50 | 89.45 | |||||
| GUESTROOM415_418 | 3.82 | 6.00 | 357.81 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM419 | 0.96 | 1.50 | 89.45 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM420_423 | 3.82 | 6.00 | 357.81 | 0.000 | 0.000 | 0.000 | 0.000 |
| GUESTROOM424 | 0.96 | 1.50 | 89.45 | 0.000 | 0.000 | 0.000 | 0.000 |
| FRONTSTAIRSFLR4 | 1.08 | 55.05 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| REARSTAIRSFLR1 | 1.08 | 67.30 | 20.07 | 0.006 | |||
| CORRIDORFLR1 | 2.24 | 8.10 | 504.62 | 150.51 | 0.046 | ||
| FRONTLOUNGEFLR1 | 14.68 | 53.00 | 546.70 | 163.06 | 0.236 | ||
| RESTROOMFLR1 | 0.49 | 1.75 | 109.34 | 32.61 | 0.000 | ||
| MEETINGROOMFLR1 | 15.31 | 43.00 | 269.14 | 80.27 | 0.126 | ||
| MECHANICALROOMFLR1 | 0.53 | 109.34 | 32.61 | 0.000 | |||
| GUESTROOM101 | 1.50 | 109.34 | 32.61 | 0.013 | |||
| GUESTROOM102 | 1.50 | 109.34 | 32.61 | 0.013 | |||
| GUESTROOM103 | 0.96 | 1.50 | 109.34 | 32.61 | 0.013 | ||
| GUESTROOM104 | 0.96 | 1.50 | 109.33 | 32.61 | 0.013 | ||
| GUESTROOM105 | 0.96 | 1.50 | 109.33 | 32.61 | 0.013 | ||
| EMPLOYEELOUNGEFLR1 | 3.53 | 18.00 | 109.33 | 32.61 | 0.051 | ||
| EXERCISECENTERFLR1 | 6.34 | 7.00 | 109.33 | 32.61 | 0.043 | ||
| FRONTOFFICEFLR1 | 4.37 | 10.00 | 437.33 | 130.44 | 0.056 | ||
| FRONTSTAIRSFLR1 | 1.08 | 67.28 | 20.07 | 0.006 | |||
| REARSTAIRSFLR2 | 1.08 | 55.06 | 20.07 | 0.006 | |||
| CORRIDORFLR2 | 1.87 | 6.75 | 344.05 | 125.42 | 0.038 | ||
| GUESTROOM201 | 1.50 | 89.46 | 32.61 | 0.013 | |||
| GUESTROOM202_205 | 3.82 | 6.00 | 357.84 | 130.45 | 0.054 | ||
| GUESTROOM206_208 | 2.87 | 4.50 | 289.02 | 105.36 | 0.043 | ||
| GUESTROOM209_212 | 3.82 | 6.00 | 357.84 | 130.45 | 0.054 | ||
| GUESTROOM213 | 0.96 | 1.50 | 89.46 | 32.61 | 0.013 | ||
| GUESTROOM214 | 0.96 | 1.50 | 89.45 | 32.61 | 0.013 | ||
| GUESTROOM215_218 | 6.00 | 357.81 | 130.44 | 0.054 | |||
| GUESTROOM219 | 0.96 | 1.50 | 89.45 | 32.61 | 0.013 | ||
| GUESTROOM220_223 | 3.82 | 6.00 | 357.81 | 130.44 | 0.054 | ||
| GUESTROOM224 | 0.96 | 1.50 | 89.45 | 32.61 | 0.013 | ||
| FRONTSTAIRSFLR2 | 1.08 | 55.05 | 20.07 | 0.006 | |||
| REARSTAIRSFLR3 | 1.08 | 55.06 | 20.07 | 0.006 | |||
| CORRIDORFLR3 | 1.87 | 6.75 | 344.05 | 125.42 | 0.038 | ||
| GUESTROOM301 | 1.50 | 89.46 | 32.61 | 0.013 | |||
| GUESTROOM302_305 | 6.00 | 357.84 | 130.45 | 0.054 | |||
| GUESTROOM306_308 | 4.50 | 289.02 | 105.36 | 0.043 | |||
| GUESTROOM309_312 | 3.82 | 6.00 | 357.84 | 130.45 | 0.054 | ||
| GUESTROOM313 | 1.50 | 89.46 | 32.61 | 0.013 | |||
| GUESTROOM314 | 0.96 | 1.50 | 89.45 | 32.61 | 0.013 | ||
| GUESTROOM315_318 | 3.82 | 6.00 | 357.81 | 130.44 | 0.054 | ||
| GUESTROOM319 | 1.50 | 89.45 | 32.61 | 0.013 | |||
| GUESTROOM320_323 | 3.82 | 6.00 | 357.81 | 130.44 | 0.054 | ||
| GUESTROOM324 | 1.50 | 89.45 | 32.61 | 0.013 | |||
| FRONTSTAIRSFLR3 | 1.08 | 55.05 | 20.07 | 0.006 | |||
| REARSTAIRSFLR4 | 1.08 | 55.06 | 20.07 | 0.006 | |||
| CORRIDORFLR4 | 1.87 | 6.75 | 344.05 | 125.42 | 0.038 | ||
| GUESTROOM401 | 0.96 | 1.50 | 89.46 | 32.61 | 0.013 | ||
| GUESTROOM402_405 | 6.00 | 357.84 | 130.45 | 0.054 | |||
| GUESTROOM406_408 | 4.50 | 289.02 | 105.36 | 0.043 | |||
| GUESTROOM409_412 | 3.82 | 6.00 | 357.84 | 130.45 | 0.054 | ||
| GUESTROOM413 | 1.50 | 89.46 | 32.61 | 0.013 | |||
| GUESTROOM414 | 1.50 | 89.45 | 32.61 | 0.013 | |||
| GUESTROOM415_418 | 3.82 | 6.00 | 357.81 | 130.44 | 0.054 | ||
| GUESTROOM419 | 0.96 | 1.50 | 89.45 | 32.61 | 0.013 | ||
| GUESTROOM420_423 | 3.82 | 6.00 | 357.81 | 130.44 | 0.054 | ||
| GUESTROOM424 | 0.96 | 1.50 | 89.45 | 32.61 | 0.013 | ||
| FRONTSTAIRSFLR4 | 1.08 | 55.05 | 20.07 | 0.006 | |||
| Total Facility | 100.34 | 285.77 | 10741.65 | 3725.09 | 0.0000 | 1.768 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 377586.10 | 377586.10 | 192934.21 | 8760.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR1 | 1446687.50 | 0.00 | 1446687.50 | 3421669.93 | 4868357.43 | 1446687.50 | 0.00 | 8760.00 | 0.00 | 0.00 |
| FRONTLOUNGEFLR1 | 7444795.00 | 0.00 | 7444795.00 | 248119.59 | 7692914.59 | 7444795.00 | 0.00 | 8760.00 | 0.00 | 0.00 |
| RESTROOMFLR1 | 0.00 | 0.00 | 0.00 | 35059.65 | 35059.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MEETINGROOMFLR1 | 1875158.49 | 0.00 | 1875158.49 | 86300.67 | 1961459.16 | 3986630.15 | 5109.97 | 3650.03 | 0.00 | 4991.42 |
| MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 35059.65 | 35059.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM101 | 17712.42 | 0.00 | 17712.42 | 35059.65 | 52772.07 | 425098.19 | 8395.00 | 365.00 | 0.00 | 365.00 |
| GUESTROOM102 | 17712.42 | 0.00 | 17712.42 | 35059.65 | 52772.07 | 425098.19 | 8395.00 | 365.00 | 0.00 | 365.00 |
| GUESTROOM103 | 313737.81 | 6920.71 | 320658.53 | 35059.65 | 355718.17 | 425098.19 | 2426.06 | 5783.50 | 550.44 | 0.00 |
| GUESTROOM104 | 314326.52 | 6667.00 | 320993.52 | 35059.65 | 356053.17 | 425068.03 | 2424.71 | 5820.76 | 514.52 | 0.00 |
| GUESTROOM105 | 322390.69 | 4024.08 | 326414.77 | 35059.65 | 361474.42 | 425068.03 | 2424.29 | 6014.03 | 321.68 | 0.00 |
| EMPLOYEELOUNGEFLR1 | 1619453.58 | 0.00 | 1619453.58 | 35059.65 | 1654513.22 | 1619453.58 | 0.00 | 8760.00 | 0.00 | 3285.00 |
| EXERCISECENTERFLR1 | 1358252.08 | 0.00 | 1358252.08 | 35059.65 | 1393311.73 | 1358252.08 | 0.00 | 8760.00 | 0.00 | 2920.00 |
| FRONTOFFICEFLR1 | 1776177.15 | 0.00 | 1776177.15 | 140238.59 | 1916415.74 | 1776177.15 | 0.00 | 8760.00 | 0.00 | 730.00 |
| FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 377565.43 | 377565.43 | 192888.02 | 8760.00 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 388051.76 | 388051.76 | 192934.21 | 8760.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR2 | 1205560.37 | 0.00 | 1205560.37 | 243904.89 | 1449465.26 | 1205560.37 | 0.00 | 8760.00 | 0.00 | 0.00 |
| GUESTROOM201 | 20063.88 | 0.00 | 20063.88 | 110871.17 | 130935.05 | 425098.19 | 8395.00 | 365.00 | 0.00 | 687.60 |
| GUESTROOM202_205 | 1265385.07 | 5286.18 | 1270671.25 | 144125.62 | 1414796.87 | 1700392.76 | 2422.33 | 5973.86 | 363.81 | 0.00 |
| GUESTROOM206_208 | 1002383.18 | 5285.76 | 1007668.94 | 116409.15 | 1124078.10 | 1347630.58 | 2422.51 | 5973.71 | 363.78 | 0.00 |
| GUESTROOM209_212 | 1262903.66 | 5392.08 | 1268295.74 | 144125.62 | 1412421.36 | 1700392.76 | 2422.79 | 5965.96 | 371.25 | 0.00 |
| GUESTROOM213 | 316346.75 | 7058.68 | 323405.42 | 36031.40 | 359436.83 | 425098.19 | 2424.98 | 5870.06 | 464.96 | 0.00 |
| GUESTROOM214 | 318805.71 | 5594.81 | 324400.51 | 36031.40 | 360431.92 | 425068.03 | 2424.26 | 5972.85 | 362.88 | 0.00 |
| GUESTROOM215_218 | 219304.49 | 0.00 | 219304.49 | 144125.62 | 363430.11 | 1700272.11 | 8395.00 | 365.00 | 0.00 | 8095.12 |
| GUESTROOM219 | 334276.95 | 1884.66 | 336161.61 | 36031.40 | 372193.01 | 425068.03 | 2430.00 | 6211.30 | 118.70 | 0.00 |
| GUESTROOM220_223 | 1274881.49 | 5815.14 | 1280696.63 | 144125.62 | 1424822.25 | 1700272.11 | 2423.31 | 5946.34 | 390.35 | 0.00 |
| GUESTROOM224 | 317768.94 | 6136.36 | 323905.30 | 36031.40 | 359936.70 | 425068.03 | 2424.37 | 5938.33 | 397.30 | 0.00 |
| FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 388030.51 | 388030.51 | 192888.02 | 8760.00 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 429201.08 | 429201.08 | 192934.21 | 8760.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR3 | 1205560.37 | 0.00 | 1205560.37 | 269768.77 | 1475329.13 | 1205560.37 | 0.00 | 8760.00 | 0.00 | 0.00 |
| GUESTROOM301 | 36182.30 | 0.00 | 36182.30 | 122628.04 | 158810.34 | 425098.19 | 8395.00 | 365.00 | 0.00 | 1836.57 |
| GUESTROOM302_305 | 94078.76 | 0.00 | 94078.76 | 159408.82 | 253487.58 | 1700392.76 | 8395.00 | 365.00 | 0.00 | 931.32 |
| GUESTROOM306_308 | 58793.01 | 0.00 | 58793.01 | 128753.27 | 187546.29 | 1347630.58 | 8395.00 | 365.00 | 0.00 | 448.16 |
| GUESTROOM309_312 | 1259811.58 | 6302.26 | 1266113.84 | 159408.82 | 1425522.66 | 1700392.76 | 2422.95 | 5939.36 | 397.68 | 0.00 |
| GUESTROOM313 | 26556.26 | 0.00 | 26556.26 | 39852.20 | 66408.46 | 425098.19 | 8395.00 | 365.00 | 0.00 | 1237.35 |
| GUESTROOM314 | 317143.25 | 6885.72 | 324028.98 | 39852.20 | 363881.18 | 425068.03 | 2424.05 | 5931.03 | 404.92 | 0.00 |
| GUESTROOM315_318 | 1290517.91 | 4500.57 | 1295018.48 | 159408.82 | 1454427.30 | 1700272.11 | 2421.89 | 6059.73 | 278.38 | 0.00 |
| GUESTROOM319 | 20338.50 | 0.00 | 20338.50 | 39852.20 | 60190.71 | 425068.03 | 8395.00 | 365.00 | 0.00 | 1688.69 |
| GUESTROOM320_323 | 1268540.90 | 6971.96 | 1275512.86 | 159408.82 | 1434921.67 | 1700272.11 | 2423.69 | 5916.81 | 419.49 | 0.00 |
| GUESTROOM324 | 17825.62 | 0.00 | 17825.62 | 39852.20 | 57677.83 | 425068.03 | 8395.00 | 365.00 | 0.00 | 432.83 |
| FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 429177.58 | 429177.58 | 192888.02 | 8760.00 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 459813.49 | 459813.49 | 192934.21 | 8760.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR4 | 1205560.37 | 0.00 | 1205560.37 | 289009.80 | 1494570.17 | 1205560.37 | 0.00 | 8760.00 | 0.00 | 0.00 |
| GUESTROOM401 | 327309.07 | 6160.50 | 333469.57 | 131374.38 | 464843.95 | 425098.19 | 2425.22 | 5965.55 | 369.23 | 0.00 |
| GUESTROOM402_405 | 207674.68 | 0.00 | 207674.68 | 170778.52 | 378453.19 | 1700392.76 | 8395.00 | 365.00 | 0.00 | 3186.75 |
| GUESTROOM406_408 | 147252.49 | 0.00 | 147252.49 | 137936.50 | 285188.98 | 1347630.58 | 8395.00 | 365.00 | 0.00 | 2845.32 |
| GUESTROOM409_412 | 1275389.69 | 5111.48 | 1280501.17 | 170778.52 | 1451279.69 | 1700392.76 | 2423.44 | 6016.92 | 319.64 | 0.00 |
| GUESTROOM413 | 47609.89 | 0.00 | 47609.89 | 42694.63 | 90304.52 | 425098.19 | 8395.00 | 365.00 | 0.00 | 3014.47 |
| GUESTROOM414 | 31217.08 | 0.00 | 31217.08 | 42694.63 | 73911.71 | 425068.03 | 8395.00 | 365.00 | 0.00 | 2015.16 |
| GUESTROOM415_418 | 1282640.15 | 5516.63 | 1288156.78 | 170778.52 | 1458935.30 | 1700272.11 | 2423.79 | 6009.09 | 327.12 | 0.00 |
| GUESTROOM419 | 320357.40 | 5721.01 | 326078.41 | 42694.63 | 368773.04 | 425068.03 | 2424.23 | 6005.78 | 329.99 | 0.00 |
| GUESTROOM420_423 | 1278065.18 | 6045.56 | 1284110.73 | 170778.52 | 1454889.25 | 1700272.11 | 2424.39 | 5980.09 | 355.52 | 0.00 |
| GUESTROOM424 | 320096.09 | 6313.08 | 326409.17 | 42694.63 | 369103.80 | 425068.03 | 2425.11 | 5976.53 | 358.36 | 0.00 |
| FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 459788.32 | 459788.32 | 192888.02 | 8760.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 36082604.71 | 119594.21 | 36202198.92 | 11443300.63 | 47645499.54 | 55740478.42 | 8760.00 | 8760.00 | 599.61 | 8756.97 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| CORRIDORFLR1 | 0.0459 | 0.0000 | 0.0459 | 0.1085 | 0.1544 | 0.0459 | 0.00 | 8760.00 | 0.00 |
| FRONTLOUNGEFLR1 | 0.2361 | 0.0000 | 0.2361 | 0.0079 | 0.2439 | 0.2361 | 0.00 | 8760.00 | 0.00 |
| RESTROOMFLR1 | 0.0000 | 0.0000 | 0.0000 | 0.0011 | 0.0011 | 0.0000 | 0.00 | 0.00 | 0.00 |
| MEETINGROOMFLR1 | 0.1059 | 0.0000 | 0.1059 | 0.0029 | 0.1088 | 0.1264 | 365.00 | 1710.00 | 0.00 |
| GUESTROOM103 | 0.0099 | 0.0002 | 0.0102 | 0.0011 | 0.0113 | 0.0135 | 2426.06 | 5783.50 | 550.44 |
| GUESTROOM104 | 0.0100 | 0.0002 | 0.0102 | 0.0011 | 0.0113 | 0.0135 | 2424.71 | 5820.76 | 514.52 |
| GUESTROOM105 | 0.0102 | 0.0001 | 0.0104 | 0.0011 | 0.0115 | 0.0135 | 2424.29 | 6014.03 | 321.68 |
| EMPLOYEELOUNGEFLR1 | 0.0514 | 0.0000 | 0.0514 | 0.0012 | 0.0525 | 0.0514 | 0.00 | 5475.00 | 0.00 |
| EXERCISECENTERFLR1 | 0.0431 | 0.0000 | 0.0431 | 0.0012 | 0.0442 | 0.0431 | 0.00 | 5840.00 | 0.00 |
| FRONTOFFICEFLR1 | 0.0563 | 0.0000 | 0.0563 | 0.0044 | 0.0607 | 0.0563 | 0.00 | 8030.00 | 0.00 |
| CORRIDORFLR2 | 0.0382 | 0.0000 | 0.0382 | 0.0077 | 0.0460 | 0.0382 | 0.00 | 8760.00 | 0.00 |
| GUESTROOM202_205 | 0.0401 | 0.0002 | 0.0403 | 0.0046 | 0.0449 | 0.0539 | 2422.33 | 5973.86 | 363.81 |
| GUESTROOM206_208 | 0.0318 | 0.0002 | 0.0320 | 0.0037 | 0.0356 | 0.0427 | 2422.51 | 5973.71 | 363.78 |
| GUESTROOM209_212 | 0.0400 | 0.0002 | 0.0402 | 0.0046 | 0.0448 | 0.0539 | 2422.79 | 5965.96 | 371.25 |
| GUESTROOM213 | 0.0100 | 0.0002 | 0.0103 | 0.0011 | 0.0114 | 0.0135 | 2424.98 | 5870.06 | 464.96 |
| GUESTROOM214 | 0.0101 | 0.0002 | 0.0103 | 0.0011 | 0.0114 | 0.0135 | 2424.26 | 5972.85 | 362.88 |
| GUESTROOM219 | 0.0106 | 0.0001 | 0.0107 | 0.0011 | 0.0118 | 0.0135 | 2430.00 | 6211.30 | 118.70 |
| GUESTROOM220_223 | 0.0404 | 0.0002 | 0.0406 | 0.0046 | 0.0452 | 0.0539 | 2423.31 | 5946.34 | 390.35 |
| GUESTROOM224 | 0.0101 | 0.0002 | 0.0103 | 0.0011 | 0.0114 | 0.0135 | 2424.37 | 5938.33 | 397.30 |
| CORRIDORFLR3 | 0.0382 | 0.0000 | 0.0382 | 0.0086 | 0.0468 | 0.0382 | 0.00 | 8760.00 | 0.00 |
| GUESTROOM309_312 | 0.0399 | 0.0002 | 0.0401 | 0.0051 | 0.0452 | 0.0539 | 2422.95 | 5939.36 | 397.68 |
| GUESTROOM314 | 0.0101 | 0.0002 | 0.0103 | 0.0013 | 0.0115 | 0.0135 | 2424.05 | 5931.03 | 404.92 |
| GUESTROOM315_318 | 0.0409 | 0.0001 | 0.0411 | 0.0051 | 0.0461 | 0.0539 | 2421.89 | 6059.73 | 278.38 |
| GUESTROOM320_323 | 0.0402 | 0.0002 | 0.0404 | 0.0051 | 0.0455 | 0.0539 | 2423.69 | 5916.81 | 419.49 |
| CORRIDORFLR4 | 0.0382 | 0.0000 | 0.0382 | 0.0092 | 0.0474 | 0.0382 | 0.00 | 8760.00 | 0.00 |
| GUESTROOM401 | 0.0104 | 0.0002 | 0.0106 | 0.0042 | 0.0147 | 0.0135 | 2425.22 | 5965.55 | 369.23 |
| GUESTROOM409_412 | 0.0404 | 0.0002 | 0.0406 | 0.0054 | 0.0460 | 0.0539 | 2423.44 | 6016.92 | 319.64 |
| GUESTROOM415_418 | 0.0407 | 0.0002 | 0.0408 | 0.0054 | 0.0463 | 0.0539 | 2423.79 | 6009.09 | 327.12 |
| GUESTROOM419 | 0.0102 | 0.0002 | 0.0103 | 0.0014 | 0.0117 | 0.0135 | 2424.23 | 6005.78 | 329.99 |
| GUESTROOM420_423 | 0.0405 | 0.0002 | 0.0407 | 0.0054 | 0.0461 | 0.0539 | 2424.39 | 5980.09 | 355.52 |
| GUESTROOM424 | 0.0102 | 0.0002 | 0.0104 | 0.0014 | 0.0117 | 0.0135 | 2425.11 | 5976.53 | 358.36 |
| Total Facility | 1.1601 | 0.0038 | 1.1639 | 0.2174 | 1.3813 | 1.3500 | 8760.00 | 8760.00 | 599.61 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| None |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| None |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| None |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| None |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Surfaces by Class| Total | Outdoors | |
| Wall | 338 | 92 |
| Floor | 75 | 19 |
| Roof | 72 | 16 |
| Internal Mass | 0 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 103 | 103 |
| Door | 3 | 3 |
| Glass Door | 0 | 0 |
| Shading | 2 | 2 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 0 |
| Conditioned Zones | 54 |
| Unconditioned Zones | 13 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 2268 |
| Defaulted Fields | 2598 |
| Fields with Defaults | 8404 |
| Autosized Fields | 834 |
| Autosizable Fields | 929 |
| Autocalculated Fields | 904 |
| Autocalculatable Fields | 1496 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 1558.78 | 28784.38 | 13-MAY-05:00 | 96735.42 | 30-JUL-19:40 |
| Electricity:Building | 965.79 | 14110.64 | 01-JAN-02:10 | 56957.45 | 01-JAN-08:10 |
| Electricity:Zone:CORRIDORFLR1 | 25.54 | 810.01 | 01-JAN-00:10 | 810.01 | 01-JAN-00:10 |
| Electricity:SpaceType:GENERAL | 965.79 | 14110.64 | 01-JAN-02:10 | 56957.45 | 01-JAN-08:10 |
| InteriorLights:Electricity | 512.99 | 7336.06 | 01-JAN-02:10 | 26853.76 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:CORRIDORFLR1 | 25.54 | 810.01 | 01-JAN-00:10 | 810.01 | 01-JAN-00:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 512.99 | 7336.06 | 01-JAN-02:10 | 26853.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity | 512.99 | 7336.06 | 01-JAN-02:10 | 26853.76 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDORFLR1 | 25.54 | 810.01 | 01-JAN-00:10 | 810.01 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 512.99 | 7336.06 | 01-JAN-02:10 | 26853.76 | 01-JAN-19:10 |
| Electricity:Zone:CORRIDORFLR2 | 21.29 | 675.01 | 01-JAN-00:10 | 675.01 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:CORRIDORFLR2 | 21.29 | 675.01 | 01-JAN-00:10 | 675.01 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDORFLR2 | 21.29 | 675.01 | 01-JAN-00:10 | 675.01 | 01-JAN-00:10 |
| Electricity:Zone:CORRIDORFLR3 | 21.29 | 675.01 | 01-JAN-00:10 | 675.01 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:CORRIDORFLR3 | 21.29 | 675.01 | 01-JAN-00:10 | 675.01 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDORFLR3 | 21.29 | 675.01 | 01-JAN-00:10 | 675.01 | 01-JAN-00:10 |
| Electricity:Zone:CORRIDORFLR4 | 21.29 | 675.01 | 01-JAN-00:10 | 675.01 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:CORRIDORFLR4 | 21.29 | 675.01 | 01-JAN-00:10 | 675.01 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:CORRIDORFLR4 | 21.29 | 675.01 | 01-JAN-00:10 | 675.01 | 01-JAN-00:10 |
| Electricity:Zone:ELEVATORCOREFLR1 | 145.03 | 3524.00 | 01-JAN-00:10 | 7633.46 | 01-JAN-07:10 |
| InteriorLights:Electricity:Zone:ELEVATORCOREFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:ELEVATORCOREFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:ELEVATORCOREFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:ELEVATORCOREFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:ELEVATORCOREFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:ELEVATORCOREFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:ELEVATORCOREFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:ELEVATORCOREFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:ELEVATORCOREFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:ELEVATORCOREFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:ELEVATORCOREFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:EMPLOYEELOUNGEFLR1 | 16.24 | 55.76 | 01-JAN-00:10 | 1093.45 | 01-JAN-08:10 |
| InteriorLights:Electricity:Zone:EMPLOYEELOUNGEFLR1 | 6.67 | 0.00 | 01-JAN-00:10 | 421.20 | 01-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:EMPLOYEELOUNGEFLR1 | 6.67 | 0.00 | 01-JAN-00:10 | 421.20 | 01-JAN-08:10 |
| Electricity:Zone:EXERCISECENTERFLR1 | 15.01 | 0.00 | 01-JAN-00:10 | 922.10 | 01-JAN-07:10 |
| InteriorLights:Electricity:Zone:EXERCISECENTERFLR1 | 6.64 | 0.00 | 01-JAN-00:10 | 315.90 | 01-JAN-07:10 |
| LightsWired:InteriorLights:Electricity:Zone:EXERCISECENTERFLR1 | 6.64 | 0.00 | 01-JAN-00:10 | 315.90 | 01-JAN-07:10 |
| Electricity:Zone:FRONTLOUNGEFLR1 | 86.49 | 892.34 | 01-JAN-00:10 | 6530.91 | 01-JAN-08:10 |
| InteriorLights:Electricity:Zone:FRONTLOUNGEFLR1 | 36.13 | 0.00 | 01-JAN-00:10 | 2281.66 | 01-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:FRONTLOUNGEFLR1 | 36.13 | 0.00 | 01-JAN-00:10 | 2281.66 | 01-JAN-08:10 |
| Electricity:Zone:FRONTOFFICEFLR1 | 61.34 | 1321.30 | 01-JAN-00:10 | 3053.91 | 03-JAN-10:10 |
| InteriorLights:Electricity:Zone:FRONTOFFICEFLR1 | 31.90 | 772.20 | 01-JAN-00:10 | 1389.96 | 01-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:FRONTOFFICEFLR1 | 31.90 | 772.20 | 01-JAN-00:10 | 1389.96 | 01-JAN-08:10 |
| Electricity:Zone:FRONTSTAIRSFLR1 | 4.09 | 129.60 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:FRONTSTAIRSFLR1 | 4.09 | 129.60 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:FRONTSTAIRSFLR1 | 4.09 | 129.60 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 |
| Electricity:Zone:FRONTSTAIRSFLR2 | 4.09 | 129.60 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:FRONTSTAIRSFLR2 | 4.09 | 129.60 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:FRONTSTAIRSFLR2 | 4.09 | 129.60 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 |
| Electricity:Zone:FRONTSTAIRSFLR3 | 4.09 | 129.60 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:FRONTSTAIRSFLR3 | 4.09 | 129.60 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:FRONTSTAIRSFLR3 | 4.09 | 129.60 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 |
| Electricity:Zone:FRONTSTAIRSFLR4 | 4.09 | 129.60 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:FRONTSTAIRSFLR4 | 4.09 | 129.60 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:FRONTSTAIRSFLR4 | 4.09 | 129.60 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 |
| Electricity:Zone:FRONTSTORAGEFLR1 | 0.85 | 10.80 | 01-JAN-00:10 | 43.20 | 01-JAN-08:10 |
| InteriorLights:Electricity:Zone:FRONTSTORAGEFLR1 | 0.85 | 10.80 | 01-JAN-00:10 | 43.20 | 01-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:FRONTSTORAGEFLR1 | 0.85 | 10.80 | 01-JAN-00:10 | 43.20 | 01-JAN-08:10 |
| Electricity:Zone:FRONTSTORAGEFLR2 | 0.85 | 10.80 | 01-JAN-00:10 | 43.20 | 01-JAN-08:10 |
| InteriorLights:Electricity:Zone:FRONTSTORAGEFLR2 | 0.85 | 10.80 | 01-JAN-00:10 | 43.20 | 01-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:FRONTSTORAGEFLR2 | 0.85 | 10.80 | 01-JAN-00:10 | 43.20 | 01-JAN-08:10 |
| Electricity:Zone:FRONTSTORAGEFLR3 | 0.85 | 10.80 | 01-JAN-00:10 | 43.20 | 01-JAN-08:10 |
| InteriorLights:Electricity:Zone:FRONTSTORAGEFLR3 | 0.85 | 10.80 | 01-JAN-00:10 | 43.20 | 01-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:FRONTSTORAGEFLR3 | 0.85 | 10.80 | 01-JAN-00:10 | 43.20 | 01-JAN-08:10 |
| Electricity:Zone:FRONTSTORAGEFLR4 | 0.85 | 10.80 | 01-JAN-00:10 | 43.20 | 01-JAN-08:10 |
| InteriorLights:Electricity:Zone:FRONTSTORAGEFLR4 | 0.85 | 10.80 | 01-JAN-00:10 | 43.20 | 01-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:FRONTSTORAGEFLR4 | 0.85 | 10.80 | 01-JAN-00:10 | 43.20 | 01-JAN-08:10 |
| Electricity:Zone:GUESTROOM101 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:GUESTROOM101 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM101 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:GUESTROOM102 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:GUESTROOM102 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM102 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:GUESTROOM103 | 8.77 | 78.93 | 01-JAN-02:10 | 667.79 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM103 | 5.20 | 44.02 | 01-JAN-02:10 | 400.17 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM103 | 5.20 | 44.02 | 01-JAN-02:10 | 400.17 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM104 | 8.77 | 78.92 | 01-JAN-02:10 | 667.74 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM104 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM104 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM105 | 8.77 | 78.92 | 01-JAN-02:10 | 667.74 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM105 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM105 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM201 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:GUESTROOM201 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM201 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:GUESTROOM202_205 | 35.10 | 315.70 | 01-JAN-02:10 | 2671.17 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM202_205 | 20.81 | 176.07 | 01-JAN-02:10 | 1600.67 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM202_205 | 20.81 | 176.07 | 01-JAN-02:10 | 1600.67 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM206_208 | 28.35 | 254.99 | 01-JAN-02:10 | 2157.48 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM206_208 | 16.81 | 142.21 | 01-JAN-02:10 | 1292.85 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM206_208 | 16.81 | 142.21 | 01-JAN-02:10 | 1292.85 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM209_212 | 35.10 | 315.70 | 01-JAN-02:10 | 2671.17 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM209_212 | 20.81 | 176.07 | 01-JAN-02:10 | 1600.67 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM209_212 | 20.81 | 176.07 | 01-JAN-02:10 | 1600.67 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM213 | 8.77 | 78.93 | 01-JAN-02:10 | 667.79 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM213 | 5.20 | 44.02 | 01-JAN-02:10 | 400.17 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM213 | 5.20 | 44.02 | 01-JAN-02:10 | 400.17 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM214 | 8.77 | 78.92 | 01-JAN-02:10 | 667.74 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM214 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM214 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM215_218 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:GUESTROOM215_218 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM215_218 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:GUESTROOM219 | 8.77 | 78.92 | 01-JAN-02:10 | 667.74 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM219 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM219 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM220_223 | 35.10 | 315.68 | 01-JAN-02:10 | 2670.98 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM220_223 | 20.81 | 176.06 | 01-JAN-02:10 | 1600.56 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM220_223 | 20.81 | 176.06 | 01-JAN-02:10 | 1600.56 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM224 | 8.77 | 78.92 | 01-JAN-02:10 | 667.74 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM224 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM224 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM301 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:GUESTROOM301 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM301 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:GUESTROOM302_305 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:GUESTROOM302_305 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM302_305 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:GUESTROOM306_308 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:GUESTROOM306_308 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM306_308 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:GUESTROOM309_312 | 35.10 | 315.70 | 01-JAN-02:10 | 2671.17 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM309_312 | 20.81 | 176.07 | 01-JAN-02:10 | 1600.67 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM309_312 | 20.81 | 176.07 | 01-JAN-02:10 | 1600.67 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM313 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:GUESTROOM313 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM313 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:GUESTROOM314 | 8.77 | 78.92 | 01-JAN-02:10 | 667.74 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM314 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM314 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM315_318 | 35.10 | 315.68 | 01-JAN-02:10 | 2670.98 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM315_318 | 20.81 | 176.06 | 01-JAN-02:10 | 1600.56 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM315_318 | 20.81 | 176.06 | 01-JAN-02:10 | 1600.56 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM319 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:GUESTROOM319 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM319 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:GUESTROOM320_323 | 35.10 | 315.68 | 01-JAN-02:10 | 2670.98 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM320_323 | 20.81 | 176.06 | 01-JAN-02:10 | 1600.56 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM320_323 | 20.81 | 176.06 | 01-JAN-02:10 | 1600.56 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM324 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:GUESTROOM324 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM324 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:GUESTROOM401 | 8.77 | 78.93 | 01-JAN-02:10 | 667.79 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM401 | 5.20 | 44.02 | 01-JAN-02:10 | 400.17 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM401 | 5.20 | 44.02 | 01-JAN-02:10 | 400.17 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM402_405 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:GUESTROOM402_405 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM402_405 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:GUESTROOM406_408 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:GUESTROOM406_408 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM406_408 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:GUESTROOM409_412 | 35.10 | 315.70 | 01-JAN-02:10 | 2671.17 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM409_412 | 20.81 | 176.07 | 01-JAN-02:10 | 1600.67 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM409_412 | 20.81 | 176.07 | 01-JAN-02:10 | 1600.67 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM413 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:GUESTROOM413 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM413 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:GUESTROOM414 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:GUESTROOM414 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM414 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Electricity:Zone:GUESTROOM415_418 | 35.10 | 315.68 | 01-JAN-02:10 | 2670.98 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM415_418 | 20.81 | 176.06 | 01-JAN-02:10 | 1600.56 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM415_418 | 20.81 | 176.06 | 01-JAN-02:10 | 1600.56 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM419 | 8.77 | 78.92 | 01-JAN-02:10 | 667.74 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM419 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM419 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM420_423 | 35.10 | 315.68 | 01-JAN-02:10 | 2670.98 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM420_423 | 20.81 | 176.06 | 01-JAN-02:10 | 1600.56 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM420_423 | 20.81 | 176.06 | 01-JAN-02:10 | 1600.56 | 01-JAN-19:10 |
| Electricity:Zone:GUESTROOM424 | 8.77 | 78.92 | 01-JAN-02:10 | 667.74 | 01-JAN-21:10 |
| InteriorLights:Electricity:Zone:GUESTROOM424 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| LightsWired:InteriorLights:Electricity:Zone:GUESTROOM424 | 5.20 | 44.02 | 01-JAN-02:10 | 400.14 | 01-JAN-19:10 |
| Electricity:Zone:LAUNDRYROOMFLR1 | 35.95 | 0.00 | 01-JAN-00:10 | 3340.87 | 01-JAN-08:10 |
| InteriorLights:Electricity:Zone:LAUNDRYROOMFLR1 | 7.47 | 0.00 | 01-JAN-00:10 | 631.80 | 01-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:LAUNDRYROOMFLR1 | 7.47 | 0.00 | 01-JAN-00:10 | 631.80 | 01-JAN-08:10 |
| Electricity:Zone:MECHANICALROOMFLR1 | 4.15 | 52.65 | 01-JAN-00:10 | 210.61 | 01-JAN-08:10 |
| InteriorLights:Electricity:Zone:MECHANICALROOMFLR1 | 4.15 | 52.65 | 01-JAN-00:10 | 210.61 | 01-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:MECHANICALROOMFLR1 | 4.15 | 52.65 | 01-JAN-00:10 | 210.61 | 01-JAN-08:10 |
| Electricity:Zone:MEETINGROOMFLR1 | 19.90 | 0.00 | 01-JAN-00:10 | 1360.97 | 01-JAN-08:10 |
| InteriorLights:Electricity:Zone:MEETINGROOMFLR1 | 17.79 | 0.00 | 01-JAN-00:10 | 1123.28 | 01-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:MEETINGROOMFLR1 | 17.79 | 0.00 | 01-JAN-00:10 | 1123.28 | 01-JAN-08:10 |
| Electricity:Zone:REARSTAIRSFLR1 | 4.09 | 129.63 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:REARSTAIRSFLR1 | 4.09 | 129.63 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:REARSTAIRSFLR1 | 4.09 | 129.63 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 |
| Electricity:Zone:REARSTAIRSFLR2 | 4.09 | 129.63 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:REARSTAIRSFLR2 | 4.09 | 129.63 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:REARSTAIRSFLR2 | 4.09 | 129.63 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 |
| Electricity:Zone:REARSTAIRSFLR3 | 4.09 | 129.63 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:REARSTAIRSFLR3 | 4.09 | 129.63 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:REARSTAIRSFLR3 | 4.09 | 129.63 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 |
| Electricity:Zone:REARSTAIRSFLR4 | 4.09 | 129.63 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:REARSTAIRSFLR4 | 4.09 | 129.63 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:REARSTAIRSFLR4 | 4.09 | 129.63 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 |
| Electricity:Zone:REARSTORAGEFLR1 | 1.36 | 17.29 | 01-JAN-00:10 | 69.14 | 01-JAN-08:10 |
| InteriorLights:Electricity:Zone:REARSTORAGEFLR1 | 1.36 | 17.29 | 01-JAN-00:10 | 69.14 | 01-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:REARSTORAGEFLR1 | 1.36 | 17.29 | 01-JAN-00:10 | 69.14 | 01-JAN-08:10 |
| Electricity:Zone:REARSTORAGEFLR2 | 1.36 | 17.29 | 01-JAN-00:10 | 69.14 | 01-JAN-08:10 |
| InteriorLights:Electricity:Zone:REARSTORAGEFLR2 | 1.36 | 17.29 | 01-JAN-00:10 | 69.14 | 01-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:REARSTORAGEFLR2 | 1.36 | 17.29 | 01-JAN-00:10 | 69.14 | 01-JAN-08:10 |
| Electricity:Zone:REARSTORAGEFLR3 | 1.36 | 17.29 | 01-JAN-00:10 | 69.14 | 01-JAN-08:10 |
| InteriorLights:Electricity:Zone:REARSTORAGEFLR3 | 1.36 | 17.29 | 01-JAN-00:10 | 69.14 | 01-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:REARSTORAGEFLR3 | 1.36 | 17.29 | 01-JAN-00:10 | 69.14 | 01-JAN-08:10 |
| Electricity:Zone:REARSTORAGEFLR4 | 1.36 | 17.29 | 01-JAN-00:10 | 69.14 | 01-JAN-08:10 |
| InteriorLights:Electricity:Zone:REARSTORAGEFLR4 | 1.36 | 17.29 | 01-JAN-00:10 | 69.14 | 01-JAN-08:10 |
| LightsWired:InteriorLights:Electricity:Zone:REARSTORAGEFLR4 | 1.36 | 17.29 | 01-JAN-00:10 | 69.14 | 01-JAN-08:10 |
| Electricity:Zone:RESTROOMFLR1 | 9.96 | 315.92 | 01-JAN-00:10 | 315.92 | 01-JAN-00:10 |
| InteriorLights:Electricity:Zone:RESTROOMFLR1 | 9.96 | 315.92 | 01-JAN-00:10 | 315.92 | 01-JAN-00:10 |
| LightsWired:InteriorLights:Electricity:Zone:RESTROOMFLR1 | 9.96 | 315.92 | 01-JAN-00:10 | 315.92 | 01-JAN-00:10 |
| InteriorEquipment:Electricity | 452.79 | 6774.57 | 01-JAN-00:10 | 34689.82 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR1 | 145.03 | 3524.00 | 01-JAN-00:10 | 7633.46 | 01-JAN-07:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 452.79 | 6774.57 | 01-JAN-00:10 | 34689.82 | 01-JAN-08:10 |
| ElevatorLift:InteriorEquipment:Electricity | 134.82 | 3200.00 | 01-JAN-00:10 | 7309.46 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR1 | 134.82 | 3200.00 | 01-JAN-00:10 | 7309.46 | 01-JAN-07:10 |
| ElevatorLift:InteriorEquipment:Electricity:SpaceType:GENERAL | 134.82 | 3200.00 | 01-JAN-00:10 | 7309.46 | 01-JAN-07:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR1 | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
| ElevatorLightsFan:InteriorEquipment:Electricity:SpaceType:GENERAL | 10.22 | 324.00 | 01-JAN-00:10 | 324.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:CORRIDORFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity | 279.28 | 3250.57 | 01-JAN-00:10 | 24347.29 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDORFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 279.28 | 3250.57 | 01-JAN-00:10 | 24347.29 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:CORRIDORFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDORFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:CORRIDORFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDORFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:CORRIDORFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:CORRIDORFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:ELEVATORCOREFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:EMPLOYEELOUNGEFLR1 | 9.57 | 55.76 | 01-JAN-00:10 | 672.25 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:EMPLOYEELOUNGEFLR1 | 9.57 | 55.76 | 01-JAN-00:10 | 672.25 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:EXERCISECENTERFLR1 | 8.36 | 0.00 | 01-JAN-00:10 | 606.20 | 01-JAN-07:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:EXERCISECENTERFLR1 | 8.36 | 0.00 | 01-JAN-00:10 | 606.20 | 01-JAN-07:10 |
| InteriorEquipment:Electricity:Zone:FRONTLOUNGEFLR1 | 50.36 | 892.34 | 01-JAN-00:10 | 4249.25 | 01-JAN-06:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:FRONTLOUNGEFLR1 | 50.36 | 892.34 | 01-JAN-00:10 | 4249.25 | 01-JAN-06:10 |
| InteriorEquipment:Electricity:Zone:FRONTOFFICEFLR1 | 29.44 | 549.10 | 01-JAN-00:10 | 1663.95 | 03-JAN-10:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:FRONTOFFICEFLR1 | 29.44 | 549.10 | 01-JAN-00:10 | 1663.95 | 03-JAN-10:10 |
| InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTAIRSFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:FRONTSTORAGEFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM101 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM101 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM102 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM102 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM103 | 3.57 | 34.91 | 01-JAN-00:10 | 349.07 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM103 | 3.57 | 34.91 | 01-JAN-00:10 | 349.07 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM104 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM104 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM105 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM105 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM201 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM201 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM202_205 | 14.29 | 139.63 | 01-JAN-00:10 | 1396.30 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM202_205 | 14.29 | 139.63 | 01-JAN-00:10 | 1396.30 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM206_208 | 11.54 | 112.78 | 01-JAN-00:10 | 1127.78 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM206_208 | 11.54 | 112.78 | 01-JAN-00:10 | 1127.78 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM209_212 | 14.29 | 139.63 | 01-JAN-00:10 | 1396.30 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM209_212 | 14.29 | 139.63 | 01-JAN-00:10 | 1396.30 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM213 | 3.57 | 34.91 | 01-JAN-00:10 | 349.07 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM213 | 3.57 | 34.91 | 01-JAN-00:10 | 349.07 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM214 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM214 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM215_218 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM215_218 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM219 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM219 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM220_223 | 14.29 | 139.62 | 01-JAN-00:10 | 1396.20 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM220_223 | 14.29 | 139.62 | 01-JAN-00:10 | 1396.20 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM224 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM224 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM301 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM301 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM302_305 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM302_305 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM306_308 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM306_308 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM309_312 | 14.29 | 139.63 | 01-JAN-00:10 | 1396.30 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM309_312 | 14.29 | 139.63 | 01-JAN-00:10 | 1396.30 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM313 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM313 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM314 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM314 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM315_318 | 14.29 | 139.62 | 01-JAN-00:10 | 1396.20 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM315_318 | 14.29 | 139.62 | 01-JAN-00:10 | 1396.20 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM319 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM319 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM320_323 | 14.29 | 139.62 | 01-JAN-00:10 | 1396.20 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM320_323 | 14.29 | 139.62 | 01-JAN-00:10 | 1396.20 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM324 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM324 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM401 | 3.57 | 34.91 | 01-JAN-00:10 | 349.07 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM401 | 3.57 | 34.91 | 01-JAN-00:10 | 349.07 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM402_405 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM402_405 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM406_408 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM406_408 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM409_412 | 14.29 | 139.63 | 01-JAN-00:10 | 1396.30 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM409_412 | 14.29 | 139.63 | 01-JAN-00:10 | 1396.30 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM413 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM413 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM414 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM414 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM415_418 | 14.29 | 139.62 | 01-JAN-00:10 | 1396.20 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM415_418 | 14.29 | 139.62 | 01-JAN-00:10 | 1396.20 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM419 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM419 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM420_423 | 14.29 | 139.62 | 01-JAN-00:10 | 1396.20 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM420_423 | 14.29 | 139.62 | 01-JAN-00:10 | 1396.20 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:GUESTROOM424 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:GUESTROOM424 | 3.57 | 34.91 | 01-JAN-00:10 | 349.05 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:MECHANICALROOMFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MECHANICALROOMFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:MEETINGROOMFLR1 | 2.12 | 0.00 | 01-JAN-00:10 | 237.69 | 01-JAN-08:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:MEETINGROOMFLR1 | 2.12 | 0.00 | 01-JAN-00:10 | 237.69 | 01-JAN-08:10 |
| InteriorEquipment:Electricity:Zone:REARSTAIRSFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:REARSTAIRSFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:REARSTAIRSFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:REARSTAIRSFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:REARSTAIRSFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:REARSTAIRSFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:REARSTAIRSFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:REARSTAIRSFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:REARSTORAGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:REARSTORAGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:REARSTORAGEFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:REARSTORAGEFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:REARSTORAGEFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:REARSTORAGEFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:REARSTORAGEFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:REARSTORAGEFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:RESTROOMFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| MiscPlug:InteriorEquipment:Electricity:Zone:RESTROOMFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| InteriorEquipment:Electricity:Zone:LAUNDRYROOMFLR1 | 28.48 | 0.00 | 01-JAN-00:10 | 2709.07 | 01-JAN-08:10 |
| Laundry:InteriorEquipment:Electricity | 28.48 | 0.00 | 01-JAN-00:10 | 2709.07 | 01-JAN-08:10 |
| Laundry:InteriorEquipment:Electricity:Zone:LAUNDRYROOMFLR1 | 28.48 | 0.00 | 01-JAN-00:10 | 2709.07 | 01-JAN-08:10 |
| Laundry:InteriorEquipment:Electricity:SpaceType:GENERAL | 28.48 | 0.00 | 01-JAN-00:10 | 2709.07 | 01-JAN-08:10 |
| Fans:Electricity | 235.89 | 3960.56 | 14-DEC-08:00 | 8924.30 | 06-FEB-17:50 |
| Fans:Electricity:Zone:GUESTROOM103 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM103 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM104 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM104 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM105 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM105 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM202_205 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM202_205 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM206_208 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM206_208 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM209_212 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM209_212 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM213 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM213 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM214 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM214 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM219 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM219 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM220_223 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM220_223 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM224 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM224 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM309_312 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM309_312 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM314 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM314 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM315_318 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM315_318 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM320_323 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM320_323 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM401 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM401 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM409_412 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM409_412 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM415_418 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM415_418 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM419 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM419 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM420_423 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM420_423 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:GUESTROOM424 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:GUESTROOM424 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 1558.78 | 28784.38 | 13-MAY-05:00 | 96735.42 | 30-JUL-19:40 |
| ElectricityPurchased:Plant | 1558.78 | 28784.38 | 13-MAY-05:00 | 96735.42 | 30-JUL-19:40 |
| Cogeneration:ElectricityPurchased | 1558.78 | 28784.38 | 13-MAY-05:00 | 96735.42 | 30-JUL-19:40 |
| General:Cogeneration:ElectricityPurchased | 1558.78 | 28784.38 | 13-MAY-05:00 | 96735.42 | 30-JUL-19:40 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 1558.78 | 28784.38 | 13-MAY-05:00 | 96735.42 | 30-JUL-19:40 |
| ElectricityNet:Plant | 1558.78 | 28784.38 | 13-MAY-05:00 | 96735.42 | 30-JUL-19:40 |
| Cogeneration:ElectricityNet | 1558.78 | 28784.38 | 13-MAY-05:00 | 96735.42 | 30-JUL-19:40 |
| General:Cogeneration:ElectricityNet | 1558.78 | 28784.38 | 13-MAY-05:00 | 96735.42 | 30-JUL-19:40 |
| Electricity:HVAC | 484.22 | 4233.46 | 20-FEB-08:00 | 52730.27 | 19-JUL-15:20 |
| General:Fans:Electricity | 235.89 | 3960.56 | 14-DEC-08:00 | 8924.30 | 06-FEB-17:50 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 248.34 | 113.06 | 07-FEB-08:00 | 43909.41 | 19-JUL-15:20 |
| General:Cooling:Electricity | 248.34 | 113.06 | 07-FEB-08:00 | 43909.41 | 19-JUL-15:20 |
| ExteriorLights:Electricity | 107.00 | 0.00 | 01-JAN-08:00 | 6812.70 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 107.00 | 0.00 | 01-JAN-08:00 | 6812.70 | 01-JAN-00:10 |
| Electricity:Plant | 1.77 | 8.11 | 12-MAR-15:10 | 441.37 | 07-FEB-07:10 |
| Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Pumps:Electricity | 1.77 | 8.11 | 12-MAR-15:10 | 441.37 | 07-FEB-07:10 |
| General:Pumps:Electricity | 1.77 | 8.11 | 12-MAR-15:10 | 441.37 | 07-FEB-07:10 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 1709.42 | 4031.46 | 16-AUG-01:00 | 217560.30 | 06-FEB-10:10 |
| NaturalGas:Building | 421.49 | 0.00 | 01-JAN-00:10 | 40096.03 | 01-JAN-09:10 |
| NaturalGas:Zone:LAUNDRYROOMFLR1 | 421.49 | 0.00 | 01-JAN-00:10 | 40096.03 | 01-JAN-09:10 |
| NaturalGas:SpaceType:GENERAL | 421.49 | 0.00 | 01-JAN-00:10 | 40096.03 | 01-JAN-09:10 |
| InteriorEquipment:NaturalGas | 421.49 | 0.00 | 01-JAN-00:10 | 40096.03 | 01-JAN-09:10 |
| InteriorEquipment:NaturalGas:Zone:LAUNDRYROOMFLR1 | 421.49 | 0.00 | 01-JAN-00:10 | 40096.03 | 01-JAN-09:10 |
| InteriorEquipment:NaturalGas:SpaceType:GENERAL | 421.49 | 0.00 | 01-JAN-00:10 | 40096.03 | 01-JAN-09:10 |
| Laundry:InteriorEquipment:NaturalGas | 421.49 | 0.00 | 01-JAN-00:10 | 40096.03 | 01-JAN-09:10 |
| Laundry:InteriorEquipment:NaturalGas:Zone:LAUNDRYROOMFLR1 | 421.49 | 0.00 | 01-JAN-00:10 | 40096.03 | 01-JAN-09:10 |
| Laundry:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 421.49 | 0.00 | 01-JAN-00:10 | 40096.03 | 01-JAN-09:10 |
| NaturalGas:HVAC | 0.60 | 0.00 | 01-JAN-00:10 | 2634.67 | 07-FEB-11:00 |
| Heating:NaturalGas | 467.06 | 0.00 | 12-MAR-10:40 | 142651.24 | 07-FEB-07:10 |
| General:Heating:NaturalGas | 0.60 | 0.00 | 01-JAN-00:10 | 2634.67 | 07-FEB-11:00 |
| NaturalGas:Plant | 1287.33 | 4031.46 | 16-AUG-01:00 | 175063.07 | 06-FEB-10:10 |
| Boiler:Heating:NaturalGas | 466.47 | 0.00 | 12-MAR-10:40 | 140767.03 | 07-FEB-07:10 |
| WaterSystems:NaturalGas | 820.86 | 4031.46 | 16-AUG-01:00 | 78879.56 | 18-FEB-08:30 |
| Water Heater:WaterSystems:NaturalGas | 820.86 | 4031.46 | 16-AUG-01:00 | 78879.56 | 18-FEB-08:30 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 2578.17 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-08:10 |
| Water:Plant | 2578.17 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-08:10 |
| WaterSystems:Water | 2578.17 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-08:10 |
| WaterUse:WaterSystems:Water | 2578.17 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-08:10 |
| MainsWater:Facility | 2578.17 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-08:10 |
| MainsWater:Plant | 2578.17 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-08:10 |
| WaterSystems:MainsWater | 2578.17 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-08:10 |
| WaterUse:WaterSystems:MainsWater | 2578.17 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-08:10 |
| Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 3366.84 | 28436.45 | 28-OCT-07:00 | 321483.10 | 26-AUG-09:00 |
| EnergyTransfer:Building | 1091.53 | 9518.89 | 01-DEC-08:00 | 114146.47 | 09-AUG-15:20 |
| EnergyTransfer:Zone:REARSTAIRSFLR1 | 0.12 | 1.74 | 22-JAN-15:50 | 6.11 | 05-FEB-14:40 |
| Heating:EnergyTransfer | 108.74 | 66.85 | 01-APR-10:40 | 57752.37 | 07-FEB-07:10 |
| Heating:EnergyTransfer:Zone:REARSTAIRSFLR1 | 0.12 | 1.74 | 22-JAN-15:50 | 6.11 | 05-FEB-14:40 |
| General:Heating:EnergyTransfer | 108.74 | 66.85 | 01-APR-10:40 | 57752.37 | 07-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:REARSTAIRSFLR1 | 0.12 | 1.74 | 22-JAN-15:50 | 6.11 | 05-FEB-14:40 |
| Cooling:EnergyTransfer | 982.79 | 2351.04 | 07-FEB-05:00 | 114038.61 | 09-AUG-15:20 |
| Cooling:EnergyTransfer:Zone:REARSTAIRSFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer | 982.79 | 2351.04 | 07-FEB-05:00 | 114038.61 | 09-AUG-15:20 |
| General:Cooling:EnergyTransfer:Zone:REARSTAIRSFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:CORRIDORFLR1 | 111.92 | 0.19 | 10-JAN-05:50 | 28582.90 | 07-FEB-07:10 |
| Heating:EnergyTransfer:Zone:CORRIDORFLR1 | 14.06 | 0.00 | 01-JAN-00:10 | 28582.90 | 07-FEB-07:10 |
| General:Heating:EnergyTransfer:Zone:CORRIDORFLR1 | 14.06 | 0.00 | 01-JAN-00:10 | 28582.90 | 07-FEB-07:10 |
| Cooling:EnergyTransfer:Zone:CORRIDORFLR1 | 97.86 | 0.00 | 01-JAN-06:10 | 12872.86 | 16-JUL-16:10 |
| General:Cooling:EnergyTransfer:Zone:CORRIDORFLR1 | 97.86 | 0.00 | 01-JAN-06:10 | 12872.86 | 16-JUL-16:10 |
| EnergyTransfer:Zone:REARSTORAGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:REARSTORAGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:REARSTORAGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:REARSTORAGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:REARSTORAGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:FRONTLOUNGEFLR1 | 72.46 | 0.31 | 13-FEB-21:50 | 6399.63 | 20-JUL-09:00 |
| Heating:EnergyTransfer:Zone:FRONTLOUNGEFLR1 | 0.38 | 0.00 | 01-JAN-00:10 | 2766.86 | 07-DEC-24:00 |
| General:Heating:EnergyTransfer:Zone:FRONTLOUNGEFLR1 | 0.38 | 0.00 | 01-JAN-00:10 | 2766.86 | 07-DEC-24:00 |
| Cooling:EnergyTransfer:Zone:FRONTLOUNGEFLR1 | 72.08 | 0.00 | 04-JAN-00:40 | 6399.63 | 20-JUL-09:00 |
| General:Cooling:EnergyTransfer:Zone:FRONTLOUNGEFLR1 | 72.08 | 0.00 | 04-JAN-00:40 | 6399.63 | 20-JUL-09:00 |
| EnergyTransfer:Zone:RESTROOMFLR1 | 5.67 | 0.05 | 30-MAR-13:10 | 528.88 | 09-AUG-16:20 |
| Heating:EnergyTransfer:Zone:RESTROOMFLR1 | 0.39 | 0.00 | 17-JAN-06:50 | 46.37 | 27-DEC-10:40 |
| General:Heating:EnergyTransfer:Zone:RESTROOMFLR1 | 0.39 | 0.00 | 17-JAN-06:50 | 46.37 | 27-DEC-10:40 |
| Cooling:EnergyTransfer:Zone:RESTROOMFLR1 | 5.28 | 0.00 | 01-JAN-00:10 | 528.88 | 09-AUG-16:20 |
| General:Cooling:EnergyTransfer:Zone:RESTROOMFLR1 | 5.28 | 0.00 | 01-JAN-00:10 | 528.88 | 09-AUG-16:20 |
| EnergyTransfer:Zone:MEETINGROOMFLR1 | 18.89 | 0.00 | 01-JAN-07:10 | 4129.52 | 11-DEC-12:50 |
| Heating:EnergyTransfer:Zone:MEETINGROOMFLR1 | 1.44 | 0.00 | 01-JAN-07:10 | 2314.58 | 11-DEC-12:50 |
| General:Heating:EnergyTransfer:Zone:MEETINGROOMFLR1 | 1.44 | 0.00 | 01-JAN-07:10 | 2314.58 | 11-DEC-12:50 |
| Cooling:EnergyTransfer:Zone:MEETINGROOMFLR1 | 17.45 | 0.00 | 01-JAN-00:10 | 2707.67 | 24-OCT-07:20 |
| General:Cooling:EnergyTransfer:Zone:MEETINGROOMFLR1 | 17.45 | 0.00 | 01-JAN-00:10 | 2707.67 | 24-OCT-07:20 |
| EnergyTransfer:Zone:MECHANICALROOMFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:MECHANICALROOMFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:MECHANICALROOMFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:MECHANICALROOMFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:MECHANICALROOMFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:GUESTROOM101 | 0.18 | 0.00 | 01-JAN-00:10 | 431.20 | 06-FEB-15:10 |
| Heating:EnergyTransfer:Zone:GUESTROOM101 | 0.01 | 0.00 | 01-JAN-00:10 | 114.18 | 15-JUL-14:10 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM101 | 0.01 | 0.00 | 01-JAN-00:10 | 114.18 | 15-JUL-14:10 |
| Cooling:EnergyTransfer:Zone:GUESTROOM101 | 0.17 | 0.00 | 01-JAN-00:10 | 431.20 | 06-FEB-15:10 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM101 | 0.17 | 0.00 | 01-JAN-00:10 | 431.20 | 06-FEB-15:10 |
| EnergyTransfer:Zone:GUESTROOM102 | 0.18 | 0.00 | 01-JAN-00:10 | 424.34 | 06-FEB-15:10 |
| Heating:EnergyTransfer:Zone:GUESTROOM102 | 0.02 | 0.00 | 01-JAN-00:10 | 128.52 | 21-JUL-14:10 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM102 | 0.02 | 0.00 | 01-JAN-00:10 | 128.52 | 21-JUL-14:10 |
| Cooling:EnergyTransfer:Zone:GUESTROOM102 | 0.16 | 0.00 | 01-JAN-00:10 | 424.34 | 06-FEB-15:10 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM102 | 0.16 | 0.00 | 01-JAN-00:10 | 424.34 | 06-FEB-15:10 |
| EnergyTransfer:Zone:GUESTROOM103 | 8.99 | 0.00 | 01-JAN-08:00 | 1594.47 | 03-AUG-20:40 |
| Heating:EnergyTransfer:Zone:GUESTROOM103 | 2.52 | 0.00 | 01-JAN-08:00 | 1190.65 | 06-FEB-16:20 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM103 | 2.52 | 0.00 | 01-JAN-08:00 | 1190.65 | 06-FEB-16:20 |
| Cooling:EnergyTransfer:Zone:GUESTROOM103 | 6.47 | 0.00 | 01-JAN-00:10 | 1594.47 | 03-AUG-20:40 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM103 | 6.47 | 0.00 | 01-JAN-00:10 | 1594.47 | 03-AUG-20:40 |
| EnergyTransfer:Zone:GUESTROOM104 | 10.42 | 0.00 | 01-JAN-08:00 | 1791.09 | 09-SEP-20:30 |
| Heating:EnergyTransfer:Zone:GUESTROOM104 | 0.56 | 0.00 | 01-JAN-00:10 | 859.76 | 07-FEB-09:10 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM104 | 0.56 | 0.00 | 01-JAN-00:10 | 859.76 | 07-FEB-09:10 |
| Cooling:EnergyTransfer:Zone:GUESTROOM104 | 9.85 | 0.00 | 01-JAN-01:20 | 1791.09 | 09-SEP-20:30 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM104 | 9.85 | 0.00 | 01-JAN-01:20 | 1791.09 | 09-SEP-20:30 |
| EnergyTransfer:Zone:GUESTROOM105 | 21.03 | 0.00 | 01-JAN-08:00 | 2180.80 | 09-SEP-20:30 |
| Heating:EnergyTransfer:Zone:GUESTROOM105 | 0.04 | 0.00 | 01-JAN-00:10 | 173.73 | 09-JAN-09:10 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM105 | 0.04 | 0.00 | 01-JAN-00:10 | 173.73 | 09-JAN-09:10 |
| Cooling:EnergyTransfer:Zone:GUESTROOM105 | 20.99 | 0.00 | 01-JAN-08:00 | 2180.80 | 09-SEP-20:30 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM105 | 20.99 | 0.00 | 01-JAN-08:00 | 2180.80 | 09-SEP-20:30 |
| EnergyTransfer:Zone:EMPLOYEELOUNGEFLR1 | 69.03 | 843.65 | 01-FEB-05:00 | 4492.92 | 21-SEP-12:00 |
| Heating:EnergyTransfer:Zone:EMPLOYEELOUNGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:EMPLOYEELOUNGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:EMPLOYEELOUNGEFLR1 | 69.03 | 843.65 | 01-FEB-05:00 | 4492.92 | 21-SEP-12:00 |
| General:Cooling:EnergyTransfer:Zone:EMPLOYEELOUNGEFLR1 | 69.03 | 843.65 | 01-FEB-05:00 | 4492.92 | 21-SEP-12:00 |
| EnergyTransfer:Zone:LAUNDRYROOMFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:LAUNDRYROOMFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:LAUNDRYROOMFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:LAUNDRYROOMFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:LAUNDRYROOMFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:ELEVATORCOREFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:ELEVATORCOREFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:ELEVATORCOREFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:EXERCISECENTERFLR1 | 22.54 | 0.01 | 27-JAN-02:50 | 1648.71 | 21-SEP-15:20 |
| Heating:EnergyTransfer:Zone:EXERCISECENTERFLR1 | 0.03 | 0.00 | 01-JAN-00:10 | 607.65 | 25-JAN-04:40 |
| General:Heating:EnergyTransfer:Zone:EXERCISECENTERFLR1 | 0.03 | 0.00 | 01-JAN-00:10 | 607.65 | 25-JAN-04:40 |
| Cooling:EnergyTransfer:Zone:EXERCISECENTERFLR1 | 22.51 | 0.00 | 04-JAN-03:00 | 1648.71 | 21-SEP-15:20 |
| General:Cooling:EnergyTransfer:Zone:EXERCISECENTERFLR1 | 22.51 | 0.00 | 04-JAN-03:00 | 1648.71 | 21-SEP-15:20 |
| EnergyTransfer:Zone:FRONTOFFICEFLR1 | 41.69 | 0.03 | 07-FEB-22:00 | 4899.06 | 21-SEP-14:10 |
| Heating:EnergyTransfer:Zone:FRONTOFFICEFLR1 | 0.11 | 0.00 | 01-JAN-00:10 | 989.18 | 11-DEC-04:10 |
| General:Heating:EnergyTransfer:Zone:FRONTOFFICEFLR1 | 0.11 | 0.00 | 01-JAN-00:10 | 989.18 | 11-DEC-04:10 |
| Cooling:EnergyTransfer:Zone:FRONTOFFICEFLR1 | 41.57 | 0.00 | 04-JAN-04:00 | 4899.06 | 21-SEP-14:10 |
| General:Cooling:EnergyTransfer:Zone:FRONTOFFICEFLR1 | 41.57 | 0.00 | 04-JAN-04:00 | 4899.06 | 21-SEP-14:10 |
| EnergyTransfer:Zone:FRONTSTAIRSFLR1 | 0.56 | 8.56 | 22-JAN-15:50 | 283.12 | 07-FEB-11:00 |
| Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR1 | 0.56 | 8.56 | 22-JAN-15:50 | 283.12 | 07-FEB-11:00 |
| General:Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR1 | 0.56 | 8.56 | 22-JAN-15:50 | 283.12 | 07-FEB-11:00 |
| Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:FRONTSTORAGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:REARSTAIRSFLR2 | 0.12 | 1.51 | 22-JAN-15:50 | 85.40 | 07-FEB-10:50 |
| Heating:EnergyTransfer:Zone:REARSTAIRSFLR2 | 0.12 | 1.51 | 22-JAN-15:50 | 85.40 | 07-FEB-10:50 |
| General:Heating:EnergyTransfer:Zone:REARSTAIRSFLR2 | 0.12 | 1.51 | 22-JAN-15:50 | 85.40 | 07-FEB-10:50 |
| Cooling:EnergyTransfer:Zone:REARSTAIRSFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:REARSTAIRSFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:CORRIDORFLR2 | 33.03 | 0.67 | 22-FEB-05:20 | 2704.16 | 17-JUL-19:40 |
| Heating:EnergyTransfer:Zone:CORRIDORFLR2 | 0.08 | 0.00 | 01-JAN-00:10 | 687.87 | 07-FEB-11:00 |
| General:Heating:EnergyTransfer:Zone:CORRIDORFLR2 | 0.08 | 0.00 | 01-JAN-00:10 | 687.87 | 07-FEB-11:00 |
| Cooling:EnergyTransfer:Zone:CORRIDORFLR2 | 32.95 | 0.00 | 12-JAN-05:00 | 2704.16 | 17-JUL-19:40 |
| General:Cooling:EnergyTransfer:Zone:CORRIDORFLR2 | 32.95 | 0.00 | 12-JAN-05:00 | 2704.16 | 17-JUL-19:40 |
| EnergyTransfer:Zone:REARSTORAGEFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:REARSTORAGEFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:REARSTORAGEFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:REARSTORAGEFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:REARSTORAGEFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:GUESTROOM201 | 0.20 | 0.00 | 01-JAN-00:10 | 333.84 | 26-DEC-15:30 |
| Heating:EnergyTransfer:Zone:GUESTROOM201 | 0.07 | 0.00 | 01-JAN-00:10 | 262.33 | 07-FEB-08:00 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM201 | 0.07 | 0.00 | 01-JAN-00:10 | 262.33 | 07-FEB-08:00 |
| Cooling:EnergyTransfer:Zone:GUESTROOM201 | 0.13 | 0.00 | 01-JAN-00:10 | 313.90 | 08-FEB-15:10 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM201 | 0.13 | 0.00 | 01-JAN-00:10 | 313.90 | 08-FEB-15:10 |
| EnergyTransfer:Zone:GUESTROOM202_205 | 33.91 | 0.00 | 01-JAN-08:00 | 5846.94 | 06-JUL-18:20 |
| Heating:EnergyTransfer:Zone:GUESTROOM202_205 | 2.86 | 0.00 | 01-JAN-07:10 | 2882.68 | 06-FEB-16:20 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM202_205 | 2.86 | 0.00 | 01-JAN-07:10 | 2882.68 | 06-FEB-16:20 |
| Cooling:EnergyTransfer:Zone:GUESTROOM202_205 | 31.05 | 0.00 | 01-JAN-00:10 | 5846.94 | 06-JUL-18:20 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM202_205 | 31.05 | 0.00 | 01-JAN-00:10 | 5846.94 | 06-JUL-18:20 |
| EnergyTransfer:Zone:GUESTROOM206_208 | 28.18 | 0.00 | 01-JAN-08:00 | 4790.70 | 30-JUN-19:20 |
| Heating:EnergyTransfer:Zone:GUESTROOM206_208 | 1.19 | 0.00 | 01-JAN-00:10 | 2089.35 | 06-FEB-16:20 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM206_208 | 1.19 | 0.00 | 01-JAN-00:10 | 2089.35 | 06-FEB-16:20 |
| Cooling:EnergyTransfer:Zone:GUESTROOM206_208 | 26.99 | 0.00 | 01-JAN-02:40 | 4790.70 | 30-JUN-19:20 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM206_208 | 26.99 | 0.00 | 01-JAN-02:40 | 4790.70 | 30-JUN-19:20 |
| EnergyTransfer:Zone:GUESTROOM209_212 | 33.61 | 0.00 | 01-JAN-08:00 | 5819.44 | 06-JUL-19:40 |
| Heating:EnergyTransfer:Zone:GUESTROOM209_212 | 0.92 | 0.00 | 01-JAN-00:10 | 2474.70 | 06-FEB-16:20 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM209_212 | 0.92 | 0.00 | 01-JAN-00:10 | 2474.70 | 06-FEB-16:20 |
| Cooling:EnergyTransfer:Zone:GUESTROOM209_212 | 32.69 | 0.00 | 01-JAN-08:00 | 5819.44 | 06-JUL-19:40 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM209_212 | 32.69 | 0.00 | 01-JAN-08:00 | 5819.44 | 06-JUL-19:40 |
| EnergyTransfer:Zone:GUESTROOM213 | 9.31 | 0.00 | 01-JAN-08:00 | 1474.78 | 02-AUG-20:20 |
| Heating:EnergyTransfer:Zone:GUESTROOM213 | 2.72 | 0.00 | 01-JAN-08:00 | 1163.73 | 06-FEB-16:20 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM213 | 2.72 | 0.00 | 01-JAN-08:00 | 1163.73 | 06-FEB-16:20 |
| Cooling:EnergyTransfer:Zone:GUESTROOM213 | 6.58 | 0.00 | 01-JAN-00:10 | 1474.78 | 02-AUG-20:20 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM213 | 6.58 | 0.00 | 01-JAN-00:10 | 1474.78 | 02-AUG-20:20 |
| EnergyTransfer:Zone:GUESTROOM214 | 13.20 | 0.00 | 01-JAN-08:00 | 1843.26 | 09-SEP-20:30 |
| Heating:EnergyTransfer:Zone:GUESTROOM214 | 0.29 | 0.00 | 01-JAN-00:10 | 654.61 | 06-FEB-09:10 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM214 | 0.29 | 0.00 | 01-JAN-00:10 | 654.61 | 06-FEB-09:10 |
| Cooling:EnergyTransfer:Zone:GUESTROOM214 | 12.91 | 0.00 | 01-JAN-08:00 | 1843.26 | 09-SEP-20:30 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM214 | 12.91 | 0.00 | 01-JAN-08:00 | 1843.26 | 09-SEP-20:30 |
| EnergyTransfer:Zone:GUESTROOM215_218 | 55.31 | 0.00 | 01-JAN-06:30 | 5279.20 | 21-SEP-14:50 |
| Heating:EnergyTransfer:Zone:GUESTROOM215_218 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM215_218 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:GUESTROOM215_218 | 55.31 | 0.00 | 01-JAN-06:30 | 5279.20 | 21-SEP-14:50 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM215_218 | 55.31 | 0.00 | 01-JAN-06:30 | 5279.20 | 21-SEP-14:50 |
| EnergyTransfer:Zone:ELEVATORCOREFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:ELEVATORCOREFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:ELEVATORCOREFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:GUESTROOM219 | 75.23 | 0.00 | 14-MAR-17:20 | 5149.85 | 20-SEP-16:10 |
| Heating:EnergyTransfer:Zone:GUESTROOM219 | 0.03 | 0.00 | 01-JAN-00:10 | 156.05 | 07-FEB-09:10 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM219 | 0.03 | 0.00 | 01-JAN-00:10 | 156.05 | 07-FEB-09:10 |
| Cooling:EnergyTransfer:Zone:GUESTROOM219 | 75.20 | 0.00 | 14-MAR-17:20 | 5149.85 | 20-SEP-16:10 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM219 | 75.20 | 0.00 | 14-MAR-17:20 | 5149.85 | 20-SEP-16:10 |
| EnergyTransfer:Zone:GUESTROOM220_223 | 45.14 | 0.00 | 01-JAN-08:00 | 6207.62 | 19-SEP-20:30 |
| Heating:EnergyTransfer:Zone:GUESTROOM220_223 | 0.24 | 0.00 | 01-JAN-00:10 | 716.66 | 06-FEB-09:10 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM220_223 | 0.24 | 0.00 | 01-JAN-00:10 | 716.66 | 06-FEB-09:10 |
| Cooling:EnergyTransfer:Zone:GUESTROOM220_223 | 44.90 | 0.00 | 01-JAN-08:00 | 6207.62 | 19-SEP-20:30 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM220_223 | 44.90 | 0.00 | 01-JAN-08:00 | 6207.62 | 19-SEP-20:30 |
| EnergyTransfer:Zone:GUESTROOM224 | 11.97 | 0.00 | 01-JAN-08:00 | 1772.51 | 09-SEP-20:30 |
| Heating:EnergyTransfer:Zone:GUESTROOM224 | 0.53 | 0.00 | 01-JAN-06:20 | 675.11 | 06-FEB-16:20 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM224 | 0.53 | 0.00 | 01-JAN-06:20 | 675.11 | 06-FEB-16:20 |
| Cooling:EnergyTransfer:Zone:GUESTROOM224 | 11.44 | 0.00 | 01-JAN-00:10 | 1772.51 | 09-SEP-20:30 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM224 | 11.44 | 0.00 | 01-JAN-00:10 | 1772.51 | 09-SEP-20:30 |
| EnergyTransfer:Zone:FRONTSTORAGEFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:FRONTSTAIRSFLR2 | 0.52 | 7.26 | 22-JAN-15:50 | 340.94 | 07-FEB-10:40 |
| Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR2 | 0.52 | 7.26 | 22-JAN-15:50 | 340.94 | 07-FEB-10:40 |
| General:Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR2 | 0.52 | 7.26 | 22-JAN-15:50 | 340.94 | 07-FEB-10:40 |
| Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR2 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:REARSTAIRSFLR3 | 0.13 | 1.51 | 22-JAN-15:50 | 86.06 | 06-FEB-19:00 |
| Heating:EnergyTransfer:Zone:REARSTAIRSFLR3 | 0.13 | 1.51 | 22-JAN-15:50 | 86.06 | 06-FEB-19:00 |
| General:Heating:EnergyTransfer:Zone:REARSTAIRSFLR3 | 0.13 | 1.51 | 22-JAN-15:50 | 86.06 | 06-FEB-19:00 |
| Cooling:EnergyTransfer:Zone:REARSTAIRSFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:REARSTAIRSFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:CORRIDORFLR3 | 22.36 | 0.02 | 17-NOV-22:50 | 2120.02 | 07-FEB-05:00 |
| Heating:EnergyTransfer:Zone:CORRIDORFLR3 | 6.34 | 0.00 | 15-JAN-09:50 | 2120.02 | 07-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:CORRIDORFLR3 | 6.34 | 0.00 | 15-JAN-09:50 | 2120.02 | 07-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:CORRIDORFLR3 | 16.02 | 0.00 | 01-JAN-00:10 | 2030.94 | 19-JUL-15:20 |
| General:Cooling:EnergyTransfer:Zone:CORRIDORFLR3 | 16.02 | 0.00 | 01-JAN-00:10 | 2030.94 | 19-JUL-15:20 |
| EnergyTransfer:Zone:REARSTORAGEFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:REARSTORAGEFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:REARSTORAGEFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:REARSTORAGEFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:REARSTORAGEFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:GUESTROOM301 | 0.93 | 0.00 | 01-JAN-00:10 | 513.61 | 06-FEB-19:00 |
| Heating:EnergyTransfer:Zone:GUESTROOM301 | 0.86 | 0.00 | 01-JAN-00:10 | 513.61 | 06-FEB-19:00 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM301 | 0.86 | 0.00 | 01-JAN-00:10 | 513.61 | 06-FEB-19:00 |
| Cooling:EnergyTransfer:Zone:GUESTROOM301 | 0.07 | 0.00 | 01-JAN-00:10 | 205.59 | 24-MAR-14:10 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM301 | 0.07 | 0.00 | 01-JAN-00:10 | 205.59 | 24-MAR-14:10 |
| EnergyTransfer:Zone:GUESTROOM302_305 | 0.78 | 0.00 | 01-JAN-00:10 | 1198.53 | 25-DEC-15:10 |
| Heating:EnergyTransfer:Zone:GUESTROOM302_305 | 0.36 | 0.00 | 01-JAN-00:10 | 699.11 | 07-FEB-08:00 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM302_305 | 0.36 | 0.00 | 01-JAN-00:10 | 699.11 | 07-FEB-08:00 |
| Cooling:EnergyTransfer:Zone:GUESTROOM302_305 | 0.42 | 0.00 | 01-JAN-00:10 | 1198.53 | 25-DEC-15:10 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM302_305 | 0.42 | 0.00 | 01-JAN-00:10 | 1198.53 | 25-DEC-15:10 |
| EnergyTransfer:Zone:GUESTROOM306_308 | 0.46 | 0.00 | 01-JAN-00:10 | 1010.56 | 12-FEB-15:10 |
| Heating:EnergyTransfer:Zone:GUESTROOM306_308 | 0.06 | 0.00 | 01-JAN-00:10 | 329.05 | 06-FEB-19:00 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM306_308 | 0.06 | 0.00 | 01-JAN-00:10 | 329.05 | 06-FEB-19:00 |
| Cooling:EnergyTransfer:Zone:GUESTROOM306_308 | 0.40 | 0.00 | 01-JAN-00:10 | 1010.56 | 12-FEB-15:10 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM306_308 | 0.40 | 0.00 | 01-JAN-00:10 | 1010.56 | 12-FEB-15:10 |
| EnergyTransfer:Zone:GUESTROOM309_312 | 30.54 | 0.00 | 01-JAN-08:00 | 5650.03 | 30-JUN-19:20 |
| Heating:EnergyTransfer:Zone:GUESTROOM309_312 | 2.39 | 0.00 | 01-JAN-06:10 | 2758.53 | 06-FEB-16:20 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM309_312 | 2.39 | 0.00 | 01-JAN-06:10 | 2758.53 | 06-FEB-16:20 |
| Cooling:EnergyTransfer:Zone:GUESTROOM309_312 | 28.15 | 0.00 | 01-JAN-00:10 | 5650.03 | 30-JUN-19:20 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM309_312 | 28.15 | 0.00 | 01-JAN-00:10 | 5650.03 | 30-JUN-19:20 |
| EnergyTransfer:Zone:GUESTROOM313 | 0.43 | 0.00 | 01-JAN-00:10 | 386.69 | 07-FEB-08:00 |
| Heating:EnergyTransfer:Zone:GUESTROOM313 | 0.36 | 0.00 | 01-JAN-00:10 | 386.69 | 07-FEB-08:00 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM313 | 0.36 | 0.00 | 01-JAN-00:10 | 386.69 | 07-FEB-08:00 |
| Cooling:EnergyTransfer:Zone:GUESTROOM313 | 0.07 | 0.00 | 01-JAN-00:10 | 242.85 | 25-DEC-15:10 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM313 | 0.07 | 0.00 | 01-JAN-00:10 | 242.85 | 25-DEC-15:10 |
| EnergyTransfer:Zone:GUESTROOM314 | 11.33 | 0.00 | 01-JAN-08:00 | 1788.22 | 09-SEP-20:30 |
| Heating:EnergyTransfer:Zone:GUESTROOM314 | 1.57 | 0.00 | 01-JAN-08:00 | 965.56 | 06-FEB-16:20 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM314 | 1.57 | 0.00 | 01-JAN-08:00 | 965.56 | 06-FEB-16:20 |
| Cooling:EnergyTransfer:Zone:GUESTROOM314 | 9.76 | 0.00 | 01-JAN-00:10 | 1788.22 | 09-SEP-20:30 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM314 | 9.76 | 0.00 | 01-JAN-00:10 | 1788.22 | 09-SEP-20:30 |
| EnergyTransfer:Zone:GUESTROOM315_318 | 60.60 | 0.00 | 01-JAN-08:00 | 7275.98 | 19-AUG-20:20 |
| Heating:EnergyTransfer:Zone:GUESTROOM315_318 | 0.12 | 0.00 | 01-JAN-00:10 | 731.16 | 06-FEB-02:40 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM315_318 | 0.12 | 0.00 | 01-JAN-00:10 | 731.16 | 06-FEB-02:40 |
| Cooling:EnergyTransfer:Zone:GUESTROOM315_318 | 60.47 | 0.00 | 01-JAN-08:00 | 7275.98 | 19-AUG-20:20 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM315_318 | 60.47 | 0.00 | 01-JAN-08:00 | 7275.98 | 19-AUG-20:20 |
| EnergyTransfer:Zone:ELEVATORCOREFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:ELEVATORCOREFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:ELEVATORCOREFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:GUESTROOM319 | 0.60 | 0.00 | 01-JAN-00:10 | 428.71 | 06-FEB-15:10 |
| Heating:EnergyTransfer:Zone:GUESTROOM319 | 0.00 | 0.00 | 01-JAN-00:10 | 37.91 | 14-MAR-15:00 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM319 | 0.00 | 0.00 | 01-JAN-00:10 | 37.91 | 14-MAR-15:00 |
| Cooling:EnergyTransfer:Zone:GUESTROOM319 | 0.60 | 0.00 | 01-JAN-00:10 | 428.71 | 06-FEB-15:10 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM319 | 0.60 | 0.00 | 01-JAN-00:10 | 428.71 | 06-FEB-15:10 |
| EnergyTransfer:Zone:GUESTROOM320_323 | 38.41 | 0.00 | 01-JAN-08:00 | 6074.00 | 19-AUG-20:20 |
| Heating:EnergyTransfer:Zone:GUESTROOM320_323 | 0.62 | 0.00 | 01-JAN-00:10 | 1519.97 | 05-DEC-16:20 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM320_323 | 0.62 | 0.00 | 01-JAN-00:10 | 1519.97 | 05-DEC-16:20 |
| Cooling:EnergyTransfer:Zone:GUESTROOM320_323 | 37.79 | 0.00 | 01-JAN-08:00 | 6074.00 | 19-AUG-20:20 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM320_323 | 37.79 | 0.00 | 01-JAN-08:00 | 6074.00 | 19-AUG-20:20 |
| EnergyTransfer:Zone:GUESTROOM324 | 0.18 | 0.00 | 01-JAN-00:10 | 407.28 | 06-FEB-15:10 |
| Heating:EnergyTransfer:Zone:GUESTROOM324 | 0.01 | 0.00 | 01-JAN-00:10 | 73.05 | 15-JUL-14:10 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM324 | 0.01 | 0.00 | 01-JAN-00:10 | 73.05 | 15-JUL-14:10 |
| Cooling:EnergyTransfer:Zone:GUESTROOM324 | 0.17 | 0.00 | 01-JAN-00:10 | 407.28 | 06-FEB-15:10 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM324 | 0.17 | 0.00 | 01-JAN-00:10 | 407.28 | 06-FEB-15:10 |
| EnergyTransfer:Zone:FRONTSTORAGEFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:FRONTSTAIRSFLR3 | 0.69 | 8.99 | 22-JAN-15:50 | 426.95 | 06-FEB-19:00 |
| Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR3 | 0.69 | 8.99 | 22-JAN-15:50 | 426.95 | 06-FEB-19:00 |
| General:Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR3 | 0.69 | 8.99 | 22-JAN-15:50 | 426.95 | 06-FEB-19:00 |
| Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR3 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:REARSTAIRSFLR4 | 0.55 | 5.96 | 22-JAN-15:50 | 309.50 | 07-FEB-03:00 |
| Heating:EnergyTransfer:Zone:REARSTAIRSFLR4 | 0.55 | 5.96 | 22-JAN-15:50 | 309.50 | 07-FEB-03:00 |
| General:Heating:EnergyTransfer:Zone:REARSTAIRSFLR4 | 0.55 | 5.96 | 22-JAN-15:50 | 309.50 | 07-FEB-03:00 |
| Cooling:EnergyTransfer:Zone:REARSTAIRSFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:REARSTAIRSFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:CORRIDORFLR4 | 35.57 | 0.03 | 14-MAR-02:30 | 3989.63 | 07-FEB-05:00 |
| Heating:EnergyTransfer:Zone:CORRIDORFLR4 | 20.94 | 0.00 | 15-JAN-13:00 | 3989.63 | 07-FEB-05:00 |
| General:Heating:EnergyTransfer:Zone:CORRIDORFLR4 | 20.94 | 0.00 | 15-JAN-13:00 | 3989.63 | 07-FEB-05:00 |
| Cooling:EnergyTransfer:Zone:CORRIDORFLR4 | 14.62 | 0.00 | 01-JAN-00:10 | 3436.34 | 09-AUG-15:10 |
| General:Cooling:EnergyTransfer:Zone:CORRIDORFLR4 | 14.62 | 0.00 | 01-JAN-00:10 | 3436.34 | 09-AUG-15:10 |
| EnergyTransfer:Zone:REARSTORAGEFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:REARSTORAGEFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:REARSTORAGEFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:REARSTORAGEFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:REARSTORAGEFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:GUESTROOM401 | 13.79 | 0.00 | 01-JAN-08:00 | 1986.90 | 24-JUN-18:20 |
| Heating:EnergyTransfer:Zone:GUESTROOM401 | 7.67 | 0.00 | 01-JAN-08:00 | 1753.38 | 06-FEB-16:20 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM401 | 7.67 | 0.00 | 01-JAN-08:00 | 1753.38 | 06-FEB-16:20 |
| Cooling:EnergyTransfer:Zone:GUESTROOM401 | 6.12 | 0.00 | 01-JAN-00:10 | 1986.90 | 24-JUN-18:20 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM401 | 6.12 | 0.00 | 01-JAN-00:10 | 1986.90 | 24-JUN-18:20 |
| EnergyTransfer:Zone:GUESTROOM402_405 | 7.37 | 0.00 | 01-JAN-11:40 | 2131.05 | 07-FEB-07:30 |
| Heating:EnergyTransfer:Zone:GUESTROOM402_405 | 6.14 | 0.00 | 01-JAN-11:40 | 2131.05 | 07-FEB-07:30 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM402_405 | 6.14 | 0.00 | 01-JAN-11:40 | 2131.05 | 07-FEB-07:30 |
| Cooling:EnergyTransfer:Zone:GUESTROOM402_405 | 1.23 | 0.00 | 01-JAN-00:10 | 1339.03 | 21-JUL-13:40 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM402_405 | 1.23 | 0.00 | 01-JAN-00:10 | 1339.03 | 21-JUL-13:40 |
| EnergyTransfer:Zone:GUESTROOM406_408 | 4.79 | 0.00 | 01-JAN-10:00 | 1590.54 | 07-FEB-07:30 |
| Heating:EnergyTransfer:Zone:GUESTROOM406_408 | 3.86 | 0.00 | 01-JAN-10:00 | 1590.54 | 07-FEB-07:30 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM406_408 | 3.86 | 0.00 | 01-JAN-10:00 | 1590.54 | 07-FEB-07:30 |
| Cooling:EnergyTransfer:Zone:GUESTROOM406_408 | 0.93 | 0.00 | 01-JAN-00:10 | 990.87 | 21-JUL-13:40 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM406_408 | 0.93 | 0.00 | 01-JAN-00:10 | 990.87 | 21-JUL-13:40 |
| EnergyTransfer:Zone:GUESTROOM409_412 | 33.39 | 0.00 | 01-JAN-08:00 | 7256.46 | 24-JUN-18:20 |
| Heating:EnergyTransfer:Zone:GUESTROOM409_412 | 8.85 | 0.00 | 01-JAN-08:00 | 4012.93 | 06-FEB-16:20 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM409_412 | 8.85 | 0.00 | 01-JAN-08:00 | 4012.93 | 06-FEB-16:20 |
| Cooling:EnergyTransfer:Zone:GUESTROOM409_412 | 24.54 | 0.00 | 01-JAN-00:10 | 7256.46 | 24-JUN-18:20 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM409_412 | 24.54 | 0.00 | 01-JAN-00:10 | 7256.46 | 24-JUN-18:20 |
| EnergyTransfer:Zone:GUESTROOM413 | 2.44 | 0.00 | 01-JAN-10:50 | 831.42 | 07-FEB-07:20 |
| Heating:EnergyTransfer:Zone:GUESTROOM413 | 2.25 | 0.00 | 01-JAN-10:50 | 831.42 | 07-FEB-07:20 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM413 | 2.25 | 0.00 | 01-JAN-10:50 | 831.42 | 07-FEB-07:20 |
| Cooling:EnergyTransfer:Zone:GUESTROOM413 | 0.20 | 0.00 | 01-JAN-00:10 | 326.75 | 21-JUL-13:50 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM413 | 0.20 | 0.00 | 01-JAN-00:10 | 326.75 | 21-JUL-13:50 |
| EnergyTransfer:Zone:GUESTROOM414 | 1.28 | 0.00 | 01-JAN-00:10 | 564.87 | 07-FEB-07:30 |
| Heating:EnergyTransfer:Zone:GUESTROOM414 | 0.65 | 0.00 | 01-JAN-00:10 | 564.87 | 07-FEB-07:30 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM414 | 0.65 | 0.00 | 01-JAN-00:10 | 564.87 | 07-FEB-07:30 |
| Cooling:EnergyTransfer:Zone:GUESTROOM414 | 0.63 | 0.00 | 01-JAN-00:10 | 559.23 | 09-AUG-13:40 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM414 | 0.63 | 0.00 | 01-JAN-00:10 | 559.23 | 09-AUG-13:40 |
| EnergyTransfer:Zone:GUESTROOM415_418 | 40.05 | 0.00 | 01-JAN-08:00 | 7772.26 | 20-SEP-16:10 |
| Heating:EnergyTransfer:Zone:GUESTROOM415_418 | 4.05 | 0.00 | 01-JAN-07:40 | 3538.64 | 06-FEB-19:10 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM415_418 | 4.05 | 0.00 | 01-JAN-07:40 | 3538.64 | 06-FEB-19:10 |
| Cooling:EnergyTransfer:Zone:GUESTROOM415_418 | 36.00 | 0.00 | 01-JAN-00:10 | 7772.26 | 20-SEP-16:10 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM415_418 | 36.00 | 0.00 | 01-JAN-00:10 | 7772.26 | 20-SEP-16:10 |
| EnergyTransfer:Zone:ELEVATORCOREFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:ELEVATORCOREFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:ELEVATORCOREFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:ELEVATORCOREFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:GUESTROOM419 | 11.52 | 0.00 | 01-JAN-08:00 | 2122.90 | 20-SEP-16:10 |
| Heating:EnergyTransfer:Zone:GUESTROOM419 | 1.40 | 0.00 | 01-JAN-08:00 | 989.02 | 06-FEB-19:10 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM419 | 1.40 | 0.00 | 01-JAN-08:00 | 989.02 | 06-FEB-19:10 |
| Cooling:EnergyTransfer:Zone:GUESTROOM419 | 10.12 | 0.00 | 01-JAN-00:10 | 2122.90 | 20-SEP-16:10 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM419 | 10.12 | 0.00 | 01-JAN-00:10 | 2122.90 | 20-SEP-16:10 |
| EnergyTransfer:Zone:GUESTROOM420_423 | 37.00 | 0.00 | 01-JAN-08:00 | 7436.57 | 20-SEP-16:10 |
| Heating:EnergyTransfer:Zone:GUESTROOM420_423 | 4.61 | 0.00 | 01-JAN-08:00 | 3480.13 | 28-DEC-16:20 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM420_423 | 4.61 | 0.00 | 01-JAN-08:00 | 3480.13 | 28-DEC-16:20 |
| Cooling:EnergyTransfer:Zone:GUESTROOM420_423 | 32.39 | 0.00 | 01-JAN-00:10 | 7436.57 | 20-SEP-16:10 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM420_423 | 32.39 | 0.00 | 01-JAN-00:10 | 7436.57 | 20-SEP-16:10 |
| EnergyTransfer:Zone:GUESTROOM424 | 11.74 | 0.00 | 01-JAN-08:00 | 2087.32 | 20-SEP-16:10 |
| Heating:EnergyTransfer:Zone:GUESTROOM424 | 3.24 | 0.00 | 01-JAN-08:00 | 1320.96 | 06-FEB-09:10 |
| General:Heating:EnergyTransfer:Zone:GUESTROOM424 | 3.24 | 0.00 | 01-JAN-08:00 | 1320.96 | 06-FEB-09:10 |
| Cooling:EnergyTransfer:Zone:GUESTROOM424 | 8.50 | 0.00 | 01-JAN-00:10 | 2087.32 | 20-SEP-16:10 |
| General:Cooling:EnergyTransfer:Zone:GUESTROOM424 | 8.50 | 0.00 | 01-JAN-00:10 | 2087.32 | 20-SEP-16:10 |
| EnergyTransfer:Zone:FRONTSTORAGEFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:FRONTSTORAGEFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:FRONTSTORAGEFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:FRONTSTAIRSFLR4 | 1.23 | 11.95 | 01-APR-10:40 | 685.52 | 06-FEB-10:00 |
| Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR4 | 1.23 | 11.95 | 01-APR-10:40 | 685.52 | 06-FEB-10:00 |
| General:Heating:EnergyTransfer:Zone:FRONTSTAIRSFLR4 | 1.23 | 11.95 | 01-APR-10:40 | 685.52 | 06-FEB-10:00 |
| Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:FRONTSTAIRSFLR4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| PlantLoopHeatingDemand:Facility | 947.38 | 3071.11 | 16-AUG-00:10 | 139760.39 | 07-FEB-09:10 |
| PlantLoopHeatingDemand:Plant | 640.31 | 3071.11 | 16-AUG-00:10 | 61816.17 | 12-FEB-08:10 |
| WaterSystems:PlantLoopHeatingDemand | 640.31 | 3071.11 | 16-AUG-00:10 | 61816.17 | 12-FEB-08:10 |
| General:WaterSystems:PlantLoopHeatingDemand | 640.31 | 3071.11 | 16-AUG-00:10 | 61816.17 | 12-FEB-08:10 |
| EnergyTransfer:HVAC | 1330.83 | 3385.36 | 12-MAY-07:00 | 180476.70 | 15-AUG-08:50 |
| HeatingCoils:EnergyTransfer | 307.55 | 0.00 | 12-MAR-10:40 | 105477.44 | 07-FEB-07:10 |
| PlantLoopHeatingDemand:HVAC | 307.08 | 0.00 | 12-MAR-10:40 | 103984.21 | 07-FEB-07:10 |
| HeatingCoils:PlantLoopHeatingDemand | 307.08 | 0.00 | 12-MAR-10:40 | 103984.21 | 07-FEB-07:10 |
| CoolingCoils:EnergyTransfer | 1023.28 | 447.97 | 07-FEB-08:00 | 180476.70 | 15-AUG-08:50 |
| EnergyTransfer:Plant | 944.47 | 3071.11 | 16-AUG-00:10 | 131042.23 | 06-FEB-10:10 |
| WaterSystems:EnergyTransfer | 640.31 | 3071.11 | 16-AUG-00:10 | 61816.17 | 12-FEB-08:10 |
| WaterUse:WaterSystems:EnergyTransfer | 640.31 | 3071.11 | 16-AUG-00:10 | 61816.17 | 12-FEB-08:10 |
| Boilers:EnergyTransfer | 304.17 | 0.00 | 12-MAR-10:40 | 103060.90 | 07-FEB-07:10 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| REARSTAIRSFLR1 | 0.123 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.088 | 0.000 | 0.000 | 0.000 | 0.035 | 0.483 | 0.000 | 0.000 | 0.000 | -4.729 | -0.000 |
| CORRIDORFLR1 | 14.061 | -97.861 | 0.000 | 0.000 | 0.000 | 0.000 | 4.921 | 25.545 | 0.000 | 2.484 | 0.000 | 0.812 | 118.442 | 0.000 | -10.265 | 0.000 | -58.139 | 0.000 |
| FRONTLOUNGEFLR1 | 0.379 | -72.083 | 0.000 | 0.000 | 0.000 | 0.000 | 34.234 | 36.127 | 50.363 | 3.564 | 0.000 | 0.050 | 0.000 | 0.000 | -13.076 | 0.000 | -4.226 | -35.332 |
| RESTROOMFLR1 | 0.392 | -5.279 | 0.000 | 0.000 | 0.000 | 0.000 | 1.051 | 9.963 | 0.000 | 0.000 | 0.000 | 0.007 | 0.000 | 0.000 | 0.000 | 0.000 | -0.658 | -5.475 |
| MEETINGROOMFLR1 | 1.441 | -17.449 | 0.000 | 0.000 | 0.000 | 0.000 | 7.452 | 17.786 | 2.117 | 2.629 | 0.000 | 0.016 | 0.000 | 0.000 | -10.422 | 0.000 | -1.484 | -2.085 |
| MECHANICALROOMFLR1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.151 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -0.743 | -3.408 |
| GUESTROOM101 | 0.013 | -0.170 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.833 | 0.000 | 0.003 | 3.303 | 0.000 | -3.391 | 0.000 | -0.589 | 0.000 |
| GUESTROOM102 | 0.015 | -0.163 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.885 | 0.000 | 0.004 | 3.052 | 0.000 | -3.231 | 0.000 | -0.562 | 0.000 |
| GUESTROOM103 | 2.520 | -6.470 | 0.000 | 0.000 | 0.000 | 0.000 | 2.456 | 5.203 | 3.572 | 0.966 | 0.000 | 0.012 | 0.000 | 0.000 | -3.135 | 0.000 | -0.612 | -4.512 |
| GUESTROOM104 | 0.561 | -9.854 | 0.000 | 0.000 | 0.000 | 0.000 | 2.437 | 5.202 | 3.572 | 3.238 | 0.000 | 0.012 | 0.000 | 0.000 | -3.009 | 0.000 | -0.625 | -1.534 |
| GUESTROOM105 | 0.040 | -20.990 | 0.000 | 0.000 | 0.000 | 0.000 | 2.408 | 5.202 | 3.572 | 3.094 | 0.000 | 0.012 | 10.604 | 0.000 | -3.315 | 0.000 | -0.627 | 0.000 |
| EMPLOYEELOUNGEFLR1 | 0.000 | -69.028 | 0.000 | 0.000 | 0.000 | 0.000 | 4.336 | 6.669 | 9.572 | 2.724 | 0.000 | 0.007 | 50.610 | 0.000 | -4.228 | 0.000 | -0.662 | 0.000 |
| EXERCISECENTERFLR1 | 0.028 | -22.508 | 0.000 | 0.000 | 0.000 | 0.000 | 10.141 | 6.641 | 8.364 | 3.133 | 0.000 | 0.007 | 0.000 | 0.000 | -3.283 | 0.000 | -0.613 | -1.910 |
| FRONTOFFICEFLR1 | 0.113 | -41.574 | 0.000 | 0.000 | 0.000 | 0.000 | 9.282 | 31.901 | 29.444 | 12.730 | 0.000 | 0.027 | 0.000 | 0.000 | -12.867 | 0.000 | -2.499 | -26.556 |
| FRONTSTAIRSFLR1 | 0.557 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.087 | 0.000 | 0.000 | 0.000 | 0.021 | 0.000 | 0.000 | 0.000 | 0.000 | -4.543 | -0.122 |
| REARSTAIRSFLR2 | 0.124 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.088 | 0.000 | 0.000 | 0.000 | 0.016 | 0.844 | 0.000 | 0.000 | 0.000 | -5.071 | -0.000 |
| CORRIDORFLR2 | 0.078 | -32.955 | 0.000 | 0.000 | 0.000 | 0.000 | 4.236 | 21.287 | 0.000 | 1.592 | 0.000 | 0.049 | 12.517 | 0.000 | -2.472 | 0.000 | -4.332 | 0.000 |
| GUESTROOM201 | 0.065 | -0.130 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.835 | 0.000 | 0.006 | 3.943 | 0.000 | -3.054 | 0.000 | -1.666 | 0.000 |
| GUESTROOM202_205 | 2.857 | -31.047 | 0.000 | 0.000 | 0.000 | 0.000 | 9.724 | 20.810 | 14.288 | 3.586 | 0.000 | 0.049 | 0.000 | 0.000 | -13.041 | 0.000 | -2.434 | -4.793 |
| GUESTROOM206_208 | 1.185 | -26.992 | 0.000 | 0.000 | 0.000 | 0.000 | 7.279 | 16.808 | 11.541 | 2.585 | 0.000 | 0.040 | 0.000 | 0.000 | -9.677 | 0.000 | -1.983 | -0.785 |
| GUESTROOM209_212 | 0.924 | -32.683 | 0.000 | 0.000 | 0.000 | 0.000 | 9.701 | 20.810 | 14.288 | 3.603 | 0.000 | 0.049 | 0.000 | 0.000 | -13.365 | 0.000 | -2.452 | -0.876 |
| GUESTROOM213 | 2.724 | -6.581 | 0.000 | 0.000 | 0.000 | 0.000 | 2.450 | 5.203 | 3.572 | 0.935 | 0.000 | 0.013 | 0.000 | 0.000 | -3.175 | 0.000 | -0.632 | -4.508 |
| GUESTROOM214 | 0.291 | -12.908 | 0.000 | 0.000 | 0.000 | 0.000 | 2.421 | 5.202 | 3.572 | 3.147 | 0.000 | 0.013 | 2.055 | 0.000 | -3.149 | 0.000 | -0.644 | -0.000 |
| GUESTROOM215_218 | 0.000 | -55.309 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 10.695 | 0.000 | 0.007 | 65.579 | 0.000 | -17.777 | 0.000 | -3.194 | 0.000 |
| GUESTROOM219 | 0.028 | -75.201 | 0.000 | 0.000 | 0.000 | 0.000 | 2.363 | 5.202 | 3.572 | 2.702 | 0.000 | 0.013 | 66.166 | 0.000 | -4.207 | 0.000 | -0.639 | 0.000 |
| GUESTROOM220_223 | 0.239 | -44.900 | 0.000 | 0.000 | 0.000 | 0.000 | 9.672 | 20.809 | 14.287 | 12.657 | 0.000 | 0.050 | 2.250 | 0.000 | -12.576 | 0.000 | -2.488 | -0.001 |
| GUESTROOM224 | 0.532 | -11.435 | 0.000 | 0.000 | 0.000 | 0.000 | 2.427 | 5.202 | 3.572 | 3.163 | 0.000 | 0.013 | 0.268 | 0.000 | -3.098 | 0.000 | -0.645 | -0.000 |
| FRONTSTAIRSFLR2 | 0.516 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.087 | 0.000 | 0.000 | 0.000 | 0.006 | 0.168 | 0.000 | 0.000 | 0.000 | -4.777 | -0.000 |
| REARSTAIRSFLR3 | 0.129 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.088 | 0.000 | 0.000 | 0.000 | 0.014 | 1.119 | 0.000 | 0.000 | 0.000 | -5.351 | -0.000 |
| CORRIDORFLR3 | 6.335 | -16.020 | 0.000 | 0.000 | 0.000 | 0.000 | 4.366 | 21.287 | 0.000 | 1.643 | 0.000 | 0.053 | 0.000 | 0.000 | -2.314 | 0.000 | -4.634 | -10.716 |
| GUESTROOM301 | 0.856 | -0.070 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.882 | 0.000 | 0.008 | 2.878 | 0.000 | -2.834 | 0.000 | -1.719 | 0.000 |
| GUESTROOM302_305 | 0.355 | -0.421 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.545 | 0.000 | 0.011 | 10.442 | 0.000 | -11.617 | 0.000 | -2.315 | 0.000 |
| GUESTROOM306_308 | 0.058 | -0.400 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.550 | 0.000 | 0.009 | 8.395 | 0.000 | -8.695 | 0.000 | -1.918 | 0.000 |
| GUESTROOM309_312 | 2.387 | -28.152 | 0.000 | 0.000 | 0.000 | 0.000 | 9.734 | 20.810 | 14.288 | 3.652 | 0.000 | 0.054 | 0.000 | 0.000 | -13.068 | 0.000 | -2.693 | -7.014 |
| GUESTROOM313 | 0.362 | -0.068 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.911 | 0.000 | 0.004 | 2.228 | 0.000 | -2.869 | 0.000 | -0.568 | 0.000 |
| GUESTROOM314 | 1.572 | -9.756 | 0.000 | 0.000 | 0.000 | 0.000 | 2.436 | 5.202 | 3.572 | 3.189 | 0.000 | 0.014 | 0.000 | 0.000 | -3.015 | 0.000 | -0.706 | -2.508 |
| GUESTROOM315_318 | 0.121 | -60.472 | 0.000 | 0.000 | 0.000 | 0.000 | 9.627 | 20.809 | 14.287 | 12.361 | 0.000 | 0.055 | 19.066 | 0.000 | -13.090 | 0.000 | -2.765 | 0.000 |
| GUESTROOM319 | 0.000 | -0.604 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.948 | 0.000 | 0.002 | 1.942 | 0.000 | -3.538 | 0.000 | -0.751 | 0.000 |
| GUESTROOM320_323 | 0.620 | -37.788 | 0.000 | 0.000 | 0.000 | 0.000 | 9.699 | 20.809 | 14.287 | 12.722 | 0.000 | 0.055 | 0.000 | 0.000 | -12.303 | 0.000 | -2.739 | -5.363 |
| GUESTROOM324 | 0.006 | -0.171 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.135 | 0.000 | 0.002 | 0.687 | 0.000 | -3.012 | 0.000 | -0.647 | 0.000 |
| FRONTSTAIRSFLR3 | 0.685 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.087 | 0.000 | 0.000 | 0.000 | 0.005 | 0.305 | 0.000 | 0.000 | 0.000 | -5.082 | -0.000 |
| REARSTAIRSFLR4 | 0.553 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.088 | 0.000 | 0.000 | 0.000 | 0.002 | 0.649 | 0.000 | 0.000 | 0.000 | -5.291 | -0.000 |
| CORRIDORFLR4 | 20.943 | -14.622 | 0.000 | 0.000 | 0.000 | 0.000 | 4.424 | 21.287 | 0.000 | 1.632 | 0.000 | 0.057 | 0.000 | 0.000 | -2.191 | 0.000 | -4.921 | -26.610 |
| GUESTROOM401 | 7.670 | -6.115 | 0.000 | 0.000 | 0.000 | 0.000 | 2.453 | 5.203 | 3.572 | 0.876 | 0.000 | 0.044 | 0.000 | 0.000 | -3.000 | 0.000 | -2.180 | -8.524 |
| GUESTROOM402_405 | 6.138 | -1.234 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.288 | 0.000 | 0.008 | 4.429 | 0.000 | -10.277 | 0.000 | -2.353 | 0.000 |
| GUESTROOM406_408 | 3.858 | -0.930 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 2.368 | 0.000 | 0.007 | 4.242 | 0.000 | -7.622 | 0.000 | -1.923 | 0.000 |
| GUESTROOM409_412 | 8.849 | -24.543 | 0.000 | 0.000 | 0.000 | 0.000 | 9.740 | 20.810 | 14.288 | 3.421 | 0.000 | 0.058 | 0.000 | 0.000 | -12.419 | 0.000 | -2.864 | -17.340 |
| GUESTROOM413 | 2.246 | -0.198 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.858 | 0.000 | 0.002 | 0.287 | 0.000 | -2.609 | 0.000 | -0.585 | -0.000 |
| GUESTROOM414 | 0.655 | -0.626 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.108 | 0.000 | 0.002 | 0.143 | 0.000 | -2.640 | 0.000 | -0.641 | -0.000 |
| GUESTROOM415_418 | 4.051 | -35.994 | 0.000 | 0.000 | 0.000 | 0.000 | 9.698 | 20.809 | 14.287 | 12.376 | 0.000 | 0.058 | 0.000 | 0.000 | -11.755 | 0.000 | -2.918 | -10.612 |
| GUESTROOM419 | 1.400 | -10.121 | 0.000 | 0.000 | 0.000 | 0.000 | 2.427 | 5.202 | 3.572 | 3.094 | 0.000 | 0.015 | 0.000 | 0.000 | -2.996 | 0.000 | -0.752 | -1.841 |
| GUESTROOM420_423 | 4.610 | -32.393 | 0.000 | 0.000 | 0.000 | 0.000 | 9.715 | 20.809 | 14.287 | 12.467 | 0.000 | 0.059 | 0.000 | 0.000 | -11.595 | 0.000 | -2.911 | -15.048 |
| GUESTROOM424 | 3.239 | -8.499 | 0.000 | 0.000 | 0.000 | 0.000 | 2.439 | 5.202 | 3.572 | 3.144 | 0.000 | 0.015 | 0.000 | 0.000 | -2.881 | 0.000 | -0.747 | -5.483 |
| FRONTSTAIRSFLR4 | 1.234 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.087 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -5.234 | -0.088 |
| REARSTORAGEFLR1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.363 | 0.000 | 0.000 | 0.000 | 0.068 | 2.901 | 0.000 | 0.000 | 0.000 | -4.331 | 0.000 |
| LAUNDRYROOMFLR1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 7.472 | 449.967 | 2.136 | 0.000 | 0.000 | 0.002 | 0.000 | -34.589 | 0.000 | -7.025 | -417.961 |
| ELEVATORCOREFLR1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 145.035 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -4.212 | -140.823 |
| FRONTSTORAGEFLR1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.851 | 0.000 | 0.000 | 0.000 | 0.004 | 0.000 | 0.000 | 0.000 | 0.000 | -0.849 | -0.006 |
| REARSTORAGEFLR2 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.363 | 0.000 | 0.000 | 0.000 | 0.035 | 3.005 | 0.000 | 0.000 | 0.000 | -4.403 | 0.000 |
| ELEVATORCOREFLR2 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.793 | 0.000 | 0.000 | 0.000 | -1.793 | 0.000 |
| FRONTSTORAGEFLR2 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.851 | 0.000 | 0.000 | 0.000 | 0.003 | 0.000 | 0.000 | 0.000 | 0.000 | -0.845 | -0.010 |
| REARSTORAGEFLR3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.363 | 0.000 | 0.000 | 0.000 | 0.029 | 3.042 | 0.000 | 0.000 | 0.000 | -4.434 | 0.000 |
| ELEVATORCOREFLR3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.002 | 1.358 | 0.000 | 0.000 | 0.000 | -1.360 | 0.000 |
| FRONTSTORAGEFLR3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.851 | 0.000 | 0.000 | 0.000 | 0.002 | 0.033 | 0.000 | 0.000 | 0.000 | -0.887 | -0.000 |
| REARSTORAGEFLR4 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.363 | 0.000 | 0.000 | 0.000 | 0.008 | 3.007 | 0.000 | 0.000 | 0.000 | -4.378 | 0.000 |
| ELEVATORCOREFLR4 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 1.255 | 0.000 | 0.000 | 0.000 | -1.259 | 0.000 |
| FRONTSTORAGEFLR4 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.851 | 0.000 | 0.000 | 0.000 | 0.001 | 0.064 | 0.000 | 0.000 | 0.000 | -0.917 | -0.000 |
| Total Facility | 108.739 | -982.768 | 0.000 | 0.000 | 0.000 | 0.000 | 205.745 | 512.994 | 874.284 | 178.086 | 0.000 | 2.116 | 413.557 | 0.000 | -336.740 | 0.000 | -214.167 | -761.844 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| REARSTAIRSFLR1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR1 | 16-JUL-16:02 | 0.00 | -12878.87 | 0.00 | 0.00 | 0.00 | 0.00 | 116.01 | 810.01 | 0.00 | 962.48 | 0.00 | 4216.25 | 6774.11 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| FRONTLOUNGEFLR1 | 06-FEB-11:15 | 0.00 | -8550.01 | 0.00 | 0.00 | 0.00 | 0.00 | 895.85 | 2281.66 | 977.33 | 0.00 | 0.00 | 0.00 | 5883.71 | 0.00 | -787.26 | 0.00 | -701.27 | 0.00 |
| RESTROOMFLR1 | 09-AUG-16:13 | 0.00 | -528.89 | 0.00 | 0.00 | 0.00 | 0.00 | 50.27 | 315.92 | 0.00 | 0.00 | 0.00 | 6.29 | 156.41 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| MEETINGROOMFLR1 | 09-AUG-14:01 | 0.00 | -6301.56 | 0.00 | 0.00 | 0.00 | 0.00 | 592.02 | 1123.28 | 114.44 | 803.19 | 0.00 | 17.89 | 3650.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| MECHANICALROOMFLR1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM101 | 06-FEB-15:01 | 0.00 | -443.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 741.67 | 0.00 | -210.44 | 0.00 | -88.03 | 0.00 |
| GUESTROOM102 | 06-FEB-15:01 | 0.00 | -436.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 724.72 | 0.00 | -202.66 | 0.00 | -86.06 | 0.00 |
| GUESTROOM103 | 30-JUN-19:11 | 0.00 | -1865.54 | 0.00 | 0.00 | 0.00 | 0.00 | 70.94 | 400.17 | 240.47 | 93.19 | 0.00 | 0.00 | 1066.04 | 0.00 | -0.00 | 0.00 | -5.29 | 0.00 |
| GUESTROOM104 | 10-SEP-16:11 | 0.00 | -2378.19 | 0.00 | 0.00 | 0.00 | 0.00 | 49.13 | 132.05 | 155.13 | 137.61 | 0.00 | 0.00 | 1912.41 | 0.00 | -0.00 | 0.00 | -8.14 | 0.00 |
| GUESTROOM105 | 06-FEB-09:01 | 0.00 | -3169.84 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 176.06 | 166.77 | 0.00 | 0.00 | 0.00 | 3212.64 | 0.00 | -318.08 | 0.00 | -91.72 | 0.00 |
| EMPLOYEELOUNGEFLR1 | 21-SEP-11:55 | 0.00 | -4493.05 | 0.00 | 0.00 | 0.00 | 0.00 | 902.41 | 421.20 | 672.25 | 1073.88 | 0.00 | 0.57 | 1422.74 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| EXERCISECENTERFLR1 | 21-SEP-15:02 | 0.00 | -1654.31 | 0.00 | 0.00 | 0.00 | 0.00 | 501.40 | 315.90 | 606.20 | 673.79 | 0.00 | 1.55 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -444.53 |
| FRONTOFFICEFLR1 | 24-NOV-15:01 | 0.00 | -7709.59 | 0.00 | 0.00 | 0.00 | 0.00 | 688.47 | 1389.96 | 1663.95 | 2056.74 | 0.00 | 0.00 | 1971.37 | 0.00 | -0.00 | 0.00 | -60.90 | 0.00 |
| FRONTSTAIRSFLR1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR2 | 17-JUL-19:32 | 0.00 | -2704.41 | 0.00 | 0.00 | 0.00 | 0.00 | 96.67 | 675.01 | 0.00 | 16.33 | 0.00 | 0.00 | 1919.42 | 0.00 | -0.00 | 0.00 | -3.01 | 0.00 |
| GUESTROOM201 | 14-AUG-15:01 | 0.00 | -409.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.14 | 0.00 | 6.28 | 220.69 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM202_205 | 03-JUN-17:01 | 0.00 | -7267.44 | 0.00 | 0.00 | 0.00 | 0.00 | 196.87 | 1360.57 | 744.69 | 315.48 | 0.00 | 0.00 | 4696.75 | 0.00 | -0.00 | 0.00 | -46.92 | 0.00 |
| GUESTROOM206_208 | 04-MAR-09:01 | 0.00 | -6177.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.79 | 724.00 | 776.92 | 0.00 | 0.00 | 0.00 | 5144.31 | 0.00 | -506.31 | 0.00 | -71.70 | 0.00 |
| GUESTROOM209_212 | 05-FEB-09:01 | 0.00 | -7649.77 | 0.00 | 0.00 | 0.00 | 0.00 | 146.37 | 896.38 | 961.90 | 0.00 | 0.00 | 0.00 | 6603.85 | 0.00 | -865.51 | 0.00 | -93.21 | 0.00 |
| GUESTROOM213 | 27-MAY-20:01 | 0.00 | -1918.35 | 0.00 | 0.00 | 0.00 | 0.00 | 72.05 | 400.17 | 267.62 | 0.00 | 0.00 | 0.00 | 1282.63 | 0.00 | -94.88 | 0.00 | -9.23 | 0.00 |
| GUESTROOM214 | 12-JAN-16:11 | 0.00 | -2585.53 | 0.00 | 0.00 | 0.00 | 0.00 | 63.76 | 112.04 | 73.69 | 98.81 | 0.00 | 0.00 | 2317.38 | 0.00 | -0.00 | 0.00 | -80.16 | 0.00 |
| GUESTROOM215_218 | 21-SEP-14:50 | 0.00 | -5279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2840.67 | 0.00 | 0.00 | 2440.74 | 0.00 | -0.00 | 0.00 | -2.16 | 0.00 |
| GUESTROOM219 | 21-AUG-18:11 | 0.00 | -8959.71 | 0.00 | 0.00 | 0.00 | 0.00 | 56.64 | 356.12 | 178.40 | 0.00 | 0.00 | 0.00 | 8475.22 | 0.00 | -101.80 | 0.00 | -4.88 | 0.00 |
| GUESTROOM220_223 | 05-FEB-09:01 | 0.00 | -9515.84 | 0.00 | 0.00 | 0.00 | 0.00 | 136.75 | 896.31 | 961.83 | 492.99 | 0.00 | 0.00 | 7123.93 | 0.00 | -0.00 | 0.00 | -95.97 | 0.00 |
| GUESTROOM224 | 12-JAN-16:11 | 0.00 | -2558.16 | 0.00 | 0.00 | 0.00 | 0.00 | 64.03 | 112.04 | 73.69 | 99.73 | 0.00 | 0.00 | 2288.67 | 0.00 | -0.00 | 0.00 | -79.99 | 0.00 |
| FRONTSTAIRSFLR2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR3 | 19-JUL-15:02 | 0.00 | -2032.79 | 0.00 | 0.00 | 0.00 | 0.00 | 193.35 | 675.01 | 0.00 | 358.16 | 0.00 | 110.90 | 695.38 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM301 | 25-DEC-15:01 | 0.00 | -266.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 550.69 | 0.00 | -170.46 | 0.00 | -113.77 | 0.00 |
| GUESTROOM302_305 | 05-FEB-15:01 | 0.00 | -1378.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2100.46 | 0.00 | -533.03 | 0.00 | -188.57 | 0.00 |
| GUESTROOM306_308 | 31-JAN-15:01 | 0.00 | -1242.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1922.64 | 0.00 | -530.25 | 0.00 | -150.11 | 0.00 |
| GUESTROOM309_312 | 03-JUN-17:01 | 0.00 | -6957.73 | 0.00 | 0.00 | 0.00 | 0.00 | 196.87 | 1360.57 | 744.69 | 325.89 | 0.00 | 0.00 | 4381.48 | 0.00 | -0.00 | 0.00 | -51.78 | 0.00 |
| GUESTROOM313 | 05-FEB-15:01 | 0.00 | -303.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.37 | 0.00 | -131.48 | 0.00 | -46.42 | 0.00 |
| GUESTROOM314 | 10-SEP-16:11 | 0.00 | -2365.52 | 0.00 | 0.00 | 0.00 | 0.00 | 48.31 | 132.05 | 155.13 | 131.33 | 0.00 | 0.00 | 1908.09 | 0.00 | -0.00 | 0.00 | -9.38 | 0.00 |
| GUESTROOM315_318 | 05-FEB-09:01 | 0.00 | -10366.04 | 0.00 | 0.00 | 0.00 | 0.00 | 133.77 | 896.31 | 961.83 | 457.52 | 0.00 | 0.00 | 8023.94 | 0.00 | -0.00 | 0.00 | -107.33 | 0.00 |
| GUESTROOM319 | 06-FEB-15:01 | 0.00 | -442.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 371.43 | 0.00 | 0.00 | 179.47 | 0.00 | -0.00 | 0.00 | -108.73 | 0.00 |
| GUESTROOM320_323 | 12-JAN-16:11 | 0.00 | -9080.76 | 0.00 | 0.00 | 0.00 | 0.00 | 240.78 | 448.16 | 294.75 | 365.78 | 0.00 | 0.00 | 8099.47 | 0.00 | -0.00 | 0.00 | -368.17 | 0.00 |
| GUESTROOM324 | 06-FEB-15:01 | 0.00 | -419.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.03 | 0.00 | 0.00 | 108.39 | 0.00 | -0.00 | 0.00 | -98.03 | 0.00 |
| FRONTSTAIRSFLR3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR4 | 09-AUG-15:02 | 0.00 | -3438.22 | 0.00 | 0.00 | 0.00 | 0.00 | 193.34 | 675.01 | 0.00 | 382.13 | 0.00 | 55.20 | 2132.54 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM401 | 01-AUG-16:11 | 0.00 | -2522.45 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 112.05 | 186.17 | 109.12 | 0.00 | 0.00 | 2089.75 | 0.00 | -0.00 | 0.00 | -15.14 | 0.00 |
| GUESTROOM402_405 | 21-JUL-13:40 | 0.00 | -1338.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 985.67 | 0.00 | 29.10 | 324.00 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM406_408 | 21-JUL-13:40 | 0.00 | -990.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 718.95 | 0.00 | 23.50 | 248.20 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM409_412 | 20-MAY-17:41 | 0.00 | -9354.21 | 0.00 | 0.00 | 0.00 | 0.00 | 160.90 | 1360.57 | 744.69 | 48.16 | 0.00 | 0.00 | 7119.71 | 0.00 | -0.00 | 0.00 | -79.83 | 0.00 |
| GUESTROOM413 | 21-JUL-13:50 | 0.00 | -326.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.97 | 0.00 | 7.33 | 70.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM414 | 09-AUG-13:40 | 0.00 | -559.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 671.16 | 0.00 | 3.99 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -115.93 |
| GUESTROOM415_418 | 05-JUN-16:21 | 0.00 | -11132.52 | 0.00 | 0.00 | 0.00 | 0.00 | 172.24 | 448.16 | 744.64 | 132.31 | 0.00 | 0.00 | 9716.30 | 0.00 | -0.00 | 0.00 | -81.13 | 0.00 |
| GUESTROOM419 | 05-JUN-16:21 | 0.00 | -2930.50 | 0.00 | 0.00 | 0.00 | 0.00 | 44.11 | 112.04 | 186.16 | 34.81 | 0.00 | 0.00 | 2573.05 | 0.00 | -0.00 | 0.00 | -19.67 | 0.00 |
| GUESTROOM420_423 | 05-JUN-16:21 | 0.00 | -10926.07 | 0.00 | 0.00 | 0.00 | 0.00 | 177.16 | 448.16 | 744.64 | 146.73 | 0.00 | 0.00 | 9488.24 | 0.00 | -0.00 | 0.00 | -78.86 | 0.00 |
| GUESTROOM424 | 30-OCT-16:11 | 0.00 | -2934.02 | 0.00 | 0.00 | 0.00 | 0.00 | 49.38 | 112.04 | 186.16 | 208.32 | 0.00 | 0.00 | 2384.52 | 0.00 | -0.00 | 0.00 | -6.40 | 0.00 |
| FRONTSTAIRSFLR4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LAUNDRYROOMFLR1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 30-JUN-18:01 | 0.00 | -140470.40 | 0.00 | 0.00 | 0.00 | 0.00 | 5477.62 | 24642.77 | 16951.20 | 9851.36 | 0.00 | 0.00 | 86154.23 | 0.00 | -996.45 | 0.00 | -1610.33 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| REARSTAIRSFLR1 | 05-FEB-14:35 | 6.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 135.05 | 0.00 | -0.00 | 0.00 | -271.35 | 0.00 |
| CORRIDORFLR1 | 06-JAN-07:02 | 29496.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.59 | 810.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -876.57 | 0.00 | -26572.76 | -3312.64 |
| FRONTLOUNGEFLR1 | 31-JAN-20:12 | 11451.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 895.85 | 456.33 | 977.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1309.59 | 0.00 | -389.02 | -12082.47 |
| RESTROOMFLR1 | 27-DEC-10:35 | 47.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.78 | 315.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -60.28 | -329.97 |
| MEETINGROOMFLR1 | 12-JAN-11:23 | 5865.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1123.28 | 114.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -681.48 | 0.00 | -243.62 | -6178.41 |
| MECHANICALROOMFLR1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM101 | 21-JUL-14:01 | 124.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.20 | 0.00 | 5.96 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -386.02 |
| GUESTROOM102 | 21-JUL-14:01 | 132.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.13 | 0.00 | 6.72 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -401.59 |
| GUESTROOM103 | 22-FEB-16:12 | 1854.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.78 | 112.05 | 73.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -20.15 | 0.00 | -26.49 | -2068.73 |
| GUESTROOM104 | 22-FEB-09:01 | 2037.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.47 | 176.06 | 166.77 | 179.16 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -63.40 | -2523.04 |
| GUESTROOM105 | 09-JAN-09:03 | 1737.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.68 | 176.06 | 166.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -218.95 | 0.00 | -29.94 | -1853.85 |
| EMPLOYEELOUNGEFLR1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| EXERCISECENTERFLR1 | 12-DEC-05:03 | 2071.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -327.87 | 0.00 | -53.19 | -1690.04 |
| FRONTOFFICEFLR1 | 26-FEB-15:01 | 6023.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.55 | 1389.96 | 1048.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -192.69 | 0.00 | -146.91 | -8556.32 |
| FRONTSTAIRSFLR1 | 07-FEB-10:53 | 283.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 306.47 | 0.00 | -0.00 | 0.00 | -719.19 | 0.00 |
| REARSTAIRSFLR2 | 07-FEB-10:45 | 85.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 512.09 | 0.00 | -0.00 | 0.00 | -727.14 | 0.00 |
| CORRIDORFLR2 | 07-FEB-17:44 | 1328.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 228.19 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -195.81 | 0.00 | -496.91 | -1539.42 |
| GUESTROOM201 | 21-FEB-15:35 | 377.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.23 | 0.00 | -177.76 | 0.00 | -251.58 | 0.00 |
| GUESTROOM202_205 | 13-JAN-16:12 | 6503.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.85 | 448.19 | 294.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -569.99 | 0.00 | -104.88 | -6862.39 |
| GUESTROOM206_208 | 10-JAN-16:12 | 5022.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.13 | 362.00 | 238.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -549.31 | 0.00 | -90.49 | -5198.46 |
| GUESTROOM209_212 | 10-JAN-16:12 | 6128.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.99 | 448.19 | 294.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -761.96 | 0.00 | -112.83 | -6282.35 |
| GUESTROOM213 | 22-FEB-16:12 | 1865.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.71 | 112.05 | 73.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18.23 | 0.00 | -27.00 | -2081.38 |
| GUESTROOM214 | 29-DEC-16:11 | 2086.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.78 | 112.04 | 73.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -200.31 | 0.00 | -48.58 | -2095.50 |
| GUESTROOM215_218 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM219 | 07-FEB-09:02 | 1560.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.29 | 176.06 | 166.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18.02 | 0.00 | -94.76 | -1812.81 |
| GUESTROOM220_223 | 26-FEB-09:03 | 5710.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.02 | 896.31 | 961.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -250.63 | 0.00 | -175.80 | -7279.32 |
| GUESTROOM224 | 22-FEB-09:01 | 2137.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.36 | 176.06 | 166.77 | 173.46 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -65.90 | -2613.79 |
| FRONTSTAIRSFLR2 | 07-FEB-10:35 | 341.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 242.93 | 0.00 | -0.00 | 0.00 | -713.68 | 0.00 |
| REARSTAIRSFLR3 | 06-FEB-18:55 | 86.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 566.07 | 0.00 | -0.00 | 0.00 | -782.03 | 0.00 |
| CORRIDORFLR3 | 07-FEB-05:00 | 2120.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.04 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -265.82 | 0.00 | -608.88 | -1977.37 |
| GUESTROOM301 | 13-JAN-16:01 | 770.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -99.27 | 0.00 | -65.00 | -605.79 |
| GUESTROOM302_305 | 07-FEB-07:51 | 699.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748.74 | 0.00 | -1099.70 | 0.00 | -348.67 | 0.00 |
| GUESTROOM306_308 | 31-JAN-15:03 | 609.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.43 | 0.00 | -530.25 | 0.00 | -148.87 | 0.00 |
| GUESTROOM309_312 | 23-DEC-16:12 | 6188.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.69 | 528.22 | 325.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -591.89 | 0.00 | -181.78 | -6427.28 |
| GUESTROOM313 | 05-FEB-15:02 | 478.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -131.48 | 0.00 | -46.60 | -300.83 |
| GUESTROOM314 | 01-FEB-09:01 | 2059.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.45 | 176.06 | 166.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -97.52 | 0.00 | -10.19 | -2321.32 |
| GUESTROOM315_318 | 29-JAN-09:03 | 5853.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.61 | 896.31 | 961.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -914.48 | 0.00 | -156.35 | -6776.55 |
| GUESTROOM319 | 14-MAR-14:01 | 45.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 498.71 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -3.93 | -540.34 |
| GUESTROOM320_323 | 29-DEC-16:11 | 6917.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.13 | 448.16 | 294.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -794.31 | 0.00 | -214.52 | -6938.05 |
| GUESTROOM324 | 15-JUL-14:01 | 119.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 417.45 | 0.00 | 11.96 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -548.72 |
| FRONTSTAIRSFLR3 | 06-FEB-18:55 | 427.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 228.59 | 0.00 | -0.00 | 0.00 | -786.08 | 0.00 |
| REARSTAIRSFLR4 | 07-FEB-03:00 | 309.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 188.06 | 0.00 | -0.00 | 0.00 | -627.18 | 0.00 |
| CORRIDORFLR4 | 07-FEB-05:00 | 3989.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.04 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -260.33 | 0.00 | -652.64 | -3808.70 |
| GUESTROOM401 | 01-DEC-09:01 | 2209.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.66 | 176.07 | 166.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -26.53 | 0.00 | -45.96 | -2506.98 |
| GUESTROOM402_405 | 07-FEB-07:27 | 2131.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1172.60 | 0.00 | -324.85 | -633.86 |
| GUESTROOM406_408 | 07-FEB-07:27 | 1590.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -858.46 | 0.00 | -262.38 | -469.99 |
| GUESTROOM409_412 | 20-DEC-16:12 | 7833.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 303.65 | 448.19 | 294.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -527.70 | 0.00 | -150.94 | -8201.22 |
| GUESTROOM413 | 07-FEB-07:16 | 831.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -305.71 | 0.00 | -77.02 | -448.72 |
| GUESTROOM414 | 07-FEB-07:27 | 564.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -320.29 | 0.00 | -81.21 | -163.45 |
| GUESTROOM415_418 | 20-DEC-16:12 | 9142.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.77 | 448.16 | 294.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -569.26 | 0.00 | -161.70 | -9445.42 |
| GUESTROOM419 | 22-FEB-09:01 | 2458.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 | 176.06 | 166.77 | 171.26 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -78.13 | -2920.51 |
| GUESTROOM420_423 | 20-DEC-16:12 | 9110.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.19 | 448.16 | 294.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -550.48 | 0.00 | -157.68 | -9441.60 |
| GUESTROOM424 | 11-JAN-09:01 | 2583.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.81 | 176.06 | 166.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -102.66 | 0.00 | -51.63 | -2798.37 |
| FRONTSTAIRSFLR4 | 06-FEB-09:53 | 687.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 51.89 | 0.00 | -0.00 | 0.00 | -868.72 | 0.00 |
| REARSTORAGEFLR1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LAUNDRYROOMFLR1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR1 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR2 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR3 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 06-FEB-19:01 | 72326.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7525.42 | 24642.77 | 16951.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -36150.52 | 0.00 | -28630.02 | -56664.99 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| None |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| None |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| None |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| None |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| None |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| None |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| None |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| None |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
| Total gross floor area [m2] | 4013.58 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| REARSTAIRSFLR1 | 20.07 | 20.07 | 0.00 | 0.00 |
| CORRIDORFLR1 | 150.51 | 150.51 | 0.00 | 168.00 |
| FRONTLOUNGEFLR1 | 163.06 | 163.06 | 0.00 | 168.00 |
| RESTROOMFLR1 | 32.61 | 32.61 | 0.00 | 168.00 |
| MEETINGROOMFLR1 | 80.27 | 80.27 | 0.00 | 39.79 |
| MECHANICALROOMFLR1 | 32.61 | 32.61 | 0.00 | 0.00 |
| GUESTROOM101 | 32.61 | 32.61 | 0.00 | 0.00 |
| GUESTROOM102 | 32.61 | 32.61 | 0.00 | 0.00 |
| GUESTROOM103 | 32.61 | 32.61 | 0.00 | 168.00 |
| GUESTROOM104 | 32.61 | 32.61 | 0.00 | 168.00 |
| GUESTROOM105 | 32.61 | 32.61 | 0.00 | 168.00 |
| EMPLOYEELOUNGEFLR1 | 32.61 | 32.61 | 0.00 | 105.00 |
| EXERCISECENTERFLR1 | 32.61 | 32.61 | 0.00 | 112.00 |
| FRONTOFFICEFLR1 | 130.44 | 130.44 | 0.00 | 154.00 |
| FRONTSTAIRSFLR1 | 20.07 | 20.07 | 0.00 | 0.00 |
| REARSTAIRSFLR2 | 20.07 | 20.07 | 0.00 | 0.00 |
| CORRIDORFLR2 | 125.42 | 125.42 | 0.00 | 168.00 |
| GUESTROOM201 | 32.61 | 32.61 | 0.00 | 0.00 |
| GUESTROOM202_205 | 130.45 | 130.45 | 0.00 | 168.00 |
| GUESTROOM206_208 | 105.36 | 105.36 | 0.00 | 168.00 |
| GUESTROOM209_212 | 130.45 | 130.45 | 0.00 | 168.00 |
| GUESTROOM213 | 32.61 | 32.61 | 0.00 | 168.00 |
| GUESTROOM214 | 32.61 | 32.61 | 0.00 | 168.00 |
| GUESTROOM215_218 | 130.44 | 130.44 | 0.00 | 0.00 |
| GUESTROOM219 | 32.61 | 32.61 | 0.00 | 168.00 |
| GUESTROOM220_223 | 130.44 | 130.44 | 0.00 | 168.00 |
| GUESTROOM224 | 32.61 | 32.61 | 0.00 | 168.00 |
| FRONTSTAIRSFLR2 | 20.07 | 20.07 | 0.00 | 0.00 |
| REARSTAIRSFLR3 | 20.07 | 20.07 | 0.00 | 0.00 |
| CORRIDORFLR3 | 125.42 | 125.42 | 0.00 | 168.00 |
| GUESTROOM301 | 32.61 | 32.61 | 0.00 | 0.00 |
| GUESTROOM302_305 | 130.45 | 130.45 | 0.00 | 0.00 |
| GUESTROOM306_308 | 105.36 | 105.36 | 0.00 | 0.00 |
| GUESTROOM309_312 | 130.45 | 130.45 | 0.00 | 168.00 |
| GUESTROOM313 | 32.61 | 32.61 | 0.00 | 0.00 |
| GUESTROOM314 | 32.61 | 32.61 | 0.00 | 168.00 |
| GUESTROOM315_318 | 130.44 | 130.44 | 0.00 | 168.00 |
| GUESTROOM319 | 32.61 | 32.61 | 0.00 | 0.00 |
| GUESTROOM320_323 | 130.44 | 130.44 | 0.00 | 168.00 |
| GUESTROOM324 | 32.61 | 32.61 | 0.00 | 0.00 |
| FRONTSTAIRSFLR3 | 20.07 | 20.07 | 0.00 | 0.00 |
| REARSTAIRSFLR4 | 20.07 | 20.07 | 0.00 | 0.00 |
| CORRIDORFLR4 | 125.42 | 125.42 | 0.00 | 168.00 |
| GUESTROOM401 | 32.61 | 32.61 | 0.00 | 168.00 |
| GUESTROOM402_405 | 130.45 | 130.45 | 0.00 | 0.00 |
| GUESTROOM406_408 | 105.36 | 105.36 | 0.00 | 0.00 |
| GUESTROOM409_412 | 130.45 | 130.45 | 0.00 | 168.00 |
| GUESTROOM413 | 32.61 | 32.61 | 0.00 | 0.00 |
| GUESTROOM414 | 32.61 | 32.61 | 0.00 | 0.00 |
| GUESTROOM415_418 | 130.44 | 130.44 | 0.00 | 168.00 |
| GUESTROOM419 | 32.61 | 32.61 | 0.00 | 168.00 |
| GUESTROOM420_423 | 130.44 | 130.44 | 0.00 | 168.00 |
| GUESTROOM424 | 32.61 | 32.61 | 0.00 | 168.00 |
| FRONTSTAIRSFLR4 | 20.07 | 20.07 | 0.00 | 0.00 |
| REARSTORAGEFLR1 | 20.07 | 0.00 | 20.07 | 0.00 |
| LAUNDRYROOMFLR1 | 97.83 | 0.00 | 97.83 | 56.00 |
| ELEVATORCOREFLR1 | 15.05 | 0.00 | 15.05 | 0.00 |
| FRONTSTORAGEFLR1 | 12.54 | 0.00 | 12.54 | 0.00 |
| REARSTORAGEFLR2 | 20.07 | 0.00 | 20.07 | 0.00 |
| ELEVATORCOREFLR2 | 15.05 | 0.00 | 15.05 | 0.00 |
| FRONTSTORAGEFLR2 | 12.54 | 0.00 | 12.54 | 0.00 |
| REARSTORAGEFLR3 | 20.07 | 0.00 | 20.07 | 0.00 |
| ELEVATORCOREFLR3 | 15.05 | 0.00 | 15.05 | 0.00 |
| FRONTSTORAGEFLR3 | 12.54 | 0.00 | 12.54 | 0.00 |
| REARSTORAGEFLR4 | 20.07 | 0.00 | 20.07 | 0.00 |
| ELEVATORCOREFLR4 | 15.05 | 0.00 | 15.05 | 0.00 |
| FRONTSTORAGEFLR4 | 12.54 | 0.00 | 12.54 | 0.00 |
| Totals | 4013.58 | 3725.09 | 288.49 |
| Data | |
| Number of hours heating loads not met | 0.33 |
| Number of hours cooling loads not met | 239.67 |
| Number of hours not met | 240.00 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 0.60 | 2634.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heating -- Boiler | 0.00 | 0.00 | 466.47 | 140767.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 248.34 | 43909.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 512.99 | 26853.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 107.00 | 6812.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLift | 134.82 | 7309.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ElevatorLightsFan | 10.22 | 324.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- MiscPlug | 279.28 | 24347.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- Laundry | 28.48 | 2709.07 | 421.49 | 40096.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 235.89 | 8924.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- General | 1.77 | 441.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 0.00 | 0.00 | 820.86 | 78879.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 452.79 | 1558.78 |
| Natural Gas | 421.49 | 1709.42 |
| Additional | 0.00 | 0.00 |
| Total | 874.28 | 3268.19 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 127.81 |
| Space Heating | 0.00 |
| Space Cooling | 61.87 |
| Fans (All) | 58.77 |
| Service Water Heating | 0.00 |
| Receptacle Equipment | 112.82 |
| Miscellaneous (All) | 388.38 |
| Subtotal | 388.38 |
| Natural Gas [MJ/m2] | |
| Space Heating | 116.37 |
| Service Water Heating | 204.52 |
| Miscellaneous (All) | 425.91 |
| Subtotal | 425.91 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 15.70 |
| Space Heating | 14.29 |
| Space Cooling | 7.60 |
| Fans (All) | 7.22 |
| Service Water Heating | 25.12 |
| Receptacle Equipment | 26.75 |
| Miscellaneous | 3.33 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| ELEVATOR_RUNNING_SCH | 146. | 4015. |
| ELEVATOR_STANDBY_SCH | 8201. | 8760. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| OFFICE_FAN_SCH | 8030. | 8030. |
| GUESTROOM_OCC_SCH | 5515. | 8760. |
| LOBBY_OCC_SCH | 2304. | 8760. |
| OFFICE_OCC_SCH | 3954. | 8760. |
| OFFICE_OCC_W_SB_SCH | 3459. | 8030. |
| EMPLOYEELOUNGE_OCC_SCH | 948. | 5475. |
| MEETINGROOM_OCC_SCH | 1168. | 4745. |
| MEETINGROOM_OCC_W_SB_SCH | 620. | 2085. |
| LAUNDRYROOM_OCC_SCH | 427. | 2920. |
| EXERCISECENTER_OCC_SCH | 5292. | 5840. |
| ALWAYSOFF_SCH | 0. | 0. |
| ALWAYSON_SCH | 8760. | 8760. |
| LTG_SCH_OFFICE | 5738. | 8760. |
| LTG_SCH_LOBBY | 4398. | 6205. |
| LTG_SCH_MECHANICAL | 2190. | 8760. |
| LTG_SCH_STORAGE | 2190. | 8760. |
| LTG_SCH_MEETING | 4398. | 6205. |
| LTG_SCH_GUESTROOM | 3599. | 8760. |
| LTG_SCH_EXERCISE | 5840. | 6205. |
| LTG_SCH_STAIR | 8760. | 8760. |
| LTG_SCH_ELEVATOR | 0. | 0. |
| LTG_SCH_LAUNDRY | 3285. | 3285. |
| LTG_SCH_LOUNGE | 4398. | 6205. |
| LTG_SCH_CORRIDOR | 8760. | 8760. |
| LTG_SCH_RESTROOM | 8760. | 8760. |
| EXTERIOR_LTG_SCH | 4380. | 4380. |
| GUESTROOM_EQP_SCH_BASE | 3009. | 8760. |
| GUESTROOM_EQP_SCH_ADVA | 2558. | 8760. |
| LOBBY_EQP_SCH | 3292. | 8760. |
| OFF_EQUIP_SCH | 4574. | 8760. |
| EMPLOYEELOUNGE_EQP_SCH | 3791. | 8760. |
| LAUNDRYROOM_EQP_ELEC_SCH | 2920. | 2920. |
| LAUNDRYROOM_EQP_GAS_SCH | 2920. | 2920. |
| MEETINGROOM_EQP_SCH | 1185. | 4745. |
| EXERCISECENTER_EQP_SCH | 3832. | 5840. |
| OCC_GUESTROOM_VENT_CTRL_30MIN | 6570. | 6570. |
| OCC_GUESTROOM_VENT_CTRL_20MIN | 6327. | 6327. |
| MEETINGROOM_FAN_SCH | 1720. | 1720. |
| GUESTROOM_INFIL_SCH | 2190. | 8760. |
| COMMONAREA_INFIL_SCH | 2190. | 8760. |
| INFIL_DOOR_OPENING_SCH | 1399. | 5840. |
| GUESTROOM_SHW_SCH | 2899. | 8760. |
| LAUNDRYROOM_SHW_SCH | 2920. | 2920. |
| SHW LATENT FRACT SCHED | 438. | 8760. |
| SHW SENSIBLE FRACT SCHED | 1752. | 8760. |
| ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
| ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
| MINOA_MOTORIZEDDAMPER_SCHED | 8760. | 8760. |
| VAC_GUESTROOM_VENT_CTRL | 365. | 365. |
| SLIDING_DOORS_VENTILATION_AVAILABILITY_SCH | 3285. | 3285. |
| SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| SEMIHEATED_HTGSP_SCH | SEMIHEATED_HTGSP | January | 7.20 | 365 | 7.20 | 365 |
| VACGUESTROOM_HTGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 15.56 | 365 | 15.56 | 365 |
| VACGUESTROOM_CLGSP_SCH | VACGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 26.67 | 365 | 26.67 | 365 |
| OBCRESET_S_OCCGUESTROOM_HTGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
| OBCRESET_S_OCCGUESTROOM_CLGSP_SCH_20MIN | S OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
| OBCRESET_N_OCCGUESTROOM_HTGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
| OBCRESET_N_OCCGUESTROOM_CLGSP_SCH_20MIN | N OCCGUESTROOM THERMOSTAT DUAL SP CONTROL | July | 23.33 | 365 | 21.11 | 365 |
| COMMONAREA_HTGSP_SCH | COMMONAREA THERMOSTAT DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
| COMMONAREA_CLGSP_SCH | COMMONAREA THERMOSTAT DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
| OFFICE_HTGSP_SCH | FRONTOFFICEFLR1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
| OFFICE_CLGSP_SCH | FRONTOFFICEFLR1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
| MEETINGROOM_HTGSP_SCH | MEETINGROOMFLR1 DUAL SP CONTROL | January | 20.55 | 365 | 21.11 | 365 |
| MEETINGROOM_CLGSP_SCH | MEETINGROOMFLR1 DUAL SP CONTROL | July | 24.45 | 365 | 23.89 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| REARSTAIRSFLR1 | 8688.33 | 71.67 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTLOUNGEFLR1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| RESTROOMFLR1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MEETINGROOMFLR1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MECHANICALROOMFLR1 | 5762.67 | 2997.33 | 0.00 | 0.00 | 0.00 |
| GUESTROOM101 | 8741.67 | 18.33 | 0.00 | 0.00 | 0.00 |
| GUESTROOM102 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
| GUESTROOM103 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM104 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM105 | 8750.83 | 9.17 | 0.00 | 0.00 | 0.00 |
| EMPLOYEELOUNGEFLR1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| EXERCISECENTERFLR1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTOFFICEFLR1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR1 | 8474.17 | 285.83 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR2 | 8361.67 | 398.33 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR2 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM201 | 8562.33 | 197.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM202_205 | 8723.33 | 36.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM206_208 | 8734.50 | 25.50 | 0.00 | 0.00 | 0.00 |
| GUESTROOM209_212 | 8742.83 | 17.17 | 0.00 | 0.00 | 0.00 |
| GUESTROOM213 | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM214 | 8748.17 | 11.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM215_218 | 8745.50 | 14.50 | 0.00 | 0.00 | 0.00 |
| GUESTROOM219 | 8251.00 | 509.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM220_223 | 8756.50 | 3.50 | 0.00 | 0.00 | 0.00 |
| GUESTROOM224 | 8754.17 | 5.83 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR2 | 7942.67 | 817.33 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR3 | 8228.33 | 531.67 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM301 | 8627.33 | 132.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM302_305 | 8647.17 | 112.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM306_308 | 8697.17 | 62.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM309_312 | 8748.00 | 12.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM313 | 8725.33 | 34.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM314 | 8752.33 | 7.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM315_318 | 8698.17 | 61.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM319 | 8131.33 | 628.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM320_323 | 8758.33 | 1.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM324 | 8637.33 | 122.67 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR3 | 7727.50 | 1025.17 | 7.33 | 0.00 | 0.00 |
| REARSTAIRSFLR4 | 7871.50 | 876.67 | 11.83 | 0.00 | 0.00 |
| CORRIDORFLR4 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM401 | 8704.00 | 56.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM402_405 | 8493.00 | 267.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM406_408 | 8486.50 | 273.50 | 0.00 | 0.00 | 0.00 |
| GUESTROOM409_412 | 8661.33 | 98.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM413 | 8450.33 | 309.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM414 | 8486.83 | 273.17 | 0.00 | 0.00 | 0.00 |
| GUESTROOM415_418 | 8726.17 | 33.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM419 | 8729.17 | 30.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM420_423 | 8740.33 | 19.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM424 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR4 | 7688.33 | 1036.50 | 35.17 | 0.00 | 0.00 |
| REARSTORAGEFLR1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 8760.00 |
| ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 4848.00 | 3912.00 |
| FRONTSTORAGEFLR1 | 8561.50 | 198.50 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR2 | 8677.17 | 82.83 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR2 | 1000.50 | 6296.33 | 1463.17 | 0.00 | 0.00 |
| FRONTSTORAGEFLR2 | 8443.00 | 317.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR3 | 8542.17 | 217.83 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR3 | 7393.67 | 1366.33 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR3 | 8164.00 | 596.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR4 | 8217.50 | 542.50 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR4 | 8468.50 | 291.50 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR4 | 7969.00 | 791.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 6296.33 | 1463.17 | 4848.00 | 8760.00 |
| Average | 8145.16 | 330.70 | 22.65 | 72.36 | 189.13 |
| Sum | 545725.50 | 22157.00 | 1517.50 | 4848.00 | 12672.00 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR1 | 12835.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTLOUNGEFLR1 | 117890.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| RESTROOMFLR1 | 1345.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MEETINGROOMFLR1 | 25650.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM103 | 4150.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM104 | 4150.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM105 | 4147.83 | 2.17 | 0.00 | 0.00 | 0.00 |
| EMPLOYEELOUNGEFLR1 | 12880.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| EXERCISECENTERFLR1 | 36500.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTOFFICEFLR1 | 34205.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR2 | 10990.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM202_205 | 30101.33 | 118.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM206_208 | 19879.67 | 60.33 | 0.00 | 0.00 | 0.00 |
| GUESTROOM209_212 | 30158.33 | 61.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM213 | 4148.50 | 1.50 | 0.00 | 0.00 | 0.00 |
| GUESTROOM214 | 4144.33 | 5.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM219 | 3965.83 | 184.17 | 0.00 | 0.00 | 0.00 |
| GUESTROOM220_223 | 30208.17 | 11.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM224 | 4147.33 | 2.67 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR3 | 10990.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM309_312 | 30175.83 | 44.17 | 0.00 | 0.00 | 0.00 |
| GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM314 | 4145.33 | 4.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM315_318 | 30008.17 | 211.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM320_323 | 30212.83 | 7.17 | 0.00 | 0.00 | 0.00 |
| GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR4 | 10990.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM401 | 4137.17 | 12.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM409_412 | 29919.33 | 300.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM415_418 | 30125.00 | 95.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM419 | 4145.17 | 4.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM420_423 | 30170.17 | 49.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM424 | 4145.33 | 4.67 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.00 |
| ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 117890.00 | 300.67 | 0.00 | 0.00 | 1825.00 |
| Average | 9114.34 | 17.68 | 0.00 | 0.00 | 27.24 |
| Sum | 610660.67 | 1184.33 | 0.00 | 0.00 | 1825.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| REARSTAIRSFLR1 | 7832.00 | 928.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR1 | 8753.00 | 7.00 | 0.00 | 0.00 | 0.00 |
| FRONTLOUNGEFLR1 | 8581.17 | 178.83 | 0.00 | 0.00 | 0.00 |
| RESTROOMFLR1 | 8662.17 | 97.83 | 0.00 | 0.00 | 0.00 |
| MEETINGROOMFLR1 | 8605.00 | 155.00 | 0.00 | 0.00 | 0.00 |
| MECHANICALROOMFLR1 | 6104.33 | 2655.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM101 | 7520.33 | 1239.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM102 | 7798.83 | 961.17 | 0.00 | 0.00 | 0.00 |
| GUESTROOM103 | 8445.50 | 314.50 | 0.00 | 0.00 | 0.00 |
| GUESTROOM104 | 8517.33 | 242.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM105 | 8486.17 | 273.83 | 0.00 | 0.00 | 0.00 |
| EMPLOYEELOUNGEFLR1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| EXERCISECENTERFLR1 | 8653.00 | 107.00 | 0.00 | 0.00 | 0.00 |
| FRONTOFFICEFLR1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR1 | 7634.00 | 1126.00 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR2 | 7519.33 | 1240.67 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR2 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM201 | 7531.50 | 1228.50 | 0.00 | 0.00 | 0.00 |
| GUESTROOM202_205 | 8264.00 | 496.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM206_208 | 8296.67 | 463.33 | 0.00 | 0.00 | 0.00 |
| GUESTROOM209_212 | 8259.17 | 500.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM213 | 8348.67 | 411.33 | 0.00 | 0.00 | 0.00 |
| GUESTROOM214 | 8419.83 | 340.17 | 0.00 | 0.00 | 0.00 |
| GUESTROOM215_218 | 8691.67 | 68.33 | 0.00 | 0.00 | 0.00 |
| GUESTROOM219 | 8278.67 | 481.33 | 0.00 | 0.00 | 0.00 |
| GUESTROOM220_223 | 8393.33 | 366.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM224 | 8430.33 | 329.67 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR2 | 7311.33 | 1448.67 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR3 | 7453.00 | 1307.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM301 | 7601.83 | 1158.17 | 0.00 | 0.00 | 0.00 |
| GUESTROOM302_305 | 7587.33 | 1172.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM306_308 | 7628.00 | 1132.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM309_312 | 8259.83 | 500.17 | 0.00 | 0.00 | 0.00 |
| GUESTROOM313 | 7720.67 | 1039.33 | 0.00 | 0.00 | 0.00 |
| GUESTROOM314 | 8424.33 | 335.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM315_318 | 8368.83 | 391.17 | 0.00 | 0.00 | 0.00 |
| GUESTROOM319 | 7503.33 | 1256.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM320_323 | 8397.83 | 362.17 | 0.00 | 0.00 | 0.00 |
| GUESTROOM324 | 7581.17 | 1178.83 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR3 | 7224.33 | 1535.67 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR4 | 7339.17 | 1420.83 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR4 | 8681.67 | 78.33 | 0.00 | 0.00 | 0.00 |
| GUESTROOM401 | 8348.67 | 411.33 | 0.00 | 0.00 | 0.00 |
| GUESTROOM402_405 | 7945.17 | 814.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM406_408 | 7921.67 | 838.33 | 0.00 | 0.00 | 0.00 |
| GUESTROOM409_412 | 8248.00 | 512.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM413 | 7860.50 | 899.50 | 0.00 | 0.00 | 0.00 |
| GUESTROOM414 | 7910.33 | 849.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM415_418 | 8395.50 | 364.50 | 0.00 | 0.00 | 0.00 |
| GUESTROOM419 | 8423.33 | 336.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM420_423 | 8405.17 | 354.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM424 | 8434.83 | 325.17 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR4 | 7220.17 | 1539.83 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR1 | 8043.83 | 716.17 | 0.00 | 0.00 | 0.00 |
| LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 8760.00 |
| ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 36.50 | 8723.50 |
| FRONTSTORAGEFLR1 | 7467.83 | 1292.17 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR2 | 7822.83 | 937.17 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR2 | 3650.33 | 4835.17 | 274.50 | 0.00 | 0.00 |
| FRONTSTORAGEFLR2 | 7428.67 | 1331.33 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR3 | 7728.83 | 1031.17 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR3 | 6990.83 | 1769.17 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR3 | 7335.50 | 1424.50 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR4 | 7626.67 | 1133.33 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR4 | 7557.33 | 1202.67 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR4 | 7358.00 | 1402.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 4835.17 | 274.50 | 36.50 | 8760.00 |
| Average | 7705.56 | 788.85 | 4.10 | 0.54 | 260.95 |
| Sum | 516272.67 | 52852.83 | 274.50 | 36.50 | 17483.50 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| REARSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR1 | 12805.33 | 29.67 | 0.00 | 0.00 | 0.00 |
| FRONTLOUNGEFLR1 | 116515.67 | 1374.33 | 0.00 | 0.00 | 0.00 |
| RESTROOMFLR1 | 1329.33 | 15.67 | 0.00 | 0.00 | 0.00 |
| MEETINGROOMFLR1 | 25216.17 | 433.83 | 0.00 | 0.00 | 0.00 |
| MECHANICALROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM101 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM102 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM103 | 4024.33 | 125.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM104 | 4048.67 | 101.33 | 0.00 | 0.00 | 0.00 |
| GUESTROOM105 | 4042.00 | 108.00 | 0.00 | 0.00 | 0.00 |
| EMPLOYEELOUNGEFLR1 | 12880.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| EXERCISECENTERFLR1 | 36401.67 | 98.33 | 0.00 | 0.00 | 0.00 |
| FRONTOFFICEFLR1 | 34205.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR2 | 10990.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM201 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM202_205 | 28623.17 | 1596.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM206_208 | 18915.33 | 1024.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM209_212 | 28602.83 | 1617.17 | 0.00 | 0.00 | 0.00 |
| GUESTROOM213 | 3985.83 | 164.17 | 0.00 | 0.00 | 0.00 |
| GUESTROOM214 | 4010.00 | 140.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM215_218 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM219 | 3985.33 | 164.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM220_223 | 29035.50 | 1184.50 | 0.00 | 0.00 | 0.00 |
| GUESTROOM224 | 4015.83 | 134.17 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR3 | 10990.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM301 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM302_305 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM306_308 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM309_312 | 28600.83 | 1619.17 | 0.00 | 0.00 | 0.00 |
| GUESTROOM313 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM314 | 4010.50 | 139.50 | 0.00 | 0.00 | 0.00 |
| GUESTROOM315_318 | 28953.17 | 1266.83 | 0.00 | 0.00 | 0.00 |
| GUESTROOM319 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM320_323 | 29040.67 | 1179.33 | 0.00 | 0.00 | 0.00 |
| GUESTROOM324 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CORRIDORFLR4 | 10792.67 | 197.33 | 0.00 | 0.00 | 0.00 |
| GUESTROOM401 | 4001.33 | 148.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM402_405 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM406_408 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM409_412 | 28608.00 | 1612.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM413 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM414 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM415_418 | 29070.33 | 1149.67 | 0.00 | 0.00 | 0.00 |
| GUESTROOM419 | 4020.00 | 130.00 | 0.00 | 0.00 | 0.00 |
| GUESTROOM420_423 | 29104.50 | 1115.50 | 0.00 | 0.00 | 0.00 |
| GUESTROOM424 | 4025.50 | 124.50 | 0.00 | 0.00 | 0.00 |
| FRONTSTAIRSFLR4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LAUNDRYROOMFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 1825.00 |
| ELEVATORCOREFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| REARSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ELEVATORCOREFLR4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| FRONTSTORAGEFLR4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 116515.67 | 1619.17 | 0.00 | 0.00 | 1825.00 |
| Average | 8878.35 | 253.66 | 0.00 | 0.00 | 27.24 |
| Sum | 594849.50 | 16995.50 | 0.00 | 0.00 | 1825.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:21:21
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME HOTELSMALL
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | -3.40 |
| February | -4.23 |
| March | 2.667 |
| April | 7.472 |
| May | 13.731 |
| June | 18.627 |
| July | 22.029 |
| August | 20.690 |
| September | 16.545 |
| October | 9.725 |
| November | 6.035 |
| December | -2.18 |
| Annual Sum or Average | 9.049 |
| Minimum of Months | -4.23 |
| Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: REARSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDORFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.123507E+10 | 2976.40 | 17-JAN-16:55 | 7.80 | 6.69 | 0.314965E+09 | 342.42 | 12-JAN-06:10 | 7.80 | 6.69 |
| February | 0.810507E+09 | 2745.92 | 22-FEB-16:55 | 11.70 | 5.56 | 0.282562E+09 | 342.42 | 01-FEB-06:49 | 11.70 | 5.56 |
| March | 0.373786E+10 | 8122.04 | 15-MAR-16:02 | 25.00 | 15.96 | 0.329842E+09 | 344.12 | 11-MAR-08:50 | 25.00 | 15.96 |
| April | 0.586662E+10 | 6140.96 | 09-APR-15:55 | 15.60 | 12.08 | 0.321092E+09 | 342.42 | 01-APR-06:10 | 15.60 | 12.08 |
| May | 0.101390E+11 | 7532.06 | 10-MAY-16:02 | 24.32 | 17.27 | 0.339309E+09 | 342.43 | 24-MAY-05:10 | 18.80 | 15.75 |
| June | 0.136337E+11 | 11288.80 | 26-JUN-16:02 | 28.03 | 20.70 | 0.332804E+09 | 342.43 | 05-JUN-05:10 | 28.03 | 20.70 |
| July | 0.163449E+11 | 12874.08 | 16-JUL-16:02 | 30.03 | 22.83 | 0.340766E+09 | 342.43 | 17-JUL-05:10 | 22.80 | 21.19 |
| August | 0.160814E+11 | 12864.54 | 09-AUG-16:02 | 29.40 | 18.45 | 0.345722E+09 | 342.43 | 25-AUG-05:10 | 18.90 | 18.50 |
| September | 0.134223E+11 | 10670.73 | 16-SEP-16:02 | 26.60 | 19.60 | 0.328114E+09 | 342.42 | 14-SEP-05:10 | 26.60 | 19.60 |
| October | 0.913153E+10 | 7887.15 | 11-OCT-15:55 | 21.70 | 14.52 | 0.334918E+09 | 342.43 | 26-OCT-05:10 | 15.50 | 14.27 |
| November | 0.577915E+10 | 5939.97 | 05-NOV-15:00 | 18.30 | 13.96 | 0.320925E+09 | 342.42 | 05-NOV-06:00 | 18.30 | 13.96 |
| December | 0.167924E+10 | 3385.44 | 01-DEC-13:00 | 13.90 | 12.22 | 0.317710E+09 | 342.42 | 15-DEC-07:10 | 2.20 | 1.62 |
| Annual Sum or Average | 0.978613E+11 | 0.390873E+10 | ||||||||
| Minimum of Months | 0.810507E+09 | 2745.92 | 7.80 | 5.56 | 0.282562E+09 | 342.42 | 2.20 | 1.62 | ||
| Maximum of Months | 0.163449E+11 | 12874.08 | 30.03 | 22.83 | 0.345722E+09 | 344.12 | 28.03 | 21.19 |
Report: ZoneCoolingSummaryMonthly
For: REARSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: FRONTLOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.361857E+10 | 8376.28 | 31-JAN-20:11 | -12.2 | -13.2 | 0.175919E+10 | 2099.17 | 17-JAN-09:00 | -12.2 | -13.2 |
| February | 0.300883E+10 | 8550.51 | 06-FEB-11:15 | -14.6 | -14.8 | 0.159539E+10 | 1957.39 | 15-FEB-09:00 | 6.70 | 4.44 |
| March | 0.461227E+10 | 6842.08 | 01-MAR-02:19 | -6.5 | -7.3 | 0.185145E+10 | 2240.51 | 14-MAR-06:19 | 12.20 | 11.84 |
| April | 0.563786E+10 | 5181.31 | 24-APR-05:40 | 0.93 | -0.2 | 0.182721E+10 | 2240.52 | 09-APR-06:19 | 0.93 | -0.2 |
| May | 0.631374E+10 | 5053.87 | 01-MAY-06:00 | 1.70 | 1.21 | 0.213203E+10 | 2240.53 | 28-MAY-06:10 | 16.88 | 12.67 |
| June | 0.722526E+10 | 6122.57 | 27-JUN-08:57 | 26.70 | 22.32 | 0.216717E+10 | 2240.52 | 04-JUN-06:19 | 26.70 | 22.32 |
| July | 0.825271E+10 | 6399.81 | 20-JUL-08:55 | 27.20 | 22.15 | 0.222796E+10 | 2240.49 | 15-JUL-06:19 | 27.20 | 22.15 |
| August | 0.828540E+10 | 6317.63 | 15-AUG-08:51 | 26.10 | 22.53 | 0.226040E+10 | 2240.50 | 13-AUG-06:19 | 26.10 | 22.53 |
| September | 0.738078E+10 | 6245.83 | 16-SEP-08:52 | 23.90 | 18.78 | 0.213220E+10 | 2240.51 | 02-SEP-06:19 | 23.90 | 18.78 |
| October | 0.722662E+10 | 5616.39 | 23-OCT-05:04 | 11.70 | 9.96 | 0.201197E+10 | 2240.52 | 22-OCT-06:19 | 11.70 | 9.96 |
| November | 0.629465E+10 | 5338.92 | 24-NOV-09:55 | -0.6 | -1.8 | 0.181236E+10 | 2240.53 | 10-NOV-07:19 | -0.6 | -1.8 |
| December | 0.422594E+10 | 6884.63 | 07-DEC-23:59 | -6.7 | -7.5 | 0.176468E+10 | 2240.51 | 01-DEC-08:30 | -6.7 | -7.5 |
| Annual Sum or Average | 0.720826E+11 | 0.235420E+11 | ||||||||
| Minimum of Months | 0.300883E+10 | 5053.87 | -14.6 | -14.8 | 0.159539E+10 | 1957.39 | -12.2 | -13.2 | ||
| Maximum of Months | 0.828540E+10 | 8550.51 | 27.20 | 22.53 | 0.226040E+10 | 2240.53 | 27.20 | 22.53 |
Report: ZoneCoolingSummaryMonthly
For: RESTROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 947677.19 | 221.87 | 18-JAN-15:01 | 2.20 | 1.51 | 70112645.16 | 74.21 | 17-JAN-06:49 | 2.20 | 1.51 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 62280947.90 | 73.79 | 19-FEB-09:00 | 3.90 | -0.4 |
| March | 74560902.46 | 303.28 | 15-MAR-16:33 | 25.00 | 15.95 | 73060697.83 | 74.19 | 11-MAR-07:00 | 25.00 | 15.95 |
| April | 0.154833E+09 | 247.20 | 09-APR-16:02 | 15.22 | 11.74 | 71670119.56 | 74.19 | 15-APR-08:20 | 5.40 | 2.55 |
| May | 0.482673E+09 | 330.43 | 23-MAY-16:41 | 23.40 | 13.14 | 74632622.97 | 74.19 | 08-MAY-05:19 | 23.40 | 13.14 |
| June | 0.840727E+09 | 476.41 | 12-JUN-15:55 | 28.30 | 20.17 | 72495646.32 | 74.19 | 14-JUN-05:19 | 6.87 | 5.04 |
| July | 0.104745E+10 | 512.12 | 20-JUL-16:02 | 29.40 | 23.05 | 73869062.43 | 74.19 | 07-JUL-05:19 | 29.40 | 23.05 |
| August | 0.106153E+10 | 528.89 | 09-AUG-16:11 | 29.40 | 18.38 | 75013782.62 | 74.19 | 13-AUG-06:19 | 16.67 | 13.48 |
| September | 0.878461E+09 | 501.99 | 16-SEP-16:02 | 26.60 | 19.60 | 71732534.82 | 74.19 | 30-SEP-06:19 | 7.40 | 6.20 |
| October | 0.507051E+09 | 385.25 | 12-OCT-16:31 | 17.57 | 14.60 | 74251049.33 | 74.19 | 30-OCT-05:19 | -0.2 | -1.0 |
| November | 0.223445E+09 | 282.46 | 05-NOV-15:00 | 18.30 | 13.96 | 71732851.50 | 74.19 | 24-NOV-06:10 | -3.8 | -4.4 |
| December | 7663036.32 | 198.09 | 15-DEC-13:01 | 2.80 | 1.23 | 71412954.39 | 74.21 | 19-DEC-07:49 | 0.68 | 0.41 |
| Annual Sum or Average | 0.527933E+10 | 0.862265E+09 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 62280947.90 | 73.79 | -3.8 | -4.4 | ||
| Maximum of Months | 0.106153E+10 | 528.89 | 29.40 | 23.05 | 75013782.62 | 74.21 | 29.40 | 23.05 |
Report: ZoneCoolingSummaryMonthly
For: MEETINGROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.768788E+09 | 4517.08 | 31-JAN-16:01 | -12.1 | -13.1 | 0.381863E+09 | 1093.91 | 17-JAN-08:09 | -12.1 | -13.1 |
| February | 0.651613E+09 | 4691.52 | 06-FEB-16:01 | -13.4 | -13.8 | 0.347083E+09 | 1035.52 | 23-FEB-08:09 | 2.70 | 1.78 |
| March | 0.104641E+10 | 5575.71 | 15-MAR-14:01 | 26.02 | 16.09 | 0.403712E+09 | 1298.43 | 17-MAR-07:10 | 9.40 | 9.07 |
| April | 0.128947E+10 | 3209.41 | 03-APR-07:02 | -2.3 | -2.9 | 0.396324E+09 | 1298.43 | 09-APR-07:10 | 11.78 | 10.18 |
| May | 0.129295E+10 | 5708.28 | 23-MAY-14:01 | 23.90 | 13.23 | 0.474501E+09 | 1298.44 | 28-MAY-07:19 | 17.97 | 13.51 |
| June | 0.188742E+10 | 6111.84 | 12-JUN-17:01 | 23.90 | 18.72 | 0.477453E+09 | 1298.46 | 27-JUN-07:49 | 24.72 | 22.02 |
| July | 0.236740E+10 | 6196.44 | 24-JUL-14:01 | 26.02 | 18.25 | 0.486005E+09 | 1298.46 | 04-JUL-07:19 | 26.02 | 18.25 |
| August | 0.232949E+10 | 6301.80 | 09-AUG-14:01 | 29.40 | 18.10 | 0.495795E+09 | 1298.47 | 18-AUG-12:09 | 28.98 | 20.65 |
| September | 0.181352E+10 | 6028.87 | 22-SEP-14:01 | 23.90 | 15.33 | 0.469652E+09 | 1298.45 | 17-SEP-07:19 | 23.90 | 15.33 |
| October | 0.164321E+10 | 5567.11 | 11-OCT-14:01 | 22.20 | 14.22 | 0.440832E+09 | 1298.44 | 01-OCT-07:19 | 22.20 | 14.22 |
| November | 0.145218E+10 | 3236.82 | 24-NOV-08:62 | -2.6 | -3.4 | 0.393678E+09 | 1298.43 | 27-NOV-08:09 | 17.20 | 12.40 |
| December | 0.906140E+09 | 4467.12 | 11-DEC-10:41 | -12.4 | -12.6 | 0.383781E+09 | 1242.44 | 01-DEC-09:00 | -12.4 | -12.6 |
| Annual Sum or Average | 0.174486E+11 | 0.515068E+10 | ||||||||
| Minimum of Months | 0.651613E+09 | 3209.41 | -13.4 | -13.8 | 0.347083E+09 | 1035.52 | -12.4 | -13.1 | ||
| Maximum of Months | 0.236740E+10 | 6301.80 | 29.40 | 18.72 | 0.495795E+09 | 1298.47 | 28.98 | 22.02 |
Report: ZoneCoolingSummaryMonthly
For: MECHANICALROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM101
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 30908067.72 | 421.72 | 31-JAN-15:01 | -11.3 | -12.6 | 0.00 | 0.00 | 01-JAN-00:10 | -11.3 | -12.6 |
| February | 28452889.84 | 443.21 | 06-FEB-15:01 | -13.3 | -13.7 | 0.00 | 0.00 | 01-FEB-00:10 | -13.3 | -13.7 |
| March | 20987930.54 | 353.04 | 06-MAR-15:01 | -6.7 | -8.9 | 0.00 | 0.00 | 01-MAR-00:10 | -6.7 | -8.9 |
| April | 13253738.58 | 280.35 | 16-APR-14:01 | 0.18 | -0.8 | 0.00 | 0.00 | 01-APR-00:10 | 0.18 | -0.8 |
| May | 6423147.08 | 174.68 | 11-MAY-14:01 | 9.32 | 9.05 | 0.00 | 0.00 | 01-MAY-00:10 | 9.32 | 9.05 |
| June | 2548649.29 | 170.18 | 13-JUN-14:01 | 11.20 | 8.28 | 0.00 | 0.00 | 01-JUN-00:10 | 11.20 | 8.28 |
| July | 285466.14 | 37.41 | 22-JUL-15:00 | 20.60 | 19.79 | 0.00 | 0.00 | 01-JUL-00:10 | 20.60 | 19.79 |
| August | 891450.02 | 89.87 | 31-AUG-14:01 | 16.70 | 13.43 | 0.00 | 0.00 | 01-AUG-00:10 | 16.70 | 13.43 |
| September | 4342161.20 | 144.11 | 28-SEP-15:00 | 11.70 | 10.14 | 0.00 | 0.00 | 01-SEP-00:10 | 11.70 | 10.14 |
| October | 13335157.96 | 244.10 | 23-OCT-14:01 | 5.50 | 4.95 | 0.00 | 0.00 | 01-OCT-00:10 | 5.50 | 4.95 |
| November | 18356707.87 | 272.70 | 28-NOV-15:01 | 2.20 | 0.76 | 0.00 | 0.00 | 01-NOV-00:10 | 2.20 | 0.76 |
| December | 30648601.03 | 405.49 | 26-DEC-15:01 | -9.4 | -10.9 | 0.00 | 0.00 | 01-DEC-00:10 | -9.4 | -10.9 |
| Annual Sum or Average | 0.170434E+09 | 0.00 | ||||||||
| Minimum of Months | 285466.14 | 37.41 | -13.3 | -13.7 | 0.00 | 0.00 | -13.3 | -13.7 | ||
| Maximum of Months | 30908067.72 | 443.21 | 20.60 | 19.79 | 0.00 | 0.00 | 20.60 | 19.79 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM102
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 30053801.21 | 414.10 | 31-JAN-15:01 | -11.3 | -12.6 | 0.00 | 0.00 | 01-JAN-00:10 | -11.3 | -12.6 |
| February | 27587405.10 | 436.00 | 06-FEB-15:01 | -13.3 | -13.7 | 0.00 | 0.00 | 01-FEB-00:10 | -13.3 | -13.7 |
| March | 20203247.94 | 345.09 | 06-MAR-15:01 | -6.7 | -8.9 | 0.00 | 0.00 | 01-MAR-00:10 | -6.7 | -8.9 |
| April | 12467428.30 | 271.63 | 16-APR-14:01 | 0.18 | -0.8 | 0.00 | 0.00 | 01-APR-00:10 | 0.18 | -0.8 |
| May | 5843024.39 | 166.68 | 11-MAY-14:01 | 9.32 | 9.05 | 0.00 | 0.00 | 01-MAY-00:10 | 9.32 | 9.05 |
| June | 2221718.68 | 162.71 | 13-JUN-14:01 | 11.20 | 8.28 | 0.00 | 0.00 | 01-JUN-00:10 | 11.20 | 8.28 |
| July | 154930.46 | 30.08 | 22-JUL-15:00 | 20.60 | 19.79 | 0.00 | 0.00 | 01-JUL-00:10 | 20.60 | 19.79 |
| August | 751434.37 | 82.13 | 31-AUG-14:01 | 16.70 | 13.43 | 0.00 | 0.00 | 01-AUG-00:10 | 16.70 | 13.43 |
| September | 3753290.04 | 136.64 | 28-SEP-15:00 | 11.70 | 10.14 | 0.00 | 0.00 | 01-SEP-00:10 | 11.70 | 10.14 |
| October | 12587485.89 | 236.66 | 23-OCT-14:01 | 5.50 | 4.95 | 0.00 | 0.00 | 01-OCT-00:10 | 5.50 | 4.95 |
| November | 17553890.50 | 264.75 | 28-NOV-15:01 | 2.20 | 0.76 | 0.00 | 0.00 | 01-NOV-00:10 | 2.20 | 0.76 |
| December | 29773153.51 | 396.87 | 26-DEC-15:01 | -9.4 | -10.9 | 0.00 | 0.00 | 01-DEC-00:10 | -9.4 | -10.9 |
| Annual Sum or Average | 0.162951E+09 | 0.00 | ||||||||
| Minimum of Months | 154930.46 | 30.08 | -13.3 | -13.7 | 0.00 | 0.00 | -13.3 | -13.7 | ||
| Maximum of Months | 30053801.21 | 436.00 | 20.60 | 19.79 | 0.00 | 0.00 | 20.60 | 19.79 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM103
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 11090924.43 | 1014.69 | 11-JAN-09:03 | 6.88 | 5.42 | 0.117201E+09 | 71.24 | 09-JAN-00:10 | 6.88 | 5.42 |
| February | 5001483.22 | 985.54 | 17-FEB-16:15 | 1.83 | 0.65 | 0.105620E+09 | 71.24 | 06-FEB-02:09 | 1.83 | 0.65 |
| March | 90905377.24 | 1681.71 | 18-MAR-08:61 | 2.02 | 0.18 | 0.119291E+09 | 88.76 | 15-MAR-21:00 | 2.02 | 0.18 |
| April | 0.180613E+09 | 1761.05 | 23-APR-08:61 | 9.27 | 3.41 | 0.117027E+09 | 80.20 | 07-APR-21:00 | 9.27 | 3.41 |
| May | 0.518246E+09 | 1771.53 | 27-MAY-20:01 | 16.52 | 9.66 | 0.126776E+09 | 94.02 | 16-MAY-21:10 | 16.52 | 9.66 |
| June | 0.974900E+09 | 1865.41 | 30-JUN-19:11 | 21.47 | 11.76 | 0.129176E+09 | 106.82 | 19-JUN-21:10 | 21.47 | 11.76 |
| July | 0.136679E+10 | 1783.96 | 06-JUL-19:31 | 19.63 | 12.40 | 0.133969E+09 | 106.86 | 18-JUL-21:10 | 23.22 | 18.88 |
| August | 0.135773E+10 | 1799.29 | 03-AUG-20:31 | 22.07 | 14.63 | 0.134398E+09 | 106.86 | 07-AUG-21:19 | 22.03 | 19.70 |
| September | 0.101972E+10 | 1730.58 | 10-SEP-18:01 | 15.82 | 10.45 | 0.129313E+09 | 106.80 | 15-SEP-21:40 | 21.30 | 20.12 |
| October | 0.637694E+09 | 1706.78 | 24-OCT-08:61 | 2.30 | 0.67 | 0.125205E+09 | 95.40 | 12-OCT-21:00 | 2.30 | 0.67 |
| November | 0.282432E+09 | 1766.92 | 18-NOV-09:01 | 2.38 | 0.04 | 0.117532E+09 | 71.23 | 22-NOV-02:49 | 1.70 | -0.5 |
| December | 25033195.69 | 1667.53 | 02-DEC-09:01 | 4.32 | 2.08 | 0.117764E+09 | 71.24 | 11-DEC-05:00 | -18.9 | -19.4 |
| Annual Sum or Average | 0.647016E+10 | 0.147327E+10 | ||||||||
| Minimum of Months | 5001483.22 | 985.54 | 1.83 | 0.04 | 0.105620E+09 | 71.23 | -18.9 | -19.4 | ||
| Maximum of Months | 0.136679E+10 | 1865.41 | 22.07 | 14.63 | 0.134398E+09 | 106.86 | 23.22 | 20.12 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM104
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.117919E+09 | 2214.87 | 16-JAN-09:01 | -0.9 | -2.2 | 0.119758E+09 | 71.23 | 26-JAN-05:10 | -7.3 | -9.0 |
| February | 70930535.85 | 2265.27 | 19-FEB-09:01 | 2.07 | -1.4 | 0.107729E+09 | 71.24 | 07-FEB-02:49 | 2.07 | -1.4 |
| March | 0.357269E+09 | 2279.92 | 07-MAR-16:11 | -1.9 | -4.8 | 0.122395E+09 | 103.06 | 15-MAR-21:10 | 18.53 | 13.66 |
| April | 0.544284E+09 | 2317.90 | 22-APR-16:41 | 15.18 | 6.61 | 0.119514E+09 | 92.74 | 07-APR-21:10 | 15.18 | 6.61 |
| May | 0.848728E+09 | 2279.69 | 27-MAY-20:41 | 15.78 | 9.75 | 0.128202E+09 | 102.49 | 23-MAY-21:10 | 15.78 | 9.75 |
| June | 0.120291E+10 | 2324.80 | 30-JUN-20:11 | 19.43 | 11.17 | 0.129618E+09 | 106.86 | 19-JUN-21:19 | 19.43 | 11.17 |
| July | 0.158932E+10 | 2294.81 | 06-JUL-16:11 | 22.20 | 13.07 | 0.133900E+09 | 108.05 | 17-JUL-21:19 | 22.20 | 19.60 |
| August | 0.166070E+10 | 2278.14 | 22-AUG-16:01 | 22.70 | 13.33 | 0.134469E+09 | 106.86 | 15-AUG-21:30 | 22.70 | 13.33 |
| September | 0.145943E+10 | 2378.15 | 10-SEP-16:11 | 17.23 | 11.04 | 0.129753E+09 | 110.23 | 13-SEP-21:10 | 22.30 | 18.74 |
| October | 0.112468E+10 | 2319.33 | 30-OCT-16:11 | 15.20 | 9.10 | 0.126577E+09 | 106.74 | 11-OCT-21:19 | 15.20 | 9.10 |
| November | 0.705344E+09 | 2254.31 | 18-NOV-09:01 | 2.38 | 0.04 | 0.119721E+09 | 73.84 | 16-NOV-19:10 | 2.38 | 0.04 |
| December | 0.172875E+09 | 2217.39 | 04-DEC-16:12 | -1.1 | -3.7 | 0.120094E+09 | 71.23 | 29-DEC-04:10 | -7.9 | -8.6 |
| Annual Sum or Average | 0.985439E+10 | 0.149173E+10 | ||||||||
| Minimum of Months | 70930535.85 | 2214.87 | -1.9 | -4.8 | 0.107729E+09 | 71.23 | -7.9 | -9.0 | ||
| Maximum of Months | 0.166070E+10 | 2378.15 | 22.70 | 13.33 | 0.134469E+09 | 110.23 | 22.70 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM105
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.113790E+10 | 3138.15 | 24-JAN-09:01 | -11.5 | -13.0 | 0.123962E+09 | 71.23 | 09-JAN-05:10 | -11.5 | -13.0 |
| February | 0.931164E+09 | 3169.92 | 06-FEB-09:01 | -15.0 | -15.3 | 0.111879E+09 | 71.23 | 25-FEB-04:30 | -8.1 | -9.0 |
| March | 0.152071E+10 | 3119.76 | 07-MAR-09:01 | -9.0 | -11.0 | 0.125200E+09 | 109.03 | 14-MAR-21:10 | 17.02 | 13.02 |
| April | 0.164589E+10 | 2994.90 | 19-APR-16:41 | 16.78 | 8.91 | 0.121387E+09 | 106.44 | 07-APR-21:30 | 16.78 | 8.91 |
| May | 0.182852E+10 | 3023.23 | 03-MAY-18:01 | 14.22 | 6.76 | 0.130705E+09 | 113.16 | 23-MAY-21:10 | 20.60 | 13.34 |
| June | 0.196989E+10 | 3002.32 | 15-JUN-16:31 | 18.17 | 10.71 | 0.132225E+09 | 110.75 | 06-JUN-21:10 | 18.17 | 10.71 |
| July | 0.229634E+10 | 2997.15 | 06-JUL-17:01 | 22.38 | 13.26 | 0.135571E+09 | 112.99 | 17-JUL-21:19 | 22.20 | 19.60 |
| August | 0.235027E+10 | 2983.51 | 22-AUG-16:51 | 22.20 | 13.51 | 0.136099E+09 | 112.61 | 17-AUG-21:40 | 22.20 | 13.51 |
| September | 0.220127E+10 | 3019.40 | 10-SEP-16:11 | 17.23 | 11.04 | 0.131514E+09 | 117.54 | 13-SEP-21:10 | 22.30 | 18.74 |
| October | 0.214412E+10 | 3027.73 | 30-OCT-16:11 | 15.20 | 9.10 | 0.127607E+09 | 110.79 | 03-OCT-21:10 | 15.20 | 9.10 |
| November | 0.175902E+10 | 2937.94 | 26-NOV-17:51 | 15.00 | 9.60 | 0.121169E+09 | 82.28 | 16-NOV-19:10 | 15.00 | 9.60 |
| December | 0.120529E+10 | 3157.93 | 26-DEC-09:01 | -12.7 | -13.9 | 0.124007E+09 | 71.23 | 11-DEC-04:49 | -12.7 | -13.9 |
| Annual Sum or Average | 0.209904E+11 | 0.152133E+10 | ||||||||
| Minimum of Months | 0.931164E+09 | 2937.94 | -15.0 | -15.3 | 0.111879E+09 | 71.23 | -12.7 | -13.9 | ||
| Maximum of Months | 0.235027E+10 | 3169.92 | 22.38 | 13.51 | 0.136099E+09 | 117.54 | 22.30 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: EMPLOYEELOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.498544E+10 | 3604.50 | 06-JAN-12:55 | -3.3 | -5.1 | 0.294826E+09 | 760.92 | 05-JAN-12:09 | -3.3 | -5.1 |
| February | 0.443712E+10 | 3648.18 | 28-FEB-12:55 | 0.00 | -2.8 | 0.271462E+09 | 760.92 | 22-FEB-12:09 | 0.00 | -2.8 |
| March | 0.540213E+10 | 3986.80 | 14-MAR-11:55 | 23.90 | 17.56 | 0.319166E+09 | 760.93 | 09-MAR-12:20 | 23.90 | 17.56 |
| April | 0.534952E+10 | 3887.37 | 24-APR-11:55 | 10.60 | 5.96 | 0.295313E+09 | 760.93 | 27-APR-11:20 | 12.97 | 8.33 |
| May | 0.592645E+10 | 3924.76 | 10-MAY-11:55 | 22.80 | 16.77 | 0.314429E+09 | 760.92 | 16-MAY-11:09 | 17.98 | 11.29 |
| June | 0.621161E+10 | 4127.09 | 12-JUN-12:00 | 29.40 | 20.11 | 0.309145E+09 | 760.92 | 15-JUN-11:09 | 17.88 | 11.67 |
| July | 0.671411E+10 | 4235.92 | 21-JUL-12:00 | 30.00 | 21.57 | 0.300732E+09 | 760.92 | 20-JUL-11:09 | 30.00 | 21.57 |
| August | 0.684271E+10 | 4320.64 | 18-AUG-12:00 | 28.90 | 20.68 | 0.321275E+09 | 760.92 | 18-AUG-11:09 | 28.90 | 20.68 |
| September | 0.652345E+10 | 4493.10 | 21-SEP-11:55 | 24.40 | 16.54 | 0.295448E+09 | 760.91 | 12-SEP-11:09 | 24.40 | 16.54 |
| October | 0.617058E+10 | 4439.73 | 11-OCT-11:55 | 21.70 | 13.44 | 0.307580E+09 | 760.91 | 25-OCT-11:09 | 11.97 | 6.42 |
| November | 0.546017E+10 | 4096.50 | 01-NOV-12:00 | 11.10 | 6.28 | 0.295419E+09 | 760.94 | 30-NOV-12:20 | 4.40 | 3.33 |
| December | 0.500493E+10 | 3735.44 | 04-DEC-13:00 | -0.6 | -3.3 | 0.296445E+09 | 760.93 | 29-DEC-12:39 | -5.2 | -5.8 |
| Annual Sum or Average | 0.690282E+11 | 0.362124E+10 | ||||||||
| Minimum of Months | 0.443712E+10 | 3604.50 | -3.3 | -5.1 | 0.271462E+09 | 760.91 | -5.2 | -5.8 | ||
| Maximum of Months | 0.684271E+10 | 4493.10 | 30.00 | 21.57 | 0.321275E+09 | 760.94 | 30.00 | 21.57 |
Report: ZoneCoolingSummaryMonthly
For: LAUNDRYROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.181490E+09 | 250.19 | 01-JAN-10:09 | -0.5 | -1.2 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.163926E+09 | 250.19 | 01-FEB-10:09 | 4.90 | 4.62 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.181490E+09 | 250.19 | 01-MAR-10:09 | -3.7 | -5.4 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.175635E+09 | 250.19 | 01-APR-09:09 | 5.47 | 3.78 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.181490E+09 | 250.19 | 01-MAY-09:09 | 11.28 | 6.89 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.175635E+09 | 250.19 | 01-JUN-09:09 | 16.97 | 14.78 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.181490E+09 | 250.19 | 01-JUL-09:09 | 19.08 | 15.85 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.181490E+09 | 250.19 | 01-AUG-09:09 | 19.68 | 15.68 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.175635E+09 | 250.19 | 01-SEP-09:09 | 15.28 | 13.36 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.181490E+09 | 250.19 | 01-OCT-09:09 | 15.18 | 14.03 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.175635E+09 | 250.19 | 01-NOV-09:09 | 6.57 | 3.59 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.181490E+09 | 250.19 | 01-DEC-10:09 | 14.50 | 11.95 |
| Annual Sum or Average | 0.00 | 0.213690E+10 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.163926E+09 | 250.19 | -3.7 | -5.4 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.181490E+09 | 250.19 | 19.68 | 15.85 |
Report: ZoneCoolingSummaryMonthly
For: ELEVATORCOREFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: EXERCISECENTERFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.162844E+10 | 1420.43 | 30-JAN-01:13 | -10.0 | -10.9 | 0.549055E+09 | 422.73 | 11-JAN-16:30 | -10.0 | -10.9 |
| February | 0.140326E+10 | 1467.79 | 21-FEB-02:41 | -11.0 | -12.2 | 0.493882E+09 | 422.74 | 22-FEB-17:40 | 12.43 | 5.97 |
| March | 0.179722E+10 | 1589.82 | 07-MAR-05:42 | -13.3 | -13.9 | 0.597012E+09 | 422.74 | 22-MAR-12:20 | 16.47 | 7.38 |
| April | 0.172796E+10 | 1178.41 | 21-APR-12:04 | 14.60 | 7.64 | 0.620658E+09 | 422.75 | 07-APR-12:09 | 14.60 | 7.64 |
| May | 0.182081E+10 | 1230.01 | 14-MAY-15:02 | 25.92 | 17.84 | 0.678207E+09 | 422.74 | 28-MAY-06:10 | 16.88 | 12.67 |
| June | 0.195670E+10 | 1361.09 | 12-JUN-15:02 | 29.72 | 20.02 | 0.660675E+09 | 422.76 | 27-JUN-12:09 | 30.10 | 23.02 |
| July | 0.217222E+10 | 1416.24 | 19-JUL-15:02 | 30.92 | 22.81 | 0.683813E+09 | 422.77 | 27-JUL-12:09 | 28.98 | 22.31 |
| August | 0.224555E+10 | 1523.42 | 18-AUG-15:02 | 29.90 | 20.94 | 0.683730E+09 | 422.77 | 13-AUG-12:09 | 29.90 | 20.94 |
| September | 0.216765E+10 | 1654.32 | 21-SEP-15:02 | 26.10 | 16.73 | 0.660577E+09 | 422.76 | 15-SEP-12:09 | 26.10 | 16.73 |
| October | 0.205791E+10 | 1545.45 | 11-OCT-15:02 | 22.12 | 14.59 | 0.668144E+09 | 422.74 | 03-OCT-12:09 | 22.12 | 14.59 |
| November | 0.186133E+10 | 1254.23 | 01-NOV-12:04 | 11.20 | 6.39 | 0.613175E+09 | 422.74 | 10-NOV-07:19 | 14.27 | 10.15 |
| December | 0.166940E+10 | 1511.16 | 27-DEC-01:51 | -11.7 | -12.1 | 0.554814E+09 | 422.74 | 01-DEC-09:20 | -11.7 | -12.1 |
| Annual Sum or Average | 0.225085E+11 | 0.746374E+10 | ||||||||
| Minimum of Months | 0.140326E+10 | 1178.41 | -13.3 | -13.9 | 0.493882E+09 | 422.73 | -11.7 | -12.1 | ||
| Maximum of Months | 0.224555E+10 | 1654.32 | 30.92 | 22.81 | 0.683813E+09 | 422.77 | 30.10 | 23.02 |
Report: ZoneCoolingSummaryMonthly
For: FRONTOFFICEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.210793E+10 | 2041.51 | 31-JAN-15:02 | -11.3 | -12.6 | 0.507802E+09 | 603.92 | 17-JAN-16:19 | -11.3 | -12.6 |
| February | 0.169637E+10 | 2148.62 | 06-FEB-15:02 | -13.3 | -13.7 | 0.463280E+09 | 603.92 | 22-FEB-15:20 | 10.60 | 4.95 |
| March | 0.274824E+10 | 7560.52 | 08-MAR-15:01 | 7.20 | 1.52 | 0.580109E+09 | 631.61 | 16-MAR-14:09 | 18.98 | 15.28 |
| April | 0.268232E+10 | 7569.17 | 05-APR-14:01 | 7.12 | 4.38 | 0.572948E+09 | 631.61 | 07-APR-12:09 | 19.50 | 11.16 |
| May | 0.318443E+10 | 7425.00 | 18-MAY-12:01 | 11.88 | 7.41 | 0.633845E+09 | 631.61 | 17-MAY-12:09 | 11.88 | 7.41 |
| June | 0.427276E+10 | 7426.61 | 13-JUN-14:01 | 11.20 | 8.28 | 0.624070E+09 | 631.62 | 07-JUN-12:09 | 11.20 | 8.28 |
| July | 0.522892E+10 | 7048.29 | 06-JUL-14:01 | 22.12 | 12.54 | 0.621978E+09 | 631.62 | 20-JUL-14:09 | 29.82 | 23.91 |
| August | 0.555187E+10 | 7042.46 | 22-AUG-14:01 | 22.88 | 13.18 | 0.647462E+09 | 631.62 | 10-AUG-12:09 | 22.88 | 13.18 |
| September | 0.504624E+10 | 7313.84 | 30-SEP-14:01 | 15.60 | 11.53 | 0.607280E+09 | 631.62 | 15-SEP-14:09 | 15.60 | 11.53 |
| October | 0.386949E+10 | 7653.12 | 16-OCT-12:01 | 6.70 | 4.42 | 0.622132E+09 | 631.61 | 06-OCT-14:09 | 6.70 | 4.42 |
| November | 0.293057E+10 | 7709.38 | 24-NOV-15:01 | 4.90 | 1.89 | 0.578340E+09 | 631.61 | 16-NOV-15:09 | 4.90 | 1.89 |
| December | 0.225508E+10 | 6458.42 | 01-DEC-13:01 | 12.97 | 11.34 | 0.513437E+09 | 628.70 | 01-DEC-13:09 | 12.97 | 11.34 |
| Annual Sum or Average | 0.415742E+11 | 0.697268E+10 | ||||||||
| Minimum of Months | 0.169637E+10 | 2041.51 | -13.3 | -13.7 | 0.463280E+09 | 603.92 | -11.3 | -12.6 | ||
| Maximum of Months | 0.555187E+10 | 7709.38 | 22.88 | 13.18 | 0.647462E+09 | 631.62 | 29.82 | 23.91 |
Report: ZoneCoolingSummaryMonthly
For: FRONTSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: FRONTSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: REARSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDORFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.155761E+10 | 1094.77 | 05-JAN-22:00 | -8.3 | -9.8 | 0.227788E+09 | 258.40 | 17-JAN-09:00 | 8.30 | 3.71 |
| February | 0.129031E+10 | 1114.58 | 27-FEB-22:00 | -7.8 | -8.4 | 0.205429E+09 | 243.77 | 19-FEB-09:00 | -7.8 | -8.4 |
| March | 0.200256E+10 | 1937.35 | 15-MAR-20:52 | 18.90 | 13.76 | 0.252042E+09 | 285.35 | 14-MAR-07:30 | 18.90 | 13.76 |
| April | 0.174668E+10 | 1649.09 | 09-APR-16:42 | 13.68 | 10.37 | 0.260938E+09 | 285.35 | 20-APR-07:30 | 11.10 | 9.21 |
| May | 0.284855E+10 | 2153.24 | 31-MAY-18:15 | 20.53 | 13.89 | 0.286476E+09 | 285.35 | 28-MAY-06:40 | 20.53 | 13.89 |
| June | 0.430305E+10 | 2654.37 | 19-JUN-19:02 | 21.93 | 14.84 | 0.278824E+09 | 285.35 | 05-JUN-05:10 | 21.93 | 14.84 |
| July | 0.511902E+10 | 2704.44 | 17-JUL-19:32 | 23.17 | 20.50 | 0.284111E+09 | 285.35 | 11-JUL-05:19 | 23.17 | 20.50 |
| August | 0.495399E+10 | 2661.21 | 19-AUG-18:05 | 21.02 | 15.38 | 0.288514E+09 | 285.35 | 13-AUG-06:19 | 21.02 | 15.38 |
| September | 0.392788E+10 | 2506.33 | 15-SEP-20:31 | 21.87 | 20.55 | 0.275818E+09 | 285.35 | 29-SEP-05:19 | 10.40 | 9.27 |
| October | 0.209615E+10 | 2001.48 | 11-OCT-16:53 | 21.70 | 14.52 | 0.278928E+09 | 285.35 | 21-OCT-08:20 | 11.10 | 8.24 |
| November | 0.163557E+10 | 1136.55 | 05-NOV-08:52 | 18.30 | 13.72 | 0.253500E+09 | 285.35 | 05-NOV-06:10 | 18.30 | 13.72 |
| December | 0.147317E+10 | 1090.03 | 28-DEC-12:05 | -9.9 | -11.0 | 0.230341E+09 | 268.48 | 01-DEC-09:00 | -9.9 | -11.0 |
| Annual Sum or Average | 0.329545E+11 | 0.312271E+10 | ||||||||
| Minimum of Months | 0.129031E+10 | 1090.03 | -9.9 | -11.0 | 0.205429E+09 | 243.77 | -9.9 | -11.0 | ||
| Maximum of Months | 0.511902E+10 | 2704.44 | 23.17 | 20.55 | 0.288514E+09 | 285.35 | 23.17 | 20.50 |
Report: ZoneCoolingSummaryMonthly
For: REARSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM201
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 18734714.74 | 364.71 | 31-JAN-15:01 | -11.3 | -12.6 | 0.00 | 0.00 | 01-JAN-00:10 | -11.3 | -12.6 |
| February | 18256113.08 | 336.24 | 21-FEB-15:01 | -9.5 | -10.9 | 0.00 | 0.00 | 01-FEB-00:10 | -9.5 | -10.9 |
| March | 16666546.43 | 302.16 | 06-MAR-15:01 | -6.7 | -8.9 | 0.00 | 0.00 | 01-MAR-00:10 | -6.7 | -8.9 |
| April | 10680578.61 | 231.13 | 16-APR-14:01 | 0.18 | -0.8 | 0.00 | 0.00 | 01-APR-00:10 | 0.18 | -0.8 |
| May | 5298607.58 | 151.31 | 11-MAY-14:01 | 9.32 | 9.05 | 0.00 | 0.00 | 01-MAY-00:10 | 9.32 | 9.05 |
| June | 3905498.41 | 148.90 | 13-JUN-14:01 | 11.20 | 8.28 | 0.00 | 0.00 | 01-JUN-00:10 | 11.20 | 8.28 |
| July | 11142820.47 | 117.40 | 21-JUL-13:30 | 31.15 | 21.91 | 0.00 | 0.00 | 01-JUL-00:10 | 31.15 | 21.91 |
| August | 2870222.99 | 409.14 | 14-AUG-15:01 | 27.80 | 21.86 | 0.00 | 0.00 | 01-AUG-00:10 | 27.80 | 21.86 |
| September | 2685554.20 | 112.28 | 28-SEP-15:00 | 11.70 | 10.14 | 0.00 | 0.00 | 01-SEP-00:10 | 11.70 | 10.14 |
| October | 9425149.16 | 205.33 | 23-OCT-14:01 | 5.50 | 4.95 | 0.00 | 0.00 | 01-OCT-00:10 | 5.50 | 4.95 |
| November | 13199464.13 | 218.72 | 28-NOV-15:01 | 2.20 | 0.76 | 0.00 | 0.00 | 01-NOV-00:10 | 2.20 | 0.76 |
| December | 16887180.13 | 340.25 | 10-DEC-15:01 | -9.6 | -10.6 | 0.00 | 0.00 | 01-DEC-00:10 | -9.6 | -10.6 |
| Annual Sum or Average | 0.129752E+09 | 0.00 | ||||||||
| Minimum of Months | 2685554.20 | 112.28 | -11.3 | -12.6 | 0.00 | 0.00 | -11.3 | -12.6 | ||
| Maximum of Months | 18734714.74 | 409.14 | 31.15 | 21.91 | 0.00 | 0.00 | 31.15 | 21.91 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM202_205
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.190762E+09 | 6800.72 | 22-JAN-09:01 | 0.00 | -1.7 | 0.473479E+09 | 284.95 | 24-JAN-05:10 | -11.8 | -13.0 |
| February | 0.160452E+09 | 6934.71 | 19-FEB-09:01 | 2.07 | -1.4 | 0.427804E+09 | 284.95 | 06-FEB-01:10 | 2.07 | -1.4 |
| March | 0.105012E+10 | 6997.84 | 25-MAR-08:61 | -3.4 | -4.7 | 0.486236E+09 | 402.25 | 15-MAR-21:00 | -3.4 | -4.7 |
| April | 0.190036E+10 | 6913.55 | 16-APR-08:61 | -2.9 | -4.2 | 0.479237E+09 | 373.85 | 07-APR-21:00 | -2.9 | -4.2 |
| May | 0.353093E+10 | 7181.78 | 27-MAY-20:01 | 16.52 | 9.66 | 0.522807E+09 | 439.26 | 16-MAY-21:10 | 16.52 | 9.66 |
| June | 0.485019E+10 | 7267.60 | 03-JUN-17:01 | 18.72 | 10.09 | 0.531855E+09 | 446.27 | 26-JUN-21:40 | 21.87 | 19.58 |
| July | 0.593607E+10 | 7252.74 | 06-JUL-16:21 | 22.20 | 13.10 | 0.546113E+09 | 461.77 | 24-JUL-21:19 | 20.93 | 17.61 |
| August | 0.547258E+10 | 7022.35 | 01-AUG-16:11 | 23.90 | 14.79 | 0.546461E+09 | 462.76 | 17-AUG-21:10 | 20.32 | 13.80 |
| September | 0.395489E+10 | 6832.73 | 02-SEP-19:31 | 13.53 | 9.92 | 0.526134E+09 | 451.72 | 15-SEP-21:10 | 21.60 | 20.41 |
| October | 0.244385E+10 | 6415.59 | 24-OCT-08:61 | 2.30 | 0.67 | 0.505011E+09 | 409.33 | 12-OCT-21:00 | 2.30 | 0.67 |
| November | 0.128490E+10 | 6759.50 | 18-NOV-09:01 | 2.38 | 0.04 | 0.472714E+09 | 284.92 | 24-NOV-04:10 | -3.2 | -3.8 |
| December | 0.273243E+09 | 6745.30 | 03-DEC-09:01 | 1.10 | -1.3 | 0.474789E+09 | 284.95 | 12-DEC-00:30 | -14.2 | -14.6 |
| Annual Sum or Average | 0.310483E+11 | 0.599264E+10 | ||||||||
| Minimum of Months | 0.160452E+09 | 6415.59 | -3.4 | -4.7 | 0.427804E+09 | 284.92 | -14.2 | -14.6 | ||
| Maximum of Months | 0.593607E+10 | 7267.60 | 23.90 | 14.79 | 0.546461E+09 | 462.76 | 21.87 | 20.41 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM206_208
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.324134E+09 | 5724.34 | 21-JAN-09:01 | -2.0 | -3.9 | 0.357562E+09 | 213.70 | 24-JAN-05:10 | -11.8 | -13.0 |
| February | 0.267625E+09 | 6053.13 | 25-FEB-09:01 | -7.6 | -8.8 | 0.322907E+09 | 213.71 | 06-FEB-23:40 | -7.6 | -8.8 |
| March | 0.114329E+10 | 6177.20 | 04-MAR-09:01 | -7.7 | -9.2 | 0.366936E+09 | 304.55 | 15-MAR-21:00 | 16.70 | 13.08 |
| April | 0.191673E+10 | 5689.03 | 16-APR-08:61 | -2.9 | -4.2 | 0.361005E+09 | 286.52 | 07-APR-21:00 | -2.9 | -4.2 |
| May | 0.309889E+10 | 5757.76 | 27-MAY-20:01 | 16.52 | 9.66 | 0.392597E+09 | 331.19 | 16-MAY-21:10 | 16.52 | 9.66 |
| June | 0.389097E+10 | 5770.55 | 30-JUN-20:21 | 19.15 | 11.12 | 0.398623E+09 | 332.56 | 26-JUN-21:40 | 19.15 | 11.12 |
| July | 0.463754E+10 | 5740.07 | 06-JUL-16:21 | 22.20 | 13.10 | 0.408974E+09 | 343.13 | 24-JUL-21:19 | 20.93 | 17.61 |
| August | 0.430218E+10 | 5534.51 | 01-AUG-16:11 | 23.90 | 14.79 | 0.409349E+09 | 345.25 | 02-AUG-21:10 | 18.12 | 12.76 |
| September | 0.325947E+10 | 5490.05 | 02-SEP-19:31 | 13.53 | 9.92 | 0.394671E+09 | 338.41 | 15-SEP-21:10 | 21.60 | 20.41 |
| October | 0.230160E+10 | 5290.53 | 24-OCT-08:61 | 2.30 | 0.67 | 0.380225E+09 | 310.21 | 11-OCT-21:19 | 2.30 | 0.67 |
| November | 0.142239E+10 | 5559.44 | 18-NOV-09:01 | 2.38 | 0.04 | 0.356864E+09 | 217.07 | 16-NOV-19:10 | 2.38 | 0.04 |
| December | 0.429080E+09 | 5664.83 | 23-DEC-09:01 | 0.68 | -2.0 | 0.358494E+09 | 213.70 | 11-DEC-02:20 | 0.68 | -2.0 |
| Annual Sum or Average | 0.269939E+11 | 0.450821E+10 | ||||||||
| Minimum of Months | 0.267625E+09 | 5290.53 | -7.7 | -9.2 | 0.322907E+09 | 213.70 | -11.8 | -13.0 | ||
| Maximum of Months | 0.463754E+10 | 6177.20 | 23.90 | 14.79 | 0.409349E+09 | 345.25 | 21.60 | 20.41 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM209_212
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.522860E+09 | 7564.59 | 29-JAN-09:01 | -7.1 | -8.8 | 0.478108E+09 | 284.93 | 24-JAN-05:10 | -7.1 | -8.8 |
| February | 0.425404E+09 | 7650.14 | 05-FEB-09:01 | -11.7 | -12.4 | 0.431642E+09 | 284.94 | 06-FEB-23:49 | -15.0 | -15.8 |
| March | 0.144407E+10 | 7552.58 | 04-MAR-09:01 | -7.7 | -9.2 | 0.490140E+09 | 402.83 | 15-MAR-21:00 | 16.70 | 13.08 |
| April | 0.232361E+10 | 6990.67 | 16-APR-08:61 | -2.9 | -4.2 | 0.481789E+09 | 385.17 | 07-APR-21:00 | -2.9 | -4.2 |
| May | 0.360006E+10 | 7020.81 | 27-MAY-20:01 | 16.52 | 9.66 | 0.522984E+09 | 440.21 | 16-MAY-21:10 | 16.52 | 9.66 |
| June | 0.449625E+10 | 7115.11 | 03-JUN-17:01 | 18.72 | 10.09 | 0.530342E+09 | 437.77 | 26-JUN-21:40 | 21.87 | 19.58 |
| July | 0.535233E+10 | 6786.60 | 06-JUL-16:41 | 22.20 | 13.15 | 0.544024E+09 | 454.44 | 07-JUL-21:19 | 19.23 | 15.13 |
| August | 0.502761E+10 | 6654.96 | 03-AUG-20:31 | 22.07 | 14.63 | 0.544831E+09 | 459.26 | 02-AUG-21:10 | 22.07 | 14.63 |
| September | 0.394756E+10 | 6691.82 | 02-SEP-19:31 | 13.53 | 9.92 | 0.526261E+09 | 451.23 | 15-SEP-21:10 | 21.60 | 20.41 |
| October | 0.295118E+10 | 6430.84 | 24-OCT-08:61 | 2.30 | 0.67 | 0.508182E+09 | 419.42 | 11-OCT-21:19 | 2.30 | 0.67 |
| November | 0.192000E+10 | 6825.10 | 18-NOV-09:01 | 2.38 | 0.04 | 0.477553E+09 | 297.10 | 16-NOV-19:10 | 2.38 | 0.04 |
| December | 0.674331E+09 | 6959.20 | 23-DEC-09:01 | 0.68 | -2.0 | 0.479556E+09 | 284.93 | 11-DEC-03:30 | 0.68 | -2.0 |
| Annual Sum or Average | 0.326853E+11 | 0.601541E+10 | ||||||||
| Minimum of Months | 0.425404E+09 | 6430.84 | -11.7 | -12.4 | 0.431642E+09 | 284.93 | -15.0 | -15.8 | ||
| Maximum of Months | 0.535233E+10 | 7650.14 | 22.20 | 14.63 | 0.544831E+09 | 459.26 | 22.07 | 20.41 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM213
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 7624155.92 | 894.11 | 03-JAN-09:03 | -5.1 | -5.9 | 0.116869E+09 | 71.24 | 24-JAN-05:00 | -12.2 | -13.5 |
| February | 4043090.60 | 929.90 | 01-FEB-09:03 | 5.50 | 5.21 | 0.105479E+09 | 71.25 | 06-FEB-23:10 | -15.0 | -15.7 |
| March | 0.135751E+09 | 1679.18 | 18-MAR-08:61 | 2.02 | 0.18 | 0.119771E+09 | 97.10 | 15-MAR-21:00 | 2.02 | 0.18 |
| April | 0.279698E+09 | 1787.35 | 23-APR-08:61 | 9.27 | 3.41 | 0.117973E+09 | 87.29 | 07-APR-21:00 | 9.27 | 3.41 |
| May | 0.701078E+09 | 1918.22 | 27-MAY-20:01 | 16.52 | 9.66 | 0.128934E+09 | 102.94 | 23-MAY-21:00 | 16.52 | 9.66 |
| June | 0.111026E+10 | 1903.15 | 03-JUN-18:21 | 17.80 | 10.37 | 0.131343E+09 | 107.71 | 26-JUN-21:40 | 21.87 | 19.58 |
| July | 0.146089E+10 | 1845.15 | 06-JUL-16:41 | 22.20 | 13.15 | 0.135384E+09 | 110.50 | 24-JUL-21:19 | 20.93 | 17.61 |
| August | 0.134140E+10 | 1822.59 | 03-AUG-20:31 | 22.07 | 14.63 | 0.135471E+09 | 112.41 | 02-AUG-21:10 | 22.07 | 14.63 |
| September | 0.907859E+09 | 1770.51 | 09-SEP-19:41 | 15.28 | 10.99 | 0.129977E+09 | 110.06 | 15-SEP-21:10 | 21.60 | 20.41 |
| October | 0.461498E+09 | 1650.83 | 25-OCT-20:11 | 14.03 | 11.39 | 0.124606E+09 | 97.34 | 12-OCT-21:00 | 14.03 | 11.39 |
| November | 0.160158E+09 | 1695.40 | 12-NOV-09:01 | 2.30 | -0.5 | 0.116562E+09 | 71.23 | 24-NOV-04:10 | -3.2 | -3.8 |
| December | 11226456.34 | 835.65 | 14-DEC-09:02 | 5.60 | 5.31 | 0.117119E+09 | 71.24 | 11-DEC-03:00 | 5.60 | 5.31 |
| Annual Sum or Average | 0.658148E+10 | 0.147949E+10 | ||||||||
| Minimum of Months | 4043090.60 | 835.65 | -5.1 | -5.9 | 0.105479E+09 | 71.23 | -15.0 | -15.7 | ||
| Maximum of Months | 0.146089E+10 | 1918.22 | 22.20 | 14.63 | 0.135471E+09 | 112.41 | 22.07 | 20.41 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM214
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.223633E+09 | 2585.64 | 12-JAN-16:11 | -6.3 | -8.3 | 0.120736E+09 | 71.24 | 24-JAN-02:20 | -11.3 | -12.7 |
| February | 0.167226E+09 | 2423.86 | 19-FEB-09:01 | 2.07 | -1.4 | 0.108780E+09 | 71.24 | 07-FEB-05:00 | 2.07 | -1.4 |
| March | 0.679138E+09 | 2563.34 | 04-MAR-09:01 | -7.7 | -9.2 | 0.124145E+09 | 108.63 | 14-MAR-21:10 | 17.02 | 13.02 |
| April | 0.962288E+09 | 2491.22 | 22-APR-16:41 | 15.18 | 6.61 | 0.120857E+09 | 103.59 | 07-APR-21:30 | 15.18 | 6.61 |
| May | 0.135339E+10 | 2516.17 | 21-MAY-17:41 | 16.88 | 9.97 | 0.130368E+09 | 114.73 | 23-MAY-21:10 | 20.60 | 13.34 |
| June | 0.161638E+10 | 2509.43 | 04-JUN-16:11 | 19.80 | 12.17 | 0.132168E+09 | 112.00 | 29-JUN-21:19 | 20.73 | 18.84 |
| July | 0.197245E+10 | 2481.12 | 06-JUL-16:11 | 22.20 | 13.07 | 0.135717E+09 | 116.86 | 17-JUL-21:19 | 22.20 | 19.60 |
| August | 0.194987E+10 | 2481.32 | 22-AUG-16:01 | 22.70 | 13.33 | 0.136042E+09 | 114.02 | 17-AUG-21:40 | 22.70 | 13.33 |
| September | 0.165934E+10 | 2551.13 | 10-SEP-16:11 | 17.23 | 11.04 | 0.131114E+09 | 117.21 | 13-SEP-21:10 | 22.30 | 18.74 |
| October | 0.127130E+10 | 2562.24 | 30-OCT-16:11 | 15.20 | 9.10 | 0.127190E+09 | 107.78 | 03-OCT-21:10 | 15.20 | 9.10 |
| November | 0.804709E+09 | 2356.99 | 18-NOV-09:01 | 2.38 | 0.04 | 0.120219E+09 | 77.41 | 16-NOV-19:10 | 2.38 | 0.04 |
| December | 0.249026E+09 | 2425.95 | 11-DEC-16:11 | -9.6 | -10.2 | 0.120704E+09 | 71.23 | 27-DEC-01:00 | -11.7 | -12.1 |
| Annual Sum or Average | 0.129087E+11 | 0.150804E+10 | ||||||||
| Minimum of Months | 0.167226E+09 | 2356.99 | -9.6 | -10.2 | 0.108780E+09 | 71.23 | -11.7 | -12.7 | ||
| Maximum of Months | 0.197245E+10 | 2585.64 | 22.70 | 13.33 | 0.136042E+09 | 117.21 | 22.70 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM215_218
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.195559E+10 | 3324.42 | 15-JAN-15:25 | 5.30 | 1.42 | 0.00 | 0.00 | 01-JAN-00:10 | 5.30 | 1.42 |
| February | 0.164287E+10 | 3181.22 | 28-FEB-15:25 | 0.30 | -2.5 | 0.00 | 0.00 | 01-FEB-00:10 | 0.30 | -2.5 |
| March | 0.360094E+10 | 4231.75 | 15-MAR-13:40 | 25.73 | 15.91 | 0.00 | 0.00 | 01-MAR-00:10 | 25.73 | 15.91 |
| April | 0.415817E+10 | 3800.80 | 09-APR-16:11 | 14.83 | 11.40 | 0.00 | 0.00 | 01-APR-00:10 | 14.83 | 11.40 |
| May | 0.548112E+10 | 3957.20 | 14-MAY-14:30 | 25.55 | 18.01 | 0.00 | 0.00 | 01-MAY-00:10 | 25.55 | 18.01 |
| June | 0.640321E+10 | 4178.42 | 12-JUN-15:23 | 29.15 | 20.10 | 0.00 | 0.00 | 01-JUN-00:10 | 29.15 | 20.10 |
| July | 0.727332E+10 | 4337.08 | 19-JUL-15:23 | 30.55 | 22.69 | 0.00 | 0.00 | 01-JUL-00:10 | 30.55 | 22.69 |
| August | 0.733849E+10 | 4688.52 | 18-AUG-15:01 | 29.90 | 20.94 | 0.00 | 0.00 | 01-AUG-00:10 | 29.90 | 20.94 |
| September | 0.670995E+10 | 5279.20 | 21-SEP-14:50 | 26.02 | 16.63 | 0.00 | 0.00 | 01-SEP-00:10 | 26.02 | 16.63 |
| October | 0.519313E+10 | 4933.77 | 11-OCT-15:00 | 22.20 | 14.61 | 0.00 | 0.00 | 01-OCT-00:10 | 22.20 | 14.61 |
| November | 0.364365E+10 | 3888.89 | 03-NOV-14:25 | 9.70 | 5.23 | 0.00 | 0.00 | 01-NOV-00:10 | 9.70 | 5.23 |
| December | 0.190879E+10 | 3141.58 | 16-DEC-13:40 | 5.60 | 2.97 | 0.00 | 0.00 | 01-DEC-00:10 | 5.60 | 2.97 |
| Annual Sum or Average | 0.553092E+11 | 0.00 | ||||||||
| Minimum of Months | 0.164287E+10 | 3141.58 | 0.30 | -2.5 | 0.00 | 0.00 | 0.30 | -2.5 | ||
| Maximum of Months | 0.733849E+10 | 5279.20 | 30.55 | 22.69 | 0.00 | 0.00 | 30.55 | 22.69 |
Report: ZoneCoolingSummaryMonthly
For: ELEVATORCOREFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM219
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.539599E+10 | 7849.47 | 16-JAN-09:01 | -0.9 | -2.2 | 0.124337E+09 | 71.23 | 12-JAN-04:00 | -0.9 | -2.2 |
| February | 0.476878E+10 | 7700.35 | 19-FEB-09:01 | 2.07 | -1.4 | 0.112350E+09 | 71.23 | 01-FEB-04:10 | 2.07 | -1.4 |
| March | 0.615923E+10 | 8742.59 | 14-MAR-18:51 | 19.40 | 14.45 | 0.125957E+09 | 141.36 | 14-MAR-21:10 | 17.02 | 13.02 |
| April | 0.627576E+10 | 8679.45 | 09-APR-16:41 | 13.68 | 10.37 | 0.122453E+09 | 138.97 | 07-APR-20:49 | 13.68 | 10.37 |
| May | 0.665197E+10 | 8801.11 | 21-MAY-19:31 | 14.80 | 9.13 | 0.136760E+09 | 152.57 | 09-MAY-21:19 | 14.80 | 9.13 |
| June | 0.660930E+10 | 8933.13 | 23-JUN-18:11 | 19.43 | 14.04 | 0.141151E+09 | 144.71 | 06-JUN-20:00 | 19.43 | 14.04 |
| July | 0.717831E+10 | 8710.74 | 09-JUL-16:01 | 22.70 | 18.30 | 0.143452E+09 | 144.70 | 18-JUL-20:30 | 23.60 | 18.96 |
| August | 0.717350E+10 | 8959.72 | 21-AUG-18:11 | 19.80 | 13.99 | 0.144071E+09 | 144.71 | 17-AUG-20:19 | 19.80 | 13.99 |
| September | 0.677378E+10 | 8943.93 | 18-SEP-19:21 | 17.75 | 14.26 | 0.138767E+09 | 162.59 | 18-SEP-21:19 | 15.03 | 11.44 |
| October | 0.678146E+10 | 8725.55 | 11-OCT-16:01 | 21.70 | 14.52 | 0.129999E+09 | 143.18 | 12-OCT-20:30 | 15.85 | 14.35 |
| November | 0.604904E+10 | 8590.98 | 05-NOV-16:11 | 12.43 | 11.47 | 0.122207E+09 | 108.01 | 27-NOV-06:00 | 18.30 | 12.56 |
| December | 0.538500E+10 | 7889.58 | 17-DEC-09:01 | 0.60 | -0.9 | 0.124336E+09 | 71.23 | 12-DEC-05:19 | 0.60 | -0.9 |
| Annual Sum or Average | 0.752021E+11 | 0.156584E+10 | ||||||||
| Minimum of Months | 0.476878E+10 | 7700.35 | -0.9 | -2.2 | 0.112350E+09 | 71.23 | -0.9 | -2.2 | ||
| Maximum of Months | 0.717831E+10 | 8959.72 | 22.70 | 18.30 | 0.144071E+09 | 162.59 | 23.60 | 18.96 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM220_223
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.137709E+10 | 9408.42 | 12-JAN-16:11 | -6.3 | -8.3 | 0.487959E+09 | 284.92 | 24-JAN-04:19 | -11.7 | -13.1 |
| February | 0.115819E+10 | 9516.17 | 05-FEB-09:01 | -11.7 | -12.4 | 0.440420E+09 | 284.93 | 13-FEB-04:19 | -8.9 | -9.5 |
| March | 0.293404E+10 | 9492.46 | 04-MAR-09:01 | -7.7 | -9.2 | 0.498630E+09 | 436.17 | 14-MAR-21:10 | 17.02 | 13.02 |
| April | 0.365096E+10 | 8880.84 | 19-APR-16:41 | 16.78 | 8.91 | 0.484314E+09 | 422.03 | 07-APR-21:10 | 16.78 | 8.91 |
| May | 0.460189E+10 | 8924.72 | 20-MAY-16:21 | 18.90 | 10.91 | 0.521420E+09 | 458.02 | 23-MAY-21:10 | 20.60 | 13.34 |
| June | 0.504300E+10 | 8864.24 | 03-JUN-16:21 | 19.45 | 10.37 | 0.527246E+09 | 439.14 | 29-JUN-21:19 | 20.73 | 18.84 |
| July | 0.588647E+10 | 8668.40 | 06-JUL-16:11 | 22.20 | 13.07 | 0.540855E+09 | 455.34 | 17-JUL-21:19 | 22.20 | 19.60 |
| August | 0.586201E+10 | 8664.04 | 22-AUG-16:01 | 22.70 | 13.33 | 0.542131E+09 | 442.02 | 16-AUG-21:10 | 22.70 | 13.33 |
| September | 0.526490E+10 | 8952.30 | 10-SEP-16:11 | 17.23 | 11.04 | 0.522998E+09 | 464.20 | 13-SEP-21:10 | 22.30 | 18.74 |
| October | 0.453952E+10 | 9102.14 | 30-OCT-16:11 | 15.20 | 9.10 | 0.508941E+09 | 432.86 | 03-OCT-21:10 | 15.20 | 9.10 |
| November | 0.317237E+10 | 8478.38 | 18-NOV-09:01 | 2.38 | 0.04 | 0.482197E+09 | 320.99 | 16-NOV-19:10 | 2.38 | 0.04 |
| December | 0.141110E+10 | 9355.16 | 10-DEC-09:01 | -11.4 | -11.8 | 0.487458E+09 | 284.92 | 26-DEC-05:10 | -12.2 | -13.2 |
| Annual Sum or Average | 0.449015E+11 | 0.604457E+10 | ||||||||
| Minimum of Months | 0.115819E+10 | 8478.38 | -11.7 | -12.4 | 0.440420E+09 | 284.92 | -12.2 | -13.2 | ||
| Maximum of Months | 0.588647E+10 | 9516.17 | 22.70 | 13.33 | 0.542131E+09 | 464.20 | 22.70 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM224
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.123563E+09 | 2558.27 | 12-JAN-16:11 | -6.3 | -8.3 | 0.119877E+09 | 71.24 | 10-JAN-00:30 | -6.3 | -8.3 |
| February | 93932372.09 | 2349.80 | 19-FEB-09:01 | 2.07 | -1.4 | 0.108065E+09 | 71.24 | 07-FEB-05:10 | 2.07 | -1.4 |
| March | 0.531142E+09 | 2515.15 | 04-MAR-09:01 | -7.7 | -9.2 | 0.123625E+09 | 106.86 | 15-MAR-21:10 | 18.53 | 13.66 |
| April | 0.816272E+09 | 2447.71 | 22-APR-16:41 | 15.18 | 6.61 | 0.120569E+09 | 100.80 | 07-APR-21:30 | 15.18 | 6.61 |
| May | 0.122368E+10 | 2479.13 | 27-MAY-19:31 | 17.23 | 9.67 | 0.130007E+09 | 112.53 | 23-MAY-21:10 | 17.23 | 9.67 |
| June | 0.148505E+10 | 2474.38 | 03-JUN-17:41 | 17.98 | 9.93 | 0.131744E+09 | 110.36 | 29-JUN-21:19 | 20.73 | 18.84 |
| July | 0.183959E+10 | 2445.14 | 06-JUL-16:11 | 22.20 | 13.07 | 0.135418E+09 | 114.97 | 17-JUL-21:19 | 22.20 | 19.60 |
| August | 0.182121E+10 | 2442.19 | 22-AUG-16:01 | 22.70 | 13.33 | 0.135733E+09 | 112.22 | 17-AUG-21:40 | 22.70 | 13.33 |
| September | 0.154737E+10 | 2516.46 | 10-SEP-16:11 | 17.23 | 11.04 | 0.130797E+09 | 115.79 | 13-SEP-21:10 | 22.30 | 18.74 |
| October | 0.114747E+10 | 2510.54 | 30-OCT-16:11 | 15.20 | 9.10 | 0.127001E+09 | 106.85 | 12-OCT-21:10 | 15.20 | 9.10 |
| November | 0.665058E+09 | 2322.47 | 18-NOV-09:01 | 2.38 | 0.04 | 0.119819E+09 | 75.45 | 16-NOV-19:10 | 2.38 | 0.04 |
| December | 0.141028E+09 | 2285.49 | 04-DEC-16:12 | -1.1 | -3.7 | 0.119846E+09 | 71.24 | 29-DEC-00:00 | -9.4 | -10.3 |
| Annual Sum or Average | 0.114354E+11 | 0.150250E+10 | ||||||||
| Minimum of Months | 93932372.09 | 2285.49 | -7.7 | -9.2 | 0.108065E+09 | 71.24 | -9.4 | -10.3 | ||
| Maximum of Months | 0.183959E+10 | 2558.27 | 22.70 | 13.33 | 0.135733E+09 | 115.79 | 22.70 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: FRONTSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: FRONTSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: REARSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDORFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 14595251.98 | 462.39 | 15-JAN-16:00 | 5.00 | 1.25 | 0.223401E+09 | 224.39 | 12-JAN-06:10 | 5.00 | 1.25 |
| February | 2217067.30 | 141.14 | 18-FEB-15:25 | 2.50 | 0.26 | 0.202861E+09 | 224.39 | 06-FEB-06:10 | 2.50 | 0.26 |
| March | 0.518779E+09 | 1051.72 | 15-MAR-20:52 | 18.90 | 13.76 | 0.234707E+09 | 285.35 | 16-MAR-06:19 | 11.67 | 10.33 |
| April | 0.106098E+10 | 941.54 | 17-APR-06:59 | -3.3 | -4.7 | 0.234009E+09 | 281.30 | 09-APR-08:00 | -3.3 | -4.7 |
| May | 0.136701E+10 | 1318.08 | 31-MAY-19:22 | 18.85 | 13.19 | 0.276030E+09 | 285.35 | 24-MAY-05:10 | 18.85 | 13.19 |
| June | 0.263000E+10 | 1982.46 | 12-JUN-15:23 | 29.15 | 20.10 | 0.277842E+09 | 285.35 | 05-JUN-05:10 | 29.15 | 20.10 |
| July | 0.349236E+10 | 2032.79 | 19-JUL-15:02 | 30.92 | 22.81 | 0.284111E+09 | 285.35 | 07-JUL-05:19 | 30.92 | 22.81 |
| August | 0.313207E+10 | 2006.91 | 09-AUG-15:23 | 29.40 | 18.31 | 0.288462E+09 | 285.35 | 13-AUG-06:10 | 16.38 | 13.30 |
| September | 0.195178E+10 | 1759.26 | 16-SEP-15:23 | 26.70 | 19.57 | 0.272236E+09 | 285.35 | 23-SEP-06:10 | 12.88 | 11.58 |
| October | 0.118124E+10 | 885.97 | 11-OCT-16:53 | 21.70 | 14.52 | 0.251242E+09 | 285.35 | 12-OCT-08:30 | 15.30 | 13.19 |
| November | 0.651138E+09 | 782.85 | 22-NOV-19:15 | -0.6 | -1.8 | 0.223454E+09 | 277.67 | 05-NOV-08:00 | -0.6 | -1.8 |
| December | 18074390.84 | 502.93 | 16-DEC-15:02 | 4.90 | 2.62 | 0.223408E+09 | 226.74 | 01-DEC-09:00 | 4.90 | 2.62 |
| Annual Sum or Average | 0.160202E+11 | 0.299176E+10 | ||||||||
| Minimum of Months | 2217067.30 | 141.14 | -3.3 | -4.7 | 0.202861E+09 | 224.39 | -3.3 | -4.7 | ||
| Maximum of Months | 0.349236E+10 | 2032.79 | 30.92 | 22.81 | 0.288462E+09 | 285.35 | 30.92 | 22.81 |
Report: ZoneCoolingSummaryMonthly
For: REARSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM301
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 4449068.05 | 229.55 | 27-JAN-15:01 | -2.9 | -5.0 | 0.00 | 0.00 | 01-JAN-00:10 | -2.9 | -5.0 |
| February | 4871163.44 | 266.15 | 10-FEB-15:01 | -5.1 | -7.0 | 0.00 | 0.00 | 01-FEB-00:10 | -5.1 | -7.0 |
| March | 9879038.71 | 248.16 | 03-MAR-15:01 | -3.9 | -6.0 | 0.00 | 0.00 | 01-MAR-00:10 | -3.9 | -6.0 |
| April | 8755032.71 | 204.78 | 16-APR-14:01 | 0.18 | -0.8 | 0.00 | 0.00 | 01-APR-00:10 | 0.18 | -0.8 |
| May | 4236541.76 | 135.22 | 11-MAY-14:01 | 9.32 | 9.05 | 0.00 | 0.00 | 01-MAY-00:10 | 9.32 | 9.05 |
| June | 2704980.10 | 136.35 | 13-JUN-14:01 | 11.20 | 8.28 | 0.00 | 0.00 | 01-JUN-00:10 | 11.20 | 8.28 |
| July | 7618068.74 | 107.21 | 21-JUL-14:02 | 31.52 | 21.93 | 0.00 | 0.00 | 01-JUL-00:10 | 31.52 | 21.93 |
| August | 879521.70 | 49.62 | 31-AUG-14:01 | 16.70 | 13.43 | 0.00 | 0.00 | 01-AUG-00:10 | 16.70 | 13.43 |
| September | 1767878.80 | 93.50 | 28-SEP-15:00 | 11.70 | 10.14 | 0.00 | 0.00 | 01-SEP-00:10 | 11.70 | 10.14 |
| October | 7238480.82 | 183.37 | 23-OCT-14:01 | 5.50 | 4.95 | 0.00 | 0.00 | 01-OCT-00:10 | 5.50 | 4.95 |
| November | 10567017.83 | 190.60 | 28-NOV-15:01 | 2.20 | 0.76 | 0.00 | 0.00 | 01-NOV-00:10 | 2.20 | 0.76 |
| December | 6916392.09 | 266.45 | 25-DEC-15:01 | -5.2 | -6.1 | 0.00 | 0.00 | 01-DEC-00:10 | -5.2 | -6.1 |
| Annual Sum or Average | 69883184.74 | 0.00 | ||||||||
| Minimum of Months | 879521.70 | 49.62 | -5.2 | -7.0 | 0.00 | 0.00 | -5.2 | -7.0 | ||
| Maximum of Months | 10567017.83 | 266.45 | 31.52 | 21.93 | 0.00 | 0.00 | 31.52 | 21.93 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM302_305
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 46386439.52 | 1351.18 | 23-JAN-15:01 | -7.9 | -9.0 | 0.00 | 0.00 | 01-JAN-00:10 | -7.9 | -9.0 |
| February | 54896290.86 | 1378.87 | 05-FEB-15:01 | -8.3 | -9.3 | 0.00 | 0.00 | 01-FEB-00:10 | -8.3 | -9.3 |
| March | 62369083.47 | 1276.08 | 06-MAR-15:01 | -6.7 | -8.9 | 0.00 | 0.00 | 01-MAR-00:10 | -6.7 | -8.9 |
| April | 45847494.97 | 988.79 | 16-APR-14:01 | 0.18 | -0.8 | 0.00 | 0.00 | 01-APR-00:10 | 0.18 | -0.8 |
| May | 25090997.75 | 684.00 | 11-MAY-14:01 | 9.32 | 9.05 | 0.00 | 0.00 | 01-MAY-00:10 | 9.32 | 9.05 |
| June | 11382852.10 | 678.90 | 13-JUN-14:01 | 11.20 | 8.28 | 0.00 | 0.00 | 01-JUN-00:10 | 11.20 | 8.28 |
| July | 12957033.25 | 227.60 | 27-JUL-14:02 | 29.40 | 19.92 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 19.92 |
| August | 3606208.48 | 305.37 | 31-AUG-14:01 | 16.70 | 13.43 | 0.00 | 0.00 | 01-AUG-00:10 | 16.70 | 13.43 |
| September | 13030967.95 | 476.26 | 28-SEP-15:00 | 11.70 | 10.14 | 0.00 | 0.00 | 01-SEP-00:10 | 11.70 | 10.14 |
| October | 38981638.14 | 880.88 | 23-OCT-14:01 | 5.50 | 4.95 | 0.00 | 0.00 | 01-OCT-00:10 | 5.50 | 4.95 |
| November | 54142983.97 | 919.59 | 28-NOV-15:01 | 2.20 | 0.76 | 0.00 | 0.00 | 01-NOV-00:10 | 2.20 | 0.76 |
| December | 52617390.76 | 1243.36 | 25-DEC-15:01 | -5.2 | -6.1 | 0.00 | 0.00 | 01-DEC-00:10 | -5.2 | -6.1 |
| Annual Sum or Average | 0.421309E+09 | 0.00 | ||||||||
| Minimum of Months | 3606208.48 | 227.60 | -8.3 | -9.3 | 0.00 | 0.00 | -8.3 | -9.3 | ||
| Maximum of Months | 62369083.47 | 1378.87 | 29.40 | 19.92 | 0.00 | 0.00 | 29.40 | 19.92 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM306_308
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 60321298.77 | 1242.29 | 31-JAN-15:01 | -11.3 | -12.6 | 0.00 | 0.00 | 01-JAN-00:10 | -11.3 | -12.6 |
| February | 61626167.36 | 1170.98 | 21-FEB-15:01 | -9.5 | -10.9 | 0.00 | 0.00 | 01-FEB-00:10 | -9.5 | -10.9 |
| March | 57233620.79 | 1045.69 | 06-MAR-15:01 | -6.7 | -8.9 | 0.00 | 0.00 | 01-MAR-00:10 | -6.7 | -8.9 |
| April | 38662058.13 | 814.50 | 16-APR-14:01 | 0.18 | -0.8 | 0.00 | 0.00 | 01-APR-00:10 | 0.18 | -0.8 |
| May | 20805841.91 | 554.97 | 11-MAY-14:01 | 9.32 | 9.05 | 0.00 | 0.00 | 01-MAY-00:10 | 9.32 | 9.05 |
| June | 8489334.42 | 539.31 | 13-JUN-14:01 | 11.20 | 8.28 | 0.00 | 0.00 | 01-JUN-00:10 | 11.20 | 8.28 |
| July | 3033312.88 | 262.20 | 27-JUL-14:35 | 29.40 | 19.32 | 0.00 | 0.00 | 01-JUL-00:10 | 29.40 | 19.32 |
| August | 2680018.72 | 245.72 | 31-AUG-14:01 | 16.70 | 13.43 | 0.00 | 0.00 | 01-AUG-00:10 | 16.70 | 13.43 |
| September | 10800890.04 | 389.47 | 28-SEP-15:00 | 11.70 | 10.14 | 0.00 | 0.00 | 01-SEP-00:10 | 11.70 | 10.14 |
| October | 32938330.31 | 714.00 | 23-OCT-14:01 | 5.50 | 4.95 | 0.00 | 0.00 | 01-OCT-00:10 | 5.50 | 4.95 |
| November | 45945882.57 | 755.76 | 28-NOV-15:01 | 2.20 | 0.76 | 0.00 | 0.00 | 01-NOV-00:10 | 2.20 | 0.76 |
| December | 57666233.08 | 1166.15 | 10-DEC-15:01 | -9.6 | -10.6 | 0.00 | 0.00 | 01-DEC-00:10 | -9.6 | -10.6 |
| Annual Sum or Average | 0.400203E+09 | 0.00 | ||||||||
| Minimum of Months | 2680018.72 | 245.72 | -11.3 | -12.6 | 0.00 | 0.00 | -11.3 | -12.6 | ||
| Maximum of Months | 61626167.36 | 1242.29 | 29.40 | 19.32 | 0.00 | 0.00 | 29.40 | 19.32 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM309_312
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.216882E+09 | 6617.08 | 22-JAN-09:01 | 0.00 | -1.7 | 0.473769E+09 | 284.95 | 24-JAN-03:20 | -11.7 | -13.1 |
| February | 0.197226E+09 | 6740.64 | 19-FEB-09:01 | 2.07 | -1.4 | 0.428236E+09 | 284.95 | 06-FEB-00:10 | 2.07 | -1.4 |
| March | 0.108660E+10 | 6790.31 | 25-MAR-08:61 | -3.4 | -4.7 | 0.486930E+09 | 404.39 | 15-MAR-21:00 | -3.4 | -4.7 |
| April | 0.193032E+10 | 6717.72 | 16-APR-08:61 | -2.9 | -4.2 | 0.479599E+09 | 386.06 | 07-APR-21:00 | -2.9 | -4.2 |
| May | 0.332690E+10 | 6890.05 | 27-MAY-20:01 | 16.52 | 9.66 | 0.522363E+09 | 442.36 | 16-MAY-21:10 | 16.52 | 9.66 |
| June | 0.433582E+10 | 6957.91 | 03-JUN-17:01 | 18.72 | 10.09 | 0.529716E+09 | 437.11 | 26-JUN-21:40 | 21.87 | 19.58 |
| July | 0.518081E+10 | 6638.67 | 06-JUL-16:41 | 22.20 | 13.15 | 0.543135E+09 | 454.78 | 07-JUL-21:19 | 19.23 | 15.13 |
| August | 0.473773E+10 | 6516.29 | 03-AUG-20:31 | 22.07 | 14.63 | 0.543354E+09 | 459.23 | 02-AUG-21:10 | 22.07 | 14.63 |
| September | 0.347447E+10 | 6491.85 | 02-SEP-19:31 | 13.53 | 9.92 | 0.524121E+09 | 447.97 | 15-SEP-21:10 | 21.60 | 20.41 |
| October | 0.219700E+10 | 6054.73 | 17-OCT-08:61 | -0.0 | -1.3 | 0.504181E+09 | 413.83 | 11-OCT-21:19 | -0.0 | -1.3 |
| November | 0.118659E+10 | 6491.75 | 18-NOV-09:01 | 2.38 | 0.04 | 0.472207E+09 | 284.92 | 25-NOV-05:00 | -1.7 | -2.5 |
| December | 0.283118E+09 | 6686.71 | 23-DEC-09:01 | 0.68 | -2.0 | 0.474727E+09 | 284.95 | 27-DEC-01:30 | -11.9 | -12.3 |
| Annual Sum or Average | 0.281535E+11 | 0.598234E+10 | ||||||||
| Minimum of Months | 0.197226E+09 | 6054.73 | -3.4 | -4.7 | 0.428236E+09 | 284.92 | -11.9 | -13.1 | ||
| Maximum of Months | 0.518081E+10 | 6957.91 | 22.20 | 14.63 | 0.543354E+09 | 459.23 | 22.07 | 20.41 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM313
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 7134284.86 | 278.03 | 03-JAN-15:01 | -6.1 | -7.5 | 0.00 | 0.00 | 01-JAN-00:10 | -6.1 | -7.5 |
| February | 8291303.30 | 303.48 | 05-FEB-15:01 | -8.3 | -9.3 | 0.00 | 0.00 | 01-FEB-00:10 | -8.3 | -9.3 |
| March | 11530174.16 | 257.06 | 04-MAR-15:01 | -4.9 | -6.7 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.7 |
| April | 8111316.25 | 203.12 | 16-APR-14:01 | 0.18 | -0.8 | 0.00 | 0.00 | 01-APR-00:10 | 0.18 | -0.8 |
| May | 3526454.26 | 132.81 | 11-MAY-14:01 | 9.32 | 9.05 | 0.00 | 0.00 | 01-MAY-00:10 | 9.32 | 9.05 |
| June | 1064910.34 | 127.43 | 13-JUN-14:01 | 11.20 | 8.28 | 0.00 | 0.00 | 01-JUN-00:10 | 11.20 | 8.28 |
| July | 69244.64 | 31.23 | 21-JUL-14:02 | 31.52 | 21.93 | 0.00 | 0.00 | 01-JUL-00:10 | 31.52 | 21.93 |
| August | 221748.72 | 38.43 | 31-AUG-14:01 | 16.70 | 13.43 | 0.00 | 0.00 | 01-AUG-00:10 | 16.70 | 13.43 |
| September | 1265102.31 | 86.87 | 28-SEP-15:00 | 11.70 | 10.14 | 0.00 | 0.00 | 01-SEP-00:10 | 11.70 | 10.14 |
| October | 6929121.39 | 183.93 | 23-OCT-14:01 | 5.50 | 4.95 | 0.00 | 0.00 | 01-OCT-00:10 | 5.50 | 4.95 |
| November | 10562700.32 | 192.68 | 28-NOV-15:01 | 2.20 | 0.76 | 0.00 | 0.00 | 01-NOV-00:10 | 2.20 | 0.76 |
| December | 9772296.03 | 269.67 | 25-DEC-15:01 | -5.2 | -6.1 | 0.00 | 0.00 | 01-DEC-00:10 | -5.2 | -6.1 |
| Annual Sum or Average | 68478656.57 | 0.00 | ||||||||
| Minimum of Months | 69244.64 | 31.23 | -8.3 | -9.3 | 0.00 | 0.00 | -8.3 | -9.3 | ||
| Maximum of Months | 11530174.16 | 303.48 | 31.52 | 21.93 | 0.00 | 0.00 | 31.52 | 21.93 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM314
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 43789533.64 | 2048.27 | 16-JAN-09:01 | -0.9 | -2.2 | 0.118219E+09 | 71.24 | 24-JAN-02:39 | -11.5 | -12.9 |
| February | 35393804.78 | 2149.75 | 28-FEB-16:12 | 0.20 | -2.5 | 0.106698E+09 | 71.24 | 06-FEB-01:10 | 0.20 | -2.5 |
| March | 0.347314E+09 | 2241.63 | 26-MAR-18:02 | -3.0 | -5.6 | 0.122283E+09 | 106.86 | 14-MAR-21:10 | -3.0 | -5.6 |
| April | 0.609498E+09 | 2309.37 | 22-APR-16:41 | 15.18 | 6.61 | 0.119798E+09 | 100.84 | 07-APR-21:30 | 15.18 | 6.61 |
| May | 0.108954E+10 | 2347.18 | 27-MAY-19:31 | 17.23 | 9.67 | 0.129845E+09 | 114.33 | 23-MAY-21:10 | 17.23 | 9.67 |
| June | 0.145798E+10 | 2337.22 | 03-JUN-17:41 | 17.98 | 9.93 | 0.131806E+09 | 112.30 | 29-JUN-21:19 | 20.73 | 18.84 |
| July | 0.184320E+10 | 2301.80 | 06-JUL-16:11 | 22.20 | 13.07 | 0.135517E+09 | 117.52 | 17-JUL-21:19 | 22.20 | 19.60 |
| August | 0.177028E+10 | 2297.84 | 22-AUG-16:01 | 22.70 | 13.33 | 0.135684E+09 | 113.42 | 17-AUG-21:40 | 22.70 | 13.33 |
| September | 0.137558E+10 | 2365.56 | 10-SEP-16:11 | 17.23 | 11.04 | 0.130506E+09 | 115.77 | 13-SEP-21:10 | 22.30 | 18.74 |
| October | 0.797069E+09 | 2264.31 | 30-OCT-16:11 | 15.20 | 9.10 | 0.126145E+09 | 106.85 | 11-OCT-21:10 | 15.20 | 9.10 |
| November | 0.341086E+09 | 2087.10 | 18-NOV-09:01 | 2.38 | 0.04 | 0.118290E+09 | 72.06 | 16-NOV-19:10 | 2.38 | 0.04 |
| December | 46247159.06 | 2048.75 | 17-DEC-09:01 | 0.60 | -0.9 | 0.118195E+09 | 71.24 | 27-DEC-03:30 | -11.7 | -12.1 |
| Annual Sum or Average | 0.975698E+10 | 0.149299E+10 | ||||||||
| Minimum of Months | 35393804.78 | 2048.27 | -3.0 | -5.6 | 0.106698E+09 | 71.24 | -11.7 | -12.9 | ||
| Maximum of Months | 0.184320E+10 | 2365.56 | 22.70 | 13.33 | 0.135684E+09 | 117.52 | 22.70 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM315_318
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.245085E+10 | 10282.97 | 24-JAN-09:01 | -11.5 | -13.0 | 0.492589E+09 | 284.92 | 07-JAN-04:49 | -11.5 | -13.0 |
| February | 0.212702E+10 | 10366.31 | 05-FEB-09:01 | -11.7 | -12.4 | 0.444790E+09 | 284.92 | 12-FEB-04:49 | 0.60 | -0.7 |
| March | 0.434517E+10 | 10254.41 | 04-MAR-09:01 | -7.7 | -9.2 | 0.500672E+09 | 468.29 | 14-MAR-21:10 | 17.02 | 13.02 |
| April | 0.503054E+10 | 9707.11 | 19-APR-16:41 | 16.78 | 8.91 | 0.485780E+09 | 454.23 | 07-APR-21:10 | 16.78 | 8.91 |
| May | 0.611363E+10 | 9817.16 | 19-MAY-16:11 | 14.80 | 9.31 | 0.525364E+09 | 490.07 | 23-MAY-21:10 | 20.60 | 13.34 |
| June | 0.660880E+10 | 9913.71 | 05-JUN-16:21 | 17.50 | 11.34 | 0.533060E+09 | 470.81 | 06-JUN-21:10 | 18.03 | 12.50 |
| July | 0.756985E+10 | 9761.21 | 06-JUL-17:01 | 22.38 | 13.26 | 0.546023E+09 | 484.57 | 17-JUL-21:19 | 22.20 | 19.60 |
| August | 0.745644E+10 | 9706.39 | 22-AUG-16:51 | 22.20 | 13.51 | 0.547242E+09 | 470.17 | 17-AUG-21:40 | 22.20 | 13.51 |
| September | 0.663068E+10 | 9801.74 | 10-SEP-16:11 | 17.23 | 11.04 | 0.527745E+09 | 492.77 | 13-SEP-21:10 | 22.30 | 18.74 |
| October | 0.564552E+10 | 9830.96 | 30-OCT-16:11 | 15.20 | 9.10 | 0.510597E+09 | 459.83 | 03-OCT-21:10 | 15.20 | 9.10 |
| November | 0.410486E+10 | 9261.27 | 26-NOV-17:51 | 15.00 | 9.60 | 0.483753E+09 | 329.11 | 16-NOV-19:10 | 15.00 | 9.60 |
| December | 0.239055E+10 | 10232.68 | 26-DEC-09:01 | -12.7 | -13.9 | 0.491842E+09 | 284.92 | 20-DEC-02:00 | -12.7 | -13.9 |
| Annual Sum or Average | 0.604739E+11 | 0.608946E+10 | ||||||||
| Minimum of Months | 0.212702E+10 | 9261.27 | -12.7 | -13.9 | 0.444790E+09 | 284.92 | -12.7 | -13.9 | ||
| Maximum of Months | 0.756985E+10 | 10366.31 | 22.38 | 13.51 | 0.547242E+09 | 492.77 | 22.30 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: ELEVATORCOREFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM319
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 30595537.48 | 424.10 | 31-JAN-15:01 | -11.3 | -12.6 | 0.00 | 0.00 | 01-JAN-00:10 | -11.3 | -12.6 |
| February | 28644850.49 | 442.17 | 06-FEB-15:01 | -13.3 | -13.7 | 0.00 | 0.00 | 01-FEB-00:10 | -13.3 | -13.7 |
| March | 24651656.81 | 402.72 | 06-MAR-15:01 | -6.7 | -8.9 | 0.00 | 0.00 | 01-MAR-00:10 | -6.7 | -8.9 |
| April | 14105609.92 | 280.47 | 16-APR-14:01 | 0.18 | -0.8 | 0.00 | 0.00 | 01-APR-00:10 | 0.18 | -0.8 |
| May | 12447558.68 | 161.45 | 11-MAY-14:01 | 9.32 | 9.05 | 0.00 | 0.00 | 01-MAY-00:10 | 9.32 | 9.05 |
| June | 64707089.69 | 198.64 | 12-JUN-13:30 | 30.00 | 19.98 | 0.00 | 0.00 | 01-JUN-00:10 | 30.00 | 19.98 |
| July | 0.129529E+09 | 226.05 | 29-JUL-13:40 | 25.77 | 21.38 | 0.00 | 0.00 | 01-JUL-00:10 | 25.77 | 21.38 |
| August | 0.136453E+09 | 291.39 | 18-AUG-13:50 | 29.90 | 20.91 | 0.00 | 0.00 | 01-AUG-00:10 | 29.90 | 20.91 |
| September | 94433209.12 | 383.27 | 21-SEP-14:00 | 25.60 | 16.62 | 0.00 | 0.00 | 01-SEP-00:10 | 25.60 | 16.62 |
| October | 22603203.35 | 252.10 | 11-OCT-14:25 | 22.20 | 14.37 | 0.00 | 0.00 | 01-OCT-00:10 | 22.20 | 14.37 |
| November | 16812524.28 | 242.82 | 28-NOV-15:01 | 2.20 | 0.76 | 0.00 | 0.00 | 01-NOV-00:10 | 2.20 | 0.76 |
| December | 29259248.26 | 425.16 | 10-DEC-15:01 | -9.6 | -10.6 | 0.00 | 0.00 | 01-DEC-00:10 | -9.6 | -10.6 |
| Annual Sum or Average | 0.604242E+09 | 0.00 | ||||||||
| Minimum of Months | 12447558.68 | 161.45 | -13.3 | -13.7 | 0.00 | 0.00 | -13.3 | -13.7 | ||
| Maximum of Months | 0.136453E+09 | 442.17 | 30.00 | 21.38 | 0.00 | 0.00 | 30.00 | 21.38 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM320_323
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.826112E+09 | 9081.13 | 12-JAN-16:11 | -6.3 | -8.3 | 0.483738E+09 | 284.93 | 26-JAN-05:10 | -7.3 | -9.0 |
| February | 0.736505E+09 | 9001.11 | 05-FEB-09:01 | -11.7 | -12.4 | 0.436831E+09 | 284.94 | 07-FEB-05:10 | -15.7 | -16.1 |
| March | 0.226054E+10 | 9006.72 | 04-MAR-09:01 | -7.7 | -9.2 | 0.496520E+09 | 433.31 | 14-MAR-21:10 | 17.02 | 13.02 |
| April | 0.295645E+10 | 8507.97 | 19-APR-16:41 | 16.78 | 8.91 | 0.482944E+09 | 417.23 | 07-APR-21:10 | 16.78 | 8.91 |
| May | 0.406293E+10 | 8554.66 | 20-MAY-16:21 | 18.90 | 10.91 | 0.520346E+09 | 458.87 | 23-MAY-21:10 | 20.60 | 13.34 |
| June | 0.471499E+10 | 8510.23 | 03-JUN-16:21 | 19.45 | 10.37 | 0.526121E+09 | 437.66 | 29-JUN-21:19 | 20.73 | 18.84 |
| July | 0.558464E+10 | 8293.40 | 06-JUL-16:11 | 22.20 | 13.07 | 0.539780E+09 | 456.56 | 17-JUL-21:19 | 22.20 | 19.60 |
| August | 0.546541E+10 | 8276.90 | 22-AUG-16:01 | 22.70 | 13.33 | 0.540753E+09 | 440.64 | 15-AUG-21:10 | 22.70 | 13.33 |
| September | 0.468412E+10 | 8560.13 | 10-SEP-16:11 | 17.23 | 11.04 | 0.521464E+09 | 461.15 | 13-SEP-21:10 | 22.30 | 18.74 |
| October | 0.350806E+10 | 8677.42 | 30-OCT-16:11 | 15.20 | 9.10 | 0.507338E+09 | 427.42 | 11-OCT-21:10 | 15.20 | 9.10 |
| November | 0.217387E+10 | 8091.61 | 18-NOV-09:01 | 2.38 | 0.04 | 0.478916E+09 | 306.32 | 16-NOV-19:10 | 2.38 | 0.04 |
| December | 0.816068E+09 | 8717.07 | 11-DEC-16:11 | -9.6 | -10.2 | 0.482880E+09 | 284.93 | 07-DEC-02:49 | -9.6 | -10.2 |
| Annual Sum or Average | 0.377897E+11 | 0.601763E+10 | ||||||||
| Minimum of Months | 0.736505E+09 | 8091.61 | -11.7 | -12.4 | 0.436831E+09 | 284.93 | -15.7 | -16.1 | ||
| Maximum of Months | 0.558464E+10 | 9081.13 | 22.70 | 13.33 | 0.540753E+09 | 461.15 | 22.70 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM324
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 28401648.22 | 400.98 | 31-JAN-15:01 | -11.3 | -12.6 | 0.00 | 0.00 | 01-JAN-00:10 | -11.3 | -12.6 |
| February | 26388163.72 | 419.38 | 06-FEB-15:01 | -13.3 | -13.7 | 0.00 | 0.00 | 01-FEB-00:10 | -13.3 | -13.7 |
| March | 21019551.01 | 385.32 | 06-MAR-15:01 | -6.7 | -8.9 | 0.00 | 0.00 | 01-MAR-00:10 | -6.7 | -8.9 |
| April | 13198860.36 | 264.71 | 16-APR-14:01 | 0.18 | -0.8 | 0.00 | 0.00 | 01-APR-00:10 | 0.18 | -0.8 |
| May | 6225649.55 | 157.99 | 11-MAY-14:01 | 9.32 | 9.05 | 0.00 | 0.00 | 01-MAY-00:10 | 9.32 | 9.05 |
| June | 2203504.36 | 150.88 | 13-JUN-14:01 | 11.20 | 8.28 | 0.00 | 0.00 | 01-JUN-00:10 | 11.20 | 8.28 |
| July | 2749339.10 | 96.14 | 25-JUL-14:06 | 27.30 | 17.69 | 0.00 | 0.00 | 01-JUL-00:10 | 27.30 | 17.69 |
| August | 7593781.82 | 98.67 | 18-AUG-14:02 | 30.00 | 20.99 | 0.00 | 0.00 | 01-AUG-00:10 | 30.00 | 20.99 |
| September | 8292228.07 | 163.33 | 21-SEP-14:01 | 25.68 | 16.62 | 0.00 | 0.00 | 01-SEP-00:10 | 25.68 | 16.62 |
| October | 11976568.35 | 217.91 | 23-OCT-14:01 | 5.50 | 4.95 | 0.00 | 0.00 | 01-OCT-00:10 | 5.50 | 4.95 |
| November | 15727595.92 | 234.48 | 28-NOV-15:01 | 2.20 | 0.76 | 0.00 | 0.00 | 01-NOV-00:10 | 2.20 | 0.76 |
| December | 27101702.79 | 402.59 | 10-DEC-15:01 | -9.6 | -10.6 | 0.00 | 0.00 | 01-DEC-00:10 | -9.6 | -10.6 |
| Annual Sum or Average | 0.170879E+09 | 0.00 | ||||||||
| Minimum of Months | 2203504.36 | 96.14 | -13.3 | -13.7 | 0.00 | 0.00 | -13.3 | -13.7 | ||
| Maximum of Months | 28401648.22 | 419.38 | 30.00 | 20.99 | 0.00 | 0.00 | 30.00 | 20.99 |
Report: ZoneCoolingSummaryMonthly
For: FRONTSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: FRONTSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: REARSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: CORRIDORFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 2492931.77 | 282.63 | 15-JAN-14:50 | 5.50 | 1.71 | 0.223405E+09 | 224.40 | 26-JAN-06:10 | -7.8 | -9.4 |
| February | 2652255.95 | 636.62 | 28-FEB-13:25 | 0.00 | -2.9 | 0.202865E+09 | 224.40 | 07-FEB-07:10 | 0.00 | -2.9 |
| March | 0.229265E+09 | 2028.02 | 15-MAR-14:13 | 25.93 | 16.12 | 0.232589E+09 | 280.66 | 15-MAR-08:00 | 25.93 | 16.12 |
| April | 0.525743E+09 | 1419.05 | 09-APR-15:02 | 16.02 | 11.18 | 0.228955E+09 | 266.70 | 08-APR-08:00 | 16.02 | 11.18 |
| May | 0.146896E+10 | 2535.91 | 14-MAY-14:40 | 25.73 | 17.96 | 0.262748E+09 | 285.35 | 28-MAY-07:19 | 17.97 | 13.51 |
| June | 0.292601E+10 | 3335.31 | 12-JUN-14:00 | 30.60 | 20.23 | 0.271882E+09 | 285.35 | 27-JUN-05:10 | 21.20 | 19.66 |
| July | 0.378696E+10 | 3427.63 | 21-JUL-13:50 | 31.52 | 21.79 | 0.282386E+09 | 285.35 | 17-JUL-05:10 | 31.52 | 21.79 |
| August | 0.322404E+10 | 3438.20 | 09-AUG-15:02 | 29.40 | 18.17 | 0.285046E+09 | 285.35 | 08-AUG-05:10 | 29.40 | 18.17 |
| September | 0.186265E+10 | 2811.72 | 16-SEP-14:00 | 27.20 | 19.82 | 0.260173E+09 | 285.35 | 14-SEP-05:10 | 27.20 | 19.82 |
| October | 0.494014E+09 | 1636.35 | 11-OCT-16:02 | 21.70 | 14.52 | 0.240186E+09 | 268.06 | 22-OCT-08:00 | 17.80 | 11.66 |
| November | 95228618.83 | 502.16 | 18-NOV-14:00 | 5.00 | 1.95 | 0.220497E+09 | 272.05 | 05-NOV-08:00 | 5.00 | 1.95 |
| December | 4011073.54 | 446.98 | 16-DEC-14:00 | 5.60 | 2.84 | 0.223405E+09 | 224.40 | 11-DEC-06:10 | 5.60 | 2.84 |
| Annual Sum or Average | 0.146220E+11 | 0.293414E+10 | ||||||||
| Minimum of Months | 2492931.77 | 282.63 | 0.00 | -2.9 | 0.202865E+09 | 224.40 | -7.8 | -9.4 | ||
| Maximum of Months | 0.378696E+10 | 3438.20 | 31.52 | 21.79 | 0.285046E+09 | 285.35 | 31.52 | 21.79 |
Report: ZoneCoolingSummaryMonthly
For: REARSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM401
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 1066506.57 | 584.67 | 17-JAN-09:03 | 7.38 | 3.03 | 0.116089E+09 | 71.25 | 31-JAN-00:10 | -10.8 | -11.8 |
| February | 973161.93 | 605.84 | 22-FEB-19:03 | 12.70 | 6.24 | 0.104930E+09 | 71.25 | 07-FEB-03:20 | 12.70 | 6.24 |
| March | 79008338.76 | 2152.00 | 15-MAR-19:21 | 21.10 | 14.63 | 0.118895E+09 | 99.43 | 15-MAR-21:00 | 16.70 | 13.08 |
| April | 0.161675E+09 | 2341.55 | 22-APR-17:11 | 14.63 | 6.44 | 0.117835E+09 | 88.49 | 07-APR-21:00 | 14.63 | 6.44 |
| May | 0.606673E+09 | 2468.41 | 21-MAY-19:31 | 14.80 | 9.13 | 0.130219E+09 | 109.54 | 16-MAY-21:10 | 14.80 | 9.13 |
| June | 0.123512E+10 | 2501.31 | 24-JUN-16:21 | 23.05 | 14.64 | 0.132831E+09 | 109.66 | 26-JUN-21:40 | 21.87 | 19.58 |
| July | 0.172941E+10 | 2492.79 | 06-JUL-16:21 | 22.20 | 13.10 | 0.135949E+09 | 113.24 | 24-JUL-21:19 | 20.93 | 17.61 |
| August | 0.144238E+10 | 2522.65 | 01-AUG-16:11 | 23.90 | 14.79 | 0.135834E+09 | 115.77 | 17-AUG-21:10 | 20.32 | 13.80 |
| September | 0.693757E+09 | 2409.39 | 02-SEP-17:31 | 17.40 | 10.40 | 0.130478E+09 | 109.80 | 15-SEP-21:10 | 21.60 | 20.41 |
| October | 0.143690E+09 | 2135.14 | 25-OCT-20:11 | 14.03 | 11.39 | 0.123082E+09 | 95.90 | 11-OCT-21:10 | 14.03 | 11.39 |
| November | 20296448.64 | 1797.85 | 27-NOV-09:51 | 11.70 | 9.09 | 0.114126E+09 | 71.24 | 24-NOV-04:10 | 11.70 | 9.09 |
| December | 1359639.65 | 545.99 | 15-DEC-19:05 | 2.20 | 1.30 | 0.116117E+09 | 71.25 | 11-DEC-05:00 | 2.20 | 1.30 |
| Annual Sum or Average | 0.611541E+10 | 0.147638E+10 | ||||||||
| Minimum of Months | 973161.93 | 545.99 | 2.20 | 1.30 | 0.104930E+09 | 71.24 | -10.8 | -11.8 | ||
| Maximum of Months | 0.172941E+10 | 2522.65 | 23.90 | 14.79 | 0.135949E+09 | 115.77 | 21.87 | 20.41 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM402_405
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 7754646.16 | 738.59 | 01-JAN-15:01 | 0.60 | -0.1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.60 | -0.1 |
| February | 14360740.88 | 1097.39 | 10-FEB-15:01 | -5.1 | -7.0 | 0.00 | 0.00 | 01-FEB-00:10 | -5.1 | -7.0 |
| March | 44591292.77 | 1035.42 | 05-MAR-15:01 | -4.1 | -6.3 | 0.00 | 0.00 | 01-MAR-00:10 | -4.1 | -6.3 |
| April | 43830822.66 | 889.43 | 16-APR-14:01 | 0.18 | -0.8 | 0.00 | 0.00 | 01-APR-00:10 | 0.18 | -0.8 |
| May | 31896186.45 | 557.61 | 11-MAY-14:01 | 9.32 | 9.05 | 0.00 | 0.00 | 01-MAY-00:10 | 9.32 | 9.05 |
| June | 0.242905E+09 | 1150.24 | 27-JUN-13:20 | 29.47 | 23.48 | 0.00 | 0.00 | 01-JUN-00:10 | 29.47 | 23.48 |
| July | 0.463013E+09 | 1339.03 | 21-JUL-13:40 | 31.33 | 21.85 | 0.00 | 0.00 | 01-JUL-00:10 | 31.33 | 21.85 |
| August | 0.281314E+09 | 1081.54 | 09-AUG-14:00 | 29.40 | 18.10 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.10 |
| September | 25028456.70 | 482.02 | 16-SEP-13:40 | 27.20 | 19.70 | 0.00 | 0.00 | 01-SEP-00:10 | 27.20 | 19.70 |
| October | 31960608.75 | 718.40 | 23-OCT-14:01 | 5.50 | 4.95 | 0.00 | 0.00 | 01-OCT-00:10 | 5.50 | 4.95 |
| November | 36396116.91 | 722.52 | 28-NOV-15:01 | 2.20 | 0.76 | 0.00 | 0.00 | 01-NOV-00:10 | 2.20 | 0.76 |
| December | 10799579.21 | 799.55 | 03-DEC-15:01 | -0.5 | -1.0 | 0.00 | 0.00 | 01-DEC-00:10 | -0.5 | -1.0 |
| Annual Sum or Average | 0.123385E+10 | 0.00 | ||||||||
| Minimum of Months | 7754646.16 | 482.02 | -5.1 | -7.0 | 0.00 | 0.00 | -5.1 | -7.0 | ||
| Maximum of Months | 0.463013E+09 | 1339.03 | 31.33 | 23.48 | 0.00 | 0.00 | 31.33 | 23.48 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM406_408
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 10626329.08 | 662.40 | 21-JAN-15:01 | -1.1 | -3.2 | 0.00 | 0.00 | 01-JAN-00:10 | -1.1 | -3.2 |
| February | 17980045.07 | 891.14 | 10-FEB-15:01 | -5.1 | -7.0 | 0.00 | 0.00 | 01-FEB-00:10 | -5.1 | -7.0 |
| March | 40924214.10 | 935.80 | 06-MAR-15:01 | -6.7 | -8.9 | 0.00 | 0.00 | 01-MAR-00:10 | -6.7 | -8.9 |
| April | 36244693.18 | 724.71 | 16-APR-14:01 | 0.18 | -0.8 | 0.00 | 0.00 | 01-APR-00:10 | 0.18 | -0.8 |
| May | 25270672.60 | 451.75 | 11-MAY-14:01 | 9.32 | 9.05 | 0.00 | 0.00 | 01-MAY-00:10 | 9.32 | 9.05 |
| June | 0.174863E+09 | 860.62 | 27-JUN-13:20 | 29.47 | 23.48 | 0.00 | 0.00 | 01-JUN-00:10 | 29.47 | 23.48 |
| July | 0.330105E+09 | 990.87 | 21-JUL-13:40 | 31.33 | 21.85 | 0.00 | 0.00 | 01-JUL-00:10 | 31.33 | 21.85 |
| August | 0.199964E+09 | 808.73 | 09-AUG-14:00 | 29.40 | 18.10 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.10 |
| September | 18855606.93 | 356.41 | 16-SEP-13:50 | 27.20 | 19.76 | 0.00 | 0.00 | 01-SEP-00:10 | 27.20 | 19.76 |
| October | 26804108.54 | 582.54 | 23-OCT-14:01 | 5.50 | 4.95 | 0.00 | 0.00 | 01-OCT-00:10 | 5.50 | 4.95 |
| November | 33130391.47 | 592.64 | 28-NOV-15:01 | 2.20 | 0.76 | 0.00 | 0.00 | 01-NOV-00:10 | 2.20 | 0.76 |
| December | 15400222.58 | 671.35 | 31-DEC-15:01 | -1.2 | -2.9 | 0.00 | 0.00 | 01-DEC-00:10 | -1.2 | -2.9 |
| Annual Sum or Average | 0.930168E+09 | 0.00 | ||||||||
| Minimum of Months | 10626329.08 | 356.41 | -6.7 | -8.9 | 0.00 | 0.00 | -6.7 | -8.9 | ||
| Maximum of Months | 0.330105E+09 | 990.87 | 31.33 | 23.48 | 0.00 | 0.00 | 31.33 | 23.48 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM409_412
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 60842847.44 | 6123.23 | 14-JAN-09:01 | 3.90 | 2.95 | 0.468498E+09 | 284.97 | 24-JAN-00:49 | -11.1 | -12.0 |
| February | 61111026.33 | 7062.71 | 22-FEB-19:02 | 12.70 | 6.24 | 0.423879E+09 | 284.97 | 09-FEB-00:20 | 12.70 | 6.24 |
| March | 0.675165E+09 | 8114.23 | 28-MAR-18:02 | 5.40 | -0.5 | 0.484991E+09 | 415.09 | 15-MAR-20:40 | 5.40 | -0.5 |
| April | 0.135783E+10 | 9031.49 | 22-APR-17:11 | 14.63 | 6.44 | 0.480504E+09 | 400.89 | 07-APR-20:40 | 14.63 | 6.44 |
| May | 0.289725E+10 | 9354.34 | 20-MAY-17:41 | 16.88 | 10.94 | 0.526517E+09 | 454.54 | 16-MAY-21:10 | 16.88 | 10.94 |
| June | 0.432565E+10 | 9299.95 | 06-JUN-16:31 | 23.30 | 14.16 | 0.533672E+09 | 440.04 | 26-JUN-21:40 | 21.87 | 19.58 |
| July | 0.549564E+10 | 9301.80 | 06-JUL-16:21 | 22.20 | 13.10 | 0.544395E+09 | 457.46 | 24-JUL-21:19 | 20.93 | 17.61 |
| August | 0.478861E+10 | 9316.74 | 01-AUG-16:11 | 23.90 | 14.79 | 0.545004E+09 | 468.71 | 17-AUG-21:10 | 20.32 | 13.80 |
| September | 0.294358E+10 | 9225.93 | 02-SEP-17:31 | 17.40 | 10.40 | 0.527352E+09 | 447.25 | 15-SEP-21:10 | 21.60 | 20.41 |
| October | 0.133568E+10 | 8042.02 | 25-OCT-20:11 | 14.03 | 11.39 | 0.504622E+09 | 418.63 | 11-OCT-21:19 | 14.03 | 11.39 |
| November | 0.520530E+09 | 7829.72 | 12-NOV-09:01 | 2.30 | -0.5 | 0.467938E+09 | 292.47 | 16-NOV-19:10 | 11.32 | 9.55 |
| December | 82177639.46 | 7368.75 | 02-DEC-09:01 | 4.32 | 2.08 | 0.469311E+09 | 284.97 | 26-DEC-01:39 | -11.5 | -12.6 |
| Annual Sum or Average | 0.245441E+11 | 0.597668E+10 | ||||||||
| Minimum of Months | 60842847.44 | 6123.23 | 2.30 | -0.5 | 0.423879E+09 | 284.97 | -11.5 | -12.6 | ||
| Maximum of Months | 0.549564E+10 | 9354.34 | 23.90 | 14.79 | 0.545004E+09 | 468.71 | 21.87 | 20.41 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM413
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 1350008.36 | 147.89 | 01-JAN-15:01 | 0.60 | -0.1 | 0.00 | 0.00 | 01-JAN-00:10 | 0.60 | -0.1 |
| February | 2004933.73 | 156.03 | 28-FEB-15:01 | 0.10 | -2.7 | 0.00 | 0.00 | 01-FEB-00:10 | 0.10 | -2.7 |
| March | 7202236.76 | 181.73 | 26-MAR-14:12 | -0.8 | -4.2 | 0.00 | 0.00 | 01-MAR-00:10 | -0.8 | -4.2 |
| April | 7047528.76 | 169.58 | 16-APR-14:01 | 0.18 | -0.8 | 0.00 | 0.00 | 01-APR-00:10 | 0.18 | -0.8 |
| May | 3093879.36 | 98.11 | 11-MAY-14:01 | 9.32 | 9.05 | 0.00 | 0.00 | 01-MAY-00:10 | 9.32 | 9.05 |
| June | 35401376.32 | 258.02 | 12-JUN-14:30 | 30.30 | 20.11 | 0.00 | 0.00 | 01-JUN-00:10 | 30.30 | 20.11 |
| July | 81086394.92 | 326.75 | 21-JUL-13:50 | 31.52 | 21.79 | 0.00 | 0.00 | 01-JUL-00:10 | 31.52 | 21.79 |
| August | 46012103.35 | 245.65 | 09-AUG-15:12 | 29.40 | 18.24 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.24 |
| September | 1903697.48 | 74.94 | 16-SEP-14:00 | 27.20 | 19.82 | 0.00 | 0.00 | 01-SEP-00:10 | 27.20 | 19.82 |
| October | 4943167.39 | 139.89 | 23-OCT-14:01 | 5.50 | 4.95 | 0.00 | 0.00 | 01-OCT-00:10 | 5.50 | 4.95 |
| November | 6518449.65 | 140.34 | 28-NOV-15:01 | 2.20 | 0.76 | 0.00 | 0.00 | 01-NOV-00:10 | 2.20 | 0.76 |
| December | 1749729.84 | 132.44 | 17-DEC-15:01 | 1.60 | 0.33 | 0.00 | 0.00 | 01-DEC-00:10 | 1.60 | 0.33 |
| Annual Sum or Average | 0.198314E+09 | 0.00 | ||||||||
| Minimum of Months | 1350008.36 | 74.94 | -0.8 | -4.2 | 0.00 | 0.00 | -0.8 | -4.2 | ||
| Maximum of Months | 81086394.92 | 326.75 | 31.52 | 21.79 | 0.00 | 0.00 | 31.52 | 21.79 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM414
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 15822280.54 | 345.62 | 30-JAN-15:01 | -9.0 | -10.4 | 0.00 | 0.00 | 01-JAN-00:10 | -9.0 | -10.4 |
| February | 16769241.13 | 344.13 | 08-FEB-15:01 | -7.8 | -9.2 | 0.00 | 0.00 | 01-FEB-00:10 | -7.8 | -9.2 |
| March | 21127673.20 | 346.18 | 06-MAR-15:01 | -6.7 | -8.9 | 0.00 | 0.00 | 01-MAR-00:10 | -6.7 | -8.9 |
| April | 11812650.70 | 223.86 | 16-APR-14:01 | 0.18 | -0.8 | 0.00 | 0.00 | 01-APR-00:10 | 0.18 | -0.8 |
| May | 21552449.48 | 239.44 | 14-MAY-14:15 | 25.37 | 18.05 | 0.00 | 0.00 | 01-MAY-00:10 | 25.37 | 18.05 |
| June | 87014240.22 | 440.82 | 12-JUN-13:30 | 30.00 | 19.98 | 0.00 | 0.00 | 01-JUN-00:10 | 30.00 | 19.98 |
| July | 0.174688E+09 | 522.41 | 21-JUL-13:30 | 31.15 | 21.91 | 0.00 | 0.00 | 01-JUL-00:10 | 31.15 | 21.91 |
| August | 0.164017E+09 | 559.23 | 09-AUG-13:40 | 29.23 | 18.12 | 0.00 | 0.00 | 01-AUG-00:10 | 29.23 | 18.12 |
| September | 73146714.40 | 556.86 | 21-SEP-13:40 | 25.40 | 16.58 | 0.00 | 0.00 | 01-SEP-00:10 | 25.40 | 16.58 |
| October | 15684741.13 | 313.04 | 11-OCT-12:40 | 22.03 | 13.91 | 0.00 | 0.00 | 01-OCT-00:10 | 22.03 | 13.91 |
| November | 10942055.39 | 198.79 | 18-NOV-15:01 | 5.00 | 2.10 | 0.00 | 0.00 | 01-NOV-00:10 | 5.00 | 2.10 |
| December | 13917414.21 | 351.85 | 10-DEC-15:01 | -9.6 | -10.6 | 0.00 | 0.00 | 01-DEC-00:10 | -9.6 | -10.6 |
| Annual Sum or Average | 0.626494E+09 | 0.00 | ||||||||
| Minimum of Months | 10942055.39 | 198.79 | -9.6 | -10.6 | 0.00 | 0.00 | -9.6 | -10.6 | ||
| Maximum of Months | 0.174688E+09 | 559.23 | 31.15 | 21.91 | 0.00 | 0.00 | 31.15 | 21.91 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM415_418
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.409228E+09 | 10840.48 | 12-JAN-16:11 | -6.3 | -8.3 | 0.479536E+09 | 284.95 | 10-JAN-00:20 | -6.3 | -8.3 |
| February | 0.439069E+09 | 10452.05 | 28-FEB-16:12 | 0.20 | -2.5 | 0.433903E+09 | 284.95 | 07-FEB-05:10 | 0.20 | -2.5 |
| March | 0.180389E+10 | 10922.48 | 06-MAR-16:11 | -6.9 | -9.1 | 0.495655E+09 | 441.81 | 14-MAR-21:10 | 17.02 | 13.02 |
| April | 0.263371E+10 | 10988.31 | 19-APR-16:21 | 16.95 | 8.85 | 0.483292E+09 | 430.50 | 07-APR-21:10 | 16.95 | 8.85 |
| May | 0.402951E+10 | 11130.04 | 22-MAY-16:21 | 17.20 | 10.93 | 0.523431E+09 | 470.35 | 23-MAY-21:10 | 20.60 | 13.34 |
| June | 0.509867E+10 | 11133.28 | 05-JUN-16:21 | 17.50 | 11.34 | 0.530216E+09 | 449.62 | 06-JUN-21:10 | 18.03 | 12.50 |
| July | 0.626681E+10 | 10822.12 | 06-JUL-17:01 | 22.38 | 13.26 | 0.542161E+09 | 464.41 | 17-JUL-21:19 | 22.20 | 19.60 |
| August | 0.590640E+10 | 10795.72 | 01-AUG-16:51 | 23.90 | 14.79 | 0.543045E+09 | 444.41 | 15-AUG-21:10 | 18.30 | 17.90 |
| September | 0.458248E+10 | 10782.84 | 05-SEP-17:02 | 19.13 | 12.64 | 0.523950E+09 | 474.37 | 13-SEP-21:10 | 22.30 | 18.74 |
| October | 0.290325E+10 | 10793.06 | 30-OCT-16:11 | 15.20 | 9.10 | 0.507583E+09 | 433.60 | 03-OCT-21:10 | 15.20 | 9.10 |
| November | 0.148930E+10 | 9965.86 | 18-NOV-09:01 | 2.38 | 0.04 | 0.476925E+09 | 317.05 | 16-NOV-19:10 | 2.38 | 0.04 |
| December | 0.433689E+09 | 10461.20 | 11-DEC-16:11 | -9.6 | -10.2 | 0.478614E+09 | 284.95 | 28-DEC-01:49 | -10.5 | -11.0 |
| Annual Sum or Average | 0.359960E+11 | 0.601831E+10 | ||||||||
| Minimum of Months | 0.409228E+09 | 9965.86 | -9.6 | -10.2 | 0.433903E+09 | 284.95 | -10.5 | -11.0 | ||
| Maximum of Months | 0.626681E+10 | 11133.28 | 23.90 | 14.79 | 0.543045E+09 | 474.37 | 22.30 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: ELEVATORCOREFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM419
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 72001516.43 | 2841.55 | 12-JAN-16:11 | -6.3 | -8.3 | 0.119279E+09 | 71.24 | 10-JAN-00:10 | -6.3 | -8.3 |
| February | 75885661.02 | 2715.69 | 28-FEB-16:12 | 0.20 | -2.5 | 0.107903E+09 | 71.24 | 07-FEB-05:10 | 0.20 | -2.5 |
| March | 0.433894E+09 | 2867.32 | 06-MAR-16:11 | -6.9 | -9.1 | 0.123543E+09 | 109.43 | 14-MAR-21:10 | 17.02 | 13.02 |
| April | 0.696931E+09 | 2864.37 | 22-APR-16:21 | 15.55 | 6.87 | 0.120609E+09 | 105.66 | 07-APR-21:30 | 15.55 | 6.87 |
| May | 0.115811E+10 | 2929.96 | 22-MAY-16:21 | 17.20 | 10.93 | 0.130765E+09 | 117.48 | 23-MAY-21:10 | 20.60 | 13.34 |
| June | 0.150409E+10 | 2930.71 | 05-JUN-16:21 | 17.50 | 11.34 | 0.132558E+09 | 112.95 | 06-JUN-21:10 | 18.03 | 12.50 |
| July | 0.186644E+10 | 2865.23 | 06-JUL-17:01 | 22.38 | 13.26 | 0.135551E+09 | 116.60 | 17-JUL-21:19 | 22.20 | 19.60 |
| August | 0.175366E+10 | 2856.84 | 01-AUG-16:51 | 23.90 | 14.79 | 0.135786E+09 | 111.79 | 17-AUG-21:40 | 19.47 | 13.80 |
| September | 0.133286E+10 | 2858.48 | 05-SEP-17:02 | 19.13 | 12.64 | 0.131053E+09 | 118.17 | 13-SEP-21:10 | 22.30 | 18.74 |
| October | 0.787441E+09 | 2859.60 | 30-OCT-16:11 | 15.20 | 9.10 | 0.126722E+09 | 106.85 | 12-OCT-21:10 | 15.20 | 9.10 |
| November | 0.360494E+09 | 2591.16 | 18-NOV-09:01 | 2.38 | 0.04 | 0.118862E+09 | 76.47 | 16-NOV-19:10 | 2.38 | 0.04 |
| December | 79645892.93 | 2643.04 | 04-DEC-16:12 | -1.1 | -3.7 | 0.119090E+09 | 71.24 | 29-DEC-00:30 | -9.4 | -10.3 |
| Annual Sum or Average | 0.101215E+11 | 0.150172E+10 | ||||||||
| Minimum of Months | 72001516.43 | 2591.16 | -6.9 | -9.1 | 0.107903E+09 | 71.24 | -9.4 | -10.3 | ||
| Maximum of Months | 0.186644E+10 | 2930.71 | 23.90 | 14.79 | 0.135786E+09 | 118.17 | 22.30 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM420_423
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.319290E+09 | 10720.48 | 12-JAN-16:11 | -6.3 | -8.3 | 0.477806E+09 | 284.95 | 09-JAN-02:49 | -6.3 | -8.3 |
| February | 0.346000E+09 | 10237.53 | 28-FEB-16:12 | 0.20 | -2.5 | 0.432348E+09 | 284.96 | 07-FEB-05:10 | 0.20 | -2.5 |
| March | 0.153283E+10 | 10803.34 | 06-MAR-16:11 | -6.9 | -9.1 | 0.494457E+09 | 432.76 | 14-MAR-21:10 | 17.02 | 13.02 |
| April | 0.231463E+10 | 10798.35 | 19-APR-16:21 | 16.95 | 8.85 | 0.482485E+09 | 421.17 | 07-APR-21:30 | 16.95 | 8.85 |
| May | 0.364334E+10 | 10875.17 | 22-MAY-16:21 | 17.20 | 10.93 | 0.522165E+09 | 463.39 | 23-MAY-21:10 | 20.60 | 13.34 |
| June | 0.467680E+10 | 10926.77 | 05-JUN-16:21 | 17.50 | 11.34 | 0.528532E+09 | 440.35 | 06-JUN-21:10 | 18.03 | 12.50 |
| July | 0.579894E+10 | 10647.11 | 06-JUL-17:01 | 22.38 | 13.26 | 0.540765E+09 | 456.37 | 17-JUL-21:19 | 22.20 | 19.60 |
| August | 0.544782E+10 | 10651.56 | 01-AUG-16:51 | 23.90 | 14.79 | 0.541551E+09 | 437.38 | 16-AUG-21:10 | 20.92 | 15.81 |
| September | 0.417060E+10 | 10644.58 | 10-SEP-16:11 | 17.23 | 11.04 | 0.522294E+09 | 466.63 | 13-SEP-21:10 | 22.30 | 18.74 |
| October | 0.255580E+10 | 10659.31 | 30-OCT-16:11 | 15.20 | 9.10 | 0.506445E+09 | 427.41 | 12-OCT-21:10 | 15.20 | 9.10 |
| November | 0.124682E+10 | 9835.30 | 18-NOV-09:01 | 2.38 | 0.04 | 0.475496E+09 | 309.08 | 16-NOV-19:10 | 2.38 | 0.04 |
| December | 0.341328E+09 | 10166.83 | 11-DEC-16:11 | -9.6 | -10.2 | 0.476985E+09 | 284.95 | 08-DEC-03:00 | -9.6 | -10.2 |
| Annual Sum or Average | 0.323942E+11 | 0.600133E+10 | ||||||||
| Minimum of Months | 0.319290E+09 | 9835.30 | -9.6 | -10.2 | 0.432348E+09 | 284.95 | -9.6 | -10.2 | ||
| Maximum of Months | 0.579894E+10 | 10926.77 | 23.90 | 14.79 | 0.541551E+09 | 466.63 | 22.30 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: GUESTROOM424
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 20324242.30 | 2395.57 | 15-JAN-16:12 | 4.63 | 1.05 | 0.117394E+09 | 71.25 | 24-JAN-05:10 | -11.8 | -13.0 |
| February | 19797925.61 | 2658.19 | 28-FEB-16:12 | 0.20 | -2.5 | 0.106174E+09 | 71.25 | 06-FEB-01:30 | 0.20 | -2.5 |
| March | 0.240273E+09 | 2752.65 | 01-MAR-16:12 | 1.30 | -1.8 | 0.122115E+09 | 106.86 | 15-MAR-21:10 | 18.53 | 13.66 |
| April | 0.469111E+09 | 2867.62 | 19-APR-16:41 | 16.78 | 8.91 | 0.119798E+09 | 101.38 | 07-APR-21:30 | 16.78 | 8.91 |
| May | 0.929278E+09 | 2896.62 | 19-MAY-16:11 | 14.80 | 9.31 | 0.130200E+09 | 115.56 | 23-MAY-21:10 | 20.60 | 13.34 |
| June | 0.136872E+10 | 2927.61 | 24-JUN-17:01 | 23.30 | 14.84 | 0.132163E+09 | 111.77 | 29-JUN-21:19 | 20.73 | 18.84 |
| July | 0.181732E+10 | 2912.09 | 06-JUL-17:01 | 22.38 | 13.26 | 0.135400E+09 | 116.69 | 17-JUL-21:19 | 22.20 | 19.60 |
| August | 0.168350E+10 | 2907.32 | 01-AUG-16:51 | 23.90 | 14.79 | 0.135589E+09 | 112.17 | 17-AUG-21:40 | 19.47 | 13.80 |
| September | 0.118376E+10 | 2903.46 | 10-SEP-16:11 | 17.23 | 11.04 | 0.130649E+09 | 116.59 | 13-SEP-21:10 | 22.30 | 18.74 |
| October | 0.562156E+09 | 2934.13 | 30-OCT-16:11 | 15.20 | 9.10 | 0.125896E+09 | 106.83 | 11-OCT-21:19 | 15.20 | 9.10 |
| November | 0.185577E+09 | 2530.27 | 03-NOV-15:12 | 9.63 | 5.30 | 0.117573E+09 | 72.26 | 16-NOV-19:10 | 11.32 | 9.55 |
| December | 19802618.74 | 2276.65 | 16-DEC-16:12 | 4.03 | 2.10 | 0.117443E+09 | 71.25 | 11-DEC-01:30 | 4.03 | 2.10 |
| Annual Sum or Average | 0.849962E+10 | 0.149039E+10 | ||||||||
| Minimum of Months | 19797925.61 | 2276.65 | 0.20 | -2.5 | 0.106174E+09 | 71.25 | -11.8 | -13.0 | ||
| Maximum of Months | 0.181732E+10 | 2934.13 | 23.90 | 14.84 | 0.135589E+09 | 116.69 | 22.30 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: FRONTSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneCoolingSummaryMonthly
For: FRONTSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 | -6.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 | 0.00 | 0.00 | 01-APR-00:10 | 4.10 | 3.72 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 | 6.11 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 | 14.04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 | 13.50 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 | 16.93 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 | 12.90 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 | 12.28 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 | 4.43 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -4.9 | -6.9 | 0.00 | 0.00 | -4.9 | -6.9 | ||
| Maximum of Months | 0.00 | 0.00 | 18.85 | 16.93 | 0.00 | 0.00 | 18.85 | 16.93 |
Report: ZoneHeatingSummaryMonthly
For: REARSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 10455127.03 | 6.27 | 22-JAN-16:45 | 0.60 |
| February | 9433439.05 | 6.67 | 05-FEB-14:35 | -8.3 |
| March | 10447795.10 | 5.71 | 26-MAR-21:35 | -4.8 |
| April | 10122455.59 | 5.61 | 10-APR-01:45 | 5.15 |
| May | 10466847.31 | 5.20 | 14-MAY-16:42 | 17.58 |
| June | 10146716.75 | 4.98 | 06-JUN-22:40 | 15.57 |
| July | 10482068.03 | 5.16 | 02-JUL-22:25 | 15.85 |
| August | 10497114.36 | 5.15 | 30-AUG-15:55 | 16.70 |
| September | 10137248.38 | 5.31 | 25-SEP-22:40 | 18.33 |
| October | 10462794.89 | 5.28 | 31-OCT-19:40 | 10.00 |
| November | 10119523.86 | 5.49 | 28-NOV-05:30 | 3.85 |
| December | 10425444.57 | 6.07 | 04-DEC-05:35 | -1.9 |
| Annual Sum or Average | 0.123197E+09 | |||
| Minimum of Months | 9433439.05 | 4.98 | -8.3 | |
| Maximum of Months | 10497114.36 | 6.67 | 18.33 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDORFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.326154E+10 | 29497.58 | 06-JAN-07:02 | -12.4 |
| February | 0.325750E+10 | 28590.73 | 07-FEB-07:02 | -16.5 |
| March | 0.192537E+10 | 27590.04 | 04-MAR-07:02 | -10.4 |
| April | 0.833868E+09 | 22098.78 | 17-APR-06:03 | -4.2 |
| May | 0.241817E+09 | 9845.11 | 01-MAY-06:05 | 2.35 |
| June | 93610829.78 | 2625.01 | 14-JUN-06:02 | 7.67 |
| July | 29990888.85 | 1743.13 | 03-JUL-06:02 | 12.77 |
| August | 63337753.80 | 1944.16 | 31-AUG-06:02 | 11.78 |
| September | 0.136468E+09 | 3942.45 | 30-SEP-06:10 | 7.30 |
| October | 0.493051E+09 | 17073.04 | 17-OCT-06:04 | -2.8 |
| November | 0.874052E+09 | 16136.77 | 25-NOV-07:04 | -1.5 |
| December | 0.285027E+10 | 28132.92 | 08-DEC-07:02 | -10.4 |
| Annual Sum or Average | 0.140609E+11 | |||
| Minimum of Months | 29990888.85 | 1743.13 | -16.5 | |
| Maximum of Months | 0.326154E+10 | 29497.58 | 12.77 |
Report: ZoneHeatingSummaryMonthly
For: REARSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: FRONTLOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 94675921.46 | 11451.65 | 31-JAN-20:12 | -12.2 |
| February | 0.168292E+09 | 10844.11 | 06-FEB-11:18 | -14.6 |
| March | 48876881.08 | 10550.67 | 01-MAR-02:20 | -6.5 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 67619718.94 | 10561.77 | 07-DEC-24:00 | -6.7 |
| Annual Sum or Average | 0.379465E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -14.6 | |
| Maximum of Months | 0.168292E+09 | 11451.65 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: RESTROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.107803E+09 | 46.55 | 23-JAN-18:35 | -9.8 |
| February | 0.102541E+09 | 46.55 | 07-FEB-10:35 | -13.5 |
| March | 73300561.60 | 46.03 | 03-MAR-18:35 | -5.9 |
| April | 17033748.63 | 45.27 | 16-APR-01:00 | 2.20 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 1883811.47 | 43.09 | 25-NOV-05:00 | -1.7 |
| December | 88966405.42 | 47.55 | 27-DEC-10:35 | -9.8 |
| Annual Sum or Average | 0.391528E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -13.5 | |
| Maximum of Months | 0.107803E+09 | 47.55 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: MEETINGROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.422289E+09 | 5866.07 | 12-JAN-11:23 | -8.3 |
| February | 0.481383E+09 | 5757.91 | 21-FEB-10:07 | -11.5 |
| March | 0.209739E+09 | 4282.47 | 06-MAR-15:01 | -6.7 |
| April | 12673874.74 | 3574.18 | 17-APR-14:01 | 6.70 |
| May | 367996.41 | 747.33 | 11-MAY-17:01 | 8.90 |
| June | 1261777.88 | 1022.62 | 12-JUN-15:01 | 29.72 |
| July | 1858741.99 | 1199.69 | 19-JUL-15:01 | 30.92 |
| August | 1884628.39 | 1050.03 | 18-AUG-15:01 | 29.90 |
| September | 332268.75 | 558.31 | 21-SEP-14:02 | 25.68 |
| October | 2997779.49 | 3072.66 | 17-OCT-14:01 | 8.98 |
| November | 9600238.41 | 3417.66 | 24-NOV-15:01 | 4.90 |
| December | 0.296501E+09 | 5687.92 | 11-DEC-10:42 | -12.4 |
| Annual Sum or Average | 0.144089E+10 | |||
| Minimum of Months | 332268.75 | 558.31 | -12.4 | |
| Maximum of Months | 0.481383E+09 | 5866.07 | 30.92 |
Report: ZoneHeatingSummaryMonthly
For: MECHANICALROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM101
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 480796.24 | 78.50 | 15-MAR-14:01 | 26.02 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 741593.42 | 77.53 | 10-MAY-14:01 | 26.10 |
| June | 2243431.01 | 116.06 | 12-JUN-14:01 | 30.50 |
| July | 4574835.17 | 124.87 | 21-JUL-14:01 | 31.52 |
| August | 3924872.04 | 109.43 | 10-AUG-14:01 | 30.50 |
| September | 636415.52 | 56.57 | 16-SEP-14:01 | 27.12 |
| October | 36586.10 | 11.63 | 11-OCT-14:01 | 22.20 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 12638529.49 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 4574835.17 | 124.87 | 31.52 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM102
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 523492.83 | 85.14 | 15-MAR-14:01 | 26.02 |
| April | 7012.56 | 5.23 | 07-APR-14:01 | 19.72 |
| May | 926768.45 | 84.51 | 10-MAY-14:01 | 26.10 |
| June | 2636309.77 | 122.91 | 12-JUN-14:01 | 30.50 |
| July | 5471262.27 | 132.74 | 21-JUL-14:01 | 31.52 |
| August | 4702518.40 | 116.87 | 10-AUG-14:01 | 30.50 |
| September | 804506.58 | 63.53 | 16-SEP-14:01 | 27.12 |
| October | 82786.17 | 18.88 | 11-OCT-14:01 | 22.20 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 15154657.03 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 5471262.27 | 132.74 | 31.52 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM103
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.697773E+09 | 1843.43 | 11-JAN-16:12 | 11.50 |
| February | 0.789228E+09 | 1854.90 | 22-FEB-16:12 | 10.97 |
| March | 0.413833E+09 | 1813.97 | 08-MAR-16:12 | 7.03 |
| April | 68627711.05 | 1778.59 | 18-APR-08:61 | 6.02 |
| May | 3648838.17 | 808.91 | 02-MAY-08:03 | 11.65 |
| June | 4177788.83 | 475.03 | 15-JUN-08:05 | 14.60 |
| July | 4661793.12 | 253.58 | 06-JUL-18:21 | 22.20 |
| August | 3477276.51 | 248.51 | 17-AUG-20:01 | 21.52 |
| September | 2646933.72 | 330.06 | 29-SEP-08:05 | 10.68 |
| October | 2044514.94 | 736.80 | 15-OCT-15:15 | 8.53 |
| November | 9267369.55 | 1178.90 | 30-NOV-16:12 | 3.90 |
| December | 0.520570E+09 | 1762.24 | 23-DEC-16:12 | 4.40 |
| Annual Sum or Average | 0.251996E+10 | |||
| Minimum of Months | 2044514.94 | 248.51 | 3.90 | |
| Maximum of Months | 0.789228E+09 | 1854.90 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM104
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.147448E+09 | 1959.73 | 26-JAN-16:12 | -3.5 |
| February | 0.229480E+09 | 2038.02 | 22-FEB-09:01 | 1.28 |
| March | 35431832.54 | 1136.23 | 29-MAR-08:02 | 1.47 |
| April | 6217744.34 | 1055.40 | 16-APR-08:02 | -2.9 |
| May | 2460471.00 | 919.07 | 05-MAY-08:04 | 13.07 |
| June | 4835330.83 | 431.89 | 14-JUN-08:04 | 11.20 |
| July | 6323414.17 | 339.57 | 05-JUL-16:21 | 23.60 |
| August | 3800986.18 | 285.71 | 15-AUG-16:21 | 21.40 |
| September | 2443552.48 | 322.65 | 01-SEP-08:05 | 14.08 |
| October | 1001815.80 | 753.87 | 24-OCT-08:04 | 2.30 |
| November | 3230595.46 | 1197.49 | 21-NOV-09:03 | 3.22 |
| December | 0.118203E+09 | 1974.74 | 29-DEC-16:11 | -2.8 |
| Annual Sum or Average | 0.560877E+09 | |||
| Minimum of Months | 1001815.80 | 285.71 | -3.5 | |
| Maximum of Months | 0.229480E+09 | 2038.02 | 23.60 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM105
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 4182691.99 | 1737.27 | 09-JAN-09:03 | -8.8 |
| February | 3981379.28 | 1700.79 | 09-FEB-09:03 | -6.6 |
| March | 2917939.68 | 728.79 | 06-MAR-16:14 | -6.9 |
| April | 2145730.40 | 610.30 | 12-APR-15:15 | 10.00 |
| May | 2053517.84 | 690.08 | 13-MAY-08:04 | 14.18 |
| June | 4138117.59 | 553.40 | 15-JUN-08:04 | 14.60 |
| July | 6230233.42 | 367.02 | 17-JUL-18:41 | 23.90 |
| August | 4112628.47 | 300.05 | 27-AUG-16:11 | 22.93 |
| September | 2650655.41 | 567.49 | 29-SEP-08:04 | 10.68 |
| October | 1189219.28 | 564.46 | 02-OCT-08:04 | 10.18 |
| November | 2096902.26 | 532.39 | 30-NOV-16:15 | 3.90 |
| December | 4057400.21 | 1676.57 | 12-DEC-09:03 | -8.7 |
| Annual Sum or Average | 39756415.82 | |||
| Minimum of Months | 1189219.28 | 300.05 | -8.8 | |
| Maximum of Months | 6230233.42 | 1737.27 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: EMPLOYEELOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: LAUNDRYROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: ELEVATORCOREFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: EXERCISECENTERFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 6625381.06 | 2068.70 | 30-JAN-01:14 | -10.0 |
| February | 16925978.49 | 2034.77 | 21-FEB-02:43 | -11.0 |
| March | 371255.67 | 2033.04 | 06-MAR-05:23 | -11.1 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 4017127.69 | 2071.09 | 12-DEC-05:03 | -9.9 |
| Annual Sum or Average | 27939742.92 | |||
| Minimum of Months | 0.00 | 0.00 | -11.1 | |
| Maximum of Months | 16925978.49 | 2071.09 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: FRONTOFFICEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 21301567.05 | 5965.41 | 26-JAN-15:01 | -3.8 |
| February | 77479484.85 | 6023.07 | 26-FEB-15:01 | -2.9 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 118209.63 | 286.29 | 17-JUN-10:01 | 25.50 |
| July | 162753.29 | 488.66 | 16-JUL-10:01 | 28.80 |
| August | 164038.23 | 387.45 | 05-AUG-10:01 | 27.30 |
| September | 25852.74 | 186.12 | 16-SEP-10:01 | 24.27 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 13420974.98 | 5882.23 | 09-DEC-15:01 | -5.8 |
| Annual Sum or Average | 0.112673E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -5.8 | |
| Maximum of Months | 77479484.85 | 6023.07 | 28.80 |
Report: ZoneHeatingSummaryMonthly
For: FRONTSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 46215147.58 | 27.05 | 11-JAN-18:55 | 6.10 |
| February | 54758409.08 | 283.13 | 07-FEB-10:53 | -13.3 |
| March | 46110526.41 | 24.05 | 05-MAR-00:30 | -6.7 |
| April | 44668609.31 | 24.58 | 10-APR-01:45 | 5.15 |
| May | 46139743.08 | 22.56 | 14-MAY-16:42 | 17.58 |
| June | 44687903.58 | 21.01 | 04-JUN-04:40 | 6.87 |
| July | 46206383.39 | 21.63 | 11-JUL-19:50 | 23.95 |
| August | 46254284.45 | 23.10 | 30-AUG-15:55 | 16.70 |
| September | 44679430.95 | 22.55 | 25-SEP-22:40 | 18.33 |
| October | 46199635.45 | 22.93 | 31-OCT-19:50 | 9.45 |
| November | 44725458.21 | 24.33 | 10-NOV-12:00 | 10.60 |
| December | 46095045.85 | 26.21 | 04-DEC-05:35 | -1.9 |
| Annual Sum or Average | 0.556741E+09 | |||
| Minimum of Months | 44668609.31 | 21.01 | -13.3 | |
| Maximum of Months | 54758409.08 | 283.13 | 23.95 |
Report: ZoneHeatingSummaryMonthly
For: FRONTSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: REARSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 10455300.64 | 6.42 | 22-JAN-16:45 | 0.60 |
| February | 9929872.63 | 85.42 | 07-FEB-10:45 | -13.4 |
| March | 10440310.23 | 6.10 | 26-MAR-21:35 | -4.8 |
| April | 10111259.50 | 5.89 | 24-APR-06:45 | 2.52 |
| May | 10470588.55 | 5.82 | 03-MAY-00:40 | 8.50 |
| June | 10167442.98 | 5.21 | 06-JUN-22:40 | 15.57 |
| July | 10493816.68 | 5.60 | 02-JUL-23:00 | 15.00 |
| August | 10507347.54 | 5.17 | 30-AUG-15:55 | 16.70 |
| September | 10148235.26 | 5.65 | 02-SEP-21:40 | 11.10 |
| October | 10469964.58 | 5.42 | 31-OCT-19:40 | 10.00 |
| November | 10123169.32 | 5.79 | 28-NOV-05:30 | 3.85 |
| December | 10420632.72 | 6.51 | 04-DEC-05:35 | -1.9 |
| Annual Sum or Average | 0.123738E+09 | |||
| Minimum of Months | 9929872.63 | 5.17 | -13.4 | |
| Maximum of Months | 10507347.54 | 85.42 | 16.70 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDORFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 3026887.53 | 285.59 | 24-JAN-05:00 | -11.7 |
| February | 71734900.78 | 1328.94 | 07-FEB-17:44 | -4.6 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 3622347.49 | 1294.17 | 28-DEC-12:10 | -9.9 |
| Annual Sum or Average | 78384135.79 | |||
| Minimum of Months | 0.00 | 0.00 | -11.7 | |
| Maximum of Months | 71734900.78 | 1328.94 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: REARSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM201
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 6578673.99 | 162.96 | 24-JAN-06:00 | -12.2 |
| February | 37747970.48 | 377.11 | 21-FEB-15:35 | -9.8 |
| March | 682050.53 | 81.86 | 14-MAR-14:01 | 24.90 |
| April | 14955.62 | 11.43 | 07-APR-14:01 | 19.72 |
| May | 851602.81 | 82.65 | 10-MAY-14:01 | 26.10 |
| June | 1303005.42 | 66.51 | 26-JUN-14:01 | 27.30 |
| July | 1582614.07 | 118.15 | 15-JUL-14:01 | 30.68 |
| August | 2140901.36 | 106.42 | 13-AUG-14:01 | 30.00 |
| September | 966373.93 | 64.22 | 16-SEP-14:01 | 27.12 |
| October | 216602.01 | 35.94 | 11-OCT-14:01 | 22.20 |
| November | 2534.57 | 1.93 | 04-NOV-15:00 | 18.30 |
| December | 13239854.18 | 361.84 | 26-DEC-15:30 | -9.4 |
| Annual Sum or Average | 65327138.97 | |||
| Minimum of Months | 2534.57 | 1.93 | -12.2 | |
| Maximum of Months | 37747970.48 | 377.11 | 30.68 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM202_205
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.876858E+09 | 6503.87 | 13-JAN-16:12 | 2.80 |
| February | 0.864762E+09 | 6494.66 | 22-FEB-09:01 | 1.28 |
| March | 0.320645E+09 | 6426.64 | 01-MAR-16:12 | 1.30 |
| April | 12069906.01 | 3715.85 | 13-APR-08:03 | 3.80 |
| May | 3122235.80 | 2169.98 | 08-MAY-08:04 | 7.38 |
| June | 4483236.22 | 1016.11 | 24-JUN-18:21 | 22.75 |
| July | 6010895.53 | 1006.71 | 06-JUL-18:21 | 22.20 |
| August | 4941287.96 | 986.65 | 23-AUG-18:21 | 21.40 |
| September | 4745338.48 | 1466.95 | 28-SEP-08:05 | 12.20 |
| October | 6309549.70 | 3009.28 | 27-OCT-08:04 | 5.68 |
| November | 25046855.14 | 3840.27 | 23-NOV-09:03 | 0.68 |
| December | 0.727685E+09 | 6447.14 | 13-DEC-16:12 | 2.80 |
| Annual Sum or Average | 0.285668E+10 | |||
| Minimum of Months | 3122235.80 | 986.65 | 0.68 | |
| Maximum of Months | 0.876858E+09 | 6503.87 | 22.75 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM206_208
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.358488E+09 | 5022.33 | 10-JAN-16:12 | -0.6 |
| February | 0.382484E+09 | 5000.13 | 09-FEB-16:11 | -1.9 |
| March | 0.105605E+09 | 5009.77 | 07-MAR-16:11 | -1.9 |
| April | 4240536.11 | 3154.56 | 05-APR-08:03 | 3.58 |
| May | 2130036.16 | 931.98 | 12-MAY-08:05 | 10.10 |
| June | 3788669.27 | 896.34 | 15-JUN-08:05 | 14.60 |
| July | 5263826.11 | 797.05 | 06-JUL-18:21 | 22.20 |
| August | 4268288.29 | 785.51 | 23-AUG-18:21 | 21.40 |
| September | 3882638.61 | 1066.19 | 05-SEP-08:05 | 11.75 |
| October | 3507560.18 | 2696.74 | 17-OCT-08:03 | -0.0 |
| November | 7076077.63 | 3055.65 | 03-NOV-08:03 | 2.98 |
| December | 0.304664E+09 | 5012.33 | 29-DEC-16:11 | -2.8 |
| Annual Sum or Average | 0.118540E+10 | |||
| Minimum of Months | 2130036.16 | 785.51 | -2.8 | |
| Maximum of Months | 0.382484E+09 | 5022.33 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM209_212
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.266791E+09 | 6128.58 | 10-JAN-16:12 | -0.6 |
| February | 0.305053E+09 | 6109.39 | 09-FEB-16:11 | -1.9 |
| March | 82197207.14 | 6117.74 | 07-MAR-16:11 | -1.9 |
| April | 5350362.89 | 3588.19 | 17-APR-08:03 | -0.8 |
| May | 3039840.48 | 1513.38 | 12-MAY-08:05 | 10.10 |
| June | 4801804.13 | 1137.90 | 15-JUN-08:05 | 14.60 |
| July | 6852704.10 | 993.16 | 06-JUL-18:21 | 22.20 |
| August | 5325583.65 | 956.09 | 23-AUG-18:21 | 21.40 |
| September | 4751168.19 | 1450.57 | 29-SEP-08:05 | 10.68 |
| October | 4327208.44 | 2975.54 | 18-OCT-08:04 | 5.78 |
| November | 9807626.69 | 3945.39 | 24-NOV-09:03 | -1.5 |
| December | 0.225364E+09 | 6123.23 | 29-DEC-16:11 | -2.8 |
| Annual Sum or Average | 0.923662E+09 | |||
| Minimum of Months | 3039840.48 | 956.09 | -2.8 | |
| Maximum of Months | 0.305053E+09 | 6128.58 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM213
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.775243E+09 | 1854.70 | 11-JAN-16:12 | 11.50 |
| February | 0.787414E+09 | 1865.23 | 22-FEB-16:12 | 10.97 |
| March | 0.343274E+09 | 1814.19 | 08-MAR-16:12 | 7.03 |
| April | 43513314.89 | 1772.75 | 17-APR-15:12 | 6.33 |
| May | 1849633.63 | 621.98 | 01-MAY-15:15 | 14.07 |
| June | 2174811.13 | 268.00 | 09-JUN-08:05 | 14.18 |
| July | 2568411.47 | 230.29 | 08-JUL-21:01 | 20.50 |
| August | 2136475.54 | 253.40 | 31-AUG-08:05 | 13.90 |
| September | 2235551.88 | 550.30 | 29-SEP-08:04 | 10.68 |
| October | 4925150.17 | 756.25 | 20-OCT-08:03 | 6.88 |
| November | 66159364.48 | 1756.96 | 30-NOV-16:12 | 3.90 |
| December | 0.692182E+09 | 1791.89 | 23-DEC-16:12 | 4.40 |
| Annual Sum or Average | 0.272368E+10 | |||
| Minimum of Months | 1849633.63 | 230.29 | 3.90 | |
| Maximum of Months | 0.787414E+09 | 1865.23 | 20.50 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM214
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 69173083.13 | 2013.97 | 24-JAN-09:01 | -11.5 |
| February | 0.115222E+09 | 2070.85 | 13-FEB-09:01 | -8.9 |
| March | 6318178.40 | 1176.27 | 23-MAR-08:03 | -0.2 |
| April | 2501283.23 | 1124.02 | 13-APR-08:03 | 3.80 |
| May | 1784568.93 | 631.19 | 10-MAY-08:04 | 15.55 |
| June | 2513134.52 | 513.56 | 06-JUN-08:04 | 13.68 |
| July | 3461182.12 | 326.26 | 17-JUL-18:41 | 23.90 |
| August | 2358200.39 | 250.93 | 27-AUG-16:11 | 22.93 |
| September | 1927818.56 | 537.25 | 28-SEP-08:04 | 12.20 |
| October | 2044218.69 | 615.62 | 14-OCT-15:15 | 5.40 |
| November | 2636085.47 | 1022.86 | 21-NOV-09:03 | 3.22 |
| December | 80946209.16 | 2086.99 | 29-DEC-16:11 | -2.8 |
| Annual Sum or Average | 0.290886E+09 | |||
| Minimum of Months | 1784568.93 | 250.93 | -11.5 | |
| Maximum of Months | 0.115222E+09 | 2086.99 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM215_218
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: ELEVATORCOREFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM219
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 2011772.21 | 1309.60 | 26-JAN-09:02 | -6.0 |
| February | 1888097.63 | 1560.48 | 07-FEB-09:02 | -15.3 |
| March | 1790329.79 | 1112.51 | 20-MAR-08:02 | -2.7 |
| April | 1400502.84 | 1024.69 | 17-APR-08:02 | -0.8 |
| May | 2265921.57 | 714.67 | 20-MAY-18:02 | 16.70 |
| June | 3423479.15 | 730.92 | 26-JUN-08:32 | 22.77 |
| July | 4131389.60 | 784.84 | 20-JUL-06:02 | 24.08 |
| August | 4022568.62 | 717.80 | 07-AUG-08:32 | 22.03 |
| September | 2178925.29 | 730.89 | 12-SEP-18:52 | 20.00 |
| October | 973109.54 | 730.90 | 24-OCT-08:02 | 2.30 |
| November | 1778171.61 | 958.79 | 22-NOV-09:02 | 1.10 |
| December | 1975793.94 | 1371.20 | 11-DEC-09:02 | -13.8 |
| Annual Sum or Average | 27840061.79 | |||
| Minimum of Months | 973109.54 | 714.67 | -15.3 | |
| Maximum of Months | 4131389.60 | 1560.48 | 24.08 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM220_223
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 38065254.18 | 5585.63 | 28-JAN-09:03 | -8.1 |
| February | 69960153.52 | 5710.68 | 26-FEB-09:03 | -6.5 |
| March | 15731356.26 | 5318.99 | 07-MAR-09:03 | -9.0 |
| April | 10752050.73 | 4000.92 | 17-APR-08:03 | -0.8 |
| May | 4769308.10 | 3148.83 | 01-MAY-08:04 | 8.77 |
| June | 8025557.31 | 2779.47 | 14-JUN-08:04 | 11.20 |
| July | 11151578.54 | 1277.61 | 17-JUL-18:41 | 23.90 |
| August | 7583163.73 | 994.50 | 27-AUG-16:11 | 22.93 |
| September | 5400151.70 | 1167.20 | 13-SEP-20:31 | 22.20 |
| October | 6897441.89 | 3178.00 | 08-OCT-15:15 | 6.30 |
| November | 15592046.34 | 3509.39 | 20-NOV-09:04 | 6.20 |
| December | 44701561.20 | 5006.93 | 23-DEC-09:03 | 0.68 |
| Annual Sum or Average | 0.238630E+09 | |||
| Minimum of Months | 4769308.10 | 994.50 | -9.0 | |
| Maximum of Months | 69960153.52 | 5710.68 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM224
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.148621E+09 | 2059.37 | 26-JAN-09:01 | -6.0 |
| February | 0.189613E+09 | 2137.08 | 22-FEB-09:01 | 1.28 |
| March | 16652091.09 | 1176.57 | 22-MAR-08:03 | 8.77 |
| April | 3579036.68 | 1226.44 | 03-APR-08:03 | 0.55 |
| May | 2197521.02 | 631.48 | 11-MAY-15:15 | 8.90 |
| June | 2782919.64 | 503.09 | 06-JUN-08:04 | 13.68 |
| July | 3572208.29 | 326.65 | 17-JUL-18:41 | 23.90 |
| August | 2412382.02 | 243.85 | 27-AUG-16:11 | 22.93 |
| September | 1955126.71 | 561.34 | 29-SEP-08:04 | 10.68 |
| October | 2354893.08 | 689.04 | 14-OCT-15:15 | 5.40 |
| November | 2974042.24 | 1217.25 | 07-NOV-09:03 | 2.30 |
| December | 0.155798E+09 | 2083.60 | 29-DEC-16:11 | -2.8 |
| Annual Sum or Average | 0.532512E+09 | |||
| Minimum of Months | 1955126.71 | 243.85 | -6.0 | |
| Maximum of Months | 0.189613E+09 | 2137.08 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: FRONTSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: FRONTSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 41718661.21 | 24.28 | 11-JAN-18:55 | 6.10 |
| February | 62416200.00 | 341.16 | 07-FEB-10:35 | -13.5 |
| March | 41600578.35 | 22.26 | 26-MAR-21:35 | -4.8 |
| April | 40303382.11 | 22.83 | 10-APR-01:45 | 5.15 |
| May | 41690654.67 | 22.59 | 03-MAY-00:50 | 8.40 |
| June | 40452694.20 | 20.44 | 22-JUN-01:00 | 15.00 |
| July | 41806080.72 | 21.61 | 02-JUL-23:00 | 15.00 |
| August | 41829113.87 | 21.12 | 30-AUG-15:55 | 16.70 |
| September | 40392863.84 | 20.96 | 02-SEP-21:40 | 11.10 |
| October | 41735262.58 | 21.14 | 31-OCT-19:50 | 9.45 |
| November | 40381124.59 | 22.81 | 28-NOV-05:40 | 3.67 |
| December | 41589567.25 | 24.79 | 04-DEC-05:35 | -1.9 |
| Annual Sum or Average | 0.515916E+09 | |||
| Minimum of Months | 40303382.11 | 20.44 | -13.5 | |
| Maximum of Months | 62416200.00 | 341.16 | 16.70 |
Report: ZoneHeatingSummaryMonthly
For: REARSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 10456244.37 | 6.32 | 22-JAN-16:45 | 0.60 |
| February | 15635426.88 | 86.33 | 06-FEB-18:55 | -14.4 |
| March | 10440510.54 | 6.19 | 26-MAR-21:35 | -4.8 |
| April | 10114231.79 | 6.04 | 24-APR-06:45 | 2.52 |
| May | 10475927.31 | 5.83 | 03-MAY-00:30 | 8.60 |
| June | 10173813.06 | 5.29 | 04-JUN-04:40 | 6.87 |
| July | 10498354.02 | 5.60 | 02-JUL-22:25 | 15.85 |
| August | 10514082.15 | 5.26 | 30-AUG-15:55 | 16.70 |
| September | 10155785.93 | 5.75 | 02-SEP-21:40 | 11.10 |
| October | 10476655.37 | 5.45 | 04-OCT-05:35 | 12.20 |
| November | 10126664.42 | 5.89 | 28-NOV-05:30 | 3.85 |
| December | 10419326.52 | 6.42 | 04-DEC-05:35 | -1.9 |
| Annual Sum or Average | 0.129487E+09 | |||
| Minimum of Months | 10114231.79 | 5.26 | -14.4 | |
| Maximum of Months | 15635426.88 | 86.33 | 16.70 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDORFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.195561E+10 | 1794.58 | 24-JAN-05:00 | -11.7 |
| February | 0.196461E+10 | 2120.02 | 07-FEB-05:00 | -15.6 |
| March | 0.432559E+09 | 1108.70 | 25-MAR-15:03 | 1.78 |
| April | 20894362.04 | 1410.76 | 17-APR-07:00 | -3.3 |
| May | 251.56 | 1.68 | 13-MAY-12:13 | 20.97 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 70800689.33 | 954.51 | 22-NOV-19:20 | -0.6 |
| December | 0.189076E+10 | 1701.76 | 27-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.633523E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -15.6 | |
| Maximum of Months | 0.196461E+10 | 2120.02 | 20.97 |
Report: ZoneHeatingSummaryMonthly
For: REARSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM301
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.271164E+09 | 770.06 | 13-JAN-16:01 | 2.80 |
| February | 0.268354E+09 | 513.86 | 06-FEB-19:00 | -14.4 |
| March | 56385053.10 | 238.99 | 07-MAR-07:01 | -12.9 |
| April | 86287.46 | 26.89 | 07-APR-14:01 | 19.72 |
| May | 1076933.32 | 92.31 | 10-MAY-14:01 | 26.10 |
| June | 1935618.34 | 73.32 | 26-JUN-14:01 | 27.30 |
| July | 2861655.92 | 124.82 | 15-JUL-14:01 | 30.68 |
| August | 3519670.55 | 114.69 | 13-AUG-14:01 | 30.00 |
| September | 1460286.97 | 73.05 | 21-SEP-14:01 | 25.68 |
| October | 464849.25 | 53.38 | 11-OCT-14:01 | 22.20 |
| November | 199543.90 | 24.28 | 04-NOV-14:13 | 17.97 |
| December | 0.248572E+09 | 387.08 | 26-DEC-07:01 | -12.3 |
| Annual Sum or Average | 0.856080E+09 | |||
| Minimum of Months | 86287.46 | 24.28 | -14.4 | |
| Maximum of Months | 0.271164E+09 | 770.06 | 30.68 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM302_305
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 77645475.13 | 565.22 | 04-JAN-15:02 | -5.7 |
| February | 0.125836E+09 | 699.62 | 07-FEB-07:51 | -15.6 |
| March | 9306170.50 | 314.14 | 14-MAR-14:01 | 24.90 |
| April | 14289.16 | 23.93 | 07-APR-14:01 | 19.72 |
| May | 2297528.51 | 289.87 | 10-MAY-14:01 | 26.10 |
| June | 3771491.42 | 200.58 | 26-JUN-14:01 | 27.30 |
| July | 7166967.41 | 415.69 | 15-JUL-14:01 | 30.68 |
| August | 10787015.49 | 399.24 | 10-AUG-14:01 | 30.50 |
| September | 2909270.05 | 227.92 | 21-SEP-14:01 | 25.68 |
| October | 762493.53 | 144.25 | 11-OCT-14:01 | 22.20 |
| November | 6342.11 | 5.83 | 04-NOV-15:00 | 18.30 |
| December | 0.114560E+09 | 641.30 | 06-DEC-15:04 | -5.1 |
| Annual Sum or Average | 0.355063E+09 | |||
| Minimum of Months | 6342.11 | 5.83 | -15.6 | |
| Maximum of Months | 0.125836E+09 | 699.62 | 30.68 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM306_308
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 1515533.86 | 609.70 | 31-JAN-15:03 | -11.3 |
| February | 26387713.83 | 442.05 | 21-FEB-15:06 | -9.5 |
| March | 1341344.21 | 232.51 | 14-MAR-14:01 | 24.90 |
| April | 1.35 | 0.02 | 07-APR-14:01 | 19.72 |
| May | 1716356.30 | 220.00 | 10-MAY-14:01 | 26.10 |
| June | 3797416.23 | 305.75 | 12-JUN-14:01 | 30.50 |
| July | 7712492.26 | 336.62 | 15-JUL-14:01 | 30.68 |
| August | 10584425.45 | 324.62 | 10-AUG-14:01 | 30.50 |
| September | 2275718.52 | 177.34 | 21-SEP-14:01 | 25.68 |
| October | 445665.14 | 98.72 | 11-OCT-14:01 | 22.20 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 2580228.73 | 588.00 | 26-DEC-15:03 | -9.4 |
| Annual Sum or Average | 58356895.89 | |||
| Minimum of Months | 0.00 | 0.00 | -11.3 | |
| Maximum of Months | 26387713.83 | 609.70 | 30.68 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM309_312
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.731254E+09 | 6182.16 | 13-JAN-16:12 | 2.80 |
| February | 0.718473E+09 | 6129.39 | 22-FEB-09:01 | 1.28 |
| March | 0.228809E+09 | 6111.07 | 01-MAR-16:12 | 1.30 |
| April | 11038051.93 | 3801.73 | 16-APR-08:03 | -2.9 |
| May | 3579679.70 | 2350.83 | 08-MAY-08:04 | 7.38 |
| June | 4789452.03 | 1459.06 | 15-JUN-08:05 | 14.60 |
| July | 6854353.80 | 951.97 | 06-JUL-18:21 | 22.20 |
| August | 5586690.12 | 934.58 | 23-AUG-18:21 | 21.40 |
| September | 5455178.47 | 1732.61 | 05-SEP-08:05 | 11.75 |
| October | 7542377.87 | 3389.08 | 18-OCT-08:03 | 5.78 |
| November | 23173526.13 | 4683.29 | 30-NOV-16:12 | 3.90 |
| December | 0.640647E+09 | 6188.62 | 23-DEC-16:12 | 4.40 |
| Annual Sum or Average | 0.238720E+10 | |||
| Minimum of Months | 3579679.70 | 934.58 | -2.9 | |
| Maximum of Months | 0.731254E+09 | 6188.62 | 22.20 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM313
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 96043859.72 | 349.81 | 10-JAN-16:01 | -0.6 |
| February | 0.124759E+09 | 478.91 | 05-FEB-15:02 | -8.3 |
| March | 8935982.54 | 111.40 | 14-MAR-14:01 | 24.90 |
| April | 212356.95 | 40.70 | 07-APR-14:01 | 19.72 |
| May | 1535138.52 | 106.53 | 10-MAY-14:01 | 26.10 |
| June | 3389638.12 | 130.53 | 12-JUN-14:01 | 30.50 |
| July | 5713982.29 | 139.27 | 21-JUL-14:01 | 31.52 |
| August | 6336743.16 | 134.47 | 10-AUG-14:01 | 30.50 |
| September | 2066979.81 | 89.81 | 21-SEP-14:01 | 25.68 |
| October | 696126.11 | 67.24 | 11-OCT-14:01 | 22.20 |
| November | 259462.21 | 29.97 | 04-NOV-14:13 | 17.97 |
| December | 0.112340E+09 | 241.91 | 27-DEC-04:00 | -11.7 |
| Annual Sum or Average | 0.362289E+09 | |||
| Minimum of Months | 212356.95 | 29.97 | -11.7 | |
| Maximum of Months | 0.124759E+09 | 478.91 | 31.52 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM314
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.458583E+09 | 1998.36 | 19-JAN-09:01 | 1.10 |
| February | 0.488341E+09 | 2059.80 | 01-FEB-09:01 | 5.50 |
| March | 94282018.95 | 1994.28 | 28-MAR-08:61 | 0.87 |
| April | 13830936.24 | 1149.88 | 17-APR-08:61 | -0.8 |
| May | 1846942.26 | 673.80 | 20-MAY-08:04 | 12.15 |
| June | 2287472.38 | 694.34 | 15-JUN-08:04 | 14.60 |
| July | 2975709.53 | 280.07 | 05-JUL-16:21 | 23.60 |
| August | 2045809.56 | 245.93 | 27-AUG-16:11 | 22.93 |
| September | 1826793.68 | 745.47 | 30-SEP-08:04 | 10.28 |
| October | 2950137.40 | 927.74 | 27-OCT-08:03 | 5.68 |
| November | 32722567.28 | 2002.91 | 30-NOV-16:12 | 3.90 |
| December | 0.470687E+09 | 2027.93 | 13-DEC-09:01 | 1.88 |
| Annual Sum or Average | 0.157238E+10 | |||
| Minimum of Months | 1826793.68 | 245.93 | -0.8 | |
| Maximum of Months | 0.488341E+09 | 2059.80 | 23.60 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM315_318
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 15943225.40 | 5853.60 | 29-JAN-09:03 | -7.1 |
| February | 22088702.84 | 4797.90 | 27-FEB-09:03 | -2.8 |
| March | 10317100.49 | 3273.85 | 20-MAR-08:03 | -2.7 |
| April | 7657074.04 | 2617.37 | 28-APR-08:04 | 10.00 |
| May | 3630865.74 | 2681.38 | 12-MAY-08:04 | 10.10 |
| June | 6775207.27 | 2071.21 | 14-JUN-08:04 | 11.20 |
| July | 10100321.34 | 1208.04 | 17-JUL-18:41 | 23.90 |
| August | 7155405.85 | 1068.12 | 27-AUG-16:11 | 22.93 |
| September | 5389815.10 | 2690.63 | 29-SEP-08:04 | 10.68 |
| October | 6859103.81 | 2589.10 | 14-OCT-15:15 | 5.40 |
| November | 11257096.56 | 2826.36 | 13-NOV-16:15 | 8.33 |
| December | 14222842.18 | 4914.09 | 10-DEC-09:03 | -11.4 |
| Annual Sum or Average | 0.121397E+09 | |||
| Minimum of Months | 3630865.74 | 1068.12 | -11.4 | |
| Maximum of Months | 22088702.84 | 5853.60 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ELEVATORCOREFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM319
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 98006.66 | 45.56 | 14-MAR-14:01 | 24.90 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 64169.40 | 32.08 | 23-MAY-14:01 | 23.90 |
| June | 66495.38 | 33.09 | 16-JUN-14:07 | 23.98 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 228671.44 | |||
| Minimum of Months | 0.00 | 0.00 | -3.3 | |
| Maximum of Months | 98006.66 | 45.56 | 24.90 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM320_323
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.150723E+09 | 6851.70 | 26-JAN-16:12 | -3.5 |
| February | 0.207307E+09 | 6704.40 | 13-FEB-09:01 | -8.9 |
| March | 21069776.41 | 5198.26 | 04-MAR-09:03 | -7.7 |
| April | 10710812.42 | 4196.02 | 16-APR-08:03 | -2.9 |
| May | 4785353.77 | 3533.75 | 04-MAY-08:04 | 10.47 |
| June | 7758723.48 | 2582.04 | 14-JUN-08:04 | 11.20 |
| July | 11165629.51 | 1548.01 | 06-JUL-16:17 | 22.20 |
| August | 7298327.95 | 978.06 | 27-AUG-16:11 | 22.93 |
| September | 5831897.19 | 1206.09 | 10-SEP-16:17 | 17.23 |
| October | 7797900.44 | 3614.35 | 18-OCT-15:15 | 10.60 |
| November | 14564472.30 | 4138.29 | 21-NOV-09:03 | 3.22 |
| December | 0.171093E+09 | 6918.18 | 29-DEC-16:11 | -2.8 |
| Annual Sum or Average | 0.620106E+09 | |||
| Minimum of Months | 4785353.77 | 978.06 | -8.9 | |
| Maximum of Months | 0.207307E+09 | 6918.18 | 22.93 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM324
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 73714.77 | 13.23 | 07-FEB-07:27 | -16.1 |
| March | 354054.98 | 53.78 | 15-MAR-14:01 | 26.02 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 575007.98 | 65.73 | 10-MAY-14:01 | 26.10 |
| June | 1729674.34 | 70.32 | 26-JUN-14:13 | 27.40 |
| July | 1871411.12 | 119.31 | 15-JUL-14:01 | 30.68 |
| August | 1043714.96 | 87.37 | 04-AUG-14:01 | 28.80 |
| September | 253481.71 | 37.53 | 15-SEP-14:01 | 25.40 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 5901059.86 | |||
| Minimum of Months | 0.00 | 0.00 | -16.1 | |
| Maximum of Months | 1871411.12 | 119.31 | 30.68 |
Report: ZoneHeatingSummaryMonthly
For: FRONTSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: FRONTSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 55462089.97 | 202.89 | 24-JAN-06:00 | -12.2 |
| February | 0.108092E+09 | 427.89 | 06-FEB-18:55 | -14.4 |
| March | 51773770.82 | 28.07 | 26-MAR-21:35 | -4.8 |
| April | 50172118.51 | 29.26 | 10-APR-01:45 | 5.15 |
| May | 51898629.62 | 28.82 | 03-MAY-00:40 | 8.50 |
| June | 50351819.45 | 25.62 | 04-JUN-04:50 | 6.78 |
| July | 52025580.48 | 26.73 | 02-JUL-23:00 | 15.00 |
| August | 52065919.56 | 26.70 | 30-AUG-15:55 | 16.70 |
| September | 50279906.43 | 26.87 | 03-SEP-05:35 | 7.20 |
| October | 51964713.40 | 26.73 | 04-OCT-05:35 | 12.20 |
| November | 50272183.08 | 28.72 | 28-NOV-05:40 | 3.67 |
| December | 61087105.69 | 195.83 | 09-DEC-20:00 | -8.9 |
| Annual Sum or Average | 0.685445E+09 | |||
| Minimum of Months | 50172118.51 | 25.62 | -14.4 | |
| Maximum of Months | 0.108092E+09 | 427.89 | 16.70 |
Report: ZoneHeatingSummaryMonthly
For: REARSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 51558499.87 | 306.64 | 12-JAN-09:00 | -11.1 |
| February | 0.107446E+09 | 309.50 | 07-FEB-03:00 | -15.6 |
| March | 37455020.99 | 22.61 | 26-MAR-21:35 | -4.8 |
| April | 36360612.43 | 24.96 | 06-APR-17:33 | 12.60 |
| May | 37574092.93 | 21.84 | 07-MAY-21:35 | 9.60 |
| June | 36410051.97 | 20.10 | 06-JUN-22:40 | 15.57 |
| July | 37588535.38 | 21.46 | 02-JUL-23:00 | 15.00 |
| August | 37629623.03 | 20.11 | 30-AUG-15:55 | 16.70 |
| September | 36266184.80 | 21.81 | 11-SEP-20:35 | 14.40 |
| October | 37536381.19 | 21.60 | 31-OCT-19:50 | 9.45 |
| November | 36215420.24 | 20.85 | 10-NOV-12:00 | 10.60 |
| December | 60724684.51 | 304.69 | 26-DEC-06:35 | -12.2 |
| Annual Sum or Average | 0.552765E+09 | |||
| Minimum of Months | 36215420.24 | 20.10 | -15.6 | |
| Maximum of Months | 0.107446E+09 | 309.50 | 16.70 |
Report: ZoneHeatingSummaryMonthly
For: CORRIDORFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.530597E+10 | 3686.43 | 24-JAN-05:00 | -11.7 |
| February | 0.485326E+10 | 3989.63 | 07-FEB-05:00 | -15.6 |
| March | 0.239343E+10 | 3077.23 | 07-MAR-05:00 | -13.3 |
| April | 0.802815E+09 | 2081.16 | 16-APR-04:30 | -2.2 |
| May | 34272238.94 | 631.27 | 07-MAY-05:00 | 3.90 |
| June | 557972.32 | 101.39 | 14-JUN-04:00 | 6.70 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 1432.57 | 2.39 | 25-AUG-04:00 | 18.90 |
| September | 9998973.54 | 571.56 | 30-SEP-05:00 | 7.20 |
| October | 0.538420E+09 | 1747.43 | 17-OCT-04:00 | -2.8 |
| November | 0.183246E+10 | 2086.77 | 24-NOV-04:50 | -2.9 |
| December | 0.517206E+10 | 3626.83 | 26-DEC-05:00 | -12.2 |
| Annual Sum or Average | 0.209433E+11 | |||
| Minimum of Months | 0.00 | 0.00 | -15.6 | |
| Maximum of Months | 0.530597E+10 | 3989.63 | 18.90 |
Report: ZoneHeatingSummaryMonthly
For: REARSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM401
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.184244E+10 | 2190.59 | 11-JAN-09:01 | 6.88 |
| February | 0.168891E+10 | 2184.78 | 15-FEB-09:01 | 6.70 |
| March | 0.972852E+09 | 2174.39 | 22-MAR-08:61 | 8.77 |
| April | 0.362512E+09 | 2148.83 | 12-APR-08:61 | 9.08 |
| May | 43278457.89 | 867.03 | 15-MAY-08:04 | 13.90 |
| June | 5218939.39 | 663.87 | 15-JUN-08:04 | 14.60 |
| July | 3121720.38 | 248.83 | 26-JUL-20:01 | 21.60 |
| August | 2316903.53 | 681.00 | 31-AUG-08:04 | 13.90 |
| September | 14568175.13 | 717.37 | 28-SEP-08:03 | 12.20 |
| October | 0.268841E+09 | 2170.39 | 31-OCT-08:61 | 9.87 |
| November | 0.706482E+09 | 2175.36 | 14-NOV-09:01 | 9.50 |
| December | 0.175989E+10 | 2209.99 | 01-DEC-09:01 | 13.48 |
| Annual Sum or Average | 0.767043E+10 | |||
| Minimum of Months | 2316903.53 | 248.83 | 6.70 | |
| Maximum of Months | 0.184244E+10 | 2209.99 | 21.60 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM402_405
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.190740E+10 | 1853.41 | 24-JAN-06:00 | -12.2 |
| February | 0.170625E+10 | 2131.32 | 07-FEB-07:27 | -16.1 |
| March | 0.688927E+09 | 1694.02 | 07-MAR-05:10 | -13.3 |
| April | 30037546.96 | 722.99 | 17-APR-05:30 | -4.2 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 514236.81 | 102.45 | 25-SEP-14:01 | 24.32 |
| October | 18091475.98 | 467.40 | 17-OCT-06:27 | -2.8 |
| November | 0.134423E+09 | 710.34 | 24-NOV-07:00 | -3.3 |
| December | 0.165261E+10 | 2012.49 | 11-DEC-06:01 | -18.5 |
| Annual Sum or Average | 0.613825E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -18.5 | |
| Maximum of Months | 0.190740E+10 | 2131.32 | 24.32 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM406_408
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.122531E+10 | 1354.87 | 24-JAN-06:00 | -12.2 |
| February | 0.110893E+10 | 1590.83 | 07-FEB-07:27 | -16.1 |
| March | 0.412676E+09 | 1214.70 | 07-MAR-05:10 | -13.3 |
| April | 11957919.33 | 437.62 | 17-APR-05:30 | -4.2 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 422438.03 | 81.92 | 25-SEP-14:01 | 24.32 |
| October | 4583396.03 | 222.02 | 17-OCT-06:27 | -2.8 |
| November | 46272240.62 | 438.17 | 24-NOV-06:50 | -3.4 |
| December | 0.104747E+10 | 1484.92 | 11-DEC-06:01 | -18.5 |
| Annual Sum or Average | 0.385762E+10 | |||
| Minimum of Months | 0.00 | 0.00 | -18.5 | |
| Maximum of Months | 0.122531E+10 | 1590.83 | 24.32 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM409_412
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.238133E+10 | 7808.95 | 17-JAN-16:12 | 7.80 |
| February | 0.215274E+10 | 7753.18 | 22-FEB-09:01 | 1.28 |
| March | 0.107068E+10 | 7718.16 | 02-MAR-09:01 | 2.88 |
| April | 0.276498E+09 | 4924.42 | 17-APR-08:61 | -0.8 |
| May | 21379610.91 | 3398.81 | 07-MAY-08:04 | 10.47 |
| June | 7110786.70 | 3473.87 | 14-JUN-08:04 | 11.20 |
| July | 10288960.47 | 1054.16 | 26-JUL-20:01 | 21.60 |
| August | 7373634.29 | 1030.88 | 12-AUG-21:57 | 16.10 |
| September | 10149580.41 | 2929.86 | 28-SEP-15:15 | 11.33 |
| October | 0.189738E+09 | 7707.40 | 30-OCT-08:61 | 2.57 |
| November | 0.547028E+09 | 7804.77 | 30-NOV-16:12 | 3.90 |
| December | 0.217496E+10 | 7833.66 | 20-DEC-16:12 | 4.40 |
| Annual Sum or Average | 0.884928E+10 | |||
| Minimum of Months | 7110786.70 | 1030.88 | -0.8 | |
| Maximum of Months | 0.238133E+10 | 7833.66 | 21.60 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM413
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.694753E+09 | 705.06 | 24-JAN-06:00 | -12.2 |
| February | 0.665881E+09 | 831.44 | 07-FEB-07:16 | -16.3 |
| March | 0.228969E+09 | 565.02 | 07-MAR-05:40 | -13.3 |
| April | 10349761.08 | 219.26 | 17-APR-05:30 | -4.2 |
| May | 910157.59 | 85.32 | 10-MAY-14:01 | 26.10 |
| June | 290433.76 | 53.46 | 16-JUN-14:01 | 23.98 |
| July | 133548.83 | 26.39 | 28-JUL-14:01 | 22.80 |
| August | 318865.74 | 54.13 | 23-AUG-14:01 | 24.32 |
| September | 1463931.93 | 77.69 | 21-SEP-14:01 | 25.68 |
| October | 2706878.36 | 91.33 | 17-OCT-05:01 | -2.8 |
| November | 25287934.90 | 186.65 | 24-NOV-06:17 | -3.7 |
| December | 0.614613E+09 | 696.44 | 11-DEC-06:00 | -18.9 |
| Annual Sum or Average | 0.224568E+10 | |||
| Minimum of Months | 133548.83 | 26.39 | -18.9 | |
| Maximum of Months | 0.694753E+09 | 831.44 | 26.10 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM414
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.197239E+09 | 459.58 | 24-JAN-06:00 | -12.2 |
| February | 0.226279E+09 | 564.96 | 07-FEB-07:27 | -16.1 |
| March | 31319024.44 | 297.01 | 07-MAR-06:40 | -13.3 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 27888.10 | 18.81 | 28-JUL-14:08 | 22.80 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 118545.73 | 21.68 | 17-SEP-14:25 | 22.50 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 25965.00 | 7.80 | 05-NOV-14:02 | 19.22 |
| December | 0.199958E+09 | 462.24 | 11-DEC-06:01 | -18.5 |
| Annual Sum or Average | 0.654967E+09 | |||
| Minimum of Months | 0.00 | 0.00 | -18.5 | |
| Maximum of Months | 0.226279E+09 | 564.96 | 22.80 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM415_418
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.107961E+10 | 8963.00 | 26-JAN-09:01 | -6.0 |
| February | 0.108967E+10 | 8956.44 | 13-FEB-09:01 | -8.9 |
| March | 0.434235E+09 | 4852.57 | 22-MAR-08:03 | 8.77 |
| April | 94322442.74 | 4646.81 | 19-APR-08:03 | 6.97 |
| May | 8795459.43 | 3362.15 | 03-MAY-16:15 | 15.37 |
| June | 11911321.65 | 2338.69 | 06-JUN-08:04 | 13.68 |
| July | 17447492.67 | 1447.44 | 17-JUL-18:41 | 23.90 |
| August | 11421520.33 | 2756.34 | 31-AUG-08:04 | 13.90 |
| September | 11184767.76 | 2885.84 | 07-SEP-08:04 | 14.60 |
| October | 64149716.98 | 3877.43 | 27-OCT-08:03 | 5.68 |
| November | 0.181280E+09 | 9115.60 | 30-NOV-16:12 | 3.90 |
| December | 0.104763E+10 | 9143.26 | 20-DEC-16:12 | 4.40 |
| Annual Sum or Average | 0.405165E+10 | |||
| Minimum of Months | 8795459.43 | 1447.44 | -8.9 | |
| Maximum of Months | 0.108967E+10 | 9143.26 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ELEVATORCOREFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM419
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.383165E+09 | 2408.89 | 26-JAN-09:01 | -6.0 |
| February | 0.385983E+09 | 2458.08 | 22-FEB-09:01 | 1.28 |
| March | 0.135645E+09 | 1672.18 | 20-MAR-08:61 | -2.7 |
| April | 27963597.74 | 1119.58 | 10-APR-08:03 | 3.98 |
| May | 1534879.39 | 1286.94 | 08-MAY-08:03 | 7.38 |
| June | 3278249.76 | 345.73 | 22-JUN-08:04 | 15.37 |
| July | 5207631.79 | 387.10 | 07-JUL-08:36 | 18.50 |
| August | 3407501.46 | 429.73 | 31-AUG-08:04 | 13.90 |
| September | 2933582.88 | 512.77 | 01-SEP-08:04 | 14.08 |
| October | 16374490.75 | 1125.17 | 15-OCT-08:03 | 4.60 |
| November | 58883028.25 | 2431.41 | 30-NOV-16:12 | 3.90 |
| December | 0.376091E+09 | 2441.49 | 20-DEC-16:12 | 4.40 |
| Annual Sum or Average | 0.140047E+10 | |||
| Minimum of Months | 1534879.39 | 345.73 | -6.0 | |
| Maximum of Months | 0.385983E+09 | 2458.08 | 18.50 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM420_423
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.122314E+10 | 8945.64 | 18-JAN-16:12 | 2.03 |
| February | 0.120828E+10 | 8864.02 | 13-FEB-09:01 | -8.9 |
| March | 0.481858E+09 | 4888.65 | 25-MAR-08:02 | -3.4 |
| April | 0.126081E+09 | 4995.02 | 16-APR-08:02 | -2.9 |
| May | 12940607.71 | 3234.53 | 30-MAY-08:04 | 13.07 |
| June | 12870815.61 | 2603.85 | 06-JUN-08:04 | 13.68 |
| July | 18588406.75 | 2178.84 | 06-JUL-08:56 | 17.80 |
| August | 12032367.12 | 2805.38 | 31-AUG-08:04 | 13.90 |
| September | 12437778.20 | 3230.61 | 07-SEP-08:04 | 14.60 |
| October | 83774622.52 | 4343.27 | 24-OCT-08:02 | 2.30 |
| November | 0.229864E+09 | 9085.25 | 30-NOV-16:12 | 3.90 |
| December | 0.118879E+10 | 9111.21 | 20-DEC-16:12 | 4.40 |
| Annual Sum or Average | 0.461065E+10 | |||
| Minimum of Months | 12032367.12 | 2178.84 | -8.9 | |
| Maximum of Months | 0.122314E+10 | 9111.21 | 17.80 |
Report: ZoneHeatingSummaryMonthly
For: GUESTROOM424
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.866541E+09 | 2583.06 | 11-JAN-09:01 | 6.88 |
| February | 0.833324E+09 | 2570.42 | 22-FEB-09:01 | 1.28 |
| March | 0.325638E+09 | 2524.10 | 28-MAR-08:61 | 0.87 |
| April | 96909470.62 | 2485.94 | 17-APR-08:61 | -0.8 |
| May | 5357892.70 | 1202.46 | 09-MAY-08:03 | 11.97 |
| June | 3859370.24 | 436.84 | 25-JUN-21:26 | 22.50 |
| July | 5601376.07 | 348.51 | 17-JUL-18:41 | 23.90 |
| August | 3761478.47 | 449.49 | 31-AUG-08:04 | 13.90 |
| September | 4062058.16 | 736.64 | 29-SEP-08:03 | 10.68 |
| October | 52137827.57 | 1268.37 | 30-OCT-08:61 | 2.57 |
| November | 0.188241E+09 | 2554.06 | 30-NOV-09:01 | 5.68 |
| December | 0.853433E+09 | 2554.57 | 13-DEC-09:01 | 1.88 |
| Annual Sum or Average | 0.323887E+10 | |||
| Minimum of Months | 3761478.47 | 348.51 | -0.8 | |
| Maximum of Months | 0.866541E+09 | 2583.06 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: FRONTSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 6.67 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 18.85 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -4.9 | |
| Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: FRONTSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.116220E+09 | 550.95 | 12-JAN-09:00 | -11.1 |
| February | 0.218397E+09 | 687.23 | 06-FEB-09:53 | -15.0 |
| March | 83899669.78 | 45.97 | 26-MAR-21:35 | -4.8 |
| April | 81472975.78 | 57.63 | 06-APR-17:33 | 12.60 |
| May | 84214140.54 | 47.29 | 14-MAY-16:42 | 17.58 |
| June | 81660999.74 | 42.52 | 12-JUN-23:40 | 15.77 |
| July | 84457938.71 | 45.43 | 02-JUL-23:00 | 15.00 |
| August | 84486367.35 | 45.02 | 30-AUG-15:55 | 16.70 |
| September | 81379771.32 | 45.85 | 25-SEP-23:00 | 17.20 |
| October | 84191579.00 | 46.22 | 31-OCT-19:50 | 9.45 |
| November | 81280735.76 | 46.76 | 10-NOV-12:00 | 10.60 |
| December | 0.152465E+09 | 442.51 | 26-DEC-07:00 | -12.2 |
| Annual Sum or Average | 0.123413E+10 | |||
| Minimum of Months | 81280735.76 | 42.52 | -15.0 | |
| Maximum of Months | 0.218397E+09 | 687.23 | 17.58 |
Report: ZoneElectricSummaryMonthly
For: REARSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.347203E+09 | 129.63 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.313603E+09 | 129.63 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.347203E+09 | 129.63 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.336003E+09 | 129.63 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.347203E+09 | 129.63 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.336003E+09 | 129.63 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.347203E+09 | 129.63 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.347203E+09 | 129.63 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.336003E+09 | 129.63 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.347203E+09 | 129.63 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.336003E+09 | 129.63 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.347203E+09 | 129.63 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.408804E+10 | 0.00 | ||||
| Minimum of Months | 0.313603E+09 | 129.63 | 0.00 | 0.00 | ||
| Maximum of Months | 0.347203E+09 | 129.63 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: CORRIDORFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.216954E+10 | 810.01 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.195959E+10 | 810.01 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.216954E+10 | 810.01 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.209956E+10 | 810.01 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.216954E+10 | 810.01 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.209956E+10 | 810.01 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.216954E+10 | 810.01 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.216954E+10 | 810.01 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.209956E+10 | 810.01 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.216954E+10 | 810.01 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.209956E+10 | 810.01 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.216954E+10 | 810.01 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.255446E+11 | 0.00 | ||||
| Minimum of Months | 0.195959E+10 | 810.01 | 0.00 | 0.00 | ||
| Maximum of Months | 0.216954E+10 | 810.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: REARSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.115743E+09 | 69.14 | 01-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.104542E+09 | 69.14 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.115743E+09 | 69.14 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.112009E+09 | 69.14 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.115743E+09 | 69.14 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.112009E+09 | 69.14 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.115743E+09 | 69.14 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.115743E+09 | 69.14 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.112009E+09 | 69.14 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.115743E+09 | 69.14 | 01-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.112009E+09 | 69.14 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.115743E+09 | 69.14 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.136278E+10 | 0.00 | ||||
| Minimum of Months | 0.104542E+09 | 69.14 | 0.00 | 0.00 | ||
| Maximum of Months | 0.115743E+09 | 69.14 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: FRONTLOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.306833E+10 | 2281.66 | 01-JAN-08:09 | 0.427743E+10 | 4249.25 | 01-JAN-06:10 |
| February | 0.277140E+10 | 2281.66 | 01-FEB-08:09 | 0.386349E+10 | 4249.25 | 01-FEB-06:10 |
| March | 0.306833E+10 | 2281.66 | 01-MAR-08:09 | 0.427743E+10 | 4249.25 | 01-MAR-06:10 |
| April | 0.296935E+10 | 2281.66 | 01-APR-07:10 | 0.413945E+10 | 4249.25 | 01-APR-05:10 |
| May | 0.306833E+10 | 2281.66 | 01-MAY-07:10 | 0.427743E+10 | 4249.25 | 01-MAY-05:10 |
| June | 0.296935E+10 | 2281.66 | 01-JUN-07:10 | 0.413945E+10 | 4249.25 | 01-JUN-05:10 |
| July | 0.306833E+10 | 2281.66 | 01-JUL-07:10 | 0.427743E+10 | 4249.25 | 01-JUL-05:10 |
| August | 0.306833E+10 | 2281.66 | 01-AUG-07:10 | 0.427743E+10 | 4249.25 | 01-AUG-05:10 |
| September | 0.296935E+10 | 2281.66 | 01-SEP-07:10 | 0.413945E+10 | 4249.25 | 01-SEP-05:10 |
| October | 0.306833E+10 | 2281.66 | 01-OCT-07:10 | 0.427743E+10 | 4249.25 | 01-OCT-05:10 |
| November | 0.296935E+10 | 2281.66 | 01-NOV-07:10 | 0.413945E+10 | 4249.25 | 01-NOV-05:10 |
| December | 0.306833E+10 | 2281.66 | 01-DEC-08:09 | 0.427743E+10 | 4249.25 | 01-DEC-06:10 |
| Annual Sum or Average | 0.361271E+11 | 0.503633E+11 | ||||
| Minimum of Months | 0.277140E+10 | 2281.66 | 0.386349E+10 | 4249.25 | ||
| Maximum of Months | 0.306833E+10 | 2281.66 | 0.427743E+10 | 4249.25 |
Report: ZoneElectricSummaryMonthly
For: RESTROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.846166E+09 | 315.92 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.764279E+09 | 315.92 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.846166E+09 | 315.92 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.818870E+09 | 315.92 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.846166E+09 | 315.92 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.818870E+09 | 315.92 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.846166E+09 | 315.92 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.846166E+09 | 315.92 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.818870E+09 | 315.92 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.846166E+09 | 315.92 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.818870E+09 | 315.92 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.846166E+09 | 315.92 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.996292E+10 | 0.00 | ||||
| Minimum of Months | 0.764279E+09 | 315.92 | 0.00 | 0.00 | ||
| Maximum of Months | 0.846166E+09 | 315.92 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: MEETINGROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.151056E+10 | 1123.28 | 01-JAN-08:09 | 0.179790E+09 | 237.69 | 01-JAN-08:09 |
| February | 0.136438E+10 | 1123.28 | 01-FEB-08:09 | 0.162391E+09 | 237.69 | 01-FEB-08:09 |
| March | 0.151056E+10 | 1123.28 | 01-MAR-08:09 | 0.179790E+09 | 237.69 | 01-MAR-08:09 |
| April | 0.146183E+10 | 1123.28 | 01-APR-07:10 | 0.173991E+09 | 237.69 | 01-APR-07:10 |
| May | 0.151056E+10 | 1123.28 | 01-MAY-07:10 | 0.179790E+09 | 237.69 | 01-MAY-07:10 |
| June | 0.146183E+10 | 1123.28 | 01-JUN-07:10 | 0.173991E+09 | 237.69 | 01-JUN-07:10 |
| July | 0.151056E+10 | 1123.28 | 01-JUL-07:10 | 0.179790E+09 | 237.69 | 01-JUL-07:10 |
| August | 0.151056E+10 | 1123.28 | 01-AUG-07:10 | 0.179790E+09 | 237.69 | 01-AUG-07:10 |
| September | 0.146183E+10 | 1123.28 | 01-SEP-07:10 | 0.173991E+09 | 237.69 | 01-SEP-07:10 |
| October | 0.151056E+10 | 1123.28 | 01-OCT-07:10 | 0.179790E+09 | 237.69 | 01-OCT-07:10 |
| November | 0.146183E+10 | 1123.28 | 01-NOV-07:10 | 0.173991E+09 | 237.69 | 01-NOV-07:10 |
| December | 0.151056E+10 | 1123.28 | 01-DEC-08:09 | 0.179790E+09 | 237.69 | 01-DEC-08:09 |
| Annual Sum or Average | 0.177857E+11 | 0.211689E+10 | ||||
| Minimum of Months | 0.136438E+10 | 1123.28 | 0.162391E+09 | 237.69 | ||
| Maximum of Months | 0.151056E+10 | 1123.28 | 0.179790E+09 | 237.69 |
Report: ZoneElectricSummaryMonthly
For: MECHANICALROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.352569E+09 | 210.61 | 01-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.318449E+09 | 210.61 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.352569E+09 | 210.61 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.341196E+09 | 210.61 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.352569E+09 | 210.61 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.341196E+09 | 210.61 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.352569E+09 | 210.61 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.352569E+09 | 210.61 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.341196E+09 | 210.61 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.352569E+09 | 210.61 | 01-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.341196E+09 | 210.61 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.352569E+09 | 210.61 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.415122E+10 | 0.00 | ||||
| Minimum of Months | 0.318449E+09 | 210.61 | 0.00 | 0.00 | ||
| Maximum of Months | 0.352569E+09 | 210.61 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM101
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM102
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM103
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.444038E+09 | 400.17 | 01-JAN-19:10 | 0.303486E+09 | 349.07 | 01-JAN-08:09 |
| February | 0.399422E+09 | 400.17 | 01-FEB-20:10 | 0.274038E+09 | 349.07 | 01-FEB-07:10 |
| March | 0.438765E+09 | 400.17 | 01-MAR-20:10 | 0.303234E+09 | 349.07 | 01-MAR-07:10 |
| April | 0.428522E+09 | 400.17 | 01-APR-18:10 | 0.293642E+09 | 349.07 | 01-APR-07:10 |
| May | 0.440523E+09 | 400.17 | 01-MAY-19:10 | 0.303318E+09 | 349.07 | 01-MAY-06:10 |
| June | 0.425123E+09 | 400.17 | 01-JUN-19:10 | 0.293474E+09 | 349.07 | 01-JUN-06:10 |
| July | 0.443980E+09 | 400.17 | 01-JUL-18:10 | 0.303486E+09 | 349.07 | 01-JUL-07:10 |
| August | 0.438765E+09 | 400.17 | 01-AUG-19:10 | 0.303234E+09 | 349.07 | 01-AUG-06:10 |
| September | 0.428638E+09 | 400.17 | 01-SEP-19:10 | 0.293642E+09 | 349.07 | 01-SEP-06:10 |
| October | 0.442223E+09 | 400.17 | 01-OCT-18:10 | 0.303402E+09 | 349.07 | 01-OCT-07:10 |
| November | 0.428580E+09 | 400.17 | 01-NOV-19:10 | 0.293642E+09 | 349.07 | 01-NOV-06:10 |
| December | 0.444038E+09 | 400.17 | 01-DEC-20:10 | 0.303486E+09 | 349.07 | 01-DEC-07:10 |
| Annual Sum or Average | 0.520262E+10 | 0.357208E+10 | ||||
| Minimum of Months | 0.399422E+09 | 400.17 | 0.274038E+09 | 349.07 | ||
| Maximum of Months | 0.444038E+09 | 400.17 | 0.303486E+09 | 349.07 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM104
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.444006E+09 | 400.14 | 01-JAN-19:10 | 0.303464E+09 | 349.05 | 01-JAN-08:09 |
| February | 0.399394E+09 | 400.14 | 01-FEB-20:10 | 0.274018E+09 | 349.05 | 01-FEB-07:10 |
| March | 0.438734E+09 | 400.14 | 01-MAR-20:10 | 0.303213E+09 | 349.05 | 01-MAR-07:10 |
| April | 0.428492E+09 | 400.14 | 01-APR-18:10 | 0.293621E+09 | 349.05 | 01-APR-07:10 |
| May | 0.440491E+09 | 400.14 | 01-MAY-19:10 | 0.303297E+09 | 349.05 | 01-MAY-06:10 |
| June | 0.425092E+09 | 400.14 | 01-JUN-19:10 | 0.293453E+09 | 349.05 | 01-JUN-06:10 |
| July | 0.443949E+09 | 400.14 | 01-JUL-18:10 | 0.303464E+09 | 349.05 | 01-JUL-07:10 |
| August | 0.438734E+09 | 400.14 | 01-AUG-19:10 | 0.303213E+09 | 349.05 | 01-AUG-06:10 |
| September | 0.428607E+09 | 400.14 | 01-SEP-19:10 | 0.293621E+09 | 349.05 | 01-SEP-06:10 |
| October | 0.442191E+09 | 400.14 | 01-OCT-18:10 | 0.303380E+09 | 349.05 | 01-OCT-07:10 |
| November | 0.428550E+09 | 400.14 | 01-NOV-19:10 | 0.293621E+09 | 349.05 | 01-NOV-06:10 |
| December | 0.444006E+09 | 400.14 | 01-DEC-20:10 | 0.303464E+09 | 349.05 | 01-DEC-07:10 |
| Annual Sum or Average | 0.520225E+10 | 0.357183E+10 | ||||
| Minimum of Months | 0.399394E+09 | 400.14 | 0.274018E+09 | 349.05 | ||
| Maximum of Months | 0.444006E+09 | 400.14 | 0.303464E+09 | 349.05 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM105
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.444006E+09 | 400.14 | 01-JAN-19:10 | 0.303464E+09 | 349.05 | 01-JAN-08:09 |
| February | 0.399394E+09 | 400.14 | 01-FEB-20:10 | 0.274018E+09 | 349.05 | 01-FEB-07:10 |
| March | 0.438734E+09 | 400.14 | 01-MAR-20:10 | 0.303213E+09 | 349.05 | 01-MAR-07:10 |
| April | 0.428492E+09 | 400.14 | 01-APR-18:10 | 0.293621E+09 | 349.05 | 01-APR-07:10 |
| May | 0.440491E+09 | 400.14 | 01-MAY-19:10 | 0.303297E+09 | 349.05 | 01-MAY-06:10 |
| June | 0.425092E+09 | 400.14 | 01-JUN-19:10 | 0.293453E+09 | 349.05 | 01-JUN-06:10 |
| July | 0.443949E+09 | 400.14 | 01-JUL-18:10 | 0.303464E+09 | 349.05 | 01-JUL-07:10 |
| August | 0.438734E+09 | 400.14 | 01-AUG-19:10 | 0.303213E+09 | 349.05 | 01-AUG-06:10 |
| September | 0.428607E+09 | 400.14 | 01-SEP-19:10 | 0.293621E+09 | 349.05 | 01-SEP-06:10 |
| October | 0.442191E+09 | 400.14 | 01-OCT-18:10 | 0.303380E+09 | 349.05 | 01-OCT-07:10 |
| November | 0.428550E+09 | 400.14 | 01-NOV-19:10 | 0.293621E+09 | 349.05 | 01-NOV-06:10 |
| December | 0.444006E+09 | 400.14 | 01-DEC-20:10 | 0.303464E+09 | 349.05 | 01-DEC-07:10 |
| Annual Sum or Average | 0.520225E+10 | 0.357183E+10 | ||||
| Minimum of Months | 0.399394E+09 | 400.14 | 0.274018E+09 | 349.05 | ||
| Maximum of Months | 0.444006E+09 | 400.14 | 0.303464E+09 | 349.05 |
Report: ZoneElectricSummaryMonthly
For: EMPLOYEELOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.566421E+09 | 421.20 | 01-JAN-08:09 | 0.812993E+09 | 672.25 | 01-JAN-08:09 |
| February | 0.511606E+09 | 421.20 | 01-FEB-08:09 | 0.734316E+09 | 672.25 | 01-FEB-08:09 |
| March | 0.566421E+09 | 421.20 | 01-MAR-08:09 | 0.812993E+09 | 672.25 | 01-MAR-08:09 |
| April | 0.548149E+09 | 421.20 | 01-APR-07:10 | 0.786767E+09 | 672.25 | 01-APR-07:10 |
| May | 0.566421E+09 | 421.20 | 01-MAY-07:10 | 0.812993E+09 | 672.25 | 01-MAY-07:10 |
| June | 0.548149E+09 | 421.20 | 01-JUN-07:10 | 0.786767E+09 | 672.25 | 01-JUN-07:10 |
| July | 0.566421E+09 | 421.20 | 01-JUL-07:10 | 0.812993E+09 | 672.25 | 01-JUL-07:10 |
| August | 0.566421E+09 | 421.20 | 01-AUG-07:10 | 0.812993E+09 | 672.25 | 01-AUG-07:10 |
| September | 0.548149E+09 | 421.20 | 01-SEP-07:10 | 0.786767E+09 | 672.25 | 01-SEP-07:10 |
| October | 0.566421E+09 | 421.20 | 01-OCT-07:10 | 0.812993E+09 | 672.25 | 01-OCT-07:10 |
| November | 0.548149E+09 | 421.20 | 01-NOV-07:10 | 0.786767E+09 | 672.25 | 01-NOV-07:10 |
| December | 0.566421E+09 | 421.20 | 01-DEC-08:09 | 0.812993E+09 | 672.25 | 01-DEC-08:09 |
| Annual Sum or Average | 0.666915E+10 | 0.957233E+10 | ||||
| Minimum of Months | 0.511606E+09 | 421.20 | 0.734316E+09 | 672.25 | ||
| Maximum of Months | 0.566421E+09 | 421.20 | 0.812993E+09 | 672.25 |
Report: ZoneElectricSummaryMonthly
For: LAUNDRYROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.634579E+09 | 631.80 | 01-JAN-08:09 | 0.241866E+10 | 2709.07 | 01-JAN-08:09 |
| February | 0.573168E+09 | 631.80 | 01-FEB-08:09 | 0.218460E+10 | 2709.07 | 01-FEB-08:09 |
| March | 0.634579E+09 | 631.80 | 01-MAR-08:09 | 0.241866E+10 | 2709.07 | 01-MAR-08:09 |
| April | 0.614109E+09 | 631.80 | 01-APR-07:10 | 0.234064E+10 | 2709.07 | 01-APR-07:10 |
| May | 0.634579E+09 | 631.80 | 01-MAY-07:10 | 0.241866E+10 | 2709.07 | 01-MAY-07:10 |
| June | 0.614109E+09 | 631.80 | 01-JUN-07:10 | 0.234064E+10 | 2709.07 | 01-JUN-07:10 |
| July | 0.634579E+09 | 631.80 | 01-JUL-07:10 | 0.241866E+10 | 2709.07 | 01-JUL-07:10 |
| August | 0.634579E+09 | 631.80 | 01-AUG-07:10 | 0.241866E+10 | 2709.07 | 01-AUG-07:10 |
| September | 0.614109E+09 | 631.80 | 01-SEP-07:10 | 0.234064E+10 | 2709.07 | 01-SEP-07:10 |
| October | 0.634579E+09 | 631.80 | 01-OCT-07:10 | 0.241866E+10 | 2709.07 | 01-OCT-07:10 |
| November | 0.614109E+09 | 631.80 | 01-NOV-07:10 | 0.234064E+10 | 2709.07 | 01-NOV-07:10 |
| December | 0.634579E+09 | 631.80 | 01-DEC-08:09 | 0.241866E+10 | 2709.07 | 01-DEC-08:09 |
| Annual Sum or Average | 0.747166E+10 | 0.284778E+11 | ||||
| Minimum of Months | 0.573168E+09 | 631.80 | 0.218460E+10 | 2709.07 | ||
| Maximum of Months | 0.634579E+09 | 631.80 | 0.241866E+10 | 2709.07 |
Report: ZoneElectricSummaryMonthly
For: ELEVATORCOREFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.123180E+11 | 7633.46 | 01-JAN-07:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.111260E+11 | 7633.46 | 01-FEB-07:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.123180E+11 | 7633.46 | 01-MAR-07:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.119207E+11 | 7633.46 | 01-APR-06:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.123180E+11 | 7633.46 | 01-MAY-06:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.119207E+11 | 7633.46 | 01-JUN-06:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.123180E+11 | 7633.46 | 01-JUL-06:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.123180E+11 | 7633.46 | 01-AUG-06:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.119207E+11 | 7633.46 | 01-SEP-06:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.123180E+11 | 7633.46 | 01-OCT-06:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.119207E+11 | 7633.46 | 01-NOV-06:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.123180E+11 | 7633.46 | 01-DEC-07:10 |
| Annual Sum or Average | 0.00 | 0.145035E+12 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.111260E+11 | 7633.46 | ||
| Maximum of Months | 0.00 | 0.00 | 0.123180E+11 | 7633.46 |
Report: ZoneElectricSummaryMonthly
For: EXERCISECENTERFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.564070E+09 | 315.90 | 01-JAN-07:10 | 0.710346E+09 | 606.20 | 01-JAN-07:10 |
| February | 0.509483E+09 | 315.90 | 01-FEB-07:10 | 0.641603E+09 | 606.20 | 01-FEB-07:10 |
| March | 0.564070E+09 | 315.90 | 01-MAR-07:10 | 0.710346E+09 | 606.20 | 01-MAR-07:10 |
| April | 0.545875E+09 | 315.90 | 01-APR-06:10 | 0.687432E+09 | 606.20 | 01-APR-06:10 |
| May | 0.564070E+09 | 315.90 | 01-MAY-06:10 | 0.710346E+09 | 606.20 | 01-MAY-06:10 |
| June | 0.545875E+09 | 315.90 | 01-JUN-06:10 | 0.687432E+09 | 606.20 | 01-JUN-06:10 |
| July | 0.564070E+09 | 315.90 | 01-JUL-06:10 | 0.710346E+09 | 606.20 | 01-JUL-06:10 |
| August | 0.564070E+09 | 315.90 | 01-AUG-06:10 | 0.710346E+09 | 606.20 | 01-AUG-06:10 |
| September | 0.545875E+09 | 315.90 | 01-SEP-06:10 | 0.687432E+09 | 606.20 | 01-SEP-06:10 |
| October | 0.564070E+09 | 315.90 | 01-OCT-06:10 | 0.710346E+09 | 606.20 | 01-OCT-06:10 |
| November | 0.545875E+09 | 315.90 | 01-NOV-06:10 | 0.687432E+09 | 606.20 | 01-NOV-06:10 |
| December | 0.564070E+09 | 315.90 | 01-DEC-07:10 | 0.710346E+09 | 606.20 | 01-DEC-07:10 |
| Annual Sum or Average | 0.664148E+10 | 0.836375E+10 | ||||
| Minimum of Months | 0.509483E+09 | 315.90 | 0.641603E+09 | 606.20 | ||
| Maximum of Months | 0.564070E+09 | 315.90 | 0.710346E+09 | 606.20 |
Report: ZoneElectricSummaryMonthly
For: FRONTOFFICEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.270942E+10 | 1389.96 | 01-JAN-08:09 | 0.248187E+10 | 1663.95 | 03-JAN-10:09 |
| February | 0.244722E+10 | 1389.96 | 01-FEB-08:09 | 0.225598E+10 | 1663.95 | 01-FEB-10:09 |
| March | 0.270942E+10 | 1389.96 | 01-MAR-08:09 | 0.252769E+10 | 1663.95 | 01-MAR-10:09 |
| April | 0.262202E+10 | 1389.96 | 01-APR-07:10 | 0.241166E+10 | 1663.95 | 03-APR-09:09 |
| May | 0.270942E+10 | 1389.96 | 01-MAY-07:10 | 0.251242E+10 | 1663.95 | 01-MAY-09:09 |
| June | 0.262202E+10 | 1389.96 | 01-JUN-07:10 | 0.244221E+10 | 1663.95 | 01-JUN-09:09 |
| July | 0.270942E+10 | 1389.96 | 01-JUL-07:10 | 0.248187E+10 | 1663.95 | 03-JUL-09:09 |
| August | 0.270942E+10 | 1389.96 | 01-AUG-07:10 | 0.252769E+10 | 1663.95 | 01-AUG-09:09 |
| September | 0.262202E+10 | 1389.96 | 01-SEP-07:10 | 0.241166E+10 | 1663.95 | 01-SEP-09:09 |
| October | 0.270942E+10 | 1389.96 | 01-OCT-07:10 | 0.249714E+10 | 1663.95 | 02-OCT-09:09 |
| November | 0.262202E+10 | 1389.96 | 01-NOV-07:10 | 0.241166E+10 | 1663.95 | 01-NOV-09:09 |
| December | 0.270942E+10 | 1389.96 | 01-DEC-08:09 | 0.248187E+10 | 1663.95 | 01-DEC-10:09 |
| Annual Sum or Average | 0.319012E+11 | 0.294437E+11 | ||||
| Minimum of Months | 0.244722E+10 | 1389.96 | 0.225598E+10 | 1663.95 | ||
| Maximum of Months | 0.270942E+10 | 1389.96 | 0.252769E+10 | 1663.95 |
Report: ZoneElectricSummaryMonthly
For: FRONTSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.347120E+09 | 129.60 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.313528E+09 | 129.60 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.347120E+09 | 129.60 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.335923E+09 | 129.60 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.347120E+09 | 129.60 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.335923E+09 | 129.60 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.347120E+09 | 129.60 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.347120E+09 | 129.60 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.335923E+09 | 129.60 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.347120E+09 | 129.60 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.335923E+09 | 129.60 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.347120E+09 | 129.60 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.408706E+10 | 0.00 | ||||
| Minimum of Months | 0.313528E+09 | 129.60 | 0.00 | 0.00 | ||
| Maximum of Months | 0.347120E+09 | 129.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: FRONTSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 72316730.02 | 43.20 | 01-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 65318336.79 | 43.20 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 72316730.02 | 43.20 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 69983932.27 | 43.20 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 72316730.02 | 43.20 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 69983932.27 | 43.20 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 72316730.02 | 43.20 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 72316730.02 | 43.20 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 69983932.27 | 43.20 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 72316730.02 | 43.20 | 01-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 69983932.27 | 43.20 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 72316730.02 | 43.20 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.851471E+09 | 0.00 | ||||
| Minimum of Months | 65318336.79 | 43.20 | 0.00 | 0.00 | ||
| Maximum of Months | 72316730.02 | 43.20 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: REARSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.347203E+09 | 129.63 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.313603E+09 | 129.63 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.347203E+09 | 129.63 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.336003E+09 | 129.63 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.347203E+09 | 129.63 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.336003E+09 | 129.63 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.347203E+09 | 129.63 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.347203E+09 | 129.63 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.336003E+09 | 129.63 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.347203E+09 | 129.63 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.336003E+09 | 129.63 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.347203E+09 | 129.63 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.408804E+10 | 0.00 | ||||
| Minimum of Months | 0.313603E+09 | 129.63 | 0.00 | 0.00 | ||
| Maximum of Months | 0.347203E+09 | 129.63 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: CORRIDORFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.180793E+10 | 675.01 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.163297E+10 | 675.01 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.180793E+10 | 675.01 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.174961E+10 | 675.01 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.180793E+10 | 675.01 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.174961E+10 | 675.01 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.180793E+10 | 675.01 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.180793E+10 | 675.01 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.174961E+10 | 675.01 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.180793E+10 | 675.01 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.174961E+10 | 675.01 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.180793E+10 | 675.01 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.212870E+11 | 0.00 | ||||
| Minimum of Months | 0.163297E+10 | 675.01 | 0.00 | 0.00 | ||
| Maximum of Months | 0.180793E+10 | 675.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: REARSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.115743E+09 | 69.14 | 01-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.104542E+09 | 69.14 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.115743E+09 | 69.14 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.112009E+09 | 69.14 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.115743E+09 | 69.14 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.112009E+09 | 69.14 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.115743E+09 | 69.14 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.115743E+09 | 69.14 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.112009E+09 | 69.14 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.115743E+09 | 69.14 | 01-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.112009E+09 | 69.14 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.115743E+09 | 69.14 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.136278E+10 | 0.00 | ||||
| Minimum of Months | 0.104542E+09 | 69.14 | 0.00 | 0.00 | ||
| Maximum of Months | 0.115743E+09 | 69.14 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM201
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM202_205
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.177615E+10 | 1600.67 | 01-JAN-19:10 | 0.121394E+10 | 1396.30 | 01-JAN-08:09 |
| February | 0.159769E+10 | 1600.67 | 01-FEB-20:10 | 0.109615E+10 | 1396.30 | 01-FEB-07:10 |
| March | 0.175506E+10 | 1600.67 | 01-MAR-20:10 | 0.121294E+10 | 1396.30 | 01-MAR-07:10 |
| April | 0.171409E+10 | 1600.67 | 01-APR-18:10 | 0.117457E+10 | 1396.30 | 01-APR-07:10 |
| May | 0.176209E+10 | 1600.67 | 01-MAY-19:10 | 0.121327E+10 | 1396.30 | 01-MAY-06:10 |
| June | 0.170049E+10 | 1600.67 | 01-JUN-19:10 | 0.117390E+10 | 1396.30 | 01-JUN-06:10 |
| July | 0.177592E+10 | 1600.67 | 01-JUL-18:10 | 0.121394E+10 | 1396.30 | 01-JUL-07:10 |
| August | 0.175506E+10 | 1600.67 | 01-AUG-19:10 | 0.121294E+10 | 1396.30 | 01-AUG-06:10 |
| September | 0.171455E+10 | 1600.67 | 01-SEP-19:10 | 0.117457E+10 | 1396.30 | 01-SEP-06:10 |
| October | 0.176889E+10 | 1600.67 | 01-OCT-18:10 | 0.121361E+10 | 1396.30 | 01-OCT-07:10 |
| November | 0.171432E+10 | 1600.67 | 01-NOV-19:10 | 0.117457E+10 | 1396.30 | 01-NOV-06:10 |
| December | 0.177615E+10 | 1600.67 | 01-DEC-20:10 | 0.121394E+10 | 1396.30 | 01-DEC-07:10 |
| Annual Sum or Average | 0.208105E+11 | 0.142883E+11 | ||||
| Minimum of Months | 0.159769E+10 | 1600.67 | 0.109615E+10 | 1396.30 | ||
| Maximum of Months | 0.177615E+10 | 1600.67 | 0.121394E+10 | 1396.30 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM206_208
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.143458E+10 | 1292.85 | 01-JAN-19:10 | 0.980492E+09 | 1127.78 | 01-JAN-08:09 |
| February | 0.129044E+10 | 1292.85 | 01-FEB-20:10 | 0.885353E+09 | 1127.78 | 01-FEB-07:10 |
| March | 0.141755E+10 | 1292.85 | 01-MAR-20:10 | 0.979680E+09 | 1127.78 | 01-MAR-07:10 |
| April | 0.138446E+10 | 1292.85 | 01-APR-18:10 | 0.948689E+09 | 1127.78 | 01-APR-07:10 |
| May | 0.142323E+10 | 1292.85 | 01-MAY-19:10 | 0.979951E+09 | 1127.78 | 01-MAY-06:10 |
| June | 0.137347E+10 | 1292.85 | 01-JUN-19:10 | 0.948148E+09 | 1127.78 | 01-JUN-06:10 |
| July | 0.143440E+10 | 1292.85 | 01-JUL-18:10 | 0.980492E+09 | 1127.78 | 01-JUL-07:10 |
| August | 0.141755E+10 | 1292.85 | 01-AUG-19:10 | 0.979680E+09 | 1127.78 | 01-AUG-06:10 |
| September | 0.138483E+10 | 1292.85 | 01-SEP-19:10 | 0.948689E+09 | 1127.78 | 01-SEP-06:10 |
| October | 0.142872E+10 | 1292.85 | 01-OCT-18:10 | 0.980222E+09 | 1127.78 | 01-OCT-07:10 |
| November | 0.138464E+10 | 1292.85 | 01-NOV-19:10 | 0.948689E+09 | 1127.78 | 01-NOV-06:10 |
| December | 0.143458E+10 | 1292.85 | 01-DEC-20:10 | 0.980492E+09 | 1127.78 | 01-DEC-07:10 |
| Annual Sum or Average | 0.168085E+11 | 0.115406E+11 | ||||
| Minimum of Months | 0.129044E+10 | 1292.85 | 0.885353E+09 | 1127.78 | ||
| Maximum of Months | 0.143458E+10 | 1292.85 | 0.980492E+09 | 1127.78 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM209_212
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.177615E+10 | 1600.67 | 01-JAN-19:10 | 0.121394E+10 | 1396.30 | 01-JAN-08:09 |
| February | 0.159769E+10 | 1600.67 | 01-FEB-20:10 | 0.109615E+10 | 1396.30 | 01-FEB-07:10 |
| March | 0.175506E+10 | 1600.67 | 01-MAR-20:10 | 0.121294E+10 | 1396.30 | 01-MAR-07:10 |
| April | 0.171409E+10 | 1600.67 | 01-APR-18:10 | 0.117457E+10 | 1396.30 | 01-APR-07:10 |
| May | 0.176209E+10 | 1600.67 | 01-MAY-19:10 | 0.121327E+10 | 1396.30 | 01-MAY-06:10 |
| June | 0.170049E+10 | 1600.67 | 01-JUN-19:10 | 0.117390E+10 | 1396.30 | 01-JUN-06:10 |
| July | 0.177592E+10 | 1600.67 | 01-JUL-18:10 | 0.121394E+10 | 1396.30 | 01-JUL-07:10 |
| August | 0.175506E+10 | 1600.67 | 01-AUG-19:10 | 0.121294E+10 | 1396.30 | 01-AUG-06:10 |
| September | 0.171455E+10 | 1600.67 | 01-SEP-19:10 | 0.117457E+10 | 1396.30 | 01-SEP-06:10 |
| October | 0.176889E+10 | 1600.67 | 01-OCT-18:10 | 0.121361E+10 | 1396.30 | 01-OCT-07:10 |
| November | 0.171432E+10 | 1600.67 | 01-NOV-19:10 | 0.117457E+10 | 1396.30 | 01-NOV-06:10 |
| December | 0.177615E+10 | 1600.67 | 01-DEC-20:10 | 0.121394E+10 | 1396.30 | 01-DEC-07:10 |
| Annual Sum or Average | 0.208105E+11 | 0.142883E+11 | ||||
| Minimum of Months | 0.159769E+10 | 1600.67 | 0.109615E+10 | 1396.30 | ||
| Maximum of Months | 0.177615E+10 | 1600.67 | 0.121394E+10 | 1396.30 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM213
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.444038E+09 | 400.17 | 01-JAN-19:10 | 0.303486E+09 | 349.07 | 01-JAN-08:09 |
| February | 0.399422E+09 | 400.17 | 01-FEB-20:10 | 0.274038E+09 | 349.07 | 01-FEB-07:10 |
| March | 0.438765E+09 | 400.17 | 01-MAR-20:10 | 0.303234E+09 | 349.07 | 01-MAR-07:10 |
| April | 0.428522E+09 | 400.17 | 01-APR-18:10 | 0.293642E+09 | 349.07 | 01-APR-07:10 |
| May | 0.440523E+09 | 400.17 | 01-MAY-19:10 | 0.303318E+09 | 349.07 | 01-MAY-06:10 |
| June | 0.425123E+09 | 400.17 | 01-JUN-19:10 | 0.293474E+09 | 349.07 | 01-JUN-06:10 |
| July | 0.443980E+09 | 400.17 | 01-JUL-18:10 | 0.303486E+09 | 349.07 | 01-JUL-07:10 |
| August | 0.438765E+09 | 400.17 | 01-AUG-19:10 | 0.303234E+09 | 349.07 | 01-AUG-06:10 |
| September | 0.428638E+09 | 400.17 | 01-SEP-19:10 | 0.293642E+09 | 349.07 | 01-SEP-06:10 |
| October | 0.442223E+09 | 400.17 | 01-OCT-18:10 | 0.303402E+09 | 349.07 | 01-OCT-07:10 |
| November | 0.428580E+09 | 400.17 | 01-NOV-19:10 | 0.293642E+09 | 349.07 | 01-NOV-06:10 |
| December | 0.444038E+09 | 400.17 | 01-DEC-20:10 | 0.303486E+09 | 349.07 | 01-DEC-07:10 |
| Annual Sum or Average | 0.520262E+10 | 0.357208E+10 | ||||
| Minimum of Months | 0.399422E+09 | 400.17 | 0.274038E+09 | 349.07 | ||
| Maximum of Months | 0.444038E+09 | 400.17 | 0.303486E+09 | 349.07 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM214
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.444006E+09 | 400.14 | 01-JAN-19:10 | 0.303464E+09 | 349.05 | 01-JAN-08:09 |
| February | 0.399394E+09 | 400.14 | 01-FEB-20:10 | 0.274018E+09 | 349.05 | 01-FEB-07:10 |
| March | 0.438734E+09 | 400.14 | 01-MAR-20:10 | 0.303213E+09 | 349.05 | 01-MAR-07:10 |
| April | 0.428492E+09 | 400.14 | 01-APR-18:10 | 0.293621E+09 | 349.05 | 01-APR-07:10 |
| May | 0.440491E+09 | 400.14 | 01-MAY-19:10 | 0.303297E+09 | 349.05 | 01-MAY-06:10 |
| June | 0.425092E+09 | 400.14 | 01-JUN-19:10 | 0.293453E+09 | 349.05 | 01-JUN-06:10 |
| July | 0.443949E+09 | 400.14 | 01-JUL-18:10 | 0.303464E+09 | 349.05 | 01-JUL-07:10 |
| August | 0.438734E+09 | 400.14 | 01-AUG-19:10 | 0.303213E+09 | 349.05 | 01-AUG-06:10 |
| September | 0.428607E+09 | 400.14 | 01-SEP-19:10 | 0.293621E+09 | 349.05 | 01-SEP-06:10 |
| October | 0.442191E+09 | 400.14 | 01-OCT-18:10 | 0.303380E+09 | 349.05 | 01-OCT-07:10 |
| November | 0.428550E+09 | 400.14 | 01-NOV-19:10 | 0.293621E+09 | 349.05 | 01-NOV-06:10 |
| December | 0.444006E+09 | 400.14 | 01-DEC-20:10 | 0.303464E+09 | 349.05 | 01-DEC-07:10 |
| Annual Sum or Average | 0.520225E+10 | 0.357183E+10 | ||||
| Minimum of Months | 0.399394E+09 | 400.14 | 0.274018E+09 | 349.05 | ||
| Maximum of Months | 0.444006E+09 | 400.14 | 0.303464E+09 | 349.05 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM215_218
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: ELEVATORCOREFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM219
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.444006E+09 | 400.14 | 01-JAN-19:10 | 0.303464E+09 | 349.05 | 01-JAN-08:09 |
| February | 0.399394E+09 | 400.14 | 01-FEB-20:10 | 0.274018E+09 | 349.05 | 01-FEB-07:10 |
| March | 0.438734E+09 | 400.14 | 01-MAR-20:10 | 0.303213E+09 | 349.05 | 01-MAR-07:10 |
| April | 0.428492E+09 | 400.14 | 01-APR-18:10 | 0.293621E+09 | 349.05 | 01-APR-07:10 |
| May | 0.440491E+09 | 400.14 | 01-MAY-19:10 | 0.303297E+09 | 349.05 | 01-MAY-06:10 |
| June | 0.425092E+09 | 400.14 | 01-JUN-19:10 | 0.293453E+09 | 349.05 | 01-JUN-06:10 |
| July | 0.443949E+09 | 400.14 | 01-JUL-18:10 | 0.303464E+09 | 349.05 | 01-JUL-07:10 |
| August | 0.438734E+09 | 400.14 | 01-AUG-19:10 | 0.303213E+09 | 349.05 | 01-AUG-06:10 |
| September | 0.428607E+09 | 400.14 | 01-SEP-19:10 | 0.293621E+09 | 349.05 | 01-SEP-06:10 |
| October | 0.442191E+09 | 400.14 | 01-OCT-18:10 | 0.303380E+09 | 349.05 | 01-OCT-07:10 |
| November | 0.428550E+09 | 400.14 | 01-NOV-19:10 | 0.293621E+09 | 349.05 | 01-NOV-06:10 |
| December | 0.444006E+09 | 400.14 | 01-DEC-20:10 | 0.303464E+09 | 349.05 | 01-DEC-07:10 |
| Annual Sum or Average | 0.520225E+10 | 0.357183E+10 | ||||
| Minimum of Months | 0.399394E+09 | 400.14 | 0.274018E+09 | 349.05 | ||
| Maximum of Months | 0.444006E+09 | 400.14 | 0.303464E+09 | 349.05 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM220_223
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.177603E+10 | 1600.56 | 01-JAN-19:10 | 0.121386E+10 | 1396.20 | 01-JAN-08:09 |
| February | 0.159758E+10 | 1600.56 | 01-FEB-20:10 | 0.109607E+10 | 1396.20 | 01-FEB-07:10 |
| March | 0.175494E+10 | 1600.56 | 01-MAR-20:10 | 0.121285E+10 | 1396.20 | 01-MAR-07:10 |
| April | 0.171397E+10 | 1600.56 | 01-APR-18:10 | 0.117448E+10 | 1396.20 | 01-APR-07:10 |
| May | 0.176197E+10 | 1600.56 | 01-MAY-19:10 | 0.121319E+10 | 1396.20 | 01-MAY-06:10 |
| June | 0.170037E+10 | 1600.56 | 01-JUN-19:10 | 0.117381E+10 | 1396.20 | 01-JUN-06:10 |
| July | 0.177579E+10 | 1600.56 | 01-JUL-18:10 | 0.121386E+10 | 1396.20 | 01-JUL-07:10 |
| August | 0.175494E+10 | 1600.56 | 01-AUG-19:10 | 0.121285E+10 | 1396.20 | 01-AUG-06:10 |
| September | 0.171443E+10 | 1600.56 | 01-SEP-19:10 | 0.117448E+10 | 1396.20 | 01-SEP-06:10 |
| October | 0.176876E+10 | 1600.56 | 01-OCT-18:10 | 0.121352E+10 | 1396.20 | 01-OCT-07:10 |
| November | 0.171420E+10 | 1600.56 | 01-NOV-19:10 | 0.117448E+10 | 1396.20 | 01-NOV-06:10 |
| December | 0.177603E+10 | 1600.56 | 01-DEC-20:10 | 0.121386E+10 | 1396.20 | 01-DEC-07:10 |
| Annual Sum or Average | 0.208090E+11 | 0.142873E+11 | ||||
| Minimum of Months | 0.159758E+10 | 1600.56 | 0.109607E+10 | 1396.20 | ||
| Maximum of Months | 0.177603E+10 | 1600.56 | 0.121386E+10 | 1396.20 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM224
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.444006E+09 | 400.14 | 01-JAN-19:10 | 0.303464E+09 | 349.05 | 01-JAN-08:09 |
| February | 0.399394E+09 | 400.14 | 01-FEB-20:10 | 0.274018E+09 | 349.05 | 01-FEB-07:10 |
| March | 0.438734E+09 | 400.14 | 01-MAR-20:10 | 0.303213E+09 | 349.05 | 01-MAR-07:10 |
| April | 0.428492E+09 | 400.14 | 01-APR-18:10 | 0.293621E+09 | 349.05 | 01-APR-07:10 |
| May | 0.440491E+09 | 400.14 | 01-MAY-19:10 | 0.303297E+09 | 349.05 | 01-MAY-06:10 |
| June | 0.425092E+09 | 400.14 | 01-JUN-19:10 | 0.293453E+09 | 349.05 | 01-JUN-06:10 |
| July | 0.443949E+09 | 400.14 | 01-JUL-18:10 | 0.303464E+09 | 349.05 | 01-JUL-07:10 |
| August | 0.438734E+09 | 400.14 | 01-AUG-19:10 | 0.303213E+09 | 349.05 | 01-AUG-06:10 |
| September | 0.428607E+09 | 400.14 | 01-SEP-19:10 | 0.293621E+09 | 349.05 | 01-SEP-06:10 |
| October | 0.442191E+09 | 400.14 | 01-OCT-18:10 | 0.303380E+09 | 349.05 | 01-OCT-07:10 |
| November | 0.428550E+09 | 400.14 | 01-NOV-19:10 | 0.293621E+09 | 349.05 | 01-NOV-06:10 |
| December | 0.444006E+09 | 400.14 | 01-DEC-20:10 | 0.303464E+09 | 349.05 | 01-DEC-07:10 |
| Annual Sum or Average | 0.520225E+10 | 0.357183E+10 | ||||
| Minimum of Months | 0.399394E+09 | 400.14 | 0.274018E+09 | 349.05 | ||
| Maximum of Months | 0.444006E+09 | 400.14 | 0.303464E+09 | 349.05 |
Report: ZoneElectricSummaryMonthly
For: FRONTSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 72316730.02 | 43.20 | 01-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 65318336.79 | 43.20 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 72316730.02 | 43.20 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 69983932.27 | 43.20 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 72316730.02 | 43.20 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 69983932.27 | 43.20 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 72316730.02 | 43.20 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 72316730.02 | 43.20 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 69983932.27 | 43.20 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 72316730.02 | 43.20 | 01-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 69983932.27 | 43.20 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 72316730.02 | 43.20 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.851471E+09 | 0.00 | ||||
| Minimum of Months | 65318336.79 | 43.20 | 0.00 | 0.00 | ||
| Maximum of Months | 72316730.02 | 43.20 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: FRONTSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.347120E+09 | 129.60 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.313528E+09 | 129.60 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.347120E+09 | 129.60 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.335923E+09 | 129.60 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.347120E+09 | 129.60 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.335923E+09 | 129.60 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.347120E+09 | 129.60 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.347120E+09 | 129.60 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.335923E+09 | 129.60 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.347120E+09 | 129.60 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.335923E+09 | 129.60 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.347120E+09 | 129.60 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.408706E+10 | 0.00 | ||||
| Minimum of Months | 0.313528E+09 | 129.60 | 0.00 | 0.00 | ||
| Maximum of Months | 0.347120E+09 | 129.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: REARSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.347203E+09 | 129.63 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.313603E+09 | 129.63 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.347203E+09 | 129.63 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.336003E+09 | 129.63 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.347203E+09 | 129.63 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.336003E+09 | 129.63 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.347203E+09 | 129.63 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.347203E+09 | 129.63 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.336003E+09 | 129.63 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.347203E+09 | 129.63 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.336003E+09 | 129.63 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.347203E+09 | 129.63 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.408804E+10 | 0.00 | ||||
| Minimum of Months | 0.313603E+09 | 129.63 | 0.00 | 0.00 | ||
| Maximum of Months | 0.347203E+09 | 129.63 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: CORRIDORFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.180793E+10 | 675.01 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.163297E+10 | 675.01 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.180793E+10 | 675.01 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.174961E+10 | 675.01 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.180793E+10 | 675.01 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.174961E+10 | 675.01 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.180793E+10 | 675.01 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.180793E+10 | 675.01 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.174961E+10 | 675.01 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.180793E+10 | 675.01 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.174961E+10 | 675.01 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.180793E+10 | 675.01 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.212870E+11 | 0.00 | ||||
| Minimum of Months | 0.163297E+10 | 675.01 | 0.00 | 0.00 | ||
| Maximum of Months | 0.180793E+10 | 675.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: REARSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.115743E+09 | 69.14 | 01-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.104542E+09 | 69.14 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.115743E+09 | 69.14 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.112009E+09 | 69.14 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.115743E+09 | 69.14 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.112009E+09 | 69.14 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.115743E+09 | 69.14 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.115743E+09 | 69.14 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.112009E+09 | 69.14 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.115743E+09 | 69.14 | 01-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.112009E+09 | 69.14 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.115743E+09 | 69.14 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.136278E+10 | 0.00 | ||||
| Minimum of Months | 0.104542E+09 | 69.14 | 0.00 | 0.00 | ||
| Maximum of Months | 0.115743E+09 | 69.14 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM301
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM302_305
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM306_308
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM309_312
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.177615E+10 | 1600.67 | 01-JAN-19:10 | 0.121394E+10 | 1396.30 | 01-JAN-08:09 |
| February | 0.159769E+10 | 1600.67 | 01-FEB-20:10 | 0.109615E+10 | 1396.30 | 01-FEB-07:10 |
| March | 0.175506E+10 | 1600.67 | 01-MAR-20:10 | 0.121294E+10 | 1396.30 | 01-MAR-07:10 |
| April | 0.171409E+10 | 1600.67 | 01-APR-18:10 | 0.117457E+10 | 1396.30 | 01-APR-07:10 |
| May | 0.176209E+10 | 1600.67 | 01-MAY-19:10 | 0.121327E+10 | 1396.30 | 01-MAY-06:10 |
| June | 0.170049E+10 | 1600.67 | 01-JUN-19:10 | 0.117390E+10 | 1396.30 | 01-JUN-06:10 |
| July | 0.177592E+10 | 1600.67 | 01-JUL-18:10 | 0.121394E+10 | 1396.30 | 01-JUL-07:10 |
| August | 0.175506E+10 | 1600.67 | 01-AUG-19:10 | 0.121294E+10 | 1396.30 | 01-AUG-06:10 |
| September | 0.171455E+10 | 1600.67 | 01-SEP-19:10 | 0.117457E+10 | 1396.30 | 01-SEP-06:10 |
| October | 0.176889E+10 | 1600.67 | 01-OCT-18:10 | 0.121361E+10 | 1396.30 | 01-OCT-07:10 |
| November | 0.171432E+10 | 1600.67 | 01-NOV-19:10 | 0.117457E+10 | 1396.30 | 01-NOV-06:10 |
| December | 0.177615E+10 | 1600.67 | 01-DEC-20:10 | 0.121394E+10 | 1396.30 | 01-DEC-07:10 |
| Annual Sum or Average | 0.208105E+11 | 0.142883E+11 | ||||
| Minimum of Months | 0.159769E+10 | 1600.67 | 0.109615E+10 | 1396.30 | ||
| Maximum of Months | 0.177615E+10 | 1600.67 | 0.121394E+10 | 1396.30 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM313
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM314
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.444006E+09 | 400.14 | 01-JAN-19:10 | 0.303464E+09 | 349.05 | 01-JAN-08:09 |
| February | 0.399394E+09 | 400.14 | 01-FEB-20:10 | 0.274018E+09 | 349.05 | 01-FEB-07:10 |
| March | 0.438734E+09 | 400.14 | 01-MAR-20:10 | 0.303213E+09 | 349.05 | 01-MAR-07:10 |
| April | 0.428492E+09 | 400.14 | 01-APR-18:10 | 0.293621E+09 | 349.05 | 01-APR-07:10 |
| May | 0.440491E+09 | 400.14 | 01-MAY-19:10 | 0.303297E+09 | 349.05 | 01-MAY-06:10 |
| June | 0.425092E+09 | 400.14 | 01-JUN-19:10 | 0.293453E+09 | 349.05 | 01-JUN-06:10 |
| July | 0.443949E+09 | 400.14 | 01-JUL-18:10 | 0.303464E+09 | 349.05 | 01-JUL-07:10 |
| August | 0.438734E+09 | 400.14 | 01-AUG-19:10 | 0.303213E+09 | 349.05 | 01-AUG-06:10 |
| September | 0.428607E+09 | 400.14 | 01-SEP-19:10 | 0.293621E+09 | 349.05 | 01-SEP-06:10 |
| October | 0.442191E+09 | 400.14 | 01-OCT-18:10 | 0.303380E+09 | 349.05 | 01-OCT-07:10 |
| November | 0.428550E+09 | 400.14 | 01-NOV-19:10 | 0.293621E+09 | 349.05 | 01-NOV-06:10 |
| December | 0.444006E+09 | 400.14 | 01-DEC-20:10 | 0.303464E+09 | 349.05 | 01-DEC-07:10 |
| Annual Sum or Average | 0.520225E+10 | 0.357183E+10 | ||||
| Minimum of Months | 0.399394E+09 | 400.14 | 0.274018E+09 | 349.05 | ||
| Maximum of Months | 0.444006E+09 | 400.14 | 0.303464E+09 | 349.05 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM315_318
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.177603E+10 | 1600.56 | 01-JAN-19:10 | 0.121386E+10 | 1396.20 | 01-JAN-08:09 |
| February | 0.159758E+10 | 1600.56 | 01-FEB-20:10 | 0.109607E+10 | 1396.20 | 01-FEB-07:10 |
| March | 0.175494E+10 | 1600.56 | 01-MAR-20:10 | 0.121285E+10 | 1396.20 | 01-MAR-07:10 |
| April | 0.171397E+10 | 1600.56 | 01-APR-18:10 | 0.117448E+10 | 1396.20 | 01-APR-07:10 |
| May | 0.176197E+10 | 1600.56 | 01-MAY-19:10 | 0.121319E+10 | 1396.20 | 01-MAY-06:10 |
| June | 0.170037E+10 | 1600.56 | 01-JUN-19:10 | 0.117381E+10 | 1396.20 | 01-JUN-06:10 |
| July | 0.177579E+10 | 1600.56 | 01-JUL-18:10 | 0.121386E+10 | 1396.20 | 01-JUL-07:10 |
| August | 0.175494E+10 | 1600.56 | 01-AUG-19:10 | 0.121285E+10 | 1396.20 | 01-AUG-06:10 |
| September | 0.171443E+10 | 1600.56 | 01-SEP-19:10 | 0.117448E+10 | 1396.20 | 01-SEP-06:10 |
| October | 0.176876E+10 | 1600.56 | 01-OCT-18:10 | 0.121352E+10 | 1396.20 | 01-OCT-07:10 |
| November | 0.171420E+10 | 1600.56 | 01-NOV-19:10 | 0.117448E+10 | 1396.20 | 01-NOV-06:10 |
| December | 0.177603E+10 | 1600.56 | 01-DEC-20:10 | 0.121386E+10 | 1396.20 | 01-DEC-07:10 |
| Annual Sum or Average | 0.208090E+11 | 0.142873E+11 | ||||
| Minimum of Months | 0.159758E+10 | 1600.56 | 0.109607E+10 | 1396.20 | ||
| Maximum of Months | 0.177603E+10 | 1600.56 | 0.121386E+10 | 1396.20 |
Report: ZoneElectricSummaryMonthly
For: ELEVATORCOREFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM319
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM320_323
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.177603E+10 | 1600.56 | 01-JAN-19:10 | 0.121386E+10 | 1396.20 | 01-JAN-08:09 |
| February | 0.159758E+10 | 1600.56 | 01-FEB-20:10 | 0.109607E+10 | 1396.20 | 01-FEB-07:10 |
| March | 0.175494E+10 | 1600.56 | 01-MAR-20:10 | 0.121285E+10 | 1396.20 | 01-MAR-07:10 |
| April | 0.171397E+10 | 1600.56 | 01-APR-18:10 | 0.117448E+10 | 1396.20 | 01-APR-07:10 |
| May | 0.176197E+10 | 1600.56 | 01-MAY-19:10 | 0.121319E+10 | 1396.20 | 01-MAY-06:10 |
| June | 0.170037E+10 | 1600.56 | 01-JUN-19:10 | 0.117381E+10 | 1396.20 | 01-JUN-06:10 |
| July | 0.177579E+10 | 1600.56 | 01-JUL-18:10 | 0.121386E+10 | 1396.20 | 01-JUL-07:10 |
| August | 0.175494E+10 | 1600.56 | 01-AUG-19:10 | 0.121285E+10 | 1396.20 | 01-AUG-06:10 |
| September | 0.171443E+10 | 1600.56 | 01-SEP-19:10 | 0.117448E+10 | 1396.20 | 01-SEP-06:10 |
| October | 0.176876E+10 | 1600.56 | 01-OCT-18:10 | 0.121352E+10 | 1396.20 | 01-OCT-07:10 |
| November | 0.171420E+10 | 1600.56 | 01-NOV-19:10 | 0.117448E+10 | 1396.20 | 01-NOV-06:10 |
| December | 0.177603E+10 | 1600.56 | 01-DEC-20:10 | 0.121386E+10 | 1396.20 | 01-DEC-07:10 |
| Annual Sum or Average | 0.208090E+11 | 0.142873E+11 | ||||
| Minimum of Months | 0.159758E+10 | 1600.56 | 0.109607E+10 | 1396.20 | ||
| Maximum of Months | 0.177603E+10 | 1600.56 | 0.121386E+10 | 1396.20 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM324
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: FRONTSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 72316730.02 | 43.20 | 01-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 65318336.79 | 43.20 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 72316730.02 | 43.20 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 69983932.27 | 43.20 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 72316730.02 | 43.20 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 69983932.27 | 43.20 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 72316730.02 | 43.20 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 72316730.02 | 43.20 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 69983932.27 | 43.20 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 72316730.02 | 43.20 | 01-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 69983932.27 | 43.20 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 72316730.02 | 43.20 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.851471E+09 | 0.00 | ||||
| Minimum of Months | 65318336.79 | 43.20 | 0.00 | 0.00 | ||
| Maximum of Months | 72316730.02 | 43.20 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: FRONTSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.347120E+09 | 129.60 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.313528E+09 | 129.60 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.347120E+09 | 129.60 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.335923E+09 | 129.60 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.347120E+09 | 129.60 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.335923E+09 | 129.60 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.347120E+09 | 129.60 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.347120E+09 | 129.60 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.335923E+09 | 129.60 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.347120E+09 | 129.60 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.335923E+09 | 129.60 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.347120E+09 | 129.60 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.408706E+10 | 0.00 | ||||
| Minimum of Months | 0.313528E+09 | 129.60 | 0.00 | 0.00 | ||
| Maximum of Months | 0.347120E+09 | 129.60 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: REARSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.347203E+09 | 129.63 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.313603E+09 | 129.63 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.347203E+09 | 129.63 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.336003E+09 | 129.63 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.347203E+09 | 129.63 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.336003E+09 | 129.63 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.347203E+09 | 129.63 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.347203E+09 | 129.63 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.336003E+09 | 129.63 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.347203E+09 | 129.63 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.336003E+09 | 129.63 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.347203E+09 | 129.63 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.408804E+10 | 0.00 | ||||
| Minimum of Months | 0.313603E+09 | 129.63 | 0.00 | 0.00 | ||
| Maximum of Months | 0.347203E+09 | 129.63 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: CORRIDORFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.180793E+10 | 675.01 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.163297E+10 | 675.01 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.180793E+10 | 675.01 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.174961E+10 | 675.01 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.180793E+10 | 675.01 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.174961E+10 | 675.01 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.180793E+10 | 675.01 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.180793E+10 | 675.01 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.174961E+10 | 675.01 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.180793E+10 | 675.01 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.174961E+10 | 675.01 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.180793E+10 | 675.01 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.212870E+11 | 0.00 | ||||
| Minimum of Months | 0.163297E+10 | 675.01 | 0.00 | 0.00 | ||
| Maximum of Months | 0.180793E+10 | 675.01 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: REARSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.115743E+09 | 69.14 | 01-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.104542E+09 | 69.14 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.115743E+09 | 69.14 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.112009E+09 | 69.14 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.115743E+09 | 69.14 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.112009E+09 | 69.14 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.115743E+09 | 69.14 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.115743E+09 | 69.14 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.112009E+09 | 69.14 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.115743E+09 | 69.14 | 01-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.112009E+09 | 69.14 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.115743E+09 | 69.14 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.136278E+10 | 0.00 | ||||
| Minimum of Months | 0.104542E+09 | 69.14 | 0.00 | 0.00 | ||
| Maximum of Months | 0.115743E+09 | 69.14 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM401
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.444038E+09 | 400.17 | 01-JAN-19:10 | 0.303486E+09 | 349.07 | 01-JAN-08:09 |
| February | 0.399422E+09 | 400.17 | 01-FEB-20:10 | 0.274038E+09 | 349.07 | 01-FEB-07:10 |
| March | 0.438765E+09 | 400.17 | 01-MAR-20:10 | 0.303234E+09 | 349.07 | 01-MAR-07:10 |
| April | 0.428522E+09 | 400.17 | 01-APR-18:10 | 0.293642E+09 | 349.07 | 01-APR-07:10 |
| May | 0.440523E+09 | 400.17 | 01-MAY-19:10 | 0.303318E+09 | 349.07 | 01-MAY-06:10 |
| June | 0.425123E+09 | 400.17 | 01-JUN-19:10 | 0.293474E+09 | 349.07 | 01-JUN-06:10 |
| July | 0.443980E+09 | 400.17 | 01-JUL-18:10 | 0.303486E+09 | 349.07 | 01-JUL-07:10 |
| August | 0.438765E+09 | 400.17 | 01-AUG-19:10 | 0.303234E+09 | 349.07 | 01-AUG-06:10 |
| September | 0.428638E+09 | 400.17 | 01-SEP-19:10 | 0.293642E+09 | 349.07 | 01-SEP-06:10 |
| October | 0.442223E+09 | 400.17 | 01-OCT-18:10 | 0.303402E+09 | 349.07 | 01-OCT-07:10 |
| November | 0.428580E+09 | 400.17 | 01-NOV-19:10 | 0.293642E+09 | 349.07 | 01-NOV-06:10 |
| December | 0.444038E+09 | 400.17 | 01-DEC-20:10 | 0.303486E+09 | 349.07 | 01-DEC-07:10 |
| Annual Sum or Average | 0.520262E+10 | 0.357208E+10 | ||||
| Minimum of Months | 0.399422E+09 | 400.17 | 0.274038E+09 | 349.07 | ||
| Maximum of Months | 0.444038E+09 | 400.17 | 0.303486E+09 | 349.07 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM402_405
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM406_408
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM409_412
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.177615E+10 | 1600.67 | 01-JAN-19:10 | 0.121394E+10 | 1396.30 | 01-JAN-08:09 |
| February | 0.159769E+10 | 1600.67 | 01-FEB-20:10 | 0.109615E+10 | 1396.30 | 01-FEB-07:10 |
| March | 0.175506E+10 | 1600.67 | 01-MAR-20:10 | 0.121294E+10 | 1396.30 | 01-MAR-07:10 |
| April | 0.171409E+10 | 1600.67 | 01-APR-18:10 | 0.117457E+10 | 1396.30 | 01-APR-07:10 |
| May | 0.176209E+10 | 1600.67 | 01-MAY-19:10 | 0.121327E+10 | 1396.30 | 01-MAY-06:10 |
| June | 0.170049E+10 | 1600.67 | 01-JUN-19:10 | 0.117390E+10 | 1396.30 | 01-JUN-06:10 |
| July | 0.177592E+10 | 1600.67 | 01-JUL-18:10 | 0.121394E+10 | 1396.30 | 01-JUL-07:10 |
| August | 0.175506E+10 | 1600.67 | 01-AUG-19:10 | 0.121294E+10 | 1396.30 | 01-AUG-06:10 |
| September | 0.171455E+10 | 1600.67 | 01-SEP-19:10 | 0.117457E+10 | 1396.30 | 01-SEP-06:10 |
| October | 0.176889E+10 | 1600.67 | 01-OCT-18:10 | 0.121361E+10 | 1396.30 | 01-OCT-07:10 |
| November | 0.171432E+10 | 1600.67 | 01-NOV-19:10 | 0.117457E+10 | 1396.30 | 01-NOV-06:10 |
| December | 0.177615E+10 | 1600.67 | 01-DEC-20:10 | 0.121394E+10 | 1396.30 | 01-DEC-07:10 |
| Annual Sum or Average | 0.208105E+11 | 0.142883E+11 | ||||
| Minimum of Months | 0.159769E+10 | 1600.67 | 0.109615E+10 | 1396.30 | ||
| Maximum of Months | 0.177615E+10 | 1600.67 | 0.121394E+10 | 1396.30 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM413
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM414
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM415_418
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.177603E+10 | 1600.56 | 01-JAN-19:10 | 0.121386E+10 | 1396.20 | 01-JAN-08:09 |
| February | 0.159758E+10 | 1600.56 | 01-FEB-20:10 | 0.109607E+10 | 1396.20 | 01-FEB-07:10 |
| March | 0.175494E+10 | 1600.56 | 01-MAR-20:10 | 0.121285E+10 | 1396.20 | 01-MAR-07:10 |
| April | 0.171397E+10 | 1600.56 | 01-APR-18:10 | 0.117448E+10 | 1396.20 | 01-APR-07:10 |
| May | 0.176197E+10 | 1600.56 | 01-MAY-19:10 | 0.121319E+10 | 1396.20 | 01-MAY-06:10 |
| June | 0.170037E+10 | 1600.56 | 01-JUN-19:10 | 0.117381E+10 | 1396.20 | 01-JUN-06:10 |
| July | 0.177579E+10 | 1600.56 | 01-JUL-18:10 | 0.121386E+10 | 1396.20 | 01-JUL-07:10 |
| August | 0.175494E+10 | 1600.56 | 01-AUG-19:10 | 0.121285E+10 | 1396.20 | 01-AUG-06:10 |
| September | 0.171443E+10 | 1600.56 | 01-SEP-19:10 | 0.117448E+10 | 1396.20 | 01-SEP-06:10 |
| October | 0.176876E+10 | 1600.56 | 01-OCT-18:10 | 0.121352E+10 | 1396.20 | 01-OCT-07:10 |
| November | 0.171420E+10 | 1600.56 | 01-NOV-19:10 | 0.117448E+10 | 1396.20 | 01-NOV-06:10 |
| December | 0.177603E+10 | 1600.56 | 01-DEC-20:10 | 0.121386E+10 | 1396.20 | 01-DEC-07:10 |
| Annual Sum or Average | 0.208090E+11 | 0.142873E+11 | ||||
| Minimum of Months | 0.159758E+10 | 1600.56 | 0.109607E+10 | 1396.20 | ||
| Maximum of Months | 0.177603E+10 | 1600.56 | 0.121386E+10 | 1396.20 |
Report: ZoneElectricSummaryMonthly
For: ELEVATORCOREFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM419
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.444006E+09 | 400.14 | 01-JAN-19:10 | 0.303464E+09 | 349.05 | 01-JAN-08:09 |
| February | 0.399394E+09 | 400.14 | 01-FEB-20:10 | 0.274018E+09 | 349.05 | 01-FEB-07:10 |
| March | 0.438734E+09 | 400.14 | 01-MAR-20:10 | 0.303213E+09 | 349.05 | 01-MAR-07:10 |
| April | 0.428492E+09 | 400.14 | 01-APR-18:10 | 0.293621E+09 | 349.05 | 01-APR-07:10 |
| May | 0.440491E+09 | 400.14 | 01-MAY-19:10 | 0.303297E+09 | 349.05 | 01-MAY-06:10 |
| June | 0.425092E+09 | 400.14 | 01-JUN-19:10 | 0.293453E+09 | 349.05 | 01-JUN-06:10 |
| July | 0.443949E+09 | 400.14 | 01-JUL-18:10 | 0.303464E+09 | 349.05 | 01-JUL-07:10 |
| August | 0.438734E+09 | 400.14 | 01-AUG-19:10 | 0.303213E+09 | 349.05 | 01-AUG-06:10 |
| September | 0.428607E+09 | 400.14 | 01-SEP-19:10 | 0.293621E+09 | 349.05 | 01-SEP-06:10 |
| October | 0.442191E+09 | 400.14 | 01-OCT-18:10 | 0.303380E+09 | 349.05 | 01-OCT-07:10 |
| November | 0.428550E+09 | 400.14 | 01-NOV-19:10 | 0.293621E+09 | 349.05 | 01-NOV-06:10 |
| December | 0.444006E+09 | 400.14 | 01-DEC-20:10 | 0.303464E+09 | 349.05 | 01-DEC-07:10 |
| Annual Sum or Average | 0.520225E+10 | 0.357183E+10 | ||||
| Minimum of Months | 0.399394E+09 | 400.14 | 0.274018E+09 | 349.05 | ||
| Maximum of Months | 0.444006E+09 | 400.14 | 0.303464E+09 | 349.05 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM420_423
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.177603E+10 | 1600.56 | 01-JAN-19:10 | 0.121386E+10 | 1396.20 | 01-JAN-08:09 |
| February | 0.159758E+10 | 1600.56 | 01-FEB-20:10 | 0.109607E+10 | 1396.20 | 01-FEB-07:10 |
| March | 0.175494E+10 | 1600.56 | 01-MAR-20:10 | 0.121285E+10 | 1396.20 | 01-MAR-07:10 |
| April | 0.171397E+10 | 1600.56 | 01-APR-18:10 | 0.117448E+10 | 1396.20 | 01-APR-07:10 |
| May | 0.176197E+10 | 1600.56 | 01-MAY-19:10 | 0.121319E+10 | 1396.20 | 01-MAY-06:10 |
| June | 0.170037E+10 | 1600.56 | 01-JUN-19:10 | 0.117381E+10 | 1396.20 | 01-JUN-06:10 |
| July | 0.177579E+10 | 1600.56 | 01-JUL-18:10 | 0.121386E+10 | 1396.20 | 01-JUL-07:10 |
| August | 0.175494E+10 | 1600.56 | 01-AUG-19:10 | 0.121285E+10 | 1396.20 | 01-AUG-06:10 |
| September | 0.171443E+10 | 1600.56 | 01-SEP-19:10 | 0.117448E+10 | 1396.20 | 01-SEP-06:10 |
| October | 0.176876E+10 | 1600.56 | 01-OCT-18:10 | 0.121352E+10 | 1396.20 | 01-OCT-07:10 |
| November | 0.171420E+10 | 1600.56 | 01-NOV-19:10 | 0.117448E+10 | 1396.20 | 01-NOV-06:10 |
| December | 0.177603E+10 | 1600.56 | 01-DEC-20:10 | 0.121386E+10 | 1396.20 | 01-DEC-07:10 |
| Annual Sum or Average | 0.208090E+11 | 0.142873E+11 | ||||
| Minimum of Months | 0.159758E+10 | 1600.56 | 0.109607E+10 | 1396.20 | ||
| Maximum of Months | 0.177603E+10 | 1600.56 | 0.121386E+10 | 1396.20 |
Report: ZoneElectricSummaryMonthly
For: GUESTROOM424
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.444006E+09 | 400.14 | 01-JAN-19:10 | 0.303464E+09 | 349.05 | 01-JAN-08:09 |
| February | 0.399394E+09 | 400.14 | 01-FEB-20:10 | 0.274018E+09 | 349.05 | 01-FEB-07:10 |
| March | 0.438734E+09 | 400.14 | 01-MAR-20:10 | 0.303213E+09 | 349.05 | 01-MAR-07:10 |
| April | 0.428492E+09 | 400.14 | 01-APR-18:10 | 0.293621E+09 | 349.05 | 01-APR-07:10 |
| May | 0.440491E+09 | 400.14 | 01-MAY-19:10 | 0.303297E+09 | 349.05 | 01-MAY-06:10 |
| June | 0.425092E+09 | 400.14 | 01-JUN-19:10 | 0.293453E+09 | 349.05 | 01-JUN-06:10 |
| July | 0.443949E+09 | 400.14 | 01-JUL-18:10 | 0.303464E+09 | 349.05 | 01-JUL-07:10 |
| August | 0.438734E+09 | 400.14 | 01-AUG-19:10 | 0.303213E+09 | 349.05 | 01-AUG-06:10 |
| September | 0.428607E+09 | 400.14 | 01-SEP-19:10 | 0.293621E+09 | 349.05 | 01-SEP-06:10 |
| October | 0.442191E+09 | 400.14 | 01-OCT-18:10 | 0.303380E+09 | 349.05 | 01-OCT-07:10 |
| November | 0.428550E+09 | 400.14 | 01-NOV-19:10 | 0.293621E+09 | 349.05 | 01-NOV-06:10 |
| December | 0.444006E+09 | 400.14 | 01-DEC-20:10 | 0.303464E+09 | 349.05 | 01-DEC-07:10 |
| Annual Sum or Average | 0.520225E+10 | 0.357183E+10 | ||||
| Minimum of Months | 0.399394E+09 | 400.14 | 0.274018E+09 | 349.05 | ||
| Maximum of Months | 0.444006E+09 | 400.14 | 0.303464E+09 | 349.05 |
Report: ZoneElectricSummaryMonthly
For: FRONTSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 72316730.02 | 43.20 | 01-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 65318336.79 | 43.20 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 72316730.02 | 43.20 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 69983932.27 | 43.20 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 72316730.02 | 43.20 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 69983932.27 | 43.20 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 72316730.02 | 43.20 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 72316730.02 | 43.20 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 69983932.27 | 43.20 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 72316730.02 | 43.20 | 01-OCT-07:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 69983932.27 | 43.20 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 72316730.02 | 43.20 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.851471E+09 | 0.00 | ||||
| Minimum of Months | 65318336.79 | 43.20 | 0.00 | 0.00 | ||
| Maximum of Months | 72316730.02 | 43.20 | 0.00 | 0.00 |
Report: ZoneElectricSummaryMonthly
For: FRONTSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.347120E+09 | 129.60 | 01-JAN-00:10 | 0.00 | 0.00 | 01-JAN-00:10 |
| February | 0.313528E+09 | 129.60 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
| March | 0.347120E+09 | 129.60 | 01-MAR-00:10 | 0.00 | 0.00 | 01-MAR-00:10 |
| April | 0.335923E+09 | 129.60 | 01-APR-00:10 | 0.00 | 0.00 | 01-APR-00:10 |
| May | 0.347120E+09 | 129.60 | 01-MAY-00:10 | 0.00 | 0.00 | 01-MAY-00:10 |
| June | 0.335923E+09 | 129.60 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
| July | 0.347120E+09 | 129.60 | 01-JUL-00:10 | 0.00 | 0.00 | 01-JUL-00:10 |
| August | 0.347120E+09 | 129.60 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
| September | 0.335923E+09 | 129.60 | 01-SEP-00:10 | 0.00 | 0.00 | 01-SEP-00:10 |
| October | 0.347120E+09 | 129.60 | 01-OCT-00:10 | 0.00 | 0.00 | 01-OCT-00:10 |
| November | 0.335923E+09 | 129.60 | 01-NOV-00:10 | 0.00 | 0.00 | 01-NOV-00:10 |
| December | 0.347120E+09 | 129.60 | 01-DEC-00:10 | 0.00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.408706E+10 | 0.00 | ||||
| Minimum of Months | 0.313528E+09 | 129.60 | 0.00 | 0.00 | ||
| Maximum of Months | 0.347120E+09 | 129.60 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: REARSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752167E+09 |
| February | 0.00 | 0.313603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760052E+09 |
| March | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1869347.75 | 0.510240E+09 |
| April | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372684E+09 |
| May | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1815259.07 | 0.199349E+09 |
| June | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10352697.18 | 0.133020E+09 |
| July | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13350938.14 | 69296174.20 |
| August | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7691724.51 | 0.103749E+09 |
| September | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 127466.96 | 0.175176E+09 |
| October | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358164E+09 |
| November | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489607E+09 |
| December | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805987E+09 |
| Annual Sum or Average | 0.00 | 0.408804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35207433.62 | 0.472949E+10 |
| Minimum of Months | 0.00 | 0.313603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69296174.20 |
| Maximum of Months | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13350938.14 | 0.805987E+09 |
Report: SpaceGainsMonthly
For: CORRIDORFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.745190E+09 | 0.216954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.944020E+10 |
| February | 0.676675E+09 | 0.195959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.889067E+10 |
| March | 0.756737E+09 | 0.216954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6542531.13 | 0.708325E+10 |
| April | 0.723635E+09 | 0.209956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504997E+10 |
| May | 0.752888E+09 | 0.216954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4154717.01 | 0.304078E+10 |
| June | 0.731333E+09 | 0.209956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143302E+09 | 0.154179E+10 |
| July | 0.745190E+09 | 0.216954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352975E+09 | 0.713317E+09 |
| August | 0.756737E+09 | 0.216954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.281406E+09 | 0.108371E+10 |
| September | 0.723635E+09 | 0.209956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23156033.54 | 0.213126E+10 |
| October | 0.749039E+09 | 0.216954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447699E+10 |
| November | 0.723635E+09 | 0.209956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.563625E+10 |
| December | 0.745190E+09 | 0.216954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.905080E+10 |
| Annual Sum or Average | 0.882988E+10 | 0.255446E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.811536E+09 | 0.581390E+11 |
| Minimum of Months | 0.676675E+09 | 0.195959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.713317E+09 |
| Maximum of Months | 0.756737E+09 | 0.216954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352975E+09 | 0.944020E+10 |
Report: SpaceGainsMonthly
For: REARSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710795E+09 |
| February | 0.00 | 0.104542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721074E+09 |
| March | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3403449.29 | 0.462483E+09 |
| April | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544831.71 | 0.331960E+09 |
| May | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4560681.17 | 0.168515E+09 |
| June | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18634197.30 | 0.111926E+09 |
| July | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24593367.88 | 52911393.48 |
| August | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14945725.25 | 82605091.66 |
| September | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1197919.69 | 0.146658E+09 |
| October | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26911.73 | 0.322720E+09 |
| November | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451945E+09 |
| December | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767648E+09 |
| Annual Sum or Average | 0.00 | 0.136278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67907084.02 | 0.433124E+10 |
| Minimum of Months | 0.00 | 0.104542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52911393.48 |
| Maximum of Months | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24593367.88 | 0.767648E+09 |
Report: SpaceGainsMonthly
For: FRONTLOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.487593E+10 | 0.306833E+10 | 0.427743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.715571E+09 |
| February | 0.442763E+10 | 0.277140E+10 | 0.386349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.758874E+09 |
| March | 0.495149E+10 | 0.306833E+10 | 0.427743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 391389.67 | 0.477697E+09 |
| April | 0.473489E+10 | 0.296935E+10 | 0.413945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344841E+09 |
| May | 0.492630E+10 | 0.306833E+10 | 0.427743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 399541.07 | 0.187639E+09 |
| June | 0.478526E+10 | 0.296935E+10 | 0.413945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10332789.64 | 0.106263E+09 |
| July | 0.487593E+10 | 0.306833E+10 | 0.427743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21629553.97 | 41222143.68 |
| August | 0.495149E+10 | 0.306833E+10 | 0.427743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15705463.59 | 57369235.29 |
| September | 0.473489E+10 | 0.296935E+10 | 0.413945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1330899.32 | 0.116165E+09 |
| October | 0.490112E+10 | 0.306833E+10 | 0.427743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265758E+09 |
| November | 0.473489E+10 | 0.296935E+10 | 0.413945E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402601E+09 |
| December | 0.487593E+10 | 0.306833E+10 | 0.427743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.752484E+09 |
| Annual Sum or Average | 0.577758E+11 | 0.361271E+11 | 0.503633E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49789637.26 | 0.422649E+10 |
| Minimum of Months | 0.442763E+10 | 0.277140E+10 | 0.386349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41222143.68 |
| Maximum of Months | 0.495149E+10 | 0.306833E+10 | 0.427743E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 21629553.97 | 0.758874E+09 |
Report: SpaceGainsMonthly
For: RESTROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.161458E+09 | 0.846166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109808E+09 |
| February | 0.146613E+09 | 0.764279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114776E+09 |
| March | 0.163960E+09 | 0.846166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55293.67 | 75386322.92 |
| April | 0.156787E+09 | 0.818870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56487993.24 |
| May | 0.163126E+09 | 0.846166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56447.23 | 29181153.03 |
| June | 0.158455E+09 | 0.818870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1459975.10 | 15610512.83 |
| July | 0.161458E+09 | 0.846166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3056255.60 | 5879397.65 |
| August | 0.163960E+09 | 0.846166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2219136.68 | 8212095.85 |
| September | 0.156787E+09 | 0.818870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188049.67 | 17167034.53 |
| October | 0.162292E+09 | 0.846166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42553218.94 |
| November | 0.156787E+09 | 0.818870E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65659471.31 |
| December | 0.161458E+09 | 0.846166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116914E+09 |
| Annual Sum or Average | 0.191314E+10 | 0.996292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7035157.95 | 0.657636E+09 |
| Minimum of Months | 0.146613E+09 | 0.764279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5879397.65 |
| Maximum of Months | 0.163960E+09 | 0.846166E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3056255.60 | 0.116914E+09 |
Report: SpaceGainsMonthly
For: MEETINGROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.106153E+10 | 0.151056E+10 | 0.179790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247588E+09 |
| February | 0.965488E+09 | 0.136438E+10 | 0.162391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262554E+09 |
| March | 0.108298E+10 | 0.151056E+10 | 0.179790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 109789.10 | 0.166190E+09 |
| April | 0.103190E+10 | 0.146183E+10 | 0.173991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122186E+09 |
| May | 0.107583E+10 | 0.151056E+10 | 0.179790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94025.17 | 68536876.03 |
| June | 0.104620E+10 | 0.146183E+10 | 0.173991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3122808.90 | 38429263.15 |
| July | 0.106153E+10 | 0.151056E+10 | 0.179790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6847800.82 | 14875638.87 |
| August | 0.108298E+10 | 0.151056E+10 | 0.179790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4963176.50 | 20661675.25 |
| September | 0.103190E+10 | 0.146183E+10 | 0.173991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 385913.19 | 42209493.68 |
| October | 0.106868E+10 | 0.151056E+10 | 0.179790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96605428.82 |
| November | 0.103190E+10 | 0.146183E+10 | 0.173991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143397E+09 |
| December | 0.106153E+10 | 0.151056E+10 | 0.179790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260901E+09 |
| Annual Sum or Average | 0.126024E+11 | 0.177857E+11 | 0.211689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15523513.68 | 0.148414E+10 |
| Minimum of Months | 0.965488E+09 | 0.136438E+10 | 0.162391E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14875638.87 |
| Maximum of Months | 0.108298E+10 | 0.151056E+10 | 0.179790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6847800.82 | 0.262554E+09 |
Report: SpaceGainsMonthly
For: MECHANICALROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.352569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112130E+09 |
| February | 0.00 | 0.318449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117053E+09 |
| March | 0.00 | 0.352569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78701642.20 |
| April | 0.00 | 0.341196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61776725.62 |
| May | 0.00 | 0.352569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38338631.30 |
| June | 0.00 | 0.341196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70017.99 | 27249850.39 |
| July | 0.00 | 0.352569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166057.99 | 15978497.46 |
| August | 0.00 | 0.352569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89413.54 | 18705187.16 |
| September | 0.00 | 0.341196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27652856.59 |
| October | 0.00 | 0.352569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51891591.15 |
| November | 0.00 | 0.341196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73314210.55 |
| December | 0.00 | 0.352569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120371E+09 |
| Annual Sum or Average | 0.00 | 0.415122E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325489.52 | 0.743164E+09 |
| Minimum of Months | 0.00 | 0.318449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15978497.46 |
| Maximum of Months | 0.00 | 0.352569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166057.99 | 0.120371E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM101
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93445227.28 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97872285.50 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88356.88 | 63932910.60 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48743353.35 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42506.84 | 27550617.39 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541568.85 | 17924826.17 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1147062.79 | 8914357.21 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862760.09 | 11574450.18 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27496.91 | 19405058.56 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40530237.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58797700.84 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100440E+09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2709752.37 | 0.589132E+09 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8914357.21 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1147062.79 | 0.100440E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM102
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90661878.52 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95135058.04 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129242.84 | 61536474.60 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46360397.84 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71243.49 | 25444428.43 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 837821.11 | 16080834.86 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1643847.62 | 7493176.58 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1203510.58 | 10065381.99 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64692.34 | 17667420.80 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38289161.24 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56123610.61 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97268931.07 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3950357.97 | 0.562127E+09 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7493176.58 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1643847.62 | 97268931.07 |
Report: SpaceGainsMonthly
For: GUESTROOM103
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.333455E+09 | 0.444038E+09 | 0.303486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98657636.07 |
| February | 0.301372E+09 | 0.399422E+09 | 0.274038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104520E+09 |
| March | 0.334054E+09 | 0.438765E+09 | 0.303234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 145731.15 | 65411743.74 |
| April | 0.322827E+09 | 0.428522E+09 | 0.293642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47131059.98 |
| May | 0.333854E+09 | 0.440523E+09 | 0.303318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 153732.43 | 23524712.01 |
| June | 0.323226E+09 | 0.425123E+09 | 0.293474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2602439.96 | 12784626.92 |
| July | 0.333455E+09 | 0.443980E+09 | 0.303486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5031912.69 | 4387268.58 |
| August | 0.334054E+09 | 0.438765E+09 | 0.303234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3603807.05 | 6526867.08 |
| September | 0.322827E+09 | 0.428638E+09 | 0.293642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 442500.01 | 14389349.37 |
| October | 0.333655E+09 | 0.442223E+09 | 0.303402E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35881398.40 |
| November | 0.322827E+09 | 0.428580E+09 | 0.293642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55800889.46 |
| December | 0.333455E+09 | 0.444038E+09 | 0.303486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104051E+09 |
| Annual Sum or Average | 0.392906E+10 | 0.520262E+10 | 0.357208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11980123.28 | 0.573067E+09 |
| Minimum of Months | 0.301372E+09 | 0.399422E+09 | 0.274038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4387268.58 |
| Maximum of Months | 0.334054E+09 | 0.444038E+09 | 0.303486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5031912.69 | 0.104520E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM104
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100678E+09 |
| February | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106297E+09 |
| March | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 106022.44 | 67786714.34 |
| April | 0.322827E+09 | 0.428492E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48680830.27 |
| May | 0.333854E+09 | 0.440491E+09 | 0.303297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 153656.63 | 24202146.61 |
| June | 0.323226E+09 | 0.425092E+09 | 0.293453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2632886.68 | 12839074.48 |
| July | 0.333455E+09 | 0.443949E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5057225.95 | 4367520.31 |
| August | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3641166.19 | 6505017.60 |
| September | 0.322827E+09 | 0.428607E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 457309.64 | 14519485.86 |
| October | 0.333655E+09 | 0.442191E+09 | 0.303380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 82.40 | 36644261.71 |
| November | 0.322827E+09 | 0.428550E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57300390.68 |
| December | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105988E+09 |
| Annual Sum or Average | 0.392906E+10 | 0.520225E+10 | 0.357183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12048349.94 | 0.585808E+09 |
| Minimum of Months | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4367520.31 |
| Maximum of Months | 0.334054E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5057225.95 | 0.106297E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM105
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103870E+09 |
| February | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109859E+09 |
| March | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 105151.31 | 69650629.67 |
| April | 0.322827E+09 | 0.428492E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49889973.17 |
| May | 0.333854E+09 | 0.440491E+09 | 0.303297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 152696.50 | 25058473.29 |
| June | 0.323226E+09 | 0.425092E+09 | 0.293453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2627299.96 | 13506065.35 |
| July | 0.333455E+09 | 0.443949E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5062009.49 | 4688348.60 |
| August | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3649175.68 | 6820413.92 |
| September | 0.322827E+09 | 0.428607E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 461452.39 | 14915130.85 |
| October | 0.333655E+09 | 0.442191E+09 | 0.303380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 94.39 | 37019359.78 |
| November | 0.322827E+09 | 0.428550E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58366270.02 |
| December | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109271E+09 |
| Annual Sum or Average | 0.392906E+10 | 0.520225E+10 | 0.357183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12057879.72 | 0.602914E+09 |
| Minimum of Months | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4688348.60 |
| Maximum of Months | 0.334054E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5062009.49 | 0.109859E+09 |
Report: SpaceGainsMonthly
For: EMPLOYEELOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.657344E+09 | 0.566421E+09 | 0.812993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111037E+09 |
| February | 0.607733E+09 | 0.511606E+09 | 0.734316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116367E+09 |
| March | 0.702251E+09 | 0.566421E+09 | 0.812993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55338.66 | 76182219.14 |
| April | 0.645797E+09 | 0.548149E+09 | 0.786767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56513192.94 |
| May | 0.687282E+09 | 0.566421E+09 | 0.812993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56466.60 | 29180396.96 |
| June | 0.675734E+09 | 0.548149E+09 | 0.786767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1460149.30 | 15610096.25 |
| July | 0.657344E+09 | 0.566421E+09 | 0.812993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056407.01 | 5879406.66 |
| August | 0.702251E+09 | 0.566421E+09 | 0.812993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2219361.28 | 8211955.85 |
| September | 0.645797E+09 | 0.548149E+09 | 0.786767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 188078.01 | 17166532.64 |
| October | 0.672313E+09 | 0.566421E+09 | 0.812993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42552433.23 |
| November | 0.645797E+09 | 0.548149E+09 | 0.786767E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65654629.98 |
| December | 0.657344E+09 | 0.566421E+09 | 0.812993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117505E+09 |
| Annual Sum or Average | 0.795699E+10 | 0.666915E+10 | 0.957233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7035800.86 | 0.661860E+09 |
| Minimum of Months | 0.607733E+09 | 0.511606E+09 | 0.734316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5879406.66 |
| Maximum of Months | 0.702251E+09 | 0.566421E+09 | 0.812993E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3056407.01 | 0.117505E+09 |
Report: SpaceGainsMonthly
For: LAUNDRYROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.181490E+09 | 0.634579E+09 | 0.241866E+10 | 0.357977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.809485E+09 |
| February | 0.163926E+09 | 0.573168E+09 | 0.218460E+10 | 0.323334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.827757E+09 |
| March | 0.181490E+09 | 0.634579E+09 | 0.241866E+10 | 0.357977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666411E+09 |
| April | 0.175635E+09 | 0.614109E+09 | 0.234064E+10 | 0.346430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577610E+09 |
| May | 0.181490E+09 | 0.634579E+09 | 0.241866E+10 | 0.357977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486945E+09 |
| June | 0.175635E+09 | 0.614109E+09 | 0.234064E+10 | 0.346430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458156E+09 |
| July | 0.181490E+09 | 0.634579E+09 | 0.241866E+10 | 0.357977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376527E+09 |
| August | 0.181490E+09 | 0.634579E+09 | 0.241866E+10 | 0.357977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376037E+09 |
| September | 0.175635E+09 | 0.614109E+09 | 0.234064E+10 | 0.346430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388384E+09 |
| October | 0.181490E+09 | 0.634579E+09 | 0.241866E+10 | 0.357977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.525846E+09 |
| November | 0.175635E+09 | 0.614109E+09 | 0.234064E+10 | 0.346430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.657513E+09 |
| December | 0.181490E+09 | 0.634579E+09 | 0.241866E+10 | 0.357977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874532E+09 |
| Annual Sum or Average | 0.213690E+10 | 0.747166E+10 | 0.284778E+11 | 0.421489E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702520E+10 |
| Minimum of Months | 0.163926E+09 | 0.573168E+09 | 0.218460E+10 | 0.323334E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376037E+09 |
| Maximum of Months | 0.181490E+09 | 0.634579E+09 | 0.241866E+10 | 0.357977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.874532E+09 |
Report: SpaceGainsMonthly
For: ELEVATORCOREFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.123180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493181E+09 |
| February | 0.00 | 0.00 | 0.111260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.504227E+09 |
| March | 0.00 | 0.00 | 0.123180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395715E+09 |
| April | 0.00 | 0.00 | 0.119207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351103E+09 |
| May | 0.00 | 0.00 | 0.123180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287292E+09 |
| June | 0.00 | 0.00 | 0.119207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267571E+09 |
| July | 0.00 | 0.00 | 0.123180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221141E+09 |
| August | 0.00 | 0.00 | 0.123180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219976E+09 |
| September | 0.00 | 0.00 | 0.119207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228121E+09 |
| October | 0.00 | 0.00 | 0.123180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314132E+09 |
| November | 0.00 | 0.00 | 0.119207E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395585E+09 |
| December | 0.00 | 0.00 | 0.123180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533630E+09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.145035E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421167E+10 |
| Minimum of Months | 0.00 | 0.00 | 0.111260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219976E+09 |
| Maximum of Months | 0.00 | 0.00 | 0.123180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533630E+09 |
Report: SpaceGainsMonthly
For: EXERCISECENTERFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.149522E+10 | 0.564070E+09 | 0.710346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101681E+09 |
| February | 0.135052E+10 | 0.509483E+09 | 0.641603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107782E+09 |
| March | 0.149522E+10 | 0.564070E+09 | 0.710346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55378.00 | 69571890.97 |
| April | 0.144698E+10 | 0.545875E+09 | 0.687432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51937379.95 |
| May | 0.149522E+10 | 0.564070E+09 | 0.710346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 56550.06 | 27856444.83 |
| June | 0.144698E+10 | 0.545875E+09 | 0.687432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1460865.07 | 15117101.11 |
| July | 0.149522E+10 | 0.564070E+09 | 0.710346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057785.85 | 5798819.32 |
| August | 0.149522E+10 | 0.564070E+09 | 0.710346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2220501.67 | 8102830.76 |
| September | 0.144698E+10 | 0.545875E+09 | 0.687432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 188256.56 | 16727959.79 |
| October | 0.149522E+10 | 0.564070E+09 | 0.710346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40340499.94 |
| November | 0.144698E+10 | 0.545875E+09 | 0.687432E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60535408.63 |
| December | 0.149522E+10 | 0.564070E+09 | 0.710346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107246E+09 |
| Annual Sum or Average | 0.176050E+11 | 0.664148E+10 | 0.836375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7039337.21 | 0.612697E+09 |
| Minimum of Months | 0.135052E+10 | 0.509483E+09 | 0.641603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5798819.32 |
| Maximum of Months | 0.149522E+10 | 0.564070E+09 | 0.710346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3057785.85 | 0.107782E+09 |
Report: SpaceGainsMonthly
For: FRONTOFFICEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.135765E+10 | 0.270942E+10 | 0.248187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409023E+09 |
| February | 0.124360E+10 | 0.244722E+10 | 0.225598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433006E+09 |
| March | 0.141324E+10 | 0.270942E+10 | 0.252769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 182618.20 | 0.284741E+09 |
| April | 0.132581E+10 | 0.262202E+10 | 0.241166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214041E+09 |
| May | 0.139471E+10 | 0.270942E+10 | 0.251242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 201334.95 | 0.116245E+09 |
| June | 0.136287E+10 | 0.262202E+10 | 0.244221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5562361.56 | 62802476.13 |
| July | 0.135765E+10 | 0.270942E+10 | 0.248187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11816363.77 | 23754911.96 |
| August | 0.141324E+10 | 0.270942E+10 | 0.252769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8546303.07 | 33152286.35 |
| September | 0.132581E+10 | 0.262202E+10 | 0.241166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 691444.00 | 69169593.05 |
| October | 0.137618E+10 | 0.270942E+10 | 0.249714E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168753E+09 |
| November | 0.132581E+10 | 0.262202E+10 | 0.241166E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252684E+09 |
| December | 0.135765E+10 | 0.270942E+10 | 0.248187E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431795E+09 |
| Annual Sum or Average | 0.162542E+11 | 0.319012E+11 | 0.294437E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 27000425.54 | 0.249917E+10 |
| Minimum of Months | 0.124360E+10 | 0.244722E+10 | 0.225598E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23754911.96 |
| Maximum of Months | 0.141324E+10 | 0.270942E+10 | 0.252769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11816363.77 | 0.433006E+09 |
Report: SpaceGainsMonthly
For: FRONTSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692952E+09 |
| February | 0.00 | 0.313528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692625E+09 |
| March | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2031738.72 | 0.471183E+09 |
| April | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.41 | 0.351440E+09 |
| May | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1832592.09 | 0.197684E+09 |
| June | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7410448.00 | 0.142102E+09 |
| July | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6546523.86 | 86786445.22 |
| August | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3310648.17 | 0.123228E+09 |
| September | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192741E+09 |
| October | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.364639E+09 |
| November | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.479695E+09 |
| December | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.747876E+09 |
| Annual Sum or Average | 0.00 | 0.408706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21132618.23 | 0.454295E+10 |
| Minimum of Months | 0.00 | 0.313528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86786445.22 |
| Maximum of Months | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7410448.00 | 0.747876E+09 |
Report: SpaceGainsMonthly
For: FRONTSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131955E+09 |
| February | 0.00 | 65318336.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135649E+09 |
| March | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161118.55 | 91705853.65 |
| April | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69405949.03 |
| May | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95972.17 | 39496438.80 |
| June | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 964407.98 | 25942955.25 |
| July | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1374800.26 | 13935352.87 |
| August | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 894497.33 | 18903923.81 |
| September | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9632.35 | 31275514.50 |
| October | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62622121.07 |
| November | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87167650.20 |
| December | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141063E+09 |
| Annual Sum or Average | 0.00 | 0.851471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3500428.64 | 0.849123E+09 |
| Minimum of Months | 0.00 | 65318336.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13935352.87 |
| Maximum of Months | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1374800.26 | 0.141063E+09 |
Report: SpaceGainsMonthly
For: REARSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772951E+09 |
| February | 0.00 | 0.313603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.787639E+09 |
| March | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 736273.39 | 0.562402E+09 |
| April | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432554E+09 |
| May | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281013.83 | 0.262147E+09 |
| June | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3398576.74 | 0.179563E+09 |
| July | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6200519.22 | 0.101757E+09 |
| August | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5126768.02 | 0.127231E+09 |
| September | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64576.88 | 0.188063E+09 |
| October | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362576E+09 |
| November | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489393E+09 |
| December | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.804973E+09 |
| Annual Sum or Average | 0.00 | 0.408804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15807728.08 | 0.507125E+10 |
| Minimum of Months | 0.00 | 0.313603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101757E+09 |
| Maximum of Months | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6200519.22 | 0.804973E+09 |
Report: SpaceGainsMonthly
For: CORRIDORFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.620991E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709353E+09 |
| February | 0.563896E+09 | 0.163297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750542E+09 |
| March | 0.630614E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377274.39 | 0.492322E+09 |
| April | 0.603029E+09 | 0.174961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.376679E+09 |
| May | 0.627407E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 385566.46 | 0.203149E+09 |
| June | 0.609444E+09 | 0.174961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10062937.04 | 0.108945E+09 |
| July | 0.620991E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21106842.23 | 41139466.66 |
| August | 0.630614E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15322317.28 | 57392187.06 |
| September | 0.603029E+09 | 0.174961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1289179.37 | 0.119698E+09 |
| October | 0.624199E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.291609E+09 |
| November | 0.603029E+09 | 0.174961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431437E+09 |
| December | 0.620991E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749695E+09 |
| Annual Sum or Average | 0.735823E+10 | 0.212870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48544116.78 | 0.433196E+10 |
| Minimum of Months | 0.563896E+09 | 0.163297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41139466.66 |
| Maximum of Months | 0.630614E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21106842.23 | 0.750542E+09 |
Report: SpaceGainsMonthly
For: REARSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692889E+09 |
| February | 0.00 | 0.104542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710160E+09 |
| March | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2072651.90 | 0.487154E+09 |
| April | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25449.06 | 0.370377E+09 |
| May | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1338292.18 | 0.218179E+09 |
| June | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7444898.45 | 0.147526E+09 |
| July | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12478483.23 | 77122298.29 |
| August | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10489563.03 | 99293098.02 |
| September | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 947606.08 | 0.149743E+09 |
| October | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90720.40 | 0.305012E+09 |
| November | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.421380E+09 |
| December | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.724290E+09 |
| Annual Sum or Average | 0.00 | 0.136278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34887664.34 | 0.440313E+10 |
| Minimum of Months | 0.00 | 0.104542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77122298.29 |
| Maximum of Months | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12478483.23 | 0.724290E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM201
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.261269E+09 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278299E+09 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 218596.53 | 0.182614E+09 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141046E+09 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73643.15 | 84713782.37 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 987804.57 | 57374256.05 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2703680.90 | 29471843.52 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2141285.90 | 35423752.79 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70227.89 | 54602026.40 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109224E+09 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156140E+09 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275861E+09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6195238.94 | 0.166604E+10 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29471843.52 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2703680.90 | 0.278299E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM202_205
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.133382E+10 | 0.177615E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409197E+09 |
| February | 0.120549E+10 | 0.159769E+10 | 0.109615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434297E+09 |
| March | 0.133621E+10 | 0.175506E+10 | 0.121294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 429634.12 | 0.274663E+09 |
| April | 0.129131E+10 | 0.171409E+10 | 0.117457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200663E+09 |
| May | 0.133542E+10 | 0.176209E+10 | 0.121327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 611058.98 | 0.103248E+09 |
| June | 0.129291E+10 | 0.170049E+10 | 0.117390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10490305.80 | 56824565.92 |
| July | 0.133382E+10 | 0.177592E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20484726.01 | 20267928.34 |
| August | 0.133621E+10 | 0.175506E+10 | 0.121294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14709912.69 | 28935945.33 |
| September | 0.129131E+10 | 0.171455E+10 | 0.117457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1809483.04 | 61511041.49 |
| October | 0.133462E+10 | 0.176889E+10 | 0.121361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149280E+09 |
| November | 0.129131E+10 | 0.171432E+10 | 0.117457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231393E+09 |
| December | 0.133382E+10 | 0.177615E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.430840E+09 |
| Annual Sum or Average | 0.157162E+11 | 0.208105E+11 | 0.142883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48535120.64 | 0.240112E+10 |
| Minimum of Months | 0.120549E+10 | 0.159769E+10 | 0.109615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20267928.34 |
| Maximum of Months | 0.133621E+10 | 0.177615E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20484726.01 | 0.434297E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM206_208
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.100036E+10 | 0.143458E+10 | 0.980492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332513E+09 |
| February | 0.904116E+09 | 0.129044E+10 | 0.885353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352638E+09 |
| March | 0.100216E+10 | 0.141755E+10 | 0.979680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 346611.84 | 0.223619E+09 |
| April | 0.968481E+09 | 0.138446E+10 | 0.948689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163239E+09 |
| May | 0.100156E+10 | 0.142323E+10 | 0.979951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 493067.73 | 83583720.21 |
| June | 0.969679E+09 | 0.137347E+10 | 0.948148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 8474024.84 | 45818971.21 |
| July | 0.100036E+10 | 0.143440E+10 | 0.980492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16557226.46 | 16246480.03 |
| August | 0.100216E+10 | 0.141755E+10 | 0.979680E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 11886068.31 | 23252721.48 |
| September | 0.968481E+09 | 0.138483E+10 | 0.948689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1460939.31 | 49702567.71 |
| October | 0.100096E+10 | 0.142872E+10 | 0.980222E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121417E+09 |
| November | 0.968481E+09 | 0.138464E+10 | 0.948689E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188665E+09 |
| December | 0.100036E+10 | 0.143458E+10 | 0.980492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350127E+09 |
| Annual Sum or Average | 0.117872E+11 | 0.168085E+11 | 0.115406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 39217938.49 | 0.195082E+10 |
| Minimum of Months | 0.904116E+09 | 0.129044E+10 | 0.885353E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16246480.03 |
| Maximum of Months | 0.100216E+10 | 0.143458E+10 | 0.980492E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 16557226.46 | 0.352638E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM209_212
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.133382E+10 | 0.177615E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412473E+09 |
| February | 0.120549E+10 | 0.159769E+10 | 0.109615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437336E+09 |
| March | 0.133621E+10 | 0.175506E+10 | 0.121294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 429563.16 | 0.277353E+09 |
| April | 0.129131E+10 | 0.171409E+10 | 0.117457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.202342E+09 |
| May | 0.133542E+10 | 0.176209E+10 | 0.121327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 610604.12 | 0.103290E+09 |
| June | 0.129291E+10 | 0.170049E+10 | 0.117390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10510416.24 | 56436280.19 |
| July | 0.133382E+10 | 0.177592E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20530575.51 | 19877068.22 |
| August | 0.133621E+10 | 0.175506E+10 | 0.121294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14729483.03 | 28578756.30 |
| September | 0.129131E+10 | 0.171455E+10 | 0.117457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1809012.01 | 61541906.76 |
| October | 0.133462E+10 | 0.176889E+10 | 0.121361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150914E+09 |
| November | 0.129131E+10 | 0.171432E+10 | 0.117457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234637E+09 |
| December | 0.133382E+10 | 0.177615E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434563E+09 |
| Annual Sum or Average | 0.157162E+11 | 0.208105E+11 | 0.142883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48619654.07 | 0.241934E+10 |
| Minimum of Months | 0.120549E+10 | 0.159769E+10 | 0.109615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19877068.22 |
| Maximum of Months | 0.133621E+10 | 0.177615E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20530575.51 | 0.437336E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM213
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.333455E+09 | 0.444038E+09 | 0.303486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101248E+09 |
| February | 0.301372E+09 | 0.399422E+09 | 0.274038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107397E+09 |
| March | 0.334054E+09 | 0.438765E+09 | 0.303234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 120178.40 | 67458710.18 |
| April | 0.322827E+09 | 0.428522E+09 | 0.293642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48999343.90 |
| May | 0.333854E+09 | 0.440523E+09 | 0.303318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 153519.30 | 25093321.33 |
| June | 0.323226E+09 | 0.425123E+09 | 0.293474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2633643.83 | 13750554.27 |
| July | 0.333455E+09 | 0.443980E+09 | 0.303486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5132735.53 | 4844569.92 |
| August | 0.334054E+09 | 0.438765E+09 | 0.303234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3684148.39 | 6984575.83 |
| September | 0.322827E+09 | 0.428638E+09 | 0.293642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 453570.56 | 14942875.29 |
| October | 0.333655E+09 | 0.442223E+09 | 0.303402E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36517499.85 |
| November | 0.322827E+09 | 0.428580E+09 | 0.293642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56674039.47 |
| December | 0.333455E+09 | 0.444038E+09 | 0.303486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106498E+09 |
| Annual Sum or Average | 0.392906E+10 | 0.520262E+10 | 0.357208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12177796.01 | 0.590408E+09 |
| Minimum of Months | 0.301372E+09 | 0.399422E+09 | 0.274038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4844569.92 |
| Maximum of Months | 0.334054E+09 | 0.444038E+09 | 0.303486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5132735.53 | 0.107397E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM214
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104297E+09 |
| February | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110199E+09 |
| March | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 106977.88 | 70924659.35 |
| April | 0.322827E+09 | 0.428492E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50945704.21 |
| May | 0.333854E+09 | 0.440491E+09 | 0.303297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 155290.86 | 25670798.94 |
| June | 0.323226E+09 | 0.425092E+09 | 0.293453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2677969.58 | 13892998.16 |
| July | 0.333455E+09 | 0.443949E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5165269.05 | 4871464.66 |
| August | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3723459.20 | 7027774.61 |
| September | 0.322827E+09 | 0.428607E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 469071.38 | 15270183.76 |
| October | 0.333655E+09 | 0.442191E+09 | 0.303380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.30 | 37936911.01 |
| November | 0.322827E+09 | 0.428550E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59288038.17 |
| December | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109487E+09 |
| Annual Sum or Average | 0.392906E+10 | 0.520225E+10 | 0.357183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12298135.25 | 0.609811E+09 |
| Minimum of Months | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4871464.66 |
| Maximum of Months | 0.334054E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5165269.05 | 0.110199E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM215_218
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508889E+09 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532848E+09 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356068E+09 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272189E+09 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.156176E+09 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1134292.27 | 96363280.07 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3282810.65 | 47667678.69 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2469238.37 | 58657883.21 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32102.99 | 99793828.49 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211934E+09 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314187E+09 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539158E+09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6918444.28 | 0.319393E+10 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47667678.69 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3282810.65 | 0.539158E+09 |
Report: SpaceGainsMonthly
For: ELEVATORCOREFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251644E+09 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260922E+09 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186406E+09 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151982E+09 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104238E+09 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80867399.10 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55311201.05 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59588154.45 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75707951.94 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127188E+09 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171846E+09 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267459E+09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179316E+10 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55311201.05 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267459E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM219
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107207E+09 |
| February | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113559E+09 |
| March | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 106655.84 | 71901949.87 |
| April | 0.322827E+09 | 0.428492E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51710444.46 |
| May | 0.333854E+09 | 0.440491E+09 | 0.303297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 156075.10 | 27477054.08 |
| June | 0.323226E+09 | 0.425092E+09 | 0.293453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2695637.11 | 15833268.77 |
| July | 0.333455E+09 | 0.443949E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5194780.55 | 6141887.75 |
| August | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3747011.17 | 8407758.47 |
| September | 0.322827E+09 | 0.428607E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 478242.46 | 16761365.87 |
| October | 0.333655E+09 | 0.442191E+09 | 0.303380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 151.39 | 38723834.14 |
| November | 0.322827E+09 | 0.428550E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60549746.11 |
| December | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112784E+09 |
| Annual Sum or Average | 0.392906E+10 | 0.520225E+10 | 0.357183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12378553.61 | 0.631057E+09 |
| Minimum of Months | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6141887.75 |
| Maximum of Months | 0.334054E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5194780.55 | 0.113559E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM220_223
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.133382E+10 | 0.177603E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420911E+09 |
| February | 0.120549E+10 | 0.159758E+10 | 0.109607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.445264E+09 |
| March | 0.133621E+10 | 0.175494E+10 | 0.121285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 428216.30 | 0.285056E+09 |
| April | 0.129131E+10 | 0.171397E+10 | 0.117448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204420E+09 |
| May | 0.133542E+10 | 0.176197E+10 | 0.121319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 621249.13 | 0.102738E+09 |
| June | 0.129291E+10 | 0.170037E+10 | 0.117381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10723081.14 | 55291709.43 |
| July | 0.133382E+10 | 0.177579E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20687331.47 | 19144149.82 |
| August | 0.133621E+10 | 0.175494E+10 | 0.121285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14911038.73 | 27738761.42 |
| September | 0.129131E+10 | 0.171443E+10 | 0.117448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1875911.95 | 60826381.63 |
| October | 0.133462E+10 | 0.176876E+10 | 0.121352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 348.15 | 0.151846E+09 |
| November | 0.129131E+10 | 0.171420E+10 | 0.117448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238148E+09 |
| December | 0.133382E+10 | 0.177603E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441664E+09 |
| Annual Sum or Average | 0.157162E+11 | 0.208090E+11 | 0.142873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 49247176.87 | 0.245305E+10 |
| Minimum of Months | 0.120549E+10 | 0.159758E+10 | 0.109607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19144149.82 |
| Maximum of Months | 0.133621E+10 | 0.177603E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20687331.47 | 0.445264E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM224
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103686E+09 |
| February | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109633E+09 |
| March | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 107086.87 | 70618845.83 |
| April | 0.322827E+09 | 0.428492E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50756714.28 |
| May | 0.333854E+09 | 0.440491E+09 | 0.303297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 155477.14 | 25552392.65 |
| June | 0.323226E+09 | 0.425092E+09 | 0.293453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2680879.29 | 13792934.75 |
| July | 0.333455E+09 | 0.443949E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5168770.49 | 4821508.74 |
| August | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3725995.08 | 6970849.59 |
| September | 0.322827E+09 | 0.428607E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 469494.99 | 15205162.03 |
| October | 0.333655E+09 | 0.442191E+09 | 0.303380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 98.75 | 37866567.01 |
| November | 0.322827E+09 | 0.428550E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59025016.50 |
| December | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108803E+09 |
| Annual Sum or Average | 0.392906E+10 | 0.520225E+10 | 0.357183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12307802.62 | 0.606732E+09 |
| Minimum of Months | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4821508.74 |
| Maximum of Months | 0.334054E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5168770.49 | 0.109633E+09 |
Report: SpaceGainsMonthly
For: FRONTSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130020E+09 |
| February | 0.00 | 65318336.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134491E+09 |
| March | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122856.21 | 93377569.72 |
| April | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71744910.53 |
| May | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57571.45 | 42566324.68 |
| June | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676627.02 | 28272018.29 |
| July | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1168871.89 | 15509355.42 |
| August | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 913981.18 | 19549877.25 |
| September | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10626.93 | 30483066.43 |
| October | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59535038.43 |
| November | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82652716.70 |
| December | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136426E+09 |
| Annual Sum or Average | 0.00 | 0.851471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2950534.67 | 0.844628E+09 |
| Minimum of Months | 0.00 | 65318336.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15509355.42 |
| Maximum of Months | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1168871.89 | 0.136426E+09 |
Report: SpaceGainsMonthly
For: FRONTSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.691420E+09 |
| February | 0.00 | 0.313528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.702766E+09 |
| March | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 872065.72 | 0.511429E+09 |
| April | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404638E+09 |
| May | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340046.20 | 0.260461E+09 |
| June | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1692282.28 | 0.193265E+09 |
| July | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1908566.50 | 0.125816E+09 |
| August | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1686595.27 | 0.148563E+09 |
| September | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201902E+09 |
| October | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.356063E+09 |
| November | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.460815E+09 |
| December | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.719974E+09 |
| Annual Sum or Average | 0.00 | 0.408706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6499555.97 | 0.477711E+10 |
| Minimum of Months | 0.00 | 0.313528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125816E+09 |
| Maximum of Months | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1908566.50 | 0.719974E+09 |
Report: SpaceGainsMonthly
For: REARSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801963E+09 |
| February | 0.00 | 0.313603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.823090E+09 |
| March | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 740065.73 | 0.595235E+09 |
| April | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463828E+09 |
| May | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204577.03 | 0.293441E+09 |
| June | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2756786.68 | 0.206462E+09 |
| July | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5100800.67 | 0.121046E+09 |
| August | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4981958.56 | 0.144609E+09 |
| September | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57151.90 | 0.201605E+09 |
| October | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374757E+09 |
| November | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497903E+09 |
| December | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826656E+09 |
| Annual Sum or Average | 0.00 | 0.408804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13841340.57 | 0.535059E+10 |
| Minimum of Months | 0.00 | 0.313603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121046E+09 |
| Maximum of Months | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5100800.67 | 0.826656E+09 |
Report: SpaceGainsMonthly
For: CORRIDORFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.620991E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.778792E+09 |
| February | 0.563896E+09 | 0.163297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826078E+09 |
| March | 0.630614E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 413538.73 | 0.522068E+09 |
| April | 0.603029E+09 | 0.174961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.384457E+09 |
| May | 0.627407E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420550.54 | 0.217341E+09 |
| June | 0.609444E+09 | 0.174961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11039011.78 | 0.119958E+09 |
| July | 0.620991E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23192630.53 | 45740359.29 |
| August | 0.630614E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16837813.85 | 63715804.06 |
| September | 0.603029E+09 | 0.174961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1410705.21 | 0.128957E+09 |
| October | 0.624199E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293185E+09 |
| November | 0.603029E+09 | 0.174961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.434924E+09 |
| December | 0.620991E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.818382E+09 |
| Annual Sum or Average | 0.735823E+10 | 0.212870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53314250.63 | 0.463360E+10 |
| Minimum of Months | 0.563896E+09 | 0.163297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45740359.29 |
| Maximum of Months | 0.630614E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23192630.53 | 0.826078E+09 |
Report: SpaceGainsMonthly
For: REARSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.678350E+09 |
| February | 0.00 | 0.104542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.698546E+09 |
| March | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2329127.06 | 0.490219E+09 |
| April | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105229.87 | 0.381320E+09 |
| May | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1301780.61 | 0.240491E+09 |
| June | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5540706.78 | 0.172930E+09 |
| July | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8741840.87 | 98363061.15 |
| August | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9465257.98 | 0.117371E+09 |
| September | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1128823.14 | 0.156258E+09 |
| October | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395789.08 | 0.297442E+09 |
| November | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28388.81 | 0.402397E+09 |
| December | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.700153E+09 |
| Annual Sum or Average | 0.00 | 0.136278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29036944.19 | 0.443384E+10 |
| Minimum of Months | 0.00 | 0.104542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98363061.15 |
| Maximum of Months | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9465257.98 | 0.700153E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM301
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.275261E+09 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295289E+09 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372290.44 | 0.187101E+09 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143564E+09 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118651.80 | 87827138.20 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1205704.25 | 60285683.54 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3132948.52 | 30954966.03 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2719629.09 | 36577066.68 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155355.47 | 54297644.82 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107305E+09 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152544E+09 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288033E+09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7704579.57 | 0.171904E+10 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30954966.03 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3132948.52 | 0.295289E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM302_305
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367079E+09 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393607E+09 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546326.27 | 0.254390E+09 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195659E+09 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154433.08 | 0.118385E+09 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1687333.23 | 80795624.23 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4211249.87 | 41245824.80 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3926817.30 | 48882379.11 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275853.50 | 72625842.25 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11709.86 | 0.145431E+09 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210132E+09 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386302E+09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10813723.10 | 0.231454E+10 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41245824.80 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4211249.87 | 0.393607E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM306_308
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304882E+09 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325376E+09 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388800.06 | 0.212386E+09 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163446E+09 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113895.19 | 97354019.81 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1502177.06 | 64727920.51 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3767496.03 | 32171477.96 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3470999.15 | 38684504.63 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 241197.64 | 59428255.74 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.74 | 0.121790E+09 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177079E+09 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320587E+09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9485197.88 | 0.191791E+10 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32171477.96 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3767496.03 | 0.325376E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM309_312
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.133382E+10 | 0.177615E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453006E+09 |
| February | 0.120549E+10 | 0.159769E+10 | 0.109615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.480939E+09 |
| March | 0.133621E+10 | 0.175506E+10 | 0.121294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 470424.75 | 0.304316E+09 |
| April | 0.129131E+10 | 0.171409E+10 | 0.117457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222216E+09 |
| May | 0.133542E+10 | 0.176209E+10 | 0.121327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 668276.89 | 0.114115E+09 |
| June | 0.129291E+10 | 0.170049E+10 | 0.117390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11544910.93 | 62343283.59 |
| July | 0.133382E+10 | 0.177592E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22588933.85 | 21877508.89 |
| August | 0.133621E+10 | 0.175506E+10 | 0.121294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16208157.25 | 31361585.45 |
| September | 0.129131E+10 | 0.171455E+10 | 0.117457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1986016.00 | 67554288.69 |
| October | 0.133462E+10 | 0.176889E+10 | 0.121361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164696E+09 |
| November | 0.129131E+10 | 0.171432E+10 | 0.117457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255485E+09 |
| December | 0.133382E+10 | 0.177615E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476656E+09 |
| Annual Sum or Average | 0.157162E+11 | 0.208105E+11 | 0.142883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 53466719.67 | 0.265456E+10 |
| Minimum of Months | 0.120549E+10 | 0.159769E+10 | 0.109615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21877508.89 |
| Maximum of Months | 0.133621E+10 | 0.177615E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22588933.85 | 0.480939E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM313
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91019424.55 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97245699.17 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159649.37 | 62561391.58 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47783788.90 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59858.08 | 28289461.16 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 623465.63 | 18706074.85 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1352311.85 | 9323082.13 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1210017.31 | 11404469.78 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100828.24 | 17537396.72 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4901.47 | 36042995.30 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52232543.62 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95689742.40 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3511031.96 | 0.567836E+09 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9323082.13 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1352311.85 | 97245699.17 |
Report: SpaceGainsMonthly
For: GUESTROOM314
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113294E+09 |
| February | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120023E+09 |
| March | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 117227.65 | 77019822.70 |
| April | 0.322827E+09 | 0.428492E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55544701.06 |
| May | 0.333854E+09 | 0.440491E+09 | 0.303297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 169983.16 | 28223353.10 |
| June | 0.323226E+09 | 0.425092E+09 | 0.293453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2938563.74 | 15297139.89 |
| July | 0.333455E+09 | 0.443949E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5673322.76 | 5373995.41 |
| August | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4089746.22 | 7727644.97 |
| September | 0.322827E+09 | 0.428607E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 512803.05 | 16741431.72 |
| October | 0.333655E+09 | 0.442191E+09 | 0.303380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 97.88 | 41454641.09 |
| November | 0.322827E+09 | 0.428550E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64073873.55 |
| December | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118865E+09 |
| Annual Sum or Average | 0.392906E+10 | 0.520225E+10 | 0.357183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13501744.45 | 0.663638E+09 |
| Minimum of Months | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5373995.41 |
| Maximum of Months | 0.334054E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5673322.76 | 0.120023E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM315_318
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.133382E+10 | 0.177603E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469923E+09 |
| February | 0.120549E+10 | 0.159758E+10 | 0.109607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497057E+09 |
| March | 0.133621E+10 | 0.175494E+10 | 0.121285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 468028.18 | 0.316947E+09 |
| April | 0.129131E+10 | 0.171397E+10 | 0.117448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227376E+09 |
| May | 0.133542E+10 | 0.176197E+10 | 0.121319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 678887.80 | 0.115217E+09 |
| June | 0.129291E+10 | 0.170037E+10 | 0.117381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11760768.28 | 62800999.21 |
| July | 0.133382E+10 | 0.177579E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22728021.73 | 22278560.47 |
| August | 0.133621E+10 | 0.175494E+10 | 0.121285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16377811.76 | 31851928.14 |
| September | 0.129131E+10 | 0.171443E+10 | 0.117448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2051367.35 | 68536240.12 |
| October | 0.133462E+10 | 0.176876E+10 | 0.121352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 339.92 | 0.168791E+09 |
| November | 0.129131E+10 | 0.171420E+10 | 0.117448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.265029E+09 |
| December | 0.133382E+10 | 0.177603E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493085E+09 |
| Annual Sum or Average | 0.157162E+11 | 0.208090E+11 | 0.142873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54065225.03 | 0.273889E+10 |
| Minimum of Months | 0.120549E+10 | 0.159758E+10 | 0.109607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22278560.47 |
| Maximum of Months | 0.133621E+10 | 0.177603E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22728021.73 | 0.497057E+09 |
Report: SpaceGainsMonthly
For: ELEVATORCOREFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209858E+09 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219436E+09 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150323E+09 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116000E+09 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71485157.74 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 425303.91 | 47489738.99 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1110214.82 | 25519350.62 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 830966.62 | 30660118.17 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47749602.45 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92476431.98 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129428E+09 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220039E+09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2366485.35 | 0.136046E+10 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25519350.62 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1110214.82 | 0.220039E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM319
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116792E+09 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122603E+09 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84353641.50 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64293990.16 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38915653.01 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311099.85 | 25060852.28 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 910115.59 | 12631074.08 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674959.84 | 15514578.28 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8335.00 | 25600416.47 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51137698.36 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71804653.48 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122268E+09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1904510.27 | 0.750976E+09 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12631074.08 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 910115.59 | 0.122603E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM320_323
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.133382E+10 | 0.177603E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462377E+09 |
| February | 0.120549E+10 | 0.159758E+10 | 0.109607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.489389E+09 |
| March | 0.133621E+10 | 0.175494E+10 | 0.121285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 469061.93 | 0.314019E+09 |
| April | 0.129131E+10 | 0.171397E+10 | 0.117448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225180E+09 |
| May | 0.133542E+10 | 0.176197E+10 | 0.121319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 679903.59 | 0.113398E+09 |
| June | 0.129291E+10 | 0.170037E+10 | 0.117381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11782914.12 | 60984966.40 |
| July | 0.133382E+10 | 0.177579E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22756091.92 | 21043703.94 |
| August | 0.133621E+10 | 0.175494E+10 | 0.121285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16396368.88 | 30489080.75 |
| September | 0.129131E+10 | 0.171443E+10 | 0.117448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2054684.02 | 67003467.69 |
| October | 0.133462E+10 | 0.176876E+10 | 0.121352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 370.55 | 0.167343E+09 |
| November | 0.129131E+10 | 0.171420E+10 | 0.117448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260768E+09 |
| December | 0.133382E+10 | 0.177603E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484598E+09 |
| Annual Sum or Average | 0.157162E+11 | 0.208090E+11 | 0.142873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 54139395.02 | 0.269659E+10 |
| Minimum of Months | 0.120549E+10 | 0.159758E+10 | 0.109607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21043703.94 |
| Maximum of Months | 0.133621E+10 | 0.177603E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22756091.92 | 0.489389E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM324
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102119E+09 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107377E+09 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2244.56 | 73893295.37 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55478089.11 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5648.56 | 32189607.41 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464170.77 | 20204206.76 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1113380.28 | 9921058.04 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813861.84 | 12734573.63 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8756.64 | 21547110.89 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43806473.53 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61579191.99 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106371E+09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2408062.65 | 0.647220E+09 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9921058.04 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1113380.28 | 0.107377E+09 |
Report: SpaceGainsMonthly
For: FRONTSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134102E+09 |
| February | 0.00 | 65318336.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139454E+09 |
| March | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134151.29 | 98343109.90 |
| April | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76246643.47 |
| May | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48088.77 | 47090003.37 |
| June | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542777.31 | 32569367.28 |
| July | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 874352.35 | 18843782.68 |
| August | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 791800.08 | 22592731.18 |
| September | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5170.04 | 32863220.68 |
| October | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61468814.53 |
| November | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83801662.43 |
| December | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139376E+09 |
| Annual Sum or Average | 0.00 | 0.851471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2396339.84 | 0.886751E+09 |
| Minimum of Months | 0.00 | 65318336.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18843782.68 |
| Maximum of Months | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 874352.35 | 0.139454E+09 |
Report: SpaceGainsMonthly
For: FRONTSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.717306E+09 |
| February | 0.00 | 0.313528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742886E+09 |
| March | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 750806.14 | 0.545624E+09 |
| April | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.439268E+09 |
| May | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200764.48 | 0.297196E+09 |
| June | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1006946.59 | 0.227088E+09 |
| July | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1162111.99 | 0.152586E+09 |
| August | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1413129.21 | 0.170912E+09 |
| September | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217457E+09 |
| October | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366624E+09 |
| November | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.466915E+09 |
| December | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737958E+09 |
| Annual Sum or Average | 0.00 | 0.408706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4533758.40 | 0.508182E+10 |
| Minimum of Months | 0.00 | 0.313528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152586E+09 |
| Maximum of Months | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1413129.21 | 0.742886E+09 |
Report: SpaceGainsMonthly
For: REARSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754177E+09 |
| February | 0.00 | 0.313603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.795791E+09 |
| March | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17899.82 | 0.579109E+09 |
| April | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462974E+09 |
| May | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315791E+09 |
| June | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287942.86 | 0.238221E+09 |
| July | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656488.36 | 0.152135E+09 |
| August | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 579896.29 | 0.169326E+09 |
| September | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215739E+09 |
| October | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367473E+09 |
| November | 0.00 | 0.336003E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.465001E+09 |
| December | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.775305E+09 |
| Annual Sum or Average | 0.00 | 0.408804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1542227.33 | 0.529104E+10 |
| Minimum of Months | 0.00 | 0.313603E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152135E+09 |
| Maximum of Months | 0.00 | 0.347203E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 656488.36 | 0.795791E+09 |
Report: SpaceGainsMonthly
For: CORRIDORFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.620991E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.834967E+09 |
| February | 0.563896E+09 | 0.163297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.885631E+09 |
| March | 0.630614E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431649.56 | 0.557775E+09 |
| April | 0.603029E+09 | 0.174961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.407235E+09 |
| May | 0.627407E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444245.33 | 0.222970E+09 |
| June | 0.609444E+09 | 0.174961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11728833.40 | 0.124444E+09 |
| July | 0.620991E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24683125.74 | 48410915.56 |
| August | 0.630614E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17921495.21 | 66774366.60 |
| September | 0.603029E+09 | 0.174961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1495040.87 | 0.131170E+09 |
| October | 0.624199E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302350E+09 |
| November | 0.603029E+09 | 0.174961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461726E+09 |
| December | 0.620991E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.877434E+09 |
| Annual Sum or Average | 0.735823E+10 | 0.212870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56704390.11 | 0.492089E+10 |
| Minimum of Months | 0.563896E+09 | 0.163297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48410915.56 |
| Maximum of Months | 0.630614E+09 | 0.180793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24683125.74 | 0.885631E+09 |
Report: SpaceGainsMonthly
For: REARSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651851E+09 |
| February | 0.00 | 0.104542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679704E+09 |
| March | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1052620.09 | 0.480281E+09 |
| April | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380994E+09 |
| May | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47758.58 | 0.256514E+09 |
| June | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1341504.35 | 0.193959E+09 |
| July | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2313753.93 | 0.116401E+09 |
| August | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2921427.70 | 0.129739E+09 |
| September | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99528.96 | 0.161062E+09 |
| October | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63567.40 | 0.285334E+09 |
| November | 0.00 | 0.112009E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373531E+09 |
| December | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668608E+09 |
| Annual Sum or Average | 0.00 | 0.136278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7840161.00 | 0.437798E+10 |
| Minimum of Months | 0.00 | 0.104542E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116401E+09 |
| Maximum of Months | 0.00 | 0.115743E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2921427.70 | 0.679704E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM401
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.333455E+09 | 0.444038E+09 | 0.303486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367939E+09 |
| February | 0.301372E+09 | 0.399422E+09 | 0.274038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390814E+09 |
| March | 0.334054E+09 | 0.438765E+09 | 0.303234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 383782.25 | 0.244042E+09 |
| April | 0.322827E+09 | 0.428522E+09 | 0.293642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178026E+09 |
| May | 0.333854E+09 | 0.440523E+09 | 0.303318E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 547210.55 | 93466291.99 |
| June | 0.323226E+09 | 0.425123E+09 | 0.293474E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9488575.33 | 51957971.76 |
| July | 0.333455E+09 | 0.443980E+09 | 0.303486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18553845.02 | 18342085.99 |
| August | 0.334054E+09 | 0.438765E+09 | 0.303234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13319724.62 | 25998485.20 |
| September | 0.322827E+09 | 0.428638E+09 | 0.293642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1649443.05 | 55031616.76 |
| October | 0.333655E+09 | 0.442223E+09 | 0.303402E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130427E+09 |
| November | 0.322827E+09 | 0.428580E+09 | 0.293642E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200485E+09 |
| December | 0.333455E+09 | 0.444038E+09 | 0.303486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386282E+09 |
| Annual Sum or Average | 0.392906E+10 | 0.520262E+10 | 0.357208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 43942580.80 | 0.214281E+10 |
| Minimum of Months | 0.301372E+09 | 0.399422E+09 | 0.274038E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18342085.99 |
| Maximum of Months | 0.334054E+09 | 0.444038E+09 | 0.303486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18553845.02 | 0.390814E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM402_405
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.380924E+09 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410329E+09 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52594.14 | 0.255534E+09 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193224E+09 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125530E+09 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1315526.07 | 87349386.61 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3956191.72 | 43614573.22 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2879101.21 | 50925829.50 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33924.19 | 74944946.40 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138513E+09 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195893E+09 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.395902E+09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8237337.33 | 0.235268E+10 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43614573.22 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3956191.72 | 0.410329E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM406_408
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308609E+09 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.332553E+09 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30530.16 | 0.209747E+09 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160450E+09 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102894E+09 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1065059.99 | 70619061.54 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3236639.72 | 34928762.43 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2335583.89 | 41001656.59 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27397.21 | 61392849.34 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115703E+09 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163811E+09 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321310E+09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6695210.98 | 0.192302E+10 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34928762.43 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3236639.72 | 0.332553E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM409_412
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.133382E+10 | 0.177615E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.481647E+09 |
| February | 0.120549E+10 | 0.159769E+10 | 0.109615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511965E+09 |
| March | 0.133621E+10 | 0.175506E+10 | 0.121294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 498540.37 | 0.324969E+09 |
| April | 0.129131E+10 | 0.171409E+10 | 0.117457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.238709E+09 |
| May | 0.133542E+10 | 0.176209E+10 | 0.121327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 711847.26 | 0.124094E+09 |
| June | 0.129291E+10 | 0.170049E+10 | 0.117390E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12396790.58 | 68363057.85 |
| July | 0.133382E+10 | 0.177592E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24233346.41 | 24003334.28 |
| August | 0.133621E+10 | 0.175506E+10 | 0.121294E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17370290.96 | 34235163.27 |
| September | 0.129131E+10 | 0.171455E+10 | 0.117457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2145890.39 | 73487705.73 |
| October | 0.133462E+10 | 0.176889E+10 | 0.121361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176713E+09 |
| November | 0.129131E+10 | 0.171432E+10 | 0.117457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270409E+09 |
| December | 0.133382E+10 | 0.177615E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.506403E+09 |
| Annual Sum or Average | 0.157162E+11 | 0.208105E+11 | 0.142883E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57356705.98 | 0.283500E+10 |
| Minimum of Months | 0.120549E+10 | 0.159769E+10 | 0.109615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24003334.28 |
| Maximum of Months | 0.133621E+10 | 0.177615E+10 | 0.121394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24233346.41 | 0.511965E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM413
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95258167.71 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102411E+09 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44313.64 | 63584951.39 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47970557.58 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.55 | 30288814.32 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 339059.67 | 20795176.11 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1017534.27 | 10538141.35 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 748544.23 | 12449433.40 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9122.87 | 18378651.46 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35103462.71 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49656478.42 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99018842.20 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2158703.23 | 0.585453E+09 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10538141.35 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1017534.27 | 0.102411E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM414
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99592991.35 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106864E+09 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72379445.22 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55114735.18 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34144807.50 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337260.90 | 22155698.94 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1020497.46 | 10891715.56 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 717863.96 | 13378216.58 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8482.16 | 21999531.19 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42706320.37 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58044791.17 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103755E+09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2084104.48 | 0.641028E+09 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10891715.56 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1020497.46 | 0.106864E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM415_418
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.133382E+10 | 0.177603E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.493138E+09 |
| February | 0.120549E+10 | 0.159758E+10 | 0.109607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522799E+09 |
| March | 0.133621E+10 | 0.175494E+10 | 0.121285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 497389.44 | 0.336671E+09 |
| April | 0.129131E+10 | 0.171397E+10 | 0.117448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241799E+09 |
| May | 0.133542E+10 | 0.176197E+10 | 0.121319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 721855.17 | 0.122934E+09 |
| June | 0.129291E+10 | 0.170037E+10 | 0.117381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12573487.47 | 66735350.21 |
| July | 0.133382E+10 | 0.177579E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24311703.45 | 23223058.68 |
| August | 0.133621E+10 | 0.175494E+10 | 0.121285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17506835.60 | 33324886.26 |
| September | 0.129131E+10 | 0.171443E+10 | 0.117448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2199632.48 | 72575022.65 |
| October | 0.133462E+10 | 0.176876E+10 | 0.121352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 405.61 | 0.179644E+09 |
| November | 0.129131E+10 | 0.171420E+10 | 0.117448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278238E+09 |
| December | 0.133382E+10 | 0.177603E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.516362E+09 |
| Annual Sum or Average | 0.157162E+11 | 0.208090E+11 | 0.142873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57811309.22 | 0.288744E+10 |
| Minimum of Months | 0.120549E+10 | 0.159758E+10 | 0.109607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23223058.68 |
| Maximum of Months | 0.133621E+10 | 0.177603E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24311703.45 | 0.522799E+09 |
Report: SpaceGainsMonthly
For: ELEVATORCOREFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200170E+09 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211284E+09 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142265E+09 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107704E+09 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64227064.29 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 595273.39 | 40498471.26 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1748652.50 | 19295203.50 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1132834.92 | 24034309.34 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11237.42 | 40578351.08 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82366210.29 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117182E+09 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209057E+09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3487998.23 | 0.125866E+10 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19295203.50 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1748652.50 | 0.211284E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM419
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122701E+09 |
| February | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130097E+09 |
| March | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 124217.08 | 83896782.47 |
| April | 0.322827E+09 | 0.428492E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60288429.10 |
| May | 0.333854E+09 | 0.440491E+09 | 0.303297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 180301.62 | 30686568.44 |
| June | 0.323226E+09 | 0.425092E+09 | 0.293453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3139574.42 | 16683637.30 |
| July | 0.333455E+09 | 0.443949E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6070769.66 | 5812188.99 |
| August | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4372354.17 | 8338367.62 |
| September | 0.322827E+09 | 0.428607E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 549303.96 | 18158093.58 |
| October | 0.333655E+09 | 0.442191E+09 | 0.303380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 105.25 | 44827761.04 |
| November | 0.322827E+09 | 0.428550E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69292851.36 |
| December | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128514E+09 |
| Annual Sum or Average | 0.392906E+10 | 0.520225E+10 | 0.357183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14436626.16 | 0.719297E+09 |
| Minimum of Months | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5812188.99 |
| Maximum of Months | 0.334054E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6070769.66 | 0.130097E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM420_423
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.133382E+10 | 0.177603E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491457E+09 |
| February | 0.120549E+10 | 0.159758E+10 | 0.109607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.521174E+09 |
| March | 0.133621E+10 | 0.175494E+10 | 0.121285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 497762.99 | 0.335833E+09 |
| April | 0.129131E+10 | 0.171397E+10 | 0.117448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241122E+09 |
| May | 0.133542E+10 | 0.176197E+10 | 0.121319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 722719.87 | 0.122449E+09 |
| June | 0.129291E+10 | 0.170037E+10 | 0.117381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12586660.03 | 66261743.70 |
| July | 0.133382E+10 | 0.177579E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24330320.55 | 22914683.55 |
| August | 0.133621E+10 | 0.175494E+10 | 0.121285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17520551.59 | 32972275.17 |
| September | 0.129131E+10 | 0.171443E+10 | 0.117448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2203216.84 | 72115624.76 |
| October | 0.133462E+10 | 0.176876E+10 | 0.121352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 431.64 | 0.179074E+09 |
| November | 0.129131E+10 | 0.171420E+10 | 0.117448E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276970E+09 |
| December | 0.133382E+10 | 0.177603E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.514658E+09 |
| Annual Sum or Average | 0.157162E+11 | 0.208090E+11 | 0.142873E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57861663.51 | 0.287700E+10 |
| Minimum of Months | 0.120549E+10 | 0.159758E+10 | 0.109607E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22914683.55 |
| Maximum of Months | 0.133621E+10 | 0.177603E+10 | 0.121386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24330320.55 | 0.521174E+09 |
Report: SpaceGainsMonthly
For: GUESTROOM424
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120878E+09 |
| February | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128365E+09 |
| March | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 124389.17 | 82770638.97 |
| April | 0.322827E+09 | 0.428492E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59614326.53 |
| May | 0.333854E+09 | 0.440491E+09 | 0.303297E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 180733.77 | 30429563.67 |
| June | 0.323226E+09 | 0.425092E+09 | 0.293453E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3144387.46 | 16550459.54 |
| July | 0.333455E+09 | 0.443949E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6075310.04 | 5766206.59 |
| August | 0.334054E+09 | 0.438734E+09 | 0.303213E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4375866.76 | 8280344.68 |
| September | 0.322827E+09 | 0.428607E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 550723.07 | 18007533.18 |
| October | 0.333655E+09 | 0.442191E+09 | 0.303380E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 113.56 | 44367326.33 |
| November | 0.322827E+09 | 0.428550E+09 | 0.293621E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68161485.98 |
| December | 0.333455E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126882E+09 |
| Annual Sum or Average | 0.392906E+10 | 0.520225E+10 | 0.357183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14451523.83 | 0.710073E+09 |
| Minimum of Months | 0.301372E+09 | 0.399394E+09 | 0.274018E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5766206.59 |
| Maximum of Months | 0.334054E+09 | 0.444006E+09 | 0.303464E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6075310.04 | 0.128365E+09 |
Report: SpaceGainsMonthly
For: FRONTSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137803E+09 |
| February | 0.00 | 65318336.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145339E+09 |
| March | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9481.44 | 0.101742E+09 |
| April | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79427136.37 |
| May | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50446046.03 |
| June | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237124.92 | 35263567.58 |
| July | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475453.56 | 20127243.36 |
| August | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 265936.11 | 23329697.48 |
| September | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33804509.11 |
| October | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62036650.95 |
| November | 0.00 | 69983932.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83946799.34 |
| December | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143295E+09 |
| Annual Sum or Average | 0.00 | 0.851471E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 987996.02 | 0.916561E+09 |
| Minimum of Months | 0.00 | 65318336.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20127243.36 |
| Maximum of Months | 0.00 | 72316730.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475453.56 | 0.145339E+09 |
Report: SpaceGainsMonthly
For: FRONTSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.718431E+09 |
| February | 0.00 | 0.313528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768683E+09 |
| March | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 948.96 | 0.555221E+09 |
| April | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454149E+09 |
| May | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322236E+09 |
| June | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255148E+09 |
| July | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207745.73 | 0.176687E+09 |
| August | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123504.54 | 0.189244E+09 |
| September | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227730E+09 |
| October | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.367388E+09 |
| November | 0.00 | 0.335923E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456320E+09 |
| December | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742745E+09 |
| Annual Sum or Average | 0.00 | 0.408706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332199.23 | 0.523398E+10 |
| Minimum of Months | 0.00 | 0.313528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176687E+09 |
| Maximum of Months | 0.00 | 0.347120E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207745.73 | 0.768683E+09 |
Report: PeakSpaceGainsMonthly
For: REARSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 834.47 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 129.63 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 749.78 | 06-FEB-09:53 |
| March | 0.00 | 01-MAR-00:10 | 129.63 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.09 | 14-MAR-14:00 | 535.54 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 129.63 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 447.32 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 129.63 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 69.29 | 14-MAY-15:00 | 253.65 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 129.63 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 109.01 | 27-JUN-13:00 | 253.59 | 13-JUN-12:00 |
| July | 0.00 | 01-JUL-00:10 | 129.63 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 137.52 | 15-JUL-15:00 | 173.14 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 129.63 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.25 | 13-AUG-13:00 | 198.87 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 129.63 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.13 | 16-SEP-13:00 | 266.14 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 129.63 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 347.65 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 129.63 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 527.89 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 129.63 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 773.45 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.14 | |||||
| Maximum of Months | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.52 | 834.47 |
Report: PeakSpaceGainsMonthly
For: CORRIDORFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 748.44 | 01-JAN-07:10 | 810.01 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 27737.53 | 04-JAN-07:51 |
| February | 748.44 | 01-FEB-06:10 | 810.01 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 31137.16 | 07-FEB-07:01 |
| March | 748.44 | 01-MAR-06:10 | 810.01 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 772.04 | 15-MAR-16:10 | 27951.58 | 07-MAR-07:01 |
| April | 748.44 | 01-APR-06:10 | 810.01 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 20731.57 | 17-APR-06:01 |
| May | 748.44 | 01-MAY-05:10 | 810.01 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 296.54 | 10-MAY-16:10 | 15681.94 | 01-MAY-06:01 |
| June | 748.44 | 01-JUN-05:10 | 810.01 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3494.46 | 17-JUN-16:51 | 11949.24 | 14-JUN-06:01 |
| July | 748.44 | 01-JUL-06:10 | 810.01 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4216.45 | 16-JUL-16:10 | 8016.53 | 03-JUL-06:01 |
| August | 748.44 | 01-AUG-05:10 | 810.01 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3841.20 | 18-AUG-16:51 | 8979.70 | 03-AUG-06:01 |
| September | 748.44 | 01-SEP-05:10 | 810.01 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1906.26 | 16-SEP-16:10 | 12847.12 | 05-SEP-06:01 |
| October | 748.44 | 01-OCT-06:10 | 810.01 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 20113.08 | 17-OCT-06:01 |
| November | 748.44 | 01-NOV-05:10 | 810.01 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 20083.03 | 24-NOV-07:01 |
| December | 748.44 | 01-DEC-06:10 | 810.01 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 30683.55 | 11-DEC-07:01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 748.44 | 810.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8016.53 | |||||
| Maximum of Months | 748.44 | 810.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4216.45 | 31137.16 |
Report: PeakSpaceGainsMonthly
For: REARSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 69.14 | 01-JAN-08:09 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 808.02 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 69.14 | 01-FEB-08:09 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 733.92 | 06-FEB-09:53 |
| March | 0.00 | 01-MAR-00:10 | 69.14 | 01-MAR-08:09 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.11 | 14-MAR-14:00 | 448.92 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 69.14 | 01-APR-07:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.12 | 08-APR-13:00 | 429.64 | 16-APR-06:51 |
| May | 0.00 | 01-MAY-00:10 | 69.14 | 01-MAY-07:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 104.84 | 14-MAY-15:00 | 235.40 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 69.14 | 01-JUN-07:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 139.75 | 12-JUN-13:00 | 237.93 | 13-JUN-12:00 |
| July | 0.00 | 01-JUL-00:10 | 69.14 | 01-JUL-07:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.44 | 15-JUL-15:00 | 157.62 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 69.14 | 01-AUG-07:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 130.23 | 13-AUG-13:00 | 186.90 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 69.14 | 01-SEP-07:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.89 | 16-SEP-13:00 | 247.14 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 69.14 | 01-OCT-07:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 | 11-OCT-13:00 | 329.09 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 69.14 | 01-NOV-07:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 496.58 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 69.14 | 01-DEC-08:09 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 743.17 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 69.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.62 | |||||
| Maximum of Months | 0.00 | 69.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.44 | 808.02 |
Report: PeakSpaceGainsMonthly
For: FRONTLOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 4897.20 | 01-JAN-07:10 | 2281.66 | 01-JAN-08:09 | 4249.25 | 01-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 833.61 | 12-JAN-08:55 |
| February | 4897.20 | 01-FEB-06:10 | 2281.66 | 01-FEB-08:09 | 4249.25 | 01-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 797.67 | 13-FEB-06:00 |
| March | 4897.20 | 01-MAR-06:10 | 2281.66 | 01-MAR-08:09 | 4249.25 | 01-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.94 | 15-MAR-14:00 | 547.39 | 01-MAR-15:00 |
| April | 4897.20 | 01-APR-06:10 | 2281.66 | 01-APR-07:10 | 4249.25 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 442.41 | 16-APR-04:00 |
| May | 4897.20 | 01-MAY-05:10 | 2281.66 | 01-MAY-07:10 | 4249.25 | 01-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 | 14-MAY-15:00 | 219.34 | 11-MAY-15:00 |
| June | 4897.20 | 01-JUN-05:10 | 2281.66 | 01-JUN-07:10 | 4249.25 | 01-JUN-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 108.05 | 12-JUN-13:00 | 223.89 | 14-JUN-08:53 |
| July | 4897.20 | 01-JUL-06:10 | 2281.66 | 01-JUL-07:10 | 4249.25 | 01-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 147.44 | 15-JUL-15:00 | 135.94 | 06-JUL-02:00 |
| August | 4897.20 | 01-AUG-05:10 | 2281.66 | 01-AUG-07:10 | 4249.25 | 01-AUG-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 114.95 | 13-AUG-13:00 | 143.59 | 30-AUG-17:55 |
| September | 4897.20 | 01-SEP-05:10 | 2281.66 | 01-SEP-07:10 | 4249.25 | 01-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.97 | 16-SEP-13:00 | 227.27 | 29-SEP-06:00 |
| October | 4897.20 | 01-OCT-06:10 | 2281.66 | 01-OCT-07:10 | 4249.25 | 01-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 254.46 | 08-OCT-09:00 |
| November | 4897.20 | 01-NOV-05:10 | 2281.66 | 01-NOV-07:10 | 4249.25 | 01-NOV-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 502.50 | 17-NOV-08:55 |
| December | 4897.20 | 01-DEC-06:10 | 2281.66 | 01-DEC-08:09 | 4249.25 | 01-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 821.55 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 4897.20 | 2281.66 | 4249.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.94 | |||||
| Maximum of Months | 4897.20 | 2281.66 | 4249.25 | 0.00 | 0.00 | 0.00 | 0.00 | 147.44 | 833.61 |
Report: PeakSpaceGainsMonthly
For: RESTROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 162.16 | 01-JAN-07:10 | 315.92 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 124.10 | 12-JAN-08:55 |
| February | 162.16 | 01-FEB-06:10 | 315.92 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 116.62 | 13-FEB-06:00 |
| March | 162.16 | 01-MAR-06:10 | 315.92 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 | 15-MAR-14:00 | 84.99 | 01-MAR-15:00 |
| April | 162.16 | 01-APR-06:10 | 315.92 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 71.54 | 04-APR-16:54 |
| May | 162.16 | 01-MAY-05:10 | 315.92 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 | 14-MAY-15:00 | 36.67 | 11-MAY-15:00 |
| June | 162.16 | 01-JUN-05:10 | 315.92 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 12-JUN-13:00 | 31.64 | 14-JUN-08:55 |
| July | 162.16 | 01-JUL-06:10 | 315.92 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 15-JUL-15:00 | 19.99 | 06-JUL-02:00 |
| August | 162.16 | 01-AUG-05:10 | 315.92 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.24 | 13-AUG-13:00 | 20.29 | 30-AUG-17:55 |
| September | 162.16 | 01-SEP-05:10 | 315.92 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 | 16-SEP-13:00 | 34.31 | 29-SEP-19:00 |
| October | 162.16 | 01-OCT-06:10 | 315.92 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 39.75 | 23-OCT-15:00 |
| November | 162.16 | 01-NOV-05:10 | 315.92 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 76.77 | 17-NOV-08:55 |
| December | 162.16 | 01-DEC-06:10 | 315.92 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 123.82 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 162.16 | 315.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.99 | |||||
| Maximum of Months | 162.16 | 315.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 124.10 |
Report: PeakSpaceGainsMonthly
For: MEETINGROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 2838.00 | 01-JAN-08:09 | 1123.28 | 01-JAN-08:09 | 237.69 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 289.95 | 12-JAN-08:55 |
| February | 2838.00 | 01-FEB-08:09 | 1123.28 | 01-FEB-08:09 | 237.69 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 277.44 | 13-FEB-06:00 |
| March | 2838.00 | 01-MAR-08:09 | 1123.28 | 01-MAR-08:09 | 237.69 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.35 | 15-MAR-14:02 | 185.23 | 01-MAR-15:00 |
| April | 2838.00 | 01-APR-07:10 | 1123.28 | 01-APR-07:10 | 237.69 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 153.88 | 16-APR-04:00 |
| May | 2838.00 | 01-MAY-07:10 | 1123.28 | 01-MAY-07:10 | 237.69 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.87 | 14-MAY-15:00 | 76.96 | 11-MAY-15:00 |
| June | 2838.00 | 01-JUN-07:10 | 1123.28 | 01-JUN-07:10 | 237.69 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.60 | 12-JUN-13:00 | 76.76 | 14-JUN-09:00 |
| July | 2838.00 | 01-JUL-07:10 | 1123.28 | 01-JUL-07:10 | 237.69 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.33 | 15-JUL-15:00 | 49.21 | 06-JUL-02:00 |
| August | 2838.00 | 01-AUG-07:10 | 1123.28 | 01-AUG-07:10 | 237.69 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.35 | 13-AUG-13:00 | 49.93 | 30-AUG-17:55 |
| September | 2838.00 | 01-SEP-07:10 | 1123.28 | 01-SEP-07:10 | 237.69 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 | 16-SEP-13:00 | 84.46 | 29-SEP-19:00 |
| October | 2838.00 | 01-OCT-07:10 | 1123.28 | 01-OCT-07:10 | 237.69 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 87.65 | 23-OCT-18:00 |
| November | 2838.00 | 01-NOV-07:10 | 1123.28 | 01-NOV-07:10 | 237.69 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 163.28 | 17-NOV-08:55 |
| December | 2838.00 | 01-DEC-08:09 | 1123.28 | 01-DEC-08:09 | 237.69 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 279.80 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 2838.00 | 1123.28 | 237.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.21 | |||||
| Maximum of Months | 2838.00 | 1123.28 | 237.69 | 0.00 | 0.00 | 0.00 | 0.00 | 47.33 | 289.95 |
Report: PeakSpaceGainsMonthly
For: MECHANICALROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 210.61 | 01-JAN-08:09 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 125.62 | 12-JAN-09:00 |
| February | 0.00 | 01-FEB-00:10 | 210.61 | 01-FEB-08:09 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 118.61 | 13-FEB-06:00 |
| March | 0.00 | 01-MAR-00:10 | 210.61 | 01-MAR-08:09 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 87.11 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 210.61 | 01-APR-07:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 75.61 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 210.61 | 01-MAY-07:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 43.31 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 210.61 | 01-JUN-07:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 27-JUN-13:00 | 42.23 | 13-JUN-15:55 |
| July | 0.00 | 01-JUL-00:10 | 210.61 | 01-JUL-07:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 15-JUL-15:00 | 29.94 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 210.61 | 01-AUG-07:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.24 | 13-AUG-13:00 | 29.67 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 210.61 | 01-SEP-07:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 43.54 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 210.61 | 01-OCT-07:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 46.80 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 210.61 | 01-NOV-07:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 84.23 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 210.61 | 01-DEC-08:09 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 127.19 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 210.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | |||||
| Maximum of Months | 0.00 | 210.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.79 | 127.19 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM101
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 108.52 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 101.86 | 13-FEB-06:00 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.09 | 14-MAR-14:00 | 70.82 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 62.04 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.45 | 14-MAY-15:00 | 32.45 | 11-MAY-15:10 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 27-JUN-13:00 | 32.81 | 13-JUN-16:00 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 | 15-JUL-15:00 | 22.53 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.30 | 13-AUG-13:00 | 23.25 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 | 16-SEP-13:05 | 33.67 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 36.81 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 69.00 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 107.65 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.53 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.82 | 108.52 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM102
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 106.31 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 99.72 | 13-FEB-06:00 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.30 | 14-MAR-14:00 | 68.05 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 59.60 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.72 | 14-MAY-15:00 | 30.83 | 11-MAY-15:10 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.75 | 12-JUN-13:00 | 30.89 | 13-JUN-16:00 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 | 15-JUL-15:00 | 20.82 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.91 | 13-AUG-13:00 | 21.94 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.44 | 16-SEP-13:05 | 31.63 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 35.46 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 66.40 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 104.51 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.82 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.48 | 106.31 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM103
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 198.00 | 01-JAN-00:10 | 400.17 | 01-JAN-19:10 | 349.07 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 117.06 | 12-JAN-09:06 |
| February | 198.00 | 01-FEB-00:10 | 400.17 | 01-FEB-20:10 | 349.07 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 112.72 | 13-FEB-06:00 |
| March | 198.00 | 01-MAR-00:10 | 400.17 | 01-MAR-20:10 | 349.07 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.41 | 14-MAR-14:00 | 68.97 | 01-MAR-15:00 |
| April | 198.00 | 01-APR-00:10 | 400.17 | 01-APR-18:10 | 349.07 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 62.52 | 16-APR-04:00 |
| May | 198.00 | 01-MAY-00:10 | 400.17 | 01-MAY-19:10 | 349.07 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.09 | 14-MAY-15:20 | 32.51 | 11-MAY-15:00 |
| June | 198.00 | 01-JUN-00:10 | 400.17 | 01-JUN-19:10 | 349.07 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.29 | 12-JUN-09:51 | 29.55 | 13-JUN-12:00 |
| July | 198.00 | 01-JUL-00:10 | 400.17 | 01-JUL-18:10 | 349.07 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 15-JUL-15:20 | 13.29 | 06-JUL-02:00 |
| August | 198.00 | 01-AUG-00:10 | 400.17 | 01-AUG-19:10 | 349.07 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.24 | 13-AUG-15:20 | 19.96 | 30-AUG-17:20 |
| September | 198.00 | 01-SEP-00:10 | 400.17 | 01-SEP-19:10 | 349.07 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.22 | 16-SEP-15:40 | 26.49 | 29-SEP-19:00 |
| October | 198.00 | 01-OCT-00:10 | 400.17 | 01-OCT-18:10 | 349.07 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 37.86 | 23-OCT-15:00 |
| November | 198.00 | 01-NOV-00:10 | 400.17 | 01-NOV-19:10 | 349.07 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 68.87 | 17-NOV-09:00 |
| December | 198.00 | 01-DEC-00:10 | 400.17 | 01-DEC-20:10 | 349.07 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 108.53 | 09-DEC-17:46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 198.00 | 400.17 | 349.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 | |||||
| Maximum of Months | 198.00 | 400.17 | 349.07 | 0.00 | 0.00 | 0.00 | 0.00 | 24.83 | 117.06 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM104
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 198.00 | 01-JAN-00:10 | 400.14 | 01-JAN-19:10 | 349.05 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 117.06 | 12-JAN-09:04 |
| February | 198.00 | 01-FEB-00:10 | 400.14 | 01-FEB-20:10 | 349.05 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 112.71 | 13-FEB-06:00 |
| March | 198.00 | 01-MAR-00:10 | 400.14 | 01-MAR-20:10 | 349.05 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 15-MAR-14:00 | 82.48 | 01-MAR-15:00 |
| April | 198.00 | 01-APR-00:10 | 400.14 | 01-APR-18:10 | 349.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 63.54 | 04-APR-17:00 |
| May | 198.00 | 01-MAY-00:10 | 400.14 | 01-MAY-19:10 | 349.05 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.09 | 14-MAY-15:18 | 34.20 | 11-MAY-15:00 |
| June | 198.00 | 01-JUN-00:10 | 400.14 | 01-JUN-19:10 | 349.05 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 | 12-JUN-09:50 | 29.55 | 13-JUN-12:00 |
| July | 198.00 | 01-JUL-00:10 | 400.14 | 01-JUL-18:10 | 349.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.13 | 15-JUL-15:20 | 13.29 | 06-JUL-02:00 |
| August | 198.00 | 01-AUG-00:10 | 400.14 | 01-AUG-19:10 | 349.05 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.71 | 13-AUG-15:20 | 19.16 | 30-AUG-17:55 |
| September | 198.00 | 01-SEP-00:10 | 400.14 | 01-SEP-19:10 | 349.05 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.22 | 16-SEP-15:20 | 27.38 | 29-SEP-12:00 |
| October | 198.00 | 01-OCT-00:10 | 400.14 | 01-OCT-18:10 | 349.05 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 11-OCT-16:10 | 38.58 | 23-OCT-15:00 |
| November | 198.00 | 01-NOV-00:10 | 400.14 | 01-NOV-19:10 | 349.05 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 71.93 | 17-NOV-09:00 |
| December | 198.00 | 01-DEC-00:10 | 400.14 | 01-DEC-20:10 | 349.05 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 110.30 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 | |||||
| Maximum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 25.13 | 117.06 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM105
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 198.00 | 01-JAN-00:10 | 400.14 | 01-JAN-19:10 | 349.05 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 123.67 | 12-JAN-09:00 |
| February | 198.00 | 01-FEB-00:10 | 400.14 | 01-FEB-20:10 | 349.05 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 113.42 | 07-FEB-11:00 |
| March | 198.00 | 01-MAR-00:10 | 400.14 | 01-MAR-20:10 | 349.05 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.41 | 15-MAR-14:00 | 85.72 | 01-MAR-15:00 |
| April | 198.00 | 01-APR-00:10 | 400.14 | 01-APR-18:10 | 349.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 68.86 | 04-APR-17:00 |
| May | 198.00 | 01-MAY-00:10 | 400.14 | 01-MAY-19:10 | 349.05 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.09 | 14-MAY-15:20 | 35.31 | 11-MAY-15:00 |
| June | 198.00 | 01-JUN-00:10 | 400.14 | 01-JUN-19:10 | 349.05 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.26 | 12-JUN-09:50 | 29.55 | 13-JUN-12:00 |
| July | 198.00 | 01-JUL-00:10 | 400.14 | 01-JUL-18:10 | 349.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.13 | 15-JUL-15:20 | 13.29 | 06-JUL-02:00 |
| August | 198.00 | 01-AUG-00:10 | 400.14 | 01-AUG-19:10 | 349.05 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.72 | 13-AUG-15:20 | 19.16 | 30-AUG-17:55 |
| September | 198.00 | 01-SEP-00:10 | 400.14 | 01-SEP-19:10 | 349.05 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.22 | 16-SEP-15:20 | 27.38 | 29-SEP-12:00 |
| October | 198.00 | 01-OCT-00:10 | 400.14 | 01-OCT-18:10 | 349.05 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 11-OCT-16:09 | 38.57 | 23-OCT-15:00 |
| November | 198.00 | 01-NOV-00:10 | 400.14 | 01-NOV-19:10 | 349.05 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 74.58 | 17-NOV-08:55 |
| December | 198.00 | 01-DEC-00:10 | 400.14 | 01-DEC-20:10 | 349.05 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 124.70 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.29 | |||||
| Maximum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 25.13 | 124.70 |
Report: PeakSpaceGainsMonthly
For: EMPLOYEELOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1663.20 | 03-JAN-12:09 | 421.20 | 01-JAN-08:09 | 672.25 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 124.24 | 12-JAN-09:50 |
| February | 1663.20 | 01-FEB-12:09 | 421.20 | 01-FEB-08:09 | 672.25 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 119.92 | 07-FEB-11:00 |
| March | 1663.20 | 01-MAR-12:09 | 421.20 | 01-MAR-08:09 | 672.25 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 | 15-MAR-14:00 | 87.82 | 01-MAR-15:00 |
| April | 1663.20 | 03-APR-11:09 | 421.20 | 01-APR-07:10 | 672.25 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 71.54 | 04-APR-17:00 |
| May | 1663.20 | 01-MAY-11:09 | 421.20 | 01-MAY-07:10 | 672.25 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.36 | 14-MAY-15:00 | 36.67 | 11-MAY-15:00 |
| June | 1663.20 | 01-JUN-11:09 | 421.20 | 01-JUN-07:10 | 672.25 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 12-JUN-13:00 | 31.64 | 14-JUN-08:53 |
| July | 1663.20 | 03-JUL-11:09 | 421.20 | 01-JUL-07:10 | 672.25 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 15-JUL-15:00 | 19.99 | 06-JUL-02:00 |
| August | 1663.20 | 01-AUG-11:09 | 421.20 | 01-AUG-07:10 | 672.25 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.24 | 13-AUG-13:00 | 20.29 | 30-AUG-17:55 |
| September | 1663.20 | 01-SEP-11:09 | 421.20 | 01-SEP-07:10 | 672.25 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.92 | 16-SEP-13:00 | 34.31 | 29-SEP-19:00 |
| October | 1663.20 | 02-OCT-11:09 | 421.20 | 01-OCT-07:10 | 672.25 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 39.74 | 23-OCT-15:00 |
| November | 1663.20 | 01-NOV-11:09 | 421.20 | 01-NOV-07:10 | 672.25 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 76.77 | 17-NOV-08:55 |
| December | 1663.20 | 01-DEC-12:09 | 421.20 | 01-DEC-08:09 | 672.25 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 128.16 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 1663.20 | 421.20 | 672.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.99 | |||||
| Maximum of Months | 1663.20 | 421.20 | 672.25 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 128.16 |
Report: PeakSpaceGainsMonthly
For: LAUNDRYROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 250.19 | 01-JAN-10:09 | 631.80 | 01-JAN-08:09 | 2709.07 | 01-JAN-08:09 | 40096.03 | 01-JAN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 1133.57 | 07-JAN-11:00 |
| February | 250.19 | 01-FEB-10:09 | 631.80 | 01-FEB-08:09 | 2709.07 | 01-FEB-08:09 | 40096.03 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1042.07 | 15-FEB-15:00 |
| March | 250.19 | 01-MAR-10:09 | 631.80 | 01-MAR-08:09 | 2709.07 | 01-MAR-08:09 | 40096.03 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1005.87 | 01-MAR-15:00 |
| April | 250.19 | 01-APR-09:09 | 631.80 | 01-APR-07:10 | 2709.07 | 01-APR-07:10 | 40096.03 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 832.03 | 04-APR-15:00 |
| May | 250.19 | 01-MAY-09:09 | 631.80 | 01-MAY-07:10 | 2709.07 | 01-MAY-07:10 | 40096.03 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 781.63 | 29-MAY-14:00 |
| June | 250.19 | 01-JUN-09:09 | 631.80 | 01-JUN-07:10 | 2709.07 | 01-JUN-07:10 | 40096.03 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 668.68 | 13-JUN-16:00 |
| July | 250.19 | 01-JUL-09:09 | 631.80 | 01-JUL-07:10 | 2709.07 | 01-JUL-07:10 | 40096.03 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 534.52 | 15-JUL-15:00 |
| August | 250.19 | 01-AUG-09:09 | 631.80 | 01-AUG-07:10 | 2709.07 | 01-AUG-07:10 | 40096.03 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 631.71 | 28-AUG-13:00 |
| September | 250.19 | 01-SEP-09:09 | 631.80 | 01-SEP-07:10 | 2709.07 | 01-SEP-07:10 | 40096.03 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 702.33 | 28-SEP-14:00 |
| October | 250.19 | 01-OCT-09:09 | 631.80 | 01-OCT-07:10 | 2709.07 | 01-OCT-07:10 | 40096.03 | 01-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 560.63 | 12-OCT-15:00 |
| November | 250.19 | 01-NOV-09:09 | 631.80 | 01-NOV-07:10 | 2709.07 | 01-NOV-07:10 | 40096.03 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1027.10 | 10-NOV-13:00 |
| December | 250.19 | 01-DEC-10:09 | 631.80 | 01-DEC-08:09 | 2709.07 | 01-DEC-08:09 | 40096.03 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1206.89 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 250.19 | 631.80 | 2709.07 | 40096.03 | 0.00 | 0.00 | 0.00 | 0.00 | 534.52 | ||||||
| Maximum of Months | 250.19 | 631.80 | 2709.07 | 40096.03 | 0.00 | 0.00 | 0.00 | 0.00 | 1206.89 |
Report: PeakSpaceGainsMonthly
For: ELEVATORCOREFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 7633.46 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 530.68 | 07-JAN-09:00 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 7633.46 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 463.40 | 13-FEB-07:10 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 7633.46 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 425.11 | 01-MAR-15:10 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 7633.46 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 385.04 | 04-APR-15:10 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 7633.46 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 348.27 | 29-MAY-15:10 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 7633.46 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 318.46 | 13-JUN-16:00 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 7633.46 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 225.40 | 15-JUL-15:10 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 7633.46 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 241.85 | 19-AUG-15:10 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 7633.46 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 298.10 | 29-SEP-16:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 7633.46 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 252.67 | 23-OCT-15:10 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 7633.46 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 456.22 | 10-NOV-13:00 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 7633.46 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 544.72 | 09-DEC-17:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 7633.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.40 | |||||
| Maximum of Months | 0.00 | 0.00 | 7633.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.72 |
Report: PeakSpaceGainsMonthly
For: EXERCISECENTERFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 924.00 | 01-JAN-07:10 | 315.90 | 01-JAN-07:10 | 606.20 | 01-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 117.79 | 12-JAN-08:55 |
| February | 924.00 | 01-FEB-07:10 | 315.90 | 01-FEB-07:10 | 606.20 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 112.71 | 13-FEB-06:00 |
| March | 924.00 | 01-MAR-07:10 | 315.90 | 01-MAR-07:10 | 606.20 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.53 | 15-MAR-14:00 | 82.59 | 01-MAR-15:00 |
| April | 924.00 | 01-APR-06:10 | 315.90 | 01-APR-06:10 | 606.20 | 01-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 65.36 | 04-APR-16:51 |
| May | 924.00 | 01-MAY-06:10 | 315.90 | 01-MAY-06:10 | 606.20 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.37 | 14-MAY-15:00 | 36.66 | 11-MAY-15:00 |
| June | 924.00 | 01-JUN-06:10 | 315.90 | 01-JUN-06:10 | 606.20 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.27 | 12-JUN-13:00 | 31.64 | 14-JUN-08:53 |
| July | 924.00 | 01-JUL-06:10 | 315.90 | 01-JUL-06:10 | 606.20 | 01-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 15-JUL-15:00 | 19.09 | 06-JUL-02:00 |
| August | 924.00 | 01-AUG-06:10 | 315.90 | 01-AUG-06:10 | 606.20 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.25 | 13-AUG-13:00 | 20.29 | 30-AUG-17:55 |
| September | 924.00 | 01-SEP-06:10 | 315.90 | 01-SEP-06:10 | 606.20 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.93 | 16-SEP-13:00 | 34.30 | 29-SEP-19:00 |
| October | 924.00 | 01-OCT-06:10 | 315.90 | 01-OCT-06:10 | 606.20 | 01-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 39.46 | 23-OCT-15:00 |
| November | 924.00 | 01-NOV-06:10 | 315.90 | 01-NOV-06:10 | 606.20 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 72.94 | 17-NOV-09:00 |
| December | 924.00 | 01-DEC-07:10 | 315.90 | 01-DEC-07:10 | 606.20 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 116.08 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 924.00 | 315.90 | 606.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.09 | |||||
| Maximum of Months | 924.00 | 315.90 | 606.20 | 0.00 | 0.00 | 0.00 | 0.00 | 20.84 | 117.79 |
Report: PeakSpaceGainsMonthly
For: FRONTOFFICEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 1320.00 | 03-JAN-08:09 | 1389.96 | 01-JAN-08:09 | 1663.95 | 03-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 471.17 | 12-JAN-09:00 |
| February | 1320.00 | 01-FEB-08:09 | 1389.96 | 01-FEB-08:09 | 1663.95 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 450.85 | 13-FEB-06:00 |
| March | 1320.00 | 01-MAR-08:09 | 1389.96 | 01-MAR-08:09 | 1663.95 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 | 15-MAR-14:04 | 347.37 | 01-MAR-15:00 |
| April | 1320.00 | 03-APR-07:10 | 1389.96 | 01-APR-07:10 | 1663.95 | 03-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 270.55 | 04-APR-16:51 |
| May | 1320.00 | 01-MAY-07:10 | 1389.96 | 01-MAY-07:10 | 1663.95 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 21.44 | 14-MAY-15:00 | 146.67 | 11-MAY-15:00 |
| June | 1320.00 | 01-JUN-07:10 | 1389.96 | 01-JUN-07:10 | 1663.95 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 61.08 | 12-JUN-13:00 | 128.07 | 13-JUN-12:00 |
| July | 1320.00 | 03-JUL-07:10 | 1389.96 | 01-JUL-07:10 | 1663.95 | 03-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 83.34 | 15-JUL-15:00 | 79.98 | 06-JUL-02:00 |
| August | 1320.00 | 01-AUG-07:10 | 1389.96 | 01-AUG-07:10 | 1663.95 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 64.98 | 13-AUG-13:00 | 81.16 | 30-AUG-17:55 |
| September | 1320.00 | 01-SEP-07:10 | 1389.96 | 01-SEP-07:10 | 1663.95 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 27.68 | 16-SEP-13:00 | 137.24 | 29-SEP-19:00 |
| October | 1320.00 | 02-OCT-07:10 | 1389.96 | 01-OCT-07:10 | 1663.95 | 02-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 158.98 | 23-OCT-15:00 |
| November | 1320.00 | 01-NOV-07:10 | 1389.96 | 01-NOV-07:10 | 1663.95 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 297.25 | 17-NOV-09:00 |
| December | 1320.00 | 01-DEC-08:09 | 1389.96 | 01-DEC-08:09 | 1663.95 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 456.14 | 09-DEC-15:03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 1320.00 | 1389.96 | 1663.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.98 | |||||
| Maximum of Months | 1320.00 | 1389.96 | 1663.95 | 0.00 | 0.00 | 0.00 | 0.00 | 83.34 | 471.17 |
Report: PeakSpaceGainsMonthly
For: FRONTSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 782.63 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 129.60 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 719.19 | 07-FEB-10:51 |
| March | 0.00 | 01-MAR-00:10 | 129.60 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.63 | 14-MAR-14:00 | 487.62 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 129.60 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.66 | 07-APR-13:00 | 427.85 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 129.60 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.51 | 14-MAY-15:00 | 254.14 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 129.60 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.36 | 27-JUN-13:00 | 266.22 | 13-JUN-03:00 |
| July | 0.00 | 01-JUL-00:10 | 129.60 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 118.98 | 15-JUL-15:00 | 190.76 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 129.60 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.39 | 13-AUG-13:00 | 209.19 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 129.60 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 267.12 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 129.60 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 353.20 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 129.60 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 518.52 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 129.60 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 713.08 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.76 | |||||
| Maximum of Months | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.98 | 782.63 |
Report: PeakSpaceGainsMonthly
For: FRONTSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 43.20 | 01-JAN-08:09 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 151.93 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 43.20 | 01-FEB-08:09 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 138.26 | 13-FEB-06:00 |
| March | 0.00 | 01-MAR-00:10 | 43.20 | 01-MAR-08:09 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 14-MAR-14:00 | 104.11 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 43.20 | 01-APR-07:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 88.17 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 43.20 | 01-MAY-07:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.91 | 14-MAY-15:00 | 50.20 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 43.20 | 01-JUN-07:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.22 | 27-JUN-13:00 | 48.32 | 13-JUN-15:55 |
| July | 0.00 | 01-JUL-00:10 | 43.20 | 01-JUL-07:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.46 | 15-JUL-15:00 | 33.59 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 43.20 | 01-AUG-07:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.78 | 13-AUG-13:00 | 35.01 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 43.20 | 01-SEP-07:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 16-SEP-13:00 | 50.06 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 43.20 | 01-OCT-07:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 60.35 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 43.20 | 01-NOV-07:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 100.23 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 43.20 | 01-DEC-08:09 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 145.69 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 43.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.59 | |||||
| Maximum of Months | 0.00 | 43.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.46 | 151.93 |
Report: PeakSpaceGainsMonthly
For: REARSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 829.69 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 129.63 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 753.82 | 06-FEB-09:53 |
| March | 0.00 | 01-MAR-00:10 | 129.63 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.58 | 14-MAR-14:00 | 552.19 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 129.63 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 494.29 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 129.63 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.42 | 10-MAY-14:00 | 299.69 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 129.63 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.88 | 27-JUN-13:00 | 293.53 | 13-JUN-03:00 |
| July | 0.00 | 01-JUL-00:10 | 129.63 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.13 | 15-JUL-15:00 | 207.89 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 129.63 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.53 | 13-AUG-13:00 | 220.95 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 129.63 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.61 | 16-SEP-13:00 | 271.87 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 129.63 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 350.53 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 129.63 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 515.09 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 129.63 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 745.73 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 207.89 | |||||
| Maximum of Months | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.13 | 829.69 |
Report: PeakSpaceGainsMonthly
For: CORRIDORFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 623.70 | 01-JAN-07:10 | 675.01 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 819.98 | 12-JAN-09:00 |
| February | 623.70 | 01-FEB-06:10 | 675.01 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 784.63 | 13-FEB-06:00 |
| March | 623.70 | 01-MAR-06:10 | 675.01 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.29 | 15-MAR-14:00 | 551.73 | 01-MAR-15:00 |
| April | 623.70 | 01-APR-06:10 | 675.01 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 465.35 | 04-APR-16:51 |
| May | 623.70 | 01-MAY-05:10 | 675.01 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.95 | 14-MAY-15:00 | 255.43 | 11-MAY-15:00 |
| June | 623.70 | 01-JUN-05:10 | 675.01 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.83 | 12-JUN-13:00 | 220.47 | 14-JUN-08:53 |
| July | 623.70 | 01-JUL-06:10 | 675.01 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 144.54 | 15-JUL-15:00 | 139.43 | 06-JUL-02:00 |
| August | 623.70 | 01-AUG-05:10 | 675.01 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.65 | 13-AUG-13:00 | 141.43 | 30-AUG-17:55 |
| September | 623.70 | 01-SEP-05:10 | 675.01 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 | 16-SEP-13:00 | 239.08 | 29-SEP-19:00 |
| October | 623.70 | 01-OCT-06:10 | 675.01 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 276.80 | 23-OCT-15:00 |
| November | 623.70 | 01-NOV-05:10 | 675.01 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 501.77 | 17-NOV-08:55 |
| December | 623.70 | 01-DEC-06:10 | 675.01 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 808.20 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 623.70 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.43 | |||||
| Maximum of Months | 623.70 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.54 | 819.98 |
Report: PeakSpaceGainsMonthly
For: REARSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 69.14 | 01-JAN-08:09 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 777.22 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 69.14 | 01-FEB-08:09 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 708.19 | 06-FEB-09:53 |
| March | 0.00 | 01-MAR-00:10 | 69.14 | 01-MAR-08:09 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 76.92 | 14-MAR-14:00 | 450.23 | 18-MAR-13:00 |
| April | 0.00 | 01-APR-00:10 | 69.14 | 01-APR-07:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.40 | 07-APR-13:05 | 443.12 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 69.14 | 01-MAY-07:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.34 | 14-MAY-15:00 | 270.84 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 69.14 | 01-JUN-07:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.43 | 27-JUN-13:00 | 270.43 | 13-JUN-03:00 |
| July | 0.00 | 01-JUL-00:10 | 69.14 | 01-JUL-07:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.73 | 15-JUL-15:00 | 183.11 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 69.14 | 01-AUG-07:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.36 | 13-AUG-13:00 | 200.67 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 69.14 | 01-SEP-07:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.31 | 16-SEP-13:00 | 235.98 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 69.14 | 01-OCT-07:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.41 | 11-OCT-12:25 | 319.92 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 69.14 | 01-NOV-07:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 459.60 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 69.14 | 01-DEC-08:09 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 684.42 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 69.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.11 | |||||
| Maximum of Months | 0.00 | 69.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.73 | 777.22 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM201
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 308.50 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 297.47 | 07-FEB-10:54 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.09 | 14-MAR-14:00 | 195.17 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 176.44 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 | 10-MAY-14:00 | 98.32 | 11-MAY-15:10 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.95 | 27-JUN-13:00 | 98.20 | 13-JUN-15:55 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.31 | 15-JUL-15:00 | 66.83 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.83 | 13-AUG-13:00 | 69.86 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.48 | 16-SEP-13:05 | 90.67 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 106.13 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 184.26 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 293.64 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.83 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.31 | 308.50 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM202_205
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 792.00 | 01-JAN-00:10 | 1600.67 | 01-JAN-19:10 | 1396.30 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 481.52 | 12-JAN-09:05 |
| February | 792.00 | 01-FEB-00:10 | 1600.67 | 01-FEB-20:10 | 1396.30 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 463.66 | 13-FEB-06:00 |
| March | 792.00 | 01-MAR-00:10 | 1600.67 | 01-MAR-20:10 | 1396.30 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 15-MAR-14:00 | 294.73 | 01-MAR-15:00 |
| April | 792.00 | 01-APR-00:10 | 1600.67 | 01-APR-18:10 | 1396.30 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 264.12 | 04-APR-17:00 |
| May | 792.00 | 01-MAY-00:10 | 1600.67 | 01-MAY-19:10 | 1396.30 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.31 | 14-MAY-15:20 | 145.34 | 11-MAY-15:00 |
| June | 792.00 | 01-JUN-00:10 | 1600.67 | 01-JUN-19:10 | 1396.30 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.72 | 12-JUN-09:50 | 121.66 | 13-JUN-12:00 |
| July | 792.00 | 01-JUL-00:10 | 1600.67 | 01-JUL-18:10 | 1396.30 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.89 | 15-JUL-15:20 | 54.84 | 06-JUL-02:00 |
| August | 792.00 | 01-AUG-00:10 | 1600.67 | 01-AUG-19:10 | 1396.30 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.77 | 13-AUG-15:20 | 87.13 | 30-AUG-17:15 |
| September | 792.00 | 01-SEP-00:10 | 1600.67 | 01-SEP-19:10 | 1396.30 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.88 | 16-SEP-15:20 | 112.80 | 29-SEP-12:00 |
| October | 792.00 | 01-OCT-00:10 | 1600.67 | 01-OCT-18:10 | 1396.30 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 158.75 | 23-OCT-15:00 |
| November | 792.00 | 01-NOV-00:10 | 1600.67 | 01-NOV-19:10 | 1396.30 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 292.86 | 17-NOV-09:00 |
| December | 792.00 | 01-DEC-00:10 | 1600.67 | 01-DEC-20:10 | 1396.30 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 446.46 | 09-DEC-17:46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 792.00 | 1600.67 | 1396.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.84 | |||||
| Maximum of Months | 792.00 | 1600.67 | 1396.30 | 0.00 | 0.00 | 0.00 | 0.00 | 100.89 | 481.52 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM206_208
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 594.00 | 01-JAN-00:10 | 1292.85 | 01-JAN-19:10 | 1127.78 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 388.92 | 12-JAN-09:04 |
| February | 594.00 | 01-FEB-00:10 | 1292.85 | 01-FEB-20:10 | 1127.78 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 374.49 | 13-FEB-06:00 |
| March | 594.00 | 01-MAR-00:10 | 1292.85 | 01-MAR-20:10 | 1127.78 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.54 | 15-MAR-14:00 | 244.69 | 01-MAR-15:00 |
| April | 594.00 | 01-APR-00:10 | 1292.85 | 01-APR-18:10 | 1127.78 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 215.72 | 04-APR-17:00 |
| May | 594.00 | 01-MAY-00:10 | 1292.85 | 01-MAY-19:10 | 1127.78 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.36 | 14-MAY-15:20 | 117.39 | 11-MAY-15:00 |
| June | 594.00 | 01-JUN-00:10 | 1292.85 | 01-JUN-19:10 | 1127.78 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.12 | 12-JUN-09:50 | 98.27 | 13-JUN-12:00 |
| July | 594.00 | 01-JUL-00:10 | 1292.85 | 01-JUL-18:10 | 1127.78 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 81.71 | 15-JUL-15:20 | 44.29 | 06-JUL-02:00 |
| August | 594.00 | 01-AUG-00:10 | 1292.85 | 01-AUG-19:10 | 1127.78 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.71 | 13-AUG-15:20 | 70.38 | 30-AUG-17:12 |
| September | 594.00 | 01-SEP-00:10 | 1292.85 | 01-SEP-19:10 | 1127.78 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.82 | 16-SEP-15:20 | 91.10 | 29-SEP-12:00 |
| October | 594.00 | 01-OCT-00:10 | 1292.85 | 01-OCT-18:10 | 1127.78 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 128.22 | 23-OCT-15:00 |
| November | 594.00 | 01-NOV-00:10 | 1292.85 | 01-NOV-19:10 | 1127.78 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 241.84 | 17-NOV-09:00 |
| December | 594.00 | 01-DEC-00:10 | 1292.85 | 01-DEC-20:10 | 1127.78 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 363.99 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 594.00 | 1292.85 | 1127.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.29 | |||||
| Maximum of Months | 594.00 | 1292.85 | 1127.78 | 0.00 | 0.00 | 0.00 | 0.00 | 81.71 | 388.92 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM209_212
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 792.00 | 01-JAN-00:10 | 1600.67 | 01-JAN-19:10 | 1396.30 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 481.52 | 12-JAN-09:04 |
| February | 792.00 | 01-FEB-00:10 | 1600.67 | 01-FEB-20:10 | 1396.30 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 463.65 | 13-FEB-06:00 |
| March | 792.00 | 01-MAR-00:10 | 1600.67 | 01-MAR-20:10 | 1396.30 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 15-MAR-14:00 | 302.92 | 01-MAR-15:00 |
| April | 792.00 | 01-APR-00:10 | 1600.67 | 01-APR-18:10 | 1396.30 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 266.69 | 04-APR-17:00 |
| May | 792.00 | 01-MAY-00:10 | 1600.67 | 01-MAY-19:10 | 1396.30 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.31 | 14-MAY-15:20 | 145.34 | 11-MAY-15:00 |
| June | 792.00 | 01-JUN-00:10 | 1600.67 | 01-JUN-19:10 | 1396.30 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.72 | 12-JUN-09:50 | 121.66 | 13-JUN-12:00 |
| July | 792.00 | 01-JUL-00:10 | 1600.67 | 01-JUL-18:10 | 1396.30 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 101.96 | 15-JUL-15:20 | 54.84 | 06-JUL-02:00 |
| August | 792.00 | 01-AUG-00:10 | 1600.67 | 01-AUG-19:10 | 1396.30 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.99 | 13-AUG-15:20 | 87.13 | 30-AUG-17:12 |
| September | 792.00 | 01-SEP-00:10 | 1600.67 | 01-SEP-19:10 | 1396.30 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.88 | 16-SEP-15:20 | 112.80 | 29-SEP-12:00 |
| October | 792.00 | 01-OCT-00:10 | 1600.67 | 01-OCT-18:10 | 1396.30 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 158.75 | 23-OCT-15:00 |
| November | 792.00 | 01-NOV-00:10 | 1600.67 | 01-NOV-19:10 | 1396.30 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 302.64 | 17-NOV-09:00 |
| December | 792.00 | 01-DEC-00:10 | 1600.67 | 01-DEC-20:10 | 1396.30 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 451.33 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 792.00 | 1600.67 | 1396.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.84 | |||||
| Maximum of Months | 792.00 | 1600.67 | 1396.30 | 0.00 | 0.00 | 0.00 | 0.00 | 101.96 | 481.52 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM213
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 198.00 | 01-JAN-00:10 | 400.17 | 01-JAN-19:10 | 349.07 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 120.38 | 12-JAN-09:06 |
| February | 198.00 | 01-FEB-00:10 | 400.17 | 01-FEB-20:10 | 349.07 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 115.92 | 13-FEB-06:00 |
| March | 198.00 | 01-MAR-00:10 | 400.17 | 01-MAR-20:10 | 349.07 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 15-MAR-14:00 | 70.96 | 01-MAR-15:00 |
| April | 198.00 | 01-APR-00:10 | 400.17 | 01-APR-18:10 | 349.07 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 64.30 | 16-APR-04:00 |
| May | 198.00 | 01-MAY-00:10 | 400.17 | 01-MAY-19:10 | 349.07 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 14-MAY-15:20 | 35.18 | 11-MAY-15:00 |
| June | 198.00 | 01-JUN-00:10 | 400.17 | 01-JUN-19:10 | 349.07 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 12-JUN-09:50 | 30.42 | 13-JUN-12:00 |
| July | 198.00 | 01-JUL-00:10 | 400.17 | 01-JUL-18:10 | 349.07 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 15-JUL-15:20 | 13.71 | 06-JUL-02:00 |
| August | 198.00 | 01-AUG-00:10 | 400.17 | 01-AUG-19:10 | 349.07 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.20 | 13-AUG-15:20 | 21.46 | 30-AUG-17:20 |
| September | 198.00 | 01-SEP-00:10 | 400.17 | 01-SEP-19:10 | 349.07 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.47 | 16-SEP-15:20 | 27.28 | 29-SEP-19:00 |
| October | 198.00 | 01-OCT-00:10 | 400.17 | 01-OCT-18:10 | 349.07 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 38.39 | 23-OCT-15:00 |
| November | 198.00 | 01-NOV-00:10 | 400.17 | 01-NOV-19:10 | 349.07 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 69.34 | 17-NOV-08:55 |
| December | 198.00 | 01-DEC-00:10 | 400.17 | 01-DEC-20:10 | 349.07 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 111.62 | 09-DEC-17:46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 198.00 | 400.17 | 349.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.71 | |||||
| Maximum of Months | 198.00 | 400.17 | 349.07 | 0.00 | 0.00 | 0.00 | 0.00 | 25.62 | 120.38 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM214
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 198.00 | 01-JAN-00:10 | 400.14 | 01-JAN-19:10 | 349.05 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 120.38 | 12-JAN-09:04 |
| February | 198.00 | 01-FEB-00:10 | 400.14 | 01-FEB-20:10 | 349.05 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 115.91 | 13-FEB-06:00 |
| March | 198.00 | 01-MAR-00:10 | 400.14 | 01-MAR-20:10 | 349.05 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 15-MAR-14:00 | 88.18 | 01-MAR-15:00 |
| April | 198.00 | 01-APR-00:10 | 400.14 | 01-APR-18:10 | 349.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 67.76 | 04-APR-17:00 |
| May | 198.00 | 01-MAY-00:10 | 400.14 | 01-MAY-19:10 | 349.05 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 14-MAY-15:20 | 36.33 | 11-MAY-15:00 |
| June | 198.00 | 01-JUN-00:10 | 400.14 | 01-JUN-19:10 | 349.05 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 12-JUN-09:50 | 30.42 | 13-JUN-12:00 |
| July | 198.00 | 01-JUL-00:10 | 400.14 | 01-JUL-18:10 | 349.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 | 15-JUL-15:20 | 13.71 | 06-JUL-02:00 |
| August | 198.00 | 01-AUG-00:10 | 400.14 | 01-AUG-19:10 | 349.05 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 | 13-AUG-15:20 | 19.73 | 30-AUG-17:55 |
| September | 198.00 | 01-SEP-00:10 | 400.14 | 01-SEP-19:10 | 349.05 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.47 | 16-SEP-15:20 | 28.20 | 29-SEP-12:00 |
| October | 198.00 | 01-OCT-00:10 | 400.14 | 01-OCT-18:10 | 349.05 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 11-OCT-16:09 | 39.69 | 23-OCT-15:00 |
| November | 198.00 | 01-NOV-00:10 | 400.14 | 01-NOV-19:10 | 349.05 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 75.21 | 17-NOV-09:00 |
| December | 198.00 | 01-DEC-00:10 | 400.14 | 01-DEC-20:10 | 349.05 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 114.12 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.71 | |||||
| Maximum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 | 120.38 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM215_218
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 545.55 | 12-JAN-09:00 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 519.77 | 13-FEB-04:00 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 404.40 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 333.11 | 04-APR-17:00 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 178.87 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.03 | 27-JUN-13:00 | 161.03 | 13-JUN-15:55 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.40 | 15-JUL-15:00 | 109.93 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.20 | 13-AUG-13:00 | 106.76 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.40 | 16-SEP-13:00 | 173.42 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 187.59 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 360.90 | 17-NOV-09:00 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 576.83 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.76 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.40 | 576.83 |
Report: PeakSpaceGainsMonthly
For: ELEVATORCOREFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 260.25 | 12-JAN-09:00 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 248.50 | 13-FEB-06:00 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 203.38 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 175.22 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 106.27 | 29-MAY-14:00 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 103.37 | 13-JUN-15:55 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 75.91 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 75.37 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 106.71 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 106.72 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 184.40 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 270.06 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.37 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.06 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM219
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 198.00 | 01-JAN-00:10 | 400.14 | 01-JAN-19:10 | 349.05 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 129.48 | 12-JAN-08:55 |
| February | 198.00 | 01-FEB-00:10 | 400.14 | 01-FEB-20:10 | 349.05 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 122.71 | 07-FEB-10:58 |
| March | 198.00 | 01-MAR-00:10 | 400.14 | 01-MAR-20:10 | 349.05 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 15-MAR-14:00 | 88.18 | 01-MAR-15:00 |
| April | 198.00 | 01-APR-00:10 | 400.14 | 01-APR-18:10 | 349.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 71.65 | 04-APR-17:00 |
| May | 198.00 | 01-MAY-00:10 | 400.14 | 01-MAY-19:10 | 349.05 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 14-MAY-15:20 | 52.53 | 29-MAY-15:40 |
| June | 198.00 | 01-JUN-00:10 | 400.14 | 01-JUN-19:10 | 349.05 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 12-JUN-09:50 | 37.66 | 09-JUN-17:07 |
| July | 198.00 | 01-JUL-00:10 | 400.14 | 01-JUL-18:10 | 349.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 | 15-JUL-15:20 | 21.33 | 05-JUL-16:40 |
| August | 198.00 | 01-AUG-00:10 | 400.14 | 01-AUG-19:10 | 349.05 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 | 13-AUG-15:20 | 25.51 | 30-AUG-16:00 |
| September | 198.00 | 01-SEP-00:10 | 400.14 | 01-SEP-19:10 | 349.05 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.47 | 16-SEP-15:20 | 34.58 | 30-SEP-17:14 |
| October | 198.00 | 01-OCT-00:10 | 400.14 | 01-OCT-18:10 | 349.05 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 11-OCT-16:08 | 39.69 | 23-OCT-15:00 |
| November | 198.00 | 01-NOV-00:10 | 400.14 | 01-NOV-19:10 | 349.05 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 76.72 | 17-NOV-08:55 |
| December | 198.00 | 01-DEC-00:10 | 400.14 | 01-DEC-20:10 | 349.05 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 129.32 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | |||||
| Maximum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 | 129.48 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM220_223
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 792.00 | 01-JAN-00:10 | 1600.56 | 01-JAN-19:10 | 1396.20 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 493.13 | 12-JAN-09:00 |
| February | 792.00 | 01-FEB-00:10 | 1600.56 | 01-FEB-20:10 | 1396.20 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 463.65 | 13-FEB-06:00 |
| March | 792.00 | 01-MAR-00:10 | 1600.56 | 01-MAR-20:10 | 1396.20 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 | 15-MAR-14:00 | 352.71 | 01-MAR-15:00 |
| April | 792.00 | 01-APR-00:10 | 1600.56 | 01-APR-18:10 | 1396.20 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 272.11 | 04-APR-17:00 |
| May | 792.00 | 01-MAY-00:10 | 1600.56 | 01-MAY-19:10 | 1396.20 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.31 | 14-MAY-15:20 | 145.34 | 11-MAY-15:00 |
| June | 792.00 | 01-JUN-00:10 | 1600.56 | 01-JUN-19:10 | 1396.20 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 70.72 | 12-JUN-09:50 | 121.66 | 13-JUN-12:00 |
| July | 792.00 | 01-JUL-00:10 | 1600.56 | 01-JUL-18:10 | 1396.20 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.07 | 15-JUL-15:20 | 54.84 | 06-JUL-02:00 |
| August | 792.00 | 01-AUG-00:10 | 1600.56 | 01-AUG-19:10 | 1396.20 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 85.00 | 13-AUG-15:20 | 78.91 | 30-AUG-17:55 |
| September | 792.00 | 01-SEP-00:10 | 1600.56 | 01-SEP-19:10 | 1396.20 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.88 | 16-SEP-15:20 | 112.79 | 29-SEP-12:00 |
| October | 792.00 | 01-OCT-00:10 | 1600.56 | 01-OCT-18:10 | 1396.20 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.32 | 11-OCT-16:09 | 158.75 | 23-OCT-15:00 |
| November | 792.00 | 01-NOV-00:10 | 1600.56 | 01-NOV-19:10 | 1396.20 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 306.91 | 17-NOV-08:55 |
| December | 792.00 | 01-DEC-00:10 | 1600.56 | 01-DEC-20:10 | 1396.20 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 469.88 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 792.00 | 1600.56 | 1396.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.84 | |||||
| Maximum of Months | 792.00 | 1600.56 | 1396.20 | 0.00 | 0.00 | 0.00 | 0.00 | 103.07 | 493.13 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM224
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 198.00 | 01-JAN-00:10 | 400.14 | 01-JAN-19:10 | 349.05 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 120.38 | 12-JAN-09:04 |
| February | 198.00 | 01-FEB-00:10 | 400.14 | 01-FEB-20:10 | 349.05 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 115.91 | 13-FEB-06:00 |
| March | 198.00 | 01-MAR-00:10 | 400.14 | 01-MAR-20:10 | 349.05 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 15-MAR-14:00 | 88.18 | 01-MAR-15:00 |
| April | 198.00 | 01-APR-00:10 | 400.14 | 01-APR-18:10 | 349.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 66.98 | 04-APR-17:00 |
| May | 198.00 | 01-MAY-00:10 | 400.14 | 01-MAY-19:10 | 349.05 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 14-MAY-15:20 | 36.33 | 11-MAY-15:00 |
| June | 198.00 | 01-JUN-00:10 | 400.14 | 01-JUN-19:10 | 349.05 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.68 | 12-JUN-09:50 | 30.42 | 13-JUN-12:00 |
| July | 198.00 | 01-JUL-00:10 | 400.14 | 01-JUL-18:10 | 349.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 | 15-JUL-15:20 | 13.71 | 06-JUL-02:00 |
| August | 198.00 | 01-AUG-00:10 | 400.14 | 01-AUG-19:10 | 349.05 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.25 | 13-AUG-15:20 | 19.73 | 30-AUG-17:55 |
| September | 198.00 | 01-SEP-00:10 | 400.14 | 01-SEP-19:10 | 349.05 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.47 | 16-SEP-15:20 | 28.20 | 29-SEP-12:00 |
| October | 198.00 | 01-OCT-00:10 | 400.14 | 01-OCT-18:10 | 349.05 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 11-OCT-16:09 | 39.69 | 23-OCT-15:00 |
| November | 198.00 | 01-NOV-00:10 | 400.14 | 01-NOV-19:10 | 349.05 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 74.83 | 17-NOV-09:00 |
| December | 198.00 | 01-DEC-00:10 | 400.14 | 01-DEC-20:10 | 349.05 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 111.97 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.71 | |||||
| Maximum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 | 120.38 |
Report: PeakSpaceGainsMonthly
For: FRONTSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 43.20 | 01-JAN-08:09 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 150.09 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 43.20 | 01-FEB-08:09 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 135.90 | 13-FEB-06:00 |
| March | 0.00 | 01-MAR-00:10 | 43.20 | 01-MAR-08:09 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.10 | 14-MAR-14:00 | 103.06 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 43.20 | 01-APR-07:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 88.78 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 43.20 | 01-MAY-07:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.44 | 14-MAY-15:00 | 52.20 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 43.20 | 01-JUN-07:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.84 | 27-JUN-13:00 | 49.10 | 13-JUN-15:55 |
| July | 0.00 | 01-JUL-00:10 | 43.20 | 01-JUL-07:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.61 | 15-JUL-15:00 | 34.93 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 43.20 | 01-AUG-07:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.44 | 13-AUG-13:00 | 36.05 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 43.20 | 01-SEP-07:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 16-SEP-13:00 | 47.03 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 43.20 | 01-OCT-07:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 59.15 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 43.20 | 01-NOV-07:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 95.59 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 43.20 | 01-DEC-08:09 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 138.76 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 43.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.93 | |||||
| Maximum of Months | 0.00 | 43.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.61 | 150.09 |
Report: PeakSpaceGainsMonthly
For: FRONTSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 762.58 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 129.60 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 736.60 | 06-FEB-09:53 |
| March | 0.00 | 01-MAR-00:10 | 129.60 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.86 | 14-MAR-14:00 | 485.69 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 129.60 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 468.10 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 129.60 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.53 | 14-MAY-15:00 | 298.42 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 129.60 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.80 | 27-JUN-13:00 | 310.82 | 13-JUN-03:00 |
| July | 0.00 | 01-JUL-00:10 | 129.60 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 86.20 | 15-JUL-15:00 | 224.24 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 129.60 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 60.86 | 13-AUG-13:00 | 229.94 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 129.60 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 260.35 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 129.60 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 351.36 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 129.60 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 490.14 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 129.60 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 664.66 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.24 | |||||
| Maximum of Months | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.20 | 762.58 |
Report: PeakSpaceGainsMonthly
For: REARSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 865.69 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 129.63 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 803.46 | 06-FEB-09:53 |
| March | 0.00 | 01-MAR-00:10 | 129.63 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.73 | 14-MAR-13:05 | 565.96 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 129.63 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 520.95 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 129.63 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.11 | 10-MAY-14:00 | 327.83 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 129.63 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.73 | 27-JUN-13:00 | 331.15 | 13-JUN-03:00 |
| July | 0.00 | 01-JUL-00:10 | 129.63 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 103.03 | 15-JUL-15:00 | 233.90 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 129.63 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 90.59 | 13-AUG-13:00 | 243.50 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 129.63 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.07 | 16-SEP-13:00 | 278.84 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 129.63 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 370.58 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 129.63 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 524.34 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 129.63 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 761.03 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.90 | |||||
| Maximum of Months | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.03 | 865.69 |
Report: PeakSpaceGainsMonthly
For: CORRIDORFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 623.70 | 01-JAN-07:10 | 675.01 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 907.45 | 12-JAN-09:00 |
| February | 623.70 | 01-FEB-06:10 | 675.01 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 868.37 | 13-FEB-06:00 |
| March | 623.70 | 01-MAR-06:10 | 675.01 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 26.65 | 15-MAR-14:00 | 596.25 | 01-MAR-15:00 |
| April | 623.70 | 01-APR-06:10 | 675.01 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 481.80 | 16-APR-04:00 |
| May | 623.70 | 01-MAY-05:10 | 675.01 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.53 | 14-MAY-15:00 | 263.96 | 11-MAY-15:00 |
| June | 623.70 | 01-JUN-05:10 | 675.01 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.67 | 12-JUN-13:00 | 241.51 | 13-JUN-15:55 |
| July | 623.70 | 01-JUL-06:10 | 675.01 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 159.48 | 15-JUL-15:00 | 154.55 | 06-JUL-02:00 |
| August | 623.70 | 01-AUG-05:10 | 675.01 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.22 | 13-AUG-13:00 | 156.70 | 30-AUG-17:55 |
| September | 623.70 | 01-SEP-05:10 | 675.01 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.63 | 16-SEP-13:00 | 238.80 | 29-SEP-19:00 |
| October | 623.70 | 01-OCT-06:10 | 675.01 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 283.61 | 23-OCT-15:00 |
| November | 623.70 | 01-NOV-05:10 | 675.01 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 507.67 | 17-NOV-09:00 |
| December | 623.70 | 01-DEC-06:10 | 675.01 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 894.51 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 623.70 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.55 | |||||
| Maximum of Months | 623.70 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.48 | 907.45 |
Report: PeakSpaceGainsMonthly
For: REARSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 69.14 | 01-JAN-08:09 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 778.15 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 69.14 | 01-FEB-08:09 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 704.09 | 06-FEB-09:53 |
| March | 0.00 | 01-MAR-00:10 | 69.14 | 01-MAR-08:09 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 88.15 | 14-MAR-14:00 | 454.02 | 18-MAR-13:00 |
| April | 0.00 | 01-APR-00:10 | 69.14 | 01-APR-07:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.58 | 07-APR-13:05 | 454.14 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 69.14 | 01-MAY-07:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.49 | 14-MAY-15:00 | 293.57 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 69.14 | 01-JUN-07:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 95.19 | 27-JUN-13:00 | 314.78 | 13-JUN-03:00 |
| July | 0.00 | 01-JUL-00:10 | 69.14 | 01-JUL-07:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.56 | 15-JUL-15:00 | 214.33 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 69.14 | 01-AUG-07:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 120.56 | 13-AUG-13:00 | 219.82 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 69.14 | 01-SEP-07:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.03 | 16-SEP-13:00 | 230.47 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 69.14 | 01-OCT-07:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.34 | 11-OCT-12:01 | 332.59 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 69.14 | 01-NOV-07:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.81 | 16-NOV-13:00 | 447.03 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 69.14 | 01-DEC-08:09 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 669.69 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 69.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 214.33 | |||||
| Maximum of Months | 0.00 | 69.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.56 | 778.15 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM301
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 341.44 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 329.22 | 07-FEB-10:54 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.78 | 14-MAR-14:00 | 197.77 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 179.55 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.91 | 10-MAY-14:00 | 102.14 | 11-MAY-15:10 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 27-JUN-13:00 | 103.75 | 13-JUN-12:00 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.41 | 15-JUL-15:00 | 73.28 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.38 | 13-AUG-13:00 | 73.44 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.62 | 16-SEP-13:05 | 87.92 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 109.31 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 184.42 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 322.17 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.28 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.41 | 341.44 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM302_305
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 443.85 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 427.97 | 07-FEB-10:54 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 | 14-MAR-14:00 | 274.26 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 250.00 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.46 | 10-MAY-14:00 | 137.74 | 11-MAY-15:10 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 39.32 | 27-JUN-13:00 | 141.92 | 13-JUN-16:00 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.73 | 15-JUL-15:00 | 100.53 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 50.14 | 13-AUG-13:00 | 99.54 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.41 | 16-SEP-13:05 | 123.00 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 | 11-OCT-13:00 | 146.11 | 23-OCT-14:01 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 259.34 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 423.16 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.54 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.73 | 443.85 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM306_308
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 365.02 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 345.67 | 07-FEB-10:54 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.90 | 14-MAR-14:00 | 229.27 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 208.02 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 10-MAY-14:00 | 113.07 | 11-MAY-15:10 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.56 | 27-JUN-13:00 | 114.19 | 13-JUN-16:00 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.63 | 15-JUL-15:00 | 80.53 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.65 | 13-AUG-13:00 | 80.40 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.63 | 16-SEP-13:05 | 102.01 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 | 11-OCT-13:00 | 119.73 | 23-OCT-14:01 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 216.94 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 350.91 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.40 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.63 | 365.02 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM309_312
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 792.00 | 01-JAN-00:10 | 1600.67 | 01-JAN-19:10 | 1396.30 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 532.88 | 12-JAN-09:05 |
| February | 792.00 | 01-FEB-00:10 | 1600.67 | 01-FEB-20:10 | 1396.30 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 513.13 | 13-FEB-06:00 |
| March | 792.00 | 01-MAR-00:10 | 1600.67 | 01-MAR-20:10 | 1396.30 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.78 | 15-MAR-14:00 | 324.88 | 01-MAR-15:00 |
| April | 792.00 | 01-APR-00:10 | 1600.67 | 01-APR-18:10 | 1396.30 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 290.96 | 04-APR-17:00 |
| May | 792.00 | 01-MAY-00:10 | 1600.67 | 01-MAY-19:10 | 1396.30 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.51 | 14-MAY-15:20 | 160.95 | 11-MAY-15:00 |
| June | 792.00 | 01-JUN-00:10 | 1600.67 | 01-JUN-19:10 | 1396.30 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.01 | 12-JUN-09:50 | 134.75 | 13-JUN-12:00 |
| July | 792.00 | 01-JUL-00:10 | 1600.67 | 01-JUL-18:10 | 1396.30 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 111.60 | 15-JUL-15:20 | 60.85 | 06-JUL-02:00 |
| August | 792.00 | 01-AUG-00:10 | 1600.67 | 01-AUG-19:10 | 1396.30 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 92.12 | 13-AUG-15:20 | 96.53 | 30-AUG-17:20 |
| September | 792.00 | 01-SEP-00:10 | 1600.67 | 01-SEP-19:10 | 1396.30 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 | 16-SEP-15:20 | 120.92 | 29-SEP-19:00 |
| October | 792.00 | 01-OCT-00:10 | 1600.67 | 01-OCT-18:10 | 1396.30 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 173.05 | 23-OCT-15:00 |
| November | 792.00 | 01-NOV-00:10 | 1600.67 | 01-NOV-19:10 | 1396.30 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 322.31 | 17-NOV-09:00 |
| December | 792.00 | 01-DEC-00:10 | 1600.67 | 01-DEC-20:10 | 1396.30 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 494.12 | 09-DEC-17:46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 792.00 | 1600.67 | 1396.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.85 | |||||
| Maximum of Months | 792.00 | 1600.67 | 1396.30 | 0.00 | 0.00 | 0.00 | 0.00 | 111.60 | 532.88 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM313
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 110.96 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 106.99 | 07-FEB-10:54 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.18 | 14-MAR-14:00 | 66.18 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 61.24 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.92 | 10-MAY-14:00 | 34.11 | 11-MAY-15:10 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.29 | 27-JUN-13:00 | 33.86 | 13-JUN-03:00 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.43 | 15-JUL-15:00 | 23.99 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.60 | 13-AUG-13:00 | 24.23 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.21 | 16-SEP-13:05 | 29.90 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.82 | 11-OCT-13:00 | 36.68 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 64.27 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 104.70 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.99 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.43 | 110.96 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM314
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 198.00 | 01-JAN-00:10 | 400.14 | 01-JAN-19:10 | 349.05 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 133.22 | 12-JAN-09:05 |
| February | 198.00 | 01-FEB-00:10 | 400.14 | 01-FEB-20:10 | 349.05 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 128.29 | 13-FEB-06:00 |
| March | 198.00 | 01-MAR-00:10 | 400.14 | 01-MAR-20:10 | 349.05 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.95 | 15-MAR-14:00 | 94.64 | 01-MAR-15:00 |
| April | 198.00 | 01-APR-00:10 | 400.14 | 01-APR-18:10 | 349.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 72.00 | 04-APR-17:00 |
| May | 198.00 | 01-MAY-00:10 | 400.14 | 01-MAY-19:10 | 349.05 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.38 | 14-MAY-15:20 | 40.21 | 11-MAY-15:00 |
| June | 198.00 | 01-JUN-00:10 | 400.14 | 01-JUN-19:10 | 349.05 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 12-JUN-09:50 | 33.69 | 13-JUN-12:00 |
| July | 198.00 | 01-JUL-00:10 | 400.14 | 01-JUL-18:10 | 349.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.44 | 15-JUL-15:20 | 15.21 | 06-JUL-02:00 |
| August | 198.00 | 01-AUG-00:10 | 400.14 | 01-AUG-19:10 | 349.05 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.43 | 13-AUG-15:20 | 21.86 | 30-AUG-17:55 |
| September | 198.00 | 01-SEP-00:10 | 400.14 | 01-SEP-19:10 | 349.05 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 11.54 | 16-SEP-15:20 | 30.23 | 29-SEP-19:00 |
| October | 198.00 | 01-OCT-00:10 | 400.14 | 01-OCT-18:10 | 349.05 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 | 11-OCT-16:09 | 43.87 | 23-OCT-15:00 |
| November | 198.00 | 01-NOV-00:10 | 400.14 | 01-NOV-19:10 | 349.05 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 77.81 | 17-NOV-08:55 |
| December | 198.00 | 01-DEC-00:10 | 400.14 | 01-DEC-20:10 | 349.05 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 123.53 | 09-DEC-17:46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.21 | |||||
| Maximum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 28.44 | 133.22 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM315_318
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 792.00 | 01-JAN-00:10 | 1600.56 | 01-JAN-19:10 | 1396.20 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 556.04 | 12-JAN-09:00 |
| February | 792.00 | 01-FEB-00:10 | 1600.56 | 01-FEB-20:10 | 1396.20 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 513.11 | 13-FEB-06:00 |
| March | 792.00 | 01-MAR-00:10 | 1600.56 | 01-MAR-20:10 | 1396.20 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.78 | 15-MAR-14:00 | 390.42 | 01-MAR-15:00 |
| April | 792.00 | 01-APR-00:10 | 1600.56 | 01-APR-18:10 | 1396.20 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 307.50 | 04-APR-17:00 |
| May | 792.00 | 01-MAY-00:10 | 1600.56 | 01-MAY-19:10 | 1396.20 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.51 | 14-MAY-15:20 | 160.94 | 11-MAY-15:00 |
| June | 792.00 | 01-JUN-00:10 | 1600.56 | 01-JUN-19:10 | 1396.20 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.01 | 12-JUN-09:50 | 134.74 | 13-JUN-12:00 |
| July | 792.00 | 01-JUL-00:10 | 1600.56 | 01-JUL-18:10 | 1396.20 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.77 | 15-JUL-15:20 | 60.85 | 06-JUL-02:00 |
| August | 792.00 | 01-AUG-00:10 | 1600.56 | 01-AUG-19:10 | 1396.20 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.81 | 13-AUG-15:20 | 87.44 | 30-AUG-17:55 |
| September | 792.00 | 01-SEP-00:10 | 1600.56 | 01-SEP-19:10 | 1396.20 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 | 16-SEP-15:20 | 124.99 | 29-SEP-12:00 |
| October | 792.00 | 01-OCT-00:10 | 1600.56 | 01-OCT-18:10 | 1396.20 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 | 11-OCT-16:10 | 175.75 | 23-OCT-15:00 |
| November | 792.00 | 01-NOV-00:10 | 1600.56 | 01-NOV-19:10 | 1396.20 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 339.77 | 17-NOV-08:55 |
| December | 792.00 | 01-DEC-00:10 | 1600.56 | 01-DEC-20:10 | 1396.20 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 538.52 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 792.00 | 1600.56 | 1396.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.85 | |||||
| Maximum of Months | 792.00 | 1600.56 | 1396.20 | 0.00 | 0.00 | 0.00 | 0.00 | 113.77 | 556.04 |
Report: PeakSpaceGainsMonthly
For: ELEVATORCOREFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 230.88 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 217.61 | 13-FEB-06:00 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 167.21 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 136.90 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 79.46 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.02 | 27-JUN-13:00 | 73.85 | 13-JUN-15:55 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 22.30 | 15-JUL-15:00 | 54.46 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.71 | 13-AUG-13:00 | 53.14 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 73.26 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 85.27 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 145.04 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 225.42 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.14 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.30 | 230.88 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM319
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 131.01 | 12-JAN-09:00 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 121.65 | 07-FEB-11:00 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 105.53 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 76.99 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 41.22 | 11-MAY-15:10 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.64 | 27-JUN-13:00 | 40.83 | 13-JUN-16:00 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.43 | 15-JUL-15:00 | 28.95 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.96 | 13-AUG-13:00 | 29.14 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 | 16-SEP-13:00 | 40.74 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 44.02 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 81.37 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 129.85 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.95 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.43 | 131.01 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM320_323
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 792.00 | 01-JAN-00:10 | 1600.56 | 01-JAN-19:10 | 1396.20 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 534.24 | 12-JAN-09:00 |
| February | 792.00 | 01-FEB-00:10 | 1600.56 | 01-FEB-20:10 | 1396.20 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 513.12 | 13-FEB-06:00 |
| March | 792.00 | 01-MAR-00:10 | 1600.56 | 01-MAR-20:10 | 1396.20 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.78 | 15-MAR-14:00 | 390.42 | 01-MAR-15:00 |
| April | 792.00 | 01-APR-00:10 | 1600.56 | 01-APR-18:10 | 1396.20 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 294.87 | 04-APR-17:00 |
| May | 792.00 | 01-MAY-00:10 | 1600.56 | 01-MAY-19:10 | 1396.20 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 45.51 | 14-MAY-15:18 | 160.95 | 11-MAY-15:00 |
| June | 792.00 | 01-JUN-00:10 | 1600.56 | 01-JUN-19:10 | 1396.20 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 78.01 | 12-JUN-09:50 | 134.75 | 13-JUN-12:00 |
| July | 792.00 | 01-JUL-00:10 | 1600.56 | 01-JUL-18:10 | 1396.20 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 113.77 | 15-JUL-15:20 | 60.85 | 06-JUL-02:00 |
| August | 792.00 | 01-AUG-00:10 | 1600.56 | 01-AUG-19:10 | 1396.20 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 93.81 | 13-AUG-15:20 | 87.44 | 30-AUG-17:55 |
| September | 792.00 | 01-SEP-00:10 | 1600.56 | 01-SEP-19:10 | 1396.20 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.17 | 16-SEP-15:20 | 124.05 | 29-SEP-12:00 |
| October | 792.00 | 01-OCT-00:10 | 1600.56 | 01-OCT-18:10 | 1396.20 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 | 11-OCT-16:09 | 175.76 | 23-OCT-15:00 |
| November | 792.00 | 01-NOV-00:10 | 1600.56 | 01-NOV-19:10 | 1396.20 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 329.45 | 17-NOV-09:00 |
| December | 792.00 | 01-DEC-00:10 | 1600.56 | 01-DEC-20:10 | 1396.20 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 505.60 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 792.00 | 1600.56 | 1396.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.85 | |||||
| Maximum of Months | 792.00 | 1600.56 | 1396.20 | 0.00 | 0.00 | 0.00 | 0.00 | 113.77 | 534.24 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM324
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 118.99 | 12-JAN-09:00 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 109.98 | 07-FEB-11:00 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.49 | 14-MAR-13:05 | 93.95 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 67.90 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 10-MAY-14:00 | 36.28 | 11-MAY-15:10 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 | 27-JUN-13:00 | 35.85 | 13-JUN-15:55 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.43 | 15-JUL-15:00 | 24.64 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.21 | 13-AUG-13:00 | 25.08 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.18 | 16-SEP-13:30 | 34.22 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 39.66 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 71.81 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 114.08 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.64 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.43 | 118.99 |
Report: PeakSpaceGainsMonthly
For: FRONTSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 43.20 | 01-JAN-08:09 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 156.52 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 43.20 | 01-FEB-08:09 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 141.29 | 06-FEB-09:53 |
| March | 0.00 | 01-MAR-00:10 | 43.20 | 01-MAR-08:09 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.13 | 14-MAR-14:00 | 107.80 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 43.20 | 01-APR-07:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 93.48 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 43.20 | 01-MAY-07:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.45 | 14-MAY-15:00 | 56.54 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 43.20 | 01-JUN-07:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.54 | 27-JUN-13:00 | 55.98 | 13-JUN-03:00 |
| July | 0.00 | 01-JUL-00:10 | 43.20 | 01-JUL-07:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.54 | 15-JUL-15:00 | 40.41 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 43.20 | 01-AUG-07:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.57 | 13-AUG-13:00 | 39.66 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 43.20 | 01-SEP-07:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.06 | 16-SEP-13:00 | 47.78 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 43.20 | 01-OCT-07:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 62.74 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 43.20 | 01-NOV-07:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 97.69 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 43.20 | 01-DEC-08:09 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 143.27 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 43.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.66 | |||||
| Maximum of Months | 0.00 | 43.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.54 | 156.52 |
Report: PeakSpaceGainsMonthly
For: FRONTSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 820.93 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 129.60 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 804.53 | 06-FEB-09:53 |
| March | 0.00 | 01-MAR-00:10 | 129.60 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.83 | 14-MAR-14:00 | 500.85 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 129.60 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 498.70 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 129.60 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.89 | 10-MAY-14:00 | 330.59 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 129.60 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 46.89 | 27-JUN-13:00 | 356.19 | 13-JUN-03:00 |
| July | 0.00 | 01-JUL-00:10 | 129.60 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 80.22 | 15-JUL-15:00 | 255.51 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 129.60 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 65.36 | 13-AUG-13:00 | 254.48 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 129.60 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 264.26 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 129.60 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 372.42 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 129.60 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 497.98 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 129.60 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 683.03 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.48 | |||||
| Maximum of Months | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.22 | 820.93 |
Report: PeakSpaceGainsMonthly
For: REARSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 129.63 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 858.19 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 129.63 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 809.43 | 06-FEB-09:53 |
| March | 0.00 | 01-MAR-00:10 | 129.63 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 7.60 | 14-MAR-12:01 | 597.07 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 129.63 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 492.26 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 129.63 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 325.14 | 05-MAY-17:13 |
| June | 0.00 | 01-JUN-00:10 | 129.63 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.88 | 27-JUN-12:13 | 315.24 | 13-JUN-03:00 |
| July | 0.00 | 01-JUL-00:10 | 129.63 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.56 | 15-JUL-14:01 | 227.48 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 129.63 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.28 | 13-AUG-12:25 | 261.58 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 129.63 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 286.92 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 129.63 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 350.91 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 129.63 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 454.13 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 129.63 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 732.79 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.48 | |||||
| Maximum of Months | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.56 | 858.19 |
Report: PeakSpaceGainsMonthly
For: CORRIDORFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 623.70 | 01-JAN-07:10 | 675.01 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 972.72 | 12-JAN-09:00 |
| February | 623.70 | 01-FEB-06:10 | 675.01 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 930.86 | 13-FEB-06:00 |
| March | 623.70 | 01-MAR-06:10 | 675.01 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.31 | 15-MAR-14:00 | 639.33 | 01-MAR-15:00 |
| April | 623.70 | 01-APR-06:10 | 675.01 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 516.58 | 16-APR-04:00 |
| May | 623.70 | 01-MAY-05:10 | 675.01 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 43.07 | 14-MAY-15:00 | 268.09 | 11-MAY-15:00 |
| June | 623.70 | 01-JUN-05:10 | 675.01 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 124.59 | 12-JUN-13:00 | 259.15 | 13-JUN-15:55 |
| July | 623.70 | 01-JUL-06:10 | 675.01 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 170.43 | 15-JUL-15:00 | 160.32 | 06-JUL-02:00 |
| August | 623.70 | 01-AUG-05:10 | 675.01 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.70 | 13-AUG-13:00 | 168.18 | 30-AUG-17:55 |
| September | 623.70 | 01-SEP-05:10 | 675.01 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 56.08 | 16-SEP-13:00 | 242.91 | 29-SEP-19:00 |
| October | 623.70 | 01-OCT-06:10 | 675.01 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 282.73 | 23-OCT-15:00 |
| November | 623.70 | 01-NOV-05:10 | 675.01 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 544.46 | 17-NOV-09:00 |
| December | 623.70 | 01-DEC-06:10 | 675.01 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 958.97 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 623.70 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.32 | |||||
| Maximum of Months | 623.70 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.43 | 972.72 |
Report: PeakSpaceGainsMonthly
For: REARSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 69.14 | 01-JAN-08:09 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 720.08 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 69.14 | 01-FEB-08:09 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 670.72 | 06-FEB-09:53 |
| March | 0.00 | 01-MAR-00:10 | 69.14 | 01-MAR-08:09 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 52.45 | 14-MAR-12:01 | 439.23 | 23-MAR-16:51 |
| April | 0.00 | 01-APR-00:10 | 69.14 | 01-APR-07:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 436.34 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 69.14 | 01-MAY-07:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 | 10-MAY-14:00 | 285.30 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 69.14 | 01-JUN-07:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.04 | 27-JUN-12:25 | 286.76 | 13-JUN-03:00 |
| July | 0.00 | 01-JUL-00:10 | 69.14 | 01-JUL-07:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.88 | 15-JUL-14:01 | 194.70 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 69.14 | 01-AUG-07:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 67.68 | 13-AUG-13:00 | 234.69 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 69.14 | 01-SEP-07:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.05 | 16-SEP-11:05 | 233.73 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 69.14 | 01-OCT-07:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.01 | 11-OCT-11:55 | 314.84 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 69.14 | 01-NOV-07:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 389.13 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 69.14 | 01-DEC-08:09 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 647.47 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 69.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.70 | |||||
| Maximum of Months | 0.00 | 69.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.88 | 720.08 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM401
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 198.00 | 01-JAN-00:10 | 400.17 | 01-JAN-19:10 | 349.07 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 439.42 | 12-JAN-09:08 |
| February | 198.00 | 01-FEB-00:10 | 400.17 | 01-FEB-20:10 | 349.07 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 423.16 | 13-FEB-06:00 |
| March | 198.00 | 01-MAR-00:10 | 400.17 | 01-MAR-20:10 | 349.07 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.20 | 15-MAR-14:00 | 259.22 | 01-MAR-15:00 |
| April | 198.00 | 01-APR-00:10 | 400.17 | 01-APR-18:10 | 349.07 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 234.83 | 16-APR-04:00 |
| May | 198.00 | 01-MAY-00:10 | 400.17 | 01-MAY-19:10 | 349.07 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.36 | 14-MAY-15:20 | 115.73 | 11-MAY-15:00 |
| June | 198.00 | 01-JUN-00:10 | 400.17 | 01-JUN-19:10 | 349.07 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.11 | 12-JUN-09:50 | 111.20 | 13-JUN-12:00 |
| July | 198.00 | 01-JUL-00:10 | 400.17 | 01-JUL-18:10 | 349.07 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.48 | 15-JUL-15:20 | 50.31 | 06-JUL-02:00 |
| August | 198.00 | 01-AUG-00:10 | 400.17 | 01-AUG-19:10 | 349.07 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.48 | 13-AUG-15:20 | 79.68 | 30-AUG-17:17 |
| September | 198.00 | 01-SEP-00:10 | 400.17 | 01-SEP-19:10 | 349.07 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 | 16-SEP-15:20 | 99.85 | 29-SEP-19:00 |
| October | 198.00 | 01-OCT-00:10 | 400.17 | 01-OCT-18:10 | 349.07 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 120.45 | 23-OCT-15:00 |
| November | 198.00 | 01-NOV-00:10 | 400.17 | 01-NOV-19:10 | 349.07 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 240.61 | 17-NOV-09:05 |
| December | 198.00 | 01-DEC-00:10 | 400.17 | 01-DEC-20:10 | 349.07 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 407.48 | 09-DEC-17:46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 198.00 | 400.17 | 349.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.31 | |||||
| Maximum of Months | 198.00 | 400.17 | 349.07 | 0.00 | 0.00 | 0.00 | 0.00 | 89.48 | 439.42 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM402_405
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 475.82 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 458.78 | 07-FEB-10:54 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 6.26 | 14-MAR-12:25 | 285.31 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 243.99 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 155.37 | 29-MAY-14:00 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.13 | 27-JUN-13:00 | 153.22 | 13-JUN-16:00 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.59 | 15-JUL-15:00 | 91.88 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.43 | 13-AUG-13:00 | 105.29 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 | 16-SEP-13:00 | 116.85 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 143.89 | 23-OCT-14:01 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 237.29 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 449.05 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.88 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.59 | 475.82 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM406_408
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 384.32 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 370.55 | 07-FEB-10:54 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.25 | 14-MAR-12:25 | 236.12 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 202.25 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 125.57 | 29-MAY-14:00 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 33.22 | 27-JUN-13:00 | 123.45 | 13-JUN-16:00 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.75 | 15-JUL-15:00 | 74.32 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 34.27 | 13-AUG-13:00 | 85.44 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.93 | 16-SEP-13:00 | 97.19 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 118.09 | 23-OCT-14:01 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 198.11 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 362.69 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.32 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.75 | 384.32 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM409_412
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 792.00 | 01-JAN-00:10 | 1600.67 | 01-JAN-19:10 | 1396.30 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 571.21 | 12-JAN-09:06 |
| February | 792.00 | 01-FEB-00:10 | 1600.67 | 01-FEB-20:10 | 1396.30 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 550.06 | 13-FEB-06:00 |
| March | 792.00 | 01-MAR-00:10 | 1600.67 | 01-MAR-20:10 | 1396.30 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 | 15-MAR-14:00 | 341.84 | 01-MAR-15:00 |
| April | 792.00 | 01-APR-00:10 | 1600.67 | 01-APR-18:10 | 1396.30 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 305.25 | 16-APR-04:00 |
| May | 792.00 | 01-MAY-00:10 | 1600.67 | 01-MAY-19:10 | 1396.30 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.57 | 14-MAY-15:20 | 169.31 | 11-MAY-15:00 |
| June | 792.00 | 01-JUN-00:10 | 1600.67 | 01-JUN-19:10 | 1396.30 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.34 | 12-JUN-09:50 | 144.55 | 13-JUN-12:00 |
| July | 792.00 | 01-JUL-00:10 | 1600.67 | 01-JUL-18:10 | 1396.30 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.62 | 15-JUL-15:20 | 65.40 | 06-JUL-02:00 |
| August | 792.00 | 01-AUG-00:10 | 1600.67 | 01-AUG-19:10 | 1396.30 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.26 | 13-AUG-15:20 | 103.57 | 30-AUG-17:15 |
| September | 792.00 | 01-SEP-00:10 | 1600.67 | 01-SEP-19:10 | 1396.30 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.31 | 16-SEP-15:20 | 129.79 | 29-SEP-19:00 |
| October | 792.00 | 01-OCT-00:10 | 1600.67 | 01-OCT-18:10 | 1396.30 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 175.51 | 23-OCT-15:00 |
| November | 792.00 | 01-NOV-00:10 | 1600.67 | 01-NOV-19:10 | 1396.30 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 323.28 | 17-NOV-08:55 |
| December | 792.00 | 01-DEC-00:10 | 1600.67 | 01-DEC-20:10 | 1396.30 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 529.69 | 09-DEC-17:46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 792.00 | 1600.67 | 1396.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.40 | |||||
| Maximum of Months | 792.00 | 1600.67 | 1396.30 | 0.00 | 0.00 | 0.00 | 0.00 | 121.62 | 571.21 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM413
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 118.96 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 114.69 | 07-FEB-10:54 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.95 | 14-MAR-12:25 | 68.94 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 60.32 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.18 | 10-MAY-14:00 | 35.79 | 29-MAY-14:00 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 27-JUN-13:00 | 35.78 | 13-JUN-15:55 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 | 15-JUL-15:00 | 22.37 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.61 | 13-AUG-13:00 | 26.27 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 16-SEP-13:00 | 29.72 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 36.30 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 59.40 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 112.26 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.37 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 | 118.96 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM414
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 118.96 | 12-JAN-09:00 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 114.69 | 07-FEB-10:54 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 100.25 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 65.28 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 39.48 | 29-MAY-14:00 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.28 | 27-JUN-13:00 | 37.52 | 13-JUN-15:55 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 | 15-JUL-15:00 | 23.27 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.61 | 13-AUG-13:00 | 27.20 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.22 | 16-SEP-13:00 | 33.89 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 38.99 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 64.87 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 112.26 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.27 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 | 118.96 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM415_418
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 792.00 | 01-JAN-00:10 | 1600.56 | 01-JAN-19:10 | 1396.20 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 571.21 | 12-JAN-09:05 |
| February | 792.00 | 01-FEB-00:10 | 1600.56 | 01-FEB-20:10 | 1396.20 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 550.04 | 13-FEB-06:00 |
| March | 792.00 | 01-MAR-00:10 | 1600.56 | 01-MAR-20:10 | 1396.20 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 | 15-MAR-14:00 | 418.59 | 01-MAR-15:00 |
| April | 792.00 | 01-APR-00:10 | 1600.56 | 01-APR-18:10 | 1396.20 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 310.96 | 04-APR-17:00 |
| May | 792.00 | 01-MAY-00:10 | 1600.56 | 01-MAY-19:10 | 1396.20 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.57 | 14-MAY-15:20 | 172.65 | 11-MAY-15:00 |
| June | 792.00 | 01-JUN-00:10 | 1600.56 | 01-JUN-19:10 | 1396.20 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.34 | 12-JUN-09:50 | 144.54 | 13-JUN-12:00 |
| July | 792.00 | 01-JUL-00:10 | 1600.56 | 01-JUL-18:10 | 1396.20 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.65 | 15-JUL-15:20 | 65.41 | 06-JUL-02:00 |
| August | 792.00 | 01-AUG-00:10 | 1600.56 | 01-AUG-19:10 | 1396.20 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.30 | 13-AUG-15:20 | 93.86 | 30-AUG-18:00 |
| September | 792.00 | 01-SEP-00:10 | 1600.56 | 01-SEP-19:10 | 1396.20 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.31 | 16-SEP-15:20 | 134.16 | 29-SEP-12:00 |
| October | 792.00 | 01-OCT-00:10 | 1600.56 | 01-OCT-18:10 | 1396.20 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 | 11-OCT-16:09 | 187.31 | 23-OCT-15:00 |
| November | 792.00 | 01-NOV-00:10 | 1600.56 | 01-NOV-19:10 | 1396.20 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 335.59 | 17-NOV-09:00 |
| December | 792.00 | 01-DEC-00:10 | 1600.56 | 01-DEC-20:10 | 1396.20 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 529.69 | 09-DEC-17:46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 792.00 | 1600.56 | 1396.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.41 | |||||
| Maximum of Months | 792.00 | 1600.56 | 1396.20 | 0.00 | 0.00 | 0.00 | 0.00 | 121.65 | 571.21 |
Report: PeakSpaceGainsMonthly
For: ELEVATORCOREFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 224.00 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 212.56 | 07-FEB-11:00 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 168.43 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 128.24 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 73.54 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 | 27-JUN-13:00 | 69.83 | 13-JUN-15:55 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.31 | 15-JUL-15:00 | 43.29 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 17.13 | 13-AUG-13:00 | 49.66 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.60 | 16-SEP-12:25 | 66.55 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 79.05 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 131.49 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 217.53 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.29 | |||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.31 | 224.00 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM419
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 198.00 | 01-JAN-00:10 | 400.14 | 01-JAN-19:10 | 349.05 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 142.80 | 12-JAN-09:05 |
| February | 198.00 | 01-FEB-00:10 | 400.14 | 01-FEB-20:10 | 349.05 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 137.51 | 13-FEB-06:00 |
| March | 198.00 | 01-MAR-00:10 | 400.14 | 01-MAR-20:10 | 349.05 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | 15-MAR-14:00 | 104.65 | 01-MAR-15:00 |
| April | 198.00 | 01-APR-00:10 | 400.14 | 01-APR-18:10 | 349.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 77.29 | 04-APR-17:00 |
| May | 198.00 | 01-MAY-00:10 | 400.14 | 01-MAY-19:10 | 349.05 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.14 | 14-MAY-15:20 | 43.16 | 11-MAY-15:00 |
| June | 198.00 | 01-JUN-00:10 | 400.14 | 01-JUN-19:10 | 349.05 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 12-JUN-09:50 | 36.14 | 13-JUN-12:00 |
| July | 198.00 | 01-JUL-00:10 | 400.14 | 01-JUL-18:10 | 349.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 15-JUL-15:20 | 16.35 | 06-JUL-02:00 |
| August | 198.00 | 01-AUG-00:10 | 400.14 | 01-AUG-19:10 | 349.05 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 | 13-AUG-15:20 | 23.46 | 30-AUG-17:55 |
| September | 198.00 | 01-SEP-00:10 | 400.14 | 01-SEP-19:10 | 349.05 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 16-SEP-15:20 | 33.08 | 29-SEP-12:00 |
| October | 198.00 | 01-OCT-00:10 | 400.14 | 01-OCT-18:10 | 349.05 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 11-OCT-16:09 | 46.75 | 23-OCT-15:00 |
| November | 198.00 | 01-NOV-00:10 | 400.14 | 01-NOV-19:10 | 349.05 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 83.08 | 17-NOV-08:55 |
| December | 198.00 | 01-DEC-00:10 | 400.14 | 01-DEC-20:10 | 349.05 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 132.42 | 09-DEC-17:46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.35 | |||||
| Maximum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 142.80 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM420_423
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 792.00 | 01-JAN-00:10 | 1600.56 | 01-JAN-19:10 | 1396.20 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 571.21 | 12-JAN-09:04 |
| February | 792.00 | 01-FEB-00:10 | 1600.56 | 01-FEB-20:10 | 1396.20 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 550.05 | 13-FEB-06:00 |
| March | 792.00 | 01-MAR-00:10 | 1600.56 | 01-MAR-20:10 | 1396.20 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 | 15-MAR-14:00 | 418.59 | 01-MAR-15:00 |
| April | 792.00 | 01-APR-00:10 | 1600.56 | 01-APR-18:10 | 1396.20 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 307.98 | 04-APR-17:00 |
| May | 792.00 | 01-MAY-00:10 | 1600.56 | 01-MAY-19:10 | 1396.20 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.56 | 14-MAY-15:20 | 171.58 | 11-MAY-15:00 |
| June | 792.00 | 01-JUN-00:10 | 1600.56 | 01-JUN-19:10 | 1396.20 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 83.34 | 12-JUN-09:50 | 144.54 | 13-JUN-12:00 |
| July | 792.00 | 01-JUL-00:10 | 1600.56 | 01-JUL-18:10 | 1396.20 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 121.65 | 15-JUL-15:20 | 65.41 | 06-JUL-02:00 |
| August | 792.00 | 01-AUG-00:10 | 1600.56 | 01-AUG-19:10 | 1396.20 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.31 | 13-AUG-15:20 | 93.86 | 30-AUG-18:00 |
| September | 792.00 | 01-SEP-00:10 | 1600.56 | 01-SEP-19:10 | 1396.20 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.31 | 16-SEP-15:20 | 132.78 | 29-SEP-12:00 |
| October | 792.00 | 01-OCT-00:10 | 1600.56 | 01-OCT-18:10 | 1396.20 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.47 | 11-OCT-16:09 | 183.43 | 23-OCT-15:00 |
| November | 792.00 | 01-NOV-00:10 | 1600.56 | 01-NOV-19:10 | 1396.20 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 332.62 | 17-NOV-08:55 |
| December | 792.00 | 01-DEC-00:10 | 1600.56 | 01-DEC-20:10 | 1396.20 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 529.69 | 09-DEC-17:46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 792.00 | 1600.56 | 1396.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.41 | |||||
| Maximum of Months | 792.00 | 1600.56 | 1396.20 | 0.00 | 0.00 | 0.00 | 0.00 | 121.65 | 571.21 |
Report: PeakSpaceGainsMonthly
For: GUESTROOM424
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 198.00 | 01-JAN-00:10 | 400.14 | 01-JAN-19:10 | 349.05 | 01-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 142.80 | 12-JAN-09:05 |
| February | 198.00 | 01-FEB-00:10 | 400.14 | 01-FEB-20:10 | 349.05 | 01-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 137.52 | 13-FEB-06:00 |
| March | 198.00 | 01-MAR-00:10 | 400.14 | 01-MAR-20:10 | 349.05 | 01-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 5.26 | 15-MAR-14:00 | 104.65 | 01-MAR-15:00 |
| April | 198.00 | 01-APR-00:10 | 400.14 | 01-APR-18:10 | 349.05 | 01-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 76.31 | 16-APR-04:00 |
| May | 198.00 | 01-MAY-00:10 | 400.14 | 01-MAY-19:10 | 349.05 | 01-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.14 | 14-MAY-15:20 | 41.71 | 11-MAY-15:00 |
| June | 198.00 | 01-JUN-00:10 | 400.14 | 01-JUN-19:10 | 349.05 | 01-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 12-JUN-09:50 | 36.14 | 13-JUN-12:00 |
| July | 198.00 | 01-JUL-00:10 | 400.14 | 01-JUL-18:10 | 349.05 | 01-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 15-JUL-15:20 | 16.35 | 06-JUL-02:00 |
| August | 198.00 | 01-AUG-00:10 | 400.14 | 01-AUG-19:10 | 349.05 | 01-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 25.07 | 13-AUG-15:20 | 23.47 | 30-AUG-17:55 |
| September | 198.00 | 01-SEP-00:10 | 400.14 | 01-SEP-19:10 | 349.05 | 01-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.33 | 16-SEP-15:20 | 32.45 | 29-SEP-19:00 |
| October | 198.00 | 01-OCT-00:10 | 400.14 | 01-OCT-18:10 | 349.05 | 01-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 | 11-OCT-16:08 | 44.81 | 23-OCT-15:00 |
| November | 198.00 | 01-NOV-00:10 | 400.14 | 01-NOV-19:10 | 349.05 | 01-NOV-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 78.95 | 17-NOV-08:55 |
| December | 198.00 | 01-DEC-00:10 | 400.14 | 01-DEC-20:10 | 349.05 | 01-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 132.42 | 09-DEC-17:46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.35 | |||||
| Maximum of Months | 198.00 | 400.14 | 349.05 | 0.00 | 0.00 | 0.00 | 0.00 | 30.41 | 142.80 |
Report: PeakSpaceGainsMonthly
For: FRONTSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 43.20 | 01-JAN-08:09 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 159.14 | 12-JAN-08:55 |
| February | 0.00 | 01-FEB-00:10 | 43.20 | 01-FEB-08:09 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 150.19 | 07-FEB-11:00 |
| March | 0.00 | 01-MAR-00:10 | 43.20 | 01-MAR-08:09 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 | 14-MAR-12:13 | 118.12 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 43.20 | 01-APR-07:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 94.19 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 43.20 | 01-MAY-07:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 57.08 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 43.20 | 01-JUN-07:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 8.06 | 27-JUN-12:25 | 55.33 | 13-JUN-15:55 |
| July | 0.00 | 01-JUL-00:10 | 43.20 | 01-JUL-07:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 | 15-JUL-15:00 | 37.02 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 43.20 | 01-AUG-07:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 10.84 | 13-AUG-13:00 | 42.50 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 43.20 | 01-SEP-07:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 49.77 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 43.20 | 01-OCT-07:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 62.04 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 43.20 | 01-NOV-07:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 94.15 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 43.20 | 01-DEC-08:09 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 147.61 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 43.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.02 | |||||
| Maximum of Months | 0.00 | 43.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 | 159.14 |
Report: PeakSpaceGainsMonthly
For: FRONTSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 01-JAN-00:10 | 129.60 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 880.34 | 12-JAN-09:00 |
| February | 0.00 | 01-FEB-00:10 | 129.60 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 878.20 | 07-FEB-10:51 |
| March | 0.00 | 01-MAR-00:10 | 129.60 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.07 | 14-MAR-12:01 | 538.05 | 01-MAR-15:00 |
| April | 0.00 | 01-APR-00:10 | 129.60 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 487.28 | 04-APR-16:51 |
| May | 0.00 | 01-MAY-00:10 | 129.60 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 324.59 | 11-MAY-15:00 |
| June | 0.00 | 01-JUN-00:10 | 129.60 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 332.60 | 13-JUN-03:00 |
| July | 0.00 | 01-JUL-00:10 | 129.60 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.18 | 15-JUL-14:01 | 240.70 | 06-JUL-02:00 |
| August | 0.00 | 01-AUG-00:10 | 129.60 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.16 | 13-AUG-12:25 | 269.25 | 30-AUG-17:55 |
| September | 0.00 | 01-SEP-00:10 | 129.60 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 271.53 | 29-SEP-19:00 |
| October | 0.00 | 01-OCT-00:10 | 129.60 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 357.22 | 23-OCT-15:00 |
| November | 0.00 | 01-NOV-00:10 | 129.60 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 449.70 | 17-NOV-08:55 |
| December | 0.00 | 01-DEC-00:10 | 129.60 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 732.75 | 09-DEC-15:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.70 | |||||
| Maximum of Months | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.18 | 880.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: REARSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.05 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.77 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 211.62 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.45 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.32 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.96 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.47 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.87 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.03 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.28 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.38 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.07 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.96 | |
| Maximum of Months | 0.00 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDORFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2976.40 | 17-JAN-16:55 | 855.36 | 1620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1828.26 |
| February | 2745.92 | 22-FEB-16:55 | 855.36 | 1620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1461.05 |
| March | 8122.04 | 15-MAR-16:02 | 4276.80 | 8100.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 772.03 | 0.00 |
| April | 6140.96 | 09-APR-15:55 | 427.68 | 1620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816.93 |
| May | 7532.06 | 10-MAY-16:02 | 4276.80 | 8100.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 296.52 | 0.00 |
| June | 11288.80 | 26-JUN-16:02 | 4276.80 | 8100.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2891.62 | 0.00 |
| July | 12874.08 | 16-JUL-16:02 | 2138.40 | 8100.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4216.25 | 0.00 |
| August | 12864.54 | 09-AUG-16:02 | 4276.80 | 8100.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3819.54 | 0.00 |
| September | 10670.73 | 16-SEP-16:02 | 2138.40 | 8100.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1906.18 | 0.00 |
| October | 7887.15 | 11-OCT-15:55 | 855.36 | 1620.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.48 |
| November | 5939.97 | 05-NOV-15:00 | 213.84 | 810.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 648.23 |
| December | 3385.44 | 01-DEC-13:00 | 213.84 | 810.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1160.93 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2745.92 | 213.84 | 810.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 12874.08 | 4276.80 | 8100.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4216.25 | 1828.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: REARSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.45 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.09 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.84 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.27 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.89 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.69 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.36 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.74 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.83 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.34 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.54 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.81 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.69 | |
| Maximum of Months | 0.00 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONTLOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 8376.28 | 31-JAN-20:11 | 12592.80 | 4106.99 | 8795.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 384.88 |
| February | 8550.51 | 06-FEB-11:15 | 5596.80 | 9126.64 | 3909.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 701.27 |
| March | 6842.08 | 01-MAR-02:19 | 5596.80 | 0.00 | 7138.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.29 |
| April | 5181.31 | 24-APR-05:40 | 9794.40 | 1369.00 | 8498.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 5053.87 | 01-MAY-06:00 | 4897.20 | 684.50 | 4249.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 6122.57 | 27-JUN-08:57 | 14691.60 | 6844.98 | 12747.75 | 0.00 | 0.00 | 0.00 | 0.00 | 38.74 | 0.00 |
| July | 6399.81 | 20-JUL-08:55 | 19588.80 | 9126.64 | 16997.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.50 | 0.00 |
| August | 6317.63 | 15-AUG-08:51 | 39177.60 | 18253.28 | 33994.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 | 0.00 |
| September | 6245.83 | 16-SEP-08:52 | 48972.00 | 22816.60 | 42492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.10 | 0.00 |
| October | 5616.39 | 23-OCT-05:04 | 39177.60 | 5475.98 | 33994.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.38 |
| November | 5338.92 | 24-NOV-09:55 | 19588.80 | 9126.64 | 16997.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.51 |
| December | 6884.63 | 07-DEC-23:59 | 5596.80 | 0.00 | 7138.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.16 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 5053.87 | 4897.20 | 0.00 | 3909.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 8550.51 | 48972.00 | 22816.60 | 42492.50 | 0.00 | 0.00 | 0.00 | 0.00 | 38.74 | 701.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: RESTROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 221.87 | 18-JAN-15:01 | 416.99 | 2843.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.02 |
| February | 0.00 | 01-FEB-00:10 | 23.17 | 315.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.36 |
| March | 303.28 | 15-MAR-16:33 | 370.66 | 1263.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.73 | 0.00 |
| April | 247.20 | 09-APR-16:02 | 463.32 | 3159.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.43 |
| May | 330.43 | 23-MAY-16:41 | 926.64 | 3159.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.63 |
| June | 476.41 | 12-JUN-15:55 | 185.33 | 631.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.51 | 0.00 |
| July | 512.12 | 20-JUL-16:02 | 926.64 | 3159.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 | 0.00 |
| August | 528.89 | 09-AUG-16:11 | 926.64 | 3159.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.29 | 0.00 |
| September | 501.99 | 16-SEP-16:02 | 463.32 | 3159.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.90 | 0.00 |
| October | 385.25 | 12-OCT-16:31 | 741.31 | 2527.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.31 |
| November | 282.46 | 05-NOV-15:00 | 46.33 | 315.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.97 |
| December | 198.09 | 15-DEC-13:01 | 370.66 | 2527.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 23.17 | 315.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 528.89 | 926.64 | 3159.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.51 | 32.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MEETINGROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 4517.08 | 31-JAN-16:01 | 0.00 | 11232.79 | 1144.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.80 |
| February | 4691.52 | 06-FEB-16:01 | 0.00 | 11232.79 | 1144.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.08 |
| March | 5575.71 | 15-MAR-14:01 | 10216.80 | 10109.51 | 1030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.81 | 0.00 |
| April | 3209.41 | 03-APR-07:02 | 14190.00 | 5616.39 | 1188.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.29 |
| May | 5708.28 | 23-MAY-14:01 | 10216.80 | 10109.51 | 1030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.08 |
| June | 6111.84 | 12-JUN-17:01 | 0.00 | 5616.39 | 220.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
| July | 6196.44 | 24-JUL-14:01 | 10216.80 | 10109.51 | 1030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.63 | 0.00 |
| August | 6301.80 | 09-AUG-14:01 | 10216.80 | 10109.51 | 1030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 | 0.00 |
| September | 6028.87 | 22-SEP-14:01 | 10216.80 | 10109.51 | 1030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.03 |
| October | 5567.11 | 11-OCT-14:01 | 10216.80 | 10109.51 | 1030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.51 |
| November | 3236.82 | 24-NOV-08:62 | 14190.00 | 5616.39 | 1188.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.38 |
| December | 4467.12 | 11-DEC-10:41 | 0.00 | 10109.51 | 1030.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.66 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3209.41 | 0.00 | 5616.39 | 220.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6301.80 | 14190.00 | 11232.79 | 1188.46 | 0.00 | 0.00 | 0.00 | 0.00 | 17.89 | 240.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MECHANICALROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.70 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.03 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.38 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.15 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.56 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.58 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.16 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.80 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.04 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.91 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.76 | |
| Maximum of Months | 0.00 | 0.00 | 52.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM101
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 421.72 | 31-JAN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.68 |
| February | 443.21 | 06-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.03 |
| March | 353.04 | 06-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.21 |
| April | 280.35 | 16-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.94 |
| May | 174.68 | 11-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.91 |
| June | 170.18 | 13-JUN-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.46 |
| July | 37.41 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 |
| August | 89.87 | 31-AUG-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.42 |
| September | 144.11 | 28-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.43 |
| October | 244.10 | 23-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.16 |
| November | 272.70 | 28-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.31 |
| December | 405.49 | 26-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.29 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 37.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 | |
| Maximum of Months | 443.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM102
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 414.10 | 31-JAN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.59 |
| February | 436.00 | 06-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.06 |
| March | 345.09 | 06-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.76 |
| April | 271.63 | 16-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.29 |
| May | 166.68 | 11-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.41 |
| June | 162.71 | 13-JUN-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 |
| July | 30.08 | 22-JUL-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
| August | 82.13 | 31-AUG-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.73 |
| September | 136.64 | 28-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 |
| October | 236.66 | 23-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.79 |
| November | 264.75 | 28-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.00 |
| December | 396.87 | 26-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.32 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 30.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 | |
| Maximum of Months | 436.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.06 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM103
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1014.69 | 11-JAN-09:03 | 396.00 | 1760.74 | 1667.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.30 |
| February | 985.54 | 17-FEB-16:15 | 641.52 | 672.28 | 442.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.51 |
| March | 1681.71 | 18-MAR-08:61 | 594.00 | 2240.94 | 2404.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.17 |
| April | 1761.05 | 23-APR-08:61 | 594.00 | 2240.94 | 2404.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.66 |
| May | 1771.53 | 27-MAY-20:01 | 1524.60 | 4001.68 | 2676.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.81 |
| June | 1865.41 | 30-JUN-19:11 | 1524.60 | 4001.68 | 2404.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.29 |
| July | 1783.96 | 06-JUL-19:31 | 1524.60 | 4001.68 | 2404.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.14 |
| August | 1799.29 | 03-AUG-20:31 | 1762.20 | 3561.50 | 2676.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 |
| September | 1730.58 | 10-SEP-18:01 | 1287.00 | 4001.68 | 1784.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.63 |
| October | 1706.78 | 24-OCT-08:61 | 396.00 | 1760.74 | 1667.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.05 |
| November | 1766.92 | 18-NOV-09:01 | 594.00 | 2240.94 | 2404.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.11 |
| December | 1667.53 | 02-DEC-09:01 | 594.00 | 2240.94 | 2404.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.78 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 985.54 | 396.00 | 672.28 | 442.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.43 | |
| Maximum of Months | 1865.41 | 1762.20 | 4001.68 | 2676.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM104
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2214.87 | 16-JAN-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.90 |
| February | 2265.27 | 19-FEB-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.57 |
| March | 2279.92 | 07-MAR-16:11 | 748.44 | 784.27 | 515.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.61 |
| April | 2317.90 | 22-APR-16:41 | 1049.40 | 1320.46 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.66 |
| May | 2279.69 | 27-MAY-20:41 | 1524.60 | 4001.40 | 2676.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.84 |
| June | 2324.80 | 30-JUN-20:11 | 1762.20 | 3561.24 | 2676.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.75 |
| July | 2294.81 | 06-JUL-16:11 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.96 |
| August | 2278.14 | 22-AUG-16:01 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 |
| September | 2378.15 | 10-SEP-16:11 | 1049.40 | 1320.46 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.14 |
| October | 2319.33 | 30-OCT-16:11 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.87 |
| November | 2254.31 | 18-NOV-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.85 |
| December | 2217.39 | 04-DEC-16:12 | 641.52 | 672.23 | 442.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.30 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2214.87 | 594.00 | 672.23 | 442.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.12 | |
| Maximum of Months | 2378.15 | 1762.20 | 4001.40 | 2676.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM105
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 3138.15 | 24-JAN-09:01 | 396.00 | 1760.61 | 1667.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.06 |
| February | 3169.92 | 06-FEB-09:01 | 396.00 | 1760.61 | 1667.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.72 |
| March | 3119.76 | 07-MAR-09:01 | 396.00 | 1760.61 | 1667.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.26 |
| April | 2994.90 | 19-APR-16:41 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.93 |
| May | 3023.23 | 03-MAY-18:01 | 1524.60 | 3561.24 | 1784.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.64 |
| June | 3002.32 | 15-JUN-16:31 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.80 |
| July | 2997.15 | 06-JUL-17:01 | 962.28 | 2412.84 | 1675.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.72 |
| August | 2983.51 | 22-AUG-16:51 | 855.36 | 896.31 | 1489.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.01 |
| September | 3019.40 | 10-SEP-16:11 | 1049.40 | 1320.46 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.21 |
| October | 3027.73 | 30-OCT-16:11 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 |
| November | 2937.94 | 26-NOV-17:51 | 839.52 | 1056.37 | 1241.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.41 |
| December | 3157.93 | 26-DEC-09:01 | 396.00 | 1760.61 | 1667.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.70 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2937.94 | 396.00 | 896.31 | 1241.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.01 | |
| Maximum of Months | 3169.92 | 1524.60 | 3561.24 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: EMPLOYEELOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 3604.50 | 06-JAN-12:55 | 3326.40 | 842.40 | 1344.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.32 |
| February | 3648.18 | 28-FEB-12:55 | 3326.40 | 842.40 | 1344.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.67 |
| March | 3986.80 | 14-MAR-11:55 | 3326.40 | 842.40 | 1344.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 | 0.00 |
| April | 3887.37 | 24-APR-11:55 | 3326.40 | 842.40 | 1344.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.56 |
| May | 3924.76 | 10-MAY-11:55 | 3326.40 | 842.40 | 1344.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.93 |
| June | 4127.09 | 12-JUN-12:00 | 3326.40 | 842.40 | 1344.50 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 0.00 |
| July | 4235.92 | 21-JUL-12:00 | 3326.40 | 842.40 | 1344.50 | 0.00 | 0.00 | 0.00 | 0.00 | 8.91 | 0.00 |
| August | 4320.64 | 18-AUG-12:00 | 1663.20 | 421.20 | 672.25 | 0.00 | 0.00 | 0.00 | 0.00 | 7.93 | 0.00 |
| September | 4493.10 | 21-SEP-11:55 | 3326.40 | 842.40 | 1344.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.57 | 0.00 |
| October | 4439.73 | 11-OCT-11:55 | 3326.40 | 842.40 | 1344.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.81 |
| November | 4096.50 | 01-NOV-12:00 | 1663.20 | 421.20 | 672.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.53 |
| December | 3735.44 | 04-DEC-13:00 | 1663.20 | 421.20 | 672.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.17 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3604.50 | 1663.20 | 421.20 | 672.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 4493.10 | 3326.40 | 842.40 | 1344.50 | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 56.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LAUNDRYROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.84 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.14 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.80 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.48 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.79 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.34 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.95 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.60 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.03 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.63 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.88 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.12 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.79 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ELEVATORCOREFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 3524.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.04 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 3524.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.36 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 3524.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.04 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 3524.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.85 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 3524.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 3524.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.15 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 3524.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.11 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 3524.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.86 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 3524.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.85 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 3524.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.59 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 3524.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.83 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 3524.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.05 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 3524.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.04 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 3524.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: EXERCISECENTERFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1420.43 | 30-JAN-01:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.06 |
| February | 1467.79 | 21-FEB-02:41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.91 |
| March | 1589.82 | 07-MAR-05:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.87 |
| April | 1178.41 | 21-APR-12:04 | 7392.00 | 2527.20 | 2424.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.50 |
| May | 1230.01 | 14-MAY-15:02 | 9240.00 | 3159.00 | 6062.01 | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 0.00 |
| June | 1361.09 | 12-JUN-15:02 | 9240.00 | 3159.00 | 6062.01 | 0.00 | 0.00 | 0.00 | 0.00 | 10.62 | 0.00 |
| July | 1416.24 | 19-JUL-15:02 | 9240.00 | 3159.00 | 6062.01 | 0.00 | 0.00 | 0.00 | 0.00 | 14.49 | 0.00 |
| August | 1523.42 | 18-AUG-15:02 | 9240.00 | 3159.00 | 6062.01 | 0.00 | 0.00 | 0.00 | 0.00 | 8.65 | 0.00 |
| September | 1654.32 | 21-SEP-15:02 | 9240.00 | 3159.00 | 6062.01 | 0.00 | 0.00 | 0.00 | 0.00 | 1.55 | 0.00 |
| October | 1545.45 | 11-OCT-15:02 | 9240.00 | 3159.00 | 6062.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.43 |
| November | 1254.23 | 01-NOV-12:04 | 7392.00 | 2527.20 | 2424.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.92 |
| December | 1511.16 | 27-DEC-01:51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1178.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1654.32 | 9240.00 | 3159.00 | 6062.01 | 0.00 | 0.00 | 0.00 | 0.00 | 14.49 | 86.91 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONTOFFICEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2041.51 | 31-JAN-15:02 | 11880.00 | 12509.63 | 14975.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.97 |
| February | 2148.62 | 06-FEB-15:02 | 11880.00 | 12509.63 | 14975.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.95 |
| March | 7560.52 | 08-MAR-15:01 | 11880.00 | 12509.63 | 14975.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.34 |
| April | 7569.17 | 05-APR-14:01 | 11880.00 | 12509.63 | 14975.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.87 |
| May | 7425.00 | 18-MAY-12:01 | 10560.00 | 11119.67 | 13311.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.00 |
| June | 7426.61 | 13-JUN-14:01 | 11880.00 | 12509.63 | 14975.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.53 |
| July | 7048.29 | 06-JUL-14:01 | 11880.00 | 12509.63 | 14975.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.60 |
| August | 7042.46 | 22-AUG-14:01 | 11880.00 | 12509.63 | 14975.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.26 |
| September | 7313.84 | 30-SEP-14:01 | 5940.00 | 12509.63 | 9434.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.84 |
| October | 7653.12 | 16-OCT-12:01 | 10560.00 | 11119.67 | 13311.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.06 |
| November | 7709.38 | 24-NOV-15:01 | 11880.00 | 12509.63 | 14975.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.90 |
| December | 6458.42 | 01-DEC-13:01 | 10560.00 | 11119.67 | 13311.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.23 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2041.51 | 5940.00 | 11119.67 | 9434.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.26 | |
| Maximum of Months | 7709.38 | 11880.00 | 12509.63 | 14975.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.95 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONTSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.10 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.71 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.47 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.49 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.13 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.78 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.30 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.00 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.05 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.71 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.00 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.88 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.78 | |
| Maximum of Months | 0.00 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.47 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONTSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.89 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.79 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.08 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.57 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.25 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.01 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.80 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.86 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.31 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.01 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.15 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.43 | |
| Maximum of Months | 0.00 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: REARSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.00 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.65 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.65 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.66 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.30 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.26 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.95 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.82 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 84.59 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.11 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.82 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.52 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.82 | |
| Maximum of Months | 0.00 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDORFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1094.77 | 05-JAN-22:00 | 178.20 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1114.58 | 27-FEB-22:00 | 178.20 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1937.35 | 15-MAR-20:52 | 1782.00 | 6750.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.73 |
| April | 1649.09 | 09-APR-16:42 | 1782.00 | 6750.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.39 |
| May | 2153.24 | 31-MAY-18:15 | 356.40 | 1350.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.64 |
| June | 2654.37 | 19-JUN-19:02 | 1425.60 | 5400.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.09 |
| July | 2704.44 | 17-JUL-19:32 | 1782.00 | 6750.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.01 |
| August | 2661.21 | 19-AUG-18:05 | 356.40 | 1350.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.44 |
| September | 2506.33 | 15-SEP-20:31 | 1603.80 | 6075.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.80 |
| October | 2001.48 | 11-OCT-16:53 | 2138.40 | 4050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.34 |
| November | 1136.55 | 05-NOV-08:52 | 6237.00 | 6750.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.05 |
| December | 1090.03 | 28-DEC-12:05 | 356.40 | 1350.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.26 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 1090.03 | 178.20 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2704.44 | 6237.00 | 6750.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 538.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: REARSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.18 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.15 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.32 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.47 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.97 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.03 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.99 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.25 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.68 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.65 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.41 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.25 | |
| Maximum of Months | 0.00 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.32 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM201
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 364.71 | 31-JAN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.56 |
| February | 336.24 | 21-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.64 |
| March | 302.16 | 06-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.25 |
| April | 231.13 | 16-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.75 |
| May | 151.31 | 11-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.17 |
| June | 148.90 | 13-JUN-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.50 |
| July | 117.40 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 0.00 |
| August | 409.14 | 14-AUG-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.28 | 0.00 |
| September | 112.28 | 28-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.14 |
| October | 205.33 | 23-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.39 |
| November | 218.72 | 28-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.22 |
| December | 340.25 | 10-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.21 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 112.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 409.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.85 | 243.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM202_205
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6800.72 | 22-JAN-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.52 |
| February | 6934.71 | 19-FEB-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.63 |
| March | 6997.84 | 25-MAR-08:61 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.23 |
| April | 6913.55 | 16-APR-08:61 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.56 |
| May | 7181.78 | 27-MAY-20:01 | 6098.40 | 16006.73 | 10704.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.41 |
| June | 7267.60 | 03-JUN-17:01 | 3421.44 | 10884.57 | 5957.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.92 |
| July | 7252.74 | 06-JUL-16:21 | 4276.80 | 4481.88 | 7446.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.61 |
| August | 7022.35 | 01-AUG-16:11 | 4276.80 | 4481.88 | 7446.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.83 |
| September | 6832.73 | 02-SEP-19:31 | 5148.00 | 16006.73 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 6415.59 | 24-OCT-08:61 | 1584.00 | 7042.96 | 6671.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.07 |
| November | 6759.50 | 18-NOV-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.84 |
| December | 6745.30 | 03-DEC-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 6415.59 | 1584.00 | 4481.88 | 5957.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 7267.60 | 6098.40 | 16006.73 | 10704.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM206_208
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 5724.34 | 21-JAN-09:01 | 1782.00 | 7239.97 | 7769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.90 |
| February | 6053.13 | 25-FEB-09:01 | 1782.00 | 7239.97 | 7769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.53 |
| March | 6177.20 | 04-MAR-09:01 | 1782.00 | 7239.97 | 7769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.70 |
| April | 5689.03 | 16-APR-08:61 | 1782.00 | 7239.97 | 7769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.30 |
| May | 5757.76 | 27-MAY-20:01 | 4573.80 | 12928.51 | 8646.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.05 |
| June | 5770.55 | 30-JUN-20:21 | 4229.28 | 9205.10 | 6917.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.94 |
| July | 5740.07 | 06-JUL-16:21 | 3207.60 | 3619.98 | 6014.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.51 |
| August | 5534.51 | 01-AUG-16:11 | 3207.60 | 3619.98 | 6014.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.88 |
| September | 5490.05 | 02-SEP-19:31 | 3861.00 | 12928.51 | 7769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 5290.53 | 24-OCT-08:61 | 1188.00 | 5688.54 | 5388.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.00 |
| November | 5559.44 | 18-NOV-09:01 | 1782.00 | 7239.97 | 7769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.80 |
| December | 5664.83 | 23-DEC-09:01 | 1782.00 | 7239.97 | 7769.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.88 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 5290.53 | 1188.00 | 3619.98 | 5388.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6177.20 | 4573.80 | 12928.51 | 8646.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.88 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM209_212
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 7564.59 | 29-JAN-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.97 |
| February | 7650.14 | 05-FEB-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.21 |
| March | 7552.58 | 04-MAR-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.72 |
| April | 6990.67 | 16-APR-08:61 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.36 |
| May | 7020.81 | 27-MAY-20:01 | 6098.40 | 16006.73 | 10704.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.47 |
| June | 7115.11 | 03-JUN-17:01 | 3421.44 | 10884.57 | 5957.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.81 |
| July | 6786.60 | 06-JUL-16:41 | 4276.80 | 4481.88 | 7446.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.72 |
| August | 6654.96 | 03-AUG-20:31 | 7048.80 | 14245.99 | 10704.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.87 |
| September | 6691.82 | 02-SEP-19:31 | 5148.00 | 16006.73 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 6430.84 | 24-OCT-08:61 | 1584.00 | 7042.96 | 6671.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.27 |
| November | 6825.10 | 18-NOV-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.40 |
| December | 6959.20 | 23-DEC-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.64 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 6430.84 | 1584.00 | 4481.88 | 5957.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 7650.14 | 7048.80 | 16006.73 | 10704.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.64 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM213
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 894.11 | 03-JAN-09:03 | 396.00 | 1760.74 | 1667.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.85 |
| February | 929.90 | 01-FEB-09:03 | 396.00 | 1760.74 | 1667.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 |
| March | 1679.18 | 18-MAR-08:61 | 594.00 | 2240.94 | 2404.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.69 |
| April | 1787.35 | 23-APR-08:61 | 594.00 | 2240.94 | 2404.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.63 |
| May | 1918.22 | 27-MAY-20:01 | 1524.60 | 4001.68 | 2676.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.23 |
| June | 1903.15 | 03-JUN-18:21 | 1287.00 | 4001.68 | 1784.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.31 |
| July | 1845.15 | 06-JUL-16:41 | 1069.20 | 1120.47 | 1861.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.06 |
| August | 1822.59 | 03-AUG-20:31 | 1762.20 | 3561.50 | 2676.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 |
| September | 1770.51 | 09-SEP-19:41 | 1287.00 | 4001.68 | 2404.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.39 |
| October | 1650.83 | 25-OCT-20:11 | 1762.20 | 3561.50 | 2676.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.94 |
| November | 1695.40 | 12-NOV-09:01 | 594.00 | 2240.94 | 2404.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.99 |
| December | 835.65 | 14-DEC-09:02 | 396.00 | 1760.74 | 1667.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.58 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 835.65 | 396.00 | 1120.47 | 1667.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | |
| Maximum of Months | 1918.22 | 1762.20 | 4001.68 | 2676.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM214
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2585.64 | 12-JAN-16:11 | 748.44 | 784.27 | 515.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.16 |
| February | 2423.86 | 19-FEB-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.72 |
| March | 2563.34 | 04-MAR-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.49 |
| April | 2491.22 | 22-APR-16:41 | 1049.40 | 1320.46 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.83 |
| May | 2516.17 | 21-MAY-17:41 | 855.36 | 2720.95 | 1489.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.70 |
| June | 2509.43 | 04-JUN-16:11 | 1049.40 | 1320.46 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.94 |
| July | 2481.12 | 06-JUL-16:11 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 |
| August | 2481.32 | 22-AUG-16:01 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 |
| September | 2551.13 | 10-SEP-16:11 | 1049.40 | 1320.46 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.43 |
| October | 2562.24 | 30-OCT-16:11 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.32 |
| November | 2356.99 | 18-NOV-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.84 |
| December | 2425.95 | 11-DEC-16:11 | 748.44 | 784.27 | 515.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.52 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2356.99 | 594.00 | 784.27 | 515.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 | |
| Maximum of Months | 2585.64 | 1069.20 | 2720.95 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM215_218
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 3324.42 | 15-JAN-15:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.67 |
| February | 3181.22 | 28-FEB-15:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.90 |
| March | 4231.75 | 15-MAR-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.58 |
| April | 3800.80 | 09-APR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.36 |
| May | 3957.20 | 14-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.82 |
| June | 4178.42 | 12-JUN-15:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.87 | 0.00 |
| July | 4337.08 | 19-JUL-15:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.93 | 0.00 |
| August | 4688.52 | 18-AUG-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.99 | 0.00 |
| September | 5279.20 | 21-SEP-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.16 |
| October | 4933.77 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.00 |
| November | 3888.89 | 03-NOV-14:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.42 |
| December | 3141.58 | 16-DEC-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.88 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 3141.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 5279.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.93 | 174.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ELEVATORCOREFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.82 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.16 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.30 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.25 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.16 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.54 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.72 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.20 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.66 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.77 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.51 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.16 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM219
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 7849.47 | 16-JAN-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.15 |
| February | 7700.35 | 19-FEB-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.93 |
| March | 8742.59 | 14-MAR-18:51 | 1524.60 | 3561.24 | 1784.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.22 |
| April | 8679.45 | 09-APR-16:41 | 1049.40 | 1320.46 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.75 |
| May | 8801.11 | 21-MAY-19:31 | 1287.00 | 4001.40 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.61 |
| June | 8933.13 | 23-JUN-18:11 | 1524.60 | 3561.24 | 1784.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.21 |
| July | 8710.74 | 09-JUL-16:01 | 1049.40 | 1320.46 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.70 |
| August | 8959.72 | 21-AUG-18:11 | 1524.60 | 3561.24 | 1784.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.88 |
| September | 8943.93 | 18-SEP-19:21 | 1524.60 | 4001.40 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.39 |
| October | 8725.55 | 11-OCT-16:01 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 |
| November | 8590.98 | 05-NOV-16:11 | 1049.40 | 1320.46 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.06 |
| December | 7889.58 | 17-DEC-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.96 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 7700.35 | 594.00 | 1120.39 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.58 | |
| Maximum of Months | 8959.72 | 1524.60 | 4001.40 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM220_223
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 9408.42 | 12-JAN-16:11 | 2993.76 | 3137.10 | 2063.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.61 |
| February | 9516.17 | 05-FEB-09:01 | 2376.00 | 8963.13 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.97 |
| March | 9492.46 | 04-MAR-09:01 | 2376.00 | 8963.13 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.11 |
| April | 8880.84 | 19-APR-16:41 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.54 |
| May | 8924.72 | 20-MAY-16:21 | 4197.60 | 5281.84 | 6205.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.76 |
| June | 8864.24 | 03-JUN-16:21 | 4197.60 | 5281.84 | 6205.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.16 |
| July | 8668.40 | 06-JUL-16:11 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.39 |
| August | 8664.04 | 22-AUG-16:01 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 |
| September | 8952.30 | 10-SEP-16:11 | 4197.60 | 5281.84 | 6205.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.04 |
| October | 9102.14 | 30-OCT-16:11 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.02 |
| November | 8478.38 | 18-NOV-09:01 | 2376.00 | 8963.13 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.08 |
| December | 9355.16 | 10-DEC-09:01 | 2376.00 | 8963.13 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.06 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 8478.38 | 2376.00 | 3137.10 | 2063.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.05 | |
| Maximum of Months | 9516.17 | 4276.80 | 8963.13 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM224
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2558.27 | 12-JAN-16:11 | 748.44 | 784.27 | 515.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.99 |
| February | 2349.80 | 19-FEB-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.32 |
| March | 2515.15 | 04-MAR-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 |
| April | 2447.71 | 22-APR-16:41 | 1049.40 | 1320.46 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.40 |
| May | 2479.13 | 27-MAY-19:31 | 1287.00 | 4001.40 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.74 |
| June | 2474.38 | 03-JUN-17:41 | 855.36 | 2720.95 | 1489.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.44 |
| July | 2445.14 | 06-JUL-16:11 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.21 |
| August | 2442.19 | 22-AUG-16:01 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 |
| September | 2516.46 | 10-SEP-16:11 | 1049.40 | 1320.46 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.43 |
| October | 2510.54 | 30-OCT-16:11 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.20 |
| November | 2322.47 | 18-NOV-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.84 |
| December | 2285.49 | 04-DEC-16:12 | 641.52 | 672.23 | 442.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.34 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2285.49 | 594.00 | 672.23 | 442.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.41 | |
| Maximum of Months | 2558.27 | 1287.00 | 4001.40 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONTSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.14 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.74 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.30 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.73 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.05 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.80 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.96 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.62 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.45 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.06 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.04 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.96 | |
| Maximum of Months | 0.00 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONTSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.41 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.73 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.13 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.81 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.27 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.37 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.93 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.14 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.47 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.09 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.02 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.22 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.27 | |
| Maximum of Months | 0.00 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: REARSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.79 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.73 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.52 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.18 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.28 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.60 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.75 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.72 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.85 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.23 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 199.18 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.46 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.72 | |
| Maximum of Months | 0.00 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 243.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDORFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 462.39 | 15-JAN-16:00 | 178.20 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.93 |
| February | 141.14 | 18-FEB-15:25 | 356.40 | 1350.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.35 |
| March | 1051.72 | 15-MAR-20:52 | 1782.00 | 6750.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.13 |
| April | 941.54 | 17-APR-06:59 | 4365.90 | 4725.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.79 |
| May | 1318.08 | 31-MAY-19:22 | 1782.00 | 6750.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.45 |
| June | 1982.46 | 12-JUN-15:23 | 1069.20 | 2025.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.93 | 0.00 |
| July | 2032.79 | 19-JUL-15:02 | 3564.00 | 6750.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.90 | 0.00 |
| August | 2006.91 | 09-AUG-15:23 | 1069.20 | 2025.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.70 | 0.00 |
| September | 1759.26 | 16-SEP-15:23 | 534.60 | 2025.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.02 | 0.00 |
| October | 885.97 | 11-OCT-16:53 | 2138.40 | 4050.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.87 |
| November | 782.85 | 22-NOV-19:15 | 356.40 | 1350.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.33 |
| December | 502.93 | 16-DEC-15:02 | 1603.80 | 6075.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.55 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 141.14 | 178.20 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 2032.79 | 4365.90 | 6750.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.90 | 268.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: REARSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.41 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.40 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.82 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.47 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.29 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.84 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.56 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.51 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.57 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.72 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.78 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.92 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.29 | |
| Maximum of Months | 0.00 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM301
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 229.55 | 27-JAN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.29 |
| February | 266.15 | 10-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.02 |
| March | 248.16 | 03-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.99 |
| April | 204.78 | 16-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 126.08 |
| May | 135.22 | 11-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.65 |
| June | 136.35 | 13-JUN-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.02 |
| July | 107.21 | 21-JUL-14:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 | 0.00 |
| August | 49.62 | 31-AUG-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.01 |
| September | 93.50 | 28-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.49 |
| October | 183.37 | 23-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.43 |
| November | 190.60 | 28-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.00 |
| December | 266.45 | 25-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.77 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 49.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 266.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.42 | 157.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM302_305
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1351.18 | 23-JAN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 240.07 |
| February | 1378.87 | 05-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.57 |
| March | 1276.08 | 06-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.97 |
| April | 988.79 | 16-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.29 |
| May | 684.00 | 11-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.41 |
| June | 678.90 | 13-JUN-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.17 |
| July | 227.60 | 27-JUL-14:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.97 | 0.00 |
| August | 305.37 | 31-AUG-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.11 |
| September | 476.26 | 28-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.61 |
| October | 880.88 | 23-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.11 |
| November | 919.59 | 28-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.46 |
| December | 1243.36 | 25-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.77 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 227.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1378.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.97 | 240.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM306_308
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 1242.29 | 31-JAN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.11 |
| February | 1170.98 | 21-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.97 |
| March | 1045.69 | 06-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.15 |
| April | 814.50 | 16-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.97 |
| May | 554.97 | 11-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.86 |
| June | 539.31 | 13-JUN-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.42 |
| July | 262.20 | 27-JUL-14:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 0.00 |
| August | 245.72 | 31-AUG-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.94 |
| September | 389.47 | 28-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.49 |
| October | 714.00 | 23-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.73 |
| November | 755.76 | 28-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.88 |
| December | 1166.15 | 10-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.87 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 245.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1242.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.59 | 288.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM309_312
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6617.08 | 22-JAN-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.98 |
| February | 6740.64 | 19-FEB-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.02 |
| March | 6790.31 | 25-MAR-08:61 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.83 |
| April | 6717.72 | 16-APR-08:61 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.34 |
| May | 6890.05 | 27-MAY-20:01 | 6098.40 | 16006.73 | 10704.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.68 |
| June | 6957.91 | 03-JUN-17:01 | 3421.44 | 10884.57 | 5957.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.78 |
| July | 6638.67 | 06-JUL-16:41 | 4276.80 | 4481.88 | 7446.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.57 |
| August | 6516.29 | 03-AUG-20:31 | 7048.80 | 14245.99 | 10704.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.11 |
| September | 6491.85 | 02-SEP-19:31 | 5148.00 | 16006.73 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 6054.73 | 17-OCT-08:61 | 1584.00 | 7042.96 | 6671.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.49 |
| November | 6491.75 | 18-NOV-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.48 |
| December | 6686.71 | 23-DEC-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.89 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 6054.73 | 1584.00 | 4481.88 | 5957.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6957.91 | 7048.80 | 16006.73 | 10704.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM313
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 278.03 | 03-JAN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.50 |
| February | 303.48 | 05-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.42 |
| March | 257.06 | 04-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.80 |
| April | 203.12 | 16-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.93 |
| May | 132.81 | 11-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.24 |
| June | 127.43 | 13-JUN-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.46 |
| July | 31.23 | 21-JUL-14:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 | 0.00 |
| August | 38.43 | 31-AUG-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.50 |
| September | 86.87 | 28-SEP-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.66 |
| October | 183.93 | 23-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.12 |
| November | 192.68 | 28-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.13 |
| December | 269.67 | 25-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.25 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 31.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 303.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.31 | 46.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM314
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2048.27 | 16-JAN-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.76 |
| February | 2149.75 | 28-FEB-16:12 | 641.52 | 672.23 | 442.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.50 |
| March | 2241.63 | 26-MAR-18:02 | 772.20 | 2400.84 | 1070.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.50 |
| April | 2309.37 | 22-APR-16:41 | 1049.40 | 1320.46 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.80 |
| May | 2347.18 | 27-MAY-19:31 | 1287.00 | 4001.40 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.78 |
| June | 2337.22 | 03-JUN-17:41 | 855.36 | 2720.95 | 1489.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.78 |
| July | 2301.80 | 06-JUL-16:11 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.87 |
| August | 2297.84 | 22-AUG-16:01 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 |
| September | 2365.56 | 10-SEP-16:11 | 1049.40 | 1320.46 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 |
| October | 2264.31 | 30-OCT-16:11 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.45 |
| November | 2087.10 | 18-NOV-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.37 |
| December | 2048.75 | 17-DEC-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.94 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2048.27 | 594.00 | 672.23 | 442.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.85 | |
| Maximum of Months | 2365.56 | 1287.00 | 4001.40 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM315_318
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 10282.97 | 24-JAN-09:01 | 1584.00 | 7042.46 | 6670.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.98 |
| February | 10366.31 | 05-FEB-09:01 | 2376.00 | 8963.13 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.33 |
| March | 10254.41 | 04-MAR-09:01 | 2376.00 | 8963.13 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.96 |
| April | 9707.11 | 19-APR-16:41 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.02 |
| May | 9817.16 | 19-MAY-16:11 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.62 |
| June | 9913.71 | 05-JUN-16:21 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.86 |
| July | 9761.21 | 06-JUL-17:01 | 3849.12 | 9651.37 | 6701.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.45 |
| August | 9706.39 | 22-AUG-16:51 | 3421.44 | 3585.25 | 5957.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.91 |
| September | 9801.74 | 10-SEP-16:11 | 4197.60 | 5281.84 | 6205.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.65 |
| October | 9830.96 | 30-OCT-16:11 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.36 |
| November | 9261.27 | 26-NOV-17:51 | 3358.08 | 4225.48 | 4964.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.78 |
| December | 10232.68 | 26-DEC-09:01 | 1584.00 | 7042.46 | 6670.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.43 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 9261.27 | 1584.00 | 3585.25 | 4964.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.36 | |
| Maximum of Months | 10366.31 | 4276.80 | 9651.37 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ELEVATORCOREFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.98 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.81 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.54 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.53 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.86 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.62 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.99 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.94 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.57 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.09 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.77 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.31 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM319
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 424.10 | 31-JAN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.81 |
| February | 442.17 | 06-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 108.73 |
| March | 402.72 | 06-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.47 |
| April | 280.47 | 16-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.21 |
| May | 161.45 | 11-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.54 |
| June | 198.64 | 12-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 | 0.00 |
| July | 226.05 | 29-JUL-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.61 |
| August | 291.39 | 18-AUG-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.94 | 0.00 |
| September | 383.27 | 21-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.24 |
| October | 252.10 | 11-OCT-14:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.06 |
| November | 242.82 | 28-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.57 |
| December | 425.16 | 10-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.12 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 161.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 442.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.77 | 108.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM320_323
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 9081.13 | 12-JAN-16:11 | 2993.76 | 3137.10 | 2063.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.17 |
| February | 9001.11 | 05-FEB-09:01 | 2376.00 | 8963.13 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.11 |
| March | 9006.72 | 04-MAR-09:01 | 2376.00 | 8963.13 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.35 |
| April | 8507.97 | 19-APR-16:41 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.07 |
| May | 8554.66 | 20-MAY-16:21 | 4197.60 | 5281.84 | 6205.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.23 |
| June | 8510.23 | 03-JUN-16:21 | 4197.60 | 5281.84 | 6205.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.18 |
| July | 8293.40 | 06-JUL-16:11 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.95 |
| August | 8276.90 | 22-AUG-16:01 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 |
| September | 8560.13 | 10-SEP-16:11 | 4197.60 | 5281.84 | 6205.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.82 |
| October | 8677.42 | 30-OCT-16:11 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 |
| November | 8091.61 | 18-NOV-09:01 | 2376.00 | 8963.13 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.57 |
| December | 8717.07 | 11-DEC-16:11 | 2993.76 | 3137.10 | 2063.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.20 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 8091.61 | 2376.00 | 3137.10 | 2063.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.76 | |
| Maximum of Months | 9081.13 | 4276.80 | 8963.13 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 368.17 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM324
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 400.98 | 31-JAN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.07 |
| February | 419.38 | 06-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.03 |
| March | 385.32 | 06-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.78 |
| April | 264.71 | 16-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.55 |
| May | 157.99 | 11-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.15 |
| June | 150.88 | 13-JUN-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.93 |
| July | 96.14 | 25-JUL-14:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.25 | 0.00 |
| August | 98.67 | 18-AUG-14:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.09 | 0.00 |
| September | 163.33 | 21-SEP-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.10 |
| October | 217.91 | 23-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.15 |
| November | 234.48 | 28-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.97 |
| December | 402.59 | 10-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.31 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 96.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 419.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.09 | 98.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONTSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.35 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.42 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.97 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.54 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.78 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.23 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.67 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.89 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.41 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.24 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.65 | |
| Maximum of Months | 0.00 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONTSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.89 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.30 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.43 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.90 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.46 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.77 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.05 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.82 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.68 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.08 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.93 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.54 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.46 | |
| Maximum of Months | 0.00 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: REARSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.16 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.10 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.61 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.85 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.06 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.18 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.78 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.28 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.51 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.20 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.28 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.23 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.06 | |
| Maximum of Months | 0.00 | 0.00 | 129.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORRIDORFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 282.63 | 15-JAN-14:50 | 178.20 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.65 |
| February | 636.62 | 28-FEB-13:25 | 356.40 | 1350.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.85 |
| March | 2028.02 | 15-MAR-14:13 | 712.80 | 2700.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.40 | 0.00 |
| April | 1419.05 | 09-APR-15:02 | 1782.00 | 6750.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.90 |
| May | 2535.91 | 14-MAY-14:40 | 356.40 | 1350.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.64 | 0.00 |
| June | 3335.31 | 12-JUN-14:00 | 178.20 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.10 | 0.00 |
| July | 3427.63 | 21-JUL-13:50 | 178.20 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.38 | 0.00 |
| August | 3438.20 | 09-AUG-15:02 | 3564.00 | 6750.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.20 | 0.00 |
| September | 2811.72 | 16-SEP-14:00 | 178.20 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.03 | 0.00 |
| October | 1636.35 | 11-OCT-16:02 | 3564.00 | 6750.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.48 |
| November | 502.16 | 18-NOV-14:00 | 178.20 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.63 |
| December | 446.98 | 16-DEC-14:00 | 178.20 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.25 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 282.63 | 178.20 | 675.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 3438.20 | 3564.00 | 6750.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.10 | 290.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: REARSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 177.15 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.24 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.85 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.14 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.99 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.00 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.55 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.80 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.08 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.00 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.95 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.20 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 56.99 | |
| Maximum of Months | 0.00 | 0.00 | 17.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.85 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM401
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 584.67 | 17-JAN-09:03 | 396.00 | 1760.74 | 1667.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.93 |
| February | 605.84 | 22-FEB-19:03 | 914.76 | 2136.90 | 1070.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.68 |
| March | 2152.00 | 15-MAR-19:21 | 1524.60 | 4001.68 | 2404.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 |
| April | 2341.55 | 22-APR-17:11 | 748.44 | 2381.00 | 1303.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.77 |
| May | 2468.41 | 21-MAY-19:31 | 1287.00 | 4001.68 | 2404.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.30 |
| June | 2501.31 | 24-JUN-16:21 | 1049.40 | 1320.55 | 1551.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.78 |
| July | 2492.79 | 06-JUL-16:21 | 1069.20 | 1120.47 | 1861.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.58 |
| August | 2522.65 | 01-AUG-16:11 | 1069.20 | 1120.47 | 1861.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.14 |
| September | 2409.39 | 02-SEP-17:31 | 1069.20 | 3401.43 | 1861.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.03 |
| October | 2135.14 | 25-OCT-20:11 | 1762.20 | 3561.50 | 2676.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.78 |
| November | 1797.85 | 27-NOV-09:51 | 396.00 | 1760.74 | 1667.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.77 |
| December | 545.99 | 15-DEC-19:05 | 914.76 | 2136.90 | 1070.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.09 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 545.99 | 396.00 | 1120.47 | 1070.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.14 | |
| Maximum of Months | 2522.65 | 1762.20 | 4001.68 | 2676.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM402_405
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 738.59 | 01-JAN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.41 |
| February | 1097.39 | 10-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.28 |
| March | 1035.42 | 05-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.06 |
| April | 889.43 | 16-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.75 |
| May | 557.61 | 11-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.51 |
| June | 1150.24 | 27-JUN-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.07 | 0.00 |
| July | 1339.03 | 21-JUL-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.10 | 0.00 |
| August | 1081.54 | 09-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.53 | 0.00 |
| September | 482.02 | 16-SEP-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 | 0.00 |
| October | 718.40 | 23-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.89 |
| November | 722.52 | 28-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.97 |
| December | 799.55 | 03-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.34 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 482.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1339.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.10 | 183.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM406_408
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 662.40 | 21-JAN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.02 |
| February | 891.14 | 10-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.89 |
| March | 935.80 | 06-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.96 |
| April | 724.71 | 16-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.53 |
| May | 451.75 | 11-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.80 |
| June | 860.62 | 27-JUN-13:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 0.00 |
| July | 990.87 | 21-JUL-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 0.00 |
| August | 808.73 | 09-AUG-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.16 | 0.00 |
| September | 356.41 | 16-SEP-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.92 | 0.00 |
| October | 582.54 | 23-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.09 |
| November | 592.64 | 28-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.29 |
| December | 671.35 | 31-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.57 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 356.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 990.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 174.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM409_412
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 6123.23 | 14-JAN-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.75 |
| February | 7062.71 | 22-FEB-19:02 | 3659.04 | 8547.59 | 4281.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.45 |
| March | 8114.23 | 28-MAR-18:02 | 3659.04 | 8547.59 | 4281.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.60 |
| April | 9031.49 | 22-APR-17:11 | 2993.76 | 9524.00 | 5212.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.10 |
| May | 9354.34 | 20-MAY-17:41 | 3421.44 | 10884.57 | 5957.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.83 |
| June | 9299.95 | 06-JUN-16:31 | 4276.80 | 4481.88 | 7446.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 |
| July | 9301.80 | 06-JUL-16:21 | 4276.80 | 4481.88 | 7446.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.37 |
| August | 9316.74 | 01-AUG-16:11 | 4276.80 | 4481.88 | 7446.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.26 |
| September | 9225.93 | 02-SEP-17:31 | 4276.80 | 13605.72 | 7446.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.24 |
| October | 8042.02 | 25-OCT-20:11 | 7048.80 | 14245.99 | 10704.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.72 |
| November | 7829.72 | 12-NOV-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.33 |
| December | 7368.75 | 02-DEC-09:01 | 2376.00 | 8963.77 | 9618.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.98 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 6123.23 | 2376.00 | 4481.88 | 4281.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 | |
| Maximum of Months | 9354.34 | 7048.80 | 14245.99 | 10704.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM413
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 147.89 | 01-JAN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.87 |
| February | 156.03 | 28-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.00 |
| March | 181.73 | 26-MAR-14:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.48 |
| April | 169.58 | 16-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.33 |
| May | 98.11 | 11-MAY-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.55 |
| June | 258.02 | 12-JUN-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 | 0.00 |
| July | 326.75 | 21-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 0.00 |
| August | 245.65 | 09-AUG-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 0.00 |
| September | 74.94 | 16-SEP-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | 0.00 |
| October | 139.89 | 23-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.57 |
| November | 140.34 | 28-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.54 |
| December | 132.44 | 17-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.27 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 74.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 326.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.09 | 43.33 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM414
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 345.62 | 30-JAN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.24 |
| February | 344.13 | 08-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47.05 |
| March | 346.18 | 06-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.89 |
| April | 223.86 | 16-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.87 |
| May | 239.44 | 14-MAY-14:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.76 |
| June | 440.82 | 12-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 | 0.00 |
| July | 522.41 | 21-JUL-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.20 | 0.00 |
| August | 559.23 | 09-AUG-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 | 0.00 |
| September | 556.86 | 21-SEP-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.59 |
| October | 313.04 | 11-OCT-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.01 |
| November | 198.79 | 18-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.99 |
| December | 351.85 | 10-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.62 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 198.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 559.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.35 | 67.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM415_418
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 10840.48 | 12-JAN-16:11 | 2993.76 | 3137.10 | 2063.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.22 |
| February | 10452.05 | 28-FEB-16:12 | 2566.08 | 2688.94 | 1768.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.53 |
| March | 10922.48 | 06-MAR-16:11 | 2993.76 | 3137.10 | 2063.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.70 |
| April | 10988.31 | 19-APR-16:21 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.30 |
| May | 11130.04 | 22-MAY-16:21 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.66 |
| June | 11133.28 | 05-JUN-16:21 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.13 |
| July | 10822.12 | 06-JUL-17:01 | 3849.12 | 9651.37 | 6701.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.18 |
| August | 10795.72 | 01-AUG-16:51 | 3421.44 | 3585.25 | 5957.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 |
| September | 10782.84 | 05-SEP-17:02 | 2566.08 | 6434.25 | 4467.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 27.10 |
| October | 10793.06 | 30-OCT-16:11 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.94 |
| November | 9965.86 | 18-NOV-09:01 | 2376.00 | 8963.13 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.52 |
| December | 10461.20 | 11-DEC-16:11 | 2993.76 | 3137.10 | 2063.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.99 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 9965.86 | 2376.00 | 2688.94 | 1768.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.92 | |
| Maximum of Months | 11133.28 | 4276.80 | 9651.37 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 391.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ELEVATORCOREFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.67 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.21 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.27 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.39 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.02 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.47 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.40 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.06 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.85 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM419
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2841.55 | 12-JAN-16:11 | 748.44 | 784.27 | 515.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.41 |
| February | 2715.69 | 28-FEB-16:12 | 641.52 | 672.23 | 442.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.01 |
| March | 2867.32 | 06-MAR-16:11 | 748.44 | 784.27 | 515.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.77 |
| April | 2864.37 | 22-APR-16:21 | 1049.40 | 1320.46 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 |
| May | 2929.96 | 22-MAY-16:21 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.41 |
| June | 2930.71 | 05-JUN-16:21 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.67 |
| July | 2865.23 | 06-JUL-17:01 | 962.28 | 2412.84 | 1675.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.86 |
| August | 2856.84 | 01-AUG-16:51 | 855.36 | 896.31 | 1489.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 |
| September | 2858.48 | 05-SEP-17:02 | 641.52 | 1608.56 | 1116.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 |
| October | 2859.60 | 30-OCT-16:11 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.44 |
| November | 2591.16 | 18-NOV-09:01 | 594.00 | 2240.78 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.48 |
| December | 2643.04 | 04-DEC-16:12 | 641.52 | 672.23 | 442.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.61 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2591.16 | 594.00 | 672.23 | 442.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.12 | |
| Maximum of Months | 2930.71 | 1069.20 | 2412.84 | 2404.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM420_423
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 10720.48 | 12-JAN-16:11 | 2993.76 | 3137.10 | 2063.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.53 |
| February | 10237.53 | 28-FEB-16:12 | 2566.08 | 2688.94 | 1768.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 168.44 |
| March | 10803.34 | 06-MAR-16:11 | 2993.76 | 3137.10 | 2063.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.54 |
| April | 10798.35 | 19-APR-16:21 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.35 |
| May | 10875.17 | 22-MAY-16:21 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.94 |
| June | 10926.77 | 05-JUN-16:21 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.86 |
| July | 10647.11 | 06-JUL-17:01 | 3849.12 | 9651.37 | 6701.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.10 |
| August | 10651.56 | 01-AUG-16:51 | 3421.44 | 3585.25 | 5957.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.22 |
| September | 10644.58 | 10-SEP-16:11 | 4197.60 | 5281.84 | 6205.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.11 |
| October | 10659.31 | 30-OCT-16:11 | 4276.80 | 4481.57 | 7446.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.91 |
| November | 9835.30 | 18-NOV-09:01 | 2376.00 | 8963.13 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.51 |
| December | 10166.83 | 11-DEC-16:11 | 2993.76 | 3137.10 | 2063.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.43 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 9835.30 | 2376.00 | 2688.94 | 1768.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.22 | |
| Maximum of Months | 10926.77 | 4276.80 | 9651.37 | 9618.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GUESTROOM424
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 2395.57 | 15-JAN-16:12 | 356.40 | 792.28 | 488.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.63 |
| February | 2658.19 | 28-FEB-16:12 | 641.52 | 672.23 | 442.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.86 |
| March | 2752.65 | 01-MAR-16:12 | 641.52 | 672.23 | 442.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.25 |
| April | 2867.62 | 19-APR-16:41 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.24 |
| May | 2896.62 | 19-MAY-16:11 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.88 |
| June | 2927.61 | 24-JUN-17:01 | 962.28 | 3061.07 | 1675.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 |
| July | 2912.09 | 06-JUL-17:01 | 962.28 | 2412.84 | 1675.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.63 |
| August | 2907.32 | 01-AUG-16:51 | 855.36 | 896.31 | 1489.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.08 |
| September | 2903.46 | 10-SEP-16:11 | 1049.40 | 1320.46 | 1551.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.96 |
| October | 2934.13 | 30-OCT-16:11 | 1069.20 | 1120.39 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.40 |
| November | 2530.27 | 03-NOV-15:12 | 641.52 | 672.23 | 442.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.93 |
| December | 2276.65 | 16-DEC-16:12 | 356.40 | 792.28 | 488.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.13 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 2276.65 | 356.40 | 672.23 | 442.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.99 | |
| Maximum of Months | 2934.13 | 1069.20 | 3061.07 | 1861.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 72.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONTSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.10 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.18 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.51 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.73 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.69 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 10.46 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.17 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.87 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.81 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.87 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32.90 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.09 | |
| Maximum of Months | 0.00 | 0.00 | 10.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: FRONTSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.07 |
| February | 0.00 | 01-FEB-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.10 |
| March | 0.00 | 01-MAR-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.69 |
| April | 0.00 | 01-APR-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.04 |
| May | 0.00 | 01-MAY-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.68 |
| June | 0.00 | 01-JUN-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.19 |
| July | 0.00 | 01-JUL-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.72 |
| August | 0.00 | 01-AUG-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.85 |
| September | 0.00 | 01-SEP-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.60 |
| October | 0.00 | 01-OCT-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.25 |
| November | 0.00 | 01-NOV-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 184.78 |
| December | 0.00 | 01-DEC-00:10 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.27 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 0.00 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 64.68 | |
| Maximum of Months | 0.00 | 0.00 | 129.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.69 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.117064E+12 | 67615.30 | 17-JAN-07:40 | 0.230756E+12 | 186645.47 | 31-JAN-09:09 |
| February | 0.104710E+12 | 67113.55 | 22-FEB-20:10 | 0.217687E+12 | 217560.30 | 06-FEB-10:09 |
| March | 0.120303E+12 | 79306.51 | 14-MAR-19:19 | 0.172049E+12 | 161681.74 | 07-MAR-09:09 |
| April | 0.119113E+12 | 77320.64 | 08-APR-19:10 | 0.125200E+12 | 140554.89 | 16-APR-09:20 |
| May | 0.132505E+12 | 84879.37 | 20-MAY-19:00 | 0.107626E+12 | 109178.23 | 06-MAY-08:09 |
| June | 0.142447E+12 | 95995.41 | 17-JUN-08:00 | 0.991294E+11 | 103638.49 | 03-JUN-08:09 |
| July | 0.160518E+12 | 96735.42 | 30-JUL-19:40 | 0.997585E+11 | 100627.98 | 01-JUL-08:09 |
| August | 0.155693E+12 | 96662.61 | 26-AUG-08:00 | 0.988775E+11 | 99649.16 | 19-AUG-08:09 |
| September | 0.140064E+12 | 96524.15 | 14-SEP-19:30 | 0.967863E+11 | 104201.39 | 30-SEP-08:09 |
| October | 0.129811E+12 | 84249.30 | 05-OCT-20:19 | 0.111946E+12 | 113802.21 | 30-OCT-08:09 |
| November | 0.118946E+12 | 84624.60 | 04-NOV-19:00 | 0.131293E+12 | 128026.73 | 24-NOV-09:09 |
| December | 0.117606E+12 | 69490.02 | 01-DEC-07:30 | 0.218307E+12 | 188929.16 | 11-DEC-09:09 |
| Annual Sum or Average | 0.155878E+13 | 0.170942E+13 | ||||
| Minimum of Months | 0.104710E+12 | 67113.55 | 0.967863E+11 | 99649.16 | ||
| Maximum of Months | 0.160518E+12 | 96735.42 | 0.230756E+12 | 217560.30 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 0.436785E+11 | 0.112369E+11 | 0.384428E+11 | 0.00 | 0.199800E+11 | 0.431316E+09 | 0.00 | 0.329451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.393689E+11 | 0.937700E+10 | 0.347329E+11 | 0.00 | 0.180668E+11 | 0.413434E+09 | 0.00 | 0.275049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.434136E+11 | 0.931569E+10 | 0.384760E+11 | 0.00 | 0.198030E+11 | 0.211510E+09 | 0.00 | 0.908336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.422096E+11 | 0.793816E+10 | 0.372099E+11 | 0.00 | 0.190963E+11 | 69097707.85 | 0.00 | 0.125901E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.435019E+11 | 0.725553E+10 | 0.384650E+11 | 0.00 | 0.199564E+11 | 26142662.84 | 0.00 | 0.232996E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.420389E+11 | 0.656472E+10 | 0.372320E+11 | 0.00 | 0.196416E+11 | 21351639.97 | 0.00 | 0.369480E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.436756E+11 | 0.696530E+10 | 0.384428E+11 | 0.00 | 0.205764E+11 | 21733134.50 | 0.00 | 0.508359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.434136E+11 | 0.777874E+10 | 0.384760E+11 | 0.00 | 0.204706E+11 | 21735892.20 | 0.00 | 0.455318E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.422154E+11 | 0.855130E+10 | 0.372099E+11 | 0.00 | 0.195646E+11 | 21687255.37 | 0.00 | 0.325013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.435873E+11 | 0.994109E+10 | 0.384539E+11 | 0.00 | 0.198120E+11 | 44889983.86 | 0.00 | 0.179720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.422125E+11 | 0.105788E+11 | 0.372099E+11 | 0.00 | 0.190048E+11 | 95681545.07 | 0.00 | 0.984466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.436785E+11 | 0.114944E+11 | 0.384428E+11 | 0.00 | 0.199160E+11 | 0.389820E+09 | 0.00 | 0.368440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.512994E+12 | 0.106998E+12 | 0.452794E+12 | 0.00 | 0.235889E+12 | 0.176840E+10 | 0.00 | 0.248336E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.393689E+11 | 0.656472E+10 | 0.347329E+11 | 0.00 | 0.180668E+11 | 21351639.97 | 0.00 | 0.275049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.436785E+11 | 0.114944E+11 | 0.384760E+11 | 0.00 | 0.205764E+11 | 0.431316E+09 | 0.00 | 0.508359E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.357977E+11 | 0.00 | 0.119436E+12 | 0.00 | 0.755230E+11 | 0.00 | 0.00 |
| February | 0.323334E+11 | 0.00 | 0.116323E+12 | 0.00 | 0.690298E+11 | 0.00 | 0.00 |
| March | 0.357977E+11 | 0.00 | 0.606810E+11 | 0.00 | 0.755701E+11 | 0.00 | 0.00 |
| April | 0.346430E+11 | 0.00 | 0.197864E+11 | 0.00 | 0.707703E+11 | 0.00 | 0.00 |
| May | 0.357977E+11 | 0.00 | 0.199562E+10 | 0.00 | 0.698327E+11 | 0.00 | 0.00 |
| June | 0.346430E+11 | 0.00 | 0.147072E+09 | 0.00 | 0.643393E+11 | 0.00 | 0.00 |
| July | 0.357977E+11 | 0.00 | 1597002.08 | 0.00 | 0.639592E+11 | 0.00 | 0.00 |
| August | 0.357977E+11 | 0.00 | 2849869.31 | 0.00 | 0.630769E+11 | 0.00 | 0.00 |
| September | 0.346430E+11 | 0.00 | 0.296338E+09 | 0.00 | 0.618470E+11 | 0.00 | 0.00 |
| October | 0.357977E+11 | 0.00 | 0.976764E+10 | 0.00 | 0.663803E+11 | 0.00 | 0.00 |
| November | 0.346430E+11 | 0.00 | 0.291917E+11 | 0.00 | 0.674583E+11 | 0.00 | 0.00 |
| December | 0.357977E+11 | 0.00 | 0.109435E+12 | 0.00 | 0.730747E+11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.421489E+12 | 0.00 | 0.467064E+12 | 0.00 | 0.820862E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.323334E+11 | 0.00 | 1597002.08 | 0.00 | 0.618470E+11 | 0.00 | 0.00 |
| Maximum of Months | 0.357977E+11 | 0.00 | 0.119436E+12 | 0.00 | 0.755701E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 26853.76 | 01-JAN-19:10 | 6812.70 | 01-JAN-00:10 | 34689.82 | 01-JAN-08:09 | 0.00 | 8838.34 | 31-JAN-17:49 | 362.36 | 24-JAN-07:10 | 0.00 | 01-JAN-00:10 |
| February | 26853.76 | 04-FEB-19:10 | 6812.70 | 01-FEB-00:10 | 34689.82 | 04-FEB-08:09 | 0.00 | 8924.30 | 06-FEB-17:49 | 441.37 | 07-FEB-07:10 | 0.00 | 01-FEB-00:10 |
| March | 26853.76 | 04-MAR-19:10 | 6812.70 | 01-MAR-00:10 | 34689.82 | 04-MAR-08:09 | 0.00 | 8731.22 | 06-MAR-17:49 | 338.70 | 07-MAR-07:10 | 0.00 | 01-MAR-00:10 |
| April | 26853.76 | 01-APR-18:10 | 6812.70 | 01-APR-00:10 | 34689.82 | 01-APR-07:10 | 0.00 | 8629.35 | 22-APR-15:20 | 174.26 | 17-APR-02:00 | 0.00 | 01-APR-00:10 |
| May | 26853.76 | 06-MAY-18:10 | 6812.70 | 01-MAY-00:10 | 34689.82 | 06-MAY-07:10 | 0.00 | 8664.03 | 14-MAY-15:20 | 44.02 | 08-MAY-03:00 | 0.00 | 01-MAY-00:10 |
| June | 26853.76 | 03-JUN-18:10 | 6812.70 | 01-JUN-00:10 | 34689.82 | 03-JUN-07:10 | 0.00 | 8794.41 | 27-JUN-12:00 | 22.93 | 14-JUN-03:00 | 0.00 | 01-JUN-00:10 |
| July | 26853.76 | 01-JUL-18:10 | 6812.70 | 01-JUL-00:10 | 34689.82 | 01-JUL-07:10 | 0.00 | 8829.05 | 21-JUL-12:00 | 9.87 | 06-JUL-08:00 | 0.00 | 01-JUL-00:10 |
| August | 26853.76 | 05-AUG-18:10 | 6812.70 | 01-AUG-00:10 | 34689.82 | 05-AUG-07:10 | 0.00 | 8803.05 | 13-AUG-15:20 | 11.54 | 31-AUG-08:09 | 0.00 | 01-AUG-00:10 |
| September | 26853.76 | 02-SEP-18:10 | 6812.70 | 01-SEP-00:10 | 34689.82 | 02-SEP-07:10 | 0.00 | 8733.63 | 21-SEP-15:20 | 25.78 | 30-SEP-03:00 | 0.00 | 01-SEP-00:10 |
| October | 26853.76 | 01-OCT-18:10 | 6812.70 | 01-OCT-00:10 | 34689.82 | 01-OCT-07:10 | 0.00 | 8691.90 | 11-OCT-15:20 | 124.26 | 17-OCT-03:00 | 0.00 | 01-OCT-00:10 |
| November | 26853.76 | 04-NOV-18:10 | 6812.70 | 01-NOV-00:10 | 34689.82 | 04-NOV-07:10 | 0.00 | 8625.53 | 03-NOV-15:20 | 158.12 | 24-NOV-04:10 | 0.00 | 01-NOV-00:10 |
| December | 26853.76 | 02-DEC-19:10 | 6812.70 | 01-DEC-00:10 | 34689.82 | 02-DEC-08:09 | 0.00 | 8838.99 | 28-DEC-17:49 | 394.55 | 11-DEC-07:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | ||||||||||||
| Minimum of Months | 26853.76 | 6812.70 | 34689.82 | 0.00 | 8625.53 | 9.87 | 0.00 | ||||||
| Maximum of Months | 26853.76 | 6812.70 | 34689.82 | 0.00 | 8924.30 | 441.37 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 9636.34 | 15-JAN-16:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 9825.29 | 22-FEB-19:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 27814.38 | 15-MAR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 19364.31 | 30-APR-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 30347.93 | 14-MAY-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 39077.86 | 27-JUN-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 43909.41 | 19-JUL-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 43324.32 | 13-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 38097.28 | 16-SEP-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 26626.94 | 22-OCT-21:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 26314.53 | 05-NOV-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 10240.97 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 9636.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 43909.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 67615.30 | 17-JAN-07:40 | 18944.89 | 30928.09 | 6812.70 | 0.00 | 8231.50 | 30.26 | 0.00 | 2667.87 | 0.00 |
| February | 67113.55 | 22-FEB-20:10 | 26471.15 | 19724.73 | 6812.70 | 0.00 | 8297.70 | 18.63 | 0.00 | 5788.64 | 0.00 |
| March | 79306.51 | 14-MAR-19:19 | 26471.15 | 19724.73 | 6812.70 | 0.00 | 8354.30 | 8.25 | 0.00 | 17935.38 | 0.00 |
| April | 77320.64 | 08-APR-19:10 | 26471.15 | 19724.73 | 6812.70 | 0.00 | 8351.71 | 8.94 | 0.00 | 15951.42 | 0.00 |
| May | 84879.37 | 20-MAY-19:00 | 26471.15 | 19724.73 | 6812.70 | 0.00 | 8353.71 | 9.64 | 0.00 | 23507.44 | 0.00 |
| June | 95995.41 | 17-JUN-08:00 | 22267.63 | 26506.39 | 0.00 | 0.00 | 8545.71 | 8.11 | 0.00 | 38667.57 | 0.00 |
| July | 96735.42 | 30-JUL-19:40 | 26471.15 | 19724.73 | 6812.70 | 0.00 | 8413.63 | 8.11 | 0.00 | 35305.10 | 0.00 |
| August | 96662.61 | 26-AUG-08:00 | 22267.63 | 26506.39 | 0.00 | 0.00 | 8551.99 | 8.11 | 0.00 | 39328.49 | 0.00 |
| September | 96524.15 | 14-SEP-19:30 | 26471.15 | 19724.73 | 6812.70 | 0.00 | 8401.84 | 8.11 | 0.00 | 35105.62 | 0.00 |
| October | 84249.30 | 05-OCT-20:19 | 23686.23 | 19101.32 | 6812.70 | 0.00 | 8355.12 | 8.18 | 0.00 | 26285.74 | 0.00 |
| November | 84624.60 | 04-NOV-19:00 | 26471.15 | 19724.73 | 6812.70 | 0.00 | 8328.28 | 8.57 | 0.00 | 23279.18 | 0.00 |
| December | 69490.02 | 01-DEC-07:30 | 18944.89 | 30928.09 | 6812.70 | 0.00 | 8228.61 | 13.36 | 0.00 | 4562.36 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | |||||||||
| Minimum of Months | 67113.55 | 18944.89 | 19101.32 | 0.00 | 0.00 | 8228.61 | 8.11 | 0.00 | 2667.87 | 0.00 | |
| Maximum of Months | 96735.42 | 26471.15 | 30928.09 | 6812.70 | 0.00 | 8551.99 | 30.26 | 0.00 | 39328.49 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
| January | 40096.03 | 01-JAN-09:09 | 0.00 | 112830.55 | 31-JAN-17:49 | 0.00 | 78593.57 | 28-JAN-08:30 | 0.00 |
| February | 40096.03 | 01-FEB-09:09 | 0.00 | 142651.24 | 07-FEB-07:10 | 0.00 | 78879.56 | 18-FEB-08:30 | 0.00 |
| March | 40096.03 | 01-MAR-09:09 | 0.00 | 97657.25 | 07-MAR-07:10 | 0.00 | 78398.89 | 04-MAR-08:30 | 0.00 |
| April | 40096.03 | 01-APR-08:09 | 0.00 | 51326.47 | 16-APR-06:49 | 0.00 | 76641.92 | 01-APR-07:40 | 0.00 |
| May | 40096.03 | 01-MAY-08:09 | 0.00 | 16194.47 | 08-MAY-03:00 | 0.00 | 73532.04 | 07-MAY-07:00 | 0.00 |
| June | 40096.03 | 01-JUN-08:09 | 0.00 | 6793.33 | 14-JUN-03:00 | 0.00 | 69993.46 | 04-JUN-07:19 | 0.00 |
| July | 40096.03 | 01-JUL-08:09 | 0.00 | 796.03 | 06-JUL-08:00 | 0.00 | 66636.42 | 01-JUL-07:19 | 0.00 |
| August | 40096.03 | 01-AUG-08:09 | 0.00 | 1568.79 | 31-AUG-08:09 | 0.00 | 65645.51 | 05-AUG-07:19 | 0.00 |
| September | 40096.03 | 01-SEP-08:09 | 0.00 | 7958.77 | 30-SEP-03:00 | 0.00 | 66526.24 | 30-SEP-07:40 | 0.00 |
| October | 40096.03 | 01-OCT-08:09 | 0.00 | 39038.23 | 17-OCT-03:00 | 0.00 | 69962.14 | 28-OCT-07:19 | 0.00 |
| November | 40096.03 | 01-NOV-08:09 | 0.00 | 48277.59 | 24-NOV-03:00 | 0.00 | 73483.48 | 26-NOV-08:00 | 0.00 |
| December | 40096.03 | 01-DEC-09:09 | 0.00 | 119709.28 | 11-DEC-07:10 | 0.00 | 77221.70 | 31-DEC-08:20 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 40096.03 | 0.00 | 796.03 | 0.00 | 65645.51 | 0.00 | |||
| Maximum of Months | 40096.03 | 0.00 | 142651.24 | 0.00 | 78879.56 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: REARSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDORFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: REARSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONTLOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: RESTROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MEETINGROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.17 | 19.83 | 0.00 | 19.83 | 0.00 | 19.83 | 0.00 | 19.83 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.17 | 20.17 | 0.17 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
| Annual Sum or Average | 0.33 | 20.00 | 0.17 | 20.06 | 0.00 | 20.06 | 0.00 | 20.06 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.17 | 20.17 | 0.17 | 20.17 | 0.00 | 20.17 | 0.00 | 20.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MECHANICALROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM101
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM102
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM103
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.88 | 0.67 | 21.88 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 6.50 | 21.92 | 6.50 | 21.92 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 22.50 | 23.83 | 22.50 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 22.67 | 36.17 | 22.67 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 30.83 | 22.66 | 30.83 | 22.66 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 17.83 | 22.81 | 17.83 | 22.81 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 22.18 | 2.50 | 22.18 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 21.69 | 0.17 | 21.69 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 118.50 | 22.60 | 118.50 | 22.60 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 36.17 | 22.81 | 36.17 | 22.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM104
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.12 | 1.17 | 22.12 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 21.75 | 1.17 | 21.75 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 10.00 | 21.95 | 10.00 | 21.95 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 22.39 | 23.33 | 22.39 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 22.59 | 29.00 | 22.59 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 26.83 | 22.60 | 26.83 | 22.60 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 22.59 | 23.50 | 22.59 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 22.26 | 5.83 | 22.26 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.98 | 0.67 | 21.98 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 121.50 | 22.47 | 121.50 | 22.47 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 22.60 | 29.00 | 22.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM105
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.31 | 1.33 | 22.31 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.18 | 1.67 | 22.18 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 22.22 | 11.17 | 22.22 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 22.40 | 21.50 | 22.40 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 22.49 | 22.17 | 22.49 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 22.44 | 23.50 | 22.44 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 22.45 | 21.17 | 22.45 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 22.32 | 5.83 | 22.32 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.21 | 1.00 | 22.21 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 109.33 | 22.41 | 109.33 | 22.41 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 23.50 | 22.49 | 23.50 | 22.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: EMPLOYEELOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LAUNDRYROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ELEVATORCOREFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: EXERCISECENTERFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONTOFFICEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONTSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONTSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: REARSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDORFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: REARSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM201
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM202_205
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.56 | 1.17 | 22.56 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.19 | 1.00 | 22.19 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 22.63 | 8.33 | 22.63 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 29.17 | 22.82 | 29.17 | 22.82 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 40.33 | 22.86 | 40.33 | 22.86 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 32.00 | 22.85 | 32.00 | 22.85 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 19.17 | 22.90 | 19.17 | 22.90 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 22.44 | 3.17 | 22.44 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.89 | 0.50 | 21.89 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 134.83 | 22.82 | 134.83 | 22.82 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 40.33 | 22.90 | 40.33 | 22.90 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM206_208
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.65 | 1.17 | 22.65 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.33 | 1.00 | 22.33 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 22.63 | 8.83 | 22.63 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 22.84 | 29.50 | 22.84 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 | 22.86 | 40.50 | 22.86 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 32.17 | 22.85 | 32.17 | 22.85 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 19.50 | 22.93 | 19.50 | 22.93 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 22.46 | 3.50 | 22.46 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.07 | 0.50 | 22.07 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 136.67 | 22.83 | 136.67 | 22.83 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 40.50 | 22.93 | 40.50 | 22.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM209_212
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.71 | 1.17 | 22.71 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.42 | 1.00 | 22.42 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 22.66 | 8.67 | 22.66 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 22.86 | 29.00 | 22.86 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 22.88 | 39.67 | 22.88 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 22.86 | 32.50 | 22.86 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 22.96 | 20.33 | 22.96 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 22.55 | 3.67 | 22.55 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.27 | 0.50 | 22.27 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 136.50 | 22.85 | 136.50 | 22.85 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 39.67 | 22.96 | 39.67 | 22.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM213
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.17 | 1.00 | 22.17 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.80 | 0.50 | 21.80 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 22.24 | 7.00 | 22.24 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 25.67 | 22.62 | 25.67 | 22.62 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 | 22.75 | 37.83 | 22.75 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 28.83 | 22.70 | 28.83 | 22.70 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 16.67 | 22.74 | 16.67 | 22.74 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 22.18 | 2.00 | 22.18 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 119.50 | 22.66 | 119.50 | 22.66 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 37.83 | 22.75 | 37.83 | 22.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM214
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.32 | 1.33 | 22.32 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.00 | 1.67 | 22.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 22.18 | 11.17 | 22.18 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 22.83 | 22.42 | 22.83 | 22.42 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 22.51 | 25.00 | 22.51 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 22.51 | 23.83 | 22.51 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 22.47 | 21.50 | 22.47 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 22.24 | 5.67 | 22.24 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 21.91 | 1.00 | 21.91 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 114.00 | 22.42 | 114.00 | 22.42 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 22.51 | 25.00 | 22.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM215_218
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ELEVATORCOREFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM219
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 30.57 | 0.17 | 30.57 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 28.59 | 0.17 | 28.59 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 30.58 | 0.50 | 30.58 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 30.59 | 0.50 | 30.59 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 30.60 | 0.33 | 30.60 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 30.58 | 0.50 | 30.58 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 2.17 | 30.43 | 2.17 | 30.43 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 30.60 | 0.50 | 30.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM220_223
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.49 | 1.33 | 22.49 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.24 | 1.67 | 22.24 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 22.35 | 11.17 | 22.35 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 | 22.57 | 23.17 | 22.57 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 22.65 | 25.83 | 22.65 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 22.64 | 24.00 | 22.64 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 22.64 | 21.33 | 22.64 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 22.42 | 5.83 | 22.42 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.15 | 1.00 | 22.15 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 115.33 | 22.58 | 115.33 | 22.58 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 22.65 | 25.83 | 22.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM224
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.23 | 1.33 | 22.23 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.91 | 1.50 | 21.91 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 22.11 | 11.00 | 22.11 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 22.39 | 22.67 | 22.39 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 22.50 | 24.67 | 22.50 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 | 22.50 | 23.67 | 22.50 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 22.46 | 21.33 | 22.46 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 22.19 | 5.67 | 22.19 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.89 | 0.67 | 21.89 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 112.50 | 22.40 | 112.50 | 22.40 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 22.50 | 24.67 | 22.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONTSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONTSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: REARSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 3.33 | 6.41 | 0.00 | 6.41 | 0.00 | 6.41 | 0.00 | 6.41 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3.33 | 6.41 | 0.00 | 6.41 | 0.00 | 6.41 | 0.00 | 6.41 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3.33 | 6.41 | 0.00 | 6.41 | 0.00 | 6.41 | 0.00 | 6.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDORFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: REARSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM301
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM302_305
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM306_308
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM309_312
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.76 | 1.17 | 22.76 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.47 | 1.00 | 22.47 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 8.67 | 22.69 | 8.67 | 22.69 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 22.87 | 29.50 | 22.87 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 | 22.88 | 41.00 | 22.88 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 32.50 | 22.85 | 32.50 | 22.85 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 22.96 | 20.17 | 22.96 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 22.53 | 3.33 | 22.53 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.02 | 0.50 | 22.02 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 137.83 | 22.85 | 137.83 | 22.85 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 41.00 | 22.96 | 41.00 | 22.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM313
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM314
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.35 | 1.33 | 22.35 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.95 | 1.50 | 21.95 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 22.19 | 10.83 | 22.19 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 24.00 | 22.49 | 24.00 | 22.49 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 22.55 | 29.33 | 22.55 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 26.17 | 22.56 | 26.17 | 22.56 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 22.52 | 22.33 | 22.52 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 22.20 | 5.17 | 22.20 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 121.17 | 22.47 | 121.17 | 22.47 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 29.33 | 22.56 | 29.33 | 22.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM315_318
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.53 | 1.33 | 22.53 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.32 | 1.67 | 22.32 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 22.40 | 11.17 | 22.40 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 23.33 | 22.57 | 23.33 | 22.57 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 22.64 | 26.00 | 22.64 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 24.17 | 22.65 | 24.17 | 22.65 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 22.64 | 21.50 | 22.64 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 22.44 | 5.83 | 22.44 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.26 | 1.00 | 22.26 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 116.00 | 22.59 | 116.00 | 22.59 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 26.00 | 22.65 | 26.00 | 22.65 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ELEVATORCOREFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM319
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM320_323
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.53 | 1.33 | 22.53 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.21 | 1.67 | 22.21 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 22.35 | 11.17 | 22.35 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 23.83 | 22.59 | 23.83 | 22.59 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 22.65 | 27.83 | 22.65 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 25.00 | 22.67 | 25.00 | 22.67 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 22.65 | 22.00 | 22.65 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 22.38 | 5.83 | 22.38 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 22.14 | 0.67 | 22.14 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 119.33 | 22.59 | 119.33 | 22.59 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 27.83 | 22.67 | 27.83 | 22.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM324
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONTSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONTSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.33 | 6.60 | 0.00 | 6.60 | 0.00 | 6.60 | 0.00 | 6.60 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.33 | 6.60 | 0.00 | 6.60 | 0.00 | 6.60 | 0.00 | 6.60 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.33 | 6.60 | 0.00 | 6.60 | 0.00 | 6.60 | 0.00 | 6.60 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: REARSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.17 | 6.63 | 0.00 | 6.63 | 0.00 | 6.63 | 0.00 | 6.63 |
| February | 26.00 | 6.08 | 0.00 | 6.08 | 0.00 | 6.08 | 0.00 | 6.08 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 26.17 | 6.09 | 0.00 | 6.09 | 0.00 | 6.09 | 0.00 | 6.09 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 26.00 | 6.63 | 0.00 | 6.63 | 0.00 | 6.63 | 0.00 | 6.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORRIDORFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: REARSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM401
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.17 | 20.51 | 0.17 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 22.30 | 0.83 | 22.30 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.77 | 0.50 | 21.77 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 22.19 | 6.83 | 22.19 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 | 22.47 | 22.67 | 22.47 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 22.57 | 28.67 | 22.57 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 22.50 | 22.00 | 22.50 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 13.17 | 22.45 | 13.17 | 22.45 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 21.99 | 1.50 | 21.99 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.17 | 20.51 | 0.17 | 20.51 | 96.17 | 22.46 | 96.17 | 22.47 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.17 | 20.51 | 0.17 | 20.51 | 28.67 | 22.57 | 28.67 | 22.57 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM402_405
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM406_408
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM409_412
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.31 | 1.17 | 22.31 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 22.22 | 1.00 | 22.22 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 22.40 | 7.83 | 22.40 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 22.67 | 20.17 | 22.67 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 22.71 | 25.83 | 22.71 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 22.65 | 21.33 | 22.65 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 14.00 | 22.64 | 14.00 | 22.64 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 22.30 | 3.00 | 22.30 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 22.04 | 0.50 | 22.04 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 94.83 | 22.63 | 94.83 | 22.63 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 25.83 | 22.71 | 25.83 | 22.71 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM413
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM414
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM415_418
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.26 | 1.33 | 22.26 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.13 | 1.67 | 22.13 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 22.20 | 11.17 | 22.20 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 22.40 | 21.83 | 22.40 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 22.56 | 21.50 | 22.56 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 22.47 | 22.00 | 22.47 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 22.40 | 20.33 | 22.40 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 22.19 | 5.67 | 22.19 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 22.09 | 0.83 | 22.09 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 106.33 | 22.41 | 106.33 | 22.41 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 22.56 | 22.00 | 22.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ELEVATORCOREFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM419
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.17 | 1.33 | 22.17 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.04 | 1.67 | 22.04 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 11.17 | 22.12 | 11.17 | 22.12 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 22.33 | 21.83 | 22.33 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 22.45 | 22.17 | 22.45 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 22.38 | 22.33 | 22.38 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 22.33 | 20.33 | 22.33 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 22.09 | 5.67 | 22.09 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 21.98 | 0.67 | 21.98 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 107.17 | 22.32 | 107.17 | 22.32 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.33 | 22.45 | 22.33 | 22.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM420_423
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 22.23 | 1.33 | 22.23 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 22.09 | 1.67 | 22.09 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 11.00 | 22.18 | 11.00 | 22.18 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 21.50 | 22.38 | 21.50 | 22.38 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 21.17 | 22.53 | 21.17 | 22.53 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 22.44 | 22.00 | 22.44 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 20.33 | 22.38 | 20.33 | 22.38 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 22.15 | 5.67 | 22.15 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 22.11 | 0.67 | 22.11 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 105.33 | 22.38 | 105.33 | 22.38 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 22.00 | 22.53 | 22.00 | 22.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GUESTROOM424
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 22.14 | 1.17 | 22.14 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 21.89 | 1.67 | 21.89 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 10.50 | 22.05 | 10.50 | 22.05 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 22.27 | 21.33 | 22.27 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 21.33 | 22.41 | 21.33 | 22.41 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 22.33 | 21.83 | 22.33 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 22.26 | 20.17 | 22.26 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 22.02 | 5.17 | 22.02 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 21.80 | 0.50 | 21.80 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 103.67 | 22.27 | 103.67 | 22.27 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.83 | 22.41 | 21.83 | 22.41 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONTSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: FRONTSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: REARSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORRIDORFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 679.50 | 23.23 | 0.00 | 23.23 | 0.00 | 23.23 |
| February | 636.33 | 23.11 | 0.00 | 23.11 | 0.00 | 23.11 |
| March | 438.00 | 23.34 | 103.67 | 23.45 | 0.00 | 23.45 |
| April | 155.00 | 23.10 | 116.33 | 23.44 | 0.00 | 23.44 |
| May | 24.67 | 22.14 | 460.33 | 23.80 | 0.00 | 23.80 |
| June | 7.00 | 22.43 | 671.00 | 23.87 | 1.67 | 23.87 |
| July | 7.33 | 23.89 | 744.00 | 23.89 | 7.33 | 23.89 |
| August | 1.67 | 23.89 | 742.83 | 23.88 | 1.67 | 23.88 |
| September | 6.00 | 21.67 | 696.00 | 23.86 | 0.00 | 23.86 |
| October | 40.50 | 21.90 | 391.67 | 23.70 | 0.00 | 23.70 |
| November | 156.00 | 23.00 | 110.83 | 23.37 | 0.00 | 23.37 |
| December | 612.00 | 23.22 | 7.33 | 23.23 | 0.00 | 23.23 |
| Annual Sum or Average | 2764.00 | 23.17 | 4044.00 | 23.59 | 10.67 | 23.59 |
| Minimum of Months | 1.67 | 21.67 | 0.00 | 23.11 | 0.00 | 23.11 |
| Maximum of Months | 679.50 | 23.89 | 744.00 | 23.89 | 7.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: REARSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FRONTLOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.12 | 452.33 | 21.12 | 452.33 | 21.12 |
| February | 672.00 | 21.12 | 418.50 | 21.12 | 418.50 | 21.11 |
| March | 708.67 | 21.28 | 241.00 | 21.25 | 238.50 | 21.22 |
| April | 712.67 | 21.60 | 12.33 | 21.59 | 12.33 | 21.58 |
| May | 527.67 | 22.42 | 41.17 | 22.52 | 0.00 | 22.52 |
| June | 181.50 | 22.98 | 423.17 | 23.61 | 59.00 | 23.63 |
| July | 136.17 | 23.82 | 704.83 | 23.87 | 127.17 | 23.87 |
| August | 82.67 | 23.59 | 650.50 | 23.85 | 59.17 | 23.85 |
| September | 174.17 | 22.52 | 361.50 | 23.43 | 15.33 | 23.45 |
| October | 596.17 | 21.83 | 35.17 | 21.94 | 0.00 | 21.94 |
| November | 703.00 | 21.46 | 0.00 | 21.46 | 0.00 | 21.46 |
| December | 744.00 | 21.14 | 259.50 | 21.13 | 259.50 | 21.13 |
| Annual Sum or Average | 5982.67 | 21.62 | 3600.00 | 22.07 | 1641.83 | 21.99 |
| Minimum of Months | 82.67 | 21.12 | 0.00 | 21.12 | 0.00 | 21.11 |
| Maximum of Months | 744.00 | 23.82 | 704.83 | 23.87 | 452.33 | 23.87 |
Report: ComfortReportSimple55Monthly
For: RESTROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 23.22 | 84.33 | 23.25 | 84.33 | 23.28 |
| February | 672.00 | 22.96 | 0.00 | 22.96 | 0.00 | 22.96 |
| March | 608.83 | 23.47 | 49.67 | 23.50 | 49.67 | 23.51 |
| April | 497.83 | 23.87 | 0.00 | 23.87 | 0.00 | 23.87 |
| May | 126.67 | 23.89 | 0.00 | 23.89 | 0.00 | 23.89 |
| June | 0.50 | 23.89 | 127.67 | 23.89 | 0.00 | 23.89 |
| July | 0.00 | 0.00 | 350.00 | 23.89 | 0.00 | 23.89 |
| August | 0.00 | 0.00 | 277.50 | 23.89 | 0.00 | 23.89 |
| September | 1.17 | 23.89 | 91.17 | 23.89 | 0.00 | 23.89 |
| October | 144.83 | 23.89 | 0.00 | 23.89 | 0.00 | 23.89 |
| November | 474.33 | 23.89 | 0.00 | 23.89 | 0.00 | 23.89 |
| December | 705.67 | 23.42 | 0.00 | 23.42 | 0.00 | 23.42 |
| Annual Sum or Average | 3975.83 | 23.46 | 980.33 | 23.54 | 134.00 | 23.54 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 22.96 | 0.00 | 22.96 |
| Maximum of Months | 744.00 | 23.89 | 350.00 | 23.89 | 84.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: MEETINGROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 175.00 | 21.12 | 98.67 | 21.12 | 98.67 | 21.12 |
| February | 159.00 | 21.11 | 82.33 | 21.11 | 82.33 | 21.11 |
| March | 168.00 | 21.36 | 47.83 | 21.32 | 46.67 | 21.28 |
| April | 169.00 | 21.83 | 1.17 | 21.83 | 1.17 | 21.83 |
| May | 112.00 | 23.14 | 15.67 | 23.23 | 1.00 | 23.24 |
| June | 40.50 | 23.73 | 84.50 | 23.84 | 15.33 | 23.84 |
| July | 26.17 | 23.89 | 134.17 | 23.89 | 25.83 | 23.89 |
| August | 14.67 | 23.89 | 125.83 | 23.89 | 10.17 | 23.89 |
| September | 39.50 | 23.61 | 74.33 | 23.79 | 3.33 | 23.79 |
| October | 138.67 | 22.34 | 9.83 | 22.44 | 0.00 | 22.44 |
| November | 165.33 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
| December | 175.00 | 21.17 | 53.67 | 21.16 | 53.67 | 21.15 |
| Annual Sum or Average | 1382.83 | 21.83 | 728.00 | 22.17 | 338.17 | 22.09 |
| Minimum of Months | 14.67 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
| Maximum of Months | 175.00 | 23.89 | 134.17 | 23.89 | 98.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: MECHANICALROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM101
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM102
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM103
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.60 | 637.33 | 20.56 | 637.33 | 20.55 |
| February | 672.00 | 20.54 | 639.83 | 20.52 | 639.83 | 20.52 |
| March | 743.83 | 20.87 | 440.33 | 20.78 | 440.33 | 20.73 |
| April | 720.00 | 21.19 | 71.00 | 21.14 | 71.00 | 21.10 |
| May | 739.00 | 21.87 | 19.50 | 21.91 | 19.33 | 21.94 |
| June | 608.17 | 22.15 | 102.33 | 22.51 | 48.33 | 22.62 |
| July | 552.50 | 22.10 | 149.67 | 22.69 | 70.33 | 22.88 |
| August | 549.67 | 22.06 | 148.67 | 22.68 | 52.67 | 22.84 |
| September | 589.67 | 22.11 | 122.67 | 22.58 | 47.00 | 22.71 |
| October | 724.33 | 21.67 | 15.50 | 21.72 | 5.67 | 21.74 |
| November | 720.00 | 21.29 | 8.33 | 21.30 | 8.33 | 21.31 |
| December | 744.00 | 20.69 | 484.50 | 20.62 | 484.50 | 20.59 |
| Annual Sum or Average | 8107.17 | 21.38 | 2839.67 | 21.38 | 2524.67 | 21.29 |
| Minimum of Months | 549.67 | 20.54 | 8.33 | 20.52 | 5.67 | 20.52 |
| Maximum of Months | 744.00 | 22.15 | 639.83 | 22.69 | 639.83 | 22.88 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM104
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.04 | 244.00 | 20.98 | 244.00 | 20.95 |
| February | 672.00 | 20.95 | 289.50 | 20.89 | 289.50 | 20.85 |
| March | 738.00 | 21.38 | 51.50 | 21.37 | 49.00 | 21.36 |
| April | 716.00 | 21.59 | 3.33 | 21.59 | 3.33 | 21.59 |
| May | 694.67 | 21.91 | 11.17 | 21.96 | 1.00 | 21.96 |
| June | 540.17 | 21.93 | 111.83 | 22.44 | 25.50 | 22.53 |
| July | 480.00 | 21.83 | 144.67 | 22.57 | 50.83 | 22.75 |
| August | 459.50 | 21.71 | 154.00 | 22.55 | 33.50 | 22.68 |
| September | 474.50 | 21.72 | 143.33 | 22.50 | 18.00 | 22.58 |
| October | 688.00 | 21.76 | 28.83 | 21.89 | 0.00 | 21.89 |
| November | 711.67 | 21.62 | 2.67 | 21.64 | 0.00 | 21.64 |
| December | 744.00 | 21.10 | 177.33 | 21.03 | 177.33 | 20.99 |
| Annual Sum or Average | 7662.50 | 21.51 | 1362.17 | 21.68 | 892.00 | 21.66 |
| Minimum of Months | 459.50 | 20.95 | 2.67 | 20.89 | 0.00 | 20.85 |
| Maximum of Months | 744.00 | 21.93 | 289.50 | 22.57 | 289.50 | 22.75 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM105
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 740.33 | 21.73 | 0.00 | 21.73 | 0.00 | 21.73 |
| February | 672.00 | 21.71 | 0.00 | 21.71 | 0.00 | 21.71 |
| March | 708.50 | 21.74 | 10.33 | 21.79 | 0.00 | 21.79 |
| April | 646.83 | 21.67 | 15.67 | 21.76 | 0.00 | 21.76 |
| May | 521.83 | 21.52 | 94.33 | 22.09 | 0.00 | 22.09 |
| June | 381.83 | 21.36 | 202.67 | 22.62 | 6.67 | 22.66 |
| July | 389.00 | 21.42 | 286.33 | 22.73 | 20.33 | 22.82 |
| August | 378.17 | 21.29 | 280.00 | 22.70 | 8.67 | 22.75 |
| September | 382.50 | 21.32 | 238.67 | 22.64 | 4.17 | 22.66 |
| October | 567.33 | 21.50 | 61.17 | 21.83 | 0.17 | 21.83 |
| November | 640.67 | 21.66 | 15.67 | 21.75 | 0.00 | 21.75 |
| December | 735.33 | 21.72 | 0.00 | 21.72 | 0.00 | 21.72 |
| Annual Sum or Average | 6764.33 | 21.59 | 1204.83 | 22.07 | 40.00 | 22.09 |
| Minimum of Months | 378.17 | 21.29 | 0.00 | 21.71 | 0.00 | 21.71 |
| Maximum of Months | 740.33 | 21.74 | 286.33 | 22.73 | 20.33 | 22.82 |
Report: ComfortReportSimple55Monthly
For: EMPLOYEELOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 69.33 | 21.96 | 337.83 | 23.56 | 0.00 | 23.56 |
| February | 74.83 | 21.80 | 299.83 | 23.47 | 0.00 | 23.47 |
| March | 63.67 | 23.09 | 393.50 | 23.78 | 35.67 | 23.79 |
| April | 81.50 | 23.89 | 437.17 | 23.89 | 81.33 | 23.89 |
| May | 145.67 | 23.89 | 464.83 | 23.89 | 145.67 | 23.89 |
| June | 216.67 | 23.89 | 450.00 | 23.89 | 216.67 | 23.89 |
| July | 283.50 | 23.89 | 465.00 | 23.89 | 283.50 | 23.89 |
| August | 278.17 | 23.89 | 465.00 | 23.89 | 278.17 | 23.89 |
| September | 246.17 | 23.89 | 450.00 | 23.89 | 246.17 | 23.89 |
| October | 161.33 | 23.89 | 465.00 | 23.89 | 161.33 | 23.89 |
| November | 64.83 | 23.89 | 428.83 | 23.89 | 64.83 | 23.89 |
| December | 44.00 | 21.81 | 368.50 | 23.66 | 0.00 | 23.66 |
| Annual Sum or Average | 1729.67 | 23.64 | 5025.50 | 23.82 | 1513.33 | 23.84 |
| Minimum of Months | 44.00 | 21.80 | 299.83 | 23.47 | 0.00 | 23.47 |
| Maximum of Months | 283.50 | 23.89 | 465.00 | 23.89 | 283.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: LAUNDRYROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 248.00 | 79.85 | 248.00 | 79.85 | 248.00 | 79.85 |
| February | 224.00 | 79.53 | 224.00 | 79.53 | 224.00 | 79.53 |
| March | 248.00 | 80.85 | 248.00 | 80.85 | 248.00 | 80.85 |
| April | 240.00 | 81.26 | 240.00 | 81.26 | 240.00 | 81.26 |
| May | 248.00 | 81.96 | 248.00 | 81.96 | 248.00 | 81.96 |
| June | 240.00 | 82.77 | 240.00 | 82.77 | 240.00 | 82.77 |
| July | 248.00 | 83.42 | 248.00 | 83.42 | 248.00 | 83.42 |
| August | 248.00 | 83.61 | 248.00 | 83.61 | 248.00 | 83.61 |
| September | 240.00 | 83.42 | 240.00 | 83.42 | 240.00 | 83.42 |
| October | 248.00 | 82.38 | 248.00 | 82.38 | 248.00 | 82.38 |
| November | 240.00 | 81.43 | 240.00 | 81.43 | 240.00 | 81.43 |
| December | 248.00 | 79.93 | 248.00 | 79.93 | 248.00 | 79.93 |
| Annual Sum or Average | 2920.00 | 81.71 | 2920.00 | 81.71 | 2920.00 | 81.71 |
| Minimum of Months | 224.00 | 79.53 | 224.00 | 79.53 | 224.00 | 79.53 |
| Maximum of Months | 248.00 | 83.61 | 248.00 | 83.61 | 248.00 | 83.61 |
Report: ComfortReportSimple55Monthly
For: ELEVATORCOREFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: EXERCISECENTERFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 496.00 | 21.31 | 13.33 | 21.31 | 13.33 | 21.30 |
| February | 448.00 | 21.27 | 16.33 | 21.27 | 16.33 | 21.26 |
| March | 418.33 | 21.89 | 49.33 | 22.09 | 2.83 | 22.08 |
| April | 292.33 | 22.48 | 30.17 | 22.62 | 0.00 | 22.62 |
| May | 88.83 | 23.14 | 189.00 | 23.65 | 0.00 | 23.65 |
| June | 25.67 | 23.32 | 390.17 | 23.85 | 8.83 | 23.85 |
| July | 24.83 | 23.84 | 487.33 | 23.89 | 23.17 | 23.89 |
| August | 9.83 | 23.72 | 481.67 | 23.88 | 7.50 | 23.88 |
| September | 16.50 | 22.97 | 426.17 | 23.85 | 1.00 | 23.85 |
| October | 137.67 | 22.76 | 195.33 | 23.42 | 0.00 | 23.42 |
| November | 334.00 | 22.47 | 48.33 | 22.65 | 0.00 | 22.65 |
| December | 493.83 | 21.41 | 7.17 | 21.41 | 7.17 | 21.40 |
| Annual Sum or Average | 2785.83 | 21.86 | 2334.33 | 22.76 | 80.17 | 22.76 |
| Minimum of Months | 9.83 | 21.27 | 7.17 | 21.27 | 0.00 | 21.26 |
| Maximum of Months | 496.00 | 23.84 | 487.33 | 23.89 | 23.17 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONTOFFICEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 682.00 | 21.36 | 202.33 | 21.30 | 202.33 | 21.27 |
| February | 616.00 | 21.32 | 228.67 | 21.26 | 228.67 | 21.23 |
| March | 612.50 | 22.04 | 50.83 | 22.04 | 33.83 | 22.00 |
| April | 562.33 | 22.74 | 1.17 | 22.73 | 1.17 | 22.73 |
| May | 284.83 | 23.49 | 57.50 | 23.56 | 0.00 | 23.56 |
| June | 42.00 | 23.71 | 387.00 | 23.87 | 0.00 | 23.87 |
| July | 0.00 | 0.00 | 633.17 | 23.89 | 0.00 | 23.89 |
| August | 0.00 | 0.00 | 587.50 | 23.89 | 0.00 | 23.89 |
| September | 9.83 | 23.60 | 429.83 | 23.88 | 0.00 | 23.88 |
| October | 283.67 | 23.28 | 112.67 | 23.45 | 0.00 | 23.45 |
| November | 539.50 | 22.84 | 7.50 | 22.86 | 0.00 | 22.86 |
| December | 682.00 | 21.46 | 123.00 | 21.41 | 123.00 | 21.37 |
| Annual Sum or Average | 4314.67 | 22.13 | 2821.17 | 22.59 | 589.00 | 22.48 |
| Minimum of Months | 0.00 | 0.00 | 1.17 | 21.26 | 0.00 | 21.23 |
| Maximum of Months | 682.00 | 23.71 | 633.17 | 23.89 | 228.67 | 23.89 |
Report: ComfortReportSimple55Monthly
For: FRONTSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FRONTSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: REARSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORRIDORFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.32 | 99.33 | 21.30 | 99.33 | 21.28 |
| February | 672.00 | 21.25 | 107.33 | 21.23 | 107.33 | 21.22 |
| March | 649.33 | 22.05 | 11.00 | 22.05 | 6.83 | 22.04 |
| April | 645.67 | 23.16 | 0.00 | 23.16 | 0.00 | 23.16 |
| May | 243.83 | 23.82 | 63.83 | 23.83 | 0.00 | 23.83 |
| June | 24.50 | 23.88 | 385.33 | 23.89 | 0.00 | 23.89 |
| July | 0.00 | 0.00 | 667.67 | 23.89 | 0.00 | 23.89 |
| August | 0.00 | 0.00 | 573.00 | 23.89 | 0.00 | 23.89 |
| September | 18.50 | 23.75 | 297.83 | 23.88 | 0.00 | 23.88 |
| October | 446.67 | 23.44 | 16.67 | 23.45 | 0.00 | 23.45 |
| November | 668.67 | 22.79 | 0.00 | 22.79 | 0.00 | 22.79 |
| December | 744.00 | 21.44 | 82.83 | 21.41 | 82.83 | 21.38 |
| Annual Sum or Average | 4857.17 | 22.22 | 2304.83 | 22.64 | 296.33 | 22.58 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 21.23 | 0.00 | 21.22 |
| Maximum of Months | 744.00 | 23.88 | 667.67 | 23.89 | 107.33 | 23.89 |
Report: ComfortReportSimple55Monthly
For: REARSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM201
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM202_205
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.78 | 508.50 | 20.72 | 508.50 | 20.70 |
| February | 672.00 | 20.77 | 466.67 | 20.72 | 466.67 | 20.70 |
| March | 731.83 | 21.15 | 247.00 | 21.09 | 238.83 | 21.02 |
| April | 708.17 | 21.55 | 14.00 | 21.58 | 7.00 | 21.57 |
| May | 621.83 | 21.83 | 86.33 | 22.25 | 4.50 | 22.27 |
| June | 442.17 | 21.86 | 221.83 | 22.92 | 42.83 | 23.07 |
| July | 430.17 | 21.92 | 297.00 | 23.04 | 69.83 | 23.26 |
| August | 430.00 | 21.82 | 245.17 | 22.96 | 56.17 | 23.16 |
| September | 523.00 | 22.04 | 178.00 | 22.84 | 50.00 | 23.01 |
| October | 715.83 | 21.72 | 32.50 | 21.87 | 12.00 | 21.91 |
| November | 719.50 | 21.38 | 19.00 | 21.39 | 18.83 | 21.41 |
| December | 744.00 | 20.83 | 362.00 | 20.74 | 362.00 | 20.70 |
| Annual Sum or Average | 7482.50 | 21.41 | 2678.00 | 21.66 | 1837.17 | 21.61 |
| Minimum of Months | 430.00 | 20.77 | 14.00 | 20.72 | 4.50 | 20.70 |
| Maximum of Months | 744.00 | 22.04 | 508.50 | 23.04 | 508.50 | 23.26 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM206_208
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.91 | 374.00 | 20.84 | 374.00 | 20.80 |
| February | 672.00 | 20.90 | 329.83 | 20.82 | 329.83 | 20.78 |
| March | 730.67 | 21.27 | 141.17 | 21.24 | 130.83 | 21.17 |
| April | 706.67 | 21.63 | 9.00 | 21.68 | 0.00 | 21.68 |
| May | 619.33 | 21.83 | 88.00 | 22.26 | 3.67 | 22.28 |
| June | 447.83 | 21.85 | 204.67 | 22.88 | 36.83 | 23.03 |
| July | 429.17 | 21.88 | 254.67 | 22.98 | 64.33 | 23.21 |
| August | 432.00 | 21.80 | 218.00 | 22.92 | 52.17 | 23.11 |
| September | 522.17 | 22.02 | 170.00 | 22.81 | 43.33 | 22.97 |
| October | 707.17 | 21.76 | 31.83 | 21.91 | 4.67 | 21.93 |
| November | 716.33 | 21.49 | 6.00 | 21.51 | 5.17 | 21.53 |
| December | 744.00 | 20.96 | 261.17 | 20.88 | 261.17 | 20.83 |
| Annual Sum or Average | 7471.33 | 21.47 | 2088.33 | 21.76 | 1306.00 | 21.72 |
| Minimum of Months | 429.17 | 20.90 | 6.00 | 20.82 | 0.00 | 20.78 |
| Maximum of Months | 744.00 | 22.02 | 374.00 | 22.98 | 374.00 | 23.21 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM209_212
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.96 | 303.83 | 20.87 | 303.83 | 20.82 |
| February | 672.00 | 20.94 | 266.17 | 20.86 | 266.17 | 20.81 |
| March | 731.00 | 21.30 | 110.83 | 21.28 | 101.00 | 21.22 |
| April | 706.17 | 21.65 | 9.33 | 21.69 | 0.00 | 21.69 |
| May | 625.67 | 21.84 | 86.83 | 22.26 | 4.67 | 22.28 |
| June | 468.67 | 21.94 | 196.33 | 22.88 | 46.83 | 23.05 |
| July | 451.33 | 21.98 | 238.67 | 22.98 | 78.50 | 23.23 |
| August | 445.50 | 21.89 | 213.33 | 22.92 | 62.67 | 23.15 |
| September | 529.33 | 22.06 | 171.83 | 22.84 | 51.33 | 23.02 |
| October | 707.33 | 21.80 | 35.00 | 21.96 | 9.50 | 22.00 |
| November | 714.17 | 21.55 | 6.33 | 21.58 | 4.83 | 21.60 |
| December | 744.00 | 21.02 | 215.00 | 20.93 | 215.00 | 20.87 |
| Annual Sum or Average | 7539.17 | 21.52 | 1853.50 | 21.81 | 1144.33 | 21.80 |
| Minimum of Months | 445.50 | 20.94 | 6.33 | 20.86 | 0.00 | 20.81 |
| Maximum of Months | 744.00 | 22.06 | 303.83 | 22.98 | 303.83 | 23.23 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM213
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.54 | 661.00 | 20.51 | 661.00 | 20.50 |
| February | 672.00 | 20.51 | 636.83 | 20.50 | 636.83 | 20.49 |
| March | 739.17 | 20.90 | 407.50 | 20.81 | 404.33 | 20.75 |
| April | 717.50 | 21.31 | 57.00 | 21.27 | 57.00 | 21.23 |
| May | 677.67 | 21.87 | 46.00 | 22.06 | 7.67 | 22.08 |
| June | 521.83 | 22.04 | 151.83 | 22.74 | 48.33 | 22.90 |
| July | 480.17 | 22.02 | 178.83 | 22.88 | 76.67 | 23.13 |
| August | 500.33 | 22.01 | 175.33 | 22.84 | 63.67 | 23.05 |
| September | 580.67 | 22.11 | 136.50 | 22.67 | 51.33 | 22.83 |
| October | 727.83 | 21.57 | 28.83 | 21.66 | 18.50 | 21.70 |
| November | 720.00 | 21.12 | 93.83 | 21.09 | 93.83 | 21.06 |
| December | 744.00 | 20.58 | 590.83 | 20.53 | 590.83 | 20.51 |
| Annual Sum or Average | 7825.17 | 21.31 | 3164.33 | 21.38 | 2710.00 | 21.30 |
| Minimum of Months | 480.17 | 20.51 | 28.83 | 20.50 | 7.67 | 20.49 |
| Maximum of Months | 744.00 | 22.11 | 661.00 | 22.88 | 661.00 | 23.13 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM214
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.20 | 154.67 | 21.15 | 154.67 | 21.11 |
| February | 672.00 | 21.14 | 175.83 | 21.08 | 175.83 | 21.03 |
| March | 721.67 | 21.59 | 25.00 | 21.63 | 15.33 | 21.62 |
| April | 691.50 | 21.70 | 12.17 | 21.76 | 0.00 | 21.76 |
| May | 586.17 | 21.71 | 80.00 | 22.14 | 1.17 | 22.15 |
| June | 423.33 | 21.63 | 192.17 | 22.69 | 21.33 | 22.79 |
| July | 420.00 | 21.69 | 266.33 | 22.83 | 46.17 | 23.00 |
| August | 412.50 | 21.58 | 255.33 | 22.78 | 30.83 | 22.90 |
| September | 429.67 | 21.59 | 192.83 | 22.64 | 16.00 | 22.72 |
| October | 653.50 | 21.71 | 40.00 | 21.91 | 0.00 | 21.91 |
| November | 703.00 | 21.66 | 8.50 | 21.70 | 0.00 | 21.70 |
| December | 744.00 | 21.19 | 137.50 | 21.13 | 137.50 | 21.08 |
| Annual Sum or Average | 7201.33 | 21.51 | 1540.33 | 21.88 | 598.83 | 21.87 |
| Minimum of Months | 412.50 | 21.14 | 8.50 | 21.08 | 0.00 | 21.03 |
| Maximum of Months | 744.00 | 21.71 | 266.33 | 22.83 | 175.83 | 23.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM215_218
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: ELEVATORCOREFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM219
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 345.50 | 21.12 | 224.17 | 21.93 | 0.00 | 21.93 |
| February | 321.33 | 21.13 | 198.83 | 21.91 | 0.00 | 21.91 |
| March | 252.33 | 21.43 | 331.83 | 22.24 | 13.33 | 22.35 |
| April | 178.33 | 21.83 | 371.00 | 22.48 | 18.67 | 22.66 |
| May | 141.83 | 26.19 | 485.17 | 24.15 | 105.50 | 24.70 |
| June | 196.83 | 27.13 | 584.17 | 24.62 | 195.17 | 25.13 |
| July | 244.67 | 26.28 | 683.33 | 24.14 | 244.67 | 24.59 |
| August | 245.17 | 26.39 | 661.17 | 24.27 | 245.17 | 24.72 |
| September | 204.00 | 26.68 | 568.33 | 24.50 | 199.67 | 24.97 |
| October | 142.83 | 23.47 | 435.50 | 23.11 | 55.67 | 23.47 |
| November | 207.00 | 21.75 | 338.17 | 22.50 | 17.33 | 22.70 |
| December | 339.00 | 21.12 | 230.17 | 21.95 | 0.00 | 21.95 |
| Annual Sum or Average | 2818.83 | 23.34 | 5111.83 | 23.33 | 1095.17 | 23.76 |
| Minimum of Months | 141.83 | 21.12 | 198.83 | 21.91 | 0.00 | 21.91 |
| Maximum of Months | 345.50 | 27.13 | 683.33 | 24.62 | 245.17 | 25.13 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM220_223
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.40 | 34.50 | 21.37 | 34.50 | 21.35 |
| February | 672.00 | 21.37 | 44.17 | 21.34 | 44.17 | 21.32 |
| March | 717.17 | 21.66 | 12.17 | 21.72 | 0.00 | 21.72 |
| April | 661.83 | 21.66 | 14.50 | 21.74 | 0.00 | 21.74 |
| May | 552.83 | 21.62 | 89.67 | 22.11 | 1.67 | 22.12 |
| June | 422.50 | 21.66 | 208.33 | 22.71 | 30.50 | 22.83 |
| July | 437.67 | 21.79 | 291.50 | 22.85 | 61.00 | 23.05 |
| August | 424.33 | 21.66 | 270.00 | 22.78 | 42.33 | 22.93 |
| September | 426.17 | 21.60 | 216.67 | 22.65 | 24.33 | 22.76 |
| October | 629.17 | 21.65 | 54.67 | 21.90 | 0.00 | 21.90 |
| November | 681.50 | 21.66 | 11.17 | 21.71 | 0.00 | 21.71 |
| December | 742.67 | 21.37 | 31.50 | 21.34 | 31.50 | 21.32 |
| Annual Sum or Average | 7111.83 | 21.57 | 1278.83 | 22.00 | 270.00 | 22.05 |
| Minimum of Months | 422.50 | 21.37 | 11.17 | 21.34 | 0.00 | 21.32 |
| Maximum of Months | 744.00 | 21.79 | 291.50 | 22.85 | 61.00 | 23.05 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM224
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.06 | 259.17 | 21.00 | 259.17 | 20.96 |
| February | 672.00 | 21.01 | 269.00 | 20.95 | 269.00 | 20.91 |
| March | 723.67 | 21.52 | 43.33 | 21.54 | 34.50 | 21.52 |
| April | 695.17 | 21.67 | 9.17 | 21.72 | 0.00 | 21.72 |
| May | 600.00 | 21.74 | 72.67 | 22.11 | 1.50 | 22.11 |
| June | 435.17 | 21.69 | 179.67 | 22.67 | 25.67 | 22.78 |
| July | 427.33 | 21.72 | 247.17 | 22.80 | 49.67 | 22.99 |
| August | 420.83 | 21.62 | 241.50 | 22.75 | 35.00 | 22.89 |
| September | 437.50 | 21.63 | 184.00 | 22.62 | 19.67 | 22.71 |
| October | 661.83 | 21.72 | 36.83 | 21.90 | 0.00 | 21.90 |
| November | 707.67 | 21.62 | 4.33 | 21.64 | 0.00 | 21.64 |
| December | 744.00 | 21.05 | 239.33 | 20.97 | 239.33 | 20.92 |
| Annual Sum or Average | 7269.17 | 21.47 | 1786.17 | 21.78 | 933.50 | 21.75 |
| Minimum of Months | 420.83 | 21.01 | 4.33 | 20.95 | 0.00 | 20.91 |
| Maximum of Months | 744.00 | 21.74 | 269.00 | 22.80 | 269.00 | 22.99 |
Report: ComfortReportSimple55Monthly
For: FRONTSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FRONTSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: REARSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORRIDORFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.11 | 639.50 | 21.11 | 639.50 | 21.11 |
| February | 672.00 | 21.11 | 582.00 | 21.11 | 582.00 | 21.11 |
| March | 699.67 | 21.31 | 325.67 | 21.25 | 325.67 | 21.22 |
| April | 707.17 | 21.95 | 25.00 | 21.93 | 25.00 | 21.90 |
| May | 501.33 | 23.24 | 8.33 | 23.25 | 0.00 | 23.25 |
| June | 112.33 | 23.65 | 234.83 | 23.81 | 0.00 | 23.81 |
| July | 0.00 | 0.00 | 493.17 | 23.89 | 0.00 | 23.89 |
| August | 4.50 | 23.68 | 308.17 | 23.89 | 0.00 | 23.89 |
| September | 196.33 | 23.36 | 148.17 | 23.59 | 0.00 | 23.59 |
| October | 691.33 | 22.25 | 0.00 | 22.25 | 0.00 | 22.25 |
| November | 720.00 | 21.43 | 64.67 | 21.40 | 64.67 | 21.38 |
| December | 744.00 | 21.11 | 539.00 | 21.11 | 539.00 | 21.11 |
| Annual Sum or Average | 5792.67 | 21.73 | 3368.50 | 21.86 | 2175.83 | 21.72 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 21.11 | 0.00 | 21.11 |
| Maximum of Months | 744.00 | 23.68 | 639.50 | 23.89 | 639.50 | 23.89 |
Report: ComfortReportSimple55Monthly
For: REARSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM301
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM302_305
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM306_308
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM309_312
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.78 | 498.50 | 20.72 | 498.50 | 20.70 |
| February | 672.00 | 20.79 | 444.50 | 20.73 | 444.50 | 20.70 |
| March | 732.17 | 21.17 | 224.17 | 21.11 | 216.17 | 21.05 |
| April | 706.50 | 21.55 | 14.33 | 21.59 | 5.00 | 21.58 |
| May | 630.67 | 21.83 | 85.00 | 22.24 | 4.83 | 22.26 |
| June | 478.17 | 21.97 | 196.83 | 22.87 | 50.33 | 23.04 |
| July | 459.00 | 22.00 | 233.00 | 22.95 | 81.67 | 23.20 |
| August | 469.50 | 21.96 | 205.50 | 22.90 | 69.17 | 23.12 |
| September | 554.33 | 22.12 | 160.83 | 22.81 | 58.17 | 22.99 |
| October | 718.83 | 21.70 | 33.17 | 21.84 | 15.17 | 21.90 |
| November | 719.50 | 21.35 | 20.83 | 21.36 | 20.83 | 21.38 |
| December | 744.00 | 20.82 | 367.33 | 20.73 | 367.33 | 20.69 |
| Annual Sum or Average | 7628.67 | 21.44 | 2484.00 | 21.65 | 1831.67 | 21.60 |
| Minimum of Months | 459.00 | 20.78 | 14.33 | 20.72 | 4.83 | 20.69 |
| Maximum of Months | 744.00 | 22.12 | 498.50 | 22.95 | 498.50 | 23.20 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM313
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM314
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.78 | 531.33 | 20.73 | 531.33 | 20.71 |
| February | 672.00 | 20.76 | 477.67 | 20.70 | 477.67 | 20.67 |
| March | 724.00 | 21.29 | 151.17 | 21.27 | 142.83 | 21.23 |
| April | 701.50 | 21.55 | 22.50 | 21.58 | 14.17 | 21.57 |
| May | 620.50 | 21.78 | 68.83 | 22.12 | 1.50 | 22.12 |
| June | 449.00 | 21.74 | 181.83 | 22.68 | 27.50 | 22.80 |
| July | 432.50 | 21.78 | 250.50 | 22.83 | 53.33 | 23.02 |
| August | 431.67 | 21.68 | 234.17 | 22.76 | 39.00 | 22.91 |
| September | 460.50 | 21.71 | 169.00 | 22.60 | 23.67 | 22.71 |
| October | 686.67 | 21.66 | 32.67 | 21.81 | 1.33 | 21.81 |
| November | 716.83 | 21.40 | 35.00 | 21.39 | 34.00 | 21.37 |
| December | 744.00 | 20.77 | 462.00 | 20.69 | 462.00 | 20.65 |
| Annual Sum or Average | 7383.17 | 21.35 | 2616.67 | 21.57 | 1808.33 | 21.49 |
| Minimum of Months | 431.67 | 20.76 | 22.50 | 20.69 | 1.33 | 20.65 |
| Maximum of Months | 744.00 | 21.78 | 531.33 | 22.83 | 531.33 | 23.02 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM315_318
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 739.83 | 21.58 | 2.00 | 21.58 | 2.00 | 21.58 |
| February | 666.83 | 21.56 | 10.50 | 21.55 | 10.50 | 21.53 |
| March | 692.17 | 21.68 | 21.33 | 21.76 | 0.17 | 21.77 |
| April | 626.50 | 21.61 | 21.83 | 21.73 | 0.00 | 21.73 |
| May | 485.83 | 21.40 | 123.50 | 22.14 | 0.83 | 22.15 |
| June | 377.33 | 21.46 | 279.33 | 22.83 | 18.67 | 22.93 |
| July | 399.17 | 21.70 | 357.00 | 22.97 | 45.17 | 23.15 |
| August | 391.83 | 21.56 | 339.50 | 22.91 | 30.67 | 23.04 |
| September | 395.67 | 21.49 | 277.67 | 22.78 | 17.50 | 22.87 |
| October | 595.17 | 21.57 | 73.67 | 21.92 | 0.67 | 21.92 |
| November | 652.00 | 21.64 | 16.00 | 21.73 | 0.00 | 21.73 |
| December | 737.33 | 21.54 | 0.17 | 21.54 | 0.17 | 21.54 |
| Annual Sum or Average | 6759.67 | 21.57 | 1522.50 | 22.12 | 126.33 | 22.17 |
| Minimum of Months | 377.33 | 21.40 | 0.17 | 21.54 | 0.00 | 21.53 |
| Maximum of Months | 739.83 | 21.70 | 357.00 | 22.97 | 45.17 | 23.15 |
Report: ComfortReportSimple55Monthly
For: ELEVATORCOREFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM319
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM320_323
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.23 | 151.00 | 21.16 | 151.00 | 21.12 |
| February | 672.00 | 21.21 | 151.17 | 21.15 | 151.17 | 21.11 |
| March | 720.50 | 21.58 | 24.83 | 21.62 | 14.50 | 21.61 |
| April | 679.17 | 21.65 | 13.67 | 21.71 | 0.00 | 21.71 |
| May | 581.33 | 21.69 | 82.00 | 22.11 | 2.33 | 22.12 |
| June | 440.83 | 21.73 | 199.33 | 22.69 | 35.50 | 22.82 |
| July | 448.83 | 21.84 | 274.83 | 22.83 | 67.50 | 23.03 |
| August | 441.33 | 21.73 | 250.67 | 22.75 | 50.33 | 22.92 |
| September | 450.00 | 21.69 | 192.17 | 22.62 | 29.33 | 22.74 |
| October | 653.67 | 21.66 | 43.67 | 21.87 | 0.67 | 21.87 |
| November | 705.17 | 21.59 | 6.33 | 21.61 | 0.50 | 21.61 |
| December | 744.00 | 21.18 | 135.00 | 21.12 | 135.00 | 21.07 |
| Annual Sum or Average | 7280.83 | 21.53 | 1524.67 | 21.88 | 637.83 | 21.90 |
| Minimum of Months | 440.83 | 21.18 | 6.33 | 21.12 | 0.00 | 21.07 |
| Maximum of Months | 744.00 | 21.84 | 274.83 | 22.83 | 151.17 | 23.03 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM324
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FRONTSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FRONTSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: REARSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: CORRIDORFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 21.11 | 731.67 | 21.11 | 731.67 | 21.11 |
| February | 672.00 | 21.11 | 664.00 | 21.11 | 664.00 | 21.11 |
| March | 716.00 | 21.29 | 463.67 | 21.23 | 457.17 | 21.20 |
| April | 685.50 | 21.65 | 207.83 | 21.53 | 207.83 | 21.45 |
| May | 527.00 | 22.50 | 67.50 | 22.57 | 18.33 | 22.53 |
| June | 224.00 | 23.02 | 299.67 | 23.51 | 17.17 | 23.52 |
| July | 131.83 | 23.55 | 525.83 | 23.82 | 49.17 | 23.83 |
| August | 187.67 | 23.41 | 404.67 | 23.74 | 31.17 | 23.74 |
| September | 354.33 | 22.66 | 177.67 | 23.07 | 13.17 | 23.09 |
| October | 685.00 | 21.73 | 123.83 | 21.63 | 123.83 | 21.56 |
| November | 720.00 | 21.29 | 438.17 | 21.22 | 438.17 | 21.19 |
| December | 744.00 | 21.11 | 722.67 | 21.11 | 722.67 | 21.11 |
| Annual Sum or Average | 6391.33 | 21.66 | 4827.17 | 21.79 | 3474.33 | 21.65 |
| Minimum of Months | 131.83 | 21.11 | 67.50 | 21.11 | 13.17 | 21.11 |
| Maximum of Months | 744.00 | 23.55 | 731.67 | 23.82 | 731.67 | 23.83 |
Report: ComfortReportSimple55Monthly
For: REARSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM401
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.42 | 744.00 | 20.42 | 744.00 | 20.42 |
| February | 672.00 | 20.42 | 672.00 | 20.42 | 672.00 | 20.42 |
| March | 726.33 | 20.69 | 560.50 | 20.64 | 553.00 | 20.60 |
| April | 703.67 | 21.22 | 268.67 | 21.12 | 264.83 | 21.05 |
| May | 584.00 | 21.63 | 112.33 | 22.06 | 30.67 | 22.05 |
| June | 433.00 | 21.85 | 256.67 | 22.94 | 48.50 | 23.11 |
| July | 452.00 | 22.05 | 335.33 | 23.05 | 80.83 | 23.30 |
| August | 454.00 | 21.92 | 288.83 | 22.94 | 63.83 | 23.14 |
| September | 490.50 | 21.80 | 177.50 | 22.64 | 50.17 | 22.79 |
| October | 717.00 | 21.25 | 222.67 | 21.24 | 203.33 | 21.17 |
| November | 720.00 | 20.71 | 559.67 | 20.63 | 559.67 | 20.60 |
| December | 744.00 | 20.43 | 740.50 | 20.43 | 740.50 | 20.43 |
| Annual Sum or Average | 7440.50 | 21.09 | 4938.67 | 21.25 | 4011.33 | 21.15 |
| Minimum of Months | 433.00 | 20.42 | 112.33 | 20.42 | 30.67 | 20.42 |
| Maximum of Months | 744.00 | 22.05 | 744.00 | 23.05 | 744.00 | 23.30 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM402_405
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM406_408
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM409_412
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.58 | 660.67 | 20.56 | 660.67 | 20.55 |
| February | 672.00 | 20.61 | 602.83 | 20.58 | 602.83 | 20.58 |
| March | 718.83 | 21.05 | 358.17 | 21.01 | 344.67 | 20.95 |
| April | 669.67 | 21.46 | 99.00 | 21.50 | 82.33 | 21.46 |
| May | 540.17 | 21.62 | 129.00 | 22.28 | 13.17 | 22.34 |
| June | 425.00 | 21.91 | 281.67 | 23.04 | 53.67 | 23.26 |
| July | 454.50 | 22.08 | 350.00 | 23.09 | 84.50 | 23.35 |
| August | 446.83 | 21.93 | 320.83 | 23.01 | 66.33 | 23.23 |
| September | 468.00 | 21.85 | 207.17 | 22.83 | 47.17 | 23.01 |
| October | 682.17 | 21.54 | 94.33 | 21.72 | 62.50 | 21.72 |
| November | 716.33 | 21.16 | 199.67 | 21.10 | 199.17 | 21.06 |
| December | 744.00 | 20.62 | 607.67 | 20.57 | 607.67 | 20.56 |
| Annual Sum or Average | 7281.50 | 21.27 | 3911.00 | 21.54 | 2824.67 | 21.46 |
| Minimum of Months | 425.00 | 20.58 | 94.33 | 20.56 | 13.17 | 20.55 |
| Maximum of Months | 744.00 | 22.08 | 660.67 | 23.09 | 660.67 | 23.35 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM413
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM414
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM415_418
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 739.83 | 21.09 | 400.50 | 21.00 | 400.50 | 20.96 |
| February | 663.67 | 21.10 | 336.83 | 21.03 | 336.83 | 20.99 |
| March | 673.83 | 21.45 | 163.33 | 21.47 | 140.17 | 21.42 |
| April | 609.17 | 21.45 | 85.33 | 21.68 | 17.50 | 21.67 |
| May | 500.17 | 21.44 | 191.00 | 22.24 | 2.67 | 22.25 |
| June | 397.83 | 21.60 | 312.17 | 22.84 | 29.33 | 22.96 |
| July | 430.00 | 21.85 | 350.00 | 22.94 | 60.83 | 23.14 |
| August | 419.17 | 21.68 | 335.00 | 22.85 | 41.17 | 23.00 |
| September | 419.17 | 21.56 | 286.33 | 22.72 | 20.67 | 22.81 |
| October | 610.83 | 21.53 | 108.33 | 21.88 | 15.83 | 21.87 |
| November | 662.00 | 21.39 | 74.00 | 21.41 | 61.83 | 21.37 |
| December | 737.33 | 21.02 | 360.50 | 20.94 | 359.50 | 20.89 |
| Annual Sum or Average | 6863.00 | 21.39 | 3003.33 | 21.81 | 1486.83 | 21.76 |
| Minimum of Months | 397.83 | 21.02 | 74.00 | 20.94 | 2.67 | 20.89 |
| Maximum of Months | 739.83 | 21.85 | 400.50 | 22.94 | 400.50 | 23.14 |
Report: ComfortReportSimple55Monthly
For: ELEVATORCOREFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM419
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 741.67 | 20.99 | 434.33 | 20.91 | 434.33 | 20.88 |
| February | 672.00 | 21.02 | 368.50 | 20.94 | 368.50 | 20.90 |
| March | 706.67 | 21.48 | 157.83 | 21.47 | 140.50 | 21.42 |
| April | 631.50 | 21.49 | 40.00 | 21.61 | 12.33 | 21.60 |
| May | 516.50 | 21.48 | 138.17 | 22.16 | 1.67 | 22.17 |
| June | 401.83 | 21.56 | 280.00 | 22.80 | 22.17 | 22.89 |
| July | 425.17 | 21.76 | 326.17 | 22.88 | 49.00 | 23.06 |
| August | 419.50 | 21.64 | 303.33 | 22.81 | 34.33 | 22.94 |
| September | 422.33 | 21.54 | 255.17 | 22.68 | 16.67 | 22.76 |
| October | 629.83 | 21.56 | 70.67 | 21.83 | 8.33 | 21.83 |
| November | 686.83 | 21.41 | 60.67 | 21.41 | 54.17 | 21.38 |
| December | 742.00 | 20.94 | 390.83 | 20.85 | 390.83 | 20.80 |
| Annual Sum or Average | 6995.83 | 21.36 | 2825.67 | 21.73 | 1532.83 | 21.66 |
| Minimum of Months | 401.83 | 20.94 | 40.00 | 20.85 | 1.67 | 20.80 |
| Maximum of Months | 742.00 | 21.76 | 434.33 | 22.88 | 434.33 | 23.06 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM420_423
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 740.33 | 21.01 | 457.33 | 20.93 | 457.33 | 20.89 |
| February | 665.17 | 21.03 | 384.50 | 20.95 | 384.50 | 20.92 |
| March | 682.83 | 21.43 | 177.33 | 21.44 | 156.33 | 21.38 |
| April | 616.17 | 21.44 | 86.00 | 21.63 | 27.83 | 21.61 |
| May | 511.00 | 21.46 | 173.00 | 22.19 | 4.50 | 22.20 |
| June | 403.67 | 21.59 | 300.33 | 22.79 | 28.67 | 22.91 |
| July | 438.83 | 21.84 | 341.67 | 22.90 | 62.33 | 23.10 |
| August | 428.00 | 21.70 | 320.67 | 22.82 | 44.00 | 22.97 |
| September | 426.50 | 21.58 | 274.33 | 22.68 | 22.67 | 22.77 |
| October | 619.33 | 21.52 | 102.33 | 21.83 | 20.33 | 21.82 |
| November | 671.83 | 21.36 | 87.00 | 21.36 | 78.33 | 21.32 |
| December | 739.17 | 20.95 | 415.83 | 20.87 | 415.83 | 20.82 |
| Annual Sum or Average | 6942.83 | 21.36 | 3120.33 | 21.75 | 1702.67 | 21.68 |
| Minimum of Months | 403.67 | 20.95 | 86.00 | 20.87 | 4.50 | 20.82 |
| Maximum of Months | 740.33 | 21.84 | 457.33 | 22.90 | 457.33 | 23.10 |
Report: ComfortReportSimple55Monthly
For: GUESTROOM424
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 744.00 | 20.67 | 647.83 | 20.63 | 647.83 | 20.62 |
| February | 672.00 | 20.69 | 574.83 | 20.64 | 574.83 | 20.62 |
| March | 720.00 | 21.28 | 281.50 | 21.24 | 265.67 | 21.17 |
| April | 649.83 | 21.41 | 85.17 | 21.45 | 70.50 | 21.41 |
| May | 540.50 | 21.53 | 111.00 | 22.08 | 3.83 | 22.09 |
| June | 415.50 | 21.60 | 259.17 | 22.75 | 24.67 | 22.85 |
| July | 430.33 | 21.76 | 319.83 | 22.86 | 50.00 | 23.03 |
| August | 424.83 | 21.64 | 292.50 | 22.78 | 35.17 | 22.92 |
| September | 438.00 | 21.59 | 236.17 | 22.64 | 19.00 | 22.72 |
| October | 648.83 | 21.50 | 89.17 | 21.70 | 40.33 | 21.67 |
| November | 714.17 | 21.29 | 170.83 | 21.19 | 168.83 | 21.12 |
| December | 744.00 | 20.66 | 608.17 | 20.61 | 608.17 | 20.58 |
| Annual Sum or Average | 7142.00 | 21.24 | 3676.17 | 21.50 | 2508.83 | 21.39 |
| Minimum of Months | 415.50 | 20.66 | 85.17 | 20.61 | 3.83 | 20.58 |
| Maximum of Months | 744.00 | 21.76 | 647.83 | 22.86 | 647.83 | 23.03 |
Report: ComfortReportSimple55Monthly
For: FRONTSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: FRONTSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDORFLR1_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDORFLR2_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDORFLR3_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: CORRIDORFLR4_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ELEVATORCOREFLR1_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ELEVATORCOREFLR2_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ELEVATORCOREFLR3_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: ELEVATORCOREFLR4_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: EMPLOYEELOUNGEFLR1_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 465.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 420.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 465.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 450.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 465.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 450.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 465.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 465.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 450.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 465.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 450.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 465.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 5475.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 420.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 465.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: EXERCISECENTERFLR1_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 496.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 448.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 496.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 480.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 496.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 480.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 496.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 496.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 480.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 496.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 480.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 496.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 5840.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 448.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 496.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: FRONTLOUNGEFLR1_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: FRONTOFFICEFLR1_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 682.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 616.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 682.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 660.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 682.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 660.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 682.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 682.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 660.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 682.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 660.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 682.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8030.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 616.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 682.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: FRONTSTAIRSFLR1_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: FRONTSTAIRSFLR2_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: FRONTSTAIRSFLR3_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: FRONTSTAIRSFLR4_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: FRONTSTORAGEFLR1_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: FRONTSTORAGEFLR2_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: FRONTSTORAGEFLR3_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: FRONTSTORAGEFLR4_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM101_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM102_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM103_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM104_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM105_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM201_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM202_205_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM206_208_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM209_212_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM213_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM214_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM215_218_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM219_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM220_223_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM224_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM301_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM302_305_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM306_308_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM309_312_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM313_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM314_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM315_318_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM319_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM320_323_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM324_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM401_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM402_405_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM406_408_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM409_412_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM413_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM414_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM415_418_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM419_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM420_423_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: GUESTROOM424_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: LAUNDRYROOMFLR1_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 248.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 224.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 248.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 240.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 248.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 240.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 248.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 248.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 240.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 248.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 240.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 248.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 2920.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 224.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 248.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: MECHANICALROOMFLR1_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: MEETINGROOMFLR1_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 175.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 159.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 178.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 170.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 177.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 172.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 175.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 178.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 170.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 176.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 170.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 175.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 2075.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 159.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 178.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: REARSTAIRSFLR1_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: REARSTAIRSFLR2_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: REARSTAIRSFLR3_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: REARSTAIRSFLR4_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: REARSTORAGEFLR1_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: REARSTORAGEFLR2_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: REARSTORAGEFLR3_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: REARSTORAGEFLR4_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 0.00000 | 0.00000 | 0.00000 | ||
| Minimum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 0.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: OccupantComfortDataSummaryMonthly
For: RESTROOMFLR1_PEOPLE
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV [] | ZONE THERMAL COMFORT FANGER MODEL PPD [] | |
| January | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| February | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| March | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| April | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| May | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| June | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| July | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| August | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| September | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| October | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| November | 720.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| December | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Annual Sum or Average | 8760.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Minimum of Months | 672.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
| Maximum of Months | 744.00000 | 0.00000 | 0.00000 | 0.00000 | 0.00000 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| BOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
| January | 0.796778E+11 | 0.00 | 744.00 | 121513.29 | 28-JAN-16:12 | 0.00 | 40.53 | 82.00 | 0.18 | 0.00 | 0.10 | 0.42 | 28-JAN-16:12 |
| February | 0.780907E+11 | 0.00 | 672.00 | 127341.65 | 12-FEB-16:12 | 0.00 | 40.36 | 82.00 | 0.19 | 0.00 | 0.11 | 0.44 | 12-FEB-16:12 |
| March | 0.386663E+11 | 0.00 | 658.08 | 84803.59 | 04-MAR-16:12 | 0.00 | 31.35 | 75.24 | 0.08 | 0.00 | 0.05 | 0.29 | 04-MAR-16:12 |
| April | 0.114798E+11 | 0.00 | 549.53 | 38063.82 | 16-APR-06:03 | 0.00 | 24.79 | 68.33 | 0.02 | 0.00 | 0.02 | 0.13 | 16-APR-06:03 |
| May | 0.112473E+10 | 0.00 | 167.88 | 21949.32 | 11-MAY-15:15 | 0.00 | 22.62 | 35.99 | 0.00 | 0.00 | 0.00 | 0.08 | 11-MAY-15:15 |
| June | 82941493.05 | 0.00 | 25.78 | 20959.62 | 14-JUN-08:04 | 0.00 | 22.31 | 24.46 | 0.00 | 0.00 | 0.00 | 0.07 | 14-JUN-08:04 |
| July | 899441.61 | 0.00 | 0.45 | 3921.84 | 06-JUL-08:56 | 0.00 | 22.50 | 22.53 | 0.00 | 0.00 | 0.00 | 0.01 | 06-JUL-08:56 |
| August | 1605064.31 | 0.00 | 0.83 | 8353.89 | 31-AUG-08:04 | 0.00 | 22.53 | 22.60 | 0.00 | 0.00 | 0.00 | 0.03 | 31-AUG-08:04 |
| September | 0.166941E+09 | 0.00 | 70.01 | 16014.60 | 28-SEP-15:15 | 0.00 | 22.69 | 28.45 | 0.00 | 0.00 | 0.00 | 0.05 | 28-SEP-15:15 |
| October | 0.558199E+10 | 0.00 | 425.58 | 31628.88 | 16-OCT-18:05 | 0.00 | 24.74 | 57.32 | 0.01 | 0.00 | 0.01 | 0.11 | 16-OCT-18:05 |
| November | 0.169714E+11 | 0.00 | 636.05 | 79441.35 | 30-NOV-16:12 | 0.00 | 27.39 | 75.32 | 0.03 | 0.00 | 0.02 | 0.27 | 30-NOV-16:12 |
| December | 0.723205E+11 | 0.00 | 744.00 | 122097.89 | 09-DEC-16:11 | 0.00 | 39.00 | 82.00 | 0.16 | 0.00 | 0.09 | 0.42 | 09-DEC-16:11 |
| Annual Sum or Average | 0.304166E+12 | 0.00 | 4694.20 | 0.00 | 28.35 | 54.52 | 0.06 | 0.00 | 0.03 | ||||
| Minimum of Months | 899441.61 | 0.00 | 0.45 | 3921.84 | 0.00 | 22.31 | 22.53 | 0.00 | 0.00 | 0.00 | 0.01 | ||
| Maximum of Months | 0.796778E+11 | 0.00 | 744.00 | 127341.65 | 0.00 | 40.53 | 82.00 | 0.19 | 0.00 | 0.11 | 0.44 |
Report: DXReportMonthly
For: 101 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 |
| July | 519301.69 | 139479.14 | 2.29 | 315624.42 | 203677.26 | 0.00 | 0.11 | 21-JUL-14:09 | 0.00 | 01-JUL-00:10 | 152.43 | 21-JUL-14:09 | 89.22 | 21-JUL-14:09 | 63.45 | 21-JUL-14:30 | 41.00 | 21-JUL-14:09 | 0.00 | 01-JUL-00:10 |
| August | 224591.13 | 62161.75 | 1.67 | 186188.73 | 38402.39 | 0.00 | 0.06 | 10-AUG-14:35 | 0.00 | 01-AUG-00:10 | 66.13 | 10-AUG-14:35 | 56.53 | 10-AUG-14:35 | 14.61 | 13-AUG-14:50 | 18.44 | 10-AUG-14:35 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 743892.81 | 201640.89 | 3.95 | 501813.16 | 242079.65 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 519301.69 | 139479.14 | 2.29 | 315624.42 | 203677.26 | 0.00 | 0.11 | 0.00 | 152.43 | 89.22 | 63.45 | 41.00 | 0.00 |
Report: DXReportMonthly
For: 102 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 | 0.00 | 01-JUN-00:10 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 | 0.00 | 01-JUL-00:10 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: 103 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 1485019.80 | 360244.53 | 1.05 | 1140882.05 | 344137.75 | 0.00 | 0.63 | 11-JAN-09:03 | 0.00 | 01-JAN-00:10 | 1114.37 | 11-JAN-09:03 | 850.91 | 11-JAN-09:03 | 437.93 | 11-JAN-19:03 | 258.26 | 11-JAN-09:03 | 0.00 | 01-JAN-00:10 |
| February | 1175793.85 | 285525.36 | 0.86 | 947292.66 | 228501.18 | 0.00 | 0.59 | 23-FEB-09:03 | 0.00 | 01-FEB-00:10 | 1032.01 | 23-FEB-09:03 | 851.12 | 22-FEB-16:15 | 290.13 | 23-FEB-09:03 | 240.92 | 23-FEB-09:03 | 0.00 | 01-FEB-00:10 |
| March | 79810963.92 | 19325034.57 | 69.46 | 53387333.78 | 26423630.14 | 0.00 | 1.00 | 12-MAR-08:61 | 0.00 | 01-MAR-00:10 | 2217.62 | 14-MAR-15:12 | 1531.45 | 15-MAR-19:21 | 1092.80 | 14-MAR-15:12 | 473.66 | 14-MAR-15:12 | 0.00 | 01-MAR-00:10 |
| April | 96403767.27 | 23570938.67 | 132.86 | 68853062.33 | 27550704.93 | 0.00 | 1.00 | 02-APR-08:61 | 0.00 | 01-APR-00:10 | 2140.04 | 30-APR-15:12 | 1675.65 | 23-APR-08:61 | 1019.36 | 30-APR-15:12 | 459.11 | 30-APR-15:12 | 0.00 | 01-APR-00:10 |
| May | 0.527722E+09 | 0.127435E+09 | 397.04 | 0.392042E+09 | 0.135680E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 2196.42 | 24-MAY-08:51 | 1768.70 | 23-MAY-16:41 | 1031.08 | 24-MAY-08:54 | 470.90 | 10-MAY-15:12 | 0.00 | 01-MAY-00:10 |
| June | 0.133344E+10 | 0.312891E+09 | 505.52 | 0.974587E+09 | 0.358849E+09 | 0.00 | 1.00 | 01-JUN-07:41 | 0.00 | 01-JUN-05:11 | 2341.03 | 18-JUN-08:12 | 1908.38 | 30-JUN-19:11 | 1171.61 | 08-JUN-08:53 | 493.28 | 18-JUN-08:12 | 0.00 | 01-JUN-00:10 |
| July | 0.207623E+10 | 0.482788E+09 | 560.71 | 0.147781E+10 | 0.598421E+09 | 0.00 | 1.00 | 01-JUL-07:51 | 0.00 | 01-JUL-06:01 | 2379.14 | 28-JUL-21:11 | 1848.80 | 06-JUL-16:41 | 1196.20 | 28-JUL-21:16 | 497.48 | 16-JUL-08:12 | 0.00 | 01-JUL-00:10 |
| August | 0.190446E+10 | 0.443787E+09 | 549.59 | 0.142089E+10 | 0.483569E+09 | 0.00 | 1.00 | 01-AUG-08:51 | 0.00 | 01-AUG-06:51 | 2354.34 | 28-AUG-21:41 | 1863.98 | 03-AUG-20:31 | 1147.75 | 28-AUG-21:45 | 491.60 | 28-AUG-21:41 | 0.00 | 01-AUG-00:10 |
| September | 0.128514E+10 | 0.301449E+09 | 511.92 | 0.955167E+09 | 0.329969E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 2331.52 | 15-SEP-21:31 | 1784.13 | 22-SEP-16:51 | 1079.12 | 15-SEP-21:37 | 488.50 | 15-SEP-21:31 | 0.00 | 01-SEP-00:10 |
| October | 0.551199E+09 | 0.133399E+09 | 436.97 | 0.413784E+09 | 0.137415E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 2185.11 | 12-OCT-21:51 | 1620.57 | 25-OCT-20:11 | 932.77 | 12-OCT-21:56 | 466.56 | 12-OCT-21:51 | 0.00 | 01-OCT-00:10 |
| November | 0.130849E+09 | 31985341.95 | 173.09 | 99144137.26 | 31705175.42 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-02:30 | 2107.97 | 05-NOV-08:51 | 1576.05 | 18-NOV-09:01 | 860.29 | 20-NOV-19:02 | 453.59 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 3285270.06 | 798787.08 | 5.13 | 2379721.06 | 905549.00 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 2021.69 | 01-DEC-09:01 | 1511.04 | 02-DEC-09:01 | 763.25 | 01-DEC-09:01 | 437.90 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.799119E+10 | 0.187807E+10 | 3344.22 | 0.586013E+10 | 0.213106E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 1175793.85 | 285525.36 | 0.86 | 947292.66 | 228501.18 | 0.00 | 0.59 | 0.00 | 1032.01 | 850.91 | 290.13 | 240.92 | 0.00 | |||||||
| Maximum of Months | 0.207623E+10 | 0.482788E+09 | 560.71 | 0.147781E+10 | 0.598421E+09 | 0.00 | 1.00 | 0.00 | 2379.14 | 1908.38 | 1196.20 | 497.48 | 0.00 |
Report: DXReportMonthly
For: 104 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 18431995.06 | 4457869.76 | 28.08 | 14918095.86 | 3513899.20 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:10 | 2474.34 | 17-JAN-19:02 | 2032.55 | 22-JAN-09:01 | 894.39 | 11-JAN-19:02 | 536.96 | 17-JAN-19:02 | 0.00 | 01-JAN-00:10 |
| February | 7751300.77 | 1870879.01 | 16.77 | 6599989.18 | 1151311.59 | 0.00 | 1.00 | 12-FEB-09:01 | 0.00 | 01-FEB-00:10 | 2399.51 | 18-FEB-16:12 | 2112.79 | 19-FEB-09:01 | 609.29 | 18-FEB-16:12 | 521.95 | 18-FEB-16:12 | 0.00 | 01-FEB-00:10 |
| March | 0.241002E+09 | 58537290.74 | 193.99 | 0.181733E+09 | 59269223.22 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 2678.08 | 12-MAR-15:12 | 2149.54 | 01-MAR-16:12 | 1149.45 | 12-MAR-15:13 | 573.87 | 12-MAR-15:12 | 0.00 | 01-MAR-00:10 |
| April | 0.412272E+09 | 0.100921E+09 | 382.03 | 0.331759E+09 | 80512459.79 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:10 | 2659.67 | 30-APR-15:12 | 2343.04 | 22-APR-16:41 | 1089.13 | 30-APR-15:13 | 570.76 | 30-APR-15:12 | 0.00 | 01-APR-00:10 |
| May | 0.925986E+09 | 0.224229E+09 | 561.65 | 0.739279E+09 | 0.186708E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-04:40 | 2718.84 | 29-MAY-08:21 | 2319.92 | 27-MAY-17:21 | 1103.34 | 24-MAY-08:55 | 580.58 | 29-MAY-08:21 | 0.00 | 01-MAY-00:10 |
| June | 0.161819E+10 | 0.383646E+09 | 532.37 | 0.123096E+10 | 0.387232E+09 | 0.00 | 1.00 | 01-JUN-06:51 | 0.00 | 01-JUN-05:11 | 2847.25 | 17-JUN-08:51 | 2409.86 | 30-JUN-19:01 | 1320.56 | 08-JUN-08:05 | 603.57 | 17-JUN-08:51 | 0.00 | 01-JUN-00:10 |
| July | 0.235397E+10 | 0.555156E+09 | 579.72 | 0.173097E+10 | 0.622997E+09 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 2924.56 | 16-JUL-07:51 | 2384.27 | 06-JUL-16:11 | 1380.47 | 16-JUL-07:56 | 614.16 | 16-JUL-07:51 | 0.00 | 01-JUL-00:10 |
| August | 0.227301E+10 | 0.535949E+09 | 581.26 | 0.175737E+10 | 0.515645E+09 | 0.00 | 1.00 | 01-AUG-08:41 | 0.00 | 01-AUG-06:51 | 2889.61 | 26-AUG-08:51 | 2398.01 | 22-AUG-16:01 | 1278.25 | 26-AUG-08:56 | 613.56 | 15-AUG-08:41 | 0.00 | 01-AUG-00:10 |
| September | 0.180544E+10 | 0.425147E+09 | 560.86 | 0.142431E+10 | 0.381131E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 2877.89 | 15-SEP-21:31 | 2398.36 | 19-SEP-16:01 | 1276.27 | 15-SEP-21:37 | 604.66 | 15-SEP-21:31 | 0.00 | 01-SEP-00:10 |
| October | 0.110292E+10 | 0.266496E+09 | 607.98 | 0.905720E+09 | 0.197202E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 2692.88 | 12-OCT-21:01 | 2358.52 | 25-OCT-16:51 | 956.61 | 12-OCT-21:08 | 576.33 | 12-OCT-21:01 | 0.00 | 01-OCT-00:10 |
| November | 0.498620E+09 | 0.122101E+09 | 449.71 | 0.417888E+09 | 80732236.37 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-06:51 | 2626.51 | 05-NOV-08:51 | 2177.15 | 25-NOV-19:02 | 880.68 | 20-NOV-16:12 | 565.06 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 38740064.45 | 9456458.27 | 65.30 | 30466743.62 | 8273320.83 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 2532.12 | 14-DEC-19:02 | 2056.96 | 04-DEC-16:12 | 1046.20 | 14-DEC-19:02 | 548.01 | 14-DEC-19:02 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.112963E+11 | 0.268797E+10 | 4559.73 | 0.877198E+10 | 0.252437E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 7751300.77 | 1870879.01 | 16.77 | 6599989.18 | 1151311.59 | 0.00 | 1.00 | 0.00 | 2399.51 | 2032.55 | 609.29 | 521.95 | 0.00 | |||||||
| Maximum of Months | 0.235397E+10 | 0.555156E+09 | 607.98 | 0.175737E+10 | 0.622997E+09 | 0.00 | 1.00 | 0.00 | 2924.56 | 2409.86 | 1380.47 | 614.16 | 0.00 |
Report: DXReportMonthly
For: 105 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.645911E+09 | 0.159776E+09 | 571.89 | 0.604848E+09 | 41062545.83 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-07:51 | 3150.75 | 11-JAN-16:12 | 2916.91 | 13-JAN-16:12 | 634.99 | 11-JAN-16:12 | 684.20 | 11-JAN-16:12 | 0.00 | 01-JAN-00:10 |
| February | 0.494499E+09 | 0.122289E+09 | 451.04 | 0.459573E+09 | 34926352.51 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-07:51 | 3142.50 | 01-FEB-09:01 | 2941.50 | 22-FEB-16:12 | 711.44 | 01-FEB-09:02 | 682.56 | 01-FEB-09:01 | 0.00 | 01-FEB-00:10 |
| March | 0.127008E+10 | 0.310409E+09 | 674.02 | 0.114324E+10 | 0.126849E+09 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-07:51 | 3374.53 | 14-MAR-21:31 | 2953.01 | 15-MAR-18:51 | 961.75 | 14-MAR-21:36 | 725.69 | 14-MAR-21:31 | 0.00 | 01-MAR-00:10 |
| April | 0.157466E+10 | 0.383381E+09 | 670.30 | 0.141611E+10 | 0.158556E+09 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-06:51 | 3286.01 | 08-APR-21:21 | 3114.52 | 07-APR-16:51 | 760.79 | 08-APR-21:32 | 709.92 | 08-APR-21:21 | 0.00 | 01-APR-00:10 |
| May | 0.202643E+10 | 0.487103E+09 | 645.31 | 0.176924E+10 | 0.257190E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-06:51 | 3488.55 | 29-MAY-08:21 | 3161.17 | 23-MAY-16:11 | 1226.26 | 24-MAY-08:55 | 744.79 | 29-MAY-08:21 | 0.00 | 01-MAY-00:10 |
| June | 0.250156E+10 | 0.593664E+09 | 591.24 | 0.205224E+10 | 0.449321E+09 | 0.00 | 1.00 | 01-JUN-06:51 | 0.00 | 01-JUN-05:11 | 3595.65 | 08-JUN-08:61 | 3145.36 | 04-JUN-16:11 | 1453.29 | 08-JUN-08:07 | 764.86 | 17-JUN-08:51 | 0.00 | 01-JUN-00:10 |
| July | 0.318171E+10 | 0.754357E+09 | 618.88 | 0.249935E+10 | 0.682358E+09 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 3656.12 | 16-JUL-07:51 | 3205.35 | 06-JUL-17:01 | 1523.07 | 29-JUL-08:57 | 774.63 | 16-JUL-07:51 | 0.00 | 01-JUL-00:10 |
| August | 0.307176E+10 | 0.727468E+09 | 617.34 | 0.250654E+10 | 0.565220E+09 | 0.00 | 1.00 | 01-AUG-08:41 | 0.00 | 01-AUG-06:51 | 3622.28 | 26-AUG-08:51 | 3216.27 | 01-AUG-16:51 | 1442.38 | 15-AUG-08:48 | 775.94 | 15-AUG-08:41 | 0.00 | 01-AUG-00:10 |
| September | 0.265018E+10 | 0.624973E+09 | 605.85 | 0.221955E+10 | 0.430623E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 3606.75 | 15-SEP-21:31 | 3242.68 | 22-SEP-16:51 | 1424.62 | 15-SEP-21:37 | 763.17 | 15-SEP-21:31 | 0.00 | 01-SEP-00:10 |
| October | 0.222467E+10 | 0.534439E+09 | 692.41 | 0.197277E+10 | 0.251899E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 3421.96 | 12-OCT-21:01 | 3218.80 | 11-OCT-16:52 | 1082.74 | 12-OCT-21:06 | 733.80 | 12-OCT-21:01 | 0.00 | 01-OCT-00:10 |
| November | 0.163190E+10 | 0.396926E+09 | 675.29 | 0.149184E+10 | 0.140059E+09 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-06:51 | 3388.41 | 05-NOV-08:51 | 3058.52 | 26-NOV-17:51 | 974.47 | 05-NOV-08:56 | 728.09 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 0.774856E+09 | 0.191306E+09 | 581.44 | 0.710407E+09 | 64448864.98 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-07:51 | 3151.53 | 01-DEC-09:01 | 2883.01 | 04-DEC-16:12 | 646.39 | 01-DEC-09:02 | 684.35 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.220482E+11 | 0.528609E+10 | 7395.01 | 0.188457E+11 | 0.320251E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.494499E+09 | 0.122289E+09 | 451.04 | 0.459573E+09 | 34926352.51 | 0.00 | 1.00 | 0.00 | 3142.50 | 2883.01 | 634.99 | 682.56 | 0.00 | |||||||
| Maximum of Months | 0.318171E+10 | 0.754357E+09 | 692.41 | 0.250654E+10 | 0.682358E+09 | 0.00 | 1.00 | 0.00 | 3656.12 | 3242.68 | 1523.07 | 775.94 | 0.00 |
Report: DXReportMonthly
For: 201 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 4338485.40 | 1149691.66 | 18.65 | 3063749.82 | 1274735.58 | 0.00 | 0.14 | 12-JUN-14:02 | 0.00 | 01-JUN-00:10 | 217.88 | 12-JUN-14:02 | 180.47 | 12-JUN-14:02 | 70.76 | 27-JUN-14:10 | 60.11 | 12-JUN-14:02 | 0.00 | 01-JUN-00:10 |
| July | 23718883.47 | 6255306.61 | 74.73 | 15581116.58 | 8137766.88 | 0.00 | 0.22 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 | 360.01 | 21-JUL-14:02 | 249.07 | 21-JUL-14:02 | 120.16 | 20-JUL-14:10 | 97.66 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 |
| August | 6151460.66 | 1672103.74 | 32.80 | 5109674.65 | 1041786.01 | 0.00 | 0.42 | 14-AUG-15:01 | 0.00 | 01-AUG-00:10 | 769.48 | 14-AUG-15:01 | 440.99 | 14-AUG-15:01 | 328.48 | 14-AUG-15:01 | 186.26 | 14-AUG-15:01 | 0.00 | 01-AUG-00:10 |
| September | 30995.52 | 8062.25 | 0.50 | 21663.79 | 9331.73 | 0.00 | 0.02 | 16-SEP-14:50 | 0.00 | 01-SEP-00:10 | 25.04 | 16-SEP-14:50 | 17.51 | 16-SEP-14:50 | 7.53 | 16-SEP-14:50 | 6.51 | 16-SEP-14:50 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 34239825.05 | 9085164.26 | 126.68 | 23776204.84 | 10463620.21 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 23718883.47 | 6255306.61 | 74.73 | 15581116.58 | 8137766.88 | 0.00 | 0.42 | 0.00 | 769.48 | 440.99 | 328.48 | 186.26 | 0.00 |
Report: DXReportMonthly
For: 202_205 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 15547621.42 | 3678312.23 | 5.73 | 11608279.21 | 3939342.21 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:10 | 7559.23 | 17-JAN-19:02 | 5917.35 | 22-JAN-09:01 | 2768.15 | 17-JAN-19:02 | 1639.47 | 17-JAN-19:02 | 0.00 | 01-JAN-00:10 |
| February | 9731961.73 | 2345131.85 | 4.23 | 7955235.92 | 1776725.80 | 0.00 | 1.00 | 12-FEB-09:01 | 0.00 | 01-FEB-00:10 | 7040.16 | 20-FEB-09:01 | 6168.27 | 19-FEB-09:01 | 1636.27 | 20-FEB-09:01 | 1532.75 | 20-FEB-09:01 | 0.00 | 01-FEB-00:10 |
| March | 0.733542E+09 | 0.177054E+09 | 152.51 | 0.531901E+09 | 0.201642E+09 | 0.00 | 1.00 | 09-MAR-19:02 | 0.00 | 01-MAR-00:10 | 8199.32 | 14-MAR-18:51 | 6474.46 | 15-MAR-19:21 | 3802.54 | 12-MAR-15:12 | 1753.86 | 14-MAR-18:51 | 0.00 | 01-MAR-00:10 |
| April | 0.123641E+10 | 0.301375E+09 | 330.44 | 0.958021E+09 | 0.278393E+09 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:10 | 7970.54 | 08-APR-18:11 | 6742.29 | 22-APR-17:11 | 3123.05 | 29-APR-15:13 | 1715.08 | 08-APR-18:11 | 0.00 | 01-APR-00:10 |
| May | 0.366729E+10 | 0.880202E+09 | 589.01 | 0.291496E+10 | 0.752322E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-03:50 | 8448.87 | 24-MAY-07:31 | 7350.00 | 23-MAY-16:41 | 3715.17 | 24-MAY-08:56 | 1793.55 | 24-MAY-07:31 | 0.00 | 01-MAY-00:10 |
| June | 0.634852E+10 | 0.148682E+10 | 567.01 | 0.479877E+10 | 0.154975E+10 | 0.00 | 1.00 | 01-JUN-07:41 | 0.00 | 01-JUN-05:11 | 8812.62 | 18-JUN-07:51 | 7559.99 | 30-JUN-17:42 | 4248.56 | 08-JUN-08:56 | 1861.25 | 27-JUN-08:11 | 0.00 | 01-JUN-00:10 |
| July | 0.880693E+10 | 0.205073E+10 | 603.89 | 0.635571E+10 | 0.245121E+10 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 8973.93 | 16-JUL-07:51 | 7430.52 | 06-JUL-16:21 | 4224.52 | 29-JUL-08:35 | 1877.33 | 16-JUL-07:51 | 0.00 | 01-JUL-00:10 |
| August | 0.762085E+10 | 0.178445E+10 | 589.74 | 0.568905E+10 | 0.193181E+10 | 0.00 | 1.00 | 01-AUG-08:51 | 0.00 | 01-AUG-06:51 | 8861.17 | 14-AUG-08:11 | 7220.36 | 01-AUG-16:11 | 4148.46 | 14-AUG-08:16 | 1862.61 | 14-AUG-08:11 | 0.00 | 01-AUG-00:10 |
| September | 0.495103E+10 | 0.116815E+10 | 553.67 | 0.364375E+10 | 0.130727E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 8761.79 | 14-SEP-08:21 | 6914.18 | 22-SEP-16:51 | 3990.43 | 14-SEP-08:27 | 1839.53 | 14-SEP-08:21 | 0.00 | 01-SEP-00:10 |
| October | 0.207977E+10 | 0.503735E+09 | 448.58 | 0.154687E+10 | 0.532905E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 8395.56 | 12-OCT-21:51 | 6081.19 | 21-OCT-21:51 | 3622.84 | 26-OCT-15:13 | 1785.30 | 12-OCT-21:51 | 0.00 | 01-OCT-00:10 |
| November | 0.612699E+09 | 0.149375E+09 | 191.80 | 0.466255E+09 | 0.146444E+09 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-01:30 | 8125.48 | 05-NOV-08:51 | 5957.78 | 18-NOV-09:01 | 3336.80 | 16-NOV-19:15 | 1741.59 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 30800766.46 | 7344411.94 | 12.05 | 22408132.48 | 8392633.98 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 7719.30 | 01-DEC-09:01 | 5889.52 | 03-DEC-09:01 | 3428.68 | 14-DEC-19:02 | 1669.80 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.361131E+11 | 0.851526E+10 | 4048.66 | 0.269473E+11 | 0.916586E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 9731961.73 | 2345131.85 | 4.23 | 7955235.92 | 1776725.80 | 0.00 | 1.00 | 0.00 | 7040.16 | 5889.52 | 1636.27 | 1532.75 | 0.00 | |||||||
| Maximum of Months | 0.880693E+10 | 0.205073E+10 | 603.89 | 0.635571E+10 | 0.245121E+10 | 0.00 | 1.00 | 0.00 | 8973.93 | 7559.99 | 4248.56 | 1877.33 | 0.00 |
Report: DXReportMonthly
For: 206_208 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 29589510.91 | 7023840.47 | 18.82 | 23389601.83 | 6199909.08 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:10 | 5966.44 | 11-JAN-19:02 | 4918.89 | 21-JAN-09:01 | 2276.66 | 11-JAN-19:02 | 1294.71 | 11-JAN-19:02 | 0.00 | 01-JAN-00:10 |
| February | 21144850.66 | 5017097.77 | 10.61 | 17802006.81 | 3342843.85 | 0.00 | 1.00 | 04-FEB-09:01 | 0.00 | 01-FEB-00:10 | 5675.87 | 15-FEB-09:01 | 5089.83 | 19-FEB-09:01 | 1570.75 | 01-FEB-09:01 | 1235.52 | 15-FEB-09:01 | 0.00 | 01-FEB-00:10 |
| March | 0.736111E+09 | 0.177719E+09 | 197.45 | 0.553708E+09 | 0.182402E+09 | 0.00 | 1.00 | 02-MAR-19:02 | 0.00 | 01-MAR-00:10 | 6462.41 | 14-MAR-20:51 | 5199.04 | 15-MAR-19:21 | 2703.48 | 12-MAR-15:13 | 1384.37 | 14-MAR-20:51 | 0.00 | 01-MAR-00:10 |
| April | 0.130584E+10 | 0.318214E+09 | 424.08 | 0.105341E+10 | 0.252437E+09 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:10 | 6289.64 | 08-APR-18:11 | 5546.30 | 22-APR-17:11 | 2187.95 | 28-APR-15:13 | 1354.71 | 08-APR-18:11 | 0.00 | 01-APR-00:10 |
| May | 0.320405E+10 | 0.767604E+09 | 605.82 | 0.260846E+10 | 0.595587E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-06:51 | 6659.04 | 24-MAY-08:51 | 5879.97 | 23-MAY-16:41 | 2838.87 | 24-MAY-08:57 | 1416.11 | 24-MAY-08:51 | 0.00 | 01-MAY-00:10 |
| June | 0.504785E+10 | 0.118183E+10 | 566.56 | 0.385099E+10 | 0.119686E+10 | 0.00 | 1.00 | 01-JUN-07:41 | 0.00 | 01-JUN-05:11 | 6959.37 | 18-JUN-07:51 | 5837.39 | 03-JUN-17:01 | 3268.05 | 08-JUN-08:56 | 1473.44 | 27-JUN-08:11 | 0.00 | 01-JUN-00:10 |
| July | 0.686326E+10 | 0.159904E+10 | 602.83 | 0.496952E+10 | 0.189374E+10 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 7085.95 | 16-JUL-07:51 | 5887.35 | 06-JUL-16:21 | 3293.43 | 29-JUL-08:36 | 1485.03 | 16-JUL-07:51 | 0.00 | 01-JUL-00:10 |
| August | 0.596300E+10 | 0.139655E+10 | 588.21 | 0.447391E+10 | 0.148910E+10 | 0.00 | 1.00 | 01-AUG-08:51 | 0.00 | 01-AUG-06:51 | 7011.11 | 14-AUG-08:11 | 5701.69 | 01-AUG-16:11 | 3249.42 | 14-AUG-08:17 | 1475.16 | 14-AUG-08:11 | 0.00 | 01-AUG-00:10 |
| September | 0.403235E+10 | 0.950522E+09 | 555.68 | 0.301329E+10 | 0.101906E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 6916.32 | 14-SEP-08:21 | 5515.87 | 22-SEP-16:51 | 3086.44 | 14-SEP-08:27 | 1454.45 | 14-SEP-08:21 | 0.00 | 01-SEP-00:10 |
| October | 0.198731E+10 | 0.481054E+09 | 500.95 | 0.153310E+10 | 0.454207E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 6626.43 | 12-OCT-21:51 | 4960.81 | 21-OCT-21:51 | 2758.44 | 12-OCT-21:57 | 1410.99 | 12-OCT-21:51 | 0.00 | 01-OCT-00:10 |
| November | 0.725611E+09 | 0.177109E+09 | 286.43 | 0.578495E+09 | 0.147116E+09 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-06:51 | 6412.80 | 05-NOV-08:51 | 4907.85 | 18-NOV-09:01 | 2467.56 | 16-NOV-19:15 | 1376.02 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 56786034.64 | 13676081.96 | 36.99 | 43116878.75 | 13669155.89 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 6068.92 | 01-DEC-09:01 | 4991.85 | 23-DEC-09:01 | 2457.60 | 14-DEC-19:02 | 1314.39 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.299729E+11 | 0.707536E+10 | 4394.45 | 0.227192E+11 | 0.725371E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 21144850.66 | 5017097.77 | 10.61 | 17802006.81 | 3342843.85 | 0.00 | 1.00 | 0.00 | 5675.87 | 4907.85 | 1570.75 | 1235.52 | 0.00 | |||||||
| Maximum of Months | 0.686326E+10 | 0.159904E+10 | 605.82 | 0.496952E+10 | 0.189374E+10 | 0.00 | 1.00 | 0.00 | 7085.95 | 5887.35 | 3293.43 | 1485.03 | 0.00 |
Report: DXReportMonthly
For: 209_212 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 46440486.78 | 10927462.29 | 20.87 | 35999352.33 | 10441134.44 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:10 | 7397.32 | 17-JAN-19:02 | 6232.88 | 29-JAN-09:01 | 2849.40 | 11-JAN-19:02 | 1603.68 | 17-JAN-19:02 | 0.00 | 01-JAN-00:10 |
| February | 34685788.30 | 8136150.84 | 12.26 | 28538175.95 | 6147612.34 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:10 | 7344.39 | 01-FEB-09:01 | 6181.70 | 19-FEB-09:01 | 2931.18 | 01-FEB-09:01 | 1593.46 | 01-FEB-09:01 | 0.00 | 01-FEB-00:10 |
| March | 0.885936E+09 | 0.213807E+09 | 196.62 | 0.651576E+09 | 0.234360E+09 | 0.00 | 1.00 | 02-MAR-09:01 | 0.00 | 01-MAR-00:10 | 7993.38 | 14-MAR-20:51 | 6303.58 | 15-MAR-19:21 | 3428.89 | 12-MAR-15:13 | 1709.83 | 14-MAR-20:51 | 0.00 | 01-MAR-00:10 |
| April | 0.154755E+10 | 0.377092E+09 | 415.30 | 0.122185E+10 | 0.325703E+09 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:10 | 7783.50 | 08-APR-18:11 | 6732.53 | 22-APR-17:11 | 2853.97 | 28-APR-15:13 | 1674.31 | 08-APR-18:11 | 0.00 | 01-APR-00:10 |
| May | 0.372223E+10 | 0.892563E+09 | 599.90 | 0.296645E+10 | 0.755781E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-06:51 | 8245.22 | 24-MAY-07:31 | 7164.02 | 23-MAY-16:41 | 3658.69 | 24-MAY-08:56 | 1749.85 | 24-MAY-07:31 | 0.00 | 01-MAY-00:10 |
| June | 0.593452E+10 | 0.139151E+10 | 563.97 | 0.442929E+10 | 0.150523E+10 | 0.00 | 1.00 | 01-JUN-07:41 | 0.00 | 01-JUN-05:11 | 8592.90 | 18-JUN-08:11 | 7199.78 | 03-JUN-17:01 | 4175.97 | 08-JUN-08:54 | 1822.52 | 27-JUN-08:11 | 0.00 | 01-JUN-00:10 |
| July | 0.812290E+10 | 0.189555E+10 | 600.72 | 0.575027E+10 | 0.237263E+10 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 8787.10 | 16-JUL-07:51 | 7015.62 | 06-JUL-16:41 | 4247.56 | 16-JUL-08:15 | 1835.12 | 16-JUL-07:51 | 0.00 | 01-JUL-00:10 |
| August | 0.710309E+10 | 0.166557E+10 | 586.34 | 0.522542E+10 | 0.187766E+10 | 0.00 | 1.00 | 01-AUG-08:51 | 0.00 | 01-AUG-06:51 | 8707.68 | 14-AUG-08:11 | 6916.84 | 22-AUG-16:51 | 4207.20 | 14-AUG-08:15 | 1824.94 | 14-AUG-08:11 | 0.00 | 01-AUG-00:10 |
| September | 0.492387E+10 | 0.116028E+10 | 555.61 | 0.361977E+10 | 0.130410E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 8559.13 | 14-SEP-08:21 | 6718.76 | 22-SEP-16:51 | 3935.15 | 14-SEP-08:27 | 1795.79 | 14-SEP-08:21 | 0.00 | 01-SEP-00:10 |
| October | 0.255585E+10 | 0.618299E+09 | 527.35 | 0.194936E+10 | 0.606492E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 8193.60 | 12-OCT-21:51 | 6096.54 | 21-OCT-21:51 | 3486.50 | 12-OCT-21:57 | 1741.87 | 12-OCT-21:51 | 0.00 | 01-OCT-00:10 |
| November | 0.100165E+10 | 0.244175E+09 | 317.40 | 0.789065E+09 | 0.212584E+09 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-06:51 | 7943.56 | 05-NOV-08:51 | 5985.57 | 25-NOV-19:02 | 3103.53 | 16-NOV-19:16 | 1701.58 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 90928700.36 | 21724056.77 | 41.13 | 67962246.52 | 22966453.84 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 7519.89 | 01-DEC-09:01 | 6063.40 | 23-DEC-09:01 | 3138.56 | 14-DEC-19:03 | 1626.85 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.359696E+11 | 0.849962E+10 | 4437.48 | 0.267355E+11 | 0.923409E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 34685788.30 | 8136150.84 | 12.26 | 28538175.95 | 6147612.34 | 0.00 | 1.00 | 0.00 | 7344.39 | 5985.57 | 2849.40 | 1593.46 | 0.00 | |||||||
| Maximum of Months | 0.812290E+10 | 0.189555E+10 | 600.72 | 0.575027E+10 | 0.237263E+10 | 0.00 | 1.00 | 0.00 | 8787.10 | 7199.78 | 4247.56 | 1835.12 | 0.00 |
Report: DXReportMonthly
For: 213 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 1294293.74 | 315505.64 | 0.98 | 958518.02 | 335775.72 | 0.00 | 0.53 | 11-JAN-19:03 | 0.00 | 01-JAN-00:10 | 981.45 | 11-JAN-19:03 | 611.69 | 11-JAN-09:03 | 414.54 | 11-JAN-19:03 | 230.71 | 11-JAN-19:03 | 0.00 | 01-JAN-00:10 |
| February | 1126875.23 | 273165.24 | 0.81 | 873428.28 | 253446.95 | 0.00 | 0.66 | 01-FEB-09:03 | 0.00 | 01-FEB-00:10 | 1256.25 | 01-FEB-09:03 | 743.69 | 01-FEB-09:03 | 512.56 | 01-FEB-09:03 | 288.89 | 01-FEB-09:03 | 0.00 | 01-FEB-00:10 |
| March | 0.120989E+09 | 29254358.50 | 98.80 | 84952911.34 | 36035998.27 | 0.00 | 1.00 | 11-MAR-09:01 | 0.00 | 01-MAR-00:10 | 2254.37 | 14-MAR-15:12 | 1669.81 | 15-MAR-19:21 | 1100.64 | 12-MAR-15:12 | 480.88 | 14-MAR-15:12 | 0.00 | 01-MAR-00:10 |
| April | 0.176179E+09 | 43082616.83 | 208.73 | 0.131300E+09 | 44879041.26 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:10 | 2190.55 | 30-APR-15:12 | 1706.34 | 23-APR-08:61 | 1028.62 | 30-APR-15:12 | 468.75 | 30-APR-15:12 | 0.00 | 01-APR-00:10 |
| May | 0.730462E+09 | 0.175816E+09 | 497.31 | 0.565642E+09 | 0.164820E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-01:20 | 2252.52 | 24-MAY-08:51 | 1921.90 | 23-MAY-16:41 | 1028.57 | 24-MAY-08:54 | 478.67 | 24-MAY-08:51 | 0.00 | 01-MAY-00:10 |
| June | 0.148750E+10 | 0.348909E+09 | 538.42 | 0.111023E+10 | 0.377272E+09 | 0.00 | 1.00 | 01-JUN-07:41 | 0.00 | 01-JUN-05:11 | 2379.31 | 18-JUN-08:11 | 1949.25 | 03-JUN-17:01 | 1204.25 | 08-JUN-08:53 | 501.94 | 27-JUN-08:11 | 0.00 | 01-JUN-00:10 |
| July | 0.218783E+10 | 0.510208E+09 | 597.54 | 0.157598E+10 | 0.611853E+09 | 0.00 | 1.00 | 01-JUL-07:51 | 0.00 | 01-JUL-06:01 | 2413.38 | 29-JUL-08:31 | 1923.82 | 06-JUL-16:41 | 1218.60 | 29-JUL-08:34 | 505.12 | 16-JUL-08:11 | 0.00 | 01-JUL-00:10 |
| August | 0.188864E+10 | 0.442645E+09 | 578.88 | 0.140670E+10 | 0.481937E+09 | 0.00 | 1.00 | 01-AUG-08:51 | 0.00 | 01-AUG-06:51 | 2400.16 | 14-AUG-08:11 | 1893.93 | 03-AUG-20:31 | 1179.93 | 14-AUG-08:14 | 502.23 | 14-AUG-08:11 | 0.00 | 01-AUG-00:10 |
| September | 0.115831E+10 | 0.273347E+09 | 517.97 | 0.844101E+09 | 0.314208E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 2364.04 | 17-SEP-08:21 | 1818.57 | 22-SEP-16:51 | 1127.14 | 14-SEP-08:24 | 494.96 | 17-SEP-08:21 | 0.00 | 01-SEP-00:10 |
| October | 0.390728E+09 | 94841569.27 | 339.35 | 0.281550E+09 | 0.109178E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 2226.71 | 12-OCT-21:51 | 1629.06 | 25-OCT-20:11 | 1049.07 | 26-OCT-15:12 | 474.61 | 12-OCT-21:51 | 0.00 | 01-OCT-00:10 |
| November | 80368064.68 | 19684055.09 | 104.91 | 59238138.08 | 21129926.59 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 2155.50 | 05-NOV-08:51 | 1518.52 | 12-NOV-09:01 | 870.86 | 16-NOV-19:13 | 462.86 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 1600167.02 | 390366.52 | 1.92 | 1139217.01 | 460950.01 | 0.00 | 0.59 | 14-DEC-09:02 | 0.00 | 01-DEC-00:10 | 1103.56 | 14-DEC-09:02 | 650.60 | 14-DEC-09:02 | 452.96 | 14-DEC-09:02 | 256.89 | 14-DEC-09:02 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.822503E+10 | 0.193877E+10 | 3485.63 | 0.606267E+10 | 0.216236E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 1126875.23 | 273165.24 | 0.81 | 873428.28 | 253446.95 | 0.00 | 0.53 | 0.00 | 981.45 | 611.69 | 414.54 | 230.71 | 0.00 | |||||||
| Maximum of Months | 0.218783E+10 | 0.510208E+09 | 597.54 | 0.157598E+10 | 0.611853E+09 | 0.00 | 1.00 | 0.00 | 2413.38 | 1949.25 | 1218.60 | 505.12 | 0.00 |
Report: DXReportMonthly
For: 214 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 52443581.51 | 12865399.56 | 81.00 | 43676006.96 | 8767574.55 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:10 | 2688.01 | 17-JAN-19:02 | 2399.93 | 12-JAN-16:11 | 941.32 | 11-JAN-19:02 | 582.51 | 17-JAN-19:02 | 0.00 | 01-JAN-00:10 |
| February | 34178631.53 | 8345525.51 | 52.33 | 29206935.28 | 4971696.25 | 0.00 | 1.00 | 12-FEB-09:01 | 0.00 | 01-FEB-00:10 | 2606.21 | 18-FEB-16:12 | 2344.15 | 22-FEB-16:12 | 942.09 | 01-FEB-09:01 | 566.47 | 18-FEB-16:12 | 0.00 | 01-FEB-00:10 |
| March | 0.491958E+09 | 0.119869E+09 | 375.19 | 0.401348E+09 | 90610617.01 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:10 | 2841.62 | 14-MAR-21:31 | 2415.54 | 15-MAR-18:51 | 1014.24 | 11-MAR-16:12 | 610.30 | 14-MAR-21:31 | 0.00 | 01-MAR-00:10 |
| April | 0.830630E+09 | 0.203137E+09 | 565.87 | 0.710505E+09 | 0.120125E+09 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-04:30 | 2742.89 | 08-APR-17:51 | 2574.00 | 07-APR-16:51 | 920.15 | 12-APR-15:13 | 592.79 | 08-APR-17:51 | 0.00 | 01-APR-00:10 |
| May | 0.148252E+10 | 0.357226E+09 | 630.61 | 0.125312E+10 | 0.229392E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-06:51 | 2955.85 | 29-MAY-08:21 | 2647.24 | 23-MAY-16:11 | 1137.38 | 24-MAY-08:55 | 629.04 | 29-MAY-08:21 | 0.00 | 01-MAY-00:10 |
| June | 0.208418E+10 | 0.493501E+09 | 585.97 | 0.165909E+10 | 0.425099E+09 | 0.00 | 1.00 | 01-JUN-06:51 | 0.00 | 01-JUN-05:11 | 3079.17 | 08-JUN-08:61 | 2618.76 | 03-JUN-17:41 | 1399.02 | 08-JUN-08:05 | 648.50 | 17-JUN-08:51 | 0.00 | 01-JUN-00:10 |
| July | 0.279439E+10 | 0.659569E+09 | 617.39 | 0.213477E+10 | 0.659612E+09 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 3127.29 | 16-JUL-07:31 | 2628.67 | 06-JUL-16:11 | 1424.34 | 16-JUL-07:54 | 657.09 | 16-JUL-07:51 | 0.00 | 01-JUL-00:10 |
| August | 0.260200E+10 | 0.614980E+09 | 613.94 | 0.206424E+10 | 0.537758E+09 | 0.00 | 1.00 | 01-AUG-08:41 | 0.00 | 01-AUG-06:51 | 3091.09 | 26-AUG-08:51 | 2661.66 | 01-AUG-16:51 | 1336.63 | 26-AUG-08:56 | 657.77 | 15-AUG-08:41 | 0.00 | 01-AUG-00:10 |
| September | 0.203299E+10 | 0.480503E+09 | 598.84 | 0.163709E+10 | 0.395899E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 3056.05 | 14-SEP-08:41 | 2626.72 | 02-SEP-16:11 | 1296.07 | 14-SEP-08:46 | 644.16 | 14-SEP-08:41 | 0.00 | 01-SEP-00:10 |
| October | 0.127107E+10 | 0.307980E+09 | 649.96 | 0.106311E+10 | 0.207960E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 2896.75 | 12-OCT-21:01 | 2581.94 | 30-OCT-16:11 | 1055.63 | 26-OCT-08:54 | 619.55 | 12-OCT-21:01 | 0.00 | 01-OCT-00:10 |
| November | 0.611657E+09 | 0.150174E+09 | 498.89 | 0.520944E+09 | 90712609.11 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-06:51 | 2851.85 | 05-NOV-08:51 | 2378.53 | 26-NOV-17:51 | 982.44 | 20-NOV-16:12 | 612.05 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 76681462.39 | 18906133.06 | 115.08 | 61938420.30 | 14743042.09 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 2744.35 | 14-DEC-19:02 | 2248.36 | 04-DEC-16:12 | 1144.67 | 14-DEC-16:12 | 593.05 | 14-DEC-19:02 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.143647E+11 | 0.342706E+10 | 5385.06 | 0.115790E+11 | 0.278565E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 34178631.53 | 8345525.51 | 52.33 | 29206935.28 | 4971696.25 | 0.00 | 1.00 | 0.00 | 2606.21 | 2248.36 | 920.15 | 566.47 | 0.00 | |||||||
| Maximum of Months | 0.279439E+10 | 0.659569E+09 | 649.96 | 0.213477E+10 | 0.659612E+09 | 0.00 | 1.00 | 0.00 | 3127.29 | 2661.66 | 1424.34 | 657.77 | 0.00 |
Report: DXReportMonthly
For: 215_218 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.174472E+10 | 0.441163E+09 | 538.83 | 0.174472E+10 | 0.00 | 0.00 | 0.20 | 15-JAN-15:00 | 0.00 | 01-JAN-06:25 | 3224.89 | 15-JAN-15:00 | 3224.89 | 15-JAN-15:00 | 0.00 | 02-JAN-16:00 | 801.02 | 15-JAN-15:00 | 0.00 | 01-JAN-00:10 |
| February | 0.145490E+10 | 0.367882E+09 | 447.17 | 0.145490E+10 | 0.00 | 0.00 | 0.19 | 28-FEB-15:00 | 0.00 | 01-FEB-05:20 | 3020.70 | 28-FEB-15:00 | 3020.70 | 28-FEB-15:00 | 0.00 | 15-FEB-15:18 | 751.01 | 28-FEB-15:00 | 0.00 | 01-FEB-00:10 |
| March | 0.344723E+10 | 0.866579E+09 | 694.07 | 0.344158E+10 | 5647737.20 | 0.00 | 0.28 | 15-MAR-14:10 | 0.00 | 01-MAR-05:30 | 4812.27 | 15-MAR-14:01 | 4812.27 | 15-MAR-14:01 | 115.29 | 16-MAR-15:43 | 1219.42 | 15-MAR-14:01 | 0.00 | 01-MAR-00:10 |
| April | 0.407350E+10 | 0.102215E+10 | 710.95 | 0.407350E+10 | 0.00 | 0.00 | 0.23 | 22-APR-15:02 | 0.00 | 05-APR-06:01 | 3849.15 | 09-APR-14:37 | 3849.15 | 09-APR-14:37 | 0.00 | 30-APR-14:25 | 949.90 | 09-APR-14:40 | 0.00 | 01-APR-00:10 |
| May | 0.553559E+10 | 0.138388E+10 | 744.00 | 0.551932E+10 | 16265516.88 | 0.00 | 0.28 | 14-MAY-15:00 | 0.04 | 12-MAY-07:02 | 4758.06 | 14-MAY-15:00 | 4622.92 | 14-MAY-15:00 | 177.49 | 14-MAY-16:42 | 1205.52 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
| June | 0.676051E+10 | 0.169140E+10 | 720.00 | 0.657762E+10 | 0.182885E+09 | 0.00 | 0.32 | 12-JUN-15:00 | 0.05 | 14-JUN-06:00 | 5568.79 | 27-JUN-15:00 | 5101.15 | 12-JUN-15:00 | 863.76 | 27-JUN-15:00 | 1441.87 | 12-JUN-15:00 | 0.00 | 01-JUN-00:10 |
| July | 0.796272E+10 | 0.200597E+10 | 744.00 | 0.757059E+10 | 0.392133E+09 | 0.00 | 0.34 | 19-JUL-15:00 | 0.08 | 06-JUL-07:02 | 5934.73 | 19-JUL-15:00 | 5335.64 | 19-JUL-15:00 | 801.06 | 20-JUL-15:00 | 1618.89 | 19-JUL-15:00 | 0.00 | 01-JUL-00:10 |
| August | 0.784145E+10 | 0.197082E+10 | 744.00 | 0.760030E+10 | 0.241153E+09 | 0.00 | 0.36 | 13-AUG-15:00 | 0.06 | 31-AUG-07:00 | 6240.35 | 13-AUG-15:00 | 5634.77 | 18-AUG-15:00 | 737.67 | 15-AUG-15:00 | 1661.18 | 13-AUG-15:00 | 0.00 | 01-AUG-00:10 |
| September | 0.695513E+10 | 0.172760E+10 | 720.00 | 0.682837E+10 | 0.126759E+09 | 0.00 | 0.35 | 21-SEP-15:00 | 0.04 | 30-SEP-06:23 | 5970.83 | 21-SEP-15:00 | 5970.83 | 21-SEP-15:00 | 516.00 | 15-SEP-15:00 | 1498.70 | 21-SEP-15:00 | 0.00 | 01-SEP-00:10 |
| October | 0.514355E+10 | 0.128599E+10 | 744.00 | 0.513787E+10 | 5682124.12 | 0.00 | 0.31 | 11-OCT-15:00 | 0.01 | 30-OCT-06:51 | 5377.93 | 11-OCT-15:00 | 5377.93 | 11-OCT-15:00 | 142.84 | 12-OCT-15:01 | 1308.88 | 11-OCT-15:00 | 0.00 | 01-OCT-00:10 |
| November | 0.352238E+10 | 0.886340E+09 | 717.44 | 0.352238E+10 | 0.00 | 0.00 | 0.23 | 03-NOV-15:02 | 0.00 | 24-NOV-06:12 | 3721.71 | 03-NOV-15:02 | 3721.71 | 03-NOV-15:02 | 0.00 | 16-NOV-15:01 | 920.22 | 03-NOV-15:02 | 0.00 | 01-NOV-00:10 |
| December | 0.171215E+10 | 0.433080E+09 | 546.96 | 0.171215E+10 | 0.00 | 0.00 | 0.19 | 16-DEC-13:40 | 0.00 | 02-DEC-06:12 | 3056.04 | 16-DEC-13:40 | 3056.04 | 16-DEC-13:40 | 0.00 | 15-DEC-15:50 | 760.33 | 16-DEC-13:35 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.561538E+11 | 0.140828E+11 | 8071.43 | 0.551833E+11 | 0.970526E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.145490E+10 | 0.367882E+09 | 447.17 | 0.145490E+10 | 0.00 | 0.00 | 0.19 | 0.00 | 3020.70 | 3020.70 | 0.00 | 751.01 | 0.00 | |||||||
| Maximum of Months | 0.796272E+10 | 0.200597E+10 | 744.00 | 0.760030E+10 | 0.392133E+09 | 0.00 | 0.36 | 0.08 | 6240.35 | 5970.83 | 863.76 | 1661.18 | 0.00 |
Report: DXReportMonthly
For: 219 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.546112E+10 | 0.134170E+10 | 739.72 | 0.539729E+10 | 63834016.84 | 0.00 | 1.00 | 15-JAN-09:01 | 0.00 | 01-JAN-07:51 | 9920.67 | 15-JAN-09:01 | 9191.32 | 16-JAN-09:01 | 800.17 | 14-JAN-09:01 | 2158.80 | 15-JAN-09:01 | 0.00 | 01-JAN-00:10 |
| February | 0.480239E+10 | 0.118070E+10 | 667.77 | 0.474426E+10 | 58127731.80 | 0.00 | 0.98 | 01-FEB-09:01 | 0.00 | 01-FEB-07:51 | 9806.00 | 01-FEB-09:01 | 9089.10 | 19-FEB-09:01 | 901.36 | 01-FEB-09:01 | 2139.17 | 01-FEB-09:01 | 0.00 | 01-FEB-00:10 |
| March | 0.652865E+10 | 0.159254E+10 | 736.34 | 0.635347E+10 | 0.175177E+09 | 0.00 | 1.00 | 11-MAR-09:01 | 0.00 | 01-MAR-07:51 | 10669.02 | 15-MAR-08:31 | 10432.05 | 14-MAR-18:51 | 1578.42 | 15-MAR-08:32 | 2305.39 | 15-MAR-08:31 | 0.00 | 01-MAR-00:10 |
| April | 0.683382E+10 | 0.166087E+10 | 711.25 | 0.661177E+10 | 0.222051E+09 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-06:51 | 10517.41 | 08-APR-21:21 | 10218.63 | 07-APR-20:11 | 1198.02 | 08-APR-21:22 | 2277.22 | 08-APR-21:21 | 0.00 | 01-APR-00:10 |
| May | 0.752969E+10 | 0.181975E+10 | 707.70 | 0.718268E+10 | 0.347013E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-06:51 | 10860.72 | 29-MAY-08:21 | 10415.26 | 21-MAY-19:31 | 2063.80 | 24-MAY-08:52 | 2339.92 | 29-MAY-08:21 | 0.00 | 01-MAY-00:10 |
| June | 0.784462E+10 | 0.189585E+10 | 663.13 | 0.727165E+10 | 0.572975E+09 | 0.00 | 1.00 | 01-JUN-06:51 | 0.00 | 01-JUN-05:11 | 11013.96 | 08-JUN-08:61 | 10614.45 | 23-JUN-18:11 | 2551.54 | 08-JUN-08:02 | 2376.67 | 17-JUN-08:51 | 0.00 | 01-JUN-00:10 |
| July | 0.881871E+10 | 0.214633E+10 | 683.01 | 0.798921E+10 | 0.829506E+09 | 0.00 | 1.00 | 01-JUL-08:31 | 0.00 | 01-JUL-06:01 | 11038.39 | 19-JUL-08:41 | 10379.76 | 09-JUL-16:01 | 2592.71 | 16-JUL-08:61 | 2371.38 | 16-JUL-07:51 | 0.00 | 01-JUL-00:10 |
| August | 0.863120E+10 | 0.209435E+10 | 684.25 | 0.793672E+10 | 0.694480E+09 | 0.00 | 1.00 | 01-AUG-08:41 | 0.00 | 01-AUG-06:51 | 11039.83 | 26-AUG-08:51 | 10647.58 | 21-AUG-18:11 | 2483.81 | 15-AUG-08:42 | 2401.90 | 15-AUG-08:41 | 0.00 | 01-AUG-00:10 |
| September | 0.791128E+10 | 0.190225E+10 | 673.39 | 0.737543E+10 | 0.535850E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 11006.03 | 17-SEP-08:51 | 10596.84 | 18-SEP-19:21 | 2453.20 | 17-SEP-08:52 | 2365.29 | 17-SEP-08:51 | 0.00 | 01-SEP-00:10 |
| October | 0.752839E+10 | 0.182307E+10 | 727.45 | 0.720475E+10 | 0.323643E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 10821.63 | 26-OCT-08:51 | 10295.70 | 22-OCT-16:11 | 2072.48 | 26-OCT-08:52 | 2332.97 | 26-OCT-08:51 | 0.00 | 01-OCT-00:10 |
| November | 0.653412E+10 | 0.159123E+10 | 708.87 | 0.634189E+10 | 0.192224E+09 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-06:51 | 10748.46 | 05-NOV-08:51 | 10173.85 | 26-NOV-17:51 | 1857.28 | 05-NOV-08:52 | 2319.84 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 0.552749E+10 | 0.135743E+10 | 739.64 | 0.542746E+10 | 0.100024E+09 | 0.00 | 1.00 | 16-DEC-09:01 | 0.00 | 01-DEC-07:51 | 9976.45 | 01-DEC-09:01 | 9253.66 | 17-DEC-09:01 | 895.69 | 01-DEC-09:01 | 2170.89 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.839515E+11 | 0.204061E+11 | 8442.50 | 0.798366E+11 | 0.411490E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.480239E+10 | 0.118070E+10 | 663.13 | 0.474426E+10 | 58127731.80 | 0.00 | 0.98 | 0.00 | 9806.00 | 9089.10 | 800.17 | 2139.17 | 0.00 | |||||||
| Maximum of Months | 0.881871E+10 | 0.214633E+10 | 739.72 | 0.798921E+10 | 0.829506E+09 | 0.00 | 1.00 | 0.00 | 11039.83 | 10647.58 | 2592.71 | 2401.90 | 0.00 |
Report: DXReportMonthly
For: 220_223 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.292581E+09 | 71073001.79 | 116.68 | 0.249829E+09 | 42751628.74 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:10 | 9398.32 | 11-JAN-16:12 | 8387.65 | 12-JAN-16:11 | 3359.71 | 14-JAN-16:12 | 2036.59 | 11-JAN-16:12 | 0.00 | 01-JAN-00:10 |
| February | 0.245950E+09 | 59665382.07 | 89.75 | 0.214487E+09 | 31462726.17 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:10 | 9360.32 | 01-FEB-09:01 | 8436.11 | 22-FEB-16:12 | 3683.79 | 01-FEB-16:12 | 2029.33 | 01-FEB-09:01 | 0.00 | 01-FEB-00:10 |
| March | 0.192126E+10 | 0.468874E+09 | 442.25 | 0.157648E+10 | 0.344783E+09 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:10 | 9952.47 | 14-MAR-21:31 | 8387.65 | 01-MAR-16:12 | 3516.10 | 11-MAR-16:13 | 2136.58 | 14-MAR-21:31 | 0.00 | 01-MAR-00:10 |
| April | 0.297462E+10 | 0.727568E+09 | 586.11 | 0.252179E+10 | 0.452829E+09 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-03:10 | 9664.64 | 08-APR-21:21 | 9048.58 | 07-APR-16:51 | 3022.20 | 12-APR-15:13 | 2086.05 | 08-APR-21:21 | 0.00 | 01-APR-00:10 |
| May | 0.494230E+10 | 0.119295E+10 | 629.98 | 0.409165E+10 | 0.850650E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-06:51 | 10369.39 | 29-MAY-08:21 | 9219.30 | 23-MAY-16:11 | 4122.14 | 24-MAY-08:56 | 2204.55 | 29-MAY-08:21 | 0.00 | 01-MAY-00:10 |
| June | 0.666922E+10 | 0.158558E+10 | 579.86 | 0.510631E+10 | 0.156290E+10 | 0.00 | 1.00 | 01-JUN-06:51 | 0.00 | 01-JUN-05:11 | 10800.24 | 08-JUN-08:61 | 9126.28 | 03-JUN-16:21 | 4978.32 | 08-JUN-08:06 | 2274.90 | 27-JUN-07:41 | 0.00 | 01-JUN-00:10 |
| July | 0.884339E+10 | 0.209827E+10 | 613.79 | 0.641644E+10 | 0.242695E+10 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 10999.05 | 16-JUL-07:31 | 9086.74 | 06-JUL-16:11 | 5166.83 | 16-JUL-07:54 | 2305.94 | 16-JUL-07:51 | 0.00 | 01-JUL-00:10 |
| August | 0.817503E+10 | 0.194336E+10 | 608.44 | 0.620226E+10 | 0.197277E+10 | 0.00 | 1.00 | 01-AUG-08:41 | 0.00 | 01-AUG-06:51 | 10882.29 | 14-AUG-07:41 | 9110.73 | 22-AUG-16:01 | 4899.97 | 15-AUG-08:47 | 2311.61 | 15-AUG-08:41 | 0.00 | 01-AUG-00:10 |
| September | 0.652858E+10 | 0.154927E+10 | 594.43 | 0.506946E+10 | 0.145912E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 10776.79 | 15-SEP-21:31 | 9069.36 | 02-SEP-16:11 | 4751.28 | 15-SEP-21:37 | 2265.06 | 15-SEP-21:31 | 0.00 | 01-SEP-00:10 |
| October | 0.437114E+10 | 0.105979E+10 | 652.36 | 0.359611E+10 | 0.775032E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 10140.66 | 12-OCT-21:01 | 9038.41 | 30-OCT-16:11 | 3777.05 | 26-OCT-08:55 | 2168.02 | 12-OCT-21:01 | 0.00 | 01-OCT-00:10 |
| November | 0.228097E+10 | 0.559202E+09 | 513.61 | 0.193441E+10 | 0.346563E+09 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-06:51 | 10033.82 | 05-NOV-07:51 | 8252.58 | 26-NOV-17:51 | 3375.81 | 20-NOV-16:12 | 2150.33 | 05-NOV-07:51 | 0.00 | 01-NOV-00:10 |
| December | 0.380797E+09 | 93059420.37 | 141.21 | 0.313039E+09 | 67758609.87 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-07:51 | 9581.04 | 14-DEC-19:02 | 8002.73 | 04-DEC-16:12 | 3868.05 | 14-DEC-16:12 | 2070.80 | 14-DEC-19:02 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.476258E+11 | 0.114087E+11 | 5568.47 | 0.372923E+11 | 0.103336E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.245950E+09 | 59665382.07 | 89.75 | 0.214487E+09 | 31462726.17 | 0.00 | 1.00 | 0.00 | 9360.32 | 8002.73 | 3022.20 | 2029.33 | 0.00 | |||||||
| Maximum of Months | 0.884339E+10 | 0.209827E+10 | 652.36 | 0.641644E+10 | 0.242695E+10 | 0.00 | 1.00 | 0.00 | 10999.05 | 9219.30 | 5166.83 | 2311.61 | 0.00 |
Report: DXReportMonthly
For: 224 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 21677501.05 | 5291937.45 | 36.02 | 17611675.23 | 4065825.82 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:10 | 2657.43 | 17-JAN-19:02 | 2367.25 | 12-JAN-16:11 | 886.16 | 17-JAN-19:02 | 575.73 | 17-JAN-19:02 | 0.00 | 01-JAN-00:10 |
| February | 14857336.60 | 3634376.43 | 26.55 | 12605851.04 | 2251485.56 | 0.00 | 1.00 | 12-FEB-09:01 | 0.00 | 01-FEB-00:10 | 2587.87 | 18-FEB-16:12 | 2228.21 | 19-FEB-09:01 | 694.25 | 18-FEB-16:12 | 562.19 | 18-FEB-16:12 | 0.00 | 01-FEB-00:10 |
| March | 0.378093E+09 | 92021428.96 | 294.68 | 0.300347E+09 | 77746120.01 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:10 | 2794.96 | 14-MAR-21:31 | 2367.01 | 15-MAR-18:51 | 1105.92 | 11-MAR-16:12 | 600.62 | 14-MAR-21:31 | 0.00 | 01-MAR-00:10 |
| April | 0.687468E+09 | 0.168331E+09 | 506.09 | 0.578825E+09 | 0.108643E+09 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-01:05 | 2723.55 | 28-APR-15:12 | 2522.41 | 07-APR-16:51 | 979.55 | 28-APR-15:13 | 588.00 | 28-APR-15:12 | 0.00 | 01-APR-00:10 |
| May | 0.134207E+10 | 0.324175E+09 | 619.10 | 0.112135E+10 | 0.220714E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-06:51 | 2916.98 | 29-MAY-08:21 | 2611.22 | 23-MAY-16:11 | 1146.65 | 24-MAY-08:55 | 620.69 | 29-MAY-08:21 | 0.00 | 01-MAY-00:10 |
| June | 0.193888E+10 | 0.460324E+09 | 577.61 | 0.152466E+10 | 0.414223E+09 | 0.00 | 1.00 | 01-JUN-06:51 | 0.00 | 01-JUN-05:11 | 3039.91 | 08-JUN-08:61 | 2582.65 | 03-JUN-17:41 | 1402.78 | 08-JUN-08:05 | 640.64 | 17-JUN-08:51 | 0.00 | 01-JUN-00:10 |
| July | 0.264599E+10 | 0.626080E+09 | 616.43 | 0.199799E+10 | 0.648006E+09 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 3089.44 | 16-JUL-07:31 | 2589.09 | 06-JUL-16:11 | 1419.99 | 16-JUL-07:54 | 648.79 | 16-JUL-07:51 | 0.00 | 01-JUL-00:10 |
| August | 0.245987E+10 | 0.582846E+09 | 611.45 | 0.193204E+10 | 0.527835E+09 | 0.00 | 1.00 | 01-AUG-08:41 | 0.00 | 01-AUG-06:51 | 3056.81 | 26-AUG-08:51 | 2592.94 | 22-AUG-16:01 | 1341.43 | 26-AUG-08:56 | 649.61 | 15-AUG-08:41 | 0.00 | 01-AUG-00:10 |
| September | 0.190941E+10 | 0.452305E+09 | 593.16 | 0.152251E+10 | 0.386901E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 3025.65 | 15-SEP-21:31 | 2585.11 | 02-SEP-16:11 | 1301.98 | 14-SEP-08:46 | 637.01 | 15-SEP-21:31 | 0.00 | 01-SEP-00:10 |
| October | 0.113849E+10 | 0.276255E+09 | 630.85 | 0.939756E+09 | 0.198732E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 2863.00 | 12-OCT-21:01 | 2529.65 | 30-OCT-16:11 | 1066.34 | 26-OCT-08:54 | 612.04 | 12-OCT-21:01 | 0.00 | 01-OCT-00:10 |
| November | 0.484877E+09 | 0.119116E+09 | 426.18 | 0.406535E+09 | 78342157.11 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-06:51 | 2811.14 | 05-NOV-08:51 | 2299.52 | 25-NOV-19:02 | 1057.77 | 20-NOV-16:12 | 603.39 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 34975489.41 | 8601117.07 | 59.46 | 27601217.10 | 7374272.31 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 2714.42 | 14-DEC-19:02 | 2171.77 | 04-DEC-16:12 | 1217.60 | 14-DEC-19:02 | 586.34 | 14-DEC-19:02 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.130567E+11 | 0.311898E+10 | 4997.56 | 0.103818E+11 | 0.267483E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 14857336.60 | 3634376.43 | 26.55 | 12605851.04 | 2251485.56 | 0.00 | 1.00 | 0.00 | 2587.87 | 2171.77 | 694.25 | 562.19 | 0.00 | |||||||
| Maximum of Months | 0.264599E+10 | 0.626080E+09 | 630.85 | 0.199799E+10 | 0.648006E+09 | 0.00 | 1.00 | 0.00 | 3089.44 | 2611.22 | 1419.99 | 649.61 | 0.00 |
Report: DXReportMonthly
For: 301 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 2874198.80 | 764995.97 | 13.52 | 1947409.74 | 926789.06 | 0.00 | 0.12 | 12-JUN-14:02 | 0.00 | 01-JUN-00:10 | 217.17 | 12-JUN-14:02 | 169.72 | 12-JUN-14:02 | 68.46 | 27-JUN-14:02 | 60.05 | 12-JUN-14:02 | 0.00 | 01-JUN-00:10 |
| July | 17834704.88 | 4725900.76 | 52.97 | 11050725.78 | 6783979.10 | 0.00 | 0.20 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 | 379.72 | 21-JUL-14:02 | 243.78 | 21-JUL-14:02 | 136.07 | 20-JUL-14:02 | 102.97 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 |
| August | 2988921.48 | 819491.16 | 14.00 | 2402817.92 | 586103.56 | 0.00 | 0.10 | 10-AUG-14:01 | 0.00 | 01-AUG-00:10 | 172.97 | 10-AUG-14:01 | 150.24 | 05-AUG-14:06 | 46.90 | 13-AUG-14:10 | 48.05 | 10-AUG-14:01 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 23697825.15 | 6310387.90 | 80.50 | 15400953.44 | 8296871.72 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 17834704.88 | 4725900.76 | 52.97 | 11050725.78 | 6783979.10 | 0.00 | 0.20 | 0.00 | 379.72 | 243.78 | 136.07 | 102.97 | 0.00 |
Report: DXReportMonthly
For: 302_305 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 3917466.29 | 1046694.52 | 8.17 | 2841935.85 | 1075530.44 | 0.00 | 0.13 | 12-JUN-14:40 | 0.00 | 01-JUN-00:10 | 533.87 | 12-JUN-14:40 | 433.55 | 12-JUN-14:40 | 173.49 | 27-JUN-14:02 | 146.92 | 12-JUN-14:40 | 0.00 | 01-JUN-00:10 |
| July | 32987280.55 | 8735026.84 | 42.83 | 20616786.71 | 12370493.84 | 0.00 | 0.22 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 | 1023.22 | 21-JUL-14:02 | 629.92 | 21-JUL-14:02 | 393.30 | 21-JUL-14:02 | 273.32 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 |
| August | 4447345.10 | 1212643.55 | 6.48 | 3569706.20 | 877638.90 | 0.00 | 0.12 | 10-AUG-14:08 | 0.00 | 01-AUG-00:10 | 512.57 | 10-AUG-14:08 | 424.27 | 10-AUG-14:08 | 118.21 | 14-AUG-14:35 | 142.17 | 10-AUG-14:08 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 41352091.93 | 10994364.91 | 57.47 | 27028428.76 | 14323663.17 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 32987280.55 | 8735026.84 | 42.83 | 20616786.71 | 12370493.84 | 0.00 | 0.22 | 0.00 | 1023.22 | 629.92 | 393.30 | 273.32 | 0.00 |
Report: DXReportMonthly
For: 306_308 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 1115741.16 | 307866.03 | 1.11 | 906842.97 | 208898.19 | 0.00 | 0.15 | 12-JUN-14:15 | 0.00 | 01-JUN-00:10 | 494.83 | 12-JUN-14:15 | 404.10 | 12-JUN-14:15 | 90.73 | 12-JUN-14:15 | 136.07 | 12-JUN-14:15 | 0.00 | 01-JUN-00:10 |
| July | 11132176.40 | 2949256.12 | 18.58 | 6760353.96 | 4371822.43 | 0.00 | 0.21 | 27-JUL-14:35 | 0.00 | 01-JUL-00:10 | 720.75 | 21-JUL-14:02 | 514.49 | 27-JUL-14:35 | 296.96 | 21-JUL-14:02 | 191.61 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 |
| August | 1003796.22 | 275919.12 | 2.58 | 821103.20 | 182693.02 | 0.00 | 0.08 | 10-AUG-14:35 | 0.00 | 01-AUG-00:10 | 262.18 | 10-AUG-14:35 | 216.55 | 10-AUG-14:35 | 45.62 | 10-AUG-14:35 | 72.74 | 10-AUG-14:35 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 13251713.78 | 3533041.27 | 22.27 | 8488300.13 | 4763413.65 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 11132176.40 | 2949256.12 | 18.58 | 6760353.96 | 4371822.43 | 0.00 | 0.21 | 0.00 | 720.75 | 514.49 | 296.96 | 191.61 | 0.00 |
Report: DXReportMonthly
For: 309_312 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 16721164.66 | 3902023.91 | 6.21 | 12595047.83 | 4126116.84 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:10 | 7183.80 | 17-JAN-19:02 | 5683.42 | 22-JAN-09:01 | 2780.40 | 11-JAN-19:02 | 1558.74 | 17-JAN-19:02 | 0.00 | 01-JAN-00:10 |
| February | 13576579.82 | 3245321.07 | 5.28 | 11151832.37 | 2424747.45 | 0.00 | 1.00 | 12-FEB-09:01 | 0.00 | 01-FEB-00:10 | 6719.72 | 19-FEB-19:02 | 5924.35 | 19-FEB-09:01 | 1801.15 | 23-FEB-09:01 | 1462.98 | 19-FEB-19:02 | 0.00 | 01-FEB-00:10 |
| March | 0.718023E+09 | 0.172891E+09 | 151.31 | 0.518428E+09 | 0.199595E+09 | 0.00 | 1.00 | 09-MAR-09:01 | 0.00 | 01-MAR-00:10 | 7832.67 | 14-MAR-18:51 | 6164.81 | 15-MAR-19:21 | 3500.42 | 12-MAR-15:13 | 1675.05 | 14-MAR-18:51 | 0.00 | 01-MAR-00:10 |
| April | 0.123100E+10 | 0.299171E+09 | 328.30 | 0.958698E+09 | 0.272305E+09 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:10 | 7614.78 | 08-APR-18:11 | 6507.22 | 22-APR-17:11 | 2968.57 | 28-APR-15:13 | 1638.20 | 08-APR-18:11 | 0.00 | 01-APR-00:10 |
| May | 0.340313E+10 | 0.814649E+09 | 572.30 | 0.268502E+10 | 0.718104E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-03:30 | 8071.49 | 24-MAY-07:31 | 7002.72 | 23-MAY-16:41 | 3625.36 | 24-MAY-08:56 | 1712.95 | 24-MAY-07:31 | 0.00 | 01-MAY-00:10 |
| June | 0.574330E+10 | 0.134467E+10 | 556.81 | 0.425635E+10 | 0.148696E+10 | 0.00 | 1.00 | 01-JUN-07:41 | 0.00 | 01-JUN-05:11 | 8441.75 | 18-JUN-08:11 | 7020.14 | 03-JUN-17:01 | 4192.34 | 08-JUN-08:54 | 1789.32 | 27-JUN-08:11 | 0.00 | 01-JUN-00:10 |
| July | 0.791539E+10 | 0.184545E+10 | 597.64 | 0.556305E+10 | 0.235234E+10 | 0.00 | 1.00 | 01-JUL-07:51 | 0.00 | 01-JUL-06:01 | 8627.77 | 16-JUL-07:51 | 6847.35 | 06-JUL-16:41 | 4281.43 | 16-JUL-08:14 | 1802.12 | 16-JUL-08:11 | 0.00 | 01-JUL-00:10 |
| August | 0.675975E+10 | 0.158520E+10 | 580.74 | 0.492062E+10 | 0.183912E+10 | 0.00 | 1.00 | 01-AUG-08:51 | 0.00 | 01-AUG-06:51 | 8578.90 | 14-AUG-08:11 | 6727.84 | 22-AUG-16:51 | 4262.15 | 14-AUG-08:15 | 1793.50 | 14-AUG-08:11 | 0.00 | 01-AUG-00:10 |
| September | 0.436903E+10 | 0.102937E+10 | 537.66 | 0.313858E+10 | 0.123045E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 8421.14 | 17-SEP-08:21 | 6509.01 | 22-SEP-16:51 | 3979.70 | 14-SEP-08:26 | 1763.79 | 17-SEP-08:21 | 0.00 | 01-SEP-00:10 |
| October | 0.179678E+10 | 0.434079E+09 | 404.36 | 0.131433E+10 | 0.482442E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 8020.30 | 12-OCT-21:51 | 5859.76 | 21-OCT-21:51 | 3492.96 | 26-OCT-15:13 | 1705.05 | 12-OCT-21:51 | 0.00 | 01-OCT-00:10 |
| November | 0.535170E+09 | 0.130080E+09 | 174.95 | 0.406511E+09 | 0.128659E+09 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:50 | 7741.93 | 05-NOV-08:51 | 5655.17 | 18-NOV-09:01 | 3144.39 | 20-NOV-19:02 | 1659.97 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 28998340.53 | 6843649.81 | 10.72 | 21214922.26 | 7783418.28 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 7359.82 | 01-DEC-09:01 | 5812.66 | 23-DEC-09:01 | 3227.31 | 14-DEC-19:02 | 1592.26 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.325309E+11 | 0.766956E+10 | 3926.26 | 0.238066E+11 | 0.872431E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 13576579.82 | 3245321.07 | 5.28 | 11151832.37 | 2424747.45 | 0.00 | 1.00 | 0.00 | 6719.72 | 5655.17 | 1801.15 | 1462.98 | 0.00 | |||||||
| Maximum of Months | 0.791539E+10 | 0.184545E+10 | 597.64 | 0.556305E+10 | 0.235234E+10 | 0.00 | 1.00 | 0.00 | 8627.77 | 7020.14 | 4281.43 | 1802.12 | 0.00 |
Report: DXReportMonthly
For: 313 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 163729.46 | 45657.63 | 0.62 | 139838.76 | 23890.71 | 0.00 | 0.04 | 12-JUN-15:00 | 0.00 | 01-JUN-00:10 | 76.51 | 12-JUN-15:00 | 65.18 | 12-JUN-15:00 | 11.33 | 12-JUN-15:00 | 21.27 | 12-JUN-15:00 | 0.00 | 01-JUN-00:10 |
| July | 2280804.20 | 608761.57 | 5.56 | 1396836.92 | 883967.28 | 0.00 | 0.15 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 | 304.71 | 21-JUL-14:02 | 172.98 | 21-JUL-14:02 | 131.73 | 21-JUL-14:02 | 81.26 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 |
| August | 71363.97 | 19896.53 | 0.67 | 62978.05 | 8385.92 | 0.00 | 0.02 | 10-AUG-14:50 | 0.00 | 01-AUG-00:10 | 37.33 | 10-AUG-14:50 | 32.25 | 10-AUG-14:50 | 5.08 | 10-AUG-14:50 | 10.45 | 10-AUG-14:50 | 0.00 | 01-AUG-00:10 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 2515897.63 | 674315.73 | 6.85 | 1599653.73 | 916243.90 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 2280804.20 | 608761.57 | 5.56 | 1396836.92 | 883967.28 | 0.00 | 0.15 | 0.00 | 304.71 | 172.98 | 131.73 | 81.26 | 0.00 |
Report: DXReportMonthly
For: 314 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 6212532.63 | 1507388.65 | 12.81 | 4897384.85 | 1315147.78 | 0.00 | 1.00 | 15-JAN-16:12 | 0.00 | 01-JAN-00:10 | 2449.33 | 15-JAN-16:12 | 1909.11 | 15-JAN-19:02 | 698.92 | 17-JAN-19:02 | 531.70 | 15-JAN-16:12 | 0.00 | 01-JAN-00:10 |
| February | 4143776.56 | 1001556.33 | 5.95 | 3471041.42 | 672735.15 | 0.00 | 1.00 | 18-FEB-16:12 | 0.00 | 01-FEB-00:10 | 2390.23 | 18-FEB-16:12 | 2028.55 | 28-FEB-16:12 | 662.57 | 18-FEB-16:12 | 519.85 | 18-FEB-16:12 | 0.00 | 01-FEB-00:10 |
| March | 0.268698E+09 | 65038557.94 | 182.33 | 0.207124E+09 | 61574066.26 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 2656.11 | 12-MAR-15:12 | 2221.33 | 15-MAR-18:51 | 1121.58 | 12-MAR-15:13 | 569.32 | 12-MAR-15:12 | 0.00 | 01-MAR-00:10 |
| April | 0.494019E+09 | 0.120601E+09 | 390.61 | 0.408045E+09 | 85974218.20 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:10 | 2605.82 | 29-APR-15:12 | 2341.22 | 07-APR-16:51 | 1096.92 | 29-APR-15:13 | 560.71 | 29-APR-15:12 | 0.00 | 01-APR-00:10 |
| May | 0.118248E+10 | 0.284784E+09 | 603.45 | 0.975249E+09 | 0.207232E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-06:51 | 2732.72 | 29-MAY-08:21 | 2445.54 | 23-MAY-16:11 | 1083.11 | 24-MAY-08:55 | 581.78 | 29-MAY-08:21 | 0.00 | 01-MAY-00:10 |
| June | 0.189918E+10 | 0.448368E+09 | 572.48 | 0.148587E+10 | 0.413308E+09 | 0.00 | 1.00 | 01-JUN-06:51 | 0.00 | 01-JUN-05:11 | 2852.87 | 08-JUN-08:61 | 2419.42 | 03-JUN-17:41 | 1354.40 | 08-JUN-08:05 | 602.75 | 27-JUN-07:41 | 0.00 | 01-JUN-00:10 |
| July | 0.264091E+10 | 0.621175E+09 | 612.80 | 0.198942E+10 | 0.651494E+09 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 2906.77 | 16-JUL-07:31 | 2424.52 | 06-JUL-16:11 | 1348.56 | 16-JUL-07:54 | 609.92 | 16-JUL-07:51 | 0.00 | 01-JUL-00:10 |
| August | 0.239272E+10 | 0.564390E+09 | 605.56 | 0.186833E+10 | 0.524388E+09 | 0.00 | 1.00 | 01-AUG-08:41 | 0.00 | 01-AUG-06:51 | 2882.51 | 26-AUG-08:51 | 2443.70 | 01-AUG-16:51 | 1288.80 | 26-AUG-08:55 | 611.03 | 15-AUG-08:41 | 0.00 | 01-AUG-00:10 |
| September | 0.171034E+10 | 0.404259E+09 | 577.44 | 0.133889E+10 | 0.371446E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 2848.00 | 14-SEP-08:41 | 2408.12 | 10-SEP-16:11 | 1253.44 | 14-SEP-08:45 | 599.07 | 14-SEP-08:41 | 0.00 | 01-SEP-00:10 |
| October | 0.769275E+09 | 0.186367E+09 | 488.26 | 0.608699E+09 | 0.160576E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 2692.69 | 12-OCT-21:01 | 2339.41 | 11-OCT-16:01 | 1159.59 | 26-OCT-15:13 | 575.37 | 12-OCT-21:01 | 0.00 | 01-OCT-00:10 |
| November | 0.231202E+09 | 56688989.94 | 241.87 | 0.185959E+09 | 45243453.69 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-06:51 | 2647.47 | 04-NOV-18:11 | 2080.94 | 25-NOV-19:02 | 1136.97 | 20-NOV-19:02 | 567.87 | 04-NOV-18:11 | 0.00 | 01-NOV-00:10 |
| December | 6911844.34 | 1672466.71 | 11.35 | 5279486.29 | 1632358.06 | 0.00 | 1.00 | 16-DEC-09:01 | 0.00 | 01-DEC-00:10 | 2478.23 | 16-DEC-16:12 | 1881.00 | 17-DEC-09:01 | 799.83 | 01-DEC-09:01 | 537.32 | 16-DEC-16:12 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.116061E+11 | 0.275585E+10 | 4304.91 | 0.908124E+10 | 0.252486E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 4143776.56 | 1001556.33 | 5.95 | 3471041.42 | 672735.15 | 0.00 | 1.00 | 0.00 | 2390.23 | 1881.00 | 662.57 | 519.85 | 0.00 | |||||||
| Maximum of Months | 0.264091E+10 | 0.621175E+09 | 612.80 | 0.198942E+10 | 0.651494E+09 | 0.00 | 1.00 | 0.00 | 2906.77 | 2445.54 | 1354.40 | 611.03 | 0.00 |
Report: DXReportMonthly
For: 315_318 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.799638E+09 | 0.197060E+09 | 282.25 | 0.716164E+09 | 83473558.90 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-01:20 | 10312.76 | 11-JAN-16:12 | 9162.20 | 12-JAN-16:11 | 3270.47 | 14-JAN-16:12 | 2233.50 | 11-JAN-16:12 | 0.00 | 01-JAN-00:10 |
| February | 0.701183E+09 | 0.172605E+09 | 242.38 | 0.631129E+09 | 70054721.91 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:10 | 10241.39 | 01-FEB-16:12 | 9347.72 | 22-FEB-16:12 | 3485.06 | 01-FEB-16:12 | 2219.92 | 01-FEB-16:12 | 0.00 | 01-FEB-00:10 |
| March | 0.319631E+10 | 0.780690E+09 | 577.10 | 0.277185E+10 | 0.424464E+09 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-01:20 | 10783.11 | 14-MAR-21:31 | 9545.93 | 15-MAR-19:41 | 3141.90 | 14-MAR-21:37 | 2318.69 | 14-MAR-21:31 | 0.00 | 01-MAR-00:10 |
| April | 0.444909E+10 | 0.108445E+10 | 656.16 | 0.390956E+10 | 0.539529E+09 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-06:51 | 10519.50 | 08-APR-21:21 | 9924.84 | 07-APR-16:51 | 2610.13 | 08-APR-21:26 | 2271.86 | 08-APR-21:21 | 0.00 | 01-APR-00:10 |
| May | 0.660993E+10 | 0.158681E+10 | 651.96 | 0.565995E+10 | 0.949979E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-06:51 | 11221.08 | 29-MAY-08:21 | 10261.84 | 23-MAY-17:01 | 4175.57 | 24-MAY-08:57 | 2391.47 | 29-MAY-08:21 | 0.00 | 01-MAY-00:10 |
| June | 0.844589E+10 | 0.199810E+10 | 593.73 | 0.673727E+10 | 0.170862E+10 | 0.00 | 1.00 | 01-JUN-06:51 | 0.00 | 01-JUN-05:11 | 11700.03 | 18-JUN-07:32 | 10307.54 | 30-JUN-17:42 | 4998.99 | 08-JUN-08:06 | 2467.72 | 18-JUN-07:32 | 0.00 | 01-JUN-00:10 |
| July | 0.107931E+11 | 0.254947E+10 | 620.43 | 0.817919E+10 | 0.261393E+10 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 11943.96 | 16-JUL-07:31 | 10300.11 | 06-JUL-17:01 | 5196.54 | 16-JUL-07:54 | 2501.62 | 16-JUL-07:31 | 0.00 | 01-JUL-00:10 |
| August | 0.999528E+10 | 0.236517E+10 | 616.94 | 0.787123E+10 | 0.212406E+10 | 0.00 | 1.00 | 01-AUG-08:41 | 0.00 | 01-AUG-06:51 | 11811.38 | 15-AUG-08:21 | 10338.13 | 01-AUG-16:51 | 4910.63 | 15-AUG-08:47 | 2508.48 | 15-AUG-08:21 | 0.00 | 01-AUG-00:10 |
| September | 0.807824E+10 | 0.190879E+10 | 603.51 | 0.649633E+10 | 0.158191E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 11630.50 | 17-SEP-08:31 | 10317.26 | 22-SEP-16:51 | 4720.65 | 14-SEP-08:47 | 2453.90 | 17-SEP-08:31 | 0.00 | 01-SEP-00:10 |
| October | 0.560799E+10 | 0.135582E+10 | 681.22 | 0.475311E+10 | 0.854875E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 10981.86 | 12-OCT-21:01 | 10257.41 | 11-OCT-16:52 | 3875.79 | 26-OCT-08:55 | 2352.49 | 12-OCT-21:01 | 0.00 | 01-OCT-00:10 |
| November | 0.327502E+10 | 0.802748E+09 | 619.12 | 0.286080E+10 | 0.414220E+09 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-06:51 | 10943.30 | 05-NOV-08:51 | 9456.10 | 26-NOV-17:51 | 3458.43 | 05-NOV-08:57 | 2346.03 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 0.911027E+09 | 0.224637E+09 | 299.20 | 0.786144E+09 | 0.124883E+09 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-07:51 | 10390.19 | 14-DEC-16:12 | 9162.20 | 26-DEC-16:11 | 3617.97 | 14-DEC-16:12 | 2248.03 | 14-DEC-16:12 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.628627E+11 | 0.150264E+11 | 6444.01 | 0.513727E+11 | 0.114900E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.701183E+09 | 0.172605E+09 | 242.38 | 0.631129E+09 | 70054721.91 | 0.00 | 1.00 | 0.00 | 10241.39 | 9162.20 | 2610.13 | 2219.92 | 0.00 | |||||||
| Maximum of Months | 0.107931E+11 | 0.254947E+10 | 681.22 | 0.817919E+10 | 0.261393E+10 | 0.00 | 1.00 | 0.00 | 11943.96 | 10338.13 | 5196.54 | 2508.48 | 0.00 |
Report: DXReportMonthly
For: 319 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 2611635.27 | 674498.72 | 11.80 | 2584896.69 | 26738.58 | 0.00 | 0.12 | 15-MAR-14:02 | 0.00 | 01-MAR-00:10 | 221.39 | 15-MAR-14:02 | 221.15 | 15-MAR-14:02 | 5.51 | 14-MAR-14:07 | 57.50 | 15-MAR-14:02 | 0.00 | 01-MAR-00:10 |
| April | 4973.66 | 1271.71 | 0.45 | 4973.66 | 0.00 | 0.00 | 0.00 | 09-APR-16:00 | 0.00 | 01-APR-00:10 | 6.93 | 09-APR-16:00 | 6.93 | 09-APR-16:00 | 0.00 | 09-APR-16:00 | 1.77 | 09-APR-16:00 | 0.00 | 01-APR-00:10 |
| May | 6544154.71 | 1676617.57 | 54.19 | 6464329.07 | 79825.64 | 0.00 | 0.11 | 14-MAY-14:30 | 0.00 | 01-MAY-00:10 | 208.31 | 14-MAY-14:30 | 201.79 | 14-MAY-14:30 | 7.94 | 14-MAY-15:00 | 53.65 | 14-MAY-14:30 | 0.00 | 01-MAY-00:10 |
| June | 77510972.08 | 19857474.42 | 274.09 | 66675778.34 | 10835193.74 | 0.00 | 0.19 | 12-JUN-14:10 | 0.00 | 01-JUN-00:10 | 359.83 | 12-JUN-14:10 | 327.94 | 12-JUN-14:02 | 94.53 | 27-JUN-14:10 | 99.40 | 12-JUN-14:10 | 0.00 | 01-JUN-00:10 |
| July | 0.170418E+09 | 43919499.58 | 407.03 | 0.140434E+09 | 29984043.53 | 0.00 | 0.22 | 19-JUL-14:20 | 0.00 | 01-JUL-00:10 | 443.56 | 19-JUL-14:20 | 363.32 | 19-JUL-14:02 | 102.16 | 20-JUL-15:00 | 121.15 | 19-JUL-14:40 | 0.00 | 01-JUL-00:10 |
| August | 0.162533E+09 | 42015644.82 | 374.64 | 0.145544E+09 | 16989744.65 | 0.00 | 0.23 | 18-AUG-14:10 | 0.00 | 01-AUG-00:10 | 458.81 | 13-AUG-15:00 | 419.58 | 18-AUG-14:02 | 116.23 | 14-AUG-14:30 | 123.25 | 13-AUG-15:00 | 0.00 | 01-AUG-00:10 |
| September | 99641348.26 | 25155782.84 | 275.06 | 91904507.84 | 7736840.42 | 0.00 | 0.23 | 21-SEP-14:01 | 0.00 | 01-SEP-00:10 | 443.10 | 21-SEP-14:01 | 443.10 | 21-SEP-14:01 | 64.12 | 15-SEP-11:25 | 112.57 | 21-SEP-14:13 | 0.00 | 01-SEP-00:10 |
| October | 9983795.85 | 2523536.42 | 37.06 | 9974045.66 | 9750.20 | 0.00 | 0.13 | 11-OCT-14:25 | 0.00 | 01-OCT-00:10 | 256.47 | 11-OCT-14:25 | 256.47 | 11-OCT-14:25 | 3.08 | 12-OCT-15:07 | 64.20 | 11-OCT-14:25 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.529248E+09 | 0.135824E+09 | 1434.32 | 0.463586E+09 | 65662136.75 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.170418E+09 | 43919499.58 | 407.03 | 0.145544E+09 | 29984043.53 | 0.00 | 0.23 | 0.00 | 458.81 | 443.10 | 116.23 | 123.25 | 0.00 |
Report: DXReportMonthly
For: 320_323 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.129117E+09 | 30974583.72 | 52.17 | 0.108900E+09 | 20217273.79 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:10 | 8968.01 | 17-JAN-19:02 | 8008.33 | 12-JAN-16:11 | 3235.96 | 11-JAN-19:02 | 1943.49 | 17-JAN-19:02 | 0.00 | 01-JAN-00:10 |
| February | 0.131445E+09 | 31630454.93 | 50.84 | 0.114862E+09 | 16583518.78 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:10 | 8914.65 | 01-FEB-09:01 | 8093.91 | 22-FEB-16:12 | 3396.85 | 01-FEB-09:01 | 1933.25 | 01-FEB-09:01 | 0.00 | 01-FEB-00:10 |
| March | 0.140557E+10 | 0.341807E+09 | 325.22 | 0.112223E+10 | 0.283333E+09 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:10 | 9505.58 | 14-MAR-21:31 | 8008.33 | 01-MAR-16:12 | 3572.44 | 11-MAR-16:12 | 2040.51 | 14-MAR-21:31 | 0.00 | 01-MAR-00:10 |
| April | 0.226118E+10 | 0.552362E+09 | 498.03 | 0.188385E+10 | 0.377326E+09 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:50 | 9211.64 | 28-APR-15:12 | 8592.71 | 19-APR-16:41 | 3446.55 | 28-APR-15:13 | 1988.82 | 28-APR-15:12 | 0.00 | 01-APR-00:10 |
| May | 0.431654E+10 | 0.104133E+10 | 616.14 | 0.352306E+10 | 0.793472E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-05:00 | 9894.48 | 29-MAY-08:21 | 8793.90 | 16-MAY-16:11 | 4020.55 | 24-MAY-08:56 | 2103.92 | 29-MAY-08:21 | 0.00 | 01-MAY-00:10 |
| June | 0.627145E+10 | 0.148862E+10 | 569.22 | 0.474634E+10 | 0.152511E+10 | 0.00 | 1.00 | 01-JUN-06:51 | 0.00 | 01-JUN-05:11 | 10329.69 | 08-JUN-08:61 | 8702.91 | 03-JUN-16:21 | 4902.26 | 08-JUN-08:05 | 2178.76 | 27-JUN-07:41 | 0.00 | 01-JUN-00:10 |
| July | 0.847052E+10 | 0.200621E+10 | 605.31 | 0.607915E+10 | 0.239137E+10 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 10573.39 | 16-JUL-07:51 | 8661.85 | 06-JUL-16:11 | 5150.82 | 16-JUL-07:56 | 2211.96 | 16-JUL-07:51 | 0.00 | 01-JUL-00:10 |
| August | 0.769569E+10 | 0.182772E+10 | 598.72 | 0.577085E+10 | 0.192484E+10 | 0.00 | 1.00 | 01-AUG-08:41 | 0.00 | 01-AUG-06:51 | 10460.66 | 14-AUG-07:41 | 8674.22 | 22-AUG-16:01 | 4859.51 | 14-AUG-07:44 | 2216.82 | 15-AUG-08:41 | 0.00 | 01-AUG-00:10 |
| September | 0.585090E+10 | 0.138786E+10 | 578.43 | 0.445848E+10 | 0.139242E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 10322.47 | 15-SEP-21:31 | 8610.08 | 10-SEP-16:11 | 4628.03 | 14-SEP-08:46 | 2167.28 | 15-SEP-21:31 | 0.00 | 01-SEP-00:10 |
| October | 0.325569E+10 | 0.789244E+09 | 564.97 | 0.259355E+10 | 0.662141E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 9713.43 | 12-OCT-21:01 | 8540.09 | 30-OCT-16:11 | 3805.00 | 26-OCT-08:54 | 2075.09 | 12-OCT-21:01 | 0.00 | 01-OCT-00:10 |
| November | 0.136620E+10 | 0.334736E+09 | 363.41 | 0.112537E+10 | 0.240833E+09 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-06:51 | 9550.83 | 04-NOV-18:11 | 7776.08 | 25-NOV-19:02 | 3671.87 | 20-NOV-16:12 | 2048.17 | 04-NOV-18:11 | 0.00 | 01-NOV-00:10 |
| December | 0.163871E+09 | 39818300.79 | 70.61 | 0.132878E+09 | 30993051.80 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 9122.25 | 01-DEC-09:01 | 7551.70 | 04-DEC-16:12 | 3809.68 | 14-DEC-19:02 | 1972.45 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.413182E+11 | 0.987232E+10 | 4893.09 | 0.316595E+11 | 0.965864E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.129117E+09 | 30974583.72 | 50.84 | 0.108900E+09 | 16583518.78 | 0.00 | 1.00 | 0.00 | 8914.65 | 7551.70 | 3235.96 | 1933.25 | 0.00 | |||||||
| Maximum of Months | 0.847052E+10 | 0.200621E+10 | 616.14 | 0.607915E+10 | 0.239137E+10 | 0.00 | 1.00 | 0.00 | 10573.39 | 8793.90 | 5150.82 | 2216.82 | 0.00 |
Report: DXReportMonthly
For: 324 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 | 0.00 | 01-MAY-00:10 |
| June | 782495.41 | 210806.82 | 3.50 | 612700.95 | 169794.46 | 0.00 | 0.10 | 12-JUN-14:01 | 0.00 | 01-JUN-00:10 | 142.51 | 12-JUN-14:01 | 122.96 | 12-JUN-14:01 | 52.13 | 27-JUN-14:03 | 39.66 | 12-JUN-14:01 | 0.00 | 01-JUN-00:10 |
| July | 9303669.66 | 2461289.88 | 34.25 | 6247716.86 | 3055952.80 | 0.00 | 0.18 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 | 294.02 | 21-JUL-14:02 | 183.97 | 21-JUL-14:02 | 110.05 | 21-JUL-14:02 | 78.94 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 |
| August | 12534997.36 | 3361260.09 | 46.33 | 10826350.10 | 1708647.26 | 0.00 | 0.16 | 10-AUG-14:10 | 0.00 | 01-AUG-00:10 | 234.15 | 10-AUG-14:10 | 209.57 | 10-AUG-14:02 | 71.02 | 14-AUG-14:08 | 64.78 | 10-AUG-14:10 | 0.00 | 01-AUG-00:10 |
| September | 5246208.85 | 1348548.97 | 18.92 | 4833109.37 | 413099.48 | 0.00 | 0.14 | 21-SEP-14:30 | 0.00 | 01-SEP-00:10 | 202.03 | 21-SEP-14:20 | 201.81 | 21-SEP-14:25 | 52.60 | 16-SEP-14:02 | 52.13 | 21-SEP-14:30 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 27867371.28 | 7381905.76 | 102.99 | 22519877.28 | 5347494.00 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 12534997.36 | 3361260.09 | 46.33 | 10826350.10 | 3055952.80 | 0.00 | 0.18 | 0.00 | 294.02 | 209.57 | 110.05 | 78.94 | 0.00 |
Report: DXReportMonthly
For: 401 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 569495.59 | 142360.07 | 0.58 | 484976.74 | 84518.85 | 0.00 | 0.24 | 17-JAN-09:03 | 0.00 | 01-JAN-00:10 | 500.22 | 17-JAN-09:03 | 422.01 | 17-JAN-09:03 | 128.80 | 11-JAN-19:05 | 123.44 | 17-JAN-09:03 | 0.00 | 01-JAN-00:10 |
| February | 443969.56 | 111271.62 | 0.57 | 414526.14 | 29443.42 | 0.00 | 0.26 | 22-FEB-19:03 | 0.00 | 01-FEB-00:10 | 526.67 | 22-FEB-19:03 | 520.07 | 22-FEB-19:03 | 65.01 | 01-FEB-19:05 | 129.51 | 22-FEB-19:03 | 0.00 | 01-FEB-00:10 |
| March | 91038196.84 | 22145120.29 | 64.47 | 67571843.21 | 23466353.63 | 0.00 | 1.00 | 12-MAR-15:12 | 0.00 | 01-MAR-00:10 | 2749.59 | 14-MAR-18:51 | 2251.12 | 15-MAR-19:21 | 1287.72 | 14-MAR-08:61 | 589.25 | 14-MAR-18:51 | 0.00 | 01-MAR-00:10 |
| April | 0.140845E+09 | 34500915.04 | 143.83 | 0.115996E+09 | 24848749.23 | 0.00 | 1.00 | 01-APR-15:12 | 0.00 | 01-APR-00:10 | 2680.32 | 09-APR-08:61 | 2395.74 | 22-APR-17:11 | 1043.86 | 30-APR-08:61 | 577.34 | 09-APR-08:61 | 0.00 | 01-APR-00:10 |
| May | 0.678595E+09 | 0.164325E+09 | 426.33 | 0.550758E+09 | 0.127836E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 2860.76 | 29-MAY-07:51 | 2571.05 | 23-MAY-16:21 | 1274.35 | 24-MAY-08:55 | 607.08 | 29-MAY-07:51 | 0.00 | 01-MAY-00:10 |
| June | 0.166496E+10 | 0.394570E+09 | 535.34 | 0.127577E+10 | 0.389190E+09 | 0.00 | 1.00 | 01-JUN-07:41 | 0.00 | 01-JUN-05:11 | 3026.85 | 18-JUN-07:51 | 2618.53 | 24-JUN-16:21 | 1508.26 | 08-JUN-08:53 | 633.84 | 18-JUN-07:51 | 0.00 | 01-JUN-00:10 |
| July | 0.255086E+10 | 0.603244E+09 | 606.04 | 0.188499E+10 | 0.665874E+09 | 0.00 | 1.00 | 01-JUL-07:51 | 0.00 | 01-JUL-06:01 | 3080.00 | 29-JUL-08:11 | 2589.95 | 06-JUL-17:52 | 1497.37 | 29-JUL-08:34 | 639.23 | 16-JUL-07:51 | 0.00 | 01-JUL-00:10 |
| August | 0.203729E+10 | 0.485583E+09 | 583.93 | 0.154630E+10 | 0.490982E+09 | 0.00 | 1.00 | 01-AUG-08:51 | 0.00 | 01-AUG-06:51 | 3018.88 | 14-AUG-08:11 | 2608.95 | 01-AUG-16:11 | 1453.70 | 25-AUG-07:13 | 632.81 | 14-AUG-08:11 | 0.00 | 01-AUG-00:10 |
| September | 0.945073E+09 | 0.225934E+09 | 452.66 | 0.678493E+09 | 0.266580E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 3009.04 | 14-SEP-08:21 | 2457.77 | 02-SEP-17:31 | 1443.54 | 14-SEP-08:24 | 628.39 | 14-SEP-08:21 | 0.00 | 01-SEP-00:10 |
| October | 0.147210E+09 | 35871736.86 | 160.05 | 0.102931E+09 | 44279627.60 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 2816.11 | 01-OCT-08:61 | 2172.31 | 25-OCT-20:11 | 1361.47 | 26-OCT-08:51 | 600.11 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 |
| November | 17549296.50 | 4293888.11 | 21.72 | 12663085.18 | 4886211.32 | 0.00 | 1.00 | 04-NOV-19:51 | 0.00 | 01-NOV-00:10 | 2693.17 | 05-NOV-08:51 | 1811.98 | 26-NOV-19:02 | 1003.70 | 05-NOV-08:53 | 579.60 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 718511.51 | 179800.63 | 0.77 | 603622.46 | 114889.05 | 0.00 | 0.21 | 01-DEC-19:05 | 0.00 | 01-DEC-00:10 | 427.22 | 14-DEC-19:05 | 357.85 | 01-DEC-19:05 | 150.91 | 14-DEC-19:05 | 106.06 | 14-DEC-19:05 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.827515E+10 | 0.197090E+10 | 2996.29 | 0.623698E+10 | 0.203817E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 443969.56 | 111271.62 | 0.57 | 414526.14 | 29443.42 | 0.00 | 0.21 | 0.00 | 427.22 | 357.85 | 65.01 | 106.06 | 0.00 | |||||||
| Maximum of Months | 0.255086E+10 | 0.603244E+09 | 606.04 | 0.188499E+10 | 0.665874E+09 | 0.00 | 1.00 | 0.00 | 3080.00 | 2618.53 | 1508.26 | 639.23 | 0.00 |
Report: DXReportMonthly
For: 402_405 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 6869750.54 | 1775923.26 | 14.41 | 6546005.48 | 323745.06 | 0.00 | 0.08 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 475.48 | 14-MAY-15:00 | 428.89 | 14-MAY-15:00 | 46.59 | 14-MAY-15:00 | 124.06 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
| June | 0.297701E+09 | 76462208.28 | 158.65 | 0.244074E+09 | 53627269.37 | 0.00 | 0.29 | 12-JUN-14:10 | 0.00 | 01-JUN-00:10 | 1801.16 | 27-JUN-14:10 | 1576.49 | 12-JUN-14:02 | 512.48 | 27-JUN-15:00 | 481.55 | 12-JUN-14:10 | 0.00 | 01-JUN-00:10 |
| July | 0.630298E+09 | 0.163177E+09 | 262.87 | 0.497960E+09 | 0.132338E+09 | 0.00 | 0.34 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 | 2187.46 | 21-JUL-14:02 | 1801.51 | 21-JUL-14:02 | 512.05 | 20-JUL-14:10 | 596.55 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 |
| August | 0.356415E+09 | 93420880.91 | 182.85 | 0.304762E+09 | 51653518.28 | 0.00 | 0.26 | 13-AUG-15:00 | 0.00 | 01-AUG-00:10 | 1679.70 | 13-AUG-15:00 | 1467.17 | 09-AUG-14:02 | 468.00 | 14-AUG-15:00 | 447.84 | 13-AUG-15:00 | 0.00 | 01-AUG-00:10 |
| September | 18525527.54 | 4756480.92 | 15.71 | 13516959.45 | 5008568.09 | 0.00 | 0.14 | 16-SEP-14:02 | 0.00 | 01-SEP-00:10 | 938.51 | 16-SEP-14:02 | 692.54 | 16-SEP-14:02 | 245.97 | 16-SEP-14:02 | 242.28 | 16-SEP-14:02 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.130981E+10 | 0.339592E+09 | 634.49 | 0.106686E+10 | 0.242951E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.630298E+09 | 0.163177E+09 | 262.87 | 0.497960E+09 | 0.132338E+09 | 0.00 | 0.34 | 0.00 | 2187.46 | 1801.51 | 512.48 | 596.55 | 0.00 |
Report: DXReportMonthly
For: 406_408 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 4993109.38 | 1292381.71 | 12.72 | 4756197.20 | 236912.18 | 0.00 | 0.08 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 373.09 | 14-MAY-15:00 | 337.27 | 14-MAY-15:00 | 35.82 | 14-MAY-15:00 | 97.35 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
| June | 0.214822E+09 | 55226523.58 | 152.63 | 0.175430E+09 | 39392108.66 | 0.00 | 0.28 | 12-JUN-14:10 | 0.00 | 01-JUN-00:10 | 1374.20 | 27-JUN-14:10 | 1205.96 | 12-JUN-14:02 | 396.56 | 27-JUN-14:40 | 369.41 | 12-JUN-14:10 | 0.00 | 01-JUN-00:10 |
| July | 0.454386E+09 | 0.117751E+09 | 251.04 | 0.356744E+09 | 97642139.48 | 0.00 | 0.33 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 | 1675.12 | 21-JUL-14:02 | 1360.59 | 21-JUL-14:02 | 402.16 | 20-JUL-14:10 | 456.56 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 |
| August | 0.255308E+09 | 67020233.60 | 175.20 | 0.217879E+09 | 37428828.08 | 0.00 | 0.25 | 13-AUG-15:00 | 0.00 | 01-AUG-00:10 | 1289.65 | 13-AUG-15:00 | 1113.77 | 09-AUG-14:02 | 364.29 | 14-AUG-15:00 | 343.99 | 13-AUG-15:00 | 0.00 | 01-AUG-00:10 |
| September | 13140592.33 | 3375111.85 | 14.50 | 9518928.05 | 3621664.29 | 0.00 | 0.14 | 16-SEP-14:02 | 0.00 | 01-SEP-00:10 | 718.17 | 16-SEP-14:02 | 525.42 | 16-SEP-14:02 | 192.75 | 16-SEP-14:02 | 185.31 | 16-SEP-14:02 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.942650E+09 | 0.244665E+09 | 606.09 | 0.764328E+09 | 0.178322E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.454386E+09 | 0.117751E+09 | 251.04 | 0.356744E+09 | 97642139.48 | 0.00 | 0.33 | 0.00 | 1675.12 | 1360.59 | 402.16 | 456.56 | 0.00 |
Report: DXReportMonthly
For: 409_412 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 11157997.25 | 2714021.59 | 1.71 | 8979603.13 | 2178394.12 | 0.00 | 0.85 | 14-JAN-09:01 | 0.00 | 01-JAN-00:10 | 7377.70 | 14-JAN-09:01 | 5566.24 | 14-JAN-09:01 | 1878.59 | 11-JAN-16:13 | 1649.32 | 14-JAN-09:01 | 0.00 | 01-JAN-00:10 |
| February | 13325122.22 | 3279026.52 | 4.13 | 11241098.25 | 2084023.97 | 0.00 | 0.94 | 22-FEB-19:02 | 0.00 | 01-FEB-00:10 | 8223.31 | 22-FEB-19:02 | 7275.04 | 22-FEB-19:02 | 1260.22 | 01-FEB-19:03 | 1808.32 | 22-FEB-19:02 | 0.00 | 01-FEB-00:10 |
| March | 0.583992E+09 | 0.141955E+09 | 126.07 | 0.421947E+09 | 0.162045E+09 | 0.00 | 1.00 | 09-MAR-19:02 | 0.00 | 01-MAR-00:10 | 10185.80 | 14-MAR-08:61 | 8264.55 | 15-MAR-19:21 | 4679.69 | 14-MAR-08:03 | 2182.02 | 14-MAR-08:61 | 0.00 | 01-MAR-00:10 |
| April | 0.110035E+10 | 0.268926E+09 | 269.52 | 0.874214E+09 | 0.226131E+09 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:10 | 10001.76 | 08-APR-17:51 | 9082.38 | 22-APR-17:11 | 4000.38 | 28-APR-15:12 | 2150.72 | 08-APR-17:51 | 0.00 | 01-APR-00:10 |
| May | 0.315662E+10 | 0.764113E+09 | 503.45 | 0.251213E+10 | 0.644487E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 10646.28 | 24-MAY-07:31 | 9646.97 | 26-MAY-16:42 | 4665.23 | 24-MAY-08:56 | 2255.16 | 24-MAY-07:31 | 0.00 | 01-MAY-00:10 |
| June | 0.585784E+10 | 0.139550E+10 | 550.17 | 0.440365E+10 | 0.145419E+10 | 0.00 | 1.00 | 01-JUN-07:41 | 0.00 | 01-JUN-05:11 | 11111.75 | 18-JUN-07:51 | 9713.28 | 06-JUN-16:31 | 5234.37 | 08-JUN-08:56 | 2333.27 | 18-JUN-07:51 | 0.00 | 01-JUN-00:10 |
| July | 0.839026E+10 | 0.199912E+10 | 605.83 | 0.603992E+10 | 0.235033E+10 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 11348.10 | 29-JUL-08:11 | 9623.40 | 06-JUL-16:21 | 5228.05 | 29-JUL-08:34 | 2359.40 | 16-JUL-07:51 | 0.00 | 01-JUL-00:10 |
| August | 0.692967E+10 | 0.166000E+10 | 588.72 | 0.513000E+10 | 0.179967E+10 | 0.00 | 1.00 | 01-AUG-08:51 | 0.00 | 01-AUG-06:51 | 11104.64 | 15-AUG-07:51 | 9673.14 | 22-AUG-16:32 | 5144.98 | 14-AUG-08:15 | 2331.50 | 14-AUG-08:11 | 0.00 | 01-AUG-00:10 |
| September | 0.390377E+10 | 0.934415E+09 | 508.06 | 0.277533E+10 | 0.112844E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 11177.94 | 16-SEP-08:23 | 9330.79 | 07-SEP-16:52 | 5056.38 | 14-SEP-08:27 | 2330.51 | 16-SEP-08:23 | 0.00 | 01-SEP-00:10 |
| October | 0.126399E+10 | 0.307751E+09 | 298.20 | 0.892723E+09 | 0.371264E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 10465.33 | 12-OCT-21:51 | 7964.16 | 25-OCT-20:11 | 4860.69 | 26-OCT-15:12 | 2227.30 | 12-OCT-21:51 | 0.00 | 01-OCT-00:10 |
| November | 0.313779E+09 | 76623693.27 | 111.08 | 0.229574E+09 | 84204674.21 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 10295.41 | 05-NOV-08:51 | 7240.14 | 25-NOV-19:02 | 3996.41 | 16-NOV-19:14 | 2200.10 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 14669987.43 | 3586465.67 | 5.20 | 10760802.92 | 3909184.51 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 9697.54 | 01-DEC-09:01 | 6891.10 | 02-DEC-09:01 | 3789.73 | 01-DEC-09:01 | 2096.33 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.315394E+11 | 0.755798E+10 | 3572.15 | 0.233105E+11 | 0.822894E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 11157997.25 | 2714021.59 | 1.71 | 8979603.13 | 2084023.97 | 0.00 | 0.85 | 0.00 | 7377.70 | 5566.24 | 1260.22 | 1649.32 | 0.00 | |||||||
| Maximum of Months | 0.839026E+10 | 0.199912E+10 | 605.83 | 0.603992E+10 | 0.235033E+10 | 0.00 | 1.00 | 0.00 | 11348.10 | 9713.28 | 5234.37 | 2359.40 | 0.00 |
Report: DXReportMonthly
For: 413 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 |
| May | 160334.47 | 42150.78 | 0.92 | 154599.65 | 5734.81 | 0.00 | 0.03 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 72.42 | 14-MAY-15:00 | 68.89 | 14-MAY-15:00 | 3.54 | 14-MAY-15:00 | 19.04 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
| June | 47307340.80 | 12277043.68 | 113.98 | 39267333.63 | 8040007.18 | 0.00 | 0.19 | 12-JUN-14:20 | 0.00 | 01-JUN-00:10 | 452.71 | 27-JUN-14:10 | 405.77 | 12-JUN-14:02 | 122.88 | 27-JUN-15:00 | 123.59 | 12-JUN-14:10 | 0.00 | 01-JUN-00:10 |
| July | 0.115878E+09 | 30408344.95 | 223.39 | 92872827.06 | 23004678.59 | 0.00 | 0.24 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 | 591.36 | 21-JUL-14:02 | 487.46 | 21-JUL-14:02 | 123.53 | 20-JUL-14:10 | 163.39 | 21-JUL-14:02 | 0.00 | 01-JUL-00:10 |
| August | 62638049.61 | 16639470.21 | 146.09 | 54904394.78 | 7733654.82 | 0.00 | 0.17 | 13-AUG-15:00 | 0.00 | 01-AUG-00:10 | 422.22 | 13-AUG-15:00 | 377.23 | 09-AUG-15:00 | 119.19 | 14-AUG-15:00 | 114.35 | 13-AUG-15:00 | 0.00 | 01-AUG-00:10 |
| September | 2167311.69 | 559035.06 | 7.79 | 1558011.03 | 609300.66 | 0.00 | 0.09 | 16-SEP-14:02 | 0.00 | 01-SEP-00:10 | 235.07 | 16-SEP-14:02 | 169.06 | 16-SEP-14:02 | 66.00 | 16-SEP-14:02 | 60.78 | 16-SEP-14:02 | 0.00 | 01-SEP-00:10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.228151E+09 | 59926044.68 | 492.17 | 0.188757E+09 | 39393376.07 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.115878E+09 | 30408344.95 | 223.39 | 92872827.06 | 23004678.59 | 0.00 | 0.24 | 0.00 | 591.36 | 487.46 | 123.53 | 163.39 | 0.00 |
Report: DXReportMonthly
For: 414 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 4437468.23 | 1140138.38 | 7.96 | 4354067.35 | 83400.88 | 0.00 | 0.16 | 15-MAR-14:10 | 0.00 | 01-MAR-00:10 | 329.83 | 15-MAR-14:02 | 329.83 | 15-MAR-14:02 | 9.18 | 14-MAR-14:10 | 85.14 | 15-MAR-14:02 | 0.00 | 01-MAR-00:10 |
| April | 455512.78 | 116154.19 | 3.15 | 455512.78 | 0.00 | 0.00 | 0.04 | 22-APR-13:40 | 0.00 | 01-APR-00:10 | 75.63 | 22-APR-13:40 | 75.63 | 22-APR-13:40 | 0.00 | 23-APR-14:00 | 19.26 | 22-APR-13:40 | 0.00 | 01-APR-00:10 |
| May | 17448822.92 | 4442898.14 | 51.25 | 17325531.05 | 123291.87 | 0.00 | 0.15 | 14-MAY-14:30 | 0.00 | 01-MAY-00:10 | 312.91 | 14-MAY-14:20 | 302.43 | 14-MAY-14:30 | 11.95 | 14-MAY-14:40 | 80.10 | 14-MAY-14:30 | 0.00 | 01-MAY-00:10 |
| June | 0.103478E+09 | 26542793.11 | 172.54 | 91292925.54 | 12185136.14 | 0.00 | 0.29 | 12-JUN-14:10 | 0.00 | 01-JUN-00:10 | 628.34 | 27-JUN-14:10 | 570.23 | 12-JUN-14:02 | 142.21 | 27-JUN-15:00 | 166.77 | 12-JUN-14:10 | 0.00 | 01-JUN-00:10 |
| July | 0.222268E+09 | 57478663.08 | 258.33 | 0.189213E+09 | 33055462.69 | 0.00 | 0.32 | 21-JUL-14:10 | 0.00 | 01-JUL-00:10 | 704.24 | 19-JUL-14:10 | 617.42 | 21-JUL-14:02 | 155.85 | 21-JUL-10:55 | 193.19 | 21-JUL-14:10 | 0.00 | 01-JUL-00:10 |
| August | 0.192165E+09 | 49854710.65 | 213.63 | 0.176361E+09 | 15804029.07 | 0.00 | 0.34 | 18-AUG-14:10 | 0.00 | 01-AUG-00:10 | 726.99 | 18-AUG-14:10 | 679.04 | 18-AUG-14:02 | 153.51 | 14-AUG-14:35 | 194.91 | 18-AUG-14:10 | 0.00 | 01-AUG-00:10 |
| September | 77076023.48 | 19408223.66 | 120.10 | 72408243.88 | 4667779.60 | 0.00 | 0.29 | 21-SEP-14:01 | 0.00 | 01-SEP-00:10 | 617.19 | 21-SEP-14:01 | 617.19 | 21-SEP-14:01 | 128.03 | 15-SEP-11:25 | 155.29 | 21-SEP-14:01 | 0.00 | 01-SEP-00:10 |
| October | 6654309.95 | 1676838.81 | 15.67 | 6654309.95 | -0.0 | 0.00 | 0.15 | 11-OCT-12:40 | 0.00 | 01-OCT-00:10 | 315.77 | 11-OCT-12:40 | 315.77 | 11-OCT-12:40 | 0.00 | 11-OCT-14:30 | 78.85 | 11-OCT-12:40 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.623984E+09 | 0.160660E+09 | 842.63 | 0.558065E+09 | 65919100.23 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.222268E+09 | 57478663.08 | 258.33 | 0.189213E+09 | 33055462.69 | 0.00 | 0.34 | 0.00 | 726.99 | 679.04 | 155.85 | 194.91 | 0.00 |
Report: DXReportMonthly
For: 415_418 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.111361E+09 | 27310372.54 | 47.93 | 97140240.09 | 14220454.61 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:10 | 11481.08 | 17-JAN-19:02 | 10183.79 | 12-JAN-16:11 | 4098.52 | 11-JAN-19:02 | 2486.02 | 17-JAN-19:02 | 0.00 | 01-JAN-00:10 |
| February | 0.142392E+09 | 35092420.75 | 45.99 | 0.131933E+09 | 10459124.65 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:10 | 11366.21 | 01-FEB-09:01 | 10411.49 | 22-FEB-16:12 | 4210.28 | 01-FEB-09:01 | 2464.17 | 01-FEB-09:01 | 0.00 | 01-FEB-00:10 |
| March | 0.145778E+10 | 0.356946E+09 | 292.38 | 0.120334E+10 | 0.254436E+09 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:10 | 12058.41 | 14-MAR-08:61 | 10356.60 | 08-MAR-16:12 | 4850.36 | 14-MAR-08:03 | 2589.80 | 14-MAR-08:61 | 0.00 | 01-MAR-00:10 |
| April | 0.235885E+10 | 0.577552E+09 | 409.20 | 0.202573E+10 | 0.333119E+09 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:10 | 11735.37 | 08-APR-21:21 | 11179.46 | 19-APR-16:21 | 4044.64 | 28-APR-15:12 | 2532.96 | 08-APR-21:21 | 0.00 | 01-APR-00:10 |
| May | 0.449025E+10 | 0.108866E+10 | 578.99 | 0.373863E+10 | 0.751614E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:30 | 12597.44 | 29-MAY-08:21 | 11466.21 | 23-MAY-17:01 | 4943.83 | 24-MAY-08:55 | 2677.80 | 29-MAY-08:21 | 0.00 | 01-MAY-00:10 |
| June | 0.686800E+10 | 0.164810E+10 | 578.84 | 0.533331E+10 | 0.153469E+10 | 0.00 | 1.00 | 01-JUN-06:51 | 0.00 | 01-JUN-05:11 | 13175.43 | 18-JUN-07:32 | 11588.54 | 24-JUN-17:01 | 5945.86 | 08-JUN-08:06 | 2766.86 | 18-JUN-07:32 | 0.00 | 01-JUN-00:10 |
| July | 0.941179E+10 | 0.226104E+10 | 616.42 | 0.698119E+10 | 0.243060E+10 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 13446.46 | 16-JUL-07:31 | 11519.05 | 06-JUL-17:01 | 5883.87 | 16-JUL-07:54 | 2803.22 | 16-JUL-07:31 | 0.00 | 01-JUL-00:10 |
| August | 0.835528E+10 | 0.201207E+10 | 610.38 | 0.642945E+10 | 0.192583E+10 | 0.00 | 1.00 | 01-AUG-08:41 | 0.00 | 01-AUG-06:51 | 13262.29 | 15-AUG-08:21 | 11649.91 | 01-AUG-16:51 | 5657.19 | 14-AUG-06:37 | 2805.84 | 15-AUG-08:21 | 0.00 | 01-AUG-00:10 |
| September | 0.589384E+10 | 0.141067E+10 | 574.38 | 0.455774E+10 | 0.133610E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 13002.26 | 14-SEP-08:41 | 11462.07 | 09-SEP-16:51 | 5604.07 | 14-SEP-08:46 | 2738.37 | 14-SEP-08:41 | 0.00 | 01-SEP-00:10 |
| October | 0.297169E+10 | 0.724387E+09 | 485.61 | 0.238956E+10 | 0.582133E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 12301.26 | 12-OCT-21:01 | 11422.50 | 11-OCT-16:52 | 5009.01 | 26-OCT-15:12 | 2630.49 | 12-OCT-21:01 | 0.00 | 01-OCT-00:10 |
| November | 0.114662E+10 | 0.282258E+09 | 277.42 | 0.945705E+09 | 0.200916E+09 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 12280.40 | 05-NOV-07:51 | 10059.37 | 26-NOV-17:51 | 4942.35 | 20-NOV-19:02 | 2627.07 | 05-NOV-07:51 | 0.00 | 01-NOV-00:10 |
| December | 0.150124E+09 | 36916729.48 | 56.89 | 0.126208E+09 | 23915338.65 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 11705.21 | 14-DEC-19:02 | 9952.06 | 04-DEC-16:12 | 5114.38 | 14-DEC-19:02 | 2527.49 | 14-DEC-19:02 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.433580E+11 | 0.104610E+11 | 4574.42 | 0.339599E+11 | 0.939803E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.111361E+09 | 27310372.54 | 45.99 | 97140240.09 | 10459124.65 | 0.00 | 1.00 | 0.00 | 11366.21 | 9952.06 | 4044.64 | 2464.17 | 0.00 | |||||||
| Maximum of Months | 0.941179E+10 | 0.226104E+10 | 616.42 | 0.698119E+10 | 0.243060E+10 | 0.00 | 1.00 | 0.00 | 13446.46 | 11649.91 | 5945.86 | 2805.84 | 0.00 |
Report: DXReportMonthly
For: 419 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 18245175.02 | 4470576.70 | 28.49 | 15380222.44 | 2864952.58 | 0.00 | 1.00 | 06-JAN-16:12 | 0.00 | 01-JAN-00:10 | 2949.84 | 17-JAN-19:02 | 2718.50 | 12-JAN-16:11 | 1062.56 | 17-JAN-19:02 | 642.33 | 17-JAN-19:02 | 0.00 | 01-JAN-00:10 |
| February | 23618021.97 | 5821651.74 | 31.43 | 21474124.12 | 2143897.85 | 0.00 | 1.00 | 12-FEB-09:01 | 0.00 | 01-FEB-00:10 | 2883.28 | 18-FEB-16:12 | 2792.10 | 22-FEB-16:12 | 612.59 | 20-FEB-16:12 | 627.49 | 18-FEB-16:12 | 0.00 | 01-FEB-00:10 |
| March | 0.371533E+09 | 90894240.88 | 269.34 | 0.304269E+09 | 67264312.46 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 3211.01 | 14-MAR-21:31 | 2766.07 | 14-MAR-17:01 | 1252.89 | 14-MAR-08:02 | 689.97 | 14-MAR-21:31 | 0.00 | 01-MAR-00:10 |
| April | 0.642267E+09 | 0.157111E+09 | 409.65 | 0.552347E+09 | 89919791.24 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:10 | 3144.77 | 28-APR-15:12 | 2946.83 | 07-APR-16:51 | 1115.35 | 28-APR-15:12 | 678.33 | 28-APR-15:12 | 0.00 | 01-APR-00:10 |
| May | 0.130014E+10 | 0.314753E+09 | 595.60 | 0.109552E+10 | 0.204622E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-01:10 | 3360.18 | 29-MAY-08:21 | 3053.67 | 23-MAY-17:01 | 1293.30 | 24-MAY-08:55 | 714.41 | 29-MAY-08:21 | 0.00 | 01-MAY-00:10 |
| June | 0.198777E+10 | 0.475512E+09 | 584.13 | 0.157716E+10 | 0.410615E+09 | 0.00 | 1.00 | 01-JUN-06:51 | 0.00 | 01-JUN-05:11 | 3506.40 | 18-JUN-07:32 | 3103.97 | 24-JUN-17:01 | 1583.42 | 08-JUN-08:06 | 737.11 | 18-JUN-07:32 | 0.00 | 01-JUN-00:10 |
| July | 0.270649E+10 | 0.647581E+09 | 615.12 | 0.206178E+10 | 0.644710E+09 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 3574.54 | 16-JUL-07:31 | 3070.08 | 06-JUL-17:01 | 1571.90 | 16-JUL-07:54 | 746.35 | 16-JUL-07:31 | 0.00 | 01-JUL-00:10 |
| August | 0.241453E+10 | 0.579210E+09 | 610.38 | 0.190094E+10 | 0.513589E+09 | 0.00 | 1.00 | 01-AUG-08:41 | 0.00 | 01-AUG-06:51 | 3525.42 | 15-AUG-08:21 | 3104.26 | 01-AUG-16:51 | 1482.73 | 14-AUG-07:43 | 747.06 | 15-AUG-08:21 | 0.00 | 01-AUG-00:10 |
| September | 0.170057E+10 | 0.406398E+09 | 580.32 | 0.134088E+10 | 0.359688E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 3467.18 | 14-SEP-08:41 | 3068.80 | 09-SEP-16:51 | 1477.83 | 14-SEP-08:46 | 730.46 | 14-SEP-08:41 | 0.00 | 01-SEP-00:10 |
| October | 0.825635E+09 | 0.201230E+09 | 486.81 | 0.668132E+09 | 0.157503E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 3281.30 | 12-OCT-21:01 | 3049.48 | 11-OCT-16:52 | 1350.18 | 26-OCT-15:12 | 701.79 | 12-OCT-21:01 | 0.00 | 01-OCT-00:10 |
| November | 0.289541E+09 | 71350850.50 | 269.07 | 0.238549E+09 | 50991437.17 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-01:10 | 3255.06 | 05-NOV-08:51 | 2681.79 | 26-NOV-17:51 | 1374.89 | 20-NOV-19:02 | 697.44 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 25250777.11 | 6236742.52 | 40.90 | 20674926.69 | 4575850.42 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 3107.04 | 01-DEC-09:01 | 2611.32 | 04-DEC-16:12 | 1090.71 | 01-DEC-09:01 | 671.48 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.123056E+11 | 0.296057E+10 | 4521.24 | 0.979710E+10 | 0.250849E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 18245175.02 | 4470576.70 | 28.49 | 15380222.44 | 2143897.85 | 0.00 | 1.00 | 0.00 | 2883.28 | 2611.32 | 612.59 | 627.49 | 0.00 | |||||||
| Maximum of Months | 0.270649E+10 | 0.647581E+09 | 615.12 | 0.206178E+10 | 0.644710E+09 | 0.00 | 1.00 | 0.00 | 3574.54 | 3104.26 | 1583.42 | 747.06 | 0.00 |
Report: DXReportMonthly
For: 420_423 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 75553205.54 | 18456218.96 | 30.94 | 65096271.52 | 10456934.02 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:10 | 11328.77 | 11-JAN-19:02 | 10059.46 | 12-JAN-16:11 | 4333.65 | 11-JAN-19:02 | 2453.38 | 11-JAN-19:02 | 0.00 | 01-JAN-00:10 |
| February | 0.103021E+09 | 25393777.08 | 36.98 | 94703732.05 | 8317259.53 | 0.00 | 1.00 | 08-FEB-16:11 | 0.00 | 01-FEB-00:10 | 10757.89 | 15-FEB-09:01 | 10292.69 | 22-FEB-16:12 | 3196.00 | 01-FEB-09:01 | 2340.44 | 15-FEB-09:01 | 0.00 | 01-FEB-00:10 |
| March | 0.122437E+10 | 0.299771E+09 | 260.24 | 0.995186E+09 | 0.229184E+09 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 12006.35 | 14-MAR-08:61 | 10177.32 | 02-MAR-16:12 | 5057.01 | 14-MAR-08:03 | 2574.33 | 14-MAR-08:61 | 0.00 | 01-MAR-00:10 |
| April | 0.206296E+10 | 0.505400E+09 | 374.81 | 0.175601E+10 | 0.306949E+09 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:10 | 11691.00 | 28-APR-15:12 | 10993.61 | 19-APR-16:21 | 4363.14 | 28-APR-15:12 | 2519.76 | 28-APR-15:12 | 0.00 | 01-APR-00:10 |
| May | 0.408410E+10 | 0.991283E+09 | 553.00 | 0.336682E+10 | 0.717279E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 12479.33 | 29-MAY-08:21 | 11282.40 | 23-MAY-17:01 | 4957.95 | 24-MAY-08:55 | 2650.64 | 29-MAY-08:21 | 0.00 | 01-MAY-00:10 |
| June | 0.639141E+10 | 0.153624E+10 | 569.13 | 0.490416E+10 | 0.148725E+10 | 0.00 | 1.00 | 01-JUN-06:51 | 0.00 | 01-JUN-05:11 | 13000.80 | 08-JUN-08:61 | 11323.00 | 24-JUN-17:01 | 6003.17 | 08-JUN-08:06 | 2730.81 | 18-JUN-07:32 | 0.00 | 01-JUN-00:10 |
| July | 0.886834E+10 | 0.213445E+10 | 613.37 | 0.649673E+10 | 0.237161E+10 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 13296.26 | 16-JUL-07:31 | 11335.17 | 06-JUL-17:01 | 5953.82 | 16-JUL-07:54 | 2770.81 | 16-JUL-07:31 | 0.00 | 01-JUL-00:10 |
| August | 0.782882E+10 | 0.188885E+10 | 607.17 | 0.595574E+10 | 0.187308E+10 | 0.00 | 1.00 | 01-AUG-08:41 | 0.00 | 01-AUG-06:51 | 13115.13 | 15-AUG-08:21 | 11496.46 | 01-AUG-16:51 | 5717.45 | 26-AUG-07:54 | 2773.49 | 15-AUG-08:21 | 0.00 | 01-AUG-00:10 |
| September | 0.542660E+10 | 0.130046E+10 | 561.91 | 0.414208E+10 | 0.128452E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 12888.37 | 14-SEP-08:41 | 11171.08 | 09-SEP-16:51 | 5658.15 | 14-SEP-08:46 | 2711.36 | 14-SEP-08:41 | 0.00 | 01-SEP-00:10 |
| October | 0.261236E+10 | 0.637039E+09 | 453.95 | 0.207242E+10 | 0.539941E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 12187.71 | 12-OCT-21:01 | 11130.86 | 11-OCT-16:52 | 5334.19 | 26-OCT-15:12 | 2604.37 | 12-OCT-21:01 | 0.00 | 01-OCT-00:10 |
| November | 0.941736E+09 | 0.231898E+09 | 241.93 | 0.766523E+09 | 0.175212E+09 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 12135.18 | 05-NOV-08:51 | 9820.14 | 03-NOV-15:12 | 5074.29 | 20-NOV-19:02 | 2595.77 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 0.102392E+09 | 25158390.01 | 41.87 | 85326998.14 | 17065336.35 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 11529.69 | 01-DEC-09:01 | 9714.22 | 04-DEC-16:12 | 4269.57 | 14-DEC-09:01 | 2490.69 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.397217E+11 | 0.959441E+10 | 4345.30 | 0.307008E+11 | 0.902087E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 75553205.54 | 18456218.96 | 30.94 | 65096271.52 | 8317259.53 | 0.00 | 1.00 | 0.00 | 10757.89 | 9714.22 | 3196.00 | 2340.44 | 0.00 | |||||||
| Maximum of Months | 0.886834E+10 | 0.213445E+10 | 613.37 | 0.649673E+10 | 0.237161E+10 | 0.00 | 1.00 | 0.00 | 13296.26 | 11496.46 | 6003.17 | 2773.49 | 0.00 |
Report: DXReportMonthly
For: 424 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 4277605.33 | 1053780.13 | 5.11 | 3407664.37 | 869940.96 | 0.00 | 1.00 | 15-JAN-16:12 | 0.00 | 01-JAN-00:10 | 3004.64 | 15-JAN-16:12 | 2432.17 | 15-JAN-16:12 | 572.47 | 15-JAN-16:12 | 653.16 | 15-JAN-16:12 | 0.00 | 01-JAN-00:10 |
| February | 6040362.22 | 1482263.97 | 10.03 | 5267509.00 | 772853.22 | 0.00 | 1.00 | 18-FEB-16:12 | 0.00 | 01-FEB-00:10 | 3031.75 | 18-FEB-16:12 | 2652.21 | 28-FEB-16:12 | 735.77 | 18-FEB-16:12 | 658.60 | 18-FEB-16:12 | 0.00 | 01-FEB-00:10 |
| March | 0.228866E+09 | 55896125.92 | 172.66 | 0.179026E+09 | 49839809.59 | 0.00 | 1.00 | 01-MAR-16:12 | 0.00 | 01-MAR-00:10 | 3320.57 | 14-MAR-08:61 | 2802.70 | 14-MAR-17:01 | 1510.93 | 14-MAR-08:02 | 711.43 | 14-MAR-08:61 | 0.00 | 01-MAR-00:10 |
| April | 0.446660E+09 | 0.109526E+09 | 314.90 | 0.376610E+09 | 70049173.17 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:10 | 3233.13 | 28-APR-15:12 | 3001.24 | 07-APR-16:51 | 1319.68 | 28-APR-15:12 | 696.41 | 28-APR-15:12 | 0.00 | 01-APR-00:10 |
| May | 0.107013E+10 | 0.259946E+09 | 540.54 | 0.885047E+09 | 0.185078E+09 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 3449.93 | 29-MAY-08:21 | 3102.11 | 23-MAY-17:01 | 1339.31 | 24-MAY-08:54 | 732.15 | 29-MAY-08:21 | 0.00 | 01-MAY-00:10 |
| June | 0.184446E+10 | 0.442493E+09 | 568.51 | 0.144716E+10 | 0.397299E+09 | 0.00 | 1.00 | 01-JUN-06:51 | 0.00 | 01-JUN-05:11 | 3603.01 | 08-JUN-08:61 | 3156.23 | 24-JUN-17:01 | 1686.23 | 08-JUN-08:04 | 754.38 | 08-JUN-08:61 | 0.00 | 01-JUN-00:10 |
| July | 0.265449E+10 | 0.636604E+09 | 614.10 | 0.201634E+10 | 0.638154E+09 | 0.00 | 1.00 | 01-JUL-07:31 | 0.00 | 01-JUL-06:01 | 3645.30 | 16-JUL-07:31 | 3127.98 | 06-JUL-17:01 | 1621.09 | 16-JUL-07:54 | 761.13 | 16-JUL-07:31 | 0.00 | 01-JUL-00:10 |
| August | 0.233975E+10 | 0.562631E+09 | 606.96 | 0.183455E+10 | 0.505207E+09 | 0.00 | 1.00 | 01-AUG-08:41 | 0.00 | 01-AUG-06:51 | 3598.24 | 15-AUG-08:21 | 3166.10 | 01-AUG-16:51 | 1544.81 | 26-AUG-07:53 | 762.25 | 15-AUG-08:21 | 0.00 | 01-AUG-00:10 |
| September | 0.154050E+10 | 0.369049E+09 | 560.67 | 0.119802E+10 | 0.342480E+09 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-06:51 | 3550.24 | 14-SEP-08:41 | 3112.80 | 09-SEP-16:51 | 1537.65 | 14-SEP-08:45 | 746.99 | 14-SEP-08:41 | 0.00 | 01-SEP-00:10 |
| October | 0.605684E+09 | 0.147853E+09 | 394.01 | 0.476371E+09 | 0.129312E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-06:51 | 3357.53 | 12-OCT-21:01 | 3005.40 | 30-OCT-16:11 | 1547.29 | 26-OCT-15:12 | 717.53 | 12-OCT-21:01 | 0.00 | 01-OCT-00:10 |
| November | 0.155589E+09 | 38381658.52 | 166.48 | 0.123130E+09 | 32459028.35 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 3314.78 | 05-NOV-08:51 | 2635.74 | 03-NOV-15:12 | 1176.53 | 04-NOV-18:14 | 710.46 | 05-NOV-08:51 | 0.00 | 01-NOV-00:10 |
| December | 5466501.68 | 1345735.37 | 8.17 | 4096943.51 | 1369558.17 | 0.00 | 1.00 | 16-DEC-16:12 | 0.00 | 01-DEC-00:10 | 3039.33 | 16-DEC-16:12 | 2299.88 | 16-DEC-16:12 | 886.27 | 01-DEC-09:01 | 660.11 | 16-DEC-16:12 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.109019E+11 | 0.262626E+10 | 3962.13 | 0.854903E+10 | 0.235289E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 4277605.33 | 1053780.13 | 5.11 | 3407664.37 | 772853.22 | 0.00 | 1.00 | 0.00 | 3004.64 | 2299.88 | 572.47 | 653.16 | 0.00 | |||||||
| Maximum of Months | 0.265449E+10 | 0.636604E+09 | 614.10 | 0.201634E+10 | 0.638154E+09 | 0.00 | 1.00 | 0.00 | 3645.30 | 3166.10 | 1686.23 | 762.25 | 0.00 |
Report: DXReportMonthly
For: CORRIDORFLR1 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.196426E+10 | 0.499673E+09 | 412.72 | 0.196403E+10 | 233932.87 | 0.00 | 0.09 | 17-JAN-16:55 | 0.00 | 01-JAN-06:01 | 4038.88 | 17-JAN-16:55 | 4038.88 | 17-JAN-16:55 | 131.24 | 11-JAN-18:10 | 1021.06 | 17-JAN-16:55 | 0.00 | 01-JAN-00:10 |
| February | 0.134076E+10 | 0.341252E+09 | 313.40 | 0.134076E+10 | 0.00 | 0.00 | 0.09 | 22-FEB-16:55 | 0.00 | 01-FEB-07:01 | 4024.68 | 22-FEB-16:55 | 4024.68 | 22-FEB-16:55 | 0.00 | 19-FEB-21:40 | 1016.27 | 22-FEB-16:55 | 0.00 | 01-FEB-00:10 |
| March | 0.557283E+10 | 0.140997E+10 | 577.01 | 0.545136E+10 | 0.121463E+09 | 0.00 | 0.21 | 15-MAR-16:10 | 0.00 | 01-MAR-06:01 | 10564.53 | 15-MAR-16:10 | 10125.05 | 15-MAR-16:02 | 1134.81 | 14-MAR-17:01 | 2668.79 | 15-MAR-16:10 | 0.00 | 01-MAR-00:10 |
| April | 0.830645E+10 | 0.209859E+10 | 646.24 | 0.828471E+10 | 21745141.08 | 0.00 | 0.16 | 08-APR-16:00 | 0.00 | 01-APR-06:01 | 7698.17 | 08-APR-16:00 | 7638.10 | 08-APR-15:53 | 407.09 | 30-APR-17:01 | 1924.11 | 08-APR-16:00 | 0.00 | 01-APR-00:10 |
| May | 0.140312E+11 | 0.352603E+10 | 709.45 | 0.136695E+11 | 0.361703E+09 | 0.00 | 0.21 | 10-MAY-16:10 | 0.00 | 01-MAY-06:01 | 10889.80 | 10-MAY-16:20 | 9512.66 | 14-MAY-16:00 | 2054.67 | 14-MAY-17:01 | 2705.71 | 10-MAY-16:20 | 0.00 | 01-MAY-00:10 |
| June | 0.196821E+11 | 0.494146E+10 | 703.29 | 0.178283E+11 | 0.185379E+10 | 0.00 | 0.37 | 17-JUN-16:30 | 0.00 | 01-JUN-06:01 | 19884.31 | 17-JUN-16:30 | 13456.71 | 26-JUN-16:02 | 7252.92 | 27-JUN-17:00 | 5121.51 | 17-JUN-16:30 | 0.00 | 01-JUN-00:10 |
| July | 0.250026E+11 | 0.630613E+10 | 739.51 | 0.212397E+11 | 0.376294E+10 | 0.00 | 0.40 | 20-JUL-16:20 | 0.00 | 03-JUL-06:01 | 21175.44 | 20-JUL-16:20 | 15152.33 | 16-JUL-16:02 | 7358.08 | 15-JUL-16:30 | 5528.75 | 20-JUL-16:20 | 0.00 | 01-JUL-00:10 |
| August | 0.232398E+11 | 0.585840E+10 | 733.77 | 0.207465E+11 | 0.249332E+10 | 0.00 | 0.39 | 13-AUG-16:20 | 0.00 | 01-AUG-06:01 | 21246.04 | 13-AUG-16:20 | 15108.67 | 09-AUG-16:02 | 7217.84 | 13-AUG-16:30 | 5459.38 | 13-AUG-16:20 | 0.00 | 01-AUG-00:10 |
| September | 0.187007E+11 | 0.467139E+10 | 694.55 | 0.172831E+11 | 0.141756E+10 | 0.00 | 0.30 | 16-SEP-16:20 | 0.00 | 01-SEP-06:01 | 15820.32 | 16-SEP-16:20 | 12760.29 | 16-SEP-16:02 | 4633.39 | 14-SEP-17:01 | 4015.46 | 16-SEP-16:20 | 0.00 | 01-SEP-00:10 |
| October | 0.122178E+11 | 0.307453E+10 | 686.28 | 0.120097E+11 | 0.208072E+09 | 0.00 | 0.20 | 11-OCT-16:00 | 0.00 | 01-OCT-06:01 | 9927.04 | 11-OCT-16:00 | 9709.32 | 11-OCT-15:55 | 1785.09 | 26-OCT-07:02 | 2464.10 | 11-OCT-16:00 | 0.00 | 01-OCT-00:10 |
| November | 0.804039E+10 | 0.203229E+10 | 644.52 | 0.800120E+10 | 39188173.93 | 0.00 | 0.16 | 05-NOV-15:00 | 0.00 | 01-NOV-06:01 | 7880.80 | 05-NOV-15:00 | 7575.01 | 05-NOV-15:00 | 626.09 | 05-NOV-07:02 | 1968.33 | 05-NOV-15:00 | 0.00 | 01-NOV-00:10 |
| December | 0.263480E+10 | 0.669677E+09 | 452.23 | 0.263075E+10 | 4055399.11 | 0.00 | 0.10 | 01-DEC-13:00 | 0.00 | 01-DEC-07:01 | 5078.73 | 01-DEC-13:00 | 4778.74 | 01-DEC-13:00 | 299.99 | 01-DEC-13:00 | 1279.14 | 01-DEC-13:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.140734E+12 | 0.354294E+11 | 7312.98 | 0.130450E+12 | 0.102841E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.134076E+10 | 0.341252E+09 | 313.40 | 0.134076E+10 | 0.00 | 0.00 | 0.09 | 0.00 | 4024.68 | 4024.68 | 0.00 | 1016.27 | 0.00 | |||||||
| Maximum of Months | 0.250026E+11 | 0.630613E+10 | 739.51 | 0.212397E+11 | 0.376294E+10 | 0.00 | 0.40 | 0.00 | 21246.04 | 15152.33 | 7358.08 | 5528.75 | 0.00 |
Report: DXReportMonthly
For: CORRIDORFLR2 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.301147E+09 | 74185752.99 | 95.08 | 0.266607E+09 | 34539657.60 | 0.00 | 0.44 | 15-MAR-15:10 | 0.00 | 01-MAR-00:10 | 2148.22 | 15-MAR-15:10 | 2042.09 | 15-MAR-15:02 | 324.22 | 14-MAR-12:35 | 528.55 | 15-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 0.393215E+09 | 98041893.49 | 209.47 | 0.382466E+09 | 10749098.79 | 0.00 | 0.31 | 08-APR-18:11 | 0.00 | 01-APR-00:10 | 1487.64 | 08-APR-18:10 | 1399.73 | 09-APR-15:55 | 111.94 | 09-APR-09:00 | 363.19 | 08-APR-18:10 | 0.00 | 01-APR-00:10 |
| May | 0.226178E+10 | 0.555904E+09 | 670.06 | 0.211993E+10 | 0.141852E+09 | 0.00 | 0.50 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 2515.76 | 14-MAY-15:00 | 2206.69 | 14-MAY-15:00 | 481.83 | 24-MAY-09:00 | 617.62 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
| June | 0.487025E+10 | 0.117133E+10 | 717.85 | 0.417075E+10 | 0.699504E+09 | 0.00 | 0.69 | 27-JUN-13:00 | 0.00 | 14-JUN-03:10 | 3798.98 | 27-JUN-15:20 | 2947.80 | 12-JUN-15:02 | 1097.03 | 27-JUN-15:10 | 941.32 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.675688E+10 | 0.161567E+10 | 744.00 | 0.539747E+10 | 0.135941E+10 | 0.00 | 0.74 | 19-JUL-15:02 | 0.17 | 06-JUL-05:00 | 3933.80 | 20-JUL-15:30 | 3099.28 | 19-JUL-15:02 | 1163.26 | 16-JUL-07:51 | 1003.59 | 19-JUL-15:02 | 0.00 | 01-JUL-00:10 |
| August | 0.601245E+10 | 0.144495E+10 | 744.00 | 0.506825E+10 | 0.944205E+09 | 0.00 | 0.73 | 13-AUG-15:20 | 0.12 | 31-AUG-04:00 | 3935.00 | 13-AUG-15:30 | 3087.67 | 10-AUG-15:12 | 1134.96 | 14-AUG-07:55 | 981.30 | 13-AUG-15:20 | 0.00 | 01-AUG-00:10 |
| September | 0.409880E+10 | 0.987049E+09 | 707.87 | 0.354910E+10 | 0.549700E+09 | 0.00 | 0.63 | 15-SEP-20:40 | 0.00 | 29-SEP-02:00 | 3403.65 | 15-SEP-20:40 | 2752.70 | 16-SEP-15:23 | 853.61 | 17-SEP-08:31 | 791.30 | 16-SEP-14:02 | 0.00 | 01-SEP-00:10 |
| October | 0.994783E+09 | 0.246004E+09 | 393.44 | 0.911166E+09 | 83616034.04 | 0.00 | 0.45 | 11-OCT-17:00 | 0.00 | 03-OCT-00:20 | 2225.47 | 11-OCT-17:00 | 2090.78 | 11-OCT-16:53 | 309.02 | 12-OCT-16:31 | 531.21 | 11-OCT-17:00 | 0.00 | 01-OCT-00:10 |
| November | 0.157967E+09 | 39620088.14 | 96.28 | 0.147216E+09 | 10751752.93 | 0.00 | 0.26 | 05-NOV-08:52 | 0.00 | 01-NOV-00:10 | 1266.38 | 05-NOV-08:52 | 1070.07 | 05-NOV-08:52 | 196.78 | 05-NOV-09:00 | 311.05 | 05-NOV-08:52 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.258473E+11 | 0.623276E+10 | 4378.05 | 0.220130E+11 | 0.383433E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.675688E+10 | 0.161567E+10 | 744.00 | 0.539747E+10 | 0.135941E+10 | 0.00 | 0.74 | 0.17 | 3935.00 | 3099.28 | 1163.26 | 1003.59 | 0.00 |
Report: DXReportMonthly
For: CORRIDORFLR3 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 82623944.50 | 20648868.30 | 38.84 | 68831291.03 | 13792653.46 | 0.00 | 0.32 | 15-MAR-15:10 | 0.00 | 01-MAR-00:10 | 1312.40 | 15-MAR-15:20 | 1174.07 | 15-MAR-15:02 | 172.37 | 14-MAR-15:12 | 328.63 | 15-MAR-15:10 | 0.00 | 01-MAR-00:10 |
| April | 23512230.59 | 5932552.43 | 23.98 | 20871666.78 | 2640563.81 | 0.00 | 0.13 | 09-APR-16:00 | 0.00 | 01-APR-00:10 | 508.61 | 09-APR-16:00 | 448.76 | 09-APR-15:55 | 62.51 | 08-APR-18:10 | 127.70 | 09-APR-16:00 | 0.00 | 01-APR-00:10 |
| May | 0.627586E+09 | 0.155846E+09 | 317.27 | 0.551265E+09 | 76321058.26 | 0.00 | 0.42 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 | 1778.06 | 14-MAY-15:00 | 1448.57 | 14-MAY-15:00 | 348.74 | 24-MAY-09:00 | 441.44 | 14-MAY-15:00 | 0.00 | 01-MAY-00:10 |
| June | 0.302383E+10 | 0.732842E+09 | 655.43 | 0.236822E+10 | 0.655612E+09 | 0.00 | 0.69 | 27-JUN-13:00 | 0.00 | 04-JUN-01:50 | 3218.69 | 27-JUN-15:23 | 2376.32 | 12-JUN-15:02 | 1110.93 | 27-JUN-15:10 | 790.61 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.494779E+10 | 0.119154E+10 | 744.00 | 0.363199E+10 | 0.131580E+10 | 0.00 | 0.75 | 19-JUL-15:02 | 0.04 | 06-JUL-05:00 | 3374.78 | 20-JUL-15:30 | 2493.53 | 19-JUL-15:02 | 1121.19 | 16-JUL-08:61 | 856.86 | 19-JUL-15:02 | 0.00 | 01-JUL-00:10 |
| August | 0.399275E+10 | 0.969779E+09 | 734.94 | 0.310789E+10 | 0.884867E+09 | 0.00 | 0.70 | 13-AUG-15:30 | 0.00 | 31-AUG-01:50 | 3211.05 | 13-AUG-15:30 | 2404.09 | 10-AUG-15:23 | 1064.12 | 14-AUG-07:55 | 800.30 | 13-AUG-15:30 | 0.00 | 01-AUG-00:10 |
| September | 0.187933E+10 | 0.457306E+09 | 544.12 | 0.145644E+10 | 0.422892E+09 | 0.00 | 0.58 | 16-SEP-15:23 | 0.00 | 01-SEP-00:10 | 2562.82 | 16-SEP-15:23 | 2025.60 | 16-SEP-15:23 | 786.96 | 17-SEP-08:52 | 624.68 | 16-SEP-15:23 | 0.00 | 01-SEP-00:10 |
| October | 0.104785E+09 | 26208138.37 | 67.97 | 87935844.36 | 16849115.08 | 0.00 | 0.26 | 11-OCT-17:00 | 0.00 | 01-OCT-00:10 | 1052.87 | 11-OCT-17:00 | 923.66 | 11-OCT-16:53 | 204.71 | 12-OCT-16:21 | 258.90 | 11-OCT-17:00 | 0.00 | 01-OCT-00:10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.146822E+11 | 0.356010E+10 | 3126.55 | 0.112934E+11 | 0.338878E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.494779E+10 | 0.119154E+10 | 744.00 | 0.363199E+10 | 0.131580E+10 | 0.00 | 0.75 | 0.04 | 3374.78 | 2493.53 | 1121.19 | 856.86 | 0.00 |
Report: DXReportMonthly
For: CORRIDORFLR4 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.124643E+09 | 30984400.01 | 29.46 | 0.108888E+09 | 15755307.45 | 0.00 | 0.40 | 15-MAR-14:02 | 0.00 | 01-MAR-00:10 | 2481.24 | 15-MAR-14:13 | 2351.25 | 15-MAR-14:13 | 429.43 | 14-MAR-13:30 | 619.90 | 15-MAR-14:02 | 0.00 | 01-MAR-00:10 |
| April | 0.169621E+09 | 42494625.90 | 75.42 | 0.166246E+09 | 3375349.53 | 0.00 | 0.24 | 08-APR-14:10 | 0.00 | 01-APR-00:10 | 1429.05 | 08-APR-14:10 | 1374.32 | 08-APR-14:02 | 68.02 | 09-APR-16:10 | 352.89 | 08-APR-14:10 | 0.00 | 01-APR-00:10 |
| May | 0.114226E+10 | 0.281028E+09 | 290.13 | 0.107680E+10 | 65454730.65 | 0.00 | 0.50 | 14-MAY-14:35 | 0.00 | 01-MAY-00:10 | 3259.42 | 14-MAY-14:35 | 2853.96 | 14-MAY-14:50 | 436.93 | 14-MAY-14:00 | 794.34 | 14-MAY-14:35 | 0.00 | 01-MAY-00:10 |
| June | 0.349954E+10 | 0.851797E+09 | 530.86 | 0.294187E+10 | 0.557667E+09 | 0.00 | 0.72 | 27-JUN-13:10 | 0.00 | 01-JUN-00:10 | 4908.16 | 27-JUN-13:30 | 3873.03 | 12-JUN-14:00 | 1366.95 | 27-JUN-08:11 | 1235.78 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.534360E+10 | 0.130237E+10 | 662.80 | 0.418269E+10 | 0.116091E+10 | 0.00 | 0.74 | 19-JUL-15:02 | 0.00 | 01-JUL-00:40 | 4876.66 | 19-JUL-15:10 | 4008.09 | 21-JUL-13:50 | 1413.86 | 16-JUL-08:11 | 1252.07 | 19-JUL-15:10 | 0.00 | 01-JUL-00:10 |
| August | 0.418407E+10 | 0.102615E+10 | 596.62 | 0.346425E+10 | 0.719822E+09 | 0.00 | 0.71 | 13-AUG-15:00 | 0.00 | 01-AUG-02:00 | 4735.19 | 13-AUG-15:02 | 3920.15 | 09-AUG-15:02 | 1254.49 | 15-AUG-08:41 | 1195.77 | 13-AUG-15:00 | 0.00 | 01-AUG-00:10 |
| September | 0.202169E+10 | 0.493772E+09 | 390.29 | 0.168832E+10 | 0.333373E+09 | 0.00 | 0.58 | 16-SEP-14:00 | 0.00 | 01-SEP-00:10 | 3776.65 | 16-SEP-14:00 | 3193.20 | 16-SEP-14:00 | 924.54 | 16-SEP-08:32 | 931.88 | 16-SEP-14:00 | 0.00 | 01-SEP-00:10 |
| October | 0.181587E+09 | 45366248.50 | 76.28 | 0.165286E+09 | 16300243.16 | 0.00 | 0.31 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 | 1885.78 | 11-OCT-16:10 | 1766.18 | 11-OCT-16:02 | 242.03 | 12-OCT-15:10 | 460.46 | 11-OCT-16:10 | 0.00 | 01-OCT-00:10 |
| November | 1484997.00 | 378283.54 | 2.94 | 1305933.95 | 179063.05 | 0.00 | 0.03 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 | 189.17 | 05-NOV-14:00 | 167.00 | 05-NOV-14:00 | 22.17 | 05-NOV-14:00 | 48.14 | 05-NOV-14:00 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.166685E+11 | 0.407434E+10 | 2654.78 | 0.137957E+11 | 0.287283E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.534360E+10 | 0.130237E+10 | 662.80 | 0.418269E+10 | 0.116091E+10 | 0.00 | 0.74 | 0.00 | 4908.16 | 4008.09 | 1413.86 | 1252.07 | 0.00 |
Report: DXReportMonthly
For: SAC_FRONTOFFICE PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 2980766.26 | 758803.67 | 4.89 | 2739040.09 | 241726.17 | 0.00 | 0.05 | 17-JAN-15:50 | 0.00 | 01-JAN-00:10 | 322.89 | 17-JAN-15:50 | 321.65 | 17-JAN-15:50 | 45.56 | 11-JAN-15:50 | 81.99 | 17-JAN-15:50 | 0.00 | 01-JAN-00:10 |
| February | 5510112.41 | 1392084.05 | 4.25 | 5510112.41 | 0.00 | 0.00 | 0.12 | 22-FEB-15:02 | 0.00 | 01-FEB-00:10 | 735.33 | 22-FEB-15:02 | 735.33 | 22-FEB-15:02 | 0.00 | 22-FEB-15:08 | 184.63 | 22-FEB-15:02 | 0.00 | 01-FEB-00:10 |
| March | 0.483185E+09 | 0.118617E+09 | 123.83 | 0.420199E+09 | 62986122.15 | 0.00 | 1.00 | 08-MAR-15:01 | 0.00 | 01-MAR-00:10 | 7830.26 | 14-MAR-12:01 | 7022.00 | 15-MAR-14:01 | 1527.29 | 14-MAR-12:01 | 1696.93 | 14-MAR-12:01 | 0.00 | 01-MAR-00:10 |
| April | 0.719576E+09 | 0.178207E+09 | 230.78 | 0.696650E+09 | 22926222.64 | 0.00 | 1.00 | 03-APR-14:01 | 0.00 | 01-APR-00:10 | 7361.06 | 30-APR-14:01 | 7131.44 | 08-APR-14:01 | 1005.93 | 28-APR-12:01 | 1601.00 | 30-APR-14:01 | 0.00 | 01-APR-00:10 |
| May | 0.223907E+10 | 0.550374E+09 | 545.00 | 0.204316E+10 | 0.195910E+09 | 0.00 | 1.00 | 01-MAY-12:01 | 0.00 | 01-MAY-00:10 | 7797.50 | 17-MAY-14:01 | 7262.47 | 23-MAY-14:01 | 1927.27 | 17-MAY-14:01 | 1694.46 | 10-MAY-14:01 | 0.00 | 01-MAY-00:10 |
| June | 0.489481E+10 | 0.118810E+10 | 690.37 | 0.399041E+10 | 0.904406E+09 | 0.00 | 1.00 | 01-JUN-12:01 | 0.00 | 01-JUN-11:05 | 8098.35 | 17-JUN-14:01 | 7292.20 | 06-JUN-14:01 | 2488.67 | 17-JUN-14:01 | 1842.78 | 27-JUN-12:01 | 0.00 | 01-JUN-00:10 |
| July | 0.730808E+10 | 0.176599E+10 | 743.42 | 0.554714E+10 | 0.176094E+10 | 0.00 | 1.00 | 01-JUL-14:01 | 0.00 | 01-JUL-10:01 | 8179.21 | 05-JUL-12:01 | 7273.28 | 06-JUL-14:01 | 2636.46 | 05-JUL-14:02 | 1861.20 | 15-JUL-14:01 | 0.00 | 01-JUL-00:10 |
| August | 0.692357E+10 | 0.167401E+10 | 743.25 | 0.562744E+10 | 0.129613E+10 | 0.00 | 1.00 | 01-AUG-12:01 | 0.00 | 05-AUG-10:01 | 8081.24 | 07-AUG-12:01 | 7310.58 | 22-AUG-14:01 | 2326.91 | 15-AUG-12:03 | 1827.13 | 13-AUG-14:01 | 0.00 | 01-AUG-00:10 |
| September | 0.521496E+10 | 0.125358E+10 | 706.98 | 0.439858E+10 | 0.816382E+09 | 0.00 | 1.00 | 01-SEP-12:01 | 0.00 | 01-SEP-11:05 | 7994.86 | 14-SEP-12:01 | 7295.03 | 20-SEP-14:01 | 2098.58 | 17-SEP-14:01 | 1742.64 | 15-SEP-12:01 | 0.00 | 01-SEP-00:10 |
| October | 0.221571E+10 | 0.541162E+09 | 501.50 | 0.202599E+10 | 0.189719E+09 | 0.00 | 1.00 | 01-OCT-14:01 | 0.00 | 01-OCT-10:01 | 7544.52 | 01-OCT-14:01 | 7213.59 | 21-OCT-14:01 | 1323.41 | 26-OCT-12:01 | 1637.84 | 01-OCT-14:01 | 0.00 | 01-OCT-00:10 |
| November | 0.668181E+09 | 0.165400E+09 | 221.99 | 0.634403E+09 | 33777967.32 | 0.00 | 1.00 | 01-NOV-12:01 | 0.00 | 01-NOV-02:70 | 7484.91 | 04-NOV-14:01 | 7202.64 | 26-NOV-15:01 | 883.73 | 04-NOV-14:01 | 1626.05 | 04-NOV-14:01 | 0.00 | 01-NOV-00:10 |
| December | 13548118.50 | 3384990.79 | 8.98 | 11426426.92 | 2121691.58 | 0.00 | 1.00 | 01-DEC-13:01 | 0.00 | 01-DEC-00:10 | 7530.32 | 01-DEC-13:01 | 6125.15 | 01-DEC-13:01 | 1405.17 | 01-DEC-13:01 | 1635.05 | 01-DEC-13:01 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.306892E+11 | 0.744097E+10 | 4525.24 | 0.254036E+11 | 0.528555E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 2980766.26 | 758803.67 | 4.25 | 2739040.09 | 0.00 | 0.00 | 0.05 | 0.00 | 322.89 | 321.65 | 0.00 | 81.99 | 0.00 | |||||||
| Maximum of Months | 0.730808E+10 | 0.176599E+10 | 743.42 | 0.562744E+10 | 0.176094E+10 | 0.00 | 1.00 | 0.00 | 8179.21 | 7310.58 | 2636.46 | 1861.20 | 0.00 |
Report: DXReportMonthly
For: SAC_FRONTLOUNGE PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 0.320621E+09 | 80290394.10 | 41.15 | 0.239103E+09 | 81517669.01 | 0.00 | 0.29 | 15-MAR-08:52 | 0.00 | 01-MAR-00:10 | 4711.22 | 15-MAR-08:52 | 3474.77 | 15-MAR-15:02 | 1400.86 | 14-MAR-09:00 | 1150.95 | 15-MAR-08:52 | 0.00 | 01-MAR-00:10 |
| April | 98630113.73 | 24854961.42 | 27.45 | 80808245.03 | 17821868.71 | 0.00 | 0.23 | 08-APR-09:00 | 0.00 | 01-APR-00:10 | 3503.59 | 08-APR-09:00 | 2762.09 | 08-APR-08:53 | 853.00 | 09-APR-08:53 | 866.48 | 08-APR-09:00 | 0.00 | 01-APR-00:10 |
| May | 0.158809E+10 | 0.395536E+09 | 250.74 | 0.123633E+10 | 0.351762E+09 | 0.00 | 0.39 | 29-MAY-07:51 | 0.00 | 01-MAY-00:10 | 6729.70 | 29-MAY-07:51 | 4294.65 | 29-MAY-07:51 | 2447.96 | 29-MAY-07:21 | 1608.46 | 29-MAY-07:51 | 0.00 | 01-MAY-00:10 |
| June | 0.716380E+10 | 0.175292E+10 | 558.29 | 0.486371E+10 | 0.230009E+10 | 0.00 | 0.68 | 27-JUN-08:53 | 0.00 | 01-JUN-00:10 | 12852.46 | 27-JUN-08:53 | 7410.00 | 27-JUN-08:57 | 5521.07 | 27-JUN-08:11 | 3009.00 | 27-JUN-08:53 | 0.00 | 01-JUN-00:10 |
| July | 0.130894E+11 | 0.318128E+10 | 696.71 | 0.819247E+10 | 0.489692E+10 | 0.00 | 0.70 | 21-JUL-08:53 | 0.00 | 01-JUL-00:20 | 13373.34 | 21-JUL-08:02 | 7828.74 | 20-JUL-09:00 | 6315.46 | 21-JUL-05:01 | 3124.31 | 21-JUL-08:45 | 0.00 | 01-JUL-00:10 |
| August | 0.105761E+11 | 0.259179E+10 | 665.87 | 0.723048E+10 | 0.334562E+10 | 0.00 | 0.69 | 15-AUG-08:51 | 0.00 | 01-AUG-01:40 | 13106.72 | 15-AUG-08:51 | 7434.79 | 15-AUG-08:51 | 5674.38 | 14-AUG-07:55 | 3034.81 | 15-AUG-08:51 | 0.00 | 01-AUG-00:10 |
| September | 0.530076E+10 | 0.129631E+10 | 481.34 | 0.358487E+10 | 0.171590E+10 | 0.00 | 0.57 | 16-SEP-08:52 | 0.00 | 01-SEP-00:10 | 10460.05 | 17-SEP-08:52 | 6733.99 | 16-SEP-08:52 | 4410.76 | 17-SEP-09:00 | 2411.49 | 17-SEP-08:52 | 0.00 | 01-SEP-00:10 |
| October | 0.708285E+09 | 0.176946E+09 | 128.31 | 0.519795E+09 | 0.188489E+09 | 0.00 | 0.29 | 12-OCT-08:53 | 0.00 | 01-OCT-00:10 | 4764.98 | 12-OCT-08:53 | 3619.89 | 22-OCT-08:52 | 1943.48 | 01-OCT-08:02 | 1163.15 | 12-OCT-08:53 | 0.00 | 01-OCT-00:10 |
| November | 0.194212E+09 | 48422917.21 | 34.93 | 0.147674E+09 | 46538679.52 | 0.00 | 0.31 | 05-NOV-08:52 | 0.00 | 01-NOV-00:10 | 4957.73 | 05-NOV-08:52 | 3551.92 | 05-NOV-08:52 | 1405.81 | 05-NOV-08:52 | 1208.19 | 05-NOV-08:52 | 0.00 | 01-NOV-00:10 |
| December | 10235538.09 | 2575408.94 | 1.93 | 6981358.88 | 3254179.22 | 0.00 | 0.14 | 01-DEC-10:00 | 0.00 | 01-DEC-00:10 | 2186.35 | 01-DEC-10:00 | 1486.33 | 01-DEC-09:58 | 700.11 | 01-DEC-10:00 | 547.19 | 01-DEC-10:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.390501E+11 | 0.955092E+10 | 2886.72 | 0.261022E+11 | 0.129479E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.130894E+11 | 0.318128E+10 | 696.71 | 0.819247E+10 | 0.489692E+10 | 0.00 | 0.70 | 0.00 | 13373.34 | 7828.74 | 6315.46 | 3124.31 | 0.00 |
Report: DXReportMonthly
For: SAC_MEETINGROOM PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 77442040.67 | 19469928.49 | 38.05 | 58981140.77 | 18460899.90 | 0.00 | 0.85 | 14-MAR-14:01 | 0.00 | 01-MAR-00:10 | 8198.60 | 14-MAR-14:01 | 6282.97 | 15-MAR-14:01 | 2316.28 | 14-MAR-14:01 | 1845.62 | 14-MAR-14:01 | 0.00 | 01-MAR-00:10 |
| April | 8860936.32 | 2244530.23 | 11.42 | 7766044.73 | 1094891.59 | 0.00 | 0.18 | 07-APR-12:15 | 0.00 | 01-APR-00:10 | 1377.24 | 07-APR-12:15 | 1345.15 | 07-APR-12:15 | 159.17 | 08-APR-09:00 | 342.71 | 07-APR-12:15 | 0.00 | 01-APR-00:10 |
| May | 0.406489E+09 | 0.102258E+09 | 286.72 | 0.323891E+09 | 82598534.57 | 0.00 | 0.89 | 10-MAY-14:01 | 0.00 | 01-MAY-00:10 | 8405.27 | 10-MAY-14:01 | 6251.84 | 10-MAY-14:01 | 2297.78 | 10-MAY-17:01 | 1922.73 | 10-MAY-14:01 | 0.00 | 01-MAY-00:10 |
| June | 0.224395E+10 | 0.558546E+09 | 633.73 | 0.156916E+10 | 0.674786E+09 | 0.00 | 1.00 | 08-JUN-14:01 | 0.00 | 01-JUN-09:01 | 10684.37 | 27-JUN-14:01 | 7271.41 | 12-JUN-14:01 | 4982.49 | 08-JUN-14:01 | 2356.01 | 27-JUN-14:01 | 0.00 | 01-JUN-00:10 |
| July | 0.401643E+10 | 0.998695E+09 | 736.16 | 0.261665E+10 | 0.139978E+10 | 0.00 | 1.00 | 05-JUL-14:01 | 0.00 | 01-JUL-11:05 | 10927.46 | 05-JUL-14:01 | 7187.01 | 14-JUL-14:01 | 5672.93 | 05-JUL-14:01 | 2421.98 | 20-JUL-14:01 | 0.00 | 01-JUL-00:10 |
| August | 0.336501E+10 | 0.841522E+09 | 721.76 | 0.239401E+10 | 0.971000E+09 | 0.00 | 1.00 | 07-AUG-14:01 | 0.00 | 01-AUG-09:01 | 10700.98 | 15-AUG-14:01 | 7519.53 | 09-AUG-14:01 | 5057.86 | 28-AUG-17:01 | 2349.53 | 14-AUG-14:01 | 0.00 | 01-AUG-00:10 |
| September | 0.164363E+10 | 0.408204E+09 | 599.02 | 0.115612E+10 | 0.487512E+09 | 0.00 | 1.00 | 13-SEP-14:01 | 0.00 | 01-SEP-09:01 | 10526.07 | 14-SEP-14:01 | 6651.38 | 21-SEP-14:01 | 4753.36 | 14-SEP-14:01 | 2283.71 | 15-SEP-14:01 | 0.00 | 01-SEP-00:10 |
| October | 0.184036E+09 | 46506905.47 | 172.42 | 0.141648E+09 | 42388106.99 | 0.00 | 0.76 | 11-OCT-14:01 | 0.00 | 01-OCT-09:01 | 6695.12 | 11-OCT-14:01 | 5698.58 | 11-OCT-14:01 | 1350.44 | 12-OCT-14:01 | 1519.04 | 11-OCT-14:01 | 0.00 | 01-OCT-00:10 |
| November | 18112193.59 | 4564729.70 | 13.59 | 13159745.88 | 4952447.72 | 0.00 | 0.20 | 16-NOV-13:05 | 0.00 | 01-NOV-00:10 | 1546.52 | 16-NOV-13:05 | 1262.94 | 16-NOV-13:05 | 438.70 | 05-NOV-09:00 | 384.49 | 16-NOV-13:05 | 0.00 | 01-NOV-00:10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.119640E+11 | 0.298201E+10 | 3212.87 | 0.828139E+10 | 0.368257E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.401643E+10 | 0.998695E+09 | 736.16 | 0.261665E+10 | 0.139978E+10 | 0.00 | 1.00 | 0.00 | 10927.46 | 7519.53 | 5672.93 | 2421.98 | 0.00 |
Report: DXReportMonthly
For: SAC_EMPLOYEELOUNGE PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.178461E+10 | 0.445569E+09 | 468.13 | 0.177921E+10 | 5398453.85 | 0.00 | 0.30 | 11-JAN-13:00 | 0.00 | 01-JAN-02:00 | 3145.69 | 11-JAN-13:00 | 2789.44 | 11-JAN-12:55 | 356.67 | 11-JAN-13:00 | 768.78 | 11-JAN-13:00 | 0.00 | 01-JAN-00:10 |
| February | 0.147046E+10 | 0.367245E+09 | 381.23 | 0.146986E+10 | 604966.60 | 0.00 | 0.29 | 22-FEB-17:02 | 0.00 | 01-FEB-00:10 | 2903.84 | 22-FEB-17:02 | 2903.84 | 22-FEB-17:02 | 169.99 | 01-FEB-13:00 | 710.47 | 22-FEB-17:02 | 0.00 | 01-FEB-00:10 |
| March | 0.321424E+10 | 0.796615E+09 | 615.71 | 0.312169E+10 | 92553722.26 | 0.00 | 0.47 | 14-MAR-12:00 | 0.00 | 01-MAR-00:10 | 5356.39 | 14-MAR-12:00 | 4471.45 | 15-MAR-12:00 | 943.23 | 14-MAR-12:00 | 1268.08 | 14-MAR-12:00 | 0.00 | 01-MAR-00:10 |
| April | 0.390266E+10 | 0.965702E+09 | 703.00 | 0.386258E+10 | 40084250.83 | 0.00 | 0.38 | 07-APR-11:55 | 0.00 | 03-APR-03:00 | 4023.27 | 20-APR-12:00 | 3983.05 | 07-APR-11:55 | 431.03 | 28-APR-12:00 | 971.09 | 20-APR-12:00 | 0.00 | 01-APR-00:10 |
| May | 0.563121E+10 | 0.138614E+10 | 744.00 | 0.540739E+10 | 0.223823E+09 | 0.00 | 0.46 | 10-MAY-12:00 | 0.03 | 01-MAY-06:00 | 5123.92 | 10-MAY-12:00 | 4283.54 | 10-MAY-11:55 | 909.21 | 17-MAY-12:00 | 1217.03 | 10-MAY-12:00 | 0.00 | 01-MAY-00:10 |
| June | 0.732908E+10 | 0.180003E+10 | 720.00 | 0.648372E+10 | 0.845359E+09 | 0.00 | 0.57 | 27-JUN-12:00 | 0.06 | 14-JUN-04:00 | 6448.26 | 27-JUN-12:00 | 4918.41 | 27-JUN-12:00 | 1530.44 | 27-JUN-11:50 | 1663.41 | 27-JUN-12:00 | 0.00 | 01-JUN-00:10 |
| July | 0.915221E+10 | 0.225485E+10 | 744.00 | 0.755368E+10 | 0.159853E+10 | 0.00 | 0.58 | 20-JUL-12:00 | 0.12 | 06-JUL-04:00 | 6531.14 | 20-JUL-12:00 | 5040.18 | 21-JUL-12:00 | 1603.10 | 05-JUL-12:00 | 1649.25 | 20-JUL-12:00 | 0.00 | 01-JUL-00:10 |
| August | 0.859998E+10 | 0.211851E+10 | 744.00 | 0.746126E+10 | 0.113872E+10 | 0.00 | 0.58 | 10-AUG-12:00 | 0.12 | 03-AUG-04:00 | 6441.69 | 10-AUG-12:00 | 5108.25 | 10-AUG-12:00 | 1628.26 | 15-AUG-12:00 | 1665.66 | 10-AUG-12:00 | 0.00 | 01-AUG-00:10 |
| September | 0.717246E+10 | 0.175108E+10 | 720.00 | 0.646347E+10 | 0.708997E+09 | 0.00 | 0.55 | 15-SEP-12:00 | 0.07 | 30-SEP-04:00 | 6249.90 | 15-SEP-12:00 | 4950.07 | 21-SEP-11:55 | 1369.26 | 15-SEP-12:00 | 1512.60 | 15-SEP-12:00 | 0.00 | 01-SEP-00:10 |
| October | 0.516629E+10 | 0.127288E+10 | 743.67 | 0.499668E+10 | 0.169616E+09 | 0.00 | 0.48 | 11-OCT-11:55 | 0.00 | 17-OCT-03:50 | 5207.48 | 11-OCT-11:55 | 4731.13 | 11-OCT-12:00 | 716.08 | 12-OCT-12:00 | 1236.35 | 11-OCT-11:55 | 0.00 | 01-OCT-00:10 |
| November | 0.378801E+10 | 0.938686E+09 | 713.29 | 0.374633E+10 | 41679847.33 | 0.00 | 0.41 | 16-NOV-13:00 | 0.00 | 24-NOV-01:40 | 4435.47 | 16-NOV-13:00 | 4021.36 | 16-NOV-13:00 | 414.11 | 16-NOV-13:00 | 1064.38 | 16-NOV-13:00 | 0.00 | 01-NOV-00:10 |
| December | 0.198866E+10 | 0.496443E+09 | 530.51 | 0.198076E+10 | 7896808.79 | 0.00 | 0.36 | 01-DEC-13:00 | 0.00 | 04-DEC-00:55 | 3907.39 | 01-DEC-13:00 | 3304.85 | 01-DEC-13:00 | 602.54 | 01-DEC-13:00 | 944.33 | 01-DEC-13:00 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.591999E+11 | 0.145938E+11 | 7827.54 | 0.543266E+11 | 0.487326E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 0.147046E+10 | 0.367245E+09 | 381.23 | 0.146986E+10 | 604966.60 | 0.00 | 0.29 | 0.00 | 2903.84 | 2789.44 | 169.99 | 710.47 | 0.00 | |||||||
| Maximum of Months | 0.915221E+10 | 0.225485E+10 | 744.00 | 0.755368E+10 | 0.159853E+10 | 0.00 | 0.58 | 0.12 | 6531.14 | 5108.25 | 1628.26 | 1665.66 | 0.00 |
Report: DXReportMonthly
For: SAC_EXERCISECENTER PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 173753.81 | 44263.84 | 0.68 | 114865.47 | 58888.33 | 0.00 | 0.05 | 11-JAN-16:10 | 0.00 | 01-JAN-00:10 | 137.19 | 11-JAN-16:10 | 91.21 | 11-JAN-16:10 | 45.98 | 11-JAN-16:10 | 34.82 | 11-JAN-16:10 | 0.00 | 01-JAN-00:10 |
| February | 1861778.47 | 471821.90 | 4.98 | 1778646.43 | 83132.05 | 0.00 | 0.09 | 22-FEB-17:00 | 0.00 | 01-FEB-00:10 | 204.01 | 22-FEB-17:00 | 196.40 | 22-FEB-16:55 | 8.49 | 22-FEB-19:20 | 51.52 | 22-FEB-17:00 | 0.00 | 01-FEB-00:10 |
| March | 0.177171E+09 | 43023656.51 | 80.00 | 0.133038E+09 | 44133586.75 | 0.00 | 0.60 | 15-MAR-15:02 | 0.00 | 01-MAR-00:10 | 1708.65 | 15-MAR-15:02 | 1408.20 | 15-MAR-15:02 | 437.52 | 16-MAR-15:02 | 407.75 | 15-MAR-15:02 | 0.00 | 01-MAR-00:10 |
| April | 0.259015E+09 | 64086146.72 | 175.14 | 0.221522E+09 | 37492466.94 | 0.00 | 0.43 | 08-APR-15:02 | 0.00 | 01-APR-00:10 | 1174.73 | 08-APR-15:02 | 938.94 | 08-APR-15:02 | 260.27 | 08-APR-18:02 | 281.03 | 08-APR-15:02 | 0.00 | 01-APR-00:10 |
| May | 0.953270E+09 | 0.232830E+09 | 436.47 | 0.767996E+09 | 0.185274E+09 | 0.00 | 0.65 | 14-MAY-15:02 | 0.00 | 01-MAY-00:10 | 1899.25 | 14-MAY-15:02 | 1418.74 | 14-MAY-15:02 | 536.14 | 17-MAY-15:02 | 450.62 | 14-MAY-15:02 | 0.00 | 01-MAY-00:10 |
| June | 0.213967E+10 | 0.509594E+09 | 564.71 | 0.150698E+10 | 0.632698E+09 | 0.00 | 0.83 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 | 2724.89 | 27-JUN-15:02 | 1746.35 | 12-JUN-15:02 | 1212.83 | 27-JUN-15:02 | 638.91 | 27-JUN-13:00 | 0.00 | 01-JUN-00:10 |
| July | 0.333760E+10 | 0.787313E+09 | 677.55 | 0.215083E+10 | 0.118677E+10 | 0.00 | 0.89 | 19-JUL-15:02 | 0.00 | 01-JUL-00:10 | 2907.61 | 20-JUL-15:02 | 1864.79 | 19-JUL-15:02 | 1212.27 | 20-JUL-21:00 | 684.68 | 19-JUL-15:02 | 0.00 | 01-JUL-00:10 |
| August | 0.291284E+10 | 0.691926E+09 | 651.74 | 0.204155E+10 | 0.871295E+09 | 0.00 | 0.92 | 13-AUG-15:02 | 0.00 | 01-AUG-01:30 | 2974.73 | 13-AUG-15:02 | 1918.15 | 18-AUG-15:02 | 1105.11 | 13-AUG-15:55 | 704.88 | 13-AUG-15:02 | 0.00 | 01-AUG-00:10 |
| September | 0.202129E+10 | 0.479811E+09 | 543.36 | 0.144202E+10 | 0.579275E+09 | 0.00 | 0.79 | 16-SEP-15:23 | 0.00 | 01-SEP-00:10 | 2413.30 | 16-SEP-15:02 | 1851.62 | 21-SEP-15:02 | 945.69 | 15-SEP-19:32 | 563.65 | 16-SEP-15:02 | 0.00 | 01-SEP-00:10 |
| October | 0.689228E+09 | 0.167724E+09 | 321.45 | 0.536669E+09 | 0.152559E+09 | 0.00 | 0.65 | 11-OCT-15:02 | 0.00 | 01-OCT-00:10 | 1858.62 | 11-OCT-15:02 | 1538.05 | 11-OCT-15:02 | 506.19 | 12-OCT-15:02 | 428.56 | 11-OCT-15:02 | 0.00 | 01-OCT-00:10 |
| November | 0.193623E+09 | 47809561.09 | 131.57 | 0.153522E+09 | 40101041.49 | 0.00 | 0.41 | 05-NOV-15:02 | 0.00 | 01-NOV-00:10 | 1126.82 | 05-NOV-15:02 | 821.39 | 16-NOV-16:55 | 318.14 | 05-NOV-15:02 | 270.23 | 05-NOV-15:02 | 0.00 | 01-NOV-00:10 |
| December | 1385591.46 | 350831.33 | 2.74 | 944754.82 | 440836.64 | 0.00 | 0.09 | 01-DEC-08:55 | 0.00 | 01-DEC-00:10 | 236.67 | 01-DEC-08:55 | 167.23 | 01-DEC-08:55 | 75.14 | 01-DEC-11:00 | 59.73 | 01-DEC-08:55 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.126871E+11 | 0.302498E+10 | 3590.41 | 0.895696E+10 | 0.373018E+10 | 0.00 | ||||||||||||||
| Minimum of Months | 173753.81 | 44263.84 | 0.68 | 114865.47 | 58888.33 | 0.00 | 0.05 | 0.00 | 137.19 | 91.21 | 8.49 | 34.82 | 0.00 | |||||||
| Maximum of Months | 0.333760E+10 | 0.787313E+09 | 677.55 | 0.215083E+10 | 0.118677E+10 | 0.00 | 0.92 | 0.00 | 2974.73 | 1918.15 | 1212.83 | 704.88 | 0.00 |
Report: DXReportMonthly
For: SAC_RESTROOM PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 8870905.13 | 2233590.18 | 68.44 | 6791781.92 | 2079123.21 | 0.00 | 0.33 | 18-JAN-15:01 | 0.00 | 01-JAN-00:10 | 334.38 | 18-JAN-15:01 | 269.54 | 18-JAN-15:01 | 64.84 | 18-JAN-15:01 | 80.96 | 18-JAN-15:01 | 0.00 | 01-JAN-00:10 |
| February | 87965.11 | 22322.41 | 3.00 | 67482.32 | 20482.80 | 0.00 | 0.01 | 19-FEB-17:01 | 0.00 | 01-FEB-00:10 | 13.00 | 19-FEB-17:01 | 10.00 | 19-FEB-17:01 | 3.00 | 19-FEB-17:01 | 3.30 | 19-FEB-17:01 | 0.00 | 01-FEB-00:10 |
| March | 0.136144E+09 | 33719532.03 | 309.66 | 0.114830E+09 | 21313858.55 | 0.00 | 0.39 | 15-MAR-16:40 | 0.00 | 01-MAR-00:10 | 383.98 | 15-MAR-16:40 | 345.55 | 15-MAR-16:33 | 81.69 | 10-MAR-17:59 | 94.24 | 15-MAR-16:40 | 0.00 | 01-MAR-00:10 |
| April | 0.283106E+09 | 70552504.65 | 648.39 | 0.247636E+09 | 35469999.92 | 0.00 | 0.32 | 09-APR-15:55 | 0.00 | 02-APR-00:40 | 317.42 | 09-APR-15:55 | 289.51 | 09-APR-16:02 | 44.99 | 06-APR-16:42 | 77.23 | 09-APR-15:55 | 0.00 | 01-APR-00:10 |
| May | 0.655731E+09 | 0.160849E+09 | 744.00 | 0.596061E+09 | 59669911.16 | 0.00 | 0.40 | 31-MAY-16:40 | 0.09 | 07-MAY-05:00 | 412.06 | 24-MAY-09:00 | 372.72 | 23-MAY-16:43 | 60.42 | 24-MAY-09:00 | 98.76 | 24-MAY-09:00 | 0.00 | 01-MAY-00:10 |
| June | 0.103278E+10 | 0.249397E+09 | 720.00 | 0.950302E+09 | 82473273.00 | 0.00 | 0.58 | 27-JUN-16:40 | 0.18 | 14-JUN-04:00 | 589.11 | 27-JUN-16:30 | 518.56 | 12-JUN-15:55 | 88.10 | 18-JUN-09:00 | 144.63 | 12-JUN-15:10 | 0.00 | 01-JUN-00:10 |
| July | 0.126345E+10 | 0.305048E+09 | 744.00 | 0.116056E+10 | 0.102883E+09 | 0.00 | 0.62 | 20-JUL-16:20 | 0.33 | 07-JUL-04:00 | 618.44 | 20-JUL-16:20 | 554.20 | 20-JUL-16:02 | 93.24 | 21-JUL-09:00 | 158.77 | 20-JUL-16:20 | 0.00 | 01-JUL-00:10 |
| August | 0.126749E+10 | 0.304799E+09 | 744.00 | 0.117468E+10 | 92810650.04 | 0.00 | 0.62 | 10-AUG-16:10 | 0.31 | 31-AUG-04:00 | 612.80 | 10-AUG-16:30 | 571.10 | 09-AUG-16:13 | 85.66 | 14-AUG-09:00 | 156.78 | 10-AUG-16:00 | 0.00 | 01-AUG-00:10 |
| September | 0.106459E+10 | 0.255173E+09 | 720.00 | 0.988047E+09 | 76544834.17 | 0.00 | 0.59 | 16-SEP-15:55 | 0.19 | 30-SEP-05:00 | 595.25 | 17-SEP-09:00 | 544.17 | 16-SEP-16:02 | 77.78 | 17-SEP-09:00 | 143.65 | 16-SEP-15:55 | 0.00 | 01-SEP-00:10 |
| October | 0.676146E+09 | 0.165469E+09 | 744.00 | 0.620439E+09 | 55707545.12 | 0.00 | 0.46 | 12-OCT-16:40 | 0.09 | 18-OCT-04:00 | 469.94 | 12-OCT-16:40 | 427.48 | 12-OCT-16:31 | 60.66 | 26-OCT-09:00 | 111.74 | 12-OCT-16:40 | 0.00 | 01-OCT-00:10 |
| November | 0.365722E+09 | 91006045.13 | 717.56 | 0.331363E+09 | 34358960.36 | 0.00 | 0.36 | 05-NOV-09:00 | 0.00 | 21-NOV-04:40 | 361.29 | 05-NOV-09:00 | 324.77 | 05-NOV-15:00 | 45.61 | 05-NOV-09:00 | 87.28 | 05-NOV-09:00 | 0.00 | 01-NOV-00:10 |
| December | 38874899.71 | 9794052.79 | 238.98 | 32271224.39 | 6603675.33 | 0.00 | 0.33 | 15-DEC-13:01 | 0.00 | 01-DEC-00:20 | 355.46 | 15-DEC-13:01 | 245.74 | 15-DEC-13:01 | 109.72 | 15-DEC-13:01 | 85.36 | 15-DEC-13:01 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.679299E+10 | 0.164806E+10 | 6402.03 | 0.622305E+10 | 0.569935E+09 | 0.00 | ||||||||||||||
| Minimum of Months | 87965.11 | 22322.41 | 3.00 | 67482.32 | 20482.80 | 0.00 | 0.01 | 0.00 | 13.00 | 10.00 | 3.00 | 3.30 | 0.00 | |||||||
| Maximum of Months | 0.126749E+10 | 0.305048E+09 | 744.00 | 0.117468E+10 | 0.102883E+09 | 0.00 | 0.62 | 0.33 | 618.44 | 571.10 | 109.72 | 158.77 | 0.00 |
Report: WindowReportMonthly
For: W_CORRIDORFLR1_2_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 24.34 | 5.73 | 18.61 | 3.06 | 170.44 | 0.00 | 0.00 | 0.00 |
| February | 39.44 | 10.18 | 29.26 | 9.02 | 160.85 | 0.00 | 0.00 | 0.00 |
| March | 62.00 | 26.65 | 35.35 | 36.05 | 111.69 | 0.00 | 0.00 | 0.00 |
| April | 75.42 | 30.87 | 44.55 | 56.17 | 81.68 | 0.00 | 0.00 | 0.00 |
| May | 89.03 | 40.20 | 48.83 | 84.51 | 52.87 | 0.00 | 0.00 | 0.00 |
| June | 107.57 | 50.61 | 56.96 | 121.69 | 32.90 | 0.00 | 0.00 | 0.00 |
| July | 96.06 | 42.06 | 54.00 | 119.38 | 22.44 | 0.00 | 0.00 | 0.00 |
| August | 86.78 | 36.81 | 49.98 | 104.85 | 29.49 | 0.00 | 0.00 | 0.00 |
| September | 68.33 | 29.53 | 38.81 | 68.89 | 48.77 | 0.00 | 0.00 | 0.00 |
| October | 44.28 | 15.60 | 28.68 | 27.66 | 83.96 | 0.00 | 0.00 | 0.00 |
| November | 26.03 | 7.39 | 18.64 | 9.22 | 113.48 | 0.00 | 0.00 | 0.00 |
| December | 22.70 | 4.92 | 17.78 | 2.76 | 164.82 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 61.93 | 25.12 | 36.82 | 53.86 | 89.08 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 22.70 | 4.92 | 17.78 | 2.76 | 22.44 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 107.57 | 50.61 | 56.96 | 121.69 | 170.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: D_CORRIDORFLR1_16_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 27.91 | 10.22 | 17.69 | 2.11 | 280.54 | 0.00 | 0.00 | 0.00 |
| February | 33.02 | 8.72 | 24.31 | 2.79 | 282.49 | 0.00 | 0.00 | 0.00 |
| March | 37.29 | 7.12 | 30.16 | 5.64 | 209.29 | 0.00 | 0.00 | 0.00 |
| April | 47.24 | 8.43 | 38.81 | 10.41 | 149.96 | 0.00 | 0.00 | 0.00 |
| May | 51.43 | 6.03 | 45.40 | 21.95 | 91.89 | 0.00 | 0.00 | 0.00 |
| June | 58.80 | 6.37 | 52.43 | 44.15 | 52.31 | 0.00 | 0.00 | 0.00 |
| July | 56.18 | 6.74 | 49.44 | 57.25 | 32.44 | 0.00 | 0.00 | 0.00 |
| August | 51.35 | 6.79 | 44.56 | 48.03 | 46.60 | 0.00 | 0.00 | 0.00 |
| September | 42.41 | 7.21 | 35.19 | 23.04 | 79.82 | 0.00 | 0.00 | 0.00 |
| October | 34.90 | 10.44 | 24.46 | 10.22 | 146.02 | 0.00 | 0.00 | 0.00 |
| November | 25.57 | 9.01 | 16.57 | 6.12 | 192.87 | 0.00 | 0.00 | 0.00 |
| December | 21.42 | 5.65 | 15.76 | 1.13 | 279.35 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 40.66 | 7.72 | 32.94 | 19.52 | 152.95 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 21.42 | 5.65 | 15.76 | 1.13 | 32.44 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 58.80 | 10.44 | 52.43 | 57.25 | 282.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_CORRIDORFLR1_20_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 15.47 | 0.00 | 15.47 | 0.00 | 178.95 | 0.00 | 0.00 | 0.00 |
| February | 23.57 | 0.00 | 23.57 | 0.00 | 169.96 | 0.00 | 0.00 | 0.00 |
| March | 28.59 | 0.00 | 28.59 | 3.19 | 124.74 | 0.00 | 0.00 | 0.00 |
| April | 36.45 | 0.18 | 36.28 | 7.50 | 86.67 | 0.00 | 0.00 | 0.00 |
| May | 42.34 | 1.82 | 40.52 | 19.50 | 52.24 | 0.00 | 0.00 | 0.00 |
| June | 50.91 | 4.33 | 46.58 | 41.85 | 31.06 | 0.00 | 0.00 | 0.00 |
| July | 47.41 | 3.23 | 44.19 | 50.11 | 21.43 | 0.00 | 0.00 | 0.00 |
| August | 41.05 | 0.79 | 40.26 | 39.20 | 29.96 | 0.00 | 0.00 | 0.00 |
| September | 31.11 | 0.01 | 31.10 | 17.86 | 51.64 | 0.00 | 0.00 | 0.00 |
| October | 23.25 | 0.00 | 23.25 | 3.18 | 89.25 | 0.00 | 0.00 | 0.00 |
| November | 15.62 | 0.00 | 15.62 | 0.52 | 118.62 | 0.00 | 0.00 | 0.00 |
| December | 14.48 | 0.00 | 14.48 | 0.00 | 170.86 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 30.89 | 0.87 | 30.02 | 15.35 | 93.40 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 14.48 | 0.00 | 14.48 | 0.00 | 21.43 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 50.91 | 4.33 | 46.58 | 50.11 | 178.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_FRONTLOUNGEFLR1_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.08 | 0.00 | 17.08 | 0.00 | 165.29 | 0.00 | 0.00 | 0.00 |
| February | 26.02 | 0.00 | 26.02 | 0.10 | 156.39 | 0.00 | 0.00 | 0.00 |
| March | 31.56 | 0.00 | 31.56 | 6.66 | 108.50 | 0.00 | 0.00 | 0.00 |
| April | 40.23 | 0.19 | 40.04 | 16.03 | 72.52 | 0.00 | 0.00 | 0.00 |
| May | 46.74 | 2.01 | 44.72 | 32.04 | 43.78 | 0.00 | 0.00 | 0.00 |
| June | 56.19 | 4.78 | 51.41 | 58.06 | 27.58 | 0.00 | 0.00 | 0.00 |
| July | 52.33 | 3.56 | 48.77 | 66.70 | 18.46 | 0.00 | 0.00 | 0.00 |
| August | 45.31 | 0.87 | 44.43 | 53.09 | 26.06 | 0.00 | 0.00 | 0.00 |
| September | 34.34 | 0.02 | 34.32 | 27.46 | 45.55 | 0.00 | 0.00 | 0.00 |
| October | 25.66 | 0.00 | 25.66 | 7.63 | 76.03 | 0.00 | 0.00 | 0.00 |
| November | 17.24 | 0.00 | 17.24 | 1.67 | 101.90 | 0.00 | 0.00 | 0.00 |
| December | 15.98 | 0.00 | 15.98 | 0.03 | 157.44 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 34.09 | 0.96 | 33.13 | 22.60 | 82.93 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 15.98 | 0.00 | 15.98 | 0.00 | 18.46 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 56.19 | 4.78 | 51.41 | 66.70 | 165.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_FRONTLOUNGEFLR1_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.08 | 0.00 | 17.08 | 0.00 | 165.29 | 0.00 | 0.00 | 0.00 |
| February | 26.02 | 0.00 | 26.02 | 0.10 | 156.39 | 0.00 | 0.00 | 0.00 |
| March | 31.56 | 0.00 | 31.56 | 6.66 | 108.50 | 0.00 | 0.00 | 0.00 |
| April | 40.23 | 0.19 | 40.04 | 16.03 | 72.52 | 0.00 | 0.00 | 0.00 |
| May | 46.74 | 2.01 | 44.72 | 32.04 | 43.78 | 0.00 | 0.00 | 0.00 |
| June | 56.19 | 4.78 | 51.41 | 58.06 | 27.58 | 0.00 | 0.00 | 0.00 |
| July | 52.33 | 3.56 | 48.77 | 66.70 | 18.46 | 0.00 | 0.00 | 0.00 |
| August | 45.31 | 0.87 | 44.43 | 53.09 | 26.06 | 0.00 | 0.00 | 0.00 |
| September | 34.34 | 0.02 | 34.32 | 27.46 | 45.55 | 0.00 | 0.00 | 0.00 |
| October | 25.66 | 0.00 | 25.66 | 7.63 | 76.03 | 0.00 | 0.00 | 0.00 |
| November | 17.24 | 0.00 | 17.24 | 1.67 | 101.90 | 0.00 | 0.00 | 0.00 |
| December | 15.98 | 0.00 | 15.98 | 0.03 | 157.44 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 34.09 | 0.96 | 33.13 | 22.60 | 82.93 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 15.98 | 0.00 | 15.98 | 0.00 | 18.46 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 56.19 | 4.78 | 51.41 | 66.70 | 165.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_FRONTLOUNGEFLR1_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.08 | 0.00 | 17.08 | 0.00 | 165.29 | 0.00 | 0.00 | 0.00 |
| February | 26.02 | 0.00 | 26.02 | 0.10 | 156.39 | 0.00 | 0.00 | 0.00 |
| March | 31.56 | 0.00 | 31.56 | 6.66 | 108.50 | 0.00 | 0.00 | 0.00 |
| April | 40.23 | 0.19 | 40.04 | 16.03 | 72.52 | 0.00 | 0.00 | 0.00 |
| May | 46.74 | 2.01 | 44.72 | 32.04 | 43.78 | 0.00 | 0.00 | 0.00 |
| June | 56.19 | 4.78 | 51.41 | 58.06 | 27.58 | 0.00 | 0.00 | 0.00 |
| July | 52.33 | 3.56 | 48.77 | 66.70 | 18.46 | 0.00 | 0.00 | 0.00 |
| August | 45.31 | 0.87 | 44.43 | 53.09 | 26.06 | 0.00 | 0.00 | 0.00 |
| September | 34.34 | 0.02 | 34.32 | 27.46 | 45.55 | 0.00 | 0.00 | 0.00 |
| October | 25.66 | 0.00 | 25.66 | 7.63 | 76.03 | 0.00 | 0.00 | 0.00 |
| November | 17.24 | 0.00 | 17.24 | 1.67 | 101.90 | 0.00 | 0.00 | 0.00 |
| December | 15.98 | 0.00 | 15.98 | 0.03 | 157.44 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 34.09 | 0.96 | 33.13 | 22.60 | 82.93 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 15.98 | 0.00 | 15.98 | 0.00 | 18.46 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 56.19 | 4.78 | 51.41 | 66.70 | 165.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_FRONTLOUNGEFLR1_5_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.08 | 0.00 | 17.08 | 0.00 | 165.29 | 0.00 | 0.00 | 0.00 |
| February | 26.02 | 0.00 | 26.02 | 0.10 | 156.39 | 0.00 | 0.00 | 0.00 |
| March | 31.56 | 0.00 | 31.56 | 6.66 | 108.50 | 0.00 | 0.00 | 0.00 |
| April | 40.23 | 0.19 | 40.04 | 16.03 | 72.52 | 0.00 | 0.00 | 0.00 |
| May | 46.74 | 2.01 | 44.72 | 32.04 | 43.78 | 0.00 | 0.00 | 0.00 |
| June | 56.19 | 4.78 | 51.41 | 58.06 | 27.58 | 0.00 | 0.00 | 0.00 |
| July | 52.33 | 3.56 | 48.77 | 66.70 | 18.46 | 0.00 | 0.00 | 0.00 |
| August | 45.31 | 0.87 | 44.43 | 53.09 | 26.06 | 0.00 | 0.00 | 0.00 |
| September | 34.34 | 0.02 | 34.32 | 27.46 | 45.55 | 0.00 | 0.00 | 0.00 |
| October | 25.66 | 0.00 | 25.66 | 7.63 | 76.03 | 0.00 | 0.00 | 0.00 |
| November | 17.24 | 0.00 | 17.24 | 1.67 | 101.90 | 0.00 | 0.00 | 0.00 |
| December | 15.98 | 0.00 | 15.98 | 0.03 | 157.44 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 34.09 | 0.96 | 33.13 | 22.60 | 82.93 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 15.98 | 0.00 | 15.98 | 0.00 | 18.46 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 56.19 | 4.78 | 51.41 | 66.70 | 165.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_FRONTLOUNGEFLR1_5_0_0_0_4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 17.08 | 0.00 | 17.08 | 0.00 | 165.29 | 0.00 | 0.00 | 0.00 |
| February | 26.02 | 0.00 | 26.02 | 0.10 | 156.39 | 0.00 | 0.00 | 0.00 |
| March | 31.56 | 0.00 | 31.56 | 6.66 | 108.50 | 0.00 | 0.00 | 0.00 |
| April | 40.23 | 0.19 | 40.04 | 16.03 | 72.52 | 0.00 | 0.00 | 0.00 |
| May | 46.74 | 2.01 | 44.72 | 32.04 | 43.78 | 0.00 | 0.00 | 0.00 |
| June | 56.19 | 4.78 | 51.41 | 58.06 | 27.58 | 0.00 | 0.00 | 0.00 |
| July | 52.33 | 3.56 | 48.77 | 66.70 | 18.46 | 0.00 | 0.00 | 0.00 |
| August | 45.31 | 0.87 | 44.43 | 53.09 | 26.06 | 0.00 | 0.00 | 0.00 |
| September | 34.34 | 0.02 | 34.32 | 27.46 | 45.55 | 0.00 | 0.00 | 0.00 |
| October | 25.66 | 0.00 | 25.66 | 7.63 | 76.03 | 0.00 | 0.00 | 0.00 |
| November | 17.24 | 0.00 | 17.24 | 1.67 | 101.90 | 0.00 | 0.00 | 0.00 |
| December | 15.98 | 0.00 | 15.98 | 0.03 | 157.44 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 34.09 | 0.96 | 33.13 | 22.60 | 82.93 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 15.98 | 0.00 | 15.98 | 0.00 | 18.46 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 56.19 | 4.78 | 51.41 | 66.70 | 165.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_MEETINGROOMFLR1_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.87 | 0.00 | 21.87 | 0.00 | 214.88 | 0.00 | 0.00 | 0.00 |
| February | 33.31 | 0.00 | 33.31 | 0.11 | 203.59 | 0.00 | 0.00 | 0.00 |
| March | 40.41 | 0.00 | 40.41 | 8.12 | 143.60 | 0.00 | 0.00 | 0.00 |
| April | 51.51 | 0.25 | 51.27 | 19.58 | 98.78 | 0.00 | 0.00 | 0.00 |
| May | 59.84 | 2.58 | 57.27 | 38.69 | 61.78 | 0.00 | 0.00 | 0.00 |
| June | 71.95 | 6.12 | 65.83 | 71.29 | 37.58 | 0.00 | 0.00 | 0.00 |
| July | 67.01 | 4.56 | 62.45 | 82.52 | 24.69 | 0.00 | 0.00 | 0.00 |
| August | 58.01 | 1.12 | 56.89 | 65.87 | 34.97 | 0.00 | 0.00 | 0.00 |
| September | 43.97 | 0.02 | 43.95 | 33.81 | 62.00 | 0.00 | 0.00 | 0.00 |
| October | 32.85 | 0.00 | 32.85 | 9.23 | 104.11 | 0.00 | 0.00 | 0.00 |
| November | 22.08 | 0.00 | 22.08 | 2.01 | 136.71 | 0.00 | 0.00 | 0.00 |
| December | 20.47 | 0.00 | 20.47 | 0.04 | 204.82 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.65 | 1.23 | 42.42 | 27.79 | 110.16 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.47 | 0.00 | 20.47 | 0.00 | 24.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.95 | 6.12 | 65.83 | 82.52 | 214.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_MEETINGROOMFLR1_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.87 | 0.00 | 21.87 | 0.00 | 214.88 | 0.00 | 0.00 | 0.00 |
| February | 33.31 | 0.00 | 33.31 | 0.11 | 203.59 | 0.00 | 0.00 | 0.00 |
| March | 40.41 | 0.00 | 40.41 | 8.12 | 143.60 | 0.00 | 0.00 | 0.00 |
| April | 51.51 | 0.25 | 51.27 | 19.58 | 98.78 | 0.00 | 0.00 | 0.00 |
| May | 59.84 | 2.58 | 57.27 | 38.69 | 61.78 | 0.00 | 0.00 | 0.00 |
| June | 71.95 | 6.12 | 65.83 | 71.29 | 37.58 | 0.00 | 0.00 | 0.00 |
| July | 67.01 | 4.56 | 62.45 | 82.52 | 24.69 | 0.00 | 0.00 | 0.00 |
| August | 58.01 | 1.12 | 56.89 | 65.87 | 34.97 | 0.00 | 0.00 | 0.00 |
| September | 43.97 | 0.02 | 43.95 | 33.81 | 62.00 | 0.00 | 0.00 | 0.00 |
| October | 32.85 | 0.00 | 32.85 | 9.23 | 104.11 | 0.00 | 0.00 | 0.00 |
| November | 22.08 | 0.00 | 22.08 | 2.01 | 136.71 | 0.00 | 0.00 | 0.00 |
| December | 20.47 | 0.00 | 20.47 | 0.04 | 204.82 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.65 | 1.23 | 42.42 | 27.79 | 110.16 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.47 | 0.00 | 20.47 | 0.00 | 24.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.95 | 6.12 | 65.83 | 82.52 | 214.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_MEETINGROOMFLR1_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.87 | 0.00 | 21.87 | 0.00 | 214.88 | 0.00 | 0.00 | 0.00 |
| February | 33.31 | 0.00 | 33.31 | 0.11 | 203.59 | 0.00 | 0.00 | 0.00 |
| March | 40.41 | 0.00 | 40.41 | 8.12 | 143.60 | 0.00 | 0.00 | 0.00 |
| April | 51.51 | 0.25 | 51.27 | 19.58 | 98.78 | 0.00 | 0.00 | 0.00 |
| May | 59.84 | 2.58 | 57.27 | 38.69 | 61.78 | 0.00 | 0.00 | 0.00 |
| June | 71.95 | 6.12 | 65.83 | 71.29 | 37.58 | 0.00 | 0.00 | 0.00 |
| July | 67.01 | 4.56 | 62.45 | 82.52 | 24.69 | 0.00 | 0.00 | 0.00 |
| August | 58.01 | 1.12 | 56.89 | 65.87 | 34.97 | 0.00 | 0.00 | 0.00 |
| September | 43.97 | 0.02 | 43.95 | 33.81 | 62.00 | 0.00 | 0.00 | 0.00 |
| October | 32.85 | 0.00 | 32.85 | 9.23 | 104.11 | 0.00 | 0.00 | 0.00 |
| November | 22.08 | 0.00 | 22.08 | 2.01 | 136.71 | 0.00 | 0.00 | 0.00 |
| December | 20.47 | 0.00 | 20.47 | 0.04 | 204.82 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.65 | 1.23 | 42.42 | 27.79 | 110.16 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.47 | 0.00 | 20.47 | 0.00 | 24.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.95 | 6.12 | 65.83 | 82.52 | 214.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM101_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.87 | 0.00 | 21.87 | 0.00 | 204.66 | 0.00 | 0.00 | 0.00 |
| February | 33.31 | 0.00 | 33.31 | 0.17 | 190.99 | 0.00 | 0.00 | 0.00 |
| March | 40.41 | 0.00 | 40.41 | 8.30 | 136.76 | 0.00 | 0.00 | 0.00 |
| April | 51.51 | 0.25 | 51.27 | 19.19 | 96.02 | 0.00 | 0.00 | 0.00 |
| May | 59.84 | 2.58 | 57.27 | 38.61 | 59.26 | 0.00 | 0.00 | 0.00 |
| June | 71.95 | 6.12 | 65.83 | 68.36 | 38.16 | 0.00 | 0.00 | 0.00 |
| July | 67.01 | 4.56 | 62.45 | 77.33 | 26.66 | 0.00 | 0.00 | 0.00 |
| August | 58.01 | 1.12 | 56.89 | 61.24 | 37.81 | 0.00 | 0.00 | 0.00 |
| September | 43.97 | 0.02 | 43.95 | 31.49 | 64.06 | 0.00 | 0.00 | 0.00 |
| October | 32.85 | 0.00 | 32.85 | 8.30 | 105.80 | 0.00 | 0.00 | 0.00 |
| November | 22.08 | 0.00 | 22.08 | 1.89 | 137.72 | 0.00 | 0.00 | 0.00 |
| December | 20.47 | 0.00 | 20.47 | 0.03 | 197.64 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.65 | 1.23 | 42.42 | 26.41 | 107.54 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.47 | 0.00 | 20.47 | 0.00 | 26.66 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.95 | 6.12 | 65.83 | 77.33 | 204.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM102_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.87 | 0.00 | 21.87 | 0.00 | 197.81 | 0.00 | 0.00 | 0.00 |
| February | 33.31 | 0.00 | 33.31 | 0.23 | 184.46 | 0.00 | 0.00 | 0.00 |
| March | 40.41 | 0.00 | 40.41 | 9.11 | 130.89 | 0.00 | 0.00 | 0.00 |
| April | 51.51 | 0.25 | 51.27 | 21.03 | 91.06 | 0.00 | 0.00 | 0.00 |
| May | 59.84 | 2.58 | 57.27 | 41.41 | 55.45 | 0.00 | 0.00 | 0.00 |
| June | 71.95 | 6.12 | 65.83 | 71.94 | 35.27 | 0.00 | 0.00 | 0.00 |
| July | 67.01 | 4.56 | 62.45 | 81.03 | 23.93 | 0.00 | 0.00 | 0.00 |
| August | 58.01 | 1.12 | 56.89 | 64.38 | 34.37 | 0.00 | 0.00 | 0.00 |
| September | 43.97 | 0.02 | 43.95 | 33.81 | 59.61 | 0.00 | 0.00 | 0.00 |
| October | 32.85 | 0.00 | 32.85 | 9.46 | 100.01 | 0.00 | 0.00 | 0.00 |
| November | 22.08 | 0.00 | 22.08 | 2.23 | 131.08 | 0.00 | 0.00 | 0.00 |
| December | 20.47 | 0.00 | 20.47 | 0.05 | 190.61 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.65 | 1.23 | 42.42 | 28.07 | 102.47 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.47 | 0.00 | 20.47 | 0.00 | 23.93 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.95 | 6.12 | 65.83 | 81.03 | 197.81 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM103_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.87 | 0.00 | 21.87 | 0.00 | 201.78 | 5.67 | 0.00 | 0.00 |
| February | 33.31 | 0.00 | 33.31 | 0.26 | 189.60 | 13.00 | 0.00 | 0.00 |
| March | 40.41 | 0.00 | 40.41 | 9.73 | 131.20 | 7.67 | 0.00 | 0.00 |
| April | 51.51 | 0.25 | 51.27 | 22.76 | 87.45 | 1.50 | 0.00 | 0.00 |
| May | 59.84 | 2.58 | 57.27 | 44.61 | 50.33 | 0.00 | 0.00 | 0.00 |
| June | 71.95 | 6.12 | 65.83 | 78.04 | 29.77 | 0.00 | 0.00 | 0.00 |
| July | 67.01 | 4.56 | 62.45 | 89.04 | 18.42 | 0.00 | 0.00 | 0.00 |
| August | 58.01 | 1.12 | 56.89 | 70.51 | 27.33 | 0.00 | 0.00 | 0.00 |
| September | 43.97 | 0.02 | 43.95 | 37.10 | 51.85 | 0.00 | 0.00 | 0.00 |
| October | 32.85 | 0.00 | 32.85 | 10.62 | 92.74 | 0.00 | 0.00 | 0.00 |
| November | 22.08 | 0.00 | 22.08 | 2.48 | 125.68 | 2.33 | 0.00 | 0.00 |
| December | 20.47 | 0.00 | 20.47 | 0.06 | 192.23 | 14.33 | 0.00 | 0.00 |
| Annual Sum or Average | 43.65 | 1.23 | 42.42 | 30.63 | 99.41 | 44.50 | 0.00 | 0.00 |
| Minimum of Months | 20.47 | 0.00 | 20.47 | 0.00 | 18.42 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 71.95 | 6.12 | 65.83 | 89.04 | 201.78 | 14.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM104_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.76 | 54.63 | 39.13 | 63.37 | 178.13 | 0.67 | 0.00 | 0.00 |
| February | 107.16 | 51.59 | 55.57 | 68.63 | 173.00 | 4.33 | 0.00 | 0.00 |
| March | 128.95 | 71.54 | 57.41 | 112.37 | 122.48 | 0.00 | 0.00 | 0.00 |
| April | 109.65 | 44.50 | 65.15 | 102.92 | 92.94 | 0.00 | 0.00 | 0.00 |
| May | 94.89 | 27.51 | 67.38 | 100.80 | 58.03 | 0.00 | 0.00 | 0.00 |
| June | 92.53 | 19.82 | 72.72 | 114.71 | 34.52 | 0.00 | 0.00 | 0.00 |
| July | 93.89 | 22.55 | 71.34 | 133.95 | 20.96 | 0.00 | 0.00 | 0.00 |
| August | 104.80 | 33.34 | 71.46 | 143.66 | 29.78 | 0.00 | 0.00 | 0.00 |
| September | 124.44 | 61.37 | 63.07 | 152.01 | 53.50 | 0.00 | 0.00 | 0.00 |
| October | 117.95 | 67.51 | 50.44 | 117.73 | 89.27 | 0.00 | 0.00 | 0.00 |
| November | 84.48 | 47.83 | 36.66 | 70.65 | 121.07 | 0.00 | 0.00 | 0.00 |
| December | 78.60 | 40.69 | 37.91 | 48.88 | 176.29 | 3.33 | 0.00 | 0.00 |
| Annual Sum or Average | 102.55 | 45.21 | 57.35 | 102.67 | 95.42 | 8.33 | 0.00 | 0.00 |
| Minimum of Months | 78.60 | 19.82 | 36.66 | 48.88 | 20.96 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 128.95 | 71.54 | 72.72 | 152.01 | 178.13 | 4.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM105_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.76 | 54.63 | 39.13 | 59.45 | 195.62 | 0.00 | 0.00 | 0.00 |
| February | 107.16 | 51.59 | 55.57 | 62.81 | 190.32 | 0.00 | 0.00 | 0.00 |
| March | 128.95 | 71.54 | 57.41 | 105.88 | 134.22 | 0.00 | 0.00 | 0.00 |
| April | 109.65 | 44.50 | 65.15 | 97.23 | 102.90 | 0.00 | 0.00 | 0.00 |
| May | 94.89 | 27.51 | 67.38 | 95.53 | 65.60 | 0.00 | 0.00 | 0.00 |
| June | 92.53 | 19.82 | 72.72 | 109.47 | 39.29 | 0.00 | 0.00 | 0.00 |
| July | 93.89 | 22.55 | 71.34 | 129.16 | 24.20 | 0.00 | 0.00 | 0.00 |
| August | 104.80 | 33.34 | 71.46 | 139.65 | 33.56 | 0.00 | 0.00 | 0.00 |
| September | 124.44 | 61.37 | 63.07 | 148.41 | 58.71 | 0.00 | 0.00 | 0.00 |
| October | 117.95 | 67.51 | 50.44 | 114.02 | 96.67 | 0.00 | 0.00 | 0.00 |
| November | 84.48 | 47.83 | 36.66 | 67.68 | 132.06 | 0.00 | 0.00 | 0.00 |
| December | 78.60 | 40.69 | 37.91 | 45.61 | 193.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.55 | 45.21 | 57.35 | 98.11 | 105.12 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.60 | 19.82 | 36.66 | 45.61 | 24.20 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 128.95 | 71.54 | 72.72 | 148.41 | 195.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_EMPLOYEELOUNGEFLR1_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.76 | 54.63 | 39.13 | 53.69 | 231.75 | 0.00 | 0.00 | 0.00 |
| February | 107.16 | 51.59 | 55.57 | 55.43 | 224.52 | 0.00 | 0.00 | 0.00 |
| March | 128.95 | 71.54 | 57.41 | 94.14 | 165.38 | 0.00 | 0.00 | 0.00 |
| April | 109.65 | 44.50 | 65.15 | 84.68 | 133.78 | 0.00 | 0.00 | 0.00 |
| May | 94.89 | 27.51 | 67.38 | 81.85 | 92.72 | 0.00 | 0.00 | 0.00 |
| June | 92.53 | 19.82 | 72.72 | 92.15 | 59.51 | 0.00 | 0.00 | 0.00 |
| July | 93.89 | 22.55 | 71.34 | 110.33 | 42.55 | 0.00 | 0.00 | 0.00 |
| August | 104.80 | 33.34 | 71.46 | 123.27 | 54.13 | 0.00 | 0.00 | 0.00 |
| September | 124.44 | 61.37 | 63.07 | 134.88 | 82.79 | 0.00 | 0.00 | 0.00 |
| October | 117.95 | 67.51 | 50.44 | 102.37 | 127.08 | 0.00 | 0.00 | 0.00 |
| November | 84.48 | 47.83 | 36.66 | 60.50 | 168.68 | 0.00 | 0.00 | 0.00 |
| December | 78.60 | 40.69 | 37.91 | 40.93 | 231.70 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.55 | 45.21 | 57.35 | 86.36 | 134.06 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.60 | 19.82 | 36.66 | 40.93 | 42.55 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 128.95 | 71.54 | 72.72 | 134.88 | 231.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_LAUNDRYROOMFLR1_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.76 | 54.63 | 39.13 | 19.98 | 488.51 | 743.67 | 0.00 | 0.00 |
| February | 107.16 | 51.59 | 55.57 | 19.06 | 479.60 | 671.67 | 0.00 | 0.00 |
| March | 128.95 | 71.54 | 57.41 | 35.17 | 397.46 | 743.17 | 0.00 | 0.00 |
| April | 109.65 | 44.50 | 65.15 | 21.33 | 360.77 | 719.33 | 0.00 | 0.00 |
| May | 94.89 | 27.51 | 67.38 | 11.26 | 317.45 | 744.00 | 0.00 | 0.00 |
| June | 92.53 | 19.82 | 72.72 | 5.92 | 269.20 | 719.50 | 0.00 | 0.00 |
| July | 93.89 | 22.55 | 71.34 | 12.49 | 242.38 | 742.83 | 0.00 | 0.00 |
| August | 104.80 | 33.34 | 71.46 | 24.67 | 254.75 | 743.17 | 0.00 | 0.00 |
| September | 124.44 | 61.37 | 63.07 | 44.70 | 295.39 | 716.33 | 0.00 | 0.00 |
| October | 117.95 | 67.51 | 50.44 | 38.69 | 362.14 | 741.33 | 0.00 | 0.00 |
| November | 84.48 | 47.83 | 36.66 | 21.22 | 427.17 | 717.67 | 0.00 | 0.00 |
| December | 78.60 | 40.69 | 37.91 | 16.25 | 499.90 | 743.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.55 | 45.21 | 57.35 | 22.58 | 365.60 | 8746.17 | 0.00 | 0.00 |
| Minimum of Months | 78.60 | 19.82 | 36.66 | 5.92 | 242.38 | 671.67 | 0.00 | 0.00 |
| Maximum of Months | 128.95 | 71.54 | 72.72 | 44.70 | 499.90 | 744.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_LAUNDRYROOMFLR1_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.76 | 54.63 | 39.13 | 19.98 | 488.51 | 743.67 | 0.00 | 0.00 |
| February | 107.16 | 51.59 | 55.57 | 19.06 | 479.60 | 671.67 | 0.00 | 0.00 |
| March | 128.95 | 71.54 | 57.41 | 35.17 | 397.46 | 743.17 | 0.00 | 0.00 |
| April | 109.65 | 44.50 | 65.15 | 21.33 | 360.77 | 719.33 | 0.00 | 0.00 |
| May | 94.89 | 27.51 | 67.38 | 11.26 | 317.45 | 744.00 | 0.00 | 0.00 |
| June | 92.53 | 19.82 | 72.72 | 5.92 | 269.20 | 719.50 | 0.00 | 0.00 |
| July | 93.89 | 22.55 | 71.34 | 12.49 | 242.38 | 742.83 | 0.00 | 0.00 |
| August | 104.80 | 33.34 | 71.46 | 24.67 | 254.75 | 743.17 | 0.00 | 0.00 |
| September | 124.44 | 61.37 | 63.07 | 44.70 | 295.39 | 716.33 | 0.00 | 0.00 |
| October | 117.95 | 67.51 | 50.44 | 38.69 | 362.14 | 741.33 | 0.00 | 0.00 |
| November | 84.48 | 47.83 | 36.66 | 21.22 | 427.17 | 717.67 | 0.00 | 0.00 |
| December | 78.60 | 40.69 | 37.91 | 16.25 | 499.90 | 743.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.55 | 45.21 | 57.35 | 22.58 | 365.60 | 8746.17 | 0.00 | 0.00 |
| Minimum of Months | 78.60 | 19.82 | 36.66 | 5.92 | 242.38 | 671.67 | 0.00 | 0.00 |
| Maximum of Months | 128.95 | 71.54 | 72.72 | 44.70 | 499.90 | 744.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_LAUNDRYROOMFLR1_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.76 | 54.63 | 39.13 | 19.98 | 488.51 | 743.67 | 0.00 | 0.00 |
| February | 107.16 | 51.59 | 55.57 | 19.06 | 479.60 | 671.67 | 0.00 | 0.00 |
| March | 128.95 | 71.54 | 57.41 | 35.17 | 397.46 | 743.17 | 0.00 | 0.00 |
| April | 109.65 | 44.50 | 65.15 | 21.33 | 360.77 | 719.33 | 0.00 | 0.00 |
| May | 94.89 | 27.51 | 67.38 | 11.26 | 317.45 | 744.00 | 0.00 | 0.00 |
| June | 92.53 | 19.82 | 72.72 | 5.92 | 269.20 | 719.50 | 0.00 | 0.00 |
| July | 93.89 | 22.55 | 71.34 | 12.49 | 242.38 | 742.83 | 0.00 | 0.00 |
| August | 104.80 | 33.34 | 71.46 | 24.67 | 254.75 | 743.17 | 0.00 | 0.00 |
| September | 124.44 | 61.37 | 63.07 | 44.70 | 295.39 | 716.33 | 0.00 | 0.00 |
| October | 117.95 | 67.51 | 50.44 | 38.69 | 362.14 | 741.33 | 0.00 | 0.00 |
| November | 84.48 | 47.83 | 36.66 | 21.22 | 427.17 | 717.67 | 0.00 | 0.00 |
| December | 78.60 | 40.69 | 37.91 | 16.25 | 499.90 | 743.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.55 | 45.21 | 57.35 | 22.58 | 365.60 | 8746.17 | 0.00 | 0.00 |
| Minimum of Months | 78.60 | 19.82 | 36.66 | 5.92 | 242.38 | 671.67 | 0.00 | 0.00 |
| Maximum of Months | 128.95 | 71.54 | 72.72 | 44.70 | 499.90 | 744.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_EXERCISECENTERFLR1_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.76 | 54.63 | 39.13 | 61.65 | 187.95 | 0.00 | 0.00 | 0.00 |
| February | 107.16 | 51.59 | 55.57 | 65.69 | 183.44 | 0.00 | 0.00 | 0.00 |
| March | 128.95 | 71.54 | 57.41 | 108.81 | 131.55 | 0.00 | 0.00 | 0.00 |
| April | 109.65 | 44.50 | 65.15 | 98.69 | 102.68 | 0.00 | 0.00 | 0.00 |
| May | 94.89 | 27.51 | 67.38 | 96.06 | 67.47 | 0.00 | 0.00 | 0.00 |
| June | 92.53 | 19.82 | 72.72 | 109.98 | 41.36 | 0.00 | 0.00 | 0.00 |
| July | 93.89 | 22.55 | 71.34 | 129.24 | 26.95 | 0.00 | 0.00 | 0.00 |
| August | 104.80 | 33.34 | 71.46 | 140.08 | 36.32 | 0.00 | 0.00 | 0.00 |
| September | 124.44 | 61.37 | 63.07 | 149.07 | 60.82 | 0.00 | 0.00 | 0.00 |
| October | 117.95 | 67.51 | 50.44 | 114.61 | 98.70 | 0.00 | 0.00 | 0.00 |
| November | 84.48 | 47.83 | 36.66 | 68.65 | 131.08 | 0.00 | 0.00 | 0.00 |
| December | 78.60 | 40.69 | 37.91 | 47.41 | 186.09 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.55 | 45.21 | 57.35 | 99.36 | 104.11 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.60 | 19.82 | 36.66 | 47.41 | 26.95 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 128.95 | 71.54 | 72.72 | 149.07 | 187.95 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_FRONTOFFICEFLR1_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.76 | 54.63 | 39.13 | 63.31 | 181.29 | 0.00 | 0.00 | 0.00 |
| February | 107.16 | 51.59 | 55.57 | 68.30 | 176.44 | 0.00 | 0.00 | 0.00 |
| March | 128.95 | 71.54 | 57.41 | 111.00 | 128.35 | 0.00 | 0.00 | 0.00 |
| April | 109.65 | 44.50 | 65.15 | 100.71 | 101.04 | 0.00 | 0.00 | 0.00 |
| May | 94.89 | 27.51 | 67.38 | 97.95 | 67.58 | 0.00 | 0.00 | 0.00 |
| June | 92.53 | 19.82 | 72.72 | 111.45 | 41.12 | 0.00 | 0.00 | 0.00 |
| July | 93.89 | 22.55 | 71.34 | 130.16 | 26.41 | 0.00 | 0.00 | 0.00 |
| August | 104.80 | 33.34 | 71.46 | 141.10 | 36.05 | 0.00 | 0.00 | 0.00 |
| September | 124.44 | 61.37 | 63.07 | 150.29 | 61.28 | 0.00 | 0.00 | 0.00 |
| October | 117.95 | 67.51 | 50.44 | 115.96 | 99.39 | 0.00 | 0.00 | 0.00 |
| November | 84.48 | 47.83 | 36.66 | 69.63 | 130.35 | 0.00 | 0.00 | 0.00 |
| December | 78.60 | 40.69 | 37.91 | 48.93 | 179.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.55 | 45.21 | 57.35 | 100.92 | 102.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.60 | 19.82 | 36.66 | 48.93 | 26.41 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 128.95 | 71.54 | 72.72 | 150.29 | 181.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_FRONTOFFICEFLR1_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.76 | 54.63 | 39.13 | 63.31 | 181.29 | 0.00 | 0.00 | 0.00 |
| February | 107.16 | 51.59 | 55.57 | 68.30 | 176.44 | 0.00 | 0.00 | 0.00 |
| March | 128.95 | 71.54 | 57.41 | 111.00 | 128.35 | 0.00 | 0.00 | 0.00 |
| April | 109.65 | 44.50 | 65.15 | 100.71 | 101.04 | 0.00 | 0.00 | 0.00 |
| May | 94.89 | 27.51 | 67.38 | 97.95 | 67.58 | 0.00 | 0.00 | 0.00 |
| June | 92.53 | 19.82 | 72.72 | 111.45 | 41.12 | 0.00 | 0.00 | 0.00 |
| July | 93.89 | 22.55 | 71.34 | 130.16 | 26.41 | 0.00 | 0.00 | 0.00 |
| August | 104.80 | 33.34 | 71.46 | 141.10 | 36.05 | 0.00 | 0.00 | 0.00 |
| September | 124.44 | 61.37 | 63.07 | 150.29 | 61.28 | 0.00 | 0.00 | 0.00 |
| October | 117.95 | 67.51 | 50.44 | 115.96 | 99.39 | 0.00 | 0.00 | 0.00 |
| November | 84.48 | 47.83 | 36.66 | 69.63 | 130.35 | 0.00 | 0.00 | 0.00 |
| December | 78.60 | 40.69 | 37.91 | 48.93 | 179.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.55 | 45.21 | 57.35 | 100.92 | 102.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.60 | 19.82 | 36.66 | 48.93 | 26.41 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 128.95 | 71.54 | 72.72 | 150.29 | 181.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_FRONTOFFICEFLR1_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.76 | 54.63 | 39.13 | 63.31 | 181.29 | 0.00 | 0.00 | 0.00 |
| February | 107.16 | 51.59 | 55.57 | 68.30 | 176.44 | 0.00 | 0.00 | 0.00 |
| March | 128.95 | 71.54 | 57.41 | 111.00 | 128.35 | 0.00 | 0.00 | 0.00 |
| April | 109.65 | 44.50 | 65.15 | 100.71 | 101.04 | 0.00 | 0.00 | 0.00 |
| May | 94.89 | 27.51 | 67.38 | 97.95 | 67.58 | 0.00 | 0.00 | 0.00 |
| June | 92.53 | 19.82 | 72.72 | 111.45 | 41.12 | 0.00 | 0.00 | 0.00 |
| July | 93.89 | 22.55 | 71.34 | 130.16 | 26.41 | 0.00 | 0.00 | 0.00 |
| August | 104.80 | 33.34 | 71.46 | 141.10 | 36.05 | 0.00 | 0.00 | 0.00 |
| September | 124.44 | 61.37 | 63.07 | 150.29 | 61.28 | 0.00 | 0.00 | 0.00 |
| October | 117.95 | 67.51 | 50.44 | 115.96 | 99.39 | 0.00 | 0.00 | 0.00 |
| November | 84.48 | 47.83 | 36.66 | 69.63 | 130.35 | 0.00 | 0.00 | 0.00 |
| December | 78.60 | 40.69 | 37.91 | 48.93 | 179.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.55 | 45.21 | 57.35 | 100.92 | 102.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.60 | 19.82 | 36.66 | 48.93 | 26.41 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 128.95 | 71.54 | 72.72 | 150.29 | 181.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_FRONTOFFICEFLR1_3_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.76 | 54.63 | 39.13 | 63.31 | 181.29 | 0.00 | 0.00 | 0.00 |
| February | 107.16 | 51.59 | 55.57 | 68.30 | 176.44 | 0.00 | 0.00 | 0.00 |
| March | 128.95 | 71.54 | 57.41 | 111.00 | 128.35 | 0.00 | 0.00 | 0.00 |
| April | 109.65 | 44.50 | 65.15 | 100.71 | 101.04 | 0.00 | 0.00 | 0.00 |
| May | 94.89 | 27.51 | 67.38 | 97.95 | 67.58 | 0.00 | 0.00 | 0.00 |
| June | 92.53 | 19.82 | 72.72 | 111.45 | 41.12 | 0.00 | 0.00 | 0.00 |
| July | 93.89 | 22.55 | 71.34 | 130.16 | 26.41 | 0.00 | 0.00 | 0.00 |
| August | 104.80 | 33.34 | 71.46 | 141.10 | 36.05 | 0.00 | 0.00 | 0.00 |
| September | 124.44 | 61.37 | 63.07 | 150.29 | 61.28 | 0.00 | 0.00 | 0.00 |
| October | 117.95 | 67.51 | 50.44 | 115.96 | 99.39 | 0.00 | 0.00 | 0.00 |
| November | 84.48 | 47.83 | 36.66 | 69.63 | 130.35 | 0.00 | 0.00 | 0.00 |
| December | 78.60 | 40.69 | 37.91 | 48.93 | 179.56 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.55 | 45.21 | 57.35 | 100.92 | 102.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.60 | 19.82 | 36.66 | 48.93 | 26.41 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 128.95 | 71.54 | 72.72 | 150.29 | 181.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_CORRIDORFLR2_2_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 11.88 | 2.80 | 9.08 | 1.68 | 79.27 | 0.00 | 0.00 | 0.00 |
| February | 19.25 | 4.97 | 14.28 | 4.71 | 75.22 | 0.00 | 0.00 | 0.00 |
| March | 30.26 | 13.01 | 17.25 | 18.29 | 52.31 | 0.00 | 0.00 | 0.00 |
| April | 36.81 | 15.06 | 21.74 | 28.11 | 38.92 | 0.00 | 0.00 | 0.00 |
| May | 43.45 | 19.62 | 23.83 | 42.03 | 25.62 | 0.00 | 0.00 | 0.00 |
| June | 52.50 | 24.70 | 27.80 | 60.50 | 15.68 | 0.00 | 0.00 | 0.00 |
| July | 46.88 | 20.52 | 26.35 | 59.66 | 10.31 | 0.00 | 0.00 | 0.00 |
| August | 42.35 | 17.96 | 24.39 | 52.55 | 13.63 | 0.00 | 0.00 | 0.00 |
| September | 33.35 | 14.41 | 18.94 | 34.75 | 22.98 | 0.00 | 0.00 | 0.00 |
| October | 21.61 | 7.61 | 14.00 | 14.18 | 39.60 | 0.00 | 0.00 | 0.00 |
| November | 12.70 | 3.61 | 9.10 | 4.86 | 52.52 | 0.00 | 0.00 | 0.00 |
| December | 11.08 | 2.40 | 8.68 | 1.51 | 76.30 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 30.22 | 12.26 | 17.97 | 27.03 | 41.69 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11.08 | 2.40 | 8.68 | 1.51 | 10.31 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 52.50 | 24.70 | 27.80 | 60.50 | 79.27 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_CORRIDORFLR2_15_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.85 | 4.50 | 9.35 | 2.79 | 75.03 | 0.00 | 0.00 | 0.00 |
| February | 20.23 | 6.04 | 14.18 | 5.68 | 71.79 | 0.00 | 0.00 | 0.00 |
| March | 29.14 | 12.18 | 16.95 | 17.11 | 51.20 | 0.00 | 0.00 | 0.00 |
| April | 38.48 | 17.01 | 21.47 | 29.41 | 36.90 | 0.00 | 0.00 | 0.00 |
| May | 43.11 | 19.06 | 24.05 | 41.39 | 24.23 | 0.00 | 0.00 | 0.00 |
| June | 48.19 | 21.30 | 26.89 | 54.78 | 14.64 | 0.00 | 0.00 | 0.00 |
| July | 46.21 | 20.31 | 25.90 | 58.71 | 9.53 | 0.00 | 0.00 | 0.00 |
| August | 41.72 | 17.46 | 24.26 | 50.88 | 13.10 | 0.00 | 0.00 | 0.00 |
| September | 34.63 | 15.30 | 19.33 | 36.14 | 22.06 | 0.00 | 0.00 | 0.00 |
| October | 23.53 | 9.70 | 13.83 | 16.22 | 37.70 | 0.00 | 0.00 | 0.00 |
| November | 13.36 | 4.28 | 9.09 | 5.38 | 51.09 | 0.00 | 0.00 | 0.00 |
| December | 10.77 | 2.23 | 8.54 | 1.17 | 74.59 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 30.31 | 12.48 | 17.84 | 26.76 | 39.99 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 10.77 | 2.23 | 8.54 | 1.17 | 9.53 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 48.19 | 21.30 | 26.89 | 58.71 | 75.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM201_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.94 | 0.00 | 21.94 | 0.00 | 182.04 | 0.00 | 0.00 | 0.00 |
| February | 33.42 | 0.00 | 33.42 | 0.37 | 171.65 | 0.00 | 0.00 | 0.00 |
| March | 40.54 | 0.00 | 40.54 | 9.08 | 124.35 | 0.00 | 0.00 | 0.00 |
| April | 51.68 | 0.25 | 51.43 | 20.48 | 89.12 | 0.00 | 0.00 | 0.00 |
| May | 60.04 | 2.59 | 57.45 | 37.96 | 58.11 | 0.00 | 0.00 | 0.00 |
| June | 72.18 | 6.14 | 66.04 | 66.06 | 38.63 | 0.00 | 0.00 | 0.00 |
| July | 67.22 | 4.57 | 62.65 | 74.72 | 27.32 | 0.00 | 0.00 | 0.00 |
| August | 58.20 | 1.12 | 57.08 | 60.47 | 36.91 | 0.00 | 0.00 | 0.00 |
| September | 44.11 | 0.02 | 44.09 | 32.99 | 58.86 | 0.00 | 0.00 | 0.00 |
| October | 32.96 | 0.00 | 32.96 | 10.76 | 91.23 | 0.00 | 0.00 | 0.00 |
| November | 22.15 | 0.00 | 22.15 | 2.79 | 116.01 | 0.00 | 0.00 | 0.00 |
| December | 20.53 | 0.00 | 20.53 | 0.09 | 172.41 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.79 | 1.23 | 42.56 | 26.48 | 96.84 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.53 | 0.00 | 20.53 | 0.00 | 27.32 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.18 | 6.14 | 66.04 | 74.72 | 182.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM202_205_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.94 | 0.00 | 21.94 | 0.00 | 206.82 | 6.17 | 0.00 | 0.00 |
| February | 33.42 | 0.00 | 33.42 | 0.17 | 196.43 | 11.50 | 0.00 | 0.00 |
| March | 40.54 | 0.00 | 40.54 | 8.22 | 138.07 | 0.67 | 0.00 | 0.00 |
| April | 51.68 | 0.25 | 51.43 | 19.28 | 93.73 | 0.00 | 0.00 | 0.00 |
| May | 60.04 | 2.59 | 57.45 | 39.32 | 55.82 | 0.00 | 0.00 | 0.00 |
| June | 72.18 | 6.14 | 66.04 | 72.48 | 33.61 | 0.00 | 0.00 | 0.00 |
| July | 67.22 | 4.57 | 62.65 | 84.30 | 21.14 | 0.00 | 0.00 | 0.00 |
| August | 58.20 | 1.12 | 57.08 | 67.25 | 30.05 | 0.00 | 0.00 | 0.00 |
| September | 44.11 | 0.02 | 44.09 | 35.40 | 54.48 | 0.00 | 0.00 | 0.00 |
| October | 32.96 | 0.00 | 32.96 | 10.14 | 93.73 | 0.00 | 0.00 | 0.00 |
| November | 22.15 | 0.00 | 22.15 | 2.33 | 126.50 | 2.83 | 0.00 | 0.00 |
| December | 20.53 | 0.00 | 20.53 | 0.05 | 195.80 | 12.83 | 0.00 | 0.00 |
| Annual Sum or Average | 43.79 | 1.23 | 42.56 | 28.43 | 103.38 | 34.00 | 0.00 | 0.00 |
| Minimum of Months | 20.53 | 0.00 | 20.53 | 0.00 | 21.14 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.18 | 6.14 | 66.04 | 84.30 | 206.82 | 12.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM202_205_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.94 | 0.00 | 21.94 | 0.00 | 206.82 | 6.17 | 0.00 | 0.00 |
| February | 33.42 | 0.00 | 33.42 | 0.17 | 196.43 | 11.50 | 0.00 | 0.00 |
| March | 40.54 | 0.00 | 40.54 | 8.22 | 138.07 | 0.67 | 0.00 | 0.00 |
| April | 51.68 | 0.25 | 51.43 | 19.28 | 93.73 | 0.00 | 0.00 | 0.00 |
| May | 60.04 | 2.59 | 57.45 | 39.32 | 55.82 | 0.00 | 0.00 | 0.00 |
| June | 72.18 | 6.14 | 66.04 | 72.48 | 33.61 | 0.00 | 0.00 | 0.00 |
| July | 67.22 | 4.57 | 62.65 | 84.30 | 21.14 | 0.00 | 0.00 | 0.00 |
| August | 58.20 | 1.12 | 57.08 | 67.25 | 30.05 | 0.00 | 0.00 | 0.00 |
| September | 44.11 | 0.02 | 44.09 | 35.40 | 54.48 | 0.00 | 0.00 | 0.00 |
| October | 32.96 | 0.00 | 32.96 | 10.14 | 93.73 | 0.00 | 0.00 | 0.00 |
| November | 22.15 | 0.00 | 22.15 | 2.33 | 126.50 | 2.83 | 0.00 | 0.00 |
| December | 20.53 | 0.00 | 20.53 | 0.05 | 195.80 | 12.83 | 0.00 | 0.00 |
| Annual Sum or Average | 43.79 | 1.23 | 42.56 | 28.43 | 103.38 | 34.00 | 0.00 | 0.00 |
| Minimum of Months | 20.53 | 0.00 | 20.53 | 0.00 | 21.14 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.18 | 6.14 | 66.04 | 84.30 | 206.82 | 12.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM202_205_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.94 | 0.00 | 21.94 | 0.00 | 206.82 | 6.17 | 0.00 | 0.00 |
| February | 33.42 | 0.00 | 33.42 | 0.17 | 196.43 | 11.50 | 0.00 | 0.00 |
| March | 40.54 | 0.00 | 40.54 | 8.22 | 138.07 | 0.67 | 0.00 | 0.00 |
| April | 51.68 | 0.25 | 51.43 | 19.28 | 93.73 | 0.00 | 0.00 | 0.00 |
| May | 60.04 | 2.59 | 57.45 | 39.32 | 55.82 | 0.00 | 0.00 | 0.00 |
| June | 72.18 | 6.14 | 66.04 | 72.48 | 33.61 | 0.00 | 0.00 | 0.00 |
| July | 67.22 | 4.57 | 62.65 | 84.30 | 21.14 | 0.00 | 0.00 | 0.00 |
| August | 58.20 | 1.12 | 57.08 | 67.25 | 30.05 | 0.00 | 0.00 | 0.00 |
| September | 44.11 | 0.02 | 44.09 | 35.40 | 54.48 | 0.00 | 0.00 | 0.00 |
| October | 32.96 | 0.00 | 32.96 | 10.14 | 93.73 | 0.00 | 0.00 | 0.00 |
| November | 22.15 | 0.00 | 22.15 | 2.33 | 126.50 | 2.83 | 0.00 | 0.00 |
| December | 20.53 | 0.00 | 20.53 | 0.05 | 195.80 | 12.83 | 0.00 | 0.00 |
| Annual Sum or Average | 43.79 | 1.23 | 42.56 | 28.43 | 103.38 | 34.00 | 0.00 | 0.00 |
| Minimum of Months | 20.53 | 0.00 | 20.53 | 0.00 | 21.14 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.18 | 6.14 | 66.04 | 84.30 | 206.82 | 12.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM202_205_5_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.94 | 0.00 | 21.94 | 0.00 | 206.82 | 6.17 | 0.00 | 0.00 |
| February | 33.42 | 0.00 | 33.42 | 0.17 | 196.43 | 11.50 | 0.00 | 0.00 |
| March | 40.54 | 0.00 | 40.54 | 8.22 | 138.07 | 0.67 | 0.00 | 0.00 |
| April | 51.68 | 0.25 | 51.43 | 19.28 | 93.73 | 0.00 | 0.00 | 0.00 |
| May | 60.04 | 2.59 | 57.45 | 39.32 | 55.82 | 0.00 | 0.00 | 0.00 |
| June | 72.18 | 6.14 | 66.04 | 72.48 | 33.61 | 0.00 | 0.00 | 0.00 |
| July | 67.22 | 4.57 | 62.65 | 84.30 | 21.14 | 0.00 | 0.00 | 0.00 |
| August | 58.20 | 1.12 | 57.08 | 67.25 | 30.05 | 0.00 | 0.00 | 0.00 |
| September | 44.11 | 0.02 | 44.09 | 35.40 | 54.48 | 0.00 | 0.00 | 0.00 |
| October | 32.96 | 0.00 | 32.96 | 10.14 | 93.73 | 0.00 | 0.00 | 0.00 |
| November | 22.15 | 0.00 | 22.15 | 2.33 | 126.50 | 2.83 | 0.00 | 0.00 |
| December | 20.53 | 0.00 | 20.53 | 0.05 | 195.80 | 12.83 | 0.00 | 0.00 |
| Annual Sum or Average | 43.79 | 1.23 | 42.56 | 28.43 | 103.38 | 34.00 | 0.00 | 0.00 |
| Minimum of Months | 20.53 | 0.00 | 20.53 | 0.00 | 21.14 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.18 | 6.14 | 66.04 | 84.30 | 206.82 | 12.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM206_208_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.94 | 0.00 | 21.94 | 0.00 | 211.76 | 0.83 | 0.00 | 0.00 |
| February | 33.42 | 0.00 | 33.42 | 0.13 | 201.11 | 3.67 | 0.00 | 0.00 |
| March | 40.54 | 0.00 | 40.54 | 7.78 | 141.95 | 0.00 | 0.00 | 0.00 |
| April | 51.68 | 0.25 | 51.43 | 18.36 | 96.23 | 0.00 | 0.00 | 0.00 |
| May | 60.04 | 2.59 | 57.45 | 38.74 | 56.75 | 0.00 | 0.00 | 0.00 |
| June | 72.18 | 6.14 | 66.04 | 72.65 | 33.63 | 0.00 | 0.00 | 0.00 |
| July | 67.22 | 4.57 | 62.65 | 84.89 | 20.91 | 0.00 | 0.00 | 0.00 |
| August | 58.20 | 1.12 | 57.08 | 67.68 | 29.85 | 0.00 | 0.00 | 0.00 |
| September | 44.11 | 0.02 | 44.09 | 35.36 | 54.87 | 0.00 | 0.00 | 0.00 |
| October | 32.96 | 0.00 | 32.96 | 9.66 | 95.96 | 0.00 | 0.00 | 0.00 |
| November | 22.15 | 0.00 | 22.15 | 2.13 | 130.37 | 0.00 | 0.00 | 0.00 |
| December | 20.53 | 0.00 | 20.53 | 0.04 | 200.50 | 3.50 | 0.00 | 0.00 |
| Annual Sum or Average | 43.79 | 1.23 | 42.56 | 28.31 | 105.68 | 8.00 | 0.00 | 0.00 |
| Minimum of Months | 20.53 | 0.00 | 20.53 | 0.00 | 20.91 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.18 | 6.14 | 66.04 | 84.89 | 211.76 | 3.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM206_208_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 19.61 | 0.00 | 19.61 | 0.00 | 191.74 | 0.33 | 0.00 | 0.00 |
| February | 29.88 | 0.00 | 29.88 | 0.12 | 182.22 | 3.00 | 0.00 | 0.00 |
| March | 36.24 | 0.00 | 36.24 | 6.92 | 128.50 | 0.00 | 0.00 | 0.00 |
| April | 46.20 | 0.22 | 45.98 | 16.31 | 86.92 | 0.00 | 0.00 | 0.00 |
| May | 53.67 | 2.31 | 51.36 | 34.61 | 51.10 | 0.00 | 0.00 | 0.00 |
| June | 64.53 | 5.49 | 59.04 | 65.11 | 30.17 | 0.00 | 0.00 | 0.00 |
| July | 60.10 | 4.09 | 56.01 | 76.23 | 18.69 | 0.00 | 0.00 | 0.00 |
| August | 52.03 | 1.00 | 51.03 | 60.74 | 26.74 | 0.00 | 0.00 | 0.00 |
| September | 39.44 | 0.02 | 39.42 | 31.65 | 49.35 | 0.00 | 0.00 | 0.00 |
| October | 29.47 | 0.00 | 29.47 | 8.58 | 86.58 | 0.00 | 0.00 | 0.00 |
| November | 19.80 | 0.00 | 19.80 | 1.89 | 117.80 | 0.00 | 0.00 | 0.00 |
| December | 18.36 | 0.00 | 18.36 | 0.04 | 181.49 | 2.67 | 0.00 | 0.00 |
| Annual Sum or Average | 39.15 | 1.10 | 38.05 | 25.35 | 95.51 | 6.00 | 0.00 | 0.00 |
| Minimum of Months | 18.36 | 0.00 | 18.36 | 0.00 | 18.69 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 64.53 | 5.49 | 59.04 | 76.23 | 191.74 | 3.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM206_208_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.94 | 0.00 | 21.94 | 0.00 | 211.76 | 0.83 | 0.00 | 0.00 |
| February | 33.42 | 0.00 | 33.42 | 0.13 | 201.11 | 3.67 | 0.00 | 0.00 |
| March | 40.54 | 0.00 | 40.54 | 7.78 | 141.95 | 0.00 | 0.00 | 0.00 |
| April | 51.68 | 0.25 | 51.43 | 18.36 | 96.23 | 0.00 | 0.00 | 0.00 |
| May | 60.04 | 2.59 | 57.45 | 38.74 | 56.75 | 0.00 | 0.00 | 0.00 |
| June | 72.18 | 6.14 | 66.04 | 72.65 | 33.63 | 0.00 | 0.00 | 0.00 |
| July | 67.22 | 4.57 | 62.65 | 84.89 | 20.91 | 0.00 | 0.00 | 0.00 |
| August | 58.20 | 1.12 | 57.08 | 67.68 | 29.85 | 0.00 | 0.00 | 0.00 |
| September | 44.11 | 0.02 | 44.09 | 35.36 | 54.87 | 0.00 | 0.00 | 0.00 |
| October | 32.96 | 0.00 | 32.96 | 9.66 | 95.96 | 0.00 | 0.00 | 0.00 |
| November | 22.15 | 0.00 | 22.15 | 2.13 | 130.37 | 0.00 | 0.00 | 0.00 |
| December | 20.53 | 0.00 | 20.53 | 0.04 | 200.50 | 3.50 | 0.00 | 0.00 |
| Annual Sum or Average | 43.79 | 1.23 | 42.56 | 28.31 | 105.68 | 8.00 | 0.00 | 0.00 |
| Minimum of Months | 20.53 | 0.00 | 20.53 | 0.00 | 20.91 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.18 | 6.14 | 66.04 | 84.89 | 211.76 | 3.67 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM209_212_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.94 | 0.00 | 21.94 | 0.00 | 212.83 | 2.50 | 0.00 | 0.00 |
| February | 33.42 | 0.00 | 33.42 | 0.12 | 201.97 | 5.67 | 0.00 | 0.00 |
| March | 40.54 | 0.00 | 40.54 | 7.74 | 142.40 | 0.00 | 0.00 | 0.00 |
| April | 51.68 | 0.25 | 51.43 | 18.33 | 96.24 | 0.00 | 0.00 | 0.00 |
| May | 60.04 | 2.59 | 57.45 | 39.22 | 56.15 | 0.00 | 0.00 | 0.00 |
| June | 72.18 | 6.14 | 66.04 | 73.60 | 33.01 | 0.00 | 0.00 | 0.00 |
| July | 67.22 | 4.57 | 62.65 | 86.01 | 20.28 | 0.00 | 0.00 | 0.00 |
| August | 58.20 | 1.12 | 57.08 | 68.43 | 29.21 | 0.00 | 0.00 | 0.00 |
| September | 44.11 | 0.02 | 44.09 | 35.54 | 54.65 | 0.00 | 0.00 | 0.00 |
| October | 32.96 | 0.00 | 32.96 | 9.47 | 96.65 | 0.00 | 0.00 | 0.00 |
| November | 22.15 | 0.00 | 22.15 | 2.02 | 131.88 | 0.00 | 0.00 | 0.00 |
| December | 20.53 | 0.00 | 20.53 | 0.04 | 201.91 | 6.33 | 0.00 | 0.00 |
| Annual Sum or Average | 43.79 | 1.23 | 42.56 | 28.57 | 105.95 | 14.50 | 0.00 | 0.00 |
| Minimum of Months | 20.53 | 0.00 | 20.53 | 0.00 | 20.28 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.18 | 6.14 | 66.04 | 86.01 | 212.83 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM209_212_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.94 | 0.00 | 21.94 | 0.00 | 212.83 | 2.50 | 0.00 | 0.00 |
| February | 33.42 | 0.00 | 33.42 | 0.12 | 201.97 | 5.67 | 0.00 | 0.00 |
| March | 40.54 | 0.00 | 40.54 | 7.74 | 142.40 | 0.00 | 0.00 | 0.00 |
| April | 51.68 | 0.25 | 51.43 | 18.33 | 96.24 | 0.00 | 0.00 | 0.00 |
| May | 60.04 | 2.59 | 57.45 | 39.22 | 56.15 | 0.00 | 0.00 | 0.00 |
| June | 72.18 | 6.14 | 66.04 | 73.60 | 33.01 | 0.00 | 0.00 | 0.00 |
| July | 67.22 | 4.57 | 62.65 | 86.01 | 20.28 | 0.00 | 0.00 | 0.00 |
| August | 58.20 | 1.12 | 57.08 | 68.43 | 29.21 | 0.00 | 0.00 | 0.00 |
| September | 44.11 | 0.02 | 44.09 | 35.54 | 54.65 | 0.00 | 0.00 | 0.00 |
| October | 32.96 | 0.00 | 32.96 | 9.47 | 96.65 | 0.00 | 0.00 | 0.00 |
| November | 22.15 | 0.00 | 22.15 | 2.02 | 131.88 | 0.00 | 0.00 | 0.00 |
| December | 20.53 | 0.00 | 20.53 | 0.04 | 201.91 | 6.33 | 0.00 | 0.00 |
| Annual Sum or Average | 43.79 | 1.23 | 42.56 | 28.57 | 105.95 | 14.50 | 0.00 | 0.00 |
| Minimum of Months | 20.53 | 0.00 | 20.53 | 0.00 | 20.28 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.18 | 6.14 | 66.04 | 86.01 | 212.83 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM209_212_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.94 | 0.00 | 21.94 | 0.00 | 212.83 | 2.50 | 0.00 | 0.00 |
| February | 33.42 | 0.00 | 33.42 | 0.12 | 201.97 | 5.67 | 0.00 | 0.00 |
| March | 40.54 | 0.00 | 40.54 | 7.74 | 142.40 | 0.00 | 0.00 | 0.00 |
| April | 51.68 | 0.25 | 51.43 | 18.33 | 96.24 | 0.00 | 0.00 | 0.00 |
| May | 60.04 | 2.59 | 57.45 | 39.22 | 56.15 | 0.00 | 0.00 | 0.00 |
| June | 72.18 | 6.14 | 66.04 | 73.60 | 33.01 | 0.00 | 0.00 | 0.00 |
| July | 67.22 | 4.57 | 62.65 | 86.01 | 20.28 | 0.00 | 0.00 | 0.00 |
| August | 58.20 | 1.12 | 57.08 | 68.43 | 29.21 | 0.00 | 0.00 | 0.00 |
| September | 44.11 | 0.02 | 44.09 | 35.54 | 54.65 | 0.00 | 0.00 | 0.00 |
| October | 32.96 | 0.00 | 32.96 | 9.47 | 96.65 | 0.00 | 0.00 | 0.00 |
| November | 22.15 | 0.00 | 22.15 | 2.02 | 131.88 | 0.00 | 0.00 | 0.00 |
| December | 20.53 | 0.00 | 20.53 | 0.04 | 201.91 | 6.33 | 0.00 | 0.00 |
| Annual Sum or Average | 43.79 | 1.23 | 42.56 | 28.57 | 105.95 | 14.50 | 0.00 | 0.00 |
| Minimum of Months | 20.53 | 0.00 | 20.53 | 0.00 | 20.28 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.18 | 6.14 | 66.04 | 86.01 | 212.83 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM209_212_5_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.94 | 0.00 | 21.94 | 0.00 | 212.83 | 2.50 | 0.00 | 0.00 |
| February | 33.42 | 0.00 | 33.42 | 0.12 | 201.97 | 5.67 | 0.00 | 0.00 |
| March | 40.54 | 0.00 | 40.54 | 7.74 | 142.40 | 0.00 | 0.00 | 0.00 |
| April | 51.68 | 0.25 | 51.43 | 18.33 | 96.24 | 0.00 | 0.00 | 0.00 |
| May | 60.04 | 2.59 | 57.45 | 39.22 | 56.15 | 0.00 | 0.00 | 0.00 |
| June | 72.18 | 6.14 | 66.04 | 73.60 | 33.01 | 0.00 | 0.00 | 0.00 |
| July | 67.22 | 4.57 | 62.65 | 86.01 | 20.28 | 0.00 | 0.00 | 0.00 |
| August | 58.20 | 1.12 | 57.08 | 68.43 | 29.21 | 0.00 | 0.00 | 0.00 |
| September | 44.11 | 0.02 | 44.09 | 35.54 | 54.65 | 0.00 | 0.00 | 0.00 |
| October | 32.96 | 0.00 | 32.96 | 9.47 | 96.65 | 0.00 | 0.00 | 0.00 |
| November | 22.15 | 0.00 | 22.15 | 2.02 | 131.88 | 0.00 | 0.00 | 0.00 |
| December | 20.53 | 0.00 | 20.53 | 0.04 | 201.91 | 6.33 | 0.00 | 0.00 |
| Annual Sum or Average | 43.79 | 1.23 | 42.56 | 28.57 | 105.95 | 14.50 | 0.00 | 0.00 |
| Minimum of Months | 20.53 | 0.00 | 20.53 | 0.00 | 20.28 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.18 | 6.14 | 66.04 | 86.01 | 212.83 | 6.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM213_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.94 | 0.00 | 21.94 | 0.00 | 203.26 | 13.00 | 0.00 | 0.00 |
| February | 33.42 | 0.00 | 33.42 | 0.26 | 192.13 | 13.17 | 0.00 | 0.00 |
| March | 40.54 | 0.00 | 40.54 | 9.04 | 134.66 | 7.67 | 0.00 | 0.00 |
| April | 51.68 | 0.25 | 51.43 | 21.16 | 90.96 | 0.83 | 0.00 | 0.00 |
| May | 60.04 | 2.59 | 57.45 | 41.53 | 53.54 | 0.00 | 0.00 | 0.00 |
| June | 72.18 | 6.14 | 66.04 | 75.04 | 31.76 | 0.00 | 0.00 | 0.00 |
| July | 67.22 | 4.57 | 62.65 | 86.70 | 19.60 | 0.00 | 0.00 | 0.00 |
| August | 58.20 | 1.12 | 57.08 | 69.20 | 28.32 | 0.00 | 0.00 | 0.00 |
| September | 44.11 | 0.02 | 44.09 | 36.81 | 52.38 | 0.00 | 0.00 | 0.00 |
| October | 32.96 | 0.00 | 32.96 | 11.08 | 91.61 | 0.83 | 0.00 | 0.00 |
| November | 22.15 | 0.00 | 22.15 | 2.63 | 123.43 | 11.00 | 0.00 | 0.00 |
| December | 20.53 | 0.00 | 20.53 | 0.07 | 191.86 | 26.33 | 0.00 | 0.00 |
| Annual Sum or Average | 43.79 | 1.23 | 42.56 | 29.65 | 100.67 | 72.83 | 0.00 | 0.00 |
| Minimum of Months | 20.53 | 0.00 | 20.53 | 0.00 | 19.60 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.18 | 6.14 | 66.04 | 86.70 | 203.26 | 26.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM214_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 94.07 | 54.80 | 39.26 | 61.68 | 183.87 | 1.67 | 0.00 | 0.00 |
| February | 107.50 | 51.76 | 55.75 | 66.01 | 179.46 | 5.83 | 0.00 | 0.00 |
| March | 129.36 | 71.77 | 57.59 | 108.37 | 128.61 | 0.00 | 0.00 | 0.00 |
| April | 110.00 | 44.64 | 65.37 | 99.06 | 99.06 | 0.00 | 0.00 | 0.00 |
| May | 95.20 | 27.60 | 67.60 | 96.64 | 63.74 | 0.00 | 0.00 | 0.00 |
| June | 92.83 | 19.88 | 72.95 | 110.43 | 38.46 | 0.00 | 0.00 | 0.00 |
| July | 94.19 | 22.63 | 71.57 | 129.98 | 23.65 | 0.00 | 0.00 | 0.00 |
| August | 105.14 | 33.45 | 71.69 | 140.65 | 32.49 | 0.00 | 0.00 | 0.00 |
| September | 124.84 | 61.57 | 63.27 | 149.69 | 56.36 | 0.00 | 0.00 | 0.00 |
| October | 118.33 | 67.73 | 50.60 | 115.77 | 92.10 | 0.00 | 0.00 | 0.00 |
| November | 84.76 | 47.98 | 36.78 | 69.27 | 124.47 | 0.00 | 0.00 | 0.00 |
| December | 78.86 | 40.82 | 38.04 | 47.60 | 180.98 | 5.67 | 0.00 | 0.00 |
| Annual Sum or Average | 102.88 | 45.35 | 57.53 | 99.79 | 99.85 | 13.17 | 0.00 | 0.00 |
| Minimum of Months | 78.86 | 19.88 | 36.78 | 47.60 | 23.65 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.36 | 71.77 | 72.95 | 149.69 | 183.87 | 5.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM215_218_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 94.07 | 54.80 | 39.26 | 53.31 | 240.05 | 0.00 | 0.00 | 0.00 |
| February | 107.50 | 51.76 | 55.75 | 54.93 | 233.75 | 0.00 | 0.00 | 0.00 |
| March | 129.36 | 71.77 | 57.59 | 93.16 | 173.48 | 0.00 | 0.00 | 0.00 |
| April | 110.00 | 44.64 | 65.37 | 83.68 | 141.22 | 0.00 | 0.00 | 0.00 |
| May | 95.20 | 27.60 | 67.60 | 80.09 | 100.21 | 0.00 | 0.00 | 0.00 |
| June | 92.83 | 19.88 | 72.95 | 88.94 | 65.73 | 0.00 | 0.00 | 0.00 |
| July | 94.19 | 22.63 | 71.57 | 106.29 | 47.85 | 0.00 | 0.00 | 0.00 |
| August | 105.14 | 33.45 | 71.69 | 119.95 | 59.69 | 0.00 | 0.00 | 0.00 |
| September | 124.84 | 61.57 | 63.27 | 132.56 | 88.93 | 0.00 | 0.00 | 0.00 |
| October | 118.33 | 67.73 | 50.60 | 101.56 | 133.01 | 0.00 | 0.00 | 0.00 |
| November | 84.76 | 47.98 | 36.78 | 60.12 | 174.25 | 0.00 | 0.00 | 0.00 |
| December | 78.86 | 40.82 | 38.04 | 40.75 | 238.91 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.88 | 45.35 | 57.53 | 84.78 | 140.93 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.86 | 19.88 | 36.78 | 40.75 | 47.85 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.36 | 71.77 | 72.95 | 132.56 | 240.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM215_218_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 94.07 | 54.80 | 39.26 | 53.31 | 240.05 | 0.00 | 0.00 | 0.00 |
| February | 107.50 | 51.76 | 55.75 | 54.93 | 233.75 | 0.00 | 0.00 | 0.00 |
| March | 129.36 | 71.77 | 57.59 | 93.16 | 173.48 | 0.00 | 0.00 | 0.00 |
| April | 110.00 | 44.64 | 65.37 | 83.68 | 141.22 | 0.00 | 0.00 | 0.00 |
| May | 95.20 | 27.60 | 67.60 | 80.09 | 100.21 | 0.00 | 0.00 | 0.00 |
| June | 92.83 | 19.88 | 72.95 | 88.94 | 65.73 | 0.00 | 0.00 | 0.00 |
| July | 94.19 | 22.63 | 71.57 | 106.29 | 47.85 | 0.00 | 0.00 | 0.00 |
| August | 105.14 | 33.45 | 71.69 | 119.95 | 59.69 | 0.00 | 0.00 | 0.00 |
| September | 124.84 | 61.57 | 63.27 | 132.56 | 88.93 | 0.00 | 0.00 | 0.00 |
| October | 118.33 | 67.73 | 50.60 | 101.56 | 133.01 | 0.00 | 0.00 | 0.00 |
| November | 84.76 | 47.98 | 36.78 | 60.12 | 174.25 | 0.00 | 0.00 | 0.00 |
| December | 78.86 | 40.82 | 38.04 | 40.75 | 238.91 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.88 | 45.35 | 57.53 | 84.78 | 140.93 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.86 | 19.88 | 36.78 | 40.75 | 47.85 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.36 | 71.77 | 72.95 | 132.56 | 240.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM215_218_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 94.07 | 54.80 | 39.26 | 53.31 | 240.05 | 0.00 | 0.00 | 0.00 |
| February | 107.50 | 51.76 | 55.75 | 54.93 | 233.75 | 0.00 | 0.00 | 0.00 |
| March | 129.36 | 71.77 | 57.59 | 93.16 | 173.48 | 0.00 | 0.00 | 0.00 |
| April | 110.00 | 44.64 | 65.37 | 83.68 | 141.22 | 0.00 | 0.00 | 0.00 |
| May | 95.20 | 27.60 | 67.60 | 80.09 | 100.21 | 0.00 | 0.00 | 0.00 |
| June | 92.83 | 19.88 | 72.95 | 88.94 | 65.73 | 0.00 | 0.00 | 0.00 |
| July | 94.19 | 22.63 | 71.57 | 106.29 | 47.85 | 0.00 | 0.00 | 0.00 |
| August | 105.14 | 33.45 | 71.69 | 119.95 | 59.69 | 0.00 | 0.00 | 0.00 |
| September | 124.84 | 61.57 | 63.27 | 132.56 | 88.93 | 0.00 | 0.00 | 0.00 |
| October | 118.33 | 67.73 | 50.60 | 101.56 | 133.01 | 0.00 | 0.00 | 0.00 |
| November | 84.76 | 47.98 | 36.78 | 60.12 | 174.25 | 0.00 | 0.00 | 0.00 |
| December | 78.86 | 40.82 | 38.04 | 40.75 | 238.91 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.88 | 45.35 | 57.53 | 84.78 | 140.93 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.86 | 19.88 | 36.78 | 40.75 | 47.85 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.36 | 71.77 | 72.95 | 132.56 | 240.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM215_218_3_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 94.07 | 54.80 | 39.26 | 53.31 | 240.05 | 0.00 | 0.00 | 0.00 |
| February | 107.50 | 51.76 | 55.75 | 54.93 | 233.75 | 0.00 | 0.00 | 0.00 |
| March | 129.36 | 71.77 | 57.59 | 93.16 | 173.48 | 0.00 | 0.00 | 0.00 |
| April | 110.00 | 44.64 | 65.37 | 83.68 | 141.22 | 0.00 | 0.00 | 0.00 |
| May | 95.20 | 27.60 | 67.60 | 80.09 | 100.21 | 0.00 | 0.00 | 0.00 |
| June | 92.83 | 19.88 | 72.95 | 88.94 | 65.73 | 0.00 | 0.00 | 0.00 |
| July | 94.19 | 22.63 | 71.57 | 106.29 | 47.85 | 0.00 | 0.00 | 0.00 |
| August | 105.14 | 33.45 | 71.69 | 119.95 | 59.69 | 0.00 | 0.00 | 0.00 |
| September | 124.84 | 61.57 | 63.27 | 132.56 | 88.93 | 0.00 | 0.00 | 0.00 |
| October | 118.33 | 67.73 | 50.60 | 101.56 | 133.01 | 0.00 | 0.00 | 0.00 |
| November | 84.76 | 47.98 | 36.78 | 60.12 | 174.25 | 0.00 | 0.00 | 0.00 |
| December | 78.86 | 40.82 | 38.04 | 40.75 | 238.91 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.88 | 45.35 | 57.53 | 84.78 | 140.93 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.86 | 19.88 | 36.78 | 40.75 | 47.85 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.36 | 71.77 | 72.95 | 132.56 | 240.05 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM219_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 94.07 | 54.80 | 39.26 | 53.85 | 228.13 | 0.00 | 0.00 | 0.00 |
| February | 107.50 | 51.76 | 55.75 | 55.34 | 222.55 | 0.00 | 0.00 | 0.00 |
| March | 129.36 | 71.77 | 57.59 | 94.05 | 162.29 | 0.00 | 0.00 | 0.00 |
| April | 110.00 | 44.64 | 65.37 | 84.78 | 131.00 | 0.00 | 0.00 | 0.00 |
| May | 95.20 | 27.60 | 67.60 | 80.93 | 95.10 | 0.00 | 0.00 | 0.00 |
| June | 92.83 | 19.88 | 72.95 | 89.96 | 63.92 | 0.00 | 0.00 | 0.00 |
| July | 94.19 | 22.63 | 71.57 | 107.92 | 45.17 | 0.00 | 0.00 | 0.00 |
| August | 105.14 | 33.45 | 71.69 | 121.27 | 57.20 | 0.00 | 0.00 | 0.00 |
| September | 124.84 | 61.57 | 63.27 | 133.57 | 86.17 | 0.00 | 0.00 | 0.00 |
| October | 118.33 | 67.73 | 50.60 | 102.50 | 124.51 | 0.00 | 0.00 | 0.00 |
| November | 84.76 | 47.98 | 36.78 | 60.85 | 163.43 | 0.00 | 0.00 | 0.00 |
| December | 78.86 | 40.82 | 38.04 | 41.06 | 226.93 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.88 | 45.35 | 57.53 | 85.68 | 133.39 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.86 | 19.88 | 36.78 | 41.06 | 45.17 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.36 | 71.77 | 72.95 | 133.57 | 228.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM220_223_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 94.07 | 54.80 | 39.26 | 61.32 | 184.98 | 0.33 | 0.00 | 0.00 |
| February | 107.50 | 51.76 | 55.75 | 65.47 | 180.98 | 1.00 | 0.00 | 0.00 |
| March | 129.36 | 71.77 | 57.59 | 108.35 | 128.92 | 0.00 | 0.00 | 0.00 |
| April | 110.00 | 44.64 | 65.37 | 99.36 | 98.86 | 0.00 | 0.00 | 0.00 |
| May | 95.20 | 27.60 | 67.60 | 97.33 | 63.15 | 0.00 | 0.00 | 0.00 |
| June | 92.83 | 19.88 | 72.95 | 111.76 | 37.52 | 0.00 | 0.00 | 0.00 |
| July | 94.19 | 22.63 | 71.57 | 131.80 | 22.62 | 0.00 | 0.00 | 0.00 |
| August | 105.14 | 33.45 | 71.69 | 142.24 | 31.23 | 0.00 | 0.00 | 0.00 |
| September | 124.84 | 61.57 | 63.27 | 150.78 | 55.27 | 0.00 | 0.00 | 0.00 |
| October | 118.33 | 67.73 | 50.60 | 116.32 | 91.62 | 0.00 | 0.00 | 0.00 |
| November | 84.76 | 47.98 | 36.78 | 69.49 | 124.41 | 0.00 | 0.00 | 0.00 |
| December | 78.86 | 40.82 | 38.04 | 47.40 | 181.96 | 0.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.88 | 45.35 | 57.53 | 100.34 | 99.69 | 1.83 | 0.00 | 0.00 |
| Minimum of Months | 78.86 | 19.88 | 36.78 | 47.40 | 22.62 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.36 | 71.77 | 72.95 | 150.78 | 184.98 | 1.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM220_223_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 94.07 | 54.80 | 39.26 | 61.32 | 184.98 | 0.33 | 0.00 | 0.00 |
| February | 107.50 | 51.76 | 55.75 | 65.47 | 180.98 | 1.00 | 0.00 | 0.00 |
| March | 129.36 | 71.77 | 57.59 | 108.35 | 128.92 | 0.00 | 0.00 | 0.00 |
| April | 110.00 | 44.64 | 65.37 | 99.36 | 98.86 | 0.00 | 0.00 | 0.00 |
| May | 95.20 | 27.60 | 67.60 | 97.33 | 63.15 | 0.00 | 0.00 | 0.00 |
| June | 92.83 | 19.88 | 72.95 | 111.76 | 37.52 | 0.00 | 0.00 | 0.00 |
| July | 94.19 | 22.63 | 71.57 | 131.80 | 22.62 | 0.00 | 0.00 | 0.00 |
| August | 105.14 | 33.45 | 71.69 | 142.24 | 31.23 | 0.00 | 0.00 | 0.00 |
| September | 124.84 | 61.57 | 63.27 | 150.78 | 55.27 | 0.00 | 0.00 | 0.00 |
| October | 118.33 | 67.73 | 50.60 | 116.32 | 91.62 | 0.00 | 0.00 | 0.00 |
| November | 84.76 | 47.98 | 36.78 | 69.49 | 124.41 | 0.00 | 0.00 | 0.00 |
| December | 78.86 | 40.82 | 38.04 | 47.40 | 181.96 | 0.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.88 | 45.35 | 57.53 | 100.34 | 99.69 | 1.83 | 0.00 | 0.00 |
| Minimum of Months | 78.86 | 19.88 | 36.78 | 47.40 | 22.62 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.36 | 71.77 | 72.95 | 150.78 | 184.98 | 1.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM220_223_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 94.07 | 54.80 | 39.26 | 61.32 | 184.98 | 0.33 | 0.00 | 0.00 |
| February | 107.50 | 51.76 | 55.75 | 65.47 | 180.98 | 1.00 | 0.00 | 0.00 |
| March | 129.36 | 71.77 | 57.59 | 108.35 | 128.92 | 0.00 | 0.00 | 0.00 |
| April | 110.00 | 44.64 | 65.37 | 99.36 | 98.86 | 0.00 | 0.00 | 0.00 |
| May | 95.20 | 27.60 | 67.60 | 97.33 | 63.15 | 0.00 | 0.00 | 0.00 |
| June | 92.83 | 19.88 | 72.95 | 111.76 | 37.52 | 0.00 | 0.00 | 0.00 |
| July | 94.19 | 22.63 | 71.57 | 131.80 | 22.62 | 0.00 | 0.00 | 0.00 |
| August | 105.14 | 33.45 | 71.69 | 142.24 | 31.23 | 0.00 | 0.00 | 0.00 |
| September | 124.84 | 61.57 | 63.27 | 150.78 | 55.27 | 0.00 | 0.00 | 0.00 |
| October | 118.33 | 67.73 | 50.60 | 116.32 | 91.62 | 0.00 | 0.00 | 0.00 |
| November | 84.76 | 47.98 | 36.78 | 69.49 | 124.41 | 0.00 | 0.00 | 0.00 |
| December | 78.86 | 40.82 | 38.04 | 47.40 | 181.96 | 0.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.88 | 45.35 | 57.53 | 100.34 | 99.69 | 1.83 | 0.00 | 0.00 |
| Minimum of Months | 78.86 | 19.88 | 36.78 | 47.40 | 22.62 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.36 | 71.77 | 72.95 | 150.78 | 184.98 | 1.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM220_223_3_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 94.07 | 54.80 | 39.26 | 61.32 | 184.98 | 0.33 | 0.00 | 0.00 |
| February | 107.50 | 51.76 | 55.75 | 65.47 | 180.98 | 1.00 | 0.00 | 0.00 |
| March | 129.36 | 71.77 | 57.59 | 108.35 | 128.92 | 0.00 | 0.00 | 0.00 |
| April | 110.00 | 44.64 | 65.37 | 99.36 | 98.86 | 0.00 | 0.00 | 0.00 |
| May | 95.20 | 27.60 | 67.60 | 97.33 | 63.15 | 0.00 | 0.00 | 0.00 |
| June | 92.83 | 19.88 | 72.95 | 111.76 | 37.52 | 0.00 | 0.00 | 0.00 |
| July | 94.19 | 22.63 | 71.57 | 131.80 | 22.62 | 0.00 | 0.00 | 0.00 |
| August | 105.14 | 33.45 | 71.69 | 142.24 | 31.23 | 0.00 | 0.00 | 0.00 |
| September | 124.84 | 61.57 | 63.27 | 150.78 | 55.27 | 0.00 | 0.00 | 0.00 |
| October | 118.33 | 67.73 | 50.60 | 116.32 | 91.62 | 0.00 | 0.00 | 0.00 |
| November | 84.76 | 47.98 | 36.78 | 69.49 | 124.41 | 0.00 | 0.00 | 0.00 |
| December | 78.86 | 40.82 | 38.04 | 47.40 | 181.96 | 0.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.88 | 45.35 | 57.53 | 100.34 | 99.69 | 1.83 | 0.00 | 0.00 |
| Minimum of Months | 78.86 | 19.88 | 36.78 | 47.40 | 22.62 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.36 | 71.77 | 72.95 | 150.78 | 184.98 | 1.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM224_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 94.07 | 54.80 | 39.26 | 62.28 | 180.57 | 5.33 | 0.00 | 0.00 |
| February | 107.50 | 51.76 | 55.75 | 66.86 | 176.68 | 8.67 | 0.00 | 0.00 |
| March | 129.36 | 71.77 | 57.59 | 109.19 | 126.82 | 0.00 | 0.00 | 0.00 |
| April | 110.00 | 44.64 | 65.37 | 99.66 | 97.73 | 0.00 | 0.00 | 0.00 |
| May | 95.20 | 27.60 | 67.60 | 97.02 | 62.73 | 0.00 | 0.00 | 0.00 |
| June | 92.83 | 19.88 | 72.95 | 110.90 | 37.59 | 0.00 | 0.00 | 0.00 |
| July | 94.19 | 22.63 | 71.57 | 130.45 | 23.00 | 0.00 | 0.00 | 0.00 |
| August | 105.14 | 33.45 | 71.69 | 141.02 | 31.77 | 0.00 | 0.00 | 0.00 |
| September | 124.84 | 61.57 | 63.27 | 149.92 | 55.52 | 0.00 | 0.00 | 0.00 |
| October | 118.33 | 67.73 | 50.60 | 116.08 | 91.11 | 0.00 | 0.00 | 0.00 |
| November | 84.76 | 47.98 | 36.78 | 69.69 | 122.71 | 0.00 | 0.00 | 0.00 |
| December | 78.86 | 40.82 | 38.04 | 48.18 | 177.61 | 11.33 | 0.00 | 0.00 |
| Annual Sum or Average | 102.88 | 45.35 | 57.53 | 100.30 | 98.23 | 25.33 | 0.00 | 0.00 |
| Minimum of Months | 78.86 | 19.88 | 36.78 | 48.18 | 23.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.36 | 71.77 | 72.95 | 149.92 | 180.57 | 11.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_CORRIDORFLR3_2_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 11.88 | 2.80 | 9.08 | 1.81 | 75.70 | 0.00 | 0.00 | 0.00 |
| February | 19.25 | 4.97 | 14.28 | 4.94 | 72.03 | 0.00 | 0.00 | 0.00 |
| March | 30.26 | 13.01 | 17.25 | 19.19 | 48.87 | 0.00 | 0.00 | 0.00 |
| April | 36.81 | 15.06 | 21.74 | 29.47 | 35.49 | 0.00 | 0.00 | 0.00 |
| May | 43.45 | 19.62 | 23.83 | 42.92 | 24.04 | 0.00 | 0.00 | 0.00 |
| June | 52.50 | 24.70 | 27.80 | 61.08 | 15.09 | 0.00 | 0.00 | 0.00 |
| July | 46.88 | 20.52 | 26.35 | 60.16 | 9.88 | 0.00 | 0.00 | 0.00 |
| August | 42.35 | 17.96 | 24.39 | 53.09 | 13.06 | 0.00 | 0.00 | 0.00 |
| September | 33.35 | 14.41 | 18.94 | 35.44 | 21.71 | 0.00 | 0.00 | 0.00 |
| October | 21.61 | 7.61 | 14.00 | 15.22 | 35.53 | 0.00 | 0.00 | 0.00 |
| November | 12.70 | 3.61 | 9.10 | 5.44 | 47.08 | 0.00 | 0.00 | 0.00 |
| December | 11.08 | 2.40 | 8.68 | 1.66 | 72.41 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 30.22 | 12.26 | 17.97 | 27.66 | 39.07 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11.08 | 2.40 | 8.68 | 1.66 | 9.88 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 52.50 | 24.70 | 27.80 | 61.08 | 75.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_CORRIDORFLR3_15_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.85 | 4.50 | 9.35 | 2.98 | 71.42 | 0.00 | 0.00 | 0.00 |
| February | 20.23 | 6.04 | 14.18 | 5.93 | 68.52 | 0.00 | 0.00 | 0.00 |
| March | 29.14 | 12.18 | 16.95 | 17.93 | 47.57 | 0.00 | 0.00 | 0.00 |
| April | 38.48 | 17.01 | 21.47 | 30.98 | 33.58 | 0.00 | 0.00 | 0.00 |
| May | 43.11 | 19.06 | 24.05 | 42.48 | 22.74 | 0.00 | 0.00 | 0.00 |
| June | 48.19 | 21.30 | 26.89 | 55.49 | 14.04 | 0.00 | 0.00 | 0.00 |
| July | 46.21 | 20.31 | 25.90 | 59.31 | 9.08 | 0.00 | 0.00 | 0.00 |
| August | 41.72 | 17.46 | 24.26 | 51.51 | 12.49 | 0.00 | 0.00 | 0.00 |
| September | 34.63 | 15.30 | 19.33 | 36.95 | 20.80 | 0.00 | 0.00 | 0.00 |
| October | 23.53 | 9.70 | 13.83 | 17.40 | 33.77 | 0.00 | 0.00 | 0.00 |
| November | 13.36 | 4.28 | 9.09 | 5.97 | 45.61 | 0.00 | 0.00 | 0.00 |
| December | 10.77 | 2.23 | 8.54 | 1.31 | 70.58 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 30.31 | 12.48 | 17.84 | 27.48 | 37.36 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 10.77 | 2.23 | 8.54 | 1.31 | 9.08 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 48.19 | 21.30 | 26.89 | 59.31 | 71.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM301_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 170.09 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.65 | 160.50 | 0.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 10.72 | 114.50 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 23.20 | 82.58 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 40.33 | 55.51 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 67.76 | 37.84 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 75.96 | 26.87 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 62.21 | 35.65 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 35.43 | 55.06 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 13.25 | 82.08 | 0.00 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 3.81 | 102.41 | 0.00 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.18 | 159.68 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 27.96 | 89.88 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 26.87 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 75.96 | 170.09 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM302_305_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 173.11 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.55 | 163.81 | 0.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 10.51 | 117.85 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 23.25 | 85.13 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 40.51 | 57.16 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 68.08 | 38.85 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 76.50 | 27.58 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 62.69 | 36.47 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 35.92 | 56.18 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 13.30 | 84.10 | 0.00 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 3.70 | 105.88 | 0.00 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.15 | 163.27 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 28.10 | 92.09 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 27.58 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 76.50 | 173.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM302_305_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 173.11 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.55 | 163.81 | 0.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 10.51 | 117.85 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 23.25 | 85.13 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 40.51 | 57.16 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 68.08 | 38.85 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 76.50 | 27.58 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 62.69 | 36.47 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 35.92 | 56.18 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 13.30 | 84.10 | 0.00 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 3.70 | 105.88 | 0.00 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.15 | 163.27 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 28.10 | 92.09 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 27.58 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 76.50 | 173.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM302_305_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 173.11 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.55 | 163.81 | 0.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 10.51 | 117.85 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 23.25 | 85.13 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 40.51 | 57.16 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 68.08 | 38.85 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 76.50 | 27.58 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 62.69 | 36.47 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 35.92 | 56.18 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 13.30 | 84.10 | 0.00 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 3.70 | 105.88 | 0.00 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.15 | 163.27 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 28.10 | 92.09 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 27.58 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 76.50 | 173.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM302_305_5_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 173.11 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.55 | 163.81 | 0.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 10.51 | 117.85 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 23.25 | 85.13 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 40.51 | 57.16 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 68.08 | 38.85 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 76.50 | 27.58 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 62.69 | 36.47 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 35.92 | 56.18 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 13.30 | 84.10 | 0.00 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 3.70 | 105.88 | 0.00 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.15 | 163.27 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 28.10 | 92.09 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 27.58 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 76.50 | 173.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM306_308_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 179.20 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.44 | 169.47 | 0.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 9.83 | 122.60 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 22.14 | 88.25 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 39.90 | 58.16 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 68.43 | 38.71 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 77.37 | 27.01 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 63.26 | 36.03 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 35.74 | 56.76 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 12.56 | 87.10 | 0.00 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 3.32 | 110.88 | 0.00 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.12 | 168.92 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 27.93 | 94.89 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 27.01 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 77.37 | 179.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM306_308_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 19.61 | 0.00 | 19.61 | 0.00 | 162.47 | 0.00 | 0.00 | 0.00 |
| February | 29.88 | 0.00 | 29.88 | 0.38 | 153.74 | 0.00 | 0.00 | 0.00 |
| March | 36.24 | 0.00 | 36.24 | 8.74 | 111.15 | 0.00 | 0.00 | 0.00 |
| April | 46.20 | 0.22 | 45.98 | 19.72 | 79.92 | 0.00 | 0.00 | 0.00 |
| May | 53.67 | 2.31 | 51.36 | 35.67 | 52.63 | 0.00 | 0.00 | 0.00 |
| June | 64.53 | 5.49 | 59.04 | 61.30 | 34.98 | 0.00 | 0.00 | 0.00 |
| July | 60.10 | 4.09 | 56.01 | 69.39 | 24.39 | 0.00 | 0.00 | 0.00 |
| August | 52.03 | 1.00 | 51.03 | 56.72 | 32.55 | 0.00 | 0.00 | 0.00 |
| September | 39.44 | 0.02 | 39.42 | 31.99 | 51.32 | 0.00 | 0.00 | 0.00 |
| October | 29.47 | 0.00 | 29.47 | 11.18 | 78.84 | 0.00 | 0.00 | 0.00 |
| November | 19.80 | 0.00 | 19.80 | 2.95 | 100.41 | 0.00 | 0.00 | 0.00 |
| December | 18.36 | 0.00 | 18.36 | 0.11 | 153.11 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 39.15 | 1.10 | 38.05 | 25.00 | 85.95 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.36 | 0.00 | 18.36 | 0.00 | 24.39 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 64.53 | 5.49 | 59.04 | 69.39 | 162.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM306_308_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 179.20 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.44 | 169.47 | 0.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 9.83 | 122.60 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 22.14 | 88.25 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 39.90 | 58.16 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 68.43 | 38.71 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 77.37 | 27.01 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 63.26 | 36.03 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 35.74 | 56.76 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 12.56 | 87.10 | 0.00 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 3.32 | 110.88 | 0.00 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.12 | 168.92 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 27.93 | 94.89 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 27.01 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 77.37 | 179.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM309_312_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 208.41 | 4.50 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.15 | 198.30 | 8.67 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 8.05 | 139.68 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 18.99 | 94.69 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 39.63 | 55.73 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 73.88 | 32.94 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 86.32 | 20.13 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 69.00 | 28.72 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 36.37 | 53.35 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 10.39 | 93.33 | 0.17 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 2.29 | 126.65 | 2.50 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.05 | 196.89 | 9.33 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 28.95 | 103.59 | 25.17 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 20.13 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 86.32 | 208.41 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM309_312_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 208.41 | 4.50 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.15 | 198.30 | 8.67 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 8.05 | 139.68 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 18.99 | 94.69 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 39.63 | 55.73 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 73.88 | 32.94 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 86.32 | 20.13 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 69.00 | 28.72 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 36.37 | 53.35 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 10.39 | 93.33 | 0.17 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 2.29 | 126.65 | 2.50 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.05 | 196.89 | 9.33 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 28.95 | 103.59 | 25.17 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 20.13 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 86.32 | 208.41 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM309_312_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 208.41 | 4.50 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.15 | 198.30 | 8.67 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 8.05 | 139.68 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 18.99 | 94.69 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 39.63 | 55.73 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 73.88 | 32.94 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 86.32 | 20.13 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 69.00 | 28.72 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 36.37 | 53.35 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 10.39 | 93.33 | 0.17 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 2.29 | 126.65 | 2.50 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.05 | 196.89 | 9.33 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 28.95 | 103.59 | 25.17 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 20.13 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 86.32 | 208.41 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM309_312_5_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 208.41 | 4.50 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.15 | 198.30 | 8.67 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 8.05 | 139.68 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 18.99 | 94.69 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 39.63 | 55.73 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 73.88 | 32.94 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 86.32 | 20.13 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 69.00 | 28.72 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 36.37 | 53.35 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 10.39 | 93.33 | 0.17 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 2.29 | 126.65 | 2.50 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.05 | 196.89 | 9.33 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 28.95 | 103.59 | 25.17 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 20.13 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 86.32 | 208.41 | 9.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM313_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 172.47 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.66 | 161.93 | 0.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 10.73 | 116.69 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 23.90 | 83.74 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 41.93 | 55.44 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 70.49 | 37.10 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 78.71 | 26.03 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 64.28 | 34.99 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 36.62 | 55.14 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 13.41 | 84.06 | 0.00 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 3.67 | 106.07 | 0.00 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.17 | 162.23 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 28.89 | 90.97 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 26.03 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 78.71 | 172.47 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM314_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 63.42 | 175.17 | 7.83 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 68.30 | 172.04 | 13.00 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 110.89 | 123.56 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 100.92 | 95.41 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 97.49 | 62.06 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 110.80 | 37.81 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 130.07 | 23.29 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 140.97 | 31.74 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 150.43 | 54.51 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 117.60 | 87.81 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 71.08 | 117.09 | 2.83 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 49.19 | 171.74 | 20.17 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 101.12 | 95.61 | 43.83 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 49.19 | 23.29 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 150.43 | 175.17 | 20.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM315_318_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 59.92 | 190.83 | 0.00 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 63.41 | 186.75 | 0.00 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 105.87 | 133.13 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 97.06 | 102.75 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 94.73 | 67.08 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 108.28 | 41.01 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 127.91 | 25.48 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 138.98 | 34.47 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 148.29 | 58.84 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 114.59 | 94.62 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 68.29 | 127.92 | 0.00 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 46.18 | 187.65 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 97.99 | 103.77 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 46.18 | 25.48 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 148.29 | 190.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM315_318_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 59.92 | 190.83 | 0.00 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 63.41 | 186.75 | 0.00 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 105.87 | 133.13 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 97.06 | 102.75 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 94.73 | 67.08 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 108.28 | 41.01 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 127.91 | 25.48 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 138.98 | 34.47 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 148.29 | 58.84 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 114.59 | 94.62 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 68.29 | 127.92 | 0.00 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 46.18 | 187.65 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 97.99 | 103.77 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 46.18 | 25.48 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 148.29 | 190.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM315_318_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 59.92 | 190.83 | 0.00 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 63.41 | 186.75 | 0.00 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 105.87 | 133.13 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 97.06 | 102.75 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 94.73 | 67.08 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 108.28 | 41.01 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 127.91 | 25.48 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 138.98 | 34.47 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 148.29 | 58.84 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 114.59 | 94.62 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 68.29 | 127.92 | 0.00 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 46.18 | 187.65 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 97.99 | 103.77 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 46.18 | 25.48 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 148.29 | 190.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM315_318_3_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 59.92 | 190.83 | 0.00 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 63.41 | 186.75 | 0.00 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 105.87 | 133.13 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 97.06 | 102.75 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 94.73 | 67.08 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 108.28 | 41.01 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 127.91 | 25.48 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 138.98 | 34.47 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 148.29 | 58.84 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 114.59 | 94.62 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 68.29 | 127.92 | 0.00 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 46.18 | 187.65 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 97.99 | 103.77 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 46.18 | 25.48 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 148.29 | 190.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM319_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 59.47 | 193.01 | 0.00 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 62.88 | 188.44 | 0.00 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 103.46 | 140.70 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 93.67 | 112.84 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 89.30 | 79.62 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 99.58 | 51.91 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 117.34 | 35.41 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 129.89 | 45.75 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 141.33 | 71.43 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 110.62 | 106.09 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 66.54 | 136.15 | 0.00 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 45.78 | 189.70 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 93.50 | 112.18 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 45.78 | 35.41 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 141.33 | 193.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM320_323_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 61.81 | 181.19 | 0.83 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 66.12 | 177.84 | 2.83 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 108.95 | 126.78 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 99.97 | 97.00 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 97.75 | 62.04 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 112.05 | 37.02 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 132.08 | 22.20 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 142.57 | 30.53 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 151.22 | 53.98 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 117.19 | 88.96 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 70.24 | 120.30 | 0.00 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 47.88 | 177.65 | 2.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 100.85 | 97.53 | 6.17 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 47.88 | 22.20 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 151.22 | 181.19 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM320_323_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 61.81 | 181.19 | 0.83 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 66.12 | 177.84 | 2.83 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 108.95 | 126.78 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 99.97 | 97.00 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 97.75 | 62.04 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 112.05 | 37.02 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 132.08 | 22.20 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 142.57 | 30.53 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 151.22 | 53.98 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 117.19 | 88.96 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 70.24 | 120.30 | 0.00 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 47.88 | 177.65 | 2.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 100.85 | 97.53 | 6.17 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 47.88 | 22.20 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 151.22 | 181.19 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM320_323_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 61.81 | 181.19 | 0.83 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 66.12 | 177.84 | 2.83 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 108.95 | 126.78 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 99.97 | 97.00 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 97.75 | 62.04 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 112.05 | 37.02 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 132.08 | 22.20 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 142.57 | 30.53 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 151.22 | 53.98 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 117.19 | 88.96 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 70.24 | 120.30 | 0.00 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 47.88 | 177.65 | 2.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 100.85 | 97.53 | 6.17 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 47.88 | 22.20 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 151.22 | 181.19 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM320_323_3_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 61.81 | 181.19 | 0.83 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 66.12 | 177.84 | 2.83 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 108.95 | 126.78 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 99.97 | 97.00 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 97.75 | 62.04 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 112.05 | 37.02 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 132.08 | 22.20 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 142.57 | 30.53 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 151.22 | 53.98 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 117.19 | 88.96 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 70.24 | 120.30 | 0.00 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 47.88 | 177.65 | 2.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 100.85 | 97.53 | 6.17 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 47.88 | 22.20 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 151.22 | 181.19 | 2.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM324_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 64.45 | 164.68 | 0.00 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 69.87 | 160.73 | 0.00 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 111.18 | 121.33 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 100.60 | 96.61 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 95.86 | 66.74 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 106.37 | 43.26 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 123.00 | 29.31 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 135.02 | 38.62 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 146.59 | 61.21 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 116.52 | 91.11 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 71.24 | 115.79 | 0.00 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 50.17 | 160.76 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 99.40 | 95.49 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 50.17 | 29.31 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 146.59 | 164.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_CORRIDORFLR4_2_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 11.88 | 2.80 | 9.08 | 1.84 | 73.26 | 0.00 | 0.00 | 0.00 |
| February | 19.25 | 4.97 | 14.28 | 4.96 | 69.78 | 0.00 | 0.00 | 0.00 |
| March | 30.26 | 13.01 | 17.25 | 19.11 | 46.66 | 0.00 | 0.00 | 0.00 |
| April | 36.81 | 15.06 | 21.74 | 28.98 | 33.02 | 0.00 | 0.00 | 0.00 |
| May | 43.45 | 19.62 | 23.83 | 42.26 | 21.57 | 0.00 | 0.00 | 0.00 |
| June | 52.50 | 24.70 | 27.80 | 60.22 | 13.69 | 0.00 | 0.00 | 0.00 |
| July | 46.88 | 20.52 | 26.35 | 59.27 | 8.99 | 0.00 | 0.00 | 0.00 |
| August | 42.35 | 17.96 | 24.39 | 52.36 | 11.94 | 0.00 | 0.00 | 0.00 |
| September | 33.35 | 14.41 | 18.94 | 35.03 | 19.56 | 0.00 | 0.00 | 0.00 |
| October | 21.61 | 7.61 | 14.00 | 15.12 | 32.58 | 0.00 | 0.00 | 0.00 |
| November | 12.70 | 3.61 | 9.10 | 5.45 | 44.34 | 0.00 | 0.00 | 0.00 |
| December | 11.08 | 2.40 | 8.68 | 1.68 | 69.97 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 30.22 | 12.26 | 17.97 | 27.32 | 36.95 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 11.08 | 2.40 | 8.68 | 1.68 | 8.99 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 52.50 | 24.70 | 27.80 | 60.22 | 73.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_CORRIDORFLR4_15_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 13.85 | 4.50 | 9.35 | 3.10 | 69.08 | 0.00 | 0.00 | 0.00 |
| February | 20.23 | 6.04 | 14.18 | 6.08 | 66.39 | 0.00 | 0.00 | 0.00 |
| March | 29.14 | 12.18 | 16.95 | 18.12 | 45.61 | 0.00 | 0.00 | 0.00 |
| April | 38.48 | 17.01 | 21.47 | 30.98 | 31.55 | 0.00 | 0.00 | 0.00 |
| May | 43.11 | 19.06 | 24.05 | 42.30 | 20.76 | 0.00 | 0.00 | 0.00 |
| June | 48.19 | 21.30 | 26.89 | 55.04 | 12.98 | 0.00 | 0.00 | 0.00 |
| July | 46.21 | 20.31 | 25.90 | 58.67 | 8.38 | 0.00 | 0.00 | 0.00 |
| August | 41.72 | 17.46 | 24.26 | 51.02 | 11.53 | 0.00 | 0.00 | 0.00 |
| September | 34.63 | 15.30 | 19.33 | 36.91 | 18.99 | 0.00 | 0.00 | 0.00 |
| October | 23.53 | 9.70 | 13.83 | 17.68 | 31.22 | 0.00 | 0.00 | 0.00 |
| November | 13.36 | 4.28 | 9.09 | 6.16 | 43.05 | 0.00 | 0.00 | 0.00 |
| December | 10.77 | 2.23 | 8.54 | 1.38 | 68.17 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 30.31 | 12.48 | 17.84 | 27.41 | 35.49 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 10.77 | 2.23 | 8.54 | 1.38 | 8.38 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 48.19 | 21.30 | 26.89 | 58.67 | 69.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM401_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 194.97 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.28 | 185.48 | 1.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 8.99 | 128.54 | 1.50 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 19.35 | 85.97 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 37.28 | 50.50 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 69.57 | 30.04 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 81.64 | 18.21 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 65.18 | 26.19 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 34.42 | 48.52 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 11.37 | 83.33 | 1.83 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 2.98 | 112.11 | 1.50 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.11 | 183.02 | 1.67 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 27.78 | 95.12 | 7.50 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 18.21 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 81.64 | 194.97 | 1.83 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM402_405_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.01 | 159.37 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.69 | 150.85 | 0.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 10.30 | 105.02 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 21.49 | 72.54 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 36.42 | 48.67 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 62.91 | 33.53 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 71.31 | 23.78 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 57.87 | 31.31 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 32.70 | 47.88 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 13.04 | 70.84 | 0.00 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 3.92 | 89.21 | 0.00 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.21 | 148.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 26.07 | 81.47 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.01 | 23.78 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 71.31 | 159.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM402_405_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.01 | 159.37 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.69 | 150.85 | 0.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 10.30 | 105.02 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 21.49 | 72.54 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 36.42 | 48.67 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 62.91 | 33.53 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 71.31 | 23.78 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 57.87 | 31.31 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 32.70 | 47.88 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 13.04 | 70.84 | 0.00 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 3.92 | 89.21 | 0.00 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.21 | 148.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 26.07 | 81.47 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.01 | 23.78 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 71.31 | 159.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM402_405_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.01 | 159.37 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.69 | 150.85 | 0.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 10.30 | 105.02 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 21.49 | 72.54 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 36.42 | 48.67 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 62.91 | 33.53 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 71.31 | 23.78 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 57.87 | 31.31 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 32.70 | 47.88 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 13.04 | 70.84 | 0.00 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 3.92 | 89.21 | 0.00 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.21 | 148.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 26.07 | 81.47 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.01 | 23.78 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 71.31 | 159.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM402_405_5_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.01 | 159.37 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.69 | 150.85 | 0.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 10.30 | 105.02 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 21.49 | 72.54 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 36.42 | 48.67 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 62.91 | 33.53 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 71.31 | 23.78 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 57.87 | 31.31 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 32.70 | 47.88 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 13.04 | 70.84 | 0.00 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 3.92 | 89.21 | 0.00 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.21 | 148.67 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 26.07 | 81.47 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.01 | 23.78 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 71.31 | 159.37 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM406_408_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 161.79 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.58 | 153.13 | 0.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 9.81 | 107.64 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 20.71 | 75.01 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 36.11 | 49.72 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 63.19 | 33.72 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 71.85 | 23.66 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 58.25 | 31.33 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 32.64 | 48.72 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 12.48 | 73.36 | 0.00 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 3.58 | 92.68 | 0.00 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.18 | 151.11 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 25.94 | 83.15 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 23.66 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 71.85 | 161.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM406_408_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 161.79 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.58 | 153.13 | 0.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 9.81 | 107.64 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 20.71 | 75.01 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 36.11 | 49.72 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 63.19 | 33.72 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 71.85 | 23.66 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 58.25 | 31.33 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 32.64 | 48.72 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 12.48 | 73.36 | 0.00 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 3.58 | 92.68 | 0.00 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.18 | 151.11 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 25.94 | 83.15 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 23.66 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 71.85 | 161.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM406_408_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 19.61 | 0.00 | 19.61 | 0.00 | 146.91 | 0.00 | 0.00 | 0.00 |
| February | 29.88 | 0.00 | 29.88 | 0.49 | 139.12 | 0.00 | 0.00 | 0.00 |
| March | 36.24 | 0.00 | 36.24 | 8.72 | 97.68 | 0.00 | 0.00 | 0.00 |
| April | 46.20 | 0.22 | 45.98 | 18.43 | 67.96 | 0.00 | 0.00 | 0.00 |
| May | 53.67 | 2.31 | 51.36 | 32.25 | 45.01 | 0.00 | 0.00 | 0.00 |
| June | 64.53 | 5.49 | 59.04 | 56.60 | 30.48 | 0.00 | 0.00 | 0.00 |
| July | 60.10 | 4.09 | 56.01 | 64.46 | 21.37 | 0.00 | 0.00 | 0.00 |
| August | 52.03 | 1.00 | 51.03 | 52.24 | 28.31 | 0.00 | 0.00 | 0.00 |
| September | 39.44 | 0.02 | 39.42 | 29.21 | 44.06 | 0.00 | 0.00 | 0.00 |
| October | 29.47 | 0.00 | 29.47 | 11.11 | 66.42 | 0.00 | 0.00 | 0.00 |
| November | 19.80 | 0.00 | 19.80 | 3.18 | 83.96 | 0.00 | 0.00 | 0.00 |
| December | 18.36 | 0.00 | 18.36 | 0.16 | 137.15 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 39.15 | 1.10 | 38.05 | 23.21 | 75.39 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 18.36 | 0.00 | 18.36 | 0.00 | 21.37 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 64.53 | 5.49 | 59.04 | 64.46 | 146.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM409_412_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 200.31 | 9.33 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.15 | 190.90 | 13.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 7.57 | 134.07 | 1.67 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 17.06 | 89.78 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 36.10 | 51.92 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 69.45 | 30.03 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 82.12 | 17.88 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 65.23 | 26.01 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 33.81 | 49.90 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 9.60 | 88.02 | 1.17 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 2.15 | 119.40 | 10.83 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.06 | 188.76 | 19.33 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 27.12 | 98.45 | 55.33 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 17.88 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 82.12 | 200.31 | 19.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM409_412_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 200.31 | 9.33 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.15 | 190.90 | 13.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 7.57 | 134.07 | 1.67 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 17.06 | 89.78 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 36.10 | 51.92 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 69.45 | 30.03 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 82.12 | 17.88 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 65.23 | 26.01 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 33.81 | 49.90 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 9.60 | 88.02 | 1.17 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 2.15 | 119.40 | 10.83 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.06 | 188.76 | 19.33 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 27.12 | 98.45 | 55.33 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 17.88 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 82.12 | 200.31 | 19.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM409_412_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 200.31 | 9.33 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.15 | 190.90 | 13.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 7.57 | 134.07 | 1.67 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 17.06 | 89.78 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 36.10 | 51.92 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 69.45 | 30.03 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 82.12 | 17.88 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 65.23 | 26.01 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 33.81 | 49.90 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 9.60 | 88.02 | 1.17 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 2.15 | 119.40 | 10.83 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.06 | 188.76 | 19.33 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 27.12 | 98.45 | 55.33 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 17.88 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 82.12 | 200.31 | 19.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM409_412_5_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.00 | 200.31 | 9.33 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.15 | 190.90 | 13.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 7.57 | 134.07 | 1.67 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 17.06 | 89.78 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 36.10 | 51.92 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 69.45 | 30.03 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 82.12 | 17.88 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 65.23 | 26.01 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 33.81 | 49.90 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 9.60 | 88.02 | 1.17 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 2.15 | 119.40 | 10.83 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.06 | 188.76 | 19.33 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 27.12 | 98.45 | 55.33 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.00 | 17.88 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 82.12 | 200.31 | 19.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM413_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 21.89 | 0.00 | 21.89 | 0.01 | 161.12 | 0.00 | 0.00 | 0.00 |
| February | 33.36 | 0.00 | 33.36 | 0.82 | 151.76 | 0.00 | 0.00 | 0.00 |
| March | 40.46 | 0.00 | 40.46 | 10.77 | 106.43 | 0.00 | 0.00 | 0.00 |
| April | 51.58 | 0.25 | 51.33 | 22.81 | 74.06 | 0.00 | 0.00 | 0.00 |
| May | 59.92 | 2.58 | 57.34 | 38.77 | 49.37 | 0.00 | 0.00 | 0.00 |
| June | 72.04 | 6.13 | 65.92 | 65.88 | 33.80 | 0.00 | 0.00 | 0.00 |
| July | 67.10 | 4.56 | 62.53 | 73.56 | 23.92 | 0.00 | 0.00 | 0.00 |
| August | 58.09 | 1.12 | 56.97 | 59.80 | 31.79 | 0.00 | 0.00 | 0.00 |
| September | 44.03 | 0.02 | 44.01 | 34.25 | 49.34 | 0.00 | 0.00 | 0.00 |
| October | 32.90 | 0.00 | 32.90 | 13.53 | 73.42 | 0.00 | 0.00 | 0.00 |
| November | 22.11 | 0.00 | 22.11 | 3.94 | 91.73 | 0.00 | 0.00 | 0.00 |
| December | 20.49 | 0.00 | 20.49 | 0.22 | 150.10 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 43.71 | 1.23 | 42.48 | 27.19 | 82.73 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 20.49 | 0.00 | 20.49 | 0.01 | 23.92 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 72.04 | 6.13 | 65.92 | 73.56 | 161.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM414_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 67.09 | 143.99 | 0.00 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 72.74 | 142.04 | 0.00 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 112.67 | 104.91 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 99.77 | 84.21 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 92.48 | 59.65 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 101.29 | 39.85 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 117.61 | 27.24 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 130.80 | 35.33 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 144.29 | 54.40 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 116.99 | 78.42 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 72.75 | 97.99 | 0.00 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 52.36 | 140.42 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 98.55 | 83.72 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 52.36 | 27.24 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 144.29 | 143.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM415_418_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 61.37 | 174.60 | 3.17 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 65.33 | 171.81 | 6.50 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 106.77 | 121.30 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 96.90 | 92.49 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 93.60 | 58.78 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 106.87 | 34.73 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 126.79 | 20.26 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 137.89 | 28.22 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 147.66 | 50.74 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 115.12 | 84.30 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 69.21 | 114.74 | 0.33 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 47.51 | 171.28 | 11.33 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 98.11 | 93.18 | 21.33 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 47.51 | 20.26 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 147.66 | 174.60 | 11.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM415_418_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 61.37 | 174.60 | 3.17 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 65.33 | 171.81 | 6.50 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 106.77 | 121.30 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 96.90 | 92.49 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 93.60 | 58.78 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 106.87 | 34.73 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 126.79 | 20.26 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 137.89 | 28.22 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 147.66 | 50.74 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 115.12 | 84.30 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 69.21 | 114.74 | 0.33 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 47.51 | 171.28 | 11.33 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 98.11 | 93.18 | 21.33 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 47.51 | 20.26 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 147.66 | 174.60 | 11.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM415_418_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 61.37 | 174.60 | 3.17 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 65.33 | 171.81 | 6.50 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 106.77 | 121.30 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 96.90 | 92.49 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 93.60 | 58.78 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 106.87 | 34.73 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 126.79 | 20.26 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 137.89 | 28.22 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 147.66 | 50.74 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 115.12 | 84.30 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 69.21 | 114.74 | 0.33 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 47.51 | 171.28 | 11.33 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 98.11 | 93.18 | 21.33 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 47.51 | 20.26 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 147.66 | 174.60 | 11.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM415_418_3_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 61.37 | 174.60 | 3.17 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 65.33 | 171.81 | 6.50 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 106.77 | 121.30 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 96.90 | 92.49 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 93.60 | 58.78 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 106.87 | 34.73 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 126.79 | 20.26 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 137.89 | 28.22 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 147.66 | 50.74 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 115.12 | 84.30 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 69.21 | 114.74 | 0.33 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 47.51 | 171.28 | 11.33 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 98.11 | 93.18 | 21.33 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 47.51 | 20.26 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 147.66 | 174.60 | 11.33 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM419_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 61.35 | 177.45 | 7.17 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 65.17 | 174.77 | 13.67 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 106.66 | 123.54 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 96.88 | 94.46 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 93.59 | 60.27 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 107.03 | 35.65 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 127.10 | 20.83 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 138.12 | 29.02 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 147.64 | 51.97 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 114.93 | 86.14 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 69.10 | 116.88 | 2.83 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 47.42 | 174.18 | 20.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 98.11 | 95.00 | 44.17 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 47.42 | 20.83 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 147.64 | 177.45 | 20.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM420_423_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 61.83 | 172.83 | 4.83 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 65.98 | 170.21 | 8.83 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 107.53 | 120.08 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 97.62 | 91.35 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 94.32 | 57.69 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 107.80 | 33.78 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 127.87 | 19.50 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 138.84 | 27.32 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 148.42 | 49.61 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 115.79 | 83.08 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 69.72 | 113.13 | 3.17 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 47.94 | 169.47 | 16.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 98.83 | 91.92 | 33.33 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 47.94 | 19.50 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 148.42 | 172.83 | 16.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM420_423_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 61.83 | 172.83 | 4.83 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 65.98 | 170.21 | 8.83 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 107.53 | 120.08 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 97.62 | 91.35 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 94.32 | 57.69 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 107.80 | 33.78 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 127.87 | 19.50 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 138.84 | 27.32 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 148.42 | 49.61 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 115.79 | 83.08 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 69.72 | 113.13 | 3.17 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 47.94 | 169.47 | 16.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 98.83 | 91.92 | 33.33 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 47.94 | 19.50 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 148.42 | 172.83 | 16.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM420_423_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 61.83 | 172.83 | 4.83 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 65.98 | 170.21 | 8.83 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 107.53 | 120.08 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 97.62 | 91.35 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 94.32 | 57.69 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 107.80 | 33.78 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 127.87 | 19.50 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 138.84 | 27.32 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 148.42 | 49.61 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 115.79 | 83.08 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 69.72 | 113.13 | 3.17 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 47.94 | 169.47 | 16.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 98.83 | 91.92 | 33.33 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 47.94 | 19.50 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 148.42 | 172.83 | 16.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM420_423_3_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 61.83 | 172.83 | 4.83 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 65.98 | 170.21 | 8.83 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 107.53 | 120.08 | 0.00 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 97.62 | 91.35 | 0.00 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 94.32 | 57.69 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 107.80 | 33.78 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 127.87 | 19.50 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 138.84 | 27.32 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 148.42 | 49.61 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 115.79 | 83.08 | 0.00 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 69.72 | 113.13 | 3.17 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 47.94 | 169.47 | 16.50 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 98.83 | 91.92 | 33.33 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 47.94 | 19.50 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 148.42 | 172.83 | 16.50 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: W_GUESTROOM424_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 93.89 | 54.70 | 39.19 | 63.57 | 169.82 | 10.83 | 0.00 | 0.00 |
| February | 107.30 | 51.66 | 55.64 | 68.20 | 167.48 | 20.33 | 0.00 | 0.00 |
| March | 129.12 | 71.64 | 57.48 | 109.52 | 118.85 | 5.83 | 0.00 | 0.00 |
| April | 109.80 | 44.55 | 65.24 | 98.90 | 91.00 | 1.33 | 0.00 | 0.00 |
| May | 95.01 | 27.55 | 67.47 | 94.87 | 58.18 | 0.00 | 0.00 | 0.00 |
| June | 92.66 | 19.84 | 72.81 | 107.94 | 34.67 | 0.00 | 0.00 | 0.00 |
| July | 94.02 | 22.58 | 71.43 | 127.48 | 20.52 | 0.00 | 0.00 | 0.00 |
| August | 104.94 | 33.39 | 71.56 | 138.58 | 28.54 | 0.00 | 0.00 | 0.00 |
| September | 124.60 | 61.46 | 63.15 | 148.46 | 50.66 | 0.00 | 0.00 | 0.00 |
| October | 118.10 | 67.60 | 50.51 | 116.51 | 83.12 | 0.33 | 0.00 | 0.00 |
| November | 84.60 | 47.89 | 36.71 | 70.69 | 111.66 | 11.50 | 0.00 | 0.00 |
| December | 78.71 | 40.74 | 37.97 | 49.32 | 166.53 | 27.67 | 0.00 | 0.00 |
| Annual Sum or Average | 102.69 | 45.27 | 57.42 | 99.68 | 91.35 | 77.83 | 0.00 | 0.00 |
| Minimum of Months | 78.71 | 19.84 | 36.71 | 49.32 | 20.52 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 129.12 | 71.64 | 72.81 | 148.46 | 169.82 | 27.67 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: W_CORRIDORFLR1_2_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 65190419.57 | 15353194.18 | 49837225.39 | 8190417.02 | 0.456517E+09 |
| February | 95408038.94 | 24623030.78 | 70785008.15 | 21830493.27 | 0.389125E+09 |
| March | 0.166056E+09 | 71384015.56 | 94671911.65 | 96552857.36 | 0.299140E+09 |
| April | 0.195485E+09 | 80010334.32 | 0.115474E+09 | 0.145582E+09 | 0.211711E+09 |
| May | 0.238471E+09 | 0.107680E+09 | 0.130790E+09 | 0.226354E+09 | 0.141620E+09 |
| June | 0.278816E+09 | 0.131173E+09 | 0.147643E+09 | 0.315411E+09 | 85281724.70 |
| July | 0.257278E+09 | 0.112641E+09 | 0.144636E+09 | 0.319737E+09 | 60093207.28 |
| August | 0.232440E+09 | 98579221.55 | 0.133860E+09 | 0.280841E+09 | 78996110.85 |
| September | 0.177118E+09 | 76529173.03 | 0.100589E+09 | 0.178575E+09 | 0.126402E+09 |
| October | 0.118598E+09 | 41776597.89 | 76821370.37 | 74087669.41 | 0.224876E+09 |
| November | 67458059.06 | 19150589.93 | 48307469.13 | 23894351.89 | 0.294132E+09 |
| December | 60809550.68 | 13176045.90 | 47633504.77 | 7397392.87 | 0.441459E+09 |
| Annual Sum or Average | 0.195313E+10 | 0.792077E+09 | 0.116105E+10 | 0.169845E+10 | 0.280935E+10 |
| Minimum of Months | 60809550.68 | 13176045.90 | 47633504.77 | 7397392.87 | 60093207.28 |
| Maximum of Months | 0.278816E+09 | 0.131173E+09 | 0.147643E+09 | 0.319737E+09 | 0.456517E+09 |
Report: WindowEnergyReportMonthly
For: D_CORRIDORFLR1_16_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 74760613.72 | 27379346.21 | 47381267.51 | 5655623.80 | 0.751391E+09 |
| February | 79888082.87 | 21088195.45 | 58799887.42 | 6760250.67 | 0.683401E+09 |
| March | 99866450.65 | 19079899.11 | 80786551.53 | 15099988.50 | 0.560569E+09 |
| April | 0.122446E+09 | 21850428.85 | 0.100596E+09 | 26988440.68 | 0.388707E+09 |
| May | 0.137753E+09 | 16163442.93 | 0.121589E+09 | 58791125.31 | 0.246117E+09 |
| June | 0.152414E+09 | 16519793.91 | 0.135895E+09 | 0.114439E+09 | 0.135580E+09 |
| July | 0.150475E+09 | 18049083.86 | 0.132426E+09 | 0.153345E+09 | 86875602.64 |
| August | 0.137534E+09 | 18192813.55 | 0.119341E+09 | 0.128635E+09 | 0.124821E+09 |
| September | 0.109921E+09 | 18699153.77 | 91222225.74 | 59718225.30 | 0.206881E+09 |
| October | 93483033.84 | 27966694.70 | 65516339.14 | 27375361.77 | 0.391107E+09 |
| November | 66279051.84 | 23341332.05 | 42937719.78 | 15851034.75 | 0.499912E+09 |
| December | 57368352.45 | 15144584.03 | 42223768.42 | 3039479.95 | 0.748198E+09 |
| Annual Sum or Average | 0.128219E+10 | 0.243475E+09 | 0.103871E+10 | 0.615698E+09 | 0.482356E+10 |
| Minimum of Months | 57368352.45 | 15144584.03 | 42223768.42 | 3039479.95 | 86875602.64 |
| Maximum of Months | 0.152414E+09 | 27966694.70 | 0.135895E+09 | 0.153345E+09 | 0.751391E+09 |
Report: WindowEnergyReportMonthly
For: W_CORRIDORFLR1_20_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 41439888.25 | 0.00 | 41439888.25 | 0.00 | 0.479294E+09 |
| February | 57028633.26 | 0.00 | 57028633.26 | 0.00 | 0.411168E+09 |
| March | 76581796.51 | 2712.18 | 76579084.33 | 8543638.04 | 0.334112E+09 |
| April | 94480729.39 | 455541.43 | 94025187.97 | 19443697.94 | 0.224661E+09 |
| May | 0.113414E+09 | 4883527.19 | 0.108531E+09 | 52216734.06 | 0.139926E+09 |
| June | 0.131958E+09 | 11220544.57 | 0.120738E+09 | 0.108472E+09 | 80509281.45 |
| July | 0.126994E+09 | 8638964.47 | 0.118355E+09 | 0.134220E+09 | 57394357.35 |
| August | 0.109948E+09 | 2122484.96 | 0.107826E+09 | 0.105000E+09 | 80240519.85 |
| September | 80642996.01 | 35688.60 | 80607307.41 | 46295229.57 | 0.133848E+09 |
| October | 62264070.91 | 0.00 | 62264070.91 | 8516622.26 | 0.239057E+09 |
| November | 40490247.89 | 0.00 | 40490247.89 | 1357856.87 | 0.307460E+09 |
| December | 38786495.56 | 0.00 | 38786495.56 | 0.00 | 0.457643E+09 |
| Annual Sum or Average | 0.974030E+09 | 27359463.39 | 0.946670E+09 | 0.484066E+09 | 0.294531E+10 |
| Minimum of Months | 38786495.56 | 0.00 | 38786495.56 | 0.00 | 57394357.35 |
| Maximum of Months | 0.131958E+09 | 11220544.57 | 0.120738E+09 | 0.134220E+09 | 0.479294E+09 |
Report: WindowEnergyReportMonthly
For: W_FRONTLOUNGEFLR1_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 45738738.46 | 0.00 | 45738738.46 | 0.00 | 0.442722E+09 |
| February | 62944613.32 | 0.00 | 62944613.32 | 241902.72 | 0.378334E+09 |
| March | 84526163.30 | 2993.53 | 84523169.77 | 17838820.44 | 0.290606E+09 |
| April | 0.104282E+09 | 502797.93 | 0.103779E+09 | 41542528.97 | 0.187974E+09 |
| May | 0.125180E+09 | 5390129.71 | 0.119789E+09 | 85820637.65 | 0.117261E+09 |
| June | 0.145647E+09 | 12384530.35 | 0.133263E+09 | 0.150487E+09 | 71495997.44 |
| July | 0.140168E+09 | 9535144.83 | 0.130633E+09 | 0.178649E+09 | 49435631.37 |
| August | 0.121354E+09 | 2342665.20 | 0.119011E+09 | 0.142192E+09 | 69811983.92 |
| September | 89008659.51 | 39390.83 | 88969268.69 | 71173557.33 | 0.118074E+09 |
| October | 68723159.63 | 0.00 | 68723159.63 | 20446028.04 | 0.203634E+09 |
| November | 44690585.24 | 0.00 | 44690585.24 | 4320917.44 | 0.264130E+09 |
| December | 42810090.75 | 0.00 | 42810090.75 | 84725.96 | 0.421681E+09 |
| Annual Sum or Average | 0.107507E+10 | 30197652.39 | 0.104488E+10 | 0.712798E+09 | 0.261516E+10 |
| Minimum of Months | 42810090.75 | 0.00 | 42810090.75 | 0.00 | 49435631.37 |
| Maximum of Months | 0.145647E+09 | 12384530.35 | 0.133263E+09 | 0.178649E+09 | 0.442722E+09 |
Report: WindowEnergyReportMonthly
For: W_FRONTLOUNGEFLR1_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 45738738.46 | 0.00 | 45738738.46 | 0.00 | 0.442722E+09 |
| February | 62944613.32 | 0.00 | 62944613.32 | 241902.72 | 0.378334E+09 |
| March | 84526163.30 | 2993.53 | 84523169.77 | 17838820.44 | 0.290606E+09 |
| April | 0.104282E+09 | 502797.93 | 0.103779E+09 | 41542528.97 | 0.187974E+09 |
| May | 0.125180E+09 | 5390129.71 | 0.119789E+09 | 85820637.65 | 0.117261E+09 |
| June | 0.145647E+09 | 12384530.35 | 0.133263E+09 | 0.150487E+09 | 71495997.44 |
| July | 0.140168E+09 | 9535144.83 | 0.130633E+09 | 0.178649E+09 | 49435631.37 |
| August | 0.121354E+09 | 2342665.20 | 0.119011E+09 | 0.142192E+09 | 69811983.92 |
| September | 89008659.51 | 39390.83 | 88969268.69 | 71173557.33 | 0.118074E+09 |
| October | 68723159.63 | 0.00 | 68723159.63 | 20446028.04 | 0.203634E+09 |
| November | 44690585.24 | 0.00 | 44690585.24 | 4320917.44 | 0.264130E+09 |
| December | 42810090.75 | 0.00 | 42810090.75 | 84725.96 | 0.421681E+09 |
| Annual Sum or Average | 0.107507E+10 | 30197652.39 | 0.104488E+10 | 0.712798E+09 | 0.261516E+10 |
| Minimum of Months | 42810090.75 | 0.00 | 42810090.75 | 0.00 | 49435631.37 |
| Maximum of Months | 0.145647E+09 | 12384530.35 | 0.133263E+09 | 0.178649E+09 | 0.442722E+09 |
Report: WindowEnergyReportMonthly
For: W_FRONTLOUNGEFLR1_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 45738738.46 | 0.00 | 45738738.46 | 0.00 | 0.442722E+09 |
| February | 62944613.32 | 0.00 | 62944613.32 | 241902.72 | 0.378334E+09 |
| March | 84526163.30 | 2993.53 | 84523169.77 | 17838820.44 | 0.290606E+09 |
| April | 0.104282E+09 | 502797.93 | 0.103779E+09 | 41542528.97 | 0.187974E+09 |
| May | 0.125180E+09 | 5390129.71 | 0.119789E+09 | 85820637.65 | 0.117261E+09 |
| June | 0.145647E+09 | 12384530.35 | 0.133263E+09 | 0.150487E+09 | 71495997.44 |
| July | 0.140168E+09 | 9535144.83 | 0.130633E+09 | 0.178649E+09 | 49435631.37 |
| August | 0.121354E+09 | 2342665.20 | 0.119011E+09 | 0.142192E+09 | 69811983.92 |
| September | 89008659.51 | 39390.83 | 88969268.69 | 71173557.33 | 0.118074E+09 |
| October | 68723159.63 | 0.00 | 68723159.63 | 20446028.04 | 0.203634E+09 |
| November | 44690585.24 | 0.00 | 44690585.24 | 4320917.44 | 0.264130E+09 |
| December | 42810090.75 | 0.00 | 42810090.75 | 84725.96 | 0.421681E+09 |
| Annual Sum or Average | 0.107507E+10 | 30197652.39 | 0.104488E+10 | 0.712798E+09 | 0.261516E+10 |
| Minimum of Months | 42810090.75 | 0.00 | 42810090.75 | 0.00 | 49435631.37 |
| Maximum of Months | 0.145647E+09 | 12384530.35 | 0.133263E+09 | 0.178649E+09 | 0.442722E+09 |
Report: WindowEnergyReportMonthly
For: W_FRONTLOUNGEFLR1_5_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 45738738.46 | 0.00 | 45738738.46 | 0.00 | 0.442722E+09 |
| February | 62944613.32 | 0.00 | 62944613.32 | 241902.72 | 0.378334E+09 |
| March | 84526163.30 | 2993.53 | 84523169.77 | 17838820.44 | 0.290606E+09 |
| April | 0.104282E+09 | 502797.93 | 0.103779E+09 | 41542528.97 | 0.187974E+09 |
| May | 0.125180E+09 | 5390129.71 | 0.119789E+09 | 85820637.65 | 0.117261E+09 |
| June | 0.145647E+09 | 12384530.35 | 0.133263E+09 | 0.150487E+09 | 71495997.44 |
| July | 0.140168E+09 | 9535144.83 | 0.130633E+09 | 0.178649E+09 | 49435631.37 |
| August | 0.121354E+09 | 2342665.20 | 0.119011E+09 | 0.142192E+09 | 69811983.92 |
| September | 89008659.51 | 39390.83 | 88969268.69 | 71173557.33 | 0.118074E+09 |
| October | 68723159.63 | 0.00 | 68723159.63 | 20446028.04 | 0.203634E+09 |
| November | 44690585.24 | 0.00 | 44690585.24 | 4320917.44 | 0.264130E+09 |
| December | 42810090.75 | 0.00 | 42810090.75 | 84725.96 | 0.421681E+09 |
| Annual Sum or Average | 0.107507E+10 | 30197652.39 | 0.104488E+10 | 0.712798E+09 | 0.261516E+10 |
| Minimum of Months | 42810090.75 | 0.00 | 42810090.75 | 0.00 | 49435631.37 |
| Maximum of Months | 0.145647E+09 | 12384530.35 | 0.133263E+09 | 0.178649E+09 | 0.442722E+09 |
Report: WindowEnergyReportMonthly
For: W_FRONTLOUNGEFLR1_5_0_0_0_4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 45738738.46 | 0.00 | 45738738.46 | 0.00 | 0.442722E+09 |
| February | 62944613.32 | 0.00 | 62944613.32 | 241902.72 | 0.378334E+09 |
| March | 84526163.30 | 2993.53 | 84523169.77 | 17838820.44 | 0.290606E+09 |
| April | 0.104282E+09 | 502797.93 | 0.103779E+09 | 41542528.97 | 0.187974E+09 |
| May | 0.125180E+09 | 5390129.71 | 0.119789E+09 | 85820637.65 | 0.117261E+09 |
| June | 0.145647E+09 | 12384530.35 | 0.133263E+09 | 0.150487E+09 | 71495997.44 |
| July | 0.140168E+09 | 9535144.83 | 0.130633E+09 | 0.178649E+09 | 49435631.37 |
| August | 0.121354E+09 | 2342665.20 | 0.119011E+09 | 0.142192E+09 | 69811983.92 |
| September | 89008659.51 | 39390.83 | 88969268.69 | 71173557.33 | 0.118074E+09 |
| October | 68723159.63 | 0.00 | 68723159.63 | 20446028.04 | 0.203634E+09 |
| November | 44690585.24 | 0.00 | 44690585.24 | 4320917.44 | 0.264130E+09 |
| December | 42810090.75 | 0.00 | 42810090.75 | 84725.96 | 0.421681E+09 |
| Annual Sum or Average | 0.107507E+10 | 30197652.39 | 0.104488E+10 | 0.712798E+09 | 0.261516E+10 |
| Minimum of Months | 42810090.75 | 0.00 | 42810090.75 | 0.00 | 49435631.37 |
| Maximum of Months | 0.145647E+09 | 12384530.35 | 0.133263E+09 | 0.178649E+09 | 0.442722E+09 |
Report: WindowEnergyReportMonthly
For: W_MEETINGROOMFLR1_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58563996.22 | 0.00 | 58563996.22 | 0.00 | 0.575544E+09 |
| February | 80594443.32 | 0.00 | 80594443.32 | 276451.21 | 0.492535E+09 |
| March | 0.108228E+09 | 3832.92 | 0.108224E+09 | 21738808.12 | 0.384626E+09 |
| April | 0.133523E+09 | 643782.76 | 0.132879E+09 | 50743311.26 | 0.256034E+09 |
| May | 0.160280E+09 | 6901525.17 | 0.153379E+09 | 0.103619E+09 | 0.165467E+09 |
| June | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.184772E+09 | 97408521.75 |
| July | 0.179472E+09 | 12208804.91 | 0.167263E+09 | 0.221018E+09 | 66120847.93 |
| August | 0.155382E+09 | 2999549.87 | 0.152382E+09 | 0.176417E+09 | 93661445.94 |
| September | 0.113967E+09 | 50436.04 | 0.113917E+09 | 87628569.69 | 0.160712E+09 |
| October | 87993325.09 | 0.00 | 87993325.09 | 24726511.13 | 0.278835E+09 |
| November | 57221937.69 | 0.00 | 57221937.69 | 5216128.34 | 0.354353E+09 |
| December | 54814143.07 | 0.00 | 54814143.07 | 108763.49 | 0.548601E+09 |
| Annual Sum or Average | 0.137653E+10 | 38665091.42 | 0.133786E+10 | 0.876264E+09 | 0.347390E+10 |
| Minimum of Months | 54814143.07 | 0.00 | 54814143.07 | 0.00 | 66120847.93 |
| Maximum of Months | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.221018E+09 | 0.575544E+09 |
Report: WindowEnergyReportMonthly
For: W_MEETINGROOMFLR1_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58563996.22 | 0.00 | 58563996.22 | 0.00 | 0.575544E+09 |
| February | 80594443.32 | 0.00 | 80594443.32 | 276451.21 | 0.492535E+09 |
| March | 0.108228E+09 | 3832.92 | 0.108224E+09 | 21738808.12 | 0.384626E+09 |
| April | 0.133523E+09 | 643782.76 | 0.132879E+09 | 50743311.26 | 0.256034E+09 |
| May | 0.160280E+09 | 6901525.17 | 0.153379E+09 | 0.103619E+09 | 0.165467E+09 |
| June | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.184772E+09 | 97408521.75 |
| July | 0.179472E+09 | 12208804.91 | 0.167263E+09 | 0.221018E+09 | 66120847.93 |
| August | 0.155382E+09 | 2999549.87 | 0.152382E+09 | 0.176417E+09 | 93661445.94 |
| September | 0.113967E+09 | 50436.04 | 0.113917E+09 | 87628569.69 | 0.160712E+09 |
| October | 87993325.09 | 0.00 | 87993325.09 | 24726511.13 | 0.278835E+09 |
| November | 57221937.69 | 0.00 | 57221937.69 | 5216128.34 | 0.354353E+09 |
| December | 54814143.07 | 0.00 | 54814143.07 | 108763.49 | 0.548601E+09 |
| Annual Sum or Average | 0.137653E+10 | 38665091.42 | 0.133786E+10 | 0.876264E+09 | 0.347390E+10 |
| Minimum of Months | 54814143.07 | 0.00 | 54814143.07 | 0.00 | 66120847.93 |
| Maximum of Months | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.221018E+09 | 0.575544E+09 |
Report: WindowEnergyReportMonthly
For: W_MEETINGROOMFLR1_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58563996.22 | 0.00 | 58563996.22 | 0.00 | 0.575544E+09 |
| February | 80594443.32 | 0.00 | 80594443.32 | 276451.21 | 0.492535E+09 |
| March | 0.108228E+09 | 3832.92 | 0.108224E+09 | 21738808.12 | 0.384626E+09 |
| April | 0.133523E+09 | 643782.76 | 0.132879E+09 | 50743311.26 | 0.256034E+09 |
| May | 0.160280E+09 | 6901525.17 | 0.153379E+09 | 0.103619E+09 | 0.165467E+09 |
| June | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.184772E+09 | 97408521.75 |
| July | 0.179472E+09 | 12208804.91 | 0.167263E+09 | 0.221018E+09 | 66120847.93 |
| August | 0.155382E+09 | 2999549.87 | 0.152382E+09 | 0.176417E+09 | 93661445.94 |
| September | 0.113967E+09 | 50436.04 | 0.113917E+09 | 87628569.69 | 0.160712E+09 |
| October | 87993325.09 | 0.00 | 87993325.09 | 24726511.13 | 0.278835E+09 |
| November | 57221937.69 | 0.00 | 57221937.69 | 5216128.34 | 0.354353E+09 |
| December | 54814143.07 | 0.00 | 54814143.07 | 108763.49 | 0.548601E+09 |
| Annual Sum or Average | 0.137653E+10 | 38665091.42 | 0.133786E+10 | 0.876264E+09 | 0.347390E+10 |
| Minimum of Months | 54814143.07 | 0.00 | 54814143.07 | 0.00 | 66120847.93 |
| Maximum of Months | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.221018E+09 | 0.575544E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM101_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58563996.22 | 0.00 | 58563996.22 | 0.00 | 0.548149E+09 |
| February | 80594443.32 | 0.00 | 80594443.32 | 401761.64 | 0.462052E+09 |
| March | 0.108228E+09 | 3832.92 | 0.108224E+09 | 22224644.01 | 0.366298E+09 |
| April | 0.133523E+09 | 643782.76 | 0.132879E+09 | 49751787.33 | 0.248889E+09 |
| May | 0.160280E+09 | 6901525.17 | 0.153379E+09 | 0.103421E+09 | 0.158722E+09 |
| June | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.177193E+09 | 98897794.46 |
| July | 0.179472E+09 | 12208804.91 | 0.167263E+09 | 0.207125E+09 | 71417655.22 |
| August | 0.155382E+09 | 2999549.87 | 0.152382E+09 | 0.164014E+09 | 0.101271E+09 |
| September | 0.113967E+09 | 50436.04 | 0.113917E+09 | 81612590.57 | 0.166038E+09 |
| October | 87993325.09 | 0.00 | 87993325.09 | 22219634.32 | 0.283367E+09 |
| November | 57221937.69 | 0.00 | 57221937.69 | 4909412.43 | 0.356974E+09 |
| December | 54814143.07 | 0.00 | 54814143.07 | 88769.36 | 0.529354E+09 |
| Annual Sum or Average | 0.137653E+10 | 38665091.42 | 0.133786E+10 | 0.832962E+09 | 0.339143E+10 |
| Minimum of Months | 54814143.07 | 0.00 | 54814143.07 | 0.00 | 71417655.22 |
| Maximum of Months | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.207125E+09 | 0.548149E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM102_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58563996.22 | 0.00 | 58563996.22 | 0.00 | 0.529809E+09 |
| February | 80594443.32 | 0.00 | 80594443.32 | 549904.41 | 0.446253E+09 |
| March | 0.108228E+09 | 3832.92 | 0.108224E+09 | 24399234.20 | 0.350574E+09 |
| April | 0.133523E+09 | 643782.76 | 0.132879E+09 | 54511594.39 | 0.236021E+09 |
| May | 0.160280E+09 | 6901525.17 | 0.153379E+09 | 0.110915E+09 | 0.148527E+09 |
| June | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.186468E+09 | 91426795.59 |
| July | 0.179472E+09 | 12208804.91 | 0.167263E+09 | 0.217038E+09 | 64095812.38 |
| August | 0.155382E+09 | 2999549.87 | 0.152382E+09 | 0.172430E+09 | 92064984.13 |
| September | 0.113967E+09 | 50436.04 | 0.113917E+09 | 87636392.07 | 0.154521E+09 |
| October | 87993325.09 | 0.00 | 87993325.09 | 25345196.16 | 0.267858E+09 |
| November | 57221937.69 | 0.00 | 57221937.69 | 5767317.31 | 0.339747E+09 |
| December | 54814143.07 | 0.00 | 54814143.07 | 130014.83 | 0.510525E+09 |
| Annual Sum or Average | 0.137653E+10 | 38665091.42 | 0.133786E+10 | 0.885191E+09 | 0.323142E+10 |
| Minimum of Months | 54814143.07 | 0.00 | 54814143.07 | 0.00 | 64095812.38 |
| Maximum of Months | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.217038E+09 | 0.529809E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM103_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58563996.22 | 0.00 | 58563996.22 | 0.00 | 0.540442E+09 |
| February | 80594443.32 | 0.00 | 80594443.32 | 634648.03 | 0.458669E+09 |
| March | 0.108228E+09 | 3832.92 | 0.108224E+09 | 26067684.37 | 0.351402E+09 |
| April | 0.133523E+09 | 643782.76 | 0.132879E+09 | 58987479.26 | 0.226666E+09 |
| May | 0.160280E+09 | 6901525.17 | 0.153379E+09 | 0.119473E+09 | 0.134791E+09 |
| June | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.202268E+09 | 77155104.75 |
| July | 0.179472E+09 | 12208804.91 | 0.167263E+09 | 0.238489E+09 | 49339527.73 |
| August | 0.155382E+09 | 2999549.87 | 0.152382E+09 | 0.188861E+09 | 73200238.78 |
| September | 0.113967E+09 | 50436.04 | 0.113917E+09 | 96160419.46 | 0.134403E+09 |
| October | 87993325.09 | 0.00 | 87993325.09 | 28451670.68 | 0.248383E+09 |
| November | 57221937.69 | 0.00 | 57221937.69 | 6428353.10 | 0.325757E+09 |
| December | 54814143.07 | 0.00 | 54814143.07 | 163177.73 | 0.514867E+09 |
| Annual Sum or Average | 0.137653E+10 | 38665091.42 | 0.133786E+10 | 0.965984E+09 | 0.313508E+10 |
| Minimum of Months | 54814143.07 | 0.00 | 54814143.07 | 0.00 | 49339527.73 |
| Maximum of Months | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.238489E+09 | 0.540442E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM104_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251133E+09 | 0.146314E+09 | 0.104819E+09 | 0.169729E+09 | 0.477114E+09 |
| February | 0.259234E+09 | 0.124802E+09 | 0.134432E+09 | 0.166035E+09 | 0.418512E+09 |
| March | 0.345370E+09 | 0.191615E+09 | 0.153754E+09 | 0.300967E+09 | 0.328059E+09 |
| April | 0.284212E+09 | 0.115333E+09 | 0.168880E+09 | 0.266780E+09 | 0.240912E+09 |
| May | 0.254148E+09 | 73678352.78 | 0.180470E+09 | 0.269976E+09 | 0.155438E+09 |
| June | 0.239847E+09 | 51367907.77 | 0.188479E+09 | 0.297326E+09 | 89483622.74 |
| July | 0.251477E+09 | 60403595.47 | 0.191073E+09 | 0.358762E+09 | 56128038.43 |
| August | 0.280704E+09 | 89301622.93 | 0.191402E+09 | 0.384772E+09 | 79765808.67 |
| September | 0.322545E+09 | 0.159080E+09 | 0.163465E+09 | 0.394012E+09 | 0.138682E+09 |
| October | 0.315906E+09 | 0.180810E+09 | 0.135096E+09 | 0.315328E+09 | 0.239091E+09 |
| November | 0.218979E+09 | 0.123963E+09 | 95015835.14 | 0.183128E+09 | 0.313819E+09 |
| December | 0.210527E+09 | 0.108976E+09 | 0.101551E+09 | 0.130924E+09 | 0.472173E+09 |
| Annual Sum or Average | 0.323408E+10 | 0.142564E+10 | 0.180844E+10 | 0.323774E+10 | 0.300918E+10 |
| Minimum of Months | 0.210527E+09 | 51367907.77 | 95015835.14 | 0.130924E+09 | 56128038.43 |
| Maximum of Months | 0.345370E+09 | 0.191615E+09 | 0.191402E+09 | 0.394012E+09 | 0.477114E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM105_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251133E+09 | 0.146314E+09 | 0.104819E+09 | 0.159220E+09 | 0.523946E+09 |
| February | 0.259234E+09 | 0.124802E+09 | 0.134432E+09 | 0.151938E+09 | 0.460430E+09 |
| March | 0.345370E+09 | 0.191615E+09 | 0.153754E+09 | 0.283594E+09 | 0.359492E+09 |
| April | 0.284212E+09 | 0.115333E+09 | 0.168880E+09 | 0.252017E+09 | 0.266714E+09 |
| May | 0.254148E+09 | 73678352.78 | 0.180470E+09 | 0.255857E+09 | 0.175711E+09 |
| June | 0.239847E+09 | 51367907.77 | 0.188479E+09 | 0.283737E+09 | 0.101838E+09 |
| July | 0.251477E+09 | 60403595.47 | 0.191073E+09 | 0.345948E+09 | 64828454.61 |
| August | 0.280704E+09 | 89301622.93 | 0.191402E+09 | 0.374045E+09 | 89892475.59 |
| September | 0.322545E+09 | 0.159080E+09 | 0.163465E+09 | 0.384680E+09 | 0.152164E+09 |
| October | 0.315906E+09 | 0.180810E+09 | 0.135096E+09 | 0.305399E+09 | 0.258924E+09 |
| November | 0.218979E+09 | 0.123963E+09 | 95015835.14 | 0.175433E+09 | 0.342306E+09 |
| December | 0.210527E+09 | 0.108976E+09 | 0.101551E+09 | 0.122153E+09 | 0.518731E+09 |
| Annual Sum or Average | 0.323408E+10 | 0.142564E+10 | 0.180844E+10 | 0.309402E+10 | 0.331498E+10 |
| Minimum of Months | 0.210527E+09 | 51367907.77 | 95015835.14 | 0.122153E+09 | 64828454.61 |
| Maximum of Months | 0.345370E+09 | 0.191615E+09 | 0.191402E+09 | 0.384680E+09 | 0.523946E+09 |
Report: WindowEnergyReportMonthly
For: W_EMPLOYEELOUNGEFLR1_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251133E+09 | 0.146314E+09 | 0.104819E+09 | 0.143801E+09 | 0.620707E+09 |
| February | 0.259234E+09 | 0.124802E+09 | 0.134432E+09 | 0.134107E+09 | 0.543159E+09 |
| March | 0.345370E+09 | 0.191615E+09 | 0.153754E+09 | 0.252137E+09 | 0.442941E+09 |
| April | 0.284212E+09 | 0.115333E+09 | 0.168880E+09 | 0.219502E+09 | 0.346759E+09 |
| May | 0.254148E+09 | 73678352.78 | 0.180470E+09 | 0.219230E+09 | 0.248340E+09 |
| June | 0.239847E+09 | 51367907.77 | 0.188479E+09 | 0.238848E+09 | 0.154252E+09 |
| July | 0.251477E+09 | 60403595.47 | 0.191073E+09 | 0.295517E+09 | 0.113978E+09 |
| August | 0.280704E+09 | 89301622.93 | 0.191402E+09 | 0.330164E+09 | 0.144977E+09 |
| September | 0.322545E+09 | 0.159080E+09 | 0.163465E+09 | 0.349603E+09 | 0.214600E+09 |
| October | 0.315906E+09 | 0.180810E+09 | 0.135096E+09 | 0.274185E+09 | 0.340362E+09 |
| November | 0.218979E+09 | 0.123963E+09 | 95015835.14 | 0.156805E+09 | 0.437224E+09 |
| December | 0.210527E+09 | 0.108976E+09 | 0.101551E+09 | 0.109633E+09 | 0.620572E+09 |
| Annual Sum or Average | 0.323408E+10 | 0.142564E+10 | 0.180844E+10 | 0.272353E+10 | 0.422787E+10 |
| Minimum of Months | 0.210527E+09 | 51367907.77 | 95015835.14 | 0.109633E+09 | 0.113978E+09 |
| Maximum of Months | 0.345370E+09 | 0.191615E+09 | 0.191402E+09 | 0.349603E+09 | 0.620707E+09 |
Report: WindowEnergyReportMonthly
For: W_LAUNDRYROOMFLR1_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251133E+09 | 0.146314E+09 | 0.104819E+09 | 53516952.55 | 0.130842E+10 |
| February | 0.259234E+09 | 0.124802E+09 | 0.134432E+09 | 46101952.09 | 0.116026E+10 |
| March | 0.345370E+09 | 0.191615E+09 | 0.153754E+09 | 94198944.91 | 0.106455E+10 |
| April | 0.284212E+09 | 0.115333E+09 | 0.168880E+09 | 55285495.82 | 0.935126E+09 |
| May | 0.254148E+09 | 73678352.78 | 0.180470E+09 | 30168428.03 | 0.850268E+09 |
| June | 0.239847E+09 | 51367907.77 | 0.188479E+09 | 15347482.83 | 0.697773E+09 |
| July | 0.251477E+09 | 60403595.47 | 0.191073E+09 | 33446004.31 | 0.649196E+09 |
| August | 0.280704E+09 | 89301622.93 | 0.191402E+09 | 66062790.80 | 0.682333E+09 |
| September | 0.322545E+09 | 0.159080E+09 | 0.163465E+09 | 0.115861E+09 | 0.765663E+09 |
| October | 0.315906E+09 | 0.180810E+09 | 0.135096E+09 | 0.103626E+09 | 0.969965E+09 |
| November | 0.218979E+09 | 0.123963E+09 | 95015835.14 | 54998984.05 | 0.110724E+10 |
| December | 0.210527E+09 | 0.108976E+09 | 0.101551E+09 | 43530404.69 | 0.133892E+10 |
| Annual Sum or Average | 0.323408E+10 | 0.142564E+10 | 0.180844E+10 | 0.712144E+09 | 0.115297E+11 |
| Minimum of Months | 0.210527E+09 | 51367907.77 | 95015835.14 | 15347482.83 | 0.649196E+09 |
| Maximum of Months | 0.345370E+09 | 0.191615E+09 | 0.191402E+09 | 0.115861E+09 | 0.133892E+10 |
Report: WindowEnergyReportMonthly
For: W_LAUNDRYROOMFLR1_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251133E+09 | 0.146314E+09 | 0.104819E+09 | 53516952.55 | 0.130842E+10 |
| February | 0.259234E+09 | 0.124802E+09 | 0.134432E+09 | 46101952.09 | 0.116026E+10 |
| March | 0.345370E+09 | 0.191615E+09 | 0.153754E+09 | 94198944.91 | 0.106455E+10 |
| April | 0.284212E+09 | 0.115333E+09 | 0.168880E+09 | 55285495.82 | 0.935126E+09 |
| May | 0.254148E+09 | 73678352.78 | 0.180470E+09 | 30168428.03 | 0.850268E+09 |
| June | 0.239847E+09 | 51367907.77 | 0.188479E+09 | 15347482.83 | 0.697773E+09 |
| July | 0.251477E+09 | 60403595.47 | 0.191073E+09 | 33446004.31 | 0.649196E+09 |
| August | 0.280704E+09 | 89301622.93 | 0.191402E+09 | 66062790.80 | 0.682333E+09 |
| September | 0.322545E+09 | 0.159080E+09 | 0.163465E+09 | 0.115861E+09 | 0.765663E+09 |
| October | 0.315906E+09 | 0.180810E+09 | 0.135096E+09 | 0.103626E+09 | 0.969965E+09 |
| November | 0.218979E+09 | 0.123963E+09 | 95015835.14 | 54998984.05 | 0.110724E+10 |
| December | 0.210527E+09 | 0.108976E+09 | 0.101551E+09 | 43530404.69 | 0.133892E+10 |
| Annual Sum or Average | 0.323408E+10 | 0.142564E+10 | 0.180844E+10 | 0.712144E+09 | 0.115297E+11 |
| Minimum of Months | 0.210527E+09 | 51367907.77 | 95015835.14 | 15347482.83 | 0.649196E+09 |
| Maximum of Months | 0.345370E+09 | 0.191615E+09 | 0.191402E+09 | 0.115861E+09 | 0.133892E+10 |
Report: WindowEnergyReportMonthly
For: W_LAUNDRYROOMFLR1_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251133E+09 | 0.146314E+09 | 0.104819E+09 | 53516952.55 | 0.130842E+10 |
| February | 0.259234E+09 | 0.124802E+09 | 0.134432E+09 | 46101952.09 | 0.116026E+10 |
| March | 0.345370E+09 | 0.191615E+09 | 0.153754E+09 | 94198944.91 | 0.106455E+10 |
| April | 0.284212E+09 | 0.115333E+09 | 0.168880E+09 | 55285495.82 | 0.935126E+09 |
| May | 0.254148E+09 | 73678352.78 | 0.180470E+09 | 30168428.03 | 0.850268E+09 |
| June | 0.239847E+09 | 51367907.77 | 0.188479E+09 | 15347482.83 | 0.697773E+09 |
| July | 0.251477E+09 | 60403595.47 | 0.191073E+09 | 33446004.31 | 0.649196E+09 |
| August | 0.280704E+09 | 89301622.93 | 0.191402E+09 | 66062790.80 | 0.682333E+09 |
| September | 0.322545E+09 | 0.159080E+09 | 0.163465E+09 | 0.115861E+09 | 0.765663E+09 |
| October | 0.315906E+09 | 0.180810E+09 | 0.135096E+09 | 0.103626E+09 | 0.969965E+09 |
| November | 0.218979E+09 | 0.123963E+09 | 95015835.14 | 54998984.05 | 0.110724E+10 |
| December | 0.210527E+09 | 0.108976E+09 | 0.101551E+09 | 43530404.69 | 0.133892E+10 |
| Annual Sum or Average | 0.323408E+10 | 0.142564E+10 | 0.180844E+10 | 0.712144E+09 | 0.115297E+11 |
| Minimum of Months | 0.210527E+09 | 51367907.77 | 95015835.14 | 15347482.83 | 0.649196E+09 |
| Maximum of Months | 0.345370E+09 | 0.191615E+09 | 0.191402E+09 | 0.115861E+09 | 0.133892E+10 |
Report: WindowEnergyReportMonthly
For: W_EXERCISECENTERFLR1_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251133E+09 | 0.146314E+09 | 0.104819E+09 | 0.165114E+09 | 0.503406E+09 |
| February | 0.259234E+09 | 0.124802E+09 | 0.134432E+09 | 0.158912E+09 | 0.443783E+09 |
| March | 0.345370E+09 | 0.191615E+09 | 0.153754E+09 | 0.291450E+09 | 0.352355E+09 |
| April | 0.284212E+09 | 0.115333E+09 | 0.168880E+09 | 0.255798E+09 | 0.266151E+09 |
| May | 0.254148E+09 | 73678352.78 | 0.180470E+09 | 0.257298E+09 | 0.180723E+09 |
| June | 0.239847E+09 | 51367907.77 | 0.188479E+09 | 0.285076E+09 | 0.107215E+09 |
| July | 0.251477E+09 | 60403595.47 | 0.191073E+09 | 0.346161E+09 | 72195166.10 |
| August | 0.280704E+09 | 89301622.93 | 0.191402E+09 | 0.375197E+09 | 97276647.17 |
| September | 0.322545E+09 | 0.159080E+09 | 0.163465E+09 | 0.386384E+09 | 0.157634E+09 |
| October | 0.315906E+09 | 0.180810E+09 | 0.135096E+09 | 0.306971E+09 | 0.264370E+09 |
| November | 0.218979E+09 | 0.123963E+09 | 95015835.14 | 0.177930E+09 | 0.339762E+09 |
| December | 0.210527E+09 | 0.108976E+09 | 0.101551E+09 | 0.126995E+09 | 0.498420E+09 |
| Annual Sum or Average | 0.323408E+10 | 0.142564E+10 | 0.180844E+10 | 0.313329E+10 | 0.328329E+10 |
| Minimum of Months | 0.210527E+09 | 51367907.77 | 95015835.14 | 0.126995E+09 | 72195166.10 |
| Maximum of Months | 0.345370E+09 | 0.191615E+09 | 0.191402E+09 | 0.386384E+09 | 0.503406E+09 |
Report: WindowEnergyReportMonthly
For: W_FRONTOFFICEFLR1_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251133E+09 | 0.146314E+09 | 0.104819E+09 | 0.169574E+09 | 0.485579E+09 |
| February | 0.259234E+09 | 0.124802E+09 | 0.134432E+09 | 0.165222E+09 | 0.426850E+09 |
| March | 0.345370E+09 | 0.191615E+09 | 0.153754E+09 | 0.297314E+09 | 0.343767E+09 |
| April | 0.284212E+09 | 0.115333E+09 | 0.168880E+09 | 0.261044E+09 | 0.261885E+09 |
| May | 0.254148E+09 | 73678352.78 | 0.180470E+09 | 0.262352E+09 | 0.181009E+09 |
| June | 0.239847E+09 | 51367907.77 | 0.188479E+09 | 0.288869E+09 | 0.106586E+09 |
| July | 0.251477E+09 | 60403595.47 | 0.191073E+09 | 0.348617E+09 | 70724744.67 |
| August | 0.280704E+09 | 89301622.93 | 0.191402E+09 | 0.377922E+09 | 96560227.04 |
| September | 0.322545E+09 | 0.159080E+09 | 0.163465E+09 | 0.389554E+09 | 0.158834E+09 |
| October | 0.315906E+09 | 0.180810E+09 | 0.135096E+09 | 0.310589E+09 | 0.266200E+09 |
| November | 0.218979E+09 | 0.123963E+09 | 95015835.14 | 0.180475E+09 | 0.337862E+09 |
| December | 0.210527E+09 | 0.108976E+09 | 0.101551E+09 | 0.131046E+09 | 0.480942E+09 |
| Annual Sum or Average | 0.323408E+10 | 0.142564E+10 | 0.180844E+10 | 0.318258E+10 | 0.321680E+10 |
| Minimum of Months | 0.210527E+09 | 51367907.77 | 95015835.14 | 0.131046E+09 | 70724744.67 |
| Maximum of Months | 0.345370E+09 | 0.191615E+09 | 0.191402E+09 | 0.389554E+09 | 0.485579E+09 |
Report: WindowEnergyReportMonthly
For: W_FRONTOFFICEFLR1_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251133E+09 | 0.146314E+09 | 0.104819E+09 | 0.169574E+09 | 0.485579E+09 |
| February | 0.259234E+09 | 0.124802E+09 | 0.134432E+09 | 0.165222E+09 | 0.426850E+09 |
| March | 0.345370E+09 | 0.191615E+09 | 0.153754E+09 | 0.297314E+09 | 0.343767E+09 |
| April | 0.284212E+09 | 0.115333E+09 | 0.168880E+09 | 0.261044E+09 | 0.261885E+09 |
| May | 0.254148E+09 | 73678352.78 | 0.180470E+09 | 0.262352E+09 | 0.181009E+09 |
| June | 0.239847E+09 | 51367907.77 | 0.188479E+09 | 0.288869E+09 | 0.106586E+09 |
| July | 0.251477E+09 | 60403595.47 | 0.191073E+09 | 0.348617E+09 | 70724744.67 |
| August | 0.280704E+09 | 89301622.93 | 0.191402E+09 | 0.377922E+09 | 96560227.04 |
| September | 0.322545E+09 | 0.159080E+09 | 0.163465E+09 | 0.389554E+09 | 0.158834E+09 |
| October | 0.315906E+09 | 0.180810E+09 | 0.135096E+09 | 0.310589E+09 | 0.266200E+09 |
| November | 0.218979E+09 | 0.123963E+09 | 95015835.14 | 0.180475E+09 | 0.337862E+09 |
| December | 0.210527E+09 | 0.108976E+09 | 0.101551E+09 | 0.131046E+09 | 0.480942E+09 |
| Annual Sum or Average | 0.323408E+10 | 0.142564E+10 | 0.180844E+10 | 0.318258E+10 | 0.321680E+10 |
| Minimum of Months | 0.210527E+09 | 51367907.77 | 95015835.14 | 0.131046E+09 | 70724744.67 |
| Maximum of Months | 0.345370E+09 | 0.191615E+09 | 0.191402E+09 | 0.389554E+09 | 0.485579E+09 |
Report: WindowEnergyReportMonthly
For: W_FRONTOFFICEFLR1_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251133E+09 | 0.146314E+09 | 0.104819E+09 | 0.169574E+09 | 0.485579E+09 |
| February | 0.259234E+09 | 0.124802E+09 | 0.134432E+09 | 0.165222E+09 | 0.426850E+09 |
| March | 0.345370E+09 | 0.191615E+09 | 0.153754E+09 | 0.297314E+09 | 0.343767E+09 |
| April | 0.284212E+09 | 0.115333E+09 | 0.168880E+09 | 0.261044E+09 | 0.261885E+09 |
| May | 0.254148E+09 | 73678352.78 | 0.180470E+09 | 0.262352E+09 | 0.181009E+09 |
| June | 0.239847E+09 | 51367907.77 | 0.188479E+09 | 0.288869E+09 | 0.106586E+09 |
| July | 0.251477E+09 | 60403595.47 | 0.191073E+09 | 0.348617E+09 | 70724744.67 |
| August | 0.280704E+09 | 89301622.93 | 0.191402E+09 | 0.377922E+09 | 96560227.04 |
| September | 0.322545E+09 | 0.159080E+09 | 0.163465E+09 | 0.389554E+09 | 0.158834E+09 |
| October | 0.315906E+09 | 0.180810E+09 | 0.135096E+09 | 0.310589E+09 | 0.266200E+09 |
| November | 0.218979E+09 | 0.123963E+09 | 95015835.14 | 0.180475E+09 | 0.337862E+09 |
| December | 0.210527E+09 | 0.108976E+09 | 0.101551E+09 | 0.131046E+09 | 0.480942E+09 |
| Annual Sum or Average | 0.323408E+10 | 0.142564E+10 | 0.180844E+10 | 0.318258E+10 | 0.321680E+10 |
| Minimum of Months | 0.210527E+09 | 51367907.77 | 95015835.14 | 0.131046E+09 | 70724744.67 |
| Maximum of Months | 0.345370E+09 | 0.191615E+09 | 0.191402E+09 | 0.389554E+09 | 0.485579E+09 |
Report: WindowEnergyReportMonthly
For: W_FRONTOFFICEFLR1_3_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251133E+09 | 0.146314E+09 | 0.104819E+09 | 0.169574E+09 | 0.485579E+09 |
| February | 0.259234E+09 | 0.124802E+09 | 0.134432E+09 | 0.165222E+09 | 0.426850E+09 |
| March | 0.345370E+09 | 0.191615E+09 | 0.153754E+09 | 0.297314E+09 | 0.343767E+09 |
| April | 0.284212E+09 | 0.115333E+09 | 0.168880E+09 | 0.261044E+09 | 0.261885E+09 |
| May | 0.254148E+09 | 73678352.78 | 0.180470E+09 | 0.262352E+09 | 0.181009E+09 |
| June | 0.239847E+09 | 51367907.77 | 0.188479E+09 | 0.288869E+09 | 0.106586E+09 |
| July | 0.251477E+09 | 60403595.47 | 0.191073E+09 | 0.348617E+09 | 70724744.67 |
| August | 0.280704E+09 | 89301622.93 | 0.191402E+09 | 0.377922E+09 | 96560227.04 |
| September | 0.322545E+09 | 0.159080E+09 | 0.163465E+09 | 0.389554E+09 | 0.158834E+09 |
| October | 0.315906E+09 | 0.180810E+09 | 0.135096E+09 | 0.310589E+09 | 0.266200E+09 |
| November | 0.218979E+09 | 0.123963E+09 | 95015835.14 | 0.180475E+09 | 0.337862E+09 |
| December | 0.210527E+09 | 0.108976E+09 | 0.101551E+09 | 0.131046E+09 | 0.480942E+09 |
| Annual Sum or Average | 0.323408E+10 | 0.142564E+10 | 0.180844E+10 | 0.318258E+10 | 0.321680E+10 |
| Minimum of Months | 0.210527E+09 | 51367907.77 | 95015835.14 | 0.131046E+09 | 70724744.67 |
| Maximum of Months | 0.345370E+09 | 0.191615E+09 | 0.191402E+09 | 0.389554E+09 | 0.485579E+09 |
Report: WindowEnergyReportMonthly
For: W_CORRIDORFLR2_2_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 31814299.38 | 7492682.50 | 24321616.88 | 4512490.39 | 0.212307E+09 |
| February | 46561134.82 | 12016558.24 | 34544576.58 | 11402971.02 | 0.181973E+09 |
| March | 81038794.01 | 34836904.83 | 46201889.18 | 48979049.72 | 0.140104E+09 |
| April | 95400584.78 | 39046730.28 | 56353854.50 | 72853994.56 | 0.100891E+09 |
| May | 0.116379E+09 | 52550318.09 | 63828365.87 | 0.112579E+09 | 68624411.05 |
| June | 0.136068E+09 | 64015190.35 | 72052700.43 | 0.156822E+09 | 40654822.00 |
| July | 0.125557E+09 | 54971331.13 | 70585625.93 | 0.159801E+09 | 27603828.85 |
| August | 0.113435E+09 | 48108738.80 | 65326739.18 | 0.140743E+09 | 36511562.41 |
| September | 86437478.29 | 37347850.17 | 49089628.12 | 90059446.15 | 59570449.48 |
| October | 57878309.33 | 20387860.69 | 37490448.63 | 37987372.19 | 0.106052E+09 |
| November | 32920955.27 | 9345891.71 | 23575063.57 | 12590901.08 | 0.136128E+09 |
| December | 29676342.99 | 6430188.24 | 23246154.75 | 4054689.61 | 0.204352E+09 |
| Annual Sum or Average | 0.953167E+09 | 0.386550E+09 | 0.566617E+09 | 0.852386E+09 | 0.131477E+10 |
| Minimum of Months | 29676342.99 | 6430188.24 | 23246154.75 | 4054689.61 | 27603828.85 |
| Maximum of Months | 0.136068E+09 | 64015190.35 | 72052700.43 | 0.159801E+09 | 0.212307E+09 |
Report: WindowEnergyReportMonthly
For: W_CORRIDORFLR2_15_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 37098023.40 | 12043509.91 | 25054513.49 | 7467197.23 | 0.200958E+09 |
| February | 48931354.12 | 14616069.33 | 34315284.79 | 13739189.77 | 0.173662E+09 |
| March | 78036018.86 | 32624659.66 | 45411359.20 | 45814108.26 | 0.137137E+09 |
| April | 99745595.56 | 44091871.74 | 55653723.81 | 76228294.29 | 95654032.54 |
| May | 0.115457E+09 | 51037941.57 | 64418752.04 | 0.110856E+09 | 64889597.45 |
| June | 0.124900E+09 | 55206349.60 | 69693194.00 | 0.141992E+09 | 37947932.21 |
| July | 0.123778E+09 | 54411133.48 | 69367020.76 | 0.157246E+09 | 25526818.10 |
| August | 0.111750E+09 | 46773193.73 | 64976390.42 | 0.136271E+09 | 35080092.01 |
| September | 89772857.57 | 39667690.25 | 50105167.32 | 93663564.61 | 57167334.26 |
| October | 63027240.95 | 25973124.56 | 37054116.39 | 43455678.46 | 0.100973E+09 |
| November | 34636493.95 | 11083346.69 | 23553147.25 | 13934038.79 | 0.132414E+09 |
| December | 28845438.38 | 5970833.92 | 22874604.46 | 3129583.57 | 0.199774E+09 |
| Annual Sum or Average | 0.955977E+09 | 0.393500E+09 | 0.562477E+09 | 0.843796E+09 | 0.126118E+10 |
| Minimum of Months | 28845438.38 | 5970833.92 | 22874604.46 | 3129583.57 | 25526818.10 |
| Maximum of Months | 0.124900E+09 | 55206349.60 | 69693194.00 | 0.157246E+09 | 0.200958E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM201_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58753532.56 | 0.00 | 58753532.56 | 0.00 | 0.487580E+09 |
| February | 80855278.93 | 0.00 | 80855278.93 | 900586.10 | 0.415247E+09 |
| March | 0.108578E+09 | 3845.32 | 0.108574E+09 | 24327787.74 | 0.333065E+09 |
| April | 0.133955E+09 | 645866.30 | 0.133309E+09 | 53095467.93 | 0.231001E+09 |
| May | 0.160799E+09 | 6923861.27 | 0.153875E+09 | 0.101679E+09 | 0.155645E+09 |
| June | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.171221E+09 | 0.100139E+09 |
| July | 0.180053E+09 | 12248317.48 | 0.167805E+09 | 0.200129E+09 | 73181670.10 |
| August | 0.155885E+09 | 3009257.61 | 0.152875E+09 | 0.161971E+09 | 98862190.21 |
| September | 0.114336E+09 | 50599.27 | 0.114285E+09 | 85511152.98 | 0.152564E+09 |
| October | 88278106.39 | 0.00 | 88278106.39 | 28811397.84 | 0.244348E+09 |
| November | 57407130.60 | 0.00 | 57407130.60 | 7240949.03 | 0.300687E+09 |
| December | 54991543.41 | 0.00 | 54991543.41 | 251070.09 | 0.461773E+09 |
| Annual Sum or Average | 0.138098E+10 | 38790227.12 | 0.134219E+10 | 0.835139E+09 | 0.305409E+10 |
| Minimum of Months | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 73181670.10 |
| Maximum of Months | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.200129E+09 | 0.487580E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM202_205_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58753532.56 | 0.00 | 58753532.56 | 0.00 | 0.553943E+09 |
| February | 80855278.93 | 0.00 | 80855278.93 | 410722.53 | 0.475203E+09 |
| March | 0.108578E+09 | 3845.32 | 0.108574E+09 | 22016706.31 | 0.369804E+09 |
| April | 0.133955E+09 | 645866.30 | 0.133309E+09 | 49972761.25 | 0.242946E+09 |
| May | 0.160799E+09 | 6923861.27 | 0.153875E+09 | 0.105306E+09 | 0.149519E+09 |
| June | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.187872E+09 | 87118074.68 |
| July | 0.180053E+09 | 12248317.48 | 0.167805E+09 | 0.225793E+09 | 56633360.94 |
| August | 0.155885E+09 | 3009257.61 | 0.152875E+09 | 0.180113E+09 | 80485888.03 |
| September | 0.114336E+09 | 50599.27 | 0.114285E+09 | 91760553.02 | 0.141219E+09 |
| October | 88278106.39 | 0.00 | 88278106.39 | 27168772.48 | 0.251055E+09 |
| November | 57407130.60 | 0.00 | 57407130.60 | 6042903.18 | 0.327884E+09 |
| December | 54991543.41 | 0.00 | 54991543.41 | 140400.71 | 0.524441E+09 |
| Annual Sum or Average | 0.138098E+10 | 38790227.12 | 0.134219E+10 | 0.896597E+09 | 0.326025E+10 |
| Minimum of Months | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 56633360.94 |
| Maximum of Months | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.225793E+09 | 0.553943E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM202_205_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58753532.56 | 0.00 | 58753532.56 | 0.00 | 0.553943E+09 |
| February | 80855278.93 | 0.00 | 80855278.93 | 410722.53 | 0.475203E+09 |
| March | 0.108578E+09 | 3845.32 | 0.108574E+09 | 22016706.31 | 0.369804E+09 |
| April | 0.133955E+09 | 645866.30 | 0.133309E+09 | 49972761.25 | 0.242946E+09 |
| May | 0.160799E+09 | 6923861.27 | 0.153875E+09 | 0.105306E+09 | 0.149519E+09 |
| June | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.187872E+09 | 87118074.68 |
| July | 0.180053E+09 | 12248317.48 | 0.167805E+09 | 0.225793E+09 | 56633360.94 |
| August | 0.155885E+09 | 3009257.61 | 0.152875E+09 | 0.180113E+09 | 80485888.03 |
| September | 0.114336E+09 | 50599.27 | 0.114285E+09 | 91760553.02 | 0.141219E+09 |
| October | 88278106.39 | 0.00 | 88278106.39 | 27168772.48 | 0.251055E+09 |
| November | 57407130.60 | 0.00 | 57407130.60 | 6042903.18 | 0.327884E+09 |
| December | 54991543.41 | 0.00 | 54991543.41 | 140400.71 | 0.524441E+09 |
| Annual Sum or Average | 0.138098E+10 | 38790227.12 | 0.134219E+10 | 0.896597E+09 | 0.326025E+10 |
| Minimum of Months | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 56633360.94 |
| Maximum of Months | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.225793E+09 | 0.553943E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM202_205_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58753532.56 | 0.00 | 58753532.56 | 0.00 | 0.553943E+09 |
| February | 80855278.93 | 0.00 | 80855278.93 | 410722.53 | 0.475203E+09 |
| March | 0.108578E+09 | 3845.32 | 0.108574E+09 | 22016706.31 | 0.369804E+09 |
| April | 0.133955E+09 | 645866.30 | 0.133309E+09 | 49972761.25 | 0.242946E+09 |
| May | 0.160799E+09 | 6923861.27 | 0.153875E+09 | 0.105306E+09 | 0.149519E+09 |
| June | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.187872E+09 | 87118074.68 |
| July | 0.180053E+09 | 12248317.48 | 0.167805E+09 | 0.225793E+09 | 56633360.94 |
| August | 0.155885E+09 | 3009257.61 | 0.152875E+09 | 0.180113E+09 | 80485888.03 |
| September | 0.114336E+09 | 50599.27 | 0.114285E+09 | 91760553.02 | 0.141219E+09 |
| October | 88278106.39 | 0.00 | 88278106.39 | 27168772.48 | 0.251055E+09 |
| November | 57407130.60 | 0.00 | 57407130.60 | 6042903.18 | 0.327884E+09 |
| December | 54991543.41 | 0.00 | 54991543.41 | 140400.71 | 0.524441E+09 |
| Annual Sum or Average | 0.138098E+10 | 38790227.12 | 0.134219E+10 | 0.896597E+09 | 0.326025E+10 |
| Minimum of Months | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 56633360.94 |
| Maximum of Months | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.225793E+09 | 0.553943E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM202_205_5_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58753532.56 | 0.00 | 58753532.56 | 0.00 | 0.553943E+09 |
| February | 80855278.93 | 0.00 | 80855278.93 | 410722.53 | 0.475203E+09 |
| March | 0.108578E+09 | 3845.32 | 0.108574E+09 | 22016706.31 | 0.369804E+09 |
| April | 0.133955E+09 | 645866.30 | 0.133309E+09 | 49972761.25 | 0.242946E+09 |
| May | 0.160799E+09 | 6923861.27 | 0.153875E+09 | 0.105306E+09 | 0.149519E+09 |
| June | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.187872E+09 | 87118074.68 |
| July | 0.180053E+09 | 12248317.48 | 0.167805E+09 | 0.225793E+09 | 56633360.94 |
| August | 0.155885E+09 | 3009257.61 | 0.152875E+09 | 0.180113E+09 | 80485888.03 |
| September | 0.114336E+09 | 50599.27 | 0.114285E+09 | 91760553.02 | 0.141219E+09 |
| October | 88278106.39 | 0.00 | 88278106.39 | 27168772.48 | 0.251055E+09 |
| November | 57407130.60 | 0.00 | 57407130.60 | 6042903.18 | 0.327884E+09 |
| December | 54991543.41 | 0.00 | 54991543.41 | 140400.71 | 0.524441E+09 |
| Annual Sum or Average | 0.138098E+10 | 38790227.12 | 0.134219E+10 | 0.896597E+09 | 0.326025E+10 |
| Minimum of Months | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 56633360.94 |
| Maximum of Months | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.225793E+09 | 0.553943E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM206_208_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58753532.56 | 0.00 | 58753532.56 | 0.00 | 0.567170E+09 |
| February | 80855278.93 | 0.00 | 80855278.93 | 325637.55 | 0.486516E+09 |
| March | 0.108578E+09 | 3845.32 | 0.108574E+09 | 20837613.64 | 0.380211E+09 |
| April | 0.133955E+09 | 645866.30 | 0.133309E+09 | 47595906.99 | 0.249436E+09 |
| May | 0.160799E+09 | 6923861.27 | 0.153875E+09 | 0.103772E+09 | 0.152005E+09 |
| June | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.188308E+09 | 87168856.67 |
| July | 0.180053E+09 | 12248317.48 | 0.167805E+09 | 0.227367E+09 | 55993520.14 |
| August | 0.155885E+09 | 3009257.61 | 0.152875E+09 | 0.181269E+09 | 79943868.87 |
| September | 0.114336E+09 | 50599.27 | 0.114285E+09 | 91654134.14 | 0.142234E+09 |
| October | 88278106.39 | 0.00 | 88278106.39 | 25875046.79 | 0.257019E+09 |
| November | 57407130.60 | 0.00 | 57407130.60 | 5519740.85 | 0.337909E+09 |
| December | 54991543.41 | 0.00 | 54991543.41 | 115645.50 | 0.537006E+09 |
| Annual Sum or Average | 0.138098E+10 | 38790227.12 | 0.134219E+10 | 0.892640E+09 | 0.333261E+10 |
| Minimum of Months | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 55993520.14 |
| Maximum of Months | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.227367E+09 | 0.567170E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM206_208_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 52527386.44 | 0.00 | 52527386.44 | 0.00 | 0.513567E+09 |
| February | 72286996.52 | 0.00 | 72286996.52 | 280072.02 | 0.440823E+09 |
| March | 97071729.42 | 3437.84 | 97068291.58 | 18521570.53 | 0.344167E+09 |
| April | 0.119760E+09 | 577424.35 | 0.119182E+09 | 42276978.86 | 0.225295E+09 |
| May | 0.143759E+09 | 6190145.07 | 0.137569E+09 | 92693988.94 | 0.136868E+09 |
| June | 0.167264E+09 | 14222670.61 | 0.153042E+09 | 0.168772E+09 | 78211015.23 |
| July | 0.160972E+09 | 10950372.80 | 0.150022E+09 | 0.204175E+09 | 50069271.50 |
| August | 0.139365E+09 | 2690368.92 | 0.136675E+09 | 0.162684E+09 | 71626373.10 |
| September | 0.102220E+09 | 45237.30 | 0.102174E+09 | 82039471.13 | 0.127912E+09 |
| October | 78923207.87 | 0.00 | 78923207.87 | 22972374.33 | 0.231902E+09 |
| November | 51323663.93 | 0.00 | 51323663.93 | 4892598.57 | 0.305332E+09 |
| December | 49164062.15 | 0.00 | 49164062.15 | 101086.99 | 0.486092E+09 |
| Annual Sum or Average | 0.123464E+10 | 34679656.89 | 0.119996E+10 | 0.799410E+09 | 0.301186E+10 |
| Minimum of Months | 49164062.15 | 0.00 | 49164062.15 | 0.00 | 50069271.50 |
| Maximum of Months | 0.167264E+09 | 14222670.61 | 0.153042E+09 | 0.204175E+09 | 0.513567E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM206_208_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58753532.56 | 0.00 | 58753532.56 | 0.00 | 0.567170E+09 |
| February | 80855278.93 | 0.00 | 80855278.93 | 325637.55 | 0.486516E+09 |
| March | 0.108578E+09 | 3845.32 | 0.108574E+09 | 20837613.64 | 0.380211E+09 |
| April | 0.133955E+09 | 645866.30 | 0.133309E+09 | 47595906.99 | 0.249436E+09 |
| May | 0.160799E+09 | 6923861.27 | 0.153875E+09 | 0.103772E+09 | 0.152005E+09 |
| June | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.188308E+09 | 87168856.67 |
| July | 0.180053E+09 | 12248317.48 | 0.167805E+09 | 0.227367E+09 | 55993520.14 |
| August | 0.155885E+09 | 3009257.61 | 0.152875E+09 | 0.181269E+09 | 79943868.87 |
| September | 0.114336E+09 | 50599.27 | 0.114285E+09 | 91654134.14 | 0.142234E+09 |
| October | 88278106.39 | 0.00 | 88278106.39 | 25875046.79 | 0.257019E+09 |
| November | 57407130.60 | 0.00 | 57407130.60 | 5519740.85 | 0.337909E+09 |
| December | 54991543.41 | 0.00 | 54991543.41 | 115645.50 | 0.537006E+09 |
| Annual Sum or Average | 0.138098E+10 | 38790227.12 | 0.134219E+10 | 0.892640E+09 | 0.333261E+10 |
| Minimum of Months | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 55993520.14 |
| Maximum of Months | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.227367E+09 | 0.567170E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM209_212_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58753532.56 | 0.00 | 58753532.56 | 0.00 | 0.570046E+09 |
| February | 80855278.93 | 0.00 | 80855278.93 | 293213.33 | 0.488603E+09 |
| March | 0.108578E+09 | 3845.32 | 0.108574E+09 | 20738201.24 | 0.381399E+09 |
| April | 0.133955E+09 | 645866.30 | 0.133309E+09 | 47508467.90 | 0.249441E+09 |
| May | 0.160799E+09 | 6923861.27 | 0.153875E+09 | 0.105050E+09 | 0.150403E+09 |
| June | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.190779E+09 | 85555504.91 |
| July | 0.180053E+09 | 12248317.48 | 0.167805E+09 | 0.230370E+09 | 54328879.00 |
| August | 0.155885E+09 | 3009257.61 | 0.152875E+09 | 0.183290E+09 | 78232993.60 |
| September | 0.114336E+09 | 50599.27 | 0.114285E+09 | 92115750.89 | 0.141646E+09 |
| October | 88278106.39 | 0.00 | 88278106.39 | 25365827.56 | 0.258857E+09 |
| November | 57407130.60 | 0.00 | 57407130.60 | 5247556.58 | 0.341843E+09 |
| December | 54991543.41 | 0.00 | 54991543.41 | 97009.61 | 0.540787E+09 |
| Annual Sum or Average | 0.138098E+10 | 38790227.12 | 0.134219E+10 | 0.900854E+09 | 0.334114E+10 |
| Minimum of Months | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 54328879.00 |
| Maximum of Months | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.230370E+09 | 0.570046E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM209_212_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58753532.56 | 0.00 | 58753532.56 | 0.00 | 0.570046E+09 |
| February | 80855278.93 | 0.00 | 80855278.93 | 293213.33 | 0.488603E+09 |
| March | 0.108578E+09 | 3845.32 | 0.108574E+09 | 20738201.24 | 0.381399E+09 |
| April | 0.133955E+09 | 645866.30 | 0.133309E+09 | 47508467.90 | 0.249441E+09 |
| May | 0.160799E+09 | 6923861.27 | 0.153875E+09 | 0.105050E+09 | 0.150403E+09 |
| June | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.190779E+09 | 85555504.91 |
| July | 0.180053E+09 | 12248317.48 | 0.167805E+09 | 0.230370E+09 | 54328879.00 |
| August | 0.155885E+09 | 3009257.61 | 0.152875E+09 | 0.183290E+09 | 78232993.60 |
| September | 0.114336E+09 | 50599.27 | 0.114285E+09 | 92115750.89 | 0.141646E+09 |
| October | 88278106.39 | 0.00 | 88278106.39 | 25365827.56 | 0.258857E+09 |
| November | 57407130.60 | 0.00 | 57407130.60 | 5247556.58 | 0.341843E+09 |
| December | 54991543.41 | 0.00 | 54991543.41 | 97009.61 | 0.540787E+09 |
| Annual Sum or Average | 0.138098E+10 | 38790227.12 | 0.134219E+10 | 0.900854E+09 | 0.334114E+10 |
| Minimum of Months | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 54328879.00 |
| Maximum of Months | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.230370E+09 | 0.570046E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM209_212_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58753532.56 | 0.00 | 58753532.56 | 0.00 | 0.570046E+09 |
| February | 80855278.93 | 0.00 | 80855278.93 | 293213.33 | 0.488603E+09 |
| March | 0.108578E+09 | 3845.32 | 0.108574E+09 | 20738201.24 | 0.381399E+09 |
| April | 0.133955E+09 | 645866.30 | 0.133309E+09 | 47508467.90 | 0.249441E+09 |
| May | 0.160799E+09 | 6923861.27 | 0.153875E+09 | 0.105050E+09 | 0.150403E+09 |
| June | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.190779E+09 | 85555504.91 |
| July | 0.180053E+09 | 12248317.48 | 0.167805E+09 | 0.230370E+09 | 54328879.00 |
| August | 0.155885E+09 | 3009257.61 | 0.152875E+09 | 0.183290E+09 | 78232993.60 |
| September | 0.114336E+09 | 50599.27 | 0.114285E+09 | 92115750.89 | 0.141646E+09 |
| October | 88278106.39 | 0.00 | 88278106.39 | 25365827.56 | 0.258857E+09 |
| November | 57407130.60 | 0.00 | 57407130.60 | 5247556.58 | 0.341843E+09 |
| December | 54991543.41 | 0.00 | 54991543.41 | 97009.61 | 0.540787E+09 |
| Annual Sum or Average | 0.138098E+10 | 38790227.12 | 0.134219E+10 | 0.900854E+09 | 0.334114E+10 |
| Minimum of Months | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 54328879.00 |
| Maximum of Months | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.230370E+09 | 0.570046E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM209_212_5_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58753532.56 | 0.00 | 58753532.56 | 0.00 | 0.570046E+09 |
| February | 80855278.93 | 0.00 | 80855278.93 | 293213.33 | 0.488603E+09 |
| March | 0.108578E+09 | 3845.32 | 0.108574E+09 | 20738201.24 | 0.381399E+09 |
| April | 0.133955E+09 | 645866.30 | 0.133309E+09 | 47508467.90 | 0.249441E+09 |
| May | 0.160799E+09 | 6923861.27 | 0.153875E+09 | 0.105050E+09 | 0.150403E+09 |
| June | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.190779E+09 | 85555504.91 |
| July | 0.180053E+09 | 12248317.48 | 0.167805E+09 | 0.230370E+09 | 54328879.00 |
| August | 0.155885E+09 | 3009257.61 | 0.152875E+09 | 0.183290E+09 | 78232993.60 |
| September | 0.114336E+09 | 50599.27 | 0.114285E+09 | 92115750.89 | 0.141646E+09 |
| October | 88278106.39 | 0.00 | 88278106.39 | 25365827.56 | 0.258857E+09 |
| November | 57407130.60 | 0.00 | 57407130.60 | 5247556.58 | 0.341843E+09 |
| December | 54991543.41 | 0.00 | 54991543.41 | 97009.61 | 0.540787E+09 |
| Annual Sum or Average | 0.138098E+10 | 38790227.12 | 0.134219E+10 | 0.900854E+09 | 0.334114E+10 |
| Minimum of Months | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 54328879.00 |
| Maximum of Months | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.230370E+09 | 0.570046E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM213_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58753532.56 | 0.00 | 58753532.56 | 0.00 | 0.544416E+09 |
| February | 80855278.93 | 0.00 | 80855278.93 | 625853.71 | 0.464793E+09 |
| March | 0.108578E+09 | 3845.32 | 0.108574E+09 | 24211894.39 | 0.360679E+09 |
| April | 0.133955E+09 | 645866.30 | 0.133309E+09 | 54844956.86 | 0.235769E+09 |
| May | 0.160799E+09 | 6923861.27 | 0.153875E+09 | 0.111246E+09 | 0.143390E+09 |
| June | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.194499E+09 | 82331850.55 |
| July | 0.180053E+09 | 12248317.48 | 0.167805E+09 | 0.232228E+09 | 52501390.88 |
| August | 0.155885E+09 | 3009257.61 | 0.152875E+09 | 0.185351E+09 | 75841903.52 |
| September | 0.114336E+09 | 50599.27 | 0.114285E+09 | 95412279.42 | 0.135776E+09 |
| October | 88278106.39 | 0.00 | 88278106.39 | 29687259.15 | 0.245368E+09 |
| November | 57407130.60 | 0.00 | 57407130.60 | 6814015.81 | 0.319932E+09 |
| December | 54991543.41 | 0.00 | 54991543.41 | 197152.68 | 0.513868E+09 |
| Annual Sum or Average | 0.138098E+10 | 38790227.12 | 0.134219E+10 | 0.935117E+09 | 0.317467E+10 |
| Minimum of Months | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 52501390.88 |
| Maximum of Months | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.232228E+09 | 0.544416E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM214_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251946E+09 | 0.146788E+09 | 0.105158E+09 | 0.165209E+09 | 0.492482E+09 |
| February | 0.260073E+09 | 0.125206E+09 | 0.134867E+09 | 0.159702E+09 | 0.434154E+09 |
| March | 0.346487E+09 | 0.192235E+09 | 0.154252E+09 | 0.290265E+09 | 0.344471E+09 |
| April | 0.285132E+09 | 0.115706E+09 | 0.169426E+09 | 0.256762E+09 | 0.256757E+09 |
| May | 0.254971E+09 | 73916805.40 | 0.181054E+09 | 0.258843E+09 | 0.170710E+09 |
| June | 0.240623E+09 | 51534154.87 | 0.189089E+09 | 0.286243E+09 | 99697433.82 |
| July | 0.252290E+09 | 60599085.67 | 0.191691E+09 | 0.348151E+09 | 63335000.16 |
| August | 0.281612E+09 | 89590638.70 | 0.192022E+09 | 0.376718E+09 | 87021153.41 |
| September | 0.323589E+09 | 0.159595E+09 | 0.163994E+09 | 0.387988E+09 | 0.146091E+09 |
| October | 0.316929E+09 | 0.181395E+09 | 0.135534E+09 | 0.310075E+09 | 0.246684E+09 |
| November | 0.219687E+09 | 0.124364E+09 | 95323344.21 | 0.179555E+09 | 0.322626E+09 |
| December | 0.211208E+09 | 0.109328E+09 | 0.101880E+09 | 0.127494E+09 | 0.484747E+09 |
| Annual Sum or Average | 0.324455E+10 | 0.143026E+10 | 0.181429E+10 | 0.314700E+10 | 0.314878E+10 |
| Minimum of Months | 0.211208E+09 | 51534154.87 | 95323344.21 | 0.127494E+09 | 63335000.16 |
| Maximum of Months | 0.346487E+09 | 0.192235E+09 | 0.192022E+09 | 0.387988E+09 | 0.492482E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM215_218_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251946E+09 | 0.146788E+09 | 0.105158E+09 | 0.142774E+09 | 0.642960E+09 |
| February | 0.260073E+09 | 0.125206E+09 | 0.134867E+09 | 0.132898E+09 | 0.565480E+09 |
| March | 0.346487E+09 | 0.192235E+09 | 0.154252E+09 | 0.249531E+09 | 0.464654E+09 |
| April | 0.285132E+09 | 0.115706E+09 | 0.169426E+09 | 0.216911E+09 | 0.366049E+09 |
| May | 0.254971E+09 | 73916805.40 | 0.181054E+09 | 0.214514E+09 | 0.268403E+09 |
| June | 0.240623E+09 | 51534154.87 | 0.189089E+09 | 0.230523E+09 | 0.170377E+09 |
| July | 0.252290E+09 | 60599085.67 | 0.191691E+09 | 0.284689E+09 | 0.128174E+09 |
| August | 0.281612E+09 | 89590638.70 | 0.192022E+09 | 0.321286E+09 | 0.159879E+09 |
| September | 0.323589E+09 | 0.159595E+09 | 0.163994E+09 | 0.343595E+09 | 0.230514E+09 |
| October | 0.316929E+09 | 0.181395E+09 | 0.135534E+09 | 0.272031E+09 | 0.356261E+09 |
| November | 0.219687E+09 | 0.124364E+09 | 95323344.21 | 0.155824E+09 | 0.451661E+09 |
| December | 0.211208E+09 | 0.109328E+09 | 0.101880E+09 | 0.109138E+09 | 0.639896E+09 |
| Annual Sum or Average | 0.324455E+10 | 0.143026E+10 | 0.181429E+10 | 0.267372E+10 | 0.444431E+10 |
| Minimum of Months | 0.211208E+09 | 51534154.87 | 95323344.21 | 0.109138E+09 | 0.128174E+09 |
| Maximum of Months | 0.346487E+09 | 0.192235E+09 | 0.192022E+09 | 0.343595E+09 | 0.642960E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM215_218_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251946E+09 | 0.146788E+09 | 0.105158E+09 | 0.142774E+09 | 0.642960E+09 |
| February | 0.260073E+09 | 0.125206E+09 | 0.134867E+09 | 0.132898E+09 | 0.565480E+09 |
| March | 0.346487E+09 | 0.192235E+09 | 0.154252E+09 | 0.249531E+09 | 0.464654E+09 |
| April | 0.285132E+09 | 0.115706E+09 | 0.169426E+09 | 0.216911E+09 | 0.366049E+09 |
| May | 0.254971E+09 | 73916805.40 | 0.181054E+09 | 0.214514E+09 | 0.268403E+09 |
| June | 0.240623E+09 | 51534154.87 | 0.189089E+09 | 0.230523E+09 | 0.170377E+09 |
| July | 0.252290E+09 | 60599085.67 | 0.191691E+09 | 0.284689E+09 | 0.128174E+09 |
| August | 0.281612E+09 | 89590638.70 | 0.192022E+09 | 0.321286E+09 | 0.159879E+09 |
| September | 0.323589E+09 | 0.159595E+09 | 0.163994E+09 | 0.343595E+09 | 0.230514E+09 |
| October | 0.316929E+09 | 0.181395E+09 | 0.135534E+09 | 0.272031E+09 | 0.356261E+09 |
| November | 0.219687E+09 | 0.124364E+09 | 95323344.21 | 0.155824E+09 | 0.451661E+09 |
| December | 0.211208E+09 | 0.109328E+09 | 0.101880E+09 | 0.109138E+09 | 0.639896E+09 |
| Annual Sum or Average | 0.324455E+10 | 0.143026E+10 | 0.181429E+10 | 0.267372E+10 | 0.444431E+10 |
| Minimum of Months | 0.211208E+09 | 51534154.87 | 95323344.21 | 0.109138E+09 | 0.128174E+09 |
| Maximum of Months | 0.346487E+09 | 0.192235E+09 | 0.192022E+09 | 0.343595E+09 | 0.642960E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM215_218_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251946E+09 | 0.146788E+09 | 0.105158E+09 | 0.142774E+09 | 0.642960E+09 |
| February | 0.260073E+09 | 0.125206E+09 | 0.134867E+09 | 0.132898E+09 | 0.565480E+09 |
| March | 0.346487E+09 | 0.192235E+09 | 0.154252E+09 | 0.249531E+09 | 0.464654E+09 |
| April | 0.285132E+09 | 0.115706E+09 | 0.169426E+09 | 0.216911E+09 | 0.366049E+09 |
| May | 0.254971E+09 | 73916805.40 | 0.181054E+09 | 0.214514E+09 | 0.268403E+09 |
| June | 0.240623E+09 | 51534154.87 | 0.189089E+09 | 0.230523E+09 | 0.170377E+09 |
| July | 0.252290E+09 | 60599085.67 | 0.191691E+09 | 0.284689E+09 | 0.128174E+09 |
| August | 0.281612E+09 | 89590638.70 | 0.192022E+09 | 0.321286E+09 | 0.159879E+09 |
| September | 0.323589E+09 | 0.159595E+09 | 0.163994E+09 | 0.343595E+09 | 0.230514E+09 |
| October | 0.316929E+09 | 0.181395E+09 | 0.135534E+09 | 0.272031E+09 | 0.356261E+09 |
| November | 0.219687E+09 | 0.124364E+09 | 95323344.21 | 0.155824E+09 | 0.451661E+09 |
| December | 0.211208E+09 | 0.109328E+09 | 0.101880E+09 | 0.109138E+09 | 0.639896E+09 |
| Annual Sum or Average | 0.324455E+10 | 0.143026E+10 | 0.181429E+10 | 0.267372E+10 | 0.444431E+10 |
| Minimum of Months | 0.211208E+09 | 51534154.87 | 95323344.21 | 0.109138E+09 | 0.128174E+09 |
| Maximum of Months | 0.346487E+09 | 0.192235E+09 | 0.192022E+09 | 0.343595E+09 | 0.642960E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM215_218_3_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251946E+09 | 0.146788E+09 | 0.105158E+09 | 0.142774E+09 | 0.642960E+09 |
| February | 0.260073E+09 | 0.125206E+09 | 0.134867E+09 | 0.132898E+09 | 0.565480E+09 |
| March | 0.346487E+09 | 0.192235E+09 | 0.154252E+09 | 0.249531E+09 | 0.464654E+09 |
| April | 0.285132E+09 | 0.115706E+09 | 0.169426E+09 | 0.216911E+09 | 0.366049E+09 |
| May | 0.254971E+09 | 73916805.40 | 0.181054E+09 | 0.214514E+09 | 0.268403E+09 |
| June | 0.240623E+09 | 51534154.87 | 0.189089E+09 | 0.230523E+09 | 0.170377E+09 |
| July | 0.252290E+09 | 60599085.67 | 0.191691E+09 | 0.284689E+09 | 0.128174E+09 |
| August | 0.281612E+09 | 89590638.70 | 0.192022E+09 | 0.321286E+09 | 0.159879E+09 |
| September | 0.323589E+09 | 0.159595E+09 | 0.163994E+09 | 0.343595E+09 | 0.230514E+09 |
| October | 0.316929E+09 | 0.181395E+09 | 0.135534E+09 | 0.272031E+09 | 0.356261E+09 |
| November | 0.219687E+09 | 0.124364E+09 | 95323344.21 | 0.155824E+09 | 0.451661E+09 |
| December | 0.211208E+09 | 0.109328E+09 | 0.101880E+09 | 0.109138E+09 | 0.639896E+09 |
| Annual Sum or Average | 0.324455E+10 | 0.143026E+10 | 0.181429E+10 | 0.267372E+10 | 0.444431E+10 |
| Minimum of Months | 0.211208E+09 | 51534154.87 | 95323344.21 | 0.109138E+09 | 0.128174E+09 |
| Maximum of Months | 0.346487E+09 | 0.192235E+09 | 0.192022E+09 | 0.343595E+09 | 0.642960E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM219_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251946E+09 | 0.146788E+09 | 0.105158E+09 | 0.144229E+09 | 0.611032E+09 |
| February | 0.260073E+09 | 0.125206E+09 | 0.134867E+09 | 0.133869E+09 | 0.538401E+09 |
| March | 0.346487E+09 | 0.192235E+09 | 0.154252E+09 | 0.251915E+09 | 0.434684E+09 |
| April | 0.285132E+09 | 0.115706E+09 | 0.169426E+09 | 0.219760E+09 | 0.339552E+09 |
| May | 0.254971E+09 | 73916805.40 | 0.181054E+09 | 0.216769E+09 | 0.254724E+09 |
| June | 0.240623E+09 | 51534154.87 | 0.189089E+09 | 0.233172E+09 | 0.165672E+09 |
| July | 0.252290E+09 | 60599085.67 | 0.191691E+09 | 0.289046E+09 | 0.120975E+09 |
| August | 0.281612E+09 | 89590638.70 | 0.192022E+09 | 0.324813E+09 | 0.153209E+09 |
| September | 0.323589E+09 | 0.159595E+09 | 0.163994E+09 | 0.346224E+09 | 0.223347E+09 |
| October | 0.316929E+09 | 0.181395E+09 | 0.135534E+09 | 0.274531E+09 | 0.333485E+09 |
| November | 0.219687E+09 | 0.124364E+09 | 95323344.21 | 0.157729E+09 | 0.423614E+09 |
| December | 0.211208E+09 | 0.109328E+09 | 0.101880E+09 | 0.109979E+09 | 0.607813E+09 |
| Annual Sum or Average | 0.324455E+10 | 0.143026E+10 | 0.181429E+10 | 0.270204E+10 | 0.420651E+10 |
| Minimum of Months | 0.211208E+09 | 51534154.87 | 95323344.21 | 0.109979E+09 | 0.120975E+09 |
| Maximum of Months | 0.346487E+09 | 0.192235E+09 | 0.192022E+09 | 0.346224E+09 | 0.611032E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM220_223_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251946E+09 | 0.146788E+09 | 0.105158E+09 | 0.164237E+09 | 0.495448E+09 |
| February | 0.260073E+09 | 0.125206E+09 | 0.134867E+09 | 0.158387E+09 | 0.437820E+09 |
| March | 0.346487E+09 | 0.192235E+09 | 0.154252E+09 | 0.290216E+09 | 0.345304E+09 |
| April | 0.285132E+09 | 0.115706E+09 | 0.169426E+09 | 0.257536E+09 | 0.256255E+09 |
| May | 0.254971E+09 | 73916805.40 | 0.181054E+09 | 0.260693E+09 | 0.169139E+09 |
| June | 0.240623E+09 | 51534154.87 | 0.189089E+09 | 0.289677E+09 | 97255495.41 |
| July | 0.252290E+09 | 60599085.67 | 0.191691E+09 | 0.353024E+09 | 60598271.73 |
| August | 0.281612E+09 | 89590638.70 | 0.192022E+09 | 0.380976E+09 | 83656363.07 |
| September | 0.323589E+09 | 0.159595E+09 | 0.163994E+09 | 0.390825E+09 | 0.143266E+09 |
| October | 0.316929E+09 | 0.181395E+09 | 0.135534E+09 | 0.311550E+09 | 0.245386E+09 |
| November | 0.219687E+09 | 0.124364E+09 | 95323344.21 | 0.180118E+09 | 0.322461E+09 |
| December | 0.211208E+09 | 0.109328E+09 | 0.101880E+09 | 0.126968E+09 | 0.487360E+09 |
| Annual Sum or Average | 0.324455E+10 | 0.143026E+10 | 0.181429E+10 | 0.316421E+10 | 0.314395E+10 |
| Minimum of Months | 0.211208E+09 | 51534154.87 | 95323344.21 | 0.126968E+09 | 60598271.73 |
| Maximum of Months | 0.346487E+09 | 0.192235E+09 | 0.192022E+09 | 0.390825E+09 | 0.495448E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM220_223_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251946E+09 | 0.146788E+09 | 0.105158E+09 | 0.164237E+09 | 0.495448E+09 |
| February | 0.260073E+09 | 0.125206E+09 | 0.134867E+09 | 0.158387E+09 | 0.437820E+09 |
| March | 0.346487E+09 | 0.192235E+09 | 0.154252E+09 | 0.290216E+09 | 0.345304E+09 |
| April | 0.285132E+09 | 0.115706E+09 | 0.169426E+09 | 0.257536E+09 | 0.256255E+09 |
| May | 0.254971E+09 | 73916805.40 | 0.181054E+09 | 0.260693E+09 | 0.169139E+09 |
| June | 0.240623E+09 | 51534154.87 | 0.189089E+09 | 0.289677E+09 | 97255495.41 |
| July | 0.252290E+09 | 60599085.67 | 0.191691E+09 | 0.353024E+09 | 60598271.73 |
| August | 0.281612E+09 | 89590638.70 | 0.192022E+09 | 0.380976E+09 | 83656363.07 |
| September | 0.323589E+09 | 0.159595E+09 | 0.163994E+09 | 0.390825E+09 | 0.143266E+09 |
| October | 0.316929E+09 | 0.181395E+09 | 0.135534E+09 | 0.311550E+09 | 0.245386E+09 |
| November | 0.219687E+09 | 0.124364E+09 | 95323344.21 | 0.180118E+09 | 0.322461E+09 |
| December | 0.211208E+09 | 0.109328E+09 | 0.101880E+09 | 0.126968E+09 | 0.487360E+09 |
| Annual Sum or Average | 0.324455E+10 | 0.143026E+10 | 0.181429E+10 | 0.316421E+10 | 0.314395E+10 |
| Minimum of Months | 0.211208E+09 | 51534154.87 | 95323344.21 | 0.126968E+09 | 60598271.73 |
| Maximum of Months | 0.346487E+09 | 0.192235E+09 | 0.192022E+09 | 0.390825E+09 | 0.495448E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM220_223_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251946E+09 | 0.146788E+09 | 0.105158E+09 | 0.164237E+09 | 0.495448E+09 |
| February | 0.260073E+09 | 0.125206E+09 | 0.134867E+09 | 0.158387E+09 | 0.437820E+09 |
| March | 0.346487E+09 | 0.192235E+09 | 0.154252E+09 | 0.290216E+09 | 0.345304E+09 |
| April | 0.285132E+09 | 0.115706E+09 | 0.169426E+09 | 0.257536E+09 | 0.256255E+09 |
| May | 0.254971E+09 | 73916805.40 | 0.181054E+09 | 0.260693E+09 | 0.169139E+09 |
| June | 0.240623E+09 | 51534154.87 | 0.189089E+09 | 0.289677E+09 | 97255495.41 |
| July | 0.252290E+09 | 60599085.67 | 0.191691E+09 | 0.353024E+09 | 60598271.73 |
| August | 0.281612E+09 | 89590638.70 | 0.192022E+09 | 0.380976E+09 | 83656363.07 |
| September | 0.323589E+09 | 0.159595E+09 | 0.163994E+09 | 0.390825E+09 | 0.143266E+09 |
| October | 0.316929E+09 | 0.181395E+09 | 0.135534E+09 | 0.311550E+09 | 0.245386E+09 |
| November | 0.219687E+09 | 0.124364E+09 | 95323344.21 | 0.180118E+09 | 0.322461E+09 |
| December | 0.211208E+09 | 0.109328E+09 | 0.101880E+09 | 0.126968E+09 | 0.487360E+09 |
| Annual Sum or Average | 0.324455E+10 | 0.143026E+10 | 0.181429E+10 | 0.316421E+10 | 0.314395E+10 |
| Minimum of Months | 0.211208E+09 | 51534154.87 | 95323344.21 | 0.126968E+09 | 60598271.73 |
| Maximum of Months | 0.346487E+09 | 0.192235E+09 | 0.192022E+09 | 0.390825E+09 | 0.495448E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM220_223_3_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251946E+09 | 0.146788E+09 | 0.105158E+09 | 0.164237E+09 | 0.495448E+09 |
| February | 0.260073E+09 | 0.125206E+09 | 0.134867E+09 | 0.158387E+09 | 0.437820E+09 |
| March | 0.346487E+09 | 0.192235E+09 | 0.154252E+09 | 0.290216E+09 | 0.345304E+09 |
| April | 0.285132E+09 | 0.115706E+09 | 0.169426E+09 | 0.257536E+09 | 0.256255E+09 |
| May | 0.254971E+09 | 73916805.40 | 0.181054E+09 | 0.260693E+09 | 0.169139E+09 |
| June | 0.240623E+09 | 51534154.87 | 0.189089E+09 | 0.289677E+09 | 97255495.41 |
| July | 0.252290E+09 | 60599085.67 | 0.191691E+09 | 0.353024E+09 | 60598271.73 |
| August | 0.281612E+09 | 89590638.70 | 0.192022E+09 | 0.380976E+09 | 83656363.07 |
| September | 0.323589E+09 | 0.159595E+09 | 0.163994E+09 | 0.390825E+09 | 0.143266E+09 |
| October | 0.316929E+09 | 0.181395E+09 | 0.135534E+09 | 0.311550E+09 | 0.245386E+09 |
| November | 0.219687E+09 | 0.124364E+09 | 95323344.21 | 0.180118E+09 | 0.322461E+09 |
| December | 0.211208E+09 | 0.109328E+09 | 0.101880E+09 | 0.126968E+09 | 0.487360E+09 |
| Annual Sum or Average | 0.324455E+10 | 0.143026E+10 | 0.181429E+10 | 0.316421E+10 | 0.314395E+10 |
| Minimum of Months | 0.211208E+09 | 51534154.87 | 95323344.21 | 0.126968E+09 | 60598271.73 |
| Maximum of Months | 0.346487E+09 | 0.192235E+09 | 0.192022E+09 | 0.390825E+09 | 0.495448E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM224_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251946E+09 | 0.146788E+09 | 0.105158E+09 | 0.166813E+09 | 0.483628E+09 |
| February | 0.260073E+09 | 0.125206E+09 | 0.134867E+09 | 0.161736E+09 | 0.427416E+09 |
| March | 0.346487E+09 | 0.192235E+09 | 0.154252E+09 | 0.292454E+09 | 0.339669E+09 |
| April | 0.285132E+09 | 0.115706E+09 | 0.169426E+09 | 0.258322E+09 | 0.253322E+09 |
| May | 0.254971E+09 | 73916805.40 | 0.181054E+09 | 0.259847E+09 | 0.168027E+09 |
| June | 0.240623E+09 | 51534154.87 | 0.189089E+09 | 0.287460E+09 | 97437023.53 |
| July | 0.252290E+09 | 60599085.67 | 0.191691E+09 | 0.349406E+09 | 61592377.20 |
| August | 0.281612E+09 | 89590638.70 | 0.192022E+09 | 0.377715E+09 | 85088094.11 |
| September | 0.323589E+09 | 0.159595E+09 | 0.163994E+09 | 0.388595E+09 | 0.143895E+09 |
| October | 0.316929E+09 | 0.181395E+09 | 0.135534E+09 | 0.310902E+09 | 0.244026E+09 |
| November | 0.219687E+09 | 0.124364E+09 | 95323344.21 | 0.180646E+09 | 0.318054E+09 |
| December | 0.211208E+09 | 0.109328E+09 | 0.101880E+09 | 0.129037E+09 | 0.475701E+09 |
| Annual Sum or Average | 0.324455E+10 | 0.143026E+10 | 0.181429E+10 | 0.316293E+10 | 0.309786E+10 |
| Minimum of Months | 0.211208E+09 | 51534154.87 | 95323344.21 | 0.129037E+09 | 61592377.20 |
| Maximum of Months | 0.346487E+09 | 0.192235E+09 | 0.192022E+09 | 0.388595E+09 | 0.483628E+09 |
Report: WindowEnergyReportMonthly
For: W_CORRIDORFLR3_2_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 31814299.38 | 7492682.50 | 24321616.88 | 4850559.44 | 0.202747E+09 |
| February | 46561134.82 | 12016558.24 | 34544576.58 | 11947821.81 | 0.174252E+09 |
| March | 81038794.01 | 34836904.83 | 46201889.18 | 51406545.73 | 0.130893E+09 |
| April | 95400584.78 | 39046730.28 | 56353854.50 | 76379962.23 | 91987925.28 |
| May | 0.116379E+09 | 52550318.09 | 63828365.87 | 0.114953E+09 | 64393615.82 |
| June | 0.136068E+09 | 64015190.35 | 72052700.43 | 0.158311E+09 | 39103102.34 |
| July | 0.125557E+09 | 54971331.13 | 70585625.93 | 0.161144E+09 | 26462830.36 |
| August | 0.113435E+09 | 48108738.80 | 65326739.18 | 0.142188E+09 | 34977416.78 |
| September | 86437478.29 | 37347850.17 | 49089628.12 | 91866645.18 | 56282642.38 |
| October | 57878309.33 | 20387860.69 | 37490448.63 | 40753689.67 | 95172492.89 |
| November | 32920955.27 | 9345891.71 | 23575063.57 | 14101701.15 | 0.122025E+09 |
| December | 29676342.99 | 6430188.24 | 23246154.75 | 4435466.89 | 0.193943E+09 |
| Annual Sum or Average | 0.953167E+09 | 0.386550E+09 | 0.566617E+09 | 0.872339E+09 | 0.123224E+10 |
| Minimum of Months | 29676342.99 | 6430188.24 | 23246154.75 | 4435466.89 | 26462830.36 |
| Maximum of Months | 0.136068E+09 | 64015190.35 | 72052700.43 | 0.161144E+09 | 0.202747E+09 |
Report: WindowEnergyReportMonthly
For: W_CORRIDORFLR3_15_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 37098023.40 | 12043509.91 | 25054513.49 | 7968366.82 | 0.191294E+09 |
| February | 48931354.12 | 14616069.33 | 34315284.79 | 14354438.64 | 0.165771E+09 |
| March | 78036018.86 | 32624659.66 | 45411359.20 | 48034893.28 | 0.127425E+09 |
| April | 99745595.56 | 44091871.74 | 55653723.81 | 80291451.28 | 87030931.82 |
| May | 0.115457E+09 | 51037941.57 | 64418752.04 | 0.113785E+09 | 60911769.44 |
| June | 0.124900E+09 | 55206349.60 | 69693194.00 | 0.143824E+09 | 36401936.36 |
| July | 0.123778E+09 | 54411133.48 | 69367020.76 | 0.158843E+09 | 24332756.28 |
| August | 0.111750E+09 | 46773193.73 | 64976390.42 | 0.137976E+09 | 33461922.41 |
| September | 89772857.57 | 39667690.25 | 50105167.32 | 95786281.90 | 53921161.85 |
| October | 63027240.95 | 25973124.56 | 37054116.39 | 46613416.55 | 90443692.21 |
| November | 34636493.95 | 11083346.69 | 23553147.25 | 15479900.41 | 0.118222E+09 |
| December | 28845438.38 | 5970833.92 | 22874604.46 | 3497287.40 | 0.189035E+09 |
| Annual Sum or Average | 0.955977E+09 | 0.393500E+09 | 0.562477E+09 | 0.866455E+09 | 0.117825E+10 |
| Minimum of Months | 28845438.38 | 5970833.92 | 22874604.46 | 3497287.40 | 24332756.28 |
| Maximum of Months | 0.124900E+09 | 55206349.60 | 69693194.00 | 0.158843E+09 | 0.191294E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM301_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 693.48 | 0.455565E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 1567868.23 | 0.388286E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 28709948.86 | 0.306690E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 60130216.73 | 0.214046E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.108030E+09 | 0.148673E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.175636E+09 | 98092887.37 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.203457E+09 | 71973914.33 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.166612E+09 | 95472695.12 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 91841659.56 | 0.142720E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 35475452.34 | 0.219840E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 9879085.51 | 0.265444E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 471360.38 | 0.427684E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.881812E+09 | 0.283449E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 693.48 | 71973914.33 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.203457E+09 | 0.455565E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM302_305_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.463654E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 1328180.30 | 0.396294E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 28155843.85 | 0.315642E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 60266557.23 | 0.220646E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.108506E+09 | 0.153101E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.176452E+09 | 0.100706E+09 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.204910E+09 | 73877043.31 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.167917E+09 | 97681257.65 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 93113384.28 | 0.145619E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 35614702.19 | 0.225258E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 9600855.97 | 0.274444E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 411234.19 | 0.437293E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.886276E+09 | 0.290422E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 73877043.31 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.204910E+09 | 0.463654E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM302_305_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.463654E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 1328180.30 | 0.396294E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 28155843.85 | 0.315642E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 60266557.23 | 0.220646E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.108506E+09 | 0.153101E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.176452E+09 | 0.100706E+09 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.204910E+09 | 73877043.31 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.167917E+09 | 97681257.65 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 93113384.28 | 0.145619E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 35614702.19 | 0.225258E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 9600855.97 | 0.274444E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 411234.19 | 0.437293E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.886276E+09 | 0.290422E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 73877043.31 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.204910E+09 | 0.463654E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM302_305_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.463654E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 1328180.30 | 0.396294E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 28155843.85 | 0.315642E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 60266557.23 | 0.220646E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.108506E+09 | 0.153101E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.176452E+09 | 0.100706E+09 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.204910E+09 | 73877043.31 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.167917E+09 | 97681257.65 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 93113384.28 | 0.145619E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 35614702.19 | 0.225258E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 9600855.97 | 0.274444E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 411234.19 | 0.437293E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.886276E+09 | 0.290422E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 73877043.31 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.204910E+09 | 0.463654E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM302_305_5_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.463654E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 1328180.30 | 0.396294E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 28155843.85 | 0.315642E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 60266557.23 | 0.220646E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.108506E+09 | 0.153101E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.176452E+09 | 0.100706E+09 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.204910E+09 | 73877043.31 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.167917E+09 | 97681257.65 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 93113384.28 | 0.145619E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 35614702.19 | 0.225258E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 9600855.97 | 0.274444E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 411234.19 | 0.437293E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.886276E+09 | 0.290422E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 73877043.31 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.204910E+09 | 0.463654E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM306_308_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.479973E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 1058432.93 | 0.409993E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 26328156.07 | 0.328372E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 57376231.60 | 0.228733E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.106872E+09 | 0.155785E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.177378E+09 | 0.100324E+09 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.207237E+09 | 72356412.27 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.169437E+09 | 96503877.72 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 92635792.70 | 0.147125E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 33635838.86 | 0.233300E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 8600634.75 | 0.287396E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 328937.03 | 0.452440E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.880889E+09 | 0.299230E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 72356412.27 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.207237E+09 | 0.479973E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM306_308_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 52527386.44 | 0.00 | 52527386.44 | 0.00 | 0.435165E+09 |
| February | 72286996.52 | 0.00 | 72286996.52 | 913607.99 | 0.371933E+09 |
| March | 97071729.42 | 3437.84 | 97068291.58 | 23410796.77 | 0.297717E+09 |
| April | 0.119760E+09 | 577424.35 | 0.119182E+09 | 51112230.06 | 0.207159E+09 |
| May | 0.143759E+09 | 6190145.07 | 0.137569E+09 | 95531729.39 | 0.140967E+09 |
| June | 0.167264E+09 | 14222670.61 | 0.153042E+09 | 0.158886E+09 | 90659336.15 |
| July | 0.160972E+09 | 10950372.80 | 0.150022E+09 | 0.185848E+09 | 65327131.95 |
| August | 0.139365E+09 | 2690368.92 | 0.136675E+09 | 0.151924E+09 | 87179561.25 |
| September | 0.102220E+09 | 45237.30 | 0.102174E+09 | 82927330.37 | 0.133028E+09 |
| October | 78923207.87 | 0.00 | 78923207.87 | 29949469.30 | 0.211174E+09 |
| November | 51323663.93 | 0.00 | 51323663.93 | 7647254.97 | 0.260271E+09 |
| December | 49164062.15 | 0.00 | 49164062.15 | 288863.29 | 0.410088E+09 |
| Annual Sum or Average | 0.123464E+10 | 34679656.89 | 0.119996E+10 | 0.788440E+09 | 0.271067E+10 |
| Minimum of Months | 49164062.15 | 0.00 | 49164062.15 | 0.00 | 65327131.95 |
| Maximum of Months | 0.167264E+09 | 14222670.61 | 0.153042E+09 | 0.185848E+09 | 0.435165E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM306_308_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.479973E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 1058432.93 | 0.409993E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 26328156.07 | 0.328372E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 57376231.60 | 0.228733E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.106872E+09 | 0.155785E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.177378E+09 | 0.100324E+09 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.207237E+09 | 72356412.27 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.169437E+09 | 96503877.72 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 92635792.70 | 0.147125E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 33635838.86 | 0.233300E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 8600634.75 | 0.287396E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 328937.03 | 0.452440E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.880889E+09 | 0.299230E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 72356412.27 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.207237E+09 | 0.479973E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM309_312_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.558204E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 367269.00 | 0.479726E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 21558133.03 | 0.374113E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 49225977.52 | 0.245443E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.106140E+09 | 0.149256E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.191487E+09 | 85390207.31 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.231204E+09 | 53926114.55 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.184818E+09 | 76924353.40 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 94276884.33 | 0.138290E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 27830839.33 | 0.249985E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 5945244.37 | 0.328268E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 137926.30 | 0.527350E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.912991E+09 | 0.326688E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 53926114.55 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.231204E+09 | 0.558204E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM309_312_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.558204E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 367269.00 | 0.479726E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 21558133.03 | 0.374113E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 49225977.52 | 0.245443E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.106140E+09 | 0.149256E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.191487E+09 | 85390207.31 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.231204E+09 | 53926114.55 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.184818E+09 | 76924353.40 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 94276884.33 | 0.138290E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 27830839.33 | 0.249985E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 5945244.37 | 0.328268E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 137926.30 | 0.527350E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.912991E+09 | 0.326688E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 53926114.55 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.231204E+09 | 0.558204E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM309_312_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.558204E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 367269.00 | 0.479726E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 21558133.03 | 0.374113E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 49225977.52 | 0.245443E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.106140E+09 | 0.149256E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.191487E+09 | 85390207.31 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.231204E+09 | 53926114.55 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.184818E+09 | 76924353.40 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 94276884.33 | 0.138290E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 27830839.33 | 0.249985E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 5945244.37 | 0.328268E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 137926.30 | 0.527350E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.912991E+09 | 0.326688E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 53926114.55 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.231204E+09 | 0.558204E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM309_312_5_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.558204E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 367269.00 | 0.479726E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 21558133.03 | 0.374113E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 49225977.52 | 0.245443E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.106140E+09 | 0.149256E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.191487E+09 | 85390207.31 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.231204E+09 | 53926114.55 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.184818E+09 | 76924353.40 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 94276884.33 | 0.138290E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 27830839.33 | 0.249985E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 5945244.37 | 0.328268E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 137926.30 | 0.527350E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.912991E+09 | 0.326688E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 53926114.55 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.231204E+09 | 0.558204E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM313_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.461953E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 1587742.58 | 0.391729E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 28749333.98 | 0.312550E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 61947968.06 | 0.217061E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.112296E+09 | 0.148489E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.182704E+09 | 96152588.80 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.210826E+09 | 69711839.50 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.172156E+09 | 93722236.51 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 94906166.17 | 0.142929E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 35904565.57 | 0.225136E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 9511653.96 | 0.274935E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 442317.46 | 0.434513E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.911032E+09 | 0.286888E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 69711839.50 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.210826E+09 | 0.461953E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM314_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.169876E+09 | 0.469168E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.165221E+09 | 0.416202E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.297003E+09 | 0.330935E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.261576E+09 | 0.247308E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.261125E+09 | 0.166227E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.287193E+09 | 98011244.34 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.348379E+09 | 62372912.95 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.377570E+09 | 85024431.63 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.389918E+09 | 0.141283E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.314985E+09 | 0.235191E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.184246E+09 | 0.303487E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.131742E+09 | 0.460002E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.318883E+10 | 0.301521E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.131742E+09 | 62372912.95 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.389918E+09 | 0.469168E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM315_318_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.160480E+09 | 0.511132E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.153404E+09 | 0.451794E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.283566E+09 | 0.356586E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.251578E+09 | 0.266325E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.253718E+09 | 0.179662E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.280659E+09 | 0.106288E+09 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.342595E+09 | 68248187.12 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.372257E+09 | 92323927.16 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.384372E+09 | 0.152506E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.306911E+09 | 0.253427E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.177001E+09 | 0.331561E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.123696E+09 | 0.502589E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.309024E+10 | 0.327244E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.123696E+09 | 68248187.12 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.384372E+09 | 0.511132E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM315_318_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.160480E+09 | 0.511132E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.153404E+09 | 0.451794E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.283566E+09 | 0.356586E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.251578E+09 | 0.266325E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.253718E+09 | 0.179662E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.280659E+09 | 0.106288E+09 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.342595E+09 | 68248187.12 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.372257E+09 | 92323927.16 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.384372E+09 | 0.152506E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.306911E+09 | 0.253427E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.177001E+09 | 0.331561E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.123696E+09 | 0.502589E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.309024E+10 | 0.327244E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.123696E+09 | 68248187.12 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.384372E+09 | 0.511132E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM315_318_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.160480E+09 | 0.511132E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.153404E+09 | 0.451794E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.283566E+09 | 0.356586E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.251578E+09 | 0.266325E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.253718E+09 | 0.179662E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.280659E+09 | 0.106288E+09 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.342595E+09 | 68248187.12 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.372257E+09 | 92323927.16 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.384372E+09 | 0.152506E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.306911E+09 | 0.253427E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.177001E+09 | 0.331561E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.123696E+09 | 0.502589E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.309024E+10 | 0.327244E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.123696E+09 | 68248187.12 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.384372E+09 | 0.511132E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM315_318_3_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.160480E+09 | 0.511132E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.153404E+09 | 0.451794E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.283566E+09 | 0.356586E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.251578E+09 | 0.266325E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.253718E+09 | 0.179662E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.280659E+09 | 0.106288E+09 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.342595E+09 | 68248187.12 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.372257E+09 | 92323927.16 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.384372E+09 | 0.152506E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.306911E+09 | 0.253427E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.177001E+09 | 0.331561E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.123696E+09 | 0.502589E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.309024E+10 | 0.327244E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.123696E+09 | 68248187.12 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.384372E+09 | 0.511132E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM319_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.159286E+09 | 0.516966E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.152124E+09 | 0.455877E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.277118E+09 | 0.376839E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.242785E+09 | 0.292483E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.239180E+09 | 0.213265E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.258100E+09 | 0.134563E+09 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.314284E+09 | 94829850.90 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.347902E+09 | 0.122532E+09 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.366327E+09 | 0.185145E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.296278E+09 | 0.284143E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.172479E+09 | 0.352898E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.122620E+09 | 0.508101E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.294848E+10 | 0.353764E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.122620E+09 | 94829850.90 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.366327E+09 | 0.516966E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM320_323_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.165550E+09 | 0.485294E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.159962E+09 | 0.430233E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.291808E+09 | 0.339566E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.259123E+09 | 0.251430E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.261808E+09 | 0.166170E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.290444E+09 | 95947951.93 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.353762E+09 | 59466106.76 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.381870E+09 | 81766738.80 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.391962E+09 | 0.139922E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.313879E+09 | 0.238264E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.182068E+09 | 0.311813E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.128241E+09 | 0.475806E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.318048E+10 | 0.307568E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.128241E+09 | 59466106.76 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.391962E+09 | 0.485294E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM320_323_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.165550E+09 | 0.485294E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.159962E+09 | 0.430233E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.291808E+09 | 0.339566E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.259123E+09 | 0.251430E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.261808E+09 | 0.166170E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.290444E+09 | 95947951.93 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.353762E+09 | 59466106.76 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.381870E+09 | 81766738.80 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.391962E+09 | 0.139922E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.313879E+09 | 0.238264E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.182068E+09 | 0.311813E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.128241E+09 | 0.475806E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.318048E+10 | 0.307568E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.128241E+09 | 59466106.76 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.391962E+09 | 0.485294E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM320_323_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.165550E+09 | 0.485294E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.159962E+09 | 0.430233E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.291808E+09 | 0.339566E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.259123E+09 | 0.251430E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.261808E+09 | 0.166170E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.290444E+09 | 95947951.93 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.353762E+09 | 59466106.76 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.381870E+09 | 81766738.80 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.391962E+09 | 0.139922E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.313879E+09 | 0.238264E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.182068E+09 | 0.311813E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.128241E+09 | 0.475806E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.318048E+10 | 0.307568E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.128241E+09 | 59466106.76 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.391962E+09 | 0.485294E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM320_323_3_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.165550E+09 | 0.485294E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.159962E+09 | 0.430233E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.291808E+09 | 0.339566E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.259123E+09 | 0.251430E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.261808E+09 | 0.166170E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.290444E+09 | 95947951.93 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.353762E+09 | 59466106.76 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.381870E+09 | 81766738.80 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.391962E+09 | 0.139922E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.313879E+09 | 0.238264E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.182068E+09 | 0.311813E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.128241E+09 | 0.475806E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.318048E+10 | 0.307568E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.128241E+09 | 59466106.76 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.391962E+09 | 0.485294E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM324_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.172635E+09 | 0.441079E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.169019E+09 | 0.388831E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.297789E+09 | 0.324974E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.260746E+09 | 0.250409E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.256763E+09 | 0.178755E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.275704E+09 | 0.112142E+09 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.329443E+09 | 78498784.27 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.361625E+09 | 0.103441E+09 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.379969E+09 | 0.158649E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.312090E+09 | 0.244030E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.184646E+09 | 0.300131E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.134364E+09 | 0.430582E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.313479E+10 | 0.301152E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.134364E+09 | 78498784.27 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.379969E+09 | 0.441079E+09 |
Report: WindowEnergyReportMonthly
For: W_CORRIDORFLR4_2_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 31814299.38 | 7492682.50 | 24321616.88 | 4937156.14 | 0.196217E+09 |
| February | 46561134.82 | 12016558.24 | 34544576.58 | 12011067.27 | 0.168815E+09 |
| March | 81038794.01 | 34836904.83 | 46201889.18 | 51175108.95 | 0.124970E+09 |
| April | 95400584.78 | 39046730.28 | 56353854.50 | 75126663.81 | 85591033.48 |
| May | 0.116379E+09 | 52550318.09 | 63828365.87 | 0.113176E+09 | 57784195.47 |
| June | 0.136068E+09 | 64015190.35 | 72052700.43 | 0.156088E+09 | 35472815.44 |
| July | 0.125557E+09 | 54971331.13 | 70585625.93 | 0.158747E+09 | 24083460.79 |
| August | 0.113435E+09 | 48108738.80 | 65326739.18 | 0.140237E+09 | 31969126.19 |
| September | 86437478.29 | 37347850.17 | 49089628.12 | 90784964.71 | 50696901.10 |
| October | 57878309.33 | 20387860.69 | 37490448.63 | 40485849.48 | 87274309.87 |
| November | 32920955.27 | 9345891.71 | 23575063.57 | 14133004.00 | 0.114931E+09 |
| December | 29676342.99 | 6430188.24 | 23246154.75 | 4511237.70 | 0.187406E+09 |
| Annual Sum or Average | 0.953167E+09 | 0.386550E+09 | 0.566617E+09 | 0.861412E+09 | 0.116521E+10 |
| Minimum of Months | 29676342.99 | 6430188.24 | 23246154.75 | 4511237.70 | 24083460.79 |
| Maximum of Months | 0.136068E+09 | 64015190.35 | 72052700.43 | 0.158747E+09 | 0.196217E+09 |
Report: WindowEnergyReportMonthly
For: W_CORRIDORFLR4_15_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 37098023.40 | 12043509.91 | 25054513.49 | 8305500.45 | 0.185029E+09 |
| February | 48931354.12 | 14616069.33 | 34315284.79 | 14701916.74 | 0.160608E+09 |
| March | 78036018.86 | 32624659.66 | 45411359.20 | 48539018.08 | 0.122161E+09 |
| April | 99745595.56 | 44091871.74 | 55653723.81 | 80304482.53 | 81784570.03 |
| May | 0.115457E+09 | 51037941.57 | 64418752.04 | 0.113305E+09 | 55598355.78 |
| June | 0.124900E+09 | 55206349.60 | 69693194.00 | 0.142653E+09 | 33646011.25 |
| July | 0.123778E+09 | 54411133.48 | 69367020.76 | 0.157146E+09 | 22454275.83 |
| August | 0.111750E+09 | 46773193.73 | 64976390.42 | 0.136661E+09 | 30870641.33 |
| September | 89772857.57 | 39667690.25 | 50105167.32 | 95673404.49 | 49218140.01 |
| October | 63027240.95 | 25973124.56 | 37054116.39 | 47361488.61 | 83612761.29 |
| November | 34636493.95 | 11083346.69 | 23553147.25 | 15955237.80 | 0.111586E+09 |
| December | 28845438.38 | 5970833.92 | 22874604.46 | 3692937.02 | 0.182581E+09 |
| Annual Sum or Average | 0.955977E+09 | 0.393500E+09 | 0.562477E+09 | 0.864298E+09 | 0.111915E+10 |
| Minimum of Months | 28845438.38 | 5970833.92 | 22874604.46 | 3692937.02 | 22454275.83 |
| Maximum of Months | 0.124900E+09 | 55206349.60 | 69693194.00 | 0.157146E+09 | 0.185029E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM401_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.522214E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 669991.85 | 0.448722E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 24089998.82 | 0.344285E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 50157317.23 | 0.222830E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 99850086.11 | 0.135262E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.180319E+09 | 77858111.25 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.218659E+09 | 48773157.13 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.174570E+09 | 70139469.16 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 89225688.81 | 0.125758E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 30444266.28 | 0.223185E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 7722825.73 | 0.290595E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 286394.60 | 0.490203E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.875994E+09 | 0.299982E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 48773157.13 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.218659E+09 | 0.522214E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM402_405_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 18264.87 | 0.426869E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 1660015.77 | 0.364938E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 27591693.69 | 0.281284E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 55697729.94 | 0.188036E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 97557855.49 | 0.130364E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.163060E+09 | 86901665.54 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.190991E+09 | 63702836.14 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.154992E+09 | 83852688.12 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 84762655.47 | 0.124112E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 34933447.45 | 0.189733E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 10170366.15 | 0.231226E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 574981.56 | 0.398208E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.822011E+09 | 0.256923E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 18264.87 | 63702836.14 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.190991E+09 | 0.426869E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM402_405_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 18264.87 | 0.426869E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 1660015.77 | 0.364938E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 27591693.69 | 0.281284E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 55697729.94 | 0.188036E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 97557855.49 | 0.130364E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.163060E+09 | 86901665.54 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.190991E+09 | 63702836.14 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.154992E+09 | 83852688.12 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 84762655.47 | 0.124112E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 34933447.45 | 0.189733E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 10170366.15 | 0.231226E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 574981.56 | 0.398208E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.822011E+09 | 0.256923E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 18264.87 | 63702836.14 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.190991E+09 | 0.426869E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM402_405_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 18264.87 | 0.426869E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 1660015.77 | 0.364938E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 27591693.69 | 0.281284E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 55697729.94 | 0.188036E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 97557855.49 | 0.130364E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.163060E+09 | 86901665.54 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.190991E+09 | 63702836.14 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.154992E+09 | 83852688.12 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 84762655.47 | 0.124112E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 34933447.45 | 0.189733E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 10170366.15 | 0.231226E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 574981.56 | 0.398208E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.822011E+09 | 0.256923E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 18264.87 | 63702836.14 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.190991E+09 | 0.426869E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM402_405_5_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 18264.87 | 0.426869E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 1660015.77 | 0.364938E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 27591693.69 | 0.281284E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 55697729.94 | 0.188036E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 97557855.49 | 0.130364E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.163060E+09 | 86901665.54 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.190991E+09 | 63702836.14 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.154992E+09 | 83852688.12 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 84762655.47 | 0.124112E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 34933447.45 | 0.189733E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 10170366.15 | 0.231226E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 574981.56 | 0.398208E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.822011E+09 | 0.256923E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 18264.87 | 63702836.14 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.190991E+09 | 0.426869E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM406_408_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 3607.22 | 0.433346E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 1396781.51 | 0.370444E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 26273699.40 | 0.288308E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 53673530.59 | 0.194435E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 96715223.96 | 0.133181E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.163795E+09 | 87405421.56 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.192441E+09 | 63359823.75 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.156010E+09 | 83902847.81 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 84614014.63 | 0.126271E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 33421096.68 | 0.196495E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 9283939.36 | 0.240226E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 478652.00 | 0.404738E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.818107E+09 | 0.262211E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 3607.22 | 63359823.75 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.192441E+09 | 0.433346E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM406_408_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 3607.22 | 0.433346E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 1396781.51 | 0.370444E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 26273699.40 | 0.288308E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 53673530.59 | 0.194435E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 96715223.96 | 0.133181E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.163795E+09 | 87405421.56 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.192441E+09 | 63359823.75 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.156010E+09 | 83902847.81 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 84614014.63 | 0.126271E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 33421096.68 | 0.196495E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 9283939.36 | 0.240226E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 478652.00 | 0.404738E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.818107E+09 | 0.262211E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 3607.22 | 63359823.75 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.192441E+09 | 0.433346E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM406_408_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 52527386.44 | 0.00 | 52527386.44 | 1837.49 | 0.393478E+09 |
| February | 72286996.52 | 0.00 | 72286996.52 | 1197234.56 | 0.336568E+09 |
| March | 97071729.42 | 3437.84 | 97068291.58 | 23351364.74 | 0.261626E+09 |
| April | 0.119760E+09 | 577424.35 | 0.119182E+09 | 47765349.83 | 0.176154E+09 |
| May | 0.143759E+09 | 6190145.07 | 0.137569E+09 | 86375977.33 | 0.120555E+09 |
| June | 0.167264E+09 | 14222670.61 | 0.153042E+09 | 0.146712E+09 | 79012400.19 |
| July | 0.160972E+09 | 10950372.80 | 0.150022E+09 | 0.172649E+09 | 57225954.55 |
| August | 0.139365E+09 | 2690368.92 | 0.136675E+09 | 0.139907E+09 | 75824230.38 |
| September | 0.102220E+09 | 45237.30 | 0.102174E+09 | 75710067.74 | 0.114208E+09 |
| October | 78923207.87 | 0.00 | 78923207.87 | 29750953.60 | 0.177896E+09 |
| November | 51323663.93 | 0.00 | 51323663.93 | 8245165.39 | 0.217619E+09 |
| December | 49164062.15 | 0.00 | 49164062.15 | 415945.12 | 0.367350E+09 |
| Annual Sum or Average | 0.123464E+10 | 34679656.89 | 0.119996E+10 | 0.732082E+09 | 0.237752E+10 |
| Minimum of Months | 49164062.15 | 0.00 | 49164062.15 | 1837.49 | 57225954.55 |
| Maximum of Months | 0.167264E+09 | 14222670.61 | 0.153042E+09 | 0.172649E+09 | 0.393478E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM409_412_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.536522E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 364498.83 | 0.461836E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 20267285.83 | 0.359098E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 44224042.30 | 0.232702E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 96696066.24 | 0.139068E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.180016E+09 | 77843766.95 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.219939E+09 | 47893709.31 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.174713E+09 | 69672181.80 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 87631070.24 | 0.129349E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 25710398.76 | 0.235757E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 5578019.77 | 0.309472E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 149414.58 | 0.505578E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.855288E+09 | 0.310479E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 47893709.31 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.219939E+09 | 0.536522E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM409_412_5_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.536522E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 364498.83 | 0.461836E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 20267285.83 | 0.359098E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 44224042.30 | 0.232702E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 96696066.24 | 0.139068E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.180016E+09 | 77843766.95 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.219939E+09 | 47893709.31 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.174713E+09 | 69672181.80 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 87631070.24 | 0.129349E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 25710398.76 | 0.235757E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 5578019.77 | 0.309472E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 149414.58 | 0.505578E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.855288E+09 | 0.310479E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 47893709.31 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.219939E+09 | 0.536522E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM409_412_5_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.536522E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 364498.83 | 0.461836E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 20267285.83 | 0.359098E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 44224042.30 | 0.232702E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 96696066.24 | 0.139068E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.180016E+09 | 77843766.95 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.219939E+09 | 47893709.31 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.174713E+09 | 69672181.80 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 87631070.24 | 0.129349E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 25710398.76 | 0.235757E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 5578019.77 | 0.309472E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 149414.58 | 0.505578E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.855288E+09 | 0.310479E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 47893709.31 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.219939E+09 | 0.536522E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM409_412_5_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.536522E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 364498.83 | 0.461836E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 20267285.83 | 0.359098E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 44224042.30 | 0.232702E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 96696066.24 | 0.139068E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.180016E+09 | 77843766.95 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.219939E+09 | 47893709.31 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.174713E+09 | 69672181.80 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 87631070.24 | 0.129349E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 25710398.76 | 0.235757E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 5578019.77 | 0.309472E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 149414.58 | 0.505578E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.855288E+09 | 0.310479E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 47893709.31 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.219939E+09 | 0.536522E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM413_5_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 58642040.59 | 0.00 | 58642040.59 | 18687.55 | 0.431535E+09 |
| February | 80701846.22 | 0.00 | 80701846.22 | 1976010.67 | 0.367127E+09 |
| March | 0.108372E+09 | 3838.03 | 0.108368E+09 | 28841742.47 | 0.285050E+09 |
| April | 0.133701E+09 | 644640.69 | 0.133056E+09 | 59112537.70 | 0.191969E+09 |
| May | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.103846E+09 | 0.132244E+09 |
| June | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.170772E+09 | 87598367.09 |
| July | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.197017E+09 | 64058612.42 |
| August | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.160170E+09 | 85139910.37 |
| September | 0.114119E+09 | 50503.25 | 0.114068E+09 | 88772547.62 | 0.127878E+09 |
| October | 88110587.98 | 0.00 | 88110587.98 | 36230638.30 | 0.196652E+09 |
| November | 57298193.59 | 0.00 | 57298193.59 | 10200654.28 | 0.237752E+09 |
| December | 54887190.27 | 0.00 | 54887190.27 | 590654.38 | 0.402020E+09 |
| Annual Sum or Average | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.857548E+09 | 0.260902E+10 |
| Minimum of Months | 54887190.27 | 0.00 | 54887190.27 | 18687.55 | 64058612.42 |
| Maximum of Months | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.197017E+09 | 0.431535E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM414_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.179682E+09 | 0.385665E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.175963E+09 | 0.343621E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.301786E+09 | 0.280996E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.258594E+09 | 0.218264E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.247687E+09 | 0.159776E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.262533E+09 | 0.103301E+09 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.314994E+09 | 72964427.27 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.350337E+09 | 94640254.70 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.374012E+09 | 0.140994E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.313340E+09 | 0.210029E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.188578E+09 | 0.253982E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.140248E+09 | 0.376111E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.310775E+10 | 0.264034E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.140248E+09 | 72964427.27 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.374012E+09 | 0.385665E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM415_418_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.164363E+09 | 0.467655E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.158054E+09 | 0.415637E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.285974E+09 | 0.324880E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.251163E+09 | 0.239738E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.250707E+09 | 0.157430E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.277008E+09 | 90009723.59 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.339606E+09 | 54271949.18 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.369336E+09 | 75592883.80 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.382732E+09 | 0.131531E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.308348E+09 | 0.225784E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.179400E+09 | 0.297401E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.127246E+09 | 0.458746E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.309394E+10 | 0.293868E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.127246E+09 | 54271949.18 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.382732E+09 | 0.467655E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM415_418_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.164363E+09 | 0.467655E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.158054E+09 | 0.415637E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.285974E+09 | 0.324880E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.251163E+09 | 0.239738E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.250707E+09 | 0.157430E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.277008E+09 | 90009723.59 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.339606E+09 | 54271949.18 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.369336E+09 | 75592883.80 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.382732E+09 | 0.131531E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.308348E+09 | 0.225784E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.179400E+09 | 0.297401E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.127246E+09 | 0.458746E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.309394E+10 | 0.293868E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.127246E+09 | 54271949.18 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.382732E+09 | 0.467655E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM415_418_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.164363E+09 | 0.467655E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.158054E+09 | 0.415637E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.285974E+09 | 0.324880E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.251163E+09 | 0.239738E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.250707E+09 | 0.157430E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.277008E+09 | 90009723.59 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.339606E+09 | 54271949.18 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.369336E+09 | 75592883.80 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.382732E+09 | 0.131531E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.308348E+09 | 0.225784E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.179400E+09 | 0.297401E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.127246E+09 | 0.458746E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.309394E+10 | 0.293868E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.127246E+09 | 54271949.18 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.382732E+09 | 0.467655E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM415_418_3_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.164363E+09 | 0.467655E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.158054E+09 | 0.415637E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.285974E+09 | 0.324880E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.251163E+09 | 0.239738E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.250707E+09 | 0.157430E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.277008E+09 | 90009723.59 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.339606E+09 | 54271949.18 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.369336E+09 | 75592883.80 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.382732E+09 | 0.131531E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.308348E+09 | 0.225784E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.179400E+09 | 0.297401E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.127246E+09 | 0.458746E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.309394E+10 | 0.293868E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.127246E+09 | 54271949.18 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.382732E+09 | 0.467655E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM419_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.164309E+09 | 0.475280E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.157667E+09 | 0.422811E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.285687E+09 | 0.330883E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.251115E+09 | 0.244834E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.250671E+09 | 0.161428E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.277423E+09 | 92397573.10 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.340434E+09 | 55779737.49 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.369941E+09 | 77732915.40 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.382684E+09 | 0.134709E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.307839E+09 | 0.230726E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.179101E+09 | 0.302944E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.127007E+09 | 0.466525E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.309388E+10 | 0.299605E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.127007E+09 | 55779737.49 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.382684E+09 | 0.475280E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM420_423_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.165606E+09 | 0.462909E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.159627E+09 | 0.411781E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.288019E+09 | 0.321613E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.253032E+09 | 0.236790E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.252626E+09 | 0.154512E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.279426E+09 | 87559980.46 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.342494E+09 | 52232642.98 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.371868E+09 | 73172978.69 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.384710E+09 | 0.128588E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.310134E+09 | 0.222509E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.180719E+09 | 0.293221E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.128404E+09 | 0.453920E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.311666E+10 | 0.289881E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.128404E+09 | 52232642.98 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.384710E+09 | 0.462909E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM420_423_3_0_0_0_1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.165606E+09 | 0.462909E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.159627E+09 | 0.411781E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.288019E+09 | 0.321613E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.253032E+09 | 0.236790E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.252626E+09 | 0.154512E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.279426E+09 | 87559980.46 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.342494E+09 | 52232642.98 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.371868E+09 | 73172978.69 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.384710E+09 | 0.128588E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.310134E+09 | 0.222509E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.180719E+09 | 0.293221E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.128404E+09 | 0.453920E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.311666E+10 | 0.289881E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.128404E+09 | 52232642.98 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.384710E+09 | 0.462909E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM420_423_3_0_0_0_2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.165606E+09 | 0.462909E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.159627E+09 | 0.411781E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.288019E+09 | 0.321613E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.253032E+09 | 0.236790E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.252626E+09 | 0.154512E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.279426E+09 | 87559980.46 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.342494E+09 | 52232642.98 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.371868E+09 | 73172978.69 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.384710E+09 | 0.128588E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.310134E+09 | 0.222509E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.180719E+09 | 0.293221E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.128404E+09 | 0.453920E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.311666E+10 | 0.289881E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.128404E+09 | 52232642.98 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.384710E+09 | 0.462909E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM420_423_3_0_0_0_3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.165606E+09 | 0.462909E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.159627E+09 | 0.411781E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.288019E+09 | 0.321613E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.253032E+09 | 0.236790E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.252626E+09 | 0.154512E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.279426E+09 | 87559980.46 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.342494E+09 | 52232642.98 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.371868E+09 | 73172978.69 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.384710E+09 | 0.128588E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.310134E+09 | 0.222509E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.180719E+09 | 0.293221E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.128404E+09 | 0.453920E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.311666E+10 | 0.289881E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.128404E+09 | 52232642.98 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.384710E+09 | 0.462909E+09 |
Report: WindowEnergyReportMonthly
For: W_GUESTROOM424_3_0_0_0_0
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.170260E+09 | 0.454838E+09 |
| February | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.164980E+09 | 0.405176E+09 |
| March | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.293333E+09 | 0.318339E+09 |
| April | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.256350E+09 | 0.235877E+09 |
| May | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.254090E+09 | 0.155841E+09 |
| June | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.279774E+09 | 89859322.66 |
| July | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.341449E+09 | 54965157.42 |
| August | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.371185E+09 | 76438655.33 |
| September | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.384800E+09 | 0.131299E+09 |
| October | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.312057E+09 | 0.222626E+09 |
| November | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.183226E+09 | 0.289430E+09 |
| December | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.132087E+09 | 0.446036E+09 |
| Annual Sum or Average | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.314359E+10 | 0.288072E+10 |
| Minimum of Months | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.132087E+09 | 54965157.42 |
| Maximum of Months | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.384800E+09 | 0.454838E+09 |
Report: WindowZoneSummaryMonthly
For: REARSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDORFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.02 | 624.78 | 67.72 | 15.95 | 51.77 | 0.00 | 0.00 |
| February | 1.83 | 603.31 | 96.03 | 18.90 | 77.14 | 0.00 | 0.00 |
| March | 19.37 | 420.21 | 127.88 | 33.78 | 94.10 | 0.00 | 0.00 |
| April | 55.75 | 299.99 | 159.11 | 39.47 | 119.64 | 0.00 | 0.00 |
| May | 116.81 | 187.86 | 182.81 | 48.06 | 134.75 | 0.00 | 0.00 |
| June | 201.45 | 110.03 | 217.28 | 61.31 | 155.97 | 0.00 | 0.00 |
| July | 223.66 | 73.22 | 199.65 | 52.02 | 147.63 | 0.00 | 0.00 |
| August | 187.83 | 101.80 | 179.18 | 44.39 | 134.79 | 0.00 | 0.00 |
| September | 101.22 | 171.65 | 141.85 | 36.75 | 105.10 | 0.00 | 0.00 |
| October | 27.32 | 305.49 | 102.43 | 26.04 | 76.39 | 0.00 | 0.00 |
| November | 4.22 | 413.33 | 67.22 | 16.39 | 50.82 | 0.00 | 0.00 |
| December | 0.00 | 611.13 | 58.60 | 10.57 | 48.03 | 0.00 | 0.00 |
| Annual Sum or Average | 78.78 | 325.49 | 133.48 | 33.70 | 99.77 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 73.22 | 58.60 | 10.57 | 48.03 | 0.00 | 0.00 |
| Maximum of Months | 223.66 | 624.78 | 217.28 | 61.31 | 155.97 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: REARSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONTLOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 826.47 | 85.38 | 0.00 | 85.38 | 0.00 | 0.00 |
| February | 0.50 | 781.94 | 130.09 | 0.00 | 130.09 | 0.00 | 0.00 |
| March | 33.30 | 542.50 | 157.79 | 0.01 | 157.79 | 0.00 | 0.00 |
| April | 80.14 | 362.60 | 201.16 | 0.97 | 200.19 | 0.00 | 0.00 |
| May | 160.21 | 218.90 | 233.68 | 10.06 | 223.62 | 0.00 | 0.00 |
| June | 290.29 | 137.92 | 280.96 | 23.89 | 257.07 | 0.00 | 0.00 |
| July | 333.50 | 92.29 | 261.66 | 17.80 | 243.86 | 0.00 | 0.00 |
| August | 265.44 | 130.32 | 226.54 | 4.37 | 222.17 | 0.00 | 0.00 |
| September | 137.29 | 227.77 | 171.70 | 0.08 | 171.62 | 0.00 | 0.00 |
| October | 38.17 | 380.14 | 128.29 | 0.00 | 128.29 | 0.00 | 0.00 |
| November | 8.34 | 509.51 | 86.21 | 0.00 | 86.21 | 0.00 | 0.00 |
| December | 0.16 | 787.19 | 79.92 | 0.00 | 79.92 | 0.00 | 0.00 |
| Annual Sum or Average | 113.01 | 414.63 | 170.45 | 4.79 | 165.66 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 92.29 | 79.92 | 0.00 | 79.92 | 0.00 | 0.00 |
| Maximum of Months | 333.50 | 826.47 | 280.96 | 23.89 | 257.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: RESTROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MEETINGROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 644.65 | 65.60 | 0.00 | 65.60 | 0.00 | 0.00 |
| February | 0.34 | 610.78 | 99.94 | 0.00 | 99.94 | 0.00 | 0.00 |
| March | 24.35 | 430.81 | 121.22 | 0.00 | 121.22 | 0.00 | 0.00 |
| April | 58.73 | 296.34 | 154.54 | 0.75 | 153.80 | 0.00 | 0.00 |
| May | 116.06 | 185.34 | 179.53 | 7.73 | 171.80 | 0.00 | 0.00 |
| June | 213.86 | 112.74 | 215.84 | 18.35 | 197.49 | 0.00 | 0.00 |
| July | 247.56 | 74.06 | 201.02 | 13.67 | 187.35 | 0.00 | 0.00 |
| August | 197.60 | 104.91 | 174.04 | 3.36 | 170.68 | 0.00 | 0.00 |
| September | 101.42 | 186.01 | 131.91 | 0.06 | 131.85 | 0.00 | 0.00 |
| October | 27.70 | 312.32 | 98.56 | 0.00 | 98.56 | 0.00 | 0.00 |
| November | 6.04 | 410.13 | 66.23 | 0.00 | 66.23 | 0.00 | 0.00 |
| December | 0.12 | 614.47 | 61.40 | 0.00 | 61.40 | 0.00 | 0.00 |
| Annual Sum or Average | 83.36 | 330.47 | 130.95 | 3.68 | 127.27 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 74.06 | 61.40 | 0.00 | 61.40 | 0.00 | 0.00 |
| Maximum of Months | 247.56 | 644.65 | 215.84 | 18.35 | 197.49 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MECHANICALROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM101
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 204.66 | 21.87 | 0.00 | 21.87 | 0.00 | 0.00 |
| February | 0.17 | 190.99 | 33.31 | 0.00 | 33.31 | 0.00 | 0.00 |
| March | 8.30 | 136.76 | 40.41 | 0.00 | 40.41 | 0.00 | 0.00 |
| April | 19.19 | 96.02 | 51.51 | 0.25 | 51.27 | 0.00 | 0.00 |
| May | 38.61 | 59.26 | 59.84 | 2.58 | 57.27 | 0.00 | 0.00 |
| June | 68.36 | 38.16 | 71.95 | 6.12 | 65.83 | 0.00 | 0.00 |
| July | 77.33 | 26.66 | 67.01 | 4.56 | 62.45 | 0.00 | 0.00 |
| August | 61.24 | 37.81 | 58.01 | 1.12 | 56.89 | 0.00 | 0.00 |
| September | 31.49 | 64.06 | 43.97 | 0.02 | 43.95 | 0.00 | 0.00 |
| October | 8.30 | 105.80 | 32.85 | 0.00 | 32.85 | 0.00 | 0.00 |
| November | 1.89 | 137.72 | 22.08 | 0.00 | 22.08 | 0.00 | 0.00 |
| December | 0.03 | 197.64 | 20.47 | 0.00 | 20.47 | 0.00 | 0.00 |
| Annual Sum or Average | 26.41 | 107.54 | 43.65 | 1.23 | 42.42 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 26.66 | 20.47 | 0.00 | 20.47 | 0.00 | 0.00 |
| Maximum of Months | 77.33 | 204.66 | 71.95 | 6.12 | 65.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM102
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 197.81 | 21.87 | 0.00 | 21.87 | 0.00 | 0.00 |
| February | 0.23 | 184.46 | 33.31 | 0.00 | 33.31 | 0.00 | 0.00 |
| March | 9.11 | 130.89 | 40.41 | 0.00 | 40.41 | 0.00 | 0.00 |
| April | 21.03 | 91.06 | 51.51 | 0.25 | 51.27 | 0.00 | 0.00 |
| May | 41.41 | 55.45 | 59.84 | 2.58 | 57.27 | 0.00 | 0.00 |
| June | 71.94 | 35.27 | 71.95 | 6.12 | 65.83 | 0.00 | 0.00 |
| July | 81.03 | 23.93 | 67.01 | 4.56 | 62.45 | 0.00 | 0.00 |
| August | 64.38 | 34.37 | 58.01 | 1.12 | 56.89 | 0.00 | 0.00 |
| September | 33.81 | 59.61 | 43.97 | 0.02 | 43.95 | 0.00 | 0.00 |
| October | 9.46 | 100.01 | 32.85 | 0.00 | 32.85 | 0.00 | 0.00 |
| November | 2.23 | 131.08 | 22.08 | 0.00 | 22.08 | 0.00 | 0.00 |
| December | 0.05 | 190.61 | 20.47 | 0.00 | 20.47 | 0.00 | 0.00 |
| Annual Sum or Average | 28.07 | 102.47 | 43.65 | 1.23 | 42.42 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 23.93 | 20.47 | 0.00 | 20.47 | 0.00 | 0.00 |
| Maximum of Months | 81.03 | 197.81 | 71.95 | 6.12 | 65.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM103
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 201.78 | 21.87 | 0.00 | 21.87 | 0.00 | 0.00 |
| February | 0.26 | 189.60 | 33.31 | 0.00 | 33.31 | 0.00 | 0.00 |
| March | 9.73 | 131.20 | 40.41 | 0.00 | 40.41 | 0.00 | 0.00 |
| April | 22.76 | 87.45 | 51.51 | 0.25 | 51.27 | 0.00 | 0.00 |
| May | 44.61 | 50.33 | 59.84 | 2.58 | 57.27 | 0.00 | 0.00 |
| June | 78.04 | 29.77 | 71.95 | 6.12 | 65.83 | 0.00 | 0.00 |
| July | 89.04 | 18.42 | 67.01 | 4.56 | 62.45 | 0.00 | 0.00 |
| August | 70.51 | 27.33 | 58.01 | 1.12 | 56.89 | 0.00 | 0.00 |
| September | 37.10 | 51.85 | 43.97 | 0.02 | 43.95 | 0.00 | 0.00 |
| October | 10.62 | 92.74 | 32.85 | 0.00 | 32.85 | 0.00 | 0.00 |
| November | 2.48 | 125.68 | 22.08 | 0.00 | 22.08 | 0.00 | 0.00 |
| December | 0.06 | 192.23 | 20.47 | 0.00 | 20.47 | 0.00 | 0.00 |
| Annual Sum or Average | 30.63 | 99.41 | 43.65 | 1.23 | 42.42 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 18.42 | 20.47 | 0.00 | 20.47 | 0.00 | 0.00 |
| Maximum of Months | 89.04 | 201.78 | 71.95 | 6.12 | 65.83 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM104
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 63.37 | 178.13 | 93.76 | 54.63 | 39.13 | 0.00 | 0.00 |
| February | 68.63 | 173.00 | 107.16 | 51.59 | 55.57 | 0.00 | 0.00 |
| March | 112.37 | 122.48 | 128.95 | 71.54 | 57.41 | 0.00 | 0.00 |
| April | 102.92 | 92.94 | 109.65 | 44.50 | 65.15 | 0.00 | 0.00 |
| May | 100.80 | 58.03 | 94.89 | 27.51 | 67.38 | 0.00 | 0.00 |
| June | 114.71 | 34.52 | 92.53 | 19.82 | 72.72 | 0.00 | 0.00 |
| July | 133.95 | 20.96 | 93.89 | 22.55 | 71.34 | 0.00 | 0.00 |
| August | 143.66 | 29.78 | 104.80 | 33.34 | 71.46 | 0.00 | 0.00 |
| September | 152.01 | 53.50 | 124.44 | 61.37 | 63.07 | 0.00 | 0.00 |
| October | 117.73 | 89.27 | 117.95 | 67.51 | 50.44 | 0.00 | 0.00 |
| November | 70.65 | 121.07 | 84.48 | 47.83 | 36.66 | 0.00 | 0.00 |
| December | 48.88 | 176.29 | 78.60 | 40.69 | 37.91 | 0.00 | 0.00 |
| Annual Sum or Average | 102.67 | 95.42 | 102.55 | 45.21 | 57.35 | 0.00 | 0.00 |
| Minimum of Months | 48.88 | 20.96 | 78.60 | 19.82 | 36.66 | 0.00 | 0.00 |
| Maximum of Months | 152.01 | 178.13 | 128.95 | 71.54 | 72.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM105
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 59.45 | 195.62 | 93.76 | 54.63 | 39.13 | 0.00 | 0.00 |
| February | 62.81 | 190.32 | 107.16 | 51.59 | 55.57 | 0.00 | 0.00 |
| March | 105.88 | 134.22 | 128.95 | 71.54 | 57.41 | 0.00 | 0.00 |
| April | 97.23 | 102.90 | 109.65 | 44.50 | 65.15 | 0.00 | 0.00 |
| May | 95.53 | 65.60 | 94.89 | 27.51 | 67.38 | 0.00 | 0.00 |
| June | 109.47 | 39.29 | 92.53 | 19.82 | 72.72 | 0.00 | 0.00 |
| July | 129.16 | 24.20 | 93.89 | 22.55 | 71.34 | 0.00 | 0.00 |
| August | 139.65 | 33.56 | 104.80 | 33.34 | 71.46 | 0.00 | 0.00 |
| September | 148.41 | 58.71 | 124.44 | 61.37 | 63.07 | 0.00 | 0.00 |
| October | 114.02 | 96.67 | 117.95 | 67.51 | 50.44 | 0.00 | 0.00 |
| November | 67.68 | 132.06 | 84.48 | 47.83 | 36.66 | 0.00 | 0.00 |
| December | 45.61 | 193.67 | 78.60 | 40.69 | 37.91 | 0.00 | 0.00 |
| Annual Sum or Average | 98.11 | 105.12 | 102.55 | 45.21 | 57.35 | 0.00 | 0.00 |
| Minimum of Months | 45.61 | 24.20 | 78.60 | 19.82 | 36.66 | 0.00 | 0.00 |
| Maximum of Months | 148.41 | 195.62 | 128.95 | 71.54 | 72.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: EMPLOYEELOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 53.69 | 231.75 | 93.76 | 54.63 | 39.13 | 0.00 | 0.00 |
| February | 55.43 | 224.52 | 107.16 | 51.59 | 55.57 | 0.00 | 0.00 |
| March | 94.14 | 165.38 | 128.95 | 71.54 | 57.41 | 0.00 | 0.00 |
| April | 84.68 | 133.78 | 109.65 | 44.50 | 65.15 | 0.00 | 0.00 |
| May | 81.85 | 92.72 | 94.89 | 27.51 | 67.38 | 0.00 | 0.00 |
| June | 92.15 | 59.51 | 92.53 | 19.82 | 72.72 | 0.00 | 0.00 |
| July | 110.33 | 42.55 | 93.89 | 22.55 | 71.34 | 0.00 | 0.00 |
| August | 123.27 | 54.13 | 104.80 | 33.34 | 71.46 | 0.00 | 0.00 |
| September | 134.88 | 82.79 | 124.44 | 61.37 | 63.07 | 0.00 | 0.00 |
| October | 102.37 | 127.08 | 117.95 | 67.51 | 50.44 | 0.00 | 0.00 |
| November | 60.50 | 168.68 | 84.48 | 47.83 | 36.66 | 0.00 | 0.00 |
| December | 40.93 | 231.70 | 78.60 | 40.69 | 37.91 | 0.00 | 0.00 |
| Annual Sum or Average | 86.36 | 134.06 | 102.55 | 45.21 | 57.35 | 0.00 | 0.00 |
| Minimum of Months | 40.93 | 42.55 | 78.60 | 19.82 | 36.66 | 0.00 | 0.00 |
| Maximum of Months | 134.88 | 231.75 | 128.95 | 71.54 | 72.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LAUNDRYROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 59.94 | 1465.52 | 281.29 | 163.88 | 117.40 | 0.00 | 0.00 |
| February | 57.17 | 1438.81 | 321.47 | 154.76 | 166.71 | 0.00 | 0.00 |
| March | 105.51 | 1192.37 | 386.84 | 214.62 | 172.22 | 0.00 | 0.00 |
| April | 63.99 | 1082.32 | 328.95 | 133.49 | 195.46 | 0.00 | 0.00 |
| May | 33.79 | 952.36 | 284.66 | 82.53 | 202.14 | 0.00 | 0.00 |
| June | 17.76 | 807.61 | 277.60 | 59.45 | 218.15 | 0.00 | 0.00 |
| July | 37.46 | 727.15 | 281.67 | 67.66 | 214.02 | 0.00 | 0.00 |
| August | 74.00 | 764.26 | 314.41 | 100.02 | 214.38 | 0.00 | 0.00 |
| September | 134.10 | 886.18 | 373.32 | 184.12 | 189.20 | 0.00 | 0.00 |
| October | 116.07 | 1086.43 | 353.84 | 202.52 | 151.32 | 0.00 | 0.00 |
| November | 63.66 | 1281.52 | 253.45 | 143.48 | 109.97 | 0.00 | 0.00 |
| December | 48.76 | 1499.69 | 235.81 | 122.06 | 113.74 | 0.00 | 0.00 |
| Annual Sum or Average | 67.75 | 1096.81 | 307.66 | 135.62 | 172.04 | 0.00 | 0.00 |
| Minimum of Months | 17.76 | 727.15 | 235.81 | 59.45 | 109.97 | 0.00 | 0.00 |
| Maximum of Months | 134.10 | 1499.69 | 386.84 | 214.62 | 218.15 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ELEVATORCOREFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: EXERCISECENTERFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 61.65 | 187.95 | 93.76 | 54.63 | 39.13 | 0.00 | 0.00 |
| February | 65.69 | 183.44 | 107.16 | 51.59 | 55.57 | 0.00 | 0.00 |
| March | 108.81 | 131.55 | 128.95 | 71.54 | 57.41 | 0.00 | 0.00 |
| April | 98.69 | 102.68 | 109.65 | 44.50 | 65.15 | 0.00 | 0.00 |
| May | 96.06 | 67.47 | 94.89 | 27.51 | 67.38 | 0.00 | 0.00 |
| June | 109.98 | 41.36 | 92.53 | 19.82 | 72.72 | 0.00 | 0.00 |
| July | 129.24 | 26.95 | 93.89 | 22.55 | 71.34 | 0.00 | 0.00 |
| August | 140.08 | 36.32 | 104.80 | 33.34 | 71.46 | 0.00 | 0.00 |
| September | 149.07 | 60.82 | 124.44 | 61.37 | 63.07 | 0.00 | 0.00 |
| October | 114.61 | 98.70 | 117.95 | 67.51 | 50.44 | 0.00 | 0.00 |
| November | 68.65 | 131.08 | 84.48 | 47.83 | 36.66 | 0.00 | 0.00 |
| December | 47.41 | 186.09 | 78.60 | 40.69 | 37.91 | 0.00 | 0.00 |
| Annual Sum or Average | 99.36 | 104.11 | 102.55 | 45.21 | 57.35 | 0.00 | 0.00 |
| Minimum of Months | 47.41 | 26.95 | 78.60 | 19.82 | 36.66 | 0.00 | 0.00 |
| Maximum of Months | 149.07 | 187.95 | 128.95 | 71.54 | 72.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONTOFFICEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 253.25 | 725.18 | 375.05 | 218.51 | 156.54 | 0.00 | 0.00 |
| February | 273.18 | 705.77 | 428.63 | 206.35 | 222.27 | 0.00 | 0.00 |
| March | 444.02 | 513.39 | 515.78 | 286.16 | 229.62 | 0.00 | 0.00 |
| April | 402.84 | 404.14 | 438.60 | 177.98 | 260.62 | 0.00 | 0.00 |
| May | 391.80 | 270.32 | 379.55 | 110.03 | 269.52 | 0.00 | 0.00 |
| June | 445.78 | 164.48 | 370.13 | 79.27 | 290.86 | 0.00 | 0.00 |
| July | 520.63 | 105.62 | 375.56 | 90.21 | 285.35 | 0.00 | 0.00 |
| August | 564.40 | 144.21 | 419.21 | 133.37 | 285.85 | 0.00 | 0.00 |
| September | 601.16 | 245.11 | 497.75 | 245.49 | 252.26 | 0.00 | 0.00 |
| October | 463.84 | 397.55 | 471.78 | 270.03 | 201.76 | 0.00 | 0.00 |
| November | 278.51 | 521.39 | 337.93 | 191.30 | 146.63 | 0.00 | 0.00 |
| December | 195.71 | 718.25 | 314.41 | 162.75 | 151.66 | 0.00 | 0.00 |
| Annual Sum or Average | 403.68 | 408.02 | 410.21 | 180.83 | 229.38 | 0.00 | 0.00 |
| Minimum of Months | 195.71 | 105.62 | 314.41 | 79.27 | 146.63 | 0.00 | 0.00 |
| Maximum of Months | 601.16 | 725.18 | 515.78 | 286.16 | 290.86 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONTSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONTSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: REARSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDORFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.81 | 150.63 | 25.73 | 7.29 | 18.43 | 0.00 | 0.00 |
| February | 5.17 | 141.78 | 39.47 | 11.01 | 28.46 | 0.00 | 0.00 |
| March | 26.69 | 94.81 | 59.39 | 25.19 | 34.20 | 0.00 | 0.00 |
| April | 52.67 | 70.98 | 75.29 | 32.08 | 43.21 | 0.00 | 0.00 |
| May | 80.70 | 47.13 | 86.56 | 38.68 | 47.88 | 0.00 | 0.00 |
| June | 113.50 | 28.54 | 100.68 | 46.00 | 54.69 | 0.00 | 0.00 |
| July | 117.39 | 18.86 | 93.09 | 40.84 | 52.25 | 0.00 | 0.00 |
| August | 102.44 | 25.74 | 84.07 | 35.42 | 48.65 | 0.00 | 0.00 |
| September | 69.05 | 43.21 | 67.98 | 29.71 | 38.27 | 0.00 | 0.00 |
| October | 26.76 | 73.65 | 45.14 | 17.31 | 27.83 | 0.00 | 0.00 |
| November | 6.95 | 100.32 | 26.06 | 7.88 | 18.18 | 0.00 | 0.00 |
| December | 0.70 | 148.90 | 21.85 | 4.63 | 17.22 | 0.00 | 0.00 |
| Annual Sum or Average | 50.49 | 78.39 | 60.54 | 24.74 | 35.80 | 0.00 | 0.00 |
| Minimum of Months | 0.70 | 18.86 | 21.85 | 4.63 | 17.22 | 0.00 | 0.00 |
| Maximum of Months | 117.39 | 150.63 | 100.68 | 46.00 | 54.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: REARSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM201
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 182.04 | 21.94 | 0.00 | 21.94 | 0.00 | 0.00 |
| February | 0.37 | 171.65 | 33.42 | 0.00 | 33.42 | 0.00 | 0.00 |
| March | 9.08 | 124.35 | 40.54 | 0.00 | 40.54 | 0.00 | 0.00 |
| April | 20.48 | 89.12 | 51.68 | 0.25 | 51.43 | 0.00 | 0.00 |
| May | 37.96 | 58.11 | 60.04 | 2.59 | 57.45 | 0.00 | 0.00 |
| June | 66.06 | 38.63 | 72.18 | 6.14 | 66.04 | 0.00 | 0.00 |
| July | 74.72 | 27.32 | 67.22 | 4.57 | 62.65 | 0.00 | 0.00 |
| August | 60.47 | 36.91 | 58.20 | 1.12 | 57.08 | 0.00 | 0.00 |
| September | 32.99 | 58.86 | 44.11 | 0.02 | 44.09 | 0.00 | 0.00 |
| October | 10.76 | 91.23 | 32.96 | 0.00 | 32.96 | 0.00 | 0.00 |
| November | 2.79 | 116.01 | 22.15 | 0.00 | 22.15 | 0.00 | 0.00 |
| December | 0.09 | 172.41 | 20.53 | 0.00 | 20.53 | 0.00 | 0.00 |
| Annual Sum or Average | 26.48 | 96.84 | 43.79 | 1.23 | 42.56 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 27.32 | 20.53 | 0.00 | 20.53 | 0.00 | 0.00 |
| Maximum of Months | 74.72 | 182.04 | 72.18 | 6.14 | 66.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM202_205
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 827.27 | 87.74 | 0.00 | 87.74 | 0.00 | 0.00 |
| February | 0.68 | 785.72 | 133.69 | 0.00 | 133.69 | 0.00 | 0.00 |
| March | 32.88 | 552.28 | 162.15 | 0.01 | 162.15 | 0.00 | 0.00 |
| April | 77.12 | 374.92 | 206.72 | 1.00 | 205.72 | 0.00 | 0.00 |
| May | 157.27 | 223.30 | 240.14 | 10.34 | 229.80 | 0.00 | 0.00 |
| June | 289.93 | 134.44 | 288.72 | 24.55 | 264.17 | 0.00 | 0.00 |
| July | 337.21 | 84.58 | 268.90 | 18.29 | 250.60 | 0.00 | 0.00 |
| August | 268.99 | 120.20 | 232.80 | 4.49 | 228.31 | 0.00 | 0.00 |
| September | 141.61 | 217.93 | 176.44 | 0.08 | 176.37 | 0.00 | 0.00 |
| October | 40.57 | 374.93 | 131.84 | 0.00 | 131.84 | 0.00 | 0.00 |
| November | 9.33 | 505.99 | 88.59 | 0.00 | 88.59 | 0.00 | 0.00 |
| December | 0.21 | 783.22 | 82.13 | 0.00 | 82.13 | 0.00 | 0.00 |
| Annual Sum or Average | 113.72 | 413.53 | 175.16 | 4.92 | 170.24 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 84.58 | 82.13 | 0.00 | 82.13 | 0.00 | 0.00 |
| Maximum of Months | 337.21 | 827.27 | 288.72 | 24.55 | 264.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM206_208
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 615.26 | 63.48 | 0.00 | 63.48 | 0.00 | 0.00 |
| February | 0.38 | 584.43 | 96.73 | 0.00 | 96.73 | 0.00 | 0.00 |
| March | 22.47 | 412.41 | 117.32 | 0.00 | 117.31 | 0.00 | 0.00 |
| April | 53.04 | 279.38 | 149.56 | 0.72 | 148.84 | 0.00 | 0.00 |
| May | 112.10 | 164.60 | 173.74 | 7.48 | 166.26 | 0.00 | 0.00 |
| June | 210.41 | 97.43 | 208.89 | 17.76 | 191.13 | 0.00 | 0.00 |
| July | 246.01 | 60.50 | 194.55 | 13.23 | 181.31 | 0.00 | 0.00 |
| August | 196.10 | 86.44 | 168.43 | 3.25 | 165.18 | 0.00 | 0.00 |
| September | 102.37 | 159.10 | 127.66 | 0.06 | 127.60 | 0.00 | 0.00 |
| October | 27.90 | 278.50 | 95.39 | 0.00 | 95.39 | 0.00 | 0.00 |
| November | 6.15 | 378.53 | 64.10 | 0.00 | 64.10 | 0.00 | 0.00 |
| December | 0.12 | 582.48 | 59.42 | 0.00 | 59.42 | 0.00 | 0.00 |
| Annual Sum or Average | 81.96 | 306.86 | 126.73 | 3.56 | 123.17 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 60.50 | 59.42 | 0.00 | 59.42 | 0.00 | 0.00 |
| Maximum of Months | 246.01 | 615.26 | 208.89 | 17.76 | 191.13 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM209_212
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 851.32 | 87.74 | 0.00 | 87.74 | 0.00 | 0.00 |
| February | 0.48 | 807.88 | 133.69 | 0.00 | 133.69 | 0.00 | 0.00 |
| March | 30.97 | 569.59 | 162.15 | 0.01 | 162.15 | 0.00 | 0.00 |
| April | 73.32 | 384.94 | 206.72 | 1.00 | 205.72 | 0.00 | 0.00 |
| May | 156.88 | 224.62 | 240.14 | 10.34 | 229.80 | 0.00 | 0.00 |
| June | 294.41 | 132.03 | 288.72 | 24.55 | 264.17 | 0.00 | 0.00 |
| July | 344.04 | 81.14 | 268.90 | 18.29 | 250.60 | 0.00 | 0.00 |
| August | 273.73 | 116.84 | 232.80 | 4.49 | 228.31 | 0.00 | 0.00 |
| September | 142.15 | 218.59 | 176.44 | 0.08 | 176.37 | 0.00 | 0.00 |
| October | 37.88 | 386.58 | 131.84 | 0.00 | 131.84 | 0.00 | 0.00 |
| November | 8.10 | 527.54 | 88.59 | 0.00 | 88.59 | 0.00 | 0.00 |
| December | 0.14 | 807.63 | 82.13 | 0.00 | 82.13 | 0.00 | 0.00 |
| Annual Sum or Average | 114.26 | 423.79 | 175.16 | 4.92 | 170.24 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 81.14 | 82.13 | 0.00 | 82.13 | 0.00 | 0.00 |
| Maximum of Months | 344.04 | 851.32 | 288.72 | 24.55 | 264.17 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM213
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 203.26 | 21.94 | 0.00 | 21.94 | 0.00 | 0.00 |
| February | 0.26 | 192.13 | 33.42 | 0.00 | 33.42 | 0.00 | 0.00 |
| March | 9.04 | 134.66 | 40.54 | 0.00 | 40.54 | 0.00 | 0.00 |
| April | 21.16 | 90.96 | 51.68 | 0.25 | 51.43 | 0.00 | 0.00 |
| May | 41.53 | 53.54 | 60.04 | 2.59 | 57.45 | 0.00 | 0.00 |
| June | 75.04 | 31.76 | 72.18 | 6.14 | 66.04 | 0.00 | 0.00 |
| July | 86.70 | 19.60 | 67.22 | 4.57 | 62.65 | 0.00 | 0.00 |
| August | 69.20 | 28.32 | 58.20 | 1.12 | 57.08 | 0.00 | 0.00 |
| September | 36.81 | 52.38 | 44.11 | 0.02 | 44.09 | 0.00 | 0.00 |
| October | 11.08 | 91.61 | 32.96 | 0.00 | 32.96 | 0.00 | 0.00 |
| November | 2.63 | 123.43 | 22.15 | 0.00 | 22.15 | 0.00 | 0.00 |
| December | 0.07 | 191.86 | 20.53 | 0.00 | 20.53 | 0.00 | 0.00 |
| Annual Sum or Average | 29.65 | 100.67 | 43.79 | 1.23 | 42.56 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 19.60 | 20.53 | 0.00 | 20.53 | 0.00 | 0.00 |
| Maximum of Months | 86.70 | 203.26 | 72.18 | 6.14 | 66.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM214
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 61.68 | 183.87 | 94.07 | 54.80 | 39.26 | 0.00 | 0.00 |
| February | 66.01 | 179.46 | 107.50 | 51.76 | 55.75 | 0.00 | 0.00 |
| March | 108.37 | 128.61 | 129.36 | 71.77 | 57.59 | 0.00 | 0.00 |
| April | 99.06 | 99.06 | 110.00 | 44.64 | 65.37 | 0.00 | 0.00 |
| May | 96.64 | 63.74 | 95.20 | 27.60 | 67.60 | 0.00 | 0.00 |
| June | 110.43 | 38.46 | 92.83 | 19.88 | 72.95 | 0.00 | 0.00 |
| July | 129.98 | 23.65 | 94.19 | 22.63 | 71.57 | 0.00 | 0.00 |
| August | 140.65 | 32.49 | 105.14 | 33.45 | 71.69 | 0.00 | 0.00 |
| September | 149.69 | 56.36 | 124.84 | 61.57 | 63.27 | 0.00 | 0.00 |
| October | 115.77 | 92.10 | 118.33 | 67.73 | 50.60 | 0.00 | 0.00 |
| November | 69.27 | 124.47 | 84.76 | 47.98 | 36.78 | 0.00 | 0.00 |
| December | 47.60 | 180.98 | 78.86 | 40.82 | 38.04 | 0.00 | 0.00 |
| Annual Sum or Average | 99.79 | 99.85 | 102.88 | 45.35 | 57.53 | 0.00 | 0.00 |
| Minimum of Months | 47.60 | 23.65 | 78.86 | 19.88 | 36.78 | 0.00 | 0.00 |
| Maximum of Months | 149.69 | 183.87 | 129.36 | 71.77 | 72.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM215_218
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 213.22 | 960.22 | 376.26 | 219.22 | 157.05 | 0.00 | 0.00 |
| February | 219.74 | 934.99 | 430.01 | 207.02 | 222.99 | 0.00 | 0.00 |
| March | 372.66 | 693.93 | 517.45 | 287.09 | 230.36 | 0.00 | 0.00 |
| April | 334.74 | 564.89 | 440.02 | 178.56 | 261.46 | 0.00 | 0.00 |
| May | 320.36 | 400.84 | 380.78 | 110.39 | 270.39 | 0.00 | 0.00 |
| June | 355.75 | 262.93 | 371.33 | 79.53 | 291.80 | 0.00 | 0.00 |
| July | 425.16 | 191.42 | 376.78 | 90.50 | 286.28 | 0.00 | 0.00 |
| August | 479.82 | 238.77 | 420.57 | 133.80 | 286.77 | 0.00 | 0.00 |
| September | 530.24 | 355.73 | 499.37 | 246.29 | 253.08 | 0.00 | 0.00 |
| October | 406.26 | 532.05 | 473.31 | 270.90 | 202.41 | 0.00 | 0.00 |
| November | 240.47 | 697.01 | 339.02 | 191.92 | 147.10 | 0.00 | 0.00 |
| December | 162.99 | 955.64 | 315.42 | 163.27 | 152.15 | 0.00 | 0.00 |
| Annual Sum or Average | 339.13 | 563.71 | 411.54 | 181.41 | 230.12 | 0.00 | 0.00 |
| Minimum of Months | 162.99 | 191.42 | 315.42 | 79.53 | 147.10 | 0.00 | 0.00 |
| Maximum of Months | 530.24 | 960.22 | 517.45 | 287.09 | 291.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ELEVATORCOREFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM219
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 53.85 | 228.13 | 94.07 | 54.80 | 39.26 | 0.00 | 0.00 |
| February | 55.34 | 222.55 | 107.50 | 51.76 | 55.75 | 0.00 | 0.00 |
| March | 94.05 | 162.29 | 129.36 | 71.77 | 57.59 | 0.00 | 0.00 |
| April | 84.78 | 131.00 | 110.00 | 44.64 | 65.37 | 0.00 | 0.00 |
| May | 80.93 | 95.10 | 95.20 | 27.60 | 67.60 | 0.00 | 0.00 |
| June | 89.96 | 63.92 | 92.83 | 19.88 | 72.95 | 0.00 | 0.00 |
| July | 107.92 | 45.17 | 94.19 | 22.63 | 71.57 | 0.00 | 0.00 |
| August | 121.27 | 57.20 | 105.14 | 33.45 | 71.69 | 0.00 | 0.00 |
| September | 133.57 | 86.17 | 124.84 | 61.57 | 63.27 | 0.00 | 0.00 |
| October | 102.50 | 124.51 | 118.33 | 67.73 | 50.60 | 0.00 | 0.00 |
| November | 60.85 | 163.43 | 84.76 | 47.98 | 36.78 | 0.00 | 0.00 |
| December | 41.06 | 226.93 | 78.86 | 40.82 | 38.04 | 0.00 | 0.00 |
| Annual Sum or Average | 85.68 | 133.39 | 102.88 | 45.35 | 57.53 | 0.00 | 0.00 |
| Minimum of Months | 41.06 | 45.17 | 78.86 | 19.88 | 36.78 | 0.00 | 0.00 |
| Maximum of Months | 133.57 | 228.13 | 129.36 | 71.77 | 72.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM220_223
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 245.28 | 739.92 | 376.26 | 219.22 | 157.05 | 0.00 | 0.00 |
| February | 261.88 | 723.91 | 430.01 | 207.02 | 222.99 | 0.00 | 0.00 |
| March | 433.42 | 515.69 | 517.45 | 287.09 | 230.36 | 0.00 | 0.00 |
| April | 397.43 | 395.46 | 440.02 | 178.56 | 261.46 | 0.00 | 0.00 |
| May | 389.33 | 252.60 | 380.78 | 110.39 | 270.39 | 0.00 | 0.00 |
| June | 447.03 | 150.09 | 371.33 | 79.53 | 291.80 | 0.00 | 0.00 |
| July | 527.22 | 90.50 | 376.78 | 90.50 | 286.28 | 0.00 | 0.00 |
| August | 568.96 | 124.93 | 420.57 | 133.80 | 286.77 | 0.00 | 0.00 |
| September | 603.13 | 221.09 | 499.37 | 246.29 | 253.08 | 0.00 | 0.00 |
| October | 465.28 | 366.47 | 473.31 | 270.90 | 202.41 | 0.00 | 0.00 |
| November | 277.96 | 497.63 | 339.02 | 191.92 | 147.10 | 0.00 | 0.00 |
| December | 189.62 | 727.84 | 315.42 | 163.27 | 152.15 | 0.00 | 0.00 |
| Annual Sum or Average | 401.35 | 398.78 | 411.54 | 181.41 | 230.12 | 0.00 | 0.00 |
| Minimum of Months | 189.62 | 90.50 | 315.42 | 79.53 | 147.10 | 0.00 | 0.00 |
| Maximum of Months | 603.13 | 739.92 | 517.45 | 287.09 | 291.80 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM224
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 62.28 | 180.57 | 94.07 | 54.80 | 39.26 | 0.00 | 0.00 |
| February | 66.86 | 176.68 | 107.50 | 51.76 | 55.75 | 0.00 | 0.00 |
| March | 109.19 | 126.82 | 129.36 | 71.77 | 57.59 | 0.00 | 0.00 |
| April | 99.66 | 97.73 | 110.00 | 44.64 | 65.37 | 0.00 | 0.00 |
| May | 97.02 | 62.73 | 95.20 | 27.60 | 67.60 | 0.00 | 0.00 |
| June | 110.90 | 37.59 | 92.83 | 19.88 | 72.95 | 0.00 | 0.00 |
| July | 130.45 | 23.00 | 94.19 | 22.63 | 71.57 | 0.00 | 0.00 |
| August | 141.02 | 31.77 | 105.14 | 33.45 | 71.69 | 0.00 | 0.00 |
| September | 149.92 | 55.52 | 124.84 | 61.57 | 63.27 | 0.00 | 0.00 |
| October | 116.08 | 91.11 | 118.33 | 67.73 | 50.60 | 0.00 | 0.00 |
| November | 69.69 | 122.71 | 84.76 | 47.98 | 36.78 | 0.00 | 0.00 |
| December | 48.18 | 177.61 | 78.86 | 40.82 | 38.04 | 0.00 | 0.00 |
| Annual Sum or Average | 100.30 | 98.23 | 102.88 | 45.35 | 57.53 | 0.00 | 0.00 |
| Minimum of Months | 48.18 | 23.00 | 78.86 | 19.88 | 36.78 | 0.00 | 0.00 |
| Maximum of Months | 149.92 | 180.57 | 129.36 | 71.77 | 72.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONTSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONTSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: REARSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDORFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.04 | 143.37 | 25.73 | 7.29 | 18.43 | 0.00 | 0.00 |
| February | 5.71 | 135.39 | 39.47 | 11.01 | 28.46 | 0.00 | 0.00 |
| March | 29.02 | 88.33 | 59.39 | 25.19 | 34.20 | 0.00 | 0.00 |
| April | 56.26 | 64.88 | 75.29 | 32.08 | 43.21 | 0.00 | 0.00 |
| May | 82.96 | 44.34 | 86.56 | 38.68 | 47.88 | 0.00 | 0.00 |
| June | 114.92 | 27.48 | 100.68 | 46.00 | 54.69 | 0.00 | 0.00 |
| July | 118.55 | 18.04 | 93.09 | 40.84 | 52.25 | 0.00 | 0.00 |
| August | 103.68 | 24.63 | 84.07 | 35.42 | 48.65 | 0.00 | 0.00 |
| September | 70.76 | 40.88 | 67.98 | 29.71 | 38.27 | 0.00 | 0.00 |
| October | 29.59 | 66.27 | 45.14 | 17.31 | 27.83 | 0.00 | 0.00 |
| November | 8.52 | 89.79 | 26.06 | 7.88 | 18.18 | 0.00 | 0.00 |
| December | 0.91 | 140.94 | 21.85 | 4.63 | 17.22 | 0.00 | 0.00 |
| Annual Sum or Average | 52.09 | 73.39 | 60.54 | 24.74 | 35.80 | 0.00 | 0.00 |
| Minimum of Months | 0.91 | 18.04 | 21.85 | 4.63 | 17.22 | 0.00 | 0.00 |
| Maximum of Months | 118.55 | 143.37 | 100.68 | 46.00 | 54.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: REARSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM301
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 170.09 | 21.89 | 0.00 | 21.89 | 0.00 | 0.00 |
| February | 0.65 | 160.50 | 33.36 | 0.00 | 33.36 | 0.00 | 0.00 |
| March | 10.72 | 114.50 | 40.46 | 0.00 | 40.46 | 0.00 | 0.00 |
| April | 23.20 | 82.58 | 51.58 | 0.25 | 51.33 | 0.00 | 0.00 |
| May | 40.33 | 55.51 | 59.92 | 2.58 | 57.34 | 0.00 | 0.00 |
| June | 67.76 | 37.84 | 72.04 | 6.13 | 65.92 | 0.00 | 0.00 |
| July | 75.96 | 26.87 | 67.10 | 4.56 | 62.53 | 0.00 | 0.00 |
| August | 62.21 | 35.65 | 58.09 | 1.12 | 56.97 | 0.00 | 0.00 |
| September | 35.43 | 55.06 | 44.03 | 0.02 | 44.01 | 0.00 | 0.00 |
| October | 13.25 | 82.08 | 32.90 | 0.00 | 32.90 | 0.00 | 0.00 |
| November | 3.81 | 102.41 | 22.11 | 0.00 | 22.11 | 0.00 | 0.00 |
| December | 0.18 | 159.68 | 20.49 | 0.00 | 20.49 | 0.00 | 0.00 |
| Annual Sum or Average | 27.96 | 89.88 | 43.71 | 1.23 | 42.48 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 26.87 | 20.49 | 0.00 | 20.49 | 0.00 | 0.00 |
| Maximum of Months | 75.96 | 170.09 | 72.04 | 6.13 | 65.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM302_305
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 692.43 | 87.58 | 0.00 | 87.58 | 0.00 | 0.00 |
| February | 2.20 | 655.25 | 133.44 | 0.00 | 133.44 | 0.00 | 0.00 |
| March | 42.05 | 471.39 | 161.85 | 0.01 | 161.84 | 0.00 | 0.00 |
| April | 93.00 | 340.50 | 206.33 | 0.99 | 205.33 | 0.00 | 0.00 |
| May | 162.05 | 228.65 | 239.69 | 10.32 | 229.37 | 0.00 | 0.00 |
| June | 272.30 | 155.41 | 288.17 | 24.50 | 263.67 | 0.00 | 0.00 |
| July | 306.02 | 110.33 | 268.39 | 18.26 | 250.13 | 0.00 | 0.00 |
| August | 250.77 | 145.88 | 232.36 | 4.49 | 227.88 | 0.00 | 0.00 |
| September | 143.69 | 224.72 | 176.11 | 0.08 | 176.03 | 0.00 | 0.00 |
| October | 53.19 | 336.41 | 131.59 | 0.00 | 131.59 | 0.00 | 0.00 |
| November | 14.82 | 423.53 | 88.42 | 0.00 | 88.42 | 0.00 | 0.00 |
| December | 0.61 | 653.07 | 81.97 | 0.00 | 81.97 | 0.00 | 0.00 |
| Annual Sum or Average | 112.41 | 368.37 | 174.83 | 4.91 | 169.92 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 110.33 | 81.97 | 0.00 | 81.97 | 0.00 | 0.00 |
| Maximum of Months | 306.02 | 692.43 | 288.17 | 24.50 | 263.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM306_308
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 520.87 | 63.40 | 0.00 | 63.40 | 0.00 | 0.00 |
| February | 1.25 | 492.69 | 96.60 | 0.00 | 96.60 | 0.00 | 0.00 |
| March | 28.40 | 356.35 | 117.17 | 0.00 | 117.16 | 0.00 | 0.00 |
| April | 63.99 | 256.41 | 149.37 | 0.72 | 148.65 | 0.00 | 0.00 |
| May | 115.47 | 168.96 | 173.52 | 7.47 | 166.05 | 0.00 | 0.00 |
| June | 198.16 | 112.39 | 208.62 | 17.74 | 190.88 | 0.00 | 0.00 |
| July | 224.13 | 78.42 | 194.29 | 13.22 | 181.08 | 0.00 | 0.00 |
| August | 183.24 | 104.61 | 168.21 | 3.25 | 164.97 | 0.00 | 0.00 |
| September | 103.47 | 164.85 | 127.49 | 0.06 | 127.43 | 0.00 | 0.00 |
| October | 36.30 | 253.05 | 95.26 | 0.00 | 95.26 | 0.00 | 0.00 |
| November | 9.59 | 322.17 | 64.01 | 0.00 | 64.01 | 0.00 | 0.00 |
| December | 0.35 | 490.95 | 59.34 | 0.00 | 59.34 | 0.00 | 0.00 |
| Annual Sum or Average | 80.87 | 275.73 | 126.57 | 3.56 | 123.01 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 78.42 | 59.34 | 0.00 | 59.34 | 0.00 | 0.00 |
| Maximum of Months | 224.13 | 520.87 | 208.62 | 17.74 | 190.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM309_312
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 833.64 | 87.58 | 0.00 | 87.58 | 0.00 | 0.00 |
| February | 0.61 | 793.20 | 133.44 | 0.00 | 133.44 | 0.00 | 0.00 |
| March | 32.20 | 558.71 | 161.85 | 0.01 | 161.84 | 0.00 | 0.00 |
| April | 75.97 | 378.77 | 206.33 | 0.99 | 205.33 | 0.00 | 0.00 |
| May | 158.51 | 222.90 | 239.69 | 10.32 | 229.37 | 0.00 | 0.00 |
| June | 295.50 | 131.78 | 288.17 | 24.50 | 263.67 | 0.00 | 0.00 |
| July | 345.29 | 80.53 | 268.39 | 18.26 | 250.13 | 0.00 | 0.00 |
| August | 276.01 | 114.88 | 232.36 | 4.49 | 227.88 | 0.00 | 0.00 |
| September | 145.49 | 213.41 | 176.11 | 0.08 | 176.03 | 0.00 | 0.00 |
| October | 41.56 | 373.33 | 131.59 | 0.00 | 131.59 | 0.00 | 0.00 |
| November | 9.17 | 506.59 | 88.42 | 0.00 | 88.42 | 0.00 | 0.00 |
| December | 0.21 | 787.56 | 81.97 | 0.00 | 81.97 | 0.00 | 0.00 |
| Annual Sum or Average | 115.80 | 414.37 | 174.83 | 4.91 | 169.92 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 80.53 | 81.97 | 0.00 | 81.97 | 0.00 | 0.00 |
| Maximum of Months | 345.29 | 833.64 | 288.17 | 24.50 | 263.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM313
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 172.47 | 21.89 | 0.00 | 21.89 | 0.00 | 0.00 |
| February | 0.66 | 161.93 | 33.36 | 0.00 | 33.36 | 0.00 | 0.00 |
| March | 10.73 | 116.69 | 40.46 | 0.00 | 40.46 | 0.00 | 0.00 |
| April | 23.90 | 83.74 | 51.58 | 0.25 | 51.33 | 0.00 | 0.00 |
| May | 41.93 | 55.44 | 59.92 | 2.58 | 57.34 | 0.00 | 0.00 |
| June | 70.49 | 37.10 | 72.04 | 6.13 | 65.92 | 0.00 | 0.00 |
| July | 78.71 | 26.03 | 67.10 | 4.56 | 62.53 | 0.00 | 0.00 |
| August | 64.28 | 34.99 | 58.09 | 1.12 | 56.97 | 0.00 | 0.00 |
| September | 36.62 | 55.14 | 44.03 | 0.02 | 44.01 | 0.00 | 0.00 |
| October | 13.41 | 84.06 | 32.90 | 0.00 | 32.90 | 0.00 | 0.00 |
| November | 3.67 | 106.07 | 22.11 | 0.00 | 22.11 | 0.00 | 0.00 |
| December | 0.17 | 162.23 | 20.49 | 0.00 | 20.49 | 0.00 | 0.00 |
| Annual Sum or Average | 28.89 | 90.97 | 43.71 | 1.23 | 42.48 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 26.03 | 20.49 | 0.00 | 20.49 | 0.00 | 0.00 |
| Maximum of Months | 78.71 | 172.47 | 72.04 | 6.13 | 65.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM314
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 63.42 | 175.17 | 93.89 | 54.70 | 39.19 | 0.00 | 0.00 |
| February | 68.30 | 172.04 | 107.30 | 51.66 | 55.64 | 0.00 | 0.00 |
| March | 110.89 | 123.56 | 129.12 | 71.64 | 57.48 | 0.00 | 0.00 |
| April | 100.92 | 95.41 | 109.80 | 44.55 | 65.24 | 0.00 | 0.00 |
| May | 97.49 | 62.06 | 95.01 | 27.55 | 67.47 | 0.00 | 0.00 |
| June | 110.80 | 37.81 | 92.66 | 19.84 | 72.81 | 0.00 | 0.00 |
| July | 130.07 | 23.29 | 94.02 | 22.58 | 71.43 | 0.00 | 0.00 |
| August | 140.97 | 31.74 | 104.94 | 33.39 | 71.56 | 0.00 | 0.00 |
| September | 150.43 | 54.51 | 124.60 | 61.46 | 63.15 | 0.00 | 0.00 |
| October | 117.60 | 87.81 | 118.10 | 67.60 | 50.51 | 0.00 | 0.00 |
| November | 71.08 | 117.09 | 84.60 | 47.89 | 36.71 | 0.00 | 0.00 |
| December | 49.19 | 171.74 | 78.71 | 40.74 | 37.97 | 0.00 | 0.00 |
| Annual Sum or Average | 101.12 | 95.61 | 102.69 | 45.27 | 57.42 | 0.00 | 0.00 |
| Minimum of Months | 49.19 | 23.29 | 78.71 | 19.84 | 36.71 | 0.00 | 0.00 |
| Maximum of Months | 150.43 | 175.17 | 129.12 | 71.64 | 72.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM315_318
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 239.67 | 763.34 | 375.55 | 218.80 | 156.75 | 0.00 | 0.00 |
| February | 253.64 | 747.01 | 429.20 | 206.63 | 222.57 | 0.00 | 0.00 |
| March | 423.49 | 532.54 | 516.47 | 286.55 | 229.93 | 0.00 | 0.00 |
| April | 388.24 | 411.00 | 439.18 | 178.22 | 260.96 | 0.00 | 0.00 |
| May | 378.91 | 268.31 | 380.06 | 110.18 | 269.88 | 0.00 | 0.00 |
| June | 433.12 | 164.02 | 370.63 | 79.38 | 291.25 | 0.00 | 0.00 |
| July | 511.64 | 101.92 | 376.06 | 90.33 | 285.73 | 0.00 | 0.00 |
| August | 555.94 | 137.88 | 419.77 | 133.54 | 286.23 | 0.00 | 0.00 |
| September | 593.17 | 235.35 | 498.42 | 245.82 | 252.60 | 0.00 | 0.00 |
| October | 458.35 | 378.48 | 472.41 | 270.39 | 202.03 | 0.00 | 0.00 |
| November | 273.15 | 511.67 | 338.38 | 191.56 | 146.82 | 0.00 | 0.00 |
| December | 184.73 | 750.58 | 314.83 | 162.96 | 151.86 | 0.00 | 0.00 |
| Annual Sum or Average | 391.96 | 415.07 | 410.75 | 181.07 | 229.69 | 0.00 | 0.00 |
| Minimum of Months | 184.73 | 101.92 | 314.83 | 79.38 | 146.82 | 0.00 | 0.00 |
| Maximum of Months | 593.17 | 763.34 | 516.47 | 286.55 | 291.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ELEVATORCOREFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM319
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 59.47 | 193.01 | 93.89 | 54.70 | 39.19 | 0.00 | 0.00 |
| February | 62.88 | 188.44 | 107.30 | 51.66 | 55.64 | 0.00 | 0.00 |
| March | 103.46 | 140.70 | 129.12 | 71.64 | 57.48 | 0.00 | 0.00 |
| April | 93.67 | 112.84 | 109.80 | 44.55 | 65.24 | 0.00 | 0.00 |
| May | 89.30 | 79.62 | 95.01 | 27.55 | 67.47 | 0.00 | 0.00 |
| June | 99.58 | 51.91 | 92.66 | 19.84 | 72.81 | 0.00 | 0.00 |
| July | 117.34 | 35.41 | 94.02 | 22.58 | 71.43 | 0.00 | 0.00 |
| August | 129.89 | 45.75 | 104.94 | 33.39 | 71.56 | 0.00 | 0.00 |
| September | 141.33 | 71.43 | 124.60 | 61.46 | 63.15 | 0.00 | 0.00 |
| October | 110.62 | 106.09 | 118.10 | 67.60 | 50.51 | 0.00 | 0.00 |
| November | 66.54 | 136.15 | 84.60 | 47.89 | 36.71 | 0.00 | 0.00 |
| December | 45.78 | 189.70 | 78.71 | 40.74 | 37.97 | 0.00 | 0.00 |
| Annual Sum or Average | 93.50 | 112.18 | 102.69 | 45.27 | 57.42 | 0.00 | 0.00 |
| Minimum of Months | 45.78 | 35.41 | 78.71 | 19.84 | 36.71 | 0.00 | 0.00 |
| Maximum of Months | 141.33 | 193.01 | 129.12 | 71.64 | 72.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM320_323
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 247.24 | 724.75 | 375.55 | 218.80 | 156.75 | 0.00 | 0.00 |
| February | 264.49 | 711.36 | 429.20 | 206.63 | 222.57 | 0.00 | 0.00 |
| March | 435.79 | 507.12 | 516.47 | 286.55 | 229.93 | 0.00 | 0.00 |
| April | 399.88 | 388.01 | 439.18 | 178.22 | 260.96 | 0.00 | 0.00 |
| May | 390.99 | 248.16 | 380.06 | 110.18 | 269.88 | 0.00 | 0.00 |
| June | 448.22 | 148.07 | 370.63 | 79.38 | 291.25 | 0.00 | 0.00 |
| July | 528.32 | 88.81 | 376.06 | 90.33 | 285.73 | 0.00 | 0.00 |
| August | 570.30 | 122.11 | 419.77 | 133.54 | 286.23 | 0.00 | 0.00 |
| September | 604.88 | 215.93 | 498.42 | 245.82 | 252.60 | 0.00 | 0.00 |
| October | 468.76 | 355.83 | 472.41 | 270.39 | 202.03 | 0.00 | 0.00 |
| November | 280.97 | 481.19 | 338.38 | 191.56 | 146.82 | 0.00 | 0.00 |
| December | 191.52 | 710.58 | 314.83 | 162.96 | 151.86 | 0.00 | 0.00 |
| Annual Sum or Average | 403.41 | 390.12 | 410.75 | 181.07 | 229.69 | 0.00 | 0.00 |
| Minimum of Months | 191.52 | 88.81 | 314.83 | 79.38 | 146.82 | 0.00 | 0.00 |
| Maximum of Months | 604.88 | 724.75 | 516.47 | 286.55 | 291.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM324
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 64.45 | 164.68 | 93.89 | 54.70 | 39.19 | 0.00 | 0.00 |
| February | 69.87 | 160.73 | 107.30 | 51.66 | 55.64 | 0.00 | 0.00 |
| March | 111.18 | 121.33 | 129.12 | 71.64 | 57.48 | 0.00 | 0.00 |
| April | 100.60 | 96.61 | 109.80 | 44.55 | 65.24 | 0.00 | 0.00 |
| May | 95.86 | 66.74 | 95.01 | 27.55 | 67.47 | 0.00 | 0.00 |
| June | 106.37 | 43.26 | 92.66 | 19.84 | 72.81 | 0.00 | 0.00 |
| July | 123.00 | 29.31 | 94.02 | 22.58 | 71.43 | 0.00 | 0.00 |
| August | 135.02 | 38.62 | 104.94 | 33.39 | 71.56 | 0.00 | 0.00 |
| September | 146.59 | 61.21 | 124.60 | 61.46 | 63.15 | 0.00 | 0.00 |
| October | 116.52 | 91.11 | 118.10 | 67.60 | 50.51 | 0.00 | 0.00 |
| November | 71.24 | 115.79 | 84.60 | 47.89 | 36.71 | 0.00 | 0.00 |
| December | 50.17 | 160.76 | 78.71 | 40.74 | 37.97 | 0.00 | 0.00 |
| Annual Sum or Average | 99.40 | 95.49 | 102.69 | 45.27 | 57.42 | 0.00 | 0.00 |
| Minimum of Months | 50.17 | 29.31 | 78.71 | 19.84 | 36.71 | 0.00 | 0.00 |
| Maximum of Months | 146.59 | 164.68 | 129.12 | 71.64 | 72.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONTSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONTSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: REARSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORRIDORFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 1.14 | 138.53 | 25.73 | 7.29 | 18.43 | 0.00 | 0.00 |
| February | 5.85 | 130.98 | 39.47 | 11.01 | 28.46 | 0.00 | 0.00 |
| March | 29.20 | 84.24 | 59.39 | 25.19 | 34.20 | 0.00 | 0.00 |
| April | 55.88 | 60.49 | 75.29 | 32.08 | 43.21 | 0.00 | 0.00 |
| May | 82.32 | 40.10 | 86.56 | 38.68 | 47.88 | 0.00 | 0.00 |
| June | 113.77 | 25.18 | 100.68 | 46.00 | 54.69 | 0.00 | 0.00 |
| July | 117.13 | 16.57 | 93.09 | 40.84 | 52.25 | 0.00 | 0.00 |
| August | 102.58 | 22.66 | 84.07 | 35.42 | 48.65 | 0.00 | 0.00 |
| September | 70.49 | 37.11 | 67.98 | 29.71 | 38.27 | 0.00 | 0.00 |
| October | 29.94 | 60.94 | 45.14 | 17.31 | 27.83 | 0.00 | 0.00 |
| November | 8.78 | 84.56 | 26.06 | 7.88 | 18.18 | 0.00 | 0.00 |
| December | 0.97 | 136.04 | 21.85 | 4.63 | 17.22 | 0.00 | 0.00 |
| Annual Sum or Average | 51.76 | 69.48 | 60.54 | 24.74 | 35.80 | 0.00 | 0.00 |
| Minimum of Months | 0.97 | 16.57 | 21.85 | 4.63 | 17.22 | 0.00 | 0.00 |
| Maximum of Months | 117.13 | 138.53 | 100.68 | 46.00 | 54.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: REARSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM401
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 194.97 | 21.89 | 0.00 | 21.89 | 0.00 | 0.00 |
| February | 0.28 | 185.48 | 33.36 | 0.00 | 33.36 | 0.00 | 0.00 |
| March | 8.99 | 128.54 | 40.46 | 0.00 | 40.46 | 0.00 | 0.00 |
| April | 19.35 | 85.97 | 51.58 | 0.25 | 51.33 | 0.00 | 0.00 |
| May | 37.28 | 50.50 | 59.92 | 2.58 | 57.34 | 0.00 | 0.00 |
| June | 69.57 | 30.04 | 72.04 | 6.13 | 65.92 | 0.00 | 0.00 |
| July | 81.64 | 18.21 | 67.10 | 4.56 | 62.53 | 0.00 | 0.00 |
| August | 65.18 | 26.19 | 58.09 | 1.12 | 56.97 | 0.00 | 0.00 |
| September | 34.42 | 48.52 | 44.03 | 0.02 | 44.01 | 0.00 | 0.00 |
| October | 11.37 | 83.33 | 32.90 | 0.00 | 32.90 | 0.00 | 0.00 |
| November | 2.98 | 112.11 | 22.11 | 0.00 | 22.11 | 0.00 | 0.00 |
| December | 0.11 | 183.02 | 20.49 | 0.00 | 20.49 | 0.00 | 0.00 |
| Annual Sum or Average | 27.78 | 95.12 | 43.71 | 1.23 | 42.48 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 18.21 | 20.49 | 0.00 | 20.49 | 0.00 | 0.00 |
| Maximum of Months | 81.64 | 194.97 | 72.04 | 6.13 | 65.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM402_405
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.03 | 637.50 | 87.58 | 0.00 | 87.58 | 0.00 | 0.00 |
| February | 2.74 | 603.40 | 133.44 | 0.00 | 133.44 | 0.00 | 0.00 |
| March | 41.21 | 420.08 | 161.85 | 0.01 | 161.84 | 0.00 | 0.00 |
| April | 85.95 | 290.18 | 206.33 | 0.99 | 205.33 | 0.00 | 0.00 |
| May | 145.70 | 194.69 | 239.69 | 10.32 | 229.37 | 0.00 | 0.00 |
| June | 251.64 | 134.11 | 288.17 | 24.50 | 263.67 | 0.00 | 0.00 |
| July | 285.23 | 95.14 | 268.39 | 18.26 | 250.13 | 0.00 | 0.00 |
| August | 231.47 | 125.23 | 232.36 | 4.49 | 227.88 | 0.00 | 0.00 |
| September | 130.81 | 191.53 | 176.11 | 0.08 | 176.03 | 0.00 | 0.00 |
| October | 52.17 | 283.35 | 131.59 | 0.00 | 131.59 | 0.00 | 0.00 |
| November | 15.70 | 356.83 | 88.42 | 0.00 | 88.42 | 0.00 | 0.00 |
| December | 0.86 | 594.69 | 81.97 | 0.00 | 81.97 | 0.00 | 0.00 |
| Annual Sum or Average | 104.26 | 325.88 | 174.83 | 4.91 | 169.92 | 0.00 | 0.00 |
| Minimum of Months | 0.03 | 95.14 | 81.97 | 0.00 | 81.97 | 0.00 | 0.00 |
| Maximum of Months | 285.23 | 637.50 | 288.17 | 24.50 | 263.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM406_408
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 470.49 | 63.40 | 0.00 | 63.40 | 0.00 | 0.00 |
| February | 1.65 | 445.38 | 96.60 | 0.00 | 96.60 | 0.00 | 0.00 |
| March | 28.34 | 312.96 | 117.17 | 0.00 | 117.16 | 0.00 | 0.00 |
| April | 59.84 | 217.99 | 149.37 | 0.72 | 148.65 | 0.00 | 0.00 |
| May | 104.47 | 144.46 | 173.52 | 7.47 | 166.05 | 0.00 | 0.00 |
| June | 182.99 | 97.93 | 208.62 | 17.74 | 190.88 | 0.00 | 0.00 |
| July | 208.16 | 68.68 | 194.29 | 13.22 | 181.08 | 0.00 | 0.00 |
| August | 168.73 | 90.96 | 168.21 | 3.25 | 164.97 | 0.00 | 0.00 |
| September | 94.50 | 141.49 | 127.49 | 0.06 | 127.43 | 0.00 | 0.00 |
| October | 36.06 | 213.14 | 95.26 | 0.00 | 95.26 | 0.00 | 0.00 |
| November | 10.34 | 269.32 | 64.01 | 0.00 | 64.01 | 0.00 | 0.00 |
| December | 0.51 | 439.38 | 59.34 | 0.00 | 59.34 | 0.00 | 0.00 |
| Annual Sum or Average | 75.10 | 241.68 | 126.57 | 3.56 | 123.01 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 68.68 | 59.34 | 0.00 | 59.34 | 0.00 | 0.00 |
| Maximum of Months | 208.16 | 470.49 | 208.62 | 17.74 | 190.88 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM409_412
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 801.26 | 87.58 | 0.00 | 87.58 | 0.00 | 0.00 |
| February | 0.60 | 763.62 | 133.44 | 0.00 | 133.44 | 0.00 | 0.00 |
| March | 30.27 | 536.29 | 161.85 | 0.01 | 161.84 | 0.00 | 0.00 |
| April | 68.25 | 359.11 | 206.33 | 0.99 | 205.33 | 0.00 | 0.00 |
| May | 144.41 | 207.69 | 239.69 | 10.32 | 229.37 | 0.00 | 0.00 |
| June | 277.80 | 120.13 | 288.17 | 24.50 | 263.67 | 0.00 | 0.00 |
| July | 328.46 | 71.53 | 268.39 | 18.26 | 250.13 | 0.00 | 0.00 |
| August | 260.92 | 104.05 | 232.36 | 4.49 | 227.88 | 0.00 | 0.00 |
| September | 135.23 | 199.61 | 176.11 | 0.08 | 176.03 | 0.00 | 0.00 |
| October | 38.40 | 352.09 | 131.59 | 0.00 | 131.59 | 0.00 | 0.00 |
| November | 8.61 | 477.58 | 88.42 | 0.00 | 88.42 | 0.00 | 0.00 |
| December | 0.22 | 755.05 | 81.97 | 0.00 | 81.97 | 0.00 | 0.00 |
| Annual Sum or Average | 108.48 | 393.81 | 174.83 | 4.91 | 169.92 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 71.53 | 81.97 | 0.00 | 81.97 | 0.00 | 0.00 |
| Maximum of Months | 328.46 | 801.26 | 288.17 | 24.50 | 263.67 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM413
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.01 | 161.12 | 21.89 | 0.00 | 21.89 | 0.00 | 0.00 |
| February | 0.82 | 151.76 | 33.36 | 0.00 | 33.36 | 0.00 | 0.00 |
| March | 10.77 | 106.43 | 40.46 | 0.00 | 40.46 | 0.00 | 0.00 |
| April | 22.81 | 74.06 | 51.58 | 0.25 | 51.33 | 0.00 | 0.00 |
| May | 38.77 | 49.37 | 59.92 | 2.58 | 57.34 | 0.00 | 0.00 |
| June | 65.88 | 33.80 | 72.04 | 6.13 | 65.92 | 0.00 | 0.00 |
| July | 73.56 | 23.92 | 67.10 | 4.56 | 62.53 | 0.00 | 0.00 |
| August | 59.80 | 31.79 | 58.09 | 1.12 | 56.97 | 0.00 | 0.00 |
| September | 34.25 | 49.34 | 44.03 | 0.02 | 44.01 | 0.00 | 0.00 |
| October | 13.53 | 73.42 | 32.90 | 0.00 | 32.90 | 0.00 | 0.00 |
| November | 3.94 | 91.73 | 22.11 | 0.00 | 22.11 | 0.00 | 0.00 |
| December | 0.22 | 150.10 | 20.49 | 0.00 | 20.49 | 0.00 | 0.00 |
| Annual Sum or Average | 27.19 | 82.73 | 43.71 | 1.23 | 42.48 | 0.00 | 0.00 |
| Minimum of Months | 0.01 | 23.92 | 20.49 | 0.00 | 20.49 | 0.00 | 0.00 |
| Maximum of Months | 73.56 | 161.12 | 72.04 | 6.13 | 65.92 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM414
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 67.09 | 143.99 | 93.89 | 54.70 | 39.19 | 0.00 | 0.00 |
| February | 72.74 | 142.04 | 107.30 | 51.66 | 55.64 | 0.00 | 0.00 |
| March | 112.67 | 104.91 | 129.12 | 71.64 | 57.48 | 0.00 | 0.00 |
| April | 99.77 | 84.21 | 109.80 | 44.55 | 65.24 | 0.00 | 0.00 |
| May | 92.48 | 59.65 | 95.01 | 27.55 | 67.47 | 0.00 | 0.00 |
| June | 101.29 | 39.85 | 92.66 | 19.84 | 72.81 | 0.00 | 0.00 |
| July | 117.61 | 27.24 | 94.02 | 22.58 | 71.43 | 0.00 | 0.00 |
| August | 130.80 | 35.33 | 104.94 | 33.39 | 71.56 | 0.00 | 0.00 |
| September | 144.29 | 54.40 | 124.60 | 61.46 | 63.15 | 0.00 | 0.00 |
| October | 116.99 | 78.42 | 118.10 | 67.60 | 50.51 | 0.00 | 0.00 |
| November | 72.75 | 97.99 | 84.60 | 47.89 | 36.71 | 0.00 | 0.00 |
| December | 52.36 | 140.42 | 78.71 | 40.74 | 37.97 | 0.00 | 0.00 |
| Annual Sum or Average | 98.55 | 83.72 | 102.69 | 45.27 | 57.42 | 0.00 | 0.00 |
| Minimum of Months | 52.36 | 27.24 | 78.71 | 19.84 | 36.71 | 0.00 | 0.00 |
| Maximum of Months | 144.29 | 143.99 | 129.12 | 71.64 | 72.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM415_418
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 245.46 | 698.41 | 375.55 | 218.80 | 156.75 | 0.00 | 0.00 |
| February | 261.33 | 687.23 | 429.20 | 206.63 | 222.57 | 0.00 | 0.00 |
| March | 427.08 | 485.19 | 516.47 | 286.55 | 229.93 | 0.00 | 0.00 |
| April | 387.60 | 369.97 | 439.18 | 178.22 | 260.96 | 0.00 | 0.00 |
| May | 374.41 | 235.11 | 380.06 | 110.18 | 269.88 | 0.00 | 0.00 |
| June | 427.48 | 138.90 | 370.63 | 79.38 | 291.25 | 0.00 | 0.00 |
| July | 507.18 | 81.05 | 376.06 | 90.33 | 285.73 | 0.00 | 0.00 |
| August | 551.58 | 112.89 | 419.77 | 133.54 | 286.23 | 0.00 | 0.00 |
| September | 590.64 | 202.98 | 498.42 | 245.82 | 252.60 | 0.00 | 0.00 |
| October | 460.50 | 337.19 | 472.41 | 270.39 | 202.03 | 0.00 | 0.00 |
| November | 276.85 | 458.95 | 338.38 | 191.56 | 146.82 | 0.00 | 0.00 |
| December | 190.03 | 685.10 | 314.83 | 162.96 | 151.86 | 0.00 | 0.00 |
| Annual Sum or Average | 392.43 | 372.74 | 410.75 | 181.07 | 229.69 | 0.00 | 0.00 |
| Minimum of Months | 190.03 | 81.05 | 314.83 | 79.38 | 146.82 | 0.00 | 0.00 |
| Maximum of Months | 590.64 | 698.41 | 516.47 | 286.55 | 291.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ELEVATORCOREFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM419
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 61.35 | 177.45 | 93.89 | 54.70 | 39.19 | 0.00 | 0.00 |
| February | 65.17 | 174.77 | 107.30 | 51.66 | 55.64 | 0.00 | 0.00 |
| March | 106.66 | 123.54 | 129.12 | 71.64 | 57.48 | 0.00 | 0.00 |
| April | 96.88 | 94.46 | 109.80 | 44.55 | 65.24 | 0.00 | 0.00 |
| May | 93.59 | 60.27 | 95.01 | 27.55 | 67.47 | 0.00 | 0.00 |
| June | 107.03 | 35.65 | 92.66 | 19.84 | 72.81 | 0.00 | 0.00 |
| July | 127.10 | 20.83 | 94.02 | 22.58 | 71.43 | 0.00 | 0.00 |
| August | 138.12 | 29.02 | 104.94 | 33.39 | 71.56 | 0.00 | 0.00 |
| September | 147.64 | 51.97 | 124.60 | 61.46 | 63.15 | 0.00 | 0.00 |
| October | 114.93 | 86.14 | 118.10 | 67.60 | 50.51 | 0.00 | 0.00 |
| November | 69.10 | 116.88 | 84.60 | 47.89 | 36.71 | 0.00 | 0.00 |
| December | 47.42 | 174.18 | 78.71 | 40.74 | 37.97 | 0.00 | 0.00 |
| Annual Sum or Average | 98.11 | 95.00 | 102.69 | 45.27 | 57.42 | 0.00 | 0.00 |
| Minimum of Months | 47.42 | 20.83 | 78.71 | 19.84 | 36.71 | 0.00 | 0.00 |
| Maximum of Months | 147.64 | 177.45 | 129.12 | 71.64 | 72.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM420_423
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 247.32 | 691.32 | 375.55 | 218.80 | 156.75 | 0.00 | 0.00 |
| February | 263.93 | 680.85 | 429.20 | 206.63 | 222.57 | 0.00 | 0.00 |
| March | 430.14 | 480.31 | 516.47 | 286.55 | 229.93 | 0.00 | 0.00 |
| April | 390.48 | 365.42 | 439.18 | 178.22 | 260.96 | 0.00 | 0.00 |
| May | 377.28 | 230.75 | 380.06 | 110.18 | 269.88 | 0.00 | 0.00 |
| June | 431.21 | 135.12 | 370.63 | 79.38 | 291.25 | 0.00 | 0.00 |
| July | 511.49 | 78.01 | 376.06 | 90.33 | 285.73 | 0.00 | 0.00 |
| August | 555.36 | 109.28 | 419.77 | 133.54 | 286.23 | 0.00 | 0.00 |
| September | 593.69 | 198.44 | 498.42 | 245.82 | 252.60 | 0.00 | 0.00 |
| October | 463.16 | 332.30 | 472.41 | 270.39 | 202.03 | 0.00 | 0.00 |
| November | 278.89 | 452.50 | 338.38 | 191.56 | 146.82 | 0.00 | 0.00 |
| December | 191.76 | 677.90 | 314.83 | 162.96 | 151.86 | 0.00 | 0.00 |
| Annual Sum or Average | 395.31 | 367.68 | 410.75 | 181.07 | 229.69 | 0.00 | 0.00 |
| Minimum of Months | 191.76 | 78.01 | 314.83 | 79.38 | 146.82 | 0.00 | 0.00 |
| Maximum of Months | 593.69 | 691.32 | 516.47 | 286.55 | 291.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GUESTROOM424
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 63.57 | 169.82 | 93.89 | 54.70 | 39.19 | 0.00 | 0.00 |
| February | 68.20 | 167.48 | 107.30 | 51.66 | 55.64 | 0.00 | 0.00 |
| March | 109.52 | 118.85 | 129.12 | 71.64 | 57.48 | 0.00 | 0.00 |
| April | 98.90 | 91.00 | 109.80 | 44.55 | 65.24 | 0.00 | 0.00 |
| May | 94.87 | 58.18 | 95.01 | 27.55 | 67.47 | 0.00 | 0.00 |
| June | 107.94 | 34.67 | 92.66 | 19.84 | 72.81 | 0.00 | 0.00 |
| July | 127.48 | 20.52 | 94.02 | 22.58 | 71.43 | 0.00 | 0.00 |
| August | 138.58 | 28.54 | 104.94 | 33.39 | 71.56 | 0.00 | 0.00 |
| September | 148.46 | 50.66 | 124.60 | 61.46 | 63.15 | 0.00 | 0.00 |
| October | 116.51 | 83.12 | 118.10 | 67.60 | 50.51 | 0.00 | 0.00 |
| November | 70.69 | 111.66 | 84.60 | 47.89 | 36.71 | 0.00 | 0.00 |
| December | 49.32 | 166.53 | 78.71 | 40.74 | 37.97 | 0.00 | 0.00 |
| Annual Sum or Average | 99.68 | 91.35 | 102.69 | 45.27 | 57.42 | 0.00 | 0.00 |
| Minimum of Months | 49.32 | 20.52 | 78.71 | 19.84 | 36.71 | 0.00 | 0.00 |
| Maximum of Months | 148.46 | 169.82 | 129.12 | 71.64 | 72.81 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONTSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: FRONTSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: REARSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDORFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 60448.66 | 0.167342E+10 | 0.181391E+09 | 42732540.39 | 0.138658E+09 | 0.00 | 0.00 |
| February | 4434000.87 | 0.145954E+10 | 0.232325E+09 | 45711226.23 | 0.186614E+09 | 0.00 | 0.00 |
| March | 51874311.95 | 0.112550E+10 | 0.342504E+09 | 90466626.85 | 0.252038E+09 | 0.00 | 0.00 |
| April | 0.144511E+09 | 0.777576E+09 | 0.412411E+09 | 0.102316E+09 | 0.310095E+09 | 0.00 | 0.00 |
| May | 0.312856E+09 | 0.503158E+09 | 0.489638E+09 | 0.128727E+09 | 0.360910E+09 | 0.00 | 0.00 |
| June | 0.522152E+09 | 0.285202E+09 | 0.563188E+09 | 0.158913E+09 | 0.404275E+09 | 0.00 | 0.00 |
| July | 0.599052E+09 | 0.196113E+09 | 0.534747E+09 | 0.139329E+09 | 0.395418E+09 | 0.00 | 0.00 |
| August | 0.503082E+09 | 0.272664E+09 | 0.479922E+09 | 0.118895E+09 | 0.361027E+09 | 0.00 | 0.00 |
| September | 0.262368E+09 | 0.444911E+09 | 0.367683E+09 | 95264015.39 | 0.272419E+09 | 0.00 | 0.00 |
| October | 73164940.48 | 0.818225E+09 | 0.274345E+09 | 69743292.60 | 0.204602E+09 | 0.00 | 0.00 |
| November | 10940897.19 | 0.107134E+10 | 0.174227E+09 | 42491921.99 | 0.131735E+09 | 0.00 | 0.00 |
| December | 0.00 | 0.163686E+10 | 0.156964E+09 | 28320629.93 | 0.128644E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.248450E+10 | 0.102645E+11 | 0.420935E+10 | 0.106291E+10 | 0.314643E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.196113E+09 | 0.156964E+09 | 28320629.93 | 0.128644E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.599052E+09 | 0.167342E+10 | 0.563188E+09 | 0.158913E+09 | 0.404275E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: REARSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONTLOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.221361E+10 | 0.228694E+09 | 0.00 | 0.228694E+09 | 0.00 | 0.00 |
| February | 1209513.59 | 0.189167E+10 | 0.314723E+09 | 0.00 | 0.314723E+09 | 0.00 | 0.00 |
| March | 89194102.22 | 0.145303E+10 | 0.422631E+09 | 14967.66 | 0.422616E+09 | 0.00 | 0.00 |
| April | 0.207713E+09 | 0.939871E+09 | 0.521409E+09 | 2513989.66 | 0.518895E+09 | 0.00 | 0.00 |
| May | 0.429103E+09 | 0.586305E+09 | 0.625898E+09 | 26950648.56 | 0.598947E+09 | 0.00 | 0.00 |
| June | 0.752435E+09 | 0.357480E+09 | 0.728236E+09 | 61922651.74 | 0.666313E+09 | 0.00 | 0.00 |
| July | 0.893246E+09 | 0.247178E+09 | 0.700842E+09 | 47675724.17 | 0.653166E+09 | 0.00 | 0.00 |
| August | 0.710962E+09 | 0.349060E+09 | 0.606769E+09 | 11713326.02 | 0.595056E+09 | 0.00 | 0.00 |
| September | 0.355868E+09 | 0.590368E+09 | 0.445043E+09 | 196954.14 | 0.444846E+09 | 0.00 | 0.00 |
| October | 0.102230E+09 | 0.101817E+10 | 0.343616E+09 | 0.00 | 0.343616E+09 | 0.00 | 0.00 |
| November | 21604587.18 | 0.132065E+10 | 0.223453E+09 | 0.00 | 0.223453E+09 | 0.00 | 0.00 |
| December | 423629.81 | 0.210840E+10 | 0.214050E+09 | 0.00 | 0.214050E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.356399E+10 | 0.130758E+11 | 0.537536E+10 | 0.150988E+09 | 0.522438E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.247178E+09 | 0.214050E+09 | 0.00 | 0.214050E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.893246E+09 | 0.221361E+10 | 0.728236E+09 | 61922651.74 | 0.666313E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: RESTROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MEETINGROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.172663E+10 | 0.175692E+09 | 0.00 | 0.175692E+09 | 0.00 | 0.00 |
| February | 829353.63 | 0.147761E+10 | 0.241783E+09 | 0.00 | 0.241783E+09 | 0.00 | 0.00 |
| March | 65216424.37 | 0.115388E+10 | 0.324683E+09 | 11498.76 | 0.324671E+09 | 0.00 | 0.00 |
| April | 0.152230E+09 | 0.768102E+09 | 0.400569E+09 | 1931348.28 | 0.398637E+09 | 0.00 | 0.00 |
| May | 0.310856E+09 | 0.496402E+09 | 0.480841E+09 | 20704575.51 | 0.460136E+09 | 0.00 | 0.00 |
| June | 0.554317E+09 | 0.292226E+09 | 0.559461E+09 | 47571479.26 | 0.511890E+09 | 0.00 | 0.00 |
| July | 0.663053E+09 | 0.198363E+09 | 0.538416E+09 | 36626414.72 | 0.501790E+09 | 0.00 | 0.00 |
| August | 0.529252E+09 | 0.280984E+09 | 0.466145E+09 | 8998649.61 | 0.457147E+09 | 0.00 | 0.00 |
| September | 0.262886E+09 | 0.482135E+09 | 0.341901E+09 | 151308.12 | 0.341750E+09 | 0.00 | 0.00 |
| October | 74179533.40 | 0.836506E+09 | 0.263980E+09 | 0.00 | 0.263980E+09 | 0.00 | 0.00 |
| November | 15648385.02 | 0.106306E+10 | 0.171666E+09 | 0.00 | 0.171666E+09 | 0.00 | 0.00 |
| December | 326290.48 | 0.164580E+10 | 0.164442E+09 | 0.00 | 0.164442E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.262879E+10 | 0.104217E+11 | 0.412958E+10 | 0.115995E+09 | 0.401358E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.198363E+09 | 0.164442E+09 | 0.00 | 0.164442E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.663053E+09 | 0.172663E+10 | 0.559461E+09 | 47571479.26 | 0.511890E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MECHANICALROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM101
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.548149E+09 | 58563996.22 | 0.00 | 58563996.22 | 0.00 | 0.00 |
| February | 401761.64 | 0.462052E+09 | 80594443.32 | 0.00 | 80594443.32 | 0.00 | 0.00 |
| March | 22224644.01 | 0.366298E+09 | 0.108228E+09 | 3832.92 | 0.108224E+09 | 0.00 | 0.00 |
| April | 49751787.33 | 0.248889E+09 | 0.133523E+09 | 643782.76 | 0.132879E+09 | 0.00 | 0.00 |
| May | 0.103421E+09 | 0.158722E+09 | 0.160280E+09 | 6901525.17 | 0.153379E+09 | 0.00 | 0.00 |
| June | 0.177193E+09 | 98897794.46 | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.00 | 0.00 |
| July | 0.207125E+09 | 71417655.22 | 0.179472E+09 | 12208804.91 | 0.167263E+09 | 0.00 | 0.00 |
| August | 0.164014E+09 | 0.101271E+09 | 0.155382E+09 | 2999549.87 | 0.152382E+09 | 0.00 | 0.00 |
| September | 81612590.57 | 0.166038E+09 | 0.113967E+09 | 50436.04 | 0.113917E+09 | 0.00 | 0.00 |
| October | 22219634.32 | 0.283367E+09 | 87993325.09 | 0.00 | 87993325.09 | 0.00 | 0.00 |
| November | 4909412.43 | 0.356974E+09 | 57221937.69 | 0.00 | 57221937.69 | 0.00 | 0.00 |
| December | 88769.36 | 0.529354E+09 | 54814143.07 | 0.00 | 54814143.07 | 0.00 | 0.00 |
| Annual Sum or Average | 0.832962E+09 | 0.339143E+10 | 0.137653E+10 | 38665091.42 | 0.133786E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 71417655.22 | 54814143.07 | 0.00 | 54814143.07 | 0.00 | 0.00 |
| Maximum of Months | 0.207125E+09 | 0.548149E+09 | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM102
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.529809E+09 | 58563996.22 | 0.00 | 58563996.22 | 0.00 | 0.00 |
| February | 549904.41 | 0.446253E+09 | 80594443.32 | 0.00 | 80594443.32 | 0.00 | 0.00 |
| March | 24399234.20 | 0.350574E+09 | 0.108228E+09 | 3832.92 | 0.108224E+09 | 0.00 | 0.00 |
| April | 54511594.39 | 0.236021E+09 | 0.133523E+09 | 643782.76 | 0.132879E+09 | 0.00 | 0.00 |
| May | 0.110915E+09 | 0.148527E+09 | 0.160280E+09 | 6901525.17 | 0.153379E+09 | 0.00 | 0.00 |
| June | 0.186468E+09 | 91426795.59 | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.00 | 0.00 |
| July | 0.217038E+09 | 64095812.38 | 0.179472E+09 | 12208804.91 | 0.167263E+09 | 0.00 | 0.00 |
| August | 0.172430E+09 | 92064984.13 | 0.155382E+09 | 2999549.87 | 0.152382E+09 | 0.00 | 0.00 |
| September | 87636392.07 | 0.154521E+09 | 0.113967E+09 | 50436.04 | 0.113917E+09 | 0.00 | 0.00 |
| October | 25345196.16 | 0.267858E+09 | 87993325.09 | 0.00 | 87993325.09 | 0.00 | 0.00 |
| November | 5767317.31 | 0.339747E+09 | 57221937.69 | 0.00 | 57221937.69 | 0.00 | 0.00 |
| December | 130014.83 | 0.510525E+09 | 54814143.07 | 0.00 | 54814143.07 | 0.00 | 0.00 |
| Annual Sum or Average | 0.885191E+09 | 0.323142E+10 | 0.137653E+10 | 38665091.42 | 0.133786E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 64095812.38 | 54814143.07 | 0.00 | 54814143.07 | 0.00 | 0.00 |
| Maximum of Months | 0.217038E+09 | 0.529809E+09 | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM103
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.540442E+09 | 58563996.22 | 0.00 | 58563996.22 | 0.00 | 0.00 |
| February | 634648.03 | 0.458669E+09 | 80594443.32 | 0.00 | 80594443.32 | 0.00 | 0.00 |
| March | 26067684.37 | 0.351402E+09 | 0.108228E+09 | 3832.92 | 0.108224E+09 | 0.00 | 0.00 |
| April | 58987479.26 | 0.226666E+09 | 0.133523E+09 | 643782.76 | 0.132879E+09 | 0.00 | 0.00 |
| May | 0.119473E+09 | 0.134791E+09 | 0.160280E+09 | 6901525.17 | 0.153379E+09 | 0.00 | 0.00 |
| June | 0.202268E+09 | 77155104.75 | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.00 | 0.00 |
| July | 0.238489E+09 | 49339527.73 | 0.179472E+09 | 12208804.91 | 0.167263E+09 | 0.00 | 0.00 |
| August | 0.188861E+09 | 73200238.78 | 0.155382E+09 | 2999549.87 | 0.152382E+09 | 0.00 | 0.00 |
| September | 96160419.46 | 0.134403E+09 | 0.113967E+09 | 50436.04 | 0.113917E+09 | 0.00 | 0.00 |
| October | 28451670.68 | 0.248383E+09 | 87993325.09 | 0.00 | 87993325.09 | 0.00 | 0.00 |
| November | 6428353.10 | 0.325757E+09 | 57221937.69 | 0.00 | 57221937.69 | 0.00 | 0.00 |
| December | 163177.73 | 0.514867E+09 | 54814143.07 | 0.00 | 54814143.07 | 0.00 | 0.00 |
| Annual Sum or Average | 0.965984E+09 | 0.313508E+10 | 0.137653E+10 | 38665091.42 | 0.133786E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 49339527.73 | 54814143.07 | 0.00 | 54814143.07 | 0.00 | 0.00 |
| Maximum of Months | 0.238489E+09 | 0.540442E+09 | 0.186487E+09 | 15857159.75 | 0.170630E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM104
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.169729E+09 | 0.477114E+09 | 0.251133E+09 | 0.146314E+09 | 0.104819E+09 | 0.00 | 0.00 |
| February | 0.166035E+09 | 0.418512E+09 | 0.259234E+09 | 0.124802E+09 | 0.134432E+09 | 0.00 | 0.00 |
| March | 0.300967E+09 | 0.328059E+09 | 0.345370E+09 | 0.191615E+09 | 0.153754E+09 | 0.00 | 0.00 |
| April | 0.266780E+09 | 0.240912E+09 | 0.284212E+09 | 0.115333E+09 | 0.168880E+09 | 0.00 | 0.00 |
| May | 0.269976E+09 | 0.155438E+09 | 0.254148E+09 | 73678352.78 | 0.180470E+09 | 0.00 | 0.00 |
| June | 0.297326E+09 | 89483622.74 | 0.239847E+09 | 51367907.77 | 0.188479E+09 | 0.00 | 0.00 |
| July | 0.358762E+09 | 56128038.43 | 0.251477E+09 | 60403595.47 | 0.191073E+09 | 0.00 | 0.00 |
| August | 0.384772E+09 | 79765808.67 | 0.280704E+09 | 89301622.93 | 0.191402E+09 | 0.00 | 0.00 |
| September | 0.394012E+09 | 0.138682E+09 | 0.322545E+09 | 0.159080E+09 | 0.163465E+09 | 0.00 | 0.00 |
| October | 0.315328E+09 | 0.239091E+09 | 0.315906E+09 | 0.180810E+09 | 0.135096E+09 | 0.00 | 0.00 |
| November | 0.183128E+09 | 0.313819E+09 | 0.218979E+09 | 0.123963E+09 | 95015835.14 | 0.00 | 0.00 |
| December | 0.130924E+09 | 0.472173E+09 | 0.210527E+09 | 0.108976E+09 | 0.101551E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.323774E+10 | 0.300918E+10 | 0.323408E+10 | 0.142564E+10 | 0.180844E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.130924E+09 | 56128038.43 | 0.210527E+09 | 51367907.77 | 95015835.14 | 0.00 | 0.00 |
| Maximum of Months | 0.394012E+09 | 0.477114E+09 | 0.345370E+09 | 0.191615E+09 | 0.191402E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM105
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.159220E+09 | 0.523946E+09 | 0.251133E+09 | 0.146314E+09 | 0.104819E+09 | 0.00 | 0.00 |
| February | 0.151938E+09 | 0.460430E+09 | 0.259234E+09 | 0.124802E+09 | 0.134432E+09 | 0.00 | 0.00 |
| March | 0.283594E+09 | 0.359492E+09 | 0.345370E+09 | 0.191615E+09 | 0.153754E+09 | 0.00 | 0.00 |
| April | 0.252017E+09 | 0.266714E+09 | 0.284212E+09 | 0.115333E+09 | 0.168880E+09 | 0.00 | 0.00 |
| May | 0.255857E+09 | 0.175711E+09 | 0.254148E+09 | 73678352.78 | 0.180470E+09 | 0.00 | 0.00 |
| June | 0.283737E+09 | 0.101838E+09 | 0.239847E+09 | 51367907.77 | 0.188479E+09 | 0.00 | 0.00 |
| July | 0.345948E+09 | 64828454.61 | 0.251477E+09 | 60403595.47 | 0.191073E+09 | 0.00 | 0.00 |
| August | 0.374045E+09 | 89892475.59 | 0.280704E+09 | 89301622.93 | 0.191402E+09 | 0.00 | 0.00 |
| September | 0.384680E+09 | 0.152164E+09 | 0.322545E+09 | 0.159080E+09 | 0.163465E+09 | 0.00 | 0.00 |
| October | 0.305399E+09 | 0.258924E+09 | 0.315906E+09 | 0.180810E+09 | 0.135096E+09 | 0.00 | 0.00 |
| November | 0.175433E+09 | 0.342306E+09 | 0.218979E+09 | 0.123963E+09 | 95015835.14 | 0.00 | 0.00 |
| December | 0.122153E+09 | 0.518731E+09 | 0.210527E+09 | 0.108976E+09 | 0.101551E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309402E+10 | 0.331498E+10 | 0.323408E+10 | 0.142564E+10 | 0.180844E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.122153E+09 | 64828454.61 | 0.210527E+09 | 51367907.77 | 95015835.14 | 0.00 | 0.00 |
| Maximum of Months | 0.384680E+09 | 0.523946E+09 | 0.345370E+09 | 0.191615E+09 | 0.191402E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: EMPLOYEELOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.143801E+09 | 0.620707E+09 | 0.251133E+09 | 0.146314E+09 | 0.104819E+09 | 0.00 | 0.00 |
| February | 0.134107E+09 | 0.543159E+09 | 0.259234E+09 | 0.124802E+09 | 0.134432E+09 | 0.00 | 0.00 |
| March | 0.252137E+09 | 0.442941E+09 | 0.345370E+09 | 0.191615E+09 | 0.153754E+09 | 0.00 | 0.00 |
| April | 0.219502E+09 | 0.346759E+09 | 0.284212E+09 | 0.115333E+09 | 0.168880E+09 | 0.00 | 0.00 |
| May | 0.219230E+09 | 0.248340E+09 | 0.254148E+09 | 73678352.78 | 0.180470E+09 | 0.00 | 0.00 |
| June | 0.238848E+09 | 0.154252E+09 | 0.239847E+09 | 51367907.77 | 0.188479E+09 | 0.00 | 0.00 |
| July | 0.295517E+09 | 0.113978E+09 | 0.251477E+09 | 60403595.47 | 0.191073E+09 | 0.00 | 0.00 |
| August | 0.330164E+09 | 0.144977E+09 | 0.280704E+09 | 89301622.93 | 0.191402E+09 | 0.00 | 0.00 |
| September | 0.349603E+09 | 0.214600E+09 | 0.322545E+09 | 0.159080E+09 | 0.163465E+09 | 0.00 | 0.00 |
| October | 0.274185E+09 | 0.340362E+09 | 0.315906E+09 | 0.180810E+09 | 0.135096E+09 | 0.00 | 0.00 |
| November | 0.156805E+09 | 0.437224E+09 | 0.218979E+09 | 0.123963E+09 | 95015835.14 | 0.00 | 0.00 |
| December | 0.109633E+09 | 0.620572E+09 | 0.210527E+09 | 0.108976E+09 | 0.101551E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.272353E+10 | 0.422787E+10 | 0.323408E+10 | 0.142564E+10 | 0.180844E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.109633E+09 | 0.113978E+09 | 0.210527E+09 | 51367907.77 | 95015835.14 | 0.00 | 0.00 |
| Maximum of Months | 0.349603E+09 | 0.620707E+09 | 0.345370E+09 | 0.191615E+09 | 0.191402E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LAUNDRYROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.160551E+09 | 0.392525E+10 | 0.753399E+09 | 0.438943E+09 | 0.314457E+09 | 0.00 | 0.00 |
| February | 0.138306E+09 | 0.348078E+10 | 0.777701E+09 | 0.374406E+09 | 0.403296E+09 | 0.00 | 0.00 |
| March | 0.282597E+09 | 0.319366E+10 | 0.103611E+10 | 0.574846E+09 | 0.461263E+09 | 0.00 | 0.00 |
| April | 0.165856E+09 | 0.280538E+10 | 0.852637E+09 | 0.345998E+09 | 0.506640E+09 | 0.00 | 0.00 |
| May | 90505284.10 | 0.255080E+10 | 0.762445E+09 | 0.221035E+09 | 0.541410E+09 | 0.00 | 0.00 |
| June | 46042448.48 | 0.209332E+10 | 0.719540E+09 | 0.154104E+09 | 0.565437E+09 | 0.00 | 0.00 |
| July | 0.100338E+09 | 0.194759E+10 | 0.754430E+09 | 0.181211E+09 | 0.573219E+09 | 0.00 | 0.00 |
| August | 0.198188E+09 | 0.204700E+10 | 0.842112E+09 | 0.267905E+09 | 0.574207E+09 | 0.00 | 0.00 |
| September | 0.347583E+09 | 0.229699E+10 | 0.967635E+09 | 0.477241E+09 | 0.490394E+09 | 0.00 | 0.00 |
| October | 0.310878E+09 | 0.290990E+10 | 0.947718E+09 | 0.542429E+09 | 0.405289E+09 | 0.00 | 0.00 |
| November | 0.164997E+09 | 0.332171E+10 | 0.656936E+09 | 0.371888E+09 | 0.285048E+09 | 0.00 | 0.00 |
| December | 0.130591E+09 | 0.401676E+10 | 0.631580E+09 | 0.326927E+09 | 0.304654E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.213643E+10 | 0.345891E+11 | 0.970224E+10 | 0.427693E+10 | 0.542531E+10 | 0.00 | 0.00 |
| Minimum of Months | 46042448.48 | 0.194759E+10 | 0.631580E+09 | 0.154104E+09 | 0.285048E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.347583E+09 | 0.401676E+10 | 0.103611E+10 | 0.574846E+09 | 0.574207E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ELEVATORCOREFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: EXERCISECENTERFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.165114E+09 | 0.503406E+09 | 0.251133E+09 | 0.146314E+09 | 0.104819E+09 | 0.00 | 0.00 |
| February | 0.158912E+09 | 0.443783E+09 | 0.259234E+09 | 0.124802E+09 | 0.134432E+09 | 0.00 | 0.00 |
| March | 0.291450E+09 | 0.352355E+09 | 0.345370E+09 | 0.191615E+09 | 0.153754E+09 | 0.00 | 0.00 |
| April | 0.255798E+09 | 0.266151E+09 | 0.284212E+09 | 0.115333E+09 | 0.168880E+09 | 0.00 | 0.00 |
| May | 0.257298E+09 | 0.180723E+09 | 0.254148E+09 | 73678352.78 | 0.180470E+09 | 0.00 | 0.00 |
| June | 0.285076E+09 | 0.107215E+09 | 0.239847E+09 | 51367907.77 | 0.188479E+09 | 0.00 | 0.00 |
| July | 0.346161E+09 | 72195166.10 | 0.251477E+09 | 60403595.47 | 0.191073E+09 | 0.00 | 0.00 |
| August | 0.375197E+09 | 97276647.17 | 0.280704E+09 | 89301622.93 | 0.191402E+09 | 0.00 | 0.00 |
| September | 0.386384E+09 | 0.157634E+09 | 0.322545E+09 | 0.159080E+09 | 0.163465E+09 | 0.00 | 0.00 |
| October | 0.306971E+09 | 0.264370E+09 | 0.315906E+09 | 0.180810E+09 | 0.135096E+09 | 0.00 | 0.00 |
| November | 0.177930E+09 | 0.339762E+09 | 0.218979E+09 | 0.123963E+09 | 95015835.14 | 0.00 | 0.00 |
| December | 0.126995E+09 | 0.498420E+09 | 0.210527E+09 | 0.108976E+09 | 0.101551E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.313329E+10 | 0.328329E+10 | 0.323408E+10 | 0.142564E+10 | 0.180844E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.126995E+09 | 72195166.10 | 0.210527E+09 | 51367907.77 | 95015835.14 | 0.00 | 0.00 |
| Maximum of Months | 0.386384E+09 | 0.503406E+09 | 0.345370E+09 | 0.191615E+09 | 0.191402E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONTOFFICEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.678297E+09 | 0.194232E+10 | 0.100453E+10 | 0.585257E+09 | 0.419275E+09 | 0.00 | 0.00 |
| February | 0.660888E+09 | 0.170740E+10 | 0.103694E+10 | 0.499208E+09 | 0.537727E+09 | 0.00 | 0.00 |
| March | 0.118925E+10 | 0.137507E+10 | 0.138148E+10 | 0.766461E+09 | 0.615017E+09 | 0.00 | 0.00 |
| April | 0.104417E+10 | 0.104754E+10 | 0.113685E+10 | 0.461330E+09 | 0.675520E+09 | 0.00 | 0.00 |
| May | 0.104941E+10 | 0.724036E+09 | 0.101659E+10 | 0.294713E+09 | 0.721881E+09 | 0.00 | 0.00 |
| June | 0.115547E+10 | 0.426343E+09 | 0.959387E+09 | 0.205472E+09 | 0.753916E+09 | 0.00 | 0.00 |
| July | 0.139447E+10 | 0.282899E+09 | 0.100591E+10 | 0.241614E+09 | 0.764292E+09 | 0.00 | 0.00 |
| August | 0.151169E+10 | 0.386241E+09 | 0.112282E+10 | 0.357206E+09 | 0.765609E+09 | 0.00 | 0.00 |
| September | 0.155822E+10 | 0.635336E+09 | 0.129018E+10 | 0.636321E+09 | 0.653858E+09 | 0.00 | 0.00 |
| October | 0.124236E+10 | 0.106480E+10 | 0.126362E+10 | 0.723239E+09 | 0.540385E+09 | 0.00 | 0.00 |
| November | 0.721900E+09 | 0.135145E+10 | 0.875914E+09 | 0.495851E+09 | 0.380063E+09 | 0.00 | 0.00 |
| December | 0.524182E+09 | 0.192377E+10 | 0.842107E+09 | 0.435902E+09 | 0.406205E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.127303E+11 | 0.128672E+11 | 0.129363E+11 | 0.570258E+10 | 0.723375E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.524182E+09 | 0.282899E+09 | 0.842107E+09 | 0.205472E+09 | 0.380063E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.155822E+10 | 0.194232E+10 | 0.138148E+10 | 0.766461E+09 | 0.765609E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONTSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONTSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: REARSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDORFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 2173847.18 | 0.403459E+09 | 68912322.79 | 19536192.41 | 49376130.37 | 0.00 | 0.00 |
| February | 12496317.32 | 0.342990E+09 | 95492488.94 | 26632627.56 | 68859861.38 | 0.00 | 0.00 |
| March | 71490751.20 | 0.253939E+09 | 0.159075E+09 | 67461564.49 | 91613248.38 | 0.00 | 0.00 |
| April | 0.136518E+09 | 0.183980E+09 | 0.195146E+09 | 83138602.03 | 0.112008E+09 | 0.00 | 0.00 |
| May | 0.216147E+09 | 0.126226E+09 | 0.231835E+09 | 0.103588E+09 | 0.128247E+09 | 0.00 | 0.00 |
| June | 0.294195E+09 | 73984756.35 | 0.260967E+09 | 0.119222E+09 | 0.141746E+09 | 0.00 | 0.00 |
| July | 0.314422E+09 | 50505428.14 | 0.249335E+09 | 0.109382E+09 | 0.139953E+09 | 0.00 | 0.00 |
| August | 0.274372E+09 | 68949008.04 | 0.225185E+09 | 94881932.53 | 0.130303E+09 | 0.00 | 0.00 |
| September | 0.178989E+09 | 0.112003E+09 | 0.176210E+09 | 77015540.42 | 99194795.44 | 0.00 | 0.00 |
| October | 71675205.01 | 0.197257E+09 | 0.120906E+09 | 46360985.25 | 74544565.03 | 0.00 | 0.00 |
| November | 18013709.01 | 0.260031E+09 | 67557449.22 | 20429238.40 | 47128210.82 | 0.00 | 0.00 |
| December | 1869862.38 | 0.398811E+09 | 58521781.37 | 12401022.16 | 46120759.22 | 0.00 | 0.00 |
| Annual Sum or Average | 0.159236E+10 | 0.247213E+10 | 0.190914E+10 | 0.780050E+09 | 0.112909E+10 | 0.00 | 0.00 |
| Minimum of Months | 1869862.38 | 50505428.14 | 58521781.37 | 12401022.16 | 46120759.22 | 0.00 | 0.00 |
| Maximum of Months | 0.314422E+09 | 0.403459E+09 | 0.260967E+09 | 0.119222E+09 | 0.141746E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: REARSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM201
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.487580E+09 | 58753532.56 | 0.00 | 58753532.56 | 0.00 | 0.00 |
| February | 900586.10 | 0.415247E+09 | 80855278.93 | 0.00 | 80855278.93 | 0.00 | 0.00 |
| March | 24327787.74 | 0.333065E+09 | 0.108578E+09 | 3845.32 | 0.108574E+09 | 0.00 | 0.00 |
| April | 53095467.93 | 0.231001E+09 | 0.133955E+09 | 645866.30 | 0.133309E+09 | 0.00 | 0.00 |
| May | 0.101679E+09 | 0.155645E+09 | 0.160799E+09 | 6923861.27 | 0.153875E+09 | 0.00 | 0.00 |
| June | 0.171221E+09 | 0.100139E+09 | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.00 | 0.00 |
| July | 0.200129E+09 | 73181670.10 | 0.180053E+09 | 12248317.48 | 0.167805E+09 | 0.00 | 0.00 |
| August | 0.161971E+09 | 98862190.21 | 0.155885E+09 | 3009257.61 | 0.152875E+09 | 0.00 | 0.00 |
| September | 85511152.98 | 0.152564E+09 | 0.114336E+09 | 50599.27 | 0.114285E+09 | 0.00 | 0.00 |
| October | 28811397.84 | 0.244348E+09 | 88278106.39 | 0.00 | 88278106.39 | 0.00 | 0.00 |
| November | 7240949.03 | 0.300687E+09 | 57407130.60 | 0.00 | 57407130.60 | 0.00 | 0.00 |
| December | 251070.09 | 0.461773E+09 | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 0.00 |
| Annual Sum or Average | 0.835139E+09 | 0.305409E+10 | 0.138098E+10 | 38790227.12 | 0.134219E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 73181670.10 | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 0.00 |
| Maximum of Months | 0.200129E+09 | 0.487580E+09 | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM202_205
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.221577E+10 | 0.235014E+09 | 0.00 | 0.235014E+09 | 0.00 | 0.00 |
| February | 1642890.11 | 0.190081E+10 | 0.323421E+09 | 0.00 | 0.323421E+09 | 0.00 | 0.00 |
| March | 88066825.24 | 0.147922E+10 | 0.434311E+09 | 15381.30 | 0.434296E+09 | 0.00 | 0.00 |
| April | 0.199891E+09 | 0.971785E+09 | 0.535820E+09 | 2583465.19 | 0.533236E+09 | 0.00 | 0.00 |
| May | 0.421226E+09 | 0.598077E+09 | 0.643196E+09 | 27695445.07 | 0.615501E+09 | 0.00 | 0.00 |
| June | 0.751488E+09 | 0.348472E+09 | 0.748363E+09 | 63633919.46 | 0.684729E+09 | 0.00 | 0.00 |
| July | 0.903173E+09 | 0.226533E+09 | 0.720211E+09 | 48993269.93 | 0.671218E+09 | 0.00 | 0.00 |
| August | 0.720451E+09 | 0.321944E+09 | 0.623539E+09 | 12037030.45 | 0.611502E+09 | 0.00 | 0.00 |
| September | 0.367042E+09 | 0.564876E+09 | 0.457343E+09 | 202397.08 | 0.457141E+09 | 0.00 | 0.00 |
| October | 0.108675E+09 | 0.100422E+10 | 0.353112E+09 | 0.00 | 0.353112E+09 | 0.00 | 0.00 |
| November | 24171612.73 | 0.131154E+10 | 0.229629E+09 | 0.00 | 0.229629E+09 | 0.00 | 0.00 |
| December | 561602.86 | 0.209777E+10 | 0.219966E+09 | 0.00 | 0.219966E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.358639E+10 | 0.130410E+11 | 0.552393E+10 | 0.155161E+09 | 0.536876E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.226533E+09 | 0.219966E+09 | 0.00 | 0.219966E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.903173E+09 | 0.221577E+10 | 0.748363E+09 | 63633919.46 | 0.684729E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM206_208
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.164791E+10 | 0.170034E+09 | 0.00 | 0.170034E+09 | 0.00 | 0.00 |
| February | 930824.57 | 0.141385E+10 | 0.233998E+09 | 0.00 | 0.233998E+09 | 0.00 | 0.00 |
| March | 60195875.47 | 0.110459E+10 | 0.314227E+09 | 11128.49 | 0.314216E+09 | 0.00 | 0.00 |
| April | 0.137467E+09 | 0.724165E+09 | 0.387670E+09 | 1869156.95 | 0.385800E+09 | 0.00 | 0.00 |
| May | 0.300236E+09 | 0.440876E+09 | 0.465357E+09 | 20037867.60 | 0.445319E+09 | 0.00 | 0.00 |
| June | 0.545389E+09 | 0.252549E+09 | 0.541446E+09 | 46039630.34 | 0.495406E+09 | 0.00 | 0.00 |
| July | 0.658908E+09 | 0.162056E+09 | 0.521078E+09 | 35447007.76 | 0.485631E+09 | 0.00 | 0.00 |
| August | 0.525222E+09 | 0.231513E+09 | 0.451135E+09 | 8708884.15 | 0.442426E+09 | 0.00 | 0.00 |
| September | 0.265348E+09 | 0.412379E+09 | 0.330891E+09 | 146435.84 | 0.330745E+09 | 0.00 | 0.00 |
| October | 74720835.90 | 0.745938E+09 | 0.255479E+09 | 0.00 | 0.255479E+09 | 0.00 | 0.00 |
| November | 15932024.24 | 0.981150E+09 | 0.166138E+09 | 0.00 | 0.166138E+09 | 0.00 | 0.00 |
| December | 332377.99 | 0.156010E+10 | 0.159147E+09 | 0.00 | 0.159147E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.258468E+10 | 0.967708E+10 | 0.399660E+10 | 0.112260E+09 | 0.388434E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.162056E+09 | 0.159147E+09 | 0.00 | 0.159147E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.658908E+09 | 0.164791E+10 | 0.541446E+09 | 46039630.34 | 0.495406E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM209_212
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.228018E+10 | 0.235014E+09 | 0.00 | 0.235014E+09 | 0.00 | 0.00 |
| February | 1172853.32 | 0.195441E+10 | 0.323421E+09 | 0.00 | 0.323421E+09 | 0.00 | 0.00 |
| March | 82952804.95 | 0.152560E+10 | 0.434311E+09 | 15381.30 | 0.434296E+09 | 0.00 | 0.00 |
| April | 0.190034E+09 | 0.997765E+09 | 0.535820E+09 | 2583465.19 | 0.533236E+09 | 0.00 | 0.00 |
| May | 0.420198E+09 | 0.601613E+09 | 0.643196E+09 | 27695445.07 | 0.615501E+09 | 0.00 | 0.00 |
| June | 0.763117E+09 | 0.342222E+09 | 0.748363E+09 | 63633919.46 | 0.684729E+09 | 0.00 | 0.00 |
| July | 0.921480E+09 | 0.217316E+09 | 0.720211E+09 | 48993269.93 | 0.671218E+09 | 0.00 | 0.00 |
| August | 0.733158E+09 | 0.312932E+09 | 0.623539E+09 | 12037030.45 | 0.611502E+09 | 0.00 | 0.00 |
| September | 0.368463E+09 | 0.566583E+09 | 0.457343E+09 | 202397.08 | 0.457141E+09 | 0.00 | 0.00 |
| October | 0.101463E+09 | 0.103543E+10 | 0.353112E+09 | 0.00 | 0.353112E+09 | 0.00 | 0.00 |
| November | 20990226.33 | 0.136737E+10 | 0.229629E+09 | 0.00 | 0.229629E+09 | 0.00 | 0.00 |
| December | 388038.46 | 0.216315E+10 | 0.219966E+09 | 0.00 | 0.219966E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.360342E+10 | 0.133646E+11 | 0.552393E+10 | 0.155161E+09 | 0.536876E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.217316E+09 | 0.219966E+09 | 0.00 | 0.219966E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.921480E+09 | 0.228018E+10 | 0.748363E+09 | 63633919.46 | 0.684729E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM213
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.544416E+09 | 58753532.56 | 0.00 | 58753532.56 | 0.00 | 0.00 |
| February | 625853.71 | 0.464793E+09 | 80855278.93 | 0.00 | 80855278.93 | 0.00 | 0.00 |
| March | 24211894.39 | 0.360679E+09 | 0.108578E+09 | 3845.32 | 0.108574E+09 | 0.00 | 0.00 |
| April | 54844956.86 | 0.235769E+09 | 0.133955E+09 | 645866.30 | 0.133309E+09 | 0.00 | 0.00 |
| May | 0.111246E+09 | 0.143390E+09 | 0.160799E+09 | 6923861.27 | 0.153875E+09 | 0.00 | 0.00 |
| June | 0.194499E+09 | 82331850.55 | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.00 | 0.00 |
| July | 0.232228E+09 | 52501390.88 | 0.180053E+09 | 12248317.48 | 0.167805E+09 | 0.00 | 0.00 |
| August | 0.185351E+09 | 75841903.52 | 0.155885E+09 | 3009257.61 | 0.152875E+09 | 0.00 | 0.00 |
| September | 95412279.42 | 0.135776E+09 | 0.114336E+09 | 50599.27 | 0.114285E+09 | 0.00 | 0.00 |
| October | 29687259.15 | 0.245368E+09 | 88278106.39 | 0.00 | 88278106.39 | 0.00 | 0.00 |
| November | 6814015.81 | 0.319932E+09 | 57407130.60 | 0.00 | 57407130.60 | 0.00 | 0.00 |
| December | 197152.68 | 0.513868E+09 | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 0.00 |
| Annual Sum or Average | 0.935117E+09 | 0.317467E+10 | 0.138098E+10 | 38790227.12 | 0.134219E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 52501390.88 | 54991543.41 | 0.00 | 54991543.41 | 0.00 | 0.00 |
| Maximum of Months | 0.232228E+09 | 0.544416E+09 | 0.187091E+09 | 15908479.86 | 0.171182E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM214
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.165209E+09 | 0.492482E+09 | 0.251946E+09 | 0.146788E+09 | 0.105158E+09 | 0.00 | 0.00 |
| February | 0.159702E+09 | 0.434154E+09 | 0.260073E+09 | 0.125206E+09 | 0.134867E+09 | 0.00 | 0.00 |
| March | 0.290265E+09 | 0.344471E+09 | 0.346487E+09 | 0.192235E+09 | 0.154252E+09 | 0.00 | 0.00 |
| April | 0.256762E+09 | 0.256757E+09 | 0.285132E+09 | 0.115706E+09 | 0.169426E+09 | 0.00 | 0.00 |
| May | 0.258843E+09 | 0.170710E+09 | 0.254971E+09 | 73916805.40 | 0.181054E+09 | 0.00 | 0.00 |
| June | 0.286243E+09 | 99697433.82 | 0.240623E+09 | 51534154.87 | 0.189089E+09 | 0.00 | 0.00 |
| July | 0.348151E+09 | 63335000.16 | 0.252290E+09 | 60599085.67 | 0.191691E+09 | 0.00 | 0.00 |
| August | 0.376718E+09 | 87021153.41 | 0.281612E+09 | 89590638.70 | 0.192022E+09 | 0.00 | 0.00 |
| September | 0.387988E+09 | 0.146091E+09 | 0.323589E+09 | 0.159595E+09 | 0.163994E+09 | 0.00 | 0.00 |
| October | 0.310075E+09 | 0.246684E+09 | 0.316929E+09 | 0.181395E+09 | 0.135534E+09 | 0.00 | 0.00 |
| November | 0.179555E+09 | 0.322626E+09 | 0.219687E+09 | 0.124364E+09 | 95323344.21 | 0.00 | 0.00 |
| December | 0.127494E+09 | 0.484747E+09 | 0.211208E+09 | 0.109328E+09 | 0.101880E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.314700E+10 | 0.314878E+10 | 0.324455E+10 | 0.143026E+10 | 0.181429E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.127494E+09 | 63335000.16 | 0.211208E+09 | 51534154.87 | 95323344.21 | 0.00 | 0.00 |
| Maximum of Months | 0.387988E+09 | 0.492482E+09 | 0.346487E+09 | 0.192235E+09 | 0.192022E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM215_218
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.571094E+09 | 0.257184E+10 | 0.100778E+10 | 0.587151E+09 | 0.420632E+09 | 0.00 | 0.00 |
| February | 0.531592E+09 | 0.226192E+10 | 0.104029E+10 | 0.500823E+09 | 0.539468E+09 | 0.00 | 0.00 |
| March | 0.998125E+09 | 0.185862E+10 | 0.138595E+10 | 0.768941E+09 | 0.617008E+09 | 0.00 | 0.00 |
| April | 0.867644E+09 | 0.146420E+10 | 0.114053E+10 | 0.462823E+09 | 0.677706E+09 | 0.00 | 0.00 |
| May | 0.858054E+09 | 0.107361E+10 | 0.101988E+10 | 0.295667E+09 | 0.724217E+09 | 0.00 | 0.00 |
| June | 0.922093E+09 | 0.681508E+09 | 0.962492E+09 | 0.206137E+09 | 0.756356E+09 | 0.00 | 0.00 |
| July | 0.113876E+10 | 0.512698E+09 | 0.100916E+10 | 0.242396E+09 | 0.766765E+09 | 0.00 | 0.00 |
| August | 0.128515E+10 | 0.639515E+09 | 0.112645E+10 | 0.358363E+09 | 0.768087E+09 | 0.00 | 0.00 |
| September | 0.137438E+10 | 0.922057E+09 | 0.129436E+10 | 0.638381E+09 | 0.655974E+09 | 0.00 | 0.00 |
| October | 0.108812E+10 | 0.142504E+10 | 0.126771E+10 | 0.725580E+09 | 0.542134E+09 | 0.00 | 0.00 |
| November | 0.623297E+09 | 0.180664E+10 | 0.878749E+09 | 0.497455E+09 | 0.381293E+09 | 0.00 | 0.00 |
| December | 0.436553E+09 | 0.255958E+10 | 0.844832E+09 | 0.437313E+09 | 0.407520E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.106949E+11 | 0.177772E+11 | 0.129782E+11 | 0.572103E+10 | 0.725716E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.436553E+09 | 0.512698E+09 | 0.844832E+09 | 0.206137E+09 | 0.381293E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.137438E+10 | 0.257184E+10 | 0.138595E+10 | 0.768941E+09 | 0.768087E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ELEVATORCOREFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM219
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.144229E+09 | 0.611032E+09 | 0.251946E+09 | 0.146788E+09 | 0.105158E+09 | 0.00 | 0.00 |
| February | 0.133869E+09 | 0.538401E+09 | 0.260073E+09 | 0.125206E+09 | 0.134867E+09 | 0.00 | 0.00 |
| March | 0.251915E+09 | 0.434684E+09 | 0.346487E+09 | 0.192235E+09 | 0.154252E+09 | 0.00 | 0.00 |
| April | 0.219760E+09 | 0.339552E+09 | 0.285132E+09 | 0.115706E+09 | 0.169426E+09 | 0.00 | 0.00 |
| May | 0.216769E+09 | 0.254724E+09 | 0.254971E+09 | 73916805.40 | 0.181054E+09 | 0.00 | 0.00 |
| June | 0.233172E+09 | 0.165672E+09 | 0.240623E+09 | 51534154.87 | 0.189089E+09 | 0.00 | 0.00 |
| July | 0.289046E+09 | 0.120975E+09 | 0.252290E+09 | 60599085.67 | 0.191691E+09 | 0.00 | 0.00 |
| August | 0.324813E+09 | 0.153209E+09 | 0.281612E+09 | 89590638.70 | 0.192022E+09 | 0.00 | 0.00 |
| September | 0.346224E+09 | 0.223347E+09 | 0.323589E+09 | 0.159595E+09 | 0.163994E+09 | 0.00 | 0.00 |
| October | 0.274531E+09 | 0.333485E+09 | 0.316929E+09 | 0.181395E+09 | 0.135534E+09 | 0.00 | 0.00 |
| November | 0.157729E+09 | 0.423614E+09 | 0.219687E+09 | 0.124364E+09 | 95323344.21 | 0.00 | 0.00 |
| December | 0.109979E+09 | 0.607813E+09 | 0.211208E+09 | 0.109328E+09 | 0.101880E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.270204E+10 | 0.420651E+10 | 0.324455E+10 | 0.143026E+10 | 0.181429E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.109979E+09 | 0.120975E+09 | 0.211208E+09 | 51534154.87 | 95323344.21 | 0.00 | 0.00 |
| Maximum of Months | 0.346224E+09 | 0.611032E+09 | 0.346487E+09 | 0.192235E+09 | 0.192022E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM220_223
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.656948E+09 | 0.198179E+10 | 0.100778E+10 | 0.587151E+09 | 0.420632E+09 | 0.00 | 0.00 |
| February | 0.633549E+09 | 0.175128E+10 | 0.104029E+10 | 0.500823E+09 | 0.539468E+09 | 0.00 | 0.00 |
| March | 0.116086E+10 | 0.138121E+10 | 0.138595E+10 | 0.768941E+09 | 0.617008E+09 | 0.00 | 0.00 |
| April | 0.103014E+10 | 0.102502E+10 | 0.114053E+10 | 0.462823E+09 | 0.677706E+09 | 0.00 | 0.00 |
| May | 0.104277E+10 | 0.676558E+09 | 0.101988E+10 | 0.295667E+09 | 0.724217E+09 | 0.00 | 0.00 |
| June | 0.115871E+10 | 0.389022E+09 | 0.962492E+09 | 0.206137E+09 | 0.756356E+09 | 0.00 | 0.00 |
| July | 0.141210E+10 | 0.242393E+09 | 0.100916E+10 | 0.242396E+09 | 0.766765E+09 | 0.00 | 0.00 |
| August | 0.152390E+10 | 0.334625E+09 | 0.112645E+10 | 0.358363E+09 | 0.768087E+09 | 0.00 | 0.00 |
| September | 0.156330E+10 | 0.573063E+09 | 0.129436E+10 | 0.638381E+09 | 0.655974E+09 | 0.00 | 0.00 |
| October | 0.124620E+10 | 0.981545E+09 | 0.126771E+10 | 0.725580E+09 | 0.542134E+09 | 0.00 | 0.00 |
| November | 0.720473E+09 | 0.128985E+10 | 0.878749E+09 | 0.497455E+09 | 0.381293E+09 | 0.00 | 0.00 |
| December | 0.507870E+09 | 0.194944E+10 | 0.844832E+09 | 0.437313E+09 | 0.407520E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.126568E+11 | 0.125758E+11 | 0.129782E+11 | 0.572103E+10 | 0.725716E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.507870E+09 | 0.242393E+09 | 0.844832E+09 | 0.206137E+09 | 0.381293E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.156330E+10 | 0.198179E+10 | 0.138595E+10 | 0.768941E+09 | 0.768087E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM224
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.166813E+09 | 0.483628E+09 | 0.251946E+09 | 0.146788E+09 | 0.105158E+09 | 0.00 | 0.00 |
| February | 0.161736E+09 | 0.427416E+09 | 0.260073E+09 | 0.125206E+09 | 0.134867E+09 | 0.00 | 0.00 |
| March | 0.292454E+09 | 0.339669E+09 | 0.346487E+09 | 0.192235E+09 | 0.154252E+09 | 0.00 | 0.00 |
| April | 0.258322E+09 | 0.253322E+09 | 0.285132E+09 | 0.115706E+09 | 0.169426E+09 | 0.00 | 0.00 |
| May | 0.259847E+09 | 0.168027E+09 | 0.254971E+09 | 73916805.40 | 0.181054E+09 | 0.00 | 0.00 |
| June | 0.287460E+09 | 97437023.53 | 0.240623E+09 | 51534154.87 | 0.189089E+09 | 0.00 | 0.00 |
| July | 0.349406E+09 | 61592377.20 | 0.252290E+09 | 60599085.67 | 0.191691E+09 | 0.00 | 0.00 |
| August | 0.377715E+09 | 85088094.11 | 0.281612E+09 | 89590638.70 | 0.192022E+09 | 0.00 | 0.00 |
| September | 0.388595E+09 | 0.143895E+09 | 0.323589E+09 | 0.159595E+09 | 0.163994E+09 | 0.00 | 0.00 |
| October | 0.310902E+09 | 0.244026E+09 | 0.316929E+09 | 0.181395E+09 | 0.135534E+09 | 0.00 | 0.00 |
| November | 0.180646E+09 | 0.318054E+09 | 0.219687E+09 | 0.124364E+09 | 95323344.21 | 0.00 | 0.00 |
| December | 0.129037E+09 | 0.475701E+09 | 0.211208E+09 | 0.109328E+09 | 0.101880E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.316293E+10 | 0.309786E+10 | 0.324455E+10 | 0.143026E+10 | 0.181429E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.129037E+09 | 61592377.20 | 0.211208E+09 | 51534154.87 | 95323344.21 | 0.00 | 0.00 |
| Maximum of Months | 0.388595E+09 | 0.483628E+09 | 0.346487E+09 | 0.192235E+09 | 0.192022E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONTSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONTSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: REARSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDORFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 2784797.47 | 0.384006E+09 | 68912322.79 | 19536192.41 | 49376130.37 | 0.00 | 0.00 |
| February | 13809104.02 | 0.327530E+09 | 95492488.94 | 26632627.56 | 68859861.38 | 0.00 | 0.00 |
| March | 77716117.86 | 0.236592E+09 | 0.159075E+09 | 67461564.49 | 91613248.38 | 0.00 | 0.00 |
| April | 0.145831E+09 | 0.168179E+09 | 0.195146E+09 | 83138602.03 | 0.112008E+09 | 0.00 | 0.00 |
| May | 0.222203E+09 | 0.118771E+09 | 0.231835E+09 | 0.103588E+09 | 0.128247E+09 | 0.00 | 0.00 |
| June | 0.297870E+09 | 71239580.33 | 0.260967E+09 | 0.119222E+09 | 0.141746E+09 | 0.00 | 0.00 |
| July | 0.317519E+09 | 48326895.35 | 0.249335E+09 | 0.109382E+09 | 0.139953E+09 | 0.00 | 0.00 |
| August | 0.277706E+09 | 65981467.42 | 0.225185E+09 | 94881932.53 | 0.130303E+09 | 0.00 | 0.00 |
| September | 0.183400E+09 | 0.105950E+09 | 0.176210E+09 | 77015540.42 | 99194795.44 | 0.00 | 0.00 |
| October | 79244503.77 | 0.177494E+09 | 0.120906E+09 | 46360985.25 | 74544565.03 | 0.00 | 0.00 |
| November | 22081283.52 | 0.232746E+09 | 67557449.22 | 20429238.40 | 47128210.82 | 0.00 | 0.00 |
| December | 2439444.88 | 0.377485E+09 | 58521781.37 | 12401022.16 | 46120759.22 | 0.00 | 0.00 |
| Annual Sum or Average | 0.164260E+10 | 0.231430E+10 | 0.190914E+10 | 0.780050E+09 | 0.112909E+10 | 0.00 | 0.00 |
| Minimum of Months | 2439444.88 | 48326895.35 | 58521781.37 | 12401022.16 | 46120759.22 | 0.00 | 0.00 |
| Maximum of Months | 0.317519E+09 | 0.384006E+09 | 0.260967E+09 | 0.119222E+09 | 0.141746E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: REARSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM301
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 693.48 | 0.455565E+09 | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.00 |
| February | 1567868.23 | 0.388286E+09 | 80701846.22 | 0.00 | 80701846.22 | 0.00 | 0.00 |
| March | 28709948.86 | 0.306690E+09 | 0.108372E+09 | 3838.03 | 0.108368E+09 | 0.00 | 0.00 |
| April | 60130216.73 | 0.214046E+09 | 0.133701E+09 | 644640.69 | 0.133056E+09 | 0.00 | 0.00 |
| May | 0.108030E+09 | 0.148673E+09 | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.00 | 0.00 |
| June | 0.175636E+09 | 98092887.37 | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.00 | 0.00 |
| July | 0.203457E+09 | 71973914.33 | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.00 | 0.00 |
| August | 0.166612E+09 | 95472695.12 | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.00 | 0.00 |
| September | 91841659.56 | 0.142720E+09 | 0.114119E+09 | 50503.25 | 0.114068E+09 | 0.00 | 0.00 |
| October | 35475452.34 | 0.219840E+09 | 88110587.98 | 0.00 | 88110587.98 | 0.00 | 0.00 |
| November | 9879085.51 | 0.265444E+09 | 57298193.59 | 0.00 | 57298193.59 | 0.00 | 0.00 |
| December | 471360.38 | 0.427684E+09 | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 0.00 |
| Annual Sum or Average | 0.881812E+09 | 0.283449E+10 | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.00 | 0.00 |
| Minimum of Months | 693.48 | 71973914.33 | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 0.00 |
| Maximum of Months | 0.203457E+09 | 0.455565E+09 | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM302_305
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.185461E+10 | 0.234568E+09 | 0.00 | 0.234568E+09 | 0.00 | 0.00 |
| February | 5312721.20 | 0.158518E+10 | 0.322807E+09 | 0.00 | 0.322807E+09 | 0.00 | 0.00 |
| March | 0.112623E+09 | 0.126257E+10 | 0.433487E+09 | 15352.11 | 0.433472E+09 | 0.00 | 0.00 |
| April | 0.241066E+09 | 0.882586E+09 | 0.534803E+09 | 2578562.75 | 0.532225E+09 | 0.00 | 0.00 |
| May | 0.434025E+09 | 0.612406E+09 | 0.641975E+09 | 27642889.55 | 0.614333E+09 | 0.00 | 0.00 |
| June | 0.705807E+09 | 0.402823E+09 | 0.746943E+09 | 63513166.25 | 0.683429E+09 | 0.00 | 0.00 |
| July | 0.819640E+09 | 0.295508E+09 | 0.718845E+09 | 48900299.16 | 0.669944E+09 | 0.00 | 0.00 |
| August | 0.671669E+09 | 0.390725E+09 | 0.622355E+09 | 12014188.70 | 0.610341E+09 | 0.00 | 0.00 |
| September | 0.372454E+09 | 0.582478E+09 | 0.456475E+09 | 202013.01 | 0.456273E+09 | 0.00 | 0.00 |
| October | 0.142459E+09 | 0.901031E+09 | 0.352442E+09 | 0.00 | 0.352442E+09 | 0.00 | 0.00 |
| November | 38403423.87 | 0.109778E+10 | 0.229193E+09 | 0.00 | 0.229193E+09 | 0.00 | 0.00 |
| December | 1644936.78 | 0.174917E+10 | 0.219549E+09 | 0.00 | 0.219549E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.354510E+10 | 0.116169E+11 | 0.551344E+10 | 0.154866E+09 | 0.535858E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.295508E+09 | 0.219549E+09 | 0.00 | 0.219549E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.819640E+09 | 0.185461E+10 | 0.746943E+09 | 63513166.25 | 0.683429E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM306_308
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.139511E+10 | 0.169811E+09 | 0.00 | 0.169811E+09 | 0.00 | 0.00 |
| February | 3030129.78 | 0.119192E+10 | 0.233691E+09 | 0.00 | 0.233691E+09 | 0.00 | 0.00 |
| March | 76065910.52 | 0.954460E+09 | 0.313815E+09 | 11113.89 | 0.313804E+09 | 0.00 | 0.00 |
| April | 0.165863E+09 | 0.664623E+09 | 0.387161E+09 | 1866705.72 | 0.385294E+09 | 0.00 | 0.00 |
| May | 0.309275E+09 | 0.452537E+09 | 0.464747E+09 | 20011589.84 | 0.444735E+09 | 0.00 | 0.00 |
| June | 0.513642E+09 | 0.291308E+09 | 0.540736E+09 | 45979253.74 | 0.494757E+09 | 0.00 | 0.00 |
| July | 0.600323E+09 | 0.210040E+09 | 0.520395E+09 | 35400522.38 | 0.484994E+09 | 0.00 | 0.00 |
| August | 0.490799E+09 | 0.280187E+09 | 0.450543E+09 | 8697463.27 | 0.441846E+09 | 0.00 | 0.00 |
| September | 0.268199E+09 | 0.427279E+09 | 0.330457E+09 | 146243.81 | 0.330311E+09 | 0.00 | 0.00 |
| October | 97220322.60 | 0.677773E+09 | 0.255144E+09 | 0.00 | 0.255144E+09 | 0.00 | 0.00 |
| November | 24848008.23 | 0.835062E+09 | 0.165920E+09 | 0.00 | 0.165920E+09 | 0.00 | 0.00 |
| December | 946637.18 | 0.131497E+10 | 0.158938E+09 | 0.00 | 0.158938E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.255021E+10 | 0.869527E+10 | 0.399136E+10 | 0.112113E+09 | 0.387925E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.210040E+09 | 0.158938E+09 | 0.00 | 0.158938E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.600323E+09 | 0.139511E+10 | 0.540736E+09 | 45979253.74 | 0.494757E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM309_312
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.223282E+10 | 0.234568E+09 | 0.00 | 0.234568E+09 | 0.00 | 0.00 |
| February | 1469076.00 | 0.191890E+10 | 0.322807E+09 | 0.00 | 0.322807E+09 | 0.00 | 0.00 |
| March | 86232532.14 | 0.149645E+10 | 0.433487E+09 | 15352.11 | 0.433472E+09 | 0.00 | 0.00 |
| April | 0.196904E+09 | 0.981772E+09 | 0.534803E+09 | 2578562.75 | 0.532225E+09 | 0.00 | 0.00 |
| May | 0.424561E+09 | 0.597023E+09 | 0.641975E+09 | 27642889.55 | 0.614333E+09 | 0.00 | 0.00 |
| June | 0.765946E+09 | 0.341561E+09 | 0.746943E+09 | 63513166.25 | 0.683429E+09 | 0.00 | 0.00 |
| July | 0.924817E+09 | 0.215704E+09 | 0.718845E+09 | 48900299.16 | 0.669944E+09 | 0.00 | 0.00 |
| August | 0.739270E+09 | 0.307697E+09 | 0.622355E+09 | 12014188.70 | 0.610341E+09 | 0.00 | 0.00 |
| September | 0.377108E+09 | 0.553159E+09 | 0.456475E+09 | 202013.01 | 0.456273E+09 | 0.00 | 0.00 |
| October | 0.111323E+09 | 0.999938E+09 | 0.352442E+09 | 0.00 | 0.352442E+09 | 0.00 | 0.00 |
| November | 23780977.49 | 0.131307E+10 | 0.229193E+09 | 0.00 | 0.229193E+09 | 0.00 | 0.00 |
| December | 551705.21 | 0.210940E+10 | 0.219549E+09 | 0.00 | 0.219549E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.365196E+10 | 0.130675E+11 | 0.551344E+10 | 0.154866E+09 | 0.535858E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.215704E+09 | 0.219549E+09 | 0.00 | 0.219549E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.924817E+09 | 0.223282E+10 | 0.746943E+09 | 63513166.25 | 0.683429E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM313
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.461953E+09 | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.00 |
| February | 1587742.58 | 0.391729E+09 | 80701846.22 | 0.00 | 80701846.22 | 0.00 | 0.00 |
| March | 28749333.98 | 0.312550E+09 | 0.108372E+09 | 3838.03 | 0.108368E+09 | 0.00 | 0.00 |
| April | 61947968.06 | 0.217061E+09 | 0.133701E+09 | 644640.69 | 0.133056E+09 | 0.00 | 0.00 |
| May | 0.112296E+09 | 0.148489E+09 | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.00 | 0.00 |
| June | 0.182704E+09 | 96152588.80 | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.00 | 0.00 |
| July | 0.210826E+09 | 69711839.50 | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.00 | 0.00 |
| August | 0.172156E+09 | 93722236.51 | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.00 | 0.00 |
| September | 94906166.17 | 0.142929E+09 | 0.114119E+09 | 50503.25 | 0.114068E+09 | 0.00 | 0.00 |
| October | 35904565.57 | 0.225136E+09 | 88110587.98 | 0.00 | 88110587.98 | 0.00 | 0.00 |
| November | 9511653.96 | 0.274935E+09 | 57298193.59 | 0.00 | 57298193.59 | 0.00 | 0.00 |
| December | 442317.46 | 0.434513E+09 | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 0.00 |
| Annual Sum or Average | 0.911032E+09 | 0.286888E+10 | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 69711839.50 | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 0.00 |
| Maximum of Months | 0.210826E+09 | 0.461953E+09 | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM314
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.169876E+09 | 0.469168E+09 | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.00 | 0.00 |
| February | 0.165221E+09 | 0.416202E+09 | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.00 | 0.00 |
| March | 0.297003E+09 | 0.330935E+09 | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.00 | 0.00 |
| April | 0.261576E+09 | 0.247308E+09 | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.00 | 0.00 |
| May | 0.261125E+09 | 0.166227E+09 | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.00 | 0.00 |
| June | 0.287193E+09 | 98011244.34 | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.00 | 0.00 |
| July | 0.348379E+09 | 62372912.95 | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.00 | 0.00 |
| August | 0.377570E+09 | 85024431.63 | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.00 | 0.00 |
| September | 0.389918E+09 | 0.141283E+09 | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.00 | 0.00 |
| October | 0.314985E+09 | 0.235191E+09 | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.00 | 0.00 |
| November | 0.184246E+09 | 0.303487E+09 | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.00 | 0.00 |
| December | 0.131742E+09 | 0.460002E+09 | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.318883E+10 | 0.301521E+10 | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.131742E+09 | 62372912.95 | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.00 | 0.00 |
| Maximum of Months | 0.389918E+09 | 0.469168E+09 | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM315_318
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.641919E+09 | 0.204453E+10 | 0.100587E+10 | 0.586037E+09 | 0.419834E+09 | 0.00 | 0.00 |
| February | 0.613615E+09 | 0.180718E+10 | 0.103832E+10 | 0.499873E+09 | 0.538444E+09 | 0.00 | 0.00 |
| March | 0.113427E+10 | 0.142634E+10 | 0.138332E+10 | 0.767482E+09 | 0.615837E+09 | 0.00 | 0.00 |
| April | 0.100631E+10 | 0.106530E+10 | 0.113836E+10 | 0.461945E+09 | 0.676420E+09 | 0.00 | 0.00 |
| May | 0.101487E+10 | 0.718650E+09 | 0.101795E+10 | 0.295106E+09 | 0.722843E+09 | 0.00 | 0.00 |
| June | 0.112264E+10 | 0.425152E+09 | 0.960666E+09 | 0.205745E+09 | 0.754920E+09 | 0.00 | 0.00 |
| July | 0.137038E+10 | 0.272993E+09 | 0.100725E+10 | 0.241936E+09 | 0.765310E+09 | 0.00 | 0.00 |
| August | 0.148903E+10 | 0.369296E+09 | 0.112431E+10 | 0.357683E+09 | 0.766630E+09 | 0.00 | 0.00 |
| September | 0.153749E+10 | 0.610022E+09 | 0.129190E+10 | 0.637169E+09 | 0.654730E+09 | 0.00 | 0.00 |
| October | 0.122764E+10 | 0.101371E+10 | 0.126531E+10 | 0.724203E+09 | 0.541106E+09 | 0.00 | 0.00 |
| November | 0.708004E+09 | 0.132625E+10 | 0.877081E+09 | 0.496511E+09 | 0.380570E+09 | 0.00 | 0.00 |
| December | 0.494784E+09 | 0.201036E+10 | 0.843229E+09 | 0.436483E+09 | 0.406746E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.123609E+11 | 0.130898E+11 | 0.129536E+11 | 0.571017E+10 | 0.724339E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.494784E+09 | 0.272993E+09 | 0.843229E+09 | 0.205745E+09 | 0.380570E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.153749E+10 | 0.204453E+10 | 0.138332E+10 | 0.767482E+09 | 0.766630E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ELEVATORCOREFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM319
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.159286E+09 | 0.516966E+09 | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.00 | 0.00 |
| February | 0.152124E+09 | 0.455877E+09 | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.00 | 0.00 |
| March | 0.277118E+09 | 0.376839E+09 | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.00 | 0.00 |
| April | 0.242785E+09 | 0.292483E+09 | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.00 | 0.00 |
| May | 0.239180E+09 | 0.213265E+09 | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.00 | 0.00 |
| June | 0.258100E+09 | 0.134563E+09 | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.00 | 0.00 |
| July | 0.314284E+09 | 94829850.90 | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.00 | 0.00 |
| August | 0.347902E+09 | 0.122532E+09 | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.00 | 0.00 |
| September | 0.366327E+09 | 0.185145E+09 | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.00 | 0.00 |
| October | 0.296278E+09 | 0.284143E+09 | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.00 | 0.00 |
| November | 0.172479E+09 | 0.352898E+09 | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.00 | 0.00 |
| December | 0.122620E+09 | 0.508101E+09 | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.294848E+10 | 0.353764E+10 | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.122620E+09 | 94829850.90 | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.00 | 0.00 |
| Maximum of Months | 0.366327E+09 | 0.516966E+09 | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM320_323
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.662199E+09 | 0.194118E+10 | 0.100587E+10 | 0.586037E+09 | 0.419834E+09 | 0.00 | 0.00 |
| February | 0.639847E+09 | 0.172093E+10 | 0.103832E+10 | 0.499873E+09 | 0.538444E+09 | 0.00 | 0.00 |
| March | 0.116723E+10 | 0.135826E+10 | 0.138332E+10 | 0.767482E+09 | 0.615837E+09 | 0.00 | 0.00 |
| April | 0.103649E+10 | 0.100572E+10 | 0.113836E+10 | 0.461945E+09 | 0.676420E+09 | 0.00 | 0.00 |
| May | 0.104723E+10 | 0.664679E+09 | 0.101795E+10 | 0.295106E+09 | 0.722843E+09 | 0.00 | 0.00 |
| June | 0.116178E+10 | 0.383792E+09 | 0.960666E+09 | 0.205745E+09 | 0.754920E+09 | 0.00 | 0.00 |
| July | 0.141505E+10 | 0.237864E+09 | 0.100725E+10 | 0.241936E+09 | 0.765310E+09 | 0.00 | 0.00 |
| August | 0.152748E+10 | 0.327067E+09 | 0.112431E+10 | 0.357683E+09 | 0.766630E+09 | 0.00 | 0.00 |
| September | 0.156785E+10 | 0.559687E+09 | 0.129190E+10 | 0.637169E+09 | 0.654730E+09 | 0.00 | 0.00 |
| October | 0.125552E+10 | 0.953054E+09 | 0.126531E+10 | 0.724203E+09 | 0.541106E+09 | 0.00 | 0.00 |
| November | 0.728274E+09 | 0.124725E+10 | 0.877081E+09 | 0.496511E+09 | 0.380570E+09 | 0.00 | 0.00 |
| December | 0.512964E+09 | 0.190322E+10 | 0.843229E+09 | 0.436483E+09 | 0.406746E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.127219E+11 | 0.123027E+11 | 0.129536E+11 | 0.571017E+10 | 0.724339E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.512964E+09 | 0.237864E+09 | 0.843229E+09 | 0.205745E+09 | 0.380570E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.156785E+10 | 0.194118E+10 | 0.138332E+10 | 0.767482E+09 | 0.766630E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM324
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.172635E+09 | 0.441079E+09 | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.00 | 0.00 |
| February | 0.169019E+09 | 0.388831E+09 | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.00 | 0.00 |
| March | 0.297789E+09 | 0.324974E+09 | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.00 | 0.00 |
| April | 0.260746E+09 | 0.250409E+09 | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.00 | 0.00 |
| May | 0.256763E+09 | 0.178755E+09 | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.00 | 0.00 |
| June | 0.275704E+09 | 0.112142E+09 | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.00 | 0.00 |
| July | 0.329443E+09 | 78498784.27 | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.00 | 0.00 |
| August | 0.361625E+09 | 0.103441E+09 | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.00 | 0.00 |
| September | 0.379969E+09 | 0.158649E+09 | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.00 | 0.00 |
| October | 0.312090E+09 | 0.244030E+09 | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.00 | 0.00 |
| November | 0.184646E+09 | 0.300131E+09 | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.00 | 0.00 |
| December | 0.134364E+09 | 0.430582E+09 | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.313479E+10 | 0.301152E+10 | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.134364E+09 | 78498784.27 | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.00 | 0.00 |
| Maximum of Months | 0.379969E+09 | 0.441079E+09 | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONTSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONTSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: REARSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORRIDORFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 3040220.16 | 0.371043E+09 | 68912322.79 | 19536192.41 | 49376130.37 | 0.00 | 0.00 |
| February | 14154921.53 | 0.316865E+09 | 95492488.94 | 26632627.56 | 68859861.38 | 0.00 | 0.00 |
| March | 78207713.62 | 0.225624E+09 | 0.159075E+09 | 67461564.49 | 91613248.38 | 0.00 | 0.00 |
| April | 0.144853E+09 | 0.156798E+09 | 0.195146E+09 | 83138602.03 | 0.112008E+09 | 0.00 | 0.00 |
| May | 0.220493E+09 | 0.107395E+09 | 0.231835E+09 | 0.103588E+09 | 0.128247E+09 | 0.00 | 0.00 |
| June | 0.294901E+09 | 65279485.17 | 0.260967E+09 | 0.119222E+09 | 0.141746E+09 | 0.00 | 0.00 |
| July | 0.313724E+09 | 44368676.36 | 0.249335E+09 | 0.109382E+09 | 0.139953E+09 | 0.00 | 0.00 |
| August | 0.274745E+09 | 60687458.39 | 0.225185E+09 | 94881932.53 | 0.130303E+09 | 0.00 | 0.00 |
| September | 0.182721E+09 | 96177659.48 | 0.176210E+09 | 77015540.42 | 99194795.44 | 0.00 | 0.00 |
| October | 80186837.85 | 0.163227E+09 | 0.120906E+09 | 46360985.25 | 74544565.03 | 0.00 | 0.00 |
| November | 22757426.45 | 0.219186E+09 | 67557449.22 | 20429238.40 | 47128210.82 | 0.00 | 0.00 |
| December | 2585891.31 | 0.364369E+09 | 58521781.37 | 12401022.16 | 46120759.22 | 0.00 | 0.00 |
| Annual Sum or Average | 0.163237E+10 | 0.219102E+10 | 0.190914E+10 | 0.780050E+09 | 0.112909E+10 | 0.00 | 0.00 |
| Minimum of Months | 2585891.31 | 44368676.36 | 58521781.37 | 12401022.16 | 46120759.22 | 0.00 | 0.00 |
| Maximum of Months | 0.313724E+09 | 0.371043E+09 | 0.260967E+09 | 0.119222E+09 | 0.141746E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: REARSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM401
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.522214E+09 | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.00 |
| February | 669991.85 | 0.448722E+09 | 80701846.22 | 0.00 | 80701846.22 | 0.00 | 0.00 |
| March | 24089998.82 | 0.344285E+09 | 0.108372E+09 | 3838.03 | 0.108368E+09 | 0.00 | 0.00 |
| April | 50157317.23 | 0.222830E+09 | 0.133701E+09 | 644640.69 | 0.133056E+09 | 0.00 | 0.00 |
| May | 99850086.11 | 0.135262E+09 | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.00 | 0.00 |
| June | 0.180319E+09 | 77858111.25 | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.00 | 0.00 |
| July | 0.218659E+09 | 48773157.13 | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.00 | 0.00 |
| August | 0.174570E+09 | 70139469.16 | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.00 | 0.00 |
| September | 89225688.81 | 0.125758E+09 | 0.114119E+09 | 50503.25 | 0.114068E+09 | 0.00 | 0.00 |
| October | 30444266.28 | 0.223185E+09 | 88110587.98 | 0.00 | 88110587.98 | 0.00 | 0.00 |
| November | 7722825.73 | 0.290595E+09 | 57298193.59 | 0.00 | 57298193.59 | 0.00 | 0.00 |
| December | 286394.60 | 0.490203E+09 | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 0.00 |
| Annual Sum or Average | 0.875994E+09 | 0.299982E+10 | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 48773157.13 | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 0.00 |
| Maximum of Months | 0.218659E+09 | 0.522214E+09 | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM402_405
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 73059.49 | 0.170748E+10 | 0.234568E+09 | 0.00 | 0.234568E+09 | 0.00 | 0.00 |
| February | 6640063.06 | 0.145975E+10 | 0.322807E+09 | 0.00 | 0.322807E+09 | 0.00 | 0.00 |
| March | 0.110367E+09 | 0.112513E+10 | 0.433487E+09 | 15352.11 | 0.433472E+09 | 0.00 | 0.00 |
| April | 0.222791E+09 | 0.752146E+09 | 0.534803E+09 | 2578562.75 | 0.532225E+09 | 0.00 | 0.00 |
| May | 0.390231E+09 | 0.521457E+09 | 0.641975E+09 | 27642889.55 | 0.614333E+09 | 0.00 | 0.00 |
| June | 0.652241E+09 | 0.347607E+09 | 0.746943E+09 | 63513166.25 | 0.683429E+09 | 0.00 | 0.00 |
| July | 0.763966E+09 | 0.254811E+09 | 0.718845E+09 | 48900299.16 | 0.669944E+09 | 0.00 | 0.00 |
| August | 0.619970E+09 | 0.335411E+09 | 0.622355E+09 | 12014188.70 | 0.610341E+09 | 0.00 | 0.00 |
| September | 0.339051E+09 | 0.496450E+09 | 0.456475E+09 | 202013.01 | 0.456273E+09 | 0.00 | 0.00 |
| October | 0.139734E+09 | 0.758931E+09 | 0.352442E+09 | 0.00 | 0.352442E+09 | 0.00 | 0.00 |
| November | 40681464.59 | 0.924902E+09 | 0.229193E+09 | 0.00 | 0.229193E+09 | 0.00 | 0.00 |
| December | 2299926.23 | 0.159283E+10 | 0.219549E+09 | 0.00 | 0.219549E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.328804E+10 | 0.102769E+11 | 0.551344E+10 | 0.154866E+09 | 0.535858E+10 | 0.00 | 0.00 |
| Minimum of Months | 73059.49 | 0.254811E+09 | 0.219549E+09 | 0.00 | 0.219549E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.763966E+09 | 0.170748E+10 | 0.746943E+09 | 63513166.25 | 0.683429E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM406_408
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 8994.40 | 0.126017E+10 | 0.169811E+09 | 0.00 | 0.169811E+09 | 0.00 | 0.00 |
| February | 3989836.09 | 0.107746E+10 | 0.233691E+09 | 0.00 | 0.233691E+09 | 0.00 | 0.00 |
| March | 75897144.57 | 0.838240E+09 | 0.313815E+09 | 11113.89 | 0.313804E+09 | 0.00 | 0.00 |
| April | 0.155111E+09 | 0.565023E+09 | 0.387161E+09 | 1866705.72 | 0.385294E+09 | 0.00 | 0.00 |
| May | 0.279806E+09 | 0.386917E+09 | 0.464747E+09 | 20011589.84 | 0.444735E+09 | 0.00 | 0.00 |
| June | 0.474302E+09 | 0.253823E+09 | 0.540736E+09 | 45979253.74 | 0.494757E+09 | 0.00 | 0.00 |
| July | 0.557531E+09 | 0.183946E+09 | 0.520395E+09 | 35400522.38 | 0.484994E+09 | 0.00 | 0.00 |
| August | 0.451927E+09 | 0.243630E+09 | 0.450543E+09 | 8697463.27 | 0.441846E+09 | 0.00 | 0.00 |
| September | 0.244938E+09 | 0.366750E+09 | 0.330457E+09 | 146243.81 | 0.330311E+09 | 0.00 | 0.00 |
| October | 96592777.45 | 0.570886E+09 | 0.255144E+09 | 0.00 | 0.255144E+09 | 0.00 | 0.00 |
| November | 26812945.72 | 0.698072E+09 | 0.165920E+09 | 0.00 | 0.165920E+09 | 0.00 | 0.00 |
| December | 1372967.54 | 0.117683E+10 | 0.158938E+09 | 0.00 | 0.158938E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.236829E+10 | 0.762174E+10 | 0.399136E+10 | 0.112113E+09 | 0.387925E+10 | 0.00 | 0.00 |
| Minimum of Months | 8994.40 | 0.183946E+09 | 0.158938E+09 | 0.00 | 0.158938E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.557531E+09 | 0.126017E+10 | 0.540736E+09 | 45979253.74 | 0.494757E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM409_412
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.214609E+10 | 0.234568E+09 | 0.00 | 0.234568E+09 | 0.00 | 0.00 |
| February | 1457995.32 | 0.184734E+10 | 0.322807E+09 | 0.00 | 0.322807E+09 | 0.00 | 0.00 |
| March | 81069143.31 | 0.143639E+10 | 0.433487E+09 | 15352.11 | 0.433472E+09 | 0.00 | 0.00 |
| April | 0.176896E+09 | 0.930806E+09 | 0.534803E+09 | 2578562.75 | 0.532225E+09 | 0.00 | 0.00 |
| May | 0.386784E+09 | 0.556272E+09 | 0.641975E+09 | 27642889.55 | 0.614333E+09 | 0.00 | 0.00 |
| June | 0.720062E+09 | 0.311375E+09 | 0.746943E+09 | 63513166.25 | 0.683429E+09 | 0.00 | 0.00 |
| July | 0.879755E+09 | 0.191575E+09 | 0.718845E+09 | 48900299.16 | 0.669944E+09 | 0.00 | 0.00 |
| August | 0.698850E+09 | 0.278689E+09 | 0.622355E+09 | 12014188.70 | 0.610341E+09 | 0.00 | 0.00 |
| September | 0.350524E+09 | 0.517396E+09 | 0.456475E+09 | 202013.01 | 0.456273E+09 | 0.00 | 0.00 |
| October | 0.102842E+09 | 0.943029E+09 | 0.352442E+09 | 0.00 | 0.352442E+09 | 0.00 | 0.00 |
| November | 22312079.06 | 0.123789E+10 | 0.229193E+09 | 0.00 | 0.229193E+09 | 0.00 | 0.00 |
| December | 597658.34 | 0.202231E+10 | 0.219549E+09 | 0.00 | 0.219549E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.342115E+10 | 0.124192E+11 | 0.551344E+10 | 0.154866E+09 | 0.535858E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.191575E+09 | 0.219549E+09 | 0.00 | 0.219549E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.879755E+09 | 0.214609E+10 | 0.746943E+09 | 63513166.25 | 0.683429E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM413
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 18687.55 | 0.431535E+09 | 58642040.59 | 0.00 | 58642040.59 | 0.00 | 0.00 |
| February | 1976010.67 | 0.367127E+09 | 80701846.22 | 0.00 | 80701846.22 | 0.00 | 0.00 |
| March | 28841742.47 | 0.285050E+09 | 0.108372E+09 | 3838.03 | 0.108368E+09 | 0.00 | 0.00 |
| April | 59112537.70 | 0.191969E+09 | 0.133701E+09 | 644640.69 | 0.133056E+09 | 0.00 | 0.00 |
| May | 0.103846E+09 | 0.132244E+09 | 0.160494E+09 | 6910722.39 | 0.153583E+09 | 0.00 | 0.00 |
| June | 0.170772E+09 | 87598367.09 | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.00 | 0.00 |
| July | 0.197017E+09 | 64058612.42 | 0.179711E+09 | 12225074.79 | 0.167486E+09 | 0.00 | 0.00 |
| August | 0.160170E+09 | 85139910.37 | 0.155589E+09 | 3003547.17 | 0.152585E+09 | 0.00 | 0.00 |
| September | 88772547.62 | 0.127878E+09 | 0.114119E+09 | 50503.25 | 0.114068E+09 | 0.00 | 0.00 |
| October | 36230638.30 | 0.196652E+09 | 88110587.98 | 0.00 | 88110587.98 | 0.00 | 0.00 |
| November | 10200654.28 | 0.237752E+09 | 57298193.59 | 0.00 | 57298193.59 | 0.00 | 0.00 |
| December | 590654.38 | 0.402020E+09 | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 0.00 |
| Annual Sum or Average | 0.857548E+09 | 0.260902E+10 | 0.137836E+10 | 38716617.88 | 0.133964E+10 | 0.00 | 0.00 |
| Minimum of Months | 18687.55 | 64058612.42 | 54887190.27 | 0.00 | 54887190.27 | 0.00 | 0.00 |
| Maximum of Months | 0.197017E+09 | 0.431535E+09 | 0.186736E+09 | 15878291.56 | 0.170857E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM414
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.179682E+09 | 0.385665E+09 | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.00 | 0.00 |
| February | 0.175963E+09 | 0.343621E+09 | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.00 | 0.00 |
| March | 0.301786E+09 | 0.280996E+09 | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.00 | 0.00 |
| April | 0.258594E+09 | 0.218264E+09 | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.00 | 0.00 |
| May | 0.247687E+09 | 0.159776E+09 | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.00 | 0.00 |
| June | 0.262533E+09 | 0.103301E+09 | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.00 | 0.00 |
| July | 0.314994E+09 | 72964427.27 | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.00 | 0.00 |
| August | 0.350337E+09 | 94640254.70 | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.00 | 0.00 |
| September | 0.374012E+09 | 0.140994E+09 | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.00 | 0.00 |
| October | 0.313340E+09 | 0.210029E+09 | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.00 | 0.00 |
| November | 0.188578E+09 | 0.253982E+09 | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.00 | 0.00 |
| December | 0.140248E+09 | 0.376111E+09 | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.310775E+10 | 0.264034E+10 | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.140248E+09 | 72964427.27 | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.00 | 0.00 |
| Maximum of Months | 0.374012E+09 | 0.385665E+09 | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM415_418
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.657452E+09 | 0.187062E+10 | 0.100587E+10 | 0.586037E+09 | 0.419834E+09 | 0.00 | 0.00 |
| February | 0.632216E+09 | 0.166255E+10 | 0.103832E+10 | 0.499873E+09 | 0.538444E+09 | 0.00 | 0.00 |
| March | 0.114390E+10 | 0.129952E+10 | 0.138332E+10 | 0.767482E+09 | 0.615837E+09 | 0.00 | 0.00 |
| April | 0.100465E+10 | 0.958953E+09 | 0.113836E+10 | 0.461945E+09 | 0.676420E+09 | 0.00 | 0.00 |
| May | 0.100283E+10 | 0.629721E+09 | 0.101795E+10 | 0.295106E+09 | 0.722843E+09 | 0.00 | 0.00 |
| June | 0.110803E+10 | 0.360039E+09 | 0.960666E+09 | 0.205745E+09 | 0.754920E+09 | 0.00 | 0.00 |
| July | 0.135842E+10 | 0.217088E+09 | 0.100725E+10 | 0.241936E+09 | 0.765310E+09 | 0.00 | 0.00 |
| August | 0.147734E+10 | 0.302372E+09 | 0.112431E+10 | 0.357683E+09 | 0.766630E+09 | 0.00 | 0.00 |
| September | 0.153093E+10 | 0.526122E+09 | 0.129190E+10 | 0.637169E+09 | 0.654730E+09 | 0.00 | 0.00 |
| October | 0.123339E+10 | 0.903136E+09 | 0.126531E+10 | 0.724203E+09 | 0.541106E+09 | 0.00 | 0.00 |
| November | 0.717602E+09 | 0.118961E+10 | 0.877081E+09 | 0.496511E+09 | 0.380570E+09 | 0.00 | 0.00 |
| December | 0.508985E+09 | 0.183499E+10 | 0.843229E+09 | 0.436483E+09 | 0.406746E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.123758E+11 | 0.117547E+11 | 0.129536E+11 | 0.571017E+10 | 0.724339E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.508985E+09 | 0.217088E+09 | 0.843229E+09 | 0.205745E+09 | 0.380570E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.153093E+10 | 0.187062E+10 | 0.138332E+10 | 0.767482E+09 | 0.766630E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ELEVATORCOREFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM419
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.164309E+09 | 0.475280E+09 | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.00 | 0.00 |
| February | 0.157667E+09 | 0.422811E+09 | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.00 | 0.00 |
| March | 0.285687E+09 | 0.330883E+09 | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.00 | 0.00 |
| April | 0.251115E+09 | 0.244834E+09 | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.00 | 0.00 |
| May | 0.250671E+09 | 0.161428E+09 | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.00 | 0.00 |
| June | 0.277423E+09 | 92397573.10 | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.00 | 0.00 |
| July | 0.340434E+09 | 55779737.49 | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.00 | 0.00 |
| August | 0.369941E+09 | 77732915.40 | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.00 | 0.00 |
| September | 0.382684E+09 | 0.134709E+09 | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.00 | 0.00 |
| October | 0.307839E+09 | 0.230726E+09 | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.00 | 0.00 |
| November | 0.179101E+09 | 0.302944E+09 | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.00 | 0.00 |
| December | 0.127007E+09 | 0.466525E+09 | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.309388E+10 | 0.299605E+10 | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.127007E+09 | 55779737.49 | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.00 | 0.00 |
| Maximum of Months | 0.382684E+09 | 0.475280E+09 | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM420_423
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.662423E+09 | 0.185164E+10 | 0.100587E+10 | 0.586037E+09 | 0.419834E+09 | 0.00 | 0.00 |
| February | 0.638508E+09 | 0.164712E+10 | 0.103832E+10 | 0.499873E+09 | 0.538444E+09 | 0.00 | 0.00 |
| March | 0.115207E+10 | 0.128645E+10 | 0.138332E+10 | 0.767482E+09 | 0.615837E+09 | 0.00 | 0.00 |
| April | 0.101213E+10 | 0.947161E+09 | 0.113836E+10 | 0.461945E+09 | 0.676420E+09 | 0.00 | 0.00 |
| May | 0.101050E+10 | 0.618046E+09 | 0.101795E+10 | 0.295106E+09 | 0.722843E+09 | 0.00 | 0.00 |
| June | 0.111770E+10 | 0.350240E+09 | 0.960666E+09 | 0.205745E+09 | 0.754920E+09 | 0.00 | 0.00 |
| July | 0.136997E+10 | 0.208931E+09 | 0.100725E+10 | 0.241936E+09 | 0.765310E+09 | 0.00 | 0.00 |
| August | 0.148747E+10 | 0.292692E+09 | 0.112431E+10 | 0.357683E+09 | 0.766630E+09 | 0.00 | 0.00 |
| September | 0.153884E+10 | 0.514350E+09 | 0.129190E+10 | 0.637169E+09 | 0.654730E+09 | 0.00 | 0.00 |
| October | 0.124053E+10 | 0.890035E+09 | 0.126531E+10 | 0.724203E+09 | 0.541106E+09 | 0.00 | 0.00 |
| November | 0.722875E+09 | 0.117288E+10 | 0.877081E+09 | 0.496511E+09 | 0.380570E+09 | 0.00 | 0.00 |
| December | 0.513617E+09 | 0.181568E+10 | 0.843229E+09 | 0.436483E+09 | 0.406746E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.124667E+11 | 0.115952E+11 | 0.129536E+11 | 0.571017E+10 | 0.724339E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.513617E+09 | 0.208931E+09 | 0.843229E+09 | 0.205745E+09 | 0.380570E+09 | 0.00 | 0.00 |
| Maximum of Months | 0.153884E+10 | 0.185164E+10 | 0.138332E+10 | 0.767482E+09 | 0.766630E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GUESTROOM424
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.170260E+09 | 0.454838E+09 | 0.251468E+09 | 0.146509E+09 | 0.104959E+09 | 0.00 | 0.00 |
| February | 0.164980E+09 | 0.405176E+09 | 0.259579E+09 | 0.124968E+09 | 0.134611E+09 | 0.00 | 0.00 |
| March | 0.293333E+09 | 0.318339E+09 | 0.345830E+09 | 0.191871E+09 | 0.153959E+09 | 0.00 | 0.00 |
| April | 0.256350E+09 | 0.235877E+09 | 0.284591E+09 | 0.115486E+09 | 0.169105E+09 | 0.00 | 0.00 |
| May | 0.254090E+09 | 0.155841E+09 | 0.254487E+09 | 73776539.16 | 0.180711E+09 | 0.00 | 0.00 |
| June | 0.279774E+09 | 89859322.66 | 0.240166E+09 | 51436362.46 | 0.188730E+09 | 0.00 | 0.00 |
| July | 0.341449E+09 | 54965157.42 | 0.251812E+09 | 60484091.44 | 0.191328E+09 | 0.00 | 0.00 |
| August | 0.371185E+09 | 76438655.33 | 0.281078E+09 | 89420629.43 | 0.191657E+09 | 0.00 | 0.00 |
| September | 0.384800E+09 | 0.131299E+09 | 0.322975E+09 | 0.159292E+09 | 0.163682E+09 | 0.00 | 0.00 |
| October | 0.312057E+09 | 0.222626E+09 | 0.316327E+09 | 0.181051E+09 | 0.135276E+09 | 0.00 | 0.00 |
| November | 0.183226E+09 | 0.289430E+09 | 0.219270E+09 | 0.124128E+09 | 95142456.52 | 0.00 | 0.00 |
| December | 0.132087E+09 | 0.446036E+09 | 0.210807E+09 | 0.109121E+09 | 0.101687E+09 | 0.00 | 0.00 |
| Annual Sum or Average | 0.314359E+10 | 0.288072E+10 | 0.323839E+10 | 0.142754E+10 | 0.181085E+10 | 0.00 | 0.00 |
| Minimum of Months | 0.132087E+09 | 54965157.42 | 0.210807E+09 | 51436362.46 | 95142456.52 | 0.00 | 0.00 |
| Maximum of Months | 0.384800E+09 | 0.454838E+09 | 0.345830E+09 | 0.191871E+09 | 0.191657E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONTSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: FRONTSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
| February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
| March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
| April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
| May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
| June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
| July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
| August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
| September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
| October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
| November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
| December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
| Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
| Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
| Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
| February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
| March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
| April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
| May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
| June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
| July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
| August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
| September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
| October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
| November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
| December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
| Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
| February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
| March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
| April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
| May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
| June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
| July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
| August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
| September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
| October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
| November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
| December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
| Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
| February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
| March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
| April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
| May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
| June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
| July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
| August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
| September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
| October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
| November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
| December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
| Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
| February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
| March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
| April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
| May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
| June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
| July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
| August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
| September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
| October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
| November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
| December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
| Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH SHOWER WATER HEATER
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.238699E+11 | -0.227762E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.109376E+10 | 60.05 | 0.00 | 0.00 |
| February | 0.218784E+11 | -0.208825E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -995853405.5 | 60.05 | 0.00 | 0.00 |
| March | 0.239185E+11 | -0.228463E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.107223E+10 | 60.05 | 0.00 | 0.00 |
| April | 0.222193E+11 | -0.212091E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -0.101020E+10 | 60.05 | 0.00 | 0.00 |
| May | 0.217106E+11 | -0.207053E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100531E+10 | 60.05 | 0.00 | 0.00 |
| June | 0.197777E+11 | -0.188396E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -938153789.2 | 60.05 | 0.00 | 0.00 |
| July | 0.194561E+11 | -0.185021E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -953930257.1 | 60.05 | 0.00 | 0.00 |
| August | 0.191476E+11 | -0.181943E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -953254332.9 | 60.05 | 0.00 | 0.00 |
| September | 0.188217E+11 | -0.178863E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -935339460.4 | 60.05 | 0.00 | 0.00 |
| October | 0.203958E+11 | -0.193923E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.100351E+10 | 60.05 | 0.00 | 0.00 |
| November | 0.209590E+11 | -0.199600E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -999044986.4 | 60.05 | 0.00 | 0.00 |
| December | 0.229356E+11 | -0.218538E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.108179E+10 | 60.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.255090E+12 | -0.243048E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120424E+11 | 60.05 | 0.00 | 0.00 |
| Minimum of Months | 0.188217E+11 | -0.228463E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.109376E+10 | 60.05 | 0.00 | 0.00 |
| Maximum of Months | 0.239185E+11 | -0.178863E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -935339460.4 | 60.05 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH LAUNDRY WATER HEATER
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.369022E+11 | -0.363331E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -569062474.3 | 82.27 | 0.00 | 0.00 |
| February | 0.336686E+11 | -0.331458E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -522761935.1 | 82.27 | 0.00 | 0.00 |
| March | 0.368912E+11 | -0.363499E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -541276732.3 | 82.28 | 0.00 | 0.00 |
| April | 0.347280E+11 | -0.342156E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -512474220.9 | 82.28 | 0.00 | 0.00 |
| May | 0.344827E+11 | -0.339735E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -509133993.2 | 82.28 | 0.00 | 0.00 |
| June | 0.319957E+11 | -0.315256E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -470106661.6 | 82.28 | 0.00 | 0.00 |
| July | 0.320112E+11 | -0.315426E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -468669401.1 | 82.28 | 0.00 | 0.00 |
| August | 0.316106E+11 | -0.311473E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -463361741.7 | 82.28 | 0.00 | 0.00 |
| September | 0.309463E+11 | -0.304922E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -454096996.2 | 82.28 | 0.00 | 0.00 |
| October | 0.330199E+11 | -0.325220E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -497816213.4 | 82.28 | 0.00 | 0.00 |
| November | 0.333235E+11 | -0.328160E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -507556042.1 | 82.28 | 0.00 | 0.00 |
| December | 0.358667E+11 | -0.353001E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -566565040.0 | 82.27 | 0.00 | 0.00 |
| Annual Sum or Average | 0.405446E+12 | -0.399364E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.608288E+10 | 82.28 | 0.00 | 0.00 |
| Minimum of Months | 0.309463E+11 | -0.363499E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -569062474.3 | 82.27 | 0.00 | 0.00 |
| Maximum of Months | 0.369022E+11 | -0.304922E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -454096996.2 | 82.28 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 255.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 262.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 339.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 371.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 332.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 430.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 406.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 289.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 314.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 258.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3928.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 230.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 439.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONTSTAIRSFLR1 UNITHEATER HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 13066130.32 | 265.94 | 07-FEB-10:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 13066130.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 13066130.32 | 265.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONTSTAIRSFLR2 UNITHEATER HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 24790990.58 | 324.77 | 07-FEB-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 24790990.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 24790990.58 | 324.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONTSTAIRSFLR3 UNITHEATER HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 3539002.12 | 183.58 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 61287826.75 | 404.27 | 06-FEB-09:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 9326070.80 | 176.52 | 09-DEC-20:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 74152899.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 61287826.75 | 404.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: FRONTSTAIRSFLR4 UNITHEATER HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 32341192.68 | 519.80 | 12-JAN-09:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.142776E+09 | 652.14 | 06-FEB-09:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 68926918.11 | 411.36 | 26-DEC-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.244044E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.142776E+09 | 652.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: REARSTAIRSFLR1 UNITHEATER HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: REARSTAIRSFLR2 UNITHEATER HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 498423.62 | 81.37 | 07-FEB-10:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 498423.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 498423.62 | 81.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: REARSTAIRSFLR3 UNITHEATER HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 6203295.59 | 81.38 | 06-FEB-09:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 6203295.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 6203295.59 | 81.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: REARSTAIRSFLR4 UNITHEATER HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 14204430.46 | 290.54 | 12-JAN-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 73748911.88 | 290.54 | 05-FEB-22:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 23509455.71 | 290.54 | 26-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.111463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 73748911.88 | 290.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: MECHRM UNITHEATER HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 101 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 102 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 134537.15 | 118.84 | 06-FEB-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 134537.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 134537.15 | 118.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 103 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.133012E+10 | 2096.53 | 31-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.139580E+10 | 2107.53 | 07-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.832004E+09 | 2087.26 | 06-MAR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.257594E+09 | 2035.31 | 16-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 11515483.50 | 952.32 | 08-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 138959.61 | 506.57 | 15-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 281769.94 | 426.54 | 29-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 22739246.87 | 902.52 | 18-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.161360E+09 | 1437.95 | 30-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.109672E+10 | 2099.11 | 11-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.510828E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.139580E+10 | 2107.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 104 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.644139E+09 | 2384.52 | 31-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.731852E+09 | 2422.30 | 07-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.284033E+09 | 1477.07 | 04-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 69900631.72 | 1351.00 | 16-APR-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1015527.09 | 958.38 | 05-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 134593.24 | 482.66 | 14-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 886.19 | 14.77 | 13-JUL-08:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 18111.90 | 165.78 | 31-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 159653.52 | 349.53 | 01-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 2316108.21 | 966.48 | 24-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 26918048.94 | 1395.42 | 21-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.536272E+09 | 2378.47 | 11-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.229676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 886.19 | 14.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.731852E+09 | 2422.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 105 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 24297118.61 | 2090.13 | 09-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 55110224.54 | 2052.60 | 07-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 5886184.00 | 1045.97 | 06-MAR-16:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 2666847.47 | 681.26 | 04-APR-18:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 990739.46 | 681.36 | 13-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 120937.51 | 537.81 | 15-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 6185.99 | 78.78 | 06-JUL-21:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 9502.14 | 48.34 | 02-AUG-08:37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 74804.30 | 615.30 | 29-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 1342831.31 | 626.09 | 19-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 2881989.47 | 681.27 | 23-NOV-16:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 23205944.76 | 2028.70 | 12-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.116593E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 6185.99 | 48.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 55110224.54 | 2090.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 201 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 22448460.42 | 441.27 | 31-JAN-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 77056678.23 | 740.37 | 21-FEB-15:35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 1479549.80 | 241.88 | 06-MAR-15:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 40870960.00 | 732.35 | 26-DEC-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.141856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 77056678.23 | 740.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 202_205 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.324506E+10 | 7986.38 | 31-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.311849E+10 | 8005.10 | 06-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.164728E+10 | 7902.57 | 06-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.321200E+09 | 4542.72 | 13-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 2605991.85 | 2728.29 | 08-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 166757.09 | 1127.71 | 15-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 17853.18 | 297.55 | 06-JUL-08:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 680394.86 | 1770.65 | 28-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.134960E+09 | 3726.09 | 27-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.583205E+09 | 4863.47 | 23-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.286941E+10 | 7973.35 | 10-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.119231E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.324506E+10 | 8005.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 206_208 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.207276E+10 | 6314.95 | 31-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.203260E+10 | 6358.33 | 06-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.978198E+09 | 6232.77 | 06-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.135591E+09 | 3824.40 | 05-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1086904.58 | 1280.82 | 12-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 109451.63 | 1013.47 | 15-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 12758.49 | 212.64 | 06-JUL-08:58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 445478.97 | 1329.96 | 05-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 50833755.43 | 3532.22 | 17-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.255832E+09 | 3752.05 | 03-NOV-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.180911E+10 | 6295.87 | 10-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.733658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.207276E+10 | 6358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 209_212 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.233862E+10 | 7780.04 | 31-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.231991E+10 | 7833.09 | 06-FEB-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.115112E+10 | 7678.81 | 06-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.175548E+09 | 4722.94 | 17-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 2029005.06 | 1961.94 | 12-MAY-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 180649.20 | 1290.88 | 15-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 694713.02 | 1861.27 | 29-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 52834069.76 | 3692.80 | 18-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.275788E+09 | 5124.94 | 24-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.202054E+10 | 7753.77 | 10-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.833726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.233862E+10 | 7833.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 213 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.141855E+10 | 2120.40 | 30-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.139993E+10 | 2128.87 | 07-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.747701E+09 | 2109.79 | 06-MAR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.195201E+09 | 2057.23 | 16-APR-15:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 3569156.52 | 656.57 | 01-MAY-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 81473.29 | 306.77 | 09-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 17812.03 | 296.87 | 31-AUG-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 389991.73 | 640.48 | 29-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 66969551.75 | 928.03 | 27-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.297911E+09 | 2048.48 | 30-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.129004E+10 | 2124.13 | 11-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.542036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.141855E+10 | 2128.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 214 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.475194E+09 | 2529.47 | 24-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.531186E+09 | 2570.01 | 07-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.140704E+09 | 1502.82 | 07-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 17275231.38 | 1302.12 | 13-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1119799.16 | 671.32 | 11-MAY-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 182374.96 | 535.60 | 06-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 8704.12 | 145.07 | 06-JUL-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 8799.04 | 146.65 | 31-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 341789.07 | 585.20 | 29-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 3080361.68 | 761.94 | 14-OCT-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 18290680.96 | 1224.42 | 22-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.440684E+09 | 2533.44 | 26-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.162808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 8704.12 | 145.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.531186E+09 | 2570.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 215_218 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 219 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 1614631.24 | 1155.21 | 31-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 1544431.19 | 1522.89 | 07-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 968463.27 | 902.35 | 07-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 457647.87 | 758.55 | 17-APR-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 16550.41 | 218.06 | 08-MAY-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 139504.81 | 414.76 | 24-OCT-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 515129.12 | 662.94 | 22-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 1524566.15 | 1310.74 | 11-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 6780924.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 1614631.24 | 1522.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 220_223 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.136051E+10 | 7109.06 | 28-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.143644E+10 | 7192.13 | 05-FEB-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.426558E+09 | 6900.48 | 07-MAR-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 58694771.93 | 5022.26 | 17-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 2925169.06 | 3608.40 | 01-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 606033.71 | 3069.52 | 14-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 37691.47 | 413.17 | 06-JUL-16:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 160834.84 | 833.60 | 23-AUG-08:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 228967.11 | 1252.23 | 29-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 14465840.84 | 3768.60 | 08-OCT-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 85643102.91 | 4241.19 | 11-NOV-16:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.123969E+10 | 6355.29 | 11-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.462596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 37691.47 | 413.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.143644E+10 | 7192.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 224 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.631192E+09 | 2511.47 | 31-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.664532E+09 | 2539.26 | 07-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.199914E+09 | 1466.94 | 24-MAR-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 34217195.86 | 1457.40 | 03-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1353926.38 | 723.82 | 11-MAY-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 230082.49 | 524.81 | 06-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 11242.35 | 106.10 | 06-JUL-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 412.48 | 6.87 | 31-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 324500.91 | 633.46 | 29-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 5477818.88 | 836.99 | 14-OCT-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 45495837.87 | 1420.01 | 07-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.591616E+09 | 2512.07 | 28-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.217437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 412.48 | 6.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.664532E+09 | 2539.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 301 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.428813E+09 | 873.74 | 13-JAN-16:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.423139E+09 | 825.58 | 06-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 97190419.88 | 449.31 | 06-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.384916E+09 | 624.93 | 26-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.133406E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.428813E+09 | 873.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 302_305 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.337246E+09 | 1864.28 | 30-JAN-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.383704E+09 | 2165.26 | 06-FEB-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 41820975.20 | 1442.01 | 06-MAR-15:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.393804E+09 | 1820.59 | 06-DEC-15:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.115658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.393804E+09 | 2165.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 306_308 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 36908289.00 | 1854.81 | 31-JAN-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.103082E+09 | 1600.92 | 21-FEB-15:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 3093669.89 | 864.46 | 06-MAR-15:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 53018601.10 | 1739.33 | 26-DEC-15:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.196103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.103082E+09 | 1854.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 309_312 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.311074E+10 | 7638.22 | 31-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.296965E+10 | 7660.24 | 06-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.153567E+10 | 7554.09 | 06-MAR-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.321690E+09 | 5075.96 | 16-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 5359000.20 | 2939.08 | 08-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 370558.49 | 1632.35 | 13-JUN-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 15260.11 | 157.73 | 21-AUG-08:59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 1337530.23 | 2081.08 | 05-SEP-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.177688E+09 | 4115.37 | 18-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.649009E+09 | 5765.23 | 30-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.280923E+10 | 7624.93 | 10-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.115808E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.311074E+10 | 7660.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 313 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.181185E+09 | 520.14 | 31-JAN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.210661E+09 | 803.96 | 05-FEB-15:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 21578870.80 | 335.56 | 06-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.193277E+09 | 516.23 | 10-DEC-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.606702E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.210661E+09 | 803.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 314 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.102354E+10 | 2398.23 | 31-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.102966E+10 | 2408.67 | 07-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.379944E+09 | 2347.00 | 07-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 91329524.81 | 1461.74 | 17-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 1181709.91 | 758.92 | 06-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 217892.40 | 710.04 | 15-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 10726.11 | 97.63 | 07-JUL-16:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 1757.43 | 29.29 | 01-AUG-08:47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 323721.91 | 830.74 | 30-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 34777521.58 | 1116.85 | 30-OCT-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.188730E+09 | 2322.56 | 30-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.995878E+09 | 2400.45 | 26-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.374560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 1757.43 | 29.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.102966E+10 | 2408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 315_318 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.680009E+09 | 7272.55 | 29-JAN-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.789578E+09 | 6177.86 | 10-FEB-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.165448E+09 | 4334.07 | 20-MAR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 15230328.98 | 3043.87 | 04-APR-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 2222742.20 | 3021.91 | 12-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 297059.74 | 2337.83 | 14-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 530193.28 | 2993.28 | 29-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 8575366.78 | 3198.99 | 14-OCT-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 23375315.61 | 3467.53 | 23-NOV-16:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.648374E+09 | 6611.36 | 10-DEC-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.233364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.789578E+09 | 7272.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 319 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 320_323 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.191417E+10 | 8514.49 | 26-JAN-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.192446E+10 | 8650.63 | 06-FEB-19:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.675293E+09 | 6716.64 | 04-MAR-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.140052E+09 | 5378.34 | 16-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 3132821.96 | 3902.21 | 04-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 575798.09 | 2874.85 | 14-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 213084.64 | 1166.30 | 06-JUL-16:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 135941.68 | 899.93 | 30-AUG-16:48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 685316.96 | 1147.43 | 10-SEP-16:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 63636478.12 | 3980.57 | 15-OCT-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.294804E+09 | 4972.44 | 21-NOV-09:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.181151E+10 | 8567.64 | 09-DEC-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.682868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 135941.68 | 899.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.192446E+10 | 8650.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 324 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 842313.50 | 134.75 | 06-FEB-15:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 842313.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 842313.50 | 134.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 401 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.250326E+10 | 2452.01 | 30-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.231118E+10 | 2460.27 | 07-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.140134E+10 | 2441.67 | 06-MAR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.591398E+09 | 2421.68 | 16-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 97239194.35 | 890.87 | 15-MAY-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 11465944.32 | 677.11 | 15-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 70599.13 | 705.79 | 31-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 31961476.08 | 770.82 | 28-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.440448E+09 | 2413.37 | 17-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.100957E+10 | 2417.95 | 24-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.237687E+10 | 2455.91 | 11-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.107748E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.250326E+10 | 2460.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 402_405 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.283236E+10 | 2690.47 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.257621E+10 | 3213.48 | 07-FEB-07:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.103083E+10 | 2536.50 | 07-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 46748055.11 | 1041.93 | 17-APR-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 27980434.89 | 698.86 | 17-OCT-06:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.202840E+09 | 1010.28 | 24-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.246148E+10 | 3187.43 | 11-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.917845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.283236E+10 | 3213.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 406_408 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.188283E+10 | 1993.13 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.172525E+10 | 2424.02 | 07-FEB-07:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.638357E+09 | 1851.26 | 07-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 19645100.31 | 659.45 | 17-APR-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 7813888.28 | 366.46 | 17-OCT-06:27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 74577608.50 | 649.48 | 24-NOV-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.161456E+10 | 2383.62 | 11-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.596303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.188283E+10 | 2424.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 409_412 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.484406E+10 | 9218.74 | 30-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.445877E+10 | 9251.77 | 07-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.255706E+10 | 9177.64 | 06-MAR-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.945703E+09 | 6195.00 | 17-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.145693E+09 | 3837.08 | 08-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 17715357.77 | 3770.59 | 14-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 9582.41 | 107.20 | 14-JUL-21:38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 152600.77 | 1002.42 | 12-AUG-21:57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 39331025.85 | 3203.96 | 30-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.662606E+09 | 8904.23 | 17-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.152775E+10 | 9016.55 | 29-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.445732E+10 | 9233.22 | 11-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.196562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 9582.41 | 107.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.484406E+10 | 9251.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 413 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.881843E+09 | 884.43 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.851332E+09 | 1070.16 | 07-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.295699E+09 | 732.61 | 07-MAR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 13292326.46 | 276.57 | 17-APR-05:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 2825238.75 | 123.82 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 33005320.36 | 237.56 | 24-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.779711E+09 | 936.92 | 11-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.285771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.881843E+09 | 1070.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 414 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.279701E+09 | 607.38 | 24-JAN-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.314834E+09 | 765.33 | 07-FEB-07:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 46917072.34 | 421.22 | 07-MAR-06:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.280081E+09 | 663.25 | 11-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.921534E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.314834E+09 | 765.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 415_418 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.306670E+10 | 10860.95 | 31-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.296114E+10 | 10915.74 | 06-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.144596E+10 | 6141.24 | 04-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.508636E+09 | 5271.22 | 16-APR-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 61678724.15 | 3268.10 | 03-MAY-16:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 6899882.96 | 2396.11 | 06-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 166915.91 | 797.81 | 10-JUL-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 404397.74 | 2794.22 | 31-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 10856101.02 | 2884.51 | 07-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.326896E+09 | 4444.73 | 27-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.781465E+09 | 10559.46 | 30-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.288250E+10 | 10865.16 | 26-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.120533E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 166915.91 | 797.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.306670E+10 | 10915.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 419 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.886472E+09 | 2885.46 | 31-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.863299E+09 | 2895.20 | 07-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.392107E+09 | 2033.41 | 20-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.123072E+09 | 1278.22 | 10-APR-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 8852497.68 | 1388.75 | 08-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 446400.07 | 328.45 | 09-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 27733.62 | 314.45 | 07-JUL-08:36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 43303.73 | 433.01 | 31-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 1463050.97 | 513.01 | 01-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 75036531.86 | 1273.63 | 15-OCT-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.207843E+09 | 2809.81 | 30-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.838501E+09 | 2887.29 | 26-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.339716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 27733.62 | 314.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.886472E+09 | 2895.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 420_423 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.327848E+10 | 10757.96 | 31-JAN-16:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.314494E+10 | 10797.83 | 07-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.156230E+10 | 6036.31 | 25-MAR-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.596780E+09 | 6110.67 | 16-APR-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 88721522.28 | 3389.77 | 11-MAY-15:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 12107954.67 | 2667.15 | 06-JUN-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 337812.18 | 1977.89 | 06-JUL-08:56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 421357.64 | 2840.84 | 31-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 18139925.30 | 3235.15 | 07-SEP-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.383958E+09 | 5137.15 | 24-OCT-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.901132E+09 | 10493.26 | 30-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.308774E+10 | 10759.68 | 26-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.130751E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 337812.18 | 1977.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.327848E+10 | 10797.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 424 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.141741E+10 | 2937.04 | 30-JAN-19:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.135699E+10 | 2944.30 | 07-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.643472E+09 | 2906.85 | 07-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.237941E+09 | 2857.36 | 17-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 25398985.47 | 1224.83 | 09-MAY-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 2082585.02 | 376.26 | 22-JUN-21:46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 8062.84 | 126.15 | 12-JUL-08:16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 66958.69 | 450.40 | 31-AUG-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 4174878.69 | 789.00 | 29-SEP-08:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.138304E+09 | 1526.22 | 30-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.391452E+09 | 2890.51 | 29-NOV-16:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.136846E+10 | 2939.99 | 11-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.558576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 8062.84 | 126.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.141741E+10 | 2944.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDORFLR1 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.275066E+10 | 28947.46 | 06-JAN-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.275898E+10 | 28686.10 | 07-FEB-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.153303E+10 | 27130.58 | 07-MAR-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.540290E+09 | 20842.46 | 17-APR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 48851327.15 | 8341.32 | 01-MAY-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 1424582.56 | 2685.70 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.233735E+09 | 15973.27 | 17-OCT-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.593012E+09 | 14996.82 | 25-NOV-07:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.239584E+10 | 27477.33 | 08-DEC-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.108558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.275898E+10 | 28947.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDORFLR2 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.933249E+09 | 1577.50 | 24-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.111229E+10 | 2340.40 | 07-FEB-17:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.137299E+09 | 970.44 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.888390E+09 | 2599.04 | 28-DEC-12:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.307123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.111229E+10 | 2599.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDORFLR3 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.454195E+10 | 3138.25 | 24-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.440326E+10 | 3639.66 | 07-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.189573E+10 | 2379.59 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.332979E+09 | 2397.82 | 17-APR-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 78177341.62 | 819.58 | 17-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.873935E+09 | 1848.06 | 22-NOV-19:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.432905E+10 | 3046.57 | 27-DEC-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.164551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.454195E+10 | 3639.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORRIDORFLR4 PTAC HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.765753E+10 | 4937.97 | 24-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.706853E+10 | 5417.14 | 07-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.392897E+10 | 4401.19 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.152857E+10 | 2922.61 | 17-APR-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.139381E+09 | 1183.11 | 07-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 7809049.91 | 526.70 | 14-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 33011973.18 | 975.09 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.107608E+10 | 2600.80 | 17-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.293824E+10 | 2949.65 | 24-NOV-04:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.737752E+10 | 4989.90 | 11-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.317557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.765753E+10 | 5417.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SAC_FRONTOFFICE HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.167210E+10 | 7688.51 | 31-JAN-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.190739E+10 | 7718.02 | 06-FEB-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.517142E+09 | 1796.25 | 07-MAR-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 60688653.28 | 1187.06 | 16-APR-11:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 17353018.87 | 644.20 | 24-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.133133E+10 | 7654.40 | 28-DEC-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.550600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.190739E+10 | 7718.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SAC_FRONTLOUNGE HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.135043E+11 | 20439.39 | 31-JAN-20:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.131018E+11 | 20715.51 | 06-FEB-11:18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.839922E+10 | 18024.17 | 01-MAR-02:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.345681E+10 | 6019.48 | 17-APR-02:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.453277E+09 | 3156.64 | 08-MAY-03:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 21151790.27 | 1219.21 | 14-JUN-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 20733930.59 | 1201.22 | 30-SEP-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.137571E+10 | 5129.87 | 17-OCT-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.383073E+10 | 5664.12 | 24-NOV-04:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.119963E+11 | 18084.12 | 07-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.561601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.135043E+11 | 20715.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SAC_MEETINGROOM HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.472004E+10 | 10067.32 | 12-JAN-11:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.474489E+10 | 10417.11 | 21-FEB-10:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.254565E+10 | 8348.69 | 06-MAR-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.482042E+09 | 5673.14 | 04-APR-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 261010.46 | 1211.97 | 11-MAY-17:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 82741928.91 | 4952.59 | 16-OCT-14:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.588455E+09 | 6008.50 | 22-NOV-15:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.396550E+10 | 10443.22 | 11-DEC-10:42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.171296E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.474489E+10 | 10443.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SAC_EMPLOYEELOUNGE HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 4825159.13 | 288.26 | 10-JAN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 34251921.39 | 743.74 | 07-FEB-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 241903.00 | 95.67 | 07-MAR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 12279087.98 | 476.31 | 11-DEC-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 51598071.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 34251921.39 | 743.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SAC_EXERCISECENTER HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.151397E+10 | 3612.28 | 30-JAN-01:14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.154756E+10 | 3626.55 | 21-FEB-02:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.739360E+09 | 3656.76 | 07-MAR-05:44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.262482E+09 | 1088.68 | 17-APR-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 24980143.70 | 528.67 | 01-MAY-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 489146.70 | 104.67 | 14-JUN-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 114331.42 | 47.48 | 30-SEP-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 79824035.83 | 758.55 | 17-OCT-05:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.241245E+09 | 1031.64 | 24-NOV-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.131850E+10 | 3634.96 | 27-DEC-01:52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.572853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.154756E+10 | 3656.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: SAC_RESTROOM HEATING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 101 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 519301.69 | 315624.42 | 152.43 | 21-JUL-14:09 | 89.22 | 0.00 |
| August | 0.00 | 0.00 | 224591.13 | 186188.73 | 66.13 | 10-AUG-14:35 | 56.53 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 743892.81 | 501813.16 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 519301.69 | 315624.42 | 152.43 | 89.22 | 0.00 |
Report: CoilReportMonthly
For: 102 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: 103 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 1485019.80 | 1140882.05 | 1114.37 | 11-JAN-09:03 | 850.91 | 0.00 |
| February | 0.00 | 0.00 | 1175793.85 | 947292.66 | 1032.01 | 23-FEB-09:03 | 741.88 | 0.00 |
| March | 0.00 | 0.00 | 79810963.92 | 53387333.78 | 2217.62 | 14-MAR-15:12 | 1124.82 | 0.00 |
| April | 0.00 | 0.00 | 96403767.27 | 68853062.33 | 2140.04 | 30-APR-15:12 | 1120.67 | 0.00 |
| May | 0.00 | 0.00 | 0.527722E+09 | 0.392042E+09 | 2196.42 | 24-MAY-08:51 | 1171.48 | 0.00 |
| June | 0.00 | 0.00 | 0.133344E+10 | 0.974587E+09 | 2341.03 | 18-JUN-08:12 | 1198.93 | 0.00 |
| July | 0.00 | 0.00 | 0.207623E+10 | 0.147781E+10 | 2379.14 | 28-JUL-21:11 | 1195.11 | 0.00 |
| August | 0.00 | 0.00 | 0.190446E+10 | 0.142089E+10 | 2354.34 | 28-AUG-21:41 | 1218.17 | 0.00 |
| September | 0.00 | 0.00 | 0.128514E+10 | 0.955167E+09 | 2331.52 | 15-SEP-21:31 | 1284.00 | 0.00 |
| October | 0.00 | 0.00 | 0.551199E+09 | 0.413784E+09 | 2185.11 | 12-OCT-21:51 | 1277.86 | 0.00 |
| November | 0.00 | 0.00 | 0.130849E+09 | 99144137.26 | 2107.97 | 05-NOV-08:51 | 1369.79 | 0.00 |
| December | 0.00 | 0.00 | 3285270.06 | 2379721.06 | 2021.69 | 01-DEC-09:01 | 1258.44 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.799119E+10 | 0.586013E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 1175793.85 | 947292.66 | 1032.01 | 741.88 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.207623E+10 | 0.147781E+10 | 2379.14 | 1369.79 | 0.00 |
Report: CoilReportMonthly
For: 104 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 18431995.06 | 14918095.86 | 2474.34 | 17-JAN-19:02 | 1717.10 | 0.00 |
| February | 0.00 | 0.00 | 7751300.77 | 6599989.18 | 2399.51 | 18-FEB-16:12 | 1790.21 | 0.00 |
| March | 0.00 | 0.00 | 0.241002E+09 | 0.181733E+09 | 2678.08 | 12-MAR-15:12 | 1533.17 | 0.00 |
| April | 0.00 | 0.00 | 0.412272E+09 | 0.331759E+09 | 2659.67 | 30-APR-15:12 | 1577.90 | 0.00 |
| May | 0.00 | 0.00 | 0.925986E+09 | 0.739279E+09 | 2718.84 | 29-MAY-08:21 | 1705.00 | 0.00 |
| June | 0.00 | 0.00 | 0.161819E+10 | 0.123096E+10 | 2847.25 | 17-JUN-08:51 | 1666.40 | 0.00 |
| July | 0.00 | 0.00 | 0.235397E+10 | 0.173097E+10 | 2924.56 | 16-JUL-07:51 | 1582.98 | 0.00 |
| August | 0.00 | 0.00 | 0.227301E+10 | 0.175737E+10 | 2889.61 | 26-AUG-08:51 | 1653.47 | 0.00 |
| September | 0.00 | 0.00 | 0.180544E+10 | 0.142431E+10 | 2877.89 | 15-SEP-21:31 | 1658.58 | 0.00 |
| October | 0.00 | 0.00 | 0.110292E+10 | 0.905720E+09 | 2692.88 | 12-OCT-21:01 | 1875.49 | 0.00 |
| November | 0.00 | 0.00 | 0.498620E+09 | 0.417888E+09 | 2626.51 | 05-NOV-08:51 | 1881.58 | 0.00 |
| December | 0.00 | 0.00 | 38740064.45 | 30466743.62 | 2532.12 | 14-DEC-19:02 | 1485.92 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.112963E+11 | 0.877198E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 7751300.77 | 6599989.18 | 2399.51 | 1485.92 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.235397E+10 | 0.175737E+10 | 2924.56 | 1881.58 | 0.00 |
Report: CoilReportMonthly
For: 105 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.645911E+09 | 0.604848E+09 | 3150.75 | 11-JAN-16:12 | 2515.76 | 0.00 |
| February | 0.00 | 0.00 | 0.494499E+09 | 0.459573E+09 | 3142.50 | 01-FEB-09:01 | 2463.81 | 0.00 |
| March | 0.00 | 0.00 | 0.127008E+10 | 0.114324E+10 | 3374.53 | 14-MAR-21:31 | 2648.94 | 0.00 |
| April | 0.00 | 0.00 | 0.157466E+10 | 0.141611E+10 | 3286.01 | 08-APR-21:21 | 2777.66 | 0.00 |
| May | 0.00 | 0.00 | 0.202643E+10 | 0.176924E+10 | 3488.55 | 29-MAY-08:21 | 2461.58 | 0.00 |
| June | 0.00 | 0.00 | 0.250156E+10 | 0.205224E+10 | 3595.65 | 08-JUN-08:61 | 2271.61 | 0.00 |
| July | 0.00 | 0.00 | 0.318171E+10 | 0.249935E+10 | 3656.12 | 16-JUL-07:51 | 2210.36 | 0.00 |
| August | 0.00 | 0.00 | 0.307176E+10 | 0.250654E+10 | 3622.28 | 26-AUG-08:51 | 2290.32 | 0.00 |
| September | 0.00 | 0.00 | 0.265018E+10 | 0.221955E+10 | 3606.75 | 15-SEP-21:31 | 2293.44 | 0.00 |
| October | 0.00 | 0.00 | 0.222467E+10 | 0.197277E+10 | 3421.96 | 12-OCT-21:01 | 2539.95 | 0.00 |
| November | 0.00 | 0.00 | 0.163190E+10 | 0.149184E+10 | 3388.41 | 05-NOV-08:51 | 2630.59 | 0.00 |
| December | 0.00 | 0.00 | 0.774856E+09 | 0.710407E+09 | 3151.53 | 01-DEC-09:01 | 2540.75 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.220482E+11 | 0.188457E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.494499E+09 | 0.459573E+09 | 3142.50 | 2210.36 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.318171E+10 | 0.250654E+10 | 3656.12 | 2777.66 | 0.00 |
Report: CoilReportMonthly
For: 201 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 4338485.40 | 3063749.82 | 217.88 | 12-JUN-14:02 | 180.47 | 0.00 |
| July | 0.00 | 0.00 | 23718883.47 | 15581116.58 | 360.01 | 21-JUL-14:02 | 249.07 | 0.00 |
| August | 0.00 | 0.00 | 6151460.66 | 5109674.65 | 769.48 | 14-AUG-15:01 | 440.99 | 0.00 |
| September | 0.00 | 0.00 | 30995.52 | 21663.79 | 25.04 | 16-SEP-14:50 | 17.51 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 34239825.05 | 23776204.84 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 23718883.47 | 15581116.58 | 769.48 | 440.99 | 0.00 |
Report: CoilReportMonthly
For: 202_205 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 15547621.42 | 11608279.21 | 7559.23 | 17-JAN-19:02 | 4791.08 | 0.00 |
| February | 0.00 | 0.00 | 9731961.73 | 7955235.92 | 7040.16 | 20-FEB-09:01 | 5403.88 | 0.00 |
| March | 0.00 | 0.00 | 0.733542E+09 | 0.531901E+09 | 8199.32 | 14-MAR-18:51 | 5570.52 | 0.00 |
| April | 0.00 | 0.00 | 0.123641E+10 | 0.958021E+09 | 7970.54 | 08-APR-18:11 | 5886.37 | 0.00 |
| May | 0.00 | 0.00 | 0.366729E+10 | 0.291496E+10 | 8448.87 | 24-MAY-07:31 | 5141.05 | 0.00 |
| June | 0.00 | 0.00 | 0.634852E+10 | 0.479877E+10 | 8812.62 | 18-JUN-07:51 | 5246.27 | 0.00 |
| July | 0.00 | 0.00 | 0.880693E+10 | 0.635571E+10 | 8973.93 | 16-JUL-07:51 | 5069.43 | 0.00 |
| August | 0.00 | 0.00 | 0.762085E+10 | 0.568905E+10 | 8861.17 | 14-AUG-08:11 | 4869.81 | 0.00 |
| September | 0.00 | 0.00 | 0.495103E+10 | 0.364375E+10 | 8761.79 | 14-SEP-08:21 | 4871.53 | 0.00 |
| October | 0.00 | 0.00 | 0.207977E+10 | 0.154687E+10 | 8395.56 | 12-OCT-21:51 | 4914.94 | 0.00 |
| November | 0.00 | 0.00 | 0.612699E+09 | 0.466255E+09 | 8125.48 | 05-NOV-08:51 | 5235.02 | 0.00 |
| December | 0.00 | 0.00 | 30800766.46 | 22408132.48 | 7719.30 | 01-DEC-09:01 | 4765.55 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.361131E+11 | 0.269473E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 9731961.73 | 7955235.92 | 7040.16 | 4765.55 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.880693E+10 | 0.635571E+10 | 8973.93 | 5886.37 | 0.00 |
Report: CoilReportMonthly
For: 206_208 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 29589510.91 | 23389601.83 | 5966.44 | 11-JAN-19:02 | 3689.78 | 0.00 |
| February | 0.00 | 0.00 | 21144850.66 | 17802006.81 | 5675.87 | 15-FEB-09:01 | 4240.80 | 0.00 |
| March | 0.00 | 0.00 | 0.736111E+09 | 0.553708E+09 | 6462.41 | 14-MAR-20:51 | 4559.41 | 0.00 |
| April | 0.00 | 0.00 | 0.130584E+10 | 0.105341E+10 | 6289.64 | 08-APR-18:11 | 4799.00 | 0.00 |
| May | 0.00 | 0.00 | 0.320405E+10 | 0.260846E+10 | 6659.04 | 24-MAY-08:51 | 3923.94 | 0.00 |
| June | 0.00 | 0.00 | 0.504785E+10 | 0.385099E+10 | 6959.37 | 18-JUN-07:51 | 4186.73 | 0.00 |
| July | 0.00 | 0.00 | 0.686326E+10 | 0.496952E+10 | 7085.95 | 16-JUL-07:51 | 4032.55 | 0.00 |
| August | 0.00 | 0.00 | 0.596300E+10 | 0.447391E+10 | 7011.11 | 14-AUG-08:11 | 3894.20 | 0.00 |
| September | 0.00 | 0.00 | 0.403235E+10 | 0.301329E+10 | 6916.32 | 14-SEP-08:21 | 3924.58 | 0.00 |
| October | 0.00 | 0.00 | 0.198731E+10 | 0.153310E+10 | 6626.43 | 12-OCT-21:51 | 4001.35 | 0.00 |
| November | 0.00 | 0.00 | 0.725611E+09 | 0.578495E+09 | 6412.80 | 05-NOV-08:51 | 4315.35 | 0.00 |
| December | 0.00 | 0.00 | 56786034.64 | 43116878.75 | 6068.92 | 01-DEC-09:01 | 4021.40 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.299729E+11 | 0.227192E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 21144850.66 | 17802006.81 | 5675.87 | 3689.78 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.686326E+10 | 0.496952E+10 | 7085.95 | 4799.00 | 0.00 |
Report: CoilReportMonthly
For: 209_212 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 46440486.78 | 35999352.33 | 7397.32 | 17-JAN-19:02 | 4910.88 | 0.00 |
| February | 0.00 | 0.00 | 34685788.30 | 28538175.95 | 7344.39 | 01-FEB-09:01 | 4413.22 | 0.00 |
| March | 0.00 | 0.00 | 0.885936E+09 | 0.651576E+09 | 7993.38 | 14-MAR-20:51 | 5530.25 | 0.00 |
| April | 0.00 | 0.00 | 0.154755E+10 | 0.122185E+10 | 7783.50 | 08-APR-18:11 | 5792.43 | 0.00 |
| May | 0.00 | 0.00 | 0.372223E+10 | 0.296645E+10 | 8245.22 | 24-MAY-07:31 | 4973.31 | 0.00 |
| June | 0.00 | 0.00 | 0.593452E+10 | 0.442929E+10 | 8592.90 | 18-JUN-08:11 | 4802.56 | 0.00 |
| July | 0.00 | 0.00 | 0.812290E+10 | 0.575027E+10 | 8787.10 | 16-JUL-07:51 | 4733.34 | 0.00 |
| August | 0.00 | 0.00 | 0.710309E+10 | 0.522542E+10 | 8707.68 | 14-AUG-08:11 | 4630.52 | 0.00 |
| September | 0.00 | 0.00 | 0.492387E+10 | 0.361977E+10 | 8559.13 | 14-SEP-08:21 | 4712.10 | 0.00 |
| October | 0.00 | 0.00 | 0.255585E+10 | 0.194936E+10 | 8193.60 | 12-OCT-21:51 | 4860.86 | 0.00 |
| November | 0.00 | 0.00 | 0.100165E+10 | 0.789065E+09 | 7943.56 | 05-NOV-08:51 | 5281.04 | 0.00 |
| December | 0.00 | 0.00 | 90928700.36 | 67962246.52 | 7519.89 | 01-DEC-09:01 | 4982.67 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.359696E+11 | 0.267355E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 34685788.30 | 28538175.95 | 7344.39 | 4413.22 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.812290E+10 | 0.575027E+10 | 8787.10 | 5792.43 | 0.00 |
Report: CoilReportMonthly
For: 213 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 1294293.74 | 958518.02 | 981.45 | 11-JAN-19:03 | 566.91 | 0.00 |
| February | 0.00 | 0.00 | 1126875.23 | 873428.28 | 1256.25 | 01-FEB-09:03 | 743.69 | 0.00 |
| March | 0.00 | 0.00 | 0.120989E+09 | 84952911.34 | 2254.37 | 14-MAR-15:12 | 1201.11 | 0.00 |
| April | 0.00 | 0.00 | 0.176179E+09 | 0.131300E+09 | 2190.55 | 30-APR-15:12 | 1161.92 | 0.00 |
| May | 0.00 | 0.00 | 0.730462E+09 | 0.565642E+09 | 2252.52 | 24-MAY-08:51 | 1236.18 | 0.00 |
| June | 0.00 | 0.00 | 0.148750E+10 | 0.111023E+10 | 2379.31 | 18-JUN-08:11 | 1284.10 | 0.00 |
| July | 0.00 | 0.00 | 0.218783E+10 | 0.157598E+10 | 2413.38 | 29-JUL-08:31 | 1199.85 | 0.00 |
| August | 0.00 | 0.00 | 0.188864E+10 | 0.140670E+10 | 2400.16 | 14-AUG-08:11 | 1254.67 | 0.00 |
| September | 0.00 | 0.00 | 0.115831E+10 | 0.844101E+09 | 2364.04 | 17-SEP-08:21 | 1295.51 | 0.00 |
| October | 0.00 | 0.00 | 0.390728E+09 | 0.281550E+09 | 2226.71 | 12-OCT-21:51 | 1294.06 | 0.00 |
| November | 0.00 | 0.00 | 80368064.68 | 59238138.08 | 2155.50 | 05-NOV-08:51 | 1352.40 | 0.00 |
| December | 0.00 | 0.00 | 1600167.02 | 1139217.01 | 1103.56 | 14-DEC-09:02 | 650.60 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.822503E+10 | 0.606267E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 1126875.23 | 873428.28 | 981.45 | 566.91 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.218783E+10 | 0.157598E+10 | 2413.38 | 1352.40 | 0.00 |
Report: CoilReportMonthly
For: 214 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 52443581.51 | 43676006.96 | 2688.01 | 17-JAN-19:02 | 1896.12 | 0.00 |
| February | 0.00 | 0.00 | 34178631.53 | 29206935.28 | 2606.21 | 18-FEB-16:12 | 2006.20 | 0.00 |
| March | 0.00 | 0.00 | 0.491958E+09 | 0.401348E+09 | 2841.62 | 14-MAR-21:31 | 2155.97 | 0.00 |
| April | 0.00 | 0.00 | 0.830630E+09 | 0.710505E+09 | 2742.89 | 08-APR-17:51 | 2345.70 | 0.00 |
| May | 0.00 | 0.00 | 0.148252E+10 | 0.125312E+10 | 2955.85 | 29-MAY-08:21 | 1933.85 | 0.00 |
| June | 0.00 | 0.00 | 0.208418E+10 | 0.165909E+10 | 3079.17 | 08-JUN-08:61 | 1730.30 | 0.00 |
| July | 0.00 | 0.00 | 0.279439E+10 | 0.213477E+10 | 3127.29 | 16-JUL-07:31 | 1824.36 | 0.00 |
| August | 0.00 | 0.00 | 0.260200E+10 | 0.206424E+10 | 3091.09 | 26-AUG-08:51 | 1802.67 | 0.00 |
| September | 0.00 | 0.00 | 0.203299E+10 | 0.163709E+10 | 3056.05 | 14-SEP-08:41 | 1820.98 | 0.00 |
| October | 0.00 | 0.00 | 0.127107E+10 | 0.106311E+10 | 2896.75 | 12-OCT-21:01 | 2034.09 | 0.00 |
| November | 0.00 | 0.00 | 0.611657E+09 | 0.520944E+09 | 2851.85 | 05-NOV-08:51 | 2052.42 | 0.00 |
| December | 0.00 | 0.00 | 76681462.39 | 61938420.30 | 2744.35 | 14-DEC-19:02 | 1656.84 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.143647E+11 | 0.115790E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 34178631.53 | 29206935.28 | 2606.21 | 1656.84 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.279439E+10 | 0.213477E+10 | 3127.29 | 2345.70 | 0.00 |
Report: CoilReportMonthly
For: 215_218 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.174472E+10 | 0.174472E+10 | 3224.89 | 15-JAN-15:00 | 3224.89 | 0.00 |
| February | 0.00 | 0.00 | 0.145490E+10 | 0.145490E+10 | 3020.70 | 28-FEB-15:00 | 3020.70 | 0.00 |
| March | 0.00 | 0.00 | 0.344723E+10 | 0.344158E+10 | 4812.27 | 15-MAR-14:01 | 4812.27 | 0.00 |
| April | 0.00 | 0.00 | 0.407350E+10 | 0.407350E+10 | 3849.15 | 09-APR-14:37 | 3849.15 | 0.00 |
| May | 0.00 | 0.00 | 0.553559E+10 | 0.551932E+10 | 4758.06 | 14-MAY-15:00 | 4622.92 | 0.00 |
| June | 0.00 | 0.00 | 0.676051E+10 | 0.657762E+10 | 5568.79 | 27-JUN-15:00 | 4705.04 | 0.00 |
| July | 0.00 | 0.00 | 0.796272E+10 | 0.757059E+10 | 5934.73 | 19-JUL-15:00 | 5335.64 | 0.00 |
| August | 0.00 | 0.00 | 0.784145E+10 | 0.760030E+10 | 6240.35 | 13-AUG-15:00 | 5518.51 | 0.00 |
| September | 0.00 | 0.00 | 0.695513E+10 | 0.682837E+10 | 5970.83 | 21-SEP-15:00 | 5970.83 | 0.00 |
| October | 0.00 | 0.00 | 0.514355E+10 | 0.513787E+10 | 5377.93 | 11-OCT-15:00 | 5377.93 | 0.00 |
| November | 0.00 | 0.00 | 0.352238E+10 | 0.352238E+10 | 3721.71 | 03-NOV-15:02 | 3721.71 | 0.00 |
| December | 0.00 | 0.00 | 0.171215E+10 | 0.171215E+10 | 3056.04 | 16-DEC-13:40 | 3056.04 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.561538E+11 | 0.551833E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.145490E+10 | 0.145490E+10 | 3020.70 | 3020.70 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.796272E+10 | 0.760030E+10 | 6240.35 | 5970.83 | 0.00 |
Report: CoilReportMonthly
For: 219 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.546112E+10 | 0.539729E+10 | 9920.67 | 15-JAN-09:01 | 9143.75 | 0.00 |
| February | 0.00 | 0.00 | 0.480239E+10 | 0.474426E+10 | 9806.00 | 01-FEB-09:01 | 8904.64 | 0.00 |
| March | 0.00 | 0.00 | 0.652865E+10 | 0.635347E+10 | 10669.02 | 15-MAR-08:31 | 9524.26 | 0.00 |
| April | 0.00 | 0.00 | 0.683382E+10 | 0.661177E+10 | 10517.41 | 08-APR-21:21 | 9798.77 | 0.00 |
| May | 0.00 | 0.00 | 0.752969E+10 | 0.718268E+10 | 10860.72 | 29-MAY-08:21 | 9146.04 | 0.00 |
| June | 0.00 | 0.00 | 0.784462E+10 | 0.727165E+10 | 11013.96 | 08-JUN-08:61 | 8847.77 | 0.00 |
| July | 0.00 | 0.00 | 0.881871E+10 | 0.798921E+10 | 11038.39 | 19-JUL-08:41 | 8905.06 | 0.00 |
| August | 0.00 | 0.00 | 0.863120E+10 | 0.793672E+10 | 11039.83 | 26-AUG-08:51 | 8918.62 | 0.00 |
| September | 0.00 | 0.00 | 0.791128E+10 | 0.737543E+10 | 11006.03 | 17-SEP-08:51 | 8921.57 | 0.00 |
| October | 0.00 | 0.00 | 0.752839E+10 | 0.720475E+10 | 10821.63 | 26-OCT-08:51 | 9196.41 | 0.00 |
| November | 0.00 | 0.00 | 0.653412E+10 | 0.634189E+10 | 10748.46 | 05-NOV-08:51 | 9345.94 | 0.00 |
| December | 0.00 | 0.00 | 0.552749E+10 | 0.542746E+10 | 9976.45 | 01-DEC-09:01 | 9080.75 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.839515E+11 | 0.798366E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.480239E+10 | 0.474426E+10 | 9806.00 | 8847.77 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.881871E+10 | 0.798921E+10 | 11039.83 | 9798.77 | 0.00 |
Report: CoilReportMonthly
For: 220_223 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.292581E+09 | 0.249829E+09 | 9398.32 | 11-JAN-16:12 | 6335.71 | 0.00 |
| February | 0.00 | 0.00 | 0.245950E+09 | 0.214487E+09 | 9360.32 | 01-FEB-09:01 | 6102.82 | 0.00 |
| March | 0.00 | 0.00 | 0.192126E+10 | 0.157648E+10 | 9952.47 | 14-MAR-21:31 | 7409.94 | 0.00 |
| April | 0.00 | 0.00 | 0.297462E+10 | 0.252179E+10 | 9664.64 | 08-APR-21:21 | 7773.10 | 0.00 |
| May | 0.00 | 0.00 | 0.494230E+10 | 0.409165E+10 | 10369.39 | 29-MAY-08:21 | 6755.03 | 0.00 |
| June | 0.00 | 0.00 | 0.666922E+10 | 0.510631E+10 | 10800.24 | 08-JUN-08:61 | 6010.21 | 0.00 |
| July | 0.00 | 0.00 | 0.884339E+10 | 0.641644E+10 | 10999.05 | 16-JUL-07:31 | 6213.27 | 0.00 |
| August | 0.00 | 0.00 | 0.817503E+10 | 0.620226E+10 | 10882.29 | 14-AUG-07:41 | 6153.16 | 0.00 |
| September | 0.00 | 0.00 | 0.652858E+10 | 0.506946E+10 | 10776.79 | 15-SEP-21:31 | 6215.43 | 0.00 |
| October | 0.00 | 0.00 | 0.437114E+10 | 0.359611E+10 | 10140.66 | 12-OCT-21:01 | 6979.99 | 0.00 |
| November | 0.00 | 0.00 | 0.228097E+10 | 0.193441E+10 | 10033.82 | 05-NOV-07:51 | 7275.97 | 0.00 |
| December | 0.00 | 0.00 | 0.380797E+09 | 0.313039E+09 | 9581.04 | 14-DEC-19:02 | 5918.92 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.476258E+11 | 0.372923E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.245950E+09 | 0.214487E+09 | 9360.32 | 5918.92 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.884339E+10 | 0.641644E+10 | 10999.05 | 7773.10 | 0.00 |
Report: CoilReportMonthly
For: 224 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 21677501.05 | 17611675.23 | 2657.43 | 17-JAN-19:02 | 1771.28 | 0.00 |
| February | 0.00 | 0.00 | 14857336.60 | 12605851.04 | 2587.87 | 18-FEB-16:12 | 1893.62 | 0.00 |
| March | 0.00 | 0.00 | 0.378093E+09 | 0.300347E+09 | 2794.96 | 14-MAR-21:31 | 2088.57 | 0.00 |
| April | 0.00 | 0.00 | 0.687468E+09 | 0.578825E+09 | 2723.55 | 28-APR-15:12 | 1764.40 | 0.00 |
| May | 0.00 | 0.00 | 0.134207E+10 | 0.112135E+10 | 2916.98 | 29-MAY-08:21 | 1890.85 | 0.00 |
| June | 0.00 | 0.00 | 0.193888E+10 | 0.152466E+10 | 3039.91 | 08-JUN-08:61 | 1679.60 | 0.00 |
| July | 0.00 | 0.00 | 0.264599E+10 | 0.199799E+10 | 3089.44 | 16-JUL-07:31 | 1786.13 | 0.00 |
| August | 0.00 | 0.00 | 0.245987E+10 | 0.193204E+10 | 3056.81 | 26-AUG-08:51 | 1762.43 | 0.00 |
| September | 0.00 | 0.00 | 0.190941E+10 | 0.152251E+10 | 3025.65 | 15-SEP-21:31 | 1791.76 | 0.00 |
| October | 0.00 | 0.00 | 0.113849E+10 | 0.939756E+09 | 2863.00 | 12-OCT-21:01 | 1991.37 | 0.00 |
| November | 0.00 | 0.00 | 0.484877E+09 | 0.406535E+09 | 2811.14 | 05-NOV-08:51 | 1992.84 | 0.00 |
| December | 0.00 | 0.00 | 34975489.41 | 27601217.10 | 2714.42 | 14-DEC-19:02 | 1496.83 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.130567E+11 | 0.103818E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 14857336.60 | 12605851.04 | 2587.87 | 1496.83 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.264599E+10 | 0.199799E+10 | 3089.44 | 2088.57 | 0.00 |
Report: CoilReportMonthly
For: 301 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 2874198.80 | 1947409.74 | 217.17 | 12-JUN-14:02 | 169.72 | 0.00 |
| July | 0.00 | 0.00 | 17834704.88 | 11050725.78 | 379.72 | 21-JUL-14:02 | 243.78 | 0.00 |
| August | 0.00 | 0.00 | 2988921.48 | 2402817.92 | 172.97 | 10-AUG-14:01 | 136.48 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 23697825.15 | 15400953.44 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 17834704.88 | 11050725.78 | 379.72 | 243.78 | 0.00 |
Report: CoilReportMonthly
For: 302_305 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 3917466.29 | 2841935.85 | 533.87 | 12-JUN-14:40 | 433.55 | 0.00 |
| July | 0.00 | 0.00 | 32987280.55 | 20616786.71 | 1023.22 | 21-JUL-14:02 | 629.92 | 0.00 |
| August | 0.00 | 0.00 | 4447345.10 | 3569706.20 | 512.57 | 10-AUG-14:08 | 424.27 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 41352091.93 | 27028428.76 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 32987280.55 | 20616786.71 | 1023.22 | 629.92 | 0.00 |
Report: CoilReportMonthly
For: 306_308 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 1115741.16 | 906842.97 | 494.83 | 12-JUN-14:15 | 404.10 | 0.00 |
| July | 0.00 | 0.00 | 11132176.40 | 6760353.96 | 720.75 | 21-JUL-14:02 | 423.79 | 0.00 |
| August | 0.00 | 0.00 | 1003796.22 | 821103.20 | 262.18 | 10-AUG-14:35 | 216.55 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 13251713.78 | 8488300.13 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 11132176.40 | 6760353.96 | 720.75 | 423.79 | 0.00 |
Report: CoilReportMonthly
For: 309_312 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 16721164.66 | 12595047.83 | 7183.80 | 17-JAN-19:02 | 4596.48 | 0.00 |
| February | 0.00 | 0.00 | 13576579.82 | 11151832.37 | 6719.72 | 19-FEB-19:02 | 5125.46 | 0.00 |
| March | 0.00 | 0.00 | 0.718023E+09 | 0.518428E+09 | 7832.67 | 14-MAR-18:51 | 5381.31 | 0.00 |
| April | 0.00 | 0.00 | 0.123100E+10 | 0.958698E+09 | 7614.78 | 08-APR-18:11 | 5660.78 | 0.00 |
| May | 0.00 | 0.00 | 0.340313E+10 | 0.268502E+10 | 8071.49 | 24-MAY-07:31 | 4820.25 | 0.00 |
| June | 0.00 | 0.00 | 0.574330E+10 | 0.425635E+10 | 8441.75 | 18-JUN-08:11 | 4644.68 | 0.00 |
| July | 0.00 | 0.00 | 0.791539E+10 | 0.556305E+10 | 8627.77 | 16-JUL-07:51 | 4508.95 | 0.00 |
| August | 0.00 | 0.00 | 0.675975E+10 | 0.492062E+10 | 8578.90 | 14-AUG-08:11 | 4433.04 | 0.00 |
| September | 0.00 | 0.00 | 0.436903E+10 | 0.313858E+10 | 8421.14 | 17-SEP-08:21 | 4602.94 | 0.00 |
| October | 0.00 | 0.00 | 0.179678E+10 | 0.131433E+10 | 8020.30 | 12-OCT-21:51 | 4657.98 | 0.00 |
| November | 0.00 | 0.00 | 0.535170E+09 | 0.406511E+09 | 7741.93 | 05-NOV-08:51 | 5009.86 | 0.00 |
| December | 0.00 | 0.00 | 28998340.53 | 21214922.26 | 7359.82 | 01-DEC-09:01 | 4566.02 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.325309E+11 | 0.238066E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 13576579.82 | 11151832.37 | 6719.72 | 4433.04 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.791539E+10 | 0.556305E+10 | 8627.77 | 5660.78 | 0.00 |
Report: CoilReportMonthly
For: 313 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 163729.46 | 139838.76 | 76.51 | 12-JUN-15:00 | 65.18 | 0.00 |
| July | 0.00 | 0.00 | 2280804.20 | 1396836.92 | 304.71 | 21-JUL-14:02 | 172.98 | 0.00 |
| August | 0.00 | 0.00 | 71363.97 | 62978.05 | 37.33 | 10-AUG-14:50 | 32.25 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 2515897.63 | 1599653.73 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 2280804.20 | 1396836.92 | 304.71 | 172.98 | 0.00 |
Report: CoilReportMonthly
For: 314 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 6212532.63 | 4897384.85 | 2449.33 | 15-JAN-16:12 | 1794.46 | 0.00 |
| February | 0.00 | 0.00 | 4143776.56 | 3471041.42 | 2390.23 | 18-FEB-16:12 | 1727.66 | 0.00 |
| March | 0.00 | 0.00 | 0.268698E+09 | 0.207124E+09 | 2656.11 | 12-MAR-15:12 | 1539.15 | 0.00 |
| April | 0.00 | 0.00 | 0.494019E+09 | 0.408045E+09 | 2605.82 | 29-APR-15:12 | 1516.36 | 0.00 |
| May | 0.00 | 0.00 | 0.118248E+10 | 0.975249E+09 | 2732.72 | 29-MAY-08:21 | 1729.14 | 0.00 |
| June | 0.00 | 0.00 | 0.189918E+10 | 0.148587E+10 | 2852.87 | 08-JUN-08:61 | 1527.96 | 0.00 |
| July | 0.00 | 0.00 | 0.264091E+10 | 0.198942E+10 | 2906.77 | 16-JUL-07:31 | 1660.75 | 0.00 |
| August | 0.00 | 0.00 | 0.239272E+10 | 0.186833E+10 | 2882.51 | 26-AUG-08:51 | 1628.17 | 0.00 |
| September | 0.00 | 0.00 | 0.171034E+10 | 0.133889E+10 | 2848.00 | 14-SEP-08:41 | 1639.29 | 0.00 |
| October | 0.00 | 0.00 | 0.769275E+09 | 0.608699E+09 | 2692.69 | 12-OCT-21:01 | 1847.10 | 0.00 |
| November | 0.00 | 0.00 | 0.231202E+09 | 0.185959E+09 | 2647.47 | 04-NOV-18:11 | 1676.36 | 0.00 |
| December | 0.00 | 0.00 | 6911844.34 | 5279486.29 | 2478.23 | 16-DEC-16:12 | 1682.79 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.116061E+11 | 0.908124E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 4143776.56 | 3471041.42 | 2390.23 | 1516.36 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.264091E+10 | 0.198942E+10 | 2906.77 | 1847.10 | 0.00 |
Report: CoilReportMonthly
For: 315_318 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.799638E+09 | 0.716164E+09 | 10312.76 | 11-JAN-16:12 | 7359.71 | 0.00 |
| February | 0.00 | 0.00 | 0.701183E+09 | 0.631129E+09 | 10241.39 | 01-FEB-16:12 | 6756.33 | 0.00 |
| March | 0.00 | 0.00 | 0.319631E+10 | 0.277185E+10 | 10783.11 | 14-MAR-21:31 | 8324.26 | 0.00 |
| April | 0.00 | 0.00 | 0.444909E+10 | 0.390956E+10 | 10519.50 | 08-APR-21:21 | 8710.06 | 0.00 |
| May | 0.00 | 0.00 | 0.660993E+10 | 0.565995E+10 | 11221.08 | 29-MAY-08:21 | 7623.33 | 0.00 |
| June | 0.00 | 0.00 | 0.844589E+10 | 0.673727E+10 | 11700.03 | 18-JUN-07:32 | 7820.51 | 0.00 |
| July | 0.00 | 0.00 | 0.107931E+11 | 0.817919E+10 | 11943.96 | 16-JUL-07:31 | 7233.84 | 0.00 |
| August | 0.00 | 0.00 | 0.999528E+10 | 0.787123E+10 | 11811.38 | 15-AUG-08:21 | 7278.66 | 0.00 |
| September | 0.00 | 0.00 | 0.807824E+10 | 0.649633E+10 | 11630.50 | 17-SEP-08:31 | 7547.51 | 0.00 |
| October | 0.00 | 0.00 | 0.560799E+10 | 0.475311E+10 | 10981.86 | 12-OCT-21:01 | 7872.16 | 0.00 |
| November | 0.00 | 0.00 | 0.327502E+10 | 0.286080E+10 | 10943.30 | 05-NOV-08:51 | 8076.24 | 0.00 |
| December | 0.00 | 0.00 | 0.911027E+09 | 0.786144E+09 | 10390.19 | 14-DEC-16:12 | 6772.22 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.628627E+11 | 0.513727E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.701183E+09 | 0.631129E+09 | 10241.39 | 6756.33 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.107931E+11 | 0.817919E+10 | 11943.96 | 8710.06 | 0.00 |
Report: CoilReportMonthly
For: 319 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 2611635.27 | 2584896.69 | 221.39 | 15-MAR-14:02 | 221.15 | 0.00 |
| April | 0.00 | 0.00 | 4973.66 | 4973.66 | 6.93 | 09-APR-16:00 | 6.93 | 0.00 |
| May | 0.00 | 0.00 | 6544154.71 | 6464329.07 | 208.31 | 14-MAY-14:30 | 201.79 | 0.00 |
| June | 0.00 | 0.00 | 77510972.08 | 66675778.34 | 359.83 | 12-JUN-14:10 | 327.46 | 0.00 |
| July | 0.00 | 0.00 | 0.170418E+09 | 0.140434E+09 | 443.56 | 19-JUL-14:20 | 362.62 | 0.00 |
| August | 0.00 | 0.00 | 0.162533E+09 | 0.145544E+09 | 458.81 | 13-AUG-15:00 | 371.64 | 0.00 |
| September | 0.00 | 0.00 | 99641348.26 | 91904507.84 | 443.10 | 21-SEP-14:01 | 443.10 | 0.00 |
| October | 0.00 | 0.00 | 9983795.85 | 9974045.66 | 256.47 | 11-OCT-14:25 | 256.47 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.529248E+09 | 0.463586E+09 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.170418E+09 | 0.145544E+09 | 458.81 | 443.10 | 0.00 |
Report: CoilReportMonthly
For: 320_323 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.129117E+09 | 0.108900E+09 | 8968.01 | 17-JAN-19:02 | 6050.88 | 0.00 |
| February | 0.00 | 0.00 | 0.131445E+09 | 0.114862E+09 | 8914.65 | 01-FEB-09:01 | 5517.80 | 0.00 |
| March | 0.00 | 0.00 | 0.140557E+10 | 0.112223E+10 | 9505.58 | 14-MAR-21:31 | 7040.55 | 0.00 |
| April | 0.00 | 0.00 | 0.226118E+10 | 0.188385E+10 | 9211.64 | 28-APR-15:12 | 5820.22 | 0.00 |
| May | 0.00 | 0.00 | 0.431654E+10 | 0.352306E+10 | 9894.48 | 29-MAY-08:21 | 6307.13 | 0.00 |
| June | 0.00 | 0.00 | 0.627145E+10 | 0.474634E+10 | 10329.69 | 08-JUN-08:61 | 5557.30 | 0.00 |
| July | 0.00 | 0.00 | 0.847052E+10 | 0.607915E+10 | 10573.39 | 16-JUL-07:51 | 5516.33 | 0.00 |
| August | 0.00 | 0.00 | 0.769569E+10 | 0.577085E+10 | 10460.66 | 14-AUG-07:41 | 5713.20 | 0.00 |
| September | 0.00 | 0.00 | 0.585090E+10 | 0.445848E+10 | 10322.47 | 15-SEP-21:31 | 5864.58 | 0.00 |
| October | 0.00 | 0.00 | 0.325569E+10 | 0.259355E+10 | 9713.43 | 12-OCT-21:01 | 6573.93 | 0.00 |
| November | 0.00 | 0.00 | 0.136620E+10 | 0.112537E+10 | 9550.83 | 04-NOV-18:11 | 6470.52 | 0.00 |
| December | 0.00 | 0.00 | 0.163871E+09 | 0.132878E+09 | 9122.25 | 01-DEC-09:01 | 5945.87 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.413182E+11 | 0.316595E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.129117E+09 | 0.108900E+09 | 8914.65 | 5516.33 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.847052E+10 | 0.607915E+10 | 10573.39 | 7040.55 | 0.00 |
Report: CoilReportMonthly
For: 324 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 782495.41 | 612700.95 | 142.51 | 12-JUN-14:01 | 122.96 | 0.00 |
| July | 0.00 | 0.00 | 9303669.66 | 6247716.86 | 294.02 | 21-JUL-14:02 | 183.97 | 0.00 |
| August | 0.00 | 0.00 | 12534997.36 | 10826350.10 | 234.15 | 10-AUG-14:10 | 209.25 | 0.00 |
| September | 0.00 | 0.00 | 5246208.85 | 4833109.37 | 202.03 | 21-SEP-14:20 | 201.59 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 27867371.28 | 22519877.28 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 12534997.36 | 10826350.10 | 294.02 | 209.25 | 0.00 |
Report: CoilReportMonthly
For: 401 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 569495.59 | 484976.74 | 500.22 | 17-JAN-09:03 | 422.01 | 0.00 |
| February | 0.00 | 0.00 | 443969.56 | 414526.14 | 526.67 | 22-FEB-19:03 | 520.07 | 0.00 |
| March | 0.00 | 0.00 | 91038196.84 | 67571843.21 | 2749.59 | 14-MAR-18:51 | 2048.71 | 0.00 |
| April | 0.00 | 0.00 | 0.140845E+09 | 0.115996E+09 | 2680.32 | 09-APR-08:61 | 1681.01 | 0.00 |
| May | 0.00 | 0.00 | 0.678595E+09 | 0.550758E+09 | 2860.76 | 29-MAY-07:51 | 1768.02 | 0.00 |
| June | 0.00 | 0.00 | 0.166496E+10 | 0.127577E+10 | 3026.85 | 18-JUN-07:51 | 1767.56 | 0.00 |
| July | 0.00 | 0.00 | 0.255086E+10 | 0.188499E+10 | 3080.00 | 29-JUL-08:11 | 1604.66 | 0.00 |
| August | 0.00 | 0.00 | 0.203729E+10 | 0.154630E+10 | 3018.88 | 14-AUG-08:11 | 1617.99 | 0.00 |
| September | 0.00 | 0.00 | 0.945073E+09 | 0.678493E+09 | 3009.04 | 14-SEP-08:21 | 1580.64 | 0.00 |
| October | 0.00 | 0.00 | 0.147210E+09 | 0.102931E+09 | 2816.11 | 01-OCT-08:61 | 1470.10 | 0.00 |
| November | 0.00 | 0.00 | 17549296.50 | 12663085.18 | 2693.17 | 05-NOV-08:51 | 1718.39 | 0.00 |
| December | 0.00 | 0.00 | 718511.51 | 603622.46 | 427.22 | 14-DEC-19:05 | 276.31 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.827515E+10 | 0.623698E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 443969.56 | 414526.14 | 427.22 | 276.31 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.255086E+10 | 0.188499E+10 | 3080.00 | 2048.71 | 0.00 |
Report: CoilReportMonthly
For: 402_405 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 6869750.54 | 6546005.48 | 475.48 | 14-MAY-15:00 | 428.89 | 0.00 |
| June | 0.00 | 0.00 | 0.297701E+09 | 0.244074E+09 | 1801.16 | 27-JUN-14:10 | 1292.98 | 0.00 |
| July | 0.00 | 0.00 | 0.630298E+09 | 0.497960E+09 | 2187.46 | 21-JUL-14:02 | 1801.51 | 0.00 |
| August | 0.00 | 0.00 | 0.356415E+09 | 0.304762E+09 | 1679.70 | 13-AUG-15:00 | 1278.30 | 0.00 |
| September | 0.00 | 0.00 | 18525527.54 | 13516959.45 | 938.51 | 16-SEP-14:02 | 692.54 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.130981E+10 | 0.106686E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.630298E+09 | 0.497960E+09 | 2187.46 | 1801.51 | 0.00 |
Report: CoilReportMonthly
For: 406_408 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 4993109.38 | 4756197.20 | 373.09 | 14-MAY-15:00 | 337.27 | 0.00 |
| June | 0.00 | 0.00 | 0.214822E+09 | 0.175430E+09 | 1374.20 | 27-JUN-14:10 | 978.21 | 0.00 |
| July | 0.00 | 0.00 | 0.454386E+09 | 0.356744E+09 | 1675.12 | 21-JUL-14:02 | 1360.59 | 0.00 |
| August | 0.00 | 0.00 | 0.255308E+09 | 0.217879E+09 | 1289.65 | 13-AUG-15:00 | 980.53 | 0.00 |
| September | 0.00 | 0.00 | 13140592.33 | 9518928.05 | 718.17 | 16-SEP-14:02 | 525.42 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.942650E+09 | 0.764328E+09 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.454386E+09 | 0.356744E+09 | 1675.12 | 1360.59 | 0.00 |
Report: CoilReportMonthly
For: 409_412 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 11157997.25 | 8979603.13 | 7377.70 | 14-JAN-09:01 | 5566.24 | 0.00 |
| February | 0.00 | 0.00 | 13325122.22 | 11241098.25 | 8223.31 | 22-FEB-19:02 | 7275.04 | 0.00 |
| March | 0.00 | 0.00 | 0.583992E+09 | 0.421947E+09 | 10185.80 | 14-MAR-08:61 | 5532.93 | 0.00 |
| April | 0.00 | 0.00 | 0.110035E+10 | 0.874214E+09 | 10001.76 | 08-APR-17:51 | 8176.87 | 0.00 |
| May | 0.00 | 0.00 | 0.315662E+10 | 0.251213E+10 | 10646.28 | 24-MAY-07:31 | 6433.25 | 0.00 |
| June | 0.00 | 0.00 | 0.585784E+10 | 0.440365E+10 | 11111.75 | 18-JUN-07:51 | 6766.87 | 0.00 |
| July | 0.00 | 0.00 | 0.839026E+10 | 0.603992E+10 | 11348.10 | 29-JUL-08:11 | 6284.89 | 0.00 |
| August | 0.00 | 0.00 | 0.692967E+10 | 0.513000E+10 | 11104.64 | 15-AUG-07:51 | 6482.28 | 0.00 |
| September | 0.00 | 0.00 | 0.390377E+10 | 0.277533E+10 | 11177.94 | 16-SEP-08:23 | 6693.36 | 0.00 |
| October | 0.00 | 0.00 | 0.126399E+10 | 0.892723E+09 | 10465.33 | 12-OCT-21:51 | 6391.20 | 0.00 |
| November | 0.00 | 0.00 | 0.313779E+09 | 0.229574E+09 | 10295.41 | 05-NOV-08:51 | 6760.23 | 0.00 |
| December | 0.00 | 0.00 | 14669987.43 | 10760802.92 | 9697.54 | 01-DEC-09:01 | 5907.81 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.315394E+11 | 0.233105E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 11157997.25 | 8979603.13 | 7377.70 | 5532.93 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.839026E+10 | 0.603992E+10 | 11348.10 | 8176.87 | 0.00 |
Report: CoilReportMonthly
For: 413 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 160334.47 | 154599.65 | 72.42 | 14-MAY-15:00 | 68.89 | 0.00 |
| June | 0.00 | 0.00 | 47307340.80 | 39267333.63 | 452.71 | 27-JUN-14:10 | 332.78 | 0.00 |
| July | 0.00 | 0.00 | 0.115878E+09 | 92872827.06 | 591.36 | 21-JUL-14:02 | 487.46 | 0.00 |
| August | 0.00 | 0.00 | 62638049.61 | 54904394.78 | 422.22 | 13-AUG-15:00 | 336.96 | 0.00 |
| September | 0.00 | 0.00 | 2167311.69 | 1558011.03 | 235.07 | 16-SEP-14:02 | 169.06 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.228151E+09 | 0.188757E+09 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.115878E+09 | 92872827.06 | 591.36 | 487.46 | 0.00 |
Report: CoilReportMonthly
For: 414 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 4437468.23 | 4354067.35 | 329.83 | 15-MAR-14:02 | 329.83 | 0.00 |
| April | 0.00 | 0.00 | 455512.78 | 455512.78 | 75.63 | 22-APR-13:40 | 75.63 | 0.00 |
| May | 0.00 | 0.00 | 17448822.92 | 17325531.05 | 312.91 | 14-MAY-14:20 | 301.54 | 0.00 |
| June | 0.00 | 0.00 | 0.103478E+09 | 91292925.54 | 628.34 | 27-JUN-14:10 | 488.83 | 0.00 |
| July | 0.00 | 0.00 | 0.222268E+09 | 0.189213E+09 | 704.24 | 19-JUL-14:10 | 596.44 | 0.00 |
| August | 0.00 | 0.00 | 0.192165E+09 | 0.176361E+09 | 726.99 | 18-AUG-14:10 | 678.90 | 0.00 |
| September | 0.00 | 0.00 | 77076023.48 | 72408243.88 | 617.19 | 21-SEP-14:01 | 617.19 | 0.00 |
| October | 0.00 | 0.00 | 6654309.95 | 6654309.95 | 315.77 | 11-OCT-12:40 | 315.77 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.623984E+09 | 0.558065E+09 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.222268E+09 | 0.189213E+09 | 726.99 | 678.90 | 0.00 |
Report: CoilReportMonthly
For: 415_418 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.111361E+09 | 97140240.09 | 11481.08 | 17-JAN-19:02 | 7510.34 | 0.00 |
| February | 0.00 | 0.00 | 0.142392E+09 | 0.131933E+09 | 11366.21 | 01-FEB-09:01 | 7155.92 | 0.00 |
| March | 0.00 | 0.00 | 0.145778E+10 | 0.120334E+10 | 12058.41 | 14-MAR-08:61 | 7323.68 | 0.00 |
| April | 0.00 | 0.00 | 0.235885E+10 | 0.202573E+10 | 11735.37 | 08-APR-21:21 | 9681.17 | 0.00 |
| May | 0.00 | 0.00 | 0.449025E+10 | 0.373863E+10 | 12597.44 | 29-MAY-08:21 | 8297.98 | 0.00 |
| June | 0.00 | 0.00 | 0.686800E+10 | 0.533331E+10 | 13175.43 | 18-JUN-07:32 | 8559.26 | 0.00 |
| July | 0.00 | 0.00 | 0.941179E+10 | 0.698119E+10 | 13446.46 | 16-JUL-07:31 | 7938.37 | 0.00 |
| August | 0.00 | 0.00 | 0.835528E+10 | 0.642945E+10 | 13262.29 | 15-AUG-08:21 | 8150.96 | 0.00 |
| September | 0.00 | 0.00 | 0.589384E+10 | 0.455774E+10 | 13002.26 | 14-SEP-08:41 | 7688.41 | 0.00 |
| October | 0.00 | 0.00 | 0.297169E+10 | 0.238956E+10 | 12301.26 | 12-OCT-21:01 | 8655.52 | 0.00 |
| November | 0.00 | 0.00 | 0.114662E+10 | 0.945705E+09 | 12280.40 | 05-NOV-07:51 | 8721.63 | 0.00 |
| December | 0.00 | 0.00 | 0.150124E+09 | 0.126208E+09 | 11705.21 | 14-DEC-19:02 | 6590.82 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.433580E+11 | 0.339599E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.111361E+09 | 97140240.09 | 11366.21 | 6590.82 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.941179E+10 | 0.698119E+10 | 13446.46 | 9681.17 | 0.00 |
Report: CoilReportMonthly
For: 419 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 18245175.02 | 15380222.44 | 2949.84 | 17-JAN-19:02 | 1887.28 | 0.00 |
| February | 0.00 | 0.00 | 23618021.97 | 21474124.12 | 2883.28 | 18-FEB-16:12 | 2469.66 | 0.00 |
| March | 0.00 | 0.00 | 0.371533E+09 | 0.304269E+09 | 3211.01 | 14-MAR-21:31 | 2478.23 | 0.00 |
| April | 0.00 | 0.00 | 0.642267E+09 | 0.552347E+09 | 3144.77 | 28-APR-15:12 | 2029.42 | 0.00 |
| May | 0.00 | 0.00 | 0.130014E+10 | 0.109552E+10 | 3360.18 | 29-MAY-08:21 | 2228.17 | 0.00 |
| June | 0.00 | 0.00 | 0.198777E+10 | 0.157716E+10 | 3506.40 | 18-JUN-07:32 | 2256.66 | 0.00 |
| July | 0.00 | 0.00 | 0.270649E+10 | 0.206178E+10 | 3574.54 | 16-JUL-07:31 | 2106.14 | 0.00 |
| August | 0.00 | 0.00 | 0.241453E+10 | 0.190094E+10 | 3525.42 | 15-AUG-08:21 | 2180.80 | 0.00 |
| September | 0.00 | 0.00 | 0.170057E+10 | 0.134088E+10 | 3467.18 | 14-SEP-08:41 | 2065.51 | 0.00 |
| October | 0.00 | 0.00 | 0.825635E+09 | 0.668132E+09 | 3281.30 | 12-OCT-21:01 | 2327.08 | 0.00 |
| November | 0.00 | 0.00 | 0.289541E+09 | 0.238549E+09 | 3255.06 | 05-NOV-08:51 | 2363.72 | 0.00 |
| December | 0.00 | 0.00 | 25250777.11 | 20674926.69 | 3107.04 | 01-DEC-09:01 | 2016.33 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.123056E+11 | 0.979710E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 18245175.02 | 15380222.44 | 2883.28 | 1887.28 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.270649E+10 | 0.206178E+10 | 3574.54 | 2478.23 | 0.00 |
Report: CoilReportMonthly
For: 420_423 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 75553205.54 | 65096271.52 | 11328.77 | 11-JAN-19:02 | 6995.12 | 0.00 |
| February | 0.00 | 0.00 | 0.103021E+09 | 94703732.05 | 10757.89 | 15-FEB-09:01 | 8067.08 | 0.00 |
| March | 0.00 | 0.00 | 0.122437E+10 | 0.995186E+09 | 12006.35 | 14-MAR-08:61 | 7038.91 | 0.00 |
| April | 0.00 | 0.00 | 0.206296E+10 | 0.175601E+10 | 11691.00 | 28-APR-15:12 | 7327.87 | 0.00 |
| May | 0.00 | 0.00 | 0.408410E+10 | 0.336682E+10 | 12479.33 | 29-MAY-08:21 | 8119.92 | 0.00 |
| June | 0.00 | 0.00 | 0.639141E+10 | 0.490416E+10 | 13000.80 | 08-JUN-08:61 | 7216.83 | 0.00 |
| July | 0.00 | 0.00 | 0.886834E+10 | 0.649673E+10 | 13296.26 | 16-JUL-07:31 | 7687.21 | 0.00 |
| August | 0.00 | 0.00 | 0.782882E+10 | 0.595574E+10 | 13115.13 | 15-AUG-08:21 | 7888.90 | 0.00 |
| September | 0.00 | 0.00 | 0.542660E+10 | 0.414208E+10 | 12888.37 | 14-SEP-08:41 | 7506.15 | 0.00 |
| October | 0.00 | 0.00 | 0.261236E+10 | 0.207242E+10 | 12187.71 | 12-OCT-21:01 | 8465.50 | 0.00 |
| November | 0.00 | 0.00 | 0.941736E+09 | 0.766523E+09 | 12135.18 | 05-NOV-08:51 | 8661.62 | 0.00 |
| December | 0.00 | 0.00 | 0.102392E+09 | 85326998.14 | 11529.69 | 01-DEC-09:01 | 7518.68 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.397217E+11 | 0.307008E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 75553205.54 | 65096271.52 | 10757.89 | 6995.12 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.886834E+10 | 0.649673E+10 | 13296.26 | 8661.62 | 0.00 |
Report: CoilReportMonthly
For: 424 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 4277605.33 | 3407664.37 | 3004.64 | 15-JAN-16:12 | 2432.17 | 0.00 |
| February | 0.00 | 0.00 | 6040362.22 | 5267509.00 | 3031.75 | 18-FEB-16:12 | 2295.97 | 0.00 |
| March | 0.00 | 0.00 | 0.228866E+09 | 0.179026E+09 | 3320.57 | 14-MAR-08:61 | 1813.83 | 0.00 |
| April | 0.00 | 0.00 | 0.446660E+09 | 0.376610E+09 | 3233.13 | 28-APR-15:12 | 1913.45 | 0.00 |
| May | 0.00 | 0.00 | 0.107013E+10 | 0.885047E+09 | 3449.93 | 29-MAY-08:21 | 2231.26 | 0.00 |
| June | 0.00 | 0.00 | 0.184446E+10 | 0.144716E+10 | 3603.01 | 08-JUN-08:61 | 1957.06 | 0.00 |
| July | 0.00 | 0.00 | 0.265449E+10 | 0.201634E+10 | 3645.30 | 16-JUL-07:31 | 2130.61 | 0.00 |
| August | 0.00 | 0.00 | 0.233975E+10 | 0.183455E+10 | 3598.24 | 15-AUG-08:21 | 2201.64 | 0.00 |
| September | 0.00 | 0.00 | 0.154050E+10 | 0.119802E+10 | 3550.24 | 14-SEP-08:41 | 2082.18 | 0.00 |
| October | 0.00 | 0.00 | 0.605684E+09 | 0.476371E+09 | 3357.53 | 12-OCT-21:01 | 2352.22 | 0.00 |
| November | 0.00 | 0.00 | 0.155589E+09 | 0.123130E+09 | 3314.78 | 05-NOV-08:51 | 2304.36 | 0.00 |
| December | 0.00 | 0.00 | 5466501.68 | 4096943.51 | 3039.33 | 16-DEC-16:12 | 2299.88 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.109019E+11 | 0.854903E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 4277605.33 | 3407664.37 | 3004.64 | 1813.83 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.265449E+10 | 0.201634E+10 | 3645.30 | 2432.17 | 0.00 |
Report: CoilReportMonthly
For: CORRIDORFLR1 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.196426E+10 | 0.196403E+10 | 4038.88 | 17-JAN-16:55 | 4038.88 | 0.00 |
| February | 0.00 | 0.00 | 0.134076E+10 | 0.134076E+10 | 4024.68 | 22-FEB-16:55 | 4024.68 | 0.00 |
| March | 0.00 | 0.00 | 0.557283E+10 | 0.545136E+10 | 10564.53 | 15-MAR-16:10 | 10124.55 | 0.00 |
| April | 0.00 | 0.00 | 0.830645E+10 | 0.828471E+10 | 7698.17 | 08-APR-16:00 | 7638.10 | 0.00 |
| May | 0.00 | 0.00 | 0.140312E+11 | 0.136695E+11 | 10889.80 | 10-MAY-16:20 | 9352.21 | 0.00 |
| June | 0.00 | 0.00 | 0.196821E+11 | 0.178283E+11 | 19884.31 | 17-JUN-16:30 | 13258.53 | 0.00 |
| July | 0.00 | 0.00 | 0.250026E+11 | 0.212397E+11 | 21175.44 | 20-JUL-16:20 | 14726.33 | 0.00 |
| August | 0.00 | 0.00 | 0.232398E+11 | 0.207465E+11 | 21246.04 | 13-AUG-16:20 | 14198.16 | 0.00 |
| September | 0.00 | 0.00 | 0.187007E+11 | 0.172831E+11 | 15820.32 | 16-SEP-16:20 | 12596.36 | 0.00 |
| October | 0.00 | 0.00 | 0.122178E+11 | 0.120097E+11 | 9927.04 | 11-OCT-16:00 | 9709.25 | 0.00 |
| November | 0.00 | 0.00 | 0.804039E+10 | 0.800120E+10 | 7880.80 | 05-NOV-15:00 | 7575.01 | 0.00 |
| December | 0.00 | 0.00 | 0.263480E+10 | 0.263075E+10 | 5078.73 | 01-DEC-13:00 | 4778.74 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.140734E+12 | 0.130450E+12 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.134076E+10 | 0.134076E+10 | 4024.68 | 4024.68 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.250026E+11 | 0.212397E+11 | 21246.04 | 14726.33 | 0.00 |
Report: CoilReportMonthly
For: CORRIDORFLR2 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.301147E+09 | 0.266607E+09 | 2148.22 | 15-MAR-15:10 | 2041.49 | 0.00 |
| April | 0.00 | 0.00 | 0.393215E+09 | 0.382466E+09 | 1487.64 | 08-APR-18:10 | 1382.99 | 0.00 |
| May | 0.00 | 0.00 | 0.226178E+10 | 0.211993E+10 | 2515.76 | 14-MAY-15:00 | 2206.69 | 0.00 |
| June | 0.00 | 0.00 | 0.487025E+10 | 0.417075E+10 | 3798.98 | 27-JUN-15:20 | 2704.34 | 0.00 |
| July | 0.00 | 0.00 | 0.675688E+10 | 0.539747E+10 | 3933.80 | 20-JUL-15:30 | 2905.76 | 0.00 |
| August | 0.00 | 0.00 | 0.601245E+10 | 0.506825E+10 | 3935.00 | 13-AUG-15:30 | 2976.84 | 0.00 |
| September | 0.00 | 0.00 | 0.409880E+10 | 0.354910E+10 | 3403.65 | 15-SEP-20:40 | 2602.01 | 0.00 |
| October | 0.00 | 0.00 | 0.994783E+09 | 0.911166E+09 | 2225.47 | 11-OCT-17:00 | 2090.73 | 0.00 |
| November | 0.00 | 0.00 | 0.157967E+09 | 0.147216E+09 | 1266.38 | 05-NOV-08:52 | 1070.07 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.258473E+11 | 0.220130E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.675688E+10 | 0.539747E+10 | 3935.00 | 2976.84 | 0.00 |
Report: CoilReportMonthly
For: CORRIDORFLR3 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 82623944.50 | 68831291.03 | 1312.40 | 15-MAR-15:20 | 1172.06 | 0.00 |
| April | 0.00 | 0.00 | 23512230.59 | 20871666.78 | 508.61 | 09-APR-16:00 | 448.74 | 0.00 |
| May | 0.00 | 0.00 | 0.627586E+09 | 0.551265E+09 | 1778.06 | 14-MAY-15:00 | 1448.57 | 0.00 |
| June | 0.00 | 0.00 | 0.302383E+10 | 0.236822E+10 | 3218.69 | 27-JUN-15:23 | 2113.60 | 0.00 |
| July | 0.00 | 0.00 | 0.494779E+10 | 0.363199E+10 | 3374.78 | 20-JUL-15:30 | 2322.72 | 0.00 |
| August | 0.00 | 0.00 | 0.399275E+10 | 0.310789E+10 | 3211.05 | 13-AUG-15:30 | 2239.73 | 0.00 |
| September | 0.00 | 0.00 | 0.187933E+10 | 0.145644E+10 | 2562.82 | 16-SEP-15:23 | 2025.60 | 0.00 |
| October | 0.00 | 0.00 | 0.104785E+09 | 87935844.36 | 1052.87 | 11-OCT-17:00 | 923.62 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.146822E+11 | 0.112934E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.494779E+10 | 0.363199E+10 | 3374.78 | 2322.72 | 0.00 |
Report: CoilReportMonthly
For: CORRIDORFLR4 PTAC PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.124643E+09 | 0.108888E+09 | 2481.24 | 15-MAR-14:13 | 2351.25 | 0.00 |
| April | 0.00 | 0.00 | 0.169621E+09 | 0.166246E+09 | 1429.05 | 08-APR-14:10 | 1374.11 | 0.00 |
| May | 0.00 | 0.00 | 0.114226E+10 | 0.107680E+10 | 3259.42 | 14-MAY-14:35 | 2849.85 | 0.00 |
| June | 0.00 | 0.00 | 0.349954E+10 | 0.294187E+10 | 4908.16 | 27-JUN-13:30 | 3737.97 | 0.00 |
| July | 0.00 | 0.00 | 0.534360E+10 | 0.418269E+10 | 4876.66 | 19-JUL-15:10 | 3946.43 | 0.00 |
| August | 0.00 | 0.00 | 0.418407E+10 | 0.346425E+10 | 4735.19 | 13-AUG-15:02 | 3696.30 | 0.00 |
| September | 0.00 | 0.00 | 0.202169E+10 | 0.168832E+10 | 3776.65 | 16-SEP-14:00 | 3193.20 | 0.00 |
| October | 0.00 | 0.00 | 0.181587E+09 | 0.165286E+09 | 1885.78 | 11-OCT-16:10 | 1765.76 | 0.00 |
| November | 0.00 | 0.00 | 1484997.00 | 1305933.95 | 189.17 | 05-NOV-14:00 | 167.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.166685E+11 | 0.137957E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.534360E+10 | 0.418269E+10 | 4908.16 | 3946.43 | 0.00 |
Report: CoilReportMonthly
For: SAC_FRONTOFFICE PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 2980766.26 | 2739040.09 | 322.89 | 17-JAN-15:50 | 321.65 | 0.00 |
| February | 0.00 | 0.00 | 5510112.41 | 5510112.41 | 735.33 | 22-FEB-15:02 | 735.33 | 0.00 |
| March | 0.00 | 0.00 | 0.483185E+09 | 0.420199E+09 | 7830.26 | 14-MAR-12:01 | 6302.98 | 0.00 |
| April | 0.00 | 0.00 | 0.719576E+09 | 0.696650E+09 | 7361.06 | 30-APR-14:01 | 6580.39 | 0.00 |
| May | 0.00 | 0.00 | 0.223907E+10 | 0.204316E+10 | 7797.50 | 17-MAY-14:01 | 5870.23 | 0.00 |
| June | 0.00 | 0.00 | 0.489481E+10 | 0.399041E+10 | 8098.35 | 17-JUN-14:01 | 5609.68 | 0.00 |
| July | 0.00 | 0.00 | 0.730808E+10 | 0.554714E+10 | 8179.21 | 05-JUL-12:01 | 5553.54 | 0.00 |
| August | 0.00 | 0.00 | 0.692357E+10 | 0.562744E+10 | 8081.24 | 07-AUG-12:01 | 5835.55 | 0.00 |
| September | 0.00 | 0.00 | 0.521496E+10 | 0.439858E+10 | 7994.86 | 14-SEP-12:01 | 5901.99 | 0.00 |
| October | 0.00 | 0.00 | 0.221571E+10 | 0.202599E+10 | 7544.52 | 01-OCT-14:01 | 6263.90 | 0.00 |
| November | 0.00 | 0.00 | 0.668181E+09 | 0.634403E+09 | 7484.91 | 04-NOV-14:01 | 6601.18 | 0.00 |
| December | 0.00 | 0.00 | 13548118.50 | 11426426.92 | 7530.32 | 01-DEC-13:01 | 6125.15 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.306892E+11 | 0.254036E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 2980766.26 | 2739040.09 | 322.89 | 321.65 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.730808E+10 | 0.562744E+10 | 8179.21 | 6601.18 | 0.00 |
Report: CoilReportMonthly
For: SAC_FRONTLOUNGE PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.320621E+09 | 0.239103E+09 | 4711.22 | 15-MAR-08:52 | 3449.32 | 0.00 |
| April | 0.00 | 0.00 | 98630113.73 | 80808245.03 | 3503.59 | 08-APR-09:00 | 2761.98 | 0.00 |
| May | 0.00 | 0.00 | 0.158809E+10 | 0.123633E+10 | 6729.70 | 29-MAY-07:51 | 4294.65 | 0.00 |
| June | 0.00 | 0.00 | 0.716380E+10 | 0.486371E+10 | 12852.46 | 27-JUN-08:53 | 7409.91 | 0.00 |
| July | 0.00 | 0.00 | 0.130894E+11 | 0.819247E+10 | 13373.34 | 21-JUL-08:02 | 7499.65 | 0.00 |
| August | 0.00 | 0.00 | 0.105761E+11 | 0.723048E+10 | 13106.72 | 15-AUG-08:51 | 7434.79 | 0.00 |
| September | 0.00 | 0.00 | 0.530076E+10 | 0.358487E+10 | 10460.05 | 17-SEP-08:52 | 6049.49 | 0.00 |
| October | 0.00 | 0.00 | 0.708285E+09 | 0.519795E+09 | 4764.98 | 12-OCT-08:53 | 3203.84 | 0.00 |
| November | 0.00 | 0.00 | 0.194212E+09 | 0.147674E+09 | 4957.73 | 05-NOV-08:52 | 3551.92 | 0.00 |
| December | 0.00 | 0.00 | 10235538.09 | 6981358.88 | 2186.35 | 01-DEC-10:00 | 1486.25 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.390501E+11 | 0.261022E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.130894E+11 | 0.819247E+10 | 13373.34 | 7499.65 | 0.00 |
Report: CoilReportMonthly
For: SAC_MEETINGROOM PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 77442040.67 | 58981140.77 | 8198.60 | 14-MAR-14:01 | 5882.31 | 0.00 |
| April | 0.00 | 0.00 | 8860936.32 | 7766044.73 | 1377.24 | 07-APR-12:15 | 1345.15 | 0.00 |
| May | 0.00 | 0.00 | 0.406489E+09 | 0.323891E+09 | 8405.27 | 10-MAY-14:01 | 6251.84 | 0.00 |
| June | 0.00 | 0.00 | 0.224395E+10 | 0.156916E+10 | 10684.37 | 27-JUN-14:01 | 5763.63 | 0.00 |
| July | 0.00 | 0.00 | 0.401643E+10 | 0.261665E+10 | 10927.46 | 05-JUL-14:01 | 5254.52 | 0.00 |
| August | 0.00 | 0.00 | 0.336501E+10 | 0.239401E+10 | 10700.98 | 15-AUG-14:01 | 5775.07 | 0.00 |
| September | 0.00 | 0.00 | 0.164363E+10 | 0.115612E+10 | 10526.07 | 14-SEP-14:01 | 5772.71 | 0.00 |
| October | 0.00 | 0.00 | 0.184036E+09 | 0.141648E+09 | 6695.12 | 11-OCT-14:01 | 5698.58 | 0.00 |
| November | 0.00 | 0.00 | 18112193.59 | 13159745.88 | 1546.52 | 16-NOV-13:05 | 1262.94 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.119640E+11 | 0.828139E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.401643E+10 | 0.261665E+10 | 10927.46 | 6251.84 | 0.00 |
Report: CoilReportMonthly
For: SAC_EMPLOYEELOUNGE PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.178461E+10 | 0.177921E+10 | 3145.69 | 11-JAN-13:00 | 2789.02 | 0.00 |
| February | 0.00 | 0.00 | 0.147046E+10 | 0.146986E+10 | 2903.84 | 22-FEB-17:02 | 2903.84 | 0.00 |
| March | 0.00 | 0.00 | 0.321424E+10 | 0.312169E+10 | 5356.39 | 14-MAR-12:00 | 4413.16 | 0.00 |
| April | 0.00 | 0.00 | 0.390266E+10 | 0.386258E+10 | 4023.27 | 20-APR-12:00 | 3728.43 | 0.00 |
| May | 0.00 | 0.00 | 0.563121E+10 | 0.540739E+10 | 5123.92 | 10-MAY-12:00 | 4283.26 | 0.00 |
| June | 0.00 | 0.00 | 0.732908E+10 | 0.648372E+10 | 6448.26 | 27-JUN-12:00 | 4918.41 | 0.00 |
| July | 0.00 | 0.00 | 0.915221E+10 | 0.755368E+10 | 6531.14 | 20-JUL-12:00 | 4938.69 | 0.00 |
| August | 0.00 | 0.00 | 0.859998E+10 | 0.746126E+10 | 6441.69 | 10-AUG-12:00 | 5108.25 | 0.00 |
| September | 0.00 | 0.00 | 0.717246E+10 | 0.646347E+10 | 6249.90 | 15-SEP-12:00 | 4880.64 | 0.00 |
| October | 0.00 | 0.00 | 0.516629E+10 | 0.499668E+10 | 5207.48 | 11-OCT-11:55 | 4731.04 | 0.00 |
| November | 0.00 | 0.00 | 0.378801E+10 | 0.374633E+10 | 4435.47 | 16-NOV-13:00 | 4021.36 | 0.00 |
| December | 0.00 | 0.00 | 0.198866E+10 | 0.198076E+10 | 3907.39 | 01-DEC-13:00 | 3304.85 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.591999E+11 | 0.543266E+11 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.147046E+10 | 0.146986E+10 | 2903.84 | 2789.02 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.915221E+10 | 0.755368E+10 | 6531.14 | 5108.25 | 0.00 |
Report: CoilReportMonthly
For: SAC_EXERCISECENTER PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 173753.81 | 114865.47 | 137.19 | 11-JAN-16:10 | 91.21 | 0.00 |
| February | 0.00 | 0.00 | 1861778.47 | 1778646.43 | 204.01 | 22-FEB-17:00 | 196.35 | 0.00 |
| March | 0.00 | 0.00 | 0.177171E+09 | 0.133038E+09 | 1708.65 | 15-MAR-15:02 | 1408.20 | 0.00 |
| April | 0.00 | 0.00 | 0.259015E+09 | 0.221522E+09 | 1174.73 | 08-APR-15:02 | 938.94 | 0.00 |
| May | 0.00 | 0.00 | 0.953270E+09 | 0.767996E+09 | 1899.25 | 14-MAY-15:02 | 1418.74 | 0.00 |
| June | 0.00 | 0.00 | 0.213967E+10 | 0.150698E+10 | 2724.89 | 27-JUN-15:02 | 1512.05 | 0.00 |
| July | 0.00 | 0.00 | 0.333760E+10 | 0.215083E+10 | 2907.61 | 20-JUL-15:02 | 1715.34 | 0.00 |
| August | 0.00 | 0.00 | 0.291284E+10 | 0.204155E+10 | 2974.73 | 13-AUG-15:02 | 1875.02 | 0.00 |
| September | 0.00 | 0.00 | 0.202129E+10 | 0.144202E+10 | 2413.30 | 16-SEP-15:02 | 1713.55 | 0.00 |
| October | 0.00 | 0.00 | 0.689228E+09 | 0.536669E+09 | 1858.62 | 11-OCT-15:02 | 1538.05 | 0.00 |
| November | 0.00 | 0.00 | 0.193623E+09 | 0.153522E+09 | 1126.82 | 05-NOV-15:02 | 808.67 | 0.00 |
| December | 0.00 | 0.00 | 1385591.46 | 944754.82 | 236.67 | 01-DEC-08:55 | 167.23 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.126871E+11 | 0.895696E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 173753.81 | 114865.47 | 137.19 | 91.21 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.333760E+10 | 0.215083E+10 | 2974.73 | 1875.02 | 0.00 |
Report: CoilReportMonthly
For: SAC_RESTROOM PTAC COOLING COIL
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 8870905.13 | 6791781.92 | 334.38 | 18-JAN-15:01 | 269.54 | 0.00 |
| February | 0.00 | 0.00 | 87965.11 | 67482.32 | 13.00 | 19-FEB-17:01 | 10.00 | 0.00 |
| March | 0.00 | 0.00 | 0.136144E+09 | 0.114830E+09 | 383.98 | 15-MAR-16:40 | 345.50 | 0.00 |
| April | 0.00 | 0.00 | 0.283106E+09 | 0.247636E+09 | 317.42 | 09-APR-15:55 | 289.41 | 0.00 |
| May | 0.00 | 0.00 | 0.655731E+09 | 0.596061E+09 | 412.06 | 24-MAY-09:00 | 351.65 | 0.00 |
| June | 0.00 | 0.00 | 0.103278E+10 | 0.950302E+09 | 589.11 | 27-JUN-16:30 | 515.51 | 0.00 |
| July | 0.00 | 0.00 | 0.126345E+10 | 0.116056E+10 | 618.44 | 20-JUL-16:20 | 553.42 | 0.00 |
| August | 0.00 | 0.00 | 0.126749E+10 | 0.117468E+10 | 612.80 | 10-AUG-16:30 | 566.37 | 0.00 |
| September | 0.00 | 0.00 | 0.106459E+10 | 0.988047E+09 | 595.25 | 17-SEP-09:00 | 517.47 | 0.00 |
| October | 0.00 | 0.00 | 0.676146E+09 | 0.620439E+09 | 469.94 | 12-OCT-16:40 | 427.45 | 0.00 |
| November | 0.00 | 0.00 | 0.365722E+09 | 0.331363E+09 | 361.29 | 05-NOV-09:00 | 315.67 | 0.00 |
| December | 0.00 | 0.00 | 38874899.71 | 32271224.39 | 355.46 | 15-DEC-13:01 | 245.74 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.679299E+10 | 0.622305E+10 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 87965.11 | 67482.32 | 13.00 | 10.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.126749E+10 | 0.117468E+10 | 618.44 | 566.37 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 29748.29 | 121513.29 | 28-JAN-16:12 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 32279.56 | 127341.65 | 12-FEB-16:12 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 14436.33 | 84803.59 | 04-MAR-16:12 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 4428.94 | 38063.82 | 16-APR-06:03 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 419.93 | 21949.32 | 11-MAY-15:15 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 32.00 | 20959.62 | 14-JUN-08:04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 0.34 | 3921.84 | 06-JUL-08:56 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 0.60 | 8353.89 | 31-AUG-08:04 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 64.41 | 16014.60 | 28-SEP-15:15 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 2084.08 | 31628.88 | 16-OCT-18:05 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 6547.60 | 79441.35 | 30-NOV-16:12 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 27001.38 | 122097.89 | 09-DEC-16:11 |
| Annual Sum or Average | 0.00 | 9645.03 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.34 | 3921.84 | ||
| Maximum of Months | 0.00 | 0.00 | 32279.56 | 127341.65 |
Report: PlantLoopDemandReportMonthly
For: SWHSYSSHOWER
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 8457.56 | 20780.79 | 31-JAN-07:14 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 8585.74 | 20854.11 | 15-FEB-07:20 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 8483.69 | 20787.68 | 01-MAR-07:16 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 8136.89 | 20206.27 | 01-APR-07:27 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 7685.46 | 19214.39 | 01-MAY-06:53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 7223.96 | 18023.06 | 01-JUN-06:14 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 6864.00 | 17019.00 | 01-JUL-07:51 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 6749.21 | 16414.30 | 01-AUG-06:40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 6856.69 | 16968.45 | 30-SEP-07:16 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 7195.89 | 17991.85 | 31-OCT-06:20 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 7655.63 | 19145.71 | 30-NOV-07:54 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 8113.68 | 20183.22 | 31-DEC-08:50 |
| Annual Sum or Average | 0.00 | 7662.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 6749.21 | 16414.30 | ||
| Maximum of Months | 0.00 | 0.00 | 8585.74 | 20854.11 |
Report: PlantLoopDemandReportMonthly
For: SWHSYSLAUNDRY
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 9516.95 | 28892.77 | 31-JAN-09:02 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 9655.07 | 28996.62 | 15-FEB-15:02 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 9523.32 | 28907.70 | 01-MAR-08:62 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 9146.65 | 28097.15 | 01-APR-07:02 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 8624.31 | 26704.66 | 01-MAY-07:02 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 8097.90 | 25040.66 | 01-JUN-07:01 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 7710.04 | 23621.70 | 01-JUL-07:02 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 7561.90 | 22765.48 | 01-AUG-07:02 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 7697.30 | 23532.49 | 30-SEP-07:26 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 8077.47 | 24964.99 | 31-OCT-14:13 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 8600.27 | 26585.93 | 30-NOV-15:03 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 9125.48 | 28048.61 | 31-DEC-13:10 |
| Annual Sum or Average | 0.00 | 8605.28 | ||||
| Minimum of Months | 0.00 | 0.00 | 7561.90 | 22765.48 | ||
| Maximum of Months | 0.00 | 0.00 | 9655.07 | 28996.62 |
Report: FanReportMonthly
For: FRONTSTAIRSFLR1 UNITHEATER FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 46026389.90 | 0.54 | 17.18 | 01-JAN-00:10 | 0.54 |
| February | 41572223.14 | 0.54 | 17.18 | 01-FEB-00:10 | 0.54 |
| March | 46026389.90 | 0.54 | 17.18 | 01-MAR-00:10 | 0.54 |
| April | 44541667.65 | 0.53 | 17.18 | 01-APR-00:10 | 0.53 |
| May | 46026389.90 | 0.53 | 17.18 | 01-MAY-00:10 | 0.53 |
| June | 44541667.65 | 0.53 | 17.18 | 01-JUN-00:10 | 0.53 |
| July | 46026389.90 | 0.53 | 17.18 | 01-JUL-00:10 | 0.53 |
| August | 46026389.90 | 0.53 | 17.18 | 01-AUG-00:10 | 0.53 |
| September | 44541667.65 | 0.53 | 17.18 | 01-SEP-00:10 | 0.53 |
| October | 46026389.90 | 0.53 | 17.18 | 01-OCT-00:10 | 0.53 |
| November | 44541667.65 | 0.53 | 17.18 | 01-NOV-00:10 | 0.53 |
| December | 46026389.90 | 0.54 | 17.18 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.541924E+09 | 0.53 | |||
| Minimum of Months | 41572223.14 | 0.53 | 17.18 | 0.53 | |
| Maximum of Months | 46026389.90 | 0.54 | 17.18 | 0.54 |
Report: FanReportMonthly
For: FRONTSTAIRSFLR2 UNITHEATER FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 41549976.43 | 0.54 | 15.51 | 01-JAN-00:10 | 0.54 |
| February | 37529010.97 | 0.54 | 15.51 | 01-FEB-00:10 | 0.54 |
| March | 41549976.43 | 0.54 | 15.51 | 01-MAR-00:10 | 0.54 |
| April | 40209654.61 | 0.53 | 15.51 | 01-APR-00:10 | 0.53 |
| May | 41549976.43 | 0.53 | 15.51 | 01-MAY-00:10 | 0.53 |
| June | 40209654.61 | 0.53 | 15.51 | 01-JUN-00:10 | 0.53 |
| July | 41549976.43 | 0.53 | 15.51 | 01-JUL-00:10 | 0.53 |
| August | 41549976.43 | 0.53 | 15.51 | 01-AUG-00:10 | 0.53 |
| September | 40209654.61 | 0.53 | 15.51 | 01-SEP-00:10 | 0.53 |
| October | 41549976.43 | 0.53 | 15.51 | 01-OCT-00:10 | 0.53 |
| November | 40209654.61 | 0.53 | 15.51 | 01-NOV-00:10 | 0.53 |
| December | 41549976.43 | 0.54 | 15.51 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.489217E+09 | 0.53 | |||
| Minimum of Months | 37529010.97 | 0.53 | 15.51 | 0.53 | |
| Maximum of Months | 41549976.43 | 0.54 | 15.51 | 0.54 |
Report: FanReportMonthly
For: FRONTSTAIRSFLR3 UNITHEATER FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 51718854.29 | 0.54 | 19.31 | 01-JAN-00:10 | 0.54 |
| February | 46713803.88 | 0.54 | 19.31 | 01-FEB-00:10 | 0.54 |
| March | 51718854.29 | 0.54 | 19.31 | 01-MAR-00:10 | 0.54 |
| April | 50050504.15 | 0.53 | 19.31 | 01-APR-00:10 | 0.53 |
| May | 51718854.29 | 0.53 | 19.31 | 01-MAY-00:10 | 0.53 |
| June | 50050504.15 | 0.53 | 19.31 | 01-JUN-00:10 | 0.53 |
| July | 51718854.29 | 0.53 | 19.31 | 01-JUL-00:10 | 0.53 |
| August | 51718854.29 | 0.53 | 19.31 | 01-AUG-00:10 | 0.53 |
| September | 50050504.15 | 0.53 | 19.31 | 01-SEP-00:10 | 0.53 |
| October | 51718854.29 | 0.53 | 19.31 | 01-OCT-00:10 | 0.53 |
| November | 50050504.15 | 0.53 | 19.31 | 01-NOV-00:10 | 0.53 |
| December | 51718854.29 | 0.54 | 19.31 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.608948E+09 | 0.53 | |||
| Minimum of Months | 46713803.88 | 0.53 | 19.31 | 0.53 | |
| Maximum of Months | 51718854.29 | 0.54 | 19.31 | 0.54 |
Report: FanReportMonthly
For: FRONTSTAIRSFLR4 UNITHEATER FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 83424535.02 | 0.54 | 31.15 | 01-JAN-00:10 | 0.54 |
| February | 75351192.92 | 0.54 | 31.15 | 01-FEB-00:10 | 0.54 |
| March | 83424535.02 | 0.54 | 31.15 | 01-MAR-00:10 | 0.54 |
| April | 80733420.99 | 0.53 | 31.15 | 01-APR-00:10 | 0.53 |
| May | 83424535.02 | 0.53 | 31.15 | 01-MAY-00:10 | 0.53 |
| June | 80733420.99 | 0.53 | 31.15 | 01-JUN-00:10 | 0.53 |
| July | 83424535.02 | 0.53 | 31.15 | 01-JUL-00:10 | 0.53 |
| August | 83424535.02 | 0.53 | 31.15 | 01-AUG-00:10 | 0.53 |
| September | 80733420.99 | 0.53 | 31.15 | 01-SEP-00:10 | 0.53 |
| October | 83424535.02 | 0.53 | 31.15 | 01-OCT-00:10 | 0.53 |
| November | 80733420.99 | 0.53 | 31.15 | 01-NOV-00:10 | 0.53 |
| December | 83424535.02 | 0.54 | 31.15 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.982257E+09 | 0.53 | |||
| Minimum of Months | 75351192.92 | 0.53 | 31.15 | 0.53 | |
| Maximum of Months | 83424535.02 | 0.54 | 31.15 | 0.54 |
Report: FanReportMonthly
For: REARSTAIRSFLR1 UNITHEATER FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 10413548.21 | 0.54 | 3.89 | 01-JAN-00:10 | 0.54 |
| February | 9405785.48 | 0.54 | 3.89 | 01-FEB-00:10 | 0.54 |
| March | 10413548.21 | 0.54 | 3.89 | 01-MAR-00:10 | 0.54 |
| April | 10077627.30 | 0.53 | 3.89 | 01-APR-00:10 | 0.53 |
| May | 10413548.21 | 0.53 | 3.89 | 01-MAY-00:10 | 0.53 |
| June | 10077627.30 | 0.53 | 3.89 | 01-JUN-00:10 | 0.53 |
| July | 10413548.21 | 0.53 | 3.89 | 01-JUL-00:10 | 0.53 |
| August | 10413548.21 | 0.53 | 3.89 | 01-AUG-00:10 | 0.53 |
| September | 10077627.30 | 0.53 | 3.89 | 01-SEP-00:10 | 0.53 |
| October | 10413548.21 | 0.53 | 3.89 | 01-OCT-00:10 | 0.53 |
| November | 10077627.30 | 0.53 | 3.89 | 01-NOV-00:10 | 0.53 |
| December | 10413548.21 | 0.54 | 3.89 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.122611E+09 | 0.53 | |||
| Minimum of Months | 9405785.48 | 0.53 | 3.89 | 0.53 | |
| Maximum of Months | 10413548.21 | 0.54 | 3.89 | 0.54 |
Report: FanReportMonthly
For: REARSTAIRSFLR2 UNITHEATER FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 10413548.21 | 0.54 | 3.89 | 01-JAN-00:10 | 0.54 |
| February | 9405785.48 | 0.54 | 3.89 | 01-FEB-00:10 | 0.54 |
| March | 10413548.21 | 0.54 | 3.89 | 01-MAR-00:10 | 0.54 |
| April | 10077627.30 | 0.53 | 3.89 | 01-APR-00:10 | 0.53 |
| May | 10413548.21 | 0.53 | 3.89 | 01-MAY-00:10 | 0.53 |
| June | 10077627.30 | 0.53 | 3.89 | 01-JUN-00:10 | 0.53 |
| July | 10413548.21 | 0.53 | 3.89 | 01-JUL-00:10 | 0.53 |
| August | 10413548.21 | 0.53 | 3.89 | 01-AUG-00:10 | 0.53 |
| September | 10077627.30 | 0.53 | 3.89 | 01-SEP-00:10 | 0.53 |
| October | 10413548.21 | 0.53 | 3.89 | 01-OCT-00:10 | 0.53 |
| November | 10077627.30 | 0.53 | 3.89 | 01-NOV-00:10 | 0.53 |
| December | 10413548.21 | 0.54 | 3.89 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.122611E+09 | 0.53 | |||
| Minimum of Months | 9405785.48 | 0.53 | 3.89 | 0.53 | |
| Maximum of Months | 10413548.21 | 0.54 | 3.89 | 0.54 |
Report: FanReportMonthly
For: REARSTAIRSFLR3 UNITHEATER FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 10413548.21 | 0.54 | 3.89 | 01-JAN-00:10 | 0.54 |
| February | 9405785.48 | 0.54 | 3.89 | 01-FEB-00:10 | 0.54 |
| March | 10413548.21 | 0.54 | 3.89 | 01-MAR-00:10 | 0.54 |
| April | 10077627.30 | 0.53 | 3.89 | 01-APR-00:10 | 0.53 |
| May | 10413548.21 | 0.53 | 3.89 | 01-MAY-00:10 | 0.53 |
| June | 10077627.30 | 0.53 | 3.89 | 01-JUN-00:10 | 0.53 |
| July | 10413548.21 | 0.53 | 3.89 | 01-JUL-00:10 | 0.53 |
| August | 10413548.21 | 0.53 | 3.89 | 01-AUG-00:10 | 0.53 |
| September | 10077627.30 | 0.53 | 3.89 | 01-SEP-00:10 | 0.53 |
| October | 10413548.21 | 0.53 | 3.89 | 01-OCT-00:10 | 0.53 |
| November | 10077627.30 | 0.53 | 3.89 | 01-NOV-00:10 | 0.53 |
| December | 10413548.21 | 0.54 | 3.89 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.122611E+09 | 0.53 | |||
| Minimum of Months | 9405785.48 | 0.53 | 3.89 | 0.53 | |
| Maximum of Months | 10413548.21 | 0.54 | 3.89 | 0.54 |
Report: FanReportMonthly
For: REARSTAIRSFLR4 UNITHEATER FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 37171651.53 | 0.54 | 13.88 | 01-JAN-00:10 | 0.54 |
| February | 33574394.93 | 0.54 | 13.88 | 01-FEB-00:10 | 0.54 |
| March | 37171651.53 | 0.54 | 13.88 | 01-MAR-00:10 | 0.54 |
| April | 35972566.00 | 0.53 | 13.88 | 01-APR-00:10 | 0.53 |
| May | 37171651.53 | 0.53 | 13.88 | 01-MAY-00:10 | 0.53 |
| June | 35972566.00 | 0.53 | 13.88 | 01-JUN-00:10 | 0.53 |
| July | 37171651.53 | 0.53 | 13.88 | 01-JUL-00:10 | 0.53 |
| August | 37171651.53 | 0.53 | 13.88 | 01-AUG-00:10 | 0.53 |
| September | 35972566.00 | 0.53 | 13.88 | 01-SEP-00:10 | 0.53 |
| October | 37171651.53 | 0.53 | 13.88 | 01-OCT-00:10 | 0.53 |
| November | 35972566.00 | 0.53 | 13.88 | 01-NOV-00:10 | 0.53 |
| December | 37171651.53 | 0.54 | 13.88 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.437666E+09 | 0.53 | |||
| Minimum of Months | 33574394.93 | 0.53 | 13.88 | 0.53 | |
| Maximum of Months | 37171651.53 | 0.54 | 13.88 | 0.54 |
Report: FanReportMonthly
For: MECHRM UNITHEATER FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: 101 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 4788925.47 | 0.02 | 42.91 | 01-JAN-15:01 | 0.54 |
| February | 4325481.07 | 0.02 | 42.91 | 01-FEB-15:01 | 0.54 |
| March | 4788925.47 | 0.02 | 42.91 | 01-MAR-15:01 | 0.54 |
| April | 4634444.01 | 0.02 | 42.91 | 01-APR-14:01 | 0.54 |
| May | 4788925.47 | 0.02 | 42.91 | 01-MAY-14:01 | 0.53 |
| June | 4634444.01 | 0.02 | 42.91 | 01-JUN-14:01 | 0.53 |
| July | 4788925.47 | 0.02 | 42.91 | 01-JUL-14:01 | 0.53 |
| August | 4788925.47 | 0.02 | 42.91 | 01-AUG-14:01 | 0.53 |
| September | 4634444.01 | 0.02 | 42.91 | 01-SEP-14:01 | 0.53 |
| October | 4788925.47 | 0.02 | 42.91 | 01-OCT-14:01 | 0.53 |
| November | 4634444.01 | 0.02 | 42.91 | 01-NOV-14:01 | 0.54 |
| December | 4788925.47 | 0.02 | 42.91 | 01-DEC-15:01 | 0.53 |
| Annual Sum or Average | 56385735.42 | 0.02 | |||
| Minimum of Months | 4325481.07 | 0.02 | 42.91 | 0.53 | |
| Maximum of Months | 4788925.47 | 0.02 | 42.91 | 0.54 |
Report: FanReportMonthly
For: 102 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 4451321.72 | 0.02 | 39.89 | 01-JAN-15:01 | 0.54 |
| February | 4020548.65 | 0.02 | 39.89 | 01-FEB-15:01 | 0.54 |
| March | 4451321.72 | 0.02 | 39.89 | 01-MAR-15:01 | 0.54 |
| April | 4307730.70 | 0.02 | 39.89 | 01-APR-14:01 | 0.54 |
| May | 4451321.72 | 0.02 | 39.89 | 01-MAY-14:01 | 0.53 |
| June | 4307730.70 | 0.02 | 39.89 | 01-JUN-14:01 | 0.53 |
| July | 4451321.72 | 0.02 | 39.89 | 01-JUL-14:01 | 0.53 |
| August | 4451321.72 | 0.02 | 39.89 | 01-AUG-14:01 | 0.53 |
| September | 4307730.70 | 0.02 | 39.89 | 01-SEP-14:01 | 0.53 |
| October | 4451321.72 | 0.02 | 39.89 | 01-OCT-14:01 | 0.53 |
| November | 4307730.70 | 0.02 | 39.89 | 01-NOV-14:01 | 0.54 |
| December | 4451321.72 | 0.02 | 39.89 | 01-DEC-15:01 | 0.53 |
| Annual Sum or Average | 52410723.46 | 0.02 | |||
| Minimum of Months | 4020548.65 | 0.02 | 39.89 | 0.53 | |
| Maximum of Months | 4451321.72 | 0.02 | 39.89 | 0.54 |
Report: FanReportMonthly
For: 103 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.137855E+09 | 0.43 | 69.66 | 01-JAN-00:10 | 0.53 |
| February | 0.125523E+09 | 0.44 | 69.66 | 01-FEB-00:10 | 0.53 |
| March | 0.135807E+09 | 0.40 | 69.66 | 01-MAR-00:10 | 0.53 |
| April | 0.130402E+09 | 0.38 | 69.66 | 01-APR-00:10 | 0.53 |
| May | 0.135058E+09 | 0.40 | 69.66 | 01-MAY-00:10 | 0.53 |
| June | 0.135000E+09 | 0.49 | 69.66 | 01-JUN-00:10 | 0.53 |
| July | 0.143903E+09 | 0.50 | 69.66 | 01-JUL-00:10 | 0.53 |
| August | 0.143278E+09 | 0.50 | 69.66 | 01-AUG-00:10 | 0.53 |
| September | 0.135039E+09 | 0.49 | 69.66 | 01-SEP-00:10 | 0.53 |
| October | 0.135207E+09 | 0.41 | 69.66 | 01-OCT-00:10 | 0.53 |
| November | 0.130410E+09 | 0.39 | 69.66 | 01-NOV-00:10 | 0.53 |
| December | 0.136850E+09 | 0.41 | 69.66 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.162433E+10 | 0.44 | |||
| Minimum of Months | 0.125523E+09 | 0.38 | 69.66 | 0.53 | |
| Maximum of Months | 0.143903E+09 | 0.50 | 69.66 | 0.53 |
Report: FanReportMonthly
For: 104 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.162878E+09 | 0.39 | 84.20 | 01-JAN-00:20 | 0.53 |
| February | 0.147256E+09 | 0.39 | 84.20 | 01-FEB-00:10 | 0.53 |
| March | 0.163319E+09 | 0.40 | 84.20 | 01-MAR-00:10 | 0.53 |
| April | 0.158548E+09 | 0.42 | 84.20 | 01-APR-00:10 | 0.53 |
| May | 0.165676E+09 | 0.48 | 84.20 | 01-MAY-00:10 | 0.53 |
| June | 0.164825E+09 | 0.50 | 84.20 | 01-JUN-00:10 | 0.53 |
| July | 0.175203E+09 | 0.51 | 84.20 | 01-JUL-00:10 | 0.53 |
| August | 0.175398E+09 | 0.51 | 84.20 | 01-AUG-00:10 | 0.53 |
| September | 0.167505E+09 | 0.51 | 84.20 | 01-SEP-00:10 | 0.53 |
| October | 0.167078E+09 | 0.49 | 84.20 | 01-OCT-00:10 | 0.53 |
| November | 0.158802E+09 | 0.43 | 84.20 | 01-NOV-00:10 | 0.53 |
| December | 0.162898E+09 | 0.39 | 84.20 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.196939E+10 | 0.45 | |||
| Minimum of Months | 0.147256E+09 | 0.39 | 84.20 | 0.53 | |
| Maximum of Months | 0.175398E+09 | 0.51 | 84.20 | 0.53 |
Report: FanReportMonthly
For: 105 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.220752E+09 | 0.49 | 112.43 | 01-JAN-00:10 | 0.53 |
| February | 0.198872E+09 | 0.48 | 112.43 | 01-FEB-00:30 | 0.53 |
| March | 0.225265E+09 | 0.52 | 112.43 | 01-MAR-00:40 | 0.53 |
| April | 0.220082E+09 | 0.53 | 112.43 | 01-APR-01:10 | 0.53 |
| May | 0.230400E+09 | 0.52 | 112.43 | 01-MAY-00:40 | 0.53 |
| June | 0.227341E+09 | 0.52 | 112.43 | 01-JUN-00:30 | 0.53 |
| July | 0.239657E+09 | 0.52 | 112.43 | 01-JUL-00:20 | 0.53 |
| August | 0.239423E+09 | 0.52 | 112.43 | 01-AUG-00:50 | 0.53 |
| September | 0.229930E+09 | 0.52 | 112.43 | 01-SEP-00:10 | 0.53 |
| October | 0.232452E+09 | 0.53 | 112.43 | 01-OCT-00:30 | 0.53 |
| November | 0.220361E+09 | 0.53 | 112.43 | 01-NOV-00:40 | 0.53 |
| December | 0.221092E+09 | 0.50 | 112.43 | 01-DEC-03:50 | 0.53 |
| Annual Sum or Average | 0.270563E+10 | 0.52 | |||
| Minimum of Months | 0.198872E+09 | 0.48 | 112.43 | 0.53 | |
| Maximum of Months | 0.239657E+09 | 0.53 | 112.43 | 0.53 |
Report: FanReportMonthly
For: 201 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 7356700.77 | 0.05 | 54.42 | 01-JAN-15:01 | 0.54 |
| February | 10249965.34 | 0.11 | 54.42 | 01-FEB-15:01 | 0.54 |
| March | 6169195.89 | 0.02 | 54.42 | 01-MAR-15:01 | 0.54 |
| April | 5876825.08 | 0.02 | 54.42 | 01-APR-14:01 | 0.53 |
| May | 6072719.25 | 0.02 | 54.42 | 01-MAY-14:01 | 0.53 |
| June | 5956660.47 | 0.03 | 54.42 | 01-JUN-14:01 | 0.53 |
| July | 6579089.52 | 0.07 | 54.42 | 01-JUL-14:01 | 0.53 |
| August | 6146337.03 | 0.04 | 54.42 | 01-AUG-14:01 | 0.53 |
| September | 5876825.08 | 0.02 | 54.42 | 01-SEP-14:01 | 0.53 |
| October | 6072719.25 | 0.02 | 54.42 | 01-OCT-14:01 | 0.53 |
| November | 5876825.08 | 0.02 | 54.42 | 01-NOV-14:01 | 0.54 |
| December | 8853815.53 | 0.08 | 54.42 | 01-DEC-15:01 | 0.53 |
| Annual Sum or Average | 81087678.27 | 0.04 | |||
| Minimum of Months | 5876825.08 | 0.02 | 54.42 | 0.53 | |
| Maximum of Months | 10249965.34 | 0.11 | 54.42 | 0.54 |
Report: FanReportMonthly
For: 202_205 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.504004E+09 | 0.39 | 260.34 | 01-JAN-00:10 | 0.53 |
| February | 0.456467E+09 | 0.39 | 260.34 | 01-FEB-00:10 | 0.53 |
| March | 0.505676E+09 | 0.40 | 260.34 | 01-MAR-00:10 | 0.53 |
| April | 0.490309E+09 | 0.42 | 260.34 | 01-APR-00:10 | 0.53 |
| May | 0.520957E+09 | 0.50 | 260.34 | 01-MAY-00:10 | 0.53 |
| June | 0.526300E+09 | 0.51 | 260.34 | 01-JUN-00:10 | 0.53 |
| July | 0.559376E+09 | 0.52 | 260.34 | 01-JUL-00:10 | 0.53 |
| August | 0.550890E+09 | 0.51 | 260.34 | 01-AUG-00:10 | 0.53 |
| September | 0.514818E+09 | 0.51 | 260.34 | 01-SEP-00:10 | 0.53 |
| October | 0.509195E+09 | 0.44 | 260.34 | 01-OCT-00:10 | 0.53 |
| November | 0.487880E+09 | 0.39 | 260.34 | 01-NOV-00:10 | 0.53 |
| December | 0.504587E+09 | 0.39 | 260.34 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.613046E+10 | 0.45 | |||
| Minimum of Months | 0.456467E+09 | 0.39 | 260.34 | 0.53 | |
| Maximum of Months | 0.559376E+09 | 0.52 | 260.34 | 0.53 |
Report: FanReportMonthly
For: 206_208 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.400347E+09 | 0.39 | 206.96 | 01-JAN-00:10 | 0.53 |
| February | 0.362015E+09 | 0.39 | 206.96 | 01-FEB-00:10 | 0.53 |
| March | 0.402334E+09 | 0.40 | 206.96 | 01-MAR-00:30 | 0.53 |
| April | 0.391061E+09 | 0.44 | 206.96 | 01-APR-00:10 | 0.53 |
| May | 0.415887E+09 | 0.51 | 206.96 | 01-MAY-00:40 | 0.53 |
| June | 0.417537E+09 | 0.51 | 206.96 | 01-JUN-00:10 | 0.53 |
| July | 0.442371E+09 | 0.52 | 206.96 | 01-JUL-00:10 | 0.53 |
| August | 0.436096E+09 | 0.51 | 206.96 | 01-AUG-00:10 | 0.53 |
| September | 0.409304E+09 | 0.51 | 206.96 | 01-SEP-00:30 | 0.53 |
| October | 0.406025E+09 | 0.45 | 206.96 | 01-OCT-00:10 | 0.53 |
| November | 0.388159E+09 | 0.40 | 206.96 | 01-NOV-00:10 | 0.53 |
| December | 0.400347E+09 | 0.39 | 206.96 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.487148E+10 | 0.45 | |||
| Minimum of Months | 0.362015E+09 | 0.39 | 206.96 | 0.53 | |
| Maximum of Months | 0.442371E+09 | 0.52 | 206.96 | 0.53 |
Report: FanReportMonthly
For: 209_212 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.488383E+09 | 0.39 | 252.47 | 01-JAN-00:10 | 0.53 |
| February | 0.441596E+09 | 0.39 | 252.47 | 01-FEB-00:10 | 0.53 |
| March | 0.490709E+09 | 0.41 | 252.47 | 01-MAR-00:10 | 0.53 |
| April | 0.477252E+09 | 0.44 | 252.47 | 01-APR-00:10 | 0.53 |
| May | 0.505597E+09 | 0.51 | 252.47 | 01-MAY-00:10 | 0.53 |
| June | 0.506446E+09 | 0.51 | 252.47 | 01-JUN-00:10 | 0.53 |
| July | 0.536112E+09 | 0.52 | 252.47 | 01-JUL-00:10 | 0.53 |
| August | 0.529554E+09 | 0.51 | 252.47 | 01-AUG-00:10 | 0.53 |
| September | 0.498776E+09 | 0.51 | 252.47 | 01-SEP-00:10 | 0.53 |
| October | 0.496351E+09 | 0.47 | 252.47 | 01-OCT-00:10 | 0.53 |
| November | 0.474174E+09 | 0.41 | 252.47 | 01-NOV-00:10 | 0.53 |
| December | 0.488383E+09 | 0.39 | 252.47 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.593333E+10 | 0.45 | |||
| Minimum of Months | 0.441596E+09 | 0.39 | 252.47 | 0.53 | |
| Maximum of Months | 0.536112E+09 | 0.52 | 252.47 | 0.53 |
Report: FanReportMonthly
For: 213 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.141909E+09 | 0.45 | 70.63 | 01-JAN-00:10 | 0.53 |
| February | 0.128833E+09 | 0.46 | 70.63 | 01-FEB-00:10 | 0.53 |
| March | 0.138066E+09 | 0.41 | 70.63 | 01-MAR-00:20 | 0.53 |
| April | 0.132351E+09 | 0.39 | 70.63 | 01-APR-00:10 | 0.53 |
| May | 0.138364E+09 | 0.45 | 70.63 | 01-MAY-00:10 | 0.53 |
| June | 0.139402E+09 | 0.50 | 70.63 | 01-JUN-00:10 | 0.53 |
| July | 0.148672E+09 | 0.51 | 70.63 | 01-JUL-00:10 | 0.53 |
| August | 0.146645E+09 | 0.51 | 70.63 | 01-AUG-00:10 | 0.53 |
| September | 0.136943E+09 | 0.49 | 70.63 | 01-SEP-00:10 | 0.53 |
| October | 0.136938E+09 | 0.41 | 70.63 | 01-OCT-00:10 | 0.53 |
| November | 0.132226E+09 | 0.38 | 70.63 | 01-NOV-00:10 | 0.53 |
| December | 0.141125E+09 | 0.44 | 70.63 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.166147E+10 | 0.45 | |||
| Minimum of Months | 0.128833E+09 | 0.38 | 70.63 | 0.53 | |
| Maximum of Months | 0.148672E+09 | 0.51 | 70.63 | 0.53 |
Report: FanReportMonthly
For: 214 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.177001E+09 | 0.39 | 91.44 | 01-JAN-00:10 | 0.53 |
| February | 0.159909E+09 | 0.39 | 91.44 | 01-FEB-00:10 | 0.53 |
| March | 0.178863E+09 | 0.44 | 91.44 | 01-MAR-00:10 | 0.53 |
| April | 0.175538E+09 | 0.49 | 91.44 | 01-APR-00:10 | 0.53 |
| May | 0.185464E+09 | 0.52 | 91.44 | 01-MAY-00:10 | 0.53 |
| June | 0.184478E+09 | 0.52 | 91.44 | 01-JUN-00:10 | 0.53 |
| July | 0.195809E+09 | 0.52 | 91.44 | 01-JUL-00:10 | 0.53 |
| August | 0.194830E+09 | 0.52 | 91.44 | 01-AUG-00:10 | 0.53 |
| September | 0.185307E+09 | 0.52 | 91.44 | 01-SEP-00:10 | 0.53 |
| October | 0.184284E+09 | 0.52 | 91.44 | 01-OCT-00:10 | 0.53 |
| November | 0.173853E+09 | 0.45 | 91.44 | 01-NOV-00:10 | 0.53 |
| December | 0.177104E+09 | 0.40 | 91.44 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.217244E+10 | 0.47 | |||
| Minimum of Months | 0.159909E+09 | 0.39 | 91.44 | 0.53 | |
| Maximum of Months | 0.195809E+09 | 0.52 | 91.44 | 0.53 |
Report: FanReportMonthly
For: 215_218 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.161486E+09 | 0.46 | 732.00 | 01-JAN-15:01 | 0.54 |
| February | 0.140225E+09 | 0.42 | 732.00 | 01-FEB-15:01 | 0.54 |
| March | 0.230143E+09 | 0.58 | 732.00 | 01-MAR-15:01 | 0.54 |
| April | 0.251499E+09 | 0.61 | 732.00 | 01-APR-14:01 | 0.53 |
| May | 0.310710E+09 | 0.61 | 732.00 | 01-MAY-14:01 | 0.53 |
| June | 0.350771E+09 | 0.61 | 732.00 | 01-JUN-14:01 | 0.53 |
| July | 0.396403E+09 | 0.61 | 732.00 | 01-JUL-14:01 | 0.53 |
| August | 0.393390E+09 | 0.61 | 732.00 | 01-AUG-14:01 | 0.53 |
| September | 0.358251E+09 | 0.61 | 732.00 | 01-SEP-14:01 | 0.53 |
| October | 0.295581E+09 | 0.61 | 732.00 | 01-OCT-14:01 | 0.53 |
| November | 0.231007E+09 | 0.62 | 732.00 | 01-NOV-14:01 | 0.54 |
| December | 0.159462E+09 | 0.46 | 732.00 | 01-DEC-15:01 | 0.53 |
| Annual Sum or Average | 0.327893E+10 | 0.57 | |||
| Minimum of Months | 0.140225E+09 | 0.42 | 732.00 | 0.53 | |
| Maximum of Months | 0.396403E+09 | 0.62 | 732.00 | 0.54 |
Report: FanReportMonthly
For: 219 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.813387E+09 | 0.55 | 389.99 | 01-JAN-00:10 | 0.53 |
| February | 0.733534E+09 | 0.55 | 389.99 | 01-FEB-00:10 | 0.53 |
| March | 0.824353E+09 | 0.55 | 389.99 | 01-MAR-00:10 | 0.53 |
| April | 0.802040E+09 | 0.55 | 389.99 | 01-APR-00:10 | 0.53 |
| May | 0.833567E+09 | 0.55 | 389.99 | 01-MAY-00:10 | 0.53 |
| June | 0.811750E+09 | 0.54 | 389.99 | 01-JUN-00:10 | 0.53 |
| July | 0.846607E+09 | 0.54 | 389.99 | 01-JUL-00:10 | 0.53 |
| August | 0.844677E+09 | 0.54 | 389.99 | 01-AUG-00:10 | 0.53 |
| September | 0.814306E+09 | 0.54 | 389.99 | 01-SEP-00:10 | 0.53 |
| October | 0.833443E+09 | 0.55 | 389.99 | 01-OCT-00:10 | 0.53 |
| November | 0.798555E+09 | 0.55 | 389.99 | 01-NOV-00:10 | 0.53 |
| December | 0.812931E+09 | 0.55 | 389.99 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.976915E+10 | 0.55 | |||
| Minimum of Months | 0.733534E+09 | 0.54 | 389.99 | 0.53 | |
| Maximum of Months | 0.846607E+09 | 0.55 | 389.99 | 0.53 |
Report: FanReportMonthly
For: 220_223 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.605323E+09 | 0.41 | 312.19 | 01-JAN-00:10 | 0.53 |
| February | 0.546677E+09 | 0.40 | 312.19 | 01-FEB-00:10 | 0.53 |
| March | 0.615462E+09 | 0.47 | 312.19 | 01-MAR-00:10 | 0.53 |
| April | 0.603108E+09 | 0.50 | 312.19 | 01-APR-00:10 | 0.53 |
| May | 0.634442E+09 | 0.52 | 312.19 | 01-MAY-00:10 | 0.53 |
| June | 0.626503E+09 | 0.52 | 312.19 | 01-JUN-00:10 | 0.53 |
| July | 0.661055E+09 | 0.52 | 312.19 | 01-JUL-00:10 | 0.53 |
| August | 0.658317E+09 | 0.52 | 312.19 | 01-AUG-00:10 | 0.53 |
| September | 0.630132E+09 | 0.52 | 312.19 | 01-SEP-00:10 | 0.53 |
| October | 0.632497E+09 | 0.52 | 312.19 | 01-OCT-00:10 | 0.53 |
| November | 0.597202E+09 | 0.47 | 312.19 | 01-NOV-00:10 | 0.53 |
| December | 0.605717E+09 | 0.40 | 312.19 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.741643E+10 | 0.48 | |||
| Minimum of Months | 0.546677E+09 | 0.40 | 312.19 | 0.53 | |
| Maximum of Months | 0.661055E+09 | 0.52 | 312.19 | 0.53 |
Report: FanReportMonthly
For: 224 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.174101E+09 | 0.39 | 89.98 | 01-JAN-00:10 | 0.53 |
| February | 0.157310E+09 | 0.39 | 89.98 | 01-FEB-00:10 | 0.53 |
| March | 0.175405E+09 | 0.42 | 89.98 | 01-MAR-00:10 | 0.53 |
| April | 0.171786E+09 | 0.47 | 89.98 | 01-APR-00:10 | 0.53 |
| May | 0.181561E+09 | 0.51 | 89.98 | 01-MAY-00:10 | 0.53 |
| June | 0.180629E+09 | 0.52 | 89.98 | 01-JUN-00:10 | 0.53 |
| July | 0.191711E+09 | 0.52 | 89.98 | 01-JUL-00:10 | 0.53 |
| August | 0.190838E+09 | 0.52 | 89.98 | 01-AUG-00:10 | 0.53 |
| September | 0.181718E+09 | 0.52 | 89.98 | 01-SEP-00:10 | 0.53 |
| October | 0.180448E+09 | 0.51 | 89.98 | 01-OCT-00:10 | 0.53 |
| November | 0.170405E+09 | 0.44 | 89.98 | 01-NOV-00:10 | 0.53 |
| December | 0.174150E+09 | 0.39 | 89.98 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.213006E+10 | 0.47 | |||
| Minimum of Months | 0.157310E+09 | 0.39 | 89.98 | 0.53 | |
| Maximum of Months | 0.191711E+09 | 0.52 | 89.98 | 0.53 |
Report: FanReportMonthly
For: 301 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 32543129.33 | 0.37 | 57.80 | 01-JAN-15:01 | 0.54 |
| February | 30009125.73 | 0.36 | 57.80 | 01-FEB-15:01 | 0.54 |
| March | 13049111.57 | 0.12 | 57.80 | 01-MAR-15:01 | 0.54 |
| April | 6241860.66 | 0.02 | 57.80 | 01-APR-14:01 | 0.54 |
| May | 6449922.68 | 0.02 | 57.80 | 01-MAY-14:01 | 0.53 |
| June | 6285334.48 | 0.03 | 57.80 | 01-JUN-14:01 | 0.53 |
| July | 6779173.44 | 0.06 | 57.80 | 01-JUL-14:01 | 0.53 |
| August | 6464241.64 | 0.03 | 57.80 | 01-AUG-14:01 | 0.53 |
| September | 6241860.66 | 0.02 | 57.80 | 01-SEP-14:01 | 0.53 |
| October | 6449922.68 | 0.02 | 57.80 | 01-OCT-14:01 | 0.53 |
| November | 6241860.66 | 0.02 | 57.80 | 01-NOV-14:01 | 0.54 |
| December | 28432959.03 | 0.29 | 57.80 | 01-DEC-15:01 | 0.53 |
| Annual Sum or Average | 0.155189E+09 | 0.11 | |||
| Minimum of Months | 6241860.66 | 0.02 | 57.80 | 0.53 | |
| Maximum of Months | 32543129.33 | 0.37 | 57.80 | 0.54 |
Report: FanReportMonthly
For: 302_305 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 33773979.74 | 0.16 | 138.07 | 01-JAN-15:01 | 0.54 |
| February | 32339574.21 | 0.14 | 138.07 | 01-FEB-15:01 | 0.54 |
| March | 17482917.96 | 0.04 | 138.07 | 01-MAR-15:01 | 0.54 |
| April | 14911038.49 | 0.02 | 138.07 | 01-APR-14:01 | 0.53 |
| May | 15408073.11 | 0.02 | 138.07 | 01-MAY-14:01 | 0.53 |
| June | 14938696.65 | 0.03 | 138.07 | 01-JUN-14:01 | 0.53 |
| July | 15909362.88 | 0.05 | 138.07 | 01-JUL-14:01 | 0.53 |
| August | 15411623.79 | 0.02 | 138.07 | 01-AUG-14:01 | 0.53 |
| September | 14911038.49 | 0.02 | 138.07 | 01-SEP-14:01 | 0.53 |
| October | 15408073.11 | 0.02 | 138.07 | 01-OCT-14:01 | 0.53 |
| November | 14911038.49 | 0.02 | 138.07 | 01-NOV-14:01 | 0.54 |
| December | 35569711.92 | 0.15 | 138.07 | 01-DEC-15:01 | 0.53 |
| Annual Sum or Average | 0.240975E+09 | 0.06 | |||
| Minimum of Months | 14911038.49 | 0.02 | 138.07 | 0.53 | |
| Maximum of Months | 35569711.92 | 0.16 | 138.07 | 0.54 |
Report: FanReportMonthly
For: 306_308 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 12416727.84 | 0.03 | 105.97 | 01-JAN-15:01 | 0.54 |
| February | 14829269.58 | 0.05 | 105.97 | 01-FEB-15:01 | 0.54 |
| March | 11826649.58 | 0.02 | 105.97 | 01-MAR-15:01 | 0.54 |
| April | 11445144.75 | 0.02 | 105.97 | 01-APR-14:01 | 0.53 |
| May | 11826649.58 | 0.02 | 105.97 | 01-MAY-14:01 | 0.53 |
| June | 11445144.75 | 0.02 | 105.97 | 01-JUN-14:01 | 0.53 |
| July | 11900156.55 | 0.03 | 105.97 | 01-JUL-14:01 | 0.53 |
| August | 11826649.58 | 0.02 | 105.97 | 01-AUG-14:01 | 0.53 |
| September | 11445144.75 | 0.02 | 105.97 | 01-SEP-14:01 | 0.53 |
| October | 11826649.58 | 0.02 | 105.97 | 01-OCT-14:01 | 0.53 |
| November | 11445144.75 | 0.02 | 105.97 | 01-NOV-14:01 | 0.54 |
| December | 13577975.48 | 0.04 | 105.97 | 01-DEC-15:01 | 0.53 |
| Annual Sum or Average | 0.145811E+09 | 0.03 | |||
| Minimum of Months | 11445144.75 | 0.02 | 105.97 | 0.53 | |
| Maximum of Months | 14829269.58 | 0.05 | 105.97 | 0.54 |
Report: FanReportMonthly
For: 309_312 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.474289E+09 | 0.39 | 244.48 | 01-JAN-00:10 | 0.53 |
| February | 0.429182E+09 | 0.40 | 244.48 | 01-FEB-00:20 | 0.53 |
| March | 0.474581E+09 | 0.40 | 244.48 | 01-MAR-00:10 | 0.53 |
| April | 0.460659E+09 | 0.42 | 244.48 | 01-APR-00:10 | 0.53 |
| May | 0.486726E+09 | 0.49 | 244.48 | 01-MAY-00:10 | 0.53 |
| June | 0.488703E+09 | 0.51 | 244.48 | 01-JUN-00:10 | 0.53 |
| July | 0.517721E+09 | 0.51 | 244.48 | 01-JUL-00:10 | 0.53 |
| August | 0.509772E+09 | 0.51 | 244.48 | 01-AUG-00:10 | 0.53 |
| September | 0.477621E+09 | 0.50 | 244.48 | 01-SEP-00:10 | 0.53 |
| October | 0.476419E+09 | 0.43 | 244.48 | 01-OCT-00:10 | 0.53 |
| November | 0.458166E+09 | 0.39 | 244.48 | 01-NOV-00:10 | 0.53 |
| December | 0.475031E+09 | 0.40 | 244.48 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.572887E+10 | 0.45 | |||
| Minimum of Months | 0.429182E+09 | 0.39 | 244.48 | 0.53 | |
| Maximum of Months | 0.517721E+09 | 0.51 | 244.48 | 0.53 |
Report: FanReportMonthly
For: 313 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 21173085.84 | 0.26 | 64.95 | 01-JAN-15:01 | 0.54 |
| February | 20176599.17 | 0.22 | 64.95 | 01-FEB-15:01 | 0.54 |
| March | 9129750.98 | 0.06 | 64.95 | 01-MAR-15:01 | 0.54 |
| April | 7015016.53 | 0.02 | 64.95 | 01-APR-14:01 | 0.53 |
| May | 7248850.42 | 0.02 | 64.95 | 01-MAY-14:01 | 0.53 |
| June | 7015016.53 | 0.02 | 64.95 | 01-JUN-14:01 | 0.53 |
| July | 7250255.14 | 0.02 | 64.95 | 01-JUL-14:01 | 0.53 |
| August | 7248850.42 | 0.02 | 64.95 | 01-AUG-14:01 | 0.53 |
| September | 7015016.53 | 0.02 | 64.95 | 01-SEP-14:01 | 0.53 |
| October | 7248850.42 | 0.02 | 64.95 | 01-OCT-14:01 | 0.53 |
| November | 7015016.53 | 0.02 | 64.95 | 01-NOV-14:01 | 0.54 |
| December | 20428306.91 | 0.20 | 64.95 | 01-DEC-15:01 | 0.53 |
| Annual Sum or Average | 0.127965E+09 | 0.08 | |||
| Minimum of Months | 7015016.53 | 0.02 | 64.95 | 0.53 | |
| Maximum of Months | 21173085.84 | 0.26 | 64.95 | 0.54 |
Report: FanReportMonthly
For: 314 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.162035E+09 | 0.40 | 83.43 | 01-JAN-00:10 | 0.53 |
| February | 0.146949E+09 | 0.40 | 83.43 | 01-FEB-00:20 | 0.53 |
| March | 0.162251E+09 | 0.40 | 83.43 | 01-MAR-00:10 | 0.53 |
| April | 0.158149E+09 | 0.43 | 83.43 | 01-APR-00:10 | 0.53 |
| May | 0.167079E+09 | 0.50 | 83.43 | 01-MAY-00:10 | 0.53 |
| June | 0.167402E+09 | 0.51 | 83.43 | 01-JUN-00:10 | 0.53 |
| July | 0.178450E+09 | 0.52 | 83.43 | 01-JUL-00:10 | 0.53 |
| August | 0.176903E+09 | 0.52 | 83.43 | 01-AUG-00:10 | 0.53 |
| September | 0.166936E+09 | 0.51 | 83.43 | 01-SEP-00:10 | 0.53 |
| October | 0.164700E+09 | 0.46 | 83.43 | 01-OCT-00:10 | 0.53 |
| November | 0.156778E+09 | 0.41 | 83.43 | 01-NOV-00:10 | 0.53 |
| December | 0.162497E+09 | 0.40 | 83.43 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.197013E+10 | 0.46 | |||
| Minimum of Months | 0.146949E+09 | 0.40 | 83.43 | 0.53 | |
| Maximum of Months | 0.178450E+09 | 0.52 | 83.43 | 0.53 |
Report: FanReportMonthly
For: 315_318 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.674535E+09 | 0.44 | 345.94 | 01-JAN-00:20 | 0.53 |
| February | 0.609218E+09 | 0.44 | 345.94 | 01-FEB-00:20 | 0.53 |
| March | 0.693203E+09 | 0.51 | 345.94 | 01-MAR-00:10 | 0.53 |
| April | 0.679604E+09 | 0.52 | 345.94 | 01-APR-00:10 | 0.53 |
| May | 0.715728E+09 | 0.53 | 345.94 | 01-MAY-00:10 | 0.53 |
| June | 0.707149E+09 | 0.52 | 345.94 | 01-JUN-00:10 | 0.53 |
| July | 0.746599E+09 | 0.52 | 345.94 | 01-JUL-00:10 | 0.53 |
| August | 0.742129E+09 | 0.52 | 345.94 | 01-AUG-00:10 | 0.53 |
| September | 0.708517E+09 | 0.52 | 345.94 | 01-SEP-00:10 | 0.53 |
| October | 0.709392E+09 | 0.53 | 345.94 | 01-OCT-00:10 | 0.53 |
| November | 0.668677E+09 | 0.50 | 345.94 | 01-NOV-00:10 | 0.53 |
| December | 0.674292E+09 | 0.43 | 345.94 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.832904E+10 | 0.50 | |||
| Minimum of Months | 0.609218E+09 | 0.43 | 345.94 | 0.53 | |
| Maximum of Months | 0.746599E+09 | 0.53 | 345.94 | 0.53 |
Report: FanReportMonthly
For: 319 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 8518156.09 | 0.02 | 76.33 | 01-JAN-15:01 | 0.54 |
| February | 7693818.40 | 0.02 | 76.33 | 01-FEB-15:01 | 0.54 |
| March | 8592770.45 | 0.03 | 76.33 | 01-MAR-15:01 | 0.54 |
| April | 8243582.78 | 0.02 | 76.33 | 01-APR-14:01 | 0.53 |
| May | 8727448.36 | 0.06 | 76.33 | 01-MAY-14:01 | 0.53 |
| June | 10780304.46 | 0.24 | 76.33 | 01-JUN-14:01 | 0.53 |
| July | 13937727.17 | 0.34 | 76.33 | 01-JUL-14:01 | 0.53 |
| August | 13800789.05 | 0.31 | 76.33 | 01-AUG-14:01 | 0.53 |
| September | 11682514.34 | 0.24 | 76.33 | 01-SEP-14:01 | 0.53 |
| October | 8870246.97 | 0.05 | 76.33 | 01-OCT-14:01 | 0.53 |
| November | 8243376.86 | 0.02 | 76.33 | 01-NOV-14:01 | 0.54 |
| December | 8518156.09 | 0.02 | 76.33 | 01-DEC-15:01 | 0.53 |
| Annual Sum or Average | 0.117609E+09 | 0.12 | |||
| Minimum of Months | 7693818.40 | 0.02 | 76.33 | 0.53 | |
| Maximum of Months | 13937727.17 | 0.34 | 76.33 | 0.54 |
Report: FanReportMonthly
For: 320_323 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.570383E+09 | 0.39 | 294.56 | 01-JAN-00:10 | 0.53 |
| February | 0.515315E+09 | 0.40 | 294.56 | 01-FEB-00:10 | 0.53 |
| March | 0.577140E+09 | 0.45 | 294.56 | 01-MAR-00:10 | 0.53 |
| April | 0.564411E+09 | 0.47 | 294.56 | 01-APR-00:10 | 0.53 |
| May | 0.594133E+09 | 0.51 | 294.56 | 01-MAY-00:10 | 0.53 |
| June | 0.588789E+09 | 0.51 | 294.56 | 01-JUN-00:10 | 0.53 |
| July | 0.622493E+09 | 0.52 | 294.56 | 01-JUL-00:10 | 0.53 |
| August | 0.618661E+09 | 0.51 | 294.56 | 01-AUG-00:10 | 0.53 |
| September | 0.589589E+09 | 0.51 | 294.56 | 01-SEP-00:10 | 0.53 |
| October | 0.588294E+09 | 0.49 | 294.56 | 01-OCT-00:10 | 0.53 |
| November | 0.558273E+09 | 0.44 | 294.56 | 01-NOV-00:10 | 0.53 |
| December | 0.570646E+09 | 0.40 | 294.56 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.695813E+10 | 0.47 | |||
| Minimum of Months | 0.515315E+09 | 0.39 | 294.56 | 0.53 | |
| Maximum of Months | 0.622493E+09 | 0.52 | 294.56 | 0.53 |
Report: FanReportMonthly
For: 324 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 5904337.15 | 0.02 | 52.91 | 01-JAN-15:01 | 0.54 |
| February | 5399792.83 | 0.02 | 52.91 | 01-FEB-15:01 | 0.54 |
| March | 5904337.15 | 0.02 | 52.91 | 01-MAR-15:01 | 0.54 |
| April | 5713874.66 | 0.02 | 52.91 | 01-APR-14:01 | 0.53 |
| May | 5904337.15 | 0.02 | 52.91 | 01-MAY-14:01 | 0.53 |
| June | 5714663.47 | 0.02 | 52.91 | 01-JUN-14:01 | 0.53 |
| July | 6007344.72 | 0.04 | 52.91 | 01-JUL-14:01 | 0.53 |
| August | 6115675.36 | 0.05 | 52.91 | 01-AUG-14:01 | 0.53 |
| September | 5845074.36 | 0.03 | 52.91 | 01-SEP-14:01 | 0.53 |
| October | 5904337.15 | 0.02 | 52.91 | 01-OCT-14:01 | 0.53 |
| November | 5713874.66 | 0.02 | 52.91 | 01-NOV-14:01 | 0.54 |
| December | 5904337.15 | 0.02 | 52.91 | 01-DEC-15:01 | 0.53 |
| Annual Sum or Average | 70031985.78 | 0.03 | |||
| Minimum of Months | 5399792.83 | 0.02 | 52.91 | 0.53 | |
| Maximum of Months | 6115675.36 | 0.05 | 52.91 | 0.54 |
Report: FanReportMonthly
For: 401 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.185387E+09 | 0.51 | 85.81 | 01-JAN-00:10 | 0.53 |
| February | 0.166840E+09 | 0.51 | 85.81 | 01-FEB-00:10 | 0.54 |
| March | 0.172764E+09 | 0.45 | 85.81 | 01-MAR-00:10 | 0.53 |
| April | 0.162172E+09 | 0.43 | 85.81 | 01-APR-00:10 | 0.53 |
| May | 0.171962E+09 | 0.48 | 85.81 | 01-MAY-00:10 | 0.53 |
| June | 0.175634E+09 | 0.51 | 85.81 | 01-JUN-00:10 | 0.53 |
| July | 0.187984E+09 | 0.52 | 85.81 | 01-JUL-00:10 | 0.53 |
| August | 0.183721E+09 | 0.51 | 85.81 | 01-AUG-00:10 | 0.53 |
| September | 0.168643E+09 | 0.48 | 85.81 | 01-SEP-00:10 | 0.53 |
| October | 0.166608E+09 | 0.41 | 85.81 | 01-OCT-00:10 | 0.53 |
| November | 0.164110E+09 | 0.43 | 85.81 | 01-NOV-00:10 | 0.53 |
| December | 0.184534E+09 | 0.51 | 85.81 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.209036E+10 | 0.48 | |||
| Minimum of Months | 0.162172E+09 | 0.41 | 85.81 | 0.53 | |
| Maximum of Months | 0.187984E+09 | 0.52 | 85.81 | 0.54 |
Report: FanReportMonthly
For: 402_405 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.174776E+09 | 0.49 | 209.97 | 01-JAN-15:01 | 0.54 |
| February | 0.156071E+09 | 0.47 | 209.97 | 01-FEB-15:01 | 0.54 |
| March | 83239238.98 | 0.23 | 209.97 | 01-MAR-15:01 | 0.54 |
| April | 26455727.05 | 0.04 | 209.97 | 01-APR-14:01 | 0.53 |
| May | 23557690.46 | 0.03 | 209.97 | 01-MAY-14:01 | 0.53 |
| June | 30758875.36 | 0.14 | 209.97 | 01-JUN-14:01 | 0.53 |
| July | 40216467.33 | 0.22 | 209.97 | 01-JUL-14:01 | 0.53 |
| August | 32657605.81 | 0.15 | 209.97 | 01-AUG-14:01 | 0.53 |
| September | 23091076.46 | 0.03 | 209.97 | 01-SEP-14:01 | 0.53 |
| October | 26052628.94 | 0.04 | 209.97 | 01-OCT-14:01 | 0.53 |
| November | 39896502.95 | 0.12 | 209.97 | 01-NOV-14:01 | 0.54 |
| December | 0.156600E+09 | 0.46 | 209.97 | 01-DEC-15:01 | 0.53 |
| Annual Sum or Average | 0.813373E+09 | 0.20 | |||
| Minimum of Months | 23091076.46 | 0.03 | 209.97 | 0.53 | |
| Maximum of Months | 0.174776E+09 | 0.49 | 209.97 | 0.54 |
Report: FanReportMonthly
For: 406_408 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.121848E+09 | 0.45 | 165.43 | 01-JAN-15:01 | 0.54 |
| February | 0.108897E+09 | 0.43 | 165.43 | 01-FEB-15:01 | 0.54 |
| March | 56606390.79 | 0.19 | 165.43 | 01-MAR-15:01 | 0.54 |
| April | 19490184.28 | 0.03 | 165.43 | 01-APR-14:01 | 0.53 |
| May | 18549411.75 | 0.03 | 165.43 | 01-MAY-14:01 | 0.53 |
| June | 23682547.85 | 0.14 | 165.43 | 01-JUN-14:01 | 0.53 |
| July | 30491846.71 | 0.21 | 165.43 | 01-JUL-14:01 | 0.53 |
| August | 25016093.02 | 0.15 | 165.43 | 01-AUG-14:01 | 0.53 |
| September | 18156042.01 | 0.03 | 165.43 | 01-SEP-14:01 | 0.53 |
| October | 19285100.01 | 0.03 | 165.43 | 01-OCT-14:01 | 0.53 |
| November | 24547486.37 | 0.08 | 165.43 | 01-NOV-14:01 | 0.54 |
| December | 0.106833E+09 | 0.41 | 165.43 | 01-DEC-15:01 | 0.53 |
| Annual Sum or Average | 0.573403E+09 | 0.18 | |||
| Minimum of Months | 18156042.01 | 0.03 | 165.43 | 0.53 | |
| Maximum of Months | 0.121848E+09 | 0.45 | 165.43 | 0.54 |
Report: FanReportMonthly
For: 409_412 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.630030E+09 | 0.44 | 316.19 | 01-JAN-00:10 | 0.53 |
| February | 0.564448E+09 | 0.43 | 316.19 | 01-FEB-00:10 | 0.53 |
| March | 0.615410E+09 | 0.41 | 316.19 | 01-MAR-00:10 | 0.53 |
| April | 0.600426E+09 | 0.44 | 316.19 | 01-APR-00:10 | 0.53 |
| May | 0.639687E+09 | 0.50 | 316.19 | 01-MAY-00:10 | 0.53 |
| June | 0.643048E+09 | 0.51 | 316.19 | 01-JUN-00:10 | 0.53 |
| July | 0.680722E+09 | 0.52 | 316.19 | 01-JUL-00:10 | 0.53 |
| August | 0.669330E+09 | 0.51 | 316.19 | 01-AUG-00:10 | 0.53 |
| September | 0.623460E+09 | 0.50 | 316.19 | 01-SEP-00:10 | 0.53 |
| October | 0.617157E+09 | 0.43 | 316.19 | 01-OCT-00:10 | 0.53 |
| November | 0.592788E+09 | 0.40 | 316.19 | 01-NOV-00:10 | 0.53 |
| December | 0.629073E+09 | 0.44 | 316.19 | 01-DEC-00:20 | 0.53 |
| Annual Sum or Average | 0.750558E+10 | 0.46 | |||
| Minimum of Months | 0.564448E+09 | 0.40 | 316.19 | 0.53 | |
| Maximum of Months | 0.680722E+09 | 0.52 | 316.19 | 0.53 |
Report: FanReportMonthly
For: 413 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 66946203.49 | 0.48 | 87.53 | 01-JAN-15:01 | 0.54 |
| February | 62626950.93 | 0.48 | 87.53 | 01-FEB-15:01 | 0.54 |
| March | 31394461.56 | 0.23 | 87.53 | 01-MAR-15:01 | 0.54 |
| April | 10826884.75 | 0.04 | 87.53 | 01-APR-14:01 | 0.53 |
| May | 9768155.54 | 0.02 | 87.53 | 01-MAY-14:01 | 0.53 |
| June | 10728797.96 | 0.11 | 87.53 | 01-JUN-14:01 | 0.53 |
| July | 12907730.55 | 0.18 | 87.53 | 01-JUL-14:01 | 0.53 |
| August | 11364131.49 | 0.12 | 87.53 | 01-AUG-14:01 | 0.53 |
| September | 9488263.43 | 0.03 | 87.53 | 01-SEP-14:01 | 0.53 |
| October | 10155247.01 | 0.03 | 87.53 | 01-OCT-14:01 | 0.53 |
| November | 13462843.66 | 0.10 | 87.53 | 01-NOV-14:01 | 0.54 |
| December | 60329185.05 | 0.45 | 87.53 | 01-DEC-15:01 | 0.53 |
| Annual Sum or Average | 0.309999E+09 | 0.19 | |||
| Minimum of Months | 9488263.43 | 0.02 | 87.53 | 0.53 | |
| Maximum of Months | 66946203.49 | 0.48 | 87.53 | 0.54 |
Report: FanReportMonthly
For: 414 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 30234298.54 | 0.23 | 83.11 | 01-JAN-15:01 | 0.54 |
| February | 30247936.15 | 0.25 | 83.11 | 01-FEB-15:01 | 0.54 |
| March | 13509097.17 | 0.08 | 83.11 | 01-MAR-15:01 | 0.54 |
| April | 8995594.03 | 0.03 | 83.11 | 01-APR-14:01 | 0.53 |
| May | 9772554.69 | 0.06 | 83.11 | 01-MAY-14:01 | 0.53 |
| June | 12099619.75 | 0.15 | 83.11 | 01-JUN-14:01 | 0.53 |
| July | 15962321.93 | 0.21 | 83.11 | 01-JUL-14:01 | 0.53 |
| August | 15089013.98 | 0.18 | 83.11 | 01-AUG-14:01 | 0.53 |
| September | 11363306.06 | 0.11 | 83.11 | 01-SEP-14:01 | 0.53 |
| October | 9491446.70 | 0.03 | 83.11 | 01-OCT-14:01 | 0.53 |
| November | 8976301.41 | 0.02 | 83.11 | 01-NOV-14:01 | 0.54 |
| December | 29243296.11 | 0.22 | 83.11 | 01-DEC-15:01 | 0.53 |
| Annual Sum or Average | 0.194985E+09 | 0.13 | |||
| Minimum of Months | 8976301.41 | 0.02 | 83.11 | 0.53 | |
| Maximum of Months | 30247936.15 | 0.25 | 83.11 | 0.54 |
Report: FanReportMonthly
For: 415_418 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.761955E+09 | 0.41 | 392.56 | 01-JAN-00:10 | 0.53 |
| February | 0.689628E+09 | 0.41 | 392.56 | 01-FEB-00:10 | 0.53 |
| March | 0.776446E+09 | 0.46 | 392.56 | 01-MAR-00:10 | 0.53 |
| April | 0.763985E+09 | 0.48 | 392.56 | 01-APR-00:20 | 0.53 |
| May | 0.807626E+09 | 0.51 | 392.56 | 01-MAY-00:10 | 0.53 |
| June | 0.802165E+09 | 0.52 | 392.56 | 01-JUN-00:10 | 0.53 |
| July | 0.847467E+09 | 0.52 | 392.56 | 01-JUL-00:10 | 0.53 |
| August | 0.840534E+09 | 0.51 | 392.56 | 01-AUG-00:20 | 0.53 |
| September | 0.796455E+09 | 0.51 | 392.56 | 01-SEP-00:10 | 0.53 |
| October | 0.789571E+09 | 0.49 | 392.56 | 01-OCT-00:10 | 0.53 |
| November | 0.746298E+09 | 0.44 | 392.56 | 01-NOV-00:10 | 0.53 |
| December | 0.762625E+09 | 0.40 | 392.56 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.938476E+10 | 0.47 | |||
| Minimum of Months | 0.689628E+09 | 0.40 | 392.56 | 0.53 | |
| Maximum of Months | 0.847467E+09 | 0.52 | 392.56 | 0.53 |
Report: FanReportMonthly
For: 419 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.204998E+09 | 0.40 | 105.72 | 01-JAN-00:10 | 0.53 |
| February | 0.185566E+09 | 0.40 | 105.72 | 01-FEB-00:10 | 0.53 |
| March | 0.207995E+09 | 0.45 | 105.72 | 01-MAR-00:10 | 0.53 |
| April | 0.204733E+09 | 0.47 | 105.72 | 01-APR-00:10 | 0.53 |
| May | 0.217153E+09 | 0.51 | 105.72 | 01-MAY-00:10 | 0.53 |
| June | 0.216341E+09 | 0.52 | 105.72 | 01-JUN-00:10 | 0.53 |
| July | 0.228949E+09 | 0.52 | 105.72 | 01-JUL-00:40 | 0.53 |
| August | 0.226944E+09 | 0.52 | 105.72 | 01-AUG-00:10 | 0.53 |
| September | 0.214534E+09 | 0.51 | 105.72 | 01-SEP-00:10 | 0.53 |
| October | 0.211704E+09 | 0.48 | 105.72 | 01-OCT-00:20 | 0.53 |
| November | 0.200271E+09 | 0.43 | 105.72 | 01-NOV-00:20 | 0.53 |
| December | 0.205373E+09 | 0.40 | 105.72 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.252456E+10 | 0.47 | |||
| Minimum of Months | 0.185566E+09 | 0.40 | 105.72 | 0.53 | |
| Maximum of Months | 0.228949E+09 | 0.52 | 105.72 | 0.53 |
Report: FanReportMonthly
For: 420_423 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.751038E+09 | 0.40 | 386.99 | 01-JAN-00:10 | 0.53 |
| February | 0.679424E+09 | 0.41 | 386.99 | 01-FEB-00:10 | 0.53 |
| March | 0.762543E+09 | 0.45 | 386.99 | 01-MAR-00:10 | 0.53 |
| April | 0.749654E+09 | 0.48 | 386.99 | 01-APR-00:10 | 0.53 |
| May | 0.791937E+09 | 0.51 | 386.99 | 01-MAY-00:10 | 0.53 |
| June | 0.786218E+09 | 0.51 | 386.99 | 01-JUN-00:20 | 0.53 |
| July | 0.830140E+09 | 0.52 | 386.99 | 01-JUL-00:10 | 0.53 |
| August | 0.823506E+09 | 0.51 | 386.99 | 01-AUG-00:10 | 0.53 |
| September | 0.780585E+09 | 0.51 | 386.99 | 01-SEP-00:10 | 0.53 |
| October | 0.774595E+09 | 0.48 | 386.99 | 01-OCT-00:10 | 0.53 |
| November | 0.733573E+09 | 0.44 | 386.99 | 01-NOV-00:10 | 0.53 |
| December | 0.752289E+09 | 0.41 | 386.99 | 01-DEC-00:20 | 0.53 |
| Annual Sum or Average | 0.921550E+10 | 0.47 | |||
| Minimum of Months | 0.679424E+09 | 0.40 | 386.99 | 0.53 | |
| Maximum of Months | 0.830140E+09 | 0.52 | 386.99 | 0.53 |
Report: FanReportMonthly
For: 424 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.213564E+09 | 0.43 | 107.98 | 01-JAN-00:10 | 0.53 |
| February | 0.192733E+09 | 0.43 | 107.98 | 01-FEB-00:10 | 0.53 |
| March | 0.210681E+09 | 0.42 | 107.98 | 01-MAR-00:10 | 0.53 |
| April | 0.206890E+09 | 0.46 | 107.98 | 01-APR-00:10 | 0.53 |
| May | 0.219119E+09 | 0.50 | 107.98 | 01-MAY-00:10 | 0.53 |
| June | 0.219073E+09 | 0.51 | 107.98 | 01-JUN-00:10 | 0.53 |
| July | 0.232766E+09 | 0.52 | 107.98 | 01-JUL-00:10 | 0.53 |
| August | 0.230499E+09 | 0.51 | 107.98 | 01-AUG-00:10 | 0.53 |
| September | 0.217127E+09 | 0.51 | 107.98 | 01-SEP-00:10 | 0.53 |
| October | 0.214103E+09 | 0.46 | 107.98 | 01-OCT-00:10 | 0.53 |
| November | 0.203420E+09 | 0.42 | 107.98 | 01-NOV-00:10 | 0.53 |
| December | 0.214742E+09 | 0.44 | 107.98 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.257472E+10 | 0.47 | |||
| Minimum of Months | 0.192733E+09 | 0.42 | 107.98 | 0.53 | |
| Maximum of Months | 0.232766E+09 | 0.52 | 107.98 | 0.53 |
Report: FanReportMonthly
For: CORRIDORFLR1 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.520285E+10 | 0.54 | 1942.52 | 01-JAN-00:10 | 0.54 |
| February | 0.469935E+10 | 0.54 | 1942.52 | 01-FEB-00:10 | 0.54 |
| March | 0.520285E+10 | 0.54 | 1942.52 | 01-MAR-00:10 | 0.54 |
| April | 0.503501E+10 | 0.53 | 1942.52 | 01-APR-00:10 | 0.53 |
| May | 0.520285E+10 | 0.53 | 1942.52 | 01-MAY-00:10 | 0.53 |
| June | 0.503501E+10 | 0.53 | 1942.52 | 01-JUN-00:10 | 0.53 |
| July | 0.520285E+10 | 0.53 | 1942.52 | 01-JUL-00:10 | 0.53 |
| August | 0.520285E+10 | 0.53 | 1942.52 | 01-AUG-00:10 | 0.53 |
| September | 0.503501E+10 | 0.53 | 1942.52 | 01-SEP-00:10 | 0.53 |
| October | 0.520285E+10 | 0.53 | 1942.52 | 01-OCT-00:10 | 0.53 |
| November | 0.503501E+10 | 0.54 | 1942.52 | 01-NOV-00:10 | 0.53 |
| December | 0.520285E+10 | 0.54 | 1942.52 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.612593E+11 | 0.53 | |||
| Minimum of Months | 0.469935E+10 | 0.53 | 1942.52 | 0.53 | |
| Maximum of Months | 0.520285E+10 | 0.54 | 1942.52 | 0.54 |
Report: FanReportMonthly
For: CORRIDORFLR2 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.508694E+09 | 0.54 | 189.92 | 01-JAN-00:10 | 0.54 |
| February | 0.459465E+09 | 0.54 | 189.92 | 01-FEB-00:10 | 0.54 |
| March | 0.508694E+09 | 0.54 | 189.92 | 01-MAR-00:10 | 0.54 |
| April | 0.492284E+09 | 0.53 | 189.92 | 01-APR-00:10 | 0.53 |
| May | 0.508694E+09 | 0.53 | 189.92 | 01-MAY-00:10 | 0.53 |
| June | 0.492284E+09 | 0.53 | 189.92 | 01-JUN-00:10 | 0.53 |
| July | 0.508694E+09 | 0.53 | 189.92 | 01-JUL-00:10 | 0.53 |
| August | 0.508694E+09 | 0.53 | 189.92 | 01-AUG-00:10 | 0.53 |
| September | 0.492284E+09 | 0.53 | 189.92 | 01-SEP-00:10 | 0.53 |
| October | 0.508694E+09 | 0.53 | 189.92 | 01-OCT-00:10 | 0.53 |
| November | 0.492284E+09 | 0.54 | 189.92 | 01-NOV-00:10 | 0.53 |
| December | 0.508694E+09 | 0.54 | 189.92 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.598946E+10 | 0.53 | |||
| Minimum of Months | 0.459465E+09 | 0.53 | 189.92 | 0.53 | |
| Maximum of Months | 0.508694E+09 | 0.54 | 189.92 | 0.54 |
Report: FanReportMonthly
For: CORRIDORFLR3 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.369844E+09 | 0.54 | 138.08 | 01-JAN-00:10 | 0.54 |
| February | 0.334052E+09 | 0.54 | 138.08 | 01-FEB-00:10 | 0.54 |
| March | 0.369844E+09 | 0.54 | 138.08 | 01-MAR-00:10 | 0.54 |
| April | 0.357913E+09 | 0.53 | 138.08 | 01-APR-00:10 | 0.53 |
| May | 0.369844E+09 | 0.53 | 138.08 | 01-MAY-00:10 | 0.53 |
| June | 0.357913E+09 | 0.53 | 138.08 | 01-JUN-00:10 | 0.53 |
| July | 0.369844E+09 | 0.53 | 138.08 | 01-JUL-00:10 | 0.53 |
| August | 0.369844E+09 | 0.53 | 138.08 | 01-AUG-00:20 | 0.53 |
| September | 0.357913E+09 | 0.53 | 138.08 | 01-SEP-00:10 | 0.53 |
| October | 0.369844E+09 | 0.53 | 138.08 | 01-OCT-00:10 | 0.53 |
| November | 0.357913E+09 | 0.54 | 138.08 | 01-NOV-00:10 | 0.53 |
| December | 0.369844E+09 | 0.54 | 138.08 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.435461E+10 | 0.53 | |||
| Minimum of Months | 0.334052E+09 | 0.53 | 138.08 | 0.53 | |
| Maximum of Months | 0.369844E+09 | 0.54 | 138.08 | 0.54 |
Report: FanReportMonthly
For: CORRIDORFLR4 PTAC_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.616541E+09 | 0.54 | 230.19 | 01-JAN-00:20 | 0.54 |
| February | 0.556876E+09 | 0.54 | 230.19 | 01-FEB-00:10 | 0.54 |
| March | 0.616541E+09 | 0.54 | 230.19 | 01-MAR-00:10 | 0.54 |
| April | 0.596652E+09 | 0.53 | 230.19 | 01-APR-00:10 | 0.53 |
| May | 0.616541E+09 | 0.53 | 230.19 | 01-MAY-00:10 | 0.53 |
| June | 0.596652E+09 | 0.53 | 230.19 | 01-JUN-00:10 | 0.53 |
| July | 0.616541E+09 | 0.53 | 230.19 | 01-JUL-00:10 | 0.53 |
| August | 0.616541E+09 | 0.53 | 230.19 | 01-AUG-00:10 | 0.53 |
| September | 0.596652E+09 | 0.53 | 230.19 | 01-SEP-00:10 | 0.53 |
| October | 0.616541E+09 | 0.53 | 230.19 | 01-OCT-00:10 | 0.53 |
| November | 0.596652E+09 | 0.54 | 230.19 | 01-NOV-00:10 | 0.53 |
| December | 0.616541E+09 | 0.54 | 230.19 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.725927E+10 | 0.53 | |||
| Minimum of Months | 0.556876E+09 | 0.53 | 230.19 | 0.53 | |
| Maximum of Months | 0.616541E+09 | 0.54 | 230.19 | 0.54 |
Report: FanReportMonthly
For: SAC_FRONTOFFICE_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.667984E+09 | 0.54 | 249.40 | 01-JAN-00:10 | 0.54 |
| February | 0.603341E+09 | 0.54 | 249.40 | 01-FEB-00:10 | 0.54 |
| March | 0.667984E+09 | 0.54 | 249.40 | 01-MAR-00:10 | 0.54 |
| April | 0.646436E+09 | 0.53 | 249.40 | 01-APR-00:10 | 0.53 |
| May | 0.667984E+09 | 0.53 | 249.40 | 01-MAY-00:10 | 0.53 |
| June | 0.646436E+09 | 0.53 | 249.40 | 01-JUN-00:10 | 0.53 |
| July | 0.667984E+09 | 0.53 | 249.40 | 01-JUL-00:10 | 0.53 |
| August | 0.667984E+09 | 0.53 | 249.40 | 01-AUG-00:10 | 0.53 |
| September | 0.646436E+09 | 0.53 | 249.40 | 01-SEP-00:10 | 0.53 |
| October | 0.667984E+09 | 0.53 | 249.40 | 01-OCT-00:10 | 0.53 |
| November | 0.646436E+09 | 0.53 | 249.40 | 01-NOV-00:10 | 0.53 |
| December | 0.667984E+09 | 0.54 | 249.40 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.786498E+10 | 0.53 | |||
| Minimum of Months | 0.603341E+09 | 0.53 | 249.40 | 0.53 | |
| Maximum of Months | 0.667984E+09 | 0.54 | 249.40 | 0.54 |
Report: FanReportMonthly
For: SAC_FRONTLOUNGE_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.133167E+10 | 0.54 | 497.19 | 01-JAN-00:10 | 0.54 |
| February | 0.120280E+10 | 0.54 | 497.19 | 01-FEB-00:10 | 0.54 |
| March | 0.133167E+10 | 0.54 | 497.19 | 01-MAR-00:10 | 0.54 |
| April | 0.128872E+10 | 0.53 | 497.19 | 01-APR-00:10 | 0.53 |
| May | 0.133167E+10 | 0.53 | 497.19 | 01-MAY-00:10 | 0.53 |
| June | 0.128872E+10 | 0.53 | 497.19 | 01-JUN-00:10 | 0.53 |
| July | 0.133167E+10 | 0.53 | 497.19 | 01-JUL-00:10 | 0.53 |
| August | 0.133167E+10 | 0.53 | 497.19 | 01-AUG-00:10 | 0.53 |
| September | 0.128872E+10 | 0.53 | 497.19 | 01-SEP-00:10 | 0.53 |
| October | 0.133167E+10 | 0.53 | 497.19 | 01-OCT-00:10 | 0.53 |
| November | 0.128872E+10 | 0.54 | 497.19 | 01-NOV-00:10 | 0.54 |
| December | 0.133167E+10 | 0.54 | 497.19 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.156794E+11 | 0.53 | |||
| Minimum of Months | 0.120280E+10 | 0.53 | 497.19 | 0.53 | |
| Maximum of Months | 0.133167E+10 | 0.54 | 497.19 | 0.54 |
Report: FanReportMonthly
For: SAC_MEETINGROOM_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.357669E+09 | 0.49 | 240.77 | 01-JAN-08:62 | 0.54 |
| February | 0.334902E+09 | 0.51 | 240.77 | 01-FEB-08:62 | 0.53 |
| March | 0.316564E+09 | 0.39 | 240.77 | 01-MAR-08:62 | 0.54 |
| April | 0.263686E+09 | 0.25 | 240.77 | 01-APR-07:02 | 0.53 |
| May | 0.273130E+09 | 0.38 | 240.77 | 01-MAY-07:02 | 0.53 |
| June | 0.283955E+09 | 0.57 | 240.77 | 01-JUN-07:01 | 0.53 |
| July | 0.307098E+09 | 0.58 | 240.77 | 01-JUL-07:02 | 0.53 |
| August | 0.303019E+09 | 0.58 | 240.77 | 01-AUG-07:02 | 0.53 |
| September | 0.281274E+09 | 0.57 | 240.77 | 01-SEP-07:02 | 0.53 |
| October | 0.271994E+09 | 0.34 | 240.77 | 01-OCT-07:02 | 0.53 |
| November | 0.260396E+09 | 0.23 | 240.77 | 01-NOV-07:02 | 0.53 |
| December | 0.334766E+09 | 0.42 | 240.77 | 01-DEC-08:62 | 0.53 |
| Annual Sum or Average | 0.358845E+10 | 0.44 | |||
| Minimum of Months | 0.260396E+09 | 0.23 | 240.77 | 0.53 | |
| Maximum of Months | 0.357669E+09 | 0.58 | 240.77 | 0.54 |
Report: FanReportMonthly
For: SAC_EMPLOYEELOUNGE_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.114743E+10 | 0.54 | 428.40 | 01-JAN-00:10 | 0.54 |
| February | 0.103639E+10 | 0.54 | 428.40 | 01-FEB-00:10 | 0.54 |
| March | 0.114743E+10 | 0.54 | 428.40 | 01-MAR-00:10 | 0.54 |
| April | 0.111042E+10 | 0.53 | 428.40 | 01-APR-00:20 | 0.53 |
| May | 0.114743E+10 | 0.53 | 428.40 | 01-MAY-00:10 | 0.53 |
| June | 0.111042E+10 | 0.53 | 428.40 | 01-JUN-00:10 | 0.53 |
| July | 0.114743E+10 | 0.53 | 428.40 | 01-JUL-00:10 | 0.53 |
| August | 0.114743E+10 | 0.53 | 428.40 | 01-AUG-00:10 | 0.53 |
| September | 0.111042E+10 | 0.53 | 428.40 | 01-SEP-00:10 | 0.53 |
| October | 0.114743E+10 | 0.53 | 428.40 | 01-OCT-00:10 | 0.53 |
| November | 0.111042E+10 | 0.54 | 428.40 | 01-NOV-00:10 | 0.53 |
| December | 0.114743E+10 | 0.54 | 428.40 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.135101E+11 | 0.53 | |||
| Minimum of Months | 0.103639E+10 | 0.53 | 428.40 | 0.53 | |
| Maximum of Months | 0.114743E+10 | 0.54 | 428.40 | 0.54 |
Report: FanReportMonthly
For: SAC_EXERCISECENTER_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.232270E+09 | 0.54 | 86.72 | 01-JAN-00:10 | 0.54 |
| February | 0.209792E+09 | 0.54 | 86.72 | 01-FEB-00:10 | 0.54 |
| March | 0.232270E+09 | 0.54 | 86.72 | 01-MAR-00:10 | 0.54 |
| April | 0.224777E+09 | 0.53 | 86.72 | 01-APR-00:10 | 0.53 |
| May | 0.232270E+09 | 0.53 | 86.72 | 01-MAY-00:10 | 0.53 |
| June | 0.224777E+09 | 0.53 | 86.72 | 01-JUN-00:10 | 0.53 |
| July | 0.232270E+09 | 0.53 | 86.72 | 01-JUL-00:10 | 0.53 |
| August | 0.232270E+09 | 0.53 | 86.72 | 01-AUG-00:10 | 0.53 |
| September | 0.224777E+09 | 0.53 | 86.72 | 01-SEP-00:10 | 0.53 |
| October | 0.232270E+09 | 0.53 | 86.72 | 01-OCT-00:10 | 0.53 |
| November | 0.224777E+09 | 0.53 | 86.72 | 01-NOV-00:10 | 0.54 |
| December | 0.232270E+09 | 0.54 | 86.72 | 01-DEC-00:10 | 0.54 |
| Annual Sum or Average | 0.273479E+10 | 0.53 | |||
| Minimum of Months | 0.209792E+09 | 0.53 | 86.72 | 0.53 | |
| Maximum of Months | 0.232270E+09 | 0.54 | 86.72 | 0.54 |
Report: FanReportMonthly
For: SAC_RESTROOM_PTAC_SUPPLY FAN
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.113496E+09 | 0.53 | 42.37 | 01-JAN-00:10 | 0.53 |
| February | 0.102513E+09 | 0.53 | 42.37 | 01-FEB-00:10 | 0.53 |
| March | 0.113496E+09 | 0.53 | 42.37 | 01-MAR-00:10 | 0.53 |
| April | 0.109835E+09 | 0.53 | 42.37 | 01-APR-00:10 | 0.53 |
| May | 0.113496E+09 | 0.53 | 42.37 | 01-MAY-00:10 | 0.53 |
| June | 0.109835E+09 | 0.53 | 42.37 | 01-JUN-00:10 | 0.53 |
| July | 0.113496E+09 | 0.53 | 42.37 | 01-JUL-00:10 | 0.53 |
| August | 0.113496E+09 | 0.53 | 42.37 | 01-AUG-00:10 | 0.53 |
| September | 0.109835E+09 | 0.53 | 42.37 | 01-SEP-00:10 | 0.53 |
| October | 0.113496E+09 | 0.53 | 42.37 | 01-OCT-00:10 | 0.53 |
| November | 0.109835E+09 | 0.53 | 42.37 | 01-NOV-00:10 | 0.53 |
| December | 0.113496E+09 | 0.53 | 42.37 | 01-DEC-00:10 | 0.53 |
| Annual Sum or Average | 0.133633E+10 | 0.53 | |||
| Minimum of Months | 0.102513E+09 | 0.53 | 42.37 | 0.53 | |
| Maximum of Months | 0.113496E+09 | 0.53 | 42.37 | 0.53 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 0.409586E+09 | 0.368628E+09 | 522.61 | 31-JAN-16:11 | 470.35 | 470.35 | 51.34 | 0.93 |
| February | 0.393807E+09 | 0.354426E+09 | 556.58 | 06-FEB-19:01 | 500.92 | 500.92 | 55.50 | 1.10 |
| March | 0.189780E+09 | 0.170802E+09 | 379.18 | 07-MAR-09:01 | 341.26 | 341.26 | 49.34 | 0.53 |
| April | 48069059.40 | 43262153.46 | 186.10 | 17-APR-06:03 | 167.49 | 167.49 | 42.39 | 0.21 |
| May | 4413059.44 | 3971753.49 | 83.35 | 11-MAY-15:15 | 75.02 | 75.02 | 23.32 | 0.09 |
| June | 322991.51 | 290692.36 | 78.40 | 14-JUN-08:04 | 70.56 | 70.56 | 22.25 | 0.08 |
| July | 3531.10 | 3177.99 | 15.32 | 06-JUL-08:56 | 13.78 | 13.78 | 22.47 | 0.02 |
| August | 6288.80 | 5659.92 | 32.36 | 31-AUG-08:04 | 29.13 | 29.13 | 22.60 | 0.03 |
| September | 658606.92 | 592746.23 | 61.50 | 28-SEP-15:15 | 55.35 | 55.35 | 23.15 | 0.07 |
| October | 23160380.46 | 20844342.41 | 133.96 | 17-OCT-06:04 | 120.57 | 120.57 | 39.71 | 0.15 |
| November | 74652896.61 | 67187606.95 | 347.42 | 30-NOV-16:12 | 312.68 | 312.68 | 41.11 | 0.46 |
| December | 0.368091E+09 | 0.331282E+09 | 527.41 | 09-DEC-16:11 | 474.67 | 474.67 | 51.35 | 0.95 |
| Annual Sum or Average | 0.151255E+10 | 0.136130E+10 | ||||||
| Minimum of Months | 3531.10 | 3177.99 | 15.32 | 13.78 | 13.78 | 22.25 | 0.02 | |
| Maximum of Months | 0.409586E+09 | 0.368628E+09 | 556.58 | 500.92 | 500.92 | 55.50 | 1.10 |
Report: PumpReportMonthly
For: SWHSYSSHOWER PUMP
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 21729602.91 | 18470162.47 | 8.11 | 01-JAN-00:10 | 6.90 | 6.90 | 52.82 | 0.18 |
| February | 19626738.11 | 16682727.40 | 8.11 | 01-FEB-00:10 | 6.90 | 6.90 | 52.96 | 0.18 |
| March | 21729602.91 | 18470162.47 | 8.11 | 01-MAR-00:10 | 6.90 | 6.90 | 52.96 | 0.18 |
| April | 21028647.98 | 17874350.78 | 8.11 | 01-APR-00:10 | 6.90 | 6.90 | 54.84 | 0.18 |
| May | 21729602.91 | 18470162.47 | 8.11 | 01-MAY-00:10 | 6.90 | 6.90 | 55.10 | 0.18 |
| June | 21028647.98 | 17874350.78 | 8.11 | 01-JUN-00:10 | 6.90 | 6.90 | 55.40 | 0.18 |
| July | 21729602.91 | 18470162.47 | 8.11 | 01-JUL-00:10 | 6.90 | 6.90 | 55.66 | 0.18 |
| August | 21729602.91 | 18470162.47 | 8.11 | 01-AUG-00:10 | 6.90 | 6.90 | 55.82 | 0.18 |
| September | 21028647.98 | 17874350.78 | 8.11 | 01-SEP-00:10 | 6.90 | 6.90 | 55.82 | 0.18 |
| October | 21729602.91 | 18470162.47 | 8.11 | 01-OCT-00:10 | 6.90 | 6.90 | 55.67 | 0.18 |
| November | 21028647.98 | 17874350.78 | 8.11 | 01-NOV-00:10 | 6.90 | 6.90 | 55.40 | 0.18 |
| December | 21729602.91 | 18470162.47 | 8.11 | 01-DEC-00:10 | 6.90 | 6.90 | 53.51 | 0.18 |
| Annual Sum or Average | 0.255849E+09 | 0.217471E+09 | ||||||
| Minimum of Months | 19626738.11 | 16682727.40 | 8.11 | 6.90 | 6.90 | 52.82 | 0.18 | |
| Maximum of Months | 21729602.91 | 18470162.47 | 8.11 | 6.90 | 6.90 | 55.82 | 0.18 |
Report: PumpReportMonthly
For: SWHSYSLAUNDRY PUMP
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 0.49 | 0.15 | 0.00 | 01-JAN-08:62 | 0.00 | 0.00 | 8.20 | 0.13 |
| February | 0.45 | 0.13 | 0.00 | 01-FEB-08:62 | 0.00 | 0.00 | 6.73 | 0.13 |
| March | 0.49 | 0.15 | 0.00 | 01-MAR-08:62 | 0.00 | 0.00 | 6.72 | 0.13 |
| April | 0.48 | 0.14 | 0.00 | 01-APR-07:02 | 0.00 | 0.00 | 8.19 | 0.13 |
| May | 0.49 | 0.15 | 0.00 | 01-MAY-07:02 | 0.00 | 0.00 | 10.72 | 0.13 |
| June | 0.48 | 0.14 | 0.00 | 01-JUN-07:01 | 0.00 | 0.00 | 13.75 | 0.13 |
| July | 0.49 | 0.15 | 0.00 | 01-JUL-07:02 | 0.00 | 0.00 | 16.34 | 0.13 |
| August | 0.49 | 0.15 | 0.00 | 01-AUG-07:02 | 0.00 | 0.00 | 17.91 | 0.13 |
| September | 0.48 | 0.14 | 0.00 | 01-SEP-07:02 | 0.00 | 0.00 | 17.93 | 0.13 |
| October | 0.49 | 0.15 | 0.00 | 01-OCT-07:02 | 0.00 | 0.00 | 16.47 | 0.13 |
| November | 0.48 | 0.14 | 0.00 | 01-NOV-07:02 | 0.00 | 0.00 | 13.83 | 0.13 |
| December | 0.49 | 0.15 | 0.00 | 01-DEC-08:62 | 0.00 | 0.00 | 10.88 | 0.13 |
| Annual Sum or Average | 5.81 | 1.74 | ||||||
| Minimum of Months | 0.45 | 0.13 | 0.00 | 0.00 | 0.00 | 6.72 | 0.13 | |
| Maximum of Months | 0.49 | 0.15 | 0.00 | 0.00 | 0.00 | 17.93 | 0.13 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 40.04 | 82.00 | 29748.29 | 121513.29 | 28-JAN-16:12 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 42.96 | 82.00 | 32279.56 | 127341.65 | 12-FEB-16:12 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 41.57 | 82.00 | 14436.33 | 84803.59 | 04-MAR-16:12 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 23.64 | 82.00 | 4428.94 | 38063.82 | 16-APR-06:03 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 22.33 | 82.00 | 419.93 | 21949.32 | 11-MAY-15:15 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 22.34 | 22.34 | 32.00 | 20959.62 | 14-JUN-08:04 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 22.45 | 22.45 | 0.34 | 3921.84 | 06-JUL-08:56 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 22.51 | 22.51 | 0.60 | 8353.89 | 31-AUG-08:04 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 22.65 | 22.65 | 64.41 | 16014.60 | 28-SEP-15:15 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 23.71 | 23.71 | 2084.08 | 31628.88 | 16-OCT-18:05 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 23.66 | 82.00 | 6547.60 | 79441.35 | 30-NOV-16:12 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 30.03 | 82.00 | 27001.38 | 122097.89 | 09-DEC-16:11 |
| Annual Sum or Average | 0.00 | 9645.03 | ||||||
| Minimum of Months | 0.00 | 0.00 | 22.33 | 22.34 | 0.34 | 3921.84 | ||
| Maximum of Months | 0.00 | 0.00 | 42.96 | 82.00 | 32279.56 | 127341.65 |
Report: CondLoopDemandReportMonthly
For: SWHSYSSHOWER
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 52.82 | 60.05 | 8457.56 | 20780.79 | 31-JAN-07:14 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 52.96 | 60.05 | 8585.74 | 20854.11 | 15-FEB-07:20 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 52.96 | 60.05 | 8483.69 | 20787.68 | 01-MAR-07:16 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 54.84 | 60.05 | 8136.89 | 20206.27 | 01-APR-07:27 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 55.10 | 60.05 | 7685.46 | 19214.39 | 01-MAY-06:53 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 55.40 | 60.05 | 7223.96 | 18023.06 | 01-JUN-06:14 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 55.66 | 60.05 | 6864.00 | 17019.00 | 01-JUL-07:51 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 55.82 | 60.05 | 6749.21 | 16414.30 | 01-AUG-06:40 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 55.82 | 60.05 | 6856.69 | 16968.45 | 30-SEP-07:16 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 55.67 | 60.05 | 7195.89 | 17991.85 | 31-OCT-06:20 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 55.40 | 60.05 | 7655.63 | 19145.71 | 30-NOV-07:54 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 53.51 | 60.05 | 8113.68 | 20183.22 | 31-DEC-08:50 |
| Annual Sum or Average | 0.00 | 7662.00 | ||||||
| Minimum of Months | 0.00 | 0.00 | 52.82 | 60.05 | 6749.21 | 16414.30 | ||
| Maximum of Months | 0.00 | 0.00 | 55.82 | 60.05 | 8585.74 | 20854.11 |
Report: CondLoopDemandReportMonthly
For: SWHSYSLAUNDRY
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:10 | 8.20 | 8.20 | 9516.95 | 28892.77 | 31-JAN-09:02 |
| February | 0.00 | 0.00 | 01-FEB-00:10 | 6.75 | 6.75 | 9655.07 | 28996.62 | 15-FEB-15:02 |
| March | 0.00 | 0.00 | 01-MAR-00:10 | 6.71 | 6.71 | 9523.32 | 28907.70 | 01-MAR-08:62 |
| April | 0.00 | 0.00 | 01-APR-00:10 | 8.15 | 8.15 | 9146.65 | 28097.15 | 01-APR-07:02 |
| May | 0.00 | 0.00 | 01-MAY-00:10 | 10.66 | 10.66 | 8624.31 | 26704.66 | 01-MAY-07:02 |
| June | 0.00 | 0.00 | 01-JUN-00:10 | 13.71 | 13.71 | 8097.90 | 25040.66 | 01-JUN-07:01 |
| July | 0.00 | 0.00 | 01-JUL-00:10 | 16.30 | 16.30 | 7710.04 | 23621.70 | 01-JUL-07:02 |
| August | 0.00 | 0.00 | 01-AUG-00:10 | 17.90 | 17.90 | 7561.90 | 22765.48 | 01-AUG-07:02 |
| September | 0.00 | 0.00 | 01-SEP-00:10 | 17.94 | 17.94 | 7697.30 | 23532.49 | 30-SEP-07:26 |
| October | 0.00 | 0.00 | 01-OCT-00:10 | 16.51 | 16.51 | 8077.47 | 24964.99 | 31-OCT-14:13 |
| November | 0.00 | 0.00 | 01-NOV-00:10 | 13.89 | 13.89 | 8600.27 | 26585.93 | 30-NOV-15:03 |
| December | 0.00 | 0.00 | 01-DEC-00:10 | 10.93 | 10.93 | 9125.48 | 28048.61 | 31-DEC-13:10 |
| Annual Sum or Average | 0.00 | 8605.28 | ||||||
| Minimum of Months | 0.00 | 0.00 | 6.71 | 6.71 | 7561.90 | 22765.48 | ||
| Maximum of Months | 0.00 | 0.00 | 17.94 | 17.94 | 9655.07 | 28996.62 |
Report: ZoneTemperatureOscillationReportMonthly
For: REARSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDORFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: REARSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONTLOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: RESTROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MEETINGROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MECHANICALROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM101
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM102
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM103
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM104
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM105
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: EMPLOYEELOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LAUNDRYROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ELEVATORCOREFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: EXERCISECENTERFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONTOFFICEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONTSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONTSTORAGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: REARSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDORFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: REARSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM201
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM202_205
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM206_208
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM209_212
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM213
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM214
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM215_218
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ELEVATORCOREFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM219
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM220_223
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM224
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONTSTORAGEFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONTSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: REARSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDORFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: REARSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM301
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM302_305
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM306_308
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM309_312
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM313
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM314
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM315_318
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ELEVATORCOREFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM319
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM320_323
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM324
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONTSTORAGEFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONTSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: REARSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORRIDORFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: REARSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM401
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM402_405
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM406_408
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM409_412
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM413
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM414
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM415_418
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ELEVATORCOREFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM419
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM420_423
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GUESTROOM424
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONTSTORAGEFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: FRONTSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: REARSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDORFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.185896E+10 | 0.00 | 0.00 | 3397526.40 | 0.00 | 0.294813E+09 | 0.182487E+10 | 0.00 | 0.33 |
| February | 0.196398E+10 | 0.00 | 0.00 | 2134874.64 | 0.00 | 0.373060E+09 | 0.133459E+10 | 0.00 | 0.33 |
| March | 0.815988E+09 | 7583990.67 | 0.00 | 12431409.96 | 0.00 | 0.199063E+09 | 0.207158E+10 | 0.00 | 0.33 |
| April | 0.232021E+09 | 0.00 | 0.00 | 23646633.35 | 0.00 | 0.109382E+09 | 0.203836E+10 | 0.00 | 0.33 |
| May | 85801764.63 | 13573657.75 | 0.00 | 49911601.98 | 2732.90 | 18510111.37 | 0.130995E+10 | 0.00 | 0.33 |
| June | 40615494.56 | 0.400748E+09 | 0.00 | 40342599.18 | 27301.67 | 46839.49 | 0.523961E+09 | 0.00 | 0.33 |
| July | 12072347.61 | 0.105006E+10 | 0.00 | 12113683.50 | 0.00 | 0.00 | 93604468.60 | 0.00 | 0.33 |
| August | 23640739.75 | 0.593790E+09 | 0.00 | 31024995.69 | 0.00 | 0.00 | 0.232590E+09 | 0.00 | 0.33 |
| September | 57501540.82 | 0.213714E+09 | 0.00 | 50177340.37 | 0.00 | 4810347.98 | 0.741256E+09 | 0.00 | 0.33 |
| October | 0.133022E+09 | 2735.98 | 0.00 | 41069725.82 | 0.00 | 60792733.37 | 0.186000E+10 | 0.00 | 0.33 |
| November | 0.188943E+09 | 0.00 | 0.00 | 22099532.69 | 0.00 | 0.128337E+09 | 0.225019E+10 | 0.00 | 0.33 |
| December | 0.158965E+10 | 0.00 | 0.00 | 4922940.08 | 0.00 | 0.282130E+09 | 0.192581E+10 | 0.00 | 0.33 |
| Annual Sum or Average | 0.700218E+10 | 0.227947E+10 | 0.00 | 0.293273E+09 | 30034.57 | 0.147095E+10 | 0.162068E+11 | 0.00 | 0.33 |
| Minimum of Months | 12072347.61 | 0.00 | 0.00 | 2134874.64 | 0.00 | 0.00 | 93604468.60 | 0.00 | 0.33 |
| Maximum of Months | 0.196398E+10 | 0.105006E+10 | 0.00 | 50177340.37 | 27301.67 | 0.373060E+09 | 0.225019E+10 | 0.00 | 0.33 |
Report: MechanicalVentilationLoadsMonthly
For: FRONTLOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.168369E+11 | 0.00 | 0.00 | 1489.80 | 0.00 | 0.320462E+10 | 3633678.54 | 0.00 | 1.56 |
| February | 0.151602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350376E+10 | 0.00 | 0.00 | 1.56 |
| March | 0.140546E+11 | 4682267.67 | 0.00 | 2840316.38 | 0.00 | 0.129450E+10 | 0.399120E+09 | 0.00 | 1.56 |
| April | 0.113869E+11 | 0.00 | 0.00 | 2431580.37 | 0.00 | 0.00 | 0.650094E+09 | 0.00 | 1.58 |
| May | 0.544838E+10 | 18996186.42 | 0.00 | 21014169.07 | 0.00 | 0.00 | 0.312699E+10 | 0.00 | 1.58 |
| June | 0.130839E+10 | 0.896484E+09 | 0.00 | 31443576.98 | 0.00 | 0.00 | 0.310538E+10 | 0.00 | 1.59 |
| July | 0.154773E+09 | 0.276058E+10 | 0.00 | 20919608.90 | 0.00 | 0.00 | 0.137552E+10 | 0.00 | 1.59 |
| August | 0.299715E+09 | 0.144254E+10 | 0.00 | 34973960.61 | 0.00 | 0.00 | 0.245250E+10 | 0.00 | 1.59 |
| September | 0.200083E+10 | 0.385289E+09 | 0.00 | 32953830.71 | 0.00 | 0.00 | 0.386210E+10 | 0.00 | 1.58 |
| October | 0.897229E+10 | 0.00 | 0.00 | 11840826.02 | 0.00 | 0.00 | 0.220360E+10 | 0.00 | 1.57 |
| November | 0.123061E+11 | 0.00 | 0.00 | 3382608.60 | 0.00 | 0.00 | 0.644731E+09 | 0.00 | 1.57 |
| December | 0.170018E+11 | 0.00 | 0.00 | 254474.99 | 0.00 | 0.210111E+10 | 56702916.71 | 0.00 | 1.57 |
| Annual Sum or Average | 0.104931E+12 | 0.550857E+10 | 0.00 | 0.162056E+09 | 0.00 | 0.101040E+11 | 0.178804E+11 | 0.00 | 1.58 |
| Minimum of Months | 0.154773E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.56 |
| Maximum of Months | 0.170018E+11 | 0.276058E+10 | 0.00 | 34973960.61 | 0.00 | 0.350376E+10 | 0.386210E+10 | 0.00 | 1.59 |
Report: MechanicalVentilationLoadsMonthly
For: RESTROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: MEETINGROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.405655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172336E+10 | 0.00 | 0.00 | 0.94 |
| February | 0.365231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192367E+10 | 0.00 | 0.00 | 0.98 |
| March | 0.310237E+10 | 2094777.53 | 0.00 | 304751.36 | 69061.93 | 0.847858E+09 | 47028614.61 | 0.00 | 0.83 |
| April | 0.225389E+10 | 0.00 | 0.00 | 139392.64 | 0.00 | 60107140.52 | 71024360.41 | 0.00 | 0.72 |
| May | 0.110846E+10 | 9834772.71 | 0.00 | 3724577.16 | 156406.20 | 43622.10 | 0.516426E+09 | 0.00 | 0.73 |
| June | 0.264435E+09 | 0.361852E+09 | 0.00 | 6413248.46 | 4533052.96 | 0.00 | 0.507138E+09 | 0.00 | 0.78 |
| July | 12033679.61 | 0.949956E+09 | 0.00 | 3447584.18 | 9163144.87 | 0.00 | 0.117209E+09 | 0.00 | 0.81 |
| August | 59270848.19 | 0.558426E+09 | 0.00 | 6671249.54 | 5208897.43 | 0.00 | 0.281453E+09 | 0.00 | 0.80 |
| September | 0.398770E+09 | 0.134110E+09 | 0.00 | 6915647.74 | 1842495.16 | 0.00 | 0.636535E+09 | 0.00 | 0.77 |
| October | 0.193269E+10 | 21246.58 | 0.00 | 1704723.95 | 0.00 | 2961460.59 | 0.299913E+09 | 0.00 | 0.72 |
| November | 0.256370E+10 | 0.00 | 0.00 | 314797.35 | 0.00 | 13386814.94 | 67236127.66 | 0.00 | 0.71 |
| December | 0.395878E+10 | 0.00 | 0.00 | 348.51 | 0.00 | 0.131039E+10 | 1133363.33 | 0.00 | 0.88 |
| Annual Sum or Average | 0.233633E+11 | 0.201630E+10 | 0.00 | 29636320.90 | 20973058.55 | 0.588178E+10 | 0.254510E+10 | 0.00 | 0.80 |
| Minimum of Months | 12033679.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.71 |
| Maximum of Months | 0.405655E+10 | 0.949956E+09 | 0.00 | 6915647.74 | 9163144.87 | 0.192367E+10 | 0.636535E+09 | 0.00 | 0.98 |
Report: MechanicalVentilationLoadsMonthly
For: MECHANICALROOMFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM101
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 36205762.07 | 0.00 | 0.00 | 0.00 | 3090.98 | 0.00 | 0.00 | 0.00 | 0.02 |
| February | 33348577.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| March | 24959913.44 | 0.00 | 0.00 | 0.00 | 286385.89 | 0.00 | 0.00 | 0.00 | 0.02 |
| April | 17607086.54 | 0.00 | 0.00 | 0.00 | 60841.04 | 0.00 | 0.00 | 0.00 | 0.02 |
| May | 12351691.53 | 0.00 | 0.00 | 0.00 | 1345240.25 | 0.00 | 0.00 | 0.00 | 0.02 |
| June | 8817785.11 | 0.00 | 0.00 | 0.00 | 3688270.75 | 0.00 | 0.00 | 0.00 | 0.02 |
| July | 4406177.10 | 0.00 | 0.00 | 0.00 | 4257211.97 | 0.00 | 0.00 | 0.00 | 0.02 |
| August | 7471368.68 | 0.00 | 0.00 | 0.00 | 3790646.09 | 0.00 | 0.00 | 0.00 | 0.02 |
| September | 10150333.76 | 0.00 | 0.00 | 0.00 | 1309866.70 | 0.00 | 0.00 | 0.00 | 0.02 |
| October | 19436815.89 | 0.00 | 0.00 | 0.00 | 16048.90 | 0.00 | 0.00 | 0.00 | 0.02 |
| November | 23231534.46 | 0.00 | 0.00 | 0.00 | 304375.16 | 0.00 | 0.00 | 0.00 | 0.02 |
| December | 36165431.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Annual Sum or Average | 0.234152E+09 | 0.00 | 0.00 | 0.00 | 15061977.73 | 0.00 | 0.00 | 0.00 | 0.02 |
| Minimum of Months | 4406177.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 36205762.07 | 0.00 | 0.00 | 0.00 | 4257211.97 | 0.00 | 0.00 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM102
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 34948666.36 | 0.00 | 0.00 | 0.00 | 26601.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| February | 32220066.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| March | 23803506.70 | 0.00 | 0.00 | 0.00 | 367878.48 | 0.00 | 0.00 | 0.00 | 0.02 |
| April | 16461923.82 | 0.00 | 0.00 | 0.00 | 94058.04 | 0.00 | 0.00 | 0.00 | 0.02 |
| May | 11320308.22 | 0.00 | 0.00 | 0.00 | 1466677.56 | 0.00 | 0.00 | 0.00 | 0.02 |
| June | 8137958.94 | 0.00 | 0.00 | 0.00 | 4084329.20 | 0.00 | 0.00 | 0.00 | 0.02 |
| July | 3851385.45 | 0.00 | 0.00 | 0.00 | 4743238.45 | 0.00 | 0.00 | 0.00 | 0.02 |
| August | 6778580.09 | 0.00 | 0.00 | 0.00 | 4203463.32 | 0.00 | 0.00 | 0.00 | 0.02 |
| September | 9285571.99 | 0.00 | 0.00 | 0.00 | 1558071.31 | 0.00 | 0.00 | 0.00 | 0.02 |
| October | 18279947.94 | 0.00 | 0.00 | 0.00 | 56221.18 | 0.00 | 0.00 | 0.00 | 0.02 |
| November | 22141897.36 | 0.00 | 0.00 | 0.00 | 413669.63 | 0.00 | 0.00 | 0.00 | 0.02 |
| December | 34864681.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Annual Sum or Average | 0.222094E+09 | 0.00 | 0.00 | 0.00 | 17014208.15 | 0.00 | 0.00 | 0.00 | 0.02 |
| Minimum of Months | 3851385.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 34948666.36 | 0.00 | 0.00 | 0.00 | 4743238.45 | 0.00 | 0.00 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM103
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 21437791.07 | 0.00 | 0.00 | 36606.60 | 0.00 | 0.106195E+10 | 24090051.44 | 0.00 | 0.33 |
| February | 13322258.08 | 0.00 | 0.00 | 25959.06 | 0.00 | 0.100829E+10 | 4557646.12 | 0.00 | 0.33 |
| March | 40505009.45 | 17954.37 | 0.00 | 624435.56 | 0.00 | 0.717536E+09 | 0.141398E+09 | 0.00 | 0.32 |
| April | 54702953.28 | 0.00 | 0.00 | 1004447.44 | 0.00 | 0.263957E+09 | 0.411800E+09 | 0.00 | 0.33 |
| May | 93079790.35 | 536609.30 | 0.00 | 4199214.01 | 26232.05 | 2118858.91 | 0.385791E+09 | 0.00 | 0.33 |
| June | 66151867.28 | 63825395.13 | 0.00 | 7140239.37 | 4945313.43 | 115143.08 | 0.134524E+09 | 0.00 | 0.34 |
| July | 25188345.84 | 0.203882E+09 | 0.00 | 4673482.76 | 13636438.26 | 0.00 | 22877774.49 | 0.00 | 0.35 |
| August | 43981285.31 | 0.112207E+09 | 0.00 | 7468582.66 | 5732281.70 | 0.00 | 54247906.88 | 0.00 | 0.34 |
| September | 71247738.04 | 28531888.69 | 0.00 | 8126795.26 | 3218707.79 | 312389.86 | 0.179225E+09 | 0.00 | 0.34 |
| October | 68607222.86 | 0.00 | 0.00 | 4052613.26 | 0.00 | 3648565.63 | 0.522988E+09 | 0.00 | 0.33 |
| November | 53725412.65 | 0.00 | 0.00 | 1424350.37 | 0.00 | 94951436.93 | 0.612357E+09 | 0.00 | 0.33 |
| December | 36273212.34 | 0.00 | 0.00 | 85383.07 | 0.00 | 0.936793E+09 | 86880705.74 | 0.00 | 0.33 |
| Annual Sum or Average | 0.588223E+09 | 0.409000E+09 | 0.00 | 38862109.40 | 27558973.22 | 0.408967E+10 | 0.258074E+10 | 0.00 | 0.33 |
| Minimum of Months | 13322258.08 | 0.00 | 0.00 | 25959.06 | 0.00 | 0.00 | 4557646.12 | 0.00 | 0.32 |
| Maximum of Months | 93079790.35 | 0.203882E+09 | 0.00 | 8126795.26 | 13636438.26 | 0.106195E+10 | 0.612357E+09 | 0.00 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM104
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 61167075.75 | 0.00 | 0.00 | 490149.87 | 0.00 | 0.656109E+09 | 0.378100E+09 | 0.00 | 0.32 |
| February | 53858672.36 | 0.00 | 0.00 | 254849.41 | 0.00 | 0.715977E+09 | 0.240686E+09 | 0.00 | 0.32 |
| March | 53499726.59 | 331219.12 | 0.00 | 2058901.87 | 10385.96 | 0.228190E+09 | 0.591521E+09 | 0.00 | 0.32 |
| April | 43932343.32 | 0.00 | 0.00 | 3125724.36 | 0.00 | 37276090.68 | 0.608403E+09 | 0.00 | 0.33 |
| May | 61446785.20 | 1658826.78 | 8821.96 | 6476074.29 | 66089.05 | 982698.77 | 0.378080E+09 | 10.75 | 0.33 |
| June | 51573462.51 | 74411652.79 | 0.00 | 7364513.15 | 5367534.57 | 142262.39 | 0.132502E+09 | 0.00 | 0.34 |
| July | 16937852.07 | 0.219294E+09 | 643.54 | 3659837.86 | 15048587.07 | 11833.24 | 22967622.97 | 60.36 | 0.35 |
| August | 29608122.48 | 0.125391E+09 | 0.00 | 6878977.30 | 6879746.30 | 33863.38 | 53169832.55 | 0.00 | 0.35 |
| September | 45703995.85 | 35855425.68 | 0.00 | 9944607.00 | 4267355.00 | 188617.54 | 0.171788E+09 | 0.00 | 0.34 |
| October | 39421436.79 | 1138.69 | 0.00 | 7156784.59 | 0.00 | 1086921.47 | 0.507251E+09 | 0.00 | 0.33 |
| November | 42931013.13 | 0.00 | 0.00 | 3645794.29 | 0.00 | 3689356.60 | 0.677191E+09 | 0.00 | 0.33 |
| December | 61029773.74 | 0.00 | 0.00 | 772087.65 | 0.00 | 0.490464E+09 | 0.496151E+09 | 0.00 | 0.32 |
| Annual Sum or Average | 0.561110E+09 | 0.456943E+09 | 9465.51 | 51828301.63 | 31639697.96 | 0.213415E+10 | 0.425781E+10 | 71.11 | 0.33 |
| Minimum of Months | 16937852.07 | 0.00 | 0.00 | 254849.41 | 0.00 | 11833.24 | 22967622.97 | 0.00 | 0.32 |
| Maximum of Months | 61446785.20 | 0.219294E+09 | 8821.96 | 9944607.00 | 15048587.07 | 0.715977E+09 | 0.677191E+09 | 60.36 | 0.35 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM105
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 45338967.24 | 0.00 | 0.00 | 5370350.25 | 0.00 | 4493569.59 | 0.102954E+10 | 0.00 | 0.33 |
| February | 44522432.39 | 0.00 | 0.00 | 4434634.86 | 0.00 | 4195952.02 | 0.946527E+09 | 0.00 | 0.33 |
| March | 12024014.82 | 1399685.29 | 0.00 | 7307591.32 | 45625.83 | 3102903.94 | 0.817363E+09 | 0.00 | 0.33 |
| April | 12691897.36 | 0.00 | 0.00 | 8225519.95 | 0.00 | 1896647.46 | 0.619035E+09 | 0.00 | 0.34 |
| May | 40555521.74 | 4011282.24 | 0.00 | 11073416.21 | 111101.32 | 765762.61 | 0.354217E+09 | 0.00 | 0.34 |
| June | 32841669.28 | 97885979.81 | 18949.17 | 8729058.89 | 6256090.97 | 129343.84 | 0.132516E+09 | 415.40 | 0.35 |
| July | 10051592.28 | 0.260418E+09 | 9939.15 | 3054858.96 | 16384943.67 | 7998.66 | 20891998.32 | 284.06 | 0.36 |
| August | 20156582.54 | 0.150400E+09 | 13142.10 | 6570213.82 | 7737254.31 | 8634.71 | 48124708.59 | 623.48 | 0.35 |
| September | 28974634.14 | 47170000.83 | 0.00 | 11151258.92 | 4993077.32 | 80684.71 | 0.165439E+09 | 0.00 | 0.35 |
| October | 16185877.67 | 20771.99 | 0.00 | 11547698.45 | 0.00 | 1225211.80 | 0.496469E+09 | 0.00 | 0.34 |
| November | 8970194.49 | 0.00 | 0.00 | 8353756.87 | 0.00 | 2484782.69 | 0.677231E+09 | 0.00 | 0.34 |
| December | 44233297.92 | 0.00 | 0.00 | 5647788.39 | 0.00 | 4135137.97 | 0.966379E+09 | 0.00 | 0.33 |
| Annual Sum or Average | 0.316547E+09 | 0.561306E+09 | 42030.42 | 91466146.91 | 35528093.42 | 22526630.02 | 0.627374E+10 | 1322.94 | 0.34 |
| Minimum of Months | 8970194.49 | 0.00 | 0.00 | 3054858.96 | 0.00 | 7998.66 | 20891998.32 | 0.00 | 0.33 |
| Maximum of Months | 45338967.24 | 0.260418E+09 | 18949.17 | 11547698.45 | 16384943.67 | 4493569.59 | 0.102954E+10 | 623.48 | 0.36 |
Report: MechanicalVentilationLoadsMonthly
For: EMPLOYEELOUNGEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.653390E+09 | 0.00 | 0.00 | 20896761.93 | 0.00 | 0.00 | 0.398563E+10 | 0.00 | 1.71 |
| February | 0.865401E+09 | 0.00 | 0.00 | 17797403.23 | 0.00 | 0.00 | 0.343110E+10 | 0.00 | 1.71 |
| March | 0.211148E+09 | 7357588.30 | 0.00 | 24862564.96 | 0.00 | 0.00 | 0.342662E+10 | 0.00 | 1.71 |
| April | 12355687.24 | 0.00 | 0.00 | 27640192.69 | 0.00 | 0.00 | 0.281215E+10 | 0.00 | 1.73 |
| May | 0.00 | 13118413.02 | 0.00 | 33302509.79 | 0.00 | 0.00 | 0.173222E+10 | 0.00 | 1.72 |
| June | 0.00 | 0.426216E+09 | 0.00 | 21705713.47 | 0.00 | 0.00 | 0.713880E+09 | 0.00 | 1.72 |
| July | 0.00 | 0.113220E+10 | 0.00 | 6310117.44 | 0.00 | 0.00 | 0.150612E+09 | 0.00 | 1.73 |
| August | 0.00 | 0.622217E+09 | 0.00 | 16745851.70 | 0.00 | 0.00 | 0.329646E+09 | 0.00 | 1.72 |
| September | 0.00 | 0.233282E+09 | 0.00 | 28009906.05 | 0.00 | 0.00 | 0.967039E+09 | 0.00 | 1.72 |
| October | 0.00 | 0.00 | 0.00 | 33314928.61 | 0.00 | 0.00 | 0.242982E+10 | 0.00 | 1.72 |
| November | 1110495.31 | 0.00 | 0.00 | 27641085.10 | 0.00 | 0.00 | 0.304821E+10 | 0.00 | 1.72 |
| December | 0.563859E+09 | 0.00 | 0.00 | 21997576.08 | 0.00 | 0.00 | 0.389127E+10 | 0.00 | 1.72 |
| Annual Sum or Average | 0.230726E+10 | 0.243439E+10 | 0.00 | 0.280225E+09 | 0.00 | 0.00 | 0.269182E+11 | 0.00 | 1.72 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 6310117.44 | 0.00 | 0.00 | 0.150612E+09 | 0.00 | 1.71 |
| Maximum of Months | 0.865401E+09 | 0.113220E+10 | 0.00 | 33314928.61 | 0.00 | 0.00 | 0.398563E+10 | 0.00 | 1.73 |
Report: MechanicalVentilationLoadsMonthly
For: EXERCISECENTERFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.362588E+10 | 0.00 | 0.00 | 34257.90 | 0.00 | 0.205621E+09 | 57236263.56 | 0.00 | 1.43 |
| February | 0.318618E+10 | 0.00 | 0.00 | 75033.39 | 0.00 | 0.385650E+09 | 35278685.32 | 0.00 | 1.43 |
| March | 0.270889E+10 | 601156.06 | 0.00 | 1716187.28 | 0.00 | 6463572.09 | 0.442850E+09 | 0.00 | 1.42 |
| April | 0.164265E+10 | 0.00 | 0.00 | 3647581.46 | 0.00 | 0.00 | 0.902609E+09 | 0.00 | 1.44 |
| May | 0.594804E+09 | 2883423.85 | 0.00 | 9376229.06 | 0.00 | 0.00 | 0.117976E+10 | 0.00 | 1.45 |
| June | 0.223171E+09 | 0.163003E+09 | 0.00 | 9537336.68 | 0.00 | 0.00 | 0.630438E+09 | 0.00 | 1.45 |
| July | 58702676.55 | 0.518638E+09 | 0.00 | 4979728.57 | 0.00 | 0.00 | 0.214974E+09 | 0.00 | 1.45 |
| August | 67093331.44 | 0.263448E+09 | 0.00 | 9186961.44 | 0.00 | 0.00 | 0.439900E+09 | 0.00 | 1.45 |
| September | 0.252174E+09 | 85101503.23 | 0.00 | 11474653.36 | 0.00 | 0.00 | 0.847621E+09 | 0.00 | 1.44 |
| October | 0.998446E+09 | 0.00 | 0.00 | 7732754.48 | 0.00 | 0.00 | 0.132353E+10 | 0.00 | 1.44 |
| November | 0.185445E+10 | 0.00 | 0.00 | 2856019.88 | 0.00 | 0.00 | 0.862490E+09 | 0.00 | 1.44 |
| December | 0.348688E+10 | 0.00 | 0.00 | 77236.47 | 0.00 | 0.163299E+09 | 89370277.58 | 0.00 | 1.43 |
| Annual Sum or Average | 0.186993E+11 | 0.103368E+10 | 0.00 | 60693979.98 | 0.00 | 0.761034E+09 | 0.702605E+10 | 0.00 | 1.44 |
| Minimum of Months | 58702676.55 | 0.00 | 0.00 | 34257.90 | 0.00 | 0.00 | 35278685.32 | 0.00 | 1.42 |
| Maximum of Months | 0.362588E+10 | 0.518638E+09 | 0.00 | 11474653.36 | 0.00 | 0.385650E+09 | 0.132353E+10 | 0.00 | 1.45 |
Report: MechanicalVentilationLoadsMonthly
For: FRONTOFFICEFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.452393E+10 | 0.00 | 0.00 | 126255.47 | 0.00 | 0.302982E+09 | 46389354.00 | 0.00 | 0.47 |
| February | 0.382196E+10 | 0.00 | 0.00 | 130136.39 | 0.00 | 0.670501E+09 | 31280163.43 | 0.00 | 0.47 |
| March | 0.344393E+10 | 1752704.35 | 0.00 | 3736604.30 | 3031.51 | 0.00 | 0.515324E+09 | 0.00 | 0.47 |
| April | 0.214986E+10 | 0.00 | 0.00 | 7427093.48 | 0.00 | 0.00 | 0.102128E+10 | 0.00 | 0.47 |
| May | 0.572104E+09 | 7948586.63 | 0.00 | 17494225.58 | 85749.02 | 0.00 | 0.161452E+10 | 0.00 | 0.47 |
| June | 54391650.67 | 0.324709E+09 | 0.00 | 16484991.22 | 607814.78 | 0.00 | 0.913486E+09 | 0.00 | 0.47 |
| July | 23237.91 | 0.974465E+09 | 0.00 | 7166968.98 | 784980.69 | 0.00 | 0.239496E+09 | 0.00 | 0.47 |
| August | 480307.05 | 0.526829E+09 | 0.00 | 16459329.05 | 296597.17 | 0.00 | 0.489011E+09 | 0.00 | 0.47 |
| September | 21594955.67 | 0.191419E+09 | 0.00 | 23596605.82 | 132596.30 | 0.00 | 0.122795E+10 | 0.00 | 0.47 |
| October | 0.924317E+09 | 0.00 | 0.00 | 18652084.60 | 0.00 | 0.00 | 0.195594E+10 | 0.00 | 0.47 |
| November | 0.221840E+10 | 0.00 | 0.00 | 7333890.54 | 0.00 | 0.00 | 0.121236E+10 | 0.00 | 0.47 |
| December | 0.439888E+10 | 0.00 | 0.00 | 251988.57 | 0.00 | 0.199780E+09 | 78509045.74 | 0.00 | 0.47 |
| Annual Sum or Average | 0.221299E+11 | 0.202712E+10 | 0.00 | 0.118860E+09 | 1910769.47 | 0.117326E+10 | 0.934555E+10 | 0.00 | 0.47 |
| Minimum of Months | 23237.91 | 0.00 | 0.00 | 126255.47 | 0.00 | 0.00 | 31280163.43 | 0.00 | 0.47 |
| Maximum of Months | 0.452393E+10 | 0.974465E+09 | 0.00 | 23596605.82 | 784980.69 | 0.670501E+09 | 0.195594E+10 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: FRONTSTAIRSFLR1
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: REARSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDORFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.314358E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 33613334.67 | 0.00 | 0.00 | 0.40 |
| February | 0.254231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.405039E+09 | 0.00 | 0.00 | 0.40 |
| March | 0.237822E+10 | 2365240.41 | 0.00 | 1662988.75 | 0.00 | 0.00 | 0.173544E+09 | 0.00 | 0.40 |
| April | 0.145818E+10 | 0.00 | 0.00 | 3814388.95 | 0.00 | 0.00 | 0.595871E+09 | 0.00 | 0.41 |
| May | 0.102770E+09 | 7637185.55 | 0.00 | 16624083.91 | 0.00 | 0.00 | 0.124509E+10 | 0.00 | 0.41 |
| June | 123586.59 | 0.294256E+09 | 0.00 | 15762941.77 | 0.00 | 0.00 | 0.555584E+09 | 0.00 | 0.41 |
| July | 0.00 | 0.808966E+09 | 0.00 | 5365456.83 | 0.00 | 0.00 | 0.115583E+09 | 0.00 | 0.41 |
| August | 0.00 | 0.438703E+09 | 0.00 | 13341419.77 | 0.00 | 0.00 | 0.265294E+09 | 0.00 | 0.41 |
| September | 15144715.54 | 0.159211E+09 | 0.00 | 17179226.10 | 0.00 | 0.00 | 0.758077E+09 | 0.00 | 0.41 |
| October | 0.907785E+09 | 0.00 | 0.00 | 8341630.44 | 0.00 | 0.00 | 0.943109E+09 | 0.00 | 0.41 |
| November | 0.195185E+10 | 0.00 | 0.00 | 1426809.84 | 0.00 | 0.00 | 0.219989E+09 | 0.00 | 0.41 |
| December | 0.296574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 79928579.11 | 0.00 | 0.00 | 0.40 |
| Annual Sum or Average | 0.154657E+11 | 0.171114E+10 | 0.00 | 83518946.36 | 0.00 | 0.518581E+09 | 0.487214E+10 | 0.00 | 0.41 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
| Maximum of Months | 0.314358E+10 | 0.808966E+09 | 0.00 | 17179226.10 | 0.00 | 0.405039E+09 | 0.124509E+10 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM201
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 31757247.07 | 0.00 | 0.00 | 0.00 | 0.00 | 10405124.52 | 0.00 | 0.00 | 0.03 |
| February | 27901990.16 | 0.00 | 0.00 | 0.00 | 0.00 | 40537530.38 | 0.00 | 0.00 | 0.04 |
| March | 22540791.68 | 0.00 | 0.00 | 0.00 | 94475.00 | 814686.21 | 0.00 | 0.00 | 0.02 |
| April | 16290646.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| May | 11761843.55 | 0.00 | 0.00 | 0.00 | 662777.16 | 0.00 | 0.00 | 0.00 | 0.02 |
| June | 7096843.20 | 659177.45 | 0.00 | 101.85 | 1157288.84 | 0.00 | 81879.99 | 0.00 | 0.02 |
| July | 2539481.80 | 2637715.12 | 0.00 | 10039.58 | 1134037.72 | 0.00 | 578123.76 | 0.00 | 0.03 |
| August | 5123223.77 | 1326758.12 | 0.00 | 789.25 | 881685.73 | 0.00 | 444527.37 | 0.00 | 0.02 |
| September | 7992741.31 | 0.00 | 0.00 | 0.00 | 589926.36 | 0.00 | 0.00 | 0.00 | 0.02 |
| October | 16288681.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| November | 19072158.97 | 0.00 | 0.00 | 0.00 | 78078.67 | 0.00 | 0.00 | 0.00 | 0.02 |
| December | 29205698.22 | 0.00 | 0.00 | 0.00 | 0.00 | 24728882.70 | 0.00 | 0.00 | 0.03 |
| Annual Sum or Average | 0.197571E+09 | 4623650.70 | 0.00 | 10930.68 | 4598269.49 | 76486223.82 | 1104531.11 | 0.00 | 0.03 |
| Minimum of Months | 2539481.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 31757247.07 | 2637715.12 | 0.00 | 10039.58 | 1157288.84 | 40537530.38 | 578123.76 | 0.00 | 0.04 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM202_205
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.218116E+09 | 0.00 | 0.00 | 751607.17 | 0.00 | 0.336258E+10 | 0.790962E+09 | 0.00 | 0.40 |
| February | 0.192723E+09 | 0.00 | 0.00 | 530391.54 | 0.00 | 0.309784E+10 | 0.745914E+09 | 0.00 | 0.40 |
| March | 0.212790E+09 | 851227.39 | 0.00 | 6395470.27 | 550.56 | 0.156817E+10 | 0.173247E+10 | 0.00 | 0.40 |
| April | 0.214279E+09 | 0.00 | 0.00 | 10830431.79 | 0.00 | 97024039.90 | 0.249062E+10 | 0.00 | 0.40 |
| May | 0.278130E+09 | 6779774.14 | 0.00 | 27820179.14 | 229436.44 | 2638225.55 | 0.153883E+10 | 0.00 | 0.41 |
| June | 0.213054E+09 | 0.305930E+09 | 0.00 | 34929653.92 | 15852390.18 | 397697.85 | 0.599057E+09 | 0.00 | 0.43 |
| July | 82616879.68 | 0.883014E+09 | 0.00 | 19648972.54 | 44123558.41 | 25022.47 | 0.124191E+09 | 0.00 | 0.44 |
| August | 0.155998E+09 | 0.464813E+09 | 0.00 | 30400306.37 | 17517256.26 | 0.00 | 0.273692E+09 | 0.00 | 0.43 |
| September | 0.257560E+09 | 0.114025E+09 | 0.00 | 32705896.58 | 10596944.25 | 714054.73 | 0.805088E+09 | 0.00 | 0.42 |
| October | 0.269537E+09 | 0.00 | 0.00 | 16007281.35 | 0.00 | 11831894.80 | 0.214633E+10 | 0.00 | 0.40 |
| November | 0.216808E+09 | 0.00 | 0.00 | 6685854.80 | 0.00 | 0.233233E+09 | 0.258724E+10 | 0.00 | 0.40 |
| December | 0.210023E+09 | 0.00 | 0.00 | 1147767.41 | 0.00 | 0.292516E+10 | 0.106364E+10 | 0.00 | 0.40 |
| Annual Sum or Average | 0.252163E+10 | 0.177541E+10 | 0.00 | 0.187854E+09 | 88320136.10 | 0.112996E+11 | 0.148980E+11 | 0.00 | 0.41 |
| Minimum of Months | 82616879.68 | 0.00 | 0.00 | 530391.54 | 0.00 | 0.00 | 0.124191E+09 | 0.00 | 0.40 |
| Maximum of Months | 0.278130E+09 | 0.883014E+09 | 0.00 | 34929653.92 | 44123558.41 | 0.336258E+10 | 0.258724E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM206_208
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.184352E+09 | 0.00 | 0.00 | 1370315.37 | 0.00 | 0.188698E+10 | 0.133167E+10 | 0.00 | 0.39 |
| February | 0.164604E+09 | 0.00 | 0.00 | 1041134.82 | 0.00 | 0.189949E+10 | 0.107649E+10 | 0.00 | 0.39 |
| March | 0.164986E+09 | 843819.72 | 0.00 | 6668100.57 | 11209.83 | 0.706160E+09 | 0.183634E+10 | 0.00 | 0.39 |
| April | 0.153805E+09 | 0.00 | 0.00 | 10648757.43 | 0.00 | 9049444.38 | 0.197546E+10 | 0.00 | 0.39 |
| May | 0.201108E+09 | 6584407.06 | 0.00 | 23727197.92 | 206236.80 | 1263488.71 | 0.118369E+10 | 0.00 | 0.40 |
| June | 0.160594E+09 | 0.245906E+09 | 0.00 | 27675315.10 | 13498248.42 | 165588.86 | 0.458296E+09 | 0.00 | 0.42 |
| July | 61169053.61 | 0.700401E+09 | 0.00 | 14734956.10 | 36974124.04 | 18716.95 | 92809755.15 | 0.00 | 0.43 |
| August | 0.117150E+09 | 0.370926E+09 | 0.00 | 23426200.18 | 14790868.49 | 0.00 | 0.205977E+09 | 0.00 | 0.42 |
| September | 0.192854E+09 | 92894231.30 | 0.00 | 26373090.04 | 9081479.00 | 295834.40 | 0.610958E+09 | 0.00 | 0.41 |
| October | 0.198154E+09 | 0.00 | 0.00 | 14657031.13 | 0.00 | 7237103.36 | 0.163411E+10 | 0.00 | 0.39 |
| November | 0.167145E+09 | 0.00 | 0.00 | 7431969.93 | 0.00 | 15624460.30 | 0.214249E+10 | 0.00 | 0.39 |
| December | 0.182257E+09 | 0.00 | 0.00 | 1904081.75 | 0.00 | 0.149438E+10 | 0.158301E+10 | 0.00 | 0.39 |
| Annual Sum or Average | 0.194818E+10 | 0.141756E+10 | 0.00 | 0.159658E+09 | 74562166.58 | 0.602066E+10 | 0.141313E+11 | 0.00 | 0.40 |
| Minimum of Months | 61169053.61 | 0.00 | 0.00 | 1041134.82 | 0.00 | 0.00 | 92809755.15 | 0.00 | 0.39 |
| Maximum of Months | 0.201108E+09 | 0.700401E+09 | 0.00 | 27675315.10 | 36974124.04 | 0.189949E+10 | 0.214249E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM209_212
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.238138E+09 | 0.00 | 0.00 | 2388596.19 | 0.00 | 0.183728E+10 | 0.228911E+10 | 0.00 | 0.39 |
| February | 0.214017E+09 | 0.00 | 0.00 | 1840632.63 | 0.00 | 0.195309E+10 | 0.185888E+10 | 0.00 | 0.40 |
| March | 0.215671E+09 | 839262.46 | 0.00 | 8712733.78 | 7536.29 | 0.668677E+09 | 0.260288E+10 | 0.00 | 0.40 |
| April | 0.201088E+09 | 0.00 | 0.00 | 13172208.03 | 0.00 | 17347049.61 | 0.254651E+10 | 0.00 | 0.40 |
| May | 0.272329E+09 | 6748893.77 | 0.00 | 28672945.24 | 221723.26 | 2610532.42 | 0.154180E+10 | 0.00 | 0.41 |
| June | 0.217913E+09 | 0.283309E+09 | 0.00 | 35106017.51 | 14945896.53 | 285059.97 | 0.606430E+09 | 0.00 | 0.42 |
| July | 87740794.15 | 0.826248E+09 | 0.00 | 20469441.09 | 41769001.50 | 25940.39 | 0.130772E+09 | 0.00 | 0.43 |
| August | 0.163141E+09 | 0.436286E+09 | 0.00 | 30807117.38 | 16331665.16 | 0.00 | 0.283467E+09 | 0.00 | 0.43 |
| September | 0.254821E+09 | 0.110146E+09 | 0.00 | 33925366.84 | 10055030.68 | 527717.53 | 0.807887E+09 | 0.00 | 0.42 |
| October | 0.253845E+09 | 0.00 | 0.00 | 19063866.05 | 0.00 | 10037189.54 | 0.210766E+10 | 0.00 | 0.40 |
| November | 0.213886E+09 | 0.00 | 0.00 | 10317480.87 | 0.00 | 31377797.88 | 0.273950E+10 | 0.00 | 0.40 |
| December | 0.235206E+09 | 0.00 | 0.00 | 3231634.86 | 0.00 | 0.153298E+10 | 0.241193E+10 | 0.00 | 0.40 |
| Annual Sum or Average | 0.256780E+10 | 0.166358E+10 | 0.00 | 0.207708E+09 | 83330853.42 | 0.605424E+10 | 0.199268E+11 | 0.00 | 0.41 |
| Minimum of Months | 87740794.15 | 0.00 | 0.00 | 1840632.63 | 0.00 | 0.00 | 0.130772E+09 | 0.00 | 0.39 |
| Maximum of Months | 0.272329E+09 | 0.826248E+09 | 0.00 | 35106017.51 | 41769001.50 | 0.195309E+10 | 0.273950E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM213
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 15627700.98 | 0.00 | 0.00 | 30961.62 | 0.00 | 0.108591E+10 | 18297975.31 | 0.00 | 0.41 |
| February | 10685011.58 | 0.00 | 0.00 | 23795.66 | 0.00 | 0.101954E+10 | 5255768.25 | 0.00 | 0.41 |
| March | 39801495.65 | 129564.21 | 0.00 | 871520.20 | 0.00 | 0.668183E+09 | 0.186693E+09 | 0.00 | 0.40 |
| April | 54615104.78 | 0.00 | 0.00 | 1518071.01 | 0.00 | 0.182159E+09 | 0.481530E+09 | 0.00 | 0.40 |
| May | 84934783.44 | 1227755.70 | 4377.45 | 5243819.46 | 49613.43 | 948343.02 | 0.376420E+09 | 59.60 | 0.40 |
| June | 62058778.04 | 72856320.31 | 0.00 | 7540292.50 | 3896045.81 | 100289.10 | 0.139480E+09 | 0.00 | 0.42 |
| July | 21499322.71 | 0.216216E+09 | 0.00 | 4678277.02 | 11187130.50 | 0.00 | 29958879.20 | 0.00 | 0.43 |
| August | 40758371.92 | 0.114279E+09 | 0.00 | 7082459.26 | 4345250.70 | 11128.91 | 65508894.11 | 0.00 | 0.42 |
| September | 73366518.10 | 27672271.73 | 0.00 | 7185745.09 | 2514134.77 | 231450.25 | 0.193306E+09 | 0.00 | 0.41 |
| October | 72803064.45 | 0.00 | 0.00 | 2878115.22 | 0.00 | 32977894.98 | 0.515419E+09 | 0.00 | 0.40 |
| November | 53907098.78 | 0.00 | 0.00 | 746684.70 | 0.00 | 0.323531E+09 | 0.393554E+09 | 0.00 | 0.40 |
| December | 26874369.98 | 0.00 | 0.00 | 39174.80 | 0.00 | 0.101472E+10 | 32171684.85 | 0.00 | 0.41 |
| Annual Sum or Average | 0.556932E+09 | 0.432381E+09 | 4377.45 | 37838916.53 | 21992175.20 | 0.432831E+10 | 0.243759E+10 | 59.60 | 0.41 |
| Minimum of Months | 10685011.58 | 0.00 | 0.00 | 23795.66 | 0.00 | 0.00 | 5255768.25 | 0.00 | 0.40 |
| Maximum of Months | 84934783.44 | 0.216216E+09 | 4377.45 | 7540292.50 | 11187130.50 | 0.108591E+10 | 0.515419E+09 | 59.60 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM214
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 61137391.12 | 0.00 | 0.00 | 1000567.69 | 0.00 | 0.400289E+09 | 0.635174E+09 | 0.00 | 0.40 |
| February | 56130428.78 | 0.00 | 0.00 | 743535.36 | 0.00 | 0.461494E+09 | 0.494499E+09 | 0.00 | 0.40 |
| March | 46900914.31 | 1074401.19 | 0.00 | 3523547.24 | 33873.70 | 51250680.77 | 0.755736E+09 | 0.00 | 0.40 |
| April | 31663872.26 | 0.00 | 0.00 | 4990267.86 | 0.00 | 2474092.30 | 0.627463E+09 | 0.00 | 0.41 |
| May | 47060275.52 | 3219494.43 | 0.00 | 8748498.51 | 81842.03 | 875342.98 | 0.368449E+09 | 0.00 | 0.41 |
| June | 38065868.90 | 91137386.37 | 0.00 | 8058078.67 | 4688938.74 | 152020.85 | 0.140104E+09 | 0.00 | 0.43 |
| July | 13247935.16 | 0.248452E+09 | 0.00 | 3560723.90 | 12911235.26 | 6096.22 | 24951006.02 | 0.00 | 0.44 |
| August | 24890610.82 | 0.139820E+09 | 0.00 | 6738457.22 | 5736851.04 | 9819.04 | 56110810.59 | 0.00 | 0.43 |
| September | 33876287.75 | 40489919.00 | 0.00 | 9745455.92 | 3747058.40 | 222938.78 | 0.181893E+09 | 0.00 | 0.43 |
| October | 29570458.48 | 3891.76 | 0.00 | 7450138.46 | 0.00 | 1818023.35 | 0.514351E+09 | 0.00 | 0.41 |
| November | 36368433.52 | 0.00 | 0.00 | 3967333.45 | 0.00 | 2973973.32 | 0.681755E+09 | 0.00 | 0.40 |
| December | 57611696.59 | 0.00 | 0.00 | 1120552.63 | 0.00 | 0.390426E+09 | 0.598845E+09 | 0.00 | 0.40 |
| Annual Sum or Average | 0.476524E+09 | 0.524198E+09 | 0.00 | 59647156.92 | 27199799.18 | 0.131199E+10 | 0.507933E+10 | 0.00 | 0.41 |
| Minimum of Months | 13247935.16 | 0.00 | 0.00 | 743535.36 | 0.00 | 6096.22 | 24951006.02 | 0.00 | 0.40 |
| Maximum of Months | 61137391.12 | 0.248452E+09 | 0.00 | 9745455.92 | 12911235.26 | 0.461494E+09 | 0.755736E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM215_218
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 14015676.21 | 0.00 | 0.00 | 9575800.10 | 0.00 | 0.00 | 0.347416E+09 | 0.00 | 0.04 |
| February | 28099375.56 | 0.00 | 0.00 | 8085203.62 | 0.00 | 0.00 | 0.291803E+09 | 0.00 | 0.04 |
| March | 0.00 | 570550.26 | 0.00 | 17349103.96 | 0.00 | 0.00 | 0.361504E+09 | 0.00 | 0.06 |
| April | 0.00 | 0.00 | 0.00 | 20923149.86 | 0.00 | 0.00 | 0.310211E+09 | 0.00 | 0.07 |
| May | 0.00 | 4230760.79 | 0.00 | 30382140.91 | 0.00 | 0.00 | 0.237786E+09 | 0.00 | 0.08 |
| June | 0.00 | 78355440.50 | 0.00 | 22557429.80 | 0.00 | 0.00 | 0.107528E+09 | 0.00 | 0.09 |
| July | 0.00 | 0.222164E+09 | 0.00 | 7480852.66 | 0.00 | 0.00 | 21439262.72 | 0.00 | 0.10 |
| August | 0.00 | 0.118200E+09 | 0.00 | 19936318.93 | 0.00 | 0.00 | 56931727.46 | 0.00 | 0.10 |
| September | 0.00 | 42940753.72 | 0.00 | 29739197.95 | 0.00 | 0.00 | 0.156118E+09 | 0.00 | 0.09 |
| October | 0.00 | 0.00 | 0.00 | 27733982.60 | 0.00 | 0.00 | 0.321389E+09 | 0.00 | 0.08 |
| November | 0.00 | 0.00 | 0.00 | 17566421.65 | 0.00 | 0.00 | 0.331393E+09 | 0.00 | 0.06 |
| December | 16959700.98 | 0.00 | 0.00 | 9200321.26 | 0.00 | 0.00 | 0.330447E+09 | 0.00 | 0.04 |
| Annual Sum or Average | 59074752.75 | 0.466462E+09 | 0.00 | 0.220530E+09 | 0.00 | 0.00 | 0.287396E+10 | 0.00 | 0.07 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 7480852.66 | 0.00 | 0.00 | 21439262.72 | 0.00 | 0.04 |
| Maximum of Months | 28099375.56 | 0.222164E+09 | 0.00 | 30382140.91 | 0.00 | 0.00 | 0.361504E+09 | 0.00 | 0.10 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM219
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 24648254.93 | 0.00 | 1121722.05 | 0.111127E+10 | 0.00 | 0.42 |
| February | 0.00 | 0.00 | 0.00 | 21730782.10 | 0.00 | 1019988.43 | 0.102447E+10 | 0.00 | 0.42 |
| March | 1099407.95 | 3056048.07 | 0.00 | 27142586.17 | 38910.26 | 833430.81 | 0.824304E+09 | 0.00 | 0.43 |
| April | 4475241.16 | 0.00 | 0.00 | 29036066.69 | 0.00 | 574650.84 | 0.594162E+09 | 0.00 | 0.43 |
| May | 19189498.32 | 8179025.14 | 0.00 | 30198951.18 | 122829.81 | 141775.12 | 0.327477E+09 | 0.00 | 0.44 |
| June | 15090102.16 | 0.142872E+09 | 0.00 | 18155260.45 | 4756771.71 | 18804.82 | 0.119275E+09 | 0.00 | 0.44 |
| July | 5011558.67 | 0.350232E+09 | 0.00 | 4553532.82 | 11939574.00 | 0.00 | 14869855.57 | 0.00 | 0.44 |
| August | 9637663.36 | 0.208798E+09 | 0.00 | 10258061.09 | 6476697.85 | 0.00 | 35983937.95 | 0.00 | 0.44 |
| September | 12761924.84 | 75486480.19 | 0.00 | 22236123.10 | 3917850.79 | 12599.97 | 0.141112E+09 | 0.00 | 0.44 |
| October | 7353079.05 | 958811.52 | 0.00 | 30818799.17 | 4201.63 | 288070.79 | 0.461501E+09 | 0.00 | 0.43 |
| November | 4172246.95 | 0.00 | 0.00 | 27112335.80 | 0.00 | 625927.33 | 0.663642E+09 | 0.00 | 0.43 |
| December | 0.00 | 0.00 | 0.00 | 24448680.57 | 0.00 | 1032833.41 | 0.103063E+10 | 0.00 | 0.42 |
| Annual Sum or Average | 78790722.46 | 0.789582E+09 | 0.00 | 0.270339E+09 | 27256836.06 | 5669803.58 | 0.634870E+10 | 0.00 | 0.43 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 4553532.82 | 0.00 | 0.00 | 14869855.57 | 0.00 | 0.42 |
| Maximum of Months | 19189498.32 | 0.350232E+09 | 0.00 | 30818799.17 | 11939574.00 | 1121722.05 | 0.111127E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM220_223
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.244561E+09 | 0.00 | 0.00 | 6924365.51 | 0.00 | 0.444671E+09 | 0.368330E+10 | 0.00 | 0.40 |
| February | 0.223465E+09 | 0.00 | 0.00 | 5878249.35 | 0.00 | 0.702805E+09 | 0.310559E+10 | 0.00 | 0.40 |
| March | 0.158597E+09 | 3837232.10 | 0.00 | 15851559.15 | 113388.26 | 17375102.09 | 0.325986E+10 | 0.00 | 0.40 |
| April | 0.118394E+09 | 0.00 | 0.00 | 19802537.58 | 0.00 | 9968846.30 | 0.254877E+10 | 0.00 | 0.41 |
| May | 0.196353E+09 | 10143924.04 | 0.00 | 33466642.06 | 281771.92 | 2820229.98 | 0.153313E+10 | 0.00 | 0.42 |
| June | 0.167806E+09 | 0.307568E+09 | 39356.75 | 32367222.71 | 16365935.19 | 470466.19 | 0.601742E+09 | 441.69 | 0.42 |
| July | 60638797.54 | 0.862630E+09 | 60200.31 | 15829323.98 | 45596710.62 | 65013.65 | 0.125685E+09 | 92.89 | 0.43 |
| August | 0.112461E+09 | 0.476157E+09 | 0.00 | 27739092.06 | 19289950.86 | 117380.71 | 0.270292E+09 | 0.00 | 0.43 |
| September | 0.146913E+09 | 0.131629E+09 | 0.00 | 38246707.43 | 12833994.37 | 327723.13 | 0.791081E+09 | 0.00 | 0.43 |
| October | 0.122094E+09 | 0.00 | 0.00 | 28652538.80 | 0.00 | 5900152.04 | 0.211369E+10 | 0.00 | 0.41 |
| November | 0.141332E+09 | 0.00 | 0.00 | 16369041.61 | 0.00 | 16798478.72 | 0.274411E+10 | 0.00 | 0.40 |
| December | 0.232198E+09 | 0.00 | 0.00 | 7006673.00 | 0.00 | 0.548971E+09 | 0.339208E+10 | 0.00 | 0.40 |
| Annual Sum or Average | 0.192481E+10 | 0.179197E+10 | 99557.06 | 0.248134E+09 | 94481751.22 | 0.175029E+10 | 0.241693E+11 | 534.58 | 0.41 |
| Minimum of Months | 60638797.54 | 0.00 | 0.00 | 5878249.35 | 0.00 | 65013.65 | 0.125685E+09 | 0.00 | 0.40 |
| Maximum of Months | 0.244561E+09 | 0.862630E+09 | 60200.31 | 38246707.43 | 45596710.62 | 0.702805E+09 | 0.368330E+10 | 441.69 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM224
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 61393730.30 | 0.00 | 0.00 | 513454.57 | 0.00 | 0.652463E+09 | 0.385656E+09 | 0.00 | 0.40 |
| February | 54688902.15 | 0.00 | 0.00 | 370839.27 | 0.00 | 0.653503E+09 | 0.305251E+09 | 0.00 | 0.40 |
| March | 50707561.05 | 917069.89 | 0.00 | 2836696.01 | 30670.04 | 0.134082E+09 | 0.678827E+09 | 0.00 | 0.40 |
| April | 34229395.51 | 0.00 | 0.00 | 4313730.12 | 0.00 | 13200543.41 | 0.623060E+09 | 0.00 | 0.40 |
| May | 51053570.09 | 2843763.39 | 0.00 | 8047380.09 | 77986.21 | 1008224.10 | 0.369145E+09 | 0.00 | 0.41 |
| June | 42125923.09 | 86617352.45 | 6034.42 | 7775004.82 | 4571718.84 | 190173.83 | 0.139178E+09 | 43.77 | 0.42 |
| July | 13580871.66 | 0.240833E+09 | 4656.03 | 3589788.44 | 12650726.62 | 13332.66 | 26392177.04 | 43.66 | 0.44 |
| August | 25774959.76 | 0.134891E+09 | 0.00 | 6640440.62 | 5507837.41 | 0.00 | 58094381.18 | 0.00 | 0.43 |
| September | 36090274.75 | 37985139.53 | 0.00 | 9494985.02 | 3604090.87 | 216384.77 | 0.183679E+09 | 0.00 | 0.43 |
| October | 34947484.96 | 0.00 | 0.00 | 6880452.02 | 0.00 | 1892236.65 | 0.515631E+09 | 0.00 | 0.41 |
| November | 41038344.52 | 0.00 | 0.00 | 3333394.23 | 0.00 | 4563943.64 | 0.684986E+09 | 0.00 | 0.40 |
| December | 57706267.27 | 0.00 | 0.00 | 615688.89 | 0.00 | 0.585463E+09 | 0.408972E+09 | 0.00 | 0.40 |
| Annual Sum or Average | 0.503337E+09 | 0.504087E+09 | 10690.45 | 54411854.10 | 26443030.00 | 0.204660E+10 | 0.437887E+10 | 87.43 | 0.41 |
| Minimum of Months | 13580871.66 | 0.00 | 0.00 | 370839.27 | 0.00 | 0.00 | 26392177.04 | 0.00 | 0.40 |
| Maximum of Months | 61393730.30 | 0.240833E+09 | 6034.42 | 9494985.02 | 12650726.62 | 0.653503E+09 | 0.684986E+09 | 43.77 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: FRONTSTAIRSFLR2
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: REARSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDORFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 97170300.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304608E+10 | 0.00 | 0.00 | 0.40 |
| February | 32436963.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289397E+10 | 0.00 | 0.00 | 0.40 |
| March | 0.103756E+10 | 1083693.99 | 0.00 | 470574.87 | 0.00 | 0.136405E+10 | 50372914.01 | 0.00 | 0.40 |
| April | 0.171815E+10 | 0.00 | 0.00 | 351108.02 | 0.00 | 0.127644E+09 | 45072833.09 | 0.00 | 0.41 |
| May | 0.883758E+09 | 5985274.41 | 0.00 | 5483098.54 | 0.00 | 0.00 | 0.464894E+09 | 0.00 | 0.41 |
| June | 0.109393E+09 | 0.269318E+09 | 0.00 | 8871716.14 | 0.00 | 0.00 | 0.466743E+09 | 0.00 | 0.41 |
| July | 0.00 | 0.765937E+09 | 0.00 | 3688780.00 | 0.00 | 0.00 | 0.127922E+09 | 0.00 | 0.41 |
| August | 11874612.92 | 0.403830E+09 | 0.00 | 7913363.25 | 0.00 | 0.00 | 0.284095E+09 | 0.00 | 0.41 |
| September | 0.301421E+09 | 0.130867E+09 | 0.00 | 7419765.53 | 0.00 | 0.00 | 0.546582E+09 | 0.00 | 0.41 |
| October | 0.164644E+10 | 0.00 | 0.00 | 1085001.63 | 0.00 | 0.00 | 88287321.65 | 0.00 | 0.40 |
| November | 0.150618E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476796E+09 | 0.00 | 0.00 | 0.40 |
| December | 73554422.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292164E+10 | 0.00 | 0.00 | 0.40 |
| Annual Sum or Average | 0.741793E+10 | 0.157702E+10 | 0.00 | 35283407.98 | 0.00 | 0.108302E+11 | 0.207397E+10 | 0.00 | 0.41 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
| Maximum of Months | 0.171815E+10 | 0.765937E+09 | 0.00 | 8871716.14 | 0.00 | 0.304608E+10 | 0.546582E+09 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM301
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 8273990.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186848E+09 | 0.00 | 0.00 | 0.11 |
| February | 12977974.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177339E+09 | 0.00 | 11.64 | 0.11 |
| March | 15524343.54 | 0.00 | 0.00 | 0.00 | 142716.82 | 47972711.70 | 0.00 | 0.00 | 0.04 |
| April | 14611575.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| May | 10778436.24 | 0.00 | 0.00 | 0.00 | 677712.58 | 0.00 | 0.00 | 0.00 | 0.02 |
| June | 6649552.21 | 534109.89 | 0.00 | 0.00 | 1146462.66 | 0.00 | 0.00 | 0.00 | 0.02 |
| July | 2532982.66 | 1770935.78 | 0.00 | 6491.80 | 1526301.74 | 0.00 | 443725.77 | 0.00 | 0.02 |
| August | 5048356.46 | 316115.21 | 0.00 | 19.69 | 1766479.77 | 0.00 | 9585.67 | 0.00 | 0.02 |
| September | 6955413.01 | 0.00 | 0.00 | 0.00 | 714515.78 | 0.00 | 0.00 | 0.00 | 0.02 |
| October | 14139099.83 | 0.00 | 0.00 | 0.00 | 20008.90 | 0.00 | 0.00 | 0.00 | 0.02 |
| November | 16710389.20 | 0.00 | 0.00 | 0.00 | 207976.30 | 0.00 | 0.00 | 0.00 | 0.02 |
| December | 12421425.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159445E+09 | 0.00 | 0.00 | 0.10 |
| Annual Sum or Average | 0.126624E+09 | 2621160.88 | 0.00 | 6511.49 | 6202174.56 | 0.571605E+09 | 453311.43 | 11.64 | 0.05 |
| Minimum of Months | 2532982.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 16710389.20 | 1770935.78 | 0.00 | 6491.80 | 1766479.77 | 0.186848E+09 | 443725.77 | 11.64 | 0.11 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM302_305
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.113962E+09 | 0.00 | 0.00 | 0.00 | 203399.59 | 0.228605E+09 | 0.00 | 0.00 | 0.05 |
| February | 99594993.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247614E+09 | 0.00 | 0.00 | 0.05 |
| March | 84526457.56 | 0.00 | 0.00 | 0.00 | 1051542.92 | 26379407.31 | 0.00 | 0.00 | 0.03 |
| April | 59627167.53 | 0.00 | 0.00 | 0.00 | 164320.17 | 0.00 | 0.00 | 0.00 | 0.02 |
| May | 45216956.59 | 0.00 | 0.00 | 0.00 | 4906214.55 | 0.00 | 0.00 | 0.00 | 0.02 |
| June | 32661327.17 | 1342332.53 | 0.00 | 0.00 | 11015928.01 | 0.00 | 0.00 | 0.00 | 0.02 |
| July | 14506480.63 | 6396265.50 | 0.00 | 12525.37 | 11079763.92 | 0.00 | 871827.43 | 0.00 | 0.02 |
| August | 26052454.21 | 454980.58 | 0.00 | 30.11 | 13367616.14 | 0.00 | 10634.68 | 0.00 | 0.02 |
| September | 31395886.47 | 0.00 | 0.00 | 0.00 | 5558405.13 | 0.00 | 0.00 | 0.00 | 0.02 |
| October | 58788094.41 | 0.00 | 0.00 | 0.00 | 689392.80 | 0.00 | 0.00 | 0.00 | 0.02 |
| November | 70946387.91 | 0.00 | 0.00 | 0.00 | 2671325.16 | 0.00 | 0.00 | 0.00 | 0.02 |
| December | 91989602.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278140E+09 | 0.00 | 0.00 | 0.05 |
| Annual Sum or Average | 0.729268E+09 | 8193578.62 | 0.00 | 12555.49 | 50707908.40 | 0.780738E+09 | 882462.11 | 0.00 | 0.03 |
| Minimum of Months | 14506480.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 0.113962E+09 | 6396265.50 | 0.00 | 12525.37 | 13367616.14 | 0.278140E+09 | 871827.43 | 0.00 | 0.05 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM306_308
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 99383268.34 | 0.00 | 0.00 | 0.00 | 79667.96 | 9002988.17 | 0.00 | 0.00 | 0.02 |
| February | 88656727.29 | 0.00 | 0.00 | 0.00 | 0.00 | 65878851.46 | 0.00 | 0.00 | 0.03 |
| March | 69563626.45 | 0.00 | 0.00 | 0.00 | 771100.93 | 0.00 | 0.00 | 0.00 | 0.02 |
| April | 49159601.03 | 0.00 | 0.00 | 0.00 | 107218.41 | 0.00 | 0.00 | 0.00 | 0.02 |
| May | 36424129.85 | 0.00 | 0.00 | 0.00 | 3832015.21 | 0.00 | 0.00 | 0.00 | 0.02 |
| June | 25700665.85 | 59092.18 | 0.00 | 0.00 | 9805125.60 | 0.00 | 0.00 | 0.00 | 0.02 |
| July | 12251839.40 | 1996976.41 | 0.00 | 2062.87 | 10729864.86 | 0.00 | 163190.26 | 0.00 | 0.02 |
| August | 20341152.31 | 0.00 | 0.00 | 0.00 | 11180646.51 | 0.00 | 0.00 | 0.00 | 0.02 |
| September | 25055911.51 | 0.00 | 0.00 | 0.00 | 4435148.73 | 0.00 | 0.00 | 0.00 | 0.02 |
| October | 48278041.64 | 0.00 | 0.00 | 0.00 | 420307.96 | 0.00 | 0.00 | 0.00 | 0.02 |
| November | 58607406.88 | 0.00 | 0.00 | 0.00 | 1887460.77 | 0.00 | 0.00 | 0.00 | 0.02 |
| December | 97573419.07 | 0.00 | 0.00 | 0.00 | 0.00 | 25470808.19 | 0.00 | 0.00 | 0.03 |
| Annual Sum or Average | 0.630996E+09 | 2056068.59 | 0.00 | 2062.87 | 43248556.93 | 0.100353E+09 | 163190.26 | 0.00 | 0.02 |
| Minimum of Months | 12251839.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 99383268.34 | 1996976.41 | 0.00 | 2062.87 | 11180646.51 | 65878851.46 | 163190.26 | 0.00 | 0.03 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM309_312
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.203940E+09 | 0.00 | 0.00 | 925943.88 | 0.00 | 0.317298E+10 | 0.978763E+09 | 0.00 | 0.40 |
| February | 0.190805E+09 | 0.00 | 0.00 | 738651.67 | 0.00 | 0.292208E+10 | 0.906231E+09 | 0.00 | 0.40 |
| March | 0.211162E+09 | 798165.85 | 0.00 | 6825481.91 | 1250.14 | 0.135862E+10 | 0.192671E+10 | 0.00 | 0.40 |
| April | 0.212428E+09 | 0.00 | 0.00 | 11143806.71 | 0.00 | 79918063.44 | 0.249870E+10 | 0.00 | 0.40 |
| May | 0.298044E+09 | 6512880.88 | 0.00 | 27547736.91 | 221095.35 | 3728977.79 | 0.153394E+10 | 0.00 | 0.41 |
| June | 0.229133E+09 | 0.280070E+09 | 0.00 | 34739050.12 | 14592609.11 | 400556.12 | 0.602071E+09 | 0.00 | 0.42 |
| July | 90915920.18 | 0.811492E+09 | 0.00 | 21021161.75 | 40638150.98 | 0.00 | 0.133569E+09 | 0.00 | 0.43 |
| August | 0.169252E+09 | 0.421848E+09 | 0.00 | 30537907.33 | 15316233.96 | 49073.31 | 0.293244E+09 | 0.00 | 0.43 |
| September | 0.283326E+09 | 0.104103E+09 | 0.00 | 32369169.55 | 9189201.06 | 1415125.14 | 0.824767E+09 | 0.00 | 0.41 |
| October | 0.288363E+09 | 0.00 | 0.00 | 15161382.04 | 0.00 | 19773193.81 | 0.214695E+10 | 0.00 | 0.40 |
| November | 0.215752E+09 | 0.00 | 0.00 | 6268429.48 | 0.00 | 0.240221E+09 | 0.257720E+10 | 0.00 | 0.40 |
| December | 0.195143E+09 | 0.00 | 0.00 | 1259162.26 | 0.00 | 0.279766E+10 | 0.119087E+10 | 0.00 | 0.40 |
| Annual Sum or Average | 0.258826E+10 | 0.162482E+10 | 0.00 | 0.188538E+09 | 79958540.60 | 0.105968E+11 | 0.156130E+11 | 0.00 | 0.41 |
| Minimum of Months | 90915920.18 | 0.00 | 0.00 | 738651.67 | 0.00 | 0.00 | 0.133569E+09 | 0.00 | 0.40 |
| Maximum of Months | 0.298044E+09 | 0.811492E+09 | 0.00 | 34739050.12 | 40638150.98 | 0.317298E+10 | 0.257720E+10 | 0.00 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM313
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 15224091.37 | 0.00 | 0.00 | 0.00 | 67430.16 | 99090948.32 | 0.00 | 0.00 | 0.06 |
| February | 19071319.17 | 0.00 | 0.00 | 0.00 | 0.00 | 95928984.72 | 0.00 | 0.00 | 0.07 |
| March | 19477204.03 | 0.00 | 0.00 | 0.00 | 300302.02 | 13475234.47 | 0.00 | 0.00 | 0.03 |
| April | 14535116.93 | 0.00 | 0.00 | 0.00 | 54053.49 | 0.00 | 0.00 | 0.00 | 0.02 |
| May | 10882574.36 | 0.00 | 0.00 | 0.00 | 1314184.76 | 0.00 | 0.00 | 0.00 | 0.02 |
| June | 7751110.94 | 0.00 | 0.00 | 0.00 | 3300291.16 | 0.00 | 0.00 | 0.00 | 0.02 |
| July | 3827777.12 | 103207.36 | 0.00 | 44.91 | 3940573.23 | 0.00 | 6886.88 | 0.00 | 0.02 |
| August | 6338326.86 | 0.00 | 0.00 | 0.00 | 3649487.71 | 0.00 | 0.00 | 0.00 | 0.02 |
| September | 7701249.62 | 0.00 | 0.00 | 0.00 | 1513313.91 | 0.00 | 0.00 | 0.00 | 0.02 |
| October | 14737293.69 | 0.00 | 0.00 | 0.00 | 193702.76 | 0.00 | 0.00 | 0.00 | 0.02 |
| November | 17803737.09 | 0.00 | 0.00 | 0.00 | 659745.53 | 0.00 | 0.00 | 0.00 | 0.02 |
| December | 15879423.87 | 0.00 | 0.00 | 0.00 | 0.00 | 95724711.59 | 0.00 | 0.00 | 0.06 |
| Annual Sum or Average | 0.153229E+09 | 103207.36 | 0.00 | 44.91 | 14993084.72 | 0.304220E+09 | 6886.88 | 0.00 | 0.03 |
| Minimum of Months | 3827777.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 19477204.03 | 103207.36 | 0.00 | 44.91 | 3940573.23 | 99090948.32 | 6886.88 | 0.00 | 0.07 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM314
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 51965368.30 | 0.00 | 0.00 | 149308.16 | 0.00 | 0.937189E+09 | 0.106859E+09 | 0.00 | 0.40 |
| February | 49747761.70 | 0.00 | 0.00 | 111031.51 | 0.00 | 0.889064E+09 | 74123864.96 | 0.00 | 0.40 |
| March | 52842150.37 | 743360.71 | 0.00 | 1885276.53 | 26930.74 | 0.351123E+09 | 0.466624E+09 | 0.00 | 0.40 |
| April | 40748671.97 | 0.00 | 0.00 | 3319026.61 | 0.00 | 70626449.63 | 0.573161E+09 | 0.00 | 0.40 |
| May | 51072959.27 | 2674964.87 | 0.00 | 7604514.36 | 75810.37 | 877242.58 | 0.377008E+09 | 0.00 | 0.41 |
| June | 41956814.68 | 87724352.16 | 0.00 | 7923012.22 | 4474508.63 | 191623.51 | 0.140903E+09 | 0.00 | 0.42 |
| July | 14541097.19 | 0.242027E+09 | 0.00 | 3790086.91 | 12355199.19 | 7538.50 | 26160039.70 | 0.00 | 0.44 |
| August | 27590749.05 | 0.133780E+09 | 0.00 | 6886068.44 | 5240383.39 | 2554.74 | 58725402.61 | 0.00 | 0.43 |
| September | 40089301.64 | 36526435.27 | 0.00 | 9093949.44 | 3422453.66 | 218685.95 | 0.188994E+09 | 0.00 | 0.42 |
| October | 47006126.12 | 0.00 | 0.00 | 5233846.02 | 0.00 | 8590834.47 | 0.523408E+09 | 0.00 | 0.40 |
| November | 48471088.23 | 0.00 | 0.00 | 1735285.33 | 0.00 | 0.194318E+09 | 0.509074E+09 | 0.00 | 0.40 |
| December | 46402820.73 | 0.00 | 0.00 | 176517.09 | 0.00 | 0.886775E+09 | 0.119993E+09 | 0.00 | 0.40 |
| Annual Sum or Average | 0.512435E+09 | 0.503476E+09 | 0.00 | 47907922.62 | 25595285.98 | 0.333898E+10 | 0.316503E+10 | 0.00 | 0.41 |
| Minimum of Months | 14541097.19 | 0.00 | 0.00 | 111031.51 | 0.00 | 2554.74 | 26160039.70 | 0.00 | 0.40 |
| Maximum of Months | 52842150.37 | 0.242027E+09 | 0.00 | 9093949.44 | 12355199.19 | 0.937189E+09 | 0.573161E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM315_318
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.219252E+09 | 0.00 | 0.00 | 11866025.81 | 0.00 | 53910129.97 | 0.407257E+10 | 0.00 | 0.40 |
| February | 0.207534E+09 | 0.00 | 0.00 | 10428456.07 | 0.00 | 0.176028E+09 | 0.362073E+10 | 0.00 | 0.40 |
| March | 89724524.05 | 5272846.64 | 0.00 | 21903115.33 | 139026.39 | 13005894.67 | 0.328557E+10 | 0.00 | 0.41 |
| April | 67548327.25 | 0.00 | 0.00 | 25992662.84 | 0.00 | 7822770.26 | 0.253972E+10 | 0.00 | 0.42 |
| May | 0.162308E+09 | 14159339.96 | 0.00 | 40591734.99 | 327738.28 | 1759255.52 | 0.150384E+10 | 0.00 | 0.42 |
| June | 0.146792E+09 | 0.363986E+09 | 0.00 | 35294783.92 | 18105838.78 | 278159.49 | 0.574864E+09 | 0.00 | 0.43 |
| July | 53597156.20 | 0.977085E+09 | 0.00 | 14963028.30 | 49666886.72 | 0.00 | 0.104460E+09 | 0.00 | 0.44 |
| August | 0.100156E+09 | 0.545268E+09 | 0.00 | 28277912.14 | 22197105.26 | 2156.60 | 0.237044E+09 | 0.00 | 0.44 |
| September | 0.132116E+09 | 0.158713E+09 | 0.00 | 41289542.68 | 14750446.90 | 372778.91 | 0.744665E+09 | 0.00 | 0.43 |
| October | 78049734.71 | 18418.09 | 0.00 | 33668467.80 | 0.00 | 5928468.80 | 0.209826E+10 | 0.00 | 0.42 |
| November | 0.126638E+09 | 0.00 | 0.00 | 20447856.61 | 0.00 | 13331314.54 | 0.271188E+10 | 0.00 | 0.41 |
| December | 0.218157E+09 | 0.00 | 0.00 | 11527995.74 | 0.00 | 35624210.25 | 0.387304E+10 | 0.00 | 0.40 |
| Annual Sum or Average | 0.160187E+10 | 0.206450E+10 | 0.00 | 0.296252E+09 | 0.105187E+09 | 0.308064E+09 | 0.253666E+11 | 0.00 | 0.42 |
| Minimum of Months | 53597156.20 | 0.00 | 0.00 | 10428456.07 | 0.00 | 0.00 | 0.104460E+09 | 0.00 | 0.40 |
| Maximum of Months | 0.219252E+09 | 0.977085E+09 | 0.00 | 41289542.68 | 49666886.72 | 0.176028E+09 | 0.407257E+10 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM319
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 40512078.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| February | 37809830.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| March | 30525172.98 | 9427.90 | 0.00 | 12962.56 | 7362.68 | 0.00 | 132540.10 | 0.00 | 0.02 |
| April | 22404177.93 | 0.00 | 0.00 | 57.96 | 0.00 | 0.00 | 295.15 | 0.00 | 0.02 |
| May | 14734297.32 | 853025.80 | 0.00 | 38669.00 | 39846.95 | 0.00 | 1512529.11 | 0.00 | 0.02 |
| June | 4671653.81 | 4389006.54 | 0.00 | 276427.62 | 486760.46 | 0.00 | 4697481.24 | 0.00 | 0.03 |
| July | 60824.46 | 13197024.07 | 0.00 | 236476.88 | 0.00 | 0.00 | 2069256.88 | 0.00 | 0.04 |
| August | 1378021.54 | 7791414.12 | 0.00 | 444348.68 | 0.00 | 0.00 | 4624716.15 | 0.00 | 0.04 |
| September | 3076907.63 | 2393680.75 | 0.00 | 449040.93 | 0.00 | 0.00 | 9620103.69 | 0.00 | 0.03 |
| October | 21233114.52 | 0.00 | 0.00 | 72210.15 | 0.00 | 0.00 | 1647065.48 | 0.00 | 0.02 |
| November | 25556038.09 | 0.00 | 0.00 | 0.00 | 31147.57 | 0.00 | 0.00 | 0.00 | 0.02 |
| December | 39449817.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Annual Sum or Average | 0.241412E+09 | 28633579.18 | 0.00 | 1530193.80 | 565117.65 | 0.00 | 24303987.79 | 0.00 | 0.03 |
| Minimum of Months | 60824.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 40512078.52 | 13197024.07 | 0.00 | 449040.93 | 486760.46 | 0.00 | 9620103.69 | 0.00 | 0.04 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM320_323
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.240198E+09 | 0.00 | 0.00 | 3981550.51 | 0.00 | 0.130043E+10 | 0.282236E+10 | 0.00 | 0.40 |
| February | 0.224472E+09 | 0.00 | 0.00 | 3549667.55 | 0.00 | 0.143957E+10 | 0.235412E+10 | 0.00 | 0.40 |
| March | 0.183524E+09 | 3149485.36 | 0.00 | 12766792.42 | 100203.24 | 0.161018E+09 | 0.311630E+10 | 0.00 | 0.40 |
| April | 0.142526E+09 | 0.00 | 0.00 | 16656505.45 | 0.00 | 12109670.71 | 0.256495E+10 | 0.00 | 0.41 |
| May | 0.210238E+09 | 9191745.47 | 0.00 | 31129212.71 | 269012.15 | 2750035.56 | 0.155202E+10 | 0.00 | 0.41 |
| June | 0.182403E+09 | 0.295973E+09 | 17823.38 | 32034961.61 | 15767822.68 | 578175.33 | 0.601794E+09 | 981.08 | 0.42 |
| July | 66872346.30 | 0.837473E+09 | 26059.00 | 16458112.09 | 44123350.56 | 120445.43 | 0.129265E+09 | 966.78 | 0.43 |
| August | 0.124204E+09 | 0.456442E+09 | 30314.23 | 28017747.21 | 18111199.73 | 148388.34 | 0.277789E+09 | 621.36 | 0.43 |
| September | 0.170646E+09 | 0.123737E+09 | 33039.28 | 36743826.13 | 11991060.91 | 686338.88 | 0.806883E+09 | 987.37 | 0.42 |
| October | 0.162399E+09 | 0.00 | 0.00 | 23933522.27 | 0.00 | 9226935.18 | 0.214319E+10 | 0.00 | 0.41 |
| November | 0.166213E+09 | 0.00 | 0.00 | 11629581.21 | 0.00 | 29365855.79 | 0.276725E+10 | 0.00 | 0.40 |
| December | 0.227944E+09 | 0.00 | 0.00 | 3895946.92 | 0.00 | 0.133415E+10 | 0.261299E+10 | 0.00 | 0.40 |
| Annual Sum or Average | 0.210164E+10 | 0.172597E+10 | 107235.89 | 0.220797E+09 | 90362649.27 | 0.429015E+10 | 0.217489E+11 | 3556.59 | 0.41 |
| Minimum of Months | 66872346.30 | 0.00 | 0.00 | 3549667.55 | 0.00 | 120445.43 | 0.129265E+09 | 0.00 | 0.40 |
| Maximum of Months | 0.240198E+09 | 0.837473E+09 | 33039.28 | 36743826.13 | 44123350.56 | 0.143957E+10 | 0.311630E+10 | 987.37 | 0.43 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM324
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 35121791.86 | 0.00 | 0.00 | 0.00 | 8.48 | 0.00 | 0.00 | 0.00 | 0.02 |
| February | 32832202.09 | 0.00 | 0.00 | 0.00 | 0.00 | 647652.25 | 0.00 | 0.00 | 0.02 |
| March | 26360951.22 | 0.00 | 0.00 | 0.00 | 80067.02 | 0.00 | 0.00 | 0.00 | 0.02 |
| April | 18760142.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| May | 13269262.13 | 0.00 | 0.00 | 0.00 | 1054882.90 | 0.00 | 0.00 | 0.00 | 0.02 |
| June | 8849318.56 | 306194.50 | 0.00 | 49.33 | 2761225.20 | 0.00 | 3002.29 | 0.00 | 0.02 |
| July | 3259391.48 | 1540197.00 | 0.00 | 4581.61 | 2677905.98 | 0.00 | 766762.23 | 0.00 | 0.02 |
| August | 4366599.22 | 2384842.97 | 0.00 | 17145.92 | 1256501.06 | 0.00 | 2588400.31 | 0.00 | 0.02 |
| September | 9169550.10 | 24798.05 | 0.00 | 10784.07 | 862545.27 | 0.00 | 956091.19 | 0.00 | 0.02 |
| October | 19222893.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| November | 21805423.99 | 0.00 | 0.00 | 0.00 | 248095.49 | 0.00 | 0.00 | 0.00 | 0.02 |
| December | 34105586.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Annual Sum or Average | 0.227123E+09 | 4256032.52 | 0.00 | 32560.92 | 8941231.41 | 647652.25 | 4314256.01 | 0.00 | 0.02 |
| Minimum of Months | 3259391.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 35121791.86 | 2384842.97 | 0.00 | 17145.92 | 2761225.20 | 647652.25 | 2588400.31 | 0.00 | 0.02 |
Report: MechanicalVentilationLoadsMonthly
For: FRONTSTAIRSFLR3
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: REARSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: CORRIDORFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 10722935.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313244E+10 | 0.00 | 0.00 | 0.40 |
| February | 19200173.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290598E+10 | 0.00 | 0.00 | 0.40 |
| March | 0.352129E+09 | 2089161.25 | 0.00 | 374982.14 | 0.00 | 0.206829E+10 | 17498230.19 | 0.00 | 0.40 |
| April | 0.711217E+09 | 0.00 | 0.00 | 1493697.18 | 0.00 | 0.102084E+10 | 0.126010E+09 | 0.00 | 0.41 |
| May | 0.784560E+09 | 8277695.97 | 0.00 | 8103077.16 | 0.00 | 0.123403E+09 | 0.370562E+09 | 0.00 | 0.41 |
| June | 0.327477E+09 | 0.249338E+09 | 0.00 | 10128234.26 | 0.00 | 4515273.64 | 0.279088E+09 | 0.00 | 0.41 |
| July | 0.111626E+09 | 0.692705E+09 | 0.00 | 3987877.05 | 126412.24 | 0.00 | 78109020.62 | 0.00 | 0.41 |
| August | 0.212723E+09 | 0.357342E+09 | 0.00 | 7548603.09 | 0.00 | 0.00 | 0.170594E+09 | 0.00 | 0.41 |
| September | 0.562131E+09 | 0.112545E+09 | 0.00 | 7420222.96 | 0.00 | 22602335.52 | 0.258205E+09 | 0.00 | 0.41 |
| October | 0.829620E+09 | 0.00 | 0.00 | 1497902.32 | 0.00 | 0.755999E+09 | 83125643.23 | 0.00 | 0.40 |
| November | 0.280407E+09 | 0.00 | 0.00 | 4737.30 | 0.00 | 0.168143E+10 | 2811099.45 | 0.00 | 0.40 |
| December | 11224896.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298280E+10 | 0.00 | 0.00 | 0.40 |
| Annual Sum or Average | 0.421304E+10 | 0.142230E+10 | 0.00 | 40559333.45 | 126412.24 | 0.146983E+11 | 0.138600E+10 | 0.00 | 0.41 |
| Minimum of Months | 10722935.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
| Maximum of Months | 0.829620E+09 | 0.692705E+09 | 0.00 | 10128234.26 | 126412.24 | 0.313244E+10 | 0.370562E+09 | 0.00 | 0.41 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM401
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 11558.20 | 0.00 | 0.110150E+10 | 1229333.95 | 0.00 | 0.44 |
| February | 0.00 | 0.00 | 0.00 | 10005.12 | 0.00 | 0.101131E+10 | 1209413.11 | 0.00 | 0.44 |
| March | 18682908.99 | 527644.35 | 0.00 | 577501.81 | 22498.12 | 0.777813E+09 | 61812184.34 | 0.00 | 0.41 |
| April | 36564538.38 | 0.00 | 0.00 | 1073368.79 | 0.00 | 0.465307E+09 | 0.172568E+09 | 0.00 | 0.40 |
| May | 60986008.15 | 2101648.44 | 0.00 | 5022225.20 | 66436.52 | 0.114230E+09 | 0.287949E+09 | 0.00 | 0.41 |
| June | 50725303.11 | 78936579.90 | 0.00 | 6866823.41 | 3438503.20 | 14267336.98 | 0.142803E+09 | 0.00 | 0.43 |
| July | 20498188.31 | 0.230214E+09 | 0.00 | 3837343.80 | 10141703.41 | 0.00 | 38217252.48 | 0.00 | 0.45 |
| August | 38893524.07 | 0.118910E+09 | 5360.98 | 5651469.81 | 3938672.59 | 41009.48 | 79602165.34 | 222.64 | 0.44 |
| September | 62826327.85 | 27304477.81 | 6738.84 | 5321536.07 | 2726031.00 | 39673271.68 | 0.194404E+09 | 1.38 | 0.42 |
| October | 60385438.48 | 0.00 | 0.00 | 1210478.91 | 0.00 | 0.389881E+09 | 0.167919E+09 | 0.00 | 0.40 |
| November | 23754727.39 | 0.00 | 0.00 | 142751.38 | 0.00 | 0.664492E+09 | 31813116.22 | 0.00 | 0.41 |
| December | 645076.90 | 0.00 | 0.00 | 14379.10 | 0.00 | 0.104715E+10 | 1454985.95 | 0.00 | 0.44 |
| Annual Sum or Average | 0.373962E+09 | 0.457994E+09 | 12099.82 | 29739441.60 | 20333844.84 | 0.562566E+10 | 0.118098E+10 | 224.02 | 0.42 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 10005.12 | 0.00 | 0.00 | 1209413.11 | 0.00 | 0.40 |
| Maximum of Months | 62826327.85 | 0.230214E+09 | 6738.84 | 6866823.41 | 10141703.41 | 0.110150E+10 | 0.287949E+09 | 222.64 | 0.45 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM402_405
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 17291052.52 | 0.00 | 0.00 | 0.00 | 126210.32 | 0.109485E+10 | 0.00 | 0.00 | 0.17 |
| February | 30918225.17 | 0.00 | 10132.86 | 0.00 | 0.00 | 0.101403E+10 | 0.00 | 1372.69 | 0.16 |
| March | 70644400.87 | 0.00 | 0.00 | 0.00 | 277476.72 | 0.399443E+09 | 0.00 | 0.00 | 0.08 |
| April | 66073713.88 | 0.00 | 0.00 | 0.00 | 0.00 | 22315719.50 | 0.00 | 0.00 | 0.03 |
| May | 49978238.06 | 3247551.39 | 0.00 | 20375.42 | 559759.35 | 0.00 | 6115588.34 | 0.00 | 0.02 |
| June | 21116280.75 | 26114497.17 | 0.00 | 448306.85 | 1317392.80 | 0.00 | 12934313.97 | 0.00 | 0.03 |
| July | 521554.50 | 65934912.13 | 0.00 | 397033.52 | 0.00 | 0.00 | 6763122.12 | 0.00 | 0.04 |
| August | 7237966.92 | 29988094.10 | 0.00 | 546715.83 | 0.00 | 0.00 | 15027317.60 | 0.00 | 0.03 |
| September | 36127059.14 | 1398482.92 | 0.00 | 13772.06 | 2634730.39 | 0.00 | 1688672.55 | 0.00 | 0.02 |
| October | 59824022.24 | 0.00 | 0.00 | 0.00 | 0.00 | 14479534.71 | 0.00 | 0.00 | 0.03 |
| November | 64477273.93 | 0.00 | 0.00 | 0.00 | 2276606.11 | 84947647.72 | 0.00 | 0.00 | 0.04 |
| December | 24687264.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.955141E+09 | 0.00 | 0.00 | 0.15 |
| Annual Sum or Average | 0.448897E+09 | 0.126684E+09 | 10132.86 | 1426203.68 | 7192175.69 | 0.358521E+10 | 42529014.58 | 1372.69 | 0.07 |
| Minimum of Months | 521554.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 70644400.87 | 65934912.13 | 10132.86 | 546715.83 | 2634730.39 | 0.109485E+10 | 15027317.60 | 1372.69 | 0.17 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM406_408
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 22640008.24 | 0.00 | 0.00 | 0.00 | 84656.82 | 0.771246E+09 | 0.00 | 0.00 | 0.14 |
| February | 40973220.29 | 0.00 | 13161.46 | 0.00 | 0.00 | 0.707156E+09 | 0.00 | 1158.35 | 0.14 |
| March | 64138656.02 | 0.00 | 0.00 | 0.00 | 208393.47 | 0.259590E+09 | 0.00 | 0.00 | 0.07 |
| April | 53842394.27 | 0.00 | 0.00 | 0.00 | 0.00 | 10207432.04 | 0.00 | 0.00 | 0.02 |
| May | 40299744.54 | 2577618.47 | 0.00 | 11871.40 | 436250.86 | 0.00 | 4411502.09 | 0.00 | 0.02 |
| June | 16807143.69 | 19337758.40 | 0.00 | 333194.25 | 1048627.40 | 0.00 | 10359330.39 | 0.00 | 0.03 |
| July | 458294.82 | 47512064.18 | 0.00 | 305355.82 | 486151.98 | 0.00 | 5674940.46 | 0.00 | 0.04 |
| August | 5855925.47 | 22199427.82 | 0.00 | 397634.87 | 0.00 | 0.00 | 12332521.84 | 0.00 | 0.03 |
| September | 28920053.06 | 981679.56 | 0.00 | 9568.46 | 2122012.55 | 0.00 | 1147922.24 | 0.00 | 0.02 |
| October | 49038058.29 | 0.00 | 0.00 | 0.00 | 0.00 | 4999084.14 | 0.00 | 0.00 | 0.02 |
| November | 53652063.02 | 0.00 | 0.00 | 0.00 | 1597963.58 | 35089935.05 | 0.00 | 0.00 | 0.03 |
| December | 35813893.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.656476E+09 | 0.00 | 0.00 | 0.13 |
| Annual Sum or Average | 0.412439E+09 | 92608548.42 | 13161.46 | 1057624.80 | 5984056.66 | 0.244477E+10 | 33926217.02 | 1158.35 | 0.06 |
| Minimum of Months | 458294.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 64138656.02 | 47512064.18 | 13161.46 | 397634.87 | 2122012.55 | 0.771246E+09 | 12332521.84 | 1158.35 | 0.14 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM409_412
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 74054759.85 | 0.00 | 0.00 | 306258.51 | 0.00 | 0.409991E+10 | 0.262635E+09 | 0.00 | 0.41 |
| February | 0.127074E+09 | 0.00 | 0.00 | 261052.42 | 0.00 | 0.375323E+10 | 0.186660E+09 | 0.00 | 0.40 |
| March | 0.199132E+09 | 2013710.27 | 0.00 | 4455637.61 | 81859.43 | 0.237685E+10 | 0.963860E+09 | 0.00 | 0.40 |
| April | 0.155838E+09 | 0.00 | 0.00 | 9091884.89 | 0.00 | 0.102799E+10 | 0.166013E+10 | 0.00 | 0.40 |
| May | 0.250071E+09 | 8376938.25 | 0.00 | 25017443.41 | 283151.78 | 0.151413E+09 | 0.152188E+10 | 0.00 | 0.41 |
| June | 0.209329E+09 | 0.288474E+09 | 24358.75 | 29492908.44 | 14697376.33 | 4752412.99 | 0.667930E+09 | 1154.69 | 0.43 |
| July | 86152740.25 | 0.843341E+09 | 66044.90 | 16218285.38 | 40842181.96 | 42158.82 | 0.169813E+09 | 930.94 | 0.44 |
| August | 0.159019E+09 | 0.434073E+09 | 12905.38 | 24278187.23 | 16392853.64 | 242629.68 | 0.351997E+09 | 552.24 | 0.43 |
| September | 0.244654E+09 | 0.103735E+09 | 10921.40 | 25030303.66 | 11245912.49 | 20834650.37 | 0.941696E+09 | 1189.00 | 0.42 |
| October | 0.261258E+09 | 0.00 | 0.00 | 10727394.13 | 0.00 | 0.775265E+09 | 0.152944E+10 | 0.00 | 0.40 |
| November | 0.205551E+09 | 0.00 | 0.00 | 3085197.78 | 0.00 | 0.171998E+10 | 0.115295E+10 | 0.00 | 0.40 |
| December | 0.105634E+09 | 0.00 | 0.00 | 374483.06 | 0.00 | 0.381695E+10 | 0.334427E+09 | 0.00 | 0.41 |
| Annual Sum or Average | 0.207777E+10 | 0.168001E+10 | 114230.44 | 0.148339E+09 | 83543335.63 | 0.177475E+11 | 0.974341E+10 | 3826.87 | 0.41 |
| Minimum of Months | 74054759.85 | 0.00 | 0.00 | 261052.42 | 0.00 | 42158.82 | 0.169813E+09 | 0.00 | 0.40 |
| Maximum of Months | 0.261258E+09 | 0.843341E+09 | 66044.90 | 29492908.44 | 40842181.96 | 0.409991E+10 | 0.166013E+10 | 1189.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM413
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 3658745.80 | 0.00 | 0.00 | 0.00 | 41373.59 | 0.252859E+09 | 0.00 | 0.00 | 0.15 |
| February | 5173690.63 | 0.00 | 3885.08 | 0.00 | 0.00 | 0.246036E+09 | 0.00 | 994.12 | 0.16 |
| March | 14217479.51 | 0.00 | 0.00 | 0.00 | 99439.52 | 90968647.03 | 0.00 | 0.00 | 0.07 |
| April | 15870266.87 | 0.00 | 0.00 | 0.00 | 2818.38 | 4855380.34 | 0.00 | 0.00 | 0.03 |
| May | 13156835.96 | 0.00 | 0.00 | 0.00 | 977524.83 | 0.00 | 0.00 | 0.00 | 0.02 |
| June | 6287325.99 | 3893200.91 | 0.00 | 78211.82 | 666123.67 | 0.00 | 1980329.94 | 0.00 | 0.03 |
| July | 130253.78 | 10115472.20 | 0.00 | 79141.10 | 544960.77 | 0.00 | 2105862.21 | 0.00 | 0.03 |
| August | 2885066.24 | 4983750.54 | 0.00 | 104868.17 | 127675.37 | 0.00 | 3200046.58 | 0.00 | 0.03 |
| September | 9040007.31 | 85726.75 | 0.00 | 2303.65 | 842076.73 | 0.00 | 23517.82 | 0.00 | 0.02 |
| October | 14944583.44 | 0.00 | 0.00 | 0.00 | 6537.24 | 1401159.82 | 0.00 | 0.00 | 0.02 |
| November | 16123478.12 | 0.00 | 0.00 | 0.00 | 528427.02 | 12363530.34 | 0.00 | 0.00 | 0.03 |
| December | 4421735.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223535E+09 | 0.00 | 0.00 | 0.14 |
| Annual Sum or Average | 0.105909E+09 | 19078150.40 | 3885.08 | 264524.75 | 3836957.13 | 0.832019E+09 | 7309756.55 | 994.12 | 0.06 |
| Minimum of Months | 130253.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 16123478.12 | 10115472.20 | 3885.08 | 104868.17 | 977524.83 | 0.252859E+09 | 3200046.58 | 994.12 | 0.16 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM414
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 26856634.03 | 0.00 | 0.00 | 0.00 | 8680.56 | 0.104230E+09 | 0.00 | 0.00 | 0.07 |
| February | 27893136.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110272E+09 | 0.00 | 0.00 | 0.08 |
| March | 26100527.20 | 33134.64 | 0.00 | 11514.67 | 0.00 | 20086777.01 | 149010.76 | 0.00 | 0.03 |
| April | 19714238.91 | 0.00 | 0.00 | 1753.19 | 0.00 | 0.00 | 770356.75 | 0.00 | 0.02 |
| May | 12211572.52 | 914066.54 | 0.00 | 68965.32 | 126210.15 | 0.00 | 3576887.04 | 0.00 | 0.02 |
| June | 3553074.95 | 5908765.56 | 0.00 | 203085.88 | 380592.99 | 0.00 | 5354610.60 | 0.00 | 0.03 |
| July | 125793.36 | 16396421.25 | 0.00 | 160658.21 | 331306.53 | 0.00 | 1726193.56 | 0.00 | 0.04 |
| August | 1573325.67 | 8784343.14 | 0.00 | 386336.90 | 0.00 | 0.00 | 3945237.57 | 0.00 | 0.04 |
| September | 2639398.42 | 1965479.89 | 0.00 | 248994.51 | 2691.26 | 0.00 | 9067652.41 | 0.00 | 0.03 |
| October | 19238242.97 | 0.00 | 0.00 | 35627.57 | 0.00 | 0.00 | 807755.61 | 0.00 | 0.02 |
| November | 20796756.46 | 0.00 | 0.00 | 0.00 | 194161.40 | 0.00 | 0.00 | 0.00 | 0.02 |
| December | 24434982.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100542E+09 | 0.00 | 0.00 | 0.07 |
| Annual Sum or Average | 0.185138E+09 | 34002211.03 | 0.00 | 1116936.26 | 1043642.89 | 0.335130E+09 | 25397704.29 | 0.00 | 0.04 |
| Minimum of Months | 125793.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 27893136.55 | 16396421.25 | 0.00 | 386336.90 | 380592.99 | 0.110272E+09 | 9067652.41 | 0.00 | 0.08 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM415_418
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.226020E+09 | 0.00 | 0.00 | 1874361.72 | 0.00 | 0.307506E+10 | 0.108630E+10 | 0.00 | 0.40 |
| February | 0.183875E+09 | 0.00 | 0.00 | 2066984.11 | 0.00 | 0.276928E+10 | 0.109125E+10 | 0.00 | 0.40 |
| March | 0.107545E+09 | 5708533.78 | 0.00 | 10703649.83 | 164188.59 | 0.139738E+10 | 0.201076E+10 | 0.00 | 0.40 |
| April | 96863657.42 | 0.00 | 0.00 | 16543680.45 | 0.00 | 0.544756E+09 | 0.213830E+10 | 0.00 | 0.41 |
| May | 0.177410E+09 | 11464082.94 | 0.00 | 31682021.00 | 314408.95 | 29575064.51 | 0.162010E+10 | 0.00 | 0.42 |
| June | 0.150198E+09 | 0.316842E+09 | 6852.23 | 29947331.27 | 16469786.08 | 1336252.73 | 0.662221E+09 | 1143.39 | 0.43 |
| July | 61947221.32 | 0.890280E+09 | 93601.64 | 13795611.39 | 45977681.25 | 98962.25 | 0.152612E+09 | 2674.20 | 0.44 |
| August | 0.110089E+09 | 0.484766E+09 | 3132.77 | 24068586.04 | 20263323.85 | 310895.80 | 0.321824E+09 | 51.14 | 0.44 |
| September | 0.141963E+09 | 0.130239E+09 | 10260.71 | 32723580.99 | 13914514.83 | 1747935.49 | 0.900344E+09 | 562.77 | 0.43 |
| October | 0.128616E+09 | 0.00 | 0.00 | 21261875.48 | 0.00 | 0.339366E+09 | 0.193177E+10 | 0.00 | 0.41 |
| November | 0.139976E+09 | 0.00 | 0.00 | 8965817.60 | 0.00 | 0.900148E+09 | 0.197364E+10 | 0.00 | 0.40 |
| December | 0.218861E+09 | 0.00 | 0.00 | 2070368.58 | 0.00 | 0.296940E+10 | 0.101002E+10 | 0.00 | 0.40 |
| Annual Sum or Average | 0.174336E+10 | 0.183930E+10 | 113847.35 | 0.195704E+09 | 97103903.55 | 0.120284E+11 | 0.148992E+11 | 4431.50 | 0.41 |
| Minimum of Months | 61947221.32 | 0.00 | 0.00 | 1874361.72 | 0.00 | 98962.25 | 0.152612E+09 | 0.00 | 0.40 |
| Maximum of Months | 0.226020E+09 | 0.890280E+09 | 93601.64 | 32723580.99 | 45977681.25 | 0.307506E+10 | 0.213830E+10 | 2674.20 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM419
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 56922569.53 | 0.00 | 0.00 | 305660.61 | 0.00 | 0.855361E+09 | 0.185794E+09 | 0.00 | 0.40 |
| February | 51119831.12 | 0.00 | 0.00 | 332488.42 | 0.00 | 0.785488E+09 | 0.175908E+09 | 0.00 | 0.40 |
| March | 31986322.42 | 1469702.67 | 0.00 | 2468225.89 | 45678.50 | 0.375307E+09 | 0.466879E+09 | 0.00 | 0.40 |
| April | 25514505.29 | 0.00 | 0.00 | 4215557.17 | 0.00 | 0.131001E+09 | 0.530800E+09 | 0.00 | 0.41 |
| May | 43539441.96 | 3281570.26 | 0.00 | 8312130.44 | 82037.32 | 1223209.45 | 0.395041E+09 | 0.00 | 0.42 |
| June | 36398299.06 | 88778927.53 | 0.00 | 7604980.28 | 4450946.27 | 285798.59 | 0.154264E+09 | 0.00 | 0.43 |
| July | 14683993.82 | 0.242144E+09 | 0.00 | 3243825.66 | 12451419.32 | 13884.62 | 31412611.11 | 0.00 | 0.44 |
| August | 26484258.67 | 0.133700E+09 | 0.00 | 5948203.95 | 5526452.75 | 51332.78 | 68714918.65 | 0.00 | 0.44 |
| September | 35160183.56 | 36627897.08 | 308.26 | 8432022.54 | 3762036.20 | 408324.68 | 0.207516E+09 | 1.96 | 0.43 |
| October | 33346355.61 | 99.89 | 0.00 | 5418710.75 | 0.00 | 81091278.07 | 0.472684E+09 | 0.00 | 0.41 |
| November | 35725935.39 | 0.00 | 0.00 | 2070050.61 | 0.00 | 0.243692E+09 | 0.472517E+09 | 0.00 | 0.40 |
| December | 51973726.76 | 0.00 | 0.00 | 353360.72 | 0.00 | 0.814565E+09 | 0.185485E+09 | 0.00 | 0.40 |
| Annual Sum or Average | 0.442855E+09 | 0.506002E+09 | 308.26 | 48705217.04 | 26318570.37 | 0.328849E+10 | 0.334702E+10 | 1.96 | 0.41 |
| Minimum of Months | 14683993.82 | 0.00 | 0.00 | 305660.61 | 0.00 | 13884.62 | 31412611.11 | 0.00 | 0.40 |
| Maximum of Months | 56922569.53 | 0.242144E+09 | 308.26 | 8432022.54 | 12451419.32 | 0.855361E+09 | 0.530800E+09 | 1.96 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM420_423
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.220191E+09 | 0.00 | 0.00 | 1412748.44 | 0.00 | 0.325181E+10 | 0.914598E+09 | 0.00 | 0.40 |
| February | 0.196314E+09 | 0.00 | 0.00 | 1563820.08 | 0.00 | 0.294923E+10 | 0.896422E+09 | 0.00 | 0.40 |
| March | 0.119079E+09 | 5246238.24 | 0.00 | 9280759.36 | 159916.73 | 0.153540E+10 | 0.187528E+10 | 0.00 | 0.40 |
| April | 0.104133E+09 | 0.00 | 0.00 | 14868521.41 | 0.00 | 0.669197E+09 | 0.202301E+10 | 0.00 | 0.41 |
| May | 0.186439E+09 | 10579625.45 | 0.00 | 29589413.00 | 310838.83 | 70928844.78 | 0.159217E+10 | 0.00 | 0.42 |
| June | 0.158509E+09 | 0.300340E+09 | 15908.81 | 28714902.70 | 15865738.97 | 1698053.23 | 0.671101E+09 | 624.28 | 0.43 |
| July | 65160912.27 | 0.856188E+09 | 71484.37 | 13807641.77 | 44633831.78 | 137643.40 | 0.161303E+09 | 3069.84 | 0.44 |
| August | 0.116006E+09 | 0.462482E+09 | 70523.93 | 23581951.23 | 19436684.92 | 322497.80 | 0.334294E+09 | 1486.98 | 0.43 |
| September | 0.154209E+09 | 0.122243E+09 | 55987.91 | 31281544.10 | 13221491.34 | 9360563.18 | 0.909606E+09 | 1794.49 | 0.43 |
| October | 0.143544E+09 | 0.00 | 0.00 | 19360174.68 | 0.00 | 0.439489E+09 | 0.184748E+10 | 0.00 | 0.41 |
| November | 0.142343E+09 | 0.00 | 0.00 | 7642718.16 | 0.00 | 0.106226E+10 | 0.182655E+10 | 0.00 | 0.40 |
| December | 0.206479E+09 | 0.00 | 0.00 | 1583391.86 | 0.00 | 0.310823E+10 | 0.888354E+09 | 0.00 | 0.40 |
| Annual Sum or Average | 0.181241E+10 | 0.175708E+10 | 213905.02 | 0.182688E+09 | 93628502.57 | 0.130981E+11 | 0.139402E+11 | 6975.59 | 0.41 |
| Minimum of Months | 65160912.27 | 0.00 | 0.00 | 1412748.44 | 0.00 | 137643.40 | 0.161303E+09 | 0.00 | 0.40 |
| Maximum of Months | 0.220191E+09 | 0.856188E+09 | 71484.37 | 31281544.10 | 44633831.78 | 0.325181E+10 | 0.202301E+10 | 3069.84 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: GUESTROOM424
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 34931787.34 | 0.00 | 0.00 | 66424.12 | 0.00 | 0.104168E+10 | 34674017.30 | 0.00 | 0.40 |
| February | 35823827.91 | 0.00 | 0.00 | 83282.11 | 0.00 | 0.955857E+09 | 31340990.55 | 0.00 | 0.40 |
| March | 46545121.52 | 1221941.86 | 0.00 | 1405162.07 | 43492.92 | 0.583744E+09 | 0.255105E+09 | 0.00 | 0.40 |
| April | 32323517.21 | 0.00 | 0.00 | 2973123.38 | 0.00 | 0.270302E+09 | 0.399401E+09 | 0.00 | 0.41 |
| May | 46488651.01 | 2826187.59 | 0.00 | 7035283.16 | 79991.96 | 32146605.09 | 0.374110E+09 | 0.00 | 0.42 |
| June | 39136822.17 | 85383012.43 | 6250.62 | 6973487.29 | 4368570.55 | 501437.55 | 0.156513E+09 | 833.45 | 0.43 |
| July | 14802957.11 | 0.239566E+09 | 8565.16 | 3147691.96 | 12408395.53 | 23448.18 | 32710480.08 | 168.03 | 0.44 |
| August | 26946424.75 | 0.131030E+09 | 8683.54 | 5710659.85 | 5436031.87 | 62538.13 | 71028040.74 | 75.93 | 0.43 |
| September | 37495339.90 | 34674695.55 | 0.00 | 7751213.55 | 3652750.91 | 6183852.33 | 0.209472E+09 | 0.00 | 0.42 |
| October | 40384972.19 | 0.00 | 0.00 | 4160493.58 | 0.00 | 0.178699E+09 | 0.390011E+09 | 0.00 | 0.41 |
| November | 40124494.53 | 0.00 | 0.00 | 1106593.64 | 0.00 | 0.447983E+09 | 0.278073E+09 | 0.00 | 0.40 |
| December | 30771647.95 | 0.00 | 0.00 | 83404.58 | 0.00 | 0.988637E+09 | 49168758.41 | 0.00 | 0.41 |
| Annual Sum or Average | 0.425776E+09 | 0.494702E+09 | 23499.31 | 40496819.28 | 25989233.75 | 0.450582E+10 | 0.228161E+10 | 1077.40 | 0.41 |
| Minimum of Months | 14802957.11 | 0.00 | 0.00 | 66424.12 | 0.00 | 23448.18 | 31340990.55 | 0.00 | 0.40 |
| Maximum of Months | 46545121.52 | 0.239566E+09 | 8683.54 | 7751213.55 | 12408395.53 | 0.104168E+10 | 0.399401E+09 | 833.45 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: FRONTSTAIRSFLR4
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:21:21
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.130543E+12 | 0.409441E+11 | 0.00 | 0.00 | 0.562543E+11 |
| February | 0.187838E+12 | 0.413774E+11 | 0.00 | 0.00 | 0.517411E+11 |
| March | 0.266977E+12 | 0.306331E+11 | 0.00 | 0.00 | 0.679760E+11 |
| April | 0.300249E+12 | 0.242266E+11 | 0.00 | 0.00 | 0.719984E+11 |
| May | 0.357582E+12 | 0.161538E+11 | 0.00 | 0.00 | 0.119671E+12 |
| June | 0.383661E+12 | 0.914552E+10 | 0.00 | 0.00 | 0.190189E+12 |
| July | 0.358366E+12 | 0.207519E+10 | 0.00 | 0.00 | 0.261806E+12 |
| August | 0.312111E+12 | 0.522269E+10 | 0.00 | 0.00 | 0.233947E+12 |
| September | 0.246526E+12 | 0.102798E+11 | 0.00 | 0.00 | 0.167527E+12 |
| October | 0.180008E+12 | 0.204881E+11 | 0.00 | 0.00 | 0.955143E+11 |
| November | 0.102274E+12 | 0.271878E+11 | 0.00 | 0.00 | 0.618808E+11 |
| December | 0.116935E+12 | 0.424572E+11 | 0.00 | 0.00 | 0.555229E+11 |
| Annual Sum or Average | 0.294307E+13 | 0.270191E+12 | 0.00 | 0.00 | 0.143403E+13 |
| Minimum of Months | 0.102274E+12 | 0.207519E+10 | 0.00 | 0.00 | 0.517411E+11 |
| Maximum of Months | 0.383661E+12 | 0.424572E+11 | 0.00 | 0.00 | 0.261806E+12 |