Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20
Tabular Output Report in Format: HTML
Building: RestaurantSitDown
Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Simulation Timestamp: 2024-07-03 12:20:43
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Values gathered over 8760.00 hours| Total Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
| Total Site Energy | 2367.01 | 4630.72 | 4630.72 |
| Net Site Energy | 2367.01 | 4630.72 | 4630.72 |
| Total Source Energy | 4948.39 | 9680.83 | 9680.83 |
| Net Source Energy | 4948.39 | 9680.83 | 9680.83 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [m2] | |
| Total Building Area | 511.15 |
| Net Conditioned Building Area | 511.15 |
| Unconditioned Building Area | 0.00 |
| Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | 0.00 | 325.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 162.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 168.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 71.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 455.60 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 248.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 428.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
| Refrigeration | 36.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 1143.81 | 1223.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
| Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | General | 0.00 | 325.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 162.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 168.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 71.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | Cooking | 417.03 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ReachInFreezer | 15.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInRefrigerator | 23.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | General | 248.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | General | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Heater | 0.00 | 428.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.43 | |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1375.86 | |
| Refrigeration | General | 6.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LowTempRefrigeration | 11.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MedTempRefrigeration | 18.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
| Heating | Unassigned | 0.00 | 325.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 162.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 168.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 71.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 455.60 | 469.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 248.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 0.00 | 428.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2201.28 |
| Refrigeration | Unassigned | 36.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 470.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 805.05 | 1473.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
| Other | 962.46 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 2237.70 | 2393.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
| Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
| Lighting | 470.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 805.05 | 1473.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
| Other | 962.46 | 919.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 2237.70 | 2393.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.31 |
| Electricity [GJ] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 1143.808 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 1143.808 | 100.00 |
| Total On-Site and Utility Electric Sources | 1143.808 | 100.00 |
| Total Electricity End Uses | 1143.808 | 100.00 |
| Heat [GJ] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | |
| Air to Air Heat Recovery for Cooling | 0.00 | |
| Air to Air Heat Recovery for Heating | 0.00 | |
| High-Temperature Geothermal* | 0.00 | |
| Solar Water Thermal | 0.00 | |
| Solar Air Thermal | 0.00 | |
| Total On-Site Thermal Sources | 0.00 |
| Water [m3] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 2201.28 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 2201.28 | 100.00 |
| Total Water End Uses | 2201.28 | 100.00 |
| Degrees [deltaC] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 37.67 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 4235.50 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |ZoneCoolingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneHeatingSummaryMonthly
| DINING | KITCHEN | ATTIC |ZoneElectricSummaryMonthly
| DINING | KITCHEN |SpaceGainsMonthly
| DINING | KITCHEN | ATTIC |PeakSpaceGainsMonthly
| DINING | KITCHEN | ATTIC |SpaceGainComponentsAtCoolingPeakMonthly
| DINING | KITCHEN | ATTIC |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| DINING | KITCHEN | ATTIC |ComfortReportSimple55Monthly
| DINING | KITCHEN | ATTIC |OccupantComfortDataSummaryMonthly
| DINING PEOPLE | KITCHEN PEOPLE |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |WindowReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| DINING_WALL_EAST_WINDOW | DINING_WALL_SOUTH_WINDOW | DINING_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |WindowEnergyZoneSummaryMonthly
| DINING | KITCHEN | ATTIC |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWH BOOSTER G WATER HEATER | SWHSYS1 WATER HEATER |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL |PlantLoopDemandReportMonthly
| SWHSYS1 |FanReportMonthly
| DINING EXHAUST FAN | KITCHEN EXHAUST FAN | PSZ-AC_1:1_ADDAQ FAN | PSZ-AC_2:2_ADDAQ FAN |PumpReportMonthly
| SWHSYS1 PUMP |CondLoopDemandReportMonthly
| SWHSYS1 |ZoneTemperatureOscillationReportMonthly
| DINING | KITCHEN | ATTIC |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 |MechanicalVentilationLoadsMonthly
| DINING | KITCHEN |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
General| Value | |
| Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2024.07.03 12:20 |
| RunPeriod | RUNPERIOD 1 |
| Weather File | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
| Latitude [deg] | 40.65 |
| Longitude [deg] | -73.8 |
| Elevation [m] | 5.00 |
| Time Zone | -5.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
| Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
| Window Opening Area [m2] | 66.16 | 0.00 | 19.55 | 27.07 | 19.55 |
| Gross Window-Wall Ratio [%] | 24.00 | 0.00 | 28.36 | 39.27 | 28.36 |
| Above Ground Window-Wall Ratio [%] | 24.00 | 0.00 | 28.36 | 39.27 | 28.36 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
| Above Ground Wall Area [m2] | 275.72 | 68.93 | 68.93 | 68.93 | 68.93 |
| Window Opening Area [m2] | 66.16 | 0.00 | 19.55 | 27.07 | 19.55 |
| Gross Window-Wall Ratio [%] | 24.00 | 0.00 | 28.36 | 39.27 | 28.36 |
| Above Ground Window-Wall Ratio [%] | 24.00 | 0.00 | 28.36 | 39.27 | 28.36 |
| Total | |
| Gross Roof Area [m2] | 569.51 |
| Skylight Area [m2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| DINING | 371.75 | Yes | Yes | 1133.39 | 1.00 | 169.19 | 0.00 | 66.16 | 66.16 | 20.6319 | 1.33 | 64.9275 |
| KITCHEN | 139.41 | Yes | Yes | 425.02 | 1.00 | 106.53 | 0.00 | 0.00 | 0.00 | 11.3949 | 18.52 | 1062.0430 |
| ATTIC | 511.15 | No | No | 856.26 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
| Total | 511.15 | 1558.40 | 275.72 | 0.00 | 66.16 | 66.16 | 18.1127 | 1.78 | 336.8677 | |||
| Conditioned Total | 511.15 | 1558.40 | 275.72 | 0.00 | 66.16 | 66.16 | 18.1127 | 1.78 | 336.8677 | |||
| Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
| Not Part of Total | 511.15 | 856.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
| Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
| DINING | 371.75 | Yes | Yes | 1.00 | DINING | GENERAL | DINING | 20.6319 | 1.33 | 64.9275 | |
| KITCHEN | 139.41 | Yes | Yes | 1.00 | KITCHEN | GENERAL | KITCHEN | 11.3949 | 18.52 | 1062.0430 | |
| ATTIC | 511.15 | No | No | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
| Total | 511.15 | 18.1127 | 0.89 | 336.8677 | |||||||
| Conditioned Total | 511.15 | 18.1127 | 0.89 | 336.8677 | |||||||
| Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
| Not Part of Total | 511.15 | 0.0000 | 0.00 | 0.0000 |
| Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
| GENERAL | 511.15 | 511.15 | 0.00 | 511.15 | 18.1127 | 1.78 | 336.8677 |
| Total | 511.15 | 511.15 | 0.00 | 511.15 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
End Uses| Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Time of Peak | 19-JUN-11:00 | 06-FEB-07:10 | - | - | - | - | - | - | - | - | - | - | 02-JAN-19:30 |
| Heating | 0.00 | 119073.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 38854.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 8332.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 22921.93 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 9365.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 26741.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 1197.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 80689.74 | 159391.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
| Heating | General | 0.00 | 119073.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 38854.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | LightsWired | 8332.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | Cooking | 21698.93 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ReachInFreezer | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| ReachInRefrigerator | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | General | 9365.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | General | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Heater | 0.00 | 26741.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 193.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LowTempRefrigeration | 366.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| MedTempRefrigeration | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Values gathered over 8760.00 hours| Source Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
| Heating | 0.00 | 352.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 514.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 533.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 227.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 1442.89 | 509.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 787.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 1.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 464.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 115.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 3622.44 | 1325.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 689.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 1006.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 1043.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 445.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 2822.81 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 1540.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 908.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 225.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 7086.80 | 2594.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
| Heating | 0.00 | 689.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 1006.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 1043.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 445.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 2822.81 | 996.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 1540.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 2.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 908.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 225.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 7086.80 | 2594.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
AirTerminal:SingleDuct:ConstantVolume:NoReheat| Design Size Maximum Air Flow Rate [m3/s] | |
| DINING DIRECT AIR | 3.97 |
| KITCHEN DIRECT AIR | 1.76 |
| Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
| PSZ-AC_1:1 | 3.97 | 3.97 | 3.97 | 3.97 | 3.97 | 3.97 | 1.00 | 1.00 | 3.97 |
| PSZ-AC_2:2 | 1.76 | 1.76 | 1.76 | 1.76 | 1.76 | 1.76 | 1.00 | 1.000000 | 1.76 |
| Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
| PSZ-AC_1:1_OA_CONTROLLER | 3.97 | 1.33 |
| PSZ-AC_2:2_OA_CONTROLLER | 1.76 | 1.22 |
| Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
| PSZ-AC_1:1_ADDAQ FAN | 3.97 | 6440.61 |
| PSZ-AC_2:2_ADDAQ FAN | 1.76 | 2924.83 |
| Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.97 | 3.97 | 3.97 | 3.97 | 98596.50 | 104398.02 | 32.11 | 1.00 |
| PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.76 | 1.76 | 1.76 | 1.76 | 43700.70 | 67606.21 | 30.11 | 1.00 |
| User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
| PSZ-AC_1:1 COOLING COIL | 3.97 | 1.99 | 2.65 | 98596.50 | 49298.25 | 0.701080 | 0.701080 |
| PSZ-AC_2:2 COOLING COIL | 1.76 | 0.879914 | 1.17 | 43700.70 | 21850.35 | 0.701080 | 0.701080 |
| Design Size Nominal Capacity [W] | |
| PSZ-AC_1:1 HEATING COIL | 104398.02 |
| PSZ-AC_2:2 HEATING COIL | 67606.21 |
| Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
| SWHSYS1 | 0.000140 | 0.016782 |
| Design Flow Rate [m3/s] | Design Power Consumption [W] | |
| SWHSYS1 PUMP | 0.000140 | 17.86 |
| Use Side Design Flow Rate [m3/s] | |
| SWHSYS1 WATER HEATER | 0.000140 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| None |
| Possible Shadow Receivers | |
| DINING_WALL_EAST | DINING_WALL_EAST_WINDOW | |
| DINING_WALL_SOUTH | DINING_WALL_SOUTH_WINDOW | |
| DINING_WALL_WEST | DINING_WALL_WEST_WINDOW | |
| KITCHEN_WALL_EAST | KITCHEN_WALL_EAST_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Version| Version ID | |
| 1 | 22.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | Yes | No | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.556 | 0.556 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 14.00 | 7.30 | 3.30 | 1.20 | -0.20 | 5.60 | 10.90 | 16.10 | 21.70 | 25.00 | 24.80 | 19.90 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
| Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
| 1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
| 1 | New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 | 40.65 | -73.80 | -5.00 | 5.00 | 101265 | 1.2036 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
| 1 | Correlation | NA | 12.47 | 25.20 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | RestaurantSitDown | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | DOE-2 |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
| 1 | ThirdOrderBackwardDifference |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
| 1 | 0.330 | 460.000 | 6.500000E-003 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
| 1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 0 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 3 | 24 | 4 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | DINING | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 8.22 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 16.44 | 0.00 | 3.05 | 3.05 | 1133.39 | TARP | DOE-2 | 371.75 | 169.19 | 103.03 | 66.16 | 6 | 3 | 0 | Yes |
| 2 | KITCHEN | 0.0 | 0.00 | 0.00 | 0.00 | 11.30 | 19.53 | 1.52 | 1 | 1 | 1 | 0.00 | 22.61 | 16.44 | 22.61 | 0.00 | 3.05 | 3.05 | 425.02 | TARP | DOE-2 | 139.41 | 106.53 | 104.58 | 0.00 | 6 | 1 | 0 | Yes |
| 3 | ATTIC | 0.0 | 0.00 | 0.00 | 3.05 | 11.30 | 11.30 | 3.92 | 1 | 1 | 1 | 0.00 | 22.61 | 0.00 | 22.61 | 3.05 | 6.82 | 1.88 | 856.26 | TARP | DOE-2 | 511.15 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | No |
| Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
| 1 | DINING | 371.75 | 280.1 | 1.327 | 0.754 | 20.632 | 64.927 | 0.000 | 0.000 | 0.000 | 0.000 | 85.559 | No |
| 2 | KITCHEN | 139.41 | 7.5 | 18.518 | 5.400E-002 | 11.395 | 412.767 | 649.276 | 0.000 | 0.000 | 0.000 | 1073.438 | No |
| 3 | ATTIC | 511.15 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
| 1 | DINING PEOPLE | BLDG_OCC_SCH | DINING | 371.75 | 280.1 | 280.1 | 0.754 | 1.327 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 280 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| 2 | KITCHEN PEOPLE | BLDG_OCC_SCH | KITCHEN | 139.41 | 7.5 | 7.5 | 5.400E-002 | 18.518 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 8 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
| 1 | DINING_LIGHTS | LTG_SCH_DINING | DINING | 371.75 | 280.1 | 7669.876 | 20.632 | 27.379 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 7669.876 |
| 2 | KITCHEN_LIGHTS | LTG_SCH_KITCHEN | KITCHEN | 139.41 | 7.5 | 1588.510 | 11.395 | 211.016 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1588.510 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | DINING_MISCELEC_EQUIP | BLDG_EQUIP_SCH | DINING | 371.75 | 280.1 | 24136.662 | 64.927 | 86.159 | 0.250 | 0.300 | 0.000 | 0.450 | Cooking | 0.000 | 6999.632 |
| 2 | KITCHEN_MISCELEC_EQUIP | BLDG_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 56318.878 | 403.994 | 7481.353 | 0.250 | 0.300 | 0.200 | 0.250 | Cooking | 0.000 | 16332.475 |
| 3 | KITCHEN_REACH-IN-FREEZER | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 493.000 | 3.536 | 65.490 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInFreezer | 493.000 | 493.000 |
| 4 | KITCHEN_REACH-IN-REFRIGERATOR | ALWAYS_ON | KITCHEN | 139.41 | 7.5 | 730.000 | 5.237 | 96.973 | 0.000 | 0.250 | 0.000 | 0.750 | ReachInRefrigerator | 730.000 | 730.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
| 1 | KITCHEN_MISCGAS_EQUIP | REST_GAS_EQUIP_SCH | KITCHEN | 139.41 | 7.5 | 90512.482 | 649.276 | 12023.603 | 0.100 | 0.200 | 0.700 | 0.000 | Cooking | 0.000 | 26248.620 |
| Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
| 1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 9.815 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
| 2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 3 | ATTICROOFDECK | 6 | 2 | 4 | 0.167 | 4.706 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
| 4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 5 | NONRES_ROOF | 17 | 2 | 4 | 0.167 | 0.3836 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 6 | NONRES_ROOF_FLOOR | 20 | 2 | 4 | 0.167 | 0.3836 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 7 | NONRES_EXT_WALL_GRD | 23 | 4 | 7 | 0.167 | 0.7871 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 8 | DINING_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1943 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| 9 | KITCHEN_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.3331 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
| Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
| 1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1019 |
| 2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
| 3 | F12 ASPHALT SHINGLES | 0.0032 | 0.040 | 1120.000 | 1260.000 | 0.8000E-01 |
| 4 | G02 16MM PLYWOOD | 0.0159 | 0.120 | 544.000 | 1210.000 | 0.1325 |
| 5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
| 6 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
| 7 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.508 |
| 8 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 10 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 2.508 |
| 11 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
| 12 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 13 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.037 |
| 14 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
| 15 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 5.069 |
| 16 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| 17 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.925 |
| 18 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
| Time | Outside | Cross | Inside | Flux (except final one) | |
| 1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
| 2 | 0 | 9.8148919 | 9.8148919 | 9.8148919 | |
| 3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
| 4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
| 5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
| 6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
| 7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
| 8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
| 9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
| 10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
| 11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
| 12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
| 13 | 4 | 0.12552254E-09 | 0.24226224E-10 | 0.35972174E-10 | -0.14154396E-16 |
| 14 | 3 | -0.27173896E-03 | 0.71777257E-04 | -0.16206070E-03 | 0.11981077E-09 |
| 15 | 2 | 0.48258702 | 0.15872105 | 0.47241503 | -0.16497355E-03 |
| 16 | 1 | -7.8004821 | 2.4804491 | -9.1443147 | 0.17387321 |
| 17 | 0 | 11.206599 | 1.2491899 | 12.560494 | |
| 18 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
| 19 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
| 20 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
| 21 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
| 22 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
| 23 | 4 | -0.36752283E-16 | 0.36650618E-15 | -0.17323971E-14 | 0.96945811E-16 |
| 24 | 3 | -0.69118654E-08 | 0.27160578E-06 | -0.56853996E-04 | 0.15386634E-12 |
| 25 | 2 | 0.11860501E-03 | 0.58949329E-02 | 1.1525899 | -0.75054507E-04 |
| 26 | 1 | -0.13685427 | 0.15202565 | -17.175506 | 0.33646671 |
| 27 | 0 | 0.39128804 | 0.96631513E-01 | 16.277526 | |
| 28 | 4 | -0.17323971E-14 | 0.36650618E-15 | -0.36752283E-16 | 0.96945811E-16 |
| 29 | 3 | -0.56853996E-04 | 0.27160578E-06 | -0.69118654E-08 | 0.15386634E-12 |
| 30 | 2 | 1.1525899 | 0.58949329E-02 | 0.11860501E-03 | -0.75054507E-04 |
| 31 | 1 | -17.175506 | 0.15202565 | -0.13685427 | 0.33646671 |
| 32 | 0 | 16.277526 | 0.96631513E-01 | 0.39128804 | |
| 33 | 7 | -0.29735092E-12 | 0.24575595E-14 | -0.94456721E-13 | 0.15324278E-15 |
| 34 | 6 | 0.28546880E-07 | 0.22114619E-09 | 0.65405332E-08 | -0.13451374E-12 |
| 35 | 5 | -0.18947583E-03 | 0.18937623E-05 | -0.97466953E-04 | 0.64660656E-08 |
| 36 | 4 | 0.29140875 | 0.92215111E-03 | 0.99417931E-01 | -0.33466744E-04 |
| 37 | 3 | -7.2517161 | 0.28579858E-01 | -2.3345767 | 0.28937395E-01 |
| 38 | 2 | 40.822959 | 0.10163225 | 15.247323 | -0.33280368 |
| 39 | 1 | -80.508872 | 0.45869584E-01 | -29.125752 | 1.0778326 |
| 40 | 0 | 46.824339 | 0.92288667E-03 | 16.291614 | |
| 41 | 7 | -0.21734457E-08 | -0.74519938E-15 | 0.50382772E-14 | -0.69890712E-16 |
| 42 | 6 | 0.54724052E-05 | 0.37200423E-08 | 0.31902721E-02 | -0.26762676E-04 |
| 43 | 5 | -0.39134311E-03 | 0.22020570E-05 | -0.22374744 | 0.19563521E-02 |
| 44 | 4 | 0.89880071E-02 | 0.10022018E-03 | 4.8299266 | -0.45268642E-01 |
| 45 | 3 | -0.78885897E-01 | 0.79680432E-03 | -38.023569 | 0.39867754 |
| 46 | 2 | 0.28005141 | 0.13253957E-02 | 116.48814 | -1.4179954 |
| 47 | 1 | -0.40417713 | 0.40366627E-03 | -143.90977 | 2.0490805 |
| 48 | 0 | 0.19704758 | 0.98000257E-05 | 60.838472 | |
| 49 | 7 | -0.12499535E-08 | -0.14387371E-15 | 0.77706651E-14 | -0.10512995E-15 |
| 50 | 6 | 0.93054176E-05 | 0.64134387E-08 | 0.31793048E-02 | -0.26670673E-04 |
| 51 | 5 | -0.67382570E-03 | 0.38039073E-05 | -0.22312401 | 0.19508494E-02 |
| 52 | 4 | 0.15526878E-01 | 0.17323304E-03 | 4.8195417 | -0.45168817E-01 |
| 53 | 3 | -0.13642300 | 0.13783931E-02 | -37.964896 | 0.39802903 |
| 54 | 2 | 0.48450154 | 0.22938927E-02 | 116.37394 | -1.4164678 |
| 55 | 1 | -0.69935771 | 0.69956273E-03 | -143.84254 | 2.0479754 |
| 56 | 0 | 0.34098252 | 0.16815417E-04 | 60.838472 |
| Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
| 1 | NONRESWINDOW_U_0.57_SHGC_SOUTH_0.39 | 38 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
| 2 | NONRESWINDOW_U_0.57_SHGC_NORTH_0.39 | 39 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
| 3 | NONRESWINDOW_U_0.57_SHGC_EAST_0.39 | 40 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 | ||
| 4 | NONRESWINDOW_U_0.57_SHGC_WEST_0.39 | 41 | 1 | VerySmooth | 3.241 | 3.241 | 1.000 | 0.391 |
| Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
| 1 | NONRES WINDOW GLAZING LAYER SOUTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
| 2 | NONRES WINDOW GLAZING LAYER NORTH | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
| 3 | NONRES WINDOW GLAZING LAYER EAST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No | |
| 4 | NONRES WINDOW GLAZING LAYER WEST | SpectralAverage | 2.00000E-003 | 0.30403 | 0.46623 | 0.46623 | 0.42900 | 0.13485 | 0.17261 | 0.00000 | 0.84000 | 0.84000 | 1.43763E-002 | 1.00000 | No |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 7 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Number of Refrigeration Compressor Racks | |
| 1 | 2 |
| Compressor Rack Name | # Refrigerated Cases Connected | # WalkIn Coolers Connected | Heat Rejection Location | Condenser Type | COP | |
| 1 | RACK1 | 1 | 0 | Zone | Air-Cooled | 2.510 |
| 2 | RACK2 | 1 | 0 | Zone | Air-Cooled | 7.290 |
| Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | SWH BOOSTER G WATER HEATER | 2.2712E-002 | 8000.0 | 0.975 | 0.8950 |
| 2 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 0.7570 | 58614.2 | 14.749 | 0.4701 |
| Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
| 1 | DINING_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 4 | No | No |
| 2 | DINING_WALL_EAST_WINDOW | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 1 | No | No |
| 3 | DINING_WALL_SOUTH | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 4 | No | No |
| 4 | DINING_WALL_SOUTH_WINDOW | 0 | 129.19 | 59.48 | 6.82 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 1 | No | No |
| 5 | DINING_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 4 | No | No |
| 6 | DINING_WALL_WEST_WINDOW | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 1 | No | No |
| 7 | DINING_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 0 | No | No |
| 8 | DINING_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 0 | No | No |
| 9 | DINING_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 0 | No | No |
| 10 | DINING_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 55.49 | 19.04 | 0.39 | 0 | No | No |
| 11 | KITCHEN_WALL_NORTH | 0 | 129.19 | 77.58 | 6.82 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
| 12 | KITCHEN_WALL_EAST | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
| 13 | KITCHEN_WALL_EAST_DOOR | 0 | 68.93 | 70.04 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
| 14 | KITCHEN_WALL_WEST | 0 | 68.93 | 51.32 | 3.05 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
| 15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
| 16 | KITCHEN_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
| 17 | KITCHEN_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
| 18 | KITCHEN_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 3.05 | 34.94 | 9.69 | 0.00 | 0 | No | No |
| 19 | ATTIC-FLOOR-DINNING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
| 20 | ATTIC-FLOOR-KITCHEN | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
| 21 | SOUTH-ROOF | 0 | 129.19 | 59.48 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
| 22 | NORTH-ROOF | 0 | 129.19 | 77.58 | 6.82 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
| 23 | WEST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
| 24 | EAST-ROOF | 0 | 448.99 | 90.43 | 3.77 | 0 | 1.88 | 0.00 | 22.61 | -999.00 | 0 | No | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | DINING_INFILTRATION | INFIL_SCH_PNNL | DINING | 371.75 | 280.1 | 9.637E-002 | 2.592E-004 | 5.696E-004 | 0.306 | 0.000 | 0.000 | 0.224 | 0.000 |
| 2 | DINING_DOOR_INFILTRATION | VESTIBULE_DOOR_INFIL_SCH | DINING | 371.75 | 280.1 | 0.390 | 1.049E-003 | 2.304E-003 | 1.238 | 1.000 | 0.000 | 0.000 | 0.000 |
| 3 | KITCHEN_INFILTRATION | INFIL_SCH_PNNL | KITCHEN | 139.41 | 7.5 | 6.067E-002 | 4.352E-004 | 5.593E-004 | 0.514 | 0.000 | 0.000 | 0.224 | 0.000 |
| 4 | ATTIC_INFILTRATION | ALWAYS_ON | ATTIC | 511.15 | 0.0 | 0.238 | 4.652E-004 | 4.176E-004 | 1.000 | 1.000 | 0.000 | 0.000 | 0.000 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | DINING | Mixing/Well-Stirred |
| 2 | KITCHEN | Mixing/Well-Stirred |
| 3 | ATTIC | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.2500 |
| 2 | Zone DINING | 1.2500 |
| 3 | Zone KITCHEN | 1.2500 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.1500 |
| 2 | Zone DINING | 1.1500 |
| 3 | Zone KITCHEN | 1.1500 |
| Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
| 1 | DINING | Cooling | 47058.33818 | 54117.08891 | 3.45259 | 3.97048 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 32.10000 | 1.41196E-002 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
| 2 | DINING | Heating | 13553.90392 | 16942.37990 | 0.99383 | 1.33138 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | -10.70000 | 1.50390E-003 | 371.74807 | 280.14173 | 1.33138 | 0.00000 |
| 3 | KITCHEN | Cooling | 20864.03781 | 23993.64348 | 1.53028 | 1.75983 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 31.43400 | 1.41184E-002 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
| 4 | KITCHEN | Heating | 2056.19698 | 2570.24622 | 0.15076 | 1.21700 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | -10.70000 | 1.50390E-003 | 139.40524 | 7.52790 | 1.21700 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
| 1 | PSZ-AC_1:1 | Cooling | Sensible | 66348.57 | 3.97048 | 3.97048 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 2 | PSZ-AC_1:1 | Heating | Sensible | 68933.72 | 1.33138 | 1.33138 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| 3 | PSZ-AC_2:2 | Cooling | Sensible | 31620.08 | 1.75983 | 1.75983 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 4 | PSZ-AC_2:2 | Heating | Sensible | 60068.00 | 1.21700 | 1.21700 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DINING DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.97048 |
| 2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | KITCHEN DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.75983 |
| 3 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.97048 |
| 4 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.97048 |
| 5 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.97048 |
| 6 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.97048 |
| 7 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.97048 |
| 8 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.97048 |
| 9 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
| 10 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 11 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.75983 |
| 12 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.75983 |
| 13 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.75983 |
| 14 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.75983 |
| 15 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.75983 |
| 16 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.75983 |
| 17 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
| 18 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 19 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.97048 |
| 20 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.75983 |
| 21 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.97048 |
| 22 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.33138 |
| 23 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.97048 |
| 24 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ FAN | Design Electric Power Consumption [W] | 6440.61281 |
| 25 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.97048 |
| 26 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.97048 |
| 27 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.97048 |
| 28 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.97048 |
| 29 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.97048 |
| 30 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.98524 |
| 31 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.64699 |
| 32 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 98596.50000 |
| 33 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 49298.25000 |
| 34 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
| 35 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
| 36 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 98596.50000 |
| 37 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 104398.02322 |
| 38 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 32.11000 |
| 39 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 40 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 104398.02322 |
| 41 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.75983 |
| 42 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.21700 |
| 43 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.75983 |
| 44 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ FAN | Design Electric Power Consumption [W] | 2924.82808 |
| 45 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.75983 |
| 46 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.75983 |
| 47 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.75983 |
| 48 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.75983 |
| 49 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.75983 |
| 50 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.87991 |
| 51 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.17322 |
| 52 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 43700.70000 |
| 53 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21850.35000 |
| 54 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
| 55 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
| 56 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 43700.70000 |
| 57 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 67606.20721 |
| 58 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 30.11000 |
| 59 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 60 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 67606.20721 |
| 61 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 1.39850E-004 |
| 62 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 1.67820E-002 |
| 63 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 1.39850E-004 |
| 64 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 17.86434 |
| 65 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 1.39850E-004 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 95774.4 | 11.03 | 10.98 | |||
| 2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 42449.9 | 10.76 | 10.71 |
| Zone Name | # Surfaces | |
| 1 | DINING | 10 |
| 2 | KITCHEN | 8 |
| 3 | ATTIC | 6 |
| Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
| 1 | DINING_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 30.58 | 50.13 | 30.58 | 90.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 2 | DINING_WALL_EAST_WINDOW | Window | DINING_WALL_EAST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_EAST_0.39 | N/A | 3.241 | No | 19.55 | 19.55 | 19.55 | 90.00 | 90.00 | 15.24 | 1.28 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 3 | DINING_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 41.86 | 68.93 | 41.86 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 4 | DINING_WALL_SOUTH_WINDOW | Window | DINING_WALL_SOUTH | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_SOUTH_0.39 | N/A | 3.241 | No | 27.07 | 27.07 | 27.07 | 180.00 | 90.00 | 21.10 | 1.28 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 5 | DINING_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 30.58 | 50.13 | 30.58 | 270.00 | 90.00 | 16.44 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 6 | DINING_WALL_WEST_WINDOW | Window | DINING_WALL_WEST | Window5 Detailed Fenestration | NONRESWINDOW_U_0.57_SHGC_WEST_0.39 | N/A | 3.241 | No | 19.55 | 19.55 | 19.55 | 270.00 | 90.00 | 15.24 | 1.28 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
| 7 | DINING_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 8 | DINING_FLOOR | Floor | CTF - ConductionTransferFunction | DINING_FLOOR_FFACTOR | 0.194 | 0.186 | 371.75 | 371.75 | 371.75 | 0.00 | 180.00 | 22.61 | 16.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 9 | DINING_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.384 | 0.358 | 371.75 | 371.75 | 371.75 | 180.00 | 0.00 | 22.61 | 16.44 | 0.00 | ATTIC-FLOOR-DINNING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 10 | DINING_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 743.50 | 743.50 | 743.50 | 0.00 | 90.00 | 743.50 | 1.00 | 0.00 | DINING_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 11 | KITCHEN_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 68.93 | 68.93 | 68.93 | 0.00 | 90.00 | 22.61 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 12 | KITCHEN_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 16.85 | 18.80 | 16.85 | 90.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 13 | KITCHEN_WALL_EAST_DOOR | Door | KITCHEN_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 9.815 | 9.815 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
| 14 | KITCHEN_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.787 | 0.704 | 18.80 | 18.80 | 18.80 | 270.00 | 90.00 | 6.17 | 3.05 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 15 | DINING_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 68.93 | 68.93 | 68.93 | 180.00 | 90.00 | 22.61 | 3.05 | 0.00 | DINING_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
| 16 | KITCHEN_FLOOR | Floor | CTF - ConductionTransferFunction | KITCHEN_FLOOR_FFACTOR | 0.333 | 0.308 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 17 | KITCHEN_CEILING | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.384 | 0.358 | 139.41 | 139.41 | 139.41 | 180.00 | 0.00 | 22.61 | 6.17 | 0.00 | ATTIC-FLOOR-KITCHEN | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
| 18 | KITCHEN_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 278.81 | 278.81 | 278.81 | 0.00 | 90.00 | 278.81 | 1.00 | 0.00 | KITCHEN_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
| 19 | ATTIC-FLOOR-DINNING | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.384 | 0.351 | 371.75 | 371.75 | 371.75 | 180.00 | 180.00 | 22.61 | 16.44 | 0.00 | DINING_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 20 | ATTIC-FLOOR-KITCHEN | Floor | CTF - ConductionTransferFunction | NONRES_ROOF_FLOOR | 0.384 | 0.351 | 139.41 | 139.41 | 139.41 | 0.00 | 180.00 | 22.61 | 6.17 | 0.00 | KITCHEN_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
| 21 | SOUTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 180.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
| 22 | NORTH-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 60.26 | 60.26 | 60.26 | 0.00 | 45.00 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 0.15 | 0.85 | 0.15 | 0.85 | 3 | ||
| 23 | WEST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 270.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 | ||
| 24 | EAST-ROOF | Roof | CTF - ConductionTransferFunction | ATTICROOFDECK | 4.706 | 2.494 | 224.50 | 224.50 | 224.50 | 90.00 | 18.44 | 12.50 | 22.61 | 0.00 | ExternalEnvironment | DOE-2 | ASHRAETARP | SunExposed | WindExposed | 2.57E-002 | 0.97 | 2.57E-002 | 0.97 | 4 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
| Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
| 1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | Yes | InputFile | 03/12 | 11/05 |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | DINING | RunPeriod: RUNPERIOD 1 | 0.1092246385 | 0.4958680819 | Pass | Pass | 0.2437207768 | 0.7357374250 | Pass | Pass |
| 2 | KITCHEN | RunPeriod: RUNPERIOD 1 | 5.5569518115E-002 | 0.3372289616 | Pass | Pass | 4.4556436372E-002 | 0.1866389096 | Pass | Pass |
| 3 | ATTIC | RunPeriod: RUNPERIOD 1 | 0.2359248177 | 0.1764267102 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Heat Emission by Components| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [GJ] | 1007.82 | 100.47 | 1460.37 | 99.58 | 1021.83 | 3690.08 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
SizingPeriod:DesignDay| Maximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
| NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -10.70 | 0.00 | -10.70 | Wetbulb [C] | 7.50 | 320.00 |
| NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 32.10 | 7.40 | 23.10 | Wetbulb [C] | 5.60 | 230.00 |
| Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
| Jan | 172.00 | 59 | |||
| Feb | 49.00 | 37 | |||
| Mar | 40.00 | 38 | |||
| Apr | 70.00 | 48 | |||
| May | 70.00 | 36 | |||
| Jun | 25.00 | 15 | |||
| Jul | 64.00 | 20 | |||
| Aug | 2.00 | 4 | |||
| Sep | 73.00 | 32 | |||
| Oct | 7.00 | 8 | |||
| Nov | 88.00 | 34 | |||
| Dec | 62.00 | 39 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Opaque Exterior| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| DINING_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 50.13 | 30.58 | 90.00 | 90.00 | E |
| DINING_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 68.93 | 41.86 | 180.00 | 90.00 | S |
| DINING_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 50.13 | 30.58 | 270.00 | 90.00 | W |
| DINING_FLOOR | DINING_FLOOR_FFACTOR | 1.00 | 0.188 | 0.194 | 371.75 | 371.75 | 0.00 | 180.00 | |
| KITCHEN_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 68.93 | 68.93 | 0.00 | 90.00 | N |
| KITCHEN_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 18.80 | 16.85 | 90.00 | 90.00 | E |
| KITCHEN_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 0.704 | 0.787 | 18.80 | 18.80 | 270.00 | 90.00 | W |
| KITCHEN_FLOOR | KITCHEN_FLOOR_FFACTOR | 1.00 | 0.316 | 0.333 | 139.41 | 139.41 | 0.00 | 180.00 | |
| SOUTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 180.00 | 45.00 | |
| NORTH-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 60.26 | 60.26 | 0.00 | 45.00 | |
| WEST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 270.00 | 18.44 | |
| EAST-ROOF | ATTICROOFDECK | 0.30 | 2.858 | 4.706 | 224.50 | 224.50 | 90.00 | 18.44 |
| Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| DINING_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 0.00 | 90.00 | N |
| DINING_CEILING | NONRES_ROOF | 0.30 | 0.348 | 0.384 | 371.75 | 371.75 | 180.00 | 0.00 | |
| DINING_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 68.93 | 68.93 | 180.00 | 90.00 | S |
| KITCHEN_CEILING | NONRES_ROOF | 0.30 | 0.348 | 0.384 | 139.41 | 139.41 | 180.00 | 0.00 | |
| ATTIC-FLOOR-DINNING | NONRES_ROOF_FLOOR | 0.30 | 0.348 | 0.384 | 371.75 | 371.75 | 180.00 | 180.00 | |
| ATTIC-FLOOR-KITCHEN | NONRES_ROOF_FLOOR | 0.30 | 0.348 | 0.384 | 139.41 | 139.41 | 0.00 | 180.00 | |
| DINING_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 743.50 | 0.00 | 90.00 | N | ||
| KITCHEN_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 278.81 | 0.00 | 90.00 | N |
| Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| DINING_WALL_EAST_WINDOW | NONRESWINDOW_U_0.57_SHGC_EAST_0.39 | 19.55 | 0.00 | 0.00 | 19.55 | 19.55 | 3.241 | 0.391 | 0.431 | No | DINING_WALL_EAST | 90.00 | 90.00 | E | |||||||
| DINING_WALL_SOUTH_WINDOW | NONRESWINDOW_U_0.57_SHGC_SOUTH_0.39 | 27.07 | 0.00 | 0.00 | 27.07 | 27.07 | 3.241 | 0.391 | 0.431 | No | DINING_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
| DINING_WALL_WEST_WINDOW | NONRESWINDOW_U_0.57_SHGC_WEST_0.39 | 19.55 | 0.00 | 0.00 | 19.55 | 19.55 | 3.241 | 0.391 | 0.431 | No | DINING_WALL_WEST | 270.00 | 90.00 | W | |||||||
| Total or Average | 66.16 | 3.241 | 0.391 | 0.431 | |||||||||||||||||
| North Total or Average | 0.00 | - | - | - | |||||||||||||||||
| Non-North Total or Average | 66.16 | 3.241 | 0.391 | 0.431 |
| Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| KITCHEN_WALL_EAST_DOOR | SWINGING DOOR_CON | 3.975 | 9.815 | 1.95 | KITCHEN_WALL_EAST |
| Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| DINING_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
| DINING_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
| DINING_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
| DINING_LIGHTS | DINING | DINING | GENERAL | 20.6319 | 371.75 | 7669.88 | LightsWired | LTG_SCH_DINING | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 139.55 |
| KITCHEN_LIGHTS | KITCHEN | KITCHEN | GENERAL | 11.3949 | 139.41 | 1588.51 | LightsWired | LTG_SCH_KITCHEN | 97.50 | 168.00 | 96.93 | 0.0000 | Y | 28.90 |
| Interior Lighting Total | 18.1127 | 511.15 | 9258.39 | 168.45 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
| EXTERIOR_LIGHTS | 4578.48 | AstronomicalClock | - | 83.64 | 83.64 | 71.89 | |
| Exterior Lighting Total | 4578.48 | 71.89 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Central Plant| Type | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
| PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 98596.50 | 69124.03 | 29472.47 | 0.70 | 3.50 | |||
| PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 43700.70 | 30637.69 | 13063.01 | 0.70 | 3.40 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| PSZ-AC_1:1 COOLING COIL | 95774.4 | 11.03 | 10.98 | ||||
| PSZ-AC_2:2 COOLING COIL | 42449.9 | 10.76 | 10.71 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
| PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
| PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
| PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 104398.02 | 0.79 | |
| PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 67606.21 | 0.79 |
| Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| DINING EXHAUST FAN | Fan:ZoneExhaust | 1.00 | 0.00 | 1.33 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| KITCHEN EXHAUST FAN | Fan:ZoneExhaust | 0.39 | 0.00 | 2.55 | 0.00 | 0.00 | 1.00 | 0.00 | General | ||
| PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 0.60 | 966.87 | 3.97 | 6440.61 | 1622.12 | 1.00 | 1.19 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
| PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 0.58 | 966.87 | 1.76 | 2924.83 | 1662.00 | 1.00 | 1.24 | General | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 |
| Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
| SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 29891.00 | 0.000140 | 17.86 | 127739.32 | 0.30 | General |
| Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
| SWH BOOSTER G WATER HEATER | WaterHeater:Mixed | 0.02 | 8000.00 | 0.80 | 0.98 | 0.90 |
| SWHSYS1 WATER HEATER | WaterHeater:Mixed | 0.76 | 58614.21 | 0.81 | 14.75 | 0.47 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Zone Sensible Cooling| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| DINING | 47058.34 | 54117.09 | 145.57 | 3.453 | 3.970 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 23.99 | 0.01042 | 32.10 | 0.01412 | 1.331 | 0.00 |
| KITCHEN | 20864.04 | 23993.64 | 172.11 | 1.530 | 1.760 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 26.00 | 25.98 | 0.01009 | 31.43 | 0.01412 | 1.217 | 0.00 |
| Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
| DINING | 13553.90 | 16942.38 | 45.57 | 0.994 | 1.331 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:50:00 | 21.00 | 21.00 | 0.00773 | -10.70 | 0.00150 | 1.331 | 0.00 |
| KITCHEN | 2056.20 | 2570.25 | 18.44 | 0.151 | 1.217 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 23:30:00 | 19.00 | 19.00 | 0.00669 | -10.70 | 0.00150 | 1.217 | 0.00 |
| Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| PSZ-AC_1:1 | 3.97 | 3.97 | 1.33 | 1.33 | 3.9705 | 3.9705 | 3.9705 | 1.0000 | 1.0000 |
| PSZ-AC_2:2 | 1.76 | 1.76 | 1.22 | 1.22 | 1.7598 | 1.7598 | 1.7598 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
| PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 98596.500 | 69124.034 | 3.970480 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 49298.25 | 32373.57 | 2.646987 | 26.71 | 19.82 | 0.01166192 | 11.58 | 11.58 | 0.00850000 | 32.10 | 0.01411964 | 23.13 | 50.2979 | 23.99 | 0.01042205 | 55.9493 | 47058.34 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 104398.023 | 104398.023 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 104398.02 | 104398.02 | 3.970481 | 10.37 | 7.94 | 0.00564070 | 32.11 | 18.73 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 33.5319 | 21.00 | 0.00772763 | 49.9573 | 13552.96 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 43700.700 | 30637.687 | 1.759830 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | 21850.35 | 13626.19 | 1.173220 | 29.75 | 21.62 | 0.01287479 | 13.55 | 12.40 | 0.00850000 | 31.43 | 0.01411844 | 22.95 | 103.7318 | 25.98 | 0.01008655 | 48.0929 | 20864.04 | 0.00 | -999.00 | -999.00 |
| PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 67606.207 | 67606.207 | -999.0 | -999.0 | -999.000 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | 67606.21 | 67606.21 | 1.759827 | -1.65 | -1.94 | 0.00310863 | 30.11 | 18.07 | 0.00800000 | -10.70 | 0.00150390 | -10.70 | 69.1546 | 19.00 | 0.00670641 | 49.1552 | 1111.46 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
| PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 98596.500 | 69124.034 | 3.970480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.5189 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.970481 | 4.77885127 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | Sensible | 49298.25 | 32373.57 | 1.0000 | 3.18589987 | 2.646987 | 26.71 | 19.82 | 0.01166192 | 56579.5 | 11.58 | 11.58 | 0.00850000 | 33072.9 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 49298.25 | 32.10 | 0.01411964 | 23.13 | 1.33137743 | 50.2979 | 23.98 | 0.01042205 | 23.99 | 0.01042205 | 55.9493 | 47058.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | DINING | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 104398.023 | 104398.023 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ FAN | Fan:SystemModel | 3.970481 | 4.77885127 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 104398.02 | 104398.02 | 1.0000 | 4.77885127 | 3.970481 | 10.37 | 7.94 | 0.00564070 | 24635.8 | 32.11 | 18.73 | 0.00800000 | 52750.5 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 104398.02 | -10.70 | 0.00150390 | -10.70 | 1.33137743 | 33.5319 | 21.00 | 0.00772763 | 21.00 | 0.00772763 | 49.9573 | 13552.96 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 43700.700 | 30637.687 | 1.759830 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1028.7736 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.759827 | 2.11811905 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 12:30:00 | Sensible | 21850.35 | 13626.19 | 1.0000 | 1.41208170 | 1.173220 | 29.75 | 21.62 | 0.01287479 | 62800.0 | 13.55 | 12.40 | 0.00850000 | 35084.3 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21850.35 | 31.43 | 0.01411844 | 22.95 | 1.21700195 | 103.7318 | 25.96 | 0.01008655 | 25.98 | 0.01008655 | 48.0929 | 20864.04 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
| PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | KITCHEN | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 67606.207 | 67606.207 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ FAN | Fan:SystemModel | 1.759827 | 2.11811905 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:20:00 | Sensible | 67606.21 | 67606.21 | 1.0000 | 2.11811905 | 1.759827 | -1.65 | -1.94 | 0.00310863 | 6103.2 | 30.11 | 18.07 | 0.00800000 | 50711.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 67606.21 | -10.70 | 0.00150390 | -10.70 | 1.21700195 | 69.1546 | 18.63 | 0.00670641 | 19.00 | 0.00670641 | 49.1552 | 1111.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| DINING | 4020.50 | 4369.83 | 1500.83 |
| KITCHEN | 4946.00 | 6299.83 | 4214.00 |
| ATTIC | 0.00 | 0.00 | 0.00 |
| Facility | 4966.50 | 6541.00 | 4235.50 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| DINING | 26.83 | 20.00 | 0.00 | 0.00 |
| KITCHEN | 0.00 | 155.50 | 0.00 | 37.67 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 26.83 | 171.00 | 0.00 | 37.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| DINING | 118.20 | 280.14 | 1133.39 | 4.294 | 0.587 | 0.000 | 0.000 |
| KITCHEN | 3.18 | 7.53 | 425.02 | 10.479 | 0.041 | 0.000 | 0.000 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
| DINING | 118.20 | 280.14 | 1133.39 | 4.072 | 0.000 | 0.000 | 0.000 |
| KITCHEN | 3.18 | 7.53 | 425.02 | 9.967 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
| DINING | PSZ-AC_1:1 | 118.20 | 280.14 | 1133.39 | 371.75 | 1.3314 | 1.331 |
| KITCHEN | PSZ-AC_2:2 | 3.18 | 7.53 | 425.02 | 139.41 | 0.1826 | 0.112 |
| Total Facility | 121.38 | 287.67 | 1558.40 | 511.15 | 1.5140 | 1.443 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| DINING | 35357161.11 | 0.00 | 35357161.11 | 4828317.45 | 40185478.55 | 41986318.57 | 1437.33 | 7322.67 | 0.00 | 290.09 |
| KITCHEN | 32459992.18 | 0.00 | 32459992.18 | 199614.80 | 32659606.99 | 38379373.44 | 1433.03 | 7301.43 | 25.54 | 516.39 |
| Total Facility | 67817153.29 | 0.00 | 67817153.29 | 5027932.25 | 72845085.54 | 80365692.01 | 1448.43 | 7323.82 | 25.54 | 609.69 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| DINING | 1.3315 | 0.0000 | 1.3315 | 0.1820 | 1.5135 | 1.3314 | 0.00 | 7187.00 | 0.00 |
| KITCHEN | 1.2170 | 0.0000 | 1.2170 | 0.0048 | 1.2218 | 1.2170 | 0.00 | 7187.00 | 0.00 |
| Total Facility | 2.5485 | 0.0000 | 2.5485 | 0.1868 | 2.7353 | 2.5484 | 0.00 | 7187.00 | 0.00 |
| Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| PSZ-AC_1:1 | 51219796.51 | 0.00 | 51219796.51 | 41986318.57 | 1420.75 | 1.67 | 7337.58 | 290.09 |
| PSZ-AC_2:2 | 47022871.63 | 0.00 | 47022871.63 | 38379373.44 | 1414.86 | 0.82 | 7344.31 | 516.39 |
| Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| PSZ-AC_1:1 | 1.9289 | 0.0000 | 1.9289 | 1.3314 | 0.00 | 0.00 | 7187.00 |
| PSZ-AC_2:2 | 1.7630 | 0.0000 | 1.7630 | 1.2170 | 0.00 | 0.00 | 7187.00 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| PSZ-AC_1:1 | 0.00 | 154.74 | 0.00 | 7322.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| PSZ-AC_2:2 | 0.00 | 0.00 | 0.00 | 7703.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
| PSZ-AC_1:1 | 0.0000 | 0.0000 | 0.0000 | 1.9289 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| PSZ-AC_2:2 | 0.0000 | 0.0000 | 0.0000 | 1.7630 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Surfaces by Class| Total | Outdoors | |
| Wall | 8 | 6 |
| Floor | 4 | 2 |
| Roof | 6 | 4 |
| Internal Mass | 2 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 3 | 3 |
| Door | 1 | 1 |
| Glass Door | 0 | 0 |
| Shading | 0 | 0 |
| Overhang | 0 | 0 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 2 |
| Conditioned Zones | 2 |
| Unconditioned Zones | 1 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 374 |
| Defaulted Fields | 277 |
| Fields with Defaults | 884 |
| Autosized Fields | 41 |
| Autosizable Fields | 97 |
| Autocalculated Fields | 30 |
| Autocalculatable Fields | 60 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Annual and Peak Values - Electricity| Electricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 1143.81 | 9667.66 | 06-FEB-01:10 | 80689.74 | 19-JUN-12:00 |
| Electricity:Building | 630.98 | 4348.05 | 01-JAN-01:10 | 35004.91 | 02-JAN-11:10 |
| Electricity:Zone:DINING | 264.66 | 1630.49 | 01-JAN-01:10 | 13894.77 | 02-JAN-11:10 |
| Electricity:SpaceType:GENERAL | 624.05 | 4211.77 | 01-JAN-01:10 | 32861.81 | 02-JAN-11:10 |
| InteriorLights:Electricity | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
| InteriorLights:Electricity:Zone:DINING | 139.55 | 1150.48 | 01-JAN-01:10 | 6902.89 | 02-JAN-10:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
| LightsWired:InteriorLights:Electricity | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
| LightsWired:InteriorLights:Electricity:Zone:DINING | 139.55 | 1150.48 | 01-JAN-01:10 | 6902.89 | 02-JAN-10:10 |
| LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 168.45 | 1388.76 | 01-JAN-01:10 | 8332.55 | 02-JAN-10:10 |
| Electricity:Zone:KITCHEN | 366.33 | 2717.56 | 01-JAN-01:10 | 21110.14 | 02-JAN-11:10 |
| InteriorLights:Electricity:Zone:KITCHEN | 28.90 | 238.28 | 01-JAN-01:10 | 1429.66 | 02-JAN-10:10 |
| LightsWired:InteriorLights:Electricity:Zone:KITCHEN | 28.90 | 238.28 | 01-JAN-01:10 | 1429.66 | 02-JAN-10:10 |
| InteriorEquipment:Electricity | 455.60 | 2823.01 | 01-JAN-01:10 | 24529.26 | 01-JAN-11:10 |
| InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 455.60 | 2823.01 | 01-JAN-01:10 | 24529.26 | 01-JAN-11:10 |
| Cooking:InteriorEquipment:Electricity | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
| Cooking:InteriorEquipment:Electricity:Zone:DINING | 125.11 | 480.00 | 01-JAN-01:10 | 6991.88 | 01-JAN-11:10 |
| Cooking:InteriorEquipment:Electricity:SpaceType:GENERAL | 417.03 | 1600.01 | 01-JAN-01:10 | 23306.26 | 01-JAN-11:10 |
| InteriorEquipment:Electricity:Zone:KITCHEN | 330.49 | 2343.01 | 01-JAN-01:10 | 17537.38 | 01-JAN-11:10 |
| Cooking:InteriorEquipment:Electricity:Zone:KITCHEN | 291.92 | 1120.01 | 01-JAN-01:10 | 16314.38 | 01-JAN-11:10 |
| ReachInFreezer:InteriorEquipment:Electricity | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
| ReachInFreezer:InteriorEquipment:Electricity:Zone:KITCHEN | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
| ReachInFreezer:InteriorEquipment:Electricity:SpaceType:GENERAL | 15.55 | 493.00 | 01-JAN-00:10 | 493.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity:Zone:KITCHEN | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| ReachInRefrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 23.02 | 730.00 | 01-JAN-00:10 | 730.00 | 01-JAN-00:10 |
| Refrigeration:Electricity | 36.37 | 595.55 | 02-JAN-23:30 | 2780.19 | 18-MAY-10:10 |
| Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
| General:Refrigeration:Electricity | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
| General:Refrigeration:Electricity:Zone:KITCHEN | 6.93 | 85.78 | 01-JAN-23:30 | 2143.10 | 02-JAN-11:10 |
| Electricity:Plant | 29.88 | 527.64 | 31-JAN-23:10 | 1668.99 | 28-JUL-03:20 |
| LowTempRefrigeration:Refrigeration:Electricity | 11.07 | 0.00 | 01-JAN-11:10 | 1031.89 | 28-JUL-03:20 |
| MedTempRefrigeration:Refrigeration:Electricity | 18.36 | 509.05 | 07-FEB-06:00 | 637.09 | 27-MAR-12:10 |
| ElectricityPurchased:Facility | 1143.81 | 9667.66 | 06-FEB-01:10 | 80689.74 | 19-JUN-12:00 |
| ElectricityPurchased:Plant | 1143.81 | 9667.66 | 06-FEB-01:10 | 80689.74 | 19-JUN-12:00 |
| Cogeneration:ElectricityPurchased | 1143.81 | 9667.66 | 06-FEB-01:10 | 80689.74 | 19-JUN-12:00 |
| General:Cogeneration:ElectricityPurchased | 1143.81 | 9667.66 | 06-FEB-01:10 | 80689.74 | 19-JUN-12:00 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 1143.81 | 9667.66 | 06-FEB-01:10 | 80689.74 | 19-JUN-12:00 |
| ElectricityNet:Plant | 1143.81 | 9667.66 | 06-FEB-01:10 | 80689.74 | 19-JUN-12:00 |
| Cogeneration:ElectricityNet | 1143.81 | 9667.66 | 06-FEB-01:10 | 80689.74 | 19-JUN-12:00 |
| General:Cogeneration:ElectricityNet | 1143.81 | 9667.66 | 06-FEB-01:10 | 80689.74 | 19-JUN-12:00 |
| Electricity:HVAC | 411.06 | 0.00 | 01-JAN-01:10 | 48220.38 | 19-JUN-12:00 |
| Fans:Electricity | 248.64 | 0.00 | 01-JAN-01:10 | 9365.44 | 02-JAN-00:20 |
| General:Fans:Electricity | 248.64 | 0.00 | 01-JAN-01:10 | 9365.44 | 02-JAN-00:20 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 162.42 | 0.00 | 01-JAN-00:10 | 38854.94 | 19-JUN-12:00 |
| General:Cooling:Electricity | 162.42 | 0.00 | 01-JAN-00:10 | 38854.94 | 19-JUN-12:00 |
| ExteriorLights:Electricity | 71.89 | 0.00 | 01-JAN-07:30 | 4578.48 | 01-JAN-00:10 |
| General:ExteriorLights:Electricity | 71.89 | 0.00 | 01-JAN-07:30 | 4578.48 | 01-JAN-00:10 |
| Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 04-JAN-00:10 |
| General:Pumps:Electricity | 0.45 | 0.00 | 01-JAN-01:10 | 17.86 | 04-JAN-00:10 |
| Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 1223.20 | 1868.52 | 27-JUL-00:40 | 159391.26 | 06-FEB-07:10 |
| NaturalGas:Building | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
| NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
| NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
| InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
| InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
| InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
| Cooking:InteriorEquipment:NaturalGas | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
| Cooking:InteriorEquipment:NaturalGas:Zone:KITCHEN | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
| Cooking:InteriorEquipment:NaturalGas:SpaceType:GENERAL | 469.79 | 1810.25 | 01-JAN-01:10 | 26248.62 | 01-JAN-11:10 |
| NaturalGas:HVAC | 325.10 | 0.00 | 01-JAN-01:10 | 131732.52 | 06-FEB-04:50 |
| Heating:NaturalGas | 325.10 | 0.00 | 01-JAN-01:10 | 131732.52 | 06-FEB-04:50 |
| General:Heating:NaturalGas | 325.10 | 0.00 | 01-JAN-01:10 | 131732.52 | 06-FEB-04:50 |
| NaturalGas:Plant | 428.31 | 58.26 | 23-JUN-03:10 | 28750.10 | 09-FEB-07:40 |
| WaterSystems:NaturalGas | 428.31 | 58.26 | 23-JUN-03:10 | 28750.10 | 09-FEB-07:40 |
| Water Heater:WaterSystems:NaturalGas | 428.31 | 58.26 | 23-JUN-03:10 | 28750.10 | 09-FEB-07:40 |
| Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-19:30 |
| Water:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-19:30 |
| WaterSystems:Water | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-19:30 |
| Water Heater:WaterSystems:Water | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 31-MAY-06:50 |
| MainsWater:Facility | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-19:30 |
| MainsWater:Plant | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-19:30 |
| WaterSystems:MainsWater | 2201.28 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-19:30 |
| Water Heater:WaterSystems:MainsWater | 825.43 | 0.00 | 01-JAN-01:10 | 0.00 | 31-MAY-06:50 |
| WaterUse:WaterSystems:Water | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-19:30 |
| WaterUse:WaterSystems:MainsWater | 1375.86 | 0.00 | 01-JAN-01:10 | 0.00 | 02-JAN-19:30 |
| Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 1965.55 | 2930.79 | 06-FEB-01:10 | 210691.35 | 04-AUG-12:00 |
| EnergyTransfer:Building | 769.77 | 1465.40 | 06-FEB-01:10 | 56098.44 | 19-JUN-11:10 |
| EnergyTransfer:Zone:KITCHEN | 420.04 | 1465.40 | 06-FEB-01:10 | 23667.51 | 05-AUG-11:00 |
| Refrigeration:EnergyTransfer | 140.15 | 2621.06 | 31-JAN-23:10 | 7834.84 | 18-MAY-10:40 |
| Refrigeration:EnergyTransfer:Zone:KITCHEN | 70.07 | 1310.53 | 31-JAN-23:10 | 3917.42 | 18-MAY-10:40 |
| General:Refrigeration:EnergyTransfer | 70.07 | 1310.53 | 31-JAN-23:10 | 3917.42 | 18-MAY-10:40 |
| General:Refrigeration:EnergyTransfer:Zone:KITCHEN | 70.07 | 1310.53 | 31-JAN-23:10 | 3917.42 | 18-MAY-10:40 |
| EnergyTransfer:Plant | 324.25 | 1465.40 | 06-FEB-01:10 | 20070.98 | 02-MAR-20:00 |
| LowTempRefrigeration:Refrigeration:EnergyTransfer | 12.10 | 0.00 | 01-JAN-11:10 | 1678.72 | 01-JAN-11:40 |
| MedTempRefrigeration:Refrigeration:EnergyTransfer | 57.98 | 1305.30 | 07-FEB-06:00 | 2238.70 | 27-MAR-12:10 |
| EnergyTransfer:Zone:DINING | 349.74 | 0.00 | 01-JAN-01:10 | 49607.74 | 02-JAN-05:00 |
| Heating:EnergyTransfer | 3.57 | 0.00 | 01-JAN-00:20 | 32951.98 | 06-FEB-04:10 |
| Heating:EnergyTransfer:Zone:DINING | 3.56 | 0.00 | 01-JAN-00:20 | 32951.98 | 06-FEB-04:10 |
| General:Heating:EnergyTransfer | 3.57 | 0.00 | 01-JAN-00:20 | 32951.98 | 06-FEB-04:10 |
| General:Heating:EnergyTransfer:Zone:DINING | 3.56 | 0.00 | 01-JAN-00:20 | 32951.98 | 06-FEB-04:10 |
| Cooling:EnergyTransfer | 696.13 | 0.00 | 01-JAN-01:10 | 53486.31 | 07-JUL-12:00 |
| Cooling:EnergyTransfer:Zone:DINING | 346.18 | 0.00 | 01-JAN-01:10 | 36072.19 | 19-JUN-12:00 |
| General:Cooling:EnergyTransfer | 696.13 | 0.00 | 01-JAN-01:10 | 53486.31 | 07-JUL-12:00 |
| General:Cooling:EnergyTransfer:Zone:DINING | 346.18 | 0.00 | 01-JAN-01:10 | 36072.19 | 19-JUN-12:00 |
| Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 1051.50 | 02-JAN-05:10 |
| General:Heating:EnergyTransfer:Zone:KITCHEN | 0.01 | 0.00 | 01-JAN-00:10 | 1051.50 | 02-JAN-05:10 |
| Cooling:EnergyTransfer:Zone:KITCHEN | 349.95 | 0.00 | 01-JAN-01:10 | 19750.09 | 05-AUG-11:00 |
| General:Cooling:EnergyTransfer:Zone:KITCHEN | 349.95 | 0.00 | 01-JAN-01:10 | 19750.09 | 05-AUG-11:00 |
| EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| PlantLoopHeatingDemand:Facility | 254.17 | 0.00 | 01-JAN-01:10 | 17731.95 | 09-FEB-07:40 |
| PlantLoopHeatingDemand:Plant | 254.17 | 0.00 | 01-JAN-01:10 | 17731.95 | 09-FEB-07:40 |
| WaterSystems:PlantLoopHeatingDemand | 254.17 | 0.00 | 01-JAN-01:10 | 17731.95 | 09-FEB-07:40 |
| General:WaterSystems:PlantLoopHeatingDemand | 254.17 | 0.00 | 01-JAN-01:10 | 17731.95 | 09-FEB-07:40 |
| EnergyTransfer:HVAC | 871.53 | 0.00 | 01-JAN-01:10 | 145496.58 | 04-AUG-12:00 |
| HeatingCoils:EnergyTransfer | 257.64 | 0.00 | 01-JAN-01:10 | 104398.02 | 01-JAN-04:30 |
| CoolingCoils:EnergyTransfer | 613.88 | 0.00 | 01-JAN-00:10 | 145496.58 | 04-AUG-12:00 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| WaterSystems:EnergyTransfer | 254.17 | 0.00 | 01-JAN-01:10 | 17731.95 | 09-FEB-07:40 |
| WaterUse:WaterSystems:EnergyTransfer | 254.17 | 0.00 | 01-JAN-01:10 | 17731.95 | 09-FEB-07:40 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
| DINING | 0.000 | 0.000 | 3.560 | -346.176 | 0.000 | 0.000 | 223.135 | 139.549 | 93.832 | 59.362 | 0.000 | 2.860 | 0.001 | 0.000 | -42.737 | 0.000 | -60.405 | -72.981 |
| KITCHEN | 0.000 | 0.000 | 0.007 | -349.946 | 0.000 | 0.000 | 5.860 | 28.902 | 293.083 | 0.000 | 0.000 | 0.027 | 25.304 | 0.000 | 0.000 | 0.000 | -3.237 | -0.000 |
| ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 3.789 | 34.385 | 0.000 | 0.000 | 0.000 | -38.174 | -0.000 |
| Total Facility | 0.000 | 0.000 | 3.567 | -696.122 | 0.000 | 0.000 | 228.995 | 168.451 | 386.915 | 59.362 | 0.000 | 6.676 | 59.690 | 0.000 | -42.737 | 0.000 | -101.816 | -72.982 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| DINING | 25-AUG-03:01 | 0.00 | 0.00 | 0.00 | -83270.50 | 0.00 | 0.00 | 0.00 | 1150.48 | 900.01 | 0.00 | 0.00 | 0.00 | 82851.33 | 0.00 | -1471.29 | 0.00 | -160.02 | 0.00 |
| KITCHEN | 07-OCT-03:01 | 0.00 | 0.00 | 0.00 | -64309.60 | 0.00 | 0.00 | 0.00 | 238.28 | 3668.14 | 0.00 | 0.00 | 0.00 | 60670.16 | 0.00 | -0.00 | 0.00 | -266.97 | 0.00 |
| ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 25-AUG-03:01 | 0.00 | 0.00 | 0.00 | -132009.08 | 0.00 | 0.00 | 0.00 | 1388.76 | 4568.15 | 0.00 | 0.00 | 268.57 | 127580.53 | 0.00 | -1471.29 | 0.00 | -325.63 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
| DINING | 03-JAN-04:01 | 0.00 | 0.00 | 71679.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1150.48 | 900.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3004.94 | 0.00 | -1355.11 | -69370.18 |
| KITCHEN | 23-MAR-04:03 | 0.00 | 0.00 | 9182.92 | 0.00 | 0.00 | 0.00 | 26.01 | 317.70 | 7108.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -33.11 | -16601.76 |
| ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 03-JAN-04:01 | 0.00 | 0.00 | 71679.74 | 0.00 | 0.00 | 0.00 | 0.00 | 1388.76 | 4568.15 | 0.00 | 0.00 | 618.68 | 0.00 | 0.00 | -3004.94 | 0.00 | -2300.05 | -72950.32 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| PSZ-AC_1:1 | 3.9705 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.9705 | 0.3353 | 1.0000 | Not calculated | 1.3314 | 0.3353 | ||
| PSZ-AC_2:2 | 1.7598 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.7598 | 0.1038 | 1.0000 | Not calculated | 0.1826 | 0.1038 |
| Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| PSZ-AC_1:1 | 3.9705 | 0.0000 | 280.1417 | 1.0000 | Calculated from schedules | 1.3314 | 3.9705 | 1.0000 | 1.0000 | Not calculated | 1.3314 | 0.3353 | ||
| PSZ-AC_2:2 | 1.7598 | 0.0000 | 7.5279 | 1.0000 | Calculated from schedules | 0.1826 | 1.7598 | 0.1500 | 1.0000 | Not calculated | 0.1826 | 0.1038 |
| AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| DINING | PSZ-AC_1:1 | 0.000000 | 280.1417 | 0.003581 | 371.75 | 1.3314 | 1.0000 | 1.3314 | 1.000 | 1.3314 |
| KITCHEN | PSZ-AC_2:2 | 0.009440 | 7.5279 | 0.000800 | 139.41 | 0.1826 | 1.0000 | 0.1826 | 1.000 | 0.1826 |
| People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
| PSZ-AC_1:1 | 0.000000 | 280.14 | 0.003581 | 371.7481 | 1.3314 | 1.3314 | 1.3314 |
| PSZ-AC_2:2 | 0.009440 | 7.53 | 0.000800 | 139.4052 | 0.1826 | 0.1826 | 0.1826 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.9705 | 3.9705 | 3.9705 | No | 1.3314 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7598 | 1.7598 | 1.7598 | No | 0.1826 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| PSZ-AC_1:1 | 3.9705 | 3.9705 | 3.9705 | 3.9705 | 1.3314 | 1.0000 |
| PSZ-AC_2:2 | 1.7598 | 1.7598 | 1.7598 | 1.7598 | 0.1826 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| DINING | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.9705 | 3.9705 | 3.9705 | No | 1.3314 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| KITCHEN | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7598 | 1.7598 | 1.7598 | No | 0.1826 | 0.1500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
| PSZ-AC_1:1 | 3.9705 | 3.9705 | 3.9705 | 3.9705 | 1.3314 | 1.0000 |
| PSZ-AC_2:2 | 1.7598 | 1.7598 | 1.7598 | 1.7598 | 0.1826 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Sec1.1A-General Information| Data | |
| Weather File | RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 |
| Total gross floor area [m2] | 511.15 |
| Principal Heating Source | Natural Gas |
| Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
| DINING | 371.75 | 371.75 | 0.00 | 137.83 |
| KITCHEN | 139.41 | 139.41 | 0.00 | 137.83 |
| ATTIC | 511.15 | 0.00 | 511.15 | 0.00 |
| Totals | 511.15 | 511.15 | 0.00 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 37.67 |
| Number of hours not met | 37.67 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
| Heating -- General | 0.00 | 0.00 | 325.10 | 131732.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 162.42 | 38854.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- LightsWired | 168.45 | 8332.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- General | 71.89 | 4578.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- Cooking | 417.03 | 23306.26 | 469.79 | 26248.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ReachInFreezer | 15.55 | 493.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- ReachInRefrigerator | 23.02 | 730.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 248.64 | 9365.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- General | 0.45 | 17.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 0.00 | 0.00 | 428.31 | 28750.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- General | 6.93 | 2143.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- LowTempRefrigeration | 11.07 | 1031.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- MedTempRefrigeration | 18.36 | 637.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [GJ] | Total Energy Use [GJ] | |
| Electricity | 491.97 | 1143.81 |
| Natural Gas | 469.79 | 1223.20 |
| Additional | 0.00 | 0.00 |
| Total | 961.75 | 2367.01 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [GJ] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [MJ/m2] | |
| Interior Lighting (All) | 329.55 |
| Space Heating | 0.00 |
| Space Cooling | 317.76 |
| Fans (All) | 486.42 |
| Service Water Heating | 0.00 |
| Receptacle Equipment | 891.32 |
| Miscellaneous (All) | 2237.70 |
| Subtotal | 2237.70 |
| Natural Gas [MJ/m2] | |
| Space Heating | 636.02 |
| Service Water Heating | 837.93 |
| Miscellaneous (All) | 2393.01 |
| Subtotal | 2393.01 |
| Additional [MJ/m2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 7.12 |
| Space Heating | 13.73 |
| Space Cooling | 6.86 |
| Fans (All) | 10.50 |
| Service Water Heating | 18.09 |
| Receptacle Equipment | 39.10 |
| Miscellaneous | 4.59 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| LTG_SCH_DINING | 5084. | 8760. |
| LTG_SCH_KITCHEN | 5084. | 8760. |
| BLDG_EQUIP_SCH | 1440. | 8760. |
| REST_GAS_EQUIP_SCH | 1442. | 8760. |
| BLDG_OCC_SCH | 2960. | 7195. |
| INFIL_HALF_ON_SCH | 5292. | 8760. |
| INFIL_SCH_PNNL | 3559. | 8760. |
| DOOR_INFIL_SCH | 3274. | 6570. |
| VESTIBULE_DOOR_INFIL_SCH | 3177. | 6570. |
| BLDG_SWH_SCH | 2744. | 6935. |
| ALWAYS_ON | 8760. | 8760. |
| EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
| EXTERIOR_LGT_189_1 | 7300. | 8760. |
| ALWAYS_OFF | 0. | 0. |
| FAN_SCH | 8760. | 8760. |
| COOLINGCOILAVAILSCHED | 8760. | 8760. |
| MINOA_MOTORIZEDDAMPER_SCHED | 6935. | 6935. |
| MINOA_SCHED | 8760. | 8760. |
| WORK_EFF_SCH | 0. | 0. |
| KITCHEN WATER EQUIPMENT LATENT FRACT SCHED | 438. | 8760. |
| KITCHEN WATER EQUIPMENT SENSIBLE FRACT SCHED | 1752. | 8760. |
| KITCHEN_CASE:1_WALKINFREEZER_CASECREDITREDUXSCHED | 2774. | 8760. |
| WALKIN_OCC_LGHT_SCH_2 | 2785. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_A | 6935. | 6935. |
| EXTERIOR_LIGHTING_SCHEDULE_B | 8213. | 8760. |
| EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 6935. | 6935. |
| EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
| KITCHEN EXHAUST FAN BALANCED EXHAUST FRACTION SCHEDULE | 3814. | 7300. |
| SZ_SYSTEM_OA_MAX_FRAC_SCH | 6570. | 8760. |
| First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
| HTGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | January | 21.00 | 365 | 21.00 | 365 |
| CLGSETP_SCH_NO_OPTIMUM | DINING DUAL SP CONTROL | July | 24.00 | 365 | 24.00 | 365 |
| HTGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | January | 19.00 | 365 | 19.00 | 365 |
| CLGSETP_KITCHEN_SCH_NO_OPTIMUM | KITCHEN DUAL SP CONTROL | July | 26.00 | 365 | 26.00 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Heat Index Hours| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| DINING | 8507.00 | 252.00 | 1.00 | 0.00 | 0.00 |
| KITCHEN | 8096.00 | 611.00 | 53.00 | 0.00 | 0.00 |
| ATTIC | 7050.17 | 554.00 | 497.00 | 503.67 | 155.17 |
| Min | 7050.17 | 252.00 | 1.00 | 0.00 | 0.00 |
| Max | 8507.00 | 611.00 | 497.00 | 503.67 | 155.17 |
| Average | 7884.39 | 472.33 | 183.67 | 167.89 | 51.72 |
| Sum | 23653.17 | 1417.00 | 551.00 | 503.67 | 155.17 |
| Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
| DINING | 823617.67 | 595.00 | 9.33 | 0.00 | 0.00 |
| KITCHEN | 19046.33 | 186.67 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 823617.67 | 595.00 | 9.33 | 0.00 | 0.00 |
| Average | 280888.00 | 260.56 | 3.11 | 0.00 | 0.00 |
| Sum | 842664.00 | 781.67 | 9.33 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| DINING | 7322.83 | 1437.00 | 0.17 | 0.00 | 0.00 |
| KITCHEN | 5544.67 | 3214.00 | 1.33 | 0.00 | 0.00 |
| ATTIC | 6532.17 | 1352.33 | 309.67 | 241.33 | 324.50 |
| Min | 5544.67 | 1352.33 | 0.17 | 0.00 | 0.00 |
| Max | 7322.83 | 3214.00 | 309.67 | 241.33 | 324.50 |
| Average | 6466.56 | 2001.11 | 103.72 | 80.44 | 108.17 |
| Sum | 19399.67 | 6003.33 | 311.17 | 241.33 | 324.50 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| DINING | 709944.67 | 114275.00 | 2.33 | 0.00 | 0.00 |
| KITCHEN | 12111.67 | 7121.33 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 709944.67 | 114275.00 | 2.33 | 0.00 | 0.00 |
| Average | 240685.44 | 40465.44 | 0.78 | 0.00 | 0.00 |
| Sum | 722056.33 | 121396.33 | 2.33 | 0.00 | 0.00 |
| SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
| None |
| SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
| None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-07-03 12:20:43
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME ASHRAE901
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2022
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RESTAURANTSITDOWN
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PERFORMANCEPATHBASELINE
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
| January | 1.168 |
| February | -0.18 |
| March | 5.585 |
| April | 10.941 |
| May | 16.049 |
| June | 21.711 |
| July | 25.046 |
| August | 24.788 |
| September | 19.956 |
| October | 14.024 |
| November | 7.310 |
| December | 3.332 |
| Annual Sum or Average | 12.554 |
| Minimum of Months | -0.18 |
| Maximum of Months | 25.046 |
Report: ZoneCoolingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.150842E+11 | 43117.13 | 02-JAN-04:52 | -12.2 | -13.6 | 0.120696E+11 | 11770.56 | 24-JAN-12:00 | 12.20 | 11.57 |
| February | 0.137727E+11 | 48440.15 | 06-FEB-04:53 | -13.3 | -14.6 | 0.108783E+11 | 10741.00 | 11-FEB-19:10 | 4.32 | -0.3 |
| March | 0.214741E+11 | 27910.97 | 22-MAR-23:01 | -2.3 | -6.2 | 0.127411E+11 | 12937.85 | 03-MAR-12:00 | -2.3 | -6.2 |
| April | 0.247280E+11 | 49764.17 | 08-APR-03:01 | 15.40 | 12.61 | 0.133447E+11 | 14051.24 | 08-APR-18:30 | 15.00 | 12.77 |
| May | 0.307370E+11 | 63545.32 | 30-MAY-03:01 | 18.22 | 15.08 | 0.151759E+11 | 14050.96 | 06-MAY-18:19 | 18.22 | 15.08 |
| June | 0.380080E+11 | 69177.43 | 23-JUN-03:01 | 21.02 | 16.87 | 0.149947E+11 | 14052.24 | 24-JUN-18:00 | 22.20 | 22.20 |
| July | 0.440467E+11 | 69182.78 | 11-JUL-03:01 | 20.50 | 15.26 | 0.153261E+11 | 14053.63 | 08-JUL-18:00 | 20.50 | 15.26 |
| August | 0.463856E+11 | 83281.94 | 25-AUG-03:01 | 19.90 | 13.38 | 0.155211E+11 | 14053.57 | 05-AUG-18:00 | 19.90 | 13.38 |
| September | 0.375445E+11 | 78887.21 | 15-SEP-03:01 | 17.12 | 13.06 | 0.148583E+11 | 14052.66 | 16-SEP-18:00 | 18.90 | 15.21 |
| October | 0.329843E+11 | 67843.47 | 14-OCT-03:01 | 14.40 | 13.43 | 0.147914E+11 | 14052.89 | 21-OCT-18:00 | 16.70 | 14.59 |
| November | 0.228108E+11 | 29504.60 | 24-NOV-00:01 | -3.3 | -5.8 | 0.126227E+11 | 14051.66 | 04-NOV-18:49 | -3.3 | -5.8 |
| December | 0.186018E+11 | 33266.61 | 22-DEC-05:02 | -3.9 | -6.5 | 0.120625E+11 | 11279.25 | 19-DEC-12:00 | -3.9 | -6.5 |
| Annual Sum or Average | 0.346178E+12 | 0.164386E+12 | ||||||||
| Minimum of Months | 0.137727E+11 | 27910.97 | -13.3 | -14.6 | 0.108783E+11 | 10741.00 | -3.9 | -6.5 | ||
| Maximum of Months | 0.463856E+11 | 83281.94 | 21.02 | 16.87 | 0.155211E+11 | 14053.63 | 22.20 | 22.20 |
Report: ZoneCoolingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.275414E+11 | 42572.68 | 02-JAN-05:01 | -12.1 | -13.5 | 0.103954E+11 | 6874.23 | 24-JAN-11:00 | 12.20 | 11.93 |
| February | 0.242873E+11 | 40876.11 | 07-FEB-05:01 | -9.0 | -10.1 | 0.938499E+10 | 6836.02 | 01-FEB-11:00 | -9.0 | -10.1 |
| March | 0.284444E+11 | 35958.92 | 23-MAR-04:01 | -5.0 | -7.6 | 0.104210E+11 | 6902.51 | 03-MAR-11:00 | -5.0 | -7.6 |
| April | 0.275291E+11 | 52025.63 | 09-APR-03:01 | 11.70 | 11.35 | 0.101462E+11 | 6930.41 | 10-APR-10:30 | 21.65 | 13.68 |
| May | 0.285676E+11 | 61858.73 | 21-MAY-03:01 | 12.12 | 7.75 | 0.105708E+11 | 6930.44 | 18-MAY-10:00 | 12.12 | 7.75 |
| June | 0.296216E+11 | 58156.38 | 03-JUN-03:01 | 13.30 | 9.30 | 0.102573E+11 | 6939.45 | 19-JUN-10:50 | 35.63 | 23.79 |
| July | 0.322194E+11 | 44135.81 | 11-JUL-03:01 | 20.50 | 15.26 | 0.105955E+11 | 6949.84 | 20-JUL-10:50 | 28.22 | 25.09 |
| August | 0.326502E+11 | 49295.57 | 20-AUG-03:11 | 15.77 | 13.28 | 0.106029E+11 | 6964.26 | 04-AUG-10:50 | 15.77 | 13.28 |
| September | 0.303359E+11 | 60316.26 | 29-SEP-03:01 | 11.78 | 8.20 | 0.102499E+11 | 6930.44 | 08-SEP-10:00 | 11.78 | 8.20 |
| October | 0.306767E+11 | 64390.37 | 07-OCT-03:01 | 9.32 | 6.01 | 0.105454E+11 | 6930.44 | 16-OCT-10:00 | 17.80 | 15.39 |
| November | 0.290917E+11 | 55178.95 | 04-NOV-03:01 | 10.10 | 9.13 | 0.101093E+11 | 6930.38 | 10-NOV-11:00 | 15.00 | 13.29 |
| December | 0.289895E+11 | 36877.37 | 22-DEC-05:01 | -3.9 | -6.5 | 0.103938E+11 | 6850.68 | 26-DEC-11:00 | 9.40 | 5.22 |
| Annual Sum or Average | 0.349955E+12 | 0.123673E+12 | ||||||||
| Minimum of Months | 0.242873E+11 | 35958.92 | -12.1 | -13.5 | 0.938499E+10 | 6836.02 | -9.0 | -10.1 | ||
| Maximum of Months | 0.326502E+11 | 64390.37 | 20.50 | 15.26 | 0.106029E+11 | 6964.26 | 35.63 | 25.09 |
Report: ZoneCoolingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 | -11.5 | 0.00 | 0.00 | 01-JAN-00:10 | -9.6 | -11.5 |
| February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 | -4.2 | 0.00 | 0.00 | 01-FEB-00:10 | -1.1 | -4.2 |
| March | 0.00 | 0.00 | 01-MAR-00:02 | 5.52 | 4.35 | 0.00 | 0.00 | 01-MAR-00:10 | 5.52 | 4.35 |
| April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 | 4.90 | 0.00 | 0.00 | 01-APR-00:10 | 5.27 | 4.90 |
| May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 | 9.91 | 0.00 | 0.00 | 01-MAY-00:10 | 10.33 | 9.91 |
| June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 | 16.59 | 0.00 | 0.00 | 01-JUN-00:10 | 18.37 | 16.59 |
| July | 0.00 | 0.00 | 01-JUL-00:01 | 20.00 | 19.29 | 0.00 | 0.00 | 01-JUL-00:10 | 20.00 | 19.29 |
| August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 | 21.46 | 0.00 | 0.00 | 01-AUG-00:10 | 23.90 | 21.46 |
| September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 | 19.79 | 0.00 | 0.00 | 01-SEP-00:10 | 23.43 | 19.79 |
| October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 | 11.77 | 0.00 | 0.00 | 01-OCT-00:10 | 12.47 | 11.77 |
| November | 0.00 | 0.00 | 01-NOV-00:01 | 10.40 | 9.04 | 0.00 | 0.00 | 01-NOV-00:10 | 10.40 | 9.04 |
| December | 0.00 | 0.00 | 01-DEC-00:02 | 5.97 | 2.86 | 0.00 | 0.00 | 01-DEC-00:10 | 5.97 | 2.86 |
| Annual Sum or Average | 0.00 | 0.00 | ||||||||
| Minimum of Months | 0.00 | 0.00 | -9.6 | -11.5 | 0.00 | 0.00 | -9.6 | -11.5 | ||
| Maximum of Months | 0.00 | 0.00 | 23.90 | 21.46 | 0.00 | 0.00 | 23.90 | 21.46 |
Report: ZoneHeatingSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.115755E+10 | 71668.06 | 03-JAN-04:01 | 2.48 |
| February | 0.132068E+10 | 66348.71 | 25-FEB-05:01 | -4.0 |
| March | 0.262294E+09 | 65362.05 | 23-MAR-04:01 | -5.0 |
| April | 56317778.84 | 19145.71 | 02-APR-03:02 | 3.90 |
| May | 118348.38 | 1749.65 | 01-MAY-04:04 | 6.60 |
| June | 19040875.40 | 7283.32 | 19-JUN-23:02 | 26.32 |
| July | 0.120258E+09 | 9027.06 | 09-JUL-23:02 | 27.48 |
| August | 0.111001E+09 | 10281.87 | 04-AUG-23:01 | 28.30 |
| September | 11679247.91 | 6611.93 | 01-SEP-23:02 | 25.92 |
| October | 682559.56 | 6529.10 | 29-OCT-04:03 | 2.30 |
| November | 0.125924E+09 | 66281.54 | 23-NOV-05:01 | -3.9 |
| December | 0.374441E+09 | 65064.27 | 22-DEC-05:01 | -3.9 |
| Annual Sum or Average | 0.355998E+10 | |||
| Minimum of Months | 118348.38 | 1749.65 | -5.0 | |
| Maximum of Months | 0.132068E+10 | 71668.06 | 28.30 |
Report: ZoneHeatingSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 2794660.96 | 8412.04 | 02-JAN-05:02 | -12.1 |
| February | 3197876.42 | 8721.04 | 25-FEB-05:03 | -4.0 |
| March | 637197.44 | 9193.53 | 23-MAR-04:03 | -5.0 |
| April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
| May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
| June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:01 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
| November | 435764.37 | 7160.50 | 23-NOV-05:03 | -3.9 |
| December | 54738.25 | 697.03 | 21-DEC-05:04 | 0.00 |
| Annual Sum or Average | 7120237.43 | |||
| Minimum of Months | 0.00 | 0.00 | -12.1 | |
| Maximum of Months | 3197876.42 | 9193.53 | 23.90 |
Report: ZoneHeatingSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
| January | 0.00 | 0.00 | 01-JAN-00:01 | -9.6 |
| February | 0.00 | 0.00 | 01-FEB-00:01 | -1.1 |
| March | 0.00 | 0.00 | 01-MAR-00:02 | 5.52 |
| April | 0.00 | 0.00 | 01-APR-00:01 | 5.27 |
| May | 0.00 | 0.00 | 01-MAY-00:01 | 10.33 |
| June | 0.00 | 0.00 | 01-JUN-00:01 | 18.37 |
| July | 0.00 | 0.00 | 01-JUL-00:01 | 20.00 |
| August | 0.00 | 0.00 | 01-AUG-00:01 | 23.90 |
| September | 0.00 | 0.00 | 01-SEP-00:01 | 23.43 |
| October | 0.00 | 0.00 | 01-OCT-00:01 | 12.47 |
| November | 0.00 | 0.00 | 01-NOV-00:01 | 10.40 |
| December | 0.00 | 0.00 | 01-DEC-00:02 | 5.97 |
| Annual Sum or Average | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | -9.6 | |
| Maximum of Months | 0.00 | 0.00 | 23.90 |
Report: ZoneElectricSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.117915E+11 | 6902.89 | 02-JAN-10:09 | 0.106257E+11 | 6991.88 | 01-JAN-11:09 |
| February | 0.106801E+11 | 6902.89 | 01-FEB-10:09 | 0.959744E+10 | 6991.88 | 01-FEB-11:09 |
| March | 0.119793E+11 | 6902.89 | 01-MAR-10:09 | 0.106258E+11 | 6991.88 | 01-MAR-11:09 |
| April | 0.114574E+11 | 6902.89 | 01-APR-16:10 | 0.102830E+11 | 6991.88 | 01-APR-10:09 |
| May | 0.118854E+11 | 6902.89 | 01-MAY-09:09 | 0.106258E+11 | 6991.88 | 01-MAY-10:09 |
| June | 0.115789E+11 | 6902.89 | 01-JUN-09:09 | 0.102830E+11 | 6991.88 | 01-JUN-10:09 |
| July | 0.117653E+11 | 6902.89 | 01-JUL-16:10 | 0.106257E+11 | 6991.88 | 01-JUL-10:09 |
| August | 0.119793E+11 | 6902.89 | 01-AUG-09:09 | 0.106258E+11 | 6991.88 | 01-AUG-10:09 |
| September | 0.114602E+11 | 6902.89 | 01-SEP-09:09 | 0.102830E+11 | 6991.88 | 01-SEP-10:09 |
| October | 0.117901E+11 | 6902.89 | 02-OCT-09:09 | 0.106257E+11 | 6991.88 | 01-OCT-10:09 |
| November | 0.114146E+11 | 6902.89 | 01-NOV-09:09 | 0.102829E+11 | 6991.88 | 01-NOV-10:09 |
| December | 0.117667E+11 | 6902.89 | 01-DEC-10:09 | 0.106257E+11 | 6991.88 | 01-DEC-11:09 |
| Annual Sum or Average | 0.139549E+12 | 0.125110E+12 | ||||
| Minimum of Months | 0.106801E+11 | 6902.89 | 0.959744E+10 | 6991.88 | ||
| Maximum of Months | 0.119793E+11 | 6902.89 | 0.106258E+11 | 6991.88 |
Report: ZoneElectricSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
| January | 0.244214E+10 | 1429.66 | 02-JAN-10:09 | 0.280690E+11 | 17537.38 | 01-JAN-11:09 |
| February | 0.221197E+10 | 1429.66 | 01-FEB-10:09 | 0.253527E+11 | 17537.38 | 01-FEB-11:09 |
| March | 0.248103E+10 | 1429.66 | 01-MAR-10:09 | 0.280692E+11 | 17537.38 | 01-MAR-11:09 |
| April | 0.237295E+10 | 1429.66 | 01-APR-16:10 | 0.271636E+11 | 17537.38 | 01-APR-10:09 |
| May | 0.246159E+10 | 1429.66 | 01-MAY-09:09 | 0.280691E+11 | 17537.38 | 01-MAY-10:09 |
| June | 0.239811E+10 | 1429.66 | 01-JUN-09:09 | 0.271637E+11 | 17537.38 | 01-JUN-10:09 |
| July | 0.243671E+10 | 1429.66 | 01-JUL-16:10 | 0.280690E+11 | 17537.38 | 01-JUL-10:09 |
| August | 0.248103E+10 | 1429.66 | 01-AUG-09:09 | 0.280692E+11 | 17537.38 | 01-AUG-10:09 |
| September | 0.237352E+10 | 1429.66 | 01-SEP-09:09 | 0.271636E+11 | 17537.38 | 01-SEP-10:09 |
| October | 0.244186E+10 | 1429.66 | 02-OCT-09:09 | 0.280690E+11 | 17537.38 | 01-OCT-10:09 |
| November | 0.236408E+10 | 1429.66 | 01-NOV-09:09 | 0.271636E+11 | 17537.38 | 01-NOV-10:09 |
| December | 0.243700E+10 | 1429.66 | 01-DEC-10:09 | 0.280690E+11 | 17537.38 | 01-DEC-11:09 |
| Annual Sum or Average | 0.289020E+11 | 0.330491E+12 | ||||
| Minimum of Months | 0.221197E+10 | 1429.66 | 0.253527E+11 | 17537.38 | ||
| Maximum of Months | 0.248103E+10 | 1429.66 | 0.280692E+11 | 17537.38 |
Report: SpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.300980E+11 | 0.117915E+11 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102904E+11 |
| February | 0.272721E+11 | 0.106801E+11 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.974474E+10 |
| March | 0.305458E+11 | 0.119793E+11 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.801128E+10 |
| April | 0.292871E+11 | 0.114574E+11 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 10628811.02 | 0.534071E+10 |
| May | 0.303219E+11 | 0.118854E+11 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 63973785.75 | 0.339811E+10 |
| June | 0.295292E+11 | 0.115789E+11 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425595E+09 | 0.113389E+10 |
| July | 0.300798E+11 | 0.117653E+11 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100846E+10 | 0.196444E+09 |
| August | 0.305458E+11 | 0.119793E+11 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117313E+10 | 0.320208E+09 |
| September | 0.292871E+11 | 0.114602E+11 | 0.102830E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176084E+09 | 0.170960E+10 |
| October | 0.300980E+11 | 0.117901E+11 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2609554.57 | 0.427318E+10 |
| November | 0.290996E+11 | 0.114146E+11 | 0.102829E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696928E+10 |
| December | 0.300798E+11 | 0.117667E+11 | 0.106257E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.901734E+10 |
| Annual Sum or Average | 0.356244E+12 | 0.139549E+12 | 0.125110E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.286048E+10 | 0.604052E+11 |
| Minimum of Months | 0.272721E+11 | 0.106801E+11 | 0.959744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196444E+09 |
| Maximum of Months | 0.305458E+11 | 0.119793E+11 | 0.106258E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117313E+10 | 0.102904E+11 |
Report: SpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.808786E+09 | 0.244214E+10 | 0.231104E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.539851E+09 |
| February | 0.732850E+09 | 0.221197E+10 | 0.208739E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454873E+09 |
| March | 0.820818E+09 | 0.248103E+10 | 0.231105E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386202E+09 |
| April | 0.786997E+09 | 0.237295E+10 | 0.223649E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 15025.72 | 0.269826E+09 |
| May | 0.814802E+09 | 0.246159E+10 | 0.231104E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 450637.94 | 0.183898E+09 |
| June | 0.793501E+09 | 0.239811E+10 | 0.223650E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 4303724.38 | 0.115852E+09 |
| July | 0.808298E+09 | 0.243671E+10 | 0.231104E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 8854876.78 | 48804629.57 |
| August | 0.820818E+09 | 0.248103E+10 | 0.231105E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 12013966.20 | 58999199.26 |
| September | 0.786997E+09 | 0.237352E+10 | 0.223649E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 1145931.98 | 0.114595E+09 |
| October | 0.808786E+09 | 0.244186E+10 | 0.231104E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233380E+09 |
| November | 0.781956E+09 | 0.236408E+10 | 0.223648E+11 | 0.115838E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377952E+09 |
| December | 0.808298E+09 | 0.243700E+10 | 0.231104E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.452560E+09 |
| Annual Sum or Average | 0.957291E+10 | 0.289020E+11 | 0.272106E+12 | 0.140936E+12 | 0.00 | 0.00 | 0.00 | 26784163.00 | 0.323679E+10 |
| Minimum of Months | 0.732850E+09 | 0.221197E+10 | 0.208739E+11 | 0.108115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48804629.57 |
| Maximum of Months | 0.820818E+09 | 0.248103E+10 | 0.231105E+11 | 0.119699E+11 | 0.00 | 0.00 | 0.00 | 12013966.20 | 0.539851E+09 |
Report: SpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196194E+09 | 0.181403E+10 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142360E+09 | 0.233996E+10 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108504E+09 | 0.332061E+10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263053E+09 | 0.347783E+10 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279070E+09 | 0.456640E+10 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294339E+09 | 0.439739E+10 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.416295E+09 | 0.449408E+10 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.579479E+09 | 0.444218E+10 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448753E+09 | 0.326399E+10 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585118E+09 | 0.285313E+10 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237516E+09 | 0.170390E+10 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237948E+09 | 0.150027E+10 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378863E+10 | 0.381738E+11 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108504E+09 | 0.150027E+10 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.585118E+09 | 0.456640E+10 |
Report: PeakSpaceGainsMonthly
For: DINING
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 30255.31 | 07-JAN-19:10 | 6902.89 | 02-JAN-10:09 | 6991.88 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 13051.89 | 14-JAN-20:00 |
| February | 30255.31 | 04-FEB-19:10 | 6902.89 | 01-FEB-10:09 | 6991.88 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 13336.39 | 06-FEB-12:10 |
| March | 30255.31 | 04-MAR-19:10 | 6902.89 | 01-MAR-10:09 | 6991.88 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 9676.03 | 17-MAR-20:00 |
| April | 30255.31 | 01-APR-18:10 | 6902.89 | 01-APR-16:10 | 6991.88 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 935.08 | 07-APR-13:00 | 6846.03 | 01-APR-18:10 |
| May | 30255.31 | 06-MAY-18:10 | 6902.89 | 01-MAY-09:09 | 6991.88 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2077.44 | 30-MAY-12:00 | 5629.63 | 01-MAY-19:55 |
| June | 30255.31 | 03-JUN-18:10 | 6902.89 | 01-JUN-09:09 | 6991.88 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4766.15 | 19-JUN-11:55 | 3269.54 | 03-JUN-19:00 |
| July | 30255.31 | 01-JUL-18:10 | 6902.89 | 01-JUL-16:10 | 6991.88 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3731.88 | 07-JUL-12:00 | 1394.00 | 01-JUL-20:00 |
| August | 30255.31 | 05-AUG-18:10 | 6902.89 | 01-AUG-09:09 | 6991.88 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3544.05 | 04-AUG-19:00 | 2046.71 | 20-AUG-06:10 |
| September | 30255.31 | 02-SEP-18:10 | 6902.89 | 01-SEP-09:09 | 6991.88 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2274.84 | 01-SEP-12:00 | 4364.87 | 29-SEP-20:00 |
| October | 30255.31 | 07-OCT-18:10 | 6902.89 | 02-OCT-09:09 | 6991.88 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 347.94 | 04-OCT-13:00 | 6750.94 | 28-OCT-19:00 |
| November | 30255.31 | 04-NOV-18:10 | 6902.89 | 01-NOV-09:09 | 6991.88 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 9630.90 | 22-NOV-21:00 |
| December | 30255.31 | 02-DEC-19:10 | 6902.89 | 01-DEC-10:09 | 6991.88 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 11013.84 | 31-DEC-21:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
| Minimum of Months | 30255.31 | 6902.89 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.00 | |||||
| Maximum of Months | 30255.31 | 6902.89 | 6991.88 | 0.00 | 0.00 | 0.00 | 0.00 | 4766.15 | 13336.39 |
Report: PeakSpaceGainsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 813.01 | 07-JAN-19:10 | 1429.66 | 02-JAN-10:09 | 14274.50 | 01-JAN-11:09 | 7874.59 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 1417.34 | 31-JAN-01:10 |
| February | 813.01 | 04-FEB-19:10 | 1429.66 | 01-FEB-10:09 | 14274.50 | 01-FEB-11:09 | 7874.59 | 01-FEB-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 1454.33 | 06-FEB-01:10 |
| March | 813.01 | 04-MAR-19:10 | 1429.66 | 01-MAR-10:09 | 14274.50 | 01-MAR-11:09 | 7874.59 | 01-MAR-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:02 | 1022.79 | 22-MAR-04:00 |
| April | 813.01 | 01-APR-18:10 | 1429.66 | 01-APR-16:10 | 14274.50 | 01-APR-10:09 | 7874.59 | 01-APR-10:09 | 0.00 | 0.00 | 0.00 | 4.20 | 07-APR-13:00 | 1100.40 | 11-APR-03:40 |
| May | 813.01 | 06-MAY-18:10 | 1429.66 | 01-MAY-09:09 | 14274.50 | 01-MAY-10:09 | 7874.59 | 01-MAY-10:09 | 0.00 | 0.00 | 0.00 | 20.13 | 30-MAY-12:55 | 676.76 | 03-MAY-03:40 |
| June | 813.01 | 03-JUN-18:10 | 1429.66 | 01-JUN-09:09 | 14274.50 | 01-JUN-10:09 | 7874.59 | 01-JUN-10:09 | 0.00 | 0.00 | 0.00 | 51.74 | 19-JUN-11:55 | 394.83 | 02-JUN-02:00 |
| July | 813.01 | 01-JUL-18:10 | 1429.66 | 01-JUL-16:10 | 14274.50 | 01-JUL-10:09 | 7874.59 | 01-JUL-10:09 | 0.00 | 0.00 | 0.00 | 51.49 | 09-JUL-24:00 | 265.33 | 28-JUL-03:10 |
| August | 813.01 | 05-AUG-18:10 | 1429.66 | 01-AUG-09:09 | 14274.50 | 01-AUG-10:09 | 7874.59 | 01-AUG-10:09 | 0.00 | 0.00 | 0.00 | 67.72 | 24-AUG-17:00 | 292.51 | 24-AUG-03:10 |
| September | 813.01 | 02-SEP-18:10 | 1429.66 | 01-SEP-09:09 | 14274.50 | 01-SEP-10:09 | 7874.59 | 01-SEP-10:09 | 0.00 | 0.00 | 0.00 | 29.48 | 14-SEP-14:00 | 393.01 | 23-SEP-02:10 |
| October | 813.01 | 07-OCT-18:10 | 1429.66 | 02-OCT-09:09 | 14274.50 | 01-OCT-10:09 | 7874.59 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 826.33 | 08-OCT-02:00 |
| November | 813.01 | 04-NOV-18:10 | 1429.66 | 01-NOV-09:09 | 14274.50 | 01-NOV-10:09 | 7874.59 | 01-NOV-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:01 | 1230.57 | 23-NOV-02:00 |
| December | 813.01 | 02-DEC-19:10 | 1429.66 | 01-DEC-10:09 | 14274.50 | 01-DEC-11:09 | 7874.59 | 01-DEC-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 1244.00 | 02-DEC-03:00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||||||
| Minimum of Months | 813.01 | 1429.66 | 14274.50 | 7874.59 | 0.00 | 0.00 | 0.00 | 0.00 | 265.33 | ||||||
| Maximum of Months | 813.01 | 1429.66 | 14274.50 | 7874.59 | 0.00 | 0.00 | 0.00 | 67.72 | 1454.33 |
Report: PeakSpaceGainsMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1194.89 | 01-JAN-00:53 | 4758.16 | 30-JAN-12:30 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 690.77 | 18-FEB-06:00 | 5495.34 | 17-FEB-13:00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1314.95 | 23-MAR-06:25 | 7321.16 | 18-MAR-13:10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1247.52 | 28-APR-00:20 | 7054.02 | 03-APR-12:00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1580.45 | 29-MAY-02:00 | 7683.25 | 14-MAY-11:30 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1503.10 | 03-JUN-22:55 | 7620.00 | 03-JUN-13:20 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1435.85 | 02-JUL-04:00 | 6693.23 | 02-JUL-12:00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1447.66 | 30-AUG-00:10 | 6707.99 | 23-AUG-12:20 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1360.04 | 02-SEP-23:20 | 6600.49 | 11-SEP-12:50 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1704.26 | 19-OCT-05:35 | 6025.80 | 12-OCT-11:20 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1115.31 | 28-NOV-07:53 | 4458.22 | 04-NOV-12:40 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 918.01 | 29-DEC-04:25 | 3996.07 | 15-DEC-11:40 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 690.77 | 3996.07 | ||
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1704.26 | 7683.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DINING
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 43117.13 | 02-JAN-04:52 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 602.25 |
| February | 48440.15 | 06-FEB-04:53 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.41 |
| March | 27910.97 | 22-MAR-23:01 | 15127.65 | 10354.33 | 6480.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641.60 |
| April | 49764.17 | 08-APR-03:01 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.37 |
| May | 63545.32 | 30-MAY-03:01 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.94 |
| June | 69177.43 | 23-JUN-03:01 | 0.00 | 9203.85 | 9600.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.83 |
| July | 69182.78 | 11-JUL-03:01 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.77 |
| August | 83281.94 | 25-AUG-03:01 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.02 |
| September | 78887.21 | 15-SEP-03:01 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.85 |
| October | 67843.47 | 14-OCT-03:01 | 0.00 | 11504.81 | 12000.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.62 |
| November | 29504.60 | 24-NOV-00:01 | 16808.50 | 11504.81 | 7200.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1194.11 |
| December | 33266.61 | 22-DEC-05:02 | 16808.50 | 15339.75 | 28931.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.67 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Minimum of Months | 27910.97 | 0.00 | 9203.85 | 6480.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.94 | |
| Maximum of Months | 83281.94 | 16808.50 | 15339.75 | 28931.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1916.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 42572.68 | 02-JAN-05:01 | 361.34 | 2541.62 | 52988.98 | 26067.59 | 0.00 | 0.00 | 0.00 | 0.00 | 100.68 |
| February | 40876.11 | 07-FEB-05:01 | 451.67 | 3177.02 | 66236.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 177.52 |
| March | 35958.92 | 23-MAR-04:01 | 451.67 | 3177.02 | 66236.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 37.27 |
| April | 52025.63 | 09-APR-03:01 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 160.54 |
| May | 61858.73 | 21-MAY-03:01 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 179.82 |
| June | 58156.38 | 03-JUN-03:01 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 261.96 |
| July | 44135.81 | 11-JUL-03:01 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 133.79 |
| August | 49295.57 | 20-AUG-03:11 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 164.93 |
| September | 60316.26 | 29-SEP-03:01 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 163.84 |
| October | 64390.37 | 07-OCT-03:01 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 266.97 |
| November | 55178.95 | 04-NOV-03:01 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 23.51 |
| December | 36877.37 | 22-DEC-05:01 | 451.67 | 3177.02 | 66236.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 116.79 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
| Minimum of Months | 35958.92 | 0.00 | 2382.77 | 34630.20 | 13576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 23.51 | |
| Maximum of Months | 64390.37 | 451.67 | 3177.02 | 66236.23 | 32584.49 | 0.00 | 0.00 | 0.00 | 0.00 | 266.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
| January | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.82 |
| February | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 659.64 | 0.00 |
| March | 0.00 | 01-MAR-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.84 |
| April | 0.00 | 01-APR-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 329.79 |
| May | 0.00 | 01-MAY-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.43 |
| June | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.62 | 0.00 |
| July | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.76 | 0.00 |
| August | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 183.49 | 0.00 |
| September | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.28 | 0.00 |
| October | 0.00 | 01-OCT-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.10 | 0.00 |
| November | 0.00 | 01-NOV-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 278.92 |
| December | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.67 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 659.64 | 329.79 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
| January | 0.844273E+11 | 45487.99 | 18-JAN-16:49 | 0.168285E+12 | 150643.71 | 02-JAN-07:10 |
| February | 0.758438E+11 | 45415.69 | 28-FEB-17:40 | 0.163290E+12 | 159391.26 | 06-FEB-07:10 |
| March | 0.837202E+11 | 51311.86 | 27-MAR-16:19 | 0.122701E+12 | 136984.72 | 22-MAR-03:09 |
| April | 0.830056E+11 | 58188.25 | 08-APR-10:09 | 0.861316E+11 | 81350.00 | 03-APR-06:10 |
| May | 0.923826E+11 | 64634.74 | 31-MAY-10:00 | 0.763400E+11 | 48292.06 | 01-MAY-06:10 |
| June | 0.108625E+12 | 80689.74 | 19-JUN-11:00 | 0.717928E+11 | 46807.16 | 03-JUN-10:39 |
| July | 0.127442E+12 | 76498.28 | 07-JUL-11:00 | 0.725421E+11 | 46319.94 | 01-JUL-10:00 |
| August | 0.124527E+12 | 78382.95 | 04-AUG-11:00 | 0.726052E+11 | 45655.78 | 27-AUG-10:20 |
| September | 0.103751E+12 | 71180.21 | 14-SEP-11:00 | 0.707232E+11 | 46641.09 | 30-SEP-10:30 |
| October | 0.935651E+11 | 64281.53 | 25-OCT-10:00 | 0.771906E+11 | 57099.46 | 09-OCT-05:00 |
| November | 0.820868E+11 | 50455.81 | 04-NOV-16:49 | 0.102246E+12 | 136984.65 | 22-NOV-04:19 |
| December | 0.844316E+11 | 45443.74 | 19-DEC-17:40 | 0.139350E+12 | 136984.70 | 15-DEC-04:10 |
| Annual Sum or Average | 0.114381E+13 | 0.122320E+13 | ||||
| Minimum of Months | 0.758438E+11 | 45415.69 | 0.707232E+11 | 45655.78 | ||
| Maximum of Months | 0.127442E+12 | 80689.74 | 0.168285E+12 | 159391.26 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 0.142337E+11 | 0.743911E+10 | 0.386947E+11 | 0.00 | 0.211593E+11 | 37879553.69 | 0.00 | 1495093.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.128921E+11 | 0.623864E+10 | 0.349501E+11 | 0.00 | 0.191610E+11 | 34213790.43 | 0.00 | 318696.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.144603E+11 | 0.624688E+10 | 0.386950E+11 | 0.00 | 0.210356E+11 | 37879553.69 | 0.00 | 0.328498E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.138304E+11 | 0.538429E+10 | 0.374466E+11 | 0.00 | 0.202568E+11 | 36657632.61 | 0.00 | 0.310939E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.143470E+11 | 0.497772E+10 | 0.386949E+11 | 0.00 | 0.209657E+11 | 37879553.69 | 0.00 | 0.101523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.139770E+11 | 0.450797E+10 | 0.374467E+11 | 0.00 | 0.204847E+11 | 36657632.61 | 0.00 | 0.289825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.142020E+11 | 0.479642E+10 | 0.386947E+11 | 0.00 | 0.214063E+11 | 37879553.69 | 0.00 | 0.449983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.144603E+11 | 0.529639E+10 | 0.386950E+11 | 0.00 | 0.213401E+11 | 37879553.69 | 0.00 | 0.413935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.138337E+11 | 0.575515E+10 | 0.374466E+11 | 0.00 | 0.204589E+11 | 36657632.61 | 0.00 | 0.230519E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.142320E+11 | 0.663422E+10 | 0.386947E+11 | 0.00 | 0.209915E+11 | 37879553.69 | 0.00 | 0.980983E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.137787E+11 | 0.702430E+10 | 0.374465E+11 | 0.00 | 0.203322E+11 | 36657632.61 | 0.00 | 0.594648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.142037E+11 | 0.758471E+10 | 0.386947E+11 | 0.00 | 0.210433E+11 | 37879553.69 | 0.00 | 2020069.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.168451E+12 | 0.718858E+11 | 0.455600E+12 | 0.00 | 0.248635E+12 | 0.446001E+09 | 0.00 | 0.162425E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.128921E+11 | 0.450797E+10 | 0.349501E+11 | 0.00 | 0.191610E+11 | 34213790.43 | 0.00 | 318696.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.144603E+11 | 0.758471E+10 | 0.386950E+11 | 0.00 | 0.214063E+11 | 37879553.69 | 0.00 | 0.449983E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS [J] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
| January | 0.398997E+11 | 0.00 | 0.885178E+11 | 0.00 | 0.398677E+11 | 0.00 | 0.00 |
| February | 0.360384E+11 | 0.00 | 0.908970E+11 | 0.00 | 0.363550E+11 | 0.00 | 0.00 |
| March | 0.398997E+11 | 0.00 | 0.429174E+11 | 0.00 | 0.398839E+11 | 0.00 | 0.00 |
| April | 0.386126E+11 | 0.00 | 0.107433E+11 | 0.00 | 0.367756E+11 | 0.00 | 0.00 |
| May | 0.398997E+11 | 0.00 | 0.392869E+09 | 0.00 | 0.360474E+11 | 0.00 | 0.00 |
| June | 0.386126E+11 | 0.00 | 0.00 | 0.00 | 0.331802E+11 | 0.00 | 0.00 |
| July | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.326424E+11 | 0.00 | 0.00 |
| August | 0.398997E+11 | 0.00 | 0.00 | 0.00 | 0.327055E+11 | 0.00 | 0.00 |
| September | 0.386126E+11 | 0.00 | 3026479.89 | 0.00 | 0.321076E+11 | 0.00 | 0.00 |
| October | 0.398997E+11 | 0.00 | 0.263722E+10 | 0.00 | 0.346537E+11 | 0.00 | 0.00 |
| November | 0.386126E+11 | 0.00 | 0.281025E+11 | 0.00 | 0.355305E+11 | 0.00 | 0.00 |
| December | 0.398997E+11 | 0.00 | 0.608909E+11 | 0.00 | 0.385590E+11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.469787E+12 | 0.00 | 0.325102E+12 | 0.00 | 0.428308E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.360384E+11 | 0.00 | 0.00 | 0.00 | 0.321076E+11 | 0.00 | 0.00 |
| Maximum of Months | 0.398997E+11 | 0.00 | 0.908970E+11 | 0.00 | 0.398839E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| INTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
| January | 8332.55 | 02-JAN-10:09 | 4578.48 | 01-JAN-00:10 | 24529.26 | 01-JAN-11:09 | 0.00 | 9365.44 | 02-JAN-00:20 | 17.86 | 04-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| February | 8332.55 | 01-FEB-10:09 | 4578.48 | 01-FEB-00:10 | 24529.26 | 01-FEB-11:09 | 0.00 | 9365.44 | 01-FEB-10:09 | 17.86 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
| March | 8332.55 | 01-MAR-10:09 | 4578.48 | 01-MAR-00:10 | 24529.26 | 01-MAR-11:09 | 0.00 | 9365.44 | 04-MAR-08:00 | 17.86 | 16-MAR-23:10 | 0.00 | 01-MAR-00:10 |
| April | 8332.55 | 01-APR-16:10 | 4578.48 | 01-APR-00:10 | 24529.26 | 01-APR-10:09 | 0.00 | 9365.44 | 01-APR-05:00 | 17.86 | 01-APR-05:10 | 0.00 | 01-APR-00:10 |
| May | 8332.55 | 01-MAY-09:09 | 4578.48 | 01-MAY-00:10 | 24529.26 | 01-MAY-10:09 | 0.00 | 9365.44 | 01-MAY-16:40 | 17.86 | 05-MAY-11:20 | 0.00 | 01-MAY-00:10 |
| June | 8332.55 | 01-JUN-09:09 | 4578.48 | 01-JUN-00:10 | 24529.26 | 01-JUN-10:09 | 0.00 | 9365.44 | 02-JUN-06:49 | 17.86 | 08-JUN-10:39 | 0.00 | 01-JUN-00:10 |
| July | 8332.55 | 01-JUL-16:10 | 4578.48 | 01-JUL-00:10 | 24529.26 | 01-JUL-10:09 | 0.00 | 9365.44 | 01-JUL-12:20 | 17.86 | 07-JUL-09:50 | 0.00 | 01-JUL-00:10 |
| August | 8332.55 | 01-AUG-09:09 | 4578.48 | 01-AUG-00:10 | 24529.26 | 01-AUG-10:09 | 0.00 | 9365.44 | 01-AUG-16:30 | 17.86 | 01-AUG-05:10 | 0.00 | 01-AUG-00:10 |
| September | 8332.55 | 01-SEP-09:09 | 4578.48 | 01-SEP-00:10 | 24529.26 | 01-SEP-10:09 | 0.00 | 9365.44 | 01-SEP-16:49 | 17.86 | 01-SEP-05:10 | 0.00 | 01-SEP-00:10 |
| October | 8332.55 | 02-OCT-09:09 | 4578.48 | 01-OCT-00:10 | 24529.26 | 01-OCT-10:09 | 0.00 | 9365.44 | 02-OCT-20:00 | 17.86 | 09-OCT-08:50 | 0.00 | 01-OCT-00:10 |
| November | 8332.55 | 01-NOV-09:09 | 4578.48 | 01-NOV-00:10 | 24529.26 | 01-NOV-10:09 | 0.00 | 9365.44 | 02-NOV-06:10 | 17.86 | 22-NOV-00:10 | 0.00 | 01-NOV-00:10 |
| December | 8332.55 | 01-DEC-10:09 | 4578.48 | 01-DEC-00:10 | 24529.26 | 01-DEC-11:09 | 0.00 | 9365.44 | 03-DEC-21:10 | 17.86 | 07-DEC-00:10 | 0.00 | 01-DEC-00:10 |
| Annual Sum or Average | 0.00 | ||||||||||||
| Minimum of Months | 8332.55 | 4578.48 | 24529.26 | 0.00 | 9365.44 | 17.86 | 0.00 | ||||||
| Maximum of Months | 8332.55 | 4578.48 | 24529.26 | 0.00 | 9365.44 | 17.86 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| COOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
| January | 534.38 | 24-JAN-04:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 216.34 | 24-FEB-04:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 10317.69 | 27-MAR-16:19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 16407.59 | 07-APR-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 22497.77 | 31-MAY-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 38854.94 | 19-JUN-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 35059.11 | 08-JUL-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 36690.89 | 16-AUG-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 29353.38 | 14-SEP-11:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 20707.83 | 25-OCT-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 7126.32 | 04-NOV-12:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 456.54 | 05-DEC-04:49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 216.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 38854.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
| January | 45487.99 | 18-JAN-16:49 | 8332.55 | 22118.27 | 4578.48 | 0.00 | 9365.44 | 17.86 | 0.00 | 0.00 | 0.00 |
| February | 45415.69 | 28-FEB-17:40 | 8332.55 | 22118.27 | 4578.48 | 0.00 | 9365.44 | 17.86 | 0.00 | 0.00 | 0.00 |
| March | 51311.86 | 27-MAR-16:19 | 8332.55 | 22118.27 | 0.00 | 0.00 | 9365.44 | 17.86 | 0.00 | 10317.69 | 0.00 |
| April | 58188.25 | 08-APR-10:09 | 7406.71 | 24529.26 | 0.00 | 0.00 | 9365.44 | 17.86 | 0.00 | 14114.62 | 0.00 |
| May | 64634.74 | 31-MAY-10:00 | 8332.55 | 24529.26 | 0.00 | 0.00 | 9365.44 | 17.86 | 0.00 | 20687.21 | 0.00 |
| June | 80689.74 | 19-JUN-11:00 | 8332.55 | 22921.93 | 0.00 | 0.00 | 9365.44 | 17.86 | 0.00 | 38854.94 | 0.00 |
| July | 76498.28 | 07-JUL-11:00 | 8332.55 | 22921.93 | 0.00 | 0.00 | 9365.44 | 17.86 | 0.00 | 34672.04 | 0.00 |
| August | 78382.95 | 04-AUG-11:00 | 8332.55 | 22921.93 | 0.00 | 0.00 | 9365.44 | 17.86 | 0.00 | 36533.01 | 0.00 |
| September | 71180.21 | 14-SEP-11:00 | 8332.55 | 22921.93 | 0.00 | 0.00 | 9365.44 | 17.86 | 0.00 | 29353.38 | 0.00 |
| October | 64281.53 | 25-OCT-10:00 | 8332.55 | 24529.26 | 0.00 | 0.00 | 9365.44 | 17.86 | 0.00 | 20334.26 | 0.00 |
| November | 50455.81 | 04-NOV-16:49 | 8332.55 | 22118.27 | 4578.48 | 0.00 | 9365.44 | 17.86 | 0.00 | 4893.25 | 0.00 |
| December | 45443.74 | 19-DEC-17:40 | 8332.55 | 22118.27 | 4578.48 | 0.00 | 9365.44 | 17.86 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | |||||||||
| Minimum of Months | 45415.69 | 7406.71 | 22118.27 | 0.00 | 0.00 | 9365.44 | 17.86 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 80689.74 | 8332.55 | 24529.26 | 4578.48 | 0.00 | 9365.44 | 17.86 | 0.00 | 38854.94 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| INTERIOREQUIPMENT:NATURALGAS {Maximum} [W] | INTERIOREQUIPMENT:NATURALGAS {TIMESTAMP} | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
| January | 26248.62 | 01-JAN-11:09 | 0.00 | 131732.52 | 01-JAN-04:19 | 0.00 | 28683.07 | 31-JAN-19:40 | 0.00 |
| February | 26248.62 | 01-FEB-11:09 | 0.00 | 131732.52 | 06-FEB-04:49 | 0.00 | 28750.10 | 09-FEB-07:40 | 0.00 |
| March | 26248.62 | 01-MAR-11:09 | 0.00 | 131732.52 | 14-MAR-03:20 | 0.00 | 28284.87 | 01-MAR-07:19 | 0.00 |
| April | 26248.62 | 01-APR-10:09 | 0.00 | 47474.19 | 01-APR-05:00 | 0.00 | 27865.29 | 04-APR-06:40 | 0.00 |
| May | 26248.62 | 01-MAY-10:09 | 0.00 | 21479.46 | 01-MAY-04:00 | 0.00 | 26477.55 | 01-MAY-06:40 | 0.00 |
| June | 26248.62 | 01-JUN-10:09 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 25024.45 | 01-JUN-18:49 | 0.00 |
| July | 26248.62 | 01-JUL-10:09 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 23758.72 | 03-JUL-18:30 | 0.00 |
| August | 26248.62 | 01-AUG-10:09 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 23592.22 | 31-AUG-06:49 | 0.00 |
| September | 26248.62 | 01-SEP-10:09 | 0.00 | 1606.95 | 24-SEP-05:00 | 0.00 | 23897.71 | 29-SEP-06:19 | 0.00 |
| October | 26248.62 | 01-OCT-10:09 | 0.00 | 38937.60 | 09-OCT-05:00 | 0.00 | 25256.02 | 31-OCT-06:19 | 0.00 |
| November | 26248.62 | 01-NOV-10:09 | 0.00 | 131732.52 | 22-NOV-04:10 | 0.00 | 26679.97 | 30-NOV-07:30 | 0.00 |
| December | 26248.62 | 01-DEC-11:09 | 0.00 | 131732.52 | 15-DEC-04:10 | 0.00 | 28058.23 | 29-DEC-19:49 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
| Minimum of Months | 26248.62 | 0.00 | 0.00 | 0.00 | 23592.22 | 0.00 | |||
| Maximum of Months | 26248.62 | 0.00 | 131732.52 | 0.00 | 28750.10 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DINING
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 9.17 | 19.53 | 0.00 | 19.53 | 0.00 | 19.53 | 0.00 | 19.53 |
| February | 9.00 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 | 0.00 | 19.65 |
| March | 2.50 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 | 0.00 | 19.75 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.67 | 0.00 | 24.67 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.84 | 0.00 | 24.84 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.11 | 0.00 | 25.11 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 25.16 | 0.00 | 25.16 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.96 | 0.00 | 24.96 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.79 | 0.00 | 24.79 |
| November | 3.83 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 | 0.00 | 19.63 |
| December | 2.33 | 19.83 | 0.00 | 19.83 | 0.00 | 19.83 | 0.00 | 19.83 |
| Annual Sum or Average | 26.83 | 19.63 | 0.00 | 19.63 | 20.00 | 21.93 | 0.00 | 21.93 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 9.17 | 19.83 | 0.00 | 19.83 | 5.17 | 25.16 | 0.00 | 25.16 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.80 | 0.00 | 26.80 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.10 | 0.00 | 27.10 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.52 | 0.00 | 27.52 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 7.00 | 28.66 | 0.00 | 28.66 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 20.83 | 30.27 | 0.00 | 30.27 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 36.00 | 29.61 | 9.50 | 29.04 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 28.69 | 28.17 | 28.06 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 20.17 | 30.39 | 0.00 | 30.39 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 29.43 | 0.00 | 29.43 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.47 | 0.00 | 27.47 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 26.70 | 0.00 | 26.70 |
| Annual Sum or Average | 0.00 | 0.00 | 155.50 | 29.32 | 37.67 | 28.84 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 54.00 | 30.39 | 28.17 | 30.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DINING
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 610.00 | 20.82 | 204.00 | 20.70 | 204.00 | 20.62 |
| February | 551.00 | 20.77 | 201.00 | 20.66 | 201.00 | 20.60 |
| March | 562.33 | 21.02 | 89.33 | 20.96 | 72.17 | 20.83 |
| April | 381.17 | 21.40 | 169.50 | 22.02 | 22.67 | 21.92 |
| May | 147.67 | 22.42 | 427.00 | 23.58 | 24.17 | 23.60 |
| June | 202.83 | 24.11 | 576.50 | 24.08 | 196.50 | 24.09 |
| July | 350.83 | 24.23 | 609.00 | 24.17 | 350.83 | 24.19 |
| August | 175.83 | 24.34 | 610.50 | 24.18 | 175.83 | 24.21 |
| September | 99.50 | 23.85 | 545.67 | 24.02 | 76.33 | 24.05 |
| October | 194.50 | 21.97 | 362.00 | 23.26 | 19.00 | 23.27 |
| November | 485.17 | 21.18 | 115.00 | 21.38 | 47.33 | 21.27 |
| December | 609.00 | 20.85 | 111.00 | 20.70 | 111.00 | 20.59 |
| Annual Sum or Average | 4369.83 | 21.68 | 4020.50 | 22.51 | 1500.83 | 22.50 |
| Minimum of Months | 99.50 | 20.77 | 89.33 | 20.66 | 19.00 | 20.59 |
| Maximum of Months | 610.00 | 24.34 | 610.50 | 24.18 | 350.83 | 24.21 |
Report: ComfortReportSimple55Monthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 608.00 | 19.21 | 332.83 | 19.14 | 332.67 | 19.10 |
| February | 551.00 | 19.05 | 345.17 | 19.03 | 345.17 | 19.03 |
| March | 554.67 | 19.49 | 212.33 | 19.68 | 173.50 | 19.62 |
| April | 432.50 | 21.29 | 285.17 | 22.23 | 155.33 | 22.42 |
| May | 395.50 | 25.07 | 516.00 | 25.23 | 329.33 | 25.40 |
| June | 557.17 | 25.99 | 591.00 | 25.95 | 557.17 | 25.96 |
| July | 609.00 | 26.02 | 609.00 | 26.02 | 609.00 | 26.02 |
| August | 603.00 | 26.05 | 612.00 | 26.04 | 603.00 | 26.04 |
| September | 511.50 | 25.94 | 579.50 | 25.85 | 507.00 | 25.89 |
| October | 406.17 | 24.10 | 442.67 | 24.66 | 277.67 | 24.94 |
| November | 462.33 | 20.03 | 199.83 | 20.70 | 103.67 | 20.70 |
| December | 609.00 | 19.19 | 220.50 | 19.14 | 220.50 | 19.11 |
| Annual Sum or Average | 6299.83 | 22.56 | 4946.00 | 23.21 | 4214.00 | 23.42 |
| Minimum of Months | 395.50 | 19.05 | 199.83 | 19.03 | 103.67 | 19.03 |
| Maximum of Months | 609.00 | 26.05 | 612.00 | 26.04 | 609.00 | 26.04 |
Report: ComfortReportSimple55Monthly
For: ATTIC
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: OccupantComfortDataSummaryMonthly
For: DINING PEOPLE
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 610.00000 | 20.81856 | 28.14677 | -0.4928 | 11.27475 |
| February | 551.00000 | 20.77286 | 23.00579 | -0.5282 | 11.90297 |
| March | 612.00000 | 21.25859 | 34.16723 | -0.2823 | 8.73739 |
| April | 590.00000 | 22.28327 | 40.77402 | 0.04354 | 8.44471 |
| May | 611.00000 | 23.58050 | 47.06545 | -0.4270 | 11.24211 |
| June | 592.00000 | 24.05345 | 57.44635 | -0.0975 | 5.74812 |
| July | 609.00000 | 24.13689 | 64.10083 | 0.02933 | 5.52477 |
| August | 612.00000 | 24.12970 | 57.64051 | 0.00930 | 5.70908 |
| September | 590.00000 | 23.97858 | 52.19437 | -0.1559 | 6.52120 |
| October | 610.00000 | 23.29859 | 44.98196 | 0.40372 | 11.03992 |
| November | 591.00000 | 21.65352 | 36.51642 | -0.1474 | 8.33286 |
| December | 609.00000 | 20.84664 | 28.15709 | -0.4452 | 9.99070 |
| Annual Sum or Average | 7187.00000 | 22.57812 | 42.97397 | -0.1722 | 8.69446 |
| Minimum of Months | 551.00000 | 20.77286 | 23.00579 | -0.5282 | 5.52477 |
| Maximum of Months | 612.00000 | 24.13689 | 64.10083 | 0.40372 | 11.90297 |
Report: OccupantComfortDataSummaryMonthly
For: KITCHEN PEOPLE
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
| January | 610.00000 | 19.21911 | 34.23193 | -0.5764 | 13.02392 |
| February | 551.00000 | 19.05455 | 29.41422 | -0.6562 | 14.49664 |
| March | 612.00000 | 19.87379 | 40.38412 | -0.3663 | 11.22325 |
| April | 590.00000 | 21.96861 | 44.28907 | 0.17135 | 14.10857 |
| May | 611.00000 | 24.74574 | 47.01306 | 0.17309 | 12.77106 |
| June | 592.00000 | 25.91313 | 55.54871 | 0.70234 | 16.44152 |
| July | 609.00000 | 26.02497 | 61.83129 | 0.83608 | 20.18183 |
| August | 612.00000 | 26.03351 | 56.21971 | 0.80710 | 19.53541 |
| September | 590.00000 | 25.70222 | 50.63512 | 0.61302 | 15.27394 |
| October | 610.00000 | 24.00490 | 45.89425 | 0.74040 | 23.74176 |
| November | 591.00000 | 20.79386 | 40.77054 | -0.1018 | 11.21590 |
| December | 609.00000 | 19.18838 | 34.28373 | -0.5521 | 12.01138 |
| Annual Sum or Average | 7187.00000 | 22.73147 | 45.14405 | 0.15379 | 15.35348 |
| Minimum of Months | 551.00000 | 19.05455 | 29.41422 | -0.6562 | 11.21590 |
| Maximum of Months | 612.00000 | 26.03351 | 61.83129 | 0.83608 | 23.74176 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 | 0.00 | 01-JAN-00:01 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 | 0.00 | 01-FEB-00:01 |
| March | 0.863402E+09 | 0.266238E+09 | 35.53 | 0.676699E+09 | 0.186703E+09 | 0.00 | 0.60 | 27-MAR-17:10 | 0.00 | 01-MAR-00:02 | 26091.08 | 27-MAR-17:10 | 19856.71 | 27-MAR-17:07 | 9507.36 | 27-MAR-12:51 | 7559.94 | 27-MAR-17:10 | 0.00 | 01-MAR-00:02 |
| April | 0.779222E+10 | 0.233290E+10 | 154.85 | 0.647768E+10 | 0.131454E+10 | 0.00 | 1.00 | 08-APR-03:01 | 0.00 | 01-APR-00:01 | 58131.73 | 08-APR-03:01 | 45578.24 | 08-APR-03:01 | 12553.50 | 08-APR-03:01 | 15064.64 | 08-APR-03:01 | 0.00 | 01-APR-00:01 |
| May | 0.250940E+11 | 0.733201E+10 | 426.66 | 0.200507E+11 | 0.504337E+10 | 0.00 | 1.00 | 19-MAY-03:01 | 0.00 | 01-MAY-00:01 | 98998.15 | 30-MAY-03:01 | 64637.20 | 30-MAY-03:01 | 34360.95 | 30-MAY-03:01 | 25437.93 | 30-MAY-03:01 | 0.00 | 01-MAY-00:01 |
| June | 0.702614E+11 | 0.187014E+11 | 572.93 | 0.450960E+11 | 0.251653E+11 | 0.00 | 1.00 | 01-JUN-03:02 | 0.00 | 01-JUN-00:01 | 108073.49 | 27-JUN-03:01 | 75803.13 | 23-JUN-03:01 | 62281.26 | 25-JUN-03:01 | 26108.69 | 19-JUN-03:02 | 0.00 | 01-JUN-00:01 |
| July | 0.109622E+12 | 0.276904E+11 | 612.38 | 0.632043E+11 | 0.464178E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 108073.49 | 08-JUL-03:02 | 72574.46 | 11-JUL-03:01 | 67588.36 | 20-JUL-03:02 | 26108.69 | 06-JUL-03:01 | 0.00 | 01-JUL-00:01 |
| August | 0.100738E+12 | 0.260000E+11 | 607.61 | 0.650006E+11 | 0.357373E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 108073.49 | 13-AUG-03:02 | 87660.71 | 25-AUG-03:01 | 68212.97 | 17-AUG-03:03 | 26108.69 | 03-AUG-03:01 | 0.00 | 01-AUG-00:01 |
| September | 0.556429E+11 | 0.151658E+11 | 542.54 | 0.385135E+11 | 0.171295E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 108073.49 | 08-SEP-03:01 | 79574.44 | 02-SEP-03:01 | 59924.39 | 14-SEP-03:01 | 26108.69 | 08-SEP-03:01 | 0.00 | 01-SEP-00:01 |
| October | 0.247634E+11 | 0.705956E+10 | 359.49 | 0.168487E+11 | 0.791474E+10 | 0.00 | 1.00 | 03-OCT-03:01 | 0.00 | 01-OCT-00:01 | 103692.59 | 06-OCT-03:01 | 62940.93 | 14-OCT-03:01 | 47494.59 | 06-OCT-03:01 | 25776.60 | 06-OCT-03:01 | 0.00 | 01-OCT-00:01 |
| November | 0.163936E+10 | 0.519648E+09 | 69.38 | 0.136974E+10 | 0.269624E+09 | 0.00 | 0.43 | 04-NOV-13:00 | 0.00 | 01-NOV-00:01 | 18201.54 | 04-NOV-13:00 | 15158.29 | 03-NOV-13:00 | 6925.49 | 04-NOV-03:01 | 5500.66 | 04-NOV-13:00 | 0.00 | 01-NOV-00:01 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
| Annual Sum or Average | 0.396417E+12 | 0.105068E+12 | 3381.36 | 0.257238E+12 | 0.139179E+12 | 0.00 | ||||||||||||||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
| Maximum of Months | 0.109622E+12 | 0.276904E+11 | 612.38 | 0.650006E+11 | 0.464178E+11 | 0.00 | 1.00 | 0.00 | 108073.49 | 87660.71 | 68212.97 | 26108.69 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
| January | 4439555.74 | 1495093.50 | 1.15 | 2527938.86 | 1911616.88 | 0.00 | 0.24 | 24-JAN-04:43 | 0.00 | 01-JAN-00:01 | 4226.70 | 24-JAN-04:43 | 1993.64 | 24-JAN-04:43 | 2233.07 | 24-JAN-04:43 | 1380.08 | 24-JAN-04:43 | 0.00 | 01-JAN-00:01 |
| February | 931897.23 | 318696.70 | 0.42 | 546851.67 | 385045.57 | 0.00 | 0.06 | 24-FEB-04:40 | 0.00 | 01-FEB-00:01 | 1069.13 | 24-FEB-04:40 | 628.69 | 24-FEB-04:40 | 440.44 | 24-FEB-04:40 | 363.91 | 24-FEB-04:40 | 0.00 | 01-FEB-00:01 |
| March | 0.198487E+09 | 62260153.74 | 11.51 | 0.139259E+09 | 59227661.34 | 0.00 | 0.56 | 27-MAR-16:20 | 0.00 | 01-MAR-00:02 | 10795.87 | 27-MAR-16:20 | 8100.99 | 27-MAR-16:20 | 3225.32 | 28-MAR-03:42 | 3249.56 | 27-MAR-16:20 | 0.00 | 01-MAR-00:02 |
| April | 0.256624E+10 | 0.776486E+09 | 104.53 | 0.211992E+10 | 0.446318E+09 | 0.00 | 1.00 | 07-APR-03:01 | 0.00 | 01-APR-00:01 | 43112.80 | 08-APR-03:01 | 26086.96 | 08-APR-03:01 | 21456.96 | 09-APR-03:01 | 11548.73 | 08-APR-03:01 | 0.00 | 01-APR-00:01 |
| May | 0.965603E+10 | 0.282027E+10 | 305.37 | 0.767439E+10 | 0.198165E+10 | 0.00 | 1.00 | 05-MAY-03:01 | 0.00 | 01-MAY-00:01 | 43112.80 | 19-MAY-03:01 | 34547.76 | 13-MAY-03:01 | 25230.66 | 19-MAY-03:01 | 11548.73 | 06-MAY-03:01 | 0.00 | 01-MAY-00:01 |
| June | 0.386973E+11 | 0.102811E+11 | 611.88 | 0.231959E+11 | 0.155014E+11 | 0.00 | 1.00 | 01-JUN-03:11 | 0.00 | 01-JUN-00:01 | 47901.15 | 19-JUN-03:11 | 36639.20 | 19-JUN-11:00 | 31883.76 | 25-JUN-03:52 | 13287.34 | 19-JUN-11:55 | 0.00 | 01-JUN-00:01 |
| July | 0.681014E+11 | 0.173079E+11 | 702.01 | 0.362084E+11 | 0.318929E+11 | 0.00 | 1.00 | 01-JUL-03:01 | 0.00 | 01-JUL-00:01 | 47901.15 | 20-JUL-10:04 | 33297.35 | 07-JUL-11:00 | 32897.36 | 30-JUL-03:01 | 12395.02 | 08-JUL-12:00 | 0.00 | 01-JUL-00:01 |
| August | 0.593776E+11 | 0.153935E+11 | 686.87 | 0.361712E+11 | 0.232064E+11 | 0.00 | 1.00 | 01-AUG-03:01 | 0.00 | 01-AUG-00:01 | 47901.15 | 02-AUG-17:20 | 35721.59 | 22-AUG-03:01 | 32117.79 | 17-AUG-03:32 | 12591.24 | 04-AUG-18:55 | 0.00 | 01-AUG-00:01 |
| September | 0.290438E+11 | 0.788608E+10 | 553.35 | 0.187247E+11 | 0.103190E+11 | 0.00 | 1.00 | 01-SEP-03:01 | 0.00 | 01-SEP-00:01 | 47767.30 | 14-SEP-03:01 | 31695.63 | 02-SEP-03:01 | 31728.62 | 14-SEP-03:01 | 11901.46 | 14-SEP-03:01 | 0.00 | 01-SEP-00:01 |
| October | 0.958596E+10 | 0.275027E+10 | 270.19 | 0.588629E+10 | 0.369966E+10 | 0.00 | 1.00 | 01-OCT-03:01 | 0.00 | 01-OCT-00:01 | 44193.92 | 06-OCT-03:11 | 37066.60 | 26-OCT-03:01 | 26627.19 | 25-OCT-03:01 | 11629.88 | 06-OCT-03:11 | 0.00 | 01-OCT-00:01 |
| November | 0.229067E+09 | 75000280.73 | 26.91 | 0.168607E+09 | 60459556.54 | 0.00 | 1.00 | 04-NOV-03:01 | 0.00 | 01-NOV-00:01 | 39050.38 | 04-NOV-03:01 | 22413.28 | 04-NOV-03:01 | 16637.10 | 04-NOV-03:01 | 10453.86 | 04-NOV-03:01 | 0.00 | 01-NOV-00:01 |
| December | 5970125.81 | 2020069.73 | 1.93 | 3839540.35 | 2130585.46 | 0.00 | 0.20 | 05-DEC-04:43 | 0.00 | 01-DEC-00:02 | 3607.66 | 05-DEC-04:43 | 2354.41 | 05-DEC-04:43 | 1253.25 | 05-DEC-04:43 | 1187.44 | 05-DEC-04:43 | 0.00 | 01-DEC-00:02 |
| Annual Sum or Average | 0.217467E+12 | 0.573567E+11 | 3276.13 | 0.130296E+12 | 0.871716E+11 | 0.00 | ||||||||||||||
| Minimum of Months | 931897.23 | 318696.70 | 0.42 | 546851.67 | 385045.57 | 0.00 | 0.06 | 0.00 | 1069.13 | 628.69 | 440.44 | 363.91 | 0.00 | |||||||
| Maximum of Months | 0.681014E+11 | 0.173079E+11 | 702.01 | 0.362084E+11 | 0.318929E+11 | 0.00 | 1.00 | 0.00 | 47901.15 | 37066.60 | 32897.36 | 13287.34 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 228.50 | 91.29 | 137.21 | 111.07 | 810.68 | 0.00 | 0.00 | 0.00 |
| February | 354.76 | 165.21 | 189.56 | 207.33 | 794.58 | 0.00 | 0.00 | 0.00 |
| March | 455.57 | 193.62 | 261.96 | 356.19 | 551.50 | 0.00 | 0.00 | 0.00 |
| April | 545.36 | 239.36 | 305.99 | 511.35 | 395.58 | 0.00 | 0.00 | 0.00 |
| May | 658.41 | 262.39 | 396.02 | 724.31 | 256.41 | 0.00 | 0.00 | 0.00 |
| June | 611.38 | 221.45 | 389.93 | 772.90 | 146.29 | 0.00 | 0.00 | 0.00 |
| July | 613.24 | 220.78 | 392.47 | 866.04 | 83.21 | 0.00 | 0.00 | 0.00 |
| August | 691.81 | 312.12 | 379.69 | 966.49 | 112.05 | 0.00 | 0.00 | 0.00 |
| September | 517.50 | 233.13 | 284.37 | 616.32 | 216.74 | 0.00 | 0.00 | 0.00 |
| October | 467.52 | 211.63 | 255.89 | 469.41 | 388.56 | 0.00 | 0.00 | 0.00 |
| November | 289.56 | 111.27 | 178.29 | 190.91 | 578.51 | 0.00 | 0.00 | 0.00 |
| December | 226.38 | 106.82 | 119.57 | 126.59 | 738.59 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 472.42 | 197.64 | 274.77 | 495.27 | 420.64 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 226.38 | 91.29 | 119.57 | 111.07 | 83.21 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 691.81 | 312.12 | 396.02 | 966.49 | 810.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 789.23 | 517.91 | 271.33 | 716.45 | 1041.62 | 0.00 | 0.00 | 0.00 |
| February | 1044.47 | 694.18 | 350.29 | 973.68 | 1021.62 | 0.00 | 0.00 | 0.00 |
| March | 925.40 | 509.42 | 415.98 | 919.87 | 752.82 | 0.00 | 0.00 | 0.00 |
| April | 736.59 | 298.01 | 438.59 | 755.26 | 572.12 | 0.00 | 0.00 | 0.00 |
| May | 632.64 | 129.52 | 503.12 | 675.94 | 377.83 | 0.00 | 0.00 | 0.00 |
| June | 597.37 | 92.04 | 505.33 | 768.31 | 212.11 | 0.00 | 0.00 | 0.00 |
| July | 621.57 | 104.91 | 516.66 | 921.35 | 118.77 | 0.00 | 0.00 | 0.00 |
| August | 832.53 | 307.11 | 525.42 | 1242.06 | 162.85 | 0.00 | 0.00 | 0.00 |
| September | 878.55 | 441.11 | 437.44 | 1137.41 | 310.66 | 0.00 | 0.00 | 0.00 |
| October | 1241.53 | 778.55 | 462.99 | 1485.44 | 527.28 | 0.00 | 0.00 | 0.00 |
| November | 859.68 | 515.70 | 343.98 | 851.74 | 762.24 | 0.00 | 0.00 | 0.00 |
| December | 852.68 | 605.62 | 247.06 | 819.82 | 941.30 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 833.35 | 414.76 | 418.60 | 939.33 | 564.15 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 597.37 | 92.04 | 247.06 | 675.94 | 118.77 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1241.53 | 778.55 | 525.42 | 1485.44 | 1041.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
| January | 226.91 | 93.15 | 133.76 | 116.05 | 820.91 | 0.00 | 0.00 | 0.00 |
| February | 333.32 | 146.28 | 187.04 | 197.29 | 819.06 | 0.00 | 0.00 | 0.00 |
| March | 495.10 | 229.44 | 265.66 | 399.14 | 545.71 | 0.00 | 0.00 | 0.00 |
| April | 537.73 | 229.80 | 307.93 | 504.88 | 403.18 | 0.00 | 0.00 | 0.00 |
| May | 628.18 | 238.80 | 389.39 | 681.76 | 260.45 | 0.00 | 0.00 | 0.00 |
| June | 686.34 | 276.99 | 409.35 | 878.61 | 148.50 | 0.00 | 0.00 | 0.00 |
| July | 642.13 | 241.30 | 400.82 | 905.59 | 84.67 | 0.00 | 0.00 | 0.00 |
| August | 710.44 | 328.48 | 381.96 | 995.71 | 116.32 | 0.00 | 0.00 | 0.00 |
| September | 505.46 | 220.67 | 284.79 | 604.09 | 223.79 | 0.00 | 0.00 | 0.00 |
| October | 501.53 | 244.32 | 257.22 | 515.55 | 391.08 | 0.00 | 0.00 | 0.00 |
| November | 236.19 | 69.00 | 167.19 | 125.00 | 591.87 | 0.00 | 0.00 | 0.00 |
| December | 208.62 | 90.06 | 118.56 | 108.08 | 751.18 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 477.00 | 201.16 | 275.84 | 504.88 | 427.49 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 208.62 | 69.00 | 118.56 | 108.08 | 84.67 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 710.44 | 328.48 | 409.35 | 995.71 | 820.91 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_EAST_WINDOW
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.612009E+09 | 0.244518E+09 | 0.367491E+09 | 0.297502E+09 | 0.217134E+10 |
| February | 0.858241E+09 | 0.399665E+09 | 0.458576E+09 | 0.501583E+09 | 0.192224E+10 |
| March | 0.122020E+10 | 0.518580E+09 | 0.701623E+09 | 0.954019E+09 | 0.147714E+10 |
| April | 0.141357E+10 | 0.620433E+09 | 0.793134E+09 | 0.132542E+10 | 0.102534E+10 |
| May | 0.176348E+10 | 0.702774E+09 | 0.106070E+10 | 0.193998E+10 | 0.686772E+09 |
| June | 0.158470E+10 | 0.574000E+09 | 0.101070E+10 | 0.200336E+10 | 0.379188E+09 |
| July | 0.164251E+10 | 0.591331E+09 | 0.105118E+10 | 0.231961E+10 | 0.222880E+09 |
| August | 0.185294E+10 | 0.835973E+09 | 0.101697E+10 | 0.258864E+10 | 0.300116E+09 |
| September | 0.134137E+10 | 0.604278E+09 | 0.737090E+09 | 0.159750E+10 | 0.561782E+09 |
| October | 0.125220E+10 | 0.566817E+09 | 0.685386E+09 | 0.125727E+10 | 0.104073E+10 |
| November | 0.750549E+09 | 0.288420E+09 | 0.462129E+09 | 0.494828E+09 | 0.149950E+10 |
| December | 0.606348E+09 | 0.286104E+09 | 0.320244E+09 | 0.339058E+09 | 0.197823E+10 |
| Annual Sum or Average | 0.148981E+11 | 0.623289E+10 | 0.866522E+10 | 0.156188E+11 | 0.132652E+11 |
| Minimum of Months | 0.606348E+09 | 0.244518E+09 | 0.320244E+09 | 0.297502E+09 | 0.222880E+09 |
| Maximum of Months | 0.185294E+10 | 0.835973E+09 | 0.106070E+10 | 0.258864E+10 | 0.217134E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_SOUTH_WINDOW
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.211388E+10 | 0.138716E+10 | 0.726723E+09 | 0.191894E+10 | 0.278989E+10 |
| February | 0.252678E+10 | 0.167937E+10 | 0.847411E+09 | 0.235553E+10 | 0.247149E+10 |
| March | 0.247859E+10 | 0.136444E+10 | 0.111416E+10 | 0.246379E+10 | 0.201635E+10 |
| April | 0.190925E+10 | 0.772436E+09 | 0.113681E+10 | 0.195765E+10 | 0.148293E+10 |
| May | 0.169447E+10 | 0.346919E+09 | 0.134756E+10 | 0.181043E+10 | 0.101199E+10 |
| June | 0.154839E+10 | 0.238574E+09 | 0.130981E+10 | 0.199147E+10 | 0.549795E+09 |
| July | 0.166481E+10 | 0.280986E+09 | 0.138382E+10 | 0.246775E+10 | 0.318122E+09 |
| August | 0.222985E+10 | 0.822572E+09 | 0.140728E+10 | 0.332674E+10 | 0.436189E+09 |
| September | 0.227719E+10 | 0.114335E+10 | 0.113384E+10 | 0.294815E+10 | 0.805236E+09 |
| October | 0.332532E+10 | 0.208526E+10 | 0.124006E+10 | 0.397861E+10 | 0.141228E+10 |
| November | 0.222829E+10 | 0.133669E+10 | 0.891602E+09 | 0.220771E+10 | 0.197572E+10 |
| December | 0.228381E+10 | 0.162208E+10 | 0.661730E+09 | 0.219580E+10 | 0.252118E+10 |
| Annual Sum or Average | 0.262806E+11 | 0.130798E+11 | 0.132008E+11 | 0.296226E+11 | 0.177912E+11 |
| Minimum of Months | 0.154839E+10 | 0.238574E+09 | 0.661730E+09 | 0.181043E+10 | 0.318122E+09 |
| Maximum of Months | 0.332532E+10 | 0.208526E+10 | 0.140728E+10 | 0.397861E+10 | 0.278989E+10 |
Report: WindowEnergyReportMonthly
For: DINING_WALL_WEST_WINDOW
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
| January | 0.607758E+09 | 0.249502E+09 | 0.358255E+09 | 0.310835E+09 | 0.219871E+10 |
| February | 0.806367E+09 | 0.353892E+09 | 0.452475E+09 | 0.477274E+09 | 0.198147E+10 |
| March | 0.132609E+10 | 0.614542E+09 | 0.711547E+09 | 0.106906E+10 | 0.146164E+10 |
| April | 0.139379E+10 | 0.595632E+09 | 0.798161E+09 | 0.130865E+10 | 0.104504E+10 |
| May | 0.168253E+10 | 0.639596E+09 | 0.104293E+10 | 0.182602E+10 | 0.697598E+09 |
| June | 0.177899E+10 | 0.717955E+09 | 0.106103E+10 | 0.227736E+10 | 0.384913E+09 |
| July | 0.171987E+10 | 0.646309E+09 | 0.107356E+10 | 0.242552E+10 | 0.226775E+09 |
| August | 0.190285E+10 | 0.879796E+09 | 0.102305E+10 | 0.266690E+10 | 0.311540E+09 |
| September | 0.131017E+10 | 0.571982E+09 | 0.738183E+09 | 0.156580E+10 | 0.580062E+09 |
| October | 0.134331E+10 | 0.654377E+09 | 0.688933E+09 | 0.138084E+10 | 0.104748E+10 |
| November | 0.612196E+09 | 0.178850E+09 | 0.433346E+09 | 0.324006E+09 | 0.153414E+10 |
| December | 0.558769E+09 | 0.241205E+09 | 0.317563E+09 | 0.289479E+09 | 0.201197E+10 |
| Annual Sum or Average | 0.150427E+11 | 0.634364E+10 | 0.869904E+10 | 0.159217E+11 | 0.134813E+11 |
| Minimum of Months | 0.558769E+09 | 0.178850E+09 | 0.317563E+09 | 0.289479E+09 | 0.226775E+09 |
| Maximum of Months | 0.190285E+10 | 0.879796E+09 | 0.107356E+10 | 0.266690E+10 | 0.219871E+10 |
Report: WindowZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 835.93 | 2565.57 | 1244.64 | 702.35 | 542.29 | 0.00 | 0.00 |
| February | 1231.92 | 2488.87 | 1732.55 | 1005.67 | 726.88 | 0.00 | 0.00 |
| March | 1595.16 | 1769.99 | 1876.08 | 932.48 | 943.59 | 0.00 | 0.00 |
| April | 1714.80 | 1314.18 | 1819.68 | 767.17 | 1052.51 | 0.00 | 0.00 |
| May | 2040.61 | 853.30 | 1919.23 | 630.71 | 1288.53 | 0.00 | 0.00 |
| June | 2402.85 | 489.93 | 1895.09 | 590.48 | 1304.61 | 0.00 | 0.00 |
| July | 2687.13 | 280.80 | 1876.94 | 566.99 | 1309.95 | 0.00 | 0.00 |
| August | 3194.10 | 381.06 | 2234.78 | 947.71 | 1287.07 | 0.00 | 0.00 |
| September | 2335.72 | 729.10 | 1901.51 | 894.91 | 1006.60 | 0.00 | 0.00 |
| October | 2436.20 | 1272.73 | 2210.59 | 1234.49 | 976.10 | 0.00 | 0.00 |
| November | 1107.17 | 1872.15 | 1385.43 | 695.97 | 689.46 | 0.00 | 0.00 |
| December | 944.70 | 2321.29 | 1287.68 | 802.49 | 485.19 | 0.00 | 0.00 |
| Annual Sum or Average | 1882.35 | 1355.17 | 1782.77 | 813.56 | 969.21 | 0.00 | 0.00 |
| Minimum of Months | 835.93 | 280.80 | 1244.64 | 566.99 | 485.19 | 0.00 | 0.00 |
| Maximum of Months | 3194.10 | 2565.57 | 2234.78 | 1234.49 | 1309.95 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DINING
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.223895E+10 | 0.687161E+10 | 0.333365E+10 | 0.188118E+10 | 0.145247E+10 | 0.00 | 0.00 |
| February | 0.298025E+10 | 0.602107E+10 | 0.419139E+10 | 0.243293E+10 | 0.175846E+10 | 0.00 | 0.00 |
| March | 0.427248E+10 | 0.474074E+10 | 0.502488E+10 | 0.249756E+10 | 0.252732E+10 | 0.00 | 0.00 |
| April | 0.444476E+10 | 0.340635E+10 | 0.471661E+10 | 0.198850E+10 | 0.272811E+10 | 0.00 | 0.00 |
| May | 0.546556E+10 | 0.228549E+10 | 0.514048E+10 | 0.168929E+10 | 0.345119E+10 | 0.00 | 0.00 |
| June | 0.622819E+10 | 0.126989E+10 | 0.491208E+10 | 0.153053E+10 | 0.338155E+10 | 0.00 | 0.00 |
| July | 0.719721E+10 | 0.752093E+09 | 0.502719E+10 | 0.151863E+10 | 0.350857E+10 | 0.00 | 0.00 |
| August | 0.855507E+10 | 0.102064E+10 | 0.598563E+10 | 0.253834E+10 | 0.344729E+10 | 0.00 | 0.00 |
| September | 0.605419E+10 | 0.188982E+10 | 0.492872E+10 | 0.231961E+10 | 0.260912E+10 | 0.00 | 0.00 |
| October | 0.652511E+10 | 0.340888E+10 | 0.592084E+10 | 0.330646E+10 | 0.261438E+10 | 0.00 | 0.00 |
| November | 0.286979E+10 | 0.485260E+10 | 0.359104E+10 | 0.180396E+10 | 0.178708E+10 | 0.00 | 0.00 |
| December | 0.253030E+10 | 0.621735E+10 | 0.344893E+10 | 0.214939E+10 | 0.129954E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.593619E+11 | 0.427365E+11 | 0.562214E+11 | 0.256564E+11 | 0.305651E+11 | 0.00 | 0.00 |
| Minimum of Months | 0.223895E+10 | 0.752093E+09 | 0.333365E+10 | 0.151863E+10 | 0.129954E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.855507E+10 | 0.687161E+10 | 0.598563E+10 | 0.330646E+10 | 0.350857E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
| January | 1.17 | -0.7 | -4.4 | 5.65 | -10.4 | 36.91 | 88.07 | 0.05 |
| February | -0.2 | -2.6 | -7.5 | 5.07 | -13.4 | 46.98 | 136.68 | 0.04 |
| March | 5.59 | 3.43 | 0.29 | 5.58 | -4.1 | 68.24 | 153.73 | 0.03 |
| April | 10.94 | 8.00 | 4.75 | 4.99 | 0.53 | 82.64 | 161.98 | 0.05 |
| May | 16.05 | 12.31 | 9.14 | 4.42 | 7.77 | 109.28 | 173.60 | 0.03 |
| June | 21.71 | 18.08 | 15.84 | 4.92 | 13.23 | 112.36 | 186.51 | 0.01 |
| July | 25.05 | 21.76 | 20.26 | 4.06 | 17.39 | 114.46 | 172.96 | 0.02 |
| August | 24.79 | 19.84 | 17.14 | 4.19 | 14.42 | 95.56 | 226.16 | 0.00 |
| September | 19.96 | 15.96 | 13.24 | 3.91 | 10.59 | 73.65 | 166.08 | 0.03 |
| October | 14.02 | 11.03 | 7.95 | 4.86 | 2.64 | 61.34 | 179.75 | 0.00 |
| November | 7.31 | 4.98 | 2.14 | 5.60 | -4.0 | 48.23 | 90.71 | 0.03 |
| December | 3.33 | 0.91 | -2.8 | 5.64 | -8.5 | 30.23 | 98.59 | 0.04 |
| Annual Sum or Average | 12.55 | 9.49 | 6.43 | 4.91 | 2.28 | 73.48 | 153.05 | 0.03 |
| Minimum of Months | -0.2 | -2.6 | -7.5 | 3.91 | -13.4 | 30.23 | 88.07 | 0.00 |
| Maximum of Months | 25.05 | 21.76 | 20.26 | 5.65 | 17.39 | 114.46 | 226.16 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 12.20 | 24-JAN-12:20 | 11.81 | 11.50 | 1.00 | 8.15 | 93.67 | 0.00 |
| February | 10.00 | 20-FEB-11:00 | 4.36 | -3.3 | 2.60 | -3.9 | 151.50 | 540.00 |
| March | 22.20 | 27-MAR-15:00 | 16.34 | 12.80 | 6.70 | 11.65 | 136.50 | 590.00 |
| April | 26.70 | 07-APR-12:00 | 16.40 | 9.40 | 6.20 | 11.65 | 179.00 | 713.50 |
| May | 30.00 | 30-MAY-12:00 | 18.00 | 10.60 | 5.20 | 17.39 | 233.50 | 730.00 |
| June | 36.70 | 19-JUN-11:00 | 24.28 | 19.40 | 5.20 | 24.83 | 185.00 | 771.50 |
| July | 33.90 | 07-JUL-11:00 | 23.31 | 18.90 | 3.60 | 23.82 | 331.00 | 570.00 |
| August | 33.90 | 24-AUG-14:00 | 20.23 | 12.80 | 8.80 | 21.61 | 240.00 | 432.00 |
| September | 31.10 | 01-SEP-13:00 | 17.34 | 8.30 | 4.60 | 18.46 | 182.00 | 662.00 |
| October | 25.00 | 04-OCT-12:00 | 18.54 | 15.00 | 5.20 | 11.27 | 171.50 | 695.00 |
| November | 17.80 | 04-NOV-12:20 | 12.57 | 8.50 | 3.60 | 6.15 | 182.50 | 595.67 |
| December | 12.20 | 17-DEC-12:20 | 4.65 | -6.1 | 4.27 | -4.7 | 53.17 | 801.67 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 10.00 | 4.36 | -6.1 | 1.00 | -4.7 | 53.17 | 0.00 | |
| Maximum of Months | 36.70 | 24.28 | 19.40 | 8.80 | 24.83 | 331.00 | 801.67 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | -12.2 | 02-JAN-04:00 | -13.6 | -19.4 | 2.60 | -30.7 | 0.00 | 0.00 |
| February | -13.9 | 06-FEB-02:00 | -15.3 | -22.8 | 7.20 | -34.1 | 0.00 | 0.00 |
| March | -5.0 | 23-MAR-03:00 | -7.6 | -14.4 | 1.50 | -23.9 | 0.00 | 0.00 |
| April | 2.20 | 01-APR-03:00 | 0.57 | -1.7 | 3.10 | -6.6 | 0.00 | 0.00 |
| May | 6.10 | 01-MAY-04:00 | 4.33 | 2.20 | 3.60 | -9.7 | 25.50 | 0.00 |
| June | 13.30 | 03-JUN-02:00 | 9.35 | 5.60 | 4.60 | -2.1 | 0.00 | 0.00 |
| July | 18.30 | 02-JUL-02:00 | 17.54 | 17.20 | 0.00 | 5.33 | 0.00 | 0.00 |
| August | 15.00 | 08-AUG-04:00 | 12.47 | 10.60 | 3.10 | 3.06 | 0.00 | 0.00 |
| September | 10.00 | 24-SEP-05:00 | 8.56 | 7.20 | 2.60 | -3.4 | 18.50 | 158.50 |
| October | 2.20 | 09-OCT-03:00 | 1.71 | 1.10 | 0.00 | -13.7 | 0.00 | 0.00 |
| November | -4.4 | 24-NOV-05:00 | -6.2 | -10.0 | 1.50 | -19.7 | 0.00 | 0.00 |
| December | -8.3 | 31-DEC-23:00 | -10.6 | -18.9 | 9.30 | -26.2 | 0.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | -13.9 | -15.3 | -22.8 | 0.00 | -34.1 | 0.00 | 0.00 | |
| Maximum of Months | 18.30 | 17.54 | 17.20 | 9.30 | 5.33 | 25.50 | 158.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 11.93 | 24-JAN-11:00 | 12.20 | 11.70 | 1.50 | 8.15 | 103.00 | 0.00 |
| February | 6.67 | 28-FEB-09:00 | 7.20 | 6.10 | 4.10 | 2.01 | 101.50 | 0.00 |
| March | 16.99 | 27-MAR-12:00 | 20.60 | 15.00 | 3.60 | 10.50 | 295.50 | 565.50 |
| April | 17.70 | 09-APR-10:00 | 21.70 | 15.60 | 4.10 | 14.84 | 244.50 | 281.50 |
| May | 20.43 | 31-MAY-12:00 | 26.10 | 17.80 | 4.10 | 17.03 | 214.00 | 772.00 |
| June | 24.96 | 15-JUN-11:00 | 31.10 | 22.80 | 5.20 | 22.47 | 380.00 | 460.00 |
| July | 26.10 | 08-JUL-11:00 | 32.20 | 23.90 | 5.20 | 22.47 | 354.00 | 501.50 |
| August | 25.84 | 03-AUG-13:00 | 30.00 | 24.40 | 6.20 | 20.57 | 298.00 | 500.00 |
| September | 23.57 | 07-SEP-13:00 | 27.20 | 22.20 | 6.20 | 15.02 | 148.00 | 730.50 |
| October | 19.76 | 25-OCT-10:00 | 25.00 | 17.20 | 7.70 | 14.84 | 189.00 | 308.50 |
| November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
| December | 10.26 | 25-DEC-08:00 | 10.60 | 10.00 | 3.60 | 6.15 | 43.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 6.67 | 7.20 | 6.10 | 1.50 | 2.01 | 43.00 | 0.00 | |
| Maximum of Months | 26.10 | 32.20 | 24.40 | 8.20 | 22.47 | 380.00 | 772.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
| January | 11.70 | 18-JAN-15:00 | 12.20 | 11.93 | 14.90 | 8.15 | 22.00 | 2.00 |
| February | 6.10 | 28-FEB-10:20 | 7.03 | 6.58 | 3.43 | 1.87 | 109.83 | 0.00 |
| March | 15.00 | 27-MAR-12:20 | 18.00 | 16.18 | 3.93 | 10.11 | 271.83 | 611.17 |
| April | 15.60 | 09-APR-10:00 | 21.70 | 17.70 | 4.10 | 14.84 | 244.50 | 281.50 |
| May | 18.00 | 18-MAY-09:00 | 18.00 | 18.00 | 4.60 | 15.39 | 265.50 | 12.00 |
| June | 22.80 | 15-JUN-11:00 | 31.10 | 24.96 | 5.20 | 22.47 | 380.00 | 460.00 |
| July | 24.40 | 09-JUL-07:00 | 27.20 | 25.17 | 2.10 | 15.39 | 195.00 | 504.00 |
| August | 25.00 | 03-AUG-19:00 | 26.10 | 25.32 | 5.70 | 19.35 | 0.00 | 0.00 |
| September | 22.20 | 07-SEP-13:00 | 27.20 | 23.57 | 6.20 | 15.02 | 148.00 | 730.50 |
| October | 18.30 | 05-OCT-18:00 | 19.40 | 18.62 | 7.70 | 6.55 | 0.00 | 0.00 |
| November | 16.10 | 10-NOV-07:00 | 16.10 | 16.10 | 8.20 | 12.98 | 71.50 | 0.00 |
| December | 10.00 | 25-DEC-08:00 | 10.60 | 10.26 | 3.60 | 6.15 | 43.00 | 0.00 |
| Annual Sum or Average | ||||||||
| Minimum of Months | 6.10 | 7.03 | 6.58 | 2.10 | 1.87 | 0.00 | 0.00 | |
| Maximum of Months | 25.00 | 31.10 | 25.32 | 14.90 | 22.47 | 380.00 | 730.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
| January | 18.00 | 13.00 | 16.00 | 10.03 | 13.58 | 0.00 |
| February | 18.00 | 13.00 | 16.00 | 9.54 | 21.42 | 0.00 |
| March | 18.00 | 13.00 | 16.00 | 10.65 | 30.29 | 0.00 |
| April | 18.00 | 13.00 | 16.00 | 13.15 | 37.02 | 0.00 |
| May | 18.00 | 13.00 | 16.00 | 16.36 | 45.86 | 0.00 |
| June | 18.00 | 13.00 | 16.00 | 19.42 | 49.74 | 0.00 |
| July | 18.00 | 13.00 | 16.00 | 21.50 | 48.12 | 0.00 |
| August | 18.00 | 13.00 | 16.00 | 22.05 | 49.54 | 0.00 |
| September | 18.00 | 13.00 | 16.00 | 20.89 | 34.71 | 0.00 |
| October | 18.00 | 13.00 | 16.00 | 18.36 | 29.93 | 0.00 |
| November | 18.00 | 13.00 | 16.00 | 15.14 | 17.00 | 0.00 |
| December | 18.00 | 13.00 | 16.00 | 12.10 | 12.41 | 0.00 |
| Annual Sum or Average | 18.00 | 13.00 | 16.00 | 15.80 | 32.53 | 0.00 |
| Minimum of Months | 18.00 | 13.00 | 16.00 | 9.54 | 12.41 | 0.00 |
| Maximum of Months | 18.00 | 13.00 | 16.00 | 22.05 | 49.74 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWH BOOSTER G WATER HEATER
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.668151E+10 | -0.650583E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175676541.5 | 82.17 | 0.00 | 0.00 |
| February | 0.604746E+10 | -0.588831E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -159155273.6 | 82.17 | 0.00 | 0.00 |
| March | 0.675128E+10 | -0.657757E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -173702038.6 | 82.17 | 0.00 | 0.00 |
| April | 0.647856E+10 | -0.631593E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -162622486.3 | 82.17 | 0.00 | 0.00 |
| May | 0.670290E+10 | -0.654241E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -160488630.7 | 82.17 | 0.00 | 0.00 |
| June | 0.651303E+10 | -0.636095E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -152087838.9 | 82.17 | 0.00 | 0.00 |
| July | 0.665421E+10 | -0.649739E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156820868.2 | 82.17 | 0.00 | 0.00 |
| August | 0.673580E+10 | -0.657898E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -156821145.8 | 82.17 | 0.00 | 0.00 |
| September | 0.646996E+10 | -0.631734E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -152617936.2 | 82.17 | 0.00 | 0.00 |
| October | 0.666674E+10 | -0.650443E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -162316193.5 | 82.17 | 0.00 | 0.00 |
| November | 0.646171E+10 | -0.629624E+10 | 0.00 | 0.00 | 720.00 | 0.00 | -165471449.9 | 82.17 | 0.00 | 0.00 |
| December | 0.667286E+10 | -0.649740E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -175460191.9 | 82.17 | 0.00 | 0.00 |
| Annual Sum or Average | 0.788360E+11 | -0.768828E+11 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.195324E+10 | 82.17 | 0.00 | 0.00 |
| Minimum of Months | 0.604746E+10 | -0.657898E+10 | 0.00 | 0.00 | 672.00 | 0.00 | -175676541.5 | 82.17 | 0.00 | 0.00 |
| Maximum of Months | 0.675128E+10 | -0.588831E+10 | 0.00 | 0.00 | 744.00 | 0.00 | -152087838.9 | 82.17 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
| January | 0.253743E+11 | -0.243371E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103726E+10 | 60.05 | 0.00 | 0.00 |
| February | 0.231843E+11 | -0.222430E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -941271257.5 | 60.05 | 0.00 | 0.00 |
| March | 0.253168E+11 | -0.242976E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101918E+10 | 60.05 | 0.00 | 0.00 |
| April | 0.230891E+11 | -0.221529E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -936159209.7 | 60.05 | 0.00 | 0.00 |
| May | 0.222768E+11 | -0.213786E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -898190456.2 | 60.05 | 0.00 | 0.00 |
| June | 0.201596E+11 | -0.193199E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -839699236.9 | 60.05 | 0.00 | 0.00 |
| July | 0.195843E+11 | -0.187197E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -864606590.3 | 60.05 | 0.00 | 0.00 |
| August | 0.195530E+11 | -0.186884E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -864608553.7 | 60.05 | 0.00 | 0.00 |
| September | 0.193393E+11 | -0.184948E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -844552520.9 | 60.05 | 0.00 | 0.00 |
| October | 0.211911E+11 | -0.202762E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -914924539.1 | 60.05 | 0.00 | 0.00 |
| November | 0.221033E+11 | -0.211411E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -962245535.5 | 60.05 | 0.00 | 0.00 |
| December | 0.243294E+11 | -0.232941E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103528E+10 | 60.05 | 0.00 | 0.00 |
| Annual Sum or Average | 0.265501E+12 | -0.254343E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.111580E+11 | 60.05 | 0.00 | 0.00 |
| Minimum of Months | 0.193393E+11 | -0.243371E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.103726E+10 | 60.05 | 0.00 | 0.00 |
| Maximum of Months | 0.253743E+11 | -0.184948E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -839699236.9 | 60.05 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
| January | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 216.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 275.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 261.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 372.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 365.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 285.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 305.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 240.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 211.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 3472.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 199.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 389.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.454094E+11 | 104398.02 | 01-JAN-04:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.458301E+11 | 104398.02 | 01-FEB-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.225085E+11 | 104398.02 | 14-MAR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.612036E+10 | 72840.07 | 03-APR-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.282501E+09 | 18544.23 | 01-MAY-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 2398485.31 | 1273.51 | 24-SEP-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.142990E+10 | 30200.84 | 29-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.151927E+11 | 104398.02 | 20-NOV-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.319275E+11 | 104398.02 | 02-DEC-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.168703E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.458301E+11 | 104398.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| HEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.247410E+11 | 51013.49 | 02-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.262058E+11 | 46428.29 | 06-FEB-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.115035E+11 | 41508.41 | 23-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.239373E+10 | 17566.68 | 01-APR-04:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 28848040.69 | 8019.95 | 15-MAY-04:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.660102E+09 | 16176.93 | 09-OCT-04:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.707845E+10 | 37861.38 | 23-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.163286E+11 | 31167.61 | 31-DEC-23:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.889399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.262058E+11 | 51013.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:01 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:01 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.863402E+09 | 0.676699E+09 | 26091.08 | 27-MAR-17:10 | 19854.57 | 0.00 |
| April | 0.00 | 0.00 | 0.779222E+10 | 0.647768E+10 | 58131.73 | 08-APR-03:01 | 45578.24 | 0.00 |
| May | 0.00 | 0.00 | 0.250940E+11 | 0.200507E+11 | 98998.15 | 30-MAY-03:01 | 64637.20 | 0.00 |
| June | 0.00 | 0.00 | 0.702614E+11 | 0.450960E+11 | 108073.49 | 27-JUN-03:01 | 49050.49 | 0.00 |
| July | 0.00 | 0.00 | 0.109622E+12 | 0.632043E+11 | 108073.49 | 08-JUL-03:02 | 50984.56 | 0.00 |
| August | 0.00 | 0.00 | 0.100738E+12 | 0.650006E+11 | 108073.49 | 13-AUG-03:02 | 54023.51 | 0.00 |
| September | 0.00 | 0.00 | 0.556429E+11 | 0.385135E+11 | 108073.49 | 08-SEP-03:01 | 51350.88 | 0.00 |
| October | 0.00 | 0.00 | 0.247634E+11 | 0.168487E+11 | 103692.59 | 06-OCT-03:01 | 56198.00 | 0.00 |
| November | 0.00 | 0.00 | 0.163936E+10 | 0.136974E+10 | 18201.54 | 04-NOV-13:00 | 14939.32 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.396417E+12 | 0.257238E+12 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.109622E+12 | 0.650006E+11 | 108073.49 | 64637.20 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| HEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
| January | 0.00 | 0.00 | 4439555.74 | 2527938.86 | 4226.70 | 24-JAN-04:43 | 1993.64 | 0.00 |
| February | 0.00 | 0.00 | 931897.23 | 546851.67 | 1069.13 | 24-FEB-04:40 | 628.69 | 0.00 |
| March | 0.00 | 0.00 | 0.198487E+09 | 0.139259E+09 | 10795.87 | 27-MAR-16:20 | 8100.99 | 0.00 |
| April | 0.00 | 0.00 | 0.256624E+10 | 0.211992E+10 | 43112.80 | 08-APR-03:01 | 26086.96 | 0.00 |
| May | 0.00 | 0.00 | 0.965603E+10 | 0.767439E+10 | 43112.80 | 19-MAY-03:01 | 17882.14 | 0.00 |
| June | 0.00 | 0.00 | 0.386973E+11 | 0.231959E+11 | 47901.15 | 19-JUN-03:11 | 18576.69 | 0.00 |
| July | 0.00 | 0.00 | 0.681014E+11 | 0.362084E+11 | 47901.15 | 20-JUL-10:04 | 20893.21 | 0.00 |
| August | 0.00 | 0.00 | 0.593776E+11 | 0.361712E+11 | 47901.15 | 02-AUG-17:20 | 24684.57 | 0.00 |
| September | 0.00 | 0.00 | 0.290438E+11 | 0.187247E+11 | 47767.30 | 14-SEP-03:01 | 16038.68 | 0.00 |
| October | 0.00 | 0.00 | 0.958596E+10 | 0.588629E+10 | 44193.92 | 06-OCT-03:11 | 19271.89 | 0.00 |
| November | 0.00 | 0.00 | 0.229067E+09 | 0.168607E+09 | 39050.38 | 04-NOV-03:01 | 22413.28 | 0.00 |
| December | 0.00 | 0.00 | 5970125.81 | 3839540.35 | 3607.66 | 05-DEC-04:43 | 2354.41 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.217467E+12 | 0.130296E+12 | 0.00 | |||
| Minimum of Months | 0.00 | 0.00 | 931897.23 | 546851.67 | 1069.13 | 628.69 | 0.00 | |
| Maximum of Months | 0.00 | 0.00 | 0.681014E+11 | 0.362084E+11 | 47901.15 | 26086.96 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:01 | 9052.64 | 17673.21 | 31-JAN-08:00 |
| February | 0.00 | 0.00 | 01-FEB-00:01 | 9160.45 | 17697.25 | 09-FEB-19:50 |
| March | 0.00 | 0.00 | 01-MAR-00:02 | 9037.92 | 17560.91 | 01-MAR-08:00 |
| April | 0.00 | 0.00 | 01-APR-00:01 | 8513.57 | 16819.78 | 03-APR-18:50 |
| May | 0.00 | 0.00 | 01-MAY-00:01 | 7949.52 | 15844.15 | 01-MAY-06:27 |
| June | 0.00 | 0.00 | 01-JUN-00:01 | 7421.99 | 14674.77 | 01-JUN-06:27 |
| July | 0.00 | 0.00 | 01-JUL-00:01 | 6958.09 | 13702.19 | 03-JUL-06:45 |
| August | 0.00 | 0.00 | 01-AUG-00:01 | 6946.41 | 13382.07 | 31-AUG-06:37 |
| September | 0.00 | 0.00 | 01-SEP-00:01 | 7104.09 | 14011.76 | 29-SEP-18:15 |
| October | 0.00 | 0.00 | 01-OCT-00:01 | 7538.44 | 15109.56 | 31-OCT-19:00 |
| November | 0.00 | 0.00 | 01-NOV-00:01 | 8123.72 | 16242.35 | 30-NOV-19:20 |
| December | 0.00 | 0.00 | 01-DEC-00:02 | 8663.74 | 17148.60 | 29-DEC-20:00 |
| Annual Sum or Average | 0.00 | 8032.72 | ||||
| Minimum of Months | 0.00 | 0.00 | 6946.41 | 13382.07 | ||
| Maximum of Months | 0.00 | 0.00 | 9160.45 | 17697.25 |
Report: FanReportMonthly
For: DINING EXHAUST FAN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | -0.0 |
| February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | 0.00 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:02 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 01-APR-00:01 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 01-MAY-00:01 | 0.00 |
| June | 0.00 | -0.0 | 0.00 | 01-JUN-00:01 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 01-JUL-00:01 | 0.00 |
| August | 0.00 | -0.0 | 0.00 | 01-AUG-00:01 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
| November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
| December | 0.00 | -0.0 | 0.00 | 01-DEC-00:02 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: KITCHEN EXHAUST FAN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.00 | -0.0 | 0.00 | 01-JAN-00:01 | -0.0 |
| February | 0.00 | -0.0 | 0.00 | 01-FEB-00:01 | -0.0 |
| March | 0.00 | -0.0 | 0.00 | 01-MAR-00:02 | 0.00 |
| April | 0.00 | -0.0 | 0.00 | 01-APR-00:01 | 0.00 |
| May | 0.00 | -0.0 | 0.00 | 01-MAY-00:01 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 01-JUN-00:01 | 0.00 |
| July | 0.00 | -0.0 | 0.00 | 01-JUL-00:01 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 01-AUG-00:01 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 01-SEP-00:01 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 01-OCT-00:01 | 0.00 |
| November | 0.00 | -0.0 | 0.00 | 01-NOV-00:01 | 0.00 |
| December | 0.00 | -0.0 | 0.00 | 01-DEC-00:02 | 0.00 |
| Annual Sum or Average | 0.00 | -0.0 | |||
| Minimum of Months | 0.00 | -0.0 | 0.00 | -0.0 | |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ FAN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.146303E+11 | 1.14 | 6440.61 | 01-JAN-00:18 | 1.34 |
| February | 0.132644E+11 | 1.15 | 6440.61 | 01-FEB-08:10 | 1.33 |
| March | 0.145040E+11 | 1.13 | 6440.61 | 01-MAR-08:20 | 1.33 |
| April | 0.139223E+11 | 1.11 | 6440.61 | 01-APR-04:01 | 1.33 |
| May | 0.143903E+11 | 1.12 | 6440.61 | 01-MAY-04:03 | 1.32 |
| June | 0.140270E+11 | 1.14 | 6440.61 | 01-JUN-11:40 | 1.32 |
| July | 0.146177E+11 | 1.14 | 6440.61 | 13-JUL-21:10 | 1.31 |
| August | 0.145805E+11 | 1.15 | 6440.61 | 01-AUG-04:30 | 1.31 |
| September | 0.140076E+11 | 1.14 | 6440.61 | 01-SEP-08:07 | 1.32 |
| October | 0.144047E+11 | 1.13 | 6440.61 | 01-OCT-17:45 | 1.32 |
| November | 0.140017E+11 | 1.12 | 6440.61 | 01-NOV-04:04 | 1.33 |
| December | 0.145141E+11 | 1.14 | 6440.61 | 01-DEC-05:06 | 1.33 |
| Annual Sum or Average | 0.170865E+12 | 1.13 | |||
| Minimum of Months | 0.132644E+11 | 1.11 | 6440.61 | 1.31 | |
| Maximum of Months | 0.146303E+11 | 1.15 | 6440.61 | 1.34 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ FAN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| FAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
| January | 0.652897E+10 | 1.14 | 2924.83 | 01-JAN-00:12 | 1.37 |
| February | 0.589661E+10 | 1.14 | 2924.83 | 01-FEB-10:32 | 1.36 |
| March | 0.653159E+10 | 1.15 | 2924.83 | 02-MAR-07:20 | 1.36 |
| April | 0.633456E+10 | 1.16 | 2924.83 | 01-APR-15:10 | 1.36 |
| May | 0.657534E+10 | 1.19 | 2924.83 | 01-MAY-11:13 | 1.36 |
| June | 0.645776E+10 | 1.28 | 2924.83 | 01-JUN-10:37 | 1.35 |
| July | 0.678861E+10 | 1.30 | 2924.83 | 01-JUL-06:30 | 1.34 |
| August | 0.675962E+10 | 1.31 | 2924.83 | 01-AUG-09:00 | 1.35 |
| September | 0.645125E+10 | 1.28 | 2924.83 | 01-SEP-10:53 | 1.35 |
| October | 0.658681E+10 | 1.22 | 2924.83 | 02-OCT-09:40 | 1.35 |
| November | 0.633047E+10 | 1.16 | 2924.83 | 01-NOV-04:08 | 1.36 |
| December | 0.652924E+10 | 1.14 | 2924.83 | 01-DEC-05:10 | 1.36 |
| Annual Sum or Average | 0.777708E+11 | 1.21 | |||
| Minimum of Months | 0.589661E+10 | 1.14 | 2924.83 | 1.34 | |
| Maximum of Months | 0.678861E+10 | 1.31 | 2924.83 | 1.37 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| PUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
| January | 37879553.69 | 11363866.11 | 17.86 | 01-JAN-00:01 | 5.36 | 5.36 | 49.31 | 0.14 |
| February | 34213790.43 | 10264137.13 | 17.86 | 01-FEB-00:01 | 5.36 | 5.36 | 48.44 | 0.14 |
| March | 37879553.69 | 11363866.11 | 17.86 | 01-MAR-00:02 | 5.36 | 5.36 | 48.80 | 0.14 |
| April | 36657632.61 | 10997289.78 | 17.86 | 01-APR-05:10 | 5.36 | 5.36 | 52.58 | 0.14 |
| May | 37879553.69 | 11363866.11 | 17.86 | 01-MAY-05:10 | 5.36 | 5.36 | 53.04 | 0.14 |
| June | 36657632.61 | 10997289.78 | 17.86 | 01-JUN-05:10 | 5.36 | 5.36 | 53.56 | 0.14 |
| July | 37879553.69 | 11363866.11 | 17.86 | 01-JUL-05:10 | 5.36 | 5.36 | 53.97 | 0.14 |
| August | 37879553.69 | 11363866.11 | 17.86 | 01-AUG-05:10 | 5.36 | 5.36 | 54.18 | 0.14 |
| September | 36657632.61 | 10997289.78 | 17.86 | 01-SEP-05:10 | 5.36 | 5.36 | 54.13 | 0.14 |
| October | 37879553.69 | 11363866.11 | 17.86 | 01-OCT-05:10 | 5.36 | 5.36 | 53.63 | 0.14 |
| November | 36657632.61 | 10997289.78 | 17.86 | 01-NOV-05:10 | 5.36 | 5.36 | 53.35 | 0.14 |
| December | 37879553.69 | 11363866.11 | 17.86 | 01-DEC-00:02 | 5.36 | 5.36 | 49.76 | 0.14 |
| Annual Sum or Average | 0.446001E+09 | 0.133800E+09 | ||||||
| Minimum of Months | 34213790.43 | 10264137.13 | 17.86 | 5.36 | 5.36 | 48.44 | 0.14 | |
| Maximum of Months | 37879553.69 | 11363866.11 | 17.86 | 5.36 | 5.36 | 54.18 | 0.14 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| PLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
| January | 0.00 | 0.00 | 01-JAN-00:01 | 49.31 | 60.06 | 9052.64 | 17673.21 | 31-JAN-08:00 |
| February | 0.00 | 0.00 | 01-FEB-00:01 | 48.44 | 60.05 | 9160.45 | 17697.25 | 09-FEB-19:50 |
| March | 0.00 | 0.00 | 01-MAR-00:02 | 48.80 | 60.05 | 9037.92 | 17560.91 | 01-MAR-08:00 |
| April | 0.00 | 0.00 | 01-APR-00:01 | 50.40 | 50.40 | 8513.57 | 16819.78 | 03-APR-18:50 |
| May | 0.00 | 0.00 | 01-MAY-00:01 | 50.98 | 50.98 | 7949.52 | 15844.15 | 01-MAY-06:27 |
| June | 0.00 | 0.00 | 01-JUN-00:01 | 51.65 | 51.65 | 7421.99 | 14674.77 | 01-JUN-06:27 |
| July | 0.00 | 0.00 | 01-JUL-00:01 | 52.18 | 52.18 | 6958.09 | 13702.19 | 03-JUL-06:45 |
| August | 0.00 | 0.00 | 01-AUG-00:01 | 52.47 | 52.47 | 6946.41 | 13382.07 | 31-AUG-06:37 |
| September | 0.00 | 0.00 | 01-SEP-00:01 | 52.41 | 52.41 | 7104.09 | 14011.76 | 29-SEP-18:15 |
| October | 0.00 | 0.00 | 01-OCT-00:01 | 50.03 | 50.03 | 7538.44 | 15109.56 | 31-OCT-19:00 |
| November | 0.00 | 0.00 | 01-NOV-00:01 | 51.42 | 51.42 | 8123.72 | 16242.35 | 30-NOV-19:20 |
| December | 0.00 | 0.00 | 01-DEC-00:02 | 49.76 | 60.05 | 8663.74 | 17148.60 | 29-DEC-20:00 |
| Annual Sum or Average | 0.00 | 8032.72 | ||||||
| Minimum of Months | 0.00 | 0.00 | 48.44 | 50.03 | 6946.41 | 13382.07 | ||
| Maximum of Months | 0.00 | 0.00 | 52.47 | 60.06 | 9160.45 | 17697.25 |
Report: ZoneTemperatureOscillationReportMonthly
For: DINING
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: ATTIC
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.146303E+11 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.132644E+11 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.147703E+11 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.162552E+11 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.217223E+11 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.327284E+11 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.423081E+11 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.405805E+11 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.291734E+11 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.214643E+11 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.145213E+11 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.145141E+11 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.275933E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.132644E+11 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.423081E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| AIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
| January | 0.00 | 0.00 | 0.00 | 0.653047E+10 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 | 0.589693E+10 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 | 0.659385E+10 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 | 0.711105E+10 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.00 | 0.939561E+10 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 | 0.167389E+11 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 | 0.240965E+11 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 | 0.221531E+11 | 0.00 | 0.00 |
| September | 0.00 | 0.00 | 0.00 | 0.143373E+11 | 0.00 | 0.00 |
| October | 0.00 | 0.00 | 0.00 | 0.933708E+10 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 | 0.640547E+10 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 | 0.653126E+10 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.135127E+12 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 0.589693E+10 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.00 | 0.240965E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.146303E+11 | 0.00 | 0.454094E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.132644E+11 | 0.00 | 0.458301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.145040E+11 | 0.863402E+09 | 0.225085E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.139223E+11 | 0.779222E+10 | 0.612036E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.143903E+11 | 0.250940E+11 | 0.282501E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.140270E+11 | 0.702614E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.146177E+11 | 0.109622E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.145805E+11 | 0.100738E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.140076E+11 | 0.556429E+11 | 2398485.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.144047E+11 | 0.247634E+11 | 0.142990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.140017E+11 | 0.163936E+10 | 0.151927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.145141E+11 | 0.00 | 0.319275E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.170865E+12 | 0.396417E+12 | 0.168703E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.132644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.146303E+11 | 0.109622E+12 | 0.458301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| AIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
| January | 0.652897E+10 | 4439555.74 | 0.247410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.589661E+10 | 931897.23 | 0.262058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.653159E+10 | 0.198487E+09 | 0.115035E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.633456E+10 | 0.256624E+10 | 0.239373E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.657534E+10 | 0.965603E+10 | 28848040.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.645776E+10 | 0.386973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.678861E+10 | 0.681014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.675962E+10 | 0.593776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.645125E+10 | 0.290438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.658681E+10 | 0.958596E+10 | 0.660102E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.633047E+10 | 0.229067E+09 | 0.707845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.652924E+10 | 5970125.81 | 0.163286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.777708E+11 | 0.217467E+12 | 0.889399E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.589661E+10 | 931897.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.678861E+10 | 0.681014E+11 | 0.262058E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.146303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.132644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.145040E+11 | 0.00 | 0.00 | 0.00 | 0.266238E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.139223E+11 | 0.00 | 0.00 | 0.00 | 0.233290E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.143903E+11 | 0.00 | 0.00 | 0.00 | 0.733201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.140270E+11 | 0.00 | 0.00 | 0.00 | 0.187014E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.146177E+11 | 0.00 | 0.00 | 0.00 | 0.276904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.145805E+11 | 0.00 | 0.00 | 0.00 | 0.260000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.140076E+11 | 0.00 | 0.00 | 0.00 | 0.151658E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.144047E+11 | 0.00 | 0.00 | 0.00 | 0.705956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.140017E+11 | 0.00 | 0.00 | 0.00 | 0.519648E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.145141E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.170865E+12 | 0.00 | 0.00 | 0.00 | 0.105068E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.132644E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.146303E+11 | 0.00 | 0.00 | 0.00 | 0.276904E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| AIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
| January | 0.652897E+10 | 0.00 | 0.00 | 0.00 | 1495093.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| February | 0.589661E+10 | 0.00 | 0.00 | 0.00 | 318696.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| March | 0.653159E+10 | 0.00 | 0.00 | 0.00 | 62260153.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| April | 0.633456E+10 | 0.00 | 0.00 | 0.00 | 0.776486E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| May | 0.657534E+10 | 0.00 | 0.00 | 0.00 | 0.282027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| June | 0.645776E+10 | 0.00 | 0.00 | 0.00 | 0.102811E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| July | 0.678861E+10 | 0.00 | 0.00 | 0.00 | 0.173079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| August | 0.675962E+10 | 0.00 | 0.00 | 0.00 | 0.153935E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| September | 0.645125E+10 | 0.00 | 0.00 | 0.00 | 0.788608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| October | 0.658681E+10 | 0.00 | 0.00 | 0.00 | 0.275027E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| November | 0.633047E+10 | 0.00 | 0.00 | 0.00 | 75000280.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| December | 0.652924E+10 | 0.00 | 0.00 | 0.00 | 2020069.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.777708E+11 | 0.00 | 0.00 | 0.00 | 0.573567E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Minimum of Months | 0.589661E+10 | 0.00 | 0.00 | 0.00 | 318696.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.678861E+10 | 0.00 | 0.00 | 0.00 | 0.173079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: DINING
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.682136E+11 | 0.00 | 0.00 | 89852.93 | 0.00 | 0.155759E+11 | 0.590348E+09 | 0.00 | 3.57 |
| February | 0.637853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171547E+11 | 0.00 | 0.00 | 3.60 |
| March | 0.573747E+11 | 0.00 | 0.00 | 8496002.81 | 0.00 | 0.507715E+10 | 0.600391E+10 | 0.00 | 3.56 |
| April | 0.314138E+11 | 10132831.68 | 0.00 | 39425304.35 | 0.00 | 0.962184E+09 | 0.163144E+11 | 0.00 | 3.57 |
| May | 0.888427E+10 | 0.548116E+09 | 0.00 | 89110021.73 | 0.00 | 2282025.26 | 0.257447E+11 | 0.00 | 3.60 |
| June | 0.102595E+10 | 0.104655E+11 | 0.00 | 59759467.13 | 32259251.68 | 0.00 | 0.709593E+10 | 0.00 | 3.67 |
| July | 0.254468E+09 | 0.328697E+11 | 0.00 | 8629166.25 | 0.221506E+09 | 0.00 | 0.203148E+09 | 0.00 | 3.71 |
| August | 0.499231E+09 | 0.253658E+11 | 0.00 | 45309850.09 | 0.178517E+09 | 0.00 | 0.266997E+10 | 0.00 | 3.69 |
| September | 0.239273E+10 | 0.567020E+10 | 0.00 | 81117538.58 | 16926614.51 | 0.00 | 0.140091E+11 | 0.00 | 3.64 |
| October | 0.141379E+11 | 0.374509E+09 | 0.00 | 74662597.03 | 0.00 | 5659430.42 | 0.240592E+11 | 0.00 | 3.59 |
| November | 0.458369E+11 | 0.00 | 0.00 | 13978096.18 | 0.00 | 0.335590E+10 | 0.120483E+11 | 0.00 | 3.58 |
| December | 0.669987E+11 | 0.00 | 0.00 | 101718.97 | 0.00 | 0.760594E+10 | 0.528523E+09 | 0.00 | 3.59 |
| Annual Sum or Average | 0.360818E+12 | 0.753039E+11 | 0.00 | 0.420680E+09 | 0.449209E+09 | 0.497397E+11 | 0.109268E+12 | 0.00 | 3.62 |
| Minimum of Months | 0.254468E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.56 |
| Maximum of Months | 0.682136E+11 | 0.328697E+11 | 0.00 | 89110021.73 | 0.221506E+09 | 0.171547E+11 | 0.257447E+11 | 0.00 | 3.71 |
Report: MechanicalVentilationLoadsMonthly
For: KITCHEN
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
| January | 0.710756E+11 | 0.00 | 0.00 | 111342.90 | 0.00 | 29877401.48 | 0.755337E+09 | 0.00 | 8.56 |
| February | 0.685877E+11 | 0.00 | 0.00 | 19986.37 | 0.00 | 43854087.61 | 13090109.23 | 0.00 | 8.60 |
| March | 0.557094E+11 | 0.00 | 0.00 | 3390744.74 | 0.00 | 5904191.57 | 0.427672E+10 | 0.00 | 8.59 |
| April | 0.314556E+11 | 0.00 | 0.00 | 27076973.68 | 0.00 | 0.00 | 0.159189E+11 | 0.00 | 8.72 |
| May | 0.836252E+10 | 37808386.51 | 0.00 | 74937647.77 | 0.00 | 0.00 | 0.320309E+11 | 0.00 | 8.88 |
| June | 0.275668E+09 | 0.384933E+10 | 0.00 | 77128919.43 | 0.00 | 0.00 | 0.146470E+11 | 0.00 | 9.14 |
| July | 0.00 | 0.171504E+11 | 0.00 | 21751989.34 | 0.00 | 0.00 | 0.175441E+10 | 0.00 | 9.35 |
| August | 4941606.06 | 0.135465E+11 | 0.00 | 63645135.74 | 0.00 | 0.00 | 0.796520E+10 | 0.00 | 9.28 |
| September | 0.126619E+10 | 0.178793E+10 | 0.00 | 84502149.05 | 0.00 | 0.00 | 0.220903E+11 | 0.00 | 9.06 |
| October | 0.142303E+11 | 636256.00 | 0.00 | 60134382.61 | 0.00 | 0.00 | 0.281845E+11 | 0.00 | 8.85 |
| November | 0.416062E+11 | 0.00 | 0.00 | 9882110.52 | 0.00 | 2967358.43 | 0.134514E+11 | 0.00 | 8.69 |
| December | 0.645265E+11 | 0.00 | 0.00 | 119075.04 | 0.00 | 2639821.79 | 0.264138E+09 | 0.00 | 8.64 |
| Annual Sum or Average | 0.357101E+12 | 0.363727E+11 | 0.00 | 0.422700E+09 | 0.00 | 85242860.87 | 0.141352E+12 | 0.00 | 8.86 |
| Minimum of Months | 0.00 | 0.00 | 0.00 | 19986.37 | 0.00 | 0.00 | 13090109.23 | 0.00 | 8.56 |
| Maximum of Months | 0.710756E+11 | 0.171504E+11 | 0.00 | 84502149.05 | 0.00 | 43854087.61 | 0.320309E+11 | 0.00 | 9.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2024-07-03 12:20:43
Custom Monthly Report| SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
| January | 0.274088E+11 | 0.143022E+11 | 0.234406E+12 | 0.121084E+11 | 0.287206E+11 |
| February | 0.485928E+11 | 0.140536E+11 | 0.223770E+12 | 0.115524E+11 | 0.287429E+11 |
| March | 0.927845E+11 | 0.135404E+11 | 0.195082E+12 | 0.115407E+11 | 0.230066E+11 |
| April | 0.101948E+12 | 0.105748E+11 | 0.152034E+12 | 0.993663E+10 | 0.298847E+11 |
| May | 0.136511E+12 | 0.921743E+10 | 0.125144E+12 | 0.853167E+10 | 0.627200E+11 |
| June | 0.135119E+12 | 0.370136E+10 | 0.284528E+11 | 0.400861E+10 | 0.156656E+12 |
| July | 0.129232E+12 | -504405372.8 | -0.620932E+11 | 0.171010E+10 | 0.242585E+12 |
| August | 0.122838E+12 | 0.624847E+09 | -0.286971E+11 | 0.302801E+10 | 0.221577E+12 |
| September | 0.820856E+11 | 0.425339E+10 | 0.647664E+11 | 0.504746E+10 | 0.125082E+12 |
| October | 0.773654E+11 | 0.744698E+10 | 0.135833E+12 | 0.928332E+10 | 0.607310E+11 |
| November | 0.335971E+11 | 0.106748E+11 | 0.179763E+12 | 0.114608E+11 | 0.196569E+11 |
| December | 0.203390E+11 | 0.125809E+11 | 0.211907E+12 | 0.113749E+11 | 0.224632E+11 |
| Annual Sum or Average | 0.100782E+13 | 0.100466E+12 | 0.146037E+13 | 0.995830E+11 | 0.102183E+13 |
| Minimum of Months | 0.203390E+11 | -504405372.8 | -0.620932E+11 | 0.171010E+10 | 0.196569E+11 |
| Maximum of Months | 0.136511E+12 | 0.143022E+11 | 0.234406E+12 | 0.121084E+11 | 0.242585E+12 |